AG2-627 Phase I Study Report

v1.00 released 2025-10-29 21:22

Woodstown-High Street 69 kV

24.0 MW Capacity / 40.0 MW Energy

Introduction

This Phase I System Impact Study Report (PH1) has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, sections 307 and 308 for New Service Requests (projects) in Transition Cycle 2. The Project Developer/Eligible Customer (developer) is South Harrison Solar, LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is Atlantic City Electric.

Preface

The Phase I System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle executive summary format and (ii) an individual project-level basis. The Phase I System Impact Study Results (for both the executive summary and individual reports) will be publicly available on PJM’s website. Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.3, PJM takes the following actions during the Phase I System Impact Study:
  1. PJM studies each New Service Request on a summer peak, winter peak and light load RTEP base case study. The case year is dependent on the new services cycle under study. PJM will identify the base case year to be used in the study of a specific cycle on its website.
  2. PJM will only perform load flow analysis during the Phase I System Impact Study.
  3. In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with Affected System impacts and provides each Affected System Operator with a list of New Service Request in the Cycle with potential impacts to their respective system.
  4. PJM will create both the short circuit and stability base cases to be used in the Phase II System Impact Study.
  5. The Phase I System Impact Study results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.
The Transmission Owner takes the following actions during the Phase I System Impact Study:
  1. Identify required Interconnection Facilities to accommodate the New Service Request.
  2. Identify required Network Upgrades to mitigate system violations from the Phase I System Impact Study.
  3. Provide planning-level preliminary estimates of Interconnection Facilities and Network Upgrades including scope, cost and elapsed time to complete the work.

Decision Point I Requirements

At the close of Phase I System Impact Study, PJM will initiate Decision Point I (DP1). During DP1, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.A.1. Additional information on these elements is available in PJM Manual 14H sections 4.4, 6, and 7.

Allowable project modifications at Decision Point I are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

General

The Project Developer has proposed a Solar generating facility located in the Atlantic City Electric zone — Gloucester County, New Jersey. The installed facilities will have a total capability of 40.0 MW with 24.0 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AG2-627
Project Name:
Woodstown-High Street 69 kV
Project Developer Name:
South Harrison Solar, LLC
State:
New Jersey
County:
Gloucester
Transmission Owner:
Atlantic City Electric
MFO:
40.0
MWE:
40.0
MWC:
24.0
Fuel Type:
Solar
Basecase Study Year:
2028

Physical Interconnection Facility Study

Physical Interconnection Facilities Study is not performed as part of the Phase I System Impact Study. Physical Interconnection Facilities Study will commence in the Phase II System Impact Study.

Point of Interconnection

AG2-627 will interconnect on the Atlantic City Electric transmission by tapping the Woodstown -  High Street 69 kV Line.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In the Phase I SIS, the costs shown are subject to change as a result of a facility study performed by the TO during the Phase II or Phase III System Impact Study.

Based on the Phase I SIS results, the AG2-627 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit are also shown below.

Cost Summary
DescriptionCost Allocated to AG2-627Cost Subject to Readiness*
Transmission Owner Interconnection Facilities (TOIF)$1,250,000$0
Other Scope$0$0
Option To Build Oversight$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$20,000,000$20,000,000
Network Upgrades$4,250,000$4,250,000
System Reliability Network Upgrades
Steady State Thermal & Voltage (SP & LL)$0$0
Transient Stability$0$0
Short Circuit$0$0
Transmission Owner Analysis
SubRegional$0$0
Distribution$0$0
Affected System Reinforcements
AFS - PJM Violatons$0$0
AFS - Non-PJM Violations$0$0
Total$25,500,000$24,250,000

* Contributes to calculation for Readiness Deposit #2 (RD2). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim deliverability study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 309 (Decision Point I) A.1.a.i and PJM Manual 14H, section 6.2, Readiness Deposit #2 (RD2) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point I (DP1), the Project Developer or Eligible Customer is required to submit Readiness Deposit #2, which is calculated as 10% of cost allocation for required Phase I Network Upgrades minus Readiness Deposit #1.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Readiness Deposit #2 Due for Project AG2-627

Readiness Deposit #2 has been calculated for the project based on the Phase I System Impact Study results and is shown in the table below. This Readiness Deposit #2 must be provided at Decision Point I through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit
Project ID10% of cost allocation for Phase I Network UpgradesReadiness Deposit #1 Received (RD1)Readiness Deposit #2 (RD2) for AG2-627 Project due at DP1
ABA - B
AG2-627$2,425,000$160,000$2,265,000

Note: Failure to provide an acceptable form of Readiness Deposit #2 by the end of Decision Point I will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Transmission Owner Interconnection Facilities
RTEP IDDescriptionTotal Cost ($USD)Allocated Cost ($USD)
(Pending)Provide OHT line to point of change in ownership from new substation. Install and terminate fiber from interconnection.$1,250,000 $1,250,000
Stand-Alone Network Upgrades
RTEP IDDescriptionTotal Cost ($USD)Allocated Cost ($USD)
(Pending)Build new 4-breaker ring bus substation by cutting into the existing 0765 69KV High Street – Woodstown line. New substation will have potential to upgrade to a 6-breaker ring bus.$20,000,000 $20,000,000
Network Upgrades
RTEP IDDescriptionTotal Cost ($USD)Allocated Cost ($USD)
(Pending)Extend existing Woodstown - High Street line to connect to terminals at new substation. Upgrade relaying at High Street and Woodstown substations. Install communications fiber from existing path.$4,250,000 $4,250,000

Based on the scope of work for the Interconnection Facilities, it is expected to take a range of 48 to 60 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

The schedule for any required Network Impact Reinforcements will be more clearly identified in the Phase II and Phase III System Impact Studies.

Transmission Owner Analysis

No impacts identified by Transmission Owner

 

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. AEC interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Meteorological Data Reporting Requirement
The solar generation facility shall provide the Transmission Provider with site-specific meteorological data including:
  • Temperature (degrees Fahrenheit)
  • Atmospheric Pressure (hectopascals)
  • Irradiance
  • Forced outage data
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AG2-627 was evaluated as a 40.0 MW (24.0 MW Capacity) injection in the AEC area.

AG2-627 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 40.0 MW (40.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AP/DVP
01DOUBS-8GOOSE CREEK 500.0 kV Ckt 1 line
AP_P7-1_PE-500-235105-004T_SRT-A
TowerAC100.81 %4357.0B4392.295.15
GD2AP/DVP
01DOUBS-8GOOSE CREEK 500.0 kV Ckt 1 line
DVP_P7-1: LN 203-9404_SRT-S
TowerAC100.81 %4357.0B4392.295.15
GD2DVP
AH1-727 TP-8BRAMBLETON 500.0 kV Ckt 1 line
DVP_P1-2: LN 9354_SRT-A
SingleAC111.34 %3256.16B3625.262.69
GD2DVP
AH1-727 TP-8BRAMBLETON 500.0 kV Ckt 1 line
DVP_P7-1: LN 9354-9363_SRT-A
TowerAC104.48 %4192.0C4379.613.91
GD2PECO/PSEG
CAMDEN-RICHRE29 230.0 kV Ckt 1 line
PECO_P4_CHICH045_SRT-A/* $ DELCO $ PECO_P4_CHICH045 $ STBK
BreakerAC108.47 %1336.0B1449.199.03
GD2PECO/PSEG
CAMDEN-RICHRE29 230.0 kV Ckt 1 line
PECO_P4_CHICH195_SRT-A/* $ DELCO $ PECO_P4_CHICH195 $ STBK
BreakerAC108.47 %1336.0B1449.129.03
GD2PECO/PSEG
CAMDEN-RICHRE29 230.0 kV Ckt 1 line
PECO_P4_CHICH435_SRT-A/* $ DELCO $ PECO_P4_CHICH435 $ STBK
BreakerAC108.46 %1336.0B1449.079.03
GD2PECO/PSEG
CAMDEN-RICHRE29 230.0 kV Ckt 1 line
PECO_P2-2_CHI230B1_SRT-A/* $ DELCO $ PECO_P2-2_CHI230B1 $ B
BusAC108.46 %1336.0B1449.019.03
GD2AP/PJM
CHAN-01DOUBS 500.0 kV Ckt 1 line
PJM_500_BG_P4_5_CNSTN_C_SRT-A
BreakerAC118.32 %4150.0B4910.188.76
GD2AP/PJM
CHAN-01DOUBS 500.0 kV Ckt 1 line
BGE_P4_GRACETON_51_SRT-A
BreakerAC118.28 %4150.0B4908.728.76
GD2AP/PJM
CHAN-01DOUBS 500.0 kV Ckt 1 line
PECO_P4_PEACH235_SRT-A/* $ CHESCO $ PECO_P4_PEACH235 $ STBK
BreakerAC118.27 %4150.0B4908.08.76
GD2AP/PJM
CHAN-01DOUBS 500.0 kV Ckt 1 line
PJM_500_BG_P4_5_CNSTN_B_SRT-A
BreakerAC117.98 %4150.0B4896.358.8
GD2AP/PJM
CHAN-01DOUBS 500.0 kV Ckt 1 line
PECO_P4_PEACH245_SRT-A/* $ CHESCO $ PECO_P4_PEACH245 $ STBK
BreakerAC108.91 %4150.0B4519.678.84
GD2AP/PJM
CHAN-01DOUBS 500.0 kV Ckt 1 line
PECO_P1-2_5012_SRT-A
SingleAC107.27 %4150.0B4451.536.11
GD2PJM
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
AP_P2-3_PE-500-019E_SRT-SL
BreakerAC140.95 %3098.0B4366.586.58
GD2PJM
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
AP_P1-2_PE-500-3835T_SRT-A
SingleAC129.83 %3098.0B4022.124.58
GD2PJM
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
AP_P2-3_PE-500-019B_SRT-A
BreakerAC122.82 %3098.0B3805.115.35
GD2PJM
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
PECO_P4_PEACH025_SRT-A/* $ CHESCO $ PECO_P4_PEACH025 $ STBK
BreakerAC115.21 %3098.0B3569.195.86
GD2PJM
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
PECO_P4_PEACH035_SRT-A/* $ CHESCO $ PECO_P4_PEACH035 $ STBK
BreakerAC112.95 %3098.0B3499.195.79
GD2PJM
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
BG_P7_CNSTN_NWEST2_SRT-A
TowerAC112.85 %3098.0B3496.214.93
GD2PJM
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
BG_P7_GRCTN_RAPHEL_SRT-A
TowerAC109.23 %3098.0B3383.934.93
GD2PJM
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
PJM_500_BG_P4_5_CNSTN_13_SRT-A
BreakerAC106.23 %3098.0B3290.974.76
GD2PJM
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
PECO_P1-2_5007_SRT-A/* $ CHESCO $ PECO_P1-2_5007 $ L
SingleAC106.13 %3098.0B3287.954.09
GD2PJM
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
AP_P2-2_PE-230-010_SRT-A
BusAC103.24 %3098.0B3198.54.7
GD2PJM
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
PJM_500_BG_P2_CNSTN_230-S_SRT-A
BusAC102.33 %3098.0B3170.184.65
GD2BGE/PECO
COOPER-GRACETON 230.0 kV Ckt 1 line
PECO_P4_PEACH235_SRT-A/* $ CHESCO $ PECO_P4_PEACH235 $ STBK
BreakerAC129.17 %578.0B746.612.32
GD2BGE/PECO
COOPER-GRACETON 230.0 kV Ckt 1 line
PJM_500_BG_P4_5_CNSTN_C_SRT-A
BreakerAC129.14 %578.0B746.452.32
GD2BGE/PECO
COOPER-GRACETON 230.0 kV Ckt 1 line
BGE_P4_GRACETON_51_SRT-A
BreakerAC129.12 %578.0B746.322.32
GD2BGE/PECO
COOPER-GRACETON 230.0 kV Ckt 1 line
PJM_500_BG_P4_5_CNSTN_B_SRT-A
BreakerAC128.12 %578.0B740.532.28
GD2BGE/PECO
COOPER-GRACETON 230.0 kV Ckt 1 line
PECO_P4_PEACH245_SRT-A/* $ CHESCO $ PECO_P4_PEACH245 $ STBK
BreakerAC122.82 %578.0B709.882.33
GD2BGE/PECO
COOPER-GRACETON 230.0 kV Ckt 1 line
PECO_P1-2_5012_SRT-A
SingleAC114.51 %578.0B661.851.62
GD2AP/PJM
KEYSTONE-01CABOT 500.0 kV Ckt 1 line
AP_P2-3_WP-500-DRT45_SRT-SL
BreakerAC108.06 %2844.0B3073.325.13
GD2AP/PJM
KEYSTONE-01SOBEND 500.0 kV Ckt 1 line
PN_P2-3_PN-500-DRT32_SRT-A
BreakerAC107.79 %2078.0B2239.814.83
GD2AP/PJM
KEYSTONE-01SOBEND 500.0 kV Ckt 1 line
PN_P2-3_PN-500-004-DRT-002_SRT-SL
BreakerAC107.79 %2078.0B2239.814.83
GD2PECO
N PHILA8-MASTER 230.0 kV Ckt 1 line
PECO_P4_CHICH045_SRT-A/* $ DELCO $ PECO_P4_CHICH045 $ STBK
BreakerAC109.92 %572.0B628.772.42
GD2PECO
N PHILA8-MASTER 230.0 kV Ckt 1 line
PECO_P4_CHICH195_SRT-A/* $ DELCO $ PECO_P4_CHICH195 $ STBK
BreakerAC109.91 %572.0B628.692.42
GD2PECO
N PHILA8-MASTER 230.0 kV Ckt 1 line
PECO_P4_CHICH435_SRT-A/* $ DELCO $ PECO_P4_CHICH435 $ STBK
BreakerAC109.91 %572.0B628.682.42
GD2PECO
N PHILA8-MASTER 230.0 kV Ckt 1 line
PECO_P2-2_CHI230B1_SRT-A/* $ DELCO $ PECO_P2-2_CHI230B1 $ B
BusAC109.9 %572.0B628.632.42
GD2PECO
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line
PJM_500_BG_P4_5_CNSTN_C_SRT-A
BreakerAC137.53 %578.0B794.942.32
GD2PECO
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line
PECO_P4_PEACH235_SRT-A/* $ CHESCO $ PECO_P4_PEACH235 $ STBK
BreakerAC137.41 %578.0B794.242.32
GD2PECO
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line
BGE_P4_GRACETON_51_SRT-A
BreakerAC137.36 %578.0B793.962.32
GD2PECO
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line
PJM_500_BG_P4_5_CNSTN_B_SRT-A
BreakerAC136.42 %578.0B788.522.28
GD2PECO
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line
PECO_P4_PEACH245_SRT-A/* $ CHESCO $ PECO_P4_PEACH245 $ STBK
BreakerAC130.99 %578.0B757.122.33
GD2PECO
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line
PECO_P1-2_5012_SRT-A
SingleAC122.76 %578.0B709.531.62
GD2PECO
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line
PJM_500_BG_P4_5_CNSTN_C_SRT-A
BreakerAC137.53 %578.0B794.942.32
GD2PECO
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line
PECO_P4_PEACH235_SRT-A/* $ CHESCO $ PECO_P4_PEACH235 $ STBK
BreakerAC137.41 %578.0B794.242.32
GD2PECO
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line
BGE_P4_GRACETON_51_SRT-A
BreakerAC137.36 %578.0B793.962.32
GD2PECO
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line
PJM_500_BG_P4_5_CNSTN_B_SRT-A
BreakerAC136.42 %578.0B788.522.28
GD2PECO
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line
PECO_P4_PEACH245_SRT-A/* $ CHESCO $ PECO_P4_PEACH245 $ STBK
BreakerAC130.99 %578.0B757.122.33
GD2PECO
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line
PECO_P1-2_5012_SRT-A
SingleAC122.76 %578.0B709.531.62
GD2PJM
PCHBTM1N-CHAN 500.0 kV Ckt 1 line
PJM_500_BG_P4_5_CNSTN_C_SRT-A
BreakerAC149.71 %3486.0B5219.010.9
GD2PJM
PCHBTM1N-CHAN 500.0 kV Ckt 1 line
BGE_P4_GRACETON_51_SRT-A
BreakerAC149.71 %3486.0B5218.9210.9
GD2PJM
PCHBTM1N-CHAN 500.0 kV Ckt 1 line
PECO_P4_PEACH235_SRT-A/* $ CHESCO $ PECO_P4_PEACH235 $ STBK
BreakerAC149.64 %3486.0B5216.4810.89
GD2PJM
PCHBTM1N-CHAN 500.0 kV Ckt 1 line
PJM_500_BG_P4_5_CNSTN_B_SRT-A
BreakerAC149.62 %3486.0B5215.6110.92
GD2PJM
PCHBTM1N-CHAN 500.0 kV Ckt 1 line
PECO_P1-2_5012_SRT-A
SingleAC135.02 %3486.0B4706.957.61
GD2PJM
PCHBTM1N-CHAN 500.0 kV Ckt 1 line
PECO_P4_PEACH245_SRT-A/* $ CHESCO $ PECO_P4_PEACH245 $ STBK
BreakerAC128.09 %3486.0B4465.1711.05
GD2PJM
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
AP_P2-3_PE-500-019E_SRT-SL
BreakerAC169.7 %3620.0B6143.2111.2
GD2PJM
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
AP_P2-3_PE-500-019B_SRT-A
BreakerAC162.94 %3620.0B5898.3210.53
GD2PJM
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
PECO_P4_PEACH025_SRT-A/* $ CHESCO $ PECO_P4_PEACH025 $ STBK
BreakerAC157.55 %3620.0B5703.411.2
GD2PJM
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
AP_P1-2_PE-500-3835T_SRT-A
SingleAC154.15 %3620.0B5580.177.81
GD2PJM
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
PECO_P4_PEACH035_SRT-A/* $ CHESCO $ PECO_P4_PEACH035 $ STBK
BreakerAC151.88 %3620.0B5498.0210.94
GD2PJM
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
PECO_P1-2_5007_SRT-A/* $ CHESCO $ PECO_P1-2_5007 $ L
SingleAC142.36 %3620.0B5153.547.82
GD2PJM
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
PECO_P4_PEACH095_SRT-A/* $ CHESCO $ PECO_P4_PEACH095 $ STBK
BreakerAC128.84 %3620.0B4663.838.75
GD2PJM
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
Base Case
SingleAC128.38 %2920.0A3748.65.64
GD2PJM
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
PECO_P2-2_NOTT230B_SRT-A/* $ CHESCO $ PECO_P2-2_NOTT230B $ B
BusAC121.38 %3620.0B4394.118.85
GD2PJM
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
PL_04_P71_001014_SRT-A
TowerAC118.7 %3620.0B4297.068.28
GD2PJM
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
PL_05_P71_000906_SRT-A
TowerAC117.69 %3620.0B4260.398.22
GD2PJM
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
PL_04_P22_102290_SRT-A
BusAC116.87 %3620.0B4230.718.17
GD2PJM
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line
BGE_P4_GRACETON_51_SRT-A
BreakerAC149.46 %2860.0B4274.427.89
GD2PJM
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line
PJM_500_BG_P4_5_CNSTN_C_SRT-A
BreakerAC149.46 %2860.0B4274.417.89
GD2PJM
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line
PJM_500_BG_P4_5_CNSTN_B_SRT-A
BreakerAC149.31 %2860.0B4270.167.9
GD2PJM
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line
PECO_P4_PEACH235_SRT-A/* $ CHESCO $ PECO_P4_PEACH235 $ STBK
BreakerAC149.28 %2860.0B4269.477.88
GD2PJM
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line
PECO_P1-2_5012_SRT-A
SingleAC133.85 %2860.0B3828.035.51
GD2PJM
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line
PECO_P4_PEACH245_SRT-A/* $ CHESCO $ PECO_P4_PEACH245 $ STBK
BreakerAC115.45 %2860.0B3301.838.11
GD2PJM
PCHBTM2S-PCHBTM1S 500.0 kV Ckt Z1 line
PECO_P4_PEACH255_SRT-A/* $ CHESCO $ PECO_P4_PEACH255 $ STBK
BreakerAC135.13 %2860.0B3864.848.92
GD2PJM
PCHBTM2S-PCHBTM1S 500.0 kV Ckt Z2 line
PECO_P4_PEACH235_SRT-A/* $ CHESCO $ PECO_P4_PEACH235 $ STBK
BreakerAC106.9 %2860.0B3057.458.15
GD2PECO
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line
PJM_500_BG_P4_5_CNSTN_C_SRT-A
BreakerAC134.98 %578.0B780.212.32
GD2PECO
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line
PECO_P4_PEACH235_SRT-A/* $ CHESCO $ PECO_P4_PEACH235 $ STBK
BreakerAC134.89 %578.0B779.652.32
GD2PECO
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line
BGE_P4_GRACETON_51_SRT-A
BreakerAC134.84 %578.0B779.372.32
GD2PECO
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line
PJM_500_BG_P4_5_CNSTN_B_SRT-A
BreakerAC133.89 %578.0B773.92.28
GD2PECO
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line
PECO_P4_PEACH245_SRT-A/* $ CHESCO $ PECO_P4_PEACH245 $ STBK
BreakerAC128.45 %578.0B742.452.33
GD2PECO
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line
PECO_P1-2_5012_SRT-A
SingleAC120.24 %578.0B694.961.62
GD2PECO
RICHMOND35-WANEETA3 230.0 kV Ckt 1 line
PECO_P4_CHICH045_SRT-A/* $ DELCO $ PECO_P4_CHICH045 $ STBK
BreakerAC118.19 %1180.0B1394.628.27
GD2PECO
RICHMOND35-WANEETA3 230.0 kV Ckt 1 line
PECO_P4_CHICH195_SRT-A/* $ DELCO $ PECO_P4_CHICH195 $ STBK
BreakerAC118.18 %1180.0B1394.548.27
GD2PECO
RICHMOND35-WANEETA3 230.0 kV Ckt 1 line
PECO_P4_CHICH435_SRT-A/* $ DELCO $ PECO_P4_CHICH435 $ STBK
BreakerAC118.18 %1180.0B1394.58.27
GD2PECO
RICHMOND35-WANEETA3 230.0 kV Ckt 1 line
PECO_P2-2_CHI230B1_SRT-A/* $ DELCO $ PECO_P2-2_CHI230B1 $ B
BusAC118.17 %1180.0B1394.448.27
GD2PECO
RICHMOND35-WANEETA3 230.0 kV Ckt 1 line
PECO_P4_PEACH215_SRT-A/* $ CHESCO $ PECO_P4_PEACH215 $ STBK
BreakerAC104.9 %1180.0B1237.878.9
GD2PECO
RICHMOND35-WANEETA3 230.0 kV Ckt 1 line
PECO_P4_PEACH205_SRT-A/* $ CHESCO $ PECO_P4_PEACH205 $ STBK
BreakerAC102.28 %1180.0B1206.948.9
GD2PECO
RICHRE29-RICHMOND29 230.0 kV Ckt 1 line
PECO_P4_CHICH045_SRT-A/* $ DELCO $ PECO_P4_CHICH045 $ STBK
BreakerAC108.47 %1336.0B1449.199.03
GD2PECO
RICHRE29-RICHMOND29 230.0 kV Ckt 1 line
PECO_P4_CHICH195_SRT-A/* $ DELCO $ PECO_P4_CHICH195 $ STBK
BreakerAC108.47 %1336.0B1449.129.03
GD2PECO
RICHRE29-RICHMOND29 230.0 kV Ckt 1 line
PECO_P4_CHICH435_SRT-A/* $ DELCO $ PECO_P4_CHICH435 $ STBK
BreakerAC108.46 %1336.0B1449.079.03
GD2PECO
RICHRE29-RICHMOND29 230.0 kV Ckt 1 line
PECO_P2-2_CHI230B1_SRT-A/* $ DELCO $ PECO_P2-2_CHI230B1 $ B
BusAC108.46 %1336.0B1449.019.03
GD2PJM
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line
PJM500_PS_P2-3_NFRD5_9-10_SRT-A
BreakerAC105.85 %2905.0B3075.0611.04
GD2PJM
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line
PECO_P4_LINWO125_SRT-A/* $ DELCO $ PECO_P4_LINWO125 $ STBK
BreakerAC105.75 %2905.0B3072.159.18
GD2PJM
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line
PECO_P4_CHICH435_SRT-A/* $ DELCO $ PECO_P4_CHICH435 $ STBK
BreakerAC105.75 %2905.0B3071.9810.48
GD2PJM
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line
PECO_P4_CHICH195_SRT-A/* $ DELCO $ PECO_P4_CHICH195 $ STBK
BreakerAC105.75 %2905.0B3071.9610.48
GD2PJM
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line
PECO_P4_CHICH045_SRT-A/* $ DELCO $ PECO_P4_CHICH045 $ STBK
BreakerAC105.75 %2905.0B3071.9110.48
GD2PJM
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line
DPL_P7_1_DBL_6NC_SRT-A
TowerAC105.74 %2905.0B3071.729.18
GD2PJM
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line
PECO_P2-2_CHI230B1_SRT-A/* $ DELCO $ PECO_P2-2_CHI230B1 $ B
BusAC105.74 %2905.0B3071.6810.48
GD2PJM
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line
DPL_P7_1_DBL_5NC_SRT-A
TowerAC101.95 %2905.0B2961.689.31
GD2PECO
WANEETA2-N PHILA 230.0 kV Ckt 1 line
PECO_P4_CHICH045_SRT-A/* $ DELCO $ PECO_P4_CHICH045 $ STBK
BreakerAC104.0 %621.0B645.834.11
GD2PECO
WANEETA2-N PHILA 230.0 kV Ckt 1 line
PECO_P4_CHICH195_SRT-A/* $ DELCO $ PECO_P4_CHICH195 $ STBK
BreakerAC103.99 %621.0B645.764.11
GD2PECO
WANEETA2-N PHILA 230.0 kV Ckt 1 line
PECO_P4_CHICH435_SRT-A/* $ DELCO $ PECO_P4_CHICH435 $ STBK
BreakerAC103.99 %621.0B645.764.11
GD2PECO
WANEETA2-N PHILA 230.0 kV Ckt 1 line
PECO_P2-2_CHI230B1_SRT-A/* $ DELCO $ PECO_P2-2_CHI230B1 $ B
BusAC103.98 %621.0B645.694.11
GD2PECO
WANEETA3-WANEETA2 230.0 kV Ckt Z line
PECO_P4_CHICH045_SRT-A/* $ DELCO $ PECO_P4_CHICH045 $ STBK
BreakerAC108.91 %1008.0B1097.836.24
GD2PECO
WANEETA3-WANEETA2 230.0 kV Ckt Z line
PECO_P4_CHICH195_SRT-A/* $ DELCO $ PECO_P4_CHICH195 $ STBK
BreakerAC108.91 %1008.0B1097.776.24
GD2PECO
WANEETA3-WANEETA2 230.0 kV Ckt Z line
PECO_P4_CHICH435_SRT-A/* $ DELCO $ PECO_P4_CHICH435 $ STBK
BreakerAC108.9 %1008.0B1097.746.24
GD2PECO
WANEETA3-WANEETA2 230.0 kV Ckt Z line
PECO_P2-2_CHI230B1_SRT-A/* $ DELCO $ PECO_P2-2_CHI230B1 $ B
BusAC108.9 %1008.0B1097.686.24

Details for 01DOUBS-8GOOSE CREEK 500.0 kV Ckt 1 line l/o AP_P7-1_PE-500-235105-004T_SRT-A


Base Case Flowgate

Area:AP/DVP
Facility Description:
01DOUBS-8GOOSE CREEK 500.0 kV Ckt 1 line
Contingency Name:
AP_P7-1_PE-500-235105-004T_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:100.81 %
Rating:4357.0 MVA
Rating Type:B
MVA to Mitigate:4392.29
MW Contribution:5.15
Bus #Bus NameTypeMW Contribution
224054DICKHCT1
50/50
1.481
966141AG1-483 GEN
50/50
92.09
23757701ROUTE 16
50/50
2.738
200035PCHBTM 3
50/50
11.704
200201DELTA2 CT2
50/50
1.967
200034PCHBTM 2
50/50
11.456
200205Y1-065-CTG2
50/50
2.317
23777801MSM_W1-116
Solar/Wind Harmer
0.963
237034AC2-136 C
Solar/Wind Harmer
0.606
237025AB1-124 C
Solar/Wind Harmer
1.349
237006AB1-125 GEN
Solar/Wind Harmer
1.012
23777901MDS_W4-102
Solar/Wind Harmer
1.305
235020AA1-095 C
Solar/Wind Harmer
0.215
237001AB1-127_GEN
Solar/Wind Harmer
0.686
237002AB1-128_GEN
Solar/Wind Harmer
0.683
235063AE1-101 C2
Solar/Wind Harmer
2.513
203982AD2-062_GEN
Solar/Wind Harmer
11.666
20464927ORTAN CT
Adder
2.907
205916AD1-020 GEN
Solar/Wind Harmer
2.513
20390526W1-045 C
Solar/Wind Harmer
0.502
233987AB2-037 GEN
Solar/Wind Harmer
8.381
233901CHERRYDALE C
Solar/Wind Harmer
0.829
232408W1-005 C
Solar/Wind Harmer
0.737
232410W1-006 C
Solar/Wind Harmer
0.737
972069AH1-584 GEN
Solar/Wind Harmer
6.591
972071AH1-585 GEN
Solar/Wind Harmer
6.591
232918OH NUG7
Adder
6.457
971747AH1-380 GEN
Solar/Wind Harmer
2.636
232905CHERITON_25
Adder
1.806
232926CRISFLD1
Adder
1.444
233946AB2-136 GEN
Solar/Wind Harmer
2.937
234036AF2-325 C
Solar/Wind Harmer
0.675
970545AG2-347 GEN
Solar/Wind Harmer
48.15
231940T-011
Adder
0.549
234041AC1-190 GEN
Solar/Wind Harmer
6.59
971149AH1-027 GEN
Solar/Wind Harmer
2.49
233939AC1-091 C
Solar/Wind Harmer
0.646
233970AC1-092 C
Solar/Wind Harmer
0.646
232899W1-062
Adder
7.075
233984AB2-036 GEN
Solar/Wind Harmer
9.159
232424Y1-079 C
Solar/Wind Harmer
0.414
234014AF1-036_GEN
Solar/Wind Harmer
1.99
231131BLOOM ENRGY
Adder
3.202
233944AB2-135 GEN
Solar/Wind Harmer
3.851
233933AB2-153 GEN
Solar/Wind Harmer
0.827
232416X2-083
Adder
0.331
213587EDDYSTN3
Adder
53.693
213589EDDYSTN4
Adder
53.695
228251CARLLS#4
Adder
0.424
230433AD2-135 GEN
Solar/Wind Harmer
0.068
228307PCLP GT
Adder
8.128
230422AE1-104_GEN1
Solar/Wind Harmer
22.636
230425AE1-104_GEN2
Solar/Wind Harmer
22.636
228304LOGAN
Adder
16.264
972233AH1-701 GEN
Adder
2.82
230407AD2-065 C
Solar/Wind Harmer
0.088
219921AF1-264
Solar/Wind Harmer
0.097
213815MOSER1-3
Adder
2.383
213815MOSER1-3
Adder
2.383
20464827MOUNT CT
Adder
2.842
20464827MOUNT CT
Adder
2.758
219615MILLCREEK C
Solar/Wind Harmer
0.16
213535CROYDN11
Adder
6.849
20716428NHV_W2-082
Solar/Wind Harmer
1.188
207500AE2-000G1
Solar/Wind Harmer
21.039
207497AE2-000G2
Solar/Wind Harmer
21.039
207507AE2-000G3
Solar/Wind Harmer
21.039
20636128O CRK C2
Adder
4.304
963401AG1-189 GEN
Solar/Wind Harmer
0.769
963391AG1-188 GEN
Solar/Wind Harmer
1.282
219114HARTZY_C
Solar/Wind Harmer
0.559
20714928UPF_X1-085
Solar/Wind Harmer
0.272
20628028LAKEHURS
Adder
0.637
219817TRENTONSOL C
Solar/Wind Harmer
0.742
20641628MLH_W1-032
Solar/Wind Harmer
0.197
20720628TIN_W1-124
Solar/Wind Harmer
0.671
20716928W4-060COL
Solar/Wind Harmer
0.481
924131AB2-057 GEN
Solar/Wind Harmer
0.698
218440SUMMTASSOC C
Solar/Wind Harmer
0.087
23776901DAM 5 HY
50/50
0.011
966461AG1-515 GEN
50/50
0.72
23732901CHBRG_I12
50/50
4.144
200202DELTA2 ST
50/50
3.337
200195DELTA ST
50/50
1.698
23776801DAM 4 HY
50/50
0.012
970429AG2-279 GEN
Solar/Wind Harmer
3.213
237085AD2-009_GEN
Solar/Wind Harmer
2.184
238208AF1-136 C
Solar/Wind Harmer
0.656
959381AF2-229 GEN
Solar/Wind Harmer
0.975
20087026C_T85_W218
Adder
0.813
20464627HAM CT
Adder
2.899
233923SMA
Solar/Wind Harmer
3.418
232912OH NUG1
Adder
6.5
232913OH NUG2
Adder
6.413
234033AF1-007_GEN
Solar/Wind Harmer
17.206
233990AG1-397 GEN
Solar/Wind Harmer
0.041
232432Z2-076 GEN
Solar/Wind Harmer
0.097
232904IR4
Adder
59.494
232920IR10
Adder
2.325
233955AB2-172 GEN
Solar/Wind Harmer
3.68
233973AC2-185 C
Solar/Wind Harmer
2.658
232813VAUGHN
Adder
0.433
233968AD2-076_GEN
Solar/Wind Harmer
4.876
970597AG2-380 GEN
Solar/Wind Harmer
3.062
232436AB1-176 C
Solar/Wind Harmer
0.169
231906DC3 NUG
Adder
10.285
231902DC CT7
Adder
8.222
231907DC10
Adder
2.568
971983AH1-536 GEN
Solar/Wind Harmer
5.501
233935AB2-179 C
Solar/Wind Harmer
1.836
231919CHRIST1
Adder
3.228
231920CHRIST2
Adder
3.157
970453AG2-297 GEN
Solar/Wind Harmer
1.854
228260V4-054C
Solar/Wind Harmer
0.69
228309CCLP NUG
Adder
17.377
228309CCLP NUG
Adder
16.529
972141AH1-641 GEN
Solar/Wind Harmer
1.933
964001AG1-254 GEN
Solar/Wind Harmer
1.367
971011AG2-627 GEN
Solar/Wind Harmer
5.152
971535AH1-265 GEN
Solar/Wind Harmer
2.86
227927V4-067C
Solar/Wind Harmer
0.133
228754AB1-001 C
Solar/Wind Harmer
0.094
213942SCHUYLKILL
Adder
2.394
213942SCHUYLKILL
Adder
1.831
213957STHWK3-4
Adder
1.83
213957STHWK3-4
Adder
1.83
219137THOSOLAR C
Solar/Wind Harmer
0.812
213561DLWR9-10
Adder
2.387
213561DLWR9-10
Adder
1.826
219914AD2-027 C
Solar/Wind Harmer
0.403
219272CLEANLIGHT C
Solar/Wind Harmer
0.122
219688LUMSOLAR_S C
Solar/Wind Harmer
0.136
205943AE1-185 GEN
Solar/Wind Harmer
0.715
219607WPEMNERT C
Solar/Wind Harmer
0.281
219224BRL12CT4
Adder
5.975
205956AE1-196_GEN
Solar/Wind Harmer
0.713
205932AD2-116_GEN
Solar/Wind Harmer
0.713
960921AF2-383 GEN
Solar/Wind Harmer
0.239
20465027TOLNA CT
Adder
2.933
960921AF2-383 GEN
Solar/Wind Harmer
1.836
214067T20SOLAR
Solar/Wind Harmer
0.169
213611FALLS1-3
Adder
2.369
213611FALLS1-3
Adder
2.369
205951AE1-129_GEN
Solar/Wind Harmer
9.964
20717128DIX_Z2-102
Solar/Wind Harmer
0.882
20715728PEM_W1-119
Solar/Wind Harmer
0.357
20715828PEM_W1-120
Solar/Wind Harmer
0.357
970025AG2-016 GEN
Solar/Wind Harmer
1.894
971189AH1-054 GEN
Solar/Wind Harmer
0.789
207459AE1-142 C O1
Solar/Wind Harmer
0.707
219620RIDERU C
Solar/Wind Harmer
0.038
20714328BYD_X4-031
Solar/Wind Harmer
0.19
20714428HOW_X1-037
Solar/Wind Harmer
0.831
203975AE1-071-GEN
Solar/Wind Harmer
3.518
971521AH1-258 GEN
Solar/Wind Harmer
1.826
20720428HOL_W1-112
Solar/Wind Harmer
0.234
218455CINNBAY_CGEN
Adder
1.233
23572301GUILF1
50/50
0.484
200192DELTA CT1
50/50
1.099
200194DELTA CT3
50/50
1.099
200204Y1-065-CTG1
50/50
2.317
200054ROCKSP 3
50/50
1.478
23779801AA1-109
Solar/Wind Harmer
0.427
238141AE2-333 GEN1
Solar/Wind Harmer
8.044
237080AD1-060 GEN
Solar/Wind Harmer
0.51
237038AE2-054 C
Solar/Wind Harmer
0.928
970651AG2-423 GEN
Solar/Wind Harmer
12.228
235062AE1-101 C1
Solar/Wind Harmer
2.513
205975AE2-345_GEN
Solar/Wind Harmer
9.433
966131AG1-482 GEN
Solar/Wind Harmer
0.118
233998TM1NIN_3.36
Solar/Wind Harmer
0.932
232404W1-003 C
Solar/Wind Harmer
0.737
232428Y3-058 C
Solar/Wind Harmer
0.614
232917OH NUG6
Adder
6.471
232915OH NUG4
Adder
6.457
232919VN10
Adder
2.066
971195AH1-057 GEN
Solar/Wind Harmer
0.806
232426Y1-080 FULL
Solar/Wind Harmer
0.141
232434Z2-077 GEN
Solar/Wind Harmer
0.184
233964AF2-378 GEN
Solar/Wind Harmer
0.094
970277AG2-181 GEN
Solar/Wind Harmer
3.691
965821AG1-450 GEN
Solar/Wind Harmer
3.832
972177AH1-672 GEN
Solar/Wind Harmer
9.885
232901NORTHST
Adder
6.123
233972AC1-094 C
Solar/Wind Harmer
0.488
233954AC2-188 GEN
Solar/Wind Harmer
0.828
233950AC2-186 GEN
Solar/Wind Harmer
0.414
232900DEMECSMY
Adder
6.786
232910NRG_G1
Adder
6.35
234012AE2-112_GEN
Solar/Wind Harmer
1.692
232422X3-066 FULL
Solar/Wind Harmer
0.184
233930AB2-032 GEN
Solar/Wind Harmer
0.613
233915AB1-141 GEN
Solar/Wind Harmer
0.729
231918WEST 1
Adder
2.454
231917EM10
Adder
1.72
228206SHRMN CT
Adder
11.139
213497CHSTR7-9
Adder
1.837
213497CHSTR7-9
Adder
1.837
945431AF1-208 GEN
Solar/Wind Harmer
5.801
228732V1-021 C
Adder
0.127
970997AG2-616 GEN
Solar/Wind Harmer
6.444
228351V2-046C
Solar/Wind Harmer
1.354
230511AF1-262
Solar/Wind Harmer
0.123
228728W1-130C
Solar/Wind Harmer
0.446
230434AG1-499 GEN
Solar/Wind Harmer
0.39
213958STHWK5-6
Adder
1.83
219258KINSLEYDEP C
Solar/Wind Harmer
0.217
219904AC1-010 C
Solar/Wind Harmer
0.254
213560DLW11-12
Adder
1.826
218660EHAMPSOLAR C
Solar/Wind Harmer
0.117
219287REEVESEAST C
Solar/Wind Harmer
0.901
219686LUMSOLAR_N C
Solar/Wind Harmer
0.136
219907AC1-030 C
Solar/Wind Harmer
0.093
219304NAMERICA C
Solar/Wind Harmer
0.208
219222BRL12CT2
Adder
5.975
20465027TOLNA CT
Adder
2.821
214194N WALES4
Adder
0.573
205967AE2-211_GEN
Solar/Wind Harmer
7.222
213611FALLS1-3
Adder
2.369
20720728JCB_W1-129
Solar/Wind Harmer
0.199
207522AF2-254 C
Solar/Wind Harmer
0.959
207487AE2-000G4
Solar/Wind Harmer
21.039
207445AB1-138_GEN
Solar/Wind Harmer
0.388
20628028LAKEHURS
Adder
1.26
963711AG1-223 GEN
Solar/Wind Harmer
0.993
20714828MDF_W3-079
Solar/Wind Harmer
0.206
219680HOPEWELLV C1
Solar/Wind Harmer
0.051
207454AA2-184 E
Solar/Wind Harmer
0.673
20715228NPK_W1-113
Solar/Wind Harmer
0.29
20742028HF_AC1-207
Solar/Wind Harmer
0.529
217197RE CRAN C
Solar/Wind Harmer
0.363
20635828PARLN1&2
Adder
5.02
20635028RRCT1&2
Adder
7.881
20635128RRCT3&4
Adder
7.608
218428ETC SOLAR C
Solar/Wind Harmer
0.024
217213AMBOY SO C
Solar/Wind Harmer
0.086
207528AF2-192 GEN
Solar/Wind Harmer
0.379
20673628F1S_V4-069
Solar/Wind Harmer
0.123
20675428EAM_W2-061
Solar/Wind Harmer
0.129
972275AH1-722 GEN
Adder
21.545
20676428JCR_X2-075
Solar/Wind Harmer
0.234
218449LINSOLAR C
Solar/Wind Harmer
0.688
217209CENTRL HS C
Solar/Wind Harmer
0.031
217083KRNY_132
Adder
6.383
217121ECCF
Adder
0.298
217208PARK ELE C
Solar/Wind Harmer
0.017
20465527S.RDG CT
Adder
2.087
20467927PC_Q59Y356
Adder
0.637
205941AD2-115 GEN
Solar/Wind Harmer
0.69
20674328GAR_V4-001
Solar/Wind Harmer
0.077
207439AE1-081 C O1
Solar/Wind Harmer
0.042
209008PAXT IPP
Adder
1.608
971519AH1-257 GEN
Solar/Wind Harmer
1.777
20675828AU_W4-064
Solar/Wind Harmer
0.121
20635928PARLN3&4
Adder
5.02
20675528CPH_W2-050
Solar/Wind Harmer
0.319
218526CNTRALGAS2 C
Solar/Wind Harmer
0.252
218524CNTRALGAS1 C
Solar/Wind Harmer
0.252
208862AG1-362 C
Solar/Wind Harmer
0.619
218404KENILWRTH C
Adder
0.895
217167KRNY_14
Adder
6.383
217086KRNY_131
Adder
6.329
217147KRNY_1212
Adder
6.071
217147KRNY_1212
Adder
5.963
217146KRNY_1234
Adder
5.949
217146KRNY_1234
Adder
5.909
20486527WR_V4-052
Adder
0.813
966261AG1-495 GEN
Solar/Wind Harmer
1.25
207530AG1-191 GEN
Solar/Wind Harmer
0.962
20676328BVR_Y1-020
Solar/Wind Harmer
0.231
207511W3-106 GEN
Solar/Wind Harmer
0.458
20674828DL_W4-046
Solar/Wind Harmer
0.454
20675928HOL_W4-097
Solar/Wind Harmer
0.093
207484AF2-139 C O1
Solar/Wind Harmer
0.358
971009AG2-626 GEN
Solar/Wind Harmer
1.154
207408W3-077 C
Solar/Wind Harmer
0.358
20675728RH_W2-091
Solar/Wind Harmer
0.242
20675128HRM_W1-127
Solar/Wind Harmer
0.121
20462827N BANGR8
Adder
0.507
966421AG1-511 GEN
Solar/Wind Harmer
6.061
209030FRFA O01
Adder
0.212
209116AE2-175 GEN
Solar/Wind Harmer
2.913
209026WIENIPP4
Adder
3.76
961261AF2-417 GEN
Solar/Wind Harmer
0.703
209045AE2-271 GEN
Solar/Wind Harmer
11.631
959431AF2-234 GEN
Solar/Wind Harmer
1.374
964051AG1-259 GEN
Solar/Wind Harmer
0.921
964061AG1-260 GEN
Solar/Wind Harmer
0.921
959421AF2-233 GEN
Solar/Wind Harmer
0.687
220910PERRYG34
Adder
12.33
220909PERRYG12
Adder
6.165
20390726Y2-042
Adder
2.167
20334726NME_Y1-047
Adder
2.029
3138216PACIFIC
Solar/Wind Helper
0.122
316411AF1-147_GEN1
Solar/Wind Helper
2.387
316415AF1-147_GEN2
Solar/Wind Helper
2.387
316164AC1-076 GEN
Solar/Wind Helper
2.474
3141426STAFORD
Solar/Wind Helper
0.113
316223AC1-118
Solar/Wind Helper
0.69
3141813NORNECK
Solar/Wind Helper
0.442
3141783LANCAST
Solar/Wind Helper
0.26
3141783LANCAST
Solar/Wind Helper
0.173
316312AB1-027
Solar/Wind Helper
0.823
3138133OCRAN
Solar/Wind Helper
0.13
3141913WHIT STONE
Solar/Wind Helper
0.432
316059AD1-063 C
Solar/Wind Helper
0.433
957601AF2-054 GEN
Solar/Wind Helper
0.576
3141873WAN 176
Solar/Wind Helper
0.086
315662AE1-191 GEN
Solar/Wind Helper
2.309
315666AE1-190 GEN
Solar/Wind Helper
0.577
3143873LANEXA
Solar/Wind Helper
0.258
316233AE1-074 FULL
Solar/Wind Helper
0.655
957831AF2-077 GEN
Solar/Wind Helper
0.571
316132AB2-190 GEN1
Solar/Wind Helper
2.394
316369SG1_INVT
Solar/Wind Helper
2.007
3143316POE
Solar/Wind Helper
1.632
316349AD2-085 GEN
Solar/Wind Helper
1.857
319010AE1-072 C
Solar/Wind Helper
4.629
316305AF2-043 C
Solar/Wind Helper
0.544
313526AB2-022
Solar/Wind Helper
0.613
3146486SUNBURY
Solar/Wind Helper
0.402
3146486SUNBURY
Solar/Wind Helper
0.402
316321Z2-027
Solar/Wind Helper
0.611
3145176PASQUOTANK
Solar/Wind Helper
0.249
316315AB2-025 C
Solar/Wind Helper
0.604
315611Z1-036_GEN2
Solar/Wind Helper
2.166
3130156CHOWAN
Solar/Wind Helper
0.39
3130156CHOWAN
Solar/Wind Helper
0.39
315816AE2-034 GEN
Solar/Wind Helper
1.755
3130546PLYMOUTH
Solar/Wind Helper
0.379
315732AD1-074 GEN1
Solar/Wind Helper
4.323
315733AD1-074 GEN2
Solar/Wind Helper
4.323
315735AD1-075 GEN1
Solar/Wind Helper
2.161
3146206CASHIE
Solar/Wind Helper
0.376
3145893MURPHYS
Solar/Wind Helper
1.013
3145893MURPHYS
Solar/Wind Helper
0.375
3145513AHOSKIE
Solar/Wind Helper
0.166
961941AG1-037 GEN
Solar/Wind Helper
0.125
3145513AHOSKIE
Solar/Wind Helper
0.371
946281AF1-292 GEN
Solar/Wind Helper
0.372
3146043SEABORD
Solar/Wind Helper
0.37
3145683EARLEYS
Solar/Wind Helper
0.739
3145683EARLEYS
Solar/Wind Helper
0.37
3145683EARLEYS
Solar/Wind Helper
0.37
315607AA1-063A GEN
Solar/Wind Helper
2.105
316087AB2-174 GEN
Solar/Wind Helper
2.573
3137643SOCKMAN
Solar/Wind Helper
1.459
3145796HORNRTN
Solar/Wind Helper
1.154
3145796HORNRTN
Solar/Wind Helper
0.144
3146033SCOT NK
Solar/Wind Helper
1.436
3144303KENBRDG
Solar/Wind Helper
0.283
316239AB2-077_GEN
Solar/Wind Helper
0.469
316238AB2-078_GEN
Solar/Wind Helper
0.469
316005AA1-067
Solar/Wind Helper
0.398
3145746EVERETS
Solar/Wind Helper
1.387
3145746EVERETS
Solar/Wind Helper
0.348
3145746EVERETS
Solar/Wind Helper
0.348
3145746EVERETS
Solar/Wind Helper
0.348
3138266HYDRAULIC
Solar/Wind Helper
0.016
3138266HYDRAULIC
Solar/Wind Helper
0.01
316420AA1-050 GEN
Solar/Wind Helper
1.963
3145573BETHELC
Solar/Wind Helper
0.341
3145573BETHELC
Solar/Wind Helper
0.341
316118AC1-105 GEN
Solar/Wind Helper
1.283
3147173SINAI
Solar/Wind Helper
0.325
3147243WELCO
Solar/Wind Helper
0.203
270494AE1-108_GEN
Solar/Wind Helper
4.33
3148133STUARTS
Solar/Wind Helper
0.185
3148013FISHERV
Solar/Wind Helper
0.177
316123AC1-075 GEN
Solar/Wind Helper
1.763
270455AD2-022 GEN
Solar/Wind Helper
1.618
270457AD2-023 GEN
Solar/Wind Helper
1.066
3148463FAIRFLD
Solar/Wind Helper
0.277
238152AF2-075_GEN
Solar/Wind Helper
0.566
20673828FLE_V3-070
Solar/Wind Harmer
0.313
207442AE1-156 GEN
Solar/Wind Harmer
0.51
20676128MHD_W3-029
Solar/Wind Harmer
0.327
218418LINDEN_G5
Adder
11.719
218419LINDEN_G6
Adder
11.719
972260AH1-715 GEN1
Adder
9.384
219036LINDEN_G7
Adder
11.438
219035LINDEN_G8
Adder
11.275
972261AH1-715 GEN2
Adder
10.949
20671828STAW2-080
Solar/Wind Harmer
0.072
217081WEATEXAS C
Solar/Wind Harmer
0.059
20674528F3S_W2-016
Solar/Wind Harmer
0.973
217202FBANKSOLAR C
Solar/Wind Harmer
0.05
217201HACKENSOLA C
Solar/Wind Harmer
0.05
972237AH1-703 GEN
Adder
6.947
217206BARNGR HS C
Solar/Wind Harmer
0.021
217086KRNY_131
Adder
6.396
217083KRNY_132
Adder
6.342
20465527S.RDG CT
Adder
2.019
217204WCALDSOLAR C
Solar/Wind Harmer
0.05
20478527GLRA_Q45
Adder
0.257
20676228FRD_X1-012
Solar/Wind Harmer
0.413
207471AF2-354 C
Solar/Wind Harmer
0.36
20674928WA_W3-044
Solar/Wind Harmer
0.339
964851AG1-348 GEN
Solar/Wind Harmer
1.237
20634528N27_Y2-018
Solar/Wind Harmer
0.189
20674128FR_U2-059
Solar/Wind Harmer
0.131
20465127PORT CT
Adder
2.812
208835TUHI V3-051
Solar/Wind Harmer
0.045
208835TUHI V3-051
Solar/Wind Harmer
0.045
966111AG1-480 GEN
Solar/Wind Harmer
0.061
966111AG1-480 GEN
Solar/Wind Harmer
2.325
211065PSPA IPP
Solar/Wind Harmer
0.32
211065PSPA IPP
Solar/Wind Harmer
0.32
961541AF2-445A GEN
Solar/Wind Harmer
2.286
208972BECR K09
Solar/Wind Harmer
0.742
961431AF2-434 GEN
Solar/Wind Harmer
0.694
209029WAYMART-WD
Solar/Wind Harmer
2.01
209009PEIP 2
Adder
5.459
209010PEIP 1
Adder
2.473
209010PEIP 1
Adder
0.362
209054AE2-059 GEN
Solar/Wind Harmer
1.167
209059AE2-084 GEN
Solar/Wind Harmer
1.723
946751AF1-339 GEN
Solar/Wind Harmer
0.687
209130AF1-271A GEN
Solar/Wind Harmer
1.932
209137AF2-361 C
Solar/Wind Harmer
2.157
220917WAGNERG1
Adder
14.098
220921WAGNR GT
Adder
1.464
315651AD1-115 GEN
Solar/Wind Helper
1.783
316447AC1-158 HLD
Solar/Wind Helper
6.448
966001AG1-469 GEN
Solar/Wind Helper
0.504
316468AD1-105 GEN
Solar/Wind Helper
2.252
316077AC2-138 C
Solar/Wind Helper
0.416
966871AG1-558 GEN
Solar/Wind Helper
0.59
316487AF1-042 GEN
Solar/Wind Helper
0.441
316075AC2-137 C
Solar/Wind Helper
0.654
3143526WINTERP
Solar/Wind Helper
2.23
3142946ENON
Solar/Wind Helper
0.043
316240AF1-291 C
Solar/Wind Helper
0.564
316033AB2-134 GEN
Solar/Wind Helper
1.435
315697AD1-025 GEN
Solar/Wind Helper
4.769
316236AE1-162_GEN
Solar/Wind Helper
0.554
316036AC1-147 C
Solar/Wind Helper
0.623
316316AC1-027 C
Solar/Wind Helper
0.645
3142956BIRDNECK
Solar/Wind Helper
0.275
316185AD1-033 GEN
Solar/Wind Helper
1.918
3145506HICKORY
Solar/Wind Helper
1.629
3145506HICKORY
Solar/Wind Helper
0.977
3145506HICKORY
Solar/Wind Helper
0.244
316339AD2-160 GEN
Solar/Wind Helper
1.547
316018AA1-139 ULT2
Solar/Wind Helper
1.745
316017AA1-139 ULT1
Solar/Wind Helper
1.855
3137176SLIGO L2192
Solar/Wind Helper
1.613
3130086AYDLETT
Solar/Wind Helper
1.619
3146386ELIZ CT
Solar/Wind Helper
0.402
316431W1029_GEN1
Solar/Wind Helper
1.613
316433W1029_GEN2
Solar/Wind Helper
1.613
3146516WINFALL
Solar/Wind Helper
0.398
3146516WINFALL
Solar/Wind Helper
0.398
3146516WINFALL
Solar/Wind Helper
0.398
3144356SAPONY
Solar/Wind Helper
0.711
3146626S HERTFORD
Solar/Wind Helper
0.397
3146626S HERTFORD
Solar/Wind Helper
0.397
315742AE1-103 GEN
Solar/Wind Helper
0.632
3145893MURPHYS
Solar/Wind Helper
0.538
3145893MURPHYS
Solar/Wind Helper
0.675
3146173TUNIS
Solar/Wind Helper
0.372
3146173TUNIS
Solar/Wind Helper
0.372
316181AB2-040 GEN
Solar/Wind Helper
2.633
3142666NORTHAMPTON
Solar/Wind Helper
0.366
3142666NORTHAMPTON
Solar/Wind Helper
0.366
3142666NORTHAMPTON
Solar/Wind Helper
0.366
3142666NORTHAMPTON
Solar/Wind Helper
0.219
3146776BUCKING
Solar/Wind Helper
1.461
3146776BUCKING
Solar/Wind Helper
0.118
316426AA2-053 GEN
Solar/Wind Helper
2.08
3145593CAROLNA
Solar/Wind Helper
0.364
3145593CAROLNA
Solar/Wind Helper
0.364
3145796HORNRTN
Solar/Wind Helper
1.082
3147133PAMPLIN
Solar/Wind Helper
0.358
3147133PAMPLIN
Solar/Wind Helper
0.287
3145933PARMELE
Solar/Wind Helper
0.707
3145933PARMELE
Solar/Wind Helper
0.354
316034AC1-036 C
Solar/Wind Helper
0.37
316274AC1-208 GEN
Solar/Wind Helper
2.151
315821AE2-092 GEN
Solar/Wind Helper
3.134
3146843MT LREL
Solar/Wind Helper
0.336
3146843MT LREL
Solar/Wind Helper
0.336
316222AC1-221 GEN
Solar/Wind Helper
1.724
3132123MT JACKSON
Solar/Wind Helper
0.871
270013AE1-250 PV
Solar/Wind Helper
0.915
316197AC1-042 GEN
Solar/Wind Helper
0.229
207437AD2-070 GEN
Solar/Wind Harmer
0.213
966181AG1-487 GEN
Solar/Wind Harmer
2.661
207518AF1-320_GEN
Solar/Wind Harmer
2.582
20671928W4-073
Solar/Wind Harmer
0.306
20465127PORT CT
Adder
2.119
208909MACR G3
Adder
112.881
208923BUSO V4-027
Solar/Wind Harmer
0.328
208856AE1-226 GEN
Solar/Wind Harmer
2.326
961301AF2-421 GEN
Solar/Wind Harmer
0.706
963151AG1-164 GEN
Solar/Wind Harmer
0.706
209023WIENIPP1
Adder
7.609
209025WIENIPP3
Adder
3.798
212266LOR1
Solar/Wind Harmer
0.091
970237AG2-161 GEN
Solar/Wind Harmer
2.444
961341AF2-425 GEN
Solar/Wind Harmer
0.695
212174INGE
Adder
0.769
209010PEIP 1
Adder
0.45
212507AE2-042_GEN
Solar/Wind Harmer
2.067
946731AF1-337 GEN
Solar/Wind Harmer
0.687
209071AE2-133 GEN
Solar/Wind Harmer
1.163
970665AG2-430 GEN
Solar/Wind Harmer
6.817
209018SUNBIPCT
Adder
5.117
972241AH1-705 GEN
Adder
3.981
223401AF1-299 GEN
Solar/Wind Harmer
0.492
970643AG2-418 GEN
Solar/Wind Harmer
2.077
220912PHIL G34
Adder
3.355
970679AG2-439 GEN
Solar/Wind Harmer
0.905
964991AG1-363 GEN
Solar/Wind Harmer
8.224
964991AG1-363 GEN
Solar/Wind Harmer
4.217
200917MEHOOPANY_G
Solar/Wind Harmer
3.019
316006AB2-029 C
Solar/Wind Helper
0.269
316045AC1-158 PL2
Solar/Wind Helper
9.379
316254AC1-120 GEN1
Solar/Wind Helper
2.401
3147666LOUISA
Solar/Wind Helper
1.913
316192AB2-158 GEN
Solar/Wind Helper
3.207
316337AD2-073 GEN
Solar/Wind Helper
0.678
964211AG1-282 GEN
Solar/Wind Helper
0.594
3141726DUNNSVL
Solar/Wind Helper
1.762
3142416OLDCHRC
Solar/Wind Helper
1.124
3142416OLDCHRC
Solar/Wind Helper
0.431
3138133OCRAN
Solar/Wind Helper
0.259
3141766HARMONY
Solar/Wind Helper
0.086
3143526WINTERP
Solar/Wind Helper
2.23
3142433PROV 92
Solar/Wind Helper
1.714
3143226MDLTHAN
Solar/Wind Helper
0.429
3142543TWELFTH
Solar/Wind Helper
0.041
316159AE1-175 C
Solar/Wind Helper
0.639
316458AB2-190 GEN2
Solar/Wind Helper
2.394
3145336SMITFLD
Solar/Wind Helper
1.649
316294AC1-161 GEN
Solar/Wind Helper
7.53
316381AD1-082 GEN
Solar/Wind Helper
2.124
316375AC2-012 GEN
Solar/Wind Helper
1.072
316072AD1-144
Solar/Wind Helper
0.466
316388AE2-253 GEN
Solar/Wind Helper
1.547
3146456SLIGO L269
Solar/Wind Helper
0.405
316246AF1-032 C
Solar/Wind Helper
0.463
3146516WINFALL
Solar/Wind Helper
1.291
3146516WINFALL
Solar/Wind Helper
0.398
316336AC2-165 C
Solar/Wind Helper
2.139
315800Z1-036_GEN1
Solar/Wind Helper
2.166
3130156CHOWAN
Solar/Wind Helper
0.39
3145663CRESWEL
Solar/Wind Helper
1.075
316023GEN1_S
Solar/Wind Helper
1.431
3146206CASHIE
Solar/Wind Helper
0.376
3145893MURPHYS
Solar/Wind Helper
1.5
3146173TUNIS
Solar/Wind Helper
0.372
3145683EARLEYS
Solar/Wind Helper
0.37
3146263WOODLND
Solar/Wind Helper
0.368
316322AB2-045
Solar/Wind Helper
0.407
3146776BUCKING
Solar/Wind Helper
0.146
3145963POPLR C
Solar/Wind Helper
0.365
3146926FARMVIL
Solar/Wind Helper
0.219
316011AB1-132 GEN
Solar/Wind Helper
3.925
316190AA2-174 GEN
Solar/Wind Helper
0.024
3145823KELFORD
Solar/Wind Helper
0.364
316174AB2-169 GEN
Solar/Wind Helper
0.924
3145783HORNRTN
Solar/Wind Helper
0.362
3145796HORNRTN
Solar/Wind Helper
1.19
3145796HORNRTN
Solar/Wind Helper
0.361
316212AC1-099_GEN
Solar/Wind Helper
1.591
316129AC1-054 GEN
Solar/Wind Helper
1.75
316237AB2-079_GEN
Solar/Wind Helper
0.469
3145746EVERETS
Solar/Wind Helper
0.348
3145746EVERETS
Solar/Wind Helper
0.348
315722AD1-056 GEN
Solar/Wind Helper
1.868
315687AD1-152 GEN
Solar/Wind Helper
1.86
316494AC1-189 GEN
Solar/Wind Helper
2.104
3146233WITAKRS
Solar/Wind Helper
1.357
961671AG1-007 GEN
Solar/Wind Helper
0.245
3146083TARBORO
Solar/Wind Helper
0.341
3145543BTLEBRO
Solar/Wind Helper
0.337
3145543BTLEBRO
Solar/Wind Helper
0.269
316359AB2-059 GEN
Solar/Wind Helper
2.564
316049AB1-081 GEN
Solar/Wind Helper
2.05
316003AC1-222 GEN
Solar/Wind Helper
1.377
3147983MERCK5
Solar/Wind Helper
0.114
3147123OTTER R
Solar/Wind Helper
0.15
270016AE1-250 BESS
Solar/Wind Helper
0.915
3147312GRETNA
Solar/Wind Helper
0.195
3146802CHATHAM
Solar/Wind Helper
0.183
238148AE2-230_GEN2
Solar/Wind Helper
0.398
270173AC1-122 GEN
Solar/Wind Helper
1.473
224055DICKHCT2
50/50
1.534
224056MCTRSH1G
50/50
0.532
23572401GUILF2
50/50
0.49
200200DELTA2 CT1
50/50
1.967
200193DELTA CT2
50/50
1.099
200203Y1-065-STG
50/50
4.017
200055ROCKSP 4
50/50
1.447
237030AB1-096 C
Solar/Wind Harmer
0.545
238142AE2-333 GEN2
Solar/Wind Harmer
8.044
238221AF1-254 C O1
Solar/Wind Harmer
0.963
235067AD1-061 GEN
Solar/Wind Harmer
0.782
205917AD1-020 ES
Solar/Wind Harmer
0.541
20464727HUNTR CT
Adder
3.167
966131AG1-482 GEN
Solar/Wind Harmer
2.633
232907VN8
Adder
22.102
233994AC2-023 GEN
Solar/Wind Harmer
1.978
233996TM1833_GEN
Solar/Wind Harmer
0.932
233997TMININ_4.2
Solar/Wind Harmer
0.932
232406W1-004 FULL
Solar/Wind Harmer
0.737
233940AF2-379 C
Solar/Wind Harmer
0.137
234015AF2-250 C
Solar/Wind Harmer
0.089
232914OH NUG3
Adder
6.5
232916OH NUG5
Adder
6.5
972073AH1-586 GEN
Solar/Wind Harmer
6.897
232921TASLEY2G
Adder
3.799
233900O-025 C
Adder
0.867
960671AF2-358 GEN
Solar/Wind Harmer
13.181
972133AH1-634 GEN
Solar/Wind Harmer
7.295
233990AG1-397 GEN
Solar/Wind Harmer
0.844
232417X3-008 C
Solar/Wind Harmer
1.472
233971AC1-093 C
Solar/Wind Harmer
0.577
970695AG2-447 GEN
Solar/Wind Harmer
2.635
233952AC2-187 GEN
Solar/Wind Harmer
0.828
233918AB1-142 GEN
Solar/Wind Harmer
0.729
233982AB2-133 GEN
Solar/Wind Harmer
3.581
972251AH1-710 GEN
Adder
32.735
228202CUMB CT
Adder
11.099
228711V2-041C
Solar/Wind Harmer
0.404
213497CHSTR7-9
Adder
1.837
971553AH1-274 GEN
Solar/Wind Harmer
1.628
230430AE1-229_GEN
Solar/Wind Harmer
5.915
230415AB2-049 C
Solar/Wind Harmer
0.127
228304LOGAN
Adder
14.627
228729W2-030 C
Solar/Wind Harmer
0.388
213958STHWK5-6
Adder
1.83
219623KINSLEYBEA C
Solar/Wind Harmer
0.287
219766PARADISE C
Solar/Wind Harmer
0.211
213560DLW11-12
Adder
1.826
219912AD2-042 GEN
Solar/Wind Harmer
0.534
219291REEVESSOUT C
Solar/Wind Harmer
0.04
213815MOSER1-3
Adder
2.383
219236SOUTHERNHQ C
Solar/Wind Harmer
0.045
219906AC1-017 C
Solar/Wind Harmer
0.149
219610FLORENCE C
Solar/Wind Harmer
0.927
219348LDSOLAR C
Solar/Wind Harmer
0.401
219221BRL12CT1
Adder
5.975
219223BRL12CT3
Adder
5.975
959561AF2-247 GEN
Solar/Wind Harmer
0.325
20716028EGP_W2-019
Solar/Wind Harmer
0.31
20720828JCB_W4-025
Solar/Wind Harmer
0.303
20715028HAN_X4-015
Solar/Wind Harmer
0.199
20636028O CRK C1
Adder
4.721
971667AH1-334 GEN
Solar/Wind Harmer
1.84
219727YARDVSOLFA C
Solar/Wind Harmer
0.611
219276PARKLANDSO C
Solar/Wind Harmer
0.311
20714528FRN_Y2-051
Solar/Wind Harmer
0.198
219918AC2-009 C
Solar/Wind Harmer
0.041
20716228APLW2-078
Solar/Wind Harmer
0.595
20720528MAN_W1-024
Solar/Wind Harmer
0.171
967451AG2-055 C O1
Solar/Wind Harmer
117.231
219612MATRIX C
Solar/Wind Harmer
0.124
218438BLK ROCK C
Solar/Wind Harmer
0.092
20635828PARLN1&2
Adder
2.274
20635928PARLN3&4
Adder
2.274
20635028RRCT1&2
Adder
8.004
20635128RRCT3&4
Adder
6.636
972221AH1-695 GEN
Adder
109.752
219908AB1-139 C
Solar/Wind Harmer
0.26
219919AE1-041 FULL
Solar/Wind Harmer
0.028
219249CENTRALDIV C
Solar/Wind Harmer
0.027
20673728F2S_V4-070
Solar/Wind Harmer
0.123
217211CAMDEN ST C
Solar/Wind Harmer
0.017
217186ESSEX_G9
Adder
10.977
217169METRODIV C
Solar/Wind Harmer
0.027
217194REDH C
Solar/Wind Harmer
0.338
20676728BRNX1-095
Solar/Wind Harmer
0.122
207510AF2-138 C
Solar/Wind Harmer
1.242
20674628WNG_W3-110
Solar/Wind Harmer
0.281
20633028GILCT9
Adder
20.111
966181AG1-487 GEN
Solar/Wind Harmer
0.178
971007AG2-625 GEN
Solar/Wind Harmer
1.809
20466127PORT 5CT
Adder
18.693
20465427SHAW CT
Adder
2.724
963161AG1-165 GEN
Solar/Wind Harmer
0.706
209025WIENIPP3
Adder
3.722
963071AG1-156 GEN
Solar/Wind Harmer
1.938
970095AG2-074 GEN
Solar/Wind Harmer
4.397
209027LOR2_Q27
Solar/Wind Harmer
3.183
209022WHFR IPP
Adder
2.285
961331AF2-424 GEN
Solar/Wind Harmer
0.695
961421AF2-433 GEN
Solar/Wind Harmer
0.694
957921AF2-086 GEN
Solar/Wind Harmer
0.675
209142AF1-226 GEN
Solar/Wind Harmer
4.017
209093AE2-110 GEN
Solar/Wind Harmer
1.735
209120AE2-241 GEN
Solar/Wind Harmer
2.296
972245AH1-707 GEN
Adder
3.758
946691AF1-333 GEN
Solar/Wind Harmer
0.687
946741AF1-338 GEN
Solar/Wind Harmer
0.687
209067AE2-060 GEN
Solar/Wind Harmer
1.116
223402AF1-300 C
Solar/Wind Harmer
0.492
970643AG2-418 GEN
Solar/Wind Harmer
0.966
220913PHIL G12
Adder
3.4
970999AG2-617 GEN
Solar/Wind Harmer
4.938
223203V3-037
Adder
0.305
3141196NOKESVL
Solar/Wind Helper
2.5
316044AC1-158 PL1
Solar/Wind Helper
2.93
316450AC1-158 RIC
Solar/Wind Helper
0.781
316170AC1-121 GEN2
Solar/Wind Helper
0.8
3132273ORANGE
Solar/Wind Helper
0.098
3147666LOUISA
Solar/Wind Helper
1.1
966881AG1-559 GEN
Solar/Wind Helper
0.63
3141906WESTMOR
Solar/Wind Helper
0.181
316404AE1-155 C
Solar/Wind Helper
3.701
316473AC1-191 GEN
Solar/Wind Helper
2.676
316484AD2-074 GEN
Solar/Wind Helper
0.843
316156AD2-030 GEN
Solar/Wind Helper
0.648
316280AD1-041 GEN
Solar/Wind Helper
1.443
3142946ENON
Solar/Wind Helper
0.142
316382AG1-145 C
Solar/Wind Helper
0.567
315839AE2-212 C
Solar/Wind Helper
0.56
3145336SMITFLD
Solar/Wind Helper
0.165
315773AC2-141 GEN
Solar/Wind Helper
8.863
3144536CHRHLND
Solar/Wind Helper
0.062
3144873MCLAUGH
Solar/Wind Helper
0.01
3146456SLIGO L269
Solar/Wind Helper
0.405
316313AB2-026
Solar/Wind Helper
0.615
316258AE1-075 C
Solar/Wind Helper
0.553
316405AF2-144 C
Solar/Wind Helper
0.461
316320Y1-086
Solar/Wind Helper
0.18
316435W1029_GEN3
Solar/Wind Helper
1.613
3146516WINFALL
Solar/Wind Helper
0.398
3146626S HERTFORD
Solar/Wind Helper
0.397
3145273HOLLAND
Solar/Wind Helper
0.297
3146376EDENTON
Solar/Wind Helper
0.39
315614AA2-178 GEN
Solar/Wind Helper
2.34
315737AD1-076 GEN
Solar/Wind Helper
3.697
316365GEN2_N
Solar/Wind Helper
1.431
3146206CASHIE
Solar/Wind Helper
0.376
3145893MURPHYS
Solar/Wind Helper
0.134
3145893MURPHYS
Solar/Wind Helper
0.375
3146173TUNIS
Solar/Wind Helper
0.372
3156021HOLLOMANSOL
Solar/Wind Helper
2.827
316463AE2-346 GEN
Solar/Wind Helper
0.339
316140AB2-099
Solar/Wind Helper
0.141
966621AG1-532 GEN
Solar/Wind Helper
0.337
3146263WOODLND
Solar/Wind Helper
0.368
313506AB2-031 GEN
Solar/Wind Helper
1.666
3142666NORTHAMPTON
Solar/Wind Helper
0.366
3146776BUCKING
Solar/Wind Helper
0.131
3145963POPLR C
Solar/Wind Helper
0.365
3146926FARMVIL
Solar/Wind Helper
0.219
316317KELFORD C
Solar/Wind Helper
0.31
3145823KELFORD
Solar/Wind Helper
0.364
3147043LAWRENC
Solar/Wind Helper
0.218
942461AE2-259 GEN
Solar/Wind Helper
2.436
3145796HORNRTN
Solar/Wind Helper
1.442
3145796HORNRTN
Solar/Wind Helper
0.361
316478AD1-087 GEN
Solar/Wind Helper
1.763
316486AD2-202 GEN
Solar/Wind Helper
0.516
3147133PAMPLIN
Solar/Wind Helper
1.124
316210AC1-098 GEN
Solar/Wind Helper
2.863
3145933PARMELE
Solar/Wind Helper
0.354
315785AD2-033 C
Solar/Wind Helper
4.116
316131AB2-060 GEN
Solar/Wind Helper
2.133
3145746EVERETS
Solar/Wind Helper
0.348
3145746EVERETS
Solar/Wind Helper
0.348
315724AD1-057 GEN
Solar/Wind Helper
1.027
316327AA2-057 GEN
Solar/Wind Helper
1.971
3146233WITAKRS
Solar/Wind Helper
0.367
3146233WITAKRS
Solar/Wind Helper
0.232
3146073TAR RVR
Solar/Wind Helper
0.341
3146083TARBORO
Solar/Wind Helper
0.341
3138543CONSLDL
Solar/Wind Helper
0.225
3145543BTLEBRO
Solar/Wind Helper
0.337
3145543BTLEBRO
Solar/Wind Helper
0.337
316248AF1-058 C
Solar/Wind Helper
0.437
3148013FISHERV
Solar/Wind Helper
0.309
316283AC2-100 C
Solar/Wind Helper
1.607
316499AE2-029_GEN
Solar/Wind Helper
0.977
315616AA1-038_C
Solar/Wind Helper
1.257
237061AD1-155 GEN
Solar/Wind Helper
0.05
3147312GRETNA
Solar/Wind Helper
0.049
270197AD1-017 GEN1
Solar/Wind Helper
1.297
270018AE2-047 C O1
Solar/Wind Helper
0.816
238147AE2-230_GEN1
Solar/Wind Helper
0.396
238149AF1-291A_GEN
Solar/Wind Helper
0.113
HAMLETPJM->LTFIMP_HAMLET
CLTF
6.833
G-007ALTFEXP_G-007A->PJM
CMTX
34.809
CBM NorthLTFEXP_CBM-N->PJM
CBM
58.092
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
2.861
BlueGrassPJM->LTFIMP_BlueG
CLTF
8.962
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
92.87
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.68
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
14.764

Details for 01DOUBS-8GOOSE CREEK 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 203-9404_SRT-S


Base Case Flowgate

Area:AP/DVP
Facility Description:
01DOUBS-8GOOSE CREEK 500.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 203-9404_SRT-S
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:100.81 %
Rating:4357.0 MVA
Rating Type:B
MVA to Mitigate:4392.29
MW Contribution:5.15
Bus #Bus NameTypeMW Contribution
224054DICKHCT1
50/50
1.481
966141AG1-483 GEN
50/50
92.09
23757701ROUTE 16
50/50
2.738
200035PCHBTM 3
50/50
11.704
200201DELTA2 CT2
50/50
1.967
200034PCHBTM 2
50/50
11.456
200205Y1-065-CTG2
50/50
2.317
23777801MSM_W1-116
Solar/Wind Harmer
0.963
237034AC2-136 C
Solar/Wind Harmer
0.606
237025AB1-124 C
Solar/Wind Harmer
1.349
237006AB1-125 GEN
Solar/Wind Harmer
1.012
23777901MDS_W4-102
Solar/Wind Harmer
1.305
235020AA1-095 C
Solar/Wind Harmer
0.215
237001AB1-127_GEN
Solar/Wind Harmer
0.686
237002AB1-128_GEN
Solar/Wind Harmer
0.683
235063AE1-101 C2
Solar/Wind Harmer
2.513
203982AD2-062_GEN
Solar/Wind Harmer
11.666
20464927ORTAN CT
Adder
2.907
205916AD1-020 GEN
Solar/Wind Harmer
2.513
20390526W1-045 C
Solar/Wind Harmer
0.502
233987AB2-037 GEN
Solar/Wind Harmer
8.381
233901CHERRYDALE C
Solar/Wind Harmer
0.829
232408W1-005 C
Solar/Wind Harmer
0.737
232410W1-006 C
Solar/Wind Harmer
0.737
972069AH1-584 GEN
Solar/Wind Harmer
6.591
972071AH1-585 GEN
Solar/Wind Harmer
6.591
232918OH NUG7
Adder
6.457
971747AH1-380 GEN
Solar/Wind Harmer
2.636
232905CHERITON_25
Adder
1.806
232926CRISFLD1
Adder
1.444
233946AB2-136 GEN
Solar/Wind Harmer
2.937
234036AF2-325 C
Solar/Wind Harmer
0.675
970545AG2-347 GEN
Solar/Wind Harmer
48.15
231940T-011
Adder
0.549
234041AC1-190 GEN
Solar/Wind Harmer
6.59
971149AH1-027 GEN
Solar/Wind Harmer
2.49
233939AC1-091 C
Solar/Wind Harmer
0.646
233970AC1-092 C
Solar/Wind Harmer
0.646
232899W1-062
Adder
7.075
233984AB2-036 GEN
Solar/Wind Harmer
9.159
232424Y1-079 C
Solar/Wind Harmer
0.414
234014AF1-036_GEN
Solar/Wind Harmer
1.99
231131BLOOM ENRGY
Adder
3.202
233944AB2-135 GEN
Solar/Wind Harmer
3.851
233933AB2-153 GEN
Solar/Wind Harmer
0.827
232416X2-083
Adder
0.331
213587EDDYSTN3
Adder
53.693
213589EDDYSTN4
Adder
53.695
228251CARLLS#4
Adder
0.424
230433AD2-135 GEN
Solar/Wind Harmer
0.068
228307PCLP GT
Adder
8.128
230422AE1-104_GEN1
Solar/Wind Harmer
22.636
230425AE1-104_GEN2
Solar/Wind Harmer
22.636
228304LOGAN
Adder
16.264
972233AH1-701 GEN
Adder
2.82
230407AD2-065 C
Solar/Wind Harmer
0.088
219921AF1-264
Solar/Wind Harmer
0.097
213815MOSER1-3
Adder
2.383
213815MOSER1-3
Adder
2.383
20464827MOUNT CT
Adder
2.842
20464827MOUNT CT
Adder
2.758
219615MILLCREEK C
Solar/Wind Harmer
0.16
213535CROYDN11
Adder
6.849
20716428NHV_W2-082
Solar/Wind Harmer
1.188
207500AE2-000G1
Solar/Wind Harmer
21.039
207497AE2-000G2
Solar/Wind Harmer
21.039
207507AE2-000G3
Solar/Wind Harmer
21.039
20636128O CRK C2
Adder
4.304
963401AG1-189 GEN
Solar/Wind Harmer
0.769
963391AG1-188 GEN
Solar/Wind Harmer
1.282
219114HARTZY_C
Solar/Wind Harmer
0.559
20714928UPF_X1-085
Solar/Wind Harmer
0.272
20628028LAKEHURS
Adder
0.637
219817TRENTONSOL C
Solar/Wind Harmer
0.742
20641628MLH_W1-032
Solar/Wind Harmer
0.197
20720628TIN_W1-124
Solar/Wind Harmer
0.671
20716928W4-060COL
Solar/Wind Harmer
0.481
924131AB2-057 GEN
Solar/Wind Harmer
0.698
218440SUMMTASSOC C
Solar/Wind Harmer
0.087
20673828FLE_V3-070
Solar/Wind Harmer
0.313
23776901DAM 5 HY
50/50
0.011
966461AG1-515 GEN
50/50
0.72
23732901CHBRG_I12
50/50
4.144
200202DELTA2 ST
50/50
3.337
200195DELTA ST
50/50
1.698
23776801DAM 4 HY
50/50
0.012
970429AG2-279 GEN
Solar/Wind Harmer
3.213
237085AD2-009_GEN
Solar/Wind Harmer
2.184
238208AF1-136 C
Solar/Wind Harmer
0.656
959381AF2-229 GEN
Solar/Wind Harmer
0.975
20087026C_T85_W218
Adder
0.813
20464627HAM CT
Adder
2.899
233923SMA
Solar/Wind Harmer
3.418
232912OH NUG1
Adder
6.5
232913OH NUG2
Adder
6.413
234033AF1-007_GEN
Solar/Wind Harmer
17.206
233990AG1-397 GEN
Solar/Wind Harmer
0.041
232432Z2-076 GEN
Solar/Wind Harmer
0.097
232904IR4
Adder
59.494
232920IR10
Adder
2.325
233955AB2-172 GEN
Solar/Wind Harmer
3.68
233973AC2-185 C
Solar/Wind Harmer
2.658
232813VAUGHN
Adder
0.433
233968AD2-076_GEN
Solar/Wind Harmer
4.876
970597AG2-380 GEN
Solar/Wind Harmer
3.062
232436AB1-176 C
Solar/Wind Harmer
0.169
231906DC3 NUG
Adder
10.285
231902DC CT7
Adder
8.222
231907DC10
Adder
2.568
971983AH1-536 GEN
Solar/Wind Harmer
5.501
233935AB2-179 C
Solar/Wind Harmer
1.836
231919CHRIST1
Adder
3.228
231920CHRIST2
Adder
3.157
970453AG2-297 GEN
Solar/Wind Harmer
1.854
228260V4-054C
Solar/Wind Harmer
0.69
228309CCLP NUG
Adder
17.377
228309CCLP NUG
Adder
16.529
972141AH1-641 GEN
Solar/Wind Harmer
1.933
964001AG1-254 GEN
Solar/Wind Harmer
1.367
971011AG2-627 GEN
Solar/Wind Harmer
5.152
971535AH1-265 GEN
Solar/Wind Harmer
2.86
227927V4-067C
Solar/Wind Harmer
0.133
228754AB1-001 C
Solar/Wind Harmer
0.094
213942SCHUYLKILL
Adder
2.394
213942SCHUYLKILL
Adder
1.831
213957STHWK3-4
Adder
1.83
213957STHWK3-4
Adder
1.83
219137THOSOLAR C
Solar/Wind Harmer
0.812
213561DLWR9-10
Adder
2.387
213561DLWR9-10
Adder
1.826
219914AD2-027 C
Solar/Wind Harmer
0.403
219272CLEANLIGHT C
Solar/Wind Harmer
0.122
219688LUMSOLAR_S C
Solar/Wind Harmer
0.136
205943AE1-185 GEN
Solar/Wind Harmer
0.715
219607WPEMNERT C
Solar/Wind Harmer
0.281
219224BRL12CT4
Adder
5.975
205956AE1-196_GEN
Solar/Wind Harmer
0.713
205932AD2-116_GEN
Solar/Wind Harmer
0.713
960921AF2-383 GEN
Solar/Wind Harmer
0.239
20465027TOLNA CT
Adder
2.933
960921AF2-383 GEN
Solar/Wind Harmer
1.836
214067T20SOLAR
Solar/Wind Harmer
0.169
213611FALLS1-3
Adder
2.369
213611FALLS1-3
Adder
2.369
205951AE1-129_GEN
Solar/Wind Harmer
9.964
20717128DIX_Z2-102
Solar/Wind Harmer
0.882
20715728PEM_W1-119
Solar/Wind Harmer
0.357
20715828PEM_W1-120
Solar/Wind Harmer
0.357
970025AG2-016 GEN
Solar/Wind Harmer
1.894
971189AH1-054 GEN
Solar/Wind Harmer
0.789
207459AE1-142 C O1
Solar/Wind Harmer
0.707
219620RIDERU C
Solar/Wind Harmer
0.038
20714328BYD_X4-031
Solar/Wind Harmer
0.19
20714428HOW_X1-037
Solar/Wind Harmer
0.831
203975AE1-071-GEN
Solar/Wind Harmer
3.518
971521AH1-258 GEN
Solar/Wind Harmer
1.826
20720428HOL_W1-112
Solar/Wind Harmer
0.234
218455CINNBAY_CGEN
Adder
1.233
20635928PARLN3&4
Adder
5.02
20675528CPH_W2-050
Solar/Wind Harmer
0.319
218526CNTRALGAS2 C
Solar/Wind Harmer
0.252
218524CNTRALGAS1 C
Solar/Wind Harmer
0.252
208862AG1-362 C
Solar/Wind Harmer
0.619
218404KENILWRTH C
Adder
0.895
217167KRNY_14
Adder
6.383
217086KRNY_131
Adder
6.329
217147KRNY_1212
Adder
6.071
217147KRNY_1212
Adder
5.963
217146KRNY_1234
Adder
5.949
217146KRNY_1234
Adder
5.909
20486527WR_V4-052
Adder
0.813
966261AG1-495 GEN
Solar/Wind Harmer
1.25
207530AG1-191 GEN
Solar/Wind Harmer
0.962
20676328BVR_Y1-020
Solar/Wind Harmer
0.231
207511W3-106 GEN
Solar/Wind Harmer
0.458
20674828DL_W4-046
Solar/Wind Harmer
0.454
20675928HOL_W4-097
Solar/Wind Harmer
0.093
207484AF2-139 C O1
Solar/Wind Harmer
0.358
971009AG2-626 GEN
Solar/Wind Harmer
1.154
207408W3-077 C
Solar/Wind Harmer
0.358
20675728RH_W2-091
Solar/Wind Harmer
0.242
20675128HRM_W1-127
Solar/Wind Harmer
0.121
20462827N BANGR8
Adder
0.507
966421AG1-511 GEN
Solar/Wind Harmer
6.061
209030FRFA O01
Adder
0.212
209116AE2-175 GEN
Solar/Wind Harmer
2.913
209026WIENIPP4
Adder
3.76
961261AF2-417 GEN
Solar/Wind Harmer
0.703
209045AE2-271 GEN
Solar/Wind Harmer
11.631
959431AF2-234 GEN
Solar/Wind Harmer
1.374
964051AG1-259 GEN
Solar/Wind Harmer
0.921
964061AG1-260 GEN
Solar/Wind Harmer
0.921
959421AF2-233 GEN
Solar/Wind Harmer
0.687
220910PERRYG34
Adder
12.33
220909PERRYG12
Adder
6.165
20390726Y2-042
Adder
2.167
20334726NME_Y1-047
Adder
2.029
3138216PACIFIC
Solar/Wind Helper
0.122
316411AF1-147_GEN1
Solar/Wind Helper
2.387
316415AF1-147_GEN2
Solar/Wind Helper
2.387
316164AC1-076 GEN
Solar/Wind Helper
2.474
3141426STAFORD
Solar/Wind Helper
0.113
316223AC1-118
Solar/Wind Helper
0.69
3141813NORNECK
Solar/Wind Helper
0.442
3141783LANCAST
Solar/Wind Helper
0.26
3141783LANCAST
Solar/Wind Helper
0.173
23572301GUILF1
50/50
0.484
200192DELTA CT1
50/50
1.099
200194DELTA CT3
50/50
1.099
200204Y1-065-CTG1
50/50
2.317
200054ROCKSP 3
50/50
1.478
23779801AA1-109
Solar/Wind Harmer
0.427
238141AE2-333 GEN1
Solar/Wind Harmer
8.044
237080AD1-060 GEN
Solar/Wind Harmer
0.51
237038AE2-054 C
Solar/Wind Harmer
0.928
970651AG2-423 GEN
Solar/Wind Harmer
12.228
235062AE1-101 C1
Solar/Wind Harmer
2.513
205975AE2-345_GEN
Solar/Wind Harmer
9.433
966131AG1-482 GEN
Solar/Wind Harmer
0.118
233998TM1NIN_3.36
Solar/Wind Harmer
0.932
232404W1-003 C
Solar/Wind Harmer
0.737
232428Y3-058 C
Solar/Wind Harmer
0.614
232917OH NUG6
Adder
6.471
232915OH NUG4
Adder
6.457
232919VN10
Adder
2.066
971195AH1-057 GEN
Solar/Wind Harmer
0.806
232426Y1-080 FULL
Solar/Wind Harmer
0.141
232434Z2-077 GEN
Solar/Wind Harmer
0.184
233964AF2-378 GEN
Solar/Wind Harmer
0.094
970277AG2-181 GEN
Solar/Wind Harmer
3.691
965821AG1-450 GEN
Solar/Wind Harmer
3.832
972177AH1-672 GEN
Solar/Wind Harmer
9.885
232901NORTHST
Adder
6.123
233972AC1-094 C
Solar/Wind Harmer
0.488
233954AC2-188 GEN
Solar/Wind Harmer
0.828
233950AC2-186 GEN
Solar/Wind Harmer
0.414
232900DEMECSMY
Adder
6.786
232910NRG_G1
Adder
6.35
234012AE2-112_GEN
Solar/Wind Harmer
1.692
232422X3-066 FULL
Solar/Wind Harmer
0.184
233930AB2-032 GEN
Solar/Wind Harmer
0.613
233915AB1-141 GEN
Solar/Wind Harmer
0.729
231918WEST 1
Adder
2.454
231917EM10
Adder
1.72
228206SHRMN CT
Adder
11.139
213497CHSTR7-9
Adder
1.837
213497CHSTR7-9
Adder
1.837
945431AF1-208 GEN
Solar/Wind Harmer
5.801
228732V1-021 C
Adder
0.127
970997AG2-616 GEN
Solar/Wind Harmer
6.444
228351V2-046C
Solar/Wind Harmer
1.354
230511AF1-262
Solar/Wind Harmer
0.123
228728W1-130C
Solar/Wind Harmer
0.446
230434AG1-499 GEN
Solar/Wind Harmer
0.39
213958STHWK5-6
Adder
1.83
219258KINSLEYDEP C
Solar/Wind Harmer
0.217
219904AC1-010 C
Solar/Wind Harmer
0.254
213560DLW11-12
Adder
1.826
218660EHAMPSOLAR C
Solar/Wind Harmer
0.117
219287REEVESEAST C
Solar/Wind Harmer
0.901
219686LUMSOLAR_N C
Solar/Wind Harmer
0.136
219907AC1-030 C
Solar/Wind Harmer
0.093
219304NAMERICA C
Solar/Wind Harmer
0.208
219222BRL12CT2
Adder
5.975
20465027TOLNA CT
Adder
2.821
214194N WALES4
Adder
0.573
205967AE2-211_GEN
Solar/Wind Harmer
7.222
213611FALLS1-3
Adder
2.369
20720728JCB_W1-129
Solar/Wind Harmer
0.199
207522AF2-254 C
Solar/Wind Harmer
0.959
207487AE2-000G4
Solar/Wind Harmer
21.039
207445AB1-138_GEN
Solar/Wind Harmer
0.388
20628028LAKEHURS
Adder
1.26
963711AG1-223 GEN
Solar/Wind Harmer
0.993
20714828MDF_W3-079
Solar/Wind Harmer
0.206
219680HOPEWELLV C1
Solar/Wind Harmer
0.051
207454AA2-184 E
Solar/Wind Harmer
0.673
20715228NPK_W1-113
Solar/Wind Harmer
0.29
20742028HF_AC1-207
Solar/Wind Harmer
0.529
217197RE CRAN C
Solar/Wind Harmer
0.363
20635828PARLN1&2
Adder
5.02
20635028RRCT1&2
Adder
7.881
20635128RRCT3&4
Adder
7.608
218428ETC SOLAR C
Solar/Wind Harmer
0.024
217213AMBOY SO C
Solar/Wind Harmer
0.086
207528AF2-192 GEN
Solar/Wind Harmer
0.379
20673628F1S_V4-069
Solar/Wind Harmer
0.123
20675428EAM_W2-061
Solar/Wind Harmer
0.129
972275AH1-722 GEN
Adder
21.545
20676428JCR_X2-075
Solar/Wind Harmer
0.234
218449LINSOLAR C
Solar/Wind Harmer
0.688
217209CENTRL HS C
Solar/Wind Harmer
0.031
217083KRNY_132
Adder
6.383
217121ECCF
Adder
0.298
217208PARK ELE C
Solar/Wind Harmer
0.017
20465527S.RDG CT
Adder
2.087
20467927PC_Q59Y356
Adder
0.637
205941AD2-115 GEN
Solar/Wind Harmer
0.69
20674328GAR_V4-001
Solar/Wind Harmer
0.077
207439AE1-081 C O1
Solar/Wind Harmer
0.042
209008PAXT IPP
Adder
1.608
971519AH1-257 GEN
Solar/Wind Harmer
1.777
20675828AU_W4-064
Solar/Wind Harmer
0.121
207437AD2-070 GEN
Solar/Wind Harmer
0.213
207442AE1-156 GEN
Solar/Wind Harmer
0.51
20676128MHD_W3-029
Solar/Wind Harmer
0.327
218418LINDEN_G5
Adder
11.719
218419LINDEN_G6
Adder
11.719
972260AH1-715 GEN1
Adder
9.384
219036LINDEN_G7
Adder
11.438
219035LINDEN_G8
Adder
11.275
972261AH1-715 GEN2
Adder
10.949
20671828STAW2-080
Solar/Wind Harmer
0.072
217081WEATEXAS C
Solar/Wind Harmer
0.059
20674528F3S_W2-016
Solar/Wind Harmer
0.973
217202FBANKSOLAR C
Solar/Wind Harmer
0.05
217201HACKENSOLA C
Solar/Wind Harmer
0.05
972237AH1-703 GEN
Adder
6.947
217206BARNGR HS C
Solar/Wind Harmer
0.021
217086KRNY_131
Adder
6.396
217083KRNY_132
Adder
6.342
20465527S.RDG CT
Adder
2.019
217204WCALDSOLAR C
Solar/Wind Harmer
0.05
20478527GLRA_Q45
Adder
0.257
20676228FRD_X1-012
Solar/Wind Harmer
0.413
207471AF2-354 C
Solar/Wind Harmer
0.36
20674928WA_W3-044
Solar/Wind Harmer
0.339
964851AG1-348 GEN
Solar/Wind Harmer
1.237
20634528N27_Y2-018
Solar/Wind Harmer
0.189
20674128FR_U2-059
Solar/Wind Harmer
0.131
20465127PORT CT
Adder
2.812
208835TUHI V3-051
Solar/Wind Harmer
0.045
208835TUHI V3-051
Solar/Wind Harmer
0.045
966111AG1-480 GEN
Solar/Wind Harmer
0.061
966111AG1-480 GEN
Solar/Wind Harmer
2.325
211065PSPA IPP
Solar/Wind Harmer
0.32
211065PSPA IPP
Solar/Wind Harmer
0.32
961541AF2-445A GEN
Solar/Wind Harmer
2.286
208972BECR K09
Solar/Wind Harmer
0.742
961431AF2-434 GEN
Solar/Wind Harmer
0.694
209029WAYMART-WD
Solar/Wind Harmer
2.01
209009PEIP 2
Adder
5.459
209010PEIP 1
Adder
2.473
209010PEIP 1
Adder
0.362
209054AE2-059 GEN
Solar/Wind Harmer
1.167
209059AE2-084 GEN
Solar/Wind Harmer
1.723
946751AF1-339 GEN
Solar/Wind Harmer
0.687
209130AF1-271A GEN
Solar/Wind Harmer
1.932
209137AF2-361 C
Solar/Wind Harmer
2.157
220917WAGNERG1
Adder
14.098
220921WAGNR GT
Adder
1.464
315651AD1-115 GEN
Solar/Wind Helper
1.783
316447AC1-158 HLD
Solar/Wind Helper
6.448
966001AG1-469 GEN
Solar/Wind Helper
0.504
316468AD1-105 GEN
Solar/Wind Helper
2.252
316077AC2-138 C
Solar/Wind Helper
0.416
966871AG1-558 GEN
Solar/Wind Helper
0.59
316487AF1-042 GEN
Solar/Wind Helper
0.441
316075AC2-137 C
Solar/Wind Helper
0.654
3143526WINTERP
Solar/Wind Helper
2.23
3142946ENON
Solar/Wind Helper
0.043
316240AF1-291 C
Solar/Wind Helper
0.564
316033AB2-134 GEN
Solar/Wind Helper
1.435
315697AD1-025 GEN
Solar/Wind Helper
4.769
316236AE1-162_GEN
Solar/Wind Helper
0.554
316036AC1-147 C
Solar/Wind Helper
0.623
316316AC1-027 C
Solar/Wind Helper
0.645
3142956BIRDNECK
Solar/Wind Helper
0.275
316185AD1-033 GEN
Solar/Wind Helper
1.918
3145506HICKORY
Solar/Wind Helper
1.629
3145506HICKORY
Solar/Wind Helper
0.977
3145506HICKORY
Solar/Wind Helper
0.244
316339AD2-160 GEN
Solar/Wind Helper
1.547
316018AA1-139 ULT2
Solar/Wind Helper
1.745
316017AA1-139 ULT1
Solar/Wind Helper
1.855
3137176SLIGO L2192
Solar/Wind Helper
1.613
3130086AYDLETT
Solar/Wind Helper
1.619
3146386ELIZ CT
Solar/Wind Helper
0.402
316431W1029_GEN1
Solar/Wind Helper
1.613
316433W1029_GEN2
Solar/Wind Helper
1.613
3146516WINFALL
Solar/Wind Helper
0.398
3146516WINFALL
Solar/Wind Helper
0.398
3146516WINFALL
Solar/Wind Helper
0.398
3144356SAPONY
Solar/Wind Helper
0.711
3146626S HERTFORD
Solar/Wind Helper
0.397
3146626S HERTFORD
Solar/Wind Helper
0.397
315742AE1-103 GEN
Solar/Wind Helper
0.632
3145893MURPHYS
Solar/Wind Helper
0.538
3145893MURPHYS
Solar/Wind Helper
0.675
3146173TUNIS
Solar/Wind Helper
0.372
3146173TUNIS
Solar/Wind Helper
0.372
316181AB2-040 GEN
Solar/Wind Helper
2.633
3142666NORTHAMPTON
Solar/Wind Helper
0.366
3142666NORTHAMPTON
Solar/Wind Helper
0.366
3142666NORTHAMPTON
Solar/Wind Helper
0.366
3142666NORTHAMPTON
Solar/Wind Helper
0.219
3146776BUCKING
Solar/Wind Helper
1.461
3146776BUCKING
Solar/Wind Helper
0.118
316426AA2-053 GEN
Solar/Wind Helper
2.08
3145593CAROLNA
Solar/Wind Helper
0.364
3145593CAROLNA
Solar/Wind Helper
0.364
3145796HORNRTN
Solar/Wind Helper
1.082
3147133PAMPLIN
Solar/Wind Helper
0.358
3147133PAMPLIN
Solar/Wind Helper
0.287
3145933PARMELE
Solar/Wind Helper
0.707
3145933PARMELE
Solar/Wind Helper
0.354
316034AC1-036 C
Solar/Wind Helper
0.37
316274AC1-208 GEN
Solar/Wind Helper
2.151
315821AE2-092 GEN
Solar/Wind Helper
3.134
3146843MT LREL
Solar/Wind Helper
0.336
3146843MT LREL
Solar/Wind Helper
0.336
316312AB1-027
Solar/Wind Helper
0.823
3138133OCRAN
Solar/Wind Helper
0.13
3141913WHIT STONE
Solar/Wind Helper
0.432
316059AD1-063 C
Solar/Wind Helper
0.433
957601AF2-054 GEN
Solar/Wind Helper
0.576
3141873WAN 176
Solar/Wind Helper
0.086
315662AE1-191 GEN
Solar/Wind Helper
2.309
315666AE1-190 GEN
Solar/Wind Helper
0.577
3143873LANEXA
Solar/Wind Helper
0.258
316233AE1-074 FULL
Solar/Wind Helper
0.655
957831AF2-077 GEN
Solar/Wind Helper
0.571
316132AB2-190 GEN1
Solar/Wind Helper
2.394
316369SG1_INVT
Solar/Wind Helper
2.007
3143316POE
Solar/Wind Helper
1.632
316349AD2-085 GEN
Solar/Wind Helper
1.857
319010AE1-072 C
Solar/Wind Helper
4.629
316305AF2-043 C
Solar/Wind Helper
0.544
313526AB2-022
Solar/Wind Helper
0.613
3146486SUNBURY
Solar/Wind Helper
0.402
3146486SUNBURY
Solar/Wind Helper
0.402
316321Z2-027
Solar/Wind Helper
0.611
3145176PASQUOTANK
Solar/Wind Helper
0.249
316315AB2-025 C
Solar/Wind Helper
0.604
315611Z1-036_GEN2
Solar/Wind Helper
2.166
3130156CHOWAN
Solar/Wind Helper
0.39
3130156CHOWAN
Solar/Wind Helper
0.39
315816AE2-034 GEN
Solar/Wind Helper
1.755
3130546PLYMOUTH
Solar/Wind Helper
0.379
315732AD1-074 GEN1
Solar/Wind Helper
4.323
315733AD1-074 GEN2
Solar/Wind Helper
4.323
315735AD1-075 GEN1
Solar/Wind Helper
2.161
3146206CASHIE
Solar/Wind Helper
0.376
3145893MURPHYS
Solar/Wind Helper
1.013
3145893MURPHYS
Solar/Wind Helper
0.375
3145513AHOSKIE
Solar/Wind Helper
0.166
961941AG1-037 GEN
Solar/Wind Helper
0.125
3145513AHOSKIE
Solar/Wind Helper
0.371
946281AF1-292 GEN
Solar/Wind Helper
0.372
3146043SEABORD
Solar/Wind Helper
0.37
3145683EARLEYS
Solar/Wind Helper
0.739
3145683EARLEYS
Solar/Wind Helper
0.37
3145683EARLEYS
Solar/Wind Helper
0.37
315607AA1-063A GEN
Solar/Wind Helper
2.105
316087AB2-174 GEN
Solar/Wind Helper
2.573
3137643SOCKMAN
Solar/Wind Helper
1.459
3145796HORNRTN
Solar/Wind Helper
1.154
3145796HORNRTN
Solar/Wind Helper
0.144
3146033SCOT NK
Solar/Wind Helper
1.436
3144303KENBRDG
Solar/Wind Helper
0.283
316239AB2-077_GEN
Solar/Wind Helper
0.469
316238AB2-078_GEN
Solar/Wind Helper
0.469
316005AA1-067
Solar/Wind Helper
0.398
3145746EVERETS
Solar/Wind Helper
1.387
3145746EVERETS
Solar/Wind Helper
0.348
3145746EVERETS
Solar/Wind Helper
0.348
3145746EVERETS
Solar/Wind Helper
0.348
3138266HYDRAULIC
Solar/Wind Helper
0.016
3138266HYDRAULIC
Solar/Wind Helper
0.01
316420AA1-050 GEN
Solar/Wind Helper
1.963
3145573BETHELC
Solar/Wind Helper
0.341
3145573BETHELC
Solar/Wind Helper
0.341
316118AC1-105 GEN
Solar/Wind Helper
1.283
3147173SINAI
Solar/Wind Helper
0.325
3147243WELCO
Solar/Wind Helper
0.203
270494AE1-108_GEN
Solar/Wind Helper
4.33
3148133STUARTS
Solar/Wind Helper
0.185
3148013FISHERV
Solar/Wind Helper
0.177
316123AC1-075 GEN
Solar/Wind Helper
1.763
270455AD2-022 GEN
Solar/Wind Helper
1.618
270457AD2-023 GEN
Solar/Wind Helper
1.066
3148463FAIRFLD
Solar/Wind Helper
0.277
238152AF2-075_GEN
Solar/Wind Helper
0.566
316222AC1-221 GEN
Solar/Wind Helper
1.724
3132123MT JACKSON
Solar/Wind Helper
0.871
270013AE1-250 PV
Solar/Wind Helper
0.915
316197AC1-042 GEN
Solar/Wind Helper
0.229
966181AG1-487 GEN
Solar/Wind Harmer
2.661
207518AF1-320_GEN
Solar/Wind Harmer
2.582
20671928W4-073
Solar/Wind Harmer
0.306
20465127PORT CT
Adder
2.119
208909MACR G3
Adder
112.881
208923BUSO V4-027
Solar/Wind Harmer
0.328
208856AE1-226 GEN
Solar/Wind Harmer
2.326
961301AF2-421 GEN
Solar/Wind Harmer
0.706
963151AG1-164 GEN
Solar/Wind Harmer
0.706
209023WIENIPP1
Adder
7.609
209025WIENIPP3
Adder
3.798
212266LOR1
Solar/Wind Harmer
0.091
970237AG2-161 GEN
Solar/Wind Harmer
2.444
961341AF2-425 GEN
Solar/Wind Harmer
0.695
212174INGE
Adder
0.769
209010PEIP 1
Adder
0.45
212507AE2-042_GEN
Solar/Wind Harmer
2.067
946731AF1-337 GEN
Solar/Wind Harmer
0.687
209071AE2-133 GEN
Solar/Wind Harmer
1.163
970665AG2-430 GEN
Solar/Wind Harmer
6.817
209018SUNBIPCT
Adder
5.117
972241AH1-705 GEN
Adder
3.981
223401AF1-299 GEN
Solar/Wind Harmer
0.492
970643AG2-418 GEN
Solar/Wind Harmer
2.077
220912PHIL G34
Adder
3.355
970679AG2-439 GEN
Solar/Wind Harmer
0.905
964991AG1-363 GEN
Solar/Wind Harmer
8.224
964991AG1-363 GEN
Solar/Wind Harmer
4.217
200917MEHOOPANY_G
Solar/Wind Harmer
3.019
316006AB2-029 C
Solar/Wind Helper
0.269
316045AC1-158 PL2
Solar/Wind Helper
9.379
316254AC1-120 GEN1
Solar/Wind Helper
2.401
3147666LOUISA
Solar/Wind Helper
1.913
316192AB2-158 GEN
Solar/Wind Helper
3.207
316337AD2-073 GEN
Solar/Wind Helper
0.678
964211AG1-282 GEN
Solar/Wind Helper
0.594
3141726DUNNSVL
Solar/Wind Helper
1.762
3142416OLDCHRC
Solar/Wind Helper
1.124
3142416OLDCHRC
Solar/Wind Helper
0.431
3138133OCRAN
Solar/Wind Helper
0.259
3141766HARMONY
Solar/Wind Helper
0.086
3143526WINTERP
Solar/Wind Helper
2.23
3142433PROV 92
Solar/Wind Helper
1.714
3143226MDLTHAN
Solar/Wind Helper
0.429
3142543TWELFTH
Solar/Wind Helper
0.041
316159AE1-175 C
Solar/Wind Helper
0.639
316458AB2-190 GEN2
Solar/Wind Helper
2.394
3145336SMITFLD
Solar/Wind Helper
1.649
316294AC1-161 GEN
Solar/Wind Helper
7.53
316381AD1-082 GEN
Solar/Wind Helper
2.124
316375AC2-012 GEN
Solar/Wind Helper
1.072
316072AD1-144
Solar/Wind Helper
0.466
316388AE2-253 GEN
Solar/Wind Helper
1.547
3146456SLIGO L269
Solar/Wind Helper
0.405
316246AF1-032 C
Solar/Wind Helper
0.463
3146516WINFALL
Solar/Wind Helper
1.291
3146516WINFALL
Solar/Wind Helper
0.398
316336AC2-165 C
Solar/Wind Helper
2.139
315800Z1-036_GEN1
Solar/Wind Helper
2.166
3130156CHOWAN
Solar/Wind Helper
0.39
3145663CRESWEL
Solar/Wind Helper
1.075
316023GEN1_S
Solar/Wind Helper
1.431
3146206CASHIE
Solar/Wind Helper
0.376
3145893MURPHYS
Solar/Wind Helper
1.5
3146173TUNIS
Solar/Wind Helper
0.372
3145683EARLEYS
Solar/Wind Helper
0.37
3146263WOODLND
Solar/Wind Helper
0.368
316322AB2-045
Solar/Wind Helper
0.407
3146776BUCKING
Solar/Wind Helper
0.146
3145963POPLR C
Solar/Wind Helper
0.365
3146926FARMVIL
Solar/Wind Helper
0.219
316011AB1-132 GEN
Solar/Wind Helper
3.925
316190AA2-174 GEN
Solar/Wind Helper
0.024
3145823KELFORD
Solar/Wind Helper
0.364
316174AB2-169 GEN
Solar/Wind Helper
0.924
3145783HORNRTN
Solar/Wind Helper
0.362
3145796HORNRTN
Solar/Wind Helper
1.19
3145796HORNRTN
Solar/Wind Helper
0.361
316212AC1-099_GEN
Solar/Wind Helper
1.591
316129AC1-054 GEN
Solar/Wind Helper
1.75
316237AB2-079_GEN
Solar/Wind Helper
0.469
3145746EVERETS
Solar/Wind Helper
0.348
3145746EVERETS
Solar/Wind Helper
0.348
315722AD1-056 GEN
Solar/Wind Helper
1.868
315687AD1-152 GEN
Solar/Wind Helper
1.86
316494AC1-189 GEN
Solar/Wind Helper
2.104
3146233WITAKRS
Solar/Wind Helper
1.357
961671AG1-007 GEN
Solar/Wind Helper
0.245
3146083TARBORO
Solar/Wind Helper
0.341
3145543BTLEBRO
Solar/Wind Helper
0.337
3145543BTLEBRO
Solar/Wind Helper
0.269
316359AB2-059 GEN
Solar/Wind Helper
2.564
316049AB1-081 GEN
Solar/Wind Helper
2.05
316003AC1-222 GEN
Solar/Wind Helper
1.377
3147983MERCK5
Solar/Wind Helper
0.114
3147123OTTER R
Solar/Wind Helper
0.15
270016AE1-250 BESS
Solar/Wind Helper
0.915
3147312GRETNA
Solar/Wind Helper
0.195
3146802CHATHAM
Solar/Wind Helper
0.183
238148AE2-230_GEN2
Solar/Wind Helper
0.398
270173AC1-122 GEN
Solar/Wind Helper
1.473
224055DICKHCT2
50/50
1.534
224056MCTRSH1G
50/50
0.532
23572401GUILF2
50/50
0.49
200200DELTA2 CT1
50/50
1.967
200193DELTA CT2
50/50
1.099
200203Y1-065-STG
50/50
4.017
200055ROCKSP 4
50/50
1.447
237030AB1-096 C
Solar/Wind Harmer
0.545
238142AE2-333 GEN2
Solar/Wind Harmer
8.044
238221AF1-254 C O1
Solar/Wind Harmer
0.963
235067AD1-061 GEN
Solar/Wind Harmer
0.782
205917AD1-020 ES
Solar/Wind Harmer
0.541
20464727HUNTR CT
Adder
3.167
966131AG1-482 GEN
Solar/Wind Harmer
2.633
232907VN8
Adder
22.102
233994AC2-023 GEN
Solar/Wind Harmer
1.978
233996TM1833_GEN
Solar/Wind Harmer
0.932
233997TMININ_4.2
Solar/Wind Harmer
0.932
232406W1-004 FULL
Solar/Wind Harmer
0.737
233940AF2-379 C
Solar/Wind Harmer
0.137
234015AF2-250 C
Solar/Wind Harmer
0.089
232914OH NUG3
Adder
6.5
232916OH NUG5
Adder
6.5
972073AH1-586 GEN
Solar/Wind Harmer
6.897
232921TASLEY2G
Adder
3.799
233900O-025 C
Adder
0.867
960671AF2-358 GEN
Solar/Wind Harmer
13.181
972133AH1-634 GEN
Solar/Wind Harmer
7.295
233990AG1-397 GEN
Solar/Wind Harmer
0.844
232417X3-008 C
Solar/Wind Harmer
1.472
233971AC1-093 C
Solar/Wind Harmer
0.577
970695AG2-447 GEN
Solar/Wind Harmer
2.635
233952AC2-187 GEN
Solar/Wind Harmer
0.828
233918AB1-142 GEN
Solar/Wind Harmer
0.729
233982AB2-133 GEN
Solar/Wind Harmer
3.581
972251AH1-710 GEN
Adder
32.735
228202CUMB CT
Adder
11.099
228711V2-041C
Solar/Wind Harmer
0.404
213497CHSTR7-9
Adder
1.837
971553AH1-274 GEN
Solar/Wind Harmer
1.628
230430AE1-229_GEN
Solar/Wind Harmer
5.915
230415AB2-049 C
Solar/Wind Harmer
0.127
228304LOGAN
Adder
14.627
228729W2-030 C
Solar/Wind Harmer
0.388
213958STHWK5-6
Adder
1.83
219623KINSLEYBEA C
Solar/Wind Harmer
0.287
219766PARADISE C
Solar/Wind Harmer
0.211
213560DLW11-12
Adder
1.826
219912AD2-042 GEN
Solar/Wind Harmer
0.534
219291REEVESSOUT C
Solar/Wind Harmer
0.04
213815MOSER1-3
Adder
2.383
219236SOUTHERNHQ C
Solar/Wind Harmer
0.045
219906AC1-017 C
Solar/Wind Harmer
0.149
219610FLORENCE C
Solar/Wind Harmer
0.927
219348LDSOLAR C
Solar/Wind Harmer
0.401
219221BRL12CT1
Adder
5.975
219223BRL12CT3
Adder
5.975
959561AF2-247 GEN
Solar/Wind Harmer
0.325
20716028EGP_W2-019
Solar/Wind Harmer
0.31
20720828JCB_W4-025
Solar/Wind Harmer
0.303
20715028HAN_X4-015
Solar/Wind Harmer
0.199
20636028O CRK C1
Adder
4.721
971667AH1-334 GEN
Solar/Wind Harmer
1.84
219727YARDVSOLFA C
Solar/Wind Harmer
0.611
219276PARKLANDSO C
Solar/Wind Harmer
0.311
20714528FRN_Y2-051
Solar/Wind Harmer
0.198
219918AC2-009 C
Solar/Wind Harmer
0.041
20716228APLW2-078
Solar/Wind Harmer
0.595
20720528MAN_W1-024
Solar/Wind Harmer
0.171
967451AG2-055 C O1
Solar/Wind Harmer
117.231
219612MATRIX C
Solar/Wind Harmer
0.124
218438BLK ROCK C
Solar/Wind Harmer
0.092
20635828PARLN1&2
Adder
2.274
20635928PARLN3&4
Adder
2.274
20635028RRCT1&2
Adder
8.004
20635128RRCT3&4
Adder
6.636
972221AH1-695 GEN
Adder
109.752
219908AB1-139 C
Solar/Wind Harmer
0.26
219919AE1-041 FULL
Solar/Wind Harmer
0.028
219249CENTRALDIV C
Solar/Wind Harmer
0.027
20673728F2S_V4-070
Solar/Wind Harmer
0.123
217211CAMDEN ST C
Solar/Wind Harmer
0.017
217186ESSEX_G9
Adder
10.977
217169METRODIV C
Solar/Wind Harmer
0.027
217194REDH C
Solar/Wind Harmer
0.338
20676728BRNX1-095
Solar/Wind Harmer
0.122
207510AF2-138 C
Solar/Wind Harmer
1.242
20674628WNG_W3-110
Solar/Wind Harmer
0.281
20633028GILCT9
Adder
20.111
966181AG1-487 GEN
Solar/Wind Harmer
0.178
971007AG2-625 GEN
Solar/Wind Harmer
1.809
20466127PORT 5CT
Adder
18.693
20465427SHAW CT
Adder
2.724
963161AG1-165 GEN
Solar/Wind Harmer
0.706
209025WIENIPP3
Adder
3.722
963071AG1-156 GEN
Solar/Wind Harmer
1.938
970095AG2-074 GEN
Solar/Wind Harmer
4.397
209027LOR2_Q27
Solar/Wind Harmer
3.183
209022WHFR IPP
Adder
2.285
961331AF2-424 GEN
Solar/Wind Harmer
0.695
961421AF2-433 GEN
Solar/Wind Harmer
0.694
957921AF2-086 GEN
Solar/Wind Harmer
0.675
209142AF1-226 GEN
Solar/Wind Harmer
4.017
209093AE2-110 GEN
Solar/Wind Harmer
1.735
209120AE2-241 GEN
Solar/Wind Harmer
2.296
972245AH1-707 GEN
Adder
3.758
946691AF1-333 GEN
Solar/Wind Harmer
0.687
946741AF1-338 GEN
Solar/Wind Harmer
0.687
209067AE2-060 GEN
Solar/Wind Harmer
1.116
223402AF1-300 C
Solar/Wind Harmer
0.492
970643AG2-418 GEN
Solar/Wind Harmer
0.966
220913PHIL G12
Adder
3.4
970999AG2-617 GEN
Solar/Wind Harmer
4.938
223203V3-037
Adder
0.305
3141196NOKESVL
Solar/Wind Helper
2.5
316044AC1-158 PL1
Solar/Wind Helper
2.93
316450AC1-158 RIC
Solar/Wind Helper
0.781
316170AC1-121 GEN2
Solar/Wind Helper
0.8
3132273ORANGE
Solar/Wind Helper
0.098
3147666LOUISA
Solar/Wind Helper
1.1
966881AG1-559 GEN
Solar/Wind Helper
0.63
3141906WESTMOR
Solar/Wind Helper
0.181
316404AE1-155 C
Solar/Wind Helper
3.701
316473AC1-191 GEN
Solar/Wind Helper
2.676
316484AD2-074 GEN
Solar/Wind Helper
0.843
316156AD2-030 GEN
Solar/Wind Helper
0.648
316280AD1-041 GEN
Solar/Wind Helper
1.443
3142946ENON
Solar/Wind Helper
0.142
316382AG1-145 C
Solar/Wind Helper
0.567
315839AE2-212 C
Solar/Wind Helper
0.56
3145336SMITFLD
Solar/Wind Helper
0.165
315773AC2-141 GEN
Solar/Wind Helper
8.863
3144536CHRHLND
Solar/Wind Helper
0.062
3144873MCLAUGH
Solar/Wind Helper
0.01
3146456SLIGO L269
Solar/Wind Helper
0.405
316313AB2-026
Solar/Wind Helper
0.615
316258AE1-075 C
Solar/Wind Helper
0.553
316405AF2-144 C
Solar/Wind Helper
0.461
316320Y1-086
Solar/Wind Helper
0.18
316435W1029_GEN3
Solar/Wind Helper
1.613
3146516WINFALL
Solar/Wind Helper
0.398
3146626S HERTFORD
Solar/Wind Helper
0.397
3145273HOLLAND
Solar/Wind Helper
0.297
3146376EDENTON
Solar/Wind Helper
0.39
315614AA2-178 GEN
Solar/Wind Helper
2.34
315737AD1-076 GEN
Solar/Wind Helper
3.697
316365GEN2_N
Solar/Wind Helper
1.431
3146206CASHIE
Solar/Wind Helper
0.376
3145893MURPHYS
Solar/Wind Helper
0.134
3145893MURPHYS
Solar/Wind Helper
0.375
3146173TUNIS
Solar/Wind Helper
0.372
3156021HOLLOMANSOL
Solar/Wind Helper
2.827
316463AE2-346 GEN
Solar/Wind Helper
0.339
316140AB2-099
Solar/Wind Helper
0.141
966621AG1-532 GEN
Solar/Wind Helper
0.337
3146263WOODLND
Solar/Wind Helper
0.368
313506AB2-031 GEN
Solar/Wind Helper
1.666
3142666NORTHAMPTON
Solar/Wind Helper
0.366
3146776BUCKING
Solar/Wind Helper
0.131
3145963POPLR C
Solar/Wind Helper
0.365
3146926FARMVIL
Solar/Wind Helper
0.219
316317KELFORD C
Solar/Wind Helper
0.31
3145823KELFORD
Solar/Wind Helper
0.364
3147043LAWRENC
Solar/Wind Helper
0.218
942461AE2-259 GEN
Solar/Wind Helper
2.436
3145796HORNRTN
Solar/Wind Helper
1.442
3145796HORNRTN
Solar/Wind Helper
0.361
316478AD1-087 GEN
Solar/Wind Helper
1.763
316486AD2-202 GEN
Solar/Wind Helper
0.516
3147133PAMPLIN
Solar/Wind Helper
1.124
316210AC1-098 GEN
Solar/Wind Helper
2.863
3145933PARMELE
Solar/Wind Helper
0.354
315785AD2-033 C
Solar/Wind Helper
4.116
316131AB2-060 GEN
Solar/Wind Helper
2.133
3145746EVERETS
Solar/Wind Helper
0.348
3145746EVERETS
Solar/Wind Helper
0.348
315724AD1-057 GEN
Solar/Wind Helper
1.027
316327AA2-057 GEN
Solar/Wind Helper
1.971
3146233WITAKRS
Solar/Wind Helper
0.367
3146233WITAKRS
Solar/Wind Helper
0.232
3146073TAR RVR
Solar/Wind Helper
0.341
3146083TARBORO
Solar/Wind Helper
0.341
3138543CONSLDL
Solar/Wind Helper
0.225
3145543BTLEBRO
Solar/Wind Helper
0.337
3145543BTLEBRO
Solar/Wind Helper
0.337
316248AF1-058 C
Solar/Wind Helper
0.437
3148013FISHERV
Solar/Wind Helper
0.309
316283AC2-100 C
Solar/Wind Helper
1.607
316499AE2-029_GEN
Solar/Wind Helper
0.977
315616AA1-038_C
Solar/Wind Helper
1.257
237061AD1-155 GEN
Solar/Wind Helper
0.05
3147312GRETNA
Solar/Wind Helper
0.049
270197AD1-017 GEN1
Solar/Wind Helper
1.297
270018AE2-047 C O1
Solar/Wind Helper
0.816
238147AE2-230_GEN1
Solar/Wind Helper
0.396
238149AF1-291A_GEN
Solar/Wind Helper
0.113
HAMLETPJM->LTFIMP_HAMLET
CLTF
6.833
G-007ALTFEXP_G-007A->PJM
CMTX
34.809
CBM NorthLTFEXP_CBM-N->PJM
CBM
58.092
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
2.861
BlueGrassPJM->LTFIMP_BlueG
CLTF
8.962
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
92.87
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.68
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
14.764

Details for AH1-727 TP-8BRAMBLETON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 9354_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-727 TP-8BRAMBLETON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 9354_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.34 %
Rating:3256.16 MVA
Rating Type:B
MVA to Mitigate:3625.26
MW Contribution:2.69
Bus #Bus NameTypeMW Contribution
23757701ROUTE 16
50/50
2.122
200035PCHBTM 3
50/50
8.711
200201DELTA2 CT2
50/50
1.461
200034PCHBTM 2
50/50
8.509
200205Y1-065-CTG2
50/50
1.722
23777201MILVL HY
50/50
0.015
235020AA1-095 C
Solar/Wind Harmer
0
23777901MDS_W4-102
Solar/Wind Harmer
0.001
237034AC2-136 C
Solar/Wind Harmer
0.001
237002AB1-128_GEN
Solar/Wind Harmer
0.001
237001AB1-127_GEN
Solar/Wind Harmer
0.001
235063AE1-101 C2
Solar/Wind Harmer
0.005
23777801MSM_W1-116
Solar/Wind Harmer
0.001
237025AB1-124 C
Solar/Wind Harmer
0.001
237006AB1-125 GEN
Solar/Wind Harmer
0.001
203982AD2-062_GEN
Solar/Wind Harmer
6.656
20390526W1-045 C
Solar/Wind Harmer
0.074
233939AC1-091 C
Solar/Wind Harmer
0.001
233970AC1-092 C
Solar/Wind Harmer
0.001
971149AH1-027 GEN
Solar/Wind Harmer
1.712
233987AB2-037 GEN
Solar/Wind Harmer
0.006
970545AG2-347 GEN
Solar/Wind Harmer
13.833
233901CHERRYDALE C
Solar/Wind Harmer
0.001
232408W1-005 C
Solar/Wind Harmer
0.355
232410W1-006 C
Solar/Wind Harmer
0.355
972069AH1-584 GEN
Solar/Wind Harmer
3.424
972071AH1-585 GEN
Solar/Wind Harmer
3.424
232899W1-062
Adder
5.27
232918OH NUG7
Adder
4.808
971747AH1-380 GEN
Solar/Wind Harmer
1.37
232905CHERITON_25
Adder
1.344
232926CRISFLD1
Adder
1.076
231940T-011
Adder
0.409
233946AB2-136 GEN
Solar/Wind Harmer
0.002
234036AF2-325 C
Solar/Wind Harmer
0
234041AC1-190 GEN
Solar/Wind Harmer
3.993
233984AB2-036 GEN
Solar/Wind Harmer
3.977
232424Y1-079 C
Solar/Wind Harmer
0
231131BLOOM ENRGY
Adder
2.382
234014AF1-036_GEN
Solar/Wind Harmer
1.271
233944AB2-135 GEN
Solar/Wind Harmer
0.003
233933AB2-153 GEN
Solar/Wind Harmer
0.001
232416X2-083
Adder
0.246
20464927ORTAN CT
Adder
2.063
205916AD1-020 GEN
Solar/Wind Harmer
0.437
228251CARLLS#4
Adder
0.317
230422AE1-104_GEN1
Solar/Wind Harmer
6.804
230425AE1-104_GEN2
Solar/Wind Harmer
6.804
228307PCLP GT
Adder
6.081
230407AD2-065 C
Solar/Wind Harmer
0
228304LOGAN
Adder
12.168
972233AH1-701 GEN
Adder
2.11
213587EDDYSTN3
Adder
40.035
213589EDDYSTN4
Adder
40.036
219921AF1-264
Solar/Wind Harmer
0
213815MOSER1-3
Adder
1.785
213815MOSER1-3
Adder
1.785
219615MILLCREEK C
Solar/Wind Harmer
0
213535CROYDN11
Adder
5.134
20716428NHV_W2-082
Solar/Wind Harmer
0
207500AE2-000G1
Solar/Wind Harmer
6.346
207497AE2-000G2
Solar/Wind Harmer
6.346
207507AE2-000G3
Solar/Wind Harmer
6.346
20636128O CRK C2
Adder
3.234
20714928UPF_X1-085
Solar/Wind Harmer
0
219114HARTZY_C
Solar/Wind Harmer
0
20628028LAKEHURS
Adder
0.479
20720628TIN_W1-124
Solar/Wind Harmer
0.001
20716928W4-060COL
Solar/Wind Harmer
0
218440SUMMTASSOC C
Solar/Wind Harmer
0
20673828FLE_V3-070
Solar/Wind Harmer
0
218418LINDEN_G5
Adder
8.844
218419LINDEN_G6
Adder
8.844
972260AH1-715 GEN1
Adder
7.082
207442AE1-156 GEN
Solar/Wind Harmer
0.031
20676128MHD_W3-029
Solar/Wind Harmer
0
219036LINDEN_G7
Adder
8.635
219035LINDEN_G8
Adder
8.512
972261AH1-715 GEN2
Adder
8.266
20464827MOUNT CT
Adder
2.082
20464827MOUNT CT
Adder
2.02
20671828STAW2-080
Solar/Wind Harmer
0
20674528F3S_W2-016
Solar/Wind Harmer
0
972237AH1-703 GEN
Adder
5.248
217086KRNY_131
Adder
4.833
217083KRNY_132
Adder
4.792
20676228FRD_X1-012
Solar/Wind Harmer
0
20674928WA_W3-044
Solar/Wind Harmer
0
20674128FR_U2-059
Solar/Wind Harmer
0
20465127PORT CT
Adder
2.132
20465527S.RDG CT
Adder
1.504
20478527GLRA_Q45
Adder
0.191
966111AG1-480 GEN
Solar/Wind Harmer
1.812
211065PSPA IPP
Solar/Wind Harmer
0
211065PSPA IPP
Solar/Wind Harmer
0
961541AF2-445A GEN
Solar/Wind Harmer
1.218
208972BECR K09
Solar/Wind Harmer
0
209054AE2-059 GEN
Solar/Wind Harmer
0.001
209059AE2-084 GEN
Solar/Wind Harmer
0.859
970761AG2-481 GEN
Solar/Wind Harmer
0.419
209029WAYMART-WD
Solar/Wind Harmer
0.001
209009PEIP 2
Adder
4.204
209010PEIP 1
Adder
1.905
209010PEIP 1
Adder
0.279
209130AF1-271A GEN
Solar/Wind Harmer
1.041
316447AC1-158 HLD
Solar/Wind Helper
7.174
315651AD1-115 GEN
Solar/Wind Helper
1.961
966001AG1-469 GEN
Solar/Wind Helper
0.541
316468AD1-105 GEN
Solar/Wind Helper
2.386
316077AC2-138 C
Solar/Wind Helper
0.439
966871AG1-558 GEN
Solar/Wind Helper
0.626
316487AF1-042 GEN
Solar/Wind Helper
0.466
316075AC2-137 C
Solar/Wind Helper
0.693
3143526WINTERP
Solar/Wind Helper
2.364
3142946ENON
Solar/Wind Helper
0.045
316240AF1-291 C
Solar/Wind Helper
0.596
316033AB2-134 GEN
Solar/Wind Helper
1.514
315697AD1-025 GEN
Solar/Wind Helper
5.03
316236AE1-162_GEN
Solar/Wind Helper
0.583
23572301GUILF1
50/50
0.368
200192DELTA CT1
50/50
0.816
200194DELTA CT3
50/50
0.816
200204Y1-065-CTG1
50/50
1.722
200054ROCKSP 3
50/50
1.098
238141AE2-333 GEN1
Solar/Wind Harmer
4.824
970651AG2-423 GEN
Solar/Wind Harmer
7.121
237080AD1-060 GEN
Solar/Wind Harmer
0.001
237038AE2-054 C
Solar/Wind Harmer
0.001
235062AE1-101 C1
Solar/Wind Harmer
0.005
23779801AA1-109
Solar/Wind Harmer
0
233972AC1-094 C
Solar/Wind Harmer
0.172
232901NORTHST
Adder
4.562
232434Z2-077 GEN
Solar/Wind Harmer
0.023
233998TM1NIN_3.36
Solar/Wind Harmer
0.001
232404W1-003 C
Solar/Wind Harmer
0.355
232428Y3-058 C
Solar/Wind Harmer
0.001
972177AH1-672 GEN
Solar/Wind Harmer
5.581
232900DEMECSMY
Adder
5.055
232917OH NUG6
Adder
4.818
232915OH NUG4
Adder
4.808
971195AH1-057 GEN
Solar/Wind Harmer
0.342
232426Y1-080 FULL
Solar/Wind Harmer
0
970277AG2-181 GEN
Solar/Wind Harmer
0.319
965821AG1-450 GEN
Solar/Wind Harmer
2.853
232919VN10
Adder
1.538
233964AF2-378 GEN
Solar/Wind Harmer
0
233954AC2-188 GEN
Solar/Wind Harmer
0.001
233950AC2-186 GEN
Solar/Wind Harmer
0
232910NRG_G1
Adder
4.727
234012AE2-112_GEN
Solar/Wind Harmer
1.271
232422X3-066 FULL
Solar/Wind Harmer
0.046
233930AB2-032 GEN
Solar/Wind Harmer
0.524
233915AB1-141 GEN
Solar/Wind Harmer
0.14
231918WEST 1
Adder
1.825
231917EM10
Adder
1.279
228206SHRMN CT
Adder
8.336
228732V1-021 C
Adder
0.095
945431AF1-208 GEN
Solar/Wind Harmer
3.029
970997AG2-616 GEN
Solar/Wind Harmer
3.628
228351V2-046C
Solar/Wind Harmer
0
230511AF1-262
Solar/Wind Harmer
0
228728W1-130C
Solar/Wind Harmer
0
230434AG1-499 GEN
Solar/Wind Harmer
0.001
205975AE2-345_GEN
Solar/Wind Harmer
4.7
213497CHSTR7-9
Adder
1.37
213497CHSTR7-9
Adder
1.37
219258KINSLEYDEP C
Solar/Wind Harmer
0
219904AC1-010 C
Solar/Wind Harmer
0
213958STHWK5-6
Adder
1.367
218660EHAMPSOLAR C
Solar/Wind Harmer
0
219287REEVESEAST C
Solar/Wind Harmer
0
219686LUMSOLAR_N C
Solar/Wind Harmer
0
213560DLW11-12
Adder
1.365
219907AC1-030 C
Solar/Wind Harmer
0
219304NAMERICA C
Solar/Wind Harmer
0.046
219222BRL12CT2
Adder
4.48
214194N WALES4
Adder
0.429
213611FALLS1-3
Adder
1.777
20720728JCB_W1-129
Solar/Wind Harmer
0
207522AF2-254 C
Solar/Wind Harmer
0.465
207487AE2-000G4
Solar/Wind Harmer
6.346
207445AB1-138_GEN
Solar/Wind Harmer
0
20628028LAKEHURS
Adder
0.948
20714828MDF_W3-079
Solar/Wind Harmer
0.05
207454AA2-184 E
Solar/Wind Harmer
0.001
20715228NPK_W1-113
Solar/Wind Harmer
0
20742028HF_AC1-207
Solar/Wind Harmer
0
217197RE CRAN C
Solar/Wind Harmer
0
20635828PARLN1&2
Adder
3.784
20635028RRCT1&2
Adder
5.942
20635128RRCT3&4
Adder
5.736
217213AMBOY SO C
Solar/Wind Harmer
0
972275AH1-722 GEN
Adder
16.258
207528AF2-192 GEN
Solar/Wind Harmer
0
20673628F1S_V4-069
Solar/Wind Harmer
0
20675428EAM_W2-061
Solar/Wind Harmer
0
20676428JCR_X2-075
Solar/Wind Harmer
0
218449LINSOLAR C
Solar/Wind Harmer
0
217083KRNY_132
Adder
4.823
217121ECCF
Adder
0.225
20674328GAR_V4-001
Solar/Wind Harmer
0
205967AE2-211_GEN
Solar/Wind Harmer
3.394
20675828AU_W4-064
Solar/Wind Harmer
0
971519AH1-257 GEN
Solar/Wind Harmer
0.869
207437AD2-070 GEN
Solar/Wind Harmer
0.035
966181AG1-487 GEN
Solar/Wind Harmer
2.053
205941AD2-115 GEN
Solar/Wind Harmer
0.065
20671928W4-073
Solar/Wind Harmer
0
20465127PORT CT
Adder
1.607
20467927PC_Q59Y356
Adder
0.475
20465527S.RDG CT
Adder
1.554
208909MACR G3
Adder
85.656
970753AG2-477 GEN
Solar/Wind Harmer
0.053
20465027TOLNA CT
Adder
2.024
209008PAXT IPP
Adder
1.197
964991AG1-363 GEN
Solar/Wind Harmer
0.001
964991AG1-363 GEN
Solar/Wind Harmer
4.225
209023WIENIPP1
Adder
5.832
209025WIENIPP3
Adder
2.911
212266LOR1
Solar/Wind Harmer
0.261
212174INGE
Adder
0.592
212507AE2-042_GEN
Solar/Wind Harmer
0.327
209010PEIP 1
Adder
0.346
209071AE2-133 GEN
Solar/Wind Harmer
0.001
970665AG2-430 GEN
Solar/Wind Harmer
3.847
209018SUNBIPCT
Adder
3.952
970757AG2-479 GEN
Solar/Wind Harmer
0.418
972241AH1-705 GEN
Adder
3.087
316006AB2-029 C
Solar/Wind Helper
0.298
316045AC1-158 PL2
Solar/Wind Helper
10.434
972285AH1-727 GEN
50/50
184.072
23572401GUILF2
50/50
0.373
200200DELTA2 CT1
50/50
1.461
200193DELTA CT2
50/50
0.816
200203Y1-065-STG
50/50
2.985
200055ROCKSP 4
50/50
1.075
238142AE2-333 GEN2
Solar/Wind Harmer
4.824
238221AF1-254 C O1
Solar/Wind Harmer
0.001
235067AD1-061 GEN
Solar/Wind Harmer
0.442
237030AB1-096 C
Solar/Wind Harmer
-0.004
233971AC1-093 C
Solar/Wind Harmer
0.024
970695AG2-447 GEN
Solar/Wind Harmer
1.37
972133AH1-634 GEN
Solar/Wind Harmer
2.02
233996TM1833_GEN
Solar/Wind Harmer
0.001
233997TMININ_4.2
Solar/Wind Harmer
0.001
232406W1-004 FULL
Solar/Wind Harmer
0.355
233940AF2-379 C
Solar/Wind Harmer
0
234015AF2-250 C
Solar/Wind Harmer
0
232907VN8
Adder
16.455
232914OH NUG3
Adder
4.84
232916OH NUG5
Adder
4.84
972073AH1-586 GEN
Solar/Wind Harmer
5.136
232921TASLEY2G
Adder
2.829
233990AG1-397 GEN
Solar/Wind Harmer
0.746
233900O-025 C
Adder
0.645
233994AC2-023 GEN
Solar/Wind Harmer
0.002
960671AF2-358 GEN
Solar/Wind Harmer
6.846
233952AC2-187 GEN
Solar/Wind Harmer
0.001
232417X3-008 C
Solar/Wind Harmer
0.001
233918AB1-142 GEN
Solar/Wind Harmer
0.14
233982AB2-133 GEN
Solar/Wind Harmer
0.002
972251AH1-710 GEN
Adder
24.445
205917AD1-020 ES
Solar/Wind Harmer
0.018
228202CUMB CT
Adder
8.306
228711V2-041C
Solar/Wind Harmer
0
971553AH1-274 GEN
Solar/Wind Harmer
0.786
20464727HUNTR CT
Adder
2.252
230430AE1-229_GEN
Solar/Wind Harmer
0.008
230415AB2-049 C
Solar/Wind Harmer
0
228729W2-030 C
Solar/Wind Harmer
0
228304LOGAN
Adder
10.944
213497CHSTR7-9
Adder
1.37
219623KINSLEYBEA C
Solar/Wind Harmer
0
219766PARADISE C
Solar/Wind Harmer
0
213958STHWK5-6
Adder
1.367
219912AD2-042 GEN
Solar/Wind Harmer
0
213560DLW11-12
Adder
1.365
213815MOSER1-3
Adder
1.785
219906AC1-017 C
Solar/Wind Harmer
0
219610FLORENCE C
Solar/Wind Harmer
0
219348LDSOLAR C
Solar/Wind Harmer
0
219221BRL12CT1
Adder
4.48
219223BRL12CT3
Adder
4.48
20716028EGP_W2-019
Solar/Wind Harmer
0
20720828JCB_W4-025
Solar/Wind Harmer
0
20715028HAN_X4-015
Solar/Wind Harmer
0
20636028O CRK C1
Adder
3.547
971667AH1-334 GEN
Solar/Wind Harmer
0.894
219727YARDVSOLFA C
Solar/Wind Harmer
0
20714528FRN_Y2-051
Solar/Wind Harmer
0
219276PARKLANDSO C
Solar/Wind Harmer
0
20716228APLW2-078
Solar/Wind Harmer
0
20720528MAN_W1-024
Solar/Wind Harmer
0
966131AG1-482 GEN
Solar/Wind Harmer
1.968
967451AG2-055 C O1
Solar/Wind Harmer
126.149
219612MATRIX C
Solar/Wind Harmer
0
218438BLK ROCK C
Solar/Wind Harmer
0
20635828PARLN1&2
Adder
1.714
20635928PARLN3&4
Adder
1.714
20635028RRCT1&2
Adder
6.035
20635128RRCT3&4
Adder
5.003
219908AB1-139 C
Solar/Wind Harmer
0
20673728F2S_V4-070
Solar/Wind Harmer
0
217186ESSEX_G9
Adder
8.294
217194REDH C
Solar/Wind Harmer
0
20676728BRNX1-095
Solar/Wind Harmer
0
207510AF2-138 C
Solar/Wind Harmer
0.001
20674628WNG_W3-110
Solar/Wind Harmer
0
971007AG2-625 GEN
Solar/Wind Harmer
0.885
972221AH1-695 GEN
Adder
81.348
20633028GILCT9
Adder
15.218
20466127PORT 5CT
Adder
14.179
970755AG2-478 GEN
Solar/Wind Harmer
0.054
20465427SHAW CT
Adder
2.07
209025WIENIPP3
Adder
2.852
963071AG1-156 GEN
Solar/Wind Harmer
0.238
970095AG2-074 GEN
Solar/Wind Harmer
2.707
209027LOR2_Q27
Solar/Wind Harmer
0.001
209022WHFR IPP
Adder
1.757
209142AF1-226 GEN
Solar/Wind Harmer
1.511
209093AE2-110 GEN
Solar/Wind Harmer
0.863
209120AE2-241 GEN
Solar/Wind Harmer
0.863
972245AH1-707 GEN
Adder
2.897
3141196NOKESVL
Solar/Wind Helper
2.668
316044AC1-158 PL1
Solar/Wind Helper
3.259
316450AC1-158 RIC
Solar/Wind Helper
0.869
316170AC1-121 GEN2
Solar/Wind Helper
0.879
3132273ORANGE
Solar/Wind Helper
0.107
3147666LOUISA
Solar/Wind Helper
1.191
966881AG1-559 GEN
Solar/Wind Helper
0.676
3141906WESTMOR
Solar/Wind Helper
0.191
316473AC1-191 GEN
Solar/Wind Helper
2.84
316404AE1-155 C
Solar/Wind Helper
3.912
316484AD2-074 GEN
Solar/Wind Helper
0.891
316280AD1-041 GEN
Solar/Wind Helper
1.526
316156AD2-030 GEN
Solar/Wind Helper
0.685
3142946ENON
Solar/Wind Helper
0.151
316382AG1-145 C
Solar/Wind Helper
0.599
315839AE2-212 C
Solar/Wind Helper
0.591
3145336SMITFLD
Solar/Wind Helper
0.174
315773AC2-141 GEN
Solar/Wind Helper
9.334
3144536CHRHLND
Solar/Wind Helper
0.065
3144873MCLAUGH
Solar/Wind Helper
0.011
3146456SLIGO L269
Solar/Wind Helper
0.426
316320Y1-086
Solar/Wind Helper
0.188
316313AB2-026
Solar/Wind Helper
0.64
316258AE1-075 C
Solar/Wind Helper
0.576
316405AF2-144 C
Solar/Wind Helper
0.48
316435W1029_GEN3
Solar/Wind Helper
1.689
3146516WINFALL
Solar/Wind Helper
0.417
3146626S HERTFORD
Solar/Wind Helper
0.415
3145273HOLLAND
Solar/Wind Helper
0.311
3146376EDENTON
Solar/Wind Helper
0.407
315614AA2-178 GEN
Solar/Wind Helper
2.432
315737AD1-076 GEN
Solar/Wind Helper
3.831
316365GEN2_N
Solar/Wind Helper
1.481
3146206CASHIE
Solar/Wind Helper
0.389
3145893MURPHYS
Solar/Wind Helper
0.139
3145893MURPHYS
Solar/Wind Helper
0.388
3146173TUNIS
Solar/Wind Helper
0.385
3156021HOLLOMANSOL
Solar/Wind Helper
2.919
316463AE2-346 GEN
Solar/Wind Helper
0.35
316140AB2-099
Solar/Wind Helper
0.146
966621AG1-532 GEN
Solar/Wind Helper
0.347
3146263WOODLND
Solar/Wind Helper
0.379
313506AB2-031 GEN
Solar/Wind Helper
1.714
3142666NORTHAMPTON
Solar/Wind Helper
0.376
3145963POPLR C
Solar/Wind Helper
0.376
316317KELFORD C
Solar/Wind Helper
0.319
3145823KELFORD
Solar/Wind Helper
0.375
3147043LAWRENC
Solar/Wind Helper
0.224
3146926FARMVIL
Solar/Wind Helper
0.223
3146776BUCKING
Solar/Wind Helper
0.133
3145796HORNRTN
Solar/Wind Helper
1.48
3145796HORNRTN
Solar/Wind Helper
0.37
316478AD1-087 GEN
Solar/Wind Helper
1.805
316486AD2-202 GEN
Solar/Wind Helper
0.528
942461AE2-259 GEN
Solar/Wind Helper
2.476
3147133PAMPLIN
Solar/Wind Helper
1.143
316210AC1-098 GEN
Solar/Wind Helper
2.927
3145933PARMELE
Solar/Wind Helper
0.361
315785AD2-033 C
Solar/Wind Helper
4.18
316131AB2-060 GEN
Solar/Wind Helper
2.165
3145746EVERETS
Solar/Wind Helper
0.355
3145746EVERETS
Solar/Wind Helper
0.355
315724AD1-057 GEN
Solar/Wind Helper
1.045
316327AA2-057 GEN
Solar/Wind Helper
2.003
3146233WITAKRS
Solar/Wind Helper
0.372
3146233WITAKRS
Solar/Wind Helper
0.235
3146073TAR RVR
Solar/Wind Helper
0.345
3146083TARBORO
Solar/Wind Helper
0.345
3138543CONSLDL
Solar/Wind Helper
0.228
3145543BTLEBRO
Solar/Wind Helper
0.34
3145543BTLEBRO
Solar/Wind Helper
0.34
316248AF1-058 C
Solar/Wind Helper
0.437
316283AC2-100 C
Solar/Wind Helper
1.577
3148013FISHERV
Solar/Wind Helper
0.287
316499AE2-029_GEN
Solar/Wind Helper
0.882
315616AA1-038_C
Solar/Wind Helper
1.121
237061AD1-155 GEN
Solar/Wind Helper
0.044
316036AC1-147 C
Solar/Wind Helper
0.656
316316AC1-027 C
Solar/Wind Helper
0.678
3142956BIRDNECK
Solar/Wind Helper
0.289
316185AD1-033 GEN
Solar/Wind Helper
2.017
3145506HICKORY
Solar/Wind Helper
1.712
3145506HICKORY
Solar/Wind Helper
1.027
3145506HICKORY
Solar/Wind Helper
0.257
316339AD2-160 GEN
Solar/Wind Helper
1.625
316018AA1-139 ULT2
Solar/Wind Helper
1.833
316017AA1-139 ULT1
Solar/Wind Helper
1.948
3137176SLIGO L2192
Solar/Wind Helper
1.694
3130086AYDLETT
Solar/Wind Helper
1.7
3146386ELIZ CT
Solar/Wind Helper
0.422
316431W1029_GEN1
Solar/Wind Helper
1.689
316433W1029_GEN2
Solar/Wind Helper
1.689
3146516WINFALL
Solar/Wind Helper
0.417
3146516WINFALL
Solar/Wind Helper
0.417
3146516WINFALL
Solar/Wind Helper
0.417
3144356SAPONY
Solar/Wind Helper
0.744
3146626S HERTFORD
Solar/Wind Helper
0.415
3146626S HERTFORD
Solar/Wind Helper
0.415
315742AE1-103 GEN
Solar/Wind Helper
0.66
3145893MURPHYS
Solar/Wind Helper
0.557
3145893MURPHYS
Solar/Wind Helper
0.698
3146173TUNIS
Solar/Wind Helper
0.385
3146173TUNIS
Solar/Wind Helper
0.385
316181AB2-040 GEN
Solar/Wind Helper
2.709
3142666NORTHAMPTON
Solar/Wind Helper
0.376
3142666NORTHAMPTON
Solar/Wind Helper
0.376
3142666NORTHAMPTON
Solar/Wind Helper
0.376
3142666NORTHAMPTON
Solar/Wind Helper
0.226
316426AA2-053 GEN
Solar/Wind Helper
2.138
3145593CAROLNA
Solar/Wind Helper
0.373
3145593CAROLNA
Solar/Wind Helper
0.373
3146776BUCKING
Solar/Wind Helper
1.48
3146776BUCKING
Solar/Wind Helper
0.12
3145796HORNRTN
Solar/Wind Helper
1.11
3147133PAMPLIN
Solar/Wind Helper
0.364
3147133PAMPLIN
Solar/Wind Helper
0.291
3145933PARMELE
Solar/Wind Helper
0.723
3145933PARMELE
Solar/Wind Helper
0.361
316274AC1-208 GEN
Solar/Wind Helper
2.196
316034AC1-036 C
Solar/Wind Helper
0.376
3146843MT LREL
Solar/Wind Helper
0.338
3146843MT LREL
Solar/Wind Helper
0.338
315821AE2-092 GEN
Solar/Wind Helper
3.06
316222AC1-221 GEN
Solar/Wind Helper
1.692
3132123MT JACKSON
Solar/Wind Helper
0.772
270013AE1-250 PV
Solar/Wind Helper
0.84
23776901DAM 5 HY
50/50
0.009
966461AG1-515 GEN
50/50
0.548
23732901CHBRG_I12
50/50
3.111
23776801DAM 4 HY
50/50
0.01
200202DELTA2 ST
50/50
2.479
200195DELTA ST
50/50
1.261
200052ROCKSP 1
50/50
1.087
200053ROCKSP 2
50/50
1.064
970279AG2-182 GEN
Solar/Wind Harmer
22.957
970429AG2-279 GEN
Solar/Wind Harmer
1.896
237085AD2-009_GEN
Solar/Wind Harmer
0.073
238208AF1-136 C
Solar/Wind Harmer
0.001
20087026C_T85_W218
Adder
0.607
233973AC2-185 C
Solar/Wind Harmer
0.001
234033AF1-007_GEN
Solar/Wind Harmer
-0.001
232432Z2-076 GEN
Solar/Wind Harmer
0.007
232904IR4
Adder
44.304
232920IR10
Adder
1.732
233923SMA
Solar/Wind Harmer
0.003
233990AG1-397 GEN
Solar/Wind Harmer
-0.087
232912OH NUG1
Adder
4.84
232913OH NUG2
Adder
4.775
233955AB2-172 GEN
Solar/Wind Harmer
0.002
232813VAUGHN
Adder
0.322
231906DC3 NUG
Adder
7.651
231902DC CT7
Adder
6.117
233968AD2-076_GEN
Solar/Wind Harmer
1.271
970597AG2-380 GEN
Solar/Wind Harmer
2.277
231907DC10
Adder
1.91
232436AB1-176 C
Solar/Wind Harmer
0
971983AH1-536 GEN
Solar/Wind Harmer
0.967
233935AB2-179 C
Solar/Wind Harmer
0.751
231919CHRIST1
Adder
2.401
231920CHRIST2
Adder
2.348
970453AG2-297 GEN
Solar/Wind Harmer
1.28
228260V4-054C
Solar/Wind Harmer
0
228309CCLP NUG
Adder
13.001
228309CCLP NUG
Adder
12.366
972141AH1-641 GEN
Solar/Wind Harmer
1.682
964001AG1-254 GEN
Solar/Wind Harmer
0.195
971011AG2-627 GEN
Solar/Wind Harmer
2.689
971535AH1-265 GEN
Solar/Wind Harmer
1.384
227927V4-067C
Solar/Wind Harmer
0
228754AB1-001 C
Solar/Wind Harmer
0
219272CLEANLIGHT C
Solar/Wind Harmer
0
213942SCHUYLKILL
Adder
1.788
213942SCHUYLKILL
Adder
1.367
213957STHWK3-4
Adder
1.367
213957STHWK3-4
Adder
1.367
219914AD2-027 C
Solar/Wind Harmer
0
203975AE1-071-GEN
Solar/Wind Harmer
0.009
219688LUMSOLAR_S C
Solar/Wind Harmer
0
213561DLWR9-10
Adder
1.786
213561DLWR9-10
Adder
1.365
219607WPEMNERT C
Solar/Wind Harmer
0
219224BRL12CT4
Adder
4.48
214067T20SOLAR
Solar/Wind Harmer
0
213611FALLS1-3
Adder
1.777
213611FALLS1-3
Adder
1.777
20717128DIX_Z2-102
Solar/Wind Harmer
0
20715728PEM_W1-119
Solar/Wind Harmer
0
20715828PEM_W1-120
Solar/Wind Harmer
0
970025AG2-016 GEN
Solar/Wind Harmer
0.92
971189AH1-054 GEN
Solar/Wind Harmer
0.383
207459AE1-142 C O1
Solar/Wind Harmer
0.001
20714328BYD_X4-031
Solar/Wind Harmer
0.077
20714428HOW_X1-037
Solar/Wind Harmer
0
20464627HAM CT
Adder
2.074
971521AH1-258 GEN
Solar/Wind Harmer
0.889
20720428HOL_W1-112
Solar/Wind Harmer
0
218455CINNBAY_CGEN
Adder
0.929
20635928PARLN3&4
Adder
3.784
218526CNTRALGAS2 C
Solar/Wind Harmer
0.393
218524CNTRALGAS1 C
Solar/Wind Harmer
0.393
218404KENILWRTH C
Adder
0.676
217167KRNY_14
Adder
4.823
217086KRNY_131
Adder
4.782
217147KRNY_1212
Adder
4.587
217147KRNY_1212
Adder
4.505
217146KRNY_1234
Adder
4.495
217146KRNY_1234
Adder
4.464
207530AG1-191 GEN
Solar/Wind Harmer
0.001
20676328BVR_Y1-020
Solar/Wind Harmer
0
207511W3-106 GEN
Solar/Wind Harmer
0.172
20674828DL_W4-046
Solar/Wind Harmer
0
20675928HOL_W4-097
Solar/Wind Harmer
0
971009AG2-626 GEN
Solar/Wind Harmer
0.564
207484AF2-139 C O1
Solar/Wind Harmer
0
207408W3-077 C
Solar/Wind Harmer
0
20675728RH_W2-091
Solar/Wind Harmer
0
20675128HRM_W1-127
Solar/Wind Harmer
0
20462827N BANGR8
Adder
0.384
20486527WR_V4-052
Adder
0.606
205943AE1-185 GEN
Solar/Wind Harmer
0.022
966421AG1-511 GEN
Solar/Wind Harmer
3.209
205956AE1-196_GEN
Solar/Wind Harmer
0.022
205932AD2-116_GEN
Solar/Wind Harmer
0.065
208862AG1-362 C
Solar/Wind Harmer
0.342
209116AE2-175 GEN
Solar/Wind Harmer
0.004
20465027TOLNA CT
Adder
2.104
960921AF2-383 GEN
Solar/Wind Harmer
1.488
209026WIENIPP4
Adder
2.882
209045AE2-271 GEN
Solar/Wind Harmer
6.257
316411AF1-147_GEN1
Solar/Wind Helper
1.969
316415AF1-147_GEN2
Solar/Wind Helper
1.969
316164AC1-076 GEN
Solar/Wind Helper
2.725
3141426STAFORD
Solar/Wind Helper
0.119
316223AC1-118
Solar/Wind Helper
0.729
3141813NORNECK
Solar/Wind Helper
0.467
316312AB1-027
Solar/Wind Helper
0.873
3141783LANCAST
Solar/Wind Helper
0.274
3141783LANCAST
Solar/Wind Helper
0.183
3138133OCRAN
Solar/Wind Helper
0.137
3141913WHIT STONE
Solar/Wind Helper
0.456
316233AE1-074 FULL
Solar/Wind Helper
0.695
316059AD1-063 C
Solar/Wind Helper
0.458
3143873LANEXA
Solar/Wind Helper
0.272
315662AE1-191 GEN
Solar/Wind Helper
2.441
315666AE1-190 GEN
Solar/Wind Helper
0.61
957601AF2-054 GEN
Solar/Wind Helper
0.609
3141873WAN 176
Solar/Wind Helper
0.091
957831AF2-077 GEN
Solar/Wind Helper
0.603
316132AB2-190 GEN1
Solar/Wind Helper
2.527
316369SG1_INVT
Solar/Wind Helper
2.117
3143316POE
Solar/Wind Helper
1.719
316349AD2-085 GEN
Solar/Wind Helper
1.951
319010AE1-072 C
Solar/Wind Helper
4.86
316305AF2-043 C
Solar/Wind Helper
0.571
313526AB2-022
Solar/Wind Helper
0.643
3146486SUNBURY
Solar/Wind Helper
0.421
3146486SUNBURY
Solar/Wind Helper
0.421
316321Z2-027
Solar/Wind Helper
0.64
3145176PASQUOTANK
Solar/Wind Helper
0.26
3138216PACIFIC
Solar/Wind Helper
0.07
316315AB2-025 C
Solar/Wind Helper
0.632
315611Z1-036_GEN2
Solar/Wind Helper
2.262
3130156CHOWAN
Solar/Wind Helper
0.407
3130156CHOWAN
Solar/Wind Helper
0.407
315816AE2-034 GEN
Solar/Wind Helper
1.824
3130546PLYMOUTH
Solar/Wind Helper
0.393
315732AD1-074 GEN1
Solar/Wind Helper
4.479
315733AD1-074 GEN2
Solar/Wind Helper
4.479
315735AD1-075 GEN1
Solar/Wind Helper
2.239
3146206CASHIE
Solar/Wind Helper
0.389
3145893MURPHYS
Solar/Wind Helper
1.047
3145893MURPHYS
Solar/Wind Helper
0.388
3145513AHOSKIE
Solar/Wind Helper
0.172
961941AG1-037 GEN
Solar/Wind Helper
0.129
3145513AHOSKIE
Solar/Wind Helper
0.383
946281AF1-292 GEN
Solar/Wind Helper
0.383
3146043SEABORD
Solar/Wind Helper
0.381
3145683EARLEYS
Solar/Wind Helper
0.762
3145683EARLEYS
Solar/Wind Helper
0.381
3145683EARLEYS
Solar/Wind Helper
0.381
315607AA1-063A GEN
Solar/Wind Helper
2.169
316087AB2-174 GEN
Solar/Wind Helper
2.65
3137643SOCKMAN
Solar/Wind Helper
1.499
3145796HORNRTN
Solar/Wind Helper
1.184
3145796HORNRTN
Solar/Wind Helper
0.148
3146033SCOT NK
Solar/Wind Helper
1.472
3144303KENBRDG
Solar/Wind Helper
0.287
316005AA1-067
Solar/Wind Helper
0.405
3145746EVERETS
Solar/Wind Helper
1.412
3145746EVERETS
Solar/Wind Helper
0.355
3145746EVERETS
Solar/Wind Helper
0.355
3145746EVERETS
Solar/Wind Helper
0.355
316239AB2-077_GEN
Solar/Wind Helper
0.476
316238AB2-078_GEN
Solar/Wind Helper
0.476
316420AA1-050 GEN
Solar/Wind Helper
1.991
3145573BETHELC
Solar/Wind Helper
0.345
3145573BETHELC
Solar/Wind Helper
0.345
3138266HYDRAULIC
Solar/Wind Helper
0.015
3138266HYDRAULIC
Solar/Wind Helper
0.01
316118AC1-105 GEN
Solar/Wind Helper
1.287
3147173SINAI
Solar/Wind Helper
0.325
3147243WELCO
Solar/Wind Helper
0.203
270494AE1-108_GEN
Solar/Wind Helper
4.233
3148133STUARTS
Solar/Wind Helper
0.172
3148013FISHERV
Solar/Wind Helper
0.165
316123AC1-075 GEN
Solar/Wind Helper
1.7
270455AD2-022 GEN
Solar/Wind Helper
1.552
270457AD2-023 GEN
Solar/Wind Helper
1.022
3148463FAIRFLD
Solar/Wind Helper
0.247
316254AC1-120 GEN1
Solar/Wind Helper
2.637
3147666LOUISA
Solar/Wind Helper
2.071
316192AB2-158 GEN
Solar/Wind Helper
3.47
316337AD2-073 GEN
Solar/Wind Helper
0.717
964211AG1-282 GEN
Solar/Wind Helper
0.628
3141726DUNNSVL
Solar/Wind Helper
1.862
3142416OLDCHRC
Solar/Wind Helper
1.192
3142416OLDCHRC
Solar/Wind Helper
0.457
3138133OCRAN
Solar/Wind Helper
0.274
3143526WINTERP
Solar/Wind Helper
2.364
3141766HARMONY
Solar/Wind Helper
0.091
3143226MDLTHAN
Solar/Wind Helper
0.454
3142433PROV 92
Solar/Wind Helper
1.813
3142543TWELFTH
Solar/Wind Helper
0.043
316159AE1-175 C
Solar/Wind Helper
0.675
316458AB2-190 GEN2
Solar/Wind Helper
2.527
3145336SMITFLD
Solar/Wind Helper
1.737
316294AC1-161 GEN
Solar/Wind Helper
7.93
316381AD1-082 GEN
Solar/Wind Helper
2.235
316375AC2-012 GEN
Solar/Wind Helper
1.127
316072AD1-144
Solar/Wind Helper
0.489
316388AE2-253 GEN
Solar/Wind Helper
1.625
3146456SLIGO L269
Solar/Wind Helper
0.426
316246AF1-032 C
Solar/Wind Helper
0.486
3146516WINFALL
Solar/Wind Helper
1.351
3146516WINFALL
Solar/Wind Helper
0.417
315800Z1-036_GEN1
Solar/Wind Helper
2.262
316336AC2-165 C
Solar/Wind Helper
2.218
3130156CHOWAN
Solar/Wind Helper
0.407
3145663CRESWEL
Solar/Wind Helper
1.117
316023GEN1_S
Solar/Wind Helper
1.481
3146206CASHIE
Solar/Wind Helper
0.389
3145893MURPHYS
Solar/Wind Helper
1.551
3146173TUNIS
Solar/Wind Helper
0.385
3145683EARLEYS
Solar/Wind Helper
0.381
3146263WOODLND
Solar/Wind Helper
0.379
3145963POPLR C
Solar/Wind Helper
0.376
316011AB1-132 GEN
Solar/Wind Helper
4.036
316190AA2-174 GEN
Solar/Wind Helper
0.025
3145823KELFORD
Solar/Wind Helper
0.375
316174AB2-169 GEN
Solar/Wind Helper
0.949
3145783HORNRTN
Solar/Wind Helper
0.371
3146926FARMVIL
Solar/Wind Helper
0.223
316322AB2-045
Solar/Wind Helper
0.413
3146776BUCKING
Solar/Wind Helper
0.148
3145796HORNRTN
Solar/Wind Helper
1.221
3145796HORNRTN
Solar/Wind Helper
0.37
316212AC1-099_GEN
Solar/Wind Helper
1.626
316129AC1-054 GEN
Solar/Wind Helper
1.784
3145746EVERETS
Solar/Wind Helper
0.355
3145746EVERETS
Solar/Wind Helper
0.355
316237AB2-079_GEN
Solar/Wind Helper
0.476
315722AD1-056 GEN
Solar/Wind Helper
1.901
315687AD1-152 GEN
Solar/Wind Helper
1.887
316494AC1-189 GEN
Solar/Wind Helper
2.137
3146233WITAKRS
Solar/Wind Helper
1.376
961671AG1-007 GEN
Solar/Wind Helper
0.248
3146083TARBORO
Solar/Wind Helper
0.345
3145543BTLEBRO
Solar/Wind Helper
0.34
3145543BTLEBRO
Solar/Wind Helper
0.272
316359AB2-059 GEN
Solar/Wind Helper
2.59
316049AB1-081 GEN
Solar/Wind Helper
2.071
316003AC1-222 GEN
Solar/Wind Helper
1.366
3147983MERCK5
Solar/Wind Helper
0.103
3147123OTTER R
Solar/Wind Helper
0.138
270016AE1-250 BESS
Solar/Wind Helper
0.84
HAMLETPJM->LTFIMP_HAMLET
CLTF
6.473
G-007ALTFEXP_G-007A->PJM
CMTX
26.244
CBM NorthLTFEXP_CBM-N->PJM
CBM
45.782
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
1.75
BlueGrassPJM->LTFIMP_BlueG
CLTF
5.516
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
70.149
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.353
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
9.941

Details for AH1-727 TP-8BRAMBLETON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 9354-9363_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-727 TP-8BRAMBLETON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 9354-9363_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:104.48 %
Rating:4192.0 MVA
Rating Type:C
MVA to Mitigate:4379.61
MW Contribution:3.91
Bus #Bus NameTypeMW Contribution
23776901DAM 5 HY
50/50
0.009
23572301GUILF1
50/50
0.366
200192DELTA CT1
50/50
0.828
200194DELTA CT3
50/50
0.828
200204Y1-065-CTG1
50/50
1.746
200054ROCKSP 3
50/50
1.114
238141AE2-333 GEN1
Solar/Wind Harmer
7.152
970651AG2-423 GEN
Solar/Wind Harmer
10.441
237080AD1-060 GEN
Solar/Wind Harmer
0.395
237038AE2-054 C
Solar/Wind Harmer
0.72
235062AE1-101 C1
Solar/Wind Harmer
1.944
23779801AA1-109
Solar/Wind Harmer
0.282
232901NORTHST
Adder
4.621
233972AC1-094 C
Solar/Wind Harmer
0.368
232434Z2-077 GEN
Solar/Wind Harmer
0.139
233998TM1NIN_3.36
Solar/Wind Harmer
0.703
232404W1-003 C
Solar/Wind Harmer
0.556
972177AH1-672 GEN
Solar/Wind Harmer
7.457
232900DEMECSMY
Adder
5.121
232917OH NUG6
Adder
4.881
232915OH NUG4
Adder
4.87
971195AH1-057 GEN
Solar/Wind Harmer
0.608
232428Y3-058 C
Solar/Wind Harmer
0.463
232919VN10
Adder
1.558
232426Y1-080 FULL
Solar/Wind Harmer
0.106
970277AG2-181 GEN
Solar/Wind Harmer
2.783
965821AG1-450 GEN
Solar/Wind Harmer
2.889
233964AF2-378 GEN
Solar/Wind Harmer
0.071
233954AC2-188 GEN
Solar/Wind Harmer
0.625
233950AC2-186 GEN
Solar/Wind Harmer
0.312
232910NRG_G1
Adder
4.787
234012AE2-112_GEN
Solar/Wind Harmer
1.274
232422X3-066 FULL
Solar/Wind Harmer
0.139
233930AB2-032 GEN
Solar/Wind Harmer
0.462
233915AB1-141 GEN
Solar/Wind Harmer
0.548
231918WEST 1
Adder
1.847
231917EM10
Adder
1.295
228206SHRMN CT
Adder
8.446
228732V1-021 C
Adder
0.096
945431AF1-208 GEN
Solar/Wind Harmer
4.398
970997AG2-616 GEN
Solar/Wind Harmer
4.885
228351V2-046C
Solar/Wind Harmer
1.027
230511AF1-262
Solar/Wind Harmer
0.093
228728W1-130C
Solar/Wind Harmer
0.339
230434AG1-499 GEN
Solar/Wind Harmer
0.296
213497CHSTR7-9
Adder
1.387
213497CHSTR7-9
Adder
1.387
219258KINSLEYDEP C
Solar/Wind Harmer
0.165
219904AC1-010 C
Solar/Wind Harmer
0.192
218660EHAMPSOLAR C
Solar/Wind Harmer
0.089
219287REEVESEAST C
Solar/Wind Harmer
0.684
219686LUMSOLAR_N C
Solar/Wind Harmer
0.103
213958STHWK5-6
Adder
1.384
219907AC1-030 C
Solar/Wind Harmer
0.071
213560DLW11-12
Adder
1.383
219304NAMERICA C
Solar/Wind Harmer
0.158
219222BRL12CT2
Adder
4.539
214194N WALES4
Adder
0.435
213611FALLS1-3
Adder
1.801
20720728JCB_W1-129
Solar/Wind Harmer
0.152
207522AF2-254 C
Solar/Wind Harmer
0.73
207487AE2-000G4
Solar/Wind Harmer
16.021
207445AB1-138_GEN
Solar/Wind Harmer
0.296
20628028LAKEHURS
Adder
0.96
963711AG1-223 GEN
Solar/Wind Harmer
0.757
20714828MDF_W3-079
Solar/Wind Harmer
0.157
219680HOPEWELLV C1
Solar/Wind Harmer
0.039
207454AA2-184 E
Solar/Wind Harmer
0.514
20715228NPK_W1-113
Solar/Wind Harmer
0.221
964991AG1-363 GEN
Solar/Wind Harmer
8.697
964991AG1-363 GEN
Solar/Wind Harmer
4.459
20742028HF_AC1-207
Solar/Wind Harmer
0.403
217197RE CRAN C
Solar/Wind Harmer
0.277
20635828PARLN1&2
Adder
3.835
20635028RRCT1&2
Adder
6.023
972285AH1-727 GEN
50/50
190.219
23572401GUILF2
50/50
0.371
200200DELTA2 CT1
50/50
1.482
200193DELTA CT2
50/50
0.828
200203Y1-065-STG
50/50
3.028
200055ROCKSP 4
50/50
1.09
238142AE2-333 GEN2
Solar/Wind Harmer
7.152
238221AF1-254 C O1
Solar/Wind Harmer
0.746
235067AD1-061 GEN
Solar/Wind Harmer
0.608
237030AB1-096 C
Solar/Wind Harmer
0.351
233971AC1-093 C
Solar/Wind Harmer
0.436
970695AG2-447 GEN
Solar/Wind Harmer
1.989
972133AH1-634 GEN
Solar/Wind Harmer
5.503
233996TM1833_GEN
Solar/Wind Harmer
0.703
233997TMININ_4.2
Solar/Wind Harmer
0.703
232406W1-004 FULL
Solar/Wind Harmer
0.556
233940AF2-379 C
Solar/Wind Harmer
0.104
234015AF2-250 C
Solar/Wind Harmer
0.067
232914OH NUG3
Adder
4.903
232916OH NUG5
Adder
4.903
972073AH1-586 GEN
Solar/Wind Harmer
5.202
232921TASLEY2G
Adder
2.865
233990AG1-397 GEN
Solar/Wind Harmer
0.637
233900O-025 C
Adder
0.654
233994AC2-023 GEN
Solar/Wind Harmer
1.492
232907VN8
Adder
16.668
960671AF2-358 GEN
Solar/Wind Harmer
9.94
233952AC2-187 GEN
Solar/Wind Harmer
0.625
232417X3-008 C
Solar/Wind Harmer
1.11
233918AB1-142 GEN
Solar/Wind Harmer
0.548
233982AB2-133 GEN
Solar/Wind Harmer
2.696
972251AH1-710 GEN
Adder
24.771
228202CUMB CT
Adder
8.416
228711V2-041C
Solar/Wind Harmer
0.306
971553AH1-274 GEN
Solar/Wind Harmer
1.234
230430AE1-229_GEN
Solar/Wind Harmer
4.484
230415AB2-049 C
Solar/Wind Harmer
0.097
228729W2-030 C
Solar/Wind Harmer
0.294
228304LOGAN
Adder
11.087
213497CHSTR7-9
Adder
1.387
219623KINSLEYBEA C
Solar/Wind Harmer
0.218
219766PARADISE C
Solar/Wind Harmer
0.16
219291REEVESSOUT C
Solar/Wind Harmer
0.031
219912AD2-042 GEN
Solar/Wind Harmer
0.405
213958STHWK5-6
Adder
1.384
219236SOUTHERNHQ C
Solar/Wind Harmer
0.034
213815MOSER1-3
Adder
1.808
213560DLW11-12
Adder
1.383
219906AC1-017 C
Solar/Wind Harmer
0.113
219610FLORENCE C
Solar/Wind Harmer
0.704
219348LDSOLAR C
Solar/Wind Harmer
0.305
219221BRL12CT1
Adder
4.539
219223BRL12CT3
Adder
4.539
959561AF2-247 GEN
Solar/Wind Harmer
0.247
20720828JCB_W4-025
Solar/Wind Harmer
0.23
20716028EGP_W2-019
Solar/Wind Harmer
0.236
20715028HAN_X4-015
Solar/Wind Harmer
0.152
20636028O CRK C1
Adder
3.595
971667AH1-334 GEN
Solar/Wind Harmer
1.402
219727YARDVSOLFA C
Solar/Wind Harmer
0.465
20714528FRN_Y2-051
Solar/Wind Harmer
0.151
219276PARKLANDSO C
Solar/Wind Harmer
0.237
219918AC2-009 C
Solar/Wind Harmer
0.032
20716228APLW2-078
Solar/Wind Harmer
0.454
20720528MAN_W1-024
Solar/Wind Harmer
0.131
967451AG2-055 C O1
Solar/Wind Harmer
89.507
219612MATRIX C
Solar/Wind Harmer
0.095
218438BLK ROCK C
Solar/Wind Harmer
0.07
20635828PARLN1&2
Adder
1.737
20635928PARLN3&4
Adder
1.737
20635028RRCT1&2
Adder
6.117
20635128RRCT3&4
Adder
5.071
205917AD1-020 ES
Solar/Wind Harmer
0.377
219908AB1-139 C
Solar/Wind Harmer
0.198
219249CENTRALDIV C
Solar/Wind Harmer
0.021
219919AE1-041 FULL
Solar/Wind Harmer
0.021
966461AG1-515 GEN
50/50
0.544
23776801DAM 4 HY
50/50
0.011
23732901CHBRG_I12
50/50
3.079
200202DELTA2 ST
50/50
2.514
200195DELTA ST
50/50
1.279
200052ROCKSP 1
50/50
1.103
200053ROCKSP 2
50/50
1.079
970279AG2-182 GEN
Solar/Wind Harmer
29.059
970429AG2-279 GEN
Solar/Wind Harmer
2.535
237085AD2-009_GEN
Solar/Wind Harmer
1.718
238208AF1-136 C
Solar/Wind Harmer
0.551
959381AF2-229 GEN
Solar/Wind Harmer
0.731
233973AC2-185 C
Solar/Wind Harmer
2.006
234033AF1-007_GEN
Solar/Wind Harmer
12.979
232432Z2-076 GEN
Solar/Wind Harmer
0.073
232904IR4
Adder
44.879
232920IR10
Adder
1.754
233923SMA
Solar/Wind Harmer
2.578
233990AG1-397 GEN
Solar/Wind Harmer
0.031
232912OH NUG1
Adder
4.903
232913OH NUG2
Adder
4.837
233955AB2-172 GEN
Solar/Wind Harmer
2.775
232813VAUGHN
Adder
0.327
231906DC3 NUG
Adder
7.748
231902DC CT7
Adder
6.194
231907DC10
Adder
1.934
233968AD2-076_GEN
Solar/Wind Harmer
3.672
970597AG2-380 GEN
Solar/Wind Harmer
2.306
232436AB1-176 C
Solar/Wind Harmer
0.127
971983AH1-536 GEN
Solar/Wind Harmer
4.142
233935AB2-179 C
Solar/Wind Harmer
1.38
231919CHRIST1
Adder
2.431
231920CHRIST2
Adder
2.377
20087026C_T85_W218
Adder
0.604
970453AG2-297 GEN
Solar/Wind Harmer
1.406
228260V4-054C
Solar/Wind Harmer
0.523
228309CCLP NUG
Adder
13.172
228309CCLP NUG
Adder
12.529
972141AH1-641 GEN
Solar/Wind Harmer
1.466
964001AG1-254 GEN
Solar/Wind Harmer
1.036
971011AG2-627 GEN
Solar/Wind Harmer
3.906
971535AH1-265 GEN
Solar/Wind Harmer
2.169
227927V4-067C
Solar/Wind Harmer
0.101
228754AB1-001 C
Solar/Wind Harmer
0.071
219137THOSOLAR C
Solar/Wind Harmer
0.615
219272CLEANLIGHT C
Solar/Wind Harmer
0.093
219914AD2-027 C
Solar/Wind Harmer
0.305
219688LUMSOLAR_S C
Solar/Wind Harmer
0.103
213942SCHUYLKILL
Adder
1.81
213942SCHUYLKILL
Adder
1.384
213957STHWK3-4
Adder
1.384
213957STHWK3-4
Adder
1.384
213561DLWR9-10
Adder
1.808
213561DLWR9-10
Adder
1.383
219607WPEMNERT C
Solar/Wind Harmer
0.213
219224BRL12CT4
Adder
4.539
214067T20SOLAR
Solar/Wind Harmer
0.129
213611FALLS1-3
Adder
1.801
213611FALLS1-3
Adder
1.801
20717128DIX_Z2-102
Solar/Wind Harmer
0.671
20715728PEM_W1-119
Solar/Wind Harmer
0.272
20715828PEM_W1-120
Solar/Wind Harmer
0.272
970025AG2-016 GEN
Solar/Wind Harmer
1.443
971189AH1-054 GEN
Solar/Wind Harmer
0.601
207459AE1-142 C O1
Solar/Wind Harmer
0.538
219620RIDERU C
Solar/Wind Harmer
0.029
20714328BYD_X4-031
Solar/Wind Harmer
0.145
20714428HOW_X1-037
Solar/Wind Harmer
0.634
971521AH1-258 GEN
Solar/Wind Harmer
1.394
20720428HOL_W1-112
Solar/Wind Harmer
0.178
203975AE1-071-GEN
Solar/Wind Harmer
2.678
20635928PARLN3&4
Adder
3.835
218455CINNBAY_CGEN
Adder
0.942
218526CNTRALGAS2 C
Solar/Wind Harmer
0.193
20675528CPH_W2-050
Solar/Wind Harmer
0.244
218524CNTRALGAS1 C
Solar/Wind Harmer
0.193
218404KENILWRTH C
Adder
0.686
217167KRNY_14
Adder
4.889
217086KRNY_131
Adder
4.847
217147KRNY_1212
Adder
4.65
217147KRNY_1212
Adder
4.567
217146KRNY_1234
Adder
4.557
217146KRNY_1234
Adder
4.526
966261AG1-495 GEN
Solar/Wind Harmer
0.957
20676328BVR_Y1-020
Solar/Wind Harmer
0.177
207530AG1-191 GEN
Solar/Wind Harmer
0.738
207511W3-106 GEN
Solar/Wind Harmer
0.351
20674828DL_W4-046
Solar/Wind Harmer
0.348
20675928HOL_W4-097
Solar/Wind Harmer
0.071
971009AG2-626 GEN
Solar/Wind Harmer
0.886
207484AF2-139 C O1
Solar/Wind Harmer
0.275
207408W3-077 C
Solar/Wind Harmer
0.275
20675728RH_W2-091
Solar/Wind Harmer
0.185
20675128HRM_W1-127
Solar/Wind Harmer
0.093
20464627HAM CT
Adder
2.05
20462827N BANGR8
Adder
0.389
966421AG1-511 GEN
Solar/Wind Harmer
4.663
20486527WR_V4-052
Adder
0.611
209116AE2-175 GEN
Solar/Wind Harmer
2.247
208862AG1-362 C
Solar/Wind Harmer
0.462
205951AE1-129_GEN
Solar/Wind Harmer
7.222
205943AE1-185 GEN
Solar/Wind Harmer
0.512
205956AE1-196_GEN
Solar/Wind Harmer
0.51
205932AD2-116_GEN
Solar/Wind Harmer
0.51
960921AF2-383 GEN
Solar/Wind Harmer
0.17
20465027TOLNA CT
Adder
2.09
960921AF2-383 GEN
Solar/Wind Harmer
1.308
209026WIENIPP4
Adder
2.925
961261AF2-417 GEN
Solar/Wind Harmer
0.547
209045AE2-271 GEN
Solar/Wind Harmer
9.101
23757701ROUTE 16
50/50
2.12
970445AG2-288 GEN
50/50
18.737
200035PCHBTM 3
50/50
8.841
200201DELTA2 CT2
50/50
1.482
200034PCHBTM 2
50/50
8.631
200205Y1-065-CTG2
50/50
1.746
23777201MILVL HY
50/50
0.015
235020AA1-095 C
Solar/Wind Harmer
0.173
23777901MDS_W4-102
Solar/Wind Harmer
1.037
237034AC2-136 C
Solar/Wind Harmer
0.432
237002AB1-128_GEN
Solar/Wind Harmer
0.523
237001AB1-127_GEN
Solar/Wind Harmer
0.522
235063AE1-101 C2
Solar/Wind Harmer
1.944
23777801MSM_W1-116
Solar/Wind Harmer
0.631
237025AB1-124 C
Solar/Wind Harmer
0.869
237006AB1-125 GEN
Solar/Wind Harmer
0.651
203982AD2-062_GEN
Solar/Wind Harmer
8.724
20390526W1-045 C
Solar/Wind Harmer
0.377
971149AH1-027 GEN
Solar/Wind Harmer
1.879
233939AC1-091 C
Solar/Wind Harmer
0.488
233970AC1-092 C
Solar/Wind Harmer
0.488
233987AB2-037 GEN
Solar/Wind Harmer
6.319
970545AG2-347 GEN
Solar/Wind Harmer
36.322
233901CHERRYDALE C
Solar/Wind Harmer
0.625
232408W1-005 C
Solar/Wind Harmer
0.556
232410W1-006 C
Solar/Wind Harmer
0.556
972069AH1-584 GEN
Solar/Wind Harmer
4.971
972071AH1-585 GEN
Solar/Wind Harmer
4.971
232899W1-062
Adder
5.339
232918OH NUG7
Adder
4.87
971747AH1-380 GEN
Solar/Wind Harmer
1.988
232905CHERITON_25
Adder
1.362
232926CRISFLD1
Adder
1.089
231940T-011
Adder
0.414
233946AB2-136 GEN
Solar/Wind Harmer
2.215
234036AF2-325 C
Solar/Wind Harmer
0.509
234041AC1-190 GEN
Solar/Wind Harmer
4.969
233984AB2-036 GEN
Solar/Wind Harmer
6.901
232424Y1-079 C
Solar/Wind Harmer
0.312
231131BLOOM ENRGY
Adder
2.412
234014AF1-036_GEN
Solar/Wind Harmer
1.499
233944AB2-135 GEN
Solar/Wind Harmer
2.9
233933AB2-153 GEN
Solar/Wind Harmer
0.623
232416X2-083
Adder
0.249
228251CARLLS#4
Adder
0.321
230433AD2-135 GEN
Solar/Wind Harmer
0.051
230422AE1-104_GEN1
Solar/Wind Harmer
17.172
230425AE1-104_GEN2
Solar/Wind Harmer
17.172
228307PCLP GT
Adder
6.161
230407AD2-065 C
Solar/Wind Harmer
0.067
228304LOGAN
Adder
12.327
972233AH1-701 GEN
Adder
2.137
213587EDDYSTN3
Adder
40.528
213589EDDYSTN4
Adder
40.529
219921AF1-264
Solar/Wind Harmer
0.074
213815MOSER1-3
Adder
1.808
213815MOSER1-3
Adder
1.808
219615MILLCREEK C
Solar/Wind Harmer
0.121
213535CROYDN11
Adder
5.202
20716428NHV_W2-082
Solar/Wind Harmer
0.904
207500AE2-000G1
Solar/Wind Harmer
16.021
207497AE2-000G2
Solar/Wind Harmer
16.021
207507AE2-000G3
Solar/Wind Harmer
16.021
20636128O CRK C2
Adder
3.278
963401AG1-189 GEN
Solar/Wind Harmer
0.585
963391AG1-188 GEN
Solar/Wind Harmer
0.977
20714928UPF_X1-085
Solar/Wind Harmer
0.207
219114HARTZY_C
Solar/Wind Harmer
0.426
20628028LAKEHURS
Adder
0.485
219817TRENTONSOL C
Solar/Wind Harmer
0.566
20641628MLH_W1-032
Solar/Wind Harmer
0.151
20720628TIN_W1-124
Solar/Wind Harmer
0.512
20716928W4-060COL
Solar/Wind Harmer
0.367
924131AB2-057 GEN
Solar/Wind Harmer
0.533
20464927ORTAN CT
Adder
2.027
218440SUMMTASSOC C
Solar/Wind Harmer
0.067
205916AD1-020 GEN
Solar/Wind Harmer
1.754
20673828FLE_V3-070
Solar/Wind Harmer
0.239
218418LINDEN_G5
Adder
8.965
218419LINDEN_G6
Adder
8.965
972260AH1-715 GEN1
Adder
7.179
207442AE1-156 GEN
Solar/Wind Harmer
0.39
20676128MHD_W3-029
Solar/Wind Harmer
0.25
219036LINDEN_G7
Adder
8.754
219035LINDEN_G8
Adder
8.629
972261AH1-715 GEN2
Adder
8.38
217081WEATEXAS C
Solar/Wind Harmer
0.045
20671828STAW2-080
Solar/Wind Harmer
0.055
217202FBANKSOLAR C
Solar/Wind Harmer
0.039
20674528F3S_W2-016
Solar/Wind Harmer
0.744
217201HACKENSOLA C
Solar/Wind Harmer
0.039
972237AH1-703 GEN
Adder
5.321
217206BARNGR HS C
Solar/Wind Harmer
0.016
217086KRNY_131
Adder
4.899
217083KRNY_132
Adder
4.858
217204WCALDSOLAR C
Solar/Wind Harmer
0.039
20676228FRD_X1-012
Solar/Wind Harmer
0.317
207471AF2-354 C
Solar/Wind Harmer
0.276
20674928WA_W3-044
Solar/Wind Harmer
0.26
964851AG1-348 GEN
Solar/Wind Harmer
0.95
20634528N27_Y2-018
Solar/Wind Harmer
0.145
20674128FR_U2-059
Solar/Wind Harmer
0.1
20465127PORT CT
Adder
2.161
20464827MOUNT CT
Adder
2.073
20464827MOUNT CT
Adder
2.012
966111AG1-480 GEN
Solar/Wind Harmer
0.047
966111AG1-480 GEN
Solar/Wind Harmer
1.791
20465527S.RDG CT
Adder
1.517
211065PSPA IPP
Solar/Wind Harmer
0.248
211065PSPA IPP
Solar/Wind Harmer
0.248
20478527GLRA_Q45
Adder
0.192
961541AF2-445A GEN
Solar/Wind Harmer
1.784
208972BECR K09
Solar/Wind Harmer
0.579
961431AF2-434 GEN
Solar/Wind Harmer
0.543
209054AE2-059 GEN
Solar/Wind Harmer
0.914
209059AE2-084 GEN
Solar/Wind Harmer
1.35
946751AF1-339 GEN
Solar/Wind Harmer
0.539
209029WAYMART-WD
Solar/Wind Harmer
1.572
209009PEIP 2
Adder
4.269
209010PEIP 1
Adder
1.934
209010PEIP 1
Adder
0.283
209130AF1-271A GEN
Solar/Wind Harmer
1.515
316447AC1-158 HLD
Solar/Wind Helper
7.361
315651AD1-115 GEN
Solar/Wind Helper
2.014
966001AG1-469 GEN
Solar/Wind Helper
0.555
316468AD1-105 GEN
Solar/Wind Helper
2.466
316077AC2-138 C
Solar/Wind Helper
0.454
966871AG1-558 GEN
Solar/Wind Helper
0.645
316487AF1-042 GEN
Solar/Wind Helper
0.481
316075AC2-137 C
Solar/Wind Helper
0.713
3143526WINTERP
Solar/Wind Helper
2.432
3142946ENON
Solar/Wind Helper
0.047
316240AF1-291 C
Solar/Wind Helper
0.613
316033AB2-134 GEN
Solar/Wind Helper
1.557
315697AD1-025 GEN
Solar/Wind Helper
5.174
316236AE1-162_GEN
Solar/Wind Helper
0.6
316036AC1-147 C
Solar/Wind Helper
0.674
316316AC1-027 C
Solar/Wind Helper
0.697
3142956BIRDNECK
Solar/Wind Helper
0.297
316185AD1-033 GEN
Solar/Wind Helper
2.073
3145506HICKORY
Solar/Wind Helper
1.76
3145506HICKORY
Solar/Wind Helper
1.056
3145506HICKORY
Solar/Wind Helper
0.264
316339AD2-160 GEN
Solar/Wind Helper
1.67
316018AA1-139 ULT2
Solar/Wind Helper
1.884
316017AA1-139 ULT1
Solar/Wind Helper
2.002
3137176SLIGO L2192
Solar/Wind Helper
1.741
3130086AYDLETT
Solar/Wind Helper
1.748
3146386ELIZ CT
Solar/Wind Helper
0.434
316431W1029_GEN1
Solar/Wind Helper
1.736
316433W1029_GEN2
Solar/Wind Helper
1.736
3146516WINFALL
Solar/Wind Helper
0.429
3146516WINFALL
Solar/Wind Helper
0.429
3146516WINFALL
Solar/Wind Helper
0.429
3144356SAPONY
Solar/Wind Helper
0.765
3146626S HERTFORD
Solar/Wind Helper
0.426
3146626S HERTFORD
Solar/Wind Helper
0.426
315742AE1-103 GEN
Solar/Wind Helper
0.678
3145893MURPHYS
Solar/Wind Helper
0.571
3145893MURPHYS
Solar/Wind Helper
0.717
3146173TUNIS
Solar/Wind Helper
0.395
3146173TUNIS
Solar/Wind Helper
0.395
316181AB2-040 GEN
Solar/Wind Helper
2.78
3142666NORTHAMPTON
Solar/Wind Helper
0.386
3142666NORTHAMPTON
Solar/Wind Helper
0.386
3142666NORTHAMPTON
Solar/Wind Helper
0.386
3142666NORTHAMPTON
Solar/Wind Helper
0.231
316426AA2-053 GEN
Solar/Wind Helper
2.193
3145593CAROLNA
Solar/Wind Helper
0.383
3145593CAROLNA
Solar/Wind Helper
0.383
3145796HORNRTN
Solar/Wind Helper
1.138
3146776BUCKING
Solar/Wind Helper
1.517
3146776BUCKING
Solar/Wind Helper
0.123
3147133PAMPLIN
Solar/Wind Helper
0.373
3147133PAMPLIN
Solar/Wind Helper
0.298
3145933PARMELE
Solar/Wind Helper
0.741
3145933PARMELE
Solar/Wind Helper
0.371
316274AC1-208 GEN
Solar/Wind Helper
2.253
316034AC1-036 C
Solar/Wind Helper
0.386
3146843MT LREL
Solar/Wind Helper
0.346
3146843MT LREL
Solar/Wind Helper
0.346
315821AE2-092 GEN
Solar/Wind Helper
3.127
316222AC1-221 GEN
Solar/Wind Helper
1.73
3132123MT JACKSON
Solar/Wind Helper
0.781
270013AE1-250 PV
Solar/Wind Helper
0.854
316197AC1-042 GEN
Solar/Wind Helper
0.21
959431AF2-234 GEN
Solar/Wind Harmer
1.078
964051AG1-259 GEN
Solar/Wind Harmer
0.723
964061AG1-260 GEN
Solar/Wind Harmer
0.723
959421AF2-233 GEN
Solar/Wind Harmer
0.539
316411AF1-147_GEN1
Solar/Wind Helper
2.156
316415AF1-147_GEN2
Solar/Wind Helper
2.156
316164AC1-076 GEN
Solar/Wind Helper
2.799
3141426STAFORD
Solar/Wind Helper
0.124
3138216PACIFIC
Solar/Wind Helper
0.084
316223AC1-118
Solar/Wind Helper
0.754
3141813NORNECK
Solar/Wind Helper
0.482
316312AB1-027
Solar/Wind Helper
0.899
3141783LANCAST
Solar/Wind Helper
0.283
3141783LANCAST
Solar/Wind Helper
0.189
3138133OCRAN
Solar/Wind Helper
0.141
3141913WHIT STONE
Solar/Wind Helper
0.47
316059AD1-063 C
Solar/Wind Helper
0.472
957601AF2-054 GEN
Solar/Wind Helper
0.628
3141873WAN 176
Solar/Wind Helper
0.094
315662AE1-191 GEN
Solar/Wind Helper
2.515
315666AE1-190 GEN
Solar/Wind Helper
0.629
3143873LANEXA
Solar/Wind Helper
0.281
316233AE1-074 FULL
Solar/Wind Helper
0.714
957831AF2-077 GEN
Solar/Wind Helper
0.621
316132AB2-190 GEN1
Solar/Wind Helper
2.599
316369SG1_INVT
Solar/Wind Helper
2.177
3143316POE
Solar/Wind Helper
1.767
316349AD2-085 GEN
Solar/Wind Helper
2.005
319010AE1-072 C
Solar/Wind Helper
4.995
316305AF2-043 C
Solar/Wind Helper
0.587
20635128RRCT3&4
Adder
5.814
218428ETC SOLAR C
Solar/Wind Harmer
0.019
217213AMBOY SO C
Solar/Wind Harmer
0.066
972275AH1-722 GEN
Adder
16.481
207528AF2-192 GEN
Solar/Wind Harmer
0.29
20673628F1S_V4-069
Solar/Wind Harmer
0.094
20675428EAM_W2-061
Solar/Wind Harmer
0.099
20676428JCR_X2-075
Solar/Wind Harmer
0.179
218449LINSOLAR C
Solar/Wind Harmer
0.526
205975AE2-345_GEN
Solar/Wind Harmer
6.638
217209CENTRL HS C
Solar/Wind Harmer
0.023
217083KRNY_132
Adder
4.889
217121ECCF
Adder
0.228
217208PARK ELE C
Solar/Wind Harmer
0.013
20674328GAR_V4-001
Solar/Wind Harmer
0.059
207439AE1-081 C O1
Solar/Wind Harmer
0.032
20675828AU_W4-064
Solar/Wind Harmer
0.093
971519AH1-257 GEN
Solar/Wind Harmer
1.364
207437AD2-070 GEN
Solar/Wind Harmer
0.164
207518AF1-320_GEN
Solar/Wind Harmer
1.982
966181AG1-487 GEN
Solar/Wind Harmer
2.041
20671928W4-073
Solar/Wind Harmer
0.235
966131AG1-482 GEN
Solar/Wind Harmer
0.084
20465127PORT CT
Adder
1.629
205941AD2-115 GEN
Solar/Wind Harmer
0.522
208909MACR G3
Adder
86.844
20467927PC_Q59Y356
Adder
0.479
20465527S.RDG CT
Adder
1.568
205967AE2-211_GEN
Solar/Wind Harmer
5.241
209008PAXT IPP
Adder
1.205
20465027TOLNA CT
Adder
2.01
961301AF2-421 GEN
Solar/Wind Harmer
0.549
963151AG1-164 GEN
Solar/Wind Harmer
0.549
209023WIENIPP1
Adder
5.919
209025WIENIPP3
Adder
2.954
212266LOR1
Solar/Wind Harmer
0.071
970237AG2-161 GEN
Solar/Wind Harmer
1.908
961341AF2-425 GEN
Solar/Wind Harmer
0.543
212174INGE
Adder
0.601
212507AE2-042_GEN
Solar/Wind Harmer
1.62
946731AF1-337 GEN
Solar/Wind Harmer
0.539
209010PEIP 1
Adder
0.352
209071AE2-133 GEN
Solar/Wind Harmer
0.913
970665AG2-430 GEN
Solar/Wind Harmer
5.347
209018SUNBIPCT
Adder
4.014
972241AH1-705 GEN
Adder
3.136
316006AB2-029 C
Solar/Wind Helper
0.306
316045AC1-158 PL2
Solar/Wind Helper
10.706
316254AC1-120 GEN1
Solar/Wind Helper
2.707
3147666LOUISA
Solar/Wind Helper
2.126
316192AB2-158 GEN
Solar/Wind Helper
3.563
316337AD2-073 GEN
Solar/Wind Helper
0.741
964211AG1-282 GEN
Solar/Wind Helper
0.648
3141726DUNNSVL
Solar/Wind Helper
1.923
3142416OLDCHRC
Solar/Wind Helper
1.227
3142416OLDCHRC
Solar/Wind Helper
0.47
3138133OCRAN
Solar/Wind Helper
0.282
3141766HARMONY
Solar/Wind Helper
0.094
3143526WINTERP
Solar/Wind Helper
2.432
3143226MDLTHAN
Solar/Wind Helper
0.467
3142433PROV 92
Solar/Wind Helper
1.867
3142543TWELFTH
Solar/Wind Helper
0.045
316159AE1-175 C
Solar/Wind Helper
0.695
316458AB2-190 GEN2
Solar/Wind Helper
2.599
3145336SMITFLD
Solar/Wind Helper
1.786
316294AC1-161 GEN
Solar/Wind Helper
8.153
316381AD1-082 GEN
Solar/Wind Helper
2.297
316375AC2-012 GEN
Solar/Wind Helper
1.159
316072AD1-144
Solar/Wind Helper
0.503
316388AE2-253 GEN
Solar/Wind Helper
1.67
3146456SLIGO L269
Solar/Wind Helper
0.437
316246AF1-032 C
Solar/Wind Helper
0.499
3146516WINFALL
Solar/Wind Helper
1.388
3146516WINFALL
Solar/Wind Helper
0.429
315800Z1-036_GEN1
Solar/Wind Helper
2.324
316336AC2-165 C
Solar/Wind Helper
2.276
3130156CHOWAN
Solar/Wind Helper
0.418
3145663CRESWEL
Solar/Wind Helper
1.148
316023GEN1_S
Solar/Wind Helper
1.52
3146206CASHIE
Solar/Wind Helper
0.399
3145893MURPHYS
Solar/Wind Helper
1.593
3146173TUNIS
Solar/Wind Helper
0.395
3145683EARLEYS
Solar/Wind Helper
0.391
3146263WOODLND
Solar/Wind Helper
0.389
3145963POPLR C
Solar/Wind Helper
0.386
316011AB1-132 GEN
Solar/Wind Helper
4.142
316190AA2-174 GEN
Solar/Wind Helper
0.026
3145823KELFORD
Solar/Wind Helper
0.384
316174AB2-169 GEN
Solar/Wind Helper
0.974
3145783HORNRTN
Solar/Wind Helper
0.381
3146926FARMVIL
Solar/Wind Helper
0.228
3145796HORNRTN
Solar/Wind Helper
1.252
3145796HORNRTN
Solar/Wind Helper
0.38
316322AB2-045
Solar/Wind Helper
0.423
3146776BUCKING
Solar/Wind Helper
0.152
316212AC1-099_GEN
Solar/Wind Helper
1.668
316129AC1-054 GEN
Solar/Wind Helper
1.829
3145746EVERETS
Solar/Wind Helper
0.364
3145746EVERETS
Solar/Wind Helper
0.364
316237AB2-079_GEN
Solar/Wind Helper
0.488
315722AD1-056 GEN
Solar/Wind Helper
1.949
315687AD1-152 GEN
Solar/Wind Helper
1.934
316494AC1-189 GEN
Solar/Wind Helper
2.191
3146233WITAKRS
Solar/Wind Helper
1.41
961671AG1-007 GEN
Solar/Wind Helper
0.254
3146083TARBORO
Solar/Wind Helper
0.354
3145543BTLEBRO
Solar/Wind Helper
0.348
3145543BTLEBRO
Solar/Wind Helper
0.279
316359AB2-059 GEN
Solar/Wind Helper
2.654
316049AB1-081 GEN
Solar/Wind Helper
2.122
316003AC1-222 GEN
Solar/Wind Helper
1.398
3147983MERCK5
Solar/Wind Helper
0.104
3147123OTTER R
Solar/Wind Helper
0.14
270016AE1-250 BESS
Solar/Wind Helper
0.854
3147312GRETNA
Solar/Wind Helper
0.179
3146802CHATHAM
Solar/Wind Helper
0.168
313526AB2-022
Solar/Wind Helper
0.66
3146486SUNBURY
Solar/Wind Helper
0.433
3146486SUNBURY
Solar/Wind Helper
0.433
316321Z2-027
Solar/Wind Helper
0.658
3145176PASQUOTANK
Solar/Wind Helper
0.268
316315AB2-025 C
Solar/Wind Helper
0.649
315611Z1-036_GEN2
Solar/Wind Helper
2.324
3130156CHOWAN
Solar/Wind Helper
0.418
3130156CHOWAN
Solar/Wind Helper
0.418
315816AE2-034 GEN
Solar/Wind Helper
1.873
3130546PLYMOUTH
Solar/Wind Helper
0.404
315732AD1-074 GEN1
Solar/Wind Helper
4.599
315733AD1-074 GEN2
Solar/Wind Helper
4.599
315735AD1-075 GEN1
Solar/Wind Helper
2.299
3146206CASHIE
Solar/Wind Helper
0.399
3145893MURPHYS
Solar/Wind Helper
1.075
3145893MURPHYS
Solar/Wind Helper
0.398
3145513AHOSKIE
Solar/Wind Helper
0.176
961941AG1-037 GEN
Solar/Wind Helper
0.132
3145513AHOSKIE
Solar/Wind Helper
0.393
946281AF1-292 GEN
Solar/Wind Helper
0.393
3146043SEABORD
Solar/Wind Helper
0.391
3145683EARLEYS
Solar/Wind Helper
0.782
3145683EARLEYS
Solar/Wind Helper
0.391
3145683EARLEYS
Solar/Wind Helper
0.391
315607AA1-063A GEN
Solar/Wind Helper
2.226
316087AB2-174 GEN
Solar/Wind Helper
2.719
3137643SOCKMAN
Solar/Wind Helper
1.539
3145796HORNRTN
Solar/Wind Helper
1.214
3145796HORNRTN
Solar/Wind Helper
0.152
3146033SCOT NK
Solar/Wind Helper
1.51
3144303KENBRDG
Solar/Wind Helper
0.295
316005AA1-067
Solar/Wind Helper
0.416
3145746EVERETS
Solar/Wind Helper
1.448
3145746EVERETS
Solar/Wind Helper
0.364
3145746EVERETS
Solar/Wind Helper
0.364
3145746EVERETS
Solar/Wind Helper
0.364
316239AB2-077_GEN
Solar/Wind Helper
0.488
316238AB2-078_GEN
Solar/Wind Helper
0.488
316420AA1-050 GEN
Solar/Wind Helper
2.041
3145573BETHELC
Solar/Wind Helper
0.354
3145573BETHELC
Solar/Wind Helper
0.354
3138266HYDRAULIC
Solar/Wind Helper
0.016
3138266HYDRAULIC
Solar/Wind Helper
0.01
316118AC1-105 GEN
Solar/Wind Helper
1.317
3147173SINAI
Solar/Wind Helper
0.333
3147243WELCO
Solar/Wind Helper
0.208
270494AE1-108_GEN
Solar/Wind Helper
4.325
3148133STUARTS
Solar/Wind Helper
0.175
3148013FISHERV
Solar/Wind Helper
0.168
316123AC1-075 GEN
Solar/Wind Helper
1.736
270455AD2-022 GEN
Solar/Wind Helper
1.583
270457AD2-023 GEN
Solar/Wind Helper
1.043
3148463FAIRFLD
Solar/Wind Helper
0.251
20673728F2S_V4-070
Solar/Wind Harmer
0.094
20464727HUNTR CT
Adder
2.216
217211CAMDEN ST C
Solar/Wind Harmer
0.013
217169METRODIV C
Solar/Wind Harmer
0.021
217186ESSEX_G9
Adder
8.408
217194REDH C
Solar/Wind Harmer
0.259
20676728BRNX1-095
Solar/Wind Harmer
0.093
207510AF2-138 C
Solar/Wind Harmer
0.953
20674628WNG_W3-110
Solar/Wind Harmer
0.216
971007AG2-625 GEN
Solar/Wind Harmer
1.389
20633028GILCT9
Adder
15.422
966181AG1-487 GEN
Solar/Wind Harmer
0.137
966131AG1-482 GEN
Solar/Wind Harmer
1.862
20466127PORT 5CT
Adder
14.376
972221AH1-695 GEN
Adder
81.834
20465427SHAW CT
Adder
2.099
963161AG1-165 GEN
Solar/Wind Harmer
0.549
209025WIENIPP3
Adder
2.895
963071AG1-156 GEN
Solar/Wind Harmer
1.51
970095AG2-074 GEN
Solar/Wind Harmer
3.427
209027LOR2_Q27
Solar/Wind Harmer
2.484
209022WHFR IPP
Adder
1.784
961331AF2-424 GEN
Solar/Wind Harmer
0.543
961421AF2-433 GEN
Solar/Wind Harmer
0.543
957921AF2-086 GEN
Solar/Wind Harmer
0.528
209142AF1-226 GEN
Solar/Wind Harmer
3.141
209093AE2-110 GEN
Solar/Wind Harmer
1.357
209120AE2-241 GEN
Solar/Wind Harmer
1.795
972245AH1-707 GEN
Adder
2.942
946691AF1-333 GEN
Solar/Wind Harmer
0.539
946741AF1-338 GEN
Solar/Wind Harmer
0.539
3141196NOKESVL
Solar/Wind Helper
2.766
316044AC1-158 PL1
Solar/Wind Helper
3.345
316450AC1-158 RIC
Solar/Wind Helper
0.892
316170AC1-121 GEN2
Solar/Wind Helper
0.902
3132273ORANGE
Solar/Wind Helper
0.109
3147666LOUISA
Solar/Wind Helper
1.223
966881AG1-559 GEN
Solar/Wind Helper
0.698
3141906WESTMOR
Solar/Wind Helper
0.198
316473AC1-191 GEN
Solar/Wind Helper
2.926
316404AE1-155 C
Solar/Wind Helper
4.036
316484AD2-074 GEN
Solar/Wind Helper
0.919
316156AD2-030 GEN
Solar/Wind Helper
0.706
316280AD1-041 GEN
Solar/Wind Helper
1.572
3142946ENON
Solar/Wind Helper
0.155
316382AG1-145 C
Solar/Wind Helper
0.616
315839AE2-212 C
Solar/Wind Helper
0.608
3145336SMITFLD
Solar/Wind Helper
0.179
315773AC2-141 GEN
Solar/Wind Helper
9.596
3144536CHRHLND
Solar/Wind Helper
0.067
3144873MCLAUGH
Solar/Wind Helper
0.011
3146456SLIGO L269
Solar/Wind Helper
0.437
316320Y1-086
Solar/Wind Helper
0.194
316313AB2-026
Solar/Wind Helper
0.657
316258AE1-075 C
Solar/Wind Helper
0.591
316405AF2-144 C
Solar/Wind Helper
0.493
316435W1029_GEN3
Solar/Wind Helper
1.736
3146516WINFALL
Solar/Wind Helper
0.429
3146626S HERTFORD
Solar/Wind Helper
0.426
3145273HOLLAND
Solar/Wind Helper
0.319
3146376EDENTON
Solar/Wind Helper
0.418
315614AA2-178 GEN
Solar/Wind Helper
2.497
315737AD1-076 GEN
Solar/Wind Helper
3.933
316365GEN2_N
Solar/Wind Helper
1.52
3146206CASHIE
Solar/Wind Helper
0.399
3145893MURPHYS
Solar/Wind Helper
0.143
3145893MURPHYS
Solar/Wind Helper
0.398
3146173TUNIS
Solar/Wind Helper
0.395
3156021HOLLOMANSOL
Solar/Wind Helper
2.996
316463AE2-346 GEN
Solar/Wind Helper
0.359
316140AB2-099
Solar/Wind Helper
0.15
966621AG1-532 GEN
Solar/Wind Helper
0.356
3146263WOODLND
Solar/Wind Helper
0.389
313506AB2-031 GEN
Solar/Wind Helper
1.759
3142666NORTHAMPTON
Solar/Wind Helper
0.386
3145963POPLR C
Solar/Wind Helper
0.386
316317KELFORD C
Solar/Wind Helper
0.327
3145823KELFORD
Solar/Wind Helper
0.384
3147043LAWRENC
Solar/Wind Helper
0.23
3146926FARMVIL
Solar/Wind Helper
0.228
3145796HORNRTN
Solar/Wind Helper
1.518
3145796HORNRTN
Solar/Wind Helper
0.38
3146776BUCKING
Solar/Wind Helper
0.136
316478AD1-087 GEN
Solar/Wind Helper
1.851
316486AD2-202 GEN
Solar/Wind Helper
0.542
942461AE2-259 GEN
Solar/Wind Helper
2.538
3147133PAMPLIN
Solar/Wind Helper
1.171
316210AC1-098 GEN
Solar/Wind Helper
3.002
3145933PARMELE
Solar/Wind Helper
0.371
315785AD2-033 C
Solar/Wind Helper
4.284
316131AB2-060 GEN
Solar/Wind Helper
2.219
3145746EVERETS
Solar/Wind Helper
0.364
3145746EVERETS
Solar/Wind Helper
0.364
315724AD1-057 GEN
Solar/Wind Helper
1.072
316327AA2-057 GEN
Solar/Wind Helper
2.054
3146233WITAKRS
Solar/Wind Helper
0.381
3146233WITAKRS
Solar/Wind Helper
0.241
3146073TAR RVR
Solar/Wind Helper
0.354
3146083TARBORO
Solar/Wind Helper
0.354
3138543CONSLDL
Solar/Wind Helper
0.233
3145543BTLEBRO
Solar/Wind Helper
0.348
3145543BTLEBRO
Solar/Wind Helper
0.348
316248AF1-058 C
Solar/Wind Helper
0.447
316283AC2-100 C
Solar/Wind Helper
1.612
3148013FISHERV
Solar/Wind Helper
0.292
316499AE2-029_GEN
Solar/Wind Helper
0.895
315616AA1-038_C
Solar/Wind Helper
1.138
237061AD1-155 GEN
Solar/Wind Helper
0.044
3147312GRETNA
Solar/Wind Helper
0.045
HAMLETPJM->LTFIMP_HAMLET
CLTF
6.599
G-007ALTFEXP_G-007A->PJM
CMTX
26.602
CBM NorthLTFEXP_CBM-N->PJM
CBM
46.587
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
1.704
BlueGrassPJM->LTFIMP_BlueG
CLTF
5.373
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
71.113
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.407
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
9.793

Details for CAMDEN-RICHRE29 230.0 kV Ckt 1 line l/o PECO_P4_CHICH045_SRT-A/* $ DELCO $ PECO_P4_CHICH045 $ STBK


Base Case Flowgate

Area:PECO/PSEG
Facility Description:
CAMDEN-RICHRE29 230.0 kV Ckt 1 line
Contingency Name:
PECO_P4_CHICH045_SRT-A/* $ DELCO $ PECO_P4_CHICH045 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.47 %
Rating:1336.0 MVA
Rating Type:B
MVA to Mitigate:1449.19
MW Contribution:9.03
Bus #Bus NameTypeMW Contribution
219126CAMDEN_CTG
50/50
1.666
219267WHEELBRDEPTF
50/50
0.234
219240MANTUACREK E
50/50
0.761
219726BAT.STORG E
50/50
0.369
972233AH1-701 GEN
50/50
5.793
228304LOGAN
50/50
32.871
228307PCLP GT
50/50
15.939
213400COVANTA DELA
50/50
1.115
219921AF1-264
Solar/Wind Harmer
0.237
219230EAGLE PT CT1
50/50
1.647
219235Y2-105
50/50
0.595
219904AC1-010 C
Solar/Wind Harmer
0.647
219258KINSLEYDEP C
Solar/Wind Harmer
0.526
219907AC1-030 C
Solar/Wind Harmer
0.201
230434AG1-499 GEN
Solar/Wind Harmer
0.671
228351V2-046C
Solar/Wind Harmer
2.274
970997AG2-616 GEN
Solar/Wind Harmer
10.419
230511AF1-262
Solar/Wind Harmer
0.196
945431AF1-208 GEN
Solar/Wind Harmer
9.097
228728W1-130C
Solar/Wind Harmer
0.679
218660EHAMPSOLAR C
Solar/Wind Harmer
0.17
219686LUMSOLAR_N C
Solar/Wind Harmer
0.196
219287REEVESEAST C
Solar/Wind Harmer
1.303
228206SHRMN CT
Adder
15.434
228732V1-021 C
Adder
0.168
219304NAMERICA C
Solar/Wind Harmer
0.231
219222BRL12CT2
Adder
6.624
20720728JCB_W1-129
Solar/Wind Harmer
0.186
207522AF2-254 C
Solar/Wind Harmer
0.885
231917EM10
Adder
1.422
231918WEST 1
Adder
1.902
207487AE2-000G4
Solar/Wind Harmer
16.555
233972AC1-094 C
Solar/Wind Harmer
0.344
232901NORTHST
Adder
4.287
232900DEMECSMY
Adder
4.729
972177AH1-672 GEN
Solar/Wind Harmer
6.808
232434Z2-077 GEN
Solar/Wind Harmer
0.126
207445AB1-138_GEN
Solar/Wind Harmer
0.278
20628028LAKEHURS
Adder
0.902
233954AC2-188 GEN
Solar/Wind Harmer
0.567
233950AC2-186 GEN
Solar/Wind Harmer
0.283
232917OH NUG6
Adder
4.424
232915OH NUG4
Adder
4.414
232404W1-003 C
Solar/Wind Harmer
0.504
971195AH1-057 GEN
Solar/Wind Harmer
0.55
233998TM1NIN_3.36
Solar/Wind Harmer
0.637
232428Y3-058 C
Solar/Wind Harmer
0.419
232919VN10
Adder
1.403
965821AG1-450 GEN
Solar/Wind Harmer
2.599
232426Y1-080 FULL
Solar/Wind Harmer
0.095
970277AG2-181 GEN
Solar/Wind Harmer
2.502
233964AF2-378 GEN
Solar/Wind Harmer
0.064
232910NRG_G1
Adder
4.287
234012AE2-112_GEN
Solar/Wind Harmer
1.099
232422X3-066 FULL
Solar/Wind Harmer
0.119
233930AB2-032 GEN
Solar/Wind Harmer
0.394
233915AB1-141 GEN
Solar/Wind Harmer
0.468
963711AG1-223 GEN
Solar/Wind Harmer
0.619
20714828MDF_W3-079
Solar/Wind Harmer
0.128
207454AA2-184 E
Solar/Wind Harmer
0.343
20715228NPK_W1-113
Solar/Wind Harmer
0.12
20742028HF_AC1-207
Solar/Wind Harmer
0.219
217197RE CRAN C
Solar/Wind Harmer
0.135
20635828PARLN1&2
Adder
1.804
219615MILLCREEK C
Solar/Wind Harmer
0.247
228251CARLLS#4
Adder
0.644
230407AD2-065 C
Solar/Wind Harmer
0.134
230433AD2-135 GEN
Solar/Wind Harmer
0.102
230422AE1-104_GEN1
Solar/Wind Harmer
29.724
230425AE1-104_GEN2
Solar/Wind Harmer
29.724
20716428NHV_W2-082
Solar/Wind Harmer
1.103
207500AE2-000G1
Solar/Wind Harmer
16.555
207497AE2-000G2
Solar/Wind Harmer
16.555
207507AE2-000G3
Solar/Wind Harmer
16.555
20636128O CRK C2
Adder
3.387
963401AG1-189 GEN
Solar/Wind Harmer
0.593
20714928UPF_X1-085
Solar/Wind Harmer
0.208
963391AG1-188 GEN
Solar/Wind Harmer
0.978
232416X2-083
Adder
0.236
233939AC1-091 C
Solar/Wind Harmer
0.455
233970AC1-092 C
Solar/Wind Harmer
0.455
971149AH1-027 GEN
Solar/Wind Harmer
1.743
232899W1-062
Adder
4.93
970545AG2-347 GEN
Solar/Wind Harmer
33.092
20628028LAKEHURS
Adder
0.456
231940T-011
Adder
0.376
972069AH1-584 GEN
Solar/Wind Harmer
4.508
972071AH1-585 GEN
Solar/Wind Harmer
4.508
971747AH1-380 GEN
Solar/Wind Harmer
1.803
233901CHERRYDALE C
Solar/Wind Harmer
0.566
232918OH NUG7
Adder
4.414
232905CHERITON_25
Adder
1.234
232408W1-005 C
Solar/Wind Harmer
0.504
232410W1-006 C
Solar/Wind Harmer
0.504
232926CRISFLD1
Adder
0.987
233946AB2-136 GEN
Solar/Wind Harmer
1.989
231131BLOOM ENRGY
Adder
2.171
234036AF2-325 C
Solar/Wind Harmer
0.457
234041AC1-190 GEN
Solar/Wind Harmer
4.453
233987AB2-037 GEN
Solar/Wind Harmer
5.633
213535CROYDN11
Adder
4.756
219114HARTZY_C
Solar/Wind Harmer
0.391
233984AB2-036 GEN
Solar/Wind Harmer
6.019
232424Y1-079 C
Solar/Wind Harmer
0.272
234014AF1-036_GEN
Solar/Wind Harmer
1.293
233944AB2-135 GEN
Solar/Wind Harmer
2.497
233933AB2-153 GEN
Solar/Wind Harmer
0.531
20720628TIN_W1-124
Solar/Wind Harmer
0.342
20641628MLH_W1-032
Solar/Wind Harmer
0.084
20716928W4-060COL
Solar/Wind Harmer
0.195
219124CAMDEN_STG
50/50
1.356
219286CAMD CO RR
50/50
0.468
230406ST-CC
50/50
5.361
230404GT1-CC
50/50
3.606
228304LOGAN
50/50
29.564
219912AD2-042 GEN
Solar/Wind Harmer
1.435
219766PARADISE C
Solar/Wind Harmer
0.539
219623KINSLEYBEA C
Solar/Wind Harmer
0.685
219236SOUTHERNHQ C
Solar/Wind Harmer
0.097
230430AE1-229_GEN
Solar/Wind Harmer
9.527
230415AB2-049 C
Solar/Wind Harmer
0.198
219906AC1-017 C
Solar/Wind Harmer
0.231
219291REEVESSOUT C
Solar/Wind Harmer
0.058
971553AH1-274 GEN
Solar/Wind Harmer
2.336
228711V2-041C
Solar/Wind Harmer
0.553
228202CUMB CT
Adder
15.027
228729W2-030 C
Solar/Wind Harmer
0.501
219610FLORENCE C
Solar/Wind Harmer
1.028
219348LDSOLAR C
Solar/Wind Harmer
0.444
219221BRL12CT1
Adder
6.624
219223BRL12CT3
Adder
6.624
20716028EGP_W2-019
Solar/Wind Harmer
0.291
20720828JCB_W4-025
Solar/Wind Harmer
0.283
20715028HAN_X4-015
Solar/Wind Harmer
0.186
959561AF2-247 GEN
Solar/Wind Harmer
0.29
972251AH1-710 GEN
Adder
27.658
20636028O CRK C1
Adder
3.715
233971AC1-093 C
Solar/Wind Harmer
0.406
970695AG2-447 GEN
Solar/Wind Harmer
1.856
971667AH1-334 GEN
Solar/Wind Harmer
1.345
972133AH1-634 GEN
Solar/Wind Harmer
5.014
233952AC2-187 GEN
Solar/Wind Harmer
0.567
972073AH1-586 GEN
Solar/Wind Harmer
4.718
233990AG1-397 GEN
Solar/Wind Harmer
0.577
232914OH NUG3
Adder
4.443
232916OH NUG5
Adder
4.443
232921TASLEY2G
Adder
2.597
232406W1-004 FULL
Solar/Wind Harmer
0.504
234015AF2-250 C
Solar/Wind Harmer
0.061
233996TM1833_GEN
Solar/Wind Harmer
0.637
233997TMININ_4.2
Solar/Wind Harmer
0.637
233900O-025 C
Adder
0.592
233940AF2-379 C
Solar/Wind Harmer
0.094
233994AC2-023 GEN
Solar/Wind Harmer
1.349
232907VN8
Adder
15.015
960671AF2-358 GEN
Solar/Wind Harmer
8.942
232417X3-008 C
Solar/Wind Harmer
0.994
233982AB2-133 GEN
Solar/Wind Harmer
2.3
233918AB1-142 GEN
Solar/Wind Harmer
0.468
219727YARDVSOLFA C
Solar/Wind Harmer
0.392
20714528FRN_Y2-051
Solar/Wind Harmer
0.122
219276PARKLANDSO C
Solar/Wind Harmer
0.16
20720528MAN_W1-024
Solar/Wind Harmer
0.073
20716228APLW2-078
Solar/Wind Harmer
0.247
219612MATRIX C
Solar/Wind Harmer
0.046
218438BLK ROCK C
Solar/Wind Harmer
0.034
20635828PARLN1&2
Adder
0.817
20635928PARLN3&4
Adder
0.817
967451AG2-055 C O1
Solar/Wind Harmer
40.283
219229EAGLE PT ST
50/50
0.833
219231EAGLE PT CT2
50/50
1.646
230405GT2-CC
50/50
3.623
219914AD2-027 C
Solar/Wind Harmer
1.083
219137THOSOLAR C
Solar/Wind Harmer
1.822
971011AG2-627 GEN
Solar/Wind Harmer
9.025
228309CCLP NUG
Adder
29.24
228309CCLP NUG
Adder
27.814
964001AG1-254 GEN
Solar/Wind Harmer
2.296
972141AH1-641 GEN
Solar/Wind Harmer
3.126
219272CLEANLIGHT C
Solar/Wind Harmer
0.199
971535AH1-265 GEN
Solar/Wind Harmer
4.38
228260V4-054C
Solar/Wind Harmer
1.047
219688LUMSOLAR_S C
Solar/Wind Harmer
0.193
970453AG2-297 GEN
Solar/Wind Harmer
2.469
228754AB1-001 C
Solar/Wind Harmer
0.121
227927V4-067C
Solar/Wind Harmer
0.17
219607WPEMNERT C
Solar/Wind Harmer
0.311
219224BRL12CT4
Adder
6.624
20717128DIX_Z2-102
Solar/Wind Harmer
0.804
20715728PEM_W1-119
Solar/Wind Harmer
0.321
20715828PEM_W1-120
Solar/Wind Harmer
0.321
231919CHRIST1
Adder
2.554
231920CHRIST2
Adder
2.497
971189AH1-054 GEN
Solar/Wind Harmer
0.624
970025AG2-016 GEN
Solar/Wind Harmer
1.448
233973AC2-185 C
Solar/Wind Harmer
1.872
207459AE1-142 C O1
Solar/Wind Harmer
0.51
234033AF1-007_GEN
Solar/Wind Harmer
11.825
232904IR4
Adder
40.889
232920IR10
Adder
1.597
232432Z2-076 GEN
Solar/Wind Harmer
0.067
233990AG1-397 GEN
Solar/Wind Harmer
0.028
232912OH NUG1
Adder
4.443
232913OH NUG2
Adder
4.384
233923SMA
Solar/Wind Harmer
2.334
232813VAUGHN
Adder
0.294
233955AB2-172 GEN
Solar/Wind Harmer
2.486
231906DC3 NUG
Adder
6.906
231902DC CT7
Adder
5.521
231907DC10
Adder
1.724
233968AD2-076_GEN
Solar/Wind Harmer
3.168
970597AG2-380 GEN
Solar/Wind Harmer
1.99
232436AB1-176 C
Solar/Wind Harmer
0.109
971983AH1-536 GEN
Solar/Wind Harmer
3.534
233935AB2-179 C
Solar/Wind Harmer
1.103
20714328BYD_X4-031
Solar/Wind Harmer
0.101
20714428HOW_X1-037
Solar/Wind Harmer
0.426
971521AH1-258 GEN
Solar/Wind Harmer
0.846
20720428HOL_W1-112
Solar/Wind Harmer
0.105
20635928PARLN3&4
Adder
1.804
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.502
G-007ALTFEXP_G-007A->PJM
CMTX
11.581
CBM NorthLTFEXP_CBM-N->PJM
CBM
4.513
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.496
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.545
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
17.921
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.306
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
2.299

Details for CAMDEN-RICHRE29 230.0 kV Ckt 1 line l/o PECO_P4_CHICH195_SRT-A/* $ DELCO $ PECO_P4_CHICH195 $ STBK


Base Case Flowgate

Area:PECO/PSEG
Facility Description:
CAMDEN-RICHRE29 230.0 kV Ckt 1 line
Contingency Name:
PECO_P4_CHICH195_SRT-A/* $ DELCO $ PECO_P4_CHICH195 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.47 %
Rating:1336.0 MVA
Rating Type:B
MVA to Mitigate:1449.12
MW Contribution:9.03
Bus #Bus NameTypeMW Contribution
219126CAMDEN_CTG
50/50
1.666
219267WHEELBRDEPTF
50/50
0.234
219240MANTUACREK E
50/50
0.761
219726BAT.STORG E
50/50
0.369
972233AH1-701 GEN
50/50
5.793
228304LOGAN
50/50
32.871
228307PCLP GT
50/50
15.939
213400COVANTA DELA
50/50
1.115
219921AF1-264
Solar/Wind Harmer
0.237
219615MILLCREEK C
Solar/Wind Harmer
0.247
228251CARLLS#4
Adder
0.644
230407AD2-065 C
Solar/Wind Harmer
0.134
230433AD2-135 GEN
Solar/Wind Harmer
0.102
230422AE1-104_GEN1
Solar/Wind Harmer
29.724
230425AE1-104_GEN2
Solar/Wind Harmer
29.724
20716428NHV_W2-082
Solar/Wind Harmer
1.103
207500AE2-000G1
Solar/Wind Harmer
16.555
207497AE2-000G2
Solar/Wind Harmer
16.555
207507AE2-000G3
Solar/Wind Harmer
16.555
20636128O CRK C2
Adder
3.387
963401AG1-189 GEN
Solar/Wind Harmer
0.593
20714928UPF_X1-085
Solar/Wind Harmer
0.208
963391AG1-188 GEN
Solar/Wind Harmer
0.978
232416X2-083
Adder
0.236
233939AC1-091 C
Solar/Wind Harmer
0.455
233970AC1-092 C
Solar/Wind Harmer
0.455
971149AH1-027 GEN
Solar/Wind Harmer
1.743
232899W1-062
Adder
4.93
970545AG2-347 GEN
Solar/Wind Harmer
33.092
20628028LAKEHURS
Adder
0.456
231940T-011
Adder
0.376
972069AH1-584 GEN
Solar/Wind Harmer
4.508
972071AH1-585 GEN
Solar/Wind Harmer
4.508
971747AH1-380 GEN
Solar/Wind Harmer
1.803
219229EAGLE PT ST
50/50
0.833
219231EAGLE PT CT2
50/50
1.646
230405GT2-CC
50/50
3.623
219914AD2-027 C
Solar/Wind Harmer
1.083
219137THOSOLAR C
Solar/Wind Harmer
1.822
971011AG2-627 GEN
Solar/Wind Harmer
9.025
228309CCLP NUG
Adder
29.24
228309CCLP NUG
Adder
27.814
964001AG1-254 GEN
Solar/Wind Harmer
2.296
972141AH1-641 GEN
Solar/Wind Harmer
3.126
219272CLEANLIGHT C
Solar/Wind Harmer
0.199
971535AH1-265 GEN
Solar/Wind Harmer
4.38
228260V4-054C
Solar/Wind Harmer
1.047
219688LUMSOLAR_S C
Solar/Wind Harmer
0.193
970453AG2-297 GEN
Solar/Wind Harmer
2.469
228754AB1-001 C
Solar/Wind Harmer
0.121
227927V4-067C
Solar/Wind Harmer
0.17
219607WPEMNERT C
Solar/Wind Harmer
0.311
219224BRL12CT4
Adder
6.624
20717128DIX_Z2-102
Solar/Wind Harmer
0.804
20715728PEM_W1-119
Solar/Wind Harmer
0.321
20715828PEM_W1-120
Solar/Wind Harmer
0.321
231919CHRIST1
Adder
2.554
231920CHRIST2
Adder
2.497
971189AH1-054 GEN
Solar/Wind Harmer
0.624
970025AG2-016 GEN
Solar/Wind Harmer
1.448
233973AC2-185 C
Solar/Wind Harmer
1.872
207459AE1-142 C O1
Solar/Wind Harmer
0.51
234033AF1-007_GEN
Solar/Wind Harmer
11.825
232904IR4
Adder
40.889
232920IR10
Adder
1.597
232432Z2-076 GEN
Solar/Wind Harmer
0.067
219230EAGLE PT CT1
50/50
1.647
219235Y2-105
50/50
0.595
219904AC1-010 C
Solar/Wind Harmer
0.647
219258KINSLEYDEP C
Solar/Wind Harmer
0.526
219907AC1-030 C
Solar/Wind Harmer
0.201
230434AG1-499 GEN
Solar/Wind Harmer
0.671
228351V2-046C
Solar/Wind Harmer
2.274
970997AG2-616 GEN
Solar/Wind Harmer
10.419
230511AF1-262
Solar/Wind Harmer
0.196
945431AF1-208 GEN
Solar/Wind Harmer
9.097
228728W1-130C
Solar/Wind Harmer
0.679
218660EHAMPSOLAR C
Solar/Wind Harmer
0.17
219686LUMSOLAR_N C
Solar/Wind Harmer
0.196
219287REEVESEAST C
Solar/Wind Harmer
1.303
228206SHRMN CT
Adder
15.434
228732V1-021 C
Adder
0.168
219304NAMERICA C
Solar/Wind Harmer
0.231
219222BRL12CT2
Adder
6.624
20720728JCB_W1-129
Solar/Wind Harmer
0.186
207522AF2-254 C
Solar/Wind Harmer
0.885
231917EM10
Adder
1.422
231918WEST 1
Adder
1.902
207487AE2-000G4
Solar/Wind Harmer
16.555
233972AC1-094 C
Solar/Wind Harmer
0.344
232901NORTHST
Adder
4.287
232900DEMECSMY
Adder
4.729
972177AH1-672 GEN
Solar/Wind Harmer
6.808
232434Z2-077 GEN
Solar/Wind Harmer
0.126
207445AB1-138_GEN
Solar/Wind Harmer
0.278
20628028LAKEHURS
Adder
0.902
233954AC2-188 GEN
Solar/Wind Harmer
0.567
233950AC2-186 GEN
Solar/Wind Harmer
0.283
232917OH NUG6
Adder
4.424
232915OH NUG4
Adder
4.414
232404W1-003 C
Solar/Wind Harmer
0.504
971195AH1-057 GEN
Solar/Wind Harmer
0.55
233998TM1NIN_3.36
Solar/Wind Harmer
0.637
232428Y3-058 C
Solar/Wind Harmer
0.419
232919VN10
Adder
1.403
965821AG1-450 GEN
Solar/Wind Harmer
2.599
232426Y1-080 FULL
Solar/Wind Harmer
0.095
970277AG2-181 GEN
Solar/Wind Harmer
2.502
233964AF2-378 GEN
Solar/Wind Harmer
0.064
232910NRG_G1
Adder
4.287
234012AE2-112_GEN
Solar/Wind Harmer
1.099
232422X3-066 FULL
Solar/Wind Harmer
0.119
233930AB2-032 GEN
Solar/Wind Harmer
0.394
233915AB1-141 GEN
Solar/Wind Harmer
0.468
963711AG1-223 GEN
Solar/Wind Harmer
0.619
20714828MDF_W3-079
Solar/Wind Harmer
0.128
207454AA2-184 E
Solar/Wind Harmer
0.343
20715228NPK_W1-113
Solar/Wind Harmer
0.12
20742028HF_AC1-207
Solar/Wind Harmer
0.219
217197RE CRAN C
Solar/Wind Harmer
0.135
20635828PARLN1&2
Adder
1.804
233901CHERRYDALE C
Solar/Wind Harmer
0.566
232918OH NUG7
Adder
4.414
232905CHERITON_25
Adder
1.234
232408W1-005 C
Solar/Wind Harmer
0.504
232410W1-006 C
Solar/Wind Harmer
0.504
232926CRISFLD1
Adder
0.987
233946AB2-136 GEN
Solar/Wind Harmer
1.989
231131BLOOM ENRGY
Adder
2.171
234036AF2-325 C
Solar/Wind Harmer
0.457
234041AC1-190 GEN
Solar/Wind Harmer
4.453
233987AB2-037 GEN
Solar/Wind Harmer
5.633
213535CROYDN11
Adder
4.756
219114HARTZY_C
Solar/Wind Harmer
0.391
233984AB2-036 GEN
Solar/Wind Harmer
6.019
232424Y1-079 C
Solar/Wind Harmer
0.272
234014AF1-036_GEN
Solar/Wind Harmer
1.293
233944AB2-135 GEN
Solar/Wind Harmer
2.497
233933AB2-153 GEN
Solar/Wind Harmer
0.531
20720628TIN_W1-124
Solar/Wind Harmer
0.342
20641628MLH_W1-032
Solar/Wind Harmer
0.084
20716928W4-060COL
Solar/Wind Harmer
0.195
219124CAMDEN_STG
50/50
1.356
219286CAMD CO RR
50/50
0.468
230406ST-CC
50/50
5.361
230404GT1-CC
50/50
3.606
228304LOGAN
50/50
29.564
219912AD2-042 GEN
Solar/Wind Harmer
1.435
219766PARADISE C
Solar/Wind Harmer
0.539
219623KINSLEYBEA C
Solar/Wind Harmer
0.685
219236SOUTHERNHQ C
Solar/Wind Harmer
0.097
230430AE1-229_GEN
Solar/Wind Harmer
9.527
230415AB2-049 C
Solar/Wind Harmer
0.198
219906AC1-017 C
Solar/Wind Harmer
0.231
219291REEVESSOUT C
Solar/Wind Harmer
0.058
971553AH1-274 GEN
Solar/Wind Harmer
2.336
228711V2-041C
Solar/Wind Harmer
0.553
228202CUMB CT
Adder
15.027
228729W2-030 C
Solar/Wind Harmer
0.501
219610FLORENCE C
Solar/Wind Harmer
1.028
219348LDSOLAR C
Solar/Wind Harmer
0.444
219221BRL12CT1
Adder
6.624
219223BRL12CT3
Adder
6.624
20716028EGP_W2-019
Solar/Wind Harmer
0.291
20720828JCB_W4-025
Solar/Wind Harmer
0.283
20715028HAN_X4-015
Solar/Wind Harmer
0.186
959561AF2-247 GEN
Solar/Wind Harmer
0.29
972251AH1-710 GEN
Adder
27.658
20636028O CRK C1
Adder
3.715
233971AC1-093 C
Solar/Wind Harmer
0.406
970695AG2-447 GEN
Solar/Wind Harmer
1.856
971667AH1-334 GEN
Solar/Wind Harmer
1.345
972133AH1-634 GEN
Solar/Wind Harmer
5.014
233952AC2-187 GEN
Solar/Wind Harmer
0.567
972073AH1-586 GEN
Solar/Wind Harmer
4.718
233990AG1-397 GEN
Solar/Wind Harmer
0.577
232914OH NUG3
Adder
4.443
232916OH NUG5
Adder
4.443
232921TASLEY2G
Adder
2.597
232406W1-004 FULL
Solar/Wind Harmer
0.504
234015AF2-250 C
Solar/Wind Harmer
0.061
233996TM1833_GEN
Solar/Wind Harmer
0.637
233997TMININ_4.2
Solar/Wind Harmer
0.637
233900O-025 C
Adder
0.592
233940AF2-379 C
Solar/Wind Harmer
0.094
233994AC2-023 GEN
Solar/Wind Harmer
1.349
232907VN8
Adder
15.015
960671AF2-358 GEN
Solar/Wind Harmer
8.942
232417X3-008 C
Solar/Wind Harmer
0.994
233982AB2-133 GEN
Solar/Wind Harmer
2.3
233918AB1-142 GEN
Solar/Wind Harmer
0.468
219727YARDVSOLFA C
Solar/Wind Harmer
0.392
20714528FRN_Y2-051
Solar/Wind Harmer
0.122
219276PARKLANDSO C
Solar/Wind Harmer
0.16
20720528MAN_W1-024
Solar/Wind Harmer
0.073
20716228APLW2-078
Solar/Wind Harmer
0.247
219612MATRIX C
Solar/Wind Harmer
0.046
218438BLK ROCK C
Solar/Wind Harmer
0.034
20635828PARLN1&2
Adder
0.817
20635928PARLN3&4
Adder
0.817
967451AG2-055 C O1
Solar/Wind Harmer
40.283
233990AG1-397 GEN
Solar/Wind Harmer
0.028
232912OH NUG1
Adder
4.443
232913OH NUG2
Adder
4.384
233923SMA
Solar/Wind Harmer
2.334
232813VAUGHN
Adder
0.294
233955AB2-172 GEN
Solar/Wind Harmer
2.486
231906DC3 NUG
Adder
6.906
231902DC CT7
Adder
5.521
231907DC10
Adder
1.724
233968AD2-076_GEN
Solar/Wind Harmer
3.168
970597AG2-380 GEN
Solar/Wind Harmer
1.99
232436AB1-176 C
Solar/Wind Harmer
0.109
971983AH1-536 GEN
Solar/Wind Harmer
3.534
233935AB2-179 C
Solar/Wind Harmer
1.103
20714328BYD_X4-031
Solar/Wind Harmer
0.101
20714428HOW_X1-037
Solar/Wind Harmer
0.426
971521AH1-258 GEN
Solar/Wind Harmer
0.846
20720428HOL_W1-112
Solar/Wind Harmer
0.105
20635928PARLN3&4
Adder
1.804
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.502
G-007ALTFEXP_G-007A->PJM
CMTX
11.581
CBM NorthLTFEXP_CBM-N->PJM
CBM
4.513
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.496
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.545
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
17.921
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.306
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
2.299

Details for CAMDEN-RICHRE29 230.0 kV Ckt 1 line l/o PECO_P4_CHICH435_SRT-A/* $ DELCO $ PECO_P4_CHICH435 $ STBK


Base Case Flowgate

Area:PECO/PSEG
Facility Description:
CAMDEN-RICHRE29 230.0 kV Ckt 1 line
Contingency Name:
PECO_P4_CHICH435_SRT-A/* $ DELCO $ PECO_P4_CHICH435 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.46 %
Rating:1336.0 MVA
Rating Type:B
MVA to Mitigate:1449.07
MW Contribution:9.03
Bus #Bus NameTypeMW Contribution
219126CAMDEN_CTG
50/50
1.666
219267WHEELBRDEPTF
50/50
0.234
219240MANTUACREK E
50/50
0.761
219726BAT.STORG E
50/50
0.369
972233AH1-701 GEN
50/50
5.794
228304LOGAN
50/50
32.872
228307PCLP GT
50/50
15.939
213400COVANTA DELA
50/50
1.115
219921AF1-264
Solar/Wind Harmer
0.237
219615MILLCREEK C
Solar/Wind Harmer
0.247
228251CARLLS#4
Adder
0.644
230407AD2-065 C
Solar/Wind Harmer
0.134
230433AD2-135 GEN
Solar/Wind Harmer
0.102
230422AE1-104_GEN1
Solar/Wind Harmer
29.725
230425AE1-104_GEN2
Solar/Wind Harmer
29.725
20716428NHV_W2-082
Solar/Wind Harmer
1.103
207500AE2-000G1
Solar/Wind Harmer
16.555
207497AE2-000G2
Solar/Wind Harmer
16.555
207507AE2-000G3
Solar/Wind Harmer
16.555
20636128O CRK C2
Adder
3.387
963401AG1-189 GEN
Solar/Wind Harmer
0.593
20714928UPF_X1-085
Solar/Wind Harmer
0.208
963391AG1-188 GEN
Solar/Wind Harmer
0.978
232416X2-083
Adder
0.236
233939AC1-091 C
Solar/Wind Harmer
0.455
233970AC1-092 C
Solar/Wind Harmer
0.455
971149AH1-027 GEN
Solar/Wind Harmer
1.743
232899W1-062
Adder
4.929
970545AG2-347 GEN
Solar/Wind Harmer
33.089
20628028LAKEHURS
Adder
0.456
231940T-011
Adder
0.376
972069AH1-584 GEN
Solar/Wind Harmer
4.507
972071AH1-585 GEN
Solar/Wind Harmer
4.507
971747AH1-380 GEN
Solar/Wind Harmer
1.802
233901CHERRYDALE C
Solar/Wind Harmer
0.566
232408W1-005 C
Solar/Wind Harmer
0.504
232410W1-006 C
Solar/Wind Harmer
0.504
232918OH NUG7
Adder
4.413
232905CHERITON_25
Adder
1.234
232926CRISFLD1
Adder
0.986
233946AB2-136 GEN
Solar/Wind Harmer
1.989
231131BLOOM ENRGY
Adder
2.171
234036AF2-325 C
Solar/Wind Harmer
0.457
234041AC1-190 GEN
Solar/Wind Harmer
4.452
233987AB2-037 GEN
Solar/Wind Harmer
5.632
213535CROYDN11
Adder
4.757
219114HARTZY_C
Solar/Wind Harmer
0.391
233984AB2-036 GEN
Solar/Wind Harmer
6.018
232424Y1-079 C
Solar/Wind Harmer
0.272
234014AF1-036_GEN
Solar/Wind Harmer
1.293
233944AB2-135 GEN
Solar/Wind Harmer
2.497
233933AB2-153 GEN
Solar/Wind Harmer
0.531
20720628TIN_W1-124
Solar/Wind Harmer
0.342
20641628MLH_W1-032
Solar/Wind Harmer
0.084
20716928W4-060COL
Solar/Wind Harmer
0.195
219230EAGLE PT CT1
50/50
1.647
219235Y2-105
50/50
0.595
219904AC1-010 C
Solar/Wind Harmer
0.647
219258KINSLEYDEP C
Solar/Wind Harmer
0.526
219907AC1-030 C
Solar/Wind Harmer
0.201
230434AG1-499 GEN
Solar/Wind Harmer
0.671
228351V2-046C
Solar/Wind Harmer
2.274
970997AG2-616 GEN
Solar/Wind Harmer
10.42
230511AF1-262
Solar/Wind Harmer
0.196
945431AF1-208 GEN
Solar/Wind Harmer
9.097
228728W1-130C
Solar/Wind Harmer
0.679
218660EHAMPSOLAR C
Solar/Wind Harmer
0.17
219686LUMSOLAR_N C
Solar/Wind Harmer
0.196
219287REEVESEAST C
Solar/Wind Harmer
1.303
228206SHRMN CT
Adder
15.434
228732V1-021 C
Adder
0.168
219304NAMERICA C
Solar/Wind Harmer
0.231
219222BRL12CT2
Adder
6.624
20720728JCB_W1-129
Solar/Wind Harmer
0.186
207522AF2-254 C
Solar/Wind Harmer
0.885
231917EM10
Adder
1.422
231918WEST 1
Adder
1.902
207487AE2-000G4
Solar/Wind Harmer
16.555
233972AC1-094 C
Solar/Wind Harmer
0.344
232901NORTHST
Adder
4.286
232900DEMECSMY
Adder
4.728
972177AH1-672 GEN
Solar/Wind Harmer
6.807
232434Z2-077 GEN
Solar/Wind Harmer
0.126
207445AB1-138_GEN
Solar/Wind Harmer
0.278
20628028LAKEHURS
Adder
0.902
233954AC2-188 GEN
Solar/Wind Harmer
0.567
233950AC2-186 GEN
Solar/Wind Harmer
0.283
232404W1-003 C
Solar/Wind Harmer
0.504
232917OH NUG6
Adder
4.423
232915OH NUG4
Adder
4.413
971195AH1-057 GEN
Solar/Wind Harmer
0.55
233998TM1NIN_3.36
Solar/Wind Harmer
0.637
232428Y3-058 C
Solar/Wind Harmer
0.419
232919VN10
Adder
1.403
965821AG1-450 GEN
Solar/Wind Harmer
2.599
232426Y1-080 FULL
Solar/Wind Harmer
0.095
970277AG2-181 GEN
Solar/Wind Harmer
2.502
233964AF2-378 GEN
Solar/Wind Harmer
0.064
232910NRG_G1
Adder
4.287
234012AE2-112_GEN
Solar/Wind Harmer
1.099
232422X3-066 FULL
Solar/Wind Harmer
0.119
233930AB2-032 GEN
Solar/Wind Harmer
0.394
233915AB1-141 GEN
Solar/Wind Harmer
0.468
963711AG1-223 GEN
Solar/Wind Harmer
0.619
20714828MDF_W3-079
Solar/Wind Harmer
0.128
207454AA2-184 E
Solar/Wind Harmer
0.343
20715228NPK_W1-113
Solar/Wind Harmer
0.12
20742028HF_AC1-207
Solar/Wind Harmer
0.219
217197RE CRAN C
Solar/Wind Harmer
0.135
20635828PARLN1&2
Adder
1.804
219229EAGLE PT ST
50/50
0.833
219231EAGLE PT CT2
50/50
1.646
230405GT2-CC
50/50
3.623
219914AD2-027 C
Solar/Wind Harmer
1.083
219137THOSOLAR C
Solar/Wind Harmer
1.822
971011AG2-627 GEN
Solar/Wind Harmer
9.025
228309CCLP NUG
Adder
29.241
228309CCLP NUG
Adder
27.815
964001AG1-254 GEN
Solar/Wind Harmer
2.296
972141AH1-641 GEN
Solar/Wind Harmer
3.126
219272CLEANLIGHT C
Solar/Wind Harmer
0.199
971535AH1-265 GEN
Solar/Wind Harmer
4.38
228260V4-054C
Solar/Wind Harmer
1.047
219688LUMSOLAR_S C
Solar/Wind Harmer
0.193
970453AG2-297 GEN
Solar/Wind Harmer
2.469
228754AB1-001 C
Solar/Wind Harmer
0.121
227927V4-067C
Solar/Wind Harmer
0.17
219607WPEMNERT C
Solar/Wind Harmer
0.311
219224BRL12CT4
Adder
6.624
20717128DIX_Z2-102
Solar/Wind Harmer
0.804
20715728PEM_W1-119
Solar/Wind Harmer
0.321
20715828PEM_W1-120
Solar/Wind Harmer
0.321
231919CHRIST1
Adder
2.554
231920CHRIST2
Adder
2.497
971189AH1-054 GEN
Solar/Wind Harmer
0.624
970025AG2-016 GEN
Solar/Wind Harmer
1.448
233973AC2-185 C
Solar/Wind Harmer
1.872
207459AE1-142 C O1
Solar/Wind Harmer
0.51
234033AF1-007_GEN
Solar/Wind Harmer
11.824
232904IR4
Adder
40.885
232920IR10
Adder
1.597
232432Z2-076 GEN
Solar/Wind Harmer
0.067
233990AG1-397 GEN
Solar/Wind Harmer
0.028
232912OH NUG1
Adder
4.443
232913OH NUG2
Adder
4.384
233923SMA
Solar/Wind Harmer
2.334
232813VAUGHN
Adder
0.294
233955AB2-172 GEN
Solar/Wind Harmer
2.485
231906DC3 NUG
Adder
6.905
231902DC CT7
Adder
5.521
231907DC10
Adder
1.724
233968AD2-076_GEN
Solar/Wind Harmer
3.168
970597AG2-380 GEN
Solar/Wind Harmer
1.989
232436AB1-176 C
Solar/Wind Harmer
0.109
971983AH1-536 GEN
Solar/Wind Harmer
3.533
233935AB2-179 C
Solar/Wind Harmer
1.103
20714328BYD_X4-031
Solar/Wind Harmer
0.101
20714428HOW_X1-037
Solar/Wind Harmer
0.426
971521AH1-258 GEN
Solar/Wind Harmer
0.846
20720428HOL_W1-112
Solar/Wind Harmer
0.105
20635928PARLN3&4
Adder
1.804
219124CAMDEN_STG
50/50
1.356
219286CAMD CO RR
50/50
0.468
230406ST-CC
50/50
5.361
230404GT1-CC
50/50
3.606
228304LOGAN
50/50
29.565
219912AD2-042 GEN
Solar/Wind Harmer
1.435
219766PARADISE C
Solar/Wind Harmer
0.539
219623KINSLEYBEA C
Solar/Wind Harmer
0.685
219236SOUTHERNHQ C
Solar/Wind Harmer
0.097
230430AE1-229_GEN
Solar/Wind Harmer
9.527
230415AB2-049 C
Solar/Wind Harmer
0.198
219906AC1-017 C
Solar/Wind Harmer
0.231
219291REEVESSOUT C
Solar/Wind Harmer
0.058
971553AH1-274 GEN
Solar/Wind Harmer
2.336
228711V2-041C
Solar/Wind Harmer
0.553
228202CUMB CT
Adder
15.028
228729W2-030 C
Solar/Wind Harmer
0.501
219610FLORENCE C
Solar/Wind Harmer
1.028
219348LDSOLAR C
Solar/Wind Harmer
0.444
219221BRL12CT1
Adder
6.624
219223BRL12CT3
Adder
6.624
20716028EGP_W2-019
Solar/Wind Harmer
0.291
20720828JCB_W4-025
Solar/Wind Harmer
0.283
20715028HAN_X4-015
Solar/Wind Harmer
0.186
959561AF2-247 GEN
Solar/Wind Harmer
0.29
972251AH1-710 GEN
Adder
27.657
20636028O CRK C1
Adder
3.715
233971AC1-093 C
Solar/Wind Harmer
0.406
970695AG2-447 GEN
Solar/Wind Harmer
1.856
971667AH1-334 GEN
Solar/Wind Harmer
1.345
972133AH1-634 GEN
Solar/Wind Harmer
5.014
233952AC2-187 GEN
Solar/Wind Harmer
0.567
972073AH1-586 GEN
Solar/Wind Harmer
4.717
233990AG1-397 GEN
Solar/Wind Harmer
0.577
232406W1-004 FULL
Solar/Wind Harmer
0.504
232914OH NUG3
Adder
4.443
232916OH NUG5
Adder
4.443
232921TASLEY2G
Adder
2.597
234015AF2-250 C
Solar/Wind Harmer
0.061
233996TM1833_GEN
Solar/Wind Harmer
0.637
233997TMININ_4.2
Solar/Wind Harmer
0.637
233900O-025 C
Adder
0.592
233940AF2-379 C
Solar/Wind Harmer
0.094
233994AC2-023 GEN
Solar/Wind Harmer
1.349
232907VN8
Adder
15.014
960671AF2-358 GEN
Solar/Wind Harmer
8.941
232417X3-008 C
Solar/Wind Harmer
0.994
233982AB2-133 GEN
Solar/Wind Harmer
2.3
233918AB1-142 GEN
Solar/Wind Harmer
0.468
219727YARDVSOLFA C
Solar/Wind Harmer
0.392
20714528FRN_Y2-051
Solar/Wind Harmer
0.122
219276PARKLANDSO C
Solar/Wind Harmer
0.16
20720528MAN_W1-024
Solar/Wind Harmer
0.073
20716228APLW2-078
Solar/Wind Harmer
0.247
219612MATRIX C
Solar/Wind Harmer
0.046
218438BLK ROCK C
Solar/Wind Harmer
0.034
20635828PARLN1&2
Adder
0.817
20635928PARLN3&4
Adder
0.817
967451AG2-055 C O1
Solar/Wind Harmer
40.285
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.502
G-007ALTFEXP_G-007A->PJM
CMTX
11.581
CBM NorthLTFEXP_CBM-N->PJM
CBM
4.514
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.496
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.545
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
17.923
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.306
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
2.299

Details for CAMDEN-RICHRE29 230.0 kV Ckt 1 line l/o PECO_P2-2_CHI230B1_SRT-A/* $ DELCO $ PECO_P2-2_CHI230B1 $ B


Base Case Flowgate

Area:PECO/PSEG
Facility Description:
CAMDEN-RICHRE29 230.0 kV Ckt 1 line
Contingency Name:
PECO_P2-2_CHI230B1_SRT-A/* $ DELCO $ PECO_P2-2_CHI230B1 $ B
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:108.46 %
Rating:1336.0 MVA
Rating Type:B
MVA to Mitigate:1449.01
MW Contribution:9.03
Bus #Bus NameTypeMW Contribution
219229EAGLE PT ST
50/50
0.833
219231EAGLE PT CT2
50/50
1.646
230405GT2-CC
50/50
3.623
219914AD2-027 C
Solar/Wind Harmer
1.083
219137THOSOLAR C
Solar/Wind Harmer
1.822
971011AG2-627 GEN
Solar/Wind Harmer
9.025
228309CCLP NUG
Adder
29.24
228309CCLP NUG
Adder
27.814
964001AG1-254 GEN
Solar/Wind Harmer
2.296
972141AH1-641 GEN
Solar/Wind Harmer
3.126
219272CLEANLIGHT C
Solar/Wind Harmer
0.199
971535AH1-265 GEN
Solar/Wind Harmer
4.38
228260V4-054C
Solar/Wind Harmer
1.047
219688LUMSOLAR_S C
Solar/Wind Harmer
0.193
970453AG2-297 GEN
Solar/Wind Harmer
2.469
228754AB1-001 C
Solar/Wind Harmer
0.121
227927V4-067C
Solar/Wind Harmer
0.17
219607WPEMNERT C
Solar/Wind Harmer
0.311
219224BRL12CT4
Adder
6.624
20717128DIX_Z2-102
Solar/Wind Harmer
0.804
20715728PEM_W1-119
Solar/Wind Harmer
0.321
20715828PEM_W1-120
Solar/Wind Harmer
0.321
231919CHRIST1
Adder
2.554
231920CHRIST2
Adder
2.497
971189AH1-054 GEN
Solar/Wind Harmer
0.624
970025AG2-016 GEN
Solar/Wind Harmer
1.448
233973AC2-185 C
Solar/Wind Harmer
1.872
207459AE1-142 C O1
Solar/Wind Harmer
0.51
234033AF1-007_GEN
Solar/Wind Harmer
11.825
232904IR4
Adder
40.889
232920IR10
Adder
1.597
232432Z2-076 GEN
Solar/Wind Harmer
0.067
233990AG1-397 GEN
Solar/Wind Harmer
0.028
232912OH NUG1
Adder
4.443
232913OH NUG2
Adder
4.384
233923SMA
Solar/Wind Harmer
2.334
232813VAUGHN
Adder
0.294
233955AB2-172 GEN
Solar/Wind Harmer
2.486
231906DC3 NUG
Adder
6.906
231902DC CT7
Adder
5.521
231907DC10
Adder
1.724
233968AD2-076_GEN
Solar/Wind Harmer
3.168
970597AG2-380 GEN
Solar/Wind Harmer
1.99
232436AB1-176 C
Solar/Wind Harmer
0.109
971983AH1-536 GEN
Solar/Wind Harmer
3.534
233935AB2-179 C
Solar/Wind Harmer
1.103
20714328BYD_X4-031
Solar/Wind Harmer
0.101
20714428HOW_X1-037
Solar/Wind Harmer
0.426
971521AH1-258 GEN
Solar/Wind Harmer
0.846
20720428HOL_W1-112
Solar/Wind Harmer
0.105
20635928PARLN3&4
Adder
1.804
219124CAMDEN_STG
50/50
1.356
219286CAMD CO RR
50/50
0.468
230406ST-CC
50/50
5.361
230404GT1-CC
50/50
3.606
228304LOGAN
50/50
29.564
219912AD2-042 GEN
Solar/Wind Harmer
1.435
219766PARADISE C
Solar/Wind Harmer
0.539
219623KINSLEYBEA C
Solar/Wind Harmer
0.685
219236SOUTHERNHQ C
Solar/Wind Harmer
0.097
230430AE1-229_GEN
Solar/Wind Harmer
9.527
230415AB2-049 C
Solar/Wind Harmer
0.198
219906AC1-017 C
Solar/Wind Harmer
0.231
219291REEVESSOUT C
Solar/Wind Harmer
0.058
971553AH1-274 GEN
Solar/Wind Harmer
2.336
228711V2-041C
Solar/Wind Harmer
0.553
228202CUMB CT
Adder
15.027
228729W2-030 C
Solar/Wind Harmer
0.501
219610FLORENCE C
Solar/Wind Harmer
1.028
219348LDSOLAR C
Solar/Wind Harmer
0.444
219221BRL12CT1
Adder
6.624
219223BRL12CT3
Adder
6.624
20716028EGP_W2-019
Solar/Wind Harmer
0.291
20720828JCB_W4-025
Solar/Wind Harmer
0.283
20715028HAN_X4-015
Solar/Wind Harmer
0.186
959561AF2-247 GEN
Solar/Wind Harmer
0.29
972251AH1-710 GEN
Adder
27.658
20636028O CRK C1
Adder
3.715
233971AC1-093 C
Solar/Wind Harmer
0.406
970695AG2-447 GEN
Solar/Wind Harmer
1.856
971667AH1-334 GEN
Solar/Wind Harmer
1.345
972133AH1-634 GEN
Solar/Wind Harmer
5.014
233952AC2-187 GEN
Solar/Wind Harmer
0.567
972073AH1-586 GEN
Solar/Wind Harmer
4.718
233990AG1-397 GEN
Solar/Wind Harmer
0.577
232914OH NUG3
Adder
4.443
232916OH NUG5
Adder
4.443
232921TASLEY2G
Adder
2.597
232406W1-004 FULL
Solar/Wind Harmer
0.504
234015AF2-250 C
Solar/Wind Harmer
0.061
233996TM1833_GEN
Solar/Wind Harmer
0.637
233997TMININ_4.2
Solar/Wind Harmer
0.637
233900O-025 C
Adder
0.592
233940AF2-379 C
Solar/Wind Harmer
0.094
233994AC2-023 GEN
Solar/Wind Harmer
1.349
232907VN8
Adder
15.015
960671AF2-358 GEN
Solar/Wind Harmer
8.942
232417X3-008 C
Solar/Wind Harmer
0.994
233982AB2-133 GEN
Solar/Wind Harmer
2.3
233918AB1-142 GEN
Solar/Wind Harmer
0.468
219727YARDVSOLFA C
Solar/Wind Harmer
0.392
20714528FRN_Y2-051
Solar/Wind Harmer
0.122
219276PARKLANDSO C
Solar/Wind Harmer
0.16
20720528MAN_W1-024
Solar/Wind Harmer
0.073
20716228APLW2-078
Solar/Wind Harmer
0.247
219612MATRIX C
Solar/Wind Harmer
0.046
218438BLK ROCK C
Solar/Wind Harmer
0.034
20635828PARLN1&2
Adder
0.817
20635928PARLN3&4
Adder
0.817
967451AG2-055 C O1
Solar/Wind Harmer
40.283
219230EAGLE PT CT1
50/50
1.647
219235Y2-105
50/50
0.595
219904AC1-010 C
Solar/Wind Harmer
0.647
219258KINSLEYDEP C
Solar/Wind Harmer
0.526
219907AC1-030 C
Solar/Wind Harmer
0.201
230434AG1-499 GEN
Solar/Wind Harmer
0.671
228351V2-046C
Solar/Wind Harmer
2.274
970997AG2-616 GEN
Solar/Wind Harmer
10.419
230511AF1-262
Solar/Wind Harmer
0.196
945431AF1-208 GEN
Solar/Wind Harmer
9.097
228728W1-130C
Solar/Wind Harmer
0.679
218660EHAMPSOLAR C
Solar/Wind Harmer
0.17
219686LUMSOLAR_N C
Solar/Wind Harmer
0.196
219287REEVESEAST C
Solar/Wind Harmer
1.303
228206SHRMN CT
Adder
15.434
228732V1-021 C
Adder
0.168
219304NAMERICA C
Solar/Wind Harmer
0.231
219222BRL12CT2
Adder
6.624
20720728JCB_W1-129
Solar/Wind Harmer
0.186
207522AF2-254 C
Solar/Wind Harmer
0.885
231917EM10
Adder
1.422
231918WEST 1
Adder
1.902
207487AE2-000G4
Solar/Wind Harmer
16.555
233972AC1-094 C
Solar/Wind Harmer
0.344
232901NORTHST
Adder
4.287
232900DEMECSMY
Adder
4.729
972177AH1-672 GEN
Solar/Wind Harmer
6.808
232434Z2-077 GEN
Solar/Wind Harmer
0.126
207445AB1-138_GEN
Solar/Wind Harmer
0.278
20628028LAKEHURS
Adder
0.902
233954AC2-188 GEN
Solar/Wind Harmer
0.567
233950AC2-186 GEN
Solar/Wind Harmer
0.283
232917OH NUG6
Adder
4.424
232915OH NUG4
Adder
4.414
232404W1-003 C
Solar/Wind Harmer
0.504
971195AH1-057 GEN
Solar/Wind Harmer
0.55
233998TM1NIN_3.36
Solar/Wind Harmer
0.637
232428Y3-058 C
Solar/Wind Harmer
0.419
232919VN10
Adder
1.403
965821AG1-450 GEN
Solar/Wind Harmer
2.599
232426Y1-080 FULL
Solar/Wind Harmer
0.095
970277AG2-181 GEN
Solar/Wind Harmer
2.502
233964AF2-378 GEN
Solar/Wind Harmer
0.064
232910NRG_G1
Adder
4.287
234012AE2-112_GEN
Solar/Wind Harmer
1.099
232422X3-066 FULL
Solar/Wind Harmer
0.119
233930AB2-032 GEN
Solar/Wind Harmer
0.394
233915AB1-141 GEN
Solar/Wind Harmer
0.468
963711AG1-223 GEN
Solar/Wind Harmer
0.619
20714828MDF_W3-079
Solar/Wind Harmer
0.128
207454AA2-184 E
Solar/Wind Harmer
0.343
20715228NPK_W1-113
Solar/Wind Harmer
0.12
20742028HF_AC1-207
Solar/Wind Harmer
0.219
217197RE CRAN C
Solar/Wind Harmer
0.135
20635828PARLN1&2
Adder
1.804
219126CAMDEN_CTG
50/50
1.666
219267WHEELBRDEPTF
50/50
0.234
219240MANTUACREK E
50/50
0.761
219726BAT.STORG E
50/50
0.369
972233AH1-701 GEN
50/50
5.793
228304LOGAN
50/50
32.871
228307PCLP GT
50/50
15.939
213400COVANTA DELA
50/50
1.115
219921AF1-264
Solar/Wind Harmer
0.237
219615MILLCREEK C
Solar/Wind Harmer
0.247
228251CARLLS#4
Adder
0.644
230407AD2-065 C
Solar/Wind Harmer
0.134
230433AD2-135 GEN
Solar/Wind Harmer
0.102
230422AE1-104_GEN1
Solar/Wind Harmer
29.724
230425AE1-104_GEN2
Solar/Wind Harmer
29.724
20716428NHV_W2-082
Solar/Wind Harmer
1.103
207500AE2-000G1
Solar/Wind Harmer
16.555
207497AE2-000G2
Solar/Wind Harmer
16.555
207507AE2-000G3
Solar/Wind Harmer
16.555
20636128O CRK C2
Adder
3.387
963401AG1-189 GEN
Solar/Wind Harmer
0.593
20714928UPF_X1-085
Solar/Wind Harmer
0.208
963391AG1-188 GEN
Solar/Wind Harmer
0.978
232416X2-083
Adder
0.236
233939AC1-091 C
Solar/Wind Harmer
0.455
233970AC1-092 C
Solar/Wind Harmer
0.455
971149AH1-027 GEN
Solar/Wind Harmer
1.743
232899W1-062
Adder
4.93
970545AG2-347 GEN
Solar/Wind Harmer
33.092
20628028LAKEHURS
Adder
0.456
231940T-011
Adder
0.376
972069AH1-584 GEN
Solar/Wind Harmer
4.508
972071AH1-585 GEN
Solar/Wind Harmer
4.508
971747AH1-380 GEN
Solar/Wind Harmer
1.803
233901CHERRYDALE C
Solar/Wind Harmer
0.566
232918OH NUG7
Adder
4.414
232905CHERITON_25
Adder
1.234
232408W1-005 C
Solar/Wind Harmer
0.504
232410W1-006 C
Solar/Wind Harmer
0.504
232926CRISFLD1
Adder
0.987
233946AB2-136 GEN
Solar/Wind Harmer
1.989
231131BLOOM ENRGY
Adder
2.171
234036AF2-325 C
Solar/Wind Harmer
0.457
234041AC1-190 GEN
Solar/Wind Harmer
4.453
233987AB2-037 GEN
Solar/Wind Harmer
5.633
213535CROYDN11
Adder
4.756
219114HARTZY_C
Solar/Wind Harmer
0.391
233984AB2-036 GEN
Solar/Wind Harmer
6.019
232424Y1-079 C
Solar/Wind Harmer
0.272
234014AF1-036_GEN
Solar/Wind Harmer
1.293
233944AB2-135 GEN
Solar/Wind Harmer
2.497
233933AB2-153 GEN
Solar/Wind Harmer
0.531
20720628TIN_W1-124
Solar/Wind Harmer
0.342
20641628MLH_W1-032
Solar/Wind Harmer
0.084
20716928W4-060COL
Solar/Wind Harmer
0.195
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.502
G-007ALTFEXP_G-007A->PJM
CMTX
11.581
CBM NorthLTFEXP_CBM-N->PJM
CBM
4.513
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.496
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.545
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
17.921
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.306
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
2.299

Details for CHAN-01DOUBS 500.0 kV Ckt 1 line l/o PJM_500_BG_P4_5_CNSTN_C_SRT-A


Base Case Flowgate

Area:AP/PJM
Facility Description:
CHAN-01DOUBS 500.0 kV Ckt 1 line
Contingency Name:
PJM_500_BG_P4_5_CNSTN_C_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:118.32 %
Rating:4150.0 MVA
Rating Type:B
MVA to Mitigate:4910.18
MW Contribution:8.76
Bus #Bus NameTypeMW Contribution
200192DELTA CT1
50/50
2.178
200194DELTA CT3
50/50
2.178
200204Y1-065-CTG1
50/50
4.512
200054ROCKSP 3
50/50
2.878
232901NORTHST
Adder
10.877
233972AC1-094 C
Solar/Wind Harmer
0.867
232900DEMECSMY
Adder
12.04
232434Z2-077 GEN
Solar/Wind Harmer
0.327
972177AH1-672 GEN
Solar/Wind Harmer
17.53
232404W1-003 C
Solar/Wind Harmer
1.307
232917OH NUG6
Adder
11.473
232915OH NUG4
Adder
11.447
233998TM1NIN_3.36
Solar/Wind Harmer
1.653
971195AH1-057 GEN
Solar/Wind Harmer
1.428
232428Y3-058 C
Solar/Wind Harmer
1.089
232919VN10
Adder
3.659
965821AG1-450 GEN
Solar/Wind Harmer
6.787
232426Y1-080 FULL
Solar/Wind Harmer
0.249
970277AG2-181 GEN
Solar/Wind Harmer
6.537
200200DELTA2 CT1
50/50
3.899
200193DELTA CT2
50/50
2.178
200203Y1-065-STG
50/50
7.823
200055ROCKSP 4
50/50
2.817
233971AC1-093 C
Solar/Wind Harmer
1.025
970695AG2-447 GEN
Solar/Wind Harmer
4.682
972133AH1-634 GEN
Solar/Wind Harmer
12.939
972073AH1-586 GEN
Solar/Wind Harmer
12.229
232406W1-004 FULL
Solar/Wind Harmer
1.307
232914OH NUG3
Adder
11.524
232916OH NUG5
Adder
11.524
232921TASLEY2G
Adder
6.735
233996TM1833_GEN
Solar/Wind Harmer
1.653
233997TMININ_4.2
Solar/Wind Harmer
1.653
233990AG1-397 GEN
Solar/Wind Harmer
1.497
233940AF2-379 C
Solar/Wind Harmer
0.243
234015AF2-250 C
Solar/Wind Harmer
0.157
233900O-025 C
Adder
1.536
233994AC2-023 GEN
Solar/Wind Harmer
3.506
232907VN8
Adder
39.168
960671AF2-358 GEN
Solar/Wind Harmer
23.348
233952AC2-187 GEN
Solar/Wind Harmer
1.467
232417X3-008 C
Solar/Wind Harmer
2.606
972251AH1-710 GEN
Adder
57.775
233918AB1-142 GEN
Solar/Wind Harmer
1.277
233982AB2-133 GEN
Solar/Wind Harmer
6.273
228202CUMB CT
Adder
18.994
228711V2-041C
Solar/Wind Harmer
0.691
971553AH1-274 GEN
Solar/Wind Harmer
2.781
230430AE1-229_GEN
Solar/Wind Harmer
10.075
230415AB2-049 C
Solar/Wind Harmer
0.217
228729W2-030 C
Solar/Wind Harmer
0.66
228304LOGAN
Adder
24.8
219623KINSLEYBEA C
Solar/Wind Harmer
0.483
219291REEVESSOUT C
Solar/Wind Harmer
0.068
213497CHSTR7-9
Adder
3.069
219766PARADISE C
Solar/Wind Harmer
0.355
219912AD2-042 GEN
Solar/Wind Harmer
0.896
219236SOUTHERNHQ C
Solar/Wind Harmer
0.076
213958STHWK5-6
Adder
3.048
213560DLW11-12
Adder
3.039
219906AC1-017 C
Solar/Wind Harmer
0.25
213815MOSER1-3
Adder
3.964
219610FLORENCE C
Solar/Wind Harmer
1.547
219348LDSOLAR C
Solar/Wind Harmer
0.669
219221BRL12CT1
Adder
9.966
219223BRL12CT3
Adder
9.966
20716028EGP_W2-019
Solar/Wind Harmer
0.515
20720828JCB_W4-025
Solar/Wind Harmer
0.503
20715028HAN_X4-015
Solar/Wind Harmer
0.331
959561AF2-247 GEN
Solar/Wind Harmer
0.539
20636028O CRK C1
Adder
7.835
971667AH1-334 GEN
Solar/Wind Harmer
3.042
219727YARDVSOLFA C
Solar/Wind Harmer
1.007
20714528FRN_Y2-051
Solar/Wind Harmer
0.326
219276PARKLANDSO C
Solar/Wind Harmer
0.51
219918AC2-009 C
Solar/Wind Harmer
0.068
20716228APLW2-078
Solar/Wind Harmer
0.975
20720528MAN_W1-024
Solar/Wind Harmer
0.28
967451AG2-055 C O1
Solar/Wind Harmer
191.48
219612MATRIX C
Solar/Wind Harmer
0.203
218438BLK ROCK C
Solar/Wind Harmer
0.15
20635828PARLN1&2
Adder
3.69
20635928PARLN3&4
Adder
3.69
20635028RRCT1&2
Adder
12.969
200035PCHBTM 3
50/50
23.2
200201DELTA2 CT2
50/50
3.899
200034PCHBTM 2
50/50
22.699
200205Y1-065-CTG2
50/50
4.512
971149AH1-027 GEN
Solar/Wind Harmer
4.423
233939AC1-091 C
Solar/Wind Harmer
1.148
233970AC1-092 C
Solar/Wind Harmer
1.148
970545AG2-347 GEN
Solar/Wind Harmer
85.4
232899W1-062
Adder
12.553
233987AB2-037 GEN
Solar/Wind Harmer
14.854
972069AH1-584 GEN
Solar/Wind Harmer
11.685
972071AH1-585 GEN
Solar/Wind Harmer
11.685
233901CHERRYDALE C
Solar/Wind Harmer
1.469
232408W1-005 C
Solar/Wind Harmer
1.307
232410W1-006 C
Solar/Wind Harmer
1.307
232918OH NUG7
Adder
11.447
971747AH1-380 GEN
Solar/Wind Harmer
4.674
232905CHERITON_25
Adder
3.201
232926CRISFLD1
Adder
2.561
231940T-011
Adder
0.973
233946AB2-136 GEN
Solar/Wind Harmer
5.201
234036AF2-325 C
Solar/Wind Harmer
1.195
234041AC1-190 GEN
Solar/Wind Harmer
11.666
233984AB2-036 GEN
Solar/Wind Harmer
16.136
232424Y1-079 C
Solar/Wind Harmer
0.729
231131BLOOM ENRGY
Adder
5.629
234014AF1-036_GEN
Solar/Wind Harmer
3.497
233944AB2-135 GEN
Solar/Wind Harmer
6.755
233933AB2-153 GEN
Solar/Wind Harmer
1.45
232416X2-083
Adder
0.576
228251CARLLS#4
Adder
0.723
230422AE1-104_GEN1
Solar/Wind Harmer
38.594
230425AE1-104_GEN2
Solar/Wind Harmer
38.594
230433AD2-135 GEN
Solar/Wind Harmer
0.116
230407AD2-065 C
Solar/Wind Harmer
0.15
228307PCLP GT
Adder
13.798
228304LOGAN
Adder
27.574
972233AH1-701 GEN
Adder
4.775
219921AF1-264
Solar/Wind Harmer
0.163
213589EDDYSTN4
Adder
89.617
213587EDDYSTN3
Adder
89.611
219615MILLCREEK C
Solar/Wind Harmer
0.267
213815MOSER1-3
Adder
3.964
213815MOSER1-3
Adder
3.964
213535CROYDN11
Adder
11.416
20716428NHV_W2-082
Solar/Wind Harmer
1.973
207500AE2-000G1
Solar/Wind Harmer
34.92
207497AE2-000G2
Solar/Wind Harmer
34.92
207507AE2-000G3
Solar/Wind Harmer
34.92
20636128O CRK C2
Adder
7.144
963401AG1-189 GEN
Solar/Wind Harmer
1.274
963391AG1-188 GEN
Solar/Wind Harmer
2.125
20714928UPF_X1-085
Solar/Wind Harmer
0.451
20628028LAKEHURS
Adder
1.053
219114HARTZY_C
Solar/Wind Harmer
0.923
219817TRENTONSOL C
Solar/Wind Harmer
1.217
20641628MLH_W1-032
Solar/Wind Harmer
0.324
20720628TIN_W1-124
Solar/Wind Harmer
1.099
20716928W4-060COL
Solar/Wind Harmer
0.783
924131AB2-057 GEN
Solar/Wind Harmer
1.132
218440SUMMTASSOC C
Solar/Wind Harmer
0.141
218418LINDEN_G5
Adder
18.869
218419LINDEN_G6
Adder
18.869
972260AH1-715 GEN1
Adder
15.109
20673828FLE_V3-070
Solar/Wind Harmer
0.503
207442AE1-156 GEN
Solar/Wind Harmer
0.817
20676128MHD_W3-029
Solar/Wind Harmer
0.524
219036LINDEN_G7
Adder
18.362
219035LINDEN_G8
Adder
18.1
972261AH1-715 GEN2
Adder
17.577
217081WEATEXAS C
Solar/Wind Harmer
0.094
217202FBANKSOLAR C
Solar/Wind Harmer
0.081
217201HACKENSOLA C
Solar/Wind Harmer
0.08
972237AH1-703 GEN
Adder
11.093
217206BARNGR HS C
Solar/Wind Harmer
0.034
217086KRNY_131
Adder
10.212
217083KRNY_132
Adder
10.126
20671828STAW2-080
Solar/Wind Harmer
0.115
217204WCALDSOLAR C
Solar/Wind Harmer
0.08
20674528F3S_W2-016
Solar/Wind Harmer
1.541
20676228FRD_X1-012
Solar/Wind Harmer
0.646
207471AF2-354 C
Solar/Wind Harmer
0.558
20674928WA_W3-044
Solar/Wind Harmer
0.526
964851AG1-348 GEN
Solar/Wind Harmer
1.917
20634528N27_Y2-018
Solar/Wind Harmer
0.293
20465127PORT CT
Adder
4.34
20674128FR_U2-059
Solar/Wind Harmer
0.201
966111AG1-480 GEN
Solar/Wind Harmer
0.094
966111AG1-480 GEN
Solar/Wind Harmer
3.579
211065PSPA IPP
Solar/Wind Harmer
0.487
211065PSPA IPP
Solar/Wind Harmer
0.487
208972BECR K09
Solar/Wind Harmer
1.098
961541AF2-445A GEN
Solar/Wind Harmer
3.355
209029WAYMART-WD
Solar/Wind Harmer
2.976
209009PEIP 2
Adder
8.081
209010PEIP 1
Adder
3.661
209010PEIP 1
Adder
0.536
961431AF2-434 GEN
Solar/Wind Harmer
1.013
209054AE2-059 GEN
Solar/Wind Harmer
1.689
209059AE2-084 GEN
Solar/Wind Harmer
2.494
946751AF1-339 GEN
Solar/Wind Harmer
0.992
209130AF1-271A GEN
Solar/Wind Harmer
2.785
20465527S.RDG CT
Adder
2.633
20478527GLRA_Q45
Adder
0.304
209137AF2-361 C
Solar/Wind Harmer
2.566
238175AF1-290_GEN
Solar/Wind Helper
0.158
315651AD1-115 GEN
Solar/Wind Helper
1.005
316447AC1-158 HLD
Solar/Wind Helper
3.655
238169AE2-226 GEN1
Solar/Wind Helper
0.722
238170AE2-226 GEN2
Solar/Wind Helper
0.722
966001AG1-469 GEN
Solar/Wind Helper
0.309
316468AD1-105 GEN
Solar/Wind Helper
1.419
316077AC2-138 C
Solar/Wind Helper
0.265
966871AG1-558 GEN
Solar/Wind Helper
0.38
316487AF1-042 GEN
Solar/Wind Helper
0.284
316075AC2-137 C
Solar/Wind Helper
0.426
3143526WINTERP
Solar/Wind Helper
1.451
3142946ENON
Solar/Wind Helper
0.028
316240AF1-291 C
Solar/Wind Helper
0.372
316033AB2-134 GEN
Solar/Wind Helper
0.948
315697AD1-025 GEN
Solar/Wind Helper
3.151
316236AE1-162_GEN
Solar/Wind Helper
0.369
316036AC1-147 C
Solar/Wind Helper
0.416
316316AC1-027 C
Solar/Wind Helper
0.431
3142956BIRDNECK
Solar/Wind Helper
0.184
316185AD1-033 GEN
Solar/Wind Helper
1.283
3145506HICKORY
Solar/Wind Helper
1.091
3145506HICKORY
Solar/Wind Helper
0.654
3145506HICKORY
Solar/Wind Helper
0.164
316339AD2-160 GEN
Solar/Wind Helper
1.037
235020AA1-095 C
Solar/Wind Helper
0.051
316018AA1-139 ULT2
Solar/Wind Helper
1.171
316017AA1-139 ULT1
Solar/Wind Helper
1.244
3137176SLIGO L2192
Solar/Wind Helper
1.083
23777901MDS_W4-102
Solar/Wind Helper
0.17
3130086AYDLETT
Solar/Wind Helper
1.088
3146386ELIZ CT
Solar/Wind Helper
0.271
316431W1029_GEN1
Solar/Wind Helper
1.092
316433W1029_GEN2
Solar/Wind Helper
1.092
3146516WINFALL
Solar/Wind Helper
0.27
3146516WINFALL
Solar/Wind Helper
0.27
3146516WINFALL
Solar/Wind Helper
0.27
3146626S HERTFORD
Solar/Wind Helper
0.27
3146626S HERTFORD
Solar/Wind Helper
0.27
3144356SAPONY
Solar/Wind Helper
0.483
315742AE1-103 GEN
Solar/Wind Helper
0.433
3132123MT JACKSON
Solar/Wind Helper
0.835
3146776BUCKING
Solar/Wind Helper
1.06
3146776BUCKING
Solar/Wind Helper
0.086
3145893MURPHYS
Solar/Wind Helper
0.378
3145893MURPHYS
Solar/Wind Helper
0.474
3146173TUNIS
Solar/Wind Helper
0.263
3146173TUNIS
Solar/Wind Helper
0.263
315821AE2-092 GEN
Solar/Wind Helper
2.433
316181AB2-040 GEN
Solar/Wind Helper
1.875
3147133PAMPLIN
Solar/Wind Helper
0.261
3147133PAMPLIN
Solar/Wind Helper
0.209
3142666NORTHAMPTON
Solar/Wind Helper
0.261
3142666NORTHAMPTON
Solar/Wind Helper
0.261
3142666NORTHAMPTON
Solar/Wind Helper
0.261
3142666NORTHAMPTON
Solar/Wind Helper
0.156
316426AA2-053 GEN
Solar/Wind Helper
1.486
3145593CAROLNA
Solar/Wind Helper
0.26
3145593CAROLNA
Solar/Wind Helper
0.26
3145796HORNRTN
Solar/Wind Helper
0.778
316034AC1-036 C
Solar/Wind Helper
0.271
3145933PARMELE
Solar/Wind Helper
0.514
3145933PARMELE
Solar/Wind Helper
0.257
316274AC1-208 GEN
Solar/Wind Helper
1.567
226929AD2-058 GEN
Solar/Wind Helper
0.099
3146843MT LREL
Solar/Wind Helper
0.253
3146843MT LREL
Solar/Wind Helper
0.253
237034AC2-136 C
Solar/Wind Helper
0.207
316222AC1-221 GEN
Solar/Wind Helper
1.387
316197AC1-042 GEN
Solar/Wind Helper
0.215
270013AE1-250 PV
Solar/Wind Helper
0.845
237002AB1-128_GEN
Solar/Wind Helper
0.363
200202DELTA2 ST
50/50
6.616
200195DELTA ST
50/50
3.366
200052ROCKSP 1
50/50
2.849
200053ROCKSP 2
50/50
2.789
233973AC2-185 C
Solar/Wind Harmer
4.722
234033AF1-007_GEN
Solar/Wind Harmer
30.517
232904IR4
Adder
105.52
232920IR10
Adder
4.124
232432Z2-076 GEN
Solar/Wind Harmer
0.172
232912OH NUG1
Adder
11.524
232913OH NUG2
Adder
11.37
233923SMA
Solar/Wind Harmer
6.059
233990AG1-397 GEN
Solar/Wind Harmer
0.072
233955AB2-172 GEN
Solar/Wind Harmer
6.515
232813VAUGHN
Adder
0.766
231906DC3 NUG
Adder
18.081
231902DC CT7
Adder
14.455
231907DC10
Adder
4.514
233968AD2-076_GEN
Solar/Wind Harmer
8.568
970597AG2-380 GEN
Solar/Wind Harmer
5.38
232436AB1-176 C
Solar/Wind Harmer
0.296
971983AH1-536 GEN
Solar/Wind Harmer
9.641
233935AB2-179 C
Solar/Wind Harmer
3.174
231919CHRIST1
Adder
5.579
231920CHRIST2
Adder
5.455
970453AG2-297 GEN
Solar/Wind Harmer
3.175
228260V4-054C
Solar/Wind Harmer
1.177
228309CCLP NUG
Adder
29.607
228309CCLP NUG
Adder
28.163
972141AH1-641 GEN
Solar/Wind Harmer
3.294
964001AG1-254 GEN
Solar/Wind Harmer
2.327
971011AG2-627 GEN
Solar/Wind Harmer
8.757
971535AH1-265 GEN
Solar/Wind Harmer
4.865
227927V4-067C
Solar/Wind Harmer
0.227
228754AB1-001 C
Solar/Wind Harmer
0.159
219137THOSOLAR C
Solar/Wind Harmer
1.368
219272CLEANLIGHT C
Solar/Wind Harmer
0.206
219688LUMSOLAR_S C
Solar/Wind Harmer
0.228
219914AD2-027 C
Solar/Wind Harmer
0.676
213942SCHUYLKILL
Adder
3.986
213942SCHUYLKILL
Adder
3.048
213957STHWK3-4
Adder
3.048
213957STHWK3-4
Adder
3.048
213561DLWR9-10
Adder
3.975
213561DLWR9-10
Adder
3.039
219607WPEMNERT C
Solar/Wind Harmer
0.468
219224BRL12CT4
Adder
9.966
214067T20SOLAR
Solar/Wind Harmer
0.281
213611FALLS1-3
Adder
3.929
213611FALLS1-3
Adder
3.929
20717128DIX_Z2-102
Solar/Wind Harmer
1.465
20715728PEM_W1-119
Solar/Wind Harmer
0.593
20715828PEM_W1-120
Solar/Wind Harmer
0.593
970025AG2-016 GEN
Solar/Wind Harmer
3.139
971189AH1-054 GEN
Solar/Wind Harmer
1.307
207459AE1-142 C O1
Solar/Wind Harmer
1.169
219620RIDERU C
Solar/Wind Harmer
0.062
20714328BYD_X4-031
Solar/Wind Harmer
0.312
20714428HOW_X1-037
Solar/Wind Harmer
1.363
971521AH1-258 GEN
Solar/Wind Harmer
2.984
20720428HOL_W1-112
Solar/Wind Harmer
0.381
20635928PARLN3&4
Adder
8.147
218455CINNBAY_CGEN
Adder
2
218526CNTRALGAS2 C
Solar/Wind Harmer
0.408
218524CNTRALGAS1 C
Solar/Wind Harmer
0.407
20675528CPH_W2-050
Solar/Wind Harmer
0.514
218404KENILWRTH C
Adder
1.432
217167KRNY_14
Adder
10.191
217086KRNY_131
Adder
10.104
217147KRNY_1212
Adder
9.693
217147KRNY_1212
Adder
9.52
217146KRNY_1234
Adder
9.498
217146KRNY_1234
Adder
9.433
966261AG1-495 GEN
Solar/Wind Harmer
1.963
20676328BVR_Y1-020
Solar/Wind Harmer
0.362
207511W3-106 GEN
Solar/Wind Harmer
0.717
207530AG1-191 GEN
Solar/Wind Harmer
1.503
20674828DL_W4-046
Solar/Wind Harmer
0.705
971009AG2-626 GEN
Solar/Wind Harmer
1.787
207408W3-077 C
Solar/Wind Harmer
0.552
20675728RH_W2-091
Solar/Wind Harmer
0.373
20675928HOL_W4-097
Solar/Wind Harmer
0.142
207484AF2-139 C O1
Solar/Wind Harmer
0.551
20675128HRM_W1-127
Solar/Wind Harmer
0.186
966421AG1-511 GEN
Solar/Wind Harmer
9.372
20462827N BANGR8
Adder
0.78
209116AE2-175 GEN
Solar/Wind Harmer
4.454
961261AF2-417 GEN
Solar/Wind Harmer
1.054
209026WIENIPP4
Adder
5.601
209045AE2-271 GEN
Solar/Wind Harmer
16.942
959431AF2-234 GEN
Solar/Wind Harmer
1.981
964051AG1-259 GEN
Solar/Wind Harmer
1.329
964061AG1-260 GEN
Solar/Wind Harmer
1.329
959421AF2-233 GEN
Solar/Wind Harmer
0.991
20486527WR_V4-052
Adder
1.062
208862AG1-362 C
Solar/Wind Harmer
0.769
20390726Y2-042
Adder
2.77
20334726NME_Y1-047
Adder
2.451
203926AA2-133 GEN
Adder
2.264
205951AE1-129_GEN
Solar/Wind Harmer
7.582
3138216PACIFIC
Solar/Wind Helper
0.054
316411AF1-147_GEN1
Solar/Wind Helper
1.09
316415AF1-147_GEN2
Solar/Wind Helper
1.09
3141426STAFORD
Solar/Wind Helper
0.066
316164AC1-076 GEN
Solar/Wind Helper
1.419
238152AF2-075_GEN
Solar/Wind Helper
0.701
316223AC1-118
Solar/Wind Helper
0.434
23546401DTGZ2-030
Solar/Wind Helper
0.089
3141813NORNECK
Solar/Wind Helper
0.282
316312AB1-027
Solar/Wind Helper
0.534
3141783LANCAST
Solar/Wind Helper
0.168
3141783LANCAST
Solar/Wind Helper
0.112
3138133OCRAN
Solar/Wind Helper
0.084
3141913WHIT STONE
Solar/Wind Helper
0.28
316059AD1-063 C
Solar/Wind Helper
0.281
3143873LANEXA
Solar/Wind Helper
0.167
315662AE1-191 GEN
Solar/Wind Helper
1.5
315666AE1-190 GEN
Solar/Wind Helper
0.375
957601AF2-054 GEN
Solar/Wind Helper
0.374
3141873WAN 176
Solar/Wind Helper
0.056
316233AE1-074 FULL
Solar/Wind Helper
0.426
957831AF2-077 GEN
Solar/Wind Helper
0.374
316132AB2-190 GEN1
Solar/Wind Helper
1.578
316369SG1_INVT
Solar/Wind Helper
1.326
3143316POE
Solar/Wind Helper
1.085
316349AD2-085 GEN
Solar/Wind Helper
1.246
319010AE1-072 C
Solar/Wind Helper
3.109
316305AF2-043 C
Solar/Wind Helper
0.366
313526AB2-022
Solar/Wind Helper
0.413
3146486SUNBURY
Solar/Wind Helper
0.271
3146486SUNBURY
Solar/Wind Helper
0.271
316321Z2-027
Solar/Wind Helper
0.413
3145176PASQUOTANK
Solar/Wind Helper
0.168
316315AB2-025 C
Solar/Wind Helper
0.411
315611Z1-036_GEN2
Solar/Wind Helper
1.479
3130156CHOWAN
Solar/Wind Helper
0.268
3130156CHOWAN
Solar/Wind Helper
0.268
315816AE2-034 GEN
Solar/Wind Helper
1.216
3138266HYDRAULIC
Solar/Wind Helper
0.012
3138266HYDRAULIC
Solar/Wind Helper
0.008
3130546PLYMOUTH
Solar/Wind Helper
0.265
315732AD1-074 GEN1
Solar/Wind Helper
3.021
315733AD1-074 GEN2
Solar/Wind Helper
3.021
315735AD1-075 GEN1
Solar/Wind Helper
1.51
3146206CASHIE
Solar/Wind Helper
0.264
3145893MURPHYS
Solar/Wind Helper
0.711
3145893MURPHYS
Solar/Wind Helper
0.264
3145513AHOSKIE
Solar/Wind Helper
0.118
961941AG1-037 GEN
Solar/Wind Helper
0.088
3145513AHOSKIE
Solar/Wind Helper
0.262
946281AF1-292 GEN
Solar/Wind Helper
0.263
3146043SEABORD
Solar/Wind Helper
0.262
3145683EARLEYS
Solar/Wind Helper
0.524
3145683EARLEYS
Solar/Wind Helper
0.262
3145683EARLEYS
Solar/Wind Helper
0.262
315607AA1-063A GEN
Solar/Wind Helper
1.494
316087AB2-174 GEN
Solar/Wind Helper
1.83
3137643SOCKMAN
Solar/Wind Helper
1.042
3148133STUARTS
Solar/Wind Helper
0.156
3148013FISHERV
Solar/Wind Helper
0.149
3145796HORNRTN
Solar/Wind Helper
0.83
3145796HORNRTN
Solar/Wind Helper
0.104
3144303KENBRDG
Solar/Wind Helper
0.207
3146033SCOT NK
Solar/Wind Helper
1.036
316239AB2-077_GEN
Solar/Wind Helper
0.345
316238AB2-078_GEN
Solar/Wind Helper
0.345
316005AA1-067
Solar/Wind Helper
0.292
3145746EVERETS
Solar/Wind Helper
1.018
3145746EVERETS
Solar/Wind Helper
0.256
3145746EVERETS
Solar/Wind Helper
0.256
3145746EVERETS
Solar/Wind Helper
0.256
270494AE1-108_GEN
Solar/Wind Helper
3.41
316420AA1-050 GEN
Solar/Wind Helper
1.456
3145573BETHELC
Solar/Wind Helper
0.254
3145573BETHELC
Solar/Wind Helper
0.254
238208AF1-136 C
Solar/Wind Helper
0.196
238109AE1-109 GEN2
Solar/Wind Helper
0.094
238110AE1-109 GEN3
Solar/Wind Helper
0.094
316118AC1-105 GEN
Solar/Wind Helper
0.977
3148463FAIRFLD
Solar/Wind Helper
0.251
3147173SINAI
Solar/Wind Helper
0.25
3147243WELCO
Solar/Wind Helper
0.156
316123AC1-075 GEN
Solar/Wind Helper
1.467
270455AD2-022 GEN
Solar/Wind Helper
1.374
270457AD2-023 GEN
Solar/Wind Helper
0.905
237085AD2-009_GEN
Solar/Wind Helper
1.357
233964AF2-378 GEN
Solar/Wind Harmer
0.166
233954AC2-188 GEN
Solar/Wind Harmer
1.467
233950AC2-186 GEN
Solar/Wind Harmer
0.733
232910NRG_G1
Adder
11.214
234012AE2-112_GEN
Solar/Wind Harmer
2.972
232422X3-066 FULL
Solar/Wind Harmer
0.323
233930AB2-032 GEN
Solar/Wind Harmer
1.075
233915AB1-141 GEN
Solar/Wind Harmer
1.277
231918WEST 1
Adder
4.241
231917EM10
Adder
2.963
228206SHRMN CT
Adder
19.049
228732V1-021 C
Adder
0.217
945431AF1-208 GEN
Solar/Wind Harmer
9.894
970997AG2-616 GEN
Solar/Wind Harmer
10.979
228351V2-046C
Solar/Wind Harmer
2.305
230511AF1-262
Solar/Wind Harmer
0.209
228728W1-130C
Solar/Wind Harmer
0.759
230434AG1-499 GEN
Solar/Wind Harmer
0.662
219258KINSLEYDEP C
Solar/Wind Harmer
0.366
218660EHAMPSOLAR C
Solar/Wind Harmer
0.197
213497CHSTR7-9
Adder
3.069
213497CHSTR7-9
Adder
3.069
219904AC1-010 C
Solar/Wind Harmer
0.426
219287REEVESEAST C
Solar/Wind Harmer
1.515
219686LUMSOLAR_N C
Solar/Wind Harmer
0.228
219907AC1-030 C
Solar/Wind Harmer
0.156
213958STHWK5-6
Adder
3.048
213560DLW11-12
Adder
3.039
219304NAMERICA C
Solar/Wind Harmer
0.347
219222BRL12CT2
Adder
9.966
213611FALLS1-3
Adder
3.929
214194N WALES4
Adder
0.947
20720728JCB_W1-129
Solar/Wind Harmer
0.331
207522AF2-254 C
Solar/Wind Harmer
1.592
207487AE2-000G4
Solar/Wind Harmer
34.92
207445AB1-138_GEN
Solar/Wind Harmer
0.642
20628028LAKEHURS
Adder
2.083
963711AG1-223 GEN
Solar/Wind Harmer
1.635
20714828MDF_W3-079
Solar/Wind Harmer
0.338
219680HOPEWELLV C1
Solar/Wind Harmer
0.084
207454AA2-184 E
Solar/Wind Harmer
1.103
20715228NPK_W1-113
Solar/Wind Harmer
0.474
20742028HF_AC1-207
Solar/Wind Harmer
0.865
217197RE CRAN C
Solar/Wind Harmer
0.591
20635828PARLN1&2
Adder
8.147
20635028RRCT1&2
Adder
12.769
20635128RRCT3&4
Adder
12.326
218428ETC SOLAR C
Solar/Wind Harmer
0.039
217213AMBOY SO C
Solar/Wind Harmer
0.139
972275AH1-722 GEN
Adder
34.688
207528AF2-192 GEN
Solar/Wind Harmer
0.608
20673628F1S_V4-069
Solar/Wind Harmer
0.197
20675428EAM_W2-061
Solar/Wind Harmer
0.207
218449LINSOLAR C
Solar/Wind Harmer
1.104
20676428JCR_X2-075
Solar/Wind Harmer
0.375
217209CENTRL HS C
Solar/Wind Harmer
0.049
217121ECCF
Adder
0.476
217083KRNY_132
Adder
10.191
217208PARK ELE C
Solar/Wind Harmer
0.028
207439AE1-081 C O1
Solar/Wind Harmer
0.065
20674328GAR_V4-001
Solar/Wind Harmer
0.12
20675828AU_W4-064
Solar/Wind Harmer
0.189
971519AH1-257 GEN
Solar/Wind Harmer
2.75
207518AF1-320_GEN
Solar/Wind Harmer
3.986
207437AD2-070 GEN
Solar/Wind Harmer
0.329
20465127PORT CT
Adder
3.271
20671928W4-073
Solar/Wind Harmer
0.471
966181AG1-487 GEN
Solar/Wind Harmer
4.076
208909MACR G3
Adder
173.279
961301AF2-421 GEN
Solar/Wind Harmer
1.051
963151AG1-164 GEN
Solar/Wind Harmer
1.051
209023WIENIPP1
Adder
11.334
209025WIENIPP3
Adder
5.658
212266LOR1
Solar/Wind Harmer
0.134
970237AG2-161 GEN
Solar/Wind Harmer
3.587
209010PEIP 1
Adder
0.666
961341AF2-425 GEN
Solar/Wind Harmer
1.016
212174INGE
Adder
1.123
205941AD2-115 GEN
Solar/Wind Harmer
0.937
212507AE2-042_GEN
Solar/Wind Harmer
2.992
946731AF1-337 GEN
Solar/Wind Harmer
0.992
209071AE2-133 GEN
Solar/Wind Harmer
1.678
970665AG2-430 GEN
Solar/Wind Harmer
9.83
209018SUNBIPCT
Adder
7.379
20467927PC_Q59Y356
Adder
0.836
20465527S.RDG CT
Adder
2.721
972241AH1-705 GEN
Adder
5.64
209008PAXT IPP
Adder
1.813
970679AG2-439 GEN
Solar/Wind Harmer
1.158
200917MEHOOPANY_G
Solar/Wind Harmer
3.648
205967AE2-211_GEN
Solar/Wind Harmer
5.774
972271AH1-720 GEN
Adder
6.105
941421AE2-139 GEN
Solar/Wind Harmer
2.743
20328326MANOR_T86
Adder
0.126
316006AB2-029 C
Solar/Wind Helper
0.146
316045AC1-158 PL2
Solar/Wind Helper
5.316
316254AC1-120 GEN1
Solar/Wind Helper
1.368
3147666LOUISA
Solar/Wind Helper
1.161
316192AB2-158 GEN
Solar/Wind Helper
1.949
238148AE2-230_GEN2
Solar/Wind Helper
0.493
316337AD2-073 GEN
Solar/Wind Helper
0.43
964211AG1-282 GEN
Solar/Wind Helper
0.38
3141726DUNNSVL
Solar/Wind Helper
1.128
3142416OLDCHRC
Solar/Wind Helper
0.729
3142416OLDCHRC
Solar/Wind Helper
0.279
3138133OCRAN
Solar/Wind Helper
0.168
3141766HARMONY
Solar/Wind Helper
0.056
3143526WINTERP
Solar/Wind Helper
1.451
3142433PROV 92
Solar/Wind Helper
1.116
3143226MDLTHAN
Solar/Wind Helper
0.279
3142543TWELFTH
Solar/Wind Helper
0.027
316159AE1-175 C
Solar/Wind Helper
0.42
316458AB2-190 GEN2
Solar/Wind Helper
1.578
3145336SMITFLD
Solar/Wind Helper
1.097
316294AC1-161 GEN
Solar/Wind Helper
5.011
316381AD1-082 GEN
Solar/Wind Helper
1.417
316375AC2-012 GEN
Solar/Wind Helper
0.716
316072AD1-144
Solar/Wind Helper
0.312
316336AC2-165 C
Solar/Wind Helper
1.47
316388AE2-253 GEN
Solar/Wind Helper
1.037
3146456SLIGO L269
Solar/Wind Helper
0.272
316246AF1-032 C
Solar/Wind Helper
0.311
3146516WINFALL
Solar/Wind Helper
0.875
3146516WINFALL
Solar/Wind Helper
0.27
315800Z1-036_GEN1
Solar/Wind Helper
1.479
3130156CHOWAN
Solar/Wind Helper
0.268
3145663CRESWEL
Solar/Wind Helper
0.745
316322AB2-045
Solar/Wind Helper
0.295
3146776BUCKING
Solar/Wind Helper
0.106
3146926FARMVIL
Solar/Wind Helper
0.158
316023GEN1_S
Solar/Wind Helper
1.004
3146206CASHIE
Solar/Wind Helper
0.264
3145893MURPHYS
Solar/Wind Helper
1.054
3146173TUNIS
Solar/Wind Helper
0.263
3147983MERCK5
Solar/Wind Helper
0.105
316097T157 G90
Solar/Wind Helper
1.209
3145683EARLEYS
Solar/Wind Helper
0.262
3146263WOODLND
Solar/Wind Helper
0.261
316190AA2-174 GEN
Solar/Wind Helper
0.017
3145963POPLR C
Solar/Wind Helper
0.261
316011AB1-132 GEN
Solar/Wind Helper
2.803
3145823KELFORD
Solar/Wind Helper
0.26
316174AB2-169 GEN
Solar/Wind Helper
0.662
3145783HORNRTN
Solar/Wind Helper
0.26
3145796HORNRTN
Solar/Wind Helper
0.856
3145796HORNRTN
Solar/Wind Helper
0.259
316129AC1-054 GEN
Solar/Wind Helper
1.276
316212AC1-099_GEN
Solar/Wind Helper
1.155
316237AB2-079_GEN
Solar/Wind Helper
0.345
3145746EVERETS
Solar/Wind Helper
0.256
3145746EVERETS
Solar/Wind Helper
0.256
315687AD1-152 GEN
Solar/Wind Helper
1.374
315722AD1-056 GEN
Solar/Wind Helper
1.374
316494AC1-189 GEN
Solar/Wind Helper
1.555
3146233WITAKRS
Solar/Wind Helper
1.01
961671AG1-007 GEN
Solar/Wind Helper
0.182
3146083TARBORO
Solar/Wind Helper
0.254
3145543BTLEBRO
Solar/Wind Helper
0.252
3145543BTLEBRO
Solar/Wind Helper
0.202
316359AB2-059 GEN
Solar/Wind Helper
1.922
316049AB1-081 GEN
Solar/Wind Helper
1.537
316003AC1-222 GEN
Solar/Wind Helper
1.076
237080AD1-060 GEN
Solar/Wind Helper
0.298
964991AG1-363 GEN
Solar/Wind Helper
3.503
237038AE2-054 C
Solar/Wind Helper
0.229
3147123OTTER R
Solar/Wind Helper
0.138
3147312GRETNA
Solar/Wind Helper
0.183
3146802CHATHAM
Solar/Wind Helper
0.172
270016AE1-250 BESS
Solar/Wind Helper
0.845
270173AC1-122 GEN
Solar/Wind Helper
1.452
20635128RRCT3&4
Adder
10.752
219908AB1-139 C
Solar/Wind Harmer
0.419
219919AE1-041 FULL
Solar/Wind Harmer
0.044
219249CENTRALDIV C
Solar/Wind Harmer
0.044
20673728F2S_V4-070
Solar/Wind Harmer
0.197
217211CAMDEN ST C
Solar/Wind Harmer
0.027
217186ESSEX_G9
Adder
17.527
217169METRODIV C
Solar/Wind Harmer
0.044
217194REDH C
Solar/Wind Harmer
0.54
20676728BRNX1-095
Solar/Wind Harmer
0.193
207510AF2-138 C
Solar/Wind Harmer
1.944
20674628WNG_W3-110
Solar/Wind Harmer
0.441
971007AG2-625 GEN
Solar/Wind Harmer
2.803
20466127PORT 5CT
Adder
28.867
20633028GILCT9
Adder
30.801
966181AG1-487 GEN
Solar/Wind Harmer
0.273
20465427SHAW CT
Adder
4.194
963161AG1-165 GEN
Solar/Wind Harmer
1.051
209025WIENIPP3
Adder
5.543
963071AG1-156 GEN
Solar/Wind Harmer
2.881
970095AG2-074 GEN
Solar/Wind Harmer
6.538
209027LOR2_Q27
Solar/Wind Harmer
4.671
209022WHFR IPP
Adder
3.354
961331AF2-424 GEN
Solar/Wind Harmer
1.016
961421AF2-433 GEN
Solar/Wind Harmer
1.013
957921AF2-086 GEN
Solar/Wind Harmer
0.985
209142AF1-226 GEN
Solar/Wind Harmer
5.866
209093AE2-110 GEN
Solar/Wind Harmer
2.533
209120AE2-241 GEN
Solar/Wind Harmer
3.352
972245AH1-707 GEN
Adder
5.462
946691AF1-333 GEN
Solar/Wind Harmer
0.992
946741AF1-338 GEN
Solar/Wind Harmer
0.992
972221AH1-695 GEN
Adder
123.484
209067AE2-060 GEN
Solar/Wind Harmer
1.327
3141196NOKESVL
Solar/Wind Helper
1.258
316044AC1-158 PL1
Solar/Wind Helper
1.661
316450AC1-158 RIC
Solar/Wind Helper
0.443
316170AC1-121 GEN2
Solar/Wind Helper
0.456
3132273ORANGE
Solar/Wind Helper
0.058
3147666LOUISA
Solar/Wind Helper
0.668
966881AG1-559 GEN
Solar/Wind Helper
0.389
238147AE2-230_GEN1
Solar/Wind Helper
0.491
238149AF1-291A_GEN
Solar/Wind Helper
0.14
3141906WESTMOR
Solar/Wind Helper
0.114
316473AC1-191 GEN
Solar/Wind Helper
1.722
237061AD1-155 GEN
Solar/Wind Helper
0.053
316404AE1-155 C
Solar/Wind Helper
2.376
316484AD2-074 GEN
Solar/Wind Helper
0.542
316280AD1-041 GEN
Solar/Wind Helper
0.938
316156AD2-030 GEN
Solar/Wind Helper
0.421
3142946ENON
Solar/Wind Helper
0.093
316382AG1-145 C
Solar/Wind Helper
0.372
315839AE2-212 C
Solar/Wind Helper
0.37
3145336SMITFLD
Solar/Wind Helper
0.11
315773AC2-141 GEN
Solar/Wind Helper
5.898
316313AB2-026
Solar/Wind Helper
0.417
316258AE1-075 C
Solar/Wind Helper
0.375
316405AF2-144 C
Solar/Wind Helper
0.313
3144536CHRHLND
Solar/Wind Helper
0.041
3144873MCLAUGH
Solar/Wind Helper
0.007
3146456SLIGO L269
Solar/Wind Helper
0.272
316320Y1-086
Solar/Wind Helper
0.121
316435W1029_GEN3
Solar/Wind Helper
1.092
3146516WINFALL
Solar/Wind Helper
0.27
3146626S HERTFORD
Solar/Wind Helper
0.27
3145273HOLLAND
Solar/Wind Helper
0.202
3146376EDENTON
Solar/Wind Helper
0.268
315614AA2-178 GEN
Solar/Wind Helper
1.621
3146776BUCKING
Solar/Wind Helper
0.095
315737AD1-076 GEN
Solar/Wind Helper
2.584
3146926FARMVIL
Solar/Wind Helper
0.158
316365GEN2_N
Solar/Wind Helper
1.004
3146206CASHIE
Solar/Wind Helper
0.264
3145893MURPHYS
Solar/Wind Helper
0.094
3145893MURPHYS
Solar/Wind Helper
0.264
3146173TUNIS
Solar/Wind Helper
0.263
316095T157 G97
Solar/Wind Helper
1.209
3156021HOLLOMANSOL
Solar/Wind Helper
1.997
316463AE2-346 GEN
Solar/Wind Helper
0.24
316140AB2-099
Solar/Wind Helper
0.1
942461AE2-259 GEN
Solar/Wind Helper
1.768
966621AG1-532 GEN
Solar/Wind Helper
0.239
316499AE2-029_GEN
Solar/Wind Helper
0.881
3146263WOODLND
Solar/Wind Helper
0.261
313506AB2-031 GEN
Solar/Wind Helper
1.186
3147133PAMPLIN
Solar/Wind Helper
0.819
3142666NORTHAMPTON
Solar/Wind Helper
0.261
3147043LAWRENC
Solar/Wind Helper
0.156
3145963POPLR C
Solar/Wind Helper
0.261
316317KELFORD C
Solar/Wind Helper
0.222
3145823KELFORD
Solar/Wind Helper
0.26
316478AD1-087 GEN
Solar/Wind Helper
1.27
316486AD2-202 GEN
Solar/Wind Helper
0.372
3148013FISHERV
Solar/Wind Helper
0.26
3145796HORNRTN
Solar/Wind Helper
1.037
3145796HORNRTN
Solar/Wind Helper
0.259
315785AD2-033 C
Solar/Wind Helper
3.016
316210AC1-098 GEN
Solar/Wind Helper
2.079
316131AB2-060 GEN
Solar/Wind Helper
1.568
3145933PARMELE
Solar/Wind Helper
0.257
23583801GRNGAP
Solar/Wind Helper
4.398
3145746EVERETS
Solar/Wind Helper
0.256
3145746EVERETS
Solar/Wind Helper
0.256
315724AD1-057 GEN
Solar/Wind Helper
0.756
316327AA2-057 GEN
Solar/Wind Helper
1.454
3146233WITAKRS
Solar/Wind Helper
0.273
3146233WITAKRS
Solar/Wind Helper
0.172
3146073TAR RVR
Solar/Wind Helper
0.254
3146083TARBORO
Solar/Wind Helper
0.254
3138543CONSLDL
Solar/Wind Helper
0.167
3145543BTLEBRO
Solar/Wind Helper
0.252
3145543BTLEBRO
Solar/Wind Helper
0.252
238108AE1-109 GEN1
Solar/Wind Helper
0.094
238221AF1-254 C O1
Solar/Wind Helper
0.248
315616AA1-038_C
Solar/Wind Helper
1.138
316248AF1-058 C
Solar/Wind Helper
0.336
227287AC2-120 GEN
Solar/Wind Helper
0.335
226910AB2-157 C
Solar/Wind Helper
0.014
316283AC2-100 C
Solar/Wind Helper
1.295
235067AD1-061 GEN
Solar/Wind Helper
0.416
3147312GRETNA
Solar/Wind Helper
0.046
270197AD1-017 GEN1
Solar/Wind Helper
1.223
270018AE2-047 C O1
Solar/Wind Helper
0.79
HAMLETPJM->LTFIMP_HAMLET
CLTF
5.987
G-007ALTFEXP_G-007A->PJM
CMTX
56.398
CBM NorthLTFEXP_CBM-N->PJM
CBM
83.022
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
4.56
BlueGrassPJM->LTFIMP_BlueG
CLTF
14.213
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
148.565
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.493
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
21.603

Details for CHAN-01DOUBS 500.0 kV Ckt 1 line l/o BGE_P4_GRACETON_51_SRT-A


Base Case Flowgate

Area:AP/PJM
Facility Description:
CHAN-01DOUBS 500.0 kV Ckt 1 line
Contingency Name:
BGE_P4_GRACETON_51_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:118.28 %
Rating:4150.0 MVA
Rating Type:B
MVA to Mitigate:4908.72
MW Contribution:8.76
Bus #Bus NameTypeMW Contribution
200202DELTA2 ST
50/50
6.616
200195DELTA ST
50/50
3.366
200052ROCKSP 1
50/50
2.849
200053ROCKSP 2
50/50
2.789
233973AC2-185 C
Solar/Wind Harmer
4.722
234033AF1-007_GEN
Solar/Wind Harmer
30.517
232904IR4
Adder
105.52
232920IR10
Adder
4.124
232432Z2-076 GEN
Solar/Wind Harmer
0.172
232912OH NUG1
Adder
11.524
232913OH NUG2
Adder
11.37
233923SMA
Solar/Wind Harmer
6.059
233990AG1-397 GEN
Solar/Wind Harmer
0.072
233955AB2-172 GEN
Solar/Wind Harmer
6.515
232813VAUGHN
Adder
0.766
231906DC3 NUG
Adder
18.081
231902DC CT7
Adder
14.455
231907DC10
Adder
4.514
233968AD2-076_GEN
Solar/Wind Harmer
8.568
970597AG2-380 GEN
Solar/Wind Harmer
5.38
232436AB1-176 C
Solar/Wind Harmer
0.296
971983AH1-536 GEN
Solar/Wind Harmer
9.641
233935AB2-179 C
Solar/Wind Harmer
3.174
231919CHRIST1
Adder
5.579
231920CHRIST2
Adder
5.455
970453AG2-297 GEN
Solar/Wind Harmer
3.175
228260V4-054C
Solar/Wind Harmer
1.177
228309CCLP NUG
Adder
29.607
228309CCLP NUG
Adder
28.163
972141AH1-641 GEN
Solar/Wind Harmer
3.294
964001AG1-254 GEN
Solar/Wind Harmer
2.327
971011AG2-627 GEN
Solar/Wind Harmer
8.757
971535AH1-265 GEN
Solar/Wind Harmer
4.865
227927V4-067C
Solar/Wind Harmer
0.227
228754AB1-001 C
Solar/Wind Harmer
0.159
219137THOSOLAR C
Solar/Wind Harmer
1.368
219272CLEANLIGHT C
Solar/Wind Harmer
0.206
219688LUMSOLAR_S C
Solar/Wind Harmer
0.228
219914AD2-027 C
Solar/Wind Harmer
0.676
213942SCHUYLKILL
Adder
3.986
213942SCHUYLKILL
Adder
3.048
213957STHWK3-4
Adder
3.048
213957STHWK3-4
Adder
3.048
213561DLWR9-10
Adder
3.975
213561DLWR9-10
Adder
3.039
219607WPEMNERT C
Solar/Wind Harmer
0.468
219224BRL12CT4
Adder
9.966
214067T20SOLAR
Solar/Wind Harmer
0.281
213611FALLS1-3
Adder
3.929
213611FALLS1-3
Adder
3.929
20717128DIX_Z2-102
Solar/Wind Harmer
1.465
20715728PEM_W1-119
Solar/Wind Harmer
0.593
20715828PEM_W1-120
Solar/Wind Harmer
0.593
970025AG2-016 GEN
Solar/Wind Harmer
3.139
971189AH1-054 GEN
Solar/Wind Harmer
1.307
200192DELTA CT1
50/50
2.178
200194DELTA CT3
50/50
2.178
200204Y1-065-CTG1
50/50
4.512
200054ROCKSP 3
50/50
2.878
232901NORTHST
Adder
10.877
233972AC1-094 C
Solar/Wind Harmer
0.867
232900DEMECSMY
Adder
12.04
232434Z2-077 GEN
Solar/Wind Harmer
0.327
972177AH1-672 GEN
Solar/Wind Harmer
17.53
232404W1-003 C
Solar/Wind Harmer
1.307
232917OH NUG6
Adder
11.473
232915OH NUG4
Adder
11.447
233998TM1NIN_3.36
Solar/Wind Harmer
1.653
971195AH1-057 GEN
Solar/Wind Harmer
1.428
232428Y3-058 C
Solar/Wind Harmer
1.089
232919VN10
Adder
3.659
965821AG1-450 GEN
Solar/Wind Harmer
6.787
232426Y1-080 FULL
Solar/Wind Harmer
0.249
970277AG2-181 GEN
Solar/Wind Harmer
6.537
233964AF2-378 GEN
Solar/Wind Harmer
0.166
233954AC2-188 GEN
Solar/Wind Harmer
1.467
233950AC2-186 GEN
Solar/Wind Harmer
0.733
232910NRG_G1
Adder
11.214
234012AE2-112_GEN
Solar/Wind Harmer
2.972
232422X3-066 FULL
Solar/Wind Harmer
0.323
233930AB2-032 GEN
Solar/Wind Harmer
1.075
233915AB1-141 GEN
Solar/Wind Harmer
1.277
231918WEST 1
Adder
4.241
231917EM10
Adder
2.963
228206SHRMN CT
Adder
19.049
228732V1-021 C
Adder
0.217
945431AF1-208 GEN
Solar/Wind Harmer
9.894
970997AG2-616 GEN
Solar/Wind Harmer
10.979
228351V2-046C
Solar/Wind Harmer
2.305
230511AF1-262
Solar/Wind Harmer
0.209
228728W1-130C
Solar/Wind Harmer
0.759
230434AG1-499 GEN
Solar/Wind Harmer
0.662
219258KINSLEYDEP C
Solar/Wind Harmer
0.366
218660EHAMPSOLAR C
Solar/Wind Harmer
0.197
213497CHSTR7-9
Adder
3.069
213497CHSTR7-9
Adder
3.069
219904AC1-010 C
Solar/Wind Harmer
0.426
219287REEVESEAST C
Solar/Wind Harmer
1.515
219686LUMSOLAR_N C
Solar/Wind Harmer
0.228
219907AC1-030 C
Solar/Wind Harmer
0.156
213958STHWK5-6
Adder
3.048
213560DLW11-12
Adder
3.039
219304NAMERICA C
Solar/Wind Harmer
0.347
219222BRL12CT2
Adder
9.966
213611FALLS1-3
Adder
3.929
214194N WALES4
Adder
0.947
20720728JCB_W1-129
Solar/Wind Harmer
0.331
207522AF2-254 C
Solar/Wind Harmer
1.592
207487AE2-000G4
Solar/Wind Harmer
34.92
207445AB1-138_GEN
Solar/Wind Harmer
0.642
20628028LAKEHURS
Adder
2.083
963711AG1-223 GEN
Solar/Wind Harmer
1.635
20714828MDF_W3-079
Solar/Wind Harmer
0.338
219680HOPEWELLV C1
Solar/Wind Harmer
0.084
207454AA2-184 E
Solar/Wind Harmer
1.103
20715228NPK_W1-113
Solar/Wind Harmer
0.474
20742028HF_AC1-207
Solar/Wind Harmer
0.865
217197RE CRAN C
Solar/Wind Harmer
0.591
20635828PARLN1&2
Adder
8.147
20635028RRCT1&2
Adder
12.769
20635128RRCT3&4
Adder
12.326
218428ETC SOLAR C
Solar/Wind Harmer
0.039
217213AMBOY SO C
Solar/Wind Harmer
0.139
972275AH1-722 GEN
Adder
34.688
207528AF2-192 GEN
Solar/Wind Harmer
0.608
20673628F1S_V4-069
Solar/Wind Harmer
0.197
20675428EAM_W2-061
Solar/Wind Harmer
0.207
218449LINSOLAR C
Solar/Wind Harmer
1.104
20676428JCR_X2-075
Solar/Wind Harmer
0.375
217209CENTRL HS C
Solar/Wind Harmer
0.049
217121ECCF
Adder
0.476
217083KRNY_132
Adder
10.191
217208PARK ELE C
Solar/Wind Harmer
0.028
207439AE1-081 C O1
Solar/Wind Harmer
0.065
20674328GAR_V4-001
Solar/Wind Harmer
0.12
20675828AU_W4-064
Solar/Wind Harmer
0.189
971519AH1-257 GEN
Solar/Wind Harmer
2.75
207518AF1-320_GEN
Solar/Wind Harmer
3.986
207437AD2-070 GEN
Solar/Wind Harmer
0.329
20465127PORT CT
Adder
3.271
20671928W4-073
Solar/Wind Harmer
0.471
966181AG1-487 GEN
Solar/Wind Harmer
4.076
208909MACR G3
Adder
173.279
961301AF2-421 GEN
Solar/Wind Harmer
1.051
963151AG1-164 GEN
Solar/Wind Harmer
1.051
209023WIENIPP1
Adder
11.334
209025WIENIPP3
Adder
5.658
212266LOR1
Solar/Wind Harmer
0.134
970237AG2-161 GEN
Solar/Wind Harmer
3.587
209010PEIP 1
Adder
0.666
961341AF2-425 GEN
Solar/Wind Harmer
1.016
212174INGE
Adder
1.123
205941AD2-115 GEN
Solar/Wind Harmer
0.937
212507AE2-042_GEN
Solar/Wind Harmer
2.992
946731AF1-337 GEN
Solar/Wind Harmer
0.992
209071AE2-133 GEN
Solar/Wind Harmer
1.678
970665AG2-430 GEN
Solar/Wind Harmer
9.83
209018SUNBIPCT
Adder
7.379
20467927PC_Q59Y356
Adder
0.836
20465527S.RDG CT
Adder
2.721
972241AH1-705 GEN
Adder
5.64
209008PAXT IPP
Adder
1.813
970679AG2-439 GEN
Solar/Wind Harmer
1.158
200917MEHOOPANY_G
Solar/Wind Harmer
3.648
205967AE2-211_GEN
Solar/Wind Harmer
5.774
972271AH1-720 GEN
Adder
6.105
941421AE2-139 GEN
Solar/Wind Harmer
2.743
20328326MANOR_T86
Adder
0.126
316006AB2-029 C
Solar/Wind Helper
0.146
316045AC1-158 PL2
Solar/Wind Helper
5.316
316254AC1-120 GEN1
Solar/Wind Helper
1.368
3147666LOUISA
Solar/Wind Helper
1.161
316192AB2-158 GEN
Solar/Wind Helper
1.949
238148AE2-230_GEN2
Solar/Wind Helper
0.493
316337AD2-073 GEN
Solar/Wind Helper
0.43
964211AG1-282 GEN
Solar/Wind Helper
0.38
3141726DUNNSVL
Solar/Wind Helper
1.128
3142416OLDCHRC
Solar/Wind Helper
0.729
3142416OLDCHRC
Solar/Wind Helper
0.279
3138133OCRAN
Solar/Wind Helper
0.168
3141766HARMONY
Solar/Wind Helper
0.056
3143526WINTERP
Solar/Wind Helper
1.451
3142433PROV 92
Solar/Wind Helper
1.116
3143226MDLTHAN
Solar/Wind Helper
0.279
3142543TWELFTH
Solar/Wind Helper
0.027
316159AE1-175 C
Solar/Wind Helper
0.42
316458AB2-190 GEN2
Solar/Wind Helper
1.578
200035PCHBTM 3
50/50
23.2
200201DELTA2 CT2
50/50
3.899
200034PCHBTM 2
50/50
22.699
200205Y1-065-CTG2
50/50
4.512
971149AH1-027 GEN
Solar/Wind Harmer
4.423
233939AC1-091 C
Solar/Wind Harmer
1.148
233970AC1-092 C
Solar/Wind Harmer
1.148
970545AG2-347 GEN
Solar/Wind Harmer
85.4
232899W1-062
Adder
12.553
233987AB2-037 GEN
Solar/Wind Harmer
14.854
972069AH1-584 GEN
Solar/Wind Harmer
11.685
972071AH1-585 GEN
Solar/Wind Harmer
11.685
233901CHERRYDALE C
Solar/Wind Harmer
1.469
232408W1-005 C
Solar/Wind Harmer
1.307
232410W1-006 C
Solar/Wind Harmer
1.307
232918OH NUG7
Adder
11.447
971747AH1-380 GEN
Solar/Wind Harmer
4.674
232905CHERITON_25
Adder
3.201
232926CRISFLD1
Adder
2.561
231940T-011
Adder
0.973
233946AB2-136 GEN
Solar/Wind Harmer
5.201
234036AF2-325 C
Solar/Wind Harmer
1.195
234041AC1-190 GEN
Solar/Wind Harmer
11.666
233984AB2-036 GEN
Solar/Wind Harmer
16.136
232424Y1-079 C
Solar/Wind Harmer
0.729
231131BLOOM ENRGY
Adder
5.629
234014AF1-036_GEN
Solar/Wind Harmer
3.497
233944AB2-135 GEN
Solar/Wind Harmer
6.755
233933AB2-153 GEN
Solar/Wind Harmer
1.45
232416X2-083
Adder
0.576
228251CARLLS#4
Adder
0.723
230422AE1-104_GEN1
Solar/Wind Harmer
38.594
230425AE1-104_GEN2
Solar/Wind Harmer
38.594
230433AD2-135 GEN
Solar/Wind Harmer
0.116
230407AD2-065 C
Solar/Wind Harmer
0.15
228307PCLP GT
Adder
13.798
228304LOGAN
Adder
27.574
972233AH1-701 GEN
Adder
4.775
219921AF1-264
Solar/Wind Harmer
0.163
213589EDDYSTN4
Adder
89.617
213587EDDYSTN3
Adder
89.611
219615MILLCREEK C
Solar/Wind Harmer
0.267
213815MOSER1-3
Adder
3.964
213815MOSER1-3
Adder
3.964
213535CROYDN11
Adder
11.416
20716428NHV_W2-082
Solar/Wind Harmer
1.973
207500AE2-000G1
Solar/Wind Harmer
34.92
207497AE2-000G2
Solar/Wind Harmer
34.92
207507AE2-000G3
Solar/Wind Harmer
34.92
20636128O CRK C2
Adder
7.144
963401AG1-189 GEN
Solar/Wind Harmer
1.274
963391AG1-188 GEN
Solar/Wind Harmer
2.125
20714928UPF_X1-085
Solar/Wind Harmer
0.451
20628028LAKEHURS
Adder
1.053
219114HARTZY_C
Solar/Wind Harmer
0.923
219817TRENTONSOL C
Solar/Wind Harmer
1.217
20641628MLH_W1-032
Solar/Wind Harmer
0.324
20720628TIN_W1-124
Solar/Wind Harmer
1.099
20716928W4-060COL
Solar/Wind Harmer
0.783
924131AB2-057 GEN
Solar/Wind Harmer
1.132
218440SUMMTASSOC C
Solar/Wind Harmer
0.141
218418LINDEN_G5
Adder
18.869
218419LINDEN_G6
Adder
18.869
972260AH1-715 GEN1
Adder
15.109
20673828FLE_V3-070
Solar/Wind Harmer
0.503
207442AE1-156 GEN
Solar/Wind Harmer
0.817
20676128MHD_W3-029
Solar/Wind Harmer
0.524
219036LINDEN_G7
Adder
18.362
219035LINDEN_G8
Adder
18.1
972261AH1-715 GEN2
Adder
17.577
217081WEATEXAS C
Solar/Wind Harmer
0.094
217202FBANKSOLAR C
Solar/Wind Harmer
0.081
217201HACKENSOLA C
Solar/Wind Harmer
0.08
972237AH1-703 GEN
Adder
11.093
217206BARNGR HS C
Solar/Wind Harmer
0.034
217086KRNY_131
Adder
10.212
217083KRNY_132
Adder
10.126
20671828STAW2-080
Solar/Wind Harmer
0.115
217204WCALDSOLAR C
Solar/Wind Harmer
0.08
200200DELTA2 CT1
50/50
3.899
200193DELTA CT2
50/50
2.178
200203Y1-065-STG
50/50
7.823
200055ROCKSP 4
50/50
2.817
233971AC1-093 C
Solar/Wind Harmer
1.025
970695AG2-447 GEN
Solar/Wind Harmer
4.682
972133AH1-634 GEN
Solar/Wind Harmer
12.939
972073AH1-586 GEN
Solar/Wind Harmer
12.229
232406W1-004 FULL
Solar/Wind Harmer
1.307
232914OH NUG3
Adder
11.524
232916OH NUG5
Adder
11.524
232921TASLEY2G
Adder
6.735
233996TM1833_GEN
Solar/Wind Harmer
1.653
233997TMININ_4.2
Solar/Wind Harmer
1.653
233990AG1-397 GEN
Solar/Wind Harmer
1.497
233940AF2-379 C
Solar/Wind Harmer
0.243
234015AF2-250 C
Solar/Wind Harmer
0.157
233900O-025 C
Adder
1.536
233994AC2-023 GEN
Solar/Wind Harmer
3.506
232907VN8
Adder
39.168
960671AF2-358 GEN
Solar/Wind Harmer
23.348
233952AC2-187 GEN
Solar/Wind Harmer
1.467
232417X3-008 C
Solar/Wind Harmer
2.606
972251AH1-710 GEN
Adder
57.775
233918AB1-142 GEN
Solar/Wind Harmer
1.277
233982AB2-133 GEN
Solar/Wind Harmer
6.273
228202CUMB CT
Adder
18.994
228711V2-041C
Solar/Wind Harmer
0.691
971553AH1-274 GEN
Solar/Wind Harmer
2.781
230430AE1-229_GEN
Solar/Wind Harmer
10.075
230415AB2-049 C
Solar/Wind Harmer
0.217
228729W2-030 C
Solar/Wind Harmer
0.66
228304LOGAN
Adder
24.8
219623KINSLEYBEA C
Solar/Wind Harmer
0.483
219291REEVESSOUT C
Solar/Wind Harmer
0.068
213497CHSTR7-9
Adder
3.069
219766PARADISE C
Solar/Wind Harmer
0.355
219912AD2-042 GEN
Solar/Wind Harmer
0.896
219236SOUTHERNHQ C
Solar/Wind Harmer
0.076
213958STHWK5-6
Adder
3.048
213560DLW11-12
Adder
3.039
219906AC1-017 C
Solar/Wind Harmer
0.25
213815MOSER1-3
Adder
3.964
219610FLORENCE C
Solar/Wind Harmer
1.547
219348LDSOLAR C
Solar/Wind Harmer
0.669
219221BRL12CT1
Adder
9.966
219223BRL12CT3
Adder
9.966
20716028EGP_W2-019
Solar/Wind Harmer
0.515
20720828JCB_W4-025
Solar/Wind Harmer
0.503
20715028HAN_X4-015
Solar/Wind Harmer
0.331
959561AF2-247 GEN
Solar/Wind Harmer
0.539
20636028O CRK C1
Adder
7.835
971667AH1-334 GEN
Solar/Wind Harmer
3.042
219727YARDVSOLFA C
Solar/Wind Harmer
1.007
20714528FRN_Y2-051
Solar/Wind Harmer
0.326
219276PARKLANDSO C
Solar/Wind Harmer
0.51
219918AC2-009 C
Solar/Wind Harmer
0.068
20716228APLW2-078
Solar/Wind Harmer
0.975
20720528MAN_W1-024
Solar/Wind Harmer
0.28
967451AG2-055 C O1
Solar/Wind Harmer
191.48
219612MATRIX C
Solar/Wind Harmer
0.203
218438BLK ROCK C
Solar/Wind Harmer
0.15
20635828PARLN1&2
Adder
3.69
20635928PARLN3&4
Adder
3.69
20635028RRCT1&2
Adder
12.969
20635128RRCT3&4
Adder
10.752
219908AB1-139 C
Solar/Wind Harmer
0.419
219919AE1-041 FULL
Solar/Wind Harmer
0.044
219249CENTRALDIV C
Solar/Wind Harmer
0.044
20673728F2S_V4-070
Solar/Wind Harmer
0.197
217211CAMDEN ST C
Solar/Wind Harmer
0.027
217186ESSEX_G9
Adder
17.527
217169METRODIV C
Solar/Wind Harmer
0.044
217194REDH C
Solar/Wind Harmer
0.54
20676728BRNX1-095
Solar/Wind Harmer
0.193
207510AF2-138 C
Solar/Wind Harmer
1.944
20674628WNG_W3-110
Solar/Wind Harmer
0.441
971007AG2-625 GEN
Solar/Wind Harmer
2.803
20466127PORT 5CT
Adder
28.867
20633028GILCT9
Adder
30.801
966181AG1-487 GEN
Solar/Wind Harmer
0.273
20465427SHAW CT
Adder
4.194
963161AG1-165 GEN
Solar/Wind Harmer
1.051
209025WIENIPP3
Adder
5.543
963071AG1-156 GEN
Solar/Wind Harmer
2.881
970095AG2-074 GEN
Solar/Wind Harmer
6.538
209027LOR2_Q27
Solar/Wind Harmer
4.671
209022WHFR IPP
Adder
3.354
961331AF2-424 GEN
Solar/Wind Harmer
1.016
961421AF2-433 GEN
Solar/Wind Harmer
1.013
957921AF2-086 GEN
Solar/Wind Harmer
0.985
209142AF1-226 GEN
Solar/Wind Harmer
5.866
209093AE2-110 GEN
Solar/Wind Harmer
2.533
209120AE2-241 GEN
Solar/Wind Harmer
3.352
972245AH1-707 GEN
Adder
5.462
946691AF1-333 GEN
Solar/Wind Harmer
0.992
946741AF1-338 GEN
Solar/Wind Harmer
0.992
972221AH1-695 GEN
Adder
123.484
209067AE2-060 GEN
Solar/Wind Harmer
1.327
3141196NOKESVL
Solar/Wind Helper
1.258
316044AC1-158 PL1
Solar/Wind Helper
1.661
316450AC1-158 RIC
Solar/Wind Helper
0.443
316170AC1-121 GEN2
Solar/Wind Helper
0.456
3132273ORANGE
Solar/Wind Helper
0.058
3147666LOUISA
Solar/Wind Helper
0.668
966881AG1-559 GEN
Solar/Wind Helper
0.389
238147AE2-230_GEN1
Solar/Wind Helper
0.491
238149AF1-291A_GEN
Solar/Wind Helper
0.14
3141906WESTMOR
Solar/Wind Helper
0.114
316473AC1-191 GEN
Solar/Wind Helper
1.722
237061AD1-155 GEN
Solar/Wind Helper
0.053
316404AE1-155 C
Solar/Wind Helper
2.376
316484AD2-074 GEN
Solar/Wind Helper
0.542
316280AD1-041 GEN
Solar/Wind Helper
0.938
316156AD2-030 GEN
Solar/Wind Helper
0.421
3142946ENON
Solar/Wind Helper
0.093
316382AG1-145 C
Solar/Wind Helper
0.372
315839AE2-212 C
Solar/Wind Helper
0.37
3145336SMITFLD
Solar/Wind Helper
0.11
315773AC2-141 GEN
Solar/Wind Helper
5.898
316313AB2-026
Solar/Wind Helper
0.417
316258AE1-075 C
Solar/Wind Helper
0.375
316405AF2-144 C
Solar/Wind Helper
0.313
3144536CHRHLND
Solar/Wind Helper
0.041
3144873MCLAUGH
Solar/Wind Helper
0.007
3146456SLIGO L269
Solar/Wind Helper
0.272
316320Y1-086
Solar/Wind Helper
0.121
316435W1029_GEN3
Solar/Wind Helper
1.092
3146516WINFALL
Solar/Wind Helper
0.27
3146626S HERTFORD
Solar/Wind Helper
0.27
3145273HOLLAND
Solar/Wind Helper
0.202
3146376EDENTON
Solar/Wind Helper
0.268
315614AA2-178 GEN
Solar/Wind Helper
1.621
3146776BUCKING
Solar/Wind Helper
0.095
315737AD1-076 GEN
Solar/Wind Helper
2.584
3146926FARMVIL
Solar/Wind Helper
0.158
316365GEN2_N
Solar/Wind Helper
1.004
3146206CASHIE
Solar/Wind Helper
0.264
3145893MURPHYS
Solar/Wind Helper
0.094
3145893MURPHYS
Solar/Wind Helper
0.264
3146173TUNIS
Solar/Wind Helper
0.263
316095T157 G97
Solar/Wind Helper
1.209
3156021HOLLOMANSOL
Solar/Wind Helper
1.997
316463AE2-346 GEN
Solar/Wind Helper
0.24
316140AB2-099
Solar/Wind Helper
0.1
207459AE1-142 C O1
Solar/Wind Harmer
1.169
219620RIDERU C
Solar/Wind Harmer
0.062
20714328BYD_X4-031
Solar/Wind Harmer
0.312
20714428HOW_X1-037
Solar/Wind Harmer
1.363
971521AH1-258 GEN
Solar/Wind Harmer
2.984
20720428HOL_W1-112
Solar/Wind Harmer
0.381
20635928PARLN3&4
Adder
8.147
218455CINNBAY_CGEN
Adder
2
218526CNTRALGAS2 C
Solar/Wind Harmer
0.408
218524CNTRALGAS1 C
Solar/Wind Harmer
0.407
20675528CPH_W2-050
Solar/Wind Harmer
0.514
218404KENILWRTH C
Adder
1.432
217167KRNY_14
Adder
10.191
217086KRNY_131
Adder
10.104
217147KRNY_1212
Adder
9.693
217147KRNY_1212
Adder
9.52
217146KRNY_1234
Adder
9.498
217146KRNY_1234
Adder
9.433
966261AG1-495 GEN
Solar/Wind Harmer
1.963
20676328BVR_Y1-020
Solar/Wind Harmer
0.362
207511W3-106 GEN
Solar/Wind Harmer
0.717
207530AG1-191 GEN
Solar/Wind Harmer
1.503
20674828DL_W4-046
Solar/Wind Harmer
0.705
971009AG2-626 GEN
Solar/Wind Harmer
1.787
207408W3-077 C
Solar/Wind Harmer
0.552
20675728RH_W2-091
Solar/Wind Harmer
0.373
20675928HOL_W4-097
Solar/Wind Harmer
0.142
207484AF2-139 C O1
Solar/Wind Harmer
0.551
20675128HRM_W1-127
Solar/Wind Harmer
0.186
966421AG1-511 GEN
Solar/Wind Harmer
9.372
20462827N BANGR8
Adder
0.78
209116AE2-175 GEN
Solar/Wind Harmer
4.454
961261AF2-417 GEN
Solar/Wind Harmer
1.054
209026WIENIPP4
Adder
5.601
209045AE2-271 GEN
Solar/Wind Harmer
16.942
959431AF2-234 GEN
Solar/Wind Harmer
1.981
964051AG1-259 GEN
Solar/Wind Harmer
1.329
964061AG1-260 GEN
Solar/Wind Harmer
1.329
959421AF2-233 GEN
Solar/Wind Harmer
0.991
20486527WR_V4-052
Adder
1.062
208862AG1-362 C
Solar/Wind Harmer
0.769
20390726Y2-042
Adder
2.77
20334726NME_Y1-047
Adder
2.451
203926AA2-133 GEN
Adder
2.264
205951AE1-129_GEN
Solar/Wind Harmer
7.582
3138216PACIFIC
Solar/Wind Helper
0.054
316411AF1-147_GEN1
Solar/Wind Helper
1.09
316415AF1-147_GEN2
Solar/Wind Helper
1.09
3141426STAFORD
Solar/Wind Helper
0.066
316164AC1-076 GEN
Solar/Wind Helper
1.419
238152AF2-075_GEN
Solar/Wind Helper
0.701
316223AC1-118
Solar/Wind Helper
0.434
23546401DTGZ2-030
Solar/Wind Helper
0.089
3141813NORNECK
Solar/Wind Helper
0.282
316312AB1-027
Solar/Wind Helper
0.534
3141783LANCAST
Solar/Wind Helper
0.168
3141783LANCAST
Solar/Wind Helper
0.112
3138133OCRAN
Solar/Wind Helper
0.084
3141913WHIT STONE
Solar/Wind Helper
0.28
316059AD1-063 C
Solar/Wind Helper
0.281
3143873LANEXA
Solar/Wind Helper
0.167
315662AE1-191 GEN
Solar/Wind Helper
1.5
315666AE1-190 GEN
Solar/Wind Helper
0.375
957601AF2-054 GEN
Solar/Wind Helper
0.374
3141873WAN 176
Solar/Wind Helper
0.056
316233AE1-074 FULL
Solar/Wind Helper
0.426
957831AF2-077 GEN
Solar/Wind Helper
0.374
316132AB2-190 GEN1
Solar/Wind Helper
1.578
316369SG1_INVT
Solar/Wind Helper
1.326
3143316POE
Solar/Wind Helper
1.085
316349AD2-085 GEN
Solar/Wind Helper
1.246
319010AE1-072 C
Solar/Wind Helper
3.109
316305AF2-043 C
Solar/Wind Helper
0.366
313526AB2-022
Solar/Wind Helper
0.413
3146486SUNBURY
Solar/Wind Helper
0.271
3146486SUNBURY
Solar/Wind Helper
0.271
316321Z2-027
Solar/Wind Helper
0.413
3145176PASQUOTANK
Solar/Wind Helper
0.168
316315AB2-025 C
Solar/Wind Helper
0.411
315611Z1-036_GEN2
Solar/Wind Helper
1.479
3130156CHOWAN
Solar/Wind Helper
0.268
3130156CHOWAN
Solar/Wind Helper
0.268
315816AE2-034 GEN
Solar/Wind Helper
1.216
3138266HYDRAULIC
Solar/Wind Helper
0.012
3138266HYDRAULIC
Solar/Wind Helper
0.008
3130546PLYMOUTH
Solar/Wind Helper
0.265
20674528F3S_W2-016
Solar/Wind Harmer
1.541
20676228FRD_X1-012
Solar/Wind Harmer
0.646
207471AF2-354 C
Solar/Wind Harmer
0.558
20674928WA_W3-044
Solar/Wind Harmer
0.526
964851AG1-348 GEN
Solar/Wind Harmer
1.917
20634528N27_Y2-018
Solar/Wind Harmer
0.293
20465127PORT CT
Adder
4.34
20674128FR_U2-059
Solar/Wind Harmer
0.201
966111AG1-480 GEN
Solar/Wind Harmer
0.094
966111AG1-480 GEN
Solar/Wind Harmer
3.579
211065PSPA IPP
Solar/Wind Harmer
0.487
211065PSPA IPP
Solar/Wind Harmer
0.487
208972BECR K09
Solar/Wind Harmer
1.098
961541AF2-445A GEN
Solar/Wind Harmer
3.355
209029WAYMART-WD
Solar/Wind Harmer
2.976
209009PEIP 2
Adder
8.081
209010PEIP 1
Adder
3.661
209010PEIP 1
Adder
0.536
961431AF2-434 GEN
Solar/Wind Harmer
1.013
209054AE2-059 GEN
Solar/Wind Harmer
1.689
209059AE2-084 GEN
Solar/Wind Harmer
2.494
946751AF1-339 GEN
Solar/Wind Harmer
0.992
209130AF1-271A GEN
Solar/Wind Harmer
2.785
20465527S.RDG CT
Adder
2.633
20478527GLRA_Q45
Adder
0.304
209137AF2-361 C
Solar/Wind Harmer
2.566
238175AF1-290_GEN
Solar/Wind Helper
0.158
315651AD1-115 GEN
Solar/Wind Helper
1.005
316447AC1-158 HLD
Solar/Wind Helper
3.655
238169AE2-226 GEN1
Solar/Wind Helper
0.722
238170AE2-226 GEN2
Solar/Wind Helper
0.722
966001AG1-469 GEN
Solar/Wind Helper
0.309
3145336SMITFLD
Solar/Wind Helper
1.097
316294AC1-161 GEN
Solar/Wind Helper
5.011
316381AD1-082 GEN
Solar/Wind Helper
1.417
316375AC2-012 GEN
Solar/Wind Helper
0.716
316072AD1-144
Solar/Wind Helper
0.312
316336AC2-165 C
Solar/Wind Helper
1.47
316388AE2-253 GEN
Solar/Wind Helper
1.037
3146456SLIGO L269
Solar/Wind Helper
0.272
316246AF1-032 C
Solar/Wind Helper
0.311
3146516WINFALL
Solar/Wind Helper
0.875
3146516WINFALL
Solar/Wind Helper
0.27
315800Z1-036_GEN1
Solar/Wind Helper
1.479
3130156CHOWAN
Solar/Wind Helper
0.268
3145663CRESWEL
Solar/Wind Helper
0.745
316322AB2-045
Solar/Wind Helper
0.295
3146776BUCKING
Solar/Wind Helper
0.106
3146926FARMVIL
Solar/Wind Helper
0.158
316023GEN1_S
Solar/Wind Helper
1.004
3146206CASHIE
Solar/Wind Helper
0.264
3145893MURPHYS
Solar/Wind Helper
1.054
3146173TUNIS
Solar/Wind Helper
0.263
3147983MERCK5
Solar/Wind Helper
0.105
316097T157 G90
Solar/Wind Helper
1.209
3145683EARLEYS
Solar/Wind Helper
0.262
3146263WOODLND
Solar/Wind Helper
0.261
316190AA2-174 GEN
Solar/Wind Helper
0.017
3145963POPLR C
Solar/Wind Helper
0.261
316011AB1-132 GEN
Solar/Wind Helper
2.803
3145823KELFORD
Solar/Wind Helper
0.26
316174AB2-169 GEN
Solar/Wind Helper
0.662
3145783HORNRTN
Solar/Wind Helper
0.26
3145796HORNRTN
Solar/Wind Helper
0.856
3145796HORNRTN
Solar/Wind Helper
0.259
316129AC1-054 GEN
Solar/Wind Helper
1.276
316212AC1-099_GEN
Solar/Wind Helper
1.155
316237AB2-079_GEN
Solar/Wind Helper
0.345
3145746EVERETS
Solar/Wind Helper
0.256
3145746EVERETS
Solar/Wind Helper
0.256
315687AD1-152 GEN
Solar/Wind Helper
1.374
315722AD1-056 GEN
Solar/Wind Helper
1.374
316494AC1-189 GEN
Solar/Wind Helper
1.555
3146233WITAKRS
Solar/Wind Helper
1.01
961671AG1-007 GEN
Solar/Wind Helper
0.182
3146083TARBORO
Solar/Wind Helper
0.254
3145543BTLEBRO
Solar/Wind Helper
0.252
3145543BTLEBRO
Solar/Wind Helper
0.202
316359AB2-059 GEN
Solar/Wind Helper
1.922
316049AB1-081 GEN
Solar/Wind Helper
1.537
316003AC1-222 GEN
Solar/Wind Helper
1.076
237080AD1-060 GEN
Solar/Wind Helper
0.298
964991AG1-363 GEN
Solar/Wind Helper
3.503
237038AE2-054 C
Solar/Wind Helper
0.229
3147123OTTER R
Solar/Wind Helper
0.138
3147312GRETNA
Solar/Wind Helper
0.183
3146802CHATHAM
Solar/Wind Helper
0.172
270016AE1-250 BESS
Solar/Wind Helper
0.845
315732AD1-074 GEN1
Solar/Wind Helper
3.021
315733AD1-074 GEN2
Solar/Wind Helper
3.021
315735AD1-075 GEN1
Solar/Wind Helper
1.51
3146206CASHIE
Solar/Wind Helper
0.264
3145893MURPHYS
Solar/Wind Helper
0.711
3145893MURPHYS
Solar/Wind Helper
0.264
3145513AHOSKIE
Solar/Wind Helper
0.118
961941AG1-037 GEN
Solar/Wind Helper
0.088
3145513AHOSKIE
Solar/Wind Helper
0.262
946281AF1-292 GEN
Solar/Wind Helper
0.263
3146043SEABORD
Solar/Wind Helper
0.262
3145683EARLEYS
Solar/Wind Helper
0.524
3145683EARLEYS
Solar/Wind Helper
0.262
3145683EARLEYS
Solar/Wind Helper
0.262
315607AA1-063A GEN
Solar/Wind Helper
1.494
316087AB2-174 GEN
Solar/Wind Helper
1.83
3137643SOCKMAN
Solar/Wind Helper
1.042
3148133STUARTS
Solar/Wind Helper
0.156
3148013FISHERV
Solar/Wind Helper
0.149
3145796HORNRTN
Solar/Wind Helper
0.83
3145796HORNRTN
Solar/Wind Helper
0.104
3144303KENBRDG
Solar/Wind Helper
0.207
3146033SCOT NK
Solar/Wind Helper
1.036
316239AB2-077_GEN
Solar/Wind Helper
0.345
316238AB2-078_GEN
Solar/Wind Helper
0.345
316005AA1-067
Solar/Wind Helper
0.292
3145746EVERETS
Solar/Wind Helper
1.018
3145746EVERETS
Solar/Wind Helper
0.256
3145746EVERETS
Solar/Wind Helper
0.256
3145746EVERETS
Solar/Wind Helper
0.256
270494AE1-108_GEN
Solar/Wind Helper
3.41
316420AA1-050 GEN
Solar/Wind Helper
1.456
3145573BETHELC
Solar/Wind Helper
0.254
3145573BETHELC
Solar/Wind Helper
0.254
238208AF1-136 C
Solar/Wind Helper
0.196
238109AE1-109 GEN2
Solar/Wind Helper
0.094
238110AE1-109 GEN3
Solar/Wind Helper
0.094
316118AC1-105 GEN
Solar/Wind Helper
0.977
3148463FAIRFLD
Solar/Wind Helper
0.251
3147173SINAI
Solar/Wind Helper
0.25
3147243WELCO
Solar/Wind Helper
0.156
316123AC1-075 GEN
Solar/Wind Helper
1.467
270455AD2-022 GEN
Solar/Wind Helper
1.374
270457AD2-023 GEN
Solar/Wind Helper
0.905
316468AD1-105 GEN
Solar/Wind Helper
1.419
316077AC2-138 C
Solar/Wind Helper
0.265
966871AG1-558 GEN
Solar/Wind Helper
0.38
316487AF1-042 GEN
Solar/Wind Helper
0.284
316075AC2-137 C
Solar/Wind Helper
0.426
3143526WINTERP
Solar/Wind Helper
1.451
3142946ENON
Solar/Wind Helper
0.028
316240AF1-291 C
Solar/Wind Helper
0.372
316033AB2-134 GEN
Solar/Wind Helper
0.948
315697AD1-025 GEN
Solar/Wind Helper
3.151
316236AE1-162_GEN
Solar/Wind Helper
0.369
316036AC1-147 C
Solar/Wind Helper
0.416
316316AC1-027 C
Solar/Wind Helper
0.431
3142956BIRDNECK
Solar/Wind Helper
0.184
316185AD1-033 GEN
Solar/Wind Helper
1.283
3145506HICKORY
Solar/Wind Helper
1.091
3145506HICKORY
Solar/Wind Helper
0.654
3145506HICKORY
Solar/Wind Helper
0.164
316339AD2-160 GEN
Solar/Wind Helper
1.037
235020AA1-095 C
Solar/Wind Helper
0.051
316018AA1-139 ULT2
Solar/Wind Helper
1.171
316017AA1-139 ULT1
Solar/Wind Helper
1.244
3137176SLIGO L2192
Solar/Wind Helper
1.083
23777901MDS_W4-102
Solar/Wind Helper
0.17
3130086AYDLETT
Solar/Wind Helper
1.088
3146386ELIZ CT
Solar/Wind Helper
0.271
316431W1029_GEN1
Solar/Wind Helper
1.092
316433W1029_GEN2
Solar/Wind Helper
1.092
3146516WINFALL
Solar/Wind Helper
0.27
3146516WINFALL
Solar/Wind Helper
0.27
3146516WINFALL
Solar/Wind Helper
0.27
3146626S HERTFORD
Solar/Wind Helper
0.27
3146626S HERTFORD
Solar/Wind Helper
0.27
3144356SAPONY
Solar/Wind Helper
0.483
315742AE1-103 GEN
Solar/Wind Helper
0.433
3132123MT JACKSON
Solar/Wind Helper
0.835
3146776BUCKING
Solar/Wind Helper
1.06
3146776BUCKING
Solar/Wind Helper
0.086
3145893MURPHYS
Solar/Wind Helper
0.378
3145893MURPHYS
Solar/Wind Helper
0.474
3146173TUNIS
Solar/Wind Helper
0.263
3146173TUNIS
Solar/Wind Helper
0.263
315821AE2-092 GEN
Solar/Wind Helper
2.433
316181AB2-040 GEN
Solar/Wind Helper
1.875
3147133PAMPLIN
Solar/Wind Helper
0.261
3147133PAMPLIN
Solar/Wind Helper
0.209
3142666NORTHAMPTON
Solar/Wind Helper
0.261
3142666NORTHAMPTON
Solar/Wind Helper
0.261
3142666NORTHAMPTON
Solar/Wind Helper
0.261
3142666NORTHAMPTON
Solar/Wind Helper
0.156
316426AA2-053 GEN
Solar/Wind Helper
1.486
3145593CAROLNA
Solar/Wind Helper
0.26
3145593CAROLNA
Solar/Wind Helper
0.26
3145796HORNRTN
Solar/Wind Helper
0.778
316034AC1-036 C
Solar/Wind Helper
0.271
3145933PARMELE
Solar/Wind Helper
0.514
3145933PARMELE
Solar/Wind Helper
0.257
316274AC1-208 GEN
Solar/Wind Helper
1.567
226929AD2-058 GEN
Solar/Wind Helper
0.099
3146843MT LREL
Solar/Wind Helper
0.253
3146843MT LREL
Solar/Wind Helper
0.253
237034AC2-136 C
Solar/Wind Helper
0.207
316222AC1-221 GEN
Solar/Wind Helper
1.387
316197AC1-042 GEN
Solar/Wind Helper
0.215
270013AE1-250 PV
Solar/Wind Helper
0.845
237002AB1-128_GEN
Solar/Wind Helper
0.363
270173AC1-122 GEN
Solar/Wind Helper
1.452
942461AE2-259 GEN
Solar/Wind Helper
1.768
966621AG1-532 GEN
Solar/Wind Helper
0.239
316499AE2-029_GEN
Solar/Wind Helper
0.881
3146263WOODLND
Solar/Wind Helper
0.261
313506AB2-031 GEN
Solar/Wind Helper
1.186
3147133PAMPLIN
Solar/Wind Helper
0.819
3142666NORTHAMPTON
Solar/Wind Helper
0.261
3147043LAWRENC
Solar/Wind Helper
0.156
3145963POPLR C
Solar/Wind Helper
0.261
316317KELFORD C
Solar/Wind Helper
0.222
3145823KELFORD
Solar/Wind Helper
0.26
316478AD1-087 GEN
Solar/Wind Helper
1.27
316486AD2-202 GEN
Solar/Wind Helper
0.372
3148013FISHERV
Solar/Wind Helper
0.26
3145796HORNRTN
Solar/Wind Helper
1.037
3145796HORNRTN
Solar/Wind Helper
0.259
315785AD2-033 C
Solar/Wind Helper
3.016
316210AC1-098 GEN
Solar/Wind Helper
2.079
316131AB2-060 GEN
Solar/Wind Helper
1.568
3145933PARMELE
Solar/Wind Helper
0.257
23583801GRNGAP
Solar/Wind Helper
4.398
3145746EVERETS
Solar/Wind Helper
0.256
3145746EVERETS
Solar/Wind Helper
0.256
315724AD1-057 GEN
Solar/Wind Helper
0.756
316327AA2-057 GEN
Solar/Wind Helper
1.454
3146233WITAKRS
Solar/Wind Helper
0.273
3146233WITAKRS
Solar/Wind Helper
0.172
3146073TAR RVR
Solar/Wind Helper
0.254
3146083TARBORO
Solar/Wind Helper
0.254
3138543CONSLDL
Solar/Wind Helper
0.167
3145543BTLEBRO
Solar/Wind Helper
0.252
3145543BTLEBRO
Solar/Wind Helper
0.252
238108AE1-109 GEN1
Solar/Wind Helper
0.094
238221AF1-254 C O1
Solar/Wind Helper
0.248
315616AA1-038_C
Solar/Wind Helper
1.138
316248AF1-058 C
Solar/Wind Helper
0.336
227287AC2-120 GEN
Solar/Wind Helper
0.335
226910AB2-157 C
Solar/Wind Helper
0.014
316283AC2-100 C
Solar/Wind Helper
1.295
235067AD1-061 GEN
Solar/Wind Helper
0.416
3147312GRETNA
Solar/Wind Helper
0.046
270197AD1-017 GEN1
Solar/Wind Helper
1.223
270018AE2-047 C O1
Solar/Wind Helper
0.79
237085AD2-009_GEN
Solar/Wind Helper
1.357
HAMLETPJM->LTFIMP_HAMLET
CLTF
5.987
G-007ALTFEXP_G-007A->PJM
CMTX
56.398
CBM NorthLTFEXP_CBM-N->PJM
CBM
83.022
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
4.56
BlueGrassPJM->LTFIMP_BlueG
CLTF
14.213
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
148.565
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.493
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
21.603

Details for CHAN-01DOUBS 500.0 kV Ckt 1 line l/o PECO_P4_PEACH235_SRT-A/* $ CHESCO $ PECO_P4_PEACH235 $ STBK


Base Case Flowgate

Area:AP/PJM
Facility Description:
CHAN-01DOUBS 500.0 kV Ckt 1 line
Contingency Name:
PECO_P4_PEACH235_SRT-A/* $ CHESCO $ PECO_P4_PEACH235 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:118.27 %
Rating:4150.0 MVA
Rating Type:B
MVA to Mitigate:4908.0
MW Contribution:8.76
Bus #Bus NameTypeMW Contribution
200035PCHBTM 3
50/50
23.203
200201DELTA2 CT2
50/50
3.899
200034PCHBTM 2
50/50
22.686
200205Y1-065-CTG2
50/50
4.509
971149AH1-027 GEN
Solar/Wind Harmer
4.422
233939AC1-091 C
Solar/Wind Harmer
1.147
233970AC1-092 C
Solar/Wind Harmer
1.147
970545AG2-347 GEN
Solar/Wind Harmer
85.37
232899W1-062
Adder
12.548
233987AB2-037 GEN
Solar/Wind Harmer
14.849
972069AH1-584 GEN
Solar/Wind Harmer
11.681
972071AH1-585 GEN
Solar/Wind Harmer
11.681
233901CHERRYDALE C
Solar/Wind Harmer
1.468
232408W1-005 C
Solar/Wind Harmer
1.306
232410W1-006 C
Solar/Wind Harmer
1.306
232918OH NUG7
Adder
11.443
971747AH1-380 GEN
Solar/Wind Harmer
4.672
232905CHERITON_25
Adder
3.2
232926CRISFLD1
Adder
2.56
231940T-011
Adder
0.973
233946AB2-136 GEN
Solar/Wind Harmer
5.2
234036AF2-325 C
Solar/Wind Harmer
1.194
234041AC1-190 GEN
Solar/Wind Harmer
11.662
233984AB2-036 GEN
Solar/Wind Harmer
16.131
232424Y1-079 C
Solar/Wind Harmer
0.729
231131BLOOM ENRGY
Adder
5.628
234014AF1-036_GEN
Solar/Wind Harmer
3.496
233944AB2-135 GEN
Solar/Wind Harmer
6.753
233933AB2-153 GEN
Solar/Wind Harmer
1.449
232416X2-083
Adder
0.576
228251CARLLS#4
Adder
0.723
230422AE1-104_GEN1
Solar/Wind Harmer
38.585
200192DELTA CT1
50/50
2.179
200194DELTA CT3
50/50
2.179
200204Y1-065-CTG1
50/50
4.509
200054ROCKSP 3
50/50
2.876
232901NORTHST
Adder
10.873
233972AC1-094 C
Solar/Wind Harmer
0.867
232900DEMECSMY
Adder
12.036
232434Z2-077 GEN
Solar/Wind Harmer
0.327
972177AH1-672 GEN
Solar/Wind Harmer
17.524
232404W1-003 C
Solar/Wind Harmer
1.306
232917OH NUG6
Adder
11.469
232915OH NUG4
Adder
11.443
233998TM1NIN_3.36
Solar/Wind Harmer
1.652
971195AH1-057 GEN
Solar/Wind Harmer
1.428
232428Y3-058 C
Solar/Wind Harmer
1.088
232919VN10
Adder
3.658
965821AG1-450 GEN
Solar/Wind Harmer
6.785
232426Y1-080 FULL
Solar/Wind Harmer
0.249
970277AG2-181 GEN
Solar/Wind Harmer
6.535
233964AF2-378 GEN
Solar/Wind Harmer
0.166
233954AC2-188 GEN
Solar/Wind Harmer
1.466
233950AC2-186 GEN
Solar/Wind Harmer
0.733
232910NRG_G1
Adder
11.21
234012AE2-112_GEN
Solar/Wind Harmer
2.971
232422X3-066 FULL
Solar/Wind Harmer
0.323
233930AB2-032 GEN
Solar/Wind Harmer
1.074
233915AB1-141 GEN
Solar/Wind Harmer
1.276
231918WEST 1
Adder
4.239
231917EM10
Adder
2.962
228206SHRMN CT
Adder
19.045
228732V1-021 C
Adder
0.217
945431AF1-208 GEN
Solar/Wind Harmer
9.891
970997AG2-616 GEN
Solar/Wind Harmer
10.977
228351V2-046C
Solar/Wind Harmer
2.305
230511AF1-262
Solar/Wind Harmer
0.209
228728W1-130C
Solar/Wind Harmer
0.759
230434AG1-499 GEN
Solar/Wind Harmer
0.662
219258KINSLEYDEP C
Solar/Wind Harmer
0.365
218660EHAMPSOLAR C
Solar/Wind Harmer
0.197
213497CHSTR7-9
Adder
3.069
213497CHSTR7-9
Adder
3.069
219904AC1-010 C
Solar/Wind Harmer
0.426
219686LUMSOLAR_N C
Solar/Wind Harmer
0.228
219287REEVESEAST C
Solar/Wind Harmer
1.515
219907AC1-030 C
Solar/Wind Harmer
0.156
213958STHWK5-6
Adder
3.047
213560DLW11-12
Adder
3.039
219304NAMERICA C
Solar/Wind Harmer
0.347
219222BRL12CT2
Adder
9.964
213611FALLS1-3
Adder
3.929
214194N WALES4
Adder
0.947
20720728JCB_W1-129
Solar/Wind Harmer
0.331
207522AF2-254 C
Solar/Wind Harmer
1.592
207487AE2-000G4
Solar/Wind Harmer
34.915
207445AB1-138_GEN
Solar/Wind Harmer
0.642
20628028LAKEHURS
Adder
2.082
963711AG1-223 GEN
Solar/Wind Harmer
1.635
20714828MDF_W3-079
Solar/Wind Harmer
0.338
219680HOPEWELLV C1
Solar/Wind Harmer
0.084
207454AA2-184 E
Solar/Wind Harmer
1.103
20715228NPK_W1-113
Solar/Wind Harmer
0.474
20742028HF_AC1-207
Solar/Wind Harmer
0.865
217197RE CRAN C
Solar/Wind Harmer
0.591
20635828PARLN1&2
Adder
8.146
20635028RRCT1&2
Adder
12.768
20635128RRCT3&4
Adder
12.324
218428ETC SOLAR C
Solar/Wind Harmer
0.039
217213AMBOY SO C
Solar/Wind Harmer
0.139
972275AH1-722 GEN
Adder
34.684
207528AF2-192 GEN
Solar/Wind Harmer
0.608
20673628F1S_V4-069
Solar/Wind Harmer
0.197
20675428EAM_W2-061
Solar/Wind Harmer
0.207
218449LINSOLAR C
Solar/Wind Harmer
1.104
20676428JCR_X2-075
Solar/Wind Harmer
0.375
217209CENTRL HS C
Solar/Wind Harmer
0.049
200200DELTA2 CT1
50/50
3.899
200193DELTA CT2
50/50
2.179
200203Y1-065-STG
50/50
7.819
200055ROCKSP 4
50/50
2.816
233971AC1-093 C
Solar/Wind Harmer
1.025
970695AG2-447 GEN
Solar/Wind Harmer
4.68
972133AH1-634 GEN
Solar/Wind Harmer
12.935
972073AH1-586 GEN
Solar/Wind Harmer
12.224
232406W1-004 FULL
Solar/Wind Harmer
1.306
232914OH NUG3
Adder
11.52
232916OH NUG5
Adder
11.52
232921TASLEY2G
Adder
6.733
233996TM1833_GEN
Solar/Wind Harmer
1.652
233997TMININ_4.2
Solar/Wind Harmer
1.652
233990AG1-397 GEN
Solar/Wind Harmer
1.496
233940AF2-379 C
Solar/Wind Harmer
0.243
233900O-025 C
Adder
1.536
234015AF2-250 C
Solar/Wind Harmer
0.157
233994AC2-023 GEN
Solar/Wind Harmer
3.505
232907VN8
Adder
39.154
960671AF2-358 GEN
Solar/Wind Harmer
23.34
233952AC2-187 GEN
Solar/Wind Harmer
1.466
232417X3-008 C
Solar/Wind Harmer
2.605
972251AH1-710 GEN
Adder
57.757
233918AB1-142 GEN
Solar/Wind Harmer
1.276
233982AB2-133 GEN
Solar/Wind Harmer
6.271
228202CUMB CT
Adder
18.989
228711V2-041C
Solar/Wind Harmer
0.69
971553AH1-274 GEN
Solar/Wind Harmer
2.78
230430AE1-229_GEN
Solar/Wind Harmer
10.073
230415AB2-049 C
Solar/Wind Harmer
0.217
228729W2-030 C
Solar/Wind Harmer
0.66
228304LOGAN
Adder
24.795
219623KINSLEYBEA C
Solar/Wind Harmer
0.483
219291REEVESSOUT C
Solar/Wind Harmer
0.068
213497CHSTR7-9
Adder
3.069
219766PARADISE C
Solar/Wind Harmer
0.355
219912AD2-042 GEN
Solar/Wind Harmer
0.896
219236SOUTHERNHQ C
Solar/Wind Harmer
0.076
213958STHWK5-6
Adder
3.047
213560DLW11-12
Adder
3.039
219906AC1-017 C
Solar/Wind Harmer
0.25
213815MOSER1-3
Adder
3.964
219610FLORENCE C
Solar/Wind Harmer
1.547
219348LDSOLAR C
Solar/Wind Harmer
0.669
219221BRL12CT1
Adder
9.964
219223BRL12CT3
Adder
9.964
20716028EGP_W2-019
Solar/Wind Harmer
0.515
20720828JCB_W4-025
Solar/Wind Harmer
0.503
20715028HAN_X4-015
Solar/Wind Harmer
0.331
959561AF2-247 GEN
Solar/Wind Harmer
0.539
20636028O CRK C1
Adder
7.834
971667AH1-334 GEN
Solar/Wind Harmer
3.042
219727YARDVSOLFA C
Solar/Wind Harmer
1.006
20714528FRN_Y2-051
Solar/Wind Harmer
0.326
219276PARKLANDSO C
Solar/Wind Harmer
0.51
219918AC2-009 C
Solar/Wind Harmer
0.068
20716228APLW2-078
Solar/Wind Harmer
0.975
20720528MAN_W1-024
Solar/Wind Harmer
0.28
967451AG2-055 C O1
Solar/Wind Harmer
191.455
219612MATRIX C
Solar/Wind Harmer
0.203
218438BLK ROCK C
Solar/Wind Harmer
0.15
20635828PARLN1&2
Adder
3.69
20635928PARLN3&4
Adder
3.69
20635028RRCT1&2
Adder
12.967
20635128RRCT3&4
Adder
10.751
219908AB1-139 C
Solar/Wind Harmer
0.419
219919AE1-041 FULL
Solar/Wind Harmer
0.044
219249CENTRALDIV C
Solar/Wind Harmer
0.044
20673728F2S_V4-070
Solar/Wind Harmer
0.197
217211CAMDEN ST C
Solar/Wind Harmer
0.027
217186ESSEX_G9
Adder
17.526
217169METRODIV C
Solar/Wind Harmer
0.044
217194REDH C
Solar/Wind Harmer
0.54
20676728BRNX1-095
Solar/Wind Harmer
0.193
207510AF2-138 C
Solar/Wind Harmer
1.944
20674628WNG_W3-110
Solar/Wind Harmer
0.441
971007AG2-625 GEN
Solar/Wind Harmer
2.802
20466127PORT 5CT
Adder
28.865
20633028GILCT9
Adder
30.799
966181AG1-487 GEN
Solar/Wind Harmer
0.273
20465427SHAW CT
Adder
4.194
963161AG1-165 GEN
Solar/Wind Harmer
1.051
209025WIENIPP3
Adder
5.543
963071AG1-156 GEN
Solar/Wind Harmer
2.881
970095AG2-074 GEN
Solar/Wind Harmer
6.538
209027LOR2_Q27
Solar/Wind Harmer
4.671
209022WHFR IPP
Adder
3.354
961331AF2-424 GEN
Solar/Wind Harmer
1.016
961421AF2-433 GEN
Solar/Wind Harmer
1.013
957921AF2-086 GEN
Solar/Wind Harmer
0.985
209142AF1-226 GEN
Solar/Wind Harmer
5.866
209093AE2-110 GEN
Solar/Wind Harmer
2.533
209120AE2-241 GEN
Solar/Wind Harmer
3.352
972245AH1-707 GEN
Adder
5.462
946691AF1-333 GEN
Solar/Wind Harmer
0.992
946741AF1-338 GEN
Solar/Wind Harmer
0.992
972221AH1-695 GEN
Adder
123.49
209067AE2-060 GEN
Solar/Wind Harmer
1.327
3141196NOKESVL
Solar/Wind Helper
1.258
316044AC1-158 PL1
Solar/Wind Helper
1.66
316450AC1-158 RIC
Solar/Wind Helper
0.443
316170AC1-121 GEN2
Solar/Wind Helper
0.456
3132273ORANGE
Solar/Wind Helper
0.058
3147666LOUISA
Solar/Wind Helper
0.667
966881AG1-559 GEN
Solar/Wind Helper
0.389
238147AE2-230_GEN1
Solar/Wind Helper
0.491
238149AF1-291A_GEN
Solar/Wind Helper
0.14
3141906WESTMOR
Solar/Wind Helper
0.114
316473AC1-191 GEN
Solar/Wind Helper
1.721
237061AD1-155 GEN
Solar/Wind Helper
0.053
230425AE1-104_GEN2
Solar/Wind Harmer
38.585
230433AD2-135 GEN
Solar/Wind Harmer
0.116
230407AD2-065 C
Solar/Wind Harmer
0.15
228307PCLP GT
Adder
13.795
228304LOGAN
Adder
27.568
972233AH1-701 GEN
Adder
4.774
219921AF1-264
Solar/Wind Harmer
0.163
213589EDDYSTN4
Adder
89.603
213587EDDYSTN3
Adder
89.597
219615MILLCREEK C
Solar/Wind Harmer
0.267
213815MOSER1-3
Adder
3.964
213815MOSER1-3
Adder
3.964
213535CROYDN11
Adder
11.414
20716428NHV_W2-082
Solar/Wind Harmer
1.972
207500AE2-000G1
Solar/Wind Harmer
34.915
207497AE2-000G2
Solar/Wind Harmer
34.915
207507AE2-000G3
Solar/Wind Harmer
34.915
20636128O CRK C2
Adder
7.143
963401AG1-189 GEN
Solar/Wind Harmer
1.274
963391AG1-188 GEN
Solar/Wind Harmer
2.124
20714928UPF_X1-085
Solar/Wind Harmer
0.451
20628028LAKEHURS
Adder
1.053
219114HARTZY_C
Solar/Wind Harmer
0.923
219817TRENTONSOL C
Solar/Wind Harmer
1.217
20641628MLH_W1-032
Solar/Wind Harmer
0.324
20720628TIN_W1-124
Solar/Wind Harmer
1.099
20716928W4-060COL
Solar/Wind Harmer
0.783
924131AB2-057 GEN
Solar/Wind Harmer
1.132
218440SUMMTASSOC C
Solar/Wind Harmer
0.141
218418LINDEN_G5
Adder
18.867
218419LINDEN_G6
Adder
18.867
972260AH1-715 GEN1
Adder
15.108
20673828FLE_V3-070
Solar/Wind Harmer
0.503
207442AE1-156 GEN
Solar/Wind Harmer
0.817
20676128MHD_W3-029
Solar/Wind Harmer
0.524
219036LINDEN_G7
Adder
18.36
219035LINDEN_G8
Adder
18.099
972261AH1-715 GEN2
Adder
17.576
217081WEATEXAS C
Solar/Wind Harmer
0.094
217202FBANKSOLAR C
Solar/Wind Harmer
0.081
217201HACKENSOLA C
Solar/Wind Harmer
0.08
972237AH1-703 GEN
Adder
11.092
217206BARNGR HS C
Solar/Wind Harmer
0.034
217086KRNY_131
Adder
10.211
217083KRNY_132
Adder
10.125
20671828STAW2-080
Solar/Wind Harmer
0.115
217204WCALDSOLAR C
Solar/Wind Harmer
0.08
20674528F3S_W2-016
Solar/Wind Harmer
1.541
20676228FRD_X1-012
Solar/Wind Harmer
0.646
207471AF2-354 C
Solar/Wind Harmer
0.558
20674928WA_W3-044
Solar/Wind Harmer
0.526
964851AG1-348 GEN
Solar/Wind Harmer
1.917
20634528N27_Y2-018
Solar/Wind Harmer
0.293
20465127PORT CT
Adder
4.34
20674128FR_U2-059
Solar/Wind Harmer
0.201
966111AG1-480 GEN
Solar/Wind Harmer
0.094
966111AG1-480 GEN
Solar/Wind Harmer
3.579
211065PSPA IPP
Solar/Wind Harmer
0.487
211065PSPA IPP
Solar/Wind Harmer
0.487
208972BECR K09
Solar/Wind Harmer
1.098
961541AF2-445A GEN
Solar/Wind Harmer
3.355
209029WAYMART-WD
Solar/Wind Harmer
2.976
209009PEIP 2
Adder
8.081
209010PEIP 1
Adder
3.661
209010PEIP 1
Adder
0.536
961431AF2-434 GEN
Solar/Wind Harmer
1.013
209054AE2-059 GEN
Solar/Wind Harmer
1.689
209059AE2-084 GEN
Solar/Wind Harmer
2.494
946751AF1-339 GEN
Solar/Wind Harmer
0.992
209130AF1-271A GEN
Solar/Wind Harmer
2.785
20465527S.RDG CT
Adder
2.633
20478527GLRA_Q45
Adder
0.304
209137AF2-361 C
Solar/Wind Harmer
2.566
238175AF1-290_GEN
Solar/Wind Helper
0.158
315651AD1-115 GEN
Solar/Wind Helper
1.005
316447AC1-158 HLD
Solar/Wind Helper
3.655
238169AE2-226 GEN1
Solar/Wind Helper
0.722
238170AE2-226 GEN2
Solar/Wind Helper
0.722
966001AG1-469 GEN
Solar/Wind Helper
0.309
316468AD1-105 GEN
Solar/Wind Helper
1.418
316077AC2-138 C
Solar/Wind Helper
0.265
966871AG1-558 GEN
Solar/Wind Helper
0.38
316487AF1-042 GEN
Solar/Wind Helper
0.284
316075AC2-137 C
Solar/Wind Helper
0.426
3143526WINTERP
Solar/Wind Helper
1.451
3142946ENON
Solar/Wind Helper
0.028
316240AF1-291 C
Solar/Wind Helper
0.371
316033AB2-134 GEN
Solar/Wind Helper
0.948
315697AD1-025 GEN
Solar/Wind Helper
3.15
316236AE1-162_GEN
Solar/Wind Helper
0.368
316036AC1-147 C
Solar/Wind Helper
0.416
316316AC1-027 C
Solar/Wind Helper
0.431
3142956BIRDNECK
Solar/Wind Helper
0.184
316185AD1-033 GEN
Solar/Wind Helper
1.283
3145506HICKORY
Solar/Wind Helper
1.091
3145506HICKORY
Solar/Wind Helper
0.654
3145506HICKORY
Solar/Wind Helper
0.164
316339AD2-160 GEN
Solar/Wind Helper
1.037
235020AA1-095 C
Solar/Wind Helper
0.051
316018AA1-139 ULT2
Solar/Wind Helper
1.171
316017AA1-139 ULT1
Solar/Wind Helper
1.244
3137176SLIGO L2192
Solar/Wind Helper
1.083
23777901MDS_W4-102
Solar/Wind Helper
0.17
3130086AYDLETT
Solar/Wind Helper
1.088
3146386ELIZ CT
Solar/Wind Helper
0.271
316431W1029_GEN1
Solar/Wind Helper
1.092
316433W1029_GEN2
Solar/Wind Helper
1.092
3146516WINFALL
Solar/Wind Helper
0.27
3146516WINFALL
Solar/Wind Helper
0.27
3146516WINFALL
Solar/Wind Helper
0.27
3146626S HERTFORD
Solar/Wind Helper
0.27
3146626S HERTFORD
Solar/Wind Helper
0.27
3144356SAPONY
Solar/Wind Helper
0.483
315742AE1-103 GEN
Solar/Wind Helper
0.433
3132123MT JACKSON
Solar/Wind Helper
0.835
3146776BUCKING
Solar/Wind Helper
1.06
3146776BUCKING
Solar/Wind Helper
0.086
3145893MURPHYS
Solar/Wind Helper
0.378
3145893MURPHYS
Solar/Wind Helper
0.474
3146173TUNIS
Solar/Wind Helper
0.263
3146173TUNIS
Solar/Wind Helper
0.263
315821AE2-092 GEN
Solar/Wind Helper
2.433
316181AB2-040 GEN
Solar/Wind Helper
1.874
3147133PAMPLIN
Solar/Wind Helper
0.261
3147133PAMPLIN
Solar/Wind Helper
0.209
3142666NORTHAMPTON
Solar/Wind Helper
0.261
3142666NORTHAMPTON
Solar/Wind Helper
0.261
3142666NORTHAMPTON
Solar/Wind Helper
0.261
3142666NORTHAMPTON
Solar/Wind Helper
0.156
316426AA2-053 GEN
Solar/Wind Helper
1.486
3145593CAROLNA
Solar/Wind Helper
0.26
3145593CAROLNA
Solar/Wind Helper
0.26
3145796HORNRTN
Solar/Wind Helper
0.778
316034AC1-036 C
Solar/Wind Helper
0.271
3145933PARMELE
Solar/Wind Helper
0.514
3145933PARMELE
Solar/Wind Helper
0.257
316274AC1-208 GEN
Solar/Wind Helper
1.567
226929AD2-058 GEN
Solar/Wind Helper
0.099
3146843MT LREL
Solar/Wind Helper
0.253
3146843MT LREL
Solar/Wind Helper
0.253
237034AC2-136 C
Solar/Wind Helper
0.207
316222AC1-221 GEN
Solar/Wind Helper
1.387
316197AC1-042 GEN
Solar/Wind Helper
0.215
270013AE1-250 PV
Solar/Wind Helper
0.844
237002AB1-128_GEN
Solar/Wind Helper
0.363
217121ECCF
Adder
0.476
217083KRNY_132
Adder
10.19
217208PARK ELE C
Solar/Wind Harmer
0.028
207439AE1-081 C O1
Solar/Wind Harmer
0.065
20674328GAR_V4-001
Solar/Wind Harmer
0.12
20675828AU_W4-064
Solar/Wind Harmer
0.189
971519AH1-257 GEN
Solar/Wind Harmer
2.75
207518AF1-320_GEN
Solar/Wind Harmer
3.986
207437AD2-070 GEN
Solar/Wind Harmer
0.328
20465127PORT CT
Adder
3.27
20671928W4-073
Solar/Wind Harmer
0.471
966181AG1-487 GEN
Solar/Wind Harmer
4.076
208909MACR G3
Adder
173.269
961301AF2-421 GEN
Solar/Wind Harmer
1.051
963151AG1-164 GEN
Solar/Wind Harmer
1.051
209023WIENIPP1
Adder
11.334
209025WIENIPP3
Adder
5.657
212266LOR1
Solar/Wind Harmer
0.134
970237AG2-161 GEN
Solar/Wind Harmer
3.587
209010PEIP 1
Adder
0.666
961341AF2-425 GEN
Solar/Wind Harmer
1.016
212174INGE
Adder
1.123
205941AD2-115 GEN
Solar/Wind Harmer
0.937
212507AE2-042_GEN
Solar/Wind Harmer
2.992
946731AF1-337 GEN
Solar/Wind Harmer
0.992
209071AE2-133 GEN
Solar/Wind Harmer
1.678
970665AG2-430 GEN
Solar/Wind Harmer
9.83
209018SUNBIPCT
Adder
7.378
20467927PC_Q59Y356
Adder
0.836
20465527S.RDG CT
Adder
2.721
972241AH1-705 GEN
Adder
5.64
209008PAXT IPP
Adder
1.813
970679AG2-439 GEN
Solar/Wind Harmer
1.158
200917MEHOOPANY_G
Solar/Wind Harmer
3.648
205967AE2-211_GEN
Solar/Wind Harmer
5.775
972271AH1-720 GEN
Adder
6.105
941421AE2-139 GEN
Solar/Wind Harmer
2.743
20328326MANOR_T86
Adder
0.126
316006AB2-029 C
Solar/Wind Helper
0.145
316045AC1-158 PL2
Solar/Wind Helper
5.315
316254AC1-120 GEN1
Solar/Wind Helper
1.368
3147666LOUISA
Solar/Wind Helper
1.161
316192AB2-158 GEN
Solar/Wind Helper
1.949
238148AE2-230_GEN2
Solar/Wind Helper
0.493
316337AD2-073 GEN
Solar/Wind Helper
0.43
964211AG1-282 GEN
Solar/Wind Helper
0.38
3141726DUNNSVL
Solar/Wind Helper
1.127
3142416OLDCHRC
Solar/Wind Helper
0.729
3142416OLDCHRC
Solar/Wind Helper
0.279
3138133OCRAN
Solar/Wind Helper
0.168
3141766HARMONY
Solar/Wind Helper
0.056
3143526WINTERP
Solar/Wind Helper
1.451
3142433PROV 92
Solar/Wind Helper
1.116
3143226MDLTHAN
Solar/Wind Helper
0.279
3142543TWELFTH
Solar/Wind Helper
0.027
316159AE1-175 C
Solar/Wind Helper
0.42
316458AB2-190 GEN2
Solar/Wind Helper
1.578
3145336SMITFLD
Solar/Wind Helper
1.097
316294AC1-161 GEN
Solar/Wind Helper
5.011
316381AD1-082 GEN
Solar/Wind Helper
1.417
316375AC2-012 GEN
Solar/Wind Helper
0.716
316072AD1-144
Solar/Wind Helper
0.312
316336AC2-165 C
Solar/Wind Helper
1.47
316388AE2-253 GEN
Solar/Wind Helper
1.037
3146456SLIGO L269
Solar/Wind Helper
0.272
316246AF1-032 C
Solar/Wind Helper
0.311
3146516WINFALL
Solar/Wind Helper
0.875
3146516WINFALL
Solar/Wind Helper
0.27
315800Z1-036_GEN1
Solar/Wind Helper
1.478
3130156CHOWAN
Solar/Wind Helper
0.268
3145663CRESWEL
Solar/Wind Helper
0.745
316322AB2-045
Solar/Wind Helper
0.295
3146776BUCKING
Solar/Wind Helper
0.106
3146926FARMVIL
Solar/Wind Helper
0.158
316023GEN1_S
Solar/Wind Helper
1.004
3146206CASHIE
Solar/Wind Helper
0.264
3145893MURPHYS
Solar/Wind Helper
1.054
3146173TUNIS
Solar/Wind Helper
0.263
3147983MERCK5
Solar/Wind Helper
0.105
316097T157 G90
Solar/Wind Helper
1.209
3145683EARLEYS
Solar/Wind Helper
0.262
3146263WOODLND
Solar/Wind Helper
0.261
316190AA2-174 GEN
Solar/Wind Helper
0.017
3145963POPLR C
Solar/Wind Helper
0.261
316011AB1-132 GEN
Solar/Wind Helper
2.803
3145823KELFORD
Solar/Wind Helper
0.26
316174AB2-169 GEN
Solar/Wind Helper
0.662
3145783HORNRTN
Solar/Wind Helper
0.26
3145796HORNRTN
Solar/Wind Helper
0.856
3145796HORNRTN
Solar/Wind Helper
0.259
316129AC1-054 GEN
Solar/Wind Helper
1.276
316212AC1-099_GEN
Solar/Wind Helper
1.155
316237AB2-079_GEN
Solar/Wind Helper
0.345
3145746EVERETS
Solar/Wind Helper
0.256
3145746EVERETS
Solar/Wind Helper
0.256
315687AD1-152 GEN
Solar/Wind Helper
1.374
315722AD1-056 GEN
Solar/Wind Helper
1.374
316494AC1-189 GEN
Solar/Wind Helper
1.555
3146233WITAKRS
Solar/Wind Helper
1.009
961671AG1-007 GEN
Solar/Wind Helper
0.182
3146083TARBORO
Solar/Wind Helper
0.254
3145543BTLEBRO
Solar/Wind Helper
0.252
3145543BTLEBRO
Solar/Wind Helper
0.202
316359AB2-059 GEN
Solar/Wind Helper
1.922
316049AB1-081 GEN
Solar/Wind Helper
1.537
316003AC1-222 GEN
Solar/Wind Helper
1.076
237080AD1-060 GEN
Solar/Wind Helper
0.298
964991AG1-363 GEN
Solar/Wind Helper
3.503
237038AE2-054 C
Solar/Wind Helper
0.229
3147123OTTER R
Solar/Wind Helper
0.138
3147312GRETNA
Solar/Wind Helper
0.183
3146802CHATHAM
Solar/Wind Helper
0.172
270016AE1-250 BESS
Solar/Wind Helper
0.844
270173AC1-122 GEN
Solar/Wind Helper
1.452
200202DELTA2 ST
50/50
6.616
200195DELTA ST
50/50
3.367
200052ROCKSP 1
50/50
2.848
200053ROCKSP 2
50/50
2.787
233973AC2-185 C
Solar/Wind Harmer
4.72
234033AF1-007_GEN
Solar/Wind Harmer
30.507
232904IR4
Adder
105.483
232920IR10
Adder
4.123
232432Z2-076 GEN
Solar/Wind Harmer
0.172
232912OH NUG1
Adder
11.52
232913OH NUG2
Adder
11.366
233923SMA
Solar/Wind Harmer
6.057
233990AG1-397 GEN
Solar/Wind Harmer
0.072
233955AB2-172 GEN
Solar/Wind Harmer
6.513
232813VAUGHN
Adder
0.765
231906DC3 NUG
Adder
18.075
231902DC CT7
Adder
14.45
231907DC10
Adder
4.512
233968AD2-076_GEN
Solar/Wind Harmer
8.565
970597AG2-380 GEN
Solar/Wind Harmer
5.378
232436AB1-176 C
Solar/Wind Harmer
0.296
971983AH1-536 GEN
Solar/Wind Harmer
9.638
233935AB2-179 C
Solar/Wind Harmer
3.173
231919CHRIST1
Adder
5.578
231920CHRIST2
Adder
5.454
970453AG2-297 GEN
Solar/Wind Harmer
3.175
228260V4-054C
Solar/Wind Harmer
1.177
228309CCLP NUG
Adder
29.6
228309CCLP NUG
Adder
28.157
972141AH1-641 GEN
Solar/Wind Harmer
3.293
964001AG1-254 GEN
Solar/Wind Harmer
2.326
971011AG2-627 GEN
Solar/Wind Harmer
8.755
971535AH1-265 GEN
Solar/Wind Harmer
4.864
227927V4-067C
Solar/Wind Harmer
0.227
228754AB1-001 C
Solar/Wind Harmer
0.159
219137THOSOLAR C
Solar/Wind Harmer
1.368
219272CLEANLIGHT C
Solar/Wind Harmer
0.206
219688LUMSOLAR_S C
Solar/Wind Harmer
0.228
219914AD2-027 C
Solar/Wind Harmer
0.675
213942SCHUYLKILL
Adder
3.985
213942SCHUYLKILL
Adder
3.048
213957STHWK3-4
Adder
3.047
213957STHWK3-4
Adder
3.047
213561DLWR9-10
Adder
3.974
213561DLWR9-10
Adder
3.039
219607WPEMNERT C
Solar/Wind Harmer
0.468
219224BRL12CT4
Adder
9.964
214067T20SOLAR
Solar/Wind Harmer
0.281
213611FALLS1-3
Adder
3.929
213611FALLS1-3
Adder
3.929
20717128DIX_Z2-102
Solar/Wind Harmer
1.464
20715728PEM_W1-119
Solar/Wind Harmer
0.593
20715828PEM_W1-120
Solar/Wind Harmer
0.593
970025AG2-016 GEN
Solar/Wind Harmer
3.139
971189AH1-054 GEN
Solar/Wind Harmer
1.307
207459AE1-142 C O1
Solar/Wind Harmer
1.169
219620RIDERU C
Solar/Wind Harmer
0.062
20714328BYD_X4-031
Solar/Wind Harmer
0.312
20714428HOW_X1-037
Solar/Wind Harmer
1.363
971521AH1-258 GEN
Solar/Wind Harmer
2.983
20720428HOL_W1-112
Solar/Wind Harmer
0.381
20635928PARLN3&4
Adder
8.146
218455CINNBAY_CGEN
Adder
2
218526CNTRALGAS2 C
Solar/Wind Harmer
0.408
218524CNTRALGAS1 C
Solar/Wind Harmer
0.407
20675528CPH_W2-050
Solar/Wind Harmer
0.514
218404KENILWRTH C
Adder
1.432
217167KRNY_14
Adder
10.19
217086KRNY_131
Adder
10.103
217147KRNY_1212
Adder
9.692
217147KRNY_1212
Adder
9.519
217146KRNY_1234
Adder
9.497
217146KRNY_1234
Adder
9.432
966261AG1-495 GEN
Solar/Wind Harmer
1.963
20676328BVR_Y1-020
Solar/Wind Harmer
0.361
207511W3-106 GEN
Solar/Wind Harmer
0.717
207530AG1-191 GEN
Solar/Wind Harmer
1.503
20674828DL_W4-046
Solar/Wind Harmer
0.705
971009AG2-626 GEN
Solar/Wind Harmer
1.787
207408W3-077 C
Solar/Wind Harmer
0.552
20675728RH_W2-091
Solar/Wind Harmer
0.373
20675928HOL_W4-097
Solar/Wind Harmer
0.142
207484AF2-139 C O1
Solar/Wind Harmer
0.551
20675128HRM_W1-127
Solar/Wind Harmer
0.185
966421AG1-511 GEN
Solar/Wind Harmer
9.371
20462827N BANGR8
Adder
0.78
209116AE2-175 GEN
Solar/Wind Harmer
4.453
961261AF2-417 GEN
Solar/Wind Harmer
1.054
209026WIENIPP4
Adder
5.6
209045AE2-271 GEN
Solar/Wind Harmer
16.941
959431AF2-234 GEN
Solar/Wind Harmer
1.981
964051AG1-259 GEN
Solar/Wind Harmer
1.329
964061AG1-260 GEN
Solar/Wind Harmer
1.329
959421AF2-233 GEN
Solar/Wind Harmer
0.991
20486527WR_V4-052
Adder
1.062
208862AG1-362 C
Solar/Wind Harmer
0.769
20390726Y2-042
Adder
2.77
20334726NME_Y1-047
Adder
2.451
205951AE1-129_GEN
Solar/Wind Harmer
7.582
203926AA2-133 GEN
Adder
2.264
3138216PACIFIC
Solar/Wind Helper
0.054
316411AF1-147_GEN1
Solar/Wind Helper
1.09
316415AF1-147_GEN2
Solar/Wind Helper
1.09
3141426STAFORD
Solar/Wind Helper
0.066
316164AC1-076 GEN
Solar/Wind Helper
1.418
238152AF2-075_GEN
Solar/Wind Helper
0.701
316223AC1-118
Solar/Wind Helper
0.434
23546401DTGZ2-030
Solar/Wind Helper
0.089
3141813NORNECK
Solar/Wind Helper
0.282
316312AB1-027
Solar/Wind Helper
0.534
3141783LANCAST
Solar/Wind Helper
0.168
3141783LANCAST
Solar/Wind Helper
0.112
3138133OCRAN
Solar/Wind Helper
0.084
3141913WHIT STONE
Solar/Wind Helper
0.28
316059AD1-063 C
Solar/Wind Helper
0.281
3143873LANEXA
Solar/Wind Helper
0.167
315662AE1-191 GEN
Solar/Wind Helper
1.5
315666AE1-190 GEN
Solar/Wind Helper
0.375
957601AF2-054 GEN
Solar/Wind Helper
0.374
3141873WAN 176
Solar/Wind Helper
0.056
316233AE1-074 FULL
Solar/Wind Helper
0.426
957831AF2-077 GEN
Solar/Wind Helper
0.374
316132AB2-190 GEN1
Solar/Wind Helper
1.578
316369SG1_INVT
Solar/Wind Helper
1.326
3143316POE
Solar/Wind Helper
1.085
316349AD2-085 GEN
Solar/Wind Helper
1.246
319010AE1-072 C
Solar/Wind Helper
3.109
316305AF2-043 C
Solar/Wind Helper
0.366
313526AB2-022
Solar/Wind Helper
0.413
3146486SUNBURY
Solar/Wind Helper
0.271
3146486SUNBURY
Solar/Wind Helper
0.271
316321Z2-027
Solar/Wind Helper
0.413
3145176PASQUOTANK
Solar/Wind Helper
0.168
316315AB2-025 C
Solar/Wind Helper
0.411
315611Z1-036_GEN2
Solar/Wind Helper
1.478
3130156CHOWAN
Solar/Wind Helper
0.268
3130156CHOWAN
Solar/Wind Helper
0.268
315816AE2-034 GEN
Solar/Wind Helper
1.216
3138266HYDRAULIC
Solar/Wind Helper
0.012
3138266HYDRAULIC
Solar/Wind Helper
0.008
3130546PLYMOUTH
Solar/Wind Helper
0.265
315732AD1-074 GEN1
Solar/Wind Helper
3.021
315733AD1-074 GEN2
Solar/Wind Helper
3.021
315735AD1-075 GEN1
Solar/Wind Helper
1.51
3146206CASHIE
Solar/Wind Helper
0.264
3145893MURPHYS
Solar/Wind Helper
0.711
3145893MURPHYS
Solar/Wind Helper
0.264
3145513AHOSKIE
Solar/Wind Helper
0.118
961941AG1-037 GEN
Solar/Wind Helper
0.088
3145513AHOSKIE
Solar/Wind Helper
0.262
946281AF1-292 GEN
Solar/Wind Helper
0.263
3146043SEABORD
Solar/Wind Helper
0.262
3145683EARLEYS
Solar/Wind Helper
0.524
3145683EARLEYS
Solar/Wind Helper
0.262
3145683EARLEYS
Solar/Wind Helper
0.262
315607AA1-063A GEN
Solar/Wind Helper
1.494
316087AB2-174 GEN
Solar/Wind Helper
1.829
3137643SOCKMAN
Solar/Wind Helper
1.042
3148133STUARTS
Solar/Wind Helper
0.156
3148013FISHERV
Solar/Wind Helper
0.149
3145796HORNRTN
Solar/Wind Helper
0.83
3145796HORNRTN
Solar/Wind Helper
0.104
3144303KENBRDG
Solar/Wind Helper
0.207
3146033SCOT NK
Solar/Wind Helper
1.035
316239AB2-077_GEN
Solar/Wind Helper
0.345
316238AB2-078_GEN
Solar/Wind Helper
0.345
316005AA1-067
Solar/Wind Helper
0.292
3145746EVERETS
Solar/Wind Helper
1.018
3145746EVERETS
Solar/Wind Helper
0.256
3145746EVERETS
Solar/Wind Helper
0.256
3145746EVERETS
Solar/Wind Helper
0.256
270494AE1-108_GEN
Solar/Wind Helper
3.409
316420AA1-050 GEN
Solar/Wind Helper
1.456
3145573BETHELC
Solar/Wind Helper
0.254
3145573BETHELC
Solar/Wind Helper
0.254
238208AF1-136 C
Solar/Wind Helper
0.196
238109AE1-109 GEN2
Solar/Wind Helper
0.094
238110AE1-109 GEN3
Solar/Wind Helper
0.094
316118AC1-105 GEN
Solar/Wind Helper
0.977
3148463FAIRFLD
Solar/Wind Helper
0.251
3147173SINAI
Solar/Wind Helper
0.25
3147243WELCO
Solar/Wind Helper
0.156
316123AC1-075 GEN
Solar/Wind Helper
1.467
270455AD2-022 GEN
Solar/Wind Helper
1.374
270457AD2-023 GEN
Solar/Wind Helper
0.905
237085AD2-009_GEN
Solar/Wind Helper
1.357
316404AE1-155 C
Solar/Wind Helper
2.375
316484AD2-074 GEN
Solar/Wind Helper
0.542
316280AD1-041 GEN
Solar/Wind Helper
0.938
316156AD2-030 GEN
Solar/Wind Helper
0.421
3142946ENON
Solar/Wind Helper
0.093
316382AG1-145 C
Solar/Wind Helper
0.372
315839AE2-212 C
Solar/Wind Helper
0.37
3145336SMITFLD
Solar/Wind Helper
0.11
315773AC2-141 GEN
Solar/Wind Helper
5.898
316313AB2-026
Solar/Wind Helper
0.417
316258AE1-075 C
Solar/Wind Helper
0.375
316405AF2-144 C
Solar/Wind Helper
0.313
3144536CHRHLND
Solar/Wind Helper
0.041
3144873MCLAUGH
Solar/Wind Helper
0.007
3146456SLIGO L269
Solar/Wind Helper
0.272
316320Y1-086
Solar/Wind Helper
0.121
316435W1029_GEN3
Solar/Wind Helper
1.092
3146516WINFALL
Solar/Wind Helper
0.27
3146626S HERTFORD
Solar/Wind Helper
0.27
3145273HOLLAND
Solar/Wind Helper
0.202
3146376EDENTON
Solar/Wind Helper
0.268
315614AA2-178 GEN
Solar/Wind Helper
1.621
3146776BUCKING
Solar/Wind Helper
0.095
315737AD1-076 GEN
Solar/Wind Helper
2.584
3146926FARMVIL
Solar/Wind Helper
0.158
316365GEN2_N
Solar/Wind Helper
1.004
3146206CASHIE
Solar/Wind Helper
0.264
3145893MURPHYS
Solar/Wind Helper
0.094
3145893MURPHYS
Solar/Wind Helper
0.264
3146173TUNIS
Solar/Wind Helper
0.263
316095T157 G97
Solar/Wind Helper
1.209
3156021HOLLOMANSOL
Solar/Wind Helper
1.997
316463AE2-346 GEN
Solar/Wind Helper
0.24
316140AB2-099
Solar/Wind Helper
0.1
942461AE2-259 GEN
Solar/Wind Helper
1.768
966621AG1-532 GEN
Solar/Wind Helper
0.239
316499AE2-029_GEN
Solar/Wind Helper
0.881
3146263WOODLND
Solar/Wind Helper
0.261
313506AB2-031 GEN
Solar/Wind Helper
1.186
3147133PAMPLIN
Solar/Wind Helper
0.819
3142666NORTHAMPTON
Solar/Wind Helper
0.261
3147043LAWRENC
Solar/Wind Helper
0.156
3145963POPLR C
Solar/Wind Helper
0.261
316317KELFORD C
Solar/Wind Helper
0.222
3145823KELFORD
Solar/Wind Helper
0.26
316478AD1-087 GEN
Solar/Wind Helper
1.27
316486AD2-202 GEN
Solar/Wind Helper
0.372
3148013FISHERV
Solar/Wind Helper
0.26
3145796HORNRTN
Solar/Wind Helper
1.037
3145796HORNRTN
Solar/Wind Helper
0.259
315785AD2-033 C
Solar/Wind Helper
3.016
316210AC1-098 GEN
Solar/Wind Helper
2.079
316131AB2-060 GEN
Solar/Wind Helper
1.568
3145933PARMELE
Solar/Wind Helper
0.257
23583801GRNGAP
Solar/Wind Helper
4.398
3145746EVERETS
Solar/Wind Helper
0.256
3145746EVERETS
Solar/Wind Helper
0.256
315724AD1-057 GEN
Solar/Wind Helper
0.756
316327AA2-057 GEN
Solar/Wind Helper
1.454
3146233WITAKRS
Solar/Wind Helper
0.273
3146233WITAKRS
Solar/Wind Helper
0.172
3146073TAR RVR
Solar/Wind Helper
0.254
3146083TARBORO
Solar/Wind Helper
0.254
3138543CONSLDL
Solar/Wind Helper
0.167
3145543BTLEBRO
Solar/Wind Helper
0.252
3145543BTLEBRO
Solar/Wind Helper
0.252
238108AE1-109 GEN1
Solar/Wind Helper
0.094
238221AF1-254 C O1
Solar/Wind Helper
0.247
315616AA1-038_C
Solar/Wind Helper
1.138
316248AF1-058 C
Solar/Wind Helper
0.336
227287AC2-120 GEN
Solar/Wind Helper
0.335
226910AB2-157 C
Solar/Wind Helper
0.014
316283AC2-100 C
Solar/Wind Helper
1.295
235067AD1-061 GEN
Solar/Wind Helper
0.416
3147312GRETNA
Solar/Wind Helper
0.046
270197AD1-017 GEN1
Solar/Wind Helper
1.223
270018AE2-047 C O1
Solar/Wind Helper
0.79
HAMLETPJM->LTFIMP_HAMLET
CLTF
5.986
G-007ALTFEXP_G-007A->PJM
CMTX
56.392
CBM NorthLTFEXP_CBM-N->PJM
CBM
83.016
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
4.559
BlueGrassPJM->LTFIMP_BlueG
CLTF
14.211
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
148.55
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.493
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
21.6

Details for CHAN-01DOUBS 500.0 kV Ckt 1 line l/o PJM_500_BG_P4_5_CNSTN_B_SRT-A


Base Case Flowgate

Area:AP/PJM
Facility Description:
CHAN-01DOUBS 500.0 kV Ckt 1 line
Contingency Name:
PJM_500_BG_P4_5_CNSTN_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.98 %
Rating:4150.0 MVA
Rating Type:B
MVA to Mitigate:4896.35
MW Contribution:8.8
Bus #Bus NameTypeMW Contribution
200202DELTA2 ST
50/50
6.635
200195DELTA ST
50/50
3.376
200052ROCKSP 1
50/50
2.858
200053ROCKSP 2
50/50
2.797
233973AC2-185 C
Solar/Wind Harmer
4.742
234033AF1-007_GEN
Solar/Wind Harmer
30.651
232904IR4
Adder
105.98
232920IR10
Adder
4.142
232432Z2-076 GEN
Solar/Wind Harmer
0.173
232912OH NUG1
Adder
11.574
232913OH NUG2
Adder
11.42
233923SMA
Solar/Wind Harmer
6.086
233990AG1-397 GEN
Solar/Wind Harmer
0.072
233955AB2-172 GEN
Solar/Wind Harmer
6.544
200035PCHBTM 3
50/50
23.268
200201DELTA2 CT2
50/50
3.91
200034PCHBTM 2
50/50
22.766
200205Y1-065-CTG2
50/50
4.526
971149AH1-027 GEN
Solar/Wind Harmer
4.442
233939AC1-091 C
Solar/Wind Harmer
1.153
233970AC1-092 C
Solar/Wind Harmer
1.153
970545AG2-347 GEN
Solar/Wind Harmer
85.772
232899W1-062
Adder
12.607
233987AB2-037 GEN
Solar/Wind Harmer
14.919
972069AH1-584 GEN
Solar/Wind Harmer
11.736
972071AH1-585 GEN
Solar/Wind Harmer
11.736
233901CHERRYDALE C
Solar/Wind Harmer
1.475
232408W1-005 C
Solar/Wind Harmer
1.313
232410W1-006 C
Solar/Wind Harmer
1.313
232918OH NUG7
Adder
11.497
971747AH1-380 GEN
Solar/Wind Harmer
4.694
232905CHERITON_25
Adder
3.215
232926CRISFLD1
Adder
2.572
231940T-011
Adder
0.977
233946AB2-136 GEN
Solar/Wind Harmer
5.224
234036AF2-325 C
Solar/Wind Harmer
1.2
234041AC1-190 GEN
Solar/Wind Harmer
11.718
233984AB2-036 GEN
Solar/Wind Harmer
16.21
232424Y1-079 C
Solar/Wind Harmer
0.732
200192DELTA CT1
50/50
2.185
200194DELTA CT3
50/50
2.185
200204Y1-065-CTG1
50/50
4.526
200054ROCKSP 3
50/50
2.887
232901NORTHST
Adder
10.924
233972AC1-094 C
Solar/Wind Harmer
0.871
232900DEMECSMY
Adder
12.092
232434Z2-077 GEN
Solar/Wind Harmer
0.328
972177AH1-672 GEN
Solar/Wind Harmer
17.606
232404W1-003 C
Solar/Wind Harmer
1.313
232917OH NUG6
Adder
11.523
232915OH NUG4
Adder
11.497
233998TM1NIN_3.36
Solar/Wind Harmer
1.66
971195AH1-057 GEN
Solar/Wind Harmer
1.434
232428Y3-058 C
Solar/Wind Harmer
1.093
232919VN10
Adder
3.675
965821AG1-450 GEN
Solar/Wind Harmer
6.817
232426Y1-080 FULL
Solar/Wind Harmer
0.25
970277AG2-181 GEN
Solar/Wind Harmer
6.566
233964AF2-378 GEN
Solar/Wind Harmer
0.167
233954AC2-188 GEN
Solar/Wind Harmer
1.473
233950AC2-186 GEN
Solar/Wind Harmer
0.737
232910NRG_G1
Adder
11.264
234012AE2-112_GEN
Solar/Wind Harmer
2.986
232422X3-066 FULL
Solar/Wind Harmer
0.325
233930AB2-032 GEN
Solar/Wind Harmer
1.08
233915AB1-141 GEN
Solar/Wind Harmer
1.283
231918WEST 1
Adder
4.261
231917EM10
Adder
2.978
228206SHRMN CT
Adder
19.135
228732V1-021 C
Adder
0.218
945431AF1-208 GEN
Solar/Wind Harmer
9.939
970997AG2-616 GEN
Solar/Wind Harmer
11.03
228351V2-046C
Solar/Wind Harmer
2.316
230511AF1-262
Solar/Wind Harmer
0.21
228728W1-130C
Solar/Wind Harmer
0.763
230434AG1-499 GEN
Solar/Wind Harmer
0.665
219258KINSLEYDEP C
Solar/Wind Harmer
0.367
213497CHSTR7-9
Adder
3.085
213497CHSTR7-9
Adder
3.085
218660EHAMPSOLAR C
Solar/Wind Harmer
0.198
219904AC1-010 C
Solar/Wind Harmer
0.428
219686LUMSOLAR_N C
Solar/Wind Harmer
0.229
219287REEVESEAST C
Solar/Wind Harmer
1.522
219907AC1-030 C
Solar/Wind Harmer
0.157
213958STHWK5-6
Adder
3.063
213560DLW11-12
Adder
3.055
219304NAMERICA C
Solar/Wind Harmer
0.348
219222BRL12CT2
Adder
10.013
213611FALLS1-3
Adder
3.948
214194N WALES4
Adder
0.952
20720728JCB_W1-129
Solar/Wind Harmer
0.333
207522AF2-254 C
Solar/Wind Harmer
1.599
207487AE2-000G4
Solar/Wind Harmer
35.082
207445AB1-138_GEN
Solar/Wind Harmer
0.645
20628028LAKEHURS
Adder
2.092
963711AG1-223 GEN
Solar/Wind Harmer
1.643
20714828MDF_W3-079
Solar/Wind Harmer
0.34
219680HOPEWELLV C1
Solar/Wind Harmer
0.084
207454AA2-184 E
Solar/Wind Harmer
1.108
20715228NPK_W1-113
Solar/Wind Harmer
0.477
200200DELTA2 CT1
50/50
3.91
200193DELTA CT2
50/50
2.185
200203Y1-065-STG
50/50
7.848
200055ROCKSP 4
50/50
2.826
233971AC1-093 C
Solar/Wind Harmer
1.03
970695AG2-447 GEN
Solar/Wind Harmer
4.702
972133AH1-634 GEN
Solar/Wind Harmer
12.996
972073AH1-586 GEN
Solar/Wind Harmer
12.282
232406W1-004 FULL
Solar/Wind Harmer
1.313
232914OH NUG3
Adder
11.574
232916OH NUG5
Adder
11.574
232921TASLEY2G
Adder
6.765
233996TM1833_GEN
Solar/Wind Harmer
1.66
233997TMININ_4.2
Solar/Wind Harmer
1.66
233990AG1-397 GEN
Solar/Wind Harmer
1.503
233940AF2-379 C
Solar/Wind Harmer
0.245
234015AF2-250 C
Solar/Wind Harmer
0.158
233900O-025 C
Adder
1.543
233994AC2-023 GEN
Solar/Wind Harmer
3.522
232907VN8
Adder
39.34
960671AF2-358 GEN
Solar/Wind Harmer
23.451
233952AC2-187 GEN
Solar/Wind Harmer
1.473
232417X3-008 C
Solar/Wind Harmer
2.617
972251AH1-710 GEN
Adder
58.018
233918AB1-142 GEN
Solar/Wind Harmer
1.283
233982AB2-133 GEN
Solar/Wind Harmer
6.303
228202CUMB CT
Adder
19.079
228711V2-041C
Solar/Wind Harmer
0.694
971553AH1-274 GEN
Solar/Wind Harmer
2.794
230430AE1-229_GEN
Solar/Wind Harmer
10.121
230415AB2-049 C
Solar/Wind Harmer
0.218
228729W2-030 C
Solar/Wind Harmer
0.663
228304LOGAN
Adder
24.915
219623KINSLEYBEA C
Solar/Wind Harmer
0.485
219291REEVESSOUT C
Solar/Wind Harmer
0.068
213497CHSTR7-9
Adder
3.085
219766PARADISE C
Solar/Wind Harmer
0.356
219912AD2-042 GEN
Solar/Wind Harmer
0.9
219236SOUTHERNHQ C
Solar/Wind Harmer
0.076
213958STHWK5-6
Adder
3.063
213560DLW11-12
Adder
3.055
219906AC1-017 C
Solar/Wind Harmer
0.251
213815MOSER1-3
Adder
3.984
219610FLORENCE C
Solar/Wind Harmer
1.554
219348LDSOLAR C
Solar/Wind Harmer
0.672
219221BRL12CT1
Adder
10.013
219223BRL12CT3
Adder
10.013
20716028EGP_W2-019
Solar/Wind Harmer
0.517
20720828JCB_W4-025
Solar/Wind Harmer
0.505
20715028HAN_X4-015
Solar/Wind Harmer
0.333
959561AF2-247 GEN
Solar/Wind Harmer
0.541
20636028O CRK C1
Adder
7.872
971667AH1-334 GEN
Solar/Wind Harmer
3.056
219727YARDVSOLFA C
Solar/Wind Harmer
1.011
20714528FRN_Y2-051
Solar/Wind Harmer
0.328
219276PARKLANDSO C
Solar/Wind Harmer
0.512
219918AC2-009 C
Solar/Wind Harmer
0.068
20716228APLW2-078
Solar/Wind Harmer
0.979
20720528MAN_W1-024
Solar/Wind Harmer
0.282
967451AG2-055 C O1
Solar/Wind Harmer
192.374
219612MATRIX C
Solar/Wind Harmer
0.204
218438BLK ROCK C
Solar/Wind Harmer
0.151
20635828PARLN1&2
Adder
3.707
20635928PARLN3&4
Adder
3.707
20635028RRCT1&2
Adder
13.03
20635128RRCT3&4
Adder
10.803
219908AB1-139 C
Solar/Wind Harmer
0.421
219919AE1-041 FULL
Solar/Wind Harmer
0.045
219249CENTRALDIV C
Solar/Wind Harmer
0.044
20673728F2S_V4-070
Solar/Wind Harmer
0.198
217211CAMDEN ST C
Solar/Wind Harmer
0.027
217186ESSEX_G9
Adder
17.611
217169METRODIV C
Solar/Wind Harmer
0.044
217194REDH C
Solar/Wind Harmer
0.542
20676728BRNX1-095
Solar/Wind Harmer
0.194
207510AF2-138 C
Solar/Wind Harmer
1.954
20674628WNG_W3-110
Solar/Wind Harmer
0.443
971007AG2-625 GEN
Solar/Wind Harmer
2.816
20466127PORT 5CT
Adder
29.008
20633028GILCT9
Adder
30.96
966181AG1-487 GEN
Solar/Wind Harmer
0.275
20465427SHAW CT
Adder
4.215
963161AG1-165 GEN
Solar/Wind Harmer
1.056
209025WIENIPP3
Adder
5.569
963071AG1-156 GEN
Solar/Wind Harmer
2.894
970095AG2-074 GEN
Solar/Wind Harmer
6.568
209027LOR2_Q27
Solar/Wind Harmer
4.692
209022WHFR IPP
Adder
3.369
961331AF2-424 GEN
Solar/Wind Harmer
1.02
961421AF2-433 GEN
Solar/Wind Harmer
1.018
957921AF2-086 GEN
Solar/Wind Harmer
0.99
209142AF1-226 GEN
Solar/Wind Harmer
5.892
209093AE2-110 GEN
Solar/Wind Harmer
2.545
209120AE2-241 GEN
Solar/Wind Harmer
3.367
972245AH1-707 GEN
Adder
5.486
946691AF1-333 GEN
Solar/Wind Harmer
0.997
946741AF1-338 GEN
Solar/Wind Harmer
0.997
972221AH1-695 GEN
Adder
124.721
209067AE2-060 GEN
Solar/Wind Harmer
1.335
3141196NOKESVL
Solar/Wind Helper
1.261
316044AC1-158 PL1
Solar/Wind Helper
1.664
316450AC1-158 RIC
Solar/Wind Helper
0.444
316170AC1-121 GEN2
Solar/Wind Helper
0.457
3132273ORANGE
Solar/Wind Helper
0.059
3147666LOUISA
Solar/Wind Helper
0.669
966881AG1-559 GEN
Solar/Wind Helper
0.39
238147AE2-230_GEN1
Solar/Wind Helper
0.492
238149AF1-291A_GEN
Solar/Wind Helper
0.141
3141906WESTMOR
Solar/Wind Helper
0.114
316473AC1-191 GEN
Solar/Wind Helper
1.726
237061AD1-155 GEN
Solar/Wind Helper
0.054
316404AE1-155 C
Solar/Wind Helper
2.382
316484AD2-074 GEN
Solar/Wind Helper
0.544
316280AD1-041 GEN
Solar/Wind Helper
0.94
316156AD2-030 GEN
Solar/Wind Helper
0.422
3142946ENON
Solar/Wind Helper
0.093
316382AG1-145 C
Solar/Wind Helper
0.373
231131BLOOM ENRGY
Adder
5.655
234014AF1-036_GEN
Solar/Wind Harmer
3.513
233944AB2-135 GEN
Solar/Wind Harmer
6.787
233933AB2-153 GEN
Solar/Wind Harmer
1.456
232416X2-083
Adder
0.579
228251CARLLS#4
Adder
0.727
230422AE1-104_GEN1
Solar/Wind Harmer
38.768
230425AE1-104_GEN2
Solar/Wind Harmer
38.768
230433AD2-135 GEN
Solar/Wind Harmer
0.116
230407AD2-065 C
Solar/Wind Harmer
0.151
228307PCLP GT
Adder
13.862
228304LOGAN
Adder
27.703
972233AH1-701 GEN
Adder
4.797
219921AF1-264
Solar/Wind Harmer
0.164
213589EDDYSTN4
Adder
90.084
213587EDDYSTN3
Adder
90.078
219615MILLCREEK C
Solar/Wind Harmer
0.268
213815MOSER1-3
Adder
3.984
213815MOSER1-3
Adder
3.984
213535CROYDN11
Adder
11.471
20716428NHV_W2-082
Solar/Wind Harmer
1.982
207500AE2-000G1
Solar/Wind Harmer
35.082
207497AE2-000G2
Solar/Wind Harmer
35.082
207507AE2-000G3
Solar/Wind Harmer
35.082
20636128O CRK C2
Adder
7.177
963401AG1-189 GEN
Solar/Wind Harmer
1.28
963391AG1-188 GEN
Solar/Wind Harmer
2.135
20714928UPF_X1-085
Solar/Wind Harmer
0.453
20628028LAKEHURS
Adder
1.058
219114HARTZY_C
Solar/Wind Harmer
0.927
219817TRENTONSOL C
Solar/Wind Harmer
1.222
20641628MLH_W1-032
Solar/Wind Harmer
0.325
20720628TIN_W1-124
Solar/Wind Harmer
1.104
20716928W4-060COL
Solar/Wind Harmer
0.787
924131AB2-057 GEN
Solar/Wind Harmer
1.137
218440SUMMTASSOC C
Solar/Wind Harmer
0.141
218418LINDEN_G5
Adder
18.958
218419LINDEN_G6
Adder
18.958
972260AH1-715 GEN1
Adder
15.181
20673828FLE_V3-070
Solar/Wind Harmer
0.505
207442AE1-156 GEN
Solar/Wind Harmer
0.821
20676128MHD_W3-029
Solar/Wind Harmer
0.527
219036LINDEN_G7
Adder
18.449
219035LINDEN_G8
Adder
18.186
972261AH1-715 GEN2
Adder
17.661
217081WEATEXAS C
Solar/Wind Harmer
0.095
217202FBANKSOLAR C
Solar/Wind Harmer
0.081
217201HACKENSOLA C
Solar/Wind Harmer
0.081
972237AH1-703 GEN
Adder
11.145
217206BARNGR HS C
Solar/Wind Harmer
0.034
217086KRNY_131
Adder
10.261
217083KRNY_132
Adder
10.174
20671828STAW2-080
Solar/Wind Harmer
0.116
217204WCALDSOLAR C
Solar/Wind Harmer
0.081
20674528F3S_W2-016
Solar/Wind Harmer
1.548
20676228FRD_X1-012
Solar/Wind Harmer
0.649
207471AF2-354 C
Solar/Wind Harmer
0.561
20674928WA_W3-044
Solar/Wind Harmer
0.528
964851AG1-348 GEN
Solar/Wind Harmer
1.927
20634528N27_Y2-018
Solar/Wind Harmer
0.295
20465127PORT CT
Adder
4.362
20674128FR_U2-059
Solar/Wind Harmer
0.202
966111AG1-480 GEN
Solar/Wind Harmer
0.094
966111AG1-480 GEN
Solar/Wind Harmer
3.596
211065PSPA IPP
Solar/Wind Harmer
0.489
211065PSPA IPP
Solar/Wind Harmer
0.489
208972BECR K09
Solar/Wind Harmer
1.103
961541AF2-445A GEN
Solar/Wind Harmer
3.37
209029WAYMART-WD
Solar/Wind Harmer
2.989
209009PEIP 2
Adder
8.117
209010PEIP 1
Adder
3.678
20742028HF_AC1-207
Solar/Wind Harmer
0.869
217197RE CRAN C
Solar/Wind Harmer
0.594
20635828PARLN1&2
Adder
8.185
20635028RRCT1&2
Adder
12.829
20635128RRCT3&4
Adder
12.384
218428ETC SOLAR C
Solar/Wind Harmer
0.04
217213AMBOY SO C
Solar/Wind Harmer
0.14
972275AH1-722 GEN
Adder
34.852
207528AF2-192 GEN
Solar/Wind Harmer
0.611
20673628F1S_V4-069
Solar/Wind Harmer
0.198
20675428EAM_W2-061
Solar/Wind Harmer
0.208
218449LINSOLAR C
Solar/Wind Harmer
1.11
20676428JCR_X2-075
Solar/Wind Harmer
0.377
217209CENTRL HS C
Solar/Wind Harmer
0.049
217121ECCF
Adder
0.478
217083KRNY_132
Adder
10.239
217208PARK ELE C
Solar/Wind Harmer
0.028
207439AE1-081 C O1
Solar/Wind Harmer
0.066
20674328GAR_V4-001
Solar/Wind Harmer
0.121
20675828AU_W4-064
Solar/Wind Harmer
0.19
971519AH1-257 GEN
Solar/Wind Harmer
2.764
207518AF1-320_GEN
Solar/Wind Harmer
4.006
207437AD2-070 GEN
Solar/Wind Harmer
0.33
20465127PORT CT
Adder
3.287
20671928W4-073
Solar/Wind Harmer
0.474
966181AG1-487 GEN
Solar/Wind Harmer
4.097
208909MACR G3
Adder
174.135
961301AF2-421 GEN
Solar/Wind Harmer
1.056
963151AG1-164 GEN
Solar/Wind Harmer
1.056
209023WIENIPP1
Adder
11.387
209025WIENIPP3
Adder
5.684
212266LOR1
Solar/Wind Harmer
0.135
970237AG2-161 GEN
Solar/Wind Harmer
3.604
209010PEIP 1
Adder
0.669
205941AD2-115 GEN
Solar/Wind Harmer
0.944
961341AF2-425 GEN
Solar/Wind Harmer
1.02
212174INGE
Adder
1.128
212507AE2-042_GEN
Solar/Wind Harmer
3.005
946731AF1-337 GEN
Solar/Wind Harmer
0.997
209071AE2-133 GEN
Solar/Wind Harmer
1.685
970665AG2-430 GEN
Solar/Wind Harmer
9.872
209018SUNBIPCT
Adder
7.411
209010PEIP 1
Adder
0.539
961431AF2-434 GEN
Solar/Wind Harmer
1.018
209054AE2-059 GEN
Solar/Wind Harmer
1.696
209059AE2-084 GEN
Solar/Wind Harmer
2.504
946751AF1-339 GEN
Solar/Wind Harmer
0.997
209130AF1-271A GEN
Solar/Wind Harmer
2.797
20465527S.RDG CT
Adder
2.656
20478527GLRA_Q45
Adder
0.306
209137AF2-361 C
Solar/Wind Harmer
2.581
238175AF1-290_GEN
Solar/Wind Helper
0.159
315651AD1-115 GEN
Solar/Wind Helper
1.008
316447AC1-158 HLD
Solar/Wind Helper
3.663
238169AE2-226 GEN1
Solar/Wind Helper
0.724
238170AE2-226 GEN2
Solar/Wind Helper
0.724
966001AG1-469 GEN
Solar/Wind Helper
0.31
316468AD1-105 GEN
Solar/Wind Helper
1.422
316077AC2-138 C
Solar/Wind Helper
0.266
966871AG1-558 GEN
Solar/Wind Helper
0.381
316487AF1-042 GEN
Solar/Wind Helper
0.285
316075AC2-137 C
Solar/Wind Helper
0.427
3143526WINTERP
Solar/Wind Helper
1.455
3142946ENON
Solar/Wind Helper
0.028
316240AF1-291 C
Solar/Wind Helper
0.372
316033AB2-134 GEN
Solar/Wind Helper
0.951
315697AD1-025 GEN
Solar/Wind Helper
3.159
316236AE1-162_GEN
Solar/Wind Helper
0.369
316036AC1-147 C
Solar/Wind Helper
0.417
316316AC1-027 C
Solar/Wind Helper
0.432
3142956BIRDNECK
Solar/Wind Helper
0.184
316185AD1-033 GEN
Solar/Wind Helper
1.287
3145506HICKORY
Solar/Wind Helper
1.094
3145506HICKORY
Solar/Wind Helper
0.656
3145506HICKORY
Solar/Wind Helper
0.164
316339AD2-160 GEN
Solar/Wind Helper
1.04
316018AA1-139 ULT2
Solar/Wind Helper
1.174
316017AA1-139 ULT1
Solar/Wind Helper
1.248
235020AA1-095 C
Solar/Wind Helper
0.051
3137176SLIGO L2192
Solar/Wind Helper
1.086
3130086AYDLETT
Solar/Wind Helper
1.091
23777901MDS_W4-102
Solar/Wind Helper
0.171
3146386ELIZ CT
Solar/Wind Helper
0.272
316431W1029_GEN1
Solar/Wind Helper
1.095
316433W1029_GEN2
Solar/Wind Helper
1.095
3146516WINFALL
Solar/Wind Helper
0.271
3146516WINFALL
Solar/Wind Helper
0.271
3146516WINFALL
Solar/Wind Helper
0.271
3146626S HERTFORD
Solar/Wind Helper
0.27
3146626S HERTFORD
Solar/Wind Helper
0.27
3144356SAPONY
Solar/Wind Helper
0.485
315742AE1-103 GEN
Solar/Wind Helper
0.434
3132123MT JACKSON
Solar/Wind Helper
0.837
3146776BUCKING
Solar/Wind Helper
1.063
3146776BUCKING
Solar/Wind Helper
0.086
3145893MURPHYS
Solar/Wind Helper
0.379
3145893MURPHYS
Solar/Wind Helper
0.476
3146173TUNIS
Solar/Wind Helper
0.264
3146173TUNIS
Solar/Wind Helper
0.264
315821AE2-092 GEN
Solar/Wind Helper
2.44
316181AB2-040 GEN
Solar/Wind Helper
1.88
3147133PAMPLIN
Solar/Wind Helper
0.262
3147133PAMPLIN
Solar/Wind Helper
0.209
3142666NORTHAMPTON
Solar/Wind Helper
0.262
3142666NORTHAMPTON
Solar/Wind Helper
0.262
3142666NORTHAMPTON
Solar/Wind Helper
0.262
3142666NORTHAMPTON
Solar/Wind Helper
0.157
316426AA2-053 GEN
Solar/Wind Helper
1.491
3145593CAROLNA
Solar/Wind Helper
0.261
3145593CAROLNA
Solar/Wind Helper
0.261
3145796HORNRTN
Solar/Wind Helper
0.78
316034AC1-036 C
Solar/Wind Helper
0.272
3145933PARMELE
Solar/Wind Helper
0.516
3145933PARMELE
Solar/Wind Helper
0.258
316274AC1-208 GEN
Solar/Wind Helper
1.572
226929AD2-058 GEN
Solar/Wind Helper
0.099
3146843MT LREL
Solar/Wind Helper
0.254
3146843MT LREL
Solar/Wind Helper
0.254
237034AC2-136 C
Solar/Wind Helper
0.207
316222AC1-221 GEN
Solar/Wind Helper
1.392
316197AC1-042 GEN
Solar/Wind Helper
0.216
270013AE1-250 PV
Solar/Wind Helper
0.848
237002AB1-128_GEN
Solar/Wind Helper
0.364
20467927PC_Q59Y356
Adder
0.843
20465527S.RDG CT
Adder
2.745
972241AH1-705 GEN
Adder
5.664
209008PAXT IPP
Adder
1.83
970679AG2-439 GEN
Solar/Wind Harmer
1.162
200917MEHOOPANY_G
Solar/Wind Harmer
3.659
205967AE2-211_GEN
Solar/Wind Harmer
5.849
972271AH1-720 GEN
Adder
6.121
941421AE2-139 GEN
Solar/Wind Harmer
2.75
20328326MANOR_T86
Adder
0.126
316006AB2-029 C
Solar/Wind Helper
0.146
316045AC1-158 PL2
Solar/Wind Helper
5.328
316254AC1-120 GEN1
Solar/Wind Helper
1.371
3147666LOUISA
Solar/Wind Helper
1.164
316192AB2-158 GEN
Solar/Wind Helper
1.953
238148AE2-230_GEN2
Solar/Wind Helper
0.494
316337AD2-073 GEN
Solar/Wind Helper
0.431
964211AG1-282 GEN
Solar/Wind Helper
0.381
3141726DUNNSVL
Solar/Wind Helper
1.13
3142416OLDCHRC
Solar/Wind Helper
0.731
3142416OLDCHRC
Solar/Wind Helper
0.28
3138133OCRAN
Solar/Wind Helper
0.168
3141766HARMONY
Solar/Wind Helper
0.056
3143526WINTERP
Solar/Wind Helper
1.455
3142433PROV 92
Solar/Wind Helper
1.119
3143226MDLTHAN
Solar/Wind Helper
0.28
3142543TWELFTH
Solar/Wind Helper
0.027
316159AE1-175 C
Solar/Wind Helper
0.421
316458AB2-190 GEN2
Solar/Wind Helper
1.582
3145336SMITFLD
Solar/Wind Helper
1.1
316294AC1-161 GEN
Solar/Wind Helper
5.025
316381AD1-082 GEN
Solar/Wind Helper
1.421
316375AC2-012 GEN
Solar/Wind Helper
0.718
316072AD1-144
Solar/Wind Helper
0.313
316336AC2-165 C
Solar/Wind Helper
1.474
316388AE2-253 GEN
Solar/Wind Helper
1.04
3146456SLIGO L269
Solar/Wind Helper
0.273
316246AF1-032 C
Solar/Wind Helper
0.312
3146516WINFALL
Solar/Wind Helper
0.878
3146516WINFALL
Solar/Wind Helper
0.271
315800Z1-036_GEN1
Solar/Wind Helper
1.483
3130156CHOWAN
Solar/Wind Helper
0.269
3145663CRESWEL
Solar/Wind Helper
0.747
316322AB2-045
Solar/Wind Helper
0.296
3146776BUCKING
Solar/Wind Helper
0.106
3146926FARMVIL
Solar/Wind Helper
0.159
316023GEN1_S
Solar/Wind Helper
1.007
3146206CASHIE
Solar/Wind Helper
0.264
3145893MURPHYS
Solar/Wind Helper
1.057
316097T157 G90
Solar/Wind Helper
1.213
3147983MERCK5
Solar/Wind Helper
0.105
3146173TUNIS
Solar/Wind Helper
0.264
3145683EARLEYS
Solar/Wind Helper
0.263
3146263WOODLND
Solar/Wind Helper
0.262
3145963POPLR C
Solar/Wind Helper
0.261
316190AA2-174 GEN
Solar/Wind Helper
0.017
316011AB1-132 GEN
Solar/Wind Helper
2.812
3145823KELFORD
Solar/Wind Helper
0.261
316174AB2-169 GEN
Solar/Wind Helper
0.664
3145783HORNRTN
Solar/Wind Helper
0.261
3145796HORNRTN
Solar/Wind Helper
0.858
3145796HORNRTN
Solar/Wind Helper
0.26
316129AC1-054 GEN
Solar/Wind Helper
1.28
316212AC1-099_GEN
Solar/Wind Helper
1.159
316237AB2-079_GEN
Solar/Wind Helper
0.346
3145746EVERETS
Solar/Wind Helper
0.257
3145746EVERETS
Solar/Wind Helper
0.257
315687AD1-152 GEN
Solar/Wind Helper
1.378
315722AD1-056 GEN
Solar/Wind Helper
1.378
316494AC1-189 GEN
Solar/Wind Helper
1.56
3146233WITAKRS
Solar/Wind Helper
1.013
961671AG1-007 GEN
Solar/Wind Helper
0.183
3146083TARBORO
Solar/Wind Helper
0.254
316359AB2-059 GEN
Solar/Wind Helper
1.928
316049AB1-081 GEN
Solar/Wind Helper
1.542
3145543BTLEBRO
Solar/Wind Helper
0.253
3145543BTLEBRO
Solar/Wind Helper
0.203
316003AC1-222 GEN
Solar/Wind Helper
1.079
237080AD1-060 GEN
Solar/Wind Helper
0.298
964991AG1-363 GEN
Solar/Wind Helper
3.518
237038AE2-054 C
Solar/Wind Helper
0.23
3147123OTTER R
Solar/Wind Helper
0.139
3147312GRETNA
Solar/Wind Helper
0.184
3146802CHATHAM
Solar/Wind Helper
0.172
270016AE1-250 BESS
Solar/Wind Helper
0.848
270173AC1-122 GEN
Solar/Wind Helper
1.458
232813VAUGHN
Adder
0.769
231906DC3 NUG
Adder
18.164
231902DC CT7
Adder
14.521
231907DC10
Adder
4.535
233968AD2-076_GEN
Solar/Wind Harmer
8.607
970597AG2-380 GEN
Solar/Wind Harmer
5.405
232436AB1-176 C
Solar/Wind Harmer
0.297
971983AH1-536 GEN
Solar/Wind Harmer
9.686
233935AB2-179 C
Solar/Wind Harmer
3.19
231919CHRIST1
Adder
5.606
231920CHRIST2
Adder
5.482
970453AG2-297 GEN
Solar/Wind Harmer
3.19
228260V4-054C
Solar/Wind Harmer
1.182
228309CCLP NUG
Adder
29.743
228309CCLP NUG
Adder
28.292
972141AH1-641 GEN
Solar/Wind Harmer
3.309
964001AG1-254 GEN
Solar/Wind Harmer
2.337
971011AG2-627 GEN
Solar/Wind Harmer
8.797
971535AH1-265 GEN
Solar/Wind Harmer
4.887
227927V4-067C
Solar/Wind Harmer
0.228
228754AB1-001 C
Solar/Wind Harmer
0.16
219137THOSOLAR C
Solar/Wind Harmer
1.375
219272CLEANLIGHT C
Solar/Wind Harmer
0.207
219688LUMSOLAR_S C
Solar/Wind Harmer
0.229
219914AD2-027 C
Solar/Wind Harmer
0.679
213942SCHUYLKILL
Adder
4.006
213942SCHUYLKILL
Adder
3.064
213957STHWK3-4
Adder
3.063
213957STHWK3-4
Adder
3.063
213561DLWR9-10
Adder
3.994
213561DLWR9-10
Adder
3.055
219607WPEMNERT C
Solar/Wind Harmer
0.47
219224BRL12CT4
Adder
10.013
214067T20SOLAR
Solar/Wind Harmer
0.282
213611FALLS1-3
Adder
3.948
213611FALLS1-3
Adder
3.948
20717128DIX_Z2-102
Solar/Wind Harmer
1.471
20715728PEM_W1-119
Solar/Wind Harmer
0.596
20715828PEM_W1-120
Solar/Wind Harmer
0.596
970025AG2-016 GEN
Solar/Wind Harmer
3.154
971189AH1-054 GEN
Solar/Wind Harmer
1.313
207459AE1-142 C O1
Solar/Wind Harmer
1.174
219620RIDERU C
Solar/Wind Harmer
0.062
20714328BYD_X4-031
Solar/Wind Harmer
0.313
20714428HOW_X1-037
Solar/Wind Harmer
1.37
971521AH1-258 GEN
Solar/Wind Harmer
2.998
20720428HOL_W1-112
Solar/Wind Harmer
0.383
20635928PARLN3&4
Adder
8.185
218455CINNBAY_CGEN
Adder
2.009
218526CNTRALGAS2 C
Solar/Wind Harmer
0.41
218524CNTRALGAS1 C
Solar/Wind Harmer
0.409
20675528CPH_W2-050
Solar/Wind Harmer
0.516
218404KENILWRTH C
Adder
1.438
217167KRNY_14
Adder
10.239
217086KRNY_131
Adder
10.152
217147KRNY_1212
Adder
9.739
217147KRNY_1212
Adder
9.565
217146KRNY_1234
Adder
9.543
217146KRNY_1234
Adder
9.478
966261AG1-495 GEN
Solar/Wind Harmer
1.972
20676328BVR_Y1-020
Solar/Wind Harmer
0.363
207511W3-106 GEN
Solar/Wind Harmer
0.721
207530AG1-191 GEN
Solar/Wind Harmer
1.51
20674828DL_W4-046
Solar/Wind Harmer
0.708
971009AG2-626 GEN
Solar/Wind Harmer
1.796
207408W3-077 C
Solar/Wind Harmer
0.555
20675728RH_W2-091
Solar/Wind Harmer
0.375
20675928HOL_W4-097
Solar/Wind Harmer
0.143
207484AF2-139 C O1
Solar/Wind Harmer
0.554
20675128HRM_W1-127
Solar/Wind Harmer
0.186
966421AG1-511 GEN
Solar/Wind Harmer
9.417
20462827N BANGR8
Adder
0.784
209116AE2-175 GEN
Solar/Wind Harmer
4.475
961261AF2-417 GEN
Solar/Wind Harmer
1.059
209026WIENIPP4
Adder
5.626
209045AE2-271 GEN
Solar/Wind Harmer
17.016
959431AF2-234 GEN
Solar/Wind Harmer
1.99
964051AG1-259 GEN
Solar/Wind Harmer
1.334
964061AG1-260 GEN
Solar/Wind Harmer
1.334
959421AF2-233 GEN
Solar/Wind Harmer
0.995
20486527WR_V4-052
Adder
1.071
208862AG1-362 C
Solar/Wind Harmer
0.777
20390726Y2-042
Adder
2.78
20334726NME_Y1-047
Adder
2.458
205951AE1-129_GEN
Solar/Wind Harmer
7.694
203926AA2-133 GEN
Adder
2.27
3138216PACIFIC
Solar/Wind Helper
0.055
316411AF1-147_GEN1
Solar/Wind Helper
1.093
316415AF1-147_GEN2
Solar/Wind Helper
1.093
3141426STAFORD
Solar/Wind Helper
0.066
316164AC1-076 GEN
Solar/Wind Helper
1.422
238152AF2-075_GEN
Solar/Wind Helper
0.703
316223AC1-118
Solar/Wind Helper
0.435
23546401DTGZ2-030
Solar/Wind Helper
0.089
3141813NORNECK
Solar/Wind Helper
0.283
316312AB1-027
Solar/Wind Helper
0.535
3141783LANCAST
Solar/Wind Helper
0.168
3141783LANCAST
Solar/Wind Helper
0.112
3138133OCRAN
Solar/Wind Helper
0.084
3141913WHIT STONE
Solar/Wind Helper
0.28
316059AD1-063 C
Solar/Wind Helper
0.282
3143873LANEXA
Solar/Wind Helper
0.168
315662AE1-191 GEN
Solar/Wind Helper
1.504
315666AE1-190 GEN
Solar/Wind Helper
0.376
957601AF2-054 GEN
Solar/Wind Helper
0.375
3141873WAN 176
Solar/Wind Helper
0.056
316233AE1-074 FULL
Solar/Wind Helper
0.427
957831AF2-077 GEN
Solar/Wind Helper
0.375
316132AB2-190 GEN1
Solar/Wind Helper
1.582
316369SG1_INVT
Solar/Wind Helper
1.329
3143316POE
Solar/Wind Helper
1.088
316349AD2-085 GEN
Solar/Wind Helper
1.249
319010AE1-072 C
Solar/Wind Helper
3.118
316305AF2-043 C
Solar/Wind Helper
0.367
313526AB2-022
Solar/Wind Helper
0.414
3146486SUNBURY
Solar/Wind Helper
0.272
3146486SUNBURY
Solar/Wind Helper
0.272
316321Z2-027
Solar/Wind Helper
0.414
3145176PASQUOTANK
Solar/Wind Helper
0.168
316315AB2-025 C
Solar/Wind Helper
0.412
315611Z1-036_GEN2
Solar/Wind Helper
1.483
3130156CHOWAN
Solar/Wind Helper
0.269
3130156CHOWAN
Solar/Wind Helper
0.269
315816AE2-034 GEN
Solar/Wind Helper
1.219
3138266HYDRAULIC
Solar/Wind Helper
0.012
3138266HYDRAULIC
Solar/Wind Helper
0.008
3130546PLYMOUTH
Solar/Wind Helper
0.265
315732AD1-074 GEN1
Solar/Wind Helper
3.03
315733AD1-074 GEN2
Solar/Wind Helper
3.03
315735AD1-075 GEN1
Solar/Wind Helper
1.514
3146206CASHIE
Solar/Wind Helper
0.264
3145893MURPHYS
Solar/Wind Helper
0.713
3145893MURPHYS
Solar/Wind Helper
0.264
3145513AHOSKIE
Solar/Wind Helper
0.118
961941AG1-037 GEN
Solar/Wind Helper
0.089
3145513AHOSKIE
Solar/Wind Helper
0.263
946281AF1-292 GEN
Solar/Wind Helper
0.264
3146043SEABORD
Solar/Wind Helper
0.263
3145683EARLEYS
Solar/Wind Helper
0.525
3145683EARLEYS
Solar/Wind Helper
0.263
3145683EARLEYS
Solar/Wind Helper
0.263
315607AA1-063A GEN
Solar/Wind Helper
1.498
316087AB2-174 GEN
Solar/Wind Helper
1.835
3137643SOCKMAN
Solar/Wind Helper
1.045
3148133STUARTS
Solar/Wind Helper
0.156
3148013FISHERV
Solar/Wind Helper
0.15
3145796HORNRTN
Solar/Wind Helper
0.832
3145796HORNRTN
Solar/Wind Helper
0.104
3144303KENBRDG
Solar/Wind Helper
0.208
3146033SCOT NK
Solar/Wind Helper
1.039
316239AB2-077_GEN
Solar/Wind Helper
0.346
316238AB2-078_GEN
Solar/Wind Helper
0.346
316005AA1-067
Solar/Wind Helper
0.293
3145746EVERETS
Solar/Wind Helper
1.021
3145746EVERETS
Solar/Wind Helper
0.257
3145746EVERETS
Solar/Wind Helper
0.257
3145746EVERETS
Solar/Wind Helper
0.257
270494AE1-108_GEN
Solar/Wind Helper
3.42
316420AA1-050 GEN
Solar/Wind Helper
1.461
3145573BETHELC
Solar/Wind Helper
0.254
3145573BETHELC
Solar/Wind Helper
0.254
238208AF1-136 C
Solar/Wind Helper
0.196
238109AE1-109 GEN2
Solar/Wind Helper
0.094
238110AE1-109 GEN3
Solar/Wind Helper
0.094
316118AC1-105 GEN
Solar/Wind Helper
0.98
3148463FAIRFLD
Solar/Wind Helper
0.252
3147173SINAI
Solar/Wind Helper
0.251
3147243WELCO
Solar/Wind Helper
0.157
316123AC1-075 GEN
Solar/Wind Helper
1.472
270455AD2-022 GEN
Solar/Wind Helper
1.379
270457AD2-023 GEN
Solar/Wind Helper
0.909
237085AD2-009_GEN
Solar/Wind Helper
1.36
315839AE2-212 C
Solar/Wind Helper
0.371
3145336SMITFLD
Solar/Wind Helper
0.11
315773AC2-141 GEN
Solar/Wind Helper
5.914
316313AB2-026
Solar/Wind Helper
0.418
316258AE1-075 C
Solar/Wind Helper
0.377
316405AF2-144 C
Solar/Wind Helper
0.314
3144536CHRHLND
Solar/Wind Helper
0.041
3144873MCLAUGH
Solar/Wind Helper
0.007
3146456SLIGO L269
Solar/Wind Helper
0.273
316320Y1-086
Solar/Wind Helper
0.121
316435W1029_GEN3
Solar/Wind Helper
1.095
3146516WINFALL
Solar/Wind Helper
0.271
3146626S HERTFORD
Solar/Wind Helper
0.27
3145273HOLLAND
Solar/Wind Helper
0.203
3146376EDENTON
Solar/Wind Helper
0.269
315614AA2-178 GEN
Solar/Wind Helper
1.625
3146776BUCKING
Solar/Wind Helper
0.096
315737AD1-076 GEN
Solar/Wind Helper
2.591
3146926FARMVIL
Solar/Wind Helper
0.159
316365GEN2_N
Solar/Wind Helper
1.007
3146206CASHIE
Solar/Wind Helper
0.264
3145893MURPHYS
Solar/Wind Helper
0.095
3145893MURPHYS
Solar/Wind Helper
0.264
316095T157 G97
Solar/Wind Helper
1.213
3146173TUNIS
Solar/Wind Helper
0.264
3156021HOLLOMANSOL
Solar/Wind Helper
2.003
316463AE2-346 GEN
Solar/Wind Helper
0.24
316140AB2-099
Solar/Wind Helper
0.1
942461AE2-259 GEN
Solar/Wind Helper
1.773
966621AG1-532 GEN
Solar/Wind Helper
0.239
316499AE2-029_GEN
Solar/Wind Helper
0.884
3146263WOODLND
Solar/Wind Helper
0.262
313506AB2-031 GEN
Solar/Wind Helper
1.19
3147133PAMPLIN
Solar/Wind Helper
0.822
3142666NORTHAMPTON
Solar/Wind Helper
0.262
3147043LAWRENC
Solar/Wind Helper
0.157
3145963POPLR C
Solar/Wind Helper
0.261
316317KELFORD C
Solar/Wind Helper
0.222
3145823KELFORD
Solar/Wind Helper
0.261
316478AD1-087 GEN
Solar/Wind Helper
1.274
316486AD2-202 GEN
Solar/Wind Helper
0.373
3148013FISHERV
Solar/Wind Helper
0.261
3145796HORNRTN
Solar/Wind Helper
1.04
3145796HORNRTN
Solar/Wind Helper
0.26
315785AD2-033 C
Solar/Wind Helper
3.025
316210AC1-098 GEN
Solar/Wind Helper
2.086
316131AB2-060 GEN
Solar/Wind Helper
1.573
3145933PARMELE
Solar/Wind Helper
0.258
23583801GRNGAP
Solar/Wind Helper
4.413
3145746EVERETS
Solar/Wind Helper
0.257
3145746EVERETS
Solar/Wind Helper
0.257
315724AD1-057 GEN
Solar/Wind Helper
0.758
316327AA2-057 GEN
Solar/Wind Helper
1.459
3146233WITAKRS
Solar/Wind Helper
0.274
3146233WITAKRS
Solar/Wind Helper
0.173
3146073TAR RVR
Solar/Wind Helper
0.254
3146083TARBORO
Solar/Wind Helper
0.254
3138543CONSLDL
Solar/Wind Helper
0.168
238108AE1-109 GEN1
Solar/Wind Helper
0.094
3145543BTLEBRO
Solar/Wind Helper
0.253
3145543BTLEBRO
Solar/Wind Helper
0.253
238221AF1-254 C O1
Solar/Wind Helper
0.248
315616AA1-038_C
Solar/Wind Helper
1.141
316248AF1-058 C
Solar/Wind Helper
0.337
227287AC2-120 GEN
Solar/Wind Helper
0.334
316283AC2-100 C
Solar/Wind Helper
1.3
226910AB2-157 C
Solar/Wind Helper
0.013
235067AD1-061 GEN
Solar/Wind Helper
0.417
3147312GRETNA
Solar/Wind Helper
0.046
270197AD1-017 GEN1
Solar/Wind Helper
1.228
270018AE2-047 C O1
Solar/Wind Helper
0.793
HAMLETPJM->LTFIMP_HAMLET
CLTF
6.009
G-007ALTFEXP_G-007A->PJM
CMTX
56.664
CBM NorthLTFEXP_CBM-N->PJM
CBM
83.355
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
4.584
BlueGrassPJM->LTFIMP_BlueG
CLTF
14.288
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
149.271
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.507
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
21.714

Details for CHAN-01DOUBS 500.0 kV Ckt 1 line l/o PECO_P4_PEACH245_SRT-A/* $ CHESCO $ PECO_P4_PEACH245 $ STBK


Base Case Flowgate

Area:AP/PJM
Facility Description:
CHAN-01DOUBS 500.0 kV Ckt 1 line
Contingency Name:
PECO_P4_PEACH245_SRT-A/* $ CHESCO $ PECO_P4_PEACH245 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.91 %
Rating:4150.0 MVA
Rating Type:B
MVA to Mitigate:4519.67
MW Contribution:8.84
Bus #Bus NameTypeMW Contribution
200035PCHBTM 3
50/50
23.369
200034PCHBTM 2
50/50
22.865
200205Y1-065-CTG2
50/50
4.546
971149AH1-027 GEN
Solar/Wind Harmer
4.461
233939AC1-091 C
Solar/Wind Harmer
1.158
233970AC1-092 C
Solar/Wind Harmer
1.158
970545AG2-347 GEN
Solar/Wind Harmer
86.133
232899W1-062
Adder
12.66
233987AB2-037 GEN
Solar/Wind Harmer
14.981
972069AH1-584 GEN
Solar/Wind Harmer
11.785
972071AH1-585 GEN
Solar/Wind Harmer
11.785
232918OH NUG7
Adder
11.545
971747AH1-380 GEN
Solar/Wind Harmer
4.714
233901CHERRYDALE C
Solar/Wind Harmer
1.482
232408W1-005 C
Solar/Wind Harmer
1.318
232410W1-006 C
Solar/Wind Harmer
1.318
232905CHERITON_25
Adder
3.229
232926CRISFLD1
Adder
2.583
231940T-011
Adder
0.981
233946AB2-136 GEN
Solar/Wind Harmer
5.246
234036AF2-325 C
Solar/Wind Harmer
1.205
234041AC1-190 GEN
Solar/Wind Harmer
11.766
233984AB2-036 GEN
Solar/Wind Harmer
16.276
232424Y1-079 C
Solar/Wind Harmer
0.735
231131BLOOM ENRGY
Adder
5.678
234014AF1-036_GEN
Solar/Wind Harmer
3.527
233944AB2-135 GEN
Solar/Wind Harmer
6.814
233933AB2-153 GEN
Solar/Wind Harmer
1.462
232416X2-083
Adder
0.581
228251CARLLS#4
Adder
0.73
230422AE1-104_GEN1
Solar/Wind Harmer
38.946
230425AE1-104_GEN2
Solar/Wind Harmer
38.946
230433AD2-135 GEN
Solar/Wind Harmer
0.117
230407AD2-065 C
Solar/Wind Harmer
0.152
228307PCLP GT
Adder
13.925
228304LOGAN
Adder
27.827
972233AH1-701 GEN
Adder
4.819
219921AF1-264
Solar/Wind Harmer
0.165
213589EDDYSTN4
Adder
90.452
213587EDDYSTN3
Adder
90.447
219615MILLCREEK C
Solar/Wind Harmer
0.269
213815MOSER1-3
Adder
4.002
213815MOSER1-3
Adder
4.002
213535CROYDN11
Adder
11.524
20716428NHV_W2-082
Solar/Wind Harmer
1.991
207500AE2-000G1
Solar/Wind Harmer
35.254
207497AE2-000G2
Solar/Wind Harmer
35.254
207507AE2-000G3
Solar/Wind Harmer
35.254
20636128O CRK C2
Adder
7.212
963401AG1-189 GEN
Solar/Wind Harmer
1.287
963391AG1-188 GEN
Solar/Wind Harmer
2.145
20714928UPF_X1-085
Solar/Wind Harmer
0.455
20628028LAKEHURS
Adder
1.063
219114HARTZY_C
Solar/Wind Harmer
0.932
219817TRENTONSOL C
Solar/Wind Harmer
1.229
20641628MLH_W1-032
Solar/Wind Harmer
0.327
200052ROCKSP 1
50/50
2.871
200053ROCKSP 2
50/50
2.81
233973AC2-185 C
Solar/Wind Harmer
4.762
234033AF1-007_GEN
Solar/Wind Harmer
30.779
232904IR4
Adder
106.425
232920IR10
Adder
4.16
232432Z2-076 GEN
Solar/Wind Harmer
0.174
232912OH NUG1
Adder
11.623
232913OH NUG2
Adder
11.468
233923SMA
Solar/Wind Harmer
6.111
233990AG1-397 GEN
Solar/Wind Harmer
0.073
233955AB2-172 GEN
Solar/Wind Harmer
6.571
232813VAUGHN
Adder
0.772
231906DC3 NUG
Adder
18.238
231902DC CT7
Adder
14.58
231907DC10
Adder
4.553
233968AD2-076_GEN
Solar/Wind Harmer
8.642
970597AG2-380 GEN
Solar/Wind Harmer
5.427
232436AB1-176 C
Solar/Wind Harmer
0.299
971983AH1-536 GEN
Solar/Wind Harmer
9.725
233935AB2-179 C
Solar/Wind Harmer
3.202
231919CHRIST1
Adder
5.629
231920CHRIST2
Adder
5.504
970453AG2-297 GEN
Solar/Wind Harmer
3.204
228260V4-054C
Solar/Wind Harmer
1.188
228309CCLP NUG
Adder
29.877
228309CCLP NUG
Adder
28.42
972141AH1-641 GEN
Solar/Wind Harmer
3.324
964001AG1-254 GEN
Solar/Wind Harmer
2.348
971011AG2-627 GEN
Solar/Wind Harmer
8.837
971535AH1-265 GEN
Solar/Wind Harmer
4.909
227927V4-067C
Solar/Wind Harmer
0.229
228754AB1-001 C
Solar/Wind Harmer
0.161
219137THOSOLAR C
Solar/Wind Harmer
1.381
219272CLEANLIGHT C
Solar/Wind Harmer
0.208
219688LUMSOLAR_S C
Solar/Wind Harmer
0.23
219914AD2-027 C
Solar/Wind Harmer
0.682
213942SCHUYLKILL
Adder
4.023
213942SCHUYLKILL
Adder
3.077
213957STHWK3-4
Adder
3.076
200204Y1-065-CTG1
50/50
4.546
200054ROCKSP 3
50/50
2.9
232901NORTHST
Adder
10.97
233972AC1-094 C
Solar/Wind Harmer
0.874
232900DEMECSMY
Adder
12.144
232434Z2-077 GEN
Solar/Wind Harmer
0.33
972177AH1-672 GEN
Solar/Wind Harmer
17.68
232917OH NUG6
Adder
11.571
232915OH NUG4
Adder
11.545
232404W1-003 C
Solar/Wind Harmer
1.318
233998TM1NIN_3.36
Solar/Wind Harmer
1.667
971195AH1-057 GEN
Solar/Wind Harmer
1.44
232428Y3-058 C
Solar/Wind Harmer
1.098
232919VN10
Adder
3.691
965821AG1-450 GEN
Solar/Wind Harmer
6.845
232426Y1-080 FULL
Solar/Wind Harmer
0.251
970277AG2-181 GEN
Solar/Wind Harmer
6.593
233964AF2-378 GEN
Solar/Wind Harmer
0.168
233954AC2-188 GEN
Solar/Wind Harmer
1.48
233950AC2-186 GEN
Solar/Wind Harmer
0.74
232910NRG_G1
Adder
11.31
234012AE2-112_GEN
Solar/Wind Harmer
2.998
232422X3-066 FULL
Solar/Wind Harmer
0.326
233930AB2-032 GEN
Solar/Wind Harmer
1.084
233915AB1-141 GEN
Solar/Wind Harmer
1.288
231918WEST 1
Adder
4.278
231917EM10
Adder
2.99
228206SHRMN CT
Adder
19.223
228732V1-021 C
Adder
0.219
945431AF1-208 GEN
Solar/Wind Harmer
9.984
970997AG2-616 GEN
Solar/Wind Harmer
11.08
228351V2-046C
Solar/Wind Harmer
2.326
230511AF1-262
Solar/Wind Harmer
0.211
228728W1-130C
Solar/Wind Harmer
0.766
230434AG1-499 GEN
Solar/Wind Harmer
0.668
219258KINSLEYDEP C
Solar/Wind Harmer
0.369
218660EHAMPSOLAR C
Solar/Wind Harmer
0.199
213497CHSTR7-9
Adder
3.098
213497CHSTR7-9
Adder
3.098
219904AC1-010 C
Solar/Wind Harmer
0.43
219686LUMSOLAR_N C
Solar/Wind Harmer
0.23
219287REEVESEAST C
Solar/Wind Harmer
1.529
219907AC1-030 C
Solar/Wind Harmer
0.157
213958STHWK5-6
Adder
3.076
213560DLW11-12
Adder
3.068
219304NAMERICA C
Solar/Wind Harmer
0.35
219222BRL12CT2
Adder
10.06
213611FALLS1-3
Adder
3.967
214194N WALES4
Adder
0.956
20720728JCB_W1-129
Solar/Wind Harmer
0.334
207522AF2-254 C
Solar/Wind Harmer
1.607
207487AE2-000G4
Solar/Wind Harmer
35.254
207445AB1-138_GEN
Solar/Wind Harmer
0.648
20628028LAKEHURS
Adder
2.103
963711AG1-223 GEN
Solar/Wind Harmer
1.651
20714828MDF_W3-079
Solar/Wind Harmer
0.342
219680HOPEWELLV C1
Solar/Wind Harmer
0.085
207454AA2-184 E
Solar/Wind Harmer
1.114
20715228NPK_W1-113
Solar/Wind Harmer
0.479
20742028HF_AC1-207
Solar/Wind Harmer
0.873
217197RE CRAN C
Solar/Wind Harmer
0.597
20635828PARLN1&2
Adder
8.228
20635028RRCT1&2
Adder
12.896
20635128RRCT3&4
Adder
12.448
218428ETC SOLAR C
Solar/Wind Harmer
0.04
217213AMBOY SO C
Solar/Wind Harmer
0.141
972275AH1-722 GEN
Adder
35.036
207528AF2-192 GEN
Solar/Wind Harmer
0.614
20673628F1S_V4-069
Solar/Wind Harmer
0.199
20675428EAM_W2-061
Solar/Wind Harmer
0.21
218449LINSOLAR C
Solar/Wind Harmer
1.115
20676428JCR_X2-075
Solar/Wind Harmer
0.379
217209CENTRL HS C
Solar/Wind Harmer
0.049
217121ECCF
Adder
0.481
217083KRNY_132
Adder
10.294
217208PARK ELE C
Solar/Wind Harmer
0.028
207439AE1-081 C O1
Solar/Wind Harmer
0.066
20674328GAR_V4-001
Solar/Wind Harmer
0.122
20675828AU_W4-064
Solar/Wind Harmer
0.191
971519AH1-257 GEN
Solar/Wind Harmer
2.779
207518AF1-320_GEN
Solar/Wind Harmer
4.029
207437AD2-070 GEN
Solar/Wind Harmer
0.332
20465127PORT CT
Adder
3.305
20671928W4-073
Solar/Wind Harmer
0.476
966181AG1-487 GEN
Solar/Wind Harmer
4.12
208909MACR G3
Adder
175.148
961301AF2-421 GEN
Solar/Wind Harmer
1.063
963151AG1-164 GEN
Solar/Wind Harmer
1.063
209023WIENIPP1
Adder
11.465
209025WIENIPP3
Adder
5.723
212266LOR1
Solar/Wind Harmer
0.136
970237AG2-161 GEN
Solar/Wind Harmer
3.63
209010PEIP 1
Adder
0.674
961341AF2-425 GEN
Solar/Wind Harmer
1.028
212174INGE
Adder
1.137
205941AD2-115 GEN
Solar/Wind Harmer
0.948
212507AE2-042_GEN
Solar/Wind Harmer
3.029
946731AF1-337 GEN
Solar/Wind Harmer
1.004
209071AE2-133 GEN
Solar/Wind Harmer
1.698
970665AG2-430 GEN
Solar/Wind Harmer
9.95
209018SUNBIPCT
Adder
7.469
20467927PC_Q59Y356
Adder
0.846
20465527S.RDG CT
Adder
2.755
972241AH1-705 GEN
Adder
5.711
209008PAXT IPP
Adder
1.839
200203Y1-065-STG
50/50
7.882
200055ROCKSP 4
50/50
2.839
233971AC1-093 C
Solar/Wind Harmer
1.034
970695AG2-447 GEN
Solar/Wind Harmer
4.722
972133AH1-634 GEN
Solar/Wind Harmer
13.05
232914OH NUG3
Adder
11.623
232916OH NUG5
Adder
11.623
972073AH1-586 GEN
Solar/Wind Harmer
12.333
232406W1-004 FULL
Solar/Wind Harmer
1.318
970679AG2-439 GEN
Solar/Wind Harmer
1.177
200917MEHOOPANY_G
Solar/Wind Harmer
3.718
205967AE2-211_GEN
Solar/Wind Harmer
5.888
972271AH1-720 GEN
Adder
6.237
941421AE2-139 GEN
Solar/Wind Harmer
2.804
20328326MANOR_T86
Adder
0.129
316006AB2-029 C
Solar/Wind Helper
0.143
316045AC1-158 PL2
Solar/Wind Helper
5.224
316254AC1-120 GEN1
Solar/Wind Helper
1.344
3147666LOUISA
Solar/Wind Helper
1.14
316192AB2-158 GEN
Solar/Wind Helper
1.914
238148AE2-230_GEN2
Solar/Wind Helper
0.484
316337AD2-073 GEN
Solar/Wind Helper
0.422
964211AG1-282 GEN
Solar/Wind Helper
0.373
3141726DUNNSVL
Solar/Wind Helper
1.107
3142416OLDCHRC
Solar/Wind Helper
0.715
3142416OLDCHRC
Solar/Wind Helper
0.274
3138133OCRAN
Solar/Wind Helper
0.165
3141766HARMONY
Solar/Wind Helper
0.055
3143526WINTERP
Solar/Wind Helper
1.424
3142433PROV 92
Solar/Wind Helper
1.095
3143226MDLTHAN
Solar/Wind Helper
0.274
3142543TWELFTH
Solar/Wind Helper
0.026
316159AE1-175 C
Solar/Wind Helper
0.412
316458AB2-190 GEN2
Solar/Wind Helper
1.548
3145336SMITFLD
Solar/Wind Helper
1.076
316294AC1-161 GEN
Solar/Wind Helper
4.916
316381AD1-082 GEN
Solar/Wind Helper
1.39
316375AC2-012 GEN
Solar/Wind Helper
0.702
316072AD1-144
Solar/Wind Helper
0.306
316336AC2-165 C
Solar/Wind Helper
1.442
316388AE2-253 GEN
Solar/Wind Helper
1.018
20720628TIN_W1-124
Solar/Wind Harmer
1.11
20716928W4-060COL
Solar/Wind Harmer
0.791
924131AB2-057 GEN
Solar/Wind Harmer
1.143
218440SUMMTASSOC C
Solar/Wind Harmer
0.142
218418LINDEN_G5
Adder
19.058
218419LINDEN_G6
Adder
19.058
972260AH1-715 GEN1
Adder
15.261
20673828FLE_V3-070
Solar/Wind Harmer
0.508
207442AE1-156 GEN
Solar/Wind Harmer
0.825
20676128MHD_W3-029
Solar/Wind Harmer
0.53
219036LINDEN_G7
Adder
18.547
219035LINDEN_G8
Adder
18.283
972261AH1-715 GEN2
Adder
17.754
217081WEATEXAS C
Solar/Wind Harmer
0.095
217202FBANKSOLAR C
Solar/Wind Harmer
0.081
217201HACKENSOLA C
Solar/Wind Harmer
0.081
972237AH1-703 GEN
Adder
11.205
217206BARNGR HS C
Solar/Wind Harmer
0.034
217086KRNY_131
Adder
10.316
217083KRNY_132
Adder
10.229
20671828STAW2-080
Solar/Wind Harmer
0.116
217204WCALDSOLAR C
Solar/Wind Harmer
0.081
20674528F3S_W2-016
Solar/Wind Harmer
1.556
20676228FRD_X1-012
Solar/Wind Harmer
0.653
207471AF2-354 C
Solar/Wind Harmer
0.564
20674928WA_W3-044
Solar/Wind Harmer
0.531
964851AG1-348 GEN
Solar/Wind Harmer
1.937
20634528N27_Y2-018
Solar/Wind Harmer
0.297
20465127PORT CT
Adder
4.387
20674128FR_U2-059
Solar/Wind Harmer
0.203
966111AG1-480 GEN
Solar/Wind Harmer
0.095
966111AG1-480 GEN
Solar/Wind Harmer
3.618
211065PSPA IPP
Solar/Wind Harmer
0.493
211065PSPA IPP
Solar/Wind Harmer
0.493
208972BECR K09
Solar/Wind Harmer
1.111
961541AF2-445A GEN
Solar/Wind Harmer
3.395
209029WAYMART-WD
Solar/Wind Harmer
3.011
209009PEIP 2
Adder
8.177
209010PEIP 1
Adder
3.705
209010PEIP 1
Adder
0.543
961431AF2-434 GEN
Solar/Wind Harmer
1.025
209054AE2-059 GEN
Solar/Wind Harmer
1.71
209059AE2-084 GEN
Solar/Wind Harmer
2.524
946751AF1-339 GEN
Solar/Wind Harmer
1.004
209130AF1-271A GEN
Solar/Wind Harmer
2.819
20465527S.RDG CT
Adder
2.665
20478527GLRA_Q45
Adder
0.308
209137AF2-361 C
Solar/Wind Harmer
2.606
238175AF1-290_GEN
Solar/Wind Helper
0.156
315651AD1-115 GEN
Solar/Wind Helper
0.988
316447AC1-158 HLD
Solar/Wind Helper
3.592
238169AE2-226 GEN1
Solar/Wind Helper
0.71
238170AE2-226 GEN2
Solar/Wind Helper
0.71
966001AG1-469 GEN
Solar/Wind Helper
0.304
316468AD1-105 GEN
Solar/Wind Helper
1.393
316077AC2-138 C
Solar/Wind Helper
0.261
966871AG1-558 GEN
Solar/Wind Helper
0.373
316487AF1-042 GEN
Solar/Wind Helper
0.279
316075AC2-137 C
Solar/Wind Helper
0.418
3143526WINTERP
Solar/Wind Helper
1.424
3142946ENON
Solar/Wind Helper
0.027
316240AF1-291 C
Solar/Wind Helper
0.365
316033AB2-134 GEN
Solar/Wind Helper
0.93
315697AD1-025 GEN
Solar/Wind Helper
3.091
316236AE1-162_GEN
Solar/Wind Helper
0.362
316036AC1-147 C
Solar/Wind Helper
0.408
3142956BIRDNECK
Solar/Wind Helper
0.18
316316AC1-027 C
Solar/Wind Helper
0.423
316185AD1-033 GEN
Solar/Wind Helper
1.259
3145506HICKORY
Solar/Wind Helper
1.07
3145506HICKORY
Solar/Wind Helper
0.642
3145506HICKORY
Solar/Wind Helper
0.16
316339AD2-160 GEN
Solar/Wind Helper
1.018
235020AA1-095 C
Solar/Wind Helper
0.05
316018AA1-139 ULT2
Solar/Wind Helper
1.149
316017AA1-139 ULT1
Solar/Wind Helper
1.221
3137176SLIGO L2192
Solar/Wind Helper
1.062
3130086AYDLETT
Solar/Wind Helper
1.067
23777901MDS_W4-102
Solar/Wind Helper
0.167
3146386ELIZ CT
Solar/Wind Helper
0.266
316431W1029_GEN1
Solar/Wind Helper
1.071
316433W1029_GEN2
Solar/Wind Helper
1.071
3146516WINFALL
Solar/Wind Helper
0.265
3146516WINFALL
Solar/Wind Helper
0.265
3146516WINFALL
Solar/Wind Helper
0.265
3146626S HERTFORD
Solar/Wind Helper
0.264
3146626S HERTFORD
Solar/Wind Helper
0.264
3144356SAPONY
Solar/Wind Helper
0.474
315742AE1-103 GEN
Solar/Wind Helper
0.424
3132123MT JACKSON
Solar/Wind Helper
0.819
3146776BUCKING
Solar/Wind Helper
1.039
3146776BUCKING
Solar/Wind Helper
0.084
3145893MURPHYS
Solar/Wind Helper
0.371
3145893MURPHYS
Solar/Wind Helper
0.465
3146173TUNIS
Solar/Wind Helper
0.258
3146173TUNIS
Solar/Wind Helper
0.258
315821AE2-092 GEN
Solar/Wind Helper
2.385
316181AB2-040 GEN
Solar/Wind Helper
1.837
3147133PAMPLIN
Solar/Wind Helper
0.256
3147133PAMPLIN
Solar/Wind Helper
0.205
3142666NORTHAMPTON
Solar/Wind Helper
0.256
3142666NORTHAMPTON
Solar/Wind Helper
0.256
3142666NORTHAMPTON
Solar/Wind Helper
0.256
3142666NORTHAMPTON
Solar/Wind Helper
0.153
316426AA2-053 GEN
Solar/Wind Helper
1.457
3145593CAROLNA
Solar/Wind Helper
0.255
3145593CAROLNA
Solar/Wind Helper
0.255
3145796HORNRTN
Solar/Wind Helper
0.762
316034AC1-036 C
Solar/Wind Helper
0.266
3145933PARMELE
Solar/Wind Helper
0.504
3145933PARMELE
Solar/Wind Helper
0.252
316274AC1-208 GEN
Solar/Wind Helper
1.535
226929AD2-058 GEN
Solar/Wind Helper
0.097
3146843MT LREL
Solar/Wind Helper
0.248
3146843MT LREL
Solar/Wind Helper
0.248
237034AC2-136 C
Solar/Wind Helper
0.203
316222AC1-221 GEN
Solar/Wind Helper
1.357
316197AC1-042 GEN
Solar/Wind Helper
0.21
270013AE1-250 PV
Solar/Wind Helper
0.825
232921TASLEY2G
Adder
6.793
233996TM1833_GEN
Solar/Wind Harmer
1.667
233997TMININ_4.2
Solar/Wind Harmer
1.667
233990AG1-397 GEN
Solar/Wind Harmer
1.51
233940AF2-379 C
Solar/Wind Harmer
0.246
234015AF2-250 C
Solar/Wind Harmer
0.158
233900O-025 C
Adder
1.549
233994AC2-023 GEN
Solar/Wind Harmer
3.537
232907VN8
Adder
39.504
960671AF2-358 GEN
Solar/Wind Harmer
23.548
233952AC2-187 GEN
Solar/Wind Harmer
1.48
232417X3-008 C
Solar/Wind Harmer
2.628
972251AH1-710 GEN
Adder
58.277
233918AB1-142 GEN
Solar/Wind Harmer
1.288
233982AB2-133 GEN
Solar/Wind Harmer
6.328
228202CUMB CT
Adder
19.166
228711V2-041C
Solar/Wind Harmer
0.697
971553AH1-274 GEN
Solar/Wind Harmer
2.806
230430AE1-229_GEN
Solar/Wind Harmer
10.167
230415AB2-049 C
Solar/Wind Harmer
0.219
228729W2-030 C
Solar/Wind Harmer
0.666
228304LOGAN
Adder
25.028
219623KINSLEYBEA C
Solar/Wind Harmer
0.488
219291REEVESSOUT C
Solar/Wind Harmer
0.068
213497CHSTR7-9
Adder
3.098
219766PARADISE C
Solar/Wind Harmer
0.358
219912AD2-042 GEN
Solar/Wind Harmer
0.904
219236SOUTHERNHQ C
Solar/Wind Harmer
0.077
213958STHWK5-6
Adder
3.076
213560DLW11-12
Adder
3.068
219906AC1-017 C
Solar/Wind Harmer
0.252
213815MOSER1-3
Adder
4.002
219610FLORENCE C
Solar/Wind Harmer
1.561
219348LDSOLAR C
Solar/Wind Harmer
0.675
219221BRL12CT1
Adder
10.06
219223BRL12CT3
Adder
10.06
20716028EGP_W2-019
Solar/Wind Harmer
0.52
20720828JCB_W4-025
Solar/Wind Harmer
0.508
20715028HAN_X4-015
Solar/Wind Harmer
0.334
959561AF2-247 GEN
Solar/Wind Harmer
0.544
20636028O CRK C1
Adder
7.91
971667AH1-334 GEN
Solar/Wind Harmer
3.071
219727YARDVSOLFA C
Solar/Wind Harmer
1.016
20714528FRN_Y2-051
Solar/Wind Harmer
0.329
219276PARKLANDSO C
Solar/Wind Harmer
0.515
219918AC2-009 C
Solar/Wind Harmer
0.069
20716228APLW2-078
Solar/Wind Harmer
0.984
20720528MAN_W1-024
Solar/Wind Harmer
0.283
967451AG2-055 C O1
Solar/Wind Harmer
193.355
219612MATRIX C
Solar/Wind Harmer
0.205
218438BLK ROCK C
Solar/Wind Harmer
0.152
20635828PARLN1&2
Adder
3.727
20635928PARLN3&4
Adder
3.727
20635028RRCT1&2
Adder
13.097
20635128RRCT3&4
Adder
10.859
219908AB1-139 C
Solar/Wind Harmer
0.423
219919AE1-041 FULL
Solar/Wind Harmer
0.045
219249CENTRALDIV C
Solar/Wind Harmer
0.044
20673728F2S_V4-070
Solar/Wind Harmer
0.199
217211CAMDEN ST C
Solar/Wind Harmer
0.027
217186ESSEX_G9
Adder
17.705
217169METRODIV C
Solar/Wind Harmer
0.044
217194REDH C
Solar/Wind Harmer
0.545
20676728BRNX1-095
Solar/Wind Harmer
0.195
207510AF2-138 C
Solar/Wind Harmer
1.965
20674628WNG_W3-110
Solar/Wind Harmer
0.445
971007AG2-625 GEN
Solar/Wind Harmer
2.832
20466127PORT 5CT
Adder
29.176
20633028GILCT9
Adder
31.132
966181AG1-487 GEN
Solar/Wind Harmer
0.276
20465427SHAW CT
Adder
4.24
963161AG1-165 GEN
Solar/Wind Harmer
1.063
209025WIENIPP3
Adder
5.607
963071AG1-156 GEN
Solar/Wind Harmer
2.914
970095AG2-074 GEN
Solar/Wind Harmer
6.614
209027LOR2_Q27
Solar/Wind Harmer
4.727
209022WHFR IPP
Adder
3.393
961331AF2-424 GEN
Solar/Wind Harmer
1.028
961421AF2-433 GEN
Solar/Wind Harmer
1.025
957921AF2-086 GEN
Solar/Wind Harmer
0.997
209142AF1-226 GEN
Solar/Wind Harmer
5.936
209093AE2-110 GEN
Solar/Wind Harmer
2.564
209120AE2-241 GEN
Solar/Wind Harmer
3.392
972245AH1-707 GEN
Adder
5.528
946691AF1-333 GEN
Solar/Wind Harmer
1.004
946741AF1-338 GEN
Solar/Wind Harmer
1.004
972221AH1-695 GEN
Adder
125.25
209067AE2-060 GEN
Solar/Wind Harmer
1.348
3141196NOKESVL
Solar/Wind Helper
1.237
316044AC1-158 PL1
Solar/Wind Helper
1.632
316450AC1-158 RIC
Solar/Wind Helper
0.435
316170AC1-121 GEN2
Solar/Wind Helper
0.448
3132273ORANGE
Solar/Wind Helper
0.057
3147666LOUISA
Solar/Wind Helper
0.656
966881AG1-559 GEN
Solar/Wind Helper
0.382
238147AE2-230_GEN1
Solar/Wind Helper
0.482
238149AF1-291A_GEN
Solar/Wind Helper
0.138
3141906WESTMOR
Solar/Wind Helper
0.112
316473AC1-191 GEN
Solar/Wind Helper
1.69
237061AD1-155 GEN
Solar/Wind Helper
0.052
316404AE1-155 C
Solar/Wind Helper
2.332
316484AD2-074 GEN
Solar/Wind Helper
0.532
316280AD1-041 GEN
Solar/Wind Helper
0.92
316156AD2-030 GEN
Solar/Wind Helper
0.413
3142946ENON
Solar/Wind Helper
0.091
316382AG1-145 C
Solar/Wind Helper
0.365
315839AE2-212 C
Solar/Wind Helper
0.363
3145336SMITFLD
Solar/Wind Helper
0.108
315773AC2-141 GEN
Solar/Wind Helper
5.786
316313AB2-026
Solar/Wind Helper
0.409
316258AE1-075 C
Solar/Wind Helper
0.368
316405AF2-144 C
Solar/Wind Helper
0.307
3144536CHRHLND
Solar/Wind Helper
0.04
3144873MCLAUGH
Solar/Wind Helper
0.007
3146456SLIGO L269
Solar/Wind Helper
0.267
316320Y1-086
Solar/Wind Helper
0.119
316435W1029_GEN3
Solar/Wind Helper
1.071
3146516WINFALL
Solar/Wind Helper
0.265
3146626S HERTFORD
Solar/Wind Helper
0.264
3145273HOLLAND
Solar/Wind Helper
0.198
3146376EDENTON
Solar/Wind Helper
0.263
315614AA2-178 GEN
Solar/Wind Helper
1.589
3146776BUCKING
Solar/Wind Helper
0.093
315737AD1-076 GEN
Solar/Wind Helper
2.533
3146926FARMVIL
Solar/Wind Helper
0.155
316365GEN2_N
Solar/Wind Helper
0.984
3146206CASHIE
Solar/Wind Helper
0.258
3145893MURPHYS
Solar/Wind Helper
0.093
3145893MURPHYS
Solar/Wind Helper
0.258
3146173TUNIS
Solar/Wind Helper
0.258
316095T157 G97
Solar/Wind Helper
1.185
3156021HOLLOMANSOL
Solar/Wind Helper
1.958
316463AE2-346 GEN
Solar/Wind Helper
0.235
316140AB2-099
Solar/Wind Helper
0.098
942461AE2-259 GEN
Solar/Wind Helper
1.733
966621AG1-532 GEN
Solar/Wind Helper
0.234
316499AE2-029_GEN
Solar/Wind Helper
0.864
3146263WOODLND
Solar/Wind Helper
0.256
313506AB2-031 GEN
Solar/Wind Helper
1.163
3147133PAMPLIN
Solar/Wind Helper
0.803
3142666NORTHAMPTON
Solar/Wind Helper
0.256
3147043LAWRENC
Solar/Wind Helper
0.153
3145963POPLR C
Solar/Wind Helper
0.255
316317KELFORD C
Solar/Wind Helper
0.217
3145823KELFORD
Solar/Wind Helper
0.255
316478AD1-087 GEN
Solar/Wind Helper
1.245
316486AD2-202 GEN
Solar/Wind Helper
0.365
3148013FISHERV
Solar/Wind Helper
0.255
3145796HORNRTN
Solar/Wind Helper
1.016
3145796HORNRTN
Solar/Wind Helper
0.254
315785AD2-033 C
Solar/Wind Helper
2.955
316210AC1-098 GEN
Solar/Wind Helper
2.037
316131AB2-060 GEN
Solar/Wind Helper
1.537
3145933PARMELE
Solar/Wind Helper
0.252
23583801GRNGAP
Solar/Wind Helper
4.309
3145746EVERETS
Solar/Wind Helper
0.251
3145746EVERETS
Solar/Wind Helper
0.251
315724AD1-057 GEN
Solar/Wind Helper
0.74
316327AA2-057 GEN
Solar/Wind Helper
1.425
3146233WITAKRS
Solar/Wind Helper
0.267
3146233WITAKRS
Solar/Wind Helper
0.169
3146073TAR RVR
Solar/Wind Helper
0.248
3146083TARBORO
Solar/Wind Helper
0.248
3138543CONSLDL
Solar/Wind Helper
0.164
3145543BTLEBRO
Solar/Wind Helper
0.247
3145543BTLEBRO
Solar/Wind Helper
0.247
238108AE1-109 GEN1
Solar/Wind Helper
0.092
238221AF1-254 C O1
Solar/Wind Helper
0.242
315616AA1-038_C
Solar/Wind Helper
1.114
316248AF1-058 C
Solar/Wind Helper
0.329
227287AC2-120 GEN
Solar/Wind Helper
0.328
226910AB2-157 C
Solar/Wind Helper
0.013
316283AC2-100 C
Solar/Wind Helper
1.268
235067AD1-061 GEN
Solar/Wind Helper
0.406
3147312GRETNA
Solar/Wind Helper
0.045
213957STHWK3-4
Adder
3.076
213561DLWR9-10
Adder
4.012
213561DLWR9-10
Adder
3.068
219607WPEMNERT C
Solar/Wind Harmer
0.472
219224BRL12CT4
Adder
10.06
214067T20SOLAR
Solar/Wind Harmer
0.284
213611FALLS1-3
Adder
3.967
213611FALLS1-3
Adder
3.967
20717128DIX_Z2-102
Solar/Wind Harmer
1.478
20715728PEM_W1-119
Solar/Wind Harmer
0.599
20715828PEM_W1-120
Solar/Wind Harmer
0.599
970025AG2-016 GEN
Solar/Wind Harmer
3.169
971189AH1-054 GEN
Solar/Wind Harmer
1.32
207459AE1-142 C O1
Solar/Wind Harmer
1.18
219620RIDERU C
Solar/Wind Harmer
0.062
20714328BYD_X4-031
Solar/Wind Harmer
0.315
20714428HOW_X1-037
Solar/Wind Harmer
1.377
971521AH1-258 GEN
Solar/Wind Harmer
3.013
20720428HOL_W1-112
Solar/Wind Harmer
0.385
20635928PARLN3&4
Adder
8.228
218455CINNBAY_CGEN
Adder
2.02
218526CNTRALGAS2 C
Solar/Wind Harmer
0.412
218524CNTRALGAS1 C
Solar/Wind Harmer
0.411
20675528CPH_W2-050
Solar/Wind Harmer
0.519
218404KENILWRTH C
Adder
1.446
217167KRNY_14
Adder
10.294
217086KRNY_131
Adder
10.207
217147KRNY_1212
Adder
9.792
217147KRNY_1212
Adder
9.617
217146KRNY_1234
Adder
9.595
217146KRNY_1234
Adder
9.529
966261AG1-495 GEN
Solar/Wind Harmer
1.983
20676328BVR_Y1-020
Solar/Wind Harmer
0.365
207511W3-106 GEN
Solar/Wind Harmer
0.725
207530AG1-191 GEN
Solar/Wind Harmer
1.519
20674828DL_W4-046
Solar/Wind Harmer
0.712
971009AG2-626 GEN
Solar/Wind Harmer
1.806
207408W3-077 C
Solar/Wind Harmer
0.558
20675728RH_W2-091
Solar/Wind Harmer
0.377
20675928HOL_W4-097
Solar/Wind Harmer
0.144
207484AF2-139 C O1
Solar/Wind Harmer
0.557
20675128HRM_W1-127
Solar/Wind Harmer
0.187
966421AG1-511 GEN
Solar/Wind Harmer
9.472
20462827N BANGR8
Adder
0.789
209116AE2-175 GEN
Solar/Wind Harmer
4.502
961261AF2-417 GEN
Solar/Wind Harmer
1.066
209026WIENIPP4
Adder
5.665
209045AE2-271 GEN
Solar/Wind Harmer
17.146
959431AF2-234 GEN
Solar/Wind Harmer
2.005
964051AG1-259 GEN
Solar/Wind Harmer
1.345
964061AG1-260 GEN
Solar/Wind Harmer
1.345
959421AF2-233 GEN
Solar/Wind Harmer
1.003
20486527WR_V4-052
Adder
1.075
208862AG1-362 C
Solar/Wind Harmer
0.779
20390726Y2-042
Adder
2.817
20334726NME_Y1-047
Adder
2.498
203926AA2-133 GEN
Adder
2.311
205951AE1-129_GEN
Solar/Wind Harmer
7.739
3138216PACIFIC
Solar/Wind Helper
0.054
316411AF1-147_GEN1
Solar/Wind Helper
1.073
316415AF1-147_GEN2
Solar/Wind Helper
1.073
3141426STAFORD
Solar/Wind Helper
0.065
316164AC1-076 GEN
Solar/Wind Helper
1.394
238152AF2-075_GEN
Solar/Wind Helper
0.689
316223AC1-118
Solar/Wind Helper
0.426
23546401DTGZ2-030
Solar/Wind Helper
0.087
3141813NORNECK
Solar/Wind Helper
0.277
316312AB1-027
Solar/Wind Helper
0.524
3141783LANCAST
Solar/Wind Helper
0.165
3141783LANCAST
Solar/Wind Helper
0.11
3138133OCRAN
Solar/Wind Helper
0.082
3141913WHIT STONE
Solar/Wind Helper
0.274
316059AD1-063 C
Solar/Wind Helper
0.276
3143873LANEXA
Solar/Wind Helper
0.164
315662AE1-191 GEN
Solar/Wind Helper
1.472
315666AE1-190 GEN
Solar/Wind Helper
0.368
957601AF2-054 GEN
Solar/Wind Helper
0.367
3141873WAN 176
Solar/Wind Helper
0.055
316233AE1-074 FULL
Solar/Wind Helper
0.418
957831AF2-077 GEN
Solar/Wind Helper
0.367
316132AB2-190 GEN1
Solar/Wind Helper
1.548
316369SG1_INVT
Solar/Wind Helper
1.301
3143316POE
Solar/Wind Helper
1.065
316349AD2-085 GEN
Solar/Wind Helper
1.222
319010AE1-072 C
Solar/Wind Helper
3.05
316305AF2-043 C
Solar/Wind Helper
0.359
313526AB2-022
Solar/Wind Helper
0.405
3146486SUNBURY
Solar/Wind Helper
0.266
3146486SUNBURY
Solar/Wind Helper
0.266
316321Z2-027
Solar/Wind Helper
0.405
3145176PASQUOTANK
Solar/Wind Helper
0.165
316315AB2-025 C
Solar/Wind Helper
0.403
315611Z1-036_GEN2
Solar/Wind Helper
1.45
3130156CHOWAN
Solar/Wind Helper
0.263
3130156CHOWAN
Solar/Wind Helper
0.263
315816AE2-034 GEN
Solar/Wind Helper
1.192
3138266HYDRAULIC
Solar/Wind Helper
0.012
3138266HYDRAULIC
Solar/Wind Helper
0.007
3130546PLYMOUTH
Solar/Wind Helper
0.259
315732AD1-074 GEN1
Solar/Wind Helper
2.962
315733AD1-074 GEN2
Solar/Wind Helper
2.962
315735AD1-075 GEN1
Solar/Wind Helper
1.48
3146206CASHIE
Solar/Wind Helper
0.258
3145893MURPHYS
Solar/Wind Helper
0.697
3145893MURPHYS
Solar/Wind Helper
0.258
3145513AHOSKIE
Solar/Wind Helper
0.115
961941AG1-037 GEN
Solar/Wind Helper
0.087
3145513AHOSKIE
Solar/Wind Helper
0.257
946281AF1-292 GEN
Solar/Wind Helper
0.258
3146043SEABORD
Solar/Wind Helper
0.257
3145683EARLEYS
Solar/Wind Helper
0.513
3145683EARLEYS
Solar/Wind Helper
0.257
3145683EARLEYS
Solar/Wind Helper
0.257
315607AA1-063A GEN
Solar/Wind Helper
1.464
316087AB2-174 GEN
Solar/Wind Helper
1.793
3137643SOCKMAN
Solar/Wind Helper
1.021
3148133STUARTS
Solar/Wind Helper
0.153
3148013FISHERV
Solar/Wind Helper
0.146
3145796HORNRTN
Solar/Wind Helper
0.813
3145796HORNRTN
Solar/Wind Helper
0.102
3144303KENBRDG
Solar/Wind Helper
0.203
3146033SCOT NK
Solar/Wind Helper
1.015
316239AB2-077_GEN
Solar/Wind Helper
0.338
316238AB2-078_GEN
Solar/Wind Helper
0.338
316005AA1-067
Solar/Wind Helper
0.286
3145746EVERETS
Solar/Wind Helper
0.997
3145746EVERETS
Solar/Wind Helper
0.251
3145746EVERETS
Solar/Wind Helper
0.251
3145746EVERETS
Solar/Wind Helper
0.251
270494AE1-108_GEN
Solar/Wind Helper
3.34
316420AA1-050 GEN
Solar/Wind Helper
1.427
3145573BETHELC
Solar/Wind Helper
0.248
3145573BETHELC
Solar/Wind Helper
0.248
238208AF1-136 C
Solar/Wind Helper
0.192
238109AE1-109 GEN2
Solar/Wind Helper
0.092
238110AE1-109 GEN3
Solar/Wind Helper
0.092
316118AC1-105 GEN
Solar/Wind Helper
0.957
3148463FAIRFLD
Solar/Wind Helper
0.246
3147173SINAI
Solar/Wind Helper
0.245
3147243WELCO
Solar/Wind Helper
0.153
316123AC1-075 GEN
Solar/Wind Helper
1.435
270455AD2-022 GEN
Solar/Wind Helper
1.344
270457AD2-023 GEN
Solar/Wind Helper
0.885
3146456SLIGO L269
Solar/Wind Helper
0.267
316246AF1-032 C
Solar/Wind Helper
0.305
3146516WINFALL
Solar/Wind Helper
0.858
3146516WINFALL
Solar/Wind Helper
0.265
315800Z1-036_GEN1
Solar/Wind Helper
1.45
3130156CHOWAN
Solar/Wind Helper
0.263
3145663CRESWEL
Solar/Wind Helper
0.73
316322AB2-045
Solar/Wind Helper
0.29
3146776BUCKING
Solar/Wind Helper
0.104
3146926FARMVIL
Solar/Wind Helper
0.155
316023GEN1_S
Solar/Wind Helper
0.984
3146206CASHIE
Solar/Wind Helper
0.258
3145893MURPHYS
Solar/Wind Helper
1.033
3147983MERCK5
Solar/Wind Helper
0.103
3146173TUNIS
Solar/Wind Helper
0.258
316097T157 G90
Solar/Wind Helper
1.185
3145683EARLEYS
Solar/Wind Helper
0.257
3146263WOODLND
Solar/Wind Helper
0.256
316190AA2-174 GEN
Solar/Wind Helper
0.017
3145963POPLR C
Solar/Wind Helper
0.255
316011AB1-132 GEN
Solar/Wind Helper
2.748
3145823KELFORD
Solar/Wind Helper
0.255
316174AB2-169 GEN
Solar/Wind Helper
0.649
3145783HORNRTN
Solar/Wind Helper
0.255
3145796HORNRTN
Solar/Wind Helper
0.839
3145796HORNRTN
Solar/Wind Helper
0.254
316129AC1-054 GEN
Solar/Wind Helper
1.25
316212AC1-099_GEN
Solar/Wind Helper
1.132
316237AB2-079_GEN
Solar/Wind Helper
0.338
3145746EVERETS
Solar/Wind Helper
0.251
3145746EVERETS
Solar/Wind Helper
0.251
315687AD1-152 GEN
Solar/Wind Helper
1.346
315722AD1-056 GEN
Solar/Wind Helper
1.346
316494AC1-189 GEN
Solar/Wind Helper
1.524
3146233WITAKRS
Solar/Wind Helper
0.989
961671AG1-007 GEN
Solar/Wind Helper
0.178
3146083TARBORO
Solar/Wind Helper
0.248
3145543BTLEBRO
Solar/Wind Helper
0.247
3145543BTLEBRO
Solar/Wind Helper
0.198
316359AB2-059 GEN
Solar/Wind Helper
1.883
316049AB1-081 GEN
Solar/Wind Helper
1.506
316003AC1-222 GEN
Solar/Wind Helper
1.053
237080AD1-060 GEN
Solar/Wind Helper
0.291
964991AG1-363 GEN
Solar/Wind Helper
3.426
237038AE2-054 C
Solar/Wind Helper
0.224
3147123OTTER R
Solar/Wind Helper
0.135
3147312GRETNA
Solar/Wind Helper
0.179
3146802CHATHAM
Solar/Wind Helper
0.168
270016AE1-250 BESS
Solar/Wind Helper
0.825
HAMLETPJM->LTFIMP_HAMLET
CLTF
5.852
G-007ALTFEXP_G-007A->PJM
CMTX
56.958
CBM NorthLTFEXP_CBM-N->PJM
CBM
84.165
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
4.43
BlueGrassPJM->LTFIMP_BlueG
CLTF
13.809
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
150.07
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.411
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
21

Details for CHAN-01DOUBS 500.0 kV Ckt 1 line l/o PECO_P1-2_5012_SRT-A


Base Case Flowgate

Area:AP/PJM
Facility Description:
CHAN-01DOUBS 500.0 kV Ckt 1 line
Contingency Name:
PECO_P1-2_5012_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:107.27 %
Rating:4150.0 MVA
Rating Type:B
MVA to Mitigate:4451.53
MW Contribution:6.11
Bus #Bus NameTypeMW Contribution
200200DELTA2 CT1
50/50
3.899
200193DELTA CT2
50/50
2.178
200203Y1-065-STG
50/50
7.823
200055ROCKSP 4
50/50
2.817
233971AC1-093 C
Solar/Wind Harmer
0.056
970695AG2-447 GEN
Solar/Wind Harmer
3.266
972133AH1-634 GEN
Solar/Wind Harmer
4.811
972073AH1-586 GEN
Solar/Wind Harmer
12.229
232406W1-004 FULL
Solar/Wind Harmer
0.845
232914OH NUG3
Adder
11.524
232916OH NUG5
Adder
11.524
232921TASLEY2G
Adder
6.735
233996TM1833_GEN
Solar/Wind Harmer
0.002
233997TMININ_4.2
Solar/Wind Harmer
0.002
233990AG1-397 GEN
Solar/Wind Harmer
1.776
233940AF2-379 C
Solar/Wind Harmer
0
234015AF2-250 C
Solar/Wind Harmer
0
233900O-025 C
Adder
1.536
233994AC2-023 GEN
Solar/Wind Harmer
0.005
232907VN8
Adder
39.168
960671AF2-358 GEN
Solar/Wind Harmer
16.289
233952AC2-187 GEN
Solar/Wind Harmer
0.002
232417X3-008 C
Solar/Wind Harmer
0.002
972251AH1-710 GEN
Adder
57.775
233918AB1-142 GEN
Solar/Wind Harmer
0.331
233982AB2-133 GEN
Solar/Wind Harmer
0.005
228202CUMB CT
Adder
18.994
228711V2-041C
Solar/Wind Harmer
0
971553AH1-274 GEN
Solar/Wind Harmer
1.793
230430AE1-229_GEN
Solar/Wind Harmer
0.019
230415AB2-049 C
Solar/Wind Harmer
0
228729W2-030 C
Solar/Wind Harmer
0.001
200035PCHBTM 3
50/50
23.2
200201DELTA2 CT2
50/50
3.899
200034PCHBTM 2
50/50
22.699
200205Y1-065-CTG2
50/50
4.512
971149AH1-027 GEN
Solar/Wind Harmer
4.083
233939AC1-091 C
Solar/Wind Harmer
0.002
233970AC1-092 C
Solar/Wind Harmer
0.002
970545AG2-347 GEN
Solar/Wind Harmer
32.946
232899W1-062
Adder
12.553
233987AB2-037 GEN
Solar/Wind Harmer
0.014
972069AH1-584 GEN
Solar/Wind Harmer
8.152
972071AH1-585 GEN
Solar/Wind Harmer
8.152
233901CHERRYDALE C
Solar/Wind Harmer
0.002
232408W1-005 C
Solar/Wind Harmer
0.845
232410W1-006 C
Solar/Wind Harmer
0.845
232918OH NUG7
Adder
11.447
971747AH1-380 GEN
Solar/Wind Harmer
3.261
232905CHERITON_25
Adder
3.201
232926CRISFLD1
Adder
2.561
231940T-011
Adder
0.973
233946AB2-136 GEN
Solar/Wind Harmer
0.005
234036AF2-325 C
Solar/Wind Harmer
0.001
234041AC1-190 GEN
Solar/Wind Harmer
9.496
233984AB2-036 GEN
Solar/Wind Harmer
9.417
232424Y1-079 C
Solar/Wind Harmer
0.001
231131BLOOM ENRGY
Adder
5.629
234014AF1-036_GEN
Solar/Wind Harmer
3.004
233944AB2-135 GEN
Solar/Wind Harmer
0.006
233933AB2-153 GEN
Solar/Wind Harmer
0.002
232416X2-083
Adder
0.576
228251CARLLS#4
Adder
0.723
230422AE1-104_GEN1
Solar/Wind Harmer
15.494
230425AE1-104_GEN2
Solar/Wind Harmer
15.494
230407AD2-065 C
Solar/Wind Harmer
0
228307PCLP GT
Adder
13.798
228304LOGAN
Adder
27.574
972233AH1-701 GEN
Adder
4.775
219921AF1-264
Solar/Wind Harmer
0
213589EDDYSTN4
Adder
89.617
213587EDDYSTN3
Adder
89.611
219615MILLCREEK C
Solar/Wind Harmer
0
213815MOSER1-3
Adder
3.964
213815MOSER1-3
Adder
3.964
213535CROYDN11
Adder
11.416
20716428NHV_W2-082
Solar/Wind Harmer
0
200202DELTA2 ST
50/50
6.616
200195DELTA ST
50/50
3.366
200052ROCKSP 1
50/50
2.849
200053ROCKSP 2
50/50
2.789
233973AC2-185 C
Solar/Wind Harmer
0.002
234033AF1-007_GEN
Solar/Wind Harmer
-0.002
232904IR4
Adder
105.52
232920IR10
Adder
4.124
232432Z2-076 GEN
Solar/Wind Harmer
0.017
232912OH NUG1
Adder
11.524
232913OH NUG2
Adder
11.37
233923SMA
Solar/Wind Harmer
0.007
233990AG1-397 GEN
Solar/Wind Harmer
-0.208
233955AB2-172 GEN
Solar/Wind Harmer
0.004
232813VAUGHN
Adder
0.766
231906DC3 NUG
Adder
18.081
231902DC CT7
Adder
14.455
231907DC10
Adder
4.514
233968AD2-076_GEN
Solar/Wind Harmer
3.004
970597AG2-380 GEN
Solar/Wind Harmer
5.38
232436AB1-176 C
Solar/Wind Harmer
0
971983AH1-536 GEN
Solar/Wind Harmer
2.28
200192DELTA CT1
50/50
2.178
200194DELTA CT3
50/50
2.178
200204Y1-065-CTG1
50/50
4.512
200054ROCKSP 3
50/50
2.878
232901NORTHST
Adder
10.877
233972AC1-094 C
Solar/Wind Harmer
0.411
232900DEMECSMY
Adder
12.04
232434Z2-077 GEN
Solar/Wind Harmer
0.055
972177AH1-672 GEN
Solar/Wind Harmer
13.29
232404W1-003 C
Solar/Wind Harmer
0.845
232917OH NUG6
Adder
11.473
232915OH NUG4
Adder
11.447
233998TM1NIN_3.36
Solar/Wind Harmer
0.002
971195AH1-057 GEN
Solar/Wind Harmer
0.815
232428Y3-058 C
Solar/Wind Harmer
0.002
232919VN10
Adder
3.659
965821AG1-450 GEN
Solar/Wind Harmer
6.787
232426Y1-080 FULL
Solar/Wind Harmer
0
970277AG2-181 GEN
Solar/Wind Harmer
0.76
233964AF2-378 GEN
Solar/Wind Harmer
0
233954AC2-188 GEN
Solar/Wind Harmer
0.002
233950AC2-186 GEN
Solar/Wind Harmer
0.001
232910NRG_G1
Adder
11.214
233935AB2-179 C
Solar/Wind Harmer
1.748
231919CHRIST1
Adder
5.579
231920CHRIST2
Adder
5.455
970453AG2-297 GEN
Solar/Wind Harmer
2.931
228260V4-054C
Solar/Wind Harmer
0
228309CCLP NUG
Adder
29.607
228309CCLP NUG
Adder
28.163
972141AH1-641 GEN
Solar/Wind Harmer
3.83
964001AG1-254 GEN
Solar/Wind Harmer
0.444
971011AG2-627 GEN
Solar/Wind Harmer
6.11
971535AH1-265 GEN
Solar/Wind Harmer
3.144
227927V4-067C
Solar/Wind Harmer
0
228754AB1-001 C
Solar/Wind Harmer
0
219272CLEANLIGHT C
Solar/Wind Harmer
0
219688LUMSOLAR_S C
Solar/Wind Harmer
0
219914AD2-027 C
Solar/Wind Harmer
0.001
213942SCHUYLKILL
Adder
3.986
213942SCHUYLKILL
Adder
3.048
213957STHWK3-4
Adder
3.048
213957STHWK3-4
Adder
3.048
213561DLWR9-10
Adder
3.975
213561DLWR9-10
Adder
3.039
219607WPEMNERT C
Solar/Wind Harmer
0
219224BRL12CT4
Adder
9.966
214067T20SOLAR
Solar/Wind Harmer
0
213611FALLS1-3
Adder
3.929
213611FALLS1-3
Adder
3.929
20717128DIX_Z2-102
Solar/Wind Harmer
0
20715728PEM_W1-119
Solar/Wind Harmer
0.001
20715828PEM_W1-120
Solar/Wind Harmer
0.001
970025AG2-016 GEN
Solar/Wind Harmer
2.028
971189AH1-054 GEN
Solar/Wind Harmer
0.845
207459AE1-142 C O1
Solar/Wind Harmer
0.001
20714328BYD_X4-031
Solar/Wind Harmer
0.168
20714428HOW_X1-037
Solar/Wind Harmer
0.001
971521AH1-258 GEN
Solar/Wind Harmer
1.928
20720428HOL_W1-112
Solar/Wind Harmer
0
20635928PARLN3&4
Adder
8.147
218455CINNBAY_CGEN
Adder
2
218526CNTRALGAS2 C
Solar/Wind Harmer
0.843
218524CNTRALGAS1 C
Solar/Wind Harmer
0.841
218404KENILWRTH C
Adder
1.432
217167KRNY_14
Adder
10.191
217086KRNY_131
Adder
10.104
217147KRNY_1212
Adder
9.693
217147KRNY_1212
Adder
9.52
217146KRNY_1234
Adder
9.498
217146KRNY_1234
Adder
9.433
20676328BVR_Y1-020
Solar/Wind Harmer
0
207511W3-106 GEN
Solar/Wind Harmer
0.357
207530AG1-191 GEN
Solar/Wind Harmer
0.001
20674828DL_W4-046
Solar/Wind Harmer
0
971009AG2-626 GEN
Solar/Wind Harmer
1.155
207408W3-077 C
Solar/Wind Harmer
0
20675728RH_W2-091
Solar/Wind Harmer
0.001
20675928HOL_W4-097
Solar/Wind Harmer
0
207484AF2-139 C O1
Solar/Wind Harmer
0
20675128HRM_W1-127
Solar/Wind Harmer
0
966421AG1-511 GEN
Solar/Wind Harmer
6.538
20462827N BANGR8
Adder
0.78
209116AE2-175 GEN
Solar/Wind Harmer
0.008
209026WIENIPP4
Adder
5.601
209045AE2-271 GEN
Solar/Wind Harmer
11.828
20486527WR_V4-052
Adder
1.062
208862AG1-362 C
Solar/Wind Harmer
0.572
20390726Y2-042
Adder
2.77
20334726NME_Y1-047
Adder
2.451
203926AA2-133 GEN
Adder
2.264
3138216PACIFIC
Solar/Wind Helper
0.054
316411AF1-147_GEN1
Solar/Wind Helper
1.09
316415AF1-147_GEN2
Solar/Wind Helper
1.09
3141426STAFORD
Solar/Wind Helper
0.066
316164AC1-076 GEN
Solar/Wind Helper
1.419
238152AF2-075_GEN
Solar/Wind Helper
0.701
316223AC1-118
Solar/Wind Helper
0.434
23546401DTGZ2-030
Solar/Wind Helper
0.089
3141813NORNECK
Solar/Wind Helper
0.282
316312AB1-027
Solar/Wind Helper
0.534
3141783LANCAST
Solar/Wind Helper
0.168
3141783LANCAST
Solar/Wind Helper
0.112
3138133OCRAN
Solar/Wind Helper
0.084
3141913WHIT STONE
Solar/Wind Helper
0.28
316059AD1-063 C
Solar/Wind Helper
0.281
3143873LANEXA
Solar/Wind Helper
0.167
315662AE1-191 GEN
Solar/Wind Helper
1.5
315666AE1-190 GEN
Solar/Wind Helper
0.375
957601AF2-054 GEN
Solar/Wind Helper
0.374
3141873WAN 176
Solar/Wind Helper
0.056
316233AE1-074 FULL
Solar/Wind Helper
0.426
957831AF2-077 GEN
Solar/Wind Helper
0.374
316132AB2-190 GEN1
Solar/Wind Helper
1.578
316369SG1_INVT
Solar/Wind Helper
1.326
3143316POE
Solar/Wind Helper
1.085
316349AD2-085 GEN
Solar/Wind Helper
1.246
319010AE1-072 C
Solar/Wind Helper
3.109
316305AF2-043 C
Solar/Wind Helper
0.366
313526AB2-022
Solar/Wind Helper
0.413
3146486SUNBURY
Solar/Wind Helper
0.271
3146486SUNBURY
Solar/Wind Helper
0.271
316321Z2-027
Solar/Wind Helper
0.413
3145176PASQUOTANK
Solar/Wind Helper
0.168
316315AB2-025 C
Solar/Wind Helper
0.411
315611Z1-036_GEN2
Solar/Wind Helper
1.479
3130156CHOWAN
Solar/Wind Helper
0.268
3130156CHOWAN
Solar/Wind Helper
0.268
315816AE2-034 GEN
Solar/Wind Helper
1.216
3138266HYDRAULIC
Solar/Wind Helper
0.012
3138266HYDRAULIC
Solar/Wind Helper
0.008
3130546PLYMOUTH
Solar/Wind Helper
0.265
315732AD1-074 GEN1
Solar/Wind Helper
3.021
315733AD1-074 GEN2
Solar/Wind Helper
3.021
315735AD1-075 GEN1
Solar/Wind Helper
1.51
3146206CASHIE
Solar/Wind Helper
0.264
3145893MURPHYS
Solar/Wind Helper
0.711
3145893MURPHYS
Solar/Wind Helper
0.264
3145513AHOSKIE
Solar/Wind Helper
0.118
961941AG1-037 GEN
Solar/Wind Helper
0.088
3145513AHOSKIE
Solar/Wind Helper
0.262
946281AF1-292 GEN
Solar/Wind Helper
0.263
3146043SEABORD
Solar/Wind Helper
0.262
3145683EARLEYS
Solar/Wind Helper
0.524
3145683EARLEYS
Solar/Wind Helper
0.262
3145683EARLEYS
Solar/Wind Helper
0.262
315607AA1-063A GEN
Solar/Wind Helper
1.494
316087AB2-174 GEN
Solar/Wind Helper
1.83
3137643SOCKMAN
Solar/Wind Helper
1.042
3148133STUARTS
Solar/Wind Helper
0.156
3148013FISHERV
Solar/Wind Helper
0.149
3145796HORNRTN
Solar/Wind Helper
0.83
3145796HORNRTN
Solar/Wind Helper
0.104
3144303KENBRDG
Solar/Wind Helper
0.207
3146033SCOT NK
Solar/Wind Helper
1.036
316239AB2-077_GEN
Solar/Wind Helper
0.345
316238AB2-078_GEN
Solar/Wind Helper
0.345
316005AA1-067
Solar/Wind Helper
0.292
3145746EVERETS
Solar/Wind Helper
1.018
3145746EVERETS
Solar/Wind Helper
0.256
3145746EVERETS
Solar/Wind Helper
0.256
3145746EVERETS
Solar/Wind Helper
0.256
270494AE1-108_GEN
Solar/Wind Helper
3.41
316420AA1-050 GEN
Solar/Wind Helper
1.456
3145573BETHELC
Solar/Wind Helper
0.254
3145573BETHELC
Solar/Wind Helper
0.254
238208AF1-136 C
Solar/Wind Helper
0.196
238109AE1-109 GEN2
Solar/Wind Helper
0.094
238110AE1-109 GEN3
Solar/Wind Helper
0.094
316118AC1-105 GEN
Solar/Wind Helper
0.977
3148463FAIRFLD
Solar/Wind Helper
0.251
3147173SINAI
Solar/Wind Helper
0.25
3147243WELCO
Solar/Wind Helper
0.156
316123AC1-075 GEN
Solar/Wind Helper
1.467
270455AD2-022 GEN
Solar/Wind Helper
1.374
270457AD2-023 GEN
Solar/Wind Helper
0.905
237085AD2-009_GEN
Solar/Wind Helper
1.357
207500AE2-000G1
Solar/Wind Harmer
14.018
207497AE2-000G2
Solar/Wind Harmer
14.018
207507AE2-000G3
Solar/Wind Harmer
14.018
20636128O CRK C2
Adder
7.144
20714928UPF_X1-085
Solar/Wind Harmer
0
20628028LAKEHURS
Adder
1.053
219114HARTZY_C
Solar/Wind Harmer
0
20720628TIN_W1-124
Solar/Wind Harmer
0.001
20716928W4-060COL
Solar/Wind Harmer
0
218440SUMMTASSOC C
Solar/Wind Harmer
0
218418LINDEN_G5
Adder
18.869
218419LINDEN_G6
Adder
18.869
972260AH1-715 GEN1
Adder
15.109
20673828FLE_V3-070
Solar/Wind Harmer
0
207442AE1-156 GEN
Solar/Wind Harmer
0.066
20676128MHD_W3-029
Solar/Wind Harmer
0
219036LINDEN_G7
Adder
18.362
219035LINDEN_G8
Adder
18.1
972261AH1-715 GEN2
Adder
17.577
972237AH1-703 GEN
Adder
11.093
217086KRNY_131
Adder
10.212
217083KRNY_132
Adder
10.126
20671828STAW2-080
Solar/Wind Harmer
0
20674528F3S_W2-016
Solar/Wind Harmer
0
20676228FRD_X1-012
Solar/Wind Harmer
0.001
20674928WA_W3-044
Solar/Wind Harmer
0.001
20465127PORT CT
Adder
4.34
20674128FR_U2-059
Solar/Wind Harmer
0
966111AG1-480 GEN
Solar/Wind Harmer
3.673
211065PSPA IPP
Solar/Wind Harmer
0.001
211065PSPA IPP
Solar/Wind Harmer
0.001
208972BECR K09
Solar/Wind Harmer
0.001
961541AF2-445A GEN
Solar/Wind Harmer
2.325
209029WAYMART-WD
Solar/Wind Harmer
0.001
209009PEIP 2
Adder
8.081
209010PEIP 1
Adder
3.661
209010PEIP 1
Adder
0.536
209054AE2-059 GEN
Solar/Wind Harmer
0.001
209059AE2-084 GEN
Solar/Wind Harmer
1.611
970761AG2-481 GEN
Solar/Wind Harmer
0.786
209130AF1-271A GEN
Solar/Wind Harmer
1.943
20465527S.RDG CT
Adder
2.633
20478527GLRA_Q45
Adder
0.304
209137AF2-361 C
Solar/Wind Harmer
0.004
238175AF1-290_GEN
Solar/Wind Helper
0.158
315651AD1-115 GEN
Solar/Wind Helper
1.005
316447AC1-158 HLD
Solar/Wind Helper
3.655
238169AE2-226 GEN1
Solar/Wind Helper
0.722
238170AE2-226 GEN2
Solar/Wind Helper
0.722
966001AG1-469 GEN
Solar/Wind Helper
0.309
316468AD1-105 GEN
Solar/Wind Helper
1.419
316077AC2-138 C
Solar/Wind Helper
0.265
966871AG1-558 GEN
Solar/Wind Helper
0.38
316487AF1-042 GEN
Solar/Wind Helper
0.284
316075AC2-137 C
Solar/Wind Helper
0.426
3143526WINTERP
Solar/Wind Helper
1.451
3142946ENON
Solar/Wind Helper
0.028
316240AF1-291 C
Solar/Wind Helper
0.372
316033AB2-134 GEN
Solar/Wind Helper
0.948
315697AD1-025 GEN
Solar/Wind Helper
3.151
316236AE1-162_GEN
Solar/Wind Helper
0.369
316036AC1-147 C
Solar/Wind Helper
0.416
316316AC1-027 C
Solar/Wind Helper
0.431
3142956BIRDNECK
Solar/Wind Helper
0.184
316185AD1-033 GEN
Solar/Wind Helper
1.283
3145506HICKORY
Solar/Wind Helper
1.091
3145506HICKORY
Solar/Wind Helper
0.654
3145506HICKORY
Solar/Wind Helper
0.164
316339AD2-160 GEN
Solar/Wind Helper
1.037
235020AA1-095 C
Solar/Wind Helper
0.051
316018AA1-139 ULT2
Solar/Wind Helper
1.171
316017AA1-139 ULT1
Solar/Wind Helper
1.244
3137176SLIGO L2192
Solar/Wind Helper
1.083
23777901MDS_W4-102
Solar/Wind Helper
0.17
3130086AYDLETT
Solar/Wind Helper
1.088
3146386ELIZ CT
Solar/Wind Helper
0.271
316431W1029_GEN1
Solar/Wind Helper
1.092
316433W1029_GEN2
Solar/Wind Helper
1.092
3146516WINFALL
Solar/Wind Helper
0.27
3146516WINFALL
Solar/Wind Helper
0.27
3146516WINFALL
Solar/Wind Helper
0.27
3146626S HERTFORD
Solar/Wind Helper
0.27
3146626S HERTFORD
Solar/Wind Helper
0.27
3144356SAPONY
Solar/Wind Helper
0.483
315742AE1-103 GEN
Solar/Wind Helper
0.433
3132123MT JACKSON
Solar/Wind Helper
0.835
3146776BUCKING
Solar/Wind Helper
1.06
3146776BUCKING
Solar/Wind Helper
0.086
3145893MURPHYS
Solar/Wind Helper
0.378
3145893MURPHYS
Solar/Wind Helper
0.474
3146173TUNIS
Solar/Wind Helper
0.263
3146173TUNIS
Solar/Wind Helper
0.263
315821AE2-092 GEN
Solar/Wind Helper
2.433
316181AB2-040 GEN
Solar/Wind Helper
1.875
3147133PAMPLIN
Solar/Wind Helper
0.261
3147133PAMPLIN
Solar/Wind Helper
0.209
3142666NORTHAMPTON
Solar/Wind Helper
0.261
3142666NORTHAMPTON
Solar/Wind Helper
0.261
3142666NORTHAMPTON
Solar/Wind Helper
0.261
3142666NORTHAMPTON
Solar/Wind Helper
0.156
316426AA2-053 GEN
Solar/Wind Helper
1.486
3145593CAROLNA
Solar/Wind Helper
0.26
3145593CAROLNA
Solar/Wind Helper
0.26
3145796HORNRTN
Solar/Wind Helper
0.778
316034AC1-036 C
Solar/Wind Helper
0.271
3145933PARMELE
Solar/Wind Helper
0.514
3145933PARMELE
Solar/Wind Helper
0.257
316274AC1-208 GEN
Solar/Wind Helper
1.567
226929AD2-058 GEN
Solar/Wind Helper
0.099
3146843MT LREL
Solar/Wind Helper
0.253
3146843MT LREL
Solar/Wind Helper
0.253
237034AC2-136 C
Solar/Wind Helper
0.207
316222AC1-221 GEN
Solar/Wind Helper
1.387
316197AC1-042 GEN
Solar/Wind Helper
0.215
270013AE1-250 PV
Solar/Wind Helper
0.845
237002AB1-128_GEN
Solar/Wind Helper
0.363
228304LOGAN
Adder
24.8
219623KINSLEYBEA C
Solar/Wind Harmer
0
213497CHSTR7-9
Adder
3.069
219766PARADISE C
Solar/Wind Harmer
0
219912AD2-042 GEN
Solar/Wind Harmer
0.001
213958STHWK5-6
Adder
3.048
213560DLW11-12
Adder
3.039
219906AC1-017 C
Solar/Wind Harmer
0
213815MOSER1-3
Adder
3.964
219610FLORENCE C
Solar/Wind Harmer
0.001
219348LDSOLAR C
Solar/Wind Harmer
0.001
219221BRL12CT1
Adder
9.966
219223BRL12CT3
Adder
9.966
20716028EGP_W2-019
Solar/Wind Harmer
0
20720828JCB_W4-025
Solar/Wind Harmer
0
20715028HAN_X4-015
Solar/Wind Harmer
0
20636028O CRK C1
Adder
7.835
971667AH1-334 GEN
Solar/Wind Harmer
1.966
219727YARDVSOLFA C
Solar/Wind Harmer
0
20714528FRN_Y2-051
Solar/Wind Harmer
0
219276PARKLANDSO C
Solar/Wind Harmer
0
20716228APLW2-078
Solar/Wind Harmer
0
20720528MAN_W1-024
Solar/Wind Harmer
0
967451AG2-055 C O1
Solar/Wind Harmer
273.543
219612MATRIX C
Solar/Wind Harmer
0
218438BLK ROCK C
Solar/Wind Harmer
0
20635828PARLN1&2
Adder
3.69
20635928PARLN3&4
Adder
3.69
20635028RRCT1&2
Adder
12.969
20635128RRCT3&4
Adder
10.752
219908AB1-139 C
Solar/Wind Harmer
0
20673728F2S_V4-070
Solar/Wind Harmer
0
217186ESSEX_G9
Adder
17.527
217194REDH C
Solar/Wind Harmer
0
20676728BRNX1-095
Solar/Wind Harmer
0
207510AF2-138 C
Solar/Wind Harmer
0.001
20674628WNG_W3-110
Solar/Wind Harmer
0
971007AG2-625 GEN
Solar/Wind Harmer
1.811
20466127PORT 5CT
Adder
28.867
20633028GILCT9
Adder
30.801
20465427SHAW CT
Adder
4.194
209025WIENIPP3
Adder
5.543
963071AG1-156 GEN
Solar/Wind Harmer
0.46
970095AG2-074 GEN
Solar/Wind Harmer
5.242
209027LOR2_Q27
Solar/Wind Harmer
0.001
209022WHFR IPP
Adder
3.354
209142AF1-226 GEN
Solar/Wind Harmer
2.865
209093AE2-110 GEN
Solar/Wind Harmer
1.637
209120AE2-241 GEN
Solar/Wind Harmer
1.637
972245AH1-707 GEN
Adder
5.462
972221AH1-695 GEN
Adder
123.484
209067AE2-060 GEN
Solar/Wind Harmer
0.001
970767AG2-484 GEN
Solar/Wind Harmer
0.618
3141196NOKESVL
Solar/Wind Helper
1.258
316044AC1-158 PL1
Solar/Wind Helper
1.661
316450AC1-158 RIC
Solar/Wind Helper
0.443
316170AC1-121 GEN2
Solar/Wind Helper
0.456
3132273ORANGE
Solar/Wind Helper
0.058
3147666LOUISA
Solar/Wind Helper
0.668
966881AG1-559 GEN
Solar/Wind Helper
0.389
238147AE2-230_GEN1
Solar/Wind Helper
0.491
238149AF1-291A_GEN
Solar/Wind Helper
0.14
3141906WESTMOR
Solar/Wind Helper
0.114
316473AC1-191 GEN
Solar/Wind Helper
1.722
237061AD1-155 GEN
Solar/Wind Helper
0.053
316404AE1-155 C
Solar/Wind Helper
2.376
316484AD2-074 GEN
Solar/Wind Helper
0.542
316280AD1-041 GEN
Solar/Wind Helper
0.938
316156AD2-030 GEN
Solar/Wind Helper
0.421
3142946ENON
Solar/Wind Helper
0.093
316382AG1-145 C
Solar/Wind Helper
0.372
315839AE2-212 C
Solar/Wind Helper
0.37
3145336SMITFLD
Solar/Wind Helper
0.11
315773AC2-141 GEN
Solar/Wind Helper
5.898
316313AB2-026
Solar/Wind Helper
0.417
316258AE1-075 C
Solar/Wind Helper
0.375
316405AF2-144 C
Solar/Wind Helper
0.313
3144536CHRHLND
Solar/Wind Helper
0.041
3144873MCLAUGH
Solar/Wind Helper
0.007
3146456SLIGO L269
Solar/Wind Helper
0.272
316320Y1-086
Solar/Wind Helper
0.121
316435W1029_GEN3
Solar/Wind Helper
1.092
3146516WINFALL
Solar/Wind Helper
0.27
3146626S HERTFORD
Solar/Wind Helper
0.27
3145273HOLLAND
Solar/Wind Helper
0.202
3146376EDENTON
Solar/Wind Helper
0.268
315614AA2-178 GEN
Solar/Wind Helper
1.621
3146776BUCKING
Solar/Wind Helper
0.095
315737AD1-076 GEN
Solar/Wind Helper
2.584
3146926FARMVIL
Solar/Wind Helper
0.158
316365GEN2_N
Solar/Wind Helper
1.004
3146206CASHIE
Solar/Wind Helper
0.264
3145893MURPHYS
Solar/Wind Helper
0.094
3145893MURPHYS
Solar/Wind Helper
0.264
3146173TUNIS
Solar/Wind Helper
0.263
316095T157 G97
Solar/Wind Helper
1.209
3156021HOLLOMANSOL
Solar/Wind Helper
1.997
316463AE2-346 GEN
Solar/Wind Helper
0.24
316140AB2-099
Solar/Wind Helper
0.1
942461AE2-259 GEN
Solar/Wind Helper
1.768
966621AG1-532 GEN
Solar/Wind Helper
0.239
316499AE2-029_GEN
Solar/Wind Helper
0.881
3146263WOODLND
Solar/Wind Helper
0.261
313506AB2-031 GEN
Solar/Wind Helper
1.186
3147133PAMPLIN
Solar/Wind Helper
0.819
3142666NORTHAMPTON
Solar/Wind Helper
0.261
3147043LAWRENC
Solar/Wind Helper
0.156
3145963POPLR C
Solar/Wind Helper
0.261
316317KELFORD C
Solar/Wind Helper
0.222
3145823KELFORD
Solar/Wind Helper
0.26
316478AD1-087 GEN
Solar/Wind Helper
1.27
316486AD2-202 GEN
Solar/Wind Helper
0.372
3148013FISHERV
Solar/Wind Helper
0.26
3145796HORNRTN
Solar/Wind Helper
1.037
3145796HORNRTN
Solar/Wind Helper
0.259
315785AD2-033 C
Solar/Wind Helper
3.016
316210AC1-098 GEN
Solar/Wind Helper
2.079
316131AB2-060 GEN
Solar/Wind Helper
1.568
3145933PARMELE
Solar/Wind Helper
0.257
23583801GRNGAP
Solar/Wind Helper
4.398
3145746EVERETS
Solar/Wind Helper
0.256
3145746EVERETS
Solar/Wind Helper
0.256
315724AD1-057 GEN
Solar/Wind Helper
0.756
316327AA2-057 GEN
Solar/Wind Helper
1.454
3146233WITAKRS
Solar/Wind Helper
0.273
3146233WITAKRS
Solar/Wind Helper
0.172
3146073TAR RVR
Solar/Wind Helper
0.254
3146083TARBORO
Solar/Wind Helper
0.254
3138543CONSLDL
Solar/Wind Helper
0.167
3145543BTLEBRO
Solar/Wind Helper
0.252
3145543BTLEBRO
Solar/Wind Helper
0.252
238108AE1-109 GEN1
Solar/Wind Helper
0.094
238221AF1-254 C O1
Solar/Wind Helper
0.248
315616AA1-038_C
Solar/Wind Helper
1.138
316248AF1-058 C
Solar/Wind Helper
0.336
227287AC2-120 GEN
Solar/Wind Helper
0.335
226910AB2-157 C
Solar/Wind Helper
0.014
316283AC2-100 C
Solar/Wind Helper
1.295
235067AD1-061 GEN
Solar/Wind Helper
0.416
3147312GRETNA
Solar/Wind Helper
0.046
270197AD1-017 GEN1
Solar/Wind Helper
1.223
270018AE2-047 C O1
Solar/Wind Helper
0.79
234012AE2-112_GEN
Solar/Wind Harmer
3.004
232422X3-066 FULL
Solar/Wind Harmer
0.108
233930AB2-032 GEN
Solar/Wind Harmer
1.235
233915AB1-141 GEN
Solar/Wind Harmer
0.331
231918WEST 1
Adder
4.241
231917EM10
Adder
2.963
228206SHRMN CT
Adder
19.049
228732V1-021 C
Adder
0.217
945431AF1-208 GEN
Solar/Wind Harmer
6.903
970997AG2-616 GEN
Solar/Wind Harmer
8.26
228351V2-046C
Solar/Wind Harmer
0.001
230511AF1-262
Solar/Wind Harmer
0
228728W1-130C
Solar/Wind Harmer
0.001
230434AG1-499 GEN
Solar/Wind Harmer
0.001
219258KINSLEYDEP C
Solar/Wind Harmer
0.001
218660EHAMPSOLAR C
Solar/Wind Harmer
0
213497CHSTR7-9
Adder
3.069
213497CHSTR7-9
Adder
3.069
219904AC1-010 C
Solar/Wind Harmer
0.001
219287REEVESEAST C
Solar/Wind Harmer
0
219686LUMSOLAR_N C
Solar/Wind Harmer
0
219907AC1-030 C
Solar/Wind Harmer
0
213958STHWK5-6
Adder
3.048
213560DLW11-12
Adder
3.039
219304NAMERICA C
Solar/Wind Harmer
0.102
219222BRL12CT2
Adder
9.966
213611FALLS1-3
Adder
3.929
214194N WALES4
Adder
0.947
20720728JCB_W1-129
Solar/Wind Harmer
0
207522AF2-254 C
Solar/Wind Harmer
1.029
207487AE2-000G4
Solar/Wind Harmer
14.018
207445AB1-138_GEN
Solar/Wind Harmer
0.001
20628028LAKEHURS
Adder
2.083
20714828MDF_W3-079
Solar/Wind Harmer
0.109
207454AA2-184 E
Solar/Wind Harmer
0.001
20715228NPK_W1-113
Solar/Wind Harmer
0
20742028HF_AC1-207
Solar/Wind Harmer
0.001
217197RE CRAN C
Solar/Wind Harmer
0
20635828PARLN1&2
Adder
8.147
20635028RRCT1&2
Adder
12.769
20635128RRCT3&4
Adder
12.326
217213AMBOY SO C
Solar/Wind Harmer
0
972275AH1-722 GEN
Adder
34.688
207528AF2-192 GEN
Solar/Wind Harmer
0.001
20673628F1S_V4-069
Solar/Wind Harmer
0
20675428EAM_W2-061
Solar/Wind Harmer
0
218449LINSOLAR C
Solar/Wind Harmer
0
20676428JCR_X2-075
Solar/Wind Harmer
0
217121ECCF
Adder
0.476
217083KRNY_132
Adder
10.191
20674328GAR_V4-001
Solar/Wind Harmer
0
20675828AU_W4-064
Solar/Wind Harmer
0
971519AH1-257 GEN
Solar/Wind Harmer
1.777
207437AD2-070 GEN
Solar/Wind Harmer
0.072
20465127PORT CT
Adder
3.271
20671928W4-073
Solar/Wind Harmer
0
966181AG1-487 GEN
Solar/Wind Harmer
4.156
208909MACR G3
Adder
173.279
209023WIENIPP1
Adder
11.334
209025WIENIPP3
Adder
5.658
212266LOR1
Solar/Wind Harmer
0.497
209010PEIP 1
Adder
0.666
212174INGE
Adder
1.123
205941AD2-115 GEN
Solar/Wind Harmer
0.119
212507AE2-042_GEN
Solar/Wind Harmer
0.614
209071AE2-133 GEN
Solar/Wind Harmer
0.001
970665AG2-430 GEN
Solar/Wind Harmer
7.182
209018SUNBIPCT
Adder
7.379
970757AG2-479 GEN
Solar/Wind Harmer
0.781
20467927PC_Q59Y356
Adder
0.836
20465527S.RDG CT
Adder
2.721
972241AH1-705 GEN
Adder
5.64
209008PAXT IPP
Adder
1.813
970679AG2-439 GEN
Solar/Wind Harmer
0.728
200917MEHOOPANY_G
Solar/Wind Harmer
0.367
205967AE2-211_GEN
Solar/Wind Harmer
3.731
972271AH1-720 GEN
Adder
6.105
941421AE2-139 GEN
Solar/Wind Harmer
0
20328326MANOR_T86
Adder
0.126
316006AB2-029 C
Solar/Wind Helper
0.146
316045AC1-158 PL2
Solar/Wind Helper
5.316
316254AC1-120 GEN1
Solar/Wind Helper
1.368
3147666LOUISA
Solar/Wind Helper
1.161
316192AB2-158 GEN
Solar/Wind Helper
1.949
238148AE2-230_GEN2
Solar/Wind Helper
0.493
316337AD2-073 GEN
Solar/Wind Helper
0.43
964211AG1-282 GEN
Solar/Wind Helper
0.38
3141726DUNNSVL
Solar/Wind Helper
1.128
3142416OLDCHRC
Solar/Wind Helper
0.729
3142416OLDCHRC
Solar/Wind Helper
0.279
3138133OCRAN
Solar/Wind Helper
0.168
3141766HARMONY
Solar/Wind Helper
0.056
3143526WINTERP
Solar/Wind Helper
1.451
3142433PROV 92
Solar/Wind Helper
1.116
3143226MDLTHAN
Solar/Wind Helper
0.279
3142543TWELFTH
Solar/Wind Helper
0.027
316159AE1-175 C
Solar/Wind Helper
0.42
316458AB2-190 GEN2
Solar/Wind Helper
1.578
3145336SMITFLD
Solar/Wind Helper
1.097
316294AC1-161 GEN
Solar/Wind Helper
5.011
316381AD1-082 GEN
Solar/Wind Helper
1.417
316375AC2-012 GEN
Solar/Wind Helper
0.716
316072AD1-144
Solar/Wind Helper
0.312
316336AC2-165 C
Solar/Wind Helper
1.47
316388AE2-253 GEN
Solar/Wind Helper
1.037
3146456SLIGO L269
Solar/Wind Helper
0.272
316246AF1-032 C
Solar/Wind Helper
0.311
3146516WINFALL
Solar/Wind Helper
0.875
3146516WINFALL
Solar/Wind Helper
0.27
315800Z1-036_GEN1
Solar/Wind Helper
1.479
3130156CHOWAN
Solar/Wind Helper
0.268
3145663CRESWEL
Solar/Wind Helper
0.745
316322AB2-045
Solar/Wind Helper
0.295
3146776BUCKING
Solar/Wind Helper
0.106
3146926FARMVIL
Solar/Wind Helper
0.158
316023GEN1_S
Solar/Wind Helper
1.004
3146206CASHIE
Solar/Wind Helper
0.264
3145893MURPHYS
Solar/Wind Helper
1.054
3146173TUNIS
Solar/Wind Helper
0.263
3147983MERCK5
Solar/Wind Helper
0.105
316097T157 G90
Solar/Wind Helper
1.209
3145683EARLEYS
Solar/Wind Helper
0.262
3146263WOODLND
Solar/Wind Helper
0.261
316190AA2-174 GEN
Solar/Wind Helper
0.017
3145963POPLR C
Solar/Wind Helper
0.261
316011AB1-132 GEN
Solar/Wind Helper
2.803
3145823KELFORD
Solar/Wind Helper
0.26
316174AB2-169 GEN
Solar/Wind Helper
0.662
3145783HORNRTN
Solar/Wind Helper
0.26
3145796HORNRTN
Solar/Wind Helper
0.856
3145796HORNRTN
Solar/Wind Helper
0.259
316129AC1-054 GEN
Solar/Wind Helper
1.276
316212AC1-099_GEN
Solar/Wind Helper
1.155
316237AB2-079_GEN
Solar/Wind Helper
0.345
3145746EVERETS
Solar/Wind Helper
0.256
3145746EVERETS
Solar/Wind Helper
0.256
315687AD1-152 GEN
Solar/Wind Helper
1.374
315722AD1-056 GEN
Solar/Wind Helper
1.374
316494AC1-189 GEN
Solar/Wind Helper
1.555
3146233WITAKRS
Solar/Wind Helper
1.01
961671AG1-007 GEN
Solar/Wind Helper
0.182
3146083TARBORO
Solar/Wind Helper
0.254
3145543BTLEBRO
Solar/Wind Helper
0.252
3145543BTLEBRO
Solar/Wind Helper
0.202
316359AB2-059 GEN
Solar/Wind Helper
1.922
316049AB1-081 GEN
Solar/Wind Helper
1.537
316003AC1-222 GEN
Solar/Wind Helper
1.076
237080AD1-060 GEN
Solar/Wind Helper
0.298
964991AG1-363 GEN
Solar/Wind Helper
3.503
237038AE2-054 C
Solar/Wind Helper
0.229
3147123OTTER R
Solar/Wind Helper
0.138
3147312GRETNA
Solar/Wind Helper
0.183
3146802CHATHAM
Solar/Wind Helper
0.172
270016AE1-250 BESS
Solar/Wind Helper
0.845
270173AC1-122 GEN
Solar/Wind Helper
1.452
HAMLETPJM->LTFIMP_HAMLET
CLTF
5.987
G-007ALTFEXP_G-007A->PJM
CMTX
56.398
CBM NorthLTFEXP_CBM-N->PJM
CBM
83.022
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
4.56
BlueGrassPJM->LTFIMP_BlueG
CLTF
14.213
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
148.565
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.493
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
21.603

Details for CNASTONE-BRIGHTON 500.0 kV Ckt 1 line l/o AP_P2-3_PE-500-019E_SRT-SL


Base Case Flowgate

Area:PJM
Facility Description:
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-500-019E_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:140.95 %
Rating:3098.0 MVA
Rating Type:B
MVA to Mitigate:4366.58
MW Contribution:6.58
Bus #Bus NameTypeMW Contribution
200202DELTA2 ST
50/50
4.752
200195DELTA ST
50/50
2.418
200052ROCKSP 1
50/50
2.058
200053ROCKSP 2
50/50
2.014
234033AF1-007_GEN
Solar/Wind Harmer
22.737
233973AC2-185 C
Solar/Wind Harmer
3.513
232904IR4
Adder
78.619
233923SMA
Solar/Wind Harmer
4.516
232432Z2-076 GEN
Solar/Wind Harmer
0.128
232912OH NUG1
Adder
8.589
232913OH NUG2
Adder
8.474
232920IR10
Adder
3.073
233990AG1-397 GEN
Solar/Wind Harmer
0.054
233955AB2-172 GEN
Solar/Wind Harmer
4.86
232813VAUGHN
Adder
0.571
233968AD2-076_GEN
Solar/Wind Harmer
6.418
970597AG2-380 GEN
Solar/Wind Harmer
4.03
231906DC3 NUG
Adder
13.537
231902DC CT7
Adder
10.822
231907DC10
Adder
3.379
232436AB1-176 C
Solar/Wind Harmer
0.222
971983AH1-536 GEN
Solar/Wind Harmer
7.232
233935AB2-179 C
Solar/Wind Harmer
2.399
231919CHRIST1
Adder
4.204
231920CHRIST2
Adder
4.111
970453AG2-297 GEN
Solar/Wind Harmer
2.38
228260V4-054C
Solar/Wind Harmer
0.883
228309CCLP NUG
Adder
22.232
228309CCLP NUG
Adder
21.148
972141AH1-641 GEN
Solar/Wind Harmer
2.473
964001AG1-254 GEN
Solar/Wind Harmer
1.747
971011AG2-627 GEN
Solar/Wind Harmer
6.58
971535AH1-265 GEN
Solar/Wind Harmer
3.653
227927V4-067C
Solar/Wind Harmer
0.17
228754AB1-001 C
Solar/Wind Harmer
0.119
219137THOSOLAR C
Solar/Wind Harmer
1.031
219272CLEANLIGHT C
Solar/Wind Harmer
0.155
213942SCHUYLKILL
Adder
3.025
213942SCHUYLKILL
Adder
2.313
213957STHWK3-4
Adder
2.312
213957STHWK3-4
Adder
2.312
219914AD2-027 C
Solar/Wind Harmer
0.509
219688LUMSOLAR_S C
Solar/Wind Harmer
0.172
213561DLWR9-10
Adder
3.009
213561DLWR9-10
Adder
2.301
219607WPEMNERT C
Solar/Wind Harmer
0.353
219224BRL12CT4
Adder
7.52
214067T20SOLAR
Solar/Wind Harmer
0.212
213611FALLS1-3
Adder
2.968
213611FALLS1-3
Adder
2.968
20717128DIX_Z2-102
Solar/Wind Harmer
1.105
20715728PEM_W1-119
Solar/Wind Harmer
0.447
20715828PEM_W1-120
Solar/Wind Harmer
0.447
970025AG2-016 GEN
Solar/Wind Harmer
2.368
971189AH1-054 GEN
Solar/Wind Harmer
0.986
207459AE1-142 C O1
Solar/Wind Harmer
0.882
200200DELTA2 CT1
50/50
2.8
200193DELTA CT2
50/50
1.565
200203Y1-065-STG
50/50
5.65
200055ROCKSP 4
50/50
2.035
233971AC1-093 C
Solar/Wind Harmer
0.763
972133AH1-634 GEN
Solar/Wind Harmer
9.641
970695AG2-447 GEN
Solar/Wind Harmer
3.484
233996TM1833_GEN
Solar/Wind Harmer
1.232
233997TMININ_4.2
Solar/Wind Harmer
1.232
232406W1-004 FULL
Solar/Wind Harmer
0.974
232907VN8
Adder
29.201
232914OH NUG3
Adder
8.589
232916OH NUG5
Adder
8.589
972073AH1-586 GEN
Solar/Wind Harmer
9.114
232921TASLEY2G
Adder
5.02
233940AF2-379 C
Solar/Wind Harmer
0.181
233990AG1-397 GEN
Solar/Wind Harmer
1.115
234015AF2-250 C
Solar/Wind Harmer
0.117
233900O-025 C
Adder
1.145
233994AC2-023 GEN
Solar/Wind Harmer
2.614
960671AF2-358 GEN
Solar/Wind Harmer
17.411
232417X3-008 C
Solar/Wind Harmer
1.944
233952AC2-187 GEN
Solar/Wind Harmer
1.094
233918AB1-142 GEN
Solar/Wind Harmer
0.958
233982AB2-133 GEN
Solar/Wind Harmer
4.707
972251AH1-710 GEN
Adder
42.952
228202CUMB CT
Adder
14.237
228711V2-041C
Solar/Wind Harmer
0.518
971553AH1-274 GEN
Solar/Wind Harmer
2.086
230430AE1-229_GEN
Solar/Wind Harmer
7.564
230415AB2-049 C
Solar/Wind Harmer
0.163
228729W2-030 C
Solar/Wind Harmer
0.495
228304LOGAN
Adder
18.654
213497CHSTR7-9
Adder
2.332
219623KINSLEYBEA C
Solar/Wind Harmer
0.364
219766PARADISE C
Solar/Wind Harmer
0.267
219291REEVESSOUT C
Solar/Wind Harmer
0.051
213958STHWK5-6
Adder
2.312
219912AD2-042 GEN
Solar/Wind Harmer
0.676
219236SOUTHERNHQ C
Solar/Wind Harmer
0.057
213560DLW11-12
Adder
2.301
219906AC1-017 C
Solar/Wind Harmer
0.188
213815MOSER1-3
Adder
2.992
219610FLORENCE C
Solar/Wind Harmer
1.167
219348LDSOLAR C
Solar/Wind Harmer
0.505
219221BRL12CT1
Adder
7.52
219223BRL12CT3
Adder
7.52
972281AH1-725 GEN
50/50
137.689
200201DELTA2 CT2
50/50
2.8
200034PCHBTM 2
50/50
16.307
200035PCHBTM 3
50/50
16.434
200205Y1-065-CTG2
50/50
3.258
233987AB2-037 GEN
Solar/Wind Harmer
11.076
971149AH1-027 GEN
Solar/Wind Harmer
3.292
233939AC1-091 C
Solar/Wind Harmer
0.854
233970AC1-092 C
Solar/Wind Harmer
0.854
970545AG2-347 GEN
Solar/Wind Harmer
63.628
233901CHERRYDALE C
Solar/Wind Harmer
1.095
232408W1-005 C
Solar/Wind Harmer
0.974
232410W1-006 C
Solar/Wind Harmer
0.974
972069AH1-584 GEN
Solar/Wind Harmer
8.709
972071AH1-585 GEN
Solar/Wind Harmer
8.709
232918OH NUG7
Adder
8.531
971747AH1-380 GEN
Solar/Wind Harmer
3.483
232905CHERITON_25
Adder
2.386
232926CRISFLD1
Adder
1.909
231940T-011
Adder
0.725
232899W1-062
Adder
9.348
233946AB2-136 GEN
Solar/Wind Harmer
3.879
234036AF2-325 C
Solar/Wind Harmer
0.891
234041AC1-190 GEN
Solar/Wind Harmer
8.703
233984AB2-036 GEN
Solar/Wind Harmer
12.071
232424Y1-079 C
Solar/Wind Harmer
0.545
234014AF1-036_GEN
Solar/Wind Harmer
2.62
231131BLOOM ENRGY
Adder
4.214
233944AB2-135 GEN
Solar/Wind Harmer
5.064
233933AB2-153 GEN
Solar/Wind Harmer
1.087
232416X2-083
Adder
0.433
228251CARLLS#4
Adder
0.543
230433AD2-135 GEN
Solar/Wind Harmer
0.087
230422AE1-104_GEN1
Solar/Wind Harmer
28.951
230425AE1-104_GEN2
Solar/Wind Harmer
28.951
228307PCLP GT
Adder
10.374
230407AD2-065 C
Solar/Wind Harmer
0.113
228304LOGAN
Adder
20.741
972233AH1-701 GEN
Adder
3.593
213589EDDYSTN4
Adder
68.107
213587EDDYSTN3
Adder
68.102
219921AF1-264
Solar/Wind Harmer
0.123
219615MILLCREEK C
Solar/Wind Harmer
0.201
213815MOSER1-3
Adder
2.992
213815MOSER1-3
Adder
2.992
213535CROYDN11
Adder
8.616
20716428NHV_W2-082
Solar/Wind Harmer
1.488
207500AE2-000G1
Solar/Wind Harmer
26.337
207497AE2-000G2
Solar/Wind Harmer
26.337
207507AE2-000G3
Solar/Wind Harmer
26.337
20636128O CRK C2
Adder
5.388
963401AG1-189 GEN
Solar/Wind Harmer
0.961
963391AG1-188 GEN
Solar/Wind Harmer
1.603
20714928UPF_X1-085
Solar/Wind Harmer
0.34
219114HARTZY_C
Solar/Wind Harmer
0.697
20628028LAKEHURS
Adder
0.795
219817TRENTONSOL C
Solar/Wind Harmer
0.92
20641628MLH_W1-032
Solar/Wind Harmer
0.245
20720628TIN_W1-124
Solar/Wind Harmer
0.831
20716928W4-060COL
Solar/Wind Harmer
0.593
924131AB2-057 GEN
Solar/Wind Harmer
0.858
218440SUMMTASSOC C
Solar/Wind Harmer
0.107
20673828FLE_V3-070
Solar/Wind Harmer
0.382
218418LINDEN_G5
Adder
14.325
218419LINDEN_G6
Adder
14.325
972260AH1-715 GEN1
Adder
11.471
207442AE1-156 GEN
Solar/Wind Harmer
0.621
20676128MHD_W3-029
Solar/Wind Harmer
0.399
219036LINDEN_G7
Adder
13.951
219035LINDEN_G8
Adder
13.752
972261AH1-715 GEN2
Adder
13.354
217081WEATEXAS C
Solar/Wind Harmer
0.072
217202FBANKSOLAR C
Solar/Wind Harmer
0.061
20671828STAW2-080
Solar/Wind Harmer
0.088
217201HACKENSOLA C
Solar/Wind Harmer
0.061
972237AH1-703 GEN
Adder
8.439
217206BARNGR HS C
Solar/Wind Harmer
0.026
217086KRNY_131
Adder
7.77
200192DELTA CT1
50/50
1.565
200194DELTA CT3
50/50
1.565
200204Y1-065-CTG1
50/50
3.258
200054ROCKSP 3
50/50
2.078
232901NORTHST
Adder
8.095
233972AC1-094 C
Solar/Wind Harmer
0.645
233998TM1NIN_3.36
Solar/Wind Harmer
1.232
232404W1-003 C
Solar/Wind Harmer
0.974
232434Z2-077 GEN
Solar/Wind Harmer
0.243
232917OH NUG6
Adder
8.55
232915OH NUG4
Adder
8.531
232428Y3-058 C
Solar/Wind Harmer
0.811
971195AH1-057 GEN
Solar/Wind Harmer
1.064
972177AH1-672 GEN
Solar/Wind Harmer
13.061
232919VN10
Adder
2.729
965821AG1-450 GEN
Solar/Wind Harmer
5.061
232426Y1-080 FULL
Solar/Wind Harmer
0.186
970277AG2-181 GEN
Solar/Wind Harmer
4.875
232900DEMECSMY
Adder
8.966
233964AF2-378 GEN
Solar/Wind Harmer
0.124
233954AC2-188 GEN
Solar/Wind Harmer
1.094
233950AC2-186 GEN
Solar/Wind Harmer
0.547
232910NRG_G1
Adder
8.374
234012AE2-112_GEN
Solar/Wind Harmer
2.227
232422X3-066 FULL
Solar/Wind Harmer
0.242
233930AB2-032 GEN
Solar/Wind Harmer
0.806
233915AB1-141 GEN
Solar/Wind Harmer
0.958
231918WEST 1
Adder
3.197
231917EM10
Adder
2.235
228206SHRMN CT
Adder
14.282
228732V1-021 C
Adder
0.163
945431AF1-208 GEN
Solar/Wind Harmer
7.426
970997AG2-616 GEN
Solar/Wind Harmer
8.243
228351V2-046C
Solar/Wind Harmer
1.731
230511AF1-262
Solar/Wind Harmer
0.157
228728W1-130C
Solar/Wind Harmer
0.57
230434AG1-499 GEN
Solar/Wind Harmer
0.498
213497CHSTR7-9
Adder
2.332
213497CHSTR7-9
Adder
2.332
219258KINSLEYDEP C
Solar/Wind Harmer
0.275
219904AC1-010 C
Solar/Wind Harmer
0.321
213958STHWK5-6
Adder
2.312
218660EHAMPSOLAR C
Solar/Wind Harmer
0.148
219287REEVESEAST C
Solar/Wind Harmer
1.141
219686LUMSOLAR_N C
Solar/Wind Harmer
0.172
219907AC1-030 C
Solar/Wind Harmer
0.118
213560DLW11-12
Adder
2.301
219304NAMERICA C
Solar/Wind Harmer
0.262
219222BRL12CT2
Adder
7.52
213611FALLS1-3
Adder
2.968
214194N WALES4
Adder
0.715
20720728JCB_W1-129
Solar/Wind Harmer
0.25
207522AF2-254 C
Solar/Wind Harmer
1.201
207487AE2-000G4
Solar/Wind Harmer
26.337
207445AB1-138_GEN
Solar/Wind Harmer
0.485
20628028LAKEHURS
Adder
1.572
963711AG1-223 GEN
Solar/Wind Harmer
1.235
20714828MDF_W3-079
Solar/Wind Harmer
0.256
219680HOPEWELLV C1
Solar/Wind Harmer
0.063
207454AA2-184 E
Solar/Wind Harmer
0.834
20715228NPK_W1-113
Solar/Wind Harmer
0.359
20742028HF_AC1-207
Solar/Wind Harmer
0.654
217197RE CRAN C
Solar/Wind Harmer
0.448
20635828PARLN1&2
Adder
6.174
20635028RRCT1&2
Adder
9.68
20635128RRCT3&4
Adder
9.344
218428ETC SOLAR C
Solar/Wind Harmer
0.03
217213AMBOY SO C
Solar/Wind Harmer
0.106
972275AH1-722 GEN
Adder
26.334
207528AF2-192 GEN
Solar/Wind Harmer
0.462
20673628F1S_V4-069
Solar/Wind Harmer
0.15
20675428EAM_W2-061
Solar/Wind Harmer
0.158
218449LINSOLAR C
Solar/Wind Harmer
0.839
20676428JCR_X2-075
Solar/Wind Harmer
0.285
217209CENTRL HS C
Solar/Wind Harmer
0.037
217121ECCF
Adder
0.362
217083KRNY_132
Adder
7.753
217208PARK ELE C
Solar/Wind Harmer
0.021
207439AE1-081 C O1
Solar/Wind Harmer
0.05
20674328GAR_V4-001
Solar/Wind Harmer
0.092
20675828AU_W4-064
Solar/Wind Harmer
0.145
971519AH1-257 GEN
Solar/Wind Harmer
2.112
207518AF1-320_GEN
Solar/Wind Harmer
3.063
207437AD2-070 GEN
Solar/Wind Harmer
0.253
20671928W4-073
Solar/Wind Harmer
0.363
966181AG1-487 GEN
Solar/Wind Harmer
3.144
20465127PORT CT
Adder
2.512
208909MACR G3
Adder
133.263
205941AD2-115 GEN
Solar/Wind Harmer
0.764
20467927PC_Q59Y356
Adder
0.696
961301AF2-421 GEN
Solar/Wind Harmer
0.815
963151AG1-164 GEN
Solar/Wind Harmer
0.815
209023WIENIPP1
Adder
8.79
209025WIENIPP3
Adder
4.387
20465527S.RDG CT
Adder
2.274
212266LOR1
Solar/Wind Harmer
0.104
970237AG2-161 GEN
Solar/Wind Harmer
2.794
209010PEIP 1
Adder
0.518
961341AF2-425 GEN
Solar/Wind Harmer
0.792
212174INGE
Adder
0.876
212507AE2-042_GEN
Solar/Wind Harmer
2.341
946731AF1-337 GEN
Solar/Wind Harmer
0.777
209071AE2-133 GEN
Solar/Wind Harmer
1.314
970665AG2-430 GEN
Solar/Wind Harmer
7.698
209018SUNBIPCT
Adder
5.779
972241AH1-705 GEN
Adder
4.441
209008PAXT IPP
Adder
1.602
205967AE2-211_GEN
Solar/Wind Harmer
6.189
20465027TOLNA CT
Adder
2.295
970679AG2-439 GEN
Solar/Wind Harmer
0.956
208923BUSO V4-027
Solar/Wind Harmer
0.248
208856AE1-226 GEN
Solar/Wind Harmer
1.76
200917MEHOOPANY_G
Solar/Wind Harmer
3.086
966131AG1-482 GEN
Solar/Wind Harmer
0.078
316006AB2-029 C
Solar/Wind Helper
0.131
316045AC1-158 PL2
Solar/Wind Helper
4.814
316254AC1-120 GEN1
Solar/Wind Helper
1.233
3147666LOUISA
Solar/Wind Helper
1.045
316192AB2-158 GEN
Solar/Wind Helper
1.754
316337AD2-073 GEN
Solar/Wind Helper
0.39
964211AG1-282 GEN
Solar/Wind Helper
0.344
3141726DUNNSVL
Solar/Wind Helper
1.02
3142416OLDCHRC
Solar/Wind Helper
0.656
3142416OLDCHRC
Solar/Wind Helper
0.251
3138133OCRAN
Solar/Wind Helper
0.151
3141766HARMONY
Solar/Wind Helper
0.05
3142433PROV 92
Solar/Wind Helper
1.004
3143526WINTERP
Solar/Wind Helper
1.303
3142543TWELFTH
Solar/Wind Helper
0.024
3143226MDLTHAN
Solar/Wind Helper
0.25
316159AE1-175 C
Solar/Wind Helper
0.377
316458AB2-190 GEN2
Solar/Wind Helper
1.414
3145336SMITFLD
Solar/Wind Helper
0.981
316294AC1-161 GEN
Solar/Wind Helper
4.478
238148AE2-230_GEN2
Solar/Wind Helper
0.423
316381AD1-082 GEN
Solar/Wind Helper
1.265
316375AC2-012 GEN
Solar/Wind Helper
0.639
316072AD1-144
Solar/Wind Helper
0.278
316388AE2-253 GEN
Solar/Wind Helper
0.925
3146456SLIGO L269
Solar/Wind Helper
0.243
316246AF1-032 C
Solar/Wind Helper
0.277
316336AC2-165 C
Solar/Wind Helper
1.305
3146516WINFALL
Solar/Wind Helper
0.779
3146516WINFALL
Solar/Wind Helper
0.24
315800Z1-036_GEN1
Solar/Wind Helper
1.314
3130156CHOWAN
Solar/Wind Helper
0.238
3145663CRESWEL
Solar/Wind Helper
0.659
316322AB2-045
Solar/Wind Helper
0.26
959561AF2-247 GEN
Solar/Wind Harmer
0.407
20716028EGP_W2-019
Solar/Wind Harmer
0.388
20720828JCB_W4-025
Solar/Wind Harmer
0.379
20715028HAN_X4-015
Solar/Wind Harmer
0.25
20636028O CRK C1
Adder
5.909
971667AH1-334 GEN
Solar/Wind Harmer
2.296
219727YARDVSOLFA C
Solar/Wind Harmer
0.761
20714528FRN_Y2-051
Solar/Wind Harmer
0.246
219276PARKLANDSO C
Solar/Wind Harmer
0.386
219918AC2-009 C
Solar/Wind Harmer
0.051
20716228APLW2-078
Solar/Wind Harmer
0.737
20720528MAN_W1-024
Solar/Wind Harmer
0.212
967451AG2-055 C O1
Solar/Wind Harmer
144.803
219612MATRIX C
Solar/Wind Harmer
0.153
218438BLK ROCK C
Solar/Wind Harmer
0.114
20635828PARLN1&2
Adder
2.796
20635928PARLN3&4
Adder
2.796
20635028RRCT1&2
Adder
9.831
20635128RRCT3&4
Adder
8.15
219908AB1-139 C
Solar/Wind Harmer
0.318
219919AE1-041 FULL
Solar/Wind Harmer
0.034
219249CENTRALDIV C
Solar/Wind Harmer
0.033
20673728F2S_V4-070
Solar/Wind Harmer
0.15
217211CAMDEN ST C
Solar/Wind Harmer
0.02
217186ESSEX_G9
Adder
13.335
217169METRODIV C
Solar/Wind Harmer
0.033
217194REDH C
Solar/Wind Harmer
0.411
20676728BRNX1-095
Solar/Wind Harmer
0.147
207510AF2-138 C
Solar/Wind Harmer
1.488
20674628WNG_W3-110
Solar/Wind Harmer
0.337
971007AG2-625 GEN
Solar/Wind Harmer
2.151
20633028GILCT9
Adder
23.759
966181AG1-487 GEN
Solar/Wind Harmer
0.211
20466127PORT 5CT
Adder
22.166
20465427SHAW CT
Adder
3.223
963161AG1-165 GEN
Solar/Wind Harmer
0.815
209025WIENIPP3
Adder
4.299
963071AG1-156 GEN
Solar/Wind Harmer
2.237
970095AG2-074 GEN
Solar/Wind Harmer
5.076
209027LOR2_Q27
Solar/Wind Harmer
3.639
219620RIDERU C
Solar/Wind Harmer
0.047
20714328BYD_X4-031
Solar/Wind Harmer
0.236
20714428HOW_X1-037
Solar/Wind Harmer
1.031
971521AH1-258 GEN
Solar/Wind Harmer
2.257
20720428HOL_W1-112
Solar/Wind Harmer
0.289
20635928PARLN3&4
Adder
6.174
218455CINNBAY_CGEN
Adder
1.515
218526CNTRALGAS2 C
Solar/Wind Harmer
0.309
218524CNTRALGAS1 C
Solar/Wind Harmer
0.309
20675528CPH_W2-050
Solar/Wind Harmer
0.39
218404KENILWRTH C
Adder
1.089
217167KRNY_14
Adder
7.753
217086KRNY_131
Adder
7.688
217147KRNY_1212
Adder
7.375
217147KRNY_1212
Adder
7.243
217146KRNY_1234
Adder
7.227
217146KRNY_1234
Adder
7.177
966261AG1-495 GEN
Solar/Wind Harmer
1.502
20676328BVR_Y1-020
Solar/Wind Harmer
0.277
207530AG1-191 GEN
Solar/Wind Harmer
1.151
207511W3-106 GEN
Solar/Wind Harmer
0.549
20674828DL_W4-046
Solar/Wind Harmer
0.541
971009AG2-626 GEN
Solar/Wind Harmer
1.372
20675928HOL_W4-097
Solar/Wind Harmer
0.11
207408W3-077 C
Solar/Wind Harmer
0.425
20675728RH_W2-091
Solar/Wind Harmer
0.287
207484AF2-139 C O1
Solar/Wind Harmer
0.424
20675128HRM_W1-127
Solar/Wind Harmer
0.143
20462827N BANGR8
Adder
0.6
966421AG1-511 GEN
Solar/Wind Harmer
7.194
209116AE2-175 GEN
Solar/Wind Harmer
3.427
961261AF2-417 GEN
Solar/Wind Harmer
0.817
209026WIENIPP4
Adder
4.343
20486527WR_V4-052
Adder
0.886
208862AG1-362 C
Solar/Wind Harmer
0.661
209045AE2-271 GEN
Solar/Wind Harmer
13.227
959431AF2-234 GEN
Solar/Wind Harmer
1.552
964051AG1-259 GEN
Solar/Wind Harmer
1.04
964061AG1-260 GEN
Solar/Wind Harmer
1.04
959421AF2-233 GEN
Solar/Wind Harmer
0.776
209030FRFA O01
Adder
0.192
205951AE1-129_GEN
Solar/Wind Harmer
8.359
205932AD2-116_GEN
Solar/Wind Harmer
0.58
205956AE1-196_GEN
Solar/Wind Harmer
0.58
960921AF2-383 GEN
Solar/Wind Harmer
0.194
20465027TOLNA CT
Adder
2.386
960921AF2-383 GEN
Solar/Wind Harmer
1.494
205943AE1-185 GEN
Solar/Wind Harmer
0.574
20390726Y2-042
Adder
2.287
20334726NME_Y1-047
Adder
2.073
20464627HAM CT
Adder
1.899
3138216PACIFIC
Solar/Wind Helper
0.049
316411AF1-147_GEN1
Solar/Wind Helper
0.978
316415AF1-147_GEN2
Solar/Wind Helper
0.978
3141426STAFORD
Solar/Wind Helper
0.062
316164AC1-076 GEN
Solar/Wind Helper
1.282
316223AC1-118
Solar/Wind Helper
0.395
3141813NORNECK
Solar/Wind Helper
0.256
3141783LANCAST
Solar/Wind Helper
0.151
3141783LANCAST
Solar/Wind Helper
0.101
316312AB1-027
Solar/Wind Helper
0.481
3138133OCRAN
Solar/Wind Helper
0.076
3141913WHIT STONE
Solar/Wind Helper
0.252
3146776BUCKING
Solar/Wind Helper
0.093
316023GEN1_S
Solar/Wind Helper
0.886
3146206CASHIE
Solar/Wind Helper
0.233
3145893MURPHYS
Solar/Wind Helper
0.93
3146926FARMVIL
Solar/Wind Helper
0.139
3146173TUNIS
Solar/Wind Helper
0.232
3145683EARLEYS
Solar/Wind Helper
0.231
3146263WOODLND
Solar/Wind Helper
0.23
217083KRNY_132
Adder
7.704
217204WCALDSOLAR C
Solar/Wind Harmer
0.061
20674528F3S_W2-016
Solar/Wind Harmer
1.176
20676228FRD_X1-012
Solar/Wind Harmer
0.494
207471AF2-354 C
Solar/Wind Harmer
0.428
20674928WA_W3-044
Solar/Wind Harmer
0.404
964851AG1-348 GEN
Solar/Wind Harmer
1.472
20634528N27_Y2-018
Solar/Wind Harmer
0.225
20674128FR_U2-059
Solar/Wind Harmer
0.154
20465127PORT CT
Adder
3.334
966111AG1-480 GEN
Solar/Wind Harmer
0.072
966111AG1-480 GEN
Solar/Wind Harmer
2.751
211065PSPA IPP
Solar/Wind Harmer
0.375
211065PSPA IPP
Solar/Wind Harmer
0.375
20465527S.RDG CT
Adder
2.2
208972BECR K09
Solar/Wind Harmer
0.853
961541AF2-445A GEN
Solar/Wind Harmer
2.614
209029WAYMART-WD
Solar/Wind Harmer
2.315
209009PEIP 2
Adder
6.287
209010PEIP 1
Adder
2.849
209010PEIP 1
Adder
0.417
961431AF2-434 GEN
Solar/Wind Harmer
0.791
209054AE2-059 GEN
Solar/Wind Harmer
1.321
209059AE2-084 GEN
Solar/Wind Harmer
1.951
946751AF1-339 GEN
Solar/Wind Harmer
0.777
209130AF1-271A GEN
Solar/Wind Harmer
2.181
20478527GLRA_Q45
Adder
0.264
209137AF2-361 C
Solar/Wind Harmer
2.172
208835TUHI V3-051
Solar/Wind Harmer
0.041
208835TUHI V3-051
Solar/Wind Harmer
0.041
20464827MOUNT CT
Adder
1.955
20464827MOUNT CT
Adder
1.897
226929AD2-058 GEN
Solar/Wind Helper
0.119
316447AC1-158 HLD
Solar/Wind Helper
3.31
315651AD1-115 GEN
Solar/Wind Helper
0.906
316468AD1-105 GEN
Solar/Wind Helper
1.29
966001AG1-469 GEN
Solar/Wind Helper
0.277
316077AC2-138 C
Solar/Wind Helper
0.24
966871AG1-558 GEN
Solar/Wind Helper
0.343
238175AF1-290_GEN
Solar/Wind Helper
0.133
316487AF1-042 GEN
Solar/Wind Helper
0.256
316075AC2-137 C
Solar/Wind Helper
0.383
238169AE2-226 GEN1
Solar/Wind Helper
0.612
238170AE2-226 GEN2
Solar/Wind Helper
0.612
3143526WINTERP
Solar/Wind Helper
1.303
3142946ENON
Solar/Wind Helper
0.025
316240AF1-291 C
Solar/Wind Helper
0.333
316033AB2-134 GEN
Solar/Wind Helper
0.849
315697AD1-025 GEN
Solar/Wind Helper
2.822
316236AE1-162_GEN
Solar/Wind Helper
0.329
316036AC1-147 C
Solar/Wind Helper
0.372
3142956BIRDNECK
Solar/Wind Helper
0.164
316316AC1-027 C
Solar/Wind Helper
0.385
316185AD1-033 GEN
Solar/Wind Helper
1.145
3145506HICKORY
Solar/Wind Helper
0.973
3145506HICKORY
Solar/Wind Helper
0.584
3145506HICKORY
Solar/Wind Helper
0.146
316339AD2-160 GEN
Solar/Wind Helper
0.925
316018AA1-139 ULT2
Solar/Wind Helper
1.044
316017AA1-139 ULT1
Solar/Wind Helper
1.11
3137176SLIGO L2192
Solar/Wind Helper
0.966
3130086AYDLETT
Solar/Wind Helper
0.97
3146386ELIZ CT
Solar/Wind Helper
0.242
316431W1029_GEN1
Solar/Wind Helper
0.972
316433W1029_GEN2
Solar/Wind Helper
0.972
3146516WINFALL
Solar/Wind Helper
0.24
3146516WINFALL
Solar/Wind Helper
0.24
3146516WINFALL
Solar/Wind Helper
0.24
3146626S HERTFORD
Solar/Wind Helper
0.24
3146626S HERTFORD
Solar/Wind Helper
0.24
3144356SAPONY
Solar/Wind Helper
0.43
315742AE1-103 GEN
Solar/Wind Helper
0.384
3146776BUCKING
Solar/Wind Helper
0.931
3146776BUCKING
Solar/Wind Helper
0.075
3145893MURPHYS
Solar/Wind Helper
0.334
3145893MURPHYS
Solar/Wind Helper
0.419
3146173TUNIS
Solar/Wind Helper
0.232
3146173TUNIS
Solar/Wind Helper
0.232
316181AB2-040 GEN
Solar/Wind Helper
1.65
3142666NORTHAMPTON
Solar/Wind Helper
0.229
3142666NORTHAMPTON
Solar/Wind Helper
0.229
3142666NORTHAMPTON
Solar/Wind Helper
0.229
3142666NORTHAMPTON
Solar/Wind Helper
0.138
3132123MT JACKSON
Solar/Wind Helper
0.717
316426AA2-053 GEN
Solar/Wind Helper
1.307
315821AE2-092 GEN
Solar/Wind Helper
2.12
3145593CAROLNA
Solar/Wind Helper
0.229
3145593CAROLNA
Solar/Wind Helper
0.229
3147133PAMPLIN
Solar/Wind Helper
0.229
3147133PAMPLIN
Solar/Wind Helper
0.183
3145796HORNRTN
Solar/Wind Helper
0.683
316034AC1-036 C
Solar/Wind Helper
0.237
3145933PARMELE
Solar/Wind Helper
0.451
3145933PARMELE
Solar/Wind Helper
0.225
316274AC1-208 GEN
Solar/Wind Helper
1.372
3145963POPLR C
Solar/Wind Helper
0.229
316190AA2-174 GEN
Solar/Wind Helper
0.015
316011AB1-132 GEN
Solar/Wind Helper
2.465
3145823KELFORD
Solar/Wind Helper
0.229
316174AB2-169 GEN
Solar/Wind Helper
0.582
3145783HORNRTN
Solar/Wind Helper
0.228
3145796HORNRTN
Solar/Wind Helper
0.751
3145796HORNRTN
Solar/Wind Helper
0.228
3147983MERCK5
Solar/Wind Helper
0.09
316212AC1-099_GEN
Solar/Wind Helper
1.012
316129AC1-054 GEN
Solar/Wind Helper
1.117
316237AB2-079_GEN
Solar/Wind Helper
0.302
3145746EVERETS
Solar/Wind Helper
0.224
3145746EVERETS
Solar/Wind Helper
0.224
315687AD1-152 GEN
Solar/Wind Helper
1.2
315722AD1-056 GEN
Solar/Wind Helper
1.201
316059AD1-063 C
Solar/Wind Helper
0.253
957601AF2-054 GEN
Solar/Wind Helper
0.337
3141873WAN 176
Solar/Wind Helper
0.05
315662AE1-191 GEN
Solar/Wind Helper
1.351
315666AE1-190 GEN
Solar/Wind Helper
0.338
3143873LANEXA
Solar/Wind Helper
0.151
316233AE1-074 FULL
Solar/Wind Helper
0.383
957831AF2-077 GEN
Solar/Wind Helper
0.336
316132AB2-190 GEN1
Solar/Wind Helper
1.414
316369SG1_INVT
Solar/Wind Helper
1.187
3143316POE
Solar/Wind Helper
0.97
238152AF2-075_GEN
Solar/Wind Helper
0.601
23546401DTGZ2-030
Solar/Wind Helper
0.076
316349AD2-085 GEN
Solar/Wind Helper
1.111
316305AF2-043 C
Solar/Wind Helper
0.326
319010AE1-072 C
Solar/Wind Helper
2.772
313526AB2-022
Solar/Wind Helper
0.368
3146486SUNBURY
Solar/Wind Helper
0.241
3146486SUNBURY
Solar/Wind Helper
0.241
316321Z2-027
Solar/Wind Helper
0.367
3145176PASQUOTANK
Solar/Wind Helper
0.15
316315AB2-025 C
Solar/Wind Helper
0.365
315611Z1-036_GEN2
Solar/Wind Helper
1.314
3130156CHOWAN
Solar/Wind Helper
0.238
3130156CHOWAN
Solar/Wind Helper
0.238
315816AE2-034 GEN
Solar/Wind Helper
1.076
3130546PLYMOUTH
Solar/Wind Helper
0.234
315732AD1-074 GEN1
Solar/Wind Helper
2.67
315733AD1-074 GEN2
Solar/Wind Helper
2.67
315735AD1-075 GEN1
Solar/Wind Helper
1.334
3146206CASHIE
Solar/Wind Helper
0.233
3145893MURPHYS
Solar/Wind Helper
0.628
3145893MURPHYS
Solar/Wind Helper
0.233
3138266HYDRAULIC
Solar/Wind Helper
0.01
3138266HYDRAULIC
Solar/Wind Helper
0.007
3145513AHOSKIE
Solar/Wind Helper
0.104
961941AG1-037 GEN
Solar/Wind Helper
0.078
3145513AHOSKIE
Solar/Wind Helper
0.231
946281AF1-292 GEN
Solar/Wind Helper
0.232
3146043SEABORD
Solar/Wind Helper
0.231
3145683EARLEYS
Solar/Wind Helper
0.461
3145683EARLEYS
Solar/Wind Helper
0.231
3145683EARLEYS
Solar/Wind Helper
0.231
315607AA1-063A GEN
Solar/Wind Helper
1.316
316087AB2-174 GEN
Solar/Wind Helper
1.61
3137643SOCKMAN
Solar/Wind Helper
0.916
3145796HORNRTN
Solar/Wind Helper
0.729
3145796HORNRTN
Solar/Wind Helper
0.091
3146033SCOT NK
Solar/Wind Helper
0.909
3144303KENBRDG
Solar/Wind Helper
0.181
316239AB2-077_GEN
Solar/Wind Helper
0.302
316238AB2-078_GEN
Solar/Wind Helper
0.302
3148133STUARTS
Solar/Wind Helper
0.135
3148013FISHERV
Solar/Wind Helper
0.129
316005AA1-067
Solar/Wind Helper
0.255
3145746EVERETS
Solar/Wind Helper
0.89
3145746EVERETS
Solar/Wind Helper
0.224
3145746EVERETS
Solar/Wind Helper
0.224
3145746EVERETS
Solar/Wind Helper
0.224
209022WHFR IPP
Adder
2.612
961331AF2-424 GEN
Solar/Wind Harmer
0.792
961421AF2-433 GEN
Solar/Wind Harmer
0.791
957921AF2-086 GEN
Solar/Wind Harmer
0.769
209142AF1-226 GEN
Solar/Wind Harmer
4.576
209093AE2-110 GEN
Solar/Wind Harmer
1.976
209120AE2-241 GEN
Solar/Wind Harmer
2.615
972245AH1-707 GEN
Adder
4.267
946691AF1-333 GEN
Solar/Wind Harmer
0.777
946741AF1-338 GEN
Solar/Wind Harmer
0.777
972221AH1-695 GEN
Adder
108.686
209067AE2-060 GEN
Solar/Wind Harmer
1.123
966131AG1-482 GEN
Solar/Wind Harmer
1.725
227287AC2-120 GEN
Solar/Wind Helper
0.414
226910AB2-157 C
Solar/Wind Helper
0.017
3141196NOKESVL
Solar/Wind Helper
1.134
316044AC1-158 PL1
Solar/Wind Helper
1.504
316450AC1-158 RIC
Solar/Wind Helper
0.401
316170AC1-121 GEN2
Solar/Wind Helper
0.411
966881AG1-559 GEN
Solar/Wind Helper
0.355
3132273ORANGE
Solar/Wind Helper
0.053
3147666LOUISA
Solar/Wind Helper
0.601
3141906WESTMOR
Solar/Wind Helper
0.104
316473AC1-191 GEN
Solar/Wind Helper
1.555
316404AE1-155 C
Solar/Wind Helper
2.148
316484AD2-074 GEN
Solar/Wind Helper
0.49
316156AD2-030 GEN
Solar/Wind Helper
0.379
316280AD1-041 GEN
Solar/Wind Helper
0.844
3142946ENON
Solar/Wind Helper
0.084
316382AG1-145 C
Solar/Wind Helper
0.334
315839AE2-212 C
Solar/Wind Helper
0.332
3145336SMITFLD
Solar/Wind Helper
0.098
315773AC2-141 GEN
Solar/Wind Helper
5.271
238147AE2-230_GEN1
Solar/Wind Helper
0.421
238149AF1-291A_GEN
Solar/Wind Helper
0.12
3144536CHRHLND
Solar/Wind Helper
0.037
3144873MCLAUGH
Solar/Wind Helper
0.006
316313AB2-026
Solar/Wind Helper
0.371
316258AE1-075 C
Solar/Wind Helper
0.334
316405AF2-144 C
Solar/Wind Helper
0.278
3146456SLIGO L269
Solar/Wind Helper
0.243
237061AD1-155 GEN
Solar/Wind Helper
0.046
316320Y1-086
Solar/Wind Helper
0.108
316435W1029_GEN3
Solar/Wind Helper
0.972
3146516WINFALL
Solar/Wind Helper
0.24
3146626S HERTFORD
Solar/Wind Helper
0.24
3145273HOLLAND
Solar/Wind Helper
0.18
3146376EDENTON
Solar/Wind Helper
0.238
315614AA2-178 GEN
Solar/Wind Helper
1.435
315737AD1-076 GEN
Solar/Wind Helper
2.283
3146776BUCKING
Solar/Wind Helper
0.084
316365GEN2_N
Solar/Wind Helper
0.886
3146206CASHIE
Solar/Wind Helper
0.233
3145893MURPHYS
Solar/Wind Helper
0.083
3145893MURPHYS
Solar/Wind Helper
0.233
3146926FARMVIL
Solar/Wind Helper
0.139
3146173TUNIS
Solar/Wind Helper
0.232
3156021HOLLOMANSOL
Solar/Wind Helper
1.761
316463AE2-346 GEN
Solar/Wind Helper
0.211
316140AB2-099
Solar/Wind Helper
0.088
966621AG1-532 GEN
Solar/Wind Helper
0.21
3146263WOODLND
Solar/Wind Helper
0.23
942461AE2-259 GEN
Solar/Wind Helper
1.552
313506AB2-031 GEN
Solar/Wind Helper
1.044
3142666NORTHAMPTON
Solar/Wind Helper
0.229
3145963POPLR C
Solar/Wind Helper
0.229
3147043LAWRENC
Solar/Wind Helper
0.137
316317KELFORD C
Solar/Wind Helper
0.195
3145823KELFORD
Solar/Wind Helper
0.229
3147133PAMPLIN
Solar/Wind Helper
0.718
316478AD1-087 GEN
Solar/Wind Helper
1.115
316486AD2-202 GEN
Solar/Wind Helper
0.326
3145796HORNRTN
Solar/Wind Helper
0.911
3145796HORNRTN
Solar/Wind Helper
0.228
315785AD2-033 C
Solar/Wind Helper
2.64
316210AC1-098 GEN
Solar/Wind Helper
1.822
3145933PARMELE
Solar/Wind Helper
0.225
316499AE2-029_GEN
Solar/Wind Helper
0.759
316131AB2-060 GEN
Solar/Wind Helper
1.371
3148013FISHERV
Solar/Wind Helper
0.225
3145746EVERETS
Solar/Wind Helper
0.224
3145746EVERETS
Solar/Wind Helper
0.224
315724AD1-057 GEN
Solar/Wind Helper
0.66
316327AA2-057 GEN
Solar/Wind Helper
1.27
HAMLETPJM->LTFIMP_HAMLET
CLTF
5.051
G-007ALTFEXP_G-007A->PJM
CMTX
42.753
CBM NorthLTFEXP_CBM-N->PJM
CBM
65.866
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
3.496
BlueGrassPJM->LTFIMP_BlueG
CLTF
10.905
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
112.974
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.905
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
16.734

Details for CNASTONE-BRIGHTON 500.0 kV Ckt 1 line l/o AP_P1-2_PE-500-3835T_SRT-A


Base Case Flowgate

Area:PJM
Facility Description:
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-500-3835T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:129.83 %
Rating:3098.0 MVA
Rating Type:B
MVA to Mitigate:4022.12
MW Contribution:4.58
Bus #Bus NameTypeMW Contribution
200192DELTA CT1
50/50
1.562
200194DELTA CT3
50/50
1.562
200204Y1-065-CTG1
50/50
3.252
200054ROCKSP 3
50/50
2.074
232901NORTHST
Adder
8.077
233972AC1-094 C
Solar/Wind Harmer
0.305
233998TM1NIN_3.36
Solar/Wind Harmer
0.001
232404W1-003 C
Solar/Wind Harmer
0.628
232434Z2-077 GEN
Solar/Wind Harmer
0.041
232917OH NUG6
Adder
8.531
232915OH NUG4
Adder
8.512
971195AH1-057 GEN
Solar/Wind Harmer
0.606
232428Y3-058 C
Solar/Wind Harmer
0.001
972177AH1-672 GEN
Solar/Wind Harmer
9.879
232919VN10
Adder
2.722
232426Y1-080 FULL
Solar/Wind Harmer
0
970277AG2-181 GEN
Solar/Wind Harmer
0.566
965821AG1-450 GEN
Solar/Wind Harmer
5.05
232900DEMECSMY
Adder
8.946
233964AF2-378 GEN
Solar/Wind Harmer
0
233954AC2-188 GEN
Solar/Wind Harmer
0.001
233950AC2-186 GEN
Solar/Wind Harmer
0.001
232910NRG_G1
Adder
8.355
234012AE2-112_GEN
Solar/Wind Harmer
2.245
232422X3-066 FULL
Solar/Wind Harmer
0.081
233930AB2-032 GEN
Solar/Wind Harmer
0.925
233915AB1-141 GEN
Solar/Wind Harmer
0.247
231918WEST 1
Adder
3.189
231917EM10
Adder
2.23
228206SHRMN CT
Adder
14.248
228732V1-021 C
Adder
0.162
945431AF1-208 GEN
Solar/Wind Harmer
5.168
970997AG2-616 GEN
Solar/Wind Harmer
6.187
228351V2-046C
Solar/Wind Harmer
0.001
230511AF1-262
Solar/Wind Harmer
0
228728W1-130C
Solar/Wind Harmer
0
230434AG1-499 GEN
Solar/Wind Harmer
0.001
213497CHSTR7-9
Adder
2.326
213497CHSTR7-9
Adder
2.326
219258KINSLEYDEP C
Solar/Wind Harmer
0
219904AC1-010 C
Solar/Wind Harmer
0
213958STHWK5-6
Adder
2.306
218660EHAMPSOLAR C
Solar/Wind Harmer
0
219287REEVESEAST C
Solar/Wind Harmer
0
219686LUMSOLAR_N C
Solar/Wind Harmer
0
219907AC1-030 C
Solar/Wind Harmer
0
213560DLW11-12
Adder
2.295
219304NAMERICA C
Solar/Wind Harmer
0.077
219222BRL12CT2
Adder
7.501
972281AH1-725 GEN
50/50
137.48
200201DELTA2 CT2
50/50
2.795
200034PCHBTM 2
50/50
16.275
200035PCHBTM 3
50/50
16.401
200205Y1-065-CTG2
50/50
3.252
233987AB2-037 GEN
Solar/Wind Harmer
0.01
971149AH1-027 GEN
Solar/Wind Harmer
3.032
233939AC1-091 C
Solar/Wind Harmer
0.001
233970AC1-092 C
Solar/Wind Harmer
0.001
970545AG2-347 GEN
Solar/Wind Harmer
24.491
233901CHERRYDALE C
Solar/Wind Harmer
0.001
232408W1-005 C
Solar/Wind Harmer
0.628
232410W1-006 C
Solar/Wind Harmer
0.628
972069AH1-584 GEN
Solar/Wind Harmer
6.062
972071AH1-585 GEN
Solar/Wind Harmer
6.062
232918OH NUG7
Adder
8.512
971747AH1-380 GEN
Solar/Wind Harmer
2.425
232905CHERITON_25
Adder
2.38
232926CRISFLD1
Adder
1.904
231940T-011
Adder
0.724
232899W1-062
Adder
9.327
233946AB2-136 GEN
Solar/Wind Harmer
0.004
234036AF2-325 C
Solar/Wind Harmer
0.001
234041AC1-190 GEN
Solar/Wind Harmer
7.067
233984AB2-036 GEN
Solar/Wind Harmer
7.028
232424Y1-079 C
Solar/Wind Harmer
0.001
234014AF1-036_GEN
Solar/Wind Harmer
2.245
231131BLOOM ENRGY
Adder
4.204
233944AB2-135 GEN
Solar/Wind Harmer
0.005
233933AB2-153 GEN
Solar/Wind Harmer
0.001
232416X2-083
Adder
0.432
228251CARLLS#4
Adder
0.541
230422AE1-104_GEN1
Solar/Wind Harmer
11.594
230425AE1-104_GEN2
Solar/Wind Harmer
11.594
228307PCLP GT
Adder
10.349
230407AD2-065 C
Solar/Wind Harmer
0
228304LOGAN
Adder
20.69
972233AH1-701 GEN
Adder
3.584
213589EDDYSTN4
Adder
67.939
213587EDDYSTN3
Adder
67.934
219921AF1-264
Solar/Wind Harmer
0
219615MILLCREEK C
Solar/Wind Harmer
0
213815MOSER1-3
Adder
2.984
213815MOSER1-3
Adder
2.984
213535CROYDN11
Adder
8.595
20716428NHV_W2-082
Solar/Wind Harmer
0
200202DELTA2 ST
50/50
4.743
200195DELTA ST
50/50
2.413
200052ROCKSP 1
50/50
2.054
200053ROCKSP 2
50/50
2.01
234033AF1-007_GEN
Solar/Wind Harmer
-0.001
233973AC2-185 C
Solar/Wind Harmer
0.001
232904IR4
Adder
78.439
233923SMA
Solar/Wind Harmer
0.005
232432Z2-076 GEN
Solar/Wind Harmer
0.013
232912OH NUG1
Adder
8.569
232913OH NUG2
Adder
8.455
232920IR10
Adder
3.066
233990AG1-397 GEN
Solar/Wind Harmer
-0.155
233955AB2-172 GEN
Solar/Wind Harmer
0.003
232813VAUGHN
Adder
0.57
233968AD2-076_GEN
Solar/Wind Harmer
2.245
970597AG2-380 GEN
Solar/Wind Harmer
4.021
231906DC3 NUG
Adder
13.506
231902DC CT7
Adder
10.797
231907DC10
Adder
3.372
232436AB1-176 C
Solar/Wind Harmer
0
971983AH1-536 GEN
Solar/Wind Harmer
1.706
233935AB2-179 C
Solar/Wind Harmer
1.318
231919CHRIST1
Adder
4.194
231920CHRIST2
Adder
4.101
970453AG2-297 GEN
Solar/Wind Harmer
2.191
228260V4-054C
Solar/Wind Harmer
0
228309CCLP NUG
Adder
22.178
228309CCLP NUG
Adder
21.097
972141AH1-641 GEN
Solar/Wind Harmer
2.869
964001AG1-254 GEN
Solar/Wind Harmer
0.333
971011AG2-627 GEN
Solar/Wind Harmer
4.58
971535AH1-265 GEN
Solar/Wind Harmer
2.355
227927V4-067C
Solar/Wind Harmer
0
228754AB1-001 C
Solar/Wind Harmer
0
219272CLEANLIGHT C
Solar/Wind Harmer
0
213942SCHUYLKILL
Adder
3.017
213942SCHUYLKILL
Adder
2.307
213957STHWK3-4
Adder
2.306
213957STHWK3-4
Adder
2.306
219914AD2-027 C
Solar/Wind Harmer
0.001
219688LUMSOLAR_S C
Solar/Wind Harmer
0
213561DLWR9-10
Adder
3.001
213561DLWR9-10
Adder
2.295
219607WPEMNERT C
Solar/Wind Harmer
0
219224BRL12CT4
Adder
7.501
214067T20SOLAR
Solar/Wind Harmer
0
213611FALLS1-3
Adder
2.961
213611FALLS1-3
Adder
2.961
20717128DIX_Z2-102
Solar/Wind Harmer
0
20715728PEM_W1-119
Solar/Wind Harmer
0.001
20715828PEM_W1-120
Solar/Wind Harmer
0.001
970025AG2-016 GEN
Solar/Wind Harmer
1.527
971189AH1-054 GEN
Solar/Wind Harmer
0.636
207459AE1-142 C O1
Solar/Wind Harmer
0.001
20714328BYD_X4-031
Solar/Wind Harmer
0.127
20714428HOW_X1-037
Solar/Wind Harmer
0.001
971521AH1-258 GEN
Solar/Wind Harmer
1.455
20720428HOL_W1-112
Solar/Wind Harmer
0
20635928PARLN3&4
Adder
6.157
218455CINNBAY_CGEN
Adder
1.511
218526CNTRALGAS2 C
Solar/Wind Harmer
0.637
218524CNTRALGAS1 C
Solar/Wind Harmer
0.636
218404KENILWRTH C
Adder
1.086
217167KRNY_14
Adder
7.733
217086KRNY_131
Adder
7.667
217147KRNY_1212
Adder
7.355
217147KRNY_1212
Adder
7.224
217146KRNY_1234
Adder
7.207
217146KRNY_1234
Adder
7.158
20676328BVR_Y1-020
Solar/Wind Harmer
0
207530AG1-191 GEN
Solar/Wind Harmer
0.001
207511W3-106 GEN
Solar/Wind Harmer
0.272
20674828DL_W4-046
Solar/Wind Harmer
0
971009AG2-626 GEN
Solar/Wind Harmer
0.884
20675928HOL_W4-097
Solar/Wind Harmer
0
207408W3-077 C
Solar/Wind Harmer
0
20675728RH_W2-091
Solar/Wind Harmer
0.001
207484AF2-139 C O1
Solar/Wind Harmer
0
20675128HRM_W1-127
Solar/Wind Harmer
0
20462827N BANGR8
Adder
0.598
966421AG1-511 GEN
Solar/Wind Harmer
5.005
209116AE2-175 GEN
Solar/Wind Harmer
0.006
209026WIENIPP4
Adder
4.331
20486527WR_V4-052
Adder
0.883
208862AG1-362 C
Solar/Wind Harmer
0.49
209045AE2-271 GEN
Solar/Wind Harmer
9.207
209030FRFA O01
Adder
0.191
205932AD2-116_GEN
Solar/Wind Harmer
0.073
205956AE1-196_GEN
Solar/Wind Harmer
0.025
20465027TOLNA CT
Adder
2.366
960921AF2-383 GEN
Solar/Wind Harmer
1.674
205943AE1-185 GEN
Solar/Wind Harmer
0.025
20390726Y2-042
Adder
2.28
20334726NME_Y1-047
Adder
2.067
3138216PACIFIC
Solar/Wind Helper
0.049
316411AF1-147_GEN1
Solar/Wind Helper
0.975
316415AF1-147_GEN2
Solar/Wind Helper
0.975
3141426STAFORD
Solar/Wind Helper
0.062
316164AC1-076 GEN
Solar/Wind Helper
1.279
316223AC1-118
Solar/Wind Helper
0.394
3141813NORNECK
Solar/Wind Helper
0.255
3141783LANCAST
Solar/Wind Helper
0.151
3141783LANCAST
Solar/Wind Helper
0.101
316312AB1-027
Solar/Wind Helper
0.48
3138133OCRAN
Solar/Wind Helper
0.075
3141913WHIT STONE
Solar/Wind Helper
0.251
316059AD1-063 C
Solar/Wind Helper
0.253
315662AE1-191 GEN
Solar/Wind Helper
1.348
315666AE1-190 GEN
Solar/Wind Helper
0.337
957601AF2-054 GEN
Solar/Wind Helper
0.336
3141873WAN 176
Solar/Wind Helper
0.05
3143873LANEXA
Solar/Wind Helper
0.15
316233AE1-074 FULL
Solar/Wind Helper
0.382
957831AF2-077 GEN
Solar/Wind Helper
0.335
316132AB2-190 GEN1
Solar/Wind Helper
1.41
316369SG1_INVT
Solar/Wind Helper
1.184
3143316POE
Solar/Wind Helper
0.967
238152AF2-075_GEN
Solar/Wind Helper
0.6
23546401DTGZ2-030
Solar/Wind Helper
0.076
316349AD2-085 GEN
Solar/Wind Helper
1.108
319010AE1-072 C
Solar/Wind Helper
2.765
316305AF2-043 C
Solar/Wind Helper
0.325
313526AB2-022
Solar/Wind Helper
0.367
3146486SUNBURY
Solar/Wind Helper
0.241
3146486SUNBURY
Solar/Wind Helper
0.241
316321Z2-027
Solar/Wind Helper
0.367
3145176PASQUOTANK
Solar/Wind Helper
0.149
316315AB2-025 C
Solar/Wind Helper
0.364
315611Z1-036_GEN2
Solar/Wind Helper
1.31
3130156CHOWAN
Solar/Wind Helper
0.237
3130156CHOWAN
Solar/Wind Helper
0.237
315816AE2-034 GEN
Solar/Wind Helper
1.074
3130546PLYMOUTH
Solar/Wind Helper
0.233
315732AD1-074 GEN1
Solar/Wind Helper
2.662
315733AD1-074 GEN2
Solar/Wind Helper
2.662
315735AD1-075 GEN1
Solar/Wind Helper
1.331
3146206CASHIE
Solar/Wind Helper
0.232
3145893MURPHYS
Solar/Wind Helper
0.626
3145893MURPHYS
Solar/Wind Helper
0.232
3138266HYDRAULIC
Solar/Wind Helper
0.01
3138266HYDRAULIC
Solar/Wind Helper
0.007
3145513AHOSKIE
Solar/Wind Helper
0.103
961941AG1-037 GEN
Solar/Wind Helper
0.078
3145513AHOSKIE
Solar/Wind Helper
0.231
946281AF1-292 GEN
Solar/Wind Helper
0.231
3146043SEABORD
Solar/Wind Helper
0.23
3145683EARLEYS
Solar/Wind Helper
0.46
3145683EARLEYS
Solar/Wind Helper
0.23
3145683EARLEYS
Solar/Wind Helper
0.23
315607AA1-063A GEN
Solar/Wind Helper
1.312
316087AB2-174 GEN
Solar/Wind Helper
1.606
3137643SOCKMAN
Solar/Wind Helper
0.914
3145796HORNRTN
Solar/Wind Helper
0.727
3145796HORNRTN
Solar/Wind Helper
0.091
3146033SCOT NK
Solar/Wind Helper
0.906
3144303KENBRDG
Solar/Wind Helper
0.181
316239AB2-077_GEN
Solar/Wind Helper
0.301
316238AB2-078_GEN
Solar/Wind Helper
0.301
3148133STUARTS
Solar/Wind Helper
0.134
3148013FISHERV
Solar/Wind Helper
0.129
316005AA1-067
Solar/Wind Helper
0.255
3145746EVERETS
Solar/Wind Helper
0.887
3145746EVERETS
Solar/Wind Helper
0.223
3145746EVERETS
Solar/Wind Helper
0.223
3145746EVERETS
Solar/Wind Helper
0.223
207500AE2-000G1
Solar/Wind Harmer
10.546
207497AE2-000G2
Solar/Wind Harmer
10.546
207507AE2-000G3
Solar/Wind Harmer
10.546
20636128O CRK C2
Adder
5.374
20714928UPF_X1-085
Solar/Wind Harmer
0
219114HARTZY_C
Solar/Wind Harmer
0
20628028LAKEHURS
Adder
0.793
20720628TIN_W1-124
Solar/Wind Harmer
0.001
20716928W4-060COL
Solar/Wind Harmer
0
218440SUMMTASSOC C
Solar/Wind Harmer
0
20673828FLE_V3-070
Solar/Wind Harmer
0
218418LINDEN_G5
Adder
14.287
218419LINDEN_G6
Adder
14.287
972260AH1-715 GEN1
Adder
11.44
207442AE1-156 GEN
Solar/Wind Harmer
0.05
20676128MHD_W3-029
Solar/Wind Harmer
0
219036LINDEN_G7
Adder
13.914
219035LINDEN_G8
Adder
13.715
972261AH1-715 GEN2
Adder
13.319
20671828STAW2-080
Solar/Wind Harmer
0
972237AH1-703 GEN
Adder
8.417
217086KRNY_131
Adder
7.749
217083KRNY_132
Adder
7.683
20674528F3S_W2-016
Solar/Wind Harmer
0
20676228FRD_X1-012
Solar/Wind Harmer
0.001
20674928WA_W3-044
Solar/Wind Harmer
0.001
20674128FR_U2-059
Solar/Wind Harmer
0
20465127PORT CT
Adder
3.325
966111AG1-480 GEN
Solar/Wind Harmer
2.815
211065PSPA IPP
Solar/Wind Harmer
0
211065PSPA IPP
Solar/Wind Harmer
0
20465527S.RDG CT
Adder
2.192
208972BECR K09
Solar/Wind Harmer
0
961541AF2-445A GEN
Solar/Wind Harmer
1.806
209029WAYMART-WD
Solar/Wind Harmer
0.001
209009PEIP 2
Adder
6.269
209010PEIP 1
Adder
2.84
209010PEIP 1
Adder
0.416
209054AE2-059 GEN
Solar/Wind Harmer
0.001
209059AE2-084 GEN
Solar/Wind Harmer
1.257
970761AG2-481 GEN
Solar/Wind Harmer
0.613
209130AF1-271A GEN
Solar/Wind Harmer
1.517
20478527GLRA_Q45
Adder
0.262
209137AF2-361 C
Solar/Wind Harmer
0.003
208835TUHI V3-051
Solar/Wind Harmer
0.073
208835TUHI V3-051
Solar/Wind Harmer
0.073
20464827MOUNT CT
Adder
1.933
20464827MOUNT CT
Adder
1.876
226929AD2-058 GEN
Solar/Wind Helper
0.119
316447AC1-158 HLD
Solar/Wind Helper
3.301
315651AD1-115 GEN
Solar/Wind Helper
0.904
316468AD1-105 GEN
Solar/Wind Helper
1.287
966001AG1-469 GEN
Solar/Wind Helper
0.276
238175AF1-290_GEN
Solar/Wind Helper
0.135
316077AC2-138 C
Solar/Wind Helper
0.24
966871AG1-558 GEN
Solar/Wind Helper
0.342
238169AE2-226 GEN1
Solar/Wind Helper
0.616
238170AE2-226 GEN2
Solar/Wind Helper
0.616
316487AF1-042 GEN
Solar/Wind Helper
0.256
316075AC2-137 C
Solar/Wind Helper
0.382
3143526WINTERP
Solar/Wind Helper
1.3
3142946ENON
Solar/Wind Helper
0.025
316240AF1-291 C
Solar/Wind Helper
0.332
316033AB2-134 GEN
Solar/Wind Helper
0.847
315697AD1-025 GEN
Solar/Wind Helper
2.814
316236AE1-162_GEN
Solar/Wind Helper
0.329
316036AC1-147 C
Solar/Wind Helper
0.371
316316AC1-027 C
Solar/Wind Helper
0.384
3142956BIRDNECK
Solar/Wind Helper
0.164
316185AD1-033 GEN
Solar/Wind Helper
1.142
3145506HICKORY
Solar/Wind Helper
0.971
3145506HICKORY
Solar/Wind Helper
0.582
3145506HICKORY
Solar/Wind Helper
0.146
316339AD2-160 GEN
Solar/Wind Helper
0.923
316018AA1-139 ULT2
Solar/Wind Helper
1.042
316017AA1-139 ULT1
Solar/Wind Helper
1.107
200200DELTA2 CT1
50/50
2.795
200193DELTA CT2
50/50
1.562
200203Y1-065-STG
50/50
5.638
200055ROCKSP 4
50/50
2.031
233971AC1-093 C
Solar/Wind Harmer
0.042
972133AH1-634 GEN
Solar/Wind Harmer
3.577
970695AG2-447 GEN
Solar/Wind Harmer
2.425
233996TM1833_GEN
Solar/Wind Harmer
0.001
233997TMININ_4.2
Solar/Wind Harmer
0.001
232406W1-004 FULL
Solar/Wind Harmer
0.628
232907VN8
Adder
29.134
232914OH NUG3
Adder
8.569
232916OH NUG5
Adder
8.569
972073AH1-586 GEN
Solar/Wind Harmer
9.093
232921TASLEY2G
Adder
5.008
233940AF2-379 C
Solar/Wind Harmer
0
233990AG1-397 GEN
Solar/Wind Harmer
1.321
234015AF2-250 C
Solar/Wind Harmer
0
233900O-025 C
Adder
1.142
233994AC2-023 GEN
Solar/Wind Harmer
0.004
960671AF2-358 GEN
Solar/Wind Harmer
12.119
232417X3-008 C
Solar/Wind Harmer
0.001
233952AC2-187 GEN
Solar/Wind Harmer
0.001
233918AB1-142 GEN
Solar/Wind Harmer
0.247
233982AB2-133 GEN
Solar/Wind Harmer
0.004
972251AH1-710 GEN
Adder
42.853
228202CUMB CT
Adder
14.203
228711V2-041C
Solar/Wind Harmer
0
971553AH1-274 GEN
Solar/Wind Harmer
1.342
230430AE1-229_GEN
Solar/Wind Harmer
0.014
230415AB2-049 C
Solar/Wind Harmer
0
228729W2-030 C
Solar/Wind Harmer
0.001
228304LOGAN
Adder
18.608
213497CHSTR7-9
Adder
2.326
219623KINSLEYBEA C
Solar/Wind Harmer
0
219766PARADISE C
Solar/Wind Harmer
0
213958STHWK5-6
Adder
2.306
219912AD2-042 GEN
Solar/Wind Harmer
0.001
213560DLW11-12
Adder
2.295
219906AC1-017 C
Solar/Wind Harmer
0
213815MOSER1-3
Adder
2.984
219610FLORENCE C
Solar/Wind Harmer
0.001
219348LDSOLAR C
Solar/Wind Harmer
0.001
219221BRL12CT1
Adder
7.501
219223BRL12CT3
Adder
7.501
20716028EGP_W2-019
Solar/Wind Harmer
0
20720828JCB_W4-025
Solar/Wind Harmer
0
20715028HAN_X4-015
Solar/Wind Harmer
0
20636028O CRK C1
Adder
5.895
971667AH1-334 GEN
Solar/Wind Harmer
1.48
219727YARDVSOLFA C
Solar/Wind Harmer
0
20714528FRN_Y2-051
Solar/Wind Harmer
0
219276PARKLANDSO C
Solar/Wind Harmer
0
20716228APLW2-078
Solar/Wind Harmer
0
20720528MAN_W1-024
Solar/Wind Harmer
0
967451AG2-055 C O1
Solar/Wind Harmer
206.325
219612MATRIX C
Solar/Wind Harmer
0
218438BLK ROCK C
Solar/Wind Harmer
0
20635828PARLN1&2
Adder
2.789
20635928PARLN3&4
Adder
2.789
20635028RRCT1&2
Adder
9.805
20635128RRCT3&4
Adder
8.129
219908AB1-139 C
Solar/Wind Harmer
0
20673728F2S_V4-070
Solar/Wind Harmer
0
217186ESSEX_G9
Adder
13.299
217194REDH C
Solar/Wind Harmer
0
20676728BRNX1-095
Solar/Wind Harmer
0
207510AF2-138 C
Solar/Wind Harmer
0.001
20674628WNG_W3-110
Solar/Wind Harmer
0
971007AG2-625 GEN
Solar/Wind Harmer
1.386
20633028GILCT9
Adder
23.692
20466127PORT 5CT
Adder
22.104
20465427SHAW CT
Adder
3.214
209025WIENIPP3
Adder
4.286
963071AG1-156 GEN
Solar/Wind Harmer
0.356
970095AG2-074 GEN
Solar/Wind Harmer
4.058
209027LOR2_Q27
Solar/Wind Harmer
0.001
209022WHFR IPP
Adder
2.605
209142AF1-226 GEN
Solar/Wind Harmer
2.228
209093AE2-110 GEN
Solar/Wind Harmer
1.273
209120AE2-241 GEN
Solar/Wind Harmer
1.273
972245AH1-707 GEN
Adder
4.254
972221AH1-695 GEN
Adder
108.167
209067AE2-060 GEN
Solar/Wind Harmer
0.001
970767AG2-484 GEN
Solar/Wind Harmer
0.521
970755AG2-478 GEN
Solar/Wind Harmer
0.059
227287AC2-120 GEN
Solar/Wind Helper
0.415
226910AB2-157 C
Solar/Wind Helper
0.017
3141196NOKESVL
Solar/Wind Helper
1.131
316044AC1-158 PL1
Solar/Wind Helper
1.5
316450AC1-158 RIC
Solar/Wind Helper
0.4
316170AC1-121 GEN2
Solar/Wind Helper
0.41
966881AG1-559 GEN
Solar/Wind Helper
0.354
3132273ORANGE
Solar/Wind Helper
0.052
3147666LOUISA
Solar/Wind Helper
0.599
3141906WESTMOR
Solar/Wind Helper
0.103
316473AC1-191 GEN
Solar/Wind Helper
1.551
316404AE1-155 C
Solar/Wind Helper
2.142
316484AD2-074 GEN
Solar/Wind Helper
0.489
316280AD1-041 GEN
Solar/Wind Helper
0.842
316156AD2-030 GEN
Solar/Wind Helper
0.378
3142946ENON
Solar/Wind Helper
0.083
316382AG1-145 C
Solar/Wind Helper
0.333
315839AE2-212 C
Solar/Wind Helper
0.331
3145336SMITFLD
Solar/Wind Helper
0.098
315773AC2-141 GEN
Solar/Wind Helper
5.257
238147AE2-230_GEN1
Solar/Wind Helper
0.42
238149AF1-291A_GEN
Solar/Wind Helper
0.12
3144536CHRHLND
Solar/Wind Helper
0.037
3144873MCLAUGH
Solar/Wind Helper
0.006
316313AB2-026
Solar/Wind Helper
0.37
316258AE1-075 C
Solar/Wind Helper
0.333
316405AF2-144 C
Solar/Wind Helper
0.278
3146456SLIGO L269
Solar/Wind Helper
0.242
237061AD1-155 GEN
Solar/Wind Helper
0.046
316320Y1-086
Solar/Wind Helper
0.108
316435W1029_GEN3
Solar/Wind Helper
0.97
3146516WINFALL
Solar/Wind Helper
0.24
3146626S HERTFORD
Solar/Wind Helper
0.239
3145273HOLLAND
Solar/Wind Helper
0.179
3146376EDENTON
Solar/Wind Helper
0.237
315614AA2-178 GEN
Solar/Wind Helper
1.431
315737AD1-076 GEN
Solar/Wind Helper
2.277
3146776BUCKING
Solar/Wind Helper
0.084
316365GEN2_N
Solar/Wind Helper
0.884
3146206CASHIE
Solar/Wind Helper
0.232
3145893MURPHYS
Solar/Wind Helper
0.083
3145893MURPHYS
Solar/Wind Helper
0.232
3146926FARMVIL
Solar/Wind Helper
0.139
3146173TUNIS
Solar/Wind Helper
0.231
3156021HOLLOMANSOL
Solar/Wind Helper
1.756
316463AE2-346 GEN
Solar/Wind Helper
0.211
316140AB2-099
Solar/Wind Helper
0.088
966621AG1-532 GEN
Solar/Wind Helper
0.21
3146263WOODLND
Solar/Wind Helper
0.23
942461AE2-259 GEN
Solar/Wind Helper
1.547
313506AB2-031 GEN
Solar/Wind Helper
1.041
3142666NORTHAMPTON
Solar/Wind Helper
0.229
3145963POPLR C
Solar/Wind Helper
0.229
3147043LAWRENC
Solar/Wind Helper
0.137
316317KELFORD C
Solar/Wind Helper
0.195
3145823KELFORD
Solar/Wind Helper
0.228
3147133PAMPLIN
Solar/Wind Helper
0.716
316478AD1-087 GEN
Solar/Wind Helper
1.112
316486AD2-202 GEN
Solar/Wind Helper
0.326
3145796HORNRTN
Solar/Wind Helper
0.908
3145796HORNRTN
Solar/Wind Helper
0.227
315785AD2-033 C
Solar/Wind Helper
2.632
316210AC1-098 GEN
Solar/Wind Helper
1.817
3145933PARMELE
Solar/Wind Helper
0.225
316499AE2-029_GEN
Solar/Wind Helper
0.756
316131AB2-060 GEN
Solar/Wind Helper
1.367
3148013FISHERV
Solar/Wind Helper
0.224
3145746EVERETS
Solar/Wind Helper
0.223
3145746EVERETS
Solar/Wind Helper
0.223
3137176SLIGO L2192
Solar/Wind Helper
0.963
3130086AYDLETT
Solar/Wind Helper
0.968
3146386ELIZ CT
Solar/Wind Helper
0.241
316431W1029_GEN1
Solar/Wind Helper
0.97
316433W1029_GEN2
Solar/Wind Helper
0.97
3146516WINFALL
Solar/Wind Helper
0.24
3146516WINFALL
Solar/Wind Helper
0.24
3146516WINFALL
Solar/Wind Helper
0.24
3146626S HERTFORD
Solar/Wind Helper
0.239
3146626S HERTFORD
Solar/Wind Helper
0.239
3144356SAPONY
Solar/Wind Helper
0.429
315742AE1-103 GEN
Solar/Wind Helper
0.383
3146776BUCKING
Solar/Wind Helper
0.929
3146776BUCKING
Solar/Wind Helper
0.075
3145893MURPHYS
Solar/Wind Helper
0.333
3145893MURPHYS
Solar/Wind Helper
0.418
3146173TUNIS
Solar/Wind Helper
0.231
3146173TUNIS
Solar/Wind Helper
0.231
316181AB2-040 GEN
Solar/Wind Helper
1.645
3142666NORTHAMPTON
Solar/Wind Helper
0.229
3142666NORTHAMPTON
Solar/Wind Helper
0.229
3142666NORTHAMPTON
Solar/Wind Helper
0.229
3142666NORTHAMPTON
Solar/Wind Helper
0.137
3132123MT JACKSON
Solar/Wind Helper
0.716
316426AA2-053 GEN
Solar/Wind Helper
1.303
3145593CAROLNA
Solar/Wind Helper
0.228
3145593CAROLNA
Solar/Wind Helper
0.228
315821AE2-092 GEN
Solar/Wind Helper
2.114
3147133PAMPLIN
Solar/Wind Helper
0.228
3147133PAMPLIN
Solar/Wind Helper
0.182
3145796HORNRTN
Solar/Wind Helper
0.681
316034AC1-036 C
Solar/Wind Helper
0.237
3145933PARMELE
Solar/Wind Helper
0.449
3145933PARMELE
Solar/Wind Helper
0.225
23777901MDS_W4-102
Solar/Wind Helper
0.141
316274AC1-208 GEN
Solar/Wind Helper
1.368
235020AA1-095 C
Solar/Wind Helper
0.042
213611FALLS1-3
Adder
2.961
214194N WALES4
Adder
0.713
20720728JCB_W1-129
Solar/Wind Harmer
0
207522AF2-254 C
Solar/Wind Harmer
0.774
207487AE2-000G4
Solar/Wind Harmer
10.546
207445AB1-138_GEN
Solar/Wind Harmer
0.001
20628028LAKEHURS
Adder
1.568
20714828MDF_W3-079
Solar/Wind Harmer
0.082
207454AA2-184 E
Solar/Wind Harmer
0.001
20715228NPK_W1-113
Solar/Wind Harmer
0
20742028HF_AC1-207
Solar/Wind Harmer
0.001
217197RE CRAN C
Solar/Wind Harmer
0
20635828PARLN1&2
Adder
6.157
20635028RRCT1&2
Adder
9.654
20635128RRCT3&4
Adder
9.319
217213AMBOY SO C
Solar/Wind Harmer
0
972275AH1-722 GEN
Adder
26.265
207528AF2-192 GEN
Solar/Wind Harmer
0.001
20673628F1S_V4-069
Solar/Wind Harmer
0
20675428EAM_W2-061
Solar/Wind Harmer
0
218449LINSOLAR C
Solar/Wind Harmer
0
20676428JCR_X2-075
Solar/Wind Harmer
0
217121ECCF
Adder
0.361
217083KRNY_132
Adder
7.733
20674328GAR_V4-001
Solar/Wind Harmer
0
20675828AU_W4-064
Solar/Wind Harmer
0
971519AH1-257 GEN
Solar/Wind Harmer
1.361
207437AD2-070 GEN
Solar/Wind Harmer
0.055
20671928W4-073
Solar/Wind Harmer
0
966181AG1-487 GEN
Solar/Wind Harmer
3.196
20465127PORT CT
Adder
2.505
208909MACR G3
Adder
132.886
205941AD2-115 GEN
Solar/Wind Harmer
0.096
20467927PC_Q59Y356
Adder
0.693
209023WIENIPP1
Adder
8.764
209025WIENIPP3
Adder
4.375
20465527S.RDG CT
Adder
2.265
212266LOR1
Solar/Wind Harmer
0.386
209010PEIP 1
Adder
0.516
212174INGE
Adder
0.873
212507AE2-042_GEN
Solar/Wind Harmer
0.479
209071AE2-133 GEN
Solar/Wind Harmer
0.001
970665AG2-430 GEN
Solar/Wind Harmer
5.608
209018SUNBIPCT
Adder
5.762
970757AG2-479 GEN
Solar/Wind Harmer
0.61
972241AH1-705 GEN
Adder
4.428
209008PAXT IPP
Adder
1.594
205967AE2-211_GEN
Solar/Wind Harmer
3.969
970753AG2-477 GEN
Solar/Wind Harmer
0.06
20465027TOLNA CT
Adder
2.276
970679AG2-439 GEN
Solar/Wind Harmer
0.599
208923BUSO V4-027
Solar/Wind Harmer
0
208856AE1-226 GEN
Solar/Wind Harmer
0.966
200917MEHOOPANY_G
Solar/Wind Harmer
0.309
316006AB2-029 C
Solar/Wind Helper
0.131
316045AC1-158 PL2
Solar/Wind Helper
4.801
316254AC1-120 GEN1
Solar/Wind Helper
1.229
3147666LOUISA
Solar/Wind Helper
1.042
316192AB2-158 GEN
Solar/Wind Helper
1.749
316337AD2-073 GEN
Solar/Wind Helper
0.39
964211AG1-282 GEN
Solar/Wind Helper
0.343
3141726DUNNSVL
Solar/Wind Helper
1.018
3142416OLDCHRC
Solar/Wind Helper
0.655
3142416OLDCHRC
Solar/Wind Helper
0.251
3138133OCRAN
Solar/Wind Helper
0.151
3141766HARMONY
Solar/Wind Helper
0.05
3142433PROV 92
Solar/Wind Helper
1.001
3143526WINTERP
Solar/Wind Helper
1.3
3142543TWELFTH
Solar/Wind Helper
0.024
3143226MDLTHAN
Solar/Wind Helper
0.25
316159AE1-175 C
Solar/Wind Helper
0.376
316458AB2-190 GEN2
Solar/Wind Helper
1.41
3145336SMITFLD
Solar/Wind Helper
0.978
316294AC1-161 GEN
Solar/Wind Helper
4.467
238148AE2-230_GEN2
Solar/Wind Helper
0.422
316381AD1-082 GEN
Solar/Wind Helper
1.262
316375AC2-012 GEN
Solar/Wind Helper
0.638
316072AD1-144
Solar/Wind Helper
0.277
316388AE2-253 GEN
Solar/Wind Helper
0.923
3146456SLIGO L269
Solar/Wind Helper
0.242
316246AF1-032 C
Solar/Wind Helper
0.276
316336AC2-165 C
Solar/Wind Helper
1.302
3146516WINFALL
Solar/Wind Helper
0.777
3146516WINFALL
Solar/Wind Helper
0.24
315800Z1-036_GEN1
Solar/Wind Helper
1.31
3130156CHOWAN
Solar/Wind Helper
0.237
3145663CRESWEL
Solar/Wind Helper
0.658
316322AB2-045
Solar/Wind Helper
0.259
3146776BUCKING
Solar/Wind Helper
0.093
316023GEN1_S
Solar/Wind Helper
0.884
3146206CASHIE
Solar/Wind Helper
0.232
3145893MURPHYS
Solar/Wind Helper
0.928
3146926FARMVIL
Solar/Wind Helper
0.139
3146173TUNIS
Solar/Wind Helper
0.231
3145683EARLEYS
Solar/Wind Helper
0.23
3146263WOODLND
Solar/Wind Helper
0.23
3145963POPLR C
Solar/Wind Helper
0.229
316190AA2-174 GEN
Solar/Wind Helper
0.015
316011AB1-132 GEN
Solar/Wind Helper
2.458
3145823KELFORD
Solar/Wind Helper
0.228
316174AB2-169 GEN
Solar/Wind Helper
0.58
3145783HORNRTN
Solar/Wind Helper
0.228
3145796HORNRTN
Solar/Wind Helper
0.749
3145796HORNRTN
Solar/Wind Helper
0.227
3147983MERCK5
Solar/Wind Helper
0.09
316212AC1-099_GEN
Solar/Wind Helper
1.01
316129AC1-054 GEN
Solar/Wind Helper
1.114
316237AB2-079_GEN
Solar/Wind Helper
0.301
3145746EVERETS
Solar/Wind Helper
0.223
3145746EVERETS
Solar/Wind Helper
0.223
HAMLETPJM->LTFIMP_HAMLET
CLTF
5.035
G-007ALTFEXP_G-007A->PJM
CMTX
42.641
CBM NorthLTFEXP_CBM-N->PJM
CBM
65.685
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
3.483
BlueGrassPJM->LTFIMP_BlueG
CLTF
10.864
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
112.673
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.896
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
16.673

Details for CNASTONE-BRIGHTON 500.0 kV Ckt 1 line l/o AP_P2-3_PE-500-019B_SRT-A


Base Case Flowgate

Area:PJM
Facility Description:
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-500-019B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:122.82 %
Rating:3098.0 MVA
Rating Type:B
MVA to Mitigate:3805.11
MW Contribution:5.35
Bus #Bus NameTypeMW Contribution
200192DELTA CT1
50/50
1.287
200194DELTA CT3
50/50
1.287
200204Y1-065-CTG1
50/50
2.676
200054ROCKSP 3
50/50
1.707
232901NORTHST
Adder
6.598
233972AC1-094 C
Solar/Wind Harmer
0.526
232434Z2-077 GEN
Solar/Wind Harmer
0.198
233998TM1NIN_3.36
Solar/Wind Harmer
1.004
232404W1-003 C
Solar/Wind Harmer
0.794
232917OH NUG6
Adder
6.967
232915OH NUG4
Adder
6.951
972177AH1-672 GEN
Solar/Wind Harmer
10.642
232428Y3-058 C
Solar/Wind Harmer
0.661
971195AH1-057 GEN
Solar/Wind Harmer
0.867
232900DEMECSMY
Adder
7.307
232919VN10
Adder
2.223
965821AG1-450 GEN
Solar/Wind Harmer
4.123
232426Y1-080 FULL
Solar/Wind Harmer
0.151
970277AG2-181 GEN
Solar/Wind Harmer
3.971
233964AF2-378 GEN
Solar/Wind Harmer
0.101
233954AC2-188 GEN
Solar/Wind Harmer
0.891
233950AC2-186 GEN
Solar/Wind Harmer
0.446
232910NRG_G1
Adder
6.819
234012AE2-112_GEN
Solar/Wind Harmer
1.812
232422X3-066 FULL
Solar/Wind Harmer
0.197
233930AB2-032 GEN
Solar/Wind Harmer
0.656
233915AB1-141 GEN
Solar/Wind Harmer
0.779
231918WEST 1
Adder
2.597
231917EM10
Adder
1.815
228206SHRMN CT
Adder
11.624
228732V1-021 C
Adder
0.133
945431AF1-208 GEN
Solar/Wind Harmer
6.042
970997AG2-616 GEN
Solar/Wind Harmer
6.706
228351V2-046C
Solar/Wind Harmer
1.408
230511AF1-262
Solar/Wind Harmer
0.128
228728W1-130C
Solar/Wind Harmer
0.464
230434AG1-499 GEN
Solar/Wind Harmer
0.405
213497CHSTR7-9
Adder
1.89
213497CHSTR7-9
Adder
1.89
219258KINSLEYDEP C
Solar/Wind Harmer
0.224
219904AC1-010 C
Solar/Wind Harmer
0.261
218660EHAMPSOLAR C
Solar/Wind Harmer
0.121
219287REEVESEAST C
Solar/Wind Harmer
0.927
219686LUMSOLAR_N C
Solar/Wind Harmer
0.14
213958STHWK5-6
Adder
1.875
219907AC1-030 C
Solar/Wind Harmer
0.096
213560DLW11-12
Adder
1.867
972281AH1-725 GEN
50/50
114.136
200201DELTA2 CT2
50/50
2.303
200034PCHBTM 2
50/50
13.411
200035PCHBTM 3
50/50
13.51
200205Y1-065-CTG2
50/50
2.676
971149AH1-027 GEN
Solar/Wind Harmer
2.683
233987AB2-037 GEN
Solar/Wind Harmer
9.023
233939AC1-091 C
Solar/Wind Harmer
0.696
233970AC1-092 C
Solar/Wind Harmer
0.696
970545AG2-347 GEN
Solar/Wind Harmer
51.846
233901CHERRYDALE C
Solar/Wind Harmer
0.892
232408W1-005 C
Solar/Wind Harmer
0.794
232410W1-006 C
Solar/Wind Harmer
0.794
972069AH1-584 GEN
Solar/Wind Harmer
7.095
972071AH1-585 GEN
Solar/Wind Harmer
7.095
232918OH NUG7
Adder
6.951
971747AH1-380 GEN
Solar/Wind Harmer
2.838
232905CHERITON_25
Adder
1.944
232926CRISFLD1
Adder
1.555
231940T-011
Adder
0.591
232899W1-062
Adder
7.618
233946AB2-136 GEN
Solar/Wind Harmer
3.16
234036AF2-325 C
Solar/Wind Harmer
0.726
234041AC1-190 GEN
Solar/Wind Harmer
7.089
233984AB2-036 GEN
Solar/Wind Harmer
9.825
232424Y1-079 C
Solar/Wind Harmer
0.444
234014AF1-036_GEN
Solar/Wind Harmer
2.131
231131BLOOM ENRGY
Adder
3.429
233944AB2-135 GEN
Solar/Wind Harmer
4.119
233933AB2-153 GEN
Solar/Wind Harmer
0.884
232416X2-083
Adder
0.352
228251CARLLS#4
Adder
0.442
230422AE1-104_GEN1
Solar/Wind Harmer
23.561
230425AE1-104_GEN2
Solar/Wind Harmer
23.561
230433AD2-135 GEN
Solar/Wind Harmer
0.071
228307PCLP GT
Adder
8.436
230407AD2-065 C
Solar/Wind Harmer
0.092
228304LOGAN
Adder
16.864
972233AH1-701 GEN
Adder
2.921
213589EDDYSTN4
Adder
55.199
213587EDDYSTN3
Adder
55.195
219921AF1-264
Solar/Wind Harmer
0.1
219615MILLCREEK C
Solar/Wind Harmer
0.164
213535CROYDN11
Adder
7.001
213815MOSER1-3
Adder
2.429
213815MOSER1-3
Adder
2.429
20716428NHV_W2-082
Solar/Wind Harmer
1.21
207500AE2-000G1
Solar/Wind Harmer
21.416
207497AE2-000G2
Solar/Wind Harmer
21.416
207507AE2-000G3
Solar/Wind Harmer
21.416
20636128O CRK C2
Adder
4.381
963401AG1-189 GEN
Solar/Wind Harmer
0.782
963391AG1-188 GEN
Solar/Wind Harmer
1.303
20714928UPF_X1-085
Solar/Wind Harmer
0.276
219114HARTZY_C
Solar/Wind Harmer
0.567
20628028LAKEHURS
Adder
0.646
219817TRENTONSOL C
Solar/Wind Harmer
0.748
20641628MLH_W1-032
Solar/Wind Harmer
0.199
20720628TIN_W1-124
Solar/Wind Harmer
0.676
20716928W4-060COL
Solar/Wind Harmer
0.482
200200DELTA2 CT1
50/50
2.303
200193DELTA CT2
50/50
1.287
200203Y1-065-STG
50/50
4.64
200055ROCKSP 4
50/50
1.671
233971AC1-093 C
Solar/Wind Harmer
0.622
970695AG2-447 GEN
Solar/Wind Harmer
2.84
972133AH1-634 GEN
Solar/Wind Harmer
7.855
233996TM1833_GEN
Solar/Wind Harmer
1.004
233997TMININ_4.2
Solar/Wind Harmer
1.004
232406W1-004 FULL
Solar/Wind Harmer
0.794
232914OH NUG3
Adder
6.998
232916OH NUG5
Adder
6.998
972073AH1-586 GEN
Solar/Wind Harmer
7.425
232921TASLEY2G
Adder
4.09
233940AF2-379 C
Solar/Wind Harmer
0.148
233990AG1-397 GEN
Solar/Wind Harmer
0.909
233900O-025 C
Adder
0.933
234015AF2-250 C
Solar/Wind Harmer
0.095
232907VN8
Adder
23.789
233994AC2-023 GEN
Solar/Wind Harmer
2.129
960671AF2-358 GEN
Solar/Wind Harmer
14.183
232417X3-008 C
Solar/Wind Harmer
1.584
233952AC2-187 GEN
Solar/Wind Harmer
0.891
219304NAMERICA C
Solar/Wind Harmer
0.213
219222BRL12CT2
Adder
6.111
213611FALLS1-3
Adder
2.412
214194N WALES4
Adder
0.581
20720728JCB_W1-129
Solar/Wind Harmer
0.203
207522AF2-254 C
Solar/Wind Harmer
0.976
207487AE2-000G4
Solar/Wind Harmer
21.416
207445AB1-138_GEN
Solar/Wind Harmer
0.394
20628028LAKEHURS
Adder
1.278
963711AG1-223 GEN
Solar/Wind Harmer
1.004
20714828MDF_W3-079
Solar/Wind Harmer
0.208
219680HOPEWELLV C1
Solar/Wind Harmer
0.052
207454AA2-184 E
Solar/Wind Harmer
0.678
20715228NPK_W1-113
Solar/Wind Harmer
0.292
20742028HF_AC1-207
Solar/Wind Harmer
0.532
217197RE CRAN C
Solar/Wind Harmer
0.364
20635828PARLN1&2
Adder
5.017
20635028RRCT1&2
Adder
7.867
20635128RRCT3&4
Adder
7.593
218428ETC SOLAR C
Solar/Wind Harmer
0.024
217213AMBOY SO C
Solar/Wind Harmer
0.086
972275AH1-722 GEN
Adder
21.399
207528AF2-192 GEN
Solar/Wind Harmer
0.375
20673628F1S_V4-069
Solar/Wind Harmer
0.122
20675428EAM_W2-061
Solar/Wind Harmer
0.128
218449LINSOLAR C
Solar/Wind Harmer
0.682
20676428JCR_X2-075
Solar/Wind Harmer
0.232
217209CENTRL HS C
Solar/Wind Harmer
0.03
217121ECCF
Adder
0.294
217083KRNY_132
Adder
6.299
217208PARK ELE C
Solar/Wind Harmer
0.017
207439AE1-081 C O1
Solar/Wind Harmer
0.041
20674328GAR_V4-001
Solar/Wind Harmer
0.075
20675828AU_W4-064
Solar/Wind Harmer
0.117
971519AH1-257 GEN
Solar/Wind Harmer
1.714
207518AF1-320_GEN
Solar/Wind Harmer
2.485
207437AD2-070 GEN
Solar/Wind Harmer
0.205
20671928W4-073
Solar/Wind Harmer
0.294
20465127PORT CT
Adder
2.039
966181AG1-487 GEN
Solar/Wind Harmer
2.548
208909MACR G3
Adder
108.145
961301AF2-421 GEN
Solar/Wind Harmer
0.663
963151AG1-164 GEN
Solar/Wind Harmer
0.663
209023WIENIPP1
Adder
7.147
209025WIENIPP3
Adder
3.568
205941AD2-115 GEN
Solar/Wind Harmer
0.612
20467927PC_Q59Y356
Adder
0.554
212266LOR1
Solar/Wind Harmer
0.085
970237AG2-161 GEN
Solar/Wind Harmer
2.273
20465527S.RDG CT
Adder
1.81
209010PEIP 1
Adder
0.422
961341AF2-425 GEN
Solar/Wind Harmer
0.645
212174INGE
Adder
0.713
212507AE2-042_GEN
Solar/Wind Harmer
1.905
946731AF1-337 GEN
Solar/Wind Harmer
0.632
209071AE2-133 GEN
Solar/Wind Harmer
1.07
970665AG2-430 GEN
Solar/Wind Harmer
6.267
209018SUNBIPCT
Adder
4.704
972241AH1-705 GEN
Adder
3.618
209008PAXT IPP
Adder
1.269
316045AC1-158 PL2
Solar/Wind Helper
3.977
316006AB2-029 C
Solar/Wind Helper
0.107
233918AB1-142 GEN
Solar/Wind Harmer
0.779
233982AB2-133 GEN
Solar/Wind Harmer
3.828
972251AH1-710 GEN
Adder
35.027
228202CUMB CT
Adder
11.588
228711V2-041C
Solar/Wind Harmer
0.421
971553AH1-274 GEN
Solar/Wind Harmer
1.697
230430AE1-229_GEN
Solar/Wind Harmer
6.154
230415AB2-049 C
Solar/Wind Harmer
0.132
228729W2-030 C
Solar/Wind Harmer
0.403
228304LOGAN
Adder
15.167
213497CHSTR7-9
Adder
1.89
219623KINSLEYBEA C
Solar/Wind Harmer
0.296
219291REEVESSOUT C
Solar/Wind Harmer
0.041
219766PARADISE C
Solar/Wind Harmer
0.217
219912AD2-042 GEN
Solar/Wind Harmer
0.549
213958STHWK5-6
Adder
1.875
219236SOUTHERNHQ C
Solar/Wind Harmer
0.046
213560DLW11-12
Adder
1.867
219906AC1-017 C
Solar/Wind Harmer
0.153
219610FLORENCE C
Solar/Wind Harmer
0.949
219348LDSOLAR C
Solar/Wind Harmer
0.41
219221BRL12CT1
Adder
6.111
219223BRL12CT3
Adder
6.111
213815MOSER1-3
Adder
2.429
959561AF2-247 GEN
Solar/Wind Harmer
0.331
20716028EGP_W2-019
Solar/Wind Harmer
0.316
20720828JCB_W4-025
Solar/Wind Harmer
0.308
20715028HAN_X4-015
Solar/Wind Harmer
0.203
20636028O CRK C1
Adder
4.805
971667AH1-334 GEN
Solar/Wind Harmer
1.867
219727YARDVSOLFA C
Solar/Wind Harmer
0.618
20714528FRN_Y2-051
Solar/Wind Harmer
0.2
219276PARKLANDSO C
Solar/Wind Harmer
0.313
219918AC2-009 C
Solar/Wind Harmer
0.042
20716228APLW2-078
Solar/Wind Harmer
0.599
20720528MAN_W1-024
Solar/Wind Harmer
0.172
967451AG2-055 C O1
Solar/Wind Harmer
117.712
219612MATRIX C
Solar/Wind Harmer
0.125
218438BLK ROCK C
Solar/Wind Harmer
0.092
20635828PARLN1&2
Adder
2.273
20635928PARLN3&4
Adder
2.273
20635028RRCT1&2
Adder
7.99
20635128RRCT3&4
Adder
6.624
219908AB1-139 C
Solar/Wind Harmer
0.258
219919AE1-041 FULL
Solar/Wind Harmer
0.027
219249CENTRALDIV C
Solar/Wind Harmer
0.027
20673728F2S_V4-070
Solar/Wind Harmer
0.122
217211CAMDEN ST C
Solar/Wind Harmer
0.017
217186ESSEX_G9
Adder
10.834
217169METRODIV C
Solar/Wind Harmer
0.027
217194REDH C
Solar/Wind Harmer
0.334
20676728BRNX1-095
Solar/Wind Harmer
0.12
207510AF2-138 C
Solar/Wind Harmer
1.208
20674628WNG_W3-110
Solar/Wind Harmer
0.274
971007AG2-625 GEN
Solar/Wind Harmer
1.746
20633028GILCT9
Adder
19.259
966181AG1-487 GEN
Solar/Wind Harmer
0.171
20466127PORT 5CT
Adder
17.993
20465427SHAW CT
Adder
2.618
963161AG1-165 GEN
Solar/Wind Harmer
0.663
209025WIENIPP3
Adder
3.495
963071AG1-156 GEN
Solar/Wind Harmer
1.82
970095AG2-074 GEN
Solar/Wind Harmer
4.129
209027LOR2_Q27
Solar/Wind Harmer
2.96
209022WHFR IPP
Adder
2.125
961331AF2-424 GEN
Solar/Wind Harmer
0.645
961421AF2-433 GEN
Solar/Wind Harmer
0.643
957921AF2-086 GEN
Solar/Wind Harmer
0.625
209142AF1-226 GEN
Solar/Wind Harmer
3.724
209093AE2-110 GEN
Solar/Wind Harmer
1.608
209120AE2-241 GEN
Solar/Wind Harmer
2.128
972245AH1-707 GEN
Adder
3.473
946691AF1-333 GEN
Solar/Wind Harmer
0.632
946741AF1-338 GEN
Solar/Wind Harmer
0.632
972221AH1-695 GEN
Adder
85.964
209067AE2-060 GEN
Solar/Wind Harmer
0.909
227287AC2-120 GEN
Solar/Wind Helper
0.515
226910AB2-157 C
Solar/Wind Helper
0.021
3141196NOKESVL
Solar/Wind Helper
0.92
316044AC1-158 PL1
Solar/Wind Helper
1.242
316450AC1-158 RIC
Solar/Wind Helper
0.331
924131AB2-057 GEN
Solar/Wind Harmer
0.697
218440SUMMTASSOC C
Solar/Wind Harmer
0.087
218418LINDEN_G5
Adder
11.64
200202DELTA2 ST
50/50
3.908
200195DELTA ST
50/50
1.989
200052ROCKSP 1
50/50
1.69
200053ROCKSP 2
50/50
1.654
233973AC2-185 C
Solar/Wind Harmer
2.864
234033AF1-007_GEN
Solar/Wind Harmer
18.527
232904IR4
Adder
64.06
232920IR10
Adder
2.504
232432Z2-076 GEN
Solar/Wind Harmer
0.105
233923SMA
Solar/Wind Harmer
3.679
232912OH NUG1
Adder
6.998
232913OH NUG2
Adder
6.904
233990AG1-397 GEN
Solar/Wind Harmer
0.044
233955AB2-172 GEN
Solar/Wind Harmer
3.959
232813VAUGHN
Adder
0.465
233968AD2-076_GEN
Solar/Wind Harmer
5.222
970597AG2-380 GEN
Solar/Wind Harmer
3.279
231906DC3 NUG
Adder
11.016
231902DC CT7
Adder
8.806
231907DC10
Adder
2.75
232436AB1-176 C
Solar/Wind Harmer
0.18
971983AH1-536 GEN
Solar/Wind Harmer
5.882
233935AB2-179 C
Solar/Wind Harmer
1.947
231919CHRIST1
Adder
3.415
231920CHRIST2
Adder
3.339
970453AG2-297 GEN
Solar/Wind Harmer
1.937
228260V4-054C
Solar/Wind Harmer
0.719
228309CCLP NUG
Adder
18.086
228309CCLP NUG
Adder
17.203
972141AH1-641 GEN
Solar/Wind Harmer
2.012
964001AG1-254 GEN
Solar/Wind Harmer
1.421
971011AG2-627 GEN
Solar/Wind Harmer
5.352
971535AH1-265 GEN
Solar/Wind Harmer
2.972
227927V4-067C
Solar/Wind Harmer
0.138
228754AB1-001 C
Solar/Wind Harmer
0.097
219137THOSOLAR C
Solar/Wind Harmer
0.838
219272CLEANLIGHT C
Solar/Wind Harmer
0.126
219688LUMSOLAR_S C
Solar/Wind Harmer
0.14
219914AD2-027 C
Solar/Wind Harmer
0.414
213942SCHUYLKILL
Adder
2.453
213942SCHUYLKILL
Adder
1.875
213957STHWK3-4
Adder
1.875
213957STHWK3-4
Adder
1.875
213561DLWR9-10
Adder
2.442
213561DLWR9-10
Adder
1.867
219607WPEMNERT C
Solar/Wind Harmer
0.287
219224BRL12CT4
Adder
6.111
214067T20SOLAR
Solar/Wind Harmer
0.173
213611FALLS1-3
Adder
2.412
213611FALLS1-3
Adder
2.412
20717128DIX_Z2-102
Solar/Wind Harmer
0.898
20715728PEM_W1-119
Solar/Wind Harmer
0.364
20715828PEM_W1-120
Solar/Wind Harmer
0.364
970025AG2-016 GEN
Solar/Wind Harmer
1.926
971189AH1-054 GEN
Solar/Wind Harmer
0.802
207459AE1-142 C O1
Solar/Wind Harmer
0.717
219620RIDERU C
Solar/Wind Harmer
0.038
20714328BYD_X4-031
Solar/Wind Harmer
0.192
20714428HOW_X1-037
Solar/Wind Harmer
0.838
971521AH1-258 GEN
Solar/Wind Harmer
1.835
20720428HOL_W1-112
Solar/Wind Harmer
0.235
20635928PARLN3&4
Adder
5.017
218455CINNBAY_CGEN
Adder
1.232
218526CNTRALGAS2 C
Solar/Wind Harmer
0.251
218524CNTRALGAS1 C
Solar/Wind Harmer
0.251
20675528CPH_W2-050
Solar/Wind Harmer
0.317
218404KENILWRTH C
Adder
0.885
217167KRNY_14
Adder
6.299
217086KRNY_131
Adder
6.246
217147KRNY_1212
Adder
5.992
217147KRNY_1212
Adder
5.885
217146KRNY_1234
Adder
5.871
217146KRNY_1234
Adder
5.831
966261AG1-495 GEN
Solar/Wind Harmer
1.219
20676328BVR_Y1-020
Solar/Wind Harmer
0.225
207511W3-106 GEN
Solar/Wind Harmer
0.446
207530AG1-191 GEN
Solar/Wind Harmer
0.934
20674828DL_W4-046
Solar/Wind Harmer
0.439
971009AG2-626 GEN
Solar/Wind Harmer
1.113
207408W3-077 C
Solar/Wind Harmer
0.345
20675728RH_W2-091
Solar/Wind Harmer
0.233
20675928HOL_W4-097
Solar/Wind Harmer
0.089
207484AF2-139 C O1
Solar/Wind Harmer
0.344
20675128HRM_W1-127
Solar/Wind Harmer
0.116
20462827N BANGR8
Adder
0.487
966421AG1-511 GEN
Solar/Wind Harmer
5.841
209116AE2-175 GEN
Solar/Wind Harmer
2.782
961261AF2-417 GEN
Solar/Wind Harmer
0.664
209026WIENIPP4
Adder
3.531
20486527WR_V4-052
Adder
0.706
209045AE2-271 GEN
Solar/Wind Harmer
10.765
208862AG1-362 C
Solar/Wind Harmer
0.522
959431AF2-234 GEN
Solar/Wind Harmer
1.263
964051AG1-259 GEN
Solar/Wind Harmer
0.847
964061AG1-260 GEN
Solar/Wind Harmer
0.847
959421AF2-233 GEN
Solar/Wind Harmer
0.632
3141426STAFORD
Solar/Wind Helper
0.054
3138216PACIFIC
Solar/Wind Helper
0.039
316411AF1-147_GEN1
Solar/Wind Helper
0.78
316415AF1-147_GEN2
Solar/Wind Helper
0.78
218419LINDEN_G6
Adder
11.64
972260AH1-715 GEN1
Adder
9.321
20673828FLE_V3-070
Solar/Wind Harmer
0.31
207442AE1-156 GEN
Solar/Wind Harmer
0.505
20676128MHD_W3-029
Solar/Wind Harmer
0.324
219036LINDEN_G7
Adder
11.336
219035LINDEN_G8
Adder
11.174
972261AH1-715 GEN2
Adder
10.851
217081WEATEXAS C
Solar/Wind Harmer
0.058
217202FBANKSOLAR C
Solar/Wind Harmer
0.05
20671828STAW2-080
Solar/Wind Harmer
0.071
217201HACKENSOLA C
Solar/Wind Harmer
0.05
972237AH1-703 GEN
Adder
6.857
217206BARNGR HS C
Solar/Wind Harmer
0.021
217086KRNY_131
Adder
6.313
217083KRNY_132
Adder
6.259
217204WCALDSOLAR C
Solar/Wind Harmer
0.05
20674528F3S_W2-016
Solar/Wind Harmer
0.955
20676228FRD_X1-012
Solar/Wind Harmer
0.402
207471AF2-354 C
Solar/Wind Harmer
0.348
20674928WA_W3-044
Solar/Wind Harmer
0.327
964851AG1-348 GEN
Solar/Wind Harmer
1.194
20634528N27_Y2-018
Solar/Wind Harmer
0.183
20465127PORT CT
Adder
2.706
20674128FR_U2-059
Solar/Wind Harmer
0.125
966111AG1-480 GEN
Solar/Wind Harmer
0.059
966111AG1-480 GEN
Solar/Wind Harmer
2.234
211065PSPA IPP
Solar/Wind Harmer
0.305
211065PSPA IPP
Solar/Wind Harmer
0.305
208972BECR K09
Solar/Wind Harmer
0.694
961541AF2-445A GEN
Solar/Wind Harmer
2.126
20465527S.RDG CT
Adder
1.751
209029WAYMART-WD
Solar/Wind Harmer
1.885
209009PEIP 2
Adder
5.119
209010PEIP 1
Adder
2.32
209010PEIP 1
Adder
0.34
961431AF2-434 GEN
Solar/Wind Harmer
0.643
209054AE2-059 GEN
Solar/Wind Harmer
1.075
209059AE2-084 GEN
Solar/Wind Harmer
1.588
946751AF1-339 GEN
Solar/Wind Harmer
0.632
209130AF1-271A GEN
Solar/Wind Harmer
1.776
20478527GLRA_Q45
Adder
0.209
209137AF2-361 C
Solar/Wind Harmer
1.757
226929AD2-058 GEN
Solar/Wind Helper
0.143
316447AC1-158 HLD
Solar/Wind Helper
2.734
HAMLETPJM->LTFIMP_HAMLET
CLTF
4.037
G-007ALTFEXP_G-007A->PJM
CMTX
34.745
CBM NorthLTFEXP_CBM-N->PJM
CBM
53.966
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
2.631
BlueGrassPJM->LTFIMP_BlueG
CLTF
8.21
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
91.791
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.3
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
12.684

Details for CNASTONE-BRIGHTON 500.0 kV Ckt 1 line l/o PECO_P4_PEACH025_SRT-A/* $ CHESCO $ PECO_P4_PEACH025 $ STBK


Base Case Flowgate

Area:PJM
Facility Description:
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
Contingency Name:
PECO_P4_PEACH025_SRT-A/* $ CHESCO $ PECO_P4_PEACH025 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.21 %
Rating:3098.0 MVA
Rating Type:B
MVA to Mitigate:3569.19
MW Contribution:5.86
Bus #Bus NameTypeMW Contribution
972281AH1-725 GEN
50/50
140.917
200201DELTA2 CT2
50/50
2.925
200034PCHBTM 2
50/50
17.026
200035PCHBTM 3
50/50
17.198
200205Y1-065-CTG2
50/50
3.352
233987AB2-037 GEN
Solar/Wind Harmer
10.542
232926CRISFLD1
Adder
1.814
233901CHERRYDALE C
Solar/Wind Harmer
1.04
232408W1-005 C
Solar/Wind Harmer
0.926
232410W1-006 C
Solar/Wind Harmer
0.926
972069AH1-584 GEN
Solar/Wind Harmer
8.276
972071AH1-585 GEN
Solar/Wind Harmer
8.276
232918OH NUG7
Adder
8.108
971747AH1-380 GEN
Solar/Wind Harmer
3.31
232905CHERITON_25
Adder
2.267
970545AG2-347 GEN
Solar/Wind Harmer
60.452
233946AB2-136 GEN
Solar/Wind Harmer
3.688
234036AF2-325 C
Solar/Wind Harmer
0.847
231940T-011
Adder
0.689
234041AC1-190 GEN
Solar/Wind Harmer
8.272
971149AH1-027 GEN
Solar/Wind Harmer
3.125
233939AC1-091 C
Solar/Wind Harmer
0.81
233970AC1-092 C
Solar/Wind Harmer
0.81
232899W1-062
Adder
8.871
233984AB2-036 GEN
Solar/Wind Harmer
11.471
232424Y1-079 C
Solar/Wind Harmer
0.518
234014AF1-036_GEN
Solar/Wind Harmer
2.488
231131BLOOM ENRGY
Adder
3.998
233944AB2-135 GEN
Solar/Wind Harmer
4.806
233933AB2-153 GEN
Solar/Wind Harmer
1.032
232416X2-083
Adder
0.409
228251CARLLS#4
Adder
0.485
230433AD2-135 GEN
Solar/Wind Harmer
0.077
230422AE1-104_GEN1
Solar/Wind Harmer
25.781
230425AE1-104_GEN2
Solar/Wind Harmer
25.781
213589EDDYSTN4
Adder
61
213587EDDYSTN3
Adder
60.986
228307PCLP GT
Adder
9.236
228304LOGAN
Adder
18.443
230407AD2-065 C
Solar/Wind Harmer
0.1
972233AH1-701 GEN
Adder
3.19
219921AF1-264
Solar/Wind Harmer
0.108
219615MILLCREEK C
Solar/Wind Harmer
0.175
213815MOSER1-3
Adder
2.585
213815MOSER1-3
Adder
2.585
213535CROYDN11
Adder
7.449
20716428NHV_W2-082
Solar/Wind Harmer
1.268
207500AE2-000G1
Solar/Wind Harmer
22.387
207497AE2-000G2
Solar/Wind Harmer
22.387
207507AE2-000G3
Solar/Wind Harmer
22.387
20636128O CRK C2
Adder
4.58
963401AG1-189 GEN
Solar/Wind Harmer
0.816
963391AG1-188 GEN
Solar/Wind Harmer
1.358
20714928UPF_X1-085
Solar/Wind Harmer
0.288
219114HARTZY_C
Solar/Wind Harmer
0.59
20628028LAKEHURS
Adder
0.67
219817TRENTONSOL C
Solar/Wind Harmer
0.766
20641628MLH_W1-032
Solar/Wind Harmer
0.203
20720628TIN_W1-124
Solar/Wind Harmer
0.69
20716928W4-060COL
Solar/Wind Harmer
0.487
924131AB2-057 GEN
Solar/Wind Harmer
0.699
218440SUMMTASSOC C
Solar/Wind Harmer
0.086
218418LINDEN_G5
Adder
11.524
218419LINDEN_G6
Adder
11.524
972260AH1-715 GEN1
Adder
9.228
20673828FLE_V3-070
Solar/Wind Harmer
0.307
207442AE1-156 GEN
Solar/Wind Harmer
0.497
20676128MHD_W3-029
Solar/Wind Harmer
0.319
219036LINDEN_G7
Adder
11.168
219035LINDEN_G8
Adder
11.009
972261AH1-715 GEN2
Adder
10.691
217081WEATEXAS C
Solar/Wind Harmer
0.057
217202FBANKSOLAR C
Solar/Wind Harmer
0.049
217201HACKENSOLA C
Solar/Wind Harmer
0.049
972237AH1-703 GEN
Adder
6.696
217206BARNGR HS C
Solar/Wind Harmer
0.02
217086KRNY_131
Adder
6.163
217083KRNY_132
Adder
6.111
20671828STAW2-080
Solar/Wind Harmer
0.069
217204WCALDSOLAR C
Solar/Wind Harmer
0.048
20674528F3S_W2-016
Solar/Wind Harmer
0.927
20676228FRD_X1-012
Solar/Wind Harmer
0.38
207471AF2-354 C
Solar/Wind Harmer
0.325
20674928WA_W3-044
Solar/Wind Harmer
0.306
964851AG1-348 GEN
Solar/Wind Harmer
1.112
20634528N27_Y2-018
Solar/Wind Harmer
0.17
20465127PORT CT
Adder
2.495
20674128FR_U2-059
Solar/Wind Harmer
0.115
966111AG1-480 GEN
Solar/Wind Harmer
0.054
966111AG1-480 GEN
Solar/Wind Harmer
2.052
211065PSPA IPP
Solar/Wind Harmer
0.272
211065PSPA IPP
Solar/Wind Harmer
0.272
209029WAYMART-WD
Solar/Wind Harmer
1.651
209009PEIP 2
Adder
4.484
209010PEIP 1
Adder
2.032
209010PEIP 1
Adder
0.298
208972BECR K09
Solar/Wind Harmer
0.599
961541AF2-445A GEN
Solar/Wind Harmer
1.777
961431AF2-434 GEN
Solar/Wind Harmer
0.533
20465527S.RDG CT
Adder
1.428
226929AD2-058 GEN
Solar/Wind Helper
0.101
200202DELTA2 ST
50/50
4.963
200195DELTA ST
50/50
2.526
200052ROCKSP 1
50/50
2.117
200053ROCKSP 2
50/50
2.072
233923SMA
Solar/Wind Harmer
4.292
232912OH NUG1
Adder
8.162
232913OH NUG2
Adder
8.053
233990AG1-397 GEN
Solar/Wind Harmer
0.051
234033AF1-007_GEN
Solar/Wind Harmer
21.602
232432Z2-076 GEN
Solar/Wind Harmer
0.122
232904IR4
Adder
74.694
232920IR10
Adder
2.92
233955AB2-172 GEN
Solar/Wind Harmer
4.62
233973AC2-185 C
Solar/Wind Harmer
3.333
232813VAUGHN
Adder
0.542
233968AD2-076_GEN
Solar/Wind Harmer
6.096
970597AG2-380 GEN
Solar/Wind Harmer
3.828
232436AB1-176 C
Solar/Wind Harmer
0.211
231906DC3 NUG
Adder
12.846
231902DC CT7
Adder
10.27
231907DC10
Adder
3.207
971983AH1-536 GEN
Solar/Wind Harmer
6.865
233935AB2-179 C
Solar/Wind Harmer
2.272
231919CHRIST1
Adder
3.94
231920CHRIST2
Adder
3.853
970453AG2-297 GEN
Solar/Wind Harmer
2.134
228260V4-054C
Solar/Wind Harmer
0.789
228309CCLP NUG
Adder
19.863
228309CCLP NUG
Adder
18.894
972141AH1-641 GEN
Solar/Wind Harmer
2.208
964001AG1-254 GEN
Solar/Wind Harmer
1.559
971011AG2-627 GEN
Solar/Wind Harmer
5.863
971535AH1-265 GEN
Solar/Wind Harmer
3.249
227927V4-067C
Solar/Wind Harmer
0.151
228754AB1-001 C
Solar/Wind Harmer
0.106
219137THOSOLAR C
Solar/Wind Harmer
0.911
213942SCHUYLKILL
Adder
2.675
213942SCHUYLKILL
Adder
2.046
213957STHWK3-4
Adder
2.043
213957STHWK3-4
Adder
2.043
219272CLEANLIGHT C
Solar/Wind Harmer
0.136
219914AD2-027 C
Solar/Wind Harmer
0.446
219688LUMSOLAR_S C
Solar/Wind Harmer
0.15
213561DLWR9-10
Adder
2.633
213561DLWR9-10
Adder
2.014
219607WPEMNERT C
Solar/Wind Harmer
0.305
219224BRL12CT4
Adder
6.504
214067T20SOLAR
Solar/Wind Harmer
0.182
213611FALLS1-3
Adder
2.542
213611FALLS1-3
Adder
2.542
20717128DIX_Z2-102
Solar/Wind Harmer
0.941
20715728PEM_W1-119
Solar/Wind Harmer
0.381
20715828PEM_W1-120
Solar/Wind Harmer
0.381
970025AG2-016 GEN
Solar/Wind Harmer
2.008
971189AH1-054 GEN
Solar/Wind Harmer
0.836
207459AE1-142 C O1
Solar/Wind Harmer
0.745
219620RIDERU C
Solar/Wind Harmer
0.039
20714328BYD_X4-031
Solar/Wind Harmer
0.196
20714428HOW_X1-037
Solar/Wind Harmer
0.857
971521AH1-258 GEN
Solar/Wind Harmer
1.865
20720428HOL_W1-112
Solar/Wind Harmer
0.238
20635928PARLN3&4
Adder
5.038
218455CINNBAY_CGEN
Adder
1.235
218526CNTRALGAS2 C
Solar/Wind Harmer
0.251
218524CNTRALGAS1 C
Solar/Wind Harmer
0.25
20675528CPH_W2-050
Solar/Wind Harmer
0.315
218404KENILWRTH C
Adder
0.866
217167KRNY_14
Adder
6.15
217086KRNY_131
Adder
6.098
217147KRNY_1212
Adder
5.849
217147KRNY_1212
Adder
5.745
217146KRNY_1234
Adder
5.732
217146KRNY_1234
Adder
5.693
966261AG1-495 GEN
Solar/Wind Harmer
1.167
20676328BVR_Y1-020
Solar/Wind Harmer
0.213
207511W3-106 GEN
Solar/Wind Harmer
0.422
207530AG1-191 GEN
Solar/Wind Harmer
0.884
20674828DL_W4-046
Solar/Wind Harmer
0.411
971009AG2-626 GEN
Solar/Wind Harmer
1.037
207408W3-077 C
Solar/Wind Harmer
0.319
20675728RH_W2-091
Solar/Wind Harmer
0.216
20675928HOL_W4-097
Solar/Wind Harmer
0.082
207484AF2-139 C O1
Solar/Wind Harmer
0.318
966421AG1-511 GEN
Solar/Wind Harmer
5.407
20675128HRM_W1-127
Solar/Wind Harmer
0.107
20462827N BANGR8
Adder
0.447
209116AE2-175 GEN
Solar/Wind Harmer
2.508
961261AF2-417 GEN
Solar/Wind Harmer
0.589
209026WIENIPP4
Adder
3.047
20486527WR_V4-052
Adder
0.576
209045AE2-271 GEN
Solar/Wind Harmer
8.878
3138216PACIFIC
Solar/Wind Helper
0.039
316411AF1-147_GEN1
Solar/Wind Helper
0.774
316415AF1-147_GEN2
Solar/Wind Helper
0.774
3141426STAFORD
Solar/Wind Helper
0.05
200192DELTA CT1
50/50
1.634
200194DELTA CT3
50/50
1.634
200204Y1-065-CTG1
50/50
3.352
200054ROCKSP 3
50/50
2.138
233998TM1NIN_3.36
Solar/Wind Harmer
1.171
232404W1-003 C
Solar/Wind Harmer
0.926
232917OH NUG6
Adder
8.126
232915OH NUG4
Adder
8.108
232428Y3-058 C
Solar/Wind Harmer
0.771
232919VN10
Adder
2.594
971195AH1-057 GEN
Solar/Wind Harmer
1.012
232426Y1-080 FULL
Solar/Wind Harmer
0.177
970277AG2-181 GEN
Solar/Wind Harmer
4.634
965821AG1-450 GEN
Solar/Wind Harmer
4.811
232434Z2-077 GEN
Solar/Wind Harmer
0.231
233964AF2-378 GEN
Solar/Wind Harmer
0.118
972177AH1-672 GEN
Solar/Wind Harmer
12.405
232901NORTHST
Adder
7.684
233972AC1-094 C
Solar/Wind Harmer
0.612
233954AC2-188 GEN
Solar/Wind Harmer
1.039
233950AC2-186 GEN
Solar/Wind Harmer
0.519
232900DEMECSMY
Adder
8.509
232910NRG_G1
Adder
7.949
234012AE2-112_GEN
Solar/Wind Harmer
2.115
232422X3-066 FULL
Solar/Wind Harmer
0.23
233930AB2-032 GEN
Solar/Wind Harmer
0.765
233915AB1-141 GEN
Solar/Wind Harmer
0.909
231918WEST 1
Adder
2.999
231917EM10
Adder
2.088
228206SHRMN CT
Adder
12.786
228732V1-021 C
Adder
0.145
945431AF1-208 GEN
Solar/Wind Harmer
6.634
970997AG2-616 GEN
Solar/Wind Harmer
7.358
228351V2-046C
Solar/Wind Harmer
1.544
230511AF1-262
Solar/Wind Harmer
0.14
213497CHSTR7-9
Adder
2.09
213497CHSTR7-9
Adder
2.09
228728W1-130C
Solar/Wind Harmer
0.507
230434AG1-499 GEN
Solar/Wind Harmer
0.442
213958STHWK5-6
Adder
2.043
219258KINSLEYDEP C
Solar/Wind Harmer
0.243
219904AC1-010 C
Solar/Wind Harmer
0.282
218660EHAMPSOLAR C
Solar/Wind Harmer
0.13
219287REEVESEAST C
Solar/Wind Harmer
0.997
219686LUMSOLAR_N C
Solar/Wind Harmer
0.15
213560DLW11-12
Adder
2.014
219907AC1-030 C
Solar/Wind Harmer
0.103
219304NAMERICA C
Solar/Wind Harmer
0.226
219222BRL12CT2
Adder
6.504
213611FALLS1-3
Adder
2.542
214194N WALES4
Adder
0.609
20720728JCB_W1-129
Solar/Wind Harmer
0.213
207522AF2-254 C
Solar/Wind Harmer
1.023
207487AE2-000G4
Solar/Wind Harmer
22.387
207445AB1-138_GEN
Solar/Wind Harmer
0.409
20628028LAKEHURS
Adder
1.326
963711AG1-223 GEN
Solar/Wind Harmer
1.035
20714828MDF_W3-079
Solar/Wind Harmer
0.214
219680HOPEWELLV C1
Solar/Wind Harmer
0.053
207454AA2-184 E
Solar/Wind Harmer
0.692
20715228NPK_W1-113
Solar/Wind Harmer
0.297
20742028HF_AC1-207
Solar/Wind Harmer
0.541
217197RE CRAN C
Solar/Wind Harmer
0.368
20635828PARLN1&2
Adder
5.038
20635028RRCT1&2
Adder
7.874
20635128RRCT3&4
Adder
7.601
218428ETC SOLAR C
Solar/Wind Harmer
0.024
217213AMBOY SO C
Solar/Wind Harmer
0.085
972275AH1-722 GEN
Adder
21.186
207528AF2-192 GEN
Solar/Wind Harmer
0.37
20673628F1S_V4-069
Solar/Wind Harmer
0.12
20675428EAM_W2-061
Solar/Wind Harmer
0.126
218449LINSOLAR C
Solar/Wind Harmer
0.672
20676428JCR_X2-075
Solar/Wind Harmer
0.228
217209CENTRL HS C
Solar/Wind Harmer
0.03
217121ECCF
Adder
0.287
217083KRNY_132
Adder
6.15
217208PARK ELE C
Solar/Wind Harmer
0.017
207439AE1-081 C O1
Solar/Wind Harmer
0.039
20674328GAR_V4-001
Solar/Wind Harmer
0.071
20675828AU_W4-064
Solar/Wind Harmer
0.111
971519AH1-257 GEN
Solar/Wind Harmer
1.594
207518AF1-320_GEN
Solar/Wind Harmer
2.301
207437AD2-070 GEN
Solar/Wind Harmer
0.189
20465127PORT CT
Adder
1.88
20671928W4-073
Solar/Wind Harmer
0.271
966181AG1-487 GEN
Solar/Wind Harmer
2.347
208909MACR G3
Adder
98.541
961301AF2-421 GEN
Solar/Wind Harmer
0.572
963151AG1-164 GEN
Solar/Wind Harmer
0.572
209023WIENIPP1
Adder
6.166
209025WIENIPP3
Adder
3.078
209010PEIP 1
Adder
0.369
205941AD2-115 GEN
Solar/Wind Harmer
0.512
212266LOR1
Solar/Wind Harmer
0.071
970237AG2-161 GEN
Solar/Wind Harmer
1.9
961341AF2-425 GEN
Solar/Wind Harmer
0.534
212174INGE
Adder
0.591
20467927PC_Q59Y356
Adder
0.455
20465527S.RDG CT
Adder
1.476
200200DELTA2 CT1
50/50
2.925
200193DELTA CT2
50/50
1.634
200203Y1-065-STG
50/50
5.812
200055ROCKSP 4
50/50
2.093
232907VN8
Adder
27.761
233996TM1833_GEN
Solar/Wind Harmer
1.171
233997TMININ_4.2
Solar/Wind Harmer
1.171
233940AF2-379 C
Solar/Wind Harmer
0.172
232406W1-004 FULL
Solar/Wind Harmer
0.926
232914OH NUG3
Adder
8.162
232916OH NUG5
Adder
8.162
972073AH1-586 GEN
Solar/Wind Harmer
8.661
232921TASLEY2G
Adder
4.77
233994AC2-023 GEN
Solar/Wind Harmer
2.484
233900O-025 C
Adder
1.088
234015AF2-250 C
Solar/Wind Harmer
0.111
233990AG1-397 GEN
Solar/Wind Harmer
1.06
960671AF2-358 GEN
Solar/Wind Harmer
16.55
972133AH1-634 GEN
Solar/Wind Harmer
9.159
232417X3-008 C
Solar/Wind Harmer
1.848
233971AC1-093 C
Solar/Wind Harmer
0.724
970695AG2-447 GEN
Solar/Wind Harmer
3.305
233952AC2-187 GEN
Solar/Wind Harmer
1.039
233918AB1-142 GEN
Solar/Wind Harmer
0.909
233982AB2-133 GEN
Solar/Wind Harmer
4.467
972251AH1-710 GEN
Adder
40.011
228202CUMB CT
Adder
12.754
228711V2-041C
Solar/Wind Harmer
0.464
971553AH1-274 GEN
Solar/Wind Harmer
1.865
230430AE1-229_GEN
Solar/Wind Harmer
6.749
213497CHSTR7-9
Adder
2.09
230415AB2-049 C
Solar/Wind Harmer
0.145
228304LOGAN
Adder
16.588
228729W2-030 C
Solar/Wind Harmer
0.44
213958STHWK5-6
Adder
2.043
219623KINSLEYBEA C
Solar/Wind Harmer
0.32
219766PARADISE C
Solar/Wind Harmer
0.235
219291REEVESSOUT C
Solar/Wind Harmer
0.045
219912AD2-042 GEN
Solar/Wind Harmer
0.592
213560DLW11-12
Adder
2.014
219236SOUTHERNHQ C
Solar/Wind Harmer
0.05
219906AC1-017 C
Solar/Wind Harmer
0.163
219610FLORENCE C
Solar/Wind Harmer
1.009
219348LDSOLAR C
Solar/Wind Harmer
0.436
219221BRL12CT1
Adder
6.504
219223BRL12CT3
Adder
6.504
213815MOSER1-3
Adder
2.585
959561AF2-247 GEN
Solar/Wind Harmer
0.348
20716028EGP_W2-019
Solar/Wind Harmer
0.331
20720828JCB_W4-025
Solar/Wind Harmer
0.323
20715028HAN_X4-015
Solar/Wind Harmer
0.213
20636028O CRK C1
Adder
5.023
971667AH1-334 GEN
Solar/Wind Harmer
1.939
219727YARDVSOLFA C
Solar/Wind Harmer
0.641
20714528FRN_Y2-051
Solar/Wind Harmer
0.206
219276PARKLANDSO C
Solar/Wind Harmer
0.323
219918AC2-009 C
Solar/Wind Harmer
0.043
20716228APLW2-078
Solar/Wind Harmer
0.611
20720528MAN_W1-024
Solar/Wind Harmer
0.176
967451AG2-055 C O1
Solar/Wind Harmer
119.13
219612MATRIX C
Solar/Wind Harmer
0.126
218438BLK ROCK C
Solar/Wind Harmer
0.093
20635828PARLN1&2
Adder
2.282
20635928PARLN3&4
Adder
2.282
20635028RRCT1&2
Adder
7.997
20635128RRCT3&4
Adder
6.63
219908AB1-139 C
Solar/Wind Harmer
0.257
219919AE1-041 FULL
Solar/Wind Harmer
0.027
219249CENTRALDIV C
Solar/Wind Harmer
0.027
20673728F2S_V4-070
Solar/Wind Harmer
0.12
217211CAMDEN ST C
Solar/Wind Harmer
0.016
217186ESSEX_G9
Adder
10.578
217169METRODIV C
Solar/Wind Harmer
0.026
217194REDH C
Solar/Wind Harmer
0.326
20676728BRNX1-095
Solar/Wind Harmer
0.115
207510AF2-138 C
Solar/Wind Harmer
1.144
20674628WNG_W3-110
Solar/Wind Harmer
0.259
971007AG2-625 GEN
Solar/Wind Harmer
1.625
20466127PORT 5CT
Adder
16.596
20633028GILCT9
Adder
17.734
966181AG1-487 GEN
Solar/Wind Harmer
0.157
20465427SHAW CT
Adder
2.405
963161AG1-165 GEN
Solar/Wind Harmer
0.572
209025WIENIPP3
Adder
3.016
963071AG1-156 GEN
Solar/Wind Harmer
1.58
970095AG2-074 GEN
Solar/Wind Harmer
3.586
209027LOR2_Q27
Solar/Wind Harmer
2.475
209022WHFR IPP
Adder
1.777
961331AF2-424 GEN
Solar/Wind Harmer
0.534
961421AF2-433 GEN
Solar/Wind Harmer
0.533
957921AF2-086 GEN
Solar/Wind Harmer
0.518
209142AF1-226 GEN
Solar/Wind Harmer
3.084
209093AE2-110 GEN
Solar/Wind Harmer
1.332
209120AE2-241 GEN
Solar/Wind Harmer
1.763
972245AH1-707 GEN
Adder
2.851
227287AC2-120 GEN
Solar/Wind Helper
0.355
226910AB2-157 C
Solar/Wind Helper
0.014
3141196NOKESVL
Solar/Wind Helper
0.902
HAMLETPJM->LTFIMP_HAMLET
CLTF
4.129
G-007ALTFEXP_G-007A->PJM
CMTX
34.779
CBM NorthLTFEXP_CBM-N->PJM
CBM
50.229
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
2.936
BlueGrassPJM->LTFIMP_BlueG
CLTF
9.156
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
89.902
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.383
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
14.015

Details for CNASTONE-BRIGHTON 500.0 kV Ckt 1 line l/o PECO_P4_PEACH035_SRT-A/* $ CHESCO $ PECO_P4_PEACH035 $ STBK


Base Case Flowgate

Area:PJM
Facility Description:
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
Contingency Name:
PECO_P4_PEACH035_SRT-A/* $ CHESCO $ PECO_P4_PEACH035 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.95 %
Rating:3098.0 MVA
Rating Type:B
MVA to Mitigate:3499.19
MW Contribution:5.79
Bus #Bus NameTypeMW Contribution
972281AH1-725 GEN
50/50
142.586
200201DELTA2 CT2
50/50
2.982
200034PCHBTM 2
50/50
17.358
200035PCHBTM 3
50/50
17.576
200205Y1-065-CTG2
50/50
3.407
232918OH NUG7
50/50
8.574
232905CHERITON_25
50/50
2.398
232926CRISFLD1
50/50
1.918
200202DELTA2 ST
50/50
5.061
200195DELTA ST
50/50
2.575
200052ROCKSP 1
50/50
2.152
200053ROCKSP 2
50/50
2.106
232912OH NUG1
50/50
8.632
232913OH NUG2
50/50
8.517
232616GEN FOOD
50/50
0.159
233923SMA
Solar/Wind Harmer
4.278
234033AF1-007_GEN
Solar/Wind Harmer
21.534
232904IR4
Adder
74.457
233990AG1-397 GEN
Solar/Wind Harmer
0.051
232432Z2-076 GEN
Solar/Wind Harmer
0.122
232920IR10
Adder
2.91
233973AC2-185 C
Solar/Wind Harmer
3.325
233955AB2-172 GEN
Solar/Wind Harmer
4.602
232813VAUGHN
Adder
0.54
233968AD2-076_GEN
Solar/Wind Harmer
6.062
970597AG2-380 GEN
Solar/Wind Harmer
3.807
233987AB2-037 GEN
Solar/Wind Harmer
10.501
233901CHERRYDALE C
Solar/Wind Harmer
1.037
232408W1-005 C
Solar/Wind Harmer
0.922
232410W1-006 C
Solar/Wind Harmer
0.922
970545AG2-347 GEN
Solar/Wind Harmer
60.26
972069AH1-584 GEN
Solar/Wind Harmer
8.248
972071AH1-585 GEN
Solar/Wind Harmer
8.248
971149AH1-027 GEN
Solar/Wind Harmer
3.117
971747AH1-380 GEN
Solar/Wind Harmer
3.299
231940T-011
Adder
0.687
233939AC1-091 C
Solar/Wind Harmer
0.808
233970AC1-092 C
Solar/Wind Harmer
0.808
233946AB2-136 GEN
Solar/Wind Harmer
3.674
234036AF2-325 C
Solar/Wind Harmer
0.844
234041AC1-190 GEN
Solar/Wind Harmer
8.241
232899W1-062
Adder
8.846
233984AB2-036 GEN
Solar/Wind Harmer
11.414
232424Y1-079 C
Solar/Wind Harmer
0.516
234014AF1-036_GEN
Solar/Wind Harmer
2.474
231131BLOOM ENRGY
Adder
3.973
233944AB2-135 GEN
Solar/Wind Harmer
4.779
233933AB2-153 GEN
Solar/Wind Harmer
1.026
232416X2-083
Adder
0.405
228251CARLLS#4
Adder
0.48
230422AE1-104_GEN1
Solar/Wind Harmer
25.56
230425AE1-104_GEN2
Solar/Wind Harmer
25.56
230433AD2-135 GEN
Solar/Wind Harmer
0.077
228307PCLP GT
Adder
9.119
230407AD2-065 C
Solar/Wind Harmer
0.099
228304LOGAN
Adder
18.2
972233AH1-701 GEN
Adder
3.147
213589EDDYSTN4
Adder
59.064
213587EDDYSTN3
Adder
59.053
219921AF1-264
Solar/Wind Harmer
0.107
219615MILLCREEK C
Solar/Wind Harmer
0.172
213535CROYDN11
Adder
7.341
213815MOSER1-3
Adder
2.535
213815MOSER1-3
Adder
2.535
20716428NHV_W2-082
Solar/Wind Harmer
1.256
207500AE2-000G1
Solar/Wind Harmer
22.187
207497AE2-000G2
Solar/Wind Harmer
22.187
207507AE2-000G3
Solar/Wind Harmer
22.187
20636128O CRK C2
Adder
4.539
963401AG1-189 GEN
Solar/Wind Harmer
0.808
963391AG1-188 GEN
Solar/Wind Harmer
1.346
20714928UPF_X1-085
Solar/Wind Harmer
0.285
219114HARTZY_C
Solar/Wind Harmer
0.582
20628028LAKEHURS
Adder
0.664
219817TRENTONSOL C
Solar/Wind Harmer
0.758
20641628MLH_W1-032
Solar/Wind Harmer
0.201
20720628TIN_W1-124
Solar/Wind Harmer
0.684
20716928W4-060COL
Solar/Wind Harmer
0.483
924131AB2-057 GEN
Solar/Wind Harmer
0.693
218440SUMMTASSOC C
Solar/Wind Harmer
0.086
218418LINDEN_G5
Adder
11.427
218419LINDEN_G6
Adder
11.427
972260AH1-715 GEN1
Adder
9.15
20673828FLE_V3-070
Solar/Wind Harmer
0.304
219036LINDEN_G7
Adder
11.076
219035LINDEN_G8
Adder
10.918
972261AH1-715 GEN2
Adder
10.602
207442AE1-156 GEN
Solar/Wind Harmer
0.493
20676128MHD_W3-029
Solar/Wind Harmer
0.316
217081WEATEXAS C
Solar/Wind Harmer
0.057
217202FBANKSOLAR C
Solar/Wind Harmer
0.048
217201HACKENSOLA C
Solar/Wind Harmer
0.048
972237AH1-703 GEN
Adder
6.642
217206BARNGR HS C
Solar/Wind Harmer
0.02
217086KRNY_131
Adder
6.113
217083KRNY_132
Adder
6.061
20671828STAW2-080
Solar/Wind Harmer
0.069
217204WCALDSOLAR C
Solar/Wind Harmer
0.048
20674528F3S_W2-016
Solar/Wind Harmer
0.918
20676228FRD_X1-012
Solar/Wind Harmer
0.377
207471AF2-354 C
Solar/Wind Harmer
0.323
20674928WA_W3-044
Solar/Wind Harmer
0.304
964851AG1-348 GEN
Solar/Wind Harmer
1.104
20634528N27_Y2-018
Solar/Wind Harmer
0.169
20465127PORT CT
Adder
2.478
20674128FR_U2-059
Solar/Wind Harmer
0.115
966111AG1-480 GEN
Solar/Wind Harmer
0.053
966111AG1-480 GEN
Solar/Wind Harmer
2.038
211065PSPA IPP
Solar/Wind Harmer
0.27
211065PSPA IPP
Solar/Wind Harmer
0.27
209029WAYMART-WD
Solar/Wind Harmer
1.643
209009PEIP 2
Adder
4.462
209010PEIP 1
Adder
2.022
209010PEIP 1
Adder
0.296
208972BECR K09
Solar/Wind Harmer
0.596
961541AF2-445A GEN
Solar/Wind Harmer
1.77
961431AF2-434 GEN
Solar/Wind Harmer
0.531
20465527S.RDG CT
Adder
1.424
226929AD2-058 GEN
Solar/Wind Helper
0.1
200192DELTA CT1
50/50
1.666
200194DELTA CT3
50/50
1.666
200204Y1-065-CTG1
50/50
3.407
200054ROCKSP 3
50/50
2.173
231912HR6
50/50
1.324
231913HR7
50/50
1.324
232917OH NUG6
50/50
8.594
232915OH NUG4
50/50
8.574
233920W3-032A-CTG1
50/50
2.026
233921W3-032A-STG1
50/50
1.216
232919VN10
50/50
2.742
232910NRG_G1
50/50
8.401
233998TM1NIN_3.36
Solar/Wind Harmer
1.167
232404W1-003 C
Solar/Wind Harmer
0.922
232901NORTHST
Adder
7.664
232434Z2-077 GEN
Solar/Wind Harmer
0.231
232428Y3-058 C
Solar/Wind Harmer
0.769
971195AH1-057 GEN
Solar/Wind Harmer
1.008
965821AG1-450 GEN
Solar/Wind Harmer
4.793
232426Y1-080 FULL
Solar/Wind Harmer
0.176
972177AH1-672 GEN
Solar/Wind Harmer
12.366
970277AG2-181 GEN
Solar/Wind Harmer
4.617
233972AC1-094 C
Solar/Wind Harmer
0.611
233964AF2-378 GEN
Solar/Wind Harmer
0.118
232900DEMECSMY
Adder
8.485
233954AC2-188 GEN
Solar/Wind Harmer
1.035
233950AC2-186 GEN
Solar/Wind Harmer
0.518
234012AE2-112_GEN
Solar/Wind Harmer
2.103
232422X3-066 FULL
Solar/Wind Harmer
0.229
233930AB2-032 GEN
Solar/Wind Harmer
0.761
233915AB1-141 GEN
Solar/Wind Harmer
0.904
231918WEST 1
Adder
2.959
231917EM10
Adder
2.056
228206SHRMN CT
Adder
12.675
228732V1-021 C
Adder
0.144
945431AF1-208 GEN
Solar/Wind Harmer
6.567
970997AG2-616 GEN
Solar/Wind Harmer
7.28
228351V2-046C
Solar/Wind Harmer
1.527
230511AF1-262
Solar/Wind Harmer
0.139
228728W1-130C
Solar/Wind Harmer
0.502
230434AG1-499 GEN
Solar/Wind Harmer
0.437
213497CHSTR7-9
Adder
2.025
213497CHSTR7-9
Adder
2.025
219258KINSLEYDEP C
Solar/Wind Harmer
0.239
219904AC1-010 C
Solar/Wind Harmer
0.278
218660EHAMPSOLAR C
Solar/Wind Harmer
0.128
219686LUMSOLAR_N C
Solar/Wind Harmer
0.148
219287REEVESEAST C
Solar/Wind Harmer
0.986
213958STHWK5-6
Adder
1.987
219907AC1-030 C
Solar/Wind Harmer
0.101
213560DLW11-12
Adder
1.968
219304NAMERICA C
Solar/Wind Harmer
0.223
219222BRL12CT2
Adder
6.412
213611FALLS1-3
Adder
2.506
20720728JCB_W1-129
Solar/Wind Harmer
0.211
207522AF2-254 C
Solar/Wind Harmer
1.013
207487AE2-000G4
Solar/Wind Harmer
22.187
214194N WALES4
Adder
0.599
207445AB1-138_GEN
Solar/Wind Harmer
0.405
20628028LAKEHURS
Adder
1.314
963711AG1-223 GEN
Solar/Wind Harmer
1.026
20714828MDF_W3-079
Solar/Wind Harmer
0.212
207454AA2-184 E
Solar/Wind Harmer
0.686
219680HOPEWELLV C1
Solar/Wind Harmer
0.052
20715228NPK_W1-113
Solar/Wind Harmer
0.295
20742028HF_AC1-207
Solar/Wind Harmer
0.537
217197RE CRAN C
Solar/Wind Harmer
0.365
20635828PARLN1&2
Adder
4.995
20635028RRCT1&2
Adder
7.808
20635128RRCT3&4
Adder
7.536
218428ETC SOLAR C
Solar/Wind Harmer
0.024
217213AMBOY SO C
Solar/Wind Harmer
0.085
972275AH1-722 GEN
Adder
21.007
218449LINSOLAR C
Solar/Wind Harmer
0.666
207528AF2-192 GEN
Solar/Wind Harmer
0.367
20673628F1S_V4-069
Solar/Wind Harmer
0.119
20675428EAM_W2-061
Solar/Wind Harmer
0.125
20676428JCR_X2-075
Solar/Wind Harmer
0.226
217209CENTRL HS C
Solar/Wind Harmer
0.029
217121ECCF
Adder
0.285
217083KRNY_132
Adder
6.1
217208PARK ELE C
Solar/Wind Harmer
0.017
207439AE1-081 C O1
Solar/Wind Harmer
0.038
20674328GAR_V4-001
Solar/Wind Harmer
0.07
20675828AU_W4-064
Solar/Wind Harmer
0.11
971519AH1-257 GEN
Solar/Wind Harmer
1.583
207518AF1-320_GEN
Solar/Wind Harmer
2.284
207437AD2-070 GEN
Solar/Wind Harmer
0.188
20465127PORT CT
Adder
1.867
20671928W4-073
Solar/Wind Harmer
0.269
966181AG1-487 GEN
Solar/Wind Harmer
2.33
208909MACR G3
Adder
97.888
961301AF2-421 GEN
Solar/Wind Harmer
0.569
963151AG1-164 GEN
Solar/Wind Harmer
0.569
209023WIENIPP1
Adder
6.136
209025WIENIPP3
Adder
3.063
209010PEIP 1
Adder
0.368
205941AD2-115 GEN
Solar/Wind Harmer
0.51
212266LOR1
Solar/Wind Harmer
0.071
970237AG2-161 GEN
Solar/Wind Harmer
1.892
961341AF2-425 GEN
Solar/Wind Harmer
0.532
212174INGE
Adder
0.588
20467927PC_Q59Y356
Adder
0.453
20465527S.RDG CT
Adder
1.472
232436AB1-176 C
Solar/Wind Harmer
0.209
231906DC3 NUG
Adder
12.77
231902DC CT7
Adder
10.209
231907DC10
Adder
3.188
971983AH1-536 GEN
Solar/Wind Harmer
6.824
233935AB2-179 C
Solar/Wind Harmer
2.252
231919CHRIST1
Adder
3.887
231920CHRIST2
Adder
3.8
970453AG2-297 GEN
Solar/Wind Harmer
2.117
228260V4-054C
Solar/Wind Harmer
0.782
228309CCLP NUG
Adder
19.643
228309CCLP NUG
Adder
18.685
972141AH1-641 GEN
Solar/Wind Harmer
2.184
964001AG1-254 GEN
Solar/Wind Harmer
1.542
971011AG2-627 GEN
Solar/Wind Harmer
5.793
971535AH1-265 GEN
Solar/Wind Harmer
3.216
227927V4-067C
Solar/Wind Harmer
0.15
228754AB1-001 C
Solar/Wind Harmer
0.105
219137THOSOLAR C
Solar/Wind Harmer
0.897
219272CLEANLIGHT C
Solar/Wind Harmer
0.134
219688LUMSOLAR_S C
Solar/Wind Harmer
0.148
219914AD2-027 C
Solar/Wind Harmer
0.439
213942SCHUYLKILL
Adder
2.6
213942SCHUYLKILL
Adder
1.988
213957STHWK3-4
Adder
1.987
213957STHWK3-4
Adder
1.987
213561DLWR9-10
Adder
2.574
213561DLWR9-10
Adder
1.968
219607WPEMNERT C
Solar/Wind Harmer
0.301
219224BRL12CT4
Adder
6.412
214067T20SOLAR
Solar/Wind Harmer
0.179
213611FALLS1-3
Adder
2.506
213611FALLS1-3
Adder
2.506
20717128DIX_Z2-102
Solar/Wind Harmer
0.932
20715728PEM_W1-119
Solar/Wind Harmer
0.377
20715828PEM_W1-120
Solar/Wind Harmer
0.377
970025AG2-016 GEN
Solar/Wind Harmer
1.989
971189AH1-054 GEN
Solar/Wind Harmer
0.828
207459AE1-142 C O1
Solar/Wind Harmer
0.738
219620RIDERU C
Solar/Wind Harmer
0.038
20714328BYD_X4-031
Solar/Wind Harmer
0.194
20714428HOW_X1-037
Solar/Wind Harmer
0.849
971521AH1-258 GEN
Solar/Wind Harmer
1.848
20720428HOL_W1-112
Solar/Wind Harmer
0.236
20635928PARLN3&4
Adder
4.995
218455CINNBAY_CGEN
Adder
1.224
218526CNTRALGAS2 C
Solar/Wind Harmer
0.248
218524CNTRALGAS1 C
Solar/Wind Harmer
0.248
20675528CPH_W2-050
Solar/Wind Harmer
0.312
218404KENILWRTH C
Adder
0.859
217167KRNY_14
Adder
6.1
217086KRNY_131
Adder
6.048
217147KRNY_1212
Adder
5.802
217147KRNY_1212
Adder
5.699
217146KRNY_1234
Adder
5.686
217146KRNY_1234
Adder
5.647
966261AG1-495 GEN
Solar/Wind Harmer
1.156
20676328BVR_Y1-020
Solar/Wind Harmer
0.211
207511W3-106 GEN
Solar/Wind Harmer
0.419
207530AG1-191 GEN
Solar/Wind Harmer
0.877
20674828DL_W4-046
Solar/Wind Harmer
0.408
971009AG2-626 GEN
Solar/Wind Harmer
1.029
207408W3-077 C
Solar/Wind Harmer
0.317
20675728RH_W2-091
Solar/Wind Harmer
0.214
200200DELTA2 CT1
50/50
2.982
200193DELTA CT2
50/50
1.666
200203Y1-065-STG
50/50
5.908
200055ROCKSP 4
50/50
2.128
231914HR8
50/50
2.013
231911HR5
50/50
1.324
232907VN8
50/50
29.353
232914OH NUG3
50/50
8.632
232916OH NUG5
50/50
8.632
232921TASLEY2G
50/50
5.045
234034AF2-060
50/50
1.726
232911NRG_G2
50/50
0.459
233996TM1833_GEN
Solar/Wind Harmer
1.167
233997TMININ_4.2
Solar/Wind Harmer
1.167
232406W1-004 FULL
Solar/Wind Harmer
0.922
233940AF2-379 C
Solar/Wind Harmer
0.172
972133AH1-634 GEN
Solar/Wind Harmer
9.13
972073AH1-586 GEN
Solar/Wind Harmer
8.632
233990AG1-397 GEN
Solar/Wind Harmer
1.056
233900O-025 C
Adder
1.085
234015AF2-250 C
Solar/Wind Harmer
0.111
233994AC2-023 GEN
Solar/Wind Harmer
2.476
960671AF2-358 GEN
Solar/Wind Harmer
16.489
233971AC1-093 C
Solar/Wind Harmer
0.722
970695AG2-447 GEN
Solar/Wind Harmer
3.297
232417X3-008 C
Solar/Wind Harmer
1.841
233952AC2-187 GEN
Solar/Wind Harmer
1.035
233918AB1-142 GEN
Solar/Wind Harmer
0.904
233982AB2-133 GEN
Solar/Wind Harmer
4.44
972251AH1-710 GEN
Adder
39.944
228202CUMB CT
Adder
12.647
228711V2-041C
Solar/Wind Harmer
0.46
971553AH1-274 GEN
Solar/Wind Harmer
1.849
230430AE1-229_GEN
Solar/Wind Harmer
6.678
230415AB2-049 C
Solar/Wind Harmer
0.143
228729W2-030 C
Solar/Wind Harmer
0.436
228304LOGAN
Adder
16.369
213497CHSTR7-9
Adder
2.025
219623KINSLEYBEA C
Solar/Wind Harmer
0.316
219291REEVESSOUT C
Solar/Wind Harmer
0.044
219766PARADISE C
Solar/Wind Harmer
0.231
219912AD2-042 GEN
Solar/Wind Harmer
0.583
213958STHWK5-6
Adder
1.987
219236SOUTHERNHQ C
Solar/Wind Harmer
0.049
213560DLW11-12
Adder
1.968
219906AC1-017 C
Solar/Wind Harmer
0.161
219610FLORENCE C
Solar/Wind Harmer
0.995
219348LDSOLAR C
Solar/Wind Harmer
0.43
219221BRL12CT1
Adder
6.412
219223BRL12CT3
Adder
6.412
213815MOSER1-3
Adder
2.535
20716028EGP_W2-019
Solar/Wind Harmer
0.328
959561AF2-247 GEN
Solar/Wind Harmer
0.343
20720828JCB_W4-025
Solar/Wind Harmer
0.32
20715028HAN_X4-015
Solar/Wind Harmer
0.211
20636028O CRK C1
Adder
4.978
971667AH1-334 GEN
Solar/Wind Harmer
1.921
219727YARDVSOLFA C
Solar/Wind Harmer
0.634
20714528FRN_Y2-051
Solar/Wind Harmer
0.205
219276PARKLANDSO C
Solar/Wind Harmer
0.319
219918AC2-009 C
Solar/Wind Harmer
0.042
20716228APLW2-078
Solar/Wind Harmer
0.606
20720528MAN_W1-024
Solar/Wind Harmer
0.174
967451AG2-055 C O1
Solar/Wind Harmer
118.172
219612MATRIX C
Solar/Wind Harmer
0.125
218438BLK ROCK C
Solar/Wind Harmer
0.093
20635828PARLN1&2
Adder
2.262
20635928PARLN3&4
Adder
2.262
20635028RRCT1&2
Adder
7.93
20635128RRCT3&4
Adder
6.574
219908AB1-139 C
Solar/Wind Harmer
0.254
219919AE1-041 FULL
Solar/Wind Harmer
0.027
219249CENTRALDIV C
Solar/Wind Harmer
0.026
20673728F2S_V4-070
Solar/Wind Harmer
0.119
217211CAMDEN ST C
Solar/Wind Harmer
0.016
217186ESSEX_G9
Adder
10.493
217169METRODIV C
Solar/Wind Harmer
0.026
217194REDH C
Solar/Wind Harmer
0.323
20676728BRNX1-095
Solar/Wind Harmer
0.114
207510AF2-138 C
Solar/Wind Harmer
1.136
20674628WNG_W3-110
Solar/Wind Harmer
0.257
971007AG2-625 GEN
Solar/Wind Harmer
1.614
20466127PORT 5CT
Adder
16.482
20633028GILCT9
Adder
17.608
966181AG1-487 GEN
Solar/Wind Harmer
0.156
20465427SHAW CT
Adder
2.389
963161AG1-165 GEN
Solar/Wind Harmer
0.569
209025WIENIPP3
Adder
3.001
963071AG1-156 GEN
Solar/Wind Harmer
1.572
970095AG2-074 GEN
Solar/Wind Harmer
3.569
209027LOR2_Q27
Solar/Wind Harmer
2.464
209022WHFR IPP
Adder
1.769
961331AF2-424 GEN
Solar/Wind Harmer
0.532
961421AF2-433 GEN
Solar/Wind Harmer
0.531
957921AF2-086 GEN
Solar/Wind Harmer
0.516
209142AF1-226 GEN
Solar/Wind Harmer
3.072
209093AE2-110 GEN
Solar/Wind Harmer
1.327
209120AE2-241 GEN
Solar/Wind Harmer
1.756
972245AH1-707 GEN
Adder
2.841
227287AC2-120 GEN
Solar/Wind Helper
0.35
226910AB2-157 C
Solar/Wind Helper
0.014
20675928HOL_W4-097
Solar/Wind Harmer
0.082
207484AF2-139 C O1
Solar/Wind Harmer
0.316
966421AG1-511 GEN
Solar/Wind Harmer
5.37
20675128HRM_W1-127
Solar/Wind Harmer
0.106
20462827N BANGR8
Adder
0.444
209116AE2-175 GEN
Solar/Wind Harmer
2.492
961261AF2-417 GEN
Solar/Wind Harmer
0.586
209026WIENIPP4
Adder
3.032
20486527WR_V4-052
Adder
0.574
209045AE2-271 GEN
Solar/Wind Harmer
8.844
3138216PACIFIC
Solar/Wind Helper
0.038
316411AF1-147_GEN1
Solar/Wind Helper
0.764
316415AF1-147_GEN2
Solar/Wind Helper
0.764
3141426STAFORD
Solar/Wind Helper
0.049
HAMLETPJM->LTFIMP_HAMLET
CLTF
4.054
G-007ALTFEXP_G-007A->PJM
CMTX
34.484
CBM NorthLTFEXP_CBM-N->PJM
CBM
49.986
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
2.868
BlueGrassPJM->LTFIMP_BlueG
CLTF
8.943
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
89.172
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.338
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
13.696

Details for CNASTONE-BRIGHTON 500.0 kV Ckt 1 line l/o BG_P7_CNSTN_NWEST2_SRT-A


Base Case Flowgate

Area:PJM
Facility Description:
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
Contingency Name:
BG_P7_CNSTN_NWEST2_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:112.85 %
Rating:3098.0 MVA
Rating Type:B
MVA to Mitigate:3496.21
MW Contribution:4.93
Bus #Bus NameTypeMW Contribution
972281AH1-725 GEN
50/50
123.829
200201DELTA2 CT2
50/50
2.126
200034PCHBTM 2
50/50
12.381
200205Y1-065-CTG2
50/50
2.471
200035PCHBTM 3
50/50
12.304
200061HUNTR401
50/50
2.947
233987AB2-037 GEN
Solar/Wind Harmer
8.367
233901CHERRYDALE C
Solar/Wind Harmer
0.827
232408W1-005 C
Solar/Wind Harmer
0.735
232410W1-006 C
Solar/Wind Harmer
0.735
972069AH1-584 GEN
Solar/Wind Harmer
6.576
972071AH1-585 GEN
Solar/Wind Harmer
6.576
232918OH NUG7
Adder
6.442
971747AH1-380 GEN
Solar/Wind Harmer
2.63
232905CHERITON_25
Adder
1.802
232926CRISFLD1
Adder
1.441
970545AG2-347 GEN
Solar/Wind Harmer
48.042
231940T-011
Adder
0.548
233946AB2-136 GEN
Solar/Wind Harmer
2.93
971149AH1-027 GEN
Solar/Wind Harmer
2.485
234036AF2-325 C
Solar/Wind Harmer
0.673
234041AC1-190 GEN
Solar/Wind Harmer
6.574
233939AC1-091 C
Solar/Wind Harmer
0.645
233970AC1-092 C
Solar/Wind Harmer
0.645
232899W1-062
Adder
7.056
233984AB2-036 GEN
Solar/Wind Harmer
9.124
232424Y1-079 C
Solar/Wind Harmer
0.412
234014AF1-036_GEN
Solar/Wind Harmer
1.981
231131BLOOM ENRGY
Adder
3.185
233944AB2-135 GEN
Solar/Wind Harmer
3.829
233933AB2-153 GEN
Solar/Wind Harmer
0.823
200192DELTA CT1
50/50
1.188
200194DELTA CT3
50/50
1.188
200204Y1-065-CTG1
50/50
2.471
200054ROCKSP 3
50/50
1.576
233998TM1NIN_3.36
Solar/Wind Harmer
0.93
232404W1-003 C
Solar/Wind Harmer
0.735
232917OH NUG6
Adder
6.457
232915OH NUG4
Adder
6.442
232428Y3-058 C
Solar/Wind Harmer
0.613
232434Z2-077 GEN
Solar/Wind Harmer
0.184
971195AH1-057 GEN
Solar/Wind Harmer
0.804
232919VN10
Adder
2.061
232426Y1-080 FULL
Solar/Wind Harmer
0.14
970277AG2-181 GEN
Solar/Wind Harmer
3.682
965821AG1-450 GEN
Solar/Wind Harmer
3.823
233964AF2-378 GEN
Solar/Wind Harmer
0.094
232901NORTHST
Adder
6.109
972177AH1-672 GEN
Solar/Wind Harmer
9.861
233972AC1-094 C
Solar/Wind Harmer
0.487
232900DEMECSMY
Adder
6.768
233954AC2-188 GEN
Solar/Wind Harmer
0.826
233950AC2-186 GEN
Solar/Wind Harmer
0.413
232910NRG_G1
Adder
6.326
234012AE2-112_GEN
Solar/Wind Harmer
1.684
232422X3-066 FULL
Solar/Wind Harmer
0.183
233930AB2-032 GEN
Solar/Wind Harmer
0.61
233915AB1-141 GEN
Solar/Wind Harmer
0.724
231918WEST 1
Adder
2.416
231917EM10
Adder
1.688
228206SHRMN CT
Adder
10.704
228732V1-021 C
Adder
0.122
945431AF1-208 GEN
Solar/Wind Harmer
5.565
970997AG2-616 GEN
Solar/Wind Harmer
6.177
228351V2-046C
Solar/Wind Harmer
1.297
230511AF1-262
Solar/Wind Harmer
0.118
228728W1-130C
Solar/Wind Harmer
0.427
200202DELTA2 ST
50/50
3.608
200195DELTA ST
50/50
1.836
200052ROCKSP 1
50/50
1.561
200053ROCKSP 2
50/50
1.527
200058HUNTR101
50/50
1.547
200059HUNTR201
50/50
1.547
200060HUNTR301
50/50
1.547
233923SMA
Solar/Wind Harmer
3.41
232912OH NUG1
Adder
6.486
232913OH NUG2
Adder
6.399
234033AF1-007_GEN
Solar/Wind Harmer
17.168
233990AG1-397 GEN
Solar/Wind Harmer
0.041
232432Z2-076 GEN
Solar/Wind Harmer
0.097
232904IR4
Adder
59.36
232920IR10
Adder
2.32
233955AB2-172 GEN
Solar/Wind Harmer
3.671
233973AC2-185 C
Solar/Wind Harmer
2.651
232813VAUGHN
Adder
0.432
233968AD2-076_GEN
Solar/Wind Harmer
4.853
970597AG2-380 GEN
Solar/Wind Harmer
3.047
232436AB1-176 C
Solar/Wind Harmer
0.168
231906DC3 NUG
Adder
10.232
231902DC CT7
Adder
8.18
231907DC10
Adder
2.554
971983AH1-536 GEN
Solar/Wind Harmer
5.47
233935AB2-179 C
Solar/Wind Harmer
1.817
231919CHRIST1
Adder
3.177
231920CHRIST2
Adder
3.106
970453AG2-297 GEN
Solar/Wind Harmer
1.784
228260V4-054C
Solar/Wind Harmer
0.662
228309CCLP NUG
Adder
16.662
228309CCLP NUG
Adder
15.85
972141AH1-641 GEN
Solar/Wind Harmer
1.853
964001AG1-254 GEN
Solar/Wind Harmer
1.309
971011AG2-627 GEN
Solar/Wind Harmer
4.931
971535AH1-265 GEN
Solar/Wind Harmer
2.736
227927V4-067C
Solar/Wind Harmer
0.127
228754AB1-001 C
Solar/Wind Harmer
0.089
219137THOSOLAR C
Solar/Wind Harmer
0.772
213942SCHUYLKILL
Adder
2.268
213942SCHUYLKILL
Adder
1.735
213957STHWK3-4
Adder
1.734
213957STHWK3-4
Adder
1.734
219272CLEANLIGHT C
Solar/Wind Harmer
0.116
219914AD2-027 C
Solar/Wind Harmer
0.381
219688LUMSOLAR_S C
Solar/Wind Harmer
0.128
213561DLWR9-10
Adder
2.252
213561DLWR9-10
Adder
1.722
219607WPEMNERT C
Solar/Wind Harmer
0.264
219224BRL12CT4
Adder
5.617
214067T20SOLAR
Solar/Wind Harmer
0.158
213611FALLS1-3
Adder
2.214
213611FALLS1-3
Adder
2.214
20717128DIX_Z2-102
Solar/Wind Harmer
0.824
20715728PEM_W1-119
Solar/Wind Harmer
0.333
20715828PEM_W1-120
Solar/Wind Harmer
0.333
970025AG2-016 GEN
Solar/Wind Harmer
1.765
971189AH1-054 GEN
Solar/Wind Harmer
0.735
207459AE1-142 C O1
Solar/Wind Harmer
0.657
219620RIDERU C
Solar/Wind Harmer
0.035
20714328BYD_X4-031
Solar/Wind Harmer
0.175
20714428HOW_X1-037
Solar/Wind Harmer
0.766
971521AH1-258 GEN
Solar/Wind Harmer
1.678
20720428HOL_W1-112
Solar/Wind Harmer
0.214
20635928PARLN3&4
Adder
4.582
218455CINNBAY_CGEN
Adder
1.125
218526CNTRALGAS2 C
Solar/Wind Harmer
0.229
218524CNTRALGAS1 C
Solar/Wind Harmer
0.229
20675528CPH_W2-050
Solar/Wind Harmer
0.289
218404KENILWRTH C
Adder
0.806
217167KRNY_14
Adder
5.741
217086KRNY_131
Adder
5.692
217147KRNY_1212
Adder
5.461
217147KRNY_1212
Adder
5.363
217146KRNY_1234
Adder
5.351
217146KRNY_1234
Adder
5.314
966261AG1-495 GEN
Solar/Wind Harmer
1.111
20676328BVR_Y1-020
Solar/Wind Harmer
0.204
207530AG1-191 GEN
Solar/Wind Harmer
0.851
207511W3-106 GEN
Solar/Wind Harmer
0.405
20674828DL_W4-046
Solar/Wind Harmer
0.399
971009AG2-626 GEN
Solar/Wind Harmer
1.013
20675928HOL_W4-097
Solar/Wind Harmer
0.081
207408W3-077 C
Solar/Wind Harmer
0.313
20675728RH_W2-091
Solar/Wind Harmer
0.212
207484AF2-139 C O1
Solar/Wind Harmer
0.313
20675128HRM_W1-127
Solar/Wind Harmer
0.105
20462827N BANGR8
Adder
0.442
966421AG1-511 GEN
Solar/Wind Harmer
5.306
209116AE2-175 GEN
Solar/Wind Harmer
2.521
20486527WR_V4-052
Adder
0.661
961261AF2-417 GEN
Solar/Wind Harmer
0.601
208862AG1-362 C
Solar/Wind Harmer
0.495
209026WIENIPP4
Adder
3.186
209045AE2-271 GEN
Solar/Wind Harmer
9.673
209030FRFA O01
Adder
0.166
959431AF2-234 GEN
Solar/Wind Harmer
1.133
964051AG1-259 GEN
Solar/Wind Harmer
0.76
964061AG1-260 GEN
Solar/Wind Harmer
0.76
959421AF2-233 GEN
Solar/Wind Harmer
0.566
200200DELTA2 CT1
50/50
2.126
200193DELTA CT2
50/50
1.188
200203Y1-065-STG
50/50
4.285
200055ROCKSP 4
50/50
1.543
232907VN8
Adder
22.054
233996TM1833_GEN
Solar/Wind Harmer
0.93
233997TMININ_4.2
Solar/Wind Harmer
0.93
232406W1-004 FULL
Solar/Wind Harmer
0.735
233940AF2-379 C
Solar/Wind Harmer
0.137
232914OH NUG3
Adder
6.486
232916OH NUG5
Adder
6.486
972073AH1-586 GEN
Solar/Wind Harmer
6.882
232921TASLEY2G
Adder
3.79
233994AC2-023 GEN
Solar/Wind Harmer
1.974
234015AF2-250 C
Solar/Wind Harmer
0.088
972133AH1-634 GEN
Solar/Wind Harmer
7.279
233990AG1-397 GEN
Solar/Wind Harmer
0.842
233900O-025 C
Adder
0.865
960671AF2-358 GEN
Solar/Wind Harmer
13.15
232417X3-008 C
Solar/Wind Harmer
1.468
233971AC1-093 C
Solar/Wind Harmer
0.576
970695AG2-447 GEN
Solar/Wind Harmer
2.629
233952AC2-187 GEN
Solar/Wind Harmer
0.826
233918AB1-142 GEN
Solar/Wind Harmer
0.724
233982AB2-133 GEN
Solar/Wind Harmer
3.56
972251AH1-710 GEN
Adder
32.313
228202CUMB CT
Adder
10.671
228711V2-041C
Solar/Wind Harmer
0.388
971553AH1-274 GEN
Solar/Wind Harmer
1.563
230430AE1-229_GEN
Solar/Wind Harmer
5.668
230415AB2-049 C
Solar/Wind Harmer
0.122
213497CHSTR7-9
Adder
1.753
228304LOGAN
Adder
13.976
228729W2-030 C
Solar/Wind Harmer
0.371
219623KINSLEYBEA C
Solar/Wind Harmer
0.272
213958STHWK5-6
Adder
1.734
219766PARADISE C
Solar/Wind Harmer
0.2
219291REEVESSOUT C
Solar/Wind Harmer
0.038
219912AD2-042 GEN
Solar/Wind Harmer
0.505
213560DLW11-12
Adder
1.722
219236SOUTHERNHQ C
Solar/Wind Harmer
0.043
219906AC1-017 C
Solar/Wind Harmer
0.141
219610FLORENCE C
Solar/Wind Harmer
0.872
219348LDSOLAR C
Solar/Wind Harmer
0.377
219221BRL12CT1
Adder
5.617
219223BRL12CT3
Adder
5.617
213815MOSER1-3
Adder
2.231
959561AF2-247 GEN
Solar/Wind Harmer
0.304
20716028EGP_W2-019
Solar/Wind Harmer
0.29
20720828JCB_W4-025
Solar/Wind Harmer
0.283
20715028HAN_X4-015
Solar/Wind Harmer
0.186
20636028O CRK C1
Adder
4.404
971667AH1-334 GEN
Solar/Wind Harmer
1.71
219727YARDVSOLFA C
Solar/Wind Harmer
0.567
20714528FRN_Y2-051
Solar/Wind Harmer
0.183
219276PARKLANDSO C
Solar/Wind Harmer
0.287
219918AC2-009 C
Solar/Wind Harmer
0.038
20716228APLW2-078
Solar/Wind Harmer
0.548
20720528MAN_W1-024
Solar/Wind Harmer
0.158
967451AG2-055 C O1
Solar/Wind Harmer
107.53
219612MATRIX C
Solar/Wind Harmer
0.114
218438BLK ROCK C
Solar/Wind Harmer
0.084
20635828PARLN1&2
Adder
2.075
20635928PARLN3&4
Adder
2.075
20635028RRCT1&2
Adder
7.295
20635128RRCT3&4
Adder
6.048
219908AB1-139 C
Solar/Wind Harmer
0.236
219919AE1-041 FULL
Solar/Wind Harmer
0.025
219249CENTRALDIV C
Solar/Wind Harmer
0.025
20673728F2S_V4-070
Solar/Wind Harmer
0.111
217211CAMDEN ST C
Solar/Wind Harmer
0.015
217186ESSEX_G9
Adder
9.874
217169METRODIV C
Solar/Wind Harmer
0.025
217194REDH C
Solar/Wind Harmer
0.304
20676728BRNX1-095
Solar/Wind Harmer
0.109
207510AF2-138 C
Solar/Wind Harmer
1.099
20674628WNG_W3-110
Solar/Wind Harmer
0.249
971007AG2-625 GEN
Solar/Wind Harmer
1.588
20633028GILCT9
Adder
17.541
966181AG1-487 GEN
Solar/Wind Harmer
0.156
20466127PORT 5CT
Adder
16.344
20465427SHAW CT
Adder
2.376
963161AG1-165 GEN
Solar/Wind Harmer
0.598
209025WIENIPP3
Adder
3.154
963071AG1-156 GEN
Solar/Wind Harmer
1.643
970095AG2-074 GEN
Solar/Wind Harmer
3.728
209027LOR2_Q27
Solar/Wind Harmer
2.663
209022WHFR IPP
Adder
1.912
961331AF2-424 GEN
Solar/Wind Harmer
0.58
961421AF2-433 GEN
Solar/Wind Harmer
0.578
957921AF2-086 GEN
Solar/Wind Harmer
0.562
209142AF1-226 GEN
Solar/Wind Harmer
3.348
209093AE2-110 GEN
Solar/Wind Harmer
1.446
209120AE2-241 GEN
Solar/Wind Harmer
1.913
972245AH1-707 GEN
Adder
3.119
946691AF1-333 GEN
Solar/Wind Harmer
0.567
946741AF1-338 GEN
Solar/Wind Harmer
0.567
972221AH1-695 GEN
Adder
80.708
227287AC2-120 GEN
Solar/Wind Helper
0.404
226910AB2-157 C
Solar/Wind Helper
0.017
213497CHSTR7-9
Adder
1.753
213497CHSTR7-9
Adder
1.753
230434AG1-499 GEN
Solar/Wind Harmer
0.373
219258KINSLEYDEP C
Solar/Wind Harmer
0.206
213958STHWK5-6
Adder
1.734
219904AC1-010 C
Solar/Wind Harmer
0.241
218660EHAMPSOLAR C
Solar/Wind Harmer
0.111
219287REEVESEAST C
Solar/Wind Harmer
0.853
219686LUMSOLAR_N C
Solar/Wind Harmer
0.128
213560DLW11-12
Adder
1.722
219907AC1-030 C
Solar/Wind Harmer
0.088
219304NAMERICA C
Solar/Wind Harmer
0.195
219222BRL12CT2
Adder
5.617
213611FALLS1-3
Adder
2.214
214194N WALES4
Adder
0.533
20720728JCB_W1-129
Solar/Wind Harmer
0.186
207522AF2-254 C
Solar/Wind Harmer
0.895
207487AE2-000G4
Solar/Wind Harmer
19.628
207445AB1-138_GEN
Solar/Wind Harmer
0.361
20628028LAKEHURS
Adder
1.171
963711AG1-223 GEN
Solar/Wind Harmer
0.919
20714828MDF_W3-079
Solar/Wind Harmer
0.19
219680HOPEWELLV C1
Solar/Wind Harmer
0.047
207454AA2-184 E
Solar/Wind Harmer
0.62
20715228NPK_W1-113
Solar/Wind Harmer
0.267
20742028HF_AC1-207
Solar/Wind Harmer
0.486
217197RE CRAN C
Solar/Wind Harmer
0.333
20635828PARLN1&2
Adder
4.582
20635028RRCT1&2
Adder
7.183
20635128RRCT3&4
Adder
6.933
218428ETC SOLAR C
Solar/Wind Harmer
0.022
217213AMBOY SO C
Solar/Wind Harmer
0.078
972275AH1-722 GEN
Adder
19.521
207528AF2-192 GEN
Solar/Wind Harmer
0.343
20673628F1S_V4-069
Solar/Wind Harmer
0.111
20675428EAM_W2-061
Solar/Wind Harmer
0.117
218449LINSOLAR C
Solar/Wind Harmer
0.622
20676428JCR_X2-075
Solar/Wind Harmer
0.212
217209CENTRL HS C
Solar/Wind Harmer
0.028
217121ECCF
Adder
0.268
217083KRNY_132
Adder
5.741
217208PARK ELE C
Solar/Wind Harmer
0.016
207439AE1-081 C O1
Solar/Wind Harmer
0.037
20674328GAR_V4-001
Solar/Wind Harmer
0.068
20675828AU_W4-064
Solar/Wind Harmer
0.107
971519AH1-257 GEN
Solar/Wind Harmer
1.559
207518AF1-320_GEN
Solar/Wind Harmer
2.26
207437AD2-070 GEN
Solar/Wind Harmer
0.187
966181AG1-487 GEN
Solar/Wind Harmer
2.321
20671928W4-073
Solar/Wind Harmer
0.268
20465127PORT CT
Adder
1.853
208909MACR G3
Adder
98.169
205941AD2-115 GEN
Solar/Wind Harmer
0.567
20467927PC_Q59Y356
Adder
0.519
20465527S.RDG CT
Adder
1.696
961301AF2-421 GEN
Solar/Wind Harmer
0.598
963151AG1-164 GEN
Solar/Wind Harmer
0.598
209023WIENIPP1
Adder
6.448
209025WIENIPP3
Adder
3.219
212266LOR1
Solar/Wind Harmer
0.076
970237AG2-161 GEN
Solar/Wind Harmer
2.045
209010PEIP 1
Adder
0.381
961341AF2-425 GEN
Solar/Wind Harmer
0.58
212174INGE
Adder
0.641
212507AE2-042_GEN
Solar/Wind Harmer
1.71
946731AF1-337 GEN
Solar/Wind Harmer
0.567
209071AE2-133 GEN
Solar/Wind Harmer
0.959
970665AG2-430 GEN
Solar/Wind Harmer
5.621
209018SUNBIPCT
Adder
4.219
972241AH1-705 GEN
Adder
3.234
209008PAXT IPP
Adder
1.195
232416X2-083
Adder
0.328
228251CARLLS#4
Adder
0.407
230433AD2-135 GEN
Solar/Wind Harmer
0.065
230422AE1-104_GEN1
Solar/Wind Harmer
21.684
230425AE1-104_GEN2
Solar/Wind Harmer
21.684
228307PCLP GT
Adder
7.773
228304LOGAN
Adder
15.54
230407AD2-065 C
Solar/Wind Harmer
0.085
213589EDDYSTN4
Adder
51.196
213587EDDYSTN3
Adder
51.19
972233AH1-701 GEN
Adder
2.692
219921AF1-264
Solar/Wind Harmer
0.092
219615MILLCREEK C
Solar/Wind Harmer
0.15
213535CROYDN11
Adder
6.435
213815MOSER1-3
Adder
2.231
213815MOSER1-3
Adder
2.231
20716428NHV_W2-082
Solar/Wind Harmer
1.109
207500AE2-000G1
Solar/Wind Harmer
19.628
207497AE2-000G2
Solar/Wind Harmer
19.628
207507AE2-000G3
Solar/Wind Harmer
19.628
20636128O CRK C2
Adder
4.016
963401AG1-189 GEN
Solar/Wind Harmer
0.716
963391AG1-188 GEN
Solar/Wind Harmer
1.194
20714928UPF_X1-085
Solar/Wind Harmer
0.253
219114HARTZY_C
Solar/Wind Harmer
0.52
20628028LAKEHURS
Adder
0.592
219817TRENTONSOL C
Solar/Wind Harmer
0.684
20641628MLH_W1-032
Solar/Wind Harmer
0.182
20720628TIN_W1-124
Solar/Wind Harmer
0.618
20716928W4-060COL
Solar/Wind Harmer
0.44
924131AB2-057 GEN
Solar/Wind Harmer
0.636
218440SUMMTASSOC C
Solar/Wind Harmer
0.079
20673828FLE_V3-070
Solar/Wind Harmer
0.283
218418LINDEN_G5
Adder
10.619
218419LINDEN_G6
Adder
10.619
972260AH1-715 GEN1
Adder
8.503
207442AE1-156 GEN
Solar/Wind Harmer
0.461
20676128MHD_W3-029
Solar/Wind Harmer
0.295
219036LINDEN_G7
Adder
10.337
219035LINDEN_G8
Adder
10.19
972261AH1-715 GEN2
Adder
9.895
217081WEATEXAS C
Solar/Wind Harmer
0.053
217202FBANKSOLAR C
Solar/Wind Harmer
0.045
20671828STAW2-080
Solar/Wind Harmer
0.065
217201HACKENSOLA C
Solar/Wind Harmer
0.045
972237AH1-703 GEN
Adder
6.249
217206BARNGR HS C
Solar/Wind Harmer
0.019
217086KRNY_131
Adder
5.753
217083KRNY_132
Adder
5.704
20674528F3S_W2-016
Solar/Wind Harmer
0.871
217204WCALDSOLAR C
Solar/Wind Harmer
0.045
20676228FRD_X1-012
Solar/Wind Harmer
0.365
207471AF2-354 C
Solar/Wind Harmer
0.316
20674928WA_W3-044
Solar/Wind Harmer
0.298
964851AG1-348 GEN
Solar/Wind Harmer
1.086
20634528N27_Y2-018
Solar/Wind Harmer
0.166
20674128FR_U2-059
Solar/Wind Harmer
0.114
20465127PORT CT
Adder
2.459
966111AG1-480 GEN
Solar/Wind Harmer
0.053
966111AG1-480 GEN
Solar/Wind Harmer
2.028
211065PSPA IPP
Solar/Wind Harmer
0.276
211065PSPA IPP
Solar/Wind Harmer
0.276
20465527S.RDG CT
Adder
1.641
208972BECR K09
Solar/Wind Harmer
0.626
961541AF2-445A GEN
Solar/Wind Harmer
1.913
209029WAYMART-WD
Solar/Wind Harmer
1.703
209009PEIP 2
Adder
4.624
209010PEIP 1
Adder
2.095
209010PEIP 1
Adder
0.307
961431AF2-434 GEN
Solar/Wind Harmer
0.578
208835TUHI V3-051
Solar/Wind Harmer
0.035
208835TUHI V3-051
Solar/Wind Harmer
0.035
20478527GLRA_Q45
Adder
0.197
209054AE2-059 GEN
Solar/Wind Harmer
0.965
209059AE2-084 GEN
Solar/Wind Harmer
1.425
946751AF1-339 GEN
Solar/Wind Harmer
0.567
209130AF1-271A GEN
Solar/Wind Harmer
1.593
226929AD2-058 GEN
Solar/Wind Helper
0.113
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.785
G-007ALTFEXP_G-007A->PJM
CMTX
31.724
CBM NorthLTFEXP_CBM-N->PJM
CBM
49.069
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
2.526
BlueGrassPJM->LTFIMP_BlueG
CLTF
7.881
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
83.672
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.165
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
12.143

Details for CNASTONE-BRIGHTON 500.0 kV Ckt 1 line l/o BG_P7_GRCTN_RAPHEL_SRT-A


Base Case Flowgate

Area:PJM
Facility Description:
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
Contingency Name:
BG_P7_GRCTN_RAPHEL_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:109.23 %
Rating:3098.0 MVA
Rating Type:B
MVA to Mitigate:3383.93
MW Contribution:4.93
Bus #Bus NameTypeMW Contribution
200202DELTA2 ST
50/50
3.565
200195DELTA ST
50/50
1.814
200052ROCKSP 1
50/50
1.544
200053ROCKSP 2
50/50
1.511
200058HUNTR101
50/50
1.523
200059HUNTR201
50/50
1.523
200060HUNTR301
50/50
1.523
233923SMA
Solar/Wind Harmer
3.404
232912OH NUG1
Adder
6.473
232913OH NUG2
Adder
6.386
233955AB2-172 GEN
Solar/Wind Harmer
3.665
233990AG1-397 GEN
Solar/Wind Harmer
0.04
232432Z2-076 GEN
Solar/Wind Harmer
0.097
234033AF1-007_GEN
Solar/Wind Harmer
17.131
232904IR4
Adder
59.234
232920IR10
Adder
2.315
233973AC2-185 C
Solar/Wind Harmer
2.644
232813VAUGHN
Adder
0.431
233968AD2-076_GEN
Solar/Wind Harmer
4.851
970597AG2-380 GEN
Solar/Wind Harmer
3.046
232436AB1-176 C
Solar/Wind Harmer
0.168
231906DC3 NUG
Adder
10.227
231902DC CT7
Adder
8.176
231907DC10
Adder
2.553
971983AH1-536 GEN
Solar/Wind Harmer
5.471
233935AB2-179 C
Solar/Wind Harmer
1.822
231919CHRIST1
Adder
3.181
231920CHRIST2
Adder
3.111
970453AG2-297 GEN
Solar/Wind Harmer
1.78
228260V4-054C
Solar/Wind Harmer
0.661
228309CCLP NUG
Adder
16.643
228309CCLP NUG
Adder
15.831
972141AH1-641 GEN
Solar/Wind Harmer
1.851
964001AG1-254 GEN
Solar/Wind Harmer
1.308
971011AG2-627 GEN
Solar/Wind Harmer
4.926
971535AH1-265 GEN
Solar/Wind Harmer
2.732
227927V4-067C
Solar/Wind Harmer
0.127
228754AB1-001 C
Solar/Wind Harmer
0.089
219137THOSOLAR C
Solar/Wind Harmer
0.772
213942SCHUYLKILL
Adder
2.274
213942SCHUYLKILL
Adder
1.739
213957STHWK3-4
Adder
1.738
213957STHWK3-4
Adder
1.738
219272CLEANLIGHT C
Solar/Wind Harmer
0.116
219914AD2-027 C
Solar/Wind Harmer
0.381
219688LUMSOLAR_S C
Solar/Wind Harmer
0.128
213561DLWR9-10
Adder
2.255
213561DLWR9-10
Adder
1.724
219607WPEMNERT C
Solar/Wind Harmer
0.264
219224BRL12CT4
Adder
5.614
214067T20SOLAR
Solar/Wind Harmer
0.158
213611FALLS1-3
Adder
2.214
213611FALLS1-3
Adder
2.214
20717128DIX_Z2-102
Solar/Wind Harmer
0.823
20715728PEM_W1-119
Solar/Wind Harmer
0.333
20715828PEM_W1-120
Solar/Wind Harmer
0.333
970025AG2-016 GEN
Solar/Wind Harmer
1.762
971189AH1-054 GEN
Solar/Wind Harmer
0.734
207459AE1-142 C O1
Solar/Wind Harmer
0.656
219620RIDERU C
Solar/Wind Harmer
0.035
20714328BYD_X4-031
Solar/Wind Harmer
0.175
20714428HOW_X1-037
Solar/Wind Harmer
0.765
971521AH1-258 GEN
Solar/Wind Harmer
1.675
20720428HOL_W1-112
Solar/Wind Harmer
0.214
20635928PARLN3&4
Adder
4.577
218455CINNBAY_CGEN
Adder
1.123
218526CNTRALGAS2 C
Solar/Wind Harmer
0.229
218524CNTRALGAS1 C
Solar/Wind Harmer
0.229
20675528CPH_W2-050
Solar/Wind Harmer
0.289
218404KENILWRTH C
Adder
0.805
217167KRNY_14
Adder
5.734
217086KRNY_131
Adder
5.686
217147KRNY_1212
Adder
5.454
217147KRNY_1212
Adder
5.357
217146KRNY_1234
Adder
5.345
217146KRNY_1234
Adder
5.308
966261AG1-495 GEN
Solar/Wind Harmer
1.111
20676328BVR_Y1-020
Solar/Wind Harmer
0.204
207530AG1-191 GEN
Solar/Wind Harmer
0.85
207511W3-106 GEN
Solar/Wind Harmer
0.405
20674828DL_W4-046
Solar/Wind Harmer
0.399
971009AG2-626 GEN
Solar/Wind Harmer
1.012
20675928HOL_W4-097
Solar/Wind Harmer
0.081
207408W3-077 C
Solar/Wind Harmer
0.313
20675728RH_W2-091
Solar/Wind Harmer
0.211
207484AF2-139 C O1
Solar/Wind Harmer
0.313
20675128HRM_W1-127
Solar/Wind Harmer
0.105
20462827N BANGR8
Adder
0.442
966421AG1-511 GEN
Solar/Wind Harmer
5.301
209116AE2-175 GEN
Solar/Wind Harmer
2.519
20486527WR_V4-052
Adder
0.664
208862AG1-362 C
Solar/Wind Harmer
0.498
961261AF2-417 GEN
Solar/Wind Harmer
0.6
209026WIENIPP4
Adder
3.183
209030FRFA O01
Adder
0.172
209045AE2-271 GEN
Solar/Wind Harmer
9.661
959431AF2-234 GEN
Solar/Wind Harmer
1.131
964051AG1-259 GEN
Solar/Wind Harmer
0.759
964061AG1-260 GEN
Solar/Wind Harmer
0.759
959421AF2-233 GEN
Solar/Wind Harmer
0.566
200200DELTA2 CT1
50/50
2.101
200193DELTA CT2
50/50
1.174
200203Y1-065-STG
50/50
4.24
200055ROCKSP 4
50/50
1.527
232907VN8
Adder
22.012
233996TM1833_GEN
Solar/Wind Harmer
0.928
233997TMININ_4.2
Solar/Wind Harmer
0.928
960671AF2-358 GEN
Solar/Wind Harmer
13.126
233994AC2-023 GEN
Solar/Wind Harmer
1.97
232406W1-004 FULL
Solar/Wind Harmer
0.734
233940AF2-379 C
Solar/Wind Harmer
0.137
232914OH NUG3
Adder
6.473
232916OH NUG5
Adder
6.473
972073AH1-586 GEN
Solar/Wind Harmer
6.868
232921TASLEY2G
Adder
3.783
233900O-025 C
Adder
0.863
232417X3-008 C
Solar/Wind Harmer
1.466
234015AF2-250 C
Solar/Wind Harmer
0.088
233990AG1-397 GEN
Solar/Wind Harmer
0.841
972133AH1-634 GEN
Solar/Wind Harmer
7.264
233952AC2-187 GEN
Solar/Wind Harmer
0.824
233971AC1-093 C
Solar/Wind Harmer
0.574
970695AG2-447 GEN
Solar/Wind Harmer
2.622
233918AB1-142 GEN
Solar/Wind Harmer
0.725
233982AB2-133 GEN
Solar/Wind Harmer
3.561
972251AH1-710 GEN
Adder
32.2
228202CUMB CT
Adder
10.651
228711V2-041C
Solar/Wind Harmer
0.387
971553AH1-274 GEN
Solar/Wind Harmer
1.56
213497CHSTR7-9
Adder
1.759
230430AE1-229_GEN
Solar/Wind Harmer
5.661
230415AB2-049 C
Solar/Wind Harmer
0.122
228304LOGAN
Adder
13.966
228729W2-030 C
Solar/Wind Harmer
0.37
213958STHWK5-6
Adder
1.738
219623KINSLEYBEA C
Solar/Wind Harmer
0.272
219766PARADISE C
Solar/Wind Harmer
0.2
219291REEVESSOUT C
Solar/Wind Harmer
0.038
219912AD2-042 GEN
Solar/Wind Harmer
0.505
213560DLW11-12
Adder
1.724
219236SOUTHERNHQ C
Solar/Wind Harmer
0.043
219906AC1-017 C
Solar/Wind Harmer
0.141
219610FLORENCE C
Solar/Wind Harmer
0.871
219348LDSOLAR C
Solar/Wind Harmer
0.377
219221BRL12CT1
Adder
5.614
219223BRL12CT3
Adder
5.614
213815MOSER1-3
Adder
2.232
959561AF2-247 GEN
Solar/Wind Harmer
0.303
20716028EGP_W2-019
Solar/Wind Harmer
0.289
20720828JCB_W4-025
Solar/Wind Harmer
0.282
20715028HAN_X4-015
Solar/Wind Harmer
0.186
20636028O CRK C1
Adder
4.398
971667AH1-334 GEN
Solar/Wind Harmer
1.708
219727YARDVSOLFA C
Solar/Wind Harmer
0.566
20714528FRN_Y2-051
Solar/Wind Harmer
0.183
219276PARKLANDSO C
Solar/Wind Harmer
0.287
219918AC2-009 C
Solar/Wind Harmer
0.038
20716228APLW2-078
Solar/Wind Harmer
0.547
20720528MAN_W1-024
Solar/Wind Harmer
0.157
967451AG2-055 C O1
Solar/Wind Harmer
107.38
219612MATRIX C
Solar/Wind Harmer
0.114
218438BLK ROCK C
Solar/Wind Harmer
0.084
20635828PARLN1&2
Adder
2.073
20635928PARLN3&4
Adder
2.073
20635028RRCT1&2
Adder
7.286
20635128RRCT3&4
Adder
6.041
219908AB1-139 C
Solar/Wind Harmer
0.235
200192DELTA CT1
50/50
1.174
200194DELTA CT3
50/50
1.174
200204Y1-065-CTG1
50/50
2.445
200054ROCKSP 3
50/50
1.56
233998TM1NIN_3.36
Solar/Wind Harmer
0.928
965821AG1-450 GEN
Solar/Wind Harmer
3.816
232919VN10
Adder
2.057
232404W1-003 C
Solar/Wind Harmer
0.734
232428Y3-058 C
Solar/Wind Harmer
0.612
232426Y1-080 FULL
Solar/Wind Harmer
0.14
233964AF2-378 GEN
Solar/Wind Harmer
0.094
232917OH NUG6
Adder
6.444
232915OH NUG4
Adder
6.429
970277AG2-181 GEN
Solar/Wind Harmer
3.675
971195AH1-057 GEN
Solar/Wind Harmer
0.802
232434Z2-077 GEN
Solar/Wind Harmer
0.183
972177AH1-672 GEN
Solar/Wind Harmer
9.84
232901NORTHST
Adder
6.094
233954AC2-188 GEN
Solar/Wind Harmer
0.824
233950AC2-186 GEN
Solar/Wind Harmer
0.412
232900DEMECSMY
Adder
6.752
233972AC1-094 C
Solar/Wind Harmer
0.486
232910NRG_G1
Adder
6.317
234012AE2-112_GEN
Solar/Wind Harmer
1.683
232422X3-066 FULL
Solar/Wind Harmer
0.183
233930AB2-032 GEN
Solar/Wind Harmer
0.61
233915AB1-141 GEN
Solar/Wind Harmer
0.725
231918WEST 1
Adder
2.42
231917EM10
Adder
1.691
228206SHRMN CT
Adder
10.685
228732V1-021 C
Adder
0.122
945431AF1-208 GEN
Solar/Wind Harmer
5.557
213497CHSTR7-9
Adder
1.759
213497CHSTR7-9
Adder
1.759
970997AG2-616 GEN
Solar/Wind Harmer
6.169
228351V2-046C
Solar/Wind Harmer
1.296
230511AF1-262
Solar/Wind Harmer
0.118
228728W1-130C
Solar/Wind Harmer
0.426
230434AG1-499 GEN
Solar/Wind Harmer
0.372
213958STHWK5-6
Adder
1.738
219258KINSLEYDEP C
Solar/Wind Harmer
0.206
219904AC1-010 C
Solar/Wind Harmer
0.24
218660EHAMPSOLAR C
Solar/Wind Harmer
0.111
219287REEVESEAST C
Solar/Wind Harmer
0.852
219686LUMSOLAR_N C
Solar/Wind Harmer
0.128
213560DLW11-12
Adder
1.724
219907AC1-030 C
Solar/Wind Harmer
0.088
219304NAMERICA C
Solar/Wind Harmer
0.195
219222BRL12CT2
Adder
5.614
213611FALLS1-3
Adder
2.214
214194N WALES4
Adder
0.532
20720728JCB_W1-129
Solar/Wind Harmer
0.186
207522AF2-254 C
Solar/Wind Harmer
0.894
207487AE2-000G4
Solar/Wind Harmer
19.601
207445AB1-138_GEN
Solar/Wind Harmer
0.36
20628028LAKEHURS
Adder
1.169
963711AG1-223 GEN
Solar/Wind Harmer
0.918
20714828MDF_W3-079
Solar/Wind Harmer
0.19
219680HOPEWELLV C1
Solar/Wind Harmer
0.047
207454AA2-184 E
Solar/Wind Harmer
0.619
20715228NPK_W1-113
Solar/Wind Harmer
0.266
20742028HF_AC1-207
Solar/Wind Harmer
0.485
217197RE CRAN C
Solar/Wind Harmer
0.332
20635828PARLN1&2
Adder
4.577
20635028RRCT1&2
Adder
7.174
20635128RRCT3&4
Adder
6.925
218428ETC SOLAR C
Solar/Wind Harmer
0.022
217213AMBOY SO C
Solar/Wind Harmer
0.078
972275AH1-722 GEN
Adder
19.498
207528AF2-192 GEN
Solar/Wind Harmer
0.342
20673628F1S_V4-069
Solar/Wind Harmer
0.111
20675428EAM_W2-061
Solar/Wind Harmer
0.117
20676428JCR_X2-075
Solar/Wind Harmer
0.211
218449LINSOLAR C
Solar/Wind Harmer
0.621
217209CENTRL HS C
Solar/Wind Harmer
0.028
217121ECCF
Adder
0.268
217083KRNY_132
Adder
5.734
217208PARK ELE C
Solar/Wind Harmer
0.016
207439AE1-081 C O1
Solar/Wind Harmer
0.037
20674328GAR_V4-001
Solar/Wind Harmer
0.068
20675828AU_W4-064
Solar/Wind Harmer
0.107
971519AH1-257 GEN
Solar/Wind Harmer
1.558
207518AF1-320_GEN
Solar/Wind Harmer
2.259
207437AD2-070 GEN
Solar/Wind Harmer
0.186
966181AG1-487 GEN
Solar/Wind Harmer
2.32
20671928W4-073
Solar/Wind Harmer
0.267
20465127PORT CT
Adder
1.851
208909MACR G3
Adder
98.088
205941AD2-115 GEN
Solar/Wind Harmer
0.569
20467927PC_Q59Y356
Adder
0.521
20465527S.RDG CT
Adder
1.704
961301AF2-421 GEN
Solar/Wind Harmer
0.597
963151AG1-164 GEN
Solar/Wind Harmer
0.597
209023WIENIPP1
Adder
6.441
209025WIENIPP3
Adder
3.215
212266LOR1
Solar/Wind Harmer
0.076
970237AG2-161 GEN
Solar/Wind Harmer
2.043
209010PEIP 1
Adder
0.381
961341AF2-425 GEN
Solar/Wind Harmer
0.579
212174INGE
Adder
0.64
212507AE2-042_GEN
Solar/Wind Harmer
1.708
946731AF1-337 GEN
Solar/Wind Harmer
0.567
209071AE2-133 GEN
Solar/Wind Harmer
0.958
970665AG2-430 GEN
Solar/Wind Harmer
5.613
209018SUNBIPCT
Adder
4.213
209008PAXT IPP
Adder
1.197
972241AH1-705 GEN
Adder
3.229
219919AE1-041 FULL
Solar/Wind Harmer
0.025
219249CENTRALDIV C
Solar/Wind Harmer
0.024
20673728F2S_V4-070
Solar/Wind Harmer
0.111
217211CAMDEN ST C
Solar/Wind Harmer
0.015
217186ESSEX_G9
Adder
9.863
217169METRODIV C
Solar/Wind Harmer
0.025
217194REDH C
Solar/Wind Harmer
0.304
20676728BRNX1-095
Solar/Wind Harmer
0.109
207510AF2-138 C
Solar/Wind Harmer
1.098
20674628WNG_W3-110
Solar/Wind Harmer
0.249
971007AG2-625 GEN
Solar/Wind Harmer
1.587
20633028GILCT9
Adder
17.532
966181AG1-487 GEN
Solar/Wind Harmer
0.156
20466127PORT 5CT
Adder
16.33
20465427SHAW CT
Adder
2.374
963161AG1-165 GEN
Solar/Wind Harmer
0.597
209025WIENIPP3
Adder
3.15
963071AG1-156 GEN
Solar/Wind Harmer
1.641
970095AG2-074 GEN
Solar/Wind Harmer
3.723
209027LOR2_Q27
Solar/Wind Harmer
2.66
209022WHFR IPP
Adder
1.91
961331AF2-424 GEN
Solar/Wind Harmer
0.579
961421AF2-433 GEN
Solar/Wind Harmer
0.578
957921AF2-086 GEN
Solar/Wind Harmer
0.562
209142AF1-226 GEN
Solar/Wind Harmer
3.343
209093AE2-110 GEN
Solar/Wind Harmer
1.444
209120AE2-241 GEN
Solar/Wind Harmer
1.91
972245AH1-707 GEN
Adder
3.115
946691AF1-333 GEN
Solar/Wind Harmer
0.567
946741AF1-338 GEN
Solar/Wind Harmer
0.567
972221AH1-695 GEN
Adder
80.855
227287AC2-120 GEN
Solar/Wind Helper
0.396
226910AB2-157 C
Solar/Wind Helper
0.016
972281AH1-725 GEN
50/50
121.693
200201DELTA2 CT2
50/50
2.101
200034PCHBTM 2
50/50
12.234
200205Y1-065-CTG2
50/50
2.445
200035PCHBTM 3
50/50
12.162
200061HUNTR401
50/50
2.902
233987AB2-037 GEN
Solar/Wind Harmer
8.352
232926CRISFLD1
Adder
1.438
233946AB2-136 GEN
Solar/Wind Harmer
2.925
233901CHERRYDALE C
Solar/Wind Harmer
0.825
232408W1-005 C
Solar/Wind Harmer
0.734
232410W1-006 C
Solar/Wind Harmer
0.734
234036AF2-325 C
Solar/Wind Harmer
0.672
972069AH1-584 GEN
Solar/Wind Harmer
6.563
972071AH1-585 GEN
Solar/Wind Harmer
6.563
232918OH NUG7
Adder
6.429
971747AH1-380 GEN
Solar/Wind Harmer
2.625
232905CHERITON_25
Adder
1.798
234041AC1-190 GEN
Solar/Wind Harmer
6.563
970545AG2-347 GEN
Solar/Wind Harmer
47.94
231940T-011
Adder
0.546
971149AH1-027 GEN
Solar/Wind Harmer
2.478
233984AB2-036 GEN
Solar/Wind Harmer
9.117
232899W1-062
Adder
7.039
233939AC1-091 C
Solar/Wind Harmer
0.643
233970AC1-092 C
Solar/Wind Harmer
0.643
232424Y1-079 C
Solar/Wind Harmer
0.412
234014AF1-036_GEN
Solar/Wind Harmer
1.98
233933AB2-153 GEN
Solar/Wind Harmer
0.823
233944AB2-135 GEN
Solar/Wind Harmer
3.829
231131BLOOM ENRGY
Adder
3.183
232416X2-083
Adder
0.328
228251CARLLS#4
Adder
0.406
213589EDDYSTN4
Adder
51.366
213587EDDYSTN3
Adder
51.36
230433AD2-135 GEN
Solar/Wind Harmer
0.065
230422AE1-104_GEN1
Solar/Wind Harmer
21.647
230425AE1-104_GEN2
Solar/Wind Harmer
21.647
228307PCLP GT
Adder
7.767
228304LOGAN
Adder
15.529
230407AD2-065 C
Solar/Wind Harmer
0.084
972233AH1-701 GEN
Adder
2.69
219921AF1-264
Solar/Wind Harmer
0.092
219615MILLCREEK C
Solar/Wind Harmer
0.15
213815MOSER1-3
Adder
2.232
213815MOSER1-3
Adder
2.232
213535CROYDN11
Adder
6.433
20716428NHV_W2-082
Solar/Wind Harmer
1.108
207500AE2-000G1
Solar/Wind Harmer
19.601
207497AE2-000G2
Solar/Wind Harmer
19.601
207507AE2-000G3
Solar/Wind Harmer
19.601
20636128O CRK C2
Adder
4.01
963401AG1-189 GEN
Solar/Wind Harmer
0.715
963391AG1-188 GEN
Solar/Wind Harmer
1.193
20714928UPF_X1-085
Solar/Wind Harmer
0.253
219114HARTZY_C
Solar/Wind Harmer
0.519
20628028LAKEHURS
Adder
0.591
219817TRENTONSOL C
Solar/Wind Harmer
0.683
20641628MLH_W1-032
Solar/Wind Harmer
0.182
20720628TIN_W1-124
Solar/Wind Harmer
0.617
20716928W4-060COL
Solar/Wind Harmer
0.44
924131AB2-057 GEN
Solar/Wind Harmer
0.636
218440SUMMTASSOC C
Solar/Wind Harmer
0.079
20673828FLE_V3-070
Solar/Wind Harmer
0.283
218418LINDEN_G5
Adder
10.606
218419LINDEN_G6
Adder
10.606
972260AH1-715 GEN1
Adder
8.493
207442AE1-156 GEN
Solar/Wind Harmer
0.46
20676128MHD_W3-029
Solar/Wind Harmer
0.295
219036LINDEN_G7
Adder
10.325
219035LINDEN_G8
Adder
10.178
972261AH1-715 GEN2
Adder
9.884
217081WEATEXAS C
Solar/Wind Harmer
0.053
217202FBANKSOLAR C
Solar/Wind Harmer
0.045
20671828STAW2-080
Solar/Wind Harmer
0.065
217201HACKENSOLA C
Solar/Wind Harmer
0.045
972237AH1-703 GEN
Adder
6.242
217206BARNGR HS C
Solar/Wind Harmer
0.019
217086KRNY_131
Adder
5.747
217083KRNY_132
Adder
5.698
20674528F3S_W2-016
Solar/Wind Harmer
0.871
217204WCALDSOLAR C
Solar/Wind Harmer
0.045
20676228FRD_X1-012
Solar/Wind Harmer
0.365
207471AF2-354 C
Solar/Wind Harmer
0.316
20674928WA_W3-044
Solar/Wind Harmer
0.298
964851AG1-348 GEN
Solar/Wind Harmer
1.085
20634528N27_Y2-018
Solar/Wind Harmer
0.166
20674128FR_U2-059
Solar/Wind Harmer
0.114
20465127PORT CT
Adder
2.457
966111AG1-480 GEN
Solar/Wind Harmer
0.053
966111AG1-480 GEN
Solar/Wind Harmer
2.026
211065PSPA IPP
Solar/Wind Harmer
0.276
211065PSPA IPP
Solar/Wind Harmer
0.276
20465527S.RDG CT
Adder
1.649
208835TUHI V3-051
Solar/Wind Harmer
0.036
208835TUHI V3-051
Solar/Wind Harmer
0.036
208972BECR K09
Solar/Wind Harmer
0.626
961541AF2-445A GEN
Solar/Wind Harmer
1.911
209029WAYMART-WD
Solar/Wind Harmer
1.701
209009PEIP 2
Adder
4.619
209010PEIP 1
Adder
2.093
209010PEIP 1
Adder
0.307
961431AF2-434 GEN
Solar/Wind Harmer
0.578
20478527GLRA_Q45
Adder
0.197
209054AE2-059 GEN
Solar/Wind Harmer
0.964
209059AE2-084 GEN
Solar/Wind Harmer
1.423
946751AF1-339 GEN
Solar/Wind Harmer
0.567
209130AF1-271A GEN
Solar/Wind Harmer
1.59
226929AD2-058 GEN
Solar/Wind Helper
0.111
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.726
G-007ALTFEXP_G-007A->PJM
CMTX
31.685
CBM NorthLTFEXP_CBM-N->PJM
CBM
49.037
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
2.482
BlueGrassPJM->LTFIMP_BlueG
CLTF
7.743
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
83.576
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.13
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
11.932

Details for CNASTONE-BRIGHTON 500.0 kV Ckt 1 line l/o PJM_500_BG_P4_5_CNSTN_13_SRT-A


Base Case Flowgate

Area:PJM
Facility Description:
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
Contingency Name:
PJM_500_BG_P4_5_CNSTN_13_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.23 %
Rating:3098.0 MVA
Rating Type:B
MVA to Mitigate:3290.97
MW Contribution:4.76
Bus #Bus NameTypeMW Contribution
972281AH1-725 GEN
50/50
125.836
200201DELTA2 CT2
50/50
2.123
200034PCHBTM 2
50/50
12.361
200061HUNTR401
50/50
2.963
200035PCHBTM 3
50/50
12.271
200205Y1-065-CTG2
50/50
2.458
233987AB2-037 GEN
Solar/Wind Harmer
8.145
971149AH1-027 GEN
Solar/Wind Harmer
2.421
233939AC1-091 C
Solar/Wind Harmer
0.628
233970AC1-092 C
Solar/Wind Harmer
0.628
970545AG2-347 GEN
Solar/Wind Harmer
46.787
233901CHERRYDALE C
Solar/Wind Harmer
0.805
232408W1-005 C
Solar/Wind Harmer
0.716
232410W1-006 C
Solar/Wind Harmer
0.716
972069AH1-584 GEN
Solar/Wind Harmer
6.403
972071AH1-585 GEN
Solar/Wind Harmer
6.403
232918OH NUG7
Adder
6.273
971747AH1-380 GEN
Solar/Wind Harmer
2.561
232905CHERITON_25
Adder
1.754
232926CRISFLD1
Adder
1.403
231940T-011
Adder
0.533
232899W1-062
Adder
6.873
233946AB2-136 GEN
Solar/Wind Harmer
2.852
234036AF2-325 C
Solar/Wind Harmer
0.655
234041AC1-190 GEN
Solar/Wind Harmer
6.398
233984AB2-036 GEN
Solar/Wind Harmer
8.866
232424Y1-079 C
Solar/Wind Harmer
0.401
234014AF1-036_GEN
Solar/Wind Harmer
1.923
231131BLOOM ENRGY
Adder
3.093
233944AB2-135 GEN
Solar/Wind Harmer
3.717
233933AB2-153 GEN
Solar/Wind Harmer
0.798
232416X2-083
Adder
0.317
228251CARLLS#4
Adder
0.393
230422AE1-104_GEN1
Solar/Wind Harmer
20.979
230425AE1-104_GEN2
Solar/Wind Harmer
20.979
230433AD2-135 GEN
Solar/Wind Harmer
0.063
228307PCLP GT
Adder
7.509
230407AD2-065 C
Solar/Wind Harmer
0.082
228304LOGAN
Adder
15.006
972233AH1-701 GEN
Adder
2.598
213589EDDYSTN4
Adder
49.13
213587EDDYSTN3
Adder
49.125
219921AF1-264
Solar/Wind Harmer
0.089
219615MILLCREEK C
Solar/Wind Harmer
0.145
213535CROYDN11
Adder
6.195
213815MOSER1-3
Adder
2.145
213815MOSER1-3
Adder
2.145
20716428NHV_W2-082
Solar/Wind Harmer
1.068
207500AE2-000G1
Solar/Wind Harmer
18.905
207497AE2-000G2
Solar/Wind Harmer
18.905
207507AE2-000G3
Solar/Wind Harmer
18.905
20636128O CRK C2
Adder
3.868
963401AG1-189 GEN
Solar/Wind Harmer
0.69
963391AG1-188 GEN
Solar/Wind Harmer
1.15
20714928UPF_X1-085
Solar/Wind Harmer
0.244
219114HARTZY_C
Solar/Wind Harmer
0.5
20628028LAKEHURS
Adder
0.57
219817TRENTONSOL C
Solar/Wind Harmer
0.657
20641628MLH_W1-032
Solar/Wind Harmer
0.175
20720628TIN_W1-124
Solar/Wind Harmer
0.594
20716928W4-060COL
Solar/Wind Harmer
0.423
924131AB2-057 GEN
Solar/Wind Harmer
0.611
218440SUMMTASSOC C
Solar/Wind Harmer
0.076
218418LINDEN_G5
Adder
10.177
218419LINDEN_G6
Adder
10.177
972260AH1-715 GEN1
Adder
8.149
20673828FLE_V3-070
Solar/Wind Harmer
0.271
207442AE1-156 GEN
Solar/Wind Harmer
0.441
20676128MHD_W3-029
Solar/Wind Harmer
0.283
219036LINDEN_G7
Adder
9.903
219035LINDEN_G8
Adder
9.762
972261AH1-715 GEN2
Adder
9.48
217081WEATEXAS C
Solar/Wind Harmer
0.051
200202DELTA2 ST
50/50
3.603
200195DELTA ST
50/50
1.833
200058HUNTR101
50/50
1.555
200059HUNTR201
50/50
1.555
200060HUNTR301
50/50
1.555
200052ROCKSP 1
50/50
1.553
200053ROCKSP 2
50/50
1.519
233973AC2-185 C
Solar/Wind Harmer
2.584
234033AF1-007_GEN
Solar/Wind Harmer
16.719
232904IR4
Adder
57.81
232920IR10
Adder
2.26
233923SMA
Solar/Wind Harmer
3.321
232432Z2-076 GEN
Solar/Wind Harmer
0.094
232912OH NUG1
Adder
6.315
232913OH NUG2
Adder
6.231
233990AG1-397 GEN
Solar/Wind Harmer
0.039
233955AB2-172 GEN
Solar/Wind Harmer
3.573
232813VAUGHN
Adder
0.42
233968AD2-076_GEN
Solar/Wind Harmer
4.712
970597AG2-380 GEN
Solar/Wind Harmer
2.959
231906DC3 NUG
Adder
9.938
231902DC CT7
Adder
7.944
231907DC10
Adder
2.481
232436AB1-176 C
Solar/Wind Harmer
0.163
971983AH1-536 GEN
Solar/Wind Harmer
5.307
233935AB2-179 C
Solar/Wind Harmer
1.756
231919CHRIST1
Adder
3.072
231920CHRIST2
Adder
3.003
970453AG2-297 GEN
Solar/Wind Harmer
1.727
228260V4-054C
Solar/Wind Harmer
0.64
228309CCLP NUG
Adder
16.11
228309CCLP NUG
Adder
15.324
972141AH1-641 GEN
Solar/Wind Harmer
1.792
964001AG1-254 GEN
Solar/Wind Harmer
1.266
971011AG2-627 GEN
Solar/Wind Harmer
4.765
971535AH1-265 GEN
Solar/Wind Harmer
2.645
227927V4-067C
Solar/Wind Harmer
0.123
200192DELTA CT1
50/50
1.186
200194DELTA CT3
50/50
1.186
200204Y1-065-CTG1
50/50
2.458
200054ROCKSP 3
50/50
1.568
232901NORTHST
Adder
5.953
233972AC1-094 C
Solar/Wind Harmer
0.474
233998TM1NIN_3.36
Solar/Wind Harmer
0.906
232404W1-003 C
Solar/Wind Harmer
0.716
232434Z2-077 GEN
Solar/Wind Harmer
0.179
232917OH NUG6
Adder
6.287
232915OH NUG4
Adder
6.273
232428Y3-058 C
Solar/Wind Harmer
0.597
971195AH1-057 GEN
Solar/Wind Harmer
0.783
972177AH1-672 GEN
Solar/Wind Harmer
9.603
232919VN10
Adder
2.006
232900DEMECSMY
Adder
6.593
965821AG1-450 GEN
Solar/Wind Harmer
3.721
232426Y1-080 FULL
Solar/Wind Harmer
0.137
970277AG2-181 GEN
Solar/Wind Harmer
3.584
233964AF2-378 GEN
Solar/Wind Harmer
0.091
233954AC2-188 GEN
Solar/Wind Harmer
0.804
233950AC2-186 GEN
Solar/Wind Harmer
0.402
232910NRG_G1
Adder
6.153
234012AE2-112_GEN
Solar/Wind Harmer
1.635
232422X3-066 FULL
Solar/Wind Harmer
0.178
233930AB2-032 GEN
Solar/Wind Harmer
0.591
233915AB1-141 GEN
Solar/Wind Harmer
0.703
231918WEST 1
Adder
2.336
231917EM10
Adder
1.631
228206SHRMN CT
Adder
10.36
228732V1-021 C
Adder
0.118
945431AF1-208 GEN
Solar/Wind Harmer
5.382
970997AG2-616 GEN
Solar/Wind Harmer
5.973
228351V2-046C
Solar/Wind Harmer
1.254
230511AF1-262
Solar/Wind Harmer
0.114
228728W1-130C
Solar/Wind Harmer
0.413
230434AG1-499 GEN
Solar/Wind Harmer
0.36
213497CHSTR7-9
Adder
1.683
213497CHSTR7-9
Adder
1.683
219258KINSLEYDEP C
Solar/Wind Harmer
0.199
219904AC1-010 C
Solar/Wind Harmer
0.232
218660EHAMPSOLAR C
Solar/Wind Harmer
0.107
219686LUMSOLAR_N C
Solar/Wind Harmer
0.124
219287REEVESEAST C
Solar/Wind Harmer
0.823
213958STHWK5-6
Adder
1.664
219907AC1-030 C
Solar/Wind Harmer
0.085
213560DLW11-12
Adder
1.655
219304NAMERICA C
Solar/Wind Harmer
0.188
219222BRL12CT2
Adder
5.408
213611FALLS1-3
Adder
2.13
20720728JCB_W1-129
Solar/Wind Harmer
0.179
207522AF2-254 C
Solar/Wind Harmer
0.862
214194N WALES4
Adder
0.512
207487AE2-000G4
Solar/Wind Harmer
18.905
207445AB1-138_GEN
Solar/Wind Harmer
0.347
20628028LAKEHURS
Adder
1.127
963711AG1-223 GEN
Solar/Wind Harmer
0.884
20714828MDF_W3-079
Solar/Wind Harmer
0.183
219680HOPEWELLV C1
Solar/Wind Harmer
0.045
207454AA2-184 E
Solar/Wind Harmer
0.596
20715228NPK_W1-113
Solar/Wind Harmer
0.256
20742028HF_AC1-207
Solar/Wind Harmer
0.467
217197RE CRAN C
Solar/Wind Harmer
0.319
20635828PARLN1&2
Adder
4.397
20635028RRCT1&2
Adder
6.891
20635128RRCT3&4
Adder
6.652
218428ETC SOLAR C
Solar/Wind Harmer
0.021
217213AMBOY SO C
Solar/Wind Harmer
0.075
972275AH1-722 GEN
Adder
18.709
207528AF2-192 GEN
Solar/Wind Harmer
0.328
20673628F1S_V4-069
Solar/Wind Harmer
0.106
20675428EAM_W2-061
Solar/Wind Harmer
0.112
218449LINSOLAR C
Solar/Wind Harmer
0.596
20676428JCR_X2-075
Solar/Wind Harmer
0.202
217209CENTRL HS C
Solar/Wind Harmer
0.026
217121ECCF
Adder
0.257
217083KRNY_132
Adder
5.495
217208PARK ELE C
Solar/Wind Harmer
0.015
207439AE1-081 C O1
Solar/Wind Harmer
0.035
20674328GAR_V4-001
Solar/Wind Harmer
0.065
20675828AU_W4-064
Solar/Wind Harmer
0.102
217202FBANKSOLAR C
Solar/Wind Harmer
0.044
217201HACKENSOLA C
Solar/Wind Harmer
0.043
972237AH1-703 GEN
Adder
5.982
20671828STAW2-080
Solar/Wind Harmer
0.062
217206BARNGR HS C
Solar/Wind Harmer
0.018
217086KRNY_131
Adder
5.507
217083KRNY_132
Adder
5.46
200200DELTA2 CT1
50/50
2.123
200193DELTA CT2
50/50
1.186
200203Y1-065-STG
50/50
4.263
200055ROCKSP 4
50/50
1.535
233971AC1-093 C
Solar/Wind Harmer
0.561
970695AG2-447 GEN
Solar/Wind Harmer
2.562
972133AH1-634 GEN
Solar/Wind Harmer
7.089
233996TM1833_GEN
Solar/Wind Harmer
0.906
233997TMININ_4.2
Solar/Wind Harmer
0.906
232406W1-004 FULL
Solar/Wind Harmer
0.716
232914OH NUG3
Adder
6.315
232916OH NUG5
Adder
6.315
972073AH1-586 GEN
Solar/Wind Harmer
6.701
232921TASLEY2G
Adder
3.691
233940AF2-379 C
Solar/Wind Harmer
0.133
232907VN8
Adder
21.471
233990AG1-397 GEN
Solar/Wind Harmer
0.82
233900O-025 C
Adder
0.842
234015AF2-250 C
Solar/Wind Harmer
0.086
233994AC2-023 GEN
Solar/Wind Harmer
1.922
960671AF2-358 GEN
Solar/Wind Harmer
12.801
232417X3-008 C
Solar/Wind Harmer
1.429
233952AC2-187 GEN
Solar/Wind Harmer
0.804
233918AB1-142 GEN
Solar/Wind Harmer
0.703
233982AB2-133 GEN
Solar/Wind Harmer
3.454
972251AH1-710 GEN
Adder
31.483
228202CUMB CT
Adder
10.33
228711V2-041C
Solar/Wind Harmer
0.376
971553AH1-274 GEN
Solar/Wind Harmer
1.512
230430AE1-229_GEN
Solar/Wind Harmer
5.48
230415AB2-049 C
Solar/Wind Harmer
0.118
228729W2-030 C
Solar/Wind Harmer
0.359
228304LOGAN
Adder
13.496
213497CHSTR7-9
Adder
1.683
219623KINSLEYBEA C
Solar/Wind Harmer
0.263
219291REEVESSOUT C
Solar/Wind Harmer
0.037
219766PARADISE C
Solar/Wind Harmer
0.193
213958STHWK5-6
Adder
1.664
219912AD2-042 GEN
Solar/Wind Harmer
0.487
219236SOUTHERNHQ C
Solar/Wind Harmer
0.041
213560DLW11-12
Adder
1.655
219906AC1-017 C
Solar/Wind Harmer
0.135
219610FLORENCE C
Solar/Wind Harmer
0.839
219348LDSOLAR C
Solar/Wind Harmer
0.363
219221BRL12CT1
Adder
5.408
219223BRL12CT3
Adder
5.408
213815MOSER1-3
Adder
2.145
959561AF2-247 GEN
Solar/Wind Harmer
0.292
20716028EGP_W2-019
Solar/Wind Harmer
0.279
20720828JCB_W4-025
Solar/Wind Harmer
0.272
20715028HAN_X4-015
Solar/Wind Harmer
0.179
20636028O CRK C1
Adder
4.242
971667AH1-334 GEN
Solar/Wind Harmer
1.646
219727YARDVSOLFA C
Solar/Wind Harmer
0.545
20714528FRN_Y2-051
Solar/Wind Harmer
0.176
219276PARKLANDSO C
Solar/Wind Harmer
0.276
219918AC2-009 C
Solar/Wind Harmer
0.037
20716228APLW2-078
Solar/Wind Harmer
0.526
20720528MAN_W1-024
Solar/Wind Harmer
0.151
967451AG2-055 C O1
Solar/Wind Harmer
103.302
219612MATRIX C
Solar/Wind Harmer
0.109
218438BLK ROCK C
Solar/Wind Harmer
0.081
20635828PARLN1&2
Adder
1.992
20635928PARLN3&4
Adder
1.992
20635028RRCT1&2
Adder
6.998
20635128RRCT3&4
Adder
5.802
219908AB1-139 C
Solar/Wind Harmer
0.226
219919AE1-041 FULL
Solar/Wind Harmer
0.024
219249CENTRALDIV C
Solar/Wind Harmer
0.024
20673728F2S_V4-070
Solar/Wind Harmer
0.106
217211CAMDEN ST C
Solar/Wind Harmer
0.014
217186ESSEX_G9
Adder
9.452
217169METRODIV C
Solar/Wind Harmer
0.024
217194REDH C
Solar/Wind Harmer
0.291
20676728BRNX1-095
Solar/Wind Harmer
0.104
207510AF2-138 C
Solar/Wind Harmer
1.049
20674628WNG_W3-110
Solar/Wind Harmer
0.238
971007AG2-625 GEN
Solar/Wind Harmer
1.511
20466127PORT 5CT
Adder
15.559
20633028GILCT9
Adder
16.643
966181AG1-487 GEN
Solar/Wind Harmer
0.148
20465427SHAW CT
Adder
2.263
963161AG1-165 GEN
Solar/Wind Harmer
0.568
209025WIENIPP3
Adder
2.998
963071AG1-156 GEN
Solar/Wind Harmer
1.562
970095AG2-074 GEN
Solar/Wind Harmer
3.545
209027LOR2_Q27
Solar/Wind Harmer
2.529
209022WHFR IPP
Adder
1.816
961331AF2-424 GEN
Solar/Wind Harmer
0.55
961421AF2-433 GEN
Solar/Wind Harmer
0.549
957921AF2-086 GEN
Solar/Wind Harmer
0.534
209142AF1-226 GEN
Solar/Wind Harmer
3.178
209093AE2-110 GEN
Solar/Wind Harmer
1.373
209120AE2-241 GEN
Solar/Wind Harmer
1.816
972245AH1-707 GEN
Adder
2.961
946691AF1-333 GEN
Solar/Wind Harmer
0.538
946741AF1-338 GEN
Solar/Wind Harmer
0.538
227287AC2-120 GEN
Solar/Wind Helper
0.382
226910AB2-157 C
Solar/Wind Helper
0.016
228754AB1-001 C
Solar/Wind Harmer
0.086
219137THOSOLAR C
Solar/Wind Harmer
0.744
219272CLEANLIGHT C
Solar/Wind Harmer
0.112
219688LUMSOLAR_S C
Solar/Wind Harmer
0.124
213942SCHUYLKILL
Adder
2.177
213942SCHUYLKILL
Adder
1.665
213957STHWK3-4
Adder
1.664
213957STHWK3-4
Adder
1.664
219914AD2-027 C
Solar/Wind Harmer
0.367
213561DLWR9-10
Adder
2.164
213561DLWR9-10
Adder
1.655
219607WPEMNERT C
Solar/Wind Harmer
0.254
219224BRL12CT4
Adder
5.408
214067T20SOLAR
Solar/Wind Harmer
0.152
213611FALLS1-3
Adder
2.13
213611FALLS1-3
Adder
2.13
20717128DIX_Z2-102
Solar/Wind Harmer
0.793
20715728PEM_W1-119
Solar/Wind Harmer
0.321
20715828PEM_W1-120
Solar/Wind Harmer
0.321
970025AG2-016 GEN
Solar/Wind Harmer
1.699
971189AH1-054 GEN
Solar/Wind Harmer
0.707
207459AE1-142 C O1
Solar/Wind Harmer
0.632
219620RIDERU C
Solar/Wind Harmer
0.033
20714328BYD_X4-031
Solar/Wind Harmer
0.169
20714428HOW_X1-037
Solar/Wind Harmer
0.737
971521AH1-258 GEN
Solar/Wind Harmer
1.612
20720428HOL_W1-112
Solar/Wind Harmer
0.206
20635928PARLN3&4
Adder
4.397
218455CINNBAY_CGEN
Adder
1.079
218526CNTRALGAS2 C
Solar/Wind Harmer
0.22
218524CNTRALGAS1 C
Solar/Wind Harmer
0.22
20675528CPH_W2-050
Solar/Wind Harmer
0.277
218404KENILWRTH C
Adder
0.772
217167KRNY_14
Adder
5.495
217086KRNY_131
Adder
5.449
217147KRNY_1212
Adder
5.227
217147KRNY_1212
Adder
5.134
217146KRNY_1234
Adder
5.122
217146KRNY_1234
Adder
5.087
966261AG1-495 GEN
Solar/Wind Harmer
1.06
20676328BVR_Y1-020
Solar/Wind Harmer
0.195
207511W3-106 GEN
Solar/Wind Harmer
0.387
207530AG1-191 GEN
Solar/Wind Harmer
0.811
20674828DL_W4-046
Solar/Wind Harmer
0.38
971009AG2-626 GEN
Solar/Wind Harmer
0.964
207408W3-077 C
Solar/Wind Harmer
0.298
20675728RH_W2-091
Solar/Wind Harmer
0.201
20675928HOL_W4-097
Solar/Wind Harmer
0.077
207484AF2-139 C O1
Solar/Wind Harmer
0.297
20675128HRM_W1-127
Solar/Wind Harmer
0.1
966421AG1-511 GEN
Solar/Wind Harmer
5.054
20462827N BANGR8
Adder
0.421
209116AE2-175 GEN
Solar/Wind Harmer
2.398
961261AF2-417 GEN
Solar/Wind Harmer
0.572
209026WIENIPP4
Adder
3.029
20486527WR_V4-052
Adder
0.598
209045AE2-271 GEN
Solar/Wind Harmer
9.184
959431AF2-234 GEN
Solar/Wind Harmer
1.075
964051AG1-259 GEN
Solar/Wind Harmer
0.721
964061AG1-260 GEN
Solar/Wind Harmer
0.721
959421AF2-233 GEN
Solar/Wind Harmer
0.537
208862AG1-362 C
Solar/Wind Harmer
0.439
217204WCALDSOLAR C
Solar/Wind Harmer
0.043
20674528F3S_W2-016
Solar/Wind Harmer
0.832
20676228FRD_X1-012
Solar/Wind Harmer
0.349
207471AF2-354 C
Solar/Wind Harmer
0.301
20674928WA_W3-044
Solar/Wind Harmer
0.284
964851AG1-348 GEN
Solar/Wind Harmer
1.034
20634528N27_Y2-018
Solar/Wind Harmer
0.158
20465127PORT CT
Adder
2.339
20674128FR_U2-059
Solar/Wind Harmer
0.108
966111AG1-480 GEN
Solar/Wind Harmer
0.051
966111AG1-480 GEN
Solar/Wind Harmer
1.931
211065PSPA IPP
Solar/Wind Harmer
0.262
211065PSPA IPP
Solar/Wind Harmer
0.262
208972BECR K09
Solar/Wind Harmer
0.596
209029WAYMART-WD
Solar/Wind Harmer
1.621
209009PEIP 2
Adder
4.402
209010PEIP 1
Adder
1.994
209010PEIP 1
Adder
0.292
961541AF2-445A GEN
Solar/Wind Harmer
1.816
961431AF2-434 GEN
Solar/Wind Harmer
0.549
20465527S.RDG CT
Adder
1.482
209054AE2-059 GEN
Solar/Wind Harmer
0.916
209059AE2-084 GEN
Solar/Wind Harmer
1.352
946751AF1-339 GEN
Solar/Wind Harmer
0.538
209130AF1-271A GEN
Solar/Wind Harmer
1.511
226929AD2-058 GEN
Solar/Wind Helper
0.107
971519AH1-257 GEN
Solar/Wind Harmer
1.483
207518AF1-320_GEN
Solar/Wind Harmer
2.15
207437AD2-070 GEN
Solar/Wind Harmer
0.177
20465127PORT CT
Adder
1.763
20671928W4-073
Solar/Wind Harmer
0.254
966181AG1-487 GEN
Solar/Wind Harmer
2.202
208909MACR G3
Adder
93.334
961301AF2-421 GEN
Solar/Wind Harmer
0.568
963151AG1-164 GEN
Solar/Wind Harmer
0.568
209023WIENIPP1
Adder
6.129
209025WIENIPP3
Adder
3.059
205941AD2-115 GEN
Solar/Wind Harmer
0.521
209010PEIP 1
Adder
0.363
212266LOR1
Solar/Wind Harmer
0.073
970237AG2-161 GEN
Solar/Wind Harmer
1.942
20467927PC_Q59Y356
Adder
0.47
961341AF2-425 GEN
Solar/Wind Harmer
0.55
212174INGE
Adder
0.608
20465527S.RDG CT
Adder
1.532
212507AE2-042_GEN
Solar/Wind Harmer
1.623
946731AF1-337 GEN
Solar/Wind Harmer
0.538
209071AE2-133 GEN
Solar/Wind Harmer
0.91
970665AG2-430 GEN
Solar/Wind Harmer
5.333
209018SUNBIPCT
Adder
4.003
972241AH1-705 GEN
Adder
3.065
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.628
G-007ALTFEXP_G-007A->PJM
CMTX
30.435
CBM NorthLTFEXP_CBM-N->PJM
CBM
46.928
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
2.42
BlueGrassPJM->LTFIMP_BlueG
CLTF
7.55
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
80.116
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.075
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
11.634

Details for CNASTONE-BRIGHTON 500.0 kV Ckt 1 line l/o PECO_P1-2_5007_SRT-A/* $ CHESCO $ PECO_P1-2_5007 $ L


Base Case Flowgate

Area:PJM
Facility Description:
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
Contingency Name:
PECO_P1-2_5007_SRT-A/* $ CHESCO $ PECO_P1-2_5007 $ L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.13 %
Rating:3098.0 MVA
Rating Type:B
MVA to Mitigate:3287.95
MW Contribution:4.09
Bus #Bus NameTypeMW Contribution
200200DELTA2 CT1
50/50
2.924
200193DELTA CT2
50/50
1.634
200203Y1-065-STG
50/50
5.81
200055ROCKSP 4
50/50
2.093
232907VN8
Adder
27.76
233996TM1833_GEN
Solar/Wind Harmer
0.001
233997TMININ_4.2
Solar/Wind Harmer
0.001
232406W1-004 FULL
Solar/Wind Harmer
0.598
233940AF2-379 C
Solar/Wind Harmer
0
232914OH NUG3
Adder
8.162
972281AH1-725 GEN
50/50
140.887
200201DELTA2 CT2
50/50
2.924
200034PCHBTM 2
50/50
17.02
200035PCHBTM 3
50/50
17.216
200205Y1-065-CTG2
50/50
3.351
233987AB2-037 GEN
Solar/Wind Harmer
0.01
233901CHERRYDALE C
Solar/Wind Harmer
0.001
232408W1-005 C
Solar/Wind Harmer
0.598
232410W1-006 C
Solar/Wind Harmer
0.598
232918OH NUG7
Adder
8.107
232905CHERITON_25
Adder
2.267
232926CRISFLD1
Adder
1.814
972069AH1-584 GEN
Solar/Wind Harmer
5.774
972071AH1-585 GEN
Solar/Wind Harmer
5.774
971747AH1-380 GEN
Solar/Wind Harmer
2.309
970545AG2-347 GEN
Solar/Wind Harmer
23.321
233946AB2-136 GEN
Solar/Wind Harmer
0.004
231940T-011
Adder
0.689
234036AF2-325 C
Solar/Wind Harmer
0.001
234041AC1-190 GEN
Solar/Wind Harmer
6.733
971149AH1-027 GEN
Solar/Wind Harmer
2.884
233939AC1-091 C
Solar/Wind Harmer
0.001
233970AC1-092 C
Solar/Wind Harmer
0.001
232899W1-062
Adder
8.871
233984AB2-036 GEN
Solar/Wind Harmer
6.694
232424Y1-079 C
Solar/Wind Harmer
0.001
234014AF1-036_GEN
Solar/Wind Harmer
2.137
231131BLOOM ENRGY
Adder
3.998
200202DELTA2 ST
50/50
4.962
200195DELTA ST
50/50
2.525
200052ROCKSP 1
50/50
2.116
200053ROCKSP 2
50/50
2.071
233923SMA
Solar/Wind Harmer
0.005
232912OH NUG1
Adder
8.162
232913OH NUG2
Adder
8.053
233990AG1-397 GEN
Solar/Wind Harmer
-0.147
232432Z2-076 GEN
Solar/Wind Harmer
0.012
234033AF1-007_GEN
Solar/Wind Harmer
-0.001
232904IR4
Adder
74.692
232920IR10
Adder
2.919
233955AB2-172 GEN
Solar/Wind Harmer
0.003
233973AC2-185 C
Solar/Wind Harmer
0.001
232813VAUGHN
Adder
0.542
233968AD2-076_GEN
Solar/Wind Harmer
2.137
970597AG2-380 GEN
Solar/Wind Harmer
3.828
232436AB1-176 C
Solar/Wind Harmer
0
200192DELTA CT1
50/50
1.634
200194DELTA CT3
50/50
1.634
200204Y1-065-CTG1
50/50
3.351
200054ROCKSP 3
50/50
2.138
232916OH NUG5
Adder
8.162
232921TASLEY2G
Adder
4.77
972073AH1-586 GEN
Solar/Wind Harmer
8.66
233994AC2-023 GEN
Solar/Wind Harmer
0.004
234015AF2-250 C
Solar/Wind Harmer
0
233900O-025 C
Adder
1.088
960671AF2-358 GEN
Solar/Wind Harmer
11.546
233990AG1-397 GEN
Solar/Wind Harmer
1.258
972133AH1-634 GEN
Solar/Wind Harmer
3.406
232417X3-008 C
Solar/Wind Harmer
0.001
233971AC1-093 C
Solar/Wind Harmer
0.04
970695AG2-447 GEN
Solar/Wind Harmer
2.306
233952AC2-187 GEN
Solar/Wind Harmer
0.001
233918AB1-142 GEN
Solar/Wind Harmer
0.235
233982AB2-133 GEN
Solar/Wind Harmer
0.004
972251AH1-710 GEN
Adder
40.011
228202CUMB CT
Adder
12.756
228711V2-041C
Solar/Wind Harmer
0
971553AH1-274 GEN
Solar/Wind Harmer
1.203
230430AE1-229_GEN
Solar/Wind Harmer
0.013
213497CHSTR7-9
Adder
2.091
230415AB2-049 C
Solar/Wind Harmer
0
228304LOGAN
Adder
16.591
228729W2-030 C
Solar/Wind Harmer
0.001
213958STHWK5-6
Adder
2.044
219623KINSLEYBEA C
Solar/Wind Harmer
0
219766PARADISE C
Solar/Wind Harmer
0
219912AD2-042 GEN
Solar/Wind Harmer
0.001
213560DLW11-12
Adder
2.014
219906AC1-017 C
Solar/Wind Harmer
0
219610FLORENCE C
Solar/Wind Harmer
0
219348LDSOLAR C
Solar/Wind Harmer
0
219221BRL12CT1
Adder
6.506
219223BRL12CT3
Adder
6.506
213815MOSER1-3
Adder
2.587
20716028EGP_W2-019
Solar/Wind Harmer
0
20720828JCB_W4-025
Solar/Wind Harmer
0
20715028HAN_X4-015
Solar/Wind Harmer
0
20636028O CRK C1
Adder
5.024
971667AH1-334 GEN
Solar/Wind Harmer
1.253
219727YARDVSOLFA C
Solar/Wind Harmer
0
20714528FRN_Y2-051
Solar/Wind Harmer
0
219276PARKLANDSO C
Solar/Wind Harmer
0
20716228APLW2-078
Solar/Wind Harmer
0
20720528MAN_W1-024
Solar/Wind Harmer
0
967451AG2-055 C O1
Solar/Wind Harmer
170.235
219612MATRIX C
Solar/Wind Harmer
0
218438BLK ROCK C
Solar/Wind Harmer
0
20635828PARLN1&2
Adder
2.282
20635928PARLN3&4
Adder
2.282
20635028RRCT1&2
Adder
8
20635128RRCT3&4
Adder
6.632
219908AB1-139 C
Solar/Wind Harmer
0
20673728F2S_V4-070
Solar/Wind Harmer
0
217186ESSEX_G9
Adder
10.582
217194REDH C
Solar/Wind Harmer
0
20676728BRNX1-095
Solar/Wind Harmer
0
207510AF2-138 C
Solar/Wind Harmer
0.001
20674628WNG_W3-110
Solar/Wind Harmer
0
971007AG2-625 GEN
Solar/Wind Harmer
1.051
20466127PORT 5CT
Adder
16.601
20633028GILCT9
Adder
17.74
20465427SHAW CT
Adder
2.406
209025WIENIPP3
Adder
3.017
963071AG1-156 GEN
Solar/Wind Harmer
0.252
970095AG2-074 GEN
Solar/Wind Harmer
2.876
209027LOR2_Q27
Solar/Wind Harmer
0.001
209022WHFR IPP
Adder
1.777
209142AF1-226 GEN
Solar/Wind Harmer
1.507
209093AE2-110 GEN
Solar/Wind Harmer
0.861
209120AE2-241 GEN
Solar/Wind Harmer
0.861
972245AH1-707 GEN
Adder
2.852
227287AC2-120 GEN
Solar/Wind Helper
0.355
226910AB2-157 C
Solar/Wind Helper
0.014
3141196NOKESVL
Solar/Wind Helper
0.902
233998TM1NIN_3.36
Solar/Wind Harmer
0.001
232404W1-003 C
Solar/Wind Harmer
0.598
232917OH NUG6
Adder
8.126
232915OH NUG4
Adder
8.107
232428Y3-058 C
Solar/Wind Harmer
0.001
232919VN10
Adder
2.593
971195AH1-057 GEN
Solar/Wind Harmer
0.577
965821AG1-450 GEN
Solar/Wind Harmer
4.811
232426Y1-080 FULL
Solar/Wind Harmer
0
232434Z2-077 GEN
Solar/Wind Harmer
0.039
970277AG2-181 GEN
Solar/Wind Harmer
0.539
233964AF2-378 GEN
Solar/Wind Harmer
0
972177AH1-672 GEN
Solar/Wind Harmer
9.405
232901NORTHST
Adder
7.684
233972AC1-094 C
Solar/Wind Harmer
0.29
233954AC2-188 GEN
Solar/Wind Harmer
0.001
233950AC2-186 GEN
Solar/Wind Harmer
0.001
232900DEMECSMY
Adder
8.509
232910NRG_G1
Adder
7.949
234012AE2-112_GEN
Solar/Wind Harmer
2.137
232422X3-066 FULL
Solar/Wind Harmer
0.077
233930AB2-032 GEN
Solar/Wind Harmer
0.88
233915AB1-141 GEN
Solar/Wind Harmer
0.235
231918WEST 1
Adder
2.999
231917EM10
Adder
2.088
228206SHRMN CT
Adder
12.788
228732V1-021 C
Adder
0.146
945431AF1-208 GEN
Solar/Wind Harmer
4.629
970997AG2-616 GEN
Solar/Wind Harmer
5.537
228351V2-046C
Solar/Wind Harmer
0.001
230511AF1-262
Solar/Wind Harmer
0
213497CHSTR7-9
Adder
2.091
213497CHSTR7-9
Adder
2.091
228728W1-130C
Solar/Wind Harmer
0
230434AG1-499 GEN
Solar/Wind Harmer
0.001
213958STHWK5-6
Adder
2.044
219258KINSLEYDEP C
Solar/Wind Harmer
0
219904AC1-010 C
Solar/Wind Harmer
0
218660EHAMPSOLAR C
Solar/Wind Harmer
0
219686LUMSOLAR_N C
Solar/Wind Harmer
0
219287REEVESEAST C
Solar/Wind Harmer
0
213560DLW11-12
Adder
2.014
219907AC1-030 C
Solar/Wind Harmer
0
219304NAMERICA C
Solar/Wind Harmer
0.067
219222BRL12CT2
Adder
6.506
213611FALLS1-3
Adder
2.543
214194N WALES4
Adder
0.609
20720728JCB_W1-129
Solar/Wind Harmer
0
207522AF2-254 C
Solar/Wind Harmer
0.661
207487AE2-000G4
Solar/Wind Harmer
8.989
207445AB1-138_GEN
Solar/Wind Harmer
0
20628028LAKEHURS
Adder
1.326
20714828MDF_W3-079
Solar/Wind Harmer
0.069
207454AA2-184 E
Solar/Wind Harmer
0.001
20715228NPK_W1-113
Solar/Wind Harmer
0
20742028HF_AC1-207
Solar/Wind Harmer
0.001
217197RE CRAN C
Solar/Wind Harmer
0
20635828PARLN1&2
Adder
5.039
20635028RRCT1&2
Adder
7.877
20635128RRCT3&4
Adder
7.603
217213AMBOY SO C
Solar/Wind Harmer
0
972275AH1-722 GEN
Adder
21.193
207528AF2-192 GEN
Solar/Wind Harmer
0
20673628F1S_V4-069
Solar/Wind Harmer
0
20675428EAM_W2-061
Solar/Wind Harmer
0
218449LINSOLAR C
Solar/Wind Harmer
0
20676428JCR_X2-075
Solar/Wind Harmer
0
217121ECCF
Adder
0.287
217083KRNY_132
Adder
6.152
20674328GAR_V4-001
Solar/Wind Harmer
0
20675828AU_W4-064
Solar/Wind Harmer
0
971519AH1-257 GEN
Solar/Wind Harmer
1.031
207437AD2-070 GEN
Solar/Wind Harmer
0.041
20465127PORT CT
Adder
1.881
20671928W4-073
Solar/Wind Harmer
0
966181AG1-487 GEN
Solar/Wind Harmer
2.393
208909MACR G3
Adder
98.576
209023WIENIPP1
Adder
6.169
209025WIENIPP3
Adder
3.079
209010PEIP 1
Adder
0.369
205941AD2-115 GEN
Solar/Wind Harmer
0.065
212266LOR1
Solar/Wind Harmer
0.264
212174INGE
Adder
0.591
20467927PC_Q59Y356
Adder
0.455
20465527S.RDG CT
Adder
1.476
233944AB2-135 GEN
Solar/Wind Harmer
0.004
233933AB2-153 GEN
Solar/Wind Harmer
0.001
232416X2-083
Adder
0.409
228251CARLLS#4
Adder
0.485
230422AE1-104_GEN1
Solar/Wind Harmer
10.351
230425AE1-104_GEN2
Solar/Wind Harmer
10.351
213589EDDYSTN4
Adder
61.019
213587EDDYSTN3
Adder
61.005
228307PCLP GT
Adder
9.238
228304LOGAN
Adder
18.447
230407AD2-065 C
Solar/Wind Harmer
0
972233AH1-701 GEN
Adder
3.191
219921AF1-264
Solar/Wind Harmer
0
219615MILLCREEK C
Solar/Wind Harmer
0
213815MOSER1-3
Adder
2.587
213815MOSER1-3
Adder
2.587
213535CROYDN11
Adder
7.451
20716428NHV_W2-082
Solar/Wind Harmer
0
207500AE2-000G1
Solar/Wind Harmer
8.989
207497AE2-000G2
Solar/Wind Harmer
8.989
207507AE2-000G3
Solar/Wind Harmer
8.989
20636128O CRK C2
Adder
4.581
20714928UPF_X1-085
Solar/Wind Harmer
0
219114HARTZY_C
Solar/Wind Harmer
0
20628028LAKEHURS
Adder
0.671
20720628TIN_W1-124
Solar/Wind Harmer
0.001
20716928W4-060COL
Solar/Wind Harmer
0
218440SUMMTASSOC C
Solar/Wind Harmer
0
218418LINDEN_G5
Adder
11.528
218419LINDEN_G6
Adder
11.528
972260AH1-715 GEN1
Adder
9.231
20673828FLE_V3-070
Solar/Wind Harmer
0
207442AE1-156 GEN
Solar/Wind Harmer
0.04
20676128MHD_W3-029
Solar/Wind Harmer
0
219036LINDEN_G7
Adder
11.172
219035LINDEN_G8
Adder
11.013
972261AH1-715 GEN2
Adder
10.694
972237AH1-703 GEN
Adder
6.698
217086KRNY_131
Adder
6.165
217083KRNY_132
Adder
6.113
20671828STAW2-080
Solar/Wind Harmer
0
20674528F3S_W2-016
Solar/Wind Harmer
0
20676228FRD_X1-012
Solar/Wind Harmer
0
20674928WA_W3-044
Solar/Wind Harmer
0
20465127PORT CT
Adder
2.496
20674128FR_U2-059
Solar/Wind Harmer
0
966111AG1-480 GEN
Solar/Wind Harmer
2.107
211065PSPA IPP
Solar/Wind Harmer
0
211065PSPA IPP
Solar/Wind Harmer
0
209029WAYMART-WD
Solar/Wind Harmer
0.001
209009PEIP 2
Adder
4.485
209010PEIP 1
Adder
2.032
209010PEIP 1
Adder
0.298
208972BECR K09
Solar/Wind Harmer
0
961541AF2-445A GEN
Solar/Wind Harmer
1.232
20465527S.RDG CT
Adder
1.429
226929AD2-058 GEN
Solar/Wind Helper
0.102
231906DC3 NUG
Adder
12.846
231902DC CT7
Adder
10.269
231907DC10
Adder
3.207
971983AH1-536 GEN
Solar/Wind Harmer
1.623
233935AB2-179 C
Solar/Wind Harmer
1.252
231919CHRIST1
Adder
3.941
231920CHRIST2
Adder
3.853
970453AG2-297 GEN
Solar/Wind Harmer
1.97
228260V4-054C
Solar/Wind Harmer
0
228309CCLP NUG
Adder
19.867
228309CCLP NUG
Adder
18.897
972141AH1-641 GEN
Solar/Wind Harmer
2.567
964001AG1-254 GEN
Solar/Wind Harmer
0.298
971011AG2-627 GEN
Solar/Wind Harmer
4.091
971535AH1-265 GEN
Solar/Wind Harmer
2.1
227927V4-067C
Solar/Wind Harmer
0
228754AB1-001 C
Solar/Wind Harmer
0
213942SCHUYLKILL
Adder
2.676
213942SCHUYLKILL
Adder
2.046
213957STHWK3-4
Adder
2.044
213957STHWK3-4
Adder
2.044
219272CLEANLIGHT C
Solar/Wind Harmer
0
219914AD2-027 C
Solar/Wind Harmer
0
219688LUMSOLAR_S C
Solar/Wind Harmer
0
213561DLWR9-10
Adder
2.634
213561DLWR9-10
Adder
2.014
219607WPEMNERT C
Solar/Wind Harmer
0
219224BRL12CT4
Adder
6.506
214067T20SOLAR
Solar/Wind Harmer
0
213611FALLS1-3
Adder
2.543
213611FALLS1-3
Adder
2.543
20717128DIX_Z2-102
Solar/Wind Harmer
0
20715728PEM_W1-119
Solar/Wind Harmer
0
20715828PEM_W1-120
Solar/Wind Harmer
0
970025AG2-016 GEN
Solar/Wind Harmer
1.298
971189AH1-054 GEN
Solar/Wind Harmer
0.54
207459AE1-142 C O1
Solar/Wind Harmer
0.001
20714328BYD_X4-031
Solar/Wind Harmer
0.106
20714428HOW_X1-037
Solar/Wind Harmer
0
971521AH1-258 GEN
Solar/Wind Harmer
1.205
20720428HOL_W1-112
Solar/Wind Harmer
0
20635928PARLN3&4
Adder
5.039
218455CINNBAY_CGEN
Adder
1.236
218526CNTRALGAS2 C
Solar/Wind Harmer
0.518
218524CNTRALGAS1 C
Solar/Wind Harmer
0.517
218404KENILWRTH C
Adder
0.866
217167KRNY_14
Adder
6.152
217086KRNY_131
Adder
6.099
217147KRNY_1212
Adder
5.851
217147KRNY_1212
Adder
5.747
217146KRNY_1234
Adder
5.734
217146KRNY_1234
Adder
5.695
20676328BVR_Y1-020
Solar/Wind Harmer
0
207511W3-106 GEN
Solar/Wind Harmer
0.21
207530AG1-191 GEN
Solar/Wind Harmer
0.001
20674828DL_W4-046
Solar/Wind Harmer
0
971009AG2-626 GEN
Solar/Wind Harmer
0.67
207408W3-077 C
Solar/Wind Harmer
0
20675728RH_W2-091
Solar/Wind Harmer
0
20675928HOL_W4-097
Solar/Wind Harmer
0
207484AF2-139 C O1
Solar/Wind Harmer
0
966421AG1-511 GEN
Solar/Wind Harmer
3.774
20675128HRM_W1-127
Solar/Wind Harmer
0
20462827N BANGR8
Adder
0.447
209116AE2-175 GEN
Solar/Wind Harmer
0.004
209026WIENIPP4
Adder
3.048
20486527WR_V4-052
Adder
0.576
209045AE2-271 GEN
Solar/Wind Harmer
6.2
3138216PACIFIC
Solar/Wind Helper
0.039
316411AF1-147_GEN1
Solar/Wind Helper
0.775
316415AF1-147_GEN2
Solar/Wind Helper
0.775
3141426STAFORD
Solar/Wind Helper
0.05
HAMLETPJM->LTFIMP_HAMLET
CLTF
4.13
G-007ALTFEXP_G-007A->PJM
CMTX
34.79
CBM NorthLTFEXP_CBM-N->PJM
CBM
50.245
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
2.937
BlueGrassPJM->LTFIMP_BlueG
CLTF
9.158
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
89.931
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.383
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
14.018

Details for CNASTONE-BRIGHTON 500.0 kV Ckt 1 line l/o AP_P2-2_PE-230-010_SRT-A


Base Case Flowgate

Area:PJM
Facility Description:
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_PE-230-010_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:103.24 %
Rating:3098.0 MVA
Rating Type:B
MVA to Mitigate:3198.5
MW Contribution:4.7
Bus #Bus NameTypeMW Contribution
972281AH1-725 GEN
50/50
118.337
200061HUNTR401
50/50
2.914
200201DELTA2 CT2
50/50
2.029
200034PCHBTM 2
50/50
11.816
200205Y1-065-CTG2
50/50
2.358
200035PCHBTM 3
50/50
11.742
233987AB2-037 GEN
Solar/Wind Harmer
7.961
971149AH1-027 GEN
Solar/Wind Harmer
2.365
233901CHERRYDALE C
Solar/Wind Harmer
0.787
232408W1-005 C
Solar/Wind Harmer
0.7
232410W1-006 C
Solar/Wind Harmer
0.7
970545AG2-347 GEN
Solar/Wind Harmer
45.719
972069AH1-584 GEN
Solar/Wind Harmer
6.258
972071AH1-585 GEN
Solar/Wind Harmer
6.258
232918OH NUG7
Adder
6.13
200058HUNTR101
50/50
1.53
200059HUNTR201
50/50
1.53
200060HUNTR301
50/50
1.53
200202DELTA2 ST
50/50
3.443
200195DELTA ST
50/50
1.752
200052ROCKSP 1
50/50
1.489
200053ROCKSP 2
50/50
1.457
234033AF1-007_GEN
Solar/Wind Harmer
16.338
233923SMA
Solar/Wind Harmer
3.245
232432Z2-076 GEN
Solar/Wind Harmer
0.092
232904IR4
Adder
56.49
232912OH NUG1
Adder
6.172
232913OH NUG2
Adder
6.089
232920IR10
Adder
2.208
233990AG1-397 GEN
Solar/Wind Harmer
0.039
233973AC2-185 C
Solar/Wind Harmer
2.524
233955AB2-172 GEN
Solar/Wind Harmer
3.493
232813VAUGHN
Adder
0.411
233968AD2-076_GEN
Solar/Wind Harmer
4.614
970597AG2-380 GEN
Solar/Wind Harmer
2.897
232436AB1-176 C
Solar/Wind Harmer
0.159
231906DC3 NUG
Adder
9.729
231902DC CT7
Adder
7.778
231907DC10
Adder
2.429
971983AH1-536 GEN
Solar/Wind Harmer
5.199
233935AB2-179 C
Solar/Wind Harmer
1.725
231919CHRIST1
Adder
3.018
231920CHRIST2
Adder
2.951
970453AG2-297 GEN
Solar/Wind Harmer
1.699
228260V4-054C
Solar/Wind Harmer
0.631
228309CCLP NUG
Adder
15.872
228309CCLP NUG
Adder
15.097
972141AH1-641 GEN
Solar/Wind Harmer
1.765
964001AG1-254 GEN
Solar/Wind Harmer
1.247
971011AG2-627 GEN
Solar/Wind Harmer
4.696
971535AH1-265 GEN
Solar/Wind Harmer
2.607
227927V4-067C
Solar/Wind Harmer
0.121
228754AB1-001 C
Solar/Wind Harmer
0.085
219137THOSOLAR C
Solar/Wind Harmer
0.735
213942SCHUYLKILL
Adder
2.157
213942SCHUYLKILL
Adder
1.649
213957STHWK3-4
Adder
1.649
213957STHWK3-4
Adder
1.649
219272CLEANLIGHT C
Solar/Wind Harmer
0.11
219914AD2-027 C
Solar/Wind Harmer
0.363
219688LUMSOLAR_S C
Solar/Wind Harmer
0.122
213561DLWR9-10
Adder
2.143
213561DLWR9-10
Adder
1.639
219607WPEMNERT C
Solar/Wind Harmer
0.251
219224BRL12CT4
Adder
5.352
214067T20SOLAR
Solar/Wind Harmer
0.151
213611FALLS1-3
Adder
2.11
213611FALLS1-3
Adder
2.11
20717128DIX_Z2-102
Solar/Wind Harmer
0.785
20715728PEM_W1-119
Solar/Wind Harmer
0.318
20715828PEM_W1-120
Solar/Wind Harmer
0.318
970025AG2-016 GEN
Solar/Wind Harmer
1.683
971189AH1-054 GEN
Solar/Wind Harmer
0.701
207459AE1-142 C O1
Solar/Wind Harmer
0.627
219620RIDERU C
Solar/Wind Harmer
0.033
20714328BYD_X4-031
Solar/Wind Harmer
0.167
20714428HOW_X1-037
Solar/Wind Harmer
0.731
971521AH1-258 GEN
Solar/Wind Harmer
1.601
20720428HOL_W1-112
Solar/Wind Harmer
0.205
20635928PARLN3&4
Adder
4.374
218455CINNBAY_CGEN
Adder
1.073
200200DELTA2 CT1
50/50
2.029
200193DELTA CT2
50/50
1.134
200203Y1-065-STG
50/50
4.088
200055ROCKSP 4
50/50
1.472
232907VN8
Adder
20.985
233996TM1833_GEN
Solar/Wind Harmer
0.885
233997TMININ_4.2
Solar/Wind Harmer
0.885
232406W1-004 FULL
Solar/Wind Harmer
0.7
233940AF2-379 C
Solar/Wind Harmer
0.13
972133AH1-634 GEN
Solar/Wind Harmer
6.927
232914OH NUG3
Adder
6.172
232916OH NUG5
Adder
6.172
972073AH1-586 GEN
Solar/Wind Harmer
6.549
232921TASLEY2G
Adder
3.607
233994AC2-023 GEN
Solar/Wind Harmer
1.878
234015AF2-250 C
Solar/Wind Harmer
0.084
233990AG1-397 GEN
Solar/Wind Harmer
0.802
233900O-025 C
Adder
0.823
233971AC1-093 C
Solar/Wind Harmer
0.548
970695AG2-447 GEN
Solar/Wind Harmer
2.502
960671AF2-358 GEN
Solar/Wind Harmer
12.512
232417X3-008 C
Solar/Wind Harmer
1.397
233952AC2-187 GEN
Solar/Wind Harmer
0.786
233918AB1-142 GEN
Solar/Wind Harmer
0.689
233982AB2-133 GEN
Solar/Wind Harmer
3.384
972251AH1-710 GEN
Adder
30.788
228202CUMB CT
Adder
10.167
228711V2-041C
Solar/Wind Harmer
0.37
971553AH1-274 GEN
Solar/Wind Harmer
1.489
230430AE1-229_GEN
Solar/Wind Harmer
5.399
230415AB2-049 C
Solar/Wind Harmer
0.116
228729W2-030 C
Solar/Wind Harmer
0.353
228304LOGAN
Adder
13.311
213497CHSTR7-9
Adder
1.666
219623KINSLEYBEA C
Solar/Wind Harmer
0.259
219766PARADISE C
Solar/Wind Harmer
0.191
213958STHWK5-6
Adder
1.649
219291REEVESSOUT C
Solar/Wind Harmer
0.036
219912AD2-042 GEN
Solar/Wind Harmer
0.481
219236SOUTHERNHQ C
Solar/Wind Harmer
0.041
213560DLW11-12
Adder
1.639
219906AC1-017 C
Solar/Wind Harmer
0.134
219610FLORENCE C
Solar/Wind Harmer
0.831
219348LDSOLAR C
Solar/Wind Harmer
0.359
219221BRL12CT1
Adder
5.352
219223BRL12CT3
Adder
5.352
213815MOSER1-3
Adder
2.125
959561AF2-247 GEN
Solar/Wind Harmer
0.289
20716028EGP_W2-019
Solar/Wind Harmer
0.276
20720828JCB_W4-025
Solar/Wind Harmer
0.27
20715028HAN_X4-015
Solar/Wind Harmer
0.177
20636028O CRK C1
Adder
4.2
971667AH1-334 GEN
Solar/Wind Harmer
1.631
219727YARDVSOLFA C
Solar/Wind Harmer
0.54
20714528FRN_Y2-051
Solar/Wind Harmer
0.175
219276PARKLANDSO C
Solar/Wind Harmer
0.274
219918AC2-009 C
Solar/Wind Harmer
0.036
20716228APLW2-078
Solar/Wind Harmer
0.523
20720528MAN_W1-024
Solar/Wind Harmer
0.15
967451AG2-055 C O1
Solar/Wind Harmer
102.625
219612MATRIX C
Solar/Wind Harmer
0.109
218438BLK ROCK C
Solar/Wind Harmer
0.081
20635828PARLN1&2
Adder
1.981
20635928PARLN3&4
Adder
1.981
20635028RRCT1&2
Adder
6.963
20635128RRCT3&4
Adder
5.773
219908AB1-139 C
Solar/Wind Harmer
0.225
219919AE1-041 FULL
Solar/Wind Harmer
0.024
219249CENTRALDIV C
Solar/Wind Harmer
0.023
20673728F2S_V4-070
Solar/Wind Harmer
0.106
217211CAMDEN ST C
Solar/Wind Harmer
0.014
217186ESSEX_G9
Adder
9.43
217169METRODIV C
Solar/Wind Harmer
0.023
217194REDH C
Solar/Wind Harmer
0.29
20676728BRNX1-095
Solar/Wind Harmer
0.104
207510AF2-138 C
Solar/Wind Harmer
1.051
20674628WNG_W3-110
Solar/Wind Harmer
0.238
971007AG2-625 GEN
Solar/Wind Harmer
1.518
20633028GILCT9
Adder
16.774
966181AG1-487 GEN
Solar/Wind Harmer
0.149
20466127PORT 5CT
Adder
15.629
20465427SHAW CT
Adder
2.273
963161AG1-165 GEN
Solar/Wind Harmer
0.573
209025WIENIPP3
Adder
3.021
963071AG1-156 GEN
Solar/Wind Harmer
1.573
970095AG2-074 GEN
Solar/Wind Harmer
3.57
209027LOR2_Q27
Solar/Wind Harmer
2.553
209022WHFR IPP
Adder
1.833
961331AF2-424 GEN
Solar/Wind Harmer
0.556
961421AF2-433 GEN
Solar/Wind Harmer
0.555
957921AF2-086 GEN
Solar/Wind Harmer
0.539
209142AF1-226 GEN
Solar/Wind Harmer
3.21
209093AE2-110 GEN
Solar/Wind Harmer
1.386
209120AE2-241 GEN
Solar/Wind Harmer
1.834
972245AH1-707 GEN
Adder
2.992
972221AH1-695 GEN
Adder
79.452
946691AF1-333 GEN
Solar/Wind Harmer
0.544
946741AF1-338 GEN
Solar/Wind Harmer
0.544
227287AC2-120 GEN
Solar/Wind Helper
0.359
226910AB2-157 C
Solar/Wind Helper
0.015
218526CNTRALGAS2 C
Solar/Wind Harmer
0.219
218524CNTRALGAS1 C
Solar/Wind Harmer
0.219
20675528CPH_W2-050
Solar/Wind Harmer
0.276
218404KENILWRTH C
Adder
0.77
217167KRNY_14
Adder
5.483
217086KRNY_131
Adder
5.436
217147KRNY_1212
Adder
5.215
217147KRNY_1212
Adder
5.122
217146KRNY_1234
Adder
5.11
217146KRNY_1234
Adder
5.076
966261AG1-495 GEN
Solar/Wind Harmer
1.062
20676328BVR_Y1-020
Solar/Wind Harmer
0.195
207530AG1-191 GEN
Solar/Wind Harmer
0.813
207511W3-106 GEN
Solar/Wind Harmer
0.387
20674828DL_W4-046
Solar/Wind Harmer
0.382
971009AG2-626 GEN
Solar/Wind Harmer
0.968
20675928HOL_W4-097
Solar/Wind Harmer
0.077
207408W3-077 C
Solar/Wind Harmer
0.3
971747AH1-380 GEN
Solar/Wind Harmer
2.503
232905CHERITON_25
Adder
1.714
232926CRISFLD1
Adder
1.371
231940T-011
Adder
0.521
233939AC1-091 C
Solar/Wind Harmer
0.614
233970AC1-092 C
Solar/Wind Harmer
0.614
233946AB2-136 GEN
Solar/Wind Harmer
2.788
234036AF2-325 C
Solar/Wind Harmer
0.64
234041AC1-190 GEN
Solar/Wind Harmer
6.254
232899W1-062
Adder
6.716
233984AB2-036 GEN
Solar/Wind Harmer
8.677
232424Y1-079 C
Solar/Wind Harmer
0.392
234014AF1-036_GEN
Solar/Wind Harmer
1.883
231131BLOOM ENRGY
Adder
3.029
233944AB2-135 GEN
Solar/Wind Harmer
3.64
233933AB2-153 GEN
Solar/Wind Harmer
0.782
232416X2-083
Adder
0.311
228251CARLLS#4
Adder
0.387
230433AD2-135 GEN
Solar/Wind Harmer
0.062
230422AE1-104_GEN1
Solar/Wind Harmer
20.663
230425AE1-104_GEN2
Solar/Wind Harmer
20.663
228307PCLP GT
Adder
7.403
230407AD2-065 C
Solar/Wind Harmer
0.081
228304LOGAN
Adder
14.8
972233AH1-701 GEN
Adder
2.563
213589EDDYSTN4
Adder
48.645
213587EDDYSTN3
Adder
48.64
219921AF1-264
Solar/Wind Harmer
0.088
219615MILLCREEK C
Solar/Wind Harmer
0.143
213535CROYDN11
Adder
6.132
213815MOSER1-3
Adder
2.125
213815MOSER1-3
Adder
2.125
20716428NHV_W2-082
Solar/Wind Harmer
1.058
207500AE2-000G1
Solar/Wind Harmer
18.72
207497AE2-000G2
Solar/Wind Harmer
18.72
207507AE2-000G3
Solar/Wind Harmer
18.72
20636128O CRK C2
Adder
3.83
963401AG1-189 GEN
Solar/Wind Harmer
0.683
963391AG1-188 GEN
Solar/Wind Harmer
1.139
20714928UPF_X1-085
Solar/Wind Harmer
0.242
219114HARTZY_C
Solar/Wind Harmer
0.495
20628028LAKEHURS
Adder
0.565
219817TRENTONSOL C
Solar/Wind Harmer
0.653
20641628MLH_W1-032
Solar/Wind Harmer
0.173
20720628TIN_W1-124
Solar/Wind Harmer
0.59
20716928W4-060COL
Solar/Wind Harmer
0.42
924131AB2-057 GEN
Solar/Wind Harmer
0.607
218440SUMMTASSOC C
Solar/Wind Harmer
0.076
20673828FLE_V3-070
Solar/Wind Harmer
0.271
218418LINDEN_G5
Adder
10.138
218419LINDEN_G6
Adder
10.138
972260AH1-715 GEN1
Adder
8.118
207442AE1-156 GEN
Solar/Wind Harmer
0.44
20676128MHD_W3-029
Solar/Wind Harmer
0.282
219036LINDEN_G7
Adder
9.871
219035LINDEN_G8
Adder
9.73
972261AH1-715 GEN2
Adder
9.449
217081WEATEXAS C
Solar/Wind Harmer
0.051
217202FBANKSOLAR C
Solar/Wind Harmer
0.043
20671828STAW2-080
Solar/Wind Harmer
0.062
217201HACKENSOLA C
Solar/Wind Harmer
0.043
972237AH1-703 GEN
Adder
5.968
217206BARNGR HS C
Solar/Wind Harmer
0.018
217086KRNY_131
Adder
5.495
217083KRNY_132
Adder
5.448
20674528F3S_W2-016
Solar/Wind Harmer
0.832
217204WCALDSOLAR C
Solar/Wind Harmer
0.043
20676228FRD_X1-012
Solar/Wind Harmer
0.349
207471AF2-354 C
Solar/Wind Harmer
0.302
20674928WA_W3-044
Solar/Wind Harmer
0.285
964851AG1-348 GEN
Solar/Wind Harmer
1.039
20634528N27_Y2-018
Solar/Wind Harmer
0.159
20674128FR_U2-059
Solar/Wind Harmer
0.109
20465127PORT CT
Adder
2.351
966111AG1-480 GEN
Solar/Wind Harmer
0.051
966111AG1-480 GEN
Solar/Wind Harmer
1.939
211065PSPA IPP
Solar/Wind Harmer
0.264
211065PSPA IPP
Solar/Wind Harmer
0.264
20465527S.RDG CT
Adder
1.569
208972BECR K09
Solar/Wind Harmer
0.6
961541AF2-445A GEN
Solar/Wind Harmer
1.834
209029WAYMART-WD
Solar/Wind Harmer
1.631
209009PEIP 2
Adder
4.428
209010PEIP 1
Adder
2.006
209010PEIP 1
Adder
0.294
20675728RH_W2-091
Solar/Wind Harmer
0.202
207484AF2-139 C O1
Solar/Wind Harmer
0.299
20675128HRM_W1-127
Solar/Wind Harmer
0.101
20462827N BANGR8
Adder
0.423
966421AG1-511 GEN
Solar/Wind Harmer
5.074
209116AE2-175 GEN
Solar/Wind Harmer
2.412
20486527WR_V4-052
Adder
0.632
961261AF2-417 GEN
Solar/Wind Harmer
0.575
209026WIENIPP4
Adder
3.052
208862AG1-362 C
Solar/Wind Harmer
0.472
209045AE2-271 GEN
Solar/Wind Harmer
9.276
959431AF2-234 GEN
Solar/Wind Harmer
1.087
964051AG1-259 GEN
Solar/Wind Harmer
0.729
964061AG1-260 GEN
Solar/Wind Harmer
0.729
959421AF2-233 GEN
Solar/Wind Harmer
0.544
960921AF2-383 GEN
Solar/Wind Harmer
0.167
20465027TOLNA CT
Adder
2.046
960921AF2-383 GEN
Solar/Wind Harmer
1.281
205932AD2-116_GEN
Solar/Wind Harmer
0.494
205956AE1-196_GEN
Solar/Wind Harmer
0.494
205943AE1-185 GEN
Solar/Wind Harmer
0.493
205951AE1-129_GEN
Solar/Wind Harmer
6.856
20478527GLRA_Q45
Adder
0.191
961431AF2-434 GEN
Solar/Wind Harmer
0.555
209054AE2-059 GEN
Solar/Wind Harmer
0.926
209059AE2-084 GEN
Solar/Wind Harmer
1.367
946751AF1-339 GEN
Solar/Wind Harmer
0.544
209130AF1-271A GEN
Solar/Wind Harmer
1.528
226929AD2-058 GEN
Solar/Wind Helper
0.102
200192DELTA CT1
50/50
1.134
200194DELTA CT3
50/50
1.134
200204Y1-065-CTG1
50/50
2.358
200054ROCKSP 3
50/50
1.504
232901NORTHST
Adder
5.815
233998TM1NIN_3.36
Solar/Wind Harmer
0.885
232404W1-003 C
Solar/Wind Harmer
0.7
232434Z2-077 GEN
Solar/Wind Harmer
0.175
232917OH NUG6
Adder
6.144
232915OH NUG4
Adder
6.13
232428Y3-058 C
Solar/Wind Harmer
0.583
971195AH1-057 GEN
Solar/Wind Harmer
0.765
233972AC1-094 C
Solar/Wind Harmer
0.463
972177AH1-672 GEN
Solar/Wind Harmer
9.384
232919VN10
Adder
1.961
232426Y1-080 FULL
Solar/Wind Harmer
0.134
970277AG2-181 GEN
Solar/Wind Harmer
3.503
965821AG1-450 GEN
Solar/Wind Harmer
3.637
233964AF2-378 GEN
Solar/Wind Harmer
0.089
232900DEMECSMY
Adder
6.442
233954AC2-188 GEN
Solar/Wind Harmer
0.786
233950AC2-186 GEN
Solar/Wind Harmer
0.393
232910NRG_G1
Adder
6.018
234012AE2-112_GEN
Solar/Wind Harmer
1.601
232422X3-066 FULL
Solar/Wind Harmer
0.174
233930AB2-032 GEN
Solar/Wind Harmer
0.579
233915AB1-141 GEN
Solar/Wind Harmer
0.689
231918WEST 1
Adder
2.296
231917EM10
Adder
1.604
228206SHRMN CT
Adder
10.198
228732V1-021 C
Adder
0.116
945431AF1-208 GEN
Solar/Wind Harmer
5.301
970997AG2-616 GEN
Solar/Wind Harmer
5.884
228351V2-046C
Solar/Wind Harmer
1.236
230511AF1-262
Solar/Wind Harmer
0.112
228728W1-130C
Solar/Wind Harmer
0.407
230434AG1-499 GEN
Solar/Wind Harmer
0.355
213497CHSTR7-9
Adder
1.666
213497CHSTR7-9
Adder
1.666
219258KINSLEYDEP C
Solar/Wind Harmer
0.196
219904AC1-010 C
Solar/Wind Harmer
0.229
213958STHWK5-6
Adder
1.649
218660EHAMPSOLAR C
Solar/Wind Harmer
0.106
219287REEVESEAST C
Solar/Wind Harmer
0.813
219686LUMSOLAR_N C
Solar/Wind Harmer
0.122
219907AC1-030 C
Solar/Wind Harmer
0.084
213560DLW11-12
Adder
1.639
219304NAMERICA C
Solar/Wind Harmer
0.186
219222BRL12CT2
Adder
5.352
213611FALLS1-3
Adder
2.11
20720728JCB_W1-129
Solar/Wind Harmer
0.178
214194N WALES4
Adder
0.507
207522AF2-254 C
Solar/Wind Harmer
0.854
207487AE2-000G4
Solar/Wind Harmer
18.72
207445AB1-138_GEN
Solar/Wind Harmer
0.344
20628028LAKEHURS
Adder
1.117
963711AG1-223 GEN
Solar/Wind Harmer
0.877
20714828MDF_W3-079
Solar/Wind Harmer
0.181
219680HOPEWELLV C1
Solar/Wind Harmer
0.045
207454AA2-184 E
Solar/Wind Harmer
0.592
20715228NPK_W1-113
Solar/Wind Harmer
0.254
20742028HF_AC1-207
Solar/Wind Harmer
0.464
217197RE CRAN C
Solar/Wind Harmer
0.317
20635828PARLN1&2
Adder
4.374
20635028RRCT1&2
Adder
6.856
20635128RRCT3&4
Adder
6.618
218428ETC SOLAR C
Solar/Wind Harmer
0.021
217213AMBOY SO C
Solar/Wind Harmer
0.075
972275AH1-722 GEN
Adder
18.638
207528AF2-192 GEN
Solar/Wind Harmer
0.327
20673628F1S_V4-069
Solar/Wind Harmer
0.106
20675428EAM_W2-061
Solar/Wind Harmer
0.112
218449LINSOLAR C
Solar/Wind Harmer
0.594
20676428JCR_X2-075
Solar/Wind Harmer
0.202
217209CENTRL HS C
Solar/Wind Harmer
0.026
217121ECCF
Adder
0.256
217083KRNY_132
Adder
5.483
217208PARK ELE C
Solar/Wind Harmer
0.015
207439AE1-081 C O1
Solar/Wind Harmer
0.035
20674328GAR_V4-001
Solar/Wind Harmer
0.065
20675828AU_W4-064
Solar/Wind Harmer
0.102
971519AH1-257 GEN
Solar/Wind Harmer
1.491
207518AF1-320_GEN
Solar/Wind Harmer
2.161
207437AD2-070 GEN
Solar/Wind Harmer
0.178
966181AG1-487 GEN
Solar/Wind Harmer
2.22
20671928W4-073
Solar/Wind Harmer
0.256
20465127PORT CT
Adder
1.772
208909MACR G3
Adder
93.896
205941AD2-115 GEN
Solar/Wind Harmer
0.545
20467927PC_Q59Y356
Adder
0.496
20465527S.RDG CT
Adder
1.622
961301AF2-421 GEN
Solar/Wind Harmer
0.573
963151AG1-164 GEN
Solar/Wind Harmer
0.573
209023WIENIPP1
Adder
6.177
209025WIENIPP3
Adder
3.083
212266LOR1
Solar/Wind Harmer
0.073
970237AG2-161 GEN
Solar/Wind Harmer
1.961
209010PEIP 1
Adder
0.365
961341AF2-425 GEN
Solar/Wind Harmer
0.556
212174INGE
Adder
0.614
212507AE2-042_GEN
Solar/Wind Harmer
1.64
205967AE2-211_GEN
Solar/Wind Harmer
5.119
946731AF1-337 GEN
Solar/Wind Harmer
0.544
209071AE2-133 GEN
Solar/Wind Harmer
0.92
970665AG2-430 GEN
Solar/Wind Harmer
5.393
209018SUNBIPCT
Adder
4.048
209008PAXT IPP
Adder
1.169
20465027TOLNA CT
Adder
1.968
972241AH1-705 GEN
Adder
3.106
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.648
G-007ALTFEXP_G-007A->PJM
CMTX
30.282
CBM NorthLTFEXP_CBM-N->PJM
CBM
46.93
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
2.448
BlueGrassPJM->LTFIMP_BlueG
CLTF
7.636
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
79.907
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.088
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
11.758

Details for CNASTONE-BRIGHTON 500.0 kV Ckt 1 line l/o PJM_500_BG_P2_CNSTN_230-S_SRT-A


Base Case Flowgate

Area:PJM
Facility Description:
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
Contingency Name:
PJM_500_BG_P2_CNSTN_230-S_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:102.33 %
Rating:3098.0 MVA
Rating Type:B
MVA to Mitigate:3170.18
MW Contribution:4.65
Bus #Bus NameTypeMW Contribution
200200DELTA2 CT1
50/50
2.087
200193DELTA CT2
50/50
1.166
200203Y1-065-STG
50/50
4.187
200055ROCKSP 4
50/50
1.508
233971AC1-093 C
Solar/Wind Harmer
0.549
970695AG2-447 GEN
Solar/Wind Harmer
2.507
972133AH1-634 GEN
Solar/Wind Harmer
6.936
233996TM1833_GEN
Solar/Wind Harmer
0.886
233997TMININ_4.2
Solar/Wind Harmer
0.886
232406W1-004 FULL
Solar/Wind Harmer
0.701
232914OH NUG3
Adder
6.179
232916OH NUG5
Adder
6.179
972073AH1-586 GEN
Solar/Wind Harmer
6.556
200202DELTA2 ST
50/50
3.541
200195DELTA ST
50/50
1.802
200058HUNTR101
50/50
1.531
200059HUNTR201
50/50
1.531
200060HUNTR301
50/50
1.531
200052ROCKSP 1
50/50
1.525
200053ROCKSP 2
50/50
1.492
233973AC2-185 C
Solar/Wind Harmer
2.528
234033AF1-007_GEN
Solar/Wind Harmer
16.358
232904IR4
Adder
56.562
232432Z2-076 GEN
Solar/Wind Harmer
0.092
232920IR10
Adder
2.211
233923SMA
Solar/Wind Harmer
3.249
232912OH NUG1
Adder
6.179
232913OH NUG2
Adder
6.096
233990AG1-397 GEN
Solar/Wind Harmer
0.039
233955AB2-172 GEN
Solar/Wind Harmer
3.495
232813VAUGHN
Adder
0.411
233968AD2-076_GEN
Solar/Wind Harmer
4.608
970597AG2-380 GEN
Solar/Wind Harmer
2.893
231906DC3 NUG
Adder
9.718
231902DC CT7
Adder
7.769
231907DC10
Adder
2.426
232436AB1-176 C
Solar/Wind Harmer
0.159
971983AH1-536 GEN
Solar/Wind Harmer
5.189
233935AB2-179 C
Solar/Wind Harmer
1.715
231919CHRIST1
Adder
3.001
231920CHRIST2
Adder
2.935
970453AG2-297 GEN
Solar/Wind Harmer
1.688
228260V4-054C
Solar/Wind Harmer
0.626
228309CCLP NUG
Adder
15.74
228309CCLP NUG
Adder
14.972
972141AH1-641 GEN
Solar/Wind Harmer
1.751
964001AG1-254 GEN
Solar/Wind Harmer
1.237
971011AG2-627 GEN
Solar/Wind Harmer
4.654
971535AH1-265 GEN
Solar/Wind Harmer
2.584
227927V4-067C
Solar/Wind Harmer
0.12
228754AB1-001 C
Solar/Wind Harmer
0.085
219137THOSOLAR C
Solar/Wind Harmer
0.727
219272CLEANLIGHT C
Solar/Wind Harmer
0.109
219688LUMSOLAR_S C
Solar/Wind Harmer
0.121
219914AD2-027 C
Solar/Wind Harmer
0.359
213942SCHUYLKILL
Adder
2.124
213942SCHUYLKILL
Adder
1.625
213957STHWK3-4
Adder
1.624
213957STHWK3-4
Adder
1.624
213561DLWR9-10
Adder
2.112
213561DLWR9-10
Adder
1.615
219607WPEMNERT C
Solar/Wind Harmer
0.248
219224BRL12CT4
Adder
5.279
214067T20SOLAR
Solar/Wind Harmer
0.149
213611FALLS1-3
Adder
2.079
213611FALLS1-3
Adder
2.079
20717128DIX_Z2-102
Solar/Wind Harmer
0.774
20715728PEM_W1-119
Solar/Wind Harmer
0.313
20715828PEM_W1-120
Solar/Wind Harmer
0.313
970025AG2-016 GEN
Solar/Wind Harmer
1.659
971189AH1-054 GEN
Solar/Wind Harmer
0.691
207459AE1-142 C O1
Solar/Wind Harmer
0.617
219620RIDERU C
Solar/Wind Harmer
0.032
20714328BYD_X4-031
Solar/Wind Harmer
0.164
20714428HOW_X1-037
Solar/Wind Harmer
0.719
971521AH1-258 GEN
Solar/Wind Harmer
1.572
20720428HOL_W1-112
Solar/Wind Harmer
0.201
20635928PARLN3&4
Adder
4.289
218455CINNBAY_CGEN
Adder
1.052
218526CNTRALGAS2 C
Solar/Wind Harmer
0.214
218524CNTRALGAS1 C
Solar/Wind Harmer
0.214
20675528CPH_W2-050
Solar/Wind Harmer
0.27
218404KENILWRTH C
Adder
0.753
217167KRNY_14
Adder
5.358
217086KRNY_131
Adder
5.312
217147KRNY_1212
Adder
5.096
217147KRNY_1212
Adder
5.005
217146KRNY_1234
Adder
4.994
217146KRNY_1234
Adder
4.96
966261AG1-495 GEN
Solar/Wind Harmer
1.032
20676328BVR_Y1-020
Solar/Wind Harmer
0.19
207511W3-106 GEN
Solar/Wind Harmer
0.377
207530AG1-191 GEN
Solar/Wind Harmer
0.79
20674828DL_W4-046
Solar/Wind Harmer
0.37
971009AG2-626 GEN
Solar/Wind Harmer
0.939
207408W3-077 C
Solar/Wind Harmer
0.29
20675728RH_W2-091
Solar/Wind Harmer
0.196
20675928HOL_W4-097
Solar/Wind Harmer
0.075
207484AF2-139 C O1
Solar/Wind Harmer
0.29
966421AG1-511 GEN
Solar/Wind Harmer
4.923
20675128HRM_W1-127
Solar/Wind Harmer
0.097
20462827N BANGR8
Adder
0.409
209116AE2-175 GEN
Solar/Wind Harmer
2.335
961261AF2-417 GEN
Solar/Wind Harmer
0.557
209026WIENIPP4
Adder
2.948
209045AE2-271 GEN
Solar/Wind Harmer
8.938
20486527WR_V4-052
Adder
0.576
959431AF2-234 GEN
Solar/Wind Harmer
1.046
964051AG1-259 GEN
Solar/Wind Harmer
0.701
964061AG1-260 GEN
Solar/Wind Harmer
0.701
959421AF2-233 GEN
Solar/Wind Harmer
0.523
972281AH1-725 GEN
50/50
124.123
200201DELTA2 CT2
50/50
2.087
200034PCHBTM 2
50/50
12.15
200061HUNTR401
50/50
2.916
200035PCHBTM 3
50/50
12.059
200205Y1-065-CTG2
50/50
2.415
233987AB2-037 GEN
Solar/Wind Harmer
7.969
971149AH1-027 GEN
Solar/Wind Harmer
2.369
233939AC1-091 C
Solar/Wind Harmer
0.615
233970AC1-092 C
Solar/Wind Harmer
0.615
970545AG2-347 GEN
Solar/Wind Harmer
45.777
233901CHERRYDALE C
Solar/Wind Harmer
0.788
232408W1-005 C
Solar/Wind Harmer
0.701
232410W1-006 C
Solar/Wind Harmer
0.701
972069AH1-584 GEN
Solar/Wind Harmer
6.265
972071AH1-585 GEN
Solar/Wind Harmer
6.265
232918OH NUG7
Adder
6.137
971747AH1-380 GEN
Solar/Wind Harmer
2.506
232905CHERITON_25
Adder
1.716
232926CRISFLD1
Adder
1.373
231940T-011
Adder
0.522
232899W1-062
Adder
6.725
233946AB2-136 GEN
Solar/Wind Harmer
2.79
234036AF2-325 C
Solar/Wind Harmer
0.641
234041AC1-190 GEN
Solar/Wind Harmer
6.259
233984AB2-036 GEN
Solar/Wind Harmer
8.671
232424Y1-079 C
Solar/Wind Harmer
0.392
234014AF1-036_GEN
Solar/Wind Harmer
1.881
231131BLOOM ENRGY
Adder
3.025
233944AB2-135 GEN
Solar/Wind Harmer
3.634
233933AB2-153 GEN
Solar/Wind Harmer
0.78
232416X2-083
Adder
0.31
228251CARLLS#4
Adder
0.384
230422AE1-104_GEN1
Solar/Wind Harmer
20.499
230425AE1-104_GEN2
Solar/Wind Harmer
20.499
230433AD2-135 GEN
Solar/Wind Harmer
0.061
228307PCLP GT
Adder
7.335
230407AD2-065 C
Solar/Wind Harmer
0.08
228304LOGAN
Adder
14.657
972233AH1-701 GEN
Adder
2.538
213589EDDYSTN4
Adder
47.935
213587EDDYSTN3
Adder
47.93
219921AF1-264
Solar/Wind Harmer
0.087
219615MILLCREEK C
Solar/Wind Harmer
0.141
213535CROYDN11
Adder
6.047
213815MOSER1-3
Adder
2.093
213815MOSER1-3
Adder
2.093
20716428NHV_W2-082
Solar/Wind Harmer
1.043
207500AE2-000G1
Solar/Wind Harmer
18.455
200192DELTA CT1
50/50
1.166
200194DELTA CT3
50/50
1.166
200204Y1-065-CTG1
50/50
2.415
200054ROCKSP 3
50/50
1.54
232901NORTHST
Adder
5.825
233972AC1-094 C
Solar/Wind Harmer
0.464
232434Z2-077 GEN
Solar/Wind Harmer
0.175
233998TM1NIN_3.36
Solar/Wind Harmer
0.886
232404W1-003 C
Solar/Wind Harmer
0.701
232917OH NUG6
Adder
6.151
232915OH NUG4
Adder
6.137
207497AE2-000G2
Solar/Wind Harmer
18.455
207507AE2-000G3
Solar/Wind Harmer
18.455
20636128O CRK C2
Adder
3.776
963401AG1-189 GEN
Solar/Wind Harmer
0.673
963391AG1-188 GEN
Solar/Wind Harmer
1.123
20714928UPF_X1-085
Solar/Wind Harmer
0.238
219114HARTZY_C
Solar/Wind Harmer
0.488
20628028LAKEHURS
Adder
0.556
219817TRENTONSOL C
Solar/Wind Harmer
0.641
20641628MLH_W1-032
Solar/Wind Harmer
0.171
20720628TIN_W1-124
Solar/Wind Harmer
0.579
20716928W4-060COL
Solar/Wind Harmer
0.413
924131AB2-057 GEN
Solar/Wind Harmer
0.596
218440SUMMTASSOC C
Solar/Wind Harmer
0.074
218418LINDEN_G5
Adder
9.925
218419LINDEN_G6
Adder
9.925
972260AH1-715 GEN1
Adder
7.948
20673828FLE_V3-070
Solar/Wind Harmer
0.265
207442AE1-156 GEN
Solar/Wind Harmer
0.43
20676128MHD_W3-029
Solar/Wind Harmer
0.276
219036LINDEN_G7
Adder
9.657
219035LINDEN_G8
Adder
9.519
972261AH1-715 GEN2
Adder
9.244
217081WEATEXAS C
Solar/Wind Harmer
0.05
217202FBANKSOLAR C
Solar/Wind Harmer
0.042
217201HACKENSOLA C
Solar/Wind Harmer
0.042
972237AH1-703 GEN
Adder
5.832
217206BARNGR HS C
Solar/Wind Harmer
0.018
217086KRNY_131
Adder
5.369
217083KRNY_132
Adder
5.324
20671828STAW2-080
Solar/Wind Harmer
0.06
217204WCALDSOLAR C
Solar/Wind Harmer
0.042
20674528F3S_W2-016
Solar/Wind Harmer
0.811
20676228FRD_X1-012
Solar/Wind Harmer
0.34
207471AF2-354 C
Solar/Wind Harmer
0.293
20674928WA_W3-044
Solar/Wind Harmer
0.276
964851AG1-348 GEN
Solar/Wind Harmer
1.007
20634528N27_Y2-018
Solar/Wind Harmer
0.154
20465127PORT CT
Adder
2.278
20674128FR_U2-059
Solar/Wind Harmer
0.105
966111AG1-480 GEN
Solar/Wind Harmer
0.049
966111AG1-480 GEN
Solar/Wind Harmer
1.88
211065PSPA IPP
Solar/Wind Harmer
0.255
211065PSPA IPP
Solar/Wind Harmer
0.255
208972BECR K09
Solar/Wind Harmer
0.58
209029WAYMART-WD
Solar/Wind Harmer
1.579
209009PEIP 2
Adder
4.286
209010PEIP 1
Adder
1.942
209010PEIP 1
Adder
0.284
961541AF2-445A GEN
Solar/Wind Harmer
1.768
961431AF2-434 GEN
Solar/Wind Harmer
0.534
20465527S.RDG CT
Adder
1.428
209054AE2-059 GEN
Solar/Wind Harmer
0.892
209059AE2-084 GEN
Solar/Wind Harmer
1.316
946751AF1-339 GEN
Solar/Wind Harmer
0.524
209130AF1-271A GEN
Solar/Wind Harmer
1.47
226929AD2-058 GEN
Solar/Wind Helper
0.103
232428Y3-058 C
Solar/Wind Harmer
0.584
972177AH1-672 GEN
Solar/Wind Harmer
9.396
971195AH1-057 GEN
Solar/Wind Harmer
0.766
232900DEMECSMY
Adder
6.451
232919VN10
Adder
1.963
965821AG1-450 GEN
Solar/Wind Harmer
3.64
232426Y1-080 FULL
Solar/Wind Harmer
0.134
970277AG2-181 GEN
Solar/Wind Harmer
3.506
233964AF2-378 GEN
Solar/Wind Harmer
0.089
233954AC2-188 GEN
Solar/Wind Harmer
0.787
233950AC2-186 GEN
Solar/Wind Harmer
0.393
232910NRG_G1
Adder
6.019
234012AE2-112_GEN
Solar/Wind Harmer
1.599
232422X3-066 FULL
Solar/Wind Harmer
0.174
233930AB2-032 GEN
Solar/Wind Harmer
0.578
233915AB1-141 GEN
Solar/Wind Harmer
0.687
231918WEST 1
Adder
2.282
231917EM10
Adder
1.594
228206SHRMN CT
Adder
10.124
228732V1-021 C
Adder
0.115
945431AF1-208 GEN
Solar/Wind Harmer
5.259
970997AG2-616 GEN
Solar/Wind Harmer
5.836
228351V2-046C
Solar/Wind Harmer
1.225
230511AF1-262
Solar/Wind Harmer
0.111
228728W1-130C
Solar/Wind Harmer
0.403
230434AG1-499 GEN
Solar/Wind Harmer
0.352
213497CHSTR7-9
Adder
1.642
213497CHSTR7-9
Adder
1.642
219258KINSLEYDEP C
Solar/Wind Harmer
0.194
219904AC1-010 C
Solar/Wind Harmer
0.226
218660EHAMPSOLAR C
Solar/Wind Harmer
0.104
219287REEVESEAST C
Solar/Wind Harmer
0.803
219686LUMSOLAR_N C
Solar/Wind Harmer
0.121
213958STHWK5-6
Adder
1.624
219907AC1-030 C
Solar/Wind Harmer
0.083
213560DLW11-12
Adder
1.615
219304NAMERICA C
Solar/Wind Harmer
0.184
219222BRL12CT2
Adder
5.279
213611FALLS1-3
Adder
2.079
20720728JCB_W1-129
Solar/Wind Harmer
0.175
207522AF2-254 C
Solar/Wind Harmer
0.842
207487AE2-000G4
Solar/Wind Harmer
18.455
214194N WALES4
Adder
0.499
207445AB1-138_GEN
Solar/Wind Harmer
0.339
20628028LAKEHURS
Adder
1.1
963711AG1-223 GEN
Solar/Wind Harmer
0.863
20714828MDF_W3-079
Solar/Wind Harmer
0.179
219680HOPEWELLV C1
Solar/Wind Harmer
0.044
207454AA2-184 E
Solar/Wind Harmer
0.581
20715228NPK_W1-113
Solar/Wind Harmer
0.25
20742028HF_AC1-207
Solar/Wind Harmer
0.456
217197RE CRAN C
Solar/Wind Harmer
0.312
20635828PARLN1&2
Adder
4.289
20635028RRCT1&2
Adder
6.721
20635128RRCT3&4
Adder
6.488
218428ETC SOLAR C
Solar/Wind Harmer
0.021
217213AMBOY SO C
Solar/Wind Harmer
0.073
972275AH1-722 GEN
Adder
18.246
207528AF2-192 GEN
Solar/Wind Harmer
0.32
20673628F1S_V4-069
Solar/Wind Harmer
0.104
20675428EAM_W2-061
Solar/Wind Harmer
0.109
218449LINSOLAR C
Solar/Wind Harmer
0.581
20676428JCR_X2-075
Solar/Wind Harmer
0.197
217209CENTRL HS C
Solar/Wind Harmer
0.026
217121ECCF
Adder
0.25
217083KRNY_132
Adder
5.358
217208PARK ELE C
Solar/Wind Harmer
0.015
207439AE1-081 C O1
Solar/Wind Harmer
0.034
20674328GAR_V4-001
Solar/Wind Harmer
0.063
20675828AU_W4-064
Solar/Wind Harmer
0.099
971519AH1-257 GEN
Solar/Wind Harmer
1.445
207518AF1-320_GEN
Solar/Wind Harmer
2.093
207437AD2-070 GEN
Solar/Wind Harmer
0.173
20465127PORT CT
Adder
1.717
20671928W4-073
Solar/Wind Harmer
0.248
966181AG1-487 GEN
Solar/Wind Harmer
2.143
208909MACR G3
Adder
90.872
961301AF2-421 GEN
Solar/Wind Harmer
0.553
963151AG1-164 GEN
Solar/Wind Harmer
0.553
209023WIENIPP1
Adder
5.967
209025WIENIPP3
Adder
2.978
205941AD2-115 GEN
Solar/Wind Harmer
0.503
209010PEIP 1
Adder
0.353
212266LOR1
Solar/Wind Harmer
0.071
970237AG2-161 GEN
Solar/Wind Harmer
1.89
961341AF2-425 GEN
Solar/Wind Harmer
0.536
212174INGE
Adder
0.592
20467927PC_Q59Y356
Adder
0.453
20465527S.RDG CT
Adder
1.476
212507AE2-042_GEN
Solar/Wind Harmer
1.579
946731AF1-337 GEN
Solar/Wind Harmer
0.524
209071AE2-133 GEN
Solar/Wind Harmer
0.886
970665AG2-430 GEN
Solar/Wind Harmer
5.19
209018SUNBIPCT
Adder
3.896
232921TASLEY2G
Adder
3.611
233940AF2-379 C
Solar/Wind Harmer
0.131
232907VN8
Adder
21.006
233990AG1-397 GEN
Solar/Wind Harmer
0.802
233900O-025 C
Adder
0.824
234015AF2-250 C
Solar/Wind Harmer
0.084
233994AC2-023 GEN
Solar/Wind Harmer
1.88
960671AF2-358 GEN
Solar/Wind Harmer
12.523
232417X3-008 C
Solar/Wind Harmer
1.398
233952AC2-187 GEN
Solar/Wind Harmer
0.787
233918AB1-142 GEN
Solar/Wind Harmer
0.687
233982AB2-133 GEN
Solar/Wind Harmer
3.377
972251AH1-710 GEN
Adder
30.805
228202CUMB CT
Adder
10.095
228711V2-041C
Solar/Wind Harmer
0.367
971553AH1-274 GEN
Solar/Wind Harmer
1.478
230430AE1-229_GEN
Solar/Wind Harmer
5.354
230415AB2-049 C
Solar/Wind Harmer
0.115
228729W2-030 C
Solar/Wind Harmer
0.35
228304LOGAN
Adder
13.182
213497CHSTR7-9
Adder
1.642
219623KINSLEYBEA C
Solar/Wind Harmer
0.256
219291REEVESSOUT C
Solar/Wind Harmer
0.036
219766PARADISE C
Solar/Wind Harmer
0.188
219912AD2-042 GEN
Solar/Wind Harmer
0.475
213958STHWK5-6
Adder
1.624
219236SOUTHERNHQ C
Solar/Wind Harmer
0.04
213560DLW11-12
Adder
1.615
219906AC1-017 C
Solar/Wind Harmer
0.132
219610FLORENCE C
Solar/Wind Harmer
0.819
219348LDSOLAR C
Solar/Wind Harmer
0.354
219221BRL12CT1
Adder
5.279
219223BRL12CT3
Adder
5.279
213815MOSER1-3
Adder
2.093
959561AF2-247 GEN
Solar/Wind Harmer
0.285
20716028EGP_W2-019
Solar/Wind Harmer
0.272
20720828JCB_W4-025
Solar/Wind Harmer
0.266
20715028HAN_X4-015
Solar/Wind Harmer
0.175
20636028O CRK C1
Adder
4.141
971667AH1-334 GEN
Solar/Wind Harmer
1.607
219727YARDVSOLFA C
Solar/Wind Harmer
0.532
20714528FRN_Y2-051
Solar/Wind Harmer
0.172
219276PARKLANDSO C
Solar/Wind Harmer
0.269
219918AC2-009 C
Solar/Wind Harmer
0.036
20716228APLW2-078
Solar/Wind Harmer
0.514
20720528MAN_W1-024
Solar/Wind Harmer
0.148
967451AG2-055 C O1
Solar/Wind Harmer
100.792
219612MATRIX C
Solar/Wind Harmer
0.107
218438BLK ROCK C
Solar/Wind Harmer
0.079
20635828PARLN1&2
Adder
1.943
20635928PARLN3&4
Adder
1.943
20635028RRCT1&2
Adder
6.826
20635128RRCT3&4
Adder
5.66
219908AB1-139 C
Solar/Wind Harmer
0.22
219919AE1-041 FULL
Solar/Wind Harmer
0.023
219249CENTRALDIV C
Solar/Wind Harmer
0.023
20673728F2S_V4-070
Solar/Wind Harmer
0.104
217211CAMDEN ST C
Solar/Wind Harmer
0.014
217186ESSEX_G9
Adder
9.215
217169METRODIV C
Solar/Wind Harmer
0.023
217194REDH C
Solar/Wind Harmer
0.284
20676728BRNX1-095
Solar/Wind Harmer
0.101
207510AF2-138 C
Solar/Wind Harmer
1.022
20674628WNG_W3-110
Solar/Wind Harmer
0.232
971007AG2-625 GEN
Solar/Wind Harmer
1.472
20466127PORT 5CT
Adder
15.152
20633028GILCT9
Adder
16.198
966181AG1-487 GEN
Solar/Wind Harmer
0.144
20465427SHAW CT
Adder
2.204
963161AG1-165 GEN
Solar/Wind Harmer
0.553
209025WIENIPP3
Adder
2.918
963071AG1-156 GEN
Solar/Wind Harmer
1.521
970095AG2-074 GEN
Solar/Wind Harmer
3.452
209027LOR2_Q27
Solar/Wind Harmer
2.461
209022WHFR IPP
Adder
1.767
961331AF2-424 GEN
Solar/Wind Harmer
0.536
961421AF2-433 GEN
Solar/Wind Harmer
0.534
957921AF2-086 GEN
Solar/Wind Harmer
0.52
209142AF1-226 GEN
Solar/Wind Harmer
3.093
209093AE2-110 GEN
Solar/Wind Harmer
1.336
209120AE2-241 GEN
Solar/Wind Harmer
1.768
972245AH1-707 GEN
Adder
2.882
946691AF1-333 GEN
Solar/Wind Harmer
0.524
946741AF1-338 GEN
Solar/Wind Harmer
0.524
227287AC2-120 GEN
Solar/Wind Helper
0.367
226910AB2-157 C
Solar/Wind Helper
0.015
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.542
G-007ALTFEXP_G-007A->PJM
CMTX
29.687
CBM NorthLTFEXP_CBM-N->PJM
CBM
45.732
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
2.366
BlueGrassPJM->LTFIMP_BlueG
CLTF
7.382
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
78.116
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.026
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
11.373

Details for COOPER-GRACETON 230.0 kV Ckt 1 line l/o PECO_P4_PEACH235_SRT-A/* $ CHESCO $ PECO_P4_PEACH235 $ STBK


Base Case Flowgate

Area:BGE/PECO
Facility Description:
COOPER-GRACETON 230.0 kV Ckt 1 line
Contingency Name:
PECO_P4_PEACH235_SRT-A/* $ CHESCO $ PECO_P4_PEACH235 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:129.17 %
Rating:578.0 MVA
Rating Type:B
MVA to Mitigate:746.61
MW Contribution:2.32
Bus #Bus NameTypeMW Contribution
213515CONOW3-4
50/50
0.746
213515CONOW3-4
50/50
0.746
213514CONOW1-2
50/50
0.56
213516CONOW5-6
50/50
0.56
233935AB2-179 C
Solar/Wind Harmer
1.162
231919CHRIST1
Adder
1.883
231920CHRIST2
Adder
1.841
971983AH1-536 GEN
Solar/Wind Harmer
3.074
232436AB1-176 C
Solar/Wind Harmer
0.092
233968AD2-076_GEN
Solar/Wind Harmer
2.659
970597AG2-380 GEN
Solar/Wind Harmer
1.67
231906DC3 NUG
Adder
5.53
231902DC CT7
Adder
4.421
231907DC10
Adder
1.381
213942SCHUYLKILL
Adder
1.305
213942SCHUYLKILL
Adder
0.998
213957STHWK3-4
Adder
0.99
213957STHWK3-4
Adder
0.99
232813VAUGHN
Adder
0.219
233955AB2-172 GEN
Solar/Wind Harmer
1.851
233923SMA
Solar/Wind Harmer
1.683
232912OH NUG1
Adder
3.197
232913OH NUG2
Adder
3.155
213508CON10-11
50/50
1.01
213518CONOW8-9
50/50
1.01
213517CONOW7
50/50
0.746
213497CHSTR7-9
Adder
1.074
233982AB2-133 GEN
Solar/Wind Harmer
2.008
233918AB1-142 GEN
Solar/Wind Harmer
0.408
213958STHWK5-6
Adder
0.99
232417X3-008 C
Solar/Wind Harmer
0.741
960671AF2-358 GEN
Solar/Wind Harmer
6.572
232907VN8
Adder
10.969
233952AC2-187 GEN
Solar/Wind Harmer
0.41
233994AC2-023 GEN
Solar/Wind Harmer
0.978
233940AF2-379 C
Solar/Wind Harmer
0.068
233900O-025 C
Adder
0.427
234015AF2-250 C
Solar/Wind Harmer
0.044
233996TM1833_GEN
Solar/Wind Harmer
0.459
233997TMININ_4.2
Solar/Wind Harmer
0.459
232406W1-004 FULL
Solar/Wind Harmer
0.363
232921TASLEY2G
Adder
1.869
232914OH NUG3
Adder
3.197
232916OH NUG5
Adder
3.197
233990AG1-397 GEN
Solar/Wind Harmer
0.415
972073AH1-586 GEN
Solar/Wind Harmer
3.39
972133AH1-634 GEN
Solar/Wind Harmer
3.56
213560DLW11-12
Adder
0.911
233971AC1-093 C
Solar/Wind Harmer
0.271
970695AG2-447 GEN
Solar/Wind Harmer
1.24
213815MOSER1-3
Adder
1.097
228304LOGAN
Adder
6.686
219766PARADISE C
Solar/Wind Harmer
0.097
219912AD2-042 GEN
Solar/Wind Harmer
0.244
219623KINSLEYBEA C
Solar/Wind Harmer
0.13
219236SOUTHERNHQ C
Solar/Wind Harmer
0.02
230430AE1-229_GEN
Solar/Wind Harmer
2.622
219906AC1-017 C
Solar/Wind Harmer
0.066
230415AB2-049 C
Solar/Wind Harmer
0.056
971553AH1-274 GEN
Solar/Wind Harmer
0.709
228711V2-041C
Solar/Wind Harmer
0.175
228202CUMB CT
Adder
4.801
219610FLORENCE C
Solar/Wind Harmer
0.405
219348LDSOLAR C
Solar/Wind Harmer
0.175
219221BRL12CT1
Adder
2.608
219223BRL12CT3
Adder
2.608
219291REEVESSOUT C
Solar/Wind Harmer
0.017
972251AH1-710 GEN
Adder
13.816
228729W2-030 C
Solar/Wind Harmer
0.165
959561AF2-247 GEN
Solar/Wind Harmer
0.137
20716028EGP_W2-019
Solar/Wind Harmer
0.124
20720828JCB_W4-025
Solar/Wind Harmer
0.121
219727YARDVSOLFA C
Solar/Wind Harmer
0.246
20715028HAN_X4-015
Solar/Wind Harmer
0.08
20636028O CRK C1
Adder
1.854
219276PARKLANDSO C
Solar/Wind Harmer
0.122
971667AH1-334 GEN
Solar/Wind Harmer
0.715
20714528FRN_Y2-051
Solar/Wind Harmer
0.076
219918AC2-009 C
Solar/Wind Harmer
0.016
20716228APLW2-078
Solar/Wind Harmer
0.222
20720528MAN_W1-024
Solar/Wind Harmer
0.064
219612MATRIX C
Solar/Wind Harmer
0.046
218438BLK ROCK C
Solar/Wind Harmer
0.034
967451AG2-055 C O1
Solar/Wind Harmer
42.608
20635828PARLN1&2
Adder
0.818
20635928PARLN3&4
Adder
0.818
20635028RRCT1&2
Adder
2.861
20635128RRCT3&4
Adder
2.372
219908AB1-139 C
Solar/Wind Harmer
0.092
219919AE1-041 FULL
Solar/Wind Harmer
0.01
219249CENTRALDIV C
Solar/Wind Harmer
0.009
20673728F2S_V4-070
Solar/Wind Harmer
0.043
223402AF1-300 C
Solar/Wind Helper
0.271
233990AG1-397 GEN
Solar/Wind Harmer
0.02
232432Z2-076 GEN
Solar/Wind Harmer
0.048
232920IR10
Adder
1.136
234033AF1-007_GEN
Solar/Wind Harmer
8.396
232904IR4
Adder
29.029
213561DLWR9-10
Adder
1.192
213561DLWR9-10
Adder
0.911
233973AC2-185 C
Solar/Wind Harmer
1.25
219137THOSOLAR C
Solar/Wind Harmer
0.376
219914AD2-027 C
Solar/Wind Harmer
0.184
971011AG2-627 GEN
Solar/Wind Harmer
2.318
228309CCLP NUG
Adder
7.781
228309CCLP NUG
Adder
7.401
964001AG1-254 GEN
Solar/Wind Harmer
0.611
972141AH1-641 GEN
Solar/Wind Harmer
0.858
228260V4-054C
Solar/Wind Harmer
0.303
971535AH1-265 GEN
Solar/Wind Harmer
1.252
219272CLEANLIGHT C
Solar/Wind Harmer
0.053
970453AG2-297 GEN
Solar/Wind Harmer
0.801
219607WPEMNERT C
Solar/Wind Harmer
0.122
219224BRL12CT4
Adder
2.608
219688LUMSOLAR_S C
Solar/Wind Harmer
0.059
228754AB1-001 C
Solar/Wind Harmer
0.04
227927V4-067C
Solar/Wind Harmer
0.057
214067T20SOLAR
Solar/Wind Harmer
0.073
213611FALLS1-3
Adder
1.015
213611FALLS1-3
Adder
1.015
20717128DIX_Z2-102
Solar/Wind Harmer
0.353
20715728PEM_W1-119
Solar/Wind Harmer
0.142
20715828PEM_W1-120
Solar/Wind Harmer
0.142
971189AH1-054 GEN
Solar/Wind Harmer
0.31
970025AG2-016 GEN
Solar/Wind Harmer
0.741
207459AE1-142 C O1
Solar/Wind Harmer
0.274
219620RIDERU C
Solar/Wind Harmer
0.014
20714328BYD_X4-031
Solar/Wind Harmer
0.071
20714428HOW_X1-037
Solar/Wind Harmer
0.312
971521AH1-258 GEN
Solar/Wind Harmer
0.675
20720428HOL_W1-112
Solar/Wind Harmer
0.086
218455CINNBAY_CGEN
Adder
0.446
20635928PARLN3&4
Adder
1.806
20675528CPH_W2-050
Solar/Wind Harmer
0.114
218526CNTRALGAS2 C
Solar/Wind Harmer
0.09
218524CNTRALGAS1 C
Solar/Wind Harmer
0.089
213508CON10-11
50/50
1.01
213518CONOW8-9
50/50
1.01
213514CONOW1-2
50/50
0.746
213516CONOW5-6
50/50
0.746
231918WEST 1
Adder
1.445
231917EM10
Adder
1.009
213497CHSTR7-9
Adder
1.074
213497CHSTR7-9
Adder
1.074
233930AB2-032 GEN
Solar/Wind Harmer
0.343
233915AB1-141 GEN
Solar/Wind Harmer
0.408
232422X3-066 FULL
Solar/Wind Harmer
0.101
234012AE2-112_GEN
Solar/Wind Harmer
0.922
213958STHWK5-6
Adder
0.99
232910NRG_G1
Adder
3.245
233964AF2-378 GEN
Solar/Wind Harmer
0.047
232426Y1-080 FULL
Solar/Wind Harmer
0.07
970277AG2-181 GEN
Solar/Wind Harmer
1.842
965821AG1-450 GEN
Solar/Wind Harmer
1.91
232919VN10
Adder
1.027
233954AC2-188 GEN
Solar/Wind Harmer
0.41
233950AC2-186 GEN
Solar/Wind Harmer
0.205
232428Y3-058 C
Solar/Wind Harmer
0.303
971195AH1-057 GEN
Solar/Wind Harmer
0.397
233998TM1NIN_3.36
Solar/Wind Harmer
0.459
232404W1-003 C
Solar/Wind Harmer
0.363
232917OH NUG6
Adder
3.183
232915OH NUG4
Adder
3.176
232434Z2-077 GEN
Solar/Wind Harmer
0.09
972177AH1-672 GEN
Solar/Wind Harmer
4.816
213560DLW11-12
Adder
0.911
232900DEMECSMY
Adder
3.257
232901NORTHST
Adder
2.902
233972AC1-094 C
Solar/Wind Harmer
0.23
213589EDDYSTN4
Adder
31.443
213587EDDYSTN3
Adder
31.416
232416X2-083
Adder
0.19
233933AB2-153 GEN
Solar/Wind Harmer
0.463
233944AB2-135 GEN
Solar/Wind Harmer
2.123
234014AF1-036_GEN
Solar/Wind Harmer
1.085
231131BLOOM ENRGY
Adder
1.716
232424Y1-079 C
Solar/Wind Harmer
0.221
233984AB2-036 GEN
Solar/Wind Harmer
4.867
234041AC1-190 GEN
Solar/Wind Harmer
3.312
233987AB2-037 GEN
Solar/Wind Harmer
4.198
234036AF2-325 C
Solar/Wind Harmer
0.338
233946AB2-136 GEN
Solar/Wind Harmer
1.47
232926CRISFLD1
Adder
0.711
233901CHERRYDALE C
Solar/Wind Harmer
0.408
232408W1-005 C
Solar/Wind Harmer
0.363
232410W1-006 C
Solar/Wind Harmer
0.363
232905CHERITON_25
Adder
0.888
232918OH NUG7
Adder
3.176
971747AH1-380 GEN
Solar/Wind Harmer
1.296
972069AH1-584 GEN
Solar/Wind Harmer
3.239
972071AH1-585 GEN
Solar/Wind Harmer
3.239
231940T-011
Adder
0.27
970545AG2-347 GEN
Solar/Wind Harmer
23.494
232899W1-062
Adder
3.396
971149AH1-027 GEN
Solar/Wind Harmer
1.18
233939AC1-091 C
Solar/Wind Harmer
0.304
233970AC1-092 C
Solar/Wind Harmer
0.304
972233AH1-701 GEN
Adder
1.291
213815MOSER1-3
Adder
1.097
213815MOSER1-3
Adder
1.097
228304LOGAN
Adder
7.434
228307PCLP GT
Adder
3.696
219921AF1-264
Solar/Wind Harmer
0.044
228251CARLLS#4
Adder
0.186
219615MILLCREEK C
Solar/Wind Harmer
0.071
230433AD2-135 GEN
Solar/Wind Harmer
0.03
230407AD2-065 C
Solar/Wind Harmer
0.039
213535CROYDN11
Adder
3.003
230422AE1-104_GEN1
Solar/Wind Harmer
9.703
230425AE1-104_GEN2
Solar/Wind Harmer
9.703
219114HARTZY_C
Solar/Wind Harmer
0.227
20716428NHV_W2-082
Solar/Wind Harmer
0.476
207500AE2-000G1
Solar/Wind Harmer
8.264
207497AE2-000G2
Solar/Wind Harmer
8.264
207507AE2-000G3
Solar/Wind Harmer
8.264
20636128O CRK C2
Adder
1.691
20714928UPF_X1-085
Solar/Wind Harmer
0.107
963401AG1-189 GEN
Solar/Wind Harmer
0.301
963391AG1-188 GEN
Solar/Wind Harmer
0.501
20628028LAKEHURS
Adder
0.247
219817TRENTONSOL C
Solar/Wind Harmer
0.285
20720628TIN_W1-124
Solar/Wind Harmer
0.25
20641628MLH_W1-032
Solar/Wind Harmer
0.073
20716928W4-060COL
Solar/Wind Harmer
0.175
924131AB2-057 GEN
Solar/Wind Harmer
0.252
218440SUMMTASSOC C
Solar/Wind Harmer
0.031
20673828FLE_V3-070
Solar/Wind Harmer
0.11
218418LINDEN_G5
Adder
4.093
218419LINDEN_G6
Adder
4.093
972260AH1-715 GEN1
Adder
3.278
207442AE1-156 GEN
Solar/Wind Harmer
0.177
20676128MHD_W3-029
Solar/Wind Harmer
0.114
219258KINSLEYDEP C
Solar/Wind Harmer
0.1
219904AC1-010 C
Solar/Wind Harmer
0.116
219907AC1-030 C
Solar/Wind Harmer
0.042
228351V2-046C
Solar/Wind Harmer
0.605
230434AG1-499 GEN
Solar/Wind Harmer
0.174
970997AG2-616 GEN
Solar/Wind Harmer
2.861
945431AF1-208 GEN
Solar/Wind Harmer
2.564
230511AF1-262
Solar/Wind Harmer
0.054
228728W1-130C
Solar/Wind Harmer
0.195
228206SHRMN CT
Adder
4.832
219304NAMERICA C
Solar/Wind Harmer
0.091
219222BRL12CT2
Adder
2.608
228732V1-021 C
Adder
0.055
218660EHAMPSOLAR C
Solar/Wind Harmer
0.051
219686LUMSOLAR_N C
Solar/Wind Harmer
0.058
219287REEVESEAST C
Solar/Wind Harmer
0.388
214194N WALES4
Adder
0.245
213611FALLS1-3
Adder
1.015
20720728JCB_W1-129
Solar/Wind Harmer
0.08
207522AF2-254 C
Solar/Wind Harmer
0.384
207487AE2-000G4
Solar/Wind Harmer
8.264
207445AB1-138_GEN
Solar/Wind Harmer
0.151
20628028LAKEHURS
Adder
0.489
963711AG1-223 GEN
Solar/Wind Harmer
0.379
20714828MDF_W3-079
Solar/Wind Harmer
0.078
219680HOPEWELLV C1
Solar/Wind Harmer
0.02
207454AA2-184 E
Solar/Wind Harmer
0.251
20715228NPK_W1-113
Solar/Wind Harmer
0.108
217197RE CRAN C
Solar/Wind Harmer
0.135
20742028HF_AC1-207
Solar/Wind Harmer
0.196
20635828PARLN1&2
Adder
1.806
20635028RRCT1&2
Adder
2.817
20635128RRCT3&4
Adder
2.719
218428ETC SOLAR C
Solar/Wind Harmer
0.009
217213AMBOY SO C
Solar/Wind Harmer
0.03
972275AH1-722 GEN
Adder
7.525
207528AF2-192 GEN
Solar/Wind Harmer
0.132
20673628F1S_V4-069
Solar/Wind Harmer
0.043
20675428EAM_W2-061
Solar/Wind Harmer
0.045
208909MACR G3
Adder
32.156
223401AF1-299 GEN
Solar/Wind Helper
0.271
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.035
G-007ALTFEXP_G-007A->PJM
CMTX
12.44
CBM NorthLTFEXP_CBM-N->PJM
CBM
16.037
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.84
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.618
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
31.566
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.609
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
3.959

Details for COOPER-GRACETON 230.0 kV Ckt 1 line l/o PJM_500_BG_P4_5_CNSTN_C_SRT-A


Base Case Flowgate

Area:BGE/PECO
Facility Description:
COOPER-GRACETON 230.0 kV Ckt 1 line
Contingency Name:
PJM_500_BG_P4_5_CNSTN_C_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:129.14 %
Rating:578.0 MVA
Rating Type:B
MVA to Mitigate:746.45
MW Contribution:2.32
Bus #Bus NameTypeMW Contribution
213508CON10-11
50/50
1.01
213518CONOW8-9
50/50
1.01
213517CONOW7
50/50
0.746
213497CHSTR7-9
Adder
1.074
233982AB2-133 GEN
Solar/Wind Harmer
2.007
233918AB1-142 GEN
Solar/Wind Harmer
0.407
213958STHWK5-6
Adder
0.989
232417X3-008 C
Solar/Wind Harmer
0.74
960671AF2-358 GEN
Solar/Wind Harmer
6.569
232907VN8
Adder
10.963
233952AC2-187 GEN
Solar/Wind Harmer
0.41
233994AC2-023 GEN
Solar/Wind Harmer
0.977
233940AF2-379 C
Solar/Wind Harmer
0.068
233900O-025 C
Adder
0.427
234015AF2-250 C
Solar/Wind Harmer
0.044
233996TM1833_GEN
Solar/Wind Harmer
0.459
233997TMININ_4.2
Solar/Wind Harmer
0.459
232406W1-004 FULL
Solar/Wind Harmer
0.362
232921TASLEY2G
Adder
1.868
232914OH NUG3
Adder
3.196
232916OH NUG5
Adder
3.196
233990AG1-397 GEN
Solar/Wind Harmer
0.415
972073AH1-586 GEN
Solar/Wind Harmer
3.388
972133AH1-634 GEN
Solar/Wind Harmer
3.558
213560DLW11-12
Adder
0.911
233971AC1-093 C
Solar/Wind Harmer
0.271
970695AG2-447 GEN
Solar/Wind Harmer
1.239
213815MOSER1-3
Adder
1.097
228304LOGAN
Adder
6.684
219766PARADISE C
Solar/Wind Harmer
0.097
219912AD2-042 GEN
Solar/Wind Harmer
0.244
219623KINSLEYBEA C
Solar/Wind Harmer
0.13
219236SOUTHERNHQ C
Solar/Wind Harmer
0.02
230430AE1-229_GEN
Solar/Wind Harmer
2.621
219906AC1-017 C
Solar/Wind Harmer
0.066
230415AB2-049 C
Solar/Wind Harmer
0.056
971553AH1-274 GEN
Solar/Wind Harmer
0.709
228711V2-041C
Solar/Wind Harmer
0.175
228202CUMB CT
Adder
4.799
219610FLORENCE C
Solar/Wind Harmer
0.405
219348LDSOLAR C
Solar/Wind Harmer
0.175
219221BRL12CT1
Adder
2.607
219223BRL12CT3
Adder
2.607
219291REEVESSOUT C
Solar/Wind Harmer
0.017
972251AH1-710 GEN
Adder
13.808
228729W2-030 C
Solar/Wind Harmer
0.165
959561AF2-247 GEN
Solar/Wind Harmer
0.137
20716028EGP_W2-019
Solar/Wind Harmer
0.124
20720828JCB_W4-025
Solar/Wind Harmer
0.121
219727YARDVSOLFA C
Solar/Wind Harmer
0.246
20715028HAN_X4-015
Solar/Wind Harmer
0.08
213508CON10-11
50/50
1.01
213518CONOW8-9
50/50
1.01
213514CONOW1-2
50/50
0.746
213516CONOW5-6
50/50
0.746
231918WEST 1
Adder
1.445
231917EM10
Adder
1.008
213497CHSTR7-9
Adder
1.074
213497CHSTR7-9
Adder
1.074
233930AB2-032 GEN
Solar/Wind Harmer
0.343
233915AB1-141 GEN
Solar/Wind Harmer
0.407
232422X3-066 FULL
Solar/Wind Harmer
0.101
234012AE2-112_GEN
Solar/Wind Harmer
0.922
213958STHWK5-6
Adder
0.989
232910NRG_G1
Adder
3.243
233964AF2-378 GEN
Solar/Wind Harmer
0.047
232426Y1-080 FULL
Solar/Wind Harmer
0.07
970277AG2-181 GEN
Solar/Wind Harmer
1.841
965821AG1-450 GEN
Solar/Wind Harmer
1.909
232919VN10
Adder
1.027
233954AC2-188 GEN
Solar/Wind Harmer
0.41
233950AC2-186 GEN
Solar/Wind Harmer
0.205
232428Y3-058 C
Solar/Wind Harmer
0.303
971195AH1-057 GEN
Solar/Wind Harmer
0.397
233998TM1NIN_3.36
Solar/Wind Harmer
0.459
232404W1-003 C
Solar/Wind Harmer
0.362
232917OH NUG6
Adder
3.182
232915OH NUG4
Adder
3.174
232434Z2-077 GEN
Solar/Wind Harmer
0.09
972177AH1-672 GEN
Solar/Wind Harmer
4.814
213560DLW11-12
Adder
0.911
232900DEMECSMY
Adder
3.256
232901NORTHST
Adder
2.9
233972AC1-094 C
Solar/Wind Harmer
0.229
219258KINSLEYDEP C
Solar/Wind Harmer
0.1
219904AC1-010 C
Solar/Wind Harmer
0.116
219907AC1-030 C
Solar/Wind Harmer
0.042
228351V2-046C
Solar/Wind Harmer
0.605
230434AG1-499 GEN
Solar/Wind Harmer
0.174
970997AG2-616 GEN
Solar/Wind Harmer
2.86
945431AF1-208 GEN
Solar/Wind Harmer
2.563
230511AF1-262
Solar/Wind Harmer
0.054
228728W1-130C
Solar/Wind Harmer
0.195
228206SHRMN CT
Adder
4.83
219304NAMERICA C
Solar/Wind Harmer
0.091
219222BRL12CT2
Adder
2.607
228732V1-021 C
Adder
0.055
218660EHAMPSOLAR C
Solar/Wind Harmer
0.051
219686LUMSOLAR_N C
Solar/Wind Harmer
0.058
219287REEVESEAST C
Solar/Wind Harmer
0.388
214194N WALES4
Adder
0.245
213611FALLS1-3
Adder
1.014
20720728JCB_W1-129
Solar/Wind Harmer
0.08
207522AF2-254 C
Solar/Wind Harmer
0.384
207487AE2-000G4
Solar/Wind Harmer
8.261
207445AB1-138_GEN
Solar/Wind Harmer
0.151
20628028LAKEHURS
Adder
0.489
963711AG1-223 GEN
Solar/Wind Harmer
0.379
20714828MDF_W3-079
Solar/Wind Harmer
0.078
219680HOPEWELLV C1
Solar/Wind Harmer
0.02
207454AA2-184 E
Solar/Wind Harmer
0.251
20715228NPK_W1-113
Solar/Wind Harmer
0.108
217197RE CRAN C
Solar/Wind Harmer
0.135
20742028HF_AC1-207
Solar/Wind Harmer
0.196
20635828PARLN1&2
Adder
1.806
20635028RRCT1&2
Adder
2.816
20635128RRCT3&4
Adder
2.718
218428ETC SOLAR C
Solar/Wind Harmer
0.009
217213AMBOY SO C
Solar/Wind Harmer
0.03
972275AH1-722 GEN
Adder
7.523
207528AF2-192 GEN
Solar/Wind Harmer
0.132
20673628F1S_V4-069
Solar/Wind Harmer
0.043
20675428EAM_W2-061
Solar/Wind Harmer
0.045
208909MACR G3
Adder
32.152
223401AF1-299 GEN
Solar/Wind Helper
0.271
20636028O CRK C1
Adder
1.854
219276PARKLANDSO C
Solar/Wind Harmer
0.122
971667AH1-334 GEN
Solar/Wind Harmer
0.715
20714528FRN_Y2-051
Solar/Wind Harmer
0.076
219918AC2-009 C
Solar/Wind Harmer
0.016
20716228APLW2-078
Solar/Wind Harmer
0.222
20720528MAN_W1-024
Solar/Wind Harmer
0.064
219612MATRIX C
Solar/Wind Harmer
0.046
218438BLK ROCK C
Solar/Wind Harmer
0.034
967451AG2-055 C O1
Solar/Wind Harmer
42.597
20635828PARLN1&2
Adder
0.818
20635928PARLN3&4
Adder
0.818
20635028RRCT1&2
Adder
2.86
20635128RRCT3&4
Adder
2.371
219908AB1-139 C
Solar/Wind Harmer
0.091
219919AE1-041 FULL
Solar/Wind Harmer
0.01
219249CENTRALDIV C
Solar/Wind Harmer
0.009
20673728F2S_V4-070
Solar/Wind Harmer
0.043
223402AF1-300 C
Solar/Wind Helper
0.271
213589EDDYSTN4
Adder
31.437
213587EDDYSTN3
Adder
31.41
232416X2-083
Adder
0.19
233933AB2-153 GEN
Solar/Wind Harmer
0.463
233944AB2-135 GEN
Solar/Wind Harmer
2.122
234014AF1-036_GEN
Solar/Wind Harmer
1.085
231131BLOOM ENRGY
Adder
1.715
232424Y1-079 C
Solar/Wind Harmer
0.221
233984AB2-036 GEN
Solar/Wind Harmer
4.865
234041AC1-190 GEN
Solar/Wind Harmer
3.31
233987AB2-037 GEN
Solar/Wind Harmer
4.196
234036AF2-325 C
Solar/Wind Harmer
0.338
233946AB2-136 GEN
Solar/Wind Harmer
1.469
232926CRISFLD1
Adder
0.711
233901CHERRYDALE C
Solar/Wind Harmer
0.407
232408W1-005 C
Solar/Wind Harmer
0.362
232410W1-006 C
Solar/Wind Harmer
0.362
232905CHERITON_25
Adder
0.888
232918OH NUG7
Adder
3.174
971747AH1-380 GEN
Solar/Wind Harmer
1.296
972069AH1-584 GEN
Solar/Wind Harmer
3.238
972071AH1-585 GEN
Solar/Wind Harmer
3.238
231940T-011
Adder
0.269
970545AG2-347 GEN
Solar/Wind Harmer
23.481
232899W1-062
Adder
3.394
971149AH1-027 GEN
Solar/Wind Harmer
1.179
233939AC1-091 C
Solar/Wind Harmer
0.304
233970AC1-092 C
Solar/Wind Harmer
0.304
972233AH1-701 GEN
Adder
1.291
213815MOSER1-3
Adder
1.097
213815MOSER1-3
Adder
1.097
228304LOGAN
Adder
7.432
228307PCLP GT
Adder
3.695
219921AF1-264
Solar/Wind Harmer
0.044
228251CARLLS#4
Adder
0.186
219615MILLCREEK C
Solar/Wind Harmer
0.071
230433AD2-135 GEN
Solar/Wind Harmer
0.03
230407AD2-065 C
Solar/Wind Harmer
0.039
213535CROYDN11
Adder
3.002
230422AE1-104_GEN1
Solar/Wind Harmer
9.699
230425AE1-104_GEN2
Solar/Wind Harmer
9.699
219114HARTZY_C
Solar/Wind Harmer
0.227
20716428NHV_W2-082
Solar/Wind Harmer
0.476
207500AE2-000G1
Solar/Wind Harmer
8.261
207497AE2-000G2
Solar/Wind Harmer
8.261
207507AE2-000G3
Solar/Wind Harmer
8.261
20636128O CRK C2
Adder
1.69
20714928UPF_X1-085
Solar/Wind Harmer
0.107
963401AG1-189 GEN
Solar/Wind Harmer
0.301
963391AG1-188 GEN
Solar/Wind Harmer
0.501
20628028LAKEHURS
Adder
0.247
219817TRENTONSOL C
Solar/Wind Harmer
0.285
20720628TIN_W1-124
Solar/Wind Harmer
0.25
20641628MLH_W1-032
Solar/Wind Harmer
0.073
20716928W4-060COL
Solar/Wind Harmer
0.175
924131AB2-057 GEN
Solar/Wind Harmer
0.252
218440SUMMTASSOC C
Solar/Wind Harmer
0.031
20673828FLE_V3-070
Solar/Wind Harmer
0.11
218418LINDEN_G5
Adder
4.092
218419LINDEN_G6
Adder
4.092
972260AH1-715 GEN1
Adder
3.277
207442AE1-156 GEN
Solar/Wind Harmer
0.177
20676128MHD_W3-029
Solar/Wind Harmer
0.114
213515CONOW3-4
50/50
0.746
213515CONOW3-4
50/50
0.746
213514CONOW1-2
50/50
0.56
213516CONOW5-6
50/50
0.56
233935AB2-179 C
Solar/Wind Harmer
1.161
231919CHRIST1
Adder
1.882
231920CHRIST2
Adder
1.84
971983AH1-536 GEN
Solar/Wind Harmer
3.073
232436AB1-176 C
Solar/Wind Harmer
0.092
233968AD2-076_GEN
Solar/Wind Harmer
2.657
970597AG2-380 GEN
Solar/Wind Harmer
1.669
231906DC3 NUG
Adder
5.528
231902DC CT7
Adder
4.419
231907DC10
Adder
1.38
213942SCHUYLKILL
Adder
1.305
213942SCHUYLKILL
Adder
0.998
213957STHWK3-4
Adder
0.989
213957STHWK3-4
Adder
0.989
232813VAUGHN
Adder
0.218
233955AB2-172 GEN
Solar/Wind Harmer
1.85
233923SMA
Solar/Wind Harmer
1.683
232912OH NUG1
Adder
3.196
232913OH NUG2
Adder
3.153
233990AG1-397 GEN
Solar/Wind Harmer
0.02
232432Z2-076 GEN
Solar/Wind Harmer
0.048
232920IR10
Adder
1.135
234033AF1-007_GEN
Solar/Wind Harmer
8.391
232904IR4
Adder
29.014
213561DLWR9-10
Adder
1.191
213561DLWR9-10
Adder
0.911
233973AC2-185 C
Solar/Wind Harmer
1.25
219137THOSOLAR C
Solar/Wind Harmer
0.375
219914AD2-027 C
Solar/Wind Harmer
0.184
971011AG2-627 GEN
Solar/Wind Harmer
2.317
228309CCLP NUG
Adder
7.778
228309CCLP NUG
Adder
7.399
964001AG1-254 GEN
Solar/Wind Harmer
0.611
972141AH1-641 GEN
Solar/Wind Harmer
0.858
228260V4-054C
Solar/Wind Harmer
0.303
971535AH1-265 GEN
Solar/Wind Harmer
1.252
219272CLEANLIGHT C
Solar/Wind Harmer
0.053
970453AG2-297 GEN
Solar/Wind Harmer
0.8
219607WPEMNERT C
Solar/Wind Harmer
0.122
219224BRL12CT4
Adder
2.607
219688LUMSOLAR_S C
Solar/Wind Harmer
0.059
228754AB1-001 C
Solar/Wind Harmer
0.04
227927V4-067C
Solar/Wind Harmer
0.057
214067T20SOLAR
Solar/Wind Harmer
0.073
213611FALLS1-3
Adder
1.014
213611FALLS1-3
Adder
1.014
20717128DIX_Z2-102
Solar/Wind Harmer
0.352
20715728PEM_W1-119
Solar/Wind Harmer
0.142
20715828PEM_W1-120
Solar/Wind Harmer
0.142
971189AH1-054 GEN
Solar/Wind Harmer
0.31
970025AG2-016 GEN
Solar/Wind Harmer
0.741
207459AE1-142 C O1
Solar/Wind Harmer
0.274
219620RIDERU C
Solar/Wind Harmer
0.014
20714328BYD_X4-031
Solar/Wind Harmer
0.071
20714428HOW_X1-037
Solar/Wind Harmer
0.311
971521AH1-258 GEN
Solar/Wind Harmer
0.675
20720428HOL_W1-112
Solar/Wind Harmer
0.086
218455CINNBAY_CGEN
Adder
0.446
20635928PARLN3&4
Adder
1.806
20675528CPH_W2-050
Solar/Wind Harmer
0.114
218526CNTRALGAS2 C
Solar/Wind Harmer
0.09
218524CNTRALGAS1 C
Solar/Wind Harmer
0.089
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.034
G-007ALTFEXP_G-007A->PJM
CMTX
12.437
CBM NorthLTFEXP_CBM-N->PJM
CBM
16.035
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.84
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.618
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
31.56
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.609
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
3.958

Details for COOPER-GRACETON 230.0 kV Ckt 1 line l/o BGE_P4_GRACETON_51_SRT-A


Base Case Flowgate

Area:BGE/PECO
Facility Description:
COOPER-GRACETON 230.0 kV Ckt 1 line
Contingency Name:
BGE_P4_GRACETON_51_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:129.12 %
Rating:578.0 MVA
Rating Type:B
MVA to Mitigate:746.32
MW Contribution:2.32
Bus #Bus NameTypeMW Contribution
213508CON10-11
50/50
1.01
213518CONOW8-9
50/50
1.01
213589EDDYSTN4
Adder
31.437
213587EDDYSTN3
Adder
31.41
232416X2-083
Adder
0.19
233933AB2-153 GEN
Solar/Wind Harmer
0.463
233944AB2-135 GEN
Solar/Wind Harmer
2.122
234014AF1-036_GEN
Solar/Wind Harmer
1.085
231131BLOOM ENRGY
Adder
1.715
232424Y1-079 C
Solar/Wind Harmer
0.221
233984AB2-036 GEN
Solar/Wind Harmer
4.865
234041AC1-190 GEN
Solar/Wind Harmer
3.31
233987AB2-037 GEN
Solar/Wind Harmer
4.196
234036AF2-325 C
Solar/Wind Harmer
0.338
233946AB2-136 GEN
Solar/Wind Harmer
1.469
232926CRISFLD1
Adder
0.711
233901CHERRYDALE C
Solar/Wind Harmer
0.407
232408W1-005 C
Solar/Wind Harmer
0.362
232410W1-006 C
Solar/Wind Harmer
0.362
232905CHERITON_25
Adder
0.888
232918OH NUG7
Adder
3.174
971747AH1-380 GEN
Solar/Wind Harmer
1.296
972069AH1-584 GEN
Solar/Wind Harmer
3.238
972071AH1-585 GEN
Solar/Wind Harmer
3.238
231940T-011
Adder
0.269
970545AG2-347 GEN
Solar/Wind Harmer
23.481
232899W1-062
Adder
3.394
971149AH1-027 GEN
Solar/Wind Harmer
1.179
233939AC1-091 C
Solar/Wind Harmer
0.304
233970AC1-092 C
Solar/Wind Harmer
0.304
972233AH1-701 GEN
Adder
1.291
213815MOSER1-3
Adder
1.097
213815MOSER1-3
Adder
1.097
228304LOGAN
Adder
7.432
228307PCLP GT
Adder
3.695
219921AF1-264
Solar/Wind Harmer
0.044
228251CARLLS#4
Adder
0.186
219615MILLCREEK C
Solar/Wind Harmer
0.071
230433AD2-135 GEN
Solar/Wind Harmer
0.03
230407AD2-065 C
Solar/Wind Harmer
0.039
213535CROYDN11
Adder
3.002
230422AE1-104_GEN1
Solar/Wind Harmer
9.699
230425AE1-104_GEN2
Solar/Wind Harmer
9.699
219114HARTZY_C
Solar/Wind Harmer
0.227
20716428NHV_W2-082
Solar/Wind Harmer
0.476
207500AE2-000G1
Solar/Wind Harmer
8.261
207497AE2-000G2
Solar/Wind Harmer
8.261
207507AE2-000G3
Solar/Wind Harmer
8.261
20636128O CRK C2
Adder
1.69
20714928UPF_X1-085
Solar/Wind Harmer
0.107
963401AG1-189 GEN
Solar/Wind Harmer
0.301
963391AG1-188 GEN
Solar/Wind Harmer
0.501
20628028LAKEHURS
Adder
0.247
219817TRENTONSOL C
Solar/Wind Harmer
0.285
20720628TIN_W1-124
Solar/Wind Harmer
0.25
20641628MLH_W1-032
Solar/Wind Harmer
0.073
20716928W4-060COL
Solar/Wind Harmer
0.175
924131AB2-057 GEN
Solar/Wind Harmer
0.252
218440SUMMTASSOC C
Solar/Wind Harmer
0.031
20673828FLE_V3-070
Solar/Wind Harmer
0.11
218418LINDEN_G5
Adder
4.092
218419LINDEN_G6
Adder
4.092
213515CONOW3-4
50/50
0.746
213515CONOW3-4
50/50
0.746
213514CONOW1-2
50/50
0.56
213516CONOW5-6
50/50
0.56
233935AB2-179 C
Solar/Wind Harmer
1.161
231919CHRIST1
Adder
1.882
231920CHRIST2
Adder
1.84
971983AH1-536 GEN
Solar/Wind Harmer
3.073
232436AB1-176 C
Solar/Wind Harmer
0.092
233968AD2-076_GEN
Solar/Wind Harmer
2.657
970597AG2-380 GEN
Solar/Wind Harmer
1.669
231906DC3 NUG
Adder
5.528
231902DC CT7
Adder
4.419
231907DC10
Adder
1.38
213942SCHUYLKILL
Adder
1.305
213942SCHUYLKILL
Adder
0.998
213957STHWK3-4
Adder
0.989
213957STHWK3-4
Adder
0.989
232813VAUGHN
Adder
0.218
233955AB2-172 GEN
Solar/Wind Harmer
1.85
233923SMA
Solar/Wind Harmer
1.683
232912OH NUG1
Adder
3.196
232913OH NUG2
Adder
3.153
233990AG1-397 GEN
Solar/Wind Harmer
0.02
232432Z2-076 GEN
Solar/Wind Harmer
0.048
232920IR10
Adder
1.135
234033AF1-007_GEN
Solar/Wind Harmer
8.391
232904IR4
Adder
29.014
213561DLWR9-10
Adder
1.191
213561DLWR9-10
Adder
0.911
233973AC2-185 C
Solar/Wind Harmer
1.25
219137THOSOLAR C
Solar/Wind Harmer
0.375
219914AD2-027 C
Solar/Wind Harmer
0.184
971011AG2-627 GEN
Solar/Wind Harmer
2.317
228309CCLP NUG
Adder
7.778
228309CCLP NUG
Adder
7.399
964001AG1-254 GEN
Solar/Wind Harmer
0.611
972141AH1-641 GEN
Solar/Wind Harmer
0.858
213514CONOW1-2
50/50
0.746
213516CONOW5-6
50/50
0.746
231918WEST 1
Adder
1.445
231917EM10
Adder
1.008
213497CHSTR7-9
Adder
1.074
213497CHSTR7-9
Adder
1.074
233930AB2-032 GEN
Solar/Wind Harmer
0.343
233915AB1-141 GEN
Solar/Wind Harmer
0.407
232422X3-066 FULL
Solar/Wind Harmer
0.101
234012AE2-112_GEN
Solar/Wind Harmer
0.922
213958STHWK5-6
Adder
0.989
232910NRG_G1
Adder
3.243
233964AF2-378 GEN
Solar/Wind Harmer
0.047
232426Y1-080 FULL
Solar/Wind Harmer
0.07
970277AG2-181 GEN
Solar/Wind Harmer
1.841
965821AG1-450 GEN
Solar/Wind Harmer
1.909
232919VN10
Adder
1.027
233954AC2-188 GEN
Solar/Wind Harmer
0.41
233950AC2-186 GEN
Solar/Wind Harmer
0.205
232428Y3-058 C
Solar/Wind Harmer
0.303
971195AH1-057 GEN
Solar/Wind Harmer
0.397
233998TM1NIN_3.36
Solar/Wind Harmer
0.459
232404W1-003 C
Solar/Wind Harmer
0.362
232917OH NUG6
Adder
3.182
232915OH NUG4
Adder
3.174
232434Z2-077 GEN
Solar/Wind Harmer
0.09
972177AH1-672 GEN
Solar/Wind Harmer
4.814
213560DLW11-12
Adder
0.911
232900DEMECSMY
Adder
3.256
232901NORTHST
Adder
2.9
233972AC1-094 C
Solar/Wind Harmer
0.229
219258KINSLEYDEP C
Solar/Wind Harmer
0.1
219904AC1-010 C
Solar/Wind Harmer
0.116
219907AC1-030 C
Solar/Wind Harmer
0.042
228351V2-046C
Solar/Wind Harmer
0.605
230434AG1-499 GEN
Solar/Wind Harmer
0.174
970997AG2-616 GEN
Solar/Wind Harmer
2.86
945431AF1-208 GEN
Solar/Wind Harmer
2.563
230511AF1-262
Solar/Wind Harmer
0.054
228728W1-130C
Solar/Wind Harmer
0.195
228206SHRMN CT
Adder
4.83
219304NAMERICA C
Solar/Wind Harmer
0.091
219222BRL12CT2
Adder
2.607
228732V1-021 C
Adder
0.055
218660EHAMPSOLAR C
Solar/Wind Harmer
0.051
219686LUMSOLAR_N C
Solar/Wind Harmer
0.058
219287REEVESEAST C
Solar/Wind Harmer
0.388
214194N WALES4
Adder
0.245
213611FALLS1-3
Adder
1.014
20720728JCB_W1-129
Solar/Wind Harmer
0.08
207522AF2-254 C
Solar/Wind Harmer
0.384
207487AE2-000G4
Solar/Wind Harmer
8.261
207445AB1-138_GEN
Solar/Wind Harmer
0.151
20628028LAKEHURS
Adder
0.489
963711AG1-223 GEN
Solar/Wind Harmer
0.379
20714828MDF_W3-079
Solar/Wind Harmer
0.078
219680HOPEWELLV C1
Solar/Wind Harmer
0.02
207454AA2-184 E
Solar/Wind Harmer
0.251
20715228NPK_W1-113
Solar/Wind Harmer
0.108
217197RE CRAN C
Solar/Wind Harmer
0.135
20742028HF_AC1-207
Solar/Wind Harmer
0.196
20635828PARLN1&2
Adder
1.806
20635028RRCT1&2
Adder
2.816
20635128RRCT3&4
Adder
2.718
218428ETC SOLAR C
Solar/Wind Harmer
0.009
217213AMBOY SO C
Solar/Wind Harmer
0.03
972275AH1-722 GEN
Adder
7.523
207528AF2-192 GEN
Solar/Wind Harmer
0.132
20673628F1S_V4-069
Solar/Wind Harmer
0.043
20675428EAM_W2-061
Solar/Wind Harmer
0.045
208909MACR G3
Adder
32.152
223401AF1-299 GEN
Solar/Wind Helper
0.271
213508CON10-11
50/50
1.01
213518CONOW8-9
50/50
1.01
213517CONOW7
50/50
0.746
213497CHSTR7-9
Adder
1.074
233982AB2-133 GEN
Solar/Wind Harmer
2.007
233918AB1-142 GEN
Solar/Wind Harmer
0.407
213958STHWK5-6
Adder
0.989
232417X3-008 C
Solar/Wind Harmer
0.74
960671AF2-358 GEN
Solar/Wind Harmer
6.569
232907VN8
Adder
10.963
233952AC2-187 GEN
Solar/Wind Harmer
0.41
233994AC2-023 GEN
Solar/Wind Harmer
0.977
233940AF2-379 C
Solar/Wind Harmer
0.068
233900O-025 C
Adder
0.427
234015AF2-250 C
Solar/Wind Harmer
0.044
233996TM1833_GEN
Solar/Wind Harmer
0.459
233997TMININ_4.2
Solar/Wind Harmer
0.459
232406W1-004 FULL
Solar/Wind Harmer
0.362
232921TASLEY2G
Adder
1.868
232914OH NUG3
Adder
3.196
232916OH NUG5
Adder
3.196
233990AG1-397 GEN
Solar/Wind Harmer
0.415
972073AH1-586 GEN
Solar/Wind Harmer
3.388
972133AH1-634 GEN
Solar/Wind Harmer
3.558
213560DLW11-12
Adder
0.911
233971AC1-093 C
Solar/Wind Harmer
0.271
970695AG2-447 GEN
Solar/Wind Harmer
1.239
213815MOSER1-3
Adder
1.097
228304LOGAN
Adder
6.684
219766PARADISE C
Solar/Wind Harmer
0.097
219912AD2-042 GEN
Solar/Wind Harmer
0.244
219623KINSLEYBEA C
Solar/Wind Harmer
0.13
219236SOUTHERNHQ C
Solar/Wind Harmer
0.02
230430AE1-229_GEN
Solar/Wind Harmer
2.621
219906AC1-017 C
Solar/Wind Harmer
0.066
230415AB2-049 C
Solar/Wind Harmer
0.056
971553AH1-274 GEN
Solar/Wind Harmer
0.709
228711V2-041C
Solar/Wind Harmer
0.175
228202CUMB CT
Adder
4.799
219610FLORENCE C
Solar/Wind Harmer
0.405
219348LDSOLAR C
Solar/Wind Harmer
0.175
219221BRL12CT1
Adder
2.607
219223BRL12CT3
Adder
2.607
219291REEVESSOUT C
Solar/Wind Harmer
0.017
972251AH1-710 GEN
Adder
13.808
228729W2-030 C
Solar/Wind Harmer
0.165
959561AF2-247 GEN
Solar/Wind Harmer
0.137
20716028EGP_W2-019
Solar/Wind Harmer
0.124
20720828JCB_W4-025
Solar/Wind Harmer
0.121
219727YARDVSOLFA C
Solar/Wind Harmer
0.246
20715028HAN_X4-015
Solar/Wind Harmer
0.08
20636028O CRK C1
Adder
1.854
219276PARKLANDSO C
Solar/Wind Harmer
0.122
971667AH1-334 GEN
Solar/Wind Harmer
0.715
20714528FRN_Y2-051
Solar/Wind Harmer
0.076
219918AC2-009 C
Solar/Wind Harmer
0.016
20716228APLW2-078
Solar/Wind Harmer
0.222
20720528MAN_W1-024
Solar/Wind Harmer
0.064
219612MATRIX C
Solar/Wind Harmer
0.046
972260AH1-715 GEN1
Adder
3.277
207442AE1-156 GEN
Solar/Wind Harmer
0.177
20676128MHD_W3-029
Solar/Wind Harmer
0.114
228260V4-054C
Solar/Wind Harmer
0.303
971535AH1-265 GEN
Solar/Wind Harmer
1.252
219272CLEANLIGHT C
Solar/Wind Harmer
0.053
970453AG2-297 GEN
Solar/Wind Harmer
0.8
219607WPEMNERT C
Solar/Wind Harmer
0.122
219224BRL12CT4
Adder
2.607
219688LUMSOLAR_S C
Solar/Wind Harmer
0.059
228754AB1-001 C
Solar/Wind Harmer
0.04
227927V4-067C
Solar/Wind Harmer
0.057
214067T20SOLAR
Solar/Wind Harmer
0.073
213611FALLS1-3
Adder
1.014
213611FALLS1-3
Adder
1.014
20717128DIX_Z2-102
Solar/Wind Harmer
0.352
20715728PEM_W1-119
Solar/Wind Harmer
0.142
20715828PEM_W1-120
Solar/Wind Harmer
0.142
971189AH1-054 GEN
Solar/Wind Harmer
0.31
970025AG2-016 GEN
Solar/Wind Harmer
0.741
207459AE1-142 C O1
Solar/Wind Harmer
0.274
219620RIDERU C
Solar/Wind Harmer
0.014
20714328BYD_X4-031
Solar/Wind Harmer
0.071
20714428HOW_X1-037
Solar/Wind Harmer
0.311
971521AH1-258 GEN
Solar/Wind Harmer
0.675
20720428HOL_W1-112
Solar/Wind Harmer
0.086
218455CINNBAY_CGEN
Adder
0.446
20635928PARLN3&4
Adder
1.806
20675528CPH_W2-050
Solar/Wind Harmer
0.114
218526CNTRALGAS2 C
Solar/Wind Harmer
0.09
218524CNTRALGAS1 C
Solar/Wind Harmer
0.089
218438BLK ROCK C
Solar/Wind Harmer
0.034
967451AG2-055 C O1
Solar/Wind Harmer
42.597
20635828PARLN1&2
Adder
0.818
20635928PARLN3&4
Adder
0.818
20635028RRCT1&2
Adder
2.86
20635128RRCT3&4
Adder
2.371
219908AB1-139 C
Solar/Wind Harmer
0.091
219919AE1-041 FULL
Solar/Wind Harmer
0.01
219249CENTRALDIV C
Solar/Wind Harmer
0.009
20673728F2S_V4-070
Solar/Wind Harmer
0.043
223402AF1-300 C
Solar/Wind Helper
0.271
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.034
G-007ALTFEXP_G-007A->PJM
CMTX
12.437
CBM NorthLTFEXP_CBM-N->PJM
CBM
16.035
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.84
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.618
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
31.56
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.609
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
3.958

Details for COOPER-GRACETON 230.0 kV Ckt 1 line l/o PJM_500_BG_P4_5_CNSTN_B_SRT-A


Base Case Flowgate

Area:BGE/PECO
Facility Description:
COOPER-GRACETON 230.0 kV Ckt 1 line
Contingency Name:
PJM_500_BG_P4_5_CNSTN_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:128.12 %
Rating:578.0 MVA
Rating Type:B
MVA to Mitigate:740.53
MW Contribution:2.28
Bus #Bus NameTypeMW Contribution
213508CON10-11
50/50
1.003
213518CONOW8-9
50/50
1.003
213514CONOW1-2
50/50
0.741
213516CONOW5-6
50/50
0.741
231918WEST 1
Adder
1.427
231917EM10
Adder
0.996
213497CHSTR7-9
Adder
1.06
213497CHSTR7-9
Adder
1.06
233930AB2-032 GEN
Solar/Wind Harmer
0.339
233915AB1-141 GEN
Solar/Wind Harmer
0.402
232422X3-066 FULL
Solar/Wind Harmer
0.099
234012AE2-112_GEN
Solar/Wind Harmer
0.91
213958STHWK5-6
Adder
0.976
232910NRG_G1
Adder
3.201
233964AF2-378 GEN
Solar/Wind Harmer
0.046
232426Y1-080 FULL
Solar/Wind Harmer
0.069
970277AG2-181 GEN
Solar/Wind Harmer
1.817
965821AG1-450 GEN
Solar/Wind Harmer
1.884
232919VN10
Adder
1.013
233954AC2-188 GEN
Solar/Wind Harmer
0.404
233950AC2-186 GEN
Solar/Wind Harmer
0.202
232428Y3-058 C
Solar/Wind Harmer
0.299
971195AH1-057 GEN
Solar/Wind Harmer
0.391
233998TM1NIN_3.36
Solar/Wind Harmer
0.453
232404W1-003 C
Solar/Wind Harmer
0.358
232917OH NUG6
Adder
3.139
232915OH NUG4
Adder
3.132
232434Z2-077 GEN
Solar/Wind Harmer
0.089
972177AH1-672 GEN
Solar/Wind Harmer
4.749
213560DLW11-12
Adder
0.898
232900DEMECSMY
Adder
3.212
232901NORTHST
Adder
2.86
233972AC1-094 C
Solar/Wind Harmer
0.226
219258KINSLEYDEP C
Solar/Wind Harmer
0.098
219904AC1-010 C
Solar/Wind Harmer
0.114
219907AC1-030 C
Solar/Wind Harmer
0.041
228351V2-046C
Solar/Wind Harmer
0.596
230434AG1-499 GEN
Solar/Wind Harmer
0.172
970997AG2-616 GEN
Solar/Wind Harmer
2.817
945431AF1-208 GEN
Solar/Wind Harmer
2.525
230511AF1-262
Solar/Wind Harmer
0.054
228728W1-130C
Solar/Wind Harmer
0.192
228206SHRMN CT
Adder
4.757
219304NAMERICA C
Solar/Wind Harmer
0.089
219222BRL12CT2
Adder
2.567
228732V1-021 C
Adder
0.054
218660EHAMPSOLAR C
Solar/Wind Harmer
0.05
219287REEVESEAST C
Solar/Wind Harmer
0.382
219686LUMSOLAR_N C
Solar/Wind Harmer
0.058
214194N WALES4
Adder
0.241
213611FALLS1-3
Adder
0.999
20720728JCB_W1-129
Solar/Wind Harmer
0.079
207522AF2-254 C
Solar/Wind Harmer
0.377
207487AE2-000G4
Solar/Wind Harmer
8.125
207445AB1-138_GEN
Solar/Wind Harmer
0.148
20628028LAKEHURS
Adder
0.48
963711AG1-223 GEN
Solar/Wind Harmer
0.373
20714828MDF_W3-079
Solar/Wind Harmer
0.077
219680HOPEWELLV C1
Solar/Wind Harmer
0.019
207454AA2-184 E
Solar/Wind Harmer
0.247
20715228NPK_W1-113
Solar/Wind Harmer
0.106
217197RE CRAN C
Solar/Wind Harmer
0.133
20742028HF_AC1-207
Solar/Wind Harmer
0.192
20635828PARLN1&2
Adder
1.773
20635028RRCT1&2
Adder
2.765
20635128RRCT3&4
Adder
2.669
218428ETC SOLAR C
Solar/Wind Harmer
0.008
217213AMBOY SO C
Solar/Wind Harmer
0.03
208909MACR G3
Adder
31.429
223401AF1-299 GEN
Solar/Wind Helper
0.284
213589EDDYSTN4
Adder
31.043
213587EDDYSTN3
Adder
31.015
232416X2-083
Adder
0.188
233933AB2-153 GEN
Solar/Wind Harmer
0.457
233944AB2-135 GEN
Solar/Wind Harmer
2.096
234014AF1-036_GEN
Solar/Wind Harmer
1.071
231131BLOOM ENRGY
Adder
1.693
232424Y1-079 C
Solar/Wind Harmer
0.218
233984AB2-036 GEN
Solar/Wind Harmer
4.803
234041AC1-190 GEN
Solar/Wind Harmer
3.266
233987AB2-037 GEN
Solar/Wind Harmer
4.141
234036AF2-325 C
Solar/Wind Harmer
0.334
233946AB2-136 GEN
Solar/Wind Harmer
1.449
232926CRISFLD1
Adder
0.702
233901CHERRYDALE C
Solar/Wind Harmer
0.402
232408W1-005 C
Solar/Wind Harmer
0.358
232410W1-006 C
Solar/Wind Harmer
0.358
232918OH NUG7
Adder
3.132
232905CHERITON_25
Adder
0.876
971747AH1-380 GEN
Solar/Wind Harmer
1.278
972069AH1-584 GEN
Solar/Wind Harmer
3.195
972071AH1-585 GEN
Solar/Wind Harmer
3.195
231940T-011
Adder
0.266
970545AG2-347 GEN
Solar/Wind Harmer
23.167
232899W1-062
Adder
3.348
971149AH1-027 GEN
Solar/Wind Harmer
1.163
233939AC1-091 C
Solar/Wind Harmer
0.3
233970AC1-092 C
Solar/Wind Harmer
0.3
972233AH1-701 GEN
Adder
1.272
213815MOSER1-3
Adder
1.08
213815MOSER1-3
Adder
1.08
228304LOGAN
Adder
7.323
228307PCLP GT
Adder
3.641
219921AF1-264
Solar/Wind Harmer
0.043
228251CARLLS#4
Adder
0.183
219615MILLCREEK C
Solar/Wind Harmer
0.07
230433AD2-135 GEN
Solar/Wind Harmer
0.029
230407AD2-065 C
Solar/Wind Harmer
0.038
213535CROYDN11
Adder
2.956
230422AE1-104_GEN1
Solar/Wind Harmer
9.552
230425AE1-104_GEN2
Solar/Wind Harmer
9.552
219114HARTZY_C
Solar/Wind Harmer
0.224
20716428NHV_W2-082
Solar/Wind Harmer
0.468
207500AE2-000G1
Solar/Wind Harmer
8.125
207497AE2-000G2
Solar/Wind Harmer
8.125
207507AE2-000G3
Solar/Wind Harmer
8.125
20636128O CRK C2
Adder
1.662
20714928UPF_X1-085
Solar/Wind Harmer
0.105
963401AG1-189 GEN
Solar/Wind Harmer
0.296
963391AG1-188 GEN
Solar/Wind Harmer
0.493
20628028LAKEHURS
Adder
0.243
219817TRENTONSOL C
Solar/Wind Harmer
0.28
20720628TIN_W1-124
Solar/Wind Harmer
0.246
20641628MLH_W1-032
Solar/Wind Harmer
0.072
20716928W4-060COL
Solar/Wind Harmer
0.172
924131AB2-057 GEN
Solar/Wind Harmer
0.248
218440SUMMTASSOC C
Solar/Wind Harmer
0.03
20673828FLE_V3-070
Solar/Wind Harmer
0.108
208835TUHI V3-051
Solar/Wind Helper
0.011
208835TUHI V3-051
Solar/Wind Helper
0.011
213515CONOW3-4
50/50
0.741
213515CONOW3-4
50/50
0.741
213514CONOW1-2
50/50
0.555
213516CONOW5-6
50/50
0.555
233935AB2-179 C
Solar/Wind Harmer
1.148
231919CHRIST1
Adder
1.859
231920CHRIST2
Adder
1.818
971983AH1-536 GEN
Solar/Wind Harmer
3.035
232436AB1-176 C
Solar/Wind Harmer
0.091
233968AD2-076_GEN
Solar/Wind Harmer
2.624
970597AG2-380 GEN
Solar/Wind Harmer
1.648
231906DC3 NUG
Adder
5.458
231902DC CT7
Adder
4.363
231907DC10
Adder
1.363
213942SCHUYLKILL
Adder
1.288
213942SCHUYLKILL
Adder
0.985
213957STHWK3-4
Adder
0.976
213957STHWK3-4
Adder
0.976
232813VAUGHN
Adder
0.216
233955AB2-172 GEN
Solar/Wind Harmer
1.826
233923SMA
Solar/Wind Harmer
1.66
232912OH NUG1
Adder
3.153
232913OH NUG2
Adder
3.111
233990AG1-397 GEN
Solar/Wind Harmer
0.02
232432Z2-076 GEN
Solar/Wind Harmer
0.047
232920IR10
Adder
1.12
234033AF1-007_GEN
Solar/Wind Harmer
8.279
232904IR4
Adder
28.625
213561DLWR9-10
Adder
1.175
213561DLWR9-10
Adder
0.898
233973AC2-185 C
Solar/Wind Harmer
1.233
219137THOSOLAR C
Solar/Wind Harmer
0.37
219914AD2-027 C
Solar/Wind Harmer
0.181
971011AG2-627 GEN
Solar/Wind Harmer
2.283
228309CCLP NUG
Adder
7.663
228309CCLP NUG
Adder
7.29
964001AG1-254 GEN
Solar/Wind Harmer
0.602
972141AH1-641 GEN
Solar/Wind Harmer
0.845
228260V4-054C
Solar/Wind Harmer
0.299
971535AH1-265 GEN
Solar/Wind Harmer
1.233
219272CLEANLIGHT C
Solar/Wind Harmer
0.053
970453AG2-297 GEN
Solar/Wind Harmer
0.788
219607WPEMNERT C
Solar/Wind Harmer
0.121
219224BRL12CT4
Adder
2.567
219688LUMSOLAR_S C
Solar/Wind Harmer
0.058
228754AB1-001 C
Solar/Wind Harmer
0.039
227927V4-067C
Solar/Wind Harmer
0.056
214067T20SOLAR
Solar/Wind Harmer
0.071
213611FALLS1-3
Adder
0.999
213611FALLS1-3
Adder
0.999
20717128DIX_Z2-102
Solar/Wind Harmer
0.347
20715728PEM_W1-119
Solar/Wind Harmer
0.14
20715828PEM_W1-120
Solar/Wind Harmer
0.14
971189AH1-054 GEN
Solar/Wind Harmer
0.304
970025AG2-016 GEN
Solar/Wind Harmer
0.728
207459AE1-142 C O1
Solar/Wind Harmer
0.27
219620RIDERU C
Solar/Wind Harmer
0.014
20714328BYD_X4-031
Solar/Wind Harmer
0.07
20714428HOW_X1-037
Solar/Wind Harmer
0.306
971521AH1-258 GEN
Solar/Wind Harmer
0.663
20720428HOL_W1-112
Solar/Wind Harmer
0.085
218455CINNBAY_CGEN
Adder
0.438
20635928PARLN3&4
Adder
1.773
20675528CPH_W2-050
Solar/Wind Harmer
0.112
218526CNTRALGAS2 C
Solar/Wind Harmer
0.088
218524CNTRALGAS1 C
Solar/Wind Harmer
0.088
213508CON10-11
50/50
1.003
213518CONOW8-9
50/50
1.003
213517CONOW7
50/50
0.741
213497CHSTR7-9
Adder
1.06
233982AB2-133 GEN
Solar/Wind Harmer
1.982
233918AB1-142 GEN
Solar/Wind Harmer
0.402
213958STHWK5-6
Adder
0.976
232417X3-008 C
Solar/Wind Harmer
0.73
960671AF2-358 GEN
Solar/Wind Harmer
6.482
232907VN8
Adder
10.817
233952AC2-187 GEN
Solar/Wind Harmer
0.404
233994AC2-023 GEN
Solar/Wind Harmer
0.964
233940AF2-379 C
Solar/Wind Harmer
0.067
234015AF2-250 C
Solar/Wind Harmer
0.043
233900O-025 C
Adder
0.421
233996TM1833_GEN
Solar/Wind Harmer
0.453
233997TMININ_4.2
Solar/Wind Harmer
0.453
232406W1-004 FULL
Solar/Wind Harmer
0.358
232914OH NUG3
Adder
3.153
232916OH NUG5
Adder
3.153
232921TASLEY2G
Adder
1.843
233990AG1-397 GEN
Solar/Wind Harmer
0.409
972073AH1-586 GEN
Solar/Wind Harmer
3.343
972133AH1-634 GEN
Solar/Wind Harmer
3.51
213560DLW11-12
Adder
0.898
233971AC1-093 C
Solar/Wind Harmer
0.268
970695AG2-447 GEN
Solar/Wind Harmer
1.222
213815MOSER1-3
Adder
1.08
228304LOGAN
Adder
6.586
219766PARADISE C
Solar/Wind Harmer
0.095
219912AD2-042 GEN
Solar/Wind Harmer
0.241
219623KINSLEYBEA C
Solar/Wind Harmer
0.128
219236SOUTHERNHQ C
Solar/Wind Harmer
0.02
230430AE1-229_GEN
Solar/Wind Harmer
2.582
219906AC1-017 C
Solar/Wind Harmer
0.065
230415AB2-049 C
Solar/Wind Harmer
0.055
971553AH1-274 GEN
Solar/Wind Harmer
0.698
228711V2-041C
Solar/Wind Harmer
0.172
228202CUMB CT
Adder
4.727
219610FLORENCE C
Solar/Wind Harmer
0.398
219348LDSOLAR C
Solar/Wind Harmer
0.172
219221BRL12CT1
Adder
2.567
219223BRL12CT3
Adder
2.567
219291REEVESSOUT C
Solar/Wind Harmer
0.017
972251AH1-710 GEN
Adder
13.602
228729W2-030 C
Solar/Wind Harmer
0.163
959561AF2-247 GEN
Solar/Wind Harmer
0.134
20716028EGP_W2-019
Solar/Wind Harmer
0.122
20720828JCB_W4-025
Solar/Wind Harmer
0.119
219727YARDVSOLFA C
Solar/Wind Harmer
0.242
20715028HAN_X4-015
Solar/Wind Harmer
0.079
20636028O CRK C1
Adder
1.823
219276PARKLANDSO C
Solar/Wind Harmer
0.12
971667AH1-334 GEN
Solar/Wind Harmer
0.703
20714528FRN_Y2-051
Solar/Wind Harmer
0.074
219918AC2-009 C
Solar/Wind Harmer
0.016
20716228APLW2-078
Solar/Wind Harmer
0.218
20720528MAN_W1-024
Solar/Wind Harmer
0.062
219612MATRIX C
Solar/Wind Harmer
0.046
218438BLK ROCK C
Solar/Wind Harmer
0.034
967451AG2-055 C O1
Solar/Wind Harmer
41.842
20635828PARLN1&2
Adder
0.803
20635928PARLN3&4
Adder
0.803
20635028RRCT1&2
Adder
2.808
20635128RRCT3&4
Adder
2.328
219908AB1-139 C
Solar/Wind Harmer
0.09
219919AE1-041 FULL
Solar/Wind Harmer
0.01
223402AF1-300 C
Solar/Wind Helper
0.284
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.016
G-007ALTFEXP_G-007A->PJM
CMTX
12.213
CBM NorthLTFEXP_CBM-N->PJM
CBM
15.754
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.82
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.554
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
30.964
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.597
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
3.864

Details for COOPER-GRACETON 230.0 kV Ckt 1 line l/o PECO_P4_PEACH245_SRT-A/* $ CHESCO $ PECO_P4_PEACH245 $ STBK


Base Case Flowgate

Area:BGE/PECO
Facility Description:
COOPER-GRACETON 230.0 kV Ckt 1 line
Contingency Name:
PECO_P4_PEACH245_SRT-A/* $ CHESCO $ PECO_P4_PEACH245 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:122.82 %
Rating:578.0 MVA
Rating Type:B
MVA to Mitigate:709.88
MW Contribution:2.33
Bus #Bus NameTypeMW Contribution
213508CON10-11
50/50
1.011
213508CON10-11
50/50
1.011
213518CONOW8-9
50/50
1.011
213517CONOW7
50/50
0.747
213497CHSTR7-9
Adder
1.078
233982AB2-133 GEN
Solar/Wind Harmer
2.015
233918AB1-142 GEN
Solar/Wind Harmer
0.409
213958STHWK5-6
Adder
0.993
232417X3-008 C
Solar/Wind Harmer
0.743
960671AF2-358 GEN
Solar/Wind Harmer
6.596
232907VN8
Adder
11.009
233952AC2-187 GEN
Solar/Wind Harmer
0.411
233994AC2-023 GEN
Solar/Wind Harmer
0.982
233940AF2-379 C
Solar/Wind Harmer
0.068
233900O-025 C
Adder
0.429
234015AF2-250 C
Solar/Wind Harmer
0.044
233996TM1833_GEN
Solar/Wind Harmer
0.461
233997TMININ_4.2
Solar/Wind Harmer
0.461
232406W1-004 FULL
Solar/Wind Harmer
0.364
232914OH NUG3
Adder
3.209
232916OH NUG5
Adder
3.209
232921TASLEY2G
Adder
1.876
233990AG1-397 GEN
Solar/Wind Harmer
0.417
972073AH1-586 GEN
Solar/Wind Harmer
3.403
972133AH1-634 GEN
Solar/Wind Harmer
3.573
213560DLW11-12
Adder
0.915
233971AC1-093 C
Solar/Wind Harmer
0.273
970695AG2-447 GEN
Solar/Wind Harmer
1.245
213815MOSER1-3
Adder
1.102
228304LOGAN
Adder
6.716
219766PARADISE C
Solar/Wind Harmer
0.097
219912AD2-042 GEN
Solar/Wind Harmer
0.245
219623KINSLEYBEA C
Solar/Wind Harmer
0.131
219236SOUTHERNHQ C
Solar/Wind Harmer
0.02
230430AE1-229_GEN
Solar/Wind Harmer
2.634
219906AC1-017 C
Solar/Wind Harmer
0.066
230415AB2-049 C
Solar/Wind Harmer
0.056
971553AH1-274 GEN
Solar/Wind Harmer
0.712
228711V2-041C
Solar/Wind Harmer
0.176
228202CUMB CT
Adder
4.823
219610FLORENCE C
Solar/Wind Harmer
0.407
219348LDSOLAR C
Solar/Wind Harmer
0.176
219221BRL12CT1
Adder
2.62
219223BRL12CT3
Adder
2.62
219291REEVESSOUT C
Solar/Wind Harmer
0.018
972251AH1-710 GEN
Adder
13.877
228729W2-030 C
Solar/Wind Harmer
0.166
959561AF2-247 GEN
Solar/Wind Harmer
0.137
20716028EGP_W2-019
Solar/Wind Harmer
0.125
20720828JCB_W4-025
Solar/Wind Harmer
0.122
219727YARDVSOLFA C
Solar/Wind Harmer
0.247
20715028HAN_X4-015
Solar/Wind Harmer
0.08
20636028O CRK C1
Adder
1.864
219276PARKLANDSO C
Solar/Wind Harmer
0.123
213515CONOW3-4
50/50
0.747
213515CONOW3-4
50/50
0.747
213514CONOW1-2
50/50
0.56
213516CONOW5-6
50/50
0.56
233935AB2-179 C
Solar/Wind Harmer
1.165
231919CHRIST1
Adder
1.889
231920CHRIST2
Adder
1.847
971983AH1-536 GEN
Solar/Wind Harmer
3.085
232436AB1-176 C
Solar/Wind Harmer
0.093
233968AD2-076_GEN
Solar/Wind Harmer
2.668
970597AG2-380 GEN
Solar/Wind Harmer
1.675
231906DC3 NUG
Adder
5.55
231902DC CT7
Adder
4.437
231907DC10
Adder
1.385
213942SCHUYLKILL
Adder
1.31
213942SCHUYLKILL
Adder
1.002
213957STHWK3-4
Adder
0.993
213957STHWK3-4
Adder
0.993
232813VAUGHN
Adder
0.219
233955AB2-172 GEN
Solar/Wind Harmer
1.858
233923SMA
Solar/Wind Harmer
1.69
232912OH NUG1
Adder
3.209
232913OH NUG2
Adder
3.167
233990AG1-397 GEN
Solar/Wind Harmer
0.02
232432Z2-076 GEN
Solar/Wind Harmer
0.048
232920IR10
Adder
1.14
234033AF1-007_GEN
Solar/Wind Harmer
8.427
232904IR4
Adder
29.139
213561DLWR9-10
Adder
1.197
213561DLWR9-10
Adder
0.915
233973AC2-185 C
Solar/Wind Harmer
1.255
219137THOSOLAR C
Solar/Wind Harmer
0.377
219914AD2-027 C
Solar/Wind Harmer
0.185
971011AG2-627 GEN
Solar/Wind Harmer
2.329
228309CCLP NUG
Adder
7.816
228309CCLP NUG
Adder
7.434
964001AG1-254 GEN
Solar/Wind Harmer
0.614
972141AH1-641 GEN
Solar/Wind Harmer
0.862
228260V4-054C
Solar/Wind Harmer
0.305
971535AH1-265 GEN
Solar/Wind Harmer
1.258
219272CLEANLIGHT C
Solar/Wind Harmer
0.054
970453AG2-297 GEN
Solar/Wind Harmer
0.804
219607WPEMNERT C
Solar/Wind Harmer
0.123
219224BRL12CT4
Adder
2.62
219688LUMSOLAR_S C
Solar/Wind Harmer
0.059
228754AB1-001 C
Solar/Wind Harmer
0.04
227927V4-067C
Solar/Wind Harmer
0.057
214067T20SOLAR
Solar/Wind Harmer
0.073
213611FALLS1-3
Adder
1.02
213611FALLS1-3
Adder
1.02
20717128DIX_Z2-102
Solar/Wind Harmer
0.354
20715728PEM_W1-119
Solar/Wind Harmer
0.143
20715828PEM_W1-120
Solar/Wind Harmer
0.143
971189AH1-054 GEN
Solar/Wind Harmer
0.311
970025AG2-016 GEN
Solar/Wind Harmer
0.745
207459AE1-142 C O1
Solar/Wind Harmer
0.276
219620RIDERU C
Solar/Wind Harmer
0.015
20714328BYD_X4-031
Solar/Wind Harmer
0.072
20714428HOW_X1-037
Solar/Wind Harmer
0.313
971521AH1-258 GEN
Solar/Wind Harmer
0.679
20720428HOL_W1-112
Solar/Wind Harmer
0.087
218455CINNBAY_CGEN
Adder
0.449
20635928PARLN3&4
Adder
1.817
20675528CPH_W2-050
Solar/Wind Harmer
0.115
218526CNTRALGAS2 C
Solar/Wind Harmer
0.09
218524CNTRALGAS1 C
Solar/Wind Harmer
0.09
213589EDDYSTN4
Adder
31.553
213587EDDYSTN3
Adder
31.525
232416X2-083
Adder
0.191
233933AB2-153 GEN
Solar/Wind Harmer
0.464
233944AB2-135 GEN
Solar/Wind Harmer
2.13
234014AF1-036_GEN
Solar/Wind Harmer
1.089
231131BLOOM ENRGY
Adder
1.722
232424Y1-079 C
Solar/Wind Harmer
0.222
233984AB2-036 GEN
Solar/Wind Harmer
4.884
234041AC1-190 GEN
Solar/Wind Harmer
3.324
233987AB2-037 GEN
Solar/Wind Harmer
4.214
234036AF2-325 C
Solar/Wind Harmer
0.339
233946AB2-136 GEN
Solar/Wind Harmer
1.475
232926CRISFLD1
Adder
0.714
233901CHERRYDALE C
Solar/Wind Harmer
0.409
232408W1-005 C
Solar/Wind Harmer
0.364
232410W1-006 C
Solar/Wind Harmer
0.364
232918OH NUG7
Adder
3.188
232905CHERITON_25
Adder
0.892
971747AH1-380 GEN
Solar/Wind Harmer
1.301
972069AH1-584 GEN
Solar/Wind Harmer
3.252
972071AH1-585 GEN
Solar/Wind Harmer
3.252
231940T-011
Adder
0.271
970545AG2-347 GEN
Solar/Wind Harmer
23.583
232899W1-062
Adder
3.409
971149AH1-027 GEN
Solar/Wind Harmer
1.185
233939AC1-091 C
Solar/Wind Harmer
0.305
233970AC1-092 C
Solar/Wind Harmer
0.305
972233AH1-701 GEN
Adder
1.297
213815MOSER1-3
Adder
1.102
213815MOSER1-3
Adder
1.102
228304LOGAN
Adder
7.467
228307PCLP GT
Adder
3.712
219921AF1-264
Solar/Wind Harmer
0.044
228251CARLLS#4
Adder
0.187
219615MILLCREEK C
Solar/Wind Harmer
0.071
230433AD2-135 GEN
Solar/Wind Harmer
0.03
230407AD2-065 C
Solar/Wind Harmer
0.039
213535CROYDN11
Adder
3.017
230422AE1-104_GEN1
Solar/Wind Harmer
9.748
230425AE1-104_GEN2
Solar/Wind Harmer
9.748
219114HARTZY_C
Solar/Wind Harmer
0.229
20716428NHV_W2-082
Solar/Wind Harmer
0.478
207500AE2-000G1
Solar/Wind Harmer
8.307
207497AE2-000G2
Solar/Wind Harmer
8.307
207507AE2-000G3
Solar/Wind Harmer
8.307
20636128O CRK C2
Adder
1.7
20714928UPF_X1-085
Solar/Wind Harmer
0.108
963401AG1-189 GEN
Solar/Wind Harmer
0.303
963391AG1-188 GEN
Solar/Wind Harmer
0.504
20628028LAKEHURS
Adder
0.248
219817TRENTONSOL C
Solar/Wind Harmer
0.287
20720628TIN_W1-124
Solar/Wind Harmer
0.252
20641628MLH_W1-032
Solar/Wind Harmer
0.074
20716928W4-060COL
Solar/Wind Harmer
0.176
924131AB2-057 GEN
Solar/Wind Harmer
0.254
218440SUMMTASSOC C
Solar/Wind Harmer
0.031
20673828FLE_V3-070
Solar/Wind Harmer
0.111
218418LINDEN_G5
Adder
4.119
218419LINDEN_G6
Adder
4.119
972260AH1-715 GEN1
Adder
3.298
207442AE1-156 GEN
Solar/Wind Harmer
0.178
20676128MHD_W3-029
Solar/Wind Harmer
0.114
219036LINDEN_G7
Adder
3.972
219035LINDEN_G8
Adder
3.915
972261AH1-715 GEN2
Adder
3.802
213518CONOW8-9
50/50
1.011
213514CONOW1-2
50/50
0.747
213516CONOW5-6
50/50
0.747
231918WEST 1
Adder
1.45
231917EM10
Adder
1.012
213497CHSTR7-9
Adder
1.078
213497CHSTR7-9
Adder
1.078
233930AB2-032 GEN
Solar/Wind Harmer
0.344
233915AB1-141 GEN
Solar/Wind Harmer
0.409
232422X3-066 FULL
Solar/Wind Harmer
0.101
234012AE2-112_GEN
Solar/Wind Harmer
0.926
213958STHWK5-6
Adder
0.993
232910NRG_G1
Adder
3.257
233964AF2-378 GEN
Solar/Wind Harmer
0.047
232426Y1-080 FULL
Solar/Wind Harmer
0.07
970277AG2-181 GEN
Solar/Wind Harmer
1.849
965821AG1-450 GEN
Solar/Wind Harmer
1.918
232919VN10
Adder
1.031
233954AC2-188 GEN
Solar/Wind Harmer
0.411
233950AC2-186 GEN
Solar/Wind Harmer
0.206
232428Y3-058 C
Solar/Wind Harmer
0.304
971195AH1-057 GEN
Solar/Wind Harmer
0.398
233998TM1NIN_3.36
Solar/Wind Harmer
0.461
232404W1-003 C
Solar/Wind Harmer
0.364
232917OH NUG6
Adder
3.195
232915OH NUG4
Adder
3.188
232434Z2-077 GEN
Solar/Wind Harmer
0.09
972177AH1-672 GEN
Solar/Wind Harmer
4.835
213560DLW11-12
Adder
0.915
232900DEMECSMY
Adder
3.27
232901NORTHST
Adder
2.913
233972AC1-094 C
Solar/Wind Harmer
0.23
219258KINSLEYDEP C
Solar/Wind Harmer
0.1
219904AC1-010 C
Solar/Wind Harmer
0.117
219907AC1-030 C
Solar/Wind Harmer
0.042
228351V2-046C
Solar/Wind Harmer
0.608
230434AG1-499 GEN
Solar/Wind Harmer
0.175
970997AG2-616 GEN
Solar/Wind Harmer
2.874
945431AF1-208 GEN
Solar/Wind Harmer
2.575
230511AF1-262
Solar/Wind Harmer
0.055
228728W1-130C
Solar/Wind Harmer
0.196
228206SHRMN CT
Adder
4.854
219304NAMERICA C
Solar/Wind Harmer
0.091
219222BRL12CT2
Adder
2.62
228732V1-021 C
Adder
0.055
218660EHAMPSOLAR C
Solar/Wind Harmer
0.051
219686LUMSOLAR_N C
Solar/Wind Harmer
0.059
219287REEVESEAST C
Solar/Wind Harmer
0.39
214194N WALES4
Adder
0.246
213611FALLS1-3
Adder
1.02
20720728JCB_W1-129
Solar/Wind Harmer
0.08
207522AF2-254 C
Solar/Wind Harmer
0.386
207487AE2-000G4
Solar/Wind Harmer
8.307
207445AB1-138_GEN
Solar/Wind Harmer
0.151
20628028LAKEHURS
Adder
0.491
963711AG1-223 GEN
Solar/Wind Harmer
0.381
20714828MDF_W3-079
Solar/Wind Harmer
0.079
219680HOPEWELLV C1
Solar/Wind Harmer
0.02
207454AA2-184 E
Solar/Wind Harmer
0.253
20715228NPK_W1-113
Solar/Wind Harmer
0.108
217197RE CRAN C
Solar/Wind Harmer
0.136
20742028HF_AC1-207
Solar/Wind Harmer
0.197
20635828PARLN1&2
Adder
1.817
20635028RRCT1&2
Adder
2.833
20635128RRCT3&4
Adder
2.735
218428ETC SOLAR C
Solar/Wind Harmer
0.009
217213AMBOY SO C
Solar/Wind Harmer
0.031
972275AH1-722 GEN
Adder
7.572
207528AF2-192 GEN
Solar/Wind Harmer
0.133
20673628F1S_V4-069
Solar/Wind Harmer
0.043
20675428EAM_W2-061
Solar/Wind Harmer
0.045
20676428JCR_X2-075
Solar/Wind Harmer
0.082
218449LINSOLAR C
Solar/Wind Harmer
0.239
208909MACR G3
Adder
32.41
223401AF1-299 GEN
Solar/Wind Helper
0.27
971667AH1-334 GEN
Solar/Wind Harmer
0.719
20714528FRN_Y2-051
Solar/Wind Harmer
0.076
219918AC2-009 C
Solar/Wind Harmer
0.016
20716228APLW2-078
Solar/Wind Harmer
0.223
20720528MAN_W1-024
Solar/Wind Harmer
0.064
219612MATRIX C
Solar/Wind Harmer
0.047
218438BLK ROCK C
Solar/Wind Harmer
0.035
967451AG2-055 C O1
Solar/Wind Harmer
42.856
20635828PARLN1&2
Adder
0.823
20635928PARLN3&4
Adder
0.823
20635028RRCT1&2
Adder
2.878
20635128RRCT3&4
Adder
2.386
219908AB1-139 C
Solar/Wind Harmer
0.092
219919AE1-041 FULL
Solar/Wind Harmer
0.01
219249CENTRALDIV C
Solar/Wind Harmer
0.01
20673728F2S_V4-070
Solar/Wind Harmer
0.043
223402AF1-300 C
Solar/Wind Helper
0.27
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.016
G-007ALTFEXP_G-007A->PJM
CMTX
12.515
CBM NorthLTFEXP_CBM-N->PJM
CBM
16.193
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.822
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.562
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
31.768
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.597
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
3.874

Details for COOPER-GRACETON 230.0 kV Ckt 1 line l/o PECO_P1-2_5012_SRT-A


Base Case Flowgate

Area:BGE/PECO
Facility Description:
COOPER-GRACETON 230.0 kV Ckt 1 line
Contingency Name:
PECO_P1-2_5012_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.51 %
Rating:578.0 MVA
Rating Type:B
MVA to Mitigate:661.85
MW Contribution:1.62
Bus #Bus NameTypeMW Contribution
231909HR2
50/50
0.609
231908HR1
50/50
0.606
231910HR3
50/50
0.606
213589EDDYSTN4
Adder
31.437
213587EDDYSTN3
Adder
31.41
232416X2-083
Adder
0.19
233933AB2-153 GEN
Solar/Wind Harmer
0.001
233944AB2-135 GEN
Solar/Wind Harmer
0.002
234014AF1-036_GEN
Solar/Wind Harmer
0.932
231131BLOOM ENRGY
Adder
1.715
232424Y1-079 C
Solar/Wind Harmer
0
233984AB2-036 GEN
Solar/Wind Harmer
2.839
234041AC1-190 GEN
Solar/Wind Harmer
2.694
233987AB2-037 GEN
Solar/Wind Harmer
0.004
234036AF2-325 C
Solar/Wind Harmer
0
233946AB2-136 GEN
Solar/Wind Harmer
0.001
232926CRISFLD1
Adder
0.711
233901CHERRYDALE C
Solar/Wind Harmer
0
232408W1-005 C
Solar/Wind Harmer
0.234
232410W1-006 C
Solar/Wind Harmer
0.234
232905CHERITON_25
Adder
0.888
232918OH NUG7
Adder
3.174
971747AH1-380 GEN
Solar/Wind Harmer
0.904
972069AH1-584 GEN
Solar/Wind Harmer
2.259
972071AH1-585 GEN
Solar/Wind Harmer
2.259
231940T-011
Adder
0.269
970545AG2-347 GEN
Solar/Wind Harmer
9.059
213508CON10-11
50/50
1.01
213518CONOW8-9
50/50
1.01
213517CONOW7
50/50
0.746
213890PHLISCT3
50/50
0.935
213888PHLISCT1
50/50
0.934
213739LIBE_CT2
50/50
0.778
213497CHSTR7-9
Adder
1.074
233982AB2-133 GEN
Solar/Wind Harmer
0.002
233918AB1-142 GEN
Solar/Wind Harmer
0.106
213958STHWK5-6
Adder
0.989
232417X3-008 C
Solar/Wind Harmer
0
960671AF2-358 GEN
Solar/Wind Harmer
4.583
232907VN8
Adder
10.963
233952AC2-187 GEN
Solar/Wind Harmer
0
233994AC2-023 GEN
Solar/Wind Harmer
0.002
233940AF2-379 C
Solar/Wind Harmer
0
233900O-025 C
Adder
0.427
234015AF2-250 C
Solar/Wind Harmer
0
213515CONOW3-4
50/50
0.746
213515CONOW3-4
50/50
0.746
213514CONOW1-2
50/50
0.56
213516CONOW5-6
50/50
0.56
213893PHLISST1
50/50
1.345
231916EM3
50/50
0.419
231919CHRIST1
50/50
1.997
231920CHRIST2
50/50
1.953
231901EM4
50/50
0.843
213740LIBE_ST1
50/50
1.071
231505HR4
50/50
0.884
233935AB2-179 C
Solar/Wind Harmer
0.64
971983AH1-536 GEN
Solar/Wind Harmer
0.727
232436AB1-176 C
Solar/Wind Harmer
0
233968AD2-076_GEN
Solar/Wind Harmer
0.932
970597AG2-380 GEN
Solar/Wind Harmer
1.669
231906DC3 NUG
Adder
5.528
231902DC CT7
Adder
4.419
231907DC10
Adder
1.38
213942SCHUYLKILL
Adder
1.305
213942SCHUYLKILL
Adder
0.998
213957STHWK3-4
Adder
0.989
213957STHWK3-4
Adder
0.989
232813VAUGHN
Adder
0.218
233955AB2-172 GEN
Solar/Wind Harmer
0.001
233923SMA
Solar/Wind Harmer
0.002
232912OH NUG1
Adder
3.196
232913OH NUG2
Adder
3.153
233990AG1-397 GEN
Solar/Wind Harmer
-0.058
232432Z2-076 GEN
Solar/Wind Harmer
0.005
232920IR10
Adder
1.135
234033AF1-007_GEN
Solar/Wind Harmer
0
232904IR4
Adder
29.014
213561DLWR9-10
Adder
1.191
213561DLWR9-10
Adder
0.911
233973AC2-185 C
Solar/Wind Harmer
0.001
219914AD2-027 C
Solar/Wind Harmer
0
971011AG2-627 GEN
Solar/Wind Harmer
1.617
228309CCLP NUG
Adder
7.778
228309CCLP NUG
Adder
7.399
964001AG1-254 GEN
Solar/Wind Harmer
0.117
972141AH1-641 GEN
Solar/Wind Harmer
0.998
228260V4-054C
Solar/Wind Harmer
0
971535AH1-265 GEN
Solar/Wind Harmer
0.809
219272CLEANLIGHT C
Solar/Wind Harmer
0
970453AG2-297 GEN
Solar/Wind Harmer
0.739
219607WPEMNERT C
Solar/Wind Harmer
0
219224BRL12CT4
Adder
2.607
219688LUMSOLAR_S C
Solar/Wind Harmer
0
228754AB1-001 C
Solar/Wind Harmer
0
227927V4-067C
Solar/Wind Harmer
0
214067T20SOLAR
Solar/Wind Harmer
0
213611FALLS1-3
Adder
1.014
213611FALLS1-3
Adder
1.014
20717128DIX_Z2-102
Solar/Wind Harmer
0
20715728PEM_W1-119
Solar/Wind Harmer
0
20715828PEM_W1-120
Solar/Wind Harmer
0
971189AH1-054 GEN
Solar/Wind Harmer
0.2
970025AG2-016 GEN
Solar/Wind Harmer
0.479
207459AE1-142 C O1
Solar/Wind Harmer
0
20714328BYD_X4-031
Solar/Wind Harmer
0.038
20714428HOW_X1-037
Solar/Wind Harmer
0
971521AH1-258 GEN
Solar/Wind Harmer
0.436
20720428HOL_W1-112
Solar/Wind Harmer
0
218455CINNBAY_CGEN
Adder
0.446
20635928PARLN3&4
Adder
1.806
218526CNTRALGAS2 C
Solar/Wind Harmer
0.186
218524CNTRALGAS1 C
Solar/Wind Harmer
0.184
232899W1-062
Adder
3.394
971149AH1-027 GEN
Solar/Wind Harmer
1.089
233939AC1-091 C
Solar/Wind Harmer
0.001
233970AC1-092 C
Solar/Wind Harmer
0.001
972233AH1-701 GEN
Adder
1.291
213815MOSER1-3
Adder
1.097
213815MOSER1-3
Adder
1.097
228304LOGAN
Adder
7.432
228307PCLP GT
Adder
3.695
219921AF1-264
Solar/Wind Harmer
0
228251CARLLS#4
Adder
0.186
219615MILLCREEK C
Solar/Wind Harmer
0
230407AD2-065 C
Solar/Wind Harmer
0
213535CROYDN11
Adder
3.002
230422AE1-104_GEN1
Solar/Wind Harmer
3.894
230425AE1-104_GEN2
Solar/Wind Harmer
3.894
219114HARTZY_C
Solar/Wind Harmer
0
20716428NHV_W2-082
Solar/Wind Harmer
0
207500AE2-000G1
Solar/Wind Harmer
3.316
207497AE2-000G2
Solar/Wind Harmer
3.316
207507AE2-000G3
Solar/Wind Harmer
3.316
20636128O CRK C2
Adder
1.69
20714928UPF_X1-085
Solar/Wind Harmer
0
20628028LAKEHURS
Adder
0.247
20720628TIN_W1-124
Solar/Wind Harmer
0
20716928W4-060COL
Solar/Wind Harmer
0
218440SUMMTASSOC C
Solar/Wind Harmer
0
20673828FLE_V3-070
Solar/Wind Harmer
0
218418LINDEN_G5
Adder
4.092
218419LINDEN_G6
Adder
4.092
972260AH1-715 GEN1
Adder
3.277
207442AE1-156 GEN
Solar/Wind Harmer
0.014
20676128MHD_W3-029
Solar/Wind Harmer
0
233996TM1833_GEN
Solar/Wind Harmer
0.001
233997TMININ_4.2
Solar/Wind Harmer
0.001
232406W1-004 FULL
Solar/Wind Harmer
0.234
232921TASLEY2G
Adder
1.868
232914OH NUG3
Adder
3.196
232916OH NUG5
Adder
3.196
233990AG1-397 GEN
Solar/Wind Harmer
0.493
972073AH1-586 GEN
Solar/Wind Harmer
3.388
972133AH1-634 GEN
Solar/Wind Harmer
1.323
213560DLW11-12
Adder
0.911
233971AC1-093 C
Solar/Wind Harmer
0.015
970695AG2-447 GEN
Solar/Wind Harmer
0.865
213815MOSER1-3
Adder
1.097
228304LOGAN
Adder
6.684
219766PARADISE C
Solar/Wind Harmer
0
219912AD2-042 GEN
Solar/Wind Harmer
0
219623KINSLEYBEA C
Solar/Wind Harmer
0
230430AE1-229_GEN
Solar/Wind Harmer
0.005
219906AC1-017 C
Solar/Wind Harmer
0
230415AB2-049 C
Solar/Wind Harmer
0
971553AH1-274 GEN
Solar/Wind Harmer
0.457
228711V2-041C
Solar/Wind Harmer
0
228202CUMB CT
Adder
4.799
219610FLORENCE C
Solar/Wind Harmer
0
219348LDSOLAR C
Solar/Wind Harmer
0
219221BRL12CT1
Adder
2.607
219223BRL12CT3
Adder
2.607
972251AH1-710 GEN
Adder
13.808
228729W2-030 C
Solar/Wind Harmer
0
20716028EGP_W2-019
Solar/Wind Harmer
0
20720828JCB_W4-025
Solar/Wind Harmer
0
219727YARDVSOLFA C
Solar/Wind Harmer
0
20715028HAN_X4-015
Solar/Wind Harmer
0
20636028O CRK C1
Adder
1.854
219276PARKLANDSO C
Solar/Wind Harmer
0
971667AH1-334 GEN
Solar/Wind Harmer
0.462
20714528FRN_Y2-051
Solar/Wind Harmer
0
20716228APLW2-078
Solar/Wind Harmer
0
20720528MAN_W1-024
Solar/Wind Harmer
0
219612MATRIX C
Solar/Wind Harmer
0
218438BLK ROCK C
Solar/Wind Harmer
0
967451AG2-055 C O1
Solar/Wind Harmer
60.853
20635828PARLN1&2
Adder
0.818
20635928PARLN3&4
Adder
0.818
20635028RRCT1&2
Adder
2.86
20635128RRCT3&4
Adder
2.371
219908AB1-139 C
Solar/Wind Harmer
0
20673728F2S_V4-070
Solar/Wind Harmer
0
223402AF1-300 C
Solar/Wind Helper
0.271
213508CON10-11
50/50
1.01
213518CONOW8-9
50/50
1.01
213514CONOW1-2
50/50
0.746
213516CONOW5-6
50/50
0.746
231918WEST 1
50/50
1.533
213889PHLISCT2
50/50
0.934
231917EM10
50/50
1.07
213738LIBE_CT1
50/50
0.778
213497CHSTR7-9
Adder
1.074
213497CHSTR7-9
Adder
1.074
233930AB2-032 GEN
Solar/Wind Harmer
0.394
233915AB1-141 GEN
Solar/Wind Harmer
0.106
232422X3-066 FULL
Solar/Wind Harmer
0.034
234012AE2-112_GEN
Solar/Wind Harmer
0.932
213958STHWK5-6
Adder
0.989
232910NRG_G1
Adder
3.243
233964AF2-378 GEN
Solar/Wind Harmer
0
232426Y1-080 FULL
Solar/Wind Harmer
0
970277AG2-181 GEN
Solar/Wind Harmer
0.214
965821AG1-450 GEN
Solar/Wind Harmer
1.909
232919VN10
Adder
1.027
233954AC2-188 GEN
Solar/Wind Harmer
0
233950AC2-186 GEN
Solar/Wind Harmer
0
232428Y3-058 C
Solar/Wind Harmer
0.001
971195AH1-057 GEN
Solar/Wind Harmer
0.226
233998TM1NIN_3.36
Solar/Wind Harmer
0.001
232404W1-003 C
Solar/Wind Harmer
0.234
232917OH NUG6
Adder
3.182
232915OH NUG4
Adder
3.174
232434Z2-077 GEN
Solar/Wind Harmer
0.015
972177AH1-672 GEN
Solar/Wind Harmer
3.649
213560DLW11-12
Adder
0.911
232900DEMECSMY
Adder
3.256
232901NORTHST
Adder
2.9
233972AC1-094 C
Solar/Wind Harmer
0.109
219258KINSLEYDEP C
Solar/Wind Harmer
0
219904AC1-010 C
Solar/Wind Harmer
0
219907AC1-030 C
Solar/Wind Harmer
0
228351V2-046C
Solar/Wind Harmer
0
230434AG1-499 GEN
Solar/Wind Harmer
0
970997AG2-616 GEN
Solar/Wind Harmer
2.151
945431AF1-208 GEN
Solar/Wind Harmer
1.788
230511AF1-262
Solar/Wind Harmer
0
228728W1-130C
Solar/Wind Harmer
0
228206SHRMN CT
Adder
4.83
219304NAMERICA C
Solar/Wind Harmer
0.027
219222BRL12CT2
Adder
2.607
228732V1-021 C
Adder
0.055
218660EHAMPSOLAR C
Solar/Wind Harmer
0
219686LUMSOLAR_N C
Solar/Wind Harmer
0
219287REEVESEAST C
Solar/Wind Harmer
0
214194N WALES4
Adder
0.245
213611FALLS1-3
Adder
1.014
20720728JCB_W1-129
Solar/Wind Harmer
0
207522AF2-254 C
Solar/Wind Harmer
0.248
207487AE2-000G4
Solar/Wind Harmer
3.316
207445AB1-138_GEN
Solar/Wind Harmer
0
20628028LAKEHURS
Adder
0.489
20714828MDF_W3-079
Solar/Wind Harmer
0.025
207454AA2-184 E
Solar/Wind Harmer
0
20715228NPK_W1-113
Solar/Wind Harmer
0
217197RE CRAN C
Solar/Wind Harmer
0
20742028HF_AC1-207
Solar/Wind Harmer
0
20635828PARLN1&2
Adder
1.806
20635028RRCT1&2
Adder
2.816
20635128RRCT3&4
Adder
2.718
217213AMBOY SO C
Solar/Wind Harmer
0
972275AH1-722 GEN
Adder
7.523
207528AF2-192 GEN
Solar/Wind Harmer
0
20673628F1S_V4-069
Solar/Wind Harmer
0
20675428EAM_W2-061
Solar/Wind Harmer
0
208909MACR G3
Adder
32.152
223401AF1-299 GEN
Solar/Wind Helper
0.271
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.034
G-007ALTFEXP_G-007A->PJM
CMTX
12.437
CBM NorthLTFEXP_CBM-N->PJM
CBM
16.035
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.84
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.618
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
31.56
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.609
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
3.958

Details for KEYSTONE-01CABOT 500.0 kV Ckt 1 line l/o AP_P2-3_WP-500-DRT45_SRT-SL


Base Case Flowgate

Area:AP/PJM
Facility Description:
KEYSTONE-01CABOT 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-500-DRT45_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.06 %
Rating:2844.0 MVA
Rating Type:B
MVA to Mitigate:3073.32
MW Contribution:5.13
Bus #Bus NameTypeMW Contribution
200033KEYS G2
50/50
9.728
235621AD2-113 G3
50/50
4.303
235622AD2-113 G4
50/50
4.303
972299AH1-734 GEN
50/50
109.978
200031CONE G2
50/50
7.97
200031CONE G2
50/50
7.417
20088626ARWF_N39
Solar/Wind Harmer
3.078
20303426NA_O38_P22
Solar/Wind Harmer
2.492
209137AF2-361 C
Solar/Wind Harmer
3.206
209130AF1-271A GEN
Solar/Wind Harmer
2.72
946751AF1-339 GEN
Solar/Wind Harmer
0.966
209054AE2-059 GEN
Solar/Wind Harmer
1.626
209059AE2-084 GEN
Solar/Wind Harmer
2.4
961431AF2-434 GEN
Solar/Wind Harmer
0.945
961541AF2-445A GEN
Solar/Wind Harmer
3.071
203857AF2-221 C
Solar/Wind Harmer
2.286
970123AG2-090 GEN
Solar/Wind Harmer
2.134
971441AH1-212 GEN
Solar/Wind Harmer
2.981
203940AF1-140 C
Solar/Wind Harmer
0.735
208972BECR K09
Solar/Wind Harmer
0.96
203839AF1-321 GEN
Solar/Wind Harmer
2.966
20084626FORWARD
Solar/Wind Harmer
1.171
211065PSPA IPP
Solar/Wind Harmer
0.389
211065PSPA IPP
Solar/Wind Harmer
0.389
209029WAYMART-WD
Solar/Wind Harmer
2.562
209009PEIP 2
Adder
6.957
209010PEIP 1
Adder
3.152
209010PEIP 1
Adder
0.462
966111AG1-480 GEN
Solar/Wind Harmer
0.072
966111AG1-480 GEN
Solar/Wind Harmer
2.738
20465127PORT CT
Adder
3.267
20674128FR_U2-059
Solar/Wind Harmer
0.151
20634528N27_Y2-018
Solar/Wind Harmer
0.218
964851AG1-348 GEN
Solar/Wind Harmer
1.423
207471AF2-354 C
Solar/Wind Harmer
0.412
20674928WA_W3-044
Solar/Wind Harmer
0.388
20676228FRD_X1-012
Solar/Wind Harmer
0.472
946071AF1-272 GEN
Solar/Wind Harmer
4.593
217204WCALDSOLAR C
Solar/Wind Harmer
0.056
217086KRNY_131
Adder
7.123
217083KRNY_132
Adder
7.063
217206BARNGR HS C
Solar/Wind Harmer
0.024
217201HACKENSOLA C
Solar/Wind Harmer
0.056
972237AH1-703 GEN
Adder
7.734
20674528F3S_W2-016
Solar/Wind Harmer
1.079
217202FBANKSOLAR C
Solar/Wind Harmer
0.056
20671828STAW2-080
Solar/Wind Harmer
0.08
217081WEATEXAS C
Solar/Wind Harmer
0.065
219036LINDEN_G7
Adder
12.627
219035LINDEN_G8
Adder
12.447
972261AH1-715 GEN2
Adder
12.087
207442AE1-156 GEN
Solar/Wind Harmer
0.56
20676128MHD_W3-029
Solar/Wind Harmer
0.359
218418LINDEN_G5
Adder
12.876
218419LINDEN_G6
Adder
12.876
972260AH1-715 GEN1
Adder
10.31
20673828FLE_V3-070
Solar/Wind Harmer
0.343
218440SUMMTASSOC C
Solar/Wind Harmer
0.095
20088926STNY CRK
Solar/Wind Harmer
1.661
971427AH1-205 GEN
Solar/Wind Harmer
2.004
924131AB2-057 GEN
Solar/Wind Harmer
0.757
20716928W4-060COL
Solar/Wind Harmer
0.519
20720628TIN_W1-124
Solar/Wind Harmer
0.717
20641628MLH_W1-032
Solar/Wind Harmer
0.211
20465527S.RDG CT
Adder
2.192
20478527GLRA_Q45
Adder
0.279
219817TRENTONSOL C
Solar/Wind Harmer
0.788
20628028LAKEHURS
Adder
0.671
20714928UPF_X1-085
Solar/Wind Harmer
0.286
963391AG1-188 GEN
Solar/Wind Harmer
1.344
219114HARTZY_C
Solar/Wind Harmer
0.586
963401AG1-189 GEN
Solar/Wind Harmer
0.805
207500AE2-000G1
Solar/Wind Harmer
21.99
207497AE2-000G2
Solar/Wind Harmer
21.99
207507AE2-000G3
Solar/Wind Harmer
21.99
20636128O CRK C2
Adder
4.499
20716428NHV_W2-082
Solar/Wind Harmer
1.237
213535CROYDN11
Adder
7.015
219615MILLCREEK C
Solar/Wind Harmer
0.163
213815MOSER1-3
Adder
2.423
213815MOSER1-3
Adder
2.423
219921AF1-264
Solar/Wind Harmer
0.098
230407AD2-065 C
Solar/Wind Harmer
0.089
230422AE1-104_GEN1
Solar/Wind Harmer
22.608
200032KEYS G1
50/50
9.37
200030CONE G1
50/50
8.067
200105AA1-076 ST
50/50
6.749
20079426CONEMAGH
50/50
1.974
972241AH1-705 GEN
Adder
5.87
209071AE2-133 GEN
Solar/Wind Harmer
1.638
970665AG2-430 GEN
Solar/Wind Harmer
9.601
209018SUNBIPCT
Adder
7.207
946731AF1-337 GEN
Solar/Wind Harmer
0.966
212507AE2-042_GEN
Solar/Wind Harmer
2.88
961341AF2-425 GEN
Solar/Wind Harmer
0.946
212174INGE
Adder
1.045
212266LOR1
Solar/Wind Harmer
0.123
970237AG2-161 GEN
Solar/Wind Harmer
3.283
970125AG2-091 GEN
Solar/Wind Harmer
0.915
971879AH1-460 GEN
Solar/Wind Harmer
9.943
961301AF2-421 GEN
Solar/Wind Harmer
0.907
963151AG1-164 GEN
Solar/Wind Harmer
0.907
209023WIENIPP1
Adder
9.782
209025WIENIPP3
Adder
4.883
203841AF2-001_GEN
Solar/Wind Harmer
2.966
209010PEIP 1
Adder
0.573
208909MACR G3
Adder
132.56
20465127PORT CT
Adder
2.462
20671928W4-073
Solar/Wind Harmer
0.354
207518AF1-320_GEN
Solar/Wind Harmer
2.977
207437AD2-070 GEN
Solar/Wind Harmer
0.246
971519AH1-257 GEN
Solar/Wind Harmer
2.043
966181AG1-487 GEN
Solar/Wind Harmer
3.061
20675828AU_W4-064
Solar/Wind Harmer
0.139
207439AE1-081 C O1
Solar/Wind Harmer
0.047
20674328GAR_V4-001
Solar/Wind Harmer
0.088
217208PARK ELE C
Solar/Wind Harmer
0.019
217083KRNY_132
Adder
7.108
217121ECCF
Adder
0.332
217209CENTRL HS C
Solar/Wind Harmer
0.034
218449LINSOLAR C
Solar/Wind Harmer
0.759
20676428JCR_X2-075
Solar/Wind Harmer
0.258
207528AF2-192 GEN
Solar/Wind Harmer
0.417
20673628F1S_V4-069
Solar/Wind Harmer
0.135
20675428EAM_W2-061
Solar/Wind Harmer
0.142
972275AH1-722 GEN
Adder
23.671
217213AMBOY SO C
Solar/Wind Harmer
0.095
218428ETC SOLAR C
Solar/Wind Harmer
0.027
205941AD2-115 GEN
Solar/Wind Harmer
0.762
209008PAXT IPP
Adder
1.79
20635028RRCT1&2
Adder
8.57
20635128RRCT3&4
Adder
8.273
971419AH1-201 GEN
Solar/Wind Harmer
4.308
20635828PARLN1&2
Adder
5.444
971541AH1-268 GEN
Solar/Wind Harmer
4.702
217197RE CRAN C
Solar/Wind Harmer
0.391
20742028HF_AC1-207
Solar/Wind Harmer
0.566
20467927PC_Q59Y356
Adder
0.693
20715228NPK_W1-113
Solar/Wind Harmer
0.31
207454AA2-184 E
Solar/Wind Harmer
0.719
20465527S.RDG CT
Adder
2.266
219680HOPEWELLV C1
Solar/Wind Harmer
0.055
20714828MDF_W3-079
Solar/Wind Harmer
0.218
963711AG1-223 GEN
Solar/Wind Harmer
1.052
207445AB1-138_GEN
Solar/Wind Harmer
0.409
20628028LAKEHURS
Adder
1.326
207487AE2-000G4
Solar/Wind Harmer
21.99
207522AF2-254 C
Solar/Wind Harmer
0.999
20720728JCB_W1-129
Solar/Wind Harmer
0.208
213611FALLS1-3
Adder
2.448
214194N WALES4
Adder
0.59
219304NAMERICA C
Solar/Wind Harmer
0.213
219222BRL12CT2
Adder
6.121
219287REEVESEAST C
Solar/Wind Harmer
0.914
219686LUMSOLAR_N C
Solar/Wind Harmer
0.138
219907AC1-030 C
Solar/Wind Harmer
0.095
218660EHAMPSOLAR C
Solar/Wind Harmer
0.119
219904AC1-010 C
Solar/Wind Harmer
0.256
219258KINSLEYDEP C
Solar/Wind Harmer
0.219
213560DLW11-12
Adder
1.839
228728W1-130C
Solar/Wind Harmer
0.446
230434AG1-499 GEN
Solar/Wind Harmer
0.389
230511AF1-262
Solar/Wind Harmer
0.123
228732V1-021 C
Adder
0.127
228351V2-046C
Solar/Wind Harmer
1.348
970997AG2-616 GEN
Solar/Wind Harmer
6.412
945431AF1-208 GEN
Solar/Wind Harmer
5.769
213958STHWK5-6
Adder
1.826
228206SHRMN CT
Adder
11.063
213497CHSTR7-9
Adder
1.807
213497CHSTR7-9
Adder
1.807
970679AG2-439 GEN
Solar/Wind Harmer
1.227
205967AE2-211_GEN
Solar/Wind Harmer
7.042
231917EM10
Adder
1.625
231918WEST 1
Adder
2.309
233972AC1-094 C
Solar/Wind Harmer
0.455
232901NORTHST
Adder
5.707
232900DEMECSMY
Adder
6.325
972177AH1-672 GEN
Solar/Wind Harmer
9.202
233954AC2-188 GEN
Solar/Wind Harmer
0.771
233950AC2-186 GEN
Solar/Wind Harmer
0.386
232434Z2-077 GEN
Solar/Wind Harmer
0.171
232910NRG_G1
Adder
5.912
232404W1-003 C
Solar/Wind Harmer
0.686
232917OH NUG6
Adder
6.019
232915OH NUG4
Adder
6.006
971195AH1-057 GEN
Solar/Wind Harmer
0.749
233998TM1NIN_3.36
Solar/Wind Harmer
0.867
232428Y3-058 C
Solar/Wind Harmer
0.571
965821AG1-450 GEN
Solar/Wind Harmer
3.563
232919VN10
Adder
1.92
232426Y1-080 FULL
Solar/Wind Harmer
0.131
200104AA1-076 CT2
50/50
5.953
200103AA1-076 CT1
50/50
5.902
20083726HOMER C1
Adder
119.436
203961AE2-224 GEN
Solar/Wind Harmer
5.066
959431AF2-234 GEN
Solar/Wind Harmer
1.935
964051AG1-259 GEN
Solar/Wind Harmer
1.298
964061AG1-260 GEN
Solar/Wind Harmer
1.298
959421AF2-233 GEN
Solar/Wind Harmer
0.968
209045AE2-271 GEN
Solar/Wind Harmer
15.932
20092526R32
Solar/Wind Harmer
2.679
209026WIENIPP4
Adder
4.833
203850AG1-041 C
Solar/Wind Harmer
1.758
203844AF2-092 C
Solar/Wind Harmer
1.75
961261AF2-417 GEN
Solar/Wind Harmer
0.878
209116AE2-175 GEN
Solar/Wind Harmer
3.49
941231AE2-117 GEN
Solar/Wind Harmer
0.862
20091526CHSTN_FL
Solar/Wind Harmer
1.261
966421AG1-511 GEN
Solar/Wind Harmer
7.075
20462827N BANGR8
Adder
0.588
20675128HRM_W1-127
Solar/Wind Harmer
0.139
207408W3-077 C
Solar/Wind Harmer
0.412
20675728RH_W2-091
Solar/Wind Harmer
0.279
207484AF2-139 C O1
Solar/Wind Harmer
0.412
971009AG2-626 GEN
Solar/Wind Harmer
1.327
20675928HOL_W4-097
Solar/Wind Harmer
0.106
20674828DL_W4-046
Solar/Wind Harmer
0.52
207511W3-106 GEN
Solar/Wind Harmer
0.523
20676328BVR_Y1-020
Solar/Wind Harmer
0.263
207530AG1-191 GEN
Solar/Wind Harmer
1.095
966261AG1-495 GEN
Solar/Wind Harmer
1.401
217167KRNY_14
Adder
7.108
217086KRNY_131
Adder
7.048
217147KRNY_1212
Adder
6.761
217147KRNY_1212
Adder
6.64
217146KRNY_1234
Adder
6.625
217146KRNY_1234
Adder
6.58
218404KENILWRTH C
Adder
0.995
218524CNTRALGAS1 C
Solar/Wind Harmer
0.275
20675528CPH_W2-050
Solar/Wind Harmer
0.348
218526CNTRALGAS2 C
Solar/Wind Harmer
0.275
218455CINNBAY_CGEN
Adder
1.337
20635928PARLN3&4
Adder
5.444
20720428HOL_W1-112
Solar/Wind Harmer
0.251
971521AH1-258 GEN
Solar/Wind Harmer
1.959
20486527WR_V4-052
Adder
0.884
20714428HOW_X1-037
Solar/Wind Harmer
0.887
20714328BYD_X4-031
Solar/Wind Harmer
0.203
219620RIDERU C
Solar/Wind Harmer
0.04
207459AE1-142 C O1
Solar/Wind Harmer
0.743
971189AH1-054 GEN
Solar/Wind Harmer
0.827
970025AG2-016 GEN
Solar/Wind Harmer
1.985
208862AG1-362 C
Solar/Wind Harmer
0.662
20715728PEM_W1-119
Solar/Wind Harmer
0.373
20715828PEM_W1-120
Solar/Wind Harmer
0.373
20717128DIX_Z2-102
Solar/Wind Harmer
0.92
214067T20SOLAR
Solar/Wind Harmer
0.175
213611FALLS1-3
Adder
2.448
213611FALLS1-3
Adder
2.448
219607WPEMNERT C
Solar/Wind Harmer
0.287
219224BRL12CT4
Adder
6.121
219688LUMSOLAR_S C
Solar/Wind Harmer
0.138
219272CLEANLIGHT C
Solar/Wind Harmer
0.124
219914AD2-027 C
Solar/Wind Harmer
0.407
213561DLWR9-10
Adder
2.405
213561DLWR9-10
Adder
1.839
227927V4-067C
Solar/Wind Harmer
0.134
228754AB1-001 C
Solar/Wind Harmer
0.094
219137THOSOLAR C
Solar/Wind Harmer
0.815
971535AH1-265 GEN
Solar/Wind Harmer
2.857
971011AG2-627 GEN
Solar/Wind Harmer
5.134
972141AH1-641 GEN
Solar/Wind Harmer
1.924
964001AG1-254 GEN
Solar/Wind Harmer
1.36
228260V4-054C
Solar/Wind Harmer
0.686
213957STHWK3-4
Adder
1.826
970277AG2-181 GEN
Solar/Wind Harmer
3.431
233964AF2-378 GEN
Solar/Wind Harmer
0.087
232422X3-066 FULL
Solar/Wind Harmer
0.171
234012AE2-112_GEN
Solar/Wind Harmer
1.572
233930AB2-032 GEN
Solar/Wind Harmer
0.57
233915AB1-141 GEN
Solar/Wind Harmer
0.677
970643AG2-418 GEN
Solar/Wind Harmer
2.399
200917MEHOOPANY_G
Solar/Wind Harmer
4.185
20465027TOLNA CT
Adder
2.636
966131AG1-482 GEN
Solar/Wind Harmer
0.103
941421AE2-139 GEN
Solar/Wind Harmer
3.454
970899AG2-561 GEN
Solar/Wind Harmer
2.237
205975AE2-345_GEN
Solar/Wind Harmer
7.727
965131AG1-378 GEN
Solar/Wind Harmer
2.199
203818AF1-086 GEN
Solar/Wind Harmer
2.781
970335AG2-220 GEN
Solar/Wind Harmer
3.369
971127AH1-005 GEN
Solar/Wind Harmer
2.173
944411AF1-106 GEN
Solar/Wind Harmer
0.234
960051AF2-296 GEN
Solar/Wind Harmer
2.055
208923BUSO V4-027
Solar/Wind Harmer
0.287
208856AE1-226 GEN
Solar/Wind Harmer
2.033
20089126CSLMN_L13
Solar/Wind Harmer
0.89
230425AE1-104_GEN2
Solar/Wind Harmer
22.608
972233AH1-701 GEN
Adder
2.817
230433AD2-135 GEN
Solar/Wind Harmer
0.068
228304LOGAN
Adder
16.226
228307PCLP GT
Adder
8.101
20083426SW_E13_K22
Solar/Wind Harmer
0.382
228251CARLLS#4
Adder
0.421
213587EDDYSTN3
Adder
52.851
213589EDDYSTN4
Adder
52.845
233939AC1-091 C
Solar/Wind Harmer
0.603
233970AC1-092 C
Solar/Wind Harmer
0.603
971149AH1-027 GEN
Solar/Wind Harmer
2.321
232899W1-062
Adder
6.594
232416X2-083
Adder
0.309
970545AG2-347 GEN
Solar/Wind Harmer
44.807
231940T-011
Adder
0.511
972069AH1-584 GEN
Solar/Wind Harmer
6.131
972071AH1-585 GEN
Solar/Wind Harmer
6.131
233901CHERRYDALE C
Solar/Wind Harmer
0.771
232408W1-005 C
Solar/Wind Harmer
0.686
232410W1-006 C
Solar/Wind Harmer
0.686
232918OH NUG7
Adder
6.006
971747AH1-380 GEN
Solar/Wind Harmer
2.452
232905CHERITON_25
Adder
1.679
232926CRISFLD1
Adder
1.343
233946AB2-136 GEN
Solar/Wind Harmer
2.731
234036AF2-325 C
Solar/Wind Harmer
0.627
234041AC1-190 GEN
Solar/Wind Harmer
6.126
231131BLOOM ENRGY
Adder
2.981
233987AB2-037 GEN
Solar/Wind Harmer
7.779
233944AB2-135 GEN
Solar/Wind Harmer
3.582
232424Y1-079 C
Solar/Wind Harmer
0.385
233984AB2-036 GEN
Solar/Wind Harmer
8.511
234014AF1-036_GEN
Solar/Wind Harmer
1.85
233933AB2-153 GEN
Solar/Wind Harmer
0.769
20464827MOUNT CT
Adder
2.671
20464827MOUNT CT
Adder
2.592
208835TUHI V3-051
Solar/Wind Harmer
0.042
208835TUHI V3-051
Solar/Wind Harmer
0.042
203952AE2-129 C
Solar/Wind Harmer
0.666
203946AE2-131 C
Solar/Wind Harmer
0.665
962411AG1-090 GEN
Solar/Wind Harmer
10.445
970313AG2-206 GEN
Solar/Wind Harmer
5.222
205916AD1-020 GEN
Solar/Wind Harmer
1.994
203859AF2-294 C
Solar/Wind Harmer
1.812
216419AE2-001 C
Solar/Wind Harmer
2.128
20398826ARMNA MT
Solar/Wind Harmer
2.479
203853AF1-134 C O1
Solar/Wind Harmer
0.621
944781AF1-143 GEN
Solar/Wind Harmer
3.05
962101AG1-054 GEN
Solar/Wind Helper
1.21
241985AE1-237 GEN
Solar/Wind Helper
0.418
241967AE2-285_GEN
Solar/Wind Helper
1.064
241801AE1-079 GEN
Solar/Wind Helper
0.414
241996AE2-282_GEN
Solar/Wind Helper
1.276
241960AC2-195 GEN
Solar/Wind Helper
1.415
270224U2-072_GEN2
Solar/Wind Helper
0.671
270227U2-072_GEN3
Solar/Wind Helper
0.671
270228U2-072_GEN4
Solar/Wind Helper
0.671
270231U2-072_GEN5
Solar/Wind Helper
0.671
270471AD2-092_GEN
Solar/Wind Helper
1.344
246938BC-WTG3
Solar/Wind Helper
2.165
246937BC-WTG2
Solar/Wind Helper
2.128
270007AE1-245 C
Solar/Wind Helper
1.986
942801AE2-298 GEN
Solar/Wind Helper
0.555
946101AF1-275 GEN
Solar/Wind Helper
0.56
253378AE2-206_GEN
Solar/Wind Helper
1.088
276820AF1-078_GEN
Solar/Wind Helper
0.508
270518AE2-148 GEN
Solar/Wind Helper
10.958
200032KEYS G1
50/50
9.738
200033KEYS G2
50/50
9.354
235619AD2-113 G1
50/50
4.303
235620AD2-113 G2
50/50
4.303
200030CONE G1
50/50
7.35
957561AF2-050 GEN
Solar/Wind Harmer
8.364
209067AE2-060 GEN
Solar/Wind Harmer
1.658
946691AF1-333 GEN
Solar/Wind Harmer
0.966
946741AF1-338 GEN
Solar/Wind Harmer
0.966
972245AH1-707 GEN
Adder
5.177
961331AF2-424 GEN
Solar/Wind Harmer
0.946
961421AF2-433 GEN
Solar/Wind Harmer
0.945
957921AF2-086 GEN
Solar/Wind Harmer
0.919
209142AF1-226 GEN
Solar/Wind Harmer
5.469
209093AE2-110 GEN
Solar/Wind Harmer
2.362
209120AE2-241 GEN
Solar/Wind Harmer
3.125
209027LOR2_Q27
Solar/Wind Harmer
4.276
209022WHFR IPP
Adder
3.07
20088826HIGHLAND
Solar/Wind Harmer
2.5
963161AG1-165 GEN
Solar/Wind Harmer
0.907
209025WIENIPP3
Adder
4.784
964201AG1-281 GEN
Solar/Wind Harmer
0.904
963071AG1-156 GEN
Solar/Wind Harmer
2.485
970095AG2-074 GEN
Solar/Wind Harmer
5.639
203843AF2-002_GEN
Solar/Wind Harmer
1.483
970631AG2-411 GEN
Solar/Wind Harmer
9.336
203987AE2-118 C
Solar/Wind Harmer
2.934
964391AG1-301 GEN
Solar/Wind Harmer
0.87
20465427SHAW CT
Adder
3.208
20466127PORT 5CT
Adder
21.799
971007AG2-625 GEN
Solar/Wind Harmer
2.081
20633028GILCT9
Adder
23.129
966181AG1-487 GEN
Solar/Wind Harmer
0.205
20674628WNG_W3-110
Solar/Wind Harmer
0.321
207510AF2-138 C
Solar/Wind Harmer
1.414
20676728BRNX1-095
Solar/Wind Harmer
0.137
217194REDH C
Solar/Wind Harmer
0.377
217169METRODIV C
Solar/Wind Harmer
0.03
217186ESSEX_G9
Adder
12.224
217211CAMDEN ST C
Solar/Wind Harmer
0.019
20673728F2S_V4-070
Solar/Wind Harmer
0.135
219249CENTRALDIV C
Solar/Wind Harmer
0.03
219908AB1-139 C
Solar/Wind Harmer
0.284
219919AE1-041 FULL
Solar/Wind Harmer
0.03
20635028RRCT1&2
Adder
8.704
20635128RRCT3&4
Adder
7.216
20635828PARLN1&2
Adder
2.466
20635928PARLN3&4
Adder
2.466
971279AH1-102 GEN
Solar/Wind Harmer
11.049
967451AG2-055 C O1
Solar/Wind Harmer
126.059
218438BLK ROCK C
Solar/Wind Harmer
0.099
219612MATRIX C
Solar/Wind Harmer
0.134
20720528MAN_W1-024
Solar/Wind Harmer
0.183
20716228APLW2-078
Solar/Wind Harmer
0.636
219918AC2-009 C
Solar/Wind Harmer
0.044
20714528FRN_Y2-051
Solar/Wind Harmer
0.21
219276PARKLANDSO C
Solar/Wind Harmer
0.329
971423AH1-203 GEN
Solar/Wind Harmer
9.332
971667AH1-334 GEN
Solar/Wind Harmer
1.934
219727YARDVSOLFA C
Solar/Wind Harmer
0.642
20636028O CRK C1
Adder
4.934
20715028HAN_X4-015
Solar/Wind Harmer
0.208
20720828JCB_W4-025
Solar/Wind Harmer
0.315
972221AH1-695 GEN
Adder
116.247
20716028EGP_W2-019
Solar/Wind Harmer
0.323
959561AF2-247 GEN
Solar/Wind Harmer
0.337
219610FLORENCE C
Solar/Wind Harmer
0.95
219348LDSOLAR C
Solar/Wind Harmer
0.411
219221BRL12CT1
Adder
6.121
219223BRL12CT3
Adder
6.121
20094526CT_V3-030
Solar/Wind Harmer
0.928
219906AC1-017 C
Solar/Wind Harmer
0.152
213815MOSER1-3
Adder
2.423
219236SOUTHERNHQ C
Solar/Wind Harmer
0.046
219291REEVESSOUT C
Solar/Wind Harmer
0.041
219912AD2-042 GEN
Solar/Wind Harmer
0.54
219766PARADISE C
Solar/Wind Harmer
0.213
219623KINSLEYBEA C
Solar/Wind Harmer
0.289
213560DLW11-12
Adder
1.839
228729W2-030 C
Solar/Wind Harmer
0.389
230415AB2-049 C
Solar/Wind Harmer
0.127
228304LOGAN
Adder
14.593
230430AE1-229_GEN
Solar/Wind Harmer
5.888
971553AH1-274 GEN
Solar/Wind Harmer
1.618
213958STHWK5-6
Adder
1.826
228711V2-041C
Solar/Wind Harmer
0.401
228202CUMB CT
Adder
11.017
213497CHSTR7-9
Adder
1.807
972251AH1-710 GEN
Adder
31.224
233971AC1-093 C
Solar/Wind Harmer
0.538
970695AG2-447 GEN
Solar/Wind Harmer
2.458
233952AC2-187 GEN
Solar/Wind Harmer
0.771
972133AH1-634 GEN
Solar/Wind Harmer
6.789
972073AH1-586 GEN
Solar/Wind Harmer
6.416
233990AG1-397 GEN
Solar/Wind Harmer
0.785
232406W1-004 FULL
Solar/Wind Harmer
0.686
234015AF2-250 C
Solar/Wind Harmer
0.082
232914OH NUG3
Adder
6.046
232916OH NUG5
Adder
6.046
232921TASLEY2G
Adder
3.534
233900O-025 C
Adder
0.806
233996TM1833_GEN
Solar/Wind Harmer
0.867
233997TMININ_4.2
Solar/Wind Harmer
0.867
233940AF2-379 C
Solar/Wind Harmer
0.128
233994AC2-023 GEN
Solar/Wind Harmer
1.84
960671AF2-358 GEN
Solar/Wind Harmer
12.255
232907VN8
Adder
20.546
232417X3-008 C
Solar/Wind Harmer
1.369
233982AB2-133 GEN
Solar/Wind Harmer
3.33
233918AB1-142 GEN
Solar/Wind Harmer
0.677
970643AG2-418 GEN
Solar/Wind Harmer
1.116
966131AG1-482 GEN
Solar/Wind Harmer
2.281
970511AG2-327 GEN
Solar/Wind Harmer
1.088
205917AD1-020 ES
Solar/Wind Harmer
0.429
238215AE2-248 C
Solar/Wind Harmer
1.728
959471AF2-238 GEN
Solar/Wind Harmer
0.649
970337AG2-221 GEN
Solar/Wind Harmer
2.145
944411AF1-106 GEN
Solar/Wind Harmer
2.176
20089226LOOKOUT
Solar/Wind Harmer
0.866
238206AE2-263_GEN
Solar/Wind Harmer
2.297
972169AH1-667 GEN
Solar/Wind Harmer
1.705
241966AE1-183 GEN
Solar/Wind Helper
0.465
254303AC2-168 GEN
Solar/Wind Helper
0.214
958961AF2-187 GEN
Solar/Wind Helper
2.479
241885AC2-103 GEN1
Solar/Wind Helper
2.341
241807AE2-176_GEN
Solar/Wind Helper
1.633
241808AF1-120 C
Solar/Wind Helper
0.713
241840AF1-064_GEN
Solar/Wind Helper
0.977
960841AF2-375 GEN
Solar/Wind Helper
1.571
247522W1-056 GEN
Solar/Wind Helper
1.295
270462AD2-086
Solar/Wind Helper
2.607
270223U2-072_GEN1
Solar/Wind Helper
0.671
270578AF1-285 GEN2
Solar/Wind Helper
0.455
270391AF1-285 GEN3
Solar/Wind Helper
0.455
270349AD2-093_GEN
Solar/Wind Helper
1.344
246936BC-WTG1
Solar/Wind Helper
2.128
944231AF1-091 GEN
Solar/Wind Helper
3.478
24695305TIMB G C
Solar/Wind Helper
2.317
247521TR3_G114
Solar/Wind Helper
1.808
270246TR4_N_V150
Solar/Wind Helper
0.457
213957STHWK3-4
Adder
1.826
228309CCLP NUG
Adder
17.271
228309CCLP NUG
Adder
16.429
213942SCHUYLKILL
Adder
2.386
213942SCHUYLKILL
Adder
1.824
970453AG2-297 GEN
Solar/Wind Harmer
1.838
20390726Y2-042
Adder
2.937
231919CHRIST1
Adder
3.04
231920CHRIST2
Adder
2.973
205951AE1-129_GEN
Solar/Wind Harmer
9.683
233973AC2-185 C
Solar/Wind Harmer
2.479
234033AF1-007_GEN
Solar/Wind Harmer
16.012
232904IR4
Adder
55.363
232920IR10
Adder
2.164
232432Z2-076 GEN
Solar/Wind Harmer
0.09
232813VAUGHN
Adder
0.403
233990AG1-397 GEN
Solar/Wind Harmer
0.038
232912OH NUG1
Adder
6.046
232913OH NUG2
Adder
5.965
233923SMA
Solar/Wind Harmer
3.179
233955AB2-172 GEN
Solar/Wind Harmer
3.421
231906DC3 NUG
Adder
9.57
231902DC CT7
Adder
7.65
231907DC10
Adder
2.389
232436AB1-176 C
Solar/Wind Harmer
0.157
233968AD2-076_GEN
Solar/Wind Harmer
4.532
970597AG2-380 GEN
Solar/Wind Harmer
2.846
20090526Q36
Solar/Wind Harmer
1.905
203993AD2-133_GEN1
Solar/Wind Harmer
1.905
971983AH1-536 GEN
Solar/Wind Harmer
5.114
233935AB2-179 C
Solar/Wind Harmer
1.708
205932AD2-116_GEN
Solar/Wind Harmer
0.672
205956AE1-196_GEN
Solar/Wind Harmer
0.672
205943AE1-185 GEN
Solar/Wind Harmer
0.67
20334726NME_Y1-047
Adder
2.811
960921AF2-383 GEN
Solar/Wind Harmer
0.223
20465027TOLNA CT
Adder
2.74
960921AF2-383 GEN
Solar/Wind Harmer
1.716
20083926HOMER C3
Adder
84.655
20083826HOMER C2
Adder
26.837
965121AG1-377 GEN
Solar/Wind Harmer
2.199
970555AG2-356 GEN
Solar/Wind Harmer
2.145
203855AF2-088 C
Solar/Wind Harmer
0.187
203975AE1-071-GEN
Solar/Wind Harmer
2.611
241997AF1-093 GEN
Solar/Wind Helper
0.465
241982AE2-343 S C
Solar/Wind Helper
0.375
254304AE2-114 C
Solar/Wind Helper
0.305
241886AC2-103 GEN2
Solar/Wind Helper
2.341
945411AF1-206 GEN
Solar/Wind Helper
2.418
945641AF1-229 GEN
Solar/Wind Helper
1.456
270499AE1-146 GEN
Solar/Wind Helper
2.492
966831AG1-554 GEN
Solar/Wind Helper
0.877
270054AF2-122 C O1
Solar/Wind Helper
1.222
270317AD1-130_GEN
Solar/Wind Helper
2.887
270284AF1-227 GEN1
Solar/Wind Helper
2.108
270286AF1-227 GEN2
Solar/Wind Helper
0.773
270287AF1-227 GEN3
Solar/Wind Helper
0.773
957201AF2-014 GEN
Solar/Wind Helper
1.682
247607V1-011 GEN
Solar/Wind Helper
1.324
270520AE2-214 GEN
Solar/Wind Helper
4.474
241973AD2-163_GEN1
Solar/Wind Helper
1.648
253383AE2-342_GEN
Solar/Wind Helper
0.73
945631AF1-228 GEN
Solar/Wind Helper
1.719
20089026BF_G21_K23
Solar/Wind Harmer
0.704
238202AE2-262_GEN
Solar/Wind Harmer
2.464
971627AH1-313 GEN
Solar/Wind Harmer
9.662
203854AF2-039 C
Solar/Wind Harmer
0.387
20334926Z1-069 C
Solar/Wind Harmer
1.923
235058AG1-386 C
Solar/Wind Helper
0.618
254305AE2-115 C
Solar/Wind Helper
0.305
241832AE2-181_GEN
Solar/Wind Helper
0.592
270541AE2-072 C
Solar/Wind Helper
1.764
270485AE1-090_GEN
Solar/Wind Helper
0.227
942871AE2-306 GEN
Solar/Wind Helper
0.341
270044AE2-322 C
Solar/Wind Helper
1.116
270404AC1-167 GEN
Solar/Wind Helper
0.93
241974AD2-163_GEN2
Solar/Wind Helper
1.648
241955AC1-078 GEN
Solar/Wind Helper
1.849
960801AF2-371 GEN
Solar/Wind Helper
0.936
964871AG1-351 GEN
Solar/Wind Helper
0.646
270191TR4_S_V150
Solar/Wind Helper
0.998
270247TR4_N_V136
Solar/Wind Helper
0.457
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.017
G-007ALTFEXP_G-007A->PJM
CMTX
37.853
CBM NorthLTFEXP_CBM-N->PJM
CBM
70.846
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
5.181
BlueGrassPJM->LTFIMP_BlueG
CLTF
16.095
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
103.105
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.085
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
23.169

Details for KEYSTONE-01SOBEND 500.0 kV Ckt 1 line l/o PN_P2-3_PN-500-DRT32_SRT-A


Base Case Flowgate

Area:AP/PJM
Facility Description:
KEYSTONE-01SOBEND 500.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-500-DRT32_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.79 %
Rating:2078.0 MVA
Rating Type:B
MVA to Mitigate:2239.81
MW Contribution:4.83
Bus #Bus NameTypeMW Contribution
200032KEYS G1
50/50
9.838
200030CONE G1
50/50
8.363
200105AA1-076 ST
50/50
6.971
20083326SEWRDB34
50/50
6.196
20079426CONEMAGH
50/50
2.01
972241AH1-705 GEN
Adder
5.792
209071AE2-133 GEN
Solar/Wind Harmer
1.612
970665AG2-430 GEN
Solar/Wind Harmer
9.444
209018SUNBIPCT
Adder
7.089
946731AF1-337 GEN
Solar/Wind Harmer
0.95
212507AE2-042_GEN
Solar/Wind Harmer
2.831
961341AF2-425 GEN
Solar/Wind Harmer
0.927
212174INGE
Adder
1.025
970125AG2-091 GEN
Solar/Wind Harmer
0.917
212266LOR1
Solar/Wind Harmer
0.12
970237AG2-161 GEN
Solar/Wind Harmer
3.216
971879AH1-460 GEN
Solar/Wind Harmer
9.935
203841AF2-001_GEN
Solar/Wind Harmer
2.951
961301AF2-421 GEN
Solar/Wind Harmer
0.886
963151AG1-164 GEN
Solar/Wind Harmer
0.886
209023WIENIPP1
Adder
9.55
209025WIENIPP3
Adder
4.767
971541AH1-268 GEN
Solar/Wind Harmer
4.975
209010PEIP 1
Adder
0.563
208909MACR G3
Adder
127.852
20465127PORT CT
Adder
2.371
20671928W4-073
Solar/Wind Harmer
0.341
207518AF1-320_GEN
Solar/Wind Harmer
2.865
207437AD2-070 GEN
Solar/Wind Harmer
0.236
971519AH1-257 GEN
Solar/Wind Harmer
1.965
966181AG1-487 GEN
Solar/Wind Harmer
2.943
20675828AU_W4-064
Solar/Wind Harmer
0.133
207439AE1-081 C O1
Solar/Wind Harmer
0.046
20674328GAR_V4-001
Solar/Wind Harmer
0.084
971419AH1-201 GEN
Solar/Wind Harmer
4.227
217208PARK ELE C
Solar/Wind Harmer
0.019
200033KEYS G2
50/50
10.214
200031CONE G2
50/50
8.262
200031CONE G2
50/50
7.69
20080926SITHE
50/50
0.407
20088626ARWF_N39
Solar/Wind Harmer
3.124
20303426NA_O38_P22
Solar/Wind Harmer
2.529
209137AF2-361 C
Solar/Wind Harmer
3.172
209130AF1-271A GEN
Solar/Wind Harmer
2.676
946751AF1-339 GEN
Solar/Wind Harmer
0.95
209054AE2-059 GEN
Solar/Wind Harmer
1.598
209059AE2-084 GEN
Solar/Wind Harmer
2.359
961431AF2-434 GEN
Solar/Wind Harmer
0.927
971441AH1-212 GEN
Solar/Wind Harmer
3.06
203857AF2-221 C
Solar/Wind Harmer
2.291
970123AG2-090 GEN
Solar/Wind Harmer
2.139
961541AF2-445A GEN
Solar/Wind Harmer
3.008
203940AF1-140 C
Solar/Wind Harmer
0.746
20084626FORWARD
Solar/Wind Harmer
1.167
203839AF1-321 GEN
Solar/Wind Harmer
2.951
208972BECR K09
Solar/Wind Harmer
0.941
209029WAYMART-WD
Solar/Wind Harmer
2.518
209009PEIP 2
Adder
6.838
209010PEIP 1
Adder
3.098
209010PEIP 1
Adder
0.454
211065PSPA IPP
Solar/Wind Harmer
0.377
211065PSPA IPP
Solar/Wind Harmer
0.377
946071AF1-272 GEN
Solar/Wind Harmer
4.639
966111AG1-480 GEN
Solar/Wind Harmer
0.069
966111AG1-480 GEN
Solar/Wind Harmer
2.644
20465127PORT CT
Adder
3.147
20674128FR_U2-059
Solar/Wind Harmer
0.145
20634528N27_Y2-018
Solar/Wind Harmer
0.21
964851AG1-348 GEN
Solar/Wind Harmer
1.368
207471AF2-354 C
Solar/Wind Harmer
0.396
20674928WA_W3-044
Solar/Wind Harmer
0.373
20676228FRD_X1-012
Solar/Wind Harmer
0.454
20088926STNY CRK
Solar/Wind Harmer
1.63
971427AH1-205 GEN
Solar/Wind Harmer
1.966
217204WCALDSOLAR C
Solar/Wind Harmer
0.054
217086KRNY_131
Adder
6.822
217083KRNY_132
Adder
6.764
217206BARNGR HS C
Solar/Wind Harmer
0.023
217201HACKENSOLA C
Solar/Wind Harmer
0.054
972237AH1-703 GEN
Adder
7.407
217202FBANKSOLAR C
Solar/Wind Harmer
0.054
20674528F3S_W2-016
Solar/Wind Harmer
1.032
20671828STAW2-080
Solar/Wind Harmer
0.077
217081WEATEXAS C
Solar/Wind Harmer
0.062
219036LINDEN_G7
Adder
12.077
219035LINDEN_G8
Adder
11.905
972261AH1-715 GEN2
Adder
11.561
207442AE1-156 GEN
Solar/Wind Harmer
0.536
20676128MHD_W3-029
Solar/Wind Harmer
0.344
218418LINDEN_G5
Adder
12.307
218419LINDEN_G6
Adder
12.307
972260AH1-715 GEN1
Adder
9.855
20673828FLE_V3-070
Solar/Wind Harmer
0.327
218440SUMMTASSOC C
Solar/Wind Harmer
0.091
924131AB2-057 GEN
Solar/Wind Harmer
0.722
20716928W4-060COL
Solar/Wind Harmer
0.494
20720628TIN_W1-124
Solar/Wind Harmer
0.682
20641628MLH_W1-032
Solar/Wind Harmer
0.201
20465527S.RDG CT
Adder
2.084
20478527GLRA_Q45
Adder
0.265
219817TRENTONSOL C
Solar/Wind Harmer
0.75
20628028LAKEHURS
Adder
0.637
20714928UPF_X1-085
Solar/Wind Harmer
0.271
963391AG1-188 GEN
Solar/Wind Harmer
1.275
219114HARTZY_C
Solar/Wind Harmer
0.556
963401AG1-189 GEN
Solar/Wind Harmer
0.764
207500AE2-000G1
Solar/Wind Harmer
20.861
207497AE2-000G2
Solar/Wind Harmer
20.861
207507AE2-000G3
Solar/Wind Harmer
20.861
20636128O CRK C2
Adder
4.268
20716428NHV_W2-082
Solar/Wind Harmer
1.173
203952AE2-129 C
Solar/Wind Harmer
0.751
203946AE2-131 C
Solar/Wind Harmer
0.749
962411AG1-090 GEN
Solar/Wind Harmer
11.772
20083426SW_E13_K22
Solar/Wind Harmer
0.368
213535CROYDN11
Adder
6.633
219615MILLCREEK C
Solar/Wind Harmer
0.154
213815MOSER1-3
Adder
2.288
213815MOSER1-3
Adder
2.288
219921AF1-264
Solar/Wind Harmer
0.092
230407AD2-065 C
Solar/Wind Harmer
0.083
970313AG2-206 GEN
Solar/Wind Harmer
5.817
230422AE1-104_GEN1
Solar/Wind Harmer
21.299
230425AE1-104_GEN2
Solar/Wind Harmer
21.299
972233AH1-701 GEN
Adder
2.653
230433AD2-135 GEN
Solar/Wind Harmer
0.064
228304LOGAN
Adder
15.28
228307PCLP GT
Adder
7.628
228251CARLLS#4
Adder
0.397
216419AE2-001 C
Solar/Wind Harmer
2.402
20398826ARMNA MT
Solar/Wind Harmer
2.799
203859AF2-294 C
Solar/Wind Harmer
2.031
213587EDDYSTN3
Adder
49.629
213589EDDYSTN4
Adder
49.623
203853AF1-134 C O1
Solar/Wind Harmer
0.719
233939AC1-091 C
Solar/Wind Harmer
0.561
233970AC1-092 C
Solar/Wind Harmer
0.561
971149AH1-027 GEN
Solar/Wind Harmer
2.162
232899W1-062
Adder
6.143
232416X2-083
Adder
0.288
970545AG2-347 GEN
Solar/Wind Harmer
41.727
231940T-011
Adder
0.476
972069AH1-584 GEN
Solar/Wind Harmer
5.709
972071AH1-585 GEN
Solar/Wind Harmer
5.709
971747AH1-380 GEN
Solar/Wind Harmer
2.283
233901CHERRYDALE C
Solar/Wind Harmer
0.718
232408W1-005 C
Solar/Wind Harmer
0.638
232410W1-006 C
Solar/Wind Harmer
0.638
232918OH NUG7
Adder
5.592
232905CHERITON_25
Adder
1.564
232926CRISFLD1
Adder
1.251
233946AB2-136 GEN
Solar/Wind Harmer
2.543
234036AF2-325 C
Solar/Wind Harmer
0.584
234041AC1-190 GEN
Solar/Wind Harmer
5.704
233987AB2-037 GEN
Solar/Wind Harmer
7.241
233944AB2-135 GEN
Solar/Wind Harmer
3.334
232424Y1-079 C
Solar/Wind Harmer
0.358
233984AB2-036 GEN
Solar/Wind Harmer
7.922
234014AF1-036_GEN
Solar/Wind Harmer
1.722
233933AB2-153 GEN
Solar/Wind Harmer
0.716
208835TUHI V3-051
Solar/Wind Harmer
0.038
208835TUHI V3-051
Solar/Wind Harmer
0.038
972075AH1-587 GEN
Solar/Wind Harmer
20.001
972077AH1-588 GEN
Solar/Wind Harmer
23.398
972079AH1-589 GEN
Solar/Wind Harmer
19.272
970715AG2-457 GEN
Solar/Wind Harmer
7.799
205916AD1-020 GEN
Solar/Wind Harmer
1.791
944781AF1-143 GEN
Solar/Wind Harmer
2.742
238217AF1-153 C O1
Solar/Wind Harmer
0.544
23652301WDPWR_K20
Solar/Wind Helper
0.194
200032KEYS G1
50/50
10.224
200033KEYS G2
50/50
9.821
200030CONE G1
50/50
7.621
957561AF2-050 GEN
Solar/Wind Harmer
8.479
209067AE2-060 GEN
Solar/Wind Harmer
1.64
946691AF1-333 GEN
Solar/Wind Harmer
0.95
946741AF1-338 GEN
Solar/Wind Harmer
0.95
20088826HIGHLAND
Solar/Wind Harmer
2.526
972245AH1-707 GEN
Adder
5.084
961331AF2-424 GEN
Solar/Wind Harmer
0.927
961421AF2-433 GEN
Solar/Wind Harmer
0.927
957921AF2-086 GEN
Solar/Wind Harmer
0.901
209142AF1-226 GEN
Solar/Wind Harmer
5.365
209093AE2-110 GEN
Solar/Wind Harmer
2.317
209120AE2-241 GEN
Solar/Wind Harmer
3.066
964201AG1-281 GEN
Solar/Wind Harmer
0.92
209027LOR2_Q27
Solar/Wind Harmer
4.188
209022WHFR IPP
Adder
3.006
203987AE2-118 C
Solar/Wind Harmer
3.014
964391AG1-301 GEN
Solar/Wind Harmer
0.896
970631AG2-411 GEN
Solar/Wind Harmer
9.297
203843AF2-002_GEN
Solar/Wind Harmer
1.475
963161AG1-165 GEN
Solar/Wind Harmer
0.886
209025WIENIPP3
Adder
4.671
963071AG1-156 GEN
Solar/Wind Harmer
2.432
970095AG2-074 GEN
Solar/Wind Harmer
5.519
971279AH1-102 GEN
Solar/Wind Harmer
11.69
20094526CT_V3-030
Solar/Wind Harmer
0.992
20465427SHAW CT
Adder
3.099
20466127PORT 5CT
Adder
21.011
971007AG2-625 GEN
Solar/Wind Harmer
2.002
20633028GILCT9
Adder
22.239
966181AG1-487 GEN
Solar/Wind Harmer
0.197
20674628WNG_W3-110
Solar/Wind Harmer
0.309
207510AF2-138 C
Solar/Wind Harmer
1.359
20676728BRNX1-095
Solar/Wind Harmer
0.131
217194REDH C
Solar/Wind Harmer
0.361
217169METRODIV C
Solar/Wind Harmer
0.029
217186ESSEX_G9
Adder
11.707
217211CAMDEN ST C
Solar/Wind Harmer
0.018
20673728F2S_V4-070
Solar/Wind Harmer
0.129
219249CENTRALDIV C
Solar/Wind Harmer
0.028
219908AB1-139 C
Solar/Wind Harmer
0.271
219919AE1-041 FULL
Solar/Wind Harmer
0.029
971423AH1-203 GEN
Solar/Wind Harmer
9.109
20635028RRCT1&2
Adder
8.307
20635128RRCT3&4
Adder
6.887
20635828PARLN1&2
Adder
2.352
20635928PARLN3&4
Adder
2.352
967451AG2-055 C O1
Solar/Wind Harmer
120.09
218438BLK ROCK C
Solar/Wind Harmer
0.095
219612MATRIX C
Solar/Wind Harmer
0.128
20720528MAN_W1-024
Solar/Wind Harmer
0.174
20716228APLW2-078
Solar/Wind Harmer
0.605
219918AC2-009 C
Solar/Wind Harmer
0.042
20714528FRN_Y2-051
Solar/Wind Harmer
0.199
219276PARKLANDSO C
Solar/Wind Harmer
0.312
971667AH1-334 GEN
Solar/Wind Harmer
1.836
219727YARDVSOLFA C
Solar/Wind Harmer
0.61
20636028O CRK C1
Adder
4.681
20715028HAN_X4-015
Solar/Wind Harmer
0.197
20720828JCB_W4-025
Solar/Wind Harmer
0.299
20716028EGP_W2-019
Solar/Wind Harmer
0.306
972221AH1-695 GEN
Adder
110.049
959561AF2-247 GEN
Solar/Wind Harmer
0.319
219610FLORENCE C
Solar/Wind Harmer
0.898
219348LDSOLAR C
Solar/Wind Harmer
0.388
219221BRL12CT1
Adder
5.788
219223BRL12CT3
Adder
5.788
219906AC1-017 C
Solar/Wind Harmer
0.144
213815MOSER1-3
Adder
2.288
219236SOUTHERNHQ C
Solar/Wind Harmer
0.043
219291REEVESSOUT C
Solar/Wind Harmer
0.038
219912AD2-042 GEN
Solar/Wind Harmer
0.509
219766PARADISE C
Solar/Wind Harmer
0.201
219623KINSLEYBEA C
Solar/Wind Harmer
0.272
213560DLW11-12
Adder
1.734
228729W2-030 C
Solar/Wind Harmer
0.366
238215AE2-248 C
Solar/Wind Harmer
1.939
970511AG2-327 GEN
Solar/Wind Harmer
1.212
230415AB2-049 C
Solar/Wind Harmer
0.12
228304LOGAN
Adder
13.743
230430AE1-229_GEN
Solar/Wind Harmer
5.544
971553AH1-274 GEN
Solar/Wind Harmer
1.523
213958STHWK5-6
Adder
1.718
228711V2-041C
Solar/Wind Harmer
0.377
228202CUMB CT
Adder
10.369
959471AF2-238 GEN
Solar/Wind Harmer
0.727
970337AG2-221 GEN
Solar/Wind Harmer
2.406
213497CHSTR7-9
Adder
1.697
20326126BLOSSBCT
Adder
2.714
970643AG2-418 GEN
Solar/Wind Harmer
1.099
20335026MILZ1-092
Adder
2.683
944411AF1-106 GEN
Solar/Wind Harmer
2.472
972251AH1-710 GEN
Adder
29.207
233971AC1-093 C
Solar/Wind Harmer
0.501
970695AG2-447 GEN
Solar/Wind Harmer
2.29
233952AC2-187 GEN
Solar/Wind Harmer
0.718
972133AH1-634 GEN
Solar/Wind Harmer
6.322
972073AH1-586 GEN
Solar/Wind Harmer
5.974
233990AG1-397 GEN
Solar/Wind Harmer
0.731
232406W1-004 FULL
Solar/Wind Harmer
0.638
234015AF2-250 C
Solar/Wind Harmer
0.077
232914OH NUG3
Adder
5.63
232916OH NUG5
Adder
5.63
232921TASLEY2G
Adder
3.29
233900O-025 C
Adder
0.751
233996TM1833_GEN
Solar/Wind Harmer
0.807
233997TMININ_4.2
Solar/Wind Harmer
0.807
233940AF2-379 C
Solar/Wind Harmer
0.119
233994AC2-023 GEN
Solar/Wind Harmer
1.713
960671AF2-358 GEN
Solar/Wind Harmer
11.411
232907VN8
Adder
15.629
232417X3-008 C
Solar/Wind Harmer
1.274
233982AB2-133 GEN
Solar/Wind Harmer
3.1
233918AB1-142 GEN
Solar/Wind Harmer
0.63
238206AE2-263_GEN
Solar/Wind Harmer
2.701
972169AH1-667 GEN
Solar/Wind Harmer
2.031
203954AE2-126 C
Solar/Wind Harmer
0.634
966131AG1-482 GEN
Solar/Wind Harmer
2.083
970713AG2-456 GEN
Solar/Wind Harmer
7.799
971705AH1-358 GEN
Solar/Wind Harmer
2.267
971709AH1-360 GEN
Solar/Wind Harmer
2.267
205917AD1-020 ES
Solar/Wind Harmer
0.385
20089226LOOKOUT
Solar/Wind Harmer
0.779
237046AF1-021 C
Solar/Wind Helper
0.659
200104AA1-076 CT2
50/50
6.15
200103AA1-076 CT1
50/50
6.096
20083726HOMER C1
Adder
119.115
203961AE2-224 GEN
Solar/Wind Harmer
5.136
959431AF2-234 GEN
Solar/Wind Harmer
1.903
964051AG1-259 GEN
Solar/Wind Harmer
1.276
964061AG1-260 GEN
Solar/Wind Harmer
1.276
959421AF2-233 GEN
Solar/Wind Harmer
0.952
20092526R32
Solar/Wind Harmer
2.707
209045AE2-271 GEN
Solar/Wind Harmer
15.641
20091526CHSTN_FL
Solar/Wind Harmer
1.307
941231AE2-117 GEN
Solar/Wind Harmer
0.891
203850AG1-041 C
Solar/Wind Harmer
1.767
209026WIENIPP4
Adder
4.719
203844AF2-092 C
Solar/Wind Harmer
1.755
961261AF2-417 GEN
Solar/Wind Harmer
0.858
209116AE2-175 GEN
Solar/Wind Harmer
3.375
966421AG1-511 GEN
Solar/Wind Harmer
6.823
20462827N BANGR8
Adder
0.566
20675128HRM_W1-127
Solar/Wind Harmer
0.134
207408W3-077 C
Solar/Wind Harmer
0.397
20675728RH_W2-091
Solar/Wind Harmer
0.268
207484AF2-139 C O1
Solar/Wind Harmer
0.396
971009AG2-626 GEN
Solar/Wind Harmer
1.277
20675928HOL_W4-097
Solar/Wind Harmer
0.102
20674828DL_W4-046
Solar/Wind Harmer
0.5
207511W3-106 GEN
Solar/Wind Harmer
0.503
20676328BVR_Y1-020
Solar/Wind Harmer
0.252
207530AG1-191 GEN
Solar/Wind Harmer
1.052
20083926HOMER C3
Adder
95.203
20083826HOMER C2
Adder
89.93
20090526Q36
Solar/Wind Harmer
2.07
203993AD2-133_GEN1
Solar/Wind Harmer
2.07
966261AG1-495 GEN
Solar/Wind Harmer
1.343
217167KRNY_14
Adder
6.808
217086KRNY_131
Adder
6.75
217147KRNY_1212
Adder
6.475
217147KRNY_1212
Adder
6.36
217146KRNY_1234
Adder
6.345
217146KRNY_1234
Adder
6.302
218404KENILWRTH C
Adder
0.952
20390726Y2-042
Adder
3.066
218524CNTRALGAS1 C
Solar/Wind Harmer
0.263
218526CNTRALGAS2 C
Solar/Wind Harmer
0.262
20675528CPH_W2-050
Solar/Wind Harmer
0.332
218455CINNBAY_CGEN
Adder
1.275
20635928PARLN3&4
Adder
5.193
20720428HOL_W1-112
Solar/Wind Harmer
0.239
971521AH1-258 GEN
Solar/Wind Harmer
1.866
20486527WR_V4-052
Adder
0.84
20714428HOW_X1-037
Solar/Wind Harmer
0.844
20714328BYD_X4-031
Solar/Wind Harmer
0.193
20334726NME_Y1-047
Adder
2.991
219620RIDERU C
Solar/Wind Harmer
0.038
207459AE1-142 C O1
Solar/Wind Harmer
0.705
971189AH1-054 GEN
Solar/Wind Harmer
0.785
970025AG2-016 GEN
Solar/Wind Harmer
1.884
203926AA2-133 GEN
Adder
2.948
208862AG1-362 C
Solar/Wind Harmer
0.628
20715728PEM_W1-119
Solar/Wind Harmer
0.353
20715828PEM_W1-120
Solar/Wind Harmer
0.353
20717128DIX_Z2-102
Solar/Wind Harmer
0.872
214067T20SOLAR
Solar/Wind Harmer
0.166
213611FALLS1-3
Adder
2.318
213611FALLS1-3
Adder
2.318
965121AG1-377 GEN
Solar/Wind Harmer
2.478
219607WPEMNERT C
Solar/Wind Harmer
0.272
219224BRL12CT4
Adder
5.788
219688LUMSOLAR_S C
Solar/Wind Harmer
0.13
219272CLEANLIGHT C
Solar/Wind Harmer
0.117
219914AD2-027 C
Solar/Wind Harmer
0.384
213561DLWR9-10
Adder
2.268
213561DLWR9-10
Adder
1.734
227927V4-067C
Solar/Wind Harmer
0.126
228754AB1-001 C
Solar/Wind Harmer
0.088
219137THOSOLAR C
Solar/Wind Harmer
0.768
971535AH1-265 GEN
Solar/Wind Harmer
2.692
971011AG2-627 GEN
Solar/Wind Harmer
4.834
964001AG1-254 GEN
Solar/Wind Harmer
1.28
972141AH1-641 GEN
Solar/Wind Harmer
1.811
228260V4-054C
Solar/Wind Harmer
0.646
228309CCLP NUG
Adder
16.257
228309CCLP NUG
Adder
15.464
213957STHWK3-4
Adder
1.718
213957STHWK3-4
Adder
1.718
213942SCHUYLKILL
Adder
2.245
213942SCHUYLKILL
Adder
1.717
970453AG2-297 GEN
Solar/Wind Harmer
1.729
970555AG2-356 GEN
Solar/Wind Harmer
2.406
231919CHRIST1
Adder
2.835
231920CHRIST2
Adder
2.772
205951AE1-129_GEN
Solar/Wind Harmer
9.022
233973AC2-185 C
Solar/Wind Harmer
2.31
234033AF1-007_GEN
Solar/Wind Harmer
14.911
232904IR4
Adder
51.558
232920IR10
Adder
2.015
232432Z2-076 GEN
Solar/Wind Harmer
0.084
232813VAUGHN
Adder
0.375
233990AG1-397 GEN
Solar/Wind Harmer
0.035
232912OH NUG1
Adder
5.63
232913OH NUG2
Adder
5.555
233923SMA
Solar/Wind Harmer
2.96
233955AB2-172 GEN
Solar/Wind Harmer
3.185
232436AB1-176 C
Solar/Wind Harmer
0.146
233968AD2-076_GEN
Solar/Wind Harmer
4.218
970597AG2-380 GEN
Solar/Wind Harmer
2.649
971983AH1-536 GEN
Solar/Wind Harmer
4.76
233935AB2-179 C
Solar/Wind Harmer
1.589
203855AF2-088 C
Solar/Wind Harmer
0.222
205932AD2-116_GEN
Solar/Wind Harmer
0.622
205956AE1-196_GEN
Solar/Wind Harmer
0.622
205943AE1-185 GEN
Solar/Wind Harmer
0.62
960921AF2-383 GEN
Solar/Wind Harmer
0.206
960921AF2-383 GEN
Solar/Wind Harmer
1.585
940863AE2-074 GEN
Solar/Wind Harmer
1.844
203804AE2-113_GEN
Solar/Wind Harmer
4.781
23750501ELLIOTTS
Solar/Wind Helper
0.734
217083KRNY_132
Adder
6.808
217121ECCF
Adder
0.318
217209CENTRL HS C
Solar/Wind Harmer
0.033
218449LINSOLAR C
Solar/Wind Harmer
0.726
20676428JCR_X2-075
Solar/Wind Harmer
0.247
970679AG2-439 GEN
Solar/Wind Harmer
1.281
207528AF2-192 GEN
Solar/Wind Harmer
0.398
20673628F1S_V4-069
Solar/Wind Harmer
0.129
20675428EAM_W2-061
Solar/Wind Harmer
0.136
972275AH1-722 GEN
Adder
22.624
217213AMBOY SO C
Solar/Wind Harmer
0.09
218428ETC SOLAR C
Solar/Wind Harmer
0.026
205941AD2-115 GEN
Solar/Wind Harmer
0.726
209008PAXT IPP
Adder
1.707
20635028RRCT1&2
Adder
8.179
20635128RRCT3&4
Adder
7.895
20635828PARLN1&2
Adder
5.193
217197RE CRAN C
Solar/Wind Harmer
0.372
20742028HF_AC1-207
Solar/Wind Harmer
0.539
20467927PC_Q59Y356
Adder
0.659
20715228NPK_W1-113
Solar/Wind Harmer
0.295
207454AA2-184 E
Solar/Wind Harmer
0.685
20465527S.RDG CT
Adder
2.154
219680HOPEWELLV C1
Solar/Wind Harmer
0.052
200917MEHOOPANY_G
Solar/Wind Harmer
4.452
20714828MDF_W3-079
Solar/Wind Harmer
0.207
963711AG1-223 GEN
Solar/Wind Harmer
1
207445AB1-138_GEN
Solar/Wind Harmer
0.388
20628028LAKEHURS
Adder
1.26
970899AG2-561 GEN
Solar/Wind Harmer
2.52
207487AE2-000G4
Solar/Wind Harmer
20.861
207522AF2-254 C
Solar/Wind Harmer
0.947
20720728JCB_W1-129
Solar/Wind Harmer
0.197
972271AH1-720 GEN
Adder
8.193
213611FALLS1-3
Adder
2.318
214194N WALES4
Adder
0.558
965131AG1-378 GEN
Solar/Wind Harmer
2.478
20328326MANOR_T86
Adder
0.176
941421AE2-139 GEN
Solar/Wind Harmer
3.761
203818AF1-086 GEN
Solar/Wind Harmer
3.159
219304NAMERICA C
Solar/Wind Harmer
0.201
219222BRL12CT2
Adder
5.788
219287REEVESEAST C
Solar/Wind Harmer
0.863
219686LUMSOLAR_N C
Solar/Wind Harmer
0.13
219907AC1-030 C
Solar/Wind Harmer
0.089
218660EHAMPSOLAR C
Solar/Wind Harmer
0.112
219904AC1-010 C
Solar/Wind Harmer
0.241
219258KINSLEYDEP C
Solar/Wind Harmer
0.206
213560DLW11-12
Adder
1.734
228728W1-130C
Solar/Wind Harmer
0.42
970335AG2-220 GEN
Solar/Wind Harmer
3.755
971127AH1-005 GEN
Solar/Wind Harmer
2.422
230434AG1-499 GEN
Solar/Wind Harmer
0.367
230511AF1-262
Solar/Wind Harmer
0.115
228732V1-021 C
Adder
0.119
20335126GROZ1-110
Adder
2.833
20335226CANZ2-011
Adder
2.754
228351V2-046C
Solar/Wind Harmer
1.269
970997AG2-616 GEN
Solar/Wind Harmer
6.037
945431AF1-208 GEN
Solar/Wind Harmer
5.431
213958STHWK5-6
Adder
1.718
228206SHRMN CT
Adder
10.413
213497CHSTR7-9
Adder
1.697
213497CHSTR7-9
Adder
1.697
960051AF2-296 GEN
Solar/Wind Harmer
2.38
970643AG2-418 GEN
Solar/Wind Harmer
2.362
944411AF1-106 GEN
Solar/Wind Harmer
0.266
205967AE2-211_GEN
Solar/Wind Harmer
6.57
231917EM10
Adder
1.516
231918WEST 1
Adder
2.152
233972AC1-094 C
Solar/Wind Harmer
0.424
232901NORTHST
Adder
5.316
232900DEMECSMY
Adder
5.892
972177AH1-672 GEN
Solar/Wind Harmer
8.57
233954AC2-188 GEN
Solar/Wind Harmer
0.718
233950AC2-186 GEN
Solar/Wind Harmer
0.359
232434Z2-077 GEN
Solar/Wind Harmer
0.16
232910NRG_G1
Adder
5.506
232404W1-003 C
Solar/Wind Harmer
0.638
232917OH NUG6
Adder
5.605
232915OH NUG4
Adder
5.592
971195AH1-057 GEN
Solar/Wind Harmer
0.698
233998TM1NIN_3.36
Solar/Wind Harmer
0.807
232428Y3-058 C
Solar/Wind Harmer
0.532
965821AG1-450 GEN
Solar/Wind Harmer
3.317
232919VN10
Adder
1.788
232426Y1-080 FULL
Solar/Wind Harmer
0.122
970277AG2-181 GEN
Solar/Wind Harmer
3.195
233964AF2-378 GEN
Solar/Wind Harmer
0.081
232422X3-066 FULL
Solar/Wind Harmer
0.159
234012AE2-112_GEN
Solar/Wind Harmer
1.463
233930AB2-032 GEN
Solar/Wind Harmer
0.531
233915AB1-141 GEN
Solar/Wind Harmer
0.63
238202AE2-262_GEN
Solar/Wind Harmer
2.898
971627AH1-313 GEN
Solar/Wind Harmer
11.361
203854AF2-039 C
Solar/Wind Harmer
0.461
20334926Z1-069 C
Solar/Wind Harmer
2.308
966131AG1-482 GEN
Solar/Wind Harmer
0.094
205975AE2-345_GEN
Solar/Wind Harmer
6.986
971703AH1-357 GEN
Solar/Wind Harmer
1.95
971707AH1-359 GEN
Solar/Wind Harmer
1.95
208923BUSO V4-027
Solar/Wind Harmer
0.256
208856AE1-226 GEN
Solar/Wind Harmer
1.812
20089126CSLMN_L13
Solar/Wind Harmer
0.8
20089026BF_G21_K23
Solar/Wind Harmer
0.633
237048AF1-022 C
Solar/Wind Helper
0.21
237043AE2-125 C
Solar/Wind Helper
0.204
964991AG1-363 GEN
Solar/Wind Helper
3.553
235058AG1-386 C
Solar/Wind Helper
0.395
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.176
G-007ALTFEXP_G-007A->PJM
CMTX
36.124
CBM NorthLTFEXP_CBM-N->PJM
CBM
71.911
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
4.323
BlueGrassPJM->LTFIMP_BlueG
CLTF
13.437
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
98.702
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.084
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
19.476

Details for KEYSTONE-01SOBEND 500.0 kV Ckt 1 line l/o PN_P2-3_PN-500-004-DRT-002_SRT-SL


Base Case Flowgate

Area:AP/PJM
Facility Description:
KEYSTONE-01SOBEND 500.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-500-004-DRT-002_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.79 %
Rating:2078.0 MVA
Rating Type:B
MVA to Mitigate:2239.81
MW Contribution:4.83
Bus #Bus NameTypeMW Contribution
200033KEYS G2
50/50
10.214
200031CONE G2
50/50
8.262
200031CONE G2
50/50
7.69
20080926SITHE
50/50
0.407
20088626ARWF_N39
Solar/Wind Harmer
3.124
20303426NA_O38_P22
Solar/Wind Harmer
2.529
209137AF2-361 C
Solar/Wind Harmer
3.172
209130AF1-271A GEN
Solar/Wind Harmer
2.676
946751AF1-339 GEN
Solar/Wind Harmer
0.95
209054AE2-059 GEN
Solar/Wind Harmer
1.598
209059AE2-084 GEN
Solar/Wind Harmer
2.359
961431AF2-434 GEN
Solar/Wind Harmer
0.927
971441AH1-212 GEN
Solar/Wind Harmer
3.06
203857AF2-221 C
Solar/Wind Harmer
2.291
970123AG2-090 GEN
Solar/Wind Harmer
2.139
961541AF2-445A GEN
Solar/Wind Harmer
3.008
203940AF1-140 C
Solar/Wind Harmer
0.746
20084626FORWARD
Solar/Wind Harmer
1.167
203839AF1-321 GEN
Solar/Wind Harmer
2.951
208972BECR K09
Solar/Wind Harmer
0.941
209029WAYMART-WD
Solar/Wind Harmer
2.518
209009PEIP 2
Adder
6.838
209010PEIP 1
Adder
3.098
209010PEIP 1
Adder
0.454
211065PSPA IPP
Solar/Wind Harmer
0.377
211065PSPA IPP
Solar/Wind Harmer
0.377
946071AF1-272 GEN
Solar/Wind Harmer
4.639
966111AG1-480 GEN
Solar/Wind Harmer
0.069
966111AG1-480 GEN
Solar/Wind Harmer
2.644
20465127PORT CT
Adder
3.147
20674128FR_U2-059
Solar/Wind Harmer
0.145
20634528N27_Y2-018
Solar/Wind Harmer
0.21
964851AG1-348 GEN
Solar/Wind Harmer
1.368
207471AF2-354 C
Solar/Wind Harmer
0.396
20674928WA_W3-044
Solar/Wind Harmer
0.373
20676228FRD_X1-012
Solar/Wind Harmer
0.454
20088926STNY CRK
Solar/Wind Harmer
1.63
971427AH1-205 GEN
Solar/Wind Harmer
1.966
217204WCALDSOLAR C
Solar/Wind Harmer
0.054
217086KRNY_131
Adder
6.822
217083KRNY_132
Adder
6.764
217206BARNGR HS C
Solar/Wind Harmer
0.023
217201HACKENSOLA C
Solar/Wind Harmer
0.054
972237AH1-703 GEN
Adder
7.407
217202FBANKSOLAR C
Solar/Wind Harmer
0.054
20674528F3S_W2-016
Solar/Wind Harmer
1.032
20671828STAW2-080
Solar/Wind Harmer
0.077
217081WEATEXAS C
Solar/Wind Harmer
0.062
219036LINDEN_G7
Adder
12.077
219035LINDEN_G8
Adder
11.905
972261AH1-715 GEN2
Adder
11.561
207442AE1-156 GEN
Solar/Wind Harmer
0.536
20676128MHD_W3-029
Solar/Wind Harmer
0.344
218418LINDEN_G5
Adder
12.307
218419LINDEN_G6
Adder
12.307
972260AH1-715 GEN1
Adder
9.855
20673828FLE_V3-070
Solar/Wind Harmer
0.327
218440SUMMTASSOC C
Solar/Wind Harmer
0.091
924131AB2-057 GEN
Solar/Wind Harmer
0.722
20716928W4-060COL
Solar/Wind Harmer
0.494
20720628TIN_W1-124
Solar/Wind Harmer
0.682
20641628MLH_W1-032
Solar/Wind Harmer
0.201
20465527S.RDG CT
Adder
2.084
20478527GLRA_Q45
Adder
0.265
219817TRENTONSOL C
Solar/Wind Harmer
0.75
20628028LAKEHURS
Adder
0.637
20714928UPF_X1-085
Solar/Wind Harmer
0.271
963391AG1-188 GEN
Solar/Wind Harmer
1.275
219114HARTZY_C
Solar/Wind Harmer
0.556
963401AG1-189 GEN
Solar/Wind Harmer
0.764
207500AE2-000G1
Solar/Wind Harmer
20.861
207497AE2-000G2
Solar/Wind Harmer
20.861
207507AE2-000G3
Solar/Wind Harmer
20.861
20636128O CRK C2
Adder
4.268
20716428NHV_W2-082
Solar/Wind Harmer
1.173
203952AE2-129 C
Solar/Wind Harmer
0.751
203946AE2-131 C
Solar/Wind Harmer
0.749
962411AG1-090 GEN
Solar/Wind Harmer
11.772
20083426SW_E13_K22
Solar/Wind Harmer
0.368
213535CROYDN11
Adder
6.633
219615MILLCREEK C
Solar/Wind Harmer
0.154
213815MOSER1-3
Adder
2.288
213815MOSER1-3
Adder
2.288
219921AF1-264
Solar/Wind Harmer
0.092
230407AD2-065 C
Solar/Wind Harmer
0.083
970313AG2-206 GEN
Solar/Wind Harmer
5.817
230422AE1-104_GEN1
Solar/Wind Harmer
21.299
230425AE1-104_GEN2
Solar/Wind Harmer
21.299
972233AH1-701 GEN
Adder
2.653
230433AD2-135 GEN
Solar/Wind Harmer
0.064
228304LOGAN
Adder
15.28
228307PCLP GT
Adder
7.628
228251CARLLS#4
Adder
0.397
216419AE2-001 C
Solar/Wind Harmer
2.402
20398826ARMNA MT
Solar/Wind Harmer
2.799
203859AF2-294 C
Solar/Wind Harmer
2.031
213587EDDYSTN3
Adder
49.629
213589EDDYSTN4
Adder
49.623
203853AF1-134 C O1
Solar/Wind Harmer
0.719
233939AC1-091 C
Solar/Wind Harmer
0.561
233970AC1-092 C
Solar/Wind Harmer
0.561
971149AH1-027 GEN
Solar/Wind Harmer
2.162
232899W1-062
Adder
6.143
232416X2-083
Adder
0.288
970545AG2-347 GEN
Solar/Wind Harmer
41.727
231940T-011
Adder
0.476
972069AH1-584 GEN
Solar/Wind Harmer
5.709
972071AH1-585 GEN
Solar/Wind Harmer
5.709
971747AH1-380 GEN
Solar/Wind Harmer
2.283
233901CHERRYDALE C
Solar/Wind Harmer
0.718
232408W1-005 C
Solar/Wind Harmer
0.638
232410W1-006 C
Solar/Wind Harmer
0.638
232918OH NUG7
Adder
5.592
200032KEYS G1
50/50
10.224
200033KEYS G2
50/50
9.821
200030CONE G1
50/50
7.621
957561AF2-050 GEN
Solar/Wind Harmer
8.479
209067AE2-060 GEN
Solar/Wind Harmer
1.64
946691AF1-333 GEN
Solar/Wind Harmer
0.95
946741AF1-338 GEN
Solar/Wind Harmer
0.95
20088826HIGHLAND
Solar/Wind Harmer
2.526
972245AH1-707 GEN
Adder
5.084
961331AF2-424 GEN
Solar/Wind Harmer
0.927
961421AF2-433 GEN
Solar/Wind Harmer
0.927
957921AF2-086 GEN
Solar/Wind Harmer
0.901
209142AF1-226 GEN
Solar/Wind Harmer
5.365
209093AE2-110 GEN
Solar/Wind Harmer
2.317
209120AE2-241 GEN
Solar/Wind Harmer
3.066
964201AG1-281 GEN
Solar/Wind Harmer
0.92
209027LOR2_Q27
Solar/Wind Harmer
4.188
209022WHFR IPP
Adder
3.006
203987AE2-118 C
Solar/Wind Harmer
3.014
964391AG1-301 GEN
Solar/Wind Harmer
0.896
970631AG2-411 GEN
Solar/Wind Harmer
9.297
203843AF2-002_GEN
Solar/Wind Harmer
1.475
963161AG1-165 GEN
Solar/Wind Harmer
0.886
209025WIENIPP3
Adder
4.671
963071AG1-156 GEN
Solar/Wind Harmer
2.432
970095AG2-074 GEN
Solar/Wind Harmer
5.519
971279AH1-102 GEN
Solar/Wind Harmer
11.69
20094526CT_V3-030
Solar/Wind Harmer
0.992
20465427SHAW CT
Adder
3.099
20466127PORT 5CT
Adder
21.011
971007AG2-625 GEN
Solar/Wind Harmer
2.002
20633028GILCT9
Adder
22.239
966181AG1-487 GEN
Solar/Wind Harmer
0.197
20674628WNG_W3-110
Solar/Wind Harmer
0.309
207510AF2-138 C
Solar/Wind Harmer
1.359
20676728BRNX1-095
Solar/Wind Harmer
0.131
217194REDH C
Solar/Wind Harmer
0.361
217169METRODIV C
Solar/Wind Harmer
0.029
217186ESSEX_G9
Adder
11.707
217211CAMDEN ST C
Solar/Wind Harmer
0.018
20673728F2S_V4-070
Solar/Wind Harmer
0.129
219249CENTRALDIV C
Solar/Wind Harmer
0.028
219908AB1-139 C
Solar/Wind Harmer
0.271
219919AE1-041 FULL
Solar/Wind Harmer
0.029
971423AH1-203 GEN
Solar/Wind Harmer
9.109
20635028RRCT1&2
Adder
8.307
20635128RRCT3&4
Adder
6.887
20635828PARLN1&2
Adder
2.352
20635928PARLN3&4
Adder
2.352
967451AG2-055 C O1
Solar/Wind Harmer
120.09
218438BLK ROCK C
Solar/Wind Harmer
0.095
219612MATRIX C
Solar/Wind Harmer
0.128
20720528MAN_W1-024
Solar/Wind Harmer
0.174
20716228APLW2-078
Solar/Wind Harmer
0.605
219918AC2-009 C
Solar/Wind Harmer
0.042
20714528FRN_Y2-051
Solar/Wind Harmer
0.199
219276PARKLANDSO C
Solar/Wind Harmer
0.312
971667AH1-334 GEN
Solar/Wind Harmer
1.836
219727YARDVSOLFA C
Solar/Wind Harmer
0.61
20636028O CRK C1
Adder
4.681
20715028HAN_X4-015
Solar/Wind Harmer
0.197
20720828JCB_W4-025
Solar/Wind Harmer
0.299
20716028EGP_W2-019
Solar/Wind Harmer
0.306
972221AH1-695 GEN
Adder
110.049
959561AF2-247 GEN
Solar/Wind Harmer
0.319
219610FLORENCE C
Solar/Wind Harmer
0.898
219348LDSOLAR C
Solar/Wind Harmer
0.388
219221BRL12CT1
Adder
5.788
219223BRL12CT3
Adder
5.788
219906AC1-017 C
Solar/Wind Harmer
0.144
213815MOSER1-3
Adder
2.288
219236SOUTHERNHQ C
Solar/Wind Harmer
0.043
219291REEVESSOUT C
Solar/Wind Harmer
0.038
219912AD2-042 GEN
Solar/Wind Harmer
0.509
219766PARADISE C
Solar/Wind Harmer
0.201
219623KINSLEYBEA C
Solar/Wind Harmer
0.272
213560DLW11-12
Adder
1.734
228729W2-030 C
Solar/Wind Harmer
0.366
238215AE2-248 C
Solar/Wind Harmer
1.939
970511AG2-327 GEN
Solar/Wind Harmer
1.212
230415AB2-049 C
Solar/Wind Harmer
0.12
228304LOGAN
Adder
13.743
230430AE1-229_GEN
Solar/Wind Harmer
5.544
971553AH1-274 GEN
Solar/Wind Harmer
1.523
213958STHWK5-6
Adder
1.718
228711V2-041C
Solar/Wind Harmer
0.377
228202CUMB CT
Adder
10.369
959471AF2-238 GEN
Solar/Wind Harmer
0.727
970337AG2-221 GEN
Solar/Wind Harmer
2.406
213497CHSTR7-9
Adder
1.697
20326126BLOSSBCT
Adder
2.714
970643AG2-418 GEN
Solar/Wind Harmer
1.099
20335026MILZ1-092
Adder
2.683
944411AF1-106 GEN
Solar/Wind Harmer
2.472
972251AH1-710 GEN
Adder
29.207
233971AC1-093 C
Solar/Wind Harmer
0.501
970695AG2-447 GEN
Solar/Wind Harmer
2.29
233952AC2-187 GEN
Solar/Wind Harmer
0.718
972133AH1-634 GEN
Solar/Wind Harmer
6.322
972073AH1-586 GEN
Solar/Wind Harmer
5.974
233990AG1-397 GEN
Solar/Wind Harmer
0.731
232406W1-004 FULL
Solar/Wind Harmer
0.638
234015AF2-250 C
Solar/Wind Harmer
0.077
232914OH NUG3
Adder
5.63
232916OH NUG5
Adder
5.63
232921TASLEY2G
Adder
3.29
233900O-025 C
Adder
0.751
233996TM1833_GEN
Solar/Wind Harmer
0.807
233997TMININ_4.2
Solar/Wind Harmer
0.807
233940AF2-379 C
Solar/Wind Harmer
0.119
233994AC2-023 GEN
Solar/Wind Harmer
1.713
960671AF2-358 GEN
Solar/Wind Harmer
11.411
232907VN8
Adder
15.629
232417X3-008 C
Solar/Wind Harmer
1.274
233982AB2-133 GEN
Solar/Wind Harmer
3.1
233918AB1-142 GEN
Solar/Wind Harmer
0.63
238206AE2-263_GEN
Solar/Wind Harmer
2.701
972169AH1-667 GEN
Solar/Wind Harmer
2.031
203954AE2-126 C
Solar/Wind Harmer
0.634
966131AG1-482 GEN
Solar/Wind Harmer
2.083
970713AG2-456 GEN
Solar/Wind Harmer
7.799
971705AH1-358 GEN
Solar/Wind Harmer
2.267
971709AH1-360 GEN
Solar/Wind Harmer
2.267
205917AD1-020 ES
Solar/Wind Harmer
0.385
20089226LOOKOUT
Solar/Wind Harmer
0.779
237046AF1-021 C
Solar/Wind Helper
0.659
232905CHERITON_25
Adder
1.564
232926CRISFLD1
Adder
1.251
233946AB2-136 GEN
Solar/Wind Harmer
2.543
234036AF2-325 C
Solar/Wind Harmer
0.584
234041AC1-190 GEN
Solar/Wind Harmer
5.704
233987AB2-037 GEN
Solar/Wind Harmer
7.241
233944AB2-135 GEN
Solar/Wind Harmer
3.334
232424Y1-079 C
Solar/Wind Harmer
0.358
233984AB2-036 GEN
Solar/Wind Harmer
7.922
234014AF1-036_GEN
Solar/Wind Harmer
1.722
233933AB2-153 GEN
Solar/Wind Harmer
0.716
208835TUHI V3-051
Solar/Wind Harmer
0.038
208835TUHI V3-051
Solar/Wind Harmer
0.038
972075AH1-587 GEN
Solar/Wind Harmer
20.001
972077AH1-588 GEN
Solar/Wind Harmer
23.398
972079AH1-589 GEN
Solar/Wind Harmer
19.272
970715AG2-457 GEN
Solar/Wind Harmer
7.799
205916AD1-020 GEN
Solar/Wind Harmer
1.791
944781AF1-143 GEN
Solar/Wind Harmer
2.742
238217AF1-153 C O1
Solar/Wind Harmer
0.544
23652301WDPWR_K20
Solar/Wind Helper
0.194
200104AA1-076 CT2
50/50
6.15
200103AA1-076 CT1
50/50
6.096
20083726HOMER C1
Adder
119.115
203961AE2-224 GEN
Solar/Wind Harmer
5.136
959431AF2-234 GEN
Solar/Wind Harmer
1.903
964051AG1-259 GEN
Solar/Wind Harmer
1.276
964061AG1-260 GEN
Solar/Wind Harmer
1.276
959421AF2-233 GEN
Solar/Wind Harmer
0.952
20092526R32
Solar/Wind Harmer
2.707
209045AE2-271 GEN
Solar/Wind Harmer
15.641
20091526CHSTN_FL
Solar/Wind Harmer
1.307
941231AE2-117 GEN
Solar/Wind Harmer
0.891
203850AG1-041 C
Solar/Wind Harmer
1.767
209026WIENIPP4
Adder
4.719
203844AF2-092 C
Solar/Wind Harmer
1.755
961261AF2-417 GEN
Solar/Wind Harmer
0.858
209116AE2-175 GEN
Solar/Wind Harmer
3.375
966421AG1-511 GEN
Solar/Wind Harmer
6.823
20462827N BANGR8
Adder
0.566
20675128HRM_W1-127
Solar/Wind Harmer
0.134
207408W3-077 C
Solar/Wind Harmer
0.397
20675728RH_W2-091
Solar/Wind Harmer
0.268
207484AF2-139 C O1
Solar/Wind Harmer
0.396
971009AG2-626 GEN
Solar/Wind Harmer
1.277
20675928HOL_W4-097
Solar/Wind Harmer
0.102
20674828DL_W4-046
Solar/Wind Harmer
0.5
207511W3-106 GEN
Solar/Wind Harmer
0.503
20676328BVR_Y1-020
Solar/Wind Harmer
0.252
207530AG1-191 GEN
Solar/Wind Harmer
1.052
20083926HOMER C3
Adder
95.203
20083826HOMER C2
Adder
89.93
20090526Q36
Solar/Wind Harmer
2.07
203993AD2-133_GEN1
Solar/Wind Harmer
2.07
966261AG1-495 GEN
Solar/Wind Harmer
1.343
217167KRNY_14
Adder
6.808
217086KRNY_131
Adder
6.75
217147KRNY_1212
Adder
6.475
217147KRNY_1212
Adder
6.36
217146KRNY_1234
Adder
6.345
217146KRNY_1234
Adder
6.302
218404KENILWRTH C
Adder
0.952
20390726Y2-042
Adder
3.066
218524CNTRALGAS1 C
Solar/Wind Harmer
0.263
218526CNTRALGAS2 C
Solar/Wind Harmer
0.262
20675528CPH_W2-050
Solar/Wind Harmer
0.332
218455CINNBAY_CGEN
Adder
1.275
20635928PARLN3&4
Adder
5.193
20720428HOL_W1-112
Solar/Wind Harmer
0.239
971521AH1-258 GEN
Solar/Wind Harmer
1.866
20486527WR_V4-052
Adder
0.84
20714428HOW_X1-037
Solar/Wind Harmer
0.844
20714328BYD_X4-031
Solar/Wind Harmer
0.193
20334726NME_Y1-047
Adder
2.991
219620RIDERU C
Solar/Wind Harmer
0.038
207459AE1-142 C O1
Solar/Wind Harmer
0.705
971189AH1-054 GEN
Solar/Wind Harmer
0.785
970025AG2-016 GEN
Solar/Wind Harmer
1.884
203926AA2-133 GEN
Adder
2.948
208862AG1-362 C
Solar/Wind Harmer
0.628
20715728PEM_W1-119
Solar/Wind Harmer
0.353
20715828PEM_W1-120
Solar/Wind Harmer
0.353
20717128DIX_Z2-102
Solar/Wind Harmer
0.872
214067T20SOLAR
Solar/Wind Harmer
0.166
213611FALLS1-3
Adder
2.318
213611FALLS1-3
Adder
2.318
965121AG1-377 GEN
Solar/Wind Harmer
2.478
219607WPEMNERT C
Solar/Wind Harmer
0.272
219224BRL12CT4
Adder
5.788
219688LUMSOLAR_S C
Solar/Wind Harmer
0.13
219272CLEANLIGHT C
Solar/Wind Harmer
0.117
219914AD2-027 C
Solar/Wind Harmer
0.384
213561DLWR9-10
Adder
2.268
213561DLWR9-10
Adder
1.734
227927V4-067C
Solar/Wind Harmer
0.126
228754AB1-001 C
Solar/Wind Harmer
0.088
219137THOSOLAR C
Solar/Wind Harmer
0.768
971535AH1-265 GEN
Solar/Wind Harmer
2.692
971011AG2-627 GEN
Solar/Wind Harmer
4.834
964001AG1-254 GEN
Solar/Wind Harmer
1.28
972141AH1-641 GEN
Solar/Wind Harmer
1.811
228260V4-054C
Solar/Wind Harmer
0.646
228309CCLP NUG
Adder
16.257
228309CCLP NUG
Adder
15.464
213957STHWK3-4
Adder
1.718
213957STHWK3-4
Adder
1.718
213942SCHUYLKILL
Adder
2.245
213942SCHUYLKILL
Adder
1.717
970453AG2-297 GEN
Solar/Wind Harmer
1.729
970555AG2-356 GEN
Solar/Wind Harmer
2.406
231919CHRIST1
Adder
2.835
231920CHRIST2
Adder
2.772
205951AE1-129_GEN
Solar/Wind Harmer
9.022
233973AC2-185 C
Solar/Wind Harmer
2.31
234033AF1-007_GEN
Solar/Wind Harmer
14.911
232904IR4
Adder
51.558
232920IR10
Adder
2.015
232432Z2-076 GEN
Solar/Wind Harmer
0.084
232813VAUGHN
Adder
0.375
233990AG1-397 GEN
Solar/Wind Harmer
0.035
232912OH NUG1
Adder
5.63
232913OH NUG2
Adder
5.555
233923SMA
Solar/Wind Harmer
2.96
233955AB2-172 GEN
Solar/Wind Harmer
3.185
232436AB1-176 C
Solar/Wind Harmer
0.146
233968AD2-076_GEN
Solar/Wind Harmer
4.218
970597AG2-380 GEN
Solar/Wind Harmer
2.649
971983AH1-536 GEN
Solar/Wind Harmer
4.76
233935AB2-179 C
Solar/Wind Harmer
1.589
203855AF2-088 C
Solar/Wind Harmer
0.222
205932AD2-116_GEN
Solar/Wind Harmer
0.622
205956AE1-196_GEN
Solar/Wind Harmer
0.622
205943AE1-185 GEN
Solar/Wind Harmer
0.62
960921AF2-383 GEN
Solar/Wind Harmer
0.206
960921AF2-383 GEN
Solar/Wind Harmer
1.585
940863AE2-074 GEN
Solar/Wind Harmer
1.844
203804AE2-113_GEN
Solar/Wind Harmer
4.781
23750501ELLIOTTS
Solar/Wind Helper
0.734
200032KEYS G1
50/50
9.838
200030CONE G1
50/50
8.363
200105AA1-076 ST
50/50
6.971
20083326SEWRDB34
50/50
6.196
20079426CONEMAGH
50/50
2.01
972241AH1-705 GEN
Adder
5.792
209071AE2-133 GEN
Solar/Wind Harmer
1.612
970665AG2-430 GEN
Solar/Wind Harmer
9.444
209018SUNBIPCT
Adder
7.089
946731AF1-337 GEN
Solar/Wind Harmer
0.95
212507AE2-042_GEN
Solar/Wind Harmer
2.831
961341AF2-425 GEN
Solar/Wind Harmer
0.927
212174INGE
Adder
1.025
970125AG2-091 GEN
Solar/Wind Harmer
0.917
212266LOR1
Solar/Wind Harmer
0.12
970237AG2-161 GEN
Solar/Wind Harmer
3.216
971879AH1-460 GEN
Solar/Wind Harmer
9.935
203841AF2-001_GEN
Solar/Wind Harmer
2.951
961301AF2-421 GEN
Solar/Wind Harmer
0.886
963151AG1-164 GEN
Solar/Wind Harmer
0.886
209023WIENIPP1
Adder
9.55
209025WIENIPP3
Adder
4.767
971541AH1-268 GEN
Solar/Wind Harmer
4.975
209010PEIP 1
Adder
0.563
208909MACR G3
Adder
127.852
20465127PORT CT
Adder
2.371
20671928W4-073
Solar/Wind Harmer
0.341
207518AF1-320_GEN
Solar/Wind Harmer
2.865
207437AD2-070 GEN
Solar/Wind Harmer
0.236
971519AH1-257 GEN
Solar/Wind Harmer
1.965
966181AG1-487 GEN
Solar/Wind Harmer
2.943
20675828AU_W4-064
Solar/Wind Harmer
0.133
207439AE1-081 C O1
Solar/Wind Harmer
0.046
20674328GAR_V4-001
Solar/Wind Harmer
0.084
971419AH1-201 GEN
Solar/Wind Harmer
4.227
217208PARK ELE C
Solar/Wind Harmer
0.019
217083KRNY_132
Adder
6.808
217121ECCF
Adder
0.318
217209CENTRL HS C
Solar/Wind Harmer
0.033
218449LINSOLAR C
Solar/Wind Harmer
0.726
20676428JCR_X2-075
Solar/Wind Harmer
0.247
970679AG2-439 GEN
Solar/Wind Harmer
1.281
207528AF2-192 GEN
Solar/Wind Harmer
0.398
20673628F1S_V4-069
Solar/Wind Harmer
0.129
20675428EAM_W2-061
Solar/Wind Harmer
0.136
972275AH1-722 GEN
Adder
22.624
217213AMBOY SO C
Solar/Wind Harmer
0.09
218428ETC SOLAR C
Solar/Wind Harmer
0.026
205941AD2-115 GEN
Solar/Wind Harmer
0.726
209008PAXT IPP
Adder
1.707
20635028RRCT1&2
Adder
8.179
20635128RRCT3&4
Adder
7.895
20635828PARLN1&2
Adder
5.193
217197RE CRAN C
Solar/Wind Harmer
0.372
20742028HF_AC1-207
Solar/Wind Harmer
0.539
20467927PC_Q59Y356
Adder
0.659
20715228NPK_W1-113
Solar/Wind Harmer
0.295
207454AA2-184 E
Solar/Wind Harmer
0.685
20465527S.RDG CT
Adder
2.154
219680HOPEWELLV C1
Solar/Wind Harmer
0.052
200917MEHOOPANY_G
Solar/Wind Harmer
4.452
20714828MDF_W3-079
Solar/Wind Harmer
0.207
963711AG1-223 GEN
Solar/Wind Harmer
1
207445AB1-138_GEN
Solar/Wind Harmer
0.388
20628028LAKEHURS
Adder
1.26
970899AG2-561 GEN
Solar/Wind Harmer
2.52
207487AE2-000G4
Solar/Wind Harmer
20.861
207522AF2-254 C
Solar/Wind Harmer
0.947
20720728JCB_W1-129
Solar/Wind Harmer
0.197
972271AH1-720 GEN
Adder
8.193
213611FALLS1-3
Adder
2.318
214194N WALES4
Adder
0.558
965131AG1-378 GEN
Solar/Wind Harmer
2.478
20328326MANOR_T86
Adder
0.176
941421AE2-139 GEN
Solar/Wind Harmer
3.761
203818AF1-086 GEN
Solar/Wind Harmer
3.159
219304NAMERICA C
Solar/Wind Harmer
0.201
219222BRL12CT2
Adder
5.788
219287REEVESEAST C
Solar/Wind Harmer
0.863
219686LUMSOLAR_N C
Solar/Wind Harmer
0.13
219907AC1-030 C
Solar/Wind Harmer
0.089
218660EHAMPSOLAR C
Solar/Wind Harmer
0.112
219904AC1-010 C
Solar/Wind Harmer
0.241
219258KINSLEYDEP C
Solar/Wind Harmer
0.206
213560DLW11-12
Adder
1.734
228728W1-130C
Solar/Wind Harmer
0.42
970335AG2-220 GEN
Solar/Wind Harmer
3.755
971127AH1-005 GEN
Solar/Wind Harmer
2.422
230434AG1-499 GEN
Solar/Wind Harmer
0.367
230511AF1-262
Solar/Wind Harmer
0.115
228732V1-021 C
Adder
0.119
20335126GROZ1-110
Adder
2.833
20335226CANZ2-011
Adder
2.754
228351V2-046C
Solar/Wind Harmer
1.269
970997AG2-616 GEN
Solar/Wind Harmer
6.037
945431AF1-208 GEN
Solar/Wind Harmer
5.431
213958STHWK5-6
Adder
1.718
228206SHRMN CT
Adder
10.413
213497CHSTR7-9
Adder
1.697
213497CHSTR7-9
Adder
1.697
960051AF2-296 GEN
Solar/Wind Harmer
2.38
970643AG2-418 GEN
Solar/Wind Harmer
2.362
944411AF1-106 GEN
Solar/Wind Harmer
0.266
205967AE2-211_GEN
Solar/Wind Harmer
6.57
231917EM10
Adder
1.516
231918WEST 1
Adder
2.152
233972AC1-094 C
Solar/Wind Harmer
0.424
232901NORTHST
Adder
5.316
232900DEMECSMY
Adder
5.892
972177AH1-672 GEN
Solar/Wind Harmer
8.57
233954AC2-188 GEN
Solar/Wind Harmer
0.718
233950AC2-186 GEN
Solar/Wind Harmer
0.359
232434Z2-077 GEN
Solar/Wind Harmer
0.16
232910NRG_G1
Adder
5.506
232404W1-003 C
Solar/Wind Harmer
0.638
232917OH NUG6
Adder
5.605
232915OH NUG4
Adder
5.592
971195AH1-057 GEN
Solar/Wind Harmer
0.698
233998TM1NIN_3.36
Solar/Wind Harmer
0.807
232428Y3-058 C
Solar/Wind Harmer
0.532
965821AG1-450 GEN
Solar/Wind Harmer
3.317
232919VN10
Adder
1.788
232426Y1-080 FULL
Solar/Wind Harmer
0.122
970277AG2-181 GEN
Solar/Wind Harmer
3.195
233964AF2-378 GEN
Solar/Wind Harmer
0.081
232422X3-066 FULL
Solar/Wind Harmer
0.159
234012AE2-112_GEN
Solar/Wind Harmer
1.463
233930AB2-032 GEN
Solar/Wind Harmer
0.531
233915AB1-141 GEN
Solar/Wind Harmer
0.63
238202AE2-262_GEN
Solar/Wind Harmer
2.898
971627AH1-313 GEN
Solar/Wind Harmer
11.361
203854AF2-039 C
Solar/Wind Harmer
0.461
20334926Z1-069 C
Solar/Wind Harmer
2.308
966131AG1-482 GEN
Solar/Wind Harmer
0.094
205975AE2-345_GEN
Solar/Wind Harmer
6.986
971703AH1-357 GEN
Solar/Wind Harmer
1.95
971707AH1-359 GEN
Solar/Wind Harmer
1.95
208923BUSO V4-027
Solar/Wind Harmer
0.256
208856AE1-226 GEN
Solar/Wind Harmer
1.812
20089126CSLMN_L13
Solar/Wind Harmer
0.8
20089026BF_G21_K23
Solar/Wind Harmer
0.633
237048AF1-022 C
Solar/Wind Helper
0.21
237043AE2-125 C
Solar/Wind Helper
0.204
964991AG1-363 GEN
Solar/Wind Helper
3.553
235058AG1-386 C
Solar/Wind Helper
0.395
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.176
G-007ALTFEXP_G-007A->PJM
CMTX
36.124
CBM NorthLTFEXP_CBM-N->PJM
CBM
71.911
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
4.323
BlueGrassPJM->LTFIMP_BlueG
CLTF
13.437
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
98.702
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.084
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
19.476

Details for N PHILA8-MASTER 230.0 kV Ckt 1 line l/o PECO_P4_CHICH045_SRT-A/* $ DELCO $ PECO_P4_CHICH045 $ STBK


Base Case Flowgate

Area:PECO
Facility Description:
N PHILA8-MASTER 230.0 kV Ckt 1 line
Contingency Name:
PECO_P4_CHICH045_SRT-A/* $ DELCO $ PECO_P4_CHICH045 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.92 %
Rating:572.0 MVA
Rating Type:B
MVA to Mitigate:628.77
MW Contribution:2.42
Bus #Bus NameTypeMW Contribution
219921AF1-264
Solar/Wind Harmer
0.061
219615MILLCREEK C
Solar/Wind Harmer
0.092
213535CROYDN11
Adder
3.701
972233AH1-701 GEN
Adder
1.437
228304LOGAN
Adder
8.143
228307PCLP GT
Adder
3.965
230407AD2-065 C
Solar/Wind Harmer
0.039
230433AD2-135 GEN
Solar/Wind Harmer
0.029
228251CARLLS#4
Adder
0.177
219114HARTZY_C
Solar/Wind Harmer
0.216
230422AE1-104_GEN1
Solar/Wind Harmer
8.521
230425AE1-104_GEN2
Solar/Wind Harmer
8.521
213918RICHMD91
50/50
0.34
219904AC1-010 C
Solar/Wind Harmer
0.165
219907AC1-030 C
Solar/Wind Harmer
0.059
219258KINSLEYDEP C
Solar/Wind Harmer
0.135
219304NAMERICA C
Solar/Wind Harmer
0.111
219222BRL12CT2
Adder
3.202
218660EHAMPSOLAR C
Solar/Wind Harmer
0.056
219686LUMSOLAR_N C
Solar/Wind Harmer
0.064
219287REEVESEAST C
Solar/Wind Harmer
0.425
230434AG1-499 GEN
Solar/Wind Harmer
0.183
228351V2-046C
Solar/Wind Harmer
0.613
213611FALLS1-3
Adder
1.076
970997AG2-616 GEN
Solar/Wind Harmer
2.828
230511AF1-262
Solar/Wind Harmer
0.054
945431AF1-208 GEN
Solar/Wind Harmer
2.482
228728W1-130C
Solar/Wind Harmer
0.189
228206SHRMN CT
Adder
4.318
228732V1-021 C
Adder
0.048
20720728JCB_W1-129
Solar/Wind Harmer
0.068
219914AD2-027 C
Solar/Wind Harmer
0.274
219137THOSOLAR C
Solar/Wind Harmer
0.47
219607WPEMNERT C
Solar/Wind Harmer
0.15
219224BRL12CT4
Adder
3.202
219272CLEANLIGHT C
Solar/Wind Harmer
0.062
219688LUMSOLAR_S C
Solar/Wind Harmer
0.067
971011AG2-627 GEN
Solar/Wind Harmer
2.415
964001AG1-254 GEN
Solar/Wind Harmer
0.618
228309CCLP NUG
Adder
7.827
228309CCLP NUG
Adder
7.445
214067T20SOLAR
Solar/Wind Harmer
0.077
213611FALLS1-3
Adder
1.076
213611FALLS1-3
Adder
1.076
972141AH1-641 GEN
Solar/Wind Harmer
0.848
971535AH1-265 GEN
Solar/Wind Harmer
1.226
228260V4-054C
Solar/Wind Harmer
0.288
228754AB1-001 C
Solar/Wind Harmer
0.035
970453AG2-297 GEN
Solar/Wind Harmer
0.693
227927V4-067C
Solar/Wind Harmer
0.05
213919RICHMD92
50/50
0.34
219912AD2-042 GEN
Solar/Wind Harmer
0.364
219766PARADISE C
Solar/Wind Harmer
0.137
219236SOUTHERNHQ C
Solar/Wind Harmer
0.029
219623KINSLEYBEA C
Solar/Wind Harmer
0.176
219906AC1-017 C
Solar/Wind Harmer
0.086
219610FLORENCE C
Solar/Wind Harmer
0.497
219348LDSOLAR C
Solar/Wind Harmer
0.215
219221BRL12CT1
Adder
3.202
219223BRL12CT3
Adder
3.202
228304LOGAN
Adder
7.324
219291REEVESSOUT C
Solar/Wind Harmer
0.019
959561AF2-247 GEN
Solar/Wind Harmer
0.148
230415AB2-049 C
Solar/Wind Harmer
0.056
230430AE1-229_GEN
Solar/Wind Harmer
2.592
971553AH1-274 GEN
Solar/Wind Harmer
0.65
228711V2-041C
Solar/Wind Harmer
0.155
228202CUMB CT
Adder
4.218
228729W2-030 C
Solar/Wind Harmer
0.145
219727YARDVSOLFA C
Solar/Wind Harmer
0.223
20716028EGP_W2-019
Solar/Wind Harmer
0.106
20720828JCB_W4-025
Solar/Wind Harmer
0.103
20715028HAN_X4-015
Solar/Wind Harmer
0.068
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.17
G-007ALTFEXP_G-007A->PJM
CMTX
6.714
CBM NorthLTFEXP_CBM-N->PJM
CBM
6.57
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.139
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.434
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
14.815
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.1
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.656

Details for N PHILA8-MASTER 230.0 kV Ckt 1 line l/o PECO_P4_CHICH195_SRT-A/* $ DELCO $ PECO_P4_CHICH195 $ STBK


Base Case Flowgate

Area:PECO
Facility Description:
N PHILA8-MASTER 230.0 kV Ckt 1 line
Contingency Name:
PECO_P4_CHICH195_SRT-A/* $ DELCO $ PECO_P4_CHICH195 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.91 %
Rating:572.0 MVA
Rating Type:B
MVA to Mitigate:628.69
MW Contribution:2.42
Bus #Bus NameTypeMW Contribution
219921AF1-264
Solar/Wind Harmer
0.061
219615MILLCREEK C
Solar/Wind Harmer
0.092
213535CROYDN11
Adder
3.701
972233AH1-701 GEN
Adder
1.437
228304LOGAN
Adder
8.143
228307PCLP GT
Adder
3.965
230407AD2-065 C
Solar/Wind Harmer
0.039
230433AD2-135 GEN
Solar/Wind Harmer
0.029
228251CARLLS#4
Adder
0.177
219114HARTZY_C
Solar/Wind Harmer
0.216
230422AE1-104_GEN1
Solar/Wind Harmer
8.521
230425AE1-104_GEN2
Solar/Wind Harmer
8.521
213918RICHMD91
50/50
0.34
219904AC1-010 C
Solar/Wind Harmer
0.165
219907AC1-030 C
Solar/Wind Harmer
0.059
219258KINSLEYDEP C
Solar/Wind Harmer
0.135
219304NAMERICA C
Solar/Wind Harmer
0.111
219222BRL12CT2
Adder
3.202
218660EHAMPSOLAR C
Solar/Wind Harmer
0.056
219686LUMSOLAR_N C
Solar/Wind Harmer
0.064
219287REEVESEAST C
Solar/Wind Harmer
0.425
230434AG1-499 GEN
Solar/Wind Harmer
0.183
228351V2-046C
Solar/Wind Harmer
0.613
213611FALLS1-3
Adder
1.076
970997AG2-616 GEN
Solar/Wind Harmer
2.828
230511AF1-262
Solar/Wind Harmer
0.054
945431AF1-208 GEN
Solar/Wind Harmer
2.482
228728W1-130C
Solar/Wind Harmer
0.189
228206SHRMN CT
Adder
4.318
228732V1-021 C
Adder
0.048
20720728JCB_W1-129
Solar/Wind Harmer
0.068
219914AD2-027 C
Solar/Wind Harmer
0.274
219137THOSOLAR C
Solar/Wind Harmer
0.47
219607WPEMNERT C
Solar/Wind Harmer
0.15
219224BRL12CT4
Adder
3.202
219272CLEANLIGHT C
Solar/Wind Harmer
0.062
219688LUMSOLAR_S C
Solar/Wind Harmer
0.067
971011AG2-627 GEN
Solar/Wind Harmer
2.415
964001AG1-254 GEN
Solar/Wind Harmer
0.618
228309CCLP NUG
Adder
7.827
228309CCLP NUG
Adder
7.445
214067T20SOLAR
Solar/Wind Harmer
0.077
213611FALLS1-3
Adder
1.076
213611FALLS1-3
Adder
1.076
972141AH1-641 GEN
Solar/Wind Harmer
0.848
971535AH1-265 GEN
Solar/Wind Harmer
1.226
228260V4-054C
Solar/Wind Harmer
0.288
228754AB1-001 C
Solar/Wind Harmer
0.035
970453AG2-297 GEN
Solar/Wind Harmer
0.693
227927V4-067C
Solar/Wind Harmer
0.05
213919RICHMD92
50/50
0.34
219912AD2-042 GEN
Solar/Wind Harmer
0.364
219766PARADISE C
Solar/Wind Harmer
0.137
219236SOUTHERNHQ C
Solar/Wind Harmer
0.029
219623KINSLEYBEA C
Solar/Wind Harmer
0.176
219906AC1-017 C
Solar/Wind Harmer
0.086
219610FLORENCE C
Solar/Wind Harmer
0.497
219348LDSOLAR C
Solar/Wind Harmer
0.215
219221BRL12CT1
Adder
3.202
219223BRL12CT3
Adder
3.202
228304LOGAN
Adder
7.324
219291REEVESSOUT C
Solar/Wind Harmer
0.019
959561AF2-247 GEN
Solar/Wind Harmer
0.148
230415AB2-049 C
Solar/Wind Harmer
0.056
230430AE1-229_GEN
Solar/Wind Harmer
2.592
971553AH1-274 GEN
Solar/Wind Harmer
0.65
228711V2-041C
Solar/Wind Harmer
0.155
228202CUMB CT
Adder
4.218
228729W2-030 C
Solar/Wind Harmer
0.145
219727YARDVSOLFA C
Solar/Wind Harmer
0.223
20716028EGP_W2-019
Solar/Wind Harmer
0.106
20720828JCB_W4-025
Solar/Wind Harmer
0.103
20715028HAN_X4-015
Solar/Wind Harmer
0.068
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.17
G-007ALTFEXP_G-007A->PJM
CMTX
6.714
CBM NorthLTFEXP_CBM-N->PJM
CBM
6.57
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.139
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.434
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
14.815
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.1
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.656

Details for N PHILA8-MASTER 230.0 kV Ckt 1 line l/o PECO_P4_CHICH435_SRT-A/* $ DELCO $ PECO_P4_CHICH435 $ STBK


Base Case Flowgate

Area:PECO
Facility Description:
N PHILA8-MASTER 230.0 kV Ckt 1 line
Contingency Name:
PECO_P4_CHICH435_SRT-A/* $ DELCO $ PECO_P4_CHICH435 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.91 %
Rating:572.0 MVA
Rating Type:B
MVA to Mitigate:628.68
MW Contribution:2.42
Bus #Bus NameTypeMW Contribution
219921AF1-264
Solar/Wind Harmer
0.061
219615MILLCREEK C
Solar/Wind Harmer
0.092
213535CROYDN11
Adder
3.701
972233AH1-701 GEN
Adder
1.437
228304LOGAN
Adder
8.143
228307PCLP GT
Adder
3.965
230407AD2-065 C
Solar/Wind Harmer
0.039
230433AD2-135 GEN
Solar/Wind Harmer
0.029
228251CARLLS#4
Adder
0.177
219114HARTZY_C
Solar/Wind Harmer
0.216
230422AE1-104_GEN1
Solar/Wind Harmer
8.521
230425AE1-104_GEN2
Solar/Wind Harmer
8.521
213918RICHMD91
50/50
0.34
219904AC1-010 C
Solar/Wind Harmer
0.165
219907AC1-030 C
Solar/Wind Harmer
0.059
219258KINSLEYDEP C
Solar/Wind Harmer
0.135
219304NAMERICA C
Solar/Wind Harmer
0.111
219222BRL12CT2
Adder
3.202
218660EHAMPSOLAR C
Solar/Wind Harmer
0.056
219686LUMSOLAR_N C
Solar/Wind Harmer
0.064
219287REEVESEAST C
Solar/Wind Harmer
0.425
230434AG1-499 GEN
Solar/Wind Harmer
0.183
228351V2-046C
Solar/Wind Harmer
0.613
213611FALLS1-3
Adder
1.076
970997AG2-616 GEN
Solar/Wind Harmer
2.828
230511AF1-262
Solar/Wind Harmer
0.054
219914AD2-027 C
Solar/Wind Harmer
0.274
219137THOSOLAR C
Solar/Wind Harmer
0.47
219607WPEMNERT C
Solar/Wind Harmer
0.15
219224BRL12CT4
Adder
3.202
219272CLEANLIGHT C
Solar/Wind Harmer
0.062
219688LUMSOLAR_S C
Solar/Wind Harmer
0.067
971011AG2-627 GEN
Solar/Wind Harmer
2.415
964001AG1-254 GEN
Solar/Wind Harmer
0.618
228309CCLP NUG
Adder
7.828
228309CCLP NUG
Adder
7.446
214067T20SOLAR
Solar/Wind Harmer
0.077
213611FALLS1-3
Adder
1.076
213611FALLS1-3
Adder
1.076
972141AH1-641 GEN
Solar/Wind Harmer
0.848
971535AH1-265 GEN
Solar/Wind Harmer
1.226
228260V4-054C
Solar/Wind Harmer
0.288
228754AB1-001 C
Solar/Wind Harmer
0.035
970453AG2-297 GEN
Solar/Wind Harmer
0.693
227927V4-067C
Solar/Wind Harmer
0.05
213919RICHMD92
50/50
0.34
219912AD2-042 GEN
Solar/Wind Harmer
0.364
219766PARADISE C
Solar/Wind Harmer
0.137
219236SOUTHERNHQ C
Solar/Wind Harmer
0.029
219623KINSLEYBEA C
Solar/Wind Harmer
0.176
219906AC1-017 C
Solar/Wind Harmer
0.086
219610FLORENCE C
Solar/Wind Harmer
0.497
219348LDSOLAR C
Solar/Wind Harmer
0.215
219221BRL12CT1
Adder
3.202
219223BRL12CT3
Adder
3.202
228304LOGAN
Adder
7.324
219291REEVESSOUT C
Solar/Wind Harmer
0.019
959561AF2-247 GEN
Solar/Wind Harmer
0.148
945431AF1-208 GEN
Solar/Wind Harmer
2.482
228728W1-130C
Solar/Wind Harmer
0.189
228206SHRMN CT
Adder
4.318
228732V1-021 C
Adder
0.048
20720728JCB_W1-129
Solar/Wind Harmer
0.068
230415AB2-049 C
Solar/Wind Harmer
0.056
230430AE1-229_GEN
Solar/Wind Harmer
2.592
971553AH1-274 GEN
Solar/Wind Harmer
0.65
228711V2-041C
Solar/Wind Harmer
0.155
228202CUMB CT
Adder
4.218
228729W2-030 C
Solar/Wind Harmer
0.145
219727YARDVSOLFA C
Solar/Wind Harmer
0.223
20716028EGP_W2-019
Solar/Wind Harmer
0.106
20720828JCB_W4-025
Solar/Wind Harmer
0.103
20715028HAN_X4-015
Solar/Wind Harmer
0.068
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.17
G-007ALTFEXP_G-007A->PJM
CMTX
6.715
CBM NorthLTFEXP_CBM-N->PJM
CBM
6.571
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.139
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.434
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
14.815
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.1
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.656

Details for N PHILA8-MASTER 230.0 kV Ckt 1 line l/o PECO_P2-2_CHI230B1_SRT-A/* $ DELCO $ PECO_P2-2_CHI230B1 $ B


Base Case Flowgate

Area:PECO
Facility Description:
N PHILA8-MASTER 230.0 kV Ckt 1 line
Contingency Name:
PECO_P2-2_CHI230B1_SRT-A/* $ DELCO $ PECO_P2-2_CHI230B1 $ B
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:109.9 %
Rating:572.0 MVA
Rating Type:B
MVA to Mitigate:628.63
MW Contribution:2.42
Bus #Bus NameTypeMW Contribution
219914AD2-027 C
Solar/Wind Harmer
0.274
219137THOSOLAR C
Solar/Wind Harmer
0.47
219607WPEMNERT C
Solar/Wind Harmer
0.15
219224BRL12CT4
Adder
3.202
219272CLEANLIGHT C
Solar/Wind Harmer
0.062
219688LUMSOLAR_S C
Solar/Wind Harmer
0.067
971011AG2-627 GEN
Solar/Wind Harmer
2.415
964001AG1-254 GEN
Solar/Wind Harmer
0.618
228309CCLP NUG
Adder
7.827
228309CCLP NUG
Adder
7.445
214067T20SOLAR
Solar/Wind Harmer
0.077
213611FALLS1-3
Adder
1.076
213611FALLS1-3
Adder
1.076
972141AH1-641 GEN
Solar/Wind Harmer
0.848
971535AH1-265 GEN
Solar/Wind Harmer
1.226
228260V4-054C
Solar/Wind Harmer
0.288
228754AB1-001 C
Solar/Wind Harmer
0.035
970453AG2-297 GEN
Solar/Wind Harmer
0.693
227927V4-067C
Solar/Wind Harmer
0.05
213918RICHMD91
50/50
0.34
219904AC1-010 C
Solar/Wind Harmer
0.165
219907AC1-030 C
Solar/Wind Harmer
0.059
219258KINSLEYDEP C
Solar/Wind Harmer
0.135
219304NAMERICA C
Solar/Wind Harmer
0.111
219222BRL12CT2
Adder
3.202
218660EHAMPSOLAR C
Solar/Wind Harmer
0.056
219686LUMSOLAR_N C
Solar/Wind Harmer
0.064
219287REEVESEAST C
Solar/Wind Harmer
0.425
230434AG1-499 GEN
Solar/Wind Harmer
0.183
228351V2-046C
Solar/Wind Harmer
0.613
213611FALLS1-3
Adder
1.076
970997AG2-616 GEN
Solar/Wind Harmer
2.828
230511AF1-262
Solar/Wind Harmer
0.054
945431AF1-208 GEN
Solar/Wind Harmer
2.482
228728W1-130C
Solar/Wind Harmer
0.189
228206SHRMN CT
Adder
4.318
228732V1-021 C
Adder
0.048
20720728JCB_W1-129
Solar/Wind Harmer
0.068
213919RICHMD92
50/50
0.34
219912AD2-042 GEN
Solar/Wind Harmer
0.364
219766PARADISE C
Solar/Wind Harmer
0.137
219236SOUTHERNHQ C
Solar/Wind Harmer
0.029
219623KINSLEYBEA C
Solar/Wind Harmer
0.176
219906AC1-017 C
Solar/Wind Harmer
0.086
219610FLORENCE C
Solar/Wind Harmer
0.497
219348LDSOLAR C
Solar/Wind Harmer
0.215
219221BRL12CT1
Adder
3.202
219223BRL12CT3
Adder
3.202
228304LOGAN
Adder
7.324
219291REEVESSOUT C
Solar/Wind Harmer
0.019
959561AF2-247 GEN
Solar/Wind Harmer
0.148
230415AB2-049 C
Solar/Wind Harmer
0.056
230430AE1-229_GEN
Solar/Wind Harmer
2.592
971553AH1-274 GEN
Solar/Wind Harmer
0.65
228711V2-041C
Solar/Wind Harmer
0.155
228202CUMB CT
Adder
4.218
228729W2-030 C
Solar/Wind Harmer
0.145
219727YARDVSOLFA C
Solar/Wind Harmer
0.223
20716028EGP_W2-019
Solar/Wind Harmer
0.106
20720828JCB_W4-025
Solar/Wind Harmer
0.103
20715028HAN_X4-015
Solar/Wind Harmer
0.068
219921AF1-264
Solar/Wind Harmer
0.061
219615MILLCREEK C
Solar/Wind Harmer
0.092
213535CROYDN11
Adder
3.701
972233AH1-701 GEN
Adder
1.437
228304LOGAN
Adder
8.143
228307PCLP GT
Adder
3.965
230407AD2-065 C
Solar/Wind Harmer
0.039
230433AD2-135 GEN
Solar/Wind Harmer
0.029
228251CARLLS#4
Adder
0.177
219114HARTZY_C
Solar/Wind Harmer
0.216
230422AE1-104_GEN1
Solar/Wind Harmer
8.521
230425AE1-104_GEN2
Solar/Wind Harmer
8.521
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.17
G-007ALTFEXP_G-007A->PJM
CMTX
6.714
CBM NorthLTFEXP_CBM-N->PJM
CBM
6.57
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.139
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.434
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
14.815
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.1
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.656

Details for NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line l/o PJM_500_BG_P4_5_CNSTN_C_SRT-A


Base Case Flowgate

Area:PECO
Facility Description:
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line
Contingency Name:
PJM_500_BG_P4_5_CNSTN_C_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:137.53 %
Rating:578.0 MVA
Rating Type:B
MVA to Mitigate:794.94
MW Contribution:2.32
Bus #Bus NameTypeMW Contribution
213589EDDYSTN4
Adder
31.437
213587EDDYSTN3
Adder
31.41
232416X2-083
Adder
0.19
233933AB2-153 GEN
Solar/Wind Harmer
0.463
233944AB2-135 GEN
Solar/Wind Harmer
2.122
234014AF1-036_GEN
Solar/Wind Harmer
1.085
231131BLOOM ENRGY
Adder
1.715
232424Y1-079 C
Solar/Wind Harmer
0.221
233984AB2-036 GEN
Solar/Wind Harmer
4.865
234041AC1-190 GEN
Solar/Wind Harmer
3.31
233987AB2-037 GEN
Solar/Wind Harmer
4.196
234036AF2-325 C
Solar/Wind Harmer
0.338
233946AB2-136 GEN
Solar/Wind Harmer
1.469
232926CRISFLD1
Adder
0.711
233901CHERRYDALE C
Solar/Wind Harmer
0.407
232408W1-005 C
Solar/Wind Harmer
0.362
232410W1-006 C
Solar/Wind Harmer
0.362
232905CHERITON_25
Adder
0.888
232918OH NUG7
Adder
3.174
971747AH1-380 GEN
Solar/Wind Harmer
1.296
972069AH1-584 GEN
Solar/Wind Harmer
3.238
972071AH1-585 GEN
Solar/Wind Harmer
3.238
231940T-011
Adder
0.269
970545AG2-347 GEN
Solar/Wind Harmer
23.481
232899W1-062
Adder
3.394
971149AH1-027 GEN
Solar/Wind Harmer
1.179
233939AC1-091 C
Solar/Wind Harmer
0.304
233970AC1-092 C
Solar/Wind Harmer
0.304
972233AH1-701 GEN
Adder
1.291
213815MOSER1-3
Adder
1.097
213815MOSER1-3
Adder
1.097
228304LOGAN
Adder
7.432
228307PCLP GT
Adder
3.695
219921AF1-264
Solar/Wind Harmer
0.044
228251CARLLS#4
Adder
0.186
219615MILLCREEK C
Solar/Wind Harmer
0.071
230433AD2-135 GEN
Solar/Wind Harmer
0.03
230407AD2-065 C
Solar/Wind Harmer
0.039
213535CROYDN11
Adder
3.002
230422AE1-104_GEN1
Solar/Wind Harmer
9.699
230425AE1-104_GEN2
Solar/Wind Harmer
9.699
219114HARTZY_C
Solar/Wind Harmer
0.227
20716428NHV_W2-082
Solar/Wind Harmer
0.476
207500AE2-000G1
Solar/Wind Harmer
8.261
207497AE2-000G2
Solar/Wind Harmer
8.261
207507AE2-000G3
Solar/Wind Harmer
8.261
20636128O CRK C2
Adder
1.69
20714928UPF_X1-085
Solar/Wind Harmer
0.107
963401AG1-189 GEN
Solar/Wind Harmer
0.301
963391AG1-188 GEN
Solar/Wind Harmer
0.501
20628028LAKEHURS
Adder
0.247
219817TRENTONSOL C
Solar/Wind Harmer
0.285
20720628TIN_W1-124
Solar/Wind Harmer
0.25
20641628MLH_W1-032
Solar/Wind Harmer
0.073
20716928W4-060COL
Solar/Wind Harmer
0.175
924131AB2-057 GEN
Solar/Wind Harmer
0.252
218440SUMMTASSOC C
Solar/Wind Harmer
0.031
20673828FLE_V3-070
Solar/Wind Harmer
0.11
218418LINDEN_G5
Adder
4.092
218419LINDEN_G6
Adder
4.092
972260AH1-715 GEN1
Adder
3.277
207442AE1-156 GEN
Solar/Wind Harmer
0.177
20676128MHD_W3-029
Solar/Wind Harmer
0.114
213508CON10-11
50/50
1.01
213518CONOW8-9
50/50
1.01
213514CONOW1-2
50/50
0.746
213516CONOW5-6
50/50
0.746
231918WEST 1
Adder
1.445
231917EM10
Adder
1.008
213497CHSTR7-9
Adder
1.074
213497CHSTR7-9
Adder
1.074
233930AB2-032 GEN
Solar/Wind Harmer
0.343
233915AB1-141 GEN
Solar/Wind Harmer
0.407
232422X3-066 FULL
Solar/Wind Harmer
0.101
234012AE2-112_GEN
Solar/Wind Harmer
0.922
213958STHWK5-6
Adder
0.989
232910NRG_G1
Adder
3.243
233964AF2-378 GEN
Solar/Wind Harmer
0.047
232426Y1-080 FULL
Solar/Wind Harmer
0.07
970277AG2-181 GEN
Solar/Wind Harmer
1.841
965821AG1-450 GEN
Solar/Wind Harmer
1.909
232919VN10
Adder
1.027
233954AC2-188 GEN
Solar/Wind Harmer
0.41
233950AC2-186 GEN
Solar/Wind Harmer
0.205
232428Y3-058 C
Solar/Wind Harmer
0.303
971195AH1-057 GEN
Solar/Wind Harmer
0.397
233998TM1NIN_3.36
Solar/Wind Harmer
0.459
232404W1-003 C
Solar/Wind Harmer
0.362
232917OH NUG6
Adder
3.182
232915OH NUG4
Adder
3.174
232434Z2-077 GEN
Solar/Wind Harmer
0.09
972177AH1-672 GEN
Solar/Wind Harmer
4.814
213560DLW11-12
Adder
0.911
232900DEMECSMY
Adder
3.256
232901NORTHST
Adder
2.9
233972AC1-094 C
Solar/Wind Harmer
0.229
219258KINSLEYDEP C
Solar/Wind Harmer
0.1
219904AC1-010 C
Solar/Wind Harmer
0.116
219907AC1-030 C
Solar/Wind Harmer
0.042
228351V2-046C
Solar/Wind Harmer
0.605
230434AG1-499 GEN
Solar/Wind Harmer
0.174
970997AG2-616 GEN
Solar/Wind Harmer
2.86
945431AF1-208 GEN
Solar/Wind Harmer
2.563
213508CON10-11
50/50
1.01
213518CONOW8-9
50/50
1.01
213517CONOW7
50/50
0.746
213497CHSTR7-9
Adder
1.074
233982AB2-133 GEN
Solar/Wind Harmer
2.007
233918AB1-142 GEN
Solar/Wind Harmer
0.407
213958STHWK5-6
Adder
0.989
232417X3-008 C
Solar/Wind Harmer
0.74
960671AF2-358 GEN
Solar/Wind Harmer
6.569
232907VN8
Adder
10.963
233952AC2-187 GEN
Solar/Wind Harmer
0.41
233994AC2-023 GEN
Solar/Wind Harmer
0.977
233940AF2-379 C
Solar/Wind Harmer
0.068
233900O-025 C
Adder
0.427
234015AF2-250 C
Solar/Wind Harmer
0.044
233996TM1833_GEN
Solar/Wind Harmer
0.459
233997TMININ_4.2
Solar/Wind Harmer
0.459
232406W1-004 FULL
Solar/Wind Harmer
0.362
232921TASLEY2G
Adder
1.868
232914OH NUG3
Adder
3.196
232916OH NUG5
Adder
3.196
233990AG1-397 GEN
Solar/Wind Harmer
0.415
972073AH1-586 GEN
Solar/Wind Harmer
3.388
972133AH1-634 GEN
Solar/Wind Harmer
3.558
213560DLW11-12
Adder
0.911
233971AC1-093 C
Solar/Wind Harmer
0.271
970695AG2-447 GEN
Solar/Wind Harmer
1.239
213815MOSER1-3
Adder
1.097
228304LOGAN
Adder
6.684
219766PARADISE C
Solar/Wind Harmer
0.097
219912AD2-042 GEN
Solar/Wind Harmer
0.244
219623KINSLEYBEA C
Solar/Wind Harmer
0.13
219236SOUTHERNHQ C
Solar/Wind Harmer
0.02
230430AE1-229_GEN
Solar/Wind Harmer
2.621
219906AC1-017 C
Solar/Wind Harmer
0.066
230415AB2-049 C
Solar/Wind Harmer
0.056
971553AH1-274 GEN
Solar/Wind Harmer
0.709
228711V2-041C
Solar/Wind Harmer
0.175
228202CUMB CT
Adder
4.799
219610FLORENCE C
Solar/Wind Harmer
0.405
219348LDSOLAR C
Solar/Wind Harmer
0.175
219221BRL12CT1
Adder
2.607
219223BRL12CT3
Adder
2.607
219291REEVESSOUT C
Solar/Wind Harmer
0.017
972251AH1-710 GEN
Adder
13.808
228729W2-030 C
Solar/Wind Harmer
0.165
959561AF2-247 GEN
Solar/Wind Harmer
0.137
20716028EGP_W2-019
Solar/Wind Harmer
0.124
20720828JCB_W4-025
Solar/Wind Harmer
0.121
219727YARDVSOLFA C
Solar/Wind Harmer
0.246
20715028HAN_X4-015
Solar/Wind Harmer
0.08
20636028O CRK C1
Adder
1.854
219276PARKLANDSO C
Solar/Wind Harmer
0.122
971667AH1-334 GEN
Solar/Wind Harmer
0.715
20714528FRN_Y2-051
Solar/Wind Harmer
0.076
219918AC2-009 C
Solar/Wind Harmer
0.016
20716228APLW2-078
Solar/Wind Harmer
0.222
20720528MAN_W1-024
Solar/Wind Harmer
0.064
219612MATRIX C
Solar/Wind Harmer
0.046
218438BLK ROCK C
Solar/Wind Harmer
0.034
967451AG2-055 C O1
Solar/Wind Harmer
42.597
20635828PARLN1&2
Adder
0.818
20635928PARLN3&4
Adder
0.818
20635028RRCT1&2
Adder
2.86
20635128RRCT3&4
Adder
2.371
219908AB1-139 C
Solar/Wind Harmer
0.091
219919AE1-041 FULL
Solar/Wind Harmer
0.01
219249CENTRALDIV C
Solar/Wind Harmer
0.009
20673728F2S_V4-070
Solar/Wind Harmer
0.043
223402AF1-300 C
Solar/Wind Helper
0.271
213515CONOW3-4
50/50
0.746
213515CONOW3-4
50/50
0.746
213514CONOW1-2
50/50
0.56
213516CONOW5-6
50/50
0.56
233935AB2-179 C
Solar/Wind Harmer
1.161
231919CHRIST1
Adder
1.882
231920CHRIST2
Adder
1.84
971983AH1-536 GEN
Solar/Wind Harmer
3.073
232436AB1-176 C
Solar/Wind Harmer
0.092
233968AD2-076_GEN
Solar/Wind Harmer
2.657
970597AG2-380 GEN
Solar/Wind Harmer
1.669
231906DC3 NUG
Adder
5.528
231902DC CT7
Adder
4.419
231907DC10
Adder
1.38
213942SCHUYLKILL
Adder
1.305
213942SCHUYLKILL
Adder
0.998
213957STHWK3-4
Adder
0.989
213957STHWK3-4
Adder
0.989
232813VAUGHN
Adder
0.218
233955AB2-172 GEN
Solar/Wind Harmer
1.85
233923SMA
Solar/Wind Harmer
1.683
232912OH NUG1
Adder
3.196
232913OH NUG2
Adder
3.153
233990AG1-397 GEN
Solar/Wind Harmer
0.02
232432Z2-076 GEN
Solar/Wind Harmer
0.048
232920IR10
Adder
1.135
234033AF1-007_GEN
Solar/Wind Harmer
8.391
232904IR4
Adder
29.014
213561DLWR9-10
Adder
1.191
213561DLWR9-10
Adder
0.911
233973AC2-185 C
Solar/Wind Harmer
1.25
219137THOSOLAR C
Solar/Wind Harmer
0.375
219914AD2-027 C
Solar/Wind Harmer
0.184
971011AG2-627 GEN
Solar/Wind Harmer
2.317
228309CCLP NUG
Adder
7.778
228309CCLP NUG
Adder
7.399
964001AG1-254 GEN
Solar/Wind Harmer
0.611
972141AH1-641 GEN
Solar/Wind Harmer
0.858
228260V4-054C
Solar/Wind Harmer
0.303
971535AH1-265 GEN
Solar/Wind Harmer
1.252
219272CLEANLIGHT C
Solar/Wind Harmer
0.053
970453AG2-297 GEN
Solar/Wind Harmer
0.8
219607WPEMNERT C
Solar/Wind Harmer
0.122
219224BRL12CT4
Adder
2.607
219688LUMSOLAR_S C
Solar/Wind Harmer
0.059
228754AB1-001 C
Solar/Wind Harmer
0.04
227927V4-067C
Solar/Wind Harmer
0.057
214067T20SOLAR
Solar/Wind Harmer
0.073
213611FALLS1-3
Adder
1.014
213611FALLS1-3
Adder
1.014
20717128DIX_Z2-102
Solar/Wind Harmer
0.352
20715728PEM_W1-119
Solar/Wind Harmer
0.142
20715828PEM_W1-120
Solar/Wind Harmer
0.142
971189AH1-054 GEN
Solar/Wind Harmer
0.31
970025AG2-016 GEN
Solar/Wind Harmer
0.741
207459AE1-142 C O1
Solar/Wind Harmer
0.274
219620RIDERU C
Solar/Wind Harmer
0.014
20714328BYD_X4-031
Solar/Wind Harmer
0.071
20714428HOW_X1-037
Solar/Wind Harmer
0.311
971521AH1-258 GEN
Solar/Wind Harmer
0.675
20720428HOL_W1-112
Solar/Wind Harmer
0.086
218455CINNBAY_CGEN
Adder
0.446
20635928PARLN3&4
Adder
1.806
20675528CPH_W2-050
Solar/Wind Harmer
0.114
218526CNTRALGAS2 C
Solar/Wind Harmer
0.09
218524CNTRALGAS1 C
Solar/Wind Harmer
0.089
230511AF1-262
Solar/Wind Harmer
0.054
228728W1-130C
Solar/Wind Harmer
0.195
228206SHRMN CT
Adder
4.83
219304NAMERICA C
Solar/Wind Harmer
0.091
219222BRL12CT2
Adder
2.607
228732V1-021 C
Adder
0.055
218660EHAMPSOLAR C
Solar/Wind Harmer
0.051
219686LUMSOLAR_N C
Solar/Wind Harmer
0.058
219287REEVESEAST C
Solar/Wind Harmer
0.388
214194N WALES4
Adder
0.245
213611FALLS1-3
Adder
1.014
20720728JCB_W1-129
Solar/Wind Harmer
0.08
207522AF2-254 C
Solar/Wind Harmer
0.384
207487AE2-000G4
Solar/Wind Harmer
8.261
207445AB1-138_GEN
Solar/Wind Harmer
0.151
20628028LAKEHURS
Adder
0.489
963711AG1-223 GEN
Solar/Wind Harmer
0.379
20714828MDF_W3-079
Solar/Wind Harmer
0.078
219680HOPEWELLV C1
Solar/Wind Harmer
0.02
207454AA2-184 E
Solar/Wind Harmer
0.251
20715228NPK_W1-113
Solar/Wind Harmer
0.108
217197RE CRAN C
Solar/Wind Harmer
0.135
20742028HF_AC1-207
Solar/Wind Harmer
0.196
20635828PARLN1&2
Adder
1.806
20635028RRCT1&2
Adder
2.816
20635128RRCT3&4
Adder
2.718
218428ETC SOLAR C
Solar/Wind Harmer
0.009
217213AMBOY SO C
Solar/Wind Harmer
0.03
972275AH1-722 GEN
Adder
7.523
207528AF2-192 GEN
Solar/Wind Harmer
0.132
20673628F1S_V4-069
Solar/Wind Harmer
0.043
20675428EAM_W2-061
Solar/Wind Harmer
0.045
208909MACR G3
Adder
32.152
223401AF1-299 GEN
Solar/Wind Helper
0.271
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.034
G-007ALTFEXP_G-007A->PJM
CMTX
12.437
CBM NorthLTFEXP_CBM-N->PJM
CBM
16.035
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.84
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.618
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
31.56
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.609
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
3.958

Details for NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line l/o PECO_P4_PEACH235_SRT-A/* $ CHESCO $ PECO_P4_PEACH235 $ STBK


Base Case Flowgate

Area:PECO
Facility Description:
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line
Contingency Name:
PECO_P4_PEACH235_SRT-A/* $ CHESCO $ PECO_P4_PEACH235 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:137.41 %
Rating:578.0 MVA
Rating Type:B
MVA to Mitigate:794.24
MW Contribution:2.32
Bus #Bus NameTypeMW Contribution
213508CON10-11
50/50
1.01
213518CONOW8-9
50/50
1.01
213514CONOW1-2
50/50
0.746
213516CONOW5-6
50/50
0.746
231918WEST 1
Adder
1.445
231917EM10
Adder
1.009
213497CHSTR7-9
Adder
1.074
213497CHSTR7-9
Adder
1.074
233930AB2-032 GEN
Solar/Wind Harmer
0.343
233915AB1-141 GEN
Solar/Wind Harmer
0.408
232422X3-066 FULL
Solar/Wind Harmer
0.101
234012AE2-112_GEN
Solar/Wind Harmer
0.922
213958STHWK5-6
Adder
0.99
232910NRG_G1
Adder
3.245
233964AF2-378 GEN
Solar/Wind Harmer
0.047
232426Y1-080 FULL
Solar/Wind Harmer
0.07
970277AG2-181 GEN
Solar/Wind Harmer
1.842
965821AG1-450 GEN
Solar/Wind Harmer
1.91
232919VN10
Adder
1.027
233954AC2-188 GEN
Solar/Wind Harmer
0.41
233950AC2-186 GEN
Solar/Wind Harmer
0.205
232428Y3-058 C
Solar/Wind Harmer
0.303
971195AH1-057 GEN
Solar/Wind Harmer
0.397
233998TM1NIN_3.36
Solar/Wind Harmer
0.459
232404W1-003 C
Solar/Wind Harmer
0.363
232917OH NUG6
Adder
3.183
232915OH NUG4
Adder
3.176
213508CON10-11
50/50
1.01
213518CONOW8-9
50/50
1.01
213517CONOW7
50/50
0.746
213497CHSTR7-9
Adder
1.074
233982AB2-133 GEN
Solar/Wind Harmer
2.008
233918AB1-142 GEN
Solar/Wind Harmer
0.408
213958STHWK5-6
Adder
0.99
232417X3-008 C
Solar/Wind Harmer
0.741
960671AF2-358 GEN
Solar/Wind Harmer
6.572
232907VN8
Adder
10.969
233952AC2-187 GEN
Solar/Wind Harmer
0.41
233994AC2-023 GEN
Solar/Wind Harmer
0.978
233940AF2-379 C
Solar/Wind Harmer
0.068
233900O-025 C
Adder
0.427
234015AF2-250 C
Solar/Wind Harmer
0.044
233996TM1833_GEN
Solar/Wind Harmer
0.459
233997TMININ_4.2
Solar/Wind Harmer
0.459
232406W1-004 FULL
Solar/Wind Harmer
0.363
232921TASLEY2G
Adder
1.869
232914OH NUG3
Adder
3.197
232916OH NUG5
Adder
3.197
233990AG1-397 GEN
Solar/Wind Harmer
0.415
972073AH1-586 GEN
Solar/Wind Harmer
3.39
972133AH1-634 GEN
Solar/Wind Harmer
3.56
213560DLW11-12
Adder
0.911
233971AC1-093 C
Solar/Wind Harmer
0.271
970695AG2-447 GEN
Solar/Wind Harmer
1.24
213815MOSER1-3
Adder
1.097
228304LOGAN
Adder
6.686
219766PARADISE C
Solar/Wind Harmer
0.097
219912AD2-042 GEN
Solar/Wind Harmer
0.244
219623KINSLEYBEA C
Solar/Wind Harmer
0.13
219236SOUTHERNHQ C
Solar/Wind Harmer
0.02
230430AE1-229_GEN
Solar/Wind Harmer
2.622
219906AC1-017 C
Solar/Wind Harmer
0.066
230415AB2-049 C
Solar/Wind Harmer
0.056
971553AH1-274 GEN
Solar/Wind Harmer
0.709
228711V2-041C
Solar/Wind Harmer
0.175
228202CUMB CT
Adder
4.801
219610FLORENCE C
Solar/Wind Harmer
0.405
219348LDSOLAR C
Solar/Wind Harmer
0.175
219221BRL12CT1
Adder
2.608
219223BRL12CT3
Adder
2.608
219291REEVESSOUT C
Solar/Wind Harmer
0.017
972251AH1-710 GEN
Adder
13.816
228729W2-030 C
Solar/Wind Harmer
0.165
959561AF2-247 GEN
Solar/Wind Harmer
0.137
20716028EGP_W2-019
Solar/Wind Harmer
0.124
20720828JCB_W4-025
Solar/Wind Harmer
0.121
219727YARDVSOLFA C
Solar/Wind Harmer
0.246
20715028HAN_X4-015
Solar/Wind Harmer
0.08
20636028O CRK C1
Adder
1.854
219276PARKLANDSO C
Solar/Wind Harmer
0.122
971667AH1-334 GEN
Solar/Wind Harmer
0.715
20714528FRN_Y2-051
Solar/Wind Harmer
0.076
219918AC2-009 C
Solar/Wind Harmer
0.016
20716228APLW2-078
Solar/Wind Harmer
0.222
20720528MAN_W1-024
Solar/Wind Harmer
0.064
219612MATRIX C
Solar/Wind Harmer
0.046
218438BLK ROCK C
Solar/Wind Harmer
0.034
967451AG2-055 C O1
Solar/Wind Harmer
42.608
20635828PARLN1&2
Adder
0.818
20635928PARLN3&4
Adder
0.818
20635028RRCT1&2
Adder
2.861
20635128RRCT3&4
Adder
2.372
219908AB1-139 C
Solar/Wind Harmer
0.092
219919AE1-041 FULL
Solar/Wind Harmer
0.01
219249CENTRALDIV C
Solar/Wind Harmer
0.009
20673728F2S_V4-070
Solar/Wind Harmer
0.043
223402AF1-300 C
Solar/Wind Helper
0.271
213589EDDYSTN4
Adder
31.443
213587EDDYSTN3
Adder
31.416
232416X2-083
Adder
0.19
233933AB2-153 GEN
Solar/Wind Harmer
0.463
233944AB2-135 GEN
Solar/Wind Harmer
2.123
234014AF1-036_GEN
Solar/Wind Harmer
1.085
231131BLOOM ENRGY
Adder
1.716
232424Y1-079 C
Solar/Wind Harmer
0.221
233984AB2-036 GEN
Solar/Wind Harmer
4.867
234041AC1-190 GEN
Solar/Wind Harmer
3.312
233987AB2-037 GEN
Solar/Wind Harmer
4.198
234036AF2-325 C
Solar/Wind Harmer
0.338
233946AB2-136 GEN
Solar/Wind Harmer
1.47
232926CRISFLD1
Adder
0.711
233901CHERRYDALE C
Solar/Wind Harmer
0.408
232408W1-005 C
Solar/Wind Harmer
0.363
232410W1-006 C
Solar/Wind Harmer
0.363
232905CHERITON_25
Adder
0.888
232918OH NUG7
Adder
3.176
971747AH1-380 GEN
Solar/Wind Harmer
1.296
972069AH1-584 GEN
Solar/Wind Harmer
3.239
972071AH1-585 GEN
Solar/Wind Harmer
3.239
231940T-011
Adder
0.27
970545AG2-347 GEN
Solar/Wind Harmer
23.494
232899W1-062
Adder
3.396
971149AH1-027 GEN
Solar/Wind Harmer
1.18
233939AC1-091 C
Solar/Wind Harmer
0.304
233970AC1-092 C
Solar/Wind Harmer
0.304
972233AH1-701 GEN
Adder
1.291
213815MOSER1-3
Adder
1.097
213815MOSER1-3
Adder
1.097
228304LOGAN
Adder
7.434
228307PCLP GT
Adder
3.696
219921AF1-264
Solar/Wind Harmer
0.044
228251CARLLS#4
Adder
0.186
219615MILLCREEK C
Solar/Wind Harmer
0.071
230433AD2-135 GEN
Solar/Wind Harmer
0.03
230407AD2-065 C
Solar/Wind Harmer
0.039
213535CROYDN11
Adder
3.003
230422AE1-104_GEN1
Solar/Wind Harmer
9.703
230425AE1-104_GEN2
Solar/Wind Harmer
9.703
219114HARTZY_C
Solar/Wind Harmer
0.227
20716428NHV_W2-082
Solar/Wind Harmer
0.476
207500AE2-000G1
Solar/Wind Harmer
8.264
207497AE2-000G2
Solar/Wind Harmer
8.264
207507AE2-000G3
Solar/Wind Harmer
8.264
20636128O CRK C2
Adder
1.691
20714928UPF_X1-085
Solar/Wind Harmer
0.107
963401AG1-189 GEN
Solar/Wind Harmer
0.301
963391AG1-188 GEN
Solar/Wind Harmer
0.501
20628028LAKEHURS
Adder
0.247
213515CONOW3-4
50/50
0.746
213515CONOW3-4
50/50
0.746
213514CONOW1-2
50/50
0.56
213516CONOW5-6
50/50
0.56
233935AB2-179 C
Solar/Wind Harmer
1.162
231919CHRIST1
Adder
1.883
231920CHRIST2
Adder
1.841
971983AH1-536 GEN
Solar/Wind Harmer
3.074
232436AB1-176 C
Solar/Wind Harmer
0.092
233968AD2-076_GEN
Solar/Wind Harmer
2.659
970597AG2-380 GEN
Solar/Wind Harmer
1.67
231906DC3 NUG
Adder
5.53
231902DC CT7
Adder
4.421
231907DC10
Adder
1.381
213942SCHUYLKILL
Adder
1.305
213942SCHUYLKILL
Adder
0.998
213957STHWK3-4
Adder
0.99
213957STHWK3-4
Adder
0.99
232813VAUGHN
Adder
0.219
233955AB2-172 GEN
Solar/Wind Harmer
1.851
233923SMA
Solar/Wind Harmer
1.683
232912OH NUG1
Adder
3.197
232913OH NUG2
Adder
3.155
233990AG1-397 GEN
Solar/Wind Harmer
0.02
232432Z2-076 GEN
Solar/Wind Harmer
0.048
232920IR10
Adder
1.136
234033AF1-007_GEN
Solar/Wind Harmer
8.396
232904IR4
Adder
29.029
213561DLWR9-10
Adder
1.192
213561DLWR9-10
Adder
0.911
233973AC2-185 C
Solar/Wind Harmer
1.25
219137THOSOLAR C
Solar/Wind Harmer
0.376
219914AD2-027 C
Solar/Wind Harmer
0.184
971011AG2-627 GEN
Solar/Wind Harmer
2.318
228309CCLP NUG
Adder
7.781
228309CCLP NUG
Adder
7.401
964001AG1-254 GEN
Solar/Wind Harmer
0.611
972141AH1-641 GEN
Solar/Wind Harmer
0.858
228260V4-054C
Solar/Wind Harmer
0.303
971535AH1-265 GEN
Solar/Wind Harmer
1.252
219272CLEANLIGHT C
Solar/Wind Harmer
0.053
970453AG2-297 GEN
Solar/Wind Harmer
0.801
219607WPEMNERT C
Solar/Wind Harmer
0.122
219224BRL12CT4
Adder
2.608
219688LUMSOLAR_S C
Solar/Wind Harmer
0.059
228754AB1-001 C
Solar/Wind Harmer
0.04
227927V4-067C
Solar/Wind Harmer
0.057
214067T20SOLAR
Solar/Wind Harmer
0.073
213611FALLS1-3
Adder
1.015
213611FALLS1-3
Adder
1.015
20717128DIX_Z2-102
Solar/Wind Harmer
0.353
20715728PEM_W1-119
Solar/Wind Harmer
0.142
20715828PEM_W1-120
Solar/Wind Harmer
0.142
971189AH1-054 GEN
Solar/Wind Harmer
0.31
970025AG2-016 GEN
Solar/Wind Harmer
0.741
207459AE1-142 C O1
Solar/Wind Harmer
0.274
219620RIDERU C
Solar/Wind Harmer
0.014
20714328BYD_X4-031
Solar/Wind Harmer
0.071
20714428HOW_X1-037
Solar/Wind Harmer
0.312
971521AH1-258 GEN
Solar/Wind Harmer
0.675
20720428HOL_W1-112
Solar/Wind Harmer
0.086
218455CINNBAY_CGEN
Adder
0.446
20635928PARLN3&4
Adder
1.806
20675528CPH_W2-050
Solar/Wind Harmer
0.114
218526CNTRALGAS2 C
Solar/Wind Harmer
0.09
218524CNTRALGAS1 C
Solar/Wind Harmer
0.089
219817TRENTONSOL C
Solar/Wind Harmer
0.285
20720628TIN_W1-124
Solar/Wind Harmer
0.25
20641628MLH_W1-032
Solar/Wind Harmer
0.073
20716928W4-060COL
Solar/Wind Harmer
0.175
924131AB2-057 GEN
Solar/Wind Harmer
0.252
218440SUMMTASSOC C
Solar/Wind Harmer
0.031
20673828FLE_V3-070
Solar/Wind Harmer
0.11
218418LINDEN_G5
Adder
4.093
218419LINDEN_G6
Adder
4.093
972260AH1-715 GEN1
Adder
3.278
207442AE1-156 GEN
Solar/Wind Harmer
0.177
20676128MHD_W3-029
Solar/Wind Harmer
0.114
232434Z2-077 GEN
Solar/Wind Harmer
0.09
972177AH1-672 GEN
Solar/Wind Harmer
4.816
213560DLW11-12
Adder
0.911
232900DEMECSMY
Adder
3.257
232901NORTHST
Adder
2.902
233972AC1-094 C
Solar/Wind Harmer
0.23
219258KINSLEYDEP C
Solar/Wind Harmer
0.1
219904AC1-010 C
Solar/Wind Harmer
0.116
219907AC1-030 C
Solar/Wind Harmer
0.042
228351V2-046C
Solar/Wind Harmer
0.605
230434AG1-499 GEN
Solar/Wind Harmer
0.174
970997AG2-616 GEN
Solar/Wind Harmer
2.861
945431AF1-208 GEN
Solar/Wind Harmer
2.564
230511AF1-262
Solar/Wind Harmer
0.054
228728W1-130C
Solar/Wind Harmer
0.195
228206SHRMN CT
Adder
4.832
219304NAMERICA C
Solar/Wind Harmer
0.091
219222BRL12CT2
Adder
2.608
228732V1-021 C
Adder
0.055
218660EHAMPSOLAR C
Solar/Wind Harmer
0.051
219686LUMSOLAR_N C
Solar/Wind Harmer
0.058
219287REEVESEAST C
Solar/Wind Harmer
0.388
214194N WALES4
Adder
0.245
213611FALLS1-3
Adder
1.015
20720728JCB_W1-129
Solar/Wind Harmer
0.08
207522AF2-254 C
Solar/Wind Harmer
0.384
207487AE2-000G4
Solar/Wind Harmer
8.264
207445AB1-138_GEN
Solar/Wind Harmer
0.151
20628028LAKEHURS
Adder
0.489
963711AG1-223 GEN
Solar/Wind Harmer
0.379
20714828MDF_W3-079
Solar/Wind Harmer
0.078
219680HOPEWELLV C1
Solar/Wind Harmer
0.02
207454AA2-184 E
Solar/Wind Harmer
0.251
20715228NPK_W1-113
Solar/Wind Harmer
0.108
217197RE CRAN C
Solar/Wind Harmer
0.135
20742028HF_AC1-207
Solar/Wind Harmer
0.196
20635828PARLN1&2
Adder
1.806
20635028RRCT1&2
Adder
2.817
20635128RRCT3&4
Adder
2.719
218428ETC SOLAR C
Solar/Wind Harmer
0.009
217213AMBOY SO C
Solar/Wind Harmer
0.03
972275AH1-722 GEN
Adder
7.525
207528AF2-192 GEN
Solar/Wind Harmer
0.132
20673628F1S_V4-069
Solar/Wind Harmer
0.043
20675428EAM_W2-061
Solar/Wind Harmer
0.045
208909MACR G3
Adder
32.156
223401AF1-299 GEN
Solar/Wind Helper
0.271
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.035
G-007ALTFEXP_G-007A->PJM
CMTX
12.44
CBM NorthLTFEXP_CBM-N->PJM
CBM
16.037
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.84
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.618
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
31.566
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.609
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
3.959

Details for NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line l/o BGE_P4_GRACETON_51_SRT-A


Base Case Flowgate

Area:PECO
Facility Description:
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line
Contingency Name:
BGE_P4_GRACETON_51_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:137.36 %
Rating:578.0 MVA
Rating Type:B
MVA to Mitigate:793.96
MW Contribution:2.32
Bus #Bus NameTypeMW Contribution
213508CON10-11
50/50
1.01
213518CONOW8-9
50/50
1.01
213517CONOW7
50/50
0.746
213497CHSTR7-9
Adder
1.074
233982AB2-133 GEN
Solar/Wind Harmer
2.007
233918AB1-142 GEN
Solar/Wind Harmer
0.407
213958STHWK5-6
Adder
0.989
232417X3-008 C
Solar/Wind Harmer
0.74
960671AF2-358 GEN
Solar/Wind Harmer
6.569
232907VN8
Adder
10.963
233952AC2-187 GEN
Solar/Wind Harmer
0.41
233994AC2-023 GEN
Solar/Wind Harmer
0.977
233940AF2-379 C
Solar/Wind Harmer
0.068
233900O-025 C
Adder
0.427
234015AF2-250 C
Solar/Wind Harmer
0.044
233996TM1833_GEN
Solar/Wind Harmer
0.459
233997TMININ_4.2
Solar/Wind Harmer
0.459
232406W1-004 FULL
Solar/Wind Harmer
0.362
232921TASLEY2G
Adder
1.868
232914OH NUG3
Adder
3.196
232916OH NUG5
Adder
3.196
233990AG1-397 GEN
Solar/Wind Harmer
0.415
972073AH1-586 GEN
Solar/Wind Harmer
3.388
972133AH1-634 GEN
Solar/Wind Harmer
3.558
213560DLW11-12
Adder
0.911
233971AC1-093 C
Solar/Wind Harmer
0.271
970695AG2-447 GEN
Solar/Wind Harmer
1.239
213815MOSER1-3
Adder
1.097
228304LOGAN
Adder
6.684
219766PARADISE C
Solar/Wind Harmer
0.097
219912AD2-042 GEN
Solar/Wind Harmer
0.244
219623KINSLEYBEA C
Solar/Wind Harmer
0.13
219236SOUTHERNHQ C
Solar/Wind Harmer
0.02
230430AE1-229_GEN
Solar/Wind Harmer
2.621
219906AC1-017 C
Solar/Wind Harmer
0.066
230415AB2-049 C
Solar/Wind Harmer
0.056
971553AH1-274 GEN
Solar/Wind Harmer
0.709
228711V2-041C
Solar/Wind Harmer
0.175
228202CUMB CT
Adder
4.799
213515CONOW3-4
50/50
0.746
213515CONOW3-4
50/50
0.746
213514CONOW1-2
50/50
0.56
213516CONOW5-6
50/50
0.56
233935AB2-179 C
Solar/Wind Harmer
1.161
231919CHRIST1
Adder
1.882
231920CHRIST2
Adder
1.84
971983AH1-536 GEN
Solar/Wind Harmer
3.073
232436AB1-176 C
Solar/Wind Harmer
0.092
233968AD2-076_GEN
Solar/Wind Harmer
2.657
970597AG2-380 GEN
Solar/Wind Harmer
1.669
231906DC3 NUG
Adder
5.528
231902DC CT7
Adder
4.419
231907DC10
Adder
1.38
213942SCHUYLKILL
Adder
1.305
213942SCHUYLKILL
Adder
0.998
213957STHWK3-4
Adder
0.989
213957STHWK3-4
Adder
0.989
232813VAUGHN
Adder
0.218
233955AB2-172 GEN
Solar/Wind Harmer
1.85
233923SMA
Solar/Wind Harmer
1.683
232912OH NUG1
Adder
3.196
232913OH NUG2
Adder
3.153
233990AG1-397 GEN
Solar/Wind Harmer
0.02
232432Z2-076 GEN
Solar/Wind Harmer
0.048
232920IR10
Adder
1.135
234033AF1-007_GEN
Solar/Wind Harmer
8.391
232904IR4
Adder
29.014
213561DLWR9-10
Adder
1.191
213561DLWR9-10
Adder
0.911
233973AC2-185 C
Solar/Wind Harmer
1.25
219137THOSOLAR C
Solar/Wind Harmer
0.375
219914AD2-027 C
Solar/Wind Harmer
0.184
971011AG2-627 GEN
Solar/Wind Harmer
2.317
228309CCLP NUG
Adder
7.778
228309CCLP NUG
Adder
7.399
964001AG1-254 GEN
Solar/Wind Harmer
0.611
972141AH1-641 GEN
Solar/Wind Harmer
0.858
228260V4-054C
Solar/Wind Harmer
0.303
971535AH1-265 GEN
Solar/Wind Harmer
1.252
219272CLEANLIGHT C
Solar/Wind Harmer
0.053
970453AG2-297 GEN
Solar/Wind Harmer
0.8
219607WPEMNERT C
Solar/Wind Harmer
0.122
219224BRL12CT4
Adder
2.607
219688LUMSOLAR_S C
Solar/Wind Harmer
0.059
228754AB1-001 C
Solar/Wind Harmer
0.04
227927V4-067C
Solar/Wind Harmer
0.057
214067T20SOLAR
Solar/Wind Harmer
0.073
213611FALLS1-3
Adder
1.014
213611FALLS1-3
Adder
1.014
20717128DIX_Z2-102
Solar/Wind Harmer
0.352
20715728PEM_W1-119
Solar/Wind Harmer
0.142
20715828PEM_W1-120
Solar/Wind Harmer
0.142
971189AH1-054 GEN
Solar/Wind Harmer
0.31
970025AG2-016 GEN
Solar/Wind Harmer
0.741
207459AE1-142 C O1
Solar/Wind Harmer
0.274
219620RIDERU C
Solar/Wind Harmer
0.014
20714328BYD_X4-031
Solar/Wind Harmer
0.071
20714428HOW_X1-037
Solar/Wind Harmer
0.311
971521AH1-258 GEN
Solar/Wind Harmer
0.675
20720428HOL_W1-112
Solar/Wind Harmer
0.086
218455CINNBAY_CGEN
Adder
0.446
20635928PARLN3&4
Adder
1.806
20675528CPH_W2-050
Solar/Wind Harmer
0.114
218526CNTRALGAS2 C
Solar/Wind Harmer
0.09
218524CNTRALGAS1 C
Solar/Wind Harmer
0.089
219610FLORENCE C
Solar/Wind Harmer
0.405
219348LDSOLAR C
Solar/Wind Harmer
0.175
219221BRL12CT1
Adder
2.607
219223BRL12CT3
Adder
2.607
219291REEVESSOUT C
Solar/Wind Harmer
0.017
972251AH1-710 GEN
Adder
13.808
228729W2-030 C
Solar/Wind Harmer
0.165
959561AF2-247 GEN
Solar/Wind Harmer
0.137
20716028EGP_W2-019
Solar/Wind Harmer
0.124
20720828JCB_W4-025
Solar/Wind Harmer
0.121
219727YARDVSOLFA C
Solar/Wind Harmer
0.246
20715028HAN_X4-015
Solar/Wind Harmer
0.08
20636028O CRK C1
Adder
1.854
219276PARKLANDSO C
Solar/Wind Harmer
0.122
971667AH1-334 GEN
Solar/Wind Harmer
0.715
20714528FRN_Y2-051
Solar/Wind Harmer
0.076
219918AC2-009 C
Solar/Wind Harmer
0.016
20716228APLW2-078
Solar/Wind Harmer
0.222
20720528MAN_W1-024
Solar/Wind Harmer
0.064
219612MATRIX C
Solar/Wind Harmer
0.046
218438BLK ROCK C
Solar/Wind Harmer
0.034
967451AG2-055 C O1
Solar/Wind Harmer
42.597
20635828PARLN1&2
Adder
0.818
20635928PARLN3&4
Adder
0.818
20635028RRCT1&2
Adder
2.86
20635128RRCT3&4
Adder
2.371
219908AB1-139 C
Solar/Wind Harmer
0.091
219919AE1-041 FULL
Solar/Wind Harmer
0.01
219249CENTRALDIV C
Solar/Wind Harmer
0.009
20673728F2S_V4-070
Solar/Wind Harmer
0.043
223402AF1-300 C
Solar/Wind Helper
0.271
213589EDDYSTN4
Adder
31.437
213587EDDYSTN3
Adder
31.41
232416X2-083
Adder
0.19
233933AB2-153 GEN
Solar/Wind Harmer
0.463
233944AB2-135 GEN
Solar/Wind Harmer
2.122
234014AF1-036_GEN
Solar/Wind Harmer
1.085
231131BLOOM ENRGY
Adder
1.715
232424Y1-079 C
Solar/Wind Harmer
0.221
233984AB2-036 GEN
Solar/Wind Harmer
4.865
234041AC1-190 GEN
Solar/Wind Harmer
3.31
233987AB2-037 GEN
Solar/Wind Harmer
4.196
234036AF2-325 C
Solar/Wind Harmer
0.338
233946AB2-136 GEN
Solar/Wind Harmer
1.469
232926CRISFLD1
Adder
0.711
233901CHERRYDALE C
Solar/Wind Harmer
0.407
232408W1-005 C
Solar/Wind Harmer
0.362
232410W1-006 C
Solar/Wind Harmer
0.362
232905CHERITON_25
Adder
0.888
232918OH NUG7
Adder
3.174
971747AH1-380 GEN
Solar/Wind Harmer
1.296
972069AH1-584 GEN
Solar/Wind Harmer
3.238
972071AH1-585 GEN
Solar/Wind Harmer
3.238
231940T-011
Adder
0.269
970545AG2-347 GEN
Solar/Wind Harmer
23.481
232899W1-062
Adder
3.394
971149AH1-027 GEN
Solar/Wind Harmer
1.179
233939AC1-091 C
Solar/Wind Harmer
0.304
233970AC1-092 C
Solar/Wind Harmer
0.304
972233AH1-701 GEN
Adder
1.291
213815MOSER1-3
Adder
1.097
213815MOSER1-3
Adder
1.097
228304LOGAN
Adder
7.432
228307PCLP GT
Adder
3.695
219921AF1-264
Solar/Wind Harmer
0.044
228251CARLLS#4
Adder
0.186
219615MILLCREEK C
Solar/Wind Harmer
0.071
230433AD2-135 GEN
Solar/Wind Harmer
0.03
230407AD2-065 C
Solar/Wind Harmer
0.039
213535CROYDN11
Adder
3.002
230422AE1-104_GEN1
Solar/Wind Harmer
9.699
230425AE1-104_GEN2
Solar/Wind Harmer
9.699
219114HARTZY_C
Solar/Wind Harmer
0.227
20716428NHV_W2-082
Solar/Wind Harmer
0.476
207500AE2-000G1
Solar/Wind Harmer
8.261
207497AE2-000G2
Solar/Wind Harmer
8.261
207507AE2-000G3
Solar/Wind Harmer
8.261
20636128O CRK C2
Adder
1.69
20714928UPF_X1-085
Solar/Wind Harmer
0.107
963401AG1-189 GEN
Solar/Wind Harmer
0.301
963391AG1-188 GEN
Solar/Wind Harmer
0.501
20628028LAKEHURS
Adder
0.247
219817TRENTONSOL C
Solar/Wind Harmer
0.285
20720628TIN_W1-124
Solar/Wind Harmer
0.25
20641628MLH_W1-032
Solar/Wind Harmer
0.073
20716928W4-060COL
Solar/Wind Harmer
0.175
924131AB2-057 GEN
Solar/Wind Harmer
0.252
218440SUMMTASSOC C
Solar/Wind Harmer
0.031
20673828FLE_V3-070
Solar/Wind Harmer
0.11
218418LINDEN_G5
Adder
4.092
218419LINDEN_G6
Adder
4.092
972260AH1-715 GEN1
Adder
3.277
207442AE1-156 GEN
Solar/Wind Harmer
0.177
20676128MHD_W3-029
Solar/Wind Harmer
0.114
213508CON10-11
50/50
1.01
213518CONOW8-9
50/50
1.01
213514CONOW1-2
50/50
0.746
213516CONOW5-6
50/50
0.746
231918WEST 1
Adder
1.445
231917EM10
Adder
1.008
213497CHSTR7-9
Adder
1.074
213497CHSTR7-9
Adder
1.074
233930AB2-032 GEN
Solar/Wind Harmer
0.343
233915AB1-141 GEN
Solar/Wind Harmer
0.407
232422X3-066 FULL
Solar/Wind Harmer
0.101
234012AE2-112_GEN
Solar/Wind Harmer
0.922
213958STHWK5-6
Adder
0.989
232910NRG_G1
Adder
3.243
233964AF2-378 GEN
Solar/Wind Harmer
0.047
232426Y1-080 FULL
Solar/Wind Harmer
0.07
970277AG2-181 GEN
Solar/Wind Harmer
1.841
965821AG1-450 GEN
Solar/Wind Harmer
1.909
232919VN10
Adder
1.027
233954AC2-188 GEN
Solar/Wind Harmer
0.41
233950AC2-186 GEN
Solar/Wind Harmer
0.205
232428Y3-058 C
Solar/Wind Harmer
0.303
971195AH1-057 GEN
Solar/Wind Harmer
0.397
233998TM1NIN_3.36
Solar/Wind Harmer
0.459
232404W1-003 C
Solar/Wind Harmer
0.362
232917OH NUG6
Adder
3.182
232915OH NUG4
Adder
3.174
232434Z2-077 GEN
Solar/Wind Harmer
0.09
972177AH1-672 GEN
Solar/Wind Harmer
4.814
213560DLW11-12
Adder
0.911
232900DEMECSMY
Adder
3.256
232901NORTHST
Adder
2.9
233972AC1-094 C
Solar/Wind Harmer
0.229
219258KINSLEYDEP C
Solar/Wind Harmer
0.1
219904AC1-010 C
Solar/Wind Harmer
0.116
219907AC1-030 C
Solar/Wind Harmer
0.042
228351V2-046C
Solar/Wind Harmer
0.605
230434AG1-499 GEN
Solar/Wind Harmer
0.174
970997AG2-616 GEN
Solar/Wind Harmer
2.86
945431AF1-208 GEN
Solar/Wind Harmer
2.563
230511AF1-262
Solar/Wind Harmer
0.054
228728W1-130C
Solar/Wind Harmer
0.195
228206SHRMN CT
Adder
4.83
219304NAMERICA C
Solar/Wind Harmer
0.091
219222BRL12CT2
Adder
2.607
228732V1-021 C
Adder
0.055
218660EHAMPSOLAR C
Solar/Wind Harmer
0.051
219686LUMSOLAR_N C
Solar/Wind Harmer
0.058
219287REEVESEAST C
Solar/Wind Harmer
0.388
214194N WALES4
Adder
0.245
213611FALLS1-3
Adder
1.014
20720728JCB_W1-129
Solar/Wind Harmer
0.08
207522AF2-254 C
Solar/Wind Harmer
0.384
207487AE2-000G4
Solar/Wind Harmer
8.261
207445AB1-138_GEN
Solar/Wind Harmer
0.151
20628028LAKEHURS
Adder
0.489
963711AG1-223 GEN
Solar/Wind Harmer
0.379
20714828MDF_W3-079
Solar/Wind Harmer
0.078
219680HOPEWELLV C1
Solar/Wind Harmer
0.02
207454AA2-184 E
Solar/Wind Harmer
0.251
20715228NPK_W1-113
Solar/Wind Harmer
0.108
217197RE CRAN C
Solar/Wind Harmer
0.135
20742028HF_AC1-207
Solar/Wind Harmer
0.196
20635828PARLN1&2
Adder
1.806
20635028RRCT1&2
Adder
2.816
20635128RRCT3&4
Adder
2.718
218428ETC SOLAR C
Solar/Wind Harmer
0.009
217213AMBOY SO C
Solar/Wind Harmer
0.03
972275AH1-722 GEN
Adder
7.523
207528AF2-192 GEN
Solar/Wind Harmer
0.132
20673628F1S_V4-069
Solar/Wind Harmer
0.043
20675428EAM_W2-061
Solar/Wind Harmer
0.045
208909MACR G3
Adder
32.152
223401AF1-299 GEN
Solar/Wind Helper
0.271
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.034
G-007ALTFEXP_G-007A->PJM
CMTX
12.437
CBM NorthLTFEXP_CBM-N->PJM
CBM
16.035
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.84
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.618
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
31.56
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.609
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
3.958

Details for NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line l/o PJM_500_BG_P4_5_CNSTN_B_SRT-A


Base Case Flowgate

Area:PECO
Facility Description:
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line
Contingency Name:
PJM_500_BG_P4_5_CNSTN_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:136.42 %
Rating:578.0 MVA
Rating Type:B
MVA to Mitigate:788.52
MW Contribution:2.28
Bus #Bus NameTypeMW Contribution
213508CON10-11
50/50
1.003
213518CONOW8-9
50/50
1.003
213514CONOW1-2
50/50
0.741
213516CONOW5-6
50/50
0.741
231918WEST 1
Adder
1.427
231917EM10
Adder
0.996
213497CHSTR7-9
Adder
1.06
213497CHSTR7-9
Adder
1.06
233930AB2-032 GEN
Solar/Wind Harmer
0.339
233915AB1-141 GEN
Solar/Wind Harmer
0.402
232422X3-066 FULL
Solar/Wind Harmer
0.099
234012AE2-112_GEN
Solar/Wind Harmer
0.91
213958STHWK5-6
Adder
0.976
232910NRG_G1
Adder
3.201
233964AF2-378 GEN
Solar/Wind Harmer
0.046
232426Y1-080 FULL
Solar/Wind Harmer
0.069
970277AG2-181 GEN
Solar/Wind Harmer
1.817
965821AG1-450 GEN
Solar/Wind Harmer
1.884
232919VN10
Adder
1.013
233954AC2-188 GEN
Solar/Wind Harmer
0.404
213508CON10-11
50/50
1.003
213518CONOW8-9
50/50
1.003
213517CONOW7
50/50
0.741
213497CHSTR7-9
Adder
1.06
233982AB2-133 GEN
Solar/Wind Harmer
1.982
233918AB1-142 GEN
Solar/Wind Harmer
0.402
213958STHWK5-6
Adder
0.976
232417X3-008 C
Solar/Wind Harmer
0.73
960671AF2-358 GEN
Solar/Wind Harmer
6.482
232907VN8
Adder
10.817
233952AC2-187 GEN
Solar/Wind Harmer
0.404
233994AC2-023 GEN
Solar/Wind Harmer
0.964
233940AF2-379 C
Solar/Wind Harmer
0.067
234015AF2-250 C
Solar/Wind Harmer
0.043
233900O-025 C
Adder
0.421
233996TM1833_GEN
Solar/Wind Harmer
0.453
233997TMININ_4.2
Solar/Wind Harmer
0.453
232406W1-004 FULL
Solar/Wind Harmer
0.358
232914OH NUG3
Adder
3.153
232916OH NUG5
Adder
3.153
232921TASLEY2G
Adder
1.843
233990AG1-397 GEN
Solar/Wind Harmer
0.409
972073AH1-586 GEN
Solar/Wind Harmer
3.343
972133AH1-634 GEN
Solar/Wind Harmer
3.51
213560DLW11-12
Adder
0.898
233971AC1-093 C
Solar/Wind Harmer
0.268
970695AG2-447 GEN
Solar/Wind Harmer
1.222
213815MOSER1-3
Adder
1.08
228304LOGAN
Adder
6.586
219766PARADISE C
Solar/Wind Harmer
0.095
219912AD2-042 GEN
Solar/Wind Harmer
0.241
219623KINSLEYBEA C
Solar/Wind Harmer
0.128
219236SOUTHERNHQ C
Solar/Wind Harmer
0.02
230430AE1-229_GEN
Solar/Wind Harmer
2.582
219906AC1-017 C
Solar/Wind Harmer
0.065
230415AB2-049 C
Solar/Wind Harmer
0.055
971553AH1-274 GEN
Solar/Wind Harmer
0.698
228711V2-041C
Solar/Wind Harmer
0.172
228202CUMB CT
Adder
4.727
219610FLORENCE C
Solar/Wind Harmer
0.398
219348LDSOLAR C
Solar/Wind Harmer
0.172
219221BRL12CT1
Adder
2.567
219223BRL12CT3
Adder
2.567
219291REEVESSOUT C
Solar/Wind Harmer
0.017
972251AH1-710 GEN
Adder
13.602
228729W2-030 C
Solar/Wind Harmer
0.163
959561AF2-247 GEN
Solar/Wind Harmer
0.134
20716028EGP_W2-019
Solar/Wind Harmer
0.122
20720828JCB_W4-025
Solar/Wind Harmer
0.119
219727YARDVSOLFA C
Solar/Wind Harmer
0.242
20715028HAN_X4-015
Solar/Wind Harmer
0.079
20636028O CRK C1
Adder
1.823
219276PARKLANDSO C
Solar/Wind Harmer
0.12
971667AH1-334 GEN
Solar/Wind Harmer
0.703
20714528FRN_Y2-051
Solar/Wind Harmer
0.074
219918AC2-009 C
Solar/Wind Harmer
0.016
20716228APLW2-078
Solar/Wind Harmer
0.218
20720528MAN_W1-024
Solar/Wind Harmer
0.062
219612MATRIX C
Solar/Wind Harmer
0.046
218438BLK ROCK C
Solar/Wind Harmer
0.034
967451AG2-055 C O1
Solar/Wind Harmer
41.842
20635828PARLN1&2
Adder
0.803
20635928PARLN3&4
Adder
0.803
20635028RRCT1&2
Adder
2.808
20635128RRCT3&4
Adder
2.328
219908AB1-139 C
Solar/Wind Harmer
0.09
219919AE1-041 FULL
Solar/Wind Harmer
0.01
223402AF1-300 C
Solar/Wind Helper
0.284
213589EDDYSTN4
Adder
31.043
213587EDDYSTN3
Adder
31.015
232416X2-083
Adder
0.188
233933AB2-153 GEN
Solar/Wind Harmer
0.457
233944AB2-135 GEN
Solar/Wind Harmer
2.096
234014AF1-036_GEN
Solar/Wind Harmer
1.071
231131BLOOM ENRGY
Adder
1.693
232424Y1-079 C
Solar/Wind Harmer
0.218
233984AB2-036 GEN
Solar/Wind Harmer
4.803
234041AC1-190 GEN
Solar/Wind Harmer
3.266
233987AB2-037 GEN
Solar/Wind Harmer
4.141
234036AF2-325 C
Solar/Wind Harmer
0.334
233946AB2-136 GEN
Solar/Wind Harmer
1.449
232926CRISFLD1
Adder
0.702
233901CHERRYDALE C
Solar/Wind Harmer
0.402
232408W1-005 C
Solar/Wind Harmer
0.358
232410W1-006 C
Solar/Wind Harmer
0.358
232918OH NUG7
Adder
3.132
232905CHERITON_25
Adder
0.876
971747AH1-380 GEN
Solar/Wind Harmer
1.278
972069AH1-584 GEN
Solar/Wind Harmer
3.195
972071AH1-585 GEN
Solar/Wind Harmer
3.195
231940T-011
Adder
0.266
970545AG2-347 GEN
Solar/Wind Harmer
23.167
232899W1-062
Adder
3.348
971149AH1-027 GEN
Solar/Wind Harmer
1.163
233939AC1-091 C
Solar/Wind Harmer
0.3
233970AC1-092 C
Solar/Wind Harmer
0.3
972233AH1-701 GEN
Adder
1.272
213815MOSER1-3
Adder
1.08
213815MOSER1-3
Adder
1.08
228304LOGAN
Adder
7.323
228307PCLP GT
Adder
3.641
219921AF1-264
Solar/Wind Harmer
0.043
228251CARLLS#4
Adder
0.183
219615MILLCREEK C
Solar/Wind Harmer
0.07
230433AD2-135 GEN
Solar/Wind Harmer
0.029
230407AD2-065 C
Solar/Wind Harmer
0.038
213535CROYDN11
Adder
2.956
230422AE1-104_GEN1
Solar/Wind Harmer
9.552
230425AE1-104_GEN2
Solar/Wind Harmer
9.552
219114HARTZY_C
Solar/Wind Harmer
0.224
20716428NHV_W2-082
Solar/Wind Harmer
0.468
207500AE2-000G1
Solar/Wind Harmer
8.125
207497AE2-000G2
Solar/Wind Harmer
8.125
207507AE2-000G3
Solar/Wind Harmer
8.125
20636128O CRK C2
Adder
1.662
20714928UPF_X1-085
Solar/Wind Harmer
0.105
963401AG1-189 GEN
Solar/Wind Harmer
0.296
963391AG1-188 GEN
Solar/Wind Harmer
0.493
20628028LAKEHURS
Adder
0.243
219817TRENTONSOL C
Solar/Wind Harmer
0.28
20720628TIN_W1-124
Solar/Wind Harmer
0.246
20641628MLH_W1-032
Solar/Wind Harmer
0.072
20716928W4-060COL
Solar/Wind Harmer
0.172
924131AB2-057 GEN
Solar/Wind Harmer
0.248
218440SUMMTASSOC C
Solar/Wind Harmer
0.03
20673828FLE_V3-070
Solar/Wind Harmer
0.108
213515CONOW3-4
50/50
0.741
213515CONOW3-4
50/50
0.741
213514CONOW1-2
50/50
0.555
213516CONOW5-6
50/50
0.555
233935AB2-179 C
Solar/Wind Harmer
1.148
231919CHRIST1
Adder
1.859
231920CHRIST2
Adder
1.818
971983AH1-536 GEN
Solar/Wind Harmer
3.035
232436AB1-176 C
Solar/Wind Harmer
0.091
233968AD2-076_GEN
Solar/Wind Harmer
2.624
970597AG2-380 GEN
Solar/Wind Harmer
1.648
231906DC3 NUG
Adder
5.458
231902DC CT7
Adder
4.363
231907DC10
Adder
1.363
213942SCHUYLKILL
Adder
1.288
213942SCHUYLKILL
Adder
0.985
213957STHWK3-4
Adder
0.976
213957STHWK3-4
Adder
0.976
232813VAUGHN
Adder
0.216
233955AB2-172 GEN
Solar/Wind Harmer
1.826
233923SMA
Solar/Wind Harmer
1.66
232912OH NUG1
Adder
3.153
232913OH NUG2
Adder
3.111
233990AG1-397 GEN
Solar/Wind Harmer
0.02
232432Z2-076 GEN
Solar/Wind Harmer
0.047
232920IR10
Adder
1.12
234033AF1-007_GEN
Solar/Wind Harmer
8.279
232904IR4
Adder
28.625
213561DLWR9-10
Adder
1.175
213561DLWR9-10
Adder
0.898
233973AC2-185 C
Solar/Wind Harmer
1.233
219137THOSOLAR C
Solar/Wind Harmer
0.37
219914AD2-027 C
Solar/Wind Harmer
0.181
971011AG2-627 GEN
Solar/Wind Harmer
2.283
228309CCLP NUG
Adder
7.663
228309CCLP NUG
Adder
7.29
964001AG1-254 GEN
Solar/Wind Harmer
0.602
972141AH1-641 GEN
Solar/Wind Harmer
0.845
228260V4-054C
Solar/Wind Harmer
0.299
971535AH1-265 GEN
Solar/Wind Harmer
1.233
219272CLEANLIGHT C
Solar/Wind Harmer
0.053
970453AG2-297 GEN
Solar/Wind Harmer
0.788
219607WPEMNERT C
Solar/Wind Harmer
0.121
219224BRL12CT4
Adder
2.567
219688LUMSOLAR_S C
Solar/Wind Harmer
0.058
228754AB1-001 C
Solar/Wind Harmer
0.039
227927V4-067C
Solar/Wind Harmer
0.056
214067T20SOLAR
Solar/Wind Harmer
0.071
213611FALLS1-3
Adder
0.999
213611FALLS1-3
Adder
0.999
20717128DIX_Z2-102
Solar/Wind Harmer
0.347
20715728PEM_W1-119
Solar/Wind Harmer
0.14
20715828PEM_W1-120
Solar/Wind Harmer
0.14
971189AH1-054 GEN
Solar/Wind Harmer
0.304
970025AG2-016 GEN
Solar/Wind Harmer
0.728
207459AE1-142 C O1
Solar/Wind Harmer
0.27
219620RIDERU C
Solar/Wind Harmer
0.014
20714328BYD_X4-031
Solar/Wind Harmer
0.07
20714428HOW_X1-037
Solar/Wind Harmer
0.306
971521AH1-258 GEN
Solar/Wind Harmer
0.663
20720428HOL_W1-112
Solar/Wind Harmer
0.085
218455CINNBAY_CGEN
Adder
0.438
20635928PARLN3&4
Adder
1.773
20675528CPH_W2-050
Solar/Wind Harmer
0.112
218526CNTRALGAS2 C
Solar/Wind Harmer
0.088
218524CNTRALGAS1 C
Solar/Wind Harmer
0.088
208835TUHI V3-051
Solar/Wind Helper
0.011
208835TUHI V3-051
Solar/Wind Helper
0.011
233950AC2-186 GEN
Solar/Wind Harmer
0.202
232428Y3-058 C
Solar/Wind Harmer
0.299
971195AH1-057 GEN
Solar/Wind Harmer
0.391
233998TM1NIN_3.36
Solar/Wind Harmer
0.453
232404W1-003 C
Solar/Wind Harmer
0.358
232917OH NUG6
Adder
3.139
232915OH NUG4
Adder
3.132
232434Z2-077 GEN
Solar/Wind Harmer
0.089
972177AH1-672 GEN
Solar/Wind Harmer
4.749
213560DLW11-12
Adder
0.898
232900DEMECSMY
Adder
3.212
232901NORTHST
Adder
2.86
233972AC1-094 C
Solar/Wind Harmer
0.226
219258KINSLEYDEP C
Solar/Wind Harmer
0.098
219904AC1-010 C
Solar/Wind Harmer
0.114
219907AC1-030 C
Solar/Wind Harmer
0.041
228351V2-046C
Solar/Wind Harmer
0.596
230434AG1-499 GEN
Solar/Wind Harmer
0.172
970997AG2-616 GEN
Solar/Wind Harmer
2.817
945431AF1-208 GEN
Solar/Wind Harmer
2.525
230511AF1-262
Solar/Wind Harmer
0.054
228728W1-130C
Solar/Wind Harmer
0.192
228206SHRMN CT
Adder
4.757
219304NAMERICA C
Solar/Wind Harmer
0.089
219222BRL12CT2
Adder
2.567
228732V1-021 C
Adder
0.054
218660EHAMPSOLAR C
Solar/Wind Harmer
0.05
219287REEVESEAST C
Solar/Wind Harmer
0.382
219686LUMSOLAR_N C
Solar/Wind Harmer
0.058
214194N WALES4
Adder
0.241
213611FALLS1-3
Adder
0.999
20720728JCB_W1-129
Solar/Wind Harmer
0.079
207522AF2-254 C
Solar/Wind Harmer
0.377
207487AE2-000G4
Solar/Wind Harmer
8.125
207445AB1-138_GEN
Solar/Wind Harmer
0.148
20628028LAKEHURS
Adder
0.48
963711AG1-223 GEN
Solar/Wind Harmer
0.373
20714828MDF_W3-079
Solar/Wind Harmer
0.077
219680HOPEWELLV C1
Solar/Wind Harmer
0.019
207454AA2-184 E
Solar/Wind Harmer
0.247
20715228NPK_W1-113
Solar/Wind Harmer
0.106
217197RE CRAN C
Solar/Wind Harmer
0.133
20742028HF_AC1-207
Solar/Wind Harmer
0.192
20635828PARLN1&2
Adder
1.773
20635028RRCT1&2
Adder
2.765
20635128RRCT3&4
Adder
2.669
218428ETC SOLAR C
Solar/Wind Harmer
0.008
217213AMBOY SO C
Solar/Wind Harmer
0.03
208909MACR G3
Adder
31.429
223401AF1-299 GEN
Solar/Wind Helper
0.284
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.016
G-007ALTFEXP_G-007A->PJM
CMTX
12.213
CBM NorthLTFEXP_CBM-N->PJM
CBM
15.754
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.82
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.554
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
30.964
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.597
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
3.864

Details for NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line l/o PECO_P4_PEACH245_SRT-A/* $ CHESCO $ PECO_P4_PEACH245 $ STBK


Base Case Flowgate

Area:PECO
Facility Description:
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line
Contingency Name:
PECO_P4_PEACH245_SRT-A/* $ CHESCO $ PECO_P4_PEACH245 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:130.99 %
Rating:578.0 MVA
Rating Type:B
MVA to Mitigate:757.12
MW Contribution:2.33
Bus #Bus NameTypeMW Contribution
213589EDDYSTN4
Adder
31.553
213587EDDYSTN3
Adder
31.525
232416X2-083
Adder
0.191
233933AB2-153 GEN
Solar/Wind Harmer
0.464
233944AB2-135 GEN
Solar/Wind Harmer
2.13
234014AF1-036_GEN
Solar/Wind Harmer
1.089
231131BLOOM ENRGY
Adder
1.722
232424Y1-079 C
Solar/Wind Harmer
0.222
233984AB2-036 GEN
Solar/Wind Harmer
4.884
234041AC1-190 GEN
Solar/Wind Harmer
3.324
233987AB2-037 GEN
Solar/Wind Harmer
4.214
234036AF2-325 C
Solar/Wind Harmer
0.339
233946AB2-136 GEN
Solar/Wind Harmer
1.475
232926CRISFLD1
Adder
0.714
233901CHERRYDALE C
Solar/Wind Harmer
0.409
232408W1-005 C
Solar/Wind Harmer
0.364
232410W1-006 C
Solar/Wind Harmer
0.364
232918OH NUG7
Adder
3.188
232905CHERITON_25
Adder
0.892
971747AH1-380 GEN
Solar/Wind Harmer
1.301
972069AH1-584 GEN
Solar/Wind Harmer
3.252
972071AH1-585 GEN
Solar/Wind Harmer
3.252
231940T-011
Adder
0.271
970545AG2-347 GEN
Solar/Wind Harmer
23.583
232899W1-062
Adder
3.409
971149AH1-027 GEN
Solar/Wind Harmer
1.185
233939AC1-091 C
Solar/Wind Harmer
0.305
233970AC1-092 C
Solar/Wind Harmer
0.305
972233AH1-701 GEN
Adder
1.297
213815MOSER1-3
Adder
1.102
213815MOSER1-3
Adder
1.102
228304LOGAN
Adder
7.467
228307PCLP GT
Adder
3.712
219921AF1-264
Solar/Wind Harmer
0.044
228251CARLLS#4
Adder
0.187
219615MILLCREEK C
Solar/Wind Harmer
0.071
230433AD2-135 GEN
Solar/Wind Harmer
0.03
230407AD2-065 C
Solar/Wind Harmer
0.039
213535CROYDN11
Adder
3.017
230422AE1-104_GEN1
Solar/Wind Harmer
9.748
230425AE1-104_GEN2
Solar/Wind Harmer
9.748
219114HARTZY_C
Solar/Wind Harmer
0.229
20716428NHV_W2-082
Solar/Wind Harmer
0.478
207500AE2-000G1
Solar/Wind Harmer
8.307
207497AE2-000G2
Solar/Wind Harmer
8.307
207507AE2-000G3
Solar/Wind Harmer
8.307
20636128O CRK C2
Adder
1.7
20714928UPF_X1-085
Solar/Wind Harmer
0.108
963401AG1-189 GEN
Solar/Wind Harmer
0.303
963391AG1-188 GEN
Solar/Wind Harmer
0.504
20628028LAKEHURS
Adder
0.248
219817TRENTONSOL C
Solar/Wind Harmer
0.287
20720628TIN_W1-124
Solar/Wind Harmer
0.252
20641628MLH_W1-032
Solar/Wind Harmer
0.074
20716928W4-060COL
Solar/Wind Harmer
0.176
924131AB2-057 GEN
Solar/Wind Harmer
0.254
218440SUMMTASSOC C
Solar/Wind Harmer
0.031
20673828FLE_V3-070
Solar/Wind Harmer
0.111
213515CONOW3-4
50/50
0.747
213515CONOW3-4
50/50
0.747
213514CONOW1-2
50/50
0.56
213516CONOW5-6
50/50
0.56
233935AB2-179 C
Solar/Wind Harmer
1.165
231919CHRIST1
Adder
1.889
231920CHRIST2
Adder
1.847
971983AH1-536 GEN
Solar/Wind Harmer
3.085
232436AB1-176 C
Solar/Wind Harmer
0.093
233968AD2-076_GEN
Solar/Wind Harmer
2.668
970597AG2-380 GEN
Solar/Wind Harmer
1.675
231906DC3 NUG
Adder
5.55
231902DC CT7
Adder
4.437
231907DC10
Adder
1.385
213942SCHUYLKILL
Adder
1.31
213942SCHUYLKILL
Adder
1.002
213957STHWK3-4
Adder
0.993
213957STHWK3-4
Adder
0.993
232813VAUGHN
Adder
0.219
233955AB2-172 GEN
Solar/Wind Harmer
1.858
233923SMA
Solar/Wind Harmer
1.69
232912OH NUG1
Adder
3.209
232913OH NUG2
Adder
3.167
233990AG1-397 GEN
Solar/Wind Harmer
0.02
232432Z2-076 GEN
Solar/Wind Harmer
0.048
232920IR10
Adder
1.14
234033AF1-007_GEN
Solar/Wind Harmer
8.427
232904IR4
Adder
29.139
213561DLWR9-10
Adder
1.197
213561DLWR9-10
Adder
0.915
233973AC2-185 C
Solar/Wind Harmer
1.255
219137THOSOLAR C
Solar/Wind Harmer
0.377
219914AD2-027 C
Solar/Wind Harmer
0.185
971011AG2-627 GEN
Solar/Wind Harmer
2.329
228309CCLP NUG
Adder
7.816
228309CCLP NUG
Adder
7.434
964001AG1-254 GEN
Solar/Wind Harmer
0.614
972141AH1-641 GEN
Solar/Wind Harmer
0.862
228260V4-054C
Solar/Wind Harmer
0.305
971535AH1-265 GEN
Solar/Wind Harmer
1.258
219272CLEANLIGHT C
Solar/Wind Harmer
0.054
970453AG2-297 GEN
Solar/Wind Harmer
0.804
219607WPEMNERT C
Solar/Wind Harmer
0.123
219224BRL12CT4
Adder
2.62
219688LUMSOLAR_S C
Solar/Wind Harmer
0.059
228754AB1-001 C
Solar/Wind Harmer
0.04
227927V4-067C
Solar/Wind Harmer
0.057
214067T20SOLAR
Solar/Wind Harmer
0.073
213611FALLS1-3
Adder
1.02
213611FALLS1-3
Adder
1.02
20717128DIX_Z2-102
Solar/Wind Harmer
0.354
20715728PEM_W1-119
Solar/Wind Harmer
0.143
20715828PEM_W1-120
Solar/Wind Harmer
0.143
971189AH1-054 GEN
Solar/Wind Harmer
0.311
970025AG2-016 GEN
Solar/Wind Harmer
0.745
207459AE1-142 C O1
Solar/Wind Harmer
0.276
219620RIDERU C
Solar/Wind Harmer
0.015
20714328BYD_X4-031
Solar/Wind Harmer
0.072
20714428HOW_X1-037
Solar/Wind Harmer
0.313
971521AH1-258 GEN
Solar/Wind Harmer
0.679
20720428HOL_W1-112
Solar/Wind Harmer
0.087
218455CINNBAY_CGEN
Adder
0.449
20635928PARLN3&4
Adder
1.817
20675528CPH_W2-050
Solar/Wind Harmer
0.115
218526CNTRALGAS2 C
Solar/Wind Harmer
0.09
218524CNTRALGAS1 C
Solar/Wind Harmer
0.09
213508CON10-11
50/50
1.011
213518CONOW8-9
50/50
1.011
213514CONOW1-2
50/50
0.747
213516CONOW5-6
50/50
0.747
231918WEST 1
Adder
1.45
231917EM10
Adder
1.012
213497CHSTR7-9
Adder
1.078
213497CHSTR7-9
Adder
1.078
233930AB2-032 GEN
Solar/Wind Harmer
0.344
233915AB1-141 GEN
Solar/Wind Harmer
0.409
232422X3-066 FULL
Solar/Wind Harmer
0.101
234012AE2-112_GEN
Solar/Wind Harmer
0.926
213958STHWK5-6
Adder
0.993
232910NRG_G1
Adder
3.257
233964AF2-378 GEN
Solar/Wind Harmer
0.047
232426Y1-080 FULL
Solar/Wind Harmer
0.07
970277AG2-181 GEN
Solar/Wind Harmer
1.849
965821AG1-450 GEN
Solar/Wind Harmer
1.918
232919VN10
Adder
1.031
233954AC2-188 GEN
Solar/Wind Harmer
0.411
233950AC2-186 GEN
Solar/Wind Harmer
0.206
232428Y3-058 C
Solar/Wind Harmer
0.304
971195AH1-057 GEN
Solar/Wind Harmer
0.398
233998TM1NIN_3.36
Solar/Wind Harmer
0.461
232404W1-003 C
Solar/Wind Harmer
0.364
232917OH NUG6
Adder
3.195
232915OH NUG4
Adder
3.188
232434Z2-077 GEN
Solar/Wind Harmer
0.09
972177AH1-672 GEN
Solar/Wind Harmer
4.835
213560DLW11-12
Adder
0.915
232900DEMECSMY
Adder
3.27
232901NORTHST
Adder
2.913
233972AC1-094 C
Solar/Wind Harmer
0.23
219258KINSLEYDEP C
Solar/Wind Harmer
0.1
219904AC1-010 C
Solar/Wind Harmer
0.117
219907AC1-030 C
Solar/Wind Harmer
0.042
228351V2-046C
Solar/Wind Harmer
0.608
230434AG1-499 GEN
Solar/Wind Harmer
0.175
970997AG2-616 GEN
Solar/Wind Harmer
2.874
945431AF1-208 GEN
Solar/Wind Harmer
2.575
230511AF1-262
Solar/Wind Harmer
0.055
228728W1-130C
Solar/Wind Harmer
0.196
228206SHRMN CT
Adder
4.854
219304NAMERICA C
Solar/Wind Harmer
0.091
219222BRL12CT2
Adder
2.62
228732V1-021 C
Adder
0.055
218660EHAMPSOLAR C
Solar/Wind Harmer
0.051
219686LUMSOLAR_N C
Solar/Wind Harmer
0.059
219287REEVESEAST C
Solar/Wind Harmer
0.39
214194N WALES4
Adder
0.246
213611FALLS1-3
Adder
1.02
20720728JCB_W1-129
Solar/Wind Harmer
0.08
207522AF2-254 C
Solar/Wind Harmer
0.386
207487AE2-000G4
Solar/Wind Harmer
8.307
207445AB1-138_GEN
Solar/Wind Harmer
0.151
20628028LAKEHURS
Adder
0.491
963711AG1-223 GEN
Solar/Wind Harmer
0.381
20714828MDF_W3-079
Solar/Wind Harmer
0.079
219680HOPEWELLV C1
Solar/Wind Harmer
0.02
207454AA2-184 E
Solar/Wind Harmer
0.253
20715228NPK_W1-113
Solar/Wind Harmer
0.108
217197RE CRAN C
Solar/Wind Harmer
0.136
20742028HF_AC1-207
Solar/Wind Harmer
0.197
20635828PARLN1&2
Adder
1.817
20635028RRCT1&2
Adder
2.833
20635128RRCT3&4
Adder
2.735
218428ETC SOLAR C
Solar/Wind Harmer
0.009
217213AMBOY SO C
Solar/Wind Harmer
0.031
972275AH1-722 GEN
Adder
7.572
207528AF2-192 GEN
Solar/Wind Harmer
0.133
20673628F1S_V4-069
Solar/Wind Harmer
0.043
20675428EAM_W2-061
Solar/Wind Harmer
0.045
20676428JCR_X2-075
Solar/Wind Harmer
0.082
218449LINSOLAR C
Solar/Wind Harmer
0.239
208909MACR G3
Adder
32.41
223401AF1-299 GEN
Solar/Wind Helper
0.27
218418LINDEN_G5
Adder
4.119
218419LINDEN_G6
Adder
4.119
972260AH1-715 GEN1
Adder
3.298
207442AE1-156 GEN
Solar/Wind Harmer
0.178
20676128MHD_W3-029
Solar/Wind Harmer
0.114
219036LINDEN_G7
Adder
3.972
219035LINDEN_G8
Adder
3.915
972261AH1-715 GEN2
Adder
3.802
213508CON10-11
50/50
1.011
213518CONOW8-9
50/50
1.011
213517CONOW7
50/50
0.747
213497CHSTR7-9
Adder
1.078
233982AB2-133 GEN
Solar/Wind Harmer
2.015
233918AB1-142 GEN
Solar/Wind Harmer
0.409
213958STHWK5-6
Adder
0.993
232417X3-008 C
Solar/Wind Harmer
0.743
960671AF2-358 GEN
Solar/Wind Harmer
6.596
232907VN8
Adder
11.009
233952AC2-187 GEN
Solar/Wind Harmer
0.411
233994AC2-023 GEN
Solar/Wind Harmer
0.982
233940AF2-379 C
Solar/Wind Harmer
0.068
233900O-025 C
Adder
0.429
234015AF2-250 C
Solar/Wind Harmer
0.044
233996TM1833_GEN
Solar/Wind Harmer
0.461
233997TMININ_4.2
Solar/Wind Harmer
0.461
232406W1-004 FULL
Solar/Wind Harmer
0.364
232914OH NUG3
Adder
3.209
232916OH NUG5
Adder
3.209
232921TASLEY2G
Adder
1.876
233990AG1-397 GEN
Solar/Wind Harmer
0.417
972073AH1-586 GEN
Solar/Wind Harmer
3.403
972133AH1-634 GEN
Solar/Wind Harmer
3.573
213560DLW11-12
Adder
0.915
233971AC1-093 C
Solar/Wind Harmer
0.273
970695AG2-447 GEN
Solar/Wind Harmer
1.245
213815MOSER1-3
Adder
1.102
228304LOGAN
Adder
6.716
219766PARADISE C
Solar/Wind Harmer
0.097
219912AD2-042 GEN
Solar/Wind Harmer
0.245
219623KINSLEYBEA C
Solar/Wind Harmer
0.131
219236SOUTHERNHQ C
Solar/Wind Harmer
0.02
230430AE1-229_GEN
Solar/Wind Harmer
2.634
219906AC1-017 C
Solar/Wind Harmer
0.066
230415AB2-049 C
Solar/Wind Harmer
0.056
971553AH1-274 GEN
Solar/Wind Harmer
0.712
228711V2-041C
Solar/Wind Harmer
0.176
228202CUMB CT
Adder
4.823
219610FLORENCE C
Solar/Wind Harmer
0.407
219348LDSOLAR C
Solar/Wind Harmer
0.176
219221BRL12CT1
Adder
2.62
219223BRL12CT3
Adder
2.62
219291REEVESSOUT C
Solar/Wind Harmer
0.018
972251AH1-710 GEN
Adder
13.877
228729W2-030 C
Solar/Wind Harmer
0.166
959561AF2-247 GEN
Solar/Wind Harmer
0.137
20716028EGP_W2-019
Solar/Wind Harmer
0.125
20720828JCB_W4-025
Solar/Wind Harmer
0.122
219727YARDVSOLFA C
Solar/Wind Harmer
0.247
20715028HAN_X4-015
Solar/Wind Harmer
0.08
20636028O CRK C1
Adder
1.864
219276PARKLANDSO C
Solar/Wind Harmer
0.123
971667AH1-334 GEN
Solar/Wind Harmer
0.719
20714528FRN_Y2-051
Solar/Wind Harmer
0.076
219918AC2-009 C
Solar/Wind Harmer
0.016
20716228APLW2-078
Solar/Wind Harmer
0.223
20720528MAN_W1-024
Solar/Wind Harmer
0.064
219612MATRIX C
Solar/Wind Harmer
0.047
218438BLK ROCK C
Solar/Wind Harmer
0.035
967451AG2-055 C O1
Solar/Wind Harmer
42.856
20635828PARLN1&2
Adder
0.823
20635928PARLN3&4
Adder
0.823
20635028RRCT1&2
Adder
2.878
20635128RRCT3&4
Adder
2.386
219908AB1-139 C
Solar/Wind Harmer
0.092
219919AE1-041 FULL
Solar/Wind Harmer
0.01
219249CENTRALDIV C
Solar/Wind Harmer
0.01
20673728F2S_V4-070
Solar/Wind Harmer
0.043
223402AF1-300 C
Solar/Wind Helper
0.27
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.016
G-007ALTFEXP_G-007A->PJM
CMTX
12.515
CBM NorthLTFEXP_CBM-N->PJM
CBM
16.193
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.822
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.562
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
31.768
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.597
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
3.874

Details for NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line l/o PECO_P1-2_5012_SRT-A


Base Case Flowgate

Area:PECO
Facility Description:
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line
Contingency Name:
PECO_P1-2_5012_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:122.76 %
Rating:578.0 MVA
Rating Type:B
MVA to Mitigate:709.53
MW Contribution:1.62
Bus #Bus NameTypeMW Contribution
213508CON10-11
50/50
1.01
213518CONOW8-9
50/50
1.01
213517CONOW7
50/50
0.746
213890PHLISCT3
50/50
0.935
213888PHLISCT1
50/50
0.934
213739LIBE_CT2
50/50
0.778
213497CHSTR7-9
Adder
1.074
233982AB2-133 GEN
Solar/Wind Harmer
0.002
233918AB1-142 GEN
Solar/Wind Harmer
0.106
213958STHWK5-6
Adder
0.989
232417X3-008 C
Solar/Wind Harmer
0
960671AF2-358 GEN
Solar/Wind Harmer
4.583
232907VN8
Adder
10.963
233952AC2-187 GEN
Solar/Wind Harmer
0
233994AC2-023 GEN
Solar/Wind Harmer
0.002
233940AF2-379 C
Solar/Wind Harmer
0
233900O-025 C
Adder
0.427
234015AF2-250 C
Solar/Wind Harmer
0
233996TM1833_GEN
Solar/Wind Harmer
0.001
233997TMININ_4.2
Solar/Wind Harmer
0.001
232406W1-004 FULL
Solar/Wind Harmer
0.234
232921TASLEY2G
Adder
1.868
232914OH NUG3
Adder
3.196
232916OH NUG5
Adder
3.196
233990AG1-397 GEN
Solar/Wind Harmer
0.493
972073AH1-586 GEN
Solar/Wind Harmer
3.388
972133AH1-634 GEN
Solar/Wind Harmer
1.323
213560DLW11-12
Adder
0.911
233971AC1-093 C
Solar/Wind Harmer
0.015
970695AG2-447 GEN
Solar/Wind Harmer
0.865
213815MOSER1-3
Adder
1.097
228304LOGAN
Adder
6.684
219766PARADISE C
Solar/Wind Harmer
0
219912AD2-042 GEN
Solar/Wind Harmer
0
219623KINSLEYBEA C
Solar/Wind Harmer
0
230430AE1-229_GEN
Solar/Wind Harmer
0.005
219906AC1-017 C
Solar/Wind Harmer
0
230415AB2-049 C
Solar/Wind Harmer
0
971553AH1-274 GEN
Solar/Wind Harmer
0.457
228711V2-041C
Solar/Wind Harmer
0
228202CUMB CT
Adder
4.799
219610FLORENCE C
Solar/Wind Harmer
0
219348LDSOLAR C
Solar/Wind Harmer
0
219221BRL12CT1
Adder
2.607
219223BRL12CT3
Adder
2.607
972251AH1-710 GEN
Adder
13.808
228729W2-030 C
Solar/Wind Harmer
0
20716028EGP_W2-019
Solar/Wind Harmer
0
20720828JCB_W4-025
Solar/Wind Harmer
0
219727YARDVSOLFA C
Solar/Wind Harmer
0
20715028HAN_X4-015
Solar/Wind Harmer
0
20636028O CRK C1
Adder
1.854
219276PARKLANDSO C
Solar/Wind Harmer
0
971667AH1-334 GEN
Solar/Wind Harmer
0.462
20714528FRN_Y2-051
Solar/Wind Harmer
0
20716228APLW2-078
Solar/Wind Harmer
0
20720528MAN_W1-024
Solar/Wind Harmer
0
219612MATRIX C
Solar/Wind Harmer
0
218438BLK ROCK C
Solar/Wind Harmer
0
967451AG2-055 C O1
Solar/Wind Harmer
60.853
20635828PARLN1&2
Adder
0.818
20635928PARLN3&4
Adder
0.818
20635028RRCT1&2
Adder
2.86
20635128RRCT3&4
Adder
2.371
219908AB1-139 C
Solar/Wind Harmer
0
20673728F2S_V4-070
Solar/Wind Harmer
0
223402AF1-300 C
Solar/Wind Helper
0.271
231909HR2
50/50
0.609
231908HR1
50/50
0.606
231910HR3
50/50
0.606
213589EDDYSTN4
Adder
31.437
213587EDDYSTN3
Adder
31.41
232416X2-083
Adder
0.19
233933AB2-153 GEN
Solar/Wind Harmer
0.001
233944AB2-135 GEN
Solar/Wind Harmer
0.002
234014AF1-036_GEN
Solar/Wind Harmer
0.932
231131BLOOM ENRGY
Adder
1.715
232424Y1-079 C
Solar/Wind Harmer
0
233984AB2-036 GEN
Solar/Wind Harmer
2.839
234041AC1-190 GEN
Solar/Wind Harmer
2.694
233987AB2-037 GEN
Solar/Wind Harmer
0.004
234036AF2-325 C
Solar/Wind Harmer
0
233946AB2-136 GEN
Solar/Wind Harmer
0.001
232926CRISFLD1
Adder
0.711
233901CHERRYDALE C
Solar/Wind Harmer
0
232408W1-005 C
Solar/Wind Harmer
0.234
232410W1-006 C
Solar/Wind Harmer
0.234
232905CHERITON_25
Adder
0.888
232918OH NUG7
Adder
3.174
971747AH1-380 GEN
Solar/Wind Harmer
0.904
972069AH1-584 GEN
Solar/Wind Harmer
2.259
972071AH1-585 GEN
Solar/Wind Harmer
2.259
231940T-011
Adder
0.269
970545AG2-347 GEN
Solar/Wind Harmer
9.059
232899W1-062
Adder
3.394
971149AH1-027 GEN
Solar/Wind Harmer
1.089
233939AC1-091 C
Solar/Wind Harmer
0.001
233970AC1-092 C
Solar/Wind Harmer
0.001
972233AH1-701 GEN
Adder
1.291
213815MOSER1-3
Adder
1.097
213815MOSER1-3
Adder
1.097
228304LOGAN
Adder
7.432
228307PCLP GT
Adder
3.695
219921AF1-264
Solar/Wind Harmer
0
228251CARLLS#4
Adder
0.186
219615MILLCREEK C
Solar/Wind Harmer
0
230407AD2-065 C
Solar/Wind Harmer
0
213535CROYDN11
Adder
3.002
230422AE1-104_GEN1
Solar/Wind Harmer
3.894
230425AE1-104_GEN2
Solar/Wind Harmer
3.894
219114HARTZY_C
Solar/Wind Harmer
0
20716428NHV_W2-082
Solar/Wind Harmer
0
207500AE2-000G1
Solar/Wind Harmer
3.316
207497AE2-000G2
Solar/Wind Harmer
3.316
207507AE2-000G3
Solar/Wind Harmer
3.316
20636128O CRK C2
Adder
1.69
20714928UPF_X1-085
Solar/Wind Harmer
0
20628028LAKEHURS
Adder
0.247
20720628TIN_W1-124
Solar/Wind Harmer
0
20716928W4-060COL
Solar/Wind Harmer
0
218440SUMMTASSOC C
Solar/Wind Harmer
0
20673828FLE_V3-070
Solar/Wind Harmer
0
218418LINDEN_G5
Adder
4.092
218419LINDEN_G6
Adder
4.092
972260AH1-715 GEN1
Adder
3.277
207442AE1-156 GEN
Solar/Wind Harmer
0.014
20676128MHD_W3-029
Solar/Wind Harmer
0
213515CONOW3-4
50/50
0.746
213515CONOW3-4
50/50
0.746
213514CONOW1-2
50/50
0.56
213516CONOW5-6
50/50
0.56
213893PHLISST1
50/50
1.345
231916EM3
50/50
0.419
231919CHRIST1
50/50
1.997
231920CHRIST2
50/50
1.953
231901EM4
50/50
0.843
213740LIBE_ST1
50/50
1.071
231505HR4
50/50
0.884
233935AB2-179 C
Solar/Wind Harmer
0.64
971983AH1-536 GEN
Solar/Wind Harmer
0.727
232436AB1-176 C
Solar/Wind Harmer
0
233968AD2-076_GEN
Solar/Wind Harmer
0.932
970597AG2-380 GEN
Solar/Wind Harmer
1.669
231906DC3 NUG
Adder
5.528
231902DC CT7
Adder
4.419
231907DC10
Adder
1.38
213942SCHUYLKILL
Adder
1.305
213942SCHUYLKILL
Adder
0.998
213957STHWK3-4
Adder
0.989
213957STHWK3-4
Adder
0.989
232813VAUGHN
Adder
0.218
233955AB2-172 GEN
Solar/Wind Harmer
0.001
233923SMA
Solar/Wind Harmer
0.002
232912OH NUG1
Adder
3.196
232913OH NUG2
Adder
3.153
233990AG1-397 GEN
Solar/Wind Harmer
-0.058
232432Z2-076 GEN
Solar/Wind Harmer
0.005
232920IR10
Adder
1.135
234033AF1-007_GEN
Solar/Wind Harmer
0
232904IR4
Adder
29.014
213561DLWR9-10
Adder
1.191
213561DLWR9-10
Adder
0.911
233973AC2-185 C
Solar/Wind Harmer
0.001
219914AD2-027 C
Solar/Wind Harmer
0
971011AG2-627 GEN
Solar/Wind Harmer
1.617
228309CCLP NUG
Adder
7.778
228309CCLP NUG
Adder
7.399
964001AG1-254 GEN
Solar/Wind Harmer
0.117
972141AH1-641 GEN
Solar/Wind Harmer
0.998
228260V4-054C
Solar/Wind Harmer
0
971535AH1-265 GEN
Solar/Wind Harmer
0.809
219272CLEANLIGHT C
Solar/Wind Harmer
0
970453AG2-297 GEN
Solar/Wind Harmer
0.739
219607WPEMNERT C
Solar/Wind Harmer
0
219224BRL12CT4
Adder
2.607
219688LUMSOLAR_S C
Solar/Wind Harmer
0
228754AB1-001 C
Solar/Wind Harmer
0
227927V4-067C
Solar/Wind Harmer
0
214067T20SOLAR
Solar/Wind Harmer
0
213611FALLS1-3
Adder
1.014
213611FALLS1-3
Adder
1.014
20717128DIX_Z2-102
Solar/Wind Harmer
0
20715728PEM_W1-119
Solar/Wind Harmer
0
20715828PEM_W1-120
Solar/Wind Harmer
0
971189AH1-054 GEN
Solar/Wind Harmer
0.2
970025AG2-016 GEN
Solar/Wind Harmer
0.479
207459AE1-142 C O1
Solar/Wind Harmer
0
20714328BYD_X4-031
Solar/Wind Harmer
0.038
20714428HOW_X1-037
Solar/Wind Harmer
0
971521AH1-258 GEN
Solar/Wind Harmer
0.436
20720428HOL_W1-112
Solar/Wind Harmer
0
218455CINNBAY_CGEN
Adder
0.446
20635928PARLN3&4
Adder
1.806
218526CNTRALGAS2 C
Solar/Wind Harmer
0.186
218524CNTRALGAS1 C
Solar/Wind Harmer
0.184
213508CON10-11
50/50
1.01
213518CONOW8-9
50/50
1.01
213514CONOW1-2
50/50
0.746
213516CONOW5-6
50/50
0.746
231918WEST 1
50/50
1.533
213889PHLISCT2
50/50
0.934
231917EM10
50/50
1.07
213738LIBE_CT1
50/50
0.778
213497CHSTR7-9
Adder
1.074
213497CHSTR7-9
Adder
1.074
233930AB2-032 GEN
Solar/Wind Harmer
0.394
233915AB1-141 GEN
Solar/Wind Harmer
0.106
232422X3-066 FULL
Solar/Wind Harmer
0.034
234012AE2-112_GEN
Solar/Wind Harmer
0.932
213958STHWK5-6
Adder
0.989
232910NRG_G1
Adder
3.243
233964AF2-378 GEN
Solar/Wind Harmer
0
232426Y1-080 FULL
Solar/Wind Harmer
0
970277AG2-181 GEN
Solar/Wind Harmer
0.214
965821AG1-450 GEN
Solar/Wind Harmer
1.909
232919VN10
Adder
1.027
233954AC2-188 GEN
Solar/Wind Harmer
0
233950AC2-186 GEN
Solar/Wind Harmer
0
232428Y3-058 C
Solar/Wind Harmer
0.001
971195AH1-057 GEN
Solar/Wind Harmer
0.226
233998TM1NIN_3.36
Solar/Wind Harmer
0.001
232404W1-003 C
Solar/Wind Harmer
0.234
232917OH NUG6
Adder
3.182
232915OH NUG4
Adder
3.174
232434Z2-077 GEN
Solar/Wind Harmer
0.015
972177AH1-672 GEN
Solar/Wind Harmer
3.649
213560DLW11-12
Adder
0.911
232900DEMECSMY
Adder
3.256
232901NORTHST
Adder
2.9
233972AC1-094 C
Solar/Wind Harmer
0.109
219258KINSLEYDEP C
Solar/Wind Harmer
0
219904AC1-010 C
Solar/Wind Harmer
0
219907AC1-030 C
Solar/Wind Harmer
0
228351V2-046C
Solar/Wind Harmer
0
230434AG1-499 GEN
Solar/Wind Harmer
0
970997AG2-616 GEN
Solar/Wind Harmer
2.151
945431AF1-208 GEN
Solar/Wind Harmer
1.788
230511AF1-262
Solar/Wind Harmer
0
228728W1-130C
Solar/Wind Harmer
0
228206SHRMN CT
Adder
4.83
219304NAMERICA C
Solar/Wind Harmer
0.027
219222BRL12CT2
Adder
2.607
228732V1-021 C
Adder
0.055
218660EHAMPSOLAR C
Solar/Wind Harmer
0
219686LUMSOLAR_N C
Solar/Wind Harmer
0
219287REEVESEAST C
Solar/Wind Harmer
0
214194N WALES4
Adder
0.245
213611FALLS1-3
Adder
1.014
20720728JCB_W1-129
Solar/Wind Harmer
0
207522AF2-254 C
Solar/Wind Harmer
0.248
207487AE2-000G4
Solar/Wind Harmer
3.316
207445AB1-138_GEN
Solar/Wind Harmer
0
20628028LAKEHURS
Adder
0.489
20714828MDF_W3-079
Solar/Wind Harmer
0.025
207454AA2-184 E
Solar/Wind Harmer
0
20715228NPK_W1-113
Solar/Wind Harmer
0
217197RE CRAN C
Solar/Wind Harmer
0
20742028HF_AC1-207
Solar/Wind Harmer
0
20635828PARLN1&2
Adder
1.806
20635028RRCT1&2
Adder
2.816
20635128RRCT3&4
Adder
2.718
217213AMBOY SO C
Solar/Wind Harmer
0
972275AH1-722 GEN
Adder
7.523
207528AF2-192 GEN
Solar/Wind Harmer
0
20673628F1S_V4-069
Solar/Wind Harmer
0
20675428EAM_W2-061
Solar/Wind Harmer
0
208909MACR G3
Adder
32.152
223401AF1-299 GEN
Solar/Wind Helper
0.271
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.034
G-007ALTFEXP_G-007A->PJM
CMTX
12.437
CBM NorthLTFEXP_CBM-N->PJM
CBM
16.035
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.84
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.618
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
31.56
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.609
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
3.958

Details for NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line l/o PJM_500_BG_P4_5_CNSTN_C_SRT-A


Base Case Flowgate

Area:PECO
Facility Description:
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line
Contingency Name:
PJM_500_BG_P4_5_CNSTN_C_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:137.53 %
Rating:578.0 MVA
Rating Type:B
MVA to Mitigate:794.94
MW Contribution:2.32
Bus #Bus NameTypeMW Contribution
213589EDDYSTN4
Adder
31.437
213587EDDYSTN3
Adder
31.41
232416X2-083
Adder
0.19
233933AB2-153 GEN
Solar/Wind Harmer
0.463
233944AB2-135 GEN
Solar/Wind Harmer
2.122
234014AF1-036_GEN
Solar/Wind Harmer
1.085
231131BLOOM ENRGY
Adder
1.715
232424Y1-079 C
Solar/Wind Harmer
0.221
233984AB2-036 GEN
Solar/Wind Harmer
4.865
234041AC1-190 GEN
Solar/Wind Harmer
3.31
233987AB2-037 GEN
Solar/Wind Harmer
4.196
234036AF2-325 C
Solar/Wind Harmer
0.338
233946AB2-136 GEN
Solar/Wind Harmer
1.469
232926CRISFLD1
Adder
0.711
233901CHERRYDALE C
Solar/Wind Harmer
0.407
232408W1-005 C
Solar/Wind Harmer
0.362
232410W1-006 C
Solar/Wind Harmer
0.362
232905CHERITON_25
Adder
0.888
232918OH NUG7
Adder
3.174
971747AH1-380 GEN
Solar/Wind Harmer
1.296
972069AH1-584 GEN
Solar/Wind Harmer
3.238
972071AH1-585 GEN
Solar/Wind Harmer
3.238
231940T-011
Adder
0.269
970545AG2-347 GEN
Solar/Wind Harmer
23.481
232899W1-062
Adder
3.394
971149AH1-027 GEN
Solar/Wind Harmer
1.179
233939AC1-091 C
Solar/Wind Harmer
0.304
233970AC1-092 C
Solar/Wind Harmer
0.304
972233AH1-701 GEN
Adder
1.291
213815MOSER1-3
Adder
1.097
213815MOSER1-3
Adder
1.097
228304LOGAN
Adder
7.432
228307PCLP GT
Adder
3.695
219921AF1-264
Solar/Wind Harmer
0.044
228251CARLLS#4
Adder
0.186
219615MILLCREEK C
Solar/Wind Harmer
0.071
230433AD2-135 GEN
Solar/Wind Harmer
0.03
230407AD2-065 C
Solar/Wind Harmer
0.039
213535CROYDN11
Adder
3.002
230422AE1-104_GEN1
Solar/Wind Harmer
9.699
230425AE1-104_GEN2
Solar/Wind Harmer
9.699
219114HARTZY_C
Solar/Wind Harmer
0.227
20716428NHV_W2-082
Solar/Wind Harmer
0.476
207500AE2-000G1
Solar/Wind Harmer
8.261
207497AE2-000G2
Solar/Wind Harmer
8.261
207507AE2-000G3
Solar/Wind Harmer
8.261
20636128O CRK C2
Adder
1.69
20714928UPF_X1-085
Solar/Wind Harmer
0.107
963401AG1-189 GEN
Solar/Wind Harmer
0.301
963391AG1-188 GEN
Solar/Wind Harmer
0.501
20628028LAKEHURS
Adder
0.247
219817TRENTONSOL C
Solar/Wind Harmer
0.285
20720628TIN_W1-124
Solar/Wind Harmer
0.25
20641628MLH_W1-032
Solar/Wind Harmer
0.073
20716928W4-060COL
Solar/Wind Harmer
0.175
924131AB2-057 GEN
Solar/Wind Harmer
0.252
218440SUMMTASSOC C
Solar/Wind Harmer
0.031
20673828FLE_V3-070
Solar/Wind Harmer
0.11
218418LINDEN_G5
Adder
4.092
218419LINDEN_G6
Adder
4.092
972260AH1-715 GEN1
Adder
3.277
207442AE1-156 GEN
Solar/Wind Harmer
0.177
20676128MHD_W3-029
Solar/Wind Harmer
0.114
213508CON10-11
50/50
1.01
213518CONOW8-9
50/50
1.01
213514CONOW1-2
50/50
0.746
213516CONOW5-6
50/50
0.746
231918WEST 1
Adder
1.445
231917EM10
Adder
1.008
213497CHSTR7-9
Adder
1.074
213497CHSTR7-9
Adder
1.074
233930AB2-032 GEN
Solar/Wind Harmer
0.343
233915AB1-141 GEN
Solar/Wind Harmer
0.407
232422X3-066 FULL
Solar/Wind Harmer
0.101
234012AE2-112_GEN
Solar/Wind Harmer
0.922
213958STHWK5-6
Adder
0.989
232910NRG_G1
Adder
3.243
233964AF2-378 GEN
Solar/Wind Harmer
0.047
232426Y1-080 FULL
Solar/Wind Harmer
0.07
970277AG2-181 GEN
Solar/Wind Harmer
1.841
965821AG1-450 GEN
Solar/Wind Harmer
1.909
232919VN10
Adder
1.027
233954AC2-188 GEN
Solar/Wind Harmer
0.41
233950AC2-186 GEN
Solar/Wind Harmer
0.205
232428Y3-058 C
Solar/Wind Harmer
0.303
971195AH1-057 GEN
Solar/Wind Harmer
0.397
233998TM1NIN_3.36
Solar/Wind Harmer
0.459
232404W1-003 C
Solar/Wind Harmer
0.362
232917OH NUG6
Adder
3.182
232915OH NUG4
Adder
3.174
232434Z2-077 GEN
Solar/Wind Harmer
0.09
972177AH1-672 GEN
Solar/Wind Harmer
4.814
213560DLW11-12
Adder
0.911
232900DEMECSMY
Adder
3.256
232901NORTHST
Adder
2.9
233972AC1-094 C
Solar/Wind Harmer
0.229
219258KINSLEYDEP C
Solar/Wind Harmer
0.1
219904AC1-010 C
Solar/Wind Harmer
0.116
219907AC1-030 C
Solar/Wind Harmer
0.042
228351V2-046C
Solar/Wind Harmer
0.605
230434AG1-499 GEN
Solar/Wind Harmer
0.174
970997AG2-616 GEN
Solar/Wind Harmer
2.86
945431AF1-208 GEN
Solar/Wind Harmer
2.563
230511AF1-262
Solar/Wind Harmer
0.054
228728W1-130C
Solar/Wind Harmer
0.195
228206SHRMN CT
Adder
4.83
219304NAMERICA C
Solar/Wind Harmer
0.091
219222BRL12CT2
Adder
2.607
228732V1-021 C
Adder
0.055
218660EHAMPSOLAR C
Solar/Wind Harmer
0.051
219686LUMSOLAR_N C
Solar/Wind Harmer
0.058
219287REEVESEAST C
Solar/Wind Harmer
0.388
214194N WALES4
Adder
0.245
213611FALLS1-3
Adder
1.014
20720728JCB_W1-129
Solar/Wind Harmer
0.08
207522AF2-254 C
Solar/Wind Harmer
0.384
207487AE2-000G4
Solar/Wind Harmer
8.261
207445AB1-138_GEN
Solar/Wind Harmer
0.151
20628028LAKEHURS
Adder
0.489
963711AG1-223 GEN
Solar/Wind Harmer
0.379
20714828MDF_W3-079
Solar/Wind Harmer
0.078
219680HOPEWELLV C1
Solar/Wind Harmer
0.02
207454AA2-184 E
Solar/Wind Harmer
0.251
20715228NPK_W1-113
Solar/Wind Harmer
0.108
217197RE CRAN C
Solar/Wind Harmer
0.135
20742028HF_AC1-207
Solar/Wind Harmer
0.196
20635828PARLN1&2
Adder
1.806
20635028RRCT1&2
Adder
2.816
20635128RRCT3&4
Adder
2.718
218428ETC SOLAR C
Solar/Wind Harmer
0.009
217213AMBOY SO C
Solar/Wind Harmer
0.03
972275AH1-722 GEN
Adder
7.523
207528AF2-192 GEN
Solar/Wind Harmer
0.132
20673628F1S_V4-069
Solar/Wind Harmer
0.043
20675428EAM_W2-061
Solar/Wind Harmer
0.045
208909MACR G3
Adder
32.152
223401AF1-299 GEN
Solar/Wind Helper
0.271
213515CONOW3-4
50/50
0.746
213515CONOW3-4
50/50
0.746
213514CONOW1-2
50/50
0.56
213516CONOW5-6
50/50
0.56
233935AB2-179 C
Solar/Wind Harmer
1.161
231919CHRIST1
Adder
1.882
231920CHRIST2
Adder
1.84
971983AH1-536 GEN
Solar/Wind Harmer
3.073
232436AB1-176 C
Solar/Wind Harmer
0.092
233968AD2-076_GEN
Solar/Wind Harmer
2.657
970597AG2-380 GEN
Solar/Wind Harmer
1.669
231906DC3 NUG
Adder
5.528
231902DC CT7
Adder
4.419
231907DC10
Adder
1.38
213942SCHUYLKILL
Adder
1.305
213942SCHUYLKILL
Adder
0.998
213957STHWK3-4
Adder
0.989
213957STHWK3-4
Adder
0.989
232813VAUGHN
Adder
0.218
233955AB2-172 GEN
Solar/Wind Harmer
1.85
233923SMA
Solar/Wind Harmer
1.683
232912OH NUG1
Adder
3.196
232913OH NUG2
Adder
3.153
233990AG1-397 GEN
Solar/Wind Harmer
0.02
232432Z2-076 GEN
Solar/Wind Harmer
0.048
232920IR10
Adder
1.135
234033AF1-007_GEN
Solar/Wind Harmer
8.391
232904IR4
Adder
29.014
213561DLWR9-10
Adder
1.191
213561DLWR9-10
Adder
0.911
233973AC2-185 C
Solar/Wind Harmer
1.25
219137THOSOLAR C
Solar/Wind Harmer
0.375
219914AD2-027 C
Solar/Wind Harmer
0.184
971011AG2-627 GEN
Solar/Wind Harmer
2.317
228309CCLP NUG
Adder
7.778
228309CCLP NUG
Adder
7.399
964001AG1-254 GEN
Solar/Wind Harmer
0.611
972141AH1-641 GEN
Solar/Wind Harmer
0.858
228260V4-054C
Solar/Wind Harmer
0.303
971535AH1-265 GEN
Solar/Wind Harmer
1.252
219272CLEANLIGHT C
Solar/Wind Harmer
0.053
970453AG2-297 GEN
Solar/Wind Harmer
0.8
219607WPEMNERT C
Solar/Wind Harmer
0.122
219224BRL12CT4
Adder
2.607
219688LUMSOLAR_S C
Solar/Wind Harmer
0.059
228754AB1-001 C
Solar/Wind Harmer
0.04
227927V4-067C
Solar/Wind Harmer
0.057
214067T20SOLAR
Solar/Wind Harmer
0.073
213611FALLS1-3
Adder
1.014
213611FALLS1-3
Adder
1.014
20717128DIX_Z2-102
Solar/Wind Harmer
0.352
20715728PEM_W1-119
Solar/Wind Harmer
0.142
20715828PEM_W1-120
Solar/Wind Harmer
0.142
971189AH1-054 GEN
Solar/Wind Harmer
0.31
970025AG2-016 GEN
Solar/Wind Harmer
0.741
207459AE1-142 C O1
Solar/Wind Harmer
0.274
219620RIDERU C
Solar/Wind Harmer
0.014
20714328BYD_X4-031
Solar/Wind Harmer
0.071
20714428HOW_X1-037
Solar/Wind Harmer
0.311
971521AH1-258 GEN
Solar/Wind Harmer
0.675
20720428HOL_W1-112
Solar/Wind Harmer
0.086
218455CINNBAY_CGEN
Adder
0.446
20635928PARLN3&4
Adder
1.806
20675528CPH_W2-050
Solar/Wind Harmer
0.114
218526CNTRALGAS2 C
Solar/Wind Harmer
0.09
218524CNTRALGAS1 C
Solar/Wind Harmer
0.089
213508CON10-11
50/50
1.01
213518CONOW8-9
50/50
1.01
213517CONOW7
50/50
0.746
213497CHSTR7-9
Adder
1.074
233982AB2-133 GEN
Solar/Wind Harmer
2.007
233918AB1-142 GEN
Solar/Wind Harmer
0.407
213958STHWK5-6
Adder
0.989
232417X3-008 C
Solar/Wind Harmer
0.74
960671AF2-358 GEN
Solar/Wind Harmer
6.569
232907VN8
Adder
10.963
233952AC2-187 GEN
Solar/Wind Harmer
0.41
233994AC2-023 GEN
Solar/Wind Harmer
0.977
233940AF2-379 C
Solar/Wind Harmer
0.068
233900O-025 C
Adder
0.427
234015AF2-250 C
Solar/Wind Harmer
0.044
233996TM1833_GEN
Solar/Wind Harmer
0.459
233997TMININ_4.2
Solar/Wind Harmer
0.459
232406W1-004 FULL
Solar/Wind Harmer
0.362
232921TASLEY2G
Adder
1.868
232914OH NUG3
Adder
3.196
232916OH NUG5
Adder
3.196
233990AG1-397 GEN
Solar/Wind Harmer
0.415
972073AH1-586 GEN
Solar/Wind Harmer
3.388
972133AH1-634 GEN
Solar/Wind Harmer
3.558
213560DLW11-12
Adder
0.911
233971AC1-093 C
Solar/Wind Harmer
0.271
970695AG2-447 GEN
Solar/Wind Harmer
1.239
213815MOSER1-3
Adder
1.097
228304LOGAN
Adder
6.684
219766PARADISE C
Solar/Wind Harmer
0.097
219912AD2-042 GEN
Solar/Wind Harmer
0.244
219623KINSLEYBEA C
Solar/Wind Harmer
0.13
219236SOUTHERNHQ C
Solar/Wind Harmer
0.02
230430AE1-229_GEN
Solar/Wind Harmer
2.621
219906AC1-017 C
Solar/Wind Harmer
0.066
230415AB2-049 C
Solar/Wind Harmer
0.056
971553AH1-274 GEN
Solar/Wind Harmer
0.709
228711V2-041C
Solar/Wind Harmer
0.175
228202CUMB CT
Adder
4.799
219610FLORENCE C
Solar/Wind Harmer
0.405
219348LDSOLAR C
Solar/Wind Harmer
0.175
219221BRL12CT1
Adder
2.607
219223BRL12CT3
Adder
2.607
219291REEVESSOUT C
Solar/Wind Harmer
0.017
972251AH1-710 GEN
Adder
13.808
228729W2-030 C
Solar/Wind Harmer
0.165
959561AF2-247 GEN
Solar/Wind Harmer
0.137
20716028EGP_W2-019
Solar/Wind Harmer
0.124
20720828JCB_W4-025
Solar/Wind Harmer
0.121
219727YARDVSOLFA C
Solar/Wind Harmer
0.246
20715028HAN_X4-015
Solar/Wind Harmer
0.08
20636028O CRK C1
Adder
1.854
219276PARKLANDSO C
Solar/Wind Harmer
0.122
971667AH1-334 GEN
Solar/Wind Harmer
0.715
20714528FRN_Y2-051
Solar/Wind Harmer
0.076
219918AC2-009 C
Solar/Wind Harmer
0.016
20716228APLW2-078
Solar/Wind Harmer
0.222
20720528MAN_W1-024
Solar/Wind Harmer
0.064
219612MATRIX C
Solar/Wind Harmer
0.046
218438BLK ROCK C
Solar/Wind Harmer
0.034
967451AG2-055 C O1
Solar/Wind Harmer
42.597
20635828PARLN1&2
Adder
0.818
20635928PARLN3&4
Adder
0.818
20635028RRCT1&2
Adder
2.86
20635128RRCT3&4
Adder
2.371
219908AB1-139 C
Solar/Wind Harmer
0.091
219919AE1-041 FULL
Solar/Wind Harmer
0.01
219249CENTRALDIV C
Solar/Wind Harmer
0.009
20673728F2S_V4-070
Solar/Wind Harmer
0.043
223402AF1-300 C
Solar/Wind Helper
0.271
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.034
G-007ALTFEXP_G-007A->PJM
CMTX
12.437
CBM NorthLTFEXP_CBM-N->PJM
CBM
16.035
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.84
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.618
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
31.56
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.609
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
3.958

Details for NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line l/o PECO_P4_PEACH235_SRT-A/* $ CHESCO $ PECO_P4_PEACH235 $ STBK


Base Case Flowgate

Area:PECO
Facility Description:
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line
Contingency Name:
PECO_P4_PEACH235_SRT-A/* $ CHESCO $ PECO_P4_PEACH235 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:137.41 %
Rating:578.0 MVA
Rating Type:B
MVA to Mitigate:794.24
MW Contribution:2.32
Bus #Bus NameTypeMW Contribution
213508CON10-11
50/50
1.01
213518CONOW8-9
50/50
1.01
213517CONOW7
50/50
0.746
213497CHSTR7-9
Adder
1.074
233982AB2-133 GEN
Solar/Wind Harmer
2.008
233918AB1-142 GEN
Solar/Wind Harmer
0.408
213958STHWK5-6
Adder
0.99
232417X3-008 C
Solar/Wind Harmer
0.741
960671AF2-358 GEN
Solar/Wind Harmer
6.572
232907VN8
Adder
10.969
233952AC2-187 GEN
Solar/Wind Harmer
0.41
233994AC2-023 GEN
Solar/Wind Harmer
0.978
233940AF2-379 C
Solar/Wind Harmer
0.068
233900O-025 C
Adder
0.427
234015AF2-250 C
Solar/Wind Harmer
0.044
233996TM1833_GEN
Solar/Wind Harmer
0.459
233997TMININ_4.2
Solar/Wind Harmer
0.459
232406W1-004 FULL
Solar/Wind Harmer
0.363
232921TASLEY2G
Adder
1.869
232914OH NUG3
Adder
3.197
232916OH NUG5
Adder
3.197
233990AG1-397 GEN
Solar/Wind Harmer
0.415
972073AH1-586 GEN
Solar/Wind Harmer
3.39
972133AH1-634 GEN
Solar/Wind Harmer
3.56
213560DLW11-12
Adder
0.911
233971AC1-093 C
Solar/Wind Harmer
0.271
970695AG2-447 GEN
Solar/Wind Harmer
1.24
213815MOSER1-3
Adder
1.097
228304LOGAN
Adder
6.686
219766PARADISE C
Solar/Wind Harmer
0.097
219912AD2-042 GEN
Solar/Wind Harmer
0.244
219623KINSLEYBEA C
Solar/Wind Harmer
0.13
219236SOUTHERNHQ C
Solar/Wind Harmer
0.02
230430AE1-229_GEN
Solar/Wind Harmer
2.622
219906AC1-017 C
Solar/Wind Harmer
0.066
230415AB2-049 C
Solar/Wind Harmer
0.056
971553AH1-274 GEN
Solar/Wind Harmer
0.709
228711V2-041C
Solar/Wind Harmer
0.175
228202CUMB CT
Adder
4.801
219610FLORENCE C
Solar/Wind Harmer
0.405
219348LDSOLAR C
Solar/Wind Harmer
0.175
219221BRL12CT1
Adder
2.608
219223BRL12CT3
Adder
2.608
219291REEVESSOUT C
Solar/Wind Harmer
0.017
972251AH1-710 GEN
Adder
13.816
228729W2-030 C
Solar/Wind Harmer
0.165
959561AF2-247 GEN
Solar/Wind Harmer
0.137
20716028EGP_W2-019
Solar/Wind Harmer
0.124
20720828JCB_W4-025
Solar/Wind Harmer
0.121
219727YARDVSOLFA C
Solar/Wind Harmer
0.246
20715028HAN_X4-015
Solar/Wind Harmer
0.08
20636028O CRK C1
Adder
1.854
219276PARKLANDSO C
Solar/Wind Harmer
0.122
971667AH1-334 GEN
Solar/Wind Harmer
0.715
20714528FRN_Y2-051
Solar/Wind Harmer
0.076
219918AC2-009 C
Solar/Wind Harmer
0.016
20716228APLW2-078
Solar/Wind Harmer
0.222
20720528MAN_W1-024
Solar/Wind Harmer
0.064
219612MATRIX C
Solar/Wind Harmer
0.046
218438BLK ROCK C
Solar/Wind Harmer
0.034
967451AG2-055 C O1
Solar/Wind Harmer
42.608
20635828PARLN1&2
Adder
0.818
20635928PARLN3&4
Adder
0.818
20635028RRCT1&2
Adder
2.861
20635128RRCT3&4
Adder
2.372
219908AB1-139 C
Solar/Wind Harmer
0.092
219919AE1-041 FULL
Solar/Wind Harmer
0.01
219249CENTRALDIV C
Solar/Wind Harmer
0.009
20673728F2S_V4-070
Solar/Wind Harmer
0.043
223402AF1-300 C
Solar/Wind Helper
0.271
213515CONOW3-4
50/50
0.746
213515CONOW3-4
50/50
0.746
213514CONOW1-2
50/50
0.56
213516CONOW5-6
50/50
0.56
233935AB2-179 C
Solar/Wind Harmer
1.162
231919CHRIST1
Adder
1.883
231920CHRIST2
Adder
1.841
971983AH1-536 GEN
Solar/Wind Harmer
3.074
232436AB1-176 C
Solar/Wind Harmer
0.092
213589EDDYSTN4
Adder
31.443
213587EDDYSTN3
Adder
31.416
232416X2-083
Adder
0.19
233933AB2-153 GEN
Solar/Wind Harmer
0.463
233944AB2-135 GEN
Solar/Wind Harmer
2.123
234014AF1-036_GEN
Solar/Wind Harmer
1.085
231131BLOOM ENRGY
Adder
1.716
232424Y1-079 C
Solar/Wind Harmer
0.221
233984AB2-036 GEN
Solar/Wind Harmer
4.867
234041AC1-190 GEN
Solar/Wind Harmer
3.312
233987AB2-037 GEN
Solar/Wind Harmer
4.198
234036AF2-325 C
Solar/Wind Harmer
0.338
233946AB2-136 GEN
Solar/Wind Harmer
1.47
232926CRISFLD1
Adder
0.711
233901CHERRYDALE C
Solar/Wind Harmer
0.408
232408W1-005 C
Solar/Wind Harmer
0.363
232410W1-006 C
Solar/Wind Harmer
0.363
232905CHERITON_25
Adder
0.888
232918OH NUG7
Adder
3.176
971747AH1-380 GEN
Solar/Wind Harmer
1.296
972069AH1-584 GEN
Solar/Wind Harmer
3.239
972071AH1-585 GEN
Solar/Wind Harmer
3.239
231940T-011
Adder
0.27
970545AG2-347 GEN
Solar/Wind Harmer
23.494
232899W1-062
Adder
3.396
971149AH1-027 GEN
Solar/Wind Harmer
1.18
233939AC1-091 C
Solar/Wind Harmer
0.304
233970AC1-092 C
Solar/Wind Harmer
0.304
972233AH1-701 GEN
Adder
1.291
213815MOSER1-3
Adder
1.097
213815MOSER1-3
Adder
1.097
228304LOGAN
Adder
7.434
228307PCLP GT
Adder
3.696
219921AF1-264
Solar/Wind Harmer
0.044
228251CARLLS#4
Adder
0.186
219615MILLCREEK C
Solar/Wind Harmer
0.071
230433AD2-135 GEN
Solar/Wind Harmer
0.03
230407AD2-065 C
Solar/Wind Harmer
0.039
213535CROYDN11
Adder
3.003
230422AE1-104_GEN1
Solar/Wind Harmer
9.703
230425AE1-104_GEN2
Solar/Wind Harmer
9.703
219114HARTZY_C
Solar/Wind Harmer
0.227
20716428NHV_W2-082
Solar/Wind Harmer
0.476
207500AE2-000G1
Solar/Wind Harmer
8.264
207497AE2-000G2
Solar/Wind Harmer
8.264
207507AE2-000G3
Solar/Wind Harmer
8.264
20636128O CRK C2
Adder
1.691
20714928UPF_X1-085
Solar/Wind Harmer
0.107
963401AG1-189 GEN
Solar/Wind Harmer
0.301
963391AG1-188 GEN
Solar/Wind Harmer
0.501
20628028LAKEHURS
Adder
0.247
219817TRENTONSOL C
Solar/Wind Harmer
0.285
20720628TIN_W1-124
Solar/Wind Harmer
0.25
20641628MLH_W1-032
Solar/Wind Harmer
0.073
20716928W4-060COL
Solar/Wind Harmer
0.175
924131AB2-057 GEN
Solar/Wind Harmer
0.252
218440SUMMTASSOC C
Solar/Wind Harmer
0.031
20673828FLE_V3-070
Solar/Wind Harmer
0.11
218418LINDEN_G5
Adder
4.093
218419LINDEN_G6
Adder
4.093
972260AH1-715 GEN1
Adder
3.278
207442AE1-156 GEN
Solar/Wind Harmer
0.177
20676128MHD_W3-029
Solar/Wind Harmer
0.114
233968AD2-076_GEN
Solar/Wind Harmer
2.659
970597AG2-380 GEN
Solar/Wind Harmer
1.67
231906DC3 NUG
Adder
5.53
231902DC CT7
Adder
4.421
231907DC10
Adder
1.381
213942SCHUYLKILL
Adder
1.305
213942SCHUYLKILL
Adder
0.998
213957STHWK3-4
Adder
0.99
213957STHWK3-4
Adder
0.99
232813VAUGHN
Adder
0.219
233955AB2-172 GEN
Solar/Wind Harmer
1.851
233923SMA
Solar/Wind Harmer
1.683
232912OH NUG1
Adder
3.197
232913OH NUG2
Adder
3.155
233990AG1-397 GEN
Solar/Wind Harmer
0.02
232432Z2-076 GEN
Solar/Wind Harmer
0.048
232920IR10
Adder
1.136
234033AF1-007_GEN
Solar/Wind Harmer
8.396
232904IR4
Adder
29.029
213561DLWR9-10
Adder
1.192
213561DLWR9-10
Adder
0.911
233973AC2-185 C
Solar/Wind Harmer
1.25
219137THOSOLAR C
Solar/Wind Harmer
0.376
219914AD2-027 C
Solar/Wind Harmer
0.184
971011AG2-627 GEN
Solar/Wind Harmer
2.318
228309CCLP NUG
Adder
7.781
228309CCLP NUG
Adder
7.401
964001AG1-254 GEN
Solar/Wind Harmer
0.611
972141AH1-641 GEN
Solar/Wind Harmer
0.858
228260V4-054C
Solar/Wind Harmer
0.303
971535AH1-265 GEN
Solar/Wind Harmer
1.252
219272CLEANLIGHT C
Solar/Wind Harmer
0.053
970453AG2-297 GEN
Solar/Wind Harmer
0.801
219607WPEMNERT C
Solar/Wind Harmer
0.122
219224BRL12CT4
Adder
2.608
219688LUMSOLAR_S C
Solar/Wind Harmer
0.059
228754AB1-001 C
Solar/Wind Harmer
0.04
227927V4-067C
Solar/Wind Harmer
0.057
214067T20SOLAR
Solar/Wind Harmer
0.073
213611FALLS1-3
Adder
1.015
213611FALLS1-3
Adder
1.015
20717128DIX_Z2-102
Solar/Wind Harmer
0.353
20715728PEM_W1-119
Solar/Wind Harmer
0.142
20715828PEM_W1-120
Solar/Wind Harmer
0.142
971189AH1-054 GEN
Solar/Wind Harmer
0.31
970025AG2-016 GEN
Solar/Wind Harmer
0.741
207459AE1-142 C O1
Solar/Wind Harmer
0.274
219620RIDERU C
Solar/Wind Harmer
0.014
20714328BYD_X4-031
Solar/Wind Harmer
0.071
20714428HOW_X1-037
Solar/Wind Harmer
0.312
971521AH1-258 GEN
Solar/Wind Harmer
0.675
20720428HOL_W1-112
Solar/Wind Harmer
0.086
218455CINNBAY_CGEN
Adder
0.446
20635928PARLN3&4
Adder
1.806
20675528CPH_W2-050
Solar/Wind Harmer
0.114
218526CNTRALGAS2 C
Solar/Wind Harmer
0.09
218524CNTRALGAS1 C
Solar/Wind Harmer
0.089
213508CON10-11
50/50
1.01
213518CONOW8-9
50/50
1.01
213514CONOW1-2
50/50
0.746
213516CONOW5-6
50/50
0.746
231918WEST 1
Adder
1.445
231917EM10
Adder
1.009
213497CHSTR7-9
Adder
1.074
213497CHSTR7-9
Adder
1.074
233930AB2-032 GEN
Solar/Wind Harmer
0.343
233915AB1-141 GEN
Solar/Wind Harmer
0.408
232422X3-066 FULL
Solar/Wind Harmer
0.101
234012AE2-112_GEN
Solar/Wind Harmer
0.922
213958STHWK5-6
Adder
0.99
232910NRG_G1
Adder
3.245
233964AF2-378 GEN
Solar/Wind Harmer
0.047
232426Y1-080 FULL
Solar/Wind Harmer
0.07
970277AG2-181 GEN
Solar/Wind Harmer
1.842
965821AG1-450 GEN
Solar/Wind Harmer
1.91
232919VN10
Adder
1.027
233954AC2-188 GEN
Solar/Wind Harmer
0.41
233950AC2-186 GEN
Solar/Wind Harmer
0.205
232428Y3-058 C
Solar/Wind Harmer
0.303
971195AH1-057 GEN
Solar/Wind Harmer
0.397
233998TM1NIN_3.36
Solar/Wind Harmer
0.459
232404W1-003 C
Solar/Wind Harmer
0.363
232917OH NUG6
Adder
3.183
232915OH NUG4
Adder
3.176
232434Z2-077 GEN
Solar/Wind Harmer
0.09
972177AH1-672 GEN
Solar/Wind Harmer
4.816
213560DLW11-12
Adder
0.911
232900DEMECSMY
Adder
3.257
232901NORTHST
Adder
2.902
233972AC1-094 C
Solar/Wind Harmer
0.23
219258KINSLEYDEP C
Solar/Wind Harmer
0.1
219904AC1-010 C
Solar/Wind Harmer
0.116
219907AC1-030 C
Solar/Wind Harmer
0.042
228351V2-046C
Solar/Wind Harmer
0.605
230434AG1-499 GEN
Solar/Wind Harmer
0.174
970997AG2-616 GEN
Solar/Wind Harmer
2.861
945431AF1-208 GEN
Solar/Wind Harmer
2.564
230511AF1-262
Solar/Wind Harmer
0.054
228728W1-130C
Solar/Wind Harmer
0.195
228206SHRMN CT
Adder
4.832
219304NAMERICA C
Solar/Wind Harmer
0.091
219222BRL12CT2
Adder
2.608
228732V1-021 C
Adder
0.055
218660EHAMPSOLAR C
Solar/Wind Harmer
0.051
219686LUMSOLAR_N C
Solar/Wind Harmer
0.058
219287REEVESEAST C
Solar/Wind Harmer
0.388
214194N WALES4
Adder
0.245
213611FALLS1-3
Adder
1.015
20720728JCB_W1-129
Solar/Wind Harmer
0.08
207522AF2-254 C
Solar/Wind Harmer
0.384
207487AE2-000G4
Solar/Wind Harmer
8.264
207445AB1-138_GEN
Solar/Wind Harmer
0.151
20628028LAKEHURS
Adder
0.489
963711AG1-223 GEN
Solar/Wind Harmer
0.379
20714828MDF_W3-079
Solar/Wind Harmer
0.078
219680HOPEWELLV C1
Solar/Wind Harmer
0.02
207454AA2-184 E
Solar/Wind Harmer
0.251
20715228NPK_W1-113
Solar/Wind Harmer
0.108
217197RE CRAN C
Solar/Wind Harmer
0.135
20742028HF_AC1-207
Solar/Wind Harmer
0.196
20635828PARLN1&2
Adder
1.806
20635028RRCT1&2
Adder
2.817
20635128RRCT3&4
Adder
2.719
218428ETC SOLAR C
Solar/Wind Harmer
0.009
217213AMBOY SO C
Solar/Wind Harmer
0.03
972275AH1-722 GEN
Adder
7.525
207528AF2-192 GEN
Solar/Wind Harmer
0.132
20673628F1S_V4-069
Solar/Wind Harmer
0.043
20675428EAM_W2-061
Solar/Wind Harmer
0.045
208909MACR G3
Adder
32.156
223401AF1-299 GEN
Solar/Wind Helper
0.271
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.035
G-007ALTFEXP_G-007A->PJM
CMTX
12.44
CBM NorthLTFEXP_CBM-N->PJM
CBM
16.037
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.84
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.618
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
31.566
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.609
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
3.959

Details for NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line l/o BGE_P4_GRACETON_51_SRT-A


Base Case Flowgate

Area:PECO
Facility Description:
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line
Contingency Name:
BGE_P4_GRACETON_51_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:137.36 %
Rating:578.0 MVA
Rating Type:B
MVA to Mitigate:793.96
MW Contribution:2.32
Bus #Bus NameTypeMW Contribution
213508CON10-11
50/50
1.01
213518CONOW8-9
50/50
1.01
213517CONOW7
50/50
0.746
213497CHSTR7-9
Adder
1.074
233982AB2-133 GEN
Solar/Wind Harmer
2.007
233918AB1-142 GEN
Solar/Wind Harmer
0.407
213958STHWK5-6
Adder
0.989
232417X3-008 C
Solar/Wind Harmer
0.74
960671AF2-358 GEN
Solar/Wind Harmer
6.569
232907VN8
Adder
10.963
233952AC2-187 GEN
Solar/Wind Harmer
0.41
233994AC2-023 GEN
Solar/Wind Harmer
0.977
233940AF2-379 C
Solar/Wind Harmer
0.068
233900O-025 C
Adder
0.427
234015AF2-250 C
Solar/Wind Harmer
0.044
233996TM1833_GEN
Solar/Wind Harmer
0.459
233997TMININ_4.2
Solar/Wind Harmer
0.459
232406W1-004 FULL
Solar/Wind Harmer
0.362
232921TASLEY2G
Adder
1.868
232914OH NUG3
Adder
3.196
232916OH NUG5
Adder
3.196
233990AG1-397 GEN
Solar/Wind Harmer
0.415
972073AH1-586 GEN
Solar/Wind Harmer
3.388
972133AH1-634 GEN
Solar/Wind Harmer
3.558
213560DLW11-12
Adder
0.911
233971AC1-093 C
Solar/Wind Harmer
0.271
970695AG2-447 GEN
Solar/Wind Harmer
1.239
213815MOSER1-3
Adder
1.097
228304LOGAN
Adder
6.684
219766PARADISE C
Solar/Wind Harmer
0.097
219912AD2-042 GEN
Solar/Wind Harmer
0.244
219623KINSLEYBEA C
Solar/Wind Harmer
0.13
219236SOUTHERNHQ C
Solar/Wind Harmer
0.02
230430AE1-229_GEN
Solar/Wind Harmer
2.621
219906AC1-017 C
Solar/Wind Harmer
0.066
230415AB2-049 C
Solar/Wind Harmer
0.056
971553AH1-274 GEN
Solar/Wind Harmer
0.709
228711V2-041C
Solar/Wind Harmer
0.175
228202CUMB CT
Adder
4.799
219610FLORENCE C
Solar/Wind Harmer
0.405
219348LDSOLAR C
Solar/Wind Harmer
0.175
219221BRL12CT1
Adder
2.607
219223BRL12CT3
Adder
2.607
219291REEVESSOUT C
Solar/Wind Harmer
0.017
972251AH1-710 GEN
Adder
13.808
228729W2-030 C
Solar/Wind Harmer
0.165
959561AF2-247 GEN
Solar/Wind Harmer
0.137
20716028EGP_W2-019
Solar/Wind Harmer
0.124
20720828JCB_W4-025
Solar/Wind Harmer
0.121
219727YARDVSOLFA C
Solar/Wind Harmer
0.246
20715028HAN_X4-015
Solar/Wind Harmer
0.08
20636028O CRK C1
Adder
1.854
219276PARKLANDSO C
Solar/Wind Harmer
0.122
971667AH1-334 GEN
Solar/Wind Harmer
0.715
20714528FRN_Y2-051
Solar/Wind Harmer
0.076
219918AC2-009 C
Solar/Wind Harmer
0.016
20716228APLW2-078
Solar/Wind Harmer
0.222
20720528MAN_W1-024
Solar/Wind Harmer
0.064
219612MATRIX C
Solar/Wind Harmer
0.046
218438BLK ROCK C
Solar/Wind Harmer
0.034
967451AG2-055 C O1
Solar/Wind Harmer
42.597
20635828PARLN1&2
Adder
0.818
20635928PARLN3&4
Adder
0.818
20635028RRCT1&2
Adder
2.86
20635128RRCT3&4
Adder
2.371
219908AB1-139 C
Solar/Wind Harmer
0.091
219919AE1-041 FULL
Solar/Wind Harmer
0.01
219249CENTRALDIV C
Solar/Wind Harmer
0.009
20673728F2S_V4-070
Solar/Wind Harmer
0.043
223402AF1-300 C
Solar/Wind Helper
0.271
213589EDDYSTN4
Adder
31.437
213587EDDYSTN3
Adder
31.41
232416X2-083
Adder
0.19
233933AB2-153 GEN
Solar/Wind Harmer
0.463
233944AB2-135 GEN
Solar/Wind Harmer
2.122
234014AF1-036_GEN
Solar/Wind Harmer
1.085
231131BLOOM ENRGY
Adder
1.715
232424Y1-079 C
Solar/Wind Harmer
0.221
233984AB2-036 GEN
Solar/Wind Harmer
4.865
234041AC1-190 GEN
Solar/Wind Harmer
3.31
233987AB2-037 GEN
Solar/Wind Harmer
4.196
234036AF2-325 C
Solar/Wind Harmer
0.338
233946AB2-136 GEN
Solar/Wind Harmer
1.469
232926CRISFLD1
Adder
0.711
233901CHERRYDALE C
Solar/Wind Harmer
0.407
232408W1-005 C
Solar/Wind Harmer
0.362
232410W1-006 C
Solar/Wind Harmer
0.362
232905CHERITON_25
Adder
0.888
232918OH NUG7
Adder
3.174
971747AH1-380 GEN
Solar/Wind Harmer
1.296
972069AH1-584 GEN
Solar/Wind Harmer
3.238
972071AH1-585 GEN
Solar/Wind Harmer
3.238
231940T-011
Adder
0.269
970545AG2-347 GEN
Solar/Wind Harmer
23.481
232899W1-062
Adder
3.394
971149AH1-027 GEN
Solar/Wind Harmer
1.179
233939AC1-091 C
Solar/Wind Harmer
0.304
233970AC1-092 C
Solar/Wind Harmer
0.304
972233AH1-701 GEN
Adder
1.291
213815MOSER1-3
Adder
1.097
213815MOSER1-3
Adder
1.097
228304LOGAN
Adder
7.432
228307PCLP GT
Adder
3.695
219921AF1-264
Solar/Wind Harmer
0.044
228251CARLLS#4
Adder
0.186
219615MILLCREEK C
Solar/Wind Harmer
0.071
230433AD2-135 GEN
Solar/Wind Harmer
0.03
230407AD2-065 C
Solar/Wind Harmer
0.039
213535CROYDN11
Adder
3.002
230422AE1-104_GEN1
Solar/Wind Harmer
9.699
230425AE1-104_GEN2
Solar/Wind Harmer
9.699
219114HARTZY_C
Solar/Wind Harmer
0.227
20716428NHV_W2-082
Solar/Wind Harmer
0.476
207500AE2-000G1
Solar/Wind Harmer
8.261
207497AE2-000G2
Solar/Wind Harmer
8.261
207507AE2-000G3
Solar/Wind Harmer
8.261
20636128O CRK C2
Adder
1.69
20714928UPF_X1-085
Solar/Wind Harmer
0.107
963401AG1-189 GEN
Solar/Wind Harmer
0.301
963391AG1-188 GEN
Solar/Wind Harmer
0.501
20628028LAKEHURS
Adder
0.247
219817TRENTONSOL C
Solar/Wind Harmer
0.285
20720628TIN_W1-124
Solar/Wind Harmer
0.25
20641628MLH_W1-032
Solar/Wind Harmer
0.073
20716928W4-060COL
Solar/Wind Harmer
0.175
924131AB2-057 GEN
Solar/Wind Harmer
0.252
218440SUMMTASSOC C
Solar/Wind Harmer
0.031
20673828FLE_V3-070
Solar/Wind Harmer
0.11
218418LINDEN_G5
Adder
4.092
218419LINDEN_G6
Adder
4.092
972260AH1-715 GEN1
Adder
3.277
207442AE1-156 GEN
Solar/Wind Harmer
0.177
20676128MHD_W3-029
Solar/Wind Harmer
0.114
213508CON10-11
50/50
1.01
213518CONOW8-9
50/50
1.01
213514CONOW1-2
50/50
0.746
213516CONOW5-6
50/50
0.746
231918WEST 1
Adder
1.445
231917EM10
Adder
1.008
213497CHSTR7-9
Adder
1.074
213497CHSTR7-9
Adder
1.074
233930AB2-032 GEN
Solar/Wind Harmer
0.343
233915AB1-141 GEN
Solar/Wind Harmer
0.407
232422X3-066 FULL
Solar/Wind Harmer
0.101
234012AE2-112_GEN
Solar/Wind Harmer
0.922
213958STHWK5-6
Adder
0.989
232910NRG_G1
Adder
3.243
233964AF2-378 GEN
Solar/Wind Harmer
0.047
232426Y1-080 FULL
Solar/Wind Harmer
0.07
970277AG2-181 GEN
Solar/Wind Harmer
1.841
965821AG1-450 GEN
Solar/Wind Harmer
1.909
232919VN10
Adder
1.027
233954AC2-188 GEN
Solar/Wind Harmer
0.41
233950AC2-186 GEN
Solar/Wind Harmer
0.205
232428Y3-058 C
Solar/Wind Harmer
0.303
971195AH1-057 GEN
Solar/Wind Harmer
0.397
233998TM1NIN_3.36
Solar/Wind Harmer
0.459
232404W1-003 C
Solar/Wind Harmer
0.362
232917OH NUG6
Adder
3.182
232915OH NUG4
Adder
3.174
232434Z2-077 GEN
Solar/Wind Harmer
0.09
972177AH1-672 GEN
Solar/Wind Harmer
4.814
213560DLW11-12
Adder
0.911
232900DEMECSMY
Adder
3.256
232901NORTHST
Adder
2.9
233972AC1-094 C
Solar/Wind Harmer
0.229
219258KINSLEYDEP C
Solar/Wind Harmer
0.1
219904AC1-010 C
Solar/Wind Harmer
0.116
219907AC1-030 C
Solar/Wind Harmer
0.042
228351V2-046C
Solar/Wind Harmer
0.605
230434AG1-499 GEN
Solar/Wind Harmer
0.174
970997AG2-616 GEN
Solar/Wind Harmer
2.86
945431AF1-208 GEN
Solar/Wind Harmer
2.563
230511AF1-262
Solar/Wind Harmer
0.054
228728W1-130C
Solar/Wind Harmer
0.195
228206SHRMN CT
Adder
4.83
219304NAMERICA C
Solar/Wind Harmer
0.091
219222BRL12CT2
Adder
2.607
228732V1-021 C
Adder
0.055
218660EHAMPSOLAR C
Solar/Wind Harmer
0.051
219686LUMSOLAR_N C
Solar/Wind Harmer
0.058
219287REEVESEAST C
Solar/Wind Harmer
0.388
214194N WALES4
Adder
0.245
213611FALLS1-3
Adder
1.014
20720728JCB_W1-129
Solar/Wind Harmer
0.08
207522AF2-254 C
Solar/Wind Harmer
0.384
207487AE2-000G4
Solar/Wind Harmer
8.261
207445AB1-138_GEN
Solar/Wind Harmer
0.151
20628028LAKEHURS
Adder
0.489
963711AG1-223 GEN
Solar/Wind Harmer
0.379
20714828MDF_W3-079
Solar/Wind Harmer
0.078
219680HOPEWELLV C1
Solar/Wind Harmer
0.02
207454AA2-184 E
Solar/Wind Harmer
0.251
20715228NPK_W1-113
Solar/Wind Harmer
0.108
217197RE CRAN C
Solar/Wind Harmer
0.135
20742028HF_AC1-207
Solar/Wind Harmer
0.196
20635828PARLN1&2
Adder
1.806
20635028RRCT1&2
Adder
2.816
20635128RRCT3&4
Adder
2.718
218428ETC SOLAR C
Solar/Wind Harmer
0.009
217213AMBOY SO C
Solar/Wind Harmer
0.03
972275AH1-722 GEN
Adder
7.523
207528AF2-192 GEN
Solar/Wind Harmer
0.132
20673628F1S_V4-069
Solar/Wind Harmer
0.043
20675428EAM_W2-061
Solar/Wind Harmer
0.045
208909MACR G3
Adder
32.152
223401AF1-299 GEN
Solar/Wind Helper
0.271
213515CONOW3-4
50/50
0.746
213515CONOW3-4
50/50
0.746
213514CONOW1-2
50/50
0.56
213516CONOW5-6
50/50
0.56
233935AB2-179 C
Solar/Wind Harmer
1.161
231919CHRIST1
Adder
1.882
231920CHRIST2
Adder
1.84
971983AH1-536 GEN
Solar/Wind Harmer
3.073
232436AB1-176 C
Solar/Wind Harmer
0.092
233968AD2-076_GEN
Solar/Wind Harmer
2.657
970597AG2-380 GEN
Solar/Wind Harmer
1.669
231906DC3 NUG
Adder
5.528
231902DC CT7
Adder
4.419
231907DC10
Adder
1.38
213942SCHUYLKILL
Adder
1.305
213942SCHUYLKILL
Adder
0.998
213957STHWK3-4
Adder
0.989
213957STHWK3-4
Adder
0.989
232813VAUGHN
Adder
0.218
233955AB2-172 GEN
Solar/Wind Harmer
1.85
233923SMA
Solar/Wind Harmer
1.683
232912OH NUG1
Adder
3.196
232913OH NUG2
Adder
3.153
233990AG1-397 GEN
Solar/Wind Harmer
0.02
232432Z2-076 GEN
Solar/Wind Harmer
0.048
232920IR10
Adder
1.135
234033AF1-007_GEN
Solar/Wind Harmer
8.391
232904IR4
Adder
29.014
213561DLWR9-10
Adder
1.191
213561DLWR9-10
Adder
0.911
233973AC2-185 C
Solar/Wind Harmer
1.25
219137THOSOLAR C
Solar/Wind Harmer
0.375
219914AD2-027 C
Solar/Wind Harmer
0.184
971011AG2-627 GEN
Solar/Wind Harmer
2.317
228309CCLP NUG
Adder
7.778
228309CCLP NUG
Adder
7.399
964001AG1-254 GEN
Solar/Wind Harmer
0.611
972141AH1-641 GEN
Solar/Wind Harmer
0.858
228260V4-054C
Solar/Wind Harmer
0.303
971535AH1-265 GEN
Solar/Wind Harmer
1.252
219272CLEANLIGHT C
Solar/Wind Harmer
0.053
970453AG2-297 GEN
Solar/Wind Harmer
0.8
219607WPEMNERT C
Solar/Wind Harmer
0.122
219224BRL12CT4
Adder
2.607
219688LUMSOLAR_S C
Solar/Wind Harmer
0.059
228754AB1-001 C
Solar/Wind Harmer
0.04
227927V4-067C
Solar/Wind Harmer
0.057
214067T20SOLAR
Solar/Wind Harmer
0.073
213611FALLS1-3
Adder
1.014
213611FALLS1-3
Adder
1.014
20717128DIX_Z2-102
Solar/Wind Harmer
0.352
20715728PEM_W1-119
Solar/Wind Harmer
0.142
20715828PEM_W1-120
Solar/Wind Harmer
0.142
971189AH1-054 GEN
Solar/Wind Harmer
0.31
970025AG2-016 GEN
Solar/Wind Harmer
0.741
207459AE1-142 C O1
Solar/Wind Harmer
0.274
219620RIDERU C
Solar/Wind Harmer
0.014
20714328BYD_X4-031
Solar/Wind Harmer
0.071
20714428HOW_X1-037
Solar/Wind Harmer
0.311
971521AH1-258 GEN
Solar/Wind Harmer
0.675
20720428HOL_W1-112
Solar/Wind Harmer
0.086
218455CINNBAY_CGEN
Adder
0.446
20635928PARLN3&4
Adder
1.806
20675528CPH_W2-050
Solar/Wind Harmer
0.114
218526CNTRALGAS2 C
Solar/Wind Harmer
0.09
218524CNTRALGAS1 C
Solar/Wind Harmer
0.089
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.034
G-007ALTFEXP_G-007A->PJM
CMTX
12.437
CBM NorthLTFEXP_CBM-N->PJM
CBM
16.035
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.84
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.618
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
31.56
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.609
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
3.958

Details for NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line l/o PJM_500_BG_P4_5_CNSTN_B_SRT-A


Base Case Flowgate

Area:PECO
Facility Description:
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line
Contingency Name:
PJM_500_BG_P4_5_CNSTN_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:136.42 %
Rating:578.0 MVA
Rating Type:B
MVA to Mitigate:788.52
MW Contribution:2.28
Bus #Bus NameTypeMW Contribution
213508CON10-11
50/50
1.003
213518CONOW8-9
50/50
1.003
213517CONOW7
50/50
0.741
213497CHSTR7-9
Adder
1.06
233982AB2-133 GEN
Solar/Wind Harmer
1.982
233918AB1-142 GEN
Solar/Wind Harmer
0.402
213958STHWK5-6
Adder
0.976
232417X3-008 C
Solar/Wind Harmer
0.73
960671AF2-358 GEN
Solar/Wind Harmer
6.482
232907VN8
Adder
10.817
233952AC2-187 GEN
Solar/Wind Harmer
0.404
233994AC2-023 GEN
Solar/Wind Harmer
0.964
233940AF2-379 C
Solar/Wind Harmer
0.067
234015AF2-250 C
Solar/Wind Harmer
0.043
233900O-025 C
Adder
0.421
233996TM1833_GEN
Solar/Wind Harmer
0.453
233997TMININ_4.2
Solar/Wind Harmer
0.453
232406W1-004 FULL
Solar/Wind Harmer
0.358
232914OH NUG3
Adder
3.153
232916OH NUG5
Adder
3.153
232921TASLEY2G
Adder
1.843
233990AG1-397 GEN
Solar/Wind Harmer
0.409
972073AH1-586 GEN
Solar/Wind Harmer
3.343
972133AH1-634 GEN
Solar/Wind Harmer
3.51
213560DLW11-12
Adder
0.898
233971AC1-093 C
Solar/Wind Harmer
0.268
970695AG2-447 GEN
Solar/Wind Harmer
1.222
213815MOSER1-3
Adder
1.08
228304LOGAN
Adder
6.586
219766PARADISE C
Solar/Wind Harmer
0.095
219912AD2-042 GEN
Solar/Wind Harmer
0.241
219623KINSLEYBEA C
Solar/Wind Harmer
0.128
219236SOUTHERNHQ C
Solar/Wind Harmer
0.02
230430AE1-229_GEN
Solar/Wind Harmer
2.582
219906AC1-017 C
Solar/Wind Harmer
0.065
230415AB2-049 C
Solar/Wind Harmer
0.055
971553AH1-274 GEN
Solar/Wind Harmer
0.698
228711V2-041C
Solar/Wind Harmer
0.172
228202CUMB CT
Adder
4.727
219610FLORENCE C
Solar/Wind Harmer
0.398
219348LDSOLAR C
Solar/Wind Harmer
0.172
219221BRL12CT1
Adder
2.567
219223BRL12CT3
Adder
2.567
219291REEVESSOUT C
Solar/Wind Harmer
0.017
972251AH1-710 GEN
Adder
13.602
228729W2-030 C
Solar/Wind Harmer
0.163
959561AF2-247 GEN
Solar/Wind Harmer
0.134
20716028EGP_W2-019
Solar/Wind Harmer
0.122
20720828JCB_W4-025
Solar/Wind Harmer
0.119
219727YARDVSOLFA C
Solar/Wind Harmer
0.242
20715028HAN_X4-015
Solar/Wind Harmer
0.079
20636028O CRK C1
Adder
1.823
219276PARKLANDSO C
Solar/Wind Harmer
0.12
971667AH1-334 GEN
Solar/Wind Harmer
0.703
20714528FRN_Y2-051
Solar/Wind Harmer
0.074
219918AC2-009 C
Solar/Wind Harmer
0.016
20716228APLW2-078
Solar/Wind Harmer
0.218
20720528MAN_W1-024
Solar/Wind Harmer
0.062
219612MATRIX C
Solar/Wind Harmer
0.046
218438BLK ROCK C
Solar/Wind Harmer
0.034
967451AG2-055 C O1
Solar/Wind Harmer
41.842
20635828PARLN1&2
Adder
0.803
20635928PARLN3&4
Adder
0.803
20635028RRCT1&2
Adder
2.808
20635128RRCT3&4
Adder
2.328
219908AB1-139 C
Solar/Wind Harmer
0.09
219919AE1-041 FULL
Solar/Wind Harmer
0.01
223402AF1-300 C
Solar/Wind Helper
0.284
213589EDDYSTN4
Adder
31.043
213587EDDYSTN3
Adder
31.015
232416X2-083
Adder
0.188
233933AB2-153 GEN
Solar/Wind Harmer
0.457
233944AB2-135 GEN
Solar/Wind Harmer
2.096
234014AF1-036_GEN
Solar/Wind Harmer
1.071
231131BLOOM ENRGY
Adder
1.693
232424Y1-079 C
Solar/Wind Harmer
0.218
233984AB2-036 GEN
Solar/Wind Harmer
4.803
234041AC1-190 GEN
Solar/Wind Harmer
3.266
233987AB2-037 GEN
Solar/Wind Harmer
4.141
234036AF2-325 C
Solar/Wind Harmer
0.334
233946AB2-136 GEN
Solar/Wind Harmer
1.449
232926CRISFLD1
Adder
0.702
233901CHERRYDALE C
Solar/Wind Harmer
0.402
232408W1-005 C
Solar/Wind Harmer
0.358
232410W1-006 C
Solar/Wind Harmer
0.358
232918OH NUG7
Adder
3.132
232905CHERITON_25
Adder
0.876
971747AH1-380 GEN
Solar/Wind Harmer
1.278
972069AH1-584 GEN
Solar/Wind Harmer
3.195
972071AH1-585 GEN
Solar/Wind Harmer
3.195
231940T-011
Adder
0.266
970545AG2-347 GEN
Solar/Wind Harmer
23.167
232899W1-062
Adder
3.348
971149AH1-027 GEN
Solar/Wind Harmer
1.163
233939AC1-091 C
Solar/Wind Harmer
0.3
233970AC1-092 C
Solar/Wind Harmer
0.3
972233AH1-701 GEN
Adder
1.272
213815MOSER1-3
Adder
1.08
213815MOSER1-3
Adder
1.08
228304LOGAN
Adder
7.323
228307PCLP GT
Adder
3.641
219921AF1-264
Solar/Wind Harmer
0.043
228251CARLLS#4
Adder
0.183
219615MILLCREEK C
Solar/Wind Harmer
0.07
230433AD2-135 GEN
Solar/Wind Harmer
0.029
230407AD2-065 C
Solar/Wind Harmer
0.038
213535CROYDN11
Adder
2.956
230422AE1-104_GEN1
Solar/Wind Harmer
9.552
230425AE1-104_GEN2
Solar/Wind Harmer
9.552
219114HARTZY_C
Solar/Wind Harmer
0.224
20716428NHV_W2-082
Solar/Wind Harmer
0.468
207500AE2-000G1
Solar/Wind Harmer
8.125
207497AE2-000G2
Solar/Wind Harmer
8.125
207507AE2-000G3
Solar/Wind Harmer
8.125
20636128O CRK C2
Adder
1.662
20714928UPF_X1-085
Solar/Wind Harmer
0.105
213508CON10-11
50/50
1.003
213518CONOW8-9
50/50
1.003
213514CONOW1-2
50/50
0.741
213516CONOW5-6
50/50
0.741
231918WEST 1
Adder
1.427
231917EM10
Adder
0.996
213497CHSTR7-9
Adder
1.06
213497CHSTR7-9
Adder
1.06
233930AB2-032 GEN
Solar/Wind Harmer
0.339
233915AB1-141 GEN
Solar/Wind Harmer
0.402
232422X3-066 FULL
Solar/Wind Harmer
0.099
234012AE2-112_GEN
Solar/Wind Harmer
0.91
213958STHWK5-6
Adder
0.976
232910NRG_G1
Adder
3.201
233964AF2-378 GEN
Solar/Wind Harmer
0.046
232426Y1-080 FULL
Solar/Wind Harmer
0.069
970277AG2-181 GEN
Solar/Wind Harmer
1.817
965821AG1-450 GEN
Solar/Wind Harmer
1.884
232919VN10
Adder
1.013
233954AC2-188 GEN
Solar/Wind Harmer
0.404
233950AC2-186 GEN
Solar/Wind Harmer
0.202
232428Y3-058 C
Solar/Wind Harmer
0.299
971195AH1-057 GEN
Solar/Wind Harmer
0.391
233998TM1NIN_3.36
Solar/Wind Harmer
0.453
232404W1-003 C
Solar/Wind Harmer
0.358
232917OH NUG6
Adder
3.139
232915OH NUG4
Adder
3.132
232434Z2-077 GEN
Solar/Wind Harmer
0.089
972177AH1-672 GEN
Solar/Wind Harmer
4.749
213560DLW11-12
Adder
0.898
232900DEMECSMY
Adder
3.212
232901NORTHST
Adder
2.86
233972AC1-094 C
Solar/Wind Harmer
0.226
219258KINSLEYDEP C
Solar/Wind Harmer
0.098
219904AC1-010 C
Solar/Wind Harmer
0.114
219907AC1-030 C
Solar/Wind Harmer
0.041
228351V2-046C
Solar/Wind Harmer
0.596
230434AG1-499 GEN
Solar/Wind Harmer
0.172
970997AG2-616 GEN
Solar/Wind Harmer
2.817
945431AF1-208 GEN
Solar/Wind Harmer
2.525
230511AF1-262
Solar/Wind Harmer
0.054
228728W1-130C
Solar/Wind Harmer
0.192
228206SHRMN CT
Adder
4.757
219304NAMERICA C
Solar/Wind Harmer
0.089
219222BRL12CT2
Adder
2.567
228732V1-021 C
Adder
0.054
218660EHAMPSOLAR C
Solar/Wind Harmer
0.05
219287REEVESEAST C
Solar/Wind Harmer
0.382
219686LUMSOLAR_N C
Solar/Wind Harmer
0.058
214194N WALES4
Adder
0.241
213611FALLS1-3
Adder
0.999
20720728JCB_W1-129
Solar/Wind Harmer
0.079
207522AF2-254 C
Solar/Wind Harmer
0.377
207487AE2-000G4
Solar/Wind Harmer
8.125
207445AB1-138_GEN
Solar/Wind Harmer
0.148
20628028LAKEHURS
Adder
0.48
963711AG1-223 GEN
Solar/Wind Harmer
0.373
20714828MDF_W3-079
Solar/Wind Harmer
0.077
219680HOPEWELLV C1
Solar/Wind Harmer
0.019
207454AA2-184 E
Solar/Wind Harmer
0.247
20715228NPK_W1-113
Solar/Wind Harmer
0.106
217197RE CRAN C
Solar/Wind Harmer
0.133
20742028HF_AC1-207
Solar/Wind Harmer
0.192
20635828PARLN1&2
Adder
1.773
20635028RRCT1&2
Adder
2.765
20635128RRCT3&4
Adder
2.669
218428ETC SOLAR C
Solar/Wind Harmer
0.008
217213AMBOY SO C
Solar/Wind Harmer
0.03
208909MACR G3
Adder
31.429
223401AF1-299 GEN
Solar/Wind Helper
0.284
213515CONOW3-4
50/50
0.741
213515CONOW3-4
50/50
0.741
213514CONOW1-2
50/50
0.555
213516CONOW5-6
50/50
0.555
233935AB2-179 C
Solar/Wind Harmer
1.148
231919CHRIST1
Adder
1.859
231920CHRIST2
Adder
1.818
971983AH1-536 GEN
Solar/Wind Harmer
3.035
232436AB1-176 C
Solar/Wind Harmer
0.091
233968AD2-076_GEN
Solar/Wind Harmer
2.624
970597AG2-380 GEN
Solar/Wind Harmer
1.648
231906DC3 NUG
Adder
5.458
231902DC CT7
Adder
4.363
231907DC10
Adder
1.363
213942SCHUYLKILL
Adder
1.288
213942SCHUYLKILL
Adder
0.985
213957STHWK3-4
Adder
0.976
213957STHWK3-4
Adder
0.976
232813VAUGHN
Adder
0.216
233955AB2-172 GEN
Solar/Wind Harmer
1.826
233923SMA
Solar/Wind Harmer
1.66
232912OH NUG1
Adder
3.153
232913OH NUG2
Adder
3.111
233990AG1-397 GEN
Solar/Wind Harmer
0.02
232432Z2-076 GEN
Solar/Wind Harmer
0.047
232920IR10
Adder
1.12
234033AF1-007_GEN
Solar/Wind Harmer
8.279
232904IR4
Adder
28.625
213561DLWR9-10
Adder
1.175
213561DLWR9-10
Adder
0.898
233973AC2-185 C
Solar/Wind Harmer
1.233
219137THOSOLAR C
Solar/Wind Harmer
0.37
219914AD2-027 C
Solar/Wind Harmer
0.181
963401AG1-189 GEN
Solar/Wind Harmer
0.296
963391AG1-188 GEN
Solar/Wind Harmer
0.493
20628028LAKEHURS
Adder
0.243
219817TRENTONSOL C
Solar/Wind Harmer
0.28
20720628TIN_W1-124
Solar/Wind Harmer
0.246
20641628MLH_W1-032
Solar/Wind Harmer
0.072
20716928W4-060COL
Solar/Wind Harmer
0.172
924131AB2-057 GEN
Solar/Wind Harmer
0.248
218440SUMMTASSOC C
Solar/Wind Harmer
0.03
20673828FLE_V3-070
Solar/Wind Harmer
0.108
208835TUHI V3-051
Solar/Wind Helper
0.011
208835TUHI V3-051
Solar/Wind Helper
0.011
971011AG2-627 GEN
Solar/Wind Harmer
2.283
228309CCLP NUG
Adder
7.663
228309CCLP NUG
Adder
7.29
964001AG1-254 GEN
Solar/Wind Harmer
0.602
972141AH1-641 GEN
Solar/Wind Harmer
0.845
228260V4-054C
Solar/Wind Harmer
0.299
971535AH1-265 GEN
Solar/Wind Harmer
1.233
219272CLEANLIGHT C
Solar/Wind Harmer
0.053
970453AG2-297 GEN
Solar/Wind Harmer
0.788
219607WPEMNERT C
Solar/Wind Harmer
0.121
219224BRL12CT4
Adder
2.567
219688LUMSOLAR_S C
Solar/Wind Harmer
0.058
228754AB1-001 C
Solar/Wind Harmer
0.039
227927V4-067C
Solar/Wind Harmer
0.056
214067T20SOLAR
Solar/Wind Harmer
0.071
213611FALLS1-3
Adder
0.999
213611FALLS1-3
Adder
0.999
20717128DIX_Z2-102
Solar/Wind Harmer
0.347
20715728PEM_W1-119
Solar/Wind Harmer
0.14
20715828PEM_W1-120
Solar/Wind Harmer
0.14
971189AH1-054 GEN
Solar/Wind Harmer
0.304
970025AG2-016 GEN
Solar/Wind Harmer
0.728
207459AE1-142 C O1
Solar/Wind Harmer
0.27
219620RIDERU C
Solar/Wind Harmer
0.014
20714328BYD_X4-031
Solar/Wind Harmer
0.07
20714428HOW_X1-037
Solar/Wind Harmer
0.306
971521AH1-258 GEN
Solar/Wind Harmer
0.663
20720428HOL_W1-112
Solar/Wind Harmer
0.085
218455CINNBAY_CGEN
Adder
0.438
20635928PARLN3&4
Adder
1.773
20675528CPH_W2-050
Solar/Wind Harmer
0.112
218526CNTRALGAS2 C
Solar/Wind Harmer
0.088
218524CNTRALGAS1 C
Solar/Wind Harmer
0.088
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.016
G-007ALTFEXP_G-007A->PJM
CMTX
12.213
CBM NorthLTFEXP_CBM-N->PJM
CBM
15.754
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.82
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.554
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
30.964
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.597
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
3.864

Details for NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line l/o PECO_P4_PEACH245_SRT-A/* $ CHESCO $ PECO_P4_PEACH245 $ STBK


Base Case Flowgate

Area:PECO
Facility Description:
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line
Contingency Name:
PECO_P4_PEACH245_SRT-A/* $ CHESCO $ PECO_P4_PEACH245 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:130.99 %
Rating:578.0 MVA
Rating Type:B
MVA to Mitigate:757.12
MW Contribution:2.33
Bus #Bus NameTypeMW Contribution
213508CON10-11
50/50
1.011
213518CONOW8-9
50/50
1.011
213514CONOW1-2
50/50
0.747
213516CONOW5-6
50/50
0.747
231918WEST 1
Adder
1.45
231917EM10
Adder
1.012
213497CHSTR7-9
Adder
1.078
213515CONOW3-4
50/50
0.747
213515CONOW3-4
50/50
0.747
213514CONOW1-2
50/50
0.56
213516CONOW5-6
50/50
0.56
233935AB2-179 C
Solar/Wind Harmer
1.165
231919CHRIST1
Adder
1.889
231920CHRIST2
Adder
1.847
971983AH1-536 GEN
Solar/Wind Harmer
3.085
232436AB1-176 C
Solar/Wind Harmer
0.093
233968AD2-076_GEN
Solar/Wind Harmer
2.668
970597AG2-380 GEN
Solar/Wind Harmer
1.675
231906DC3 NUG
Adder
5.55
231902DC CT7
Adder
4.437
231907DC10
Adder
1.385
213942SCHUYLKILL
Adder
1.31
213942SCHUYLKILL
Adder
1.002
213957STHWK3-4
Adder
0.993
213957STHWK3-4
Adder
0.993
232813VAUGHN
Adder
0.219
233955AB2-172 GEN
Solar/Wind Harmer
1.858
233923SMA
Solar/Wind Harmer
1.69
232912OH NUG1
Adder
3.209
232913OH NUG2
Adder
3.167
233990AG1-397 GEN
Solar/Wind Harmer
0.02
232432Z2-076 GEN
Solar/Wind Harmer
0.048
232920IR10
Adder
1.14
234033AF1-007_GEN
Solar/Wind Harmer
8.427
232904IR4
Adder
29.139
213561DLWR9-10
Adder
1.197
213561DLWR9-10
Adder
0.915
233973AC2-185 C
Solar/Wind Harmer
1.255
219137THOSOLAR C
Solar/Wind Harmer
0.377
219914AD2-027 C
Solar/Wind Harmer
0.185
971011AG2-627 GEN
Solar/Wind Harmer
2.329
228309CCLP NUG
Adder
7.816
228309CCLP NUG
Adder
7.434
964001AG1-254 GEN
Solar/Wind Harmer
0.614
972141AH1-641 GEN
Solar/Wind Harmer
0.862
228260V4-054C
Solar/Wind Harmer
0.305
971535AH1-265 GEN
Solar/Wind Harmer
1.258
219272CLEANLIGHT C
Solar/Wind Harmer
0.054
970453AG2-297 GEN
Solar/Wind Harmer
0.804
219607WPEMNERT C
Solar/Wind Harmer
0.123
219224BRL12CT4
Adder
2.62
219688LUMSOLAR_S C
Solar/Wind Harmer
0.059
228754AB1-001 C
Solar/Wind Harmer
0.04
227927V4-067C
Solar/Wind Harmer
0.057
214067T20SOLAR
Solar/Wind Harmer
0.073
213611FALLS1-3
Adder
1.02
213611FALLS1-3
Adder
1.02
20717128DIX_Z2-102
Solar/Wind Harmer
0.354
20715728PEM_W1-119
Solar/Wind Harmer
0.143
20715828PEM_W1-120
Solar/Wind Harmer
0.143
971189AH1-054 GEN
Solar/Wind Harmer
0.311
970025AG2-016 GEN
Solar/Wind Harmer
0.745
207459AE1-142 C O1
Solar/Wind Harmer
0.276
219620RIDERU C
Solar/Wind Harmer
0.015
20714328BYD_X4-031
Solar/Wind Harmer
0.072
20714428HOW_X1-037
Solar/Wind Harmer
0.313
971521AH1-258 GEN
Solar/Wind Harmer
0.679
20720428HOL_W1-112
Solar/Wind Harmer
0.087
218455CINNBAY_CGEN
Adder
0.449
20635928PARLN3&4
Adder
1.817
20675528CPH_W2-050
Solar/Wind Harmer
0.115
218526CNTRALGAS2 C
Solar/Wind Harmer
0.09
218524CNTRALGAS1 C
Solar/Wind Harmer
0.09
213508CON10-11
50/50
1.011
213518CONOW8-9
50/50
1.011
213517CONOW7
50/50
0.747
213497CHSTR7-9
Adder
1.078
233982AB2-133 GEN
Solar/Wind Harmer
2.015
233918AB1-142 GEN
Solar/Wind Harmer
0.409
213958STHWK5-6
Adder
0.993
232417X3-008 C
Solar/Wind Harmer
0.743
960671AF2-358 GEN
Solar/Wind Harmer
6.596
232907VN8
Adder
11.009
233952AC2-187 GEN
Solar/Wind Harmer
0.411
233994AC2-023 GEN
Solar/Wind Harmer
0.982
233940AF2-379 C
Solar/Wind Harmer
0.068
233900O-025 C
Adder
0.429
234015AF2-250 C
Solar/Wind Harmer
0.044
233996TM1833_GEN
Solar/Wind Harmer
0.461
233997TMININ_4.2
Solar/Wind Harmer
0.461
232406W1-004 FULL
Solar/Wind Harmer
0.364
232914OH NUG3
Adder
3.209
232916OH NUG5
Adder
3.209
232921TASLEY2G
Adder
1.876
233990AG1-397 GEN
Solar/Wind Harmer
0.417
972073AH1-586 GEN
Solar/Wind Harmer
3.403
972133AH1-634 GEN
Solar/Wind Harmer
3.573
213560DLW11-12
Adder
0.915
233971AC1-093 C
Solar/Wind Harmer
0.273
970695AG2-447 GEN
Solar/Wind Harmer
1.245
213815MOSER1-3
Adder
1.102
228304LOGAN
Adder
6.716
219766PARADISE C
Solar/Wind Harmer
0.097
219912AD2-042 GEN
Solar/Wind Harmer
0.245
219623KINSLEYBEA C
Solar/Wind Harmer
0.131
219236SOUTHERNHQ C
Solar/Wind Harmer
0.02
230430AE1-229_GEN
Solar/Wind Harmer
2.634
219906AC1-017 C
Solar/Wind Harmer
0.066
230415AB2-049 C
Solar/Wind Harmer
0.056
971553AH1-274 GEN
Solar/Wind Harmer
0.712
228711V2-041C
Solar/Wind Harmer
0.176
228202CUMB CT
Adder
4.823
219610FLORENCE C
Solar/Wind Harmer
0.407
219348LDSOLAR C
Solar/Wind Harmer
0.176
219221BRL12CT1
Adder
2.62
219223BRL12CT3
Adder
2.62
219291REEVESSOUT C
Solar/Wind Harmer
0.018
972251AH1-710 GEN
Adder
13.877
228729W2-030 C
Solar/Wind Harmer
0.166
959561AF2-247 GEN
Solar/Wind Harmer
0.137
20716028EGP_W2-019
Solar/Wind Harmer
0.125
20720828JCB_W4-025
Solar/Wind Harmer
0.122
219727YARDVSOLFA C
Solar/Wind Harmer
0.247
20715028HAN_X4-015
Solar/Wind Harmer
0.08
20636028O CRK C1
Adder
1.864
219276PARKLANDSO C
Solar/Wind Harmer
0.123
971667AH1-334 GEN
Solar/Wind Harmer
0.719
20714528FRN_Y2-051
Solar/Wind Harmer
0.076
219918AC2-009 C
Solar/Wind Harmer
0.016
20716228APLW2-078
Solar/Wind Harmer
0.223
20720528MAN_W1-024
Solar/Wind Harmer
0.064
219612MATRIX C
Solar/Wind Harmer
0.047
218438BLK ROCK C
Solar/Wind Harmer
0.035
967451AG2-055 C O1
Solar/Wind Harmer
42.856
20635828PARLN1&2
Adder
0.823
20635928PARLN3&4
Adder
0.823
20635028RRCT1&2
Adder
2.878
20635128RRCT3&4
Adder
2.386
219908AB1-139 C
Solar/Wind Harmer
0.092
219919AE1-041 FULL
Solar/Wind Harmer
0.01
219249CENTRALDIV C
Solar/Wind Harmer
0.01
20673728F2S_V4-070
Solar/Wind Harmer
0.043
223402AF1-300 C
Solar/Wind Helper
0.27
213497CHSTR7-9
Adder
1.078
233930AB2-032 GEN
Solar/Wind Harmer
0.344
233915AB1-141 GEN
Solar/Wind Harmer
0.409
232422X3-066 FULL
Solar/Wind Harmer
0.101
234012AE2-112_GEN
Solar/Wind Harmer
0.926
213958STHWK5-6
Adder
0.993
232910NRG_G1
Adder
3.257
233964AF2-378 GEN
Solar/Wind Harmer
0.047
232426Y1-080 FULL
Solar/Wind Harmer
0.07
970277AG2-181 GEN
Solar/Wind Harmer
1.849
965821AG1-450 GEN
Solar/Wind Harmer
1.918
232919VN10
Adder
1.031
233954AC2-188 GEN
Solar/Wind Harmer
0.411
233950AC2-186 GEN
Solar/Wind Harmer
0.206
232428Y3-058 C
Solar/Wind Harmer
0.304
971195AH1-057 GEN
Solar/Wind Harmer
0.398
233998TM1NIN_3.36
Solar/Wind Harmer
0.461
232404W1-003 C
Solar/Wind Harmer
0.364
232917OH NUG6
Adder
3.195
232915OH NUG4
Adder
3.188
232434Z2-077 GEN
Solar/Wind Harmer
0.09
972177AH1-672 GEN
Solar/Wind Harmer
4.835
213560DLW11-12
Adder
0.915
232900DEMECSMY
Adder
3.27
232901NORTHST
Adder
2.913
233972AC1-094 C
Solar/Wind Harmer
0.23
219258KINSLEYDEP C
Solar/Wind Harmer
0.1
219904AC1-010 C
Solar/Wind Harmer
0.117
219907AC1-030 C
Solar/Wind Harmer
0.042
228351V2-046C
Solar/Wind Harmer
0.608
230434AG1-499 GEN
Solar/Wind Harmer
0.175
970997AG2-616 GEN
Solar/Wind Harmer
2.874
945431AF1-208 GEN
Solar/Wind Harmer
2.575
230511AF1-262
Solar/Wind Harmer
0.055
228728W1-130C
Solar/Wind Harmer
0.196
228206SHRMN CT
Adder
4.854
219304NAMERICA C
Solar/Wind Harmer
0.091
219222BRL12CT2
Adder
2.62
228732V1-021 C
Adder
0.055
218660EHAMPSOLAR C
Solar/Wind Harmer
0.051
219686LUMSOLAR_N C
Solar/Wind Harmer
0.059
219287REEVESEAST C
Solar/Wind Harmer
0.39
214194N WALES4
Adder
0.246
213611FALLS1-3
Adder
1.02
20720728JCB_W1-129
Solar/Wind Harmer
0.08
207522AF2-254 C
Solar/Wind Harmer
0.386
207487AE2-000G4
Solar/Wind Harmer
8.307
207445AB1-138_GEN
Solar/Wind Harmer
0.151
20628028LAKEHURS
Adder
0.491
963711AG1-223 GEN
Solar/Wind Harmer
0.381
20714828MDF_W3-079
Solar/Wind Harmer
0.079
219680HOPEWELLV C1
Solar/Wind Harmer
0.02
207454AA2-184 E
Solar/Wind Harmer
0.253
20715228NPK_W1-113
Solar/Wind Harmer
0.108
217197RE CRAN C
Solar/Wind Harmer
0.136
20742028HF_AC1-207
Solar/Wind Harmer
0.197
20635828PARLN1&2
Adder
1.817
20635028RRCT1&2
Adder
2.833
20635128RRCT3&4
Adder
2.735
218428ETC SOLAR C
Solar/Wind Harmer
0.009
217213AMBOY SO C
Solar/Wind Harmer
0.031
972275AH1-722 GEN
Adder
7.572
207528AF2-192 GEN
Solar/Wind Harmer
0.133
20673628F1S_V4-069
Solar/Wind Harmer
0.043
20675428EAM_W2-061
Solar/Wind Harmer
0.045
20676428JCR_X2-075
Solar/Wind Harmer
0.082
218449LINSOLAR C
Solar/Wind Harmer
0.239
208909MACR G3
Adder
32.41
223401AF1-299 GEN
Solar/Wind Helper
0.27
213589EDDYSTN4
Adder
31.553
213587EDDYSTN3
Adder
31.525
232416X2-083
Adder
0.191
233933AB2-153 GEN
Solar/Wind Harmer
0.464
233944AB2-135 GEN
Solar/Wind Harmer
2.13
234014AF1-036_GEN
Solar/Wind Harmer
1.089
231131BLOOM ENRGY
Adder
1.722
232424Y1-079 C
Solar/Wind Harmer
0.222
233984AB2-036 GEN
Solar/Wind Harmer
4.884
234041AC1-190 GEN
Solar/Wind Harmer
3.324
233987AB2-037 GEN
Solar/Wind Harmer
4.214
234036AF2-325 C
Solar/Wind Harmer
0.339
233946AB2-136 GEN
Solar/Wind Harmer
1.475
232926CRISFLD1
Adder
0.714
233901CHERRYDALE C
Solar/Wind Harmer
0.409
232408W1-005 C
Solar/Wind Harmer
0.364
232410W1-006 C
Solar/Wind Harmer
0.364
232918OH NUG7
Adder
3.188
232905CHERITON_25
Adder
0.892
971747AH1-380 GEN
Solar/Wind Harmer
1.301
972069AH1-584 GEN
Solar/Wind Harmer
3.252
972071AH1-585 GEN
Solar/Wind Harmer
3.252
231940T-011
Adder
0.271
970545AG2-347 GEN
Solar/Wind Harmer
23.583
232899W1-062
Adder
3.409
971149AH1-027 GEN
Solar/Wind Harmer
1.185
233939AC1-091 C
Solar/Wind Harmer
0.305
233970AC1-092 C
Solar/Wind Harmer
0.305
972233AH1-701 GEN
Adder
1.297
213815MOSER1-3
Adder
1.102
213815MOSER1-3
Adder
1.102
228304LOGAN
Adder
7.467
228307PCLP GT
Adder
3.712
219921AF1-264
Solar/Wind Harmer
0.044
228251CARLLS#4
Adder
0.187
219615MILLCREEK C
Solar/Wind Harmer
0.071
230433AD2-135 GEN
Solar/Wind Harmer
0.03
230407AD2-065 C
Solar/Wind Harmer
0.039
213535CROYDN11
Adder
3.017
230422AE1-104_GEN1
Solar/Wind Harmer
9.748
230425AE1-104_GEN2
Solar/Wind Harmer
9.748
219114HARTZY_C
Solar/Wind Harmer
0.229
20716428NHV_W2-082
Solar/Wind Harmer
0.478
207500AE2-000G1
Solar/Wind Harmer
8.307
207497AE2-000G2
Solar/Wind Harmer
8.307
207507AE2-000G3
Solar/Wind Harmer
8.307
20636128O CRK C2
Adder
1.7
20714928UPF_X1-085
Solar/Wind Harmer
0.108
963401AG1-189 GEN
Solar/Wind Harmer
0.303
963391AG1-188 GEN
Solar/Wind Harmer
0.504
20628028LAKEHURS
Adder
0.248
219817TRENTONSOL C
Solar/Wind Harmer
0.287
20720628TIN_W1-124
Solar/Wind Harmer
0.252
20641628MLH_W1-032
Solar/Wind Harmer
0.074
20716928W4-060COL
Solar/Wind Harmer
0.176
924131AB2-057 GEN
Solar/Wind Harmer
0.254
218440SUMMTASSOC C
Solar/Wind Harmer
0.031
20673828FLE_V3-070
Solar/Wind Harmer
0.111
218418LINDEN_G5
Adder
4.119
218419LINDEN_G6
Adder
4.119
972260AH1-715 GEN1
Adder
3.298
207442AE1-156 GEN
Solar/Wind Harmer
0.178
20676128MHD_W3-029
Solar/Wind Harmer
0.114
219036LINDEN_G7
Adder
3.972
219035LINDEN_G8
Adder
3.915
972261AH1-715 GEN2
Adder
3.802
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.016
G-007ALTFEXP_G-007A->PJM
CMTX
12.515
CBM NorthLTFEXP_CBM-N->PJM
CBM
16.193
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.822
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.562
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
31.768
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.597
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
3.874

Details for NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line l/o PECO_P1-2_5012_SRT-A


Base Case Flowgate

Area:PECO
Facility Description:
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line
Contingency Name:
PECO_P1-2_5012_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:122.76 %
Rating:578.0 MVA
Rating Type:B
MVA to Mitigate:709.53
MW Contribution:1.62
Bus #Bus NameTypeMW Contribution
213508CON10-11
50/50
1.01
213518CONOW8-9
50/50
1.01
213517CONOW7
50/50
0.746
213890PHLISCT3
50/50
0.935
213888PHLISCT1
50/50
0.934
213739LIBE_CT2
50/50
0.778
213497CHSTR7-9
Adder
1.074
233982AB2-133 GEN
Solar/Wind Harmer
0.002
233918AB1-142 GEN
Solar/Wind Harmer
0.106
213958STHWK5-6
Adder
0.989
232417X3-008 C
Solar/Wind Harmer
0
960671AF2-358 GEN
Solar/Wind Harmer
4.583
232907VN8
Adder
10.963
233952AC2-187 GEN
Solar/Wind Harmer
0
233994AC2-023 GEN
Solar/Wind Harmer
0.002
233940AF2-379 C
Solar/Wind Harmer
0
233900O-025 C
Adder
0.427
234015AF2-250 C
Solar/Wind Harmer
0
233996TM1833_GEN
Solar/Wind Harmer
0.001
233997TMININ_4.2
Solar/Wind Harmer
0.001
232406W1-004 FULL
Solar/Wind Harmer
0.234
232921TASLEY2G
Adder
1.868
232914OH NUG3
Adder
3.196
232916OH NUG5
Adder
3.196
233990AG1-397 GEN
Solar/Wind Harmer
0.493
972073AH1-586 GEN
Solar/Wind Harmer
3.388
972133AH1-634 GEN
Solar/Wind Harmer
1.323
213560DLW11-12
Adder
0.911
233971AC1-093 C
Solar/Wind Harmer
0.015
970695AG2-447 GEN
Solar/Wind Harmer
0.865
213815MOSER1-3
Adder
1.097
228304LOGAN
Adder
6.684
219766PARADISE C
Solar/Wind Harmer
0
219912AD2-042 GEN
Solar/Wind Harmer
0
219623KINSLEYBEA C
Solar/Wind Harmer
0
230430AE1-229_GEN
Solar/Wind Harmer
0.005
219906AC1-017 C
Solar/Wind Harmer
0
230415AB2-049 C
Solar/Wind Harmer
0
971553AH1-274 GEN
Solar/Wind Harmer
0.457
228711V2-041C
Solar/Wind Harmer
0
228202CUMB CT
Adder
4.799
219610FLORENCE C
Solar/Wind Harmer
0
219348LDSOLAR C
Solar/Wind Harmer
0
219221BRL12CT1
Adder
2.607
219223BRL12CT3
Adder
2.607
972251AH1-710 GEN
Adder
13.808
228729W2-030 C
Solar/Wind Harmer
0
20716028EGP_W2-019
Solar/Wind Harmer
0
20720828JCB_W4-025
Solar/Wind Harmer
0
219727YARDVSOLFA C
Solar/Wind Harmer
0
20715028HAN_X4-015
Solar/Wind Harmer
0
20636028O CRK C1
Adder
1.854
219276PARKLANDSO C
Solar/Wind Harmer
0
971667AH1-334 GEN
Solar/Wind Harmer
0.462
20714528FRN_Y2-051
Solar/Wind Harmer
0
20716228APLW2-078
Solar/Wind Harmer
0
20720528MAN_W1-024
Solar/Wind Harmer
0
219612MATRIX C
Solar/Wind Harmer
0
218438BLK ROCK C
Solar/Wind Harmer
0
967451AG2-055 C O1
Solar/Wind Harmer
60.853
20635828PARLN1&2
Adder
0.818
20635928PARLN3&4
Adder
0.818
20635028RRCT1&2
Adder
2.86
20635128RRCT3&4
Adder
2.371
219908AB1-139 C
Solar/Wind Harmer
0
20673728F2S_V4-070
Solar/Wind Harmer
0
223402AF1-300 C
Solar/Wind Helper
0.271
213508CON10-11
50/50
1.01
213518CONOW8-9
50/50
1.01
213514CONOW1-2
50/50
0.746
213516CONOW5-6
50/50
0.746
231918WEST 1
50/50
1.533
213889PHLISCT2
50/50
0.934
231917EM10
50/50
1.07
213738LIBE_CT1
50/50
0.778
213497CHSTR7-9
Adder
1.074
213497CHSTR7-9
Adder
1.074
233930AB2-032 GEN
Solar/Wind Harmer
0.394
233915AB1-141 GEN
Solar/Wind Harmer
0.106
232422X3-066 FULL
Solar/Wind Harmer
0.034
234012AE2-112_GEN
Solar/Wind Harmer
0.932
213958STHWK5-6
Adder
0.989
232910NRG_G1
Adder
3.243
233964AF2-378 GEN
Solar/Wind Harmer
0
232426Y1-080 FULL
Solar/Wind Harmer
0
970277AG2-181 GEN
Solar/Wind Harmer
0.214
965821AG1-450 GEN
Solar/Wind Harmer
1.909
232919VN10
Adder
1.027
233954AC2-188 GEN
Solar/Wind Harmer
0
233950AC2-186 GEN
Solar/Wind Harmer
0
232428Y3-058 C
Solar/Wind Harmer
0.001
971195AH1-057 GEN
Solar/Wind Harmer
0.226
233998TM1NIN_3.36
Solar/Wind Harmer
0.001
232404W1-003 C
Solar/Wind Harmer
0.234
232917OH NUG6
Adder
3.182
232915OH NUG4
Adder
3.174
232434Z2-077 GEN
Solar/Wind Harmer
0.015
972177AH1-672 GEN
Solar/Wind Harmer
3.649
213560DLW11-12
Adder
0.911
232900DEMECSMY
Adder
3.256
232901NORTHST
Adder
2.9
233972AC1-094 C
Solar/Wind Harmer
0.109
219258KINSLEYDEP C
Solar/Wind Harmer
0
219904AC1-010 C
Solar/Wind Harmer
0
219907AC1-030 C
Solar/Wind Harmer
0
228351V2-046C
Solar/Wind Harmer
0
230434AG1-499 GEN
Solar/Wind Harmer
0
970997AG2-616 GEN
Solar/Wind Harmer
2.151
945431AF1-208 GEN
Solar/Wind Harmer
1.788
230511AF1-262
Solar/Wind Harmer
0
228728W1-130C
Solar/Wind Harmer
0
228206SHRMN CT
Adder
4.83
219304NAMERICA C
Solar/Wind Harmer
0.027
219222BRL12CT2
Adder
2.607
228732V1-021 C
Adder
0.055
218660EHAMPSOLAR C
Solar/Wind Harmer
0
219686LUMSOLAR_N C
Solar/Wind Harmer
0
219287REEVESEAST C
Solar/Wind Harmer
0
214194N WALES4
Adder
0.245
213611FALLS1-3
Adder
1.014
20720728JCB_W1-129
Solar/Wind Harmer
0
207522AF2-254 C
Solar/Wind Harmer
0.248
207487AE2-000G4
Solar/Wind Harmer
3.316
207445AB1-138_GEN
Solar/Wind Harmer
0
20628028LAKEHURS
Adder
0.489
20714828MDF_W3-079
Solar/Wind Harmer
0.025
207454AA2-184 E
Solar/Wind Harmer
0
20715228NPK_W1-113
Solar/Wind Harmer
0
217197RE CRAN C
Solar/Wind Harmer
0
20742028HF_AC1-207
Solar/Wind Harmer
0
20635828PARLN1&2
Adder
1.806
20635028RRCT1&2
Adder
2.816
20635128RRCT3&4
Adder
2.718
217213AMBOY SO C
Solar/Wind Harmer
0
972275AH1-722 GEN
Adder
7.523
207528AF2-192 GEN
Solar/Wind Harmer
0
20673628F1S_V4-069
Solar/Wind Harmer
0
20675428EAM_W2-061
Solar/Wind Harmer
0
208909MACR G3
Adder
32.152
223401AF1-299 GEN
Solar/Wind Helper
0.271
213515CONOW3-4
50/50
0.746
213515CONOW3-4
50/50
0.746
213514CONOW1-2
50/50
0.56
213516CONOW5-6
50/50
0.56
213893PHLISST1
50/50
1.345
231916EM3
50/50
0.419
231919CHRIST1
50/50
1.997
231920CHRIST2
50/50
1.953
231901EM4
50/50
0.843
213740LIBE_ST1
50/50
1.071
231505HR4
50/50
0.884
233935AB2-179 C
Solar/Wind Harmer
0.64
971983AH1-536 GEN
Solar/Wind Harmer
0.727
232436AB1-176 C
Solar/Wind Harmer
0
233968AD2-076_GEN
Solar/Wind Harmer
0.932
970597AG2-380 GEN
Solar/Wind Harmer
1.669
231906DC3 NUG
Adder
5.528
231902DC CT7
Adder
4.419
231907DC10
Adder
1.38
213942SCHUYLKILL
Adder
1.305
213942SCHUYLKILL
Adder
0.998
213957STHWK3-4
Adder
0.989
213957STHWK3-4
Adder
0.989
232813VAUGHN
Adder
0.218
233955AB2-172 GEN
Solar/Wind Harmer
0.001
233923SMA
Solar/Wind Harmer
0.002
232912OH NUG1
Adder
3.196
232913OH NUG2
Adder
3.153
233990AG1-397 GEN
Solar/Wind Harmer
-0.058
232432Z2-076 GEN
Solar/Wind Harmer
0.005
232920IR10
Adder
1.135
234033AF1-007_GEN
Solar/Wind Harmer
0
232904IR4
Adder
29.014
213561DLWR9-10
Adder
1.191
213561DLWR9-10
Adder
0.911
233973AC2-185 C
Solar/Wind Harmer
0.001
219914AD2-027 C
Solar/Wind Harmer
0
971011AG2-627 GEN
Solar/Wind Harmer
1.617
228309CCLP NUG
Adder
7.778
228309CCLP NUG
Adder
7.399
964001AG1-254 GEN
Solar/Wind Harmer
0.117
972141AH1-641 GEN
Solar/Wind Harmer
0.998
228260V4-054C
Solar/Wind Harmer
0
971535AH1-265 GEN
Solar/Wind Harmer
0.809
219272CLEANLIGHT C
Solar/Wind Harmer
0
970453AG2-297 GEN
Solar/Wind Harmer
0.739
219607WPEMNERT C
Solar/Wind Harmer
0
219224BRL12CT4
Adder
2.607
219688LUMSOLAR_S C
Solar/Wind Harmer
0
228754AB1-001 C
Solar/Wind Harmer
0
227927V4-067C
Solar/Wind Harmer
0
214067T20SOLAR
Solar/Wind Harmer
0
213611FALLS1-3
Adder
1.014
213611FALLS1-3
Adder
1.014
20717128DIX_Z2-102
Solar/Wind Harmer
0
20715728PEM_W1-119
Solar/Wind Harmer
0
20715828PEM_W1-120
Solar/Wind Harmer
0
971189AH1-054 GEN
Solar/Wind Harmer
0.2
970025AG2-016 GEN
Solar/Wind Harmer
0.479
207459AE1-142 C O1
Solar/Wind Harmer
0
20714328BYD_X4-031
Solar/Wind Harmer
0.038
20714428HOW_X1-037
Solar/Wind Harmer
0
971521AH1-258 GEN
Solar/Wind Harmer
0.436
20720428HOL_W1-112
Solar/Wind Harmer
0
218455CINNBAY_CGEN
Adder
0.446
20635928PARLN3&4
Adder
1.806
218526CNTRALGAS2 C
Solar/Wind Harmer
0.186
218524CNTRALGAS1 C
Solar/Wind Harmer
0.184
231909HR2
50/50
0.609
231908HR1
50/50
0.606
231910HR3
50/50
0.606
213589EDDYSTN4
Adder
31.437
213587EDDYSTN3
Adder
31.41
232416X2-083
Adder
0.19
233933AB2-153 GEN
Solar/Wind Harmer
0.001
233944AB2-135 GEN
Solar/Wind Harmer
0.002
234014AF1-036_GEN
Solar/Wind Harmer
0.932
231131BLOOM ENRGY
Adder
1.715
232424Y1-079 C
Solar/Wind Harmer
0
233984AB2-036 GEN
Solar/Wind Harmer
2.839
234041AC1-190 GEN
Solar/Wind Harmer
2.694
233987AB2-037 GEN
Solar/Wind Harmer
0.004
234036AF2-325 C
Solar/Wind Harmer
0
233946AB2-136 GEN
Solar/Wind Harmer
0.001
232926CRISFLD1
Adder
0.711
233901CHERRYDALE C
Solar/Wind Harmer
0
232408W1-005 C
Solar/Wind Harmer
0.234
232410W1-006 C
Solar/Wind Harmer
0.234
232905CHERITON_25
Adder
0.888
232918OH NUG7
Adder
3.174
971747AH1-380 GEN
Solar/Wind Harmer
0.904
972069AH1-584 GEN
Solar/Wind Harmer
2.259
972071AH1-585 GEN
Solar/Wind Harmer
2.259
231940T-011
Adder
0.269
970545AG2-347 GEN
Solar/Wind Harmer
9.059
232899W1-062
Adder
3.394
971149AH1-027 GEN
Solar/Wind Harmer
1.089
233939AC1-091 C
Solar/Wind Harmer
0.001
233970AC1-092 C
Solar/Wind Harmer
0.001
972233AH1-701 GEN
Adder
1.291
213815MOSER1-3
Adder
1.097
213815MOSER1-3
Adder
1.097
228304LOGAN
Adder
7.432
228307PCLP GT
Adder
3.695
219921AF1-264
Solar/Wind Harmer
0
228251CARLLS#4
Adder
0.186
219615MILLCREEK C
Solar/Wind Harmer
0
230407AD2-065 C
Solar/Wind Harmer
0
213535CROYDN11
Adder
3.002
230422AE1-104_GEN1
Solar/Wind Harmer
3.894
230425AE1-104_GEN2
Solar/Wind Harmer
3.894
219114HARTZY_C
Solar/Wind Harmer
0
20716428NHV_W2-082
Solar/Wind Harmer
0
207500AE2-000G1
Solar/Wind Harmer
3.316
207497AE2-000G2
Solar/Wind Harmer
3.316
207507AE2-000G3
Solar/Wind Harmer
3.316
20636128O CRK C2
Adder
1.69
20714928UPF_X1-085
Solar/Wind Harmer
0
20628028LAKEHURS
Adder
0.247
20720628TIN_W1-124
Solar/Wind Harmer
0
20716928W4-060COL
Solar/Wind Harmer
0
218440SUMMTASSOC C
Solar/Wind Harmer
0
20673828FLE_V3-070
Solar/Wind Harmer
0
218418LINDEN_G5
Adder
4.092
218419LINDEN_G6
Adder
4.092
972260AH1-715 GEN1
Adder
3.277
207442AE1-156 GEN
Solar/Wind Harmer
0.014
20676128MHD_W3-029
Solar/Wind Harmer
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.034
G-007ALTFEXP_G-007A->PJM
CMTX
12.437
CBM NorthLTFEXP_CBM-N->PJM
CBM
16.035
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.84
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.618
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
31.56
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.609
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
3.958

Details for PCHBTM1N-CHAN 500.0 kV Ckt 1 line l/o PJM_500_BG_P4_5_CNSTN_C_SRT-A


Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1N-CHAN 500.0 kV Ckt 1 line
Contingency Name:
PJM_500_BG_P4_5_CNSTN_C_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:149.71 %
Rating:3486.0 MVA
Rating Type:B
MVA to Mitigate:5219.0
MW Contribution:10.9
Bus #Bus NameTypeMW Contribution
200192DELTA CT1
50/50
3.848
200194DELTA CT3
50/50
3.848
200204Y1-065-CTG1
50/50
7.737
200054ROCKSP 3
50/50
4.936
233998TM1NIN_3.36
Solar/Wind Harmer
2.396
232404W1-003 C
Solar/Wind Harmer
1.894
232917OH NUG6
Adder
16.63
232915OH NUG4
Adder
16.593
232428Y3-058 C
Solar/Wind Harmer
1.578
232434Z2-077 GEN
Solar/Wind Harmer
0.473
971195AH1-057 GEN
Solar/Wind Harmer
2.07
232919VN10
Adder
5.306
232901NORTHST
Adder
15.73
965821AG1-450 GEN
Solar/Wind Harmer
9.841
232426Y1-080 FULL
Solar/Wind Harmer
0.361
970277AG2-181 GEN
Solar/Wind Harmer
9.478
200200DELTA2 CT1
50/50
6.886
200193DELTA CT2
50/50
3.848
200203Y1-065-STG
50/50
13.417
200055ROCKSP 4
50/50
4.832
232907VN8
Adder
56.816
233996TM1833_GEN
Solar/Wind Harmer
2.396
233997TMININ_4.2
Solar/Wind Harmer
2.396
232406W1-004 FULL
Solar/Wind Harmer
1.894
232914OH NUG3
Adder
16.704
232916OH NUG5
Adder
16.704
232921TASLEY2G
Adder
9.763
233940AF2-379 C
Solar/Wind Harmer
0.353
972073AH1-586 GEN
Solar/Wind Harmer
17.724
233900O-025 C
Adder
2.227
200035PCHBTM 3
50/50
41.108
200201DELTA2 CT2
50/50
6.886
200034PCHBTM 2
50/50
40.065
200205Y1-065-CTG2
50/50
7.737
233987AB2-037 GEN
Solar/Wind Harmer
21.599
232926CRISFLD1
Adder
3.712
233901CHERRYDALE C
Solar/Wind Harmer
2.129
232408W1-005 C
Solar/Wind Harmer
1.894
232410W1-006 C
Solar/Wind Harmer
1.894
232918OH NUG7
Adder
16.593
232905CHERITON_25
Adder
4.64
972069AH1-584 GEN
Solar/Wind Harmer
16.937
972071AH1-585 GEN
Solar/Wind Harmer
16.937
971747AH1-380 GEN
Solar/Wind Harmer
6.775
970545AG2-347 GEN
Solar/Wind Harmer
123.721
231940T-011
Adder
1.41
971149AH1-027 GEN
Solar/Wind Harmer
6.397
233946AB2-136 GEN
Solar/Wind Harmer
7.542
234036AF2-325 C
Solar/Wind Harmer
1.732
234041AC1-190 GEN
Solar/Wind Harmer
16.916
233939AC1-091 C
Solar/Wind Harmer
1.658
233970AC1-092 C
Solar/Wind Harmer
1.658
232899W1-062
Adder
18.141
233984AB2-036 GEN
Solar/Wind Harmer
23.372
232424Y1-079 C
Solar/Wind Harmer
1.055
234014AF1-036_GEN
Solar/Wind Harmer
5.057
231131BLOOM ENRGY
Adder
8.121
233944AB2-135 GEN
Solar/Wind Harmer
9.752
233933AB2-153 GEN
Solar/Wind Harmer
2.094
232416X2-083
Adder
0.822
228251CARLLS#4
Adder
0.908
230433AD2-135 GEN
Solar/Wind Harmer
0.144
230422AE1-104_GEN1
Solar/Wind Harmer
48.016
230425AE1-104_GEN2
Solar/Wind Harmer
48.016
228307PCLP GT
Adder
17.143
228304LOGAN
Adder
34.151
213589EDDYSTN4
Adder
112.515
213587EDDYSTN3
Adder
112.468
230407AD2-065 C
Solar/Wind Harmer
0.186
972233AH1-701 GEN
Adder
5.892
219921AF1-264
Solar/Wind Harmer
0.196
219615MILLCREEK C
Solar/Wind Harmer
0.311
213815MOSER1-3
Adder
4.564
213815MOSER1-3
Adder
4.564
213535CROYDN11
Adder
13.155
20716428NHV_W2-082
Solar/Wind Harmer
2.192
207500AE2-000G1
Solar/Wind Harmer
38.522
207497AE2-000G2
Solar/Wind Harmer
38.522
207507AE2-000G3
Solar/Wind Harmer
38.522
20636128O CRK C2
Adder
7.881
200202DELTA2 ST
50/50
11.685
200195DELTA ST
50/50
5.946
200052ROCKSP 1
50/50
4.887
200053ROCKSP 2
50/50
4.782
233923SMA
Solar/Wind Harmer
8.784
232912OH NUG1
Adder
16.704
232913OH NUG2
Adder
16.481
234033AF1-007_GEN
Solar/Wind Harmer
44.212
233990AG1-397 GEN
Solar/Wind Harmer
0.104
232904IR4
Adder
152.87
232432Z2-076 GEN
Solar/Wind Harmer
0.25
232920IR10
Adder
5.975
233955AB2-172 GEN
Solar/Wind Harmer
9.446
233973AC2-185 C
Solar/Wind Harmer
6.821
232813VAUGHN
Adder
1.107
233968AD2-076_GEN
Solar/Wind Harmer
12.391
970597AG2-380 GEN
Solar/Wind Harmer
7.781
232436AB1-176 C
Solar/Wind Harmer
0.428
231906DC3 NUG
Adder
26.102
231902DC CT7
Adder
20.867
231907DC10
Adder
6.516
971983AH1-536 GEN
Solar/Wind Harmer
13.924
233935AB2-179 C
Solar/Wind Harmer
4.553
231919CHRIST1
Adder
7.819
231920CHRIST2
Adder
7.646
970453AG2-297 GEN
Solar/Wind Harmer
4.022
228260V4-054C
Solar/Wind Harmer
1.477
228309CCLP NUG
Adder
37.117
228309CCLP NUG
Adder
35.307
972141AH1-641 GEN
Solar/Wind Harmer
4.121
964001AG1-254 GEN
Solar/Wind Harmer
2.908
971011AG2-627 GEN
Solar/Wind Harmer
10.9
971535AH1-265 GEN
Solar/Wind Harmer
6.031
227927V4-067C
Solar/Wind Harmer
0.279
228754AB1-001 C
Solar/Wind Harmer
0.196
219137THOSOLAR C
Solar/Wind Harmer
1.665
213942SCHUYLKILL
Adder
4.853
213942SCHUYLKILL
Adder
3.711
213957STHWK3-4
Adder
3.703
213957STHWK3-4
Adder
3.703
219272CLEANLIGHT C
Solar/Wind Harmer
0.246
219914AD2-027 C
Solar/Wind Harmer
0.806
219688LUMSOLAR_S C
Solar/Wind Harmer
0.271
213561DLWR9-10
Adder
4.718
213561DLWR9-10
Adder
3.608
219607WPEMNERT C
Solar/Wind Harmer
0.54
219224BRL12CT4
Adder
11.496
214067T20SOLAR
Solar/Wind Harmer
0.316
213611FALLS1-3
Adder
4.417
213611FALLS1-3
Adder
4.417
20717128DIX_Z2-102
Solar/Wind Harmer
1.624
20715728PEM_W1-119
Solar/Wind Harmer
0.656
20715828PEM_W1-120
Solar/Wind Harmer
0.656
970025AG2-016 GEN
Solar/Wind Harmer
3.437
971189AH1-054 GEN
Solar/Wind Harmer
1.429
207459AE1-142 C O1
Solar/Wind Harmer
1.268
219620RIDERU C
Solar/Wind Harmer
0.064
20714328BYD_X4-031
Solar/Wind Harmer
0.324
20714428HOW_X1-037
Solar/Wind Harmer
1.414
971521AH1-258 GEN
Solar/Wind Harmer
3.039
20720428HOL_W1-112
Solar/Wind Harmer
0.387
20635928PARLN3&4
Adder
8.012
218455CINNBAY_CGEN
Adder
1.96
218526CNTRALGAS2 C
Solar/Wind Harmer
0.393
218524CNTRALGAS1 C
Solar/Wind Harmer
0.391
963401AG1-189 GEN
Solar/Wind Harmer
1.399
963391AG1-188 GEN
Solar/Wind Harmer
2.325
20714928UPF_X1-085
Solar/Wind Harmer
0.49
219114HARTZY_C
Solar/Wind Harmer
1.002
20628028LAKEHURS
Adder
1.137
219817TRENTONSOL C
Solar/Wind Harmer
1.268
20641628MLH_W1-032
Solar/Wind Harmer
0.334
20720628TIN_W1-124
Solar/Wind Harmer
1.134
20716928W4-060COL
Solar/Wind Harmer
0.785
924131AB2-057 GEN
Solar/Wind Harmer
1.109
218440SUMMTASSOC C
Solar/Wind Harmer
0.135
218418LINDEN_G5
Adder
17.783
218419LINDEN_G6
Adder
17.783
972260AH1-715 GEN1
Adder
14.24
20673828FLE_V3-070
Solar/Wind Harmer
0.472
219036LINDEN_G7
Adder
17.045
219035LINDEN_G8
Adder
16.802
972261AH1-715 GEN2
Adder
16.317
207442AE1-156 GEN
Solar/Wind Harmer
0.757
20676128MHD_W3-029
Solar/Wind Harmer
0.486
217081WEATEXAS C
Solar/Wind Harmer
0.087
217202FBANKSOLAR C
Solar/Wind Harmer
0.074
217201HACKENSOLA C
Solar/Wind Harmer
0.073
972237AH1-703 GEN
Adder
10.011
217206BARNGR HS C
Solar/Wind Harmer
0.03
217086KRNY_131
Adder
9.208
217083KRNY_132
Adder
9.13
20671828STAW2-080
Solar/Wind Harmer
0.103
217204WCALDSOLAR C
Solar/Wind Harmer
0.072
20674528F3S_W2-016
Solar/Wind Harmer
1.358
20676228FRD_X1-012
Solar/Wind Harmer
0.524
207471AF2-354 C
Solar/Wind Harmer
0.433
20674928WA_W3-044
Solar/Wind Harmer
0.408
964851AG1-348 GEN
Solar/Wind Harmer
1.466
20634528N27_Y2-018
Solar/Wind Harmer
0.224
20465127PORT CT
Adder
3.203
20674128FR_U2-059
Solar/Wind Harmer
0.147
966111AG1-480 GEN
Solar/Wind Harmer
0.068
966111AG1-480 GEN
Solar/Wind Harmer
2.611
211065PSPA IPP
Solar/Wind Harmer
0.315
211065PSPA IPP
Solar/Wind Harmer
0.315
209029WAYMART-WD
Solar/Wind Harmer
1.79
209009PEIP 2
Adder
4.862
209010PEIP 1
Adder
2.203
209010PEIP 1
Adder
0.323
208972BECR K09
Solar/Wind Harmer
0.618
238175AF1-290_GEN
Solar/Wind Helper
0.124
238169AE2-226 GEN1
Solar/Wind Helper
0.572
238170AE2-226 GEN2
Solar/Wind Helper
0.572
315651AD1-115 GEN
Solar/Wind Helper
0.784
316447AC1-158 HLD
Solar/Wind Helper
2.85
966001AG1-469 GEN
Solar/Wind Helper
0.246
235020AA1-095 C
Solar/Wind Helper
0.043
23777901MDS_W4-102
Solar/Wind Helper
0.143
316468AD1-105 GEN
Solar/Wind Helper
1.135
316077AC2-138 C
Solar/Wind Helper
0.214
966871AG1-558 GEN
Solar/Wind Helper
0.306
316487AF1-042 GEN
Solar/Wind Helper
0.229
316075AC2-137 C
Solar/Wind Helper
0.345
3143526WINTERP
Solar/Wind Helper
1.176
3142946ENON
Solar/Wind Helper
0.023
316240AF1-291 C
Solar/Wind Helper
0.303
316033AB2-134 GEN
Solar/Wind Helper
0.774
315697AD1-025 GEN
Solar/Wind Helper
2.571
316236AE1-162_GEN
Solar/Wind Helper
0.302
316036AC1-147 C
Solar/Wind Helper
0.341
3142956BIRDNECK
Solar/Wind Helper
0.151
316316AC1-027 C
Solar/Wind Helper
0.354
316185AD1-033 GEN
Solar/Wind Helper
1.054
3145506HICKORY
Solar/Wind Helper
0.896
3145506HICKORY
Solar/Wind Helper
0.537
3145506HICKORY
Solar/Wind Helper
0.134
316339AD2-160 GEN
Solar/Wind Helper
0.852
316018AA1-139 ULT2
Solar/Wind Helper
0.962
316017AA1-139 ULT1
Solar/Wind Helper
1.023
3137176SLIGO L2192
Solar/Wind Helper
0.89
3130086AYDLETT
Solar/Wind Helper
0.895
3146386ELIZ CT
Solar/Wind Helper
0.223
316431W1029_GEN1
Solar/Wind Helper
0.902
316433W1029_GEN2
Solar/Wind Helper
0.902
3146516WINFALL
Solar/Wind Helper
0.223
3146516WINFALL
Solar/Wind Helper
0.223
3146516WINFALL
Solar/Wind Helper
0.223
237034AC2-136 C
Solar/Wind Helper
0.184
3146626S HERTFORD
Solar/Wind Helper
0.223
3146626S HERTFORD
Solar/Wind Helper
0.223
3144356SAPONY
Solar/Wind Helper
0.4
972133AH1-634 GEN
Solar/Wind Harmer
18.746
233990AG1-397 GEN
Solar/Wind Harmer
2.169
234015AF2-250 C
Solar/Wind Harmer
0.228
233994AC2-023 GEN
Solar/Wind Harmer
5.083
960671AF2-358 GEN
Solar/Wind Harmer
33.854
232417X3-008 C
Solar/Wind Harmer
3.779
233971AC1-093 C
Solar/Wind Harmer
1.481
970695AG2-447 GEN
Solar/Wind Harmer
6.763
233952AC2-187 GEN
Solar/Wind Harmer
2.123
233918AB1-142 GEN
Solar/Wind Harmer
1.844
233982AB2-133 GEN
Solar/Wind Harmer
9.053
972251AH1-710 GEN
Adder
80.123
228202CUMB CT
Adder
23.982
228711V2-041C
Solar/Wind Harmer
0.871
971553AH1-274 GEN
Solar/Wind Harmer
3.497
230430AE1-229_GEN
Solar/Wind Harmer
12.59
230415AB2-049 C
Solar/Wind Harmer
0.269
213497CHSTR7-9
Adder
3.862
228304LOGAN
Adder
30.715
228729W2-030 C
Solar/Wind Harmer
0.814
219623KINSLEYBEA C
Solar/Wind Harmer
0.583
213958STHWK5-6
Adder
3.703
219766PARADISE C
Solar/Wind Harmer
0.426
219291REEVESSOUT C
Solar/Wind Harmer
0.081
219912AD2-042 GEN
Solar/Wind Harmer
1.068
213560DLW11-12
Adder
3.608
219236SOUTHERNHQ C
Solar/Wind Harmer
0.089
219906AC1-017 C
Solar/Wind Harmer
0.291
219610FLORENCE C
Solar/Wind Harmer
1.784
219348LDSOLAR C
Solar/Wind Harmer
0.771
219221BRL12CT1
Adder
11.496
219223BRL12CT3
Adder
11.496
213815MOSER1-3
Adder
4.564
959561AF2-247 GEN
Solar/Wind Harmer
0.603
20716028EGP_W2-019
Solar/Wind Harmer
0.573
20720828JCB_W4-025
Solar/Wind Harmer
0.559
20715028HAN_X4-015
Solar/Wind Harmer
0.368
20636028O CRK C1
Adder
8.644
971667AH1-334 GEN
Solar/Wind Harmer
3.297
219727YARDVSOLFA C
Solar/Wind Harmer
1.084
20714528FRN_Y2-051
Solar/Wind Harmer
0.346
219276PARKLANDSO C
Solar/Wind Harmer
0.538
219918AC2-009 C
Solar/Wind Harmer
0.07
20716228APLW2-078
Solar/Wind Harmer
1.003
20720528MAN_W1-024
Solar/Wind Harmer
0.288
967451AG2-055 C O1
Solar/Wind Harmer
192.98
219612MATRIX C
Solar/Wind Harmer
0.204
218438BLK ROCK C
Solar/Wind Harmer
0.151
20635828PARLN1&2
Adder
3.629
20635928PARLN3&4
Adder
3.629
20635028RRCT1&2
Adder
12.638
20635128RRCT3&4
Adder
10.477
219908AB1-139 C
Solar/Wind Harmer
0.399
219919AE1-041 FULL
Solar/Wind Harmer
0.042
219249CENTRALDIV C
Solar/Wind Harmer
0.041
20673728F2S_V4-070
Solar/Wind Harmer
0.183
217211CAMDEN ST C
Solar/Wind Harmer
0.024
217186ESSEX_G9
Adder
15.809
217169METRODIV C
Solar/Wind Harmer
0.039
217194REDH C
Solar/Wind Harmer
0.486
20676728BRNX1-095
Solar/Wind Harmer
0.166
207510AF2-138 C
Solar/Wind Harmer
1.582
20674628WNG_W3-110
Solar/Wind Harmer
0.359
971007AG2-625 GEN
Solar/Wind Harmer
2.14
20466127PORT 5CT
Adder
21.343
20633028GILCT9
Adder
22.387
966181AG1-487 GEN
Solar/Wind Harmer
0.199
20465427SHAW CT
Adder
3.059
963071AG1-156 GEN
Solar/Wind Harmer
1.673
970095AG2-074 GEN
Solar/Wind Harmer
3.796
963161AG1-165 GEN
Solar/Wind Harmer
0.593
209025WIENIPP3
Adder
3.127
3141196NOKESVL
Solar/Wind Helper
0.957
316044AC1-158 PL1
Solar/Wind Helper
1.295
316450AC1-158 RIC
Solar/Wind Helper
0.345
316170AC1-121 GEN2
Solar/Wind Helper
0.356
3132273ORANGE
Solar/Wind Helper
0.046
3147666LOUISA
Solar/Wind Helper
0.53
238147AE2-230_GEN1
Solar/Wind Helper
0.395
238149AF1-291A_GEN
Solar/Wind Helper
0.113
966881AG1-559 GEN
Solar/Wind Helper
0.309
237061AD1-155 GEN
Solar/Wind Helper
0.043
3141906WESTMOR
Solar/Wind Helper
0.091
316473AC1-191 GEN
Solar/Wind Helper
1.387
316404AE1-155 C
Solar/Wind Helper
1.916
316484AD2-074 GEN
Solar/Wind Helper
0.438
316280AD1-041 GEN
Solar/Wind Helper
0.76
316156AD2-030 GEN
Solar/Wind Helper
0.341
3142946ENON
Solar/Wind Helper
0.075
316382AG1-145 C
Solar/Wind Helper
0.303
315839AE2-212 C
Solar/Wind Helper
0.302
316313AB2-026
Solar/Wind Helper
0.342
316258AE1-075 C
Solar/Wind Helper
0.308
316405AF2-144 C
Solar/Wind Helper
0.256
3145336SMITFLD
Solar/Wind Helper
0.09
315773AC2-141 GEN
Solar/Wind Helper
4.83
3144536CHRHLND
Solar/Wind Helper
0.034
3144873MCLAUGH
Solar/Wind Helper
0.006
3146456SLIGO L269
Solar/Wind Helper
0.224
316320Y1-086
Solar/Wind Helper
0.1
316435W1029_GEN3
Solar/Wind Helper
0.902
3146516WINFALL
Solar/Wind Helper
0.223
238221AF1-254 C O1
Solar/Wind Helper
0.219
3146626S HERTFORD
Solar/Wind Helper
0.223
3145273HOLLAND
Solar/Wind Helper
0.167
233964AF2-378 GEN
Solar/Wind Harmer
0.241
972177AH1-672 GEN
Solar/Wind Harmer
25.38
233972AC1-094 C
Solar/Wind Harmer
1.252
232900DEMECSMY
Adder
17.4
233954AC2-188 GEN
Solar/Wind Harmer
2.123
233950AC2-186 GEN
Solar/Wind Harmer
1.061
232910NRG_G1
Adder
16.205
234012AE2-112_GEN
Solar/Wind Harmer
4.299
232422X3-066 FULL
Solar/Wind Harmer
0.467
233930AB2-032 GEN
Solar/Wind Harmer
1.552
233915AB1-141 GEN
Solar/Wind Harmer
1.844
231918WEST 1
Adder
5.956
231917EM10
Adder
4.123
228206SHRMN CT
Adder
24.012
228732V1-021 C
Adder
0.272
945431AF1-208 GEN
Solar/Wind Harmer
12.406
970997AG2-616 GEN
Solar/Wind Harmer
13.737
228351V2-046C
Solar/Wind Harmer
2.879
230511AF1-262
Solar/Wind Harmer
0.261
228728W1-130C
Solar/Wind Harmer
0.942
213497CHSTR7-9
Adder
3.862
213497CHSTR7-9
Adder
3.862
230434AG1-499 GEN
Solar/Wind Harmer
0.82
219258KINSLEYDEP C
Solar/Wind Harmer
0.441
213958STHWK5-6
Adder
3.703
219904AC1-010 C
Solar/Wind Harmer
0.511
218660EHAMPSOLAR C
Solar/Wind Harmer
0.235
219686LUMSOLAR_N C
Solar/Wind Harmer
0.271
219287REEVESEAST C
Solar/Wind Harmer
1.8
213560DLW11-12
Adder
3.608
219907AC1-030 C
Solar/Wind Harmer
0.184
219304NAMERICA C
Solar/Wind Harmer
0.4
219222BRL12CT2
Adder
11.496
213611FALLS1-3
Adder
4.417
20720728JCB_W1-129
Solar/Wind Harmer
0.368
207522AF2-254 C
Solar/Wind Harmer
1.768
214194N WALES4
Adder
1.05
207487AE2-000G4
Solar/Wind Harmer
38.522
207445AB1-138_GEN
Solar/Wind Harmer
0.693
20628028LAKEHURS
Adder
2.25
963711AG1-223 GEN
Solar/Wind Harmer
1.734
20714828MDF_W3-079
Solar/Wind Harmer
0.358
219680HOPEWELLV C1
Solar/Wind Harmer
0.087
207454AA2-184 E
Solar/Wind Harmer
1.138
20715228NPK_W1-113
Solar/Wind Harmer
0.488
20742028HF_AC1-207
Solar/Wind Harmer
0.886
217197RE CRAN C
Solar/Wind Harmer
0.594
20635828PARLN1&2
Adder
8.012
20635028RRCT1&2
Adder
12.443
20635128RRCT3&4
Adder
12.011
218428ETC SOLAR C
Solar/Wind Harmer
0.038
217213AMBOY SO C
Solar/Wind Harmer
0.133
972275AH1-722 GEN
Adder
32.692
218449LINSOLAR C
Solar/Wind Harmer
1.025
207528AF2-192 GEN
Solar/Wind Harmer
0.563
20673628F1S_V4-069
Solar/Wind Harmer
0.183
20675428EAM_W2-061
Solar/Wind Harmer
0.192
20676428JCR_X2-075
Solar/Wind Harmer
0.346
217209CENTRL HS C
Solar/Wind Harmer
0.045
217121ECCF
Adder
0.429
217083KRNY_132
Adder
9.189
217208PARK ELE C
Solar/Wind Harmer
0.025
207439AE1-081 C O1
Solar/Wind Harmer
0.054
20674328GAR_V4-001
Solar/Wind Harmer
0.097
20675828AU_W4-064
Solar/Wind Harmer
0.152
971519AH1-257 GEN
Solar/Wind Harmer
2.092
207518AF1-320_GEN
Solar/Wind Harmer
2.976
207437AD2-070 GEN
Solar/Wind Harmer
0.243
20465127PORT CT
Adder
2.414
20671928W4-073
Solar/Wind Harmer
0.345
966181AG1-487 GEN
Solar/Wind Harmer
2.962
208909MACR G3
Adder
122.259
209010PEIP 1
Adder
0.4
961301AF2-421 GEN
Solar/Wind Harmer
0.593
963151AG1-164 GEN
Solar/Wind Harmer
0.593
209023WIENIPP1
Adder
6.394
209025WIENIPP3
Adder
3.192
316006AB2-029 C
Solar/Wind Helper
0.112
316045AC1-158 PL2
Solar/Wind Helper
4.145
316254AC1-120 GEN1
Solar/Wind Helper
1.069
3147666LOUISA
Solar/Wind Helper
0.921
316192AB2-158 GEN
Solar/Wind Helper
1.547
238148AE2-230_GEN2
Solar/Wind Helper
0.397
316337AD2-073 GEN
Solar/Wind Helper
0.345
964211AG1-282 GEN
Solar/Wind Helper
0.306
3141726DUNNSVL
Solar/Wind Helper
0.908
3142416OLDCHRC
Solar/Wind Helper
0.589
3142416OLDCHRC
Solar/Wind Helper
0.226
3138133OCRAN
Solar/Wind Helper
0.136
3143526WINTERP
Solar/Wind Helper
1.176
3141766HARMONY
Solar/Wind Helper
0.045
3143226MDLTHAN
Solar/Wind Helper
0.226
3142433PROV 92
Solar/Wind Helper
0.904
3142543TWELFTH
Solar/Wind Helper
0.022
316159AE1-175 C
Solar/Wind Helper
0.342
316458AB2-190 GEN2
Solar/Wind Helper
1.286
3145336SMITFLD
Solar/Wind Helper
0.898
316294AC1-161 GEN
Solar/Wind Helper
4.104
316381AD1-082 GEN
Solar/Wind Helper
1.161
316375AC2-012 GEN
Solar/Wind Helper
0.587
316336AC2-165 C
Solar/Wind Helper
1.208
316072AD1-144
Solar/Wind Helper
0.256
316388AE2-253 GEN
Solar/Wind Helper
0.852
3146456SLIGO L269
Solar/Wind Helper
0.224
316246AF1-032 C
Solar/Wind Helper
0.256
3146516WINFALL
Solar/Wind Helper
0.723
3146516WINFALL
Solar/Wind Helper
0.223
20675528CPH_W2-050
Solar/Wind Harmer
0.489
218404KENILWRTH C
Adder
1.302
217167KRNY_14
Adder
9.189
217086KRNY_131
Adder
9.111
217147KRNY_1212
Adder
8.74
217147KRNY_1212
Adder
8.584
217146KRNY_1234
Adder
8.564
217146KRNY_1234
Adder
8.506
966261AG1-495 GEN
Solar/Wind Harmer
1.648
20676328BVR_Y1-020
Solar/Wind Harmer
0.296
207511W3-106 GEN
Solar/Wind Harmer
0.583
207530AG1-191 GEN
Solar/Wind Harmer
1.214
20674828DL_W4-046
Solar/Wind Harmer
0.549
971009AG2-626 GEN
Solar/Wind Harmer
1.365
207408W3-077 C
Solar/Wind Harmer
0.414
20675728RH_W2-091
Solar/Wind Harmer
0.28
966421AG1-511 GEN
Solar/Wind Harmer
7.027
20675928HOL_W4-097
Solar/Wind Harmer
0.106
207484AF2-139 C O1
Solar/Wind Harmer
0.408
20675128HRM_W1-127
Solar/Wind Harmer
0.136
20462827N BANGR8
Adder
0.568
209116AE2-175 GEN
Solar/Wind Harmer
3.023
961261AF2-417 GEN
Solar/Wind Harmer
0.669
209026WIENIPP4
Adder
3.159
3138216PACIFIC
Solar/Wind Helper
0.041
316411AF1-147_GEN1
Solar/Wind Helper
0.817
316415AF1-147_GEN2
Solar/Wind Helper
0.817
3141426STAFORD
Solar/Wind Helper
0.051
316164AC1-076 GEN
Solar/Wind Helper
1.11
238152AF2-075_GEN
Solar/Wind Helper
0.565
23546401DTGZ2-030
Solar/Wind Helper
0.072
316223AC1-118
Solar/Wind Helper
0.347
3141813NORNECK
Solar/Wind Helper
0.227
316312AB1-027
Solar/Wind Helper
0.431
3141783LANCAST
Solar/Wind Helper
0.136
3141783LANCAST
Solar/Wind Helper
0.091
3138133OCRAN
Solar/Wind Helper
0.068
3141913WHIT STONE
Solar/Wind Helper
0.226
316233AE1-074 FULL
Solar/Wind Helper
0.346
316059AD1-063 C
Solar/Wind Helper
0.228
3143873LANEXA
Solar/Wind Helper
0.136
315662AE1-191 GEN
Solar/Wind Helper
1.216
315666AE1-190 GEN
Solar/Wind Helper
0.304
957601AF2-054 GEN
Solar/Wind Helper
0.303
3141873WAN 176
Solar/Wind Helper
0.045
957831AF2-077 GEN
Solar/Wind Helper
0.304
316132AB2-190 GEN1
Solar/Wind Helper
1.286
316369SG1_INVT
Solar/Wind Helper
1.082
3143316POE
Solar/Wind Helper
0.889
316349AD2-085 GEN
Solar/Wind Helper
1.024
319010AE1-072 C
Solar/Wind Helper
2.557
316305AF2-043 C
Solar/Wind Helper
0.301
313526AB2-022
Solar/Wind Helper
0.34
3146486SUNBURY
Solar/Wind Helper
0.223
3146486SUNBURY
Solar/Wind Helper
0.223
316321Z2-027
Solar/Wind Helper
0.34
3145176PASQUOTANK
Solar/Wind Helper
0.138
316315AB2-025 C
Solar/Wind Helper
0.339
HAMLETPJM->LTFIMP_HAMLET
CLTF
5.427
G-007ALTFEXP_G-007A->PJM
CMTX
54.959
CBM NorthLTFEXP_CBM-N->PJM
CBM
62.949
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
4.801
BlueGrassPJM->LTFIMP_BlueG
CLTF
14.952
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
135.356
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.242
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
22.436

Details for PCHBTM1N-CHAN 500.0 kV Ckt 1 line l/o BGE_P4_GRACETON_51_SRT-A


Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1N-CHAN 500.0 kV Ckt 1 line
Contingency Name:
BGE_P4_GRACETON_51_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:149.71 %
Rating:3486.0 MVA
Rating Type:B
MVA to Mitigate:5218.92
MW Contribution:10.9
Bus #Bus NameTypeMW Contribution
200202DELTA2 ST
50/50
11.685
200195DELTA ST
50/50
5.946
200052ROCKSP 1
50/50
4.887
200053ROCKSP 2
50/50
4.782
233923SMA
Solar/Wind Harmer
8.784
232912OH NUG1
Adder
16.704
232913OH NUG2
Adder
16.481
234033AF1-007_GEN
Solar/Wind Harmer
44.212
233990AG1-397 GEN
Solar/Wind Harmer
0.104
232904IR4
Adder
152.87
232432Z2-076 GEN
Solar/Wind Harmer
0.25
232920IR10
Adder
5.975
233955AB2-172 GEN
Solar/Wind Harmer
9.446
233973AC2-185 C
Solar/Wind Harmer
6.821
232813VAUGHN
Adder
1.107
233968AD2-076_GEN
Solar/Wind Harmer
12.391
970597AG2-380 GEN
Solar/Wind Harmer
7.781
232436AB1-176 C
Solar/Wind Harmer
0.428
231906DC3 NUG
Adder
26.102
231902DC CT7
Adder
20.867
231907DC10
Adder
6.516
971983AH1-536 GEN
Solar/Wind Harmer
13.924
233935AB2-179 C
Solar/Wind Harmer
4.553
231919CHRIST1
Adder
7.819
231920CHRIST2
Adder
7.646
970453AG2-297 GEN
Solar/Wind Harmer
4.022
228260V4-054C
Solar/Wind Harmer
1.477
228309CCLP NUG
Adder
37.117
228309CCLP NUG
Adder
35.307
972141AH1-641 GEN
Solar/Wind Harmer
4.121
964001AG1-254 GEN
Solar/Wind Harmer
2.908
971011AG2-627 GEN
Solar/Wind Harmer
10.9
971535AH1-265 GEN
Solar/Wind Harmer
6.031
227927V4-067C
Solar/Wind Harmer
0.279
228754AB1-001 C
Solar/Wind Harmer
0.196
219137THOSOLAR C
Solar/Wind Harmer
1.665
213942SCHUYLKILL
Adder
4.853
213942SCHUYLKILL
Adder
3.711
213957STHWK3-4
Adder
3.703
213957STHWK3-4
Adder
3.703
219272CLEANLIGHT C
Solar/Wind Harmer
0.246
219914AD2-027 C
Solar/Wind Harmer
0.806
219688LUMSOLAR_S C
Solar/Wind Harmer
0.271
213561DLWR9-10
Adder
4.718
213561DLWR9-10
Adder
3.608
219607WPEMNERT C
Solar/Wind Harmer
0.54
219224BRL12CT4
Adder
11.496
214067T20SOLAR
Solar/Wind Harmer
0.316
213611FALLS1-3
Adder
4.417
213611FALLS1-3
Adder
4.417
20717128DIX_Z2-102
Solar/Wind Harmer
1.624
20715728PEM_W1-119
Solar/Wind Harmer
0.656
20715828PEM_W1-120
Solar/Wind Harmer
0.656
970025AG2-016 GEN
Solar/Wind Harmer
3.437
971189AH1-054 GEN
Solar/Wind Harmer
1.429
207459AE1-142 C O1
Solar/Wind Harmer
1.268
219620RIDERU C
Solar/Wind Harmer
0.064
20714328BYD_X4-031
Solar/Wind Harmer
0.324
20714428HOW_X1-037
Solar/Wind Harmer
1.414
971521AH1-258 GEN
Solar/Wind Harmer
3.039
20720428HOL_W1-112
Solar/Wind Harmer
0.387
20635928PARLN3&4
Adder
8.012
218455CINNBAY_CGEN
Adder
1.96
218526CNTRALGAS2 C
Solar/Wind Harmer
0.393
218524CNTRALGAS1 C
Solar/Wind Harmer
0.391
20675528CPH_W2-050
Solar/Wind Harmer
0.489
218404KENILWRTH C
Adder
1.302
217167KRNY_14
Adder
9.189
217086KRNY_131
Adder
9.111
217147KRNY_1212
Adder
8.74
217147KRNY_1212
Adder
8.584
217146KRNY_1234
Adder
8.564
217146KRNY_1234
Adder
8.506
966261AG1-495 GEN
Solar/Wind Harmer
1.648
20676328BVR_Y1-020
Solar/Wind Harmer
0.296
207511W3-106 GEN
Solar/Wind Harmer
0.583
207530AG1-191 GEN
Solar/Wind Harmer
1.214
20674828DL_W4-046
Solar/Wind Harmer
0.549
971009AG2-626 GEN
Solar/Wind Harmer
1.365
207408W3-077 C
Solar/Wind Harmer
0.414
20675728RH_W2-091
Solar/Wind Harmer
0.28
966421AG1-511 GEN
Solar/Wind Harmer
7.027
20675928HOL_W4-097
Solar/Wind Harmer
0.106
207484AF2-139 C O1
Solar/Wind Harmer
0.408
20675128HRM_W1-127
Solar/Wind Harmer
0.136
20462827N BANGR8
Adder
0.568
209116AE2-175 GEN
Solar/Wind Harmer
3.023
961261AF2-417 GEN
Solar/Wind Harmer
0.669
209026WIENIPP4
Adder
3.159
3138216PACIFIC
Solar/Wind Helper
0.041
316411AF1-147_GEN1
Solar/Wind Helper
0.817
316415AF1-147_GEN2
Solar/Wind Helper
0.817
3141426STAFORD
Solar/Wind Helper
0.051
316164AC1-076 GEN
Solar/Wind Helper
1.11
238152AF2-075_GEN
Solar/Wind Helper
0.565
23546401DTGZ2-030
Solar/Wind Helper
0.072
316223AC1-118
Solar/Wind Helper
0.347
3141813NORNECK
Solar/Wind Helper
0.227
316312AB1-027
Solar/Wind Helper
0.431
3141783LANCAST
Solar/Wind Helper
0.136
3141783LANCAST
Solar/Wind Helper
0.091
3138133OCRAN
Solar/Wind Helper
0.068
3141913WHIT STONE
Solar/Wind Helper
0.226
316233AE1-074 FULL
Solar/Wind Helper
0.346
316059AD1-063 C
Solar/Wind Helper
0.228
3143873LANEXA
Solar/Wind Helper
0.136
315662AE1-191 GEN
Solar/Wind Helper
1.216
315666AE1-190 GEN
Solar/Wind Helper
0.304
957601AF2-054 GEN
Solar/Wind Helper
0.303
3141873WAN 176
Solar/Wind Helper
0.045
957831AF2-077 GEN
Solar/Wind Helper
0.304
316132AB2-190 GEN1
Solar/Wind Helper
1.286
200035PCHBTM 3
50/50
41.108
200201DELTA2 CT2
50/50
6.886
200034PCHBTM 2
50/50
40.065
200205Y1-065-CTG2
50/50
7.737
233987AB2-037 GEN
Solar/Wind Harmer
21.599
232926CRISFLD1
Adder
3.712
233901CHERRYDALE C
Solar/Wind Harmer
2.129
232408W1-005 C
Solar/Wind Harmer
1.894
232410W1-006 C
Solar/Wind Harmer
1.894
232918OH NUG7
Adder
16.593
232905CHERITON_25
Adder
4.64
972069AH1-584 GEN
Solar/Wind Harmer
16.937
972071AH1-585 GEN
Solar/Wind Harmer
16.937
971747AH1-380 GEN
Solar/Wind Harmer
6.775
970545AG2-347 GEN
Solar/Wind Harmer
123.721
200200DELTA2 CT1
50/50
6.886
200193DELTA CT2
50/50
3.848
200203Y1-065-STG
50/50
13.417
231940T-011
Adder
1.41
971149AH1-027 GEN
Solar/Wind Harmer
6.397
233946AB2-136 GEN
Solar/Wind Harmer
7.542
234036AF2-325 C
Solar/Wind Harmer
1.732
234041AC1-190 GEN
Solar/Wind Harmer
16.916
233939AC1-091 C
Solar/Wind Harmer
1.658
233970AC1-092 C
Solar/Wind Harmer
1.658
232899W1-062
Adder
18.141
233984AB2-036 GEN
Solar/Wind Harmer
23.372
232424Y1-079 C
Solar/Wind Harmer
1.055
234014AF1-036_GEN
Solar/Wind Harmer
5.057
231131BLOOM ENRGY
Adder
8.121
233944AB2-135 GEN
Solar/Wind Harmer
9.752
233933AB2-153 GEN
Solar/Wind Harmer
2.094
232416X2-083
Adder
0.822
228251CARLLS#4
Adder
0.908
230433AD2-135 GEN
Solar/Wind Harmer
0.144
230422AE1-104_GEN1
Solar/Wind Harmer
48.016
230425AE1-104_GEN2
Solar/Wind Harmer
48.016
228307PCLP GT
Adder
17.143
228304LOGAN
Adder
34.151
213589EDDYSTN4
Adder
112.515
213587EDDYSTN3
Adder
112.468
230407AD2-065 C
Solar/Wind Harmer
0.186
972233AH1-701 GEN
Adder
5.892
219921AF1-264
Solar/Wind Harmer
0.196
219615MILLCREEK C
Solar/Wind Harmer
0.311
200055ROCKSP 4
50/50
4.832
232907VN8
Adder
56.816
233996TM1833_GEN
Solar/Wind Harmer
2.396
233997TMININ_4.2
Solar/Wind Harmer
2.396
232406W1-004 FULL
Solar/Wind Harmer
1.894
232914OH NUG3
Adder
16.704
232916OH NUG5
Adder
16.704
232921TASLEY2G
Adder
9.763
233940AF2-379 C
Solar/Wind Harmer
0.353
972073AH1-586 GEN
Solar/Wind Harmer
17.724
233900O-025 C
Adder
2.227
972133AH1-634 GEN
Solar/Wind Harmer
18.746
233990AG1-397 GEN
Solar/Wind Harmer
2.169
234015AF2-250 C
Solar/Wind Harmer
0.228
233994AC2-023 GEN
Solar/Wind Harmer
5.083
960671AF2-358 GEN
Solar/Wind Harmer
33.854
232417X3-008 C
Solar/Wind Harmer
3.779
233971AC1-093 C
Solar/Wind Harmer
1.481
970695AG2-447 GEN
Solar/Wind Harmer
6.763
233952AC2-187 GEN
Solar/Wind Harmer
2.123
233918AB1-142 GEN
Solar/Wind Harmer
1.844
233982AB2-133 GEN
Solar/Wind Harmer
9.053
972251AH1-710 GEN
Adder
80.123
228202CUMB CT
Adder
23.982
228711V2-041C
Solar/Wind Harmer
0.871
971553AH1-274 GEN
Solar/Wind Harmer
3.497
230430AE1-229_GEN
Solar/Wind Harmer
12.59
230415AB2-049 C
Solar/Wind Harmer
0.269
213497CHSTR7-9
Adder
3.862
228304LOGAN
Adder
30.715
228729W2-030 C
Solar/Wind Harmer
0.814
219623KINSLEYBEA C
Solar/Wind Harmer
0.583
213958STHWK5-6
Adder
3.703
219766PARADISE C
Solar/Wind Harmer
0.426
219291REEVESSOUT C
Solar/Wind Harmer
0.081
219912AD2-042 GEN
Solar/Wind Harmer
1.068
213560DLW11-12
Adder
3.608
219236SOUTHERNHQ C
Solar/Wind Harmer
0.089
219906AC1-017 C
Solar/Wind Harmer
0.291
219610FLORENCE C
Solar/Wind Harmer
1.784
219348LDSOLAR C
Solar/Wind Harmer
0.771
219221BRL12CT1
Adder
11.496
219223BRL12CT3
Adder
11.496
213815MOSER1-3
Adder
4.564
959561AF2-247 GEN
Solar/Wind Harmer
0.603
20716028EGP_W2-019
Solar/Wind Harmer
0.573
20720828JCB_W4-025
Solar/Wind Harmer
0.559
20715028HAN_X4-015
Solar/Wind Harmer
0.368
20636028O CRK C1
Adder
8.644
971667AH1-334 GEN
Solar/Wind Harmer
3.297
219727YARDVSOLFA C
Solar/Wind Harmer
1.084
20714528FRN_Y2-051
Solar/Wind Harmer
0.346
219276PARKLANDSO C
Solar/Wind Harmer
0.538
219918AC2-009 C
Solar/Wind Harmer
0.07
20716228APLW2-078
Solar/Wind Harmer
1.003
20720528MAN_W1-024
Solar/Wind Harmer
0.288
967451AG2-055 C O1
Solar/Wind Harmer
192.98
219612MATRIX C
Solar/Wind Harmer
0.204
218438BLK ROCK C
Solar/Wind Harmer
0.151
20635828PARLN1&2
Adder
3.629
20635928PARLN3&4
Adder
3.629
20635028RRCT1&2
Adder
12.638
20635128RRCT3&4
Adder
10.477
219908AB1-139 C
Solar/Wind Harmer
0.399
219919AE1-041 FULL
Solar/Wind Harmer
0.042
219249CENTRALDIV C
Solar/Wind Harmer
0.041
20673728F2S_V4-070
Solar/Wind Harmer
0.183
217211CAMDEN ST C
Solar/Wind Harmer
0.024
217186ESSEX_G9
Adder
15.809
217169METRODIV C
Solar/Wind Harmer
0.039
217194REDH C
Solar/Wind Harmer
0.486
20676728BRNX1-095
Solar/Wind Harmer
0.166
207510AF2-138 C
Solar/Wind Harmer
1.582
20674628WNG_W3-110
Solar/Wind Harmer
0.359
971007AG2-625 GEN
Solar/Wind Harmer
2.14
20466127PORT 5CT
Adder
21.343
20633028GILCT9
Adder
22.387
966181AG1-487 GEN
Solar/Wind Harmer
0.199
20465427SHAW CT
Adder
3.059
963071AG1-156 GEN
Solar/Wind Harmer
1.673
970095AG2-074 GEN
Solar/Wind Harmer
3.796
963161AG1-165 GEN
Solar/Wind Harmer
0.593
209025WIENIPP3
Adder
3.127
3141196NOKESVL
Solar/Wind Helper
0.957
316044AC1-158 PL1
Solar/Wind Helper
1.295
316450AC1-158 RIC
Solar/Wind Helper
0.345
316170AC1-121 GEN2
Solar/Wind Helper
0.356
3132273ORANGE
Solar/Wind Helper
0.046
3147666LOUISA
Solar/Wind Helper
0.53
238147AE2-230_GEN1
Solar/Wind Helper
0.395
238149AF1-291A_GEN
Solar/Wind Helper
0.113
966881AG1-559 GEN
Solar/Wind Helper
0.309
237061AD1-155 GEN
Solar/Wind Helper
0.043
3141906WESTMOR
Solar/Wind Helper
0.091
316473AC1-191 GEN
Solar/Wind Helper
1.387
316404AE1-155 C
Solar/Wind Helper
1.916
316484AD2-074 GEN
Solar/Wind Helper
0.438
316280AD1-041 GEN
Solar/Wind Helper
0.76
316156AD2-030 GEN
Solar/Wind Helper
0.341
3142946ENON
Solar/Wind Helper
0.075
316382AG1-145 C
Solar/Wind Helper
0.303
315839AE2-212 C
Solar/Wind Helper
0.302
316313AB2-026
Solar/Wind Helper
0.342
316258AE1-075 C
Solar/Wind Helper
0.308
316405AF2-144 C
Solar/Wind Helper
0.256
3145336SMITFLD
Solar/Wind Helper
0.09
315773AC2-141 GEN
Solar/Wind Helper
4.83
3144536CHRHLND
Solar/Wind Helper
0.034
200192DELTA CT1
50/50
3.848
200194DELTA CT3
50/50
3.848
200204Y1-065-CTG1
50/50
7.737
200054ROCKSP 3
50/50
4.936
233998TM1NIN_3.36
Solar/Wind Harmer
2.396
232404W1-003 C
Solar/Wind Harmer
1.894
232917OH NUG6
Adder
16.63
232915OH NUG4
Adder
16.593
232428Y3-058 C
Solar/Wind Harmer
1.578
232434Z2-077 GEN
Solar/Wind Harmer
0.473
971195AH1-057 GEN
Solar/Wind Harmer
2.07
232919VN10
Adder
5.306
232901NORTHST
Adder
15.73
965821AG1-450 GEN
Solar/Wind Harmer
9.841
232426Y1-080 FULL
Solar/Wind Harmer
0.361
970277AG2-181 GEN
Solar/Wind Harmer
9.478
233964AF2-378 GEN
Solar/Wind Harmer
0.241
972177AH1-672 GEN
Solar/Wind Harmer
25.38
233972AC1-094 C
Solar/Wind Harmer
1.252
232900DEMECSMY
Adder
17.4
233954AC2-188 GEN
Solar/Wind Harmer
2.123
233950AC2-186 GEN
Solar/Wind Harmer
1.061
232910NRG_G1
Adder
16.205
234012AE2-112_GEN
Solar/Wind Harmer
4.299
232422X3-066 FULL
Solar/Wind Harmer
0.467
233930AB2-032 GEN
Solar/Wind Harmer
1.552
233915AB1-141 GEN
Solar/Wind Harmer
1.844
231918WEST 1
Adder
5.956
231917EM10
Adder
4.123
228206SHRMN CT
Adder
24.012
228732V1-021 C
Adder
0.272
945431AF1-208 GEN
Solar/Wind Harmer
12.406
970997AG2-616 GEN
Solar/Wind Harmer
13.737
228351V2-046C
Solar/Wind Harmer
2.879
230511AF1-262
Solar/Wind Harmer
0.261
228728W1-130C
Solar/Wind Harmer
0.942
213497CHSTR7-9
Adder
3.862
213497CHSTR7-9
Adder
3.862
230434AG1-499 GEN
Solar/Wind Harmer
0.82
219258KINSLEYDEP C
Solar/Wind Harmer
0.441
213958STHWK5-6
Adder
3.703
219904AC1-010 C
Solar/Wind Harmer
0.511
218660EHAMPSOLAR C
Solar/Wind Harmer
0.235
219686LUMSOLAR_N C
Solar/Wind Harmer
0.271
219287REEVESEAST C
Solar/Wind Harmer
1.8
213560DLW11-12
Adder
3.608
219907AC1-030 C
Solar/Wind Harmer
0.184
219304NAMERICA C
Solar/Wind Harmer
0.4
219222BRL12CT2
Adder
11.496
213611FALLS1-3
Adder
4.417
20720728JCB_W1-129
Solar/Wind Harmer
0.368
207522AF2-254 C
Solar/Wind Harmer
1.768
214194N WALES4
Adder
1.05
207487AE2-000G4
Solar/Wind Harmer
38.522
207445AB1-138_GEN
Solar/Wind Harmer
0.693
20628028LAKEHURS
Adder
2.25
963711AG1-223 GEN
Solar/Wind Harmer
1.734
20714828MDF_W3-079
Solar/Wind Harmer
0.358
219680HOPEWELLV C1
Solar/Wind Harmer
0.087
207454AA2-184 E
Solar/Wind Harmer
1.138
20715228NPK_W1-113
Solar/Wind Harmer
0.488
20742028HF_AC1-207
Solar/Wind Harmer
0.886
217197RE CRAN C
Solar/Wind Harmer
0.594
20635828PARLN1&2
Adder
8.012
20635028RRCT1&2
Adder
12.443
20635128RRCT3&4
Adder
12.011
218428ETC SOLAR C
Solar/Wind Harmer
0.038
217213AMBOY SO C
Solar/Wind Harmer
0.133
972275AH1-722 GEN
Adder
32.692
218449LINSOLAR C
Solar/Wind Harmer
1.025
207528AF2-192 GEN
Solar/Wind Harmer
0.563
20673628F1S_V4-069
Solar/Wind Harmer
0.183
20675428EAM_W2-061
Solar/Wind Harmer
0.192
20676428JCR_X2-075
Solar/Wind Harmer
0.346
217209CENTRL HS C
Solar/Wind Harmer
0.045
217121ECCF
Adder
0.429
217083KRNY_132
Adder
9.189
217208PARK ELE C
Solar/Wind Harmer
0.025
207439AE1-081 C O1
Solar/Wind Harmer
0.054
20674328GAR_V4-001
Solar/Wind Harmer
0.097
20675828AU_W4-064
Solar/Wind Harmer
0.152
971519AH1-257 GEN
Solar/Wind Harmer
2.092
207518AF1-320_GEN
Solar/Wind Harmer
2.976
207437AD2-070 GEN
Solar/Wind Harmer
0.243
20465127PORT CT
Adder
2.414
20671928W4-073
Solar/Wind Harmer
0.345
966181AG1-487 GEN
Solar/Wind Harmer
2.962
208909MACR G3
Adder
122.259
209010PEIP 1
Adder
0.4
961301AF2-421 GEN
Solar/Wind Harmer
0.593
963151AG1-164 GEN
Solar/Wind Harmer
0.593
209023WIENIPP1
Adder
6.394
209025WIENIPP3
Adder
3.192
316006AB2-029 C
Solar/Wind Helper
0.112
316045AC1-158 PL2
Solar/Wind Helper
4.145
316254AC1-120 GEN1
Solar/Wind Helper
1.069
3147666LOUISA
Solar/Wind Helper
0.921
316192AB2-158 GEN
Solar/Wind Helper
1.547
238148AE2-230_GEN2
Solar/Wind Helper
0.397
316337AD2-073 GEN
Solar/Wind Helper
0.345
964211AG1-282 GEN
Solar/Wind Helper
0.306
3141726DUNNSVL
Solar/Wind Helper
0.908
3142416OLDCHRC
Solar/Wind Helper
0.589
3142416OLDCHRC
Solar/Wind Helper
0.226
3138133OCRAN
Solar/Wind Helper
0.136
3143526WINTERP
Solar/Wind Helper
1.176
3141766HARMONY
Solar/Wind Helper
0.045
3143226MDLTHAN
Solar/Wind Helper
0.226
3142433PROV 92
Solar/Wind Helper
0.904
3142543TWELFTH
Solar/Wind Helper
0.022
316159AE1-175 C
Solar/Wind Helper
0.342
213815MOSER1-3
Adder
4.564
213815MOSER1-3
Adder
4.564
213535CROYDN11
Adder
13.155
20716428NHV_W2-082
Solar/Wind Harmer
2.192
207500AE2-000G1
Solar/Wind Harmer
38.522
207497AE2-000G2
Solar/Wind Harmer
38.522
207507AE2-000G3
Solar/Wind Harmer
38.522
20636128O CRK C2
Adder
7.881
963401AG1-189 GEN
Solar/Wind Harmer
1.399
963391AG1-188 GEN
Solar/Wind Harmer
2.325
20714928UPF_X1-085
Solar/Wind Harmer
0.49
219114HARTZY_C
Solar/Wind Harmer
1.002
20628028LAKEHURS
Adder
1.137
219817TRENTONSOL C
Solar/Wind Harmer
1.268
20641628MLH_W1-032
Solar/Wind Harmer
0.334
20720628TIN_W1-124
Solar/Wind Harmer
1.134
20716928W4-060COL
Solar/Wind Harmer
0.785
924131AB2-057 GEN
Solar/Wind Harmer
1.109
218440SUMMTASSOC C
Solar/Wind Harmer
0.135
218418LINDEN_G5
Adder
17.783
218419LINDEN_G6
Adder
17.783
972260AH1-715 GEN1
Adder
14.24
20673828FLE_V3-070
Solar/Wind Harmer
0.472
219036LINDEN_G7
Adder
17.045
219035LINDEN_G8
Adder
16.802
972261AH1-715 GEN2
Adder
16.317
207442AE1-156 GEN
Solar/Wind Harmer
0.757
20676128MHD_W3-029
Solar/Wind Harmer
0.486
217081WEATEXAS C
Solar/Wind Harmer
0.087
217202FBANKSOLAR C
Solar/Wind Harmer
0.074
217201HACKENSOLA C
Solar/Wind Harmer
0.073
972237AH1-703 GEN
Adder
10.011
217206BARNGR HS C
Solar/Wind Harmer
0.03
217086KRNY_131
Adder
9.208
217083KRNY_132
Adder
9.13
20671828STAW2-080
Solar/Wind Harmer
0.103
217204WCALDSOLAR C
Solar/Wind Harmer
0.072
20674528F3S_W2-016
Solar/Wind Harmer
1.358
20676228FRD_X1-012
Solar/Wind Harmer
0.524
207471AF2-354 C
Solar/Wind Harmer
0.433
20674928WA_W3-044
Solar/Wind Harmer
0.408
964851AG1-348 GEN
Solar/Wind Harmer
1.466
20634528N27_Y2-018
Solar/Wind Harmer
0.224
20465127PORT CT
Adder
3.203
20674128FR_U2-059
Solar/Wind Harmer
0.147
966111AG1-480 GEN
Solar/Wind Harmer
0.068
966111AG1-480 GEN
Solar/Wind Harmer
2.611
211065PSPA IPP
Solar/Wind Harmer
0.315
211065PSPA IPP
Solar/Wind Harmer
0.315
209029WAYMART-WD
Solar/Wind Harmer
1.79
209009PEIP 2
Adder
4.862
209010PEIP 1
Adder
2.203
209010PEIP 1
Adder
0.323
208972BECR K09
Solar/Wind Harmer
0.618
238175AF1-290_GEN
Solar/Wind Helper
0.124
238169AE2-226 GEN1
Solar/Wind Helper
0.572
238170AE2-226 GEN2
Solar/Wind Helper
0.572
315651AD1-115 GEN
Solar/Wind Helper
0.784
316447AC1-158 HLD
Solar/Wind Helper
2.85
966001AG1-469 GEN
Solar/Wind Helper
0.246
235020AA1-095 C
Solar/Wind Helper
0.043
23777901MDS_W4-102
Solar/Wind Helper
0.143
316468AD1-105 GEN
Solar/Wind Helper
1.135
316077AC2-138 C
Solar/Wind Helper
0.214
966871AG1-558 GEN
Solar/Wind Helper
0.306
316487AF1-042 GEN
Solar/Wind Helper
0.229
316075AC2-137 C
Solar/Wind Helper
0.345
3143526WINTERP
Solar/Wind Helper
1.176
3142946ENON
Solar/Wind Helper
0.023
316240AF1-291 C
Solar/Wind Helper
0.303
316033AB2-134 GEN
Solar/Wind Helper
0.774
315697AD1-025 GEN
Solar/Wind Helper
2.571
316236AE1-162_GEN
Solar/Wind Helper
0.302
316036AC1-147 C
Solar/Wind Helper
0.341
3142956BIRDNECK
Solar/Wind Helper
0.151
316316AC1-027 C
Solar/Wind Helper
0.354
316185AD1-033 GEN
Solar/Wind Helper
1.054
3145506HICKORY
Solar/Wind Helper
0.896
3145506HICKORY
Solar/Wind Helper
0.537
3145506HICKORY
Solar/Wind Helper
0.134
316339AD2-160 GEN
Solar/Wind Helper
0.852
316018AA1-139 ULT2
Solar/Wind Helper
0.962
316017AA1-139 ULT1
Solar/Wind Helper
1.023
3137176SLIGO L2192
Solar/Wind Helper
0.89
3130086AYDLETT
Solar/Wind Helper
0.895
3146386ELIZ CT
Solar/Wind Helper
0.223
316431W1029_GEN1
Solar/Wind Helper
0.902
316433W1029_GEN2
Solar/Wind Helper
0.902
3146516WINFALL
Solar/Wind Helper
0.223
3146516WINFALL
Solar/Wind Helper
0.223
3146516WINFALL
Solar/Wind Helper
0.223
237034AC2-136 C
Solar/Wind Helper
0.184
3146626S HERTFORD
Solar/Wind Helper
0.223
3146626S HERTFORD
Solar/Wind Helper
0.223
3144356SAPONY
Solar/Wind Helper
0.4
316369SG1_INVT
Solar/Wind Helper
1.082
3143316POE
Solar/Wind Helper
0.889
316349AD2-085 GEN
Solar/Wind Helper
1.024
319010AE1-072 C
Solar/Wind Helper
2.557
316305AF2-043 C
Solar/Wind Helper
0.301
313526AB2-022
Solar/Wind Helper
0.34
3146486SUNBURY
Solar/Wind Helper
0.223
3146486SUNBURY
Solar/Wind Helper
0.223
316321Z2-027
Solar/Wind Helper
0.34
3145176PASQUOTANK
Solar/Wind Helper
0.138
316315AB2-025 C
Solar/Wind Helper
0.339
316458AB2-190 GEN2
Solar/Wind Helper
1.286
3145336SMITFLD
Solar/Wind Helper
0.898
316294AC1-161 GEN
Solar/Wind Helper
4.104
316381AD1-082 GEN
Solar/Wind Helper
1.161
316375AC2-012 GEN
Solar/Wind Helper
0.587
316336AC2-165 C
Solar/Wind Helper
1.208
316072AD1-144
Solar/Wind Helper
0.256
316388AE2-253 GEN
Solar/Wind Helper
0.852
3146456SLIGO L269
Solar/Wind Helper
0.224
316246AF1-032 C
Solar/Wind Helper
0.256
3146516WINFALL
Solar/Wind Helper
0.723
3146516WINFALL
Solar/Wind Helper
0.223
3144873MCLAUGH
Solar/Wind Helper
0.006
3146456SLIGO L269
Solar/Wind Helper
0.224
316320Y1-086
Solar/Wind Helper
0.1
316435W1029_GEN3
Solar/Wind Helper
0.902
3146516WINFALL
Solar/Wind Helper
0.223
238221AF1-254 C O1
Solar/Wind Helper
0.219
3146626S HERTFORD
Solar/Wind Helper
0.223
3145273HOLLAND
Solar/Wind Helper
0.167
HAMLETPJM->LTFIMP_HAMLET
CLTF
5.427
G-007ALTFEXP_G-007A->PJM
CMTX
54.959
CBM NorthLTFEXP_CBM-N->PJM
CBM
62.949
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
4.801
BlueGrassPJM->LTFIMP_BlueG
CLTF
14.952
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
135.356
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.242
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
22.436

Details for PCHBTM1N-CHAN 500.0 kV Ckt 1 line l/o PECO_P4_PEACH235_SRT-A/* $ CHESCO $ PECO_P4_PEACH235 $ STBK


Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1N-CHAN 500.0 kV Ckt 1 line
Contingency Name:
PECO_P4_PEACH235_SRT-A/* $ CHESCO $ PECO_P4_PEACH235 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:149.64 %
Rating:3486.0 MVA
Rating Type:B
MVA to Mitigate:5216.48
MW Contribution:10.89
Bus #Bus NameTypeMW Contribution
200035PCHBTM 3
50/50
41.119
200201DELTA2 CT2
50/50
6.888
200034PCHBTM 2
50/50
40.02
200205Y1-065-CTG2
50/50
7.729
233987AB2-037 GEN
Solar/Wind Harmer
21.582
232926CRISFLD1
Adder
3.709
233901CHERRYDALE C
Solar/Wind Harmer
2.128
232408W1-005 C
Solar/Wind Harmer
1.893
232410W1-006 C
Solar/Wind Harmer
1.893
232918OH NUG7
Adder
16.579
232905CHERITON_25
Adder
4.636
972069AH1-584 GEN
Solar/Wind Harmer
16.923
972071AH1-585 GEN
Solar/Wind Harmer
16.923
200202DELTA2 ST
50/50
11.688
200195DELTA ST
50/50
5.947
971747AH1-380 GEN
Solar/Wind Harmer
6.769
970545AG2-347 GEN
Solar/Wind Harmer
123.621
231940T-011
Adder
1.409
971149AH1-027 GEN
Solar/Wind Harmer
6.392
233946AB2-136 GEN
Solar/Wind Harmer
7.536
234036AF2-325 C
Solar/Wind Harmer
1.731
234041AC1-190 GEN
Solar/Wind Harmer
16.902
233939AC1-091 C
Solar/Wind Harmer
1.657
233970AC1-092 C
Solar/Wind Harmer
1.657
232899W1-062
Adder
18.126
233984AB2-036 GEN
Solar/Wind Harmer
23.353
232424Y1-079 C
Solar/Wind Harmer
1.055
234014AF1-036_GEN
Solar/Wind Harmer
5.053
231131BLOOM ENRGY
Adder
8.114
233944AB2-135 GEN
Solar/Wind Harmer
9.744
233933AB2-153 GEN
Solar/Wind Harmer
2.092
232416X2-083
Adder
0.821
228251CARLLS#4
Adder
0.907
230433AD2-135 GEN
Solar/Wind Harmer
0.144
230422AE1-104_GEN1
Solar/Wind Harmer
47.987
230425AE1-104_GEN2
Solar/Wind Harmer
47.987
228307PCLP GT
Adder
17.133
228304LOGAN
Adder
34.132
213589EDDYSTN4
Adder
112.467
213587EDDYSTN3
Adder
112.421
230407AD2-065 C
Solar/Wind Harmer
0.186
972233AH1-701 GEN
Adder
5.889
219921AF1-264
Solar/Wind Harmer
0.196
219615MILLCREEK C
Solar/Wind Harmer
0.311
213815MOSER1-3
Adder
4.563
213815MOSER1-3
Adder
4.563
213535CROYDN11
Adder
13.149
20716428NHV_W2-082
Solar/Wind Harmer
2.191
207500AE2-000G1
Solar/Wind Harmer
38.502
207497AE2-000G2
Solar/Wind Harmer
38.502
207507AE2-000G3
Solar/Wind Harmer
38.502
20636128O CRK C2
Adder
7.877
963401AG1-189 GEN
Solar/Wind Harmer
1.398
963391AG1-188 GEN
Solar/Wind Harmer
2.324
20714928UPF_X1-085
Solar/Wind Harmer
0.49
219114HARTZY_C
Solar/Wind Harmer
1.002
20628028LAKEHURS
Adder
1.137
219817TRENTONSOL C
Solar/Wind Harmer
1.268
20641628MLH_W1-032
Solar/Wind Harmer
0.334
20720628TIN_W1-124
Solar/Wind Harmer
1.134
20716928W4-060COL
Solar/Wind Harmer
0.784
924131AB2-057 GEN
Solar/Wind Harmer
1.109
218440SUMMTASSOC C
Solar/Wind Harmer
0.135
218418LINDEN_G5
Adder
17.776
218419LINDEN_G6
Adder
17.776
972260AH1-715 GEN1
Adder
14.234
20673828FLE_V3-070
Solar/Wind Harmer
0.472
219036LINDEN_G7
Adder
17.039
219035LINDEN_G8
Adder
16.796
972261AH1-715 GEN2
Adder
16.31
207442AE1-156 GEN
Solar/Wind Harmer
0.757
20676128MHD_W3-029
Solar/Wind Harmer
0.485
217081WEATEXAS C
Solar/Wind Harmer
0.087
217202FBANKSOLAR C
Solar/Wind Harmer
0.074
217201HACKENSOLA C
Solar/Wind Harmer
0.073
972237AH1-703 GEN
Adder
10.007
217206BARNGR HS C
Solar/Wind Harmer
0.03
217086KRNY_131
Adder
9.205
217083KRNY_132
Adder
9.127
20671828STAW2-080
Solar/Wind Harmer
0.103
217204WCALDSOLAR C
Solar/Wind Harmer
0.072
20674528F3S_W2-016
Solar/Wind Harmer
1.358
20676228FRD_X1-012
Solar/Wind Harmer
0.523
207471AF2-354 C
Solar/Wind Harmer
0.433
20674928WA_W3-044
Solar/Wind Harmer
0.408
964851AG1-348 GEN
Solar/Wind Harmer
1.466
20634528N27_Y2-018
Solar/Wind Harmer
0.224
20465127PORT CT
Adder
3.202
20674128FR_U2-059
Solar/Wind Harmer
0.147
966111AG1-480 GEN
Solar/Wind Harmer
0.068
966111AG1-480 GEN
Solar/Wind Harmer
2.61
211065PSPA IPP
Solar/Wind Harmer
0.315
211065PSPA IPP
Solar/Wind Harmer
0.315
209029WAYMART-WD
Solar/Wind Harmer
1.79
209009PEIP 2
Adder
4.86
209010PEIP 1
Adder
2.202
209010PEIP 1
Adder
0.323
208972BECR K09
Solar/Wind Harmer
0.618
238175AF1-290_GEN
Solar/Wind Helper
0.124
238169AE2-226 GEN1
Solar/Wind Helper
0.571
238170AE2-226 GEN2
Solar/Wind Helper
0.571
315651AD1-115 GEN
Solar/Wind Helper
0.784
316447AC1-158 HLD
Solar/Wind Helper
2.849
966001AG1-469 GEN
Solar/Wind Helper
0.246
235020AA1-095 C
Solar/Wind Helper
0.043
23777901MDS_W4-102
Solar/Wind Helper
0.143
316468AD1-105 GEN
Solar/Wind Helper
1.134
316077AC2-138 C
Solar/Wind Helper
0.214
966871AG1-558 GEN
Solar/Wind Helper
0.306
316487AF1-042 GEN
Solar/Wind Helper
0.229
316075AC2-137 C
Solar/Wind Helper
0.345
3143526WINTERP
Solar/Wind Helper
1.176
3142946ENON
Solar/Wind Helper
0.023
316240AF1-291 C
Solar/Wind Helper
0.303
316033AB2-134 GEN
Solar/Wind Helper
0.773
315697AD1-025 GEN
Solar/Wind Helper
2.57
316236AE1-162_GEN
Solar/Wind Helper
0.302
316036AC1-147 C
Solar/Wind Helper
0.341
3142956BIRDNECK
Solar/Wind Helper
0.151
316316AC1-027 C
Solar/Wind Helper
0.353
316185AD1-033 GEN
Solar/Wind Helper
1.053
3145506HICKORY
Solar/Wind Helper
0.895
3145506HICKORY
Solar/Wind Helper
0.537
3145506HICKORY
Solar/Wind Helper
0.134
316339AD2-160 GEN
Solar/Wind Helper
0.852
316018AA1-139 ULT2
Solar/Wind Helper
0.962
316017AA1-139 ULT1
Solar/Wind Helper
1.022
3137176SLIGO L2192
Solar/Wind Helper
0.89
3130086AYDLETT
Solar/Wind Helper
0.894
3146386ELIZ CT
Solar/Wind Helper
0.223
316431W1029_GEN1
Solar/Wind Helper
0.901
316433W1029_GEN2
Solar/Wind Helper
0.901
3146516WINFALL
Solar/Wind Helper
0.223
3146516WINFALL
Solar/Wind Helper
0.223
3146516WINFALL
Solar/Wind Helper
0.223
237034AC2-136 C
Solar/Wind Helper
0.184
3146626S HERTFORD
Solar/Wind Helper
0.223
3146626S HERTFORD
Solar/Wind Helper
0.223
3144356SAPONY
Solar/Wind Helper
0.4
200192DELTA CT1
50/50
3.849
200194DELTA CT3
50/50
3.849
200204Y1-065-CTG1
50/50
7.729
200054ROCKSP 3
50/50
4.931
233998TM1NIN_3.36
Solar/Wind Harmer
2.394
232404W1-003 C
Solar/Wind Harmer
1.893
232917OH NUG6
Adder
16.617
232915OH NUG4
Adder
16.579
232428Y3-058 C
Solar/Wind Harmer
1.577
232434Z2-077 GEN
Solar/Wind Harmer
0.473
971195AH1-057 GEN
Solar/Wind Harmer
2.068
232919VN10
Adder
5.302
232901NORTHST
Adder
15.717
965821AG1-450 GEN
Solar/Wind Harmer
9.833
232426Y1-080 FULL
Solar/Wind Harmer
0.361
970277AG2-181 GEN
Solar/Wind Harmer
9.471
233964AF2-378 GEN
Solar/Wind Harmer
0.241
972177AH1-672 GEN
Solar/Wind Harmer
25.36
233972AC1-094 C
Solar/Wind Harmer
1.251
232900DEMECSMY
Adder
17.386
233954AC2-188 GEN
Solar/Wind Harmer
2.121
233950AC2-186 GEN
Solar/Wind Harmer
1.06
232910NRG_G1
Adder
16.192
234012AE2-112_GEN
Solar/Wind Harmer
4.295
232422X3-066 FULL
Solar/Wind Harmer
0.467
233930AB2-032 GEN
Solar/Wind Harmer
1.551
233915AB1-141 GEN
Solar/Wind Harmer
1.842
231918WEST 1
Adder
5.952
231917EM10
Adder
4.12
228206SHRMN CT
Adder
23.997
228732V1-021 C
Adder
0.272
945431AF1-208 GEN
Solar/Wind Harmer
12.398
970997AG2-616 GEN
Solar/Wind Harmer
13.729
228351V2-046C
Solar/Wind Harmer
2.877
230511AF1-262
Solar/Wind Harmer
0.261
228728W1-130C
Solar/Wind Harmer
0.942
213497CHSTR7-9
Adder
3.86
213497CHSTR7-9
Adder
3.86
230434AG1-499 GEN
Solar/Wind Harmer
0.819
219258KINSLEYDEP C
Solar/Wind Harmer
0.441
213958STHWK5-6
Adder
3.702
219904AC1-010 C
Solar/Wind Harmer
0.511
218660EHAMPSOLAR C
Solar/Wind Harmer
0.235
219686LUMSOLAR_N C
Solar/Wind Harmer
0.271
219287REEVESEAST C
Solar/Wind Harmer
1.799
213560DLW11-12
Adder
3.607
219907AC1-030 C
Solar/Wind Harmer
0.184
219304NAMERICA C
Solar/Wind Harmer
0.4
219222BRL12CT2
Adder
11.491
213611FALLS1-3
Adder
4.415
20720728JCB_W1-129
Solar/Wind Harmer
0.368
207522AF2-254 C
Solar/Wind Harmer
1.767
214194N WALES4
Adder
1.049
207487AE2-000G4
Solar/Wind Harmer
38.502
207445AB1-138_GEN
Solar/Wind Harmer
0.693
20628028LAKEHURS
Adder
2.249
963711AG1-223 GEN
Solar/Wind Harmer
1.733
20714828MDF_W3-079
Solar/Wind Harmer
0.358
219680HOPEWELLV C1
Solar/Wind Harmer
0.087
207454AA2-184 E
Solar/Wind Harmer
1.138
20715228NPK_W1-113
Solar/Wind Harmer
0.488
20742028HF_AC1-207
Solar/Wind Harmer
0.885
217197RE CRAN C
Solar/Wind Harmer
0.594
20635828PARLN1&2
Adder
8.008
20635028RRCT1&2
Adder
12.438
20635128RRCT3&4
Adder
12.006
218428ETC SOLAR C
Solar/Wind Harmer
0.038
217213AMBOY SO C
Solar/Wind Harmer
0.132
972275AH1-722 GEN
Adder
32.679
218449LINSOLAR C
Solar/Wind Harmer
1.025
207528AF2-192 GEN
Solar/Wind Harmer
0.563
20673628F1S_V4-069
Solar/Wind Harmer
0.183
20675428EAM_W2-061
Solar/Wind Harmer
0.192
20676428JCR_X2-075
Solar/Wind Harmer
0.346
217209CENTRL HS C
Solar/Wind Harmer
0.045
217121ECCF
Adder
0.429
217083KRNY_132
Adder
9.185
217208PARK ELE C
Solar/Wind Harmer
0.025
207439AE1-081 C O1
Solar/Wind Harmer
0.054
20674328GAR_V4-001
Solar/Wind Harmer
0.097
20675828AU_W4-064
Solar/Wind Harmer
0.152
971519AH1-257 GEN
Solar/Wind Harmer
2.091
207518AF1-320_GEN
Solar/Wind Harmer
2.975
207437AD2-070 GEN
Solar/Wind Harmer
0.243
20465127PORT CT
Adder
2.413
20671928W4-073
Solar/Wind Harmer
0.345
966181AG1-487 GEN
Solar/Wind Harmer
2.962
208909MACR G3
Adder
122.225
209010PEIP 1
Adder
0.4
961301AF2-421 GEN
Solar/Wind Harmer
0.593
963151AG1-164 GEN
Solar/Wind Harmer
0.593
209023WIENIPP1
Adder
6.392
209025WIENIPP3
Adder
3.191
316006AB2-029 C
Solar/Wind Helper
0.112
316045AC1-158 PL2
Solar/Wind Helper
4.143
316254AC1-120 GEN1
Solar/Wind Helper
1.069
3147666LOUISA
Solar/Wind Helper
0.921
316192AB2-158 GEN
Solar/Wind Helper
1.546
238148AE2-230_GEN2
Solar/Wind Helper
0.397
316337AD2-073 GEN
Solar/Wind Helper
0.345
964211AG1-282 GEN
Solar/Wind Helper
0.306
3141726DUNNSVL
Solar/Wind Helper
0.908
3142416OLDCHRC
Solar/Wind Helper
0.589
3142416OLDCHRC
Solar/Wind Helper
0.226
3138133OCRAN
Solar/Wind Helper
0.136
3143526WINTERP
Solar/Wind Helper
1.176
3141766HARMONY
Solar/Wind Helper
0.045
3143226MDLTHAN
Solar/Wind Helper
0.226
3142433PROV 92
Solar/Wind Helper
0.904
3142543TWELFTH
Solar/Wind Helper
0.022
316159AE1-175 C
Solar/Wind Helper
0.342
316458AB2-190 GEN2
Solar/Wind Helper
1.286
3145336SMITFLD
Solar/Wind Helper
0.898
316294AC1-161 GEN
Solar/Wind Helper
4.102
316381AD1-082 GEN
Solar/Wind Helper
1.161
316375AC2-012 GEN
Solar/Wind Helper
0.587
316336AC2-165 C
Solar/Wind Helper
1.207
316072AD1-144
Solar/Wind Helper
0.256
316388AE2-253 GEN
Solar/Wind Helper
0.852
3146456SLIGO L269
Solar/Wind Helper
0.224
316246AF1-032 C
Solar/Wind Helper
0.255
3146516WINFALL
Solar/Wind Helper
0.722
3146516WINFALL
Solar/Wind Helper
0.223
200200DELTA2 CT1
50/50
6.888
200193DELTA CT2
50/50
3.849
200203Y1-065-STG
50/50
13.403
200055ROCKSP 4
50/50
4.827
232907VN8
Adder
56.77
233996TM1833_GEN
Solar/Wind Harmer
2.394
233997TMININ_4.2
Solar/Wind Harmer
2.394
232406W1-004 FULL
Solar/Wind Harmer
1.893
232914OH NUG3
Adder
16.691
232916OH NUG5
Adder
16.691
232921TASLEY2G
Adder
9.755
233940AF2-379 C
Solar/Wind Harmer
0.353
972073AH1-586 GEN
Solar/Wind Harmer
17.71
233990AG1-397 GEN
Solar/Wind Harmer
2.167
233900O-025 C
Adder
2.225
972133AH1-634 GEN
Solar/Wind Harmer
18.73
234015AF2-250 C
Solar/Wind Harmer
0.227
233994AC2-023 GEN
Solar/Wind Harmer
5.079
960671AF2-358 GEN
Solar/Wind Harmer
33.827
232417X3-008 C
Solar/Wind Harmer
3.775
233971AC1-093 C
Solar/Wind Harmer
1.48
970695AG2-447 GEN
Solar/Wind Harmer
6.758
233952AC2-187 GEN
Solar/Wind Harmer
2.121
233918AB1-142 GEN
Solar/Wind Harmer
1.842
233982AB2-133 GEN
Solar/Wind Harmer
9.046
972251AH1-710 GEN
Adder
80.06
228202CUMB CT
Adder
23.967
228711V2-041C
Solar/Wind Harmer
0.87
971553AH1-274 GEN
Solar/Wind Harmer
3.495
230430AE1-229_GEN
Solar/Wind Harmer
12.583
230415AB2-049 C
Solar/Wind Harmer
0.269
213497CHSTR7-9
Adder
3.86
228304LOGAN
Adder
30.698
228729W2-030 C
Solar/Wind Harmer
0.814
219623KINSLEYBEA C
Solar/Wind Harmer
0.583
213958STHWK5-6
Adder
3.702
219766PARADISE C
Solar/Wind Harmer
0.425
219291REEVESSOUT C
Solar/Wind Harmer
0.081
219912AD2-042 GEN
Solar/Wind Harmer
1.068
213560DLW11-12
Adder
3.607
219236SOUTHERNHQ C
Solar/Wind Harmer
0.089
219906AC1-017 C
Solar/Wind Harmer
0.29
219610FLORENCE C
Solar/Wind Harmer
1.783
219348LDSOLAR C
Solar/Wind Harmer
0.771
219221BRL12CT1
Adder
11.491
219223BRL12CT3
Adder
11.491
213815MOSER1-3
Adder
4.563
959561AF2-247 GEN
Solar/Wind Harmer
0.602
20716028EGP_W2-019
Solar/Wind Harmer
0.572
20720828JCB_W4-025
Solar/Wind Harmer
0.559
20715028HAN_X4-015
Solar/Wind Harmer
0.368
20636028O CRK C1
Adder
8.639
971667AH1-334 GEN
Solar/Wind Harmer
3.295
219727YARDVSOLFA C
Solar/Wind Harmer
1.083
20714528FRN_Y2-051
Solar/Wind Harmer
0.345
219276PARKLANDSO C
Solar/Wind Harmer
0.538
219918AC2-009 C
Solar/Wind Harmer
0.07
20716228APLW2-078
Solar/Wind Harmer
1.003
20720528MAN_W1-024
Solar/Wind Harmer
0.288
967451AG2-055 C O1
Solar/Wind Harmer
192.897
219612MATRIX C
Solar/Wind Harmer
0.204
218438BLK ROCK C
Solar/Wind Harmer
0.151
20635828PARLN1&2
Adder
3.627
20635928PARLN3&4
Adder
3.627
20635028RRCT1&2
Adder
12.633
20635128RRCT3&4
Adder
10.473
219908AB1-139 C
Solar/Wind Harmer
0.399
219919AE1-041 FULL
Solar/Wind Harmer
0.042
219249CENTRALDIV C
Solar/Wind Harmer
0.041
20673728F2S_V4-070
Solar/Wind Harmer
0.183
217211CAMDEN ST C
Solar/Wind Harmer
0.024
217186ESSEX_G9
Adder
15.803
217169METRODIV C
Solar/Wind Harmer
0.039
217194REDH C
Solar/Wind Harmer
0.486
20676728BRNX1-095
Solar/Wind Harmer
0.166
207510AF2-138 C
Solar/Wind Harmer
1.582
20674628WNG_W3-110
Solar/Wind Harmer
0.359
971007AG2-625 GEN
Solar/Wind Harmer
2.139
20466127PORT 5CT
Adder
21.337
20633028GILCT9
Adder
22.381
966181AG1-487 GEN
Solar/Wind Harmer
0.199
20465427SHAW CT
Adder
3.058
963071AG1-156 GEN
Solar/Wind Harmer
1.672
970095AG2-074 GEN
Solar/Wind Harmer
3.795
963161AG1-165 GEN
Solar/Wind Harmer
0.593
209025WIENIPP3
Adder
3.126
3141196NOKESVL
Solar/Wind Helper
0.957
316044AC1-158 PL1
Solar/Wind Helper
1.294
316450AC1-158 RIC
Solar/Wind Helper
0.345
316170AC1-121 GEN2
Solar/Wind Helper
0.356
3132273ORANGE
Solar/Wind Helper
0.046
3147666LOUISA
Solar/Wind Helper
0.529
238147AE2-230_GEN1
Solar/Wind Helper
0.395
238149AF1-291A_GEN
Solar/Wind Helper
0.113
966881AG1-559 GEN
Solar/Wind Helper
0.309
237061AD1-155 GEN
Solar/Wind Helper
0.043
3141906WESTMOR
Solar/Wind Helper
0.091
316473AC1-191 GEN
Solar/Wind Helper
1.387
316404AE1-155 C
Solar/Wind Helper
1.915
316484AD2-074 GEN
Solar/Wind Helper
0.438
316280AD1-041 GEN
Solar/Wind Helper
0.759
316156AD2-030 GEN
Solar/Wind Helper
0.341
3142946ENON
Solar/Wind Helper
0.075
316382AG1-145 C
Solar/Wind Helper
0.303
315839AE2-212 C
Solar/Wind Helper
0.302
316313AB2-026
Solar/Wind Helper
0.342
316258AE1-075 C
Solar/Wind Helper
0.308
316405AF2-144 C
Solar/Wind Helper
0.256
3145336SMITFLD
Solar/Wind Helper
0.09
315773AC2-141 GEN
Solar/Wind Helper
4.828
3144536CHRHLND
Solar/Wind Helper
0.034
3144873MCLAUGH
Solar/Wind Helper
0.006
3146456SLIGO L269
Solar/Wind Helper
0.224
316320Y1-086
Solar/Wind Helper
0.1
316435W1029_GEN3
Solar/Wind Helper
0.901
3146516WINFALL
Solar/Wind Helper
0.223
3146626S HERTFORD
Solar/Wind Helper
0.223
238221AF1-254 C O1
Solar/Wind Helper
0.219
3145273HOLLAND
Solar/Wind Helper
0.167
200052ROCKSP 1
50/50
4.882
200053ROCKSP 2
50/50
4.777
233923SMA
Solar/Wind Harmer
8.777
232912OH NUG1
Adder
16.691
232913OH NUG2
Adder
16.468
233990AG1-397 GEN
Solar/Wind Harmer
0.104
234033AF1-007_GEN
Solar/Wind Harmer
44.176
232904IR4
Adder
152.746
232432Z2-076 GEN
Solar/Wind Harmer
0.25
232920IR10
Adder
5.97
233955AB2-172 GEN
Solar/Wind Harmer
9.439
233973AC2-185 C
Solar/Wind Harmer
6.815
232813VAUGHN
Adder
1.106
233968AD2-076_GEN
Solar/Wind Harmer
12.381
970597AG2-380 GEN
Solar/Wind Harmer
7.774
232436AB1-176 C
Solar/Wind Harmer
0.427
231906DC3 NUG
Adder
26.081
231902DC CT7
Adder
20.85
231907DC10
Adder
6.511
971983AH1-536 GEN
Solar/Wind Harmer
13.913
233935AB2-179 C
Solar/Wind Harmer
4.55
231919CHRIST1
Adder
7.814
231920CHRIST2
Adder
7.64
970453AG2-297 GEN
Solar/Wind Harmer
4.019
228260V4-054C
Solar/Wind Harmer
1.477
228309CCLP NUG
Adder
37.095
228309CCLP NUG
Adder
35.286
972141AH1-641 GEN
Solar/Wind Harmer
4.119
964001AG1-254 GEN
Solar/Wind Harmer
2.906
971011AG2-627 GEN
Solar/Wind Harmer
10.894
971535AH1-265 GEN
Solar/Wind Harmer
6.027
227927V4-067C
Solar/Wind Harmer
0.279
228754AB1-001 C
Solar/Wind Harmer
0.196
219137THOSOLAR C
Solar/Wind Harmer
1.664
213942SCHUYLKILL
Adder
4.851
213942SCHUYLKILL
Adder
3.71
213957STHWK3-4
Adder
3.702
213957STHWK3-4
Adder
3.702
219272CLEANLIGHT C
Solar/Wind Harmer
0.246
219914AD2-027 C
Solar/Wind Harmer
0.805
219688LUMSOLAR_S C
Solar/Wind Harmer
0.271
213561DLWR9-10
Adder
4.717
213561DLWR9-10
Adder
3.607
219607WPEMNERT C
Solar/Wind Harmer
0.54
219224BRL12CT4
Adder
11.491
214067T20SOLAR
Solar/Wind Harmer
0.316
213611FALLS1-3
Adder
4.415
213611FALLS1-3
Adder
4.415
20717128DIX_Z2-102
Solar/Wind Harmer
1.623
20715728PEM_W1-119
Solar/Wind Harmer
0.656
20715828PEM_W1-120
Solar/Wind Harmer
0.656
970025AG2-016 GEN
Solar/Wind Harmer
3.435
971189AH1-054 GEN
Solar/Wind Harmer
1.428
207459AE1-142 C O1
Solar/Wind Harmer
1.267
219620RIDERU C
Solar/Wind Harmer
0.064
20714328BYD_X4-031
Solar/Wind Harmer
0.324
20714428HOW_X1-037
Solar/Wind Harmer
1.413
971521AH1-258 GEN
Solar/Wind Harmer
3.038
20720428HOL_W1-112
Solar/Wind Harmer
0.387
20635928PARLN3&4
Adder
8.008
218455CINNBAY_CGEN
Adder
1.959
218526CNTRALGAS2 C
Solar/Wind Harmer
0.393
218524CNTRALGAS1 C
Solar/Wind Harmer
0.391
20675528CPH_W2-050
Solar/Wind Harmer
0.489
218404KENILWRTH C
Adder
1.301
217167KRNY_14
Adder
9.185
217086KRNY_131
Adder
9.107
217147KRNY_1212
Adder
8.737
217147KRNY_1212
Adder
8.581
217146KRNY_1234
Adder
8.561
217146KRNY_1234
Adder
8.503
966261AG1-495 GEN
Solar/Wind Harmer
1.648
20676328BVR_Y1-020
Solar/Wind Harmer
0.296
207511W3-106 GEN
Solar/Wind Harmer
0.583
207530AG1-191 GEN
Solar/Wind Harmer
1.214
20674828DL_W4-046
Solar/Wind Harmer
0.549
971009AG2-626 GEN
Solar/Wind Harmer
1.365
207408W3-077 C
Solar/Wind Harmer
0.414
20675728RH_W2-091
Solar/Wind Harmer
0.279
966421AG1-511 GEN
Solar/Wind Harmer
7.025
20675928HOL_W4-097
Solar/Wind Harmer
0.106
207484AF2-139 C O1
Solar/Wind Harmer
0.408
20675128HRM_W1-127
Solar/Wind Harmer
0.136
20462827N BANGR8
Adder
0.568
209116AE2-175 GEN
Solar/Wind Harmer
3.022
961261AF2-417 GEN
Solar/Wind Harmer
0.669
209026WIENIPP4
Adder
3.159
3138216PACIFIC
Solar/Wind Helper
0.041
316411AF1-147_GEN1
Solar/Wind Helper
0.817
316415AF1-147_GEN2
Solar/Wind Helper
0.817
3141426STAFORD
Solar/Wind Helper
0.051
316164AC1-076 GEN
Solar/Wind Helper
1.109
238152AF2-075_GEN
Solar/Wind Helper
0.565
23546401DTGZ2-030
Solar/Wind Helper
0.072
316223AC1-118
Solar/Wind Helper
0.347
3141813NORNECK
Solar/Wind Helper
0.227
316312AB1-027
Solar/Wind Helper
0.431
3141783LANCAST
Solar/Wind Helper
0.136
3141783LANCAST
Solar/Wind Helper
0.091
3138133OCRAN
Solar/Wind Helper
0.068
3141913WHIT STONE
Solar/Wind Helper
0.226
316233AE1-074 FULL
Solar/Wind Helper
0.345
316059AD1-063 C
Solar/Wind Helper
0.228
3143873LANEXA
Solar/Wind Helper
0.136
315662AE1-191 GEN
Solar/Wind Helper
1.215
315666AE1-190 GEN
Solar/Wind Helper
0.304
957601AF2-054 GEN
Solar/Wind Helper
0.303
3141873WAN 176
Solar/Wind Helper
0.045
957831AF2-077 GEN
Solar/Wind Helper
0.304
316132AB2-190 GEN1
Solar/Wind Helper
1.286
316369SG1_INVT
Solar/Wind Helper
1.081
3143316POE
Solar/Wind Helper
0.888
316349AD2-085 GEN
Solar/Wind Helper
1.023
319010AE1-072 C
Solar/Wind Helper
2.555
316305AF2-043 C
Solar/Wind Helper
0.301
313526AB2-022
Solar/Wind Helper
0.34
3146486SUNBURY
Solar/Wind Helper
0.223
3146486SUNBURY
Solar/Wind Helper
0.223
316321Z2-027
Solar/Wind Helper
0.34
3145176PASQUOTANK
Solar/Wind Helper
0.138
316315AB2-025 C
Solar/Wind Helper
0.339
HAMLETPJM->LTFIMP_HAMLET
CLTF
5.425
G-007ALTFEXP_G-007A->PJM
CMTX
54.936
CBM NorthLTFEXP_CBM-N->PJM
CBM
62.929
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
4.799
BlueGrassPJM->LTFIMP_BlueG
CLTF
14.946
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
135.306
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.24
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
22.427

Details for PCHBTM1N-CHAN 500.0 kV Ckt 1 line l/o PJM_500_BG_P4_5_CNSTN_B_SRT-A


Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1N-CHAN 500.0 kV Ckt 1 line
Contingency Name:
PJM_500_BG_P4_5_CNSTN_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:149.62 %
Rating:3486.0 MVA
Rating Type:B
MVA to Mitigate:5215.61
MW Contribution:10.92
Bus #Bus NameTypeMW Contribution
200035PCHBTM 3
50/50
41.146
200201DELTA2 CT2
50/50
6.892
200034PCHBTM 2
50/50
40.101
200205Y1-065-CTG2
50/50
7.745
233987AB2-037 GEN
Solar/Wind Harmer
21.635
232926CRISFLD1
Adder
3.718
233901CHERRYDALE C
Solar/Wind Harmer
2.133
232408W1-005 C
Solar/Wind Harmer
1.897
232410W1-006 C
Solar/Wind Harmer
1.897
232918OH NUG7
Adder
16.62
232905CHERITON_25
Adder
4.648
972069AH1-584 GEN
Solar/Wind Harmer
16.965
972071AH1-585 GEN
Solar/Wind Harmer
16.965
971747AH1-380 GEN
Solar/Wind Harmer
6.786
970545AG2-347 GEN
Solar/Wind Harmer
123.926
231940T-011
Adder
1.412
971149AH1-027 GEN
Solar/Wind Harmer
6.407
233946AB2-136 GEN
Solar/Wind Harmer
7.555
234036AF2-325 C
Solar/Wind Harmer
1.735
234041AC1-190 GEN
Solar/Wind Harmer
16.944
233939AC1-091 C
Solar/Wind Harmer
1.661
233970AC1-092 C
Solar/Wind Harmer
1.661
232899W1-062
Adder
18.17
233984AB2-036 GEN
Solar/Wind Harmer
23.412
232424Y1-079 C
Solar/Wind Harmer
1.057
234014AF1-036_GEN
Solar/Wind Harmer
5.066
231131BLOOM ENRGY
Adder
8.135
233944AB2-135 GEN
Solar/Wind Harmer
9.769
233933AB2-153 GEN
Solar/Wind Harmer
2.097
232416X2-083
Adder
0.823
228251CARLLS#4
Adder
0.91
230433AD2-135 GEN
Solar/Wind Harmer
0.144
230422AE1-104_GEN1
Solar/Wind Harmer
48.112
230425AE1-104_GEN2
Solar/Wind Harmer
48.112
228307PCLP GT
Adder
17.178
228304LOGAN
Adder
34.221
213589EDDYSTN4
Adder
112.771
213587EDDYSTN3
Adder
112.724
230407AD2-065 C
Solar/Wind Harmer
0.186
972233AH1-701 GEN
Adder
5.904
219921AF1-264
Solar/Wind Harmer
0.197
219615MILLCREEK C
Solar/Wind Harmer
0.311
213815MOSER1-3
Adder
4.574
213815MOSER1-3
Adder
4.574
213535CROYDN11
Adder
13.184
20716428NHV_W2-082
Solar/Wind Harmer
2.197
207500AE2-000G1
Solar/Wind Harmer
38.61
207497AE2-000G2
Solar/Wind Harmer
38.61
207507AE2-000G3
Solar/Wind Harmer
38.61
20636128O CRK C2
Adder
7.899
963401AG1-189 GEN
Solar/Wind Harmer
1.402
963391AG1-188 GEN
Solar/Wind Harmer
2.33
20714928UPF_X1-085
Solar/Wind Harmer
0.492
219114HARTZY_C
Solar/Wind Harmer
1.005
20628028LAKEHURS
Adder
1.14
219817TRENTONSOL C
Solar/Wind Harmer
1.271
20641628MLH_W1-032
Solar/Wind Harmer
0.335
20720628TIN_W1-124
Solar/Wind Harmer
1.137
20716928W4-060COL
Solar/Wind Harmer
0.787
924131AB2-057 GEN
Solar/Wind Harmer
1.112
218440SUMMTASSOC C
Solar/Wind Harmer
0.135
218418LINDEN_G5
Adder
17.832
218419LINDEN_G6
Adder
17.832
972260AH1-715 GEN1
Adder
14.279
20673828FLE_V3-070
Solar/Wind Harmer
0.474
219036LINDEN_G7
Adder
17.093
219035LINDEN_G8
Adder
16.849
972261AH1-715 GEN2
Adder
16.362
207442AE1-156 GEN
Solar/Wind Harmer
0.759
20676128MHD_W3-029
Solar/Wind Harmer
0.487
217081WEATEXAS C
Solar/Wind Harmer
0.087
217202FBANKSOLAR C
Solar/Wind Harmer
0.074
217201HACKENSOLA C
Solar/Wind Harmer
0.073
972237AH1-703 GEN
Adder
10.04
217206BARNGR HS C
Solar/Wind Harmer
0.031
217086KRNY_131
Adder
9.235
217083KRNY_132
Adder
9.156
20671828STAW2-080
Solar/Wind Harmer
0.103
217204WCALDSOLAR C
Solar/Wind Harmer
0.072
20674528F3S_W2-016
Solar/Wind Harmer
1.362
20676228FRD_X1-012
Solar/Wind Harmer
0.525
207471AF2-354 C
Solar/Wind Harmer
0.434
20674928WA_W3-044
Solar/Wind Harmer
0.409
964851AG1-348 GEN
Solar/Wind Harmer
1.471
20634528N27_Y2-018
Solar/Wind Harmer
0.225
20465127PORT CT
Adder
3.215
20674128FR_U2-059
Solar/Wind Harmer
0.147
966111AG1-480 GEN
Solar/Wind Harmer
0.069
966111AG1-480 GEN
Solar/Wind Harmer
2.62
211065PSPA IPP
Solar/Wind Harmer
0.317
211065PSPA IPP
Solar/Wind Harmer
0.317
209029WAYMART-WD
Solar/Wind Harmer
1.798
209009PEIP 2
Adder
4.881
209010PEIP 1
Adder
2.212
209010PEIP 1
Adder
0.324
208972BECR K09
Solar/Wind Harmer
0.62
238175AF1-290_GEN
Solar/Wind Helper
0.125
238169AE2-226 GEN1
Solar/Wind Helper
0.573
238170AE2-226 GEN2
Solar/Wind Helper
0.573
315651AD1-115 GEN
Solar/Wind Helper
0.785
316447AC1-158 HLD
Solar/Wind Helper
2.854
966001AG1-469 GEN
Solar/Wind Helper
0.247
235020AA1-095 C
Solar/Wind Helper
0.043
23777901MDS_W4-102
Solar/Wind Helper
0.144
316468AD1-105 GEN
Solar/Wind Helper
1.137
316077AC2-138 C
Solar/Wind Helper
0.214
966871AG1-558 GEN
Solar/Wind Helper
0.307
316487AF1-042 GEN
Solar/Wind Helper
0.23
316075AC2-137 C
Solar/Wind Helper
0.345
3143526WINTERP
Solar/Wind Helper
1.178
3142946ENON
Solar/Wind Helper
0.023
316240AF1-291 C
Solar/Wind Helper
0.303
316033AB2-134 GEN
Solar/Wind Helper
0.775
315697AD1-025 GEN
Solar/Wind Helper
2.576
316236AE1-162_GEN
Solar/Wind Helper
0.302
316036AC1-147 C
Solar/Wind Helper
0.342
3142956BIRDNECK
Solar/Wind Helper
0.151
316316AC1-027 C
Solar/Wind Helper
0.354
316185AD1-033 GEN
Solar/Wind Helper
1.055
3145506HICKORY
Solar/Wind Helper
0.897
3145506HICKORY
Solar/Wind Helper
0.538
3145506HICKORY
Solar/Wind Helper
0.135
316339AD2-160 GEN
Solar/Wind Helper
0.854
316018AA1-139 ULT2
Solar/Wind Helper
0.964
316017AA1-139 ULT1
Solar/Wind Helper
1.025
3137176SLIGO L2192
Solar/Wind Helper
0.892
3130086AYDLETT
Solar/Wind Helper
0.896
3146386ELIZ CT
Solar/Wind Helper
0.224
316431W1029_GEN1
Solar/Wind Helper
0.903
316433W1029_GEN2
Solar/Wind Helper
0.903
3146516WINFALL
Solar/Wind Helper
0.223
3146516WINFALL
Solar/Wind Helper
0.223
3146516WINFALL
Solar/Wind Helper
0.223
3144356SAPONY
Solar/Wind Helper
0.4
3146626S HERTFORD
Solar/Wind Helper
0.223
3146626S HERTFORD
Solar/Wind Helper
0.223
237034AC2-136 C
Solar/Wind Helper
0.184
3132123MT JACKSON
Solar/Wind Helper
0.698
315742AE1-103 GEN
Solar/Wind Helper
0.359
200192DELTA CT1
50/50
3.851
200194DELTA CT3
50/50
3.851
200204Y1-065-CTG1
50/50
7.745
200054ROCKSP 3
50/50
4.941
233998TM1NIN_3.36
Solar/Wind Harmer
2.4
232404W1-003 C
Solar/Wind Harmer
1.897
232917OH NUG6
Adder
16.658
232915OH NUG4
Adder
16.62
232428Y3-058 C
Solar/Wind Harmer
1.581
971195AH1-057 GEN
Solar/Wind Harmer
2.073
232434Z2-077 GEN
Solar/Wind Harmer
0.474
232919VN10
Adder
5.315
965821AG1-450 GEN
Solar/Wind Harmer
9.858
232901NORTHST
Adder
15.755
232426Y1-080 FULL
Solar/Wind Harmer
0.362
970277AG2-181 GEN
Solar/Wind Harmer
9.494
233964AF2-378 GEN
Solar/Wind Harmer
0.242
972177AH1-672 GEN
Solar/Wind Harmer
25.422
233972AC1-094 C
Solar/Wind Harmer
1.254
232900DEMECSMY
Adder
17.429
233954AC2-188 GEN
Solar/Wind Harmer
2.126
233950AC2-186 GEN
Solar/Wind Harmer
1.063
232910NRG_G1
Adder
16.233
234012AE2-112_GEN
Solar/Wind Harmer
4.306
232422X3-066 FULL
Solar/Wind Harmer
0.468
233930AB2-032 GEN
Solar/Wind Harmer
1.554
233915AB1-141 GEN
Solar/Wind Harmer
1.847
231918WEST 1
Adder
5.968
231917EM10
Adder
4.131
228206SHRMN CT
Adder
24.059
228732V1-021 C
Adder
0.273
945431AF1-208 GEN
Solar/Wind Harmer
12.43
970997AG2-616 GEN
Solar/Wind Harmer
13.764
228351V2-046C
Solar/Wind Harmer
2.885
230511AF1-262
Solar/Wind Harmer
0.261
228728W1-130C
Solar/Wind Harmer
0.944
213497CHSTR7-9
Adder
3.87
213497CHSTR7-9
Adder
3.87
230434AG1-499 GEN
Solar/Wind Harmer
0.822
219258KINSLEYDEP C
Solar/Wind Harmer
0.442
213958STHWK5-6
Adder
3.712
219904AC1-010 C
Solar/Wind Harmer
0.513
218660EHAMPSOLAR C
Solar/Wind Harmer
0.235
219686LUMSOLAR_N C
Solar/Wind Harmer
0.272
219287REEVESEAST C
Solar/Wind Harmer
1.804
213560DLW11-12
Adder
3.617
219907AC1-030 C
Solar/Wind Harmer
0.184
219304NAMERICA C
Solar/Wind Harmer
0.401
219222BRL12CT2
Adder
11.522
213611FALLS1-3
Adder
4.427
20720728JCB_W1-129
Solar/Wind Harmer
0.369
207522AF2-254 C
Solar/Wind Harmer
1.772
214194N WALES4
Adder
1.052
207487AE2-000G4
Solar/Wind Harmer
38.61
207445AB1-138_GEN
Solar/Wind Harmer
0.695
20628028LAKEHURS
Adder
2.255
963711AG1-223 GEN
Solar/Wind Harmer
1.738
20714828MDF_W3-079
Solar/Wind Harmer
0.359
219680HOPEWELLV C1
Solar/Wind Harmer
0.087
207454AA2-184 E
Solar/Wind Harmer
1.141
20715228NPK_W1-113
Solar/Wind Harmer
0.489
20742028HF_AC1-207
Solar/Wind Harmer
0.888
217197RE CRAN C
Solar/Wind Harmer
0.596
20635828PARLN1&2
Adder
8.033
20635028RRCT1&2
Adder
12.476
20635128RRCT3&4
Adder
12.043
218428ETC SOLAR C
Solar/Wind Harmer
0.038
217213AMBOY SO C
Solar/Wind Harmer
0.133
972275AH1-722 GEN
Adder
32.782
218449LINSOLAR C
Solar/Wind Harmer
1.028
207528AF2-192 GEN
Solar/Wind Harmer
0.565
20673628F1S_V4-069
Solar/Wind Harmer
0.183
20675428EAM_W2-061
Solar/Wind Harmer
0.193
20676428JCR_X2-075
Solar/Wind Harmer
0.347
217209CENTRL HS C
Solar/Wind Harmer
0.045
217121ECCF
Adder
0.431
217083KRNY_132
Adder
9.215
217208PARK ELE C
Solar/Wind Harmer
0.025
207439AE1-081 C O1
Solar/Wind Harmer
0.054
20674328GAR_V4-001
Solar/Wind Harmer
0.097
20675828AU_W4-064
Solar/Wind Harmer
0.152
971519AH1-257 GEN
Solar/Wind Harmer
2.099
207518AF1-320_GEN
Solar/Wind Harmer
2.987
207437AD2-070 GEN
Solar/Wind Harmer
0.244
20465127PORT CT
Adder
2.423
20671928W4-073
Solar/Wind Harmer
0.347
966181AG1-487 GEN
Solar/Wind Harmer
2.974
208909MACR G3
Adder
122.728
209010PEIP 1
Adder
0.402
961301AF2-421 GEN
Solar/Wind Harmer
0.596
963151AG1-164 GEN
Solar/Wind Harmer
0.596
209023WIENIPP1
Adder
6.422
209025WIENIPP3
Adder
3.206
316006AB2-029 C
Solar/Wind Helper
0.113
316045AC1-158 PL2
Solar/Wind Helper
4.152
316254AC1-120 GEN1
Solar/Wind Helper
1.071
3147666LOUISA
Solar/Wind Helper
0.923
316192AB2-158 GEN
Solar/Wind Helper
1.549
238148AE2-230_GEN2
Solar/Wind Helper
0.398
316337AD2-073 GEN
Solar/Wind Helper
0.346
964211AG1-282 GEN
Solar/Wind Helper
0.307
3141726DUNNSVL
Solar/Wind Helper
0.91
3142416OLDCHRC
Solar/Wind Helper
0.59
3142416OLDCHRC
Solar/Wind Helper
0.226
3138133OCRAN
Solar/Wind Helper
0.136
3143526WINTERP
Solar/Wind Helper
1.178
3141766HARMONY
Solar/Wind Helper
0.045
3143226MDLTHAN
Solar/Wind Helper
0.227
3142433PROV 92
Solar/Wind Helper
0.906
3142543TWELFTH
Solar/Wind Helper
0.022
316159AE1-175 C
Solar/Wind Helper
0.342
316458AB2-190 GEN2
Solar/Wind Helper
1.288
3145336SMITFLD
Solar/Wind Helper
0.899
316294AC1-161 GEN
Solar/Wind Helper
4.111
316381AD1-082 GEN
Solar/Wind Helper
1.163
316375AC2-012 GEN
Solar/Wind Helper
0.588
316336AC2-165 C
Solar/Wind Helper
1.21
316072AD1-144
Solar/Wind Helper
0.256
316388AE2-253 GEN
Solar/Wind Helper
0.854
3146456SLIGO L269
Solar/Wind Helper
0.224
316246AF1-032 C
Solar/Wind Helper
0.256
3146516WINFALL
Solar/Wind Helper
0.724
3146516WINFALL
Solar/Wind Helper
0.223
315800Z1-036_GEN1
Solar/Wind Helper
1.226
3130156CHOWAN
Solar/Wind Helper
0.223
200200DELTA2 CT1
50/50
6.892
200193DELTA CT2
50/50
3.851
200203Y1-065-STG
50/50
13.431
200055ROCKSP 4
50/50
4.837
232907VN8
Adder
56.91
233996TM1833_GEN
Solar/Wind Harmer
2.4
233997TMININ_4.2
Solar/Wind Harmer
2.4
232406W1-004 FULL
Solar/Wind Harmer
1.897
233940AF2-379 C
Solar/Wind Harmer
0.354
232914OH NUG3
Adder
16.732
232916OH NUG5
Adder
16.732
232921TASLEY2G
Adder
9.779
972073AH1-586 GEN
Solar/Wind Harmer
17.754
233990AG1-397 GEN
Solar/Wind Harmer
2.173
233900O-025 C
Adder
2.231
234015AF2-250 C
Solar/Wind Harmer
0.228
972133AH1-634 GEN
Solar/Wind Harmer
18.777
233994AC2-023 GEN
Solar/Wind Harmer
5.092
960671AF2-358 GEN
Solar/Wind Harmer
33.911
232417X3-008 C
Solar/Wind Harmer
3.785
233971AC1-093 C
Solar/Wind Harmer
1.483
970695AG2-447 GEN
Solar/Wind Harmer
6.774
233952AC2-187 GEN
Solar/Wind Harmer
2.126
233918AB1-142 GEN
Solar/Wind Harmer
1.847
233982AB2-133 GEN
Solar/Wind Harmer
9.07
972251AH1-710 GEN
Adder
80.256
228202CUMB CT
Adder
24.029
228711V2-041C
Solar/Wind Harmer
0.873
971553AH1-274 GEN
Solar/Wind Harmer
3.504
230430AE1-229_GEN
Solar/Wind Harmer
12.615
230415AB2-049 C
Solar/Wind Harmer
0.27
213497CHSTR7-9
Adder
3.87
228304LOGAN
Adder
30.778
228729W2-030 C
Solar/Wind Harmer
0.816
219623KINSLEYBEA C
Solar/Wind Harmer
0.584
213958STHWK5-6
Adder
3.712
219766PARADISE C
Solar/Wind Harmer
0.426
219291REEVESSOUT C
Solar/Wind Harmer
0.081
219912AD2-042 GEN
Solar/Wind Harmer
1.071
213560DLW11-12
Adder
3.617
219236SOUTHERNHQ C
Solar/Wind Harmer
0.09
219906AC1-017 C
Solar/Wind Harmer
0.291
219610FLORENCE C
Solar/Wind Harmer
1.788
219348LDSOLAR C
Solar/Wind Harmer
0.773
219221BRL12CT1
Adder
11.522
219223BRL12CT3
Adder
11.522
213815MOSER1-3
Adder
4.574
959561AF2-247 GEN
Solar/Wind Harmer
0.604
20716028EGP_W2-019
Solar/Wind Harmer
0.574
20720828JCB_W4-025
Solar/Wind Harmer
0.56
20715028HAN_X4-015
Solar/Wind Harmer
0.369
20636028O CRK C1
Adder
8.663
971667AH1-334 GEN
Solar/Wind Harmer
3.305
219727YARDVSOLFA C
Solar/Wind Harmer
1.086
20714528FRN_Y2-051
Solar/Wind Harmer
0.346
219276PARKLANDSO C
Solar/Wind Harmer
0.539
219918AC2-009 C
Solar/Wind Harmer
0.07
20716228APLW2-078
Solar/Wind Harmer
1.006
20720528MAN_W1-024
Solar/Wind Harmer
0.289
967451AG2-055 C O1
Solar/Wind Harmer
193.47
219612MATRIX C
Solar/Wind Harmer
0.204
218438BLK ROCK C
Solar/Wind Harmer
0.151
20635828PARLN1&2
Adder
3.638
20635928PARLN3&4
Adder
3.638
20635028RRCT1&2
Adder
12.671
20635128RRCT3&4
Adder
10.505
219908AB1-139 C
Solar/Wind Harmer
0.4
219919AE1-041 FULL
Solar/Wind Harmer
0.042
219249CENTRALDIV C
Solar/Wind Harmer
0.041
20673728F2S_V4-070
Solar/Wind Harmer
0.183
217211CAMDEN ST C
Solar/Wind Harmer
0.024
217186ESSEX_G9
Adder
15.855
217169METRODIV C
Solar/Wind Harmer
0.039
217194REDH C
Solar/Wind Harmer
0.487
20676728BRNX1-095
Solar/Wind Harmer
0.167
207510AF2-138 C
Solar/Wind Harmer
1.587
20674628WNG_W3-110
Solar/Wind Harmer
0.36
971007AG2-625 GEN
Solar/Wind Harmer
2.147
20466127PORT 5CT
Adder
21.421
20633028GILCT9
Adder
22.474
966181AG1-487 GEN
Solar/Wind Harmer
0.199
20465427SHAW CT
Adder
3.07
963071AG1-156 GEN
Solar/Wind Harmer
1.68
970095AG2-074 GEN
Solar/Wind Harmer
3.812
963161AG1-165 GEN
Solar/Wind Harmer
0.596
209025WIENIPP3
Adder
3.141
3141196NOKESVL
Solar/Wind Helper
0.959
316044AC1-158 PL1
Solar/Wind Helper
1.297
316450AC1-158 RIC
Solar/Wind Helper
0.346
316170AC1-121 GEN2
Solar/Wind Helper
0.357
3132273ORANGE
Solar/Wind Helper
0.046
3147666LOUISA
Solar/Wind Helper
0.531
238147AE2-230_GEN1
Solar/Wind Helper
0.396
238149AF1-291A_GEN
Solar/Wind Helper
0.113
966881AG1-559 GEN
Solar/Wind Helper
0.31
237061AD1-155 GEN
Solar/Wind Helper
0.043
3141906WESTMOR
Solar/Wind Helper
0.091
316473AC1-191 GEN
Solar/Wind Helper
1.39
316404AE1-155 C
Solar/Wind Helper
1.919
316484AD2-074 GEN
Solar/Wind Helper
0.439
316280AD1-041 GEN
Solar/Wind Helper
0.761
316156AD2-030 GEN
Solar/Wind Helper
0.342
3142946ENON
Solar/Wind Helper
0.076
316382AG1-145 C
Solar/Wind Helper
0.304
315839AE2-212 C
Solar/Wind Helper
0.303
316313AB2-026
Solar/Wind Helper
0.343
316258AE1-075 C
Solar/Wind Helper
0.308
316405AF2-144 C
Solar/Wind Helper
0.257
3145336SMITFLD
Solar/Wind Helper
0.09
315773AC2-141 GEN
Solar/Wind Helper
4.839
3144536CHRHLND
Solar/Wind Helper
0.034
3144873MCLAUGH
Solar/Wind Helper
0.006
3146456SLIGO L269
Solar/Wind Helper
0.224
316320Y1-086
Solar/Wind Helper
0.1
316435W1029_GEN3
Solar/Wind Helper
0.903
3146516WINFALL
Solar/Wind Helper
0.223
3146626S HERTFORD
Solar/Wind Helper
0.223
3145273HOLLAND
Solar/Wind Helper
0.167
238221AF1-254 C O1
Solar/Wind Helper
0.22
3146376EDENTON
Solar/Wind Helper
0.223
200202DELTA2 ST
50/50
11.696
200195DELTA ST
50/50
5.951
200052ROCKSP 1
50/50
4.892
200053ROCKSP 2
50/50
4.787
233923SMA
Solar/Wind Harmer
8.798
232912OH NUG1
Adder
16.732
232913OH NUG2
Adder
16.509
233990AG1-397 GEN
Solar/Wind Harmer
0.104
234033AF1-007_GEN
Solar/Wind Harmer
44.285
232904IR4
Adder
153.122
232432Z2-076 GEN
Solar/Wind Harmer
0.25
232920IR10
Adder
5.985
233955AB2-172 GEN
Solar/Wind Harmer
9.462
233973AC2-185 C
Solar/Wind Harmer
6.832
232813VAUGHN
Adder
1.109
233968AD2-076_GEN
Solar/Wind Harmer
12.412
970597AG2-380 GEN
Solar/Wind Harmer
7.794
232436AB1-176 C
Solar/Wind Harmer
0.429
231906DC3 NUG
Adder
26.147
231902DC CT7
Adder
20.903
231907DC10
Adder
6.528
971983AH1-536 GEN
Solar/Wind Harmer
13.949
233935AB2-179 C
Solar/Wind Harmer
4.562
231919CHRIST1
Adder
7.834
231920CHRIST2
Adder
7.66
970453AG2-297 GEN
Solar/Wind Harmer
4.03
228260V4-054C
Solar/Wind Harmer
1.48
228309CCLP NUG
Adder
37.192
228309CCLP NUG
Adder
35.378
972141AH1-641 GEN
Solar/Wind Harmer
4.129
964001AG1-254 GEN
Solar/Wind Harmer
2.914
971011AG2-627 GEN
Solar/Wind Harmer
10.923
971535AH1-265 GEN
Solar/Wind Harmer
6.043
227927V4-067C
Solar/Wind Harmer
0.28
228754AB1-001 C
Solar/Wind Harmer
0.196
219137THOSOLAR C
Solar/Wind Harmer
1.669
213942SCHUYLKILL
Adder
4.864
213942SCHUYLKILL
Adder
3.72
213957STHWK3-4
Adder
3.712
213957STHWK3-4
Adder
3.712
219272CLEANLIGHT C
Solar/Wind Harmer
0.247
219914AD2-027 C
Solar/Wind Harmer
0.807
219688LUMSOLAR_S C
Solar/Wind Harmer
0.271
213561DLWR9-10
Adder
4.729
213561DLWR9-10
Adder
3.617
219607WPEMNERT C
Solar/Wind Harmer
0.541
219224BRL12CT4
Adder
11.522
214067T20SOLAR
Solar/Wind Harmer
0.317
213611FALLS1-3
Adder
4.427
213611FALLS1-3
Adder
4.427
20717128DIX_Z2-102
Solar/Wind Harmer
1.628
20715728PEM_W1-119
Solar/Wind Harmer
0.658
20715828PEM_W1-120
Solar/Wind Harmer
0.658
970025AG2-016 GEN
Solar/Wind Harmer
3.445
971189AH1-054 GEN
Solar/Wind Harmer
1.432
207459AE1-142 C O1
Solar/Wind Harmer
1.271
219620RIDERU C
Solar/Wind Harmer
0.064
20714328BYD_X4-031
Solar/Wind Harmer
0.325
20714428HOW_X1-037
Solar/Wind Harmer
1.418
971521AH1-258 GEN
Solar/Wind Harmer
3.047
20720428HOL_W1-112
Solar/Wind Harmer
0.388
20635928PARLN3&4
Adder
8.033
218455CINNBAY_CGEN
Adder
1.965
218526CNTRALGAS2 C
Solar/Wind Harmer
0.394
218524CNTRALGAS1 C
Solar/Wind Harmer
0.392
20675528CPH_W2-050
Solar/Wind Harmer
0.49
218404KENILWRTH C
Adder
1.305
217167KRNY_14
Adder
9.215
217086KRNY_131
Adder
9.137
217147KRNY_1212
Adder
8.765
217147KRNY_1212
Adder
8.609
217146KRNY_1234
Adder
8.589
217146KRNY_1234
Adder
8.53
966261AG1-495 GEN
Solar/Wind Harmer
1.654
20676328BVR_Y1-020
Solar/Wind Harmer
0.297
207511W3-106 GEN
Solar/Wind Harmer
0.585
207530AG1-191 GEN
Solar/Wind Harmer
1.218
20674828DL_W4-046
Solar/Wind Harmer
0.551
971009AG2-626 GEN
Solar/Wind Harmer
1.37
207408W3-077 C
Solar/Wind Harmer
0.416
20675728RH_W2-091
Solar/Wind Harmer
0.281
966421AG1-511 GEN
Solar/Wind Harmer
7.052
20675928HOL_W4-097
Solar/Wind Harmer
0.106
207484AF2-139 C O1
Solar/Wind Harmer
0.409
20675128HRM_W1-127
Solar/Wind Harmer
0.136
20462827N BANGR8
Adder
0.57
209116AE2-175 GEN
Solar/Wind Harmer
3.034
961261AF2-417 GEN
Solar/Wind Harmer
0.672
209026WIENIPP4
Adder
3.173
3138216PACIFIC
Solar/Wind Helper
0.041
316411AF1-147_GEN1
Solar/Wind Helper
0.818
316415AF1-147_GEN2
Solar/Wind Helper
0.818
316164AC1-076 GEN
Solar/Wind Helper
1.111
3141426STAFORD
Solar/Wind Helper
0.051
238152AF2-075_GEN
Solar/Wind Helper
0.566
23546401DTGZ2-030
Solar/Wind Helper
0.072
316223AC1-118
Solar/Wind Helper
0.348
3141813NORNECK
Solar/Wind Helper
0.228
316312AB1-027
Solar/Wind Helper
0.432
3141783LANCAST
Solar/Wind Helper
0.136
3141783LANCAST
Solar/Wind Helper
0.091
3138133OCRAN
Solar/Wind Helper
0.068
3141913WHIT STONE
Solar/Wind Helper
0.227
316233AE1-074 FULL
Solar/Wind Helper
0.346
316059AD1-063 C
Solar/Wind Helper
0.228
315662AE1-191 GEN
Solar/Wind Helper
1.218
315666AE1-190 GEN
Solar/Wind Helper
0.304
957601AF2-054 GEN
Solar/Wind Helper
0.304
3143873LANEXA
Solar/Wind Helper
0.136
3141873WAN 176
Solar/Wind Helper
0.045
957831AF2-077 GEN
Solar/Wind Helper
0.305
316132AB2-190 GEN1
Solar/Wind Helper
1.288
316369SG1_INVT
Solar/Wind Helper
1.084
3143316POE
Solar/Wind Helper
0.89
316349AD2-085 GEN
Solar/Wind Helper
1.025
319010AE1-072 C
Solar/Wind Helper
2.561
316305AF2-043 C
Solar/Wind Helper
0.301
313526AB2-022
Solar/Wind Helper
0.341
3146486SUNBURY
Solar/Wind Helper
0.224
3146486SUNBURY
Solar/Wind Helper
0.224
316321Z2-027
Solar/Wind Helper
0.341
3145176PASQUOTANK
Solar/Wind Helper
0.139
316315AB2-025 C
Solar/Wind Helper
0.34
315611Z1-036_GEN2
Solar/Wind Helper
1.226
238208AF1-136 C
Solar/Wind Helper
0.172
3130156CHOWAN
Solar/Wind Helper
0.223
3130156CHOWAN
Solar/Wind Helper
0.223
HAMLETPJM->LTFIMP_HAMLET
CLTF
5.439
G-007ALTFEXP_G-007A->PJM
CMTX
55.105
CBM NorthLTFEXP_CBM-N->PJM
CBM
63.132
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
4.814
BlueGrassPJM->LTFIMP_BlueG
CLTF
14.993
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
135.743
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.249
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
22.497

Details for PCHBTM1N-CHAN 500.0 kV Ckt 1 line l/o PECO_P1-2_5012_SRT-A


Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1N-CHAN 500.0 kV Ckt 1 line
Contingency Name:
PECO_P1-2_5012_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:135.02 %
Rating:3486.0 MVA
Rating Type:B
MVA to Mitigate:4706.95
MW Contribution:7.61
Bus #Bus NameTypeMW Contribution
200192DELTA CT1
50/50
3.848
200194DELTA CT3
50/50
3.848
200204Y1-065-CTG1
50/50
7.737
200054ROCKSP 3
50/50
4.936
233998TM1NIN_3.36
Solar/Wind Harmer
0.003
232404W1-003 C
Solar/Wind Harmer
1.225
232917OH NUG6
Adder
16.63
232915OH NUG4
Adder
16.593
232428Y3-058 C
Solar/Wind Harmer
0.003
232434Z2-077 GEN
Solar/Wind Harmer
0.08
971195AH1-057 GEN
Solar/Wind Harmer
1.181
232919VN10
Adder
5.306
232901NORTHST
Adder
15.73
965821AG1-450 GEN
Solar/Wind Harmer
9.841
232426Y1-080 FULL
Solar/Wind Harmer
0
970277AG2-181 GEN
Solar/Wind Harmer
1.102
233964AF2-378 GEN
Solar/Wind Harmer
0
972177AH1-672 GEN
Solar/Wind Harmer
19.242
233972AC1-094 C
Solar/Wind Harmer
0.594
232900DEMECSMY
Adder
17.4
233954AC2-188 GEN
Solar/Wind Harmer
0.002
233950AC2-186 GEN
Solar/Wind Harmer
0.001
232910NRG_G1
Adder
16.205
234012AE2-112_GEN
Solar/Wind Harmer
4.344
232422X3-066 FULL
Solar/Wind Harmer
0.156
233930AB2-032 GEN
Solar/Wind Harmer
1.784
233915AB1-141 GEN
Solar/Wind Harmer
0.477
231918WEST 1
Adder
5.956
231917EM10
Adder
4.123
228206SHRMN CT
Adder
24.012
228732V1-021 C
Adder
0.272
945431AF1-208 GEN
Solar/Wind Harmer
8.655
970997AG2-616 GEN
Solar/Wind Harmer
10.334
228351V2-046C
Solar/Wind Harmer
0.001
230511AF1-262
Solar/Wind Harmer
0
228728W1-130C
Solar/Wind Harmer
0.001
213497CHSTR7-9
Adder
3.862
213497CHSTR7-9
Adder
3.862
230434AG1-499 GEN
Solar/Wind Harmer
0.002
219258KINSLEYDEP C
Solar/Wind Harmer
0.001
213958STHWK5-6
Adder
3.703
219904AC1-010 C
Solar/Wind Harmer
0.001
218660EHAMPSOLAR C
Solar/Wind Harmer
0
219686LUMSOLAR_N C
Solar/Wind Harmer
0
219287REEVESEAST C
Solar/Wind Harmer
0
213560DLW11-12
Adder
3.608
219907AC1-030 C
Solar/Wind Harmer
0
219304NAMERICA C
Solar/Wind Harmer
0.118
219222BRL12CT2
Adder
11.496
213611FALLS1-3
Adder
4.417
20720728JCB_W1-129
Solar/Wind Harmer
0
207522AF2-254 C
Solar/Wind Harmer
1.142
214194N WALES4
Adder
1.05
207487AE2-000G4
Solar/Wind Harmer
15.464
207445AB1-138_GEN
Solar/Wind Harmer
0.001
20628028LAKEHURS
Adder
2.25
20714828MDF_W3-079
Solar/Wind Harmer
0.116
207454AA2-184 E
Solar/Wind Harmer
0.001
20715228NPK_W1-113
Solar/Wind Harmer
0
20742028HF_AC1-207
Solar/Wind Harmer
0.001
217197RE CRAN C
Solar/Wind Harmer
0
20635828PARLN1&2
Adder
8.012
20635028RRCT1&2
Adder
12.443
20635128RRCT3&4
Adder
12.011
217213AMBOY SO C
Solar/Wind Harmer
0
972275AH1-722 GEN
Adder
32.692
218449LINSOLAR C
Solar/Wind Harmer
0
207528AF2-192 GEN
Solar/Wind Harmer
0.001
20673628F1S_V4-069
Solar/Wind Harmer
0
20675428EAM_W2-061
Solar/Wind Harmer
0
20676428JCR_X2-075
Solar/Wind Harmer
0
217121ECCF
Adder
0.429
217083KRNY_132
Adder
9.189
20674328GAR_V4-001
Solar/Wind Harmer
0
20675828AU_W4-064
Solar/Wind Harmer
0
971519AH1-257 GEN
Solar/Wind Harmer
1.352
207437AD2-070 GEN
Solar/Wind Harmer
0.053
20465127PORT CT
Adder
2.414
20671928W4-073
Solar/Wind Harmer
0
966181AG1-487 GEN
Solar/Wind Harmer
3.02
208909MACR G3
Adder
122.259
209010PEIP 1
Adder
0.4
209023WIENIPP1
Adder
6.394
209025WIENIPP3
Adder
3.192
316006AB2-029 C
Solar/Wind Helper
0.112
316045AC1-158 PL2
Solar/Wind Helper
4.145
316254AC1-120 GEN1
Solar/Wind Helper
1.069
3147666LOUISA
Solar/Wind Helper
0.921
316192AB2-158 GEN
Solar/Wind Helper
1.547
238148AE2-230_GEN2
Solar/Wind Helper
0.397
316337AD2-073 GEN
Solar/Wind Helper
0.345
964211AG1-282 GEN
Solar/Wind Helper
0.306
3141726DUNNSVL
Solar/Wind Helper
0.908
3142416OLDCHRC
Solar/Wind Helper
0.589
3142416OLDCHRC
Solar/Wind Helper
0.226
3138133OCRAN
Solar/Wind Helper
0.136
3143526WINTERP
Solar/Wind Helper
1.176
3141766HARMONY
Solar/Wind Helper
0.045
3143226MDLTHAN
Solar/Wind Helper
0.226
3142433PROV 92
Solar/Wind Helper
0.904
3142543TWELFTH
Solar/Wind Helper
0.022
316159AE1-175 C
Solar/Wind Helper
0.342
316458AB2-190 GEN2
Solar/Wind Helper
1.286
3145336SMITFLD
Solar/Wind Helper
0.898
316294AC1-161 GEN
Solar/Wind Helper
4.104
316381AD1-082 GEN
Solar/Wind Helper
1.161
316375AC2-012 GEN
Solar/Wind Helper
0.587
316336AC2-165 C
Solar/Wind Helper
1.208
316072AD1-144
Solar/Wind Helper
0.256
316388AE2-253 GEN
Solar/Wind Helper
0.852
3146456SLIGO L269
Solar/Wind Helper
0.224
316246AF1-032 C
Solar/Wind Helper
0.256
3146516WINFALL
Solar/Wind Helper
0.723
3146516WINFALL
Solar/Wind Helper
0.223
200035PCHBTM 3
50/50
41.108
200201DELTA2 CT2
50/50
6.886
200034PCHBTM 2
50/50
40.065
200205Y1-065-CTG2
50/50
7.737
233987AB2-037 GEN
Solar/Wind Harmer
0.02
232926CRISFLD1
Adder
3.712
233901CHERRYDALE C
Solar/Wind Harmer
0.002
232408W1-005 C
Solar/Wind Harmer
1.225
232410W1-006 C
Solar/Wind Harmer
1.225
232918OH NUG7
Adder
16.593
232905CHERITON_25
Adder
4.64
972069AH1-584 GEN
Solar/Wind Harmer
11.816
972071AH1-585 GEN
Solar/Wind Harmer
11.816
971747AH1-380 GEN
Solar/Wind Harmer
4.727
970545AG2-347 GEN
Solar/Wind Harmer
47.731
231940T-011
Adder
1.41
971149AH1-027 GEN
Solar/Wind Harmer
5.905
233946AB2-136 GEN
Solar/Wind Harmer
0.007
234036AF2-325 C
Solar/Wind Harmer
0.001
234041AC1-190 GEN
Solar/Wind Harmer
13.768
233939AC1-091 C
Solar/Wind Harmer
0.003
233970AC1-092 C
Solar/Wind Harmer
0.003
232899W1-062
Adder
18.141
233984AB2-036 GEN
Solar/Wind Harmer
13.64
232424Y1-079 C
Solar/Wind Harmer
0.001
234014AF1-036_GEN
Solar/Wind Harmer
4.344
231131BLOOM ENRGY
Adder
8.121
233944AB2-135 GEN
Solar/Wind Harmer
0.009
233933AB2-153 GEN
Solar/Wind Harmer
0.002
232416X2-083
Adder
0.822
228251CARLLS#4
Adder
0.908
230422AE1-104_GEN1
Solar/Wind Harmer
19.276
230425AE1-104_GEN2
Solar/Wind Harmer
19.276
228307PCLP GT
Adder
17.143
228304LOGAN
Adder
34.151
213589EDDYSTN4
Adder
112.515
213587EDDYSTN3
Adder
112.468
230407AD2-065 C
Solar/Wind Harmer
0
972233AH1-701 GEN
Adder
5.892
219921AF1-264
Solar/Wind Harmer
0
219615MILLCREEK C
Solar/Wind Harmer
0
213815MOSER1-3
Adder
4.564
213815MOSER1-3
Adder
4.564
213535CROYDN11
Adder
13.155
20716428NHV_W2-082
Solar/Wind Harmer
0.001
207500AE2-000G1
Solar/Wind Harmer
15.464
207497AE2-000G2
Solar/Wind Harmer
15.464
207507AE2-000G3
Solar/Wind Harmer
15.464
20636128O CRK C2
Adder
7.881
20714928UPF_X1-085
Solar/Wind Harmer
0
219114HARTZY_C
Solar/Wind Harmer
0
20628028LAKEHURS
Adder
1.137
20720628TIN_W1-124
Solar/Wind Harmer
0.001
20716928W4-060COL
Solar/Wind Harmer
0
218440SUMMTASSOC C
Solar/Wind Harmer
0
218418LINDEN_G5
Adder
17.783
218419LINDEN_G6
Adder
17.783
972260AH1-715 GEN1
Adder
14.24
20673828FLE_V3-070
Solar/Wind Harmer
0
219036LINDEN_G7
Adder
17.045
219035LINDEN_G8
Adder
16.802
972261AH1-715 GEN2
Adder
16.317
207442AE1-156 GEN
Solar/Wind Harmer
0.061
20676128MHD_W3-029
Solar/Wind Harmer
0
972237AH1-703 GEN
Adder
10.011
217086KRNY_131
Adder
9.208
217083KRNY_132
Adder
9.13
20671828STAW2-080
Solar/Wind Harmer
0
20674528F3S_W2-016
Solar/Wind Harmer
0
20676228FRD_X1-012
Solar/Wind Harmer
0.001
20674928WA_W3-044
Solar/Wind Harmer
0.001
20465127PORT CT
Adder
3.203
20674128FR_U2-059
Solar/Wind Harmer
0
966111AG1-480 GEN
Solar/Wind Harmer
2.679
211065PSPA IPP
Solar/Wind Harmer
0
211065PSPA IPP
Solar/Wind Harmer
0
209029WAYMART-WD
Solar/Wind Harmer
0.001
209009PEIP 2
Adder
4.862
209010PEIP 1
Adder
2.203
209010PEIP 1
Adder
0.323
208972BECR K09
Solar/Wind Harmer
0
238175AF1-290_GEN
Solar/Wind Helper
0.124
238169AE2-226 GEN1
Solar/Wind Helper
0.572
238170AE2-226 GEN2
Solar/Wind Helper
0.572
315651AD1-115 GEN
Solar/Wind Helper
0.784
316447AC1-158 HLD
Solar/Wind Helper
2.85
966001AG1-469 GEN
Solar/Wind Helper
0.246
235020AA1-095 C
Solar/Wind Helper
0.043
23777901MDS_W4-102
Solar/Wind Helper
0.143
316468AD1-105 GEN
Solar/Wind Helper
1.135
316077AC2-138 C
Solar/Wind Helper
0.214
966871AG1-558 GEN
Solar/Wind Helper
0.306
316487AF1-042 GEN
Solar/Wind Helper
0.229
316075AC2-137 C
Solar/Wind Helper
0.345
3143526WINTERP
Solar/Wind Helper
1.176
3142946ENON
Solar/Wind Helper
0.023
316240AF1-291 C
Solar/Wind Helper
0.303
316033AB2-134 GEN
Solar/Wind Helper
0.774
315697AD1-025 GEN
Solar/Wind Helper
2.571
316236AE1-162_GEN
Solar/Wind Helper
0.302
316036AC1-147 C
Solar/Wind Helper
0.341
3142956BIRDNECK
Solar/Wind Helper
0.151
316316AC1-027 C
Solar/Wind Helper
0.354
316185AD1-033 GEN
Solar/Wind Helper
1.054
3145506HICKORY
Solar/Wind Helper
0.896
3145506HICKORY
Solar/Wind Helper
0.537
3145506HICKORY
Solar/Wind Helper
0.134
316339AD2-160 GEN
Solar/Wind Helper
0.852
316018AA1-139 ULT2
Solar/Wind Helper
0.962
316017AA1-139 ULT1
Solar/Wind Helper
1.023
3137176SLIGO L2192
Solar/Wind Helper
0.89
3130086AYDLETT
Solar/Wind Helper
0.895
3146386ELIZ CT
Solar/Wind Helper
0.223
316431W1029_GEN1
Solar/Wind Helper
0.902
316433W1029_GEN2
Solar/Wind Helper
0.902
3146516WINFALL
Solar/Wind Helper
0.223
3146516WINFALL
Solar/Wind Helper
0.223
3146516WINFALL
Solar/Wind Helper
0.223
237034AC2-136 C
Solar/Wind Helper
0.184
3146626S HERTFORD
Solar/Wind Helper
0.223
3146626S HERTFORD
Solar/Wind Helper
0.223
3144356SAPONY
Solar/Wind Helper
0.4
200202DELTA2 ST
50/50
11.685
200195DELTA ST
50/50
5.946
200052ROCKSP 1
50/50
4.887
200053ROCKSP 2
50/50
4.782
233923SMA
Solar/Wind Harmer
0.009
232912OH NUG1
Adder
16.704
232913OH NUG2
Adder
16.481
234033AF1-007_GEN
Solar/Wind Harmer
-0.002
233990AG1-397 GEN
Solar/Wind Harmer
-0.301
232904IR4
Adder
152.87
232432Z2-076 GEN
Solar/Wind Harmer
0.025
232920IR10
Adder
5.975
233955AB2-172 GEN
Solar/Wind Harmer
0.006
233973AC2-185 C
Solar/Wind Harmer
0.003
232813VAUGHN
Adder
1.107
233968AD2-076_GEN
Solar/Wind Harmer
4.344
970597AG2-380 GEN
Solar/Wind Harmer
7.781
232436AB1-176 C
Solar/Wind Harmer
0
231906DC3 NUG
Adder
26.102
231902DC CT7
Adder
20.867
231907DC10
Adder
6.516
971983AH1-536 GEN
Solar/Wind Harmer
3.292
233935AB2-179 C
Solar/Wind Harmer
2.508
231919CHRIST1
Adder
7.819
231920CHRIST2
Adder
7.646
970453AG2-297 GEN
Solar/Wind Harmer
3.713
228260V4-054C
Solar/Wind Harmer
0
228309CCLP NUG
Adder
37.117
228309CCLP NUG
Adder
35.307
972141AH1-641 GEN
Solar/Wind Harmer
4.792
964001AG1-254 GEN
Solar/Wind Harmer
0.555
971011AG2-627 GEN
Solar/Wind Harmer
7.605
971535AH1-265 GEN
Solar/Wind Harmer
3.898
227927V4-067C
Solar/Wind Harmer
0
228754AB1-001 C
Solar/Wind Harmer
0
213942SCHUYLKILL
Adder
4.853
213942SCHUYLKILL
Adder
3.711
213957STHWK3-4
Adder
3.703
213957STHWK3-4
Adder
3.703
219272CLEANLIGHT C
Solar/Wind Harmer
0
219914AD2-027 C
Solar/Wind Harmer
0.001
219688LUMSOLAR_S C
Solar/Wind Harmer
0
213561DLWR9-10
Adder
4.718
213561DLWR9-10
Adder
3.608
219607WPEMNERT C
Solar/Wind Harmer
0.001
219224BRL12CT4
Adder
11.496
214067T20SOLAR
Solar/Wind Harmer
0
213611FALLS1-3
Adder
4.417
213611FALLS1-3
Adder
4.417
20717128DIX_Z2-102
Solar/Wind Harmer
0.001
20715728PEM_W1-119
Solar/Wind Harmer
0.001
20715828PEM_W1-120
Solar/Wind Harmer
0.001
970025AG2-016 GEN
Solar/Wind Harmer
2.221
971189AH1-054 GEN
Solar/Wind Harmer
0.923
207459AE1-142 C O1
Solar/Wind Harmer
0.002
20714328BYD_X4-031
Solar/Wind Harmer
0.175
20714428HOW_X1-037
Solar/Wind Harmer
0.001
971521AH1-258 GEN
Solar/Wind Harmer
1.964
20720428HOL_W1-112
Solar/Wind Harmer
0
20635928PARLN3&4
Adder
8.012
218455CINNBAY_CGEN
Adder
1.96
218526CNTRALGAS2 C
Solar/Wind Harmer
0.813
218524CNTRALGAS1 C
Solar/Wind Harmer
0.808
218404KENILWRTH C
Adder
1.302
217167KRNY_14
Adder
9.189
217086KRNY_131
Adder
9.111
217147KRNY_1212
Adder
8.74
217147KRNY_1212
Adder
8.584
217146KRNY_1234
Adder
8.564
217146KRNY_1234
Adder
8.506
20676328BVR_Y1-020
Solar/Wind Harmer
0
207511W3-106 GEN
Solar/Wind Harmer
0.29
207530AG1-191 GEN
Solar/Wind Harmer
0.001
20674828DL_W4-046
Solar/Wind Harmer
0
971009AG2-626 GEN
Solar/Wind Harmer
0.882
207408W3-077 C
Solar/Wind Harmer
0
20675728RH_W2-091
Solar/Wind Harmer
0
966421AG1-511 GEN
Solar/Wind Harmer
4.902
20675928HOL_W4-097
Solar/Wind Harmer
0
207484AF2-139 C O1
Solar/Wind Harmer
0
20675128HRM_W1-127
Solar/Wind Harmer
0
20462827N BANGR8
Adder
0.568
209116AE2-175 GEN
Solar/Wind Harmer
0.005
209026WIENIPP4
Adder
3.159
3138216PACIFIC
Solar/Wind Helper
0.041
316411AF1-147_GEN1
Solar/Wind Helper
0.817
316415AF1-147_GEN2
Solar/Wind Helper
0.817
3141426STAFORD
Solar/Wind Helper
0.051
316164AC1-076 GEN
Solar/Wind Helper
1.11
238152AF2-075_GEN
Solar/Wind Helper
0.565
23546401DTGZ2-030
Solar/Wind Helper
0.072
316223AC1-118
Solar/Wind Helper
0.347
3141813NORNECK
Solar/Wind Helper
0.227
316312AB1-027
Solar/Wind Helper
0.431
3141783LANCAST
Solar/Wind Helper
0.136
3141783LANCAST
Solar/Wind Helper
0.091
3138133OCRAN
Solar/Wind Helper
0.068
3141913WHIT STONE
Solar/Wind Helper
0.226
316233AE1-074 FULL
Solar/Wind Helper
0.346
316059AD1-063 C
Solar/Wind Helper
0.228
3143873LANEXA
Solar/Wind Helper
0.136
315662AE1-191 GEN
Solar/Wind Helper
1.216
315666AE1-190 GEN
Solar/Wind Helper
0.304
957601AF2-054 GEN
Solar/Wind Helper
0.303
3141873WAN 176
Solar/Wind Helper
0.045
957831AF2-077 GEN
Solar/Wind Helper
0.304
316132AB2-190 GEN1
Solar/Wind Helper
1.286
316369SG1_INVT
Solar/Wind Helper
1.082
3143316POE
Solar/Wind Helper
0.889
316349AD2-085 GEN
Solar/Wind Helper
1.024
319010AE1-072 C
Solar/Wind Helper
2.557
316305AF2-043 C
Solar/Wind Helper
0.301
313526AB2-022
Solar/Wind Helper
0.34
3146486SUNBURY
Solar/Wind Helper
0.223
3146486SUNBURY
Solar/Wind Helper
0.223
316321Z2-027
Solar/Wind Helper
0.34
3145176PASQUOTANK
Solar/Wind Helper
0.138
316315AB2-025 C
Solar/Wind Helper
0.339
200200DELTA2 CT1
50/50
6.886
200193DELTA CT2
50/50
3.848
200203Y1-065-STG
50/50
13.417
200055ROCKSP 4
50/50
4.832
232907VN8
Adder
56.816
233996TM1833_GEN
Solar/Wind Harmer
0.003
233997TMININ_4.2
Solar/Wind Harmer
0.003
232406W1-004 FULL
Solar/Wind Harmer
1.225
232914OH NUG3
Adder
16.704
232916OH NUG5
Adder
16.704
232921TASLEY2G
Adder
9.763
233940AF2-379 C
Solar/Wind Harmer
0
972073AH1-586 GEN
Solar/Wind Harmer
17.724
233900O-025 C
Adder
2.227
972133AH1-634 GEN
Solar/Wind Harmer
6.971
233990AG1-397 GEN
Solar/Wind Harmer
2.575
234015AF2-250 C
Solar/Wind Harmer
0
233994AC2-023 GEN
Solar/Wind Harmer
0.008
960671AF2-358 GEN
Solar/Wind Harmer
23.619
232417X3-008 C
Solar/Wind Harmer
0.002
233971AC1-093 C
Solar/Wind Harmer
0.081
970695AG2-447 GEN
Solar/Wind Harmer
4.718
233952AC2-187 GEN
Solar/Wind Harmer
0.002
233918AB1-142 GEN
Solar/Wind Harmer
0.477
233982AB2-133 GEN
Solar/Wind Harmer
0.007
972251AH1-710 GEN
Adder
80.123
228202CUMB CT
Adder
23.982
228711V2-041C
Solar/Wind Harmer
0
971553AH1-274 GEN
Solar/Wind Harmer
2.255
230430AE1-229_GEN
Solar/Wind Harmer
0.024
230415AB2-049 C
Solar/Wind Harmer
0
213497CHSTR7-9
Adder
3.862
228304LOGAN
Adder
30.715
228729W2-030 C
Solar/Wind Harmer
0.001
219623KINSLEYBEA C
Solar/Wind Harmer
0
213958STHWK5-6
Adder
3.703
219766PARADISE C
Solar/Wind Harmer
0
219912AD2-042 GEN
Solar/Wind Harmer
0.001
213560DLW11-12
Adder
3.608
219906AC1-017 C
Solar/Wind Harmer
0
219610FLORENCE C
Solar/Wind Harmer
0.001
219348LDSOLAR C
Solar/Wind Harmer
0.001
219221BRL12CT1
Adder
11.496
219223BRL12CT3
Adder
11.496
213815MOSER1-3
Adder
4.564
20716028EGP_W2-019
Solar/Wind Harmer
0
20720828JCB_W4-025
Solar/Wind Harmer
0.001
20715028HAN_X4-015
Solar/Wind Harmer
0
20636028O CRK C1
Adder
8.644
971667AH1-334 GEN
Solar/Wind Harmer
2.13
219727YARDVSOLFA C
Solar/Wind Harmer
0
20714528FRN_Y2-051
Solar/Wind Harmer
0
219276PARKLANDSO C
Solar/Wind Harmer
0.001
20716228APLW2-078
Solar/Wind Harmer
0
20720528MAN_W1-024
Solar/Wind Harmer
0
967451AG2-055 C O1
Solar/Wind Harmer
275.686
219612MATRIX C
Solar/Wind Harmer
0
218438BLK ROCK C
Solar/Wind Harmer
0
20635828PARLN1&2
Adder
3.629
20635928PARLN3&4
Adder
3.629
20635028RRCT1&2
Adder
12.638
20635128RRCT3&4
Adder
10.477
219908AB1-139 C
Solar/Wind Harmer
0
20673728F2S_V4-070
Solar/Wind Harmer
0
217186ESSEX_G9
Adder
15.809
217194REDH C
Solar/Wind Harmer
0
20676728BRNX1-095
Solar/Wind Harmer
0
207510AF2-138 C
Solar/Wind Harmer
0.001
20674628WNG_W3-110
Solar/Wind Harmer
0
971007AG2-625 GEN
Solar/Wind Harmer
1.383
20466127PORT 5CT
Adder
21.343
20633028GILCT9
Adder
22.387
20465427SHAW CT
Adder
3.059
963071AG1-156 GEN
Solar/Wind Harmer
0.267
970095AG2-074 GEN
Solar/Wind Harmer
3.043
209025WIENIPP3
Adder
3.127
3141196NOKESVL
Solar/Wind Helper
0.957
316044AC1-158 PL1
Solar/Wind Helper
1.295
316450AC1-158 RIC
Solar/Wind Helper
0.345
316170AC1-121 GEN2
Solar/Wind Helper
0.356
3132273ORANGE
Solar/Wind Helper
0.046
3147666LOUISA
Solar/Wind Helper
0.53
238147AE2-230_GEN1
Solar/Wind Helper
0.395
238149AF1-291A_GEN
Solar/Wind Helper
0.113
966881AG1-559 GEN
Solar/Wind Helper
0.309
237061AD1-155 GEN
Solar/Wind Helper
0.043
3141906WESTMOR
Solar/Wind Helper
0.091
316473AC1-191 GEN
Solar/Wind Helper
1.387
316404AE1-155 C
Solar/Wind Helper
1.916
316484AD2-074 GEN
Solar/Wind Helper
0.438
316280AD1-041 GEN
Solar/Wind Helper
0.76
316156AD2-030 GEN
Solar/Wind Helper
0.341
3142946ENON
Solar/Wind Helper
0.075
316382AG1-145 C
Solar/Wind Helper
0.303
315839AE2-212 C
Solar/Wind Helper
0.302
316313AB2-026
Solar/Wind Helper
0.342
316258AE1-075 C
Solar/Wind Helper
0.308
316405AF2-144 C
Solar/Wind Helper
0.256
3145336SMITFLD
Solar/Wind Helper
0.09
315773AC2-141 GEN
Solar/Wind Helper
4.83
3144536CHRHLND
Solar/Wind Helper
0.034
3144873MCLAUGH
Solar/Wind Helper
0.006
3146456SLIGO L269
Solar/Wind Helper
0.224
316320Y1-086
Solar/Wind Helper
0.1
316435W1029_GEN3
Solar/Wind Helper
0.902
3146516WINFALL
Solar/Wind Helper
0.223
238221AF1-254 C O1
Solar/Wind Helper
0.219
3146626S HERTFORD
Solar/Wind Helper
0.223
3145273HOLLAND
Solar/Wind Helper
0.167
HAMLETPJM->LTFIMP_HAMLET
CLTF
5.427
G-007ALTFEXP_G-007A->PJM
CMTX
54.959
CBM NorthLTFEXP_CBM-N->PJM
CBM
62.949
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
4.801
BlueGrassPJM->LTFIMP_BlueG
CLTF
14.952
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
135.356
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.242
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
22.436

Details for PCHBTM1N-CHAN 500.0 kV Ckt 1 line l/o PECO_P4_PEACH245_SRT-A/* $ CHESCO $ PECO_P4_PEACH245 $ STBK


Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1N-CHAN 500.0 kV Ckt 1 line
Contingency Name:
PECO_P4_PEACH245_SRT-A/* $ CHESCO $ PECO_P4_PEACH245 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:128.09 %
Rating:3486.0 MVA
Rating Type:B
MVA to Mitigate:4465.17
MW Contribution:11.05
Bus #Bus NameTypeMW Contribution
200035PCHBTM 3
50/50
41.416
200034PCHBTM 2
50/50
40.367
200205Y1-065-CTG2
50/50
7.799
233987AB2-037 GEN
Solar/Wind Harmer
21.831
232926CRISFLD1
Adder
3.752
233901CHERRYDALE C
Solar/Wind Harmer
2.152
232408W1-005 C
Solar/Wind Harmer
1.915
232410W1-006 C
Solar/Wind Harmer
1.915
232918OH NUG7
Adder
16.772
232905CHERITON_25
Adder
4.69
972069AH1-584 GEN
Solar/Wind Harmer
17.119
972071AH1-585 GEN
Solar/Wind Harmer
17.119
971747AH1-380 GEN
Solar/Wind Harmer
6.848
970545AG2-347 GEN
Solar/Wind Harmer
125.054
231940T-011
Adder
1.425
971149AH1-027 GEN
Solar/Wind Harmer
6.466
233946AB2-136 GEN
Solar/Wind Harmer
7.623
234036AF2-325 C
Solar/Wind Harmer
1.751
234041AC1-190 GEN
Solar/Wind Harmer
17.098
233939AC1-091 C
Solar/Wind Harmer
1.676
233970AC1-092 C
Solar/Wind Harmer
1.676
232899W1-062
Adder
18.337
233984AB2-036 GEN
Solar/Wind Harmer
23.625
232424Y1-079 C
Solar/Wind Harmer
1.067
234014AF1-036_GEN
Solar/Wind Harmer
5.113
231131BLOOM ENRGY
Adder
8.209
233944AB2-135 GEN
Solar/Wind Harmer
9.858
200052ROCKSP 1
50/50
4.926
200053ROCKSP 2
50/50
4.82
233923SMA
Solar/Wind Harmer
8.878
232912OH NUG1
Adder
16.884
232913OH NUG2
Adder
16.659
233990AG1-397 GEN
Solar/Wind Harmer
0.105
234033AF1-007_GEN
Solar/Wind Harmer
44.688
232904IR4
Adder
154.516
232432Z2-076 GEN
Solar/Wind Harmer
0.253
232920IR10
Adder
6.039
233955AB2-172 GEN
Solar/Wind Harmer
9.548
233973AC2-185 C
Solar/Wind Harmer
6.894
232813VAUGHN
Adder
1.119
233968AD2-076_GEN
Solar/Wind Harmer
12.526
970597AG2-380 GEN
Solar/Wind Harmer
7.865
232436AB1-176 C
Solar/Wind Harmer
0.432
231906DC3 NUG
Adder
26.387
231902DC CT7
Adder
21.095
231907DC10
Adder
6.587
971983AH1-536 GEN
Solar/Wind Harmer
14.077
233935AB2-179 C
Solar/Wind Harmer
4.604
231919CHRIST1
Adder
7.909
231920CHRIST2
Adder
7.734
970453AG2-297 GEN
Solar/Wind Harmer
4.074
228260V4-054C
Solar/Wind Harmer
1.497
228309CCLP NUG
Adder
37.609
228309CCLP NUG
Adder
35.774
972141AH1-641 GEN
Solar/Wind Harmer
4.176
964001AG1-254 GEN
Solar/Wind Harmer
2.947
971011AG2-627 GEN
Solar/Wind Harmer
11.046
971535AH1-265 GEN
Solar/Wind Harmer
6.112
227927V4-067C
Solar/Wind Harmer
0.283
228754AB1-001 C
Solar/Wind Harmer
0.199
219137THOSOLAR C
Solar/Wind Harmer
1.688
213942SCHUYLKILL
Adder
4.921
213942SCHUYLKILL
Adder
3.763
213957STHWK3-4
Adder
3.755
213957STHWK3-4
Adder
3.755
219272CLEANLIGHT C
Solar/Wind Harmer
0.25
219914AD2-027 C
Solar/Wind Harmer
0.817
219688LUMSOLAR_S C
Solar/Wind Harmer
0.275
213561DLWR9-10
Adder
4.786
213561DLWR9-10
Adder
3.66
219607WPEMNERT C
Solar/Wind Harmer
0.548
219224BRL12CT4
Adder
11.667
214067T20SOLAR
Solar/Wind Harmer
0.321
213611FALLS1-3
Adder
4.485
200204Y1-065-CTG1
50/50
7.799
200054ROCKSP 3
50/50
4.975
233998TM1NIN_3.36
Solar/Wind Harmer
2.422
232404W1-003 C
Solar/Wind Harmer
1.915
232917OH NUG6
Adder
16.809
232915OH NUG4
Adder
16.772
232428Y3-058 C
Solar/Wind Harmer
1.595
232434Z2-077 GEN
Solar/Wind Harmer
0.478
971195AH1-057 GEN
Solar/Wind Harmer
2.092
232919VN10
Adder
5.363
232901NORTHST
Adder
15.899
965821AG1-450 GEN
Solar/Wind Harmer
9.947
232426Y1-080 FULL
Solar/Wind Harmer
0.365
970277AG2-181 GEN
Solar/Wind Harmer
9.581
233964AF2-378 GEN
Solar/Wind Harmer
0.244
972177AH1-672 GEN
Solar/Wind Harmer
25.654
233972AC1-094 C
Solar/Wind Harmer
1.266
232900DEMECSMY
Adder
17.588
233954AC2-188 GEN
Solar/Wind Harmer
2.146
233950AC2-186 GEN
Solar/Wind Harmer
1.073
232910NRG_G1
Adder
16.381
234012AE2-112_GEN
Solar/Wind Harmer
4.346
232422X3-066 FULL
Solar/Wind Harmer
0.472
233930AB2-032 GEN
Solar/Wind Harmer
1.569
233915AB1-141 GEN
Solar/Wind Harmer
1.864
231918WEST 1
Adder
6.025
231917EM10
Adder
4.171
228206SHRMN CT
Adder
24.327
228732V1-021 C
Adder
0.276
945431AF1-208 GEN
Solar/Wind Harmer
12.57
970997AG2-616 GEN
Solar/Wind Harmer
13.919
228351V2-046C
Solar/Wind Harmer
2.917
230511AF1-262
Solar/Wind Harmer
0.264
228728W1-130C
Solar/Wind Harmer
0.955
213497CHSTR7-9
Adder
3.914
213497CHSTR7-9
Adder
3.914
230434AG1-499 GEN
Solar/Wind Harmer
0.831
219258KINSLEYDEP C
Solar/Wind Harmer
0.447
213958STHWK5-6
Adder
3.755
219904AC1-010 C
Solar/Wind Harmer
0.519
218660EHAMPSOLAR C
Solar/Wind Harmer
0.238
219686LUMSOLAR_N C
Solar/Wind Harmer
0.275
219287REEVESEAST C
Solar/Wind Harmer
1.826
213560DLW11-12
Adder
3.66
219907AC1-030 C
Solar/Wind Harmer
0.187
219304NAMERICA C
Solar/Wind Harmer
0.406
219222BRL12CT2
Adder
11.667
213611FALLS1-3
Adder
4.485
20720728JCB_W1-129
Solar/Wind Harmer
0.374
207522AF2-254 C
Solar/Wind Harmer
1.795
214194N WALES4
Adder
1.066
207487AE2-000G4
Solar/Wind Harmer
39.127
207445AB1-138_GEN
Solar/Wind Harmer
0.705
20628028LAKEHURS
Adder
2.286
963711AG1-223 GEN
Solar/Wind Harmer
1.762
20714828MDF_W3-079
Solar/Wind Harmer
0.364
219680HOPEWELLV C1
Solar/Wind Harmer
0.088
207454AA2-184 E
Solar/Wind Harmer
1.158
20715228NPK_W1-113
Solar/Wind Harmer
0.497
20742028HF_AC1-207
Solar/Wind Harmer
0.901
217197RE CRAN C
Solar/Wind Harmer
0.605
20635828PARLN1&2
Adder
8.158
20635028RRCT1&2
Adder
12.674
20635128RRCT3&4
Adder
12.234
218428ETC SOLAR C
Solar/Wind Harmer
0.038
217213AMBOY SO C
Solar/Wind Harmer
0.135
972275AH1-722 GEN
Adder
33.324
218449LINSOLAR C
Solar/Wind Harmer
1.045
207528AF2-192 GEN
Solar/Wind Harmer
0.574
20673628F1S_V4-069
Solar/Wind Harmer
0.186
20675428EAM_W2-061
Solar/Wind Harmer
0.196
20676428JCR_X2-075
Solar/Wind Harmer
0.353
217209CENTRL HS C
Solar/Wind Harmer
0.046
217121ECCF
Adder
0.438
217083KRNY_132
Adder
9.377
217208PARK ELE C
Solar/Wind Harmer
0.025
207439AE1-081 C O1
Solar/Wind Harmer
0.055
20674328GAR_V4-001
Solar/Wind Harmer
0.099
20675828AU_W4-064
Solar/Wind Harmer
0.155
971519AH1-257 GEN
Solar/Wind Harmer
2.145
207518AF1-320_GEN
Solar/Wind Harmer
3.053
207437AD2-070 GEN
Solar/Wind Harmer
0.249
20465127PORT CT
Adder
2.477
20671928W4-073
Solar/Wind Harmer
0.355
966181AG1-487 GEN
Solar/Wind Harmer
3.042
208909MACR G3
Adder
125.657
209010PEIP 1
Adder
0.415
961301AF2-421 GEN
Solar/Wind Harmer
0.615
963151AG1-164 GEN
Solar/Wind Harmer
0.615
209023WIENIPP1
Adder
6.632
209025WIENIPP3
Adder
3.31
316006AB2-029 C
Solar/Wind Helper
0.108
316045AC1-158 PL2
Solar/Wind Helper
3.978
316254AC1-120 GEN1
Solar/Wind Helper
1.026
233933AB2-153 GEN
Solar/Wind Harmer
2.116
232416X2-083
Adder
0.831
228251CARLLS#4
Adder
0.92
230433AD2-135 GEN
Solar/Wind Harmer
0.146
230422AE1-104_GEN1
Solar/Wind Harmer
48.658
230425AE1-104_GEN2
Solar/Wind Harmer
48.658
228307PCLP GT
Adder
17.373
228304LOGAN
Adder
34.612
213589EDDYSTN4
Adder
114.034
213587EDDYSTN3
Adder
113.987
230407AD2-065 C
Solar/Wind Harmer
0.188
972233AH1-701 GEN
Adder
5.972
219921AF1-264
Solar/Wind Harmer
0.199
219615MILLCREEK C
Solar/Wind Harmer
0.315
213535CROYDN11
Adder
13.35
213815MOSER1-3
Adder
4.632
213815MOSER1-3
Adder
4.632
20716428NHV_W2-082
Solar/Wind Harmer
2.226
207500AE2-000G1
Solar/Wind Harmer
39.127
207497AE2-000G2
Solar/Wind Harmer
39.127
207507AE2-000G3
Solar/Wind Harmer
39.127
20636128O CRK C2
Adder
8.005
963401AG1-189 GEN
Solar/Wind Harmer
1.421
963391AG1-188 GEN
Solar/Wind Harmer
2.362
20714928UPF_X1-085
Solar/Wind Harmer
0.498
219114HARTZY_C
Solar/Wind Harmer
1.018
20628028LAKEHURS
Adder
1.156
219817TRENTONSOL C
Solar/Wind Harmer
1.29
20641628MLH_W1-032
Solar/Wind Harmer
0.34
20720628TIN_W1-124
Solar/Wind Harmer
1.154
20716928W4-060COL
Solar/Wind Harmer
0.799
924131AB2-057 GEN
Solar/Wind Harmer
1.13
218440SUMMTASSOC C
Solar/Wind Harmer
0.138
218418LINDEN_G5
Adder
18.127
218419LINDEN_G6
Adder
18.127
972260AH1-715 GEN1
Adder
14.515
20673828FLE_V3-070
Solar/Wind Harmer
0.481
219036LINDEN_G7
Adder
17.381
219035LINDEN_G8
Adder
17.133
972261AH1-715 GEN2
Adder
16.638
207442AE1-156 GEN
Solar/Wind Harmer
0.772
20676128MHD_W3-029
Solar/Wind Harmer
0.495
217081WEATEXAS C
Solar/Wind Harmer
0.088
217202FBANKSOLAR C
Solar/Wind Harmer
0.075
217201HACKENSOLA C
Solar/Wind Harmer
0.074
972237AH1-703 GEN
Adder
10.216
217206BARNGR HS C
Solar/Wind Harmer
0.031
217086KRNY_131
Adder
9.397
217083KRNY_132
Adder
9.317
20671828STAW2-080
Solar/Wind Harmer
0.105
217204WCALDSOLAR C
Solar/Wind Harmer
0.073
20674528F3S_W2-016
Solar/Wind Harmer
1.387
20676228FRD_X1-012
Solar/Wind Harmer
0.536
207471AF2-354 C
Solar/Wind Harmer
0.444
20674928WA_W3-044
Solar/Wind Harmer
0.418
964851AG1-348 GEN
Solar/Wind Harmer
1.503
20634528N27_Y2-018
Solar/Wind Harmer
0.23
20465127PORT CT
Adder
3.288
20674128FR_U2-059
Solar/Wind Harmer
0.151
966111AG1-480 GEN
Solar/Wind Harmer
0.07
966111AG1-480 GEN
Solar/Wind Harmer
2.681
211065PSPA IPP
Solar/Wind Harmer
0.325
211065PSPA IPP
Solar/Wind Harmer
0.325
209029WAYMART-WD
Solar/Wind Harmer
1.855
209009PEIP 2
Adder
5.036
209010PEIP 1
Adder
2.282
209010PEIP 1
Adder
0.334
208972BECR K09
Solar/Wind Harmer
0.641
238175AF1-290_GEN
Solar/Wind Helper
0.119
238169AE2-226 GEN1
Solar/Wind Helper
0.549
238170AE2-226 GEN2
Solar/Wind Helper
0.549
315651AD1-115 GEN
Solar/Wind Helper
0.752
316447AC1-158 HLD
Solar/Wind Helper
2.735
200203Y1-065-STG
50/50
13.524
200055ROCKSP 4
50/50
4.87
232907VN8
Adder
57.427
233996TM1833_GEN
Solar/Wind Harmer
2.422
233997TMININ_4.2
Solar/Wind Harmer
2.422
232406W1-004 FULL
Solar/Wind Harmer
1.915
233940AF2-379 C
Solar/Wind Harmer
0.357
232914OH NUG3
Adder
16.884
232916OH NUG5
Adder
16.884
232921TASLEY2G
Adder
9.868
972073AH1-586 GEN
Solar/Wind Harmer
17.915
233990AG1-397 GEN
Solar/Wind Harmer
2.193
233900O-025 C
Adder
2.251
972133AH1-634 GEN
Solar/Wind Harmer
18.948
234015AF2-250 C
Solar/Wind Harmer
0.23
233994AC2-023 GEN
Solar/Wind Harmer
5.138
960671AF2-358 GEN
Solar/Wind Harmer
34.219
232417X3-008 C
Solar/Wind Harmer
3.819
233971AC1-093 C
Solar/Wind Harmer
1.497
970695AG2-447 GEN
Solar/Wind Harmer
6.836
233952AC2-187 GEN
Solar/Wind Harmer
2.146
233918AB1-142 GEN
Solar/Wind Harmer
1.864
233982AB2-133 GEN
Solar/Wind Harmer
9.153
972251AH1-710 GEN
Adder
81.035
228202CUMB CT
Adder
24.296
228711V2-041C
Solar/Wind Harmer
0.882
971553AH1-274 GEN
Solar/Wind Harmer
3.543
230430AE1-229_GEN
Solar/Wind Harmer
12.758
230415AB2-049 C
Solar/Wind Harmer
0.273
213497CHSTR7-9
Adder
3.914
228304LOGAN
Adder
31.129
228729W2-030 C
Solar/Wind Harmer
0.825
219623KINSLEYBEA C
Solar/Wind Harmer
0.591
213958STHWK5-6
Adder
3.755
219766PARADISE C
Solar/Wind Harmer
0.432
219291REEVESSOUT C
Solar/Wind Harmer
0.082
219912AD2-042 GEN
Solar/Wind Harmer
1.083
213560DLW11-12
Adder
3.66
219236SOUTHERNHQ C
Solar/Wind Harmer
0.091
219906AC1-017 C
Solar/Wind Harmer
0.295
219610FLORENCE C
Solar/Wind Harmer
1.811
219348LDSOLAR C
Solar/Wind Harmer
0.783
219221BRL12CT1
Adder
11.667
219223BRL12CT3
Adder
11.667
213815MOSER1-3
Adder
4.632
959561AF2-247 GEN
Solar/Wind Harmer
0.612
20716028EGP_W2-019
Solar/Wind Harmer
0.582
20720828JCB_W4-025
Solar/Wind Harmer
0.568
20715028HAN_X4-015
Solar/Wind Harmer
0.374
20636028O CRK C1
Adder
8.779
971667AH1-334 GEN
Solar/Wind Harmer
3.35
219727YARDVSOLFA C
Solar/Wind Harmer
1.101
20714528FRN_Y2-051
Solar/Wind Harmer
0.351
219276PARKLANDSO C
Solar/Wind Harmer
0.547
219918AC2-009 C
Solar/Wind Harmer
0.071
20716228APLW2-078
Solar/Wind Harmer
1.02
20720528MAN_W1-024
Solar/Wind Harmer
0.293
967451AG2-055 C O1
Solar/Wind Harmer
196.389
219612MATRIX C
Solar/Wind Harmer
0.207
218438BLK ROCK C
Solar/Wind Harmer
0.154
20635828PARLN1&2
Adder
3.695
20635928PARLN3&4
Adder
3.695
20635028RRCT1&2
Adder
12.872
20635128RRCT3&4
Adder
10.671
219908AB1-139 C
Solar/Wind Harmer
0.407
219919AE1-041 FULL
Solar/Wind Harmer
0.043
219249CENTRALDIV C
Solar/Wind Harmer
0.042
20673728F2S_V4-070
Solar/Wind Harmer
0.186
217211CAMDEN ST C
Solar/Wind Harmer
0.025
217186ESSEX_G9
Adder
16.133
217169METRODIV C
Solar/Wind Harmer
0.04
217194REDH C
Solar/Wind Harmer
0.496
20676728BRNX1-095
Solar/Wind Harmer
0.17
207510AF2-138 C
Solar/Wind Harmer
1.619
20674628WNG_W3-110
Solar/Wind Harmer
0.367
971007AG2-625 GEN
Solar/Wind Harmer
2.194
20466127PORT 5CT
Adder
21.905
20633028GILCT9
Adder
22.988
966181AG1-487 GEN
Solar/Wind Harmer
0.204
20465427SHAW CT
Adder
3.142
963071AG1-156 GEN
Solar/Wind Harmer
1.734
970095AG2-074 GEN
Solar/Wind Harmer
3.934
963161AG1-165 GEN
Solar/Wind Harmer
0.615
209025WIENIPP3
Adder
3.243
3141196NOKESVL
Solar/Wind Helper
0.919
316044AC1-158 PL1
Solar/Wind Helper
1.243
316450AC1-158 RIC
Solar/Wind Helper
0.331
316170AC1-121 GEN2
Solar/Wind Helper
0.342
213611FALLS1-3
Adder
4.485
20717128DIX_Z2-102
Solar/Wind Harmer
1.649
20715728PEM_W1-119
Solar/Wind Harmer
0.667
20715828PEM_W1-120
Solar/Wind Harmer
0.667
970025AG2-016 GEN
Solar/Wind Harmer
3.491
971189AH1-054 GEN
Solar/Wind Harmer
1.451
207459AE1-142 C O1
Solar/Wind Harmer
1.288
219620RIDERU C
Solar/Wind Harmer
0.065
20714328BYD_X4-031
Solar/Wind Harmer
0.33
20714428HOW_X1-037
Solar/Wind Harmer
1.438
971521AH1-258 GEN
Solar/Wind Harmer
3.092
20720428HOL_W1-112
Solar/Wind Harmer
0.394
20635928PARLN3&4
Adder
8.158
218455CINNBAY_CGEN
Adder
1.996
218526CNTRALGAS2 C
Solar/Wind Harmer
0.401
218524CNTRALGAS1 C
Solar/Wind Harmer
0.398
20675528CPH_W2-050
Solar/Wind Harmer
0.498
218404KENILWRTH C
Adder
1.328
217167KRNY_14
Adder
9.377
217086KRNY_131
Adder
9.297
217147KRNY_1212
Adder
8.919
217147KRNY_1212
Adder
8.76
217146KRNY_1234
Adder
8.74
217146KRNY_1234
Adder
8.68
966261AG1-495 GEN
Solar/Wind Harmer
1.685
20676328BVR_Y1-020
Solar/Wind Harmer
0.303
207511W3-106 GEN
Solar/Wind Harmer
0.597
207530AG1-191 GEN
Solar/Wind Harmer
1.243
20674828DL_W4-046
Solar/Wind Harmer
0.562
971009AG2-626 GEN
Solar/Wind Harmer
1.399
207408W3-077 C
Solar/Wind Harmer
0.425
20675728RH_W2-091
Solar/Wind Harmer
0.287
966421AG1-511 GEN
Solar/Wind Harmer
7.209
20675928HOL_W4-097
Solar/Wind Harmer
0.109
207484AF2-139 C O1
Solar/Wind Harmer
0.419
20675128HRM_W1-127
Solar/Wind Harmer
0.139
20462827N BANGR8
Adder
0.583
209116AE2-175 GEN
Solar/Wind Harmer
3.111
961261AF2-417 GEN
Solar/Wind Harmer
0.691
209026WIENIPP4
Adder
3.277
3138216PACIFIC
Solar/Wind Helper
0.039
316411AF1-147_GEN1
Solar/Wind Helper
0.785
316415AF1-147_GEN2
Solar/Wind Helper
0.785
3141426STAFORD
Solar/Wind Helper
0.049
316164AC1-076 GEN
Solar/Wind Helper
1.065
HAMLETPJM->LTFIMP_HAMLET
CLTF
5.182
G-007ALTFEXP_G-007A->PJM
CMTX
55.976
CBM NorthLTFEXP_CBM-N->PJM
CBM
65.028
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
4.565
BlueGrassPJM->LTFIMP_BlueG
CLTF
14.217
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
138.092
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.093
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
21.341

Details for PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line l/o AP_P2-3_PE-500-019E_SRT-SL


Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-500-019E_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:169.7 %
Rating:3620.0 MVA
Rating Type:B
MVA to Mitigate:6143.21
MW Contribution:11.2
Bus #Bus NameTypeMW Contribution
200192DELTA CT1
50/50
3.137
200194DELTA CT3
50/50
3.137
200204Y1-065-CTG1
50/50
6.421
200054ROCKSP 3
50/50
4.096
232901NORTHST
Adder
14.49
233972AC1-094 C
Solar/Wind Harmer
1.155
232900DEMECSMY
Adder
16.029
232434Z2-077 GEN
Solar/Wind Harmer
0.435
972177AH1-672 GEN
Solar/Wind Harmer
23.335
232917OH NUG6
Adder
15.271
232915OH NUG4
Adder
15.237
232404W1-003 C
Solar/Wind Harmer
1.739
233998TM1NIN_3.36
Solar/Wind Harmer
2.2
971195AH1-057 GEN
Solar/Wind Harmer
1.901
232428Y3-058 C
Solar/Wind Harmer
1.449
232919VN10
Adder
4.869
965821AG1-450 GEN
Solar/Wind Harmer
9.03
232426Y1-080 FULL
Solar/Wind Harmer
0.332
970277AG2-181 GEN
Solar/Wind Harmer
8.697
233964AF2-378 GEN
Solar/Wind Harmer
0.221
233954AC2-188 GEN
Solar/Wind Harmer
1.951
233950AC2-186 GEN
Solar/Wind Harmer
0.976
232910NRG_G1
Adder
14.89
234012AE2-112_GEN
Solar/Wind Harmer
3.936
232422X3-066 FULL
Solar/Wind Harmer
0.428
233930AB2-032 GEN
Solar/Wind Harmer
1.421
233915AB1-141 GEN
Solar/Wind Harmer
1.688
231918WEST 1
Adder
5.543
231917EM10
Adder
3.862
228206SHRMN CT
Adder
24.488
228732V1-021 C
Adder
0.279
945431AF1-208 GEN
Solar/Wind Harmer
12.689
970997AG2-616 GEN
Solar/Wind Harmer
14.07
228351V2-046C
Solar/Wind Harmer
2.952
230511AF1-262
Solar/Wind Harmer
0.268
228728W1-130C
Solar/Wind Harmer
0.972
230434AG1-499 GEN
Solar/Wind Harmer
0.846
219258KINSLEYDEP C
Solar/Wind Harmer
0.463
218660EHAMPSOLAR C
Solar/Wind Harmer
0.25
219686LUMSOLAR_N C
Solar/Wind Harmer
0.289
219287REEVESEAST C
Solar/Wind Harmer
1.918
219904AC1-010 C
Solar/Wind Harmer
0.539
213497CHSTR7-9
Adder
3.881
213497CHSTR7-9
Adder
3.881
219907AC1-030 C
Solar/Wind Harmer
0.197
213958STHWK5-6
Adder
3.833
213560DLW11-12
Adder
3.815
219304NAMERICA C
Solar/Wind Harmer
0.435
219222BRL12CT2
Adder
12.51
213611FALLS1-3
Adder
4.905
20720728JCB_W1-129
Solar/Wind Harmer
0.414
207522AF2-254 C
Solar/Wind Harmer
1.989
200200DELTA2 CT1
50/50
5.614
200193DELTA CT2
50/50
3.137
200203Y1-065-STG
50/50
11.135
200055ROCKSP 4
50/50
4.01
233971AC1-093 C
Solar/Wind Harmer
1.366
970695AG2-447 GEN
Solar/Wind Harmer
6.237
972133AH1-634 GEN
Solar/Wind Harmer
17.227
972073AH1-586 GEN
Solar/Wind Harmer
16.278
232914OH NUG3
Adder
15.339
232916OH NUG5
Adder
15.339
232406W1-004 FULL
Solar/Wind Harmer
1.739
232921TASLEY2G
Adder
8.965
233996TM1833_GEN
Solar/Wind Harmer
2.2
233997TMININ_4.2
Solar/Wind Harmer
2.2
233990AG1-397 GEN
Solar/Wind Harmer
1.992
233940AF2-379 C
Solar/Wind Harmer
0.324
234015AF2-250 C
Solar/Wind Harmer
0.209
233900O-025 C
Adder
2.045
232907VN8
Adder
52.128
233994AC2-023 GEN
Solar/Wind Harmer
4.667
960671AF2-358 GEN
Solar/Wind Harmer
31.064
233952AC2-187 GEN
Solar/Wind Harmer
1.951
232417X3-008 C
Solar/Wind Harmer
3.466
972251AH1-710 GEN
Adder
76.366
233918AB1-142 GEN
Solar/Wind Harmer
1.688
233982AB2-133 GEN
Solar/Wind Harmer
8.292
228202CUMB CT
Adder
24.431
228711V2-041C
Solar/Wind Harmer
0.888
971553AH1-274 GEN
Solar/Wind Harmer
3.572
230430AE1-229_GEN
Solar/Wind Harmer
12.907
230415AB2-049 C
Solar/Wind Harmer
0.277
228729W2-030 C
Solar/Wind Harmer
0.844
228304LOGAN
Adder
31.647
219623KINSLEYBEA C
Solar/Wind Harmer
0.612
219291REEVESSOUT C
Solar/Wind Harmer
0.086
219766PARADISE C
Solar/Wind Harmer
0.449
213497CHSTR7-9
Adder
3.881
219912AD2-042 GEN
Solar/Wind Harmer
1.131
219236SOUTHERNHQ C
Solar/Wind Harmer
0.096
213958STHWK5-6
Adder
3.833
219906AC1-017 C
Solar/Wind Harmer
0.314
213560DLW11-12
Adder
3.815
219610FLORENCE C
Solar/Wind Harmer
1.942
219348LDSOLAR C
Solar/Wind Harmer
0.839
219221BRL12CT1
Adder
12.51
219223BRL12CT3
Adder
12.51
213815MOSER1-3
Adder
4.948
20716028EGP_W2-019
Solar/Wind Harmer
0.643
20720828JCB_W4-025
Solar/Wind Harmer
0.628
20715028HAN_X4-015
Solar/Wind Harmer
0.414
959561AF2-247 GEN
Solar/Wind Harmer
0.673
20636028O CRK C1
Adder
9.782
971667AH1-334 GEN
Solar/Wind Harmer
3.783
219727YARDVSOLFA C
Solar/Wind Harmer
1.248
207487AE2-000G4
Solar/Wind Harmer
43.594
214194N WALES4
Adder
1.176
207445AB1-138_GEN
Solar/Wind Harmer
0.798
20628028LAKEHURS
Adder
2.589
963711AG1-223 GEN
Solar/Wind Harmer
2.025
20714828MDF_W3-079
Solar/Wind Harmer
0.419
207454AA2-184 E
Solar/Wind Harmer
1.358
20715228NPK_W1-113
Solar/Wind Harmer
0.584
219680HOPEWELLV C1
Solar/Wind Harmer
0.103
20742028HF_AC1-207
Solar/Wind Harmer
1.064
217197RE CRAN C
Solar/Wind Harmer
0.724
20635828PARLN1&2
Adder
9.944
20635028RRCT1&2
Adder
15.558
20635128RRCT3&4
Adder
15.018
218428ETC SOLAR C
Solar/Wind Harmer
0.048
217213AMBOY SO C
Solar/Wind Harmer
0.169
972275AH1-722 GEN
Adder
42.003
218449LINSOLAR C
Solar/Wind Harmer
1.334
207528AF2-192 GEN
Solar/Wind Harmer
0.733
20673628F1S_V4-069
Solar/Wind Harmer
0.238
20675428EAM_W2-061
Solar/Wind Harmer
0.25
20676428JCR_X2-075
Solar/Wind Harmer
0.452
217209CENTRL HS C
Solar/Wind Harmer
0.059
217121ECCF
Adder
0.572
217083KRNY_132
Adder
12.241
217208PARK ELE C
Solar/Wind Harmer
0.033
207439AE1-081 C O1
Solar/Wind Harmer
0.077
20674328GAR_V4-001
Solar/Wind Harmer
0.142
20675828AU_W4-064
Solar/Wind Harmer
0.222
971519AH1-257 GEN
Solar/Wind Harmer
3.205
207518AF1-320_GEN
Solar/Wind Harmer
4.633
20465127PORT CT
Adder
3.799
207437AD2-070 GEN
Solar/Wind Harmer
0.381
20671928W4-073
Solar/Wind Harmer
0.546
966181AG1-487 GEN
Solar/Wind Harmer
4.706
208909MACR G3
Adder
200.044
961301AF2-421 GEN
Solar/Wind Harmer
1.181
963151AG1-164 GEN
Solar/Wind Harmer
1.181
209023WIENIPP1
Adder
12.737
209025WIENIPP3
Adder
6.358
209010PEIP 1
Adder
0.752
212266LOR1
Solar/Wind Harmer
0.148
970237AG2-161 GEN
Solar/Wind Harmer
3.967
961341AF2-425 GEN
Solar/Wind Harmer
1.118
212174INGE
Adder
1.236
212507AE2-042_GEN
Solar/Wind Harmer
3.263
946731AF1-337 GEN
Solar/Wind Harmer
1.078
209071AE2-133 GEN
Solar/Wind Harmer
1.821
970665AG2-430 GEN
Solar/Wind Harmer
10.672
209018SUNBIPCT
Adder
8.011
205941AD2-115 GEN
Solar/Wind Harmer
0.965
972241AH1-705 GEN
Adder
6.001
20467927PC_Q59Y356
Adder
0.826
20465527S.RDG CT
Adder
2.666
970679AG2-439 GEN
Solar/Wind Harmer
1.228
209008PAXT IPP
Adder
1.515
200917MEHOOPANY_G
Solar/Wind Harmer
3.765
972271AH1-720 GEN
Adder
6.093
941421AE2-139 GEN
Solar/Wind Harmer
2.712
20328326MANOR_T86
Adder
0.124
223401AF1-299 GEN
Solar/Wind Helper
0.531
316006AB2-029 C
Solar/Wind Helper
0.149
316045AC1-158 PL2
Solar/Wind Helper
5.501
316254AC1-120 GEN1
Solar/Wind Helper
1.411
3147666LOUISA
Solar/Wind Helper
1.21
316192AB2-158 GEN
Solar/Wind Helper
2.031
316337AD2-073 GEN
Solar/Wind Helper
0.456
964211AG1-282 GEN
Solar/Wind Helper
0.403
3141726DUNNSVL
Solar/Wind Helper
1.195
3142416OLDCHRC
Solar/Wind Helper
0.771
3142416OLDCHRC
Solar/Wind Helper
0.295
3138133OCRAN
Solar/Wind Helper
0.178
3141766HARMONY
Solar/Wind Helper
0.059
3142433PROV 92
Solar/Wind Helper
1.181
3143526WINTERP
Solar/Wind Helper
1.534
3142543TWELFTH
Solar/Wind Helper
0.028
3143226MDLTHAN
Solar/Wind Helper
0.295
316159AE1-175 C
Solar/Wind Helper
0.445
316458AB2-190 GEN2
Solar/Wind Helper
1.672
3145336SMITFLD
Solar/Wind Helper
1.163
316294AC1-161 GEN
Solar/Wind Helper
5.313
316381AD1-082 GEN
Solar/Wind Helper
1.503
316375AC2-012 GEN
Solar/Wind Helper
0.759
316072AD1-144
Solar/Wind Helper
0.331
316388AE2-253 GEN
Solar/Wind Helper
1.101
3146456SLIGO L269
Solar/Wind Helper
0.289
316246AF1-032 C
Solar/Wind Helper
0.33
316336AC2-165 C
Solar/Wind Helper
1.553
238148AE2-230_GEN2
Solar/Wind Helper
0.497
3146516WINFALL
Solar/Wind Helper
0.93
3146516WINFALL
Solar/Wind Helper
0.287
315800Z1-036_GEN1
Solar/Wind Helper
1.572
3130156CHOWAN
Solar/Wind Helper
0.285
3145663CRESWEL
Solar/Wind Helper
0.793
316023GEN1_S
Solar/Wind Helper
1.07
3146206CASHIE
Solar/Wind Helper
0.281
3145893MURPHYS
Solar/Wind Helper
1.124
316322AB2-045
Solar/Wind Helper
0.313
3146776BUCKING
Solar/Wind Helper
0.112
3146173TUNIS
Solar/Wind Helper
0.28
3146926FARMVIL
Solar/Wind Helper
0.168
3145683EARLEYS
Solar/Wind Helper
0.28
3146263WOODLND
Solar/Wind Helper
0.279
3145963POPLR C
Solar/Wind Helper
0.278
316190AA2-174 GEN
Solar/Wind Helper
0.019
316011AB1-132 GEN
Solar/Wind Helper
2.995
3145823KELFORD
Solar/Wind Helper
0.278
200201DELTA2 CT2
50/50
5.614
200034PCHBTM 2
50/50
32.678
200035PCHBTM 3
50/50
32.706
200205Y1-065-CTG2
50/50
6.421
971149AH1-027 GEN
Solar/Wind Harmer
5.893
233939AC1-091 C
Solar/Wind Harmer
1.529
233970AC1-092 C
Solar/Wind Harmer
1.529
970545AG2-347 GEN
Solar/Wind Harmer
113.695
232899W1-062
Adder
16.711
233987AB2-037 GEN
Solar/Wind Harmer
19.775
972069AH1-584 GEN
Solar/Wind Harmer
15.554
972071AH1-585 GEN
Solar/Wind Harmer
15.554
232918OH NUG7
Adder
15.237
971747AH1-380 GEN
Solar/Wind Harmer
6.221
233901CHERRYDALE C
Solar/Wind Harmer
1.955
232408W1-005 C
Solar/Wind Harmer
1.739
232410W1-006 C
Solar/Wind Harmer
1.739
232905CHERITON_25
Adder
4.261
232926CRISFLD1
Adder
3.409
231940T-011
Adder
1.295
233946AB2-136 GEN
Solar/Wind Harmer
6.92
234036AF2-325 C
Solar/Wind Harmer
1.589
234041AC1-190 GEN
Solar/Wind Harmer
15.516
233984AB2-036 GEN
Solar/Wind Harmer
21.404
232424Y1-079 C
Solar/Wind Harmer
0.967
231131BLOOM ENRGY
Adder
7.454
234014AF1-036_GEN
Solar/Wind Harmer
4.631
233944AB2-135 GEN
Solar/Wind Harmer
8.936
233933AB2-153 GEN
Solar/Wind Harmer
1.917
232416X2-083
Adder
0.758
228251CARLLS#4
Adder
0.928
230422AE1-104_GEN1
Solar/Wind Harmer
49.466
230425AE1-104_GEN2
Solar/Wind Harmer
49.466
230433AD2-135 GEN
Solar/Wind Harmer
0.148
230407AD2-065 C
Solar/Wind Harmer
0.192
228307PCLP GT
Adder
17.627
228304LOGAN
Adder
35.187
972233AH1-701 GEN
Adder
6.087
219921AF1-264
Solar/Wind Harmer
0.207
213589EDDYSTN4
Adder
113.232
213587EDDYSTN3
Adder
113.219
219615MILLCREEK C
Solar/Wind Harmer
0.336
213535CROYDN11
Adder
14.323
213815MOSER1-3
Adder
4.948
213815MOSER1-3
Adder
4.948
20716428NHV_W2-082
Solar/Wind Harmer
2.464
207500AE2-000G1
Solar/Wind Harmer
43.594
207497AE2-000G2
Solar/Wind Harmer
43.594
207507AE2-000G3
Solar/Wind Harmer
43.594
20636128O CRK C2
Adder
8.919
963401AG1-189 GEN
Solar/Wind Harmer
1.589
963391AG1-188 GEN
Solar/Wind Harmer
2.648
20714928UPF_X1-085
Solar/Wind Harmer
0.561
20628028LAKEHURS
Adder
1.308
219114HARTZY_C
Solar/Wind Harmer
1.146
219817TRENTONSOL C
Solar/Wind Harmer
1.5
20641628MLH_W1-032
Solar/Wind Harmer
0.399
20720628TIN_W1-124
Solar/Wind Harmer
1.354
20716928W4-060COL
Solar/Wind Harmer
0.959
924131AB2-057 GEN
Solar/Wind Harmer
1.38
218440SUMMTASSOC C
Solar/Wind Harmer
0.171
218418LINDEN_G5
Adder
22.848
218419LINDEN_G6
Adder
22.848
972260AH1-715 GEN1
Adder
18.295
20673828FLE_V3-070
Solar/Wind Harmer
0.608
219036LINDEN_G7
Adder
22.173
219035LINDEN_G8
Adder
21.857
972261AH1-715 GEN2
Adder
21.225
207442AE1-156 GEN
Solar/Wind Harmer
0.985
20676128MHD_W3-029
Solar/Wind Harmer
0.632
217081WEATEXAS C
Solar/Wind Harmer
0.114
217202FBANKSOLAR C
Solar/Wind Harmer
0.097
217201HACKENSOLA C
Solar/Wind Harmer
0.097
972237AH1-703 GEN
Adder
13.327
217206BARNGR HS C
Solar/Wind Harmer
0.041
217086KRNY_131
Adder
12.267
217083KRNY_132
Adder
12.164
20671828STAW2-080
Solar/Wind Harmer
0.138
217204WCALDSOLAR C
Solar/Wind Harmer
0.096
20674528F3S_W2-016
Solar/Wind Harmer
1.838
20676228FRD_X1-012
Solar/Wind Harmer
0.762
207471AF2-354 C
Solar/Wind Harmer
0.653
20674928WA_W3-044
Solar/Wind Harmer
0.615
964851AG1-348 GEN
Solar/Wind Harmer
2.237
20634528N27_Y2-018
Solar/Wind Harmer
0.342
20465127PORT CT
Adder
5.041
20674128FR_U2-059
Solar/Wind Harmer
0.233
966111AG1-480 GEN
Solar/Wind Harmer
0.109
966111AG1-480 GEN
Solar/Wind Harmer
4.153
211065PSPA IPP
Solar/Wind Harmer
0.557
211065PSPA IPP
Solar/Wind Harmer
0.557
208972BECR K09
Solar/Wind Harmer
1.232
209029WAYMART-WD
Solar/Wind Harmer
3.36
209009PEIP 2
Adder
9.125
209010PEIP 1
Adder
4.135
209010PEIP 1
Adder
0.606
961541AF2-445A GEN
Solar/Wind Harmer
3.71
961431AF2-434 GEN
Solar/Wind Harmer
1.115
209054AE2-059 GEN
Solar/Wind Harmer
1.842
209059AE2-084 GEN
Solar/Wind Harmer
2.719
946751AF1-339 GEN
Solar/Wind Harmer
1.078
209130AF1-271A GEN
Solar/Wind Harmer
3.024
20465527S.RDG CT
Adder
2.579
20478527GLRA_Q45
Adder
0.268
209137AF2-361 C
Solar/Wind Harmer
2.352
226929AD2-058 GEN
Solar/Wind Helper
0.145
316447AC1-158 HLD
Solar/Wind Helper
3.782
315651AD1-115 GEN
Solar/Wind Helper
1.035
316468AD1-105 GEN
Solar/Wind Helper
1.503
966001AG1-469 GEN
Solar/Wind Helper
0.322
316077AC2-138 C
Solar/Wind Helper
0.281
966871AG1-558 GEN
Solar/Wind Helper
0.402
316487AF1-042 GEN
Solar/Wind Helper
0.301
238175AF1-290_GEN
Solar/Wind Helper
0.156
316075AC2-137 C
Solar/Wind Helper
0.45
3143526WINTERP
Solar/Wind Helper
1.534
3142946ENON
Solar/Wind Helper
0.03
238169AE2-226 GEN1
Solar/Wind Helper
0.717
238170AE2-226 GEN2
Solar/Wind Helper
0.717
316240AF1-291 C
Solar/Wind Helper
0.393
316033AB2-134 GEN
Solar/Wind Helper
1.005
315697AD1-025 GEN
Solar/Wind Helper
3.339
316236AE1-162_GEN
Solar/Wind Helper
0.391
316036AC1-147 C
Solar/Wind Helper
0.442
316316AC1-027 C
Solar/Wind Helper
0.457
3142956BIRDNECK
Solar/Wind Helper
0.195
316185AD1-033 GEN
Solar/Wind Helper
1.362
3145506HICKORY
Solar/Wind Helper
1.157
3145506HICKORY
Solar/Wind Helper
0.694
3145506HICKORY
Solar/Wind Helper
0.174
316339AD2-160 GEN
Solar/Wind Helper
1.101
316018AA1-139 ULT2
Solar/Wind Helper
1.243
316017AA1-139 ULT1
Solar/Wind Helper
1.321
3137176SLIGO L2192
Solar/Wind Helper
1.15
3130086AYDLETT
Solar/Wind Helper
1.155
3146386ELIZ CT
Solar/Wind Helper
0.288
316431W1029_GEN1
Solar/Wind Helper
1.161
316433W1029_GEN2
Solar/Wind Helper
1.161
3146516WINFALL
Solar/Wind Helper
0.287
3146516WINFALL
Solar/Wind Helper
0.287
3146516WINFALL
Solar/Wind Helper
0.287
3146626S HERTFORD
Solar/Wind Helper
0.287
3146626S HERTFORD
Solar/Wind Helper
0.287
3144356SAPONY
Solar/Wind Helper
0.514
315742AE1-103 GEN
Solar/Wind Helper
0.46
3145893MURPHYS
Solar/Wind Helper
0.403
3145893MURPHYS
Solar/Wind Helper
0.506
3146776BUCKING
Solar/Wind Helper
1.123
3146776BUCKING
Solar/Wind Helper
0.091
3146173TUNIS
Solar/Wind Helper
0.28
3146173TUNIS
Solar/Wind Helper
0.28
316181AB2-040 GEN
Solar/Wind Helper
2.001
3142666NORTHAMPTON
Solar/Wind Helper
0.278
3142666NORTHAMPTON
Solar/Wind Helper
0.278
3142666NORTHAMPTON
Solar/Wind Helper
0.278
3142666NORTHAMPTON
Solar/Wind Helper
0.167
316426AA2-053 GEN
Solar/Wind Helper
1.587
3145593CAROLNA
Solar/Wind Helper
0.278
3145593CAROLNA
Solar/Wind Helper
0.278
3147133PAMPLIN
Solar/Wind Helper
0.278
3147133PAMPLIN
Solar/Wind Helper
0.222
315821AE2-092 GEN
Solar/Wind Helper
2.571
3145796HORNRTN
Solar/Wind Helper
0.831
3132123MT JACKSON
Solar/Wind Helper
0.866
316034AC1-036 C
Solar/Wind Helper
0.289
23777901MDS_W4-102
Solar/Wind Helper
0.173
3145933PARMELE
Solar/Wind Helper
0.551
3145933PARMELE
Solar/Wind Helper
0.275
316274AC1-208 GEN
Solar/Wind Helper
1.677
235020AA1-095 C
Solar/Wind Helper
0.051
3146843MT LREL
Solar/Wind Helper
0.271
3146843MT LREL
Solar/Wind Helper
0.271
237034AC2-136 C
Solar/Wind Helper
0.221
316222AC1-221 GEN
Solar/Wind Helper
1.498
270013AE1-250 PV
Solar/Wind Helper
0.92
316197AC1-042 GEN
Solar/Wind Helper
0.234
23777801MSM_W1-116
Solar/Wind Helper
0.106
237002AB1-128_GEN
Solar/Wind Helper
0.388
237001AB1-127_GEN
Solar/Wind Helper
0.384
235063AE1-101 C2
Solar/Wind Helper
1.418
270214AC2-123 GEN
Solar/Wind Helper
0.811
238120AE2-309 GEN
Solar/Wind Helper
0.406
237025AB1-124 C
Solar/Wind Helper
0.143
237006AB1-125 GEN
Solar/Wind Helper
0.107
200202DELTA2 ST
50/50
9.527
200195DELTA ST
50/50
4.848
200052ROCKSP 1
50/50
4.056
200053ROCKSP 2
50/50
3.969
233973AC2-185 C
Solar/Wind Harmer
6.29
234033AF1-007_GEN
Solar/Wind Harmer
40.629
232904IR4
Adder
140.481
232920IR10
Adder
5.49
232432Z2-076 GEN
Solar/Wind Harmer
0.23
232912OH NUG1
Adder
15.339
232913OH NUG2
Adder
15.135
233923SMA
Solar/Wind Harmer
8.065
233990AG1-397 GEN
Solar/Wind Harmer
0.096
233955AB2-172 GEN
Solar/Wind Harmer
8.665
232813VAUGHN
Adder
1.017
231906DC3 NUG
Adder
23.945
231902DC CT7
Adder
19.143
231907DC10
Adder
5.978
233968AD2-076_GEN
Solar/Wind Harmer
11.346
970597AG2-380 GEN
Solar/Wind Harmer
7.125
232436AB1-176 C
Solar/Wind Harmer
0.392
971983AH1-536 GEN
Solar/Wind Harmer
12.748
233935AB2-179 C
Solar/Wind Harmer
4.161
231919CHRIST1
Adder
7.291
231920CHRIST2
Adder
7.129
970453AG2-297 GEN
Solar/Wind Harmer
4.088
228260V4-054C
Solar/Wind Harmer
1.51
228309CCLP NUG
Adder
37.945
228309CCLP NUG
Adder
36.094
972141AH1-641 GEN
Solar/Wind Harmer
4.221
964001AG1-254 GEN
Solar/Wind Harmer
2.98
971535AH1-265 GEN
Solar/Wind Harmer
6.223
971011AG2-627 GEN
Solar/Wind Harmer
11.199
227927V4-067C
Solar/Wind Harmer
0.29
228754AB1-001 C
Solar/Wind Harmer
0.204
219137THOSOLAR C
Solar/Wind Harmer
1.737
219272CLEANLIGHT C
Solar/Wind Harmer
0.261
219688LUMSOLAR_S C
Solar/Wind Harmer
0.288
219914AD2-027 C
Solar/Wind Harmer
0.853
213942SCHUYLKILL
Adder
5.013
213942SCHUYLKILL
Adder
3.834
213957STHWK3-4
Adder
3.833
213957STHWK3-4
Adder
3.833
213561DLWR9-10
Adder
4.989
213561DLWR9-10
Adder
3.815
219607WPEMNERT C
Solar/Wind Harmer
0.588
219224BRL12CT4
Adder
12.51
214067T20SOLAR
Solar/Wind Harmer
0.351
213611FALLS1-3
Adder
4.905
213611FALLS1-3
Adder
4.905
20717128DIX_Z2-102
Solar/Wind Harmer
1.829
20715728PEM_W1-119
Solar/Wind Harmer
0.74
20715828PEM_W1-120
Solar/Wind Harmer
0.74
970025AG2-016 GEN
Solar/Wind Harmer
3.913
971189AH1-054 GEN
Solar/Wind Harmer
1.628
207459AE1-142 C O1
Solar/Wind Harmer
1.454
219620RIDERU C
Solar/Wind Harmer
0.076
20714328BYD_X4-031
Solar/Wind Harmer
0.385
20714428HOW_X1-037
Solar/Wind Harmer
1.681
971521AH1-258 GEN
Solar/Wind Harmer
3.666
20720428HOL_W1-112
Solar/Wind Harmer
0.468
20635928PARLN3&4
Adder
9.944
218455CINNBAY_CGEN
Adder
2.439
218526CNTRALGAS2 C
Solar/Wind Harmer
0.496
218524CNTRALGAS1 C
Solar/Wind Harmer
0.495
20675528CPH_W2-050
Solar/Wind Harmer
0.622
218404KENILWRTH C
Adder
1.722
217167KRNY_14
Adder
12.241
217086KRNY_131
Adder
12.138
217147KRNY_1212
Adder
11.644
217147KRNY_1212
Adder
11.436
217146KRNY_1234
Adder
11.41
217146KRNY_1234
Adder
11.332
966261AG1-495 GEN
Solar/Wind Harmer
2.322
20676328BVR_Y1-020
Solar/Wind Harmer
0.427
207511W3-106 GEN
Solar/Wind Harmer
0.846
207530AG1-191 GEN
Solar/Wind Harmer
1.769
20674828DL_W4-046
Solar/Wind Harmer
0.825
971009AG2-626 GEN
Solar/Wind Harmer
2.085
207408W3-077 C
Solar/Wind Harmer
0.642
20675728RH_W2-091
Solar/Wind Harmer
0.434
966421AG1-511 GEN
Solar/Wind Harmer
10.917
20675928HOL_W4-097
Solar/Wind Harmer
0.165
207484AF2-139 C O1
Solar/Wind Harmer
0.639
20462827N BANGR8
Adder
0.904
20675128HRM_W1-127
Solar/Wind Harmer
0.215
209116AE2-175 GEN
Solar/Wind Harmer
5.121
961261AF2-417 GEN
Solar/Wind Harmer
1.199
209026WIENIPP4
Adder
6.294
209045AE2-271 GEN
Solar/Wind Harmer
18.602
959431AF2-234 GEN
Solar/Wind Harmer
2.151
964051AG1-259 GEN
Solar/Wind Harmer
1.442
964061AG1-260 GEN
Solar/Wind Harmer
1.442
959421AF2-233 GEN
Solar/Wind Harmer
1.075
20486527WR_V4-052
Adder
1.044
208862AG1-362 C
Solar/Wind Harmer
0.705
20390726Y2-042
Adder
2.939
20334726NME_Y1-047
Adder
2.529
203926AA2-133 GEN
Adder
2.288
3138216PACIFIC
Solar/Wind Helper
0.054
316411AF1-147_GEN1
Solar/Wind Helper
1.085
316415AF1-147_GEN2
Solar/Wind Helper
1.085
3141426STAFORD
Solar/Wind Helper
0.07
316164AC1-076 GEN
Solar/Wind Helper
1.469
316223AC1-118
Solar/Wind Helper
0.46
3141813NORNECK
Solar/Wind Helper
0.299
3141783LANCAST
Solar/Wind Helper
0.178
3141783LANCAST
Solar/Wind Helper
0.119
316312AB1-027
Solar/Wind Helper
0.565
3138133OCRAN
Solar/Wind Helper
0.089
3141913WHIT STONE
Solar/Wind Helper
0.296
316059AD1-063 C
Solar/Wind Helper
0.298
957601AF2-054 GEN
Solar/Wind Helper
0.397
3141873WAN 176
Solar/Wind Helper
0.059
315662AE1-191 GEN
Solar/Wind Helper
1.589
315666AE1-190 GEN
Solar/Wind Helper
0.397
3143873LANEXA
Solar/Wind Helper
0.177
316233AE1-074 FULL
Solar/Wind Helper
0.451
957831AF2-077 GEN
Solar/Wind Helper
0.396
316132AB2-190 GEN1
Solar/Wind Helper
1.672
316369SG1_INVT
Solar/Wind Helper
1.405
3143316POE
Solar/Wind Helper
1.151
316349AD2-085 GEN
Solar/Wind Helper
1.322
316305AF2-043 C
Solar/Wind Helper
0.388
319010AE1-072 C
Solar/Wind Helper
3.3
313526AB2-022
Solar/Wind Helper
0.439
3146486SUNBURY
Solar/Wind Helper
0.288
3146486SUNBURY
Solar/Wind Helper
0.288
316321Z2-027
Solar/Wind Helper
0.438
3145176PASQUOTANK
Solar/Wind Helper
0.178
238152AF2-075_GEN
Solar/Wind Helper
0.707
23546401DTGZ2-030
Solar/Wind Helper
0.09
316315AB2-025 C
Solar/Wind Helper
0.436
315611Z1-036_GEN2
Solar/Wind Helper
1.572
3130156CHOWAN
Solar/Wind Helper
0.285
3130156CHOWAN
Solar/Wind Helper
0.285
315816AE2-034 GEN
Solar/Wind Helper
1.295
3130546PLYMOUTH
Solar/Wind Helper
0.282
315732AD1-074 GEN1
Solar/Wind Helper
3.22
315733AD1-074 GEN2
Solar/Wind Helper
3.22
315735AD1-075 GEN1
Solar/Wind Helper
1.61
3146206CASHIE
Solar/Wind Helper
0.281
3145893MURPHYS
Solar/Wind Helper
0.759
3145893MURPHYS
Solar/Wind Helper
0.281
3145513AHOSKIE
Solar/Wind Helper
0.125
961941AG1-037 GEN
Solar/Wind Helper
0.094
3145513AHOSKIE
Solar/Wind Helper
0.28
3138266HYDRAULIC
Solar/Wind Helper
0.013
3138266HYDRAULIC
Solar/Wind Helper
0.008
946281AF1-292 GEN
Solar/Wind Helper
0.281
3146043SEABORD
Solar/Wind Helper
0.28
3145683EARLEYS
Solar/Wind Helper
0.559
3145683EARLEYS
Solar/Wind Helper
0.28
3145683EARLEYS
Solar/Wind Helper
0.28
315607AA1-063A GEN
Solar/Wind Helper
1.594
316087AB2-174 GEN
Solar/Wind Helper
1.953
3137643SOCKMAN
Solar/Wind Helper
1.112
3145796HORNRTN
Solar/Wind Helper
0.887
3145796HORNRTN
Solar/Wind Helper
0.111
3146033SCOT NK
Solar/Wind Helper
1.107
3144303KENBRDG
Solar/Wind Helper
0.221
316239AB2-077_GEN
Solar/Wind Helper
0.369
316238AB2-078_GEN
Solar/Wind Helper
0.369
316005AA1-067
Solar/Wind Helper
0.313
3145746EVERETS
Solar/Wind Helper
1.09
3145746EVERETS
Solar/Wind Helper
0.274
3145746EVERETS
Solar/Wind Helper
0.274
3145746EVERETS
Solar/Wind Helper
0.274
3148133STUARTS
Solar/Wind Helper
0.164
3148013FISHERV
Solar/Wind Helper
0.157
316420AA1-050 GEN
Solar/Wind Helper
1.562
3145573BETHELC
Solar/Wind Helper
0.272
3145573BETHELC
Solar/Wind Helper
0.272
270494AE1-108_GEN
Solar/Wind Helper
3.633
316118AC1-105 GEN
Solar/Wind Helper
1.048
3147173SINAI
Solar/Wind Helper
0.269
3147243WELCO
Solar/Wind Helper
0.168
3148463FAIRFLD
Solar/Wind Helper
0.266
316123AC1-075 GEN
Solar/Wind Helper
1.584
238208AF1-136 C
Solar/Wind Helper
0.199
270455AD2-022 GEN
Solar/Wind Helper
1.491
270457AD2-023 GEN
Solar/Wind Helper
0.983
238109AE1-109 GEN2
Solar/Wind Helper
0.095
238110AE1-109 GEN3
Solar/Wind Helper
0.095
237085AD2-009_GEN
Solar/Wind Helper
1.433
270069AE2-166 C O1
Solar/Wind Helper
1.061
238126S14_GEN_1
Solar/Wind Helper
0.637
20714528FRN_Y2-051
Solar/Wind Harmer
0.404
219276PARKLANDSO C
Solar/Wind Harmer
0.63
20716228APLW2-078
Solar/Wind Harmer
1.2
20720528MAN_W1-024
Solar/Wind Harmer
0.345
219918AC2-009 C
Solar/Wind Harmer
0.084
967451AG2-055 C O1
Solar/Wind Harmer
234.982
219612MATRIX C
Solar/Wind Harmer
0.248
218438BLK ROCK C
Solar/Wind Harmer
0.184
20635828PARLN1&2
Adder
4.504
20635928PARLN3&4
Adder
4.504
20635028RRCT1&2
Adder
15.802
20635128RRCT3&4
Adder
13.1
219908AB1-139 C
Solar/Wind Harmer
0.508
219919AE1-041 FULL
Solar/Wind Harmer
0.054
219249CENTRALDIV C
Solar/Wind Harmer
0.053
20673728F2S_V4-070
Solar/Wind Harmer
0.238
217211CAMDEN ST C
Solar/Wind Harmer
0.032
217186ESSEX_G9
Adder
21.056
217169METRODIV C
Solar/Wind Harmer
0.052
217194REDH C
Solar/Wind Harmer
0.648
20676728BRNX1-095
Solar/Wind Harmer
0.23
207510AF2-138 C
Solar/Wind Harmer
2.293
20674628WNG_W3-110
Solar/Wind Harmer
0.52
971007AG2-625 GEN
Solar/Wind Harmer
3.27
20466127PORT 5CT
Adder
33.554
20633028GILCT9
Adder
35.561
966181AG1-487 GEN
Solar/Wind Harmer
0.316
20465427SHAW CT
Adder
4.866
963161AG1-165 GEN
Solar/Wind Harmer
1.181
209025WIENIPP3
Adder
6.229
963071AG1-156 GEN
Solar/Wind Harmer
3.245
970095AG2-074 GEN
Solar/Wind Harmer
7.364
209027LOR2_Q27
Solar/Wind Harmer
5.166
209022WHFR IPP
Adder
3.709
961331AF2-424 GEN
Solar/Wind Harmer
1.118
961421AF2-433 GEN
Solar/Wind Harmer
1.115
957921AF2-086 GEN
Solar/Wind Harmer
1.084
209142AF1-226 GEN
Solar/Wind Harmer
6.455
209093AE2-110 GEN
Solar/Wind Harmer
2.788
209120AE2-241 GEN
Solar/Wind Harmer
3.689
972245AH1-707 GEN
Adder
5.983
946691AF1-333 GEN
Solar/Wind Harmer
1.078
946741AF1-338 GEN
Solar/Wind Harmer
1.078
209067AE2-060 GEN
Solar/Wind Harmer
1.216
972221AH1-695 GEN
Adder
101.471
226910AB2-157 C
Solar/Wind Helper
0.021
227287AC2-120 GEN
Solar/Wind Helper
0.512
223402AF1-300 C
Solar/Wind Helper
0.531
3141196NOKESVL
Solar/Wind Helper
1.273
316044AC1-158 PL1
Solar/Wind Helper
1.718
316450AC1-158 RIC
Solar/Wind Helper
0.458
316170AC1-121 GEN2
Solar/Wind Helper
0.47
966881AG1-559 GEN
Solar/Wind Helper
0.412
3132273ORANGE
Solar/Wind Helper
0.061
3147666LOUISA
Solar/Wind Helper
0.696
3141906WESTMOR
Solar/Wind Helper
0.121
316404AE1-155 C
Solar/Wind Helper
2.518
316473AC1-191 GEN
Solar/Wind Helper
1.821
316484AD2-074 GEN
Solar/Wind Helper
0.575
316156AD2-030 GEN
Solar/Wind Helper
0.446
316280AD1-041 GEN
Solar/Wind Helper
0.993
3142946ENON
Solar/Wind Helper
0.098
316382AG1-145 C
Solar/Wind Helper
0.394
315839AE2-212 C
Solar/Wind Helper
0.392
3145336SMITFLD
Solar/Wind Helper
0.116
315773AC2-141 GEN
Solar/Wind Helper
6.253
3144536CHRHLND
Solar/Wind Helper
0.044
3144873MCLAUGH
Solar/Wind Helper
0.007
316313AB2-026
Solar/Wind Helper
0.441
316258AE1-075 C
Solar/Wind Helper
0.397
316405AF2-144 C
Solar/Wind Helper
0.331
3146456SLIGO L269
Solar/Wind Helper
0.289
316320Y1-086
Solar/Wind Helper
0.129
238147AE2-230_GEN1
Solar/Wind Helper
0.495
238149AF1-291A_GEN
Solar/Wind Helper
0.141
316435W1029_GEN3
Solar/Wind Helper
1.161
3146516WINFALL
Solar/Wind Helper
0.287
3146626S HERTFORD
Solar/Wind Helper
0.287
3145273HOLLAND
Solar/Wind Helper
0.215
237061AD1-155 GEN
Solar/Wind Helper
0.054
3146376EDENTON
Solar/Wind Helper
0.285
315614AA2-178 GEN
Solar/Wind Helper
1.726
315737AD1-076 GEN
Solar/Wind Helper
2.754
316365GEN2_N
Solar/Wind Helper
1.07
3146206CASHIE
Solar/Wind Helper
0.281
3145893MURPHYS
Solar/Wind Helper
0.101
3145893MURPHYS
Solar/Wind Helper
0.281
3146776BUCKING
Solar/Wind Helper
0.101
3146173TUNIS
Solar/Wind Helper
0.28
3146926FARMVIL
Solar/Wind Helper
0.168
3156021HOLLOMANSOL
Solar/Wind Helper
2.131
316463AE2-346 GEN
Solar/Wind Helper
0.256
316140AB2-099
Solar/Wind Helper
0.107
966621AG1-532 GEN
Solar/Wind Helper
0.254
3146263WOODLND
Solar/Wind Helper
0.279
313506AB2-031 GEN
Solar/Wind Helper
1.266
942461AE2-259 GEN
Solar/Wind Helper
1.88
3142666NORTHAMPTON
Solar/Wind Helper
0.278
3145963POPLR C
Solar/Wind Helper
0.278
3147043LAWRENC
Solar/Wind Helper
0.167
316317KELFORD C
Solar/Wind Helper
0.237
3145823KELFORD
Solar/Wind Helper
0.278
3147133PAMPLIN
Solar/Wind Helper
0.872
316478AD1-087 GEN
Solar/Wind Helper
1.356
316486AD2-202 GEN
Solar/Wind Helper
0.397
3145796HORNRTN
Solar/Wind Helper
1.109
3145796HORNRTN
Solar/Wind Helper
0.277
315785AD2-033 C
Solar/Wind Helper
3.219
316210AC1-098 GEN
Solar/Wind Helper
2.225
3145933PARMELE
Solar/Wind Helper
0.275
316131AB2-060 GEN
Solar/Wind Helper
1.676
316499AE2-029_GEN
Solar/Wind Helper
0.923
3145746EVERETS
Solar/Wind Helper
0.274
3145746EVERETS
Solar/Wind Helper
0.274
3148013FISHERV
Solar/Wind Helper
0.274
315724AD1-057 GEN
Solar/Wind Helper
0.81
316327AA2-057 GEN
Solar/Wind Helper
1.559
3146233WITAKRS
Solar/Wind Helper
0.293
3146233WITAKRS
Solar/Wind Helper
0.185
3146073TAR RVR
Solar/Wind Helper
0.272
3146083TARBORO
Solar/Wind Helper
0.272
3138543CONSLDL
Solar/Wind Helper
0.179
3145543BTLEBRO
Solar/Wind Helper
0.271
3145543BTLEBRO
Solar/Wind Helper
0.271
316248AF1-058 C
Solar/Wind Helper
0.361
316095T157 G97
Solar/Wind Helper
1.231
315616AA1-038_C
Solar/Wind Helper
1.207
23583801GRNGAP
Solar/Wind Helper
4.532
316283AC2-100 C
Solar/Wind Helper
1.4
238221AF1-254 C O1
Solar/Wind Helper
0.257
238108AE1-109 GEN1
Solar/Wind Helper
0.095
3147312GRETNA
Solar/Wind Helper
0.05
270197AD1-017 GEN1
Solar/Wind Helper
1.334
235067AD1-061 GEN
Solar/Wind Helper
0.439
270018AE2-047 C O1
Solar/Wind Helper
0.865
943811AF1-049 GEN
Solar/Wind Helper
1.493
270336AE1-100 GEN
Solar/Wind Helper
1.036
237030AB1-096 C
Solar/Wind Helper
0.062
235531U2-073 GEN
Solar/Wind Helper
2.539
235054AD2-180 GEN
Solar/Wind Helper
1.52
238117U2-030
Solar/Wind Helper
0.261
238185AF2-356 C
Solar/Wind Helper
1.919
316174AB2-169 GEN
Solar/Wind Helper
0.708
3145783HORNRTN
Solar/Wind Helper
0.278
3145796HORNRTN
Solar/Wind Helper
0.915
3145796HORNRTN
Solar/Wind Helper
0.277
316212AC1-099_GEN
Solar/Wind Helper
1.236
316129AC1-054 GEN
Solar/Wind Helper
1.364
316237AB2-079_GEN
Solar/Wind Helper
0.369
3147983MERCK5
Solar/Wind Helper
0.11
3145746EVERETS
Solar/Wind Helper
0.274
3145746EVERETS
Solar/Wind Helper
0.274
315722AD1-056 GEN
Solar/Wind Helper
1.473
315687AD1-152 GEN
Solar/Wind Helper
1.471
316494AC1-189 GEN
Solar/Wind Helper
1.668
3146233WITAKRS
Solar/Wind Helper
1.083
961671AG1-007 GEN
Solar/Wind Helper
0.195
3146083TARBORO
Solar/Wind Helper
0.272
3145543BTLEBRO
Solar/Wind Helper
0.271
3145543BTLEBRO
Solar/Wind Helper
0.217
316359AB2-059 GEN
Solar/Wind Helper
2.064
316049AB1-081 GEN
Solar/Wind Helper
1.651
316097T157 G90
Solar/Wind Helper
1.231
316003AC1-222 GEN
Solar/Wind Helper
1.157
23779801AA1-109
Solar/Wind Helper
0.183
237080AD1-060 GEN
Solar/Wind Helper
0.312
3147123OTTER R
Solar/Wind Helper
0.15
270016AE1-250 BESS
Solar/Wind Helper
0.92
3147312GRETNA
Solar/Wind Helper
0.199
3146802CHATHAM
Solar/Wind Helper
0.187
237038AE2-054 C
Solar/Wind Helper
0.242
270173AC1-122 GEN
Solar/Wind Helper
1.585
964991AG1-363 GEN
Solar/Wind Helper
3.565
235062AE1-101 C1
Solar/Wind Helper
1.418
958121AF2-106 GEN
Solar/Wind Helper
1.719
23750701CROSSCHOOL
Solar/Wind Helper
1.107
238127S14_GEN_2
Solar/Wind Helper
0.637
238118U2-030_1
Solar/Wind Helper
0.261
HAMLETPJM->LTFIMP_HAMLET
CLTF
6.529
G-007ALTFEXP_G-007A->PJM
CMTX
68.717
CBM NorthLTFEXP_CBM-N->PJM
CBM
95.198
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
5.235
BlueGrassPJM->LTFIMP_BlueG
CLTF
16.312
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
178.798
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.836
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
24.685

Details for PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line l/o AP_P2-3_PE-500-019B_SRT-A


Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-500-019B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:162.94 %
Rating:3620.0 MVA
Rating Type:B
MVA to Mitigate:5898.32
MW Contribution:10.53
Bus #Bus NameTypeMW Contribution
200201DELTA2 CT2
50/50
5.344
200034PCHBTM 2
50/50
31.103
200035PCHBTM 3
50/50
31.115
200205Y1-065-CTG2
50/50
6.105
971149AH1-027 GEN
Solar/Wind Harmer
5.562
233939AC1-091 C
Solar/Wind Harmer
1.443
233970AC1-092 C
Solar/Wind Harmer
1.443
970545AG2-347 GEN
Solar/Wind Harmer
107.291
232899W1-062
Adder
15.77
233987AB2-037 GEN
Solar/Wind Harmer
18.659
972069AH1-584 GEN
Solar/Wind Harmer
14.677
972071AH1-585 GEN
Solar/Wind Harmer
14.677
233901CHERRYDALE C
Solar/Wind Harmer
1.845
232408W1-005 C
Solar/Wind Harmer
1.641
232410W1-006 C
Solar/Wind Harmer
1.641
232918OH NUG7
Adder
14.378
971747AH1-380 GEN
Solar/Wind Harmer
5.871
232905CHERITON_25
Adder
4.021
232926CRISFLD1
Adder
3.216
231940T-011
Adder
1.222
233946AB2-136 GEN
Solar/Wind Harmer
6.529
234036AF2-325 C
Solar/Wind Harmer
1.5
234041AC1-190 GEN
Solar/Wind Harmer
14.639
233984AB2-036 GEN
Solar/Wind Harmer
20.183
232424Y1-079 C
Solar/Wind Harmer
0.911
231131BLOOM ENRGY
Adder
7.028
234014AF1-036_GEN
Solar/Wind Harmer
4.366
233944AB2-135 GEN
Solar/Wind Harmer
8.423
233933AB2-153 GEN
Solar/Wind Harmer
1.806
232416X2-083
Adder
0.714
228251CARLLS#4
Adder
0.873
230422AE1-104_GEN1
Solar/Wind Harmer
46.538
230425AE1-104_GEN2
Solar/Wind Harmer
46.538
230433AD2-135 GEN
Solar/Wind Harmer
0.139
230407AD2-065 C
Solar/Wind Harmer
0.181
228307PCLP GT
Adder
16.574
228304LOGAN
Adder
33.081
972233AH1-701 GEN
Adder
5.722
219921AF1-264
Solar/Wind Harmer
0.194
213589EDDYSTN4
Adder
106.219
213587EDDYSTN3
Adder
106.207
219615MILLCREEK C
Solar/Wind Harmer
0.315
213535CROYDN11
Adder
13.445
213815MOSER1-3
Adder
4.643
213815MOSER1-3
Adder
4.643
20716428NHV_W2-082
Solar/Wind Harmer
2.313
207500AE2-000G1
Solar/Wind Harmer
40.922
207497AE2-000G2
Solar/Wind Harmer
40.922
207507AE2-000G3
Solar/Wind Harmer
40.922
20636128O CRK C2
Adder
8.372
963401AG1-189 GEN
Solar/Wind Harmer
1.492
963391AG1-188 GEN
Solar/Wind Harmer
2.485
20714928UPF_X1-085
Solar/Wind Harmer
0.526
20628028LAKEHURS
Adder
1.228
219114HARTZY_C
Solar/Wind Harmer
1.075
219817TRENTONSOL C
Solar/Wind Harmer
1.406
20641628MLH_W1-032
Solar/Wind Harmer
0.374
20720628TIN_W1-124
Solar/Wind Harmer
1.269
20716928W4-060COL
Solar/Wind Harmer
0.899
924131AB2-057 GEN
Solar/Wind Harmer
1.293
218440SUMMTASSOC C
Solar/Wind Harmer
0.16
218418LINDEN_G5
Adder
21.39
218419LINDEN_G6
Adder
21.39
972260AH1-715 GEN1
Adder
17.128
20673828FLE_V3-070
Solar/Wind Harmer
0.569
219036LINDEN_G7
Adder
20.753
219035LINDEN_G8
Adder
20.457
972261AH1-715 GEN2
Adder
19.866
207442AE1-156 GEN
Solar/Wind Harmer
0.922
20676128MHD_W3-029
Solar/Wind Harmer
0.591
217081WEATEXAS C
Solar/Wind Harmer
0.106
217202FBANKSOLAR C
Solar/Wind Harmer
0.091
217201HACKENSOLA C
Solar/Wind Harmer
0.09
972237AH1-703 GEN
Adder
12.468
217206BARNGR HS C
Solar/Wind Harmer
0.038
217086KRNY_131
Adder
11.476
217083KRNY_132
Adder
11.379
20671828STAW2-080
Solar/Wind Harmer
0.129
200202DELTA2 ST
50/50
9.068
200195DELTA ST
50/50
4.614
200052ROCKSP 1
50/50
3.856
200053ROCKSP 2
50/50
3.773
233973AC2-185 C
Solar/Wind Harmer
5.937
234033AF1-007_GEN
Solar/Wind Harmer
38.34
232904IR4
Adder
132.568
232920IR10
Adder
5.181
232432Z2-076 GEN
Solar/Wind Harmer
0.217
232912OH NUG1
Adder
14.475
232913OH NUG2
Adder
14.282
233990AG1-397 GEN
Solar/Wind Harmer
0.09
233923SMA
Solar/Wind Harmer
7.61
233955AB2-172 GEN
Solar/Wind Harmer
8.175
232813VAUGHN
Adder
0.96
231906DC3 NUG
Adder
22.575
231902DC CT7
Adder
18.047
231907DC10
Adder
5.636
233968AD2-076_GEN
Solar/Wind Harmer
10.696
970597AG2-380 GEN
Solar/Wind Harmer
6.716
232436AB1-176 C
Solar/Wind Harmer
0.369
971983AH1-536 GEN
Solar/Wind Harmer
12.014
233935AB2-179 C
Solar/Wind Harmer
3.916
231919CHRIST1
Adder
6.862
231920CHRIST2
Adder
6.709
970453AG2-297 GEN
Solar/Wind Harmer
3.848
228260V4-054C
Solar/Wind Harmer
1.421
228309CCLP NUG
Adder
35.691
228309CCLP NUG
Adder
33.95
972141AH1-641 GEN
Solar/Wind Harmer
3.97
964001AG1-254 GEN
Solar/Wind Harmer
2.803
971535AH1-265 GEN
Solar/Wind Harmer
5.853
971011AG2-627 GEN
Solar/Wind Harmer
10.531
227927V4-067C
Solar/Wind Harmer
0.273
228754AB1-001 C
Solar/Wind Harmer
0.191
219137THOSOLAR C
Solar/Wind Harmer
1.632
219272CLEANLIGHT C
Solar/Wind Harmer
0.245
219688LUMSOLAR_S C
Solar/Wind Harmer
0.271
219914AD2-027 C
Solar/Wind Harmer
0.801
213942SCHUYLKILL
Adder
4.702
213942SCHUYLKILL
Adder
3.596
213957STHWK3-4
Adder
3.595
213957STHWK3-4
Adder
3.595
213561DLWR9-10
Adder
4.681
213561DLWR9-10
Adder
3.58
219607WPEMNERT C
Solar/Wind Harmer
0.552
219224BRL12CT4
Adder
11.745
214067T20SOLAR
Solar/Wind Harmer
0.329
213611FALLS1-3
Adder
4.603
213611FALLS1-3
Adder
4.603
20717128DIX_Z2-102
Solar/Wind Harmer
1.717
20715728PEM_W1-119
Solar/Wind Harmer
0.695
20715828PEM_W1-120
Solar/Wind Harmer
0.695
970025AG2-016 GEN
Solar/Wind Harmer
3.672
971189AH1-054 GEN
Solar/Wind Harmer
1.528
207459AE1-142 C O1
Solar/Wind Harmer
1.364
219620RIDERU C
Solar/Wind Harmer
0.071
20714328BYD_X4-031
Solar/Wind Harmer
0.361
20714428HOW_X1-037
Solar/Wind Harmer
1.576
971521AH1-258 GEN
Solar/Wind Harmer
3.437
20720428HOL_W1-112
Solar/Wind Harmer
0.439
20635928PARLN3&4
Adder
9.316
218455CINNBAY_CGEN
Adder
2.285
218526CNTRALGAS2 C
Solar/Wind Harmer
0.464
218524CNTRALGAS1 C
Solar/Wind Harmer
0.463
20675528CPH_W2-050
Solar/Wind Harmer
0.582
218404KENILWRTH C
Adder
1.612
217167KRNY_14
Adder
11.452
217086KRNY_131
Adder
11.355
217147KRNY_1212
Adder
10.893
217147KRNY_1212
Adder
10.698
217146KRNY_1234
Adder
10.674
217146KRNY_1234
Adder
10.601
966261AG1-495 GEN
Solar/Wind Harmer
2.168
20676328BVR_Y1-020
Solar/Wind Harmer
0.399
207511W3-106 GEN
Solar/Wind Harmer
0.79
207530AG1-191 GEN
Solar/Wind Harmer
1.652
20674828DL_W4-046
Solar/Wind Harmer
0.769
971009AG2-626 GEN
Solar/Wind Harmer
1.945
207408W3-077 C
Solar/Wind Harmer
0.599
217204WCALDSOLAR C
Solar/Wind Harmer
0.09
20674528F3S_W2-016
Solar/Wind Harmer
1.718
20676228FRD_X1-012
Solar/Wind Harmer
0.711
207471AF2-354 C
Solar/Wind Harmer
0.609
20674928WA_W3-044
Solar/Wind Harmer
0.574
200200DELTA2 CT1
50/50
5.344
200193DELTA CT2
50/50
2.986
200203Y1-065-STG
50/50
10.586
200055ROCKSP 4
50/50
3.812
233971AC1-093 C
Solar/Wind Harmer
1.289
970695AG2-447 GEN
Solar/Wind Harmer
5.887
972133AH1-634 GEN
Solar/Wind Harmer
16.256
972073AH1-586 GEN
Solar/Wind Harmer
15.36
232406W1-004 FULL
Solar/Wind Harmer
1.641
232914OH NUG3
Adder
14.475
232916OH NUG5
Adder
14.475
232921TASLEY2G
Adder
8.46
233990AG1-397 GEN
Solar/Wind Harmer
1.88
233996TM1833_GEN
Solar/Wind Harmer
2.076
233997TMININ_4.2
Solar/Wind Harmer
2.076
233940AF2-379 C
Solar/Wind Harmer
0.306
233900O-025 C
Adder
1.929
234015AF2-250 C
Solar/Wind Harmer
0.197
233994AC2-023 GEN
Solar/Wind Harmer
4.403
232907VN8
Adder
49.187
960671AF2-358 GEN
Solar/Wind Harmer
29.309
233952AC2-187 GEN
Solar/Wind Harmer
1.841
232417X3-008 C
Solar/Wind Harmer
3.27
972251AH1-710 GEN
Adder
72.059
233918AB1-142 GEN
Solar/Wind Harmer
1.591
233982AB2-133 GEN
Solar/Wind Harmer
7.814
228202CUMB CT
Adder
22.991
228711V2-041C
Solar/Wind Harmer
0.835
971553AH1-274 GEN
Solar/Wind Harmer
3.361
230430AE1-229_GEN
Solar/Wind Harmer
12.141
230415AB2-049 C
Solar/Wind Harmer
0.261
228729W2-030 C
Solar/Wind Harmer
0.794
228304LOGAN
Adder
29.753
219623KINSLEYBEA C
Solar/Wind Harmer
0.575
219291REEVESSOUT C
Solar/Wind Harmer
0.081
219766PARADISE C
Solar/Wind Harmer
0.422
213497CHSTR7-9
Adder
3.641
219912AD2-042 GEN
Solar/Wind Harmer
1.063
219236SOUTHERNHQ C
Solar/Wind Harmer
0.09
213958STHWK5-6
Adder
3.595
219906AC1-017 C
Solar/Wind Harmer
0.295
213560DLW11-12
Adder
3.58
219610FLORENCE C
Solar/Wind Harmer
1.823
219348LDSOLAR C
Solar/Wind Harmer
0.788
219221BRL12CT1
Adder
11.745
219223BRL12CT3
Adder
11.745
213815MOSER1-3
Adder
4.643
20716028EGP_W2-019
Solar/Wind Harmer
0.604
20720828JCB_W4-025
Solar/Wind Harmer
0.59
20715028HAN_X4-015
Solar/Wind Harmer
0.388
959561AF2-247 GEN
Solar/Wind Harmer
0.631
20636028O CRK C1
Adder
9.182
971667AH1-334 GEN
Solar/Wind Harmer
3.55
219727YARDVSOLFA C
Solar/Wind Harmer
1.17
20714528FRN_Y2-051
Solar/Wind Harmer
0.379
219276PARKLANDSO C
Solar/Wind Harmer
0.591
20716228APLW2-078
Solar/Wind Harmer
1.125
20720528MAN_W1-024
Solar/Wind Harmer
0.324
219918AC2-009 C
Solar/Wind Harmer
0.078
967451AG2-055 C O1
Solar/Wind Harmer
220.269
219612MATRIX C
Solar/Wind Harmer
0.233
218438BLK ROCK C
Solar/Wind Harmer
0.172
20635828PARLN1&2
Adder
4.219
20635928PARLN3&4
Adder
4.219
20635028RRCT1&2
Adder
14.802
20635128RRCT3&4
Adder
12.271
219908AB1-139 C
Solar/Wind Harmer
0.476
219919AE1-041 FULL
Solar/Wind Harmer
0.05
219249CENTRALDIV C
Solar/Wind Harmer
0.049
20673728F2S_V4-070
Solar/Wind Harmer
0.222
217211CAMDEN ST C
Solar/Wind Harmer
0.03
217186ESSEX_G9
Adder
19.698
217169METRODIV C
Solar/Wind Harmer
0.049
217194REDH C
Solar/Wind Harmer
0.606
20676728BRNX1-095
Solar/Wind Harmer
0.215
207510AF2-138 C
Solar/Wind Harmer
2.141
20674628WNG_W3-110
Solar/Wind Harmer
0.486
971007AG2-625 GEN
Solar/Wind Harmer
3.05
20466127PORT 5CT
Adder
31.289
20633028GILCT9
Adder
33.118
966181AG1-487 GEN
Solar/Wind Harmer
0.294
20465427SHAW CT
Adder
4.538
963161AG1-165 GEN
Solar/Wind Harmer
1.099
209025WIENIPP3
Adder
5.794
963071AG1-156 GEN
Solar/Wind Harmer
3.019
970095AG2-074 GEN
Solar/Wind Harmer
6.851
209027LOR2_Q27
Solar/Wind Harmer
4.797
209022WHFR IPP
Adder
3.444
961331AF2-424 GEN
Solar/Wind Harmer
1.038
961421AF2-433 GEN
Solar/Wind Harmer
1.035
957921AF2-086 GEN
Solar/Wind Harmer
1.007
209142AF1-226 GEN
Solar/Wind Harmer
5.993
209093AE2-110 GEN
Solar/Wind Harmer
2.588
209120AE2-241 GEN
Solar/Wind Harmer
3.424
972245AH1-707 GEN
Adder
5.552
946691AF1-333 GEN
Solar/Wind Harmer
1
946741AF1-338 GEN
Solar/Wind Harmer
1
209067AE2-060 GEN
Solar/Wind Harmer
1.1
972221AH1-695 GEN
Adder
89.197
226910AB2-157 C
Solar/Wind Helper
0.024
227287AC2-120 GEN
Solar/Wind Helper
0.567
223402AF1-300 C
Solar/Wind Helper
0.611
3141196NOKESVL
Solar/Wind Helper
1.156
316044AC1-158 PL1
Solar/Wind Helper
1.576
316450AC1-158 RIC
Solar/Wind Helper
0.42
966881AG1-559 GEN
Solar/Wind Helper
0.382
316170AC1-121 GEN2
Solar/Wind Helper
0.431
3141906WESTMOR
Solar/Wind Helper
0.112
3147666LOUISA
Solar/Wind Helper
0.639
3132273ORANGE
Solar/Wind Helper
0.056
316404AE1-155 C
Solar/Wind Helper
2.329
316473AC1-191 GEN
Solar/Wind Helper
1.683
316484AD2-074 GEN
Solar/Wind Helper
0.532
316156AD2-030 GEN
Solar/Wind Helper
0.412
316280AD1-041 GEN
Solar/Wind Helper
0.918
3142946ENON
Solar/Wind Helper
0.091
316382AG1-145 C
Solar/Wind Helper
0.364
315839AE2-212 C
Solar/Wind Helper
0.362
3145336SMITFLD
Solar/Wind Helper
0.107
315773AC2-141 GEN
Solar/Wind Helper
5.765
3144536CHRHLND
Solar/Wind Helper
0.04
3144873MCLAUGH
Solar/Wind Helper
0.007
3146456SLIGO L269
Solar/Wind Helper
0.266
316313AB2-026
Solar/Wind Helper
0.406
316258AE1-075 C
Solar/Wind Helper
0.365
316405AF2-144 C
Solar/Wind Helper
0.304
316320Y1-086
Solar/Wind Helper
0.119
316435W1029_GEN3
Solar/Wind Helper
1.069
3146516WINFALL
Solar/Wind Helper
0.265
3146626S HERTFORD
Solar/Wind Helper
0.264
3145273HOLLAND
Solar/Wind Helper
0.198
3146376EDENTON
Solar/Wind Helper
0.262
315614AA2-178 GEN
Solar/Wind Helper
1.589
315737AD1-076 GEN
Solar/Wind Helper
2.535
316365GEN2_N
Solar/Wind Helper
0.985
3146206CASHIE
Solar/Wind Helper
0.259
3145893MURPHYS
Solar/Wind Helper
0.093
3145893MURPHYS
Solar/Wind Helper
0.259
3146173TUNIS
Solar/Wind Helper
0.258
3156021HOLLOMANSOL
Solar/Wind Helper
1.961
316463AE2-346 GEN
Solar/Wind Helper
0.235
316140AB2-099
Solar/Wind Helper
0.098
3146776BUCKING
Solar/Wind Helper
0.093
966621AG1-532 GEN
Solar/Wind Helper
0.234
3146926FARMVIL
Solar/Wind Helper
0.154
3146263WOODLND
Solar/Wind Helper
0.257
313506AB2-031 GEN
Solar/Wind Helper
1.165
238147AE2-230_GEN1
Solar/Wind Helper
0.442
238149AF1-291A_GEN
Solar/Wind Helper
0.126
3142666NORTHAMPTON
Solar/Wind Helper
0.256
3145963POPLR C
Solar/Wind Helper
0.256
237061AD1-155 GEN
Solar/Wind Helper
0.049
942461AE2-259 GEN
Solar/Wind Helper
1.726
316317KELFORD C
Solar/Wind Helper
0.218
3145823KELFORD
Solar/Wind Helper
0.256
3147043LAWRENC
Solar/Wind Helper
0.153
3147133PAMPLIN
Solar/Wind Helper
0.801
3145796HORNRTN
Solar/Wind Helper
1.02
3145796HORNRTN
Solar/Wind Helper
0.255
316478AD1-087 GEN
Solar/Wind Helper
1.246
316486AD2-202 GEN
Solar/Wind Helper
0.365
316210AC1-098 GEN
Solar/Wind Helper
2.046
315785AD2-033 C
Solar/Wind Helper
2.956
3145933PARMELE
Solar/Wind Helper
0.253
316131AB2-060 GEN
Solar/Wind Helper
1.539
3145746EVERETS
Solar/Wind Helper
0.252
3145746EVERETS
Solar/Wind Helper
0.252
315724AD1-057 GEN
Solar/Wind Helper
0.744
316327AA2-057 GEN
Solar/Wind Helper
1.433
3146233WITAKRS
Solar/Wind Helper
0.269
3146233WITAKRS
Solar/Wind Helper
0.17
3146073TAR RVR
Solar/Wind Helper
0.25
3146083TARBORO
Solar/Wind Helper
0.25
3138543CONSLDL
Solar/Wind Helper
0.165
3148013FISHERV
Solar/Wind Helper
0.249
3145543BTLEBRO
Solar/Wind Helper
0.249
3145543BTLEBRO
Solar/Wind Helper
0.249
316499AE2-029_GEN
Solar/Wind Helper
0.838
316248AF1-058 C
Solar/Wind Helper
0.331
315616AA1-038_C
Solar/Wind Helper
1.097
316283AC2-100 C
Solar/Wind Helper
1.283
316095T157 G97
Solar/Wind Helper
1.092
23583801GRNGAP
Solar/Wind Helper
4.045
238221AF1-254 C O1
Solar/Wind Helper
0.23
3147312GRETNA
Solar/Wind Helper
0.045
270197AD1-017 GEN1
Solar/Wind Helper
1.219
238108AE1-109 GEN1
Solar/Wind Helper
0.083
270018AE2-047 C O1
Solar/Wind Helper
0.79
200192DELTA CT1
50/50
2.986
200194DELTA CT3
50/50
2.986
200204Y1-065-CTG1
50/50
6.105
200054ROCKSP 3
50/50
3.894
232901NORTHST
Adder
13.676
233972AC1-094 C
Solar/Wind Harmer
1.09
232900DEMECSMY
Adder
15.127
232434Z2-077 GEN
Solar/Wind Harmer
0.41
972177AH1-672 GEN
Solar/Wind Harmer
22.02
232404W1-003 C
Solar/Wind Harmer
1.641
232917OH NUG6
Adder
14.41
232915OH NUG4
Adder
14.378
233998TM1NIN_3.36
Solar/Wind Harmer
2.076
971195AH1-057 GEN
Solar/Wind Harmer
1.794
232428Y3-058 C
Solar/Wind Harmer
1.367
232919VN10
Adder
4.594
965821AG1-450 GEN
Solar/Wind Harmer
8.52
232426Y1-080 FULL
Solar/Wind Harmer
0.313
970277AG2-181 GEN
Solar/Wind Harmer
8.206
233964AF2-378 GEN
Solar/Wind Harmer
0.209
233954AC2-188 GEN
Solar/Wind Harmer
1.841
233950AC2-186 GEN
Solar/Wind Harmer
0.92
232910NRG_G1
Adder
14.045
234012AE2-112_GEN
Solar/Wind Harmer
3.711
232422X3-066 FULL
Solar/Wind Harmer
0.403
233930AB2-032 GEN
Solar/Wind Harmer
1.339
233915AB1-141 GEN
Solar/Wind Harmer
1.591
231918WEST 1
Adder
5.216
231917EM10
Adder
3.634
228206SHRMN CT
Adder
23.043
228732V1-021 C
Adder
0.262
945431AF1-208 GEN
Solar/Wind Harmer
11.937
970997AG2-616 GEN
Solar/Wind Harmer
13.234
228351V2-046C
Solar/Wind Harmer
2.776
230511AF1-262
Solar/Wind Harmer
0.252
228728W1-130C
Solar/Wind Harmer
0.914
230434AG1-499 GEN
Solar/Wind Harmer
0.795
219258KINSLEYDEP C
Solar/Wind Harmer
0.435
218660EHAMPSOLAR C
Solar/Wind Harmer
0.234
219287REEVESEAST C
Solar/Wind Harmer
1.802
219686LUMSOLAR_N C
Solar/Wind Harmer
0.271
219904AC1-010 C
Solar/Wind Harmer
0.507
213497CHSTR7-9
Adder
3.641
213497CHSTR7-9
Adder
3.641
219907AC1-030 C
Solar/Wind Harmer
0.185
213958STHWK5-6
Adder
3.595
213560DLW11-12
Adder
3.58
219304NAMERICA C
Solar/Wind Harmer
0.409
219222BRL12CT2
Adder
11.745
20720728JCB_W1-129
Solar/Wind Harmer
0.388
213611FALLS1-3
Adder
4.603
207522AF2-254 C
Solar/Wind Harmer
1.867
207487AE2-000G4
Solar/Wind Harmer
40.922
214194N WALES4
Adder
1.103
207445AB1-138_GEN
Solar/Wind Harmer
0.749
20628028LAKEHURS
Adder
2.429
963711AG1-223 GEN
Solar/Wind Harmer
1.9
20714828MDF_W3-079
Solar/Wind Harmer
0.393
207454AA2-184 E
Solar/Wind Harmer
1.274
20715228NPK_W1-113
Solar/Wind Harmer
0.548
219680HOPEWELLV C1
Solar/Wind Harmer
0.097
20742028HF_AC1-207
Solar/Wind Harmer
0.998
217197RE CRAN C
Solar/Wind Harmer
0.679
20635828PARLN1&2
Adder
9.316
20635028RRCT1&2
Adder
14.574
20635128RRCT3&4
Adder
14.068
218428ETC SOLAR C
Solar/Wind Harmer
0.045
217213AMBOY SO C
Solar/Wind Harmer
0.158
972275AH1-722 GEN
Adder
39.323
218449LINSOLAR C
Solar/Wind Harmer
1.248
207528AF2-192 GEN
Solar/Wind Harmer
0.686
20673628F1S_V4-069
Solar/Wind Harmer
0.222
20675428EAM_W2-061
Solar/Wind Harmer
0.234
20676428JCR_X2-075
Solar/Wind Harmer
0.423
217209CENTRL HS C
Solar/Wind Harmer
0.055
217121ECCF
Adder
0.535
217083KRNY_132
Adder
11.452
217208PARK ELE C
Solar/Wind Harmer
0.031
207439AE1-081 C O1
Solar/Wind Harmer
0.072
20674328GAR_V4-001
Solar/Wind Harmer
0.132
20675828AU_W4-064
Solar/Wind Harmer
0.208
971519AH1-257 GEN
Solar/Wind Harmer
2.989
207518AF1-320_GEN
Solar/Wind Harmer
4.32
20465127PORT CT
Adder
3.542
207437AD2-070 GEN
Solar/Wind Harmer
0.355
20671928W4-073
Solar/Wind Harmer
0.509
966181AG1-487 GEN
Solar/Wind Harmer
4.382
208909MACR G3
Adder
186.413
961301AF2-421 GEN
Solar/Wind Harmer
1.099
963151AG1-164 GEN
Solar/Wind Harmer
1.099
209023WIENIPP1
Adder
11.846
209025WIENIPP3
Adder
5.913
209010PEIP 1
Adder
0.7
212266LOR1
Solar/Wind Harmer
0.138
970237AG2-161 GEN
Solar/Wind Harmer
3.684
961341AF2-425 GEN
Solar/Wind Harmer
1.038
212174INGE
Adder
1.148
212507AE2-042_GEN
Solar/Wind Harmer
3.027
946731AF1-337 GEN
Solar/Wind Harmer
1
209071AE2-133 GEN
Solar/Wind Harmer
1.689
970665AG2-430 GEN
Solar/Wind Harmer
9.896
209018SUNBIPCT
Adder
7.428
205941AD2-115 GEN
Solar/Wind Harmer
0.883
972241AH1-705 GEN
Adder
5.554
20467927PC_Q59Y356
Adder
0.749
20465527S.RDG CT
Adder
2.414
970679AG2-439 GEN
Solar/Wind Harmer
1.137
209008PAXT IPP
Adder
1.336
200917MEHOOPANY_G
Solar/Wind Harmer
3.476
223401AF1-299 GEN
Solar/Wind Helper
0.611
316006AB2-029 C
Solar/Wind Helper
0.136
316045AC1-158 PL2
Solar/Wind Helper
5.046
316254AC1-120 GEN1
Solar/Wind Helper
1.292
316337AD2-073 GEN
Solar/Wind Helper
0.423
3147666LOUISA
Solar/Wind Helper
1.111
316192AB2-158 GEN
Solar/Wind Helper
1.865
964211AG1-282 GEN
Solar/Wind Helper
0.373
3141726DUNNSVL
Solar/Wind Helper
1.106
3138133OCRAN
Solar/Wind Helper
0.164
3142416OLDCHRC
Solar/Wind Helper
0.712
3142416OLDCHRC
Solar/Wind Helper
0.273
3141766HARMONY
Solar/Wind Helper
0.055
3142433PROV 92
Solar/Wind Helper
1.091
3142543TWELFTH
Solar/Wind Helper
0.026
3143526WINTERP
Solar/Wind Helper
1.414
3143226MDLTHAN
Solar/Wind Helper
0.272
316159AE1-175 C
Solar/Wind Helper
0.411
316458AB2-190 GEN2
Solar/Wind Helper
1.542
3145336SMITFLD
Solar/Wind Helper
1.072
316294AC1-161 GEN
Solar/Wind Helper
4.898
316381AD1-082 GEN
Solar/Wind Helper
1.385
316375AC2-012 GEN
Solar/Wind Helper
0.7
316072AD1-144
Solar/Wind Helper
0.305
316388AE2-253 GEN
Solar/Wind Helper
1.015
3146456SLIGO L269
Solar/Wind Helper
0.266
316246AF1-032 C
Solar/Wind Helper
0.304
316336AC2-165 C
Solar/Wind Helper
1.428
3146516WINFALL
Solar/Wind Helper
0.857
3146516WINFALL
Solar/Wind Helper
0.265
315800Z1-036_GEN1
Solar/Wind Helper
1.448
3130156CHOWAN
Solar/Wind Helper
0.262
3145663CRESWEL
Solar/Wind Helper
0.73
316023GEN1_S
Solar/Wind Helper
0.985
3146206CASHIE
Solar/Wind Helper
0.259
3145893MURPHYS
Solar/Wind Helper
1.034
3146173TUNIS
Solar/Wind Helper
0.258
316322AB2-045
Solar/Wind Helper
0.287
3146776BUCKING
Solar/Wind Helper
0.103
3145683EARLEYS
Solar/Wind Helper
0.257
3146926FARMVIL
Solar/Wind Helper
0.154
3146263WOODLND
Solar/Wind Helper
0.257
238148AE2-230_GEN2
Solar/Wind Helper
0.443
3145963POPLR C
Solar/Wind Helper
0.256
316011AB1-132 GEN
Solar/Wind Helper
2.755
316190AA2-174 GEN
Solar/Wind Helper
0.017
3145823KELFORD
Solar/Wind Helper
0.256
316174AB2-169 GEN
Solar/Wind Helper
0.651
3145783HORNRTN
Solar/Wind Helper
0.255
3145796HORNRTN
Solar/Wind Helper
0.841
3145796HORNRTN
Solar/Wind Helper
0.255
316212AC1-099_GEN
Solar/Wind Helper
1.137
316129AC1-054 GEN
Solar/Wind Helper
1.254
316237AB2-079_GEN
Solar/Wind Helper
0.339
3145746EVERETS
Solar/Wind Helper
0.252
3145746EVERETS
Solar/Wind Helper
0.252
315722AD1-056 GEN
Solar/Wind Helper
1.354
315687AD1-152 GEN
Solar/Wind Helper
1.351
316494AC1-189 GEN
Solar/Wind Helper
1.533
3146233WITAKRS
Solar/Wind Helper
0.995
961671AG1-007 GEN
Solar/Wind Helper
0.179
3146083TARBORO
Solar/Wind Helper
0.25
3147983MERCK5
Solar/Wind Helper
0.1
3145543BTLEBRO
Solar/Wind Helper
0.249
3145543BTLEBRO
Solar/Wind Helper
0.199
316359AB2-059 GEN
Solar/Wind Helper
1.896
316049AB1-081 GEN
Solar/Wind Helper
1.516
316003AC1-222 GEN
Solar/Wind Helper
1.061
23779801AA1-109
Solar/Wind Helper
0.172
316097T157 G90
Solar/Wind Helper
1.092
3147123OTTER R
Solar/Wind Helper
0.137
270016AE1-250 BESS
Solar/Wind Helper
0.841
3147312GRETNA
Solar/Wind Helper
0.182
3146802CHATHAM
Solar/Wind Helper
0.171
237080AD1-060 GEN
Solar/Wind Helper
0.28
270173AC1-122 GEN
Solar/Wind Helper
1.446
20675728RH_W2-091
Solar/Wind Harmer
0.404
966421AG1-511 GEN
Solar/Wind Harmer
10.183
20675928HOL_W4-097
Solar/Wind Harmer
0.154
207484AF2-139 C O1
Solar/Wind Harmer
0.596
20462827N BANGR8
Adder
0.843
20675128HRM_W1-127
Solar/Wind Harmer
0.2
209116AE2-175 GEN
Solar/Wind Harmer
4.772
961261AF2-417 GEN
Solar/Wind Harmer
1.117
209026WIENIPP4
Adder
5.853
209045AE2-271 GEN
Solar/Wind Harmer
17.266
959431AF2-234 GEN
Solar/Wind Harmer
1.994
964051AG1-259 GEN
Solar/Wind Harmer
1.337
964061AG1-260 GEN
Solar/Wind Harmer
1.337
959421AF2-233 GEN
Solar/Wind Harmer
0.997
20486527WR_V4-052
Adder
0.946
208862AG1-362 C
Solar/Wind Harmer
0.63
20390726Y2-042
Adder
2.721
20334726NME_Y1-047
Adder
2.335
203926AA2-133 GEN
Adder
2.108
3141426STAFORD
Solar/Wind Helper
0.066
3138216PACIFIC
Solar/Wind Helper
0.049
316411AF1-147_GEN1
Solar/Wind Helper
0.977
316415AF1-147_GEN2
Solar/Wind Helper
0.977
316164AC1-076 GEN
Solar/Wind Helper
1.347
316223AC1-118
Solar/Wind Helper
0.427
3141813NORNECK
Solar/Wind Helper
0.277
3141783LANCAST
Solar/Wind Helper
0.164
3141783LANCAST
Solar/Wind Helper
0.11
3138133OCRAN
Solar/Wind Helper
0.082
316312AB1-027
Solar/Wind Helper
0.521
3141913WHIT STONE
Solar/Wind Helper
0.274
316059AD1-063 C
Solar/Wind Helper
0.275
957601AF2-054 GEN
Solar/Wind Helper
0.366
3141873WAN 176
Solar/Wind Helper
0.055
315662AE1-191 GEN
Solar/Wind Helper
1.468
315666AE1-190 GEN
Solar/Wind Helper
0.367
3143873LANEXA
Solar/Wind Helper
0.164
316233AE1-074 FULL
Solar/Wind Helper
0.415
957831AF2-077 GEN
Solar/Wind Helper
0.366
316132AB2-190 GEN1
Solar/Wind Helper
1.542
316369SG1_INVT
Solar/Wind Helper
1.296
3143316POE
Solar/Wind Helper
1.061
316349AD2-085 GEN
Solar/Wind Helper
1.218
319010AE1-072 C
Solar/Wind Helper
3.041
316305AF2-043 C
Solar/Wind Helper
0.358
313526AB2-022
Solar/Wind Helper
0.404
3146486SUNBURY
Solar/Wind Helper
0.265
3146486SUNBURY
Solar/Wind Helper
0.265
316321Z2-027
Solar/Wind Helper
0.404
3145176PASQUOTANK
Solar/Wind Helper
0.164
316315AB2-025 C
Solar/Wind Helper
0.402
315611Z1-036_GEN2
Solar/Wind Helper
1.448
3130156CHOWAN
Solar/Wind Helper
0.262
3130156CHOWAN
Solar/Wind Helper
0.262
315816AE2-034 GEN
Solar/Wind Helper
1.192
3130546PLYMOUTH
Solar/Wind Helper
0.26
315732AD1-074 GEN1
Solar/Wind Helper
2.964
315733AD1-074 GEN2
Solar/Wind Helper
2.964
315735AD1-075 GEN1
Solar/Wind Helper
1.482
3146206CASHIE
Solar/Wind Helper
0.259
3145893MURPHYS
Solar/Wind Helper
0.698
3145893MURPHYS
Solar/Wind Helper
0.259
3145513AHOSKIE
Solar/Wind Helper
0.115
961941AG1-037 GEN
Solar/Wind Helper
0.087
3145513AHOSKIE
Solar/Wind Helper
0.258
946281AF1-292 GEN
Solar/Wind Helper
0.258
3146043SEABORD
Solar/Wind Helper
0.257
3145683EARLEYS
Solar/Wind Helper
0.514
3145683EARLEYS
Solar/Wind Helper
0.257
3145683EARLEYS
Solar/Wind Helper
0.257
315607AA1-063A GEN
Solar/Wind Helper
1.467
23546401DTGZ2-030
Solar/Wind Helper
0.08
316087AB2-174 GEN
Solar/Wind Helper
1.796
238152AF2-075_GEN
Solar/Wind Helper
0.631
3137643SOCKMAN
Solar/Wind Helper
1.023
3138266HYDRAULIC
Solar/Wind Helper
0.011
3138266HYDRAULIC
Solar/Wind Helper
0.007
3145796HORNRTN
Solar/Wind Helper
0.816
3145796HORNRTN
Solar/Wind Helper
0.102
3146033SCOT NK
Solar/Wind Helper
1.018
3144303KENBRDG
Solar/Wind Helper
0.203
316239AB2-077_GEN
Solar/Wind Helper
0.339
316238AB2-078_GEN
Solar/Wind Helper
0.339
316005AA1-067
Solar/Wind Helper
0.288
3145746EVERETS
Solar/Wind Helper
1.002
3145746EVERETS
Solar/Wind Helper
0.252
3145746EVERETS
Solar/Wind Helper
0.252
3145746EVERETS
Solar/Wind Helper
0.252
316420AA1-050 GEN
Solar/Wind Helper
1.436
3145573BETHELC
Solar/Wind Helper
0.25
3145573BETHELC
Solar/Wind Helper
0.25
3148133STUARTS
Solar/Wind Helper
0.15
3148013FISHERV
Solar/Wind Helper
0.143
270494AE1-108_GEN
Solar/Wind Helper
3.323
316118AC1-105 GEN
Solar/Wind Helper
0.962
3147173SINAI
Solar/Wind Helper
0.246
3147243WELCO
Solar/Wind Helper
0.154
3148463FAIRFLD
Solar/Wind Helper
0.242
316123AC1-075 GEN
Solar/Wind Helper
1.451
270455AD2-022 GEN
Solar/Wind Helper
1.366
270457AD2-023 GEN
Solar/Wind Helper
0.9
238208AF1-136 C
Solar/Wind Helper
0.176
238109AE1-109 GEN2
Solar/Wind Helper
0.083
238110AE1-109 GEN3
Solar/Wind Helper
0.083
964851AG1-348 GEN
Solar/Wind Harmer
2.087
20634528N27_Y2-018
Solar/Wind Harmer
0.319
20465127PORT CT
Adder
4.7
20674128FR_U2-059
Solar/Wind Harmer
0.217
966111AG1-480 GEN
Solar/Wind Harmer
0.101
966111AG1-480 GEN
Solar/Wind Harmer
3.872
211065PSPA IPP
Solar/Wind Harmer
0.518
211065PSPA IPP
Solar/Wind Harmer
0.518
208972BECR K09
Solar/Wind Harmer
1.146
209029WAYMART-WD
Solar/Wind Harmer
3.127
209009PEIP 2
Adder
8.492
209010PEIP 1
Adder
3.847
209010PEIP 1
Adder
0.564
961541AF2-445A GEN
Solar/Wind Harmer
3.446
961431AF2-434 GEN
Solar/Wind Harmer
1.035
209054AE2-059 GEN
Solar/Wind Harmer
1.709
209059AE2-084 GEN
Solar/Wind Harmer
2.522
946751AF1-339 GEN
Solar/Wind Harmer
1
209130AF1-271A GEN
Solar/Wind Harmer
2.804
20465527S.RDG CT
Adder
2.336
20478527GLRA_Q45
Adder
0.238
209137AF2-361 C
Solar/Wind Harmer
2.127
226929AD2-058 GEN
Solar/Wind Helper
0.158
316447AC1-158 HLD
Solar/Wind Helper
3.47
315651AD1-115 GEN
Solar/Wind Helper
0.947
316468AD1-105 GEN
Solar/Wind Helper
1.392
316077AC2-138 C
Solar/Wind Helper
0.26
966871AG1-558 GEN
Solar/Wind Helper
0.371
316487AF1-042 GEN
Solar/Wind Helper
0.278
966001AG1-469 GEN
Solar/Wind Helper
0.294
316075AC2-137 C
Solar/Wind Helper
0.416
3142946ENON
Solar/Wind Helper
0.027
3143526WINTERP
Solar/Wind Helper
1.414
316240AF1-291 C
Solar/Wind Helper
0.363
316033AB2-134 GEN
Solar/Wind Helper
0.927
315697AD1-025 GEN
Solar/Wind Helper
3.079
316236AE1-162_GEN
Solar/Wind Helper
0.36
316036AC1-147 C
Solar/Wind Helper
0.407
3142956BIRDNECK
Solar/Wind Helper
0.18
316316AC1-027 C
Solar/Wind Helper
0.421
316185AD1-033 GEN
Solar/Wind Helper
1.255
3145506HICKORY
Solar/Wind Helper
1.067
3145506HICKORY
Solar/Wind Helper
0.64
3145506HICKORY
Solar/Wind Helper
0.16
316339AD2-160 GEN
Solar/Wind Helper
1.015
316018AA1-139 ULT2
Solar/Wind Helper
1.145
316017AA1-139 ULT1
Solar/Wind Helper
1.217
3137176SLIGO L2192
Solar/Wind Helper
1.059
3130086AYDLETT
Solar/Wind Helper
1.064
3146386ELIZ CT
Solar/Wind Helper
0.265
316431W1029_GEN1
Solar/Wind Helper
1.069
316433W1029_GEN2
Solar/Wind Helper
1.069
3146516WINFALL
Solar/Wind Helper
0.265
3146516WINFALL
Solar/Wind Helper
0.265
3146516WINFALL
Solar/Wind Helper
0.265
3146626S HERTFORD
Solar/Wind Helper
0.264
3146626S HERTFORD
Solar/Wind Helper
0.264
3144356SAPONY
Solar/Wind Helper
0.473
315742AE1-103 GEN
Solar/Wind Helper
0.424
238175AF1-290_GEN
Solar/Wind Helper
0.138
238169AE2-226 GEN1
Solar/Wind Helper
0.637
238170AE2-226 GEN2
Solar/Wind Helper
0.637
3145893MURPHYS
Solar/Wind Helper
0.371
3145893MURPHYS
Solar/Wind Helper
0.466
3146173TUNIS
Solar/Wind Helper
0.258
3146173TUNIS
Solar/Wind Helper
0.258
3146776BUCKING
Solar/Wind Helper
1.03
3146776BUCKING
Solar/Wind Helper
0.083
316181AB2-040 GEN
Solar/Wind Helper
1.841
3142666NORTHAMPTON
Solar/Wind Helper
0.256
3142666NORTHAMPTON
Solar/Wind Helper
0.256
3142666NORTHAMPTON
Solar/Wind Helper
0.256
3142666NORTHAMPTON
Solar/Wind Helper
0.154
316426AA2-053 GEN
Solar/Wind Helper
1.46
3145593CAROLNA
Solar/Wind Helper
0.256
3145593CAROLNA
Solar/Wind Helper
0.256
3147133PAMPLIN
Solar/Wind Helper
0.255
3147133PAMPLIN
Solar/Wind Helper
0.204
3145796HORNRTN
Solar/Wind Helper
0.765
316034AC1-036 C
Solar/Wind Helper
0.266
315821AE2-092 GEN
Solar/Wind Helper
2.35
3145933PARMELE
Solar/Wind Helper
0.506
3145933PARMELE
Solar/Wind Helper
0.253
316274AC1-208 GEN
Solar/Wind Helper
1.542
3132123MT JACKSON
Solar/Wind Helper
0.783
3146843MT LREL
Solar/Wind Helper
0.249
3146843MT LREL
Solar/Wind Helper
0.249
23777901MDS_W4-102
Solar/Wind Helper
0.154
237034AC2-136 C
Solar/Wind Helper
0.201
235020AA1-095 C
Solar/Wind Helper
0.045
316222AC1-221 GEN
Solar/Wind Helper
1.374
23777801MSM_W1-116
Solar/Wind Helper
0.1
270013AE1-250 PV
Solar/Wind Helper
0.841
316197AC1-042 GEN
Solar/Wind Helper
0.213
HAMLETPJM->LTFIMP_HAMLET
CLTF
5.978
G-007ALTFEXP_G-007A->PJM
CMTX
64.369
CBM NorthLTFEXP_CBM-N->PJM
CBM
88.74
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
4.765
BlueGrassPJM->LTFIMP_BlueG
CLTF
14.85
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
167.297
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.508
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
22.487

Details for PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line l/o PECO_P4_PEACH025_SRT-A/* $ CHESCO $ PECO_P4_PEACH025 $ STBK


Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
Contingency Name:
PECO_P4_PEACH025_SRT-A/* $ CHESCO $ PECO_P4_PEACH025 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:157.55 %
Rating:3620.0 MVA
Rating Type:B
MVA to Mitigate:5703.4
MW Contribution:11.2
Bus #Bus NameTypeMW Contribution
200200DELTA2 CT1
50/50
6.582
200193DELTA CT2
50/50
3.678
200203Y1-065-STG
50/50
12.888
200055ROCKSP 4
50/50
4.641
233971AC1-093 C
Solar/Wind Harmer
1.465
970695AG2-447 GEN
Solar/Wind Harmer
6.69
972133AH1-634 GEN
Solar/Wind Harmer
18.508
233996TM1833_GEN
Solar/Wind Harmer
2.364
233997TMININ_4.2
Solar/Wind Harmer
2.364
232406W1-004 FULL
Solar/Wind Harmer
1.87
232914OH NUG3
Adder
16.486
232916OH NUG5
Adder
16.486
972073AH1-586 GEN
Solar/Wind Harmer
17.494
232921TASLEY2G
Adder
9.635
233940AF2-379 C
Solar/Wind Harmer
0.348
232907VN8
Adder
56.05
233990AG1-397 GEN
Solar/Wind Harmer
2.141
233900O-025 C
Adder
2.198
234015AF2-250 C
Solar/Wind Harmer
0.225
233994AC2-023 GEN
Solar/Wind Harmer
5.016
960671AF2-358 GEN
Solar/Wind Harmer
33.396
232417X3-008 C
Solar/Wind Harmer
3.726
233952AC2-187 GEN
Solar/Wind Harmer
2.095
233918AB1-142 GEN
Solar/Wind Harmer
1.813
233982AB2-133 GEN
Solar/Wind Harmer
8.905
972251AH1-710 GEN
Adder
80.295
228202CUMB CT
Adder
24.591
228711V2-041C
Solar/Wind Harmer
0.893
971553AH1-274 GEN
Solar/Wind Harmer
3.589
230430AE1-229_GEN
Solar/Wind Harmer
12.931
230415AB2-049 C
Solar/Wind Harmer
0.277
228729W2-030 C
Solar/Wind Harmer
0.841
228304LOGAN
Adder
31.581
213497CHSTR7-9
Adder
3.91
219623KINSLEYBEA C
Solar/Wind Harmer
0.604
219291REEVESSOUT C
Solar/Wind Harmer
0.084
219766PARADISE C
Solar/Wind Harmer
0.441
213958STHWK5-6
Adder
3.796
219912AD2-042 GEN
Solar/Wind Harmer
1.109
219236SOUTHERNHQ C
Solar/Wind Harmer
0.093
213560DLW11-12
Adder
3.735
219906AC1-017 C
Solar/Wind Harmer
0.304
219610FLORENCE C
Solar/Wind Harmer
1.874
219348LDSOLAR C
Solar/Wind Harmer
0.81
219221BRL12CT1
Adder
12.072
219223BRL12CT3
Adder
12.072
213815MOSER1-3
Adder
4.772
959561AF2-247 GEN
Solar/Wind Harmer
0.639
20716028EGP_W2-019
Solar/Wind Harmer
0.61
20720828JCB_W4-025
Solar/Wind Harmer
0.596
20715028HAN_X4-015
Solar/Wind Harmer
0.392
20636028O CRK C1
Adder
9.239
971667AH1-334 GEN
Solar/Wind Harmer
3.544
219727YARDVSOLFA C
Solar/Wind Harmer
1.165
20714528FRN_Y2-051
Solar/Wind Harmer
0.374
219276PARKLANDSO C
Solar/Wind Harmer
0.583
219918AC2-009 C
Solar/Wind Harmer
0.077
20716228APLW2-078
Solar/Wind Harmer
1.097
20720528MAN_W1-024
Solar/Wind Harmer
0.315
967451AG2-055 C O1
Solar/Wind Harmer
212.782
219612MATRIX C
Solar/Wind Harmer
0.225
218438BLK ROCK C
Solar/Wind Harmer
0.166
20635828PARLN1&2
Adder
4.033
20635928PARLN3&4
Adder
4.033
20635028RRCT1&2
Adder
14.089
20635128RRCT3&4
Adder
11.681
219908AB1-139 C
Solar/Wind Harmer
0.449
219919AE1-041 FULL
Solar/Wind Harmer
0.048
219249CENTRALDIV C
Solar/Wind Harmer
0.046
20673728F2S_V4-070
Solar/Wind Harmer
0.207
217211CAMDEN ST C
Solar/Wind Harmer
0.028
217186ESSEX_G9
Adder
18.123
217169METRODIV C
Solar/Wind Harmer
0.045
217194REDH C
Solar/Wind Harmer
0.557
20676728BRNX1-095
Solar/Wind Harmer
0.194
207510AF2-138 C
Solar/Wind Harmer
1.885
20674628WNG_W3-110
Solar/Wind Harmer
0.428
971007AG2-625 GEN
Solar/Wind Harmer
2.613
20466127PORT 5CT
Adder
26.444
20465427SHAW CT
Adder
3.813
20633028GILCT9
Adder
27.813
966181AG1-487 GEN
Solar/Wind Harmer
0.247
963071AG1-156 GEN
Solar/Wind Harmer
2.312
970095AG2-074 GEN
Solar/Wind Harmer
5.248
963161AG1-165 GEN
Solar/Wind Harmer
0.832
209025WIENIPP3
Adder
4.389
209027LOR2_Q27
Solar/Wind Harmer
3.43
209022WHFR IPP
Adder
2.463
961331AF2-424 GEN
Solar/Wind Harmer
0.73
961421AF2-433 GEN
Solar/Wind Harmer
0.727
957921AF2-086 GEN
Solar/Wind Harmer
0.707
209142AF1-226 GEN
Solar/Wind Harmer
4.209
209093AE2-110 GEN
Solar/Wind Harmer
1.818
209120AE2-241 GEN
Solar/Wind Harmer
2.405
972245AH1-707 GEN
Adder
3.832
946691AF1-333 GEN
Solar/Wind Harmer
0.669
946741AF1-338 GEN
Solar/Wind Harmer
0.669
223402AF1-300 C
Solar/Wind Helper
0.483
226910AB2-157 C
Solar/Wind Helper
0.018
227287AC2-120 GEN
Solar/Wind Helper
0.425
3141196NOKESVL
Solar/Wind Helper
1.011
316044AC1-158 PL1
Solar/Wind Helper
1.382
316450AC1-158 RIC
Solar/Wind Helper
0.369
966881AG1-559 GEN
Solar/Wind Helper
0.334
316170AC1-121 GEN2
Solar/Wind Helper
0.379
3141906WESTMOR
Solar/Wind Helper
0.099
3132273ORANGE
Solar/Wind Helper
0.049
3147666LOUISA
Solar/Wind Helper
0.565
316404AE1-155 C
Solar/Wind Helper
2.06
316473AC1-191 GEN
Solar/Wind Helper
1.49
316484AD2-074 GEN
Solar/Wind Helper
0.471
316156AD2-030 GEN
Solar/Wind Helper
0.366
316280AD1-041 GEN
Solar/Wind Helper
0.815
3142946ENON
Solar/Wind Helper
0.081
316382AG1-145 C
Solar/Wind Helper
0.324
315839AE2-212 C
Solar/Wind Helper
0.323
3145336SMITFLD
Solar/Wind Helper
0.096
315773AC2-141 GEN
Solar/Wind Helper
5.156
3144536CHRHLND
Solar/Wind Helper
0.036
3144873MCLAUGH
Solar/Wind Helper
0.006
316313AB2-026
Solar/Wind Helper
0.364
316258AE1-075 C
Solar/Wind Helper
0.327
316405AF2-144 C
Solar/Wind Helper
0.273
3146456SLIGO L269
Solar/Wind Helper
0.239
316320Y1-086
Solar/Wind Helper
0.106
316435W1029_GEN3
Solar/Wind Helper
0.96
3146516WINFALL
Solar/Wind Helper
0.238
3146626S HERTFORD
Solar/Wind Helper
0.237
3145273HOLLAND
Solar/Wind Helper
0.178
3146376EDENTON
Solar/Wind Helper
0.236
315614AA2-178 GEN
Solar/Wind Helper
1.435
238147AE2-230_GEN1
Solar/Wind Helper
0.405
238149AF1-291A_GEN
Solar/Wind Helper
0.116
315737AD1-076 GEN
Solar/Wind Helper
2.294
237061AD1-155 GEN
Solar/Wind Helper
0.044
316365GEN2_N
Solar/Wind Helper
0.892
3146206CASHIE
Solar/Wind Helper
0.234
3145893MURPHYS
Solar/Wind Helper
0.084
3145893MURPHYS
Solar/Wind Helper
0.234
3146173TUNIS
Solar/Wind Helper
0.234
3146776BUCKING
Solar/Wind Helper
0.084
3156021HOLLOMANSOL
Solar/Wind Helper
1.779
200192DELTA CT1
50/50
3.678
200194DELTA CT3
50/50
3.678
200204Y1-065-CTG1
50/50
7.432
200054ROCKSP 3
50/50
4.741
232901NORTHST
Adder
15.551
233972AC1-094 C
Solar/Wind Harmer
1.239
232434Z2-077 GEN
Solar/Wind Harmer
0.467
233998TM1NIN_3.36
Solar/Wind Harmer
2.364
232404W1-003 C
Solar/Wind Harmer
1.87
232917OH NUG6
Adder
16.413
232915OH NUG4
Adder
16.377
971195AH1-057 GEN
Solar/Wind Harmer
2.043
232428Y3-058 C
Solar/Wind Harmer
1.557
972177AH1-672 GEN
Solar/Wind Harmer
25.064
232919VN10
Adder
5.235
965821AG1-450 GEN
Solar/Wind Harmer
9.708
232900DEMECSMY
Adder
17.199
232426Y1-080 FULL
Solar/Wind Harmer
0.356
970277AG2-181 GEN
Solar/Wind Harmer
9.35
233964AF2-378 GEN
Solar/Wind Harmer
0.238
233954AC2-188 GEN
Solar/Wind Harmer
2.095
233950AC2-186 GEN
Solar/Wind Harmer
1.048
232910NRG_G1
Adder
15.986
234012AE2-112_GEN
Solar/Wind Harmer
4.23
232422X3-066 FULL
Solar/Wind Harmer
0.46
233930AB2-032 GEN
Solar/Wind Harmer
1.526
233915AB1-141 GEN
Solar/Wind Harmer
1.813
231918WEST 1
Adder
5.881
231917EM10
Adder
4.08
228206SHRMN CT
Adder
24.629
228732V1-021 C
Adder
0.28
945431AF1-208 GEN
Solar/Wind Harmer
12.732
970997AG2-616 GEN
Solar/Wind Harmer
14.104
228351V2-046C
Solar/Wind Harmer
2.957
230511AF1-262
Solar/Wind Harmer
0.268
228728W1-130C
Solar/Wind Harmer
0.97
230434AG1-499 GEN
Solar/Wind Harmer
0.844
213497CHSTR7-9
Adder
3.91
213497CHSTR7-9
Adder
3.91
219258KINSLEYDEP C
Solar/Wind Harmer
0.457
219904AC1-010 C
Solar/Wind Harmer
0.53
218660EHAMPSOLAR C
Solar/Wind Harmer
0.244
219686LUMSOLAR_N C
Solar/Wind Harmer
0.282
219287REEVESEAST C
Solar/Wind Harmer
1.876
213958STHWK5-6
Adder
3.796
219907AC1-030 C
Solar/Wind Harmer
0.192
213560DLW11-12
Adder
3.735
219304NAMERICA C
Solar/Wind Harmer
0.42
219222BRL12CT2
Adder
12.072
213611FALLS1-3
Adder
4.676
20720728JCB_W1-129
Solar/Wind Harmer
0.392
207522AF2-254 C
Solar/Wind Harmer
1.884
207487AE2-000G4
Solar/Wind Harmer
41.175
214194N WALES4
Adder
1.113
207445AB1-138_GEN
Solar/Wind Harmer
0.746
20628028LAKEHURS
Adder
2.421
963711AG1-223 GEN
Solar/Wind Harmer
1.877
20714828MDF_W3-079
Solar/Wind Harmer
0.388
207454AA2-184 E
Solar/Wind Harmer
1.244
219680HOPEWELLV C1
Solar/Wind Harmer
0.095
20715228NPK_W1-113
Solar/Wind Harmer
0.534
20742028HF_AC1-207
Solar/Wind Harmer
0.971
217197RE CRAN C
Solar/Wind Harmer
0.655
20635828PARLN1&2
Adder
8.903
20635028RRCT1&2
Adder
13.873
20635128RRCT3&4
Adder
13.391
218428ETC SOLAR C
Solar/Wind Harmer
0.042
217213AMBOY SO C
Solar/Wind Harmer
0.149
972275AH1-722 GEN
Adder
36.882
218449LINSOLAR C
Solar/Wind Harmer
1.163
207528AF2-192 GEN
Solar/Wind Harmer
0.638
20673628F1S_V4-069
Solar/Wind Harmer
0.207
20675428EAM_W2-061
Solar/Wind Harmer
0.218
20676428JCR_X2-075
Solar/Wind Harmer
0.393
217209CENTRL HS C
Solar/Wind Harmer
0.051
217121ECCF
Adder
0.492
217083KRNY_132
Adder
10.535
217208PARK ELE C
Solar/Wind Harmer
0.029
207439AE1-081 C O1
Solar/Wind Harmer
0.064
20674328GAR_V4-001
Solar/Wind Harmer
0.116
20675828AU_W4-064
Solar/Wind Harmer
0.182
971519AH1-257 GEN
Solar/Wind Harmer
2.557
207518AF1-320_GEN
Solar/Wind Harmer
3.667
207437AD2-070 GEN
Solar/Wind Harmer
0.3
20465127PORT CT
Adder
2.991
20671928W4-073
Solar/Wind Harmer
0.429
966181AG1-487 GEN
Solar/Wind Harmer
3.68
208909MACR G3
Adder
154.513
209010PEIP 1
Adder
0.543
961301AF2-421 GEN
Solar/Wind Harmer
0.832
963151AG1-164 GEN
Solar/Wind Harmer
0.832
209023WIENIPP1
Adder
8.974
209025WIENIPP3
Adder
4.48
212266LOR1
Solar/Wind Harmer
0.098
970237AG2-161 GEN
Solar/Wind Harmer
2.634
961341AF2-425 GEN
Solar/Wind Harmer
0.73
212174INGE
Adder
0.807
212507AE2-042_GEN
Solar/Wind Harmer
2.052
946731AF1-337 GEN
Solar/Wind Harmer
0.669
209071AE2-133 GEN
Solar/Wind Harmer
1.124
970665AG2-430 GEN
Solar/Wind Harmer
6.588
209018SUNBIPCT
Adder
4.945
205941AD2-115 GEN
Solar/Wind Harmer
0.584
972241AH1-705 GEN
Adder
3.39
20467927PC_Q59Y356
Adder
0.451
223401AF1-299 GEN
Solar/Wind Helper
0.483
316006AB2-029 C
Solar/Wind Helper
0.119
316045AC1-158 PL2
Solar/Wind Helper
4.425
316254AC1-120 GEN1
Solar/Wind Helper
1.137
3147666LOUISA
Solar/Wind Helper
0.982
316192AB2-158 GEN
Solar/Wind Helper
1.649
316337AD2-073 GEN
Solar/Wind Helper
0.372
964211AG1-282 GEN
Solar/Wind Helper
0.329
3141726DUNNSVL
Solar/Wind Helper
0.977
3142416OLDCHRC
Solar/Wind Helper
0.632
3142416OLDCHRC
Solar/Wind Helper
0.242
3138133OCRAN
Solar/Wind Helper
0.146
3141766HARMONY
Solar/Wind Helper
0.048
3142433PROV 92
Solar/Wind Helper
0.969
3143526WINTERP
Solar/Wind Helper
1.258
3142543TWELFTH
Solar/Wind Helper
0.023
3143226MDLTHAN
Solar/Wind Helper
0.242
316159AE1-175 C
Solar/Wind Helper
0.366
316458AB2-190 GEN2
Solar/Wind Helper
1.375
3145336SMITFLD
Solar/Wind Helper
0.959
316294AC1-161 GEN
Solar/Wind Helper
4.381
316381AD1-082 GEN
Solar/Wind Helper
1.239
316375AC2-012 GEN
Solar/Wind Helper
0.627
316072AD1-144
Solar/Wind Helper
0.273
316388AE2-253 GEN
Solar/Wind Helper
0.909
3146456SLIGO L269
Solar/Wind Helper
0.239
316246AF1-032 C
Solar/Wind Helper
0.273
316336AC2-165 C
Solar/Wind Helper
1.283
3146516WINFALL
Solar/Wind Helper
0.77
3146516WINFALL
Solar/Wind Helper
0.238
315800Z1-036_GEN1
Solar/Wind Helper
1.303
3130156CHOWAN
Solar/Wind Helper
0.236
3145663CRESWEL
Solar/Wind Helper
0.659
238148AE2-230_GEN2
Solar/Wind Helper
0.406
316023GEN1_S
Solar/Wind Helper
0.892
3146206CASHIE
Solar/Wind Helper
0.234
3145893MURPHYS
Solar/Wind Helper
0.937
3146173TUNIS
Solar/Wind Helper
0.234
316322AB2-045
Solar/Wind Helper
0.261
3146776BUCKING
Solar/Wind Helper
0.094
3146926FARMVIL
Solar/Wind Helper
0.14
3145683EARLEYS
Solar/Wind Helper
0.233
3146263WOODLND
Solar/Wind Helper
0.233
3145963POPLR C
Solar/Wind Helper
0.233
316011AB1-132 GEN
Solar/Wind Helper
2.505
316190AA2-174 GEN
Solar/Wind Helper
0.015
3145823KELFORD
Solar/Wind Helper
0.233
316174AB2-169 GEN
Solar/Wind Helper
0.592
3145783HORNRTN
Solar/Wind Helper
0.232
3145796HORNRTN
Solar/Wind Helper
0.766
3145796HORNRTN
Solar/Wind Helper
0.232
316212AC1-099_GEN
Solar/Wind Helper
1.037
316129AC1-054 GEN
Solar/Wind Helper
1.145
23779801AA1-109
Solar/Wind Helper
0.167
316237AB2-079_GEN
Solar/Wind Helper
0.31
3145746EVERETS
Solar/Wind Helper
0.23
3145746EVERETS
Solar/Wind Helper
0.23
315722AD1-056 GEN
Solar/Wind Helper
1.239
315687AD1-152 GEN
Solar/Wind Helper
1.237
316494AC1-189 GEN
Solar/Wind Helper
1.404
3147983MERCK5
Solar/Wind Helper
0.092
3146233WITAKRS
Solar/Wind Helper
0.913
961671AG1-007 GEN
Solar/Wind Helper
0.165
3146083TARBORO
Solar/Wind Helper
0.229
316359AB2-059 GEN
Solar/Wind Helper
1.742
316049AB1-081 GEN
Solar/Wind Helper
1.393
3145543BTLEBRO
Solar/Wind Helper
0.229
3145543BTLEBRO
Solar/Wind Helper
0.183
316003AC1-222 GEN
Solar/Wind Helper
0.982
316097T157 G90
Solar/Wind Helper
1.03
200201DELTA2 CT2
50/50
6.582
200034PCHBTM 2
50/50
38.302
200035PCHBTM 3
50/50
38.588
200205Y1-065-CTG2
50/50
7.432
233987AB2-037 GEN
Solar/Wind Harmer
21.289
971149AH1-027 GEN
Solar/Wind Harmer
6.324
233939AC1-091 C
Solar/Wind Harmer
1.64
233970AC1-092 C
Solar/Wind Harmer
1.64
970545AG2-347 GEN
Solar/Wind Harmer
122.156
233901CHERRYDALE C
Solar/Wind Harmer
2.102
232408W1-005 C
Solar/Wind Harmer
1.87
232410W1-006 C
Solar/Wind Harmer
1.87
972069AH1-584 GEN
Solar/Wind Harmer
16.717
972071AH1-585 GEN
Solar/Wind Harmer
16.717
232918OH NUG7
Adder
16.377
232905CHERITON_25
Adder
4.58
232926CRISFLD1
Adder
3.664
971747AH1-380 GEN
Solar/Wind Harmer
6.686
231940T-011
Adder
1.392
232899W1-062
Adder
17.931
233946AB2-136 GEN
Solar/Wind Harmer
7.439
234036AF2-325 C
Solar/Wind Harmer
1.709
234041AC1-190 GEN
Solar/Wind Harmer
16.682
233984AB2-036 GEN
Solar/Wind Harmer
23.013
232424Y1-079 C
Solar/Wind Harmer
1.039
234014AF1-036_GEN
Solar/Wind Harmer
4.977
231131BLOOM ENRGY
Adder
8.001
233944AB2-135 GEN
Solar/Wind Harmer
9.597
233933AB2-153 GEN
Solar/Wind Harmer
2.059
232416X2-083
Adder
0.81
228251CARLLS#4
Adder
0.932
230422AE1-104_GEN1
Solar/Wind Harmer
49.445
230425AE1-104_GEN2
Solar/Wind Harmer
49.445
230433AD2-135 GEN
Solar/Wind Harmer
0.148
228307PCLP GT
Adder
17.615
230407AD2-065 C
Solar/Wind Harmer
0.191
228304LOGAN
Adder
35.114
972233AH1-701 GEN
Adder
6.064
213589EDDYSTN4
Adder
113.975
213587EDDYSTN3
Adder
113.943
219921AF1-264
Solar/Wind Harmer
0.203
219615MILLCREEK C
Solar/Wind Harmer
0.325
213535CROYDN11
Adder
13.814
213815MOSER1-3
Adder
4.772
213815MOSER1-3
Adder
4.772
20716428NHV_W2-082
Solar/Wind Harmer
2.336
207500AE2-000G1
Solar/Wind Harmer
41.175
207497AE2-000G2
Solar/Wind Harmer
41.175
207507AE2-000G3
Solar/Wind Harmer
41.175
20636128O CRK C2
Adder
8.424
963401AG1-189 GEN
Solar/Wind Harmer
1.497
963391AG1-188 GEN
Solar/Wind Harmer
2.491
20714928UPF_X1-085
Solar/Wind Harmer
0.526
219114HARTZY_C
Solar/Wind Harmer
1.074
20628028LAKEHURS
Adder
1.224
316463AE2-346 GEN
Solar/Wind Helper
0.214
316140AB2-099
Solar/Wind Helper
0.089
966621AG1-532 GEN
Solar/Wind Helper
0.212
3146926FARMVIL
Solar/Wind Helper
0.14
3146263WOODLND
Solar/Wind Helper
0.233
313506AB2-031 GEN
Solar/Wind Helper
1.058
942461AE2-259 GEN
Solar/Wind Helper
1.57
3142666NORTHAMPTON
Solar/Wind Helper
0.233
3145963POPLR C
Solar/Wind Helper
0.233
316317KELFORD C
Solar/Wind Helper
0.198
3145823KELFORD
Solar/Wind Helper
0.233
3147043LAWRENC
Solar/Wind Helper
0.14
3147133PAMPLIN
Solar/Wind Helper
0.729
316478AD1-087 GEN
Solar/Wind Helper
1.135
316486AD2-202 GEN
Solar/Wind Helper
0.332
3145796HORNRTN
Solar/Wind Helper
0.929
3145796HORNRTN
Solar/Wind Helper
0.232
315785AD2-033 C
Solar/Wind Helper
2.698
316210AC1-098 GEN
Solar/Wind Helper
1.867
3145933PARMELE
Solar/Wind Helper
0.231
316131AB2-060 GEN
Solar/Wind Helper
1.407
3145746EVERETS
Solar/Wind Helper
0.23
3145746EVERETS
Solar/Wind Helper
0.23
315724AD1-057 GEN
Solar/Wind Helper
0.681
316327AA2-057 GEN
Solar/Wind Helper
1.312
3148013FISHERV
Solar/Wind Helper
0.23
3146233WITAKRS
Solar/Wind Helper
0.247
3146233WITAKRS
Solar/Wind Helper
0.156
316499AE2-029_GEN
Solar/Wind Helper
0.773
3146073TAR RVR
Solar/Wind Helper
0.229
3146083TARBORO
Solar/Wind Helper
0.229
3138543CONSLDL
Solar/Wind Helper
0.151
3145543BTLEBRO
Solar/Wind Helper
0.229
3145543BTLEBRO
Solar/Wind Helper
0.229
316248AF1-058 C
Solar/Wind Helper
0.306
237030AB1-096 C
Solar/Wind Helper
0.061
315616AA1-038_C
Solar/Wind Helper
1.021
238221AF1-254 C O1
Solar/Wind Helper
0.221
316095T157 G97
Solar/Wind Helper
1.03
316283AC2-100 C
Solar/Wind Helper
1.196
23583801GRNGAP
Solar/Wind Helper
3.82
200202DELTA2 ST
50/50
11.17
200195DELTA ST
50/50
5.684
200052ROCKSP 1
50/50
4.694
200053ROCKSP 2
50/50
4.594
233973AC2-185 C
Solar/Wind Harmer
6.747
234033AF1-007_GEN
Solar/Wind Harmer
43.652
232904IR4
Adder
150.935
232920IR10
Adder
5.899
232432Z2-076 GEN
Solar/Wind Harmer
0.247
233923SMA
Solar/Wind Harmer
8.669
232912OH NUG1
Adder
16.486
232913OH NUG2
Adder
16.267
233990AG1-397 GEN
Solar/Wind Harmer
0.103
233955AB2-172 GEN
Solar/Wind Harmer
9.316
232813VAUGHN
Adder
1.092
233968AD2-076_GEN
Solar/Wind Harmer
12.194
970597AG2-380 GEN
Solar/Wind Harmer
7.657
231906DC3 NUG
Adder
25.709
231902DC CT7
Adder
20.553
231907DC10
Adder
6.418
232436AB1-176 C
Solar/Wind Harmer
0.421
971983AH1-536 GEN
Solar/Wind Harmer
13.695
233935AB2-179 C
Solar/Wind Harmer
4.463
231919CHRIST1
Adder
7.727
231920CHRIST2
Adder
7.556
970453AG2-297 GEN
Solar/Wind Harmer
4.121
228260V4-054C
Solar/Wind Harmer
1.516
228309CCLP NUG
Adder
38.076
228309CCLP NUG
Adder
36.219
972141AH1-641 GEN
Solar/Wind Harmer
4.231
964001AG1-254 GEN
Solar/Wind Harmer
2.986
971011AG2-627 GEN
Solar/Wind Harmer
11.201
971535AH1-265 GEN
Solar/Wind Harmer
6.211
227927V4-067C
Solar/Wind Harmer
0.288
228754AB1-001 C
Solar/Wind Harmer
0.203
219137THOSOLAR C
Solar/Wind Harmer
1.719
219272CLEANLIGHT C
Solar/Wind Harmer
0.256
213942SCHUYLKILL
Adder
4.97
213942SCHUYLKILL
Adder
3.801
219817TRENTONSOL C
Solar/Wind Harmer
1.38
20641628MLH_W1-032
Solar/Wind Harmer
0.365
20720628TIN_W1-124
Solar/Wind Harmer
1.239
20716928W4-060COL
Solar/Wind Harmer
0.866
924131AB2-057 GEN
Solar/Wind Harmer
1.234
218440SUMMTASSOC C
Solar/Wind Harmer
0.151
218418LINDEN_G5
Adder
20.062
218419LINDEN_G6
Adder
20.062
972260AH1-715 GEN1
Adder
16.065
20673828FLE_V3-070
Solar/Wind Harmer
0.533
219036LINDEN_G7
Adder
19.336
219035LINDEN_G8
Adder
19.06
972261AH1-715 GEN2
Adder
18.509
207442AE1-156 GEN
Solar/Wind Harmer
0.858
20676128MHD_W3-029
Solar/Wind Harmer
0.551
217081WEATEXAS C
Solar/Wind Harmer
0.099
217202FBANKSOLAR C
Solar/Wind Harmer
0.084
217201HACKENSOLA C
Solar/Wind Harmer
0.083
972237AH1-703 GEN
Adder
11.474
217206BARNGR HS C
Solar/Wind Harmer
0.035
217086KRNY_131
Adder
10.557
217083KRNY_132
Adder
10.468
20671828STAW2-080
Solar/Wind Harmer
0.118
217204WCALDSOLAR C
Solar/Wind Harmer
0.082
20674528F3S_W2-016
Solar/Wind Harmer
1.566
20676228FRD_X1-012
Solar/Wind Harmer
0.625
207471AF2-354 C
Solar/Wind Harmer
0.525
20674928WA_W3-044
Solar/Wind Harmer
0.495
964851AG1-348 GEN
Solar/Wind Harmer
1.789
20634528N27_Y2-018
Solar/Wind Harmer
0.274
20465127PORT CT
Adder
3.97
20674128FR_U2-059
Solar/Wind Harmer
0.182
966111AG1-480 GEN
Solar/Wind Harmer
0.085
966111AG1-480 GEN
Solar/Wind Harmer
3.254
211065PSPA IPP
Solar/Wind Harmer
0.415
211065PSPA IPP
Solar/Wind Harmer
0.415
209029WAYMART-WD
Solar/Wind Harmer
2.428
209009PEIP 2
Adder
6.594
209010PEIP 1
Adder
2.988
209010PEIP 1
Adder
0.438
208972BECR K09
Solar/Wind Harmer
0.867
961541AF2-445A GEN
Solar/Wind Harmer
2.464
961431AF2-434 GEN
Solar/Wind Harmer
0.727
209054AE2-059 GEN
Solar/Wind Harmer
1.158
209059AE2-084 GEN
Solar/Wind Harmer
1.71
946751AF1-339 GEN
Solar/Wind Harmer
0.669
209130AF1-271A GEN
Solar/Wind Harmer
1.867
226929AD2-058 GEN
Solar/Wind Helper
0.119
316447AC1-158 HLD
Solar/Wind Helper
3.042
315651AD1-115 GEN
Solar/Wind Helper
0.833
316468AD1-105 GEN
Solar/Wind Helper
1.225
316077AC2-138 C
Solar/Wind Helper
0.23
966001AG1-469 GEN
Solar/Wind Helper
0.262
966871AG1-558 GEN
Solar/Wind Helper
0.329
316487AF1-042 GEN
Solar/Wind Helper
0.246
316075AC2-137 C
Solar/Wind Helper
0.369
3142946ENON
Solar/Wind Helper
0.024
3143526WINTERP
Solar/Wind Helper
1.258
316240AF1-291 C
Solar/Wind Helper
0.324
316033AB2-134 GEN
Solar/Wind Helper
0.827
315697AD1-025 GEN
Solar/Wind Helper
2.748
316236AE1-162_GEN
Solar/Wind Helper
0.322
238175AF1-290_GEN
Solar/Wind Helper
0.126
316036AC1-147 C
Solar/Wind Helper
0.364
3142956BIRDNECK
Solar/Wind Helper
0.161
316316AC1-027 C
Solar/Wind Helper
0.377
316185AD1-033 GEN
Solar/Wind Helper
1.124
3145506HICKORY
Solar/Wind Helper
0.955
3145506HICKORY
Solar/Wind Helper
0.573
3145506HICKORY
Solar/Wind Helper
0.143
238169AE2-226 GEN1
Solar/Wind Helper
0.582
238170AE2-226 GEN2
Solar/Wind Helper
0.582
316339AD2-160 GEN
Solar/Wind Helper
0.909
316018AA1-139 ULT2
Solar/Wind Helper
1.026
316017AA1-139 ULT1
Solar/Wind Helper
1.091
3137176SLIGO L2192
Solar/Wind Helper
0.95
3130086AYDLETT
Solar/Wind Helper
0.954
3146386ELIZ CT
Solar/Wind Helper
0.238
316431W1029_GEN1
Solar/Wind Helper
0.96
316433W1029_GEN2
Solar/Wind Helper
0.96
3146516WINFALL
Solar/Wind Helper
0.238
3146516WINFALL
Solar/Wind Helper
0.238
3146516WINFALL
Solar/Wind Helper
0.238
3146626S HERTFORD
Solar/Wind Helper
0.237
3146626S HERTFORD
Solar/Wind Helper
0.237
3144356SAPONY
Solar/Wind Helper
0.425
315742AE1-103 GEN
Solar/Wind Helper
0.382
3145893MURPHYS
Solar/Wind Helper
0.336
3145893MURPHYS
Solar/Wind Helper
0.422
3146173TUNIS
Solar/Wind Helper
0.234
3146173TUNIS
Solar/Wind Helper
0.234
3146776BUCKING
Solar/Wind Helper
0.935
3146776BUCKING
Solar/Wind Helper
0.076
316181AB2-040 GEN
Solar/Wind Helper
1.672
3142666NORTHAMPTON
Solar/Wind Helper
0.233
3142666NORTHAMPTON
Solar/Wind Helper
0.233
3142666NORTHAMPTON
Solar/Wind Helper
0.233
3142666NORTHAMPTON
Solar/Wind Helper
0.14
316426AA2-053 GEN
Solar/Wind Helper
1.328
3145593CAROLNA
Solar/Wind Helper
0.233
3145593CAROLNA
Solar/Wind Helper
0.233
3147133PAMPLIN
Solar/Wind Helper
0.232
3147133PAMPLIN
Solar/Wind Helper
0.186
3145796HORNRTN
Solar/Wind Helper
0.696
315821AE2-092 GEN
Solar/Wind Helper
2.148
316034AC1-036 C
Solar/Wind Helper
0.242
23777901MDS_W4-102
Solar/Wind Helper
0.145
237034AC2-136 C
Solar/Wind Helper
0.191
3145933PARMELE
Solar/Wind Helper
0.462
3145933PARMELE
Solar/Wind Helper
0.231
316274AC1-208 GEN
Solar/Wind Helper
1.408
3132123MT JACKSON
Solar/Wind Helper
0.721
235020AA1-095 C
Solar/Wind Helper
0.043
23777801MSM_W1-116
Solar/Wind Helper
0.099
3146843MT LREL
Solar/Wind Helper
0.229
3146843MT LREL
Solar/Wind Helper
0.229
237025AB1-124 C
Solar/Wind Helper
0.141
237006AB1-125 GEN
Solar/Wind Helper
0.106
316222AC1-221 GEN
Solar/Wind Helper
1.28
213957STHWK3-4
Adder
3.796
213957STHWK3-4
Adder
3.796
219688LUMSOLAR_S C
Solar/Wind Harmer
0.282
219914AD2-027 C
Solar/Wind Harmer
0.836
213561DLWR9-10
Adder
4.884
213561DLWR9-10
Adder
3.735
219607WPEMNERT C
Solar/Wind Harmer
0.567
219224BRL12CT4
Adder
12.072
214067T20SOLAR
Solar/Wind Harmer
0.334
213611FALLS1-3
Adder
4.676
213611FALLS1-3
Adder
4.676
20717128DIX_Z2-102
Solar/Wind Harmer
1.732
20715728PEM_W1-119
Solar/Wind Harmer
0.7
20715828PEM_W1-120
Solar/Wind Harmer
0.7
970025AG2-016 GEN
Solar/Wind Harmer
3.682
971189AH1-054 GEN
Solar/Wind Harmer
1.531
207459AE1-142 C O1
Solar/Wind Harmer
1.363
219620RIDERU C
Solar/Wind Harmer
0.07
20714328BYD_X4-031
Solar/Wind Harmer
0.353
20714428HOW_X1-037
Solar/Wind Harmer
1.543
971521AH1-258 GEN
Solar/Wind Harmer
3.336
20720428HOL_W1-112
Solar/Wind Harmer
0.425
20635928PARLN3&4
Adder
8.903
218455CINNBAY_CGEN
Adder
2.18
218526CNTRALGAS2 C
Solar/Wind Harmer
0.44
218524CNTRALGAS1 C
Solar/Wind Harmer
0.438
20675528CPH_W2-050
Solar/Wind Harmer
0.549
218404KENILWRTH C
Adder
1.488
217167KRNY_14
Adder
10.535
217086KRNY_131
Adder
10.445
217147KRNY_1212
Adder
10.02
217147KRNY_1212
Adder
9.842
217146KRNY_1234
Adder
9.819
217146KRNY_1234
Adder
9.752
966261AG1-495 GEN
Solar/Wind Harmer
1.935
20676328BVR_Y1-020
Solar/Wind Harmer
0.352
207511W3-106 GEN
Solar/Wind Harmer
0.695
207530AG1-191 GEN
Solar/Wind Harmer
1.449
20674828DL_W4-046
Solar/Wind Harmer
0.665
971009AG2-626 GEN
Solar/Wind Harmer
1.667
207408W3-077 C
Solar/Wind Harmer
0.509
20675728RH_W2-091
Solar/Wind Harmer
0.344
966421AG1-511 GEN
Solar/Wind Harmer
8.656
20675928HOL_W4-097
Solar/Wind Harmer
0.13
207484AF2-139 C O1
Solar/Wind Harmer
0.504
20675128HRM_W1-127
Solar/Wind Harmer
0.169
20462827N BANGR8
Adder
0.708
209116AE2-175 GEN
Solar/Wind Harmer
3.891
961261AF2-417 GEN
Solar/Wind Harmer
0.886
209026WIENIPP4
Adder
4.434
209045AE2-271 GEN
Solar/Wind Harmer
12.024
959431AF2-234 GEN
Solar/Wind Harmer
1.328
964051AG1-259 GEN
Solar/Wind Harmer
0.89
964061AG1-260 GEN
Solar/Wind Harmer
0.89
959421AF2-233 GEN
Solar/Wind Harmer
0.664
3141426STAFORD
Solar/Wind Helper
0.056
3138216PACIFIC
Solar/Wind Helper
0.042
316411AF1-147_GEN1
Solar/Wind Helper
0.854
316415AF1-147_GEN2
Solar/Wind Helper
0.854
316164AC1-076 GEN
Solar/Wind Helper
1.183
316223AC1-118
Solar/Wind Helper
0.375
3141813NORNECK
Solar/Wind Helper
0.245
3141783LANCAST
Solar/Wind Helper
0.146
3141783LANCAST
Solar/Wind Helper
0.097
316312AB1-027
Solar/Wind Helper
0.462
3138133OCRAN
Solar/Wind Helper
0.073
3141913WHIT STONE
Solar/Wind Helper
0.243
316059AD1-063 C
Solar/Wind Helper
0.244
957601AF2-054 GEN
Solar/Wind Helper
0.325
3141873WAN 176
Solar/Wind Helper
0.048
315662AE1-191 GEN
Solar/Wind Helper
1.303
315666AE1-190 GEN
Solar/Wind Helper
0.326
3143873LANEXA
Solar/Wind Helper
0.145
316233AE1-074 FULL
Solar/Wind Helper
0.37
957831AF2-077 GEN
Solar/Wind Helper
0.326
316132AB2-190 GEN1
Solar/Wind Helper
1.375
316369SG1_INVT
Solar/Wind Helper
1.156
3143316POE
Solar/Wind Helper
0.949
316349AD2-085 GEN
Solar/Wind Helper
1.092
316305AF2-043 C
Solar/Wind Helper
0.321
319010AE1-072 C
Solar/Wind Helper
2.726
313526AB2-022
Solar/Wind Helper
0.363
3146486SUNBURY
Solar/Wind Helper
0.238
3146486SUNBURY
Solar/Wind Helper
0.238
316321Z2-027
Solar/Wind Helper
0.363
3145176PASQUOTANK
Solar/Wind Helper
0.148
316315AB2-025 C
Solar/Wind Helper
0.361
315611Z1-036_GEN2
Solar/Wind Helper
1.303
3130156CHOWAN
Solar/Wind Helper
0.236
3130156CHOWAN
Solar/Wind Helper
0.236
315816AE2-034 GEN
Solar/Wind Helper
1.076
23546401DTGZ2-030
Solar/Wind Helper
0.074
238152AF2-075_GEN
Solar/Wind Helper
0.578
3130546PLYMOUTH
Solar/Wind Helper
0.235
315732AD1-074 GEN1
Solar/Wind Helper
2.682
315733AD1-074 GEN2
Solar/Wind Helper
2.682
315735AD1-075 GEN1
Solar/Wind Helper
1.341
3146206CASHIE
Solar/Wind Helper
0.234
3145893MURPHYS
Solar/Wind Helper
0.632
3145893MURPHYS
Solar/Wind Helper
0.234
3145513AHOSKIE
Solar/Wind Helper
0.105
961941AG1-037 GEN
Solar/Wind Helper
0.079
3145513AHOSKIE
Solar/Wind Helper
0.234
946281AF1-292 GEN
Solar/Wind Helper
0.235
3146043SEABORD
Solar/Wind Helper
0.234
3145683EARLEYS
Solar/Wind Helper
0.467
3145683EARLEYS
Solar/Wind Helper
0.233
3145683EARLEYS
Solar/Wind Helper
0.233
315607AA1-063A GEN
Solar/Wind Helper
1.331
316087AB2-174 GEN
Solar/Wind Helper
1.631
3138266HYDRAULIC
Solar/Wind Helper
0.01
3138266HYDRAULIC
Solar/Wind Helper
0.007
3137643SOCKMAN
Solar/Wind Helper
0.93
3145796HORNRTN
Solar/Wind Helper
0.743
3145796HORNRTN
Solar/Wind Helper
0.093
3146033SCOT NK
Solar/Wind Helper
0.928
3144303KENBRDG
Solar/Wind Helper
0.185
316239AB2-077_GEN
Solar/Wind Helper
0.31
316238AB2-078_GEN
Solar/Wind Helper
0.31
316005AA1-067
Solar/Wind Helper
0.263
3145746EVERETS
Solar/Wind Helper
0.917
3145746EVERETS
Solar/Wind Helper
0.23
3145746EVERETS
Solar/Wind Helper
0.23
3145746EVERETS
Solar/Wind Helper
0.23
316420AA1-050 GEN
Solar/Wind Helper
1.316
3148133STUARTS
Solar/Wind Helper
0.138
3148013FISHERV
Solar/Wind Helper
0.132
3145573BETHELC
Solar/Wind Helper
0.229
3145573BETHELC
Solar/Wind Helper
0.229
270494AE1-108_GEN
Solar/Wind Helper
3.061
316118AC1-105 GEN
Solar/Wind Helper
0.886
3147173SINAI
Solar/Wind Helper
0.227
3147243WELCO
Solar/Wind Helper
0.142
3148463FAIRFLD
Solar/Wind Helper
0.225
316123AC1-075 GEN
Solar/Wind Helper
1.356
HAMLETPJM->LTFIMP_HAMLET
CLTF
5.659
G-007ALTFEXP_G-007A->PJM
CMTX
61.271
CBM NorthLTFEXP_CBM-N->PJM
CBM
75.807
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
4.878
BlueGrassPJM->LTFIMP_BlueG
CLTF
15.195
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
154.599
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.363
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
22.852

Details for PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line l/o AP_P1-2_PE-500-3835T_SRT-A


Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-500-3835T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:154.15 %
Rating:3620.0 MVA
Rating Type:B
MVA to Mitigate:5580.17
MW Contribution:7.81
Bus #Bus NameTypeMW Contribution
200202DELTA2 ST
50/50
9.525
200195DELTA ST
50/50
4.847
200052ROCKSP 1
50/50
4.055
200053ROCKSP 2
50/50
3.968
233973AC2-185 C
Solar/Wind Harmer
0.003
234033AF1-007_GEN
Solar/Wind Harmer
-0.002
232904IR4
Adder
140.44
232920IR10
Adder
5.489
232432Z2-076 GEN
Solar/Wind Harmer
0.023
232912OH NUG1
Adder
15.335
232913OH NUG2
Adder
15.13
233923SMA
Solar/Wind Harmer
0.009
233990AG1-397 GEN
Solar/Wind Harmer
-0.276
233955AB2-172 GEN
Solar/Wind Harmer
0.005
232813VAUGHN
Adder
1.017
231906DC3 NUG
Adder
23.938
231902DC CT7
Adder
19.137
231907DC10
Adder
5.976
233968AD2-076_GEN
Solar/Wind Harmer
3.977
970597AG2-380 GEN
Solar/Wind Harmer
7.123
232436AB1-176 C
Solar/Wind Harmer
0
971983AH1-536 GEN
Solar/Wind Harmer
3.013
233935AB2-179 C
Solar/Wind Harmer
2.292
231919CHRIST1
Adder
7.288
231920CHRIST2
Adder
7.126
970453AG2-297 GEN
Solar/Wind Harmer
3.772
228260V4-054C
Solar/Wind Harmer
0
228309CCLP NUG
Adder
37.932
228309CCLP NUG
Adder
36.082
972141AH1-641 GEN
Solar/Wind Harmer
4.906
964001AG1-254 GEN
Solar/Wind Harmer
0.568
971535AH1-265 GEN
Solar/Wind Harmer
4.02
971011AG2-627 GEN
Solar/Wind Harmer
7.811
227927V4-067C
Solar/Wind Harmer
0
228754AB1-001 C
Solar/Wind Harmer
0
219272CLEANLIGHT C
Solar/Wind Harmer
0
219688LUMSOLAR_S C
Solar/Wind Harmer
0
219914AD2-027 C
Solar/Wind Harmer
0.001
213942SCHUYLKILL
Adder
5.011
213942SCHUYLKILL
Adder
3.832
213957STHWK3-4
Adder
3.832
213957STHWK3-4
Adder
3.832
213561DLWR9-10
Adder
4.987
213561DLWR9-10
Adder
3.814
219607WPEMNERT C
Solar/Wind Harmer
0.001
219224BRL12CT4
Adder
12.506
214067T20SOLAR
Solar/Wind Harmer
0
213611FALLS1-3
Adder
4.903
213611FALLS1-3
Adder
4.903
20717128DIX_Z2-102
Solar/Wind Harmer
0.001
20715728PEM_W1-119
Solar/Wind Harmer
0.001
20715828PEM_W1-120
Solar/Wind Harmer
0.001
970025AG2-016 GEN
Solar/Wind Harmer
2.527
971189AH1-054 GEN
Solar/Wind Harmer
1.052
207459AE1-142 C O1
Solar/Wind Harmer
0.002
20714328BYD_X4-031
Solar/Wind Harmer
0.207
20714428HOW_X1-037
Solar/Wind Harmer
0.001
971521AH1-258 GEN
Solar/Wind Harmer
2.368
20720428HOL_W1-112
Solar/Wind Harmer
0
20635928PARLN3&4
Adder
9.94
218455CINNBAY_CGEN
Adder
2.438
218526CNTRALGAS2 C
Solar/Wind Harmer
1.024
218524CNTRALGAS1 C
Solar/Wind Harmer
1.022
218404KENILWRTH C
Adder
1.722
217167KRNY_14
Adder
12.237
217086KRNY_131
Adder
12.133
217147KRNY_1212
Adder
11.639
217147KRNY_1212
Adder
11.431
217146KRNY_1234
Adder
11.405
217146KRNY_1234
Adder
11.327
20676328BVR_Y1-020
Solar/Wind Harmer
0
207511W3-106 GEN
Solar/Wind Harmer
0.421
207530AG1-191 GEN
Solar/Wind Harmer
0.001
20674828DL_W4-046
Solar/Wind Harmer
0.001
971009AG2-626 GEN
Solar/Wind Harmer
1.347
207408W3-077 C
Solar/Wind Harmer
0.001
20675728RH_W2-091
Solar/Wind Harmer
0.001
966421AG1-511 GEN
Solar/Wind Harmer
7.613
20675928HOL_W4-097
Solar/Wind Harmer
0
207484AF2-139 C O1
Solar/Wind Harmer
0.001
20462827N BANGR8
Adder
0.904
20675128HRM_W1-127
Solar/Wind Harmer
0
209116AE2-175 GEN
Solar/Wind Harmer
0.009
209026WIENIPP4
Adder
6.291
209045AE2-271 GEN
Solar/Wind Harmer
12.981
20486527WR_V4-052
Adder
1.043
208862AG1-362 C
Solar/Wind Harmer
0.524
20390726Y2-042
Adder
2.938
20334726NME_Y1-047
Adder
2.528
203926AA2-133 GEN
Adder
2.286
3138216PACIFIC
Solar/Wind Helper
0.054
316411AF1-147_GEN1
Solar/Wind Helper
1.084
316415AF1-147_GEN2
Solar/Wind Helper
1.084
3141426STAFORD
Solar/Wind Helper
0.07
316164AC1-076 GEN
Solar/Wind Helper
1.468
316223AC1-118
Solar/Wind Helper
0.46
3141813NORNECK
Solar/Wind Helper
0.299
3141783LANCAST
Solar/Wind Helper
0.178
3141783LANCAST
Solar/Wind Helper
0.119
316312AB1-027
Solar/Wind Helper
0.564
3138133OCRAN
Solar/Wind Helper
0.089
3141913WHIT STONE
Solar/Wind Helper
0.296
316059AD1-063 C
Solar/Wind Helper
0.298
957601AF2-054 GEN
Solar/Wind Helper
0.396
3141873WAN 176
Solar/Wind Helper
0.059
315662AE1-191 GEN
Solar/Wind Helper
1.589
315666AE1-190 GEN
Solar/Wind Helper
0.397
3143873LANEXA
Solar/Wind Helper
0.177
316233AE1-074 FULL
Solar/Wind Helper
0.45
957831AF2-077 GEN
Solar/Wind Helper
0.396
316132AB2-190 GEN1
Solar/Wind Helper
1.671
316369SG1_INVT
Solar/Wind Helper
1.404
3143316POE
Solar/Wind Helper
1.15
316349AD2-085 GEN
Solar/Wind Helper
1.321
319010AE1-072 C
Solar/Wind Helper
3.298
316305AF2-043 C
Solar/Wind Helper
0.388
313526AB2-022
Solar/Wind Helper
0.439
3146486SUNBURY
Solar/Wind Helper
0.288
3146486SUNBURY
Solar/Wind Helper
0.288
316321Z2-027
Solar/Wind Helper
0.438
3145176PASQUOTANK
Solar/Wind Helper
0.178
238152AF2-075_GEN
Solar/Wind Helper
0.707
23546401DTGZ2-030
Solar/Wind Helper
0.09
316315AB2-025 C
Solar/Wind Helper
0.436
315611Z1-036_GEN2
Solar/Wind Helper
1.571
3130156CHOWAN
Solar/Wind Helper
0.285
3130156CHOWAN
Solar/Wind Helper
0.285
315816AE2-034 GEN
Solar/Wind Helper
1.294
3130546PLYMOUTH
Solar/Wind Helper
0.282
315732AD1-074 GEN1
Solar/Wind Helper
3.218
315733AD1-074 GEN2
Solar/Wind Helper
3.218
315735AD1-075 GEN1
Solar/Wind Helper
1.609
3146206CASHIE
Solar/Wind Helper
0.281
3145893MURPHYS
Solar/Wind Helper
0.758
200201DELTA2 CT2
50/50
5.613
200034PCHBTM 2
50/50
32.671
200035PCHBTM 3
50/50
32.699
200205Y1-065-CTG2
50/50
6.42
971149AH1-027 GEN
Solar/Wind Harmer
5.438
233939AC1-091 C
Solar/Wind Harmer
0.003
233970AC1-092 C
Solar/Wind Harmer
0.003
970545AG2-347 GEN
Solar/Wind Harmer
43.85
232899W1-062
Adder
16.706
233987AB2-037 GEN
Solar/Wind Harmer
0.019
972069AH1-584 GEN
Solar/Wind Harmer
10.849
972071AH1-585 GEN
Solar/Wind Harmer
10.849
233901CHERRYDALE C
Solar/Wind Harmer
0.002
232408W1-005 C
Solar/Wind Harmer
1.124
232410W1-006 C
Solar/Wind Harmer
1.124
232918OH NUG7
Adder
15.233
971747AH1-380 GEN
Solar/Wind Harmer
4.339
232905CHERITON_25
Adder
4.26
232926CRISFLD1
Adder
3.408
231940T-011
Adder
1.295
233946AB2-136 GEN
Solar/Wind Harmer
0.007
234036AF2-325 C
Solar/Wind Harmer
0.001
234041AC1-190 GEN
Solar/Wind Harmer
12.626
233984AB2-036 GEN
Solar/Wind Harmer
12.488
232424Y1-079 C
Solar/Wind Harmer
0.001
231131BLOOM ENRGY
Adder
7.452
234014AF1-036_GEN
Solar/Wind Harmer
3.977
233944AB2-135 GEN
Solar/Wind Harmer
0.008
233933AB2-153 GEN
Solar/Wind Harmer
0.002
232416X2-083
Adder
0.758
228251CARLLS#4
Adder
0.928
230422AE1-104_GEN1
Solar/Wind Harmer
19.852
230425AE1-104_GEN2
Solar/Wind Harmer
19.852
200200DELTA2 CT1
50/50
5.613
200193DELTA CT2
50/50
3.136
200203Y1-065-STG
50/50
11.132
200055ROCKSP 4
50/50
4.009
233971AC1-093 C
Solar/Wind Harmer
0.075
970695AG2-447 GEN
Solar/Wind Harmer
4.35
972133AH1-634 GEN
Solar/Wind Harmer
6.404
972073AH1-586 GEN
Solar/Wind Harmer
16.273
232406W1-004 FULL
Solar/Wind Harmer
1.124
232914OH NUG3
Adder
15.335
232916OH NUG5
Adder
15.335
232921TASLEY2G
Adder
8.962
233996TM1833_GEN
Solar/Wind Harmer
0.003
233997TMININ_4.2
Solar/Wind Harmer
0.003
233990AG1-397 GEN
Solar/Wind Harmer
2.364
233940AF2-379 C
Solar/Wind Harmer
0
233900O-025 C
Adder
2.044
234015AF2-250 C
Solar/Wind Harmer
0
233994AC2-023 GEN
Solar/Wind Harmer
0.007
232907VN8
Adder
52.113
960671AF2-358 GEN
Solar/Wind Harmer
21.666
233952AC2-187 GEN
Solar/Wind Harmer
0.002
232417X3-008 C
Solar/Wind Harmer
0.002
972251AH1-710 GEN
Adder
76.344
233918AB1-142 GEN
Solar/Wind Harmer
0.437
233982AB2-133 GEN
Solar/Wind Harmer
0.007
228202CUMB CT
Adder
24.423
228711V2-041C
Solar/Wind Harmer
0
971553AH1-274 GEN
Solar/Wind Harmer
2.303
230430AE1-229_GEN
Solar/Wind Harmer
0.025
230415AB2-049 C
Solar/Wind Harmer
0
228729W2-030 C
Solar/Wind Harmer
0.001
228304LOGAN
Adder
31.636
219623KINSLEYBEA C
Solar/Wind Harmer
0
219766PARADISE C
Solar/Wind Harmer
0
213497CHSTR7-9
Adder
3.88
219912AD2-042 GEN
Solar/Wind Harmer
0.001
213958STHWK5-6
Adder
3.832
219906AC1-017 C
Solar/Wind Harmer
0
213560DLW11-12
Adder
3.814
219610FLORENCE C
Solar/Wind Harmer
0.001
219348LDSOLAR C
Solar/Wind Harmer
0.001
219221BRL12CT1
Adder
12.506
219223BRL12CT3
Adder
12.506
213815MOSER1-3
Adder
4.947
20716028EGP_W2-019
Solar/Wind Harmer
0
20720828JCB_W4-025
Solar/Wind Harmer
0.001
20715028HAN_X4-015
Solar/Wind Harmer
0
20636028O CRK C1
Adder
9.778
971667AH1-334 GEN
Solar/Wind Harmer
2.444
219727YARDVSOLFA C
Solar/Wind Harmer
0
20714528FRN_Y2-051
Solar/Wind Harmer
0
219276PARKLANDSO C
Solar/Wind Harmer
0.001
20716228APLW2-078
Solar/Wind Harmer
0.001
20720528MAN_W1-024
Solar/Wind Harmer
0
967451AG2-055 C O1
Solar/Wind Harmer
335.566
219612MATRIX C
Solar/Wind Harmer
0
218438BLK ROCK C
Solar/Wind Harmer
0
20635828PARLN1&2
Adder
4.502
20635928PARLN3&4
Adder
4.502
20635028RRCT1&2
Adder
15.796
20635128RRCT3&4
Adder
13.096
219908AB1-139 C
Solar/Wind Harmer
0.001
20673728F2S_V4-070
Solar/Wind Harmer
0
217186ESSEX_G9
Adder
21.048
217194REDH C
Solar/Wind Harmer
0
20676728BRNX1-095
Solar/Wind Harmer
0
207510AF2-138 C
Solar/Wind Harmer
0.002
20674628WNG_W3-110
Solar/Wind Harmer
0.001
971007AG2-625 GEN
Solar/Wind Harmer
2.112
20466127PORT 5CT
Adder
33.54
20633028GILCT9
Adder
35.545
20465427SHAW CT
Adder
4.864
209025WIENIPP3
Adder
6.227
963071AG1-156 GEN
Solar/Wind Harmer
0.518
970095AG2-074 GEN
Solar/Wind Harmer
5.901
209027LOR2_Q27
Solar/Wind Harmer
0.001
209022WHFR IPP
Adder
3.707
209142AF1-226 GEN
Solar/Wind Harmer
3.151
209093AE2-110 GEN
Solar/Wind Harmer
1.801
209120AE2-241 GEN
Solar/Wind Harmer
1.801
972245AH1-707 GEN
Adder
5.98
209067AE2-060 GEN
Solar/Wind Harmer
0.001
970767AG2-484 GEN
Solar/Wind Harmer
0.566
972221AH1-695 GEN
Adder
101.353
226910AB2-157 C
Solar/Wind Helper
0.021
227287AC2-120 GEN
Solar/Wind Helper
0.512
223402AF1-300 C
Solar/Wind Helper
0.531
3141196NOKESVL
Solar/Wind Helper
1.272
316044AC1-158 PL1
Solar/Wind Helper
1.717
316450AC1-158 RIC
Solar/Wind Helper
0.458
316170AC1-121 GEN2
Solar/Wind Helper
0.47
966881AG1-559 GEN
Solar/Wind Helper
0.411
3132273ORANGE
Solar/Wind Helper
0.061
3147666LOUISA
Solar/Wind Helper
0.696
3141906WESTMOR
Solar/Wind Helper
0.121
316404AE1-155 C
Solar/Wind Helper
2.516
316473AC1-191 GEN
Solar/Wind Helper
1.82
316484AD2-074 GEN
Solar/Wind Helper
0.575
316156AD2-030 GEN
Solar/Wind Helper
0.446
316280AD1-041 GEN
Solar/Wind Helper
0.993
3142946ENON
Solar/Wind Helper
0.098
316382AG1-145 C
Solar/Wind Helper
0.394
315839AE2-212 C
Solar/Wind Helper
0.392
3145336SMITFLD
Solar/Wind Helper
0.116
315773AC2-141 GEN
Solar/Wind Helper
6.25
3144536CHRHLND
Solar/Wind Helper
0.044
3144873MCLAUGH
Solar/Wind Helper
0.007
316313AB2-026
Solar/Wind Helper
0.441
316258AE1-075 C
Solar/Wind Helper
0.397
316405AF2-144 C
Solar/Wind Helper
0.33
3146456SLIGO L269
Solar/Wind Helper
0.289
316320Y1-086
Solar/Wind Helper
0.129
238147AE2-230_GEN1
Solar/Wind Helper
0.495
238149AF1-291A_GEN
Solar/Wind Helper
0.141
316435W1029_GEN3
Solar/Wind Helper
1.16
3146516WINFALL
Solar/Wind Helper
0.287
3146626S HERTFORD
Solar/Wind Helper
0.286
3145273HOLLAND
Solar/Wind Helper
0.215
237061AD1-155 GEN
Solar/Wind Helper
0.054
3146376EDENTON
Solar/Wind Helper
0.285
315614AA2-178 GEN
Solar/Wind Helper
1.725
315737AD1-076 GEN
Solar/Wind Helper
2.753
316365GEN2_N
Solar/Wind Helper
1.07
3146206CASHIE
Solar/Wind Helper
0.281
3145893MURPHYS
Solar/Wind Helper
0.101
3145893MURPHYS
Solar/Wind Helper
0.281
3146776BUCKING
Solar/Wind Helper
0.101
3146173TUNIS
Solar/Wind Helper
0.28
3146926FARMVIL
Solar/Wind Helper
0.168
3156021HOLLOMANSOL
Solar/Wind Helper
2.13
316463AE2-346 GEN
Solar/Wind Helper
0.256
316140AB2-099
Solar/Wind Helper
0.107
230407AD2-065 C
Solar/Wind Harmer
0
228307PCLP GT
Adder
17.621
228304LOGAN
Adder
35.175
972233AH1-701 GEN
Adder
6.085
219921AF1-264
Solar/Wind Harmer
0
213589EDDYSTN4
Adder
113.194
213587EDDYSTN3
Adder
113.181
219615MILLCREEK C
Solar/Wind Harmer
0
213535CROYDN11
Adder
14.318
213815MOSER1-3
Adder
4.947
213815MOSER1-3
Adder
4.947
20716428NHV_W2-082
Solar/Wind Harmer
0.001
207500AE2-000G1
Solar/Wind Harmer
17.494
207497AE2-000G2
Solar/Wind Harmer
17.494
207507AE2-000G3
Solar/Wind Harmer
17.494
20636128O CRK C2
Adder
8.916
20714928UPF_X1-085
Solar/Wind Harmer
0
20628028LAKEHURS
Adder
1.308
219114HARTZY_C
Solar/Wind Harmer
0
20720628TIN_W1-124
Solar/Wind Harmer
0.001
20716928W4-060COL
Solar/Wind Harmer
0.001
218440SUMMTASSOC C
Solar/Wind Harmer
0
218418LINDEN_G5
Adder
22.839
218419LINDEN_G6
Adder
22.839
972260AH1-715 GEN1
Adder
18.289
20673828FLE_V3-070
Solar/Wind Harmer
0.001
219036LINDEN_G7
Adder
22.165
219035LINDEN_G8
Adder
21.848
972261AH1-715 GEN2
Adder
21.217
207442AE1-156 GEN
Solar/Wind Harmer
0.08
20676128MHD_W3-029
Solar/Wind Harmer
0.001
972237AH1-703 GEN
Adder
13.322
217086KRNY_131
Adder
12.263
217083KRNY_132
Adder
12.159
20671828STAW2-080
Solar/Wind Harmer
0
20674528F3S_W2-016
Solar/Wind Harmer
0.001
20676228FRD_X1-012
Solar/Wind Harmer
0.001
20674928WA_W3-044
Solar/Wind Harmer
0.001
20465127PORT CT
Adder
5.039
20674128FR_U2-059
Solar/Wind Harmer
0
966111AG1-480 GEN
Solar/Wind Harmer
4.26
211065PSPA IPP
Solar/Wind Harmer
0.001
211065PSPA IPP
Solar/Wind Harmer
0.001
208972BECR K09
Solar/Wind Harmer
0.001
209029WAYMART-WD
Solar/Wind Harmer
0.001
209009PEIP 2
Adder
9.121
209010PEIP 1
Adder
4.133
209010PEIP 1
Adder
0.605
961541AF2-445A GEN
Solar/Wind Harmer
2.57
209054AE2-059 GEN
Solar/Wind Harmer
0.001
209059AE2-084 GEN
Solar/Wind Harmer
1.756
970761AG2-481 GEN
Solar/Wind Harmer
0.857
209130AF1-271A GEN
Solar/Wind Harmer
2.109
20465527S.RDG CT
Adder
2.577
20478527GLRA_Q45
Adder
0.267
209137AF2-361 C
Solar/Wind Harmer
0.004
226929AD2-058 GEN
Solar/Wind Helper
0.145
316447AC1-158 HLD
Solar/Wind Helper
3.78
315651AD1-115 GEN
Solar/Wind Helper
1.035
316468AD1-105 GEN
Solar/Wind Helper
1.502
966001AG1-469 GEN
Solar/Wind Helper
0.321
316077AC2-138 C
Solar/Wind Helper
0.281
966871AG1-558 GEN
Solar/Wind Helper
0.402
316487AF1-042 GEN
Solar/Wind Helper
0.301
238175AF1-290_GEN
Solar/Wind Helper
0.156
316075AC2-137 C
Solar/Wind Helper
0.45
3143526WINTERP
Solar/Wind Helper
1.533
238169AE2-226 GEN1
Solar/Wind Helper
0.718
238170AE2-226 GEN2
Solar/Wind Helper
0.718
3142946ENON
Solar/Wind Helper
0.03
316240AF1-291 C
Solar/Wind Helper
0.393
316033AB2-134 GEN
Solar/Wind Helper
1.004
315697AD1-025 GEN
Solar/Wind Helper
3.337
316236AE1-162_GEN
Solar/Wind Helper
0.391
316036AC1-147 C
Solar/Wind Helper
0.441
3142956BIRDNECK
Solar/Wind Helper
0.195
316316AC1-027 C
Solar/Wind Helper
0.457
316185AD1-033 GEN
Solar/Wind Helper
1.361
3145506HICKORY
Solar/Wind Helper
1.157
3145506HICKORY
Solar/Wind Helper
0.694
3145506HICKORY
Solar/Wind Helper
0.173
316339AD2-160 GEN
Solar/Wind Helper
1.1
316018AA1-139 ULT2
Solar/Wind Helper
1.242
316017AA1-139 ULT1
Solar/Wind Helper
1.32
3137176SLIGO L2192
Solar/Wind Helper
1.149
3130086AYDLETT
Solar/Wind Helper
1.154
3146386ELIZ CT
Solar/Wind Helper
0.288
316431W1029_GEN1
Solar/Wind Helper
1.16
316433W1029_GEN2
Solar/Wind Helper
1.16
3146516WINFALL
Solar/Wind Helper
0.287
3146516WINFALL
Solar/Wind Helper
0.287
3146516WINFALL
Solar/Wind Helper
0.287
3146626S HERTFORD
Solar/Wind Helper
0.286
3146626S HERTFORD
Solar/Wind Helper
0.286
3144356SAPONY
Solar/Wind Helper
0.513
315742AE1-103 GEN
Solar/Wind Helper
0.46
3145893MURPHYS
Solar/Wind Helper
0.403
3145893MURPHYS
Solar/Wind Helper
0.506
3146776BUCKING
Solar/Wind Helper
1.123
3146776BUCKING
Solar/Wind Helper
0.091
3146173TUNIS
Solar/Wind Helper
0.28
200192DELTA CT1
50/50
3.136
200194DELTA CT3
50/50
3.136
200204Y1-065-CTG1
50/50
6.42
200054ROCKSP 3
50/50
4.095
232901NORTHST
Adder
14.486
233972AC1-094 C
Solar/Wind Harmer
0.547
232900DEMECSMY
Adder
16.024
232434Z2-077 GEN
Solar/Wind Harmer
0.073
972177AH1-672 GEN
Solar/Wind Harmer
17.686
232404W1-003 C
Solar/Wind Harmer
1.124
232917OH NUG6
Adder
15.267
232915OH NUG4
Adder
15.233
233998TM1NIN_3.36
Solar/Wind Harmer
0.003
971195AH1-057 GEN
Solar/Wind Harmer
1.085
232428Y3-058 C
Solar/Wind Harmer
0.003
232919VN10
Adder
4.868
965821AG1-450 GEN
Solar/Wind Harmer
9.028
232426Y1-080 FULL
Solar/Wind Harmer
0
970277AG2-181 GEN
Solar/Wind Harmer
1.011
233964AF2-378 GEN
Solar/Wind Harmer
0
233954AC2-188 GEN
Solar/Wind Harmer
0.002
233950AC2-186 GEN
Solar/Wind Harmer
0.001
232910NRG_G1
Adder
14.885
234012AE2-112_GEN
Solar/Wind Harmer
3.977
232422X3-066 FULL
Solar/Wind Harmer
0.143
233930AB2-032 GEN
Solar/Wind Harmer
1.633
233915AB1-141 GEN
Solar/Wind Harmer
0.437
231918WEST 1
Adder
5.541
231917EM10
Adder
3.861
228206SHRMN CT
Adder
24.48
228732V1-021 C
Adder
0.279
945431AF1-208 GEN
Solar/Wind Harmer
8.85
970997AG2-616 GEN
Solar/Wind Harmer
10.581
228351V2-046C
Solar/Wind Harmer
0.001
230511AF1-262
Solar/Wind Harmer
0
228728W1-130C
Solar/Wind Harmer
0.001
230434AG1-499 GEN
Solar/Wind Harmer
0.002
219258KINSLEYDEP C
Solar/Wind Harmer
0.001
218660EHAMPSOLAR C
Solar/Wind Harmer
0
219686LUMSOLAR_N C
Solar/Wind Harmer
0
219287REEVESEAST C
Solar/Wind Harmer
0
219904AC1-010 C
Solar/Wind Harmer
0.001
213497CHSTR7-9
Adder
3.88
213497CHSTR7-9
Adder
3.88
219907AC1-030 C
Solar/Wind Harmer
0
213958STHWK5-6
Adder
3.832
213560DLW11-12
Adder
3.814
219304NAMERICA C
Solar/Wind Harmer
0.128
219222BRL12CT2
Adder
12.506
213611FALLS1-3
Adder
4.903
20720728JCB_W1-129
Solar/Wind Harmer
0
207522AF2-254 C
Solar/Wind Harmer
1.285
207487AE2-000G4
Solar/Wind Harmer
17.494
214194N WALES4
Adder
1.175
207445AB1-138_GEN
Solar/Wind Harmer
0.001
20628028LAKEHURS
Adder
2.588
20714828MDF_W3-079
Solar/Wind Harmer
0.135
207454AA2-184 E
Solar/Wind Harmer
0.002
20715228NPK_W1-113
Solar/Wind Harmer
0.001
20742028HF_AC1-207
Solar/Wind Harmer
0.001
217197RE CRAN C
Solar/Wind Harmer
0
20635828PARLN1&2
Adder
9.94
20635028RRCT1&2
Adder
15.553
20635128RRCT3&4
Adder
15.013
217213AMBOY SO C
Solar/Wind Harmer
0
972275AH1-722 GEN
Adder
41.987
218449LINSOLAR C
Solar/Wind Harmer
0
207528AF2-192 GEN
Solar/Wind Harmer
0.001
20673628F1S_V4-069
Solar/Wind Harmer
0
20675428EAM_W2-061
Solar/Wind Harmer
0
20676428JCR_X2-075
Solar/Wind Harmer
0.001
217121ECCF
Adder
0.572
217083KRNY_132
Adder
12.237
20674328GAR_V4-001
Solar/Wind Harmer
0
20675828AU_W4-064
Solar/Wind Harmer
0
971519AH1-257 GEN
Solar/Wind Harmer
2.07
20465127PORT CT
Adder
3.797
207437AD2-070 GEN
Solar/Wind Harmer
0.083
20671928W4-073
Solar/Wind Harmer
0.001
966181AG1-487 GEN
Solar/Wind Harmer
4.796
208909MACR G3
Adder
199.958
209023WIENIPP1
Adder
12.731
209025WIENIPP3
Adder
6.355
209010PEIP 1
Adder
0.751
212266LOR1
Solar/Wind Harmer
0.55
212174INGE
Adder
1.236
212507AE2-042_GEN
Solar/Wind Harmer
0.669
209071AE2-133 GEN
Solar/Wind Harmer
0.001
970665AG2-430 GEN
Solar/Wind Harmer
7.793
209018SUNBIPCT
Adder
8.007
970757AG2-479 GEN
Solar/Wind Harmer
0.848
205941AD2-115 GEN
Solar/Wind Harmer
0.122
972241AH1-705 GEN
Adder
5.998
20467927PC_Q59Y356
Adder
0.825
20465527S.RDG CT
Adder
2.664
970679AG2-439 GEN
Solar/Wind Harmer
0.772
209008PAXT IPP
Adder
1.514
200917MEHOOPANY_G
Solar/Wind Harmer
0.378
972271AH1-720 GEN
Adder
6.089
941421AE2-139 GEN
Solar/Wind Harmer
0
20328326MANOR_T86
Adder
0.124
223401AF1-299 GEN
Solar/Wind Helper
0.531
316006AB2-029 C
Solar/Wind Helper
0.149
316045AC1-158 PL2
Solar/Wind Helper
5.498
316254AC1-120 GEN1
Solar/Wind Helper
1.411
3147666LOUISA
Solar/Wind Helper
1.21
316192AB2-158 GEN
Solar/Wind Helper
2.03
316337AD2-073 GEN
Solar/Wind Helper
0.456
964211AG1-282 GEN
Solar/Wind Helper
0.402
3141726DUNNSVL
Solar/Wind Helper
1.194
3142416OLDCHRC
Solar/Wind Helper
0.771
3142416OLDCHRC
Solar/Wind Helper
0.295
3138133OCRAN
Solar/Wind Helper
0.178
3141766HARMONY
Solar/Wind Helper
0.059
3142433PROV 92
Solar/Wind Helper
1.181
3143526WINTERP
Solar/Wind Helper
1.533
3142543TWELFTH
Solar/Wind Helper
0.028
3143226MDLTHAN
Solar/Wind Helper
0.294
316159AE1-175 C
Solar/Wind Helper
0.445
316458AB2-190 GEN2
Solar/Wind Helper
1.671
3145336SMITFLD
Solar/Wind Helper
1.162
316294AC1-161 GEN
Solar/Wind Helper
5.311
316381AD1-082 GEN
Solar/Wind Helper
1.502
316375AC2-012 GEN
Solar/Wind Helper
0.759
316072AD1-144
Solar/Wind Helper
0.331
316388AE2-253 GEN
Solar/Wind Helper
1.1
3146456SLIGO L269
Solar/Wind Helper
0.289
316246AF1-032 C
Solar/Wind Helper
0.33
316336AC2-165 C
Solar/Wind Helper
1.553
238148AE2-230_GEN2
Solar/Wind Helper
0.497
3146516WINFALL
Solar/Wind Helper
0.929
3146516WINFALL
Solar/Wind Helper
0.287
315800Z1-036_GEN1
Solar/Wind Helper
1.571
3130156CHOWAN
Solar/Wind Helper
0.285
3145663CRESWEL
Solar/Wind Helper
0.793
966621AG1-532 GEN
Solar/Wind Helper
0.254
3146263WOODLND
Solar/Wind Helper
0.279
313506AB2-031 GEN
Solar/Wind Helper
1.265
942461AE2-259 GEN
Solar/Wind Helper
1.879
3142666NORTHAMPTON
Solar/Wind Helper
0.278
3145963POPLR C
Solar/Wind Helper
0.278
3147043LAWRENC
Solar/Wind Helper
0.167
316317KELFORD C
Solar/Wind Helper
0.237
3145823KELFORD
Solar/Wind Helper
0.278
3147133PAMPLIN
Solar/Wind Helper
0.872
316478AD1-087 GEN
Solar/Wind Helper
1.355
316486AD2-202 GEN
Solar/Wind Helper
0.397
3145796HORNRTN
Solar/Wind Helper
1.108
3145796HORNRTN
Solar/Wind Helper
0.277
315785AD2-033 C
Solar/Wind Helper
3.217
316210AC1-098 GEN
Solar/Wind Helper
2.224
3145933PARMELE
Solar/Wind Helper
0.275
316131AB2-060 GEN
Solar/Wind Helper
1.675
316499AE2-029_GEN
Solar/Wind Helper
0.923
3145746EVERETS
Solar/Wind Helper
0.274
3145746EVERETS
Solar/Wind Helper
0.274
3148013FISHERV
Solar/Wind Helper
0.274
315724AD1-057 GEN
Solar/Wind Helper
0.81
316327AA2-057 GEN
Solar/Wind Helper
1.558
3146233WITAKRS
Solar/Wind Helper
0.293
3146233WITAKRS
Solar/Wind Helper
0.185
3146073TAR RVR
Solar/Wind Helper
0.272
3146083TARBORO
Solar/Wind Helper
0.272
3138543CONSLDL
Solar/Wind Helper
0.179
3145543BTLEBRO
Solar/Wind Helper
0.271
3145543BTLEBRO
Solar/Wind Helper
0.271
316248AF1-058 C
Solar/Wind Helper
0.361
316095T157 G97
Solar/Wind Helper
1.23
315616AA1-038_C
Solar/Wind Helper
1.206
23583801GRNGAP
Solar/Wind Helper
4.529
238221AF1-254 C O1
Solar/Wind Helper
0.258
316283AC2-100 C
Solar/Wind Helper
1.399
238108AE1-109 GEN1
Solar/Wind Helper
0.095
3147312GRETNA
Solar/Wind Helper
0.05
270197AD1-017 GEN1
Solar/Wind Helper
1.333
235067AD1-061 GEN
Solar/Wind Helper
0.44
270018AE2-047 C O1
Solar/Wind Helper
0.865
943811AF1-049 GEN
Solar/Wind Helper
1.493
270336AE1-100 GEN
Solar/Wind Helper
1.035
237030AB1-096 C
Solar/Wind Helper
0.062
235531U2-073 GEN
Solar/Wind Helper
2.539
235054AD2-180 GEN
Solar/Wind Helper
1.519
238117U2-030
Solar/Wind Helper
0.261
238185AF2-356 C
Solar/Wind Helper
1.918
3146173TUNIS
Solar/Wind Helper
0.28
316181AB2-040 GEN
Solar/Wind Helper
2
3142666NORTHAMPTON
Solar/Wind Helper
0.278
3142666NORTHAMPTON
Solar/Wind Helper
0.278
3142666NORTHAMPTON
Solar/Wind Helper
0.278
3142666NORTHAMPTON
Solar/Wind Helper
0.167
316426AA2-053 GEN
Solar/Wind Helper
1.587
3145593CAROLNA
Solar/Wind Helper
0.278
3145593CAROLNA
Solar/Wind Helper
0.278
3147133PAMPLIN
Solar/Wind Helper
0.278
3147133PAMPLIN
Solar/Wind Helper
0.222
315821AE2-092 GEN
Solar/Wind Helper
2.57
3145796HORNRTN
Solar/Wind Helper
0.831
3132123MT JACKSON
Solar/Wind Helper
0.866
23777901MDS_W4-102
Solar/Wind Helper
0.173
316034AC1-036 C
Solar/Wind Helper
0.289
235020AA1-095 C
Solar/Wind Helper
0.051
3145933PARMELE
Solar/Wind Helper
0.55
3145933PARMELE
Solar/Wind Helper
0.275
316274AC1-208 GEN
Solar/Wind Helper
1.676
3146843MT LREL
Solar/Wind Helper
0.271
3146843MT LREL
Solar/Wind Helper
0.271
237034AC2-136 C
Solar/Wind Helper
0.222
316222AC1-221 GEN
Solar/Wind Helper
1.498
270013AE1-250 PV
Solar/Wind Helper
0.92
316197AC1-042 GEN
Solar/Wind Helper
0.234
23777801MSM_W1-116
Solar/Wind Helper
0.107
237002AB1-128_GEN
Solar/Wind Helper
0.389
237001AB1-127_GEN
Solar/Wind Helper
0.386
235063AE1-101 C2
Solar/Wind Helper
1.424
270214AC2-123 GEN
Solar/Wind Helper
0.811
237025AB1-124 C
Solar/Wind Helper
0.144
237006AB1-125 GEN
Solar/Wind Helper
0.108
238120AE2-309 GEN
Solar/Wind Helper
0.406
3145893MURPHYS
Solar/Wind Helper
0.281
3145513AHOSKIE
Solar/Wind Helper
0.125
961941AG1-037 GEN
Solar/Wind Helper
0.094
3145513AHOSKIE
Solar/Wind Helper
0.28
3138266HYDRAULIC
Solar/Wind Helper
0.013
3138266HYDRAULIC
Solar/Wind Helper
0.008
946281AF1-292 GEN
Solar/Wind Helper
0.281
3146043SEABORD
Solar/Wind Helper
0.28
3145683EARLEYS
Solar/Wind Helper
0.559
3145683EARLEYS
Solar/Wind Helper
0.279
3145683EARLEYS
Solar/Wind Helper
0.279
315607AA1-063A GEN
Solar/Wind Helper
1.593
316087AB2-174 GEN
Solar/Wind Helper
1.952
3137643SOCKMAN
Solar/Wind Helper
1.112
3145796HORNRTN
Solar/Wind Helper
0.886
3145796HORNRTN
Solar/Wind Helper
0.111
3146033SCOT NK
Solar/Wind Helper
1.107
3144303KENBRDG
Solar/Wind Helper
0.221
316239AB2-077_GEN
Solar/Wind Helper
0.369
316238AB2-078_GEN
Solar/Wind Helper
0.369
316005AA1-067
Solar/Wind Helper
0.313
3145746EVERETS
Solar/Wind Helper
1.09
3145746EVERETS
Solar/Wind Helper
0.274
3145746EVERETS
Solar/Wind Helper
0.274
3145746EVERETS
Solar/Wind Helper
0.274
3148133STUARTS
Solar/Wind Helper
0.164
3148013FISHERV
Solar/Wind Helper
0.157
316420AA1-050 GEN
Solar/Wind Helper
1.561
3145573BETHELC
Solar/Wind Helper
0.272
3145573BETHELC
Solar/Wind Helper
0.272
270494AE1-108_GEN
Solar/Wind Helper
3.631
316118AC1-105 GEN
Solar/Wind Helper
1.048
3147173SINAI
Solar/Wind Helper
0.268
3147243WELCO
Solar/Wind Helper
0.168
3148463FAIRFLD
Solar/Wind Helper
0.266
316123AC1-075 GEN
Solar/Wind Helper
1.584
238208AF1-136 C
Solar/Wind Helper
0.2
270455AD2-022 GEN
Solar/Wind Helper
1.49
270457AD2-023 GEN
Solar/Wind Helper
0.982
238109AE1-109 GEN2
Solar/Wind Helper
0.095
238110AE1-109 GEN3
Solar/Wind Helper
0.095
237085AD2-009_GEN
Solar/Wind Helper
1.438
270069AE2-166 C O1
Solar/Wind Helper
1.061
238126S14_GEN_1
Solar/Wind Helper
0.637
316023GEN1_S
Solar/Wind Helper
1.07
3146206CASHIE
Solar/Wind Helper
0.281
3145893MURPHYS
Solar/Wind Helper
1.123
316322AB2-045
Solar/Wind Helper
0.313
3146776BUCKING
Solar/Wind Helper
0.112
3146173TUNIS
Solar/Wind Helper
0.28
3146926FARMVIL
Solar/Wind Helper
0.168
3145683EARLEYS
Solar/Wind Helper
0.279
3146263WOODLND
Solar/Wind Helper
0.279
3145963POPLR C
Solar/Wind Helper
0.278
316190AA2-174 GEN
Solar/Wind Helper
0.018
316011AB1-132 GEN
Solar/Wind Helper
2.993
3145823KELFORD
Solar/Wind Helper
0.278
316174AB2-169 GEN
Solar/Wind Helper
0.707
3145783HORNRTN
Solar/Wind Helper
0.277
3145796HORNRTN
Solar/Wind Helper
0.914
3145796HORNRTN
Solar/Wind Helper
0.277
316212AC1-099_GEN
Solar/Wind Helper
1.236
316129AC1-054 GEN
Solar/Wind Helper
1.363
316237AB2-079_GEN
Solar/Wind Helper
0.369
3147983MERCK5
Solar/Wind Helper
0.11
3145746EVERETS
Solar/Wind Helper
0.274
3145746EVERETS
Solar/Wind Helper
0.274
315722AD1-056 GEN
Solar/Wind Helper
1.472
315687AD1-152 GEN
Solar/Wind Helper
1.47
316494AC1-189 GEN
Solar/Wind Helper
1.667
3146233WITAKRS
Solar/Wind Helper
1.082
961671AG1-007 GEN
Solar/Wind Helper
0.195
3146083TARBORO
Solar/Wind Helper
0.272
316359AB2-059 GEN
Solar/Wind Helper
2.063
316049AB1-081 GEN
Solar/Wind Helper
1.65
3145543BTLEBRO
Solar/Wind Helper
0.271
3145543BTLEBRO
Solar/Wind Helper
0.217
316097T157 G90
Solar/Wind Helper
1.23
316003AC1-222 GEN
Solar/Wind Helper
1.156
23779801AA1-109
Solar/Wind Helper
0.184
237080AD1-060 GEN
Solar/Wind Helper
0.313
3147123OTTER R
Solar/Wind Helper
0.15
270016AE1-250 BESS
Solar/Wind Helper
0.92
3147312GRETNA
Solar/Wind Helper
0.199
3146802CHATHAM
Solar/Wind Helper
0.187
237038AE2-054 C
Solar/Wind Helper
0.243
270173AC1-122 GEN
Solar/Wind Helper
1.584
964991AG1-363 GEN
Solar/Wind Helper
3.563
235062AE1-101 C1
Solar/Wind Helper
1.424
958121AF2-106 GEN
Solar/Wind Helper
1.718
23750701CROSSCHOOL
Solar/Wind Helper
1.106
238127S14_GEN_2
Solar/Wind Helper
0.637
238118U2-030_1
Solar/Wind Helper
0.261
HAMLETPJM->LTFIMP_HAMLET
CLTF
6.525
G-007ALTFEXP_G-007A->PJM
CMTX
68.692
CBM NorthLTFEXP_CBM-N->PJM
CBM
95.157
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
5.232
BlueGrassPJM->LTFIMP_BlueG
CLTF
16.303
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
178.729
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.834
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
24.671

Details for PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line l/o PECO_P4_PEACH035_SRT-A/* $ CHESCO $ PECO_P4_PEACH035 $ STBK


Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
Contingency Name:
PECO_P4_PEACH035_SRT-A/* $ CHESCO $ PECO_P4_PEACH035 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:151.88 %
Rating:3620.0 MVA
Rating Type:B
MVA to Mitigate:5498.02
MW Contribution:10.94
Bus #Bus NameTypeMW Contribution
200202DELTA2 ST
50/50
11.481
200195DELTA ST
50/50
5.842
200052ROCKSP 1
50/50
4.804
200053ROCKSP 2
50/50
4.702
232616GEN FOOD
50/50
0.321
232904IR4
50/50
159.021
232920IR10
50/50
6.215
232912OH NUG1
50/50
17.364
232913OH NUG2
50/50
17.133
233973AC2-185 C
Solar/Wind Harmer
6.708
234033AF1-007_GEN
Solar/Wind Harmer
43.342
232432Z2-076 GEN
Solar/Wind Harmer
0.245
233923SMA
Solar/Wind Harmer
8.604
233990AG1-397 GEN
Solar/Wind Harmer
0.102
233955AB2-172 GEN
Solar/Wind Harmer
9.239
232813VAUGHN
Adder
1.083
233968AD2-076_GEN
Solar/Wind Harmer
12.059
970597AG2-380 GEN
Solar/Wind Harmer
7.572
231906DC3 NUG
Adder
25.405
231902DC CT7
Adder
20.31
231907DC10
Adder
6.342
232436AB1-176 C
Solar/Wind Harmer
0.416
971983AH1-536 GEN
Solar/Wind Harmer
13.531
233935AB2-179 C
Solar/Wind Harmer
4.387
231919CHRIST1
Adder
7.533
231920CHRIST2
Adder
7.365
970453AG2-297 GEN
Solar/Wind Harmer
4.054
228260V4-054C
Solar/Wind Harmer
1.487
228309CCLP NUG
Adder
37.255
228309CCLP NUG
Adder
35.437
972141AH1-641 GEN
Solar/Wind Harmer
4.143
964001AG1-254 GEN
Solar/Wind Harmer
2.921
971535AH1-265 GEN
Solar/Wind Harmer
6.086
971011AG2-627 GEN
Solar/Wind Harmer
10.943
227927V4-067C
Solar/Wind Harmer
0.283
228754AB1-001 C
Solar/Wind Harmer
0.199
219137THOSOLAR C
Solar/Wind Harmer
1.669
219272CLEANLIGHT C
Solar/Wind Harmer
0.25
219688LUMSOLAR_S C
Solar/Wind Harmer
0.275
219914AD2-027 C
Solar/Wind Harmer
0.811
213942SCHUYLKILL
Adder
4.707
213942SCHUYLKILL
Adder
3.599
213957STHWK3-4
Adder
3.599
213957STHWK3-4
Adder
3.599
213561DLWR9-10
Adder
4.672
213561DLWR9-10
Adder
3.573
219607WPEMNERT C
Solar/Wind Harmer
0.551
219224BRL12CT4
Adder
11.736
214067T20SOLAR
Solar/Wind Harmer
0.325
213611FALLS1-3
Adder
4.543
213611FALLS1-3
Adder
4.543
20717128DIX_Z2-102
Solar/Wind Harmer
1.696
20715728PEM_W1-119
Solar/Wind Harmer
0.686
20715828PEM_W1-120
Solar/Wind Harmer
0.686
970025AG2-016 GEN
Solar/Wind Harmer
3.612
971189AH1-054 GEN
Solar/Wind Harmer
1.501
207459AE1-142 C O1
Solar/Wind Harmer
1.337
20714328BYD_X4-031
Solar/Wind Harmer
0.347
219620RIDERU C
Solar/Wind Harmer
0.068
20714428HOW_X1-037
Solar/Wind Harmer
1.513
971521AH1-258 GEN
Solar/Wind Harmer
3.273
20720428HOL_W1-112
Solar/Wind Harmer
0.417
20635928PARLN3&4
Adder
8.734
218455CINNBAY_CGEN
Adder
2.136
218526CNTRALGAS2 C
Solar/Wind Harmer
0.431
218524CNTRALGAS1 C
Solar/Wind Harmer
0.429
20675528CPH_W2-050
Solar/Wind Harmer
0.537
218404KENILWRTH C
Adder
1.46
217167KRNY_14
Adder
10.336
217086KRNY_131
Adder
10.248
217147KRNY_1212
Adder
9.831
217147KRNY_1212
Adder
9.656
217146KRNY_1234
Adder
9.634
217146KRNY_1234
Adder
9.568
966261AG1-495 GEN
Solar/Wind Harmer
1.894
20676328BVR_Y1-020
Solar/Wind Harmer
0.345
200201DELTA2 CT2
50/50
6.765
200034PCHBTM 2
50/50
39.365
200035PCHBTM 3
50/50
39.795
200205Y1-065-CTG2
50/50
7.607
232918OH NUG7
50/50
17.249
232905CHERITON_25
50/50
4.823
232926CRISFLD1
50/50
3.858
232899W1-062
50/50
18.904
231940T-011
50/50
1.466
971149AH1-027 GEN
Solar/Wind Harmer
6.286
233939AC1-091 C
Solar/Wind Harmer
1.631
233970AC1-092 C
Solar/Wind Harmer
1.631
233987AB2-037 GEN
Solar/Wind Harmer
21.115
970545AG2-347 GEN
Solar/Wind Harmer
121.287
972069AH1-584 GEN
Solar/Wind Harmer
16.593
972071AH1-585 GEN
Solar/Wind Harmer
16.593
233901CHERRYDALE C
Solar/Wind Harmer
2.086
232408W1-005 C
Solar/Wind Harmer
1.856
232410W1-006 C
Solar/Wind Harmer
1.856
971747AH1-380 GEN
Solar/Wind Harmer
6.637
233946AB2-136 GEN
Solar/Wind Harmer
7.38
200200DELTA2 CT1
50/50
6.765
200193DELTA CT2
50/50
3.78
200203Y1-065-STG
50/50
13.19
200055ROCKSP 4
50/50
4.75
231914HR8
50/50
4.082
231911HR5
50/50
2.686
232914OH NUG3
50/50
17.364
232916OH NUG5
50/50
17.364
232921TASLEY2G
50/50
10.148
234034AF2-060
50/50
3.473
233900O-025 C
50/50
2.315
232911NRG_G2
50/50
0.92
233971AC1-093 C
Solar/Wind Harmer
1.456
970695AG2-447 GEN
Solar/Wind Harmer
6.651
972133AH1-634 GEN
Solar/Wind Harmer
18.377
972073AH1-586 GEN
Solar/Wind Harmer
17.365
232406W1-004 FULL
Solar/Wind Harmer
1.856
233996TM1833_GEN
Solar/Wind Harmer
2.347
233997TMININ_4.2
Solar/Wind Harmer
2.347
233990AG1-397 GEN
Solar/Wind Harmer
2.125
233940AF2-379 C
Solar/Wind Harmer
0.346
234015AF2-250 C
Solar/Wind Harmer
0.223
232907VN8
Adder
55.615
233994AC2-023 GEN
Solar/Wind Harmer
4.978
960671AF2-358 GEN
Solar/Wind Harmer
33.132
232417X3-008 C
Solar/Wind Harmer
3.696
233952AC2-187 GEN
Solar/Wind Harmer
2.08
233918AB1-142 GEN
Solar/Wind Harmer
1.792
233982AB2-133 GEN
Solar/Wind Harmer
8.797
972251AH1-710 GEN
Adder
79.914
228202CUMB CT
Adder
24.179
228711V2-041C
Solar/Wind Harmer
0.878
971553AH1-274 GEN
Solar/Wind Harmer
3.524
230430AE1-229_GEN
Solar/Wind Harmer
12.663
230415AB2-049 C
Solar/Wind Harmer
0.271
228729W2-030 C
Solar/Wind Harmer
0.826
228304LOGAN
Adder
30.777
219623KINSLEYBEA C
Solar/Wind Harmer
0.587
219291REEVESSOUT C
Solar/Wind Harmer
0.082
219766PARADISE C
Solar/Wind Harmer
0.428
213497CHSTR7-9
Adder
3.682
219912AD2-042 GEN
Solar/Wind Harmer
1.076
219236SOUTHERNHQ C
Solar/Wind Harmer
0.09
213958STHWK5-6
Adder
3.599
219906AC1-017 C
Solar/Wind Harmer
0.295
213560DLW11-12
Adder
3.573
219610FLORENCE C
Solar/Wind Harmer
1.822
219348LDSOLAR C
Solar/Wind Harmer
0.787
219221BRL12CT1
Adder
11.736
219223BRL12CT3
Adder
11.736
213815MOSER1-3
Adder
4.591
20716028EGP_W2-019
Solar/Wind Harmer
0.597
20720828JCB_W4-025
Solar/Wind Harmer
0.583
20715028HAN_X4-015
Solar/Wind Harmer
0.384
959561AF2-247 GEN
Solar/Wind Harmer
0.623
20636028O CRK C1
Adder
9.065
971667AH1-334 GEN
Solar/Wind Harmer
3.476
219727YARDVSOLFA C
Solar/Wind Harmer
1.137
20714528FRN_Y2-051
Solar/Wind Harmer
0.367
219276PARKLANDSO C
Solar/Wind Harmer
0.569
20716228APLW2-078
Solar/Wind Harmer
1.077
20720528MAN_W1-024
Solar/Wind Harmer
0.31
219918AC2-009 C
Solar/Wind Harmer
0.075
967451AG2-055 C O1
Solar/Wind Harmer
208.979
219612MATRIX C
Solar/Wind Harmer
0.22
218438BLK ROCK C
Solar/Wind Harmer
0.163
20635828PARLN1&2
Adder
3.956
20635928PARLN3&4
Adder
3.956
20635028RRCT1&2
Adder
13.821
20635128RRCT3&4
Adder
11.459
219908AB1-139 C
Solar/Wind Harmer
0.44
219919AE1-041 FULL
Solar/Wind Harmer
0.047
219249CENTRALDIV C
Solar/Wind Harmer
0.046
20673728F2S_V4-070
Solar/Wind Harmer
0.203
217211CAMDEN ST C
Solar/Wind Harmer
0.027
217186ESSEX_G9
Adder
17.781
217169METRODIV C
Solar/Wind Harmer
0.044
217194REDH C
Solar/Wind Harmer
0.547
20676728BRNX1-095
Solar/Wind Harmer
0.19
20674628WNG_W3-110
Solar/Wind Harmer
0.42
207510AF2-138 C
Solar/Wind Harmer
1.849
971007AG2-625 GEN
Solar/Wind Harmer
2.564
20466127PORT 5CT
Adder
25.964
20465427SHAW CT
Adder
3.744
20633028GILCT9
Adder
27.286
966181AG1-487 GEN
Solar/Wind Harmer
0.242
963071AG1-156 GEN
Solar/Wind Harmer
2.275
234036AF2-325 C
Solar/Wind Harmer
1.695
234041AC1-190 GEN
Solar/Wind Harmer
16.546
233984AB2-036 GEN
Solar/Wind Harmer
22.779
232424Y1-079 C
Solar/Wind Harmer
1.028
234014AF1-036_GEN
Solar/Wind Harmer
4.922
231131BLOOM ENRGY
Adder
7.904
233944AB2-135 GEN
Solar/Wind Harmer
9.487
233933AB2-153 GEN
Solar/Wind Harmer
2.034
232416X2-083
Adder
0.794
228251CARLLS#4
Adder
0.914
230422AE1-104_GEN1
Solar/Wind Harmer
48.595
230425AE1-104_GEN2
Solar/Wind Harmer
48.595
230433AD2-135 GEN
Solar/Wind Harmer
0.145
230407AD2-065 C
Solar/Wind Harmer
0.188
228307PCLP GT
Adder
17.185
228304LOGAN
Adder
34.22
972233AH1-701 GEN
Adder
5.905
219921AF1-264
Solar/Wind Harmer
0.198
213589EDDYSTN4
Adder
107.225
213587EDDYSTN3
Adder
107.204
219615MILLCREEK C
Solar/Wind Harmer
0.316
213535CROYDN11
Adder
13.419
213815MOSER1-3
Adder
4.591
213815MOSER1-3
Adder
4.591
20716428NHV_W2-082
Solar/Wind Harmer
2.288
207500AE2-000G1
Solar/Wind Harmer
40.4
207497AE2-000G2
Solar/Wind Harmer
40.4
207507AE2-000G3
Solar/Wind Harmer
40.4
20636128O CRK C2
Adder
8.265
963401AG1-189 GEN
Solar/Wind Harmer
1.469
963391AG1-188 GEN
Solar/Wind Harmer
2.444
20714928UPF_X1-085
Solar/Wind Harmer
0.516
20628028LAKEHURS
Adder
1.2
219114HARTZY_C
Solar/Wind Harmer
1.048
219817TRENTONSOL C
Solar/Wind Harmer
1.35
20641628MLH_W1-032
Solar/Wind Harmer
0.358
20720628TIN_W1-124
Solar/Wind Harmer
1.216
20716928W4-060COL
Solar/Wind Harmer
0.85
924131AB2-057 GEN
Solar/Wind Harmer
1.209
218440SUMMTASSOC C
Solar/Wind Harmer
0.149
218418LINDEN_G5
Adder
19.676
218419LINDEN_G6
Adder
19.676
972260AH1-715 GEN1
Adder
15.756
20673828FLE_V3-070
Solar/Wind Harmer
0.521
219036LINDEN_G7
Adder
18.966
219035LINDEN_G8
Adder
18.696
972261AH1-715 GEN2
Adder
18.155
207442AE1-156 GEN
Solar/Wind Harmer
0.841
20676128MHD_W3-029
Solar/Wind Harmer
0.539
217081WEATEXAS C
Solar/Wind Harmer
0.097
217202FBANKSOLAR C
Solar/Wind Harmer
0.082
217201HACKENSOLA C
Solar/Wind Harmer
0.082
972237AH1-703 GEN
Adder
11.257
217206BARNGR HS C
Solar/Wind Harmer
0.034
217086KRNY_131
Adder
10.358
217083KRNY_132
Adder
10.27
20671828STAW2-080
Solar/Wind Harmer
0.116
217204WCALDSOLAR C
Solar/Wind Harmer
0.081
20674528F3S_W2-016
Solar/Wind Harmer
1.531
20676228FRD_X1-012
Solar/Wind Harmer
0.613
207471AF2-354 C
Solar/Wind Harmer
0.515
20674928WA_W3-044
Solar/Wind Harmer
0.485
964851AG1-348 GEN
Solar/Wind Harmer
1.756
20634528N27_Y2-018
Solar/Wind Harmer
0.269
20465127PORT CT
Adder
3.897
20674128FR_U2-059
Solar/Wind Harmer
0.179
966111AG1-480 GEN
Solar/Wind Harmer
0.084
966111AG1-480 GEN
Solar/Wind Harmer
3.195
211065PSPA IPP
Solar/Wind Harmer
0.408
211065PSPA IPP
Solar/Wind Harmer
0.408
209029WAYMART-WD
Solar/Wind Harmer
2.39
209009PEIP 2
Adder
6.491
209010PEIP 1
Adder
2.941
209010PEIP 1
Adder
0.431
208972BECR K09
Solar/Wind Harmer
0.853
961541AF2-445A GEN
Solar/Wind Harmer
2.426
961431AF2-434 GEN
Solar/Wind Harmer
0.716
209054AE2-059 GEN
Solar/Wind Harmer
1.142
209059AE2-084 GEN
Solar/Wind Harmer
1.685
946751AF1-339 GEN
Solar/Wind Harmer
0.659
209130AF1-271A GEN
Solar/Wind Harmer
1.841
226929AD2-058 GEN
Solar/Wind Helper
0.116
200192DELTA CT1
50/50
3.78
200194DELTA CT3
50/50
3.78
200204Y1-065-CTG1
50/50
7.607
200054ROCKSP 3
50/50
4.852
231912HR6
50/50
2.686
231913HR7
50/50
2.686
233920W3-032A-CTG1
50/50
4.085
233921W3-032A-STG1
50/50
2.453
232901NORTHST
50/50
16.402
232917OH NUG6
50/50
17.287
232915OH NUG4
50/50
17.249
232900DEMECSMY
50/50
18.133
232910NRG_G1
50/50
16.817
233972AC1-094 C
Solar/Wind Harmer
1.232
232434Z2-077 GEN
Solar/Wind Harmer
0.464
232404W1-003 C
Solar/Wind Harmer
1.856
972177AH1-672 GEN
Solar/Wind Harmer
24.887
233998TM1NIN_3.36
Solar/Wind Harmer
2.347
971195AH1-057 GEN
Solar/Wind Harmer
2.028
232428Y3-058 C
Solar/Wind Harmer
1.545
232919VN10
Adder
5.194
965821AG1-450 GEN
Solar/Wind Harmer
9.632
232426Y1-080 FULL
Solar/Wind Harmer
0.354
970277AG2-181 GEN
Solar/Wind Harmer
9.276
233964AF2-378 GEN
Solar/Wind Harmer
0.236
233954AC2-188 GEN
Solar/Wind Harmer
2.08
233950AC2-186 GEN
Solar/Wind Harmer
1.04
234012AE2-112_GEN
Solar/Wind Harmer
4.184
232422X3-066 FULL
Solar/Wind Harmer
0.454
233930AB2-032 GEN
Solar/Wind Harmer
1.508
233915AB1-141 GEN
Solar/Wind Harmer
1.792
231918WEST 1
Adder
5.736
231917EM10
Adder
3.965
228206SHRMN CT
Adder
24.205
228732V1-021 C
Adder
0.275
945431AF1-208 GEN
Solar/Wind Harmer
12.478
970997AG2-616 GEN
Solar/Wind Harmer
13.811
228351V2-046C
Solar/Wind Harmer
2.892
230511AF1-262
Solar/Wind Harmer
0.263
228728W1-130C
Solar/Wind Harmer
0.951
230434AG1-499 GEN
Solar/Wind Harmer
0.825
219258KINSLEYDEP C
Solar/Wind Harmer
0.443
218660EHAMPSOLAR C
Solar/Wind Harmer
0.239
219686LUMSOLAR_N C
Solar/Wind Harmer
0.276
219287REEVESEAST C
Solar/Wind Harmer
1.833
219904AC1-010 C
Solar/Wind Harmer
0.515
213497CHSTR7-9
Adder
3.682
213497CHSTR7-9
Adder
3.682
219907AC1-030 C
Solar/Wind Harmer
0.186
213958STHWK5-6
Adder
3.599
213560DLW11-12
Adder
3.573
219304NAMERICA C
Solar/Wind Harmer
0.408
219222BRL12CT2
Adder
11.736
20720728JCB_W1-129
Solar/Wind Harmer
0.384
207522AF2-254 C
Solar/Wind Harmer
1.846
213611FALLS1-3
Adder
4.543
207487AE2-000G4
Solar/Wind Harmer
40.4
214194N WALES4
Adder
1.078
207445AB1-138_GEN
Solar/Wind Harmer
0.732
20628028LAKEHURS
Adder
2.374
963711AG1-223 GEN
Solar/Wind Harmer
1.841
20714828MDF_W3-079
Solar/Wind Harmer
0.381
207454AA2-184 E
Solar/Wind Harmer
1.22
20715228NPK_W1-113
Solar/Wind Harmer
0.524
219680HOPEWELLV C1
Solar/Wind Harmer
0.092
20742028HF_AC1-207
Solar/Wind Harmer
0.952
217197RE CRAN C
Solar/Wind Harmer
0.641
20635828PARLN1&2
Adder
8.734
20635028RRCT1&2
Adder
13.609
20635128RRCT3&4
Adder
13.136
218428ETC SOLAR C
Solar/Wind Harmer
0.041
217213AMBOY SO C
Solar/Wind Harmer
0.146
972275AH1-722 GEN
Adder
36.172
218449LINSOLAR C
Solar/Wind Harmer
1.141
207528AF2-192 GEN
Solar/Wind Harmer
0.625
20673628F1S_V4-069
Solar/Wind Harmer
0.203
20675428EAM_W2-061
Solar/Wind Harmer
0.213
20676428JCR_X2-075
Solar/Wind Harmer
0.385
217209CENTRL HS C
Solar/Wind Harmer
0.05
217121ECCF
Adder
0.483
217083KRNY_132
Adder
10.336
217208PARK ELE C
Solar/Wind Harmer
0.028
207439AE1-081 C O1
Solar/Wind Harmer
0.062
20674328GAR_V4-001
Solar/Wind Harmer
0.114
20675828AU_W4-064
Solar/Wind Harmer
0.179
971519AH1-257 GEN
Solar/Wind Harmer
2.509
207518AF1-320_GEN
Solar/Wind Harmer
3.599
20465127PORT CT
Adder
2.937
207437AD2-070 GEN
Solar/Wind Harmer
0.295
20671928W4-073
Solar/Wind Harmer
0.421
966181AG1-487 GEN
Solar/Wind Harmer
3.611
208909MACR G3
Adder
151.733
209010PEIP 1
Adder
0.535
961301AF2-421 GEN
Solar/Wind Harmer
0.819
963151AG1-164 GEN
Solar/Wind Harmer
0.819
209023WIENIPP1
Adder
8.831
209025WIENIPP3
Adder
4.408
212266LOR1
Solar/Wind Harmer
0.097
970237AG2-161 GEN
Solar/Wind Harmer
2.594
961341AF2-425 GEN
Solar/Wind Harmer
0.719
212174INGE
Adder
0.795
212507AE2-042_GEN
Solar/Wind Harmer
2.023
946731AF1-337 GEN
Solar/Wind Harmer
0.659
209071AE2-133 GEN
Solar/Wind Harmer
1.109
970665AG2-430 GEN
Solar/Wind Harmer
6.497
209018SUNBIPCT
Adder
4.877
205941AD2-115 GEN
Solar/Wind Harmer
0.572
972241AH1-705 GEN
Adder
3.348
223401AF1-299 GEN
Solar/Wind Helper
0.472
316006AB2-029 C
Solar/Wind Helper
0.115
316045AC1-158 PL2
Solar/Wind Helper
4.27
316254AC1-120 GEN1
Solar/Wind Helper
1.097
3147666LOUISA
Solar/Wind Helper
0.948
316192AB2-158 GEN
Solar/Wind Helper
1.591
316337AD2-073 GEN
Solar/Wind Helper
0.359
964211AG1-282 GEN
Solar/Wind Helper
0.318
3141726DUNNSVL
Solar/Wind Helper
0.943
3142416OLDCHRC
Solar/Wind Helper
0.609
3142416OLDCHRC
Solar/Wind Helper
0.233
3138133OCRAN
Solar/Wind Helper
0.141
3141766HARMONY
Solar/Wind Helper
0.047
3142433PROV 92
Solar/Wind Helper
0.935
3143526WINTERP
Solar/Wind Helper
1.213
3142543TWELFTH
Solar/Wind Helper
0.022
3143226MDLTHAN
Solar/Wind Helper
0.233
316159AE1-175 C
Solar/Wind Helper
0.353
316458AB2-190 GEN2
Solar/Wind Helper
1.326
3145336SMITFLD
Solar/Wind Helper
0.925
316294AC1-161 GEN
Solar/Wind Helper
4.225
316381AD1-082 GEN
Solar/Wind Helper
1.195
316375AC2-012 GEN
Solar/Wind Helper
0.604
316072AD1-144
Solar/Wind Helper
0.263
316388AE2-253 GEN
Solar/Wind Helper
0.877
3146456SLIGO L269
Solar/Wind Helper
0.23
316246AF1-032 C
Solar/Wind Helper
0.263
316336AC2-165 C
Solar/Wind Helper
1.237
3146516WINFALL
Solar/Wind Helper
0.742
3146516WINFALL
Solar/Wind Helper
0.229
315800Z1-036_GEN1
Solar/Wind Helper
1.257
3130156CHOWAN
Solar/Wind Helper
0.228
3145663CRESWEL
Solar/Wind Helper
0.636
238148AE2-230_GEN2
Solar/Wind Helper
0.392
316023GEN1_S
Solar/Wind Helper
0.86
3146206CASHIE
Solar/Wind Helper
0.226
3145893MURPHYS
Solar/Wind Helper
0.903
3146173TUNIS
Solar/Wind Helper
0.225
316322AB2-045
Solar/Wind Helper
0.251
3146776BUCKING
Solar/Wind Helper
0.09
3146926FARMVIL
Solar/Wind Helper
0.135
3145683EARLEYS
Solar/Wind Helper
0.225
3146263WOODLND
Solar/Wind Helper
0.225
3145963POPLR C
Solar/Wind Helper
0.224
316190AA2-174 GEN
Solar/Wind Helper
0.015
316011AB1-132 GEN
Solar/Wind Helper
2.415
3145823KELFORD
Solar/Wind Helper
0.224
316174AB2-169 GEN
Solar/Wind Helper
0.571
3145783HORNRTN
Solar/Wind Helper
0.224
3145796HORNRTN
Solar/Wind Helper
0.738
3145796HORNRTN
Solar/Wind Helper
0.224
316212AC1-099_GEN
Solar/Wind Helper
1
316129AC1-054 GEN
Solar/Wind Helper
1.103
23779801AA1-109
Solar/Wind Helper
0.161
970095AG2-074 GEN
Solar/Wind Harmer
5.164
963161AG1-165 GEN
Solar/Wind Harmer
0.819
209025WIENIPP3
Adder
4.319
209027LOR2_Q27
Solar/Wind Harmer
3.378
209022WHFR IPP
Adder
2.425
961331AF2-424 GEN
Solar/Wind Harmer
0.719
961421AF2-433 GEN
Solar/Wind Harmer
0.716
957921AF2-086 GEN
Solar/Wind Harmer
0.697
209142AF1-226 GEN
Solar/Wind Harmer
4.147
209093AE2-110 GEN
Solar/Wind Harmer
1.791
209120AE2-241 GEN
Solar/Wind Harmer
2.369
972245AH1-707 GEN
Adder
3.776
946691AF1-333 GEN
Solar/Wind Harmer
0.659
946741AF1-338 GEN
Solar/Wind Harmer
0.659
223402AF1-300 C
Solar/Wind Helper
0.472
226910AB2-157 C
Solar/Wind Helper
0.017
227287AC2-120 GEN
Solar/Wind Helper
0.411
3141196NOKESVL
Solar/Wind Helper
0.976
316044AC1-158 PL1
Solar/Wind Helper
1.334
316450AC1-158 RIC
Solar/Wind Helper
0.356
966881AG1-559 GEN
Solar/Wind Helper
0.323
316170AC1-121 GEN2
Solar/Wind Helper
0.366
3141906WESTMOR
Solar/Wind Helper
0.095
3132273ORANGE
Solar/Wind Helper
0.047
3147666LOUISA
Solar/Wind Helper
0.545
316404AE1-155 C
Solar/Wind Helper
1.987
316473AC1-191 GEN
Solar/Wind Helper
1.437
316484AD2-074 GEN
Solar/Wind Helper
0.454
316156AD2-030 GEN
Solar/Wind Helper
0.353
316280AD1-041 GEN
Solar/Wind Helper
0.786
3142946ENON
Solar/Wind Helper
0.078
316382AG1-145 C
Solar/Wind Helper
0.313
315839AE2-212 C
Solar/Wind Helper
0.311
3145336SMITFLD
Solar/Wind Helper
0.092
315773AC2-141 GEN
Solar/Wind Helper
4.972
3144536CHRHLND
Solar/Wind Helper
0.035
3144873MCLAUGH
Solar/Wind Helper
0.006
316313AB2-026
Solar/Wind Helper
0.351
316258AE1-075 C
Solar/Wind Helper
0.316
316405AF2-144 C
Solar/Wind Helper
0.263
3146456SLIGO L269
Solar/Wind Helper
0.23
316320Y1-086
Solar/Wind Helper
0.103
316435W1029_GEN3
Solar/Wind Helper
0.926
3146516WINFALL
Solar/Wind Helper
0.229
3146626S HERTFORD
Solar/Wind Helper
0.229
3145273HOLLAND
Solar/Wind Helper
0.172
3146376EDENTON
Solar/Wind Helper
0.228
315614AA2-178 GEN
Solar/Wind Helper
1.384
238147AE2-230_GEN1
Solar/Wind Helper
0.39
238149AF1-291A_GEN
Solar/Wind Helper
0.111
315737AD1-076 GEN
Solar/Wind Helper
2.212
237061AD1-155 GEN
Solar/Wind Helper
0.043
316365GEN2_N
Solar/Wind Helper
0.86
3146206CASHIE
Solar/Wind Helper
0.226
3145893MURPHYS
Solar/Wind Helper
0.081
3145893MURPHYS
Solar/Wind Helper
0.226
3146173TUNIS
Solar/Wind Helper
0.225
3146776BUCKING
Solar/Wind Helper
0.081
3156021HOLLOMANSOL
Solar/Wind Helper
1.715
316463AE2-346 GEN
Solar/Wind Helper
0.206
316140AB2-099
Solar/Wind Helper
0.086
966621AG1-532 GEN
Solar/Wind Helper
0.205
3146926FARMVIL
Solar/Wind Helper
0.135
3146263WOODLND
Solar/Wind Helper
0.225
313506AB2-031 GEN
Solar/Wind Helper
1.02
942461AE2-259 GEN
Solar/Wind Helper
1.514
3142666NORTHAMPTON
Solar/Wind Helper
0.224
3145963POPLR C
Solar/Wind Helper
0.224
316317KELFORD C
Solar/Wind Helper
0.191
3145823KELFORD
Solar/Wind Helper
0.224
3147043LAWRENC
Solar/Wind Helper
0.135
3147133PAMPLIN
Solar/Wind Helper
0.703
316478AD1-087 GEN
Solar/Wind Helper
1.094
316486AD2-202 GEN
Solar/Wind Helper
0.32
3145796HORNRTN
Solar/Wind Helper
0.895
3145796HORNRTN
Solar/Wind Helper
0.224
315785AD2-033 C
Solar/Wind Helper
2.601
316210AC1-098 GEN
Solar/Wind Helper
1.8
3145933PARMELE
Solar/Wind Helper
0.223
316447AC1-158 HLD
Solar/Wind Helper
2.936
315651AD1-115 GEN
Solar/Wind Helper
0.804
316468AD1-105 GEN
Solar/Wind Helper
1.182
316077AC2-138 C
Solar/Wind Helper
0.222
966001AG1-469 GEN
Solar/Wind Helper
0.252
966871AG1-558 GEN
Solar/Wind Helper
0.317
316487AF1-042 GEN
Solar/Wind Helper
0.238
316075AC2-137 C
Solar/Wind Helper
0.356
3142946ENON
Solar/Wind Helper
0.023
3143526WINTERP
Solar/Wind Helper
1.213
316240AF1-291 C
Solar/Wind Helper
0.312
316033AB2-134 GEN
Solar/Wind Helper
0.797
315697AD1-025 GEN
Solar/Wind Helper
2.65
316236AE1-162_GEN
Solar/Wind Helper
0.311
238175AF1-290_GEN
Solar/Wind Helper
0.121
316036AC1-147 C
Solar/Wind Helper
0.351
316316AC1-027 C
Solar/Wind Helper
0.364
3142956BIRDNECK
Solar/Wind Helper
0.155
316185AD1-033 GEN
Solar/Wind Helper
1.084
3145506HICKORY
Solar/Wind Helper
0.921
3145506HICKORY
Solar/Wind Helper
0.553
3145506HICKORY
Solar/Wind Helper
0.138
238169AE2-226 GEN1
Solar/Wind Helper
0.561
238170AE2-226 GEN2
Solar/Wind Helper
0.561
316339AD2-160 GEN
Solar/Wind Helper
0.877
316018AA1-139 ULT2
Solar/Wind Helper
0.99
316017AA1-139 ULT1
Solar/Wind Helper
1.052
3137176SLIGO L2192
Solar/Wind Helper
0.916
3130086AYDLETT
Solar/Wind Helper
0.92
3146386ELIZ CT
Solar/Wind Helper
0.23
316431W1029_GEN1
Solar/Wind Helper
0.926
316433W1029_GEN2
Solar/Wind Helper
0.926
3146516WINFALL
Solar/Wind Helper
0.229
3146516WINFALL
Solar/Wind Helper
0.229
3146516WINFALL
Solar/Wind Helper
0.229
3146626S HERTFORD
Solar/Wind Helper
0.229
3146626S HERTFORD
Solar/Wind Helper
0.229
3144356SAPONY
Solar/Wind Helper
0.41
315742AE1-103 GEN
Solar/Wind Helper
0.368
3145893MURPHYS
Solar/Wind Helper
0.324
3145893MURPHYS
Solar/Wind Helper
0.407
3146173TUNIS
Solar/Wind Helper
0.225
3146173TUNIS
Solar/Wind Helper
0.225
3146776BUCKING
Solar/Wind Helper
0.902
3146776BUCKING
Solar/Wind Helper
0.073
316181AB2-040 GEN
Solar/Wind Helper
1.612
3142666NORTHAMPTON
Solar/Wind Helper
0.224
3142666NORTHAMPTON
Solar/Wind Helper
0.224
3142666NORTHAMPTON
Solar/Wind Helper
0.224
3142666NORTHAMPTON
Solar/Wind Helper
0.135
316426AA2-053 GEN
Solar/Wind Helper
1.28
3145593CAROLNA
Solar/Wind Helper
0.224
3145593CAROLNA
Solar/Wind Helper
0.224
3147133PAMPLIN
Solar/Wind Helper
0.224
3147133PAMPLIN
Solar/Wind Helper
0.179
3145796HORNRTN
Solar/Wind Helper
0.671
315821AE2-092 GEN
Solar/Wind Helper
2.07
316034AC1-036 C
Solar/Wind Helper
0.234
23777901MDS_W4-102
Solar/Wind Helper
0.14
237034AC2-136 C
Solar/Wind Helper
0.184
3145933PARMELE
Solar/Wind Helper
0.446
3145933PARMELE
Solar/Wind Helper
0.223
316274AC1-208 GEN
Solar/Wind Helper
1.357
207511W3-106 GEN
Solar/Wind Harmer
0.682
207530AG1-191 GEN
Solar/Wind Harmer
1.422
20674828DL_W4-046
Solar/Wind Harmer
0.652
971009AG2-626 GEN
Solar/Wind Harmer
1.636
207408W3-077 C
Solar/Wind Harmer
0.5
20675728RH_W2-091
Solar/Wind Harmer
0.337
966421AG1-511 GEN
Solar/Wind Harmer
8.499
20675928HOL_W4-097
Solar/Wind Harmer
0.128
207484AF2-139 C O1
Solar/Wind Harmer
0.494
20675128HRM_W1-127
Solar/Wind Harmer
0.165
20462827N BANGR8
Adder
0.695
209116AE2-175 GEN
Solar/Wind Harmer
3.823
961261AF2-417 GEN
Solar/Wind Harmer
0.872
209026WIENIPP4
Adder
4.363
209045AE2-271 GEN
Solar/Wind Harmer
11.848
959431AF2-234 GEN
Solar/Wind Harmer
1.309
964051AG1-259 GEN
Solar/Wind Harmer
0.878
964061AG1-260 GEN
Solar/Wind Harmer
0.878
959421AF2-233 GEN
Solar/Wind Harmer
0.655
3141426STAFORD
Solar/Wind Helper
0.055
3138216PACIFIC
Solar/Wind Helper
0.041
316411AF1-147_GEN1
Solar/Wind Helper
0.824
316415AF1-147_GEN2
Solar/Wind Helper
0.824
316164AC1-076 GEN
Solar/Wind Helper
1.142
316223AC1-118
Solar/Wind Helper
0.362
3141813NORNECK
Solar/Wind Helper
0.236
3141783LANCAST
Solar/Wind Helper
0.141
3141783LANCAST
Solar/Wind Helper
0.094
316312AB1-027
Solar/Wind Helper
0.446
3138133OCRAN
Solar/Wind Helper
0.07
3141913WHIT STONE
Solar/Wind Helper
0.234
316059AD1-063 C
Solar/Wind Helper
0.236
957601AF2-054 GEN
Solar/Wind Helper
0.314
3141873WAN 176
Solar/Wind Helper
0.047
315662AE1-191 GEN
Solar/Wind Helper
1.257
315666AE1-190 GEN
Solar/Wind Helper
0.314
3143873LANEXA
Solar/Wind Helper
0.14
316233AE1-074 FULL
Solar/Wind Helper
0.356
957831AF2-077 GEN
Solar/Wind Helper
0.314
316132AB2-190 GEN1
Solar/Wind Helper
1.326
316369SG1_INVT
Solar/Wind Helper
1.115
3143316POE
Solar/Wind Helper
0.915
316349AD2-085 GEN
Solar/Wind Helper
1.053
319010AE1-072 C
Solar/Wind Helper
2.629
316305AF2-043 C
Solar/Wind Helper
0.309
313526AB2-022
Solar/Wind Helper
0.35
3146486SUNBURY
Solar/Wind Helper
0.23
3146486SUNBURY
Solar/Wind Helper
0.23
316321Z2-027
Solar/Wind Helper
0.35
3145176PASQUOTANK
Solar/Wind Helper
0.142
316315AB2-025 C
Solar/Wind Helper
0.349
315611Z1-036_GEN2
Solar/Wind Helper
1.257
3130156CHOWAN
Solar/Wind Helper
0.228
3130156CHOWAN
Solar/Wind Helper
0.228
315816AE2-034 GEN
Solar/Wind Helper
1.038
23546401DTGZ2-030
Solar/Wind Helper
0.071
238152AF2-075_GEN
Solar/Wind Helper
0.557
3130546PLYMOUTH
Solar/Wind Helper
0.226
315732AD1-074 GEN1
Solar/Wind Helper
2.586
315733AD1-074 GEN2
Solar/Wind Helper
2.586
315735AD1-075 GEN1
Solar/Wind Helper
1.293
3146206CASHIE
Solar/Wind Helper
0.226
3145893MURPHYS
Solar/Wind Helper
0.61
3145893MURPHYS
Solar/Wind Helper
0.226
3145513AHOSKIE
Solar/Wind Helper
0.101
961941AG1-037 GEN
Solar/Wind Helper
0.076
3145513AHOSKIE
Solar/Wind Helper
0.225
946281AF1-292 GEN
Solar/Wind Helper
0.226
3146043SEABORD
Solar/Wind Helper
0.225
3145683EARLEYS
Solar/Wind Helper
0.45
3145683EARLEYS
Solar/Wind Helper
0.225
3145683EARLEYS
Solar/Wind Helper
0.225
315607AA1-063A GEN
Solar/Wind Helper
1.284
316087AB2-174 GEN
Solar/Wind Helper
1.573
3138266HYDRAULIC
Solar/Wind Helper
0.01
3138266HYDRAULIC
Solar/Wind Helper
0.006
3137643SOCKMAN
Solar/Wind Helper
0.897
3145796HORNRTN
Solar/Wind Helper
0.716
3145796HORNRTN
Solar/Wind Helper
0.089
3146033SCOT NK
Solar/Wind Helper
0.894
3144303KENBRDG
Solar/Wind Helper
0.179
HAMLETPJM->LTFIMP_HAMLET
CLTF
5.45
G-007ALTFEXP_G-007A->PJM
CMTX
60.105
CBM NorthLTFEXP_CBM-N->PJM
CBM
74.634
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
4.689
BlueGrassPJM->LTFIMP_BlueG
CLTF
14.605
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
151.676
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.238
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
21.969

Details for PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line l/o PECO_P1-2_5007_SRT-A/* $ CHESCO $ PECO_P1-2_5007 $ L


Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
Contingency Name:
PECO_P1-2_5007_SRT-A/* $ CHESCO $ PECO_P1-2_5007 $ L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:142.36 %
Rating:3620.0 MVA
Rating Type:B
MVA to Mitigate:5153.54
MW Contribution:7.82
Bus #Bus NameTypeMW Contribution
200192DELTA CT1
50/50
3.676
200194DELTA CT3
50/50
3.676
200204Y1-065-CTG1
50/50
7.429
200054ROCKSP 3
50/50
4.739
232901NORTHST
Adder
15.55
233972AC1-094 C
Solar/Wind Harmer
0.587
232434Z2-077 GEN
Solar/Wind Harmer
0.079
232917OH NUG6
Adder
16.412
232915OH NUG4
Adder
16.376
233998TM1NIN_3.36
Solar/Wind Harmer
0.003
232404W1-003 C
Solar/Wind Harmer
1.209
971195AH1-057 GEN
Solar/Wind Harmer
1.166
232428Y3-058 C
Solar/Wind Harmer
0.003
972177AH1-672 GEN
Solar/Wind Harmer
19.001
232919VN10
Adder
5.234
965821AG1-450 GEN
Solar/Wind Harmer
9.708
232900DEMECSMY
Adder
17.198
232426Y1-080 FULL
Solar/Wind Harmer
0
970277AG2-181 GEN
Solar/Wind Harmer
1.087
233964AF2-378 GEN
Solar/Wind Harmer
0
233954AC2-188 GEN
Solar/Wind Harmer
0.002
233950AC2-186 GEN
Solar/Wind Harmer
0.001
232910NRG_G1
Adder
15.986
234012AE2-112_GEN
Solar/Wind Harmer
4.275
232422X3-066 FULL
Solar/Wind Harmer
0.154
233930AB2-032 GEN
Solar/Wind Harmer
1.755
233915AB1-141 GEN
Solar/Wind Harmer
0.47
231918WEST 1
Adder
5.882
231917EM10
Adder
4.08
228206SHRMN CT
Adder
24.635
228732V1-021 C
Adder
0.28
945431AF1-208 GEN
Solar/Wind Harmer
8.885
970997AG2-616 GEN
Solar/Wind Harmer
10.614
228351V2-046C
Solar/Wind Harmer
0.001
230511AF1-262
Solar/Wind Harmer
0
228728W1-130C
Solar/Wind Harmer
0.001
230434AG1-499 GEN
Solar/Wind Harmer
0.002
213497CHSTR7-9
Adder
3.912
213497CHSTR7-9
Adder
3.912
219258KINSLEYDEP C
Solar/Wind Harmer
0.001
219904AC1-010 C
Solar/Wind Harmer
0.001
218660EHAMPSOLAR C
Solar/Wind Harmer
0
219686LUMSOLAR_N C
Solar/Wind Harmer
0
219287REEVESEAST C
Solar/Wind Harmer
0
213958STHWK5-6
Adder
3.798
219907AC1-030 C
Solar/Wind Harmer
0
213560DLW11-12
Adder
3.737
219304NAMERICA C
Solar/Wind Harmer
0.124
219222BRL12CT2
Adder
12.077
213611FALLS1-3
Adder
4.678
20720728JCB_W1-129
Solar/Wind Harmer
0
207522AF2-254 C
Solar/Wind Harmer
1.218
207487AE2-000G4
Solar/Wind Harmer
16.536
214194N WALES4
Adder
1.114
207445AB1-138_GEN
Solar/Wind Harmer
0.001
20628028LAKEHURS
Adder
2.422
20714828MDF_W3-079
Solar/Wind Harmer
0.125
207454AA2-184 E
Solar/Wind Harmer
0.002
20715228NPK_W1-113
Solar/Wind Harmer
0.001
20742028HF_AC1-207
Solar/Wind Harmer
0.001
217197RE CRAN C
Solar/Wind Harmer
0
20635828PARLN1&2
Adder
8.908
20635028RRCT1&2
Adder
13.88
20635128RRCT3&4
Adder
13.398
217213AMBOY SO C
Solar/Wind Harmer
0
972275AH1-722 GEN
Adder
36.902
218449LINSOLAR C
Solar/Wind Harmer
0
207528AF2-192 GEN
Solar/Wind Harmer
0.001
20673628F1S_V4-069
Solar/Wind Harmer
0
20675428EAM_W2-061
Solar/Wind Harmer
0
20676428JCR_X2-075
Solar/Wind Harmer
0
217121ECCF
Adder
0.493
217083KRNY_132
Adder
10.541
20674328GAR_V4-001
Solar/Wind Harmer
0
20675828AU_W4-064
Solar/Wind Harmer
0
971519AH1-257 GEN
Solar/Wind Harmer
1.653
207437AD2-070 GEN
Solar/Wind Harmer
0.066
20465127PORT CT
Adder
2.993
20671928W4-073
Solar/Wind Harmer
0
966181AG1-487 GEN
Solar/Wind Harmer
3.755
208909MACR G3
Adder
154.619
209010PEIP 1
Adder
0.544
209023WIENIPP1
Adder
8.981
209025WIENIPP3
Adder
4.483
212266LOR1
Solar/Wind Harmer
0.365
212174INGE
Adder
0.807
212507AE2-042_GEN
Solar/Wind Harmer
0.421
209071AE2-133 GEN
Solar/Wind Harmer
0.001
970665AG2-430 GEN
Solar/Wind Harmer
4.817
209018SUNBIPCT
Adder
4.949
970757AG2-479 GEN
Solar/Wind Harmer
0.524
205941AD2-115 GEN
Solar/Wind Harmer
0.074
972241AH1-705 GEN
Adder
3.392
20467927PC_Q59Y356
Adder
0.451
223401AF1-299 GEN
Solar/Wind Helper
0.483
316006AB2-029 C
Solar/Wind Helper
0.119
316045AC1-158 PL2
Solar/Wind Helper
4.427
316254AC1-120 GEN1
Solar/Wind Helper
1.137
3147666LOUISA
Solar/Wind Helper
0.983
316192AB2-158 GEN
Solar/Wind Helper
1.65
316337AD2-073 GEN
Solar/Wind Helper
0.373
964211AG1-282 GEN
Solar/Wind Helper
0.329
3141726DUNNSVL
Solar/Wind Helper
0.978
3142416OLDCHRC
Solar/Wind Helper
0.632
3142416OLDCHRC
Solar/Wind Helper
0.242
3138133OCRAN
Solar/Wind Helper
0.146
3141766HARMONY
Solar/Wind Helper
0.049
3142433PROV 92
Solar/Wind Helper
0.97
3143526WINTERP
Solar/Wind Helper
1.258
3142543TWELFTH
Solar/Wind Helper
0.023
3143226MDLTHAN
Solar/Wind Helper
0.242
316159AE1-175 C
Solar/Wind Helper
0.366
316458AB2-190 GEN2
Solar/Wind Helper
1.376
3145336SMITFLD
Solar/Wind Helper
0.959
316294AC1-161 GEN
Solar/Wind Helper
4.382
316381AD1-082 GEN
Solar/Wind Helper
1.24
316375AC2-012 GEN
Solar/Wind Helper
0.627
316072AD1-144
Solar/Wind Helper
0.273
316388AE2-253 GEN
Solar/Wind Helper
0.909
3146456SLIGO L269
Solar/Wind Helper
0.239
316246AF1-032 C
Solar/Wind Helper
0.273
316336AC2-165 C
Solar/Wind Helper
1.283
3146516WINFALL
Solar/Wind Helper
0.77
3146516WINFALL
Solar/Wind Helper
0.238
315800Z1-036_GEN1
Solar/Wind Helper
1.304
3130156CHOWAN
Solar/Wind Helper
0.237
3145663CRESWEL
Solar/Wind Helper
0.66
238148AE2-230_GEN2
Solar/Wind Helper
0.406
316023GEN1_S
Solar/Wind Helper
0.893
3146206CASHIE
Solar/Wind Helper
0.234
3145893MURPHYS
Solar/Wind Helper
0.937
3146173TUNIS
Solar/Wind Helper
0.234
316322AB2-045
Solar/Wind Helper
0.261
3146776BUCKING
Solar/Wind Helper
0.094
3146926FARMVIL
Solar/Wind Helper
0.14
3145683EARLEYS
Solar/Wind Helper
0.234
3146263WOODLND
Solar/Wind Helper
0.233
3145963POPLR C
Solar/Wind Helper
0.233
316190AA2-174 GEN
Solar/Wind Helper
0.015
316011AB1-132 GEN
Solar/Wind Helper
2.506
3145823KELFORD
Solar/Wind Helper
0.233
316174AB2-169 GEN
Solar/Wind Helper
0.592
3145783HORNRTN
Solar/Wind Helper
0.232
3145796HORNRTN
Solar/Wind Helper
0.766
3145796HORNRTN
Solar/Wind Helper
0.232
316212AC1-099_GEN
Solar/Wind Helper
1.038
316129AC1-054 GEN
Solar/Wind Helper
1.145
23779801AA1-109
Solar/Wind Helper
0.167
316237AB2-079_GEN
Solar/Wind Helper
0.31
3145746EVERETS
Solar/Wind Helper
0.231
3145746EVERETS
Solar/Wind Helper
0.231
315722AD1-056 GEN
Solar/Wind Helper
1.239
315687AD1-152 GEN
Solar/Wind Helper
1.238
316494AC1-189 GEN
Solar/Wind Helper
1.405
3147983MERCK5
Solar/Wind Helper
0.092
3146233WITAKRS
Solar/Wind Helper
0.913
961671AG1-007 GEN
Solar/Wind Helper
0.165
3146083TARBORO
Solar/Wind Helper
0.229
3145543BTLEBRO
Solar/Wind Helper
0.229
3145543BTLEBRO
Solar/Wind Helper
0.183
316359AB2-059 GEN
Solar/Wind Helper
1.743
316049AB1-081 GEN
Solar/Wind Helper
1.394
316003AC1-222 GEN
Solar/Wind Helper
0.982
316097T157 G90
Solar/Wind Helper
1.031
200201DELTA2 CT2
50/50
6.579
200034PCHBTM 2
50/50
38.283
200035PCHBTM 3
50/50
38.641
200205Y1-065-CTG2
50/50
7.429
233987AB2-037 GEN
Solar/Wind Harmer
0.02
971149AH1-027 GEN
Solar/Wind Harmer
5.838
233939AC1-091 C
Solar/Wind Harmer
0.003
233970AC1-092 C
Solar/Wind Harmer
0.003
970545AG2-347 GEN
Solar/Wind Harmer
47.124
232918OH NUG7
Adder
16.376
233901CHERRYDALE C
Solar/Wind Harmer
0.002
232408W1-005 C
Solar/Wind Harmer
1.209
232410W1-006 C
Solar/Wind Harmer
1.209
972069AH1-584 GEN
Solar/Wind Harmer
11.662
972071AH1-585 GEN
Solar/Wind Harmer
11.662
971747AH1-380 GEN
Solar/Wind Harmer
4.665
232905CHERITON_25
Adder
4.579
232926CRISFLD1
Adder
3.663
231940T-011
Adder
1.392
232899W1-062
Adder
17.93
233946AB2-136 GEN
Solar/Wind Harmer
0.007
234036AF2-325 C
Solar/Wind Harmer
0.001
234041AC1-190 GEN
Solar/Wind Harmer
13.578
233984AB2-036 GEN
Solar/Wind Harmer
13.43
232424Y1-079 C
Solar/Wind Harmer
0.001
234014AF1-036_GEN
Solar/Wind Harmer
4.275
231131BLOOM ENRGY
Adder
8
233944AB2-135 GEN
Solar/Wind Harmer
0.009
233933AB2-153 GEN
Solar/Wind Harmer
0.002
232416X2-083
Adder
0.81
228251CARLLS#4
Adder
0.932
230422AE1-104_GEN1
Solar/Wind Harmer
19.855
230425AE1-104_GEN2
Solar/Wind Harmer
19.855
228307PCLP GT
Adder
17.621
230407AD2-065 C
Solar/Wind Harmer
0
228304LOGAN
Adder
35.125
972233AH1-701 GEN
Adder
6.066
213589EDDYSTN4
Adder
114.034
213587EDDYSTN3
Adder
114.001
219921AF1-264
Solar/Wind Harmer
0
219615MILLCREEK C
Solar/Wind Harmer
0
213535CROYDN11
Adder
13.821
213815MOSER1-3
Adder
4.776
213815MOSER1-3
Adder
4.776
20716428NHV_W2-082
Solar/Wind Harmer
0.001
207500AE2-000G1
Solar/Wind Harmer
16.536
207497AE2-000G2
Solar/Wind Harmer
16.536
207507AE2-000G3
Solar/Wind Harmer
16.536
20636128O CRK C2
Adder
8.427
20714928UPF_X1-085
Solar/Wind Harmer
0
219114HARTZY_C
Solar/Wind Harmer
0
20628028LAKEHURS
Adder
1.224
20720628TIN_W1-124
Solar/Wind Harmer
0.001
20716928W4-060COL
Solar/Wind Harmer
0.001
218440SUMMTASSOC C
Solar/Wind Harmer
0
218418LINDEN_G5
Adder
20.073
218419LINDEN_G6
Adder
20.073
972260AH1-715 GEN1
Adder
16.074
20673828FLE_V3-070
Solar/Wind Harmer
0
219036LINDEN_G7
Adder
19.347
219035LINDEN_G8
Adder
19.071
972261AH1-715 GEN2
Adder
18.52
207442AE1-156 GEN
Solar/Wind Harmer
0.07
20676128MHD_W3-029
Solar/Wind Harmer
0
972237AH1-703 GEN
Adder
11.481
217086KRNY_131
Adder
10.563
217083KRNY_132
Adder
10.474
20671828STAW2-080
Solar/Wind Harmer
0
20674528F3S_W2-016
Solar/Wind Harmer
0
20676228FRD_X1-012
Solar/Wind Harmer
0.001
20674928WA_W3-044
Solar/Wind Harmer
0.001
20465127PORT CT
Adder
3.972
20674128FR_U2-059
Solar/Wind Harmer
0
966111AG1-480 GEN
Solar/Wind Harmer
3.341
211065PSPA IPP
Solar/Wind Harmer
0.001
211065PSPA IPP
Solar/Wind Harmer
0.001
209029WAYMART-WD
Solar/Wind Harmer
0.001
209009PEIP 2
Adder
6.599
209010PEIP 1
Adder
2.99
209010PEIP 1
Adder
0.438
208972BECR K09
Solar/Wind Harmer
0
961541AF2-445A GEN
Solar/Wind Harmer
1.709
209054AE2-059 GEN
Solar/Wind Harmer
0.001
209059AE2-084 GEN
Solar/Wind Harmer
1.106
970761AG2-481 GEN
Solar/Wind Harmer
0.54
209130AF1-271A GEN
Solar/Wind Harmer
1.303
226929AD2-058 GEN
Solar/Wind Helper
0.12
316447AC1-158 HLD
Solar/Wind Helper
3.044
315651AD1-115 GEN
Solar/Wind Helper
0.833
316468AD1-105 GEN
Solar/Wind Helper
1.225
316077AC2-138 C
Solar/Wind Helper
0.23
966001AG1-469 GEN
Solar/Wind Helper
0.262
966871AG1-558 GEN
Solar/Wind Helper
0.329
316487AF1-042 GEN
Solar/Wind Helper
0.246
316075AC2-137 C
Solar/Wind Helper
0.369
3142946ENON
Solar/Wind Helper
0.024
3143526WINTERP
Solar/Wind Helper
1.258
316240AF1-291 C
Solar/Wind Helper
0.324
316033AB2-134 GEN
Solar/Wind Helper
0.827
315697AD1-025 GEN
Solar/Wind Helper
2.749
316236AE1-162_GEN
Solar/Wind Helper
0.322
238175AF1-290_GEN
Solar/Wind Helper
0.126
316036AC1-147 C
Solar/Wind Helper
0.364
3142956BIRDNECK
Solar/Wind Helper
0.161
316316AC1-027 C
Solar/Wind Helper
0.377
316185AD1-033 GEN
Solar/Wind Helper
1.124
3145506HICKORY
Solar/Wind Helper
0.956
3145506HICKORY
Solar/Wind Helper
0.574
3145506HICKORY
Solar/Wind Helper
0.143
238169AE2-226 GEN1
Solar/Wind Helper
0.582
238170AE2-226 GEN2
Solar/Wind Helper
0.582
316339AD2-160 GEN
Solar/Wind Helper
0.909
316018AA1-139 ULT2
Solar/Wind Helper
1.027
316017AA1-139 ULT1
Solar/Wind Helper
1.091
3137176SLIGO L2192
Solar/Wind Helper
0.95
3130086AYDLETT
Solar/Wind Helper
0.955
3146386ELIZ CT
Solar/Wind Helper
0.238
316431W1029_GEN1
Solar/Wind Helper
0.961
316433W1029_GEN2
Solar/Wind Helper
0.961
3146516WINFALL
Solar/Wind Helper
0.238
3146516WINFALL
Solar/Wind Helper
0.238
3146516WINFALL
Solar/Wind Helper
0.238
3146626S HERTFORD
Solar/Wind Helper
0.237
3146626S HERTFORD
Solar/Wind Helper
0.237
3144356SAPONY
Solar/Wind Helper
0.426
315742AE1-103 GEN
Solar/Wind Helper
0.382
3145893MURPHYS
Solar/Wind Helper
0.336
3145893MURPHYS
Solar/Wind Helper
0.422
3146173TUNIS
Solar/Wind Helper
0.234
3146173TUNIS
Solar/Wind Helper
0.234
3146776BUCKING
Solar/Wind Helper
0.936
3146776BUCKING
Solar/Wind Helper
0.076
316181AB2-040 GEN
Solar/Wind Helper
1.673
3142666NORTHAMPTON
Solar/Wind Helper
0.233
3142666NORTHAMPTON
Solar/Wind Helper
0.233
3142666NORTHAMPTON
Solar/Wind Helper
0.233
3142666NORTHAMPTON
Solar/Wind Helper
0.14
316426AA2-053 GEN
Solar/Wind Helper
1.328
3145593CAROLNA
Solar/Wind Helper
0.233
3145593CAROLNA
Solar/Wind Helper
0.233
3147133PAMPLIN
Solar/Wind Helper
0.232
3147133PAMPLIN
Solar/Wind Helper
0.186
3145796HORNRTN
Solar/Wind Helper
0.697
315821AE2-092 GEN
Solar/Wind Helper
2.149
316034AC1-036 C
Solar/Wind Helper
0.243
23777901MDS_W4-102
Solar/Wind Helper
0.145
237034AC2-136 C
Solar/Wind Helper
0.191
3145933PARMELE
Solar/Wind Helper
0.462
3145933PARMELE
Solar/Wind Helper
0.231
316274AC1-208 GEN
Solar/Wind Helper
1.409
3132123MT JACKSON
Solar/Wind Helper
0.722
235020AA1-095 C
Solar/Wind Helper
0.043
23777801MSM_W1-116
Solar/Wind Helper
0.099
3146843MT LREL
Solar/Wind Helper
0.229
3146843MT LREL
Solar/Wind Helper
0.229
237025AB1-124 C
Solar/Wind Helper
0.141
237006AB1-125 GEN
Solar/Wind Helper
0.106
316222AC1-221 GEN
Solar/Wind Helper
1.28
200202DELTA2 ST
50/50
11.164
200195DELTA ST
50/50
5.681
200052ROCKSP 1
50/50
4.692
200053ROCKSP 2
50/50
4.592
233973AC2-185 C
Solar/Wind Harmer
0.003
234033AF1-007_GEN
Solar/Wind Harmer
-0.002
232904IR4
Adder
150.928
232920IR10
Adder
5.899
232432Z2-076 GEN
Solar/Wind Harmer
0.025
232912OH NUG1
Adder
16.486
232913OH NUG2
Adder
16.266
233923SMA
Solar/Wind Harmer
0.009
233990AG1-397 GEN
Solar/Wind Harmer
-0.297
233955AB2-172 GEN
Solar/Wind Harmer
0.006
232813VAUGHN
Adder
1.092
233968AD2-076_GEN
Solar/Wind Harmer
4.275
970597AG2-380 GEN
Solar/Wind Harmer
7.657
231906DC3 NUG
Adder
25.708
231902DC CT7
Adder
20.552
231907DC10
Adder
6.418
232436AB1-176 C
Solar/Wind Harmer
0
971983AH1-536 GEN
Solar/Wind Harmer
3.238
233935AB2-179 C
Solar/Wind Harmer
2.459
231919CHRIST1
Adder
7.728
231920CHRIST2
Adder
7.556
970453AG2-297 GEN
Solar/Wind Harmer
3.805
228260V4-054C
Solar/Wind Harmer
0
228309CCLP NUG
Adder
38.086
228309CCLP NUG
Adder
36.229
972141AH1-641 GEN
Solar/Wind Harmer
4.921
964001AG1-254 GEN
Solar/Wind Harmer
0.57
971011AG2-627 GEN
Solar/Wind Harmer
7.817
971535AH1-265 GEN
Solar/Wind Harmer
4.015
227927V4-067C
Solar/Wind Harmer
0
228754AB1-001 C
Solar/Wind Harmer
0
219272CLEANLIGHT C
Solar/Wind Harmer
0
213942SCHUYLKILL
Adder
4.973
213942SCHUYLKILL
Adder
3.803
213957STHWK3-4
Adder
3.798
213957STHWK3-4
Adder
3.798
219688LUMSOLAR_S C
Solar/Wind Harmer
0
219914AD2-027 C
Solar/Wind Harmer
0.001
213561DLWR9-10
Adder
4.887
213561DLWR9-10
Adder
3.737
219607WPEMNERT C
Solar/Wind Harmer
0.001
219224BRL12CT4
Adder
12.077
214067T20SOLAR
Solar/Wind Harmer
0
213611FALLS1-3
Adder
4.678
213611FALLS1-3
Adder
4.678
20717128DIX_Z2-102
Solar/Wind Harmer
0.001
20715728PEM_W1-119
Solar/Wind Harmer
0.001
20715828PEM_W1-120
Solar/Wind Harmer
0.001
970025AG2-016 GEN
Solar/Wind Harmer
2.38
971189AH1-054 GEN
Solar/Wind Harmer
0.99
207459AE1-142 C O1
Solar/Wind Harmer
0.002
20714328BYD_X4-031
Solar/Wind Harmer
0.19
20714428HOW_X1-037
Solar/Wind Harmer
0.001
971521AH1-258 GEN
Solar/Wind Harmer
2.157
20720428HOL_W1-112
Solar/Wind Harmer
0
20635928PARLN3&4
Adder
8.908
218455CINNBAY_CGEN
Adder
2.181
218526CNTRALGAS2 C
Solar/Wind Harmer
0.91
218524CNTRALGAS1 C
Solar/Wind Harmer
0.906
218404KENILWRTH C
Adder
1.489
217167KRNY_14
Adder
10.541
217086KRNY_131
Adder
10.451
217147KRNY_1212
Adder
10.026
217147KRNY_1212
Adder
9.847
217146KRNY_1234
Adder
9.825
217146KRNY_1234
Adder
9.758
20676328BVR_Y1-020
Solar/Wind Harmer
0
207511W3-106 GEN
Solar/Wind Harmer
0.346
207530AG1-191 GEN
Solar/Wind Harmer
0.001
20674828DL_W4-046
Solar/Wind Harmer
0
971009AG2-626 GEN
Solar/Wind Harmer
1.078
207408W3-077 C
Solar/Wind Harmer
0
20675728RH_W2-091
Solar/Wind Harmer
0.001
966421AG1-511 GEN
Solar/Wind Harmer
6.043
20675928HOL_W4-097
Solar/Wind Harmer
0
207484AF2-139 C O1
Solar/Wind Harmer
0
20675128HRM_W1-127
Solar/Wind Harmer
0
20462827N BANGR8
Adder
0.708
209116AE2-175 GEN
Solar/Wind Harmer
0.007
209026WIENIPP4
Adder
4.438
209045AE2-271 GEN
Solar/Wind Harmer
8.4
3141426STAFORD
Solar/Wind Helper
0.056
3138216PACIFIC
Solar/Wind Helper
0.043
316411AF1-147_GEN1
Solar/Wind Helper
0.855
316415AF1-147_GEN2
Solar/Wind Helper
0.855
316164AC1-076 GEN
Solar/Wind Helper
1.184
316223AC1-118
Solar/Wind Helper
0.375
3141813NORNECK
Solar/Wind Helper
0.245
3141783LANCAST
Solar/Wind Helper
0.146
3141783LANCAST
Solar/Wind Helper
0.097
316312AB1-027
Solar/Wind Helper
0.463
3138133OCRAN
Solar/Wind Helper
0.073
3141913WHIT STONE
Solar/Wind Helper
0.243
316059AD1-063 C
Solar/Wind Helper
0.245
315662AE1-191 GEN
Solar/Wind Helper
1.304
315666AE1-190 GEN
Solar/Wind Helper
0.326
957601AF2-054 GEN
Solar/Wind Helper
0.325
3141873WAN 176
Solar/Wind Helper
0.049
3143873LANEXA
Solar/Wind Helper
0.145
316233AE1-074 FULL
Solar/Wind Helper
0.37
957831AF2-077 GEN
Solar/Wind Helper
0.326
316132AB2-190 GEN1
Solar/Wind Helper
1.376
316369SG1_INVT
Solar/Wind Helper
1.157
3143316POE
Solar/Wind Helper
0.949
316349AD2-085 GEN
Solar/Wind Helper
1.092
319010AE1-072 C
Solar/Wind Helper
2.727
316305AF2-043 C
Solar/Wind Helper
0.321
313526AB2-022
Solar/Wind Helper
0.363
3146486SUNBURY
Solar/Wind Helper
0.238
3146486SUNBURY
Solar/Wind Helper
0.238
316321Z2-027
Solar/Wind Helper
0.363
3145176PASQUOTANK
Solar/Wind Helper
0.148
316315AB2-025 C
Solar/Wind Helper
0.362
315611Z1-036_GEN2
Solar/Wind Helper
1.304
3130156CHOWAN
Solar/Wind Helper
0.237
3130156CHOWAN
Solar/Wind Helper
0.237
315816AE2-034 GEN
Solar/Wind Helper
1.077
23546401DTGZ2-030
Solar/Wind Helper
0.074
238152AF2-075_GEN
Solar/Wind Helper
0.578
3130546PLYMOUTH
Solar/Wind Helper
0.235
315732AD1-074 GEN1
Solar/Wind Helper
2.683
315733AD1-074 GEN2
Solar/Wind Helper
2.683
315735AD1-075 GEN1
Solar/Wind Helper
1.341
3146206CASHIE
Solar/Wind Helper
0.234
3145893MURPHYS
Solar/Wind Helper
0.633
3145893MURPHYS
Solar/Wind Helper
0.234
3145513AHOSKIE
Solar/Wind Helper
0.105
961941AG1-037 GEN
Solar/Wind Helper
0.079
3145513AHOSKIE
Solar/Wind Helper
0.234
946281AF1-292 GEN
Solar/Wind Helper
0.235
3146043SEABORD
Solar/Wind Helper
0.234
3145683EARLEYS
Solar/Wind Helper
0.467
3145683EARLEYS
Solar/Wind Helper
0.234
3145683EARLEYS
Solar/Wind Helper
0.234
315607AA1-063A GEN
Solar/Wind Helper
1.332
316087AB2-174 GEN
Solar/Wind Helper
1.632
3138266HYDRAULIC
Solar/Wind Helper
0.01
3138266HYDRAULIC
Solar/Wind Helper
0.007
3137643SOCKMAN
Solar/Wind Helper
0.931
3145796HORNRTN
Solar/Wind Helper
0.743
3145796HORNRTN
Solar/Wind Helper
0.093
3146033SCOT NK
Solar/Wind Helper
0.928
3144303KENBRDG
Solar/Wind Helper
0.185
316239AB2-077_GEN
Solar/Wind Helper
0.31
316238AB2-078_GEN
Solar/Wind Helper
0.31
316005AA1-067
Solar/Wind Helper
0.263
3145746EVERETS
Solar/Wind Helper
0.917
3145746EVERETS
Solar/Wind Helper
0.231
3145746EVERETS
Solar/Wind Helper
0.231
3145746EVERETS
Solar/Wind Helper
0.231
316420AA1-050 GEN
Solar/Wind Helper
1.317
3148133STUARTS
Solar/Wind Helper
0.138
3148013FISHERV
Solar/Wind Helper
0.132
3145573BETHELC
Solar/Wind Helper
0.229
3145573BETHELC
Solar/Wind Helper
0.229
270494AE1-108_GEN
Solar/Wind Helper
3.063
316118AC1-105 GEN
Solar/Wind Helper
0.886
3147173SINAI
Solar/Wind Helper
0.227
3147243WELCO
Solar/Wind Helper
0.142
3148463FAIRFLD
Solar/Wind Helper
0.225
316123AC1-075 GEN
Solar/Wind Helper
1.357
200200DELTA2 CT1
50/50
6.579
200193DELTA CT2
50/50
3.676
200203Y1-065-STG
50/50
12.882
200055ROCKSP 4
50/50
4.639
233971AC1-093 C
Solar/Wind Harmer
0.08
970695AG2-447 GEN
Solar/Wind Harmer
4.667
972133AH1-634 GEN
Solar/Wind Harmer
6.882
232914OH NUG3
Adder
16.486
232916OH NUG5
Adder
16.486
233996TM1833_GEN
Solar/Wind Harmer
0.003
233997TMININ_4.2
Solar/Wind Harmer
0.003
232406W1-004 FULL
Solar/Wind Harmer
1.209
972073AH1-586 GEN
Solar/Wind Harmer
17.493
232921TASLEY2G
Adder
9.635
232907VN8
Adder
56.047
233940AF2-379 C
Solar/Wind Harmer
0
233990AG1-397 GEN
Solar/Wind Harmer
2.541
233900O-025 C
Adder
2.198
234015AF2-250 C
Solar/Wind Harmer
0
233994AC2-023 GEN
Solar/Wind Harmer
0.008
960671AF2-358 GEN
Solar/Wind Harmer
23.299
232417X3-008 C
Solar/Wind Harmer
0.002
233952AC2-187 GEN
Solar/Wind Harmer
0.002
233918AB1-142 GEN
Solar/Wind Harmer
0.47
233982AB2-133 GEN
Solar/Wind Harmer
0.007
972251AH1-710 GEN
Adder
80.295
228202CUMB CT
Adder
24.596
228711V2-041C
Solar/Wind Harmer
0
971553AH1-274 GEN
Solar/Wind Harmer
2.315
230430AE1-229_GEN
Solar/Wind Harmer
0.025
230415AB2-049 C
Solar/Wind Harmer
0
228729W2-030 C
Solar/Wind Harmer
0.001
228304LOGAN
Adder
31.591
213497CHSTR7-9
Adder
3.912
219623KINSLEYBEA C
Solar/Wind Harmer
0
219766PARADISE C
Solar/Wind Harmer
0
213958STHWK5-6
Adder
3.798
219912AD2-042 GEN
Solar/Wind Harmer
0.001
213560DLW11-12
Adder
3.737
219906AC1-017 C
Solar/Wind Harmer
0
219610FLORENCE C
Solar/Wind Harmer
0.001
219348LDSOLAR C
Solar/Wind Harmer
0.001
219221BRL12CT1
Adder
12.077
219223BRL12CT3
Adder
12.077
213815MOSER1-3
Adder
4.776
20716028EGP_W2-019
Solar/Wind Harmer
0
20720828JCB_W4-025
Solar/Wind Harmer
0.001
20715028HAN_X4-015
Solar/Wind Harmer
0
20636028O CRK C1
Adder
9.242
971667AH1-334 GEN
Solar/Wind Harmer
2.291
219727YARDVSOLFA C
Solar/Wind Harmer
0
20714528FRN_Y2-051
Solar/Wind Harmer
0
219276PARKLANDSO C
Solar/Wind Harmer
0.001
20716228APLW2-078
Solar/Wind Harmer
0.001
20720528MAN_W1-024
Solar/Wind Harmer
0
967451AG2-055 C O1
Solar/Wind Harmer
304.124
219612MATRIX C
Solar/Wind Harmer
0
218438BLK ROCK C
Solar/Wind Harmer
0
20635828PARLN1&2
Adder
4.035
20635928PARLN3&4
Adder
4.035
20635028RRCT1&2
Adder
14.097
20635128RRCT3&4
Adder
11.687
219908AB1-139 C
Solar/Wind Harmer
0.001
20673728F2S_V4-070
Solar/Wind Harmer
0
217186ESSEX_G9
Adder
18.134
217194REDH C
Solar/Wind Harmer
0
20676728BRNX1-095
Solar/Wind Harmer
0
207510AF2-138 C
Solar/Wind Harmer
0.001
20674628WNG_W3-110
Solar/Wind Harmer
0
971007AG2-625 GEN
Solar/Wind Harmer
1.689
20466127PORT 5CT
Adder
26.462
20465427SHAW CT
Adder
3.815
20633028GILCT9
Adder
27.831
963071AG1-156 GEN
Solar/Wind Harmer
0.37
970095AG2-074 GEN
Solar/Wind Harmer
4.21
209025WIENIPP3
Adder
4.392
209027LOR2_Q27
Solar/Wind Harmer
0.001
209022WHFR IPP
Adder
2.464
209142AF1-226 GEN
Solar/Wind Harmer
2.057
209093AE2-110 GEN
Solar/Wind Harmer
1.175
209120AE2-241 GEN
Solar/Wind Harmer
1.175
972245AH1-707 GEN
Adder
3.835
223402AF1-300 C
Solar/Wind Helper
0.483
226910AB2-157 C
Solar/Wind Helper
0.018
227287AC2-120 GEN
Solar/Wind Helper
0.425
3141196NOKESVL
Solar/Wind Helper
1.011
316044AC1-158 PL1
Solar/Wind Helper
1.383
316450AC1-158 RIC
Solar/Wind Helper
0.369
966881AG1-559 GEN
Solar/Wind Helper
0.335
316170AC1-121 GEN2
Solar/Wind Helper
0.379
3141906WESTMOR
Solar/Wind Helper
0.099
3132273ORANGE
Solar/Wind Helper
0.049
3147666LOUISA
Solar/Wind Helper
0.565
316404AE1-155 C
Solar/Wind Helper
2.061
316473AC1-191 GEN
Solar/Wind Helper
1.49
316484AD2-074 GEN
Solar/Wind Helper
0.471
316280AD1-041 GEN
Solar/Wind Helper
0.815
316156AD2-030 GEN
Solar/Wind Helper
0.366
3142946ENON
Solar/Wind Helper
0.081
316382AG1-145 C
Solar/Wind Helper
0.324
315839AE2-212 C
Solar/Wind Helper
0.323
3145336SMITFLD
Solar/Wind Helper
0.096
315773AC2-141 GEN
Solar/Wind Helper
5.158
3144536CHRHLND
Solar/Wind Helper
0.036
3144873MCLAUGH
Solar/Wind Helper
0.006
316313AB2-026
Solar/Wind Helper
0.364
316258AE1-075 C
Solar/Wind Helper
0.327
316405AF2-144 C
Solar/Wind Helper
0.273
3146456SLIGO L269
Solar/Wind Helper
0.239
316320Y1-086
Solar/Wind Helper
0.106
316435W1029_GEN3
Solar/Wind Helper
0.961
3146516WINFALL
Solar/Wind Helper
0.238
3146626S HERTFORD
Solar/Wind Helper
0.237
3145273HOLLAND
Solar/Wind Helper
0.178
3146376EDENTON
Solar/Wind Helper
0.237
315614AA2-178 GEN
Solar/Wind Helper
1.436
238147AE2-230_GEN1
Solar/Wind Helper
0.405
238149AF1-291A_GEN
Solar/Wind Helper
0.116
315737AD1-076 GEN
Solar/Wind Helper
2.295
237061AD1-155 GEN
Solar/Wind Helper
0.044
316365GEN2_N
Solar/Wind Helper
0.893
3146206CASHIE
Solar/Wind Helper
0.234
3145893MURPHYS
Solar/Wind Helper
0.084
3145893MURPHYS
Solar/Wind Helper
0.234
3146173TUNIS
Solar/Wind Helper
0.234
3146776BUCKING
Solar/Wind Helper
0.084
3156021HOLLOMANSOL
Solar/Wind Helper
1.779
316463AE2-346 GEN
Solar/Wind Helper
0.214
316140AB2-099
Solar/Wind Helper
0.089
966621AG1-532 GEN
Solar/Wind Helper
0.213
3146926FARMVIL
Solar/Wind Helper
0.14
3146263WOODLND
Solar/Wind Helper
0.233
313506AB2-031 GEN
Solar/Wind Helper
1.059
942461AE2-259 GEN
Solar/Wind Helper
1.571
3142666NORTHAMPTON
Solar/Wind Helper
0.233
3145963POPLR C
Solar/Wind Helper
0.233
316317KELFORD C
Solar/Wind Helper
0.198
3145823KELFORD
Solar/Wind Helper
0.233
3147043LAWRENC
Solar/Wind Helper
0.14
3147133PAMPLIN
Solar/Wind Helper
0.73
316478AD1-087 GEN
Solar/Wind Helper
1.136
316486AD2-202 GEN
Solar/Wind Helper
0.333
3145796HORNRTN
Solar/Wind Helper
0.929
3145796HORNRTN
Solar/Wind Helper
0.232
315785AD2-033 C
Solar/Wind Helper
2.699
316210AC1-098 GEN
Solar/Wind Helper
1.868
3145933PARMELE
Solar/Wind Helper
0.231
316131AB2-060 GEN
Solar/Wind Helper
1.407
3145746EVERETS
Solar/Wind Helper
0.231
3145746EVERETS
Solar/Wind Helper
0.231
315724AD1-057 GEN
Solar/Wind Helper
0.682
316327AA2-057 GEN
Solar/Wind Helper
1.313
3148013FISHERV
Solar/Wind Helper
0.23
3146233WITAKRS
Solar/Wind Helper
0.247
3146233WITAKRS
Solar/Wind Helper
0.156
316499AE2-029_GEN
Solar/Wind Helper
0.773
3146073TAR RVR
Solar/Wind Helper
0.229
3146083TARBORO
Solar/Wind Helper
0.229
3138543CONSLDL
Solar/Wind Helper
0.151
3145543BTLEBRO
Solar/Wind Helper
0.229
3145543BTLEBRO
Solar/Wind Helper
0.229
316248AF1-058 C
Solar/Wind Helper
0.306
237030AB1-096 C
Solar/Wind Helper
0.061
315616AA1-038_C
Solar/Wind Helper
1.022
238221AF1-254 C O1
Solar/Wind Helper
0.222
316095T157 G97
Solar/Wind Helper
1.031
316283AC2-100 C
Solar/Wind Helper
1.196
23583801GRNGAP
Solar/Wind Helper
3.822
HAMLETPJM->LTFIMP_HAMLET
CLTF
5.661
G-007ALTFEXP_G-007A->PJM
CMTX
61.304
CBM NorthLTFEXP_CBM-N->PJM
CBM
75.856
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
4.88
BlueGrassPJM->LTFIMP_BlueG
CLTF
15.2
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
154.687
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.365
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
22.861

Details for PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line l/o PECO_P4_PEACH095_SRT-A/* $ CHESCO $ PECO_P4_PEACH095 $ STBK


Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
Contingency Name:
PECO_P4_PEACH095_SRT-A/* $ CHESCO $ PECO_P4_PEACH095 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:128.84 %
Rating:3620.0 MVA
Rating Type:B
MVA to Mitigate:4663.83
MW Contribution:8.75
Bus #Bus NameTypeMW Contribution
200201DELTA2 CT2
50/50
8.055
200034PCHBTM 2
50/50
46.841
200205Y1-065-CTG2
50/50
8.843
232918OH NUG7
50/50
16.875
232905CHERITON_25
50/50
4.719
232926CRISFLD1
50/50
3.775
231940T-011
50/50
1.434
971149AH1-027 GEN
Solar/Wind Harmer
6.154
233939AC1-091 C
Solar/Wind Harmer
1.596
233970AC1-092 C
Solar/Wind Harmer
1.596
233987AB2-037 GEN
Solar/Wind Harmer
20.676
970545AG2-347 GEN
Solar/Wind Harmer
118.674
972069AH1-584 GEN
Solar/Wind Harmer
16.234
972071AH1-585 GEN
Solar/Wind Harmer
16.234
233901CHERRYDALE C
Solar/Wind Harmer
2.041
232408W1-005 C
Solar/Wind Harmer
1.815
232410W1-006 C
Solar/Wind Harmer
1.815
971747AH1-380 GEN
Solar/Wind Harmer
6.493
232899W1-062
Adder
17.421
233946AB2-136 GEN
Solar/Wind Harmer
7.214
234036AF2-325 C
Solar/Wind Harmer
1.657
234041AC1-190 GEN
Solar/Wind Harmer
16.171
233984AB2-036 GEN
Solar/Wind Harmer
22.17
232424Y1-079 C
Solar/Wind Harmer
1
234014AF1-036_GEN
Solar/Wind Harmer
4.778
233944AB2-135 GEN
Solar/Wind Harmer
9.192
231131BLOOM ENRGY
Adder
7.631
233933AB2-153 GEN
Solar/Wind Harmer
1.969
232416X2-083
Adder
0.748
228251CARLLS#4
Adder
0.75
230422AE1-104_GEN1
Solar/Wind Harmer
40.07
230425AE1-104_GEN2
Solar/Wind Harmer
40.07
230433AD2-135 GEN
Solar/Wind Harmer
0.118
230407AD2-065 C
Solar/Wind Harmer
0.151
228307PCLP GT
Adder
13.618
228304LOGAN
Adder
26.897
972233AH1-701 GEN
Adder
4.608
219921AF1-264
Solar/Wind Harmer
0.146
213589EDDYSTN4
Adder
75.705
213587EDDYSTN3
Adder
75.643
219615MILLCREEK C
Solar/Wind Harmer
0.226
207500AE2-000G1
Solar/Wind Harmer
29.891
207497AE2-000G2
Solar/Wind Harmer
29.891
207507AE2-000G3
Solar/Wind Harmer
29.891
20636128O CRK C2
Adder
6.115
20716428NHV_W2-082
Solar/Wind Harmer
1.677
963401AG1-189 GEN
Solar/Wind Harmer
1.081
963391AG1-188 GEN
Solar/Wind Harmer
1.792
213535CROYDN11
Adder
9.445
20714928UPF_X1-085
Solar/Wind Harmer
0.372
20628028LAKEHURS
Adder
0.868
219114HARTZY_C
Solar/Wind Harmer
0.722
20720628TIN_W1-124
Solar/Wind Harmer
0.848
20641628MLH_W1-032
Solar/Wind Harmer
0.249
219817TRENTONSOL C
Solar/Wind Harmer
0.904
20716928W4-060COL
Solar/Wind Harmer
0.58
924131AB2-057 GEN
Solar/Wind Harmer
0.797
218440SUMMTASSOC C
Solar/Wind Harmer
0.098
218418LINDEN_G5
Adder
12.811
218419LINDEN_G6
Adder
12.811
972260AH1-715 GEN1
Adder
10.259
219036LINDEN_G7
Adder
12.268
219035LINDEN_G8
Adder
12.093
972261AH1-715 GEN2
Adder
11.744
217081WEATEXAS C
Solar/Wind Harmer
0.062
20673828FLE_V3-070
Solar/Wind Harmer
0.327
217202FBANKSOLAR C
Solar/Wind Harmer
0.053
207442AE1-156 GEN
Solar/Wind Harmer
0.528
20676128MHD_W3-029
Solar/Wind Harmer
0.339
217201HACKENSOLA C
Solar/Wind Harmer
0.052
972237AH1-703 GEN
Adder
7.191
217206BARNGR HS C
Solar/Wind Harmer
0.022
217086KRNY_131
Adder
6.614
217083KRNY_132
Adder
6.557
217204WCALDSOLAR C
Solar/Wind Harmer
0.051
20671828STAW2-080
Solar/Wind Harmer
0.072
213815MOSER1-3
Adder
2.312
213815MOSER1-3
Adder
2.312
20674528F3S_W2-016
Solar/Wind Harmer
0.937
20676228FRD_X1-012
Solar/Wind Harmer
0.378
207471AF2-354 C
Solar/Wind Harmer
0.311
20674928WA_W3-044
Solar/Wind Harmer
0.293
964851AG1-348 GEN
Solar/Wind Harmer
1.054
20634528N27_Y2-018
Solar/Wind Harmer
0.161
20465127PORT CT
Adder
2.311
966111AG1-480 GEN
Solar/Wind Harmer
0.05
966111AG1-480 GEN
Solar/Wind Harmer
1.902
20674128FR_U2-059
Solar/Wind Harmer
0.106
211065PSPA IPP
Solar/Wind Harmer
0.234
211065PSPA IPP
Solar/Wind Harmer
0.234
200202DELTA2 ST
50/50
13.669
200195DELTA ST
50/50
6.955
200052ROCKSP 1
50/50
5.585
200053ROCKSP 2
50/50
5.466
232616GEN FOOD
50/50
0.315
232904IR4
50/50
155.596
232920IR10
50/50
6.081
232912OH NUG1
50/50
16.988
232913OH NUG2
50/50
16.762
233973AC2-185 C
Solar/Wind Harmer
6.565
234033AF1-007_GEN
Solar/Wind Harmer
42.408
232432Z2-076 GEN
Solar/Wind Harmer
0.24
233923SMA
Solar/Wind Harmer
8.418
233990AG1-397 GEN
Solar/Wind Harmer
0.1
233955AB2-172 GEN
Solar/Wind Harmer
9.029
232813VAUGHN
Adder
1.056
233968AD2-076_GEN
Solar/Wind Harmer
11.705
970597AG2-380 GEN
Solar/Wind Harmer
7.35
232436AB1-176 C
Solar/Wind Harmer
0.404
231906DC3 NUG
Adder
24.561
231902DC CT7
Adder
19.635
231907DC10
Adder
6.132
971983AH1-536 GEN
Solar/Wind Harmer
13.101
233935AB2-179 C
Solar/Wind Harmer
4.189
231919CHRIST1
Adder
6.863
231920CHRIST2
Adder
6.71
970453AG2-297 GEN
Solar/Wind Harmer
3.407
228260V4-054C
Solar/Wind Harmer
1.222
972141AH1-641 GEN
Solar/Wind Harmer
3.367
228309CCLP NUG
Adder
30.211
228309CCLP NUG
Adder
28.737
227927V4-067C
Solar/Wind Harmer
0.232
228754AB1-001 C
Solar/Wind Harmer
0.162
964001AG1-254 GEN
Solar/Wind Harmer
2.361
971535AH1-265 GEN
Solar/Wind Harmer
4.92
971011AG2-627 GEN
Solar/Wind Harmer
8.753
219137THOSOLAR C
Solar/Wind Harmer
1.259
219272CLEANLIGHT C
Solar/Wind Harmer
0.19
219688LUMSOLAR_S C
Solar/Wind Harmer
0.208
219914AD2-027 C
Solar/Wind Harmer
0.587
20717128DIX_Z2-102
Solar/Wind Harmer
1.243
20715728PEM_W1-119
Solar/Wind Harmer
0.502
20715828PEM_W1-120
Solar/Wind Harmer
0.502
219607WPEMNERT C
Solar/Wind Harmer
0.392
219224BRL12CT4
Adder
8.347
970025AG2-016 GEN
Solar/Wind Harmer
2.65
971189AH1-054 GEN
Solar/Wind Harmer
1.094
207459AE1-142 C O1
Solar/Wind Harmer
0.972
213942SCHUYLKILL
Adder
3.148
213942SCHUYLKILL
Adder
2.408
213957STHWK3-4
Adder
2.407
213957STHWK3-4
Adder
2.407
214067T20SOLAR
Solar/Wind Harmer
0.223
213611FALLS1-3
Adder
3.111
213611FALLS1-3
Adder
3.111
213561DLWR9-10
Adder
3.073
213561DLWR9-10
Adder
2.35
20714328BYD_X4-031
Solar/Wind Harmer
0.243
20714428HOW_X1-037
Solar/Wind Harmer
1.059
971521AH1-258 GEN
Solar/Wind Harmer
2.262
20720428HOL_W1-112
Solar/Wind Harmer
0.287
219620RIDERU C
Solar/Wind Harmer
0.046
20635928PARLN3&4
Adder
5.878
218455CINNBAY_CGEN
Adder
1.409
218526CNTRALGAS2 C
Solar/Wind Harmer
0.283
218524CNTRALGAS1 C
Solar/Wind Harmer
0.282
20675528CPH_W2-050
Solar/Wind Harmer
0.337
218404KENILWRTH C
Adder
0.936
217167KRNY_14
Adder
6.6
217086KRNY_131
Adder
6.543
217147KRNY_1212
Adder
6.277
217147KRNY_1212
Adder
6.165
217146KRNY_1234
Adder
6.151
217146KRNY_1234
Adder
6.109
966261AG1-495 GEN
Solar/Wind Harmer
1.148
20676328BVR_Y1-020
Solar/Wind Harmer
0.213
207511W3-106 GEN
Solar/Wind Harmer
0.42
207530AG1-191 GEN
Solar/Wind Harmer
0.873
20674828DL_W4-046
Solar/Wind Harmer
0.394
971009AG2-626 GEN
Solar/Wind Harmer
0.981
966421AG1-511 GEN
Solar/Wind Harmer
5.098
207408W3-077 C
Solar/Wind Harmer
0.298
20675728RH_W2-091
Solar/Wind Harmer
0.201
20675928HOL_W4-097
Solar/Wind Harmer
0.076
207484AF2-139 C O1
Solar/Wind Harmer
0.292
20675128HRM_W1-127
Solar/Wind Harmer
0.098
20462827N BANGR8
Adder
0.409
209116AE2-175 GEN
Solar/Wind Harmer
2.217
200192DELTA CT1
50/50
4.501
200194DELTA CT3
50/50
4.501
200204Y1-065-CTG1
50/50
8.843
200054ROCKSP 3
50/50
5.641
231912HR6
50/50
2.658
231913HR7
50/50
2.658
233920W3-032A-CTG1
50/50
3.999
233921W3-032A-STG1
50/50
2.402
232901NORTHST
50/50
16.057
232917OH NUG6
50/50
16.913
232915OH NUG4
50/50
16.875
232910NRG_G1
50/50
16.384
233972AC1-094 C
Solar/Wind Harmer
1.205
232434Z2-077 GEN
Solar/Wind Harmer
0.454
232404W1-003 C
Solar/Wind Harmer
1.815
233998TM1NIN_3.36
Solar/Wind Harmer
2.296
972177AH1-672 GEN
Solar/Wind Harmer
24.344
971195AH1-057 GEN
Solar/Wind Harmer
1.983
232428Y3-058 C
Solar/Wind Harmer
1.512
232900DEMECSMY
Adder
16.71
232919VN10
Adder
5.079
965821AG1-450 GEN
Solar/Wind Harmer
9.418
232426Y1-080 FULL
Solar/Wind Harmer
0.346
970277AG2-181 GEN
Solar/Wind Harmer
9.069
233964AF2-378 GEN
Solar/Wind Harmer
0.231
233954AC2-188 GEN
Solar/Wind Harmer
2.032
233950AC2-186 GEN
Solar/Wind Harmer
1.016
234012AE2-112_GEN
Solar/Wind Harmer
4.061
232422X3-066 FULL
Solar/Wind Harmer
0.441
233930AB2-032 GEN
Solar/Wind Harmer
1.46
233915AB1-141 GEN
Solar/Wind Harmer
1.734
231918WEST 1
Adder
5.245
231917EM10
Adder
3.558
228206SHRMN CT
Adder
20.161
228732V1-021 C
Adder
0.229
945431AF1-208 GEN
Solar/Wind Harmer
10.202
970997AG2-616 GEN
Solar/Wind Harmer
11.225
230511AF1-262
Solar/Wind Harmer
0.213
228351V2-046C
Solar/Wind Harmer
2.335
228728W1-130C
Solar/Wind Harmer
0.77
230434AG1-499 GEN
Solar/Wind Harmer
0.657
218660EHAMPSOLAR C
Solar/Wind Harmer
0.182
219686LUMSOLAR_N C
Solar/Wind Harmer
0.21
219287REEVESEAST C
Solar/Wind Harmer
1.397
219258KINSLEYDEP C
Solar/Wind Harmer
0.329
219904AC1-010 C
Solar/Wind Harmer
0.378
219907AC1-030 C
Solar/Wind Harmer
0.134
213497CHSTR7-9
Adder
2.615
213497CHSTR7-9
Adder
2.615
207487AE2-000G4
Solar/Wind Harmer
29.891
20720728JCB_W1-129
Solar/Wind Harmer
0.282
207522AF2-254 C
Solar/Wind Harmer
1.353
219304NAMERICA C
Solar/Wind Harmer
0.29
219222BRL12CT2
Adder
8.347
207445AB1-138_GEN
Solar/Wind Harmer
0.529
20628028LAKEHURS
Adder
1.718
213958STHWK5-6
Adder
2.407
213611FALLS1-3
Adder
3.111
963711AG1-223 GEN
Solar/Wind Harmer
1.311
20714828MDF_W3-079
Solar/Wind Harmer
0.271
213560DLW11-12
Adder
2.35
207454AA2-184 E
Solar/Wind Harmer
0.851
20715228NPK_W1-113
Solar/Wind Harmer
0.362
20742028HF_AC1-207
Solar/Wind Harmer
0.658
219680HOPEWELLV C1
Solar/Wind Harmer
0.062
217197RE CRAN C
Solar/Wind Harmer
0.427
20635828PARLN1&2
Adder
5.878
20635028RRCT1&2
Adder
9.094
20635128RRCT3&4
Adder
8.779
218428ETC SOLAR C
Solar/Wind Harmer
0.027
217213AMBOY SO C
Solar/Wind Harmer
0.096
972275AH1-722 GEN
Adder
23.552
218449LINSOLAR C
Solar/Wind Harmer
0.738
217209CENTRL HS C
Solar/Wind Harmer
0.032
207528AF2-192 GEN
Solar/Wind Harmer
0.393
20673628F1S_V4-069
Solar/Wind Harmer
0.127
20675428EAM_W2-061
Solar/Wind Harmer
0.134
20676428JCR_X2-075
Solar/Wind Harmer
0.241
217121ECCF
Adder
0.308
217083KRNY_132
Adder
6.6
217208PARK ELE C
Solar/Wind Harmer
0.018
214194N WALES4
Adder
0.562
207439AE1-081 C O1
Solar/Wind Harmer
0.039
20675828AU_W4-064
Solar/Wind Harmer
0.11
20674328GAR_V4-001
Solar/Wind Harmer
0.069
971519AH1-257 GEN
Solar/Wind Harmer
1.503
207518AF1-320_GEN
Solar/Wind Harmer
2.139
20465127PORT CT
Adder
1.742
207437AD2-070 GEN
Solar/Wind Harmer
0.174
20671928W4-073
Solar/Wind Harmer
0.248
966181AG1-487 GEN
Solar/Wind Harmer
2.129
208909MACR G3
Adder
88.543
223401AF1-299 GEN
Solar/Wind Helper
0.367
200200DELTA2 CT1
50/50
8.055
200193DELTA CT2
50/50
4.501
200203Y1-065-STG
50/50
15.334
200055ROCKSP 4
50/50
5.522
231914HR8
50/50
4.04
231911HR5
50/50
2.658
232914OH NUG3
50/50
16.988
232916OH NUG5
50/50
16.988
232921TASLEY2G
50/50
9.929
234034AF2-060
50/50
3.398
233900O-025 C
50/50
2.264
232911NRG_G2
50/50
0.896
233971AC1-093 C
Solar/Wind Harmer
1.425
970695AG2-447 GEN
Solar/Wind Harmer
6.509
972133AH1-634 GEN
Solar/Wind Harmer
17.981
972073AH1-586 GEN
Solar/Wind Harmer
16.989
232406W1-004 FULL
Solar/Wind Harmer
1.815
233996TM1833_GEN
Solar/Wind Harmer
2.296
233997TMININ_4.2
Solar/Wind Harmer
2.296
233940AF2-379 C
Solar/Wind Harmer
0.338
233990AG1-397 GEN
Solar/Wind Harmer
2.079
234015AF2-250 C
Solar/Wind Harmer
0.218
232907VN8
Adder
54.407
233994AC2-023 GEN
Solar/Wind Harmer
4.869
960671AF2-358 GEN
Solar/Wind Harmer
32.396
232417X3-008 C
Solar/Wind Harmer
3.612
233952AC2-187 GEN
Solar/Wind Harmer
2.032
233918AB1-142 GEN
Solar/Wind Harmer
1.734
233982AB2-133 GEN
Solar/Wind Harmer
8.512
972251AH1-710 GEN
Adder
75.72
228202CUMB CT
Adder
20.221
228711V2-041C
Solar/Wind Harmer
0.733
971553AH1-274 GEN
Solar/Wind Harmer
2.917
228729W2-030 C
Solar/Wind Harmer
0.676
230430AE1-229_GEN
Solar/Wind Harmer
10.282
230415AB2-049 C
Solar/Wind Harmer
0.219
228304LOGAN
Adder
24.191
219291REEVESSOUT C
Solar/Wind Harmer
0.063
219623KINSLEYBEA C
Solar/Wind Harmer
0.439
219766PARADISE C
Solar/Wind Harmer
0.314
219912AD2-042 GEN
Solar/Wind Harmer
0.778
219236SOUTHERNHQ C
Solar/Wind Harmer
0.065
213497CHSTR7-9
Adder
2.615
219906AC1-017 C
Solar/Wind Harmer
0.211
20636028O CRK C1
Adder
6.707
20716028EGP_W2-019
Solar/Wind Harmer
0.438
20720828JCB_W4-025
Solar/Wind Harmer
0.428
20715028HAN_X4-015
Solar/Wind Harmer
0.282
219610FLORENCE C
Solar/Wind Harmer
1.296
219348LDSOLAR C
Solar/Wind Harmer
0.56
219221BRL12CT1
Adder
8.347
219223BRL12CT3
Adder
8.347
971667AH1-334 GEN
Solar/Wind Harmer
2.522
959561AF2-247 GEN
Solar/Wind Harmer
0.436
213958STHWK5-6
Adder
2.407
20714528FRN_Y2-051
Solar/Wind Harmer
0.261
213560DLW11-12
Adder
2.35
219727YARDVSOLFA C
Solar/Wind Harmer
0.78
20720528MAN_W1-024
Solar/Wind Harmer
0.215
20716228APLW2-078
Solar/Wind Harmer
0.745
219276PARKLANDSO C
Solar/Wind Harmer
0.386
967451AG2-055 C O1
Solar/Wind Harmer
142.913
219918AC2-009 C
Solar/Wind Harmer
0.05
219612MATRIX C
Solar/Wind Harmer
0.146
218438BLK ROCK C
Solar/Wind Harmer
0.108
20635828PARLN1&2
Adder
2.662
20635928PARLN3&4
Adder
2.662
20635028RRCT1&2
Adder
9.236
20635128RRCT3&4
Adder
7.658
219908AB1-139 C
Solar/Wind Harmer
0.288
219919AE1-041 FULL
Solar/Wind Harmer
0.031
219249CENTRALDIV C
Solar/Wind Harmer
0.029
217211CAMDEN ST C
Solar/Wind Harmer
0.018
20673728F2S_V4-070
Solar/Wind Harmer
0.127
217186ESSEX_G9
Adder
11.355
217169METRODIV C
Solar/Wind Harmer
0.028
217194REDH C
Solar/Wind Harmer
0.349
213815MOSER1-3
Adder
2.312
20676728BRNX1-095
Solar/Wind Harmer
0.119
20674628WNG_W3-110
Solar/Wind Harmer
0.259
207510AF2-138 C
Solar/Wind Harmer
1.139
971007AG2-625 GEN
Solar/Wind Harmer
1.539
20466127PORT 5CT
Adder
15.45
20465427SHAW CT
Adder
2.229
20633028GILCT9
Adder
16.09
966181AG1-487 GEN
Solar/Wind Harmer
0.143
223402AF1-300 C
Solar/Wind Helper
0.367
226910AB2-157 C
Solar/Wind Helper
0.013
227287AC2-120 GEN
Solar/Wind Helper
0.306
HAMLETPJM->LTFIMP_HAMLET
CLTF
4.058
G-007ALTFEXP_G-007A->PJM
CMTX
40.167
CBM NorthLTFEXP_CBM-N->PJM
CBM
44.941
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
3.557
BlueGrassPJM->LTFIMP_BlueG
CLTF
11.08
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
97.34
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.419
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
16.641

Details for PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:128.38 %
Rating:2920.0 MVA
Rating Type:A
MVA to Mitigate:3748.6
MW Contribution:5.64
Bus #Bus NameTypeMW Contribution
200202DELTA2 ST
50/50
7.408
200195DELTA ST
50/50
3.77
200052ROCKSP 1
50/50
3.132
200053ROCKSP 2
50/50
3.066
233973AC2-185 C
Solar/Wind Harmer
0.002
234033AF1-007_GEN
Solar/Wind Harmer
-0.001
232904IR4
Adder
104.145
232920IR10
Adder
4.07
232432Z2-076 GEN
Solar/Wind Harmer
0.017
232912OH NUG1
Adder
11.371
232913OH NUG2
Adder
11.219
233923SMA
Solar/Wind Harmer
0.006
233990AG1-397 GEN
Solar/Wind Harmer
-0.205
233955AB2-172 GEN
Solar/Wind Harmer
0.004
232813VAUGHN
Adder
0.753
231906DC3 NUG
Adder
17.69
231902DC CT7
Adder
14.142
231907DC10
Adder
4.416
233968AD2-076_GEN
Solar/Wind Harmer
2.939
970597AG2-380 GEN
Solar/Wind Harmer
5.264
232436AB1-176 C
Solar/Wind Harmer
0
971983AH1-536 GEN
Solar/Wind Harmer
2.225
233935AB2-179 C
Solar/Wind Harmer
1.683
231919CHRIST1
Adder
5.339
231920CHRIST2
Adder
5.22
970453AG2-297 GEN
Solar/Wind Harmer
2.736
228260V4-054C
Solar/Wind Harmer
0
228309CCLP NUG
Adder
27.422
228309CCLP NUG
Adder
26.085
972141AH1-641 GEN
Solar/Wind Harmer
3.547
964001AG1-254 GEN
Solar/Wind Harmer
0.411
971535AH1-265 GEN
Solar/Wind Harmer
2.903
971011AG2-627 GEN
Solar/Wind Harmer
5.638
227927V4-067C
Solar/Wind Harmer
0
228754AB1-001 C
Solar/Wind Harmer
0
219272CLEANLIGHT C
Solar/Wind Harmer
0
219688LUMSOLAR_S C
Solar/Wind Harmer
0
219914AD2-027 C
Solar/Wind Harmer
0.001
213942SCHUYLKILL
Adder
3.576
213942SCHUYLKILL
Adder
2.734
213957STHWK3-4
Adder
2.734
213957STHWK3-4
Adder
2.734
213561DLWR9-10
Adder
3.553
213561DLWR9-10
Adder
2.717
219607WPEMNERT C
Solar/Wind Harmer
0
219224BRL12CT4
Adder
8.91
214067T20SOLAR
Solar/Wind Harmer
0
213611FALLS1-3
Adder
3.479
213611FALLS1-3
Adder
3.479
20717128DIX_Z2-102
Solar/Wind Harmer
0
20715728PEM_W1-119
Solar/Wind Harmer
0.001
20715828PEM_W1-120
Solar/Wind Harmer
0.001
970025AG2-016 GEN
Solar/Wind Harmer
1.791
971189AH1-054 GEN
Solar/Wind Harmer
0.745
207459AE1-142 C O1
Solar/Wind Harmer
0.001
20714328BYD_X4-031
Solar/Wind Harmer
0.146
20714428HOW_X1-037
Solar/Wind Harmer
0.001
971521AH1-258 GEN
Solar/Wind Harmer
1.661
20720428HOL_W1-112
Solar/Wind Harmer
0
20635928PARLN3&4
Adder
6.938
218455CINNBAY_CGEN
Adder
1.7
218526CNTRALGAS2 C
Solar/Wind Harmer
0.713
218524CNTRALGAS1 C
Solar/Wind Harmer
0.711
218404KENILWRTH C
Adder
1.189
217167KRNY_14
Adder
8.438
217086KRNY_131
Adder
8.366
217147KRNY_1212
Adder
8.026
217147KRNY_1212
Adder
7.883
217146KRNY_1234
Adder
7.865
217146KRNY_1234
Adder
7.811
20676328BVR_Y1-020
Solar/Wind Harmer
0
207511W3-106 GEN
Solar/Wind Harmer
0.286
207530AG1-191 GEN
Solar/Wind Harmer
0.001
200200DELTA2 CT1
50/50
4.366
200193DELTA CT2
50/50
2.439
200203Y1-065-STG
50/50
8.6
200055ROCKSP 4
50/50
3.097
233971AC1-093 C
Solar/Wind Harmer
0.055
970695AG2-447 GEN
Solar/Wind Harmer
3.227
972133AH1-634 GEN
Solar/Wind Harmer
4.749
972073AH1-586 GEN
Solar/Wind Harmer
12.066
232406W1-004 FULL
Solar/Wind Harmer
0.834
232914OH NUG3
Adder
11.371
232916OH NUG5
Adder
11.371
232921TASLEY2G
Adder
6.645
233996TM1833_GEN
Solar/Wind Harmer
0.002
233997TMININ_4.2
Solar/Wind Harmer
0.002
233990AG1-397 GEN
Solar/Wind Harmer
1.753
233940AF2-379 C
Solar/Wind Harmer
0
234015AF2-250 C
Solar/Wind Harmer
0
233900O-025 C
Adder
1.516
232907VN8
Adder
38.637
233994AC2-023 GEN
Solar/Wind Harmer
0.005
960671AF2-358 GEN
Solar/Wind Harmer
16.06
233952AC2-187 GEN
Solar/Wind Harmer
0.002
232417X3-008 C
Solar/Wind Harmer
0.002
972251AH1-710 GEN
Adder
56.349
233918AB1-142 GEN
Solar/Wind Harmer
0.323
233982AB2-133 GEN
Solar/Wind Harmer
0.005
228202CUMB CT
Adder
17.7
228711V2-041C
Solar/Wind Harmer
0
971553AH1-274 GEN
Solar/Wind Harmer
1.667
230430AE1-229_GEN
Solar/Wind Harmer
0.018
230415AB2-049 C
Solar/Wind Harmer
0
228729W2-030 C
Solar/Wind Harmer
0.001
228304LOGAN
Adder
22.803
219623KINSLEYBEA C
Solar/Wind Harmer
0
219766PARADISE C
Solar/Wind Harmer
0
213497CHSTR7-9
Adder
2.778
219912AD2-042 GEN
Solar/Wind Harmer
0.001
213958STHWK5-6
Adder
2.734
219906AC1-017 C
Solar/Wind Harmer
0
213560DLW11-12
Adder
2.717
219610FLORENCE C
Solar/Wind Harmer
0.001
219348LDSOLAR C
Solar/Wind Harmer
0.001
219221BRL12CT1
Adder
8.91
219223BRL12CT3
Adder
8.91
213815MOSER1-3
Adder
3.51
20716028EGP_W2-019
Solar/Wind Harmer
0
20720828JCB_W4-025
Solar/Wind Harmer
0
20715028HAN_X4-015
Solar/Wind Harmer
0
20636028O CRK C1
Adder
6.939
971667AH1-334 GEN
Solar/Wind Harmer
1.73
219727YARDVSOLFA C
Solar/Wind Harmer
0
20714528FRN_Y2-051
Solar/Wind Harmer
0
219276PARKLANDSO C
Solar/Wind Harmer
0
20716228APLW2-078
Solar/Wind Harmer
0
20720528MAN_W1-024
Solar/Wind Harmer
0
967451AG2-055 C O1
Solar/Wind Harmer
235.168
219612MATRIX C
Solar/Wind Harmer
0
218438BLK ROCK C
Solar/Wind Harmer
0
20635828PARLN1&2
Adder
3.142
20635928PARLN3&4
Adder
3.142
20635028RRCT1&2
Adder
11.011
20635128RRCT3&4
Adder
9.128
219908AB1-139 C
Solar/Wind Harmer
0
20673728F2S_V4-070
Solar/Wind Harmer
0
217186ESSEX_G9
Adder
14.514
217194REDH C
Solar/Wind Harmer
0
20676728BRNX1-095
Solar/Wind Harmer
0
20674628WNG_W3-110
Solar/Wind Harmer
0
207510AF2-138 C
Solar/Wind Harmer
0.001
971007AG2-625 GEN
Solar/Wind Harmer
1.423
20466127PORT 5CT
Adder
22.531
20465427SHAW CT
Adder
3.263
20633028GILCT9
Adder
23.745
209025WIENIPP3
Adder
4.065
963071AG1-156 GEN
Solar/Wind Harmer
0.339
970095AG2-074 GEN
Solar/Wind Harmer
3.86
209027LOR2_Q27
Solar/Wind Harmer
0.001
209022WHFR IPP
Adder
2.386
209142AF1-226 GEN
Solar/Wind Harmer
2.019
209093AE2-110 GEN
Solar/Wind Harmer
1.154
209120AE2-241 GEN
Solar/Wind Harmer
1.154
972245AH1-707 GEN
Adder
3.816
223402AF1-300 C
Solar/Wind Helper
0.594
226910AB2-157 C
Solar/Wind Helper
0.017
227287AC2-120 GEN
Solar/Wind Helper
0.412
200201DELTA2 CT2
50/50
4.366
200034PCHBTM 2
50/50
25.408
200035PCHBTM 3
50/50
25.122
200205Y1-065-CTG2
50/50
4.96
971149AH1-027 GEN
Solar/Wind Harmer
4.034
233939AC1-091 C
Solar/Wind Harmer
0.002
233970AC1-092 C
Solar/Wind Harmer
0.002
970545AG2-347 GEN
Solar/Wind Harmer
32.517
232899W1-062
Adder
12.388
233987AB2-037 GEN
Solar/Wind Harmer
0.014
972069AH1-584 GEN
Solar/Wind Harmer
8.044
972071AH1-585 GEN
Solar/Wind Harmer
8.044
233901CHERRYDALE C
Solar/Wind Harmer
0.002
232408W1-005 C
Solar/Wind Harmer
0.834
232410W1-006 C
Solar/Wind Harmer
0.834
232918OH NUG7
Adder
11.295
971747AH1-380 GEN
Solar/Wind Harmer
3.217
232905CHERITON_25
Adder
3.158
232926CRISFLD1
Adder
2.527
231940T-011
Adder
0.96
233946AB2-136 GEN
Solar/Wind Harmer
0.005
234036AF2-325 C
Solar/Wind Harmer
0.001
234041AC1-190 GEN
Solar/Wind Harmer
9.357
233984AB2-036 GEN
Solar/Wind Harmer
9.238
232424Y1-079 C
Solar/Wind Harmer
0.001
231131BLOOM ENRGY
Adder
5.507
234014AF1-036_GEN
Solar/Wind Harmer
2.939
233944AB2-135 GEN
Solar/Wind Harmer
0.006
233933AB2-153 GEN
Solar/Wind Harmer
0.002
232416X2-083
Adder
0.557
228251CARLLS#4
Adder
0.671
230422AE1-104_GEN1
Solar/Wind Harmer
14.353
230425AE1-104_GEN2
Solar/Wind Harmer
14.353
230407AD2-065 C
Solar/Wind Harmer
0
228307PCLP GT
Adder
12.711
228304LOGAN
Adder
25.354
972233AH1-701 GEN
Adder
4.382
219921AF1-264
Solar/Wind Harmer
0
213589EDDYSTN4
Adder
81.023
213587EDDYSTN3
Adder
81.01
219615MILLCREEK C
Solar/Wind Harmer
0
213535CROYDN11
Adder
10.197
213815MOSER1-3
Adder
3.51
213815MOSER1-3
Adder
3.51
20716428NHV_W2-082
Solar/Wind Harmer
0
207500AE2-000G1
Solar/Wind Harmer
12.415
207497AE2-000G2
Solar/Wind Harmer
12.415
207507AE2-000G3
Solar/Wind Harmer
12.415
20636128O CRK C2
Adder
6.327
20714928UPF_X1-085
Solar/Wind Harmer
0
20628028LAKEHURS
Adder
0.925
219114HARTZY_C
Solar/Wind Harmer
0
20720628TIN_W1-124
Solar/Wind Harmer
0.001
20716928W4-060COL
Solar/Wind Harmer
0
218440SUMMTASSOC C
Solar/Wind Harmer
0
218418LINDEN_G5
Adder
15.845
218419LINDEN_G6
Adder
15.845
972260AH1-715 GEN1
Adder
12.688
20673828FLE_V3-070
Solar/Wind Harmer
0
219036LINDEN_G7
Adder
15.345
219035LINDEN_G8
Adder
15.126
972261AH1-715 GEN2
Adder
14.689
207442AE1-156 GEN
Solar/Wind Harmer
0.055
20676128MHD_W3-029
Solar/Wind Harmer
0
972237AH1-703 GEN
Adder
9.187
217086KRNY_131
Adder
8.456
217083KRNY_132
Adder
8.384
20671828STAW2-080
Solar/Wind Harmer
0
20674528F3S_W2-016
Solar/Wind Harmer
0
20676228FRD_X1-012
Solar/Wind Harmer
0.001
20674928WA_W3-044
Solar/Wind Harmer
0.001
20465127PORT CT
Adder
3.383
20674128FR_U2-059
Solar/Wind Harmer
0
966111AG1-480 GEN
Solar/Wind Harmer
2.857
211065PSPA IPP
Solar/Wind Harmer
0
211065PSPA IPP
Solar/Wind Harmer
0
209029WAYMART-WD
Solar/Wind Harmer
0.001
209009PEIP 2
Adder
5.98
209010PEIP 1
Adder
2.709
200192DELTA CT1
50/50
2.439
200194DELTA CT3
50/50
2.439
200204Y1-065-CTG1
50/50
4.96
200054ROCKSP 3
50/50
3.164
232901NORTHST
Adder
10.747
233972AC1-094 C
Solar/Wind Harmer
0.406
232900DEMECSMY
Adder
11.882
232434Z2-077 GEN
Solar/Wind Harmer
0.054
972177AH1-672 GEN
Solar/Wind Harmer
13.114
232404W1-003 C
Solar/Wind Harmer
0.834
232917OH NUG6
Adder
11.32
232915OH NUG4
Adder
11.295
233998TM1NIN_3.36
Solar/Wind Harmer
0.002
971195AH1-057 GEN
Solar/Wind Harmer
0.804
232428Y3-058 C
Solar/Wind Harmer
0.002
232919VN10
Adder
3.609
965821AG1-450 GEN
Solar/Wind Harmer
6.692
232426Y1-080 FULL
Solar/Wind Harmer
0
970277AG2-181 GEN
Solar/Wind Harmer
0.749
233964AF2-378 GEN
Solar/Wind Harmer
0
233954AC2-188 GEN
Solar/Wind Harmer
0.002
233950AC2-186 GEN
Solar/Wind Harmer
0.001
232910NRG_G1
Adder
11.02
234012AE2-112_GEN
Solar/Wind Harmer
2.939
232422X3-066 FULL
Solar/Wind Harmer
0.106
233930AB2-032 GEN
Solar/Wind Harmer
1.205
233915AB1-141 GEN
Solar/Wind Harmer
0.323
231918WEST 1
Adder
4.059
231917EM10
Adder
2.823
228206SHRMN CT
Adder
17.734
228732V1-021 C
Adder
0.202
945431AF1-208 GEN
Solar/Wind Harmer
6.401
970997AG2-616 GEN
Solar/Wind Harmer
7.649
228351V2-046C
Solar/Wind Harmer
0.001
230511AF1-262
Solar/Wind Harmer
0
228728W1-130C
Solar/Wind Harmer
0
230434AG1-499 GEN
Solar/Wind Harmer
0.001
219258KINSLEYDEP C
Solar/Wind Harmer
0
218660EHAMPSOLAR C
Solar/Wind Harmer
0
219686LUMSOLAR_N C
Solar/Wind Harmer
0
219287REEVESEAST C
Solar/Wind Harmer
0
219904AC1-010 C
Solar/Wind Harmer
0
213497CHSTR7-9
Adder
2.778
213497CHSTR7-9
Adder
2.778
219907AC1-030 C
Solar/Wind Harmer
0
213958STHWK5-6
Adder
2.734
213560DLW11-12
Adder
2.717
219304NAMERICA C
Solar/Wind Harmer
0.091
219222BRL12CT2
Adder
8.91
20720728JCB_W1-129
Solar/Wind Harmer
0
213611FALLS1-3
Adder
3.479
207522AF2-254 C
Solar/Wind Harmer
0.912
207487AE2-000G4
Solar/Wind Harmer
12.415
214194N WALES4
Adder
0.831
207445AB1-138_GEN
Solar/Wind Harmer
0.001
20628028LAKEHURS
Adder
1.83
20714828MDF_W3-079
Solar/Wind Harmer
0.095
207454AA2-184 E
Solar/Wind Harmer
0.001
20715228NPK_W1-113
Solar/Wind Harmer
0
20742028HF_AC1-207
Solar/Wind Harmer
0.001
217197RE CRAN C
Solar/Wind Harmer
0
20635828PARLN1&2
Adder
6.938
20635028RRCT1&2
Adder
10.841
20635128RRCT3&4
Adder
10.465
217213AMBOY SO C
Solar/Wind Harmer
0
972275AH1-722 GEN
Adder
29.13
218449LINSOLAR C
Solar/Wind Harmer
0
207528AF2-192 GEN
Solar/Wind Harmer
0.001
20673628F1S_V4-069
Solar/Wind Harmer
0
20675428EAM_W2-061
Solar/Wind Harmer
0
20676428JCR_X2-075
Solar/Wind Harmer
0
217121ECCF
Adder
0.394
217083KRNY_132
Adder
8.438
20675828AU_W4-064
Solar/Wind Harmer
0
20674328GAR_V4-001
Solar/Wind Harmer
0
971519AH1-257 GEN
Solar/Wind Harmer
1.394
20465127PORT CT
Adder
2.549
207437AD2-070 GEN
Solar/Wind Harmer
0.056
20671928W4-073
Solar/Wind Harmer
0
966181AG1-487 GEN
Solar/Wind Harmer
3.204
208909MACR G3
Adder
133.569
209023WIENIPP1
Adder
8.312
209025WIENIPP3
Adder
4.149
209010PEIP 1
Adder
0.493
212266LOR1
Solar/Wind Harmer
0.354
212174INGE
Adder
0.792
212507AE2-042_GEN
Solar/Wind Harmer
0.425
209071AE2-133 GEN
Solar/Wind Harmer
0.001
970665AG2-430 GEN
Solar/Wind Harmer
4.932
209018SUNBIPCT
Adder
5.067
970757AG2-479 GEN
Solar/Wind Harmer
0.536
972241AH1-705 GEN
Adder
3.724
205941AD2-115 GEN
Solar/Wind Harmer
0.073
20467927PC_Q59Y356
Adder
0.474
20465527S.RDG CT
Adder
1.516
223401AF1-299 GEN
Solar/Wind Helper
0.594
20674828DL_W4-046
Solar/Wind Harmer
0
971009AG2-626 GEN
Solar/Wind Harmer
0.908
207408W3-077 C
Solar/Wind Harmer
0
20675728RH_W2-091
Solar/Wind Harmer
0.001
966421AG1-511 GEN
Solar/Wind Harmer
5.123
20675928HOL_W4-097
Solar/Wind Harmer
0
207484AF2-139 C O1
Solar/Wind Harmer
0
20462827N BANGR8
Adder
0.606
20675128HRM_W1-127
Solar/Wind Harmer
0
209116AE2-175 GEN
Solar/Wind Harmer
0.006
209026WIENIPP4
Adder
4.107
209045AE2-271 GEN
Solar/Wind Harmer
8.301
20486527WR_V4-052
Adder
0.596
209010PEIP 1
Adder
0.397
208972BECR K09
Solar/Wind Harmer
0
961541AF2-445A GEN
Solar/Wind Harmer
1.654
209054AE2-059 GEN
Solar/Wind Harmer
0.001
209059AE2-084 GEN
Solar/Wind Harmer
1.116
970761AG2-481 GEN
Solar/Wind Harmer
0.545
209130AF1-271A GEN
Solar/Wind Harmer
1.334
20465527S.RDG CT
Adder
1.467
226929AD2-058 GEN
Solar/Wind Helper
0.113
HAMLETPJM->LTFIMP_HAMLET
CLTF
4.146
G-007ALTFEXP_G-007A->PJM
CMTX
47.883
CBM NorthLTFEXP_CBM-N->PJM
CBM
63.205
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
3.478
BlueGrassPJM->LTFIMP_BlueG
CLTF
10.836
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
123.421
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.452
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
16.337

Details for PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line l/o PECO_P2-2_NOTT230B_SRT-A/* $ CHESCO $ PECO_P2-2_NOTT230B $ B


Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
Contingency Name:
PECO_P2-2_NOTT230B_SRT-A/* $ CHESCO $ PECO_P2-2_NOTT230B $ B
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:121.38 %
Rating:3620.0 MVA
Rating Type:B
MVA to Mitigate:4394.11
MW Contribution:8.85
Bus #Bus NameTypeMW Contribution
200200DELTA2 CT1
50/50
4.431
200193DELTA CT2
50/50
2.476
200203Y1-065-STG
50/50
8.807
200055ROCKSP 4
50/50
3.172
232907VN8
Adder
42.278
960671AF2-358 GEN
Solar/Wind Harmer
25.208
232417X3-008 C
Solar/Wind Harmer
2.816
233994AC2-023 GEN
Solar/Wind Harmer
3.783
233996TM1833_GEN
Solar/Wind Harmer
1.782
233997TMININ_4.2
Solar/Wind Harmer
1.782
233940AF2-379 C
Solar/Wind Harmer
0.263
232406W1-004 FULL
Solar/Wind Harmer
1.409
232914OH NUG3
Adder
12.427
232916OH NUG5
Adder
12.427
232921TASLEY2G
Adder
7.263
233900O-025 C
Adder
1.657
234015AF2-250 C
Solar/Wind Harmer
0.169
972073AH1-586 GEN
Solar/Wind Harmer
13.185
233990AG1-397 GEN
Solar/Wind Harmer
1.614
972133AH1-634 GEN
Solar/Wind Harmer
13.941
233952AC2-187 GEN
Solar/Wind Harmer
1.582
233971AC1-093 C
Solar/Wind Harmer
1.1
970695AG2-447 GEN
Solar/Wind Harmer
5.024
233918AB1-142 GEN
Solar/Wind Harmer
1.391
233982AB2-133 GEN
Solar/Wind Harmer
6.833
972251AH1-710 GEN
Adder
60.545
228202CUMB CT
Adder
19.243
228711V2-041C
Solar/Wind Harmer
0.699
213497CHSTR7-9
Adder
3.178
971553AH1-274 GEN
Solar/Wind Harmer
2.814
230430AE1-229_GEN
Solar/Wind Harmer
10.184
230415AB2-049 C
Solar/Wind Harmer
0.218
228304LOGAN
Adder
25.036
228729W2-030 C
Solar/Wind Harmer
0.662
213958STHWK5-6
Adder
3.094
219623KINSLEYBEA C
Solar/Wind Harmer
0.483
219766PARADISE C
Solar/Wind Harmer
0.354
219291REEVESSOUT C
Solar/Wind Harmer
0.067
219912AD2-042 GEN
Solar/Wind Harmer
0.892
213560DLW11-12
Adder
3.039
219236SOUTHERNHQ C
Solar/Wind Harmer
0.075
219906AC1-017 C
Solar/Wind Harmer
0.246
219610FLORENCE C
Solar/Wind Harmer
1.518
219348LDSOLAR C
Solar/Wind Harmer
0.656
219221BRL12CT1
Adder
9.78
219223BRL12CT3
Adder
9.78
213815MOSER1-3
Adder
3.886
959561AF2-247 GEN
Solar/Wind Harmer
0.522
20716028EGP_W2-019
Solar/Wind Harmer
0.497
20720828JCB_W4-025
Solar/Wind Harmer
0.485
20715028HAN_X4-015
Solar/Wind Harmer
0.319
20636028O CRK C1
Adder
7.53
971667AH1-334 GEN
Solar/Wind Harmer
2.904
219727YARDVSOLFA C
Solar/Wind Harmer
0.96
20714528FRN_Y2-051
Solar/Wind Harmer
0.309
219276PARKLANDSO C
Solar/Wind Harmer
0.483
219918AC2-009 C
Solar/Wind Harmer
0.064
20716228APLW2-078
Solar/Wind Harmer
0.913
20720528MAN_W1-024
Solar/Wind Harmer
0.262
967451AG2-055 C O1
Solar/Wind Harmer
177.931
219612MATRIX C
Solar/Wind Harmer
0.188
200202DELTA2 ST
50/50
7.519
200195DELTA ST
50/50
3.826
200052ROCKSP 1
50/50
3.208
200053ROCKSP 2
50/50
3.139
233955AB2-172 GEN
Solar/Wind Harmer
7.039
233923SMA
Solar/Wind Harmer
6.535
232912OH NUG1
Adder
12.427
232913OH NUG2
Adder
12.261
233990AG1-397 GEN
Solar/Wind Harmer
0.078
232432Z2-076 GEN
Solar/Wind Harmer
0.186
232920IR10
Adder
4.444
234033AF1-007_GEN
Solar/Wind Harmer
32.879
232904IR4
Adder
113.686
233968AD2-076_GEN
Solar/Wind Harmer
9.314
970597AG2-380 GEN
Solar/Wind Harmer
5.849
232813VAUGHN
Adder
0.827
232436AB1-176 C
Solar/Wind Harmer
0.322
233973AC2-185 C
Solar/Wind Harmer
5.067
971983AH1-536 GEN
Solar/Wind Harmer
10.501
231906DC3 NUG
Adder
19.615
231902DC CT7
Adder
15.681
231907DC10
Adder
4.897
233935AB2-179 C
Solar/Wind Harmer
3.492
231919CHRIST1
Adder
6.025
231920CHRIST2
Adder
5.891
970453AG2-297 GEN
Solar/Wind Harmer
3.22
228260V4-054C
Solar/Wind Harmer
1.191
228309CCLP NUG
Adder
29.981
228309CCLP NUG
Adder
28.519
972141AH1-641 GEN
Solar/Wind Harmer
3.331
964001AG1-254 GEN
Solar/Wind Harmer
2.353
971011AG2-627 GEN
Solar/Wind Harmer
8.848
971535AH1-265 GEN
Solar/Wind Harmer
4.899
227927V4-067C
Solar/Wind Harmer
0.227
228754AB1-001 C
Solar/Wind Harmer
0.16
213942SCHUYLKILL
Adder
4.052
213942SCHUYLKILL
Adder
3.098
219137THOSOLAR C
Solar/Wind Harmer
1.374
213957STHWK3-4
Adder
3.094
213957STHWK3-4
Adder
3.094
219272CLEANLIGHT C
Solar/Wind Harmer
0.205
219914AD2-027 C
Solar/Wind Harmer
0.673
213561DLWR9-10
Adder
3.974
213561DLWR9-10
Adder
3.039
219688LUMSOLAR_S C
Solar/Wind Harmer
0.226
219607WPEMNERT C
Solar/Wind Harmer
0.459
219224BRL12CT4
Adder
9.78
214067T20SOLAR
Solar/Wind Harmer
0.273
213611FALLS1-3
Adder
3.817
213611FALLS1-3
Adder
3.817
20717128DIX_Z2-102
Solar/Wind Harmer
1.411
20715728PEM_W1-119
Solar/Wind Harmer
0.571
20715828PEM_W1-120
Solar/Wind Harmer
0.571
970025AG2-016 GEN
Solar/Wind Harmer
3.008
971189AH1-054 GEN
Solar/Wind Harmer
1.252
207459AE1-142 C O1
Solar/Wind Harmer
1.116
219620RIDERU C
Solar/Wind Harmer
0.058
20714328BYD_X4-031
Solar/Wind Harmer
0.293
20714428HOW_X1-037
Solar/Wind Harmer
1.28
971521AH1-258 GEN
Solar/Wind Harmer
2.783
20720428HOL_W1-112
Solar/Wind Harmer
0.355
20635928PARLN3&4
Adder
7.504
218455CINNBAY_CGEN
Adder
1.841
218526CNTRALGAS2 C
Solar/Wind Harmer
0.373
218524CNTRALGAS1 C
Solar/Wind Harmer
0.372
20675528CPH_W2-050
Solar/Wind Harmer
0.467
218404KENILWRTH C
Adder
1.283
217167KRNY_14
Adder
9.105
217086KRNY_131
Adder
9.027
217147KRNY_1212
Adder
8.66
217147KRNY_1212
Adder
8.505
217146KRNY_1234
Adder
8.486
217146KRNY_1234
Adder
8.428
966261AG1-495 GEN
Solar/Wind Harmer
1.706
20676328BVR_Y1-020
Solar/Wind Harmer
0.312
207511W3-106 GEN
Solar/Wind Harmer
0.619
207530AG1-191 GEN
Solar/Wind Harmer
1.291
20674828DL_W4-046
Solar/Wind Harmer
0.598
971009AG2-626 GEN
Solar/Wind Harmer
1.509
207408W3-077 C
Solar/Wind Harmer
0.463
20675728RH_W2-091
Solar/Wind Harmer
0.313
966421AG1-511 GEN
Solar/Wind Harmer
7.885
20675928HOL_W4-097
Solar/Wind Harmer
0.119
207484AF2-139 C O1
Solar/Wind Harmer
0.46
20675128HRM_W1-127
Solar/Wind Harmer
0.154
20462827N BANGR8
Adder
0.65
209116AE2-175 GEN
Solar/Wind Harmer
3.65
961261AF2-417 GEN
Solar/Wind Harmer
0.847
209026WIENIPP4
Adder
4.385
209045AE2-271 GEN
Solar/Wind Harmer
12.651
959431AF2-234 GEN
Solar/Wind Harmer
1.445
964051AG1-259 GEN
Solar/Wind Harmer
0.969
964061AG1-260 GEN
Solar/Wind Harmer
0.969
959421AF2-233 GEN
Solar/Wind Harmer
0.723
20486527WR_V4-052
Adder
0.618
200201DELTA2 CT2
50/50
4.431
200034PCHBTM 2
50/50
25.792
200035PCHBTM 3
50/50
25.526
200205Y1-065-CTG2
50/50
5.079
233987AB2-037 GEN
Solar/Wind Harmer
16.06
233946AB2-136 GEN
Solar/Wind Harmer
5.617
234036AF2-325 C
Solar/Wind Harmer
1.291
234041AC1-190 GEN
Solar/Wind Harmer
12.604
232926CRISFLD1
Adder
2.762
233901CHERRYDALE C
Solar/Wind Harmer
1.584
232408W1-005 C
Solar/Wind Harmer
1.409
232410W1-006 C
Solar/Wind Harmer
1.409
232918OH NUG7
Adder
12.344
232905CHERITON_25
Adder
3.452
971747AH1-380 GEN
Solar/Wind Harmer
5.04
972069AH1-584 GEN
Solar/Wind Harmer
12.599
972071AH1-585 GEN
Solar/Wind Harmer
12.599
231940T-011
Adder
1.049
970545AG2-347 GEN
Solar/Wind Harmer
92.009
233984AB2-036 GEN
Solar/Wind Harmer
17.511
232424Y1-079 C
Solar/Wind Harmer
0.791
234014AF1-036_GEN
Solar/Wind Harmer
3.802
971149AH1-027 GEN
Solar/Wind Harmer
4.751
232899W1-062
Adder
13.494
233939AC1-091 C
Solar/Wind Harmer
1.232
233970AC1-092 C
Solar/Wind Harmer
1.232
233933AB2-153 GEN
Solar/Wind Harmer
1.579
233944AB2-135 GEN
Solar/Wind Harmer
7.347
231131BLOOM ENRGY
Adder
6.103
232416X2-083
Adder
0.626
213589EDDYSTN4
Adder
92.739
213587EDDYSTN3
Adder
92.714
228251CARLLS#4
Adder
0.732
230433AD2-135 GEN
Solar/Wind Harmer
0.117
230422AE1-104_GEN1
Solar/Wind Harmer
38.87
230425AE1-104_GEN2
Solar/Wind Harmer
38.87
228307PCLP GT
Adder
13.94
228304LOGAN
Adder
27.837
230407AD2-065 C
Solar/Wind Harmer
0.151
972233AH1-701 GEN
Adder
4.815
219921AF1-264
Solar/Wind Harmer
0.163
219615MILLCREEK C
Solar/Wind Harmer
0.263
213535CROYDN11
Adder
11.201
213815MOSER1-3
Adder
3.886
213815MOSER1-3
Adder
3.886
20716428NHV_W2-082
Solar/Wind Harmer
1.902
207500AE2-000G1
Solar/Wind Harmer
33.557
207497AE2-000G2
Solar/Wind Harmer
33.557
207507AE2-000G3
Solar/Wind Harmer
33.557
20636128O CRK C2
Adder
6.865
963401AG1-189 GEN
Solar/Wind Harmer
1.222
963391AG1-188 GEN
Solar/Wind Harmer
2.036
20714928UPF_X1-085
Solar/Wind Harmer
0.431
219114HARTZY_C
Solar/Wind Harmer
0.884
20628028LAKEHURS
Adder
1.004
219817TRENTONSOL C
Solar/Wind Harmer
1.146
20641628MLH_W1-032
Solar/Wind Harmer
0.303
20720628TIN_W1-124
Solar/Wind Harmer
1.03
20716928W4-060COL
Solar/Wind Harmer
0.726
924131AB2-057 GEN
Solar/Wind Harmer
1.042
218440SUMMTASSOC C
Solar/Wind Harmer
0.129
218418LINDEN_G5
Adder
17.122
218419LINDEN_G6
Adder
17.122
972260AH1-715 GEN1
Adder
13.711
20673828FLE_V3-070
Solar/Wind Harmer
0.455
219036LINDEN_G7
Adder
16.573
219035LINDEN_G8
Adder
16.337
972261AH1-715 GEN2
Adder
15.865
207442AE1-156 GEN
Solar/Wind Harmer
0.736
20676128MHD_W3-029
Solar/Wind Harmer
0.472
217081WEATEXAS C
Solar/Wind Harmer
0.085
217202FBANKSOLAR C
Solar/Wind Harmer
0.072
217201HACKENSOLA C
Solar/Wind Harmer
0.072
972237AH1-703 GEN
Adder
9.914
217206BARNGR HS C
Solar/Wind Harmer
0.03
217086KRNY_131
Adder
9.124
217083KRNY_132
Adder
9.047
20671828STAW2-080
Solar/Wind Harmer
0.102
217204WCALDSOLAR C
Solar/Wind Harmer
0.071
20674528F3S_W2-016
Solar/Wind Harmer
1.362
20676228FRD_X1-012
Solar/Wind Harmer
0.557
207471AF2-354 C
Solar/Wind Harmer
0.473
20674928WA_W3-044
Solar/Wind Harmer
0.446
964851AG1-348 GEN
Solar/Wind Harmer
1.619
20634528N27_Y2-018
Solar/Wind Harmer
0.248
20465127PORT CT
Adder
3.63
20674128FR_U2-059
Solar/Wind Harmer
0.167
966111AG1-480 GEN
Solar/Wind Harmer
0.078
966111AG1-480 GEN
Solar/Wind Harmer
2.987
211065PSPA IPP
Solar/Wind Harmer
0.394
211065PSPA IPP
Solar/Wind Harmer
0.394
209029WAYMART-WD
Solar/Wind Harmer
2.355
209009PEIP 2
Adder
6.395
209010PEIP 1
Adder
2.898
209010PEIP 1
Adder
0.424
208972BECR K09
Solar/Wind Harmer
0.857
961541AF2-445A GEN
Solar/Wind Harmer
2.542
961431AF2-434 GEN
Solar/Wind Harmer
0.76
209054AE2-059 GEN
Solar/Wind Harmer
1.243
209059AE2-084 GEN
Solar/Wind Harmer
1.836
946751AF1-339 GEN
Solar/Wind Harmer
0.725
218438BLK ROCK C
Solar/Wind Harmer
0.14
20635828PARLN1&2
Adder
3.399
20635928PARLN3&4
Adder
3.399
20635028RRCT1&2
Adder
11.906
20635128RRCT3&4
Adder
9.871
219908AB1-139 C
Solar/Wind Harmer
0.382
219919AE1-041 FULL
Solar/Wind Harmer
0.04
219249CENTRALDIV C
Solar/Wind Harmer
0.04
20673728F2S_V4-070
Solar/Wind Harmer
0.178
217211CAMDEN ST C
Solar/Wind Harmer
0.024
217186ESSEX_G9
Adder
15.661
217169METRODIV C
Solar/Wind Harmer
0.039
217194REDH C
Solar/Wind Harmer
0.482
20676728BRNX1-095
Solar/Wind Harmer
0.17
20674628WNG_W3-110
Solar/Wind Harmer
0.38
207510AF2-138 C
Solar/Wind Harmer
1.676
971007AG2-625 GEN
Solar/Wind Harmer
2.365
20466127PORT 5CT
Adder
24.18
20465427SHAW CT
Adder
3.501
20633028GILCT9
Adder
25.473
966181AG1-487 GEN
Solar/Wind Harmer
0.226
963161AG1-165 GEN
Solar/Wind Harmer
0.823
209025WIENIPP3
Adder
4.34
963071AG1-156 GEN
Solar/Wind Harmer
2.267
970095AG2-074 GEN
Solar/Wind Harmer
5.145
209027LOR2_Q27
Solar/Wind Harmer
3.539
209022WHFR IPP
Adder
2.541
961331AF2-424 GEN
Solar/Wind Harmer
0.762
961421AF2-433 GEN
Solar/Wind Harmer
0.76
957921AF2-086 GEN
Solar/Wind Harmer
0.739
209142AF1-226 GEN
Solar/Wind Harmer
4.4
209093AE2-110 GEN
Solar/Wind Harmer
1.901
209120AE2-241 GEN
Solar/Wind Harmer
2.515
972245AH1-707 GEN
Adder
4.059
946691AF1-333 GEN
Solar/Wind Harmer
0.725
946741AF1-338 GEN
Solar/Wind Harmer
0.725
223402AF1-300 C
Solar/Wind Helper
0.701
226910AB2-157 C
Solar/Wind Helper
0.019
227287AC2-120 GEN
Solar/Wind Helper
0.446
200192DELTA CT1
50/50
2.476
200194DELTA CT3
50/50
2.476
200204Y1-065-CTG1
50/50
5.079
200054ROCKSP 3
50/50
3.24
232426Y1-080 FULL
Solar/Wind Harmer
0.269
233964AF2-378 GEN
Solar/Wind Harmer
0.18
970277AG2-181 GEN
Solar/Wind Harmer
7.058
965821AG1-450 GEN
Solar/Wind Harmer
7.328
232919VN10
Adder
3.95
233998TM1NIN_3.36
Solar/Wind Harmer
1.782
232428Y3-058 C
Solar/Wind Harmer
1.174
232404W1-003 C
Solar/Wind Harmer
1.409
232917OH NUG6
Adder
12.371
232915OH NUG4
Adder
12.344
971195AH1-057 GEN
Solar/Wind Harmer
1.54
232434Z2-077 GEN
Solar/Wind Harmer
0.352
972177AH1-672 GEN
Solar/Wind Harmer
18.88
233954AC2-188 GEN
Solar/Wind Harmer
1.582
233950AC2-186 GEN
Solar/Wind Harmer
0.791
234012AE2-112_GEN
Solar/Wind Harmer
3.232
232901NORTHST
Adder
11.683
232422X3-066 FULL
Solar/Wind Harmer
0.351
232910NRG_G1
Adder
12.118
232900DEMECSMY
Adder
12.943
233972AC1-094 C
Solar/Wind Harmer
0.93
233930AB2-032 GEN
Solar/Wind Harmer
1.17
233915AB1-141 GEN
Solar/Wind Harmer
1.391
231918WEST 1
Adder
4.588
231917EM10
Adder
3.192
228206SHRMN CT
Adder
19.291
213497CHSTR7-9
Adder
3.178
213497CHSTR7-9
Adder
3.178
228732V1-021 C
Adder
0.219
945431AF1-208 GEN
Solar/Wind Harmer
10.011
970997AG2-616 GEN
Solar/Wind Harmer
11.104
228351V2-046C
Solar/Wind Harmer
2.331
230511AF1-262
Solar/Wind Harmer
0.211
228728W1-130C
Solar/Wind Harmer
0.765
230434AG1-499 GEN
Solar/Wind Harmer
0.667
213958STHWK5-6
Adder
3.094
219258KINSLEYDEP C
Solar/Wind Harmer
0.366
219904AC1-010 C
Solar/Wind Harmer
0.425
218660EHAMPSOLAR C
Solar/Wind Harmer
0.195
219686LUMSOLAR_N C
Solar/Wind Harmer
0.226
219287REEVESEAST C
Solar/Wind Harmer
1.501
213560DLW11-12
Adder
3.039
219907AC1-030 C
Solar/Wind Harmer
0.154
219304NAMERICA C
Solar/Wind Harmer
0.34
219222BRL12CT2
Adder
9.78
213611FALLS1-3
Adder
3.817
20720728JCB_W1-129
Solar/Wind Harmer
0.319
214194N WALES4
Adder
0.912
207522AF2-254 C
Solar/Wind Harmer
1.535
207487AE2-000G4
Solar/Wind Harmer
33.557
207445AB1-138_GEN
Solar/Wind Harmer
0.612
20628028LAKEHURS
Adder
1.986
963711AG1-223 GEN
Solar/Wind Harmer
1.548
20714828MDF_W3-079
Solar/Wind Harmer
0.32
219680HOPEWELLV C1
Solar/Wind Harmer
0.079
207454AA2-184 E
Solar/Wind Harmer
1.034
20715228NPK_W1-113
Solar/Wind Harmer
0.444
20742028HF_AC1-207
Solar/Wind Harmer
0.808
217197RE CRAN C
Solar/Wind Harmer
0.55
20635828PARLN1&2
Adder
7.504
20635028RRCT1&2
Adder
11.723
20635128RRCT3&4
Adder
11.316
218428ETC SOLAR C
Solar/Wind Harmer
0.036
217213AMBOY SO C
Solar/Wind Harmer
0.127
972275AH1-722 GEN
Adder
31.477
218449LINSOLAR C
Solar/Wind Harmer
0.997
207528AF2-192 GEN
Solar/Wind Harmer
0.548
20673628F1S_V4-069
Solar/Wind Harmer
0.178
20675428EAM_W2-061
Solar/Wind Harmer
0.187
20676428JCR_X2-075
Solar/Wind Harmer
0.338
217209CENTRL HS C
Solar/Wind Harmer
0.044
217121ECCF
Adder
0.425
217083KRNY_132
Adder
9.105
217208PARK ELE C
Solar/Wind Harmer
0.025
207439AE1-081 C O1
Solar/Wind Harmer
0.057
20675828AU_W4-064
Solar/Wind Harmer
0.162
20674328GAR_V4-001
Solar/Wind Harmer
0.103
971519AH1-257 GEN
Solar/Wind Harmer
2.317
207518AF1-320_GEN
Solar/Wind Harmer
3.34
20465127PORT CT
Adder
2.735
207437AD2-070 GEN
Solar/Wind Harmer
0.274
20671928W4-073
Solar/Wind Harmer
0.392
966181AG1-487 GEN
Solar/Wind Harmer
3.371
208909MACR G3
Adder
143.164
961301AF2-421 GEN
Solar/Wind Harmer
0.823
963151AG1-164 GEN
Solar/Wind Harmer
0.823
209023WIENIPP1
Adder
8.874
209025WIENIPP3
Adder
4.429
209010PEIP 1
Adder
0.527
212266LOR1
Solar/Wind Harmer
0.102
970237AG2-161 GEN
Solar/Wind Harmer
2.718
961341AF2-425 GEN
Solar/Wind Harmer
0.762
212174INGE
Adder
0.843
212507AE2-042_GEN
Solar/Wind Harmer
2.203
946731AF1-337 GEN
Solar/Wind Harmer
0.725
209071AE2-133 GEN
Solar/Wind Harmer
1.224
970665AG2-430 GEN
Solar/Wind Harmer
7.17
209018SUNBIPCT
Adder
5.382
972241AH1-705 GEN
Adder
3.942
205941AD2-115 GEN
Solar/Wind Harmer
0.609
20467927PC_Q59Y356
Adder
0.493
20465527S.RDG CT
Adder
1.571
223401AF1-299 GEN
Solar/Wind Helper
0.701
209130AF1-271A GEN
Solar/Wind Harmer
2.031
20465527S.RDG CT
Adder
1.52
226929AD2-058 GEN
Solar/Wind Helper
0.123
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
HAMLETPJM->LTFIMP_HAMLET
CLTF
4.464
G-007ALTFEXP_G-007A->PJM
CMTX
51.777
CBM NorthLTFEXP_CBM-N->PJM
CBM
68.151
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
3.731
BlueGrassPJM->LTFIMP_BlueG
CLTF
11.624
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
133.211
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.638
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
17.53

Details for PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line l/o PL_04_P71_001014_SRT-A


Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
Contingency Name:
PL_04_P71_001014_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:118.7 %
Rating:3620.0 MVA
Rating Type:B
MVA to Mitigate:4297.06
MW Contribution:8.28
Bus #Bus NameTypeMW Contribution
200201DELTA2 CT2
50/50
4.378
200034PCHBTM 2
50/50
25.48
200035PCHBTM 3
50/50
25.205
200205Y1-065-CTG2
50/50
4.982
971149AH1-027 GEN
Solar/Wind Harmer
4.434
233939AC1-091 C
Solar/Wind Harmer
1.151
233970AC1-092 C
Solar/Wind Harmer
1.151
232899W1-062
Adder
12.569
970545AG2-347 GEN
Solar/Wind Harmer
85.498
233987AB2-037 GEN
Solar/Wind Harmer
14.866
972069AH1-584 GEN
Solar/Wind Harmer
11.695
972071AH1-585 GEN
Solar/Wind Harmer
11.695
233901CHERRYDALE C
Solar/Wind Harmer
1.47
232408W1-005 C
Solar/Wind Harmer
1.308
232410W1-006 C
Solar/Wind Harmer
1.308
232918OH NUG7
Adder
11.456
971747AH1-380 GEN
Solar/Wind Harmer
4.678
232905CHERITON_25
Adder
3.204
232926CRISFLD1
Adder
2.563
231940T-011
Adder
0.974
233946AB2-136 GEN
Solar/Wind Harmer
5.2
234036AF2-325 C
Solar/Wind Harmer
1.194
234041AC1-190 GEN
Solar/Wind Harmer
11.659
233984AB2-036 GEN
Solar/Wind Harmer
16.052
232424Y1-079 C
Solar/Wind Harmer
0.725
231131BLOOM ENRGY
Adder
5.586
234014AF1-036_GEN
Solar/Wind Harmer
3.469
233944AB2-135 GEN
Solar/Wind Harmer
6.691
233933AB2-153 GEN
Solar/Wind Harmer
1.434
232416X2-083
Adder
0.566
228251CARLLS#4
Adder
0.688
230422AE1-104_GEN1
Solar/Wind Harmer
36.635
230425AE1-104_GEN2
Solar/Wind Harmer
36.635
230433AD2-135 GEN
Solar/Wind Harmer
0.11
230407AD2-065 C
Solar/Wind Harmer
0.142
228307PCLP GT
Adder
13.028
228304LOGAN
Adder
25.992
972233AH1-701 GEN
Adder
4.494
219921AF1-264
Solar/Wind Harmer
0.152
213589EDDYSTN4
Adder
82.97
213587EDDYSTN3
Adder
82.96
219615MILLCREEK C
Solar/Wind Harmer
0.246
213535CROYDN11
Adder
10.503
213815MOSER1-3
Adder
3.619
213815MOSER1-3
Adder
3.619
20716428NHV_W2-082
Solar/Wind Harmer
1.805
207500AE2-000G1
Solar/Wind Harmer
31.921
207497AE2-000G2
Solar/Wind Harmer
31.921
207507AE2-000G3
Solar/Wind Harmer
31.921
20636128O CRK C2
Adder
6.53
963401AG1-189 GEN
Solar/Wind Harmer
1.163
963391AG1-188 GEN
Solar/Wind Harmer
1.937
20714928UPF_X1-085
Solar/Wind Harmer
0.41
20628028LAKEHURS
Adder
0.956
219114HARTZY_C
Solar/Wind Harmer
0.836
219817TRENTONSOL C
Solar/Wind Harmer
1.092
20641628MLH_W1-032
Solar/Wind Harmer
0.29
20720628TIN_W1-124
Solar/Wind Harmer
0.985
20716928W4-060COL
Solar/Wind Harmer
0.697
924131AB2-057 GEN
Solar/Wind Harmer
1
218440SUMMTASSOC C
Solar/Wind Harmer
0.124
218418LINDEN_G5
Adder
16.501
218419LINDEN_G6
Adder
16.501
972260AH1-715 GEN1
Adder
13.213
20673828FLE_V3-070
Solar/Wind Harmer
0.439
219036LINDEN_G7
Adder
15.993
219035LINDEN_G8
Adder
15.765
972261AH1-715 GEN2
Adder
15.31
207442AE1-156 GEN
Solar/Wind Harmer
0.711
20676128MHD_W3-029
Solar/Wind Harmer
0.456
217081WEATEXAS C
Solar/Wind Harmer
0.082
217202FBANKSOLAR C
Solar/Wind Harmer
0.07
217201HACKENSOLA C
Solar/Wind Harmer
0.069
972237AH1-703 GEN
Adder
9.59
217206BARNGR HS C
Solar/Wind Harmer
0.029
217086KRNY_131
Adder
8.827
217083KRNY_132
Adder
8.752
20671828STAW2-080
Solar/Wind Harmer
0.099
217204WCALDSOLAR C
Solar/Wind Harmer
0.069
20674528F3S_W2-016
Solar/Wind Harmer
1.322
20676228FRD_X1-012
Solar/Wind Harmer
0.544
207471AF2-354 C
Solar/Wind Harmer
0.465
20674928WA_W3-044
Solar/Wind Harmer
0.438
964851AG1-348 GEN
Solar/Wind Harmer
1.593
20634528N27_Y2-018
Solar/Wind Harmer
0.244
20465127PORT CT
Adder
3.578
20674128FR_U2-059
Solar/Wind Harmer
0.165
966111AG1-480 GEN
Solar/Wind Harmer
0.077
966111AG1-480 GEN
Solar/Wind Harmer
2.937
211065PSPA IPP
Solar/Wind Harmer
0.39
211065PSPA IPP
Solar/Wind Harmer
0.39
209029WAYMART-WD
Solar/Wind Harmer
2.314
209009PEIP 2
Adder
6.284
209010PEIP 1
Adder
2.847
209010PEIP 1
Adder
0.417
208972BECR K09
Solar/Wind Harmer
0.845
961541AF2-445A GEN
Solar/Wind Harmer
2.512
961431AF2-434 GEN
Solar/Wind Harmer
0.751
20465527S.RDG CT
Adder
1.984
209054AE2-059 GEN
Solar/Wind Harmer
1.229
209059AE2-084 GEN
Solar/Wind Harmer
1.815
946751AF1-339 GEN
Solar/Wind Harmer
0.717
209130AF1-271A GEN
Solar/Wind Harmer
2.009
226929AD2-058 GEN
Solar/Wind Helper
0.117
208835TUHI V3-051
Solar/Wind Helper
0.026
208835TUHI V3-051
Solar/Wind Helper
0.026
200202DELTA2 ST
50/50
7.429
200195DELTA ST
50/50
3.78
200052ROCKSP 1
50/50
3.147
200053ROCKSP 2
50/50
3.079
233973AC2-185 C
Solar/Wind Harmer
4.733
234033AF1-007_GEN
Solar/Wind Harmer
30.553
232904IR4
Adder
105.641
232920IR10
Adder
4.129
232432Z2-076 GEN
Solar/Wind Harmer
0.173
232912OH NUG1
Adder
11.533
232913OH NUG2
Adder
11.379
233990AG1-397 GEN
Solar/Wind Harmer
0.072
233923SMA
Solar/Wind Harmer
6.064
233955AB2-172 GEN
Solar/Wind Harmer
6.511
232813VAUGHN
Adder
0.764
231906DC3 NUG
Adder
17.942
231902DC CT7
Adder
14.344
231907DC10
Adder
4.479
233968AD2-076_GEN
Solar/Wind Harmer
8.5
970597AG2-380 GEN
Solar/Wind Harmer
5.338
232436AB1-176 C
Solar/Wind Harmer
0.293
971983AH1-536 GEN
Solar/Wind Harmer
9.54
233935AB2-179 C
Solar/Wind Harmer
3.097
231919CHRIST1
Adder
5.425
231920CHRIST2
Adder
5.304
970453AG2-297 GEN
Solar/Wind Harmer
3.034
228260V4-054C
Solar/Wind Harmer
1.119
228309CCLP NUG
Adder
28.089
228309CCLP NUG
Adder
26.719
972141AH1-641 GEN
Solar/Wind Harmer
3.125
964001AG1-254 GEN
Solar/Wind Harmer
2.205
971535AH1-265 GEN
Solar/Wind Harmer
4.604
971011AG2-627 GEN
Solar/Wind Harmer
8.282
227927V4-067C
Solar/Wind Harmer
0.214
228754AB1-001 C
Solar/Wind Harmer
0.151
219137THOSOLAR C
Solar/Wind Harmer
1.28
219272CLEANLIGHT C
Solar/Wind Harmer
0.192
219688LUMSOLAR_S C
Solar/Wind Harmer
0.212
219914AD2-027 C
Solar/Wind Harmer
0.627
213942SCHUYLKILL
Adder
3.67
213942SCHUYLKILL
Adder
2.807
213957STHWK3-4
Adder
2.807
213957STHWK3-4
Adder
2.807
213561DLWR9-10
Adder
3.654
213561DLWR9-10
Adder
2.795
219607WPEMNERT C
Solar/Wind Harmer
0.431
219224BRL12CT4
Adder
9.176
214067T20SOLAR
Solar/Wind Harmer
0.257
213611FALLS1-3
Adder
3.589
213611FALLS1-3
Adder
3.589
20717128DIX_Z2-102
Solar/Wind Harmer
1.339
20715728PEM_W1-119
Solar/Wind Harmer
0.542
20715828PEM_W1-120
Solar/Wind Harmer
0.542
970025AG2-016 GEN
Solar/Wind Harmer
2.863
971189AH1-054 GEN
Solar/Wind Harmer
1.191
207459AE1-142 C O1
Solar/Wind Harmer
1.063
219620RIDERU C
Solar/Wind Harmer
0.055
20714328BYD_X4-031
Solar/Wind Harmer
0.28
20714428HOW_X1-037
Solar/Wind Harmer
1.224
971521AH1-258 GEN
Solar/Wind Harmer
2.666
20720428HOL_W1-112
Solar/Wind Harmer
0.34
20635928PARLN3&4
Adder
7.208
218455CINNBAY_CGEN
Adder
1.767
218526CNTRALGAS2 C
Solar/Wind Harmer
0.359
218524CNTRALGAS1 C
Solar/Wind Harmer
0.358
20675528CPH_W2-050
Solar/Wind Harmer
0.45
218404KENILWRTH C
Adder
1.24
217167KRNY_14
Adder
8.808
217086KRNY_131
Adder
8.733
217147KRNY_1212
Adder
8.378
217147KRNY_1212
Adder
8.229
217146KRNY_1234
Adder
8.21
217146KRNY_1234
Adder
8.154
966261AG1-495 GEN
Solar/Wind Harmer
1.665
20676328BVR_Y1-020
Solar/Wind Harmer
0.305
207511W3-106 GEN
Solar/Wind Harmer
0.604
207530AG1-191 GEN
Solar/Wind Harmer
1.264
20674828DL_W4-046
Solar/Wind Harmer
0.588
971009AG2-626 GEN
Solar/Wind Harmer
1.485
207408W3-077 C
Solar/Wind Harmer
0.457
20675728RH_W2-091
Solar/Wind Harmer
0.309
20675928HOL_W4-097
Solar/Wind Harmer
0.118
207484AF2-139 C O1
Solar/Wind Harmer
0.455
966421AG1-511 GEN
Solar/Wind Harmer
7.742
20675128HRM_W1-127
Solar/Wind Harmer
0.153
20462827N BANGR8
Adder
0.642
209116AE2-175 GEN
Solar/Wind Harmer
3.601
961261AF2-417 GEN
Solar/Wind Harmer
0.833
209026WIENIPP4
Adder
4.328
209045AE2-271 GEN
Solar/Wind Harmer
12.499
20486527WR_V4-052
Adder
0.793
208862AG1-362 C
Solar/Wind Harmer
0.591
959431AF2-234 GEN
Solar/Wind Harmer
1.429
964051AG1-259 GEN
Solar/Wind Harmer
0.958
964061AG1-260 GEN
Solar/Wind Harmer
0.958
959421AF2-233 GEN
Solar/Wind Harmer
0.714
200192DELTA CT1
50/50
2.446
200194DELTA CT3
50/50
2.446
200204Y1-065-CTG1
50/50
4.982
200054ROCKSP 3
50/50
3.178
232901NORTHST
Adder
10.903
233972AC1-094 C
Solar/Wind Harmer
0.869
232900DEMECSMY
Adder
12.056
232434Z2-077 GEN
Solar/Wind Harmer
0.327
972177AH1-672 GEN
Solar/Wind Harmer
17.547
232404W1-003 C
Solar/Wind Harmer
1.308
232917OH NUG6
Adder
11.482
232915OH NUG4
Adder
11.456
233998TM1NIN_3.36
Solar/Wind Harmer
1.654
971195AH1-057 GEN
Solar/Wind Harmer
1.429
232428Y3-058 C
Solar/Wind Harmer
1.089
232919VN10
Adder
3.66
965821AG1-450 GEN
Solar/Wind Harmer
6.787
232426Y1-080 FULL
Solar/Wind Harmer
0.249
970277AG2-181 GEN
Solar/Wind Harmer
6.536
233964AF2-378 GEN
Solar/Wind Harmer
0.166
233954AC2-188 GEN
Solar/Wind Harmer
1.466
233950AC2-186 GEN
Solar/Wind Harmer
0.733
232910NRG_G1
Adder
11.178
234012AE2-112_GEN
Solar/Wind Harmer
2.949
232422X3-066 FULL
Solar/Wind Harmer
0.32
233930AB2-032 GEN
Solar/Wind Harmer
1.063
233915AB1-141 GEN
Solar/Wind Harmer
1.263
231918WEST 1
Adder
4.124
231917EM10
Adder
2.87
228206SHRMN CT
Adder
18.158
228732V1-021 C
Adder
0.207
945431AF1-208 GEN
Solar/Wind Harmer
9.397
970997AG2-616 GEN
Solar/Wind Harmer
10.416
228351V2-046C
Solar/Wind Harmer
2.184
230511AF1-262
Solar/Wind Harmer
0.198
228728W1-130C
Solar/Wind Harmer
0.719
230434AG1-499 GEN
Solar/Wind Harmer
0.625
219258KINSLEYDEP C
Solar/Wind Harmer
0.341
218660EHAMPSOLAR C
Solar/Wind Harmer
0.184
219686LUMSOLAR_N C
Solar/Wind Harmer
0.213
219287REEVESEAST C
Solar/Wind Harmer
1.412
219904AC1-010 C
Solar/Wind Harmer
0.397
213497CHSTR7-9
Adder
2.845
213497CHSTR7-9
Adder
2.845
219907AC1-030 C
Solar/Wind Harmer
0.144
213958STHWK5-6
Adder
2.807
213560DLW11-12
Adder
2.795
219304NAMERICA C
Solar/Wind Harmer
0.319
219222BRL12CT2
Adder
9.176
20720728JCB_W1-129
Solar/Wind Harmer
0.303
207522AF2-254 C
Solar/Wind Harmer
1.456
213611FALLS1-3
Adder
3.589
207487AE2-000G4
Solar/Wind Harmer
31.921
214194N WALES4
Adder
0.859
207445AB1-138_GEN
Solar/Wind Harmer
0.583
20628028LAKEHURS
Adder
1.892
963711AG1-223 GEN
Solar/Wind Harmer
1.478
20714828MDF_W3-079
Solar/Wind Harmer
0.306
207454AA2-184 E
Solar/Wind Harmer
0.989
20715228NPK_W1-113
Solar/Wind Harmer
0.425
219680HOPEWELLV C1
Solar/Wind Harmer
0.075
20742028HF_AC1-207
Solar/Wind Harmer
0.774
217197RE CRAN C
Solar/Wind Harmer
0.526
20635828PARLN1&2
Adder
7.208
20635028RRCT1&2
Adder
11.27
20635128RRCT3&4
Adder
10.879
218428ETC SOLAR C
Solar/Wind Harmer
0.035
217213AMBOY SO C
Solar/Wind Harmer
0.122
972275AH1-722 GEN
Adder
30.335
218449LINSOLAR C
Solar/Wind Harmer
0.962
207528AF2-192 GEN
Solar/Wind Harmer
0.529
20673628F1S_V4-069
Solar/Wind Harmer
0.172
20675428EAM_W2-061
Solar/Wind Harmer
0.18
20676428JCR_X2-075
Solar/Wind Harmer
0.326
217209CENTRL HS C
Solar/Wind Harmer
0.042
217121ECCF
Adder
0.412
217083KRNY_132
Adder
8.808
217208PARK ELE C
Solar/Wind Harmer
0.024
207439AE1-081 C O1
Solar/Wind Harmer
0.055
20674328GAR_V4-001
Solar/Wind Harmer
0.101
20675828AU_W4-064
Solar/Wind Harmer
0.159
971519AH1-257 GEN
Solar/Wind Harmer
2.282
207518AF1-320_GEN
Solar/Wind Harmer
3.295
207437AD2-070 GEN
Solar/Wind Harmer
0.271
20465127PORT CT
Adder
2.696
20671928W4-073
Solar/Wind Harmer
0.388
966181AG1-487 GEN
Solar/Wind Harmer
3.348
208909MACR G3
Adder
141.472
961301AF2-421 GEN
Solar/Wind Harmer
0.812
963151AG1-164 GEN
Solar/Wind Harmer
0.812
209023WIENIPP1
Adder
8.759
209025WIENIPP3
Adder
4.372
209010PEIP 1
Adder
0.518
212266LOR1
Solar/Wind Harmer
0.1
970237AG2-161 GEN
Solar/Wind Harmer
2.686
961341AF2-425 GEN
Solar/Wind Harmer
0.754
212174INGE
Adder
0.833
20467927PC_Q59Y356
Adder
0.63
20465527S.RDG CT
Adder
2.051
205941AD2-115 GEN
Solar/Wind Harmer
0.677
212507AE2-042_GEN
Solar/Wind Harmer
2.177
946731AF1-337 GEN
Solar/Wind Harmer
0.717
209071AE2-133 GEN
Solar/Wind Harmer
1.21
970665AG2-430 GEN
Solar/Wind Harmer
7.089
209018SUNBIPCT
Adder
5.321
972241AH1-705 GEN
Adder
3.903
223401AF1-299 GEN
Solar/Wind Helper
0.629
200200DELTA2 CT1
50/50
4.378
200193DELTA CT2
50/50
2.446
200203Y1-065-STG
50/50
8.639
200055ROCKSP 4
50/50
3.111
233971AC1-093 C
Solar/Wind Harmer
1.028
970695AG2-447 GEN
Solar/Wind Harmer
4.693
972133AH1-634 GEN
Solar/Wind Harmer
12.954
972073AH1-586 GEN
Solar/Wind Harmer
12.239
232406W1-004 FULL
Solar/Wind Harmer
1.308
232914OH NUG3
Adder
11.533
232916OH NUG5
Adder
11.533
232921TASLEY2G
Adder
6.74
233990AG1-397 GEN
Solar/Wind Harmer
1.498
233996TM1833_GEN
Solar/Wind Harmer
1.654
233997TMININ_4.2
Solar/Wind Harmer
1.654
233940AF2-379 C
Solar/Wind Harmer
0.244
233900O-025 C
Adder
1.537
234015AF2-250 C
Solar/Wind Harmer
0.157
233994AC2-023 GEN
Solar/Wind Harmer
3.508
232907VN8
Adder
39.187
960671AF2-358 GEN
Solar/Wind Harmer
23.347
233952AC2-187 GEN
Solar/Wind Harmer
1.466
232417X3-008 C
Solar/Wind Harmer
2.604
972251AH1-710 GEN
Adder
57.342
233918AB1-142 GEN
Solar/Wind Harmer
1.263
233982AB2-133 GEN
Solar/Wind Harmer
6.204
228202CUMB CT
Adder
18.121
228711V2-041C
Solar/Wind Harmer
0.658
971553AH1-274 GEN
Solar/Wind Harmer
2.647
230430AE1-229_GEN
Solar/Wind Harmer
9.554
230415AB2-049 C
Solar/Wind Harmer
0.205
228729W2-030 C
Solar/Wind Harmer
0.625
228304LOGAN
Adder
23.377
219623KINSLEYBEA C
Solar/Wind Harmer
0.451
219291REEVESSOUT C
Solar/Wind Harmer
0.063
219766PARADISE C
Solar/Wind Harmer
0.33
213497CHSTR7-9
Adder
2.845
219912AD2-042 GEN
Solar/Wind Harmer
0.832
219236SOUTHERNHQ C
Solar/Wind Harmer
0.07
213958STHWK5-6
Adder
2.807
219906AC1-017 C
Solar/Wind Harmer
0.23
213560DLW11-12
Adder
2.795
219610FLORENCE C
Solar/Wind Harmer
1.424
219348LDSOLAR C
Solar/Wind Harmer
0.616
219221BRL12CT1
Adder
9.176
219223BRL12CT3
Adder
9.176
213815MOSER1-3
Adder
3.619
20716028EGP_W2-019
Solar/Wind Harmer
0.471
20720828JCB_W4-025
Solar/Wind Harmer
0.46
20715028HAN_X4-015
Solar/Wind Harmer
0.303
959561AF2-247 GEN
Solar/Wind Harmer
0.492
20636028O CRK C1
Adder
7.162
971667AH1-334 GEN
Solar/Wind Harmer
2.766
219727YARDVSOLFA C
Solar/Wind Harmer
0.91
20714528FRN_Y2-051
Solar/Wind Harmer
0.295
219276PARKLANDSO C
Solar/Wind Harmer
0.459
20716228APLW2-078
Solar/Wind Harmer
0.874
20720528MAN_W1-024
Solar/Wind Harmer
0.251
219918AC2-009 C
Solar/Wind Harmer
0.061
967451AG2-055 C O1
Solar/Wind Harmer
170.766
219612MATRIX C
Solar/Wind Harmer
0.18
218438BLK ROCK C
Solar/Wind Harmer
0.133
20635828PARLN1&2
Adder
3.265
20635928PARLN3&4
Adder
3.265
20635028RRCT1&2
Adder
11.446
20635128RRCT3&4
Adder
9.489
219908AB1-139 C
Solar/Wind Harmer
0.367
219919AE1-041 FULL
Solar/Wind Harmer
0.039
219249CENTRALDIV C
Solar/Wind Harmer
0.038
20673728F2S_V4-070
Solar/Wind Harmer
0.172
217211CAMDEN ST C
Solar/Wind Harmer
0.023
217186ESSEX_G9
Adder
15.151
217169METRODIV C
Solar/Wind Harmer
0.038
217194REDH C
Solar/Wind Harmer
0.466
20676728BRNX1-095
Solar/Wind Harmer
0.165
207510AF2-138 C
Solar/Wind Harmer
1.638
20674628WNG_W3-110
Solar/Wind Harmer
0.371
971007AG2-625 GEN
Solar/Wind Harmer
2.328
20466127PORT 5CT
Adder
23.794
20633028GILCT9
Adder
25.3
966181AG1-487 GEN
Solar/Wind Harmer
0.224
20465427SHAW CT
Adder
3.442
963161AG1-165 GEN
Solar/Wind Harmer
0.812
209025WIENIPP3
Adder
4.284
963071AG1-156 GEN
Solar/Wind Harmer
2.233
970095AG2-074 GEN
Solar/Wind Harmer
5.067
209027LOR2_Q27
Solar/Wind Harmer
3.498
209022WHFR IPP
Adder
2.511
961331AF2-424 GEN
Solar/Wind Harmer
0.754
961421AF2-433 GEN
Solar/Wind Harmer
0.751
957921AF2-086 GEN
Solar/Wind Harmer
0.73
209142AF1-226 GEN
Solar/Wind Harmer
4.348
209093AE2-110 GEN
Solar/Wind Harmer
1.878
209120AE2-241 GEN
Solar/Wind Harmer
2.485
972245AH1-707 GEN
Adder
4.011
946691AF1-333 GEN
Solar/Wind Harmer
0.717
946741AF1-338 GEN
Solar/Wind Harmer
0.717
223402AF1-300 C
Solar/Wind Helper
0.629
226910AB2-157 C
Solar/Wind Helper
0.018
227287AC2-120 GEN
Solar/Wind Helper
0.426
HAMLETPJM->LTFIMP_HAMLET
CLTF
4.266
G-007ALTFEXP_G-007A->PJM
CMTX
49.776
CBM NorthLTFEXP_CBM-N->PJM
CBM
66.171
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
3.567
BlueGrassPJM->LTFIMP_BlueG
CLTF
11.113
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
128.765
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.521
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
16.758

Details for PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line l/o PL_05_P71_000906_SRT-A


Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
Contingency Name:
PL_05_P71_000906_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:117.69 %
Rating:3620.0 MVA
Rating Type:B
MVA to Mitigate:4260.39
MW Contribution:8.22
Bus #Bus NameTypeMW Contribution
200202DELTA2 ST
50/50
7.384
200195DELTA ST
50/50
3.757
200052ROCKSP 1
50/50
3.127
200053ROCKSP 2
50/50
3.06
233973AC2-185 C
Solar/Wind Harmer
4.695
234033AF1-007_GEN
Solar/Wind Harmer
30.297
232904IR4
Adder
104.758
232920IR10
Adder
4.094
232432Z2-076 GEN
Solar/Wind Harmer
0.171
200200DELTA2 CT1
50/50
4.351
200193DELTA CT2
50/50
2.432
200203Y1-065-STG
50/50
8.585
200055ROCKSP 4
50/50
3.092
233971AC1-093 C
Solar/Wind Harmer
1.019
970695AG2-447 GEN
Solar/Wind Harmer
4.656
972133AH1-634 GEN
Solar/Wind Harmer
12.846
972073AH1-586 GEN
Solar/Wind Harmer
12.136
232406W1-004 FULL
Solar/Wind Harmer
1.297
232914OH NUG3
Adder
11.436
232916OH NUG5
Adder
11.436
232921TASLEY2G
Adder
6.684
233990AG1-397 GEN
Solar/Wind Harmer
1.485
233996TM1833_GEN
Solar/Wind Harmer
1.64
233997TMININ_4.2
Solar/Wind Harmer
1.64
233940AF2-379 C
Solar/Wind Harmer
0.242
234015AF2-250 C
Solar/Wind Harmer
0.156
233900O-025 C
Adder
1.524
233994AC2-023 GEN
Solar/Wind Harmer
3.478
232907VN8
Adder
38.853
960671AF2-358 GEN
Solar/Wind Harmer
23.148
233952AC2-187 GEN
Solar/Wind Harmer
1.454
232417X3-008 C
Solar/Wind Harmer
2.582
972251AH1-710 GEN
Adder
56.94
233918AB1-142 GEN
Solar/Wind Harmer
1.251
233982AB2-133 GEN
Solar/Wind Harmer
6.144
228202CUMB CT
Adder
17.997
228711V2-041C
Solar/Wind Harmer
0.654
971553AH1-274 GEN
Solar/Wind Harmer
2.629
230430AE1-229_GEN
Solar/Wind Harmer
9.487
230415AB2-049 C
Solar/Wind Harmer
0.204
228729W2-030 C
Solar/Wind Harmer
0.621
228304LOGAN
Adder
23.206
219623KINSLEYBEA C
Solar/Wind Harmer
0.448
219291REEVESSOUT C
Solar/Wind Harmer
0.063
219766PARADISE C
Solar/Wind Harmer
0.328
219912AD2-042 GEN
Solar/Wind Harmer
0.826
213497CHSTR7-9
Adder
2.816
219236SOUTHERNHQ C
Solar/Wind Harmer
0.07
219906AC1-017 C
Solar/Wind Harmer
0.229
213958STHWK5-6
Adder
2.781
219610FLORENCE C
Solar/Wind Harmer
1.415
219348LDSOLAR C
Solar/Wind Harmer
0.612
219221BRL12CT1
Adder
9.116
219223BRL12CT3
Adder
9.116
213560DLW11-12
Adder
2.772
213815MOSER1-3
Adder
3.592
20716028EGP_W2-019
Solar/Wind Harmer
0.469
20720828JCB_W4-025
Solar/Wind Harmer
0.458
20715028HAN_X4-015
Solar/Wind Harmer
0.301
20636028O CRK C1
Adder
7.124
959561AF2-247 GEN
Solar/Wind Harmer
0.489
971667AH1-334 GEN
Solar/Wind Harmer
2.751
219727YARDVSOLFA C
Solar/Wind Harmer
0.905
20714528FRN_Y2-051
Solar/Wind Harmer
0.293
219276PARKLANDSO C
Solar/Wind Harmer
0.456
20716228APLW2-078
Solar/Wind Harmer
0.87
20720528MAN_W1-024
Solar/Wind Harmer
0.25
219918AC2-009 C
Solar/Wind Harmer
0.06
967451AG2-055 C O1
Solar/Wind Harmer
170.047
219612MATRIX C
Solar/Wind Harmer
0.179
218438BLK ROCK C
Solar/Wind Harmer
0.133
20635828PARLN1&2
Adder
3.252
200192DELTA CT1
50/50
2.432
200194DELTA CT3
50/50
2.432
200204Y1-065-CTG1
50/50
4.951
200054ROCKSP 3
50/50
3.158
233972AC1-094 C
Solar/Wind Harmer
0.862
232901NORTHST
Adder
10.815
232900DEMECSMY
Adder
11.957
232434Z2-077 GEN
Solar/Wind Harmer
0.324
972177AH1-672 GEN
Solar/Wind Harmer
17.401
232404W1-003 C
Solar/Wind Harmer
1.297
232917OH NUG6
Adder
11.385
232915OH NUG4
Adder
11.36
233998TM1NIN_3.36
Solar/Wind Harmer
1.64
200201DELTA2 CT2
50/50
4.351
200034PCHBTM 2
50/50
25.326
200035PCHBTM 3
50/50
25.061
200205Y1-065-CTG2
50/50
4.951
233939AC1-091 C
Solar/Wind Harmer
1.141
233970AC1-092 C
Solar/Wind Harmer
1.141
971149AH1-027 GEN
Solar/Wind Harmer
4.398
232899W1-062
Adder
12.465
970545AG2-347 GEN
Solar/Wind Harmer
84.784
972069AH1-584 GEN
Solar/Wind Harmer
11.596
972071AH1-585 GEN
Solar/Wind Harmer
11.596
233987AB2-037 GEN
Solar/Wind Harmer
14.738
233901CHERRYDALE C
Solar/Wind Harmer
1.458
232408W1-005 C
Solar/Wind Harmer
1.297
232410W1-006 C
Solar/Wind Harmer
1.297
232918OH NUG7
Adder
11.36
971747AH1-380 GEN
Solar/Wind Harmer
4.638
232905CHERITON_25
Adder
3.177
232926CRISFLD1
Adder
2.541
231940T-011
Adder
0.966
233946AB2-136 GEN
Solar/Wind Harmer
5.155
232912OH NUG1
Adder
11.436
232913OH NUG2
Adder
11.283
233990AG1-397 GEN
Solar/Wind Harmer
0.071
233923SMA
Solar/Wind Harmer
6.013
233955AB2-172 GEN
Solar/Wind Harmer
6.454
232813VAUGHN
Adder
0.757
231906DC3 NUG
Adder
17.776
231902DC CT7
Adder
14.211
231907DC10
Adder
4.438
233968AD2-076_GEN
Solar/Wind Harmer
8.42
970597AG2-380 GEN
Solar/Wind Harmer
5.287
232436AB1-176 C
Solar/Wind Harmer
0.291
971983AH1-536 GEN
Solar/Wind Harmer
9.448
233935AB2-179 C
Solar/Wind Harmer
3.063
231919CHRIST1
Adder
5.37
231920CHRIST2
Adder
5.251
970453AG2-297 GEN
Solar/Wind Harmer
3.013
228260V4-054C
Solar/Wind Harmer
1.111
228309CCLP NUG
Adder
27.889
228309CCLP NUG
Adder
26.528
972141AH1-641 GEN
Solar/Wind Harmer
3.103
964001AG1-254 GEN
Solar/Wind Harmer
2.189
971535AH1-265 GEN
Solar/Wind Harmer
4.572
227927V4-067C
Solar/Wind Harmer
0.213
971011AG2-627 GEN
Solar/Wind Harmer
8.222
228754AB1-001 C
Solar/Wind Harmer
0.15
219137THOSOLAR C
Solar/Wind Harmer
1.27
219272CLEANLIGHT C
Solar/Wind Harmer
0.191
219688LUMSOLAR_S C
Solar/Wind Harmer
0.211
219914AD2-027 C
Solar/Wind Harmer
0.623
213957STHWK3-4
Adder
2.781
213957STHWK3-4
Adder
2.781
213942SCHUYLKILL
Adder
3.636
213942SCHUYLKILL
Adder
2.781
219607WPEMNERT C
Solar/Wind Harmer
0.428
219224BRL12CT4
Adder
9.116
213561DLWR9-10
Adder
3.624
213561DLWR9-10
Adder
2.772
20717128DIX_Z2-102
Solar/Wind Harmer
1.332
214067T20SOLAR
Solar/Wind Harmer
0.255
213611FALLS1-3
Adder
3.567
213611FALLS1-3
Adder
3.567
20715728PEM_W1-119
Solar/Wind Harmer
0.539
20715828PEM_W1-120
Solar/Wind Harmer
0.539
970025AG2-016 GEN
Solar/Wind Harmer
2.848
971189AH1-054 GEN
Solar/Wind Harmer
1.185
207459AE1-142 C O1
Solar/Wind Harmer
1.058
20714328BYD_X4-031
Solar/Wind Harmer
0.279
219620RIDERU C
Solar/Wind Harmer
0.055
20714428HOW_X1-037
Solar/Wind Harmer
1.219
971521AH1-258 GEN
Solar/Wind Harmer
2.654
20720428HOL_W1-112
Solar/Wind Harmer
0.339
20635928PARLN3&4
Adder
7.18
218455CINNBAY_CGEN
Adder
1.76
218526CNTRALGAS2 C
Solar/Wind Harmer
0.357
218524CNTRALGAS1 C
Solar/Wind Harmer
0.356
20675528CPH_W2-050
Solar/Wind Harmer
0.448
218404KENILWRTH C
Adder
1.237
217167KRNY_14
Adder
8.784
217086KRNY_131
Adder
8.71
217147KRNY_1212
Adder
8.355
217147KRNY_1212
Adder
8.206
217146KRNY_1234
Adder
8.187
217146KRNY_1234
Adder
8.131
966261AG1-495 GEN
Solar/Wind Harmer
1.66
20676328BVR_Y1-020
Solar/Wind Harmer
0.304
207511W3-106 GEN
Solar/Wind Harmer
0.603
207530AG1-191 GEN
Solar/Wind Harmer
1.262
20674828DL_W4-046
Solar/Wind Harmer
0.587
971009AG2-626 GEN
Solar/Wind Harmer
1.483
207408W3-077 C
Solar/Wind Harmer
0.456
20675728RH_W2-091
Solar/Wind Harmer
0.308
20675928HOL_W4-097
Solar/Wind Harmer
0.117
966421AG1-511 GEN
Solar/Wind Harmer
7.74
207484AF2-139 C O1
Solar/Wind Harmer
0.454
20675128HRM_W1-127
Solar/Wind Harmer
0.152
20462827N BANGR8
Adder
0.641
209116AE2-175 GEN
Solar/Wind Harmer
3.606
961261AF2-417 GEN
Solar/Wind Harmer
0.837
209026WIENIPP4
Adder
4.361
209045AE2-271 GEN
Solar/Wind Harmer
12.677
959431AF2-234 GEN
Solar/Wind Harmer
1.454
964051AG1-259 GEN
Solar/Wind Harmer
0.975
964061AG1-260 GEN
Solar/Wind Harmer
0.975
959421AF2-233 GEN
Solar/Wind Harmer
0.727
20486527WR_V4-052
Adder
0.756
208862AG1-362 C
Solar/Wind Harmer
0.529
234036AF2-325 C
Solar/Wind Harmer
1.184
234041AC1-190 GEN
Solar/Wind Harmer
11.559
233984AB2-036 GEN
Solar/Wind Harmer
15.905
232424Y1-079 C
Solar/Wind Harmer
0.718
231131BLOOM ENRGY
Adder
5.534
234014AF1-036_GEN
Solar/Wind Harmer
3.437
233944AB2-135 GEN
Solar/Wind Harmer
6.627
233933AB2-153 GEN
Solar/Wind Harmer
1.421
232416X2-083
Adder
0.56
228251CARLLS#4
Adder
0.683
230422AE1-104_GEN1
Solar/Wind Harmer
36.391
230425AE1-104_GEN2
Solar/Wind Harmer
36.391
230433AD2-135 GEN
Solar/Wind Harmer
0.109
230407AD2-065 C
Solar/Wind Harmer
0.141
228307PCLP GT
Adder
12.933
228304LOGAN
Adder
25.802
972233AH1-701 GEN
Adder
4.461
219921AF1-264
Solar/Wind Harmer
0.151
213589EDDYSTN4
Adder
82.132
213587EDDYSTN3
Adder
82.123
219615MILLCREEK C
Solar/Wind Harmer
0.245
213535CROYDN11
Adder
10.433
213815MOSER1-3
Adder
3.592
213815MOSER1-3
Adder
3.592
20716428NHV_W2-082
Solar/Wind Harmer
1.795
207500AE2-000G1
Solar/Wind Harmer
31.751
207497AE2-000G2
Solar/Wind Harmer
31.751
207507AE2-000G3
Solar/Wind Harmer
31.751
20636128O CRK C2
Adder
6.496
963401AG1-189 GEN
Solar/Wind Harmer
1.157
963391AG1-188 GEN
Solar/Wind Harmer
1.927
20714928UPF_X1-085
Solar/Wind Harmer
0.408
20628028LAKEHURS
Adder
0.951
219114HARTZY_C
Solar/Wind Harmer
0.832
219817TRENTONSOL C
Solar/Wind Harmer
1.087
20641628MLH_W1-032
Solar/Wind Harmer
0.289
20720628TIN_W1-124
Solar/Wind Harmer
0.981
20716928W4-060COL
Solar/Wind Harmer
0.694
924131AB2-057 GEN
Solar/Wind Harmer
0.996
218440SUMMTASSOC C
Solar/Wind Harmer
0.123
218418LINDEN_G5
Adder
16.445
218419LINDEN_G6
Adder
16.445
972260AH1-715 GEN1
Adder
13.169
20673828FLE_V3-070
Solar/Wind Harmer
0.437
219036LINDEN_G7
Adder
15.943
219035LINDEN_G8
Adder
15.715
972261AH1-715 GEN2
Adder
15.261
207442AE1-156 GEN
Solar/Wind Harmer
0.708
20676128MHD_W3-029
Solar/Wind Harmer
0.454
217081WEATEXAS C
Solar/Wind Harmer
0.082
217202FBANKSOLAR C
Solar/Wind Harmer
0.07
217201HACKENSOLA C
Solar/Wind Harmer
0.069
972237AH1-703 GEN
Adder
9.564
217206BARNGR HS C
Solar/Wind Harmer
0.029
217086KRNY_131
Adder
8.803
217083KRNY_132
Adder
8.728
20671828STAW2-080
Solar/Wind Harmer
0.099
217204WCALDSOLAR C
Solar/Wind Harmer
0.069
20674528F3S_W2-016
Solar/Wind Harmer
1.318
20676228FRD_X1-012
Solar/Wind Harmer
0.543
207471AF2-354 C
Solar/Wind Harmer
0.464
20674928WA_W3-044
Solar/Wind Harmer
0.438
964851AG1-348 GEN
Solar/Wind Harmer
1.591
20634528N27_Y2-018
Solar/Wind Harmer
0.243
20465127PORT CT
Adder
3.575
20674128FR_U2-059
Solar/Wind Harmer
0.165
966111AG1-480 GEN
Solar/Wind Harmer
0.077
966111AG1-480 GEN
Solar/Wind Harmer
2.938
211065PSPA IPP
Solar/Wind Harmer
0.391
211065PSPA IPP
Solar/Wind Harmer
0.391
209029WAYMART-WD
Solar/Wind Harmer
2.331
209009PEIP 2
Adder
6.329
209010PEIP 1
Adder
2.868
209010PEIP 1
Adder
0.42
208972BECR K09
Solar/Wind Harmer
0.852
961541AF2-445A GEN
Solar/Wind Harmer
2.543
961431AF2-434 GEN
Solar/Wind Harmer
0.761
209054AE2-059 GEN
Solar/Wind Harmer
1.249
209059AE2-084 GEN
Solar/Wind Harmer
1.844
946751AF1-339 GEN
Solar/Wind Harmer
0.729
209130AF1-271A GEN
Solar/Wind Harmer
2.044
20465527S.RDG CT
Adder
1.876
226929AD2-058 GEN
Solar/Wind Helper
0.121
971195AH1-057 GEN
Solar/Wind Harmer
1.417
232428Y3-058 C
Solar/Wind Harmer
1.08
232919VN10
Adder
3.629
965821AG1-450 GEN
Solar/Wind Harmer
6.729
232426Y1-080 FULL
Solar/Wind Harmer
0.247
970277AG2-181 GEN
Solar/Wind Harmer
6.48
233964AF2-378 GEN
Solar/Wind Harmer
0.165
233954AC2-188 GEN
Solar/Wind Harmer
1.454
233950AC2-186 GEN
Solar/Wind Harmer
0.727
232910NRG_G1
Adder
11.08
234012AE2-112_GEN
Solar/Wind Harmer
2.921
232422X3-066 FULL
Solar/Wind Harmer
0.317
233930AB2-032 GEN
Solar/Wind Harmer
1.053
233915AB1-141 GEN
Solar/Wind Harmer
1.251
231918WEST 1
Adder
4.082
231917EM10
Adder
2.841
228206SHRMN CT
Adder
18.034
228732V1-021 C
Adder
0.205
945431AF1-208 GEN
Solar/Wind Harmer
9.331
970997AG2-616 GEN
Solar/Wind Harmer
10.342
228351V2-046C
Solar/Wind Harmer
2.169
230511AF1-262
Solar/Wind Harmer
0.197
228728W1-130C
Solar/Wind Harmer
0.714
230434AG1-499 GEN
Solar/Wind Harmer
0.621
219258KINSLEYDEP C
Solar/Wind Harmer
0.338
218660EHAMPSOLAR C
Solar/Wind Harmer
0.183
219287REEVESEAST C
Solar/Wind Harmer
1.403
219686LUMSOLAR_N C
Solar/Wind Harmer
0.211
219904AC1-010 C
Solar/Wind Harmer
0.394
213497CHSTR7-9
Adder
2.816
213497CHSTR7-9
Adder
2.816
219907AC1-030 C
Solar/Wind Harmer
0.143
213958STHWK5-6
Adder
2.781
219304NAMERICA C
Solar/Wind Harmer
0.317
219222BRL12CT2
Adder
9.116
213560DLW11-12
Adder
2.772
20720728JCB_W1-129
Solar/Wind Harmer
0.301
207522AF2-254 C
Solar/Wind Harmer
1.448
213611FALLS1-3
Adder
3.567
207487AE2-000G4
Solar/Wind Harmer
31.751
214194N WALES4
Adder
0.853
207445AB1-138_GEN
Solar/Wind Harmer
0.58
20628028LAKEHURS
Adder
1.882
963711AG1-223 GEN
Solar/Wind Harmer
1.47
20714828MDF_W3-079
Solar/Wind Harmer
0.304
207454AA2-184 E
Solar/Wind Harmer
0.984
20715228NPK_W1-113
Solar/Wind Harmer
0.423
219680HOPEWELLV C1
Solar/Wind Harmer
0.075
20742028HF_AC1-207
Solar/Wind Harmer
0.771
217197RE CRAN C
Solar/Wind Harmer
0.523
20635828PARLN1&2
Adder
7.18
20635028RRCT1&2
Adder
11.227
20635128RRCT3&4
Adder
10.837
218428ETC SOLAR C
Solar/Wind Harmer
0.034
217213AMBOY SO C
Solar/Wind Harmer
0.122
972275AH1-722 GEN
Adder
30.232
218449LINSOLAR C
Solar/Wind Harmer
0.959
207528AF2-192 GEN
Solar/Wind Harmer
0.527
20673628F1S_V4-069
Solar/Wind Harmer
0.171
20675428EAM_W2-061
Solar/Wind Harmer
0.18
20676428JCR_X2-075
Solar/Wind Harmer
0.325
217209CENTRL HS C
Solar/Wind Harmer
0.042
217121ECCF
Adder
0.41
217083KRNY_132
Adder
8.784
217208PARK ELE C
Solar/Wind Harmer
0.024
207439AE1-081 C O1
Solar/Wind Harmer
0.055
20674328GAR_V4-001
Solar/Wind Harmer
0.101
20675828AU_W4-064
Solar/Wind Harmer
0.158
971519AH1-257 GEN
Solar/Wind Harmer
2.278
207518AF1-320_GEN
Solar/Wind Harmer
3.291
207437AD2-070 GEN
Solar/Wind Harmer
0.271
20465127PORT CT
Adder
2.694
20671928W4-073
Solar/Wind Harmer
0.387
966181AG1-487 GEN
Solar/Wind Harmer
3.342
208909MACR G3
Adder
141.457
961301AF2-421 GEN
Solar/Wind Harmer
0.818
963151AG1-164 GEN
Solar/Wind Harmer
0.818
209023WIENIPP1
Adder
8.825
209025WIENIPP3
Adder
4.405
209010PEIP 1
Adder
0.521
212266LOR1
Solar/Wind Harmer
0.102
970237AG2-161 GEN
Solar/Wind Harmer
2.718
961341AF2-425 GEN
Solar/Wind Harmer
0.764
212174INGE
Adder
0.844
212507AE2-042_GEN
Solar/Wind Harmer
2.213
205941AD2-115 GEN
Solar/Wind Harmer
0.679
946731AF1-337 GEN
Solar/Wind Harmer
0.729
209071AE2-133 GEN
Solar/Wind Harmer
1.231
970665AG2-430 GEN
Solar/Wind Harmer
7.214
209018SUNBIPCT
Adder
5.415
20467927PC_Q59Y356
Adder
0.599
20465527S.RDG CT
Adder
1.939
972241AH1-705 GEN
Adder
3.996
223401AF1-299 GEN
Solar/Wind Helper
0.681
20635928PARLN3&4
Adder
3.252
20635028RRCT1&2
Adder
11.402
20635128RRCT3&4
Adder
9.453
219908AB1-139 C
Solar/Wind Harmer
0.366
219919AE1-041 FULL
Solar/Wind Harmer
0.039
219249CENTRALDIV C
Solar/Wind Harmer
0.038
20673728F2S_V4-070
Solar/Wind Harmer
0.171
217211CAMDEN ST C
Solar/Wind Harmer
0.023
217186ESSEX_G9
Adder
15.109
217169METRODIV C
Solar/Wind Harmer
0.038
217194REDH C
Solar/Wind Harmer
0.465
20676728BRNX1-095
Solar/Wind Harmer
0.165
207510AF2-138 C
Solar/Wind Harmer
1.635
20674628WNG_W3-110
Solar/Wind Harmer
0.371
971007AG2-625 GEN
Solar/Wind Harmer
2.324
20466127PORT 5CT
Adder
23.783
20633028GILCT9
Adder
25.253
966181AG1-487 GEN
Solar/Wind Harmer
0.224
20465427SHAW CT
Adder
3.443
963161AG1-165 GEN
Solar/Wind Harmer
0.818
209025WIENIPP3
Adder
4.316
963071AG1-156 GEN
Solar/Wind Harmer
2.249
970095AG2-074 GEN
Solar/Wind Harmer
5.105
209027LOR2_Q27
Solar/Wind Harmer
3.54
209022WHFR IPP
Adder
2.541
961331AF2-424 GEN
Solar/Wind Harmer
0.764
961421AF2-433 GEN
Solar/Wind Harmer
0.761
957921AF2-086 GEN
Solar/Wind Harmer
0.74
209142AF1-226 GEN
Solar/Wind Harmer
4.407
209093AE2-110 GEN
Solar/Wind Harmer
1.903
209120AE2-241 GEN
Solar/Wind Harmer
2.518
972245AH1-707 GEN
Adder
4.071
946691AF1-333 GEN
Solar/Wind Harmer
0.729
946741AF1-338 GEN
Solar/Wind Harmer
0.729
223402AF1-300 C
Solar/Wind Helper
0.681
226910AB2-157 C
Solar/Wind Helper
0.018
227287AC2-120 GEN
Solar/Wind Helper
0.439
HAMLETPJM->LTFIMP_HAMLET
CLTF
4.344
G-007ALTFEXP_G-007A->PJM
CMTX
49.586
CBM NorthLTFEXP_CBM-N->PJM
CBM
66.332
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
3.607
BlueGrassPJM->LTFIMP_BlueG
CLTF
11.238
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
128.394
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.565
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
16.958

Details for PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line l/o PL_04_P22_102290_SRT-A


Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
Contingency Name:
PL_04_P22_102290_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:116.87 %
Rating:3620.0 MVA
Rating Type:B
MVA to Mitigate:4230.71
MW Contribution:8.17
Bus #Bus NameTypeMW Contribution
200201DELTA2 CT2
50/50
4.381
200034PCHBTM 2
50/50
25.5
200035PCHBTM 3
50/50
25.222
200205Y1-065-CTG2
50/50
4.98
971149AH1-027 GEN
Solar/Wind Harmer
4.403
233939AC1-091 C
Solar/Wind Harmer
1.142
233970AC1-092 C
Solar/Wind Harmer
1.142
970545AG2-347 GEN
Solar/Wind Harmer
84.899
232899W1-062
Adder
12.479
233987AB2-037 GEN
Solar/Wind Harmer
14.764
972069AH1-584 GEN
Solar/Wind Harmer
11.613
972071AH1-585 GEN
Solar/Wind Harmer
11.613
232918OH NUG7
Adder
11.376
971747AH1-380 GEN
Solar/Wind Harmer
4.645
233901CHERRYDALE C
Solar/Wind Harmer
1.46
232408W1-005 C
Solar/Wind Harmer
1.299
232410W1-006 C
Solar/Wind Harmer
1.299
232905CHERITON_25
Adder
3.181
232926CRISFLD1
Adder
2.545
231940T-011
Adder
0.967
233946AB2-136 GEN
Solar/Wind Harmer
5.164
234036AF2-325 C
Solar/Wind Harmer
1.186
234041AC1-190 GEN
Solar/Wind Harmer
11.578
233984AB2-036 GEN
Solar/Wind Harmer
15.942
232424Y1-079 C
Solar/Wind Harmer
0.72
231131BLOOM ENRGY
Adder
5.546
234014AF1-036_GEN
Solar/Wind Harmer
3.446
233944AB2-135 GEN
Solar/Wind Harmer
6.645
233933AB2-153 GEN
Solar/Wind Harmer
1.425
232416X2-083
Adder
0.561
228251CARLLS#4
Adder
0.678
230422AE1-104_GEN1
Solar/Wind Harmer
36.136
230425AE1-104_GEN2
Solar/Wind Harmer
36.136
230433AD2-135 GEN
Solar/Wind Harmer
0.108
230407AD2-065 C
Solar/Wind Harmer
0.14
228307PCLP GT
Adder
12.845
228304LOGAN
Adder
25.622
972233AH1-701 GEN
Adder
4.429
219921AF1-264
Solar/Wind Harmer
0.15
213589EDDYSTN4
Adder
81.796
213587EDDYSTN3
Adder
81.784
219615MILLCREEK C
Solar/Wind Harmer
0.242
213535CROYDN11
Adder
10.32
213815MOSER1-3
Adder
3.555
213815MOSER1-3
Adder
3.555
20716428NHV_W2-082
Solar/Wind Harmer
1.773
207500AE2-000G1
Solar/Wind Harmer
31.346
207497AE2-000G2
Solar/Wind Harmer
31.346
207507AE2-000G3
Solar/Wind Harmer
31.346
20636128O CRK C2
Adder
6.413
963401AG1-189 GEN
Solar/Wind Harmer
1.142
963391AG1-188 GEN
Solar/Wind Harmer
1.902
20714928UPF_X1-085
Solar/Wind Harmer
0.402
20628028LAKEHURS
Adder
0.938
219114HARTZY_C
Solar/Wind Harmer
0.82
219817TRENTONSOL C
Solar/Wind Harmer
1.07
20641628MLH_W1-032
Solar/Wind Harmer
0.284
20720628TIN_W1-124
Solar/Wind Harmer
0.965
20716928W4-060COL
Solar/Wind Harmer
0.681
924131AB2-057 GEN
Solar/Wind Harmer
0.978
218440SUMMTASSOC C
Solar/Wind Harmer
0.121
218418LINDEN_G5
Adder
16.102
218419LINDEN_G6
Adder
16.102
972260AH1-715 GEN1
Adder
12.894
20673828FLE_V3-070
Solar/Wind Harmer
0.427
219036LINDEN_G7
Adder
15.593
219035LINDEN_G8
Adder
15.37
972261AH1-715 GEN2
Adder
14.926
207442AE1-156 GEN
Solar/Wind Harmer
0.691
200202DELTA2 ST
50/50
7.435
200195DELTA ST
50/50
3.783
200052ROCKSP 1
50/50
3.146
200053ROCKSP 2
50/50
3.078
233973AC2-185 C
Solar/Wind Harmer
4.699
234033AF1-007_GEN
Solar/Wind Harmer
30.339
232904IR4
Adder
104.901
232920IR10
Adder
4.1
232432Z2-076 GEN
Solar/Wind Harmer
0.171
232912OH NUG1
Adder
11.453
232913OH NUG2
Adder
11.3
233923SMA
Solar/Wind Harmer
6.022
233990AG1-397 GEN
Solar/Wind Harmer
0.072
233955AB2-172 GEN
Solar/Wind Harmer
6.465
232813VAUGHN
Adder
0.759
231906DC3 NUG
Adder
17.817
231902DC CT7
Adder
14.243
231907DC10
Adder
4.448
233968AD2-076_GEN
Solar/Wind Harmer
8.442
970597AG2-380 GEN
Solar/Wind Harmer
5.301
232436AB1-176 C
Solar/Wind Harmer
0.291
971983AH1-536 GEN
Solar/Wind Harmer
9.475
233935AB2-179 C
Solar/Wind Harmer
3.076
231919CHRIST1
Adder
5.379
231920CHRIST2
Adder
5.26
970453AG2-297 GEN
Solar/Wind Harmer
2.994
228260V4-054C
Solar/Wind Harmer
1.104
228309CCLP NUG
Adder
27.708
228309CCLP NUG
Adder
26.356
972141AH1-641 GEN
Solar/Wind Harmer
3.082
964001AG1-254 GEN
Solar/Wind Harmer
2.175
971535AH1-265 GEN
Solar/Wind Harmer
4.54
971011AG2-627 GEN
Solar/Wind Harmer
8.166
227927V4-067C
Solar/Wind Harmer
0.211
228754AB1-001 C
Solar/Wind Harmer
0.148
219137THOSOLAR C
Solar/Wind Harmer
1.26
219272CLEANLIGHT C
Solar/Wind Harmer
0.189
219688LUMSOLAR_S C
Solar/Wind Harmer
0.209
200200DELTA2 CT1
50/50
4.381
200193DELTA CT2
50/50
2.448
200203Y1-065-STG
50/50
8.636
200055ROCKSP 4
50/50
3.11
233971AC1-093 C
Solar/Wind Harmer
1.02
970695AG2-447 GEN
Solar/Wind Harmer
4.66
972133AH1-634 GEN
Solar/Wind Harmer
12.863
972073AH1-586 GEN
Solar/Wind Harmer
12.153
232914OH NUG3
Adder
11.453
232916OH NUG5
Adder
11.453
232406W1-004 FULL
Solar/Wind Harmer
1.299
232921TASLEY2G
Adder
6.693
233996TM1833_GEN
Solar/Wind Harmer
1.642
233997TMININ_4.2
Solar/Wind Harmer
1.642
233990AG1-397 GEN
Solar/Wind Harmer
1.487
233940AF2-379 C
Solar/Wind Harmer
0.242
234015AF2-250 C
Solar/Wind Harmer
0.156
233900O-025 C
Adder
1.527
233994AC2-023 GEN
Solar/Wind Harmer
3.484
232907VN8
Adder
38.915
960671AF2-358 GEN
Solar/Wind Harmer
23.185
233952AC2-187 GEN
Solar/Wind Harmer
1.456
232417X3-008 C
Solar/Wind Harmer
2.586
972251AH1-710 GEN
Adder
56.828
233918AB1-142 GEN
Solar/Wind Harmer
1.255
233982AB2-133 GEN
Solar/Wind Harmer
6.161
228202CUMB CT
Adder
17.884
228711V2-041C
Solar/Wind Harmer
0.65
971553AH1-274 GEN
Solar/Wind Harmer
2.612
230430AE1-229_GEN
Solar/Wind Harmer
9.424
230415AB2-049 C
Solar/Wind Harmer
0.202
228729W2-030 C
Solar/Wind Harmer
0.616
228304LOGAN
Adder
23.044
219623KINSLEYBEA C
Solar/Wind Harmer
0.444
219291REEVESSOUT C
Solar/Wind Harmer
0.062
219766PARADISE C
Solar/Wind Harmer
0.325
213497CHSTR7-9
Adder
2.805
219912AD2-042 GEN
Solar/Wind Harmer
0.818
219236SOUTHERNHQ C
Solar/Wind Harmer
0.069
213958STHWK5-6
Adder
2.762
219906AC1-017 C
Solar/Wind Harmer
0.226
213560DLW11-12
Adder
2.747
219610FLORENCE C
Solar/Wind Harmer
1.4
219348LDSOLAR C
Solar/Wind Harmer
0.605
219221BRL12CT1
Adder
9.018
219223BRL12CT3
Adder
9.018
213815MOSER1-3
Adder
3.555
20716028EGP_W2-019
Solar/Wind Harmer
0.463
20720828JCB_W4-025
Solar/Wind Harmer
0.452
20715028HAN_X4-015
Solar/Wind Harmer
0.297
959561AF2-247 GEN
Solar/Wind Harmer
0.483
20636028O CRK C1
Adder
7.034
971667AH1-334 GEN
Solar/Wind Harmer
2.714
219727YARDVSOLFA C
Solar/Wind Harmer
0.893
20714528FRN_Y2-051
Solar/Wind Harmer
0.289
219276PARKLANDSO C
Solar/Wind Harmer
0.45
20716228APLW2-078
Solar/Wind Harmer
0.856
20720528MAN_W1-024
Solar/Wind Harmer
0.246
219918AC2-009 C
Solar/Wind Harmer
0.06
967451AG2-055 C O1
Solar/Wind Harmer
167.311
219612MATRIX C
Solar/Wind Harmer
0.176
218438BLK ROCK C
Solar/Wind Harmer
0.131
20635828PARLN1&2
Adder
3.191
20635928PARLN3&4
Adder
3.191
20635028RRCT1&2
Adder
11.184
20635128RRCT3&4
Adder
9.272
219908AB1-139 C
Solar/Wind Harmer
0.359
219919AE1-041 FULL
Solar/Wind Harmer
0.038
219249CENTRALDIV C
Solar/Wind Harmer
0.037
20673728F2S_V4-070
Solar/Wind Harmer
0.167
217211CAMDEN ST C
Solar/Wind Harmer
0.023
217186ESSEX_G9
Adder
14.748
217169METRODIV C
Solar/Wind Harmer
0.037
217194REDH C
Solar/Wind Harmer
0.454
20676728BRNX1-095
Solar/Wind Harmer
0.16
20674628WNG_W3-110
Solar/Wind Harmer
0.358
219914AD2-027 C
Solar/Wind Harmer
0.617
213942SCHUYLKILL
Adder
3.612
213942SCHUYLKILL
Adder
2.762
213957STHWK3-4
Adder
2.762
213957STHWK3-4
Adder
2.762
213561DLWR9-10
Adder
3.592
213561DLWR9-10
Adder
2.747
219607WPEMNERT C
Solar/Wind Harmer
0.424
219224BRL12CT4
Adder
9.018
214067T20SOLAR
Solar/Wind Harmer
0.252
213611FALLS1-3
Adder
3.524
213611FALLS1-3
Adder
3.524
20717128DIX_Z2-102
Solar/Wind Harmer
1.315
20715728PEM_W1-119
Solar/Wind Harmer
0.532
20715828PEM_W1-120
Solar/Wind Harmer
0.532
970025AG2-016 GEN
Solar/Wind Harmer
2.811
971189AH1-054 GEN
Solar/Wind Harmer
1.169
207459AE1-142 C O1
Solar/Wind Harmer
1.043
219620RIDERU C
Solar/Wind Harmer
0.054
20714328BYD_X4-031
Solar/Wind Harmer
0.275
20714428HOW_X1-037
Solar/Wind Harmer
1.2
971521AH1-258 GEN
Solar/Wind Harmer
2.61
20720428HOL_W1-112
Solar/Wind Harmer
0.333
20635928PARLN3&4
Adder
7.046
218455CINNBAY_CGEN
Adder
1.728
218526CNTRALGAS2 C
Solar/Wind Harmer
0.35
218524CNTRALGAS1 C
Solar/Wind Harmer
0.349
20675528CPH_W2-050
Solar/Wind Harmer
0.438
218404KENILWRTH C
Adder
1.208
217167KRNY_14
Adder
8.574
217086KRNY_131
Adder
8.501
217147KRNY_1212
Adder
8.155
217147KRNY_1212
Adder
8.009
217146KRNY_1234
Adder
7.991
217146KRNY_1234
Adder
7.936
966261AG1-495 GEN
Solar/Wind Harmer
1.596
20676328BVR_Y1-020
Solar/Wind Harmer
0.294
207511W3-106 GEN
Solar/Wind Harmer
0.583
207530AG1-191 GEN
Solar/Wind Harmer
1.214
20674828DL_W4-046
Solar/Wind Harmer
0.563
971009AG2-626 GEN
Solar/Wind Harmer
1.42
966421AG1-511 GEN
Solar/Wind Harmer
7.451
207408W3-077 C
Solar/Wind Harmer
0.435
20675728RH_W2-091
Solar/Wind Harmer
0.294
20675928HOL_W4-097
Solar/Wind Harmer
0.111
20462827N BANGR8
Adder
0.612
207484AF2-139 C O1
Solar/Wind Harmer
0.431
20675128HRM_W1-127
Solar/Wind Harmer
0.145
209116AE2-175 GEN
Solar/Wind Harmer
3.469
961261AF2-417 GEN
Solar/Wind Harmer
0.807
209026WIENIPP4
Adder
4.192
209045AE2-271 GEN
Solar/Wind Harmer
12.156
959431AF2-234 GEN
Solar/Wind Harmer
1.392
964051AG1-259 GEN
Solar/Wind Harmer
0.933
964061AG1-260 GEN
Solar/Wind Harmer
0.933
959421AF2-233 GEN
Solar/Wind Harmer
0.696
200192DELTA CT1
50/50
2.448
200194DELTA CT3
50/50
2.448
200204Y1-065-CTG1
50/50
4.98
200054ROCKSP 3
50/50
3.177
232901NORTHST
Adder
10.826
233972AC1-094 C
Solar/Wind Harmer
0.863
232900DEMECSMY
Adder
11.97
232434Z2-077 GEN
Solar/Wind Harmer
0.325
972177AH1-672 GEN
Solar/Wind Harmer
17.424
232917OH NUG6
Adder
11.402
232915OH NUG4
Adder
11.376
232404W1-003 C
Solar/Wind Harmer
1.299
233998TM1NIN_3.36
Solar/Wind Harmer
1.642
971195AH1-057 GEN
Solar/Wind Harmer
1.419
232428Y3-058 C
Solar/Wind Harmer
1.082
232919VN10
Adder
3.635
965821AG1-450 GEN
Solar/Wind Harmer
6.74
232426Y1-080 FULL
Solar/Wind Harmer
0.247
970277AG2-181 GEN
Solar/Wind Harmer
6.491
233964AF2-378 GEN
Solar/Wind Harmer
0.165
233954AC2-188 GEN
Solar/Wind Harmer
1.456
233950AC2-186 GEN
Solar/Wind Harmer
0.728
232910NRG_G1
Adder
11.099
234012AE2-112_GEN
Solar/Wind Harmer
2.929
232422X3-066 FULL
Solar/Wind Harmer
0.318
233930AB2-032 GEN
Solar/Wind Harmer
1.056
233915AB1-141 GEN
Solar/Wind Harmer
1.255
231918WEST 1
Adder
4.09
231917EM10
Adder
2.845
228206SHRMN CT
Adder
17.919
228732V1-021 C
Adder
0.204
945431AF1-208 GEN
Solar/Wind Harmer
9.27
970997AG2-616 GEN
Solar/Wind Harmer
10.274
228351V2-046C
Solar/Wind Harmer
2.154
230511AF1-262
Solar/Wind Harmer
0.196
228728W1-130C
Solar/Wind Harmer
0.709
230434AG1-499 GEN
Solar/Wind Harmer
0.616
219258KINSLEYDEP C
Solar/Wind Harmer
0.336
218660EHAMPSOLAR C
Solar/Wind Harmer
0.181
219686LUMSOLAR_N C
Solar/Wind Harmer
0.209
219287REEVESEAST C
Solar/Wind Harmer
1.39
219904AC1-010 C
Solar/Wind Harmer
0.391
213497CHSTR7-9
Adder
2.805
213497CHSTR7-9
Adder
2.805
219907AC1-030 C
Solar/Wind Harmer
0.142
213958STHWK5-6
Adder
2.762
213560DLW11-12
Adder
2.747
219304NAMERICA C
Solar/Wind Harmer
0.314
219222BRL12CT2
Adder
9.018
20720728JCB_W1-129
Solar/Wind Harmer
0.298
207522AF2-254 C
Solar/Wind Harmer
1.43
213611FALLS1-3
Adder
3.524
207487AE2-000G4
Solar/Wind Harmer
31.346
214194N WALES4
Adder
0.841
207445AB1-138_GEN
Solar/Wind Harmer
0.572
20628028LAKEHURS
Adder
1.856
963711AG1-223 GEN
Solar/Wind Harmer
1.449
20714828MDF_W3-079
Solar/Wind Harmer
0.3
207454AA2-184 E
Solar/Wind Harmer
0.969
20715228NPK_W1-113
Solar/Wind Harmer
0.417
219680HOPEWELLV C1
Solar/Wind Harmer
0.074
20742028HF_AC1-207
Solar/Wind Harmer
0.758
217197RE CRAN C
Solar/Wind Harmer
0.515
20635828PARLN1&2
Adder
7.046
20635028RRCT1&2
Adder
11.012
20635128RRCT3&4
Adder
10.629
218428ETC SOLAR C
Solar/Wind Harmer
0.034
217213AMBOY SO C
Solar/Wind Harmer
0.119
972275AH1-722 GEN
Adder
29.601
218449LINSOLAR C
Solar/Wind Harmer
0.938
207528AF2-192 GEN
Solar/Wind Harmer
0.514
20673628F1S_V4-069
Solar/Wind Harmer
0.167
20675428EAM_W2-061
Solar/Wind Harmer
0.175
20676428JCR_X2-075
Solar/Wind Harmer
0.317
217209CENTRL HS C
Solar/Wind Harmer
0.041
217121ECCF
Adder
0.401
217083KRNY_132
Adder
8.574
217208PARK ELE C
Solar/Wind Harmer
0.023
207439AE1-081 C O1
Solar/Wind Harmer
0.053
20675828AU_W4-064
Solar/Wind Harmer
0.153
20674328GAR_V4-001
Solar/Wind Harmer
0.097
971519AH1-257 GEN
Solar/Wind Harmer
2.178
207518AF1-320_GEN
Solar/Wind Harmer
3.142
20465127PORT CT
Adder
2.581
207437AD2-070 GEN
Solar/Wind Harmer
0.257
20671928W4-073
Solar/Wind Harmer
0.369
208909MACR G3
Adder
135.389
966181AG1-487 GEN
Solar/Wind Harmer
3.149
961301AF2-421 GEN
Solar/Wind Harmer
0.787
963151AG1-164 GEN
Solar/Wind Harmer
0.787
209023WIENIPP1
Adder
8.485
209025WIENIPP3
Adder
4.235
209010PEIP 1
Adder
0.503
212266LOR1
Solar/Wind Harmer
0.097
970237AG2-161 GEN
Solar/Wind Harmer
2.606
961341AF2-425 GEN
Solar/Wind Harmer
0.732
212174INGE
Adder
0.809
212507AE2-042_GEN
Solar/Wind Harmer
2.12
946731AF1-337 GEN
Solar/Wind Harmer
0.698
209071AE2-133 GEN
Solar/Wind Harmer
1.178
970665AG2-430 GEN
Solar/Wind Harmer
6.905
209018SUNBIPCT
Adder
5.183
972241AH1-705 GEN
Adder
3.813
205941AD2-115 GEN
Solar/Wind Harmer
0.507
223401AF1-299 GEN
Solar/Wind Helper
0.608
20676128MHD_W3-029
Solar/Wind Harmer
0.443
217081WEATEXAS C
Solar/Wind Harmer
0.08
217202FBANKSOLAR C
Solar/Wind Harmer
0.068
217201HACKENSOLA C
Solar/Wind Harmer
0.068
972237AH1-703 GEN
Adder
9.335
217206BARNGR HS C
Solar/Wind Harmer
0.028
217086KRNY_131
Adder
8.592
217083KRNY_132
Adder
8.519
217204WCALDSOLAR C
Solar/Wind Harmer
0.067
20671828STAW2-080
Solar/Wind Harmer
0.096
20674528F3S_W2-016
Solar/Wind Harmer
1.273
20676228FRD_X1-012
Solar/Wind Harmer
0.525
207471AF2-354 C
Solar/Wind Harmer
0.445
20674928WA_W3-044
Solar/Wind Harmer
0.419
964851AG1-348 GEN
Solar/Wind Harmer
1.523
20634528N27_Y2-018
Solar/Wind Harmer
0.233
20465127PORT CT
Adder
3.425
966111AG1-480 GEN
Solar/Wind Harmer
0.074
966111AG1-480 GEN
Solar/Wind Harmer
2.826
20674128FR_U2-059
Solar/Wind Harmer
0.157
211065PSPA IPP
Solar/Wind Harmer
0.375
211065PSPA IPP
Solar/Wind Harmer
0.375
209029WAYMART-WD
Solar/Wind Harmer
2.25
209009PEIP 2
Adder
6.11
209010PEIP 1
Adder
2.768
209010PEIP 1
Adder
0.405
208972BECR K09
Solar/Wind Harmer
0.82
961541AF2-445A GEN
Solar/Wind Harmer
2.438
961431AF2-434 GEN
Solar/Wind Harmer
0.73
207510AF2-138 C
Solar/Wind Harmer
1.578
971007AG2-625 GEN
Solar/Wind Harmer
2.226
20466127PORT 5CT
Adder
22.847
20465427SHAW CT
Adder
3.312
20633028GILCT9
Adder
23.794
966181AG1-487 GEN
Solar/Wind Harmer
0.211
963161AG1-165 GEN
Solar/Wind Harmer
0.787
209025WIENIPP3
Adder
4.15
963071AG1-156 GEN
Solar/Wind Harmer
2.166
970095AG2-074 GEN
Solar/Wind Harmer
4.916
209027LOR2_Q27
Solar/Wind Harmer
3.394
209022WHFR IPP
Adder
2.436
961331AF2-424 GEN
Solar/Wind Harmer
0.732
961421AF2-433 GEN
Solar/Wind Harmer
0.73
957921AF2-086 GEN
Solar/Wind Harmer
0.71
209142AF1-226 GEN
Solar/Wind Harmer
4.225
209093AE2-110 GEN
Solar/Wind Harmer
1.825
209120AE2-241 GEN
Solar/Wind Harmer
2.415
972245AH1-707 GEN
Adder
3.902
946691AF1-333 GEN
Solar/Wind Harmer
0.698
946741AF1-338 GEN
Solar/Wind Harmer
0.698
223402AF1-300 C
Solar/Wind Helper
0.608
226910AB2-157 C
Solar/Wind Helper
0.017
227287AC2-120 GEN
Solar/Wind Helper
0.416
209054AE2-059 GEN
Solar/Wind Harmer
1.196
209059AE2-084 GEN
Solar/Wind Harmer
1.766
946751AF1-339 GEN
Solar/Wind Harmer
0.698
209130AF1-271A GEN
Solar/Wind Harmer
1.956
226929AD2-058 GEN
Solar/Wind Helper
0.115
HAMLETPJM->LTFIMP_HAMLET
CLTF
4.17
G-007ALTFEXP_G-007A->PJM
CMTX
48.636
CBM NorthLTFEXP_CBM-N->PJM
CBM
64.448
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
3.49
BlueGrassPJM->LTFIMP_BlueG
CLTF
10.874
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
125.41
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.465
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
16.397

Details for PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line l/o BGE_P4_GRACETON_51_SRT-A


Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line
Contingency Name:
BGE_P4_GRACETON_51_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:149.46 %
Rating:2860.0 MVA
Rating Type:B
MVA to Mitigate:4274.42
MW Contribution:7.89
Bus #Bus NameTypeMW Contribution
200201DELTA2 CT2
50/50
9.773
200034PCHBTM 2
50/50
56.818
200205Y1-065-CTG2
50/50
10.592
232918OH NUG7
50/50
18.154
232905CHERITON_25
50/50
5.077
232926CRISFLD1
50/50
4.061
200035PCHBTM 3
50/50
-13.937
971149AH1-027 GEN
Solar/Wind Harmer
6.62
233987AB2-037 GEN
Solar/Wind Harmer
22.264
233939AC1-091 C
Solar/Wind Harmer
1.716
233970AC1-092 C
Solar/Wind Harmer
1.716
970545AG2-347 GEN
Solar/Wind Harmer
127.668
972069AH1-584 GEN
Solar/Wind Harmer
17.464
972071AH1-585 GEN
Solar/Wind Harmer
17.464
233901CHERRYDALE C
Solar/Wind Harmer
2.196
232408W1-005 C
Solar/Wind Harmer
1.953
232410W1-006 C
Solar/Wind Harmer
1.953
971747AH1-380 GEN
Solar/Wind Harmer
6.985
231940T-011
Adder
1.454
232899W1-062
Adder
18.729
233946AB2-136 GEN
Solar/Wind Harmer
7.758
234036AF2-325 C
Solar/Wind Harmer
1.782
234041AC1-190 GEN
Solar/Wind Harmer
17.388
233984AB2-036 GEN
Solar/Wind Harmer
23.783
232424Y1-079 C
Solar/Wind Harmer
1.073
234014AF1-036_GEN
Solar/Wind Harmer
5.117
233944AB2-135 GEN
Solar/Wind Harmer
9.831
233933AB2-153 GEN
Solar/Wind Harmer
2.106
231131BLOOM ENRGY
Adder
8.138
232416X2-083
Adder
0.783
230422AE1-104_GEN1
Solar/Wind Harmer
37.145
230425AE1-104_GEN2
Solar/Wind Harmer
37.145
228251CARLLS#4
Adder
0.694
230433AD2-135 GEN
Solar/Wind Harmer
0.109
230407AD2-065 C
Solar/Wind Harmer
0.136
228307PCLP GT
Adder
12.166
228304LOGAN
Adder
23.826
972233AH1-701 GEN
Adder
4.051
219921AF1-264
Solar/Wind Harmer
0.121
207500AE2-000G1
Solar/Wind Harmer
24.229
207497AE2-000G2
Solar/Wind Harmer
24.229
207507AE2-000G3
Solar/Wind Harmer
24.229
20636128O CRK C2
Adder
4.957
20716428NHV_W2-082
Solar/Wind Harmer
1.348
963401AG1-189 GEN
Solar/Wind Harmer
0.869
219615MILLCREEK C
Solar/Wind Harmer
0.179
213589EDDYSTN4
Adder
59.162
213587EDDYSTN3
Adder
59.07
963391AG1-188 GEN
Solar/Wind Harmer
1.434
213535CROYDN11
Adder
7.309
20714928UPF_X1-085
Solar/Wind Harmer
0.291
20628028LAKEHURS
Adder
0.682
219114HARTZY_C
Solar/Wind Harmer
0.535
20720628TIN_W1-124
Solar/Wind Harmer
0.628
20641628MLH_W1-032
Solar/Wind Harmer
0.183
219817TRENTONSOL C
Solar/Wind Harmer
0.636
20716928W4-060COL
Solar/Wind Harmer
0.412
924131AB2-057 GEN
Solar/Wind Harmer
0.534
218440SUMMTASSOC C
Solar/Wind Harmer
0.064
218418LINDEN_G5
Adder
8.267
218419LINDEN_G6
Adder
8.267
972260AH1-715 GEN1
Adder
6.62
200192DELTA CT1
50/50
5.461
200194DELTA CT3
50/50
5.461
200204Y1-065-CTG1
50/50
10.592
200054ROCKSP 3
50/50
6.757
231912HR6
50/50
2.882
231913HR7
50/50
2.882
233920W3-032A-CTG1
50/50
4.302
233921W3-032A-STG1
50/50
2.584
232901NORTHST
50/50
17.274
232917OH NUG6
50/50
18.195
232915OH NUG4
50/50
18.154
232910NRG_G1
50/50
17.58
233972AC1-094 C
Solar/Wind Harmer
1.296
232434Z2-077 GEN
Solar/Wind Harmer
0.488
232404W1-003 C
Solar/Wind Harmer
1.953
233998TM1NIN_3.36
Solar/Wind Harmer
2.47
972177AH1-672 GEN
Solar/Wind Harmer
26.183
971195AH1-057 GEN
Solar/Wind Harmer
2.134
232428Y3-058 C
Solar/Wind Harmer
1.626
232900DEMECSMY
Adder
17.964
232919VN10
Adder
5.463
965821AG1-450 GEN
Solar/Wind Harmer
10.129
232426Y1-080 FULL
Solar/Wind Harmer
0.372
970277AG2-181 GEN
Solar/Wind Harmer
9.754
233964AF2-378 GEN
Solar/Wind Harmer
0.248
233954AC2-188 GEN
Solar/Wind Harmer
2.183
233950AC2-186 GEN
Solar/Wind Harmer
1.092
234012AE2-112_GEN
Solar/Wind Harmer
4.349
232422X3-066 FULL
Solar/Wind Harmer
0.472
233930AB2-032 GEN
Solar/Wind Harmer
1.561
233915AB1-141 GEN
Solar/Wind Harmer
1.855
231918WEST 1
Adder
5.369
231917EM10
Adder
3.586
228206SHRMN CT
Adder
18.897
228732V1-021 C
Adder
0.214
945431AF1-208 GEN
Solar/Wind Harmer
9.398
970997AG2-616 GEN
Solar/Wind Harmer
10.281
230511AF1-262
Solar/Wind Harmer
0.194
228728W1-130C
Solar/Wind Harmer
0.702
228351V2-046C
Solar/Wind Harmer
2.126
230434AG1-499 GEN
Solar/Wind Harmer
0.589
218660EHAMPSOLAR C
Solar/Wind Harmer
0.155
219686LUMSOLAR_N C
Solar/Wind Harmer
0.179
219287REEVESEAST C
Solar/Wind Harmer
1.19
219258KINSLEYDEP C
Solar/Wind Harmer
0.274
219904AC1-010 C
Solar/Wind Harmer
0.31
219907AC1-030 C
Solar/Wind Harmer
0.107
207487AE2-000G4
Solar/Wind Harmer
24.229
213497CHSTR7-9
Adder
2.06
213497CHSTR7-9
Adder
2.06
20720728JCB_W1-129
Solar/Wind Harmer
0.226
207522AF2-254 C
Solar/Wind Harmer
1.087
219304NAMERICA C
Solar/Wind Harmer
0.228
219222BRL12CT2
Adder
6.542
207445AB1-138_GEN
Solar/Wind Harmer
0.416
20628028LAKEHURS
Adder
1.349
963711AG1-223 GEN
Solar/Wind Harmer
1.005
20714828MDF_W3-079
Solar/Wind Harmer
0.207
213611FALLS1-3
Adder
2.308
213958STHWK5-6
Adder
1.752
207454AA2-184 E
Solar/Wind Harmer
0.63
213560DLW11-12
Adder
1.671
20715228NPK_W1-113
Solar/Wind Harmer
0.265
20742028HF_AC1-207
Solar/Wind Harmer
0.479
219680HOPEWELLV C1
Solar/Wind Harmer
0.043
217197RE CRAN C
Solar/Wind Harmer
0.293
20635828PARLN1&2
Adder
4.065
20635028RRCT1&2
Adder
6.201
20635128RRCT3&4
Adder
5.986
218428ETC SOLAR C
Solar/Wind Harmer
0.018
217213AMBOY SO C
Solar/Wind Harmer
0.062
972275AH1-722 GEN
Adder
15.198
200200DELTA2 CT1
50/50
9.773
200193DELTA CT2
50/50
5.461
200203Y1-065-STG
50/50
18.368
200055ROCKSP 4
50/50
6.615
231914HR8
50/50
4.38
231911HR5
50/50
2.882
232914OH NUG3
50/50
18.276
232916OH NUG5
50/50
18.276
232921TASLEY2G
50/50
10.681
234034AF2-060
50/50
3.655
232911NRG_G2
50/50
0.961
233971AC1-093 C
Solar/Wind Harmer
1.533
970695AG2-447 GEN
Solar/Wind Harmer
7.001
972133AH1-634 GEN
Solar/Wind Harmer
19.344
972073AH1-586 GEN
Solar/Wind Harmer
18.276
232406W1-004 FULL
Solar/Wind Harmer
1.953
233996TM1833_GEN
Solar/Wind Harmer
2.47
233997TMININ_4.2
Solar/Wind Harmer
2.47
233940AF2-379 C
Solar/Wind Harmer
0.364
233990AG1-397 GEN
Solar/Wind Harmer
2.236
232907VN8
Adder
58.535
233900O-025 C
Adder
2.295
234015AF2-250 C
Solar/Wind Harmer
0.235
233994AC2-023 GEN
Solar/Wind Harmer
5.238
960671AF2-358 GEN
Solar/Wind Harmer
34.843
232417X3-008 C
Solar/Wind Harmer
3.883
233952AC2-187 GEN
Solar/Wind Harmer
2.183
233918AB1-142 GEN
Solar/Wind Harmer
1.855
233982AB2-133 GEN
Solar/Wind Harmer
9.098
972251AH1-710 GEN
Adder
79.357
228202CUMB CT
Adder
19.025
228711V2-041C
Solar/Wind Harmer
0.688
971553AH1-274 GEN
Solar/Wind Harmer
2.719
228729W2-030 C
Solar/Wind Harmer
0.621
230430AE1-229_GEN
Solar/Wind Harmer
9.407
230415AB2-049 C
Solar/Wind Harmer
0.199
228304LOGAN
Adder
21.429
219291REEVESSOUT C
Solar/Wind Harmer
0.054
219623KINSLEYBEA C
Solar/Wind Harmer
0.368
219766PARADISE C
Solar/Wind Harmer
0.258
219912AD2-042 GEN
Solar/Wind Harmer
0.628
219236SOUTHERNHQ C
Solar/Wind Harmer
0.052
20636028O CRK C1
Adder
5.436
213497CHSTR7-9
Adder
2.06
20716028EGP_W2-019
Solar/Wind Harmer
0.352
20720828JCB_W4-025
Solar/Wind Harmer
0.344
20715028HAN_X4-015
Solar/Wind Harmer
0.226
219906AC1-017 C
Solar/Wind Harmer
0.167
219610FLORENCE C
Solar/Wind Harmer
1.015
219348LDSOLAR C
Solar/Wind Harmer
0.439
219221BRL12CT1
Adder
6.542
219223BRL12CT3
Adder
6.542
971667AH1-334 GEN
Solar/Wind Harmer
1.99
959561AF2-247 GEN
Solar/Wind Harmer
0.332
20714528FRN_Y2-051
Solar/Wind Harmer
0.2
213958STHWK5-6
Adder
1.752
219727YARDVSOLFA C
Solar/Wind Harmer
0.572
213560DLW11-12
Adder
1.671
20720528MAN_W1-024
Solar/Wind Harmer
0.157
20716228APLW2-078
Solar/Wind Harmer
0.544
219276PARKLANDSO C
Solar/Wind Harmer
0.278
967451AG2-055 C O1
Solar/Wind Harmer
102.144
219918AC2-009 C
Solar/Wind Harmer
0.035
219612MATRIX C
Solar/Wind Harmer
0.101
218438BLK ROCK C
Solar/Wind Harmer
0.074
20635828PARLN1&2
Adder
1.841
20635928PARLN3&4
Adder
1.841
20635028RRCT1&2
Adder
6.298
20635128RRCT3&4
Adder
5.221
219908AB1-139 C
Solar/Wind Harmer
0.188
219919AE1-041 FULL
Solar/Wind Harmer
0.02
200202DELTA2 ST
50/50
16.585
200195DELTA ST
50/50
8.439
200052ROCKSP 1
50/50
6.69
200053ROCKSP 2
50/50
6.547
232616GEN FOOD
50/50
0.339
232904IR4
50/50
167.387
232920IR10
50/50
6.541
232912OH NUG1
50/50
18.276
232913OH NUG2
50/50
18.032
233973AC2-185 C
Solar/Wind Harmer
7.06
234033AF1-007_GEN
Solar/Wind Harmer
45.622
232432Z2-076 GEN
Solar/Wind Harmer
0.258
233923SMA
Solar/Wind Harmer
9.056
233990AG1-397 GEN
Solar/Wind Harmer
0.108
233955AB2-172 GEN
Solar/Wind Harmer
9.708
232813VAUGHN
Adder
1.134
233968AD2-076_GEN
Solar/Wind Harmer
12.537
970597AG2-380 GEN
Solar/Wind Harmer
7.872
232436AB1-176 C
Solar/Wind Harmer
0.432
231906DC3 NUG
Adder
26.221
231902DC CT7
Adder
20.962
231907DC10
Adder
6.546
971983AH1-536 GEN
Solar/Wind Harmer
14.01
233935AB2-179 C
Solar/Wind Harmer
4.441
231919CHRIST1
Adder
7.003
231920CHRIST2
Adder
6.847
970453AG2-297 GEN
Solar/Wind Harmer
3.221
228260V4-054C
Solar/Wind Harmer
1.13
972141AH1-641 GEN
Solar/Wind Harmer
3.084
227927V4-067C
Solar/Wind Harmer
0.213
228309CCLP NUG
Adder
27.623
228309CCLP NUG
Adder
26.275
228754AB1-001 C
Solar/Wind Harmer
0.149
964001AG1-254 GEN
Solar/Wind Harmer
2.15
971535AH1-265 GEN
Solar/Wind Harmer
4.479
971011AG2-627 GEN
Solar/Wind Harmer
7.893
219272CLEANLIGHT C
Solar/Wind Harmer
0.162
219137THOSOLAR C
Solar/Wind Harmer
1.066
219688LUMSOLAR_S C
Solar/Wind Harmer
0.176
219914AD2-027 C
Solar/Wind Harmer
0.473
20717128DIX_Z2-102
Solar/Wind Harmer
0.998
20715728PEM_W1-119
Solar/Wind Harmer
0.403
20715828PEM_W1-120
Solar/Wind Harmer
0.403
970025AG2-016 GEN
Solar/Wind Harmer
2.123
219607WPEMNERT C
Solar/Wind Harmer
0.307
219224BRL12CT4
Adder
6.542
971189AH1-054 GEN
Solar/Wind Harmer
0.869
207459AE1-142 C O1
Solar/Wind Harmer
0.769
214067T20SOLAR
Solar/Wind Harmer
0.165
213611FALLS1-3
Adder
2.308
213611FALLS1-3
Adder
2.308
213942SCHUYLKILL
Adder
2.292
213942SCHUYLKILL
Adder
1.753
213957STHWK3-4
Adder
1.752
213957STHWK3-4
Adder
1.752
20714328BYD_X4-031
Solar/Wind Harmer
0.182
20714428HOW_X1-037
Solar/Wind Harmer
0.788
213561DLWR9-10
Adder
2.185
213561DLWR9-10
Adder
1.671
971521AH1-258 GEN
Solar/Wind Harmer
1.644
20720428HOL_W1-112
Solar/Wind Harmer
0.208
219620RIDERU C
Solar/Wind Harmer
0.032
20635928PARLN3&4
Adder
4.065
218455CINNBAY_CGEN
Adder
0.944
218526CNTRALGAS2 C
Solar/Wind Harmer
0.187
218524CNTRALGAS1 C
Solar/Wind Harmer
0.186
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.332
G-007ALTFEXP_G-007A->PJM
CMTX
27.389
CBM NorthLTFEXP_CBM-N->PJM
CBM
22.771
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
3.049
BlueGrassPJM->LTFIMP_BlueG
CLTF
9.494
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
60.337
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.002
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
14.209

Details for PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line l/o PJM_500_BG_P4_5_CNSTN_C_SRT-A


Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line
Contingency Name:
PJM_500_BG_P4_5_CNSTN_C_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:149.46 %
Rating:2860.0 MVA
Rating Type:B
MVA to Mitigate:4274.41
MW Contribution:7.89
Bus #Bus NameTypeMW Contribution
200201DELTA2 CT2
50/50
9.773
200034PCHBTM 2
50/50
56.818
200205Y1-065-CTG2
50/50
10.592
232918OH NUG7
50/50
18.154
232905CHERITON_25
50/50
5.077
232926CRISFLD1
50/50
4.061
200035PCHBTM 3
50/50
-13.937
971149AH1-027 GEN
Solar/Wind Harmer
6.62
233987AB2-037 GEN
Solar/Wind Harmer
22.264
233939AC1-091 C
Solar/Wind Harmer
1.716
233970AC1-092 C
Solar/Wind Harmer
1.716
970545AG2-347 GEN
Solar/Wind Harmer
127.668
972069AH1-584 GEN
Solar/Wind Harmer
17.464
972071AH1-585 GEN
Solar/Wind Harmer
17.464
233901CHERRYDALE C
Solar/Wind Harmer
2.196
232408W1-005 C
Solar/Wind Harmer
1.953
232410W1-006 C
Solar/Wind Harmer
1.953
971747AH1-380 GEN
Solar/Wind Harmer
6.985
231940T-011
Adder
1.454
232899W1-062
Adder
18.729
233946AB2-136 GEN
Solar/Wind Harmer
7.758
234036AF2-325 C
Solar/Wind Harmer
1.782
234041AC1-190 GEN
Solar/Wind Harmer
17.388
233984AB2-036 GEN
Solar/Wind Harmer
23.783
232424Y1-079 C
Solar/Wind Harmer
1.073
234014AF1-036_GEN
Solar/Wind Harmer
5.117
233944AB2-135 GEN
Solar/Wind Harmer
9.831
233933AB2-153 GEN
Solar/Wind Harmer
2.106
231131BLOOM ENRGY
Adder
8.138
232416X2-083
Adder
0.783
230422AE1-104_GEN1
Solar/Wind Harmer
37.145
230425AE1-104_GEN2
Solar/Wind Harmer
37.145
228251CARLLS#4
Adder
0.694
230433AD2-135 GEN
Solar/Wind Harmer
0.109
230407AD2-065 C
Solar/Wind Harmer
0.136
228307PCLP GT
Adder
12.166
228304LOGAN
Adder
23.826
972233AH1-701 GEN
Adder
4.051
219921AF1-264
Solar/Wind Harmer
0.121
207500AE2-000G1
Solar/Wind Harmer
24.229
207497AE2-000G2
Solar/Wind Harmer
24.229
207507AE2-000G3
Solar/Wind Harmer
24.229
20636128O CRK C2
Adder
4.957
20716428NHV_W2-082
Solar/Wind Harmer
1.348
963401AG1-189 GEN
Solar/Wind Harmer
0.869
219615MILLCREEK C
Solar/Wind Harmer
0.179
200200DELTA2 CT1
50/50
9.773
200193DELTA CT2
50/50
5.461
200203Y1-065-STG
50/50
18.368
200055ROCKSP 4
50/50
6.615
231914HR8
50/50
4.38
231911HR5
50/50
2.882
232914OH NUG3
50/50
18.276
232916OH NUG5
50/50
18.276
232921TASLEY2G
50/50
10.681
234034AF2-060
50/50
3.655
232911NRG_G2
50/50
0.961
233971AC1-093 C
Solar/Wind Harmer
1.533
970695AG2-447 GEN
Solar/Wind Harmer
7.001
972133AH1-634 GEN
Solar/Wind Harmer
19.344
972073AH1-586 GEN
Solar/Wind Harmer
18.276
232406W1-004 FULL
Solar/Wind Harmer
1.953
233996TM1833_GEN
Solar/Wind Harmer
2.47
233997TMININ_4.2
Solar/Wind Harmer
2.47
233940AF2-379 C
Solar/Wind Harmer
0.364
233990AG1-397 GEN
Solar/Wind Harmer
2.236
232907VN8
Adder
58.535
233900O-025 C
Adder
2.295
234015AF2-250 C
Solar/Wind Harmer
0.235
233994AC2-023 GEN
Solar/Wind Harmer
5.238
960671AF2-358 GEN
Solar/Wind Harmer
34.843
232417X3-008 C
Solar/Wind Harmer
3.883
233952AC2-187 GEN
Solar/Wind Harmer
2.183
233918AB1-142 GEN
Solar/Wind Harmer
1.855
200192DELTA CT1
50/50
5.461
200194DELTA CT3
50/50
5.461
200204Y1-065-CTG1
50/50
10.592
200054ROCKSP 3
50/50
6.757
231912HR6
50/50
2.882
231913HR7
50/50
2.882
233920W3-032A-CTG1
50/50
4.302
233921W3-032A-STG1
50/50
2.584
232901NORTHST
50/50
17.274
232917OH NUG6
50/50
18.195
232915OH NUG4
50/50
18.154
232910NRG_G1
50/50
17.58
233972AC1-094 C
Solar/Wind Harmer
1.296
232434Z2-077 GEN
Solar/Wind Harmer
0.488
232404W1-003 C
Solar/Wind Harmer
1.953
233998TM1NIN_3.36
Solar/Wind Harmer
2.47
972177AH1-672 GEN
Solar/Wind Harmer
26.183
971195AH1-057 GEN
Solar/Wind Harmer
2.134
232428Y3-058 C
Solar/Wind Harmer
1.626
232900DEMECSMY
Adder
17.964
232919VN10
Adder
5.463
965821AG1-450 GEN
Solar/Wind Harmer
10.129
232426Y1-080 FULL
Solar/Wind Harmer
0.372
970277AG2-181 GEN
Solar/Wind Harmer
9.754
233964AF2-378 GEN
Solar/Wind Harmer
0.248
233954AC2-188 GEN
Solar/Wind Harmer
2.183
233950AC2-186 GEN
Solar/Wind Harmer
1.092
200202DELTA2 ST
50/50
16.585
200195DELTA ST
50/50
8.439
200052ROCKSP 1
50/50
6.69
200053ROCKSP 2
50/50
6.547
232616GEN FOOD
50/50
0.339
232904IR4
50/50
167.387
232920IR10
50/50
6.541
232912OH NUG1
50/50
18.276
232913OH NUG2
50/50
18.032
233973AC2-185 C
Solar/Wind Harmer
7.06
234033AF1-007_GEN
Solar/Wind Harmer
45.622
232432Z2-076 GEN
Solar/Wind Harmer
0.258
233923SMA
Solar/Wind Harmer
9.056
233990AG1-397 GEN
Solar/Wind Harmer
0.108
233955AB2-172 GEN
Solar/Wind Harmer
9.708
232813VAUGHN
Adder
1.134
233968AD2-076_GEN
Solar/Wind Harmer
12.537
970597AG2-380 GEN
Solar/Wind Harmer
7.872
232436AB1-176 C
Solar/Wind Harmer
0.432
231906DC3 NUG
Adder
26.221
231902DC CT7
Adder
20.962
231907DC10
Adder
6.546
971983AH1-536 GEN
Solar/Wind Harmer
14.01
233935AB2-179 C
Solar/Wind Harmer
4.441
231919CHRIST1
Adder
7.003
231920CHRIST2
Adder
6.847
970453AG2-297 GEN
Solar/Wind Harmer
3.221
228260V4-054C
Solar/Wind Harmer
1.13
972141AH1-641 GEN
Solar/Wind Harmer
3.084
227927V4-067C
Solar/Wind Harmer
0.213
228309CCLP NUG
Adder
27.623
228309CCLP NUG
Adder
26.275
228754AB1-001 C
Solar/Wind Harmer
0.149
964001AG1-254 GEN
Solar/Wind Harmer
2.15
971535AH1-265 GEN
Solar/Wind Harmer
4.479
971011AG2-627 GEN
Solar/Wind Harmer
7.893
219272CLEANLIGHT C
Solar/Wind Harmer
0.162
219137THOSOLAR C
Solar/Wind Harmer
1.066
213589EDDYSTN4
Adder
59.162
213587EDDYSTN3
Adder
59.07
963391AG1-188 GEN
Solar/Wind Harmer
1.434
213535CROYDN11
Adder
7.309
20714928UPF_X1-085
Solar/Wind Harmer
0.291
20628028LAKEHURS
Adder
0.682
219114HARTZY_C
Solar/Wind Harmer
0.535
20720628TIN_W1-124
Solar/Wind Harmer
0.628
20641628MLH_W1-032
Solar/Wind Harmer
0.183
219817TRENTONSOL C
Solar/Wind Harmer
0.636
20716928W4-060COL
Solar/Wind Harmer
0.412
924131AB2-057 GEN
Solar/Wind Harmer
0.534
218440SUMMTASSOC C
Solar/Wind Harmer
0.064
218418LINDEN_G5
Adder
8.267
218419LINDEN_G6
Adder
8.267
972260AH1-715 GEN1
Adder
6.62
234012AE2-112_GEN
Solar/Wind Harmer
4.349
232422X3-066 FULL
Solar/Wind Harmer
0.472
233930AB2-032 GEN
Solar/Wind Harmer
1.561
233915AB1-141 GEN
Solar/Wind Harmer
1.855
231918WEST 1
Adder
5.369
231917EM10
Adder
3.586
228206SHRMN CT
Adder
18.897
228732V1-021 C
Adder
0.214
945431AF1-208 GEN
Solar/Wind Harmer
9.398
970997AG2-616 GEN
Solar/Wind Harmer
10.281
230511AF1-262
Solar/Wind Harmer
0.194
228728W1-130C
Solar/Wind Harmer
0.702
228351V2-046C
Solar/Wind Harmer
2.126
230434AG1-499 GEN
Solar/Wind Harmer
0.589
218660EHAMPSOLAR C
Solar/Wind Harmer
0.155
219686LUMSOLAR_N C
Solar/Wind Harmer
0.179
219287REEVESEAST C
Solar/Wind Harmer
1.19
219258KINSLEYDEP C
Solar/Wind Harmer
0.274
219904AC1-010 C
Solar/Wind Harmer
0.31
219907AC1-030 C
Solar/Wind Harmer
0.107
207487AE2-000G4
Solar/Wind Harmer
24.229
213497CHSTR7-9
Adder
2.06
213497CHSTR7-9
Adder
2.06
20720728JCB_W1-129
Solar/Wind Harmer
0.226
207522AF2-254 C
Solar/Wind Harmer
1.087
219304NAMERICA C
Solar/Wind Harmer
0.228
219222BRL12CT2
Adder
6.542
207445AB1-138_GEN
Solar/Wind Harmer
0.416
20628028LAKEHURS
Adder
1.349
963711AG1-223 GEN
Solar/Wind Harmer
1.005
20714828MDF_W3-079
Solar/Wind Harmer
0.207
213611FALLS1-3
Adder
2.308
213958STHWK5-6
Adder
1.752
207454AA2-184 E
Solar/Wind Harmer
0.63
213560DLW11-12
Adder
1.671
20715228NPK_W1-113
Solar/Wind Harmer
0.265
20742028HF_AC1-207
Solar/Wind Harmer
0.479
219680HOPEWELLV C1
Solar/Wind Harmer
0.043
217197RE CRAN C
Solar/Wind Harmer
0.293
20635828PARLN1&2
Adder
4.065
20635028RRCT1&2
Adder
6.201
20635128RRCT3&4
Adder
5.986
218428ETC SOLAR C
Solar/Wind Harmer
0.018
217213AMBOY SO C
Solar/Wind Harmer
0.062
972275AH1-722 GEN
Adder
15.198
233982AB2-133 GEN
Solar/Wind Harmer
9.098
972251AH1-710 GEN
Adder
79.357
228202CUMB CT
Adder
19.025
228711V2-041C
Solar/Wind Harmer
0.688
971553AH1-274 GEN
Solar/Wind Harmer
2.719
228729W2-030 C
Solar/Wind Harmer
0.621
230430AE1-229_GEN
Solar/Wind Harmer
9.407
230415AB2-049 C
Solar/Wind Harmer
0.199
228304LOGAN
Adder
21.429
219291REEVESSOUT C
Solar/Wind Harmer
0.054
219623KINSLEYBEA C
Solar/Wind Harmer
0.368
219766PARADISE C
Solar/Wind Harmer
0.258
219912AD2-042 GEN
Solar/Wind Harmer
0.628
219236SOUTHERNHQ C
Solar/Wind Harmer
0.052
20636028O CRK C1
Adder
5.436
213497CHSTR7-9
Adder
2.06
20716028EGP_W2-019
Solar/Wind Harmer
0.352
20720828JCB_W4-025
Solar/Wind Harmer
0.344
20715028HAN_X4-015
Solar/Wind Harmer
0.226
219906AC1-017 C
Solar/Wind Harmer
0.167
219610FLORENCE C
Solar/Wind Harmer
1.015
219348LDSOLAR C
Solar/Wind Harmer
0.439
219221BRL12CT1
Adder
6.542
219223BRL12CT3
Adder
6.542
971667AH1-334 GEN
Solar/Wind Harmer
1.99
959561AF2-247 GEN
Solar/Wind Harmer
0.332
20714528FRN_Y2-051
Solar/Wind Harmer
0.2
213958STHWK5-6
Adder
1.752
219727YARDVSOLFA C
Solar/Wind Harmer
0.572
213560DLW11-12
Adder
1.671
20720528MAN_W1-024
Solar/Wind Harmer
0.157
20716228APLW2-078
Solar/Wind Harmer
0.544
219276PARKLANDSO C
Solar/Wind Harmer
0.278
967451AG2-055 C O1
Solar/Wind Harmer
102.144
219918AC2-009 C
Solar/Wind Harmer
0.035
219612MATRIX C
Solar/Wind Harmer
0.101
218438BLK ROCK C
Solar/Wind Harmer
0.074
20635828PARLN1&2
Adder
1.841
20635928PARLN3&4
Adder
1.841
20635028RRCT1&2
Adder
6.298
20635128RRCT3&4
Adder
5.221
219908AB1-139 C
Solar/Wind Harmer
0.188
219919AE1-041 FULL
Solar/Wind Harmer
0.02
219688LUMSOLAR_S C
Solar/Wind Harmer
0.176
219914AD2-027 C
Solar/Wind Harmer
0.473
20717128DIX_Z2-102
Solar/Wind Harmer
0.998
20715728PEM_W1-119
Solar/Wind Harmer
0.403
20715828PEM_W1-120
Solar/Wind Harmer
0.403
970025AG2-016 GEN
Solar/Wind Harmer
2.123
219607WPEMNERT C
Solar/Wind Harmer
0.307
219224BRL12CT4
Adder
6.542
971189AH1-054 GEN
Solar/Wind Harmer
0.869
207459AE1-142 C O1
Solar/Wind Harmer
0.769
214067T20SOLAR
Solar/Wind Harmer
0.165
213611FALLS1-3
Adder
2.308
213611FALLS1-3
Adder
2.308
213942SCHUYLKILL
Adder
2.292
213942SCHUYLKILL
Adder
1.753
213957STHWK3-4
Adder
1.752
213957STHWK3-4
Adder
1.752
20714328BYD_X4-031
Solar/Wind Harmer
0.182
20714428HOW_X1-037
Solar/Wind Harmer
0.788
213561DLWR9-10
Adder
2.185
213561DLWR9-10
Adder
1.671
971521AH1-258 GEN
Solar/Wind Harmer
1.644
20720428HOL_W1-112
Solar/Wind Harmer
0.208
219620RIDERU C
Solar/Wind Harmer
0.032
20635928PARLN3&4
Adder
4.065
218455CINNBAY_CGEN
Adder
0.944
218526CNTRALGAS2 C
Solar/Wind Harmer
0.187
218524CNTRALGAS1 C
Solar/Wind Harmer
0.186
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.332
G-007ALTFEXP_G-007A->PJM
CMTX
27.389
CBM NorthLTFEXP_CBM-N->PJM
CBM
22.771
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
3.049
BlueGrassPJM->LTFIMP_BlueG
CLTF
9.494
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
60.337
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.002
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
14.209

Details for PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line l/o PJM_500_BG_P4_5_CNSTN_B_SRT-A


Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line
Contingency Name:
PJM_500_BG_P4_5_CNSTN_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:149.31 %
Rating:2860.0 MVA
Rating Type:B
MVA to Mitigate:4270.16
MW Contribution:7.9
Bus #Bus NameTypeMW Contribution
200201DELTA2 CT2
50/50
9.776
200034PCHBTM 2
50/50
56.834
200205Y1-065-CTG2
50/50
10.596
232918OH NUG7
50/50
18.167
232905CHERITON_25
50/50
5.08
232926CRISFLD1
50/50
4.064
200035PCHBTM 3
50/50
-13.921
971149AH1-027 GEN
Solar/Wind Harmer
6.625
233987AB2-037 GEN
Solar/Wind Harmer
22.279
233939AC1-091 C
Solar/Wind Harmer
1.718
233970AC1-092 C
Solar/Wind Harmer
1.718
970545AG2-347 GEN
Solar/Wind Harmer
127.755
972069AH1-584 GEN
Solar/Wind Harmer
17.476
972071AH1-585 GEN
Solar/Wind Harmer
17.476
233901CHERRYDALE C
Solar/Wind Harmer
2.197
232408W1-005 C
Solar/Wind Harmer
1.954
232410W1-006 C
Solar/Wind Harmer
1.954
971747AH1-380 GEN
Solar/Wind Harmer
6.99
200192DELTA CT1
50/50
5.463
200194DELTA CT3
50/50
5.463
200204Y1-065-CTG1
50/50
10.596
200054ROCKSP 3
50/50
6.759
231912HR6
50/50
2.884
231913HR7
50/50
2.884
233920W3-032A-CTG1
50/50
4.305
233921W3-032A-STG1
50/50
2.586
232901NORTHST
50/50
17.286
232917OH NUG6
50/50
18.207
232915OH NUG4
50/50
18.167
232910NRG_G1
50/50
17.593
233972AC1-094 C
Solar/Wind Harmer
1.297
232434Z2-077 GEN
Solar/Wind Harmer
0.489
232404W1-003 C
Solar/Wind Harmer
1.954
233998TM1NIN_3.36
Solar/Wind Harmer
2.472
972177AH1-672 GEN
Solar/Wind Harmer
26.2
971195AH1-057 GEN
Solar/Wind Harmer
2.135
232428Y3-058 C
Solar/Wind Harmer
1.627
232900DEMECSMY
Adder
17.976
232919VN10
Adder
5.467
965821AG1-450 GEN
Solar/Wind Harmer
10.136
232426Y1-080 FULL
Solar/Wind Harmer
0.372
970277AG2-181 GEN
Solar/Wind Harmer
9.76
233964AF2-378 GEN
Solar/Wind Harmer
0.248
233954AC2-188 GEN
Solar/Wind Harmer
2.185
233950AC2-186 GEN
Solar/Wind Harmer
1.092
234012AE2-112_GEN
Solar/Wind Harmer
4.353
232422X3-066 FULL
Solar/Wind Harmer
0.472
233930AB2-032 GEN
Solar/Wind Harmer
1.562
233915AB1-141 GEN
Solar/Wind Harmer
1.856
231918WEST 1
Adder
5.374
231917EM10
Adder
3.589
228206SHRMN CT
Adder
18.917
228732V1-021 C
Adder
0.214
945431AF1-208 GEN
Solar/Wind Harmer
9.409
970997AG2-616 GEN
Solar/Wind Harmer
10.293
230511AF1-262
Solar/Wind Harmer
0.195
228728W1-130C
Solar/Wind Harmer
0.703
228351V2-046C
Solar/Wind Harmer
2.128
230434AG1-499 GEN
Solar/Wind Harmer
0.59
218660EHAMPSOLAR C
Solar/Wind Harmer
0.156
219686LUMSOLAR_N C
Solar/Wind Harmer
0.179
219287REEVESEAST C
Solar/Wind Harmer
1.192
219258KINSLEYDEP C
Solar/Wind Harmer
0.274
219904AC1-010 C
Solar/Wind Harmer
0.31
219907AC1-030 C
Solar/Wind Harmer
0.107
207487AE2-000G4
Solar/Wind Harmer
24.267
213497CHSTR7-9
Adder
2.063
213497CHSTR7-9
Adder
2.063
20720728JCB_W1-129
Solar/Wind Harmer
0.227
207522AF2-254 C
Solar/Wind Harmer
1.088
219304NAMERICA C
Solar/Wind Harmer
0.228
219222BRL12CT2
Adder
6.554
207445AB1-138_GEN
Solar/Wind Harmer
0.416
20628028LAKEHURS
Adder
1.351
963711AG1-223 GEN
Solar/Wind Harmer
1.006
20714828MDF_W3-079
Solar/Wind Harmer
0.208
213611FALLS1-3
Adder
2.312
213958STHWK5-6
Adder
1.756
207454AA2-184 E
Solar/Wind Harmer
0.631
213560DLW11-12
Adder
1.675
20715228NPK_W1-113
Solar/Wind Harmer
0.265
20742028HF_AC1-207
Solar/Wind Harmer
0.48
219680HOPEWELLV C1
Solar/Wind Harmer
0.043
217197RE CRAN C
Solar/Wind Harmer
0.294
20635828PARLN1&2
Adder
4.074
20635028RRCT1&2
Adder
6.215
20635128RRCT3&4
Adder
5.999
218428ETC SOLAR C
Solar/Wind Harmer
0.018
217213AMBOY SO C
Solar/Wind Harmer
0.062
972275AH1-722 GEN
Adder
15.237
200200DELTA2 CT1
50/50
9.776
200193DELTA CT2
50/50
5.463
200203Y1-065-STG
50/50
18.374
200055ROCKSP 4
50/50
6.617
231914HR8
50/50
4.383
231911HR5
50/50
2.884
232914OH NUG3
50/50
18.289
232916OH NUG5
50/50
18.289
232921TASLEY2G
50/50
10.689
234034AF2-060
50/50
3.658
232911NRG_G2
50/50
0.962
233971AC1-093 C
Solar/Wind Harmer
1.534
970695AG2-447 GEN
Solar/Wind Harmer
7.005
972133AH1-634 GEN
Solar/Wind Harmer
19.357
972073AH1-586 GEN
Solar/Wind Harmer
18.289
232406W1-004 FULL
Solar/Wind Harmer
1.954
233996TM1833_GEN
Solar/Wind Harmer
2.472
233997TMININ_4.2
Solar/Wind Harmer
2.472
233940AF2-379 C
Solar/Wind Harmer
0.364
233990AG1-397 GEN
Solar/Wind Harmer
2.238
232907VN8
Adder
58.576
233900O-025 C
Adder
2.297
234015AF2-250 C
Solar/Wind Harmer
0.235
233994AC2-023 GEN
Solar/Wind Harmer
5.241
960671AF2-358 GEN
Solar/Wind Harmer
34.867
232417X3-008 C
Solar/Wind Harmer
3.886
233952AC2-187 GEN
Solar/Wind Harmer
2.185
233918AB1-142 GEN
Solar/Wind Harmer
1.856
233982AB2-133 GEN
Solar/Wind Harmer
9.105
972251AH1-710 GEN
Adder
79.414
228202CUMB CT
Adder
19.045
228711V2-041C
Solar/Wind Harmer
0.688
971553AH1-274 GEN
Solar/Wind Harmer
2.722
228729W2-030 C
Solar/Wind Harmer
0.622
230430AE1-229_GEN
Solar/Wind Harmer
9.418
230415AB2-049 C
Solar/Wind Harmer
0.2
228304LOGAN
Adder
21.456
219291REEVESSOUT C
Solar/Wind Harmer
0.054
219623KINSLEYBEA C
Solar/Wind Harmer
0.368
219766PARADISE C
Solar/Wind Harmer
0.258
219912AD2-042 GEN
Solar/Wind Harmer
0.629
219236SOUTHERNHQ C
Solar/Wind Harmer
0.052
20636028O CRK C1
Adder
5.445
213497CHSTR7-9
Adder
2.063
20716028EGP_W2-019
Solar/Wind Harmer
0.353
20720828JCB_W4-025
Solar/Wind Harmer
0.344
20715028HAN_X4-015
Solar/Wind Harmer
0.227
219906AC1-017 C
Solar/Wind Harmer
0.167
219610FLORENCE C
Solar/Wind Harmer
1.017
219348LDSOLAR C
Solar/Wind Harmer
0.44
219221BRL12CT1
Adder
6.554
219223BRL12CT3
Adder
6.554
971667AH1-334 GEN
Solar/Wind Harmer
1.993
959561AF2-247 GEN
Solar/Wind Harmer
0.333
20714528FRN_Y2-051
Solar/Wind Harmer
0.201
213958STHWK5-6
Adder
1.756
219727YARDVSOLFA C
Solar/Wind Harmer
0.573
213560DLW11-12
Adder
1.675
20720528MAN_W1-024
Solar/Wind Harmer
0.158
20716228APLW2-078
Solar/Wind Harmer
0.545
219276PARKLANDSO C
Solar/Wind Harmer
0.278
967451AG2-055 C O1
Solar/Wind Harmer
102.353
219918AC2-009 C
Solar/Wind Harmer
0.035
219612MATRIX C
Solar/Wind Harmer
0.101
218438BLK ROCK C
Solar/Wind Harmer
0.075
20635828PARLN1&2
Adder
1.845
20635928PARLN3&4
Adder
1.845
20635028RRCT1&2
Adder
6.312
20635128RRCT3&4
Adder
5.233
219908AB1-139 C
Solar/Wind Harmer
0.188
219919AE1-041 FULL
Solar/Wind Harmer
0.02
231940T-011
Adder
1.455
232899W1-062
Adder
18.741
233946AB2-136 GEN
Solar/Wind Harmer
7.763
234036AF2-325 C
Solar/Wind Harmer
1.783
234041AC1-190 GEN
Solar/Wind Harmer
17.4
233984AB2-036 GEN
Solar/Wind Harmer
23.8
232424Y1-079 C
Solar/Wind Harmer
1.074
234014AF1-036_GEN
Solar/Wind Harmer
5.121
233944AB2-135 GEN
Solar/Wind Harmer
9.839
233933AB2-153 GEN
Solar/Wind Harmer
2.107
231131BLOOM ENRGY
Adder
8.144
232416X2-083
Adder
0.783
230422AE1-104_GEN1
Solar/Wind Harmer
37.186
230425AE1-104_GEN2
Solar/Wind Harmer
37.186
228251CARLLS#4
Adder
0.695
230433AD2-135 GEN
Solar/Wind Harmer
0.109
230407AD2-065 C
Solar/Wind Harmer
0.137
228307PCLP GT
Adder
12.181
228304LOGAN
Adder
23.856
972233AH1-701 GEN
Adder
4.056
219921AF1-264
Solar/Wind Harmer
0.122
207500AE2-000G1
Solar/Wind Harmer
24.267
207497AE2-000G2
Solar/Wind Harmer
24.267
207507AE2-000G3
Solar/Wind Harmer
24.267
20636128O CRK C2
Adder
4.965
20716428NHV_W2-082
Solar/Wind Harmer
1.35
963401AG1-189 GEN
Solar/Wind Harmer
0.871
219615MILLCREEK C
Solar/Wind Harmer
0.179
213589EDDYSTN4
Adder
59.272
213587EDDYSTN3
Adder
59.179
963391AG1-188 GEN
Solar/Wind Harmer
1.436
213535CROYDN11
Adder
7.322
20714928UPF_X1-085
Solar/Wind Harmer
0.292
20628028LAKEHURS
Adder
0.683
219114HARTZY_C
Solar/Wind Harmer
0.536
20720628TIN_W1-124
Solar/Wind Harmer
0.629
20641628MLH_W1-032
Solar/Wind Harmer
0.183
219817TRENTONSOL C
Solar/Wind Harmer
0.637
20716928W4-060COL
Solar/Wind Harmer
0.412
924131AB2-057 GEN
Solar/Wind Harmer
0.535
218440SUMMTASSOC C
Solar/Wind Harmer
0.065
218418LINDEN_G5
Adder
8.288
218419LINDEN_G6
Adder
8.288
972260AH1-715 GEN1
Adder
6.637
200202DELTA2 ST
50/50
16.589
200195DELTA ST
50/50
8.441
200052ROCKSP 1
50/50
6.692
200053ROCKSP 2
50/50
6.549
232616GEN FOOD
50/50
0.339
232904IR4
50/50
167.502
232920IR10
50/50
6.546
232912OH NUG1
50/50
18.289
232913OH NUG2
50/50
18.045
233973AC2-185 C
Solar/Wind Harmer
7.065
234033AF1-007_GEN
Solar/Wind Harmer
45.653
232432Z2-076 GEN
Solar/Wind Harmer
0.258
233923SMA
Solar/Wind Harmer
9.062
233990AG1-397 GEN
Solar/Wind Harmer
0.108
233955AB2-172 GEN
Solar/Wind Harmer
9.715
232813VAUGHN
Adder
1.135
233968AD2-076_GEN
Solar/Wind Harmer
12.546
970597AG2-380 GEN
Solar/Wind Harmer
7.878
232436AB1-176 C
Solar/Wind Harmer
0.433
231906DC3 NUG
Adder
26.24
231902DC CT7
Adder
20.977
231907DC10
Adder
6.551
971983AH1-536 GEN
Solar/Wind Harmer
14.02
233935AB2-179 C
Solar/Wind Harmer
4.445
231919CHRIST1
Adder
7.009
231920CHRIST2
Adder
6.854
970453AG2-297 GEN
Solar/Wind Harmer
3.224
228260V4-054C
Solar/Wind Harmer
1.131
972141AH1-641 GEN
Solar/Wind Harmer
3.088
227927V4-067C
Solar/Wind Harmer
0.213
228309CCLP NUG
Adder
27.655
228309CCLP NUG
Adder
26.306
228754AB1-001 C
Solar/Wind Harmer
0.149
964001AG1-254 GEN
Solar/Wind Harmer
2.153
971535AH1-265 GEN
Solar/Wind Harmer
4.484
971011AG2-627 GEN
Solar/Wind Harmer
7.902
219272CLEANLIGHT C
Solar/Wind Harmer
0.162
219137THOSOLAR C
Solar/Wind Harmer
1.067
219688LUMSOLAR_S C
Solar/Wind Harmer
0.176
219914AD2-027 C
Solar/Wind Harmer
0.474
20717128DIX_Z2-102
Solar/Wind Harmer
0.999
20715728PEM_W1-119
Solar/Wind Harmer
0.403
20715828PEM_W1-120
Solar/Wind Harmer
0.403
970025AG2-016 GEN
Solar/Wind Harmer
2.126
219607WPEMNERT C
Solar/Wind Harmer
0.308
219224BRL12CT4
Adder
6.554
971189AH1-054 GEN
Solar/Wind Harmer
0.871
207459AE1-142 C O1
Solar/Wind Harmer
0.771
214067T20SOLAR
Solar/Wind Harmer
0.165
213611FALLS1-3
Adder
2.312
213611FALLS1-3
Adder
2.312
213942SCHUYLKILL
Adder
2.297
213942SCHUYLKILL
Adder
1.756
213957STHWK3-4
Adder
1.756
213957STHWK3-4
Adder
1.756
20714328BYD_X4-031
Solar/Wind Harmer
0.182
20714428HOW_X1-037
Solar/Wind Harmer
0.79
213561DLWR9-10
Adder
2.19
213561DLWR9-10
Adder
1.675
971521AH1-258 GEN
Solar/Wind Harmer
1.648
20720428HOL_W1-112
Solar/Wind Harmer
0.208
219620RIDERU C
Solar/Wind Harmer
0.032
20635928PARLN3&4
Adder
4.074
218455CINNBAY_CGEN
Adder
0.946
218526CNTRALGAS2 C
Solar/Wind Harmer
0.187
218524CNTRALGAS1 C
Solar/Wind Harmer
0.187
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.337
G-007ALTFEXP_G-007A->PJM
CMTX
27.451
CBM NorthLTFEXP_CBM-N->PJM
CBM
22.849
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
3.055
BlueGrassPJM->LTFIMP_BlueG
CLTF
9.512
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
60.502
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.005
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
14.235

Details for PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line l/o PECO_P4_PEACH235_SRT-A/* $ CHESCO $ PECO_P4_PEACH235 $ STBK


Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line
Contingency Name:
PECO_P4_PEACH235_SRT-A/* $ CHESCO $ PECO_P4_PEACH235 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:149.28 %
Rating:2860.0 MVA
Rating Type:B
MVA to Mitigate:4269.47
MW Contribution:7.88
Bus #Bus NameTypeMW Contribution
200200DELTA2 CT1
50/50
9.777
200193DELTA CT2
50/50
5.463
200203Y1-065-STG
50/50
18.336
200055ROCKSP 4
50/50
6.603
231914HR8
50/50
4.372
231911HR5
50/50
2.877
232914OH NUG3
50/50
18.244
232916OH NUG5
50/50
18.244
234034AF2-060
50/50
3.649
232921TASLEY2G
50/50
10.663
200192DELTA CT1
50/50
5.463
200194DELTA CT3
50/50
5.463
200204Y1-065-CTG1
50/50
10.574
200054ROCKSP 3
50/50
6.745
231912HR6
50/50
2.877
231913HR7
50/50
2.877
233920W3-032A-CTG1
50/50
4.295
233921W3-032A-STG1
50/50
2.579
232901NORTHST
50/50
17.244
232917OH NUG6
50/50
18.163
232915OH NUG4
50/50
18.122
232910NRG_G1
50/50
17.549
233972AC1-094 C
Solar/Wind Harmer
1.294
232434Z2-077 GEN
Solar/Wind Harmer
0.487
232404W1-003 C
Solar/Wind Harmer
1.95
233998TM1NIN_3.36
Solar/Wind Harmer
2.466
972177AH1-672 GEN
Solar/Wind Harmer
26.137
971195AH1-057 GEN
Solar/Wind Harmer
2.13
232428Y3-058 C
Solar/Wind Harmer
1.623
200202DELTA2 ST
50/50
16.591
200195DELTA ST
50/50
8.443
200052ROCKSP 1
50/50
6.678
200053ROCKSP 2
50/50
6.536
232616GEN FOOD
50/50
0.338
232904IR4
50/50
167.094
232920IR10
50/50
6.53
232912OH NUG1
50/50
18.244
232913OH NUG2
50/50
18.001
233973AC2-185 C
Solar/Wind Harmer
7.048
234033AF1-007_GEN
Solar/Wind Harmer
45.542
232432Z2-076 GEN
Solar/Wind Harmer
0.257
233923SMA
Solar/Wind Harmer
9.04
233990AG1-397 GEN
Solar/Wind Harmer
0.107
233955AB2-172 GEN
Solar/Wind Harmer
9.691
232813VAUGHN
Adder
1.132
233968AD2-076_GEN
Solar/Wind Harmer
12.515
970597AG2-380 GEN
Solar/Wind Harmer
7.858
232436AB1-176 C
Solar/Wind Harmer
0.431
231906DC3 NUG
Adder
26.175
231902DC CT7
Adder
20.925
231907DC10
Adder
6.534
971983AH1-536 GEN
Solar/Wind Harmer
13.985
233935AB2-179 C
Solar/Wind Harmer
4.434
231919CHRIST1
Adder
6.991
231920CHRIST2
Adder
6.835
970453AG2-297 GEN
Solar/Wind Harmer
3.215
232911NRG_G2
50/50
0.96
233971AC1-093 C
Solar/Wind Harmer
1.53
970695AG2-447 GEN
Solar/Wind Harmer
6.988
972133AH1-634 GEN
Solar/Wind Harmer
19.31
972073AH1-586 GEN
Solar/Wind Harmer
18.244
232406W1-004 FULL
Solar/Wind Harmer
1.95
233996TM1833_GEN
Solar/Wind Harmer
2.466
233997TMININ_4.2
Solar/Wind Harmer
2.466
233940AF2-379 C
Solar/Wind Harmer
0.363
233990AG1-397 GEN
Solar/Wind Harmer
2.233
232907VN8
Adder
58.432
233900O-025 C
Adder
2.291
234015AF2-250 C
Solar/Wind Harmer
0.234
233994AC2-023 GEN
Solar/Wind Harmer
5.228
960671AF2-358 GEN
Solar/Wind Harmer
34.782
232417X3-008 C
Solar/Wind Harmer
3.877
233952AC2-187 GEN
Solar/Wind Harmer
2.18
233918AB1-142 GEN
Solar/Wind Harmer
1.851
233982AB2-133 GEN
Solar/Wind Harmer
9.082
972251AH1-710 GEN
Adder
79.218
228202CUMB CT
Adder
18.991
228711V2-041C
Solar/Wind Harmer
0.686
971553AH1-274 GEN
Solar/Wind Harmer
2.714
228729W2-030 C
Solar/Wind Harmer
0.62
230430AE1-229_GEN
Solar/Wind Harmer
9.39
230415AB2-049 C
Solar/Wind Harmer
0.199
228304LOGAN
Adder
21.39
219291REEVESSOUT C
Solar/Wind Harmer
0.054
219623KINSLEYBEA C
Solar/Wind Harmer
0.367
219766PARADISE C
Solar/Wind Harmer
0.257
219912AD2-042 GEN
Solar/Wind Harmer
0.627
219236SOUTHERNHQ C
Solar/Wind Harmer
0.052
20636028O CRK C1
Adder
5.427
213497CHSTR7-9
Adder
2.056
20716028EGP_W2-019
Solar/Wind Harmer
0.352
20720828JCB_W4-025
Solar/Wind Harmer
0.343
20715028HAN_X4-015
Solar/Wind Harmer
0.226
219906AC1-017 C
Solar/Wind Harmer
0.167
219610FLORENCE C
Solar/Wind Harmer
1.014
219348LDSOLAR C
Solar/Wind Harmer
0.438
219221BRL12CT1
Adder
6.531
219223BRL12CT3
Adder
6.531
971667AH1-334 GEN
Solar/Wind Harmer
1.986
959561AF2-247 GEN
Solar/Wind Harmer
0.331
20714528FRN_Y2-051
Solar/Wind Harmer
0.2
213958STHWK5-6
Adder
1.749
219727YARDVSOLFA C
Solar/Wind Harmer
0.571
213560DLW11-12
Adder
1.668
20720528MAN_W1-024
Solar/Wind Harmer
0.157
20716228APLW2-078
Solar/Wind Harmer
0.543
219276PARKLANDSO C
Solar/Wind Harmer
0.277
967451AG2-055 C O1
Solar/Wind Harmer
101.957
219918AC2-009 C
Solar/Wind Harmer
0.035
219612MATRIX C
Solar/Wind Harmer
0.1
218438BLK ROCK C
Solar/Wind Harmer
0.074
20635828PARLN1&2
Adder
1.838
20635928PARLN3&4
Adder
1.838
20635028RRCT1&2
Adder
6.286
20635128RRCT3&4
Adder
5.212
219908AB1-139 C
Solar/Wind Harmer
0.188
219919AE1-041 FULL
Solar/Wind Harmer
0.02
200201DELTA2 CT2
50/50
9.777
200034PCHBTM 2
50/50
56.719
200205Y1-065-CTG2
50/50
10.574
232918OH NUG7
50/50
18.122
232905CHERITON_25
50/50
5.068
232926CRISFLD1
50/50
4.054
200035PCHBTM 3
50/50
-13.914
971149AH1-027 GEN
Solar/Wind Harmer
6.609
233987AB2-037 GEN
Solar/Wind Harmer
22.225
233939AC1-091 C
Solar/Wind Harmer
1.713
233970AC1-092 C
Solar/Wind Harmer
1.713
970545AG2-347 GEN
Solar/Wind Harmer
127.444
972069AH1-584 GEN
Solar/Wind Harmer
17.433
972071AH1-585 GEN
Solar/Wind Harmer
17.433
233901CHERRYDALE C
Solar/Wind Harmer
2.192
232408W1-005 C
Solar/Wind Harmer
1.95
232410W1-006 C
Solar/Wind Harmer
1.95
971747AH1-380 GEN
Solar/Wind Harmer
6.973
231940T-011
Adder
1.451
232899W1-062
Adder
18.696
233946AB2-136 GEN
Solar/Wind Harmer
7.744
234036AF2-325 C
Solar/Wind Harmer
1.778
234041AC1-190 GEN
Solar/Wind Harmer
17.357
233984AB2-036 GEN
Solar/Wind Harmer
23.741
232424Y1-079 C
Solar/Wind Harmer
1.071
234014AF1-036_GEN
Solar/Wind Harmer
5.108
233944AB2-135 GEN
Solar/Wind Harmer
9.814
233933AB2-153 GEN
Solar/Wind Harmer
2.102
231131BLOOM ENRGY
Adder
8.123
232416X2-083
Adder
0.781
230422AE1-104_GEN1
Solar/Wind Harmer
37.079
230425AE1-104_GEN2
Solar/Wind Harmer
37.079
228251CARLLS#4
Adder
0.693
230433AD2-135 GEN
Solar/Wind Harmer
0.108
230407AD2-065 C
Solar/Wind Harmer
0.136
228307PCLP GT
Adder
12.144
228304LOGAN
Adder
23.783
972233AH1-701 GEN
Adder
4.043
219921AF1-264
Solar/Wind Harmer
0.121
207500AE2-000G1
Solar/Wind Harmer
24.185
207497AE2-000G2
Solar/Wind Harmer
24.185
207507AE2-000G3
Solar/Wind Harmer
24.185
20636128O CRK C2
Adder
4.948
20716428NHV_W2-082
Solar/Wind Harmer
1.346
963401AG1-189 GEN
Solar/Wind Harmer
0.868
219615MILLCREEK C
Solar/Wind Harmer
0.178
213589EDDYSTN4
Adder
59.056
213587EDDYSTN3
Adder
58.963
963391AG1-188 GEN
Solar/Wind Harmer
1.431
213535CROYDN11
Adder
7.296
20714928UPF_X1-085
Solar/Wind Harmer
0.291
20628028LAKEHURS
Adder
0.68
219114HARTZY_C
Solar/Wind Harmer
0.534
20720628TIN_W1-124
Solar/Wind Harmer
0.627
20641628MLH_W1-032
Solar/Wind Harmer
0.183
219817TRENTONSOL C
Solar/Wind Harmer
0.635
20716928W4-060COL
Solar/Wind Harmer
0.411
924131AB2-057 GEN
Solar/Wind Harmer
0.533
218440SUMMTASSOC C
Solar/Wind Harmer
0.064
218418LINDEN_G5
Adder
8.252
218419LINDEN_G6
Adder
8.252
972260AH1-715 GEN1
Adder
6.608
228260V4-054C
Solar/Wind Harmer
1.128
972141AH1-641 GEN
Solar/Wind Harmer
3.079
227927V4-067C
Solar/Wind Harmer
0.212
228309CCLP NUG
Adder
27.574
228309CCLP NUG
Adder
26.229
232900DEMECSMY
Adder
17.933
232919VN10
Adder
5.454
965821AG1-450 GEN
Solar/Wind Harmer
10.111
232426Y1-080 FULL
Solar/Wind Harmer
0.371
970277AG2-181 GEN
Solar/Wind Harmer
9.737
233964AF2-378 GEN
Solar/Wind Harmer
0.248
233954AC2-188 GEN
Solar/Wind Harmer
2.18
233950AC2-186 GEN
Solar/Wind Harmer
1.09
234012AE2-112_GEN
Solar/Wind Harmer
4.342
232422X3-066 FULL
Solar/Wind Harmer
0.471
233930AB2-032 GEN
Solar/Wind Harmer
1.558
233915AB1-141 GEN
Solar/Wind Harmer
1.851
231918WEST 1
Adder
5.359
231917EM10
Adder
3.579
228206SHRMN CT
Adder
18.864
228732V1-021 C
Adder
0.214
945431AF1-208 GEN
Solar/Wind Harmer
9.382
970997AG2-616 GEN
Solar/Wind Harmer
10.263
230511AF1-262
Solar/Wind Harmer
0.194
228728W1-130C
Solar/Wind Harmer
0.701
228351V2-046C
Solar/Wind Harmer
2.122
230434AG1-499 GEN
Solar/Wind Harmer
0.588
218660EHAMPSOLAR C
Solar/Wind Harmer
0.155
219686LUMSOLAR_N C
Solar/Wind Harmer
0.179
219287REEVESEAST C
Solar/Wind Harmer
1.188
219258KINSLEYDEP C
Solar/Wind Harmer
0.273
219904AC1-010 C
Solar/Wind Harmer
0.309
219907AC1-030 C
Solar/Wind Harmer
0.107
207487AE2-000G4
Solar/Wind Harmer
24.185
213497CHSTR7-9
Adder
2.056
213497CHSTR7-9
Adder
2.056
20720728JCB_W1-129
Solar/Wind Harmer
0.226
207522AF2-254 C
Solar/Wind Harmer
1.085
219304NAMERICA C
Solar/Wind Harmer
0.227
219222BRL12CT2
Adder
6.531
207445AB1-138_GEN
Solar/Wind Harmer
0.415
20628028LAKEHURS
Adder
1.346
963711AG1-223 GEN
Solar/Wind Harmer
1.003
20714828MDF_W3-079
Solar/Wind Harmer
0.207
213611FALLS1-3
Adder
2.304
213958STHWK5-6
Adder
1.749
207454AA2-184 E
Solar/Wind Harmer
0.629
213560DLW11-12
Adder
1.668
20715228NPK_W1-113
Solar/Wind Harmer
0.264
20742028HF_AC1-207
Solar/Wind Harmer
0.478
219680HOPEWELLV C1
Solar/Wind Harmer
0.043
217197RE CRAN C
Solar/Wind Harmer
0.293
20635828PARLN1&2
Adder
4.057
20635028RRCT1&2
Adder
6.19
20635128RRCT3&4
Adder
5.975
218428ETC SOLAR C
Solar/Wind Harmer
0.018
217213AMBOY SO C
Solar/Wind Harmer
0.062
972275AH1-722 GEN
Adder
15.17
228754AB1-001 C
Solar/Wind Harmer
0.149
964001AG1-254 GEN
Solar/Wind Harmer
2.147
971535AH1-265 GEN
Solar/Wind Harmer
4.471
971011AG2-627 GEN
Solar/Wind Harmer
7.879
219272CLEANLIGHT C
Solar/Wind Harmer
0.161
219137THOSOLAR C
Solar/Wind Harmer
1.064
219688LUMSOLAR_S C
Solar/Wind Harmer
0.175
219914AD2-027 C
Solar/Wind Harmer
0.473
20717128DIX_Z2-102
Solar/Wind Harmer
0.996
20715728PEM_W1-119
Solar/Wind Harmer
0.402
20715828PEM_W1-120
Solar/Wind Harmer
0.402
970025AG2-016 GEN
Solar/Wind Harmer
2.119
219607WPEMNERT C
Solar/Wind Harmer
0.307
219224BRL12CT4
Adder
6.531
971189AH1-054 GEN
Solar/Wind Harmer
0.868
207459AE1-142 C O1
Solar/Wind Harmer
0.768
214067T20SOLAR
Solar/Wind Harmer
0.165
213611FALLS1-3
Adder
2.304
213611FALLS1-3
Adder
2.304
213942SCHUYLKILL
Adder
2.288
213942SCHUYLKILL
Adder
1.749
213957STHWK3-4
Adder
1.749
213957STHWK3-4
Adder
1.749
20714328BYD_X4-031
Solar/Wind Harmer
0.181
20714428HOW_X1-037
Solar/Wind Harmer
0.787
213561DLWR9-10
Adder
2.181
213561DLWR9-10
Adder
1.668
971521AH1-258 GEN
Solar/Wind Harmer
1.641
20720428HOL_W1-112
Solar/Wind Harmer
0.207
219620RIDERU C
Solar/Wind Harmer
0.032
20635928PARLN3&4
Adder
4.057
218455CINNBAY_CGEN
Adder
0.942
218526CNTRALGAS2 C
Solar/Wind Harmer
0.187
218524CNTRALGAS1 C
Solar/Wind Harmer
0.186
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.327
G-007ALTFEXP_G-007A->PJM
CMTX
27.338
CBM NorthLTFEXP_CBM-N->PJM
CBM
22.725
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
3.044
BlueGrassPJM->LTFIMP_BlueG
CLTF
9.48
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
60.224
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.999
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
14.188

Details for PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line l/o PECO_P1-2_5012_SRT-A


Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line
Contingency Name:
PECO_P1-2_5012_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:133.85 %
Rating:2860.0 MVA
Rating Type:B
MVA to Mitigate:3828.03
MW Contribution:5.51
Bus #Bus NameTypeMW Contribution
200201DELTA2 CT2
50/50
9.773
200034PCHBTM 2
50/50
56.818
200205Y1-065-CTG2
50/50
10.592
232918OH NUG7
50/50
18.154
232905CHERITON_25
50/50
5.077
232926CRISFLD1
50/50
4.061
200035PCHBTM 3
50/50
-13.937
971149AH1-027 GEN
Solar/Wind Harmer
6.111
233987AB2-037 GEN
Solar/Wind Harmer
0.021
233939AC1-091 C
Solar/Wind Harmer
0.003
233970AC1-092 C
Solar/Wind Harmer
0.003
970545AG2-347 GEN
Solar/Wind Harmer
49.253
972069AH1-584 GEN
Solar/Wind Harmer
12.184
972071AH1-585 GEN
Solar/Wind Harmer
12.184
233901CHERRYDALE C
Solar/Wind Harmer
0.002
232408W1-005 C
Solar/Wind Harmer
1.263
232410W1-006 C
Solar/Wind Harmer
1.263
971747AH1-380 GEN
Solar/Wind Harmer
4.873
231940T-011
Adder
1.454
232899W1-062
Adder
18.729
233946AB2-136 GEN
Solar/Wind Harmer
0.008
234036AF2-325 C
Solar/Wind Harmer
0.001
234041AC1-190 GEN
Solar/Wind Harmer
14.153
233984AB2-036 GEN
Solar/Wind Harmer
13.88
232424Y1-079 C
Solar/Wind Harmer
0.001
234014AF1-036_GEN
Solar/Wind Harmer
4.395
233944AB2-135 GEN
Solar/Wind Harmer
0.009
233933AB2-153 GEN
Solar/Wind Harmer
0.002
231131BLOOM ENRGY
Adder
8.138
232416X2-083
Adder
0.783
230422AE1-104_GEN1
Solar/Wind Harmer
14.912
230425AE1-104_GEN2
Solar/Wind Harmer
14.912
228251CARLLS#4
Adder
0.694
230407AD2-065 C
Solar/Wind Harmer
0
228307PCLP GT
Adder
12.166
228304LOGAN
Adder
23.826
972233AH1-701 GEN
Adder
4.051
219921AF1-264
Solar/Wind Harmer
0
207500AE2-000G1
Solar/Wind Harmer
9.726
207497AE2-000G2
Solar/Wind Harmer
9.726
207507AE2-000G3
Solar/Wind Harmer
9.726
20636128O CRK C2
Adder
4.957
20716428NHV_W2-082
Solar/Wind Harmer
0
219615MILLCREEK C
Solar/Wind Harmer
0
213589EDDYSTN4
Adder
59.162
213587EDDYSTN3
Adder
59.07
213535CROYDN11
Adder
7.309
20714928UPF_X1-085
Solar/Wind Harmer
0
20628028LAKEHURS
Adder
0.682
219114HARTZY_C
Solar/Wind Harmer
0
20720628TIN_W1-124
Solar/Wind Harmer
0.001
20716928W4-060COL
Solar/Wind Harmer
0
218440SUMMTASSOC C
Solar/Wind Harmer
0
218418LINDEN_G5
Adder
8.267
218419LINDEN_G6
Adder
8.267
972260AH1-715 GEN1
Adder
6.62
200192DELTA CT1
50/50
5.461
200194DELTA CT3
50/50
5.461
200204Y1-065-CTG1
50/50
10.592
200054ROCKSP 3
50/50
6.757
231912HR6
50/50
2.882
231913HR7
50/50
2.882
233920W3-032A-CTG1
50/50
4.302
233921W3-032A-STG1
50/50
2.584
232901NORTHST
50/50
17.274
232917OH NUG6
50/50
18.195
232915OH NUG4
50/50
18.154
232910NRG_G1
50/50
17.58
233972AC1-094 C
Solar/Wind Harmer
0.615
232434Z2-077 GEN
Solar/Wind Harmer
0.082
232404W1-003 C
Solar/Wind Harmer
1.263
233998TM1NIN_3.36
Solar/Wind Harmer
0.003
972177AH1-672 GEN
Solar/Wind Harmer
19.85
971195AH1-057 GEN
Solar/Wind Harmer
1.218
232428Y3-058 C
Solar/Wind Harmer
0.003
232900DEMECSMY
Adder
17.964
232919VN10
Adder
5.463
965821AG1-450 GEN
Solar/Wind Harmer
10.129
232426Y1-080 FULL
Solar/Wind Harmer
0
970277AG2-181 GEN
Solar/Wind Harmer
1.134
233964AF2-378 GEN
Solar/Wind Harmer
0
233954AC2-188 GEN
Solar/Wind Harmer
0.002
233950AC2-186 GEN
Solar/Wind Harmer
0.001
234012AE2-112_GEN
Solar/Wind Harmer
4.395
232422X3-066 FULL
Solar/Wind Harmer
0.158
233930AB2-032 GEN
Solar/Wind Harmer
1.795
233915AB1-141 GEN
Solar/Wind Harmer
0.48
231918WEST 1
Adder
5.369
231917EM10
Adder
3.586
228206SHRMN CT
Adder
18.897
228732V1-021 C
Adder
0.214
945431AF1-208 GEN
Solar/Wind Harmer
6.557
970997AG2-616 GEN
Solar/Wind Harmer
7.735
230511AF1-262
Solar/Wind Harmer
0
228728W1-130C
Solar/Wind Harmer
0
228351V2-046C
Solar/Wind Harmer
0.001
230434AG1-499 GEN
Solar/Wind Harmer
0.001
218660EHAMPSOLAR C
Solar/Wind Harmer
0
219686LUMSOLAR_N C
Solar/Wind Harmer
0
219287REEVESEAST C
Solar/Wind Harmer
0
219258KINSLEYDEP C
Solar/Wind Harmer
0
219904AC1-010 C
Solar/Wind Harmer
0
219907AC1-030 C
Solar/Wind Harmer
0
207487AE2-000G4
Solar/Wind Harmer
9.726
213497CHSTR7-9
Adder
2.06
213497CHSTR7-9
Adder
2.06
20720728JCB_W1-129
Solar/Wind Harmer
0
207522AF2-254 C
Solar/Wind Harmer
0.702
219304NAMERICA C
Solar/Wind Harmer
0.067
219222BRL12CT2
Adder
6.542
207445AB1-138_GEN
Solar/Wind Harmer
0
20628028LAKEHURS
Adder
1.349
20714828MDF_W3-079
Solar/Wind Harmer
0.067
213611FALLS1-3
Adder
2.308
213958STHWK5-6
Adder
1.752
207454AA2-184 E
Solar/Wind Harmer
0.001
213560DLW11-12
Adder
1.671
20715228NPK_W1-113
Solar/Wind Harmer
0
20742028HF_AC1-207
Solar/Wind Harmer
0.001
217197RE CRAN C
Solar/Wind Harmer
0
20635828PARLN1&2
Adder
4.065
20635028RRCT1&2
Adder
6.201
20635128RRCT3&4
Adder
5.986
217213AMBOY SO C
Solar/Wind Harmer
0
972275AH1-722 GEN
Adder
15.198
200200DELTA2 CT1
50/50
9.773
200193DELTA CT2
50/50
5.461
200203Y1-065-STG
50/50
18.368
200055ROCKSP 4
50/50
6.615
231914HR8
50/50
4.38
231911HR5
50/50
2.882
232914OH NUG3
50/50
18.276
232916OH NUG5
50/50
18.276
232921TASLEY2G
50/50
10.681
234034AF2-060
50/50
3.655
232911NRG_G2
50/50
0.961
233971AC1-093 C
Solar/Wind Harmer
0.084
970695AG2-447 GEN
Solar/Wind Harmer
4.884
972133AH1-634 GEN
Solar/Wind Harmer
7.193
972073AH1-586 GEN
Solar/Wind Harmer
18.276
232406W1-004 FULL
Solar/Wind Harmer
1.263
233996TM1833_GEN
Solar/Wind Harmer
0.003
233997TMININ_4.2
Solar/Wind Harmer
0.003
233940AF2-379 C
Solar/Wind Harmer
0
233990AG1-397 GEN
Solar/Wind Harmer
2.655
232907VN8
Adder
58.535
233900O-025 C
Adder
2.295
234015AF2-250 C
Solar/Wind Harmer
0
233994AC2-023 GEN
Solar/Wind Harmer
0.008
960671AF2-358 GEN
Solar/Wind Harmer
24.309
232417X3-008 C
Solar/Wind Harmer
0.002
233952AC2-187 GEN
Solar/Wind Harmer
0.002
233918AB1-142 GEN
Solar/Wind Harmer
0.48
233982AB2-133 GEN
Solar/Wind Harmer
0.007
972251AH1-710 GEN
Adder
79.357
228202CUMB CT
Adder
19.025
228711V2-041C
Solar/Wind Harmer
0
971553AH1-274 GEN
Solar/Wind Harmer
1.753
228729W2-030 C
Solar/Wind Harmer
0.001
230430AE1-229_GEN
Solar/Wind Harmer
0.018
230415AB2-049 C
Solar/Wind Harmer
0
228304LOGAN
Adder
21.429
219623KINSLEYBEA C
Solar/Wind Harmer
0
219766PARADISE C
Solar/Wind Harmer
0
219912AD2-042 GEN
Solar/Wind Harmer
0.001
20636028O CRK C1
Adder
5.436
213497CHSTR7-9
Adder
2.06
20716028EGP_W2-019
Solar/Wind Harmer
0
20720828JCB_W4-025
Solar/Wind Harmer
0
20715028HAN_X4-015
Solar/Wind Harmer
0
219906AC1-017 C
Solar/Wind Harmer
0
219610FLORENCE C
Solar/Wind Harmer
0
219348LDSOLAR C
Solar/Wind Harmer
0
219221BRL12CT1
Adder
6.542
219223BRL12CT3
Adder
6.542
971667AH1-334 GEN
Solar/Wind Harmer
1.286
20714528FRN_Y2-051
Solar/Wind Harmer
0
213958STHWK5-6
Adder
1.752
219727YARDVSOLFA C
Solar/Wind Harmer
0
213560DLW11-12
Adder
1.671
20720528MAN_W1-024
Solar/Wind Harmer
0
20716228APLW2-078
Solar/Wind Harmer
0
219276PARKLANDSO C
Solar/Wind Harmer
0
967451AG2-055 C O1
Solar/Wind Harmer
145.919
219612MATRIX C
Solar/Wind Harmer
0
218438BLK ROCK C
Solar/Wind Harmer
0
20635828PARLN1&2
Adder
1.841
20635928PARLN3&4
Adder
1.841
20635028RRCT1&2
Adder
6.298
20635128RRCT3&4
Adder
5.221
219908AB1-139 C
Solar/Wind Harmer
0
200202DELTA2 ST
50/50
16.585
200195DELTA ST
50/50
8.439
200052ROCKSP 1
50/50
6.69
200053ROCKSP 2
50/50
6.547
232616GEN FOOD
50/50
0.339
232904IR4
50/50
167.387
232920IR10
50/50
6.541
232912OH NUG1
50/50
18.276
232913OH NUG2
50/50
18.032
233973AC2-185 C
Solar/Wind Harmer
0.003
234033AF1-007_GEN
Solar/Wind Harmer
-0.002
232432Z2-076 GEN
Solar/Wind Harmer
0.026
233923SMA
Solar/Wind Harmer
0.01
233990AG1-397 GEN
Solar/Wind Harmer
-0.31
233955AB2-172 GEN
Solar/Wind Harmer
0.006
232813VAUGHN
Adder
1.134
233968AD2-076_GEN
Solar/Wind Harmer
4.395
970597AG2-380 GEN
Solar/Wind Harmer
7.872
232436AB1-176 C
Solar/Wind Harmer
0
231906DC3 NUG
Adder
26.221
231902DC CT7
Adder
20.962
231907DC10
Adder
6.546
971983AH1-536 GEN
Solar/Wind Harmer
3.313
233935AB2-179 C
Solar/Wind Harmer
2.447
231919CHRIST1
Adder
7.003
231920CHRIST2
Adder
6.847
970453AG2-297 GEN
Solar/Wind Harmer
2.973
228260V4-054C
Solar/Wind Harmer
0
972141AH1-641 GEN
Solar/Wind Harmer
3.586
227927V4-067C
Solar/Wind Harmer
0
228309CCLP NUG
Adder
27.623
228309CCLP NUG
Adder
26.275
228754AB1-001 C
Solar/Wind Harmer
0
964001AG1-254 GEN
Solar/Wind Harmer
0.41
971535AH1-265 GEN
Solar/Wind Harmer
2.894
971011AG2-627 GEN
Solar/Wind Harmer
5.507
219272CLEANLIGHT C
Solar/Wind Harmer
0
219688LUMSOLAR_S C
Solar/Wind Harmer
0
219914AD2-027 C
Solar/Wind Harmer
0.001
20717128DIX_Z2-102
Solar/Wind Harmer
0
20715728PEM_W1-119
Solar/Wind Harmer
0
20715828PEM_W1-120
Solar/Wind Harmer
0
970025AG2-016 GEN
Solar/Wind Harmer
1.372
219607WPEMNERT C
Solar/Wind Harmer
0
219224BRL12CT4
Adder
6.542
971189AH1-054 GEN
Solar/Wind Harmer
0.562
207459AE1-142 C O1
Solar/Wind Harmer
0.001
214067T20SOLAR
Solar/Wind Harmer
0
213611FALLS1-3
Adder
2.308
213611FALLS1-3
Adder
2.308
213942SCHUYLKILL
Adder
2.292
213942SCHUYLKILL
Adder
1.753
213957STHWK3-4
Adder
1.752
213957STHWK3-4
Adder
1.752
20714328BYD_X4-031
Solar/Wind Harmer
0.098
20714428HOW_X1-037
Solar/Wind Harmer
0
213561DLWR9-10
Adder
2.185
213561DLWR9-10
Adder
1.671
971521AH1-258 GEN
Solar/Wind Harmer
1.063
20720428HOL_W1-112
Solar/Wind Harmer
0
20635928PARLN3&4
Adder
4.065
218455CINNBAY_CGEN
Adder
0.944
218526CNTRALGAS2 C
Solar/Wind Harmer
0.387
218524CNTRALGAS1 C
Solar/Wind Harmer
0.385
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.332
G-007ALTFEXP_G-007A->PJM
CMTX
27.389
CBM NorthLTFEXP_CBM-N->PJM
CBM
22.771
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
3.049
BlueGrassPJM->LTFIMP_BlueG
CLTF
9.494
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
60.337
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.002
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
14.209

Details for PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line l/o PECO_P4_PEACH245_SRT-A/* $ CHESCO $ PECO_P4_PEACH245 $ STBK


Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line
Contingency Name:
PECO_P4_PEACH245_SRT-A/* $ CHESCO $ PECO_P4_PEACH245 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.45 %
Rating:2860.0 MVA
Rating Type:B
MVA to Mitigate:3301.83
MW Contribution:8.11
Bus #Bus NameTypeMW Contribution
200034PCHBTM 2
50/50
57.256
200205Y1-065-CTG2
50/50
10.682
232918OH NUG7
50/50
18.429
232905CHERITON_25
50/50
5.154
232926CRISFLD1
50/50
4.123
231940T-011
50/50
1.566
232899W1-062
50/50
20.175
200035PCHBTM 3
50/50
-13.491
971149AH1-027 GEN
Solar/Wind Harmer
6.721
233987AB2-037 GEN
Solar/Wind Harmer
22.6
233939AC1-091 C
Solar/Wind Harmer
1.742
233970AC1-092 C
Solar/Wind Harmer
1.742
970545AG2-347 GEN
Solar/Wind Harmer
129.602
972069AH1-584 GEN
Solar/Wind Harmer
17.729
972071AH1-585 GEN
Solar/Wind Harmer
17.729
233901CHERRYDALE C
Solar/Wind Harmer
2.229
232408W1-005 C
Solar/Wind Harmer
1.983
232410W1-006 C
Solar/Wind Harmer
1.983
971747AH1-380 GEN
Solar/Wind Harmer
7.091
233946AB2-136 GEN
Solar/Wind Harmer
7.876
234036AF2-325 C
Solar/Wind Harmer
1.809
234041AC1-190 GEN
Solar/Wind Harmer
17.652
233984AB2-036 GEN
Solar/Wind Harmer
24.151
232424Y1-079 C
Solar/Wind Harmer
1.089
234014AF1-036_GEN
Solar/Wind Harmer
5.197
233944AB2-135 GEN
Solar/Wind Harmer
9.986
233933AB2-153 GEN
Solar/Wind Harmer
2.139
231131BLOOM ENRGY
Adder
8.266
232416X2-083
Adder
0.796
230422AE1-104_GEN1
Solar/Wind Harmer
38.076
230425AE1-104_GEN2
Solar/Wind Harmer
38.076
228251CARLLS#4
Adder
0.712
230433AD2-135 GEN
Solar/Wind Harmer
0.111
230407AD2-065 C
Solar/Wind Harmer
0.14
228307PCLP GT
Adder
12.5
228304LOGAN
Adder
24.495
972233AH1-701 GEN
Adder
4.167
219921AF1-264
Solar/Wind Harmer
0.125
207500AE2-000G1
Solar/Wind Harmer
25.108
207497AE2-000G2
Solar/Wind Harmer
25.108
207507AE2-000G3
Solar/Wind Harmer
25.108
20636128O CRK C2
Adder
5.137
20716428NHV_W2-082
Solar/Wind Harmer
1.398
963401AG1-189 GEN
Solar/Wind Harmer
0.901
219615MILLCREEK C
Solar/Wind Harmer
0.185
213589EDDYSTN4
Adder
61.367
213587EDDYSTN3
Adder
61.274
963391AG1-188 GEN
Solar/Wind Harmer
1.488
213535CROYDN11
Adder
7.593
20714928UPF_X1-085
Solar/Wind Harmer
0.303
20628028LAKEHURS
Adder
0.708
219114HARTZY_C
Solar/Wind Harmer
0.558
20720628TIN_W1-124
Solar/Wind Harmer
0.656
20641628MLH_W1-032
Solar/Wind Harmer
0.191
219817TRENTONSOL C
Solar/Wind Harmer
0.667
20716928W4-060COL
Solar/Wind Harmer
0.432
924131AB2-057 GEN
Solar/Wind Harmer
0.564
218440SUMMTASSOC C
Solar/Wind Harmer
0.068
218418LINDEN_G5
Adder
8.766
218419LINDEN_G6
Adder
8.766
972260AH1-715 GEN1
Adder
7.019
219036LINDEN_G7
Adder
8.264
219035LINDEN_G8
Adder
8.146
972261AH1-715 GEN2
Adder
7.911
217081WEATEXAS C
Solar/Wind Harmer
0.041
217202FBANKSOLAR C
Solar/Wind Harmer
0.035
200052ROCKSP 1
50/50
6.747
200053ROCKSP 2
50/50
6.602
232616GEN FOOD
50/50
0.344
232904IR4
50/50
169.923
232920IR10
50/50
6.64
232912OH NUG1
50/50
18.553
232913OH NUG2
50/50
18.306
232813VAUGHN
50/50
1.222
233973AC2-185 C
Solar/Wind Harmer
7.167
234033AF1-007_GEN
Solar/Wind Harmer
46.313
232432Z2-076 GEN
Solar/Wind Harmer
0.262
233923SMA
Solar/Wind Harmer
9.193
233990AG1-397 GEN
Solar/Wind Harmer
0.109
233955AB2-172 GEN
Solar/Wind Harmer
9.856
233968AD2-076_GEN
Solar/Wind Harmer
12.733
970597AG2-380 GEN
Solar/Wind Harmer
7.995
232436AB1-176 C
Solar/Wind Harmer
0.439
231906DC3 NUG
Adder
26.634
231902DC CT7
Adder
21.292
231907DC10
Adder
6.649
971983AH1-536 GEN
Solar/Wind Harmer
14.231
233935AB2-179 C
Solar/Wind Harmer
4.515
231919CHRIST1
Adder
7.133
231920CHRIST2
Adder
6.975
970453AG2-297 GEN
Solar/Wind Harmer
3.297
228260V4-054C
Solar/Wind Harmer
1.158
972141AH1-641 GEN
Solar/Wind Harmer
3.164
227927V4-067C
Solar/Wind Harmer
0.218
228309CCLP NUG
Adder
28.336
228309CCLP NUG
Adder
26.954
228754AB1-001 C
Solar/Wind Harmer
0.153
964001AG1-254 GEN
Solar/Wind Harmer
2.207
971535AH1-265 GEN
Solar/Wind Harmer
4.596
971011AG2-627 GEN
Solar/Wind Harmer
8.105
219272CLEANLIGHT C
Solar/Wind Harmer
0.167
219137THOSOLAR C
Solar/Wind Harmer
1.099
219688LUMSOLAR_S C
Solar/Wind Harmer
0.181
219914AD2-027 C
Solar/Wind Harmer
0.49
20717128DIX_Z2-102
Solar/Wind Harmer
1.034
20715728PEM_W1-119
Solar/Wind Harmer
0.418
20715828PEM_W1-120
Solar/Wind Harmer
0.418
970025AG2-016 GEN
Solar/Wind Harmer
2.202
219607WPEMNERT C
Solar/Wind Harmer
0.319
219224BRL12CT4
Adder
6.79
971189AH1-054 GEN
Solar/Wind Harmer
0.902
207459AE1-142 C O1
Solar/Wind Harmer
0.799
214067T20SOLAR
Solar/Wind Harmer
0.172
213611FALLS1-3
Adder
2.407
213611FALLS1-3
Adder
2.407
213942SCHUYLKILL
Adder
2.39
213942SCHUYLKILL
Adder
1.828
213957STHWK3-4
Adder
1.827
213957STHWK3-4
Adder
1.827
20714328BYD_X4-031
Solar/Wind Harmer
0.19
20714428HOW_X1-037
Solar/Wind Harmer
0.823
213561DLWR9-10
Adder
2.284
213561DLWR9-10
Adder
1.746
971521AH1-258 GEN
Solar/Wind Harmer
1.721
20720428HOL_W1-112
Solar/Wind Harmer
0.218
219620RIDERU C
Solar/Wind Harmer
0.034
20635928PARLN3&4
Adder
4.277
218455CINNBAY_CGEN
Adder
0.996
218526CNTRALGAS2 C
Solar/Wind Harmer
0.198
218524CNTRALGAS1 C
Solar/Wind Harmer
0.197
200204Y1-065-CTG1
50/50
10.682
200054ROCKSP 3
50/50
6.814
231912HR6
50/50
2.924
231913HR7
50/50
2.924
233920W3-032A-CTG1
50/50
4.367
233921W3-032A-STG1
50/50
2.623
232901NORTHST
50/50
17.535
232917OH NUG6
50/50
18.471
232915OH NUG4
50/50
18.429
232900DEMECSMY
50/50
19.352
232919VN10
50/50
5.885
232910NRG_G1
50/50
17.851
233972AC1-094 C
Solar/Wind Harmer
1.316
232434Z2-077 GEN
Solar/Wind Harmer
0.496
232404W1-003 C
Solar/Wind Harmer
1.983
233998TM1NIN_3.36
Solar/Wind Harmer
2.507
972177AH1-672 GEN
Solar/Wind Harmer
26.58
971195AH1-057 GEN
Solar/Wind Harmer
2.166
232428Y3-058 C
Solar/Wind Harmer
1.651
965821AG1-450 GEN
Solar/Wind Harmer
10.283
232426Y1-080 FULL
Solar/Wind Harmer
0.377
970277AG2-181 GEN
Solar/Wind Harmer
9.902
233964AF2-378 GEN
Solar/Wind Harmer
0.252
233954AC2-188 GEN
Solar/Wind Harmer
2.217
233950AC2-186 GEN
Solar/Wind Harmer
1.108
234012AE2-112_GEN
Solar/Wind Harmer
4.417
232422X3-066 FULL
Solar/Wind Harmer
0.479
233930AB2-032 GEN
Solar/Wind Harmer
1.586
233915AB1-141 GEN
Solar/Wind Harmer
1.884
231918WEST 1
Adder
5.468
231917EM10
Adder
3.655
228206SHRMN CT
Adder
19.354
228732V1-021 C
Adder
0.219
945431AF1-208 GEN
Solar/Wind Harmer
9.636
970997AG2-616 GEN
Solar/Wind Harmer
10.546
230511AF1-262
Solar/Wind Harmer
0.199
228728W1-130C
Solar/Wind Harmer
0.721
228351V2-046C
Solar/Wind Harmer
2.181
230434AG1-499 GEN
Solar/Wind Harmer
0.605
218660EHAMPSOLAR C
Solar/Wind Harmer
0.16
219686LUMSOLAR_N C
Solar/Wind Harmer
0.185
219287REEVESEAST C
Solar/Wind Harmer
1.227
219258KINSLEYDEP C
Solar/Wind Harmer
0.283
219904AC1-010 C
Solar/Wind Harmer
0.32
219907AC1-030 C
Solar/Wind Harmer
0.111
207487AE2-000G4
Solar/Wind Harmer
25.108
213497CHSTR7-9
Adder
2.135
213497CHSTR7-9
Adder
2.135
20720728JCB_W1-129
Solar/Wind Harmer
0.235
207522AF2-254 C
Solar/Wind Harmer
1.127
219304NAMERICA C
Solar/Wind Harmer
0.236
219222BRL12CT2
Adder
6.79
207445AB1-138_GEN
Solar/Wind Harmer
0.432
20628028LAKEHURS
Adder
1.401
963711AG1-223 GEN
Solar/Wind Harmer
1.046
20714828MDF_W3-079
Solar/Wind Harmer
0.216
213611FALLS1-3
Adder
2.407
213958STHWK5-6
Adder
1.828
207454AA2-184 E
Solar/Wind Harmer
0.658
213560DLW11-12
Adder
1.746
20715228NPK_W1-113
Solar/Wind Harmer
0.277
20742028HF_AC1-207
Solar/Wind Harmer
0.501
219680HOPEWELLV C1
Solar/Wind Harmer
0.045
217197RE CRAN C
Solar/Wind Harmer
0.309
20635828PARLN1&2
Adder
4.277
20635028RRCT1&2
Adder
6.535
20635128RRCT3&4
Adder
6.308
218428ETC SOLAR C
Solar/Wind Harmer
0.019
217213AMBOY SO C
Solar/Wind Harmer
0.066
972275AH1-722 GEN
Adder
16.115
218449LINSOLAR C
Solar/Wind Harmer
0.497
200203Y1-065-STG
50/50
18.523
200055ROCKSP 4
50/50
6.671
231914HR8
50/50
4.444
231911HR5
50/50
2.924
232914OH NUG3
50/50
18.553
232916OH NUG5
50/50
18.553
232921TASLEY2G
50/50
10.843
234034AF2-060
50/50
3.711
232907VN8
50/50
63.055
233900O-025 C
50/50
2.473
232911NRG_G2
50/50
0.976
233971AC1-093 C
Solar/Wind Harmer
1.556
970695AG2-447 GEN
Solar/Wind Harmer
7.107
972133AH1-634 GEN
Solar/Wind Harmer
19.637
972073AH1-586 GEN
Solar/Wind Harmer
18.553
232406W1-004 FULL
Solar/Wind Harmer
1.983
233996TM1833_GEN
Solar/Wind Harmer
2.507
233997TMININ_4.2
Solar/Wind Harmer
2.507
233940AF2-379 C
Solar/Wind Harmer
0.369
233990AG1-397 GEN
Solar/Wind Harmer
2.27
234015AF2-250 C
Solar/Wind Harmer
0.238
233994AC2-023 GEN
Solar/Wind Harmer
5.317
960671AF2-358 GEN
Solar/Wind Harmer
35.372
232417X3-008 C
Solar/Wind Harmer
3.943
233952AC2-187 GEN
Solar/Wind Harmer
2.217
233918AB1-142 GEN
Solar/Wind Harmer
1.884
233982AB2-133 GEN
Solar/Wind Harmer
9.242
972251AH1-710 GEN
Adder
80.681
228202CUMB CT
Adder
19.48
228711V2-041C
Solar/Wind Harmer
0.704
971553AH1-274 GEN
Solar/Wind Harmer
2.786
228729W2-030 C
Solar/Wind Harmer
0.637
230430AE1-229_GEN
Solar/Wind Harmer
9.65
230415AB2-049 C
Solar/Wind Harmer
0.205
228304LOGAN
Adder
22.03
219291REEVESSOUT C
Solar/Wind Harmer
0.056
219623KINSLEYBEA C
Solar/Wind Harmer
0.38
219766PARADISE C
Solar/Wind Harmer
0.266
219912AD2-042 GEN
Solar/Wind Harmer
0.65
219236SOUTHERNHQ C
Solar/Wind Harmer
0.054
20636028O CRK C1
Adder
5.634
213497CHSTR7-9
Adder
2.135
20716028EGP_W2-019
Solar/Wind Harmer
0.365
20720828JCB_W4-025
Solar/Wind Harmer
0.357
20715028HAN_X4-015
Solar/Wind Harmer
0.235
219906AC1-017 C
Solar/Wind Harmer
0.173
219610FLORENCE C
Solar/Wind Harmer
1.054
219348LDSOLAR C
Solar/Wind Harmer
0.456
219221BRL12CT1
Adder
6.79
219223BRL12CT3
Adder
6.79
971667AH1-334 GEN
Solar/Wind Harmer
2.067
959561AF2-247 GEN
Solar/Wind Harmer
0.346
20714528FRN_Y2-051
Solar/Wind Harmer
0.209
213958STHWK5-6
Adder
1.828
219727YARDVSOLFA C
Solar/Wind Harmer
0.598
213560DLW11-12
Adder
1.746
20720528MAN_W1-024
Solar/Wind Harmer
0.164
20716228APLW2-078
Solar/Wind Harmer
0.569
219276PARKLANDSO C
Solar/Wind Harmer
0.291
967451AG2-055 C O1
Solar/Wind Harmer
107.09
219918AC2-009 C
Solar/Wind Harmer
0.036
219612MATRIX C
Solar/Wind Harmer
0.106
218438BLK ROCK C
Solar/Wind Harmer
0.078
20635828PARLN1&2
Adder
1.937
20635928PARLN3&4
Adder
1.937
20635028RRCT1&2
Adder
6.637
20635128RRCT3&4
Adder
5.503
219908AB1-139 C
Solar/Wind Harmer
0.199
219919AE1-041 FULL
Solar/Wind Harmer
0.021
219249CENTRALDIV C
Solar/Wind Harmer
0.02
HAMLETPJM->LTFIMP_HAMLET
CLTF
2.977
G-007ALTFEXP_G-007A->PJM
CMTX
28.864
CBM NorthLTFEXP_CBM-N->PJM
CBM
25.787
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
2.706
BlueGrassPJM->LTFIMP_BlueG
CLTF
8.428
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
64.307
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.786
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
12.619

Details for PCHBTM2S-PCHBTM1S 500.0 kV Ckt Z1 line l/o PECO_P4_PEACH255_SRT-A/* $ CHESCO $ PECO_P4_PEACH255 $ STBK


Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM2S-PCHBTM1S 500.0 kV Ckt Z1 line
Contingency Name:
PECO_P4_PEACH255_SRT-A/* $ CHESCO $ PECO_P4_PEACH255 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:135.13 %
Rating:2860.0 MVA
Rating Type:B
MVA to Mitigate:3864.84
MW Contribution:8.92
Bus #Bus NameTypeMW Contribution
200034PCHBTM 2
50/50
47.146
200205Y1-065-CTG2
50/50
8.906
232918OH NUG7
50/50
17.081
232905CHERITON_25
50/50
4.777
232926CRISFLD1
50/50
3.821
231940T-011
50/50
1.451
232899W1-062
50/50
18.711
971149AH1-027 GEN
Solar/Wind Harmer
6.229
233939AC1-091 C
Solar/Wind Harmer
1.615
233970AC1-092 C
Solar/Wind Harmer
1.615
233987AB2-037 GEN
Solar/Wind Harmer
20.928
970545AG2-347 GEN
Solar/Wind Harmer
120.122
972069AH1-584 GEN
Solar/Wind Harmer
16.432
200203Y1-065-STG
50/50
15.443
200055ROCKSP 4
50/50
5.561
231914HR8
50/50
4.087
231911HR5
50/50
2.69
232914OH NUG3
50/50
17.196
232916OH NUG5
50/50
17.196
232921TASLEY2G
50/50
10.05
234034AF2-060
50/50
3.439
233900O-025 C
50/50
2.292
232907VN8
50/50
58.438
232911NRG_G2
50/50
0.907
233971AC1-093 C
Solar/Wind Harmer
1.443
970695AG2-447 GEN
Solar/Wind Harmer
6.588
972133AH1-634 GEN
Solar/Wind Harmer
18.2
972073AH1-586 GEN
Solar/Wind Harmer
17.196
232406W1-004 FULL
Solar/Wind Harmer
1.838
233996TM1833_GEN
Solar/Wind Harmer
2.324
233997TMININ_4.2
Solar/Wind Harmer
2.324
233990AG1-397 GEN
Solar/Wind Harmer
2.104
233940AF2-379 C
Solar/Wind Harmer
0.342
234015AF2-250 C
Solar/Wind Harmer
0.221
233994AC2-023 GEN
Solar/Wind Harmer
4.929
960671AF2-358 GEN
Solar/Wind Harmer
32.793
232417X3-008 C
Solar/Wind Harmer
3.656
200052ROCKSP 1
50/50
5.625
200053ROCKSP 2
50/50
5.504
232616GEN FOOD
50/50
0.319
232904IR4
50/50
157.493
232920IR10
50/50
6.155
232912OH NUG1
50/50
17.196
232913OH NUG2
50/50
16.966
232813VAUGHN
50/50
1.135
233973AC2-185 C
Solar/Wind Harmer
6.645
234033AF1-007_GEN
Solar/Wind Harmer
42.925
232432Z2-076 GEN
Solar/Wind Harmer
0.242
233923SMA
Solar/Wind Harmer
8.52
233990AG1-397 GEN
Solar/Wind Harmer
0.101
233955AB2-172 GEN
Solar/Wind Harmer
9.14
233968AD2-076_GEN
Solar/Wind Harmer
11.853
970597AG2-380 GEN
Solar/Wind Harmer
7.443
232436AB1-176 C
Solar/Wind Harmer
0.409
231906DC3 NUG
Adder
24.871
231902DC CT7
Adder
19.883
231907DC10
Adder
6.209
971983AH1-536 GEN
Solar/Wind Harmer
13.267
233935AB2-179 C
Solar/Wind Harmer
4.245
231919CHRIST1
Adder
6.962
231920CHRIST2
Adder
6.807
970453AG2-297 GEN
Solar/Wind Harmer
3.466
228260V4-054C
Solar/Wind Harmer
1.243
972141AH1-641 GEN
Solar/Wind Harmer
3.429
228309CCLP NUG
Adder
30.761
228309CCLP NUG
Adder
29.26
227927V4-067C
Solar/Wind Harmer
0.236
228754AB1-001 C
Solar/Wind Harmer
0.165
964001AG1-254 GEN
Solar/Wind Harmer
2.404
971535AH1-265 GEN
Solar/Wind Harmer
5.011
971011AG2-627 GEN
Solar/Wind Harmer
8.917
219137THOSOLAR C
Solar/Wind Harmer
1.285
219272CLEANLIGHT C
Solar/Wind Harmer
0.194
219688LUMSOLAR_S C
Solar/Wind Harmer
0.212
219914AD2-027 C
Solar/Wind Harmer
0.6
20717128DIX_Z2-102
Solar/Wind Harmer
1.272
20715728PEM_W1-119
Solar/Wind Harmer
0.514
20715828PEM_W1-120
Solar/Wind Harmer
0.514
219607WPEMNERT C
Solar/Wind Harmer
0.401
219224BRL12CT4
Adder
8.541
970025AG2-016 GEN
Solar/Wind Harmer
2.712
971189AH1-054 GEN
Solar/Wind Harmer
1.12
207459AE1-142 C O1
Solar/Wind Harmer
0.995
213942SCHUYLKILL
Adder
3.226
213942SCHUYLKILL
Adder
2.467
213957STHWK3-4
Adder
2.466
213957STHWK3-4
Adder
2.466
214067T20SOLAR
Solar/Wind Harmer
0.228
213611FALLS1-3
Adder
3.188
213611FALLS1-3
Adder
3.188
213561DLWR9-10
Adder
3.15
213561DLWR9-10
Adder
2.409
20714328BYD_X4-031
Solar/Wind Harmer
0.249
20714428HOW_X1-037
Solar/Wind Harmer
1.087
971521AH1-258 GEN
Solar/Wind Harmer
2.322
20720428HOL_W1-112
Solar/Wind Harmer
0.295
219620RIDERU C
Solar/Wind Harmer
0.047
20635928PARLN3&4
Adder
6.046
218455CINNBAY_CGEN
Adder
1.45
218526CNTRALGAS2 C
Solar/Wind Harmer
0.292
218524CNTRALGAS1 C
Solar/Wind Harmer
0.291
20675528CPH_W2-050
Solar/Wind Harmer
0.348
218404KENILWRTH C
Adder
0.966
217167KRNY_14
Adder
6.816
217086KRNY_131
Adder
6.758
217147KRNY_1212
Adder
6.483
217147KRNY_1212
Adder
6.368
217146KRNY_1234
Adder
6.353
217146KRNY_1234
Adder
6.31
966261AG1-495 GEN
Solar/Wind Harmer
1.191
20676328BVR_Y1-020
Solar/Wind Harmer
0.221
207511W3-106 GEN
Solar/Wind Harmer
0.436
207530AG1-191 GEN
Solar/Wind Harmer
0.906
20674828DL_W4-046
Solar/Wind Harmer
0.41
971009AG2-626 GEN
Solar/Wind Harmer
1.021
966421AG1-511 GEN
Solar/Wind Harmer
5.31
207408W3-077 C
Solar/Wind Harmer
0.31
20675728RH_W2-091
Solar/Wind Harmer
0.209
20675928HOL_W4-097
Solar/Wind Harmer
0.079
207484AF2-139 C O1
Solar/Wind Harmer
0.304
20675128HRM_W1-127
Solar/Wind Harmer
0.102
20462827N BANGR8
Adder
0.427
209116AE2-175 GEN
Solar/Wind Harmer
2.32
961261AF2-417 GEN
Solar/Wind Harmer
0.534
972071AH1-585 GEN
Solar/Wind Harmer
16.432
233901CHERRYDALE C
Solar/Wind Harmer
2.066
232408W1-005 C
Solar/Wind Harmer
1.838
232410W1-006 C
Solar/Wind Harmer
1.838
971747AH1-380 GEN
Solar/Wind Harmer
6.572
233946AB2-136 GEN
Solar/Wind Harmer
7.302
234036AF2-325 C
Solar/Wind Harmer
1.677
234041AC1-190 GEN
Solar/Wind Harmer
16.369
233984AB2-036 GEN
Solar/Wind Harmer
22.446
232424Y1-079 C
Solar/Wind Harmer
1.013
234014AF1-036_GEN
Solar/Wind Harmer
4.838
233944AB2-135 GEN
Solar/Wind Harmer
9.308
231131BLOOM ENRGY
Adder
7.727
233933AB2-153 GEN
Solar/Wind Harmer
1.994
232416X2-083
Adder
0.758
228251CARLLS#4
Adder
0.764
230422AE1-104_GEN1
Solar/Wind Harmer
40.787
230425AE1-104_GEN2
Solar/Wind Harmer
40.787
230433AD2-135 GEN
Solar/Wind Harmer
0.12
230407AD2-065 C
Solar/Wind Harmer
0.154
228307PCLP GT
Adder
13.876
228304LOGAN
Adder
27.414
972233AH1-701 GEN
Adder
4.698
219921AF1-264
Solar/Wind Harmer
0.149
213589EDDYSTN4
Adder
77.426
213587EDDYSTN3
Adder
77.364
219615MILLCREEK C
Solar/Wind Harmer
0.231
207500AE2-000G1
Solar/Wind Harmer
30.577
207497AE2-000G2
Solar/Wind Harmer
30.577
207507AE2-000G3
Solar/Wind Harmer
30.577
20636128O CRK C2
Adder
6.256
20716428NHV_W2-082
Solar/Wind Harmer
1.716
963401AG1-189 GEN
Solar/Wind Harmer
1.106
963391AG1-188 GEN
Solar/Wind Harmer
1.833
213535CROYDN11
Adder
9.667
20714928UPF_X1-085
Solar/Wind Harmer
0.381
20628028LAKEHURS
Adder
0.889
219114HARTZY_C
Solar/Wind Harmer
0.741
20720628TIN_W1-124
Solar/Wind Harmer
0.871
20641628MLH_W1-032
Solar/Wind Harmer
0.255
219817TRENTONSOL C
Solar/Wind Harmer
0.929
20716928W4-060COL
Solar/Wind Harmer
0.596
924131AB2-057 GEN
Solar/Wind Harmer
0.821
218440SUMMTASSOC C
Solar/Wind Harmer
0.101
218418LINDEN_G5
Adder
13.206
218419LINDEN_G6
Adder
13.206
972260AH1-715 GEN1
Adder
10.575
219036LINDEN_G7
Adder
12.655
219035LINDEN_G8
Adder
12.474
972261AH1-715 GEN2
Adder
12.114
217081WEATEXAS C
Solar/Wind Harmer
0.064
20673828FLE_V3-070
Solar/Wind Harmer
0.338
217202FBANKSOLAR C
Solar/Wind Harmer
0.055
207442AE1-156 GEN
Solar/Wind Harmer
0.545
20676128MHD_W3-029
Solar/Wind Harmer
0.35
217201HACKENSOLA C
Solar/Wind Harmer
0.054
972237AH1-703 GEN
Adder
7.427
217206BARNGR HS C
Solar/Wind Harmer
0.023
217086KRNY_131
Adder
6.831
217083KRNY_132
Adder
6.773
217204WCALDSOLAR C
Solar/Wind Harmer
0.053
20671828STAW2-080
Solar/Wind Harmer
0.075
213815MOSER1-3
Adder
2.39
213815MOSER1-3
Adder
2.39
20674528F3S_W2-016
Solar/Wind Harmer
0.97
20676228FRD_X1-012
Solar/Wind Harmer
0.392
207471AF2-354 C
Solar/Wind Harmer
0.323
20674928WA_W3-044
Solar/Wind Harmer
0.304
964851AG1-348 GEN
Solar/Wind Harmer
1.097
20634528N27_Y2-018
Solar/Wind Harmer
0.168
20465127PORT CT
Adder
2.409
966111AG1-480 GEN
Solar/Wind Harmer
0.052
966111AG1-480 GEN
Solar/Wind Harmer
1.983
20674128FR_U2-059
Solar/Wind Harmer
0.11
211065PSPA IPP
Solar/Wind Harmer
0.245
211065PSPA IPP
Solar/Wind Harmer
0.245
200204Y1-065-CTG1
50/50
8.906
200054ROCKSP 3
50/50
5.681
231912HR6
50/50
2.69
231913HR7
50/50
2.69
233920W3-032A-CTG1
50/50
4.048
233921W3-032A-STG1
50/50
2.431
232901NORTHST
50/50
16.252
232917OH NUG6
50/50
17.119
232915OH NUG4
50/50
17.081
232900DEMECSMY
50/50
17.948
232919VN10
50/50
5.455
232910NRG_G1
50/50
16.587
233972AC1-094 C
Solar/Wind Harmer
1.22
232434Z2-077 GEN
Solar/Wind Harmer
0.459
232404W1-003 C
Solar/Wind Harmer
1.838
233998TM1NIN_3.36
Solar/Wind Harmer
2.324
972177AH1-672 GEN
Solar/Wind Harmer
24.641
971195AH1-057 GEN
Solar/Wind Harmer
2.008
232428Y3-058 C
Solar/Wind Harmer
1.53
965821AG1-450 GEN
Solar/Wind Harmer
9.533
232426Y1-080 FULL
Solar/Wind Harmer
0.35
970277AG2-181 GEN
Solar/Wind Harmer
9.18
233964AF2-378 GEN
Solar/Wind Harmer
0.234
233954AC2-188 GEN
Solar/Wind Harmer
2.057
233950AC2-186 GEN
Solar/Wind Harmer
1.028
234012AE2-112_GEN
Solar/Wind Harmer
4.112
232422X3-066 FULL
Solar/Wind Harmer
0.446
233930AB2-032 GEN
Solar/Wind Harmer
1.478
233915AB1-141 GEN
Solar/Wind Harmer
1.756
231918WEST 1
Adder
5.32
231917EM10
Adder
3.611
228206SHRMN CT
Adder
20.513
228732V1-021 C
Adder
0.233
945431AF1-208 GEN
Solar/Wind Harmer
10.385
970997AG2-616 GEN
Solar/Wind Harmer
11.429
230511AF1-262
Solar/Wind Harmer
0.217
228351V2-046C
Solar/Wind Harmer
2.378
228728W1-130C
Solar/Wind Harmer
0.784
230434AG1-499 GEN
Solar/Wind Harmer
0.669
218660EHAMPSOLAR C
Solar/Wind Harmer
0.186
219686LUMSOLAR_N C
Solar/Wind Harmer
0.215
219287REEVESEAST C
Solar/Wind Harmer
1.426
219258KINSLEYDEP C
Solar/Wind Harmer
0.336
219904AC1-010 C
Solar/Wind Harmer
0.386
219907AC1-030 C
Solar/Wind Harmer
0.137
213497CHSTR7-9
Adder
2.674
213497CHSTR7-9
Adder
2.674
207487AE2-000G4
Solar/Wind Harmer
30.577
20720728JCB_W1-129
Solar/Wind Harmer
0.288
207522AF2-254 C
Solar/Wind Harmer
1.384
219304NAMERICA C
Solar/Wind Harmer
0.297
219222BRL12CT2
Adder
8.541
207445AB1-138_GEN
Solar/Wind Harmer
0.542
20628028LAKEHURS
Adder
1.759
213958STHWK5-6
Adder
2.466
213611FALLS1-3
Adder
3.188
963711AG1-223 GEN
Solar/Wind Harmer
1.344
20714828MDF_W3-079
Solar/Wind Harmer
0.278
213560DLW11-12
Adder
2.409
207454AA2-184 E
Solar/Wind Harmer
0.874
20715228NPK_W1-113
Solar/Wind Harmer
0.372
20742028HF_AC1-207
Solar/Wind Harmer
0.675
219680HOPEWELLV C1
Solar/Wind Harmer
0.063
217197RE CRAN C
Solar/Wind Harmer
0.439
20635828PARLN1&2
Adder
6.046
20635028RRCT1&2
Adder
9.358
20635128RRCT3&4
Adder
9.033
218428ETC SOLAR C
Solar/Wind Harmer
0.028
217213AMBOY SO C
Solar/Wind Harmer
0.098
972275AH1-722 GEN
Adder
24.278
218449LINSOLAR C
Solar/Wind Harmer
0.761
217209CENTRL HS C
Solar/Wind Harmer
0.033
207528AF2-192 GEN
Solar/Wind Harmer
0.405
20673628F1S_V4-069
Solar/Wind Harmer
0.132
20675428EAM_W2-061
Solar/Wind Harmer
0.138
20676428JCR_X2-075
Solar/Wind Harmer
0.249
217121ECCF
Adder
0.319
217083KRNY_132
Adder
6.816
217208PARK ELE C
Solar/Wind Harmer
0.019
214194N WALES4
Adder
0.581
207439AE1-081 C O1
Solar/Wind Harmer
0.04
20675828AU_W4-064
Solar/Wind Harmer
0.114
20674328GAR_V4-001
Solar/Wind Harmer
0.072
971519AH1-257 GEN
Solar/Wind Harmer
1.564
207518AF1-320_GEN
Solar/Wind Harmer
2.229
20465127PORT CT
Adder
1.816
207437AD2-070 GEN
Solar/Wind Harmer
0.181
20671928W4-073
Solar/Wind Harmer
0.259
966181AG1-487 GEN
Solar/Wind Harmer
2.222
208909MACR G3
Adder
92.496
223401AF1-299 GEN
Solar/Wind Helper
0.35
233952AC2-187 GEN
Solar/Wind Harmer
2.057
233918AB1-142 GEN
Solar/Wind Harmer
1.756
233982AB2-133 GEN
Solar/Wind Harmer
8.62
972251AH1-710 GEN
Adder
76.717
228202CUMB CT
Adder
20.571
228711V2-041C
Solar/Wind Harmer
0.745
971553AH1-274 GEN
Solar/Wind Harmer
2.969
228729W2-030 C
Solar/Wind Harmer
0.688
230430AE1-229_GEN
Solar/Wind Harmer
10.469
230415AB2-049 C
Solar/Wind Harmer
0.223
228304LOGAN
Adder
24.656
219291REEVESSOUT C
Solar/Wind Harmer
0.064
219623KINSLEYBEA C
Solar/Wind Harmer
0.448
219766PARADISE C
Solar/Wind Harmer
0.321
219912AD2-042 GEN
Solar/Wind Harmer
0.796
219236SOUTHERNHQ C
Solar/Wind Harmer
0.067
213497CHSTR7-9
Adder
2.674
219906AC1-017 C
Solar/Wind Harmer
0.216
20636028O CRK C1
Adder
6.861
20716028EGP_W2-019
Solar/Wind Harmer
0.448
20720828JCB_W4-025
Solar/Wind Harmer
0.438
20715028HAN_X4-015
Solar/Wind Harmer
0.288
219610FLORENCE C
Solar/Wind Harmer
1.326
219348LDSOLAR C
Solar/Wind Harmer
0.573
219221BRL12CT1
Adder
8.541
219223BRL12CT3
Adder
8.541
971667AH1-334 GEN
Solar/Wind Harmer
2.582
959561AF2-247 GEN
Solar/Wind Harmer
0.446
213958STHWK5-6
Adder
2.466
20714528FRN_Y2-051
Solar/Wind Harmer
0.268
213560DLW11-12
Adder
2.409
219727YARDVSOLFA C
Solar/Wind Harmer
0.8
20720528MAN_W1-024
Solar/Wind Harmer
0.22
20716228APLW2-078
Solar/Wind Harmer
0.764
219276PARKLANDSO C
Solar/Wind Harmer
0.397
967451AG2-055 C O1
Solar/Wind Harmer
146.807
219918AC2-009 C
Solar/Wind Harmer
0.051
219612MATRIX C
Solar/Wind Harmer
0.151
218438BLK ROCK C
Solar/Wind Harmer
0.112
20635828PARLN1&2
Adder
2.738
20635928PARLN3&4
Adder
2.738
20635028RRCT1&2
Adder
9.504
20635128RRCT3&4
Adder
7.88
219908AB1-139 C
Solar/Wind Harmer
0.296
219919AE1-041 FULL
Solar/Wind Harmer
0.031
219249CENTRALDIV C
Solar/Wind Harmer
0.03
217211CAMDEN ST C
Solar/Wind Harmer
0.018
20673728F2S_V4-070
Solar/Wind Harmer
0.132
217186ESSEX_G9
Adder
11.728
217169METRODIV C
Solar/Wind Harmer
0.029
217194REDH C
Solar/Wind Harmer
0.361
213815MOSER1-3
Adder
2.39
20676728BRNX1-095
Solar/Wind Harmer
0.124
20674628WNG_W3-110
Solar/Wind Harmer
0.268
207510AF2-138 C
Solar/Wind Harmer
1.181
971007AG2-625 GEN
Solar/Wind Harmer
1.601
20466127PORT 5CT
Adder
16.103
20465427SHAW CT
Adder
2.324
20633028GILCT9
Adder
16.788
966181AG1-487 GEN
Solar/Wind Harmer
0.149
223402AF1-300 C
Solar/Wind Helper
0.35
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.759
G-007ALTFEXP_G-007A->PJM
CMTX
41.332
CBM NorthLTFEXP_CBM-N->PJM
CBM
47.372
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
3.269
BlueGrassPJM->LTFIMP_BlueG
CLTF
10.183
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
100.488
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.237
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
15.304

Details for PCHBTM2S-PCHBTM1S 500.0 kV Ckt Z2 line l/o PECO_P4_PEACH235_SRT-A/* $ CHESCO $ PECO_P4_PEACH235 $ STBK


Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM2S-PCHBTM1S 500.0 kV Ckt Z2 line
Contingency Name:
PECO_P4_PEACH235_SRT-A/* $ CHESCO $ PECO_P4_PEACH235 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.9 %
Rating:2860.0 MVA
Rating Type:B
MVA to Mitigate:3057.45
MW Contribution:8.15
Bus #Bus NameTypeMW Contribution
200034PCHBTM 2
50/50
57.275
200205Y1-065-CTG2
50/50
10.687
232918OH NUG7
50/50
18.471
232905CHERITON_25
50/50
5.165
232926CRISFLD1
50/50
4.132
231940T-011
50/50
1.569
232899W1-062
50/50
20.221
200035PCHBTM 3
50/50
-13.349
971149AH1-027 GEN
Solar/Wind Harmer
6.736
233987AB2-037 GEN
Solar/Wind Harmer
22.651
233939AC1-091 C
Solar/Wind Harmer
1.746
233970AC1-092 C
Solar/Wind Harmer
1.746
970545AG2-347 GEN
Solar/Wind Harmer
129.894
972069AH1-584 GEN
Solar/Wind Harmer
17.769
972071AH1-585 GEN
Solar/Wind Harmer
17.769
233901CHERRYDALE C
Solar/Wind Harmer
2.234
232408W1-005 C
Solar/Wind Harmer
1.987
232410W1-006 C
Solar/Wind Harmer
1.987
971747AH1-380 GEN
Solar/Wind Harmer
7.107
233946AB2-136 GEN
Solar/Wind Harmer
7.894
234036AF2-325 C
Solar/Wind Harmer
1.813
234041AC1-190 GEN
Solar/Wind Harmer
17.693
233984AB2-036 GEN
Solar/Wind Harmer
24.207
232424Y1-079 C
Solar/Wind Harmer
1.092
234014AF1-036_GEN
Solar/Wind Harmer
5.209
233944AB2-135 GEN
Solar/Wind Harmer
10.01
233933AB2-153 GEN
Solar/Wind Harmer
2.144
231131BLOOM ENRGY
Adder
8.287
232416X2-083
Adder
0.798
230422AE1-104_GEN1
Solar/Wind Harmer
38.259
230425AE1-104_GEN2
Solar/Wind Harmer
38.259
228251CARLLS#4
Adder
0.715
230433AD2-135 GEN
Solar/Wind Harmer
0.112
230407AD2-065 C
Solar/Wind Harmer
0.141
228307PCLP GT
Adder
12.568
228304LOGAN
Adder
24.631
972233AH1-701 GEN
Adder
4.19
219921AF1-264
Solar/Wind Harmer
0.126
207500AE2-000G1
Solar/Wind Harmer
25.299
207497AE2-000G2
Solar/Wind Harmer
25.299
207507AE2-000G3
Solar/Wind Harmer
25.299
20636128O CRK C2
Adder
5.176
20716428NHV_W2-082
Solar/Wind Harmer
1.409
963401AG1-189 GEN
Solar/Wind Harmer
0.908
219615MILLCREEK C
Solar/Wind Harmer
0.187
213589EDDYSTN4
Adder
61.848
213587EDDYSTN3
Adder
61.756
963391AG1-188 GEN
Solar/Wind Harmer
1.499
213535CROYDN11
Adder
7.656
20714928UPF_X1-085
Solar/Wind Harmer
0.305
20628028LAKEHURS
Adder
0.714
219114HARTZY_C
Solar/Wind Harmer
0.563
20720628TIN_W1-124
Solar/Wind Harmer
0.663
20641628MLH_W1-032
Solar/Wind Harmer
0.193
219817TRENTONSOL C
Solar/Wind Harmer
0.674
20716928W4-060COL
Solar/Wind Harmer
0.437
924131AB2-057 GEN
Solar/Wind Harmer
0.571
218440SUMMTASSOC C
Solar/Wind Harmer
0.069
218418LINDEN_G5
Adder
8.884
218419LINDEN_G6
Adder
8.884
972260AH1-715 GEN1
Adder
7.114
219036LINDEN_G7
Adder
8.38
219035LINDEN_G8
Adder
8.26
972261AH1-715 GEN2
Adder
8.022
217081WEATEXAS C
Solar/Wind Harmer
0.042
217202FBANKSOLAR C
Solar/Wind Harmer
0.036
200203Y1-065-STG
50/50
18.533
200055ROCKSP 4
50/50
6.674
231914HR8
50/50
4.453
231911HR5
50/50
2.93
232914OH NUG3
50/50
18.595
232916OH NUG5
50/50
18.595
232921TASLEY2G
50/50
10.868
234034AF2-060
50/50
3.719
232907VN8
50/50
63.197
233900O-025 C
50/50
2.478
232911NRG_G2
50/50
0.978
233971AC1-093 C
Solar/Wind Harmer
1.559
970695AG2-447 GEN
Solar/Wind Harmer
7.123
972133AH1-634 GEN
Solar/Wind Harmer
19.681
972073AH1-586 GEN
Solar/Wind Harmer
18.595
232406W1-004 FULL
Solar/Wind Harmer
1.987
233996TM1833_GEN
Solar/Wind Harmer
2.513
233997TMININ_4.2
Solar/Wind Harmer
2.513
233940AF2-379 C
Solar/Wind Harmer
0.37
233990AG1-397 GEN
Solar/Wind Harmer
2.275
234015AF2-250 C
Solar/Wind Harmer
0.239
233994AC2-023 GEN
Solar/Wind Harmer
5.329
960671AF2-358 GEN
Solar/Wind Harmer
35.453
232417X3-008 C
Solar/Wind Harmer
3.951
233952AC2-187 GEN
Solar/Wind Harmer
2.222
233918AB1-142 GEN
Solar/Wind Harmer
1.888
233982AB2-133 GEN
Solar/Wind Harmer
9.264
972251AH1-710 GEN
Adder
80.895
228202CUMB CT
Adder
19.568
228711V2-041C
Solar/Wind Harmer
0.707
971553AH1-274 GEN
Solar/Wind Harmer
2.799
228729W2-030 C
Solar/Wind Harmer
0.64
230430AE1-229_GEN
Solar/Wind Harmer
9.698
230415AB2-049 C
Solar/Wind Harmer
0.206
228304LOGAN
Adder
22.153
219291REEVESSOUT C
Solar/Wind Harmer
0.056
219623KINSLEYBEA C
Solar/Wind Harmer
0.382
219766PARADISE C
Solar/Wind Harmer
0.268
219912AD2-042 GEN
Solar/Wind Harmer
0.654
219236SOUTHERNHQ C
Solar/Wind Harmer
0.054
20636028O CRK C1
Adder
5.677
213497CHSTR7-9
Adder
2.152
20716028EGP_W2-019
Solar/Wind Harmer
0.368
20720828JCB_W4-025
Solar/Wind Harmer
0.359
20715028HAN_X4-015
Solar/Wind Harmer
0.236
219906AC1-017 C
Solar/Wind Harmer
0.174
219610FLORENCE C
Solar/Wind Harmer
1.062
219348LDSOLAR C
Solar/Wind Harmer
0.459
219221BRL12CT1
Adder
6.845
219223BRL12CT3
Adder
6.845
971667AH1-334 GEN
Solar/Wind Harmer
2.083
959561AF2-247 GEN
Solar/Wind Harmer
0.349
20714528FRN_Y2-051
Solar/Wind Harmer
0.21
213958STHWK5-6
Adder
1.844
219727YARDVSOLFA C
Solar/Wind Harmer
0.604
213560DLW11-12
Adder
1.763
20720528MAN_W1-024
Solar/Wind Harmer
0.166
20716228APLW2-078
Solar/Wind Harmer
0.575
219276PARKLANDSO C
Solar/Wind Harmer
0.294
967451AG2-055 C O1
Solar/Wind Harmer
108.224
219918AC2-009 C
Solar/Wind Harmer
0.037
219612MATRIX C
Solar/Wind Harmer
0.107
218438BLK ROCK C
Solar/Wind Harmer
0.079
20635828PARLN1&2
Adder
1.96
20635928PARLN3&4
Adder
1.96
20635028RRCT1&2
Adder
6.716
20635128RRCT3&4
Adder
5.568
219908AB1-139 C
Solar/Wind Harmer
0.202
219919AE1-041 FULL
Solar/Wind Harmer
0.021
219249CENTRALDIV C
Solar/Wind Harmer
0.02
217211CAMDEN ST C
Solar/Wind Harmer
0.012
200052ROCKSP 1
50/50
6.75
200053ROCKSP 2
50/50
6.606
232616GEN FOOD
50/50
0.344
232904IR4
50/50
170.306
232920IR10
50/50
6.655
232912OH NUG1
50/50
18.595
232913OH NUG2
50/50
18.347
232813VAUGHN
50/50
1.225
233973AC2-185 C
Solar/Wind Harmer
7.183
234033AF1-007_GEN
Solar/Wind Harmer
46.417
232432Z2-076 GEN
Solar/Wind Harmer
0.262
233923SMA
Solar/Wind Harmer
9.214
233990AG1-397 GEN
Solar/Wind Harmer
0.109
233955AB2-172 GEN
Solar/Wind Harmer
9.879
233968AD2-076_GEN
Solar/Wind Harmer
12.763
970597AG2-380 GEN
Solar/Wind Harmer
8.014
232436AB1-176 C
Solar/Wind Harmer
0.44
231906DC3 NUG
Adder
26.699
231902DC CT7
Adder
21.344
231907DC10
Adder
6.665
971983AH1-536 GEN
Solar/Wind Harmer
14.265
233935AB2-179 C
Solar/Wind Harmer
4.527
231919CHRIST1
Adder
7.156
231920CHRIST2
Adder
6.997
970453AG2-297 GEN
Solar/Wind Harmer
3.312
228260V4-054C
Solar/Wind Harmer
1.164
972141AH1-641 GEN
Solar/Wind Harmer
3.179
227927V4-067C
Solar/Wind Harmer
0.219
228309CCLP NUG
Adder
28.478
228309CCLP NUG
Adder
27.089
228754AB1-001 C
Solar/Wind Harmer
0.154
964001AG1-254 GEN
Solar/Wind Harmer
2.218
971535AH1-265 GEN
Solar/Wind Harmer
4.62
971011AG2-627 GEN
Solar/Wind Harmer
8.147
219272CLEANLIGHT C
Solar/Wind Harmer
0.168
219137THOSOLAR C
Solar/Wind Harmer
1.106
219688LUMSOLAR_S C
Solar/Wind Harmer
0.183
219914AD2-027 C
Solar/Wind Harmer
0.494
20717128DIX_Z2-102
Solar/Wind Harmer
1.042
20715728PEM_W1-119
Solar/Wind Harmer
0.421
20715828PEM_W1-120
Solar/Wind Harmer
0.421
970025AG2-016 GEN
Solar/Wind Harmer
2.219
219607WPEMNERT C
Solar/Wind Harmer
0.321
219224BRL12CT4
Adder
6.845
971189AH1-054 GEN
Solar/Wind Harmer
0.91
207459AE1-142 C O1
Solar/Wind Harmer
0.805
214067T20SOLAR
Solar/Wind Harmer
0.174
213611FALLS1-3
Adder
2.429
213611FALLS1-3
Adder
2.429
213942SCHUYLKILL
Adder
2.413
213942SCHUYLKILL
Adder
1.845
213957STHWK3-4
Adder
1.844
213957STHWK3-4
Adder
1.844
20714328BYD_X4-031
Solar/Wind Harmer
0.191
20714428HOW_X1-037
Solar/Wind Harmer
0.831
213561DLWR9-10
Adder
2.306
213561DLWR9-10
Adder
1.763
971521AH1-258 GEN
Solar/Wind Harmer
1.739
20720428HOL_W1-112
Solar/Wind Harmer
0.22
219620RIDERU C
Solar/Wind Harmer
0.034
20635928PARLN3&4
Adder
4.326
218455CINNBAY_CGEN
Adder
1.008
218526CNTRALGAS2 C
Solar/Wind Harmer
0.2
218524CNTRALGAS1 C
Solar/Wind Harmer
0.199
20675528CPH_W2-050
Solar/Wind Harmer
0.222
218404KENILWRTH C
Adder
0.626
200204Y1-065-CTG1
50/50
10.687
200054ROCKSP 3
50/50
6.818
231912HR6
50/50
2.93
231913HR7
50/50
2.93
233920W3-032A-CTG1
50/50
4.377
233921W3-032A-STG1
50/50
2.629
232901NORTHST
50/50
17.575
232917OH NUG6
50/50
18.512
232915OH NUG4
50/50
18.471
232900DEMECSMY
50/50
19.395
232919VN10
50/50
5.898
232910NRG_G1
50/50
17.892
233972AC1-094 C
Solar/Wind Harmer
1.319
232434Z2-077 GEN
Solar/Wind Harmer
0.497
232404W1-003 C
Solar/Wind Harmer
1.987
233998TM1NIN_3.36
Solar/Wind Harmer
2.513
972177AH1-672 GEN
Solar/Wind Harmer
26.64
971195AH1-057 GEN
Solar/Wind Harmer
2.171
232428Y3-058 C
Solar/Wind Harmer
1.655
965821AG1-450 GEN
Solar/Wind Harmer
10.306
232426Y1-080 FULL
Solar/Wind Harmer
0.378
970277AG2-181 GEN
Solar/Wind Harmer
9.924
233964AF2-378 GEN
Solar/Wind Harmer
0.253
233954AC2-188 GEN
Solar/Wind Harmer
2.222
233950AC2-186 GEN
Solar/Wind Harmer
1.111
234012AE2-112_GEN
Solar/Wind Harmer
4.428
232422X3-066 FULL
Solar/Wind Harmer
0.48
233930AB2-032 GEN
Solar/Wind Harmer
1.589
233915AB1-141 GEN
Solar/Wind Harmer
1.888
231918WEST 1
Adder
5.485
231917EM10
Adder
3.667
228206SHRMN CT
Adder
19.443
228732V1-021 C
Adder
0.22
945431AF1-208 GEN
Solar/Wind Harmer
9.683
970997AG2-616 GEN
Solar/Wind Harmer
10.598
230511AF1-262
Solar/Wind Harmer
0.2
228728W1-130C
Solar/Wind Harmer
0.724
228351V2-046C
Solar/Wind Harmer
2.192
230434AG1-499 GEN
Solar/Wind Harmer
0.608
218660EHAMPSOLAR C
Solar/Wind Harmer
0.161
219686LUMSOLAR_N C
Solar/Wind Harmer
0.186
219287REEVESEAST C
Solar/Wind Harmer
1.235
219258KINSLEYDEP C
Solar/Wind Harmer
0.285
219904AC1-010 C
Solar/Wind Harmer
0.322
219907AC1-030 C
Solar/Wind Harmer
0.112
207487AE2-000G4
Solar/Wind Harmer
25.299
213497CHSTR7-9
Adder
2.152
213497CHSTR7-9
Adder
2.152
20720728JCB_W1-129
Solar/Wind Harmer
0.237
207522AF2-254 C
Solar/Wind Harmer
1.135
219304NAMERICA C
Solar/Wind Harmer
0.238
219222BRL12CT2
Adder
6.845
207445AB1-138_GEN
Solar/Wind Harmer
0.435
20628028LAKEHURS
Adder
1.413
963711AG1-223 GEN
Solar/Wind Harmer
1.056
20714828MDF_W3-079
Solar/Wind Harmer
0.218
213611FALLS1-3
Adder
2.429
213958STHWK5-6
Adder
1.844
207454AA2-184 E
Solar/Wind Harmer
0.665
213560DLW11-12
Adder
1.763
20715228NPK_W1-113
Solar/Wind Harmer
0.28
20742028HF_AC1-207
Solar/Wind Harmer
0.506
219680HOPEWELLV C1
Solar/Wind Harmer
0.045
217197RE CRAN C
Solar/Wind Harmer
0.312
20635828PARLN1&2
Adder
4.326
20635028RRCT1&2
Adder
6.613
20635128RRCT3&4
Adder
6.383
218428ETC SOLAR C
Solar/Wind Harmer
0.019
217213AMBOY SO C
Solar/Wind Harmer
0.067
972275AH1-722 GEN
Adder
16.332
218449LINSOLAR C
Solar/Wind Harmer
0.504
217209CENTRL HS C
Solar/Wind Harmer
0.022
HAMLETPJM->LTFIMP_HAMLET
CLTF
2.877
G-007ALTFEXP_G-007A->PJM
CMTX
29.208
CBM NorthLTFEXP_CBM-N->PJM
CBM
26.546
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
2.61
BlueGrassPJM->LTFIMP_BlueG
CLTF
8.129
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
65.254
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.726
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
12.174

Details for PCHBTMTP-COOPER2 230.0 kV Ckt 1 line l/o PJM_500_BG_P4_5_CNSTN_C_SRT-A


Base Case Flowgate

Area:PECO
Facility Description:
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line
Contingency Name:
PJM_500_BG_P4_5_CNSTN_C_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:134.98 %
Rating:578.0 MVA
Rating Type:B
MVA to Mitigate:780.21
MW Contribution:2.32
Bus #Bus NameTypeMW Contribution
213508CON10-11
50/50
1.01
213518CONOW8-9
50/50
1.01
213517CONOW7
50/50
0.746
213497CHSTR7-9
Adder
1.074
233982AB2-133 GEN
Solar/Wind Harmer
2.007
233918AB1-142 GEN
Solar/Wind Harmer
0.407
213958STHWK5-6
Adder
0.989
232417X3-008 C
Solar/Wind Harmer
0.74
960671AF2-358 GEN
Solar/Wind Harmer
6.569
232907VN8
Adder
10.963
233952AC2-187 GEN
Solar/Wind Harmer
0.41
233994AC2-023 GEN
Solar/Wind Harmer
0.977
233940AF2-379 C
Solar/Wind Harmer
0.068
233900O-025 C
Adder
0.427
234015AF2-250 C
Solar/Wind Harmer
0.044
233996TM1833_GEN
Solar/Wind Harmer
0.459
233997TMININ_4.2
Solar/Wind Harmer
0.459
232406W1-004 FULL
Solar/Wind Harmer
0.362
232921TASLEY2G
Adder
1.868
213589EDDYSTN4
Adder
31.437
213587EDDYSTN3
Adder
31.41
232416X2-083
Adder
0.19
233933AB2-153 GEN
Solar/Wind Harmer
0.463
233944AB2-135 GEN
Solar/Wind Harmer
2.122
234014AF1-036_GEN
Solar/Wind Harmer
1.085
231131BLOOM ENRGY
Adder
1.715
232424Y1-079 C
Solar/Wind Harmer
0.221
233984AB2-036 GEN
Solar/Wind Harmer
4.865
234041AC1-190 GEN
Solar/Wind Harmer
3.31
233987AB2-037 GEN
Solar/Wind Harmer
4.196
234036AF2-325 C
Solar/Wind Harmer
0.338
233946AB2-136 GEN
Solar/Wind Harmer
1.469
232926CRISFLD1
Adder
0.711
233901CHERRYDALE C
Solar/Wind Harmer
0.407
232408W1-005 C
Solar/Wind Harmer
0.362
232410W1-006 C
Solar/Wind Harmer
0.362
232905CHERITON_25
Adder
0.888
232918OH NUG7
Adder
3.174
971747AH1-380 GEN
Solar/Wind Harmer
1.296
972069AH1-584 GEN
Solar/Wind Harmer
3.238
972071AH1-585 GEN
Solar/Wind Harmer
3.238
231940T-011
Adder
0.269
970545AG2-347 GEN
Solar/Wind Harmer
23.481
232899W1-062
Adder
3.394
971149AH1-027 GEN
Solar/Wind Harmer
1.179
233939AC1-091 C
Solar/Wind Harmer
0.304
233970AC1-092 C
Solar/Wind Harmer
0.304
972233AH1-701 GEN
Adder
1.291
213815MOSER1-3
Adder
1.097
213815MOSER1-3
Adder
1.097
228304LOGAN
Adder
7.432
228307PCLP GT
Adder
3.695
219921AF1-264
Solar/Wind Harmer
0.044
228251CARLLS#4
Adder
0.186
219615MILLCREEK C
Solar/Wind Harmer
0.071
230433AD2-135 GEN
Solar/Wind Harmer
0.03
230407AD2-065 C
Solar/Wind Harmer
0.039
213535CROYDN11
Adder
3.002
230422AE1-104_GEN1
Solar/Wind Harmer
9.699
230425AE1-104_GEN2
Solar/Wind Harmer
9.699
219114HARTZY_C
Solar/Wind Harmer
0.227
20716428NHV_W2-082
Solar/Wind Harmer
0.476
207500AE2-000G1
Solar/Wind Harmer
8.261
207497AE2-000G2
Solar/Wind Harmer
8.261
207507AE2-000G3
Solar/Wind Harmer
8.261
20636128O CRK C2
Adder
1.69
20714928UPF_X1-085
Solar/Wind Harmer
0.107
963401AG1-189 GEN
Solar/Wind Harmer
0.301
963391AG1-188 GEN
Solar/Wind Harmer
0.501
20628028LAKEHURS
Adder
0.247
219817TRENTONSOL C
Solar/Wind Harmer
0.285
20720628TIN_W1-124
Solar/Wind Harmer
0.25
20641628MLH_W1-032
Solar/Wind Harmer
0.073
20716928W4-060COL
Solar/Wind Harmer
0.175
924131AB2-057 GEN
Solar/Wind Harmer
0.252
218440SUMMTASSOC C
Solar/Wind Harmer
0.031
20673828FLE_V3-070
Solar/Wind Harmer
0.11
218418LINDEN_G5
Adder
4.092
218419LINDEN_G6
Adder
4.092
972260AH1-715 GEN1
Adder
3.277
207442AE1-156 GEN
Solar/Wind Harmer
0.177
20676128MHD_W3-029
Solar/Wind Harmer
0.114
213515CONOW3-4
50/50
0.746
213515CONOW3-4
50/50
0.746
213514CONOW1-2
50/50
0.56
213516CONOW5-6
50/50
0.56
233935AB2-179 C
Solar/Wind Harmer
1.161
231919CHRIST1
Adder
1.882
231920CHRIST2
Adder
1.84
971983AH1-536 GEN
Solar/Wind Harmer
3.073
232436AB1-176 C
Solar/Wind Harmer
0.092
233968AD2-076_GEN
Solar/Wind Harmer
2.657
970597AG2-380 GEN
Solar/Wind Harmer
1.669
231906DC3 NUG
Adder
5.528
231902DC CT7
Adder
4.419
231907DC10
Adder
1.38
213942SCHUYLKILL
Adder
1.305
213942SCHUYLKILL
Adder
0.998
213957STHWK3-4
Adder
0.989
213957STHWK3-4
Adder
0.989
232813VAUGHN
Adder
0.218
233955AB2-172 GEN
Solar/Wind Harmer
1.85
233923SMA
Solar/Wind Harmer
1.683
232912OH NUG1
Adder
3.196
232913OH NUG2
Adder
3.153
233990AG1-397 GEN
Solar/Wind Harmer
0.02
232432Z2-076 GEN
Solar/Wind Harmer
0.048
232920IR10
Adder
1.135
234033AF1-007_GEN
Solar/Wind Harmer
8.391
232904IR4
Adder
29.014
213561DLWR9-10
Adder
1.191
213561DLWR9-10
Adder
0.911
233973AC2-185 C
Solar/Wind Harmer
1.25
219137THOSOLAR C
Solar/Wind Harmer
0.375
219914AD2-027 C
Solar/Wind Harmer
0.184
971011AG2-627 GEN
Solar/Wind Harmer
2.317
228309CCLP NUG
Adder
7.778
228309CCLP NUG
Adder
7.399
964001AG1-254 GEN
Solar/Wind Harmer
0.611
972141AH1-641 GEN
Solar/Wind Harmer
0.858
228260V4-054C
Solar/Wind Harmer
0.303
971535AH1-265 GEN
Solar/Wind Harmer
1.252
219272CLEANLIGHT C
Solar/Wind Harmer
0.053
970453AG2-297 GEN
Solar/Wind Harmer
0.8
219607WPEMNERT C
Solar/Wind Harmer
0.122
219224BRL12CT4
Adder
2.607
219688LUMSOLAR_S C
Solar/Wind Harmer
0.059
228754AB1-001 C
Solar/Wind Harmer
0.04
227927V4-067C
Solar/Wind Harmer
0.057
214067T20SOLAR
Solar/Wind Harmer
0.073
213611FALLS1-3
Adder
1.014
213611FALLS1-3
Adder
1.014
213508CON10-11
50/50
1.01
213518CONOW8-9
50/50
1.01
213514CONOW1-2
50/50
0.746
213516CONOW5-6
50/50
0.746
231918WEST 1
Adder
1.445
231917EM10
Adder
1.008
213497CHSTR7-9
Adder
1.074
213497CHSTR7-9
Adder
1.074
233930AB2-032 GEN
Solar/Wind Harmer
0.343
233915AB1-141 GEN
Solar/Wind Harmer
0.407
232422X3-066 FULL
Solar/Wind Harmer
0.101
234012AE2-112_GEN
Solar/Wind Harmer
0.922
20717128DIX_Z2-102
Solar/Wind Harmer
0.352
20715728PEM_W1-119
Solar/Wind Harmer
0.142
20715828PEM_W1-120
Solar/Wind Harmer
0.142
971189AH1-054 GEN
Solar/Wind Harmer
0.31
970025AG2-016 GEN
Solar/Wind Harmer
0.741
207459AE1-142 C O1
Solar/Wind Harmer
0.274
219620RIDERU C
Solar/Wind Harmer
0.014
20714328BYD_X4-031
Solar/Wind Harmer
0.071
20714428HOW_X1-037
Solar/Wind Harmer
0.311
971521AH1-258 GEN
Solar/Wind Harmer
0.675
20720428HOL_W1-112
Solar/Wind Harmer
0.086
218455CINNBAY_CGEN
Adder
0.446
20635928PARLN3&4
Adder
1.806
20675528CPH_W2-050
Solar/Wind Harmer
0.114
218526CNTRALGAS2 C
Solar/Wind Harmer
0.09
218524CNTRALGAS1 C
Solar/Wind Harmer
0.089
213958STHWK5-6
Adder
0.989
232910NRG_G1
Adder
3.243
233964AF2-378 GEN
Solar/Wind Harmer
0.047
232426Y1-080 FULL
Solar/Wind Harmer
0.07
970277AG2-181 GEN
Solar/Wind Harmer
1.841
965821AG1-450 GEN
Solar/Wind Harmer
1.909
232919VN10
Adder
1.027
233954AC2-188 GEN
Solar/Wind Harmer
0.41
233950AC2-186 GEN
Solar/Wind Harmer
0.205
232428Y3-058 C
Solar/Wind Harmer
0.303
971195AH1-057 GEN
Solar/Wind Harmer
0.397
233998TM1NIN_3.36
Solar/Wind Harmer
0.459
232404W1-003 C
Solar/Wind Harmer
0.362
232917OH NUG6
Adder
3.182
232915OH NUG4
Adder
3.174
232434Z2-077 GEN
Solar/Wind Harmer
0.09
972177AH1-672 GEN
Solar/Wind Harmer
4.814
213560DLW11-12
Adder
0.911
232900DEMECSMY
Adder
3.256
232901NORTHST
Adder
2.9
233972AC1-094 C
Solar/Wind Harmer
0.229
219258KINSLEYDEP C
Solar/Wind Harmer
0.1
219904AC1-010 C
Solar/Wind Harmer
0.116
219907AC1-030 C
Solar/Wind Harmer
0.042
228351V2-046C
Solar/Wind Harmer
0.605
230434AG1-499 GEN
Solar/Wind Harmer
0.174
970997AG2-616 GEN
Solar/Wind Harmer
2.86
945431AF1-208 GEN
Solar/Wind Harmer
2.563
230511AF1-262
Solar/Wind Harmer
0.054
228728W1-130C
Solar/Wind Harmer
0.195
228206SHRMN CT
Adder
4.83
219304NAMERICA C
Solar/Wind Harmer
0.091
219222BRL12CT2
Adder
2.607
228732V1-021 C
Adder
0.055
218660EHAMPSOLAR C
Solar/Wind Harmer
0.051
219686LUMSOLAR_N C
Solar/Wind Harmer
0.058
219287REEVESEAST C
Solar/Wind Harmer
0.388
214194N WALES4
Adder
0.245
213611FALLS1-3
Adder
1.014
20720728JCB_W1-129
Solar/Wind Harmer
0.08
207522AF2-254 C
Solar/Wind Harmer
0.384
207487AE2-000G4
Solar/Wind Harmer
8.261
207445AB1-138_GEN
Solar/Wind Harmer
0.151
20628028LAKEHURS
Adder
0.489
963711AG1-223 GEN
Solar/Wind Harmer
0.379
20714828MDF_W3-079
Solar/Wind Harmer
0.078
219680HOPEWELLV C1
Solar/Wind Harmer
0.02
207454AA2-184 E
Solar/Wind Harmer
0.251
20715228NPK_W1-113
Solar/Wind Harmer
0.108
217197RE CRAN C
Solar/Wind Harmer
0.135
20742028HF_AC1-207
Solar/Wind Harmer
0.196
20635828PARLN1&2
Adder
1.806
20635028RRCT1&2
Adder
2.816
20635128RRCT3&4
Adder
2.718
218428ETC SOLAR C
Solar/Wind Harmer
0.009
217213AMBOY SO C
Solar/Wind Harmer
0.03
972275AH1-722 GEN
Adder
7.523
207528AF2-192 GEN
Solar/Wind Harmer
0.132
20673628F1S_V4-069
Solar/Wind Harmer
0.043
20675428EAM_W2-061
Solar/Wind Harmer
0.045
208909MACR G3
Adder
32.152
223401AF1-299 GEN
Solar/Wind Helper
0.271
232914OH NUG3
Adder
3.196
232916OH NUG5
Adder
3.196
233990AG1-397 GEN
Solar/Wind Harmer
0.415
972073AH1-586 GEN
Solar/Wind Harmer
3.388
972133AH1-634 GEN
Solar/Wind Harmer
3.558
213560DLW11-12
Adder
0.911
233971AC1-093 C
Solar/Wind Harmer
0.271
970695AG2-447 GEN
Solar/Wind Harmer
1.239
213815MOSER1-3
Adder
1.097
228304LOGAN
Adder
6.684
219766PARADISE C
Solar/Wind Harmer
0.097
219912AD2-042 GEN
Solar/Wind Harmer
0.244
219623KINSLEYBEA C
Solar/Wind Harmer
0.13
219236SOUTHERNHQ C
Solar/Wind Harmer
0.02
230430AE1-229_GEN
Solar/Wind Harmer
2.621
219906AC1-017 C
Solar/Wind Harmer
0.066
230415AB2-049 C
Solar/Wind Harmer
0.056
971553AH1-274 GEN
Solar/Wind Harmer
0.709
228711V2-041C
Solar/Wind Harmer
0.175
228202CUMB CT
Adder
4.799
219610FLORENCE C
Solar/Wind Harmer
0.405
219348LDSOLAR C
Solar/Wind Harmer
0.175
219221BRL12CT1
Adder
2.607
219223BRL12CT3
Adder
2.607
219291REEVESSOUT C
Solar/Wind Harmer
0.017
972251AH1-710 GEN
Adder
13.808
228729W2-030 C
Solar/Wind Harmer
0.165
959561AF2-247 GEN
Solar/Wind Harmer
0.137
20716028EGP_W2-019
Solar/Wind Harmer
0.124
20720828JCB_W4-025
Solar/Wind Harmer
0.121
219727YARDVSOLFA C
Solar/Wind Harmer
0.246
20715028HAN_X4-015
Solar/Wind Harmer
0.08
20636028O CRK C1
Adder
1.854
219276PARKLANDSO C
Solar/Wind Harmer
0.122
971667AH1-334 GEN
Solar/Wind Harmer
0.715
20714528FRN_Y2-051
Solar/Wind Harmer
0.076
219918AC2-009 C
Solar/Wind Harmer
0.016
20716228APLW2-078
Solar/Wind Harmer
0.222
20720528MAN_W1-024
Solar/Wind Harmer
0.064
219612MATRIX C
Solar/Wind Harmer
0.046
218438BLK ROCK C
Solar/Wind Harmer
0.034
967451AG2-055 C O1
Solar/Wind Harmer
42.597
20635828PARLN1&2
Adder
0.818
20635928PARLN3&4
Adder
0.818
20635028RRCT1&2
Adder
2.86
20635128RRCT3&4
Adder
2.371
219908AB1-139 C
Solar/Wind Harmer
0.091
219919AE1-041 FULL
Solar/Wind Harmer
0.01
219249CENTRALDIV C
Solar/Wind Harmer
0.009
20673728F2S_V4-070
Solar/Wind Harmer
0.043
223402AF1-300 C
Solar/Wind Helper
0.271
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.034
G-007ALTFEXP_G-007A->PJM
CMTX
12.437
CBM NorthLTFEXP_CBM-N->PJM
CBM
16.035
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.84
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.618
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
31.56
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.609
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
3.958

Details for PCHBTMTP-COOPER2 230.0 kV Ckt 1 line l/o PECO_P4_PEACH235_SRT-A/* $ CHESCO $ PECO_P4_PEACH235 $ STBK


Base Case Flowgate

Area:PECO
Facility Description:
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line
Contingency Name:
PECO_P4_PEACH235_SRT-A/* $ CHESCO $ PECO_P4_PEACH235 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:134.89 %
Rating:578.0 MVA
Rating Type:B
MVA to Mitigate:779.65
MW Contribution:2.32
Bus #Bus NameTypeMW Contribution
213589EDDYSTN4
Adder
31.443
213587EDDYSTN3
Adder
31.416
232416X2-083
Adder
0.19
233933AB2-153 GEN
Solar/Wind Harmer
0.463
233944AB2-135 GEN
Solar/Wind Harmer
2.123
234014AF1-036_GEN
Solar/Wind Harmer
1.085
231131BLOOM ENRGY
Adder
1.716
232424Y1-079 C
Solar/Wind Harmer
0.221
233984AB2-036 GEN
Solar/Wind Harmer
4.867
234041AC1-190 GEN
Solar/Wind Harmer
3.312
233987AB2-037 GEN
Solar/Wind Harmer
4.198
234036AF2-325 C
Solar/Wind Harmer
0.338
233946AB2-136 GEN
Solar/Wind Harmer
1.47
232926CRISFLD1
Adder
0.711
233901CHERRYDALE C
Solar/Wind Harmer
0.408
232408W1-005 C
Solar/Wind Harmer
0.363
232410W1-006 C
Solar/Wind Harmer
0.363
232905CHERITON_25
Adder
0.888
232918OH NUG7
Adder
3.176
971747AH1-380 GEN
Solar/Wind Harmer
1.296
972069AH1-584 GEN
Solar/Wind Harmer
3.239
972071AH1-585 GEN
Solar/Wind Harmer
3.239
231940T-011
Adder
0.27
970545AG2-347 GEN
Solar/Wind Harmer
23.494
232899W1-062
Adder
3.396
971149AH1-027 GEN
Solar/Wind Harmer
1.18
233939AC1-091 C
Solar/Wind Harmer
0.304
233970AC1-092 C
Solar/Wind Harmer
0.304
972233AH1-701 GEN
Adder
1.291
213815MOSER1-3
Adder
1.097
213815MOSER1-3
Adder
1.097
228304LOGAN
Adder
7.434
228307PCLP GT
Adder
3.696
219921AF1-264
Solar/Wind Harmer
0.044
228251CARLLS#4
Adder
0.186
219615MILLCREEK C
Solar/Wind Harmer
0.071
230433AD2-135 GEN
Solar/Wind Harmer
0.03
230407AD2-065 C
Solar/Wind Harmer
0.039
213535CROYDN11
Adder
3.003
230422AE1-104_GEN1
Solar/Wind Harmer
9.703
230425AE1-104_GEN2
Solar/Wind Harmer
9.703
219114HARTZY_C
Solar/Wind Harmer
0.227
20716428NHV_W2-082
Solar/Wind Harmer
0.476
207500AE2-000G1
Solar/Wind Harmer
8.264
207497AE2-000G2
Solar/Wind Harmer
8.264
207507AE2-000G3
Solar/Wind Harmer
8.264
20636128O CRK C2
Adder
1.691
20714928UPF_X1-085
Solar/Wind Harmer
0.107
963401AG1-189 GEN
Solar/Wind Harmer
0.301
963391AG1-188 GEN
Solar/Wind Harmer
0.501
20628028LAKEHURS
Adder
0.247
219817TRENTONSOL C
Solar/Wind Harmer
0.285
20720628TIN_W1-124
Solar/Wind Harmer
0.25
20641628MLH_W1-032
Solar/Wind Harmer
0.073
20716928W4-060COL
Solar/Wind Harmer
0.175
924131AB2-057 GEN
Solar/Wind Harmer
0.252
218440SUMMTASSOC C
Solar/Wind Harmer
0.031
20673828FLE_V3-070
Solar/Wind Harmer
0.11
218418LINDEN_G5
Adder
4.093
218419LINDEN_G6
Adder
4.093
972260AH1-715 GEN1
Adder
3.278
207442AE1-156 GEN
Solar/Wind Harmer
0.177
20676128MHD_W3-029
Solar/Wind Harmer
0.114
213508CON10-11
50/50
1.01
213518CONOW8-9
50/50
1.01
213514CONOW1-2
50/50
0.746
213516CONOW5-6
50/50
0.746
231918WEST 1
Adder
1.445
231917EM10
Adder
1.009
213497CHSTR7-9
Adder
1.074
213497CHSTR7-9
Adder
1.074
233930AB2-032 GEN
Solar/Wind Harmer
0.343
233915AB1-141 GEN
Solar/Wind Harmer
0.408
232422X3-066 FULL
Solar/Wind Harmer
0.101
234012AE2-112_GEN
Solar/Wind Harmer
0.922
213958STHWK5-6
Adder
0.99
232910NRG_G1
Adder
3.245
233964AF2-378 GEN
Solar/Wind Harmer
0.047
232426Y1-080 FULL
Solar/Wind Harmer
0.07
970277AG2-181 GEN
Solar/Wind Harmer
1.842
965821AG1-450 GEN
Solar/Wind Harmer
1.91
232919VN10
Adder
1.027
233954AC2-188 GEN
Solar/Wind Harmer
0.41
233950AC2-186 GEN
Solar/Wind Harmer
0.205
232428Y3-058 C
Solar/Wind Harmer
0.303
971195AH1-057 GEN
Solar/Wind Harmer
0.397
233998TM1NIN_3.36
Solar/Wind Harmer
0.459
232404W1-003 C
Solar/Wind Harmer
0.363
232917OH NUG6
Adder
3.183
232915OH NUG4
Adder
3.176
232434Z2-077 GEN
Solar/Wind Harmer
0.09
972177AH1-672 GEN
Solar/Wind Harmer
4.816
213560DLW11-12
Adder
0.911
232900DEMECSMY
Adder
3.257
232901NORTHST
Adder
2.902
233972AC1-094 C
Solar/Wind Harmer
0.23
219258KINSLEYDEP C
Solar/Wind Harmer
0.1
219904AC1-010 C
Solar/Wind Harmer
0.116
219907AC1-030 C
Solar/Wind Harmer
0.042
228351V2-046C
Solar/Wind Harmer
0.605
230434AG1-499 GEN
Solar/Wind Harmer
0.174
970997AG2-616 GEN
Solar/Wind Harmer
2.861
945431AF1-208 GEN
Solar/Wind Harmer
2.564
230511AF1-262
Solar/Wind Harmer
0.054
228728W1-130C
Solar/Wind Harmer
0.195
228206SHRMN CT
Adder
4.832
219304NAMERICA C
Solar/Wind Harmer
0.091
219222BRL12CT2
Adder
2.608
228732V1-021 C
Adder
0.055
218660EHAMPSOLAR C
Solar/Wind Harmer
0.051
219686LUMSOLAR_N C
Solar/Wind Harmer
0.058
219287REEVESEAST C
Solar/Wind Harmer
0.388
214194N WALES4
Adder
0.245
213611FALLS1-3
Adder
1.015
20720728JCB_W1-129
Solar/Wind Harmer
0.08
207522AF2-254 C
Solar/Wind Harmer
0.384
207487AE2-000G4
Solar/Wind Harmer
8.264
207445AB1-138_GEN
Solar/Wind Harmer
0.151
20628028LAKEHURS
Adder
0.489
963711AG1-223 GEN
Solar/Wind Harmer
0.379
20714828MDF_W3-079
Solar/Wind Harmer
0.078
219680HOPEWELLV C1
Solar/Wind Harmer
0.02
207454AA2-184 E
Solar/Wind Harmer
0.251
20715228NPK_W1-113
Solar/Wind Harmer
0.108
217197RE CRAN C
Solar/Wind Harmer
0.135
20742028HF_AC1-207
Solar/Wind Harmer
0.196
20635828PARLN1&2
Adder
1.806
20635028RRCT1&2
Adder
2.817
20635128RRCT3&4
Adder
2.719
218428ETC SOLAR C
Solar/Wind Harmer
0.009
217213AMBOY SO C
Solar/Wind Harmer
0.03
972275AH1-722 GEN
Adder
7.525
207528AF2-192 GEN
Solar/Wind Harmer
0.132
20673628F1S_V4-069
Solar/Wind Harmer
0.043
20675428EAM_W2-061
Solar/Wind Harmer
0.045
208909MACR G3
Adder
32.156
223401AF1-299 GEN
Solar/Wind Helper
0.271
213515CONOW3-4
50/50
0.746
213515CONOW3-4
50/50
0.746
213514CONOW1-2
50/50
0.56
213516CONOW5-6
50/50
0.56
233935AB2-179 C
Solar/Wind Harmer
1.162
231919CHRIST1
Adder
1.883
231920CHRIST2
Adder
1.841
971983AH1-536 GEN
Solar/Wind Harmer
3.074
232436AB1-176 C
Solar/Wind Harmer
0.092
233968AD2-076_GEN
Solar/Wind Harmer
2.659
970597AG2-380 GEN
Solar/Wind Harmer
1.67
231906DC3 NUG
Adder
5.53
231902DC CT7
Adder
4.421
231907DC10
Adder
1.381
213942SCHUYLKILL
Adder
1.305
213942SCHUYLKILL
Adder
0.998
213957STHWK3-4
Adder
0.99
213957STHWK3-4
Adder
0.99
232813VAUGHN
Adder
0.219
233955AB2-172 GEN
Solar/Wind Harmer
1.851
233923SMA
Solar/Wind Harmer
1.683
232912OH NUG1
Adder
3.197
232913OH NUG2
Adder
3.155
233990AG1-397 GEN
Solar/Wind Harmer
0.02
232432Z2-076 GEN
Solar/Wind Harmer
0.048
232920IR10
Adder
1.136
234033AF1-007_GEN
Solar/Wind Harmer
8.396
232904IR4
Adder
29.029
213561DLWR9-10
Adder
1.192
213561DLWR9-10
Adder
0.911
233973AC2-185 C
Solar/Wind Harmer
1.25
219137THOSOLAR C
Solar/Wind Harmer
0.376
219914AD2-027 C
Solar/Wind Harmer
0.184
971011AG2-627 GEN
Solar/Wind Harmer
2.318
228309CCLP NUG
Adder
7.781
228309CCLP NUG
Adder
7.401
964001AG1-254 GEN
Solar/Wind Harmer
0.611
972141AH1-641 GEN
Solar/Wind Harmer
0.858
228260V4-054C
Solar/Wind Harmer
0.303
971535AH1-265 GEN
Solar/Wind Harmer
1.252
219272CLEANLIGHT C
Solar/Wind Harmer
0.053
970453AG2-297 GEN
Solar/Wind Harmer
0.801
219607WPEMNERT C
Solar/Wind Harmer
0.122
219224BRL12CT4
Adder
2.608
219688LUMSOLAR_S C
Solar/Wind Harmer
0.059
228754AB1-001 C
Solar/Wind Harmer
0.04
227927V4-067C
Solar/Wind Harmer
0.057
214067T20SOLAR
Solar/Wind Harmer
0.073
213611FALLS1-3
Adder
1.015
213611FALLS1-3
Adder
1.015
20717128DIX_Z2-102
Solar/Wind Harmer
0.353
20715728PEM_W1-119
Solar/Wind Harmer
0.142
20715828PEM_W1-120
Solar/Wind Harmer
0.142
971189AH1-054 GEN
Solar/Wind Harmer
0.31
970025AG2-016 GEN
Solar/Wind Harmer
0.741
207459AE1-142 C O1
Solar/Wind Harmer
0.274
219620RIDERU C
Solar/Wind Harmer
0.014
20714328BYD_X4-031
Solar/Wind Harmer
0.071
20714428HOW_X1-037
Solar/Wind Harmer
0.312
971521AH1-258 GEN
Solar/Wind Harmer
0.675
20720428HOL_W1-112
Solar/Wind Harmer
0.086
218455CINNBAY_CGEN
Adder
0.446
20635928PARLN3&4
Adder
1.806
20675528CPH_W2-050
Solar/Wind Harmer
0.114
218526CNTRALGAS2 C
Solar/Wind Harmer
0.09
218524CNTRALGAS1 C
Solar/Wind Harmer
0.089
213508CON10-11
50/50
1.01
213518CONOW8-9
50/50
1.01
213517CONOW7
50/50
0.746
213497CHSTR7-9
Adder
1.074
233982AB2-133 GEN
Solar/Wind Harmer
2.008
233918AB1-142 GEN
Solar/Wind Harmer
0.408
213958STHWK5-6
Adder
0.99
232417X3-008 C
Solar/Wind Harmer
0.741
960671AF2-358 GEN
Solar/Wind Harmer
6.572
232907VN8
Adder
10.969
233952AC2-187 GEN
Solar/Wind Harmer
0.41
233994AC2-023 GEN
Solar/Wind Harmer
0.978
233940AF2-379 C
Solar/Wind Harmer
0.068
233900O-025 C
Adder
0.427
234015AF2-250 C
Solar/Wind Harmer
0.044
233996TM1833_GEN
Solar/Wind Harmer
0.459
233997TMININ_4.2
Solar/Wind Harmer
0.459
232406W1-004 FULL
Solar/Wind Harmer
0.363
232921TASLEY2G
Adder
1.869
232914OH NUG3
Adder
3.197
232916OH NUG5
Adder
3.197
233990AG1-397 GEN
Solar/Wind Harmer
0.415
972073AH1-586 GEN
Solar/Wind Harmer
3.39
972133AH1-634 GEN
Solar/Wind Harmer
3.56
213560DLW11-12
Adder
0.911
233971AC1-093 C
Solar/Wind Harmer
0.271
970695AG2-447 GEN
Solar/Wind Harmer
1.24
213815MOSER1-3
Adder
1.097
228304LOGAN
Adder
6.686
219766PARADISE C
Solar/Wind Harmer
0.097
219912AD2-042 GEN
Solar/Wind Harmer
0.244
219623KINSLEYBEA C
Solar/Wind Harmer
0.13
219236SOUTHERNHQ C
Solar/Wind Harmer
0.02
230430AE1-229_GEN
Solar/Wind Harmer
2.622
219906AC1-017 C
Solar/Wind Harmer
0.066
230415AB2-049 C
Solar/Wind Harmer
0.056
971553AH1-274 GEN
Solar/Wind Harmer
0.709
228711V2-041C
Solar/Wind Harmer
0.175
228202CUMB CT
Adder
4.801
219610FLORENCE C
Solar/Wind Harmer
0.405
219348LDSOLAR C
Solar/Wind Harmer
0.175
219221BRL12CT1
Adder
2.608
219223BRL12CT3
Adder
2.608
219291REEVESSOUT C
Solar/Wind Harmer
0.017
972251AH1-710 GEN
Adder
13.816
228729W2-030 C
Solar/Wind Harmer
0.165
959561AF2-247 GEN
Solar/Wind Harmer
0.137
20716028EGP_W2-019
Solar/Wind Harmer
0.124
20720828JCB_W4-025
Solar/Wind Harmer
0.121
219727YARDVSOLFA C
Solar/Wind Harmer
0.246
20715028HAN_X4-015
Solar/Wind Harmer
0.08
20636028O CRK C1
Adder
1.854
219276PARKLANDSO C
Solar/Wind Harmer
0.122
971667AH1-334 GEN
Solar/Wind Harmer
0.715
20714528FRN_Y2-051
Solar/Wind Harmer
0.076
219918AC2-009 C
Solar/Wind Harmer
0.016
20716228APLW2-078
Solar/Wind Harmer
0.222
20720528MAN_W1-024
Solar/Wind Harmer
0.064
219612MATRIX C
Solar/Wind Harmer
0.046
218438BLK ROCK C
Solar/Wind Harmer
0.034
967451AG2-055 C O1
Solar/Wind Harmer
42.608
20635828PARLN1&2
Adder
0.818
20635928PARLN3&4
Adder
0.818
20635028RRCT1&2
Adder
2.861
20635128RRCT3&4
Adder
2.372
219908AB1-139 C
Solar/Wind Harmer
0.092
219919AE1-041 FULL
Solar/Wind Harmer
0.01
219249CENTRALDIV C
Solar/Wind Harmer
0.009
20673728F2S_V4-070
Solar/Wind Harmer
0.043
223402AF1-300 C
Solar/Wind Helper
0.271
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.035
G-007ALTFEXP_G-007A->PJM
CMTX
12.44
CBM NorthLTFEXP_CBM-N->PJM
CBM
16.037
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.84
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.618
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
31.566
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.609
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
3.959

Details for PCHBTMTP-COOPER2 230.0 kV Ckt 1 line l/o BGE_P4_GRACETON_51_SRT-A


Base Case Flowgate

Area:PECO
Facility Description:
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line
Contingency Name:
BGE_P4_GRACETON_51_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:134.84 %
Rating:578.0 MVA
Rating Type:B
MVA to Mitigate:779.37
MW Contribution:2.32
Bus #Bus NameTypeMW Contribution
213589EDDYSTN4
Adder
31.437
213587EDDYSTN3
Adder
31.41
232416X2-083
Adder
0.19
233933AB2-153 GEN
Solar/Wind Harmer
0.463
233944AB2-135 GEN
Solar/Wind Harmer
2.122
234014AF1-036_GEN
Solar/Wind Harmer
1.085
231131BLOOM ENRGY
Adder
1.715
232424Y1-079 C
Solar/Wind Harmer
0.221
233984AB2-036 GEN
Solar/Wind Harmer
4.865
234041AC1-190 GEN
Solar/Wind Harmer
3.31
233987AB2-037 GEN
Solar/Wind Harmer
4.196
234036AF2-325 C
Solar/Wind Harmer
0.338
233946AB2-136 GEN
Solar/Wind Harmer
1.469
232926CRISFLD1
Adder
0.711
233901CHERRYDALE C
Solar/Wind Harmer
0.407
232408W1-005 C
Solar/Wind Harmer
0.362
232410W1-006 C
Solar/Wind Harmer
0.362
232905CHERITON_25
Adder
0.888
232918OH NUG7
Adder
3.174
971747AH1-380 GEN
Solar/Wind Harmer
1.296
972069AH1-584 GEN
Solar/Wind Harmer
3.238
972071AH1-585 GEN
Solar/Wind Harmer
3.238
231940T-011
Adder
0.269
970545AG2-347 GEN
Solar/Wind Harmer
23.481
232899W1-062
Adder
3.394
971149AH1-027 GEN
Solar/Wind Harmer
1.179
233939AC1-091 C
Solar/Wind Harmer
0.304
233970AC1-092 C
Solar/Wind Harmer
0.304
972233AH1-701 GEN
Adder
1.291
213815MOSER1-3
Adder
1.097
213815MOSER1-3
Adder
1.097
228304LOGAN
Adder
7.432
228307PCLP GT
Adder
3.695
219921AF1-264
Solar/Wind Harmer
0.044
228251CARLLS#4
Adder
0.186
219615MILLCREEK C
Solar/Wind Harmer
0.071
230433AD2-135 GEN
Solar/Wind Harmer
0.03
230407AD2-065 C
Solar/Wind Harmer
0.039
213535CROYDN11
Adder
3.002
230422AE1-104_GEN1
Solar/Wind Harmer
9.699
230425AE1-104_GEN2
Solar/Wind Harmer
9.699
219114HARTZY_C
Solar/Wind Harmer
0.227
20716428NHV_W2-082
Solar/Wind Harmer
0.476
207500AE2-000G1
Solar/Wind Harmer
8.261
207497AE2-000G2
Solar/Wind Harmer
8.261
207507AE2-000G3
Solar/Wind Harmer
8.261
20636128O CRK C2
Adder
1.69
20714928UPF_X1-085
Solar/Wind Harmer
0.107
963401AG1-189 GEN
Solar/Wind Harmer
0.301
963391AG1-188 GEN
Solar/Wind Harmer
0.501
20628028LAKEHURS
Adder
0.247
219817TRENTONSOL C
Solar/Wind Harmer
0.285
20720628TIN_W1-124
Solar/Wind Harmer
0.25
20641628MLH_W1-032
Solar/Wind Harmer
0.073
20716928W4-060COL
Solar/Wind Harmer
0.175
924131AB2-057 GEN
Solar/Wind Harmer
0.252
218440SUMMTASSOC C
Solar/Wind Harmer
0.031
20673828FLE_V3-070
Solar/Wind Harmer
0.11
218418LINDEN_G5
Adder
4.092
218419LINDEN_G6
Adder
4.092
972260AH1-715 GEN1
Adder
3.277
207442AE1-156 GEN
Solar/Wind Harmer
0.177
20676128MHD_W3-029
Solar/Wind Harmer
0.114
213508CON10-11
50/50
1.01
213518CONOW8-9
50/50
1.01
213514CONOW1-2
50/50
0.746
213516CONOW5-6
50/50
0.746
231918WEST 1
Adder
1.445
231917EM10
Adder
1.008
213497CHSTR7-9
Adder
1.074
213497CHSTR7-9
Adder
1.074
233930AB2-032 GEN
Solar/Wind Harmer
0.343
233915AB1-141 GEN
Solar/Wind Harmer
0.407
232422X3-066 FULL
Solar/Wind Harmer
0.101
234012AE2-112_GEN
Solar/Wind Harmer
0.922
213958STHWK5-6
Adder
0.989
232910NRG_G1
Adder
3.243
233964AF2-378 GEN
Solar/Wind Harmer
0.047
232426Y1-080 FULL
Solar/Wind Harmer
0.07
970277AG2-181 GEN
Solar/Wind Harmer
1.841
965821AG1-450 GEN
Solar/Wind Harmer
1.909
232919VN10
Adder
1.027
233954AC2-188 GEN
Solar/Wind Harmer
0.41
233950AC2-186 GEN
Solar/Wind Harmer
0.205
232428Y3-058 C
Solar/Wind Harmer
0.303
971195AH1-057 GEN
Solar/Wind Harmer
0.397
233998TM1NIN_3.36
Solar/Wind Harmer
0.459
232404W1-003 C
Solar/Wind Harmer
0.362
232917OH NUG6
Adder
3.182
232915OH NUG4
Adder
3.174
232434Z2-077 GEN
Solar/Wind Harmer
0.09
972177AH1-672 GEN
Solar/Wind Harmer
4.814
213560DLW11-12
Adder
0.911
232900DEMECSMY
Adder
3.256
232901NORTHST
Adder
2.9
233972AC1-094 C
Solar/Wind Harmer
0.229
219258KINSLEYDEP C
Solar/Wind Harmer
0.1
219904AC1-010 C
Solar/Wind Harmer
0.116
219907AC1-030 C
Solar/Wind Harmer
0.042
228351V2-046C
Solar/Wind Harmer
0.605
230434AG1-499 GEN
Solar/Wind Harmer
0.174
970997AG2-616 GEN
Solar/Wind Harmer
2.86
945431AF1-208 GEN
Solar/Wind Harmer
2.563
230511AF1-262
Solar/Wind Harmer
0.054
228728W1-130C
Solar/Wind Harmer
0.195
228206SHRMN CT
Adder
4.83
219304NAMERICA C
Solar/Wind Harmer
0.091
219222BRL12CT2
Adder
2.607
228732V1-021 C
Adder
0.055
218660EHAMPSOLAR C
Solar/Wind Harmer
0.051
219686LUMSOLAR_N C
Solar/Wind Harmer
0.058
219287REEVESEAST C
Solar/Wind Harmer
0.388
214194N WALES4
Adder
0.245
213611FALLS1-3
Adder
1.014
20720728JCB_W1-129
Solar/Wind Harmer
0.08
207522AF2-254 C
Solar/Wind Harmer
0.384
207487AE2-000G4
Solar/Wind Harmer
8.261
207445AB1-138_GEN
Solar/Wind Harmer
0.151
20628028LAKEHURS
Adder
0.489
213515CONOW3-4
50/50
0.746
213515CONOW3-4
50/50
0.746
213514CONOW1-2
50/50
0.56
213516CONOW5-6
50/50
0.56
233935AB2-179 C
Solar/Wind Harmer
1.161
231919CHRIST1
Adder
1.882
231920CHRIST2
Adder
1.84
971983AH1-536 GEN
Solar/Wind Harmer
3.073
232436AB1-176 C
Solar/Wind Harmer
0.092
233968AD2-076_GEN
Solar/Wind Harmer
2.657
970597AG2-380 GEN
Solar/Wind Harmer
1.669
231906DC3 NUG
Adder
5.528
231902DC CT7
Adder
4.419
231907DC10
Adder
1.38
213942SCHUYLKILL
Adder
1.305
213942SCHUYLKILL
Adder
0.998
213957STHWK3-4
Adder
0.989
213957STHWK3-4
Adder
0.989
232813VAUGHN
Adder
0.218
233955AB2-172 GEN
Solar/Wind Harmer
1.85
233923SMA
Solar/Wind Harmer
1.683
232912OH NUG1
Adder
3.196
232913OH NUG2
Adder
3.153
233990AG1-397 GEN
Solar/Wind Harmer
0.02
232432Z2-076 GEN
Solar/Wind Harmer
0.048
232920IR10
Adder
1.135
234033AF1-007_GEN
Solar/Wind Harmer
8.391
232904IR4
Adder
29.014
213561DLWR9-10
Adder
1.191
213561DLWR9-10
Adder
0.911
233973AC2-185 C
Solar/Wind Harmer
1.25
219137THOSOLAR C
Solar/Wind Harmer
0.375
219914AD2-027 C
Solar/Wind Harmer
0.184
971011AG2-627 GEN
Solar/Wind Harmer
2.317
228309CCLP NUG
Adder
7.778
228309CCLP NUG
Adder
7.399
964001AG1-254 GEN
Solar/Wind Harmer
0.611
972141AH1-641 GEN
Solar/Wind Harmer
0.858
228260V4-054C
Solar/Wind Harmer
0.303
971535AH1-265 GEN
Solar/Wind Harmer
1.252
219272CLEANLIGHT C
Solar/Wind Harmer
0.053
970453AG2-297 GEN
Solar/Wind Harmer
0.8
219607WPEMNERT C
Solar/Wind Harmer
0.122
219224BRL12CT4
Adder
2.607
219688LUMSOLAR_S C
Solar/Wind Harmer
0.059
228754AB1-001 C
Solar/Wind Harmer
0.04
227927V4-067C
Solar/Wind Harmer
0.057
214067T20SOLAR
Solar/Wind Harmer
0.073
213611FALLS1-3
Adder
1.014
213611FALLS1-3
Adder
1.014
20717128DIX_Z2-102
Solar/Wind Harmer
0.352
20715728PEM_W1-119
Solar/Wind Harmer
0.142
20715828PEM_W1-120
Solar/Wind Harmer
0.142
971189AH1-054 GEN
Solar/Wind Harmer
0.31
970025AG2-016 GEN
Solar/Wind Harmer
0.741
207459AE1-142 C O1
Solar/Wind Harmer
0.274
219620RIDERU C
Solar/Wind Harmer
0.014
20714328BYD_X4-031
Solar/Wind Harmer
0.071
20714428HOW_X1-037
Solar/Wind Harmer
0.311
971521AH1-258 GEN
Solar/Wind Harmer
0.675
20720428HOL_W1-112
Solar/Wind Harmer
0.086
218455CINNBAY_CGEN
Adder
0.446
20635928PARLN3&4
Adder
1.806
20675528CPH_W2-050
Solar/Wind Harmer
0.114
218526CNTRALGAS2 C
Solar/Wind Harmer
0.09
218524CNTRALGAS1 C
Solar/Wind Harmer
0.089
963711AG1-223 GEN
Solar/Wind Harmer
0.379
20714828MDF_W3-079
Solar/Wind Harmer
0.078
219680HOPEWELLV C1
Solar/Wind Harmer
0.02
207454AA2-184 E
Solar/Wind Harmer
0.251
20715228NPK_W1-113
Solar/Wind Harmer
0.108
217197RE CRAN C
Solar/Wind Harmer
0.135
20742028HF_AC1-207
Solar/Wind Harmer
0.196
20635828PARLN1&2
Adder
1.806
20635028RRCT1&2
Adder
2.816
20635128RRCT3&4
Adder
2.718
218428ETC SOLAR C
Solar/Wind Harmer
0.009
217213AMBOY SO C
Solar/Wind Harmer
0.03
972275AH1-722 GEN
Adder
7.523
207528AF2-192 GEN
Solar/Wind Harmer
0.132
20673628F1S_V4-069
Solar/Wind Harmer
0.043
20675428EAM_W2-061
Solar/Wind Harmer
0.045
208909MACR G3
Adder
32.152
223401AF1-299 GEN
Solar/Wind Helper
0.271
213508CON10-11
50/50
1.01
213518CONOW8-9
50/50
1.01
213517CONOW7
50/50
0.746
213497CHSTR7-9
Adder
1.074
233982AB2-133 GEN
Solar/Wind Harmer
2.007
233918AB1-142 GEN
Solar/Wind Harmer
0.407
213958STHWK5-6
Adder
0.989
232417X3-008 C
Solar/Wind Harmer
0.74
960671AF2-358 GEN
Solar/Wind Harmer
6.569
232907VN8
Adder
10.963
233952AC2-187 GEN
Solar/Wind Harmer
0.41
233994AC2-023 GEN
Solar/Wind Harmer
0.977
233940AF2-379 C
Solar/Wind Harmer
0.068
233900O-025 C
Adder
0.427
234015AF2-250 C
Solar/Wind Harmer
0.044
233996TM1833_GEN
Solar/Wind Harmer
0.459
233997TMININ_4.2
Solar/Wind Harmer
0.459
232406W1-004 FULL
Solar/Wind Harmer
0.362
232921TASLEY2G
Adder
1.868
232914OH NUG3
Adder
3.196
232916OH NUG5
Adder
3.196
233990AG1-397 GEN
Solar/Wind Harmer
0.415
972073AH1-586 GEN
Solar/Wind Harmer
3.388
972133AH1-634 GEN
Solar/Wind Harmer
3.558
213560DLW11-12
Adder
0.911
233971AC1-093 C
Solar/Wind Harmer
0.271
970695AG2-447 GEN
Solar/Wind Harmer
1.239
213815MOSER1-3
Adder
1.097
228304LOGAN
Adder
6.684
219766PARADISE C
Solar/Wind Harmer
0.097
219912AD2-042 GEN
Solar/Wind Harmer
0.244
219623KINSLEYBEA C
Solar/Wind Harmer
0.13
219236SOUTHERNHQ C
Solar/Wind Harmer
0.02
230430AE1-229_GEN
Solar/Wind Harmer
2.621
219906AC1-017 C
Solar/Wind Harmer
0.066
230415AB2-049 C
Solar/Wind Harmer
0.056
971553AH1-274 GEN
Solar/Wind Harmer
0.709
228711V2-041C
Solar/Wind Harmer
0.175
228202CUMB CT
Adder
4.799
219610FLORENCE C
Solar/Wind Harmer
0.405
219348LDSOLAR C
Solar/Wind Harmer
0.175
219221BRL12CT1
Adder
2.607
219223BRL12CT3
Adder
2.607
219291REEVESSOUT C
Solar/Wind Harmer
0.017
972251AH1-710 GEN
Adder
13.808
228729W2-030 C
Solar/Wind Harmer
0.165
959561AF2-247 GEN
Solar/Wind Harmer
0.137
20716028EGP_W2-019
Solar/Wind Harmer
0.124
20720828JCB_W4-025
Solar/Wind Harmer
0.121
219727YARDVSOLFA C
Solar/Wind Harmer
0.246
20715028HAN_X4-015
Solar/Wind Harmer
0.08
20636028O CRK C1
Adder
1.854
219276PARKLANDSO C
Solar/Wind Harmer
0.122
971667AH1-334 GEN
Solar/Wind Harmer
0.715
20714528FRN_Y2-051
Solar/Wind Harmer
0.076
219918AC2-009 C
Solar/Wind Harmer
0.016
20716228APLW2-078
Solar/Wind Harmer
0.222
20720528MAN_W1-024
Solar/Wind Harmer
0.064
219612MATRIX C
Solar/Wind Harmer
0.046
218438BLK ROCK C
Solar/Wind Harmer
0.034
967451AG2-055 C O1
Solar/Wind Harmer
42.597
20635828PARLN1&2
Adder
0.818
20635928PARLN3&4
Adder
0.818
20635028RRCT1&2
Adder
2.86
20635128RRCT3&4
Adder
2.371
219908AB1-139 C
Solar/Wind Harmer
0.091
219919AE1-041 FULL
Solar/Wind Harmer
0.01
219249CENTRALDIV C
Solar/Wind Harmer
0.009
20673728F2S_V4-070
Solar/Wind Harmer
0.043
223402AF1-300 C
Solar/Wind Helper
0.271
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.034
G-007ALTFEXP_G-007A->PJM
CMTX
12.437
CBM NorthLTFEXP_CBM-N->PJM
CBM
16.035
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.84
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.618
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
31.56
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.609
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
3.958

Details for PCHBTMTP-COOPER2 230.0 kV Ckt 1 line l/o PJM_500_BG_P4_5_CNSTN_B_SRT-A


Base Case Flowgate

Area:PECO
Facility Description:
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line
Contingency Name:
PJM_500_BG_P4_5_CNSTN_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:133.89 %
Rating:578.0 MVA
Rating Type:B
MVA to Mitigate:773.9
MW Contribution:2.28
Bus #Bus NameTypeMW Contribution
213515CONOW3-4
50/50
0.741
213515CONOW3-4
50/50
0.741
213514CONOW1-2
50/50
0.555
213516CONOW5-6
50/50
0.555
233935AB2-179 C
Solar/Wind Harmer
1.148
231919CHRIST1
Adder
1.859
231920CHRIST2
Adder
1.818
971983AH1-536 GEN
Solar/Wind Harmer
3.035
232436AB1-176 C
Solar/Wind Harmer
0.091
233968AD2-076_GEN
Solar/Wind Harmer
2.624
970597AG2-380 GEN
Solar/Wind Harmer
1.648
231906DC3 NUG
Adder
5.458
231902DC CT7
Adder
4.363
231907DC10
Adder
1.363
213942SCHUYLKILL
Adder
1.288
213942SCHUYLKILL
Adder
0.985
213957STHWK3-4
Adder
0.976
213957STHWK3-4
Adder
0.976
232813VAUGHN
Adder
0.216
233955AB2-172 GEN
Solar/Wind Harmer
1.826
233923SMA
Solar/Wind Harmer
1.66
232912OH NUG1
Adder
3.153
232913OH NUG2
Adder
3.111
233990AG1-397 GEN
Solar/Wind Harmer
0.02
232432Z2-076 GEN
Solar/Wind Harmer
0.047
232920IR10
Adder
1.12
234033AF1-007_GEN
Solar/Wind Harmer
8.279
232904IR4
Adder
28.625
213561DLWR9-10
Adder
1.175
213561DLWR9-10
Adder
0.898
233973AC2-185 C
Solar/Wind Harmer
1.233
219137THOSOLAR C
Solar/Wind Harmer
0.37
219914AD2-027 C
Solar/Wind Harmer
0.181
971011AG2-627 GEN
Solar/Wind Harmer
2.283
228309CCLP NUG
Adder
7.663
228309CCLP NUG
Adder
7.29
964001AG1-254 GEN
Solar/Wind Harmer
0.602
972141AH1-641 GEN
Solar/Wind Harmer
0.845
228260V4-054C
Solar/Wind Harmer
0.299
971535AH1-265 GEN
Solar/Wind Harmer
1.233
219272CLEANLIGHT C
Solar/Wind Harmer
0.053
970453AG2-297 GEN
Solar/Wind Harmer
0.788
219607WPEMNERT C
Solar/Wind Harmer
0.121
219224BRL12CT4
Adder
2.567
219688LUMSOLAR_S C
Solar/Wind Harmer
0.058
228754AB1-001 C
Solar/Wind Harmer
0.039
227927V4-067C
Solar/Wind Harmer
0.056
214067T20SOLAR
Solar/Wind Harmer
0.071
213611FALLS1-3
Adder
0.999
213611FALLS1-3
Adder
0.999
20717128DIX_Z2-102
Solar/Wind Harmer
0.347
20715728PEM_W1-119
Solar/Wind Harmer
0.14
20715828PEM_W1-120
Solar/Wind Harmer
0.14
971189AH1-054 GEN
Solar/Wind Harmer
0.304
970025AG2-016 GEN
Solar/Wind Harmer
0.728
207459AE1-142 C O1
Solar/Wind Harmer
0.27
219620RIDERU C
Solar/Wind Harmer
0.014
20714328BYD_X4-031
Solar/Wind Harmer
0.07
20714428HOW_X1-037
Solar/Wind Harmer
0.306
971521AH1-258 GEN
Solar/Wind Harmer
0.663
20720428HOL_W1-112
Solar/Wind Harmer
0.085
218455CINNBAY_CGEN
Adder
0.438
20635928PARLN3&4
Adder
1.773
213589EDDYSTN4
Adder
31.043
213587EDDYSTN3
Adder
31.015
232416X2-083
Adder
0.188
233933AB2-153 GEN
Solar/Wind Harmer
0.457
233944AB2-135 GEN
Solar/Wind Harmer
2.096
234014AF1-036_GEN
Solar/Wind Harmer
1.071
231131BLOOM ENRGY
Adder
1.693
232424Y1-079 C
Solar/Wind Harmer
0.218
233984AB2-036 GEN
Solar/Wind Harmer
4.803
234041AC1-190 GEN
Solar/Wind Harmer
3.266
233987AB2-037 GEN
Solar/Wind Harmer
4.141
234036AF2-325 C
Solar/Wind Harmer
0.334
233946AB2-136 GEN
Solar/Wind Harmer
1.449
232926CRISFLD1
Adder
0.702
233901CHERRYDALE C
Solar/Wind Harmer
0.402
232408W1-005 C
Solar/Wind Harmer
0.358
232410W1-006 C
Solar/Wind Harmer
0.358
232918OH NUG7
Adder
3.132
232905CHERITON_25
Adder
0.876
971747AH1-380 GEN
Solar/Wind Harmer
1.278
213508CON10-11
50/50
1.003
213518CONOW8-9
50/50
1.003
213514CONOW1-2
50/50
0.741
213516CONOW5-6
50/50
0.741
231918WEST 1
Adder
1.427
231917EM10
Adder
0.996
213497CHSTR7-9
Adder
1.06
213497CHSTR7-9
Adder
1.06
233930AB2-032 GEN
Solar/Wind Harmer
0.339
233915AB1-141 GEN
Solar/Wind Harmer
0.402
232422X3-066 FULL
Solar/Wind Harmer
0.099
234012AE2-112_GEN
Solar/Wind Harmer
0.91
213958STHWK5-6
Adder
0.976
232910NRG_G1
Adder
3.201
233964AF2-378 GEN
Solar/Wind Harmer
0.046
232426Y1-080 FULL
Solar/Wind Harmer
0.069
970277AG2-181 GEN
Solar/Wind Harmer
1.817
965821AG1-450 GEN
Solar/Wind Harmer
1.884
232919VN10
Adder
1.013
233954AC2-188 GEN
Solar/Wind Harmer
0.404
233950AC2-186 GEN
Solar/Wind Harmer
0.202
232428Y3-058 C
Solar/Wind Harmer
0.299
971195AH1-057 GEN
Solar/Wind Harmer
0.391
233998TM1NIN_3.36
Solar/Wind Harmer
0.453
232404W1-003 C
Solar/Wind Harmer
0.358
232917OH NUG6
Adder
3.139
232915OH NUG4
Adder
3.132
232434Z2-077 GEN
Solar/Wind Harmer
0.089
972177AH1-672 GEN
Solar/Wind Harmer
4.749
213560DLW11-12
Adder
0.898
232900DEMECSMY
Adder
3.212
232901NORTHST
Adder
2.86
233972AC1-094 C
Solar/Wind Harmer
0.226
219258KINSLEYDEP C
Solar/Wind Harmer
0.098
219904AC1-010 C
Solar/Wind Harmer
0.114
219907AC1-030 C
Solar/Wind Harmer
0.041
228351V2-046C
Solar/Wind Harmer
0.596
230434AG1-499 GEN
Solar/Wind Harmer
0.172
970997AG2-616 GEN
Solar/Wind Harmer
2.817
945431AF1-208 GEN
Solar/Wind Harmer
2.525
230511AF1-262
Solar/Wind Harmer
0.054
228728W1-130C
Solar/Wind Harmer
0.192
228206SHRMN CT
Adder
4.757
219304NAMERICA C
Solar/Wind Harmer
0.089
219222BRL12CT2
Adder
2.567
228732V1-021 C
Adder
0.054
218660EHAMPSOLAR C
Solar/Wind Harmer
0.05
219287REEVESEAST C
Solar/Wind Harmer
0.382
219686LUMSOLAR_N C
Solar/Wind Harmer
0.058
214194N WALES4
Adder
0.241
213611FALLS1-3
Adder
0.999
20720728JCB_W1-129
Solar/Wind Harmer
0.079
207522AF2-254 C
Solar/Wind Harmer
0.377
207487AE2-000G4
Solar/Wind Harmer
8.125
207445AB1-138_GEN
Solar/Wind Harmer
0.148
20628028LAKEHURS
Adder
0.48
963711AG1-223 GEN
Solar/Wind Harmer
0.373
20714828MDF_W3-079
Solar/Wind Harmer
0.077
219680HOPEWELLV C1
Solar/Wind Harmer
0.019
207454AA2-184 E
Solar/Wind Harmer
0.247
20715228NPK_W1-113
Solar/Wind Harmer
0.106
217197RE CRAN C
Solar/Wind Harmer
0.133
20742028HF_AC1-207
Solar/Wind Harmer
0.192
20635828PARLN1&2
Adder
1.773
20635028RRCT1&2
Adder
2.765
20635128RRCT3&4
Adder
2.669
218428ETC SOLAR C
Solar/Wind Harmer
0.008
217213AMBOY SO C
Solar/Wind Harmer
0.03
208909MACR G3
Adder
31.429
223401AF1-299 GEN
Solar/Wind Helper
0.284
213508CON10-11
50/50
1.003
213518CONOW8-9
50/50
1.003
213517CONOW7
50/50
0.741
213497CHSTR7-9
Adder
1.06
233982AB2-133 GEN
Solar/Wind Harmer
1.982
233918AB1-142 GEN
Solar/Wind Harmer
0.402
213958STHWK5-6
Adder
0.976
232417X3-008 C
Solar/Wind Harmer
0.73
960671AF2-358 GEN
Solar/Wind Harmer
6.482
232907VN8
Adder
10.817
233952AC2-187 GEN
Solar/Wind Harmer
0.404
233994AC2-023 GEN
Solar/Wind Harmer
0.964
233940AF2-379 C
Solar/Wind Harmer
0.067
234015AF2-250 C
Solar/Wind Harmer
0.043
233900O-025 C
Adder
0.421
233996TM1833_GEN
Solar/Wind Harmer
0.453
233997TMININ_4.2
Solar/Wind Harmer
0.453
232406W1-004 FULL
Solar/Wind Harmer
0.358
232914OH NUG3
Adder
3.153
232916OH NUG5
Adder
3.153
232921TASLEY2G
Adder
1.843
233990AG1-397 GEN
Solar/Wind Harmer
0.409
972073AH1-586 GEN
Solar/Wind Harmer
3.343
972133AH1-634 GEN
Solar/Wind Harmer
3.51
213560DLW11-12
Adder
0.898
233971AC1-093 C
Solar/Wind Harmer
0.268
970695AG2-447 GEN
Solar/Wind Harmer
1.222
213815MOSER1-3
Adder
1.08
228304LOGAN
Adder
6.586
219766PARADISE C
Solar/Wind Harmer
0.095
20675528CPH_W2-050
Solar/Wind Harmer
0.112
218526CNTRALGAS2 C
Solar/Wind Harmer
0.088
218524CNTRALGAS1 C
Solar/Wind Harmer
0.088
219912AD2-042 GEN
Solar/Wind Harmer
0.241
219623KINSLEYBEA C
Solar/Wind Harmer
0.128
219236SOUTHERNHQ C
Solar/Wind Harmer
0.02
230430AE1-229_GEN
Solar/Wind Harmer
2.582
219906AC1-017 C
Solar/Wind Harmer
0.065
230415AB2-049 C
Solar/Wind Harmer
0.055
971553AH1-274 GEN
Solar/Wind Harmer
0.698
228711V2-041C
Solar/Wind Harmer
0.172
228202CUMB CT
Adder
4.727
219610FLORENCE C
Solar/Wind Harmer
0.398
219348LDSOLAR C
Solar/Wind Harmer
0.172
219221BRL12CT1
Adder
2.567
219223BRL12CT3
Adder
2.567
219291REEVESSOUT C
Solar/Wind Harmer
0.017
972251AH1-710 GEN
Adder
13.602
228729W2-030 C
Solar/Wind Harmer
0.163
959561AF2-247 GEN
Solar/Wind Harmer
0.134
20716028EGP_W2-019
Solar/Wind Harmer
0.122
20720828JCB_W4-025
Solar/Wind Harmer
0.119
219727YARDVSOLFA C
Solar/Wind Harmer
0.242
20715028HAN_X4-015
Solar/Wind Harmer
0.079
20636028O CRK C1
Adder
1.823
219276PARKLANDSO C
Solar/Wind Harmer
0.12
971667AH1-334 GEN
Solar/Wind Harmer
0.703
20714528FRN_Y2-051
Solar/Wind Harmer
0.074
219918AC2-009 C
Solar/Wind Harmer
0.016
20716228APLW2-078
Solar/Wind Harmer
0.218
20720528MAN_W1-024
Solar/Wind Harmer
0.062
219612MATRIX C
Solar/Wind Harmer
0.046
218438BLK ROCK C
Solar/Wind Harmer
0.034
967451AG2-055 C O1
Solar/Wind Harmer
41.842
20635828PARLN1&2
Adder
0.803
20635928PARLN3&4
Adder
0.803
20635028RRCT1&2
Adder
2.808
20635128RRCT3&4
Adder
2.328
219908AB1-139 C
Solar/Wind Harmer
0.09
219919AE1-041 FULL
Solar/Wind Harmer
0.01
223402AF1-300 C
Solar/Wind Helper
0.284
972069AH1-584 GEN
Solar/Wind Harmer
3.195
972071AH1-585 GEN
Solar/Wind Harmer
3.195
231940T-011
Adder
0.266
970545AG2-347 GEN
Solar/Wind Harmer
23.167
232899W1-062
Adder
3.348
971149AH1-027 GEN
Solar/Wind Harmer
1.163
233939AC1-091 C
Solar/Wind Harmer
0.3
233970AC1-092 C
Solar/Wind Harmer
0.3
972233AH1-701 GEN
Adder
1.272
213815MOSER1-3
Adder
1.08
213815MOSER1-3
Adder
1.08
228304LOGAN
Adder
7.323
228307PCLP GT
Adder
3.641
219921AF1-264
Solar/Wind Harmer
0.043
228251CARLLS#4
Adder
0.183
219615MILLCREEK C
Solar/Wind Harmer
0.07
230433AD2-135 GEN
Solar/Wind Harmer
0.029
230407AD2-065 C
Solar/Wind Harmer
0.038
213535CROYDN11
Adder
2.956
230422AE1-104_GEN1
Solar/Wind Harmer
9.552
230425AE1-104_GEN2
Solar/Wind Harmer
9.552
219114HARTZY_C
Solar/Wind Harmer
0.224
20716428NHV_W2-082
Solar/Wind Harmer
0.468
207500AE2-000G1
Solar/Wind Harmer
8.125
207497AE2-000G2
Solar/Wind Harmer
8.125
207507AE2-000G3
Solar/Wind Harmer
8.125
20636128O CRK C2
Adder
1.662
20714928UPF_X1-085
Solar/Wind Harmer
0.105
963401AG1-189 GEN
Solar/Wind Harmer
0.296
963391AG1-188 GEN
Solar/Wind Harmer
0.493
20628028LAKEHURS
Adder
0.243
219817TRENTONSOL C
Solar/Wind Harmer
0.28
20720628TIN_W1-124
Solar/Wind Harmer
0.246
20641628MLH_W1-032
Solar/Wind Harmer
0.072
20716928W4-060COL
Solar/Wind Harmer
0.172
924131AB2-057 GEN
Solar/Wind Harmer
0.248
218440SUMMTASSOC C
Solar/Wind Harmer
0.03
20673828FLE_V3-070
Solar/Wind Harmer
0.108
208835TUHI V3-051
Solar/Wind Helper
0.011
208835TUHI V3-051
Solar/Wind Helper
0.011
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.016
G-007ALTFEXP_G-007A->PJM
CMTX
12.213
CBM NorthLTFEXP_CBM-N->PJM
CBM
15.754
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.82
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.554
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
30.964
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.597
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
3.864

Details for PCHBTMTP-COOPER2 230.0 kV Ckt 1 line l/o PECO_P4_PEACH245_SRT-A/* $ CHESCO $ PECO_P4_PEACH245 $ STBK


Base Case Flowgate

Area:PECO
Facility Description:
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line
Contingency Name:
PECO_P4_PEACH245_SRT-A/* $ CHESCO $ PECO_P4_PEACH245 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:128.45 %
Rating:578.0 MVA
Rating Type:B
MVA to Mitigate:742.45
MW Contribution:2.33
Bus #Bus NameTypeMW Contribution
213515CONOW3-4
50/50
0.747
213515CONOW3-4
50/50
0.747
213589EDDYSTN4
Adder
31.553
213587EDDYSTN3
Adder
31.525
232416X2-083
Adder
0.191
233933AB2-153 GEN
Solar/Wind Harmer
0.464
233944AB2-135 GEN
Solar/Wind Harmer
2.13
234014AF1-036_GEN
Solar/Wind Harmer
1.089
213508CON10-11
50/50
1.011
213518CONOW8-9
50/50
1.011
213514CONOW1-2
50/50
0.747
213516CONOW5-6
50/50
0.747
231918WEST 1
Adder
1.45
231917EM10
Adder
1.012
213497CHSTR7-9
Adder
1.078
213497CHSTR7-9
Adder
1.078
233930AB2-032 GEN
Solar/Wind Harmer
0.344
233915AB1-141 GEN
Solar/Wind Harmer
0.409
232422X3-066 FULL
Solar/Wind Harmer
0.101
234012AE2-112_GEN
Solar/Wind Harmer
0.926
213958STHWK5-6
Adder
0.993
232910NRG_G1
Adder
3.257
233964AF2-378 GEN
Solar/Wind Harmer
0.047
232426Y1-080 FULL
Solar/Wind Harmer
0.07
970277AG2-181 GEN
Solar/Wind Harmer
1.849
965821AG1-450 GEN
Solar/Wind Harmer
1.918
232919VN10
Adder
1.031
233954AC2-188 GEN
Solar/Wind Harmer
0.411
233950AC2-186 GEN
Solar/Wind Harmer
0.206
232428Y3-058 C
Solar/Wind Harmer
0.304
971195AH1-057 GEN
Solar/Wind Harmer
0.398
233998TM1NIN_3.36
Solar/Wind Harmer
0.461
232404W1-003 C
Solar/Wind Harmer
0.364
232917OH NUG6
Adder
3.195
232915OH NUG4
Adder
3.188
232434Z2-077 GEN
Solar/Wind Harmer
0.09
972177AH1-672 GEN
Solar/Wind Harmer
4.835
213560DLW11-12
Adder
0.915
232900DEMECSMY
Adder
3.27
232901NORTHST
Adder
2.913
233972AC1-094 C
Solar/Wind Harmer
0.23
219258KINSLEYDEP C
Solar/Wind Harmer
0.1
219904AC1-010 C
Solar/Wind Harmer
0.117
219907AC1-030 C
Solar/Wind Harmer
0.042
228351V2-046C
Solar/Wind Harmer
0.608
230434AG1-499 GEN
Solar/Wind Harmer
0.175
970997AG2-616 GEN
Solar/Wind Harmer
2.874
945431AF1-208 GEN
Solar/Wind Harmer
2.575
230511AF1-262
Solar/Wind Harmer
0.055
228728W1-130C
Solar/Wind Harmer
0.196
228206SHRMN CT
Adder
4.854
219304NAMERICA C
Solar/Wind Harmer
0.091
219222BRL12CT2
Adder
2.62
228732V1-021 C
Adder
0.055
218660EHAMPSOLAR C
Solar/Wind Harmer
0.051
219686LUMSOLAR_N C
Solar/Wind Harmer
0.059
219287REEVESEAST C
Solar/Wind Harmer
0.39
214194N WALES4
Adder
0.246
213611FALLS1-3
Adder
1.02
20720728JCB_W1-129
Solar/Wind Harmer
0.08
207522AF2-254 C
Solar/Wind Harmer
0.386
207487AE2-000G4
Solar/Wind Harmer
8.307
207445AB1-138_GEN
Solar/Wind Harmer
0.151
20628028LAKEHURS
Adder
0.491
963711AG1-223 GEN
Solar/Wind Harmer
0.381
20714828MDF_W3-079
Solar/Wind Harmer
0.079
219680HOPEWELLV C1
Solar/Wind Harmer
0.02
207454AA2-184 E
Solar/Wind Harmer
0.253
20715228NPK_W1-113
Solar/Wind Harmer
0.108
217197RE CRAN C
Solar/Wind Harmer
0.136
20742028HF_AC1-207
Solar/Wind Harmer
0.197
20635828PARLN1&2
Adder
1.817
20635028RRCT1&2
Adder
2.833
20635128RRCT3&4
Adder
2.735
218428ETC SOLAR C
Solar/Wind Harmer
0.009
217213AMBOY SO C
Solar/Wind Harmer
0.031
972275AH1-722 GEN
Adder
7.572
207528AF2-192 GEN
Solar/Wind Harmer
0.133
20673628F1S_V4-069
Solar/Wind Harmer
0.043
20675428EAM_W2-061
Solar/Wind Harmer
0.045
20676428JCR_X2-075
Solar/Wind Harmer
0.082
218449LINSOLAR C
Solar/Wind Harmer
0.239
208909MACR G3
Adder
32.41
223401AF1-299 GEN
Solar/Wind Helper
0.27
213508CON10-11
50/50
1.011
213518CONOW8-9
50/50
1.011
213517CONOW7
50/50
0.747
213497CHSTR7-9
Adder
1.078
233982AB2-133 GEN
Solar/Wind Harmer
2.015
233918AB1-142 GEN
Solar/Wind Harmer
0.409
213958STHWK5-6
Adder
0.993
232417X3-008 C
Solar/Wind Harmer
0.743
960671AF2-358 GEN
Solar/Wind Harmer
6.596
232907VN8
Adder
11.009
233952AC2-187 GEN
Solar/Wind Harmer
0.411
233994AC2-023 GEN
Solar/Wind Harmer
0.982
233940AF2-379 C
Solar/Wind Harmer
0.068
233900O-025 C
Adder
0.429
234015AF2-250 C
Solar/Wind Harmer
0.044
233996TM1833_GEN
Solar/Wind Harmer
0.461
233997TMININ_4.2
Solar/Wind Harmer
0.461
232406W1-004 FULL
Solar/Wind Harmer
0.364
232914OH NUG3
Adder
3.209
232916OH NUG5
Adder
3.209
232921TASLEY2G
Adder
1.876
233990AG1-397 GEN
Solar/Wind Harmer
0.417
972073AH1-586 GEN
Solar/Wind Harmer
3.403
972133AH1-634 GEN
Solar/Wind Harmer
3.573
213560DLW11-12
Adder
0.915
233971AC1-093 C
Solar/Wind Harmer
0.273
970695AG2-447 GEN
Solar/Wind Harmer
1.245
213815MOSER1-3
Adder
1.102
228304LOGAN
Adder
6.716
219766PARADISE C
Solar/Wind Harmer
0.097
219912AD2-042 GEN
Solar/Wind Harmer
0.245
219623KINSLEYBEA C
Solar/Wind Harmer
0.131
219236SOUTHERNHQ C
Solar/Wind Harmer
0.02
230430AE1-229_GEN
Solar/Wind Harmer
2.634
219906AC1-017 C
Solar/Wind Harmer
0.066
230415AB2-049 C
Solar/Wind Harmer
0.056
971553AH1-274 GEN
Solar/Wind Harmer
0.712
228711V2-041C
Solar/Wind Harmer
0.176
228202CUMB CT
Adder
4.823
219610FLORENCE C
Solar/Wind Harmer
0.407
219348LDSOLAR C
Solar/Wind Harmer
0.176
219221BRL12CT1
Adder
2.62
219223BRL12CT3
Adder
2.62
219291REEVESSOUT C
Solar/Wind Harmer
0.018
972251AH1-710 GEN
Adder
13.877
228729W2-030 C
Solar/Wind Harmer
0.166
959561AF2-247 GEN
Solar/Wind Harmer
0.137
20716028EGP_W2-019
Solar/Wind Harmer
0.125
20720828JCB_W4-025
Solar/Wind Harmer
0.122
219727YARDVSOLFA C
Solar/Wind Harmer
0.247
20715028HAN_X4-015
Solar/Wind Harmer
0.08
20636028O CRK C1
Adder
1.864
219276PARKLANDSO C
Solar/Wind Harmer
0.123
971667AH1-334 GEN
Solar/Wind Harmer
0.719
20714528FRN_Y2-051
Solar/Wind Harmer
0.076
219918AC2-009 C
Solar/Wind Harmer
0.016
20716228APLW2-078
Solar/Wind Harmer
0.223
20720528MAN_W1-024
Solar/Wind Harmer
0.064
219612MATRIX C
Solar/Wind Harmer
0.047
218438BLK ROCK C
Solar/Wind Harmer
0.035
967451AG2-055 C O1
Solar/Wind Harmer
42.856
20635828PARLN1&2
Adder
0.823
20635928PARLN3&4
Adder
0.823
20635028RRCT1&2
Adder
2.878
20635128RRCT3&4
Adder
2.386
219908AB1-139 C
Solar/Wind Harmer
0.092
219919AE1-041 FULL
Solar/Wind Harmer
0.01
219249CENTRALDIV C
Solar/Wind Harmer
0.01
20673728F2S_V4-070
Solar/Wind Harmer
0.043
223402AF1-300 C
Solar/Wind Helper
0.27
231131BLOOM ENRGY
Adder
1.722
232424Y1-079 C
Solar/Wind Harmer
0.222
233984AB2-036 GEN
Solar/Wind Harmer
4.884
234041AC1-190 GEN
Solar/Wind Harmer
3.324
233987AB2-037 GEN
Solar/Wind Harmer
4.214
234036AF2-325 C
Solar/Wind Harmer
0.339
233946AB2-136 GEN
Solar/Wind Harmer
1.475
232926CRISFLD1
Adder
0.714
233901CHERRYDALE C
Solar/Wind Harmer
0.409
232408W1-005 C
Solar/Wind Harmer
0.364
232410W1-006 C
Solar/Wind Harmer
0.364
232918OH NUG7
Adder
3.188
232905CHERITON_25
Adder
0.892
971747AH1-380 GEN
Solar/Wind Harmer
1.301
972069AH1-584 GEN
Solar/Wind Harmer
3.252
972071AH1-585 GEN
Solar/Wind Harmer
3.252
231940T-011
Adder
0.271
970545AG2-347 GEN
Solar/Wind Harmer
23.583
232899W1-062
Adder
3.409
971149AH1-027 GEN
Solar/Wind Harmer
1.185
233939AC1-091 C
Solar/Wind Harmer
0.305
233970AC1-092 C
Solar/Wind Harmer
0.305
972233AH1-701 GEN
Adder
1.297
213815MOSER1-3
Adder
1.102
213815MOSER1-3
Adder
1.102
228304LOGAN
Adder
7.467
228307PCLP GT
Adder
3.712
219921AF1-264
Solar/Wind Harmer
0.044
228251CARLLS#4
Adder
0.187
219615MILLCREEK C
Solar/Wind Harmer
0.071
230433AD2-135 GEN
Solar/Wind Harmer
0.03
230407AD2-065 C
Solar/Wind Harmer
0.039
213535CROYDN11
Adder
3.017
230422AE1-104_GEN1
Solar/Wind Harmer
9.748
230425AE1-104_GEN2
Solar/Wind Harmer
9.748
219114HARTZY_C
Solar/Wind Harmer
0.229
20716428NHV_W2-082
Solar/Wind Harmer
0.478
207500AE2-000G1
Solar/Wind Harmer
8.307
207497AE2-000G2
Solar/Wind Harmer
8.307
207507AE2-000G3
Solar/Wind Harmer
8.307
20636128O CRK C2
Adder
1.7
20714928UPF_X1-085
Solar/Wind Harmer
0.108
963401AG1-189 GEN
Solar/Wind Harmer
0.303
963391AG1-188 GEN
Solar/Wind Harmer
0.504
20628028LAKEHURS
Adder
0.248
219817TRENTONSOL C
Solar/Wind Harmer
0.287
20720628TIN_W1-124
Solar/Wind Harmer
0.252
20641628MLH_W1-032
Solar/Wind Harmer
0.074
20716928W4-060COL
Solar/Wind Harmer
0.176
924131AB2-057 GEN
Solar/Wind Harmer
0.254
218440SUMMTASSOC C
Solar/Wind Harmer
0.031
20673828FLE_V3-070
Solar/Wind Harmer
0.111
218418LINDEN_G5
Adder
4.119
218419LINDEN_G6
Adder
4.119
972260AH1-715 GEN1
Adder
3.298
207442AE1-156 GEN
Solar/Wind Harmer
0.178
20676128MHD_W3-029
Solar/Wind Harmer
0.114
219036LINDEN_G7
Adder
3.972
219035LINDEN_G8
Adder
3.915
972261AH1-715 GEN2
Adder
3.802
213514CONOW1-2
50/50
0.56
213516CONOW5-6
50/50
0.56
233935AB2-179 C
Solar/Wind Harmer
1.165
231919CHRIST1
Adder
1.889
231920CHRIST2
Adder
1.847
971983AH1-536 GEN
Solar/Wind Harmer
3.085
232436AB1-176 C
Solar/Wind Harmer
0.093
233968AD2-076_GEN
Solar/Wind Harmer
2.668
970597AG2-380 GEN
Solar/Wind Harmer
1.675
231906DC3 NUG
Adder
5.55
231902DC CT7
Adder
4.437
231907DC10
Adder
1.385
213942SCHUYLKILL
Adder
1.31
213942SCHUYLKILL
Adder
1.002
213957STHWK3-4
Adder
0.993
213957STHWK3-4
Adder
0.993
232813VAUGHN
Adder
0.219
233955AB2-172 GEN
Solar/Wind Harmer
1.858
233923SMA
Solar/Wind Harmer
1.69
232912OH NUG1
Adder
3.209
232913OH NUG2
Adder
3.167
233990AG1-397 GEN
Solar/Wind Harmer
0.02
232432Z2-076 GEN
Solar/Wind Harmer
0.048
232920IR10
Adder
1.14
234033AF1-007_GEN
Solar/Wind Harmer
8.427
232904IR4
Adder
29.139
213561DLWR9-10
Adder
1.197
213561DLWR9-10
Adder
0.915
233973AC2-185 C
Solar/Wind Harmer
1.255
219137THOSOLAR C
Solar/Wind Harmer
0.377
219914AD2-027 C
Solar/Wind Harmer
0.185
971011AG2-627 GEN
Solar/Wind Harmer
2.329
228309CCLP NUG
Adder
7.816
228309CCLP NUG
Adder
7.434
964001AG1-254 GEN
Solar/Wind Harmer
0.614
972141AH1-641 GEN
Solar/Wind Harmer
0.862
228260V4-054C
Solar/Wind Harmer
0.305
971535AH1-265 GEN
Solar/Wind Harmer
1.258
219272CLEANLIGHT C
Solar/Wind Harmer
0.054
970453AG2-297 GEN
Solar/Wind Harmer
0.804
219607WPEMNERT C
Solar/Wind Harmer
0.123
219224BRL12CT4
Adder
2.62
219688LUMSOLAR_S C
Solar/Wind Harmer
0.059
228754AB1-001 C
Solar/Wind Harmer
0.04
227927V4-067C
Solar/Wind Harmer
0.057
214067T20SOLAR
Solar/Wind Harmer
0.073
213611FALLS1-3
Adder
1.02
213611FALLS1-3
Adder
1.02
20717128DIX_Z2-102
Solar/Wind Harmer
0.354
20715728PEM_W1-119
Solar/Wind Harmer
0.143
20715828PEM_W1-120
Solar/Wind Harmer
0.143
971189AH1-054 GEN
Solar/Wind Harmer
0.311
970025AG2-016 GEN
Solar/Wind Harmer
0.745
207459AE1-142 C O1
Solar/Wind Harmer
0.276
219620RIDERU C
Solar/Wind Harmer
0.015
20714328BYD_X4-031
Solar/Wind Harmer
0.072
20714428HOW_X1-037
Solar/Wind Harmer
0.313
971521AH1-258 GEN
Solar/Wind Harmer
0.679
20720428HOL_W1-112
Solar/Wind Harmer
0.087
218455CINNBAY_CGEN
Adder
0.449
20635928PARLN3&4
Adder
1.817
20675528CPH_W2-050
Solar/Wind Harmer
0.115
218526CNTRALGAS2 C
Solar/Wind Harmer
0.09
218524CNTRALGAS1 C
Solar/Wind Harmer
0.09
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.016
G-007ALTFEXP_G-007A->PJM
CMTX
12.515
CBM NorthLTFEXP_CBM-N->PJM
CBM
16.193
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.822
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.562
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
31.768
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.597
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
3.874

Details for PCHBTMTP-COOPER2 230.0 kV Ckt 1 line l/o PECO_P1-2_5012_SRT-A


Base Case Flowgate

Area:PECO
Facility Description:
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line
Contingency Name:
PECO_P1-2_5012_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.24 %
Rating:578.0 MVA
Rating Type:B
MVA to Mitigate:694.96
MW Contribution:1.62
Bus #Bus NameTypeMW Contribution
213508CON10-11
50/50
1.01
213518CONOW8-9
50/50
1.01
213517CONOW7
50/50
0.746
213890PHLISCT3
50/50
0.935
213888PHLISCT1
50/50
0.934
213739LIBE_CT2
50/50
0.778
213497CHSTR7-9
Adder
1.074
233982AB2-133 GEN
Solar/Wind Harmer
0.002
233918AB1-142 GEN
Solar/Wind Harmer
0.106
213958STHWK5-6
Adder
0.989
232417X3-008 C
Solar/Wind Harmer
0
960671AF2-358 GEN
Solar/Wind Harmer
4.583
232907VN8
Adder
10.963
233952AC2-187 GEN
Solar/Wind Harmer
0
233994AC2-023 GEN
Solar/Wind Harmer
0.002
233940AF2-379 C
Solar/Wind Harmer
0
233900O-025 C
Adder
0.427
234015AF2-250 C
Solar/Wind Harmer
0
233996TM1833_GEN
Solar/Wind Harmer
0.001
233997TMININ_4.2
Solar/Wind Harmer
0.001
232406W1-004 FULL
Solar/Wind Harmer
0.234
232921TASLEY2G
Adder
1.868
232914OH NUG3
Adder
3.196
232916OH NUG5
Adder
3.196
233990AG1-397 GEN
Solar/Wind Harmer
0.493
972073AH1-586 GEN
Solar/Wind Harmer
3.388
972133AH1-634 GEN
Solar/Wind Harmer
1.323
213560DLW11-12
Adder
0.911
233971AC1-093 C
Solar/Wind Harmer
0.015
970695AG2-447 GEN
Solar/Wind Harmer
0.865
213815MOSER1-3
Adder
1.097
228304LOGAN
Adder
6.684
219766PARADISE C
Solar/Wind Harmer
0
219912AD2-042 GEN
Solar/Wind Harmer
0
219623KINSLEYBEA C
Solar/Wind Harmer
0
230430AE1-229_GEN
Solar/Wind Harmer
0.005
219906AC1-017 C
Solar/Wind Harmer
0
230415AB2-049 C
Solar/Wind Harmer
0
971553AH1-274 GEN
Solar/Wind Harmer
0.457
228711V2-041C
Solar/Wind Harmer
0
228202CUMB CT
Adder
4.799
219610FLORENCE C
Solar/Wind Harmer
0
219348LDSOLAR C
Solar/Wind Harmer
0
213508CON10-11
50/50
1.01
213518CONOW8-9
50/50
1.01
213514CONOW1-2
50/50
0.746
213516CONOW5-6
50/50
0.746
231918WEST 1
50/50
1.533
213889PHLISCT2
50/50
0.934
231917EM10
50/50
1.07
213738LIBE_CT1
50/50
0.778
213497CHSTR7-9
Adder
1.074
213497CHSTR7-9
Adder
1.074
233930AB2-032 GEN
Solar/Wind Harmer
0.394
233915AB1-141 GEN
Solar/Wind Harmer
0.106
232422X3-066 FULL
Solar/Wind Harmer
0.034
234012AE2-112_GEN
Solar/Wind Harmer
0.932
213958STHWK5-6
Adder
0.989
232910NRG_G1
Adder
3.243
233964AF2-378 GEN
Solar/Wind Harmer
0
232426Y1-080 FULL
Solar/Wind Harmer
0
970277AG2-181 GEN
Solar/Wind Harmer
0.214
965821AG1-450 GEN
Solar/Wind Harmer
1.909
232919VN10
Adder
1.027
233954AC2-188 GEN
Solar/Wind Harmer
0
233950AC2-186 GEN
Solar/Wind Harmer
0
232428Y3-058 C
Solar/Wind Harmer
0.001
971195AH1-057 GEN
Solar/Wind Harmer
0.226
213515CONOW3-4
50/50
0.746
213515CONOW3-4
50/50
0.746
213514CONOW1-2
50/50
0.56
213516CONOW5-6
50/50
0.56
213893PHLISST1
50/50
1.345
231916EM3
50/50
0.419
231919CHRIST1
50/50
1.997
231920CHRIST2
50/50
1.953
231901EM4
50/50
0.843
213740LIBE_ST1
50/50
1.071
231505HR4
50/50
0.884
233935AB2-179 C
Solar/Wind Harmer
0.64
971983AH1-536 GEN
Solar/Wind Harmer
0.727
232436AB1-176 C
Solar/Wind Harmer
0
233968AD2-076_GEN
Solar/Wind Harmer
0.932
970597AG2-380 GEN
Solar/Wind Harmer
1.669
231906DC3 NUG
Adder
5.528
231902DC CT7
Adder
4.419
231907DC10
Adder
1.38
213942SCHUYLKILL
Adder
1.305
213942SCHUYLKILL
Adder
0.998
213957STHWK3-4
Adder
0.989
213957STHWK3-4
Adder
0.989
232813VAUGHN
Adder
0.218
233955AB2-172 GEN
Solar/Wind Harmer
0.001
233923SMA
Solar/Wind Harmer
0.002
232912OH NUG1
Adder
3.196
232913OH NUG2
Adder
3.153
233990AG1-397 GEN
Solar/Wind Harmer
-0.058
232432Z2-076 GEN
Solar/Wind Harmer
0.005
232920IR10
Adder
1.135
234033AF1-007_GEN
Solar/Wind Harmer
0
232904IR4
Adder
29.014
231909HR2
50/50
0.609
231908HR1
50/50
0.606
231910HR3
50/50
0.606
213589EDDYSTN4
Adder
31.437
213587EDDYSTN3
Adder
31.41
232416X2-083
Adder
0.19
233933AB2-153 GEN
Solar/Wind Harmer
0.001
233944AB2-135 GEN
Solar/Wind Harmer
0.002
234014AF1-036_GEN
Solar/Wind Harmer
0.932
231131BLOOM ENRGY
Adder
1.715
232424Y1-079 C
Solar/Wind Harmer
0
233984AB2-036 GEN
Solar/Wind Harmer
2.839
234041AC1-190 GEN
Solar/Wind Harmer
2.694
233987AB2-037 GEN
Solar/Wind Harmer
0.004
234036AF2-325 C
Solar/Wind Harmer
0
233946AB2-136 GEN
Solar/Wind Harmer
0.001
232926CRISFLD1
Adder
0.711
233901CHERRYDALE C
Solar/Wind Harmer
0
232408W1-005 C
Solar/Wind Harmer
0.234
232410W1-006 C
Solar/Wind Harmer
0.234
232905CHERITON_25
Adder
0.888
232918OH NUG7
Adder
3.174
971747AH1-380 GEN
Solar/Wind Harmer
0.904
972069AH1-584 GEN
Solar/Wind Harmer
2.259
972071AH1-585 GEN
Solar/Wind Harmer
2.259
231940T-011
Adder
0.269
970545AG2-347 GEN
Solar/Wind Harmer
9.059
232899W1-062
Adder
3.394
971149AH1-027 GEN
Solar/Wind Harmer
1.089
233939AC1-091 C
Solar/Wind Harmer
0.001
233970AC1-092 C
Solar/Wind Harmer
0.001
972233AH1-701 GEN
Adder
1.291
213815MOSER1-3
Adder
1.097
213815MOSER1-3
Adder
1.097
228304LOGAN
Adder
7.432
228307PCLP GT
Adder
3.695
219921AF1-264
Solar/Wind Harmer
0
228251CARLLS#4
Adder
0.186
219615MILLCREEK C
Solar/Wind Harmer
0
230407AD2-065 C
Solar/Wind Harmer
0
213535CROYDN11
Adder
3.002
230422AE1-104_GEN1
Solar/Wind Harmer
3.894
230425AE1-104_GEN2
Solar/Wind Harmer
3.894
219114HARTZY_C
Solar/Wind Harmer
0
20716428NHV_W2-082
Solar/Wind Harmer
0
207500AE2-000G1
Solar/Wind Harmer
3.316
207497AE2-000G2
Solar/Wind Harmer
3.316
207507AE2-000G3
Solar/Wind Harmer
3.316
20636128O CRK C2
Adder
1.69
20714928UPF_X1-085
Solar/Wind Harmer
0
20628028LAKEHURS
Adder
0.247
20720628TIN_W1-124
Solar/Wind Harmer
0
20716928W4-060COL
Solar/Wind Harmer
0
218440SUMMTASSOC C
Solar/Wind Harmer
0
20673828FLE_V3-070
Solar/Wind Harmer
0
218418LINDEN_G5
Adder
4.092
218419LINDEN_G6
Adder
4.092
972260AH1-715 GEN1
Adder
3.277
207442AE1-156 GEN
Solar/Wind Harmer
0.014
20676128MHD_W3-029
Solar/Wind Harmer
0
233998TM1NIN_3.36
Solar/Wind Harmer
0.001
232404W1-003 C
Solar/Wind Harmer
0.234
232917OH NUG6
Adder
3.182
232915OH NUG4
Adder
3.174
232434Z2-077 GEN
Solar/Wind Harmer
0.015
972177AH1-672 GEN
Solar/Wind Harmer
3.649
213560DLW11-12
Adder
0.911
232900DEMECSMY
Adder
3.256
232901NORTHST
Adder
2.9
233972AC1-094 C
Solar/Wind Harmer
0.109
219258KINSLEYDEP C
Solar/Wind Harmer
0
219904AC1-010 C
Solar/Wind Harmer
0
219907AC1-030 C
Solar/Wind Harmer
0
228351V2-046C
Solar/Wind Harmer
0
230434AG1-499 GEN
Solar/Wind Harmer
0
970997AG2-616 GEN
Solar/Wind Harmer
2.151
945431AF1-208 GEN
Solar/Wind Harmer
1.788
230511AF1-262
Solar/Wind Harmer
0
228728W1-130C
Solar/Wind Harmer
0
228206SHRMN CT
Adder
4.83
219304NAMERICA C
Solar/Wind Harmer
0.027
219222BRL12CT2
Adder
2.607
228732V1-021 C
Adder
0.055
218660EHAMPSOLAR C
Solar/Wind Harmer
0
219686LUMSOLAR_N C
Solar/Wind Harmer
0
219287REEVESEAST C
Solar/Wind Harmer
0
214194N WALES4
Adder
0.245
213611FALLS1-3
Adder
1.014
20720728JCB_W1-129
Solar/Wind Harmer
0
207522AF2-254 C
Solar/Wind Harmer
0.248
207487AE2-000G4
Solar/Wind Harmer
3.316
207445AB1-138_GEN
Solar/Wind Harmer
0
20628028LAKEHURS
Adder
0.489
20714828MDF_W3-079
Solar/Wind Harmer
0.025
207454AA2-184 E
Solar/Wind Harmer
0
20715228NPK_W1-113
Solar/Wind Harmer
0
217197RE CRAN C
Solar/Wind Harmer
0
20742028HF_AC1-207
Solar/Wind Harmer
0
20635828PARLN1&2
Adder
1.806
20635028RRCT1&2
Adder
2.816
20635128RRCT3&4
Adder
2.718
219221BRL12CT1
Adder
2.607
219223BRL12CT3
Adder
2.607
972251AH1-710 GEN
Adder
13.808
228729W2-030 C
Solar/Wind Harmer
0
20716028EGP_W2-019
Solar/Wind Harmer
0
20720828JCB_W4-025
Solar/Wind Harmer
0
219727YARDVSOLFA C
Solar/Wind Harmer
0
20715028HAN_X4-015
Solar/Wind Harmer
0
20636028O CRK C1
Adder
1.854
219276PARKLANDSO C
Solar/Wind Harmer
0
971667AH1-334 GEN
Solar/Wind Harmer
0.462
20714528FRN_Y2-051
Solar/Wind Harmer
0
20716228APLW2-078
Solar/Wind Harmer
0
20720528MAN_W1-024
Solar/Wind Harmer
0
219612MATRIX C
Solar/Wind Harmer
0
218438BLK ROCK C
Solar/Wind Harmer
0
967451AG2-055 C O1
Solar/Wind Harmer
60.853
20635828PARLN1&2
Adder
0.818
20635928PARLN3&4
Adder
0.818
20635028RRCT1&2
Adder
2.86
20635128RRCT3&4
Adder
2.371
219908AB1-139 C
Solar/Wind Harmer
0
20673728F2S_V4-070
Solar/Wind Harmer
0
223402AF1-300 C
Solar/Wind Helper
0.271
213561DLWR9-10
Adder
1.191
213561DLWR9-10
Adder
0.911
233973AC2-185 C
Solar/Wind Harmer
0.001
219914AD2-027 C
Solar/Wind Harmer
0
971011AG2-627 GEN
Solar/Wind Harmer
1.617
228309CCLP NUG
Adder
7.778
228309CCLP NUG
Adder
7.399
964001AG1-254 GEN
Solar/Wind Harmer
0.117
972141AH1-641 GEN
Solar/Wind Harmer
0.998
228260V4-054C
Solar/Wind Harmer
0
971535AH1-265 GEN
Solar/Wind Harmer
0.809
219272CLEANLIGHT C
Solar/Wind Harmer
0
970453AG2-297 GEN
Solar/Wind Harmer
0.739
219607WPEMNERT C
Solar/Wind Harmer
0
219224BRL12CT4
Adder
2.607
219688LUMSOLAR_S C
Solar/Wind Harmer
0
228754AB1-001 C
Solar/Wind Harmer
0
227927V4-067C
Solar/Wind Harmer
0
214067T20SOLAR
Solar/Wind Harmer
0
213611FALLS1-3
Adder
1.014
213611FALLS1-3
Adder
1.014
20717128DIX_Z2-102
Solar/Wind Harmer
0
20715728PEM_W1-119
Solar/Wind Harmer
0
20715828PEM_W1-120
Solar/Wind Harmer
0
971189AH1-054 GEN
Solar/Wind Harmer
0.2
970025AG2-016 GEN
Solar/Wind Harmer
0.479
207459AE1-142 C O1
Solar/Wind Harmer
0
20714328BYD_X4-031
Solar/Wind Harmer
0.038
20714428HOW_X1-037
Solar/Wind Harmer
0
971521AH1-258 GEN
Solar/Wind Harmer
0.436
20720428HOL_W1-112
Solar/Wind Harmer
0
218455CINNBAY_CGEN
Adder
0.446
20635928PARLN3&4
Adder
1.806
218526CNTRALGAS2 C
Solar/Wind Harmer
0.186
218524CNTRALGAS1 C
Solar/Wind Harmer
0.184
217213AMBOY SO C
Solar/Wind Harmer
0
972275AH1-722 GEN
Adder
7.523
207528AF2-192 GEN
Solar/Wind Harmer
0
20673628F1S_V4-069
Solar/Wind Harmer
0
20675428EAM_W2-061
Solar/Wind Harmer
0
208909MACR G3
Adder
32.152
223401AF1-299 GEN
Solar/Wind Helper
0.271
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.034
G-007ALTFEXP_G-007A->PJM
CMTX
12.437
CBM NorthLTFEXP_CBM-N->PJM
CBM
16.035
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.84
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.618
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
31.56
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.609
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
3.958

Details for RICHMOND35-WANEETA3 230.0 kV Ckt 1 line l/o PECO_P4_CHICH045_SRT-A/* $ DELCO $ PECO_P4_CHICH045 $ STBK


Base Case Flowgate

Area:PECO
Facility Description:
RICHMOND35-WANEETA3 230.0 kV Ckt 1 line
Contingency Name:
PECO_P4_CHICH045_SRT-A/* $ DELCO $ PECO_P4_CHICH045 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:118.19 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1394.62
MW Contribution:8.27
Bus #Bus NameTypeMW Contribution
213918RICHMD91
50/50
1.234
219230EAGLE PT CT1
50/50
1.468
219235Y2-105
50/50
0.53
219222BRL12CT2
50/50
10.293
219904AC1-010 C
Solar/Wind Harmer
0.575
219258KINSLEYDEP C
Solar/Wind Harmer
0.469
219907AC1-030 C
Solar/Wind Harmer
0.198
219304NAMERICA C
Solar/Wind Harmer
0.338
230434AG1-499 GEN
Solar/Wind Harmer
0.622
228351V2-046C
Solar/Wind Harmer
2.092
218660EHAMPSOLAR C
Solar/Wind Harmer
0.181
219686LUMSOLAR_N C
Solar/Wind Harmer
0.206
219287REEVESEAST C
Solar/Wind Harmer
1.371
970997AG2-616 GEN
Solar/Wind Harmer
9.619
230511AF1-262
Solar/Wind Harmer
0.182
945431AF1-208 GEN
Solar/Wind Harmer
8.422
228728W1-130C
Solar/Wind Harmer
0.635
228206SHRMN CT
Adder
14.479
228732V1-021 C
Adder
0.159
213611FALLS1-3
Adder
2.517
20720728JCB_W1-129
Solar/Wind Harmer
0.2
207522AF2-254 C
Solar/Wind Harmer
0.953
207487AE2-000G4
Solar/Wind Harmer
17.443
207445AB1-138_GEN
Solar/Wind Harmer
0.302
20628028LAKEHURS
Adder
0.98
231917EM10
Adder
1.289
231918WEST 1
Adder
1.725
963711AG1-223 GEN
Solar/Wind Harmer
0.689
20714828MDF_W3-079
Solar/Wind Harmer
0.142
233972AC1-094 C
Solar/Wind Harmer
0.319
232901NORTHST
Adder
3.979
232900DEMECSMY
Adder
4.386
972177AH1-672 GEN
Solar/Wind Harmer
6.299
232434Z2-077 GEN
Solar/Wind Harmer
0.117
233954AC2-188 GEN
Solar/Wind Harmer
0.524
233950AC2-186 GEN
Solar/Wind Harmer
0.262
232404W1-003 C
Solar/Wind Harmer
0.465
232917OH NUG6
Adder
4.086
232915OH NUG4
Adder
4.077
971195AH1-057 GEN
Solar/Wind Harmer
0.508
233998TM1NIN_3.36
Solar/Wind Harmer
0.588
232428Y3-058 C
Solar/Wind Harmer
0.387
232919VN10
Adder
1.294
965821AG1-450 GEN
Solar/Wind Harmer
2.398
232426Y1-080 FULL
Solar/Wind Harmer
0.088
970277AG2-181 GEN
Solar/Wind Harmer
2.308
233964AF2-378 GEN
Solar/Wind Harmer
0.059
232910NRG_G1
Adder
3.954
234012AE2-112_GEN
Solar/Wind Harmer
1.007
232422X3-066 FULL
Solar/Wind Harmer
0.109
233930AB2-032 GEN
Solar/Wind Harmer
0.36
233915AB1-141 GEN
Solar/Wind Harmer
0.428
207454AA2-184 E
Solar/Wind Harmer
0.394
217197RE CRAN C
Solar/Wind Harmer
0.205
20715228NPK_W1-113
Solar/Wind Harmer
0.147
20742028HF_AC1-207
Solar/Wind Harmer
0.264
219680HOPEWELLV C1
Solar/Wind Harmer
0.024
20635828PARLN1&2
Adder
2.217
20635028RRCT1&2
Adder
3.28
20635128RRCT3&4
Adder
3.167
218428ETC SOLAR C
Solar/Wind Harmer
0.009
217213AMBOY SO C
Solar/Wind Harmer
0.032
972275AH1-722 GEN
Adder
7.525
219126CAMDEN_CTG
50/50
1.481
219267WHEELBRDEPTF
50/50
0.208
219240MANTUACREK E
50/50
0.676
219726BAT.STORG E
50/50
0.331
972233AH1-701 GEN
50/50
5.259
228304LOGAN
50/50
29.813
228307PCLP GT
50/50
14.49
213400COVANTA DELA
50/50
1.006
219921AF1-264
Solar/Wind Harmer
0.212
219615MILLCREEK C
Solar/Wind Harmer
0.293
213535CROYDN11
Adder
10.659
230407AD2-065 C
Solar/Wind Harmer
0.129
230433AD2-135 GEN
Solar/Wind Harmer
0.097
228251CARLLS#4
Adder
0.598
230422AE1-104_GEN1
Solar/Wind Harmer
28.184
230425AE1-104_GEN2
Solar/Wind Harmer
28.184
219114HARTZY_C
Solar/Wind Harmer
0.594
20716428NHV_W2-082
Solar/Wind Harmer
1.189
20714928UPF_X1-085
Solar/Wind Harmer
0.23
207500AE2-000G1
Solar/Wind Harmer
17.443
207497AE2-000G2
Solar/Wind Harmer
17.443
207507AE2-000G3
Solar/Wind Harmer
17.443
20636128O CRK C2
Adder
3.568
963401AG1-189 GEN
Solar/Wind Harmer
0.63
963391AG1-188 GEN
Solar/Wind Harmer
1.044
20628028LAKEHURS
Adder
0.496
233939AC1-091 C
Solar/Wind Harmer
0.423
233970AC1-092 C
Solar/Wind Harmer
0.423
971149AH1-027 GEN
Solar/Wind Harmer
1.618
232899W1-062
Adder
4.573
232416X2-083
Adder
0.214
970545AG2-347 GEN
Solar/Wind Harmer
30.603
231940T-011
Adder
0.347
972069AH1-584 GEN
Solar/Wind Harmer
4.165
972071AH1-585 GEN
Solar/Wind Harmer
4.165
971747AH1-380 GEN
Solar/Wind Harmer
1.665
233901CHERRYDALE C
Solar/Wind Harmer
0.523
232408W1-005 C
Solar/Wind Harmer
0.465
232410W1-006 C
Solar/Wind Harmer
0.465
232918OH NUG7
Adder
4.077
232905CHERITON_25
Adder
1.14
232926CRISFLD1
Adder
0.911
233946AB2-136 GEN
Solar/Wind Harmer
1.834
234036AF2-325 C
Solar/Wind Harmer
0.421
234041AC1-190 GEN
Solar/Wind Harmer
4.104
231131BLOOM ENRGY
Adder
1.988
233987AB2-037 GEN
Solar/Wind Harmer
5.183
233984AB2-036 GEN
Solar/Wind Harmer
5.521
232424Y1-079 C
Solar/Wind Harmer
0.249
234014AF1-036_GEN
Solar/Wind Harmer
1.184
233944AB2-135 GEN
Solar/Wind Harmer
2.287
233933AB2-153 GEN
Solar/Wind Harmer
0.486
20720628TIN_W1-124
Solar/Wind Harmer
0.392
20641628MLH_W1-032
Solar/Wind Harmer
0.1
20716928W4-060COL
Solar/Wind Harmer
0.234
219817TRENTONSOL C
Solar/Wind Harmer
0.345
924131AB2-057 GEN
Solar/Wind Harmer
0.31
218440SUMMTASSOC C
Solar/Wind Harmer
0.033
218418LINDEN_G5
Adder
4.093
218419LINDEN_G6
Adder
4.093
972260AH1-715 GEN1
Adder
3.278
219229EAGLE PT ST
50/50
0.743
219231EAGLE PT CT2
50/50
1.467
230405GT2-CC
50/50
3.263
219224BRL12CT4
50/50
10.293
219914AD2-027 C
Solar/Wind Harmer
0.958
219137THOSOLAR C
Solar/Wind Harmer
1.633
219272CLEANLIGHT C
Solar/Wind Harmer
0.202
219607WPEMNERT C
Solar/Wind Harmer
0.456
971011AG2-627 GEN
Solar/Wind Harmer
8.268
219688LUMSOLAR_S C
Solar/Wind Harmer
0.214
964001AG1-254 GEN
Solar/Wind Harmer
2.11
228309CCLP NUG
Adder
26.788
228309CCLP NUG
Adder
25.481
972141AH1-641 GEN
Solar/Wind Harmer
2.886
971535AH1-265 GEN
Solar/Wind Harmer
4.118
228260V4-054C
Solar/Wind Harmer
0.973
970453AG2-297 GEN
Solar/Wind Harmer
2.32
228754AB1-001 C
Solar/Wind Harmer
0.115
227927V4-067C
Solar/Wind Harmer
0.162
214067T20SOLAR
Solar/Wind Harmer
0.18
213611FALLS1-3
Adder
2.517
213611FALLS1-3
Adder
2.517
20717128DIX_Z2-102
Solar/Wind Harmer
0.866
20715728PEM_W1-119
Solar/Wind Harmer
0.346
20715828PEM_W1-120
Solar/Wind Harmer
0.346
971189AH1-054 GEN
Solar/Wind Harmer
0.673
970025AG2-016 GEN
Solar/Wind Harmer
1.544
207459AE1-142 C O1
Solar/Wind Harmer
0.55
231919CHRIST1
Adder
2.318
231920CHRIST2
Adder
2.266
233973AC2-185 C
Solar/Wind Harmer
1.74
234033AF1-007_GEN
Solar/Wind Harmer
10.936
232904IR4
Adder
37.813
232920IR10
Adder
1.477
232432Z2-076 GEN
Solar/Wind Harmer
0.062
233990AG1-397 GEN
Solar/Wind Harmer
0.026
232912OH NUG1
Adder
4.105
232913OH NUG2
Adder
4.05
233923SMA
Solar/Wind Harmer
2.156
232813VAUGHN
Adder
0.271
233955AB2-172 GEN
Solar/Wind Harmer
2.291
231906DC3 NUG
Adder
6.324
231902DC CT7
Adder
5.056
231907DC10
Adder
1.579
233968AD2-076_GEN
Solar/Wind Harmer
2.901
970597AG2-380 GEN
Solar/Wind Harmer
1.822
232436AB1-176 C
Solar/Wind Harmer
0.1
971983AH1-536 GEN
Solar/Wind Harmer
3.23
20714328BYD_X4-031
Solar/Wind Harmer
0.116
20714428HOW_X1-037
Solar/Wind Harmer
0.489
233935AB2-179 C
Solar/Wind Harmer
0.997
971521AH1-258 GEN
Solar/Wind Harmer
0.989
20720428HOL_W1-112
Solar/Wind Harmer
0.124
219620RIDERU C
Solar/Wind Harmer
0.018
218455CINNBAY_CGEN
Adder
0.548
20635928PARLN3&4
Adder
2.217
218526CNTRALGAS2 C
Solar/Wind Harmer
0.102
218524CNTRALGAS1 C
Solar/Wind Harmer
0.096
213919RICHMD92
50/50
1.234
219124CAMDEN_STG
50/50
1.205
219286CAMD CO RR
50/50
0.415
230406ST-CC
50/50
4.829
230404GT1-CC
50/50
3.247
228304LOGAN
50/50
26.814
219221BRL12CT1
50/50
10.293
219223BRL12CT3
50/50
10.293
219924AG1-130 C
50/50
0.482
219912AD2-042 GEN
Solar/Wind Harmer
1.27
219766PARADISE C
Solar/Wind Harmer
0.479
219623KINSLEYBEA C
Solar/Wind Harmer
0.613
219236SOUTHERNHQ C
Solar/Wind Harmer
0.096
219906AC1-017 C
Solar/Wind Harmer
0.274
219610FLORENCE C
Solar/Wind Harmer
1.505
219348LDSOLAR C
Solar/Wind Harmer
0.651
219291REEVESSOUT C
Solar/Wind Harmer
0.062
230430AE1-229_GEN
Solar/Wind Harmer
8.807
230415AB2-049 C
Solar/Wind Harmer
0.188
971553AH1-274 GEN
Solar/Wind Harmer
2.187
959561AF2-247 GEN
Solar/Wind Harmer
0.431
228711V2-041C
Solar/Wind Harmer
0.519
228202CUMB CT
Adder
14.118
228729W2-030 C
Solar/Wind Harmer
0.478
20716028EGP_W2-019
Solar/Wind Harmer
0.313
20720828JCB_W4-025
Solar/Wind Harmer
0.304
20715028HAN_X4-015
Solar/Wind Harmer
0.2
219727YARDVSOLFA C
Solar/Wind Harmer
0.602
20636028O CRK C1
Adder
3.914
972251AH1-710 GEN
Adder
26.246
219276PARKLANDSO C
Solar/Wind Harmer
0.252
971667AH1-334 GEN
Solar/Wind Harmer
1.456
20714528FRN_Y2-051
Solar/Wind Harmer
0.136
233971AC1-093 C
Solar/Wind Harmer
0.378
970695AG2-447 GEN
Solar/Wind Harmer
1.725
972133AH1-634 GEN
Solar/Wind Harmer
4.637
233952AC2-187 GEN
Solar/Wind Harmer
0.524
972073AH1-586 GEN
Solar/Wind Harmer
4.358
233990AG1-397 GEN
Solar/Wind Harmer
0.533
232406W1-004 FULL
Solar/Wind Harmer
0.465
232914OH NUG3
Adder
4.105
232916OH NUG5
Adder
4.105
232921TASLEY2G
Adder
2.399
234015AF2-250 C
Solar/Wind Harmer
0.056
233900O-025 C
Adder
0.547
233996TM1833_GEN
Solar/Wind Harmer
0.588
233997TMININ_4.2
Solar/Wind Harmer
0.588
233940AF2-379 C
Solar/Wind Harmer
0.087
233994AC2-023 GEN
Solar/Wind Harmer
1.245
232907VN8
Adder
13.852
960671AF2-358 GEN
Solar/Wind Harmer
8.248
232417X3-008 C
Solar/Wind Harmer
0.916
233982AB2-133 GEN
Solar/Wind Harmer
2.103
233918AB1-142 GEN
Solar/Wind Harmer
0.428
219612MATRIX C
Solar/Wind Harmer
0.071
218438BLK ROCK C
Solar/Wind Harmer
0.052
20720528MAN_W1-024
Solar/Wind Harmer
0.087
20716228APLW2-078
Solar/Wind Harmer
0.301
219918AC2-009 C
Solar/Wind Harmer
0.02
20635828PARLN1&2
Adder
1.004
20635928PARLN3&4
Adder
1.004
967451AG2-055 C O1
Solar/Wind Harmer
48.983
20635028RRCT1&2
Adder
3.332
20635128RRCT3&4
Adder
2.762
219908AB1-139 C
Solar/Wind Harmer
0.097
219919AE1-041 FULL
Solar/Wind Harmer
0.01
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.625
G-007ALTFEXP_G-007A->PJM
CMTX
14.489
CBM NorthLTFEXP_CBM-N->PJM
CBM
7.986
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.604
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.879
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
26.441
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.379
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
2.801

Details for RICHMOND35-WANEETA3 230.0 kV Ckt 1 line l/o PECO_P4_CHICH195_SRT-A/* $ DELCO $ PECO_P4_CHICH195 $ STBK


Base Case Flowgate

Area:PECO
Facility Description:
RICHMOND35-WANEETA3 230.0 kV Ckt 1 line
Contingency Name:
PECO_P4_CHICH195_SRT-A/* $ DELCO $ PECO_P4_CHICH195 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:118.18 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1394.54
MW Contribution:8.27
Bus #Bus NameTypeMW Contribution
219126CAMDEN_CTG
50/50
1.481
219267WHEELBRDEPTF
50/50
0.208
219240MANTUACREK E
50/50
0.676
219726BAT.STORG E
50/50
0.331
972233AH1-701 GEN
50/50
5.259
228304LOGAN
50/50
29.813
228307PCLP GT
50/50
14.49
213400COVANTA DELA
50/50
1.006
219921AF1-264
Solar/Wind Harmer
0.212
219615MILLCREEK C
Solar/Wind Harmer
0.293
213535CROYDN11
Adder
10.659
230407AD2-065 C
Solar/Wind Harmer
0.129
230433AD2-135 GEN
Solar/Wind Harmer
0.097
228251CARLLS#4
Adder
0.598
230422AE1-104_GEN1
Solar/Wind Harmer
28.184
230425AE1-104_GEN2
Solar/Wind Harmer
28.184
219114HARTZY_C
Solar/Wind Harmer
0.594
20716428NHV_W2-082
Solar/Wind Harmer
1.189
20714928UPF_X1-085
Solar/Wind Harmer
0.23
207500AE2-000G1
Solar/Wind Harmer
17.443
207497AE2-000G2
Solar/Wind Harmer
17.443
207507AE2-000G3
Solar/Wind Harmer
17.443
20636128O CRK C2
Adder
3.568
963401AG1-189 GEN
Solar/Wind Harmer
0.63
963391AG1-188 GEN
Solar/Wind Harmer
1.044
20628028LAKEHURS
Adder
0.496
233939AC1-091 C
Solar/Wind Harmer
0.423
233970AC1-092 C
Solar/Wind Harmer
0.423
971149AH1-027 GEN
Solar/Wind Harmer
1.618
232899W1-062
Adder
4.573
232416X2-083
Adder
0.214
970545AG2-347 GEN
Solar/Wind Harmer
30.603
231940T-011
Adder
0.347
972069AH1-584 GEN
Solar/Wind Harmer
4.165
972071AH1-585 GEN
Solar/Wind Harmer
4.165
971747AH1-380 GEN
Solar/Wind Harmer
1.665
233901CHERRYDALE C
Solar/Wind Harmer
0.523
232408W1-005 C
Solar/Wind Harmer
0.465
232410W1-006 C
Solar/Wind Harmer
0.465
232918OH NUG7
Adder
4.077
232905CHERITON_25
Adder
1.14
232926CRISFLD1
Adder
0.911
233946AB2-136 GEN
Solar/Wind Harmer
1.834
234036AF2-325 C
Solar/Wind Harmer
0.421
234041AC1-190 GEN
Solar/Wind Harmer
4.104
231131BLOOM ENRGY
Adder
1.988
233987AB2-037 GEN
Solar/Wind Harmer
5.183
233984AB2-036 GEN
Solar/Wind Harmer
5.521
232424Y1-079 C
Solar/Wind Harmer
0.249
234014AF1-036_GEN
Solar/Wind Harmer
1.184
233944AB2-135 GEN
Solar/Wind Harmer
2.287
233933AB2-153 GEN
Solar/Wind Harmer
0.486
20720628TIN_W1-124
Solar/Wind Harmer
0.392
20641628MLH_W1-032
Solar/Wind Harmer
0.1
20716928W4-060COL
Solar/Wind Harmer
0.234
219817TRENTONSOL C
Solar/Wind Harmer
0.345
924131AB2-057 GEN
Solar/Wind Harmer
0.31
218440SUMMTASSOC C
Solar/Wind Harmer
0.033
218418LINDEN_G5
Adder
4.093
218419LINDEN_G6
Adder
4.093
972260AH1-715 GEN1
Adder
3.278
213918RICHMD91
50/50
1.234
219230EAGLE PT CT1
50/50
1.468
219235Y2-105
50/50
0.53
219222BRL12CT2
50/50
10.293
219904AC1-010 C
Solar/Wind Harmer
0.575
219258KINSLEYDEP C
Solar/Wind Harmer
0.469
219907AC1-030 C
Solar/Wind Harmer
0.198
219304NAMERICA C
Solar/Wind Harmer
0.338
230434AG1-499 GEN
Solar/Wind Harmer
0.622
228351V2-046C
Solar/Wind Harmer
2.092
218660EHAMPSOLAR C
Solar/Wind Harmer
0.181
219686LUMSOLAR_N C
Solar/Wind Harmer
0.206
219287REEVESEAST C
Solar/Wind Harmer
1.371
970997AG2-616 GEN
Solar/Wind Harmer
9.619
230511AF1-262
Solar/Wind Harmer
0.182
945431AF1-208 GEN
Solar/Wind Harmer
8.422
228728W1-130C
Solar/Wind Harmer
0.635
228206SHRMN CT
Adder
14.479
228732V1-021 C
Adder
0.159
213611FALLS1-3
Adder
2.517
20720728JCB_W1-129
Solar/Wind Harmer
0.2
207522AF2-254 C
Solar/Wind Harmer
0.953
207487AE2-000G4
Solar/Wind Harmer
17.443
207445AB1-138_GEN
Solar/Wind Harmer
0.302
20628028LAKEHURS
Adder
0.98
231917EM10
Adder
1.289
231918WEST 1
Adder
1.725
963711AG1-223 GEN
Solar/Wind Harmer
0.689
20714828MDF_W3-079
Solar/Wind Harmer
0.142
233972AC1-094 C
Solar/Wind Harmer
0.319
232901NORTHST
Adder
3.979
232900DEMECSMY
Adder
4.386
972177AH1-672 GEN
Solar/Wind Harmer
6.299
232434Z2-077 GEN
Solar/Wind Harmer
0.117
233954AC2-188 GEN
Solar/Wind Harmer
0.524
233950AC2-186 GEN
Solar/Wind Harmer
0.262
232404W1-003 C
Solar/Wind Harmer
0.465
232917OH NUG6
Adder
4.086
232915OH NUG4
Adder
4.077
971195AH1-057 GEN
Solar/Wind Harmer
0.508
233998TM1NIN_3.36
Solar/Wind Harmer
0.588
232428Y3-058 C
Solar/Wind Harmer
0.387
232919VN10
Adder
1.294
965821AG1-450 GEN
Solar/Wind Harmer
2.398
232426Y1-080 FULL
Solar/Wind Harmer
0.088
970277AG2-181 GEN
Solar/Wind Harmer
2.308
233964AF2-378 GEN
Solar/Wind Harmer
0.059
232910NRG_G1
Adder
3.954
234012AE2-112_GEN
Solar/Wind Harmer
1.007
232422X3-066 FULL
Solar/Wind Harmer
0.109
233930AB2-032 GEN
Solar/Wind Harmer
0.36
233915AB1-141 GEN
Solar/Wind Harmer
0.428
207454AA2-184 E
Solar/Wind Harmer
0.394
217197RE CRAN C
Solar/Wind Harmer
0.205
20715228NPK_W1-113
Solar/Wind Harmer
0.147
20742028HF_AC1-207
Solar/Wind Harmer
0.264
219680HOPEWELLV C1
Solar/Wind Harmer
0.024
20635828PARLN1&2
Adder
2.217
20635028RRCT1&2
Adder
3.28
20635128RRCT3&4
Adder
3.167
218428ETC SOLAR C
Solar/Wind Harmer
0.009
217213AMBOY SO C
Solar/Wind Harmer
0.032
972275AH1-722 GEN
Adder
7.525
219229EAGLE PT ST
50/50
0.743
219231EAGLE PT CT2
50/50
1.467
230405GT2-CC
50/50
3.263
219224BRL12CT4
50/50
10.293
219914AD2-027 C
Solar/Wind Harmer
0.958
219137THOSOLAR C
Solar/Wind Harmer
1.633
219272CLEANLIGHT C
Solar/Wind Harmer
0.202
219607WPEMNERT C
Solar/Wind Harmer
0.456
971011AG2-627 GEN
Solar/Wind Harmer
8.268
219688LUMSOLAR_S C
Solar/Wind Harmer
0.214
964001AG1-254 GEN
Solar/Wind Harmer
2.11
228309CCLP NUG
Adder
26.788
228309CCLP NUG
Adder
25.481
972141AH1-641 GEN
Solar/Wind Harmer
2.886
971535AH1-265 GEN
Solar/Wind Harmer
4.118
228260V4-054C
Solar/Wind Harmer
0.973
970453AG2-297 GEN
Solar/Wind Harmer
2.32
228754AB1-001 C
Solar/Wind Harmer
0.115
227927V4-067C
Solar/Wind Harmer
0.162
214067T20SOLAR
Solar/Wind Harmer
0.18
213611FALLS1-3
Adder
2.517
213611FALLS1-3
Adder
2.517
20717128DIX_Z2-102
Solar/Wind Harmer
0.866
20715728PEM_W1-119
Solar/Wind Harmer
0.346
20715828PEM_W1-120
Solar/Wind Harmer
0.346
971189AH1-054 GEN
Solar/Wind Harmer
0.673
970025AG2-016 GEN
Solar/Wind Harmer
1.544
207459AE1-142 C O1
Solar/Wind Harmer
0.55
231919CHRIST1
Adder
2.318
231920CHRIST2
Adder
2.266
233973AC2-185 C
Solar/Wind Harmer
1.74
234033AF1-007_GEN
Solar/Wind Harmer
10.936
232904IR4
Adder
37.813
232920IR10
Adder
1.477
232432Z2-076 GEN
Solar/Wind Harmer
0.062
233990AG1-397 GEN
Solar/Wind Harmer
0.026
232912OH NUG1
Adder
4.105
232913OH NUG2
Adder
4.05
233923SMA
Solar/Wind Harmer
2.156
232813VAUGHN
Adder
0.271
233955AB2-172 GEN
Solar/Wind Harmer
2.291
231906DC3 NUG
Adder
6.324
231902DC CT7
Adder
5.056
231907DC10
Adder
1.579
233968AD2-076_GEN
Solar/Wind Harmer
2.901
970597AG2-380 GEN
Solar/Wind Harmer
1.822
232436AB1-176 C
Solar/Wind Harmer
0.1
971983AH1-536 GEN
Solar/Wind Harmer
3.23
20714328BYD_X4-031
Solar/Wind Harmer
0.116
20714428HOW_X1-037
Solar/Wind Harmer
0.489
233935AB2-179 C
Solar/Wind Harmer
0.997
971521AH1-258 GEN
Solar/Wind Harmer
0.989
20720428HOL_W1-112
Solar/Wind Harmer
0.124
219620RIDERU C
Solar/Wind Harmer
0.018
218455CINNBAY_CGEN
Adder
0.548
20635928PARLN3&4
Adder
2.217
218526CNTRALGAS2 C
Solar/Wind Harmer
0.102
218524CNTRALGAS1 C
Solar/Wind Harmer
0.096
213919RICHMD92
50/50
1.234
219124CAMDEN_STG
50/50
1.205
219286CAMD CO RR
50/50
0.415
230406ST-CC
50/50
4.829
230404GT1-CC
50/50
3.247
228304LOGAN
50/50
26.814
219221BRL12CT1
50/50
10.293
219223BRL12CT3
50/50
10.293
219924AG1-130 C
50/50
0.482
219912AD2-042 GEN
Solar/Wind Harmer
1.27
219766PARADISE C
Solar/Wind Harmer
0.479
219623KINSLEYBEA C
Solar/Wind Harmer
0.613
219236SOUTHERNHQ C
Solar/Wind Harmer
0.096
219906AC1-017 C
Solar/Wind Harmer
0.274
219610FLORENCE C
Solar/Wind Harmer
1.505
219348LDSOLAR C
Solar/Wind Harmer
0.651
219291REEVESSOUT C
Solar/Wind Harmer
0.062
230430AE1-229_GEN
Solar/Wind Harmer
8.807
230415AB2-049 C
Solar/Wind Harmer
0.188
971553AH1-274 GEN
Solar/Wind Harmer
2.187
959561AF2-247 GEN
Solar/Wind Harmer
0.431
228711V2-041C
Solar/Wind Harmer
0.519
228202CUMB CT
Adder
14.118
228729W2-030 C
Solar/Wind Harmer
0.478
20716028EGP_W2-019
Solar/Wind Harmer
0.313
20720828JCB_W4-025
Solar/Wind Harmer
0.304
20715028HAN_X4-015
Solar/Wind Harmer
0.2
219727YARDVSOLFA C
Solar/Wind Harmer
0.602
20636028O CRK C1
Adder
3.914
972251AH1-710 GEN
Adder
26.246
219276PARKLANDSO C
Solar/Wind Harmer
0.252
971667AH1-334 GEN
Solar/Wind Harmer
1.456
20714528FRN_Y2-051
Solar/Wind Harmer
0.136
233971AC1-093 C
Solar/Wind Harmer
0.378
970695AG2-447 GEN
Solar/Wind Harmer
1.725
972133AH1-634 GEN
Solar/Wind Harmer
4.637
233952AC2-187 GEN
Solar/Wind Harmer
0.524
972073AH1-586 GEN
Solar/Wind Harmer
4.358
233990AG1-397 GEN
Solar/Wind Harmer
0.533
232406W1-004 FULL
Solar/Wind Harmer
0.465
232914OH NUG3
Adder
4.105
232916OH NUG5
Adder
4.105
232921TASLEY2G
Adder
2.399
234015AF2-250 C
Solar/Wind Harmer
0.056
233900O-025 C
Adder
0.547
233996TM1833_GEN
Solar/Wind Harmer
0.588
233997TMININ_4.2
Solar/Wind Harmer
0.588
233940AF2-379 C
Solar/Wind Harmer
0.087
233994AC2-023 GEN
Solar/Wind Harmer
1.245
232907VN8
Adder
13.852
960671AF2-358 GEN
Solar/Wind Harmer
8.248
232417X3-008 C
Solar/Wind Harmer
0.916
233982AB2-133 GEN
Solar/Wind Harmer
2.103
233918AB1-142 GEN
Solar/Wind Harmer
0.428
219612MATRIX C
Solar/Wind Harmer
0.071
218438BLK ROCK C
Solar/Wind Harmer
0.052
20720528MAN_W1-024
Solar/Wind Harmer
0.087
20716228APLW2-078
Solar/Wind Harmer
0.301
219918AC2-009 C
Solar/Wind Harmer
0.02
20635828PARLN1&2
Adder
1.004
20635928PARLN3&4
Adder
1.004
967451AG2-055 C O1
Solar/Wind Harmer
48.983
20635028RRCT1&2
Adder
3.332
20635128RRCT3&4
Adder
2.762
219908AB1-139 C
Solar/Wind Harmer
0.097
219919AE1-041 FULL
Solar/Wind Harmer
0.01
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.625
G-007ALTFEXP_G-007A->PJM
CMTX
14.489
CBM NorthLTFEXP_CBM-N->PJM
CBM
7.986
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.604
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.879
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
26.441
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.379
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
2.801

Details for RICHMOND35-WANEETA3 230.0 kV Ckt 1 line l/o PECO_P4_CHICH435_SRT-A/* $ DELCO $ PECO_P4_CHICH435 $ STBK


Base Case Flowgate

Area:PECO
Facility Description:
RICHMOND35-WANEETA3 230.0 kV Ckt 1 line
Contingency Name:
PECO_P4_CHICH435_SRT-A/* $ DELCO $ PECO_P4_CHICH435 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:118.18 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1394.5
MW Contribution:8.27
Bus #Bus NameTypeMW Contribution
213918RICHMD91
50/50
1.234
219230EAGLE PT CT1
50/50
1.468
219235Y2-105
50/50
0.53
219222BRL12CT2
50/50
10.293
219904AC1-010 C
Solar/Wind Harmer
0.575
219258KINSLEYDEP C
Solar/Wind Harmer
0.469
219907AC1-030 C
Solar/Wind Harmer
0.198
219304NAMERICA C
Solar/Wind Harmer
0.338
230434AG1-499 GEN
Solar/Wind Harmer
0.622
228351V2-046C
Solar/Wind Harmer
2.092
218660EHAMPSOLAR C
Solar/Wind Harmer
0.181
219686LUMSOLAR_N C
Solar/Wind Harmer
0.206
219287REEVESEAST C
Solar/Wind Harmer
1.371
970997AG2-616 GEN
Solar/Wind Harmer
9.619
230511AF1-262
Solar/Wind Harmer
0.182
945431AF1-208 GEN
Solar/Wind Harmer
8.422
228728W1-130C
Solar/Wind Harmer
0.635
228206SHRMN CT
Adder
14.479
228732V1-021 C
Adder
0.159
213611FALLS1-3
Adder
2.517
20720728JCB_W1-129
Solar/Wind Harmer
0.2
207522AF2-254 C
Solar/Wind Harmer
0.953
207487AE2-000G4
Solar/Wind Harmer
17.443
207445AB1-138_GEN
Solar/Wind Harmer
0.302
20628028LAKEHURS
Adder
0.98
231917EM10
Adder
1.289
231918WEST 1
Adder
1.724
963711AG1-223 GEN
Solar/Wind Harmer
0.689
20714828MDF_W3-079
Solar/Wind Harmer
0.142
233972AC1-094 C
Solar/Wind Harmer
0.319
232901NORTHST
Adder
3.979
232900DEMECSMY
Adder
4.386
972177AH1-672 GEN
Solar/Wind Harmer
6.299
232434Z2-077 GEN
Solar/Wind Harmer
0.117
233954AC2-188 GEN
Solar/Wind Harmer
0.524
233950AC2-186 GEN
Solar/Wind Harmer
0.262
232404W1-003 C
Solar/Wind Harmer
0.465
232917OH NUG6
Adder
4.086
232915OH NUG4
Adder
4.077
971195AH1-057 GEN
Solar/Wind Harmer
0.508
233998TM1NIN_3.36
Solar/Wind Harmer
0.588
232428Y3-058 C
Solar/Wind Harmer
0.387
232919VN10
Adder
1.294
965821AG1-450 GEN
Solar/Wind Harmer
2.397
232426Y1-080 FULL
Solar/Wind Harmer
0.088
970277AG2-181 GEN
Solar/Wind Harmer
2.308
233964AF2-378 GEN
Solar/Wind Harmer
0.059
232910NRG_G1
Adder
3.954
234012AE2-112_GEN
Solar/Wind Harmer
1.007
232422X3-066 FULL
Solar/Wind Harmer
0.109
233930AB2-032 GEN
Solar/Wind Harmer
0.36
233915AB1-141 GEN
Solar/Wind Harmer
0.428
207454AA2-184 E
Solar/Wind Harmer
0.394
217197RE CRAN C
Solar/Wind Harmer
0.205
20715228NPK_W1-113
Solar/Wind Harmer
0.147
20742028HF_AC1-207
Solar/Wind Harmer
0.264
219680HOPEWELLV C1
Solar/Wind Harmer
0.024
20635828PARLN1&2
Adder
2.217
20635028RRCT1&2
Adder
3.281
20635128RRCT3&4
Adder
3.167
218428ETC SOLAR C
Solar/Wind Harmer
0.009
217213AMBOY SO C
Solar/Wind Harmer
0.032
219126CAMDEN_CTG
50/50
1.481
219267WHEELBRDEPTF
50/50
0.208
219240MANTUACREK E
50/50
0.676
219726BAT.STORG E
50/50
0.331
972233AH1-701 GEN
50/50
5.259
228304LOGAN
50/50
29.815
228307PCLP GT
50/50
14.491
213400COVANTA DELA
50/50
1.006
219921AF1-264
Solar/Wind Harmer
0.212
219615MILLCREEK C
Solar/Wind Harmer
0.293
213535CROYDN11
Adder
10.66
230407AD2-065 C
Solar/Wind Harmer
0.129
230433AD2-135 GEN
Solar/Wind Harmer
0.097
228251CARLLS#4
Adder
0.598
230422AE1-104_GEN1
Solar/Wind Harmer
28.185
230425AE1-104_GEN2
Solar/Wind Harmer
28.185
219114HARTZY_C
Solar/Wind Harmer
0.594
20716428NHV_W2-082
Solar/Wind Harmer
1.189
20714928UPF_X1-085
Solar/Wind Harmer
0.23
207500AE2-000G1
Solar/Wind Harmer
17.443
207497AE2-000G2
Solar/Wind Harmer
17.443
207507AE2-000G3
Solar/Wind Harmer
17.443
20636128O CRK C2
Adder
3.569
963401AG1-189 GEN
Solar/Wind Harmer
0.63
963391AG1-188 GEN
Solar/Wind Harmer
1.044
20628028LAKEHURS
Adder
0.496
233939AC1-091 C
Solar/Wind Harmer
0.423
233970AC1-092 C
Solar/Wind Harmer
0.423
971149AH1-027 GEN
Solar/Wind Harmer
1.618
232899W1-062
Adder
4.573
232416X2-083
Adder
0.214
970545AG2-347 GEN
Solar/Wind Harmer
30.601
231940T-011
Adder
0.347
972069AH1-584 GEN
Solar/Wind Harmer
4.164
972071AH1-585 GEN
Solar/Wind Harmer
4.164
971747AH1-380 GEN
Solar/Wind Harmer
1.665
233901CHERRYDALE C
Solar/Wind Harmer
0.523
232408W1-005 C
Solar/Wind Harmer
0.465
232410W1-006 C
Solar/Wind Harmer
0.465
232918OH NUG7
Adder
4.077
232905CHERITON_25
Adder
1.14
232926CRISFLD1
Adder
0.911
233946AB2-136 GEN
Solar/Wind Harmer
1.834
234036AF2-325 C
Solar/Wind Harmer
0.421
234041AC1-190 GEN
Solar/Wind Harmer
4.104
231131BLOOM ENRGY
Adder
1.988
233987AB2-037 GEN
Solar/Wind Harmer
5.182
233984AB2-036 GEN
Solar/Wind Harmer
5.521
232424Y1-079 C
Solar/Wind Harmer
0.249
234014AF1-036_GEN
Solar/Wind Harmer
1.184
233944AB2-135 GEN
Solar/Wind Harmer
2.286
233933AB2-153 GEN
Solar/Wind Harmer
0.485
20720628TIN_W1-124
Solar/Wind Harmer
0.392
20641628MLH_W1-032
Solar/Wind Harmer
0.1
20716928W4-060COL
Solar/Wind Harmer
0.234
219817TRENTONSOL C
Solar/Wind Harmer
0.345
924131AB2-057 GEN
Solar/Wind Harmer
0.31
218440SUMMTASSOC C
Solar/Wind Harmer
0.033
218418LINDEN_G5
Adder
4.093
218419LINDEN_G6
Adder
4.093
972260AH1-715 GEN1
Adder
3.278
219229EAGLE PT ST
50/50
0.743
219231EAGLE PT CT2
50/50
1.467
230405GT2-CC
50/50
3.263
219224BRL12CT4
50/50
10.293
219914AD2-027 C
Solar/Wind Harmer
0.958
219137THOSOLAR C
Solar/Wind Harmer
1.633
219272CLEANLIGHT C
Solar/Wind Harmer
0.202
219607WPEMNERT C
Solar/Wind Harmer
0.456
971011AG2-627 GEN
Solar/Wind Harmer
8.269
219688LUMSOLAR_S C
Solar/Wind Harmer
0.214
964001AG1-254 GEN
Solar/Wind Harmer
2.11
228309CCLP NUG
Adder
26.789
228309CCLP NUG
Adder
25.482
972141AH1-641 GEN
Solar/Wind Harmer
2.886
971535AH1-265 GEN
Solar/Wind Harmer
4.118
228260V4-054C
Solar/Wind Harmer
0.973
970453AG2-297 GEN
Solar/Wind Harmer
2.32
228754AB1-001 C
Solar/Wind Harmer
0.115
227927V4-067C
Solar/Wind Harmer
0.162
214067T20SOLAR
Solar/Wind Harmer
0.18
213611FALLS1-3
Adder
2.517
213611FALLS1-3
Adder
2.517
20717128DIX_Z2-102
Solar/Wind Harmer
0.866
20715728PEM_W1-119
Solar/Wind Harmer
0.346
20715828PEM_W1-120
Solar/Wind Harmer
0.346
971189AH1-054 GEN
Solar/Wind Harmer
0.673
970025AG2-016 GEN
Solar/Wind Harmer
1.544
207459AE1-142 C O1
Solar/Wind Harmer
0.55
231919CHRIST1
Adder
2.318
231920CHRIST2
Adder
2.266
233973AC2-185 C
Solar/Wind Harmer
1.74
234033AF1-007_GEN
Solar/Wind Harmer
10.935
232904IR4
Adder
37.81
232920IR10
Adder
1.477
232432Z2-076 GEN
Solar/Wind Harmer
0.062
233990AG1-397 GEN
Solar/Wind Harmer
0.026
232912OH NUG1
Adder
4.104
232913OH NUG2
Adder
4.049
233923SMA
Solar/Wind Harmer
2.156
232813VAUGHN
Adder
0.271
233955AB2-172 GEN
Solar/Wind Harmer
2.291
231906DC3 NUG
Adder
6.324
231902DC CT7
Adder
5.055
231907DC10
Adder
1.579
233968AD2-076_GEN
Solar/Wind Harmer
2.901
970597AG2-380 GEN
Solar/Wind Harmer
1.822
232436AB1-176 C
Solar/Wind Harmer
0.1
971983AH1-536 GEN
Solar/Wind Harmer
3.23
20714328BYD_X4-031
Solar/Wind Harmer
0.116
20714428HOW_X1-037
Solar/Wind Harmer
0.489
233935AB2-179 C
Solar/Wind Harmer
0.997
971521AH1-258 GEN
Solar/Wind Harmer
0.989
20720428HOL_W1-112
Solar/Wind Harmer
0.124
219620RIDERU C
Solar/Wind Harmer
0.018
218455CINNBAY_CGEN
Adder
0.548
20635928PARLN3&4
Adder
2.217
218526CNTRALGAS2 C
Solar/Wind Harmer
0.102
218524CNTRALGAS1 C
Solar/Wind Harmer
0.096
972275AH1-722 GEN
Adder
7.525
213919RICHMD92
50/50
1.234
219124CAMDEN_STG
50/50
1.205
219286CAMD CO RR
50/50
0.415
230406ST-CC
50/50
4.829
230404GT1-CC
50/50
3.248
228304LOGAN
50/50
26.815
219221BRL12CT1
50/50
10.293
219223BRL12CT3
50/50
10.293
219924AG1-130 C
50/50
0.482
219912AD2-042 GEN
Solar/Wind Harmer
1.27
219766PARADISE C
Solar/Wind Harmer
0.479
219623KINSLEYBEA C
Solar/Wind Harmer
0.613
219236SOUTHERNHQ C
Solar/Wind Harmer
0.096
219906AC1-017 C
Solar/Wind Harmer
0.274
219610FLORENCE C
Solar/Wind Harmer
1.506
219348LDSOLAR C
Solar/Wind Harmer
0.651
219291REEVESSOUT C
Solar/Wind Harmer
0.062
230430AE1-229_GEN
Solar/Wind Harmer
8.808
230415AB2-049 C
Solar/Wind Harmer
0.188
971553AH1-274 GEN
Solar/Wind Harmer
2.187
959561AF2-247 GEN
Solar/Wind Harmer
0.431
228711V2-041C
Solar/Wind Harmer
0.519
228202CUMB CT
Adder
14.118
228729W2-030 C
Solar/Wind Harmer
0.478
20716028EGP_W2-019
Solar/Wind Harmer
0.313
20720828JCB_W4-025
Solar/Wind Harmer
0.304
20715028HAN_X4-015
Solar/Wind Harmer
0.2
219727YARDVSOLFA C
Solar/Wind Harmer
0.602
20636028O CRK C1
Adder
3.914
972251AH1-710 GEN
Adder
26.245
219276PARKLANDSO C
Solar/Wind Harmer
0.252
971667AH1-334 GEN
Solar/Wind Harmer
1.456
20714528FRN_Y2-051
Solar/Wind Harmer
0.136
233971AC1-093 C
Solar/Wind Harmer
0.378
970695AG2-447 GEN
Solar/Wind Harmer
1.725
972133AH1-634 GEN
Solar/Wind Harmer
4.637
233952AC2-187 GEN
Solar/Wind Harmer
0.524
972073AH1-586 GEN
Solar/Wind Harmer
4.358
233990AG1-397 GEN
Solar/Wind Harmer
0.533
232406W1-004 FULL
Solar/Wind Harmer
0.465
232914OH NUG3
Adder
4.104
232916OH NUG5
Adder
4.104
232921TASLEY2G
Adder
2.399
234015AF2-250 C
Solar/Wind Harmer
0.056
233900O-025 C
Adder
0.547
233996TM1833_GEN
Solar/Wind Harmer
0.588
233997TMININ_4.2
Solar/Wind Harmer
0.588
233940AF2-379 C
Solar/Wind Harmer
0.087
233994AC2-023 GEN
Solar/Wind Harmer
1.245
232907VN8
Adder
13.851
960671AF2-358 GEN
Solar/Wind Harmer
8.247
232417X3-008 C
Solar/Wind Harmer
0.916
233982AB2-133 GEN
Solar/Wind Harmer
2.103
233918AB1-142 GEN
Solar/Wind Harmer
0.428
219612MATRIX C
Solar/Wind Harmer
0.071
218438BLK ROCK C
Solar/Wind Harmer
0.052
20720528MAN_W1-024
Solar/Wind Harmer
0.087
20716228APLW2-078
Solar/Wind Harmer
0.301
219918AC2-009 C
Solar/Wind Harmer
0.02
20635828PARLN1&2
Adder
1.004
20635928PARLN3&4
Adder
1.004
967451AG2-055 C O1
Solar/Wind Harmer
48.985
20635028RRCT1&2
Adder
3.332
20635128RRCT3&4
Adder
2.762
219908AB1-139 C
Solar/Wind Harmer
0.097
219919AE1-041 FULL
Solar/Wind Harmer
0.01
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.625
G-007ALTFEXP_G-007A->PJM
CMTX
14.489
CBM NorthLTFEXP_CBM-N->PJM
CBM
7.987
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.604
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.879
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
26.442
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.379
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
2.801

Details for RICHMOND35-WANEETA3 230.0 kV Ckt 1 line l/o PECO_P2-2_CHI230B1_SRT-A/* $ DELCO $ PECO_P2-2_CHI230B1 $ B


Base Case Flowgate

Area:PECO
Facility Description:
RICHMOND35-WANEETA3 230.0 kV Ckt 1 line
Contingency Name:
PECO_P2-2_CHI230B1_SRT-A/* $ DELCO $ PECO_P2-2_CHI230B1 $ B
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:118.17 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1394.44
MW Contribution:8.27
Bus #Bus NameTypeMW Contribution
219126CAMDEN_CTG
50/50
1.481
219267WHEELBRDEPTF
50/50
0.208
219240MANTUACREK E
50/50
0.676
219726BAT.STORG E
50/50
0.331
972233AH1-701 GEN
50/50
5.259
228304LOGAN
50/50
29.813
228307PCLP GT
50/50
14.49
213400COVANTA DELA
50/50
1.006
219921AF1-264
Solar/Wind Harmer
0.212
219615MILLCREEK C
Solar/Wind Harmer
0.293
213535CROYDN11
Adder
10.659
230407AD2-065 C
Solar/Wind Harmer
0.129
230433AD2-135 GEN
Solar/Wind Harmer
0.097
228251CARLLS#4
Adder
0.598
230422AE1-104_GEN1
Solar/Wind Harmer
28.184
230425AE1-104_GEN2
Solar/Wind Harmer
28.184
219114HARTZY_C
Solar/Wind Harmer
0.594
20716428NHV_W2-082
Solar/Wind Harmer
1.189
20714928UPF_X1-085
Solar/Wind Harmer
0.23
207500AE2-000G1
Solar/Wind Harmer
17.443
207497AE2-000G2
Solar/Wind Harmer
17.443
207507AE2-000G3
Solar/Wind Harmer
17.443
20636128O CRK C2
Adder
3.568
963401AG1-189 GEN
Solar/Wind Harmer
0.63
963391AG1-188 GEN
Solar/Wind Harmer
1.044
20628028LAKEHURS
Adder
0.496
233939AC1-091 C
Solar/Wind Harmer
0.423
233970AC1-092 C
Solar/Wind Harmer
0.423
971149AH1-027 GEN
Solar/Wind Harmer
1.618
232899W1-062
Adder
4.573
232416X2-083
Adder
0.214
970545AG2-347 GEN
Solar/Wind Harmer
30.603
231940T-011
Adder
0.347
972069AH1-584 GEN
Solar/Wind Harmer
4.165
972071AH1-585 GEN
Solar/Wind Harmer
4.165
971747AH1-380 GEN
Solar/Wind Harmer
1.665
233901CHERRYDALE C
Solar/Wind Harmer
0.523
232408W1-005 C
Solar/Wind Harmer
0.465
232410W1-006 C
Solar/Wind Harmer
0.465
232918OH NUG7
Adder
4.077
232905CHERITON_25
Adder
1.14
232926CRISFLD1
Adder
0.911
233946AB2-136 GEN
Solar/Wind Harmer
1.834
234036AF2-325 C
Solar/Wind Harmer
0.421
234041AC1-190 GEN
Solar/Wind Harmer
4.104
231131BLOOM ENRGY
Adder
1.988
233987AB2-037 GEN
Solar/Wind Harmer
5.183
233984AB2-036 GEN
Solar/Wind Harmer
5.521
232424Y1-079 C
Solar/Wind Harmer
0.249
234014AF1-036_GEN
Solar/Wind Harmer
1.184
233944AB2-135 GEN
Solar/Wind Harmer
2.287
233933AB2-153 GEN
Solar/Wind Harmer
0.486
20720628TIN_W1-124
Solar/Wind Harmer
0.392
20641628MLH_W1-032
Solar/Wind Harmer
0.1
20716928W4-060COL
Solar/Wind Harmer
0.234
219817TRENTONSOL C
Solar/Wind Harmer
0.345
924131AB2-057 GEN
Solar/Wind Harmer
0.31
218440SUMMTASSOC C
Solar/Wind Harmer
0.033
218418LINDEN_G5
Adder
4.093
218419LINDEN_G6
Adder
4.093
972260AH1-715 GEN1
Adder
3.278
213919RICHMD92
50/50
1.234
219124CAMDEN_STG
50/50
1.205
219286CAMD CO RR
50/50
0.415
230406ST-CC
50/50
4.829
230404GT1-CC
50/50
3.247
228304LOGAN
50/50
26.814
219221BRL12CT1
50/50
10.293
219223BRL12CT3
50/50
10.293
219924AG1-130 C
50/50
0.482
219912AD2-042 GEN
Solar/Wind Harmer
1.27
219766PARADISE C
Solar/Wind Harmer
0.479
219623KINSLEYBEA C
Solar/Wind Harmer
0.613
219236SOUTHERNHQ C
Solar/Wind Harmer
0.096
219906AC1-017 C
Solar/Wind Harmer
0.274
219610FLORENCE C
Solar/Wind Harmer
1.505
219348LDSOLAR C
Solar/Wind Harmer
0.651
219291REEVESSOUT C
Solar/Wind Harmer
0.062
230430AE1-229_GEN
Solar/Wind Harmer
8.807
230415AB2-049 C
Solar/Wind Harmer
0.188
971553AH1-274 GEN
Solar/Wind Harmer
2.187
959561AF2-247 GEN
Solar/Wind Harmer
0.431
228711V2-041C
Solar/Wind Harmer
0.519
228202CUMB CT
Adder
14.118
228729W2-030 C
Solar/Wind Harmer
0.478
20716028EGP_W2-019
Solar/Wind Harmer
0.313
20720828JCB_W4-025
Solar/Wind Harmer
0.304
20715028HAN_X4-015
Solar/Wind Harmer
0.2
219727YARDVSOLFA C
Solar/Wind Harmer
0.602
20636028O CRK C1
Adder
3.914
972251AH1-710 GEN
Adder
26.246
219276PARKLANDSO C
Solar/Wind Harmer
0.252
971667AH1-334 GEN
Solar/Wind Harmer
1.456
20714528FRN_Y2-051
Solar/Wind Harmer
0.136
233971AC1-093 C
Solar/Wind Harmer
0.378
970695AG2-447 GEN
Solar/Wind Harmer
1.725
972133AH1-634 GEN
Solar/Wind Harmer
4.637
233952AC2-187 GEN
Solar/Wind Harmer
0.524
972073AH1-586 GEN
Solar/Wind Harmer
4.358
233990AG1-397 GEN
Solar/Wind Harmer
0.533
232406W1-004 FULL
Solar/Wind Harmer
0.465
232914OH NUG3
Adder
4.105
232916OH NUG5
Adder
4.105
232921TASLEY2G
Adder
2.399
234015AF2-250 C
Solar/Wind Harmer
0.056
233900O-025 C
Adder
0.547
233996TM1833_GEN
Solar/Wind Harmer
0.588
233997TMININ_4.2
Solar/Wind Harmer
0.588
233940AF2-379 C
Solar/Wind Harmer
0.087
233994AC2-023 GEN
Solar/Wind Harmer
1.245
232907VN8
Adder
13.852
960671AF2-358 GEN
Solar/Wind Harmer
8.248
232417X3-008 C
Solar/Wind Harmer
0.916
233982AB2-133 GEN
Solar/Wind Harmer
2.103
233918AB1-142 GEN
Solar/Wind Harmer
0.428
219612MATRIX C
Solar/Wind Harmer
0.071
218438BLK ROCK C
Solar/Wind Harmer
0.052
20720528MAN_W1-024
Solar/Wind Harmer
0.087
20716228APLW2-078
Solar/Wind Harmer
0.301
219918AC2-009 C
Solar/Wind Harmer
0.02
20635828PARLN1&2
Adder
1.004
20635928PARLN3&4
Adder
1.004
967451AG2-055 C O1
Solar/Wind Harmer
48.983
20635028RRCT1&2
Adder
3.332
20635128RRCT3&4
Adder
2.762
219908AB1-139 C
Solar/Wind Harmer
0.097
219919AE1-041 FULL
Solar/Wind Harmer
0.01
219229EAGLE PT ST
50/50
0.743
219231EAGLE PT CT2
50/50
1.467
230405GT2-CC
50/50
3.263
219224BRL12CT4
50/50
10.293
219914AD2-027 C
Solar/Wind Harmer
0.958
219137THOSOLAR C
Solar/Wind Harmer
1.633
219272CLEANLIGHT C
Solar/Wind Harmer
0.202
219607WPEMNERT C
Solar/Wind Harmer
0.456
971011AG2-627 GEN
Solar/Wind Harmer
8.268
219688LUMSOLAR_S C
Solar/Wind Harmer
0.214
964001AG1-254 GEN
Solar/Wind Harmer
2.11
228309CCLP NUG
Adder
26.788
228309CCLP NUG
Adder
25.481
972141AH1-641 GEN
Solar/Wind Harmer
2.886
971535AH1-265 GEN
Solar/Wind Harmer
4.118
228260V4-054C
Solar/Wind Harmer
0.973
970453AG2-297 GEN
Solar/Wind Harmer
2.32
228754AB1-001 C
Solar/Wind Harmer
0.115
227927V4-067C
Solar/Wind Harmer
0.162
214067T20SOLAR
Solar/Wind Harmer
0.18
213611FALLS1-3
Adder
2.517
213611FALLS1-3
Adder
2.517
20717128DIX_Z2-102
Solar/Wind Harmer
0.866
20715728PEM_W1-119
Solar/Wind Harmer
0.346
20715828PEM_W1-120
Solar/Wind Harmer
0.346
971189AH1-054 GEN
Solar/Wind Harmer
0.673
970025AG2-016 GEN
Solar/Wind Harmer
1.544
207459AE1-142 C O1
Solar/Wind Harmer
0.55
231919CHRIST1
Adder
2.318
231920CHRIST2
Adder
2.266
233973AC2-185 C
Solar/Wind Harmer
1.74
234033AF1-007_GEN
Solar/Wind Harmer
10.936
232904IR4
Adder
37.813
232920IR10
Adder
1.477
232432Z2-076 GEN
Solar/Wind Harmer
0.062
233990AG1-397 GEN
Solar/Wind Harmer
0.026
232912OH NUG1
Adder
4.105
232913OH NUG2
Adder
4.05
233923SMA
Solar/Wind Harmer
2.156
232813VAUGHN
Adder
0.271
233955AB2-172 GEN
Solar/Wind Harmer
2.291
231906DC3 NUG
Adder
6.324
231902DC CT7
Adder
5.056
231907DC10
Adder
1.579
233968AD2-076_GEN
Solar/Wind Harmer
2.901
970597AG2-380 GEN
Solar/Wind Harmer
1.822
232436AB1-176 C
Solar/Wind Harmer
0.1
971983AH1-536 GEN
Solar/Wind Harmer
3.23
20714328BYD_X4-031
Solar/Wind Harmer
0.116
20714428HOW_X1-037
Solar/Wind Harmer
0.489
213918RICHMD91
50/50
1.234
219230EAGLE PT CT1
50/50
1.468
219235Y2-105
50/50
0.53
219222BRL12CT2
50/50
10.293
219904AC1-010 C
Solar/Wind Harmer
0.575
219258KINSLEYDEP C
Solar/Wind Harmer
0.469
219907AC1-030 C
Solar/Wind Harmer
0.198
219304NAMERICA C
Solar/Wind Harmer
0.338
230434AG1-499 GEN
Solar/Wind Harmer
0.622
228351V2-046C
Solar/Wind Harmer
2.092
218660EHAMPSOLAR C
Solar/Wind Harmer
0.181
219686LUMSOLAR_N C
Solar/Wind Harmer
0.206
219287REEVESEAST C
Solar/Wind Harmer
1.371
970997AG2-616 GEN
Solar/Wind Harmer
9.619
230511AF1-262
Solar/Wind Harmer
0.182
945431AF1-208 GEN
Solar/Wind Harmer
8.422
228728W1-130C
Solar/Wind Harmer
0.635
228206SHRMN CT
Adder
14.479
228732V1-021 C
Adder
0.159
213611FALLS1-3
Adder
2.517
20720728JCB_W1-129
Solar/Wind Harmer
0.2
207522AF2-254 C
Solar/Wind Harmer
0.953
207487AE2-000G4
Solar/Wind Harmer
17.443
207445AB1-138_GEN
Solar/Wind Harmer
0.302
20628028LAKEHURS
Adder
0.98
231917EM10
Adder
1.289
231918WEST 1
Adder
1.725
963711AG1-223 GEN
Solar/Wind Harmer
0.689
20714828MDF_W3-079
Solar/Wind Harmer
0.142
233972AC1-094 C
Solar/Wind Harmer
0.319
232901NORTHST
Adder
3.979
232900DEMECSMY
Adder
4.386
972177AH1-672 GEN
Solar/Wind Harmer
6.299
232434Z2-077 GEN
Solar/Wind Harmer
0.117
233954AC2-188 GEN
Solar/Wind Harmer
0.524
233950AC2-186 GEN
Solar/Wind Harmer
0.262
232404W1-003 C
Solar/Wind Harmer
0.465
232917OH NUG6
Adder
4.086
232915OH NUG4
Adder
4.077
971195AH1-057 GEN
Solar/Wind Harmer
0.508
233998TM1NIN_3.36
Solar/Wind Harmer
0.588
232428Y3-058 C
Solar/Wind Harmer
0.387
232919VN10
Adder
1.294
965821AG1-450 GEN
Solar/Wind Harmer
2.398
232426Y1-080 FULL
Solar/Wind Harmer
0.088
970277AG2-181 GEN
Solar/Wind Harmer
2.308
233964AF2-378 GEN
Solar/Wind Harmer
0.059
232910NRG_G1
Adder
3.954
234012AE2-112_GEN
Solar/Wind Harmer
1.007
232422X3-066 FULL
Solar/Wind Harmer
0.109
233930AB2-032 GEN
Solar/Wind Harmer
0.36
233915AB1-141 GEN
Solar/Wind Harmer
0.428
207454AA2-184 E
Solar/Wind Harmer
0.394
217197RE CRAN C
Solar/Wind Harmer
0.205
20715228NPK_W1-113
Solar/Wind Harmer
0.147
20742028HF_AC1-207
Solar/Wind Harmer
0.264
219680HOPEWELLV C1
Solar/Wind Harmer
0.024
20635828PARLN1&2
Adder
2.217
20635028RRCT1&2
Adder
3.28
20635128RRCT3&4
Adder
3.167
218428ETC SOLAR C
Solar/Wind Harmer
0.009
217213AMBOY SO C
Solar/Wind Harmer
0.032
972275AH1-722 GEN
Adder
7.525
233935AB2-179 C
Solar/Wind Harmer
0.997
971521AH1-258 GEN
Solar/Wind Harmer
0.989
20720428HOL_W1-112
Solar/Wind Harmer
0.124
219620RIDERU C
Solar/Wind Harmer
0.018
218455CINNBAY_CGEN
Adder
0.548
20635928PARLN3&4
Adder
2.217
218526CNTRALGAS2 C
Solar/Wind Harmer
0.102
218524CNTRALGAS1 C
Solar/Wind Harmer
0.096
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.625
G-007ALTFEXP_G-007A->PJM
CMTX
14.489
CBM NorthLTFEXP_CBM-N->PJM
CBM
7.986
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.604
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.879
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
26.441
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.379
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
2.801

Details for RICHMOND35-WANEETA3 230.0 kV Ckt 1 line l/o PECO_P4_PEACH215_SRT-A/* $ CHESCO $ PECO_P4_PEACH215 $ STBK


Base Case Flowgate

Area:PECO
Facility Description:
RICHMOND35-WANEETA3 230.0 kV Ckt 1 line
Contingency Name:
PECO_P4_PEACH215_SRT-A/* $ CHESCO $ PECO_P4_PEACH215 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.9 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1237.87
MW Contribution:8.9
Bus #Bus NameTypeMW Contribution
213919RICHMD92
50/50
1.356
219124CAMDEN_STG
50/50
1.315
219286CAMD CO RR
50/50
0.453
230406ST-CC
50/50
4.982
230404GT1-CC
50/50
3.351
219221BRL12CT1
50/50
11.818
219223BRL12CT3
50/50
11.818
219924AG1-130 C
50/50
0.553
228304LOGAN
50/50
28.25
213542CROYDN42
50/50
0.718
219912AD2-042 GEN
Solar/Wind Harmer
1.393
219766PARADISE C
Solar/Wind Harmer
0.522
219623KINSLEYBEA C
Solar/Wind Harmer
0.672
219236SOUTHERNHQ C
Solar/Wind Harmer
0.106
219906AC1-017 C
Solar/Wind Harmer
0.309
219610FLORENCE C
Solar/Wind Harmer
1.729
219126CAMDEN_CTG
50/50
1.615
219267WHEELBRDEPTF
50/50
0.227
219240MANTUACREK E
50/50
0.737
219726BAT.STORG E
50/50
0.363
972233AH1-701 GEN
50/50
5.528
228304LOGAN
50/50
31.41
213535CROYDN11
50/50
13.132
228307PCLP GT
50/50
15.37
219921AF1-264
Solar/Wind Harmer
0.233
219615MILLCREEK C
Solar/Wind Harmer
0.331
230407AD2-065 C
Solar/Wind Harmer
0.146
230433AD2-135 GEN
Solar/Wind Harmer
0.11
228251CARLLS#4
Adder
0.666
230422AE1-104_GEN1
Solar/Wind Harmer
32.433
230425AE1-104_GEN2
Solar/Wind Harmer
32.433
219114HARTZY_C
Solar/Wind Harmer
0.721
20716428NHV_W2-082
Solar/Wind Harmer
1.436
20714928UPF_X1-085
Solar/Wind Harmer
0.287
207500AE2-000G1
Solar/Wind Harmer
21.662
207497AE2-000G2
Solar/Wind Harmer
21.662
207507AE2-000G3
Solar/Wind Harmer
21.662
20636128O CRK C2
Adder
4.432
963401AG1-189 GEN
Solar/Wind Harmer
0.785
963391AG1-188 GEN
Solar/Wind Harmer
1.303
20628028LAKEHURS
Adder
0.625
233939AC1-091 C
Solar/Wind Harmer
0.544
233970AC1-092 C
Solar/Wind Harmer
0.544
971149AH1-027 GEN
Solar/Wind Harmer
2.06
232899W1-062
Adder
5.814
970545AG2-347 GEN
Solar/Wind Harmer
38.019
231940T-011
Adder
0.43
972069AH1-584 GEN
Solar/Wind Harmer
5.14
972071AH1-585 GEN
Solar/Wind Harmer
5.14
971747AH1-380 GEN
Solar/Wind Harmer
2.054
233901CHERRYDALE C
Solar/Wind Harmer
0.645
232918OH NUG7
Adder
5.027
232905CHERITON_25
Adder
1.406
232408W1-005 C
Solar/Wind Harmer
0.574
232410W1-006 C
Solar/Wind Harmer
0.574
232926CRISFLD1
Adder
1.122
233946AB2-136 GEN
Solar/Wind Harmer
2.238
234036AF2-325 C
Solar/Wind Harmer
0.513
234041AC1-190 GEN
Solar/Wind Harmer
4.997
20720628TIN_W1-124
Solar/Wind Harmer
0.526
233987AB2-037 GEN
Solar/Wind Harmer
6.195
233984AB2-036 GEN
Solar/Wind Harmer
6.57
232424Y1-079 C
Solar/Wind Harmer
0.297
233944AB2-135 GEN
Solar/Wind Harmer
2.727
234014AF1-036_GEN
Solar/Wind Harmer
1.403
233933AB2-153 GEN
Solar/Wind Harmer
0.572
20641628MLH_W1-032
Solar/Wind Harmer
0.14
231131BLOOM ENRGY
Adder
2.168
219817TRENTONSOL C
Solar/Wind Harmer
0.507
20716928W4-060COL
Solar/Wind Harmer
0.328
924131AB2-057 GEN
Solar/Wind Harmer
0.449
218440SUMMTASSOC C
Solar/Wind Harmer
0.05
232416X2-083
Adder
0.177
219348LDSOLAR C
Solar/Wind Harmer
0.747
219291REEVESSOUT C
Solar/Wind Harmer
0.071
230415AB2-049 C
Solar/Wind Harmer
0.211
230430AE1-229_GEN
Solar/Wind Harmer
9.675
959561AF2-247 GEN
Solar/Wind Harmer
0.507
971553AH1-274 GEN
Solar/Wind Harmer
2.471
228711V2-041C
Solar/Wind Harmer
0.593
228202CUMB CT
Adder
16.163
228729W2-030 C
Solar/Wind Harmer
0.551
20716028EGP_W2-019
Solar/Wind Harmer
0.378
20720828JCB_W4-025
Solar/Wind Harmer
0.368
20715028HAN_X4-015
Solar/Wind Harmer
0.242
219727YARDVSOLFA C
Solar/Wind Harmer
0.739
972251AH1-710 GEN
Adder
35.081
20636028O CRK C1
Adder
4.861
219276PARKLANDSO C
Solar/Wind Harmer
0.32
971667AH1-334 GEN
Solar/Wind Harmer
1.829
20714528FRN_Y2-051
Solar/Wind Harmer
0.176
233971AC1-093 C
Solar/Wind Harmer
0.486
970695AG2-447 GEN
Solar/Wind Harmer
2.217
972133AH1-634 GEN
Solar/Wind Harmer
5.761
233952AC2-187 GEN
Solar/Wind Harmer
0.652
233990AG1-397 GEN
Solar/Wind Harmer
0.658
972073AH1-586 GEN
Solar/Wind Harmer
5.379
232914OH NUG3
Adder
5.061
232916OH NUG5
Adder
5.061
232921TASLEY2G
Adder
2.958
232406W1-004 FULL
Solar/Wind Harmer
0.574
234015AF2-250 C
Solar/Wind Harmer
0.069
233900O-025 C
Adder
0.674
233996TM1833_GEN
Solar/Wind Harmer
0.724
233997TMININ_4.2
Solar/Wind Harmer
0.724
233940AF2-379 C
Solar/Wind Harmer
0.107
233994AC2-023 GEN
Solar/Wind Harmer
1.531
232907VN8
Adder
16.924
960671AF2-358 GEN
Solar/Wind Harmer
10.08
232417X3-008 C
Solar/Wind Harmer
1.115
219612MATRIX C
Solar/Wind Harmer
0.096
218438BLK ROCK C
Solar/Wind Harmer
0.071
233982AB2-133 GEN
Solar/Wind Harmer
2.486
233918AB1-142 GEN
Solar/Wind Harmer
0.504
20720528MAN_W1-024
Solar/Wind Harmer
0.122
20716228APLW2-078
Solar/Wind Harmer
0.422
219918AC2-009 C
Solar/Wind Harmer
0.029
20635828PARLN1&2
Adder
1.445
20635928PARLN3&4
Adder
1.445
967451AG2-055 C O1
Solar/Wind Harmer
72.184
20635028RRCT1&2
Adder
4.874
20635128RRCT3&4
Adder
4.041
219908AB1-139 C
Solar/Wind Harmer
0.147
219919AE1-041 FULL
Solar/Wind Harmer
0.016
219249CENTRALDIV C
Solar/Wind Harmer
0.013
217211CAMDEN ST C
Solar/Wind Harmer
0.008
217186ESSEX_G9
Adder
4.952
217169METRODIV C
Solar/Wind Harmer
0.012
217194REDH C
Solar/Wind Harmer
0.152
20673728F2S_V4-070
Solar/Wind Harmer
0.047
20676728BRNX1-095
Solar/Wind Harmer
0.046
219229EAGLE PT ST
50/50
0.8
219231EAGLE PT CT2
50/50
1.58
230405GT2-CC
50/50
3.367
219224BRL12CT4
50/50
11.818
213537CROYDN21
50/50
0.718
213538CROYDN22
50/50
0.718
213539CROYDN31
50/50
0.718
213540CROYDN32
50/50
0.703
228309CCLP NUG
50/50
30.82
219914AD2-027 C
Solar/Wind Harmer
1.051
219137THOSOLAR C
Solar/Wind Harmer
1.72
219272CLEANLIGHT C
Solar/Wind Harmer
0.23
219607WPEMNERT C
Solar/Wind Harmer
0.523
219688LUMSOLAR_S C
Solar/Wind Harmer
0.244
971011AG2-627 GEN
Solar/Wind Harmer
8.896
964001AG1-254 GEN
Solar/Wind Harmer
2.293
228309CCLP NUG
Adder
27.628
972141AH1-641 GEN
Solar/Wind Harmer
3.165
218418LINDEN_G5
Adder
6.323
218419LINDEN_G6
Adder
6.323
972260AH1-715 GEN1
Adder
5.063
219036LINDEN_G7
Adder
5.812
219035LINDEN_G8
Adder
5.729
972261AH1-715 GEN2
Adder
5.563
217081WEATEXAS C
Solar/Wind Harmer
0.029
217202FBANKSOLAR C
Solar/Wind Harmer
0.024
217201HACKENSOLA C
Solar/Wind Harmer
0.023
972237AH1-703 GEN
Adder
3.142
217206BARNGR HS C
Solar/Wind Harmer
0.01
217086KRNY_131
Adder
2.881
217083KRNY_132
Adder
2.857
217204WCALDSOLAR C
Solar/Wind Harmer
0.022
207442AE1-156 GEN
Solar/Wind Harmer
0.195
20676128MHD_W3-029
Solar/Wind Harmer
0.125
20673828FLE_V3-070
Solar/Wind Harmer
0.118
20671828STAW2-080
Solar/Wind Harmer
0.026
213918RICHMD91
50/50
1.356
219230EAGLE PT CT1
50/50
1.581
219235Y2-105
50/50
0.571
219222BRL12CT2
50/50
11.818
213536CROYDN12
50/50
6.049
213541CROYDN41
50/50
0.718
219904AC1-010 C
Solar/Wind Harmer
0.628
219907AC1-030 C
Solar/Wind Harmer
0.22
219258KINSLEYDEP C
Solar/Wind Harmer
0.504
219304NAMERICA C
Solar/Wind Harmer
0.388
218660EHAMPSOLAR C
Solar/Wind Harmer
0.206
230434AG1-499 GEN
Solar/Wind Harmer
0.677
219686LUMSOLAR_N C
Solar/Wind Harmer
0.236
219287REEVESEAST C
Solar/Wind Harmer
1.568
228351V2-046C
Solar/Wind Harmer
2.274
970997AG2-616 GEN
Solar/Wind Harmer
10.551
230511AF1-262
Solar/Wind Harmer
0.201
945431AF1-208 GEN
Solar/Wind Harmer
9.302
971535AH1-265 GEN
Solar/Wind Harmer
4.602
228260V4-054C
Solar/Wind Harmer
1.084
970453AG2-297 GEN
Solar/Wind Harmer
2.667
228754AB1-001 C
Solar/Wind Harmer
0.133
227927V4-067C
Solar/Wind Harmer
0.188
214067T20SOLAR
Solar/Wind Harmer
0.223
213611FALLS1-3
Adder
3.121
213611FALLS1-3
Adder
3.121
20717128DIX_Z2-102
Solar/Wind Harmer
1.05
20715728PEM_W1-119
Solar/Wind Harmer
0.42
20715828PEM_W1-120
Solar/Wind Harmer
0.42
971189AH1-054 GEN
Solar/Wind Harmer
0.834
970025AG2-016 GEN
Solar/Wind Harmer
1.926
207459AE1-142 C O1
Solar/Wind Harmer
0.693
233973AC2-185 C
Solar/Wind Harmer
2.236
234033AF1-007_GEN
Solar/Wind Harmer
13.586
232904IR4
Adder
46.977
232920IR10
Adder
1.833
232432Z2-076 GEN
Solar/Wind Harmer
0.076
233990AG1-397 GEN
Solar/Wind Harmer
0.032
232912OH NUG1
Adder
5.061
232913OH NUG2
Adder
4.993
233923SMA
Solar/Wind Harmer
2.655
232813VAUGHN
Adder
0.336
20714328BYD_X4-031
Solar/Wind Harmer
0.154
233955AB2-172 GEN
Solar/Wind Harmer
2.788
20714428HOW_X1-037
Solar/Wind Harmer
0.656
233968AD2-076_GEN
Solar/Wind Harmer
3.437
970597AG2-380 GEN
Solar/Wind Harmer
2.158
971521AH1-258 GEN
Solar/Wind Harmer
1.35
232436AB1-176 C
Solar/Wind Harmer
0.119
20720428HOL_W1-112
Solar/Wind Harmer
0.17
971983AH1-536 GEN
Solar/Wind Harmer
3.805
231906DC3 NUG
Adder
7.024
231902DC CT7
Adder
5.615
231907DC10
Adder
1.754
219620RIDERU C
Solar/Wind Harmer
0.026
233935AB2-179 C
Solar/Wind Harmer
1.128
218455CINNBAY_CGEN
Adder
0.793
20635928PARLN3&4
Adder
3.19
218526CNTRALGAS2 C
Solar/Wind Harmer
0.151
218524CNTRALGAS1 C
Solar/Wind Harmer
0.144
218404KENILWRTH C
Adder
0.416
231919CHRIST1
Adder
1.411
231920CHRIST2
Adder
1.38
217167KRNY_14
Adder
2.875
217086KRNY_131
Adder
2.851
217147KRNY_1212
Adder
2.735
217147KRNY_1212
Adder
2.686
217146KRNY_1234
Adder
2.68
217146KRNY_1234
Adder
2.662
20675528CPH_W2-050
Solar/Wind Harmer
0.119
228728W1-130C
Solar/Wind Harmer
0.708
228206SHRMN CT
Adder
16.487
228732V1-021 C
Adder
0.183
213611FALLS1-3
Adder
3.121
20720728JCB_W1-129
Solar/Wind Harmer
0.242
207522AF2-254 C
Solar/Wind Harmer
1.153
207487AE2-000G4
Solar/Wind Harmer
21.662
207445AB1-138_GEN
Solar/Wind Harmer
0.381
20628028LAKEHURS
Adder
1.236
963711AG1-223 GEN
Solar/Wind Harmer
0.889
20714828MDF_W3-079
Solar/Wind Harmer
0.184
233972AC1-094 C
Solar/Wind Harmer
0.411
232901NORTHST
Adder
5.065
232900DEMECSMY
Adder
5.576
972177AH1-672 GEN
Solar/Wind Harmer
7.862
233954AC2-188 GEN
Solar/Wind Harmer
0.652
233950AC2-186 GEN
Solar/Wind Harmer
0.326
232434Z2-077 GEN
Solar/Wind Harmer
0.145
232917OH NUG6
Adder
5.038
232915OH NUG4
Adder
5.027
232404W1-003 C
Solar/Wind Harmer
0.574
971195AH1-057 GEN
Solar/Wind Harmer
0.626
233998TM1NIN_3.36
Solar/Wind Harmer
0.724
232428Y3-058 C
Solar/Wind Harmer
0.476
232910NRG_G1
Adder
4.884
232919VN10
Adder
1.584
965821AG1-450 GEN
Solar/Wind Harmer
2.93
232426Y1-080 FULL
Solar/Wind Harmer
0.107
970277AG2-181 GEN
Solar/Wind Harmer
2.819
233964AF2-378 GEN
Solar/Wind Harmer
0.072
207454AA2-184 E
Solar/Wind Harmer
0.528
217197RE CRAN C
Solar/Wind Harmer
0.28
234012AE2-112_GEN
Solar/Wind Harmer
1.192
232422X3-066 FULL
Solar/Wind Harmer
0.13
233930AB2-032 GEN
Solar/Wind Harmer
0.424
233915AB1-141 GEN
Solar/Wind Harmer
0.504
20715228NPK_W1-113
Solar/Wind Harmer
0.205
20742028HF_AC1-207
Solar/Wind Harmer
0.371
219680HOPEWELLV C1
Solar/Wind Harmer
0.035
20635828PARLN1&2
Adder
3.19
20635028RRCT1&2
Adder
4.799
20635128RRCT3&4
Adder
4.633
218428ETC SOLAR C
Solar/Wind Harmer
0.014
217213AMBOY SO C
Solar/Wind Harmer
0.048
972275AH1-722 GEN
Adder
11.623
218449LINSOLAR C
Solar/Wind Harmer
0.35
217209CENTRL HS C
Solar/Wind Harmer
0.014
231918WEST 1
Adder
1.09
217121ECCF
Adder
0.135
217083KRNY_132
Adder
2.875
217208PARK ELE C
Solar/Wind Harmer
0.008
231917EM10
Adder
0.663
207528AF2-192 GEN
Solar/Wind Harmer
0.145
20673628F1S_V4-069
Solar/Wind Harmer
0.047
20675428EAM_W2-061
Solar/Wind Harmer
0.05
20676428JCR_X2-075
Solar/Wind Harmer
0.089
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.015
G-007ALTFEXP_G-007A->PJM
CMTX
21.198
CBM NorthLTFEXP_CBM-N->PJM
CBM
16.653
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.93
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.896
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
43.544
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.61
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.334

Details for RICHMOND35-WANEETA3 230.0 kV Ckt 1 line l/o PECO_P4_PEACH205_SRT-A/* $ CHESCO $ PECO_P4_PEACH205 $ STBK


Base Case Flowgate

Area:PECO
Facility Description:
RICHMOND35-WANEETA3 230.0 kV Ckt 1 line
Contingency Name:
PECO_P4_PEACH205_SRT-A/* $ CHESCO $ PECO_P4_PEACH205 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.28 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1206.94
MW Contribution:8.9
Bus #Bus NameTypeMW Contribution
219126CAMDEN_CTG
50/50
1.615
219267WHEELBRDEPTF
50/50
0.227
219240MANTUACREK E
50/50
0.737
219726BAT.STORG E
50/50
0.363
972233AH1-701 GEN
50/50
5.528
228304LOGAN
50/50
31.41
213535CROYDN11
50/50
13.132
228307PCLP GT
50/50
15.37
219921AF1-264
Solar/Wind Harmer
0.233
219615MILLCREEK C
Solar/Wind Harmer
0.331
230407AD2-065 C
Solar/Wind Harmer
0.146
230433AD2-135 GEN
Solar/Wind Harmer
0.11
228251CARLLS#4
Adder
0.666
230422AE1-104_GEN1
Solar/Wind Harmer
32.433
230425AE1-104_GEN2
Solar/Wind Harmer
32.433
219114HARTZY_C
Solar/Wind Harmer
0.721
20716428NHV_W2-082
Solar/Wind Harmer
1.436
20714928UPF_X1-085
Solar/Wind Harmer
0.287
207500AE2-000G1
Solar/Wind Harmer
21.662
207497AE2-000G2
Solar/Wind Harmer
21.662
207507AE2-000G3
Solar/Wind Harmer
21.662
20636128O CRK C2
Adder
4.432
963401AG1-189 GEN
Solar/Wind Harmer
0.785
963391AG1-188 GEN
Solar/Wind Harmer
1.303
20628028LAKEHURS
Adder
0.625
233939AC1-091 C
Solar/Wind Harmer
0.544
233970AC1-092 C
Solar/Wind Harmer
0.544
971149AH1-027 GEN
Solar/Wind Harmer
2.06
232899W1-062
Adder
5.814
970545AG2-347 GEN
Solar/Wind Harmer
38.019
231940T-011
Adder
0.43
972069AH1-584 GEN
Solar/Wind Harmer
5.14
972071AH1-585 GEN
Solar/Wind Harmer
5.14
971747AH1-380 GEN
Solar/Wind Harmer
2.054
233901CHERRYDALE C
Solar/Wind Harmer
0.645
232918OH NUG7
Adder
5.027
232905CHERITON_25
Adder
1.406
232408W1-005 C
Solar/Wind Harmer
0.574
232410W1-006 C
Solar/Wind Harmer
0.574
232926CRISFLD1
Adder
1.122
233946AB2-136 GEN
Solar/Wind Harmer
2.238
234036AF2-325 C
Solar/Wind Harmer
0.513
234041AC1-190 GEN
Solar/Wind Harmer
4.997
20720628TIN_W1-124
Solar/Wind Harmer
0.526
233987AB2-037 GEN
Solar/Wind Harmer
6.195
233984AB2-036 GEN
Solar/Wind Harmer
6.57
232424Y1-079 C
Solar/Wind Harmer
0.297
233944AB2-135 GEN
Solar/Wind Harmer
2.727
234014AF1-036_GEN
Solar/Wind Harmer
1.403
233933AB2-153 GEN
Solar/Wind Harmer
0.572
20641628MLH_W1-032
Solar/Wind Harmer
0.14
231131BLOOM ENRGY
Adder
2.168
219817TRENTONSOL C
Solar/Wind Harmer
0.507
20716928W4-060COL
Solar/Wind Harmer
0.328
924131AB2-057 GEN
Solar/Wind Harmer
0.449
218440SUMMTASSOC C
Solar/Wind Harmer
0.05
232416X2-083
Adder
0.177
218418LINDEN_G5
Adder
6.323
218419LINDEN_G6
Adder
6.323
972260AH1-715 GEN1
Adder
5.063
219036LINDEN_G7
Adder
5.812
219035LINDEN_G8
Adder
5.729
972261AH1-715 GEN2
Adder
5.563
217081WEATEXAS C
Solar/Wind Harmer
0.029
217202FBANKSOLAR C
Solar/Wind Harmer
0.024
217201HACKENSOLA C
Solar/Wind Harmer
0.023
972237AH1-703 GEN
Adder
3.142
217206BARNGR HS C
Solar/Wind Harmer
0.01
217086KRNY_131
Adder
2.881
217083KRNY_132
Adder
2.857
217204WCALDSOLAR C
Solar/Wind Harmer
0.022
207442AE1-156 GEN
Solar/Wind Harmer
0.195
20676128MHD_W3-029
Solar/Wind Harmer
0.125
20673828FLE_V3-070
Solar/Wind Harmer
0.118
20671828STAW2-080
Solar/Wind Harmer
0.026
213919RICHMD92
50/50
1.356
219124CAMDEN_STG
50/50
1.315
219286CAMD CO RR
50/50
0.453
230406ST-CC
50/50
4.982
230404GT1-CC
50/50
3.351
219221BRL12CT1
50/50
11.818
219223BRL12CT3
50/50
11.818
219924AG1-130 C
50/50
0.553
228304LOGAN
50/50
28.25
213542CROYDN42
50/50
0.718
219912AD2-042 GEN
Solar/Wind Harmer
1.393
219766PARADISE C
Solar/Wind Harmer
0.522
219623KINSLEYBEA C
Solar/Wind Harmer
0.672
219236SOUTHERNHQ C
Solar/Wind Harmer
0.106
219906AC1-017 C
Solar/Wind Harmer
0.309
219610FLORENCE C
Solar/Wind Harmer
1.729
219348LDSOLAR C
Solar/Wind Harmer
0.747
219291REEVESSOUT C
Solar/Wind Harmer
0.071
230415AB2-049 C
Solar/Wind Harmer
0.211
230430AE1-229_GEN
Solar/Wind Harmer
9.675
959561AF2-247 GEN
Solar/Wind Harmer
0.507
971553AH1-274 GEN
Solar/Wind Harmer
2.471
228711V2-041C
Solar/Wind Harmer
0.593
228202CUMB CT
Adder
16.163
228729W2-030 C
Solar/Wind Harmer
0.551
20716028EGP_W2-019
Solar/Wind Harmer
0.378
20720828JCB_W4-025
Solar/Wind Harmer
0.368
20715028HAN_X4-015
Solar/Wind Harmer
0.242
219727YARDVSOLFA C
Solar/Wind Harmer
0.739
972251AH1-710 GEN
Adder
35.081
20636028O CRK C1
Adder
4.861
219276PARKLANDSO C
Solar/Wind Harmer
0.32
971667AH1-334 GEN
Solar/Wind Harmer
1.829
20714528FRN_Y2-051
Solar/Wind Harmer
0.176
233971AC1-093 C
Solar/Wind Harmer
0.486
970695AG2-447 GEN
Solar/Wind Harmer
2.217
972133AH1-634 GEN
Solar/Wind Harmer
5.761
233952AC2-187 GEN
Solar/Wind Harmer
0.652
233990AG1-397 GEN
Solar/Wind Harmer
0.658
972073AH1-586 GEN
Solar/Wind Harmer
5.379
232914OH NUG3
Adder
5.061
232916OH NUG5
Adder
5.061
232921TASLEY2G
Adder
2.958
232406W1-004 FULL
Solar/Wind Harmer
0.574
234015AF2-250 C
Solar/Wind Harmer
0.069
233900O-025 C
Adder
0.674
233996TM1833_GEN
Solar/Wind Harmer
0.724
233997TMININ_4.2
Solar/Wind Harmer
0.724
233940AF2-379 C
Solar/Wind Harmer
0.107
233994AC2-023 GEN
Solar/Wind Harmer
1.531
232907VN8
Adder
16.924
960671AF2-358 GEN
Solar/Wind Harmer
10.08
232417X3-008 C
Solar/Wind Harmer
1.115
219612MATRIX C
Solar/Wind Harmer
0.096
218438BLK ROCK C
Solar/Wind Harmer
0.071
233982AB2-133 GEN
Solar/Wind Harmer
2.486
219229EAGLE PT ST
50/50
0.8
219231EAGLE PT CT2
50/50
1.58
230405GT2-CC
50/50
3.367
219224BRL12CT4
50/50
11.818
213537CROYDN21
50/50
0.718
213538CROYDN22
50/50
0.718
213539CROYDN31
50/50
0.718
213540CROYDN32
50/50
0.703
228309CCLP NUG
50/50
30.82
219914AD2-027 C
Solar/Wind Harmer
1.051
219137THOSOLAR C
Solar/Wind Harmer
1.72
219272CLEANLIGHT C
Solar/Wind Harmer
0.23
219607WPEMNERT C
Solar/Wind Harmer
0.523
219688LUMSOLAR_S C
Solar/Wind Harmer
0.244
971011AG2-627 GEN
Solar/Wind Harmer
8.896
964001AG1-254 GEN
Solar/Wind Harmer
2.293
228309CCLP NUG
Adder
27.628
972141AH1-641 GEN
Solar/Wind Harmer
3.165
971535AH1-265 GEN
Solar/Wind Harmer
4.602
228260V4-054C
Solar/Wind Harmer
1.084
970453AG2-297 GEN
Solar/Wind Harmer
2.667
228754AB1-001 C
Solar/Wind Harmer
0.133
227927V4-067C
Solar/Wind Harmer
0.188
214067T20SOLAR
Solar/Wind Harmer
0.223
213611FALLS1-3
Adder
3.121
213611FALLS1-3
Adder
3.121
20717128DIX_Z2-102
Solar/Wind Harmer
1.05
20715728PEM_W1-119
Solar/Wind Harmer
0.42
20715828PEM_W1-120
Solar/Wind Harmer
0.42
971189AH1-054 GEN
Solar/Wind Harmer
0.834
970025AG2-016 GEN
Solar/Wind Harmer
1.926
207459AE1-142 C O1
Solar/Wind Harmer
0.693
233973AC2-185 C
Solar/Wind Harmer
2.236
234033AF1-007_GEN
Solar/Wind Harmer
13.586
232904IR4
Adder
46.977
232920IR10
Adder
1.833
232432Z2-076 GEN
Solar/Wind Harmer
0.076
233990AG1-397 GEN
Solar/Wind Harmer
0.032
232912OH NUG1
Adder
5.061
232913OH NUG2
Adder
4.993
233923SMA
Solar/Wind Harmer
2.655
232813VAUGHN
Adder
0.336
20714328BYD_X4-031
Solar/Wind Harmer
0.154
233955AB2-172 GEN
Solar/Wind Harmer
2.788
20714428HOW_X1-037
Solar/Wind Harmer
0.656
233968AD2-076_GEN
Solar/Wind Harmer
3.437
970597AG2-380 GEN
Solar/Wind Harmer
2.158
971521AH1-258 GEN
Solar/Wind Harmer
1.35
232436AB1-176 C
Solar/Wind Harmer
0.119
20720428HOL_W1-112
Solar/Wind Harmer
0.17
971983AH1-536 GEN
Solar/Wind Harmer
3.805
231906DC3 NUG
Adder
7.024
231902DC CT7
Adder
5.615
231907DC10
Adder
1.754
219620RIDERU C
Solar/Wind Harmer
0.026
233935AB2-179 C
Solar/Wind Harmer
1.128
218455CINNBAY_CGEN
Adder
0.793
20635928PARLN3&4
Adder
3.19
218526CNTRALGAS2 C
Solar/Wind Harmer
0.151
218524CNTRALGAS1 C
Solar/Wind Harmer
0.144
218404KENILWRTH C
Adder
0.416
231919CHRIST1
Adder
1.411
231920CHRIST2
Adder
1.38
217167KRNY_14
Adder
2.875
217086KRNY_131
Adder
2.851
217147KRNY_1212
Adder
2.735
217147KRNY_1212
Adder
2.686
217146KRNY_1234
Adder
2.68
217146KRNY_1234
Adder
2.662
20675528CPH_W2-050
Solar/Wind Harmer
0.119
233918AB1-142 GEN
Solar/Wind Harmer
0.504
20720528MAN_W1-024
Solar/Wind Harmer
0.122
20716228APLW2-078
Solar/Wind Harmer
0.422
219918AC2-009 C
Solar/Wind Harmer
0.029
20635828PARLN1&2
Adder
1.445
20635928PARLN3&4
Adder
1.445
967451AG2-055 C O1
Solar/Wind Harmer
72.184
20635028RRCT1&2
Adder
4.874
20635128RRCT3&4
Adder
4.041
219908AB1-139 C
Solar/Wind Harmer
0.147
219919AE1-041 FULL
Solar/Wind Harmer
0.016
219249CENTRALDIV C
Solar/Wind Harmer
0.013
217211CAMDEN ST C
Solar/Wind Harmer
0.008
217186ESSEX_G9
Adder
4.952
217169METRODIV C
Solar/Wind Harmer
0.012
217194REDH C
Solar/Wind Harmer
0.152
20673728F2S_V4-070
Solar/Wind Harmer
0.047
20676728BRNX1-095
Solar/Wind Harmer
0.046
213918RICHMD91
50/50
1.356
219230EAGLE PT CT1
50/50
1.581
219235Y2-105
50/50
0.571
219222BRL12CT2
50/50
11.818
213536CROYDN12
50/50
6.049
213541CROYDN41
50/50
0.718
219904AC1-010 C
Solar/Wind Harmer
0.628
219907AC1-030 C
Solar/Wind Harmer
0.22
219258KINSLEYDEP C
Solar/Wind Harmer
0.504
219304NAMERICA C
Solar/Wind Harmer
0.388
218660EHAMPSOLAR C
Solar/Wind Harmer
0.206
230434AG1-499 GEN
Solar/Wind Harmer
0.677
219686LUMSOLAR_N C
Solar/Wind Harmer
0.236
219287REEVESEAST C
Solar/Wind Harmer
1.568
228351V2-046C
Solar/Wind Harmer
2.274
970997AG2-616 GEN
Solar/Wind Harmer
10.551
230511AF1-262
Solar/Wind Harmer
0.201
945431AF1-208 GEN
Solar/Wind Harmer
9.302
228728W1-130C
Solar/Wind Harmer
0.708
228206SHRMN CT
Adder
16.487
228732V1-021 C
Adder
0.183
213611FALLS1-3
Adder
3.121
20720728JCB_W1-129
Solar/Wind Harmer
0.242
207522AF2-254 C
Solar/Wind Harmer
1.153
207487AE2-000G4
Solar/Wind Harmer
21.662
207445AB1-138_GEN
Solar/Wind Harmer
0.381
20628028LAKEHURS
Adder
1.236
963711AG1-223 GEN
Solar/Wind Harmer
0.889
20714828MDF_W3-079
Solar/Wind Harmer
0.184
233972AC1-094 C
Solar/Wind Harmer
0.411
232901NORTHST
Adder
5.065
232900DEMECSMY
Adder
5.576
972177AH1-672 GEN
Solar/Wind Harmer
7.862
233954AC2-188 GEN
Solar/Wind Harmer
0.652
233950AC2-186 GEN
Solar/Wind Harmer
0.326
232434Z2-077 GEN
Solar/Wind Harmer
0.145
232917OH NUG6
Adder
5.038
232915OH NUG4
Adder
5.027
232404W1-003 C
Solar/Wind Harmer
0.574
971195AH1-057 GEN
Solar/Wind Harmer
0.626
233998TM1NIN_3.36
Solar/Wind Harmer
0.724
232428Y3-058 C
Solar/Wind Harmer
0.476
232910NRG_G1
Adder
4.884
232919VN10
Adder
1.584
965821AG1-450 GEN
Solar/Wind Harmer
2.93
232426Y1-080 FULL
Solar/Wind Harmer
0.107
970277AG2-181 GEN
Solar/Wind Harmer
2.819
233964AF2-378 GEN
Solar/Wind Harmer
0.072
207454AA2-184 E
Solar/Wind Harmer
0.528
217197RE CRAN C
Solar/Wind Harmer
0.28
234012AE2-112_GEN
Solar/Wind Harmer
1.192
232422X3-066 FULL
Solar/Wind Harmer
0.13
233930AB2-032 GEN
Solar/Wind Harmer
0.424
233915AB1-141 GEN
Solar/Wind Harmer
0.504
20715228NPK_W1-113
Solar/Wind Harmer
0.205
20742028HF_AC1-207
Solar/Wind Harmer
0.371
219680HOPEWELLV C1
Solar/Wind Harmer
0.035
20635828PARLN1&2
Adder
3.19
20635028RRCT1&2
Adder
4.799
20635128RRCT3&4
Adder
4.633
218428ETC SOLAR C
Solar/Wind Harmer
0.014
217213AMBOY SO C
Solar/Wind Harmer
0.048
972275AH1-722 GEN
Adder
11.623
218449LINSOLAR C
Solar/Wind Harmer
0.35
217209CENTRL HS C
Solar/Wind Harmer
0.014
231918WEST 1
Adder
1.09
217121ECCF
Adder
0.135
217083KRNY_132
Adder
2.875
217208PARK ELE C
Solar/Wind Harmer
0.008
231917EM10
Adder
0.663
207528AF2-192 GEN
Solar/Wind Harmer
0.145
20673628F1S_V4-069
Solar/Wind Harmer
0.047
20675428EAM_W2-061
Solar/Wind Harmer
0.05
20676428JCR_X2-075
Solar/Wind Harmer
0.089
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.015
G-007ALTFEXP_G-007A->PJM
CMTX
21.198
CBM NorthLTFEXP_CBM-N->PJM
CBM
16.653
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.93
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.896
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
43.544
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.61
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.334

Details for RICHRE29-RICHMOND29 230.0 kV Ckt 1 line l/o PECO_P4_CHICH045_SRT-A/* $ DELCO $ PECO_P4_CHICH045 $ STBK


Base Case Flowgate

Area:PECO
Facility Description:
RICHRE29-RICHMOND29 230.0 kV Ckt 1 line
Contingency Name:
PECO_P4_CHICH045_SRT-A/* $ DELCO $ PECO_P4_CHICH045 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.47 %
Rating:1336.0 MVA
Rating Type:B
MVA to Mitigate:1449.19
MW Contribution:9.03
Bus #Bus NameTypeMW Contribution
219230EAGLE PT CT1
50/50
1.647
219235Y2-105
50/50
0.595
219904AC1-010 C
Solar/Wind Harmer
0.647
219258KINSLEYDEP C
Solar/Wind Harmer
0.526
219907AC1-030 C
Solar/Wind Harmer
0.201
230434AG1-499 GEN
Solar/Wind Harmer
0.671
228351V2-046C
Solar/Wind Harmer
2.274
970997AG2-616 GEN
Solar/Wind Harmer
10.419
230511AF1-262
Solar/Wind Harmer
0.196
945431AF1-208 GEN
Solar/Wind Harmer
9.097
228728W1-130C
Solar/Wind Harmer
0.679
219126CAMDEN_CTG
50/50
1.666
219267WHEELBRDEPTF
50/50
0.234
219240MANTUACREK E
50/50
0.761
219726BAT.STORG E
50/50
0.369
972233AH1-701 GEN
50/50
5.793
228304LOGAN
50/50
32.871
228307PCLP GT
50/50
15.939
213400COVANTA DELA
50/50
1.115
219921AF1-264
Solar/Wind Harmer
0.237
219615MILLCREEK C
Solar/Wind Harmer
0.247
228251CARLLS#4
Adder
0.644
230407AD2-065 C
Solar/Wind Harmer
0.134
230433AD2-135 GEN
Solar/Wind Harmer
0.102
230422AE1-104_GEN1
Solar/Wind Harmer
29.724
230425AE1-104_GEN2
Solar/Wind Harmer
29.724
20716428NHV_W2-082
Solar/Wind Harmer
1.103
207500AE2-000G1
Solar/Wind Harmer
16.555
207497AE2-000G2
Solar/Wind Harmer
16.555
207507AE2-000G3
Solar/Wind Harmer
16.555
20636128O CRK C2
Adder
3.387
963401AG1-189 GEN
Solar/Wind Harmer
0.593
20714928UPF_X1-085
Solar/Wind Harmer
0.208
963391AG1-188 GEN
Solar/Wind Harmer
0.978
232416X2-083
Adder
0.236
233939AC1-091 C
Solar/Wind Harmer
0.455
233970AC1-092 C
Solar/Wind Harmer
0.455
971149AH1-027 GEN
Solar/Wind Harmer
1.743
232899W1-062
Adder
4.93
970545AG2-347 GEN
Solar/Wind Harmer
33.092
20628028LAKEHURS
Adder
0.456
231940T-011
Adder
0.376
972069AH1-584 GEN
Solar/Wind Harmer
4.508
972071AH1-585 GEN
Solar/Wind Harmer
4.508
971747AH1-380 GEN
Solar/Wind Harmer
1.803
233901CHERRYDALE C
Solar/Wind Harmer
0.566
232918OH NUG7
Adder
4.414
232905CHERITON_25
Adder
1.234
232408W1-005 C
Solar/Wind Harmer
0.504
232410W1-006 C
Solar/Wind Harmer
0.504
232926CRISFLD1
Adder
0.987
233946AB2-136 GEN
Solar/Wind Harmer
1.989
231131BLOOM ENRGY
Adder
2.171
234036AF2-325 C
Solar/Wind Harmer
0.457
234041AC1-190 GEN
Solar/Wind Harmer
4.453
233987AB2-037 GEN
Solar/Wind Harmer
5.633
213535CROYDN11
Adder
4.756
219114HARTZY_C
Solar/Wind Harmer
0.391
233984AB2-036 GEN
Solar/Wind Harmer
6.019
232424Y1-079 C
Solar/Wind Harmer
0.272
234014AF1-036_GEN
Solar/Wind Harmer
1.293
233944AB2-135 GEN
Solar/Wind Harmer
2.497
233933AB2-153 GEN
Solar/Wind Harmer
0.531
20720628TIN_W1-124
Solar/Wind Harmer
0.342
20641628MLH_W1-032
Solar/Wind Harmer
0.084
20716928W4-060COL
Solar/Wind Harmer
0.195
219124CAMDEN_STG
50/50
1.356
219286CAMD CO RR
50/50
0.468
230406ST-CC
50/50
5.361
230404GT1-CC
50/50
3.606
228304LOGAN
50/50
29.564
219912AD2-042 GEN
Solar/Wind Harmer
1.435
219766PARADISE C
Solar/Wind Harmer
0.539
219623KINSLEYBEA C
Solar/Wind Harmer
0.685
219236SOUTHERNHQ C
Solar/Wind Harmer
0.097
230430AE1-229_GEN
Solar/Wind Harmer
9.527
230415AB2-049 C
Solar/Wind Harmer
0.198
219906AC1-017 C
Solar/Wind Harmer
0.231
219291REEVESSOUT C
Solar/Wind Harmer
0.058
971553AH1-274 GEN
Solar/Wind Harmer
2.336
228711V2-041C
Solar/Wind Harmer
0.553
228202CUMB CT
Adder
15.027
228729W2-030 C
Solar/Wind Harmer
0.501
219610FLORENCE C
Solar/Wind Harmer
1.028
219348LDSOLAR C
Solar/Wind Harmer
0.444
219221BRL12CT1
Adder
6.624
219223BRL12CT3
Adder
6.624
20716028EGP_W2-019
Solar/Wind Harmer
0.291
20720828JCB_W4-025
Solar/Wind Harmer
0.283
20715028HAN_X4-015
Solar/Wind Harmer
0.186
959561AF2-247 GEN
Solar/Wind Harmer
0.29
972251AH1-710 GEN
Adder
27.658
20636028O CRK C1
Adder
3.715
233971AC1-093 C
Solar/Wind Harmer
0.406
970695AG2-447 GEN
Solar/Wind Harmer
1.856
971667AH1-334 GEN
Solar/Wind Harmer
1.345
972133AH1-634 GEN
Solar/Wind Harmer
5.014
233952AC2-187 GEN
Solar/Wind Harmer
0.567
972073AH1-586 GEN
Solar/Wind Harmer
4.718
233990AG1-397 GEN
Solar/Wind Harmer
0.577
232914OH NUG3
Adder
4.443
232916OH NUG5
Adder
4.443
232921TASLEY2G
Adder
2.597
232406W1-004 FULL
Solar/Wind Harmer
0.504
234015AF2-250 C
Solar/Wind Harmer
0.061
233996TM1833_GEN
Solar/Wind Harmer
0.637
233997TMININ_4.2
Solar/Wind Harmer
0.637
233900O-025 C
Adder
0.592
233940AF2-379 C
Solar/Wind Harmer
0.094
233994AC2-023 GEN
Solar/Wind Harmer
1.349
232907VN8
Adder
15.015
960671AF2-358 GEN
Solar/Wind Harmer
8.942
232417X3-008 C
Solar/Wind Harmer
0.994
233982AB2-133 GEN
Solar/Wind Harmer
2.3
233918AB1-142 GEN
Solar/Wind Harmer
0.468
219727YARDVSOLFA C
Solar/Wind Harmer
0.392
20714528FRN_Y2-051
Solar/Wind Harmer
0.122
219229EAGLE PT ST
50/50
0.833
219231EAGLE PT CT2
50/50
1.646
230405GT2-CC
50/50
3.623
219914AD2-027 C
Solar/Wind Harmer
1.083
219137THOSOLAR C
Solar/Wind Harmer
1.822
971011AG2-627 GEN
Solar/Wind Harmer
9.025
228309CCLP NUG
Adder
29.24
228309CCLP NUG
Adder
27.814
964001AG1-254 GEN
Solar/Wind Harmer
2.296
972141AH1-641 GEN
Solar/Wind Harmer
3.126
219272CLEANLIGHT C
Solar/Wind Harmer
0.199
971535AH1-265 GEN
Solar/Wind Harmer
4.38
228260V4-054C
Solar/Wind Harmer
1.047
219688LUMSOLAR_S C
Solar/Wind Harmer
0.193
970453AG2-297 GEN
Solar/Wind Harmer
2.469
228754AB1-001 C
Solar/Wind Harmer
0.121
227927V4-067C
Solar/Wind Harmer
0.17
219607WPEMNERT C
Solar/Wind Harmer
0.311
219224BRL12CT4
Adder
6.624
20717128DIX_Z2-102
Solar/Wind Harmer
0.804
20715728PEM_W1-119
Solar/Wind Harmer
0.321
20715828PEM_W1-120
Solar/Wind Harmer
0.321
231919CHRIST1
Adder
2.554
231920CHRIST2
Adder
2.497
971189AH1-054 GEN
Solar/Wind Harmer
0.624
970025AG2-016 GEN
Solar/Wind Harmer
1.448
233973AC2-185 C
Solar/Wind Harmer
1.872
207459AE1-142 C O1
Solar/Wind Harmer
0.51
234033AF1-007_GEN
Solar/Wind Harmer
11.825
232904IR4
Adder
40.889
232920IR10
Adder
1.597
232432Z2-076 GEN
Solar/Wind Harmer
0.067
233990AG1-397 GEN
Solar/Wind Harmer
0.028
232912OH NUG1
Adder
4.443
232913OH NUG2
Adder
4.384
233923SMA
Solar/Wind Harmer
2.334
232813VAUGHN
Adder
0.294
233955AB2-172 GEN
Solar/Wind Harmer
2.486
231906DC3 NUG
Adder
6.906
231902DC CT7
Adder
5.521
231907DC10
Adder
1.724
233968AD2-076_GEN
Solar/Wind Harmer
3.168
970597AG2-380 GEN
Solar/Wind Harmer
1.99
232436AB1-176 C
Solar/Wind Harmer
0.109
971983AH1-536 GEN
Solar/Wind Harmer
3.534
233935AB2-179 C
Solar/Wind Harmer
1.103
20714328BYD_X4-031
Solar/Wind Harmer
0.101
20714428HOW_X1-037
Solar/Wind Harmer
0.426
971521AH1-258 GEN
Solar/Wind Harmer
0.846
20720428HOL_W1-112
Solar/Wind Harmer
0.105
20635928PARLN3&4
Adder
1.804
218660EHAMPSOLAR C
Solar/Wind Harmer
0.17
219686LUMSOLAR_N C
Solar/Wind Harmer
0.196
219287REEVESEAST C
Solar/Wind Harmer
1.303
228206SHRMN CT
Adder
15.434
228732V1-021 C
Adder
0.168
219304NAMERICA C
Solar/Wind Harmer
0.231
219222BRL12CT2
Adder
6.624
20720728JCB_W1-129
Solar/Wind Harmer
0.186
207522AF2-254 C
Solar/Wind Harmer
0.885
231917EM10
Adder
1.422
231918WEST 1
Adder
1.902
207487AE2-000G4
Solar/Wind Harmer
16.555
233972AC1-094 C
Solar/Wind Harmer
0.344
232901NORTHST
Adder
4.287
232900DEMECSMY
Adder
4.729
972177AH1-672 GEN
Solar/Wind Harmer
6.808
232434Z2-077 GEN
Solar/Wind Harmer
0.126
207445AB1-138_GEN
Solar/Wind Harmer
0.278
20628028LAKEHURS
Adder
0.902
233954AC2-188 GEN
Solar/Wind Harmer
0.567
233950AC2-186 GEN
Solar/Wind Harmer
0.283
232917OH NUG6
Adder
4.424
232915OH NUG4
Adder
4.414
232404W1-003 C
Solar/Wind Harmer
0.504
971195AH1-057 GEN
Solar/Wind Harmer
0.55
233998TM1NIN_3.36
Solar/Wind Harmer
0.637
232428Y3-058 C
Solar/Wind Harmer
0.419
232919VN10
Adder
1.403
965821AG1-450 GEN
Solar/Wind Harmer
2.599
232426Y1-080 FULL
Solar/Wind Harmer
0.095
970277AG2-181 GEN
Solar/Wind Harmer
2.502
233964AF2-378 GEN
Solar/Wind Harmer
0.064
232910NRG_G1
Adder
4.287
234012AE2-112_GEN
Solar/Wind Harmer
1.099
232422X3-066 FULL
Solar/Wind Harmer
0.119
233930AB2-032 GEN
Solar/Wind Harmer
0.394
233915AB1-141 GEN
Solar/Wind Harmer
0.468
963711AG1-223 GEN
Solar/Wind Harmer
0.619
20714828MDF_W3-079
Solar/Wind Harmer
0.128
207454AA2-184 E
Solar/Wind Harmer
0.343
20715228NPK_W1-113
Solar/Wind Harmer
0.12
20742028HF_AC1-207
Solar/Wind Harmer
0.219
217197RE CRAN C
Solar/Wind Harmer
0.135
20635828PARLN1&2
Adder
1.804
219276PARKLANDSO C
Solar/Wind Harmer
0.16
20720528MAN_W1-024
Solar/Wind Harmer
0.073
20716228APLW2-078
Solar/Wind Harmer
0.247
219612MATRIX C
Solar/Wind Harmer
0.046
218438BLK ROCK C
Solar/Wind Harmer
0.034
20635828PARLN1&2
Adder
0.817
20635928PARLN3&4
Adder
0.817
967451AG2-055 C O1
Solar/Wind Harmer
40.283
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.502
G-007ALTFEXP_G-007A->PJM
CMTX
11.581
CBM NorthLTFEXP_CBM-N->PJM
CBM
4.513
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.496
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.545
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
17.921
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.306
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
2.299

Details for RICHRE29-RICHMOND29 230.0 kV Ckt 1 line l/o PECO_P4_CHICH195_SRT-A/* $ DELCO $ PECO_P4_CHICH195 $ STBK


Base Case Flowgate

Area:PECO
Facility Description:
RICHRE29-RICHMOND29 230.0 kV Ckt 1 line
Contingency Name:
PECO_P4_CHICH195_SRT-A/* $ DELCO $ PECO_P4_CHICH195 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.47 %
Rating:1336.0 MVA
Rating Type:B
MVA to Mitigate:1449.12
MW Contribution:9.03
Bus #Bus NameTypeMW Contribution
219126CAMDEN_CTG
50/50
1.666
219267WHEELBRDEPTF
50/50
0.234
219240MANTUACREK E
50/50
0.761
219726BAT.STORG E
50/50
0.369
972233AH1-701 GEN
50/50
5.793
228304LOGAN
50/50
32.871
228307PCLP GT
50/50
15.939
213400COVANTA DELA
50/50
1.115
219921AF1-264
Solar/Wind Harmer
0.237
219615MILLCREEK C
Solar/Wind Harmer
0.247
228251CARLLS#4
Adder
0.644
230407AD2-065 C
Solar/Wind Harmer
0.134
230433AD2-135 GEN
Solar/Wind Harmer
0.102
230422AE1-104_GEN1
Solar/Wind Harmer
29.724
230425AE1-104_GEN2
Solar/Wind Harmer
29.724
20716428NHV_W2-082
Solar/Wind Harmer
1.103
207500AE2-000G1
Solar/Wind Harmer
16.555
207497AE2-000G2
Solar/Wind Harmer
16.555
207507AE2-000G3
Solar/Wind Harmer
16.555
20636128O CRK C2
Adder
3.387
963401AG1-189 GEN
Solar/Wind Harmer
0.593
20714928UPF_X1-085
Solar/Wind Harmer
0.208
963391AG1-188 GEN
Solar/Wind Harmer
0.978
232416X2-083
Adder
0.236
233939AC1-091 C
Solar/Wind Harmer
0.455
233970AC1-092 C
Solar/Wind Harmer
0.455
971149AH1-027 GEN
Solar/Wind Harmer
1.743
232899W1-062
Adder
4.93
970545AG2-347 GEN
Solar/Wind Harmer
33.092
20628028LAKEHURS
Adder
0.456
231940T-011
Adder
0.376
972069AH1-584 GEN
Solar/Wind Harmer
4.508
972071AH1-585 GEN
Solar/Wind Harmer
4.508
971747AH1-380 GEN
Solar/Wind Harmer
1.803
233901CHERRYDALE C
Solar/Wind Harmer
0.566
232918OH NUG7
Adder
4.414
232905CHERITON_25
Adder
1.234
232408W1-005 C
Solar/Wind Harmer
0.504
232410W1-006 C
Solar/Wind Harmer
0.504
232926CRISFLD1
Adder
0.987
233946AB2-136 GEN
Solar/Wind Harmer
1.989
231131BLOOM ENRGY
Adder
2.171
234036AF2-325 C
Solar/Wind Harmer
0.457
234041AC1-190 GEN
Solar/Wind Harmer
4.453
233987AB2-037 GEN
Solar/Wind Harmer
5.633
213535CROYDN11
Adder
4.756
219114HARTZY_C
Solar/Wind Harmer
0.391
233984AB2-036 GEN
Solar/Wind Harmer
6.019
232424Y1-079 C
Solar/Wind Harmer
0.272
234014AF1-036_GEN
Solar/Wind Harmer
1.293
233944AB2-135 GEN
Solar/Wind Harmer
2.497
233933AB2-153 GEN
Solar/Wind Harmer
0.531
20720628TIN_W1-124
Solar/Wind Harmer
0.342
20641628MLH_W1-032
Solar/Wind Harmer
0.084
20716928W4-060COL
Solar/Wind Harmer
0.195
219229EAGLE PT ST
50/50
0.833
219231EAGLE PT CT2
50/50
1.646
230405GT2-CC
50/50
3.623
219914AD2-027 C
Solar/Wind Harmer
1.083
219137THOSOLAR C
Solar/Wind Harmer
1.822
971011AG2-627 GEN
Solar/Wind Harmer
9.025
228309CCLP NUG
Adder
29.24
228309CCLP NUG
Adder
27.814
964001AG1-254 GEN
Solar/Wind Harmer
2.296
972141AH1-641 GEN
Solar/Wind Harmer
3.126
219272CLEANLIGHT C
Solar/Wind Harmer
0.199
971535AH1-265 GEN
Solar/Wind Harmer
4.38
228260V4-054C
Solar/Wind Harmer
1.047
219688LUMSOLAR_S C
Solar/Wind Harmer
0.193
970453AG2-297 GEN
Solar/Wind Harmer
2.469
228754AB1-001 C
Solar/Wind Harmer
0.121
227927V4-067C
Solar/Wind Harmer
0.17
219607WPEMNERT C
Solar/Wind Harmer
0.311
219224BRL12CT4
Adder
6.624
20717128DIX_Z2-102
Solar/Wind Harmer
0.804
20715728PEM_W1-119
Solar/Wind Harmer
0.321
20715828PEM_W1-120
Solar/Wind Harmer
0.321
231919CHRIST1
Adder
2.554
231920CHRIST2
Adder
2.497
971189AH1-054 GEN
Solar/Wind Harmer
0.624
970025AG2-016 GEN
Solar/Wind Harmer
1.448
233973AC2-185 C
Solar/Wind Harmer
1.872
207459AE1-142 C O1
Solar/Wind Harmer
0.51
234033AF1-007_GEN
Solar/Wind Harmer
11.825
232904IR4
Adder
40.889
232920IR10
Adder
1.597
232432Z2-076 GEN
Solar/Wind Harmer
0.067
233990AG1-397 GEN
Solar/Wind Harmer
0.028
232912OH NUG1
Adder
4.443
232913OH NUG2
Adder
4.384
233923SMA
Solar/Wind Harmer
2.334
232813VAUGHN
Adder
0.294
233955AB2-172 GEN
Solar/Wind Harmer
2.486
231906DC3 NUG
Adder
6.906
231902DC CT7
Adder
5.521
231907DC10
Adder
1.724
233968AD2-076_GEN
Solar/Wind Harmer
3.168
970597AG2-380 GEN
Solar/Wind Harmer
1.99
232436AB1-176 C
Solar/Wind Harmer
0.109
971983AH1-536 GEN
Solar/Wind Harmer
3.534
233935AB2-179 C
Solar/Wind Harmer
1.103
20714328BYD_X4-031
Solar/Wind Harmer
0.101
20714428HOW_X1-037
Solar/Wind Harmer
0.426
971521AH1-258 GEN
Solar/Wind Harmer
0.846
20720428HOL_W1-112
Solar/Wind Harmer
0.105
20635928PARLN3&4
Adder
1.804
219230EAGLE PT CT1
50/50
1.647
219235Y2-105
50/50
0.595
219904AC1-010 C
Solar/Wind Harmer
0.647
219258KINSLEYDEP C
Solar/Wind Harmer
0.526
219907AC1-030 C
Solar/Wind Harmer
0.201
230434AG1-499 GEN
Solar/Wind Harmer
0.671
228351V2-046C
Solar/Wind Harmer
2.274
970997AG2-616 GEN
Solar/Wind Harmer
10.419
230511AF1-262
Solar/Wind Harmer
0.196
945431AF1-208 GEN
Solar/Wind Harmer
9.097
228728W1-130C
Solar/Wind Harmer
0.679
218660EHAMPSOLAR C
Solar/Wind Harmer
0.17
219686LUMSOLAR_N C
Solar/Wind Harmer
0.196
219287REEVESEAST C
Solar/Wind Harmer
1.303
228206SHRMN CT
Adder
15.434
228732V1-021 C
Adder
0.168
219304NAMERICA C
Solar/Wind Harmer
0.231
219222BRL12CT2
Adder
6.624
20720728JCB_W1-129
Solar/Wind Harmer
0.186
207522AF2-254 C
Solar/Wind Harmer
0.885
231917EM10
Adder
1.422
231918WEST 1
Adder
1.902
207487AE2-000G4
Solar/Wind Harmer
16.555
233972AC1-094 C
Solar/Wind Harmer
0.344
232901NORTHST
Adder
4.287
232900DEMECSMY
Adder
4.729
972177AH1-672 GEN
Solar/Wind Harmer
6.808
232434Z2-077 GEN
Solar/Wind Harmer
0.126
207445AB1-138_GEN
Solar/Wind Harmer
0.278
20628028LAKEHURS
Adder
0.902
233954AC2-188 GEN
Solar/Wind Harmer
0.567
233950AC2-186 GEN
Solar/Wind Harmer
0.283
232917OH NUG6
Adder
4.424
232915OH NUG4
Adder
4.414
232404W1-003 C
Solar/Wind Harmer
0.504
971195AH1-057 GEN
Solar/Wind Harmer
0.55
233998TM1NIN_3.36
Solar/Wind Harmer
0.637
232428Y3-058 C
Solar/Wind Harmer
0.419
232919VN10
Adder
1.403
965821AG1-450 GEN
Solar/Wind Harmer
2.599
232426Y1-080 FULL
Solar/Wind Harmer
0.095
970277AG2-181 GEN
Solar/Wind Harmer
2.502
233964AF2-378 GEN
Solar/Wind Harmer
0.064
232910NRG_G1
Adder
4.287
234012AE2-112_GEN
Solar/Wind Harmer
1.099
232422X3-066 FULL
Solar/Wind Harmer
0.119
233930AB2-032 GEN
Solar/Wind Harmer
0.394
233915AB1-141 GEN
Solar/Wind Harmer
0.468
963711AG1-223 GEN
Solar/Wind Harmer
0.619
20714828MDF_W3-079
Solar/Wind Harmer
0.128
207454AA2-184 E
Solar/Wind Harmer
0.343
20715228NPK_W1-113
Solar/Wind Harmer
0.12
20742028HF_AC1-207
Solar/Wind Harmer
0.219
217197RE CRAN C
Solar/Wind Harmer
0.135
20635828PARLN1&2
Adder
1.804
219124CAMDEN_STG
50/50
1.356
219286CAMD CO RR
50/50
0.468
230406ST-CC
50/50
5.361
230404GT1-CC
50/50
3.606
228304LOGAN
50/50
29.564
219912AD2-042 GEN
Solar/Wind Harmer
1.435
219766PARADISE C
Solar/Wind Harmer
0.539
219623KINSLEYBEA C
Solar/Wind Harmer
0.685
219236SOUTHERNHQ C
Solar/Wind Harmer
0.097
230430AE1-229_GEN
Solar/Wind Harmer
9.527
230415AB2-049 C
Solar/Wind Harmer
0.198
219906AC1-017 C
Solar/Wind Harmer
0.231
219291REEVESSOUT C
Solar/Wind Harmer
0.058
971553AH1-274 GEN
Solar/Wind Harmer
2.336
228711V2-041C
Solar/Wind Harmer
0.553
228202CUMB CT
Adder
15.027
228729W2-030 C
Solar/Wind Harmer
0.501
219610FLORENCE C
Solar/Wind Harmer
1.028
219348LDSOLAR C
Solar/Wind Harmer
0.444
219221BRL12CT1
Adder
6.624
219223BRL12CT3
Adder
6.624
20716028EGP_W2-019
Solar/Wind Harmer
0.291
20720828JCB_W4-025
Solar/Wind Harmer
0.283
20715028HAN_X4-015
Solar/Wind Harmer
0.186
959561AF2-247 GEN
Solar/Wind Harmer
0.29
972251AH1-710 GEN
Adder
27.658
20636028O CRK C1
Adder
3.715
233971AC1-093 C
Solar/Wind Harmer
0.406
970695AG2-447 GEN
Solar/Wind Harmer
1.856
971667AH1-334 GEN
Solar/Wind Harmer
1.345
972133AH1-634 GEN
Solar/Wind Harmer
5.014
233952AC2-187 GEN
Solar/Wind Harmer
0.567
972073AH1-586 GEN
Solar/Wind Harmer
4.718
233990AG1-397 GEN
Solar/Wind Harmer
0.577
232914OH NUG3
Adder
4.443
232916OH NUG5
Adder
4.443
232921TASLEY2G
Adder
2.597
232406W1-004 FULL
Solar/Wind Harmer
0.504
234015AF2-250 C
Solar/Wind Harmer
0.061
233996TM1833_GEN
Solar/Wind Harmer
0.637
233997TMININ_4.2
Solar/Wind Harmer
0.637
233900O-025 C
Adder
0.592
233940AF2-379 C
Solar/Wind Harmer
0.094
233994AC2-023 GEN
Solar/Wind Harmer
1.349
232907VN8
Adder
15.015
960671AF2-358 GEN
Solar/Wind Harmer
8.942
232417X3-008 C
Solar/Wind Harmer
0.994
233982AB2-133 GEN
Solar/Wind Harmer
2.3
233918AB1-142 GEN
Solar/Wind Harmer
0.468
219727YARDVSOLFA C
Solar/Wind Harmer
0.392
20714528FRN_Y2-051
Solar/Wind Harmer
0.122
219276PARKLANDSO C
Solar/Wind Harmer
0.16
20720528MAN_W1-024
Solar/Wind Harmer
0.073
20716228APLW2-078
Solar/Wind Harmer
0.247
219612MATRIX C
Solar/Wind Harmer
0.046
218438BLK ROCK C
Solar/Wind Harmer
0.034
20635828PARLN1&2
Adder
0.817
20635928PARLN3&4
Adder
0.817
967451AG2-055 C O1
Solar/Wind Harmer
40.283
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.502
G-007ALTFEXP_G-007A->PJM
CMTX
11.581
CBM NorthLTFEXP_CBM-N->PJM
CBM
4.513
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.496
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.545
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
17.921
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.306
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
2.299

Details for RICHRE29-RICHMOND29 230.0 kV Ckt 1 line l/o PECO_P4_CHICH435_SRT-A/* $ DELCO $ PECO_P4_CHICH435 $ STBK


Base Case Flowgate

Area:PECO
Facility Description:
RICHRE29-RICHMOND29 230.0 kV Ckt 1 line
Contingency Name:
PECO_P4_CHICH435_SRT-A/* $ DELCO $ PECO_P4_CHICH435 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.46 %
Rating:1336.0 MVA
Rating Type:B
MVA to Mitigate:1449.07
MW Contribution:9.03
Bus #Bus NameTypeMW Contribution
219126CAMDEN_CTG
50/50
1.666
219267WHEELBRDEPTF
50/50
0.234
219240MANTUACREK E
50/50
0.761
219726BAT.STORG E
50/50
0.369
972233AH1-701 GEN
50/50
5.794
228304LOGAN
50/50
32.872
228307PCLP GT
50/50
15.939
213400COVANTA DELA
50/50
1.115
219921AF1-264
Solar/Wind Harmer
0.237
219615MILLCREEK C
Solar/Wind Harmer
0.247
228251CARLLS#4
Adder
0.644
230407AD2-065 C
Solar/Wind Harmer
0.134
230433AD2-135 GEN
Solar/Wind Harmer
0.102
230422AE1-104_GEN1
Solar/Wind Harmer
29.725
230425AE1-104_GEN2
Solar/Wind Harmer
29.725
20716428NHV_W2-082
Solar/Wind Harmer
1.103
207500AE2-000G1
Solar/Wind Harmer
16.555
207497AE2-000G2
Solar/Wind Harmer
16.555
207507AE2-000G3
Solar/Wind Harmer
16.555
20636128O CRK C2
Adder
3.387
963401AG1-189 GEN
Solar/Wind Harmer
0.593
20714928UPF_X1-085
Solar/Wind Harmer
0.208
963391AG1-188 GEN
Solar/Wind Harmer
0.978
232416X2-083
Adder
0.236
233939AC1-091 C
Solar/Wind Harmer
0.455
233970AC1-092 C
Solar/Wind Harmer
0.455
971149AH1-027 GEN
Solar/Wind Harmer
1.743
232899W1-062
Adder
4.929
970545AG2-347 GEN
Solar/Wind Harmer
33.089
20628028LAKEHURS
Adder
0.456
231940T-011
Adder
0.376
972069AH1-584 GEN
Solar/Wind Harmer
4.507
972071AH1-585 GEN
Solar/Wind Harmer
4.507
971747AH1-380 GEN
Solar/Wind Harmer
1.802
233901CHERRYDALE C
Solar/Wind Harmer
0.566
219229EAGLE PT ST
50/50
0.833
219231EAGLE PT CT2
50/50
1.646
230405GT2-CC
50/50
3.623
219914AD2-027 C
Solar/Wind Harmer
1.083
219137THOSOLAR C
Solar/Wind Harmer
1.822
971011AG2-627 GEN
Solar/Wind Harmer
9.025
228309CCLP NUG
Adder
29.241
228309CCLP NUG
Adder
27.815
964001AG1-254 GEN
Solar/Wind Harmer
2.296
972141AH1-641 GEN
Solar/Wind Harmer
3.126
219272CLEANLIGHT C
Solar/Wind Harmer
0.199
971535AH1-265 GEN
Solar/Wind Harmer
4.38
228260V4-054C
Solar/Wind Harmer
1.047
232408W1-005 C
Solar/Wind Harmer
0.504
232410W1-006 C
Solar/Wind Harmer
0.504
232918OH NUG7
Adder
4.413
232905CHERITON_25
Adder
1.234
232926CRISFLD1
Adder
0.986
233946AB2-136 GEN
Solar/Wind Harmer
1.989
231131BLOOM ENRGY
Adder
2.171
234036AF2-325 C
Solar/Wind Harmer
0.457
234041AC1-190 GEN
Solar/Wind Harmer
4.452
233987AB2-037 GEN
Solar/Wind Harmer
5.632
213535CROYDN11
Adder
4.757
219114HARTZY_C
Solar/Wind Harmer
0.391
233984AB2-036 GEN
Solar/Wind Harmer
6.018
232424Y1-079 C
Solar/Wind Harmer
0.272
234014AF1-036_GEN
Solar/Wind Harmer
1.293
233944AB2-135 GEN
Solar/Wind Harmer
2.497
233933AB2-153 GEN
Solar/Wind Harmer
0.531
20720628TIN_W1-124
Solar/Wind Harmer
0.342
20641628MLH_W1-032
Solar/Wind Harmer
0.084
20716928W4-060COL
Solar/Wind Harmer
0.195
219230EAGLE PT CT1
50/50
1.647
219235Y2-105
50/50
0.595
219904AC1-010 C
Solar/Wind Harmer
0.647
219258KINSLEYDEP C
Solar/Wind Harmer
0.526
219907AC1-030 C
Solar/Wind Harmer
0.201
230434AG1-499 GEN
Solar/Wind Harmer
0.671
228351V2-046C
Solar/Wind Harmer
2.274
970997AG2-616 GEN
Solar/Wind Harmer
10.42
230511AF1-262
Solar/Wind Harmer
0.196
945431AF1-208 GEN
Solar/Wind Harmer
9.097
228728W1-130C
Solar/Wind Harmer
0.679
218660EHAMPSOLAR C
Solar/Wind Harmer
0.17
219686LUMSOLAR_N C
Solar/Wind Harmer
0.196
219287REEVESEAST C
Solar/Wind Harmer
1.303
228206SHRMN CT
Adder
15.434
228732V1-021 C
Adder
0.168
219304NAMERICA C
Solar/Wind Harmer
0.231
219222BRL12CT2
Adder
6.624
20720728JCB_W1-129
Solar/Wind Harmer
0.186
207522AF2-254 C
Solar/Wind Harmer
0.885
231917EM10
Adder
1.422
231918WEST 1
Adder
1.902
207487AE2-000G4
Solar/Wind Harmer
16.555
233972AC1-094 C
Solar/Wind Harmer
0.344
232901NORTHST
Adder
4.286
232900DEMECSMY
Adder
4.728
972177AH1-672 GEN
Solar/Wind Harmer
6.807
232434Z2-077 GEN
Solar/Wind Harmer
0.126
207445AB1-138_GEN
Solar/Wind Harmer
0.278
20628028LAKEHURS
Adder
0.902
233954AC2-188 GEN
Solar/Wind Harmer
0.567
233950AC2-186 GEN
Solar/Wind Harmer
0.283
232404W1-003 C
Solar/Wind Harmer
0.504
232917OH NUG6
Adder
4.423
232915OH NUG4
Adder
4.413
971195AH1-057 GEN
Solar/Wind Harmer
0.55
233998TM1NIN_3.36
Solar/Wind Harmer
0.637
232428Y3-058 C
Solar/Wind Harmer
0.419
232919VN10
Adder
1.403
965821AG1-450 GEN
Solar/Wind Harmer
2.599
232426Y1-080 FULL
Solar/Wind Harmer
0.095
970277AG2-181 GEN
Solar/Wind Harmer
2.502
233964AF2-378 GEN
Solar/Wind Harmer
0.064
232910NRG_G1
Adder
4.287
234012AE2-112_GEN
Solar/Wind Harmer
1.099
232422X3-066 FULL
Solar/Wind Harmer
0.119
233930AB2-032 GEN
Solar/Wind Harmer
0.394
233915AB1-141 GEN
Solar/Wind Harmer
0.468
963711AG1-223 GEN
Solar/Wind Harmer
0.619
20714828MDF_W3-079
Solar/Wind Harmer
0.128
207454AA2-184 E
Solar/Wind Harmer
0.343
20715228NPK_W1-113
Solar/Wind Harmer
0.12
20742028HF_AC1-207
Solar/Wind Harmer
0.219
217197RE CRAN C
Solar/Wind Harmer
0.135
20635828PARLN1&2
Adder
1.804
219688LUMSOLAR_S C
Solar/Wind Harmer
0.193
970453AG2-297 GEN
Solar/Wind Harmer
2.469
228754AB1-001 C
Solar/Wind Harmer
0.121
227927V4-067C
Solar/Wind Harmer
0.17
219607WPEMNERT C
Solar/Wind Harmer
0.311
219224BRL12CT4
Adder
6.624
20717128DIX_Z2-102
Solar/Wind Harmer
0.804
20715728PEM_W1-119
Solar/Wind Harmer
0.321
20715828PEM_W1-120
Solar/Wind Harmer
0.321
231919CHRIST1
Adder
2.554
231920CHRIST2
Adder
2.497
971189AH1-054 GEN
Solar/Wind Harmer
0.624
970025AG2-016 GEN
Solar/Wind Harmer
1.448
233973AC2-185 C
Solar/Wind Harmer
1.872
207459AE1-142 C O1
Solar/Wind Harmer
0.51
234033AF1-007_GEN
Solar/Wind Harmer
11.824
232904IR4
Adder
40.885
232920IR10
Adder
1.597
232432Z2-076 GEN
Solar/Wind Harmer
0.067
233990AG1-397 GEN
Solar/Wind Harmer
0.028
232912OH NUG1
Adder
4.443
232913OH NUG2
Adder
4.384
233923SMA
Solar/Wind Harmer
2.334
232813VAUGHN
Adder
0.294
233955AB2-172 GEN
Solar/Wind Harmer
2.485
231906DC3 NUG
Adder
6.905
231902DC CT7
Adder
5.521
231907DC10
Adder
1.724
233968AD2-076_GEN
Solar/Wind Harmer
3.168
970597AG2-380 GEN
Solar/Wind Harmer
1.989
232436AB1-176 C
Solar/Wind Harmer
0.109
971983AH1-536 GEN
Solar/Wind Harmer
3.533
233935AB2-179 C
Solar/Wind Harmer
1.103
20714328BYD_X4-031
Solar/Wind Harmer
0.101
20714428HOW_X1-037
Solar/Wind Harmer
0.426
971521AH1-258 GEN
Solar/Wind Harmer
0.846
20720428HOL_W1-112
Solar/Wind Harmer
0.105
20635928PARLN3&4
Adder
1.804
219124CAMDEN_STG
50/50
1.356
219286CAMD CO RR
50/50
0.468
230406ST-CC
50/50
5.361
230404GT1-CC
50/50
3.606
228304LOGAN
50/50
29.565
219912AD2-042 GEN
Solar/Wind Harmer
1.435
219766PARADISE C
Solar/Wind Harmer
0.539
219623KINSLEYBEA C
Solar/Wind Harmer
0.685
219236SOUTHERNHQ C
Solar/Wind Harmer
0.097
230430AE1-229_GEN
Solar/Wind Harmer
9.527
230415AB2-049 C
Solar/Wind Harmer
0.198
219906AC1-017 C
Solar/Wind Harmer
0.231
219291REEVESSOUT C
Solar/Wind Harmer
0.058
971553AH1-274 GEN
Solar/Wind Harmer
2.336
228711V2-041C
Solar/Wind Harmer
0.553
228202CUMB CT
Adder
15.028
228729W2-030 C
Solar/Wind Harmer
0.501
219610FLORENCE C
Solar/Wind Harmer
1.028
219348LDSOLAR C
Solar/Wind Harmer
0.444
219221BRL12CT1
Adder
6.624
219223BRL12CT3
Adder
6.624
20716028EGP_W2-019
Solar/Wind Harmer
0.291
20720828JCB_W4-025
Solar/Wind Harmer
0.283
20715028HAN_X4-015
Solar/Wind Harmer
0.186
959561AF2-247 GEN
Solar/Wind Harmer
0.29
972251AH1-710 GEN
Adder
27.657
20636028O CRK C1
Adder
3.715
233971AC1-093 C
Solar/Wind Harmer
0.406
970695AG2-447 GEN
Solar/Wind Harmer
1.856
971667AH1-334 GEN
Solar/Wind Harmer
1.345
972133AH1-634 GEN
Solar/Wind Harmer
5.014
233952AC2-187 GEN
Solar/Wind Harmer
0.567
972073AH1-586 GEN
Solar/Wind Harmer
4.717
233990AG1-397 GEN
Solar/Wind Harmer
0.577
232406W1-004 FULL
Solar/Wind Harmer
0.504
232914OH NUG3
Adder
4.443
232916OH NUG5
Adder
4.443
232921TASLEY2G
Adder
2.597
234015AF2-250 C
Solar/Wind Harmer
0.061
233996TM1833_GEN
Solar/Wind Harmer
0.637
233997TMININ_4.2
Solar/Wind Harmer
0.637
233900O-025 C
Adder
0.592
233940AF2-379 C
Solar/Wind Harmer
0.094
233994AC2-023 GEN
Solar/Wind Harmer
1.349
232907VN8
Adder
15.014
960671AF2-358 GEN
Solar/Wind Harmer
8.941
232417X3-008 C
Solar/Wind Harmer
0.994
233982AB2-133 GEN
Solar/Wind Harmer
2.3
233918AB1-142 GEN
Solar/Wind Harmer
0.468
219727YARDVSOLFA C
Solar/Wind Harmer
0.392
20714528FRN_Y2-051
Solar/Wind Harmer
0.122
219276PARKLANDSO C
Solar/Wind Harmer
0.16
20720528MAN_W1-024
Solar/Wind Harmer
0.073
20716228APLW2-078
Solar/Wind Harmer
0.247
219612MATRIX C
Solar/Wind Harmer
0.046
218438BLK ROCK C
Solar/Wind Harmer
0.034
20635828PARLN1&2
Adder
0.817
20635928PARLN3&4
Adder
0.817
967451AG2-055 C O1
Solar/Wind Harmer
40.285
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.502
G-007ALTFEXP_G-007A->PJM
CMTX
11.581
CBM NorthLTFEXP_CBM-N->PJM
CBM
4.514
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.496
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.545
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
17.923
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.306
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
2.299

Details for RICHRE29-RICHMOND29 230.0 kV Ckt 1 line l/o PECO_P2-2_CHI230B1_SRT-A/* $ DELCO $ PECO_P2-2_CHI230B1 $ B


Base Case Flowgate

Area:PECO
Facility Description:
RICHRE29-RICHMOND29 230.0 kV Ckt 1 line
Contingency Name:
PECO_P2-2_CHI230B1_SRT-A/* $ DELCO $ PECO_P2-2_CHI230B1 $ B
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:108.46 %
Rating:1336.0 MVA
Rating Type:B
MVA to Mitigate:1449.01
MW Contribution:9.03
Bus #Bus NameTypeMW Contribution
219229EAGLE PT ST
50/50
0.833
219231EAGLE PT CT2
50/50
1.646
230405GT2-CC
50/50
3.623
219914AD2-027 C
Solar/Wind Harmer
1.083
219137THOSOLAR C
Solar/Wind Harmer
1.822
971011AG2-627 GEN
Solar/Wind Harmer
9.025
228309CCLP NUG
Adder
29.24
228309CCLP NUG
Adder
27.814
964001AG1-254 GEN
Solar/Wind Harmer
2.296
972141AH1-641 GEN
Solar/Wind Harmer
3.126
219272CLEANLIGHT C
Solar/Wind Harmer
0.199
971535AH1-265 GEN
Solar/Wind Harmer
4.38
228260V4-054C
Solar/Wind Harmer
1.047
219688LUMSOLAR_S C
Solar/Wind Harmer
0.193
970453AG2-297 GEN
Solar/Wind Harmer
2.469
228754AB1-001 C
Solar/Wind Harmer
0.121
227927V4-067C
Solar/Wind Harmer
0.17
219607WPEMNERT C
Solar/Wind Harmer
0.311
219224BRL12CT4
Adder
6.624
20717128DIX_Z2-102
Solar/Wind Harmer
0.804
20715728PEM_W1-119
Solar/Wind Harmer
0.321
20715828PEM_W1-120
Solar/Wind Harmer
0.321
231919CHRIST1
Adder
2.554
231920CHRIST2
Adder
2.497
971189AH1-054 GEN
Solar/Wind Harmer
0.624
970025AG2-016 GEN
Solar/Wind Harmer
1.448
233973AC2-185 C
Solar/Wind Harmer
1.872
207459AE1-142 C O1
Solar/Wind Harmer
0.51
234033AF1-007_GEN
Solar/Wind Harmer
11.825
232904IR4
Adder
40.889
232920IR10
Adder
1.597
232432Z2-076 GEN
Solar/Wind Harmer
0.067
233990AG1-397 GEN
Solar/Wind Harmer
0.028
232912OH NUG1
Adder
4.443
232913OH NUG2
Adder
4.384
233923SMA
Solar/Wind Harmer
2.334
232813VAUGHN
Adder
0.294
233955AB2-172 GEN
Solar/Wind Harmer
2.486
231906DC3 NUG
Adder
6.906
231902DC CT7
Adder
5.521
231907DC10
Adder
1.724
233968AD2-076_GEN
Solar/Wind Harmer
3.168
970597AG2-380 GEN
Solar/Wind Harmer
1.99
232436AB1-176 C
Solar/Wind Harmer
0.109
971983AH1-536 GEN
Solar/Wind Harmer
3.534
233935AB2-179 C
Solar/Wind Harmer
1.103
20714328BYD_X4-031
Solar/Wind Harmer
0.101
219124CAMDEN_STG
50/50
1.356
219286CAMD CO RR
50/50
0.468
230406ST-CC
50/50
5.361
230404GT1-CC
50/50
3.606
228304LOGAN
50/50
29.564
219912AD2-042 GEN
Solar/Wind Harmer
1.435
219766PARADISE C
Solar/Wind Harmer
0.539
219623KINSLEYBEA C
Solar/Wind Harmer
0.685
219236SOUTHERNHQ C
Solar/Wind Harmer
0.097
230430AE1-229_GEN
Solar/Wind Harmer
9.527
230415AB2-049 C
Solar/Wind Harmer
0.198
219906AC1-017 C
Solar/Wind Harmer
0.231
219291REEVESSOUT C
Solar/Wind Harmer
0.058
971553AH1-274 GEN
Solar/Wind Harmer
2.336
228711V2-041C
Solar/Wind Harmer
0.553
228202CUMB CT
Adder
15.027
228729W2-030 C
Solar/Wind Harmer
0.501
219610FLORENCE C
Solar/Wind Harmer
1.028
219348LDSOLAR C
Solar/Wind Harmer
0.444
219221BRL12CT1
Adder
6.624
219223BRL12CT3
Adder
6.624
20716028EGP_W2-019
Solar/Wind Harmer
0.291
20720828JCB_W4-025
Solar/Wind Harmer
0.283
20715028HAN_X4-015
Solar/Wind Harmer
0.186
959561AF2-247 GEN
Solar/Wind Harmer
0.29
972251AH1-710 GEN
Adder
27.658
20636028O CRK C1
Adder
3.715
233971AC1-093 C
Solar/Wind Harmer
0.406
970695AG2-447 GEN
Solar/Wind Harmer
1.856
971667AH1-334 GEN
Solar/Wind Harmer
1.345
972133AH1-634 GEN
Solar/Wind Harmer
5.014
233952AC2-187 GEN
Solar/Wind Harmer
0.567
972073AH1-586 GEN
Solar/Wind Harmer
4.718
233990AG1-397 GEN
Solar/Wind Harmer
0.577
232914OH NUG3
Adder
4.443
232916OH NUG5
Adder
4.443
232921TASLEY2G
Adder
2.597
232406W1-004 FULL
Solar/Wind Harmer
0.504
234015AF2-250 C
Solar/Wind Harmer
0.061
233996TM1833_GEN
Solar/Wind Harmer
0.637
233997TMININ_4.2
Solar/Wind Harmer
0.637
233900O-025 C
Adder
0.592
233940AF2-379 C
Solar/Wind Harmer
0.094
233994AC2-023 GEN
Solar/Wind Harmer
1.349
232907VN8
Adder
15.015
960671AF2-358 GEN
Solar/Wind Harmer
8.942
232417X3-008 C
Solar/Wind Harmer
0.994
20714428HOW_X1-037
Solar/Wind Harmer
0.426
971521AH1-258 GEN
Solar/Wind Harmer
0.846
20720428HOL_W1-112
Solar/Wind Harmer
0.105
20635928PARLN3&4
Adder
1.804
233982AB2-133 GEN
Solar/Wind Harmer
2.3
233918AB1-142 GEN
Solar/Wind Harmer
0.468
219727YARDVSOLFA C
Solar/Wind Harmer
0.392
20714528FRN_Y2-051
Solar/Wind Harmer
0.122
219276PARKLANDSO C
Solar/Wind Harmer
0.16
20720528MAN_W1-024
Solar/Wind Harmer
0.073
20716228APLW2-078
Solar/Wind Harmer
0.247
219612MATRIX C
Solar/Wind Harmer
0.046
218438BLK ROCK C
Solar/Wind Harmer
0.034
20635828PARLN1&2
Adder
0.817
20635928PARLN3&4
Adder
0.817
967451AG2-055 C O1
Solar/Wind Harmer
40.283
219230EAGLE PT CT1
50/50
1.647
219235Y2-105
50/50
0.595
219904AC1-010 C
Solar/Wind Harmer
0.647
219258KINSLEYDEP C
Solar/Wind Harmer
0.526
219907AC1-030 C
Solar/Wind Harmer
0.201
230434AG1-499 GEN
Solar/Wind Harmer
0.671
228351V2-046C
Solar/Wind Harmer
2.274
970997AG2-616 GEN
Solar/Wind Harmer
10.419
230511AF1-262
Solar/Wind Harmer
0.196
945431AF1-208 GEN
Solar/Wind Harmer
9.097
228728W1-130C
Solar/Wind Harmer
0.679
218660EHAMPSOLAR C
Solar/Wind Harmer
0.17
219686LUMSOLAR_N C
Solar/Wind Harmer
0.196
219287REEVESEAST C
Solar/Wind Harmer
1.303
228206SHRMN CT
Adder
15.434
228732V1-021 C
Adder
0.168
219304NAMERICA C
Solar/Wind Harmer
0.231
219222BRL12CT2
Adder
6.624
20720728JCB_W1-129
Solar/Wind Harmer
0.186
207522AF2-254 C
Solar/Wind Harmer
0.885
231917EM10
Adder
1.422
231918WEST 1
Adder
1.902
207487AE2-000G4
Solar/Wind Harmer
16.555
233972AC1-094 C
Solar/Wind Harmer
0.344
232901NORTHST
Adder
4.287
232900DEMECSMY
Adder
4.729
972177AH1-672 GEN
Solar/Wind Harmer
6.808
232434Z2-077 GEN
Solar/Wind Harmer
0.126
207445AB1-138_GEN
Solar/Wind Harmer
0.278
20628028LAKEHURS
Adder
0.902
233954AC2-188 GEN
Solar/Wind Harmer
0.567
233950AC2-186 GEN
Solar/Wind Harmer
0.283
232917OH NUG6
Adder
4.424
232915OH NUG4
Adder
4.414
232404W1-003 C
Solar/Wind Harmer
0.504
971195AH1-057 GEN
Solar/Wind Harmer
0.55
233998TM1NIN_3.36
Solar/Wind Harmer
0.637
232428Y3-058 C
Solar/Wind Harmer
0.419
232919VN10
Adder
1.403
965821AG1-450 GEN
Solar/Wind Harmer
2.599
232426Y1-080 FULL
Solar/Wind Harmer
0.095
970277AG2-181 GEN
Solar/Wind Harmer
2.502
233964AF2-378 GEN
Solar/Wind Harmer
0.064
232910NRG_G1
Adder
4.287
234012AE2-112_GEN
Solar/Wind Harmer
1.099
232422X3-066 FULL
Solar/Wind Harmer
0.119
233930AB2-032 GEN
Solar/Wind Harmer
0.394
233915AB1-141 GEN
Solar/Wind Harmer
0.468
963711AG1-223 GEN
Solar/Wind Harmer
0.619
20714828MDF_W3-079
Solar/Wind Harmer
0.128
207454AA2-184 E
Solar/Wind Harmer
0.343
20715228NPK_W1-113
Solar/Wind Harmer
0.12
20742028HF_AC1-207
Solar/Wind Harmer
0.219
217197RE CRAN C
Solar/Wind Harmer
0.135
20635828PARLN1&2
Adder
1.804
219126CAMDEN_CTG
50/50
1.666
219267WHEELBRDEPTF
50/50
0.234
219240MANTUACREK E
50/50
0.761
219726BAT.STORG E
50/50
0.369
972233AH1-701 GEN
50/50
5.793
228304LOGAN
50/50
32.871
228307PCLP GT
50/50
15.939
213400COVANTA DELA
50/50
1.115
219921AF1-264
Solar/Wind Harmer
0.237
219615MILLCREEK C
Solar/Wind Harmer
0.247
228251CARLLS#4
Adder
0.644
230407AD2-065 C
Solar/Wind Harmer
0.134
230433AD2-135 GEN
Solar/Wind Harmer
0.102
230422AE1-104_GEN1
Solar/Wind Harmer
29.724
230425AE1-104_GEN2
Solar/Wind Harmer
29.724
20716428NHV_W2-082
Solar/Wind Harmer
1.103
207500AE2-000G1
Solar/Wind Harmer
16.555
207497AE2-000G2
Solar/Wind Harmer
16.555
207507AE2-000G3
Solar/Wind Harmer
16.555
20636128O CRK C2
Adder
3.387
963401AG1-189 GEN
Solar/Wind Harmer
0.593
20714928UPF_X1-085
Solar/Wind Harmer
0.208
963391AG1-188 GEN
Solar/Wind Harmer
0.978
232416X2-083
Adder
0.236
233939AC1-091 C
Solar/Wind Harmer
0.455
233970AC1-092 C
Solar/Wind Harmer
0.455
971149AH1-027 GEN
Solar/Wind Harmer
1.743
232899W1-062
Adder
4.93
970545AG2-347 GEN
Solar/Wind Harmer
33.092
20628028LAKEHURS
Adder
0.456
231940T-011
Adder
0.376
972069AH1-584 GEN
Solar/Wind Harmer
4.508
972071AH1-585 GEN
Solar/Wind Harmer
4.508
971747AH1-380 GEN
Solar/Wind Harmer
1.803
233901CHERRYDALE C
Solar/Wind Harmer
0.566
232918OH NUG7
Adder
4.414
232905CHERITON_25
Adder
1.234
232408W1-005 C
Solar/Wind Harmer
0.504
232410W1-006 C
Solar/Wind Harmer
0.504
232926CRISFLD1
Adder
0.987
233946AB2-136 GEN
Solar/Wind Harmer
1.989
231131BLOOM ENRGY
Adder
2.171
234036AF2-325 C
Solar/Wind Harmer
0.457
234041AC1-190 GEN
Solar/Wind Harmer
4.453
233987AB2-037 GEN
Solar/Wind Harmer
5.633
213535CROYDN11
Adder
4.756
219114HARTZY_C
Solar/Wind Harmer
0.391
233984AB2-036 GEN
Solar/Wind Harmer
6.019
232424Y1-079 C
Solar/Wind Harmer
0.272
234014AF1-036_GEN
Solar/Wind Harmer
1.293
233944AB2-135 GEN
Solar/Wind Harmer
2.497
233933AB2-153 GEN
Solar/Wind Harmer
0.531
20720628TIN_W1-124
Solar/Wind Harmer
0.342
20641628MLH_W1-032
Solar/Wind Harmer
0.084
20716928W4-060COL
Solar/Wind Harmer
0.195
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.502
G-007ALTFEXP_G-007A->PJM
CMTX
11.581
CBM NorthLTFEXP_CBM-N->PJM
CBM
4.513
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.496
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.545
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
17.921
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.306
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
2.299

Details for ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line l/o PJM500_PS_P2-3_NFRD5_9-10_SRT-A


Base Case Flowgate

Area:PJM
Facility Description:
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line
Contingency Name:
PJM500_PS_P2-3_NFRD5_9-10_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.85 %
Rating:2905.0 MVA
Rating Type:B
MVA to Mitigate:3075.06
MW Contribution:11.04
Bus #Bus NameTypeMW Contribution
200203Y1-065-STG
50/50
20.648
200055ROCKSP 4
50/50
7.436
231914HR8
50/50
5.524
231911HR5
50/50
3.635
234034AF2-060
50/50
4.638
232914OH NUG3
50/50
23.192
232916OH NUG5
50/50
23.192
232921TASLEY2G
50/50
13.554
233900O-025 C
50/50
3.091
232907VN8
50/50
78.692
232911NRG_G2
50/50
1.223
200037SALEM-G2
50/50
30.445
972251AH1-710 GEN
50/50
114.358
233971AC1-093 C
Solar/Wind Harmer
1.961
970695AG2-447 GEN
Solar/Wind Harmer
8.954
972133AH1-634 GEN
Solar/Wind Harmer
24.58
972073AH1-586 GEN
Solar/Wind Harmer
23.196
232406W1-004 FULL
Solar/Wind Harmer
2.478
233990AG1-397 GEN
Solar/Wind Harmer
2.839
233996TM1833_GEN
Solar/Wind Harmer
3.134
233997TMININ_4.2
Solar/Wind Harmer
3.134
233940AF2-379 C
Solar/Wind Harmer
0.462
234015AF2-250 C
Solar/Wind Harmer
0.298
233994AC2-023 GEN
Solar/Wind Harmer
6.644
233952AC2-187 GEN
Solar/Wind Harmer
2.778
960671AF2-358 GEN
Solar/Wind Harmer
44.159
200052ROCKSP 1
50/50
7.52
200053ROCKSP 2
50/50
7.36
232616GEN FOOD
50/50
0.432
232904IR4
50/50
212.696
232920IR10
50/50
8.311
232912OH NUG1
50/50
23.192
232913OH NUG2
50/50
22.883
232813VAUGHN
50/50
1.531
200039HOPE CG1
50/50
32.771
233973AC2-185 C
Solar/Wind Harmer
9.031
234033AF1-007_GEN
Solar/Wind Harmer
57.971
232432Z2-076 GEN
Solar/Wind Harmer
0.327
233990AG1-397 GEN
Solar/Wind Harmer
0.137
233923SMA
Solar/Wind Harmer
11.489
233955AB2-172 GEN
Solar/Wind Harmer
12.298
233968AD2-076_GEN
Solar/Wind Harmer
15.869
970597AG2-380 GEN
Solar/Wind Harmer
9.965
232436AB1-176 C
Solar/Wind Harmer
0.547
231906DC3 NUG
Adder
33.185
231902DC CT7
Adder
26.529
231907DC10
Adder
8.285
971983AH1-536 GEN
Solar/Wind Harmer
17.744
233935AB2-179 C
Solar/Wind Harmer
5.636
231919CHRIST1
Adder
8.958
231920CHRIST2
Adder
8.759
970453AG2-297 GEN
Solar/Wind Harmer
4.492
228260V4-054C
Solar/Wind Harmer
1.579
972141AH1-641 GEN
Solar/Wind Harmer
4.314
228309CCLP NUG
Adder
38.646
228309CCLP NUG
Adder
36.761
964001AG1-254 GEN
Solar/Wind Harmer
3.009
227927V4-067C
Solar/Wind Harmer
0.292
971535AH1-265 GEN
Solar/Wind Harmer
6.257
228754AB1-001 C
Solar/Wind Harmer
0.204
971011AG2-627 GEN
Solar/Wind Harmer
11.041
219137THOSOLAR C
Solar/Wind Harmer
1.488
219272CLEANLIGHT C
Solar/Wind Harmer
0.222
219688LUMSOLAR_S C
Solar/Wind Harmer
0.24
219914AD2-027 C
Solar/Wind Harmer
0.659
219607WPEMNERT C
Solar/Wind Harmer
0.411
219224BRL12CT4
Adder
8.758
213942SCHUYLKILL
Adder
3.268
213942SCHUYLKILL
Adder
2.499
213957STHWK3-4
Adder
2.497
213957STHWK3-4
Adder
2.497
20717128DIX_Z2-102
Solar/Wind Harmer
1.196
20715728PEM_W1-119
Solar/Wind Harmer
0.482
20715828PEM_W1-120
Solar/Wind Harmer
0.482
213561DLWR9-10
Adder
3.122
213561DLWR9-10
Adder
2.387
970025AG2-016 GEN
Solar/Wind Harmer
2.476
971189AH1-054 GEN
Solar/Wind Harmer
1.012
214067T20SOLAR
Solar/Wind Harmer
0.215
213611FALLS1-3
Adder
3.008
213611FALLS1-3
Adder
3.008
207459AE1-142 C O1
Solar/Wind Harmer
0.881
20714328BYD_X4-031
Solar/Wind Harmer
0.192
20714428HOW_X1-037
Solar/Wind Harmer
0.815
971521AH1-258 GEN
Solar/Wind Harmer
1.715
20720428HOL_W1-112
Solar/Wind Harmer
0.216
219620RIDERU C
Solar/Wind Harmer
0.033
20635928PARLN3&4
Adder
4.224
218455CINNBAY_CGEN
Adder
0.965
218526CNTRALGAS2 C
Solar/Wind Harmer
0.19
218524CNTRALGAS1 C
Solar/Wind Harmer
0.184
20675528CPH_W2-050
Solar/Wind Harmer
0.228
232417X3-008 C
Solar/Wind Harmer
4.919
233918AB1-142 GEN
Solar/Wind Harmer
2.349
233982AB2-133 GEN
Solar/Wind Harmer
11.535
228202CUMB CT
Adder
26.517
228711V2-041C
Solar/Wind Harmer
0.959
971553AH1-274 GEN
Solar/Wind Harmer
3.796
230430AE1-229_GEN
Solar/Wind Harmer
13.155
230415AB2-049 C
Solar/Wind Harmer
0.28
228729W2-030 C
Solar/Wind Harmer
0.854
228304LOGAN
Adder
29.951
219291REEVESSOUT C
Solar/Wind Harmer
0.074
219623KINSLEYBEA C
Solar/Wind Harmer
0.514
219766PARADISE C
Solar/Wind Harmer
0.359
219912AD2-042 GEN
Solar/Wind Harmer
0.874
219236SOUTHERNHQ C
Solar/Wind Harmer
0.071
213497CHSTR7-9
Adder
2.873
219906AC1-017 C
Solar/Wind Harmer
0.226
219610FLORENCE C
Solar/Wind Harmer
1.359
219348LDSOLAR C
Solar/Wind Harmer
0.588
219221BRL12CT1
Adder
8.758
219223BRL12CT3
Adder
8.758
213958STHWK5-6
Adder
2.497
20716028EGP_W2-019
Solar/Wind Harmer
0.425
20720828JCB_W4-025
Solar/Wind Harmer
0.415
20715028HAN_X4-015
Solar/Wind Harmer
0.273
20636028O CRK C1
Adder
6.431
213560DLW11-12
Adder
2.387
959561AF2-247 GEN
Solar/Wind Harmer
0.424
971667AH1-334 GEN
Solar/Wind Harmer
2.275
219727YARDVSOLFA C
Solar/Wind Harmer
0.686
20714528FRN_Y2-051
Solar/Wind Harmer
0.218
219276PARKLANDSO C
Solar/Wind Harmer
0.319
219918AC2-009 C
Solar/Wind Harmer
0.036
20720528MAN_W1-024
Solar/Wind Harmer
0.149
20716228APLW2-078
Solar/Wind Harmer
0.515
219612MATRIX C
Solar/Wind Harmer
0.108
218438BLK ROCK C
Solar/Wind Harmer
0.08
20635828PARLN1&2
Adder
1.913
20635928PARLN3&4
Adder
1.913
20635028RRCT1&2
Adder
6.535
20635128RRCT3&4
Adder
5.418
967451AG2-055 C O1
Solar/Wind Harmer
88.317
219908AB1-139 C
Solar/Wind Harmer
0.189
219919AE1-041 FULL
Solar/Wind Harmer
0.02
213815MOSER1-3
Adder
1.68
219249CENTRALDIV C
Solar/Wind Harmer
0.019
200205Y1-065-CTG2
50/50
11.907
232899W1-062
50/50
25.374
231940T-011
50/50
1.959
232918OH NUG7
50/50
23.037
232905CHERITON_25
50/50
6.442
232926CRISFLD1
50/50
5.152
233939AC1-091 C
Solar/Wind Harmer
2.195
233970AC1-092 C
Solar/Wind Harmer
2.195
971149AH1-027 GEN
Solar/Wind Harmer
8.45
970545AG2-347 GEN
Solar/Wind Harmer
162.225
972069AH1-584 GEN
Solar/Wind Harmer
22.165
972071AH1-585 GEN
Solar/Wind Harmer
22.165
971747AH1-380 GEN
Solar/Wind Harmer
8.865
233901CHERRYDALE C
Solar/Wind Harmer
2.786
232408W1-005 C
Solar/Wind Harmer
2.478
232410W1-006 C
Solar/Wind Harmer
2.478
233987AB2-037 GEN
Solar/Wind Harmer
28.082
233946AB2-136 GEN
Solar/Wind Harmer
9.831
234036AF2-325 C
Solar/Wind Harmer
2.257
234041AC1-190 GEN
Solar/Wind Harmer
22.028
233984AB2-036 GEN
Solar/Wind Harmer
30.082
232424Y1-079 C
Solar/Wind Harmer
1.357
234014AF1-036_GEN
Solar/Wind Harmer
6.477
233944AB2-135 GEN
Solar/Wind Harmer
12.473
233933AB2-153 GEN
Solar/Wind Harmer
2.667
231131BLOOM ENRGY
Adder
10.301
232416X2-083
Adder
0.991
228251CARLLS#4
Adder
0.97
230422AE1-104_GEN1
Solar/Wind Harmer
51.307
230425AE1-104_GEN2
Solar/Wind Harmer
51.307
230433AD2-135 GEN
Solar/Wind Harmer
0.153
230407AD2-065 C
Solar/Wind Harmer
0.191
228307PCLP GT
Adder
17.009
228304LOGAN
Adder
33.302
972233AH1-701 GEN
Adder
5.663
219921AF1-264
Solar/Wind Harmer
0.169
213589EDDYSTN4
Adder
82.748
213587EDDYSTN3
Adder
82.635
219615MILLCREEK C
Solar/Wind Harmer
0.242
213535CROYDN11
Adder
9.812
20716428NHV_W2-082
Solar/Wind Harmer
1.624
207500AE2-000G1
Solar/Wind Harmer
28.661
207497AE2-000G2
Solar/Wind Harmer
28.661
207507AE2-000G3
Solar/Wind Harmer
28.661
20636128O CRK C2
Adder
5.864
963401AG1-189 GEN
Solar/Wind Harmer
1.019
963391AG1-188 GEN
Solar/Wind Harmer
1.671
20628028LAKEHURS
Adder
0.774
20714928UPF_X1-085
Solar/Wind Harmer
0.328
219114HARTZY_C
Solar/Wind Harmer
0.651
20720628TIN_W1-124
Solar/Wind Harmer
0.66
219817TRENTONSOL C
Solar/Wind Harmer
0.652
20716928W4-060COL
Solar/Wind Harmer
0.424
20641628MLH_W1-032
Solar/Wind Harmer
0.17
924131AB2-057 GEN
Solar/Wind Harmer
0.546
218440SUMMTASSOC C
Solar/Wind Harmer
0.064
213815MOSER1-3
Adder
1.68
213815MOSER1-3
Adder
1.68
218418LINDEN_G5
Adder
8.353
218419LINDEN_G6
Adder
8.353
972260AH1-715 GEN1
Adder
6.689
20673828FLE_V3-070
Solar/Wind Harmer
0.218
219036LINDEN_G7
Adder
7.93
219035LINDEN_G8
Adder
7.817
972261AH1-715 GEN2
Adder
7.591
200204Y1-065-CTG1
50/50
11.907
200054ROCKSP 3
50/50
7.596
231912HR6
50/50
3.635
231913HR7
50/50
3.635
233920W3-032A-CTG1
50/50
5.491
233921W3-032A-STG1
50/50
3.298
232901NORTHST
50/50
22.047
232900DEMECSMY
50/50
24.338
232917OH NUG6
50/50
23.089
232915OH NUG4
50/50
23.037
232919VN10
50/50
7.348
232910NRG_G1
50/50
22.37
200036SALEM-G1
50/50
30.607
233972AC1-094 C
Solar/Wind Harmer
1.658
972177AH1-672 GEN
Solar/Wind Harmer
33.305
232434Z2-077 GEN
Solar/Wind Harmer
0.62
232404W1-003 C
Solar/Wind Harmer
2.478
233998TM1NIN_3.36
Solar/Wind Harmer
3.134
971195AH1-057 GEN
Solar/Wind Harmer
2.707
232428Y3-058 C
Solar/Wind Harmer
2.063
233954AC2-188 GEN
Solar/Wind Harmer
2.778
233950AC2-186 GEN
Solar/Wind Harmer
1.389
965821AG1-450 GEN
Solar/Wind Harmer
12.837
232426Y1-080 FULL
Solar/Wind Harmer
0.471
970277AG2-181 GEN
Solar/Wind Harmer
12.361
233964AF2-378 GEN
Solar/Wind Harmer
0.315
234012AE2-112_GEN
Solar/Wind Harmer
5.506
232422X3-066 FULL
Solar/Wind Harmer
0.598
233930AB2-032 GEN
Solar/Wind Harmer
1.977
233915AB1-141 GEN
Solar/Wind Harmer
2.349
231918WEST 1
Adder
6.856
231917EM10
Adder
4.603
228206SHRMN CT
Adder
26.353
228732V1-021 C
Adder
0.297
945431AF1-208 GEN
Solar/Wind Harmer
13.135
970997AG2-616 GEN
Solar/Wind Harmer
14.379
230511AF1-262
Solar/Wind Harmer
0.272
228351V2-046C
Solar/Wind Harmer
2.974
228728W1-130C
Solar/Wind Harmer
0.978
230434AG1-499 GEN
Solar/Wind Harmer
0.827
218660EHAMPSOLAR C
Solar/Wind Harmer
0.212
219686LUMSOLAR_N C
Solar/Wind Harmer
0.244
219287REEVESEAST C
Solar/Wind Harmer
1.618
219258KINSLEYDEP C
Solar/Wind Harmer
0.382
219904AC1-010 C
Solar/Wind Harmer
0.432
219907AC1-030 C
Solar/Wind Harmer
0.147
213497CHSTR7-9
Adder
2.873
213497CHSTR7-9
Adder
2.873
219304NAMERICA C
Solar/Wind Harmer
0.305
219222BRL12CT2
Adder
8.758
213958STHWK5-6
Adder
2.497
20720728JCB_W1-129
Solar/Wind Harmer
0.273
207522AF2-254 C
Solar/Wind Harmer
1.307
207487AE2-000G4
Solar/Wind Harmer
28.661
213560DLW11-12
Adder
2.387
213611FALLS1-3
Adder
3.008
207445AB1-138_GEN
Solar/Wind Harmer
0.472
20628028LAKEHURS
Adder
1.531
963711AG1-223 GEN
Solar/Wind Harmer
1.096
20714828MDF_W3-079
Solar/Wind Harmer
0.226
207454AA2-184 E
Solar/Wind Harmer
0.663
219680HOPEWELLV C1
Solar/Wind Harmer
0.045
20715228NPK_W1-113
Solar/Wind Harmer
0.251
20742028HF_AC1-207
Solar/Wind Harmer
0.457
217197RE CRAN C
Solar/Wind Harmer
0.314
20635828PARLN1&2
Adder
4.224
20635028RRCT1&2
Adder
6.434
20635128RRCT3&4
Adder
6.211
214194N WALES4
Adder
0.413
218428ETC SOLAR C
Solar/Wind Harmer
0.018
217213AMBOY SO C
Solar/Wind Harmer
0.063
972275AH1-722 GEN
Adder
15.356
218449LINSOLAR C
Solar/Wind Harmer
0.477
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.061
G-007ALTFEXP_G-007A->PJM
CMTX
28.418
CBM NorthLTFEXP_CBM-N->PJM
CBM
25.657
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
2.755
BlueGrassPJM->LTFIMP_BlueG
CLTF
8.579
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
62.083
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.833
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
12.857

Details for ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line l/o PECO_P4_LINWO125_SRT-A/* $ DELCO $ PECO_P4_LINWO125 $ STBK


Base Case Flowgate

Area:PJM
Facility Description:
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line
Contingency Name:
PECO_P4_LINWO125_SRT-A/* $ DELCO $ PECO_P4_LINWO125 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.75 %
Rating:2905.0 MVA
Rating Type:B
MVA to Mitigate:3072.15
MW Contribution:9.18
Bus #Bus NameTypeMW Contribution
200052ROCKSP 1
50/50
7.46
200053ROCKSP 2
50/50
7.3
231505HR4
50/50
5.496
233955AB2-172 GEN
Solar/Wind Harmer
12.734
233923SMA
Solar/Wind Harmer
11.815
232912OH NUG1
Adder
22.46
232913OH NUG2
Adder
22.161
233990AG1-397 GEN
Solar/Wind Harmer
0.14
231919CHRIST1
Adder
11.219
200203Y1-065-STG
50/50
20.481
200055ROCKSP 4
50/50
7.376
231914HR8
50/50
5.621
231911HR5
50/50
3.699
232907VN8
50/50
81.306
960671AF2-358 GEN
Solar/Wind Harmer
45.614
232417X3-008 C
Solar/Wind Harmer
5.094
233996TM1833_GEN
Solar/Wind Harmer
3.223
233997TMININ_4.2
Solar/Wind Harmer
3.223
233994AC2-023 GEN
Solar/Wind Harmer
6.839
233940AF2-379 C
Solar/Wind Harmer
0.475
232406W1-004 FULL
Solar/Wind Harmer
2.547
232914OH NUG3
Adder
22.46
232916OH NUG5
Adder
22.46
232921TASLEY2G
Adder
13.127
233900O-025 C
Adder
2.994
234015AF2-250 C
Solar/Wind Harmer
0.306
972073AH1-586 GEN
Solar/Wind Harmer
23.825
233990AG1-397 GEN
Solar/Wind Harmer
2.915
972133AH1-634 GEN
Solar/Wind Harmer
25.144
233952AC2-187 GEN
Solar/Wind Harmer
2.838
233971AC1-093 C
Solar/Wind Harmer
1.962
970695AG2-447 GEN
Solar/Wind Harmer
8.96
233918AB1-142 GEN
Solar/Wind Harmer
2.472
233982AB2-133 GEN
Solar/Wind Harmer
12.115
972251AH1-710 GEN
Adder
96.659
228202CUMB CT
Adder
22.742
228711V2-041C
Solar/Wind Harmer
0.821
971553AH1-274 GEN
Solar/Wind Harmer
3.236
228729W2-030 C
Solar/Wind Harmer
0.746
230430AE1-229_GEN
Solar/Wind Harmer
11.064
230415AB2-049 C
Solar/Wind Harmer
0.236
228304LOGAN
Adder
24.587
219291REEVESSOUT C
Solar/Wind Harmer
0.064
219623KINSLEYBEA C
Solar/Wind Harmer
0.428
20636028O CRK C1
Adder
6.782
219766PARADISE C
Solar/Wind Harmer
0.297
20716028EGP_W2-019
Solar/Wind Harmer
0.436
20720828JCB_W4-025
Solar/Wind Harmer
0.426
20715028HAN_X4-015
Solar/Wind Harmer
0.28
219912AD2-042 GEN
Solar/Wind Harmer
0.726
971667AH1-334 GEN
Solar/Wind Harmer
2.499
219236SOUTHERNHQ C
Solar/Wind Harmer
0.061
219906AC1-017 C
Solar/Wind Harmer
0.197
219610FLORENCE C
Solar/Wind Harmer
1.209
219348LDSOLAR C
Solar/Wind Harmer
0.522
219221BRL12CT1
Adder
7.787
219223BRL12CT3
Adder
7.787
20714528FRN_Y2-051
Solar/Wind Harmer
0.255
959561AF2-247 GEN
Solar/Wind Harmer
0.403
20720528MAN_W1-024
Solar/Wind Harmer
0.204
20716228APLW2-078
Solar/Wind Harmer
0.705
219727YARDVSOLFA C
Solar/Wind Harmer
0.713
967451AG2-055 C O1
Solar/Wind Harmer
134.403
219276PARKLANDSO C
Solar/Wind Harmer
0.351
219918AC2-009 C
Solar/Wind Harmer
0.045
20635828PARLN1&2
Adder
2.436
20635928PARLN3&4
Adder
2.436
219612MATRIX C
Solar/Wind Harmer
0.131
218438BLK ROCK C
Solar/Wind Harmer
0.097
20635028RRCT1&2
Adder
8.379
20635128RRCT3&4
Adder
6.947
213560DLW11-12
Adder
1.785
219908AB1-139 C
Solar/Wind Harmer
0.254
219919AE1-041 FULL
Solar/Wind Harmer
0.027
219249CENTRALDIV C
Solar/Wind Harmer
0.025
213958STHWK5-6
Adder
1.659
213497CHSTR7-9
Adder
1.642
217211CAMDEN ST C
Solar/Wind Harmer
0.015
217186ESSEX_G9
Adder
9.683
217169METRODIV C
Solar/Wind Harmer
0.024
217194REDH C
Solar/Wind Harmer
0.297
20673728F2S_V4-070
Solar/Wind Harmer
0.106
20676728BRNX1-095
Solar/Wind Harmer
0.099
20674628WNG_W3-110
Solar/Wind Harmer
0.207
207510AF2-138 C
Solar/Wind Harmer
0.91
231920CHRIST2
Adder
10.97
232432Z2-076 GEN
Solar/Wind Harmer
0.335
232920IR10
Adder
8.016
234033AF1-007_GEN
Solar/Wind Harmer
59.302
232904IR4
Adder
205.046
231906DC3 NUG
Adder
35.476
231902DC CT7
Adder
28.361
231907DC10
Adder
8.856
233968AD2-076_GEN
Solar/Wind Harmer
16.66
970597AG2-380 GEN
Solar/Wind Harmer
10.461
232813VAUGHN
Adder
1.478
232436AB1-176 C
Solar/Wind Harmer
0.574
233973AC2-185 C
Solar/Wind Harmer
9.037
971983AH1-536 GEN
Solar/Wind Harmer
18.675
233935AB2-179 C
Solar/Wind Harmer
6.037
970453AG2-297 GEN
Solar/Wind Harmer
3.855
228260V4-054C
Solar/Wind Harmer
1.337
227927V4-067C
Solar/Wind Harmer
0.256
228754AB1-001 C
Solar/Wind Harmer
0.179
972141AH1-641 GEN
Solar/Wind Harmer
3.625
228309CCLP NUG
Adder
32.285
228309CCLP NUG
Adder
30.71
971535AH1-265 GEN
Solar/Wind Harmer
5.308
964001AG1-254 GEN
Solar/Wind Harmer
2.515
971011AG2-627 GEN
Solar/Wind Harmer
9.181
219272CLEANLIGHT C
Solar/Wind Harmer
0.193
219688LUMSOLAR_S C
Solar/Wind Harmer
0.21
219137THOSOLAR C
Solar/Wind Harmer
1.209
20717128DIX_Z2-102
Solar/Wind Harmer
1.236
970025AG2-016 GEN
Solar/Wind Harmer
2.656
20715728PEM_W1-119
Solar/Wind Harmer
0.5
20715828PEM_W1-120
Solar/Wind Harmer
0.5
971189AH1-054 GEN
Solar/Wind Harmer
1.087
219914AD2-027 C
Solar/Wind Harmer
0.548
207459AE1-142 C O1
Solar/Wind Harmer
0.967
219607WPEMNERT C
Solar/Wind Harmer
0.366
219224BRL12CT4
Adder
7.787
20714328BYD_X4-031
Solar/Wind Harmer
0.233
20714428HOW_X1-037
Solar/Wind Harmer
1.014
214067T20SOLAR
Solar/Wind Harmer
0.2
213611FALLS1-3
Adder
2.791
213611FALLS1-3
Adder
2.791
971521AH1-258 GEN
Solar/Wind Harmer
2.134
20720428HOL_W1-112
Solar/Wind Harmer
0.27
219620RIDERU C
Solar/Wind Harmer
0.042
20635928PARLN3&4
Adder
5.378
218455CINNBAY_CGEN
Adder
1.255
213561DLWR9-10
Adder
2.334
213561DLWR9-10
Adder
1.785
218526CNTRALGAS2 C
Solar/Wind Harmer
0.251
218524CNTRALGAS1 C
Solar/Wind Harmer
0.251
213957STHWK3-4
Adder
1.659
213957STHWK3-4
Adder
1.659
213942SCHUYLKILL
Adder
2.148
213942SCHUYLKILL
Adder
1.643
218404KENILWRTH C
Adder
0.803
20675528CPH_W2-050
Solar/Wind Harmer
0.281
217167KRNY_14
Adder
5.626
217086KRNY_131
Adder
5.579
217147KRNY_1212
Adder
5.352
217147KRNY_1212
Adder
5.256
217146KRNY_1234
Adder
5.244
217146KRNY_1234
Adder
5.208
20676328BVR_Y1-020
Solar/Wind Harmer
0.171
207511W3-106 GEN
Solar/Wind Harmer
0.337
207530AG1-191 GEN
Solar/Wind Harmer
0.694
966261AG1-495 GEN
Solar/Wind Harmer
0.895
200205Y1-065-CTG2
50/50
11.811
231900EM5
50/50
12.878
232416X2-083
50/50
1.222
231908HR1
50/50
3.631
231910HR3
50/50
3.631
231909HR2
50/50
3.625
233987AB2-037 GEN
Solar/Wind Harmer
29.385
233946AB2-136 GEN
Solar/Wind Harmer
10.164
234036AF2-325 C
Solar/Wind Harmer
2.335
234041AC1-190 GEN
Solar/Wind Harmer
22.802
232926CRISFLD1
Adder
4.993
232408W1-005 C
Solar/Wind Harmer
2.547
232410W1-006 C
Solar/Wind Harmer
2.547
233901CHERRYDALE C
Solar/Wind Harmer
2.863
232918OH NUG7
Adder
22.31
232905CHERITON_25
Adder
6.239
971747AH1-380 GEN
Solar/Wind Harmer
9.107
972069AH1-584 GEN
Solar/Wind Harmer
22.766
972071AH1-585 GEN
Solar/Wind Harmer
22.766
231131BLOOM ENRGY
Adder
11.067
231940T-011
Adder
1.893
970545AG2-347 GEN
Solar/Wind Harmer
165.949
233984AB2-036 GEN
Solar/Wind Harmer
31.518
232424Y1-079 C
Solar/Wind Harmer
1.422
971149AH1-027 GEN
Solar/Wind Harmer
8.512
234014AF1-036_GEN
Solar/Wind Harmer
6.8
232899W1-062
Adder
24.104
233939AC1-091 C
Solar/Wind Harmer
2.197
233970AC1-092 C
Solar/Wind Harmer
2.197
233933AB2-153 GEN
Solar/Wind Harmer
2.807
233944AB2-135 GEN
Solar/Wind Harmer
13.043
230422AE1-104_GEN1
Solar/Wind Harmer
44.537
230425AE1-104_GEN2
Solar/Wind Harmer
44.537
228251CARLLS#4
Adder
0.821
230433AD2-135 GEN
Solar/Wind Harmer
0.129
230407AD2-065 C
Solar/Wind Harmer
0.162
228307PCLP GT
Adder
14.03
228304LOGAN
Adder
27.338
972233AH1-701 GEN
Adder
4.636
219921AF1-264
Solar/Wind Harmer
0.141
207500AE2-000G1
Solar/Wind Harmer
30.224
207497AE2-000G2
Solar/Wind Harmer
30.224
207507AE2-000G3
Solar/Wind Harmer
30.224
20636128O CRK C2
Adder
6.183
963401AG1-189 GEN
Solar/Wind Harmer
1.086
20716428NHV_W2-082
Solar/Wind Harmer
1.669
963391AG1-188 GEN
Solar/Wind Harmer
1.794
20628028LAKEHURS
Adder
0.858
20714928UPF_X1-085
Solar/Wind Harmer
0.365
219615MILLCREEK C
Solar/Wind Harmer
0.211
213535CROYDN11
Adder
8.693
20720628TIN_W1-124
Solar/Wind Harmer
0.809
20641628MLH_W1-032
Solar/Wind Harmer
0.237
219114HARTZY_C
Solar/Wind Harmer
0.662
20716928W4-060COL
Solar/Wind Harmer
0.539
219817TRENTONSOL C
Solar/Wind Harmer
0.821
924131AB2-057 GEN
Solar/Wind Harmer
0.71
218440SUMMTASSOC C
Solar/Wind Harmer
0.087
218418LINDEN_G5
Adder
11.232
218419LINDEN_G6
Adder
11.232
972260AH1-715 GEN1
Adder
8.994
219036LINDEN_G7
Adder
10.657
219035LINDEN_G8
Adder
10.505
972261AH1-715 GEN2
Adder
10.202
213589EDDYSTN4
Adder
47.992
213587EDDYSTN3
Adder
47.987
217081WEATEXAS C
Solar/Wind Harmer
0.054
217202FBANKSOLAR C
Solar/Wind Harmer
0.046
217201HACKENSOLA C
Solar/Wind Harmer
0.044
972237AH1-703 GEN
Adder
6.134
217206BARNGR HS C
Solar/Wind Harmer
0.019
217086KRNY_131
Adder
5.638
217083KRNY_132
Adder
5.591
20673828FLE_V3-070
Solar/Wind Harmer
0.273
207442AE1-156 GEN
Solar/Wind Harmer
0.441
20676128MHD_W3-029
Solar/Wind Harmer
0.283
217204WCALDSOLAR C
Solar/Wind Harmer
0.044
20671828STAW2-080
Solar/Wind Harmer
0.06
20674528F3S_W2-016
Solar/Wind Harmer
0.745
20676228FRD_X1-012
Solar/Wind Harmer
0.302
200204Y1-065-CTG1
50/50
11.811
200054ROCKSP 3
50/50
7.534
231912HR6
50/50
3.699
231913HR7
50/50
3.699
232919VN10
50/50
7.585
231917EM10
Adder
6
965821AG1-450 GEN
Solar/Wind Harmer
13.26
232426Y1-080 FULL
Solar/Wind Harmer
0.487
970277AG2-181 GEN
Solar/Wind Harmer
12.771
233964AF2-378 GEN
Solar/Wind Harmer
0.325
233998TM1NIN_3.36
Solar/Wind Harmer
3.223
232428Y3-058 C
Solar/Wind Harmer
2.123
232404W1-003 C
Solar/Wind Harmer
2.547
232917OH NUG6
Adder
22.36
232915OH NUG4
Adder
22.31
971195AH1-057 GEN
Solar/Wind Harmer
2.783
232434Z2-077 GEN
Solar/Wind Harmer
0.635
231918WEST 1
Adder
8.509
972177AH1-672 GEN
Solar/Wind Harmer
33.97
233954AC2-188 GEN
Solar/Wind Harmer
2.838
233950AC2-186 GEN
Solar/Wind Harmer
1.419
232901NORTHST
Adder
20.929
234012AE2-112_GEN
Solar/Wind Harmer
5.78
232900DEMECSMY
Adder
23.12
232422X3-066 FULL
Solar/Wind Harmer
0.627
232910NRG_G1
Adder
21.626
233972AC1-094 C
Solar/Wind Harmer
1.659
233930AB2-032 GEN
Solar/Wind Harmer
2.081
233915AB1-141 GEN
Solar/Wind Harmer
2.472
228206SHRMN CT
Adder
22.551
228732V1-021 C
Adder
0.256
945431AF1-208 GEN
Solar/Wind Harmer
11.082
970997AG2-616 GEN
Solar/Wind Harmer
12.084
228728W1-130C
Solar/Wind Harmer
0.832
230511AF1-262
Solar/Wind Harmer
0.229
228351V2-046C
Solar/Wind Harmer
2.487
230434AG1-499 GEN
Solar/Wind Harmer
0.688
218660EHAMPSOLAR C
Solar/Wind Harmer
0.186
219686LUMSOLAR_N C
Solar/Wind Harmer
0.215
219287REEVESEAST C
Solar/Wind Harmer
1.425
219258KINSLEYDEP C
Solar/Wind Harmer
0.314
207487AE2-000G4
Solar/Wind Harmer
30.224
219904AC1-010 C
Solar/Wind Harmer
0.358
20720728JCB_W1-129
Solar/Wind Harmer
0.28
207522AF2-254 C
Solar/Wind Harmer
1.346
219907AC1-030 C
Solar/Wind Harmer
0.125
207445AB1-138_GEN
Solar/Wind Harmer
0.523
20628028LAKEHURS
Adder
1.697
219304NAMERICA C
Solar/Wind Harmer
0.271
219222BRL12CT2
Adder
7.787
963711AG1-223 GEN
Solar/Wind Harmer
1.276
20714828MDF_W3-079
Solar/Wind Harmer
0.264
207454AA2-184 E
Solar/Wind Harmer
0.812
213611FALLS1-3
Adder
2.791
20715228NPK_W1-113
Solar/Wind Harmer
0.343
20742028HF_AC1-207
Solar/Wind Harmer
0.622
219680HOPEWELLV C1
Solar/Wind Harmer
0.055
20635828PARLN1&2
Adder
5.378
217197RE CRAN C
Solar/Wind Harmer
0.383
20635028RRCT1&2
Adder
8.251
20635128RRCT3&4
Adder
7.964
213560DLW11-12
Adder
1.785
218428ETC SOLAR C
Solar/Wind Harmer
0.024
217213AMBOY SO C
Solar/Wind Harmer
0.084
972275AH1-722 GEN
Adder
20.649
213958STHWK5-6
Adder
1.659
218449LINSOLAR C
Solar/Wind Harmer
0.641
213497CHSTR7-9
Adder
1.642
213497CHSTR7-9
Adder
1.642
217209CENTRL HS C
Solar/Wind Harmer
0.028
217121ECCF
Adder
0.263
217083KRNY_132
Adder
5.626
217208PARK ELE C
Solar/Wind Harmer
0.015
207528AF2-192 GEN
Solar/Wind Harmer
0.328
20673628F1S_V4-069
Solar/Wind Harmer
0.106
20675428EAM_W2-061
Solar/Wind Harmer
0.112
20676428JCR_X2-075
Solar/Wind Harmer
0.201
207439AE1-081 C O1
Solar/Wind Harmer
0.031
20675828AU_W4-064
Solar/Wind Harmer
0.087
20674328GAR_V4-001
Solar/Wind Harmer
0.054
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.109
G-007ALTFEXP_G-007A->PJM
CMTX
36.44
CBM NorthLTFEXP_CBM-N->PJM
CBM
36.716
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
2.769
BlueGrassPJM->LTFIMP_BlueG
CLTF
8.625
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
83.626
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.859
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
12.936

Details for ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line l/o PECO_P4_CHICH435_SRT-A/* $ DELCO $ PECO_P4_CHICH435 $ STBK


Base Case Flowgate

Area:PJM
Facility Description:
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line
Contingency Name:
PECO_P4_CHICH435_SRT-A/* $ DELCO $ PECO_P4_CHICH435 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.75 %
Rating:2905.0 MVA
Rating Type:B
MVA to Mitigate:3071.98
MW Contribution:10.48
Bus #Bus NameTypeMW Contribution
200205Y1-065-CTG2
50/50
11.728
232926CRISFLD1
50/50
5.088
232918OH NUG7
50/50
22.739
232905CHERITON_25
50/50
6.359
231940T-011
50/50
1.93
232899W1-062
50/50
24.717
231131BLOOM ENRGY
50/50
11.104
233987AB2-037 GEN
Solar/Wind Harmer
28.069
233901CHERRYDALE C
Solar/Wind Harmer
2.75
232408W1-005 C
Solar/Wind Harmer
2.446
232410W1-006 C
Solar/Wind Harmer
2.446
971747AH1-380 GEN
Solar/Wind Harmer
8.749
972069AH1-584 GEN
Solar/Wind Harmer
21.871
972071AH1-585 GEN
Solar/Wind Harmer
21.871
233946AB2-136 GEN
Solar/Wind Harmer
9.743
234036AF2-325 C
Solar/Wind Harmer
2.238
970545AG2-347 GEN
Solar/Wind Harmer
159.632
234041AC1-190 GEN
Solar/Wind Harmer
21.847
971149AH1-027 GEN
Solar/Wind Harmer
8.229
233939AC1-091 C
Solar/Wind Harmer
2.128
233970AC1-092 C
Solar/Wind Harmer
2.128
233984AB2-036 GEN
Solar/Wind Harmer
30.062
232424Y1-079 C
Solar/Wind Harmer
1.356
234014AF1-036_GEN
Solar/Wind Harmer
6.479
233944AB2-135 GEN
Solar/Wind Harmer
12.438
233933AB2-153 GEN
Solar/Wind Harmer
2.671
232416X2-083
Adder
1.06
228251CARLLS#4
Adder
0.901
230422AE1-104_GEN1
Solar/Wind Harmer
47.71
230425AE1-104_GEN2
Solar/Wind Harmer
47.71
230433AD2-135 GEN
Solar/Wind Harmer
0.14
228307PCLP GT
Adder
16.33
230407AD2-065 C
Solar/Wind Harmer
0.176
228304LOGAN
Adder
32.197
972233AH1-701 GEN
Adder
5.495
219921AF1-264
Solar/Wind Harmer
0.159
207500AE2-000G1
Solar/Wind Harmer
32.09
207497AE2-000G2
Solar/Wind Harmer
32.09
207507AE2-000G3
Solar/Wind Harmer
32.09
20636128O CRK C2
Adder
6.565
20716428NHV_W2-082
Solar/Wind Harmer
1.782
963401AG1-189 GEN
Solar/Wind Harmer
1.153
963391AG1-188 GEN
Solar/Wind Harmer
1.905
219615MILLCREEK C
Solar/Wind Harmer
0.234
20628028LAKEHURS
Adder
0.91
20714928UPF_X1-085
Solar/Wind Harmer
0.388
213535CROYDN11
Adder
9.543
219114HARTZY_C
Solar/Wind Harmer
0.716
20720628TIN_W1-124
Solar/Wind Harmer
0.854
20641628MLH_W1-032
Solar/Wind Harmer
0.249
20716928W4-060COL
Solar/Wind Harmer
0.568
219817TRENTONSOL C
Solar/Wind Harmer
0.867
924131AB2-057 GEN
Solar/Wind Harmer
0.75
218440SUMMTASSOC C
Solar/Wind Harmer
0.091
218418LINDEN_G5
Adder
11.824
218419LINDEN_G6
Adder
11.824
972260AH1-715 GEN1
Adder
9.468
219036LINDEN_G7
Adder
11.214
219035LINDEN_G8
Adder
11.054
972261AH1-715 GEN2
Adder
10.735
217081WEATEXAS C
Solar/Wind Harmer
0.057
217202FBANKSOLAR C
Solar/Wind Harmer
0.048
217201HACKENSOLA C
Solar/Wind Harmer
0.047
972237AH1-703 GEN
Adder
6.451
217206BARNGR HS C
Solar/Wind Harmer
0.02
217086KRNY_131
Adder
5.929
217083KRNY_132
Adder
5.879
20673828FLE_V3-070
Solar/Wind Harmer
0.288
207442AE1-156 GEN
Solar/Wind Harmer
0.463
20676128MHD_W3-029
Solar/Wind Harmer
0.297
217204WCALDSOLAR C
Solar/Wind Harmer
0.046
20671828STAW2-080
Solar/Wind Harmer
0.063
213587EDDYSTN3
Adder
44.398
213589EDDYSTN4
Adder
44.372
20674528F3S_W2-016
Solar/Wind Harmer
0.783
20676228FRD_X1-012
Solar/Wind Harmer
0.317
200204Y1-065-CTG1
50/50
11.728
200054ROCKSP 3
50/50
7.481
231912HR6
50/50
3.57
231913HR7
50/50
3.57
232917OH NUG6
50/50
22.79
232915OH NUG4
50/50
22.739
232919VN10
50/50
7.275
233920W3-032A-CTG1
50/50
5.347
233921W3-032A-STG1
50/50
3.211
232901NORTHST
50/50
21.471
232900DEMECSMY
50/50
23.708
232910NRG_G1
50/50
22.038
233998TM1NIN_3.36
Solar/Wind Harmer
3.095
232404W1-003 C
Solar/Wind Harmer
2.446
232428Y3-058 C
Solar/Wind Harmer
2.038
965821AG1-450 GEN
Solar/Wind Harmer
12.714
971195AH1-057 GEN
Solar/Wind Harmer
2.673
232426Y1-080 FULL
Solar/Wind Harmer
0.467
970277AG2-181 GEN
Solar/Wind Harmer
12.245
233964AF2-378 GEN
Solar/Wind Harmer
0.312
232434Z2-077 GEN
Solar/Wind Harmer
0.611
972177AH1-672 GEN
Solar/Wind Harmer
32.705
233954AC2-188 GEN
Solar/Wind Harmer
2.73
233950AC2-186 GEN
Solar/Wind Harmer
1.365
233972AC1-094 C
Solar/Wind Harmer
1.607
234012AE2-112_GEN
Solar/Wind Harmer
5.507
232422X3-066 FULL
Solar/Wind Harmer
0.597
233930AB2-032 GEN
Solar/Wind Harmer
1.98
233915AB1-141 GEN
Solar/Wind Harmer
2.353
231918WEST 1
Adder
7.667
231917EM10
Adder
5.324
228206SHRMN CT
Adder
24.265
228732V1-021 C
Adder
0.274
945431AF1-208 GEN
Solar/Wind Harmer
12.256
970997AG2-616 GEN
Solar/Wind Harmer
13.465
228351V2-046C
Solar/Wind Harmer
2.8
230511AF1-262
Solar/Wind Harmer
0.254
228728W1-130C
Solar/Wind Harmer
0.915
230434AG1-499 GEN
Solar/Wind Harmer
0.778
218660EHAMPSOLAR C
Solar/Wind Harmer
0.201
219686LUMSOLAR_N C
Solar/Wind Harmer
0.232
219287REEVESEAST C
Solar/Wind Harmer
1.542
219258KINSLEYDEP C
Solar/Wind Harmer
0.367
219904AC1-010 C
Solar/Wind Harmer
0.408
207487AE2-000G4
Solar/Wind Harmer
32.09
219907AC1-030 C
Solar/Wind Harmer
0.14
20720728JCB_W1-129
Solar/Wind Harmer
0.299
207522AF2-254 C
Solar/Wind Harmer
1.437
219304NAMERICA C
Solar/Wind Harmer
0.298
219222BRL12CT2
Adder
8.563
207445AB1-138_GEN
Solar/Wind Harmer
0.555
20628028LAKEHURS
Adder
1.8
963711AG1-223 GEN
Solar/Wind Harmer
1.351
20714828MDF_W3-079
Solar/Wind Harmer
0.279
213611FALLS1-3
Adder
3.035
207454AA2-184 E
Solar/Wind Harmer
0.857
20715228NPK_W1-113
Solar/Wind Harmer
0.361
20742028HF_AC1-207
Solar/Wind Harmer
0.654
219680HOPEWELLV C1
Solar/Wind Harmer
0.059
20635828PARLN1&2
Adder
5.667
217197RE CRAN C
Solar/Wind Harmer
0.407
20635028RRCT1&2
Adder
8.692
20635128RRCT3&4
Adder
8.39
213560DLW11-12
Adder
1.868
218428ETC SOLAR C
Solar/Wind Harmer
0.025
217213AMBOY SO C
Solar/Wind Harmer
0.089
972275AH1-722 GEN
Adder
21.736
218449LINSOLAR C
Solar/Wind Harmer
0.674
217209CENTRL HS C
Solar/Wind Harmer
0.029
213958STHWK5-6
Adder
1.639
217121ECCF
Adder
0.277
217083KRNY_132
Adder
5.917
217208PARK ELE C
Solar/Wind Harmer
0.016
207528AF2-192 GEN
Solar/Wind Harmer
0.345
20673628F1S_V4-069
Solar/Wind Harmer
0.112
20675428EAM_W2-061
Solar/Wind Harmer
0.118
20676428JCR_X2-075
Solar/Wind Harmer
0.212
213497CHSTR7-9
Adder
1.513
213497CHSTR7-9
Adder
1.513
207439AE1-081 C O1
Solar/Wind Harmer
0.033
20675828AU_W4-064
Solar/Wind Harmer
0.092
20674328GAR_V4-001
Solar/Wind Harmer
0.057
200052ROCKSP 1
50/50
7.407
200053ROCKSP 2
50/50
7.249
232912OH NUG1
50/50
22.892
232913OH NUG2
50/50
22.587
232904IR4
50/50
209.296
232920IR10
50/50
8.181
232616GEN FOOD
50/50
0.421
232813VAUGHN
50/50
1.507
233923SMA
Solar/Wind Harmer
11.346
233990AG1-397 GEN
Solar/Wind Harmer
0.135
232432Z2-076 GEN
Solar/Wind Harmer
0.322
234033AF1-007_GEN
Solar/Wind Harmer
57.044
233955AB2-172 GEN
Solar/Wind Harmer
12.2
233973AC2-185 C
Solar/Wind Harmer
8.755
231906DC3 NUG
Adder
33.6
231902DC CT7
Adder
26.861
200203Y1-065-STG
50/50
20.337
200055ROCKSP 4
50/50
7.324
231914HR8
50/50
5.425
231911HR5
50/50
3.57
232907VN8
50/50
77.961
232914OH NUG3
50/50
22.892
232916OH NUG5
50/50
22.892
232921TASLEY2G
50/50
13.379
234034AF2-060
50/50
4.578
233900O-025 C
50/50
3.051
232911NRG_G2
50/50
1.205
233996TM1833_GEN
Solar/Wind Harmer
3.095
233997TMININ_4.2
Solar/Wind Harmer
3.095
233940AF2-379 C
Solar/Wind Harmer
0.456
232406W1-004 FULL
Solar/Wind Harmer
2.446
233994AC2-023 GEN
Solar/Wind Harmer
6.565
972073AH1-586 GEN
Solar/Wind Harmer
22.888
960671AF2-358 GEN
Solar/Wind Harmer
43.737
234015AF2-250 C
Solar/Wind Harmer
0.294
233990AG1-397 GEN
Solar/Wind Harmer
2.801
972133AH1-634 GEN
Solar/Wind Harmer
24.187
232417X3-008 C
Solar/Wind Harmer
4.88
233952AC2-187 GEN
Solar/Wind Harmer
2.73
233971AC1-093 C
Solar/Wind Harmer
1.901
970695AG2-447 GEN
Solar/Wind Harmer
8.681
233918AB1-142 GEN
Solar/Wind Harmer
2.353
233982AB2-133 GEN
Solar/Wind Harmer
11.535
972251AH1-710 GEN
Adder
96.69
228202CUMB CT
Adder
24.37
228711V2-041C
Solar/Wind Harmer
0.882
971553AH1-274 GEN
Solar/Wind Harmer
3.504
230430AE1-229_GEN
Solar/Wind Harmer
12.316
228729W2-030 C
Solar/Wind Harmer
0.799
230415AB2-049 C
Solar/Wind Harmer
0.258
228304LOGAN
Adder
28.958
219291REEVESSOUT C
Solar/Wind Harmer
0.07
219623KINSLEYBEA C
Solar/Wind Harmer
0.482
219766PARADISE C
Solar/Wind Harmer
0.339
219912AD2-042 GEN
Solar/Wind Harmer
0.82
20636028O CRK C1
Adder
7.2
219236SOUTHERNHQ C
Solar/Wind Harmer
0.068
20716028EGP_W2-019
Solar/Wind Harmer
0.466
20720828JCB_W4-025
Solar/Wind Harmer
0.455
20715028HAN_X4-015
Solar/Wind Harmer
0.299
219906AC1-017 C
Solar/Wind Harmer
0.218
219610FLORENCE C
Solar/Wind Harmer
1.329
219348LDSOLAR C
Solar/Wind Harmer
0.574
219221BRL12CT1
Adder
8.563
219223BRL12CT3
Adder
8.563
971667AH1-334 GEN
Solar/Wind Harmer
2.652
959561AF2-247 GEN
Solar/Wind Harmer
0.439
20714528FRN_Y2-051
Solar/Wind Harmer
0.269
219727YARDVSOLFA C
Solar/Wind Harmer
0.769
20720528MAN_W1-024
Solar/Wind Harmer
0.214
20716228APLW2-078
Solar/Wind Harmer
0.741
219276PARKLANDSO C
Solar/Wind Harmer
0.376
967451AG2-055 C O1
Solar/Wind Harmer
140.568
219918AC2-009 C
Solar/Wind Harmer
0.047
20635828PARLN1&2
Adder
2.567
20635928PARLN3&4
Adder
2.567
219612MATRIX C
Solar/Wind Harmer
0.139
218438BLK ROCK C
Solar/Wind Harmer
0.103
20635028RRCT1&2
Adder
8.828
20635128RRCT3&4
Adder
7.319
213560DLW11-12
Adder
1.868
219908AB1-139 C
Solar/Wind Harmer
0.267
219919AE1-041 FULL
Solar/Wind Harmer
0.028
219249CENTRALDIV C
Solar/Wind Harmer
0.027
217211CAMDEN ST C
Solar/Wind Harmer
0.016
213958STHWK5-6
Adder
1.639
217186ESSEX_G9
Adder
10.183
217169METRODIV C
Solar/Wind Harmer
0.025
217194REDH C
Solar/Wind Harmer
0.313
20673728F2S_V4-070
Solar/Wind Harmer
0.112
213497CHSTR7-9
Adder
1.513
20676728BRNX1-095
Solar/Wind Harmer
0.104
20674628WNG_W3-110
Solar/Wind Harmer
0.218
207510AF2-138 C
Solar/Wind Harmer
0.956
231907DC10
Adder
8.388
233968AD2-076_GEN
Solar/Wind Harmer
15.873
970597AG2-380 GEN
Solar/Wind Harmer
9.967
232436AB1-176 C
Solar/Wind Harmer
0.547
971983AH1-536 GEN
Solar/Wind Harmer
17.771
231919CHRIST1
Adder
10.079
231920CHRIST2
Adder
9.855
233935AB2-179 C
Solar/Wind Harmer
5.699
970453AG2-297 GEN
Solar/Wind Harmer
4.117
228260V4-054C
Solar/Wind Harmer
1.467
228309CCLP NUG
Adder
36.399
228309CCLP NUG
Adder
34.624
972141AH1-641 GEN
Solar/Wind Harmer
4.04
964001AG1-254 GEN
Solar/Wind Harmer
2.833
227927V4-067C
Solar/Wind Harmer
0.274
228754AB1-001 C
Solar/Wind Harmer
0.192
971535AH1-265 GEN
Solar/Wind Harmer
5.822
971011AG2-627 GEN
Solar/Wind Harmer
10.48
219137THOSOLAR C
Solar/Wind Harmer
1.455
219272CLEANLIGHT C
Solar/Wind Harmer
0.209
219688LUMSOLAR_S C
Solar/Wind Harmer
0.228
219914AD2-027 C
Solar/Wind Harmer
0.619
20717128DIX_Z2-102
Solar/Wind Harmer
1.32
20715728PEM_W1-119
Solar/Wind Harmer
0.533
20715828PEM_W1-120
Solar/Wind Harmer
0.533
970025AG2-016 GEN
Solar/Wind Harmer
2.819
971189AH1-054 GEN
Solar/Wind Harmer
1.156
207459AE1-142 C O1
Solar/Wind Harmer
1.025
219607WPEMNERT C
Solar/Wind Harmer
0.402
219224BRL12CT4
Adder
8.563
214067T20SOLAR
Solar/Wind Harmer
0.217
213611FALLS1-3
Adder
3.035
213611FALLS1-3
Adder
3.035
20714328BYD_X4-031
Solar/Wind Harmer
0.246
20714428HOW_X1-037
Solar/Wind Harmer
1.07
971521AH1-258 GEN
Solar/Wind Harmer
2.251
20720428HOL_W1-112
Solar/Wind Harmer
0.285
219620RIDERU C
Solar/Wind Harmer
0.044
20635928PARLN3&4
Adder
5.667
218455CINNBAY_CGEN
Adder
1.325
213561DLWR9-10
Adder
2.443
213561DLWR9-10
Adder
1.868
218526CNTRALGAS2 C
Solar/Wind Harmer
0.264
218524CNTRALGAS1 C
Solar/Wind Harmer
0.264
218404KENILWRTH C
Adder
0.844
20675528CPH_W2-050
Solar/Wind Harmer
0.296
213957STHWK3-4
Adder
1.639
213957STHWK3-4
Adder
1.639
217167KRNY_14
Adder
5.917
217086KRNY_131
Adder
5.866
217147KRNY_1212
Adder
5.628
217147KRNY_1212
Adder
5.527
217146KRNY_1234
Adder
5.515
217146KRNY_1234
Adder
5.477
213942SCHUYLKILL
Adder
2.109
213942SCHUYLKILL
Adder
1.613
20676328BVR_Y1-020
Solar/Wind Harmer
0.18
207511W3-106 GEN
Solar/Wind Harmer
0.354
207530AG1-191 GEN
Solar/Wind Harmer
0.729
966261AG1-495 GEN
Solar/Wind Harmer
0.941
20674828DL_W4-046
Solar/Wind Harmer
0.32
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.239
G-007ALTFEXP_G-007A->PJM
CMTX
38.39
CBM NorthLTFEXP_CBM-N->PJM
CBM
38.597
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
2.883
BlueGrassPJM->LTFIMP_BlueG
CLTF
8.98
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
87.938
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.936
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
13.469

Details for ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line l/o PECO_P4_CHICH195_SRT-A/* $ DELCO $ PECO_P4_CHICH195 $ STBK


Base Case Flowgate

Area:PJM
Facility Description:
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line
Contingency Name:
PECO_P4_CHICH195_SRT-A/* $ DELCO $ PECO_P4_CHICH195 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.75 %
Rating:2905.0 MVA
Rating Type:B
MVA to Mitigate:3071.96
MW Contribution:10.48
Bus #Bus NameTypeMW Contribution
200205Y1-065-CTG2
50/50
11.728
232926CRISFLD1
50/50
5.088
232918OH NUG7
50/50
22.739
232905CHERITON_25
50/50
6.359
231940T-011
50/50
1.93
232899W1-062
50/50
24.717
231131BLOOM ENRGY
50/50
11.104
233987AB2-037 GEN
Solar/Wind Harmer
28.068
233901CHERRYDALE C
Solar/Wind Harmer
2.75
232408W1-005 C
Solar/Wind Harmer
2.446
232410W1-006 C
Solar/Wind Harmer
2.446
971747AH1-380 GEN
Solar/Wind Harmer
8.748
972069AH1-584 GEN
Solar/Wind Harmer
21.87
972071AH1-585 GEN
Solar/Wind Harmer
21.87
233946AB2-136 GEN
Solar/Wind Harmer
9.742
234036AF2-325 C
Solar/Wind Harmer
2.238
970545AG2-347 GEN
Solar/Wind Harmer
159.629
234041AC1-190 GEN
Solar/Wind Harmer
21.847
971149AH1-027 GEN
Solar/Wind Harmer
8.229
233939AC1-091 C
Solar/Wind Harmer
2.128
233970AC1-092 C
Solar/Wind Harmer
2.128
233984AB2-036 GEN
Solar/Wind Harmer
30.061
232424Y1-079 C
Solar/Wind Harmer
1.356
234014AF1-036_GEN
Solar/Wind Harmer
6.479
233944AB2-135 GEN
Solar/Wind Harmer
12.437
233933AB2-153 GEN
Solar/Wind Harmer
2.671
232416X2-083
Adder
1.06
228251CARLLS#4
Adder
0.901
230422AE1-104_GEN1
Solar/Wind Harmer
47.71
230425AE1-104_GEN2
Solar/Wind Harmer
47.71
230433AD2-135 GEN
Solar/Wind Harmer
0.14
228307PCLP GT
Adder
16.33
230407AD2-065 C
Solar/Wind Harmer
0.176
228304LOGAN
Adder
32.199
972233AH1-701 GEN
Adder
5.495
219921AF1-264
Solar/Wind Harmer
0.159
207500AE2-000G1
Solar/Wind Harmer
32.091
207497AE2-000G2
Solar/Wind Harmer
32.091
207507AE2-000G3
Solar/Wind Harmer
32.091
20636128O CRK C2
Adder
6.565
20716428NHV_W2-082
Solar/Wind Harmer
1.782
963401AG1-189 GEN
Solar/Wind Harmer
1.153
963391AG1-188 GEN
Solar/Wind Harmer
1.905
219615MILLCREEK C
Solar/Wind Harmer
0.234
20628028LAKEHURS
Adder
0.91
20714928UPF_X1-085
Solar/Wind Harmer
0.388
213535CROYDN11
Adder
9.544
219114HARTZY_C
Solar/Wind Harmer
0.716
20720628TIN_W1-124
Solar/Wind Harmer
0.854
20641628MLH_W1-032
Solar/Wind Harmer
0.249
20716928W4-060COL
Solar/Wind Harmer
0.568
219817TRENTONSOL C
Solar/Wind Harmer
0.867
924131AB2-057 GEN
Solar/Wind Harmer
0.75
218440SUMMTASSOC C
Solar/Wind Harmer
0.091
218418LINDEN_G5
Adder
11.824
218419LINDEN_G6
Adder
11.824
972260AH1-715 GEN1
Adder
9.468
219036LINDEN_G7
Adder
11.214
219035LINDEN_G8
Adder
11.054
972261AH1-715 GEN2
Adder
10.735
217081WEATEXAS C
Solar/Wind Harmer
0.057
217202FBANKSOLAR C
Solar/Wind Harmer
0.048
217201HACKENSOLA C
Solar/Wind Harmer
0.047
972237AH1-703 GEN
Adder
6.451
217206BARNGR HS C
Solar/Wind Harmer
0.02
217086KRNY_131
Adder
5.929
217083KRNY_132
Adder
5.879
20673828FLE_V3-070
Solar/Wind Harmer
0.288
207442AE1-156 GEN
Solar/Wind Harmer
0.463
20676128MHD_W3-029
Solar/Wind Harmer
0.297
217204WCALDSOLAR C
Solar/Wind Harmer
0.046
20671828STAW2-080
Solar/Wind Harmer
0.063
213587EDDYSTN3
Adder
44.399
213589EDDYSTN4
Adder
44.374
20674528F3S_W2-016
Solar/Wind Harmer
0.783
20676228FRD_X1-012
Solar/Wind Harmer
0.317
200203Y1-065-STG
50/50
20.337
200055ROCKSP 4
50/50
7.324
231914HR8
50/50
5.425
231911HR5
50/50
3.57
232907VN8
50/50
77.96
232914OH NUG3
50/50
22.892
232916OH NUG5
50/50
22.892
232921TASLEY2G
50/50
13.379
234034AF2-060
50/50
4.578
233900O-025 C
50/50
3.051
232911NRG_G2
50/50
1.205
233996TM1833_GEN
Solar/Wind Harmer
3.095
233997TMININ_4.2
Solar/Wind Harmer
3.095
233940AF2-379 C
Solar/Wind Harmer
0.456
232406W1-004 FULL
Solar/Wind Harmer
2.446
233994AC2-023 GEN
Solar/Wind Harmer
6.565
972073AH1-586 GEN
Solar/Wind Harmer
22.888
960671AF2-358 GEN
Solar/Wind Harmer
43.736
234015AF2-250 C
Solar/Wind Harmer
0.294
233990AG1-397 GEN
Solar/Wind Harmer
2.801
972133AH1-634 GEN
Solar/Wind Harmer
24.186
232417X3-008 C
Solar/Wind Harmer
4.88
233952AC2-187 GEN
Solar/Wind Harmer
2.73
233971AC1-093 C
Solar/Wind Harmer
1.901
970695AG2-447 GEN
Solar/Wind Harmer
8.681
233918AB1-142 GEN
Solar/Wind Harmer
2.353
233982AB2-133 GEN
Solar/Wind Harmer
11.534
972251AH1-710 GEN
Adder
96.689
228202CUMB CT
Adder
24.371
228711V2-041C
Solar/Wind Harmer
0.882
971553AH1-274 GEN
Solar/Wind Harmer
3.504
230430AE1-229_GEN
Solar/Wind Harmer
12.316
228729W2-030 C
Solar/Wind Harmer
0.799
230415AB2-049 C
Solar/Wind Harmer
0.258
228304LOGAN
Adder
28.959
219291REEVESSOUT C
Solar/Wind Harmer
0.07
219623KINSLEYBEA C
Solar/Wind Harmer
0.482
219766PARADISE C
Solar/Wind Harmer
0.339
219912AD2-042 GEN
Solar/Wind Harmer
0.82
20636028O CRK C1
Adder
7.201
219236SOUTHERNHQ C
Solar/Wind Harmer
0.068
20716028EGP_W2-019
Solar/Wind Harmer
0.466
20720828JCB_W4-025
Solar/Wind Harmer
0.455
20715028HAN_X4-015
Solar/Wind Harmer
0.299
219906AC1-017 C
Solar/Wind Harmer
0.218
219610FLORENCE C
Solar/Wind Harmer
1.329
219348LDSOLAR C
Solar/Wind Harmer
0.575
219221BRL12CT1
Adder
8.563
219223BRL12CT3
Adder
8.563
971667AH1-334 GEN
Solar/Wind Harmer
2.652
959561AF2-247 GEN
Solar/Wind Harmer
0.439
20714528FRN_Y2-051
Solar/Wind Harmer
0.269
219727YARDVSOLFA C
Solar/Wind Harmer
0.769
20720528MAN_W1-024
Solar/Wind Harmer
0.214
20716228APLW2-078
Solar/Wind Harmer
0.741
219276PARKLANDSO C
Solar/Wind Harmer
0.376
967451AG2-055 C O1
Solar/Wind Harmer
140.57
219918AC2-009 C
Solar/Wind Harmer
0.047
20635828PARLN1&2
Adder
2.567
20635928PARLN3&4
Adder
2.567
219612MATRIX C
Solar/Wind Harmer
0.139
218438BLK ROCK C
Solar/Wind Harmer
0.103
20635028RRCT1&2
Adder
8.828
20635128RRCT3&4
Adder
7.319
213560DLW11-12
Adder
1.868
219908AB1-139 C
Solar/Wind Harmer
0.267
219919AE1-041 FULL
Solar/Wind Harmer
0.028
219249CENTRALDIV C
Solar/Wind Harmer
0.027
217211CAMDEN ST C
Solar/Wind Harmer
0.016
213958STHWK5-6
Adder
1.639
217186ESSEX_G9
Adder
10.183
217169METRODIV C
Solar/Wind Harmer
0.025
217194REDH C
Solar/Wind Harmer
0.313
20673728F2S_V4-070
Solar/Wind Harmer
0.112
213497CHSTR7-9
Adder
1.514
20676728BRNX1-095
Solar/Wind Harmer
0.104
20674628WNG_W3-110
Solar/Wind Harmer
0.218
207510AF2-138 C
Solar/Wind Harmer
0.956
200052ROCKSP 1
50/50
7.407
200053ROCKSP 2
50/50
7.249
232912OH NUG1
50/50
22.892
232913OH NUG2
50/50
22.586
232904IR4
50/50
209.292
232920IR10
50/50
8.18
232616GEN FOOD
50/50
0.421
232813VAUGHN
50/50
1.507
233923SMA
Solar/Wind Harmer
11.346
233990AG1-397 GEN
Solar/Wind Harmer
0.135
232432Z2-076 GEN
Solar/Wind Harmer
0.322
234033AF1-007_GEN
Solar/Wind Harmer
57.043
233955AB2-172 GEN
Solar/Wind Harmer
12.2
233973AC2-185 C
Solar/Wind Harmer
8.755
231906DC3 NUG
Adder
33.599
231902DC CT7
Adder
26.861
231907DC10
Adder
8.388
233968AD2-076_GEN
Solar/Wind Harmer
15.873
970597AG2-380 GEN
Solar/Wind Harmer
9.967
232436AB1-176 C
Solar/Wind Harmer
0.547
971983AH1-536 GEN
Solar/Wind Harmer
17.77
231919CHRIST1
Adder
10.079
231920CHRIST2
Adder
9.855
233935AB2-179 C
Solar/Wind Harmer
5.699
970453AG2-297 GEN
Solar/Wind Harmer
4.117
228260V4-054C
Solar/Wind Harmer
1.467
228309CCLP NUG
Adder
36.401
228309CCLP NUG
Adder
34.625
972141AH1-641 GEN
Solar/Wind Harmer
4.04
964001AG1-254 GEN
Solar/Wind Harmer
2.833
227927V4-067C
Solar/Wind Harmer
0.274
228754AB1-001 C
Solar/Wind Harmer
0.192
971535AH1-265 GEN
Solar/Wind Harmer
5.823
971011AG2-627 GEN
Solar/Wind Harmer
10.481
219137THOSOLAR C
Solar/Wind Harmer
1.455
219272CLEANLIGHT C
Solar/Wind Harmer
0.209
219688LUMSOLAR_S C
Solar/Wind Harmer
0.228
219914AD2-027 C
Solar/Wind Harmer
0.619
20717128DIX_Z2-102
Solar/Wind Harmer
1.32
20715728PEM_W1-119
Solar/Wind Harmer
0.533
20715828PEM_W1-120
Solar/Wind Harmer
0.533
970025AG2-016 GEN
Solar/Wind Harmer
2.819
971189AH1-054 GEN
Solar/Wind Harmer
1.156
207459AE1-142 C O1
Solar/Wind Harmer
1.025
219607WPEMNERT C
Solar/Wind Harmer
0.402
219224BRL12CT4
Adder
8.563
214067T20SOLAR
Solar/Wind Harmer
0.217
213611FALLS1-3
Adder
3.036
213611FALLS1-3
Adder
3.036
20714328BYD_X4-031
Solar/Wind Harmer
0.246
20714428HOW_X1-037
Solar/Wind Harmer
1.07
971521AH1-258 GEN
Solar/Wind Harmer
2.251
20720428HOL_W1-112
Solar/Wind Harmer
0.285
219620RIDERU C
Solar/Wind Harmer
0.044
20635928PARLN3&4
Adder
5.668
218455CINNBAY_CGEN
Adder
1.325
213561DLWR9-10
Adder
2.443
213561DLWR9-10
Adder
1.868
218526CNTRALGAS2 C
Solar/Wind Harmer
0.264
218524CNTRALGAS1 C
Solar/Wind Harmer
0.264
218404KENILWRTH C
Adder
0.844
20675528CPH_W2-050
Solar/Wind Harmer
0.296
213957STHWK3-4
Adder
1.64
213957STHWK3-4
Adder
1.64
217167KRNY_14
Adder
5.917
217086KRNY_131
Adder
5.867
217147KRNY_1212
Adder
5.628
217147KRNY_1212
Adder
5.527
217146KRNY_1234
Adder
5.515
217146KRNY_1234
Adder
5.477
213942SCHUYLKILL
Adder
2.109
213942SCHUYLKILL
Adder
1.613
20676328BVR_Y1-020
Solar/Wind Harmer
0.18
207511W3-106 GEN
Solar/Wind Harmer
0.354
207530AG1-191 GEN
Solar/Wind Harmer
0.729
966261AG1-495 GEN
Solar/Wind Harmer
0.941
20674828DL_W4-046
Solar/Wind Harmer
0.32
200204Y1-065-CTG1
50/50
11.728
200054ROCKSP 3
50/50
7.481
231912HR6
50/50
3.57
231913HR7
50/50
3.57
232917OH NUG6
50/50
22.79
232915OH NUG4
50/50
22.739
232919VN10
50/50
7.274
233920W3-032A-CTG1
50/50
5.347
233921W3-032A-STG1
50/50
3.211
232901NORTHST
50/50
21.47
232900DEMECSMY
50/50
23.708
232910NRG_G1
50/50
22.038
233998TM1NIN_3.36
Solar/Wind Harmer
3.095
232404W1-003 C
Solar/Wind Harmer
2.446
232428Y3-058 C
Solar/Wind Harmer
2.038
965821AG1-450 GEN
Solar/Wind Harmer
12.714
971195AH1-057 GEN
Solar/Wind Harmer
2.673
232426Y1-080 FULL
Solar/Wind Harmer
0.467
970277AG2-181 GEN
Solar/Wind Harmer
12.245
233964AF2-378 GEN
Solar/Wind Harmer
0.312
232434Z2-077 GEN
Solar/Wind Harmer
0.611
972177AH1-672 GEN
Solar/Wind Harmer
32.705
233954AC2-188 GEN
Solar/Wind Harmer
2.73
233950AC2-186 GEN
Solar/Wind Harmer
1.365
233972AC1-094 C
Solar/Wind Harmer
1.607
234012AE2-112_GEN
Solar/Wind Harmer
5.507
232422X3-066 FULL
Solar/Wind Harmer
0.597
233930AB2-032 GEN
Solar/Wind Harmer
1.98
233915AB1-141 GEN
Solar/Wind Harmer
2.353
231918WEST 1
Adder
7.666
231917EM10
Adder
5.324
228206SHRMN CT
Adder
24.266
228732V1-021 C
Adder
0.274
945431AF1-208 GEN
Solar/Wind Harmer
12.256
970997AG2-616 GEN
Solar/Wind Harmer
13.466
228351V2-046C
Solar/Wind Harmer
2.8
230511AF1-262
Solar/Wind Harmer
0.254
228728W1-130C
Solar/Wind Harmer
0.915
230434AG1-499 GEN
Solar/Wind Harmer
0.778
218660EHAMPSOLAR C
Solar/Wind Harmer
0.201
219686LUMSOLAR_N C
Solar/Wind Harmer
0.232
219287REEVESEAST C
Solar/Wind Harmer
1.542
219258KINSLEYDEP C
Solar/Wind Harmer
0.367
219904AC1-010 C
Solar/Wind Harmer
0.408
207487AE2-000G4
Solar/Wind Harmer
32.091
219907AC1-030 C
Solar/Wind Harmer
0.14
20720728JCB_W1-129
Solar/Wind Harmer
0.299
207522AF2-254 C
Solar/Wind Harmer
1.437
219304NAMERICA C
Solar/Wind Harmer
0.298
219222BRL12CT2
Adder
8.563
207445AB1-138_GEN
Solar/Wind Harmer
0.555
20628028LAKEHURS
Adder
1.8
963711AG1-223 GEN
Solar/Wind Harmer
1.351
20714828MDF_W3-079
Solar/Wind Harmer
0.279
213611FALLS1-3
Adder
3.036
207454AA2-184 E
Solar/Wind Harmer
0.857
20715228NPK_W1-113
Solar/Wind Harmer
0.361
20742028HF_AC1-207
Solar/Wind Harmer
0.654
219680HOPEWELLV C1
Solar/Wind Harmer
0.059
20635828PARLN1&2
Adder
5.668
217197RE CRAN C
Solar/Wind Harmer
0.407
20635028RRCT1&2
Adder
8.692
20635128RRCT3&4
Adder
8.39
213560DLW11-12
Adder
1.868
218428ETC SOLAR C
Solar/Wind Harmer
0.025
217213AMBOY SO C
Solar/Wind Harmer
0.089
972275AH1-722 GEN
Adder
21.736
218449LINSOLAR C
Solar/Wind Harmer
0.674
217209CENTRL HS C
Solar/Wind Harmer
0.029
213958STHWK5-6
Adder
1.639
217121ECCF
Adder
0.277
217083KRNY_132
Adder
5.917
217208PARK ELE C
Solar/Wind Harmer
0.016
207528AF2-192 GEN
Solar/Wind Harmer
0.345
20673628F1S_V4-069
Solar/Wind Harmer
0.112
20675428EAM_W2-061
Solar/Wind Harmer
0.118
20676428JCR_X2-075
Solar/Wind Harmer
0.212
213497CHSTR7-9
Adder
1.514
213497CHSTR7-9
Adder
1.514
207439AE1-081 C O1
Solar/Wind Harmer
0.033
20675828AU_W4-064
Solar/Wind Harmer
0.092
20674328GAR_V4-001
Solar/Wind Harmer
0.057
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.239
G-007ALTFEXP_G-007A->PJM
CMTX
38.39
CBM NorthLTFEXP_CBM-N->PJM
CBM
38.598
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
2.883
BlueGrassPJM->LTFIMP_BlueG
CLTF
8.98
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
87.939
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.936
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
13.469

Details for ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line l/o PECO_P4_CHICH045_SRT-A/* $ DELCO $ PECO_P4_CHICH045 $ STBK


Base Case Flowgate

Area:PJM
Facility Description:
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line
Contingency Name:
PECO_P4_CHICH045_SRT-A/* $ DELCO $ PECO_P4_CHICH045 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.75 %
Rating:2905.0 MVA
Rating Type:B
MVA to Mitigate:3071.91
MW Contribution:10.48
Bus #Bus NameTypeMW Contribution
200205Y1-065-CTG2
50/50
11.728
232926CRISFLD1
50/50
5.088
232918OH NUG7
50/50
22.739
232905CHERITON_25
50/50
6.359
231940T-011
50/50
1.93
232899W1-062
50/50
24.717
231131BLOOM ENRGY
50/50
11.104
233987AB2-037 GEN
Solar/Wind Harmer
28.068
233901CHERRYDALE C
Solar/Wind Harmer
2.75
232408W1-005 C
Solar/Wind Harmer
2.446
232410W1-006 C
Solar/Wind Harmer
2.446
971747AH1-380 GEN
Solar/Wind Harmer
8.748
972069AH1-584 GEN
Solar/Wind Harmer
21.87
972071AH1-585 GEN
Solar/Wind Harmer
21.87
233946AB2-136 GEN
Solar/Wind Harmer
9.742
234036AF2-325 C
Solar/Wind Harmer
2.238
970545AG2-347 GEN
Solar/Wind Harmer
159.629
234041AC1-190 GEN
Solar/Wind Harmer
21.847
971149AH1-027 GEN
Solar/Wind Harmer
8.229
233939AC1-091 C
Solar/Wind Harmer
2.128
233970AC1-092 C
Solar/Wind Harmer
2.128
233984AB2-036 GEN
Solar/Wind Harmer
30.061
232424Y1-079 C
Solar/Wind Harmer
1.356
234014AF1-036_GEN
Solar/Wind Harmer
6.479
233944AB2-135 GEN
Solar/Wind Harmer
12.437
233933AB2-153 GEN
Solar/Wind Harmer
2.671
232416X2-083
Adder
1.06
228251CARLLS#4
Adder
0.901
230422AE1-104_GEN1
Solar/Wind Harmer
47.71
230425AE1-104_GEN2
Solar/Wind Harmer
47.71
230433AD2-135 GEN
Solar/Wind Harmer
0.14
228307PCLP GT
Adder
16.33
230407AD2-065 C
Solar/Wind Harmer
0.176
228304LOGAN
Adder
32.199
972233AH1-701 GEN
Adder
5.495
219921AF1-264
Solar/Wind Harmer
0.159
207500AE2-000G1
Solar/Wind Harmer
32.091
207497AE2-000G2
Solar/Wind Harmer
32.091
207507AE2-000G3
Solar/Wind Harmer
32.091
200204Y1-065-CTG1
50/50
11.728
200054ROCKSP 3
50/50
7.481
231912HR6
50/50
3.57
231913HR7
50/50
3.57
232917OH NUG6
50/50
22.79
232915OH NUG4
50/50
22.739
232919VN10
50/50
7.274
233920W3-032A-CTG1
50/50
5.347
233921W3-032A-STG1
50/50
3.211
232901NORTHST
50/50
21.47
232900DEMECSMY
50/50
23.708
232910NRG_G1
50/50
22.038
233998TM1NIN_3.36
Solar/Wind Harmer
3.095
232404W1-003 C
Solar/Wind Harmer
2.446
232428Y3-058 C
Solar/Wind Harmer
2.038
965821AG1-450 GEN
Solar/Wind Harmer
12.714
971195AH1-057 GEN
Solar/Wind Harmer
2.673
232426Y1-080 FULL
Solar/Wind Harmer
0.467
970277AG2-181 GEN
Solar/Wind Harmer
12.245
233964AF2-378 GEN
Solar/Wind Harmer
0.312
232434Z2-077 GEN
Solar/Wind Harmer
0.611
972177AH1-672 GEN
Solar/Wind Harmer
32.705
233954AC2-188 GEN
Solar/Wind Harmer
2.73
233950AC2-186 GEN
Solar/Wind Harmer
1.365
233972AC1-094 C
Solar/Wind Harmer
1.607
234012AE2-112_GEN
Solar/Wind Harmer
5.507
232422X3-066 FULL
Solar/Wind Harmer
0.597
233930AB2-032 GEN
Solar/Wind Harmer
1.98
233915AB1-141 GEN
Solar/Wind Harmer
2.353
231918WEST 1
Adder
7.666
231917EM10
Adder
5.324
228206SHRMN CT
Adder
24.266
228732V1-021 C
Adder
0.274
945431AF1-208 GEN
Solar/Wind Harmer
12.256
970997AG2-616 GEN
Solar/Wind Harmer
13.466
228351V2-046C
Solar/Wind Harmer
2.8
230511AF1-262
Solar/Wind Harmer
0.254
228728W1-130C
Solar/Wind Harmer
0.915
230434AG1-499 GEN
Solar/Wind Harmer
0.778
218660EHAMPSOLAR C
Solar/Wind Harmer
0.201
219686LUMSOLAR_N C
Solar/Wind Harmer
0.232
219287REEVESEAST C
Solar/Wind Harmer
1.542
219258KINSLEYDEP C
Solar/Wind Harmer
0.367
219904AC1-010 C
Solar/Wind Harmer
0.408
207487AE2-000G4
Solar/Wind Harmer
32.091
219907AC1-030 C
Solar/Wind Harmer
0.14
20720728JCB_W1-129
Solar/Wind Harmer
0.299
207522AF2-254 C
Solar/Wind Harmer
1.437
219304NAMERICA C
Solar/Wind Harmer
0.298
219222BRL12CT2
Adder
8.563
207445AB1-138_GEN
Solar/Wind Harmer
0.555
20628028LAKEHURS
Adder
1.8
963711AG1-223 GEN
Solar/Wind Harmer
1.351
20714828MDF_W3-079
Solar/Wind Harmer
0.279
213611FALLS1-3
Adder
3.036
207454AA2-184 E
Solar/Wind Harmer
0.857
20715228NPK_W1-113
Solar/Wind Harmer
0.361
20742028HF_AC1-207
Solar/Wind Harmer
0.654
219680HOPEWELLV C1
Solar/Wind Harmer
0.059
20635828PARLN1&2
Adder
5.668
217197RE CRAN C
Solar/Wind Harmer
0.407
20635028RRCT1&2
Adder
8.692
20635128RRCT3&4
Adder
8.39
213560DLW11-12
Adder
1.868
218428ETC SOLAR C
Solar/Wind Harmer
0.025
200203Y1-065-STG
50/50
20.337
200055ROCKSP 4
50/50
7.324
231914HR8
50/50
5.425
231911HR5
50/50
3.57
232907VN8
50/50
77.96
232914OH NUG3
50/50
22.892
232916OH NUG5
50/50
22.892
232921TASLEY2G
50/50
13.379
234034AF2-060
50/50
4.578
233900O-025 C
50/50
3.051
232911NRG_G2
50/50
1.205
233996TM1833_GEN
Solar/Wind Harmer
3.095
233997TMININ_4.2
Solar/Wind Harmer
3.095
233940AF2-379 C
Solar/Wind Harmer
0.456
232406W1-004 FULL
Solar/Wind Harmer
2.446
233994AC2-023 GEN
Solar/Wind Harmer
6.565
972073AH1-586 GEN
Solar/Wind Harmer
22.888
960671AF2-358 GEN
Solar/Wind Harmer
43.736
234015AF2-250 C
Solar/Wind Harmer
0.294
233990AG1-397 GEN
Solar/Wind Harmer
2.801
972133AH1-634 GEN
Solar/Wind Harmer
24.186
232417X3-008 C
Solar/Wind Harmer
4.88
233952AC2-187 GEN
Solar/Wind Harmer
2.73
233971AC1-093 C
Solar/Wind Harmer
1.901
970695AG2-447 GEN
Solar/Wind Harmer
8.681
233918AB1-142 GEN
Solar/Wind Harmer
2.353
233982AB2-133 GEN
Solar/Wind Harmer
11.534
972251AH1-710 GEN
Adder
96.689
228202CUMB CT
Adder
24.371
228711V2-041C
Solar/Wind Harmer
0.882
971553AH1-274 GEN
Solar/Wind Harmer
3.504
230430AE1-229_GEN
Solar/Wind Harmer
12.316
228729W2-030 C
Solar/Wind Harmer
0.799
230415AB2-049 C
Solar/Wind Harmer
0.258
228304LOGAN
Adder
28.959
219291REEVESSOUT C
Solar/Wind Harmer
0.07
219623KINSLEYBEA C
Solar/Wind Harmer
0.482
219766PARADISE C
Solar/Wind Harmer
0.339
219912AD2-042 GEN
Solar/Wind Harmer
0.82
20636028O CRK C1
Adder
7.201
219236SOUTHERNHQ C
Solar/Wind Harmer
0.068
20716028EGP_W2-019
Solar/Wind Harmer
0.466
20720828JCB_W4-025
Solar/Wind Harmer
0.455
20715028HAN_X4-015
Solar/Wind Harmer
0.299
219906AC1-017 C
Solar/Wind Harmer
0.218
219610FLORENCE C
Solar/Wind Harmer
1.329
219348LDSOLAR C
Solar/Wind Harmer
0.575
219221BRL12CT1
Adder
8.563
219223BRL12CT3
Adder
8.563
971667AH1-334 GEN
Solar/Wind Harmer
2.652
959561AF2-247 GEN
Solar/Wind Harmer
0.439
20714528FRN_Y2-051
Solar/Wind Harmer
0.269
219727YARDVSOLFA C
Solar/Wind Harmer
0.769
20720528MAN_W1-024
Solar/Wind Harmer
0.214
20716228APLW2-078
Solar/Wind Harmer
0.741
219276PARKLANDSO C
Solar/Wind Harmer
0.376
200052ROCKSP 1
50/50
7.407
200053ROCKSP 2
50/50
7.249
232912OH NUG1
50/50
22.892
232913OH NUG2
50/50
22.586
232904IR4
50/50
209.292
232920IR10
50/50
8.18
232616GEN FOOD
50/50
0.421
232813VAUGHN
50/50
1.507
233923SMA
Solar/Wind Harmer
11.346
233990AG1-397 GEN
Solar/Wind Harmer
0.135
232432Z2-076 GEN
Solar/Wind Harmer
0.322
234033AF1-007_GEN
Solar/Wind Harmer
57.043
233955AB2-172 GEN
Solar/Wind Harmer
12.2
233973AC2-185 C
Solar/Wind Harmer
8.755
231906DC3 NUG
Adder
33.599
231902DC CT7
Adder
26.861
231907DC10
Adder
8.388
233968AD2-076_GEN
Solar/Wind Harmer
15.873
970597AG2-380 GEN
Solar/Wind Harmer
9.967
232436AB1-176 C
Solar/Wind Harmer
0.547
971983AH1-536 GEN
Solar/Wind Harmer
17.77
231919CHRIST1
Adder
10.079
231920CHRIST2
Adder
9.855
233935AB2-179 C
Solar/Wind Harmer
5.699
970453AG2-297 GEN
Solar/Wind Harmer
4.117
228260V4-054C
Solar/Wind Harmer
1.467
228309CCLP NUG
Adder
36.401
228309CCLP NUG
Adder
34.625
972141AH1-641 GEN
Solar/Wind Harmer
4.04
964001AG1-254 GEN
Solar/Wind Harmer
2.833
227927V4-067C
Solar/Wind Harmer
0.274
967451AG2-055 C O1
Solar/Wind Harmer
140.57
219918AC2-009 C
Solar/Wind Harmer
0.047
20635828PARLN1&2
Adder
2.567
20635928PARLN3&4
Adder
2.567
219612MATRIX C
Solar/Wind Harmer
0.139
218438BLK ROCK C
Solar/Wind Harmer
0.103
20635028RRCT1&2
Adder
8.828
20635128RRCT3&4
Adder
7.319
213560DLW11-12
Adder
1.868
219908AB1-139 C
Solar/Wind Harmer
0.267
219919AE1-041 FULL
Solar/Wind Harmer
0.028
219249CENTRALDIV C
Solar/Wind Harmer
0.027
217211CAMDEN ST C
Solar/Wind Harmer
0.016
213958STHWK5-6
Adder
1.639
217186ESSEX_G9
Adder
10.183
217169METRODIV C
Solar/Wind Harmer
0.025
20636128O CRK C2
Adder
6.565
20716428NHV_W2-082
Solar/Wind Harmer
1.782
963401AG1-189 GEN
Solar/Wind Harmer
1.153
963391AG1-188 GEN
Solar/Wind Harmer
1.905
219615MILLCREEK C
Solar/Wind Harmer
0.234
20628028LAKEHURS
Adder
0.91
20714928UPF_X1-085
Solar/Wind Harmer
0.388
213535CROYDN11
Adder
9.544
219114HARTZY_C
Solar/Wind Harmer
0.716
20720628TIN_W1-124
Solar/Wind Harmer
0.854
20641628MLH_W1-032
Solar/Wind Harmer
0.249
20716928W4-060COL
Solar/Wind Harmer
0.568
219817TRENTONSOL C
Solar/Wind Harmer
0.867
924131AB2-057 GEN
Solar/Wind Harmer
0.75
218440SUMMTASSOC C
Solar/Wind Harmer
0.091
218418LINDEN_G5
Adder
11.824
218419LINDEN_G6
Adder
11.824
972260AH1-715 GEN1
Adder
9.468
219036LINDEN_G7
Adder
11.214
219035LINDEN_G8
Adder
11.054
972261AH1-715 GEN2
Adder
10.735
217081WEATEXAS C
Solar/Wind Harmer
0.057
217202FBANKSOLAR C
Solar/Wind Harmer
0.048
217201HACKENSOLA C
Solar/Wind Harmer
0.047
972237AH1-703 GEN
Adder
6.451
217206BARNGR HS C
Solar/Wind Harmer
0.02
217086KRNY_131
Adder
5.929
217083KRNY_132
Adder
5.879
20673828FLE_V3-070
Solar/Wind Harmer
0.288
207442AE1-156 GEN
Solar/Wind Harmer
0.463
20676128MHD_W3-029
Solar/Wind Harmer
0.297
217204WCALDSOLAR C
Solar/Wind Harmer
0.046
20671828STAW2-080
Solar/Wind Harmer
0.063
213587EDDYSTN3
Adder
44.399
213589EDDYSTN4
Adder
44.374
20674528F3S_W2-016
Solar/Wind Harmer
0.783
20676228FRD_X1-012
Solar/Wind Harmer
0.317
228754AB1-001 C
Solar/Wind Harmer
0.192
971535AH1-265 GEN
Solar/Wind Harmer
5.823
971011AG2-627 GEN
Solar/Wind Harmer
10.481
219137THOSOLAR C
Solar/Wind Harmer
1.455
219272CLEANLIGHT C
Solar/Wind Harmer
0.209
219688LUMSOLAR_S C
Solar/Wind Harmer
0.228
219914AD2-027 C
Solar/Wind Harmer
0.619
20717128DIX_Z2-102
Solar/Wind Harmer
1.32
20715728PEM_W1-119
Solar/Wind Harmer
0.533
20715828PEM_W1-120
Solar/Wind Harmer
0.533
970025AG2-016 GEN
Solar/Wind Harmer
2.819
971189AH1-054 GEN
Solar/Wind Harmer
1.156
207459AE1-142 C O1
Solar/Wind Harmer
1.025
219607WPEMNERT C
Solar/Wind Harmer
0.402
219224BRL12CT4
Adder
8.563
214067T20SOLAR
Solar/Wind Harmer
0.217
213611FALLS1-3
Adder
3.036
213611FALLS1-3
Adder
3.036
20714328BYD_X4-031
Solar/Wind Harmer
0.246
20714428HOW_X1-037
Solar/Wind Harmer
1.07
971521AH1-258 GEN
Solar/Wind Harmer
2.251
20720428HOL_W1-112
Solar/Wind Harmer
0.285
219620RIDERU C
Solar/Wind Harmer
0.044
20635928PARLN3&4
Adder
5.668
218455CINNBAY_CGEN
Adder
1.325
213561DLWR9-10
Adder
2.443
213561DLWR9-10
Adder
1.868
218526CNTRALGAS2 C
Solar/Wind Harmer
0.264
218524CNTRALGAS1 C
Solar/Wind Harmer
0.264
218404KENILWRTH C
Adder
0.844
20675528CPH_W2-050
Solar/Wind Harmer
0.296
213957STHWK3-4
Adder
1.64
213957STHWK3-4
Adder
1.64
217167KRNY_14
Adder
5.917
217086KRNY_131
Adder
5.867
217147KRNY_1212
Adder
5.628
217147KRNY_1212
Adder
5.527
217146KRNY_1234
Adder
5.515
217146KRNY_1234
Adder
5.477
213942SCHUYLKILL
Adder
2.109
213942SCHUYLKILL
Adder
1.613
20676328BVR_Y1-020
Solar/Wind Harmer
0.18
207511W3-106 GEN
Solar/Wind Harmer
0.354
207530AG1-191 GEN
Solar/Wind Harmer
0.729
966261AG1-495 GEN
Solar/Wind Harmer
0.941
20674828DL_W4-046
Solar/Wind Harmer
0.32
217194REDH C
Solar/Wind Harmer
0.313
20673728F2S_V4-070
Solar/Wind Harmer
0.112
213497CHSTR7-9
Adder
1.514
20676728BRNX1-095
Solar/Wind Harmer
0.104
20674628WNG_W3-110
Solar/Wind Harmer
0.218
207510AF2-138 C
Solar/Wind Harmer
0.956
217213AMBOY SO C
Solar/Wind Harmer
0.089
972275AH1-722 GEN
Adder
21.736
218449LINSOLAR C
Solar/Wind Harmer
0.674
217209CENTRL HS C
Solar/Wind Harmer
0.029
213958STHWK5-6
Adder
1.639
217121ECCF
Adder
0.277
217083KRNY_132
Adder
5.917
217208PARK ELE C
Solar/Wind Harmer
0.016
207528AF2-192 GEN
Solar/Wind Harmer
0.345
20673628F1S_V4-069
Solar/Wind Harmer
0.112
20675428EAM_W2-061
Solar/Wind Harmer
0.118
20676428JCR_X2-075
Solar/Wind Harmer
0.212
213497CHSTR7-9
Adder
1.514
213497CHSTR7-9
Adder
1.514
207439AE1-081 C O1
Solar/Wind Harmer
0.033
20675828AU_W4-064
Solar/Wind Harmer
0.092
20674328GAR_V4-001
Solar/Wind Harmer
0.057
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.239
G-007ALTFEXP_G-007A->PJM
CMTX
38.39
CBM NorthLTFEXP_CBM-N->PJM
CBM
38.598
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
2.883
BlueGrassPJM->LTFIMP_BlueG
CLTF
8.98
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
87.939
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.936
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
13.469

Details for ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line l/o DPL_P7_1_DBL_6NC_SRT-A


Base Case Flowgate

Area:PJM
Facility Description:
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line
Contingency Name:
DPL_P7_1_DBL_6NC_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:105.74 %
Rating:2905.0 MVA
Rating Type:B
MVA to Mitigate:3071.72
MW Contribution:9.18
Bus #Bus NameTypeMW Contribution
200052ROCKSP 1
50/50
7.46
200053ROCKSP 2
50/50
7.3
231505HR4
50/50
5.496
233955AB2-172 GEN
Solar/Wind Harmer
12.734
233923SMA
Solar/Wind Harmer
11.815
232912OH NUG1
Adder
22.46
232913OH NUG2
Adder
22.161
233990AG1-397 GEN
Solar/Wind Harmer
0.14
231919CHRIST1
Adder
11.219
231920CHRIST2
Adder
10.97
232432Z2-076 GEN
Solar/Wind Harmer
0.335
232920IR10
Adder
8.016
234033AF1-007_GEN
Solar/Wind Harmer
59.302
232904IR4
Adder
205.046
231906DC3 NUG
Adder
35.476
231902DC CT7
Adder
28.361
231907DC10
Adder
8.856
200205Y1-065-CTG2
50/50
11.811
231900EM5
50/50
12.878
232416X2-083
50/50
1.222
231908HR1
50/50
3.631
231910HR3
50/50
3.631
231909HR2
50/50
3.625
233987AB2-037 GEN
Solar/Wind Harmer
29.385
233946AB2-136 GEN
Solar/Wind Harmer
10.164
234036AF2-325 C
Solar/Wind Harmer
2.335
234041AC1-190 GEN
Solar/Wind Harmer
22.802
232926CRISFLD1
Adder
4.993
232408W1-005 C
Solar/Wind Harmer
2.547
232410W1-006 C
Solar/Wind Harmer
2.547
233901CHERRYDALE C
Solar/Wind Harmer
2.863
232918OH NUG7
Adder
22.31
232905CHERITON_25
Adder
6.239
971747AH1-380 GEN
Solar/Wind Harmer
9.107
972069AH1-584 GEN
Solar/Wind Harmer
22.766
972071AH1-585 GEN
Solar/Wind Harmer
22.766
231131BLOOM ENRGY
Adder
11.067
231940T-011
Adder
1.893
970545AG2-347 GEN
Solar/Wind Harmer
165.949
233984AB2-036 GEN
Solar/Wind Harmer
31.518
200204Y1-065-CTG1
50/50
11.811
200054ROCKSP 3
50/50
7.534
231912HR6
50/50
3.699
231913HR7
50/50
3.699
232919VN10
50/50
7.585
231917EM10
Adder
6
965821AG1-450 GEN
Solar/Wind Harmer
13.26
232426Y1-080 FULL
Solar/Wind Harmer
0.487
970277AG2-181 GEN
Solar/Wind Harmer
12.771
233964AF2-378 GEN
Solar/Wind Harmer
0.325
233998TM1NIN_3.36
Solar/Wind Harmer
3.223
232428Y3-058 C
Solar/Wind Harmer
2.123
232404W1-003 C
Solar/Wind Harmer
2.547
232917OH NUG6
Adder
22.36
232915OH NUG4
Adder
22.31
971195AH1-057 GEN
Solar/Wind Harmer
2.783
232434Z2-077 GEN
Solar/Wind Harmer
0.635
231918WEST 1
Adder
8.509
972177AH1-672 GEN
Solar/Wind Harmer
33.97
233954AC2-188 GEN
Solar/Wind Harmer
2.838
233950AC2-186 GEN
Solar/Wind Harmer
1.419
232901NORTHST
Adder
20.929
234012AE2-112_GEN
Solar/Wind Harmer
5.78
232900DEMECSMY
Adder
23.12
232422X3-066 FULL
Solar/Wind Harmer
0.627
232910NRG_G1
Adder
21.626
233972AC1-094 C
Solar/Wind Harmer
1.659
233930AB2-032 GEN
Solar/Wind Harmer
2.081
233915AB1-141 GEN
Solar/Wind Harmer
2.472
228206SHRMN CT
Adder
22.551
228732V1-021 C
Adder
0.256
945431AF1-208 GEN
Solar/Wind Harmer
11.082
970997AG2-616 GEN
Solar/Wind Harmer
12.084
228728W1-130C
Solar/Wind Harmer
0.832
230511AF1-262
Solar/Wind Harmer
0.229
228351V2-046C
Solar/Wind Harmer
2.487
230434AG1-499 GEN
Solar/Wind Harmer
0.688
218660EHAMPSOLAR C
Solar/Wind Harmer
0.186
219686LUMSOLAR_N C
Solar/Wind Harmer
0.215
219287REEVESEAST C
Solar/Wind Harmer
1.425
219258KINSLEYDEP C
Solar/Wind Harmer
0.314
232424Y1-079 C
Solar/Wind Harmer
1.422
971149AH1-027 GEN
Solar/Wind Harmer
8.512
234014AF1-036_GEN
Solar/Wind Harmer
6.8
232899W1-062
Adder
24.104
233939AC1-091 C
Solar/Wind Harmer
2.197
233970AC1-092 C
Solar/Wind Harmer
2.197
233933AB2-153 GEN
Solar/Wind Harmer
2.807
233944AB2-135 GEN
Solar/Wind Harmer
13.043
230422AE1-104_GEN1
Solar/Wind Harmer
44.537
230425AE1-104_GEN2
Solar/Wind Harmer
44.537
228251CARLLS#4
Adder
0.821
230433AD2-135 GEN
Solar/Wind Harmer
0.129
230407AD2-065 C
Solar/Wind Harmer
0.162
228307PCLP GT
Adder
14.03
228304LOGAN
Adder
27.338
972233AH1-701 GEN
Adder
4.636
219921AF1-264
Solar/Wind Harmer
0.141
207500AE2-000G1
Solar/Wind Harmer
30.224
207497AE2-000G2
Solar/Wind Harmer
30.224
207507AE2-000G3
Solar/Wind Harmer
30.224
20636128O CRK C2
Adder
6.183
963401AG1-189 GEN
Solar/Wind Harmer
1.086
20716428NHV_W2-082
Solar/Wind Harmer
1.669
963391AG1-188 GEN
Solar/Wind Harmer
1.794
20628028LAKEHURS
Adder
0.858
20714928UPF_X1-085
Solar/Wind Harmer
0.365
219615MILLCREEK C
Solar/Wind Harmer
0.211
213535CROYDN11
Adder
8.692
20720628TIN_W1-124
Solar/Wind Harmer
0.809
20641628MLH_W1-032
Solar/Wind Harmer
0.237
219114HARTZY_C
Solar/Wind Harmer
0.662
20716928W4-060COL
Solar/Wind Harmer
0.539
219817TRENTONSOL C
Solar/Wind Harmer
0.821
924131AB2-057 GEN
Solar/Wind Harmer
0.71
218440SUMMTASSOC C
Solar/Wind Harmer
0.087
218418LINDEN_G5
Adder
11.232
218419LINDEN_G6
Adder
11.232
972260AH1-715 GEN1
Adder
8.994
219036LINDEN_G7
Adder
10.657
219035LINDEN_G8
Adder
10.505
972261AH1-715 GEN2
Adder
10.202
213589EDDYSTN4
Adder
47.992
213587EDDYSTN3
Adder
47.987
217081WEATEXAS C
Solar/Wind Harmer
0.054
217202FBANKSOLAR C
Solar/Wind Harmer
0.046
217201HACKENSOLA C
Solar/Wind Harmer
0.044
972237AH1-703 GEN
Adder
6.134
217206BARNGR HS C
Solar/Wind Harmer
0.019
217086KRNY_131
Adder
5.638
217083KRNY_132
Adder
5.591
20673828FLE_V3-070
Solar/Wind Harmer
0.273
207442AE1-156 GEN
Solar/Wind Harmer
0.441
20676128MHD_W3-029
Solar/Wind Harmer
0.283
217204WCALDSOLAR C
Solar/Wind Harmer
0.044
20671828STAW2-080
Solar/Wind Harmer
0.06
20674528F3S_W2-016
Solar/Wind Harmer
0.745
20676228FRD_X1-012
Solar/Wind Harmer
0.302
233968AD2-076_GEN
Solar/Wind Harmer
16.66
970597AG2-380 GEN
Solar/Wind Harmer
10.461
232813VAUGHN
Adder
1.478
232436AB1-176 C
Solar/Wind Harmer
0.574
233973AC2-185 C
Solar/Wind Harmer
9.037
971983AH1-536 GEN
Solar/Wind Harmer
18.675
233935AB2-179 C
Solar/Wind Harmer
6.037
970453AG2-297 GEN
Solar/Wind Harmer
3.855
228260V4-054C
Solar/Wind Harmer
1.337
227927V4-067C
Solar/Wind Harmer
0.256
228754AB1-001 C
Solar/Wind Harmer
0.179
972141AH1-641 GEN
Solar/Wind Harmer
3.625
228309CCLP NUG
Adder
32.285
228309CCLP NUG
Adder
30.71
971535AH1-265 GEN
Solar/Wind Harmer
5.308
964001AG1-254 GEN
Solar/Wind Harmer
2.515
971011AG2-627 GEN
Solar/Wind Harmer
9.181
219272CLEANLIGHT C
Solar/Wind Harmer
0.193
219688LUMSOLAR_S C
Solar/Wind Harmer
0.21
219137THOSOLAR C
Solar/Wind Harmer
1.209
20717128DIX_Z2-102
Solar/Wind Harmer
1.236
970025AG2-016 GEN
Solar/Wind Harmer
2.656
20715728PEM_W1-119
Solar/Wind Harmer
0.5
20715828PEM_W1-120
Solar/Wind Harmer
0.5
971189AH1-054 GEN
Solar/Wind Harmer
1.087
219914AD2-027 C
Solar/Wind Harmer
0.548
207459AE1-142 C O1
Solar/Wind Harmer
0.967
219607WPEMNERT C
Solar/Wind Harmer
0.366
219224BRL12CT4
Adder
7.787
20714328BYD_X4-031
Solar/Wind Harmer
0.233
20714428HOW_X1-037
Solar/Wind Harmer
1.014
214067T20SOLAR
Solar/Wind Harmer
0.2
213611FALLS1-3
Adder
2.791
213611FALLS1-3
Adder
2.791
971521AH1-258 GEN
Solar/Wind Harmer
2.134
20720428HOL_W1-112
Solar/Wind Harmer
0.27
219620RIDERU C
Solar/Wind Harmer
0.042
20635928PARLN3&4
Adder
5.378
218455CINNBAY_CGEN
Adder
1.255
213561DLWR9-10
Adder
2.334
213561DLWR9-10
Adder
1.785
218526CNTRALGAS2 C
Solar/Wind Harmer
0.251
218524CNTRALGAS1 C
Solar/Wind Harmer
0.251
213957STHWK3-4
Adder
1.659
213957STHWK3-4
Adder
1.659
213942SCHUYLKILL
Adder
2.148
213942SCHUYLKILL
Adder
1.643
218404KENILWRTH C
Adder
0.803
20675528CPH_W2-050
Solar/Wind Harmer
0.281
217167KRNY_14
Adder
5.626
217086KRNY_131
Adder
5.579
217147KRNY_1212
Adder
5.352
217147KRNY_1212
Adder
5.256
217146KRNY_1234
Adder
5.244
217146KRNY_1234
Adder
5.208
20676328BVR_Y1-020
Solar/Wind Harmer
0.171
207511W3-106 GEN
Solar/Wind Harmer
0.337
207530AG1-191 GEN
Solar/Wind Harmer
0.694
966261AG1-495 GEN
Solar/Wind Harmer
0.895
207487AE2-000G4
Solar/Wind Harmer
30.224
219904AC1-010 C
Solar/Wind Harmer
0.358
20720728JCB_W1-129
Solar/Wind Harmer
0.28
207522AF2-254 C
Solar/Wind Harmer
1.346
219907AC1-030 C
Solar/Wind Harmer
0.125
207445AB1-138_GEN
Solar/Wind Harmer
0.523
20628028LAKEHURS
Adder
1.697
219304NAMERICA C
Solar/Wind Harmer
0.271
219222BRL12CT2
Adder
7.787
963711AG1-223 GEN
Solar/Wind Harmer
1.276
20714828MDF_W3-079
Solar/Wind Harmer
0.264
207454AA2-184 E
Solar/Wind Harmer
0.812
213611FALLS1-3
Adder
2.791
20715228NPK_W1-113
Solar/Wind Harmer
0.343
20742028HF_AC1-207
Solar/Wind Harmer
0.622
219680HOPEWELLV C1
Solar/Wind Harmer
0.055
20635828PARLN1&2
Adder
5.378
217197RE CRAN C
Solar/Wind Harmer
0.383
20635028RRCT1&2
Adder
8.251
20635128RRCT3&4
Adder
7.964
213560DLW11-12
Adder
1.785
218428ETC SOLAR C
Solar/Wind Harmer
0.024
217213AMBOY SO C
Solar/Wind Harmer
0.084
972275AH1-722 GEN
Adder
20.649
213958STHWK5-6
Adder
1.659
218449LINSOLAR C
Solar/Wind Harmer
0.641
213497CHSTR7-9
Adder
1.642
213497CHSTR7-9
Adder
1.642
217209CENTRL HS C
Solar/Wind Harmer
0.028
217121ECCF
Adder
0.263
217083KRNY_132
Adder
5.626
217208PARK ELE C
Solar/Wind Harmer
0.015
207528AF2-192 GEN
Solar/Wind Harmer
0.328
20673628F1S_V4-069
Solar/Wind Harmer
0.106
20675428EAM_W2-061
Solar/Wind Harmer
0.112
20676428JCR_X2-075
Solar/Wind Harmer
0.201
207439AE1-081 C O1
Solar/Wind Harmer
0.031
20675828AU_W4-064
Solar/Wind Harmer
0.087
20674328GAR_V4-001
Solar/Wind Harmer
0.054
200203Y1-065-STG
50/50
20.481
200055ROCKSP 4
50/50
7.376
231914HR8
50/50
5.621
231911HR5
50/50
3.699
232907VN8
50/50
81.306
960671AF2-358 GEN
Solar/Wind Harmer
45.614
232417X3-008 C
Solar/Wind Harmer
5.094
233996TM1833_GEN
Solar/Wind Harmer
3.223
233997TMININ_4.2
Solar/Wind Harmer
3.223
233994AC2-023 GEN
Solar/Wind Harmer
6.839
233940AF2-379 C
Solar/Wind Harmer
0.475
232406W1-004 FULL
Solar/Wind Harmer
2.547
232914OH NUG3
Adder
22.46
232916OH NUG5
Adder
22.46
232921TASLEY2G
Adder
13.127
233900O-025 C
Adder
2.994
234015AF2-250 C
Solar/Wind Harmer
0.306
972073AH1-586 GEN
Solar/Wind Harmer
23.825
233990AG1-397 GEN
Solar/Wind Harmer
2.915
972133AH1-634 GEN
Solar/Wind Harmer
25.144
233952AC2-187 GEN
Solar/Wind Harmer
2.838
233971AC1-093 C
Solar/Wind Harmer
1.962
970695AG2-447 GEN
Solar/Wind Harmer
8.96
233918AB1-142 GEN
Solar/Wind Harmer
2.472
233982AB2-133 GEN
Solar/Wind Harmer
12.115
972251AH1-710 GEN
Adder
96.659
228202CUMB CT
Adder
22.742
228711V2-041C
Solar/Wind Harmer
0.821
971553AH1-274 GEN
Solar/Wind Harmer
3.236
228729W2-030 C
Solar/Wind Harmer
0.746
230430AE1-229_GEN
Solar/Wind Harmer
11.064
230415AB2-049 C
Solar/Wind Harmer
0.236
228304LOGAN
Adder
24.587
219291REEVESSOUT C
Solar/Wind Harmer
0.064
219623KINSLEYBEA C
Solar/Wind Harmer
0.428
20636028O CRK C1
Adder
6.782
219766PARADISE C
Solar/Wind Harmer
0.297
20716028EGP_W2-019
Solar/Wind Harmer
0.436
20720828JCB_W4-025
Solar/Wind Harmer
0.426
20715028HAN_X4-015
Solar/Wind Harmer
0.28
219912AD2-042 GEN
Solar/Wind Harmer
0.726
971667AH1-334 GEN
Solar/Wind Harmer
2.499
219236SOUTHERNHQ C
Solar/Wind Harmer
0.061
219906AC1-017 C
Solar/Wind Harmer
0.197
219610FLORENCE C
Solar/Wind Harmer
1.209
219348LDSOLAR C
Solar/Wind Harmer
0.522
219221BRL12CT1
Adder
7.787
219223BRL12CT3
Adder
7.787
20714528FRN_Y2-051
Solar/Wind Harmer
0.255
959561AF2-247 GEN
Solar/Wind Harmer
0.403
20720528MAN_W1-024
Solar/Wind Harmer
0.204
20716228APLW2-078
Solar/Wind Harmer
0.705
219727YARDVSOLFA C
Solar/Wind Harmer
0.713
967451AG2-055 C O1
Solar/Wind Harmer
134.403
219276PARKLANDSO C
Solar/Wind Harmer
0.351
219918AC2-009 C
Solar/Wind Harmer
0.045
20635828PARLN1&2
Adder
2.436
20635928PARLN3&4
Adder
2.436
219612MATRIX C
Solar/Wind Harmer
0.131
218438BLK ROCK C
Solar/Wind Harmer
0.097
20635028RRCT1&2
Adder
8.379
20635128RRCT3&4
Adder
6.947
213560DLW11-12
Adder
1.785
219908AB1-139 C
Solar/Wind Harmer
0.254
219919AE1-041 FULL
Solar/Wind Harmer
0.027
219249CENTRALDIV C
Solar/Wind Harmer
0.025
213958STHWK5-6
Adder
1.659
213497CHSTR7-9
Adder
1.642
217211CAMDEN ST C
Solar/Wind Harmer
0.015
217186ESSEX_G9
Adder
9.683
217169METRODIV C
Solar/Wind Harmer
0.024
217194REDH C
Solar/Wind Harmer
0.297
20673728F2S_V4-070
Solar/Wind Harmer
0.106
20676728BRNX1-095
Solar/Wind Harmer
0.099
20674628WNG_W3-110
Solar/Wind Harmer
0.207
207510AF2-138 C
Solar/Wind Harmer
0.91
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.109
G-007ALTFEXP_G-007A->PJM
CMTX
36.44
CBM NorthLTFEXP_CBM-N->PJM
CBM
36.716
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
2.769
BlueGrassPJM->LTFIMP_BlueG
CLTF
8.625
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
83.626
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.859
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
12.936

Details for ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line l/o PECO_P2-2_CHI230B1_SRT-A/* $ DELCO $ PECO_P2-2_CHI230B1 $ B


Base Case Flowgate

Area:PJM
Facility Description:
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line
Contingency Name:
PECO_P2-2_CHI230B1_SRT-A/* $ DELCO $ PECO_P2-2_CHI230B1 $ B
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:105.74 %
Rating:2905.0 MVA
Rating Type:B
MVA to Mitigate:3071.68
MW Contribution:10.48
Bus #Bus NameTypeMW Contribution
200052ROCKSP 1
50/50
7.407
200053ROCKSP 2
50/50
7.249
232912OH NUG1
50/50
22.892
232913OH NUG2
50/50
22.586
232904IR4
50/50
209.292
232920IR10
50/50
8.18
232616GEN FOOD
50/50
0.421
232813VAUGHN
50/50
1.507
233923SMA
Solar/Wind Harmer
11.346
233990AG1-397 GEN
Solar/Wind Harmer
0.135
232432Z2-076 GEN
Solar/Wind Harmer
0.322
234033AF1-007_GEN
Solar/Wind Harmer
57.043
233955AB2-172 GEN
Solar/Wind Harmer
12.2
233973AC2-185 C
Solar/Wind Harmer
8.755
231906DC3 NUG
Adder
33.599
231902DC CT7
Adder
26.861
231907DC10
Adder
8.388
233968AD2-076_GEN
Solar/Wind Harmer
15.873
970597AG2-380 GEN
Solar/Wind Harmer
9.967
232436AB1-176 C
Solar/Wind Harmer
0.547
971983AH1-536 GEN
Solar/Wind Harmer
17.77
231919CHRIST1
Adder
10.079
231920CHRIST2
Adder
9.855
233935AB2-179 C
Solar/Wind Harmer
5.699
970453AG2-297 GEN
Solar/Wind Harmer
4.117
228260V4-054C
Solar/Wind Harmer
1.467
228309CCLP NUG
Adder
36.401
228309CCLP NUG
Adder
34.625
972141AH1-641 GEN
Solar/Wind Harmer
4.04
964001AG1-254 GEN
Solar/Wind Harmer
2.833
227927V4-067C
Solar/Wind Harmer
0.274
228754AB1-001 C
Solar/Wind Harmer
0.192
971535AH1-265 GEN
Solar/Wind Harmer
5.823
971011AG2-627 GEN
Solar/Wind Harmer
10.481
219137THOSOLAR C
Solar/Wind Harmer
1.455
219272CLEANLIGHT C
Solar/Wind Harmer
0.209
219688LUMSOLAR_S C
Solar/Wind Harmer
0.228
219914AD2-027 C
Solar/Wind Harmer
0.619
20717128DIX_Z2-102
Solar/Wind Harmer
1.32
20715728PEM_W1-119
Solar/Wind Harmer
0.533
20715828PEM_W1-120
Solar/Wind Harmer
0.533
970025AG2-016 GEN
Solar/Wind Harmer
2.819
971189AH1-054 GEN
Solar/Wind Harmer
1.156
207459AE1-142 C O1
Solar/Wind Harmer
1.025
219607WPEMNERT C
Solar/Wind Harmer
0.402
219224BRL12CT4
Adder
8.563
214067T20SOLAR
Solar/Wind Harmer
0.217
213611FALLS1-3
Adder
3.036
213611FALLS1-3
Adder
3.036
20714328BYD_X4-031
Solar/Wind Harmer
0.246
20714428HOW_X1-037
Solar/Wind Harmer
1.07
971521AH1-258 GEN
Solar/Wind Harmer
2.251
20720428HOL_W1-112
Solar/Wind Harmer
0.285
219620RIDERU C
Solar/Wind Harmer
0.044
20635928PARLN3&4
Adder
5.668
218455CINNBAY_CGEN
Adder
1.325
213561DLWR9-10
Adder
2.443
213561DLWR9-10
Adder
1.868
218526CNTRALGAS2 C
Solar/Wind Harmer
0.264
218524CNTRALGAS1 C
Solar/Wind Harmer
0.264
218404KENILWRTH C
Adder
0.844
200204Y1-065-CTG1
50/50
11.728
200054ROCKSP 3
50/50
7.481
231912HR6
50/50
3.57
231913HR7
50/50
3.57
232917OH NUG6
50/50
22.79
232915OH NUG4
50/50
22.739
232919VN10
50/50
7.274
233920W3-032A-CTG1
50/50
5.347
233921W3-032A-STG1
50/50
3.211
232901NORTHST
50/50
21.47
232900DEMECSMY
50/50
23.708
232910NRG_G1
50/50
22.038
233998TM1NIN_3.36
Solar/Wind Harmer
3.095
232404W1-003 C
Solar/Wind Harmer
2.446
232428Y3-058 C
Solar/Wind Harmer
2.038
965821AG1-450 GEN
Solar/Wind Harmer
12.714
971195AH1-057 GEN
Solar/Wind Harmer
2.673
232426Y1-080 FULL
Solar/Wind Harmer
0.467
970277AG2-181 GEN
Solar/Wind Harmer
12.245
233964AF2-378 GEN
Solar/Wind Harmer
0.312
232434Z2-077 GEN
Solar/Wind Harmer
0.611
972177AH1-672 GEN
Solar/Wind Harmer
32.705
233954AC2-188 GEN
Solar/Wind Harmer
2.73
233950AC2-186 GEN
Solar/Wind Harmer
1.365
233972AC1-094 C
Solar/Wind Harmer
1.607
234012AE2-112_GEN
Solar/Wind Harmer
5.507
232422X3-066 FULL
Solar/Wind Harmer
0.597
233930AB2-032 GEN
Solar/Wind Harmer
1.98
233915AB1-141 GEN
Solar/Wind Harmer
2.353
231918WEST 1
Adder
7.666
231917EM10
Adder
5.324
228206SHRMN CT
Adder
24.266
228732V1-021 C
Adder
0.274
945431AF1-208 GEN
Solar/Wind Harmer
12.256
970997AG2-616 GEN
Solar/Wind Harmer
13.466
228351V2-046C
Solar/Wind Harmer
2.8
230511AF1-262
Solar/Wind Harmer
0.254
228728W1-130C
Solar/Wind Harmer
0.915
230434AG1-499 GEN
Solar/Wind Harmer
0.778
218660EHAMPSOLAR C
Solar/Wind Harmer
0.201
219686LUMSOLAR_N C
Solar/Wind Harmer
0.232
219287REEVESEAST C
Solar/Wind Harmer
1.542
219258KINSLEYDEP C
Solar/Wind Harmer
0.367
219904AC1-010 C
Solar/Wind Harmer
0.408
207487AE2-000G4
Solar/Wind Harmer
32.091
219907AC1-030 C
Solar/Wind Harmer
0.14
20720728JCB_W1-129
Solar/Wind Harmer
0.299
207522AF2-254 C
Solar/Wind Harmer
1.437
219304NAMERICA C
Solar/Wind Harmer
0.298
219222BRL12CT2
Adder
8.563
207445AB1-138_GEN
Solar/Wind Harmer
0.555
20628028LAKEHURS
Adder
1.8
963711AG1-223 GEN
Solar/Wind Harmer
1.351
20714828MDF_W3-079
Solar/Wind Harmer
0.279
213611FALLS1-3
Adder
3.036
207454AA2-184 E
Solar/Wind Harmer
0.857
20715228NPK_W1-113
Solar/Wind Harmer
0.361
20742028HF_AC1-207
Solar/Wind Harmer
0.654
219680HOPEWELLV C1
Solar/Wind Harmer
0.059
20635828PARLN1&2
Adder
5.668
217197RE CRAN C
Solar/Wind Harmer
0.407
20635028RRCT1&2
Adder
8.692
20635128RRCT3&4
Adder
8.39
213560DLW11-12
Adder
1.868
218428ETC SOLAR C
Solar/Wind Harmer
0.025
217213AMBOY SO C
Solar/Wind Harmer
0.089
972275AH1-722 GEN
Adder
21.736
218449LINSOLAR C
Solar/Wind Harmer
0.674
217209CENTRL HS C
Solar/Wind Harmer
0.029
213958STHWK5-6
Adder
1.639
217121ECCF
Adder
0.277
217083KRNY_132
Adder
5.917
217208PARK ELE C
Solar/Wind Harmer
0.016
207528AF2-192 GEN
Solar/Wind Harmer
0.345
20673628F1S_V4-069
Solar/Wind Harmer
0.112
20675428EAM_W2-061
Solar/Wind Harmer
0.118
20676428JCR_X2-075
Solar/Wind Harmer
0.212
213497CHSTR7-9
Adder
1.514
213497CHSTR7-9
Adder
1.514
207439AE1-081 C O1
Solar/Wind Harmer
0.033
200203Y1-065-STG
50/50
20.337
200055ROCKSP 4
50/50
7.324
231914HR8
50/50
5.425
231911HR5
50/50
3.57
232907VN8
50/50
77.96
232914OH NUG3
50/50
22.892
232916OH NUG5
50/50
22.892
232921TASLEY2G
50/50
13.379
234034AF2-060
50/50
4.578
233900O-025 C
50/50
3.051
232911NRG_G2
50/50
1.205
233996TM1833_GEN
Solar/Wind Harmer
3.095
233997TMININ_4.2
Solar/Wind Harmer
3.095
233940AF2-379 C
Solar/Wind Harmer
0.456
232406W1-004 FULL
Solar/Wind Harmer
2.446
233994AC2-023 GEN
Solar/Wind Harmer
6.565
972073AH1-586 GEN
Solar/Wind Harmer
22.888
960671AF2-358 GEN
Solar/Wind Harmer
43.736
234015AF2-250 C
Solar/Wind Harmer
0.294
233990AG1-397 GEN
Solar/Wind Harmer
2.801
972133AH1-634 GEN
Solar/Wind Harmer
24.186
232417X3-008 C
Solar/Wind Harmer
4.88
233952AC2-187 GEN
Solar/Wind Harmer
2.73
233971AC1-093 C
Solar/Wind Harmer
1.901
970695AG2-447 GEN
Solar/Wind Harmer
8.681
233918AB1-142 GEN
Solar/Wind Harmer
2.353
233982AB2-133 GEN
Solar/Wind Harmer
11.534
972251AH1-710 GEN
Adder
96.689
228202CUMB CT
Adder
24.371
228711V2-041C
Solar/Wind Harmer
0.882
971553AH1-274 GEN
Solar/Wind Harmer
3.504
230430AE1-229_GEN
Solar/Wind Harmer
12.316
228729W2-030 C
Solar/Wind Harmer
0.799
230415AB2-049 C
Solar/Wind Harmer
0.258
228304LOGAN
Adder
28.959
219291REEVESSOUT C
Solar/Wind Harmer
0.07
219623KINSLEYBEA C
Solar/Wind Harmer
0.482
219766PARADISE C
Solar/Wind Harmer
0.339
219912AD2-042 GEN
Solar/Wind Harmer
0.82
20636028O CRK C1
Adder
7.201
219236SOUTHERNHQ C
Solar/Wind Harmer
0.068
20716028EGP_W2-019
Solar/Wind Harmer
0.466
20720828JCB_W4-025
Solar/Wind Harmer
0.455
20715028HAN_X4-015
Solar/Wind Harmer
0.299
219906AC1-017 C
Solar/Wind Harmer
0.218
219610FLORENCE C
Solar/Wind Harmer
1.329
219348LDSOLAR C
Solar/Wind Harmer
0.575
219221BRL12CT1
Adder
8.563
219223BRL12CT3
Adder
8.563
971667AH1-334 GEN
Solar/Wind Harmer
2.652
959561AF2-247 GEN
Solar/Wind Harmer
0.439
20714528FRN_Y2-051
Solar/Wind Harmer
0.269
219727YARDVSOLFA C
Solar/Wind Harmer
0.769
20720528MAN_W1-024
Solar/Wind Harmer
0.214
20716228APLW2-078
Solar/Wind Harmer
0.741
219276PARKLANDSO C
Solar/Wind Harmer
0.376
967451AG2-055 C O1
Solar/Wind Harmer
140.57
219918AC2-009 C
Solar/Wind Harmer
0.047
20635828PARLN1&2
Adder
2.567
20635928PARLN3&4
Adder
2.567
219612MATRIX C
Solar/Wind Harmer
0.139
218438BLK ROCK C
Solar/Wind Harmer
0.103
20635028RRCT1&2
Adder
8.828
20635128RRCT3&4
Adder
7.319
213560DLW11-12
Adder
1.868
219908AB1-139 C
Solar/Wind Harmer
0.267
219919AE1-041 FULL
Solar/Wind Harmer
0.028
219249CENTRALDIV C
Solar/Wind Harmer
0.027
217211CAMDEN ST C
Solar/Wind Harmer
0.016
213958STHWK5-6
Adder
1.639
217186ESSEX_G9
Adder
10.183
217169METRODIV C
Solar/Wind Harmer
0.025
217194REDH C
Solar/Wind Harmer
0.313
20673728F2S_V4-070
Solar/Wind Harmer
0.112
213497CHSTR7-9
Adder
1.514
20676728BRNX1-095
Solar/Wind Harmer
0.104
20674628WNG_W3-110
Solar/Wind Harmer
0.218
207510AF2-138 C
Solar/Wind Harmer
0.956
200205Y1-065-CTG2
50/50
11.728
232926CRISFLD1
50/50
5.088
232918OH NUG7
50/50
22.739
232905CHERITON_25
50/50
6.359
231940T-011
50/50
1.93
232899W1-062
50/50
24.717
231131BLOOM ENRGY
50/50
11.104
233987AB2-037 GEN
Solar/Wind Harmer
28.068
233901CHERRYDALE C
Solar/Wind Harmer
2.75
232408W1-005 C
Solar/Wind Harmer
2.446
232410W1-006 C
Solar/Wind Harmer
2.446
971747AH1-380 GEN
Solar/Wind Harmer
8.748
972069AH1-584 GEN
Solar/Wind Harmer
21.87
972071AH1-585 GEN
Solar/Wind Harmer
21.87
233946AB2-136 GEN
Solar/Wind Harmer
9.742
234036AF2-325 C
Solar/Wind Harmer
2.238
970545AG2-347 GEN
Solar/Wind Harmer
159.629
234041AC1-190 GEN
Solar/Wind Harmer
21.847
971149AH1-027 GEN
Solar/Wind Harmer
8.229
233939AC1-091 C
Solar/Wind Harmer
2.128
233970AC1-092 C
Solar/Wind Harmer
2.128
233984AB2-036 GEN
Solar/Wind Harmer
30.061
232424Y1-079 C
Solar/Wind Harmer
1.356
234014AF1-036_GEN
Solar/Wind Harmer
6.479
233944AB2-135 GEN
Solar/Wind Harmer
12.437
233933AB2-153 GEN
Solar/Wind Harmer
2.671
232416X2-083
Adder
1.06
228251CARLLS#4
Adder
0.901
230422AE1-104_GEN1
Solar/Wind Harmer
47.71
230425AE1-104_GEN2
Solar/Wind Harmer
47.71
230433AD2-135 GEN
Solar/Wind Harmer
0.14
228307PCLP GT
Adder
16.33
230407AD2-065 C
Solar/Wind Harmer
0.176
228304LOGAN
Adder
32.199
972233AH1-701 GEN
Adder
5.495
219921AF1-264
Solar/Wind Harmer
0.159
207500AE2-000G1
Solar/Wind Harmer
32.091
207497AE2-000G2
Solar/Wind Harmer
32.091
207507AE2-000G3
Solar/Wind Harmer
32.091
20636128O CRK C2
Adder
6.565
20716428NHV_W2-082
Solar/Wind Harmer
1.782
963401AG1-189 GEN
Solar/Wind Harmer
1.153
963391AG1-188 GEN
Solar/Wind Harmer
1.905
219615MILLCREEK C
Solar/Wind Harmer
0.234
20628028LAKEHURS
Adder
0.91
20714928UPF_X1-085
Solar/Wind Harmer
0.388
213535CROYDN11
Adder
9.544
219114HARTZY_C
Solar/Wind Harmer
0.716
20720628TIN_W1-124
Solar/Wind Harmer
0.854
20641628MLH_W1-032
Solar/Wind Harmer
0.249
20716928W4-060COL
Solar/Wind Harmer
0.568
219817TRENTONSOL C
Solar/Wind Harmer
0.867
924131AB2-057 GEN
Solar/Wind Harmer
0.75
218440SUMMTASSOC C
Solar/Wind Harmer
0.091
218418LINDEN_G5
Adder
11.824
218419LINDEN_G6
Adder
11.824
972260AH1-715 GEN1
Adder
9.468
219036LINDEN_G7
Adder
11.214
219035LINDEN_G8
Adder
11.054
972261AH1-715 GEN2
Adder
10.735
217081WEATEXAS C
Solar/Wind Harmer
0.057
217202FBANKSOLAR C
Solar/Wind Harmer
0.048
217201HACKENSOLA C
Solar/Wind Harmer
0.047
972237AH1-703 GEN
Adder
6.451
217206BARNGR HS C
Solar/Wind Harmer
0.02
217086KRNY_131
Adder
5.929
217083KRNY_132
Adder
5.879
20673828FLE_V3-070
Solar/Wind Harmer
0.288
207442AE1-156 GEN
Solar/Wind Harmer
0.463
20676128MHD_W3-029
Solar/Wind Harmer
0.297
217204WCALDSOLAR C
Solar/Wind Harmer
0.046
20671828STAW2-080
Solar/Wind Harmer
0.063
213587EDDYSTN3
Adder
44.399
213589EDDYSTN4
Adder
44.374
20674528F3S_W2-016
Solar/Wind Harmer
0.783
20676228FRD_X1-012
Solar/Wind Harmer
0.317
20675528CPH_W2-050
Solar/Wind Harmer
0.296
213957STHWK3-4
Adder
1.64
213957STHWK3-4
Adder
1.64
217167KRNY_14
Adder
5.917
217086KRNY_131
Adder
5.867
217147KRNY_1212
Adder
5.628
217147KRNY_1212
Adder
5.527
217146KRNY_1234
Adder
5.515
217146KRNY_1234
Adder
5.477
213942SCHUYLKILL
Adder
2.109
213942SCHUYLKILL
Adder
1.613
20676328BVR_Y1-020
Solar/Wind Harmer
0.18
207511W3-106 GEN
Solar/Wind Harmer
0.354
207530AG1-191 GEN
Solar/Wind Harmer
0.729
966261AG1-495 GEN
Solar/Wind Harmer
0.941
20674828DL_W4-046
Solar/Wind Harmer
0.32
20675828AU_W4-064
Solar/Wind Harmer
0.092
20674328GAR_V4-001
Solar/Wind Harmer
0.057
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.239
G-007ALTFEXP_G-007A->PJM
CMTX
38.39
CBM NorthLTFEXP_CBM-N->PJM
CBM
38.598
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
2.883
BlueGrassPJM->LTFIMP_BlueG
CLTF
8.98
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
87.939
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.936
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
13.469

Details for ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line l/o DPL_P7_1_DBL_5NC_SRT-A


Base Case Flowgate

Area:PJM
Facility Description:
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line
Contingency Name:
DPL_P7_1_DBL_5NC_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:101.95 %
Rating:2905.0 MVA
Rating Type:B
MVA to Mitigate:2961.68
MW Contribution:9.31
Bus #Bus NameTypeMW Contribution
200205Y1-065-CTG2
50/50
11.765
232926CRISFLD1
50/50
5.143
232918OH NUG7
50/50
22.982
232905CHERITON_25
50/50
6.427
231940T-011
50/50
1.95
233987AB2-037 GEN
Solar/Wind Harmer
28.466
233946AB2-136 GEN
Solar/Wind Harmer
9.857
234036AF2-325 C
Solar/Wind Harmer
2.264
232408W1-005 C
Solar/Wind Harmer
2.473
232410W1-006 C
Solar/Wind Harmer
2.473
233901CHERRYDALE C
Solar/Wind Harmer
2.779
234041AC1-190 GEN
Solar/Wind Harmer
22.107
971747AH1-380 GEN
Solar/Wind Harmer
8.842
972069AH1-584 GEN
Solar/Wind Harmer
22.102
972071AH1-585 GEN
Solar/Wind Harmer
22.102
970545AG2-347 GEN
Solar/Wind Harmer
161.205
971149AH1-027 GEN
Solar/Wind Harmer
8.287
233984AB2-036 GEN
Solar/Wind Harmer
30.471
232424Y1-079 C
Solar/Wind Harmer
1.374
232899W1-062
Adder
23.457
233939AC1-091 C
Solar/Wind Harmer
2.141
233970AC1-092 C
Solar/Wind Harmer
2.141
234014AF1-036_GEN
Solar/Wind Harmer
6.567
231131BLOOM ENRGY
Adder
10.566
233933AB2-153 GEN
Solar/Wind Harmer
2.708
233944AB2-135 GEN
Solar/Wind Harmer
12.595
232416X2-083
Adder
1.085
230422AE1-104_GEN1
Solar/Wind Harmer
44.694
230425AE1-104_GEN2
Solar/Wind Harmer
44.694
228251CARLLS#4
Adder
0.827
230433AD2-135 GEN
Solar/Wind Harmer
0.13
200204Y1-065-CTG1
50/50
11.765
200054ROCKSP 3
50/50
7.505
231912HR6
50/50
3.599
231913HR7
50/50
3.599
232919VN10
50/50
7.358
232917OH NUG6
50/50
23.034
232915OH NUG4
50/50
22.982
233920W3-032A-CTG1
50/50
5.385
233921W3-032A-STG1
50/50
3.234
232901NORTHST
50/50
21.622
232910NRG_G1
50/50
22.255
965821AG1-450 GEN
Solar/Wind Harmer
12.861
232426Y1-080 FULL
Solar/Wind Harmer
0.472
970277AG2-181 GEN
Solar/Wind Harmer
12.387
233998TM1NIN_3.36
Solar/Wind Harmer
3.128
233964AF2-378 GEN
Solar/Wind Harmer
0.316
232404W1-003 C
Solar/Wind Harmer
2.473
232428Y3-058 C
Solar/Wind Harmer
2.06
971195AH1-057 GEN
Solar/Wind Harmer
2.701
232434Z2-077 GEN
Solar/Wind Harmer
0.617
972177AH1-672 GEN
Solar/Wind Harmer
33.009
233954AC2-188 GEN
Solar/Wind Harmer
2.756
233950AC2-186 GEN
Solar/Wind Harmer
1.378
232900DEMECSMY
Adder
22.5
233972AC1-094 C
Solar/Wind Harmer
1.617
234012AE2-112_GEN
Solar/Wind Harmer
5.582
232422X3-066 FULL
Solar/Wind Harmer
0.605
233930AB2-032 GEN
Solar/Wind Harmer
2.007
233915AB1-141 GEN
Solar/Wind Harmer
2.385
231918WEST 1
Adder
7.541
231917EM10
Adder
5.082
228206SHRMN CT
Adder
22.629
228732V1-021 C
Adder
0.257
945431AF1-208 GEN
Solar/Wind Harmer
11.172
970997AG2-616 GEN
Solar/Wind Harmer
12.199
230511AF1-262
Solar/Wind Harmer
0.231
228728W1-130C
Solar/Wind Harmer
0.839
228351V2-046C
Solar/Wind Harmer
2.515
230434AG1-499 GEN
Solar/Wind Harmer
0.697
218660EHAMPSOLAR C
Solar/Wind Harmer
0.188
219686LUMSOLAR_N C
Solar/Wind Harmer
0.217
219287REEVESEAST C
Solar/Wind Harmer
1.443
219258KINSLEYDEP C
Solar/Wind Harmer
0.322
219904AC1-010 C
Solar/Wind Harmer
0.367
207487AE2-000G4
Solar/Wind Harmer
30.496
20720728JCB_W1-129
Solar/Wind Harmer
0.283
207522AF2-254 C
Solar/Wind Harmer
1.361
219907AC1-030 C
Solar/Wind Harmer
0.128
207445AB1-138_GEN
Solar/Wind Harmer
0.529
20628028LAKEHURS
Adder
1.715
219304NAMERICA C
Solar/Wind Harmer
0.278
219222BRL12CT2
Adder
7.976
963711AG1-223 GEN
Solar/Wind Harmer
1.291
230407AD2-065 C
Solar/Wind Harmer
0.164
228307PCLP GT
Adder
14.268
228304LOGAN
Adder
27.862
972233AH1-701 GEN
Adder
4.732
219921AF1-264
Solar/Wind Harmer
0.144
207500AE2-000G1
Solar/Wind Harmer
30.496
207497AE2-000G2
Solar/Wind Harmer
30.496
207507AE2-000G3
Solar/Wind Harmer
30.496
20636128O CRK C2
Adder
6.239
963401AG1-189 GEN
Solar/Wind Harmer
1.097
20716428NHV_W2-082
Solar/Wind Harmer
1.688
963391AG1-188 GEN
Solar/Wind Harmer
1.812
219615MILLCREEK C
Solar/Wind Harmer
0.216
20628028LAKEHURS
Adder
0.867
20714928UPF_X1-085
Solar/Wind Harmer
0.369
213535CROYDN11
Adder
8.918
200052ROCKSP 1
50/50
7.431
200053ROCKSP 2
50/50
7.272
232912OH NUG1
50/50
23.137
232913OH NUG2
50/50
22.828
232920IR10
50/50
8.262
232904IR4
50/50
211.358
232616GEN FOOD
50/50
0.424
233923SMA
Solar/Wind Harmer
11.469
233955AB2-172 GEN
Solar/Wind Harmer
12.345
233990AG1-397 GEN
Solar/Wind Harmer
0.136
232432Z2-076 GEN
Solar/Wind Harmer
0.326
234033AF1-007_GEN
Solar/Wind Harmer
57.606
233973AC2-185 C
Solar/Wind Harmer
8.806
232813VAUGHN
Adder
1.434
233968AD2-076_GEN
Solar/Wind Harmer
16.089
970597AG2-380 GEN
Solar/Wind Harmer
10.103
231906DC3 NUG
Adder
33.933
231902DC CT7
Adder
27.128
231907DC10
Adder
8.471
232436AB1-176 C
Solar/Wind Harmer
0.555
971983AH1-536 GEN
Solar/Wind Harmer
18.016
233935AB2-179 C
Solar/Wind Harmer
5.786
231919CHRIST1
Adder
10.165
231920CHRIST2
Adder
9.939
970453AG2-297 GEN
Solar/Wind Harmer
3.862
228260V4-054C
Solar/Wind Harmer
1.347
227927V4-067C
Solar/Wind Harmer
0.257
228754AB1-001 C
Solar/Wind Harmer
0.18
972141AH1-641 GEN
Solar/Wind Harmer
3.66
228309CCLP NUG
Adder
32.643
228309CCLP NUG
Adder
31.051
971535AH1-265 GEN
Solar/Wind Harmer
5.351
964001AG1-254 GEN
Solar/Wind Harmer
2.544
971011AG2-627 GEN
Solar/Wind Harmer
9.307
219272CLEANLIGHT C
Solar/Wind Harmer
0.195
219688LUMSOLAR_S C
Solar/Wind Harmer
0.213
219137THOSOLAR C
Solar/Wind Harmer
1.242
20717128DIX_Z2-102
Solar/Wind Harmer
1.251
20715728PEM_W1-119
Solar/Wind Harmer
0.505
20715828PEM_W1-120
Solar/Wind Harmer
0.505
970025AG2-016 GEN
Solar/Wind Harmer
2.681
219914AD2-027 C
Solar/Wind Harmer
0.563
971189AH1-054 GEN
Solar/Wind Harmer
1.099
207459AE1-142 C O1
Solar/Wind Harmer
0.976
219607WPEMNERT C
Solar/Wind Harmer
0.375
219224BRL12CT4
Adder
7.976
20714328BYD_X4-031
Solar/Wind Harmer
0.236
20714428HOW_X1-037
Solar/Wind Harmer
1.026
214067T20SOLAR
Solar/Wind Harmer
0.205
213611FALLS1-3
Adder
2.867
213611FALLS1-3
Adder
2.867
971521AH1-258 GEN
Solar/Wind Harmer
2.161
20720428HOL_W1-112
Solar/Wind Harmer
0.274
219620RIDERU C
Solar/Wind Harmer
0.042
20635928PARLN3&4
Adder
5.455
213561DLWR9-10
Adder
2.491
213561DLWR9-10
Adder
1.905
218455CINNBAY_CGEN
Adder
1.276
213957STHWK3-4
Adder
1.828
213957STHWK3-4
Adder
1.828
213942SCHUYLKILL
Adder
2.375
213942SCHUYLKILL
Adder
1.816
218526CNTRALGAS2 C
Solar/Wind Harmer
0.255
218524CNTRALGAS1 C
Solar/Wind Harmer
0.255
218404KENILWRTH C
Adder
0.818
20675528CPH_W2-050
Solar/Wind Harmer
0.288
217167KRNY_14
Adder
5.73
217086KRNY_131
Adder
5.681
217147KRNY_1212
Adder
5.45
217147KRNY_1212
Adder
5.353
217146KRNY_1234
Adder
5.34
217146KRNY_1234
Adder
5.304
20676328BVR_Y1-020
Solar/Wind Harmer
0.175
207511W3-106 GEN
Solar/Wind Harmer
0.344
966261AG1-495 GEN
Solar/Wind Harmer
0.919
207530AG1-191 GEN
Solar/Wind Harmer
0.71
20720628TIN_W1-124
Solar/Wind Harmer
0.819
219114HARTZY_C
Solar/Wind Harmer
0.676
20641628MLH_W1-032
Solar/Wind Harmer
0.24
20716928W4-060COL
Solar/Wind Harmer
0.546
219817TRENTONSOL C
Solar/Wind Harmer
0.835
213589EDDYSTN4
Adder
54.988
213587EDDYSTN3
Adder
54.962
924131AB2-057 GEN
Solar/Wind Harmer
0.722
218440SUMMTASSOC C
Solar/Wind Harmer
0.088
218418LINDEN_G5
Adder
11.424
218419LINDEN_G6
Adder
11.424
972260AH1-715 GEN1
Adder
9.148
219036LINDEN_G7
Adder
10.844
219035LINDEN_G8
Adder
10.689
972261AH1-715 GEN2
Adder
10.38
217081WEATEXAS C
Solar/Wind Harmer
0.055
217202FBANKSOLAR C
Solar/Wind Harmer
0.046
217201HACKENSOLA C
Solar/Wind Harmer
0.045
972237AH1-703 GEN
Adder
6.247
217206BARNGR HS C
Solar/Wind Harmer
0.019
20673828FLE_V3-070
Solar/Wind Harmer
0.279
217086KRNY_131
Adder
5.742
217083KRNY_132
Adder
5.693
207442AE1-156 GEN
Solar/Wind Harmer
0.45
20676128MHD_W3-029
Solar/Wind Harmer
0.289
217204WCALDSOLAR C
Solar/Wind Harmer
0.044
20671828STAW2-080
Solar/Wind Harmer
0.061
20674528F3S_W2-016
Solar/Wind Harmer
0.764
20676228FRD_X1-012
Solar/Wind Harmer
0.308
20714828MDF_W3-079
Solar/Wind Harmer
0.267
213611FALLS1-3
Adder
2.867
207454AA2-184 E
Solar/Wind Harmer
0.822
20715228NPK_W1-113
Solar/Wind Harmer
0.348
20742028HF_AC1-207
Solar/Wind Harmer
0.629
219680HOPEWELLV C1
Solar/Wind Harmer
0.056
20635828PARLN1&2
Adder
5.455
217197RE CRAN C
Solar/Wind Harmer
0.39
213560DLW11-12
Adder
1.905
213497CHSTR7-9
Adder
1.89
213497CHSTR7-9
Adder
1.89
20635028RRCT1&2
Adder
8.373
20635128RRCT3&4
Adder
8.082
213958STHWK5-6
Adder
1.828
218428ETC SOLAR C
Solar/Wind Harmer
0.024
217213AMBOY SO C
Solar/Wind Harmer
0.086
972275AH1-722 GEN
Adder
21.002
218449LINSOLAR C
Solar/Wind Harmer
0.652
217209CENTRL HS C
Solar/Wind Harmer
0.028
217121ECCF
Adder
0.268
217083KRNY_132
Adder
5.73
217208PARK ELE C
Solar/Wind Harmer
0.016
207528AF2-192 GEN
Solar/Wind Harmer
0.335
20673628F1S_V4-069
Solar/Wind Harmer
0.109
20675428EAM_W2-061
Solar/Wind Harmer
0.114
20676428JCR_X2-075
Solar/Wind Harmer
0.205
207439AE1-081 C O1
Solar/Wind Harmer
0.032
20675828AU_W4-064
Solar/Wind Harmer
0.089
20674328GAR_V4-001
Solar/Wind Harmer
0.056
200203Y1-065-STG
50/50
20.401
200055ROCKSP 4
50/50
7.347
231914HR8
50/50
5.47
231911HR5
50/50
3.599
232907VN8
50/50
78.872
232914OH NUG3
50/50
23.137
232916OH NUG5
50/50
23.137
232921TASLEY2G
50/50
13.522
234034AF2-060
50/50
4.627
233900O-025 C
50/50
3.084
232911NRG_G2
50/50
1.217
960671AF2-358 GEN
Solar/Wind Harmer
44.242
233996TM1833_GEN
Solar/Wind Harmer
3.128
233997TMININ_4.2
Solar/Wind Harmer
3.128
233940AF2-379 C
Solar/Wind Harmer
0.461
233994AC2-023 GEN
Solar/Wind Harmer
6.637
232406W1-004 FULL
Solar/Wind Harmer
2.473
232417X3-008 C
Solar/Wind Harmer
4.938
972073AH1-586 GEN
Solar/Wind Harmer
23.13
234015AF2-250 C
Solar/Wind Harmer
0.297
233990AG1-397 GEN
Solar/Wind Harmer
2.83
972133AH1-634 GEN
Solar/Wind Harmer
24.425
233952AC2-187 GEN
Solar/Wind Harmer
2.756
233971AC1-093 C
Solar/Wind Harmer
1.912
970695AG2-447 GEN
Solar/Wind Harmer
8.731
233918AB1-142 GEN
Solar/Wind Harmer
2.385
233982AB2-133 GEN
Solar/Wind Harmer
11.688
972251AH1-710 GEN
Adder
95.495
228202CUMB CT
Adder
22.803
228711V2-041C
Solar/Wind Harmer
0.824
971553AH1-274 GEN
Solar/Wind Harmer
3.251
228729W2-030 C
Solar/Wind Harmer
0.749
230430AE1-229_GEN
Solar/Wind Harmer
11.169
230415AB2-049 C
Solar/Wind Harmer
0.238
228304LOGAN
Adder
25.059
219291REEVESSOUT C
Solar/Wind Harmer
0.065
219623KINSLEYBEA C
Solar/Wind Harmer
0.437
219766PARADISE C
Solar/Wind Harmer
0.305
20636028O CRK C1
Adder
6.843
20716028EGP_W2-019
Solar/Wind Harmer
0.441
20720828JCB_W4-025
Solar/Wind Harmer
0.431
20715028HAN_X4-015
Solar/Wind Harmer
0.283
219912AD2-042 GEN
Solar/Wind Harmer
0.746
219236SOUTHERNHQ C
Solar/Wind Harmer
0.062
971667AH1-334 GEN
Solar/Wind Harmer
2.525
219906AC1-017 C
Solar/Wind Harmer
0.202
219610FLORENCE C
Solar/Wind Harmer
1.238
219348LDSOLAR C
Solar/Wind Harmer
0.535
219221BRL12CT1
Adder
7.976
219223BRL12CT3
Adder
7.976
20714528FRN_Y2-051
Solar/Wind Harmer
0.257
959561AF2-247 GEN
Solar/Wind Harmer
0.412
20720528MAN_W1-024
Solar/Wind Harmer
0.206
20716228APLW2-078
Solar/Wind Harmer
0.714
219727YARDVSOLFA C
Solar/Wind Harmer
0.728
967451AG2-055 C O1
Solar/Wind Harmer
135.92
219276PARKLANDSO C
Solar/Wind Harmer
0.358
219918AC2-009 C
Solar/Wind Harmer
0.046
20635828PARLN1&2
Adder
2.471
20635928PARLN3&4
Adder
2.471
219612MATRIX C
Solar/Wind Harmer
0.134
218438BLK ROCK C
Solar/Wind Harmer
0.099
213560DLW11-12
Adder
1.905
213497CHSTR7-9
Adder
1.89
20635028RRCT1&2
Adder
8.504
20635128RRCT3&4
Adder
7.05
213958STHWK5-6
Adder
1.828
219908AB1-139 C
Solar/Wind Harmer
0.258
219919AE1-041 FULL
Solar/Wind Harmer
0.027
219249CENTRALDIV C
Solar/Wind Harmer
0.026
217211CAMDEN ST C
Solar/Wind Harmer
0.015
217186ESSEX_G9
Adder
9.861
217169METRODIV C
Solar/Wind Harmer
0.025
217194REDH C
Solar/Wind Harmer
0.303
20673728F2S_V4-070
Solar/Wind Harmer
0.109
20676728BRNX1-095
Solar/Wind Harmer
0.101
20674628WNG_W3-110
Solar/Wind Harmer
0.212
207510AF2-138 C
Solar/Wind Harmer
0.93
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.113
G-007ALTFEXP_G-007A->PJM
CMTX
36.981
CBM NorthLTFEXP_CBM-N->PJM
CBM
37.578
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
2.769
BlueGrassPJM->LTFIMP_BlueG
CLTF
8.623
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
85.125
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.86
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
12.934

Details for WANEETA2-N PHILA 230.0 kV Ckt 1 line l/o PECO_P4_CHICH045_SRT-A/* $ DELCO $ PECO_P4_CHICH045 $ STBK


Base Case Flowgate

Area:PECO
Facility Description:
WANEETA2-N PHILA 230.0 kV Ckt 1 line
Contingency Name:
PECO_P4_CHICH045_SRT-A/* $ DELCO $ PECO_P4_CHICH045 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.0 %
Rating:621.0 MVA
Rating Type:B
MVA to Mitigate:645.83
MW Contribution:4.11
Bus #Bus NameTypeMW Contribution
219126CAMDEN_CTG
50/50
0.727
219267WHEELBRDEPTF
50/50
0.102
219240MANTUACREK E
50/50
0.332
219726BAT.STORG E
50/50
0.163
213535CROYDN11
50/50
6.488
972233AH1-701 GEN
50/50
2.603
228304LOGAN
50/50
14.752
213619FORDBCT1
50/50
1.293
213620FORDBCT2
50/50
1.293
228307PCLP GT
50/50
7.178
219921AF1-264
Solar/Wind Harmer
0.105
219615MILLCREEK C
Solar/Wind Harmer
0.154
230407AD2-065 C
Solar/Wind Harmer
0.065
230433AD2-135 GEN
Solar/Wind Harmer
0.049
228251CARLLS#4
Adder
0.299
230422AE1-104_GEN1
Solar/Wind Harmer
14.25
230425AE1-104_GEN2
Solar/Wind Harmer
14.25
219114HARTZY_C
Solar/Wind Harmer
0.34
20716428NHV_W2-082
Solar/Wind Harmer
0.636
20714928UPF_X1-085
Solar/Wind Harmer
0.126
207500AE2-000G1
Solar/Wind Harmer
9.417
207497AE2-000G2
Solar/Wind Harmer
9.417
207507AE2-000G3
Solar/Wind Harmer
9.417
20636128O CRK C2
Adder
1.926
963401AG1-189 GEN
Solar/Wind Harmer
0.341
963391AG1-188 GEN
Solar/Wind Harmer
0.567
20628028LAKEHURS
Adder
0.272
213919RICHMD92
50/50
0.588
219124CAMDEN_STG
50/50
0.592
219286CAMD CO RR
50/50
0.204
230406ST-CC
50/50
2.382
230404GT1-CC
50/50
1.602
213542CROYDN42
50/50
0.355
219221BRL12CT1
50/50
5.636
219223BRL12CT3
50/50
5.636
219924AG1-130 C
50/50
0.264
228304LOGAN
50/50
13.268
213621FORDBST1
50/50
1.796
213616FORDACT1
50/50
1.288
219912AD2-042 GEN
Solar/Wind Harmer
0.623
219766PARADISE C
Solar/Wind Harmer
0.235
219236SOUTHERNHQ C
Solar/Wind Harmer
0.048
219623KINSLEYBEA C
Solar/Wind Harmer
0.302
219906AC1-017 C
Solar/Wind Harmer
0.144
219610FLORENCE C
Solar/Wind Harmer
0.824
219348LDSOLAR C
Solar/Wind Harmer
0.356
219291REEVESSOUT C
Solar/Wind Harmer
0.032
230430AE1-229_GEN
Solar/Wind Harmer
4.395
230415AB2-049 C
Solar/Wind Harmer
0.094
959561AF2-247 GEN
Solar/Wind Harmer
0.241
971553AH1-274 GEN
Solar/Wind Harmer
1.097
228711V2-041C
Solar/Wind Harmer
0.261
228202CUMB CT
Adder
7.101
228729W2-030 C
Solar/Wind Harmer
0.242
219727YARDVSOLFA C
Solar/Wind Harmer
0.348
20716028EGP_W2-019
Solar/Wind Harmer
0.167
20720828JCB_W4-025
Solar/Wind Harmer
0.163
20715028HAN_X4-015
Solar/Wind Harmer
0.107
219276PARKLANDSO C
Solar/Wind Harmer
0.15
20636028O CRK C1
Adder
2.113
971667AH1-334 GEN
Solar/Wind Harmer
0.796
972251AH1-710 GEN
Adder
13.19
20714528FRN_Y2-051
Solar/Wind Harmer
0.076
219612MATRIX C
Solar/Wind Harmer
0.043
218438BLK ROCK C
Solar/Wind Harmer
0.032
219229EAGLE PT ST
50/50
0.365
219231EAGLE PT CT2
50/50
0.721
230405GT2-CC
50/50
1.609
213537CROYDN21
50/50
0.355
213538CROYDN22
50/50
0.355
213539CROYDN31
50/50
0.355
213540CROYDN32
50/50
0.348
219224BRL12CT4
50/50
5.636
219914AD2-027 C
Solar/Wind Harmer
0.47
219137THOSOLAR C
Solar/Wind Harmer
0.804
219607WPEMNERT C
Solar/Wind Harmer
0.249
219272CLEANLIGHT C
Solar/Wind Harmer
0.104
219688LUMSOLAR_S C
Solar/Wind Harmer
0.112
971011AG2-627 GEN
Solar/Wind Harmer
4.109
964001AG1-254 GEN
Solar/Wind Harmer
1.05
228309CCLP NUG
Adder
13.316
228309CCLP NUG
Adder
12.666
972141AH1-641 GEN
Solar/Wind Harmer
1.439
971535AH1-265 GEN
Solar/Wind Harmer
2.068
214067T20SOLAR
Solar/Wind Harmer
0.123
213611FALLS1-3
Adder
1.714
213611FALLS1-3
Adder
1.714
228260V4-054C
Solar/Wind Harmer
0.487
970453AG2-297 GEN
Solar/Wind Harmer
1.167
228754AB1-001 C
Solar/Wind Harmer
0.059
227927V4-067C
Solar/Wind Harmer
0.082
20717128DIX_Z2-102
Solar/Wind Harmer
0.464
20715728PEM_W1-119
Solar/Wind Harmer
0.185
20715828PEM_W1-120
Solar/Wind Harmer
0.185
971189AH1-054 GEN
Solar/Wind Harmer
0.365
970025AG2-016 GEN
Solar/Wind Harmer
0.838
207459AE1-142 C O1
Solar/Wind Harmer
0.301
231919CHRIST1
Adder
1.094
231920CHRIST2
Adder
1.069
20714328BYD_X4-031
Solar/Wind Harmer
0.066
213918RICHMD91
50/50
0.588
219230EAGLE PT CT1
50/50
0.721
219235Y2-105
50/50
0.261
213536CROYDN12
50/50
2.989
213541CROYDN41
50/50
0.355
219222BRL12CT2
50/50
5.636
213618FORDAST1
50/50
1.79
213617FORDACT2
50/50
1.288
219904AC1-010 C
Solar/Wind Harmer
0.283
219907AC1-030 C
Solar/Wind Harmer
0.1
219258KINSLEYDEP C
Solar/Wind Harmer
0.23
219304NAMERICA C
Solar/Wind Harmer
0.185
230434AG1-499 GEN
Solar/Wind Harmer
0.311
218660EHAMPSOLAR C
Solar/Wind Harmer
0.094
219686LUMSOLAR_N C
Solar/Wind Harmer
0.107
219287REEVESEAST C
Solar/Wind Harmer
0.709
228351V2-046C
Solar/Wind Harmer
1.041
970997AG2-616 GEN
Solar/Wind Harmer
4.797
230511AF1-262
Solar/Wind Harmer
0.091
945431AF1-208 GEN
Solar/Wind Harmer
4.205
213611FALLS1-3
Adder
1.714
228728W1-130C
Solar/Wind Harmer
0.318
228206SHRMN CT
Adder
7.276
228732V1-021 C
Adder
0.08
20720728JCB_W1-129
Solar/Wind Harmer
0.107
207522AF2-254 C
Solar/Wind Harmer
0.51
207487AE2-000G4
Solar/Wind Harmer
9.417
207445AB1-138_GEN
Solar/Wind Harmer
0.166
20628028LAKEHURS
Adder
0.537
963711AG1-223 GEN
Solar/Wind Harmer
0.384
20714828MDF_W3-079
Solar/Wind Harmer
0.079
231917EM10
Adder
0.61
217197RE CRAN C
Solar/Wind Harmer
0.126
231918WEST 1
Adder
0.81
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.313
G-007ALTFEXP_G-007A->PJM
CMTX
8.873
CBM NorthLTFEXP_CBM-N->PJM
CBM
6.478
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.29
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.904
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
17.755
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.188
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.352

Details for WANEETA2-N PHILA 230.0 kV Ckt 1 line l/o PECO_P4_CHICH195_SRT-A/* $ DELCO $ PECO_P4_CHICH195 $ STBK


Base Case Flowgate

Area:PECO
Facility Description:
WANEETA2-N PHILA 230.0 kV Ckt 1 line
Contingency Name:
PECO_P4_CHICH195_SRT-A/* $ DELCO $ PECO_P4_CHICH195 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.99 %
Rating:621.0 MVA
Rating Type:B
MVA to Mitigate:645.76
MW Contribution:4.11
Bus #Bus NameTypeMW Contribution
219126CAMDEN_CTG
50/50
0.727
219267WHEELBRDEPTF
50/50
0.102
219240MANTUACREK E
50/50
0.332
219726BAT.STORG E
50/50
0.163
213535CROYDN11
50/50
6.488
972233AH1-701 GEN
50/50
2.603
228304LOGAN
50/50
14.752
213619FORDBCT1
50/50
1.293
213620FORDBCT2
50/50
1.293
228307PCLP GT
50/50
7.178
219921AF1-264
Solar/Wind Harmer
0.105
219615MILLCREEK C
Solar/Wind Harmer
0.154
230407AD2-065 C
Solar/Wind Harmer
0.065
230433AD2-135 GEN
Solar/Wind Harmer
0.049
228251CARLLS#4
Adder
0.299
230422AE1-104_GEN1
Solar/Wind Harmer
14.25
230425AE1-104_GEN2
Solar/Wind Harmer
14.25
219114HARTZY_C
Solar/Wind Harmer
0.34
20716428NHV_W2-082
Solar/Wind Harmer
0.636
20714928UPF_X1-085
Solar/Wind Harmer
0.126
207500AE2-000G1
Solar/Wind Harmer
9.417
207497AE2-000G2
Solar/Wind Harmer
9.417
207507AE2-000G3
Solar/Wind Harmer
9.417
20636128O CRK C2
Adder
1.926
963401AG1-189 GEN
Solar/Wind Harmer
0.341
963391AG1-188 GEN
Solar/Wind Harmer
0.567
20628028LAKEHURS
Adder
0.272
213919RICHMD92
50/50
0.588
219124CAMDEN_STG
50/50
0.592
219286CAMD CO RR
50/50
0.204
230406ST-CC
50/50
2.382
230404GT1-CC
50/50
1.602
213542CROYDN42
50/50
0.355
219221BRL12CT1
50/50
5.636
219223BRL12CT3
50/50
5.636
219924AG1-130 C
50/50
0.264
228304LOGAN
50/50
13.268
213621FORDBST1
50/50
1.796
213616FORDACT1
50/50
1.288
219912AD2-042 GEN
Solar/Wind Harmer
0.623
219766PARADISE C
Solar/Wind Harmer
0.235
219236SOUTHERNHQ C
Solar/Wind Harmer
0.048
219623KINSLEYBEA C
Solar/Wind Harmer
0.302
219906AC1-017 C
Solar/Wind Harmer
0.144
219610FLORENCE C
Solar/Wind Harmer
0.824
219348LDSOLAR C
Solar/Wind Harmer
0.356
219291REEVESSOUT C
Solar/Wind Harmer
0.032
230430AE1-229_GEN
Solar/Wind Harmer
4.395
230415AB2-049 C
Solar/Wind Harmer
0.094
959561AF2-247 GEN
Solar/Wind Harmer
0.241
971553AH1-274 GEN
Solar/Wind Harmer
1.097
228711V2-041C
Solar/Wind Harmer
0.261
228202CUMB CT
Adder
7.101
228729W2-030 C
Solar/Wind Harmer
0.242
219727YARDVSOLFA C
Solar/Wind Harmer
0.348
20716028EGP_W2-019
Solar/Wind Harmer
0.167
20720828JCB_W4-025
Solar/Wind Harmer
0.163
20715028HAN_X4-015
Solar/Wind Harmer
0.107
219276PARKLANDSO C
Solar/Wind Harmer
0.15
20636028O CRK C1
Adder
2.113
971667AH1-334 GEN
Solar/Wind Harmer
0.796
972251AH1-710 GEN
Adder
13.19
20714528FRN_Y2-051
Solar/Wind Harmer
0.076
219612MATRIX C
Solar/Wind Harmer
0.043
218438BLK ROCK C
Solar/Wind Harmer
0.032
219229EAGLE PT ST
50/50
0.365
219231EAGLE PT CT2
50/50
0.721
230405GT2-CC
50/50
1.609
213537CROYDN21
50/50
0.355
213538CROYDN22
50/50
0.355
213539CROYDN31
50/50
0.355
213540CROYDN32
50/50
0.348
219224BRL12CT4
50/50
5.636
219914AD2-027 C
Solar/Wind Harmer
0.47
219137THOSOLAR C
Solar/Wind Harmer
0.804
219607WPEMNERT C
Solar/Wind Harmer
0.249
219272CLEANLIGHT C
Solar/Wind Harmer
0.104
219688LUMSOLAR_S C
Solar/Wind Harmer
0.112
971011AG2-627 GEN
Solar/Wind Harmer
4.109
964001AG1-254 GEN
Solar/Wind Harmer
1.05
228309CCLP NUG
Adder
13.316
228309CCLP NUG
Adder
12.666
972141AH1-641 GEN
Solar/Wind Harmer
1.439
971535AH1-265 GEN
Solar/Wind Harmer
2.068
214067T20SOLAR
Solar/Wind Harmer
0.123
213611FALLS1-3
Adder
1.714
213611FALLS1-3
Adder
1.714
228260V4-054C
Solar/Wind Harmer
0.487
970453AG2-297 GEN
Solar/Wind Harmer
1.167
228754AB1-001 C
Solar/Wind Harmer
0.059
227927V4-067C
Solar/Wind Harmer
0.082
20717128DIX_Z2-102
Solar/Wind Harmer
0.464
20715728PEM_W1-119
Solar/Wind Harmer
0.185
20715828PEM_W1-120
Solar/Wind Harmer
0.185
971189AH1-054 GEN
Solar/Wind Harmer
0.365
970025AG2-016 GEN
Solar/Wind Harmer
0.838
207459AE1-142 C O1
Solar/Wind Harmer
0.301
231919CHRIST1
Adder
1.094
231920CHRIST2
Adder
1.069
20714328BYD_X4-031
Solar/Wind Harmer
0.066
213918RICHMD91
50/50
0.588
219230EAGLE PT CT1
50/50
0.721
219235Y2-105
50/50
0.261
213536CROYDN12
50/50
2.989
213541CROYDN41
50/50
0.355
219222BRL12CT2
50/50
5.636
213618FORDAST1
50/50
1.79
213617FORDACT2
50/50
1.288
219904AC1-010 C
Solar/Wind Harmer
0.283
219907AC1-030 C
Solar/Wind Harmer
0.1
219258KINSLEYDEP C
Solar/Wind Harmer
0.23
219304NAMERICA C
Solar/Wind Harmer
0.185
230434AG1-499 GEN
Solar/Wind Harmer
0.311
218660EHAMPSOLAR C
Solar/Wind Harmer
0.094
219686LUMSOLAR_N C
Solar/Wind Harmer
0.107
219287REEVESEAST C
Solar/Wind Harmer
0.709
228351V2-046C
Solar/Wind Harmer
1.041
970997AG2-616 GEN
Solar/Wind Harmer
4.797
230511AF1-262
Solar/Wind Harmer
0.091
945431AF1-208 GEN
Solar/Wind Harmer
4.205
213611FALLS1-3
Adder
1.714
228728W1-130C
Solar/Wind Harmer
0.318
228206SHRMN CT
Adder
7.276
228732V1-021 C
Adder
0.08
20720728JCB_W1-129
Solar/Wind Harmer
0.107
207522AF2-254 C
Solar/Wind Harmer
0.51
207487AE2-000G4
Solar/Wind Harmer
9.417
207445AB1-138_GEN
Solar/Wind Harmer
0.166
20628028LAKEHURS
Adder
0.537
963711AG1-223 GEN
Solar/Wind Harmer
0.384
20714828MDF_W3-079
Solar/Wind Harmer
0.079
231917EM10
Adder
0.61
217197RE CRAN C
Solar/Wind Harmer
0.126
231918WEST 1
Adder
0.81
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.313
G-007ALTFEXP_G-007A->PJM
CMTX
8.873
CBM NorthLTFEXP_CBM-N->PJM
CBM
6.478
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.29
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.904
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
17.755
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.188
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.352

Details for WANEETA2-N PHILA 230.0 kV Ckt 1 line l/o PECO_P4_CHICH435_SRT-A/* $ DELCO $ PECO_P4_CHICH435 $ STBK


Base Case Flowgate

Area:PECO
Facility Description:
WANEETA2-N PHILA 230.0 kV Ckt 1 line
Contingency Name:
PECO_P4_CHICH435_SRT-A/* $ DELCO $ PECO_P4_CHICH435 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.99 %
Rating:621.0 MVA
Rating Type:B
MVA to Mitigate:645.76
MW Contribution:4.11
Bus #Bus NameTypeMW Contribution
213919RICHMD92
50/50
0.588
219124CAMDEN_STG
50/50
0.592
219286CAMD CO RR
50/50
0.204
230406ST-CC
50/50
2.382
230404GT1-CC
50/50
1.602
213542CROYDN42
50/50
0.355
219221BRL12CT1
50/50
5.636
219223BRL12CT3
50/50
5.636
219924AG1-130 C
50/50
0.264
228304LOGAN
50/50
13.269
213621FORDBST1
50/50
1.796
219126CAMDEN_CTG
50/50
0.727
219267WHEELBRDEPTF
50/50
0.102
219240MANTUACREK E
50/50
0.332
219726BAT.STORG E
50/50
0.163
213535CROYDN11
50/50
6.488
972233AH1-701 GEN
50/50
2.603
228304LOGAN
50/50
14.753
213619FORDBCT1
50/50
1.293
213620FORDBCT2
50/50
1.293
228307PCLP GT
50/50
7.178
219921AF1-264
Solar/Wind Harmer
0.105
219615MILLCREEK C
Solar/Wind Harmer
0.154
230407AD2-065 C
Solar/Wind Harmer
0.065
230433AD2-135 GEN
Solar/Wind Harmer
0.049
228251CARLLS#4
Adder
0.299
230422AE1-104_GEN1
Solar/Wind Harmer
14.251
230425AE1-104_GEN2
Solar/Wind Harmer
14.251
219114HARTZY_C
Solar/Wind Harmer
0.34
20716428NHV_W2-082
Solar/Wind Harmer
0.636
20714928UPF_X1-085
Solar/Wind Harmer
0.126
207500AE2-000G1
Solar/Wind Harmer
9.417
207497AE2-000G2
Solar/Wind Harmer
9.417
207507AE2-000G3
Solar/Wind Harmer
9.417
20636128O CRK C2
Adder
1.927
963401AG1-189 GEN
Solar/Wind Harmer
0.341
963391AG1-188 GEN
Solar/Wind Harmer
0.567
20628028LAKEHURS
Adder
0.272
213616FORDACT1
50/50
1.288
219912AD2-042 GEN
Solar/Wind Harmer
0.623
219766PARADISE C
Solar/Wind Harmer
0.235
219236SOUTHERNHQ C
Solar/Wind Harmer
0.048
219623KINSLEYBEA C
Solar/Wind Harmer
0.302
219906AC1-017 C
Solar/Wind Harmer
0.144
219610FLORENCE C
Solar/Wind Harmer
0.824
219348LDSOLAR C
Solar/Wind Harmer
0.356
219291REEVESSOUT C
Solar/Wind Harmer
0.032
230430AE1-229_GEN
Solar/Wind Harmer
4.395
230415AB2-049 C
Solar/Wind Harmer
0.094
959561AF2-247 GEN
Solar/Wind Harmer
0.241
971553AH1-274 GEN
Solar/Wind Harmer
1.097
228711V2-041C
Solar/Wind Harmer
0.261
228202CUMB CT
Adder
7.101
228729W2-030 C
Solar/Wind Harmer
0.242
219727YARDVSOLFA C
Solar/Wind Harmer
0.348
20716028EGP_W2-019
Solar/Wind Harmer
0.167
20720828JCB_W4-025
Solar/Wind Harmer
0.163
20715028HAN_X4-015
Solar/Wind Harmer
0.107
219276PARKLANDSO C
Solar/Wind Harmer
0.15
20636028O CRK C1
Adder
2.113
971667AH1-334 GEN
Solar/Wind Harmer
0.796
972251AH1-710 GEN
Adder
13.19
20714528FRN_Y2-051
Solar/Wind Harmer
0.076
219612MATRIX C
Solar/Wind Harmer
0.043
218438BLK ROCK C
Solar/Wind Harmer
0.032
219229EAGLE PT ST
50/50
0.365
219231EAGLE PT CT2
50/50
0.721
230405GT2-CC
50/50
1.609
213537CROYDN21
50/50
0.355
213538CROYDN22
50/50
0.355
213539CROYDN31
50/50
0.355
213540CROYDN32
50/50
0.348
219224BRL12CT4
50/50
5.636
219914AD2-027 C
Solar/Wind Harmer
0.47
219137THOSOLAR C
Solar/Wind Harmer
0.804
219607WPEMNERT C
Solar/Wind Harmer
0.249
219272CLEANLIGHT C
Solar/Wind Harmer
0.104
219688LUMSOLAR_S C
Solar/Wind Harmer
0.112
971011AG2-627 GEN
Solar/Wind Harmer
4.109
964001AG1-254 GEN
Solar/Wind Harmer
1.05
228309CCLP NUG
Adder
13.316
228309CCLP NUG
Adder
12.667
972141AH1-641 GEN
Solar/Wind Harmer
1.439
971535AH1-265 GEN
Solar/Wind Harmer
2.068
214067T20SOLAR
Solar/Wind Harmer
0.123
213611FALLS1-3
Adder
1.714
213611FALLS1-3
Adder
1.714
228260V4-054C
Solar/Wind Harmer
0.487
970453AG2-297 GEN
Solar/Wind Harmer
1.167
228754AB1-001 C
Solar/Wind Harmer
0.059
227927V4-067C
Solar/Wind Harmer
0.082
20717128DIX_Z2-102
Solar/Wind Harmer
0.464
20715728PEM_W1-119
Solar/Wind Harmer
0.185
20715828PEM_W1-120
Solar/Wind Harmer
0.185
971189AH1-054 GEN
Solar/Wind Harmer
0.365
970025AG2-016 GEN
Solar/Wind Harmer
0.838
207459AE1-142 C O1
Solar/Wind Harmer
0.301
231919CHRIST1
Adder
1.093
231920CHRIST2
Adder
1.069
20714328BYD_X4-031
Solar/Wind Harmer
0.066
213918RICHMD91
50/50
0.588
219230EAGLE PT CT1
50/50
0.721
219235Y2-105
50/50
0.261
213536CROYDN12
50/50
2.989
213541CROYDN41
50/50
0.355
219222BRL12CT2
50/50
5.636
213618FORDAST1
50/50
1.79
213617FORDACT2
50/50
1.288
219904AC1-010 C
Solar/Wind Harmer
0.283
219907AC1-030 C
Solar/Wind Harmer
0.1
219258KINSLEYDEP C
Solar/Wind Harmer
0.23
219304NAMERICA C
Solar/Wind Harmer
0.185
230434AG1-499 GEN
Solar/Wind Harmer
0.311
218660EHAMPSOLAR C
Solar/Wind Harmer
0.094
219686LUMSOLAR_N C
Solar/Wind Harmer
0.107
219287REEVESEAST C
Solar/Wind Harmer
0.709
228351V2-046C
Solar/Wind Harmer
1.041
970997AG2-616 GEN
Solar/Wind Harmer
4.797
230511AF1-262
Solar/Wind Harmer
0.091
945431AF1-208 GEN
Solar/Wind Harmer
4.206
213611FALLS1-3
Adder
1.714
228728W1-130C
Solar/Wind Harmer
0.318
228206SHRMN CT
Adder
7.276
228732V1-021 C
Adder
0.08
20720728JCB_W1-129
Solar/Wind Harmer
0.107
207522AF2-254 C
Solar/Wind Harmer
0.51
207487AE2-000G4
Solar/Wind Harmer
9.417
207445AB1-138_GEN
Solar/Wind Harmer
0.166
20628028LAKEHURS
Adder
0.537
963711AG1-223 GEN
Solar/Wind Harmer
0.384
20714828MDF_W3-079
Solar/Wind Harmer
0.079
231917EM10
Adder
0.61
217197RE CRAN C
Solar/Wind Harmer
0.126
231918WEST 1
Adder
0.81
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.313
G-007ALTFEXP_G-007A->PJM
CMTX
8.873
CBM NorthLTFEXP_CBM-N->PJM
CBM
6.479
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.29
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.904
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
17.756
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.188
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.352

Details for WANEETA2-N PHILA 230.0 kV Ckt 1 line l/o PECO_P2-2_CHI230B1_SRT-A/* $ DELCO $ PECO_P2-2_CHI230B1 $ B


Base Case Flowgate

Area:PECO
Facility Description:
WANEETA2-N PHILA 230.0 kV Ckt 1 line
Contingency Name:
PECO_P2-2_CHI230B1_SRT-A/* $ DELCO $ PECO_P2-2_CHI230B1 $ B
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:103.98 %
Rating:621.0 MVA
Rating Type:B
MVA to Mitigate:645.69
MW Contribution:4.11
Bus #Bus NameTypeMW Contribution
213919RICHMD92
50/50
0.588
219124CAMDEN_STG
50/50
0.592
219286CAMD CO RR
50/50
0.204
230406ST-CC
50/50
2.382
230404GT1-CC
50/50
1.602
213542CROYDN42
50/50
0.355
219221BRL12CT1
50/50
5.636
219223BRL12CT3
50/50
5.636
219924AG1-130 C
50/50
0.264
228304LOGAN
50/50
13.268
213621FORDBST1
50/50
1.796
219126CAMDEN_CTG
50/50
0.727
219267WHEELBRDEPTF
50/50
0.102
219240MANTUACREK E
50/50
0.332
219726BAT.STORG E
50/50
0.163
213535CROYDN11
50/50
6.488
972233AH1-701 GEN
50/50
2.603
228304LOGAN
50/50
14.752
213619FORDBCT1
50/50
1.293
213620FORDBCT2
50/50
1.293
228307PCLP GT
50/50
7.178
219921AF1-264
Solar/Wind Harmer
0.105
219615MILLCREEK C
Solar/Wind Harmer
0.154
230407AD2-065 C
Solar/Wind Harmer
0.065
230433AD2-135 GEN
Solar/Wind Harmer
0.049
228251CARLLS#4
Adder
0.299
230422AE1-104_GEN1
Solar/Wind Harmer
14.25
230425AE1-104_GEN2
Solar/Wind Harmer
14.25
219114HARTZY_C
Solar/Wind Harmer
0.34
20716428NHV_W2-082
Solar/Wind Harmer
0.636
20714928UPF_X1-085
Solar/Wind Harmer
0.126
207500AE2-000G1
Solar/Wind Harmer
9.417
207497AE2-000G2
Solar/Wind Harmer
9.417
207507AE2-000G3
Solar/Wind Harmer
9.417
20636128O CRK C2
Adder
1.926
963401AG1-189 GEN
Solar/Wind Harmer
0.341
963391AG1-188 GEN
Solar/Wind Harmer
0.567
20628028LAKEHURS
Adder
0.272
219229EAGLE PT ST
50/50
0.365
219231EAGLE PT CT2
50/50
0.721
230405GT2-CC
50/50
1.609
213537CROYDN21
50/50
0.355
213538CROYDN22
50/50
0.355
213539CROYDN31
50/50
0.355
213540CROYDN32
50/50
0.348
219224BRL12CT4
50/50
5.636
219914AD2-027 C
Solar/Wind Harmer
0.47
219137THOSOLAR C
Solar/Wind Harmer
0.804
219607WPEMNERT C
Solar/Wind Harmer
0.249
219272CLEANLIGHT C
Solar/Wind Harmer
0.104
219688LUMSOLAR_S C
Solar/Wind Harmer
0.112
971011AG2-627 GEN
Solar/Wind Harmer
4.109
964001AG1-254 GEN
Solar/Wind Harmer
1.05
228309CCLP NUG
Adder
13.316
228309CCLP NUG
Adder
12.666
972141AH1-641 GEN
Solar/Wind Harmer
1.439
971535AH1-265 GEN
Solar/Wind Harmer
2.068
214067T20SOLAR
Solar/Wind Harmer
0.123
213611FALLS1-3
Adder
1.714
213611FALLS1-3
Adder
1.714
228260V4-054C
Solar/Wind Harmer
0.487
970453AG2-297 GEN
Solar/Wind Harmer
1.167
228754AB1-001 C
Solar/Wind Harmer
0.059
227927V4-067C
Solar/Wind Harmer
0.082
20717128DIX_Z2-102
Solar/Wind Harmer
0.464
20715728PEM_W1-119
Solar/Wind Harmer
0.185
20715828PEM_W1-120
Solar/Wind Harmer
0.185
971189AH1-054 GEN
Solar/Wind Harmer
0.365
970025AG2-016 GEN
Solar/Wind Harmer
0.838
207459AE1-142 C O1
Solar/Wind Harmer
0.301
231919CHRIST1
Adder
1.094
231920CHRIST2
Adder
1.069
20714328BYD_X4-031
Solar/Wind Harmer
0.066
213918RICHMD91
50/50
0.588
219230EAGLE PT CT1
50/50
0.721
219235Y2-105
50/50
0.261
213536CROYDN12
50/50
2.989
213541CROYDN41
50/50
0.355
219222BRL12CT2
50/50
5.636
213618FORDAST1
50/50
1.79
213617FORDACT2
50/50
1.288
219904AC1-010 C
Solar/Wind Harmer
0.283
219907AC1-030 C
Solar/Wind Harmer
0.1
219258KINSLEYDEP C
Solar/Wind Harmer
0.23
219304NAMERICA C
Solar/Wind Harmer
0.185
230434AG1-499 GEN
Solar/Wind Harmer
0.311
218660EHAMPSOLAR C
Solar/Wind Harmer
0.094
219686LUMSOLAR_N C
Solar/Wind Harmer
0.107
219287REEVESEAST C
Solar/Wind Harmer
0.709
228351V2-046C
Solar/Wind Harmer
1.041
970997AG2-616 GEN
Solar/Wind Harmer
4.797
230511AF1-262
Solar/Wind Harmer
0.091
945431AF1-208 GEN
Solar/Wind Harmer
4.205
213611FALLS1-3
Adder
1.714
228728W1-130C
Solar/Wind Harmer
0.318
228206SHRMN CT
Adder
7.276
228732V1-021 C
Adder
0.08
20720728JCB_W1-129
Solar/Wind Harmer
0.107
207522AF2-254 C
Solar/Wind Harmer
0.51
207487AE2-000G4
Solar/Wind Harmer
9.417
207445AB1-138_GEN
Solar/Wind Harmer
0.166
20628028LAKEHURS
Adder
0.537
963711AG1-223 GEN
Solar/Wind Harmer
0.384
20714828MDF_W3-079
Solar/Wind Harmer
0.079
231917EM10
Adder
0.61
217197RE CRAN C
Solar/Wind Harmer
0.126
231918WEST 1
Adder
0.81
213616FORDACT1
50/50
1.288
219912AD2-042 GEN
Solar/Wind Harmer
0.623
219766PARADISE C
Solar/Wind Harmer
0.235
219236SOUTHERNHQ C
Solar/Wind Harmer
0.048
219623KINSLEYBEA C
Solar/Wind Harmer
0.302
219906AC1-017 C
Solar/Wind Harmer
0.144
219610FLORENCE C
Solar/Wind Harmer
0.824
219348LDSOLAR C
Solar/Wind Harmer
0.356
219291REEVESSOUT C
Solar/Wind Harmer
0.032
230430AE1-229_GEN
Solar/Wind Harmer
4.395
230415AB2-049 C
Solar/Wind Harmer
0.094
959561AF2-247 GEN
Solar/Wind Harmer
0.241
971553AH1-274 GEN
Solar/Wind Harmer
1.097
228711V2-041C
Solar/Wind Harmer
0.261
228202CUMB CT
Adder
7.101
228729W2-030 C
Solar/Wind Harmer
0.242
219727YARDVSOLFA C
Solar/Wind Harmer
0.348
20716028EGP_W2-019
Solar/Wind Harmer
0.167
20720828JCB_W4-025
Solar/Wind Harmer
0.163
20715028HAN_X4-015
Solar/Wind Harmer
0.107
219276PARKLANDSO C
Solar/Wind Harmer
0.15
20636028O CRK C1
Adder
2.113
971667AH1-334 GEN
Solar/Wind Harmer
0.796
972251AH1-710 GEN
Adder
13.19
20714528FRN_Y2-051
Solar/Wind Harmer
0.076
219612MATRIX C
Solar/Wind Harmer
0.043
218438BLK ROCK C
Solar/Wind Harmer
0.032
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.313
G-007ALTFEXP_G-007A->PJM
CMTX
8.873
CBM NorthLTFEXP_CBM-N->PJM
CBM
6.478
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.29
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.904
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
17.755
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.188
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.352

Details for WANEETA3-WANEETA2 230.0 kV Ckt Z line l/o PECO_P4_CHICH045_SRT-A/* $ DELCO $ PECO_P4_CHICH045 $ STBK


Base Case Flowgate

Area:PECO
Facility Description:
WANEETA3-WANEETA2 230.0 kV Ckt Z line
Contingency Name:
PECO_P4_CHICH045_SRT-A/* $ DELCO $ PECO_P4_CHICH045 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.91 %
Rating:1008.0 MVA
Rating Type:B
MVA to Mitigate:1097.83
MW Contribution:6.24
Bus #Bus NameTypeMW Contribution
219126CAMDEN_CTG
50/50
1.112
219267WHEELBRDEPTF
50/50
0.156
219240MANTUACREK E
50/50
0.508
219726BAT.STORG E
50/50
0.249
972233AH1-701 GEN
50/50
3.961
228304LOGAN
50/50
22.455
228307PCLP GT
50/50
10.918
213535CROYDN11
50/50
9.028
213400COVANTA DELA
50/50
0.755
219921AF1-264
Solar/Wind Harmer
0.16
219615MILLCREEK C
Solar/Wind Harmer
0.226
230407AD2-065 C
Solar/Wind Harmer
0.098
230433AD2-135 GEN
Solar/Wind Harmer
0.073
228251CARLLS#4
Adder
0.453
230422AE1-104_GEN1
Solar/Wind Harmer
21.429
230425AE1-104_GEN2
Solar/Wind Harmer
21.429
219114HARTZY_C
Solar/Wind Harmer
0.476
20716428NHV_W2-082
Solar/Wind Harmer
0.928
20714928UPF_X1-085
Solar/Wind Harmer
0.182
207500AE2-000G1
Solar/Wind Harmer
13.696
207497AE2-000G2
Solar/Wind Harmer
13.696
207507AE2-000G3
Solar/Wind Harmer
13.696
20636128O CRK C2
Adder
2.802
963401AG1-189 GEN
Solar/Wind Harmer
0.496
963391AG1-188 GEN
Solar/Wind Harmer
0.822
20628028LAKEHURS
Adder
0.392
233939AC1-091 C
Solar/Wind Harmer
0.315
233970AC1-092 C
Solar/Wind Harmer
0.315
971149AH1-027 GEN
Solar/Wind Harmer
1.203
232899W1-062
Adder
3.395
970545AG2-347 GEN
Solar/Wind Harmer
22.659
232416X2-083
Adder
0.156
231940T-011
Adder
0.257
972069AH1-584 GEN
Solar/Wind Harmer
3.08
972071AH1-585 GEN
Solar/Wind Harmer
3.08
971747AH1-380 GEN
Solar/Wind Harmer
1.232
233901CHERRYDALE C
Solar/Wind Harmer
0.387
232408W1-005 C
Solar/Wind Harmer
0.344
232410W1-006 C
Solar/Wind Harmer
0.344
232918OH NUG7
Adder
3.015
232905CHERITON_25
Adder
0.843
232926CRISFLD1
Adder
0.674
233946AB2-136 GEN
Solar/Wind Harmer
1.353
234036AF2-325 C
Solar/Wind Harmer
0.31
234041AC1-190 GEN
Solar/Wind Harmer
3.026
233987AB2-037 GEN
Solar/Wind Harmer
3.821
231131BLOOM ENRGY
Adder
1.455
20720628TIN_W1-124
Solar/Wind Harmer
0.318
233984AB2-036 GEN
Solar/Wind Harmer
4.039
232424Y1-079 C
Solar/Wind Harmer
0.182
234014AF1-036_GEN
Solar/Wind Harmer
0.863
233944AB2-135 GEN
Solar/Wind Harmer
1.664
233933AB2-153 GEN
Solar/Wind Harmer
0.352
20641628MLH_W1-032
Solar/Wind Harmer
0.083
219817TRENTONSOL C
Solar/Wind Harmer
0.298
20716928W4-060COL
Solar/Wind Harmer
0.193
924131AB2-057 GEN
Solar/Wind Harmer
0.263
213918RICHMD91
50/50
0.916
219230EAGLE PT CT1
50/50
1.103
219235Y2-105
50/50
0.398
219222BRL12CT2
50/50
8.067
213536CROYDN12
50/50
4.159
213541CROYDN41
50/50
0.494
219904AC1-010 C
Solar/Wind Harmer
0.432
219258KINSLEYDEP C
Solar/Wind Harmer
0.352
219907AC1-030 C
Solar/Wind Harmer
0.15
219304NAMERICA C
Solar/Wind Harmer
0.265
230434AG1-499 GEN
Solar/Wind Harmer
0.47
218660EHAMPSOLAR C
Solar/Wind Harmer
0.139
228351V2-046C
Solar/Wind Harmer
1.579
219686LUMSOLAR_N C
Solar/Wind Harmer
0.158
219287REEVESEAST C
Solar/Wind Harmer
1.051
970997AG2-616 GEN
Solar/Wind Harmer
7.268
230511AF1-262
Solar/Wind Harmer
0.138
945431AF1-208 GEN
Solar/Wind Harmer
6.367
228728W1-130C
Solar/Wind Harmer
0.481
228206SHRMN CT
Adder
10.977
228732V1-021 C
Adder
0.121
213611FALLS1-3
Adder
2.165
20720728JCB_W1-129
Solar/Wind Harmer
0.156
207522AF2-254 C
Solar/Wind Harmer
0.744
207487AE2-000G4
Solar/Wind Harmer
13.696
207445AB1-138_GEN
Solar/Wind Harmer
0.239
20628028LAKEHURS
Adder
0.775
231917EM10
Adder
0.945
963711AG1-223 GEN
Solar/Wind Harmer
0.55
20714828MDF_W3-079
Solar/Wind Harmer
0.113
231918WEST 1
Adder
1.259
233972AC1-094 C
Solar/Wind Harmer
0.238
232901NORTHST
Adder
2.958
232900DEMECSMY
Adder
3.256
972177AH1-672 GEN
Solar/Wind Harmer
4.665
232434Z2-077 GEN
Solar/Wind Harmer
0.086
233954AC2-188 GEN
Solar/Wind Harmer
0.387
233950AC2-186 GEN
Solar/Wind Harmer
0.194
232404W1-003 C
Solar/Wind Harmer
0.344
232917OH NUG6
Adder
3.022
232915OH NUG4
Adder
3.015
971195AH1-057 GEN
Solar/Wind Harmer
0.376
233998TM1NIN_3.36
Solar/Wind Harmer
0.435
232428Y3-058 C
Solar/Wind Harmer
0.286
232919VN10
Adder
0.956
965821AG1-450 GEN
Solar/Wind Harmer
1.77
232426Y1-080 FULL
Solar/Wind Harmer
0.065
970277AG2-181 GEN
Solar/Wind Harmer
1.703
233964AF2-378 GEN
Solar/Wind Harmer
0.043
232910NRG_G1
Adder
2.911
207454AA2-184 E
Solar/Wind Harmer
0.319
217197RE CRAN C
Solar/Wind Harmer
0.171
234012AE2-112_GEN
Solar/Wind Harmer
0.734
232422X3-066 FULL
Solar/Wind Harmer
0.08
233930AB2-032 GEN
Solar/Wind Harmer
0.261
233915AB1-141 GEN
Solar/Wind Harmer
0.31
20715228NPK_W1-113
Solar/Wind Harmer
0.121
20742028HF_AC1-207
Solar/Wind Harmer
0.218
219680HOPEWELLV C1
Solar/Wind Harmer
0.021
20635828PARLN1&2
Adder
1.85
20635028RRCT1&2
Adder
2.757
20635128RRCT3&4
Adder
2.661
213919RICHMD92
50/50
0.916
219124CAMDEN_STG
50/50
0.905
219286CAMD CO RR
50/50
0.312
230406ST-CC
50/50
3.632
230404GT1-CC
50/50
2.443
228304LOGAN
50/50
20.196
219221BRL12CT1
50/50
8.067
219223BRL12CT3
50/50
8.067
219924AG1-130 C
50/50
0.377
213542CROYDN42
50/50
0.494
219912AD2-042 GEN
Solar/Wind Harmer
0.954
219766PARADISE C
Solar/Wind Harmer
0.359
219623KINSLEYBEA C
Solar/Wind Harmer
0.461
219236SOUTHERNHQ C
Solar/Wind Harmer
0.073
219906AC1-017 C
Solar/Wind Harmer
0.211
219610FLORENCE C
Solar/Wind Harmer
1.18
219348LDSOLAR C
Solar/Wind Harmer
0.51
219291REEVESSOUT C
Solar/Wind Harmer
0.048
230430AE1-229_GEN
Solar/Wind Harmer
6.657
230415AB2-049 C
Solar/Wind Harmer
0.142
959561AF2-247 GEN
Solar/Wind Harmer
0.341
971553AH1-274 GEN
Solar/Wind Harmer
1.657
228711V2-041C
Solar/Wind Harmer
0.394
228202CUMB CT
Adder
10.707
228729W2-030 C
Solar/Wind Harmer
0.364
219727YARDVSOLFA C
Solar/Wind Harmer
0.485
20716028EGP_W2-019
Solar/Wind Harmer
0.244
20720828JCB_W4-025
Solar/Wind Harmer
0.238
20715028HAN_X4-015
Solar/Wind Harmer
0.156
219276PARKLANDSO C
Solar/Wind Harmer
0.206
20636028O CRK C1
Adder
3.073
972251AH1-710 GEN
Adder
19.86
971667AH1-334 GEN
Solar/Wind Harmer
1.15
20714528FRN_Y2-051
Solar/Wind Harmer
0.109
233971AC1-093 C
Solar/Wind Harmer
0.281
970695AG2-447 GEN
Solar/Wind Harmer
1.284
972133AH1-634 GEN
Solar/Wind Harmer
3.433
233952AC2-187 GEN
Solar/Wind Harmer
0.387
972073AH1-586 GEN
Solar/Wind Harmer
3.224
233990AG1-397 GEN
Solar/Wind Harmer
0.395
232406W1-004 FULL
Solar/Wind Harmer
0.344
232914OH NUG3
Adder
3.035
232916OH NUG5
Adder
3.035
232921TASLEY2G
Adder
1.774
234015AF2-250 C
Solar/Wind Harmer
0.041
233900O-025 C
Adder
0.404
233996TM1833_GEN
Solar/Wind Harmer
0.435
233997TMININ_4.2
Solar/Wind Harmer
0.435
233940AF2-379 C
Solar/Wind Harmer
0.064
233994AC2-023 GEN
Solar/Wind Harmer
0.92
232907VN8
Adder
10.231
960671AF2-358 GEN
Solar/Wind Harmer
6.088
232417X3-008 C
Solar/Wind Harmer
0.676
219612MATRIX C
Solar/Wind Harmer
0.059
218438BLK ROCK C
Solar/Wind Harmer
0.043
233982AB2-133 GEN
Solar/Wind Harmer
1.526
233918AB1-142 GEN
Solar/Wind Harmer
0.31
20720528MAN_W1-024
Solar/Wind Harmer
0.072
20716228APLW2-078
Solar/Wind Harmer
0.249
219918AC2-009 C
Solar/Wind Harmer
0.017
20635828PARLN1&2
Adder
0.838
20635928PARLN3&4
Adder
0.838
967451AG2-055 C O1
Solar/Wind Harmer
40.968
20635028RRCT1&2
Adder
2.8
20635128RRCT3&4
Adder
2.321
219229EAGLE PT ST
50/50
0.558
219231EAGLE PT CT2
50/50
1.102
230405GT2-CC
50/50
2.454
219224BRL12CT4
50/50
8.067
213537CROYDN21
50/50
0.494
213538CROYDN22
50/50
0.494
213539CROYDN31
50/50
0.494
213540CROYDN32
50/50
0.484
219914AD2-027 C
Solar/Wind Harmer
0.719
219137THOSOLAR C
Solar/Wind Harmer
1.227
219607WPEMNERT C
Solar/Wind Harmer
0.357
219272CLEANLIGHT C
Solar/Wind Harmer
0.155
971011AG2-627 GEN
Solar/Wind Harmer
6.239
219688LUMSOLAR_S C
Solar/Wind Harmer
0.165
964001AG1-254 GEN
Solar/Wind Harmer
1.593
228309CCLP NUG
Adder
20.214
228309CCLP NUG
Adder
19.228
972141AH1-641 GEN
Solar/Wind Harmer
2.18
971535AH1-265 GEN
Solar/Wind Harmer
3.121
228260V4-054C
Solar/Wind Harmer
0.736
970453AG2-297 GEN
Solar/Wind Harmer
1.76
228754AB1-001 C
Solar/Wind Harmer
0.088
227927V4-067C
Solar/Wind Harmer
0.124
214067T20SOLAR
Solar/Wind Harmer
0.155
213611FALLS1-3
Adder
2.165
213611FALLS1-3
Adder
2.165
20717128DIX_Z2-102
Solar/Wind Harmer
0.677
20715728PEM_W1-119
Solar/Wind Harmer
0.27
20715828PEM_W1-120
Solar/Wind Harmer
0.27
971189AH1-054 GEN
Solar/Wind Harmer
0.529
970025AG2-016 GEN
Solar/Wind Harmer
1.216
207459AE1-142 C O1
Solar/Wind Harmer
0.435
231919CHRIST1
Adder
1.696
231920CHRIST2
Adder
1.658
233973AC2-185 C
Solar/Wind Harmer
1.295
234033AF1-007_GEN
Solar/Wind Harmer
8.097
232904IR4
Adder
27.997
232920IR10
Adder
1.093
232432Z2-076 GEN
Solar/Wind Harmer
0.046
20714328BYD_X4-031
Solar/Wind Harmer
0.093
233990AG1-397 GEN
Solar/Wind Harmer
0.019
232912OH NUG1
Adder
3.035
232913OH NUG2
Adder
2.995
233923SMA
Solar/Wind Harmer
1.594
232813VAUGHN
Adder
0.2
233955AB2-172 GEN
Solar/Wind Harmer
1.689
20714428HOW_X1-037
Solar/Wind Harmer
0.397
231906DC3 NUG
Adder
4.626
231902DC CT7
Adder
3.698
231907DC10
Adder
1.155
233968AD2-076_GEN
Solar/Wind Harmer
2.115
970597AG2-380 GEN
Solar/Wind Harmer
1.328
232436AB1-176 C
Solar/Wind Harmer
0.073
971983AH1-536 GEN
Solar/Wind Harmer
2.345
971521AH1-258 GEN
Solar/Wind Harmer
0.807
20720428HOL_W1-112
Solar/Wind Harmer
0.101
219620RIDERU C
Solar/Wind Harmer
0.015
233935AB2-179 C
Solar/Wind Harmer
0.707
218455CINNBAY_CGEN
Adder
0.464
20635928PARLN3&4
Adder
1.85
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.48
G-007ALTFEXP_G-007A->PJM
CMTX
12.177
CBM NorthLTFEXP_CBM-N->PJM
CBM
7.961
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.454
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.413
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
23.42
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.29
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
2.109

Details for WANEETA3-WANEETA2 230.0 kV Ckt Z line l/o PECO_P4_CHICH195_SRT-A/* $ DELCO $ PECO_P4_CHICH195 $ STBK


Base Case Flowgate

Area:PECO
Facility Description:
WANEETA3-WANEETA2 230.0 kV Ckt Z line
Contingency Name:
PECO_P4_CHICH195_SRT-A/* $ DELCO $ PECO_P4_CHICH195 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.91 %
Rating:1008.0 MVA
Rating Type:B
MVA to Mitigate:1097.77
MW Contribution:6.24
Bus #Bus NameTypeMW Contribution
219126CAMDEN_CTG
50/50
1.112
219267WHEELBRDEPTF
50/50
0.156
219240MANTUACREK E
50/50
0.508
219726BAT.STORG E
50/50
0.249
972233AH1-701 GEN
50/50
3.961
228304LOGAN
50/50
22.455
228307PCLP GT
50/50
10.918
213535CROYDN11
50/50
9.028
213400COVANTA DELA
50/50
0.755
219921AF1-264
Solar/Wind Harmer
0.16
219615MILLCREEK C
Solar/Wind Harmer
0.226
230407AD2-065 C
Solar/Wind Harmer
0.098
230433AD2-135 GEN
Solar/Wind Harmer
0.073
228251CARLLS#4
Adder
0.453
230422AE1-104_GEN1
Solar/Wind Harmer
21.429
230425AE1-104_GEN2
Solar/Wind Harmer
21.429
219114HARTZY_C
Solar/Wind Harmer
0.476
20716428NHV_W2-082
Solar/Wind Harmer
0.928
20714928UPF_X1-085
Solar/Wind Harmer
0.182
207500AE2-000G1
Solar/Wind Harmer
13.696
207497AE2-000G2
Solar/Wind Harmer
13.696
207507AE2-000G3
Solar/Wind Harmer
13.696
20636128O CRK C2
Adder
2.802
963401AG1-189 GEN
Solar/Wind Harmer
0.496
963391AG1-188 GEN
Solar/Wind Harmer
0.822
20628028LAKEHURS
Adder
0.392
233939AC1-091 C
Solar/Wind Harmer
0.315
233970AC1-092 C
Solar/Wind Harmer
0.315
971149AH1-027 GEN
Solar/Wind Harmer
1.203
232899W1-062
Adder
3.395
970545AG2-347 GEN
Solar/Wind Harmer
22.659
232416X2-083
Adder
0.156
231940T-011
Adder
0.257
972069AH1-584 GEN
Solar/Wind Harmer
3.08
972071AH1-585 GEN
Solar/Wind Harmer
3.08
971747AH1-380 GEN
Solar/Wind Harmer
1.232
233901CHERRYDALE C
Solar/Wind Harmer
0.387
232408W1-005 C
Solar/Wind Harmer
0.344
232410W1-006 C
Solar/Wind Harmer
0.344
232918OH NUG7
Adder
3.015
232905CHERITON_25
Adder
0.843
232926CRISFLD1
Adder
0.674
233946AB2-136 GEN
Solar/Wind Harmer
1.353
234036AF2-325 C
Solar/Wind Harmer
0.31
234041AC1-190 GEN
Solar/Wind Harmer
3.026
233987AB2-037 GEN
Solar/Wind Harmer
3.821
231131BLOOM ENRGY
Adder
1.455
20720628TIN_W1-124
Solar/Wind Harmer
0.318
233984AB2-036 GEN
Solar/Wind Harmer
4.039
232424Y1-079 C
Solar/Wind Harmer
0.182
234014AF1-036_GEN
Solar/Wind Harmer
0.863
233944AB2-135 GEN
Solar/Wind Harmer
1.664
233933AB2-153 GEN
Solar/Wind Harmer
0.352
20641628MLH_W1-032
Solar/Wind Harmer
0.083
219817TRENTONSOL C
Solar/Wind Harmer
0.298
20716928W4-060COL
Solar/Wind Harmer
0.193
924131AB2-057 GEN
Solar/Wind Harmer
0.263
213918RICHMD91
50/50
0.916
219230EAGLE PT CT1
50/50
1.103
219235Y2-105
50/50
0.398
219222BRL12CT2
50/50
8.067
213536CROYDN12
50/50
4.159
213541CROYDN41
50/50
0.494
219904AC1-010 C
Solar/Wind Harmer
0.432
219258KINSLEYDEP C
Solar/Wind Harmer
0.352
219907AC1-030 C
Solar/Wind Harmer
0.15
219304NAMERICA C
Solar/Wind Harmer
0.265
230434AG1-499 GEN
Solar/Wind Harmer
0.47
218660EHAMPSOLAR C
Solar/Wind Harmer
0.139
228351V2-046C
Solar/Wind Harmer
1.579
219686LUMSOLAR_N C
Solar/Wind Harmer
0.158
219287REEVESEAST C
Solar/Wind Harmer
1.051
970997AG2-616 GEN
Solar/Wind Harmer
7.268
230511AF1-262
Solar/Wind Harmer
0.138
945431AF1-208 GEN
Solar/Wind Harmer
6.367
228728W1-130C
Solar/Wind Harmer
0.481
228206SHRMN CT
Adder
10.977
228732V1-021 C
Adder
0.121
213611FALLS1-3
Adder
2.165
20720728JCB_W1-129
Solar/Wind Harmer
0.156
207522AF2-254 C
Solar/Wind Harmer
0.744
207487AE2-000G4
Solar/Wind Harmer
13.696
207445AB1-138_GEN
Solar/Wind Harmer
0.239
20628028LAKEHURS
Adder
0.775
231917EM10
Adder
0.945
963711AG1-223 GEN
Solar/Wind Harmer
0.55
20714828MDF_W3-079
Solar/Wind Harmer
0.113
231918WEST 1
Adder
1.259
233972AC1-094 C
Solar/Wind Harmer
0.238
232901NORTHST
Adder
2.958
232900DEMECSMY
Adder
3.256
972177AH1-672 GEN
Solar/Wind Harmer
4.665
232434Z2-077 GEN
Solar/Wind Harmer
0.086
233954AC2-188 GEN
Solar/Wind Harmer
0.387
233950AC2-186 GEN
Solar/Wind Harmer
0.194
232404W1-003 C
Solar/Wind Harmer
0.344
232917OH NUG6
Adder
3.022
232915OH NUG4
Adder
3.015
971195AH1-057 GEN
Solar/Wind Harmer
0.376
233998TM1NIN_3.36
Solar/Wind Harmer
0.435
232428Y3-058 C
Solar/Wind Harmer
0.286
232919VN10
Adder
0.956
965821AG1-450 GEN
Solar/Wind Harmer
1.77
232426Y1-080 FULL
Solar/Wind Harmer
0.065
970277AG2-181 GEN
Solar/Wind Harmer
1.703
233964AF2-378 GEN
Solar/Wind Harmer
0.043
232910NRG_G1
Adder
2.911
207454AA2-184 E
Solar/Wind Harmer
0.319
217197RE CRAN C
Solar/Wind Harmer
0.171
234012AE2-112_GEN
Solar/Wind Harmer
0.734
232422X3-066 FULL
Solar/Wind Harmer
0.08
233930AB2-032 GEN
Solar/Wind Harmer
0.261
233915AB1-141 GEN
Solar/Wind Harmer
0.31
20715228NPK_W1-113
Solar/Wind Harmer
0.121
20742028HF_AC1-207
Solar/Wind Harmer
0.218
219680HOPEWELLV C1
Solar/Wind Harmer
0.021
20635828PARLN1&2
Adder
1.85
20635028RRCT1&2
Adder
2.757
20635128RRCT3&4
Adder
2.661
219229EAGLE PT ST
50/50
0.558
219231EAGLE PT CT2
50/50
1.102
230405GT2-CC
50/50
2.454
219224BRL12CT4
50/50
8.067
213537CROYDN21
50/50
0.494
213538CROYDN22
50/50
0.494
213539CROYDN31
50/50
0.494
213540CROYDN32
50/50
0.484
219914AD2-027 C
Solar/Wind Harmer
0.719
219137THOSOLAR C
Solar/Wind Harmer
1.227
219607WPEMNERT C
Solar/Wind Harmer
0.357
219272CLEANLIGHT C
Solar/Wind Harmer
0.155
971011AG2-627 GEN
Solar/Wind Harmer
6.239
219688LUMSOLAR_S C
Solar/Wind Harmer
0.165
964001AG1-254 GEN
Solar/Wind Harmer
1.593
228309CCLP NUG
Adder
20.214
228309CCLP NUG
Adder
19.228
972141AH1-641 GEN
Solar/Wind Harmer
2.18
971535AH1-265 GEN
Solar/Wind Harmer
3.121
228260V4-054C
Solar/Wind Harmer
0.736
970453AG2-297 GEN
Solar/Wind Harmer
1.76
228754AB1-001 C
Solar/Wind Harmer
0.088
227927V4-067C
Solar/Wind Harmer
0.124
214067T20SOLAR
Solar/Wind Harmer
0.155
213611FALLS1-3
Adder
2.165
213611FALLS1-3
Adder
2.165
20717128DIX_Z2-102
Solar/Wind Harmer
0.677
20715728PEM_W1-119
Solar/Wind Harmer
0.27
20715828PEM_W1-120
Solar/Wind Harmer
0.27
971189AH1-054 GEN
Solar/Wind Harmer
0.529
970025AG2-016 GEN
Solar/Wind Harmer
1.216
207459AE1-142 C O1
Solar/Wind Harmer
0.435
231919CHRIST1
Adder
1.696
231920CHRIST2
Adder
1.658
233973AC2-185 C
Solar/Wind Harmer
1.295
234033AF1-007_GEN
Solar/Wind Harmer
8.097
232904IR4
Adder
27.997
232920IR10
Adder
1.093
232432Z2-076 GEN
Solar/Wind Harmer
0.046
20714328BYD_X4-031
Solar/Wind Harmer
0.093
233990AG1-397 GEN
Solar/Wind Harmer
0.019
232912OH NUG1
Adder
3.035
232913OH NUG2
Adder
2.995
233923SMA
Solar/Wind Harmer
1.594
232813VAUGHN
Adder
0.2
233955AB2-172 GEN
Solar/Wind Harmer
1.689
20714428HOW_X1-037
Solar/Wind Harmer
0.397
231906DC3 NUG
Adder
4.626
231902DC CT7
Adder
3.698
231907DC10
Adder
1.155
233968AD2-076_GEN
Solar/Wind Harmer
2.115
970597AG2-380 GEN
Solar/Wind Harmer
1.328
232436AB1-176 C
Solar/Wind Harmer
0.073
971983AH1-536 GEN
Solar/Wind Harmer
2.345
971521AH1-258 GEN
Solar/Wind Harmer
0.807
20720428HOL_W1-112
Solar/Wind Harmer
0.101
219620RIDERU C
Solar/Wind Harmer
0.015
233935AB2-179 C
Solar/Wind Harmer
0.707
218455CINNBAY_CGEN
Adder
0.464
20635928PARLN3&4
Adder
1.85
213919RICHMD92
50/50
0.916
219124CAMDEN_STG
50/50
0.905
219286CAMD CO RR
50/50
0.312
230406ST-CC
50/50
3.632
230404GT1-CC
50/50
2.443
228304LOGAN
50/50
20.196
219221BRL12CT1
50/50
8.067
219223BRL12CT3
50/50
8.067
219924AG1-130 C
50/50
0.377
213542CROYDN42
50/50
0.494
219912AD2-042 GEN
Solar/Wind Harmer
0.954
219766PARADISE C
Solar/Wind Harmer
0.359
219623KINSLEYBEA C
Solar/Wind Harmer
0.461
219236SOUTHERNHQ C
Solar/Wind Harmer
0.073
219906AC1-017 C
Solar/Wind Harmer
0.211
219610FLORENCE C
Solar/Wind Harmer
1.18
219348LDSOLAR C
Solar/Wind Harmer
0.51
219291REEVESSOUT C
Solar/Wind Harmer
0.048
230430AE1-229_GEN
Solar/Wind Harmer
6.657
230415AB2-049 C
Solar/Wind Harmer
0.142
959561AF2-247 GEN
Solar/Wind Harmer
0.341
971553AH1-274 GEN
Solar/Wind Harmer
1.657
228711V2-041C
Solar/Wind Harmer
0.394
228202CUMB CT
Adder
10.707
228729W2-030 C
Solar/Wind Harmer
0.364
219727YARDVSOLFA C
Solar/Wind Harmer
0.485
20716028EGP_W2-019
Solar/Wind Harmer
0.244
20720828JCB_W4-025
Solar/Wind Harmer
0.238
20715028HAN_X4-015
Solar/Wind Harmer
0.156
219276PARKLANDSO C
Solar/Wind Harmer
0.206
20636028O CRK C1
Adder
3.073
972251AH1-710 GEN
Adder
19.86
971667AH1-334 GEN
Solar/Wind Harmer
1.15
20714528FRN_Y2-051
Solar/Wind Harmer
0.109
233971AC1-093 C
Solar/Wind Harmer
0.281
970695AG2-447 GEN
Solar/Wind Harmer
1.284
972133AH1-634 GEN
Solar/Wind Harmer
3.433
233952AC2-187 GEN
Solar/Wind Harmer
0.387
972073AH1-586 GEN
Solar/Wind Harmer
3.224
233990AG1-397 GEN
Solar/Wind Harmer
0.395
232406W1-004 FULL
Solar/Wind Harmer
0.344
232914OH NUG3
Adder
3.035
232916OH NUG5
Adder
3.035
232921TASLEY2G
Adder
1.774
234015AF2-250 C
Solar/Wind Harmer
0.041
233900O-025 C
Adder
0.404
233996TM1833_GEN
Solar/Wind Harmer
0.435
233997TMININ_4.2
Solar/Wind Harmer
0.435
233940AF2-379 C
Solar/Wind Harmer
0.064
233994AC2-023 GEN
Solar/Wind Harmer
0.92
232907VN8
Adder
10.231
960671AF2-358 GEN
Solar/Wind Harmer
6.088
232417X3-008 C
Solar/Wind Harmer
0.676
219612MATRIX C
Solar/Wind Harmer
0.059
218438BLK ROCK C
Solar/Wind Harmer
0.043
233982AB2-133 GEN
Solar/Wind Harmer
1.526
233918AB1-142 GEN
Solar/Wind Harmer
0.31
20720528MAN_W1-024
Solar/Wind Harmer
0.072
20716228APLW2-078
Solar/Wind Harmer
0.249
219918AC2-009 C
Solar/Wind Harmer
0.017
20635828PARLN1&2
Adder
0.838
20635928PARLN3&4
Adder
0.838
967451AG2-055 C O1
Solar/Wind Harmer
40.968
20635028RRCT1&2
Adder
2.8
20635128RRCT3&4
Adder
2.321
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.48
G-007ALTFEXP_G-007A->PJM
CMTX
12.177
CBM NorthLTFEXP_CBM-N->PJM
CBM
7.961
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.454
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.413
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
23.42
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.29
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
2.109

Details for WANEETA3-WANEETA2 230.0 kV Ckt Z line l/o PECO_P4_CHICH435_SRT-A/* $ DELCO $ PECO_P4_CHICH435 $ STBK


Base Case Flowgate

Area:PECO
Facility Description:
WANEETA3-WANEETA2 230.0 kV Ckt Z line
Contingency Name:
PECO_P4_CHICH435_SRT-A/* $ DELCO $ PECO_P4_CHICH435 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.9 %
Rating:1008.0 MVA
Rating Type:B
MVA to Mitigate:1097.74
MW Contribution:6.24
Bus #Bus NameTypeMW Contribution
219126CAMDEN_CTG
50/50
1.112
219267WHEELBRDEPTF
50/50
0.156
219240MANTUACREK E
50/50
0.508
219726BAT.STORG E
50/50
0.249
972233AH1-701 GEN
50/50
3.962
228304LOGAN
50/50
22.456
228307PCLP GT
50/50
10.919
213535CROYDN11
50/50
9.028
213400COVANTA DELA
50/50
0.755
219921AF1-264
Solar/Wind Harmer
0.16
219615MILLCREEK C
Solar/Wind Harmer
0.226
230407AD2-065 C
Solar/Wind Harmer
0.098
230433AD2-135 GEN
Solar/Wind Harmer
0.073
228251CARLLS#4
Adder
0.453
230422AE1-104_GEN1
Solar/Wind Harmer
21.429
230425AE1-104_GEN2
Solar/Wind Harmer
21.429
219114HARTZY_C
Solar/Wind Harmer
0.476
20716428NHV_W2-082
Solar/Wind Harmer
0.928
20714928UPF_X1-085
Solar/Wind Harmer
0.182
207500AE2-000G1
Solar/Wind Harmer
13.697
207497AE2-000G2
Solar/Wind Harmer
13.697
207507AE2-000G3
Solar/Wind Harmer
13.697
20636128O CRK C2
Adder
2.802
963401AG1-189 GEN
Solar/Wind Harmer
0.496
963391AG1-188 GEN
Solar/Wind Harmer
0.822
20628028LAKEHURS
Adder
0.392
233939AC1-091 C
Solar/Wind Harmer
0.315
233970AC1-092 C
Solar/Wind Harmer
0.315
971149AH1-027 GEN
Solar/Wind Harmer
1.203
232899W1-062
Adder
3.394
970545AG2-347 GEN
Solar/Wind Harmer
22.657
232416X2-083
Adder
0.156
231940T-011
Adder
0.257
972069AH1-584 GEN
Solar/Wind Harmer
3.08
972071AH1-585 GEN
Solar/Wind Harmer
3.08
971747AH1-380 GEN
Solar/Wind Harmer
1.231
232918OH NUG7
Adder
3.015
233901CHERRYDALE C
Solar/Wind Harmer
0.387
232408W1-005 C
Solar/Wind Harmer
0.344
232410W1-006 C
Solar/Wind Harmer
0.344
232905CHERITON_25
Adder
0.843
232926CRISFLD1
Adder
0.674
233946AB2-136 GEN
Solar/Wind Harmer
1.353
234036AF2-325 C
Solar/Wind Harmer
0.31
234041AC1-190 GEN
Solar/Wind Harmer
3.026
233987AB2-037 GEN
Solar/Wind Harmer
3.82
231131BLOOM ENRGY
Adder
1.455
20720628TIN_W1-124
Solar/Wind Harmer
0.318
233984AB2-036 GEN
Solar/Wind Harmer
4.039
232424Y1-079 C
Solar/Wind Harmer
0.182
234014AF1-036_GEN
Solar/Wind Harmer
0.863
233944AB2-135 GEN
Solar/Wind Harmer
1.664
233933AB2-153 GEN
Solar/Wind Harmer
0.352
20641628MLH_W1-032
Solar/Wind Harmer
0.083
219817TRENTONSOL C
Solar/Wind Harmer
0.298
20716928W4-060COL
Solar/Wind Harmer
0.193
924131AB2-057 GEN
Solar/Wind Harmer
0.263
213919RICHMD92
50/50
0.916
219124CAMDEN_STG
50/50
0.905
219286CAMD CO RR
50/50
0.312
230406ST-CC
50/50
3.632
230404GT1-CC
50/50
2.443
228304LOGAN
50/50
20.197
219221BRL12CT1
50/50
8.067
219223BRL12CT3
50/50
8.067
219924AG1-130 C
50/50
0.377
213542CROYDN42
50/50
0.494
219912AD2-042 GEN
Solar/Wind Harmer
0.954
219766PARADISE C
Solar/Wind Harmer
0.359
219623KINSLEYBEA C
Solar/Wind Harmer
0.461
219236SOUTHERNHQ C
Solar/Wind Harmer
0.073
219906AC1-017 C
Solar/Wind Harmer
0.211
219610FLORENCE C
Solar/Wind Harmer
1.18
219348LDSOLAR C
Solar/Wind Harmer
0.51
219291REEVESSOUT C
Solar/Wind Harmer
0.048
230430AE1-229_GEN
Solar/Wind Harmer
6.657
230415AB2-049 C
Solar/Wind Harmer
0.142
959561AF2-247 GEN
Solar/Wind Harmer
0.341
971553AH1-274 GEN
Solar/Wind Harmer
1.657
228711V2-041C
Solar/Wind Harmer
0.394
228202CUMB CT
Adder
10.708
228729W2-030 C
Solar/Wind Harmer
0.364
219727YARDVSOLFA C
Solar/Wind Harmer
0.485
20716028EGP_W2-019
Solar/Wind Harmer
0.244
20720828JCB_W4-025
Solar/Wind Harmer
0.238
20715028HAN_X4-015
Solar/Wind Harmer
0.156
219276PARKLANDSO C
Solar/Wind Harmer
0.206
20636028O CRK C1
Adder
3.073
972251AH1-710 GEN
Adder
19.86
971667AH1-334 GEN
Solar/Wind Harmer
1.15
20714528FRN_Y2-051
Solar/Wind Harmer
0.109
233971AC1-093 C
Solar/Wind Harmer
0.281
970695AG2-447 GEN
Solar/Wind Harmer
1.283
972133AH1-634 GEN
Solar/Wind Harmer
3.433
233952AC2-187 GEN
Solar/Wind Harmer
0.387
972073AH1-586 GEN
Solar/Wind Harmer
3.223
233990AG1-397 GEN
Solar/Wind Harmer
0.394
232914OH NUG3
Adder
3.035
232916OH NUG5
Adder
3.035
232406W1-004 FULL
Solar/Wind Harmer
0.344
232921TASLEY2G
Adder
1.774
234015AF2-250 C
Solar/Wind Harmer
0.041
233996TM1833_GEN
Solar/Wind Harmer
0.435
233997TMININ_4.2
Solar/Wind Harmer
0.435
233900O-025 C
Adder
0.404
219229EAGLE PT ST
50/50
0.558
219231EAGLE PT CT2
50/50
1.102
230405GT2-CC
50/50
2.455
219224BRL12CT4
50/50
8.067
213537CROYDN21
50/50
0.494
213538CROYDN22
50/50
0.494
213539CROYDN31
50/50
0.494
213540CROYDN32
50/50
0.484
219914AD2-027 C
Solar/Wind Harmer
0.719
219137THOSOLAR C
Solar/Wind Harmer
1.227
219607WPEMNERT C
Solar/Wind Harmer
0.357
219272CLEANLIGHT C
Solar/Wind Harmer
0.155
971011AG2-627 GEN
Solar/Wind Harmer
6.239
219688LUMSOLAR_S C
Solar/Wind Harmer
0.165
964001AG1-254 GEN
Solar/Wind Harmer
1.593
228309CCLP NUG
Adder
20.215
228309CCLP NUG
Adder
19.229
972141AH1-641 GEN
Solar/Wind Harmer
2.181
971535AH1-265 GEN
Solar/Wind Harmer
3.121
228260V4-054C
Solar/Wind Harmer
0.736
970453AG2-297 GEN
Solar/Wind Harmer
1.76
228754AB1-001 C
Solar/Wind Harmer
0.088
227927V4-067C
Solar/Wind Harmer
0.124
214067T20SOLAR
Solar/Wind Harmer
0.155
213611FALLS1-3
Adder
2.165
213611FALLS1-3
Adder
2.165
20717128DIX_Z2-102
Solar/Wind Harmer
0.677
20715728PEM_W1-119
Solar/Wind Harmer
0.27
20715828PEM_W1-120
Solar/Wind Harmer
0.27
971189AH1-054 GEN
Solar/Wind Harmer
0.529
970025AG2-016 GEN
Solar/Wind Harmer
1.216
207459AE1-142 C O1
Solar/Wind Harmer
0.435
231919CHRIST1
Adder
1.696
231920CHRIST2
Adder
1.658
233973AC2-185 C
Solar/Wind Harmer
1.294
234033AF1-007_GEN
Solar/Wind Harmer
8.096
232904IR4
Adder
27.995
232920IR10
Adder
1.093
232432Z2-076 GEN
Solar/Wind Harmer
0.046
20714328BYD_X4-031
Solar/Wind Harmer
0.093
233990AG1-397 GEN
Solar/Wind Harmer
0.019
232912OH NUG1
Adder
3.035
232913OH NUG2
Adder
2.995
233923SMA
Solar/Wind Harmer
1.594
232813VAUGHN
Adder
0.2
233955AB2-172 GEN
Solar/Wind Harmer
1.689
20714428HOW_X1-037
Solar/Wind Harmer
0.397
231906DC3 NUG
Adder
4.625
231902DC CT7
Adder
3.698
231907DC10
Adder
1.155
233968AD2-076_GEN
Solar/Wind Harmer
2.114
970597AG2-380 GEN
Solar/Wind Harmer
1.328
232436AB1-176 C
Solar/Wind Harmer
0.073
971983AH1-536 GEN
Solar/Wind Harmer
2.345
971521AH1-258 GEN
Solar/Wind Harmer
0.807
20720428HOL_W1-112
Solar/Wind Harmer
0.101
219620RIDERU C
Solar/Wind Harmer
0.015
233935AB2-179 C
Solar/Wind Harmer
0.707
218455CINNBAY_CGEN
Adder
0.464
20635928PARLN3&4
Adder
1.85
213918RICHMD91
50/50
0.916
219230EAGLE PT CT1
50/50
1.103
219235Y2-105
50/50
0.398
219222BRL12CT2
50/50
8.067
213536CROYDN12
50/50
4.159
213541CROYDN41
50/50
0.494
219904AC1-010 C
Solar/Wind Harmer
0.432
219258KINSLEYDEP C
Solar/Wind Harmer
0.352
219907AC1-030 C
Solar/Wind Harmer
0.15
219304NAMERICA C
Solar/Wind Harmer
0.265
230434AG1-499 GEN
Solar/Wind Harmer
0.47
218660EHAMPSOLAR C
Solar/Wind Harmer
0.139
228351V2-046C
Solar/Wind Harmer
1.579
219686LUMSOLAR_N C
Solar/Wind Harmer
0.158
219287REEVESEAST C
Solar/Wind Harmer
1.051
970997AG2-616 GEN
Solar/Wind Harmer
7.269
230511AF1-262
Solar/Wind Harmer
0.138
945431AF1-208 GEN
Solar/Wind Harmer
6.368
228728W1-130C
Solar/Wind Harmer
0.481
228206SHRMN CT
Adder
10.977
228732V1-021 C
Adder
0.121
213611FALLS1-3
Adder
2.165
20720728JCB_W1-129
Solar/Wind Harmer
0.156
207522AF2-254 C
Solar/Wind Harmer
0.744
207487AE2-000G4
Solar/Wind Harmer
13.697
207445AB1-138_GEN
Solar/Wind Harmer
0.239
20628028LAKEHURS
Adder
0.775
231917EM10
Adder
0.945
963711AG1-223 GEN
Solar/Wind Harmer
0.55
20714828MDF_W3-079
Solar/Wind Harmer
0.113
231918WEST 1
Adder
1.259
233972AC1-094 C
Solar/Wind Harmer
0.238
232901NORTHST
Adder
2.957
232900DEMECSMY
Adder
3.256
972177AH1-672 GEN
Solar/Wind Harmer
4.665
232434Z2-077 GEN
Solar/Wind Harmer
0.086
233954AC2-188 GEN
Solar/Wind Harmer
0.387
233950AC2-186 GEN
Solar/Wind Harmer
0.194
232917OH NUG6
Adder
3.022
232915OH NUG4
Adder
3.015
232404W1-003 C
Solar/Wind Harmer
0.344
971195AH1-057 GEN
Solar/Wind Harmer
0.376
233998TM1NIN_3.36
Solar/Wind Harmer
0.435
232428Y3-058 C
Solar/Wind Harmer
0.286
232919VN10
Adder
0.956
965821AG1-450 GEN
Solar/Wind Harmer
1.77
232426Y1-080 FULL
Solar/Wind Harmer
0.065
970277AG2-181 GEN
Solar/Wind Harmer
1.703
233964AF2-378 GEN
Solar/Wind Harmer
0.043
232910NRG_G1
Adder
2.911
207454AA2-184 E
Solar/Wind Harmer
0.319
217197RE CRAN C
Solar/Wind Harmer
0.171
234012AE2-112_GEN
Solar/Wind Harmer
0.734
232422X3-066 FULL
Solar/Wind Harmer
0.08
233930AB2-032 GEN
Solar/Wind Harmer
0.261
233915AB1-141 GEN
Solar/Wind Harmer
0.31
20715228NPK_W1-113
Solar/Wind Harmer
0.121
20742028HF_AC1-207
Solar/Wind Harmer
0.218
219680HOPEWELLV C1
Solar/Wind Harmer
0.021
20635828PARLN1&2
Adder
1.85
20635028RRCT1&2
Adder
2.757
20635128RRCT3&4
Adder
2.661
233940AF2-379 C
Solar/Wind Harmer
0.064
233994AC2-023 GEN
Solar/Wind Harmer
0.92
232907VN8
Adder
10.23
960671AF2-358 GEN
Solar/Wind Harmer
6.088
232417X3-008 C
Solar/Wind Harmer
0.676
219612MATRIX C
Solar/Wind Harmer
0.059
218438BLK ROCK C
Solar/Wind Harmer
0.043
233982AB2-133 GEN
Solar/Wind Harmer
1.526
233918AB1-142 GEN
Solar/Wind Harmer
0.31
20720528MAN_W1-024
Solar/Wind Harmer
0.072
20716228APLW2-078
Solar/Wind Harmer
0.249
219918AC2-009 C
Solar/Wind Harmer
0.017
20635828PARLN1&2
Adder
0.838
20635928PARLN3&4
Adder
0.838
967451AG2-055 C O1
Solar/Wind Harmer
40.969
20635028RRCT1&2
Adder
2.8
20635128RRCT3&4
Adder
2.321
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.48
G-007ALTFEXP_G-007A->PJM
CMTX
12.177
CBM NorthLTFEXP_CBM-N->PJM
CBM
7.962
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.454
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.413
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
23.421
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.29
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
2.109

Details for WANEETA3-WANEETA2 230.0 kV Ckt Z line l/o PECO_P2-2_CHI230B1_SRT-A/* $ DELCO $ PECO_P2-2_CHI230B1 $ B


Base Case Flowgate

Area:PECO
Facility Description:
WANEETA3-WANEETA2 230.0 kV Ckt Z line
Contingency Name:
PECO_P2-2_CHI230B1_SRT-A/* $ DELCO $ PECO_P2-2_CHI230B1 $ B
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:108.9 %
Rating:1008.0 MVA
Rating Type:B
MVA to Mitigate:1097.68
MW Contribution:6.24
Bus #Bus NameTypeMW Contribution
219126CAMDEN_CTG
50/50
1.112
219267WHEELBRDEPTF
50/50
0.156
219240MANTUACREK E
50/50
0.508
219726BAT.STORG E
50/50
0.249
972233AH1-701 GEN
50/50
3.961
228304LOGAN
50/50
22.455
228307PCLP GT
50/50
10.918
213535CROYDN11
50/50
9.028
213400COVANTA DELA
50/50
0.755
219921AF1-264
Solar/Wind Harmer
0.16
219615MILLCREEK C
Solar/Wind Harmer
0.226
230407AD2-065 C
Solar/Wind Harmer
0.098
230433AD2-135 GEN
Solar/Wind Harmer
0.073
228251CARLLS#4
Adder
0.453
230422AE1-104_GEN1
Solar/Wind Harmer
21.429
230425AE1-104_GEN2
Solar/Wind Harmer
21.429
219114HARTZY_C
Solar/Wind Harmer
0.476
20716428NHV_W2-082
Solar/Wind Harmer
0.928
20714928UPF_X1-085
Solar/Wind Harmer
0.182
207500AE2-000G1
Solar/Wind Harmer
13.696
207497AE2-000G2
Solar/Wind Harmer
13.696
207507AE2-000G3
Solar/Wind Harmer
13.696
20636128O CRK C2
Adder
2.802
963401AG1-189 GEN
Solar/Wind Harmer
0.496
963391AG1-188 GEN
Solar/Wind Harmer
0.822
20628028LAKEHURS
Adder
0.392
233939AC1-091 C
Solar/Wind Harmer
0.315
233970AC1-092 C
Solar/Wind Harmer
0.315
971149AH1-027 GEN
Solar/Wind Harmer
1.203
232899W1-062
Adder
3.395
970545AG2-347 GEN
Solar/Wind Harmer
22.659
232416X2-083
Adder
0.156
231940T-011
Adder
0.257
972069AH1-584 GEN
Solar/Wind Harmer
3.08
972071AH1-585 GEN
Solar/Wind Harmer
3.08
971747AH1-380 GEN
Solar/Wind Harmer
1.232
233901CHERRYDALE C
Solar/Wind Harmer
0.387
232408W1-005 C
Solar/Wind Harmer
0.344
232410W1-006 C
Solar/Wind Harmer
0.344
232918OH NUG7
Adder
3.015
232905CHERITON_25
Adder
0.843
232926CRISFLD1
Adder
0.674
233946AB2-136 GEN
Solar/Wind Harmer
1.353
234036AF2-325 C
Solar/Wind Harmer
0.31
234041AC1-190 GEN
Solar/Wind Harmer
3.026
233987AB2-037 GEN
Solar/Wind Harmer
3.821
231131BLOOM ENRGY
Adder
1.455
20720628TIN_W1-124
Solar/Wind Harmer
0.318
233984AB2-036 GEN
Solar/Wind Harmer
4.039
232424Y1-079 C
Solar/Wind Harmer
0.182
234014AF1-036_GEN
Solar/Wind Harmer
0.863
233944AB2-135 GEN
Solar/Wind Harmer
1.664
233933AB2-153 GEN
Solar/Wind Harmer
0.352
20641628MLH_W1-032
Solar/Wind Harmer
0.083
219817TRENTONSOL C
Solar/Wind Harmer
0.298
20716928W4-060COL
Solar/Wind Harmer
0.193
924131AB2-057 GEN
Solar/Wind Harmer
0.263
213919RICHMD92
50/50
0.916
219124CAMDEN_STG
50/50
0.905
219286CAMD CO RR
50/50
0.312
230406ST-CC
50/50
3.632
230404GT1-CC
50/50
2.443
228304LOGAN
50/50
20.196
219221BRL12CT1
50/50
8.067
219223BRL12CT3
50/50
8.067
219924AG1-130 C
50/50
0.377
213542CROYDN42
50/50
0.494
219912AD2-042 GEN
Solar/Wind Harmer
0.954
219766PARADISE C
Solar/Wind Harmer
0.359
219623KINSLEYBEA C
Solar/Wind Harmer
0.461
219236SOUTHERNHQ C
Solar/Wind Harmer
0.073
219906AC1-017 C
Solar/Wind Harmer
0.211
219610FLORENCE C
Solar/Wind Harmer
1.18
219348LDSOLAR C
Solar/Wind Harmer
0.51
219291REEVESSOUT C
Solar/Wind Harmer
0.048
230430AE1-229_GEN
Solar/Wind Harmer
6.657
230415AB2-049 C
Solar/Wind Harmer
0.142
959561AF2-247 GEN
Solar/Wind Harmer
0.341
971553AH1-274 GEN
Solar/Wind Harmer
1.657
228711V2-041C
Solar/Wind Harmer
0.394
228202CUMB CT
Adder
10.707
228729W2-030 C
Solar/Wind Harmer
0.364
219727YARDVSOLFA C
Solar/Wind Harmer
0.485
20716028EGP_W2-019
Solar/Wind Harmer
0.244
20720828JCB_W4-025
Solar/Wind Harmer
0.238
20715028HAN_X4-015
Solar/Wind Harmer
0.156
219276PARKLANDSO C
Solar/Wind Harmer
0.206
20636028O CRK C1
Adder
3.073
972251AH1-710 GEN
Adder
19.86
971667AH1-334 GEN
Solar/Wind Harmer
1.15
20714528FRN_Y2-051
Solar/Wind Harmer
0.109
233971AC1-093 C
Solar/Wind Harmer
0.281
970695AG2-447 GEN
Solar/Wind Harmer
1.284
972133AH1-634 GEN
Solar/Wind Harmer
3.433
233952AC2-187 GEN
Solar/Wind Harmer
0.387
972073AH1-586 GEN
Solar/Wind Harmer
3.224
233990AG1-397 GEN
Solar/Wind Harmer
0.395
232406W1-004 FULL
Solar/Wind Harmer
0.344
213918RICHMD91
50/50
0.916
219230EAGLE PT CT1
50/50
1.103
219235Y2-105
50/50
0.398
219222BRL12CT2
50/50
8.067
213536CROYDN12
50/50
4.159
213541CROYDN41
50/50
0.494
219904AC1-010 C
Solar/Wind Harmer
0.432
219258KINSLEYDEP C
Solar/Wind Harmer
0.352
219907AC1-030 C
Solar/Wind Harmer
0.15
219304NAMERICA C
Solar/Wind Harmer
0.265
230434AG1-499 GEN
Solar/Wind Harmer
0.47
218660EHAMPSOLAR C
Solar/Wind Harmer
0.139
228351V2-046C
Solar/Wind Harmer
1.579
219686LUMSOLAR_N C
Solar/Wind Harmer
0.158
219287REEVESEAST C
Solar/Wind Harmer
1.051
970997AG2-616 GEN
Solar/Wind Harmer
7.268
230511AF1-262
Solar/Wind Harmer
0.138
945431AF1-208 GEN
Solar/Wind Harmer
6.367
228728W1-130C
Solar/Wind Harmer
0.481
228206SHRMN CT
Adder
10.977
228732V1-021 C
Adder
0.121
213611FALLS1-3
Adder
2.165
20720728JCB_W1-129
Solar/Wind Harmer
0.156
207522AF2-254 C
Solar/Wind Harmer
0.744
207487AE2-000G4
Solar/Wind Harmer
13.696
207445AB1-138_GEN
Solar/Wind Harmer
0.239
20628028LAKEHURS
Adder
0.775
231917EM10
Adder
0.945
963711AG1-223 GEN
Solar/Wind Harmer
0.55
20714828MDF_W3-079
Solar/Wind Harmer
0.113
231918WEST 1
Adder
1.259
233972AC1-094 C
Solar/Wind Harmer
0.238
232901NORTHST
Adder
2.958
232900DEMECSMY
Adder
3.256
972177AH1-672 GEN
Solar/Wind Harmer
4.665
232434Z2-077 GEN
Solar/Wind Harmer
0.086
233954AC2-188 GEN
Solar/Wind Harmer
0.387
233950AC2-186 GEN
Solar/Wind Harmer
0.194
232404W1-003 C
Solar/Wind Harmer
0.344
232917OH NUG6
Adder
3.022
232915OH NUG4
Adder
3.015
971195AH1-057 GEN
Solar/Wind Harmer
0.376
233998TM1NIN_3.36
Solar/Wind Harmer
0.435
232428Y3-058 C
Solar/Wind Harmer
0.286
232919VN10
Adder
0.956
965821AG1-450 GEN
Solar/Wind Harmer
1.77
232426Y1-080 FULL
Solar/Wind Harmer
0.065
970277AG2-181 GEN
Solar/Wind Harmer
1.703
233964AF2-378 GEN
Solar/Wind Harmer
0.043
232910NRG_G1
Adder
2.911
207454AA2-184 E
Solar/Wind Harmer
0.319
217197RE CRAN C
Solar/Wind Harmer
0.171
234012AE2-112_GEN
Solar/Wind Harmer
0.734
232422X3-066 FULL
Solar/Wind Harmer
0.08
233930AB2-032 GEN
Solar/Wind Harmer
0.261
233915AB1-141 GEN
Solar/Wind Harmer
0.31
20715228NPK_W1-113
Solar/Wind Harmer
0.121
20742028HF_AC1-207
Solar/Wind Harmer
0.218
219680HOPEWELLV C1
Solar/Wind Harmer
0.021
20635828PARLN1&2
Adder
1.85
20635028RRCT1&2
Adder
2.757
20635128RRCT3&4
Adder
2.661
219229EAGLE PT ST
50/50
0.558
219231EAGLE PT CT2
50/50
1.102
230405GT2-CC
50/50
2.454
219224BRL12CT4
50/50
8.067
213537CROYDN21
50/50
0.494
213538CROYDN22
50/50
0.494
213539CROYDN31
50/50
0.494
213540CROYDN32
50/50
0.484
219914AD2-027 C
Solar/Wind Harmer
0.719
219137THOSOLAR C
Solar/Wind Harmer
1.227
219607WPEMNERT C
Solar/Wind Harmer
0.357
219272CLEANLIGHT C
Solar/Wind Harmer
0.155
971011AG2-627 GEN
Solar/Wind Harmer
6.239
219688LUMSOLAR_S C
Solar/Wind Harmer
0.165
964001AG1-254 GEN
Solar/Wind Harmer
1.593
228309CCLP NUG
Adder
20.214
228309CCLP NUG
Adder
19.228
972141AH1-641 GEN
Solar/Wind Harmer
2.18
971535AH1-265 GEN
Solar/Wind Harmer
3.121
228260V4-054C
Solar/Wind Harmer
0.736
970453AG2-297 GEN
Solar/Wind Harmer
1.76
228754AB1-001 C
Solar/Wind Harmer
0.088
227927V4-067C
Solar/Wind Harmer
0.124
214067T20SOLAR
Solar/Wind Harmer
0.155
213611FALLS1-3
Adder
2.165
213611FALLS1-3
Adder
2.165
20717128DIX_Z2-102
Solar/Wind Harmer
0.677
20715728PEM_W1-119
Solar/Wind Harmer
0.27
20715828PEM_W1-120
Solar/Wind Harmer
0.27
971189AH1-054 GEN
Solar/Wind Harmer
0.529
970025AG2-016 GEN
Solar/Wind Harmer
1.216
207459AE1-142 C O1
Solar/Wind Harmer
0.435
231919CHRIST1
Adder
1.696
231920CHRIST2
Adder
1.658
233973AC2-185 C
Solar/Wind Harmer
1.295
234033AF1-007_GEN
Solar/Wind Harmer
8.097
232904IR4
Adder
27.997
232920IR10
Adder
1.093
232432Z2-076 GEN
Solar/Wind Harmer
0.046
20714328BYD_X4-031
Solar/Wind Harmer
0.093
233990AG1-397 GEN
Solar/Wind Harmer
0.019
232912OH NUG1
Adder
3.035
232913OH NUG2
Adder
2.995
233923SMA
Solar/Wind Harmer
1.594
232813VAUGHN
Adder
0.2
233955AB2-172 GEN
Solar/Wind Harmer
1.689
20714428HOW_X1-037
Solar/Wind Harmer
0.397
231906DC3 NUG
Adder
4.626
231902DC CT7
Adder
3.698
231907DC10
Adder
1.155
233968AD2-076_GEN
Solar/Wind Harmer
2.115
970597AG2-380 GEN
Solar/Wind Harmer
1.328
232436AB1-176 C
Solar/Wind Harmer
0.073
971983AH1-536 GEN
Solar/Wind Harmer
2.345
971521AH1-258 GEN
Solar/Wind Harmer
0.807
20720428HOL_W1-112
Solar/Wind Harmer
0.101
219620RIDERU C
Solar/Wind Harmer
0.015
233935AB2-179 C
Solar/Wind Harmer
0.707
218455CINNBAY_CGEN
Adder
0.464
20635928PARLN3&4
Adder
1.85
232914OH NUG3
Adder
3.035
232916OH NUG5
Adder
3.035
232921TASLEY2G
Adder
1.774
234015AF2-250 C
Solar/Wind Harmer
0.041
233900O-025 C
Adder
0.404
233996TM1833_GEN
Solar/Wind Harmer
0.435
233997TMININ_4.2
Solar/Wind Harmer
0.435
233940AF2-379 C
Solar/Wind Harmer
0.064
233994AC2-023 GEN
Solar/Wind Harmer
0.92
232907VN8
Adder
10.231
960671AF2-358 GEN
Solar/Wind Harmer
6.088
232417X3-008 C
Solar/Wind Harmer
0.676
219612MATRIX C
Solar/Wind Harmer
0.059
218438BLK ROCK C
Solar/Wind Harmer
0.043
233982AB2-133 GEN
Solar/Wind Harmer
1.526
233918AB1-142 GEN
Solar/Wind Harmer
0.31
20720528MAN_W1-024
Solar/Wind Harmer
0.072
20716228APLW2-078
Solar/Wind Harmer
0.249
219918AC2-009 C
Solar/Wind Harmer
0.017
20635828PARLN1&2
Adder
0.838
20635928PARLN3&4
Adder
0.838
967451AG2-055 C O1
Solar/Wind Harmer
40.968
20635028RRCT1&2
Adder
2.8
20635128RRCT3&4
Adder
2.321
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.48
G-007ALTFEXP_G-007A->PJM
CMTX
12.177
CBM NorthLTFEXP_CBM-N->PJM
CBM
7.961
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.454
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.413
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
23.42
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.29
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
2.109
CONTINGENCY 'AP_P7-1_PE-500-235105-004T_SRT-A'
 OPEN BRANCH FROM BUS 223938 TO BUS 314290 CKT 1   /*DICKH230     230.0 - 6EDFERRY     230.0
 OPEN BRANCH FROM BUS 235105 TO BUS 313403 CKT 1   /*01DOUBS      500.0 - 8ASPEN       500.0
 OPEN BRANCH FROM BUS 313911 TO BUS 314290 CKT 1   /*6TWINCREEK   230.0 - 6EDFERRY     230.0
 OPEN BUS 314290                                   /*6EDFERRY     230.0
END
CONTINGENCY 'DVP_P7-1: LN 203-9404_SRT-S'
 OPEN BRANCH FROM BUS 223938 TO BUS 314290 CKT 1                /*DICKH230     230.0 - 6EDFERRY     230.0
 OPEN BRANCH FROM BUS 235105 TO BUS 313403 CKT 1                /*01DOUBS      500.0 - 8ASPEN       500.0
 OPEN BRANCH FROM BUS 313911 TO BUS 314290 CKT 1                /*6TWINCREEK   230.0 - 6EDFERRY     230.0
 OPEN BUS 314290                                                /*6EDFERRY     230.0
 SET POSTCONTRATING 1315 BRANCH FROM BUS 314004 TO BUS 314072 CKT 1 /*6ASHBURN     230.0 - 6PL VIEW     230.0
 SET PRECONTRATING 1219 BRANCH FROM BUS 314004 TO BUS 314072 CKT 1 /*6ASHBURN     230.0 - 6PL VIEW     230.0
END
CONTINGENCY 'DVP_P1-2: LN 9354_SRT-A'
 OPEN BRANCH FROM BUS 313400 TO BUS 313403 CKT 1   /*8GOLDEN      500.0 - 8ASPEN       500.0
END
CONTINGENCY 'DVP_P7-1: LN 9354-9363_SRT-A'
 OPEN BRANCH FROM BUS 313396 TO BUS 313402 CKT 1   /*6SYCOLIN     230.0 - 6ASPEN       230.0
 OPEN BRANCH FROM BUS 313400 TO BUS 313403 CKT 1   /*8GOLDEN      500.0 - 8ASPEN       500.0
END
CONTINGENCY 'PECO_P4_CHICH045_SRT-A
 DISCONNECT BUS 213489   /*CHICHST1     230.0
 DISCONNECT BUS 213627   /*FOULK8       230.0
END
CONTINGENCY 'PECO_P4_CHICH195_SRT-A
 DISCONNECT BUS 213489   /*CHICHST1     230.0
 DISCONNECT BUS 214203   /*CHICHST1     138.0
 DISCONNECT BUS 214340   /*CHI9AB HS LD 230.0
END
CONTINGENCY 'PECO_P4_CHICH435_SRT-A
 DISCONNECT BUS 213489   /*CHICHST1     230.0
 DISCONNECT BUS 213750   /*LINWOOD43    230.0
 DISCONNECT BUS 214221   /*CHIREACT_43  230.0
END
CONTINGENCY 'PECO_P2-2_CHI230B1_SRT-A
 DISCONNECT BUS 213489   /*CHICHST1     230.0
END
CONTINGENCY 'PJM_500_BG_P4_5_CNSTN_C_SRT-A'
 OPEN BRANCH FROM BUS 200004 TO BUS 200064 CKT 1    /*CNASTONE     500.0 - PCHBTM1S     500.0
 OPEN BRANCH FROM BUS 200004 TO BUS 200100 CKT ZC   /*CNASTONE     500.0 - CNASTCAP     500.0
END
CONTINGENCY 'BGE_P4_GRACETON_51_SRT-A'
 OPEN BRANCH FROM BUS 200004 TO BUS 200064 CKT 1   /*CNASTONE     500.0 - PCHBTM1S     500.0
END
CONTINGENCY 'PECO_P4_PEACH235_SRT-A
 TRIP BRANCH FROM BUS 200064 TO BUS 200004 CKT 1    /*PCHBTM1S     500.0 - CNASTONE     500.0
 TRIP BRANCH FROM BUS 200064 TO BUS 200065 CKT Z1   /*PCHBTM1S     500.0 - PCHBTM2S     500.0
END
CONTINGENCY 'PJM_500_BG_P4_5_CNSTN_B_SRT-A'
 OPEN BRANCH FROM BUS 200004 TO BUS 200064 CKT 1   /*CNASTONE     500.0 - PCHBTM1S     500.0
 OPEN BRANCH FROM BUS 200004 TO BUS 220963 CKT 2   /*CNASTONE     500.0 - CONASTON     230.0
END
CONTINGENCY 'PECO_P4_PEACH245_SRT-A
 DISCONNECT BUS 200122                             /*DELTA        500.0
 DISCONNECT BUS 200192                             /*DELTA CT1     13.8
 DISCONNECT BUS 200193                             /*DELTA CT2     13.8
 DISCONNECT BUS 200194                             /*DELTA CT3     13.8
 DISCONNECT BUS 200195                             /*DELTA ST      18.0
 DISCONNECT BUS 200199                             /*DELTA2 POI   500.0
 DISCONNECT BUS 200200                             /*DELTA2 CT1    18.0
 DISCONNECT BUS 200201                             /*DELTA2 CT2    18.0
 DISCONNECT BUS 200202                             /*DELTA2 ST     19.5
 TRIP BRANCH FROM BUS 200064 TO BUS 200004 CKT 1   /*PCHBTM1S     500.0 - CNASTONE     500.0
END
CONTINGENCY 'PECO_P1-2_5012_SRT-A'
 TRIP BRANCH FROM BUS 200064 TO BUS 200004 CKT 1   /*PCHBTM1S     500.0 - CNASTONE     500.0
END
CONTINGENCY 'AP_P2-3_PE-500-019E_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235105 TO BUS 235459 CKT 1          /*01DOUBS      500.0 - 01DOUBS      230.0
 DISCONNECT BRANCH FROM BUS 235105 TO BUS 235459 CKT 3          /*01DOUBS      500.0 - 01DOUBS      230.0
 DISCONNECT BRANCH FROM BUS 270095 TO BUS 235105 CKT 1          /*CHAN         500.0 - 01DOUBS      500.0
 REMOVE SWSHUNT FROM BUS 235105 BLOCK 1 STEP 2                  /*01DOUBS      500.0
 SET PRECONTRATING 4178 BRANCH FROM BUS 235105 TO BUS 235098 CKT 1 /*01DOUBS      500.0 - WOODSIDE     500.0
END
CONTINGENCY 'AP_P1-2_PE-500-3835T_SRT-A'
 DISCONNECT BRANCH FROM BUS 270095 TO BUS 235105 CKT 1   /*CHAN         500.0 - 01DOUBS      500.0
END
CONTINGENCY 'AP_P2-3_PE-500-019B_SRT-A'
 DISCONNECT BRANCH FROM BUS 235105 TO BUS 200003 CKT 1   /*01DOUBS      500.0 - BRIGHTON     500.0
 DISCONNECT BRANCH FROM BUS 270095 TO BUS 235105 CKT 1   /*CHAN         500.0 - 01DOUBS      500.0
END
CONTINGENCY 'PECO_P4_PEACH025_SRT-A
 TRIP BRANCH FROM BUS 200013 TO BUS 200066 CKT Z1   /*PCHBTM2N     500.0 - PCHBTM1N     500.0
 TRIP BRANCH FROM BUS 200013 TO BUS 214347 CKT Z1   /*PCHBTM2N     500.0 - PBN_EXP_BAY  500.0
 TRIP BRANCH FROM BUS 270095 TO BUS 200066 CKT 1    /*CHAN         500.0 - PCHBTM1N     500.0
END
CONTINGENCY 'PECO_P4_PEACH035_SRT-A
 DISCONNECT BUS 213791                             /*MDDYRN07     230.0
 DISCONNECT BUS 213794                             /*MDYRN5-6      13.8
 DISCONNECT BUS 213795                             /*MDYRN7-8      13.8
 DISCONNECT BUS 213866                             /*PCHBTM       230.0
 DISCONNECT BUS 213867                             /*PCHBTM        35.0
 TRIP BRANCH FROM BUS 200066 TO BUS 270095 CKT 1   /*PCHBTM1N     500.0 - CHAN         500.0
END
CONTINGENCY 'BG_P7_CNSTN_NWEST2_SRT-A'
 OPEN BRANCH FROM BUS 220961 TO BUS 220963 CKT 1   /*NWEST326     230.0 - CONASTON     230.0
 OPEN BRANCH FROM BUS 220962 TO BUS 220963 CKT 1   /*NWEST311     230.0 - CONASTON     230.0
END
CONTINGENCY 'BG_P7_GRCTN_RAPHEL_SRT-A'
 OPEN BRANCH FROM BUS 220964 TO BUS 220999 CKT 13   /*GRACETON     230.0 - BAGLEY2      230.0
 OPEN BRANCH FROM BUS 220964 TO BUS 221000 CKT 5    /*GRACETON     230.0 - BAGLEY       230.0
 OPEN BRANCH FROM BUS 220980 TO BUS 220999 CKT 13   /*RAPHAEL      230.0 - BAGLEY2      230.0
 OPEN BRANCH FROM BUS 220980 TO BUS 221000 CKT 5    /*RAPHAEL      230.0 - BAGLEY       230.0
END
CONTINGENCY 'PJM_500_BG_P4_5_CNSTN_13_SRT-A'
 OPEN BRANCH FROM BUS 200004 TO BUS 220963 CKT 2   /*CNASTONE     500.0 - CONASTON     230.0
 OPEN BRANCH FROM BUS 220962 TO BUS 220963 CKT 1   /*NWEST311     230.0 - CONASTON     230.0
END
CONTINGENCY 'PECO_P1-2_5007_SRT-A
 TRIP BRANCH FROM BUS 200066 TO BUS 270095 CKT 1   /*PCHBTM1N     500.0 - CHAN         500.0
END
CONTINGENCY 'AP_P2-2_PE-230-010_SRT-A'
 DISCONNECT BRANCH FROM BUS 235450 TO BUS 235451 CKT 4   /*01CARROL     138.0 - 01CARROL     230.0
 DISCONNECT BRANCH FROM BUS 235491 TO BUS 235451 CKT 1   /*01MTAIRY     230.0 - 01CARROL     230.0
END
CONTINGENCY 'PJM_500_BG_P2_CNSTN_230-S_SRT-A'
 OPEN BRANCH FROM BUS 200004 TO BUS 220963 CKT 2   /*CNASTONE     500.0 - CONASTON     230.0
END
CONTINGENCY 'AP_P2-3_WP-500-DRT45_SRT-SL'
 OPEN BRANCH FROM BUS 235116 TO BUS 235118 CKT 1                /*01YUKON      500.0 - 01SOBEND     500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235116 TO BUS 235109 CKT 1 /*01YUKON      500.0 - AB1-106 POI  500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235116 TO BUS 235109 CKT 1 /*01YUKON      500.0 - AB1-106 POI  500.0
END
CONTINGENCY 'PN_P2-3_PN-500-DRT32_SRT-A'
 DISCONNECT BRANCH FROM BUS 200011 TO BUS 200810 TO BUS 200907 CKT 4 /*KEYSTONE     500.0 - 26KEYSTONE   230.0 - 26KEYSTN#4    20.0
 OPEN BRANCH FROM BUS 200011 TO BUS 235104 CKT 1                /*KEYSTONE     500.0 - 01CABOT      500.0
 REDUCE BUS 200011 SHUNT BY 100 PERCENT                         /*KEYSTONE     500.0
 SET POSTCONTRATING 2078 BRANCH FROM BUS 235118 TO BUS 200011 CKT 1 /*01SOBEND     500.0 - KEYSTONE     500.0
 SET PRECONTRATING 2078 BRANCH FROM BUS 235118 TO BUS 200011 CKT 1 /*01SOBEND     500.0 - KEYSTONE     500.0
END
CONTINGENCY 'PN_P2-3_PN-500-004-DRT-002_SRT-SL'
 DISCONNECT BRANCH FROM BUS 200011 TO BUS 200810 TO BUS 200907 CKT 4 /*KEYSTONE     500.0 - 26KEYSTONE   230.0 - 26KEYSTN#4    20.0
 DISCONNECT BRANCH FROM BUS 200011 TO BUS 235104 CKT 1          /*KEYSTONE     500.0 - 01CABOT      500.0
 REDUCE BUS 200011 SHUNT BY 100 PERCENT                         /*KEYSTONE     500.0
 SET POSTCONTRATING 2078 BRANCH FROM BUS 200011 TO BUS 235118 CKT 1 /*KEYSTONE     500.0 - 01SOBEND     500.0
 SET POSTCONTRATING 2771 BRANCH FROM BUS 200005 TO BUS 200011 CKT 1 /*CONEM-GH     500.0 - KEYSTONE     500.0
 SET PRECONTRATING 2078 BRANCH FROM BUS 200011 TO BUS 235118 CKT 1 /*KEYSTONE     500.0 - 01SOBEND     500.0
 SET PRECONTRATING 2426 BRANCH FROM BUS 200011 TO BUS 200009 CKT 1 /*KEYSTONE     500.0 - JUNI         500.0
END
CONTINGENCY 'PECO_P4_PEACH095_SRT-A
 TRIP BRANCH FROM BUS 200013 TO BUS 200066 CKT Z2   /*PCHBTM2N     500.0 - PCHBTM1N     500.0
 TRIP BRANCH FROM BUS 214347 TO BUS 200013 CKT Z2   /*PBN_EXP_BAY  500.0 - PCHBTM2N     500.0
 TRIP BRANCH FROM BUS 214347 TO BUS 200064 CKT 2    /*PBN_EXP_BAY  500.0 - PCHBTM1S     500.0
END
CONTINGENCY 'PECO_P2-2_NOTT230B_SRT-A
 DISCONNECT BUS 213844   /*NOTTNGHM     230.0
END
CONTINGENCY 'PL_04_P71_001014_SRT-A'
 DISCONNECT BRANCH FROM BUS 208045 TO BUS 208078 CKT 3   /*LAUS         230.0 - SAKR         230.0
 DISCONNECT BRANCH FROM BUS 208045 TO BUS 208078 CKT 4   /*LAUS         230.0 - SAKR         230.0
END
CONTINGENCY 'PL_05_P71_000906_SRT-A'
 DISCONNECT BRANCH FROM BUS 208019 TO BUS 208020 CKT 1   /*MANO         230.0 - MANO TR3     230.0
 DISCONNECT BRANCH FROM BUS 208019 TO BUS 208021 CKT 1   /*MANO         230.0 - MANO TR4     230.0
 DISCONNECT BRANCH FROM BUS 208066 TO BUS 208914 CKT 1   /*SAHA0102     230.0 - SAHA 34       13.8
 DISCONNECT BRANCH FROM BUS 208066 TO BUS 208915 CKT 1   /*SAHA0102     230.0 - SAHA 567      13.8
 DISCONNECT BRANCH FROM BUS 208067 TO BUS 208916 CKT 1   /*SAHA0304     230.0 - SAHA8910      13.8
 DISCONNECT BRANCH FROM BUS 208067 TO BUS 208917 CKT 1   /*SAHA0304     230.0 - SAHA1112      13.8
 DISCONNECT BRANCH FROM BUS 208070 TO BUS 208019 CKT 1   /*SAHA12TP     230.0 - MANO         230.0
 DISCONNECT BRANCH FROM BUS 208070 TO BUS 208048 CKT 1   /*SAHA12TP     230.0 - OTCR         230.0
 DISCONNECT BRANCH FROM BUS 208070 TO BUS 208066 CKT 1   /*SAHA12TP     230.0 - SAHA0102     230.0
 DISCONNECT BRANCH FROM BUS 208071 TO BUS 208019 CKT 1   /*SAHA34TP     230.0 - MANO         230.0
 DISCONNECT BRANCH FROM BUS 208071 TO BUS 208067 CKT 1   /*SAHA34TP     230.0 - SAHA0304     230.0
 DISCONNECT BRANCH FROM BUS 208071 TO BUS 220964 CKT 1   /*SAHA34TP     230.0 - GRACETON     230.0
END
CONTINGENCY 'PL_04_P22_102290_SRT-A'
 DISCONNECT BRANCH FROM BUS 200099 TO BUS 208045 CKT 3   /*LAUS         500.0 - LAUS         230.0
END
CONTINGENCY 'PECO_P4_PEACH255_SRT-A
 DISCONNECT BUS 200122                              /*DELTA        500.0
 DISCONNECT BUS 200192                              /*DELTA CT1     13.8
 DISCONNECT BUS 200193                              /*DELTA CT2     13.8
 DISCONNECT BUS 200194                              /*DELTA CT3     13.8
 DISCONNECT BUS 200195                              /*DELTA ST      18.0
 DISCONNECT BUS 200199                              /*DELTA2 POI   500.0
 DISCONNECT BUS 200200                              /*DELTA2 CT1    18.0
 DISCONNECT BUS 200201                              /*DELTA2 CT2    18.0
 DISCONNECT BUS 200202                              /*DELTA2 ST     19.5
 TRIP BRANCH FROM BUS 200064 TO BUS 200065 CKT Z2   /*PCHBTM1S     500.0 - PCHBTM2S     500.0
 TRIP BRANCH FROM BUS 214347 TO BUS 200064 CKT 2    /*PBN_EXP_BAY  500.0 - PCHBTM1S     500.0
END
CONTINGENCY 'PECO_P4_PEACH215_SRT-A
 REMOVE MACHINE 1 FROM BUS 200034                  /*PCHBTM 2      22.0
 TRIP BRANCH FROM BUS 200065 TO BUS 200051 CKT 1   /*PCHBTM2S     500.0 - ROCKSPGS     500.0
END
CONTINGENCY 'PECO_P4_PEACH205_SRT-A
 TRIP BRANCH FROM BUS 200065 TO BUS 200051 CKT 1    /*PCHBTM2S     500.0 - ROCKSPGS     500.0
 TRIP BRANCH FROM BUS 200065 TO BUS 200064 CKT Z1   /*PCHBTM2S     500.0 - PCHBTM1S     500.0
END
CONTINGENCY 'PJM500_PS_P2-3_NFRD5_9-10_SRT-A'
 DISCONNECT BRANCH FROM BUS 200012 TO BUS 219100 CKT 4   /*NEWFRDM      500.0 - NEWFRDM      230.0
 TRIP LINE FROM BUS 200012 TO BUS 200028 CKT 1           /*NEWFRDM      500.0 - WINDSOR      500.0
END
CONTINGENCY 'PECO_P4_LINWO125_SRT-A
 DISCONNECT BUS 214235   /*LINWOOD84    230.0
 DISCONNECT BUS 214236   /*LINWOOD85    230.0
END
CONTINGENCY 'DPL_P7_1_DBL_6NC_SRT-A'
 OPEN LINE FROM BUS 231000 TO BUS 214235 CKT 1   /*CLAY_230     230.0 - LINWOOD84    230.0
 OPEN LINE FROM BUS 231001 TO BUS 214236 CKT 1   /*EDGEMR 5     230.0 - LINWOOD85    230.0
END
CONTINGENCY 'DPL_P7_1_DBL_5NC_SRT-A'
 OPEN LINE FROM BUS 231001 TO BUS 214236 CKT 1   /*EDGEMR 5     230.0 - LINWOOD85    230.0
 OPEN LINE FROM BUS 231001 TO BUS 231000 CKT 1   /*EDGEMR 5     230.0 - CLAY_230     230.0
END
235105 to 314939 ckt 1
972284 to 314933 ckt 1
219125 to 214206 ckt 1
270095 to 235105 ckt 1
200004 to 200003 ckt 1
214084 to 220964 ckt 1
200011 to 235104 ckt 1
200011 to 235118 ckt 1
213819 to 213783 ckt 1
213844 to 213846 ckt 1
213846 to 213869 ckt 1
200066 to 270095 ckt 1
200064 to 200004 ckt 1
200064 to 214347 ckt 2
200065 to 200064 ckt Z1
200065 to 200064 ckt Z2
213869 to 214087 ckt 1
214277 to 214012 ckt 1
214206 to 214274 ckt 1
200051 to 200065 ckt 1
214010 to 213817 ckt 1
214012 to 214010 ckt Z

Winter Peak Analysis

The New Service Request AG2-627 was evaluated as a 40.0 MW (24.0 MW Capacity) injection in the AEC area.

AG2-627 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 40.0 MW (40.0 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2DVP
AH1-727 TP-8BRAMBLETON 500.0 kV Ckt 1 line
DVP_P1-2: LN 9354_SRT-A
SingleAC106.43 %3776.92B4019.910.21
GD2AP/PJM
CHAN-01DOUBS 500.0 kV Ckt 1 line
PJM_500_BG_P4_5_CNSTN_C_SRT-A
BreakerAC116.17 %4595.0B5338.090.49
GD2AP/PJM
CHAN-01DOUBS 500.0 kV Ckt 1 line
PECO_P1-2_5012_SRT-A
SingleAC116.13 %4595.0B5335.980.49
GD2AP/PJM
CHAN-01DOUBS 500.0 kV Ckt 1 line
BGE_P4_GRACETON_51_SRT-A
BreakerAC116.12 %4595.0B5335.850.49
GD2AP/PJM
CHAN-01DOUBS 500.0 kV Ckt 1 line
PJM_500_BG_P1_5011_SRT-A
SingleAC105.03 %4595.0B4826.350.42
GD2PJM
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
AP_P1-2_PE-500-3835T_SRT-A
SingleAC137.01 %3507.0B4805.10.37
GD2PJM
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
AP_P2-3_PE-500-019E_SRT-W
BreakerAC136.75 %3507.0B4795.710.37
GD2PJM
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
AP_P2-3_PE-500-019B_SRT-A
BreakerAC119.38 %3507.0B4186.650.3
GD2PJM
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
PECO_P1-2_5007_SRT-A/* $ CHESCO $ PECO_P1-2_5007 $ L
SingleAC116.36 %3507.0B4080.660.33
GD2PJM
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
BG_P7_CNSTN_NWEST2_SRT-A
TowerAC108.78 %3507.0B3814.930.28
GD2PJM
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
BG_P7_GRCTN_RAPHEL_SRT-A
TowerAC106.71 %3507.0B3742.490.28
GD2PJM
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
Base Case
SingleAC104.54 %3202.0A3347.240.26
GD2PJM
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
PJM_500_BG_P2_CNSTN_230-S_SRT-A
BusAC101.14 %3507.0B3546.850.26
GD2PJM
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
PJM_500_BG_P2_CNSTN_230-N_SRT-A
BusAC101.12 %3507.0B3546.330.26
GD2BGE/PECO
COOPER-GRACETON 230.0 kV Ckt 1 line
PECO_P1-2_5012_SRT-A
SingleAC141.29 %639.0B902.850.13
GD2BGE/PECO
COOPER-GRACETON 230.0 kV Ckt 1 line
PECO_P4_PEACH235_SRT-A/* $ CHESCO $ PECO_P4_PEACH235 $ STBK
BreakerAC138.68 %639.0B886.190.13
GD2BGE/PECO
COOPER-GRACETON 230.0 kV Ckt 1 line
PJM_500_BG_P4_5_CNSTN_C_SRT-A
BreakerAC138.68 %639.0B886.160.13
GD2BGE/PECO
COOPER-GRACETON 230.0 kV Ckt 1 line
PECO_P1-2_5014_SRT-A/* $ CHESCO $ PECO_P1-2_5012 $ L
SingleAC103.86 %639.0B663.670.13
GD2PJM
HOPE CREEK-SILVER RUN 230.0 kV Ckt 1 line
PJM500_PS_P1-2_5015_SRT-A
SingleAC109.26 %1150.0B1256.450.26
GD2PJM
HOPE CREEK-SILVER RUN 230.0 kV Ckt 1 line
PJM500_PS_P2-3_HOPC_3-4_SRT-A
BreakerAC109.26 %1150.0B1256.430.26
GD2PJM
HOPE CREEK-SILVER RUN 230.0 kV Ckt 1 line
DPL_P4_2_REDLION-HOPE AT50_SRT-A
BreakerAC108.14 %1150.0B1243.570.25
GD2PECO
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line
PECO_P1-2_5012_SRT-A
SingleAC147.41 %639.0B941.930.13
GD2PECO
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line
PJM_500_BG_P4_5_CNSTN_C_SRT-A
BreakerAC144.84 %639.0B925.550.13
GD2PECO
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line
PECO_P4_PEACH235_SRT-A/* $ CHESCO $ PECO_P4_PEACH235 $ STBK
BreakerAC144.81 %639.0B925.350.13
GD2PECO
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line
PECO_P1-2_5014_SRT-A/* $ CHESCO $ PECO_P1-2_5012 $ L
SingleAC110.18 %639.0B704.060.13
IPDPECO
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line
PJM_500_BG_P4_5_CNSTN_C_SRT-A
BreakerAC104.8 %639.0B669.662.63
IPDPECO
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line
PECO_P4_PEACH235_SRT-A/* $ CHESCO $ PECO_P4_PEACH235 $ STBK
BreakerAC104.74 %639.0B669.32.63
IPDPECO
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line
BGE_P4_GRACETON_51_SRT-A
BreakerAC104.71 %639.0B669.132.63
IPDPECO
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line
PECO_P1-2_5012_SRT-A
SingleAC104.71 %639.0B669.132.63
GD2PECO
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line
PECO_P1-2_5012_SRT-A
SingleAC147.41 %639.0B941.930.13
GD2PECO
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line
PJM_500_BG_P4_5_CNSTN_C_SRT-A
BreakerAC144.84 %639.0B925.550.13
GD2PECO
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line
PECO_P4_PEACH235_SRT-A/* $ CHESCO $ PECO_P4_PEACH235 $ STBK
BreakerAC144.81 %639.0B925.350.13
GD2PECO
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line
PECO_P1-2_5014_SRT-A/* $ CHESCO $ PECO_P1-2_5012 $ L
SingleAC110.18 %639.0B704.060.13
IPDPECO
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line
PJM_500_BG_P4_5_CNSTN_C_SRT-A
BreakerAC104.8 %639.0B669.662.63
IPDPECO
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line
PECO_P4_PEACH235_SRT-A/* $ CHESCO $ PECO_P4_PEACH235 $ STBK
BreakerAC104.74 %639.0B669.32.63
IPDPECO
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line
PECO_P1-2_5012_SRT-A
SingleAC104.71 %639.0B669.132.63
IPDPECO
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line
BGE_P4_GRACETON_51_SRT-A
BreakerAC104.71 %639.0B669.132.63
GD2PJM
PCHBTM1N-CHAN 500.0 kV Ckt 1 line
PECO_P1-2_5012_SRT-A
SingleAC152.01 %3926.0B5967.810.62
GD2PJM
PCHBTM1N-CHAN 500.0 kV Ckt 1 line
BGE_P4_GRACETON_51_SRT-A
BreakerAC152.0 %3926.0B5967.690.62
GD2PJM
PCHBTM1N-CHAN 500.0 kV Ckt 1 line
PECO_P4_PEACH235_SRT-A/* $ CHESCO $ PECO_P4_PEACH235 $ STBK
BreakerAC151.94 %3926.0B5965.210.62
GD2PJM
PCHBTM1N-CHAN 500.0 kV Ckt 1 line
PJM_500_BG_P1_5011_SRT-A
SingleAC108.62 %3926.0B4264.260.43
GD2PJM
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
AP_P2-3_PE-500-019E_SRT-W
BreakerAC180.58 %3700.0B6681.320.64
GD2PJM
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
AP_P1-2_PE-500-3835T_SRT-A
SingleAC180.55 %3700.0B6680.420.63
GD2PJM
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
PECO_P4_PEACH035_SRT-A/* $ CHESCO $ PECO_P4_PEACH035 $ STBK
BreakerAC170.51 %3700.0B6308.690.62
GD2PJM
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
PECO_P1-2_5007_SRT-A/* $ CHESCO $ PECO_P1-2_5007 $ L
SingleAC167.58 %3700.0B6200.510.64
GD2PJM
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
Base Case
SingleAC129.51 %3464.0A4486.180.46
GD2PJM
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
PECO_P2-2_NOTT230B_SRT-A/* $ CHESCO $ PECO_P2-2_NOTT230B $ B
BusAC128.48 %3700.0B4753.650.5
GD2PJM
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
PL_04_P71_001014_SRT-A
TowerAC125.36 %3700.0B4638.190.47
GD2PJM
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
PL_05_P71_000906_SRT-A
TowerAC125.04 %3700.0B4626.310.47
GD2PJM
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
PL_04_P22_102817_SRT-A
BusAC123.71 %3700.0B4577.250.47
IPDPJM
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
AP_P1-2_PE-500-3835T_SRT-A
SingleAC118.17 %3700.0B4372.312.69
IPDPJM
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
AP_P2-3_PE-500-019E_SRT-W
BreakerAC118.13 %3700.0B4370.9712.69
IPDPJM
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
AP_P2-3_PE-500-019B_SRT-A
BreakerAC114.1 %3700.0B4221.7611.95
IPDPJM
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
PECO_P1-2_5007_SRT-A/* $ CHESCO $ PECO_P1-2_5007 $ L
SingleAC109.27 %3700.0B4043.0612.72
GD2PJM
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line
PJM_500_BG_P4_5_CNSTN_C_SRT-A
BreakerAC163.3 %3022.0B4934.90.45
GD2PJM
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line
PECO_P1-2_5012_SRT-A
SingleAC163.21 %3022.0B4932.260.45
GD2PJM
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line
BGE_P4_GRACETON_51_SRT-A
BreakerAC163.21 %3022.0B4932.210.45
GD2PJM
PCHBTM2S-PCHBTM1S 500.0 kV Ckt Z1 line
PECO_P4_PEACH255_SRT-A/* $ CHESCO $ PECO_P4_PEACH255 $ STBK
BreakerAC134.81 %3277.0B4417.810.51
GD2PJM
PCHBTM2S-PCHBTM1S 500.0 kV Ckt Z1 line
PECO_P4_PEACH225_SRT-A/* $ CHESCO $ PECO_P4_PEACH225 $ STBK
BreakerAC100.06 %3277.0B3278.920.55
GD2PJM
PCHBTM2S-PCHBTM1S 500.0 kV Ckt Z2 line
PECO_P4_PEACH235_SRT-A/* $ CHESCO $ PECO_P4_PEACH235 $ STBK
BreakerAC118.38 %3022.0B3577.590.47
GD2PECO
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line
PECO_P1-2_5012_SRT-A
SingleAC145.16 %639.0B927.560.13
GD2PECO
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line
PJM_500_BG_P4_5_CNSTN_C_SRT-A
BreakerAC142.58 %639.0B911.080.13
GD2PECO
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line
PECO_P4_PEACH235_SRT-A/* $ CHESCO $ PECO_P4_PEACH235 $ STBK
BreakerAC142.56 %639.0B910.960.13
GD2PECO
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line
PECO_P1-2_5014_SRT-A/* $ CHESCO $ PECO_P1-2_5012 $ L
SingleAC107.87 %639.0B689.320.13
IPDPECO
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line
PJM_500_BG_P4_5_CNSTN_C_SRT-A
BreakerAC102.53 %639.0B655.172.63
IPDPECO
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line
PECO_P4_PEACH235_SRT-A/* $ CHESCO $ PECO_P4_PEACH235 $ STBK
BreakerAC102.49 %639.0B654.892.63
IPDPECO
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line
PECO_P1-2_5012_SRT-A
SingleAC102.46 %639.0B654.722.63
IPDPECO
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line
BGE_P4_GRACETON_51_SRT-A
BreakerAC102.46 %639.0B654.722.63
GD2PECO
RICHMOND35-WANEETA3 230.0 kV Ckt 1 line
PECO_P4_CHICH045_SRT-A/* $ DELCO $ PECO_P4_CHICH045 $ STBK
BreakerAC102.65 %1201.0B1232.790.48
GD2PECO
RICHMOND35-WANEETA3 230.0 kV Ckt 1 line
PECO_P4_CHICH195_SRT-A/* $ DELCO $ PECO_P4_CHICH195 $ STBK
BreakerAC102.65 %1201.0B1232.770.48
GD2PECO
RICHMOND35-WANEETA3 230.0 kV Ckt 1 line
PECO_P2-2_CHI230B1_SRT-A/* $ DELCO $ PECO_P2-2_CHI230B1 $ B
BusAC102.65 %1201.0B1232.770.48
GD2PECO
RICHMOND35-WANEETA3 230.0 kV Ckt 1 line
PECO_P4_CHICH435_SRT-A/* $ DELCO $ PECO_P4_CHICH435 $ STBK
BreakerAC102.64 %1201.0B1232.760.48
GD2DP&L
RL_230-KEEN_230 230.0 kV Ckt 1 line
DPL_P1_2_CKT 5036_SRT-A
SingleAC103.73 %1171.0B1214.640.26
GD2DP&L
RL_230-KEEN_230 230.0 kV Ckt 1 line
DPL_P4_2_REDLION-KEENEY AT50_SRT-A
BreakerAC103.37 %1171.0B1210.440.24
GD2DP&L
RL_230-KEEN_230 230.0 kV Ckt 1 line
DPL_P4_2_REDLION-KEENEY AT51_SRT-A
BreakerAC100.73 %1171.0B1179.490.23
GD2PJM
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line
PECO_P2-2_CHI230B1_SRT-A/* $ DELCO $ PECO_P2-2_CHI230B1 $ B
BusAC115.06 %3106.0B3573.910.6
GD2PJM
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line
PECO_P4_CHICH435_SRT-A/* $ DELCO $ PECO_P4_CHICH435 $ STBK
BreakerAC115.06 %3106.0B3573.850.6
GD2PJM
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line
PECO_P4_CHICH195_SRT-A/* $ DELCO $ PECO_P4_CHICH195 $ STBK
BreakerAC115.06 %3106.0B3573.840.6
GD2PJM
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line
PECO_P4_CHICH045_SRT-A/* $ DELCO $ PECO_P4_CHICH045 $ STBK
BreakerAC115.06 %3106.0B3573.810.6
GD2PJM
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line
PECO_P4_PEACH065_SRT-A/* $ CHESCO $ PECO_P4_PEACH065 $ STBK
BreakerAC114.58 %3106.0B3558.70.63
GD2PJM
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line
Base Case
SingleAC111.42 %2863.0A3189.860.56
GD2PJM
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line
DPL_P7_1_DBL_5NC_SRT-A
TowerAC109.52 %3106.0B3401.810.53
GD2PJM
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line
PECO_P4_NOTTI785_SRT-A
BreakerAC108.6 %3106.0B3373.030.58
GD2PJM
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line
PECO_P2-2_NOTT230B_SRT-A/* $ CHESCO $ PECO_P2-2_NOTT230B $ B
BusAC108.46 %3106.0B3368.690.58
GD2PJM
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line
PECO_P1-2_PBS-NDELTA_SRT-A/* $ CHESCO $ PECO_P1-2_PBS-NDELTA $ L
SingleAC108.36 %3106.0B3365.650.56
GD2PJM
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line
PECO_P1-2_5034_SRT-A/* $ CHESCO $ PECO_P1-2_5034 $ L
SingleAC108.36 %3106.0B3365.650.56
GD2PJM
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line
PECO_P2-2_NOTT230B2_SRT-A/* $ CHESCO $ PECO_P2-2_NOTT230B2 $ B
BusAC105.37 %3106.0B3272.90.56
GD2PJM
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line
PECO_P2-2_CONC230B_SRT-A/* $ DELCO $ PECO_P2-2_CONC230B $ B
BusAC105.32 %3106.0B3271.120.58
GD2PJM
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line
PECO_CBO_NOTT785_SRT-A/* $ CHESCO $ PECO_CBO_NOTT785 $ K
BusAC105.2 %3106.0B3267.530.56
GD2PJM
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line
PS_P7-1_P2242+V2274_LT_SRT-A
TowerAC104.51 %3106.0B3246.00.61

Details for AH1-727 TP-8BRAMBLETON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 9354_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-727 TP-8BRAMBLETON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 9354_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.43 %
Rating:3776.92 MVA
Rating Type:B
MVA to Mitigate:4019.91
MW Contribution:0.21
Bus #Bus NameTypeMW Contribution
972285AH1-727 GEN
50/50
182.324
23776901DAM 5 HY
50/50
0.684
23757701ROUTE 16
50/50
0.112
23572301GUILF1
50/50
0.362
23572401GUILF2
50/50
0.362
966461AG1-515 GEN
50/50
0.53
23776801DAM 4 HY
50/50
0.571
23732901CHBRG_I12
50/50
3.008
200035PCHBTM 3
50/50
8.578
200202DELTA2 ST
50/50
2.612
200200DELTA2 CT1
50/50
1.462
200201DELTA2 CT2
50/50
1.462
200195DELTA ST
50/50
1.293
200192DELTA CT1
50/50
0.775
200193DELTA CT2
50/50
0.775
200194DELTA CT3
50/50
0.775
200034PCHBTM 2
50/50
51.243
200203Y1-065-STG
50/50
3.01
200204Y1-065-CTG1
50/50
1.896
200205Y1-065-CTG2
50/50
1.896
200052ROCKSP 1
50/50
22.49
200053ROCKSP 2
50/50
22.49
200054ROCKSP 3
50/50
22.261
200055ROCKSP 4
50/50
22.261
970279AG2-182 GEN
Solar/Wind Harmer
1.68
238141AE2-333 GEN1
Solar/Wind Harmer
0.391
238142AE2-333 GEN2
Solar/Wind Harmer
0.391
970651AG2-423 GEN
Solar/Wind Harmer
0.576
235020AA1-095 C
Solar/Wind Harmer
0
970429AG2-279 GEN
Solar/Wind Harmer
0.143
238208AF1-136 C
Solar/Wind Harmer
-0.001
237030AB1-096 C
Solar/Wind Harmer
-0.012
203982AD2-062_GEN
Solar/Wind Harmer
0.493
20390526W1-045 C
Solar/Wind Harmer
-0.001
233972AC1-094 C
Solar/Wind Harmer
-0.001
971149AH1-027 GEN
Solar/Wind Harmer
0.137
970695AG2-447 GEN
Solar/Wind Harmer
0.11
233987AB2-037 GEN
Solar/Wind Harmer
0
234033AF1-007_GEN
Solar/Wind Harmer
11.483
970545AG2-347 GEN
Solar/Wind Harmer
47.304
972133AH1-634 GEN
Solar/Wind Harmer
7.167
233923SMA
Solar/Wind Harmer
-0.001
233998TM1NIN_3.36
Solar/Wind Harmer
-0.001
233997TMININ_4.2
Solar/Wind Harmer
-0.001
233996TM1833_GEN
Solar/Wind Harmer
-0.001
233990AG1-397 GEN
Solar/Wind Harmer
0
233940AF2-379 C
Solar/Wind Harmer
-0.001
234015AF2-250 C
Solar/Wind Harmer
0
972177AH1-672 GEN
Solar/Wind Harmer
0.412
972069AH1-584 GEN
Solar/Wind Harmer
0.274
972071AH1-585 GEN
Solar/Wind Harmer
0.274
972073AH1-586 GEN
Solar/Wind Harmer
4.94
971747AH1-380 GEN
Solar/Wind Harmer
0.11
233990AG1-397 GEN
Solar/Wind Harmer
0.878
971195AH1-057 GEN
Solar/Wind Harmer
0.04
232426Y1-080 FULL
Solar/Wind Harmer
0
960671AF2-358 GEN
Solar/Wind Harmer
0.549
970277AG2-181 GEN
Solar/Wind Harmer
0.154
965821AG1-450 GEN
Solar/Wind Harmer
2.744
233946AB2-136 GEN
Solar/Wind Harmer
-0.001
233964AF2-378 GEN
Solar/Wind Harmer
0
234041AC1-190 GEN
Solar/Wind Harmer
0.274
233984AB2-036 GEN
Solar/Wind Harmer
0.504
233968AD2-076_GEN
Solar/Wind Harmer
0.268
234014AF1-036_GEN
Solar/Wind Harmer
0.11
970597AG2-380 GEN
Solar/Wind Harmer
2.19
234012AE2-112_GEN
Solar/Wind Harmer
0.093
971983AH1-536 GEN
Solar/Wind Harmer
0.229
205916AD1-020 GEN
Solar/Wind Harmer
0
205917AD1-020 ES
Solar/Wind Harmer
0
970453AG2-297 GEN
Solar/Wind Harmer
0.103
971553AH1-274 GEN
Solar/Wind Harmer
0.09
945431AF1-208 GEN
Solar/Wind Harmer
0.243
970997AG2-616 GEN
Solar/Wind Harmer
0.269
972141AH1-641 GEN
Solar/Wind Harmer
0.081
230430AE1-229_GEN
Solar/Wind Harmer
-0.001
228351V2-046C
Solar/Wind Harmer
-0.001
230433AD2-135 GEN
Solar/Wind Harmer
0
230422AE1-104_GEN1
Solar/Wind Harmer
22.342
230425AE1-104_GEN2
Solar/Wind Harmer
22.342
971011AG2-627 GEN
Solar/Wind Harmer
0.215
971535AH1-265 GEN
Solar/Wind Harmer
0.158
230407AD2-065 C
Solar/Wind Harmer
0
228754AB1-001 C
Solar/Wind Harmer
-0.001
205975AE2-345_GEN
Solar/Wind Harmer
0.376
219137THOSOLAR C
Solar/Wind Harmer
0
219623KINSLEYBEA C
Solar/Wind Harmer
0
219258KINSLEYDEP C
Solar/Wind Harmer
0
219766PARADISE C
Solar/Wind Harmer
-0.001
218660EHAMPSOLAR C
Solar/Wind Harmer
-0.001
203975AE1-071-GEN
Solar/Wind Harmer
-0.001
219907AC1-030 C
Solar/Wind Harmer
-0.001
219236SOUTHERNHQ C
Solar/Wind Harmer
0
219906AC1-017 C
Solar/Wind Harmer
-0.001
219615MILLCREEK C
Solar/Wind Harmer
-0.001
214067T20SOLAR
Solar/Wind Harmer
-0.001
207522AF2-254 C
Solar/Wind Harmer
0.053
207500AE2-000G1
Solar/Wind Harmer
20.831
207497AE2-000G2
Solar/Wind Harmer
20.831
207507AE2-000G3
Solar/Wind Harmer
20.831
207487AE2-000G4
Solar/Wind Harmer
20.831
970025AG2-016 GEN
Solar/Wind Harmer
0.105
971189AH1-054 GEN
Solar/Wind Harmer
0.044
971667AH1-334 GEN
Solar/Wind Harmer
0.102
219727YARDVSOLFA C
Solar/Wind Harmer
0
219276PARKLANDSO C
Solar/Wind Harmer
0
219817TRENTONSOL C
Solar/Wind Harmer
0
219620RIDERU C
Solar/Wind Harmer
-0.001
20714328BYD_X4-031
Solar/Wind Harmer
0.011
20714428HOW_X1-037
Solar/Wind Harmer
0
219918AC2-009 C
Solar/Wind Harmer
0
20720628TIN_W1-124
Solar/Wind Harmer
-0.001
20742028HF_AC1-207
Solar/Wind Harmer
-0.001
966131AG1-482 GEN
Solar/Wind Harmer
1.89
971521AH1-258 GEN
Solar/Wind Harmer
0.102
967451AG2-055 C O1
Solar/Wind Harmer
116.324
219612MATRIX C
Solar/Wind Harmer
0
218438BLK ROCK C
Solar/Wind Harmer
0
218526CNTRALGAS2 C
Solar/Wind Harmer
0
218524CNTRALGAS1 C
Solar/Wind Harmer
0
219249CENTRALDIV C
Solar/Wind Harmer
0
218428ETC SOLAR C
Solar/Wind Harmer
0
217213AMBOY SO C
Solar/Wind Harmer
-0.001
20673828FLE_V3-070
Solar/Wind Harmer
0.038
20675428EAM_W2-061
Solar/Wind Harmer
0
218449LINSOLAR C
Solar/Wind Harmer
0
217081WEATEXAS C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
217206BARNGR HS C
Solar/Wind Harmer
0
217208PARK ELE C
Solar/Wind Harmer
0
207439AE1-081 C O1
Solar/Wind Harmer
0
20676328BVR_Y1-020
Solar/Wind Harmer
0
20674628WNG_W3-110
Solar/Wind Harmer
-0.001
207511W3-106 GEN
Solar/Wind Harmer
0.026
205967AE2-211_GEN
Solar/Wind Harmer
0.388
971519AH1-257 GEN
Solar/Wind Harmer
0.099
971007AG2-625 GEN
Solar/Wind Harmer
0.101
971009AG2-626 GEN
Solar/Wind Harmer
0.064
207437AD2-070 GEN
Solar/Wind Harmer
-0.001
966181AG1-487 GEN
Solar/Wind Harmer
0
966181AG1-487 GEN
Solar/Wind Harmer
1.97
208862AG1-362 C
Solar/Wind Harmer
0.026
966111AG1-480 GEN
Solar/Wind Harmer
0
966111AG1-480 GEN
Solar/Wind Harmer
1.739
960921AF2-383 GEN
Solar/Wind Harmer
1.427
964991AG1-363 GEN
Solar/Wind Harmer
0
964991AG1-363 GEN
Solar/Wind Harmer
4.055
3141196NOKESVL
Solar/Wind Helper
3.781
316006AB2-029 C
Solar/Wind Helper
0.282
316045AC1-158 PL2
Solar/Wind Helper
3.124
316447AC1-158 HLD
Solar/Wind Helper
2.147
316044AC1-158 PL1
Solar/Wind Helper
0.977
316450AC1-158 RIC
Solar/Wind Helper
0.26
316411AF1-147_GEN1
Solar/Wind Helper
0.668
316415AF1-147_GEN2
Solar/Wind Helper
0.668
315651AD1-115 GEN
Solar/Wind Helper
2.001
316254AC1-120 GEN1
Solar/Wind Helper
0.788
316170AC1-121 GEN2
Solar/Wind Helper
0.263
316164AC1-076 GEN
Solar/Wind Helper
0.818
3141426STAFORD
Solar/Wind Helper
0.169
3132273ORANGE
Solar/Wind Helper
0.151
3147666LOUISA
Solar/Wind Helper
2.946
3147666LOUISA
Solar/Wind Helper
1.694
316192AB2-158 GEN
Solar/Wind Helper
1.041
966001AG1-469 GEN
Solar/Wind Helper
0.162
966881AG1-559 GEN
Solar/Wind Helper
0.229
944491AF1-114 GEN
Solar/Wind Helper
1.125
957971AF2-091 GEN
Solar/Wind Helper
0.383
316468AD1-105 GEN
Solar/Wind Helper
0.813
316223AC1-118
Solar/Wind Helper
0.219
3141906WESTMOR
Solar/Wind Helper
0.273
316337AD2-073 GEN
Solar/Wind Helper
0.216
316077AC2-138 C
Solar/Wind Helper
0.15
3141813NORNECK
Solar/Wind Helper
0.666
964211AG1-282 GEN
Solar/Wind Helper
0.213
3141726DUNNSVL
Solar/Wind Helper
2.655
316473AC1-191 GEN
Solar/Wind Helper
0.852
966871AG1-558 GEN
Solar/Wind Helper
0.213
316404AE1-155 C
Solar/Wind Helper
1.347
316484AD2-074 GEN
Solar/Wind Helper
0.908
316487AF1-042 GEN
Solar/Wind Helper
0.475
961951AG1-038 GEN
Solar/Wind Helper
0.475
316312AB1-027
Solar/Wind Helper
0.263
3142416OLDCHRC
Solar/Wind Helper
1.7
3142416OLDCHRC
Solar/Wind Helper
0.651
3141783LANCAST
Solar/Wind Helper
0.391
3141783LANCAST
Solar/Wind Helper
0.261
3138133OCRAN
Solar/Wind Helper
0.391
3138133OCRAN
Solar/Wind Helper
0.195
3141913WHIT STONE
Solar/Wind Helper
0.65
316314AB2-024 C
Solar/Wind Helper
0.208
316075AC2-137 C
Solar/Wind Helper
0.208
316233AE1-074 FULL
Solar/Wind Helper
0.208
3143526WINTERP
Solar/Wind Helper
3.372
3143526WINTERP
Solar/Wind Helper
3.372
316059AD1-063 C
Solar/Wind Helper
0.156
3141766HARMONY
Solar/Wind Helper
0.13
3143226MDLTHAN
Solar/Wind Helper
0.648
3143873LANEXA
Solar/Wind Helper
0.389
316203AE2-005 GEN
Solar/Wind Helper
1.353
315662AE1-191 GEN
Solar/Wind Helper
0.832
316280AD1-041 GEN
Solar/Wind Helper
0.52
315666AE1-190 GEN
Solar/Wind Helper
0.208
316441AF1-014 GEN
Solar/Wind Helper
0.207
957601AF2-054 GEN
Solar/Wind Helper
0.207
316156AD2-030 GEN
Solar/Wind Helper
0.206
3141873WAN 176
Solar/Wind Helper
0.129
3142433PROV 92
Solar/Wind Helper
2.585
3142543TWELFTH
Solar/Wind Helper
0.062
3142946ENON
Solar/Wind Helper
0.215
3142946ENON
Solar/Wind Helper
0.064
957831AF2-077 GEN
Solar/Wind Helper
0.205
316382AG1-145 C
Solar/Wind Helper
0.204
316159AE1-175 C
Solar/Wind Helper
0.204
316240AF1-291 C
Solar/Wind Helper
0.203
316132AB2-190 GEN1
Solar/Wind Helper
0.761
316458AB2-190 GEN2
Solar/Wind Helper
0.761
315697AD1-025 GEN
Solar/Wind Helper
1.514
316033AB2-134 GEN
Solar/Wind Helper
1.437
316369SG1_INVT
Solar/Wind Helper
0.989
315839AE2-212 C
Solar/Wind Helper
0.202
961611AG1-000B GEN
Solar/Wind Helper
0.894
316236AE1-162_GEN
Solar/Wind Helper
0.199
3145336SMITFLD
Solar/Wind Helper
2.479
3145336SMITFLD
Solar/Wind Helper
0.248
3143316POE
Solar/Wind Helper
2.454
316294AC1-161 GEN
Solar/Wind Helper
2.387
315773AC2-141 GEN
Solar/Wind Helper
2.387
3144536CHRHLND
Solar/Wind Helper
0.092
316381AD1-082 GEN
Solar/Wind Helper
0.673
316083AB2-161 GEN
Solar/Wind Helper
0.495
316375AC2-012 GEN
Solar/Wind Helper
1.165
316036AC1-147 C
Solar/Wind Helper
0.197
3144873MCLAUGH
Solar/Wind Helper
0.015
316316AC1-027 C
Solar/Wind Helper
0.173
316185AD1-033 GEN
Solar/Wind Helper
0.689
316072AD1-144
Solar/Wind Helper
0.147
3145506HICKORY
Solar/Wind Helper
2.445
3145506HICKORY
Solar/Wind Helper
1.467
3145506HICKORY
Solar/Wind Helper
0.367
316339AD2-160 GEN
Solar/Wind Helper
0.489
316388AE2-253 GEN
Solar/Wind Helper
0.489
316349AD2-085 GEN
Solar/Wind Helper
0.499
315833AF1-017_GEN
Solar/Wind Helper
0.391
316017AA1-139 ULT1
Solar/Wind Helper
0.587
316018AA1-139 ULT2
Solar/Wind Helper
0.587
3137176SLIGO L2192
Solar/Wind Helper
2.419
3146456SLIGO L269
Solar/Wind Helper
0.608
3146456SLIGO L269
Solar/Wind Helper
0.608
319010AE1-072 C
Solar/Wind Helper
1.464
316305AF2-043 C
Solar/Wind Helper
0.195
316246AF1-032 C
Solar/Wind Helper
0.146
3130086AYDLETT
Solar/Wind Helper
2.428
316320Y1-086
Solar/Wind Helper
0.194
313526AB2-022
Solar/Wind Helper
0.194
3146386ELIZ CT
Solar/Wind Helper
0.602
3146486SUNBURY
Solar/Wind Helper
0.601
3146486SUNBURY
Solar/Wind Helper
0.601
316313AB2-026
Solar/Wind Helper
0.193
316258AE1-075 C
Solar/Wind Helper
0.174
316405AF2-144 C
Solar/Wind Helper
0.164
316321Z2-027
Solar/Wind Helper
0.193
3145176PASQUOTANK
Solar/Wind Helper
0.372
3138216PACIFIC
Solar/Wind Helper
0.099
3146516WINFALL
Solar/Wind Helper
1.93
3146516WINFALL
Solar/Wind Helper
0.596
3146516WINFALL
Solar/Wind Helper
0.596
3146516WINFALL
Solar/Wind Helper
0.596
3146516WINFALL
Solar/Wind Helper
0.596
3146516WINFALL
Solar/Wind Helper
0.596
316315AB2-025 C
Solar/Wind Helper
0.191
3146626S HERTFORD
Solar/Wind Helper
0.592
3146626S HERTFORD
Solar/Wind Helper
0.592
3146626S HERTFORD
Solar/Wind Helper
0.592
3145273HOLLAND
Solar/Wind Helper
0.444
316336AC2-165 C
Solar/Wind Helper
0.944
315742AE1-103 GEN
Solar/Wind Helper
0.376
3130156CHOWAN
Solar/Wind Helper
0.582
3130156CHOWAN
Solar/Wind Helper
0.582
3130156CHOWAN
Solar/Wind Helper
0.582
3146376EDENTON
Solar/Wind Helper
0.582
315614AA2-178 GEN
Solar/Wind Helper
0.734
315816AE2-034 GEN
Solar/Wind Helper
0.55
3145663CRESWEL
Solar/Wind Helper
1.598
3130546PLYMOUTH
Solar/Wind Helper
0.562
3156081AA2-088 GEN
Solar/Wind Helper
0.902
315732AD1-074 GEN1
Solar/Wind Helper
1.351
315733AD1-074 GEN2
Solar/Wind Helper
1.351
315737AD1-076 GEN
Solar/Wind Helper
0.982
315735AD1-075 GEN1
Solar/Wind Helper
0.676
316065AD1-022 GEN
Solar/Wind Helper
0.717
316023GEN1_S
Solar/Wind Helper
0.447
316365GEN2_N
Solar/Wind Helper
0.447
3146206CASHIE
Solar/Wind Helper
0.556
3146206CASHIE
Solar/Wind Helper
0.556
3146206CASHIE
Solar/Wind Helper
0.556
3145893MURPHYS
Solar/Wind Helper
2.22
3145893MURPHYS
Solar/Wind Helper
1.776
3145893MURPHYS
Solar/Wind Helper
1.499
316318V4-068
Solar/Wind Helper
0.041
3145893MURPHYS
Solar/Wind Helper
0.999
3145893MURPHYS
Solar/Wind Helper
0.555
3145893MURPHYS
Solar/Wind Helper
0.555
3145893MURPHYS
Solar/Wind Helper
0.444
3146173TUNIS
Solar/Wind Helper
0.551
3146173TUNIS
Solar/Wind Helper
0.551
3146173TUNIS
Solar/Wind Helper
0.551
3146173TUNIS
Solar/Wind Helper
0.551
3156021HOLLOMANSOL
Solar/Wind Helper
0.881
316463AE2-346 GEN
Solar/Wind Helper
0.106
316140AB2-099
Solar/Wind Helper
0.044
961941AG1-037 GEN
Solar/Wind Helper
0.044
3145513AHOSKIE
Solar/Wind Helper
0.548
3145513AHOSKIE
Solar/Wind Helper
0.548
946281AF1-292 GEN
Solar/Wind Helper
0.131
966621AG1-532 GEN
Solar/Wind Helper
0.118
3146043SEABORD
Solar/Wind Helper
0.546
3145683EARLEYS
Solar/Wind Helper
1.091
3145683EARLEYS
Solar/Wind Helper
0.546
3145683EARLEYS
Solar/Wind Helper
0.546
3145683EARLEYS
Solar/Wind Helper
0.546
315607AA1-063A GEN
Solar/Wind Helper
0.656
3146263WOODLND
Solar/Wind Helper
0.543
3146263WOODLND
Solar/Wind Helper
0.543
316087AB2-174 GEN
Solar/Wind Helper
0.697
316181AB2-040 GEN
Solar/Wind Helper
0.695
313506AB2-031 GEN
Solar/Wind Helper
0.518
3142666NORTHAMPTON
Solar/Wind Helper
0.538
3142666NORTHAMPTON
Solar/Wind Helper
0.538
3142666NORTHAMPTON
Solar/Wind Helper
0.538
3142666NORTHAMPTON
Solar/Wind Helper
0.538
3142666NORTHAMPTON
Solar/Wind Helper
0.323
3145963POPLR C
Solar/Wind Helper
0.538
3145963POPLR C
Solar/Wind Helper
0.538
3137643SOCKMAN
Solar/Wind Helper
2.148
316011AB1-132 GEN
Solar/Wind Helper
12.891
316426AA2-053 GEN
Solar/Wind Helper
0.647
316190AA2-174 GEN
Solar/Wind Helper
0.043
316317KELFORD C
Solar/Wind Helper
0.199
3145823KELFORD
Solar/Wind Helper
0.536
3145823KELFORD
Solar/Wind Helper
0.536
3147043LAWRENC
Solar/Wind Helper
0.321
3145593CAROLNA
Solar/Wind Helper
0.535
3145593CAROLNA
Solar/Wind Helper
0.535
316174AB2-169 GEN
Solar/Wind Helper
0.635
3145783HORNRTN
Solar/Wind Helper
0.532
3146926FARMVIL
Solar/Wind Helper
0.319
3146926FARMVIL
Solar/Wind Helper
0.319
316322AB2-045
Solar/Wind Helper
0.169
3146776BUCKING
Solar/Wind Helper
2.121
3146776BUCKING
Solar/Wind Helper
0.212
3146776BUCKING
Solar/Wind Helper
0.191
3146776BUCKING
Solar/Wind Helper
0.172
3145796HORNRTN
Solar/Wind Helper
2.12
3145796HORNRTN
Solar/Wind Helper
1.749
3145796HORNRTN
Solar/Wind Helper
1.696
3145796HORNRTN
Solar/Wind Helper
1.59
3145796HORNRTN
Solar/Wind Helper
0.53
3145796HORNRTN
Solar/Wind Helper
0.53
3145796HORNRTN
Solar/Wind Helper
0.212
316478AD1-087 GEN
Solar/Wind Helper
0.545
316486AD2-202 GEN
Solar/Wind Helper
0.16
3146033SCOT NK
Solar/Wind Helper
2.109
942461AE2-259 GEN
Solar/Wind Helper
0.846
3147133PAMPLIN
Solar/Wind Helper
1.638
3147133PAMPLIN
Solar/Wind Helper
0.522
3147133PAMPLIN
Solar/Wind Helper
0.417
316210AC1-098 GEN
Solar/Wind Helper
0.752
316212AC1-099_GEN
Solar/Wind Helper
0.418
3145933PARMELE
Solar/Wind Helper
1.036
3145933PARMELE
Solar/Wind Helper
0.518
3145933PARMELE
Solar/Wind Helper
0.518
316274AC1-208 GEN
Solar/Wind Helper
0.664
316129AC1-054 GEN
Solar/Wind Helper
0.54
316034AC1-036 C
Solar/Wind Helper
0.114
3144303KENBRDG
Solar/Wind Helper
0.412
315785AD2-033 C
Solar/Wind Helper
1.074
316131AB2-060 GEN
Solar/Wind Helper
0.655
313527AB2-043 GEN
Solar/Wind Helper
0.409
316005AA1-067
Solar/Wind Helper
0.123
3145746EVERETS
Solar/Wind Helper
2.025
3145746EVERETS
Solar/Wind Helper
0.509
3145746EVERETS
Solar/Wind Helper
0.509
3145746EVERETS
Solar/Wind Helper
0.509
3145746EVERETS
Solar/Wind Helper
0.509
3145746EVERETS
Solar/Wind Helper
0.509
3145746EVERETS
Solar/Wind Helper
0.509
3145746EVERETS
Solar/Wind Helper
0.509
316239AB2-077_GEN
Solar/Wind Helper
0.163
316238AB2-078_GEN
Solar/Wind Helper
0.163
316237AB2-079_GEN
Solar/Wind Helper
0.163
315722AD1-056 GEN
Solar/Wind Helper
0.488
315724AD1-057 GEN
Solar/Wind Helper
0.269
315687AD1-152 GEN
Solar/Wind Helper
0.648
316327AA2-057 GEN
Solar/Wind Helper
0.607
316494AC1-189 GEN
Solar/Wind Helper
0.645
316420AA1-050 GEN
Solar/Wind Helper
0.64
316319Z2-044 C
Solar/Wind Helper
0.096
3146233WITAKRS
Solar/Wind Helper
1.974
3146233WITAKRS
Solar/Wind Helper
0.337
961671AG1-007 GEN
Solar/Wind Helper
0.075
3145573BETHELC
Solar/Wind Helper
0.496
3145573BETHELC
Solar/Wind Helper
0.496
3146073TAR RVR
Solar/Wind Helper
0.496
3146083TARBORO
Solar/Wind Helper
0.496
3146083TARBORO
Solar/Wind Helper
0.496
3138543CONSLDL
Solar/Wind Helper
0.327
3138266HYDRAULIC
Solar/Wind Helper
0.022
3138266HYDRAULIC
Solar/Wind Helper
0.014
3145543BTLEBRO
Solar/Wind Helper
0.488
3145543BTLEBRO
Solar/Wind Helper
0.488
3145543BTLEBRO
Solar/Wind Helper
0.488
3145543BTLEBRO
Solar/Wind Helper
0.391
316359AB2-059 GEN
Solar/Wind Helper
0.784
316049AB1-081 GEN
Solar/Wind Helper
0.627
3146843MT LREL
Solar/Wind Helper
0.485
3146843MT LREL
Solar/Wind Helper
0.485
316118AC1-105 GEN
Solar/Wind Helper
0.39
315821AE2-092 GEN
Solar/Wind Helper
1.052
316248AF1-058 C
Solar/Wind Helper
0.15
3147173SINAI
Solar/Wind Helper
0.467
3147243WELCO
Solar/Wind Helper
0.292
270494AE1-108_GEN
Solar/Wind Helper
1.092
316003AC1-222 GEN
Solar/Wind Helper
0.472
316222AC1-221 GEN
Solar/Wind Helper
0.515
316283AC2-100 C
Solar/Wind Helper
0.478
3148013FISHERV
Solar/Wind Helper
0.414
3148133STUARTS
Solar/Wind Helper
0.249
3148013FISHERV
Solar/Wind Helper
0.238
316123AC1-075 GEN
Solar/Wind Helper
0.518
270455AD2-022 GEN
Solar/Wind Helper
0.595
270457AD2-023 GEN
Solar/Wind Helper
0.334
316499AE2-029_GEN
Solar/Wind Helper
0.304
3147983MERCK5
Solar/Wind Helper
0.149
3148463FAIRFLD
Solar/Wind Helper
0.359
3132123MT JACKSON
Solar/Wind Helper
1.12
237061AD1-155 GEN
Solar/Wind Helper
0.408
3147123OTTER R
Solar/Wind Helper
0.2
270016AE1-250 BESS
Solar/Wind Helper
0.399
270013AE1-250 PV
Solar/Wind Helper
0.399
316217AC1-145 GEN
Solar/Wind Helper
0.258
316197AC1-042 GEN
Solar/Wind Helper
0.217
3147312GRETNA
Solar/Wind Helper
0.257
3146802CHATHAM
Solar/Wind Helper
0.241
3147312GRETNA
Solar/Wind Helper
0.064
270197AD1-017 GEN1
Solar/Wind Helper
0.307
270574AD1-017 GEN2
Solar/Wind Helper
0.307
G-007ALTFEXP_G-007A->PJM
CMTX
25.204
HAMLETPJM->LTFIMP_HAMLET
CLTF
6.711
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.497
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
11.019
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
1.982
BlueGrassPJM->LTFIMP_BlueG
CLTF
6.238
CBM NorthLTFEXP_CBM-N->PJM
CBM
43.667
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
67.353

Details for CHAN-01DOUBS 500.0 kV Ckt 1 line l/o PJM_500_BG_P4_5_CNSTN_C_SRT-A


Base Case Flowgate

Area:AP/PJM
Facility Description:
CHAN-01DOUBS 500.0 kV Ckt 1 line
Contingency Name:
PJM_500_BG_P4_5_CNSTN_C_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.17 %
Rating:4595.0 MVA
Rating Type:B
MVA to Mitigate:5338.09
MW Contribution:0.49
Bus #Bus NameTypeMW Contribution
200035PCHBTM 3
50/50
23.165
200202DELTA2 ST
50/50
7.071
200200DELTA2 CT1
50/50
3.958
200201DELTA2 CT2
50/50
3.958
200195DELTA ST
50/50
3.498
200192DELTA CT1
50/50
2.098
200193DELTA CT2
50/50
2.098
200194DELTA CT3
50/50
2.098
200034PCHBTM 2
50/50
138.633
200203Y1-065-STG
50/50
7.997
200204Y1-065-CTG1
50/50
5.036
200205Y1-065-CTG2
50/50
5.036
200052ROCKSP 1
50/50
59.746
200053ROCKSP 2
50/50
59.746
200054ROCKSP 3
50/50
59.14
200055ROCKSP 4
50/50
59.14
971149AH1-027 GEN
Solar/Wind Harmer
0.331
233972AC1-094 C
Solar/Wind Harmer
-0.001
970695AG2-447 GEN
Solar/Wind Harmer
0.265
234033AF1-007_GEN
Solar/Wind Harmer
27.672
970545AG2-347 GEN
Solar/Wind Harmer
113.991
972133AH1-634 GEN
Solar/Wind Harmer
17.271
233987AB2-037 GEN
Solar/Wind Harmer
0
972177AH1-672 GEN
Solar/Wind Harmer
0.992
972069AH1-584 GEN
Solar/Wind Harmer
0.661
972071AH1-585 GEN
Solar/Wind Harmer
0.661
972073AH1-586 GEN
Solar/Wind Harmer
11.902
971747AH1-380 GEN
Solar/Wind Harmer
0.264
233923SMA
Solar/Wind Harmer
-0.001
233998TM1NIN_3.36
Solar/Wind Harmer
-0.001
233997TMININ_4.2
Solar/Wind Harmer
-0.001
233996TM1833_GEN
Solar/Wind Harmer
-0.001
233990AG1-397 GEN
Solar/Wind Harmer
0
233990AG1-397 GEN
Solar/Wind Harmer
2.116
233940AF2-379 C
Solar/Wind Harmer
-0.001
234015AF2-250 C
Solar/Wind Harmer
-0.001
971195AH1-057 GEN
Solar/Wind Harmer
0.095
960671AF2-358 GEN
Solar/Wind Harmer
1.321
965821AG1-450 GEN
Solar/Wind Harmer
6.606
232426Y1-080 FULL
Solar/Wind Harmer
0
970277AG2-181 GEN
Solar/Wind Harmer
0.37
233946AB2-136 GEN
Solar/Wind Harmer
-0.001
233964AF2-378 GEN
Solar/Wind Harmer
0.001
234041AC1-190 GEN
Solar/Wind Harmer
0.66
233984AB2-036 GEN
Solar/Wind Harmer
1.208
233968AD2-076_GEN
Solar/Wind Harmer
0.641
234014AF1-036_GEN
Solar/Wind Harmer
0.262
970597AG2-380 GEN
Solar/Wind Harmer
5.235
234012AE2-112_GEN
Solar/Wind Harmer
0.222
971983AH1-536 GEN
Solar/Wind Harmer
0.545
970453AG2-297 GEN
Solar/Wind Harmer
0.237
971553AH1-274 GEN
Solar/Wind Harmer
0.208
945431AF1-208 GEN
Solar/Wind Harmer
0.559
970997AG2-616 GEN
Solar/Wind Harmer
0.62
972141AH1-641 GEN
Solar/Wind Harmer
0.186
230422AE1-104_GEN1
Solar/Wind Harmer
51.422
230425AE1-104_GEN2
Solar/Wind Harmer
51.422
230430AE1-229_GEN
Solar/Wind Harmer
-0.001
230433AD2-135 GEN
Solar/Wind Harmer
0
228351V2-046C
Solar/Wind Harmer
-0.001
971011AG2-627 GEN
Solar/Wind Harmer
0.495
971535AH1-265 GEN
Solar/Wind Harmer
0.364
228754AB1-001 C
Solar/Wind Harmer
-0.001
230407AD2-065 C
Solar/Wind Harmer
0
219137THOSOLAR C
Solar/Wind Harmer
0.001
219623KINSLEYBEA C
Solar/Wind Harmer
-0.001
219258KINSLEYDEP C
Solar/Wind Harmer
0
218660EHAMPSOLAR C
Solar/Wind Harmer
-0.001
219766PARADISE C
Solar/Wind Harmer
-0.001
219907AC1-030 C
Solar/Wind Harmer
-0.001
219236SOUTHERNHQ C
Solar/Wind Harmer
-0.001
219906AC1-017 C
Solar/Wind Harmer
-0.001
219615MILLCREEK C
Solar/Wind Harmer
-0.001
214067T20SOLAR
Solar/Wind Harmer
-0.001
207522AF2-254 C
Solar/Wind Harmer
0.119
207500AE2-000G1
Solar/Wind Harmer
46.467
207497AE2-000G2
Solar/Wind Harmer
46.467
207507AE2-000G3
Solar/Wind Harmer
46.467
207487AE2-000G4
Solar/Wind Harmer
46.467
970025AG2-016 GEN
Solar/Wind Harmer
0.234
971189AH1-054 GEN
Solar/Wind Harmer
0.098
971667AH1-334 GEN
Solar/Wind Harmer
0.227
219727YARDVSOLFA C
Solar/Wind Harmer
0.001
219276PARKLANDSO C
Solar/Wind Harmer
0
219620RIDERU C
Solar/Wind Harmer
-0.001
219817TRENTONSOL C
Solar/Wind Harmer
0.001
20714328BYD_X4-031
Solar/Wind Harmer
0.023
20714428HOW_X1-037
Solar/Wind Harmer
-0.001
219918AC2-009 C
Solar/Wind Harmer
0
20720628TIN_W1-124
Solar/Wind Harmer
-0.001
20742028HF_AC1-207
Solar/Wind Harmer
-0.001
971521AH1-258 GEN
Solar/Wind Harmer
0.223
967451AG2-055 C O1
Solar/Wind Harmer
254.589
219612MATRIX C
Solar/Wind Harmer
0.001
218438BLK ROCK C
Solar/Wind Harmer
-0.001
218526CNTRALGAS2 C
Solar/Wind Harmer
0.001
218524CNTRALGAS1 C
Solar/Wind Harmer
0.001
218428ETC SOLAR C
Solar/Wind Harmer
0
217213AMBOY SO C
Solar/Wind Harmer
-0.001
219249CENTRALDIV C
Solar/Wind Harmer
-0.001
20673828FLE_V3-070
Solar/Wind Harmer
0.081
20675428EAM_W2-061
Solar/Wind Harmer
0
218449LINSOLAR C
Solar/Wind Harmer
0.001
217081WEATEXAS C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
217206BARNGR HS C
Solar/Wind Harmer
-0.001
217208PARK ELE C
Solar/Wind Harmer
0
207439AE1-081 C O1
Solar/Wind Harmer
0.001
20676328BVR_Y1-020
Solar/Wind Harmer
-0.001
20674628WNG_W3-110
Solar/Wind Harmer
-0.001
207511W3-106 GEN
Solar/Wind Harmer
0.053
971009AG2-626 GEN
Solar/Wind Harmer
0.133
971007AG2-625 GEN
Solar/Wind Harmer
0.208
971519AH1-257 GEN
Solar/Wind Harmer
0.205
207437AD2-070 GEN
Solar/Wind Harmer
-0.001
966181AG1-487 GEN
Solar/Wind Harmer
0
966181AG1-487 GEN
Solar/Wind Harmer
4.017
966111AG1-480 GEN
Solar/Wind Harmer
0
966111AG1-480 GEN
Solar/Wind Harmer
3.549
970095AG2-074 GEN
Solar/Wind Harmer
0.366
208972BECR K09
Solar/Wind Harmer
2.693
209027LOR2_Q27
Solar/Wind Harmer
10.76
212266LOR1
Solar/Wind Harmer
0.201
970237AG2-161 GEN
Solar/Wind Harmer
0.237
961541AF2-445A GEN
Solar/Wind Harmer
0.188
209029WAYMART-WD
Solar/Wind Harmer
7.167
209142AF1-226 GEN
Solar/Wind Harmer
0.328
209093AE2-110 GEN
Solar/Wind Harmer
0.188
209120AE2-241 GEN
Solar/Wind Harmer
0.188
209045AE2-271 GEN
Solar/Wind Harmer
0.948
209059AE2-084 GEN
Solar/Wind Harmer
0.185
970665AG2-430 GEN
Solar/Wind Harmer
0.55
209130AF1-271A GEN
Solar/Wind Harmer
0.156
208862AG1-362 C
Solar/Wind Harmer
0.043
970679AG2-439 GEN
Solar/Wind Harmer
0.064
200917MEHOOPANY_G
Solar/Wind Harmer
8.98
205967AE2-211_GEN
Solar/Wind Harmer
0.417
3138216PACIFIC
Solar/Wind Helper
0.08
316411AF1-147_GEN1
Solar/Wind Helper
0.383
316415AF1-147_GEN2
Solar/Wind Helper
0.383
3141196NOKESVL
Solar/Wind Helper
1.85
316006AB2-029 C
Solar/Wind Helper
0.143
238175AF1-290_GEN
Solar/Wind Helper
0.571
3141426STAFORD
Solar/Wind Helper
0.097
315651AD1-115 GEN
Solar/Wind Helper
1.065
316045AC1-158 PL2
Solar/Wind Helper
1.652
316447AC1-158 HLD
Solar/Wind Helper
1.136
316044AC1-158 PL1
Solar/Wind Helper
0.517
316450AC1-158 RIC
Solar/Wind Helper
0.138
316254AC1-120 GEN1
Solar/Wind Helper
0.424
316170AC1-121 GEN2
Solar/Wind Helper
0.141
316164AC1-076 GEN
Solar/Wind Helper
0.442
238169AE2-226 GEN1
Solar/Wind Helper
0.349
238170AE2-226 GEN2
Solar/Wind Helper
0.349
964441AG1-307 GEN
Solar/Wind Helper
0.559
3132273ORANGE
Solar/Wind Helper
0.086
3147666LOUISA
Solar/Wind Helper
1.714
3147666LOUISA
Solar/Wind Helper
0.986
316192AB2-158 GEN
Solar/Wind Helper
0.607
966881AG1-559 GEN
Solar/Wind Helper
0.137
966001AG1-469 GEN
Solar/Wind Helper
0.096
944491AF1-114 GEN
Solar/Wind Helper
0.684
957971AF2-091 GEN
Solar/Wind Helper
0.232
316468AD1-105 GEN
Solar/Wind Helper
0.501
238152AF2-075_GEN
Solar/Wind Helper
0.338
238147AE2-230_GEN1
Solar/Wind Helper
0.474
238148AE2-230_GEN2
Solar/Wind Helper
0.474
238149AF1-291A_GEN
Solar/Wind Helper
0.068
316223AC1-118
Solar/Wind Helper
0.135
3141906WESTMOR
Solar/Wind Helper
0.168
23546401DTGZ2-030
Solar/Wind Helper
0.067
316337AD2-073 GEN
Solar/Wind Helper
0.135
316077AC2-138 C
Solar/Wind Helper
0.094
3141813NORNECK
Solar/Wind Helper
0.417
964211AG1-282 GEN
Solar/Wind Helper
0.134
3141726DUNNSVL
Solar/Wind Helper
1.668
316473AC1-191 GEN
Solar/Wind Helper
0.536
966871AG1-558 GEN
Solar/Wind Helper
0.134
237061AD1-155 GEN
Solar/Wind Helper
0.502
316404AE1-155 C
Solar/Wind Helper
0.849
316484AD2-074 GEN
Solar/Wind Helper
0.574
316487AF1-042 GEN
Solar/Wind Helper
0.3
961951AG1-038 GEN
Solar/Wind Helper
0.3
316312AB1-027
Solar/Wind Helper
0.167
3142416OLDCHRC
Solar/Wind Helper
1.078
3142416OLDCHRC
Solar/Wind Helper
0.413
3141783LANCAST
Solar/Wind Helper
0.248
3141783LANCAST
Solar/Wind Helper
0.166
3138133OCRAN
Solar/Wind Helper
0.248
3138133OCRAN
Solar/Wind Helper
0.124
3141913WHIT STONE
Solar/Wind Helper
0.414
316075AC2-137 C
Solar/Wind Helper
0.133
316314AB2-024 C
Solar/Wind Helper
0.133
316059AD1-063 C
Solar/Wind Helper
0.1
3141766HARMONY
Solar/Wind Helper
0.083
316203AE2-005 GEN
Solar/Wind Helper
0.863
315662AE1-191 GEN
Solar/Wind Helper
0.531
316280AD1-041 GEN
Solar/Wind Helper
0.332
315666AE1-190 GEN
Solar/Wind Helper
0.133
316441AF1-014 GEN
Solar/Wind Helper
0.132
3143873LANEXA
Solar/Wind Helper
0.248
957601AF2-054 GEN
Solar/Wind Helper
0.132
316156AD2-030 GEN
Solar/Wind Helper
0.131
3141873WAN 176
Solar/Wind Helper
0.083
316233AE1-074 FULL
Solar/Wind Helper
0.133
3143526WINTERP
Solar/Wind Helper
2.147
3143526WINTERP
Solar/Wind Helper
2.147
3142433PROV 92
Solar/Wind Helper
1.651
3143226MDLTHAN
Solar/Wind Helper
0.413
3142543TWELFTH
Solar/Wind Helper
0.04
3142946ENON
Solar/Wind Helper
0.138
3142946ENON
Solar/Wind Helper
0.041
957831AF2-077 GEN
Solar/Wind Helper
0.132
316382AG1-145 C
Solar/Wind Helper
0.132
316159AE1-175 C
Solar/Wind Helper
0.132
316240AF1-291 C
Solar/Wind Helper
0.132
316132AB2-190 GEN1
Solar/Wind Helper
0.493
316458AB2-190 GEN2
Solar/Wind Helper
0.493
315697AD1-025 GEN
Solar/Wind Helper
0.984
316033AB2-134 GEN
Solar/Wind Helper
0.934
316369SG1_INVT
Solar/Wind Helper
0.643
315839AE2-212 C
Solar/Wind Helper
0.131
961611AG1-000B GEN
Solar/Wind Helper
0.583
316236AE1-162_GEN
Solar/Wind Helper
0.131
3145336SMITFLD
Solar/Wind Helper
1.625
3145336SMITFLD
Solar/Wind Helper
0.162
3143316POE
Solar/Wind Helper
1.608
316294AC1-161 GEN
Solar/Wind Helper
1.565
315773AC2-141 GEN
Solar/Wind Helper
1.565
316313AB2-026
Solar/Wind Helper
0.13
316258AE1-075 C
Solar/Wind Helper
0.117
316405AF2-144 C
Solar/Wind Helper
0.111
3144536CHRHLND
Solar/Wind Helper
0.061
316381AD1-082 GEN
Solar/Wind Helper
0.443
316083AB2-161 GEN
Solar/Wind Helper
0.325
316375AC2-012 GEN
Solar/Wind Helper
0.767
316036AC1-147 C
Solar/Wind Helper
0.13
3144873MCLAUGH
Solar/Wind Helper
0.01
316316AC1-027 C
Solar/Wind Helper
0.114
316185AD1-033 GEN
Solar/Wind Helper
0.455
316072AD1-144
Solar/Wind Helper
0.097
3145506HICKORY
Solar/Wind Helper
1.616
3145506HICKORY
Solar/Wind Helper
0.97
3145506HICKORY
Solar/Wind Helper
0.242
316336AC2-165 C
Solar/Wind Helper
0.649
316349AD2-085 GEN
Solar/Wind Helper
0.331
316339AD2-160 GEN
Solar/Wind Helper
0.324
316388AE2-253 GEN
Solar/Wind Helper
0.324
315833AF1-017_GEN
Solar/Wind Helper
0.259
235020AA1-095 C
Solar/Wind Helper
0.027
316017AA1-139 ULT1
Solar/Wind Helper
0.389
316018AA1-139 ULT2
Solar/Wind Helper
0.389
3137176SLIGO L2192
Solar/Wind Helper
1.605
3146456SLIGO L269
Solar/Wind Helper
0.403
3146456SLIGO L269
Solar/Wind Helper
0.403
316305AF2-043 C
Solar/Wind Helper
0.13
316246AF1-032 C
Solar/Wind Helper
0.097
319010AE1-072 C
Solar/Wind Helper
0.972
23777901MDS_W4-102
Solar/Wind Helper
0.13
3130086AYDLETT
Solar/Wind Helper
1.612
316320Y1-086
Solar/Wind Helper
0.129
313526AB2-022
Solar/Wind Helper
0.129
3146386ELIZ CT
Solar/Wind Helper
0.402
3146486SUNBURY
Solar/Wind Helper
0.402
3146486SUNBURY
Solar/Wind Helper
0.402
316321Z2-027
Solar/Wind Helper
0.129
3145176PASQUOTANK
Solar/Wind Helper
0.249
3146516WINFALL
Solar/Wind Helper
1.297
3146516WINFALL
Solar/Wind Helper
0.4
3146516WINFALL
Solar/Wind Helper
0.4
3146516WINFALL
Solar/Wind Helper
0.4
3146516WINFALL
Solar/Wind Helper
0.4
3146516WINFALL
Solar/Wind Helper
0.4
3146626S HERTFORD
Solar/Wind Helper
0.4
3146626S HERTFORD
Solar/Wind Helper
0.4
3146626S HERTFORD
Solar/Wind Helper
0.4
316315AB2-025 C
Solar/Wind Helper
0.128
3145273HOLLAND
Solar/Wind Helper
0.3
315742AE1-103 GEN
Solar/Wind Helper
0.256
3130156CHOWAN
Solar/Wind Helper
0.397
3130156CHOWAN
Solar/Wind Helper
0.397
3130156CHOWAN
Solar/Wind Helper
0.397
3146376EDENTON
Solar/Wind Helper
0.397
3132123MT JACKSON
Solar/Wind Helper
1.239
315614AA2-178 GEN
Solar/Wind Helper
0.507
315816AE2-034 GEN
Solar/Wind Helper
0.38
3145663CRESWEL
Solar/Wind Helper
1.105
3138266HYDRAULIC
Solar/Wind Helper
0.018
3138266HYDRAULIC
Solar/Wind Helper
0.011
316322AB2-045
Solar/Wind Helper
0.125
3146776BUCKING
Solar/Wind Helper
1.573
3146776BUCKING
Solar/Wind Helper
0.157
3146776BUCKING
Solar/Wind Helper
0.142
3146776BUCKING
Solar/Wind Helper
0.127
3130546PLYMOUTH
Solar/Wind Helper
0.393
3156081AA2-088 GEN
Solar/Wind Helper
0.631
315732AD1-074 GEN1
Solar/Wind Helper
0.946
315733AD1-074 GEN2
Solar/Wind Helper
0.946
315737AD1-076 GEN
Solar/Wind Helper
0.687
315735AD1-075 GEN1
Solar/Wind Helper
0.473
316065AD1-022 GEN
Solar/Wind Helper
0.503
3146926FARMVIL
Solar/Wind Helper
0.235
3146926FARMVIL
Solar/Wind Helper
0.235
316023GEN1_S
Solar/Wind Helper
0.314
316365GEN2_N
Solar/Wind Helper
0.314
3146206CASHIE
Solar/Wind Helper
0.391
3146206CASHIE
Solar/Wind Helper
0.391
3146206CASHIE
Solar/Wind Helper
0.391
3145893MURPHYS
Solar/Wind Helper
1.565
3145893MURPHYS
Solar/Wind Helper
1.252
3145893MURPHYS
Solar/Wind Helper
1.056
316318V4-068
Solar/Wind Helper
0.029
3145893MURPHYS
Solar/Wind Helper
0.704
3145893MURPHYS
Solar/Wind Helper
0.391
3145893MURPHYS
Solar/Wind Helper
0.391
3145893MURPHYS
Solar/Wind Helper
0.313
3146173TUNIS
Solar/Wind Helper
0.39
3146173TUNIS
Solar/Wind Helper
0.39
3146173TUNIS
Solar/Wind Helper
0.39
3146173TUNIS
Solar/Wind Helper
0.39
3147983MERCK5
Solar/Wind Helper
0.156
316097T157 G90
Solar/Wind Helper
0.257
316095T157 G97
Solar/Wind Helper
0.257
315821AE2-092 GEN
Solar/Wind Helper
0.864
3156021HOLLOMANSOL
Solar/Wind Helper
0.625
316463AE2-346 GEN
Solar/Wind Helper
0.075
316140AB2-099
Solar/Wind Helper
0.031
961941AG1-037 GEN
Solar/Wind Helper
0.031
3145513AHOSKIE
Solar/Wind Helper
0.389
3145513AHOSKIE
Solar/Wind Helper
0.389
942461AE2-259 GEN
Solar/Wind Helper
0.626
946281AF1-292 GEN
Solar/Wind Helper
0.093
966621AG1-532 GEN
Solar/Wind Helper
0.084
3146043SEABORD
Solar/Wind Helper
0.389
3145683EARLEYS
Solar/Wind Helper
0.778
3145683EARLEYS
Solar/Wind Helper
0.389
3145683EARLEYS
Solar/Wind Helper
0.389
3145683EARLEYS
Solar/Wind Helper
0.389
315607AA1-063A GEN
Solar/Wind Helper
0.468
316087AB2-174 GEN
Solar/Wind Helper
0.499
316499AE2-029_GEN
Solar/Wind Helper
0.312
3146263WOODLND
Solar/Wind Helper
0.388
3146263WOODLND
Solar/Wind Helper
0.388
316181AB2-040 GEN
Solar/Wind Helper
0.499
313506AB2-031 GEN
Solar/Wind Helper
0.372
3147133PAMPLIN
Solar/Wind Helper
1.217
3147133PAMPLIN
Solar/Wind Helper
0.387
3147133PAMPLIN
Solar/Wind Helper
0.31
3137643SOCKMAN
Solar/Wind Helper
1.547
3142666NORTHAMPTON
Solar/Wind Helper
0.387
3142666NORTHAMPTON
Solar/Wind Helper
0.387
3142666NORTHAMPTON
Solar/Wind Helper
0.387
3142666NORTHAMPTON
Solar/Wind Helper
0.387
3142666NORTHAMPTON
Solar/Wind Helper
0.232
3147043LAWRENC
Solar/Wind Helper
0.232
316426AA2-053 GEN
Solar/Wind Helper
0.466
316190AA2-174 GEN
Solar/Wind Helper
0.031
3145963POPLR C
Solar/Wind Helper
0.387
3145963POPLR C
Solar/Wind Helper
0.387
316011AB1-132 GEN
Solar/Wind Helper
9.287
316317KELFORD C
Solar/Wind Helper
0.144
3145823KELFORD
Solar/Wind Helper
0.387
3145823KELFORD
Solar/Wind Helper
0.387
3145593CAROLNA
Solar/Wind Helper
0.387
3145593CAROLNA
Solar/Wind Helper
0.387
316174AB2-169 GEN
Solar/Wind Helper
0.459
316478AD1-087 GEN
Solar/Wind Helper
0.398
316486AD2-202 GEN
Solar/Wind Helper
0.117
3145783HORNRTN
Solar/Wind Helper
0.386
3148013FISHERV
Solar/Wind Helper
0.386
3148133STUARTS
Solar/Wind Helper
0.232
3148013FISHERV
Solar/Wind Helper
0.222
3145796HORNRTN
Solar/Wind Helper
1.541
3145796HORNRTN
Solar/Wind Helper
1.271
3145796HORNRTN
Solar/Wind Helper
1.233
3145796HORNRTN
Solar/Wind Helper
1.156
3145796HORNRTN
Solar/Wind Helper
0.385
3145796HORNRTN
Solar/Wind Helper
0.385
3145796HORNRTN
Solar/Wind Helper
0.154
316034AC1-036 C
Solar/Wind Helper
0.085
3144303KENBRDG
Solar/Wind Helper
0.308
3146033SCOT NK
Solar/Wind Helper
1.539
315785AD2-033 C
Solar/Wind Helper
0.803
316129AC1-054 GEN
Solar/Wind Helper
0.4
316210AC1-098 GEN
Solar/Wind Helper
0.554
316212AC1-099_GEN
Solar/Wind Helper
0.308
316131AB2-060 GEN
Solar/Wind Helper
0.492
313527AB2-043 GEN
Solar/Wind Helper
0.307
3145933PARMELE
Solar/Wind Helper
0.765
3145933PARMELE
Solar/Wind Helper
0.382
3145933PARMELE
Solar/Wind Helper
0.382
316274AC1-208 GEN
Solar/Wind Helper
0.491
316239AB2-077_GEN
Solar/Wind Helper
0.123
316238AB2-078_GEN
Solar/Wind Helper
0.123
316237AB2-079_GEN
Solar/Wind Helper
0.123
23583801GRNGAP
Solar/Wind Helper
0.637
316005AA1-067
Solar/Wind Helper
0.092
3145746EVERETS
Solar/Wind Helper
1.513
3145746EVERETS
Solar/Wind Helper
0.38
3145746EVERETS
Solar/Wind Helper
0.38
3145746EVERETS
Solar/Wind Helper
0.38
3145746EVERETS
Solar/Wind Helper
0.38
3145746EVERETS
Solar/Wind Helper
0.38
3145746EVERETS
Solar/Wind Helper
0.38
3145746EVERETS
Solar/Wind Helper
0.38
315687AD1-152 GEN
Solar/Wind Helper
0.489
315722AD1-056 GEN
Solar/Wind Helper
0.366
315724AD1-057 GEN
Solar/Wind Helper
0.201
316327AA2-057 GEN
Solar/Wind Helper
0.457
226929AD2-058 GEN
Solar/Wind Helper
0.034
316494AC1-189 GEN
Solar/Wind Helper
0.487
270494AE1-108_GEN
Solar/Wind Helper
0.909
316420AA1-050 GEN
Solar/Wind Helper
0.486
316319Z2-044 C
Solar/Wind Helper
0.073
3146233WITAKRS
Solar/Wind Helper
1.502
3146233WITAKRS
Solar/Wind Helper
0.257
961671AG1-007 GEN
Solar/Wind Helper
0.057
3145573BETHELC
Solar/Wind Helper
0.377
3145573BETHELC
Solar/Wind Helper
0.377
3146073TAR RVR
Solar/Wind Helper
0.377
3146083TARBORO
Solar/Wind Helper
0.377
3146083TARBORO
Solar/Wind Helper
0.377
238208AF1-136 C
Solar/Wind Helper
0.096
3138543CONSLDL
Solar/Wind Helper
0.249
3146843MT LREL
Solar/Wind Helper
0.377
3146843MT LREL
Solar/Wind Helper
0.377
3145543BTLEBRO
Solar/Wind Helper
0.376
3145543BTLEBRO
Solar/Wind Helper
0.376
3145543BTLEBRO
Solar/Wind Helper
0.376
3145543BTLEBRO
Solar/Wind Helper
0.3
316359AB2-059 GEN
Solar/Wind Helper
0.603
316049AB1-081 GEN
Solar/Wind Helper
0.483
238108AE1-109 GEN1
Solar/Wind Helper
0.04
238109AE1-109 GEN2
Solar/Wind Helper
0.04
238110AE1-109 GEN3
Solar/Wind Helper
0.04
316118AC1-105 GEN
Solar/Wind Helper
0.307
238221AF1-254 C O1
Solar/Wind Helper
0.12
3148463FAIRFLD
Solar/Wind Helper
0.374
237034AC2-136 C
Solar/Wind Helper
0.071
316248AF1-058 C
Solar/Wind Helper
0.12
3147173SINAI
Solar/Wind Helper
0.372
3147243WELCO
Solar/Wind Helper
0.233
316003AC1-222 GEN
Solar/Wind Helper
0.385
227287AC2-120 GEN
Solar/Wind Helper
0.163
226910AB2-157 C
Solar/Wind Helper
0.015
316222AC1-221 GEN
Solar/Wind Helper
0.437
316283AC2-100 C
Solar/Wind Helper
0.407
237080AD1-060 GEN
Solar/Wind Helper
0.087
316123AC1-075 GEN
Solar/Wind Helper
0.462
964991AG1-363 GEN
Solar/Wind Helper
1.702
270455AD2-022 GEN
Solar/Wind Helper
0.544
270457AD2-023 GEN
Solar/Wind Helper
0.306
237038AE2-054 C
Solar/Wind Helper
0.112
235067AD1-061 GEN
Solar/Wind Helper
0.111
3147123OTTER R
Solar/Wind Helper
0.207
316217AC1-145 GEN
Solar/Wind Helper
0.275
316197AC1-042 GEN
Solar/Wind Helper
0.231
3147312GRETNA
Solar/Wind Helper
0.274
3146802CHATHAM
Solar/Wind Helper
0.257
3147312GRETNA
Solar/Wind Helper
0.069
270016AE1-250 BESS
Solar/Wind Helper
0.413
270013AE1-250 PV
Solar/Wind Helper
0.413
237085AD2-009_GEN
Solar/Wind Helper
0.384
270197AD1-017 GEN1
Solar/Wind Helper
0.328
270574AD1-017 GEN2
Solar/Wind Helper
0.328
237002AB1-128_GEN
Solar/Wind Helper
0.108
270173AC1-122 GEN
Solar/Wind Helper
0.411
270018AE2-047 C O1
Solar/Wind Helper
0.269
237001AB1-127_GEN
Solar/Wind Helper
0.107
943811AF1-049 GEN
Solar/Wind Helper
0.663
23750701CROSSCHOOL
Solar/Wind Helper
0.143
235062AE1-101 C1
Solar/Wind Helper
0.397
235063AE1-101 C2
Solar/Wind Helper
0.397
270069AE2-166 C O1
Solar/Wind Helper
0.473
270336AE1-100 GEN
Solar/Wind Helper
0.347
238120AE2-309 GEN
Solar/Wind Helper
0.103
235531U2-073 GEN
Solar/Wind Helper
0.3
23779801AA1-109
Solar/Wind Helper
0.046
238126S14_GEN_1
Solar/Wind Helper
0.32
238127S14_GEN_2
Solar/Wind Helper
0.32
235054AD2-180 GEN
Solar/Wind Helper
0.303
958121AF2-106 GEN
Solar/Wind Helper
0.761
238185AF2-356 C
Solar/Wind Helper
0.884
238118U2-030_1
Solar/Wind Helper
0.04
270214AC2-123 GEN
Solar/Wind Helper
0.376
966391AG1-508 GEN
Solar/Wind Helper
1.775
G-007ALTFEXP_G-007A->PJM
CMTX
54.655
HAMLETPJM->LTFIMP_HAMLET
CLTF
6.408
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.748
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
23.489
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
4.966
BlueGrassPJM->LTFIMP_BlueG
CLTF
15.477
CBM NorthLTFEXP_CBM-N->PJM
CBM
79.452
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
143.875

Details for CHAN-01DOUBS 500.0 kV Ckt 1 line l/o PECO_P1-2_5012_SRT-A


Base Case Flowgate

Area:AP/PJM
Facility Description:
CHAN-01DOUBS 500.0 kV Ckt 1 line
Contingency Name:
PECO_P1-2_5012_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.13 %
Rating:4595.0 MVA
Rating Type:B
MVA to Mitigate:5335.98
MW Contribution:0.49
Bus #Bus NameTypeMW Contribution
200035PCHBTM 3
50/50
23.165
200202DELTA2 ST
50/50
7.071
200200DELTA2 CT1
50/50
3.958
200201DELTA2 CT2
50/50
3.958
200195DELTA ST
50/50
3.498
200192DELTA CT1
50/50
2.098
200193DELTA CT2
50/50
2.098
200194DELTA CT3
50/50
2.098
200034PCHBTM 2
50/50
138.633
200203Y1-065-STG
50/50
7.997
200204Y1-065-CTG1
50/50
5.036
200205Y1-065-CTG2
50/50
5.036
200052ROCKSP 1
50/50
59.746
200053ROCKSP 2
50/50
59.746
200054ROCKSP 3
50/50
59.14
200055ROCKSP 4
50/50
59.14
971149AH1-027 GEN
Solar/Wind Harmer
0.331
233972AC1-094 C
Solar/Wind Harmer
-0.001
970695AG2-447 GEN
Solar/Wind Harmer
0.265
234033AF1-007_GEN
Solar/Wind Harmer
27.672
970545AG2-347 GEN
Solar/Wind Harmer
113.991
972133AH1-634 GEN
Solar/Wind Harmer
17.271
233987AB2-037 GEN
Solar/Wind Harmer
0
972177AH1-672 GEN
Solar/Wind Harmer
0.992
972069AH1-584 GEN
Solar/Wind Harmer
0.661
972071AH1-585 GEN
Solar/Wind Harmer
0.661
972073AH1-586 GEN
Solar/Wind Harmer
11.902
971747AH1-380 GEN
Solar/Wind Harmer
0.264
233923SMA
Solar/Wind Harmer
-0.001
233998TM1NIN_3.36
Solar/Wind Harmer
-0.001
233997TMININ_4.2
Solar/Wind Harmer
-0.001
233996TM1833_GEN
Solar/Wind Harmer
-0.001
233990AG1-397 GEN
Solar/Wind Harmer
0
233990AG1-397 GEN
Solar/Wind Harmer
2.116
233940AF2-379 C
Solar/Wind Harmer
-0.001
234015AF2-250 C
Solar/Wind Harmer
-0.001
971195AH1-057 GEN
Solar/Wind Harmer
0.095
960671AF2-358 GEN
Solar/Wind Harmer
1.321
965821AG1-450 GEN
Solar/Wind Harmer
6.606
232426Y1-080 FULL
Solar/Wind Harmer
0
970277AG2-181 GEN
Solar/Wind Harmer
0.37
233946AB2-136 GEN
Solar/Wind Harmer
-0.001
233964AF2-378 GEN
Solar/Wind Harmer
0.001
234041AC1-190 GEN
Solar/Wind Harmer
0.66
233984AB2-036 GEN
Solar/Wind Harmer
1.208
233968AD2-076_GEN
Solar/Wind Harmer
0.641
234014AF1-036_GEN
Solar/Wind Harmer
0.262
970597AG2-380 GEN
Solar/Wind Harmer
5.235
234012AE2-112_GEN
Solar/Wind Harmer
0.222
971983AH1-536 GEN
Solar/Wind Harmer
0.545
970453AG2-297 GEN
Solar/Wind Harmer
0.237
971553AH1-274 GEN
Solar/Wind Harmer
0.208
945431AF1-208 GEN
Solar/Wind Harmer
0.559
970997AG2-616 GEN
Solar/Wind Harmer
0.62
972141AH1-641 GEN
Solar/Wind Harmer
0.186
230422AE1-104_GEN1
Solar/Wind Harmer
51.422
230425AE1-104_GEN2
Solar/Wind Harmer
51.422
230430AE1-229_GEN
Solar/Wind Harmer
-0.001
230433AD2-135 GEN
Solar/Wind Harmer
0
228351V2-046C
Solar/Wind Harmer
-0.001
971011AG2-627 GEN
Solar/Wind Harmer
0.495
971535AH1-265 GEN
Solar/Wind Harmer
0.364
228754AB1-001 C
Solar/Wind Harmer
-0.001
230407AD2-065 C
Solar/Wind Harmer
0
219137THOSOLAR C
Solar/Wind Harmer
0.001
219623KINSLEYBEA C
Solar/Wind Harmer
-0.001
219258KINSLEYDEP C
Solar/Wind Harmer
0
218660EHAMPSOLAR C
Solar/Wind Harmer
-0.001
219766PARADISE C
Solar/Wind Harmer
-0.001
219907AC1-030 C
Solar/Wind Harmer
-0.001
219236SOUTHERNHQ C
Solar/Wind Harmer
-0.001
219906AC1-017 C
Solar/Wind Harmer
-0.001
219615MILLCREEK C
Solar/Wind Harmer
-0.001
214067T20SOLAR
Solar/Wind Harmer
-0.001
207522AF2-254 C
Solar/Wind Harmer
0.119
207500AE2-000G1
Solar/Wind Harmer
46.467
207497AE2-000G2
Solar/Wind Harmer
46.467
207507AE2-000G3
Solar/Wind Harmer
46.467
207487AE2-000G4
Solar/Wind Harmer
46.467
970025AG2-016 GEN
Solar/Wind Harmer
0.234
971189AH1-054 GEN
Solar/Wind Harmer
0.098
971667AH1-334 GEN
Solar/Wind Harmer
0.227
219727YARDVSOLFA C
Solar/Wind Harmer
0.001
219276PARKLANDSO C
Solar/Wind Harmer
0
219620RIDERU C
Solar/Wind Harmer
-0.001
219817TRENTONSOL C
Solar/Wind Harmer
0.001
20714328BYD_X4-031
Solar/Wind Harmer
0.023
20714428HOW_X1-037
Solar/Wind Harmer
-0.001
219918AC2-009 C
Solar/Wind Harmer
0
20720628TIN_W1-124
Solar/Wind Harmer
-0.001
20742028HF_AC1-207
Solar/Wind Harmer
-0.001
971521AH1-258 GEN
Solar/Wind Harmer
0.223
967451AG2-055 C O1
Solar/Wind Harmer
254.589
219612MATRIX C
Solar/Wind Harmer
0.001
218438BLK ROCK C
Solar/Wind Harmer
-0.001
218526CNTRALGAS2 C
Solar/Wind Harmer
0.001
218524CNTRALGAS1 C
Solar/Wind Harmer
0.001
218428ETC SOLAR C
Solar/Wind Harmer
0
217213AMBOY SO C
Solar/Wind Harmer
-0.001
219249CENTRALDIV C
Solar/Wind Harmer
-0.001
20673828FLE_V3-070
Solar/Wind Harmer
0.081
20675428EAM_W2-061
Solar/Wind Harmer
0
218449LINSOLAR C
Solar/Wind Harmer
0.001
217081WEATEXAS C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
217206BARNGR HS C
Solar/Wind Harmer
-0.001
217208PARK ELE C
Solar/Wind Harmer
0
207439AE1-081 C O1
Solar/Wind Harmer
0.001
20676328BVR_Y1-020
Solar/Wind Harmer
-0.001
20674628WNG_W3-110
Solar/Wind Harmer
-0.001
207511W3-106 GEN
Solar/Wind Harmer
0.053
971009AG2-626 GEN
Solar/Wind Harmer
0.133
971007AG2-625 GEN
Solar/Wind Harmer
0.208
971519AH1-257 GEN
Solar/Wind Harmer
0.205
207437AD2-070 GEN
Solar/Wind Harmer
-0.001
966181AG1-487 GEN
Solar/Wind Harmer
0
966181AG1-487 GEN
Solar/Wind Harmer
4.017
966111AG1-480 GEN
Solar/Wind Harmer
0
966111AG1-480 GEN
Solar/Wind Harmer
3.549
970095AG2-074 GEN
Solar/Wind Harmer
0.366
208972BECR K09
Solar/Wind Harmer
2.693
209027LOR2_Q27
Solar/Wind Harmer
10.76
212266LOR1
Solar/Wind Harmer
0.201
970237AG2-161 GEN
Solar/Wind Harmer
0.237
961541AF2-445A GEN
Solar/Wind Harmer
0.188
209029WAYMART-WD
Solar/Wind Harmer
7.167
209142AF1-226 GEN
Solar/Wind Harmer
0.328
209093AE2-110 GEN
Solar/Wind Harmer
0.188
209120AE2-241 GEN
Solar/Wind Harmer
0.188
209045AE2-271 GEN
Solar/Wind Harmer
0.948
209059AE2-084 GEN
Solar/Wind Harmer
0.185
970665AG2-430 GEN
Solar/Wind Harmer
0.55
209130AF1-271A GEN
Solar/Wind Harmer
0.156
208862AG1-362 C
Solar/Wind Harmer
0.043
970679AG2-439 GEN
Solar/Wind Harmer
0.064
200917MEHOOPANY_G
Solar/Wind Harmer
8.98
205967AE2-211_GEN
Solar/Wind Harmer
0.417
3138216PACIFIC
Solar/Wind Helper
0.08
316411AF1-147_GEN1
Solar/Wind Helper
0.383
316415AF1-147_GEN2
Solar/Wind Helper
0.383
3141196NOKESVL
Solar/Wind Helper
1.85
316006AB2-029 C
Solar/Wind Helper
0.143
238175AF1-290_GEN
Solar/Wind Helper
0.571
3141426STAFORD
Solar/Wind Helper
0.097
315651AD1-115 GEN
Solar/Wind Helper
1.065
316045AC1-158 PL2
Solar/Wind Helper
1.652
316447AC1-158 HLD
Solar/Wind Helper
1.136
316044AC1-158 PL1
Solar/Wind Helper
0.517
316450AC1-158 RIC
Solar/Wind Helper
0.138
316254AC1-120 GEN1
Solar/Wind Helper
0.424
316170AC1-121 GEN2
Solar/Wind Helper
0.141
316164AC1-076 GEN
Solar/Wind Helper
0.442
238169AE2-226 GEN1
Solar/Wind Helper
0.349
238170AE2-226 GEN2
Solar/Wind Helper
0.349
964441AG1-307 GEN
Solar/Wind Helper
0.559
3132273ORANGE
Solar/Wind Helper
0.086
3147666LOUISA
Solar/Wind Helper
1.714
3147666LOUISA
Solar/Wind Helper
0.986
316192AB2-158 GEN
Solar/Wind Helper
0.607
966881AG1-559 GEN
Solar/Wind Helper
0.137
966001AG1-469 GEN
Solar/Wind Helper
0.096
944491AF1-114 GEN
Solar/Wind Helper
0.684
957971AF2-091 GEN
Solar/Wind Helper
0.232
316468AD1-105 GEN
Solar/Wind Helper
0.501
238152AF2-075_GEN
Solar/Wind Helper
0.338
238147AE2-230_GEN1
Solar/Wind Helper
0.474
238148AE2-230_GEN2
Solar/Wind Helper
0.474
238149AF1-291A_GEN
Solar/Wind Helper
0.068
316223AC1-118
Solar/Wind Helper
0.135
3141906WESTMOR
Solar/Wind Helper
0.168
23546401DTGZ2-030
Solar/Wind Helper
0.067
316337AD2-073 GEN
Solar/Wind Helper
0.135
316077AC2-138 C
Solar/Wind Helper
0.094
3141813NORNECK
Solar/Wind Helper
0.417
964211AG1-282 GEN
Solar/Wind Helper
0.134
3141726DUNNSVL
Solar/Wind Helper
1.668
316473AC1-191 GEN
Solar/Wind Helper
0.536
966871AG1-558 GEN
Solar/Wind Helper
0.134
237061AD1-155 GEN
Solar/Wind Helper
0.502
316404AE1-155 C
Solar/Wind Helper
0.849
316484AD2-074 GEN
Solar/Wind Helper
0.574
316487AF1-042 GEN
Solar/Wind Helper
0.3
961951AG1-038 GEN
Solar/Wind Helper
0.3
316312AB1-027
Solar/Wind Helper
0.167
3142416OLDCHRC
Solar/Wind Helper
1.078
3142416OLDCHRC
Solar/Wind Helper
0.413
3141783LANCAST
Solar/Wind Helper
0.248
3141783LANCAST
Solar/Wind Helper
0.166
3138133OCRAN
Solar/Wind Helper
0.248
3138133OCRAN
Solar/Wind Helper
0.124
3141913WHIT STONE
Solar/Wind Helper
0.414
316075AC2-137 C
Solar/Wind Helper
0.133
316314AB2-024 C
Solar/Wind Helper
0.133
316059AD1-063 C
Solar/Wind Helper
0.1
3141766HARMONY
Solar/Wind Helper
0.083
316203AE2-005 GEN
Solar/Wind Helper
0.863
315662AE1-191 GEN
Solar/Wind Helper
0.531
316280AD1-041 GEN
Solar/Wind Helper
0.332
315666AE1-190 GEN
Solar/Wind Helper
0.133
316441AF1-014 GEN
Solar/Wind Helper
0.132
3143873LANEXA
Solar/Wind Helper
0.248
957601AF2-054 GEN
Solar/Wind Helper
0.132
316156AD2-030 GEN
Solar/Wind Helper
0.131
3141873WAN 176
Solar/Wind Helper
0.083
316233AE1-074 FULL
Solar/Wind Helper
0.133
3143526WINTERP
Solar/Wind Helper
2.147
3143526WINTERP
Solar/Wind Helper
2.147
3142433PROV 92
Solar/Wind Helper
1.651
3143226MDLTHAN
Solar/Wind Helper
0.413
3142543TWELFTH
Solar/Wind Helper
0.04
3142946ENON
Solar/Wind Helper
0.138
3142946ENON
Solar/Wind Helper
0.041
957831AF2-077 GEN
Solar/Wind Helper
0.132
316382AG1-145 C
Solar/Wind Helper
0.132
316159AE1-175 C
Solar/Wind Helper
0.132
316240AF1-291 C
Solar/Wind Helper
0.132
316132AB2-190 GEN1
Solar/Wind Helper
0.493
316458AB2-190 GEN2
Solar/Wind Helper
0.493
315697AD1-025 GEN
Solar/Wind Helper
0.984
316033AB2-134 GEN
Solar/Wind Helper
0.934
316369SG1_INVT
Solar/Wind Helper
0.643
315839AE2-212 C
Solar/Wind Helper
0.131
961611AG1-000B GEN
Solar/Wind Helper
0.583
316236AE1-162_GEN
Solar/Wind Helper
0.131
3145336SMITFLD
Solar/Wind Helper
1.625
3145336SMITFLD
Solar/Wind Helper
0.162
3143316POE
Solar/Wind Helper
1.608
316294AC1-161 GEN
Solar/Wind Helper
1.565
315773AC2-141 GEN
Solar/Wind Helper
1.565
316313AB2-026
Solar/Wind Helper
0.13
316258AE1-075 C
Solar/Wind Helper
0.117
316405AF2-144 C
Solar/Wind Helper
0.111
3144536CHRHLND
Solar/Wind Helper
0.061
316381AD1-082 GEN
Solar/Wind Helper
0.443
316083AB2-161 GEN
Solar/Wind Helper
0.325
316375AC2-012 GEN
Solar/Wind Helper
0.767
316036AC1-147 C
Solar/Wind Helper
0.13
3144873MCLAUGH
Solar/Wind Helper
0.01
316316AC1-027 C
Solar/Wind Helper
0.114
316185AD1-033 GEN
Solar/Wind Helper
0.455
316072AD1-144
Solar/Wind Helper
0.097
3145506HICKORY
Solar/Wind Helper
1.616
3145506HICKORY
Solar/Wind Helper
0.97
3145506HICKORY
Solar/Wind Helper
0.242
316336AC2-165 C
Solar/Wind Helper
0.649
316349AD2-085 GEN
Solar/Wind Helper
0.331
316339AD2-160 GEN
Solar/Wind Helper
0.324
316388AE2-253 GEN
Solar/Wind Helper
0.324
315833AF1-017_GEN
Solar/Wind Helper
0.259
235020AA1-095 C
Solar/Wind Helper
0.027
316017AA1-139 ULT1
Solar/Wind Helper
0.389
316018AA1-139 ULT2
Solar/Wind Helper
0.389
3137176SLIGO L2192
Solar/Wind Helper
1.605
3146456SLIGO L269
Solar/Wind Helper
0.403
3146456SLIGO L269
Solar/Wind Helper
0.403
316305AF2-043 C
Solar/Wind Helper
0.13
316246AF1-032 C
Solar/Wind Helper
0.097
319010AE1-072 C
Solar/Wind Helper
0.972
23777901MDS_W4-102
Solar/Wind Helper
0.13
3130086AYDLETT
Solar/Wind Helper
1.612
316320Y1-086
Solar/Wind Helper
0.129
313526AB2-022
Solar/Wind Helper
0.129
3146386ELIZ CT
Solar/Wind Helper
0.402
3146486SUNBURY
Solar/Wind Helper
0.402
3146486SUNBURY
Solar/Wind Helper
0.402
316321Z2-027
Solar/Wind Helper
0.129
3145176PASQUOTANK
Solar/Wind Helper
0.249
3146516WINFALL
Solar/Wind Helper
1.297
3146516WINFALL
Solar/Wind Helper
0.4
3146516WINFALL
Solar/Wind Helper
0.4
3146516WINFALL
Solar/Wind Helper
0.4
3146516WINFALL
Solar/Wind Helper
0.4
3146516WINFALL
Solar/Wind Helper
0.4
3146626S HERTFORD
Solar/Wind Helper
0.4
3146626S HERTFORD
Solar/Wind Helper
0.4
3146626S HERTFORD
Solar/Wind Helper
0.4
316315AB2-025 C
Solar/Wind Helper
0.128
3145273HOLLAND
Solar/Wind Helper
0.3
315742AE1-103 GEN
Solar/Wind Helper
0.256
3130156CHOWAN
Solar/Wind Helper
0.397
3130156CHOWAN
Solar/Wind Helper
0.397
3130156CHOWAN
Solar/Wind Helper
0.397
3146376EDENTON
Solar/Wind Helper
0.397
3132123MT JACKSON
Solar/Wind Helper
1.239
315614AA2-178 GEN
Solar/Wind Helper
0.507
315816AE2-034 GEN
Solar/Wind Helper
0.38
3145663CRESWEL
Solar/Wind Helper
1.105
3138266HYDRAULIC
Solar/Wind Helper
0.018
3138266HYDRAULIC
Solar/Wind Helper
0.011
316322AB2-045
Solar/Wind Helper
0.125
3146776BUCKING
Solar/Wind Helper
1.573
3146776BUCKING
Solar/Wind Helper
0.157
3146776BUCKING
Solar/Wind Helper
0.142
3146776BUCKING
Solar/Wind Helper
0.127
3130546PLYMOUTH
Solar/Wind Helper
0.393
3156081AA2-088 GEN
Solar/Wind Helper
0.631
315732AD1-074 GEN1
Solar/Wind Helper
0.946
315733AD1-074 GEN2
Solar/Wind Helper
0.946
315737AD1-076 GEN
Solar/Wind Helper
0.687
315735AD1-075 GEN1
Solar/Wind Helper
0.473
316065AD1-022 GEN
Solar/Wind Helper
0.503
3146926FARMVIL
Solar/Wind Helper
0.235
3146926FARMVIL
Solar/Wind Helper
0.235
316023GEN1_S
Solar/Wind Helper
0.314
316365GEN2_N
Solar/Wind Helper
0.314
3146206CASHIE
Solar/Wind Helper
0.391
3146206CASHIE
Solar/Wind Helper
0.391
3146206CASHIE
Solar/Wind Helper
0.391
3145893MURPHYS
Solar/Wind Helper
1.565
3145893MURPHYS
Solar/Wind Helper
1.252
3145893MURPHYS
Solar/Wind Helper
1.056
316318V4-068
Solar/Wind Helper
0.029
3145893MURPHYS
Solar/Wind Helper
0.704
3145893MURPHYS
Solar/Wind Helper
0.391
3145893MURPHYS
Solar/Wind Helper
0.391
3145893MURPHYS
Solar/Wind Helper
0.313
3146173TUNIS
Solar/Wind Helper
0.39
3146173TUNIS
Solar/Wind Helper
0.39
3146173TUNIS
Solar/Wind Helper
0.39
3146173TUNIS
Solar/Wind Helper
0.39
3147983MERCK5
Solar/Wind Helper
0.156
316097T157 G90
Solar/Wind Helper
0.257
316095T157 G97
Solar/Wind Helper
0.257
315821AE2-092 GEN
Solar/Wind Helper
0.864
3156021HOLLOMANSOL
Solar/Wind Helper
0.625
316463AE2-346 GEN
Solar/Wind Helper
0.075
316140AB2-099
Solar/Wind Helper
0.031
961941AG1-037 GEN
Solar/Wind Helper
0.031
3145513AHOSKIE
Solar/Wind Helper
0.389
3145513AHOSKIE
Solar/Wind Helper
0.389
942461AE2-259 GEN
Solar/Wind Helper
0.626
946281AF1-292 GEN
Solar/Wind Helper
0.093
966621AG1-532 GEN
Solar/Wind Helper
0.084
3146043SEABORD
Solar/Wind Helper
0.389
3145683EARLEYS
Solar/Wind Helper
0.778
3145683EARLEYS
Solar/Wind Helper
0.389
3145683EARLEYS
Solar/Wind Helper
0.389
3145683EARLEYS
Solar/Wind Helper
0.389
315607AA1-063A GEN
Solar/Wind Helper
0.468
316087AB2-174 GEN
Solar/Wind Helper
0.499
316499AE2-029_GEN
Solar/Wind Helper
0.312
3146263WOODLND
Solar/Wind Helper
0.388
3146263WOODLND
Solar/Wind Helper
0.388
316181AB2-040 GEN
Solar/Wind Helper
0.499
313506AB2-031 GEN
Solar/Wind Helper
0.372
3147133PAMPLIN
Solar/Wind Helper
1.217
3147133PAMPLIN
Solar/Wind Helper
0.387
3147133PAMPLIN
Solar/Wind Helper
0.31
3137643SOCKMAN
Solar/Wind Helper
1.547
3142666NORTHAMPTON
Solar/Wind Helper
0.387
3142666NORTHAMPTON
Solar/Wind Helper
0.387
3142666NORTHAMPTON
Solar/Wind Helper
0.387
3142666NORTHAMPTON
Solar/Wind Helper
0.387
3142666NORTHAMPTON
Solar/Wind Helper
0.232
3147043LAWRENC
Solar/Wind Helper
0.232
316426AA2-053 GEN
Solar/Wind Helper
0.466
316190AA2-174 GEN
Solar/Wind Helper
0.031
3145963POPLR C
Solar/Wind Helper
0.387
3145963POPLR C
Solar/Wind Helper
0.387
316011AB1-132 GEN
Solar/Wind Helper
9.287
316317KELFORD C
Solar/Wind Helper
0.144
3145823KELFORD
Solar/Wind Helper
0.387
3145823KELFORD
Solar/Wind Helper
0.387
3145593CAROLNA
Solar/Wind Helper
0.387
3145593CAROLNA
Solar/Wind Helper
0.387
316174AB2-169 GEN
Solar/Wind Helper
0.459
316478AD1-087 GEN
Solar/Wind Helper
0.398
316486AD2-202 GEN
Solar/Wind Helper
0.117
3145783HORNRTN
Solar/Wind Helper
0.386
3148013FISHERV
Solar/Wind Helper
0.386
3148133STUARTS
Solar/Wind Helper
0.232
3148013FISHERV
Solar/Wind Helper
0.222
3145796HORNRTN
Solar/Wind Helper
1.541
3145796HORNRTN
Solar/Wind Helper
1.271
3145796HORNRTN
Solar/Wind Helper
1.233
3145796HORNRTN
Solar/Wind Helper
1.156
3145796HORNRTN
Solar/Wind Helper
0.385
3145796HORNRTN
Solar/Wind Helper
0.385
3145796HORNRTN
Solar/Wind Helper
0.154
316034AC1-036 C
Solar/Wind Helper
0.085
3144303KENBRDG
Solar/Wind Helper
0.308
3146033SCOT NK
Solar/Wind Helper
1.539
315785AD2-033 C
Solar/Wind Helper
0.803
316129AC1-054 GEN
Solar/Wind Helper
0.4
316210AC1-098 GEN
Solar/Wind Helper
0.554
316212AC1-099_GEN
Solar/Wind Helper
0.308
316131AB2-060 GEN
Solar/Wind Helper
0.492
313527AB2-043 GEN
Solar/Wind Helper
0.307
3145933PARMELE
Solar/Wind Helper
0.765
3145933PARMELE
Solar/Wind Helper
0.382
3145933PARMELE
Solar/Wind Helper
0.382
316274AC1-208 GEN
Solar/Wind Helper
0.491
316239AB2-077_GEN
Solar/Wind Helper
0.123
316238AB2-078_GEN
Solar/Wind Helper
0.123
316237AB2-079_GEN
Solar/Wind Helper
0.123
23583801GRNGAP
Solar/Wind Helper
0.637
316005AA1-067
Solar/Wind Helper
0.092
3145746EVERETS
Solar/Wind Helper
1.513
3145746EVERETS
Solar/Wind Helper
0.38
3145746EVERETS
Solar/Wind Helper
0.38
3145746EVERETS
Solar/Wind Helper
0.38
3145746EVERETS
Solar/Wind Helper
0.38
3145746EVERETS
Solar/Wind Helper
0.38
3145746EVERETS
Solar/Wind Helper
0.38
3145746EVERETS
Solar/Wind Helper
0.38
315687AD1-152 GEN
Solar/Wind Helper
0.489
315722AD1-056 GEN
Solar/Wind Helper
0.366
315724AD1-057 GEN
Solar/Wind Helper
0.201
316327AA2-057 GEN
Solar/Wind Helper
0.457
226929AD2-058 GEN
Solar/Wind Helper
0.034
316494AC1-189 GEN
Solar/Wind Helper
0.487
270494AE1-108_GEN
Solar/Wind Helper
0.909
316420AA1-050 GEN
Solar/Wind Helper
0.486
316319Z2-044 C
Solar/Wind Helper
0.073
3146233WITAKRS
Solar/Wind Helper
1.502
3146233WITAKRS
Solar/Wind Helper
0.257
961671AG1-007 GEN
Solar/Wind Helper
0.057
3145573BETHELC
Solar/Wind Helper
0.377
3145573BETHELC
Solar/Wind Helper
0.377
3146073TAR RVR
Solar/Wind Helper
0.377
3146083TARBORO
Solar/Wind Helper
0.377
3146083TARBORO
Solar/Wind Helper
0.377
238208AF1-136 C
Solar/Wind Helper
0.096
3138543CONSLDL
Solar/Wind Helper
0.249
3146843MT LREL
Solar/Wind Helper
0.377
3146843MT LREL
Solar/Wind Helper
0.377
3145543BTLEBRO
Solar/Wind Helper
0.376
3145543BTLEBRO
Solar/Wind Helper
0.376
3145543BTLEBRO
Solar/Wind Helper
0.376
3145543BTLEBRO
Solar/Wind Helper
0.3
316359AB2-059 GEN
Solar/Wind Helper
0.603
316049AB1-081 GEN
Solar/Wind Helper
0.483
238108AE1-109 GEN1
Solar/Wind Helper
0.04
238109AE1-109 GEN2
Solar/Wind Helper
0.04
238110AE1-109 GEN3
Solar/Wind Helper
0.04
316118AC1-105 GEN
Solar/Wind Helper
0.307
238221AF1-254 C O1
Solar/Wind Helper
0.12
3148463FAIRFLD
Solar/Wind Helper
0.374
237034AC2-136 C
Solar/Wind Helper
0.071
316248AF1-058 C
Solar/Wind Helper
0.12
3147173SINAI
Solar/Wind Helper
0.372
3147243WELCO
Solar/Wind Helper
0.233
316003AC1-222 GEN
Solar/Wind Helper
0.385
227287AC2-120 GEN
Solar/Wind Helper
0.163
226910AB2-157 C
Solar/Wind Helper
0.015
316222AC1-221 GEN
Solar/Wind Helper
0.437
316283AC2-100 C
Solar/Wind Helper
0.407
237080AD1-060 GEN
Solar/Wind Helper
0.087
316123AC1-075 GEN
Solar/Wind Helper
0.462
964991AG1-363 GEN
Solar/Wind Helper
1.702
270455AD2-022 GEN
Solar/Wind Helper
0.544
270457AD2-023 GEN
Solar/Wind Helper
0.306
237038AE2-054 C
Solar/Wind Helper
0.112
235067AD1-061 GEN
Solar/Wind Helper
0.111
3147123OTTER R
Solar/Wind Helper
0.207
316217AC1-145 GEN
Solar/Wind Helper
0.275
316197AC1-042 GEN
Solar/Wind Helper
0.231
3147312GRETNA
Solar/Wind Helper
0.274
3146802CHATHAM
Solar/Wind Helper
0.257
3147312GRETNA
Solar/Wind Helper
0.069
270016AE1-250 BESS
Solar/Wind Helper
0.413
270013AE1-250 PV
Solar/Wind Helper
0.413
237085AD2-009_GEN
Solar/Wind Helper
0.384
270197AD1-017 GEN1
Solar/Wind Helper
0.328
270574AD1-017 GEN2
Solar/Wind Helper
0.328
237002AB1-128_GEN
Solar/Wind Helper
0.108
270173AC1-122 GEN
Solar/Wind Helper
0.411
270018AE2-047 C O1
Solar/Wind Helper
0.269
237001AB1-127_GEN
Solar/Wind Helper
0.107
943811AF1-049 GEN
Solar/Wind Helper
0.663
23750701CROSSCHOOL
Solar/Wind Helper
0.143
235062AE1-101 C1
Solar/Wind Helper
0.397
235063AE1-101 C2
Solar/Wind Helper
0.397
270069AE2-166 C O1
Solar/Wind Helper
0.473
270336AE1-100 GEN
Solar/Wind Helper
0.347
238120AE2-309 GEN
Solar/Wind Helper
0.103
235531U2-073 GEN
Solar/Wind Helper
0.3
23779801AA1-109
Solar/Wind Helper
0.046
238126S14_GEN_1
Solar/Wind Helper
0.32
238127S14_GEN_2
Solar/Wind Helper
0.32
235054AD2-180 GEN
Solar/Wind Helper
0.303
958121AF2-106 GEN
Solar/Wind Helper
0.761
238185AF2-356 C
Solar/Wind Helper
0.884
238118U2-030_1
Solar/Wind Helper
0.04
270214AC2-123 GEN
Solar/Wind Helper
0.376
966391AG1-508 GEN
Solar/Wind Helper
1.775
G-007ALTFEXP_G-007A->PJM
CMTX
54.655
HAMLETPJM->LTFIMP_HAMLET
CLTF
6.408
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.748
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
23.489
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
4.966
BlueGrassPJM->LTFIMP_BlueG
CLTF
15.477
CBM NorthLTFEXP_CBM-N->PJM
CBM
79.452
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
143.875

Details for CHAN-01DOUBS 500.0 kV Ckt 1 line l/o BGE_P4_GRACETON_51_SRT-A


Base Case Flowgate

Area:AP/PJM
Facility Description:
CHAN-01DOUBS 500.0 kV Ckt 1 line
Contingency Name:
BGE_P4_GRACETON_51_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.12 %
Rating:4595.0 MVA
Rating Type:B
MVA to Mitigate:5335.85
MW Contribution:0.49
Bus #Bus NameTypeMW Contribution
200035PCHBTM 3
50/50
23.165
200202DELTA2 ST
50/50
7.071
200200DELTA2 CT1
50/50
3.958
200201DELTA2 CT2
50/50
3.958
200195DELTA ST
50/50
3.498
200192DELTA CT1
50/50
2.098
200193DELTA CT2
50/50
2.098
200194DELTA CT3
50/50
2.098
200034PCHBTM 2
50/50
138.633
200203Y1-065-STG
50/50
7.997
200204Y1-065-CTG1
50/50
5.036
200205Y1-065-CTG2
50/50
5.036
200052ROCKSP 1
50/50
59.746
200053ROCKSP 2
50/50
59.746
200054ROCKSP 3
50/50
59.14
200055ROCKSP 4
50/50
59.14
971149AH1-027 GEN
Solar/Wind Harmer
0.331
233972AC1-094 C
Solar/Wind Harmer
-0.001
970695AG2-447 GEN
Solar/Wind Harmer
0.265
234033AF1-007_GEN
Solar/Wind Harmer
27.672
970545AG2-347 GEN
Solar/Wind Harmer
113.991
972133AH1-634 GEN
Solar/Wind Harmer
17.271
233987AB2-037 GEN
Solar/Wind Harmer
0
972177AH1-672 GEN
Solar/Wind Harmer
0.992
972069AH1-584 GEN
Solar/Wind Harmer
0.661
972071AH1-585 GEN
Solar/Wind Harmer
0.661
972073AH1-586 GEN
Solar/Wind Harmer
11.902
971747AH1-380 GEN
Solar/Wind Harmer
0.264
233923SMA
Solar/Wind Harmer
-0.001
233998TM1NIN_3.36
Solar/Wind Harmer
-0.001
233997TMININ_4.2
Solar/Wind Harmer
-0.001
233996TM1833_GEN
Solar/Wind Harmer
-0.001
233990AG1-397 GEN
Solar/Wind Harmer
0
233990AG1-397 GEN
Solar/Wind Harmer
2.116
233940AF2-379 C
Solar/Wind Harmer
-0.001
234015AF2-250 C
Solar/Wind Harmer
-0.001
971195AH1-057 GEN
Solar/Wind Harmer
0.095
960671AF2-358 GEN
Solar/Wind Harmer
1.321
965821AG1-450 GEN
Solar/Wind Harmer
6.606
232426Y1-080 FULL
Solar/Wind Harmer
0
970277AG2-181 GEN
Solar/Wind Harmer
0.37
233946AB2-136 GEN
Solar/Wind Harmer
-0.001
233964AF2-378 GEN
Solar/Wind Harmer
0.001
234041AC1-190 GEN
Solar/Wind Harmer
0.66
233984AB2-036 GEN
Solar/Wind Harmer
1.208
233968AD2-076_GEN
Solar/Wind Harmer
0.641
234014AF1-036_GEN
Solar/Wind Harmer
0.262
970597AG2-380 GEN
Solar/Wind Harmer
5.235
234012AE2-112_GEN
Solar/Wind Harmer
0.222
971983AH1-536 GEN
Solar/Wind Harmer
0.545
970453AG2-297 GEN
Solar/Wind Harmer
0.237
971553AH1-274 GEN
Solar/Wind Harmer
0.208
945431AF1-208 GEN
Solar/Wind Harmer
0.559
970997AG2-616 GEN
Solar/Wind Harmer
0.62
972141AH1-641 GEN
Solar/Wind Harmer
0.186
230422AE1-104_GEN1
Solar/Wind Harmer
51.422
230425AE1-104_GEN2
Solar/Wind Harmer
51.422
230430AE1-229_GEN
Solar/Wind Harmer
-0.001
230433AD2-135 GEN
Solar/Wind Harmer
0
228351V2-046C
Solar/Wind Harmer
-0.001
971011AG2-627 GEN
Solar/Wind Harmer
0.495
971535AH1-265 GEN
Solar/Wind Harmer
0.364
228754AB1-001 C
Solar/Wind Harmer
-0.001
230407AD2-065 C
Solar/Wind Harmer
0
219137THOSOLAR C
Solar/Wind Harmer
0.001
219623KINSLEYBEA C
Solar/Wind Harmer
-0.001
219258KINSLEYDEP C
Solar/Wind Harmer
0
218660EHAMPSOLAR C
Solar/Wind Harmer
-0.001
219766PARADISE C
Solar/Wind Harmer
-0.001
219907AC1-030 C
Solar/Wind Harmer
-0.001
219236SOUTHERNHQ C
Solar/Wind Harmer
-0.001
219906AC1-017 C
Solar/Wind Harmer
-0.001
219615MILLCREEK C
Solar/Wind Harmer
-0.001
214067T20SOLAR
Solar/Wind Harmer
-0.001
207522AF2-254 C
Solar/Wind Harmer
0.119
207500AE2-000G1
Solar/Wind Harmer
46.467
207497AE2-000G2
Solar/Wind Harmer
46.467
207507AE2-000G3
Solar/Wind Harmer
46.467
207487AE2-000G4
Solar/Wind Harmer
46.467
970025AG2-016 GEN
Solar/Wind Harmer
0.234
971189AH1-054 GEN
Solar/Wind Harmer
0.098
971667AH1-334 GEN
Solar/Wind Harmer
0.227
219727YARDVSOLFA C
Solar/Wind Harmer
0.001
219276PARKLANDSO C
Solar/Wind Harmer
0
219620RIDERU C
Solar/Wind Harmer
-0.001
219817TRENTONSOL C
Solar/Wind Harmer
0.001
20714328BYD_X4-031
Solar/Wind Harmer
0.023
20714428HOW_X1-037
Solar/Wind Harmer
-0.001
219918AC2-009 C
Solar/Wind Harmer
0
20720628TIN_W1-124
Solar/Wind Harmer
-0.001
20742028HF_AC1-207
Solar/Wind Harmer
-0.001
971521AH1-258 GEN
Solar/Wind Harmer
0.223
967451AG2-055 C O1
Solar/Wind Harmer
254.589
219612MATRIX C
Solar/Wind Harmer
0.001
218438BLK ROCK C
Solar/Wind Harmer
-0.001
218526CNTRALGAS2 C
Solar/Wind Harmer
0.001
218524CNTRALGAS1 C
Solar/Wind Harmer
0.001
218428ETC SOLAR C
Solar/Wind Harmer
0
217213AMBOY SO C
Solar/Wind Harmer
-0.001
219249CENTRALDIV C
Solar/Wind Harmer
-0.001
20673828FLE_V3-070
Solar/Wind Harmer
0.081
20675428EAM_W2-061
Solar/Wind Harmer
0
218449LINSOLAR C
Solar/Wind Harmer
0.001
217081WEATEXAS C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
217206BARNGR HS C
Solar/Wind Harmer
-0.001
217208PARK ELE C
Solar/Wind Harmer
0
207439AE1-081 C O1
Solar/Wind Harmer
0.001
20676328BVR_Y1-020
Solar/Wind Harmer
-0.001
20674628WNG_W3-110
Solar/Wind Harmer
-0.001
207511W3-106 GEN
Solar/Wind Harmer
0.053
971009AG2-626 GEN
Solar/Wind Harmer
0.133
971007AG2-625 GEN
Solar/Wind Harmer
0.208
971519AH1-257 GEN
Solar/Wind Harmer
0.205
207437AD2-070 GEN
Solar/Wind Harmer
-0.001
966181AG1-487 GEN
Solar/Wind Harmer
0
966181AG1-487 GEN
Solar/Wind Harmer
4.017
966111AG1-480 GEN
Solar/Wind Harmer
0
966111AG1-480 GEN
Solar/Wind Harmer
3.549
970095AG2-074 GEN
Solar/Wind Harmer
0.366
208972BECR K09
Solar/Wind Harmer
2.693
209027LOR2_Q27
Solar/Wind Harmer
10.76
212266LOR1
Solar/Wind Harmer
0.201
970237AG2-161 GEN
Solar/Wind Harmer
0.237
961541AF2-445A GEN
Solar/Wind Harmer
0.188
209029WAYMART-WD
Solar/Wind Harmer
7.167
209142AF1-226 GEN
Solar/Wind Harmer
0.328
209093AE2-110 GEN
Solar/Wind Harmer
0.188
209120AE2-241 GEN
Solar/Wind Harmer
0.188
209045AE2-271 GEN
Solar/Wind Harmer
0.948
209059AE2-084 GEN
Solar/Wind Harmer
0.185
970665AG2-430 GEN
Solar/Wind Harmer
0.55
209130AF1-271A GEN
Solar/Wind Harmer
0.156
208862AG1-362 C
Solar/Wind Harmer
0.043
970679AG2-439 GEN
Solar/Wind Harmer
0.064
200917MEHOOPANY_G
Solar/Wind Harmer
8.98
205967AE2-211_GEN
Solar/Wind Harmer
0.417
3138216PACIFIC
Solar/Wind Helper
0.08
316411AF1-147_GEN1
Solar/Wind Helper
0.383
316415AF1-147_GEN2
Solar/Wind Helper
0.383
3141196NOKESVL
Solar/Wind Helper
1.85
316006AB2-029 C
Solar/Wind Helper
0.143
238175AF1-290_GEN
Solar/Wind Helper
0.571
3141426STAFORD
Solar/Wind Helper
0.097
315651AD1-115 GEN
Solar/Wind Helper
1.065
316045AC1-158 PL2
Solar/Wind Helper
1.652
316447AC1-158 HLD
Solar/Wind Helper
1.136
316044AC1-158 PL1
Solar/Wind Helper
0.517
316450AC1-158 RIC
Solar/Wind Helper
0.138
316254AC1-120 GEN1
Solar/Wind Helper
0.424
316170AC1-121 GEN2
Solar/Wind Helper
0.141
316164AC1-076 GEN
Solar/Wind Helper
0.442
238169AE2-226 GEN1
Solar/Wind Helper
0.349
238170AE2-226 GEN2
Solar/Wind Helper
0.349
964441AG1-307 GEN
Solar/Wind Helper
0.559
3132273ORANGE
Solar/Wind Helper
0.086
3147666LOUISA
Solar/Wind Helper
1.714
3147666LOUISA
Solar/Wind Helper
0.986
316192AB2-158 GEN
Solar/Wind Helper
0.607
966881AG1-559 GEN
Solar/Wind Helper
0.137
966001AG1-469 GEN
Solar/Wind Helper
0.096
944491AF1-114 GEN
Solar/Wind Helper
0.684
957971AF2-091 GEN
Solar/Wind Helper
0.232
316468AD1-105 GEN
Solar/Wind Helper
0.501
238152AF2-075_GEN
Solar/Wind Helper
0.338
238147AE2-230_GEN1
Solar/Wind Helper
0.474
238148AE2-230_GEN2
Solar/Wind Helper
0.474
238149AF1-291A_GEN
Solar/Wind Helper
0.068
316223AC1-118
Solar/Wind Helper
0.135
3141906WESTMOR
Solar/Wind Helper
0.168
23546401DTGZ2-030
Solar/Wind Helper
0.067
316337AD2-073 GEN
Solar/Wind Helper
0.135
316077AC2-138 C
Solar/Wind Helper
0.094
3141813NORNECK
Solar/Wind Helper
0.417
964211AG1-282 GEN
Solar/Wind Helper
0.134
3141726DUNNSVL
Solar/Wind Helper
1.668
316473AC1-191 GEN
Solar/Wind Helper
0.536
966871AG1-558 GEN
Solar/Wind Helper
0.134
237061AD1-155 GEN
Solar/Wind Helper
0.502
316404AE1-155 C
Solar/Wind Helper
0.849
316484AD2-074 GEN
Solar/Wind Helper
0.574
316487AF1-042 GEN
Solar/Wind Helper
0.3
961951AG1-038 GEN
Solar/Wind Helper
0.3
316312AB1-027
Solar/Wind Helper
0.167
3142416OLDCHRC
Solar/Wind Helper
1.078
3142416OLDCHRC
Solar/Wind Helper
0.413
3141783LANCAST
Solar/Wind Helper
0.248
3141783LANCAST
Solar/Wind Helper
0.166
3138133OCRAN
Solar/Wind Helper
0.248
3138133OCRAN
Solar/Wind Helper
0.124
3141913WHIT STONE
Solar/Wind Helper
0.414
316075AC2-137 C
Solar/Wind Helper
0.133
316314AB2-024 C
Solar/Wind Helper
0.133
316059AD1-063 C
Solar/Wind Helper
0.1
3141766HARMONY
Solar/Wind Helper
0.083
316203AE2-005 GEN
Solar/Wind Helper
0.863
315662AE1-191 GEN
Solar/Wind Helper
0.531
316280AD1-041 GEN
Solar/Wind Helper
0.332
315666AE1-190 GEN
Solar/Wind Helper
0.133
316441AF1-014 GEN
Solar/Wind Helper
0.132
3143873LANEXA
Solar/Wind Helper
0.248
957601AF2-054 GEN
Solar/Wind Helper
0.132
316156AD2-030 GEN
Solar/Wind Helper
0.131
3141873WAN 176
Solar/Wind Helper
0.083
316233AE1-074 FULL
Solar/Wind Helper
0.133
3143526WINTERP
Solar/Wind Helper
2.147
3143526WINTERP
Solar/Wind Helper
2.147
3142433PROV 92
Solar/Wind Helper
1.651
3143226MDLTHAN
Solar/Wind Helper
0.413
3142543TWELFTH
Solar/Wind Helper
0.04
3142946ENON
Solar/Wind Helper
0.138
3142946ENON
Solar/Wind Helper
0.041
957831AF2-077 GEN
Solar/Wind Helper
0.132
316382AG1-145 C
Solar/Wind Helper
0.132
316159AE1-175 C
Solar/Wind Helper
0.132
316240AF1-291 C
Solar/Wind Helper
0.132
316132AB2-190 GEN1
Solar/Wind Helper
0.493
316458AB2-190 GEN2
Solar/Wind Helper
0.493
315697AD1-025 GEN
Solar/Wind Helper
0.984
316033AB2-134 GEN
Solar/Wind Helper
0.934
316369SG1_INVT
Solar/Wind Helper
0.643
315839AE2-212 C
Solar/Wind Helper
0.131
961611AG1-000B GEN
Solar/Wind Helper
0.583
316236AE1-162_GEN
Solar/Wind Helper
0.131
3145336SMITFLD
Solar/Wind Helper
1.625
3145336SMITFLD
Solar/Wind Helper
0.162
3143316POE
Solar/Wind Helper
1.608
316294AC1-161 GEN
Solar/Wind Helper
1.565
315773AC2-141 GEN
Solar/Wind Helper
1.565
316313AB2-026
Solar/Wind Helper
0.13
316258AE1-075 C
Solar/Wind Helper
0.117
316405AF2-144 C
Solar/Wind Helper
0.111
3144536CHRHLND
Solar/Wind Helper
0.061
316381AD1-082 GEN
Solar/Wind Helper
0.443
316083AB2-161 GEN
Solar/Wind Helper
0.325
316375AC2-012 GEN
Solar/Wind Helper
0.767
316036AC1-147 C
Solar/Wind Helper
0.13
3144873MCLAUGH
Solar/Wind Helper
0.01
316316AC1-027 C
Solar/Wind Helper
0.114
316185AD1-033 GEN
Solar/Wind Helper
0.455
316072AD1-144
Solar/Wind Helper
0.097
3145506HICKORY
Solar/Wind Helper
1.616
3145506HICKORY
Solar/Wind Helper
0.97
3145506HICKORY
Solar/Wind Helper
0.242
316336AC2-165 C
Solar/Wind Helper
0.649
316349AD2-085 GEN
Solar/Wind Helper
0.331
316339AD2-160 GEN
Solar/Wind Helper
0.324
316388AE2-253 GEN
Solar/Wind Helper
0.324
315833AF1-017_GEN
Solar/Wind Helper
0.259
235020AA1-095 C
Solar/Wind Helper
0.027
316017AA1-139 ULT1
Solar/Wind Helper
0.389
316018AA1-139 ULT2
Solar/Wind Helper
0.389
3137176SLIGO L2192
Solar/Wind Helper
1.605
3146456SLIGO L269
Solar/Wind Helper
0.403
3146456SLIGO L269
Solar/Wind Helper
0.403
316305AF2-043 C
Solar/Wind Helper
0.13
316246AF1-032 C
Solar/Wind Helper
0.097
319010AE1-072 C
Solar/Wind Helper
0.972
23777901MDS_W4-102
Solar/Wind Helper
0.13
3130086AYDLETT
Solar/Wind Helper
1.612
316320Y1-086
Solar/Wind Helper
0.129
313526AB2-022
Solar/Wind Helper
0.129
3146386ELIZ CT
Solar/Wind Helper
0.402
3146486SUNBURY
Solar/Wind Helper
0.402
3146486SUNBURY
Solar/Wind Helper
0.402
316321Z2-027
Solar/Wind Helper
0.129
3145176PASQUOTANK
Solar/Wind Helper
0.249
3146516WINFALL
Solar/Wind Helper
1.297
3146516WINFALL
Solar/Wind Helper
0.4
3146516WINFALL
Solar/Wind Helper
0.4
3146516WINFALL
Solar/Wind Helper
0.4
3146516WINFALL
Solar/Wind Helper
0.4
3146516WINFALL
Solar/Wind Helper
0.4
3146626S HERTFORD
Solar/Wind Helper
0.4
3146626S HERTFORD
Solar/Wind Helper
0.4
3146626S HERTFORD
Solar/Wind Helper
0.4
316315AB2-025 C
Solar/Wind Helper
0.128
3145273HOLLAND
Solar/Wind Helper
0.3
315742AE1-103 GEN
Solar/Wind Helper
0.256
3130156CHOWAN
Solar/Wind Helper
0.397
3130156CHOWAN
Solar/Wind Helper
0.397
3130156CHOWAN
Solar/Wind Helper
0.397
3146376EDENTON
Solar/Wind Helper
0.397
3132123MT JACKSON
Solar/Wind Helper
1.239
315614AA2-178 GEN
Solar/Wind Helper
0.507
315816AE2-034 GEN
Solar/Wind Helper
0.38
3145663CRESWEL
Solar/Wind Helper
1.105
3138266HYDRAULIC
Solar/Wind Helper
0.018
3138266HYDRAULIC
Solar/Wind Helper
0.011
316322AB2-045
Solar/Wind Helper
0.125
3146776BUCKING
Solar/Wind Helper
1.573
3146776BUCKING
Solar/Wind Helper
0.157
3146776BUCKING
Solar/Wind Helper
0.142
3146776BUCKING
Solar/Wind Helper
0.127
3130546PLYMOUTH
Solar/Wind Helper
0.393
3156081AA2-088 GEN
Solar/Wind Helper
0.631
315732AD1-074 GEN1
Solar/Wind Helper
0.946
315733AD1-074 GEN2
Solar/Wind Helper
0.946
315737AD1-076 GEN
Solar/Wind Helper
0.687
315735AD1-075 GEN1
Solar/Wind Helper
0.473
316065AD1-022 GEN
Solar/Wind Helper
0.503
3146926FARMVIL
Solar/Wind Helper
0.235
3146926FARMVIL
Solar/Wind Helper
0.235
316023GEN1_S
Solar/Wind Helper
0.314
316365GEN2_N
Solar/Wind Helper
0.314
3146206CASHIE
Solar/Wind Helper
0.391
3146206CASHIE
Solar/Wind Helper
0.391
3146206CASHIE
Solar/Wind Helper
0.391
3145893MURPHYS
Solar/Wind Helper
1.565
3145893MURPHYS
Solar/Wind Helper
1.252
3145893MURPHYS
Solar/Wind Helper
1.056
316318V4-068
Solar/Wind Helper
0.029
3145893MURPHYS
Solar/Wind Helper
0.704
3145893MURPHYS
Solar/Wind Helper
0.391
3145893MURPHYS
Solar/Wind Helper
0.391
3145893MURPHYS
Solar/Wind Helper
0.313
3146173TUNIS
Solar/Wind Helper
0.39
3146173TUNIS
Solar/Wind Helper
0.39
3146173TUNIS
Solar/Wind Helper
0.39
3146173TUNIS
Solar/Wind Helper
0.39
3147983MERCK5
Solar/Wind Helper
0.156
316097T157 G90
Solar/Wind Helper
0.257
316095T157 G97
Solar/Wind Helper
0.257
315821AE2-092 GEN
Solar/Wind Helper
0.864
3156021HOLLOMANSOL
Solar/Wind Helper
0.625
316463AE2-346 GEN
Solar/Wind Helper
0.075
316140AB2-099
Solar/Wind Helper
0.031
961941AG1-037 GEN
Solar/Wind Helper
0.031
3145513AHOSKIE
Solar/Wind Helper
0.389
3145513AHOSKIE
Solar/Wind Helper
0.389
942461AE2-259 GEN
Solar/Wind Helper
0.626
946281AF1-292 GEN
Solar/Wind Helper
0.093
966621AG1-532 GEN
Solar/Wind Helper
0.084
3146043SEABORD
Solar/Wind Helper
0.389
3145683EARLEYS
Solar/Wind Helper
0.778
3145683EARLEYS
Solar/Wind Helper
0.389
3145683EARLEYS
Solar/Wind Helper
0.389
3145683EARLEYS
Solar/Wind Helper
0.389
315607AA1-063A GEN
Solar/Wind Helper
0.468
316087AB2-174 GEN
Solar/Wind Helper
0.499
316499AE2-029_GEN
Solar/Wind Helper
0.312
3146263WOODLND
Solar/Wind Helper
0.388
3146263WOODLND
Solar/Wind Helper
0.388
316181AB2-040 GEN
Solar/Wind Helper
0.499
313506AB2-031 GEN
Solar/Wind Helper
0.372
3147133PAMPLIN
Solar/Wind Helper
1.217
3147133PAMPLIN
Solar/Wind Helper
0.387
3147133PAMPLIN
Solar/Wind Helper
0.31
3137643SOCKMAN
Solar/Wind Helper
1.547
3142666NORTHAMPTON
Solar/Wind Helper
0.387
3142666NORTHAMPTON
Solar/Wind Helper
0.387
3142666NORTHAMPTON
Solar/Wind Helper
0.387
3142666NORTHAMPTON
Solar/Wind Helper
0.387
3142666NORTHAMPTON
Solar/Wind Helper
0.232
3147043LAWRENC
Solar/Wind Helper
0.232
316426AA2-053 GEN
Solar/Wind Helper
0.466
316190AA2-174 GEN
Solar/Wind Helper
0.031
3145963POPLR C
Solar/Wind Helper
0.387
3145963POPLR C
Solar/Wind Helper
0.387
316011AB1-132 GEN
Solar/Wind Helper
9.287
316317KELFORD C
Solar/Wind Helper
0.144
3145823KELFORD
Solar/Wind Helper
0.387
3145823KELFORD
Solar/Wind Helper
0.387
3145593CAROLNA
Solar/Wind Helper
0.387
3145593CAROLNA
Solar/Wind Helper
0.387
316174AB2-169 GEN
Solar/Wind Helper
0.459
316478AD1-087 GEN
Solar/Wind Helper
0.398
316486AD2-202 GEN
Solar/Wind Helper
0.117
3145783HORNRTN
Solar/Wind Helper
0.386
3148013FISHERV
Solar/Wind Helper
0.386
3148133STUARTS
Solar/Wind Helper
0.232
3148013FISHERV
Solar/Wind Helper
0.222
3145796HORNRTN
Solar/Wind Helper
1.541
3145796HORNRTN
Solar/Wind Helper
1.271
3145796HORNRTN
Solar/Wind Helper
1.233
3145796HORNRTN
Solar/Wind Helper
1.156
3145796HORNRTN
Solar/Wind Helper
0.385
3145796HORNRTN
Solar/Wind Helper
0.385
3145796HORNRTN
Solar/Wind Helper
0.154
316034AC1-036 C
Solar/Wind Helper
0.085
3144303KENBRDG
Solar/Wind Helper
0.308
3146033SCOT NK
Solar/Wind Helper
1.539
315785AD2-033 C
Solar/Wind Helper
0.803
316129AC1-054 GEN
Solar/Wind Helper
0.4
316210AC1-098 GEN
Solar/Wind Helper
0.554
316212AC1-099_GEN
Solar/Wind Helper
0.308
316131AB2-060 GEN
Solar/Wind Helper
0.492
313527AB2-043 GEN
Solar/Wind Helper
0.307
3145933PARMELE
Solar/Wind Helper
0.765
3145933PARMELE
Solar/Wind Helper
0.382
3145933PARMELE
Solar/Wind Helper
0.382
316274AC1-208 GEN
Solar/Wind Helper
0.491
316239AB2-077_GEN
Solar/Wind Helper
0.123
316238AB2-078_GEN
Solar/Wind Helper
0.123
316237AB2-079_GEN
Solar/Wind Helper
0.123
23583801GRNGAP
Solar/Wind Helper
0.637
316005AA1-067
Solar/Wind Helper
0.092
3145746EVERETS
Solar/Wind Helper
1.513
3145746EVERETS
Solar/Wind Helper
0.38
3145746EVERETS
Solar/Wind Helper
0.38
3145746EVERETS
Solar/Wind Helper
0.38
3145746EVERETS
Solar/Wind Helper
0.38
3145746EVERETS
Solar/Wind Helper
0.38
3145746EVERETS
Solar/Wind Helper
0.38
3145746EVERETS
Solar/Wind Helper
0.38
315687AD1-152 GEN
Solar/Wind Helper
0.489
315722AD1-056 GEN
Solar/Wind Helper
0.366
315724AD1-057 GEN
Solar/Wind Helper
0.201
316327AA2-057 GEN
Solar/Wind Helper
0.457
226929AD2-058 GEN
Solar/Wind Helper
0.034
316494AC1-189 GEN
Solar/Wind Helper
0.487
270494AE1-108_GEN
Solar/Wind Helper
0.909
316420AA1-050 GEN
Solar/Wind Helper
0.486
316319Z2-044 C
Solar/Wind Helper
0.073
3146233WITAKRS
Solar/Wind Helper
1.502
3146233WITAKRS
Solar/Wind Helper
0.257
961671AG1-007 GEN
Solar/Wind Helper
0.057
3145573BETHELC
Solar/Wind Helper
0.377
3145573BETHELC
Solar/Wind Helper
0.377
3146073TAR RVR
Solar/Wind Helper
0.377
3146083TARBORO
Solar/Wind Helper
0.377
3146083TARBORO
Solar/Wind Helper
0.377
238208AF1-136 C
Solar/Wind Helper
0.096
3138543CONSLDL
Solar/Wind Helper
0.249
3146843MT LREL
Solar/Wind Helper
0.377
3146843MT LREL
Solar/Wind Helper
0.377
3145543BTLEBRO
Solar/Wind Helper
0.376
3145543BTLEBRO
Solar/Wind Helper
0.376
3145543BTLEBRO
Solar/Wind Helper
0.376
3145543BTLEBRO
Solar/Wind Helper
0.3
316359AB2-059 GEN
Solar/Wind Helper
0.603
316049AB1-081 GEN
Solar/Wind Helper
0.483
238108AE1-109 GEN1
Solar/Wind Helper
0.04
238109AE1-109 GEN2
Solar/Wind Helper
0.04
238110AE1-109 GEN3
Solar/Wind Helper
0.04
316118AC1-105 GEN
Solar/Wind Helper
0.307
238221AF1-254 C O1
Solar/Wind Helper
0.12
3148463FAIRFLD
Solar/Wind Helper
0.374
237034AC2-136 C
Solar/Wind Helper
0.071
316248AF1-058 C
Solar/Wind Helper
0.12
3147173SINAI
Solar/Wind Helper
0.372
3147243WELCO
Solar/Wind Helper
0.233
316003AC1-222 GEN
Solar/Wind Helper
0.385
227287AC2-120 GEN
Solar/Wind Helper
0.163
226910AB2-157 C
Solar/Wind Helper
0.015
316222AC1-221 GEN
Solar/Wind Helper
0.437
316283AC2-100 C
Solar/Wind Helper
0.407
237080AD1-060 GEN
Solar/Wind Helper
0.087
316123AC1-075 GEN
Solar/Wind Helper
0.462
964991AG1-363 GEN
Solar/Wind Helper
1.702
270455AD2-022 GEN
Solar/Wind Helper
0.544
270457AD2-023 GEN
Solar/Wind Helper
0.306
237038AE2-054 C
Solar/Wind Helper
0.112
235067AD1-061 GEN
Solar/Wind Helper
0.111
3147123OTTER R
Solar/Wind Helper
0.207
316217AC1-145 GEN
Solar/Wind Helper
0.275
316197AC1-042 GEN
Solar/Wind Helper
0.231
3147312GRETNA
Solar/Wind Helper
0.274
3146802CHATHAM
Solar/Wind Helper
0.257
3147312GRETNA
Solar/Wind Helper
0.069
270016AE1-250 BESS
Solar/Wind Helper
0.413
270013AE1-250 PV
Solar/Wind Helper
0.413
237085AD2-009_GEN
Solar/Wind Helper
0.384
270197AD1-017 GEN1
Solar/Wind Helper
0.328
270574AD1-017 GEN2
Solar/Wind Helper
0.328
237002AB1-128_GEN
Solar/Wind Helper
0.108
270173AC1-122 GEN
Solar/Wind Helper
0.411
270018AE2-047 C O1
Solar/Wind Helper
0.269
237001AB1-127_GEN
Solar/Wind Helper
0.107
943811AF1-049 GEN
Solar/Wind Helper
0.663
23750701CROSSCHOOL
Solar/Wind Helper
0.143
235062AE1-101 C1
Solar/Wind Helper
0.397
235063AE1-101 C2
Solar/Wind Helper
0.397
270069AE2-166 C O1
Solar/Wind Helper
0.473
270336AE1-100 GEN
Solar/Wind Helper
0.347
238120AE2-309 GEN
Solar/Wind Helper
0.103
235531U2-073 GEN
Solar/Wind Helper
0.3
23779801AA1-109
Solar/Wind Helper
0.046
238126S14_GEN_1
Solar/Wind Helper
0.32
238127S14_GEN_2
Solar/Wind Helper
0.32
235054AD2-180 GEN
Solar/Wind Helper
0.303
958121AF2-106 GEN
Solar/Wind Helper
0.761
238185AF2-356 C
Solar/Wind Helper
0.884
238118U2-030_1
Solar/Wind Helper
0.04
270214AC2-123 GEN
Solar/Wind Helper
0.376
966391AG1-508 GEN
Solar/Wind Helper
1.775
G-007ALTFEXP_G-007A->PJM
CMTX
54.655
HAMLETPJM->LTFIMP_HAMLET
CLTF
6.408
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.748
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
23.489
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
4.966
BlueGrassPJM->LTFIMP_BlueG
CLTF
15.477
CBM NorthLTFEXP_CBM-N->PJM
CBM
79.452
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
143.875

Details for CHAN-01DOUBS 500.0 kV Ckt 1 line l/o PJM_500_BG_P1_5011_SRT-A


Base Case Flowgate

Area:AP/PJM
Facility Description:
CHAN-01DOUBS 500.0 kV Ckt 1 line
Contingency Name:
PJM_500_BG_P1_5011_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.03 %
Rating:4595.0 MVA
Rating Type:B
MVA to Mitigate:4826.35
MW Contribution:0.42
Bus #Bus NameTypeMW Contribution
200035PCHBTM 3
50/50
18.05
200202DELTA2 ST
50/50
5.45
200200DELTA2 CT1
50/50
3.051
200201DELTA2 CT2
50/50
3.051
200195DELTA ST
50/50
2.696
200192DELTA CT1
50/50
1.617
200193DELTA CT2
50/50
1.617
200194DELTA CT3
50/50
1.617
200034PCHBTM 2
50/50
106.876
200203Y1-065-STG
50/50
6.225
200204Y1-065-CTG1
50/50
3.92
200205Y1-065-CTG2
50/50
3.92
200052ROCKSP 1
50/50
46.506
200053ROCKSP 2
50/50
46.506
200054ROCKSP 3
50/50
46.034
200055ROCKSP 4
50/50
46.034
971149AH1-027 GEN
Solar/Wind Harmer
0.272
233972AC1-094 C
Solar/Wind Harmer
-0.001
970695AG2-447 GEN
Solar/Wind Harmer
0.217
233987AB2-037 GEN
Solar/Wind Harmer
0
234033AF1-007_GEN
Solar/Wind Harmer
22.719
970545AG2-347 GEN
Solar/Wind Harmer
93.587
972133AH1-634 GEN
Solar/Wind Harmer
14.18
972177AH1-672 GEN
Solar/Wind Harmer
0.814
972069AH1-584 GEN
Solar/Wind Harmer
0.543
972071AH1-585 GEN
Solar/Wind Harmer
0.543
972073AH1-586 GEN
Solar/Wind Harmer
9.773
233923SMA
Solar/Wind Harmer
-0.001
233998TM1NIN_3.36
Solar/Wind Harmer
-0.001
233997TMININ_4.2
Solar/Wind Harmer
-0.001
233996TM1833_GEN
Solar/Wind Harmer
-0.001
233990AG1-397 GEN
Solar/Wind Harmer
0
971747AH1-380 GEN
Solar/Wind Harmer
0.217
233990AG1-397 GEN
Solar/Wind Harmer
1.737
233940AF2-379 C
Solar/Wind Harmer
-0.001
234015AF2-250 C
Solar/Wind Harmer
-0.001
971195AH1-057 GEN
Solar/Wind Harmer
0.078
960671AF2-358 GEN
Solar/Wind Harmer
1.085
965821AG1-450 GEN
Solar/Wind Harmer
5.427
232426Y1-080 FULL
Solar/Wind Harmer
0
970277AG2-181 GEN
Solar/Wind Harmer
0.304
233946AB2-136 GEN
Solar/Wind Harmer
-0.001
233964AF2-378 GEN
Solar/Wind Harmer
0.001
234041AC1-190 GEN
Solar/Wind Harmer
0.542
233984AB2-036 GEN
Solar/Wind Harmer
0.995
233968AD2-076_GEN
Solar/Wind Harmer
0.529
234014AF1-036_GEN
Solar/Wind Harmer
0.216
970597AG2-380 GEN
Solar/Wind Harmer
4.319
234012AE2-112_GEN
Solar/Wind Harmer
0.184
971983AH1-536 GEN
Solar/Wind Harmer
0.451
970453AG2-297 GEN
Solar/Wind Harmer
0.199
971553AH1-274 GEN
Solar/Wind Harmer
0.175
945431AF1-208 GEN
Solar/Wind Harmer
0.47
970997AG2-616 GEN
Solar/Wind Harmer
0.522
972141AH1-641 GEN
Solar/Wind Harmer
0.157
230430AE1-229_GEN
Solar/Wind Harmer
-0.001
228351V2-046C
Solar/Wind Harmer
-0.001
230433AD2-135 GEN
Solar/Wind Harmer
0
230422AE1-104_GEN1
Solar/Wind Harmer
43.284
230425AE1-104_GEN2
Solar/Wind Harmer
43.284
971011AG2-627 GEN
Solar/Wind Harmer
0.417
971535AH1-265 GEN
Solar/Wind Harmer
0.306
230407AD2-065 C
Solar/Wind Harmer
0
228754AB1-001 C
Solar/Wind Harmer
-0.001
219137THOSOLAR C
Solar/Wind Harmer
0.001
219623KINSLEYBEA C
Solar/Wind Harmer
-0.001
219258KINSLEYDEP C
Solar/Wind Harmer
0
219766PARADISE C
Solar/Wind Harmer
-0.001
218660EHAMPSOLAR C
Solar/Wind Harmer
-0.001
219907AC1-030 C
Solar/Wind Harmer
-0.001
219236SOUTHERNHQ C
Solar/Wind Harmer
-0.001
219906AC1-017 C
Solar/Wind Harmer
-0.001
219615MILLCREEK C
Solar/Wind Harmer
-0.001
214067T20SOLAR
Solar/Wind Harmer
-0.001
207522AF2-254 C
Solar/Wind Harmer
0.102
207500AE2-000G1
Solar/Wind Harmer
39.772
207497AE2-000G2
Solar/Wind Harmer
39.772
207507AE2-000G3
Solar/Wind Harmer
39.772
207487AE2-000G4
Solar/Wind Harmer
39.772
970025AG2-016 GEN
Solar/Wind Harmer
0.201
971189AH1-054 GEN
Solar/Wind Harmer
0.084
971667AH1-334 GEN
Solar/Wind Harmer
0.195
219727YARDVSOLFA C
Solar/Wind Harmer
0.001
219276PARKLANDSO C
Solar/Wind Harmer
0
219817TRENTONSOL C
Solar/Wind Harmer
0.001
219620RIDERU C
Solar/Wind Harmer
-0.001
20714328BYD_X4-031
Solar/Wind Harmer
0.02
20714428HOW_X1-037
Solar/Wind Harmer
-0.001
219918AC2-009 C
Solar/Wind Harmer
0
20720628TIN_W1-124
Solar/Wind Harmer
-0.001
20742028HF_AC1-207
Solar/Wind Harmer
-0.001
971521AH1-258 GEN
Solar/Wind Harmer
0.192
967451AG2-055 C O1
Solar/Wind Harmer
220.162
219612MATRIX C
Solar/Wind Harmer
0
218438BLK ROCK C
Solar/Wind Harmer
0
218526CNTRALGAS2 C
Solar/Wind Harmer
0.001
218524CNTRALGAS1 C
Solar/Wind Harmer
0.001
218428ETC SOLAR C
Solar/Wind Harmer
0
219249CENTRALDIV C
Solar/Wind Harmer
-0.001
217213AMBOY SO C
Solar/Wind Harmer
-0.001
20673828FLE_V3-070
Solar/Wind Harmer
0.071
20675428EAM_W2-061
Solar/Wind Harmer
0
218449LINSOLAR C
Solar/Wind Harmer
0.001
217081WEATEXAS C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
217206BARNGR HS C
Solar/Wind Harmer
0
217208PARK ELE C
Solar/Wind Harmer
0
207439AE1-081 C O1
Solar/Wind Harmer
0
20676328BVR_Y1-020
Solar/Wind Harmer
0
20674628WNG_W3-110
Solar/Wind Harmer
-0.001
207511W3-106 GEN
Solar/Wind Harmer
0.047
971009AG2-626 GEN
Solar/Wind Harmer
0.119
971007AG2-625 GEN
Solar/Wind Harmer
0.186
971519AH1-257 GEN
Solar/Wind Harmer
0.183
207437AD2-070 GEN
Solar/Wind Harmer
-0.001
966181AG1-487 GEN
Solar/Wind Harmer
0
966181AG1-487 GEN
Solar/Wind Harmer
3.607
966111AG1-480 GEN
Solar/Wind Harmer
0
966111AG1-480 GEN
Solar/Wind Harmer
3.176
970095AG2-074 GEN
Solar/Wind Harmer
0.334
208862AG1-362 C
Solar/Wind Harmer
0.044
209027LOR2_Q27
Solar/Wind Harmer
9.893
212266LOR1
Solar/Wind Harmer
0.185
970237AG2-161 GEN
Solar/Wind Harmer
0.218
961541AF2-445A GEN
Solar/Wind Harmer
0.173
208972BECR K09
Solar/Wind Harmer
2.458
209142AF1-226 GEN
Solar/Wind Harmer
0.303
209093AE2-110 GEN
Solar/Wind Harmer
0.173
209120AE2-241 GEN
Solar/Wind Harmer
0.173
209045AE2-271 GEN
Solar/Wind Harmer
0.875
209029WAYMART-WD
Solar/Wind Harmer
6.522
209059AE2-084 GEN
Solar/Wind Harmer
0.171
970665AG2-430 GEN
Solar/Wind Harmer
0.51
209130AF1-271A GEN
Solar/Wind Harmer
0.145
205967AE2-211_GEN
Solar/Wind Harmer
0.515
208835TUHI V3-051
Solar/Wind Harmer
0.062
208835TUHI V3-051
Solar/Wind Harmer
0.062
970679AG2-439 GEN
Solar/Wind Harmer
0.061
960921AF2-383 GEN
Solar/Wind Harmer
1.733
200917MEHOOPANY_G
Solar/Wind Harmer
8.726
208856AE1-226 GEN
Solar/Wind Harmer
0.101
3138216PACIFIC
Solar/Wind Helper
0.079
316411AF1-147_GEN1
Solar/Wind Helper
0.381
316415AF1-147_GEN2
Solar/Wind Helper
0.381
3141196NOKESVL
Solar/Wind Helper
1.832
316006AB2-029 C
Solar/Wind Helper
0.141
238175AF1-290_GEN
Solar/Wind Helper
0.563
315651AD1-115 GEN
Solar/Wind Helper
1.047
316045AC1-158 PL2
Solar/Wind Helper
1.625
316447AC1-158 HLD
Solar/Wind Helper
1.117
316044AC1-158 PL1
Solar/Wind Helper
0.508
316450AC1-158 RIC
Solar/Wind Helper
0.135
3141426STAFORD
Solar/Wind Helper
0.096
316254AC1-120 GEN1
Solar/Wind Helper
0.417
316170AC1-121 GEN2
Solar/Wind Helper
0.139
316164AC1-076 GEN
Solar/Wind Helper
0.434
238169AE2-226 GEN1
Solar/Wind Helper
0.342
238170AE2-226 GEN2
Solar/Wind Helper
0.342
964441AG1-307 GEN
Solar/Wind Helper
0.549
3132273ORANGE
Solar/Wind Helper
0.085
3147666LOUISA
Solar/Wind Helper
1.678
3147666LOUISA
Solar/Wind Helper
0.965
316192AB2-158 GEN
Solar/Wind Helper
0.594
966001AG1-469 GEN
Solar/Wind Helper
0.094
966881AG1-559 GEN
Solar/Wind Helper
0.134
944491AF1-114 GEN
Solar/Wind Helper
0.668
957971AF2-091 GEN
Solar/Wind Helper
0.227
238152AF2-075_GEN
Solar/Wind Helper
0.331
238147AE2-230_GEN1
Solar/Wind Helper
0.464
238148AE2-230_GEN2
Solar/Wind Helper
0.464
238149AF1-291A_GEN
Solar/Wind Helper
0.066
316468AD1-105 GEN
Solar/Wind Helper
0.489
316223AC1-118
Solar/Wind Helper
0.132
3141906WESTMOR
Solar/Wind Helper
0.164
23546401DTGZ2-030
Solar/Wind Helper
0.066
316337AD2-073 GEN
Solar/Wind Helper
0.131
316077AC2-138 C
Solar/Wind Helper
0.091
3141813NORNECK
Solar/Wind Helper
0.406
237061AD1-155 GEN
Solar/Wind Helper
0.49
964211AG1-282 GEN
Solar/Wind Helper
0.13
3141726DUNNSVL
Solar/Wind Helper
1.624
316473AC1-191 GEN
Solar/Wind Helper
0.522
966871AG1-558 GEN
Solar/Wind Helper
0.13
316404AE1-155 C
Solar/Wind Helper
0.827
316484AD2-074 GEN
Solar/Wind Helper
0.559
316487AF1-042 GEN
Solar/Wind Helper
0.292
961951AG1-038 GEN
Solar/Wind Helper
0.292
316312AB1-027
Solar/Wind Helper
0.162
3142416OLDCHRC
Solar/Wind Helper
1.049
3142416OLDCHRC
Solar/Wind Helper
0.402
3141783LANCAST
Solar/Wind Helper
0.242
3141783LANCAST
Solar/Wind Helper
0.161
3138133OCRAN
Solar/Wind Helper
0.242
3138133OCRAN
Solar/Wind Helper
0.121
3141913WHIT STONE
Solar/Wind Helper
0.402
316075AC2-137 C
Solar/Wind Helper
0.129
316314AB2-024 C
Solar/Wind Helper
0.129
316059AD1-063 C
Solar/Wind Helper
0.097
3141766HARMONY
Solar/Wind Helper
0.08
3143873LANEXA
Solar/Wind Helper
0.241
316203AE2-005 GEN
Solar/Wind Helper
0.839
315662AE1-191 GEN
Solar/Wind Helper
0.516
316280AD1-041 GEN
Solar/Wind Helper
0.323
315666AE1-190 GEN
Solar/Wind Helper
0.129
316441AF1-014 GEN
Solar/Wind Helper
0.128
957601AF2-054 GEN
Solar/Wind Helper
0.128
316156AD2-030 GEN
Solar/Wind Helper
0.128
3141873WAN 176
Solar/Wind Helper
0.08
316233AE1-074 FULL
Solar/Wind Helper
0.129
3143526WINTERP
Solar/Wind Helper
2.089
3143526WINTERP
Solar/Wind Helper
2.089
3143226MDLTHAN
Solar/Wind Helper
0.401
3142433PROV 92
Solar/Wind Helper
1.606
3142543TWELFTH
Solar/Wind Helper
0.039
3142946ENON
Solar/Wind Helper
0.134
3142946ENON
Solar/Wind Helper
0.04
957831AF2-077 GEN
Solar/Wind Helper
0.128
316382AG1-145 C
Solar/Wind Helper
0.128
316159AE1-175 C
Solar/Wind Helper
0.128
316240AF1-291 C
Solar/Wind Helper
0.128
316132AB2-190 GEN1
Solar/Wind Helper
0.479
316458AB2-190 GEN2
Solar/Wind Helper
0.479
315697AD1-025 GEN
Solar/Wind Helper
0.955
316033AB2-134 GEN
Solar/Wind Helper
0.907
316369SG1_INVT
Solar/Wind Helper
0.624
315839AE2-212 C
Solar/Wind Helper
0.127
961611AG1-000B GEN
Solar/Wind Helper
0.566
316236AE1-162_GEN
Solar/Wind Helper
0.127
3145336SMITFLD
Solar/Wind Helper
1.576
3145336SMITFLD
Solar/Wind Helper
0.158
3143316POE
Solar/Wind Helper
1.56
316294AC1-161 GEN
Solar/Wind Helper
1.518
315773AC2-141 GEN
Solar/Wind Helper
1.518
316313AB2-026
Solar/Wind Helper
0.127
316258AE1-075 C
Solar/Wind Helper
0.114
316405AF2-144 C
Solar/Wind Helper
0.108
316381AD1-082 GEN
Solar/Wind Helper
0.429
316083AB2-161 GEN
Solar/Wind Helper
0.316
3144536CHRHLND
Solar/Wind Helper
0.059
316375AC2-012 GEN
Solar/Wind Helper
0.744
316036AC1-147 C
Solar/Wind Helper
0.126
3144873MCLAUGH
Solar/Wind Helper
0.01
316316AC1-027 C
Solar/Wind Helper
0.111
316185AD1-033 GEN
Solar/Wind Helper
0.441
316072AD1-144
Solar/Wind Helper
0.094
316336AC2-165 C
Solar/Wind Helper
0.629
3145506HICKORY
Solar/Wind Helper
1.567
3145506HICKORY
Solar/Wind Helper
0.94
3145506HICKORY
Solar/Wind Helper
0.235
316349AD2-085 GEN
Solar/Wind Helper
0.321
315833AF1-017_GEN
Solar/Wind Helper
0.251
316339AD2-160 GEN
Solar/Wind Helper
0.314
316388AE2-253 GEN
Solar/Wind Helper
0.314
316017AA1-139 ULT1
Solar/Wind Helper
0.377
316018AA1-139 ULT2
Solar/Wind Helper
0.377
3137176SLIGO L2192
Solar/Wind Helper
1.556
3146456SLIGO L269
Solar/Wind Helper
0.391
3146456SLIGO L269
Solar/Wind Helper
0.391
316305AF2-043 C
Solar/Wind Helper
0.126
316246AF1-032 C
Solar/Wind Helper
0.094
319010AE1-072 C
Solar/Wind Helper
0.942
3130086AYDLETT
Solar/Wind Helper
1.563
235020AA1-095 C
Solar/Wind Helper
0.026
316320Y1-086
Solar/Wind Helper
0.125
313526AB2-022
Solar/Wind Helper
0.125
3146386ELIZ CT
Solar/Wind Helper
0.389
23777901MDS_W4-102
Solar/Wind Helper
0.125
3146486SUNBURY
Solar/Wind Helper
0.389
3146486SUNBURY
Solar/Wind Helper
0.389
316321Z2-027
Solar/Wind Helper
0.125
3145176PASQUOTANK
Solar/Wind Helper
0.241
3146516WINFALL
Solar/Wind Helper
1.256
3146516WINFALL
Solar/Wind Helper
0.388
3146516WINFALL
Solar/Wind Helper
0.388
3146516WINFALL
Solar/Wind Helper
0.388
3146516WINFALL
Solar/Wind Helper
0.388
3146516WINFALL
Solar/Wind Helper
0.388
3146626S HERTFORD
Solar/Wind Helper
0.387
3146626S HERTFORD
Solar/Wind Helper
0.387
3146626S HERTFORD
Solar/Wind Helper
0.387
316315AB2-025 C
Solar/Wind Helper
0.124
3145273HOLLAND
Solar/Wind Helper
0.29
315742AE1-103 GEN
Solar/Wind Helper
0.247
3130156CHOWAN
Solar/Wind Helper
0.384
3130156CHOWAN
Solar/Wind Helper
0.384
3130156CHOWAN
Solar/Wind Helper
0.384
3146376EDENTON
Solar/Wind Helper
0.384
3132123MT JACKSON
Solar/Wind Helper
1.199
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.011
315614AA2-178 GEN
Solar/Wind Helper
0.49
315816AE2-034 GEN
Solar/Wind Helper
0.368
3145663CRESWEL
Solar/Wind Helper
1.067
316322AB2-045
Solar/Wind Helper
0.121
3146776BUCKING
Solar/Wind Helper
1.519
3146776BUCKING
Solar/Wind Helper
0.152
3146776BUCKING
Solar/Wind Helper
0.137
3146776BUCKING
Solar/Wind Helper
0.123
3130546PLYMOUTH
Solar/Wind Helper
0.379
3156081AA2-088 GEN
Solar/Wind Helper
0.609
315732AD1-074 GEN1
Solar/Wind Helper
0.912
315733AD1-074 GEN2
Solar/Wind Helper
0.912
315737AD1-076 GEN
Solar/Wind Helper
0.663
315735AD1-075 GEN1
Solar/Wind Helper
0.456
316065AD1-022 GEN
Solar/Wind Helper
0.486
3146926FARMVIL
Solar/Wind Helper
0.227
3146926FARMVIL
Solar/Wind Helper
0.227
316023GEN1_S
Solar/Wind Helper
0.303
316365GEN2_N
Solar/Wind Helper
0.303
3146206CASHIE
Solar/Wind Helper
0.377
3146206CASHIE
Solar/Wind Helper
0.377
3146206CASHIE
Solar/Wind Helper
0.377
3145893MURPHYS
Solar/Wind Helper
1.509
3145893MURPHYS
Solar/Wind Helper
1.207
3145893MURPHYS
Solar/Wind Helper
1.019
316318V4-068
Solar/Wind Helper
0.028
3145893MURPHYS
Solar/Wind Helper
0.679
3145893MURPHYS
Solar/Wind Helper
0.377
3145893MURPHYS
Solar/Wind Helper
0.377
3145893MURPHYS
Solar/Wind Helper
0.302
316097T157 G90
Solar/Wind Helper
0.248
316095T157 G97
Solar/Wind Helper
0.248
3147983MERCK5
Solar/Wind Helper
0.151
3146173TUNIS
Solar/Wind Helper
0.376
3146173TUNIS
Solar/Wind Helper
0.376
3146173TUNIS
Solar/Wind Helper
0.376
3146173TUNIS
Solar/Wind Helper
0.376
315821AE2-092 GEN
Solar/Wind Helper
0.833
3156021HOLLOMANSOL
Solar/Wind Helper
0.603
942461AE2-259 GEN
Solar/Wind Helper
0.603
316463AE2-346 GEN
Solar/Wind Helper
0.072
316140AB2-099
Solar/Wind Helper
0.03
961941AG1-037 GEN
Solar/Wind Helper
0.03
3145513AHOSKIE
Solar/Wind Helper
0.375
3145513AHOSKIE
Solar/Wind Helper
0.375
946281AF1-292 GEN
Solar/Wind Helper
0.09
966621AG1-532 GEN
Solar/Wind Helper
0.081
3146043SEABORD
Solar/Wind Helper
0.375
3145683EARLEYS
Solar/Wind Helper
0.75
3145683EARLEYS
Solar/Wind Helper
0.375
3145683EARLEYS
Solar/Wind Helper
0.375
3145683EARLEYS
Solar/Wind Helper
0.375
315607AA1-063A GEN
Solar/Wind Helper
0.451
316499AE2-029_GEN
Solar/Wind Helper
0.301
316087AB2-174 GEN
Solar/Wind Helper
0.481
3146263WOODLND
Solar/Wind Helper
0.374
3146263WOODLND
Solar/Wind Helper
0.374
316181AB2-040 GEN
Solar/Wind Helper
0.481
313506AB2-031 GEN
Solar/Wind Helper
0.358
3147133PAMPLIN
Solar/Wind Helper
1.172
3147133PAMPLIN
Solar/Wind Helper
0.373
3147133PAMPLIN
Solar/Wind Helper
0.299
3137643SOCKMAN
Solar/Wind Helper
1.49
3142666NORTHAMPTON
Solar/Wind Helper
0.373
3142666NORTHAMPTON
Solar/Wind Helper
0.373
3142666NORTHAMPTON
Solar/Wind Helper
0.373
3142666NORTHAMPTON
Solar/Wind Helper
0.373
3142666NORTHAMPTON
Solar/Wind Helper
0.224
3147043LAWRENC
Solar/Wind Helper
0.224
316426AA2-053 GEN
Solar/Wind Helper
0.449
316190AA2-174 GEN
Solar/Wind Helper
0.03
3145963POPLR C
Solar/Wind Helper
0.373
3145963POPLR C
Solar/Wind Helper
0.373
316011AB1-132 GEN
Solar/Wind Helper
8.943
316317KELFORD C
Solar/Wind Helper
0.138
3145823KELFORD
Solar/Wind Helper
0.372
3145823KELFORD
Solar/Wind Helper
0.372
3145593CAROLNA
Solar/Wind Helper
0.372
3145593CAROLNA
Solar/Wind Helper
0.372
3148013FISHERV
Solar/Wind Helper
0.372
3148133STUARTS
Solar/Wind Helper
0.223
3148013FISHERV
Solar/Wind Helper
0.214
316174AB2-169 GEN
Solar/Wind Helper
0.442
316478AD1-087 GEN
Solar/Wind Helper
0.383
316486AD2-202 GEN
Solar/Wind Helper
0.112
3145783HORNRTN
Solar/Wind Helper
0.371
3145796HORNRTN
Solar/Wind Helper
1.483
3145796HORNRTN
Solar/Wind Helper
1.223
3145796HORNRTN
Solar/Wind Helper
1.186
3145796HORNRTN
Solar/Wind Helper
1.112
3145796HORNRTN
Solar/Wind Helper
0.371
3145796HORNRTN
Solar/Wind Helper
0.371
3145796HORNRTN
Solar/Wind Helper
0.148
316034AC1-036 C
Solar/Wind Helper
0.082
3144303KENBRDG
Solar/Wind Helper
0.296
3146033SCOT NK
Solar/Wind Helper
1.48
315785AD2-033 C
Solar/Wind Helper
0.772
316129AC1-054 GEN
Solar/Wind Helper
0.385
316210AC1-098 GEN
Solar/Wind Helper
0.532
316212AC1-099_GEN
Solar/Wind Helper
0.296
316131AB2-060 GEN
Solar/Wind Helper
0.473
313527AB2-043 GEN
Solar/Wind Helper
0.295
3145933PARMELE
Solar/Wind Helper
0.735
3145933PARMELE
Solar/Wind Helper
0.368
3145933PARMELE
Solar/Wind Helper
0.368
316274AC1-208 GEN
Solar/Wind Helper
0.472
316239AB2-077_GEN
Solar/Wind Helper
0.118
316238AB2-078_GEN
Solar/Wind Helper
0.118
316237AB2-079_GEN
Solar/Wind Helper
0.118
23583801GRNGAP
Solar/Wind Helper
0.613
316005AA1-067
Solar/Wind Helper
0.088
3145746EVERETS
Solar/Wind Helper
1.453
3145746EVERETS
Solar/Wind Helper
0.365
3145746EVERETS
Solar/Wind Helper
0.365
3145746EVERETS
Solar/Wind Helper
0.365
3145746EVERETS
Solar/Wind Helper
0.365
3145746EVERETS
Solar/Wind Helper
0.365
3145746EVERETS
Solar/Wind Helper
0.365
3145746EVERETS
Solar/Wind Helper
0.365
315687AD1-152 GEN
Solar/Wind Helper
0.469
315722AD1-056 GEN
Solar/Wind Helper
0.352
315724AD1-057 GEN
Solar/Wind Helper
0.193
316327AA2-057 GEN
Solar/Wind Helper
0.439
316494AC1-189 GEN
Solar/Wind Helper
0.467
270494AE1-108_GEN
Solar/Wind Helper
0.873
316420AA1-050 GEN
Solar/Wind Helper
0.466
238208AF1-136 C
Solar/Wind Helper
0.092
316319Z2-044 C
Solar/Wind Helper
0.07
3146233WITAKRS
Solar/Wind Helper
1.44
3146233WITAKRS
Solar/Wind Helper
0.246
961671AG1-007 GEN
Solar/Wind Helper
0.055
3145573BETHELC
Solar/Wind Helper
0.362
3145573BETHELC
Solar/Wind Helper
0.362
3146073TAR RVR
Solar/Wind Helper
0.362
3146083TARBORO
Solar/Wind Helper
0.362
3146083TARBORO
Solar/Wind Helper
0.362
3138543CONSLDL
Solar/Wind Helper
0.239
3146843MT LREL
Solar/Wind Helper
0.361
3146843MT LREL
Solar/Wind Helper
0.361
238108AE1-109 GEN1
Solar/Wind Helper
0.038
238109AE1-109 GEN2
Solar/Wind Helper
0.038
238110AE1-109 GEN3
Solar/Wind Helper
0.038
316359AB2-059 GEN
Solar/Wind Helper
0.578
316049AB1-081 GEN
Solar/Wind Helper
0.462
3145543BTLEBRO
Solar/Wind Helper
0.36
3145543BTLEBRO
Solar/Wind Helper
0.36
3145543BTLEBRO
Solar/Wind Helper
0.36
3145543BTLEBRO
Solar/Wind Helper
0.288
316118AC1-105 GEN
Solar/Wind Helper
0.294
3148463FAIRFLD
Solar/Wind Helper
0.358
238221AF1-254 C O1
Solar/Wind Helper
0.115
316248AF1-058 C
Solar/Wind Helper
0.114
3147173SINAI
Solar/Wind Helper
0.356
3147243WELCO
Solar/Wind Helper
0.223
316003AC1-222 GEN
Solar/Wind Helper
0.368
237034AC2-136 C
Solar/Wind Helper
0.067
226929AD2-058 GEN
Solar/Wind Helper
0.031
316222AC1-221 GEN
Solar/Wind Helper
0.416
316283AC2-100 C
Solar/Wind Helper
0.387
237080AD1-060 GEN
Solar/Wind Helper
0.083
316123AC1-075 GEN
Solar/Wind Helper
0.439
964991AG1-363 GEN
Solar/Wind Helper
1.618
270455AD2-022 GEN
Solar/Wind Helper
0.515
270457AD2-023 GEN
Solar/Wind Helper
0.29
227287AC2-120 GEN
Solar/Wind Helper
0.148
237038AE2-054 C
Solar/Wind Helper
0.106
235067AD1-061 GEN
Solar/Wind Helper
0.105
3147123OTTER R
Solar/Wind Helper
0.196
226910AB2-157 C
Solar/Wind Helper
0.014
316217AC1-145 GEN
Solar/Wind Helper
0.26
316197AC1-042 GEN
Solar/Wind Helper
0.218
3147312GRETNA
Solar/Wind Helper
0.259
3146802CHATHAM
Solar/Wind Helper
0.242
3147312GRETNA
Solar/Wind Helper
0.065
270016AE1-250 BESS
Solar/Wind Helper
0.389
270013AE1-250 PV
Solar/Wind Helper
0.389
237085AD2-009_GEN
Solar/Wind Helper
0.362
270197AD1-017 GEN1
Solar/Wind Helper
0.309
270574AD1-017 GEN2
Solar/Wind Helper
0.309
237002AB1-128_GEN
Solar/Wind Helper
0.102
270173AC1-122 GEN
Solar/Wind Helper
0.387
270018AE2-047 C O1
Solar/Wind Helper
0.253
237001AB1-127_GEN
Solar/Wind Helper
0.1
G-007ALTFEXP_G-007A->PJM
CMTX
47.482
HAMLETPJM->LTFIMP_HAMLET
CLTF
6.05
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.515
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
21.262
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
4.474
BlueGrassPJM->LTFIMP_BlueG
CLTF
13.95
CBM NorthLTFEXP_CBM-N->PJM
CBM
72.155
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
125.936

Details for CNASTONE-BRIGHTON 500.0 kV Ckt 1 line l/o AP_P1-2_PE-500-3835T_SRT-A


Base Case Flowgate

Area:PJM
Facility Description:
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-500-3835T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:137.01 %
Rating:3507.0 MVA
Rating Type:B
MVA to Mitigate:4805.1
MW Contribution:0.37
Bus #Bus NameTypeMW Contribution
972281AH1-725 GEN
50/50
134.551
200202DELTA2 ST
50/50
5.054
200200DELTA2 CT1
50/50
2.829
200201DELTA2 CT2
50/50
2.829
200195DELTA ST
50/50
2.501
200192DELTA CT1
50/50
1.5
200193DELTA CT2
50/50
1.5
200194DELTA CT3
50/50
1.5
200034PCHBTM 2
50/50
99.11
200035PCHBTM 3
50/50
16.323
200203Y1-065-STG
50/50
5.747
200204Y1-065-CTG1
50/50
3.619
200205Y1-065-CTG2
50/50
3.619
200052ROCKSP 1
50/50
42.938
200053ROCKSP 2
50/50
42.938
200054ROCKSP 3
50/50
42.502
200055ROCKSP 4
50/50
42.502
233987AB2-037 GEN
Solar/Wind Harmer
0
971149AH1-027 GEN
Solar/Wind Harmer
0.245
234033AF1-007_GEN
Solar/Wind Harmer
20.523
233972AC1-094 C
Solar/Wind Harmer
-0.001
970545AG2-347 GEN
Solar/Wind Harmer
84.541
972133AH1-634 GEN
Solar/Wind Harmer
12.809
970695AG2-447 GEN
Solar/Wind Harmer
0.196
972069AH1-584 GEN
Solar/Wind Harmer
0.491
972071AH1-585 GEN
Solar/Wind Harmer
0.491
972073AH1-586 GEN
Solar/Wind Harmer
8.829
233923SMA
Solar/Wind Harmer
-0.001
233998TM1NIN_3.36
Solar/Wind Harmer
-0.001
233997TMININ_4.2
Solar/Wind Harmer
-0.001
233996TM1833_GEN
Solar/Wind Harmer
-0.001
233990AG1-397 GEN
Solar/Wind Harmer
0
233940AF2-379 C
Solar/Wind Harmer
-0.001
971747AH1-380 GEN
Solar/Wind Harmer
0.196
233990AG1-397 GEN
Solar/Wind Harmer
1.57
234015AF2-250 C
Solar/Wind Harmer
0
971195AH1-057 GEN
Solar/Wind Harmer
0.071
972177AH1-672 GEN
Solar/Wind Harmer
0.736
232426Y1-080 FULL
Solar/Wind Harmer
0
960671AF2-358 GEN
Solar/Wind Harmer
0.981
970277AG2-181 GEN
Solar/Wind Harmer
0.275
965821AG1-450 GEN
Solar/Wind Harmer
4.903
233946AB2-136 GEN
Solar/Wind Harmer
-0.001
233964AF2-378 GEN
Solar/Wind Harmer
0
234041AC1-190 GEN
Solar/Wind Harmer
0.49
233984AB2-036 GEN
Solar/Wind Harmer
0.899
233968AD2-076_GEN
Solar/Wind Harmer
0.478
234014AF1-036_GEN
Solar/Wind Harmer
0.195
970597AG2-380 GEN
Solar/Wind Harmer
3.904
234012AE2-112_GEN
Solar/Wind Harmer
0.166
971983AH1-536 GEN
Solar/Wind Harmer
0.407
970453AG2-297 GEN
Solar/Wind Harmer
0.177
971553AH1-274 GEN
Solar/Wind Harmer
0.155
945431AF1-208 GEN
Solar/Wind Harmer
0.418
970997AG2-616 GEN
Solar/Wind Harmer
0.463
972141AH1-641 GEN
Solar/Wind Harmer
0.139
230430AE1-229_GEN
Solar/Wind Harmer
-0.001
228351V2-046C
Solar/Wind Harmer
-0.001
230433AD2-135 GEN
Solar/Wind Harmer
0
230422AE1-104_GEN1
Solar/Wind Harmer
38.394
230425AE1-104_GEN2
Solar/Wind Harmer
38.394
971011AG2-627 GEN
Solar/Wind Harmer
0.37
971535AH1-265 GEN
Solar/Wind Harmer
0.272
230407AD2-065 C
Solar/Wind Harmer
0
228754AB1-001 C
Solar/Wind Harmer
-0.001
219137THOSOLAR C
Solar/Wind Harmer
0.001
219623KINSLEYBEA C
Solar/Wind Harmer
-0.001
219258KINSLEYDEP C
Solar/Wind Harmer
0
219766PARADISE C
Solar/Wind Harmer
-0.001
218660EHAMPSOLAR C
Solar/Wind Harmer
-0.001
219907AC1-030 C
Solar/Wind Harmer
-0.001
219236SOUTHERNHQ C
Solar/Wind Harmer
-0.001
219906AC1-017 C
Solar/Wind Harmer
-0.001
219615MILLCREEK C
Solar/Wind Harmer
-0.001
214067T20SOLAR
Solar/Wind Harmer
-0.001
207522AF2-254 C
Solar/Wind Harmer
0.089
207500AE2-000G1
Solar/Wind Harmer
34.882
207497AE2-000G2
Solar/Wind Harmer
34.882
207507AE2-000G3
Solar/Wind Harmer
34.882
207487AE2-000G4
Solar/Wind Harmer
34.882
970025AG2-016 GEN
Solar/Wind Harmer
0.176
971189AH1-054 GEN
Solar/Wind Harmer
0.073
971667AH1-334 GEN
Solar/Wind Harmer
0.171
219727YARDVSOLFA C
Solar/Wind Harmer
0.001
219276PARKLANDSO C
Solar/Wind Harmer
0
219817TRENTONSOL C
Solar/Wind Harmer
0.001
219620RIDERU C
Solar/Wind Harmer
-0.001
20714328BYD_X4-031
Solar/Wind Harmer
0.018
20714428HOW_X1-037
Solar/Wind Harmer
-0.001
219918AC2-009 C
Solar/Wind Harmer
0
20720628TIN_W1-124
Solar/Wind Harmer
-0.001
20742028HF_AC1-207
Solar/Wind Harmer
-0.001
971521AH1-258 GEN
Solar/Wind Harmer
0.168
967451AG2-055 C O1
Solar/Wind Harmer
191.622
219612MATRIX C
Solar/Wind Harmer
0
218438BLK ROCK C
Solar/Wind Harmer
0
218526CNTRALGAS2 C
Solar/Wind Harmer
0.001
218524CNTRALGAS1 C
Solar/Wind Harmer
0.001
218428ETC SOLAR C
Solar/Wind Harmer
0
217213AMBOY SO C
Solar/Wind Harmer
-0.001
219249CENTRALDIV C
Solar/Wind Harmer
0
20673828FLE_V3-070
Solar/Wind Harmer
0.061
20675428EAM_W2-061
Solar/Wind Harmer
0
218449LINSOLAR C
Solar/Wind Harmer
0.001
217081WEATEXAS C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
217206BARNGR HS C
Solar/Wind Harmer
0
217208PARK ELE C
Solar/Wind Harmer
0
207439AE1-081 C O1
Solar/Wind Harmer
0
20676328BVR_Y1-020
Solar/Wind Harmer
0
20674628WNG_W3-110
Solar/Wind Harmer
-0.001
207511W3-106 GEN
Solar/Wind Harmer
0.041
971009AG2-626 GEN
Solar/Wind Harmer
0.102
971007AG2-625 GEN
Solar/Wind Harmer
0.159
971519AH1-257 GEN
Solar/Wind Harmer
0.156
207437AD2-070 GEN
Solar/Wind Harmer
-0.001
966181AG1-487 GEN
Solar/Wind Harmer
0
966181AG1-487 GEN
Solar/Wind Harmer
3.085
966111AG1-480 GEN
Solar/Wind Harmer
0
966111AG1-480 GEN
Solar/Wind Harmer
2.715
970095AG2-074 GEN
Solar/Wind Harmer
0.283
208972BECR K09
Solar/Wind Harmer
2.085
208862AG1-362 C
Solar/Wind Harmer
0.037
209027LOR2_Q27
Solar/Wind Harmer
8.345
212266LOR1
Solar/Wind Harmer
0.156
970237AG2-161 GEN
Solar/Wind Harmer
0.184
961541AF2-445A GEN
Solar/Wind Harmer
0.146
209029WAYMART-WD
Solar/Wind Harmer
5.552
209142AF1-226 GEN
Solar/Wind Harmer
0.255
209093AE2-110 GEN
Solar/Wind Harmer
0.146
209120AE2-241 GEN
Solar/Wind Harmer
0.146
209045AE2-271 GEN
Solar/Wind Harmer
0.737
209059AE2-084 GEN
Solar/Wind Harmer
0.144
970665AG2-430 GEN
Solar/Wind Harmer
0.429
209130AF1-271A GEN
Solar/Wind Harmer
0.121
208835TUHI V3-051
Solar/Wind Harmer
0.059
208835TUHI V3-051
Solar/Wind Harmer
0.059
205967AE2-211_GEN
Solar/Wind Harmer
0.451
960921AF2-383 GEN
Solar/Wind Harmer
1.592
970679AG2-439 GEN
Solar/Wind Harmer
0.053
226929AD2-058 GEN
Solar/Wind Helper
0.04
227287AC2-120 GEN
Solar/Wind Helper
0.198
226910AB2-157 C
Solar/Wind Helper
0.018
3138216PACIFIC
Solar/Wind Helper
0.071
316411AF1-147_GEN1
Solar/Wind Helper
0.341
316415AF1-147_GEN2
Solar/Wind Helper
0.341
3141196NOKESVL
Solar/Wind Helper
1.655
3141426STAFORD
Solar/Wind Helper
0.09
316006AB2-029 C
Solar/Wind Helper
0.128
316045AC1-158 PL2
Solar/Wind Helper
1.484
316447AC1-158 HLD
Solar/Wind Helper
1.02
316044AC1-158 PL1
Solar/Wind Helper
0.464
316450AC1-158 RIC
Solar/Wind Helper
0.124
315651AD1-115 GEN
Solar/Wind Helper
0.952
316164AC1-076 GEN
Solar/Wind Helper
0.396
316254AC1-120 GEN1
Solar/Wind Helper
0.379
316170AC1-121 GEN2
Solar/Wind Helper
0.126
944491AF1-114 GEN
Solar/Wind Helper
0.62
957971AF2-091 GEN
Solar/Wind Helper
0.211
966881AG1-559 GEN
Solar/Wind Helper
0.124
3132273ORANGE
Solar/Wind Helper
0.077
3147666LOUISA
Solar/Wind Helper
1.531
3147666LOUISA
Solar/Wind Helper
0.88
316192AB2-158 GEN
Solar/Wind Helper
0.542
316468AD1-105 GEN
Solar/Wind Helper
0.452
316223AC1-118
Solar/Wind Helper
0.122
3141906WESTMOR
Solar/Wind Helper
0.152
966001AG1-469 GEN
Solar/Wind Helper
0.085
316337AD2-073 GEN
Solar/Wind Helper
0.121
238175AF1-290_GEN
Solar/Wind Helper
0.484
316077AC2-138 C
Solar/Wind Helper
0.084
3141813NORNECK
Solar/Wind Helper
0.375
964211AG1-282 GEN
Solar/Wind Helper
0.12
3141726DUNNSVL
Solar/Wind Helper
1.497
316473AC1-191 GEN
Solar/Wind Helper
0.48
966871AG1-558 GEN
Solar/Wind Helper
0.12
316404AE1-155 C
Solar/Wind Helper
0.761
238169AE2-226 GEN1
Solar/Wind Helper
0.297
238170AE2-226 GEN2
Solar/Wind Helper
0.297
316484AD2-074 GEN
Solar/Wind Helper
0.514
316487AF1-042 GEN
Solar/Wind Helper
0.269
961951AG1-038 GEN
Solar/Wind Helper
0.269
3141783LANCAST
Solar/Wind Helper
0.222
3141783LANCAST
Solar/Wind Helper
0.148
964441AG1-307 GEN
Solar/Wind Helper
0.476
316312AB1-027
Solar/Wind Helper
0.149
3142416OLDCHRC
Solar/Wind Helper
0.963
3142416OLDCHRC
Solar/Wind Helper
0.369
3138133OCRAN
Solar/Wind Helper
0.222
3138133OCRAN
Solar/Wind Helper
0.111
3141913WHIT STONE
Solar/Wind Helper
0.37
316314AB2-024 C
Solar/Wind Helper
0.119
316059AD1-063 C
Solar/Wind Helper
0.089
3141766HARMONY
Solar/Wind Helper
0.074
316075AC2-137 C
Solar/Wind Helper
0.119
957601AF2-054 GEN
Solar/Wind Helper
0.118
316156AD2-030 GEN
Solar/Wind Helper
0.117
3141873WAN 176
Solar/Wind Helper
0.074
316203AE2-005 GEN
Solar/Wind Helper
0.77
315662AE1-191 GEN
Solar/Wind Helper
0.474
316280AD1-041 GEN
Solar/Wind Helper
0.296
315666AE1-190 GEN
Solar/Wind Helper
0.119
316441AF1-014 GEN
Solar/Wind Helper
0.118
3143873LANEXA
Solar/Wind Helper
0.221
3142433PROV 92
Solar/Wind Helper
1.473
316233AE1-074 FULL
Solar/Wind Helper
0.118
3143526WINTERP
Solar/Wind Helper
1.913
3143526WINTERP
Solar/Wind Helper
1.913
3142946ENON
Solar/Wind Helper
0.123
3142946ENON
Solar/Wind Helper
0.037
3142543TWELFTH
Solar/Wind Helper
0.035
3143226MDLTHAN
Solar/Wind Helper
0.367
957831AF2-077 GEN
Solar/Wind Helper
0.118
316382AG1-145 C
Solar/Wind Helper
0.117
316159AE1-175 C
Solar/Wind Helper
0.117
316240AF1-291 C
Solar/Wind Helper
0.117
316132AB2-190 GEN1
Solar/Wind Helper
0.438
316458AB2-190 GEN2
Solar/Wind Helper
0.438
315697AD1-025 GEN
Solar/Wind Helper
0.874
316033AB2-134 GEN
Solar/Wind Helper
0.83
316369SG1_INVT
Solar/Wind Helper
0.571
315839AE2-212 C
Solar/Wind Helper
0.116
961611AG1-000B GEN
Solar/Wind Helper
0.517
316236AE1-162_GEN
Solar/Wind Helper
0.116
3145336SMITFLD
Solar/Wind Helper
1.441
3145336SMITFLD
Solar/Wind Helper
0.144
3143316POE
Solar/Wind Helper
1.425
316294AC1-161 GEN
Solar/Wind Helper
1.387
315773AC2-141 GEN
Solar/Wind Helper
1.387
238152AF2-075_GEN
Solar/Wind Helper
0.289
238147AE2-230_GEN1
Solar/Wind Helper
0.404
238148AE2-230_GEN2
Solar/Wind Helper
0.404
238149AF1-291A_GEN
Solar/Wind Helper
0.058
3144536CHRHLND
Solar/Wind Helper
0.054
316381AD1-082 GEN
Solar/Wind Helper
0.392
316083AB2-161 GEN
Solar/Wind Helper
0.288
316375AC2-012 GEN
Solar/Wind Helper
0.68
316036AC1-147 C
Solar/Wind Helper
0.115
23546401DTGZ2-030
Solar/Wind Helper
0.058
3144873MCLAUGH
Solar/Wind Helper
0.009
316313AB2-026
Solar/Wind Helper
0.115
316258AE1-075 C
Solar/Wind Helper
0.104
316405AF2-144 C
Solar/Wind Helper
0.098
316316AC1-027 C
Solar/Wind Helper
0.101
316185AD1-033 GEN
Solar/Wind Helper
0.403
316072AD1-144
Solar/Wind Helper
0.086
3145506HICKORY
Solar/Wind Helper
1.431
3145506HICKORY
Solar/Wind Helper
0.858
3145506HICKORY
Solar/Wind Helper
0.215
316349AD2-085 GEN
Solar/Wind Helper
0.293
316339AD2-160 GEN
Solar/Wind Helper
0.287
316388AE2-253 GEN
Solar/Wind Helper
0.287
315833AF1-017_GEN
Solar/Wind Helper
0.23
316017AA1-139 ULT1
Solar/Wind Helper
0.344
316018AA1-139 ULT2
Solar/Wind Helper
0.344
3137176SLIGO L2192
Solar/Wind Helper
1.42
3146456SLIGO L269
Solar/Wind Helper
0.357
3146456SLIGO L269
Solar/Wind Helper
0.357
319010AE1-072 C
Solar/Wind Helper
0.859
316305AF2-043 C
Solar/Wind Helper
0.115
316246AF1-032 C
Solar/Wind Helper
0.086
3130086AYDLETT
Solar/Wind Helper
1.426
316336AC2-165 C
Solar/Wind Helper
0.572
237061AD1-155 GEN
Solar/Wind Helper
0.429
316320Y1-086
Solar/Wind Helper
0.114
313526AB2-022
Solar/Wind Helper
0.114
3146386ELIZ CT
Solar/Wind Helper
0.355
3146486SUNBURY
Solar/Wind Helper
0.355
3146486SUNBURY
Solar/Wind Helper
0.355
316321Z2-027
Solar/Wind Helper
0.114
3145176PASQUOTANK
Solar/Wind Helper
0.22
3146516WINFALL
Solar/Wind Helper
1.145
3146516WINFALL
Solar/Wind Helper
0.354
3146516WINFALL
Solar/Wind Helper
0.354
3146516WINFALL
Solar/Wind Helper
0.354
3146516WINFALL
Solar/Wind Helper
0.354
3146516WINFALL
Solar/Wind Helper
0.354
3146626S HERTFORD
Solar/Wind Helper
0.353
3146626S HERTFORD
Solar/Wind Helper
0.353
3146626S HERTFORD
Solar/Wind Helper
0.353
316315AB2-025 C
Solar/Wind Helper
0.113
3145273HOLLAND
Solar/Wind Helper
0.264
315742AE1-103 GEN
Solar/Wind Helper
0.225
3130156CHOWAN
Solar/Wind Helper
0.35
3130156CHOWAN
Solar/Wind Helper
0.35
3130156CHOWAN
Solar/Wind Helper
0.35
3146376EDENTON
Solar/Wind Helper
0.35
315614AA2-178 GEN
Solar/Wind Helper
0.446
315816AE2-034 GEN
Solar/Wind Helper
0.334
3145663CRESWEL
Solar/Wind Helper
0.971
3130546PLYMOUTH
Solar/Wind Helper
0.344
3156081AA2-088 GEN
Solar/Wind Helper
0.553
315732AD1-074 GEN1
Solar/Wind Helper
0.829
315733AD1-074 GEN2
Solar/Wind Helper
0.829
315737AD1-076 GEN
Solar/Wind Helper
0.603
315735AD1-075 GEN1
Solar/Wind Helper
0.415
316065AD1-022 GEN
Solar/Wind Helper
0.441
316322AB2-045
Solar/Wind Helper
0.109
3146776BUCKING
Solar/Wind Helper
1.372
3146776BUCKING
Solar/Wind Helper
0.137
3146776BUCKING
Solar/Wind Helper
0.123
3146776BUCKING
Solar/Wind Helper
0.111
316023GEN1_S
Solar/Wind Helper
0.275
316365GEN2_N
Solar/Wind Helper
0.275
3146206CASHIE
Solar/Wind Helper
0.343
3146206CASHIE
Solar/Wind Helper
0.343
3146206CASHIE
Solar/Wind Helper
0.343
3145893MURPHYS
Solar/Wind Helper
1.371
3145893MURPHYS
Solar/Wind Helper
1.096
3145893MURPHYS
Solar/Wind Helper
0.925
316318V4-068
Solar/Wind Helper
0.025
3145893MURPHYS
Solar/Wind Helper
0.617
3145893MURPHYS
Solar/Wind Helper
0.343
3145893MURPHYS
Solar/Wind Helper
0.343
3145893MURPHYS
Solar/Wind Helper
0.274
3138266HYDRAULIC
Solar/Wind Helper
0.015
3138266HYDRAULIC
Solar/Wind Helper
0.01
3146926FARMVIL
Solar/Wind Helper
0.205
3146926FARMVIL
Solar/Wind Helper
0.205
3146173TUNIS
Solar/Wind Helper
0.341
3146173TUNIS
Solar/Wind Helper
0.341
3146173TUNIS
Solar/Wind Helper
0.341
3146173TUNIS
Solar/Wind Helper
0.341
3156021HOLLOMANSOL
Solar/Wind Helper
0.547
316463AE2-346 GEN
Solar/Wind Helper
0.066
316140AB2-099
Solar/Wind Helper
0.027
961941AG1-037 GEN
Solar/Wind Helper
0.027
3145513AHOSKIE
Solar/Wind Helper
0.341
3145513AHOSKIE
Solar/Wind Helper
0.341
946281AF1-292 GEN
Solar/Wind Helper
0.081
966621AG1-532 GEN
Solar/Wind Helper
0.074
3146043SEABORD
Solar/Wind Helper
0.34
3145683EARLEYS
Solar/Wind Helper
0.68
3145683EARLEYS
Solar/Wind Helper
0.34
3145683EARLEYS
Solar/Wind Helper
0.34
3145683EARLEYS
Solar/Wind Helper
0.34
315607AA1-063A GEN
Solar/Wind Helper
0.409
316087AB2-174 GEN
Solar/Wind Helper
0.436
3146263WOODLND
Solar/Wind Helper
0.339
3146263WOODLND
Solar/Wind Helper
0.339
942461AE2-259 GEN
Solar/Wind Helper
0.545
316181AB2-040 GEN
Solar/Wind Helper
0.436
313506AB2-031 GEN
Solar/Wind Helper
0.325
3142666NORTHAMPTON
Solar/Wind Helper
0.338
3142666NORTHAMPTON
Solar/Wind Helper
0.338
3142666NORTHAMPTON
Solar/Wind Helper
0.338
3142666NORTHAMPTON
Solar/Wind Helper
0.338
3142666NORTHAMPTON
Solar/Wind Helper
0.203
3137643SOCKMAN
Solar/Wind Helper
1.351
3132123MT JACKSON
Solar/Wind Helper
1.058
3145963POPLR C
Solar/Wind Helper
0.338
3145963POPLR C
Solar/Wind Helper
0.338
3147043LAWRENC
Solar/Wind Helper
0.203
316426AA2-053 GEN
Solar/Wind Helper
0.407
316190AA2-174 GEN
Solar/Wind Helper
0.027
316011AB1-132 GEN
Solar/Wind Helper
8.105
316317KELFORD C
Solar/Wind Helper
0.125
3145823KELFORD
Solar/Wind Helper
0.338
3145823KELFORD
Solar/Wind Helper
0.338
3145593CAROLNA
Solar/Wind Helper
0.337
3145593CAROLNA
Solar/Wind Helper
0.337
315821AE2-092 GEN
Solar/Wind Helper
0.748
3147133PAMPLIN
Solar/Wind Helper
1.059
3147133PAMPLIN
Solar/Wind Helper
0.337
3147133PAMPLIN
Solar/Wind Helper
0.27
316174AB2-169 GEN
Solar/Wind Helper
0.4
3145783HORNRTN
Solar/Wind Helper
0.336
316478AD1-087 GEN
Solar/Wind Helper
0.347
316486AD2-202 GEN
Solar/Wind Helper
0.102
3145796HORNRTN
Solar/Wind Helper
1.343
3145796HORNRTN
Solar/Wind Helper
1.108
3145796HORNRTN
Solar/Wind Helper
1.075
3145796HORNRTN
Solar/Wind Helper
1.007
3145796HORNRTN
Solar/Wind Helper
0.336
3145796HORNRTN
Solar/Wind Helper
0.336
3145796HORNRTN
Solar/Wind Helper
0.134
3146033SCOT NK
Solar/Wind Helper
1.341
316034AC1-036 C
Solar/Wind Helper
0.074
3144303KENBRDG
Solar/Wind Helper
0.268
315785AD2-033 C
Solar/Wind Helper
0.698
3147983MERCK5
Solar/Wind Helper
0.133
316210AC1-098 GEN
Solar/Wind Helper
0.482
316212AC1-099_GEN
Solar/Wind Helper
0.268
316129AC1-054 GEN
Solar/Wind Helper
0.348
3145933PARMELE
Solar/Wind Helper
0.665
3145933PARMELE
Solar/Wind Helper
0.333
3145933PARMELE
Solar/Wind Helper
0.333
23777901MDS_W4-102
Solar/Wind Helper
0.107
316274AC1-208 GEN
Solar/Wind Helper
0.427
235020AA1-095 C
Solar/Wind Helper
0.022
316499AE2-029_GEN
Solar/Wind Helper
0.267
316131AB2-060 GEN
Solar/Wind Helper
0.427
313527AB2-043 GEN
Solar/Wind Helper
0.267
316239AB2-077_GEN
Solar/Wind Helper
0.107
316238AB2-078_GEN
Solar/Wind Helper
0.107
316237AB2-079_GEN
Solar/Wind Helper
0.107
3148013FISHERV
Solar/Wind Helper
0.331
3148133STUARTS
Solar/Wind Helper
0.199
3148013FISHERV
Solar/Wind Helper
0.19
316005AA1-067
Solar/Wind Helper
0.08
3145746EVERETS
Solar/Wind Helper
1.313
3145746EVERETS
Solar/Wind Helper
0.33
3145746EVERETS
Solar/Wind Helper
0.33
3145746EVERETS
Solar/Wind Helper
0.33
3145746EVERETS
Solar/Wind Helper
0.33
3145746EVERETS
Solar/Wind Helper
0.33
3145746EVERETS
Solar/Wind Helper
0.33
3145746EVERETS
Solar/Wind Helper
0.33
315687AD1-152 GEN
Solar/Wind Helper
0.424
315722AD1-056 GEN
Solar/Wind Helper
0.318
315724AD1-057 GEN
Solar/Wind Helper
0.175
316327AA2-057 GEN
Solar/Wind Helper
0.396
316494AC1-189 GEN
Solar/Wind Helper
0.422
316420AA1-050 GEN
Solar/Wind Helper
0.421
316319Z2-044 C
Solar/Wind Helper
0.063
3146233WITAKRS
Solar/Wind Helper
1.3
3146233WITAKRS
Solar/Wind Helper
0.222
961671AG1-007 GEN
Solar/Wind Helper
0.049
3145573BETHELC
Solar/Wind Helper
0.326
3145573BETHELC
Solar/Wind Helper
0.326
3146073TAR RVR
Solar/Wind Helper
0.326
3146083TARBORO
Solar/Wind Helper
0.326
3146083TARBORO
Solar/Wind Helper
0.326
3138543CONSLDL
Solar/Wind Helper
0.215
270494AE1-108_GEN
Solar/Wind Helper
0.782
3146843MT LREL
Solar/Wind Helper
0.325
3146843MT LREL
Solar/Wind Helper
0.325
316359AB2-059 GEN
Solar/Wind Helper
0.521
316049AB1-081 GEN
Solar/Wind Helper
0.417
3145543BTLEBRO
Solar/Wind Helper
0.324
3145543BTLEBRO
Solar/Wind Helper
0.324
3145543BTLEBRO
Solar/Wind Helper
0.324
3145543BTLEBRO
Solar/Wind Helper
0.26
316097T157 G90
Solar/Wind Helper
0.213
316095T157 G97
Solar/Wind Helper
0.213
316118AC1-105 GEN
Solar/Wind Helper
0.264
316248AF1-058 C
Solar/Wind Helper
0.103
3147173SINAI
Solar/Wind Helper
0.32
3147243WELCO
Solar/Wind Helper
0.2
3148463FAIRFLD
Solar/Wind Helper
0.317
316003AC1-222 GEN
Solar/Wind Helper
0.33
23583801GRNGAP
Solar/Wind Helper
0.529
G-007ALTFEXP_G-007A->PJM
CMTX
41.238
HAMLETPJM->LTFIMP_HAMLET
CLTF
5.375
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.101
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
18.191
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
3.81
BlueGrassPJM->LTFIMP_BlueG
CLTF
11.882
CBM NorthLTFEXP_CBM-N->PJM
CBM
62.813
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
108.897

Details for CNASTONE-BRIGHTON 500.0 kV Ckt 1 line l/o AP_P2-3_PE-500-019E_SRT-W


Base Case Flowgate

Area:PJM
Facility Description:
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-500-019E_SRT-W
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:136.75 %
Rating:3507.0 MVA
Rating Type:B
MVA to Mitigate:4795.71
MW Contribution:0.37
Bus #Bus NameTypeMW Contribution
972281AH1-725 GEN
50/50
134.755
200202DELTA2 ST
50/50
5.064
200200DELTA2 CT1
50/50
2.835
200201DELTA2 CT2
50/50
2.835
200195DELTA ST
50/50
2.506
200192DELTA CT1
50/50
1.503
200193DELTA CT2
50/50
1.503
200194DELTA CT3
50/50
1.503
200034PCHBTM 2
50/50
99.305
200035PCHBTM 3
50/50
16.356
200203Y1-065-STG
50/50
5.759
200204Y1-065-CTG1
50/50
3.626
200205Y1-065-CTG2
50/50
3.626
200052ROCKSP 1
50/50
43.025
200053ROCKSP 2
50/50
43.025
200054ROCKSP 3
50/50
42.588
200055ROCKSP 4
50/50
42.588
233987AB2-037 GEN
Solar/Wind Harmer
0
971149AH1-027 GEN
Solar/Wind Harmer
0.246
234033AF1-007_GEN
Solar/Wind Harmer
20.571
233972AC1-094 C
Solar/Wind Harmer
-0.001
970545AG2-347 GEN
Solar/Wind Harmer
84.736
972133AH1-634 GEN
Solar/Wind Harmer
12.839
970695AG2-447 GEN
Solar/Wind Harmer
0.197
233923SMA
Solar/Wind Harmer
-0.001
233998TM1NIN_3.36
Solar/Wind Harmer
-0.001
233997TMININ_4.2
Solar/Wind Harmer
-0.001
233996TM1833_GEN
Solar/Wind Harmer
-0.001
972069AH1-584 GEN
Solar/Wind Harmer
0.492
972071AH1-585 GEN
Solar/Wind Harmer
0.492
972073AH1-586 GEN
Solar/Wind Harmer
8.85
971747AH1-380 GEN
Solar/Wind Harmer
0.197
233990AG1-397 GEN
Solar/Wind Harmer
0
233940AF2-379 C
Solar/Wind Harmer
-0.001
233990AG1-397 GEN
Solar/Wind Harmer
1.573
234015AF2-250 C
Solar/Wind Harmer
0
971195AH1-057 GEN
Solar/Wind Harmer
0.071
972177AH1-672 GEN
Solar/Wind Harmer
0.737
960671AF2-358 GEN
Solar/Wind Harmer
0.983
965821AG1-450 GEN
Solar/Wind Harmer
4.915
232426Y1-080 FULL
Solar/Wind Harmer
0
970277AG2-181 GEN
Solar/Wind Harmer
0.275
233946AB2-136 GEN
Solar/Wind Harmer
-0.001
233964AF2-378 GEN
Solar/Wind Harmer
0
234041AC1-190 GEN
Solar/Wind Harmer
0.491
233984AB2-036 GEN
Solar/Wind Harmer
0.902
233968AD2-076_GEN
Solar/Wind Harmer
0.479
234014AF1-036_GEN
Solar/Wind Harmer
0.196
970597AG2-380 GEN
Solar/Wind Harmer
3.913
234012AE2-112_GEN
Solar/Wind Harmer
0.166
971983AH1-536 GEN
Solar/Wind Harmer
0.408
970453AG2-297 GEN
Solar/Wind Harmer
0.177
971553AH1-274 GEN
Solar/Wind Harmer
0.156
945431AF1-208 GEN
Solar/Wind Harmer
0.419
970997AG2-616 GEN
Solar/Wind Harmer
0.465
972141AH1-641 GEN
Solar/Wind Harmer
0.139
230430AE1-229_GEN
Solar/Wind Harmer
-0.001
228351V2-046C
Solar/Wind Harmer
-0.001
230433AD2-135 GEN
Solar/Wind Harmer
0
230422AE1-104_GEN1
Solar/Wind Harmer
38.489
230425AE1-104_GEN2
Solar/Wind Harmer
38.489
971011AG2-627 GEN
Solar/Wind Harmer
0.371
971535AH1-265 GEN
Solar/Wind Harmer
0.272
230407AD2-065 C
Solar/Wind Harmer
0
228754AB1-001 C
Solar/Wind Harmer
-0.001
219137THOSOLAR C
Solar/Wind Harmer
0.001
219623KINSLEYBEA C
Solar/Wind Harmer
-0.001
219258KINSLEYDEP C
Solar/Wind Harmer
0
219766PARADISE C
Solar/Wind Harmer
-0.001
218660EHAMPSOLAR C
Solar/Wind Harmer
-0.001
219907AC1-030 C
Solar/Wind Harmer
-0.001
219236SOUTHERNHQ C
Solar/Wind Harmer
-0.001
219906AC1-017 C
Solar/Wind Harmer
-0.001
219615MILLCREEK C
Solar/Wind Harmer
-0.001
214067T20SOLAR
Solar/Wind Harmer
-0.001
207522AF2-254 C
Solar/Wind Harmer
0.089
207500AE2-000G1
Solar/Wind Harmer
34.971
207497AE2-000G2
Solar/Wind Harmer
34.971
207507AE2-000G3
Solar/Wind Harmer
34.971
207487AE2-000G4
Solar/Wind Harmer
34.971
970025AG2-016 GEN
Solar/Wind Harmer
0.176
971189AH1-054 GEN
Solar/Wind Harmer
0.073
971667AH1-334 GEN
Solar/Wind Harmer
0.171
219727YARDVSOLFA C
Solar/Wind Harmer
0.001
219276PARKLANDSO C
Solar/Wind Harmer
0
219817TRENTONSOL C
Solar/Wind Harmer
0.001
219620RIDERU C
Solar/Wind Harmer
-0.001
20714328BYD_X4-031
Solar/Wind Harmer
0.018
20714428HOW_X1-037
Solar/Wind Harmer
-0.001
219918AC2-009 C
Solar/Wind Harmer
0
20720628TIN_W1-124
Solar/Wind Harmer
-0.001
20742028HF_AC1-207
Solar/Wind Harmer
-0.001
971521AH1-258 GEN
Solar/Wind Harmer
0.168
967451AG2-055 C O1
Solar/Wind Harmer
192.126
219612MATRIX C
Solar/Wind Harmer
0
218438BLK ROCK C
Solar/Wind Harmer
0
218526CNTRALGAS2 C
Solar/Wind Harmer
0.001
218524CNTRALGAS1 C
Solar/Wind Harmer
0.001
218428ETC SOLAR C
Solar/Wind Harmer
0
217213AMBOY SO C
Solar/Wind Harmer
-0.001
219249CENTRALDIV C
Solar/Wind Harmer
0
20673828FLE_V3-070
Solar/Wind Harmer
0.062
20675428EAM_W2-061
Solar/Wind Harmer
0
218449LINSOLAR C
Solar/Wind Harmer
0.001
217081WEATEXAS C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
217206BARNGR HS C
Solar/Wind Harmer
0
217208PARK ELE C
Solar/Wind Harmer
0
207439AE1-081 C O1
Solar/Wind Harmer
0
20676328BVR_Y1-020
Solar/Wind Harmer
0
20674628WNG_W3-110
Solar/Wind Harmer
-0.001
207511W3-106 GEN
Solar/Wind Harmer
0.041
971007AG2-625 GEN
Solar/Wind Harmer
0.16
971009AG2-626 GEN
Solar/Wind Harmer
0.102
971519AH1-257 GEN
Solar/Wind Harmer
0.157
207437AD2-070 GEN
Solar/Wind Harmer
-0.001
966181AG1-487 GEN
Solar/Wind Harmer
0
966181AG1-487 GEN
Solar/Wind Harmer
3.093
966111AG1-480 GEN
Solar/Wind Harmer
0
966111AG1-480 GEN
Solar/Wind Harmer
2.723
970095AG2-074 GEN
Solar/Wind Harmer
0.284
208972BECR K09
Solar/Wind Harmer
2.091
208862AG1-362 C
Solar/Wind Harmer
0.037
209027LOR2_Q27
Solar/Wind Harmer
8.37
212266LOR1
Solar/Wind Harmer
0.156
970237AG2-161 GEN
Solar/Wind Harmer
0.184
961541AF2-445A GEN
Solar/Wind Harmer
0.146
209029WAYMART-WD
Solar/Wind Harmer
5.568
209142AF1-226 GEN
Solar/Wind Harmer
0.256
209093AE2-110 GEN
Solar/Wind Harmer
0.146
209120AE2-241 GEN
Solar/Wind Harmer
0.146
209045AE2-271 GEN
Solar/Wind Harmer
0.739
209059AE2-084 GEN
Solar/Wind Harmer
0.144
970665AG2-430 GEN
Solar/Wind Harmer
0.43
209130AF1-271A GEN
Solar/Wind Harmer
0.122
208835TUHI V3-051
Solar/Wind Harmer
0.06
208835TUHI V3-051
Solar/Wind Harmer
0.06
205967AE2-211_GEN
Solar/Wind Harmer
0.454
960921AF2-383 GEN
Solar/Wind Harmer
1.606
970679AG2-439 GEN
Solar/Wind Harmer
0.053
226929AD2-058 GEN
Solar/Wind Helper
0.04
227287AC2-120 GEN
Solar/Wind Helper
0.197
226910AB2-157 C
Solar/Wind Helper
0.018
3138216PACIFIC
Solar/Wind Helper
0.071
316411AF1-147_GEN1
Solar/Wind Helper
0.342
316415AF1-147_GEN2
Solar/Wind Helper
0.342
3141196NOKESVL
Solar/Wind Helper
1.66
3141426STAFORD
Solar/Wind Helper
0.09
316006AB2-029 C
Solar/Wind Helper
0.128
316045AC1-158 PL2
Solar/Wind Helper
1.488
316447AC1-158 HLD
Solar/Wind Helper
1.023
316044AC1-158 PL1
Solar/Wind Helper
0.465
316450AC1-158 RIC
Solar/Wind Helper
0.124
315651AD1-115 GEN
Solar/Wind Helper
0.955
316164AC1-076 GEN
Solar/Wind Helper
0.397
316254AC1-120 GEN1
Solar/Wind Helper
0.38
316170AC1-121 GEN2
Solar/Wind Helper
0.127
944491AF1-114 GEN
Solar/Wind Helper
0.622
957971AF2-091 GEN
Solar/Wind Helper
0.211
966881AG1-559 GEN
Solar/Wind Helper
0.124
3132273ORANGE
Solar/Wind Helper
0.077
3147666LOUISA
Solar/Wind Helper
1.535
3147666LOUISA
Solar/Wind Helper
0.883
316192AB2-158 GEN
Solar/Wind Helper
0.543
316468AD1-105 GEN
Solar/Wind Helper
0.453
316223AC1-118
Solar/Wind Helper
0.122
3141906WESTMOR
Solar/Wind Helper
0.152
966001AG1-469 GEN
Solar/Wind Helper
0.086
316337AD2-073 GEN
Solar/Wind Helper
0.122
316077AC2-138 C
Solar/Wind Helper
0.084
3141813NORNECK
Solar/Wind Helper
0.376
964211AG1-282 GEN
Solar/Wind Helper
0.121
3141726DUNNSVL
Solar/Wind Helper
1.5
316473AC1-191 GEN
Solar/Wind Helper
0.481
966871AG1-558 GEN
Solar/Wind Helper
0.12
316404AE1-155 C
Solar/Wind Helper
0.763
238175AF1-290_GEN
Solar/Wind Helper
0.48
316484AD2-074 GEN
Solar/Wind Helper
0.515
316487AF1-042 GEN
Solar/Wind Helper
0.27
961951AG1-038 GEN
Solar/Wind Helper
0.27
3141783LANCAST
Solar/Wind Helper
0.223
3141783LANCAST
Solar/Wind Helper
0.149
316312AB1-027
Solar/Wind Helper
0.149
3142416OLDCHRC
Solar/Wind Helper
0.966
3142416OLDCHRC
Solar/Wind Helper
0.37
3138133OCRAN
Solar/Wind Helper
0.223
3138133OCRAN
Solar/Wind Helper
0.111
3141913WHIT STONE
Solar/Wind Helper
0.371
316314AB2-024 C
Solar/Wind Helper
0.119
316059AD1-063 C
Solar/Wind Helper
0.089
3141766HARMONY
Solar/Wind Helper
0.074
315662AE1-191 GEN
Solar/Wind Helper
0.475
316280AD1-041 GEN
Solar/Wind Helper
0.297
316075AC2-137 C
Solar/Wind Helper
0.119
315666AE1-190 GEN
Solar/Wind Helper
0.119
957601AF2-054 GEN
Solar/Wind Helper
0.118
316156AD2-030 GEN
Solar/Wind Helper
0.118
3141873WAN 176
Solar/Wind Helper
0.074
316203AE2-005 GEN
Solar/Wind Helper
0.772
316441AF1-014 GEN
Solar/Wind Helper
0.118
3143873LANEXA
Solar/Wind Helper
0.222
238169AE2-226 GEN1
Solar/Wind Helper
0.294
238170AE2-226 GEN2
Solar/Wind Helper
0.294
3142433PROV 92
Solar/Wind Helper
1.477
316233AE1-074 FULL
Solar/Wind Helper
0.118
3143526WINTERP
Solar/Wind Helper
1.917
3143526WINTERP
Solar/Wind Helper
1.917
3142946ENON
Solar/Wind Helper
0.123
3142946ENON
Solar/Wind Helper
0.037
3142543TWELFTH
Solar/Wind Helper
0.035
3143226MDLTHAN
Solar/Wind Helper
0.368
964441AG1-307 GEN
Solar/Wind Helper
0.473
957831AF2-077 GEN
Solar/Wind Helper
0.118
316382AG1-145 C
Solar/Wind Helper
0.118
316159AE1-175 C
Solar/Wind Helper
0.118
316240AF1-291 C
Solar/Wind Helper
0.117
316132AB2-190 GEN1
Solar/Wind Helper
0.439
316458AB2-190 GEN2
Solar/Wind Helper
0.439
315697AD1-025 GEN
Solar/Wind Helper
0.876
316033AB2-134 GEN
Solar/Wind Helper
0.832
316369SG1_INVT
Solar/Wind Helper
0.572
315839AE2-212 C
Solar/Wind Helper
0.117
961611AG1-000B GEN
Solar/Wind Helper
0.519
316236AE1-162_GEN
Solar/Wind Helper
0.116
3145336SMITFLD
Solar/Wind Helper
1.445
3145336SMITFLD
Solar/Wind Helper
0.144
3143316POE
Solar/Wind Helper
1.429
316294AC1-161 GEN
Solar/Wind Helper
1.391
315773AC2-141 GEN
Solar/Wind Helper
1.391
238152AF2-075_GEN
Solar/Wind Helper
0.289
238147AE2-230_GEN1
Solar/Wind Helper
0.405
238148AE2-230_GEN2
Solar/Wind Helper
0.405
238149AF1-291A_GEN
Solar/Wind Helper
0.058
316381AD1-082 GEN
Solar/Wind Helper
0.393
316083AB2-161 GEN
Solar/Wind Helper
0.289
3144536CHRHLND
Solar/Wind Helper
0.054
316375AC2-012 GEN
Solar/Wind Helper
0.681
316036AC1-147 C
Solar/Wind Helper
0.116
3144873MCLAUGH
Solar/Wind Helper
0.009
316313AB2-026
Solar/Wind Helper
0.115
316258AE1-075 C
Solar/Wind Helper
0.104
316405AF2-144 C
Solar/Wind Helper
0.098
316316AC1-027 C
Solar/Wind Helper
0.102
316185AD1-033 GEN
Solar/Wind Helper
0.404
316072AD1-144
Solar/Wind Helper
0.086
23546401DTGZ2-030
Solar/Wind Helper
0.058
3145506HICKORY
Solar/Wind Helper
1.434
3145506HICKORY
Solar/Wind Helper
0.861
3145506HICKORY
Solar/Wind Helper
0.215
316349AD2-085 GEN
Solar/Wind Helper
0.293
315833AF1-017_GEN
Solar/Wind Helper
0.23
316339AD2-160 GEN
Solar/Wind Helper
0.288
316388AE2-253 GEN
Solar/Wind Helper
0.288
316017AA1-139 ULT1
Solar/Wind Helper
0.345
316018AA1-139 ULT2
Solar/Wind Helper
0.345
3137176SLIGO L2192
Solar/Wind Helper
1.424
3146456SLIGO L269
Solar/Wind Helper
0.358
3146456SLIGO L269
Solar/Wind Helper
0.358
319010AE1-072 C
Solar/Wind Helper
0.862
316305AF2-043 C
Solar/Wind Helper
0.115
316246AF1-032 C
Solar/Wind Helper
0.086
3130086AYDLETT
Solar/Wind Helper
1.43
316336AC2-165 C
Solar/Wind Helper
0.573
237061AD1-155 GEN
Solar/Wind Helper
0.43
316320Y1-086
Solar/Wind Helper
0.114
313526AB2-022
Solar/Wind Helper
0.114
3146386ELIZ CT
Solar/Wind Helper
0.356
3146486SUNBURY
Solar/Wind Helper
0.356
3146486SUNBURY
Solar/Wind Helper
0.356
316321Z2-027
Solar/Wind Helper
0.114
3145176PASQUOTANK
Solar/Wind Helper
0.221
3146516WINFALL
Solar/Wind Helper
1.148
3146516WINFALL
Solar/Wind Helper
0.354
3146516WINFALL
Solar/Wind Helper
0.354
3146516WINFALL
Solar/Wind Helper
0.354
3146516WINFALL
Solar/Wind Helper
0.354
3146516WINFALL
Solar/Wind Helper
0.354
3146626S HERTFORD
Solar/Wind Helper
0.354
3146626S HERTFORD
Solar/Wind Helper
0.354
3146626S HERTFORD
Solar/Wind Helper
0.354
316315AB2-025 C
Solar/Wind Helper
0.114
3145273HOLLAND
Solar/Wind Helper
0.265
315742AE1-103 GEN
Solar/Wind Helper
0.226
3146376EDENTON
Solar/Wind Helper
0.351
3130156CHOWAN
Solar/Wind Helper
0.351
3130156CHOWAN
Solar/Wind Helper
0.351
3130156CHOWAN
Solar/Wind Helper
0.351
315614AA2-178 GEN
Solar/Wind Helper
0.447
315816AE2-034 GEN
Solar/Wind Helper
0.335
3145663CRESWEL
Solar/Wind Helper
0.973
3130546PLYMOUTH
Solar/Wind Helper
0.345
3156081AA2-088 GEN
Solar/Wind Helper
0.555
315732AD1-074 GEN1
Solar/Wind Helper
0.831
315733AD1-074 GEN2
Solar/Wind Helper
0.831
315737AD1-076 GEN
Solar/Wind Helper
0.604
315735AD1-075 GEN1
Solar/Wind Helper
0.416
316065AD1-022 GEN
Solar/Wind Helper
0.442
316322AB2-045
Solar/Wind Helper
0.109
3146776BUCKING
Solar/Wind Helper
1.376
3146776BUCKING
Solar/Wind Helper
0.138
3146776BUCKING
Solar/Wind Helper
0.124
3146776BUCKING
Solar/Wind Helper
0.111
316023GEN1_S
Solar/Wind Helper
0.276
316365GEN2_N
Solar/Wind Helper
0.276
3146206CASHIE
Solar/Wind Helper
0.344
3146206CASHIE
Solar/Wind Helper
0.344
3146206CASHIE
Solar/Wind Helper
0.344
3145893MURPHYS
Solar/Wind Helper
1.374
3145893MURPHYS
Solar/Wind Helper
1.099
3145893MURPHYS
Solar/Wind Helper
0.928
316318V4-068
Solar/Wind Helper
0.025
3145893MURPHYS
Solar/Wind Helper
0.618
3145893MURPHYS
Solar/Wind Helper
0.344
3145893MURPHYS
Solar/Wind Helper
0.344
3145893MURPHYS
Solar/Wind Helper
0.275
3138266HYDRAULIC
Solar/Wind Helper
0.015
3138266HYDRAULIC
Solar/Wind Helper
0.01
3146926FARMVIL
Solar/Wind Helper
0.205
3146926FARMVIL
Solar/Wind Helper
0.205
3146173TUNIS
Solar/Wind Helper
0.342
3146173TUNIS
Solar/Wind Helper
0.342
3146173TUNIS
Solar/Wind Helper
0.342
3146173TUNIS
Solar/Wind Helper
0.342
3156021HOLLOMANSOL
Solar/Wind Helper
0.549
316463AE2-346 GEN
Solar/Wind Helper
0.066
316140AB2-099
Solar/Wind Helper
0.027
961941AG1-037 GEN
Solar/Wind Helper
0.027
3145513AHOSKIE
Solar/Wind Helper
0.342
3145513AHOSKIE
Solar/Wind Helper
0.342
946281AF1-292 GEN
Solar/Wind Helper
0.082
966621AG1-532 GEN
Solar/Wind Helper
0.074
3146043SEABORD
Solar/Wind Helper
0.341
3145683EARLEYS
Solar/Wind Helper
0.682
3145683EARLEYS
Solar/Wind Helper
0.341
3145683EARLEYS
Solar/Wind Helper
0.341
3145683EARLEYS
Solar/Wind Helper
0.341
315607AA1-063A GEN
Solar/Wind Helper
0.411
316087AB2-174 GEN
Solar/Wind Helper
0.437
3146263WOODLND
Solar/Wind Helper
0.34
3146263WOODLND
Solar/Wind Helper
0.34
942461AE2-259 GEN
Solar/Wind Helper
0.547
316181AB2-040 GEN
Solar/Wind Helper
0.437
313506AB2-031 GEN
Solar/Wind Helper
0.325
3142666NORTHAMPTON
Solar/Wind Helper
0.339
3142666NORTHAMPTON
Solar/Wind Helper
0.339
3142666NORTHAMPTON
Solar/Wind Helper
0.339
3142666NORTHAMPTON
Solar/Wind Helper
0.339
3142666NORTHAMPTON
Solar/Wind Helper
0.203
3137643SOCKMAN
Solar/Wind Helper
1.354
3132123MT JACKSON
Solar/Wind Helper
1.061
3145963POPLR C
Solar/Wind Helper
0.339
3145963POPLR C
Solar/Wind Helper
0.339
3147043LAWRENC
Solar/Wind Helper
0.203
316426AA2-053 GEN
Solar/Wind Helper
0.408
316190AA2-174 GEN
Solar/Wind Helper
0.027
316011AB1-132 GEN
Solar/Wind Helper
8.127
316317KELFORD C
Solar/Wind Helper
0.126
3145823KELFORD
Solar/Wind Helper
0.338
3145823KELFORD
Solar/Wind Helper
0.338
315821AE2-092 GEN
Solar/Wind Helper
0.75
3145593CAROLNA
Solar/Wind Helper
0.338
3145593CAROLNA
Solar/Wind Helper
0.338
3147133PAMPLIN
Solar/Wind Helper
1.062
3147133PAMPLIN
Solar/Wind Helper
0.338
3147133PAMPLIN
Solar/Wind Helper
0.271
316174AB2-169 GEN
Solar/Wind Helper
0.401
3145783HORNRTN
Solar/Wind Helper
0.337
316478AD1-087 GEN
Solar/Wind Helper
0.348
316486AD2-202 GEN
Solar/Wind Helper
0.102
3145796HORNRTN
Solar/Wind Helper
1.347
3145796HORNRTN
Solar/Wind Helper
1.111
3145796HORNRTN
Solar/Wind Helper
1.077
3145796HORNRTN
Solar/Wind Helper
1.01
3145796HORNRTN
Solar/Wind Helper
0.337
3145796HORNRTN
Solar/Wind Helper
0.337
3145796HORNRTN
Solar/Wind Helper
0.135
3146033SCOT NK
Solar/Wind Helper
1.344
316034AC1-036 C
Solar/Wind Helper
0.074
3144303KENBRDG
Solar/Wind Helper
0.268
315785AD2-033 C
Solar/Wind Helper
0.699
3147983MERCK5
Solar/Wind Helper
0.134
316210AC1-098 GEN
Solar/Wind Helper
0.483
316212AC1-099_GEN
Solar/Wind Helper
0.268
316129AC1-054 GEN
Solar/Wind Helper
0.349
3145933PARMELE
Solar/Wind Helper
0.667
3145933PARMELE
Solar/Wind Helper
0.333
3145933PARMELE
Solar/Wind Helper
0.333
316274AC1-208 GEN
Solar/Wind Helper
0.428
316499AE2-029_GEN
Solar/Wind Helper
0.268
316131AB2-060 GEN
Solar/Wind Helper
0.428
313527AB2-043 GEN
Solar/Wind Helper
0.267
316239AB2-077_GEN
Solar/Wind Helper
0.107
316238AB2-078_GEN
Solar/Wind Helper
0.107
316237AB2-079_GEN
Solar/Wind Helper
0.107
3148013FISHERV
Solar/Wind Helper
0.332
3148133STUARTS
Solar/Wind Helper
0.199
3148013FISHERV
Solar/Wind Helper
0.191
316005AA1-067
Solar/Wind Helper
0.08
3145746EVERETS
Solar/Wind Helper
1.317
3145746EVERETS
Solar/Wind Helper
0.331
3145746EVERETS
Solar/Wind Helper
0.331
3145746EVERETS
Solar/Wind Helper
0.331
3145746EVERETS
Solar/Wind Helper
0.331
3145746EVERETS
Solar/Wind Helper
0.331
3145746EVERETS
Solar/Wind Helper
0.331
3145746EVERETS
Solar/Wind Helper
0.331
315687AD1-152 GEN
Solar/Wind Helper
0.425
315722AD1-056 GEN
Solar/Wind Helper
0.318
315724AD1-057 GEN
Solar/Wind Helper
0.175
316327AA2-057 GEN
Solar/Wind Helper
0.397
316494AC1-189 GEN
Solar/Wind Helper
0.423
316420AA1-050 GEN
Solar/Wind Helper
0.422
316319Z2-044 C
Solar/Wind Helper
0.063
3146233WITAKRS
Solar/Wind Helper
1.304
3146233WITAKRS
Solar/Wind Helper
0.223
961671AG1-007 GEN
Solar/Wind Helper
0.049
3145573BETHELC
Solar/Wind Helper
0.327
3145573BETHELC
Solar/Wind Helper
0.327
3146073TAR RVR
Solar/Wind Helper
0.327
3146083TARBORO
Solar/Wind Helper
0.327
3146083TARBORO
Solar/Wind Helper
0.327
3138543CONSLDL
Solar/Wind Helper
0.216
235020AA1-095 C
Solar/Wind Helper
0.022
23777901MDS_W4-102
Solar/Wind Helper
0.105
270494AE1-108_GEN
Solar/Wind Helper
0.784
3146843MT LREL
Solar/Wind Helper
0.326
3146843MT LREL
Solar/Wind Helper
0.326
3145543BTLEBRO
Solar/Wind Helper
0.325
3145543BTLEBRO
Solar/Wind Helper
0.325
3145543BTLEBRO
Solar/Wind Helper
0.325
3145543BTLEBRO
Solar/Wind Helper
0.26
316359AB2-059 GEN
Solar/Wind Helper
0.523
316049AB1-081 GEN
Solar/Wind Helper
0.418
316097T157 G90
Solar/Wind Helper
0.214
316095T157 G97
Solar/Wind Helper
0.214
316118AC1-105 GEN
Solar/Wind Helper
0.265
316248AF1-058 C
Solar/Wind Helper
0.103
3147173SINAI
Solar/Wind Helper
0.321
3147243WELCO
Solar/Wind Helper
0.201
3148463FAIRFLD
Solar/Wind Helper
0.318
316003AC1-222 GEN
Solar/Wind Helper
0.331
23583801GRNGAP
Solar/Wind Helper
0.531
G-007ALTFEXP_G-007A->PJM
CMTX
41.347
HAMLETPJM->LTFIMP_HAMLET
CLTF
5.391
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.111
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
18.255
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
3.824
BlueGrassPJM->LTFIMP_BlueG
CLTF
11.925
CBM NorthLTFEXP_CBM-N->PJM
CBM
62.988
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
109.192

Details for CNASTONE-BRIGHTON 500.0 kV Ckt 1 line l/o AP_P2-3_PE-500-019B_SRT-A


Base Case Flowgate

Area:PJM
Facility Description:
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-500-019B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:119.38 %
Rating:3507.0 MVA
Rating Type:B
MVA to Mitigate:4186.65
MW Contribution:0.3
Bus #Bus NameTypeMW Contribution
972281AH1-725 GEN
50/50
111.84
200202DELTA2 ST
50/50
4.17
200200DELTA2 CT1
50/50
2.335
200201DELTA2 CT2
50/50
2.335
200195DELTA ST
50/50
2.063
200192DELTA CT1
50/50
1.238
200193DELTA CT2
50/50
1.238
200194DELTA CT3
50/50
1.238
200034PCHBTM 2
50/50
81.771
200035PCHBTM 3
50/50
13.463
200203Y1-065-STG
50/50
4.736
200204Y1-065-CTG1
50/50
2.982
200205Y1-065-CTG2
50/50
2.982
200052ROCKSP 1
50/50
35.381
200053ROCKSP 2
50/50
35.381
200054ROCKSP 3
50/50
35.022
200055ROCKSP 4
50/50
35.022
971149AH1-027 GEN
Solar/Wind Harmer
0.201
233987AB2-037 GEN
Solar/Wind Harmer
0
233972AC1-094 C
Solar/Wind Harmer
-0.001
970695AG2-447 GEN
Solar/Wind Harmer
0.161
234033AF1-007_GEN
Solar/Wind Harmer
16.781
970545AG2-347 GEN
Solar/Wind Harmer
69.125
972133AH1-634 GEN
Solar/Wind Harmer
10.474
233923SMA
Solar/Wind Harmer
-0.001
233998TM1NIN_3.36
Solar/Wind Harmer
-0.001
233997TMININ_4.2
Solar/Wind Harmer
-0.001
233996TM1833_GEN
Solar/Wind Harmer
-0.001
972069AH1-584 GEN
Solar/Wind Harmer
0.401
972071AH1-585 GEN
Solar/Wind Harmer
0.401
972073AH1-586 GEN
Solar/Wind Harmer
7.219
971747AH1-380 GEN
Solar/Wind Harmer
0.16
233990AG1-397 GEN
Solar/Wind Harmer
0
233940AF2-379 C
Solar/Wind Harmer
-0.001
972177AH1-672 GEN
Solar/Wind Harmer
0.602
233990AG1-397 GEN
Solar/Wind Harmer
1.283
234015AF2-250 C
Solar/Wind Harmer
0
971195AH1-057 GEN
Solar/Wind Harmer
0.058
960671AF2-358 GEN
Solar/Wind Harmer
0.802
965821AG1-450 GEN
Solar/Wind Harmer
4.008
232426Y1-080 FULL
Solar/Wind Harmer
0
970277AG2-181 GEN
Solar/Wind Harmer
0.224
233946AB2-136 GEN
Solar/Wind Harmer
-0.001
233964AF2-378 GEN
Solar/Wind Harmer
0
234041AC1-190 GEN
Solar/Wind Harmer
0.401
233984AB2-036 GEN
Solar/Wind Harmer
0.735
233968AD2-076_GEN
Solar/Wind Harmer
0.39
234014AF1-036_GEN
Solar/Wind Harmer
0.159
970597AG2-380 GEN
Solar/Wind Harmer
3.187
234012AE2-112_GEN
Solar/Wind Harmer
0.135
971983AH1-536 GEN
Solar/Wind Harmer
0.332
970453AG2-297 GEN
Solar/Wind Harmer
0.145
971553AH1-274 GEN
Solar/Wind Harmer
0.127
945431AF1-208 GEN
Solar/Wind Harmer
0.341
970997AG2-616 GEN
Solar/Wind Harmer
0.378
972141AH1-641 GEN
Solar/Wind Harmer
0.114
230430AE1-229_GEN
Solar/Wind Harmer
-0.001
230422AE1-104_GEN1
Solar/Wind Harmer
31.36
230425AE1-104_GEN2
Solar/Wind Harmer
31.36
228351V2-046C
Solar/Wind Harmer
-0.001
230433AD2-135 GEN
Solar/Wind Harmer
0
971011AG2-627 GEN
Solar/Wind Harmer
0.302
971535AH1-265 GEN
Solar/Wind Harmer
0.222
230407AD2-065 C
Solar/Wind Harmer
0
228754AB1-001 C
Solar/Wind Harmer
-0.001
219137THOSOLAR C
Solar/Wind Harmer
0.001
219623KINSLEYBEA C
Solar/Wind Harmer
-0.001
219258KINSLEYDEP C
Solar/Wind Harmer
0
219766PARADISE C
Solar/Wind Harmer
-0.001
218660EHAMPSOLAR C
Solar/Wind Harmer
-0.001
219907AC1-030 C
Solar/Wind Harmer
-0.001
219236SOUTHERNHQ C
Solar/Wind Harmer
-0.001
219906AC1-017 C
Solar/Wind Harmer
-0.001
219615MILLCREEK C
Solar/Wind Harmer
-0.001
214067T20SOLAR
Solar/Wind Harmer
-0.001
207522AF2-254 C
Solar/Wind Harmer
0.073
207500AE2-000G1
Solar/Wind Harmer
28.472
207497AE2-000G2
Solar/Wind Harmer
28.472
207507AE2-000G3
Solar/Wind Harmer
28.472
207487AE2-000G4
Solar/Wind Harmer
28.472
970025AG2-016 GEN
Solar/Wind Harmer
0.144
971189AH1-054 GEN
Solar/Wind Harmer
0.06
971667AH1-334 GEN
Solar/Wind Harmer
0.139
219727YARDVSOLFA C
Solar/Wind Harmer
0.001
219276PARKLANDSO C
Solar/Wind Harmer
0
219817TRENTONSOL C
Solar/Wind Harmer
0.001
219620RIDERU C
Solar/Wind Harmer
-0.001
20714328BYD_X4-031
Solar/Wind Harmer
0.014
20714428HOW_X1-037
Solar/Wind Harmer
0
219918AC2-009 C
Solar/Wind Harmer
0
20720628TIN_W1-124
Solar/Wind Harmer
-0.001
20742028HF_AC1-207
Solar/Wind Harmer
-0.001
971521AH1-258 GEN
Solar/Wind Harmer
0.137
967451AG2-055 C O1
Solar/Wind Harmer
156.372
219612MATRIX C
Solar/Wind Harmer
0
218438BLK ROCK C
Solar/Wind Harmer
0
218526CNTRALGAS2 C
Solar/Wind Harmer
0
218524CNTRALGAS1 C
Solar/Wind Harmer
0
218428ETC SOLAR C
Solar/Wind Harmer
0
217213AMBOY SO C
Solar/Wind Harmer
-0.001
219249CENTRALDIV C
Solar/Wind Harmer
0
20673828FLE_V3-070
Solar/Wind Harmer
0.05
20675428EAM_W2-061
Solar/Wind Harmer
0
218449LINSOLAR C
Solar/Wind Harmer
0
217081WEATEXAS C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
217206BARNGR HS C
Solar/Wind Harmer
0
217208PARK ELE C
Solar/Wind Harmer
0
207439AE1-081 C O1
Solar/Wind Harmer
0
20676328BVR_Y1-020
Solar/Wind Harmer
0
20674628WNG_W3-110
Solar/Wind Harmer
-0.001
207511W3-106 GEN
Solar/Wind Harmer
0.033
971009AG2-626 GEN
Solar/Wind Harmer
0.083
971007AG2-625 GEN
Solar/Wind Harmer
0.13
971519AH1-257 GEN
Solar/Wind Harmer
0.127
207437AD2-070 GEN
Solar/Wind Harmer
-0.001
966181AG1-487 GEN
Solar/Wind Harmer
0
966181AG1-487 GEN
Solar/Wind Harmer
2.511
966111AG1-480 GEN
Solar/Wind Harmer
0
966111AG1-480 GEN
Solar/Wind Harmer
2.214
970095AG2-074 GEN
Solar/Wind Harmer
0.231
208972BECR K09
Solar/Wind Harmer
1.704
209027LOR2_Q27
Solar/Wind Harmer
6.819
212266LOR1
Solar/Wind Harmer
0.127
970237AG2-161 GEN
Solar/Wind Harmer
0.15
961541AF2-445A GEN
Solar/Wind Harmer
0.119
209029WAYMART-WD
Solar/Wind Harmer
4.541
209142AF1-226 GEN
Solar/Wind Harmer
0.208
209093AE2-110 GEN
Solar/Wind Harmer
0.119
209120AE2-241 GEN
Solar/Wind Harmer
0.119
209045AE2-271 GEN
Solar/Wind Harmer
0.603
209059AE2-084 GEN
Solar/Wind Harmer
0.118
208862AG1-362 C
Solar/Wind Harmer
0.029
970665AG2-430 GEN
Solar/Wind Harmer
0.351
209130AF1-271A GEN
Solar/Wind Harmer
0.099
227287AC2-120 GEN
Solar/Wind Helper
0.242
226910AB2-157 C
Solar/Wind Helper
0.023
226929AD2-058 GEN
Solar/Wind Helper
0.047
3141426STAFORD
Solar/Wind Helper
0.078
3138216PACIFIC
Solar/Wind Helper
0.057
316411AF1-147_GEN1
Solar/Wind Helper
0.272
316415AF1-147_GEN2
Solar/Wind Helper
0.272
3141196NOKESVL
Solar/Wind Helper
1.344
316045AC1-158 PL2
Solar/Wind Helper
1.227
316447AC1-158 HLD
Solar/Wind Helper
0.843
316044AC1-158 PL1
Solar/Wind Helper
0.384
316006AB2-029 C
Solar/Wind Helper
0.104
316450AC1-158 RIC
Solar/Wind Helper
0.102
944491AF1-114 GEN
Solar/Wind Helper
0.526
957971AF2-091 GEN
Solar/Wind Helper
0.179
966881AG1-559 GEN
Solar/Wind Helper
0.105
316164AC1-076 GEN
Solar/Wind Helper
0.327
315651AD1-115 GEN
Solar/Wind Helper
0.781
316254AC1-120 GEN1
Solar/Wind Helper
0.312
316170AC1-121 GEN2
Solar/Wind Helper
0.104
316223AC1-118
Solar/Wind Helper
0.103
3141906WESTMOR
Solar/Wind Helper
0.128
316468AD1-105 GEN
Solar/Wind Helper
0.381
316337AD2-073 GEN
Solar/Wind Helper
0.102
3147666LOUISA
Solar/Wind Helper
1.264
3147666LOUISA
Solar/Wind Helper
0.727
3132273ORANGE
Solar/Wind Helper
0.063
316192AB2-158 GEN
Solar/Wind Helper
0.447
316077AC2-138 C
Solar/Wind Helper
0.071
3141813NORNECK
Solar/Wind Helper
0.314
964211AG1-282 GEN
Solar/Wind Helper
0.101
3141726DUNNSVL
Solar/Wind Helper
1.255
316404AE1-155 C
Solar/Wind Helper
0.638
316473AC1-191 GEN
Solar/Wind Helper
0.401
966871AG1-558 GEN
Solar/Wind Helper
0.1
316484AD2-074 GEN
Solar/Wind Helper
0.43
316487AF1-042 GEN
Solar/Wind Helper
0.225
961951AG1-038 GEN
Solar/Wind Helper
0.225
G-007ALTFEXP_G-007A->PJM
CMTX
33.644
HAMLETPJM->LTFIMP_HAMLET
CLTF
4.305
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.462
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
13.881
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
2.889
BlueGrassPJM->LTFIMP_BlueG
CLTF
9.012
CBM NorthLTFEXP_CBM-N->PJM
CBM
51.71
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
88.829

Details for CNASTONE-BRIGHTON 500.0 kV Ckt 1 line l/o PECO_P1-2_5007_SRT-A/* $ CHESCO $ PECO_P1-2_5007 $ L


Base Case Flowgate

Area:PJM
Facility Description:
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
Contingency Name:
PECO_P1-2_5007_SRT-A/* $ CHESCO $ PECO_P1-2_5007 $ L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.36 %
Rating:3507.0 MVA
Rating Type:B
MVA to Mitigate:4080.66
MW Contribution:0.33
Bus #Bus NameTypeMW Contribution
972281AH1-725 GEN
50/50
138.416
200202DELTA2 ST
50/50
5.315
200200DELTA2 CT1
50/50
2.975
200201DELTA2 CT2
50/50
2.975
200195DELTA ST
50/50
2.629
200192DELTA CT1
50/50
1.577
200193DELTA CT2
50/50
1.577
200194DELTA CT3
50/50
1.577
200034PCHBTM 2
50/50
104.173
200035PCHBTM 3
50/50
17.223
200203Y1-065-STG
50/50
5.951
200204Y1-065-CTG1
50/50
3.748
200205Y1-065-CTG2
50/50
3.748
200052ROCKSP 1
50/50
44.463
200053ROCKSP 2
50/50
44.463
200054ROCKSP 3
50/50
44.011
200055ROCKSP 4
50/50
44.011
233987AB2-037 GEN
Solar/Wind Harmer
0
233923SMA
Solar/Wind Harmer
-0.001
233998TM1NIN_3.36
Solar/Wind Harmer
-0.001
233997TMININ_4.2
Solar/Wind Harmer
-0.001
233996TM1833_GEN
Solar/Wind Harmer
-0.001
233940AF2-379 C
Solar/Wind Harmer
-0.001
972069AH1-584 GEN
Solar/Wind Harmer
0.469
972071AH1-585 GEN
Solar/Wind Harmer
0.469
972073AH1-586 GEN
Solar/Wind Harmer
8.438
971747AH1-380 GEN
Solar/Wind Harmer
0.188
234015AF2-250 C
Solar/Wind Harmer
0
971195AH1-057 GEN
Solar/Wind Harmer
0.068
233990AG1-397 GEN
Solar/Wind Harmer
0
960671AF2-358 GEN
Solar/Wind Harmer
0.937
965821AG1-450 GEN
Solar/Wind Harmer
4.687
233990AG1-397 GEN
Solar/Wind Harmer
1.5
232426Y1-080 FULL
Solar/Wind Harmer
0
970277AG2-181 GEN
Solar/Wind Harmer
0.262
234033AF1-007_GEN
Solar/Wind Harmer
19.609
970545AG2-347 GEN
Solar/Wind Harmer
80.774
972133AH1-634 GEN
Solar/Wind Harmer
12.239
233946AB2-136 GEN
Solar/Wind Harmer
-0.001
233964AF2-378 GEN
Solar/Wind Harmer
0
234041AC1-190 GEN
Solar/Wind Harmer
0.469
972177AH1-672 GEN
Solar/Wind Harmer
0.703
971149AH1-027 GEN
Solar/Wind Harmer
0.234
233972AC1-094 C
Solar/Wind Harmer
-0.001
970695AG2-447 GEN
Solar/Wind Harmer
0.187
233984AB2-036 GEN
Solar/Wind Harmer
0.86
233968AD2-076_GEN
Solar/Wind Harmer
0.457
234014AF1-036_GEN
Solar/Wind Harmer
0.186
970597AG2-380 GEN
Solar/Wind Harmer
3.729
234012AE2-112_GEN
Solar/Wind Harmer
0.158
971983AH1-536 GEN
Solar/Wind Harmer
0.389
970453AG2-297 GEN
Solar/Wind Harmer
0.16
971553AH1-274 GEN
Solar/Wind Harmer
0.139
945431AF1-208 GEN
Solar/Wind Harmer
0.375
970997AG2-616 GEN
Solar/Wind Harmer
0.416
972141AH1-641 GEN
Solar/Wind Harmer
0.125
230430AE1-229_GEN
Solar/Wind Harmer
-0.001
228351V2-046C
Solar/Wind Harmer
-0.001
230433AD2-135 GEN
Solar/Wind Harmer
0
230422AE1-104_GEN1
Solar/Wind Harmer
34.337
230425AE1-104_GEN2
Solar/Wind Harmer
34.337
971011AG2-627 GEN
Solar/Wind Harmer
0.331
971535AH1-265 GEN
Solar/Wind Harmer
0.243
230407AD2-065 C
Solar/Wind Harmer
0
228754AB1-001 C
Solar/Wind Harmer
-0.001
219137THOSOLAR C
Solar/Wind Harmer
0.001
219623KINSLEYBEA C
Solar/Wind Harmer
-0.001
219258KINSLEYDEP C
Solar/Wind Harmer
0
219766PARADISE C
Solar/Wind Harmer
-0.001
218660EHAMPSOLAR C
Solar/Wind Harmer
-0.001
219907AC1-030 C
Solar/Wind Harmer
-0.001
219236SOUTHERNHQ C
Solar/Wind Harmer
-0.001
219906AC1-017 C
Solar/Wind Harmer
-0.001
219615MILLCREEK C
Solar/Wind Harmer
-0.001
214067T20SOLAR
Solar/Wind Harmer
-0.001
207522AF2-254 C
Solar/Wind Harmer
0.076
207500AE2-000G1
Solar/Wind Harmer
29.74
207497AE2-000G2
Solar/Wind Harmer
29.74
207507AE2-000G3
Solar/Wind Harmer
29.74
207487AE2-000G4
Solar/Wind Harmer
29.74
970025AG2-016 GEN
Solar/Wind Harmer
0.15
971189AH1-054 GEN
Solar/Wind Harmer
0.062
971667AH1-334 GEN
Solar/Wind Harmer
0.144
219727YARDVSOLFA C
Solar/Wind Harmer
0.001
219276PARKLANDSO C
Solar/Wind Harmer
0
219620RIDERU C
Solar/Wind Harmer
-0.001
219817TRENTONSOL C
Solar/Wind Harmer
0.001
20714328BYD_X4-031
Solar/Wind Harmer
0.015
20714428HOW_X1-037
Solar/Wind Harmer
0
219918AC2-009 C
Solar/Wind Harmer
0
20720628TIN_W1-124
Solar/Wind Harmer
-0.001
20742028HF_AC1-207
Solar/Wind Harmer
-0.001
971521AH1-258 GEN
Solar/Wind Harmer
0.139
967451AG2-055 C O1
Solar/Wind Harmer
157.975
219612MATRIX C
Solar/Wind Harmer
0
218438BLK ROCK C
Solar/Wind Harmer
0
218526CNTRALGAS2 C
Solar/Wind Harmer
0
218524CNTRALGAS1 C
Solar/Wind Harmer
0
218428ETC SOLAR C
Solar/Wind Harmer
0
217213AMBOY SO C
Solar/Wind Harmer
-0.001
219249CENTRALDIV C
Solar/Wind Harmer
0
20673828FLE_V3-070
Solar/Wind Harmer
0.049
20675428EAM_W2-061
Solar/Wind Harmer
0
218449LINSOLAR C
Solar/Wind Harmer
0
217081WEATEXAS C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
217206BARNGR HS C
Solar/Wind Harmer
0
217208PARK ELE C
Solar/Wind Harmer
0
207439AE1-081 C O1
Solar/Wind Harmer
0
20676328BVR_Y1-020
Solar/Wind Harmer
0
20674628WNG_W3-110
Solar/Wind Harmer
-0.001
207511W3-106 GEN
Solar/Wind Harmer
0.031
971009AG2-626 GEN
Solar/Wind Harmer
0.077
971007AG2-625 GEN
Solar/Wind Harmer
0.12
971519AH1-257 GEN
Solar/Wind Harmer
0.118
207437AD2-070 GEN
Solar/Wind Harmer
-0.001
966181AG1-487 GEN
Solar/Wind Harmer
0
966181AG1-487 GEN
Solar/Wind Harmer
2.299
966111AG1-480 GEN
Solar/Wind Harmer
0
966111AG1-480 GEN
Solar/Wind Harmer
2.023
970095AG2-074 GEN
Solar/Wind Harmer
0.199
209029WAYMART-WD
Solar/Wind Harmer
3.943
208972BECR K09
Solar/Wind Harmer
1.457
227287AC2-120 GEN
Solar/Wind Helper
0.169
226929AD2-058 GEN
Solar/Wind Helper
0.034
226910AB2-157 C
Solar/Wind Helper
0.016
3138216PACIFIC
Solar/Wind Helper
0.056
316411AF1-147_GEN1
Solar/Wind Helper
0.271
316415AF1-147_GEN2
Solar/Wind Helper
0.271
3141426STAFORD
Solar/Wind Helper
0.073
3141196NOKESVL
Solar/Wind Helper
1.324
316006AB2-029 C
Solar/Wind Helper
0.103
316045AC1-158 PL2
Solar/Wind Helper
1.194
316447AC1-158 HLD
Solar/Wind Helper
0.82
316044AC1-158 PL1
Solar/Wind Helper
0.373
316450AC1-158 RIC
Solar/Wind Helper
0.099
315651AD1-115 GEN
Solar/Wind Helper
0.765
316164AC1-076 GEN
Solar/Wind Helper
0.319
316254AC1-120 GEN1
Solar/Wind Helper
0.305
316170AC1-121 GEN2
Solar/Wind Helper
0.102
944491AF1-114 GEN
Solar/Wind Helper
0.502
957971AF2-091 GEN
Solar/Wind Helper
0.171
966881AG1-559 GEN
Solar/Wind Helper
0.1
G-007ALTFEXP_G-007A->PJM
CMTX
33.604
HAMLETPJM->LTFIMP_HAMLET
CLTF
4.416
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.557
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
15.298
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
3.212
BlueGrassPJM->LTFIMP_BlueG
CLTF
10.016
CBM NorthLTFEXP_CBM-N->PJM
CBM
47.818
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
86.741

Details for CNASTONE-BRIGHTON 500.0 kV Ckt 1 line l/o BG_P7_CNSTN_NWEST2_SRT-A


Base Case Flowgate

Area:PJM
Facility Description:
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
Contingency Name:
BG_P7_CNSTN_NWEST2_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:108.78 %
Rating:3507.0 MVA
Rating Type:B
MVA to Mitigate:3814.93
MW Contribution:0.28
Bus #Bus NameTypeMW Contribution
972281AH1-725 GEN
50/50
121.649
200202DELTA2 ST
50/50
3.847
200200DELTA2 CT1
50/50
2.154
200201DELTA2 CT2
50/50
2.154
200195DELTA ST
50/50
1.903
200192DELTA CT1
50/50
1.142
200193DELTA CT2
50/50
1.142
200194DELTA CT3
50/50
1.142
200034PCHBTM 2
50/50
75.435
200203Y1-065-STG
50/50
4.37
200204Y1-065-CTG1
50/50
2.752
200205Y1-065-CTG2
50/50
2.752
200052ROCKSP 1
50/50
32.647
200053ROCKSP 2
50/50
32.647
200054ROCKSP 3
50/50
32.316
200055ROCKSP 4
50/50
32.316
200035PCHBTM 3
50/50
12.247
200061HUNTR401
50/50
2.876
200058HUNTR101
50/50
1.505
200059HUNTR201
50/50
1.505
200060HUNTR301
50/50
1.505
233987AB2-037 GEN
Solar/Wind Harmer
0
233923SMA
Solar/Wind Harmer
-0.001
233998TM1NIN_3.36
Solar/Wind Harmer
-0.001
233997TMININ_4.2
Solar/Wind Harmer
-0.001
233996TM1833_GEN
Solar/Wind Harmer
-0.001
233940AF2-379 C
Solar/Wind Harmer
-0.001
972069AH1-584 GEN
Solar/Wind Harmer
0.371
972071AH1-585 GEN
Solar/Wind Harmer
0.371
972073AH1-586 GEN
Solar/Wind Harmer
6.686
971747AH1-380 GEN
Solar/Wind Harmer
0.149
234033AF1-007_GEN
Solar/Wind Harmer
15.538
233990AG1-397 GEN
Solar/Wind Harmer
0
234015AF2-250 C
Solar/Wind Harmer
0
970545AG2-347 GEN
Solar/Wind Harmer
64.008
972133AH1-634 GEN
Solar/Wind Harmer
9.698
233990AG1-397 GEN
Solar/Wind Harmer
1.189
971195AH1-057 GEN
Solar/Wind Harmer
0.053
232426Y1-080 FULL
Solar/Wind Harmer
0
960671AF2-358 GEN
Solar/Wind Harmer
0.743
970277AG2-181 GEN
Solar/Wind Harmer
0.208
965821AG1-450 GEN
Solar/Wind Harmer
3.714
233946AB2-136 GEN
Solar/Wind Harmer
-0.001
233964AF2-378 GEN
Solar/Wind Harmer
0
971149AH1-027 GEN
Solar/Wind Harmer
0.186
972177AH1-672 GEN
Solar/Wind Harmer
0.557
234041AC1-190 GEN
Solar/Wind Harmer
0.371
233972AC1-094 C
Solar/Wind Harmer
-0.001
970695AG2-447 GEN
Solar/Wind Harmer
0.148
233984AB2-036 GEN
Solar/Wind Harmer
0.682
233968AD2-076_GEN
Solar/Wind Harmer
0.363
234014AF1-036_GEN
Solar/Wind Harmer
0.148
970597AG2-380 GEN
Solar/Wind Harmer
2.96
234012AE2-112_GEN
Solar/Wind Harmer
0.126
971983AH1-536 GEN
Solar/Wind Harmer
0.309
970453AG2-297 GEN
Solar/Wind Harmer
0.133
971553AH1-274 GEN
Solar/Wind Harmer
0.117
945431AF1-208 GEN
Solar/Wind Harmer
0.314
970997AG2-616 GEN
Solar/Wind Harmer
0.348
972141AH1-641 GEN
Solar/Wind Harmer
0.104
230430AE1-229_GEN
Solar/Wind Harmer
-0.001
228351V2-046C
Solar/Wind Harmer
-0.001
230433AD2-135 GEN
Solar/Wind Harmer
0
230422AE1-104_GEN1
Solar/Wind Harmer
28.834
230425AE1-104_GEN2
Solar/Wind Harmer
28.834
971011AG2-627 GEN
Solar/Wind Harmer
0.278
971535AH1-265 GEN
Solar/Wind Harmer
0.204
230407AD2-065 C
Solar/Wind Harmer
0
228754AB1-001 C
Solar/Wind Harmer
-0.001
219137THOSOLAR C
Solar/Wind Harmer
0
219623KINSLEYBEA C
Solar/Wind Harmer
-0.001
219258KINSLEYDEP C
Solar/Wind Harmer
0
219766PARADISE C
Solar/Wind Harmer
-0.001
218660EHAMPSOLAR C
Solar/Wind Harmer
-0.001
219907AC1-030 C
Solar/Wind Harmer
-0.001
219236SOUTHERNHQ C
Solar/Wind Harmer
0
219906AC1-017 C
Solar/Wind Harmer
-0.001
219615MILLCREEK C
Solar/Wind Harmer
-0.001
214067T20SOLAR
Solar/Wind Harmer
-0.001
207522AF2-254 C
Solar/Wind Harmer
0.067
207500AE2-000G1
Solar/Wind Harmer
26.065
207497AE2-000G2
Solar/Wind Harmer
26.065
207507AE2-000G3
Solar/Wind Harmer
26.065
207487AE2-000G4
Solar/Wind Harmer
26.065
970025AG2-016 GEN
Solar/Wind Harmer
0.131
971189AH1-054 GEN
Solar/Wind Harmer
0.055
971667AH1-334 GEN
Solar/Wind Harmer
0.127
219727YARDVSOLFA C
Solar/Wind Harmer
0
219276PARKLANDSO C
Solar/Wind Harmer
0
219817TRENTONSOL C
Solar/Wind Harmer
0
219620RIDERU C
Solar/Wind Harmer
-0.001
20714328BYD_X4-031
Solar/Wind Harmer
0.013
20714428HOW_X1-037
Solar/Wind Harmer
0
219918AC2-009 C
Solar/Wind Harmer
0
20720628TIN_W1-124
Solar/Wind Harmer
-0.001
20742028HF_AC1-207
Solar/Wind Harmer
-0.001
971521AH1-258 GEN
Solar/Wind Harmer
0.125
967451AG2-055 C O1
Solar/Wind Harmer
142.665
219612MATRIX C
Solar/Wind Harmer
0
218438BLK ROCK C
Solar/Wind Harmer
0
218526CNTRALGAS2 C
Solar/Wind Harmer
0
218524CNTRALGAS1 C
Solar/Wind Harmer
0
218428ETC SOLAR C
Solar/Wind Harmer
0
217213AMBOY SO C
Solar/Wind Harmer
-0.001
219249CENTRALDIV C
Solar/Wind Harmer
0
20673828FLE_V3-070
Solar/Wind Harmer
0.046
20675428EAM_W2-061
Solar/Wind Harmer
0
218449LINSOLAR C
Solar/Wind Harmer
0
217081WEATEXAS C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
217206BARNGR HS C
Solar/Wind Harmer
0
217208PARK ELE C
Solar/Wind Harmer
0
207439AE1-081 C O1
Solar/Wind Harmer
0
20676328BVR_Y1-020
Solar/Wind Harmer
0
20674628WNG_W3-110
Solar/Wind Harmer
-0.001
207511W3-106 GEN
Solar/Wind Harmer
0.03
971009AG2-626 GEN
Solar/Wind Harmer
0.075
971007AG2-625 GEN
Solar/Wind Harmer
0.118
971519AH1-257 GEN
Solar/Wind Harmer
0.116
207437AD2-070 GEN
Solar/Wind Harmer
-0.001
966181AG1-487 GEN
Solar/Wind Harmer
0
966181AG1-487 GEN
Solar/Wind Harmer
2.283
966111AG1-480 GEN
Solar/Wind Harmer
0
966111AG1-480 GEN
Solar/Wind Harmer
2.007
208862AG1-362 C
Solar/Wind Harmer
0.028
970095AG2-074 GEN
Solar/Wind Harmer
0.208
208972BECR K09
Solar/Wind Harmer
1.534
209027LOR2_Q27
Solar/Wind Harmer
6.123
212266LOR1
Solar/Wind Harmer
0.114
970237AG2-161 GEN
Solar/Wind Harmer
0.135
961541AF2-445A GEN
Solar/Wind Harmer
0.107
209029WAYMART-WD
Solar/Wind Harmer
4.094
209142AF1-226 GEN
Solar/Wind Harmer
0.187
209093AE2-110 GEN
Solar/Wind Harmer
0.107
209120AE2-241 GEN
Solar/Wind Harmer
0.107
209045AE2-271 GEN
Solar/Wind Harmer
0.54
208835TUHI V3-051
Solar/Wind Harmer
0.052
208835TUHI V3-051
Solar/Wind Harmer
0.052
209059AE2-084 GEN
Solar/Wind Harmer
0.105
970665AG2-430 GEN
Solar/Wind Harmer
0.314
209130AF1-271A GEN
Solar/Wind Harmer
0.089
227287AC2-120 GEN
Solar/Wind Helper
0.191
226910AB2-157 C
Solar/Wind Helper
0.018
226929AD2-058 GEN
Solar/Wind Helper
0.038
3141426STAFORD
Solar/Wind Helper
0.071
3138216PACIFIC
Solar/Wind Helper
0.054
316411AF1-147_GEN1
Solar/Wind Helper
0.257
316415AF1-147_GEN2
Solar/Wind Helper
0.257
3141196NOKESVL
Solar/Wind Helper
1.258
G-007ALTFEXP_G-007A->PJM
CMTX
30.678
HAMLETPJM->LTFIMP_HAMLET
CLTF
4.037
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.317
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
13.27
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
2.769
BlueGrassPJM->LTFIMP_BlueG
CLTF
8.637
CBM NorthLTFEXP_CBM-N->PJM
CBM
46.931
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
80.859

Details for CNASTONE-BRIGHTON 500.0 kV Ckt 1 line l/o BG_P7_GRCTN_RAPHEL_SRT-A


Base Case Flowgate

Area:PJM
Facility Description:
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
Contingency Name:
BG_P7_GRCTN_RAPHEL_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:106.71 %
Rating:3507.0 MVA
Rating Type:B
MVA to Mitigate:3742.49
MW Contribution:0.28
Bus #Bus NameTypeMW Contribution
972281AH1-725 GEN
50/50
119.482
200202DELTA2 ST
50/50
3.799
200200DELTA2 CT1
50/50
2.127
200201DELTA2 CT2
50/50
2.127
200195DELTA ST
50/50
1.879
200192DELTA CT1
50/50
1.127
200193DELTA CT2
50/50
1.127
200194DELTA CT3
50/50
1.127
200034PCHBTM 2
50/50
74.49
200203Y1-065-STG
50/50
4.321
200204Y1-065-CTG1
50/50
2.721
200205Y1-065-CTG2
50/50
2.721
200052ROCKSP 1
50/50
32.283
200053ROCKSP 2
50/50
32.283
200054ROCKSP 3
50/50
31.955
200055ROCKSP 4
50/50
31.955
200035PCHBTM 3
50/50
12.097
200061HUNTR401
50/50
2.829
200058HUNTR101
50/50
1.481
200059HUNTR201
50/50
1.481
200060HUNTR301
50/50
1.481
233987AB2-037 GEN
Solar/Wind Harmer
0
233923SMA
Solar/Wind Harmer
-0.001
233946AB2-136 GEN
Solar/Wind Harmer
-0.001
233998TM1NIN_3.36
Solar/Wind Harmer
-0.001
233997TMININ_4.2
Solar/Wind Harmer
-0.001
233996TM1833_GEN
Solar/Wind Harmer
-0.001
233940AF2-379 C
Solar/Wind Harmer
-0.001
232426Y1-080 FULL
Solar/Wind Harmer
0
233964AF2-378 GEN
Solar/Wind Harmer
0
960671AF2-358 GEN
Solar/Wind Harmer
0.741
970277AG2-181 GEN
Solar/Wind Harmer
0.207
965821AG1-450 GEN
Solar/Wind Harmer
3.705
233990AG1-397 GEN
Solar/Wind Harmer
0
234015AF2-250 C
Solar/Wind Harmer
0
234041AC1-190 GEN
Solar/Wind Harmer
0.37
972069AH1-584 GEN
Solar/Wind Harmer
0.37
972071AH1-585 GEN
Solar/Wind Harmer
0.37
972073AH1-586 GEN
Solar/Wind Harmer
6.669
971747AH1-380 GEN
Solar/Wind Harmer
0.148
233990AG1-397 GEN
Solar/Wind Harmer
1.186
971195AH1-057 GEN
Solar/Wind Harmer
0.053
234033AF1-007_GEN
Solar/Wind Harmer
15.498
970545AG2-347 GEN
Solar/Wind Harmer
63.84
972133AH1-634 GEN
Solar/Wind Harmer
9.673
972177AH1-672 GEN
Solar/Wind Harmer
0.555
971149AH1-027 GEN
Solar/Wind Harmer
0.185
233984AB2-036 GEN
Solar/Wind Harmer
0.681
233972AC1-094 C
Solar/Wind Harmer
-0.001
970695AG2-447 GEN
Solar/Wind Harmer
0.148
233968AD2-076_GEN
Solar/Wind Harmer
0.362
234014AF1-036_GEN
Solar/Wind Harmer
0.148
970597AG2-380 GEN
Solar/Wind Harmer
2.958
234012AE2-112_GEN
Solar/Wind Harmer
0.126
971983AH1-536 GEN
Solar/Wind Harmer
0.309
970453AG2-297 GEN
Solar/Wind Harmer
0.133
971553AH1-274 GEN
Solar/Wind Harmer
0.116
945431AF1-208 GEN
Solar/Wind Harmer
0.313
970997AG2-616 GEN
Solar/Wind Harmer
0.348
972141AH1-641 GEN
Solar/Wind Harmer
0.104
230430AE1-229_GEN
Solar/Wind Harmer
-0.001
228351V2-046C
Solar/Wind Harmer
-0.001
230433AD2-135 GEN
Solar/Wind Harmer
0
971011AG2-627 GEN
Solar/Wind Harmer
0.278
230422AE1-104_GEN1
Solar/Wind Harmer
28.771
230425AE1-104_GEN2
Solar/Wind Harmer
28.771
971535AH1-265 GEN
Solar/Wind Harmer
0.204
230407AD2-065 C
Solar/Wind Harmer
0
228754AB1-001 C
Solar/Wind Harmer
-0.001
219137THOSOLAR C
Solar/Wind Harmer
0
219623KINSLEYBEA C
Solar/Wind Harmer
-0.001
219258KINSLEYDEP C
Solar/Wind Harmer
0
219766PARADISE C
Solar/Wind Harmer
-0.001
218660EHAMPSOLAR C
Solar/Wind Harmer
-0.001
219907AC1-030 C
Solar/Wind Harmer
-0.001
219236SOUTHERNHQ C
Solar/Wind Harmer
0
219906AC1-017 C
Solar/Wind Harmer
-0.001
219615MILLCREEK C
Solar/Wind Harmer
-0.001
214067T20SOLAR
Solar/Wind Harmer
-0.001
207522AF2-254 C
Solar/Wind Harmer
0.067
207500AE2-000G1
Solar/Wind Harmer
26.015
207497AE2-000G2
Solar/Wind Harmer
26.015
207507AE2-000G3
Solar/Wind Harmer
26.015
207487AE2-000G4
Solar/Wind Harmer
26.015
970025AG2-016 GEN
Solar/Wind Harmer
0.131
971189AH1-054 GEN
Solar/Wind Harmer
0.055
971667AH1-334 GEN
Solar/Wind Harmer
0.127
219727YARDVSOLFA C
Solar/Wind Harmer
0
219276PARKLANDSO C
Solar/Wind Harmer
0
219817TRENTONSOL C
Solar/Wind Harmer
0
219620RIDERU C
Solar/Wind Harmer
-0.001
20714328BYD_X4-031
Solar/Wind Harmer
0.013
20714428HOW_X1-037
Solar/Wind Harmer
0
219918AC2-009 C
Solar/Wind Harmer
0
20720628TIN_W1-124
Solar/Wind Harmer
-0.001
20742028HF_AC1-207
Solar/Wind Harmer
-0.001
971521AH1-258 GEN
Solar/Wind Harmer
0.125
967451AG2-055 C O1
Solar/Wind Harmer
142.39
219612MATRIX C
Solar/Wind Harmer
0
218438BLK ROCK C
Solar/Wind Harmer
0
218526CNTRALGAS2 C
Solar/Wind Harmer
0
218524CNTRALGAS1 C
Solar/Wind Harmer
0
218428ETC SOLAR C
Solar/Wind Harmer
0
217213AMBOY SO C
Solar/Wind Harmer
-0.001
219249CENTRALDIV C
Solar/Wind Harmer
0
20673828FLE_V3-070
Solar/Wind Harmer
0.046
20675428EAM_W2-061
Solar/Wind Harmer
0
218449LINSOLAR C
Solar/Wind Harmer
0
217081WEATEXAS C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
217206BARNGR HS C
Solar/Wind Harmer
0
217208PARK ELE C
Solar/Wind Harmer
0
207439AE1-081 C O1
Solar/Wind Harmer
0
20676328BVR_Y1-020
Solar/Wind Harmer
0
20674628WNG_W3-110
Solar/Wind Harmer
-0.001
207511W3-106 GEN
Solar/Wind Harmer
0.03
971007AG2-625 GEN
Solar/Wind Harmer
0.118
971009AG2-626 GEN
Solar/Wind Harmer
0.075
971519AH1-257 GEN
Solar/Wind Harmer
0.116
207437AD2-070 GEN
Solar/Wind Harmer
-0.001
966181AG1-487 GEN
Solar/Wind Harmer
0
966181AG1-487 GEN
Solar/Wind Harmer
2.281
966111AG1-480 GEN
Solar/Wind Harmer
0
966111AG1-480 GEN
Solar/Wind Harmer
2.004
208862AG1-362 C
Solar/Wind Harmer
0.028
208835TUHI V3-051
Solar/Wind Harmer
0.054
208835TUHI V3-051
Solar/Wind Harmer
0.054
970095AG2-074 GEN
Solar/Wind Harmer
0.208
208972BECR K09
Solar/Wind Harmer
1.531
209027LOR2_Q27
Solar/Wind Harmer
6.111
212266LOR1
Solar/Wind Harmer
0.114
970237AG2-161 GEN
Solar/Wind Harmer
0.134
961541AF2-445A GEN
Solar/Wind Harmer
0.107
209029WAYMART-WD
Solar/Wind Harmer
4.087
209142AF1-226 GEN
Solar/Wind Harmer
0.187
209093AE2-110 GEN
Solar/Wind Harmer
0.107
209120AE2-241 GEN
Solar/Wind Harmer
0.107
209045AE2-271 GEN
Solar/Wind Harmer
0.539
209059AE2-084 GEN
Solar/Wind Harmer
0.105
970665AG2-430 GEN
Solar/Wind Harmer
0.313
209130AF1-271A GEN
Solar/Wind Harmer
0.089
227287AC2-120 GEN
Solar/Wind Helper
0.187
226910AB2-157 C
Solar/Wind Helper
0.017
226929AD2-058 GEN
Solar/Wind Helper
0.037
3141426STAFORD
Solar/Wind Helper
0.07
3138216PACIFIC
Solar/Wind Helper
0.053
316411AF1-147_GEN1
Solar/Wind Helper
0.254
316415AF1-147_GEN2
Solar/Wind Helper
0.254
G-007ALTFEXP_G-007A->PJM
CMTX
30.625
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.982
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.285
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
13.076
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
2.728
BlueGrassPJM->LTFIMP_BlueG
CLTF
8.509
CBM NorthLTFEXP_CBM-N->PJM
CBM
46.867
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
80.723

Details for CNASTONE-BRIGHTON 500.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:PJM
Facility Description:
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.54 %
Rating:3202.0 MVA
Rating Type:A
MVA to Mitigate:3347.24
MW Contribution:0.26
Bus #Bus NameTypeMW Contribution
972281AH1-725 GEN
50/50
114.423
200202DELTA2 ST
50/50
3.587
200200DELTA2 CT1
50/50
2.008
200201DELTA2 CT2
50/50
2.008
200195DELTA ST
50/50
1.775
200192DELTA CT1
50/50
1.065
200193DELTA CT2
50/50
1.065
200194DELTA CT3
50/50
1.065
200034PCHBTM 2
50/50
70.339
200203Y1-065-STG
50/50
4.068
200204Y1-065-CTG1
50/50
2.562
200205Y1-065-CTG2
50/50
2.562
200052ROCKSP 1
50/50
30.396
200053ROCKSP 2
50/50
30.396
200054ROCKSP 3
50/50
30.087
200055ROCKSP 4
50/50
30.087
200061HUNTR401
50/50
2.69
200058HUNTR101
50/50
1.408
200059HUNTR201
50/50
1.408
200060HUNTR301
50/50
1.408
200035PCHBTM 3
50/50
11.414
233987AB2-037 GEN
Solar/Wind Harmer
0
234033AF1-007_GEN
Solar/Wind Harmer
14.341
233923SMA
Solar/Wind Harmer
-0.001
233998TM1NIN_3.36
Solar/Wind Harmer
-0.001
233997TMININ_4.2
Solar/Wind Harmer
-0.001
233996TM1833_GEN
Solar/Wind Harmer
-0.001
233940AF2-379 C
Solar/Wind Harmer
-0.001
970545AG2-347 GEN
Solar/Wind Harmer
59.074
972133AH1-634 GEN
Solar/Wind Harmer
8.951
972069AH1-584 GEN
Solar/Wind Harmer
0.343
972071AH1-585 GEN
Solar/Wind Harmer
0.343
972073AH1-586 GEN
Solar/Wind Harmer
6.17
971149AH1-027 GEN
Solar/Wind Harmer
0.171
971747AH1-380 GEN
Solar/Wind Harmer
0.137
233990AG1-397 GEN
Solar/Wind Harmer
0
234015AF2-250 C
Solar/Wind Harmer
0
233990AG1-397 GEN
Solar/Wind Harmer
1.097
971195AH1-057 GEN
Solar/Wind Harmer
0.049
232426Y1-080 FULL
Solar/Wind Harmer
0
960671AF2-358 GEN
Solar/Wind Harmer
0.685
972177AH1-672 GEN
Solar/Wind Harmer
0.514
970277AG2-181 GEN
Solar/Wind Harmer
0.192
965821AG1-450 GEN
Solar/Wind Harmer
3.427
233972AC1-094 C
Solar/Wind Harmer
-0.001
970695AG2-447 GEN
Solar/Wind Harmer
0.137
233946AB2-136 GEN
Solar/Wind Harmer
-0.001
233964AF2-378 GEN
Solar/Wind Harmer
0
234041AC1-190 GEN
Solar/Wind Harmer
0.343
233984AB2-036 GEN
Solar/Wind Harmer
0.629
233968AD2-076_GEN
Solar/Wind Harmer
0.334
234014AF1-036_GEN
Solar/Wind Harmer
0.136
970597AG2-380 GEN
Solar/Wind Harmer
2.729
234012AE2-112_GEN
Solar/Wind Harmer
0.116
971983AH1-536 GEN
Solar/Wind Harmer
0.285
970453AG2-297 GEN
Solar/Wind Harmer
0.122
971553AH1-274 GEN
Solar/Wind Harmer
0.107
945431AF1-208 GEN
Solar/Wind Harmer
0.289
970997AG2-616 GEN
Solar/Wind Harmer
0.32
972141AH1-641 GEN
Solar/Wind Harmer
0.096
230430AE1-229_GEN
Solar/Wind Harmer
-0.001
228351V2-046C
Solar/Wind Harmer
-0.001
230433AD2-135 GEN
Solar/Wind Harmer
0
230422AE1-104_GEN1
Solar/Wind Harmer
26.53
230425AE1-104_GEN2
Solar/Wind Harmer
26.53
971011AG2-627 GEN
Solar/Wind Harmer
0.256
971535AH1-265 GEN
Solar/Wind Harmer
0.188
230407AD2-065 C
Solar/Wind Harmer
0
228754AB1-001 C
Solar/Wind Harmer
-0.001
219137THOSOLAR C
Solar/Wind Harmer
0
219623KINSLEYBEA C
Solar/Wind Harmer
-0.001
219258KINSLEYDEP C
Solar/Wind Harmer
0
219766PARADISE C
Solar/Wind Harmer
-0.001
218660EHAMPSOLAR C
Solar/Wind Harmer
-0.001
219907AC1-030 C
Solar/Wind Harmer
-0.001
219236SOUTHERNHQ C
Solar/Wind Harmer
0
219906AC1-017 C
Solar/Wind Harmer
-0.001
219615MILLCREEK C
Solar/Wind Harmer
-0.001
214067T20SOLAR
Solar/Wind Harmer
-0.001
207522AF2-254 C
Solar/Wind Harmer
0.061
207500AE2-000G1
Solar/Wind Harmer
23.931
207497AE2-000G2
Solar/Wind Harmer
23.931
207507AE2-000G3
Solar/Wind Harmer
23.931
207487AE2-000G4
Solar/Wind Harmer
23.931
970025AG2-016 GEN
Solar/Wind Harmer
0.121
971189AH1-054 GEN
Solar/Wind Harmer
0.05
971667AH1-334 GEN
Solar/Wind Harmer
0.117
219727YARDVSOLFA C
Solar/Wind Harmer
0
219276PARKLANDSO C
Solar/Wind Harmer
0
219817TRENTONSOL C
Solar/Wind Harmer
0
219620RIDERU C
Solar/Wind Harmer
-0.001
20714328BYD_X4-031
Solar/Wind Harmer
0.012
20714428HOW_X1-037
Solar/Wind Harmer
0
219918AC2-009 C
Solar/Wind Harmer
0
20720628TIN_W1-124
Solar/Wind Harmer
-0.001
20742028HF_AC1-207
Solar/Wind Harmer
-0.001
971521AH1-258 GEN
Solar/Wind Harmer
0.114
967451AG2-055 C O1
Solar/Wind Harmer
130.824
219612MATRIX C
Solar/Wind Harmer
0
218438BLK ROCK C
Solar/Wind Harmer
0
218526CNTRALGAS2 C
Solar/Wind Harmer
0
218524CNTRALGAS1 C
Solar/Wind Harmer
0
218428ETC SOLAR C
Solar/Wind Harmer
0
217213AMBOY SO C
Solar/Wind Harmer
-0.001
219249CENTRALDIV C
Solar/Wind Harmer
0
20673828FLE_V3-070
Solar/Wind Harmer
0.042
20675428EAM_W2-061
Solar/Wind Harmer
0
218449LINSOLAR C
Solar/Wind Harmer
0
217081WEATEXAS C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
217206BARNGR HS C
Solar/Wind Harmer
0
217208PARK ELE C
Solar/Wind Harmer
0
207439AE1-081 C O1
Solar/Wind Harmer
0
20676328BVR_Y1-020
Solar/Wind Harmer
0
20674628WNG_W3-110
Solar/Wind Harmer
-0.001
207511W3-106 GEN
Solar/Wind Harmer
0.028
971009AG2-626 GEN
Solar/Wind Harmer
0.069
971007AG2-625 GEN
Solar/Wind Harmer
0.108
971519AH1-257 GEN
Solar/Wind Harmer
0.106
207437AD2-070 GEN
Solar/Wind Harmer
-0.001
966181AG1-487 GEN
Solar/Wind Harmer
0
966181AG1-487 GEN
Solar/Wind Harmer
2.082
966111AG1-480 GEN
Solar/Wind Harmer
0
966111AG1-480 GEN
Solar/Wind Harmer
1.832
970095AG2-074 GEN
Solar/Wind Harmer
0.19
227287AC2-120 GEN
Solar/Wind Helper
0.166
226910AB2-157 C
Solar/Wind Helper
0.015
226929AD2-058 GEN
Solar/Wind Helper
0.033
G-007ALTFEXP_G-007A->PJM
CMTX
28.115
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.718
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.136
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
12.281
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
2.564
BlueGrassPJM->LTFIMP_BlueG
CLTF
7.998
CBM NorthLTFEXP_CBM-N->PJM
CBM
42.889
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
74.033

Details for CNASTONE-BRIGHTON 500.0 kV Ckt 1 line l/o PJM_500_BG_P2_CNSTN_230-S_SRT-A


Base Case Flowgate

Area:PJM
Facility Description:
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
Contingency Name:
PJM_500_BG_P2_CNSTN_230-S_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:101.14 %
Rating:3507.0 MVA
Rating Type:B
MVA to Mitigate:3546.85
MW Contribution:0.26
Bus #Bus NameTypeMW Contribution
972281AH1-725 GEN
50/50
122.08
200202DELTA2 ST
50/50
3.78
200200DELTA2 CT1
50/50
2.116
200201DELTA2 CT2
50/50
2.116
200195DELTA ST
50/50
1.87
200192DELTA CT1
50/50
1.122
200193DELTA CT2
50/50
1.122
200194DELTA CT3
50/50
1.122
200034PCHBTM 2
50/50
74.114
200061HUNTR401
50/50
2.849
200058HUNTR101
50/50
1.491
200059HUNTR201
50/50
1.491
200060HUNTR301
50/50
1.491
200035PCHBTM 3
50/50
12.017
200203Y1-065-STG
50/50
4.275
200204Y1-065-CTG1
50/50
2.692
200205Y1-065-CTG2
50/50
2.692
200052ROCKSP 1
50/50
31.935
200053ROCKSP 2
50/50
31.935
200054ROCKSP 3
50/50
31.611
200055ROCKSP 4
50/50
31.611
233987AB2-037 GEN
Solar/Wind Harmer
0
971149AH1-027 GEN
Solar/Wind Harmer
0.177
233972AC1-094 C
Solar/Wind Harmer
-0.001
970695AG2-447 GEN
Solar/Wind Harmer
0.142
234033AF1-007_GEN
Solar/Wind Harmer
14.813
970545AG2-347 GEN
Solar/Wind Harmer
61.02
972133AH1-634 GEN
Solar/Wind Harmer
9.245
972069AH1-584 GEN
Solar/Wind Harmer
0.354
972071AH1-585 GEN
Solar/Wind Harmer
0.354
972073AH1-586 GEN
Solar/Wind Harmer
6.372
233923SMA
Solar/Wind Harmer
-0.001
233998TM1NIN_3.36
Solar/Wind Harmer
-0.001
233997TMININ_4.2
Solar/Wind Harmer
-0.001
233996TM1833_GEN
Solar/Wind Harmer
-0.001
233990AG1-397 GEN
Solar/Wind Harmer
0
233940AF2-379 C
Solar/Wind Harmer
-0.001
971747AH1-380 GEN
Solar/Wind Harmer
0.142
233990AG1-397 GEN
Solar/Wind Harmer
1.133
234015AF2-250 C
Solar/Wind Harmer
0
971195AH1-057 GEN
Solar/Wind Harmer
0.051
972177AH1-672 GEN
Solar/Wind Harmer
0.531
960671AF2-358 GEN
Solar/Wind Harmer
0.708
965821AG1-450 GEN
Solar/Wind Harmer
3.538
232426Y1-080 FULL
Solar/Wind Harmer
0
970277AG2-181 GEN
Solar/Wind Harmer
0.198
233946AB2-136 GEN
Solar/Wind Harmer
-0.001
233964AF2-378 GEN
Solar/Wind Harmer
0
234041AC1-190 GEN
Solar/Wind Harmer
0.354
233984AB2-036 GEN
Solar/Wind Harmer
0.648
233968AD2-076_GEN
Solar/Wind Harmer
0.344
234014AF1-036_GEN
Solar/Wind Harmer
0.141
970597AG2-380 GEN
Solar/Wind Harmer
2.812
234012AE2-112_GEN
Solar/Wind Harmer
0.119
971983AH1-536 GEN
Solar/Wind Harmer
0.293
970453AG2-297 GEN
Solar/Wind Harmer
0.126
971553AH1-274 GEN
Solar/Wind Harmer
0.11
945431AF1-208 GEN
Solar/Wind Harmer
0.297
970997AG2-616 GEN
Solar/Wind Harmer
0.329
972141AH1-641 GEN
Solar/Wind Harmer
0.099
230430AE1-229_GEN
Solar/Wind Harmer
-0.001
230422AE1-104_GEN1
Solar/Wind Harmer
27.265
230425AE1-104_GEN2
Solar/Wind Harmer
27.265
228351V2-046C
Solar/Wind Harmer
-0.001
230433AD2-135 GEN
Solar/Wind Harmer
0
971011AG2-627 GEN
Solar/Wind Harmer
0.262
971535AH1-265 GEN
Solar/Wind Harmer
0.193
230407AD2-065 C
Solar/Wind Harmer
0
228754AB1-001 C
Solar/Wind Harmer
-0.001
219137THOSOLAR C
Solar/Wind Harmer
0
219623KINSLEYBEA C
Solar/Wind Harmer
-0.001
219258KINSLEYDEP C
Solar/Wind Harmer
0
219766PARADISE C
Solar/Wind Harmer
-0.001
218660EHAMPSOLAR C
Solar/Wind Harmer
-0.001
219907AC1-030 C
Solar/Wind Harmer
-0.001
219236SOUTHERNHQ C
Solar/Wind Harmer
0
219906AC1-017 C
Solar/Wind Harmer
-0.001
219615MILLCREEK C
Solar/Wind Harmer
-0.001
214067T20SOLAR
Solar/Wind Harmer
-0.001
207522AF2-254 C
Solar/Wind Harmer
0.063
207500AE2-000G1
Solar/Wind Harmer
24.509
207497AE2-000G2
Solar/Wind Harmer
24.509
207507AE2-000G3
Solar/Wind Harmer
24.509
207487AE2-000G4
Solar/Wind Harmer
24.509
970025AG2-016 GEN
Solar/Wind Harmer
0.124
971189AH1-054 GEN
Solar/Wind Harmer
0.051
971667AH1-334 GEN
Solar/Wind Harmer
0.12
219727YARDVSOLFA C
Solar/Wind Harmer
0
219276PARKLANDSO C
Solar/Wind Harmer
0
219817TRENTONSOL C
Solar/Wind Harmer
0
219620RIDERU C
Solar/Wind Harmer
-0.001
20714328BYD_X4-031
Solar/Wind Harmer
0.012
20714428HOW_X1-037
Solar/Wind Harmer
0
20720628TIN_W1-124
Solar/Wind Harmer
-0.001
219918AC2-009 C
Solar/Wind Harmer
0
20742028HF_AC1-207
Solar/Wind Harmer
-0.001
971521AH1-258 GEN
Solar/Wind Harmer
0.117
967451AG2-055 C O1
Solar/Wind Harmer
133.726
219612MATRIX C
Solar/Wind Harmer
0
218438BLK ROCK C
Solar/Wind Harmer
0
218526CNTRALGAS2 C
Solar/Wind Harmer
0
218524CNTRALGAS1 C
Solar/Wind Harmer
0
218428ETC SOLAR C
Solar/Wind Harmer
0
217213AMBOY SO C
Solar/Wind Harmer
-0.001
219249CENTRALDIV C
Solar/Wind Harmer
0
20673828FLE_V3-070
Solar/Wind Harmer
0.043
20675428EAM_W2-061
Solar/Wind Harmer
0
218449LINSOLAR C
Solar/Wind Harmer
0
217081WEATEXAS C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
217206BARNGR HS C
Solar/Wind Harmer
0
217208PARK ELE C
Solar/Wind Harmer
0
207439AE1-081 C O1
Solar/Wind Harmer
0
20676328BVR_Y1-020
Solar/Wind Harmer
0
20674628WNG_W3-110
Solar/Wind Harmer
-0.001
207511W3-106 GEN
Solar/Wind Harmer
0.028
971007AG2-625 GEN
Solar/Wind Harmer
0.109
971009AG2-626 GEN
Solar/Wind Harmer
0.07
971519AH1-257 GEN
Solar/Wind Harmer
0.107
207437AD2-070 GEN
Solar/Wind Harmer
-0.001
966181AG1-487 GEN
Solar/Wind Harmer
0
966181AG1-487 GEN
Solar/Wind Harmer
2.107
966111AG1-480 GEN
Solar/Wind Harmer
0
966111AG1-480 GEN
Solar/Wind Harmer
1.86
970095AG2-074 GEN
Solar/Wind Harmer
0.193
208972BECR K09
Solar/Wind Harmer
1.42
227287AC2-120 GEN
Solar/Wind Helper
0.173
226910AB2-157 C
Solar/Wind Helper
0.016
226929AD2-058 GEN
Solar/Wind Helper
0.035
G-007ALTFEXP_G-007A->PJM
CMTX
28.707
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.778
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.169
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
12.429
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
2.594
BlueGrassPJM->LTFIMP_BlueG
CLTF
8.09
CBM NorthLTFEXP_CBM-N->PJM
CBM
43.729
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
75.481

Details for CNASTONE-BRIGHTON 500.0 kV Ckt 1 line l/o PJM_500_BG_P2_CNSTN_230-N_SRT-A


Base Case Flowgate

Area:PJM
Facility Description:
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
Contingency Name:
PJM_500_BG_P2_CNSTN_230-N_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:101.12 %
Rating:3507.0 MVA
Rating Type:B
MVA to Mitigate:3546.33
MW Contribution:0.26
Bus #Bus NameTypeMW Contribution
972281AH1-725 GEN
50/50
122.056
200202DELTA2 ST
50/50
3.78
200200DELTA2 CT1
50/50
2.116
200201DELTA2 CT2
50/50
2.116
200195DELTA ST
50/50
1.87
200192DELTA CT1
50/50
1.122
200193DELTA CT2
50/50
1.122
200194DELTA CT3
50/50
1.122
200034PCHBTM 2
50/50
74.102
200061HUNTR401
50/50
2.849
200058HUNTR101
50/50
1.491
200059HUNTR201
50/50
1.491
200060HUNTR301
50/50
1.491
200035PCHBTM 3
50/50
12.015
200203Y1-065-STG
50/50
4.274
200204Y1-065-CTG1
50/50
2.691
200205Y1-065-CTG2
50/50
2.691
200052ROCKSP 1
50/50
31.93
200053ROCKSP 2
50/50
31.93
200054ROCKSP 3
50/50
31.606
200055ROCKSP 4
50/50
31.606
233987AB2-037 GEN
Solar/Wind Harmer
0
971149AH1-027 GEN
Solar/Wind Harmer
0.177
233972AC1-094 C
Solar/Wind Harmer
-0.001
970695AG2-447 GEN
Solar/Wind Harmer
0.142
234033AF1-007_GEN
Solar/Wind Harmer
14.812
970545AG2-347 GEN
Solar/Wind Harmer
61.014
972133AH1-634 GEN
Solar/Wind Harmer
9.245
233923SMA
Solar/Wind Harmer
-0.001
233998TM1NIN_3.36
Solar/Wind Harmer
-0.001
233997TMININ_4.2
Solar/Wind Harmer
-0.001
233996TM1833_GEN
Solar/Wind Harmer
-0.001
972069AH1-584 GEN
Solar/Wind Harmer
0.354
972071AH1-585 GEN
Solar/Wind Harmer
0.354
972073AH1-586 GEN
Solar/Wind Harmer
6.372
971747AH1-380 GEN
Solar/Wind Harmer
0.142
233990AG1-397 GEN
Solar/Wind Harmer
0
233940AF2-379 C
Solar/Wind Harmer
-0.001
233990AG1-397 GEN
Solar/Wind Harmer
1.133
234015AF2-250 C
Solar/Wind Harmer
0
972177AH1-672 GEN
Solar/Wind Harmer
0.531
971195AH1-057 GEN
Solar/Wind Harmer
0.051
960671AF2-358 GEN
Solar/Wind Harmer
0.708
965821AG1-450 GEN
Solar/Wind Harmer
3.538
232426Y1-080 FULL
Solar/Wind Harmer
0
970277AG2-181 GEN
Solar/Wind Harmer
0.198
233946AB2-136 GEN
Solar/Wind Harmer
-0.001
233964AF2-378 GEN
Solar/Wind Harmer
0
234041AC1-190 GEN
Solar/Wind Harmer
0.354
233984AB2-036 GEN
Solar/Wind Harmer
0.648
233968AD2-076_GEN
Solar/Wind Harmer
0.344
234014AF1-036_GEN
Solar/Wind Harmer
0.141
970597AG2-380 GEN
Solar/Wind Harmer
2.811
234012AE2-112_GEN
Solar/Wind Harmer
0.119
971983AH1-536 GEN
Solar/Wind Harmer
0.293
970453AG2-297 GEN
Solar/Wind Harmer
0.126
971553AH1-274 GEN
Solar/Wind Harmer
0.11
945431AF1-208 GEN
Solar/Wind Harmer
0.297
970997AG2-616 GEN
Solar/Wind Harmer
0.329
972141AH1-641 GEN
Solar/Wind Harmer
0.099
230430AE1-229_GEN
Solar/Wind Harmer
-0.001
230422AE1-104_GEN1
Solar/Wind Harmer
27.263
230425AE1-104_GEN2
Solar/Wind Harmer
27.263
228351V2-046C
Solar/Wind Harmer
-0.001
230433AD2-135 GEN
Solar/Wind Harmer
0
971011AG2-627 GEN
Solar/Wind Harmer
0.262
971535AH1-265 GEN
Solar/Wind Harmer
0.193
230407AD2-065 C
Solar/Wind Harmer
0
228754AB1-001 C
Solar/Wind Harmer
-0.001
219137THOSOLAR C
Solar/Wind Harmer
0
219623KINSLEYBEA C
Solar/Wind Harmer
-0.001
219258KINSLEYDEP C
Solar/Wind Harmer
0
219766PARADISE C
Solar/Wind Harmer
-0.001
218660EHAMPSOLAR C
Solar/Wind Harmer
-0.001
219907AC1-030 C
Solar/Wind Harmer
-0.001
219236SOUTHERNHQ C
Solar/Wind Harmer
0
219906AC1-017 C
Solar/Wind Harmer
-0.001
219615MILLCREEK C
Solar/Wind Harmer
-0.001
214067T20SOLAR
Solar/Wind Harmer
-0.001
207522AF2-254 C
Solar/Wind Harmer
0.063
207500AE2-000G1
Solar/Wind Harmer
24.508
207497AE2-000G2
Solar/Wind Harmer
24.508
207507AE2-000G3
Solar/Wind Harmer
24.508
207487AE2-000G4
Solar/Wind Harmer
24.508
970025AG2-016 GEN
Solar/Wind Harmer
0.124
971189AH1-054 GEN
Solar/Wind Harmer
0.051
971667AH1-334 GEN
Solar/Wind Harmer
0.12
219727YARDVSOLFA C
Solar/Wind Harmer
0
219276PARKLANDSO C
Solar/Wind Harmer
0
219817TRENTONSOL C
Solar/Wind Harmer
0
219620RIDERU C
Solar/Wind Harmer
-0.001
20714328BYD_X4-031
Solar/Wind Harmer
0.012
20714428HOW_X1-037
Solar/Wind Harmer
0
20720628TIN_W1-124
Solar/Wind Harmer
-0.001
219918AC2-009 C
Solar/Wind Harmer
0
20742028HF_AC1-207
Solar/Wind Harmer
-0.001
971521AH1-258 GEN
Solar/Wind Harmer
0.117
967451AG2-055 C O1
Solar/Wind Harmer
133.717
219612MATRIX C
Solar/Wind Harmer
0
218438BLK ROCK C
Solar/Wind Harmer
0
218526CNTRALGAS2 C
Solar/Wind Harmer
0
218524CNTRALGAS1 C
Solar/Wind Harmer
0
218428ETC SOLAR C
Solar/Wind Harmer
0
217213AMBOY SO C
Solar/Wind Harmer
-0.001
219249CENTRALDIV C
Solar/Wind Harmer
0
20673828FLE_V3-070
Solar/Wind Harmer
0.043
20675428EAM_W2-061
Solar/Wind Harmer
0
218449LINSOLAR C
Solar/Wind Harmer
0
217081WEATEXAS C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
217206BARNGR HS C
Solar/Wind Harmer
0
217208PARK ELE C
Solar/Wind Harmer
0
207439AE1-081 C O1
Solar/Wind Harmer
0
20676328BVR_Y1-020
Solar/Wind Harmer
0
20674628WNG_W3-110
Solar/Wind Harmer
-0.001
207511W3-106 GEN
Solar/Wind Harmer
0.028
971009AG2-626 GEN
Solar/Wind Harmer
0.07
971007AG2-625 GEN
Solar/Wind Harmer
0.109
971519AH1-257 GEN
Solar/Wind Harmer
0.107
207437AD2-070 GEN
Solar/Wind Harmer
-0.001
966181AG1-487 GEN
Solar/Wind Harmer
0
966181AG1-487 GEN
Solar/Wind Harmer
2.107
966111AG1-480 GEN
Solar/Wind Harmer
0
966111AG1-480 GEN
Solar/Wind Harmer
1.86
970095AG2-074 GEN
Solar/Wind Harmer
0.193
208972BECR K09
Solar/Wind Harmer
1.42
227287AC2-120 GEN
Solar/Wind Helper
0.173
226910AB2-157 C
Solar/Wind Helper
0.016
226929AD2-058 GEN
Solar/Wind Helper
0.035
G-007ALTFEXP_G-007A->PJM
CMTX
28.705
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.778
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.169
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
12.429
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
2.594
BlueGrassPJM->LTFIMP_BlueG
CLTF
8.09
CBM NorthLTFEXP_CBM-N->PJM
CBM
43.726
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
75.477

Details for COOPER-GRACETON 230.0 kV Ckt 1 line l/o PECO_P1-2_5012_SRT-A


Base Case Flowgate

Area:BGE/PECO
Facility Description:
COOPER-GRACETON 230.0 kV Ckt 1 line
Contingency Name:
PECO_P1-2_5012_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:141.29 %
Rating:639.0 MVA
Rating Type:B
MVA to Mitigate:902.85
MW Contribution:0.13
Bus #Bus NameTypeMW Contribution
213508CON10-11
50/50
0.991
213508CON10-11
50/50
0.991
213518CONOW8-9
50/50
0.991
213518CONOW8-9
50/50
0.991
213515CONOW3-4
50/50
1.041
213517CONOW7
50/50
1.041
213515CONOW3-4
50/50
0.949
213516CONOW5-6
50/50
0.949
213514CONOW1-2
50/50
0.778
213516CONOW5-6
50/50
0.778
213514CONOW1-2
50/50
0.739
231918WEST 1
50/50
0.098
213893PHLISST1
50/50
1.432
213890PHLISCT3
50/50
0.992
213888PHLISCT1
50/50
0.992
213889PHLISCT2
50/50
0.992
231909HR2
50/50
0.598
231916EM3
50/50
0.412
231917EM10
50/50
0.087
231919CHRIST1
50/50
2.327
231920CHRIST2
50/50
2.327
231901EM4
50/50
0.829
231908HR1
50/50
0.595
231910HR3
50/50
0.595
213740LIBE_ST1
50/50
1.193
213738LIBE_CT1
50/50
0.916
213739LIBE_CT2
50/50
0.916
231505HR4
50/50
0.934
971983AH1-536 GEN
Solar/Wind Harmer
0.175
233968AD2-076_GEN
Solar/Wind Harmer
0.2
234014AF1-036_GEN
Solar/Wind Harmer
0.082
970597AG2-380 GEN
Solar/Wind Harmer
1.636
234012AE2-112_GEN
Solar/Wind Harmer
0.07
233984AB2-036 GEN
Solar/Wind Harmer
0.367
234041AC1-190 GEN
Solar/Wind Harmer
0.188
233987AB2-037 GEN
Solar/Wind Harmer
0
233964AF2-378 GEN
Solar/Wind Harmer
0
233946AB2-136 GEN
Solar/Wind Harmer
0
232426Y1-080 FULL
Solar/Wind Harmer
0
970277AG2-181 GEN
Solar/Wind Harmer
0.105
960671AF2-358 GEN
Solar/Wind Harmer
0.374
965821AG1-450 GEN
Solar/Wind Harmer
1.869
233940AF2-379 C
Solar/Wind Harmer
0
234015AF2-250 C
Solar/Wind Harmer
0
971195AH1-057 GEN
Solar/Wind Harmer
0.027
233923SMA
Solar/Wind Harmer
0
233998TM1NIN_3.36
Solar/Wind Harmer
0
233997TMININ_4.2
Solar/Wind Harmer
0
233996TM1833_GEN
Solar/Wind Harmer
0
233990AG1-397 GEN
Solar/Wind Harmer
0
971747AH1-380 GEN
Solar/Wind Harmer
0.074
233990AG1-397 GEN
Solar/Wind Harmer
0.59
972069AH1-584 GEN
Solar/Wind Harmer
0.184
972071AH1-585 GEN
Solar/Wind Harmer
0.184
972073AH1-586 GEN
Solar/Wind Harmer
3.315
234033AF1-007_GEN
Solar/Wind Harmer
7.648
970545AG2-347 GEN
Solar/Wind Harmer
31.505
972133AH1-634 GEN
Solar/Wind Harmer
4.773
972177AH1-672 GEN
Solar/Wind Harmer
0.274
971149AH1-027 GEN
Solar/Wind Harmer
0.089
233972AC1-094 C
Solar/Wind Harmer
0
970695AG2-447 GEN
Solar/Wind Harmer
0.07
219137THOSOLAR C
Solar/Wind Harmer
0
219258KINSLEYDEP C
Solar/Wind Harmer
0
219766PARADISE C
Solar/Wind Harmer
0
219623KINSLEYBEA C
Solar/Wind Harmer
0
971011AG2-627 GEN
Solar/Wind Harmer
0.131
219907AC1-030 C
Solar/Wind Harmer
0
228351V2-046C
Solar/Wind Harmer
0
219236SOUTHERNHQ C
Solar/Wind Harmer
0
970997AG2-616 GEN
Solar/Wind Harmer
0.162
972141AH1-641 GEN
Solar/Wind Harmer
0.049
230430AE1-229_GEN
Solar/Wind Harmer
0
945431AF1-208 GEN
Solar/Wind Harmer
0.145
219906AC1-017 C
Solar/Wind Harmer
0
219615MILLCREEK C
Solar/Wind Harmer
0
971535AH1-265 GEN
Solar/Wind Harmer
0.094
971553AH1-274 GEN
Solar/Wind Harmer
0.053
230433AD2-135 GEN
Solar/Wind Harmer
0
230407AD2-065 C
Solar/Wind Harmer
0
970453AG2-297 GEN
Solar/Wind Harmer
0.06
218660EHAMPSOLAR C
Solar/Wind Harmer
0
230422AE1-104_GEN1
Solar/Wind Harmer
12.966
230425AE1-104_GEN2
Solar/Wind Harmer
12.966
228754AB1-001 C
Solar/Wind Harmer
0
214067T20SOLAR
Solar/Wind Harmer
0
219727YARDVSOLFA C
Solar/Wind Harmer
0
207522AF2-254 C
Solar/Wind Harmer
0.029
207500AE2-000G1
Solar/Wind Harmer
11.012
207497AE2-000G2
Solar/Wind Harmer
11.012
207507AE2-000G3
Solar/Wind Harmer
11.012
207487AE2-000G4
Solar/Wind Harmer
11.012
971189AH1-054 GEN
Solar/Wind Harmer
0.023
219276PARKLANDSO C
Solar/Wind Harmer
0
970025AG2-016 GEN
Solar/Wind Harmer
0.055
971667AH1-334 GEN
Solar/Wind Harmer
0.053
219620RIDERU C
Solar/Wind Harmer
0
219817TRENTONSOL C
Solar/Wind Harmer
0
219918AC2-009 C
Solar/Wind Harmer
0
20714328BYD_X4-031
Solar/Wind Harmer
0.005
20714428HOW_X1-037
Solar/Wind Harmer
0
20720628TIN_W1-124
Solar/Wind Harmer
0
219612MATRIX C
Solar/Wind Harmer
0
218438BLK ROCK C
Solar/Wind Harmer
0
20742028HF_AC1-207
Solar/Wind Harmer
0
971521AH1-258 GEN
Solar/Wind Harmer
0.05
967451AG2-055 C O1
Solar/Wind Harmer
56.631
218526CNTRALGAS2 C
Solar/Wind Harmer
0
223401AF1-299 GEN
Solar/Wind Helper
0.063
223402AF1-300 C
Solar/Wind Helper
0.063
208923BUSO V4-027
Solar/Wind Helper
0.015
G-007ALTFEXP_G-007A->PJM
CMTX
12.048
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.129
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.666
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.379
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.931
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.9
CBM NorthLTFEXP_CBM-N->PJM
CBM
15.238
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
30.513

Details for COOPER-GRACETON 230.0 kV Ckt 1 line l/o PECO_P4_PEACH235_SRT-A/* $ CHESCO $ PECO_P4_PEACH235 $ STBK


Base Case Flowgate

Area:BGE/PECO
Facility Description:
COOPER-GRACETON 230.0 kV Ckt 1 line
Contingency Name:
PECO_P4_PEACH235_SRT-A/* $ CHESCO $ PECO_P4_PEACH235 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:138.68 %
Rating:639.0 MVA
Rating Type:B
MVA to Mitigate:886.19
MW Contribution:0.13
Bus #Bus NameTypeMW Contribution
213508CON10-11
50/50
0.991
213508CON10-11
50/50
0.991
213518CONOW8-9
50/50
0.991
213518CONOW8-9
50/50
0.991
213515CONOW3-4
50/50
1.041
213517CONOW7
50/50
1.041
213515CONOW3-4
50/50
0.949
213516CONOW5-6
50/50
0.949
213514CONOW1-2
50/50
0.778
213516CONOW5-6
50/50
0.778
213514CONOW1-2
50/50
0.739
971983AH1-536 GEN
Solar/Wind Harmer
0.175
233968AD2-076_GEN
Solar/Wind Harmer
0.201
234014AF1-036_GEN
Solar/Wind Harmer
0.082
970597AG2-380 GEN
Solar/Wind Harmer
1.637
234012AE2-112_GEN
Solar/Wind Harmer
0.07
233984AB2-036 GEN
Solar/Wind Harmer
0.367
234041AC1-190 GEN
Solar/Wind Harmer
0.188
233987AB2-037 GEN
Solar/Wind Harmer
0
233964AF2-378 GEN
Solar/Wind Harmer
0
233946AB2-136 GEN
Solar/Wind Harmer
0
232426Y1-080 FULL
Solar/Wind Harmer
0
970277AG2-181 GEN
Solar/Wind Harmer
0.105
960671AF2-358 GEN
Solar/Wind Harmer
0.374
965821AG1-450 GEN
Solar/Wind Harmer
1.87
233940AF2-379 C
Solar/Wind Harmer
0
234015AF2-250 C
Solar/Wind Harmer
0
971195AH1-057 GEN
Solar/Wind Harmer
0.027
233923SMA
Solar/Wind Harmer
0
233998TM1NIN_3.36
Solar/Wind Harmer
0
233997TMININ_4.2
Solar/Wind Harmer
0
233996TM1833_GEN
Solar/Wind Harmer
0
233990AG1-397 GEN
Solar/Wind Harmer
0
971747AH1-380 GEN
Solar/Wind Harmer
0.074
233990AG1-397 GEN
Solar/Wind Harmer
0.59
972069AH1-584 GEN
Solar/Wind Harmer
0.184
972071AH1-585 GEN
Solar/Wind Harmer
0.184
972073AH1-586 GEN
Solar/Wind Harmer
3.317
234033AF1-007_GEN
Solar/Wind Harmer
7.652
970545AG2-347 GEN
Solar/Wind Harmer
31.523
972133AH1-634 GEN
Solar/Wind Harmer
4.776
972177AH1-672 GEN
Solar/Wind Harmer
0.274
971149AH1-027 GEN
Solar/Wind Harmer
0.089
233972AC1-094 C
Solar/Wind Harmer
0
970695AG2-447 GEN
Solar/Wind Harmer
0.07
219137THOSOLAR C
Solar/Wind Harmer
0
219258KINSLEYDEP C
Solar/Wind Harmer
0
219766PARADISE C
Solar/Wind Harmer
0
219623KINSLEYBEA C
Solar/Wind Harmer
0
971011AG2-627 GEN
Solar/Wind Harmer
0.132
219907AC1-030 C
Solar/Wind Harmer
0
228351V2-046C
Solar/Wind Harmer
0
219236SOUTHERNHQ C
Solar/Wind Harmer
0
970997AG2-616 GEN
Solar/Wind Harmer
0.162
972141AH1-641 GEN
Solar/Wind Harmer
0.049
230430AE1-229_GEN
Solar/Wind Harmer
0
945431AF1-208 GEN
Solar/Wind Harmer
0.145
219906AC1-017 C
Solar/Wind Harmer
0
219615MILLCREEK C
Solar/Wind Harmer
0
971535AH1-265 GEN
Solar/Wind Harmer
0.094
971553AH1-274 GEN
Solar/Wind Harmer
0.053
230433AD2-135 GEN
Solar/Wind Harmer
0
230407AD2-065 C
Solar/Wind Harmer
0
970453AG2-297 GEN
Solar/Wind Harmer
0.06
218660EHAMPSOLAR C
Solar/Wind Harmer
0
230422AE1-104_GEN1
Solar/Wind Harmer
12.971
230425AE1-104_GEN2
Solar/Wind Harmer
12.971
228754AB1-001 C
Solar/Wind Harmer
0
214067T20SOLAR
Solar/Wind Harmer
0
219727YARDVSOLFA C
Solar/Wind Harmer
0
207522AF2-254 C
Solar/Wind Harmer
0.029
207500AE2-000G1
Solar/Wind Harmer
11.015
207497AE2-000G2
Solar/Wind Harmer
11.015
207507AE2-000G3
Solar/Wind Harmer
11.015
207487AE2-000G4
Solar/Wind Harmer
11.015
971189AH1-054 GEN
Solar/Wind Harmer
0.023
219276PARKLANDSO C
Solar/Wind Harmer
0
970025AG2-016 GEN
Solar/Wind Harmer
0.055
971667AH1-334 GEN
Solar/Wind Harmer
0.053
219817TRENTONSOL C
Solar/Wind Harmer
0
219620RIDERU C
Solar/Wind Harmer
0
219918AC2-009 C
Solar/Wind Harmer
0
20714328BYD_X4-031
Solar/Wind Harmer
0.005
20714428HOW_X1-037
Solar/Wind Harmer
0
20720628TIN_W1-124
Solar/Wind Harmer
0
219612MATRIX C
Solar/Wind Harmer
0
218438BLK ROCK C
Solar/Wind Harmer
0
20742028HF_AC1-207
Solar/Wind Harmer
0
971521AH1-258 GEN
Solar/Wind Harmer
0.05
967451AG2-055 C O1
Solar/Wind Harmer
56.646
218526CNTRALGAS2 C
Solar/Wind Harmer
0
223401AF1-299 GEN
Solar/Wind Helper
0.063
223402AF1-300 C
Solar/Wind Helper
0.063
208923BUSO V4-027
Solar/Wind Helper
0.015
G-007ALTFEXP_G-007A->PJM
CMTX
12.051
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.129
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.666
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.38
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.931
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.901
CBM NorthLTFEXP_CBM-N->PJM
CBM
15.241
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
30.52

Details for COOPER-GRACETON 230.0 kV Ckt 1 line l/o PJM_500_BG_P4_5_CNSTN_C_SRT-A


Base Case Flowgate

Area:BGE/PECO
Facility Description:
COOPER-GRACETON 230.0 kV Ckt 1 line
Contingency Name:
PJM_500_BG_P4_5_CNSTN_C_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:138.68 %
Rating:639.0 MVA
Rating Type:B
MVA to Mitigate:886.16
MW Contribution:0.13
Bus #Bus NameTypeMW Contribution
213508CON10-11
50/50
0.991
213508CON10-11
50/50
0.991
213518CONOW8-9
50/50
0.991
213518CONOW8-9
50/50
0.991
213515CONOW3-4
50/50
1.041
213517CONOW7
50/50
1.041
213515CONOW3-4
50/50
0.949
213516CONOW5-6
50/50
0.949
213514CONOW1-2
50/50
0.778
213516CONOW5-6
50/50
0.778
213514CONOW1-2
50/50
0.739
971983AH1-536 GEN
Solar/Wind Harmer
0.175
233968AD2-076_GEN
Solar/Wind Harmer
0.2
234014AF1-036_GEN
Solar/Wind Harmer
0.082
970597AG2-380 GEN
Solar/Wind Harmer
1.636
234012AE2-112_GEN
Solar/Wind Harmer
0.07
233984AB2-036 GEN
Solar/Wind Harmer
0.367
234041AC1-190 GEN
Solar/Wind Harmer
0.188
233987AB2-037 GEN
Solar/Wind Harmer
0
233964AF2-378 GEN
Solar/Wind Harmer
0
233946AB2-136 GEN
Solar/Wind Harmer
0
232426Y1-080 FULL
Solar/Wind Harmer
0
970277AG2-181 GEN
Solar/Wind Harmer
0.105
960671AF2-358 GEN
Solar/Wind Harmer
0.374
965821AG1-450 GEN
Solar/Wind Harmer
1.869
233940AF2-379 C
Solar/Wind Harmer
0
234015AF2-250 C
Solar/Wind Harmer
0
971195AH1-057 GEN
Solar/Wind Harmer
0.027
233923SMA
Solar/Wind Harmer
0
233998TM1NIN_3.36
Solar/Wind Harmer
0
233997TMININ_4.2
Solar/Wind Harmer
0
233996TM1833_GEN
Solar/Wind Harmer
0
233990AG1-397 GEN
Solar/Wind Harmer
0
971747AH1-380 GEN
Solar/Wind Harmer
0.074
233990AG1-397 GEN
Solar/Wind Harmer
0.59
972069AH1-584 GEN
Solar/Wind Harmer
0.184
972071AH1-585 GEN
Solar/Wind Harmer
0.184
972073AH1-586 GEN
Solar/Wind Harmer
3.315
234033AF1-007_GEN
Solar/Wind Harmer
7.648
970545AG2-347 GEN
Solar/Wind Harmer
31.505
972133AH1-634 GEN
Solar/Wind Harmer
4.773
972177AH1-672 GEN
Solar/Wind Harmer
0.274
971149AH1-027 GEN
Solar/Wind Harmer
0.089
233972AC1-094 C
Solar/Wind Harmer
0
970695AG2-447 GEN
Solar/Wind Harmer
0.07
219137THOSOLAR C
Solar/Wind Harmer
0
219258KINSLEYDEP C
Solar/Wind Harmer
0
219766PARADISE C
Solar/Wind Harmer
0
219623KINSLEYBEA C
Solar/Wind Harmer
0
971011AG2-627 GEN
Solar/Wind Harmer
0.131
219907AC1-030 C
Solar/Wind Harmer
0
228351V2-046C
Solar/Wind Harmer
0
219236SOUTHERNHQ C
Solar/Wind Harmer
0
970997AG2-616 GEN
Solar/Wind Harmer
0.162
972141AH1-641 GEN
Solar/Wind Harmer
0.049
230430AE1-229_GEN
Solar/Wind Harmer
0
945431AF1-208 GEN
Solar/Wind Harmer
0.145
219906AC1-017 C
Solar/Wind Harmer
0
219615MILLCREEK C
Solar/Wind Harmer
0
971535AH1-265 GEN
Solar/Wind Harmer
0.094
971553AH1-274 GEN
Solar/Wind Harmer
0.053
230433AD2-135 GEN
Solar/Wind Harmer
0
230407AD2-065 C
Solar/Wind Harmer
0
970453AG2-297 GEN
Solar/Wind Harmer
0.06
218660EHAMPSOLAR C
Solar/Wind Harmer
0
230422AE1-104_GEN1
Solar/Wind Harmer
12.966
230425AE1-104_GEN2
Solar/Wind Harmer
12.966
228754AB1-001 C
Solar/Wind Harmer
0
214067T20SOLAR
Solar/Wind Harmer
0
219727YARDVSOLFA C
Solar/Wind Harmer
0
207522AF2-254 C
Solar/Wind Harmer
0.029
207500AE2-000G1
Solar/Wind Harmer
11.012
207497AE2-000G2
Solar/Wind Harmer
11.012
207507AE2-000G3
Solar/Wind Harmer
11.012
207487AE2-000G4
Solar/Wind Harmer
11.012
971189AH1-054 GEN
Solar/Wind Harmer
0.023
219276PARKLANDSO C
Solar/Wind Harmer
0
970025AG2-016 GEN
Solar/Wind Harmer
0.055
971667AH1-334 GEN
Solar/Wind Harmer
0.053
219620RIDERU C
Solar/Wind Harmer
0
219817TRENTONSOL C
Solar/Wind Harmer
0
219918AC2-009 C
Solar/Wind Harmer
0
20714328BYD_X4-031
Solar/Wind Harmer
0.005
20714428HOW_X1-037
Solar/Wind Harmer
0
20720628TIN_W1-124
Solar/Wind Harmer
0
219612MATRIX C
Solar/Wind Harmer
0
218438BLK ROCK C
Solar/Wind Harmer
0
20742028HF_AC1-207
Solar/Wind Harmer
0
971521AH1-258 GEN
Solar/Wind Harmer
0.05
967451AG2-055 C O1
Solar/Wind Harmer
56.631
218526CNTRALGAS2 C
Solar/Wind Harmer
0
223401AF1-299 GEN
Solar/Wind Helper
0.063
223402AF1-300 C
Solar/Wind Helper
0.063
208923BUSO V4-027
Solar/Wind Helper
0.015
G-007ALTFEXP_G-007A->PJM
CMTX
12.048
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.129
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.666
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.379
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.931
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.9
CBM NorthLTFEXP_CBM-N->PJM
CBM
15.238
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
30.513

Details for COOPER-GRACETON 230.0 kV Ckt 1 line l/o PECO_P1-2_5014_SRT-A/* $ CHESCO $ PECO_P1-2_5012 $ L


Base Case Flowgate

Area:BGE/PECO
Facility Description:
COOPER-GRACETON 230.0 kV Ckt 1 line
Contingency Name:
PECO_P1-2_5014_SRT-A/* $ CHESCO $ PECO_P1-2_5012 $ L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.86 %
Rating:639.0 MVA
Rating Type:B
MVA to Mitigate:663.67
MW Contribution:0.13
Bus #Bus NameTypeMW Contribution
213508CON10-11
50/50
0.988
213508CON10-11
50/50
0.988
213518CONOW8-9
50/50
0.988
213518CONOW8-9
50/50
0.988
213515CONOW3-4
50/50
1.038
213517CONOW7
50/50
1.038
213515CONOW3-4
50/50
0.946
213516CONOW5-6
50/50
0.946
213514CONOW1-2
50/50
0.776
213516CONOW5-6
50/50
0.776
213514CONOW1-2
50/50
0.737
970431AG2-281 GEN
50/50
4.747
231918WEST 1
50/50
0.104
232416X2-083
50/50
0.015
231919CHRIST1
50/50
2.482
231920CHRIST2
50/50
2.482
231909HR2
50/50
0.632
231916EM3
50/50
0.435
231917EM10
50/50
0.092
231901EM4
50/50
0.877
231908HR1
50/50
0.629
231910HR3
50/50
0.629
231902DC CT7
50/50
0.443
231915DC CT6
50/50
0.443
231906DC3 NUG
50/50
0.355
231907DC10
50/50
0.115
231131BLOOM ENRGY
50/50
0.122
231505HR4
50/50
0.951
971983AH1-536 GEN
Solar/Wind Harmer
0.195
233968AD2-076_GEN
Solar/Wind Harmer
0.224
234014AF1-036_GEN
Solar/Wind Harmer
0.092
970597AG2-380 GEN
Solar/Wind Harmer
1.831
234012AE2-112_GEN
Solar/Wind Harmer
0.078
233984AB2-036 GEN
Solar/Wind Harmer
0.412
234041AC1-190 GEN
Solar/Wind Harmer
0.214
233987AB2-037 GEN
Solar/Wind Harmer
0
233964AF2-378 GEN
Solar/Wind Harmer
0
233946AB2-136 GEN
Solar/Wind Harmer
0
232426Y1-080 FULL
Solar/Wind Harmer
0
970277AG2-181 GEN
Solar/Wind Harmer
0.119
960671AF2-358 GEN
Solar/Wind Harmer
0.425
965821AG1-450 GEN
Solar/Wind Harmer
2.125
233940AF2-379 C
Solar/Wind Harmer
0
234015AF2-250 C
Solar/Wind Harmer
0
971195AH1-057 GEN
Solar/Wind Harmer
0.03
233923SMA
Solar/Wind Harmer
0
233998TM1NIN_3.36
Solar/Wind Harmer
0
233997TMININ_4.2
Solar/Wind Harmer
0
233996TM1833_GEN
Solar/Wind Harmer
0
971747AH1-380 GEN
Solar/Wind Harmer
0.084
233990AG1-397 GEN
Solar/Wind Harmer
0
233990AG1-397 GEN
Solar/Wind Harmer
0.672
972069AH1-584 GEN
Solar/Wind Harmer
0.21
972071AH1-585 GEN
Solar/Wind Harmer
0.21
972073AH1-586 GEN
Solar/Wind Harmer
3.778
234033AF1-007_GEN
Solar/Wind Harmer
8.724
970545AG2-347 GEN
Solar/Wind Harmer
35.936
972133AH1-634 GEN
Solar/Wind Harmer
5.445
972177AH1-672 GEN
Solar/Wind Harmer
0.312
971149AH1-027 GEN
Solar/Wind Harmer
0.102
233972AC1-094 C
Solar/Wind Harmer
0
970695AG2-447 GEN
Solar/Wind Harmer
0.081
971011AG2-627 GEN
Solar/Wind Harmer
0.13
228351V2-046C
Solar/Wind Harmer
0
970997AG2-616 GEN
Solar/Wind Harmer
0.162
972141AH1-641 GEN
Solar/Wind Harmer
0.049
945431AF1-208 GEN
Solar/Wind Harmer
0.146
230430AE1-229_GEN
Solar/Wind Harmer
0
219137THOSOLAR C
Solar/Wind Harmer
0
970453AG2-297 GEN
Solar/Wind Harmer
0.061
971553AH1-274 GEN
Solar/Wind Harmer
0.054
219258KINSLEYDEP C
Solar/Wind Harmer
0
230433AD2-135 GEN
Solar/Wind Harmer
0
971535AH1-265 GEN
Solar/Wind Harmer
0.094
230407AD2-065 C
Solar/Wind Harmer
0
219623KINSLEYBEA C
Solar/Wind Harmer
0
230422AE1-104_GEN1
Solar/Wind Harmer
13.092
230425AE1-104_GEN2
Solar/Wind Harmer
13.092
219766PARADISE C
Solar/Wind Harmer
0
228754AB1-001 C
Solar/Wind Harmer
0
219907AC1-030 C
Solar/Wind Harmer
0
219236SOUTHERNHQ C
Solar/Wind Harmer
0
218660EHAMPSOLAR C
Solar/Wind Harmer
0
219906AC1-017 C
Solar/Wind Harmer
0
219615MILLCREEK C
Solar/Wind Harmer
0
214067T20SOLAR
Solar/Wind Harmer
0
207522AF2-254 C
Solar/Wind Harmer
0.027
207500AE2-000G1
Solar/Wind Harmer
10.314
207497AE2-000G2
Solar/Wind Harmer
10.314
207507AE2-000G3
Solar/Wind Harmer
10.314
207487AE2-000G4
Solar/Wind Harmer
10.314
970025AG2-016 GEN
Solar/Wind Harmer
0.052
971189AH1-054 GEN
Solar/Wind Harmer
0.021
219727YARDVSOLFA C
Solar/Wind Harmer
0
971667AH1-334 GEN
Solar/Wind Harmer
0.049
219276PARKLANDSO C
Solar/Wind Harmer
0
967451AG2-055 C O1
Solar/Wind Harmer
50.18
223401AF1-299 GEN
Solar/Wind Helper
0.053
223402AF1-300 C
Solar/Wind Helper
0.053
208923BUSO V4-027
Solar/Wind Helper
0.013
G-007ALTFEXP_G-007A->PJM
CMTX
10.511
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.959
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.567
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
3.752
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.798
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.487
CBM NorthLTFEXP_CBM-N->PJM
CBM
12.425
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
25.801

Details for HOPE CREEK-SILVER RUN 230.0 kV Ckt 1 line l/o PJM500_PS_P1-2_5015_SRT-A


Base Case Flowgate

Area:PJM
Facility Description:
HOPE CREEK-SILVER RUN 230.0 kV Ckt 1 line
Contingency Name:
PJM500_PS_P1-2_5015_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:109.26 %
Rating:1150.0 MVA
Rating Type:B
MVA to Mitigate:1256.45
MW Contribution:0.26
Bus #Bus NameTypeMW Contribution
200039HOPE CG1
50/50
24.45
200036SALEM-G1
50/50
17.72
200037SALEM-G2
50/50
17.593
972251AH1-710 GEN
50/50
64.616
228203P06
50/50
16.243
228202CUMB CT
50/50
14.881
228206SHRMN CT
50/50
14.632
228732V1-021 C
50/50
0.297
957251AF2-019 GEN
50/50
1.25
945731AF1-238 GEN
50/50
3.054
945741AF1-239 GEN
50/50
1.832
228727W2-039G
50/50
9.613
228717S121
50/50
9.524
971525AH1-260 GEN
50/50
44.874
957311AF2-025 GEN
50/50
1.181
228251CARLLS#4
50/50
0.705
970453AG2-297 GEN
Solar/Wind Harmer
0.154
971553AH1-274 GEN
Solar/Wind Harmer
0.127
230422AE1-104_GEN1
Solar/Wind Harmer
31.562
230425AE1-104_GEN2
Solar/Wind Harmer
31.562
228754AB1-001 C
Solar/Wind Harmer
-0.001
230433AD2-135 GEN
Solar/Wind Harmer
0
945431AF1-208 GEN
Solar/Wind Harmer
0.323
970997AG2-616 GEN
Solar/Wind Harmer
0.349
972141AH1-641 GEN
Solar/Wind Harmer
0.105
971535AH1-265 GEN
Solar/Wind Harmer
0.205
230430AE1-229_GEN
Solar/Wind Harmer
-0.001
230407AD2-065 C
Solar/Wind Harmer
0
228351V2-046C
Solar/Wind Harmer
-0.001
971011AG2-627 GEN
Solar/Wind Harmer
0.258
218660EHAMPSOLAR C
Solar/Wind Harmer
-0.001
207500AE2-000G1
Solar/Wind Harmer
21.201
207497AE2-000G2
Solar/Wind Harmer
21.201
207507AE2-000G3
Solar/Wind Harmer
21.201
207487AE2-000G4
Solar/Wind Harmer
21.201
970025AG2-016 GEN
Solar/Wind Harmer
0.104
207522AF2-254 C
Solar/Wind Harmer
0.052
971189AH1-054 GEN
Solar/Wind Harmer
0.042
219623KINSLEYBEA C
Solar/Wind Harmer
0
971667AH1-334 GEN
Solar/Wind Harmer
0.098
219137THOSOLAR C
Solar/Wind Harmer
0
219258KINSLEYDEP C
Solar/Wind Harmer
0
219766PARADISE C
Solar/Wind Harmer
0
20714328BYD_X4-031
Solar/Wind Harmer
0.009
20714428HOW_X1-037
Solar/Wind Harmer
0
20720628TIN_W1-124
Solar/Wind Harmer
0
219907AC1-030 C
Solar/Wind Harmer
0
219236SOUTHERNHQ C
Solar/Wind Harmer
0
219906AC1-017 C
Solar/Wind Harmer
0
219615MILLCREEK C
Solar/Wind Harmer
0
20742028HF_AC1-207
Solar/Wind Harmer
0
971521AH1-258 GEN
Solar/Wind Harmer
0.084
967451AG2-055 C O1
Solar/Wind Harmer
95.376
219727YARDVSOLFA C
Solar/Wind Harmer
0
219817TRENTONSOL C
Solar/Wind Harmer
0
219620RIDERU C
Solar/Wind Harmer
0
219276PARKLANDSO C
Solar/Wind Harmer
0
214067T20SOLAR
Solar/Wind Harmer
0
219918AC2-009 C
Solar/Wind Harmer
0
219612MATRIX C
Solar/Wind Harmer
0
218438BLK ROCK C
Solar/Wind Harmer
0
218524CNTRALGAS1 C
Solar/Wind Harmer
0
218526CNTRALGAS2 C
Solar/Wind Harmer
0
218428ETC SOLAR C
Solar/Wind Harmer
0
217213AMBOY SO C
Solar/Wind Harmer
0
219249CENTRALDIV C
Solar/Wind Harmer
0
218449LINSOLAR C
Solar/Wind Harmer
0
217081WEATEXAS C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
217206BARNGR HS C
Solar/Wind Harmer
0
217208PARK ELE C
Solar/Wind Harmer
0
20673828FLE_V3-070
Solar/Wind Harmer
0.023
20675428EAM_W2-061
Solar/Wind Harmer
0
207439AE1-081 C O1
Solar/Wind Harmer
0
20676328BVR_Y1-020
Solar/Wind Harmer
0
20674628WNG_W3-110
Solar/Wind Harmer
0
207511W3-106 GEN
Solar/Wind Harmer
0.013
233973AC2-185 C
Solar/Wind Helper
0.627
233939AC1-091 C
Solar/Wind Helper
0.31
233970AC1-092 C
Solar/Wind Helper
0.31
233971AC1-093 C
Solar/Wind Helper
0.294
233972AC1-094 C
Solar/Wind Helper
0.251
233952AC2-187 GEN
Solar/Wind Helper
0.265
233954AC2-188 GEN
Solar/Wind Helper
0.265
233950AC2-186 GEN
Solar/Wind Helper
0.132
234033AF1-007_GEN
Solar/Wind Helper
27.339
232434Z2-077 GEN
Solar/Wind Helper
0.065
232432Z2-076 GEN
Solar/Wind Helper
0.034
233990AG1-397 GEN
Solar/Wind Helper
0.126
233901CHERRYDALE C
Solar/Wind Helper
0.251
232404W1-003 C
Solar/Wind Helper
0.251
232406W1-004 FULL
Solar/Wind Helper
0.251
232408W1-005 C
Solar/Wind Helper
0.251
232410W1-006 C
Solar/Wind Helper
0.251
234015AF2-250 C
Solar/Wind Helper
0.025
233923SMA
Solar/Wind Helper
1.028
233998TM1NIN_3.36
Solar/Wind Helper
0.281
233997TMININ_4.2
Solar/Wind Helper
0.281
233996TM1833_GEN
Solar/Wind Helper
0.281
233940AF2-379 C
Solar/Wind Helper
0.05
232428Y3-058 C
Solar/Wind Helper
0.186
233994AC2-023 GEN
Solar/Wind Helper
0.565
232426Y1-080 FULL
Solar/Wind Helper
0.04
233946AB2-136 GEN
Solar/Wind Helper
0.606
233964AF2-378 GEN
Solar/Wind Helper
0.031
234036AF2-325 C
Solar/Wind Helper
0.118
233955AB2-172 GEN
Solar/Wind Helper
0.583
232417X3-008 C
Solar/Wind Helper
0.233
233944AB2-135 GEN
Solar/Wind Helper
0.691
232424Y1-079 C
Solar/Wind Helper
0.105
232422X3-066 FULL
Solar/Wind Helper
0.062
232436AB1-176 C
Solar/Wind Helper
0.042
233987AB2-037 GEN
Solar/Wind Helper
2.089
233982AB2-133 GEN
Solar/Wind Helper
0.576
233930AB2-032 GEN
Solar/Wind Helper
0.201
233933AB2-153 GEN
Solar/Wind Helper
0.201
233915AB1-141 GEN
Solar/Wind Helper
0.199
233918AB1-142 GEN
Solar/Wind Helper
0.199
233935AB2-179 C
Solar/Wind Helper
0.43
G-007ALTFEXP_G-007A->PJM
CMTX
18.635
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.773
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.457
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
3.037
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.647
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.014
CBM NorthLTFEXP_CBM-N->PJM
CBM
20.692
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
42.94

Details for HOPE CREEK-SILVER RUN 230.0 kV Ckt 1 line l/o PJM500_PS_P2-3_HOPC_3-4_SRT-A


Base Case Flowgate

Area:PJM
Facility Description:
HOPE CREEK-SILVER RUN 230.0 kV Ckt 1 line
Contingency Name:
PJM500_PS_P2-3_HOPC_3-4_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.26 %
Rating:1150.0 MVA
Rating Type:B
MVA to Mitigate:1256.43
MW Contribution:0.26
Bus #Bus NameTypeMW Contribution
200039HOPE CG1
50/50
24.45
200036SALEM-G1
50/50
17.72
200037SALEM-G2
50/50
17.593
972251AH1-710 GEN
50/50
64.616
228203P06
50/50
16.243
228202CUMB CT
50/50
14.881
228206SHRMN CT
50/50
14.632
228732V1-021 C
50/50
0.297
957251AF2-019 GEN
50/50
1.25
945731AF1-238 GEN
50/50
3.054
945741AF1-239 GEN
50/50
1.832
228727W2-039G
50/50
9.613
228717S121
50/50
9.524
971525AH1-260 GEN
50/50
44.874
957311AF2-025 GEN
50/50
1.181
228251CARLLS#4
50/50
0.705
970453AG2-297 GEN
Solar/Wind Harmer
0.154
971553AH1-274 GEN
Solar/Wind Harmer
0.127
230422AE1-104_GEN1
Solar/Wind Harmer
31.562
230425AE1-104_GEN2
Solar/Wind Harmer
31.562
228754AB1-001 C
Solar/Wind Harmer
-0.001
230433AD2-135 GEN
Solar/Wind Harmer
0
945431AF1-208 GEN
Solar/Wind Harmer
0.323
970997AG2-616 GEN
Solar/Wind Harmer
0.349
972141AH1-641 GEN
Solar/Wind Harmer
0.105
971535AH1-265 GEN
Solar/Wind Harmer
0.205
230430AE1-229_GEN
Solar/Wind Harmer
-0.001
230407AD2-065 C
Solar/Wind Harmer
0
228351V2-046C
Solar/Wind Harmer
-0.001
971011AG2-627 GEN
Solar/Wind Harmer
0.258
218660EHAMPSOLAR C
Solar/Wind Harmer
-0.001
207500AE2-000G1
Solar/Wind Harmer
21.201
207497AE2-000G2
Solar/Wind Harmer
21.201
207507AE2-000G3
Solar/Wind Harmer
21.201
207487AE2-000G4
Solar/Wind Harmer
21.201
970025AG2-016 GEN
Solar/Wind Harmer
0.104
207522AF2-254 C
Solar/Wind Harmer
0.052
971189AH1-054 GEN
Solar/Wind Harmer
0.042
219623KINSLEYBEA C
Solar/Wind Harmer
0
971667AH1-334 GEN
Solar/Wind Harmer
0.098
219137THOSOLAR C
Solar/Wind Harmer
0
219258KINSLEYDEP C
Solar/Wind Harmer
0
219766PARADISE C
Solar/Wind Harmer
0
20714328BYD_X4-031
Solar/Wind Harmer
0.009
20714428HOW_X1-037
Solar/Wind Harmer
0
20720628TIN_W1-124
Solar/Wind Harmer
0
219907AC1-030 C
Solar/Wind Harmer
0
219236SOUTHERNHQ C
Solar/Wind Harmer
0
219906AC1-017 C
Solar/Wind Harmer
0
219615MILLCREEK C
Solar/Wind Harmer
0
20742028HF_AC1-207
Solar/Wind Harmer
0
971521AH1-258 GEN
Solar/Wind Harmer
0.084
967451AG2-055 C O1
Solar/Wind Harmer
95.376
219727YARDVSOLFA C
Solar/Wind Harmer
0
219817TRENTONSOL C
Solar/Wind Harmer
0
219620RIDERU C
Solar/Wind Harmer
0
219276PARKLANDSO C
Solar/Wind Harmer
0
214067T20SOLAR
Solar/Wind Harmer
0
219918AC2-009 C
Solar/Wind Harmer
0
219612MATRIX C
Solar/Wind Harmer
0
218438BLK ROCK C
Solar/Wind Harmer
0
218524CNTRALGAS1 C
Solar/Wind Harmer
0
218526CNTRALGAS2 C
Solar/Wind Harmer
0
218428ETC SOLAR C
Solar/Wind Harmer
0
217213AMBOY SO C
Solar/Wind Harmer
0
219249CENTRALDIV C
Solar/Wind Harmer
0
218449LINSOLAR C
Solar/Wind Harmer
0
217081WEATEXAS C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
217206BARNGR HS C
Solar/Wind Harmer
0
217208PARK ELE C
Solar/Wind Harmer
0
20673828FLE_V3-070
Solar/Wind Harmer
0.023
20675428EAM_W2-061
Solar/Wind Harmer
0
207439AE1-081 C O1
Solar/Wind Harmer
0
20676328BVR_Y1-020
Solar/Wind Harmer
0
20674628WNG_W3-110
Solar/Wind Harmer
0
207511W3-106 GEN
Solar/Wind Harmer
0.013
233973AC2-185 C
Solar/Wind Helper
0.627
233939AC1-091 C
Solar/Wind Helper
0.31
233970AC1-092 C
Solar/Wind Helper
0.31
233971AC1-093 C
Solar/Wind Helper
0.294
233972AC1-094 C
Solar/Wind Helper
0.251
233952AC2-187 GEN
Solar/Wind Helper
0.265
233954AC2-188 GEN
Solar/Wind Helper
0.265
233950AC2-186 GEN
Solar/Wind Helper
0.132
234033AF1-007_GEN
Solar/Wind Helper
27.339
232434Z2-077 GEN
Solar/Wind Helper
0.065
232432Z2-076 GEN
Solar/Wind Helper
0.034
233990AG1-397 GEN
Solar/Wind Helper
0.126
233901CHERRYDALE C
Solar/Wind Helper
0.251
232404W1-003 C
Solar/Wind Helper
0.251
232406W1-004 FULL
Solar/Wind Helper
0.251
232408W1-005 C
Solar/Wind Helper
0.251
232410W1-006 C
Solar/Wind Helper
0.251
234015AF2-250 C
Solar/Wind Helper
0.025
233923SMA
Solar/Wind Helper
1.028
233998TM1NIN_3.36
Solar/Wind Helper
0.281
233997TMININ_4.2
Solar/Wind Helper
0.281
233996TM1833_GEN
Solar/Wind Helper
0.281
233940AF2-379 C
Solar/Wind Helper
0.05
232428Y3-058 C
Solar/Wind Helper
0.186
233994AC2-023 GEN
Solar/Wind Helper
0.565
232426Y1-080 FULL
Solar/Wind Helper
0.04
233946AB2-136 GEN
Solar/Wind Helper
0.606
233964AF2-378 GEN
Solar/Wind Helper
0.031
234036AF2-325 C
Solar/Wind Helper
0.118
233955AB2-172 GEN
Solar/Wind Helper
0.583
232417X3-008 C
Solar/Wind Helper
0.233
233944AB2-135 GEN
Solar/Wind Helper
0.691
232424Y1-079 C
Solar/Wind Helper
0.105
232422X3-066 FULL
Solar/Wind Helper
0.062
232436AB1-176 C
Solar/Wind Helper
0.042
233987AB2-037 GEN
Solar/Wind Helper
2.089
233982AB2-133 GEN
Solar/Wind Helper
0.576
233930AB2-032 GEN
Solar/Wind Helper
0.201
233933AB2-153 GEN
Solar/Wind Helper
0.201
233915AB1-141 GEN
Solar/Wind Helper
0.199
233918AB1-142 GEN
Solar/Wind Helper
0.199
233935AB2-179 C
Solar/Wind Helper
0.43
G-007ALTFEXP_G-007A->PJM
CMTX
18.635
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.773
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.457
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
3.037
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.647
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.014
CBM NorthLTFEXP_CBM-N->PJM
CBM
20.692
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
42.94

Details for HOPE CREEK-SILVER RUN 230.0 kV Ckt 1 line l/o DPL_P4_2_REDLION-HOPE AT50_SRT-A


Base Case Flowgate

Area:PJM
Facility Description:
HOPE CREEK-SILVER RUN 230.0 kV Ckt 1 line
Contingency Name:
DPL_P4_2_REDLION-HOPE AT50_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.14 %
Rating:1150.0 MVA
Rating Type:B
MVA to Mitigate:1243.57
MW Contribution:0.25
Bus #Bus NameTypeMW Contribution
200039HOPE CG1
50/50
23.936
200036SALEM-G1
50/50
17.348
200037SALEM-G2
50/50
17.223
972251AH1-710 GEN
50/50
63.257
228203P06
50/50
15.846
228202CUMB CT
50/50
14.514
228206SHRMN CT
50/50
14.269
228732V1-021 C
50/50
0.29
957251AF2-019 GEN
50/50
1.219
945731AF1-238 GEN
50/50
2.977
945741AF1-239 GEN
50/50
1.786
228727W2-039G
50/50
9.371
228717S121
50/50
9.283
971525AH1-260 GEN
50/50
43.746
957311AF2-025 GEN
50/50
1.151
228251CARLLS#4
50/50
0.687
970453AG2-297 GEN
Solar/Wind Harmer
0.151
971553AH1-274 GEN
Solar/Wind Harmer
0.124
230422AE1-104_GEN1
Solar/Wind Harmer
30.78
230425AE1-104_GEN2
Solar/Wind Harmer
30.78
228754AB1-001 C
Solar/Wind Harmer
-0.001
230433AD2-135 GEN
Solar/Wind Harmer
0
945431AF1-208 GEN
Solar/Wind Harmer
0.315
970997AG2-616 GEN
Solar/Wind Harmer
0.34
972141AH1-641 GEN
Solar/Wind Harmer
0.102
971535AH1-265 GEN
Solar/Wind Harmer
0.2
230430AE1-229_GEN
Solar/Wind Harmer
-0.001
230407AD2-065 C
Solar/Wind Harmer
0
228351V2-046C
Solar/Wind Harmer
-0.001
971011AG2-627 GEN
Solar/Wind Harmer
0.251
218660EHAMPSOLAR C
Solar/Wind Harmer
-0.001
207500AE2-000G1
Solar/Wind Harmer
20.657
207497AE2-000G2
Solar/Wind Harmer
20.657
207507AE2-000G3
Solar/Wind Harmer
20.657
207487AE2-000G4
Solar/Wind Harmer
20.657
970025AG2-016 GEN
Solar/Wind Harmer
0.102
207522AF2-254 C
Solar/Wind Harmer
0.051
971189AH1-054 GEN
Solar/Wind Harmer
0.041
219623KINSLEYBEA C
Solar/Wind Harmer
0
971667AH1-334 GEN
Solar/Wind Harmer
0.095
219137THOSOLAR C
Solar/Wind Harmer
0
219258KINSLEYDEP C
Solar/Wind Harmer
0
219766PARADISE C
Solar/Wind Harmer
0
20714328BYD_X4-031
Solar/Wind Harmer
0.009
20714428HOW_X1-037
Solar/Wind Harmer
0
20720628TIN_W1-124
Solar/Wind Harmer
0
219907AC1-030 C
Solar/Wind Harmer
0
219236SOUTHERNHQ C
Solar/Wind Harmer
0
219906AC1-017 C
Solar/Wind Harmer
0
219615MILLCREEK C
Solar/Wind Harmer
0
20742028HF_AC1-207
Solar/Wind Harmer
0
971521AH1-258 GEN
Solar/Wind Harmer
0.082
967451AG2-055 C O1
Solar/Wind Harmer
92.935
219727YARDVSOLFA C
Solar/Wind Harmer
0
219817TRENTONSOL C
Solar/Wind Harmer
0
219620RIDERU C
Solar/Wind Harmer
0
219276PARKLANDSO C
Solar/Wind Harmer
0
214067T20SOLAR
Solar/Wind Harmer
0
219918AC2-009 C
Solar/Wind Harmer
0
219612MATRIX C
Solar/Wind Harmer
0
218438BLK ROCK C
Solar/Wind Harmer
0
218524CNTRALGAS1 C
Solar/Wind Harmer
0
218526CNTRALGAS2 C
Solar/Wind Harmer
0
218428ETC SOLAR C
Solar/Wind Harmer
0
217213AMBOY SO C
Solar/Wind Harmer
0
219249CENTRALDIV C
Solar/Wind Harmer
0
218449LINSOLAR C
Solar/Wind Harmer
0
217081WEATEXAS C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
217206BARNGR HS C
Solar/Wind Harmer
0
217208PARK ELE C
Solar/Wind Harmer
0
20673828FLE_V3-070
Solar/Wind Harmer
0.022
20675428EAM_W2-061
Solar/Wind Harmer
0
207439AE1-081 C O1
Solar/Wind Harmer
0
20676328BVR_Y1-020
Solar/Wind Harmer
0
20674628WNG_W3-110
Solar/Wind Harmer
0
207511W3-106 GEN
Solar/Wind Harmer
0.013
233973AC2-185 C
Solar/Wind Helper
0.65
233939AC1-091 C
Solar/Wind Helper
0.322
233970AC1-092 C
Solar/Wind Helper
0.322
233971AC1-093 C
Solar/Wind Helper
0.305
233972AC1-094 C
Solar/Wind Helper
0.26
233952AC2-187 GEN
Solar/Wind Helper
0.275
233954AC2-188 GEN
Solar/Wind Helper
0.275
233950AC2-186 GEN
Solar/Wind Helper
0.138
234033AF1-007_GEN
Solar/Wind Helper
28.38
232434Z2-077 GEN
Solar/Wind Helper
0.067
232432Z2-076 GEN
Solar/Wind Helper
0.035
233990AG1-397 GEN
Solar/Wind Helper
0.131
233901CHERRYDALE C
Solar/Wind Helper
0.26
232404W1-003 C
Solar/Wind Helper
0.26
232406W1-004 FULL
Solar/Wind Helper
0.26
232408W1-005 C
Solar/Wind Helper
0.26
232410W1-006 C
Solar/Wind Helper
0.26
234015AF2-250 C
Solar/Wind Helper
0.026
233923SMA
Solar/Wind Helper
1.067
233998TM1NIN_3.36
Solar/Wind Helper
0.292
233997TMININ_4.2
Solar/Wind Helper
0.292
233996TM1833_GEN
Solar/Wind Helper
0.292
233940AF2-379 C
Solar/Wind Helper
0.052
232428Y3-058 C
Solar/Wind Helper
0.193
233994AC2-023 GEN
Solar/Wind Helper
0.587
232426Y1-080 FULL
Solar/Wind Helper
0.042
233946AB2-136 GEN
Solar/Wind Helper
0.629
233964AF2-378 GEN
Solar/Wind Helper
0.032
234036AF2-325 C
Solar/Wind Helper
0.122
233955AB2-172 GEN
Solar/Wind Helper
0.606
232417X3-008 C
Solar/Wind Helper
0.242
233944AB2-135 GEN
Solar/Wind Helper
0.72
232424Y1-079 C
Solar/Wind Helper
0.109
232422X3-066 FULL
Solar/Wind Helper
0.065
232436AB1-176 C
Solar/Wind Helper
0.043
233982AB2-133 GEN
Solar/Wind Helper
0.6
233987AB2-037 GEN
Solar/Wind Helper
2.171
233930AB2-032 GEN
Solar/Wind Helper
0.21
233933AB2-153 GEN
Solar/Wind Helper
0.21
233915AB1-141 GEN
Solar/Wind Helper
0.208
233918AB1-142 GEN
Solar/Wind Helper
0.208
233935AB2-179 C
Solar/Wind Helper
0.451
G-007ALTFEXP_G-007A->PJM
CMTX
18.145
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.73
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.432
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
2.86
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.609
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.896
CBM NorthLTFEXP_CBM-N->PJM
CBM
20.187
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
41.8

Details for NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line l/o PECO_P1-2_5012_SRT-A


Base Case Flowgate

Area:PECO
Facility Description:
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line
Contingency Name:
PECO_P1-2_5012_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:147.41 %
Rating:639.0 MVA
Rating Type:B
MVA to Mitigate:941.93
MW Contribution:0.13
Bus #Bus NameTypeMW Contribution
213508CON10-11
50/50
0.991
213508CON10-11
50/50
0.991
213518CONOW8-9
50/50
0.991
213518CONOW8-9
50/50
0.991
213515CONOW3-4
50/50
1.041
213517CONOW7
50/50
1.041
213515CONOW3-4
50/50
0.949
213516CONOW5-6
50/50
0.949
213514CONOW1-2
50/50
0.778
213516CONOW5-6
50/50
0.778
213514CONOW1-2
50/50
0.739
231918WEST 1
50/50
0.098
213893PHLISST1
50/50
1.432
213890PHLISCT3
50/50
0.992
213888PHLISCT1
50/50
0.992
213889PHLISCT2
50/50
0.992
231909HR2
50/50
0.598
231916EM3
50/50
0.412
231917EM10
50/50
0.087
231919CHRIST1
50/50
2.327
231920CHRIST2
50/50
2.327
231901EM4
50/50
0.829
231908HR1
50/50
0.595
231910HR3
50/50
0.595
213740LIBE_ST1
50/50
1.193
213738LIBE_CT1
50/50
0.916
213739LIBE_CT2
50/50
0.916
231505HR4
50/50
0.934
971983AH1-536 GEN
Solar/Wind Harmer
0.175
233968AD2-076_GEN
Solar/Wind Harmer
0.2
234014AF1-036_GEN
Solar/Wind Harmer
0.082
970597AG2-380 GEN
Solar/Wind Harmer
1.636
234012AE2-112_GEN
Solar/Wind Harmer
0.07
233984AB2-036 GEN
Solar/Wind Harmer
0.367
234041AC1-190 GEN
Solar/Wind Harmer
0.188
233987AB2-037 GEN
Solar/Wind Harmer
0
233964AF2-378 GEN
Solar/Wind Harmer
0
233946AB2-136 GEN
Solar/Wind Harmer
0
232426Y1-080 FULL
Solar/Wind Harmer
0
970277AG2-181 GEN
Solar/Wind Harmer
0.105
960671AF2-358 GEN
Solar/Wind Harmer
0.374
965821AG1-450 GEN
Solar/Wind Harmer
1.869
233940AF2-379 C
Solar/Wind Harmer
0
234015AF2-250 C
Solar/Wind Harmer
0
971195AH1-057 GEN
Solar/Wind Harmer
0.027
233923SMA
Solar/Wind Harmer
0
233998TM1NIN_3.36
Solar/Wind Harmer
0
233997TMININ_4.2
Solar/Wind Harmer
0
233996TM1833_GEN
Solar/Wind Harmer
0
233990AG1-397 GEN
Solar/Wind Harmer
0
971747AH1-380 GEN
Solar/Wind Harmer
0.074
233990AG1-397 GEN
Solar/Wind Harmer
0.59
972069AH1-584 GEN
Solar/Wind Harmer
0.184
972071AH1-585 GEN
Solar/Wind Harmer
0.184
972073AH1-586 GEN
Solar/Wind Harmer
3.315
234033AF1-007_GEN
Solar/Wind Harmer
7.648
970545AG2-347 GEN
Solar/Wind Harmer
31.505
972133AH1-634 GEN
Solar/Wind Harmer
4.773
972177AH1-672 GEN
Solar/Wind Harmer
0.274
971149AH1-027 GEN
Solar/Wind Harmer
0.089
233972AC1-094 C
Solar/Wind Harmer
0
970695AG2-447 GEN
Solar/Wind Harmer
0.07
219137THOSOLAR C
Solar/Wind Harmer
0
219258KINSLEYDEP C
Solar/Wind Harmer
0
219766PARADISE C
Solar/Wind Harmer
0
219623KINSLEYBEA C
Solar/Wind Harmer
0
971011AG2-627 GEN
Solar/Wind Harmer
0.131
219907AC1-030 C
Solar/Wind Harmer
0
228351V2-046C
Solar/Wind Harmer
0
219236SOUTHERNHQ C
Solar/Wind Harmer
0
970997AG2-616 GEN
Solar/Wind Harmer
0.162
972141AH1-641 GEN
Solar/Wind Harmer
0.049
230430AE1-229_GEN
Solar/Wind Harmer
0
945431AF1-208 GEN
Solar/Wind Harmer
0.145
219906AC1-017 C
Solar/Wind Harmer
0
219615MILLCREEK C
Solar/Wind Harmer
0
971535AH1-265 GEN
Solar/Wind Harmer
0.094
971553AH1-274 GEN
Solar/Wind Harmer
0.053
230433AD2-135 GEN
Solar/Wind Harmer
0
230407AD2-065 C
Solar/Wind Harmer
0
970453AG2-297 GEN
Solar/Wind Harmer
0.06
218660EHAMPSOLAR C
Solar/Wind Harmer
0
230422AE1-104_GEN1
Solar/Wind Harmer
12.966
230425AE1-104_GEN2
Solar/Wind Harmer
12.966
228754AB1-001 C
Solar/Wind Harmer
0
214067T20SOLAR
Solar/Wind Harmer
0
219727YARDVSOLFA C
Solar/Wind Harmer
0
207522AF2-254 C
Solar/Wind Harmer
0.029
207500AE2-000G1
Solar/Wind Harmer
11.012
207497AE2-000G2
Solar/Wind Harmer
11.012
207507AE2-000G3
Solar/Wind Harmer
11.012
207487AE2-000G4
Solar/Wind Harmer
11.012
971189AH1-054 GEN
Solar/Wind Harmer
0.023
219276PARKLANDSO C
Solar/Wind Harmer
0
970025AG2-016 GEN
Solar/Wind Harmer
0.055
971667AH1-334 GEN
Solar/Wind Harmer
0.053
219620RIDERU C
Solar/Wind Harmer
0
219817TRENTONSOL C
Solar/Wind Harmer
0
219918AC2-009 C
Solar/Wind Harmer
0
20714328BYD_X4-031
Solar/Wind Harmer
0.005
20714428HOW_X1-037
Solar/Wind Harmer
0
20720628TIN_W1-124
Solar/Wind Harmer
0
219612MATRIX C
Solar/Wind Harmer
0
218438BLK ROCK C
Solar/Wind Harmer
0
20742028HF_AC1-207
Solar/Wind Harmer
0
971521AH1-258 GEN
Solar/Wind Harmer
0.05
967451AG2-055 C O1
Solar/Wind Harmer
56.631
218526CNTRALGAS2 C
Solar/Wind Harmer
0
223401AF1-299 GEN
Solar/Wind Helper
0.063
223402AF1-300 C
Solar/Wind Helper
0.063
208923BUSO V4-027
Solar/Wind Helper
0.015
G-007ALTFEXP_G-007A->PJM
CMTX
12.048
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.129
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.666
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.379
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.931
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.9
CBM NorthLTFEXP_CBM-N->PJM
CBM
15.238
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
30.513

Details for NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line l/o PJM_500_BG_P4_5_CNSTN_C_SRT-A


Base Case Flowgate

Area:PECO
Facility Description:
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line
Contingency Name:
PJM_500_BG_P4_5_CNSTN_C_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:144.84 %
Rating:639.0 MVA
Rating Type:B
MVA to Mitigate:925.55
MW Contribution:0.13
Bus #Bus NameTypeMW Contribution
213508CON10-11
50/50
0.991
213508CON10-11
50/50
0.991
213518CONOW8-9
50/50
0.991
213518CONOW8-9
50/50
0.991
213515CONOW3-4
50/50
1.041
213517CONOW7
50/50
1.041
213515CONOW3-4
50/50
0.949
213516CONOW5-6
50/50
0.949
213514CONOW1-2
50/50
0.778
213516CONOW5-6
50/50
0.778
213514CONOW1-2
50/50
0.739
971983AH1-536 GEN
Solar/Wind Harmer
0.175
233968AD2-076_GEN
Solar/Wind Harmer
0.2
234014AF1-036_GEN
Solar/Wind Harmer
0.082
970597AG2-380 GEN
Solar/Wind Harmer
1.636
234012AE2-112_GEN
Solar/Wind Harmer
0.07
233984AB2-036 GEN
Solar/Wind Harmer
0.367
234041AC1-190 GEN
Solar/Wind Harmer
0.188
233987AB2-037 GEN
Solar/Wind Harmer
0
233964AF2-378 GEN
Solar/Wind Harmer
0
233946AB2-136 GEN
Solar/Wind Harmer
0
232426Y1-080 FULL
Solar/Wind Harmer
0
970277AG2-181 GEN
Solar/Wind Harmer
0.105
960671AF2-358 GEN
Solar/Wind Harmer
0.374
965821AG1-450 GEN
Solar/Wind Harmer
1.869
233940AF2-379 C
Solar/Wind Harmer
0
234015AF2-250 C
Solar/Wind Harmer
0
971195AH1-057 GEN
Solar/Wind Harmer
0.027
233923SMA
Solar/Wind Harmer
0
233998TM1NIN_3.36
Solar/Wind Harmer
0
233997TMININ_4.2
Solar/Wind Harmer
0
233996TM1833_GEN
Solar/Wind Harmer
0
233990AG1-397 GEN
Solar/Wind Harmer
0
971747AH1-380 GEN
Solar/Wind Harmer
0.074
233990AG1-397 GEN
Solar/Wind Harmer
0.59
972069AH1-584 GEN
Solar/Wind Harmer
0.184
972071AH1-585 GEN
Solar/Wind Harmer
0.184
972073AH1-586 GEN
Solar/Wind Harmer
3.315
234033AF1-007_GEN
Solar/Wind Harmer
7.648
970545AG2-347 GEN
Solar/Wind Harmer
31.505
972133AH1-634 GEN
Solar/Wind Harmer
4.773
972177AH1-672 GEN
Solar/Wind Harmer
0.274
971149AH1-027 GEN
Solar/Wind Harmer
0.089
233972AC1-094 C
Solar/Wind Harmer
0
970695AG2-447 GEN
Solar/Wind Harmer
0.07
219137THOSOLAR C
Solar/Wind Harmer
0
219258KINSLEYDEP C
Solar/Wind Harmer
0
219766PARADISE C
Solar/Wind Harmer
0
219623KINSLEYBEA C
Solar/Wind Harmer
0
971011AG2-627 GEN
Solar/Wind Harmer
0.131
219907AC1-030 C
Solar/Wind Harmer
0
228351V2-046C
Solar/Wind Harmer
0
219236SOUTHERNHQ C
Solar/Wind Harmer
0
970997AG2-616 GEN
Solar/Wind Harmer
0.162
972141AH1-641 GEN
Solar/Wind Harmer
0.049
230430AE1-229_GEN
Solar/Wind Harmer
0
945431AF1-208 GEN
Solar/Wind Harmer
0.145
219906AC1-017 C
Solar/Wind Harmer
0
219615MILLCREEK C
Solar/Wind Harmer
0
971535AH1-265 GEN
Solar/Wind Harmer
0.094
971553AH1-274 GEN
Solar/Wind Harmer
0.053
230433AD2-135 GEN
Solar/Wind Harmer
0
230407AD2-065 C
Solar/Wind Harmer
0
970453AG2-297 GEN
Solar/Wind Harmer
0.06
218660EHAMPSOLAR C
Solar/Wind Harmer
0
230422AE1-104_GEN1
Solar/Wind Harmer
12.966
230425AE1-104_GEN2
Solar/Wind Harmer
12.966
228754AB1-001 C
Solar/Wind Harmer
0
214067T20SOLAR
Solar/Wind Harmer
0
219727YARDVSOLFA C
Solar/Wind Harmer
0
207522AF2-254 C
Solar/Wind Harmer
0.029
207500AE2-000G1
Solar/Wind Harmer
11.012
207497AE2-000G2
Solar/Wind Harmer
11.012
207507AE2-000G3
Solar/Wind Harmer
11.012
207487AE2-000G4
Solar/Wind Harmer
11.012
971189AH1-054 GEN
Solar/Wind Harmer
0.023
219276PARKLANDSO C
Solar/Wind Harmer
0
970025AG2-016 GEN
Solar/Wind Harmer
0.055
971667AH1-334 GEN
Solar/Wind Harmer
0.053
219620RIDERU C
Solar/Wind Harmer
0
219817TRENTONSOL C
Solar/Wind Harmer
0
219918AC2-009 C
Solar/Wind Harmer
0
20714328BYD_X4-031
Solar/Wind Harmer
0.005
20714428HOW_X1-037
Solar/Wind Harmer
0
20720628TIN_W1-124
Solar/Wind Harmer
0
219612MATRIX C
Solar/Wind Harmer
0
218438BLK ROCK C
Solar/Wind Harmer
0
20742028HF_AC1-207
Solar/Wind Harmer
0
971521AH1-258 GEN
Solar/Wind Harmer
0.05
967451AG2-055 C O1
Solar/Wind Harmer
56.631
218526CNTRALGAS2 C
Solar/Wind Harmer
0
223401AF1-299 GEN
Solar/Wind Helper
0.063
223402AF1-300 C
Solar/Wind Helper
0.063
208923BUSO V4-027
Solar/Wind Helper
0.015
G-007ALTFEXP_G-007A->PJM
CMTX
12.048
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.129
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.666
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.379
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.931
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.9
CBM NorthLTFEXP_CBM-N->PJM
CBM
15.238
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
30.513

Details for NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line l/o PECO_P4_PEACH235_SRT-A/* $ CHESCO $ PECO_P4_PEACH235 $ STBK


Base Case Flowgate

Area:PECO
Facility Description:
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line
Contingency Name:
PECO_P4_PEACH235_SRT-A/* $ CHESCO $ PECO_P4_PEACH235 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:144.81 %
Rating:639.0 MVA
Rating Type:B
MVA to Mitigate:925.35
MW Contribution:0.13
Bus #Bus NameTypeMW Contribution
213508CON10-11
50/50
0.991
213508CON10-11
50/50
0.991
213518CONOW8-9
50/50
0.991
213518CONOW8-9
50/50
0.991
213515CONOW3-4
50/50
1.041
213517CONOW7
50/50
1.041
213515CONOW3-4
50/50
0.949
213516CONOW5-6
50/50
0.949
213514CONOW1-2
50/50
0.778
213516CONOW5-6
50/50
0.778
213514CONOW1-2
50/50
0.739
971983AH1-536 GEN
Solar/Wind Harmer
0.175
233968AD2-076_GEN
Solar/Wind Harmer
0.201
234014AF1-036_GEN
Solar/Wind Harmer
0.082
970597AG2-380 GEN
Solar/Wind Harmer
1.637
234012AE2-112_GEN
Solar/Wind Harmer
0.07
233984AB2-036 GEN
Solar/Wind Harmer
0.367
234041AC1-190 GEN
Solar/Wind Harmer
0.188
233987AB2-037 GEN
Solar/Wind Harmer
0
233964AF2-378 GEN
Solar/Wind Harmer
0
233946AB2-136 GEN
Solar/Wind Harmer
0
232426Y1-080 FULL
Solar/Wind Harmer
0
970277AG2-181 GEN
Solar/Wind Harmer
0.105
960671AF2-358 GEN
Solar/Wind Harmer
0.374
965821AG1-450 GEN
Solar/Wind Harmer
1.87
233940AF2-379 C
Solar/Wind Harmer
0
234015AF2-250 C
Solar/Wind Harmer
0
971195AH1-057 GEN
Solar/Wind Harmer
0.027
233923SMA
Solar/Wind Harmer
0
233998TM1NIN_3.36
Solar/Wind Harmer
0
233997TMININ_4.2
Solar/Wind Harmer
0
233996TM1833_GEN
Solar/Wind Harmer
0
233990AG1-397 GEN
Solar/Wind Harmer
0
971747AH1-380 GEN
Solar/Wind Harmer
0.074
233990AG1-397 GEN
Solar/Wind Harmer
0.59
972069AH1-584 GEN
Solar/Wind Harmer
0.184
972071AH1-585 GEN
Solar/Wind Harmer
0.184
972073AH1-586 GEN
Solar/Wind Harmer
3.317
234033AF1-007_GEN
Solar/Wind Harmer
7.652
970545AG2-347 GEN
Solar/Wind Harmer
31.523
972133AH1-634 GEN
Solar/Wind Harmer
4.776
972177AH1-672 GEN
Solar/Wind Harmer
0.274
971149AH1-027 GEN
Solar/Wind Harmer
0.089
233972AC1-094 C
Solar/Wind Harmer
0
970695AG2-447 GEN
Solar/Wind Harmer
0.07
219137THOSOLAR C
Solar/Wind Harmer
0
219258KINSLEYDEP C
Solar/Wind Harmer
0
219766PARADISE C
Solar/Wind Harmer
0
219623KINSLEYBEA C
Solar/Wind Harmer
0
971011AG2-627 GEN
Solar/Wind Harmer
0.132
219907AC1-030 C
Solar/Wind Harmer
0
228351V2-046C
Solar/Wind Harmer
0
219236SOUTHERNHQ C
Solar/Wind Harmer
0
970997AG2-616 GEN
Solar/Wind Harmer
0.162
972141AH1-641 GEN
Solar/Wind Harmer
0.049
230430AE1-229_GEN
Solar/Wind Harmer
0
945431AF1-208 GEN
Solar/Wind Harmer
0.145
219906AC1-017 C
Solar/Wind Harmer
0
219615MILLCREEK C
Solar/Wind Harmer
0
971535AH1-265 GEN
Solar/Wind Harmer
0.094
971553AH1-274 GEN
Solar/Wind Harmer
0.053
230433AD2-135 GEN
Solar/Wind Harmer
0
230407AD2-065 C
Solar/Wind Harmer
0
970453AG2-297 GEN
Solar/Wind Harmer
0.06
218660EHAMPSOLAR C
Solar/Wind Harmer
0
230422AE1-104_GEN1
Solar/Wind Harmer
12.971
230425AE1-104_GEN2
Solar/Wind Harmer
12.971
228754AB1-001 C
Solar/Wind Harmer
0
214067T20SOLAR
Solar/Wind Harmer
0
219727YARDVSOLFA C
Solar/Wind Harmer
0
207522AF2-254 C
Solar/Wind Harmer
0.029
207500AE2-000G1
Solar/Wind Harmer
11.015
207497AE2-000G2
Solar/Wind Harmer
11.015
207507AE2-000G3
Solar/Wind Harmer
11.015
207487AE2-000G4
Solar/Wind Harmer
11.015
971189AH1-054 GEN
Solar/Wind Harmer
0.023
219276PARKLANDSO C
Solar/Wind Harmer
0
970025AG2-016 GEN
Solar/Wind Harmer
0.055
971667AH1-334 GEN
Solar/Wind Harmer
0.053
219817TRENTONSOL C
Solar/Wind Harmer
0
219620RIDERU C
Solar/Wind Harmer
0
219918AC2-009 C
Solar/Wind Harmer
0
20714328BYD_X4-031
Solar/Wind Harmer
0.005
20714428HOW_X1-037
Solar/Wind Harmer
0
20720628TIN_W1-124
Solar/Wind Harmer
0
219612MATRIX C
Solar/Wind Harmer
0
218438BLK ROCK C
Solar/Wind Harmer
0
20742028HF_AC1-207
Solar/Wind Harmer
0
971521AH1-258 GEN
Solar/Wind Harmer
0.05
967451AG2-055 C O1
Solar/Wind Harmer
56.646
218526CNTRALGAS2 C
Solar/Wind Harmer
0
223401AF1-299 GEN
Solar/Wind Helper
0.063
223402AF1-300 C
Solar/Wind Helper
0.063
208923BUSO V4-027
Solar/Wind Helper
0.015
G-007ALTFEXP_G-007A->PJM
CMTX
12.051
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.129
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.666
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.38
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.931
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.901
CBM NorthLTFEXP_CBM-N->PJM
CBM
15.241
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
30.52

Details for NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line l/o PECO_P1-2_5014_SRT-A/* $ CHESCO $ PECO_P1-2_5012 $ L


Base Case Flowgate

Area:PECO
Facility Description:
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line
Contingency Name:
PECO_P1-2_5014_SRT-A/* $ CHESCO $ PECO_P1-2_5012 $ L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.18 %
Rating:639.0 MVA
Rating Type:B
MVA to Mitigate:704.06
MW Contribution:0.13
Bus #Bus NameTypeMW Contribution
213508CON10-11
50/50
0.988
213508CON10-11
50/50
0.988
213518CONOW8-9
50/50
0.988
213518CONOW8-9
50/50
0.988
213515CONOW3-4
50/50
1.038
213517CONOW7
50/50
1.038
213515CONOW3-4
50/50
0.946
213516CONOW5-6
50/50
0.946
213514CONOW1-2
50/50
0.776
213516CONOW5-6
50/50
0.776
213514CONOW1-2
50/50
0.737
970431AG2-281 GEN
50/50
4.747
231918WEST 1
50/50
0.104
232416X2-083
50/50
0.015
231919CHRIST1
50/50
2.482
231920CHRIST2
50/50
2.482
231909HR2
50/50
0.632
231916EM3
50/50
0.435
231917EM10
50/50
0.092
231901EM4
50/50
0.877
231908HR1
50/50
0.629
231910HR3
50/50
0.629
231902DC CT7
50/50
0.443
231915DC CT6
50/50
0.443
231906DC3 NUG
50/50
0.355
231907DC10
50/50
0.115
231131BLOOM ENRGY
50/50
0.122
231505HR4
50/50
0.951
971983AH1-536 GEN
Solar/Wind Harmer
0.195
233968AD2-076_GEN
Solar/Wind Harmer
0.224
234014AF1-036_GEN
Solar/Wind Harmer
0.092
970597AG2-380 GEN
Solar/Wind Harmer
1.831
234012AE2-112_GEN
Solar/Wind Harmer
0.078
233984AB2-036 GEN
Solar/Wind Harmer
0.412
234041AC1-190 GEN
Solar/Wind Harmer
0.214
233987AB2-037 GEN
Solar/Wind Harmer
0
233964AF2-378 GEN
Solar/Wind Harmer
0
233946AB2-136 GEN
Solar/Wind Harmer
0
232426Y1-080 FULL
Solar/Wind Harmer
0
970277AG2-181 GEN
Solar/Wind Harmer
0.119
960671AF2-358 GEN
Solar/Wind Harmer
0.425
965821AG1-450 GEN
Solar/Wind Harmer
2.125
233940AF2-379 C
Solar/Wind Harmer
0
234015AF2-250 C
Solar/Wind Harmer
0
971195AH1-057 GEN
Solar/Wind Harmer
0.03
233923SMA
Solar/Wind Harmer
0
233998TM1NIN_3.36
Solar/Wind Harmer
0
233997TMININ_4.2
Solar/Wind Harmer
0
233996TM1833_GEN
Solar/Wind Harmer
0
971747AH1-380 GEN
Solar/Wind Harmer
0.084
233990AG1-397 GEN
Solar/Wind Harmer
0
233990AG1-397 GEN
Solar/Wind Harmer
0.672
972069AH1-584 GEN
Solar/Wind Harmer
0.21
972071AH1-585 GEN
Solar/Wind Harmer
0.21
972073AH1-586 GEN
Solar/Wind Harmer
3.778
234033AF1-007_GEN
Solar/Wind Harmer
8.724
970545AG2-347 GEN
Solar/Wind Harmer
35.936
972133AH1-634 GEN
Solar/Wind Harmer
5.445
972177AH1-672 GEN
Solar/Wind Harmer
0.312
971149AH1-027 GEN
Solar/Wind Harmer
0.102
233972AC1-094 C
Solar/Wind Harmer
0
970695AG2-447 GEN
Solar/Wind Harmer
0.081
971011AG2-627 GEN
Solar/Wind Harmer
0.13
228351V2-046C
Solar/Wind Harmer
0
970997AG2-616 GEN
Solar/Wind Harmer
0.162
972141AH1-641 GEN
Solar/Wind Harmer
0.049
945431AF1-208 GEN
Solar/Wind Harmer
0.146
230430AE1-229_GEN
Solar/Wind Harmer
0
219137THOSOLAR C
Solar/Wind Harmer
0
970453AG2-297 GEN
Solar/Wind Harmer
0.061
971553AH1-274 GEN
Solar/Wind Harmer
0.054
219258KINSLEYDEP C
Solar/Wind Harmer
0
230433AD2-135 GEN
Solar/Wind Harmer
0
971535AH1-265 GEN
Solar/Wind Harmer
0.094
230407AD2-065 C
Solar/Wind Harmer
0
219623KINSLEYBEA C
Solar/Wind Harmer
0
230422AE1-104_GEN1
Solar/Wind Harmer
13.092
230425AE1-104_GEN2
Solar/Wind Harmer
13.092
219766PARADISE C
Solar/Wind Harmer
0
228754AB1-001 C
Solar/Wind Harmer
0
219907AC1-030 C
Solar/Wind Harmer
0
219236SOUTHERNHQ C
Solar/Wind Harmer
0
218660EHAMPSOLAR C
Solar/Wind Harmer
0
219906AC1-017 C
Solar/Wind Harmer
0
219615MILLCREEK C
Solar/Wind Harmer
0
214067T20SOLAR
Solar/Wind Harmer
0
207522AF2-254 C
Solar/Wind Harmer
0.027
207500AE2-000G1
Solar/Wind Harmer
10.314
207497AE2-000G2
Solar/Wind Harmer
10.314
207507AE2-000G3
Solar/Wind Harmer
10.314
207487AE2-000G4
Solar/Wind Harmer
10.314
970025AG2-016 GEN
Solar/Wind Harmer
0.052
971189AH1-054 GEN
Solar/Wind Harmer
0.021
219727YARDVSOLFA C
Solar/Wind Harmer
0
971667AH1-334 GEN
Solar/Wind Harmer
0.049
219276PARKLANDSO C
Solar/Wind Harmer
0
967451AG2-055 C O1
Solar/Wind Harmer
50.18
223401AF1-299 GEN
Solar/Wind Helper
0.053
223402AF1-300 C
Solar/Wind Helper
0.053
208923BUSO V4-027
Solar/Wind Helper
0.013
G-007ALTFEXP_G-007A->PJM
CMTX
10.511
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.959
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.567
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
3.752
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.798
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.487
CBM NorthLTFEXP_CBM-N->PJM
CBM
12.425
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
25.801

Details for [AG2-627] NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line l/o PJM_500_BG_P4_5_CNSTN_C_SRT-A


Base Case Flowgate

Area:PECO
Facility Description:
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line
Contingency Name:
PJM_500_BG_P4_5_CNSTN_C_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.8 %
Rating:639.0 MVA
Rating Type:B
MVA to Mitigate:669.66
MW Contribution:2.63
IPD Plant:AG2-627
Bus #Bus NameTypeMW Contribution
971011AG2-627 GEN
PJM_IPD
2.63

Details for [AG2-627] NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line l/o PECO_P4_PEACH235_SRT-A/* $ CHESCO $ PECO_P4_PEACH235 $ STBK


Base Case Flowgate

Area:PECO
Facility Description:
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line
Contingency Name:
PECO_P4_PEACH235_SRT-A/* $ CHESCO $ PECO_P4_PEACH235 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.74 %
Rating:639.0 MVA
Rating Type:B
MVA to Mitigate:669.3
MW Contribution:2.63
IPD Plant:AG2-627
Bus #Bus NameTypeMW Contribution
971011AG2-627 GEN
PJM_IPD
2.631

Details for [AG2-627] NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line l/o BGE_P4_GRACETON_51_SRT-A


Base Case Flowgate

Area:PECO
Facility Description:
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line
Contingency Name:
BGE_P4_GRACETON_51_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.71 %
Rating:639.0 MVA
Rating Type:B
MVA to Mitigate:669.13
MW Contribution:2.63
IPD Plant:AG2-627
Bus #Bus NameTypeMW Contribution
971011AG2-627 GEN
PJM_IPD
2.63

Details for [AG2-627] NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line l/o PECO_P1-2_5012_SRT-A


Base Case Flowgate

Area:PECO
Facility Description:
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line
Contingency Name:
PECO_P1-2_5012_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.71 %
Rating:639.0 MVA
Rating Type:B
MVA to Mitigate:669.13
MW Contribution:2.63
IPD Plant:AG2-627
Bus #Bus NameTypeMW Contribution
971011AG2-627 GEN
PJM_IPD
2.63

Details for NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line l/o PECO_P1-2_5012_SRT-A


Base Case Flowgate

Area:PECO
Facility Description:
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line
Contingency Name:
PECO_P1-2_5012_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:147.41 %
Rating:639.0 MVA
Rating Type:B
MVA to Mitigate:941.93
MW Contribution:0.13
Bus #Bus NameTypeMW Contribution
213508CON10-11
50/50
0.991
213508CON10-11
50/50
0.991
213518CONOW8-9
50/50
0.991
213518CONOW8-9
50/50
0.991
213515CONOW3-4
50/50
1.041
213517CONOW7
50/50
1.041
213515CONOW3-4
50/50
0.949
213516CONOW5-6
50/50
0.949
213514CONOW1-2
50/50
0.778
213516CONOW5-6
50/50
0.778
213514CONOW1-2
50/50
0.739
231918WEST 1
50/50
0.098
213893PHLISST1
50/50
1.432
213890PHLISCT3
50/50
0.992
213888PHLISCT1
50/50
0.992
213889PHLISCT2
50/50
0.992
231909HR2
50/50
0.598
231916EM3
50/50
0.412
231917EM10
50/50
0.087
231919CHRIST1
50/50
2.327
231920CHRIST2
50/50
2.327
231901EM4
50/50
0.829
231908HR1
50/50
0.595
231910HR3
50/50
0.595
213740LIBE_ST1
50/50
1.193
213738LIBE_CT1
50/50
0.916
213739LIBE_CT2
50/50
0.916
231505HR4
50/50
0.934
971983AH1-536 GEN
Solar/Wind Harmer
0.175
233968AD2-076_GEN
Solar/Wind Harmer
0.2
234014AF1-036_GEN
Solar/Wind Harmer
0.082
970597AG2-380 GEN
Solar/Wind Harmer
1.636
234012AE2-112_GEN
Solar/Wind Harmer
0.07
233984AB2-036 GEN
Solar/Wind Harmer
0.367
234041AC1-190 GEN
Solar/Wind Harmer
0.188
233987AB2-037 GEN
Solar/Wind Harmer
0
233964AF2-378 GEN
Solar/Wind Harmer
0
233946AB2-136 GEN
Solar/Wind Harmer
0
232426Y1-080 FULL
Solar/Wind Harmer
0
970277AG2-181 GEN
Solar/Wind Harmer
0.105
960671AF2-358 GEN
Solar/Wind Harmer
0.374
965821AG1-450 GEN
Solar/Wind Harmer
1.869
233940AF2-379 C
Solar/Wind Harmer
0
234015AF2-250 C
Solar/Wind Harmer
0
971195AH1-057 GEN
Solar/Wind Harmer
0.027
233923SMA
Solar/Wind Harmer
0
233998TM1NIN_3.36
Solar/Wind Harmer
0
233997TMININ_4.2
Solar/Wind Harmer
0
233996TM1833_GEN
Solar/Wind Harmer
0
233990AG1-397 GEN
Solar/Wind Harmer
0
971747AH1-380 GEN
Solar/Wind Harmer
0.074
233990AG1-397 GEN
Solar/Wind Harmer
0.59
972069AH1-584 GEN
Solar/Wind Harmer
0.184
972071AH1-585 GEN
Solar/Wind Harmer
0.184
972073AH1-586 GEN
Solar/Wind Harmer
3.315
234033AF1-007_GEN
Solar/Wind Harmer
7.648
970545AG2-347 GEN
Solar/Wind Harmer
31.505
972133AH1-634 GEN
Solar/Wind Harmer
4.773
972177AH1-672 GEN
Solar/Wind Harmer
0.274
971149AH1-027 GEN
Solar/Wind Harmer
0.089
233972AC1-094 C
Solar/Wind Harmer
0
970695AG2-447 GEN
Solar/Wind Harmer
0.07
219137THOSOLAR C
Solar/Wind Harmer
0
219258KINSLEYDEP C
Solar/Wind Harmer
0
219766PARADISE C
Solar/Wind Harmer
0
219623KINSLEYBEA C
Solar/Wind Harmer
0
971011AG2-627 GEN
Solar/Wind Harmer
0.131
219907AC1-030 C
Solar/Wind Harmer
0
228351V2-046C
Solar/Wind Harmer
0
219236SOUTHERNHQ C
Solar/Wind Harmer
0
970997AG2-616 GEN
Solar/Wind Harmer
0.162
972141AH1-641 GEN
Solar/Wind Harmer
0.049
230430AE1-229_GEN
Solar/Wind Harmer
0
945431AF1-208 GEN
Solar/Wind Harmer
0.145
219906AC1-017 C
Solar/Wind Harmer
0
219615MILLCREEK C
Solar/Wind Harmer
0
971535AH1-265 GEN
Solar/Wind Harmer
0.094
971553AH1-274 GEN
Solar/Wind Harmer
0.053
230433AD2-135 GEN
Solar/Wind Harmer
0
230407AD2-065 C
Solar/Wind Harmer
0
970453AG2-297 GEN
Solar/Wind Harmer
0.06
218660EHAMPSOLAR C
Solar/Wind Harmer
0
230422AE1-104_GEN1
Solar/Wind Harmer
12.966
230425AE1-104_GEN2
Solar/Wind Harmer
12.966
228754AB1-001 C
Solar/Wind Harmer
0
214067T20SOLAR
Solar/Wind Harmer
0
219727YARDVSOLFA C
Solar/Wind Harmer
0
207522AF2-254 C
Solar/Wind Harmer
0.029
207500AE2-000G1
Solar/Wind Harmer
11.012
207497AE2-000G2
Solar/Wind Harmer
11.012
207507AE2-000G3
Solar/Wind Harmer
11.012
207487AE2-000G4
Solar/Wind Harmer
11.012
971189AH1-054 GEN
Solar/Wind Harmer
0.023
219276PARKLANDSO C
Solar/Wind Harmer
0
970025AG2-016 GEN
Solar/Wind Harmer
0.055
971667AH1-334 GEN
Solar/Wind Harmer
0.053
219620RIDERU C
Solar/Wind Harmer
0
219817TRENTONSOL C
Solar/Wind Harmer
0
219918AC2-009 C
Solar/Wind Harmer
0
20714328BYD_X4-031
Solar/Wind Harmer
0.005
20714428HOW_X1-037
Solar/Wind Harmer
0
20720628TIN_W1-124
Solar/Wind Harmer
0
219612MATRIX C
Solar/Wind Harmer
0
218438BLK ROCK C
Solar/Wind Harmer
0
20742028HF_AC1-207
Solar/Wind Harmer
0
971521AH1-258 GEN
Solar/Wind Harmer
0.05
967451AG2-055 C O1
Solar/Wind Harmer
56.631
218526CNTRALGAS2 C
Solar/Wind Harmer
0
223401AF1-299 GEN
Solar/Wind Helper
0.063
223402AF1-300 C
Solar/Wind Helper
0.063
208923BUSO V4-027
Solar/Wind Helper
0.015
G-007ALTFEXP_G-007A->PJM
CMTX
12.048
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.129
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.666
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.379
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.931
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.9
CBM NorthLTFEXP_CBM-N->PJM
CBM
15.238
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
30.513

Details for NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line l/o PJM_500_BG_P4_5_CNSTN_C_SRT-A


Base Case Flowgate

Area:PECO
Facility Description:
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line
Contingency Name:
PJM_500_BG_P4_5_CNSTN_C_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:144.84 %
Rating:639.0 MVA
Rating Type:B
MVA to Mitigate:925.55
MW Contribution:0.13
Bus #Bus NameTypeMW Contribution
213508CON10-11
50/50
0.991
213508CON10-11
50/50
0.991
213518CONOW8-9
50/50
0.991
213518CONOW8-9
50/50
0.991
213515CONOW3-4
50/50
1.041
213517CONOW7
50/50
1.041
213515CONOW3-4
50/50
0.949
213516CONOW5-6
50/50
0.949
213514CONOW1-2
50/50
0.778
213516CONOW5-6
50/50
0.778
213514CONOW1-2
50/50
0.739
971983AH1-536 GEN
Solar/Wind Harmer
0.175
233968AD2-076_GEN
Solar/Wind Harmer
0.2
234014AF1-036_GEN
Solar/Wind Harmer
0.082
970597AG2-380 GEN
Solar/Wind Harmer
1.636
234012AE2-112_GEN
Solar/Wind Harmer
0.07
233984AB2-036 GEN
Solar/Wind Harmer
0.367
234041AC1-190 GEN
Solar/Wind Harmer
0.188
233987AB2-037 GEN
Solar/Wind Harmer
0
233964AF2-378 GEN
Solar/Wind Harmer
0
233946AB2-136 GEN
Solar/Wind Harmer
0
232426Y1-080 FULL
Solar/Wind Harmer
0
970277AG2-181 GEN
Solar/Wind Harmer
0.105
960671AF2-358 GEN
Solar/Wind Harmer
0.374
965821AG1-450 GEN
Solar/Wind Harmer
1.869
233940AF2-379 C
Solar/Wind Harmer
0
234015AF2-250 C
Solar/Wind Harmer
0
971195AH1-057 GEN
Solar/Wind Harmer
0.027
233923SMA
Solar/Wind Harmer
0
233998TM1NIN_3.36
Solar/Wind Harmer
0
233997TMININ_4.2
Solar/Wind Harmer
0
233996TM1833_GEN
Solar/Wind Harmer
0
233990AG1-397 GEN
Solar/Wind Harmer
0
971747AH1-380 GEN
Solar/Wind Harmer
0.074
233990AG1-397 GEN
Solar/Wind Harmer
0.59
972069AH1-584 GEN
Solar/Wind Harmer
0.184
972071AH1-585 GEN
Solar/Wind Harmer
0.184
972073AH1-586 GEN
Solar/Wind Harmer
3.315
234033AF1-007_GEN
Solar/Wind Harmer
7.648
970545AG2-347 GEN
Solar/Wind Harmer
31.505
972133AH1-634 GEN
Solar/Wind Harmer
4.773
972177AH1-672 GEN
Solar/Wind Harmer
0.274
971149AH1-027 GEN
Solar/Wind Harmer
0.089
233972AC1-094 C
Solar/Wind Harmer
0
970695AG2-447 GEN
Solar/Wind Harmer
0.07
219137THOSOLAR C
Solar/Wind Harmer
0
219258KINSLEYDEP C
Solar/Wind Harmer
0
219766PARADISE C
Solar/Wind Harmer
0
219623KINSLEYBEA C
Solar/Wind Harmer
0
971011AG2-627 GEN
Solar/Wind Harmer
0.131
219907AC1-030 C
Solar/Wind Harmer
0
228351V2-046C
Solar/Wind Harmer
0
219236SOUTHERNHQ C
Solar/Wind Harmer
0
970997AG2-616 GEN
Solar/Wind Harmer
0.162
972141AH1-641 GEN
Solar/Wind Harmer
0.049
230430AE1-229_GEN
Solar/Wind Harmer
0
945431AF1-208 GEN
Solar/Wind Harmer
0.145
219906AC1-017 C
Solar/Wind Harmer
0
219615MILLCREEK C
Solar/Wind Harmer
0
971535AH1-265 GEN
Solar/Wind Harmer
0.094
971553AH1-274 GEN
Solar/Wind Harmer
0.053
230433AD2-135 GEN
Solar/Wind Harmer
0
230407AD2-065 C
Solar/Wind Harmer
0
970453AG2-297 GEN
Solar/Wind Harmer
0.06
218660EHAMPSOLAR C
Solar/Wind Harmer
0
230422AE1-104_GEN1
Solar/Wind Harmer
12.966
230425AE1-104_GEN2
Solar/Wind Harmer
12.966
228754AB1-001 C
Solar/Wind Harmer
0
214067T20SOLAR
Solar/Wind Harmer
0
219727YARDVSOLFA C
Solar/Wind Harmer
0
207522AF2-254 C
Solar/Wind Harmer
0.029
207500AE2-000G1
Solar/Wind Harmer
11.012
207497AE2-000G2
Solar/Wind Harmer
11.012
207507AE2-000G3
Solar/Wind Harmer
11.012
207487AE2-000G4
Solar/Wind Harmer
11.012
971189AH1-054 GEN
Solar/Wind Harmer
0.023
219276PARKLANDSO C
Solar/Wind Harmer
0
970025AG2-016 GEN
Solar/Wind Harmer
0.055
971667AH1-334 GEN
Solar/Wind Harmer
0.053
219620RIDERU C
Solar/Wind Harmer
0
219817TRENTONSOL C
Solar/Wind Harmer
0
219918AC2-009 C
Solar/Wind Harmer
0
20714328BYD_X4-031
Solar/Wind Harmer
0.005
20714428HOW_X1-037
Solar/Wind Harmer
0
20720628TIN_W1-124
Solar/Wind Harmer
0
219612MATRIX C
Solar/Wind Harmer
0
218438BLK ROCK C
Solar/Wind Harmer
0
20742028HF_AC1-207
Solar/Wind Harmer
0
971521AH1-258 GEN
Solar/Wind Harmer
0.05
967451AG2-055 C O1
Solar/Wind Harmer
56.631
218526CNTRALGAS2 C
Solar/Wind Harmer
0
223401AF1-299 GEN
Solar/Wind Helper
0.063
223402AF1-300 C
Solar/Wind Helper
0.063
208923BUSO V4-027
Solar/Wind Helper
0.015
G-007ALTFEXP_G-007A->PJM
CMTX
12.048
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.129
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.666
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.379
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.931
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.9
CBM NorthLTFEXP_CBM-N->PJM
CBM
15.238
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
30.513

Details for NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line l/o PECO_P4_PEACH235_SRT-A/* $ CHESCO $ PECO_P4_PEACH235 $ STBK


Base Case Flowgate

Area:PECO
Facility Description:
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line
Contingency Name:
PECO_P4_PEACH235_SRT-A/* $ CHESCO $ PECO_P4_PEACH235 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:144.81 %
Rating:639.0 MVA
Rating Type:B
MVA to Mitigate:925.35
MW Contribution:0.13
Bus #Bus NameTypeMW Contribution
213508CON10-11
50/50
0.991
213508CON10-11
50/50
0.991
213518CONOW8-9
50/50
0.991
213518CONOW8-9
50/50
0.991
213515CONOW3-4
50/50
1.041
213517CONOW7
50/50
1.041
213515CONOW3-4
50/50
0.949
213516CONOW5-6
50/50
0.949
213514CONOW1-2
50/50
0.778
213516CONOW5-6
50/50
0.778
213514CONOW1-2
50/50
0.739
971983AH1-536 GEN
Solar/Wind Harmer
0.175
233968AD2-076_GEN
Solar/Wind Harmer
0.201
234014AF1-036_GEN
Solar/Wind Harmer
0.082
970597AG2-380 GEN
Solar/Wind Harmer
1.637
234012AE2-112_GEN
Solar/Wind Harmer
0.07
233984AB2-036 GEN
Solar/Wind Harmer
0.367
234041AC1-190 GEN
Solar/Wind Harmer
0.188
233987AB2-037 GEN
Solar/Wind Harmer
0
233964AF2-378 GEN
Solar/Wind Harmer
0
233946AB2-136 GEN
Solar/Wind Harmer
0
232426Y1-080 FULL
Solar/Wind Harmer
0
970277AG2-181 GEN
Solar/Wind Harmer
0.105
960671AF2-358 GEN
Solar/Wind Harmer
0.374
965821AG1-450 GEN
Solar/Wind Harmer
1.87
233940AF2-379 C
Solar/Wind Harmer
0
234015AF2-250 C
Solar/Wind Harmer
0
971195AH1-057 GEN
Solar/Wind Harmer
0.027
233923SMA
Solar/Wind Harmer
0
233998TM1NIN_3.36
Solar/Wind Harmer
0
233997TMININ_4.2
Solar/Wind Harmer
0
233996TM1833_GEN
Solar/Wind Harmer
0
233990AG1-397 GEN
Solar/Wind Harmer
0
971747AH1-380 GEN
Solar/Wind Harmer
0.074
233990AG1-397 GEN
Solar/Wind Harmer
0.59
972069AH1-584 GEN
Solar/Wind Harmer
0.184
972071AH1-585 GEN
Solar/Wind Harmer
0.184
972073AH1-586 GEN
Solar/Wind Harmer
3.317
234033AF1-007_GEN
Solar/Wind Harmer
7.652
970545AG2-347 GEN
Solar/Wind Harmer
31.523
972133AH1-634 GEN
Solar/Wind Harmer
4.776
972177AH1-672 GEN
Solar/Wind Harmer
0.274
971149AH1-027 GEN
Solar/Wind Harmer
0.089
233972AC1-094 C
Solar/Wind Harmer
0
970695AG2-447 GEN
Solar/Wind Harmer
0.07
219137THOSOLAR C
Solar/Wind Harmer
0
219258KINSLEYDEP C
Solar/Wind Harmer
0
219766PARADISE C
Solar/Wind Harmer
0
219623KINSLEYBEA C
Solar/Wind Harmer
0
971011AG2-627 GEN
Solar/Wind Harmer
0.132
219907AC1-030 C
Solar/Wind Harmer
0
228351V2-046C
Solar/Wind Harmer
0
219236SOUTHERNHQ C
Solar/Wind Harmer
0
970997AG2-616 GEN
Solar/Wind Harmer
0.162
972141AH1-641 GEN
Solar/Wind Harmer
0.049
230430AE1-229_GEN
Solar/Wind Harmer
0
945431AF1-208 GEN
Solar/Wind Harmer
0.145
219906AC1-017 C
Solar/Wind Harmer
0
219615MILLCREEK C
Solar/Wind Harmer
0
971535AH1-265 GEN
Solar/Wind Harmer
0.094
971553AH1-274 GEN
Solar/Wind Harmer
0.053
230433AD2-135 GEN
Solar/Wind Harmer
0
230407AD2-065 C
Solar/Wind Harmer
0
970453AG2-297 GEN
Solar/Wind Harmer
0.06
218660EHAMPSOLAR C
Solar/Wind Harmer
0
230422AE1-104_GEN1
Solar/Wind Harmer
12.971
230425AE1-104_GEN2
Solar/Wind Harmer
12.971
228754AB1-001 C
Solar/Wind Harmer
0
214067T20SOLAR
Solar/Wind Harmer
0
219727YARDVSOLFA C
Solar/Wind Harmer
0
207522AF2-254 C
Solar/Wind Harmer
0.029
207500AE2-000G1
Solar/Wind Harmer
11.015
207497AE2-000G2
Solar/Wind Harmer
11.015
207507AE2-000G3
Solar/Wind Harmer
11.015
207487AE2-000G4
Solar/Wind Harmer
11.015
971189AH1-054 GEN
Solar/Wind Harmer
0.023
219276PARKLANDSO C
Solar/Wind Harmer
0
970025AG2-016 GEN
Solar/Wind Harmer
0.055
971667AH1-334 GEN
Solar/Wind Harmer
0.053
219817TRENTONSOL C
Solar/Wind Harmer
0
219620RIDERU C
Solar/Wind Harmer
0
219918AC2-009 C
Solar/Wind Harmer
0
20714328BYD_X4-031
Solar/Wind Harmer
0.005
20714428HOW_X1-037
Solar/Wind Harmer
0
20720628TIN_W1-124
Solar/Wind Harmer
0
219612MATRIX C
Solar/Wind Harmer
0
218438BLK ROCK C
Solar/Wind Harmer
0
20742028HF_AC1-207
Solar/Wind Harmer
0
971521AH1-258 GEN
Solar/Wind Harmer
0.05
967451AG2-055 C O1
Solar/Wind Harmer
56.646
218526CNTRALGAS2 C
Solar/Wind Harmer
0
223401AF1-299 GEN
Solar/Wind Helper
0.063
223402AF1-300 C
Solar/Wind Helper
0.063
208923BUSO V4-027
Solar/Wind Helper
0.015
G-007ALTFEXP_G-007A->PJM
CMTX
12.051
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.129
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.666
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.38
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.931
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.901
CBM NorthLTFEXP_CBM-N->PJM
CBM
15.241
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
30.52

Details for NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line l/o PECO_P1-2_5014_SRT-A/* $ CHESCO $ PECO_P1-2_5012 $ L


Base Case Flowgate

Area:PECO
Facility Description:
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line
Contingency Name:
PECO_P1-2_5014_SRT-A/* $ CHESCO $ PECO_P1-2_5012 $ L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.18 %
Rating:639.0 MVA
Rating Type:B
MVA to Mitigate:704.06
MW Contribution:0.13
Bus #Bus NameTypeMW Contribution
213508CON10-11
50/50
0.988
213508CON10-11
50/50
0.988
213518CONOW8-9
50/50
0.988
213518CONOW8-9
50/50
0.988
213515CONOW3-4
50/50
1.038
213517CONOW7
50/50
1.038
213515CONOW3-4
50/50
0.946
213516CONOW5-6
50/50
0.946
213514CONOW1-2
50/50
0.776
213516CONOW5-6
50/50
0.776
213514CONOW1-2
50/50
0.737
970431AG2-281 GEN
50/50
4.747
231918WEST 1
50/50
0.104
232416X2-083
50/50
0.015
231919CHRIST1
50/50
2.482
231920CHRIST2
50/50
2.482
231909HR2
50/50
0.632
231916EM3
50/50
0.435
231917EM10
50/50
0.092
231901EM4
50/50
0.877
231908HR1
50/50
0.629
231910HR3
50/50
0.629
231902DC CT7
50/50
0.443
231915DC CT6
50/50
0.443
231906DC3 NUG
50/50
0.355
231907DC10
50/50
0.115
231131BLOOM ENRGY
50/50
0.122
231505HR4
50/50
0.951
971983AH1-536 GEN
Solar/Wind Harmer
0.195
233968AD2-076_GEN
Solar/Wind Harmer
0.224
234014AF1-036_GEN
Solar/Wind Harmer
0.092
970597AG2-380 GEN
Solar/Wind Harmer
1.831
234012AE2-112_GEN
Solar/Wind Harmer
0.078
233984AB2-036 GEN
Solar/Wind Harmer
0.412
234041AC1-190 GEN
Solar/Wind Harmer
0.214
233987AB2-037 GEN
Solar/Wind Harmer
0
233964AF2-378 GEN
Solar/Wind Harmer
0
233946AB2-136 GEN
Solar/Wind Harmer
0
232426Y1-080 FULL
Solar/Wind Harmer
0
970277AG2-181 GEN
Solar/Wind Harmer
0.119
960671AF2-358 GEN
Solar/Wind Harmer
0.425
965821AG1-450 GEN
Solar/Wind Harmer
2.125
233940AF2-379 C
Solar/Wind Harmer
0
234015AF2-250 C
Solar/Wind Harmer
0
971195AH1-057 GEN
Solar/Wind Harmer
0.03
233923SMA
Solar/Wind Harmer
0
233998TM1NIN_3.36
Solar/Wind Harmer
0
233997TMININ_4.2
Solar/Wind Harmer
0
233996TM1833_GEN
Solar/Wind Harmer
0
971747AH1-380 GEN
Solar/Wind Harmer
0.084
233990AG1-397 GEN
Solar/Wind Harmer
0
233990AG1-397 GEN
Solar/Wind Harmer
0.672
972069AH1-584 GEN
Solar/Wind Harmer
0.21
972071AH1-585 GEN
Solar/Wind Harmer
0.21
972073AH1-586 GEN
Solar/Wind Harmer
3.778
234033AF1-007_GEN
Solar/Wind Harmer
8.724
970545AG2-347 GEN
Solar/Wind Harmer
35.936
972133AH1-634 GEN
Solar/Wind Harmer
5.445
972177AH1-672 GEN
Solar/Wind Harmer
0.312
971149AH1-027 GEN
Solar/Wind Harmer
0.102
233972AC1-094 C
Solar/Wind Harmer
0
970695AG2-447 GEN
Solar/Wind Harmer
0.081
971011AG2-627 GEN
Solar/Wind Harmer
0.13
228351V2-046C
Solar/Wind Harmer
0
970997AG2-616 GEN
Solar/Wind Harmer
0.162
972141AH1-641 GEN
Solar/Wind Harmer
0.049
945431AF1-208 GEN
Solar/Wind Harmer
0.146
230430AE1-229_GEN
Solar/Wind Harmer
0
219137THOSOLAR C
Solar/Wind Harmer
0
970453AG2-297 GEN
Solar/Wind Harmer
0.061
971553AH1-274 GEN
Solar/Wind Harmer
0.054
219258KINSLEYDEP C
Solar/Wind Harmer
0
230433AD2-135 GEN
Solar/Wind Harmer
0
971535AH1-265 GEN
Solar/Wind Harmer
0.094
230407AD2-065 C
Solar/Wind Harmer
0
219623KINSLEYBEA C
Solar/Wind Harmer
0
230422AE1-104_GEN1
Solar/Wind Harmer
13.092
230425AE1-104_GEN2
Solar/Wind Harmer
13.092
219766PARADISE C
Solar/Wind Harmer
0
228754AB1-001 C
Solar/Wind Harmer
0
219907AC1-030 C
Solar/Wind Harmer
0
219236SOUTHERNHQ C
Solar/Wind Harmer
0
218660EHAMPSOLAR C
Solar/Wind Harmer
0
219906AC1-017 C
Solar/Wind Harmer
0
219615MILLCREEK C
Solar/Wind Harmer
0
214067T20SOLAR
Solar/Wind Harmer
0
207522AF2-254 C
Solar/Wind Harmer
0.027
207500AE2-000G1
Solar/Wind Harmer
10.314
207497AE2-000G2
Solar/Wind Harmer
10.314
207507AE2-000G3
Solar/Wind Harmer
10.314
207487AE2-000G4
Solar/Wind Harmer
10.314
970025AG2-016 GEN
Solar/Wind Harmer
0.052
971189AH1-054 GEN
Solar/Wind Harmer
0.021
219727YARDVSOLFA C
Solar/Wind Harmer
0
971667AH1-334 GEN
Solar/Wind Harmer
0.049
219276PARKLANDSO C
Solar/Wind Harmer
0
967451AG2-055 C O1
Solar/Wind Harmer
50.18
223401AF1-299 GEN
Solar/Wind Helper
0.053
223402AF1-300 C
Solar/Wind Helper
0.053
208923BUSO V4-027
Solar/Wind Helper
0.013
G-007ALTFEXP_G-007A->PJM
CMTX
10.511
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.959
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.567
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
3.752
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.798
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.487
CBM NorthLTFEXP_CBM-N->PJM
CBM
12.425
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
25.801

Details for [AG2-627] NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line l/o PJM_500_BG_P4_5_CNSTN_C_SRT-A


Base Case Flowgate

Area:PECO
Facility Description:
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line
Contingency Name:
PJM_500_BG_P4_5_CNSTN_C_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.8 %
Rating:639.0 MVA
Rating Type:B
MVA to Mitigate:669.66
MW Contribution:2.63
IPD Plant:AG2-627
Bus #Bus NameTypeMW Contribution
971011AG2-627 GEN
PJM_IPD
2.63

Details for [AG2-627] NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line l/o PECO_P4_PEACH235_SRT-A/* $ CHESCO $ PECO_P4_PEACH235 $ STBK


Base Case Flowgate

Area:PECO
Facility Description:
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line
Contingency Name:
PECO_P4_PEACH235_SRT-A/* $ CHESCO $ PECO_P4_PEACH235 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.74 %
Rating:639.0 MVA
Rating Type:B
MVA to Mitigate:669.3
MW Contribution:2.63
IPD Plant:AG2-627
Bus #Bus NameTypeMW Contribution
971011AG2-627 GEN
PJM_IPD
2.631

Details for [AG2-627] NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line l/o PECO_P1-2_5012_SRT-A


Base Case Flowgate

Area:PECO
Facility Description:
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line
Contingency Name:
PECO_P1-2_5012_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.71 %
Rating:639.0 MVA
Rating Type:B
MVA to Mitigate:669.13
MW Contribution:2.63
IPD Plant:AG2-627
Bus #Bus NameTypeMW Contribution
971011AG2-627 GEN
PJM_IPD
2.63

Details for [AG2-627] NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line l/o BGE_P4_GRACETON_51_SRT-A


Base Case Flowgate

Area:PECO
Facility Description:
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line
Contingency Name:
BGE_P4_GRACETON_51_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.71 %
Rating:639.0 MVA
Rating Type:B
MVA to Mitigate:669.13
MW Contribution:2.63
IPD Plant:AG2-627
Bus #Bus NameTypeMW Contribution
971011AG2-627 GEN
PJM_IPD
2.63

Details for PCHBTM1N-CHAN 500.0 kV Ckt 1 line l/o PECO_P1-2_5012_SRT-A


Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1N-CHAN 500.0 kV Ckt 1 line
Contingency Name:
PECO_P1-2_5012_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:152.01 %
Rating:3926.0 MVA
Rating Type:B
MVA to Mitigate:5967.81
MW Contribution:0.62
Bus #Bus NameTypeMW Contribution
200035PCHBTM 3
50/50
41.449
200202DELTA2 ST
50/50
12.612
200200DELTA2 CT1
50/50
7.06
200201DELTA2 CT2
50/50
7.06
200195DELTA ST
50/50
6.24
200192DELTA CT1
50/50
3.743
200193DELTA CT2
50/50
3.743
200194DELTA CT3
50/50
3.743
200034PCHBTM 2
50/50
247.091
200203Y1-065-STG
50/50
13.847
200204Y1-065-CTG1
50/50
8.72
200205Y1-065-CTG2
50/50
8.72
200052ROCKSP 1
50/50
103.454
200053ROCKSP 2
50/50
103.454
200054ROCKSP 3
50/50
102.403
200055ROCKSP 4
50/50
102.403
233987AB2-037 GEN
Solar/Wind Harmer
0
233923SMA
Solar/Wind Harmer
-0.002
233998TM1NIN_3.36
Solar/Wind Harmer
-0.002
233997TMININ_4.2
Solar/Wind Harmer
-0.002
233996TM1833_GEN
Solar/Wind Harmer
-0.002
233940AF2-379 C
Solar/Wind Harmer
-0.002
972069AH1-584 GEN
Solar/Wind Harmer
0.966
972071AH1-585 GEN
Solar/Wind Harmer
0.966
972073AH1-586 GEN
Solar/Wind Harmer
17.39
971747AH1-380 GEN
Solar/Wind Harmer
0.386
234033AF1-007_GEN
Solar/Wind Harmer
40.414
233990AG1-397 GEN
Solar/Wind Harmer
-0.001
970545AG2-347 GEN
Solar/Wind Harmer
166.475
972133AH1-634 GEN
Solar/Wind Harmer
25.224
233990AG1-397 GEN
Solar/Wind Harmer
3.091
234015AF2-250 C
Solar/Wind Harmer
-0.001
971195AH1-057 GEN
Solar/Wind Harmer
0.139
960671AF2-358 GEN
Solar/Wind Harmer
1.931
965821AG1-450 GEN
Solar/Wind Harmer
9.656
971149AH1-027 GEN
Solar/Wind Harmer
0.483
232426Y1-080 FULL
Solar/Wind Harmer
0
970277AG2-181 GEN
Solar/Wind Harmer
0.541
233946AB2-136 GEN
Solar/Wind Harmer
-0.002
233964AF2-378 GEN
Solar/Wind Harmer
0.001
972177AH1-672 GEN
Solar/Wind Harmer
1.448
234041AC1-190 GEN
Solar/Wind Harmer
0.965
233972AC1-094 C
Solar/Wind Harmer
-0.002
970695AG2-447 GEN
Solar/Wind Harmer
0.386
233984AB2-036 GEN
Solar/Wind Harmer
1.764
233968AD2-076_GEN
Solar/Wind Harmer
0.935
234014AF1-036_GEN
Solar/Wind Harmer
0.382
970597AG2-380 GEN
Solar/Wind Harmer
7.632
234012AE2-112_GEN
Solar/Wind Harmer
0.324
971983AH1-536 GEN
Solar/Wind Harmer
0.794
970453AG2-297 GEN
Solar/Wind Harmer
0.302
971553AH1-274 GEN
Solar/Wind Harmer
0.263
945431AF1-208 GEN
Solar/Wind Harmer
0.705
970997AG2-616 GEN
Solar/Wind Harmer
0.78
972141AH1-641 GEN
Solar/Wind Harmer
0.234
230430AE1-229_GEN
Solar/Wind Harmer
-0.001
228351V2-046C
Solar/Wind Harmer
-0.002
230433AD2-135 GEN
Solar/Wind Harmer
0
230422AE1-104_GEN1
Solar/Wind Harmer
64.31
230425AE1-104_GEN2
Solar/Wind Harmer
64.31
971011AG2-627 GEN
Solar/Wind Harmer
0.619
971535AH1-265 GEN
Solar/Wind Harmer
0.453
230407AD2-065 C
Solar/Wind Harmer
0
228754AB1-001 C
Solar/Wind Harmer
-0.002
219137THOSOLAR C
Solar/Wind Harmer
0.001
219623KINSLEYBEA C
Solar/Wind Harmer
-0.001
219258KINSLEYDEP C
Solar/Wind Harmer
-0.001
219766PARADISE C
Solar/Wind Harmer
-0.001
218660EHAMPSOLAR C
Solar/Wind Harmer
-0.001
219907AC1-030 C
Solar/Wind Harmer
-0.001
219236SOUTHERNHQ C
Solar/Wind Harmer
-0.001
219906AC1-017 C
Solar/Wind Harmer
-0.001
219615MILLCREEK C
Solar/Wind Harmer
-0.001
214067T20SOLAR
Solar/Wind Harmer
-0.001
207522AF2-254 C
Solar/Wind Harmer
0.132
207500AE2-000G1
Solar/Wind Harmer
51.374
207497AE2-000G2
Solar/Wind Harmer
51.374
207507AE2-000G3
Solar/Wind Harmer
51.374
207487AE2-000G4
Solar/Wind Harmer
51.374
970025AG2-016 GEN
Solar/Wind Harmer
0.257
971189AH1-054 GEN
Solar/Wind Harmer
0.107
971667AH1-334 GEN
Solar/Wind Harmer
0.246
219727YARDVSOLFA C
Solar/Wind Harmer
0.001
219276PARKLANDSO C
Solar/Wind Harmer
0
219620RIDERU C
Solar/Wind Harmer
-0.001
219817TRENTONSOL C
Solar/Wind Harmer
0.001
20714328BYD_X4-031
Solar/Wind Harmer
0.024
20714428HOW_X1-037
Solar/Wind Harmer
-0.001
219918AC2-009 C
Solar/Wind Harmer
0
20720628TIN_W1-124
Solar/Wind Harmer
-0.001
20742028HF_AC1-207
Solar/Wind Harmer
-0.001
971521AH1-258 GEN
Solar/Wind Harmer
0.227
967451AG2-055 C O1
Solar/Wind Harmer
256.464
219612MATRIX C
Solar/Wind Harmer
0.001
218438BLK ROCK C
Solar/Wind Harmer
-0.001
218526CNTRALGAS2 C
Solar/Wind Harmer
0.001
218524CNTRALGAS1 C
Solar/Wind Harmer
0.001
218428ETC SOLAR C
Solar/Wind Harmer
0
217213AMBOY SO C
Solar/Wind Harmer
-0.001
219249CENTRALDIV C
Solar/Wind Harmer
-0.001
20673828FLE_V3-070
Solar/Wind Harmer
0.076
218449LINSOLAR C
Solar/Wind Harmer
0.001
20675428EAM_W2-061
Solar/Wind Harmer
0
217081WEATEXAS C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
217206BARNGR HS C
Solar/Wind Harmer
-0.001
217208PARK ELE C
Solar/Wind Harmer
0
207439AE1-081 C O1
Solar/Wind Harmer
0
20676328BVR_Y1-020
Solar/Wind Harmer
0
20674628WNG_W3-110
Solar/Wind Harmer
-0.001
207511W3-106 GEN
Solar/Wind Harmer
0.043
971009AG2-626 GEN
Solar/Wind Harmer
0.1
971007AG2-625 GEN
Solar/Wind Harmer
0.157
971519AH1-257 GEN
Solar/Wind Harmer
0.154
207437AD2-070 GEN
Solar/Wind Harmer
-0.001
966181AG1-487 GEN
Solar/Wind Harmer
0
966181AG1-487 GEN
Solar/Wind Harmer
2.878
966111AG1-480 GEN
Solar/Wind Harmer
0
966111AG1-480 GEN
Solar/Wind Harmer
2.552
209029WAYMART-WD
Solar/Wind Harmer
4.195
970095AG2-074 GEN
Solar/Wind Harmer
0.207
208972BECR K09
Solar/Wind Harmer
1.468
3138216PACIFIC
Solar/Wind Helper
0.061
316411AF1-147_GEN1
Solar/Wind Helper
0.292
316415AF1-147_GEN2
Solar/Wind Helper
0.292
3141196NOKESVL
Solar/Wind Helper
1.431
238175AF1-290_GEN
Solar/Wind Helper
0.455
316006AB2-029 C
Solar/Wind Helper
0.112
238169AE2-226 GEN1
Solar/Wind Helper
0.28
238170AE2-226 GEN2
Solar/Wind Helper
0.28
964441AG1-307 GEN
Solar/Wind Helper
0.45
315651AD1-115 GEN
Solar/Wind Helper
0.844
316045AC1-158 PL2
Solar/Wind Helper
1.309
316447AC1-158 HLD
Solar/Wind Helper
0.9
316044AC1-158 PL1
Solar/Wind Helper
0.409
316450AC1-158 RIC
Solar/Wind Helper
0.109
316254AC1-120 GEN1
Solar/Wind Helper
0.337
316170AC1-121 GEN2
Solar/Wind Helper
0.112
3141426STAFORD
Solar/Wind Helper
0.077
316164AC1-076 GEN
Solar/Wind Helper
0.351
3132273ORANGE
Solar/Wind Helper
0.069
3147666LOUISA
Solar/Wind Helper
1.381
3147666LOUISA
Solar/Wind Helper
0.794
316192AB2-158 GEN
Solar/Wind Helper
0.489
966001AG1-469 GEN
Solar/Wind Helper
0.078
238152AF2-075_GEN
Solar/Wind Helper
0.277
238147AE2-230_GEN1
Solar/Wind Helper
0.387
238148AE2-230_GEN2
Solar/Wind Helper
0.387
238149AF1-291A_GEN
Solar/Wind Helper
0.055
966881AG1-559 GEN
Solar/Wind Helper
0.111
23546401DTGZ2-030
Solar/Wind Helper
0.055
944491AF1-114 GEN
Solar/Wind Helper
0.552
957971AF2-091 GEN
Solar/Wind Helper
0.188
235020AA1-095 C
Solar/Wind Helper
0.023
23777901MDS_W4-102
Solar/Wind Helper
0.11
316468AD1-105 GEN
Solar/Wind Helper
0.407
237061AD1-155 GEN
Solar/Wind Helper
0.412
316223AC1-118
Solar/Wind Helper
0.11
3141906WESTMOR
Solar/Wind Helper
0.137
316337AD2-073 GEN
Solar/Wind Helper
0.11
316077AC2-138 C
Solar/Wind Helper
0.077
3141813NORNECK
Solar/Wind Helper
0.341
316473AC1-191 GEN
Solar/Wind Helper
0.438
964211AG1-282 GEN
Solar/Wind Helper
0.109
966871AG1-558 GEN
Solar/Wind Helper
0.109
3141726DUNNSVL
Solar/Wind Helper
1.363
316404AE1-155 C
Solar/Wind Helper
0.695
316484AD2-074 GEN
Solar/Wind Helper
0.47
316487AF1-042 GEN
Solar/Wind Helper
0.246
961951AG1-038 GEN
Solar/Wind Helper
0.246
316312AB1-027
Solar/Wind Helper
0.137
3142416OLDCHRC
Solar/Wind Helper
0.884
3142416OLDCHRC
Solar/Wind Helper
0.339
3141783LANCAST
Solar/Wind Helper
0.204
3141783LANCAST
Solar/Wind Helper
0.136
3138133OCRAN
Solar/Wind Helper
0.204
3138133OCRAN
Solar/Wind Helper
0.102
3141913WHIT STONE
Solar/Wind Helper
0.34
316075AC2-137 C
Solar/Wind Helper
0.109
316314AB2-024 C
Solar/Wind Helper
0.109
316233AE1-074 FULL
Solar/Wind Helper
0.109
316059AD1-063 C
Solar/Wind Helper
0.082
3143526WINTERP
Solar/Wind Helper
1.766
3143526WINTERP
Solar/Wind Helper
1.766
3141766HARMONY
Solar/Wind Helper
0.068
3143873LANEXA
Solar/Wind Helper
0.204
316203AE2-005 GEN
Solar/Wind Helper
0.709
315662AE1-191 GEN
Solar/Wind Helper
0.436
316280AD1-041 GEN
Solar/Wind Helper
0.273
315666AE1-190 GEN
Solar/Wind Helper
0.109
316441AF1-014 GEN
Solar/Wind Helper
0.109
957601AF2-054 GEN
Solar/Wind Helper
0.109
316156AD2-030 GEN
Solar/Wind Helper
0.108
3141873WAN 176
Solar/Wind Helper
0.068
3143226MDLTHAN
Solar/Wind Helper
0.339
3142433PROV 92
Solar/Wind Helper
1.358
3142543TWELFTH
Solar/Wind Helper
0.033
3142946ENON
Solar/Wind Helper
0.113
3142946ENON
Solar/Wind Helper
0.034
957831AF2-077 GEN
Solar/Wind Helper
0.109
316382AG1-145 C
Solar/Wind Helper
0.109
316159AE1-175 C
Solar/Wind Helper
0.109
316240AF1-291 C
Solar/Wind Helper
0.109
316132AB2-190 GEN1
Solar/Wind Helper
0.407
316458AB2-190 GEN2
Solar/Wind Helper
0.407
315697AD1-025 GEN
Solar/Wind Helper
0.814
316033AB2-134 GEN
Solar/Wind Helper
0.773
316369SG1_INVT
Solar/Wind Helper
0.532
315839AE2-212 C
Solar/Wind Helper
0.109
961611AG1-000B GEN
Solar/Wind Helper
0.483
316313AB2-026
Solar/Wind Helper
0.108
316236AE1-162_GEN
Solar/Wind Helper
0.108
316258AE1-075 C
Solar/Wind Helper
0.097
316405AF2-144 C
Solar/Wind Helper
0.092
3145336SMITFLD
Solar/Wind Helper
1.349
3145336SMITFLD
Solar/Wind Helper
0.135
3143316POE
Solar/Wind Helper
1.335
316294AC1-161 GEN
Solar/Wind Helper
1.3
315773AC2-141 GEN
Solar/Wind Helper
1.3
3144536CHRHLND
Solar/Wind Helper
0.051
316381AD1-082 GEN
Solar/Wind Helper
0.368
316083AB2-161 GEN
Solar/Wind Helper
0.271
316375AC2-012 GEN
Solar/Wind Helper
0.638
316036AC1-147 C
Solar/Wind Helper
0.108
3144873MCLAUGH
Solar/Wind Helper
0.008
316316AC1-027 C
Solar/Wind Helper
0.095
316336AC2-165 C
Solar/Wind Helper
0.541
316185AD1-033 GEN
Solar/Wind Helper
0.378
316072AD1-144
Solar/Wind Helper
0.081
3145506HICKORY
Solar/Wind Helper
1.346
3145506HICKORY
Solar/Wind Helper
0.807
3145506HICKORY
Solar/Wind Helper
0.202
316349AD2-085 GEN
Solar/Wind Helper
0.275
316339AD2-160 GEN
Solar/Wind Helper
0.27
316388AE2-253 GEN
Solar/Wind Helper
0.27
315833AF1-017_GEN
Solar/Wind Helper
0.216
316017AA1-139 ULT1
Solar/Wind Helper
0.324
316018AA1-139 ULT2
Solar/Wind Helper
0.324
3137176SLIGO L2192
Solar/Wind Helper
1.338
3146456SLIGO L269
Solar/Wind Helper
0.336
3146456SLIGO L269
Solar/Wind Helper
0.336
319010AE1-072 C
Solar/Wind Helper
0.81
316305AF2-043 C
Solar/Wind Helper
0.108
316246AF1-032 C
Solar/Wind Helper
0.081
3130086AYDLETT
Solar/Wind Helper
1.344
316320Y1-086
Solar/Wind Helper
0.108
313526AB2-022
Solar/Wind Helper
0.108
3146386ELIZ CT
Solar/Wind Helper
0.336
3146486SUNBURY
Solar/Wind Helper
0.336
3146486SUNBURY
Solar/Wind Helper
0.336
316321Z2-027
Solar/Wind Helper
0.108
3145176PASQUOTANK
Solar/Wind Helper
0.208
3146516WINFALL
Solar/Wind Helper
1.086
3146516WINFALL
Solar/Wind Helper
0.335
3146516WINFALL
Solar/Wind Helper
0.335
3146516WINFALL
Solar/Wind Helper
0.335
3146516WINFALL
Solar/Wind Helper
0.335
3146516WINFALL
Solar/Wind Helper
0.335
237034AC2-136 C
Solar/Wind Helper
0.064
3146626S HERTFORD
Solar/Wind Helper
0.335
3146626S HERTFORD
Solar/Wind Helper
0.335
3146626S HERTFORD
Solar/Wind Helper
0.335
316315AB2-025 C
Solar/Wind Helper
0.108
238221AF1-254 C O1
Solar/Wind Helper
0.108
3145273HOLLAND
Solar/Wind Helper
0.251
3132123MT JACKSON
Solar/Wind Helper
1.047
315742AE1-103 GEN
Solar/Wind Helper
0.215
238208AF1-136 C
Solar/Wind Helper
0.085
3146376EDENTON
Solar/Wind Helper
0.334
3130156CHOWAN
Solar/Wind Helper
0.334
3130156CHOWAN
Solar/Wind Helper
0.334
3130156CHOWAN
Solar/Wind Helper
0.334
3138266HYDRAULIC
Solar/Wind Helper
0.015
3138266HYDRAULIC
Solar/Wind Helper
0.009
316097T157 G90
Solar/Wind Helper
0.219
316095T157 G97
Solar/Wind Helper
0.219
315614AA2-178 GEN
Solar/Wind Helper
0.428
315816AE2-034 GEN
Solar/Wind Helper
0.321
3145663CRESWEL
Solar/Wind Helper
0.933
316322AB2-045
Solar/Wind Helper
0.106
3146776BUCKING
Solar/Wind Helper
1.331
3146776BUCKING
Solar/Wind Helper
0.133
3146776BUCKING
Solar/Wind Helper
0.12
3146776BUCKING
Solar/Wind Helper
0.108
3156081AA2-088 GEN
Solar/Wind Helper
0.534
3130546PLYMOUTH
Solar/Wind Helper
0.332
315732AD1-074 GEN1
Solar/Wind Helper
0.801
315733AD1-074 GEN2
Solar/Wind Helper
0.801
315737AD1-076 GEN
Solar/Wind Helper
0.582
315735AD1-075 GEN1
Solar/Wind Helper
0.4
3147983MERCK5
Solar/Wind Helper
0.133
3146926FARMVIL
Solar/Wind Helper
0.199
3146926FARMVIL
Solar/Wind Helper
0.199
316065AD1-022 GEN
Solar/Wind Helper
0.427
316023GEN1_S
Solar/Wind Helper
0.267
316365GEN2_N
Solar/Wind Helper
0.267
3146206CASHIE
Solar/Wind Helper
0.332
3146206CASHIE
Solar/Wind Helper
0.332
3146206CASHIE
Solar/Wind Helper
0.332
3145893MURPHYS
Solar/Wind Helper
1.328
3145893MURPHYS
Solar/Wind Helper
1.062
3145893MURPHYS
Solar/Wind Helper
0.896
316318V4-068
Solar/Wind Helper
0.025
3145893MURPHYS
Solar/Wind Helper
0.597
3145893MURPHYS
Solar/Wind Helper
0.332
3145893MURPHYS
Solar/Wind Helper
0.332
3145893MURPHYS
Solar/Wind Helper
0.266
315821AE2-092 GEN
Solar/Wind Helper
0.735
316499AE2-029_GEN
Solar/Wind Helper
0.266
3146173TUNIS
Solar/Wind Helper
0.331
3146173TUNIS
Solar/Wind Helper
0.331
3146173TUNIS
Solar/Wind Helper
0.331
3146173TUNIS
Solar/Wind Helper
0.331
942461AE2-259 GEN
Solar/Wind Helper
0.532
3156021HOLLOMANSOL
Solar/Wind Helper
0.532
316463AE2-346 GEN
Solar/Wind Helper
0.064
316140AB2-099
Solar/Wind Helper
0.027
961941AG1-037 GEN
Solar/Wind Helper
0.027
3145513AHOSKIE
Solar/Wind Helper
0.331
3145513AHOSKIE
Solar/Wind Helper
0.331
946281AF1-292 GEN
Solar/Wind Helper
0.079
966621AG1-532 GEN
Solar/Wind Helper
0.072
3146043SEABORD
Solar/Wind Helper
0.331
3145683EARLEYS
Solar/Wind Helper
0.662
3145683EARLEYS
Solar/Wind Helper
0.331
3145683EARLEYS
Solar/Wind Helper
0.331
3145683EARLEYS
Solar/Wind Helper
0.331
315607AA1-063A GEN
Solar/Wind Helper
0.399
316087AB2-174 GEN
Solar/Wind Helper
0.425
3146263WOODLND
Solar/Wind Helper
0.331
3146263WOODLND
Solar/Wind Helper
0.331
316181AB2-040 GEN
Solar/Wind Helper
0.425
313506AB2-031 GEN
Solar/Wind Helper
0.317
3147133PAMPLIN
Solar/Wind Helper
1.038
3147133PAMPLIN
Solar/Wind Helper
0.331
3147133PAMPLIN
Solar/Wind Helper
0.265
237080AD1-060 GEN
Solar/Wind Helper
0.08
3148013FISHERV
Solar/Wind Helper
0.331
3148133STUARTS
Solar/Wind Helper
0.198
3148013FISHERV
Solar/Wind Helper
0.19
3137643SOCKMAN
Solar/Wind Helper
1.321
3147043LAWRENC
Solar/Wind Helper
0.198
3142666NORTHAMPTON
Solar/Wind Helper
0.33
3142666NORTHAMPTON
Solar/Wind Helper
0.33
3142666NORTHAMPTON
Solar/Wind Helper
0.33
3142666NORTHAMPTON
Solar/Wind Helper
0.33
3142666NORTHAMPTON
Solar/Wind Helper
0.198
316426AA2-053 GEN
Solar/Wind Helper
0.398
316190AA2-174 GEN
Solar/Wind Helper
0.027
3145963POPLR C
Solar/Wind Helper
0.33
3145963POPLR C
Solar/Wind Helper
0.33
316011AB1-132 GEN
Solar/Wind Helper
7.929
316317KELFORD C
Solar/Wind Helper
0.123
3145823KELFORD
Solar/Wind Helper
0.33
3145823KELFORD
Solar/Wind Helper
0.33
3145593CAROLNA
Solar/Wind Helper
0.33
3145593CAROLNA
Solar/Wind Helper
0.33
316174AB2-169 GEN
Solar/Wind Helper
0.392
316478AD1-087 GEN
Solar/Wind Helper
0.34
316486AD2-202 GEN
Solar/Wind Helper
0.1
3145783HORNRTN
Solar/Wind Helper
0.33
23583801GRNGAP
Solar/Wind Helper
0.551
3145796HORNRTN
Solar/Wind Helper
1.319
3145796HORNRTN
Solar/Wind Helper
1.088
3145796HORNRTN
Solar/Wind Helper
1.055
3145796HORNRTN
Solar/Wind Helper
0.989
3145796HORNRTN
Solar/Wind Helper
0.33
3145796HORNRTN
Solar/Wind Helper
0.33
3145796HORNRTN
Solar/Wind Helper
0.132
316034AC1-036 C
Solar/Wind Helper
0.073
3144303KENBRDG
Solar/Wind Helper
0.264
3146033SCOT NK
Solar/Wind Helper
1.318
315785AD2-033 C
Solar/Wind Helper
0.688
316129AC1-054 GEN
Solar/Wind Helper
0.344
316210AC1-098 GEN
Solar/Wind Helper
0.476
316212AC1-099_GEN
Solar/Wind Helper
0.264
316131AB2-060 GEN
Solar/Wind Helper
0.423
238108AE1-109 GEN1
Solar/Wind Helper
0.035
238109AE1-109 GEN2
Solar/Wind Helper
0.035
238110AE1-109 GEN3
Solar/Wind Helper
0.035
313527AB2-043 GEN
Solar/Wind Helper
0.264
3145933PARMELE
Solar/Wind Helper
0.658
3145933PARMELE
Solar/Wind Helper
0.329
3145933PARMELE
Solar/Wind Helper
0.329
316274AC1-208 GEN
Solar/Wind Helper
0.423
316239AB2-077_GEN
Solar/Wind Helper
0.106
316238AB2-078_GEN
Solar/Wind Helper
0.106
316237AB2-079_GEN
Solar/Wind Helper
0.106
315687AD1-152 GEN
Solar/Wind Helper
0.422
316005AA1-067
Solar/Wind Helper
0.079
3145746EVERETS
Solar/Wind Helper
1.306
3145746EVERETS
Solar/Wind Helper
0.328
3145746EVERETS
Solar/Wind Helper
0.328
3145746EVERETS
Solar/Wind Helper
0.328
3145746EVERETS
Solar/Wind Helper
0.328
3145746EVERETS
Solar/Wind Helper
0.328
3145746EVERETS
Solar/Wind Helper
0.328
3145746EVERETS
Solar/Wind Helper
0.328
315722AD1-056 GEN
Solar/Wind Helper
0.316
315724AD1-057 GEN
Solar/Wind Helper
0.174
316327AA2-057 GEN
Solar/Wind Helper
0.395
270494AE1-108_GEN
Solar/Wind Helper
0.787
316494AC1-189 GEN
Solar/Wind Helper
0.421
316420AA1-050 GEN
Solar/Wind Helper
0.421
316319Z2-044 C
Solar/Wind Helper
0.063
3146233WITAKRS
Solar/Wind Helper
1.302
3146233WITAKRS
Solar/Wind Helper
0.222
961671AG1-007 GEN
Solar/Wind Helper
0.049
3145573BETHELC
Solar/Wind Helper
0.327
3145573BETHELC
Solar/Wind Helper
0.327
3146073TAR RVR
Solar/Wind Helper
0.327
3146083TARBORO
Solar/Wind Helper
0.327
3146083TARBORO
Solar/Wind Helper
0.327
3138543CONSLDL
Solar/Wind Helper
0.216
3146843MT LREL
Solar/Wind Helper
0.327
3146843MT LREL
Solar/Wind Helper
0.327
237038AE2-054 C
Solar/Wind Helper
0.105
3145543BTLEBRO
Solar/Wind Helper
0.326
3145543BTLEBRO
Solar/Wind Helper
0.326
3145543BTLEBRO
Solar/Wind Helper
0.326
3145543BTLEBRO
Solar/Wind Helper
0.261
316359AB2-059 GEN
Solar/Wind Helper
0.524
316049AB1-081 GEN
Solar/Wind Helper
0.419
235067AD1-061 GEN
Solar/Wind Helper
0.105
3148463FAIRFLD
Solar/Wind Helper
0.326
316118AC1-105 GEN
Solar/Wind Helper
0.267
316248AF1-058 C
Solar/Wind Helper
0.105
3147173SINAI
Solar/Wind Helper
0.325
3147243WELCO
Solar/Wind Helper
0.203
316003AC1-222 GEN
Solar/Wind Helper
0.338
237085AD2-009_GEN
Solar/Wind Helper
0.365
237002AB1-128_GEN
Solar/Wind Helper
0.104
237001AB1-127_GEN
Solar/Wind Helper
0.104
316222AC1-221 GEN
Solar/Wind Helper
0.388
964991AG1-363 GEN
Solar/Wind Helper
1.549
316283AC2-100 C
Solar/Wind Helper
0.362
235062AE1-101 C1
Solar/Wind Helper
0.387
235063AE1-101 C2
Solar/Wind Helper
0.387
316123AC1-075 GEN
Solar/Wind Helper
0.412
23779801AA1-109
Solar/Wind Helper
0.046
270455AD2-022 GEN
Solar/Wind Helper
0.491
270457AD2-023 GEN
Solar/Wind Helper
0.276
226929AD2-058 GEN
Solar/Wind Helper
0.028
3147123OTTER R
Solar/Wind Helper
0.19
23777801MSM_W1-116
Solar/Wind Helper
0.071
316217AC1-145 GEN
Solar/Wind Helper
0.253
316197AC1-042 GEN
Solar/Wind Helper
0.213
3147312GRETNA
Solar/Wind Helper
0.252
3146802CHATHAM
Solar/Wind Helper
0.236
3147312GRETNA
Solar/Wind Helper
0.063
270016AE1-250 BESS
Solar/Wind Helper
0.379
270013AE1-250 PV
Solar/Wind Helper
0.379
270197AD1-017 GEN1
Solar/Wind Helper
0.303
270574AD1-017 GEN2
Solar/Wind Helper
0.303
270173AC1-122 GEN
Solar/Wind Helper
0.382
23750701CROSSCHOOL
Solar/Wind Helper
0.136
270018AE2-047 C O1
Solar/Wind Helper
0.251
G-007ALTFEXP_G-007A->PJM
CMTX
53.176
HAMLETPJM->LTFIMP_HAMLET
CLTF
5.859
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.503
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
24.367
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
5.217
BlueGrassPJM->LTFIMP_BlueG
CLTF
16.247
CBM NorthLTFEXP_CBM-N->PJM
CBM
59.298
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
130.559

Details for PCHBTM1N-CHAN 500.0 kV Ckt 1 line l/o BGE_P4_GRACETON_51_SRT-A


Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1N-CHAN 500.0 kV Ckt 1 line
Contingency Name:
BGE_P4_GRACETON_51_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:152.0 %
Rating:3926.0 MVA
Rating Type:B
MVA to Mitigate:5967.69
MW Contribution:0.62
Bus #Bus NameTypeMW Contribution
200035PCHBTM 3
50/50
41.449
200202DELTA2 ST
50/50
12.612
200200DELTA2 CT1
50/50
7.06
200201DELTA2 CT2
50/50
7.06
200195DELTA ST
50/50
6.24
200192DELTA CT1
50/50
3.743
200193DELTA CT2
50/50
3.743
200194DELTA CT3
50/50
3.743
200034PCHBTM 2
50/50
247.091
200203Y1-065-STG
50/50
13.847
200204Y1-065-CTG1
50/50
8.72
200205Y1-065-CTG2
50/50
8.72
200052ROCKSP 1
50/50
103.454
200053ROCKSP 2
50/50
103.454
200054ROCKSP 3
50/50
102.403
200055ROCKSP 4
50/50
102.403
233987AB2-037 GEN
Solar/Wind Harmer
0
233923SMA
Solar/Wind Harmer
-0.002
233998TM1NIN_3.36
Solar/Wind Harmer
-0.002
233997TMININ_4.2
Solar/Wind Harmer
-0.002
233996TM1833_GEN
Solar/Wind Harmer
-0.002
233940AF2-379 C
Solar/Wind Harmer
-0.002
972069AH1-584 GEN
Solar/Wind Harmer
0.966
972071AH1-585 GEN
Solar/Wind Harmer
0.966
972073AH1-586 GEN
Solar/Wind Harmer
17.39
971747AH1-380 GEN
Solar/Wind Harmer
0.386
234033AF1-007_GEN
Solar/Wind Harmer
40.414
233990AG1-397 GEN
Solar/Wind Harmer
-0.001
970545AG2-347 GEN
Solar/Wind Harmer
166.475
972133AH1-634 GEN
Solar/Wind Harmer
25.224
233990AG1-397 GEN
Solar/Wind Harmer
3.091
234015AF2-250 C
Solar/Wind Harmer
-0.001
971195AH1-057 GEN
Solar/Wind Harmer
0.139
960671AF2-358 GEN
Solar/Wind Harmer
1.931
965821AG1-450 GEN
Solar/Wind Harmer
9.656
971149AH1-027 GEN
Solar/Wind Harmer
0.483
232426Y1-080 FULL
Solar/Wind Harmer
0
970277AG2-181 GEN
Solar/Wind Harmer
0.541
233946AB2-136 GEN
Solar/Wind Harmer
-0.002
233964AF2-378 GEN
Solar/Wind Harmer
0.001
972177AH1-672 GEN
Solar/Wind Harmer
1.448
234041AC1-190 GEN
Solar/Wind Harmer
0.965
233972AC1-094 C
Solar/Wind Harmer
-0.002
970695AG2-447 GEN
Solar/Wind Harmer
0.386
233984AB2-036 GEN
Solar/Wind Harmer
1.764
233968AD2-076_GEN
Solar/Wind Harmer
0.935
234014AF1-036_GEN
Solar/Wind Harmer
0.382
970597AG2-380 GEN
Solar/Wind Harmer
7.632
234012AE2-112_GEN
Solar/Wind Harmer
0.324
971983AH1-536 GEN
Solar/Wind Harmer
0.794
970453AG2-297 GEN
Solar/Wind Harmer
0.302
971553AH1-274 GEN
Solar/Wind Harmer
0.263
945431AF1-208 GEN
Solar/Wind Harmer
0.705
970997AG2-616 GEN
Solar/Wind Harmer
0.78
972141AH1-641 GEN
Solar/Wind Harmer
0.234
230430AE1-229_GEN
Solar/Wind Harmer
-0.001
228351V2-046C
Solar/Wind Harmer
-0.002
230433AD2-135 GEN
Solar/Wind Harmer
0
230422AE1-104_GEN1
Solar/Wind Harmer
64.31
230425AE1-104_GEN2
Solar/Wind Harmer
64.31
971011AG2-627 GEN
Solar/Wind Harmer
0.619
971535AH1-265 GEN
Solar/Wind Harmer
0.453
230407AD2-065 C
Solar/Wind Harmer
0
228754AB1-001 C
Solar/Wind Harmer
-0.002
219137THOSOLAR C
Solar/Wind Harmer
0.001
219623KINSLEYBEA C
Solar/Wind Harmer
-0.001
219258KINSLEYDEP C
Solar/Wind Harmer
-0.001
219766PARADISE C
Solar/Wind Harmer
-0.001
218660EHAMPSOLAR C
Solar/Wind Harmer
-0.001
219907AC1-030 C
Solar/Wind Harmer
-0.001
219236SOUTHERNHQ C
Solar/Wind Harmer
-0.001
219906AC1-017 C
Solar/Wind Harmer
-0.001
219615MILLCREEK C
Solar/Wind Harmer
-0.001
214067T20SOLAR
Solar/Wind Harmer
-0.001
207522AF2-254 C
Solar/Wind Harmer
0.132
207500AE2-000G1
Solar/Wind Harmer
51.374
207497AE2-000G2
Solar/Wind Harmer
51.374
207507AE2-000G3
Solar/Wind Harmer
51.374
207487AE2-000G4
Solar/Wind Harmer
51.374
970025AG2-016 GEN
Solar/Wind Harmer
0.257
971189AH1-054 GEN
Solar/Wind Harmer
0.107
971667AH1-334 GEN
Solar/Wind Harmer
0.246
219727YARDVSOLFA C
Solar/Wind Harmer
0.001
219276PARKLANDSO C
Solar/Wind Harmer
0
219620RIDERU C
Solar/Wind Harmer
-0.001
219817TRENTONSOL C
Solar/Wind Harmer
0.001
20714328BYD_X4-031
Solar/Wind Harmer
0.024
20714428HOW_X1-037
Solar/Wind Harmer
-0.001
219918AC2-009 C
Solar/Wind Harmer
0
20720628TIN_W1-124
Solar/Wind Harmer
-0.001
20742028HF_AC1-207
Solar/Wind Harmer
-0.001
971521AH1-258 GEN
Solar/Wind Harmer
0.227
967451AG2-055 C O1
Solar/Wind Harmer
256.464
219612MATRIX C
Solar/Wind Harmer
0.001
218438BLK ROCK C
Solar/Wind Harmer
-0.001
218526CNTRALGAS2 C
Solar/Wind Harmer
0.001
218524CNTRALGAS1 C
Solar/Wind Harmer
0.001
218428ETC SOLAR C
Solar/Wind Harmer
0
217213AMBOY SO C
Solar/Wind Harmer
-0.001
219249CENTRALDIV C
Solar/Wind Harmer
-0.001
20673828FLE_V3-070
Solar/Wind Harmer
0.076
218449LINSOLAR C
Solar/Wind Harmer
0.001
20675428EAM_W2-061
Solar/Wind Harmer
0
217081WEATEXAS C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
217206BARNGR HS C
Solar/Wind Harmer
-0.001
217208PARK ELE C
Solar/Wind Harmer
0
207439AE1-081 C O1
Solar/Wind Harmer
0
20676328BVR_Y1-020
Solar/Wind Harmer
0
20674628WNG_W3-110
Solar/Wind Harmer
-0.001
207511W3-106 GEN
Solar/Wind Harmer
0.043
971009AG2-626 GEN
Solar/Wind Harmer
0.1
971007AG2-625 GEN
Solar/Wind Harmer
0.157
971519AH1-257 GEN
Solar/Wind Harmer
0.154
207437AD2-070 GEN
Solar/Wind Harmer
-0.001
966181AG1-487 GEN
Solar/Wind Harmer
0
966181AG1-487 GEN
Solar/Wind Harmer
2.878
966111AG1-480 GEN
Solar/Wind Harmer
0
966111AG1-480 GEN
Solar/Wind Harmer
2.552
209029WAYMART-WD
Solar/Wind Harmer
4.195
970095AG2-074 GEN
Solar/Wind Harmer
0.207
208972BECR K09
Solar/Wind Harmer
1.468
3138216PACIFIC
Solar/Wind Helper
0.061
316411AF1-147_GEN1
Solar/Wind Helper
0.292
316415AF1-147_GEN2
Solar/Wind Helper
0.292
3141196NOKESVL
Solar/Wind Helper
1.431
238175AF1-290_GEN
Solar/Wind Helper
0.455
316006AB2-029 C
Solar/Wind Helper
0.112
238169AE2-226 GEN1
Solar/Wind Helper
0.28
238170AE2-226 GEN2
Solar/Wind Helper
0.28
964441AG1-307 GEN
Solar/Wind Helper
0.45
315651AD1-115 GEN
Solar/Wind Helper
0.844
316045AC1-158 PL2
Solar/Wind Helper
1.309
316447AC1-158 HLD
Solar/Wind Helper
0.9
316044AC1-158 PL1
Solar/Wind Helper
0.409
316450AC1-158 RIC
Solar/Wind Helper
0.109
316254AC1-120 GEN1
Solar/Wind Helper
0.337
316170AC1-121 GEN2
Solar/Wind Helper
0.112
3141426STAFORD
Solar/Wind Helper
0.077
316164AC1-076 GEN
Solar/Wind Helper
0.351
3132273ORANGE
Solar/Wind Helper
0.069
3147666LOUISA
Solar/Wind Helper
1.381
3147666LOUISA
Solar/Wind Helper
0.794
316192AB2-158 GEN
Solar/Wind Helper
0.489
966001AG1-469 GEN
Solar/Wind Helper
0.078
238152AF2-075_GEN
Solar/Wind Helper
0.277
238147AE2-230_GEN1
Solar/Wind Helper
0.387
238148AE2-230_GEN2
Solar/Wind Helper
0.387
238149AF1-291A_GEN
Solar/Wind Helper
0.055
966881AG1-559 GEN
Solar/Wind Helper
0.111
23546401DTGZ2-030
Solar/Wind Helper
0.055
944491AF1-114 GEN
Solar/Wind Helper
0.552
957971AF2-091 GEN
Solar/Wind Helper
0.188
235020AA1-095 C
Solar/Wind Helper
0.023
23777901MDS_W4-102
Solar/Wind Helper
0.11
316468AD1-105 GEN
Solar/Wind Helper
0.407
237061AD1-155 GEN
Solar/Wind Helper
0.412
316223AC1-118
Solar/Wind Helper
0.11
3141906WESTMOR
Solar/Wind Helper
0.137
316337AD2-073 GEN
Solar/Wind Helper
0.11
316077AC2-138 C
Solar/Wind Helper
0.077
3141813NORNECK
Solar/Wind Helper
0.341
316473AC1-191 GEN
Solar/Wind Helper
0.438
964211AG1-282 GEN
Solar/Wind Helper
0.109
966871AG1-558 GEN
Solar/Wind Helper
0.109
3141726DUNNSVL
Solar/Wind Helper
1.363
316404AE1-155 C
Solar/Wind Helper
0.695
316484AD2-074 GEN
Solar/Wind Helper
0.47
316487AF1-042 GEN
Solar/Wind Helper
0.246
961951AG1-038 GEN
Solar/Wind Helper
0.246
316312AB1-027
Solar/Wind Helper
0.137
3142416OLDCHRC
Solar/Wind Helper
0.884
3142416OLDCHRC
Solar/Wind Helper
0.339
3141783LANCAST
Solar/Wind Helper
0.204
3141783LANCAST
Solar/Wind Helper
0.136
3138133OCRAN
Solar/Wind Helper
0.204
3138133OCRAN
Solar/Wind Helper
0.102
3141913WHIT STONE
Solar/Wind Helper
0.34
316075AC2-137 C
Solar/Wind Helper
0.109
316314AB2-024 C
Solar/Wind Helper
0.109
316233AE1-074 FULL
Solar/Wind Helper
0.109
316059AD1-063 C
Solar/Wind Helper
0.082
3143526WINTERP
Solar/Wind Helper
1.766
3143526WINTERP
Solar/Wind Helper
1.766
3141766HARMONY
Solar/Wind Helper
0.068
3143873LANEXA
Solar/Wind Helper
0.204
316203AE2-005 GEN
Solar/Wind Helper
0.709
315662AE1-191 GEN
Solar/Wind Helper
0.436
316280AD1-041 GEN
Solar/Wind Helper
0.273
315666AE1-190 GEN
Solar/Wind Helper
0.109
316441AF1-014 GEN
Solar/Wind Helper
0.109
957601AF2-054 GEN
Solar/Wind Helper
0.109
316156AD2-030 GEN
Solar/Wind Helper
0.108
3141873WAN 176
Solar/Wind Helper
0.068
3143226MDLTHAN
Solar/Wind Helper
0.339
3142433PROV 92
Solar/Wind Helper
1.358
3142543TWELFTH
Solar/Wind Helper
0.033
3142946ENON
Solar/Wind Helper
0.113
3142946ENON
Solar/Wind Helper
0.034
957831AF2-077 GEN
Solar/Wind Helper
0.109
316382AG1-145 C
Solar/Wind Helper
0.109
316159AE1-175 C
Solar/Wind Helper
0.109
316240AF1-291 C
Solar/Wind Helper
0.109
316132AB2-190 GEN1
Solar/Wind Helper
0.407
316458AB2-190 GEN2
Solar/Wind Helper
0.407
315697AD1-025 GEN
Solar/Wind Helper
0.814
316033AB2-134 GEN
Solar/Wind Helper
0.773
316369SG1_INVT
Solar/Wind Helper
0.532
315839AE2-212 C
Solar/Wind Helper
0.109
961611AG1-000B GEN
Solar/Wind Helper
0.483
316313AB2-026
Solar/Wind Helper
0.108
316236AE1-162_GEN
Solar/Wind Helper
0.108
316258AE1-075 C
Solar/Wind Helper
0.097
316405AF2-144 C
Solar/Wind Helper
0.092
3145336SMITFLD
Solar/Wind Helper
1.349
3145336SMITFLD
Solar/Wind Helper
0.135
3143316POE
Solar/Wind Helper
1.335
316294AC1-161 GEN
Solar/Wind Helper
1.3
315773AC2-141 GEN
Solar/Wind Helper
1.3
3144536CHRHLND
Solar/Wind Helper
0.051
316381AD1-082 GEN
Solar/Wind Helper
0.368
316083AB2-161 GEN
Solar/Wind Helper
0.271
316375AC2-012 GEN
Solar/Wind Helper
0.638
316036AC1-147 C
Solar/Wind Helper
0.108
3144873MCLAUGH
Solar/Wind Helper
0.008
316316AC1-027 C
Solar/Wind Helper
0.095
316336AC2-165 C
Solar/Wind Helper
0.541
316185AD1-033 GEN
Solar/Wind Helper
0.378
316072AD1-144
Solar/Wind Helper
0.081
3145506HICKORY
Solar/Wind Helper
1.346
3145506HICKORY
Solar/Wind Helper
0.807
3145506HICKORY
Solar/Wind Helper
0.202
316349AD2-085 GEN
Solar/Wind Helper
0.275
316339AD2-160 GEN
Solar/Wind Helper
0.27
316388AE2-253 GEN
Solar/Wind Helper
0.27
315833AF1-017_GEN
Solar/Wind Helper
0.216
316017AA1-139 ULT1
Solar/Wind Helper
0.324
316018AA1-139 ULT2
Solar/Wind Helper
0.324
3137176SLIGO L2192
Solar/Wind Helper
1.338
3146456SLIGO L269
Solar/Wind Helper
0.336
3146456SLIGO L269
Solar/Wind Helper
0.336
319010AE1-072 C
Solar/Wind Helper
0.81
316305AF2-043 C
Solar/Wind Helper
0.108
316246AF1-032 C
Solar/Wind Helper
0.081
3130086AYDLETT
Solar/Wind Helper
1.344
316320Y1-086
Solar/Wind Helper
0.108
313526AB2-022
Solar/Wind Helper
0.108
3146386ELIZ CT
Solar/Wind Helper
0.336
3146486SUNBURY
Solar/Wind Helper
0.336
3146486SUNBURY
Solar/Wind Helper
0.336
316321Z2-027
Solar/Wind Helper
0.108
3145176PASQUOTANK
Solar/Wind Helper
0.208
3146516WINFALL
Solar/Wind Helper
1.086
3146516WINFALL
Solar/Wind Helper
0.335
3146516WINFALL
Solar/Wind Helper
0.335
3146516WINFALL
Solar/Wind Helper
0.335
3146516WINFALL
Solar/Wind Helper
0.335
3146516WINFALL
Solar/Wind Helper
0.335
237034AC2-136 C
Solar/Wind Helper
0.064
3146626S HERTFORD
Solar/Wind Helper
0.335
3146626S HERTFORD
Solar/Wind Helper
0.335
3146626S HERTFORD
Solar/Wind Helper
0.335
316315AB2-025 C
Solar/Wind Helper
0.108
238221AF1-254 C O1
Solar/Wind Helper
0.108
3145273HOLLAND
Solar/Wind Helper
0.251
3132123MT JACKSON
Solar/Wind Helper
1.047
315742AE1-103 GEN
Solar/Wind Helper
0.215
238208AF1-136 C
Solar/Wind Helper
0.085
3146376EDENTON
Solar/Wind Helper
0.334
3130156CHOWAN
Solar/Wind Helper
0.334
3130156CHOWAN
Solar/Wind Helper
0.334
3130156CHOWAN
Solar/Wind Helper
0.334
3138266HYDRAULIC
Solar/Wind Helper
0.015
3138266HYDRAULIC
Solar/Wind Helper
0.009
316097T157 G90
Solar/Wind Helper
0.219
316095T157 G97
Solar/Wind Helper
0.219
315614AA2-178 GEN
Solar/Wind Helper
0.428
315816AE2-034 GEN
Solar/Wind Helper
0.321
3145663CRESWEL
Solar/Wind Helper
0.933
316322AB2-045
Solar/Wind Helper
0.106
3146776BUCKING
Solar/Wind Helper
1.331
3146776BUCKING
Solar/Wind Helper
0.133
3146776BUCKING
Solar/Wind Helper
0.12
3146776BUCKING
Solar/Wind Helper
0.108
3156081AA2-088 GEN
Solar/Wind Helper
0.534
3130546PLYMOUTH
Solar/Wind Helper
0.332
315732AD1-074 GEN1
Solar/Wind Helper
0.801
315733AD1-074 GEN2
Solar/Wind Helper
0.801
315737AD1-076 GEN
Solar/Wind Helper
0.582
315735AD1-075 GEN1
Solar/Wind Helper
0.4
3147983MERCK5
Solar/Wind Helper
0.133
3146926FARMVIL
Solar/Wind Helper
0.199
3146926FARMVIL
Solar/Wind Helper
0.199
316065AD1-022 GEN
Solar/Wind Helper
0.427
316023GEN1_S
Solar/Wind Helper
0.267
316365GEN2_N
Solar/Wind Helper
0.267
3146206CASHIE
Solar/Wind Helper
0.332
3146206CASHIE
Solar/Wind Helper
0.332
3146206CASHIE
Solar/Wind Helper
0.332
3145893MURPHYS
Solar/Wind Helper
1.328
3145893MURPHYS
Solar/Wind Helper
1.062
3145893MURPHYS
Solar/Wind Helper
0.896
316318V4-068
Solar/Wind Helper
0.025
3145893MURPHYS
Solar/Wind Helper
0.597
3145893MURPHYS
Solar/Wind Helper
0.332
3145893MURPHYS
Solar/Wind Helper
0.332
3145893MURPHYS
Solar/Wind Helper
0.266
315821AE2-092 GEN
Solar/Wind Helper
0.735
316499AE2-029_GEN
Solar/Wind Helper
0.266
3146173TUNIS
Solar/Wind Helper
0.331
3146173TUNIS
Solar/Wind Helper
0.331
3146173TUNIS
Solar/Wind Helper
0.331
3146173TUNIS
Solar/Wind Helper
0.331
942461AE2-259 GEN
Solar/Wind Helper
0.532
3156021HOLLOMANSOL
Solar/Wind Helper
0.532
316463AE2-346 GEN
Solar/Wind Helper
0.064
316140AB2-099
Solar/Wind Helper
0.027
961941AG1-037 GEN
Solar/Wind Helper
0.027
3145513AHOSKIE
Solar/Wind Helper
0.331
3145513AHOSKIE
Solar/Wind Helper
0.331
946281AF1-292 GEN
Solar/Wind Helper
0.079
966621AG1-532 GEN
Solar/Wind Helper
0.072
3146043SEABORD
Solar/Wind Helper
0.331
3145683EARLEYS
Solar/Wind Helper
0.662
3145683EARLEYS
Solar/Wind Helper
0.331
3145683EARLEYS
Solar/Wind Helper
0.331
3145683EARLEYS
Solar/Wind Helper
0.331
315607AA1-063A GEN
Solar/Wind Helper
0.399
316087AB2-174 GEN
Solar/Wind Helper
0.425
3146263WOODLND
Solar/Wind Helper
0.331
3146263WOODLND
Solar/Wind Helper
0.331
316181AB2-040 GEN
Solar/Wind Helper
0.425
313506AB2-031 GEN
Solar/Wind Helper
0.317
3147133PAMPLIN
Solar/Wind Helper
1.038
3147133PAMPLIN
Solar/Wind Helper
0.331
3147133PAMPLIN
Solar/Wind Helper
0.265
237080AD1-060 GEN
Solar/Wind Helper
0.08
3148013FISHERV
Solar/Wind Helper
0.331
3148133STUARTS
Solar/Wind Helper
0.198
3148013FISHERV
Solar/Wind Helper
0.19
3137643SOCKMAN
Solar/Wind Helper
1.321
3147043LAWRENC
Solar/Wind Helper
0.198
3142666NORTHAMPTON
Solar/Wind Helper
0.33
3142666NORTHAMPTON
Solar/Wind Helper
0.33
3142666NORTHAMPTON
Solar/Wind Helper
0.33
3142666NORTHAMPTON
Solar/Wind Helper
0.33
3142666NORTHAMPTON
Solar/Wind Helper
0.198
316426AA2-053 GEN
Solar/Wind Helper
0.398
316190AA2-174 GEN
Solar/Wind Helper
0.027
3145963POPLR C
Solar/Wind Helper
0.33
3145963POPLR C
Solar/Wind Helper
0.33
316011AB1-132 GEN
Solar/Wind Helper
7.929
316317KELFORD C
Solar/Wind Helper
0.123
3145823KELFORD
Solar/Wind Helper
0.33
3145823KELFORD
Solar/Wind Helper
0.33
3145593CAROLNA
Solar/Wind Helper
0.33
3145593CAROLNA
Solar/Wind Helper
0.33
316174AB2-169 GEN
Solar/Wind Helper
0.392
316478AD1-087 GEN
Solar/Wind Helper
0.34
316486AD2-202 GEN
Solar/Wind Helper
0.1
3145783HORNRTN
Solar/Wind Helper
0.33
23583801GRNGAP
Solar/Wind Helper
0.551
3145796HORNRTN
Solar/Wind Helper
1.319
3145796HORNRTN
Solar/Wind Helper
1.088
3145796HORNRTN
Solar/Wind Helper
1.055
3145796HORNRTN
Solar/Wind Helper
0.989
3145796HORNRTN
Solar/Wind Helper
0.33
3145796HORNRTN
Solar/Wind Helper
0.33
3145796HORNRTN
Solar/Wind Helper
0.132
316034AC1-036 C
Solar/Wind Helper
0.073
3144303KENBRDG
Solar/Wind Helper
0.264
3146033SCOT NK
Solar/Wind Helper
1.318
315785AD2-033 C
Solar/Wind Helper
0.688
316129AC1-054 GEN
Solar/Wind Helper
0.344
316210AC1-098 GEN
Solar/Wind Helper
0.476
316212AC1-099_GEN
Solar/Wind Helper
0.264
316131AB2-060 GEN
Solar/Wind Helper
0.423
238108AE1-109 GEN1
Solar/Wind Helper
0.035
238109AE1-109 GEN2
Solar/Wind Helper
0.035
238110AE1-109 GEN3
Solar/Wind Helper
0.035
313527AB2-043 GEN
Solar/Wind Helper
0.264
3145933PARMELE
Solar/Wind Helper
0.658
3145933PARMELE
Solar/Wind Helper
0.329
3145933PARMELE
Solar/Wind Helper
0.329
316274AC1-208 GEN
Solar/Wind Helper
0.423
316239AB2-077_GEN
Solar/Wind Helper
0.106
316238AB2-078_GEN
Solar/Wind Helper
0.106
316237AB2-079_GEN
Solar/Wind Helper
0.106
315687AD1-152 GEN
Solar/Wind Helper
0.422
316005AA1-067
Solar/Wind Helper
0.079
3145746EVERETS
Solar/Wind Helper
1.306
3145746EVERETS
Solar/Wind Helper
0.328
3145746EVERETS
Solar/Wind Helper
0.328
3145746EVERETS
Solar/Wind Helper
0.328
3145746EVERETS
Solar/Wind Helper
0.328
3145746EVERETS
Solar/Wind Helper
0.328
3145746EVERETS
Solar/Wind Helper
0.328
3145746EVERETS
Solar/Wind Helper
0.328
315722AD1-056 GEN
Solar/Wind Helper
0.316
315724AD1-057 GEN
Solar/Wind Helper
0.174
316327AA2-057 GEN
Solar/Wind Helper
0.395
270494AE1-108_GEN
Solar/Wind Helper
0.787
316494AC1-189 GEN
Solar/Wind Helper
0.421
316420AA1-050 GEN
Solar/Wind Helper
0.421
316319Z2-044 C
Solar/Wind Helper
0.063
3146233WITAKRS
Solar/Wind Helper
1.302
3146233WITAKRS
Solar/Wind Helper
0.222
961671AG1-007 GEN
Solar/Wind Helper
0.049
3145573BETHELC
Solar/Wind Helper
0.327
3145573BETHELC
Solar/Wind Helper
0.327
3146073TAR RVR
Solar/Wind Helper
0.327
3146083TARBORO
Solar/Wind Helper
0.327
3146083TARBORO
Solar/Wind Helper
0.327
3138543CONSLDL
Solar/Wind Helper
0.216
3146843MT LREL
Solar/Wind Helper
0.327
3146843MT LREL
Solar/Wind Helper
0.327
237038AE2-054 C
Solar/Wind Helper
0.105
3145543BTLEBRO
Solar/Wind Helper
0.326
3145543BTLEBRO
Solar/Wind Helper
0.326
3145543BTLEBRO
Solar/Wind Helper
0.326
3145543BTLEBRO
Solar/Wind Helper
0.261
316359AB2-059 GEN
Solar/Wind Helper
0.524
316049AB1-081 GEN
Solar/Wind Helper
0.419
235067AD1-061 GEN
Solar/Wind Helper
0.105
3148463FAIRFLD
Solar/Wind Helper
0.326
316118AC1-105 GEN
Solar/Wind Helper
0.267
316248AF1-058 C
Solar/Wind Helper
0.105
3147173SINAI
Solar/Wind Helper
0.325
3147243WELCO
Solar/Wind Helper
0.203
316003AC1-222 GEN
Solar/Wind Helper
0.338
237085AD2-009_GEN
Solar/Wind Helper
0.365
237002AB1-128_GEN
Solar/Wind Helper
0.104
237001AB1-127_GEN
Solar/Wind Helper
0.104
316222AC1-221 GEN
Solar/Wind Helper
0.388
964991AG1-363 GEN
Solar/Wind Helper
1.549
316283AC2-100 C
Solar/Wind Helper
0.362
235062AE1-101 C1
Solar/Wind Helper
0.387
235063AE1-101 C2
Solar/Wind Helper
0.387
316123AC1-075 GEN
Solar/Wind Helper
0.412
23779801AA1-109
Solar/Wind Helper
0.046
270455AD2-022 GEN
Solar/Wind Helper
0.491
270457AD2-023 GEN
Solar/Wind Helper
0.276
226929AD2-058 GEN
Solar/Wind Helper
0.028
3147123OTTER R
Solar/Wind Helper
0.19
23777801MSM_W1-116
Solar/Wind Helper
0.071
316217AC1-145 GEN
Solar/Wind Helper
0.253
316197AC1-042 GEN
Solar/Wind Helper
0.213
3147312GRETNA
Solar/Wind Helper
0.252
3146802CHATHAM
Solar/Wind Helper
0.236
3147312GRETNA
Solar/Wind Helper
0.063
270016AE1-250 BESS
Solar/Wind Helper
0.379
270013AE1-250 PV
Solar/Wind Helper
0.379
270197AD1-017 GEN1
Solar/Wind Helper
0.303
270574AD1-017 GEN2
Solar/Wind Helper
0.303
270173AC1-122 GEN
Solar/Wind Helper
0.382
23750701CROSSCHOOL
Solar/Wind Helper
0.136
270018AE2-047 C O1
Solar/Wind Helper
0.251
G-007ALTFEXP_G-007A->PJM
CMTX
53.176
HAMLETPJM->LTFIMP_HAMLET
CLTF
5.859
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.503
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
24.367
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
5.217
BlueGrassPJM->LTFIMP_BlueG
CLTF
16.247
CBM NorthLTFEXP_CBM-N->PJM
CBM
59.298
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
130.559

Details for PCHBTM1N-CHAN 500.0 kV Ckt 1 line l/o PECO_P4_PEACH235_SRT-A/* $ CHESCO $ PECO_P4_PEACH235 $ STBK


Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1N-CHAN 500.0 kV Ckt 1 line
Contingency Name:
PECO_P4_PEACH235_SRT-A/* $ CHESCO $ PECO_P4_PEACH235 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:151.94 %
Rating:3926.0 MVA
Rating Type:B
MVA to Mitigate:5965.21
MW Contribution:0.62
Bus #Bus NameTypeMW Contribution
200035PCHBTM 3
50/50
41.46
200202DELTA2 ST
50/50
12.615
200200DELTA2 CT1
50/50
7.062
200201DELTA2 CT2
50/50
7.062
200195DELTA ST
50/50
6.241
200192DELTA CT1
50/50
3.744
200193DELTA CT2
50/50
3.744
200194DELTA CT3
50/50
3.744
200034PCHBTM 2
50/50
246.815
200203Y1-065-STG
50/50
13.832
200204Y1-065-CTG1
50/50
8.71
200205Y1-065-CTG2
50/50
8.71
200052ROCKSP 1
50/50
103.342
200053ROCKSP 2
50/50
103.342
200054ROCKSP 3
50/50
102.293
200055ROCKSP 4
50/50
102.293
233987AB2-037 GEN
Solar/Wind Harmer
0
233923SMA
Solar/Wind Harmer
-0.002
233998TM1NIN_3.36
Solar/Wind Harmer
-0.002
233997TMININ_4.2
Solar/Wind Harmer
-0.002
233996TM1833_GEN
Solar/Wind Harmer
-0.002
233940AF2-379 C
Solar/Wind Harmer
-0.002
972069AH1-584 GEN
Solar/Wind Harmer
0.965
972071AH1-585 GEN
Solar/Wind Harmer
0.965
972073AH1-586 GEN
Solar/Wind Harmer
17.376
971747AH1-380 GEN
Solar/Wind Harmer
0.386
234033AF1-007_GEN
Solar/Wind Harmer
40.38
233990AG1-397 GEN
Solar/Wind Harmer
-0.001
970545AG2-347 GEN
Solar/Wind Harmer
166.338
972133AH1-634 GEN
Solar/Wind Harmer
25.203
233990AG1-397 GEN
Solar/Wind Harmer
3.089
234015AF2-250 C
Solar/Wind Harmer
-0.001
971195AH1-057 GEN
Solar/Wind Harmer
0.139
960671AF2-358 GEN
Solar/Wind Harmer
1.93
965821AG1-450 GEN
Solar/Wind Harmer
9.648
971149AH1-027 GEN
Solar/Wind Harmer
0.482
232426Y1-080 FULL
Solar/Wind Harmer
0
970277AG2-181 GEN
Solar/Wind Harmer
0.54
233946AB2-136 GEN
Solar/Wind Harmer
-0.002
233964AF2-378 GEN
Solar/Wind Harmer
0.001
972177AH1-672 GEN
Solar/Wind Harmer
1.447
234041AC1-190 GEN
Solar/Wind Harmer
0.964
233972AC1-094 C
Solar/Wind Harmer
-0.002
970695AG2-447 GEN
Solar/Wind Harmer
0.385
233984AB2-036 GEN
Solar/Wind Harmer
1.762
233968AD2-076_GEN
Solar/Wind Harmer
0.934
234014AF1-036_GEN
Solar/Wind Harmer
0.381
970597AG2-380 GEN
Solar/Wind Harmer
7.626
234012AE2-112_GEN
Solar/Wind Harmer
0.324
971983AH1-536 GEN
Solar/Wind Harmer
0.793
970453AG2-297 GEN
Solar/Wind Harmer
0.302
971553AH1-274 GEN
Solar/Wind Harmer
0.263
945431AF1-208 GEN
Solar/Wind Harmer
0.704
970997AG2-616 GEN
Solar/Wind Harmer
0.78
972141AH1-641 GEN
Solar/Wind Harmer
0.234
230430AE1-229_GEN
Solar/Wind Harmer
-0.001
228351V2-046C
Solar/Wind Harmer
-0.002
230433AD2-135 GEN
Solar/Wind Harmer
0
230422AE1-104_GEN1
Solar/Wind Harmer
64.27
230425AE1-104_GEN2
Solar/Wind Harmer
64.27
971011AG2-627 GEN
Solar/Wind Harmer
0.619
971535AH1-265 GEN
Solar/Wind Harmer
0.453
230407AD2-065 C
Solar/Wind Harmer
0
228754AB1-001 C
Solar/Wind Harmer
-0.002
219137THOSOLAR C
Solar/Wind Harmer
0.001
219623KINSLEYBEA C
Solar/Wind Harmer
-0.001
219258KINSLEYDEP C
Solar/Wind Harmer
-0.001
219766PARADISE C
Solar/Wind Harmer
-0.001
218660EHAMPSOLAR C
Solar/Wind Harmer
-0.001
219907AC1-030 C
Solar/Wind Harmer
-0.001
219236SOUTHERNHQ C
Solar/Wind Harmer
-0.001
219906AC1-017 C
Solar/Wind Harmer
-0.001
219615MILLCREEK C
Solar/Wind Harmer
-0.001
214067T20SOLAR
Solar/Wind Harmer
-0.001
207522AF2-254 C
Solar/Wind Harmer
0.132
207500AE2-000G1
Solar/Wind Harmer
51.347
207497AE2-000G2
Solar/Wind Harmer
51.347
207507AE2-000G3
Solar/Wind Harmer
51.347
207487AE2-000G4
Solar/Wind Harmer
51.347
970025AG2-016 GEN
Solar/Wind Harmer
0.257
971189AH1-054 GEN
Solar/Wind Harmer
0.107
971667AH1-334 GEN
Solar/Wind Harmer
0.246
219727YARDVSOLFA C
Solar/Wind Harmer
0.001
219276PARKLANDSO C
Solar/Wind Harmer
0
219620RIDERU C
Solar/Wind Harmer
-0.001
219817TRENTONSOL C
Solar/Wind Harmer
0.001
20714328BYD_X4-031
Solar/Wind Harmer
0.024
20714428HOW_X1-037
Solar/Wind Harmer
-0.001
219918AC2-009 C
Solar/Wind Harmer
0
20720628TIN_W1-124
Solar/Wind Harmer
-0.001
20742028HF_AC1-207
Solar/Wind Harmer
-0.001
971521AH1-258 GEN
Solar/Wind Harmer
0.227
967451AG2-055 C O1
Solar/Wind Harmer
256.35
219612MATRIX C
Solar/Wind Harmer
0.001
218438BLK ROCK C
Solar/Wind Harmer
-0.001
218526CNTRALGAS2 C
Solar/Wind Harmer
0.001
218524CNTRALGAS1 C
Solar/Wind Harmer
0.001
218428ETC SOLAR C
Solar/Wind Harmer
0
217213AMBOY SO C
Solar/Wind Harmer
-0.001
219249CENTRALDIV C
Solar/Wind Harmer
-0.001
20673828FLE_V3-070
Solar/Wind Harmer
0.076
218449LINSOLAR C
Solar/Wind Harmer
0.001
20675428EAM_W2-061
Solar/Wind Harmer
0
217081WEATEXAS C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
217206BARNGR HS C
Solar/Wind Harmer
-0.001
217208PARK ELE C
Solar/Wind Harmer
0
207439AE1-081 C O1
Solar/Wind Harmer
0
20676328BVR_Y1-020
Solar/Wind Harmer
0
20674628WNG_W3-110
Solar/Wind Harmer
-0.001
207511W3-106 GEN
Solar/Wind Harmer
0.043
971009AG2-626 GEN
Solar/Wind Harmer
0.1
971007AG2-625 GEN
Solar/Wind Harmer
0.157
971519AH1-257 GEN
Solar/Wind Harmer
0.154
207437AD2-070 GEN
Solar/Wind Harmer
-0.001
966181AG1-487 GEN
Solar/Wind Harmer
0
966181AG1-487 GEN
Solar/Wind Harmer
2.877
966111AG1-480 GEN
Solar/Wind Harmer
0
966111AG1-480 GEN
Solar/Wind Harmer
2.552
209029WAYMART-WD
Solar/Wind Harmer
4.194
970095AG2-074 GEN
Solar/Wind Harmer
0.206
208972BECR K09
Solar/Wind Harmer
1.468
3138216PACIFIC
Solar/Wind Helper
0.061
316411AF1-147_GEN1
Solar/Wind Helper
0.292
316415AF1-147_GEN2
Solar/Wind Helper
0.292
3141196NOKESVL
Solar/Wind Helper
1.431
238175AF1-290_GEN
Solar/Wind Helper
0.455
316006AB2-029 C
Solar/Wind Helper
0.112
238169AE2-226 GEN1
Solar/Wind Helper
0.28
238170AE2-226 GEN2
Solar/Wind Helper
0.28
964441AG1-307 GEN
Solar/Wind Helper
0.45
315651AD1-115 GEN
Solar/Wind Helper
0.844
316045AC1-158 PL2
Solar/Wind Helper
1.309
316447AC1-158 HLD
Solar/Wind Helper
0.899
316044AC1-158 PL1
Solar/Wind Helper
0.409
316450AC1-158 RIC
Solar/Wind Helper
0.109
316254AC1-120 GEN1
Solar/Wind Helper
0.337
316170AC1-121 GEN2
Solar/Wind Helper
0.112
3141426STAFORD
Solar/Wind Helper
0.077
316164AC1-076 GEN
Solar/Wind Helper
0.351
3132273ORANGE
Solar/Wind Helper
0.069
3147666LOUISA
Solar/Wind Helper
1.381
3147666LOUISA
Solar/Wind Helper
0.794
316192AB2-158 GEN
Solar/Wind Helper
0.489
966001AG1-469 GEN
Solar/Wind Helper
0.078
238152AF2-075_GEN
Solar/Wind Helper
0.276
238147AE2-230_GEN1
Solar/Wind Helper
0.387
238148AE2-230_GEN2
Solar/Wind Helper
0.387
238149AF1-291A_GEN
Solar/Wind Helper
0.055
966881AG1-559 GEN
Solar/Wind Helper
0.111
23546401DTGZ2-030
Solar/Wind Helper
0.055
944491AF1-114 GEN
Solar/Wind Helper
0.552
957971AF2-091 GEN
Solar/Wind Helper
0.188
235020AA1-095 C
Solar/Wind Helper
0.023
23777901MDS_W4-102
Solar/Wind Helper
0.11
316468AD1-105 GEN
Solar/Wind Helper
0.407
237061AD1-155 GEN
Solar/Wind Helper
0.412
316223AC1-118
Solar/Wind Helper
0.11
3141906WESTMOR
Solar/Wind Helper
0.137
316337AD2-073 GEN
Solar/Wind Helper
0.11
316077AC2-138 C
Solar/Wind Helper
0.077
3141813NORNECK
Solar/Wind Helper
0.341
316473AC1-191 GEN
Solar/Wind Helper
0.438
964211AG1-282 GEN
Solar/Wind Helper
0.109
966871AG1-558 GEN
Solar/Wind Helper
0.109
3141726DUNNSVL
Solar/Wind Helper
1.363
316404AE1-155 C
Solar/Wind Helper
0.694
316484AD2-074 GEN
Solar/Wind Helper
0.47
316487AF1-042 GEN
Solar/Wind Helper
0.246
961951AG1-038 GEN
Solar/Wind Helper
0.246
316312AB1-027
Solar/Wind Helper
0.137
3142416OLDCHRC
Solar/Wind Helper
0.884
3142416OLDCHRC
Solar/Wind Helper
0.339
3141783LANCAST
Solar/Wind Helper
0.204
3141783LANCAST
Solar/Wind Helper
0.136
3138133OCRAN
Solar/Wind Helper
0.204
3138133OCRAN
Solar/Wind Helper
0.102
3141913WHIT STONE
Solar/Wind Helper
0.34
316075AC2-137 C
Solar/Wind Helper
0.109
316314AB2-024 C
Solar/Wind Helper
0.109
316059AD1-063 C
Solar/Wind Helper
0.082
3141766HARMONY
Solar/Wind Helper
0.068
316233AE1-074 FULL
Solar/Wind Helper
0.109
3143526WINTERP
Solar/Wind Helper
1.765
3143526WINTERP
Solar/Wind Helper
1.765
316203AE2-005 GEN
Solar/Wind Helper
0.709
315662AE1-191 GEN
Solar/Wind Helper
0.436
316280AD1-041 GEN
Solar/Wind Helper
0.273
315666AE1-190 GEN
Solar/Wind Helper
0.109
316441AF1-014 GEN
Solar/Wind Helper
0.109
957601AF2-054 GEN
Solar/Wind Helper
0.108
316156AD2-030 GEN
Solar/Wind Helper
0.108
3143873LANEXA
Solar/Wind Helper
0.204
3141873WAN 176
Solar/Wind Helper
0.068
3143226MDLTHAN
Solar/Wind Helper
0.339
3142433PROV 92
Solar/Wind Helper
1.357
3142543TWELFTH
Solar/Wind Helper
0.033
3142946ENON
Solar/Wind Helper
0.113
3142946ENON
Solar/Wind Helper
0.034
957831AF2-077 GEN
Solar/Wind Helper
0.109
316382AG1-145 C
Solar/Wind Helper
0.109
316159AE1-175 C
Solar/Wind Helper
0.109
316240AF1-291 C
Solar/Wind Helper
0.109
316132AB2-190 GEN1
Solar/Wind Helper
0.407
316458AB2-190 GEN2
Solar/Wind Helper
0.407
315697AD1-025 GEN
Solar/Wind Helper
0.814
316033AB2-134 GEN
Solar/Wind Helper
0.773
316369SG1_INVT
Solar/Wind Helper
0.532
315839AE2-212 C
Solar/Wind Helper
0.108
961611AG1-000B GEN
Solar/Wind Helper
0.483
316313AB2-026
Solar/Wind Helper
0.108
316236AE1-162_GEN
Solar/Wind Helper
0.108
316258AE1-075 C
Solar/Wind Helper
0.097
316405AF2-144 C
Solar/Wind Helper
0.092
3145336SMITFLD
Solar/Wind Helper
1.348
3145336SMITFLD
Solar/Wind Helper
0.135
3143316POE
Solar/Wind Helper
1.334
316294AC1-161 GEN
Solar/Wind Helper
1.299
315773AC2-141 GEN
Solar/Wind Helper
1.299
316381AD1-082 GEN
Solar/Wind Helper
0.368
316083AB2-161 GEN
Solar/Wind Helper
0.27
3144536CHRHLND
Solar/Wind Helper
0.051
316375AC2-012 GEN
Solar/Wind Helper
0.638
316036AC1-147 C
Solar/Wind Helper
0.108
3144873MCLAUGH
Solar/Wind Helper
0.008
316316AC1-027 C
Solar/Wind Helper
0.095
316336AC2-165 C
Solar/Wind Helper
0.54
316185AD1-033 GEN
Solar/Wind Helper
0.378
316072AD1-144
Solar/Wind Helper
0.081
3145506HICKORY
Solar/Wind Helper
1.345
3145506HICKORY
Solar/Wind Helper
0.807
3145506HICKORY
Solar/Wind Helper
0.202
316349AD2-085 GEN
Solar/Wind Helper
0.275
316339AD2-160 GEN
Solar/Wind Helper
0.27
316388AE2-253 GEN
Solar/Wind Helper
0.27
315833AF1-017_GEN
Solar/Wind Helper
0.216
316017AA1-139 ULT1
Solar/Wind Helper
0.324
316018AA1-139 ULT2
Solar/Wind Helper
0.324
3137176SLIGO L2192
Solar/Wind Helper
1.337
3146456SLIGO L269
Solar/Wind Helper
0.336
3146456SLIGO L269
Solar/Wind Helper
0.336
319010AE1-072 C
Solar/Wind Helper
0.81
316305AF2-043 C
Solar/Wind Helper
0.108
316246AF1-032 C
Solar/Wind Helper
0.081
3130086AYDLETT
Solar/Wind Helper
1.344
316320Y1-086
Solar/Wind Helper
0.108
313526AB2-022
Solar/Wind Helper
0.108
3146386ELIZ CT
Solar/Wind Helper
0.336
3146486SUNBURY
Solar/Wind Helper
0.335
3146486SUNBURY
Solar/Wind Helper
0.335
316321Z2-027
Solar/Wind Helper
0.108
3145176PASQUOTANK
Solar/Wind Helper
0.208
3146516WINFALL
Solar/Wind Helper
1.085
3146516WINFALL
Solar/Wind Helper
0.335
3146516WINFALL
Solar/Wind Helper
0.335
3146516WINFALL
Solar/Wind Helper
0.335
3146516WINFALL
Solar/Wind Helper
0.335
3146516WINFALL
Solar/Wind Helper
0.335
237034AC2-136 C
Solar/Wind Helper
0.063
316315AB2-025 C
Solar/Wind Helper
0.108
238221AF1-254 C O1
Solar/Wind Helper
0.108
3146626S HERTFORD
Solar/Wind Helper
0.335
3146626S HERTFORD
Solar/Wind Helper
0.335
3146626S HERTFORD
Solar/Wind Helper
0.335
3145273HOLLAND
Solar/Wind Helper
0.251
3132123MT JACKSON
Solar/Wind Helper
1.046
315742AE1-103 GEN
Solar/Wind Helper
0.215
238208AF1-136 C
Solar/Wind Helper
0.085
3130156CHOWAN
Solar/Wind Helper
0.334
3130156CHOWAN
Solar/Wind Helper
0.334
3130156CHOWAN
Solar/Wind Helper
0.334
3146376EDENTON
Solar/Wind Helper
0.334
3138266HYDRAULIC
Solar/Wind Helper
0.015
3138266HYDRAULIC
Solar/Wind Helper
0.009
316097T157 G90
Solar/Wind Helper
0.219
316095T157 G97
Solar/Wind Helper
0.219
315614AA2-178 GEN
Solar/Wind Helper
0.428
315816AE2-034 GEN
Solar/Wind Helper
0.321
3145663CRESWEL
Solar/Wind Helper
0.932
316322AB2-045
Solar/Wind Helper
0.106
3146776BUCKING
Solar/Wind Helper
1.331
3146776BUCKING
Solar/Wind Helper
0.133
3146776BUCKING
Solar/Wind Helper
0.12
3146776BUCKING
Solar/Wind Helper
0.108
3156081AA2-088 GEN
Solar/Wind Helper
0.534
3130546PLYMOUTH
Solar/Wind Helper
0.332
3147983MERCK5
Solar/Wind Helper
0.133
315732AD1-074 GEN1
Solar/Wind Helper
0.8
315733AD1-074 GEN2
Solar/Wind Helper
0.8
315737AD1-076 GEN
Solar/Wind Helper
0.582
315735AD1-075 GEN1
Solar/Wind Helper
0.4
3146926FARMVIL
Solar/Wind Helper
0.199
3146926FARMVIL
Solar/Wind Helper
0.199
316065AD1-022 GEN
Solar/Wind Helper
0.427
316023GEN1_S
Solar/Wind Helper
0.267
316365GEN2_N
Solar/Wind Helper
0.267
3146206CASHIE
Solar/Wind Helper
0.332
3146206CASHIE
Solar/Wind Helper
0.332
3146206CASHIE
Solar/Wind Helper
0.332
3145893MURPHYS
Solar/Wind Helper
1.327
3145893MURPHYS
Solar/Wind Helper
1.062
3145893MURPHYS
Solar/Wind Helper
0.896
316318V4-068
Solar/Wind Helper
0.025
3145893MURPHYS
Solar/Wind Helper
0.597
3145893MURPHYS
Solar/Wind Helper
0.332
3145893MURPHYS
Solar/Wind Helper
0.332
3145893MURPHYS
Solar/Wind Helper
0.265
315821AE2-092 GEN
Solar/Wind Helper
0.735
316499AE2-029_GEN
Solar/Wind Helper
0.266
3146173TUNIS
Solar/Wind Helper
0.331
3146173TUNIS
Solar/Wind Helper
0.331
3146173TUNIS
Solar/Wind Helper
0.331
3146173TUNIS
Solar/Wind Helper
0.331
942461AE2-259 GEN
Solar/Wind Helper
0.532
3156021HOLLOMANSOL
Solar/Wind Helper
0.532
316463AE2-346 GEN
Solar/Wind Helper
0.064
316140AB2-099
Solar/Wind Helper
0.027
961941AG1-037 GEN
Solar/Wind Helper
0.027
3145513AHOSKIE
Solar/Wind Helper
0.331
3145513AHOSKIE
Solar/Wind Helper
0.331
946281AF1-292 GEN
Solar/Wind Helper
0.079
966621AG1-532 GEN
Solar/Wind Helper
0.072
3146043SEABORD
Solar/Wind Helper
0.331
3145683EARLEYS
Solar/Wind Helper
0.662
3145683EARLEYS
Solar/Wind Helper
0.331
3145683EARLEYS
Solar/Wind Helper
0.331
3145683EARLEYS
Solar/Wind Helper
0.331
315607AA1-063A GEN
Solar/Wind Helper
0.399
316087AB2-174 GEN
Solar/Wind Helper
0.425
3146263WOODLND
Solar/Wind Helper
0.331
3146263WOODLND
Solar/Wind Helper
0.331
316181AB2-040 GEN
Solar/Wind Helper
0.425
313506AB2-031 GEN
Solar/Wind Helper
0.317
3147133PAMPLIN
Solar/Wind Helper
1.038
3147133PAMPLIN
Solar/Wind Helper
0.331
3147133PAMPLIN
Solar/Wind Helper
0.264
237080AD1-060 GEN
Solar/Wind Helper
0.08
3148013FISHERV
Solar/Wind Helper
0.33
3148133STUARTS
Solar/Wind Helper
0.198
3148013FISHERV
Solar/Wind Helper
0.19
3137643SOCKMAN
Solar/Wind Helper
1.32
3147043LAWRENC
Solar/Wind Helper
0.198
3142666NORTHAMPTON
Solar/Wind Helper
0.33
3142666NORTHAMPTON
Solar/Wind Helper
0.33
3142666NORTHAMPTON
Solar/Wind Helper
0.33
3142666NORTHAMPTON
Solar/Wind Helper
0.33
3142666NORTHAMPTON
Solar/Wind Helper
0.198
316426AA2-053 GEN
Solar/Wind Helper
0.398
316190AA2-174 GEN
Solar/Wind Helper
0.027
3145963POPLR C
Solar/Wind Helper
0.33
3145963POPLR C
Solar/Wind Helper
0.33
316011AB1-132 GEN
Solar/Wind Helper
7.926
316317KELFORD C
Solar/Wind Helper
0.123
3145823KELFORD
Solar/Wind Helper
0.33
3145823KELFORD
Solar/Wind Helper
0.33
3145593CAROLNA
Solar/Wind Helper
0.33
3145593CAROLNA
Solar/Wind Helper
0.33
316174AB2-169 GEN
Solar/Wind Helper
0.392
316478AD1-087 GEN
Solar/Wind Helper
0.34
316486AD2-202 GEN
Solar/Wind Helper
0.1
3145783HORNRTN
Solar/Wind Helper
0.33
23583801GRNGAP
Solar/Wind Helper
0.551
3145796HORNRTN
Solar/Wind Helper
1.319
3145796HORNRTN
Solar/Wind Helper
1.088
3145796HORNRTN
Solar/Wind Helper
1.055
3145796HORNRTN
Solar/Wind Helper
0.989
3145796HORNRTN
Solar/Wind Helper
0.33
3145796HORNRTN
Solar/Wind Helper
0.33
3145796HORNRTN
Solar/Wind Helper
0.132
316034AC1-036 C
Solar/Wind Helper
0.073
3144303KENBRDG
Solar/Wind Helper
0.264
3146033SCOT NK
Solar/Wind Helper
1.318
315785AD2-033 C
Solar/Wind Helper
0.688
316129AC1-054 GEN
Solar/Wind Helper
0.343
316210AC1-098 GEN
Solar/Wind Helper
0.476
316212AC1-099_GEN
Solar/Wind Helper
0.264
316131AB2-060 GEN
Solar/Wind Helper
0.423
238108AE1-109 GEN1
Solar/Wind Helper
0.035
238109AE1-109 GEN2
Solar/Wind Helper
0.035
238110AE1-109 GEN3
Solar/Wind Helper
0.035
313527AB2-043 GEN
Solar/Wind Helper
0.264
3145933PARMELE
Solar/Wind Helper
0.657
3145933PARMELE
Solar/Wind Helper
0.329
3145933PARMELE
Solar/Wind Helper
0.329
316274AC1-208 GEN
Solar/Wind Helper
0.422
316239AB2-077_GEN
Solar/Wind Helper
0.106
316238AB2-078_GEN
Solar/Wind Helper
0.106
316237AB2-079_GEN
Solar/Wind Helper
0.106
315687AD1-152 GEN
Solar/Wind Helper
0.421
316005AA1-067
Solar/Wind Helper
0.079
3145746EVERETS
Solar/Wind Helper
1.305
3145746EVERETS
Solar/Wind Helper
0.328
3145746EVERETS
Solar/Wind Helper
0.328
3145746EVERETS
Solar/Wind Helper
0.328
3145746EVERETS
Solar/Wind Helper
0.328
3145746EVERETS
Solar/Wind Helper
0.328
3145746EVERETS
Solar/Wind Helper
0.328
3145746EVERETS
Solar/Wind Helper
0.328
315722AD1-056 GEN
Solar/Wind Helper
0.316
315724AD1-057 GEN
Solar/Wind Helper
0.174
316327AA2-057 GEN
Solar/Wind Helper
0.395
270494AE1-108_GEN
Solar/Wind Helper
0.787
316494AC1-189 GEN
Solar/Wind Helper
0.421
316420AA1-050 GEN
Solar/Wind Helper
0.42
316319Z2-044 C
Solar/Wind Helper
0.063
3146233WITAKRS
Solar/Wind Helper
1.301
3146233WITAKRS
Solar/Wind Helper
0.222
961671AG1-007 GEN
Solar/Wind Helper
0.049
3145573BETHELC
Solar/Wind Helper
0.327
3145573BETHELC
Solar/Wind Helper
0.327
3146073TAR RVR
Solar/Wind Helper
0.327
3146083TARBORO
Solar/Wind Helper
0.327
3146083TARBORO
Solar/Wind Helper
0.327
3138543CONSLDL
Solar/Wind Helper
0.216
3146843MT LREL
Solar/Wind Helper
0.327
3146843MT LREL
Solar/Wind Helper
0.327
237038AE2-054 C
Solar/Wind Helper
0.105
3145543BTLEBRO
Solar/Wind Helper
0.326
3145543BTLEBRO
Solar/Wind Helper
0.326
3145543BTLEBRO
Solar/Wind Helper
0.326
3145543BTLEBRO
Solar/Wind Helper
0.261
316359AB2-059 GEN
Solar/Wind Helper
0.524
316049AB1-081 GEN
Solar/Wind Helper
0.419
235067AD1-061 GEN
Solar/Wind Helper
0.105
3148463FAIRFLD
Solar/Wind Helper
0.326
316118AC1-105 GEN
Solar/Wind Helper
0.267
316248AF1-058 C
Solar/Wind Helper
0.104
3147173SINAI
Solar/Wind Helper
0.325
3147243WELCO
Solar/Wind Helper
0.203
316003AC1-222 GEN
Solar/Wind Helper
0.338
237085AD2-009_GEN
Solar/Wind Helper
0.365
237002AB1-128_GEN
Solar/Wind Helper
0.104
237001AB1-127_GEN
Solar/Wind Helper
0.104
316222AC1-221 GEN
Solar/Wind Helper
0.388
964991AG1-363 GEN
Solar/Wind Helper
1.549
316283AC2-100 C
Solar/Wind Helper
0.361
235062AE1-101 C1
Solar/Wind Helper
0.386
235063AE1-101 C2
Solar/Wind Helper
0.386
316123AC1-075 GEN
Solar/Wind Helper
0.412
23779801AA1-109
Solar/Wind Helper
0.046
270455AD2-022 GEN
Solar/Wind Helper
0.491
270457AD2-023 GEN
Solar/Wind Helper
0.276
226929AD2-058 GEN
Solar/Wind Helper
0.028
3147123OTTER R
Solar/Wind Helper
0.189
23777801MSM_W1-116
Solar/Wind Helper
0.071
316217AC1-145 GEN
Solar/Wind Helper
0.253
316197AC1-042 GEN
Solar/Wind Helper
0.212
3147312GRETNA
Solar/Wind Helper
0.252
3146802CHATHAM
Solar/Wind Helper
0.236
3147312GRETNA
Solar/Wind Helper
0.063
270016AE1-250 BESS
Solar/Wind Helper
0.379
270013AE1-250 PV
Solar/Wind Helper
0.379
270197AD1-017 GEN1
Solar/Wind Helper
0.303
270574AD1-017 GEN2
Solar/Wind Helper
0.303
270173AC1-122 GEN
Solar/Wind Helper
0.382
23750701CROSSCHOOL
Solar/Wind Helper
0.135
270018AE2-047 C O1
Solar/Wind Helper
0.251
G-007ALTFEXP_G-007A->PJM
CMTX
53.154
HAMLETPJM->LTFIMP_HAMLET
CLTF
5.857
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.502
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
24.357
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
5.215
BlueGrassPJM->LTFIMP_BlueG
CLTF
16.24
CBM NorthLTFEXP_CBM-N->PJM
CBM
59.278
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
130.509

Details for PCHBTM1N-CHAN 500.0 kV Ckt 1 line l/o PJM_500_BG_P1_5011_SRT-A


Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1N-CHAN 500.0 kV Ckt 1 line
Contingency Name:
PJM_500_BG_P1_5011_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.62 %
Rating:3926.0 MVA
Rating Type:B
MVA to Mitigate:4264.26
MW Contribution:0.43
Bus #Bus NameTypeMW Contribution
200035PCHBTM 3
50/50
30.099
200202DELTA2 ST
50/50
9.02
200200DELTA2 CT1
50/50
5.049
200201DELTA2 CT2
50/50
5.049
200195DELTA ST
50/50
4.463
200192DELTA CT1
50/50
2.677
200193DELTA CT2
50/50
2.677
200194DELTA CT3
50/50
2.677
200034PCHBTM 2
50/50
176.721
200203Y1-065-STG
50/50
9.892
200204Y1-065-CTG1
50/50
6.229
200205Y1-065-CTG2
50/50
6.229
200052ROCKSP 1
50/50
73.903
200053ROCKSP 2
50/50
73.903
200054ROCKSP 3
50/50
73.153
200055ROCKSP 4
50/50
73.153
233987AB2-037 GEN
Solar/Wind Harmer
0
233923SMA
Solar/Wind Harmer
-0.001
233998TM1NIN_3.36
Solar/Wind Harmer
-0.001
233997TMININ_4.2
Solar/Wind Harmer
-0.001
233996TM1833_GEN
Solar/Wind Harmer
-0.001
233940AF2-379 C
Solar/Wind Harmer
-0.001
960671AF2-358 GEN
Solar/Wind Harmer
1.377
965821AG1-450 GEN
Solar/Wind Harmer
6.883
232426Y1-080 FULL
Solar/Wind Harmer
0
970277AG2-181 GEN
Solar/Wind Harmer
0.385
233946AB2-136 GEN
Solar/Wind Harmer
-0.001
233964AF2-378 GEN
Solar/Wind Harmer
0.001
972069AH1-584 GEN
Solar/Wind Harmer
0.688
972071AH1-585 GEN
Solar/Wind Harmer
0.688
972073AH1-586 GEN
Solar/Wind Harmer
12.386
971747AH1-380 GEN
Solar/Wind Harmer
0.275
234015AF2-250 C
Solar/Wind Harmer
-0.001
971195AH1-057 GEN
Solar/Wind Harmer
0.099
233990AG1-397 GEN
Solar/Wind Harmer
0
234041AC1-190 GEN
Solar/Wind Harmer
0.688
233990AG1-397 GEN
Solar/Wind Harmer
2.202
234033AF1-007_GEN
Solar/Wind Harmer
28.773
970545AG2-347 GEN
Solar/Wind Harmer
118.524
972133AH1-634 GEN
Solar/Wind Harmer
17.958
972177AH1-672 GEN
Solar/Wind Harmer
1.031
971149AH1-027 GEN
Solar/Wind Harmer
0.343
233984AB2-036 GEN
Solar/Wind Harmer
1.261
233972AC1-094 C
Solar/Wind Harmer
-0.001
970695AG2-447 GEN
Solar/Wind Harmer
0.274
233968AD2-076_GEN
Solar/Wind Harmer
0.669
234014AF1-036_GEN
Solar/Wind Harmer
0.273
970597AG2-380 GEN
Solar/Wind Harmer
5.464
234012AE2-112_GEN
Solar/Wind Harmer
0.232
971983AH1-536 GEN
Solar/Wind Harmer
0.569
970453AG2-297 GEN
Solar/Wind Harmer
0.21
971553AH1-274 GEN
Solar/Wind Harmer
0.183
945431AF1-208 GEN
Solar/Wind Harmer
0.49
970997AG2-616 GEN
Solar/Wind Harmer
0.543
972141AH1-641 GEN
Solar/Wind Harmer
0.163
230430AE1-229_GEN
Solar/Wind Harmer
-0.001
228351V2-046C
Solar/Wind Harmer
-0.001
230433AD2-135 GEN
Solar/Wind Harmer
0
971011AG2-627 GEN
Solar/Wind Harmer
0.431
230422AE1-104_GEN1
Solar/Wind Harmer
44.599
230425AE1-104_GEN2
Solar/Wind Harmer
44.599
971535AH1-265 GEN
Solar/Wind Harmer
0.314
230407AD2-065 C
Solar/Wind Harmer
0
228754AB1-001 C
Solar/Wind Harmer
-0.001
219137THOSOLAR C
Solar/Wind Harmer
0.001
219623KINSLEYBEA C
Solar/Wind Harmer
-0.001
219258KINSLEYDEP C
Solar/Wind Harmer
0
219766PARADISE C
Solar/Wind Harmer
-0.001
218660EHAMPSOLAR C
Solar/Wind Harmer
-0.001
219907AC1-030 C
Solar/Wind Harmer
-0.001
219236SOUTHERNHQ C
Solar/Wind Harmer
-0.001
219906AC1-017 C
Solar/Wind Harmer
-0.001
219615MILLCREEK C
Solar/Wind Harmer
-0.001
214067T20SOLAR
Solar/Wind Harmer
-0.001
207522AF2-254 C
Solar/Wind Harmer
0.09
207500AE2-000G1
Solar/Wind Harmer
34.743
207497AE2-000G2
Solar/Wind Harmer
34.743
207507AE2-000G3
Solar/Wind Harmer
34.743
207487AE2-000G4
Solar/Wind Harmer
34.743
970025AG2-016 GEN
Solar/Wind Harmer
0.174
971189AH1-054 GEN
Solar/Wind Harmer
0.072
971667AH1-334 GEN
Solar/Wind Harmer
0.166
219727YARDVSOLFA C
Solar/Wind Harmer
0.001
219276PARKLANDSO C
Solar/Wind Harmer
0
219620RIDERU C
Solar/Wind Harmer
-0.001
219817TRENTONSOL C
Solar/Wind Harmer
0.001
20714328BYD_X4-031
Solar/Wind Harmer
0.016
20714428HOW_X1-037
Solar/Wind Harmer
0
219918AC2-009 C
Solar/Wind Harmer
0
20720628TIN_W1-124
Solar/Wind Harmer
-0.001
20742028HF_AC1-207
Solar/Wind Harmer
-0.001
971521AH1-258 GEN
Solar/Wind Harmer
0.15
967451AG2-055 C O1
Solar/Wind Harmer
169.413
219612MATRIX C
Solar/Wind Harmer
0
218438BLK ROCK C
Solar/Wind Harmer
0
218526CNTRALGAS2 C
Solar/Wind Harmer
0.001
218524CNTRALGAS1 C
Solar/Wind Harmer
0
218428ETC SOLAR C
Solar/Wind Harmer
0
217213AMBOY SO C
Solar/Wind Harmer
-0.001
219249CENTRALDIV C
Solar/Wind Harmer
0
20673828FLE_V3-070
Solar/Wind Harmer
0.049
218449LINSOLAR C
Solar/Wind Harmer
0
20675428EAM_W2-061
Solar/Wind Harmer
0
217081WEATEXAS C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
217206BARNGR HS C
Solar/Wind Harmer
0
217208PARK ELE C
Solar/Wind Harmer
0
207439AE1-081 C O1
Solar/Wind Harmer
0
20676328BVR_Y1-020
Solar/Wind Harmer
0
20674628WNG_W3-110
Solar/Wind Harmer
-0.001
207511W3-106 GEN
Solar/Wind Harmer
0.027
G-007ALTFEXP_G-007A->PJM
CMTX
34.869
HAMLETPJM->LTFIMP_HAMLET
CLTF
4.488
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.666
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
17.984
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
3.837
BlueGrassPJM->LTFIMP_BlueG
CLTF
11.952
CBM NorthLTFEXP_CBM-N->PJM
CBM
37.857
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
84.043

Details for PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line l/o AP_P2-3_PE-500-019E_SRT-W


Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-500-019E_SRT-W
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:180.58 %
Rating:3700.0 MVA
Rating Type:B
MVA to Mitigate:6681.32
MW Contribution:0.64
Bus #Bus NameTypeMW Contribution
200202DELTA2 ST
50/50
10.233
200200DELTA2 CT1
50/50
5.728
200201DELTA2 CT2
50/50
5.728
200195DELTA ST
50/50
5.063
200192DELTA CT1
50/50
3.037
200193DELTA CT2
50/50
3.037
200194DELTA CT3
50/50
3.037
200034PCHBTM 2
50/50
200.576
200035PCHBTM 3
50/50
32.807
200203Y1-065-STG
50/50
11.438
200204Y1-065-CTG1
50/50
7.202
200205Y1-065-CTG2
50/50
7.202
200052ROCKSP 1
50/50
85.452
200053ROCKSP 2
50/50
85.452
200054ROCKSP 3
50/50
84.584
200055ROCKSP 4
50/50
84.584
971149AH1-027 GEN
Solar/Wind Harmer
0.443
233972AC1-094 C
Solar/Wind Harmer
-0.002
970695AG2-447 GEN
Solar/Wind Harmer
0.354
234033AF1-007_GEN
Solar/Wind Harmer
36.994
970545AG2-347 GEN
Solar/Wind Harmer
152.388
972133AH1-634 GEN
Solar/Wind Harmer
23.089
233987AB2-037 GEN
Solar/Wind Harmer
0
972177AH1-672 GEN
Solar/Wind Harmer
1.326
972069AH1-584 GEN
Solar/Wind Harmer
0.884
972071AH1-585 GEN
Solar/Wind Harmer
0.884
972073AH1-586 GEN
Solar/Wind Harmer
15.908
971747AH1-380 GEN
Solar/Wind Harmer
0.354
233923SMA
Solar/Wind Harmer
-0.002
233998TM1NIN_3.36
Solar/Wind Harmer
-0.002
233997TMININ_4.2
Solar/Wind Harmer
-0.002
233996TM1833_GEN
Solar/Wind Harmer
-0.002
233990AG1-397 GEN
Solar/Wind Harmer
-0.001
233990AG1-397 GEN
Solar/Wind Harmer
2.828
233940AF2-379 C
Solar/Wind Harmer
-0.002
234015AF2-250 C
Solar/Wind Harmer
-0.001
971195AH1-057 GEN
Solar/Wind Harmer
0.127
960671AF2-358 GEN
Solar/Wind Harmer
1.765
965821AG1-450 GEN
Solar/Wind Harmer
8.825
232426Y1-080 FULL
Solar/Wind Harmer
0
970277AG2-181 GEN
Solar/Wind Harmer
0.494
233946AB2-136 GEN
Solar/Wind Harmer
-0.002
233964AF2-378 GEN
Solar/Wind Harmer
0.001
234041AC1-190 GEN
Solar/Wind Harmer
0.882
233984AB2-036 GEN
Solar/Wind Harmer
1.609
233968AD2-076_GEN
Solar/Wind Harmer
0.853
234014AF1-036_GEN
Solar/Wind Harmer
0.348
970597AG2-380 GEN
Solar/Wind Harmer
6.96
234012AE2-112_GEN
Solar/Wind Harmer
0.296
971983AH1-536 GEN
Solar/Wind Harmer
0.724
970453AG2-297 GEN
Solar/Wind Harmer
0.307
971553AH1-274 GEN
Solar/Wind Harmer
0.268
945431AF1-208 GEN
Solar/Wind Harmer
0.719
970997AG2-616 GEN
Solar/Wind Harmer
0.797
972141AH1-641 GEN
Solar/Wind Harmer
0.239
230422AE1-104_GEN1
Solar/Wind Harmer
66.137
230425AE1-104_GEN2
Solar/Wind Harmer
66.137
230430AE1-229_GEN
Solar/Wind Harmer
-0.002
230433AD2-135 GEN
Solar/Wind Harmer
0
228351V2-046C
Solar/Wind Harmer
-0.002
971535AH1-265 GEN
Solar/Wind Harmer
0.467
971011AG2-627 GEN
Solar/Wind Harmer
0.635
228754AB1-001 C
Solar/Wind Harmer
-0.002
230407AD2-065 C
Solar/Wind Harmer
0
219137THOSOLAR C
Solar/Wind Harmer
0.001
219623KINSLEYBEA C
Solar/Wind Harmer
-0.001
219258KINSLEYDEP C
Solar/Wind Harmer
-0.001
218660EHAMPSOLAR C
Solar/Wind Harmer
-0.002
219766PARADISE C
Solar/Wind Harmer
-0.002
219907AC1-030 C
Solar/Wind Harmer
-0.002
219236SOUTHERNHQ C
Solar/Wind Harmer
-0.001
219906AC1-017 C
Solar/Wind Harmer
-0.002
219615MILLCREEK C
Solar/Wind Harmer
-0.002
214067T20SOLAR
Solar/Wind Harmer
-0.001
207522AF2-254 C
Solar/Wind Harmer
0.149
207500AE2-000G1
Solar/Wind Harmer
58.179
207497AE2-000G2
Solar/Wind Harmer
58.179
207507AE2-000G3
Solar/Wind Harmer
58.179
207487AE2-000G4
Solar/Wind Harmer
58.179
970025AG2-016 GEN
Solar/Wind Harmer
0.293
971189AH1-054 GEN
Solar/Wind Harmer
0.122
971667AH1-334 GEN
Solar/Wind Harmer
0.283
219727YARDVSOLFA C
Solar/Wind Harmer
0.001
219276PARKLANDSO C
Solar/Wind Harmer
0.001
219620RIDERU C
Solar/Wind Harmer
-0.001
219817TRENTONSOL C
Solar/Wind Harmer
0.001
20714328BYD_X4-031
Solar/Wind Harmer
0.029
20714428HOW_X1-037
Solar/Wind Harmer
-0.001
20720628TIN_W1-124
Solar/Wind Harmer
-0.001
219918AC2-009 C
Solar/Wind Harmer
0
20742028HF_AC1-207
Solar/Wind Harmer
-0.001
971521AH1-258 GEN
Solar/Wind Harmer
0.274
967451AG2-055 C O1
Solar/Wind Harmer
313.212
219612MATRIX C
Solar/Wind Harmer
0.001
218438BLK ROCK C
Solar/Wind Harmer
-0.001
218526CNTRALGAS2 C
Solar/Wind Harmer
0.001
218524CNTRALGAS1 C
Solar/Wind Harmer
0.001
218428ETC SOLAR C
Solar/Wind Harmer
0
217213AMBOY SO C
Solar/Wind Harmer
-0.001
219249CENTRALDIV C
Solar/Wind Harmer
-0.001
20673828FLE_V3-070
Solar/Wind Harmer
0.098
218449LINSOLAR C
Solar/Wind Harmer
0.001
20675428EAM_W2-061
Solar/Wind Harmer
-0.001
217081WEATEXAS C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
217206BARNGR HS C
Solar/Wind Harmer
-0.001
217208PARK ELE C
Solar/Wind Harmer
0
207439AE1-081 C O1
Solar/Wind Harmer
0.001
20676328BVR_Y1-020
Solar/Wind Harmer
-0.001
20674628WNG_W3-110
Solar/Wind Harmer
-0.001
207511W3-106 GEN
Solar/Wind Harmer
0.063
971009AG2-626 GEN
Solar/Wind Harmer
0.155
971007AG2-625 GEN
Solar/Wind Harmer
0.243
971519AH1-257 GEN
Solar/Wind Harmer
0.239
207437AD2-070 GEN
Solar/Wind Harmer
-0.001
966181AG1-487 GEN
Solar/Wind Harmer
0
966181AG1-487 GEN
Solar/Wind Harmer
4.641
966111AG1-480 GEN
Solar/Wind Harmer
0
966111AG1-480 GEN
Solar/Wind Harmer
4.122
970095AG2-074 GEN
Solar/Wind Harmer
0.413
208972BECR K09
Solar/Wind Harmer
3.022
209029WAYMART-WD
Solar/Wind Harmer
8.093
209027LOR2_Q27
Solar/Wind Harmer
11.889
212266LOR1
Solar/Wind Harmer
0.222
970237AG2-161 GEN
Solar/Wind Harmer
0.261
961541AF2-445A GEN
Solar/Wind Harmer
0.208
209142AF1-226 GEN
Solar/Wind Harmer
0.361
209093AE2-110 GEN
Solar/Wind Harmer
0.206
209120AE2-241 GEN
Solar/Wind Harmer
0.206
209045AE2-271 GEN
Solar/Wind Harmer
1.04
209059AE2-084 GEN
Solar/Wind Harmer
0.201
970665AG2-430 GEN
Solar/Wind Harmer
0.596
209130AF1-271A GEN
Solar/Wind Harmer
0.169
208862AG1-362 C
Solar/Wind Harmer
0.039
970679AG2-439 GEN
Solar/Wind Harmer
0.067
200917MEHOOPANY_G
Solar/Wind Harmer
9.213
226910AB2-157 C
Solar/Wind Helper
0.023
227287AC2-120 GEN
Solar/Wind Helper
0.246
226929AD2-058 GEN
Solar/Wind Helper
0.049
223401AF1-299 GEN
Solar/Wind Helper
0.127
223402AF1-300 C
Solar/Wind Helper
0.127
3138216PACIFIC
Solar/Wind Helper
0.08
316411AF1-147_GEN1
Solar/Wind Helper
0.383
316415AF1-147_GEN2
Solar/Wind Helper
0.383
3141426STAFORD
Solar/Wind Helper
0.104
3141196NOKESVL
Solar/Wind Helper
1.883
316006AB2-029 C
Solar/Wind Helper
0.147
316045AC1-158 PL2
Solar/Wind Helper
1.718
316447AC1-158 HLD
Solar/Wind Helper
1.181
316044AC1-158 PL1
Solar/Wind Helper
0.537
316450AC1-158 RIC
Solar/Wind Helper
0.143
315651AD1-115 GEN
Solar/Wind Helper
1.103
316164AC1-076 GEN
Solar/Wind Helper
0.46
316254AC1-120 GEN1
Solar/Wind Helper
0.44
316170AC1-121 GEN2
Solar/Wind Helper
0.147
944491AF1-114 GEN
Solar/Wind Helper
0.728
957971AF2-091 GEN
Solar/Wind Helper
0.248
966881AG1-559 GEN
Solar/Wind Helper
0.145
3132273ORANGE
Solar/Wind Helper
0.09
3147666LOUISA
Solar/Wind Helper
1.795
3147666LOUISA
Solar/Wind Helper
1.032
316192AB2-158 GEN
Solar/Wind Helper
0.636
316468AD1-105 GEN
Solar/Wind Helper
0.533
316223AC1-118
Solar/Wind Helper
0.144
3141906WESTMOR
Solar/Wind Helper
0.179
316337AD2-073 GEN
Solar/Wind Helper
0.143
966001AG1-469 GEN
Solar/Wind Helper
0.1
316077AC2-138 C
Solar/Wind Helper
0.1
3141813NORNECK
Solar/Wind Helper
0.444
964211AG1-282 GEN
Solar/Wind Helper
0.142
3141726DUNNSVL
Solar/Wind Helper
1.774
316404AE1-155 C
Solar/Wind Helper
0.903
316473AC1-191 GEN
Solar/Wind Helper
0.569
966871AG1-558 GEN
Solar/Wind Helper
0.142
316484AD2-074 GEN
Solar/Wind Helper
0.61
316487AF1-042 GEN
Solar/Wind Helper
0.319
961951AG1-038 GEN
Solar/Wind Helper
0.319
3141783LANCAST
Solar/Wind Helper
0.264
3141783LANCAST
Solar/Wind Helper
0.176
316312AB1-027
Solar/Wind Helper
0.177
3142416OLDCHRC
Solar/Wind Helper
1.145
3142416OLDCHRC
Solar/Wind Helper
0.439
3138133OCRAN
Solar/Wind Helper
0.264
3138133OCRAN
Solar/Wind Helper
0.132
3141913WHIT STONE
Solar/Wind Helper
0.44
238175AF1-290_GEN
Solar/Wind Helper
0.565
316314AB2-024 C
Solar/Wind Helper
0.141
316059AD1-063 C
Solar/Wind Helper
0.106
3141766HARMONY
Solar/Wind Helper
0.088
957601AF2-054 GEN
Solar/Wind Helper
0.14
316156AD2-030 GEN
Solar/Wind Helper
0.14
3141873WAN 176
Solar/Wind Helper
0.088
316203AE2-005 GEN
Solar/Wind Helper
0.917
315662AE1-191 GEN
Solar/Wind Helper
0.565
316280AD1-041 GEN
Solar/Wind Helper
0.353
315666AE1-190 GEN
Solar/Wind Helper
0.141
316441AF1-014 GEN
Solar/Wind Helper
0.14
316075AC2-137 C
Solar/Wind Helper
0.141
3143873LANEXA
Solar/Wind Helper
0.263
3142433PROV 92
Solar/Wind Helper
1.755
316233AE1-074 FULL
Solar/Wind Helper
0.141
3143526WINTERP
Solar/Wind Helper
2.278
3143526WINTERP
Solar/Wind Helper
2.278
3142946ENON
Solar/Wind Helper
0.146
3142946ENON
Solar/Wind Helper
0.044
3142543TWELFTH
Solar/Wind Helper
0.042
3143226MDLTHAN
Solar/Wind Helper
0.438
238169AE2-226 GEN1
Solar/Wind Helper
0.348
238170AE2-226 GEN2
Solar/Wind Helper
0.348
957831AF2-077 GEN
Solar/Wind Helper
0.14
316382AG1-145 C
Solar/Wind Helper
0.14
316159AE1-175 C
Solar/Wind Helper
0.14
964441AG1-307 GEN
Solar/Wind Helper
0.56
316240AF1-291 C
Solar/Wind Helper
0.14
316132AB2-190 GEN1
Solar/Wind Helper
0.524
316458AB2-190 GEN2
Solar/Wind Helper
0.524
315697AD1-025 GEN
Solar/Wind Helper
1.046
316033AB2-134 GEN
Solar/Wind Helper
0.993
316369SG1_INVT
Solar/Wind Helper
0.684
315839AE2-212 C
Solar/Wind Helper
0.139
961611AG1-000B GEN
Solar/Wind Helper
0.62
316236AE1-162_GEN
Solar/Wind Helper
0.139
3145336SMITFLD
Solar/Wind Helper
1.729
3145336SMITFLD
Solar/Wind Helper
0.173
3143316POE
Solar/Wind Helper
1.711
316294AC1-161 GEN
Solar/Wind Helper
1.665
315773AC2-141 GEN
Solar/Wind Helper
1.665
3144536CHRHLND
Solar/Wind Helper
0.065
316381AD1-082 GEN
Solar/Wind Helper
0.471
316083AB2-161 GEN
Solar/Wind Helper
0.347
316375AC2-012 GEN
Solar/Wind Helper
0.817
316036AC1-147 C
Solar/Wind Helper
0.138
3144873MCLAUGH
Solar/Wind Helper
0.011
316316AC1-027 C
Solar/Wind Helper
0.122
316185AD1-033 GEN
Solar/Wind Helper
0.484
316313AB2-026
Solar/Wind Helper
0.138
316258AE1-075 C
Solar/Wind Helper
0.124
316405AF2-144 C
Solar/Wind Helper
0.118
316072AD1-144
Solar/Wind Helper
0.104
3145506HICKORY
Solar/Wind Helper
1.721
3145506HICKORY
Solar/Wind Helper
1.033
3145506HICKORY
Solar/Wind Helper
0.258
316349AD2-085 GEN
Solar/Wind Helper
0.352
316339AD2-160 GEN
Solar/Wind Helper
0.345
316388AE2-253 GEN
Solar/Wind Helper
0.345
315833AF1-017_GEN
Solar/Wind Helper
0.276
316017AA1-139 ULT1
Solar/Wind Helper
0.414
316018AA1-139 ULT2
Solar/Wind Helper
0.414
3137176SLIGO L2192
Solar/Wind Helper
1.71
3146456SLIGO L269
Solar/Wind Helper
0.43
3146456SLIGO L269
Solar/Wind Helper
0.43
319010AE1-072 C
Solar/Wind Helper
1.035
316305AF2-043 C
Solar/Wind Helper
0.138
316246AF1-032 C
Solar/Wind Helper
0.104
3130086AYDLETT
Solar/Wind Helper
1.718
316336AC2-165 C
Solar/Wind Helper
0.689
316320Y1-086
Solar/Wind Helper
0.138
313526AB2-022
Solar/Wind Helper
0.138
3146386ELIZ CT
Solar/Wind Helper
0.428
3146486SUNBURY
Solar/Wind Helper
0.428
3146486SUNBURY
Solar/Wind Helper
0.428
316321Z2-027
Solar/Wind Helper
0.138
3145176PASQUOTANK
Solar/Wind Helper
0.265
238152AF2-075_GEN
Solar/Wind Helper
0.343
238147AE2-230_GEN1
Solar/Wind Helper
0.481
238148AE2-230_GEN2
Solar/Wind Helper
0.481
238149AF1-291A_GEN
Solar/Wind Helper
0.069
23546401DTGZ2-030
Solar/Wind Helper
0.069
3146516WINFALL
Solar/Wind Helper
1.384
3146516WINFALL
Solar/Wind Helper
0.427
3146516WINFALL
Solar/Wind Helper
0.427
3146516WINFALL
Solar/Wind Helper
0.427
3146516WINFALL
Solar/Wind Helper
0.427
3146516WINFALL
Solar/Wind Helper
0.427
3146626S HERTFORD
Solar/Wind Helper
0.426
3146626S HERTFORD
Solar/Wind Helper
0.426
3146626S HERTFORD
Solar/Wind Helper
0.426
3145273HOLLAND
Solar/Wind Helper
0.32
316315AB2-025 C
Solar/Wind Helper
0.137
237061AD1-155 GEN
Solar/Wind Helper
0.512
315742AE1-103 GEN
Solar/Wind Helper
0.273
3146376EDENTON
Solar/Wind Helper
0.424
3130156CHOWAN
Solar/Wind Helper
0.424
3130156CHOWAN
Solar/Wind Helper
0.424
3130156CHOWAN
Solar/Wind Helper
0.424
315614AA2-178 GEN
Solar/Wind Helper
0.542
315816AE2-034 GEN
Solar/Wind Helper
0.407
3145663CRESWEL
Solar/Wind Helper
1.181
3130546PLYMOUTH
Solar/Wind Helper
0.42
3156081AA2-088 GEN
Solar/Wind Helper
0.675
315732AD1-074 GEN1
Solar/Wind Helper
1.011
315733AD1-074 GEN2
Solar/Wind Helper
1.011
315737AD1-076 GEN
Solar/Wind Helper
0.735
315735AD1-075 GEN1
Solar/Wind Helper
0.506
316065AD1-022 GEN
Solar/Wind Helper
0.539
316023GEN1_S
Solar/Wind Helper
0.336
316365GEN2_N
Solar/Wind Helper
0.336
3146206CASHIE
Solar/Wind Helper
0.419
3146206CASHIE
Solar/Wind Helper
0.419
3146206CASHIE
Solar/Wind Helper
0.419
3145893MURPHYS
Solar/Wind Helper
1.674
3145893MURPHYS
Solar/Wind Helper
1.34
3145893MURPHYS
Solar/Wind Helper
1.13
316318V4-068
Solar/Wind Helper
0.031
3145893MURPHYS
Solar/Wind Helper
0.754
3145893MURPHYS
Solar/Wind Helper
0.419
3145893MURPHYS
Solar/Wind Helper
0.419
3145893MURPHYS
Solar/Wind Helper
0.335
316322AB2-045
Solar/Wind Helper
0.133
3146776BUCKING
Solar/Wind Helper
1.674
3146776BUCKING
Solar/Wind Helper
0.167
3146776BUCKING
Solar/Wind Helper
0.151
3146776BUCKING
Solar/Wind Helper
0.136
3146173TUNIS
Solar/Wind Helper
0.418
3146173TUNIS
Solar/Wind Helper
0.418
3146173TUNIS
Solar/Wind Helper
0.418
3146173TUNIS
Solar/Wind Helper
0.418
3146926FARMVIL
Solar/Wind Helper
0.25
3146926FARMVIL
Solar/Wind Helper
0.25
3156021HOLLOMANSOL
Solar/Wind Helper
0.67
316463AE2-346 GEN
Solar/Wind Helper
0.08
316140AB2-099
Solar/Wind Helper
0.034
961941AG1-037 GEN
Solar/Wind Helper
0.034
3145513AHOSKIE
Solar/Wind Helper
0.417
3145513AHOSKIE
Solar/Wind Helper
0.417
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
946281AF1-292 GEN
Solar/Wind Helper
0.1
966621AG1-532 GEN
Solar/Wind Helper
0.09
3146043SEABORD
Solar/Wind Helper
0.417
3145683EARLEYS
Solar/Wind Helper
0.833
3145683EARLEYS
Solar/Wind Helper
0.417
3145683EARLEYS
Solar/Wind Helper
0.417
3145683EARLEYS
Solar/Wind Helper
0.417
315607AA1-063A GEN
Solar/Wind Helper
0.502
316087AB2-174 GEN
Solar/Wind Helper
0.535
3146263WOODLND
Solar/Wind Helper
0.416
3146263WOODLND
Solar/Wind Helper
0.416
316181AB2-040 GEN
Solar/Wind Helper
0.534
313506AB2-031 GEN
Solar/Wind Helper
0.398
942461AE2-259 GEN
Solar/Wind Helper
0.668
3142666NORTHAMPTON
Solar/Wind Helper
0.415
3142666NORTHAMPTON
Solar/Wind Helper
0.415
3142666NORTHAMPTON
Solar/Wind Helper
0.415
3142666NORTHAMPTON
Solar/Wind Helper
0.415
3142666NORTHAMPTON
Solar/Wind Helper
0.249
3137643SOCKMAN
Solar/Wind Helper
1.658
3145963POPLR C
Solar/Wind Helper
0.415
3145963POPLR C
Solar/Wind Helper
0.415
316426AA2-053 GEN
Solar/Wind Helper
0.5
316190AA2-174 GEN
Solar/Wind Helper
0.033
3147043LAWRENC
Solar/Wind Helper
0.249
316011AB1-132 GEN
Solar/Wind Helper
9.955
316317KELFORD C
Solar/Wind Helper
0.154
3145823KELFORD
Solar/Wind Helper
0.415
3145823KELFORD
Solar/Wind Helper
0.415
3145593CAROLNA
Solar/Wind Helper
0.414
3145593CAROLNA
Solar/Wind Helper
0.414
3147133PAMPLIN
Solar/Wind Helper
1.3
3147133PAMPLIN
Solar/Wind Helper
0.414
3147133PAMPLIN
Solar/Wind Helper
0.331
316174AB2-169 GEN
Solar/Wind Helper
0.492
3145783HORNRTN
Solar/Wind Helper
0.414
315821AE2-092 GEN
Solar/Wind Helper
0.917
316478AD1-087 GEN
Solar/Wind Helper
0.427
316486AD2-202 GEN
Solar/Wind Helper
0.125
3145796HORNRTN
Solar/Wind Helper
1.653
3145796HORNRTN
Solar/Wind Helper
1.364
3145796HORNRTN
Solar/Wind Helper
1.322
3145796HORNRTN
Solar/Wind Helper
1.24
3145796HORNRTN
Solar/Wind Helper
0.413
3145796HORNRTN
Solar/Wind Helper
0.413
3145796HORNRTN
Solar/Wind Helper
0.165
3132123MT JACKSON
Solar/Wind Helper
1.292
3146033SCOT NK
Solar/Wind Helper
1.651
316034AC1-036 C
Solar/Wind Helper
0.091
3144303KENBRDG
Solar/Wind Helper
0.33
315785AD2-033 C
Solar/Wind Helper
0.86
316210AC1-098 GEN
Solar/Wind Helper
0.595
316212AC1-099_GEN
Solar/Wind Helper
0.33
316129AC1-054 GEN
Solar/Wind Helper
0.429
23777901MDS_W4-102
Solar/Wind Helper
0.132
3145933PARMELE
Solar/Wind Helper
0.822
3145933PARMELE
Solar/Wind Helper
0.411
3145933PARMELE
Solar/Wind Helper
0.411
316274AC1-208 GEN
Solar/Wind Helper
0.528
316131AB2-060 GEN
Solar/Wind Helper
0.527
313527AB2-043 GEN
Solar/Wind Helper
0.33
316239AB2-077_GEN
Solar/Wind Helper
0.132
316238AB2-078_GEN
Solar/Wind Helper
0.132
316237AB2-079_GEN
Solar/Wind Helper
0.132
3147983MERCK5
Solar/Wind Helper
0.164
235020AA1-095 C
Solar/Wind Helper
0.028
316499AE2-029_GEN
Solar/Wind Helper
0.328
316005AA1-067
Solar/Wind Helper
0.099
3145746EVERETS
Solar/Wind Helper
1.627
3145746EVERETS
Solar/Wind Helper
0.409
3145746EVERETS
Solar/Wind Helper
0.409
3145746EVERETS
Solar/Wind Helper
0.409
3145746EVERETS
Solar/Wind Helper
0.409
3145746EVERETS
Solar/Wind Helper
0.409
3145746EVERETS
Solar/Wind Helper
0.409
3145746EVERETS
Solar/Wind Helper
0.409
3148013FISHERV
Solar/Wind Helper
0.409
3148133STUARTS
Solar/Wind Helper
0.245
3148013FISHERV
Solar/Wind Helper
0.235
315722AD1-056 GEN
Solar/Wind Helper
0.394
315724AD1-057 GEN
Solar/Wind Helper
0.217
315687AD1-152 GEN
Solar/Wind Helper
0.525
316327AA2-057 GEN
Solar/Wind Helper
0.491
316494AC1-189 GEN
Solar/Wind Helper
0.524
316420AA1-050 GEN
Solar/Wind Helper
0.523
316319Z2-044 C
Solar/Wind Helper
0.078
3146233WITAKRS
Solar/Wind Helper
1.617
3146233WITAKRS
Solar/Wind Helper
0.276
961671AG1-007 GEN
Solar/Wind Helper
0.061
3145573BETHELC
Solar/Wind Helper
0.406
3145573BETHELC
Solar/Wind Helper
0.406
3146073TAR RVR
Solar/Wind Helper
0.406
3146083TARBORO
Solar/Wind Helper
0.406
3146083TARBORO
Solar/Wind Helper
0.406
3138543CONSLDL
Solar/Wind Helper
0.268
3146843MT LREL
Solar/Wind Helper
0.405
3146843MT LREL
Solar/Wind Helper
0.405
270494AE1-108_GEN
Solar/Wind Helper
0.973
316359AB2-059 GEN
Solar/Wind Helper
0.65
316049AB1-081 GEN
Solar/Wind Helper
0.52
3145543BTLEBRO
Solar/Wind Helper
0.404
3145543BTLEBRO
Solar/Wind Helper
0.404
3145543BTLEBRO
Solar/Wind Helper
0.404
3145543BTLEBRO
Solar/Wind Helper
0.324
316118AC1-105 GEN
Solar/Wind Helper
0.33
316248AF1-058 C
Solar/Wind Helper
0.129
3147173SINAI
Solar/Wind Helper
0.401
3147243WELCO
Solar/Wind Helper
0.251
316097T157 G90
Solar/Wind Helper
0.263
316095T157 G97
Solar/Wind Helper
0.263
237034AC2-136 C
Solar/Wind Helper
0.076
316003AC1-222 GEN
Solar/Wind Helper
0.415
3148463FAIRFLD
Solar/Wind Helper
0.398
23583801GRNGAP
Solar/Wind Helper
0.66
316222AC1-221 GEN
Solar/Wind Helper
0.473
316283AC2-100 C
Solar/Wind Helper
0.441
238221AF1-254 C O1
Solar/Wind Helper
0.125
316123AC1-075 GEN
Solar/Wind Helper
0.5
238208AF1-136 C
Solar/Wind Helper
0.098
270455AD2-022 GEN
Solar/Wind Helper
0.592
270457AD2-023 GEN
Solar/Wind Helper
0.333
238108AE1-109 GEN1
Solar/Wind Helper
0.041
238109AE1-109 GEN2
Solar/Wind Helper
0.041
238110AE1-109 GEN3
Solar/Wind Helper
0.041
23779801AA1-109
Solar/Wind Helper
0.055
237080AD1-060 GEN
Solar/Wind Helper
0.091
3147123OTTER R
Solar/Wind Helper
0.226
270016AE1-250 BESS
Solar/Wind Helper
0.451
270013AE1-250 PV
Solar/Wind Helper
0.451
316217AC1-145 GEN
Solar/Wind Helper
0.301
316197AC1-042 GEN
Solar/Wind Helper
0.252
3147312GRETNA
Solar/Wind Helper
0.299
3146802CHATHAM
Solar/Wind Helper
0.281
3147312GRETNA
Solar/Wind Helper
0.075
270197AD1-017 GEN1
Solar/Wind Helper
0.359
270574AD1-017 GEN2
Solar/Wind Helper
0.359
23777801MSM_W1-116
Solar/Wind Helper
0.083
237038AE2-054 C
Solar/Wind Helper
0.119
270173AC1-122 GEN
Solar/Wind Helper
0.45
235067AD1-061 GEN
Solar/Wind Helper
0.118
270018AE2-047 C O1
Solar/Wind Helper
0.295
943811AF1-049 GEN
Solar/Wind Helper
0.73
964991AG1-363 GEN
Solar/Wind Helper
1.745
237085AD2-009_GEN
Solar/Wind Helper
0.407
237002AB1-128_GEN
Solar/Wind Helper
0.116
270069AE2-166 C O1
Solar/Wind Helper
0.522
270336AE1-100 GEN
Solar/Wind Helper
0.382
237001AB1-127_GEN
Solar/Wind Helper
0.115
235062AE1-101 C1
Solar/Wind Helper
0.426
235063AE1-101 C2
Solar/Wind Helper
0.426
958121AF2-106 GEN
Solar/Wind Helper
0.844
23750701CROSSCHOOL
Solar/Wind Helper
0.151
270214AC2-123 GEN
Solar/Wind Helper
0.418
966391AG1-508 GEN
Solar/Wind Helper
1.976
238120AE2-309 GEN
Solar/Wind Helper
0.11
237030AB1-096 C
Solar/Wind Helper
0.055
237025AB1-124 C
Solar/Wind Helper
0.111
237006AB1-125 GEN
Solar/Wind Helper
0.083
235531U2-073 GEN
Solar/Wind Helper
0.322
238126S14_GEN_1
Solar/Wind Helper
0.345
238127S14_GEN_2
Solar/Wind Helper
0.345
235054AD2-180 GEN
Solar/Wind Helper
0.325
238118U2-030_1
Solar/Wind Helper
0.043
238185AF2-356 C
Solar/Wind Helper
0.949
960911AF2-382 GEN
Solar/Wind Helper
0.404
962211AG1-066 GEN
Solar/Wind Helper
0.424
23585401KL_K28_T16
Solar/Wind Helper
0.012
339255AE2-071 GEN
Solar/Wind Helper
0.185
339250AF1-203 GEN
Solar/Wind Helper
0.106
339231AF1-038_GEN
Solar/Wind Helper
0.316
957241AF2-018 GEN
Solar/Wind Helper
1.052
270053AF1-130 C
Solar/Wind Helper
1
339236AF1-050_GEN
Solar/Wind Helper
0.315
339241AF1-083 GEN
Solar/Wind Helper
0.288
235780M24_1
Solar/Wind Helper
1.057
237033AB1-150 GEN
Solar/Wind Helper
0.124
339206AE1-143 GEN
Solar/Wind Helper
0.502
339211AE2-254 GEN
Solar/Wind Helper
0.26
23751101LEADS_P59
Solar/Wind Helper
0.1
23562501BACKB
Solar/Wind Helper
0.076
943111AE2-339 GEN
Solar/Wind Helper
0.206
23751201ROTHROCK
Solar/Wind Helper
0.103
339216AC1-074 GEN
Solar/Wind Helper
0.409
339221AD2-048_GEN
Solar/Wind Helper
0.358
339243AC2-075 GEN1
Solar/Wind Helper
0.102
270330AC1-082 GEN2
Solar/Wind Helper
0.097
270329AC1-082 GEN1
Solar/Wind Helper
0.081
270331AC1-082 GEN3
Solar/Wind Helper
0.081
957381AF2-032 GEN
Solar/Wind Helper
0.102
270444AC2-157 GEN1
Solar/Wind Helper
0.509
270445AC2-157 GEN2
Solar/Wind Helper
0.509
276621W2-048 GEN
Solar/Wind Helper
1.623
276615X2-022 GEN
Solar/Wind Helper
0.477
276838X2-022 GEN2
Solar/Wind Helper
0.057
276763AC1-053 GEN1
Solar/Wind Helper
0.203
276764AC1-053 GEN2
Solar/Wind Helper
0.203
276785W4-005 GEN1
Solar/Wind Helper
0.156
276174W4-005 GEN2
Solar/Wind Helper
0.156
276686W4-005 GEN3
Solar/Wind Helper
0.156
274880W4-005 GEN4
Solar/Wind Helper
0.156
276848AB2-070 GEN3
Solar/Wind Helper
0.695
276668AB2-070 GEN1
Solar/Wind Helper
0.696
276849AB2-070 GEN2
Solar/Wind Helper
0.696
276157O29GEN1
Solar/Wind Helper
0.262
276158O29GEN2
Solar/Wind Helper
0.262
276741O09 GEN1
Solar/Wind Helper
0.968
276708O09 GEN2
Solar/Wind Helper
0.968
274848CAMPGROVE;RU
Solar/Wind Helper
0.963
276782AC1-033 GEN
Solar/Wind Helper
0.204
274877BISHOP HL;1U
Solar/Wind Helper
0.913
274878BISHOP HL;2U
Solar/Wind Helper
0.913
276603SUBLETTE C
Solar/Wind Helper
0.034
274853TWINGROVE;U1
Solar/Wind Helper
0.945
274854TWINGROVE;U2
Solar/Wind Helper
1.076
274857EASY ROAD;U1
Solar/Wind Helper
0.203
274858EASY ROAD;U2
Solar/Wind Helper
0.203
960001AF2-291 GEN
Solar/Wind Helper
0.507
274851PROVIDENC;RU
Solar/Wind Helper
0.219
274849CRESCENT ;1U
Solar/Wind Helper
0.376
276645AC1-214 GEN1
Solar/Wind Helper
0.52
276646AC1-214 GEN2
Solar/Wind Helper
0.52
274856ECOGROVE ;U1
Solar/Wind Helper
0.851
276611AD2-172 GEN
Solar/Wind Helper
0.253
276612AE2-035 GEN
Solar/Wind Helper
0.253
270186AC1-089 GEN
Solar/Wind Helper
0.759
276726Z2-087_GEN
Solar/Wind Helper
0.405
276655WTG1_EQ
Solar/Wind Helper
6.259
276656WTG2_EQ
Solar/Wind Helper
0.829
274855GSG-6 ;RU
Solar/Wind Helper
0.997
274850MENDOTA H;RU
Solar/Wind Helper
0.609
276602WESTBROOK C
Solar/Wind Helper
0.117
276863AD2-134 GEN
Solar/Wind Helper
0.483
276861AD2-134 GEN
Solar/Wind Helper
0.483
276799AD1-013 GEN
Solar/Wind Helper
0.202
946671AF1-331 GEN
Solar/Wind Helper
0.101
276872AE1-163_GEN1
Solar/Wind Helper
0.531
276876AE1-163_GEN2
Solar/Wind Helper
0.531
276889AE2-281 GEN
Solar/Wind Helper
0.152
270367AC2-061_GEN
Solar/Wind Helper
0.591
274872LEEDK;1U
Solar/Wind Helper
1.597
960751AF2-366 GEN
Solar/Wind Helper
0.479
252507AC2-088 GEN
Solar/Wind Helper
0.354
252509AD1-136 GEN
Solar/Wind Helper
0.051
276868AE1-113 GEN
Solar/Wind Helper
3.334
274879MINONK ;1U
Solar/Wind Helper
1.667
276882AE2-255 GEN
Solar/Wind Helper
1.414
962581AG1-107 GEN
Solar/Wind Helper
0.757
961491AF2-440 GEN
Solar/Wind Helper
0.252
274863CRW1-WTG
Solar/Wind Helper
0.606
274864CRW2-WTG
Solar/Wind Helper
0.606
276805AD2-038 GEN
Solar/Wind Helper
1
276901AD2-066 C O1
Solar/Wind Helper
0.586
25183208HLCRTG
Solar/Wind Helper
1.009
252510AF1-249 C
Solar/Wind Helper
0.101
274861TOP CROP ;1U
Solar/Wind Helper
0.192
274862TOP CROP ;2U
Solar/Wind Helper
1.876
276691AA1-018 GEN1
Solar/Wind Helper
0.39
252524AE2-267 GEN
Solar/Wind Helper
0.247
270356AE2-297 GEN
Solar/Wind Helper
0.769
927014AC1-188 GEN
Solar/Wind Helper
0.353
957541AF2-048 GEN
Solar/Wind Helper
0.353
274847GR RIDGE ;BU
Solar/Wind Helper
0.966
24385905FR-11G C
Solar/Wind Helper
5.547
966841AG1-555 GEN
Solar/Wind Helper
0.605
24387305FR-4G C
Solar/Wind Helper
4.232
24386205FR-12G C
Solar/Wind Helper
2.945
24386405FR-21G C
Solar/Wind Helper
2.821
24386605FR-22G C
Solar/Wind Helper
2.821
24387005FR-3G C
Solar/Wind Helper
2.793
276893AG1-478 C
Solar/Wind Helper
0.101
253316AC1-085 GEN3
Solar/Wind Helper
0.755
253317AC1-085 GEN4
Solar/Wind Helper
0.755
253433AC1-085 GEN1
Solar/Wind Helper
0.478
253432AC1-085 GEN2
Solar/Wind Helper
0.025
276897AD1-100 C
Solar/Wind Helper
5.69
939351AE1-166 GEN
Solar/Wind Helper
0.755
941551AE2-152 GEN
Solar/Wind Helper
0.755
274888KELLY CRK;1U
Solar/Wind Helper
1.585
274887GEN-1.85
Solar/Wind Helper
1.27
276772AC2-154 GEN
Solar/Wind Helper
0.252
276776AD2-060 GEN
Solar/Wind Helper
0.102
276843GEN-1.7
Solar/Wind Helper
0.315
944031AF1-071 GEN
Solar/Wind Helper
0.091
24725505WLD G2 C
Solar/Wind Helper
0.181
24699105WLD G1 C
Solar/Wind Helper
0.221
946581AF1-322 GEN
Solar/Wind Helper
1.006
24690905MDL-1G C
Solar/Wind Helper
0.37
270180AB1-006 GEN1
Solar/Wind Helper
0.297
24691005MDL-2G C
Solar/Wind Helper
0.422
24697605MDL-3G C
Solar/Wind Helper
0.433
24697905MDL-4G C
Solar/Wind Helper
0.329
24791305MDL-5G
Solar/Wind Helper
0.329
24755605MDL-5G
Solar/Wind Helper
0.329
270181AB1-006 GEN2
Solar/Wind Helper
0.563
276164X3-005 C
Solar/Wind Helper
0.045
24379505HDWTR1G C
Solar/Wind Helper
0.402
270240V3-007_GEN2
Solar/Wind Helper
0.319
942081AE2-220 GEN
Solar/Wind Helper
0.628
270209AC1-174_GEN
Solar/Wind Helper
0.503
270437AC2-090 C
Solar/Wind Helper
0.503
926881AC1-175 GEN
Solar/Wind Helper
0.503
270239V3-007_GEN1
Solar/Wind Helper
0.083
253394AE2-221_GEN
Solar/Wind Helper
0.754
253398AE2-221_GEN2
Solar/Wind Helper
0.754
957841AF2-078 GEN
Solar/Wind Helper
1.005
945421AF1-207 GEN
Solar/Wind Helper
0.904
253406AD2-031_GEN
Solar/Wind Helper
0.251
270383AD1-128 GEN
Solar/Wind Helper
0.753
247642Z2-115 C
Solar/Wind Helper
0.013
965461AG1-414 GEN
Solar/Wind Helper
0.377
940581AE2-045 GEN
Solar/Wind Helper
1.004
959141AF2-205 GEN
Solar/Wind Helper
1.003
958391AF2-133 GEN
Solar/Wind Helper
1.504
964861AG1-349 GEN
Solar/Wind Helper
1.303
270340AC2-060 GEN
Solar/Wind Helper
0.602
958381AF2-132 GEN
Solar/Wind Helper
1.504
964401AG1-302 GEN
Solar/Wind Helper
1.504
945581AF1-223 GEN
Solar/Wind Helper
0.751
945371AF1-202 GEN
Solar/Wind Helper
5.611
253415AE1-040 GEN
Solar/Wind Helper
0.24
270543AE2-219 C
Solar/Wind Helper
0.501
270535AF1-215 GEN1
Solar/Wind Helper
0.751
270536AF1-215 GEN2
Solar/Wind Helper
0.751
270055AF2-134 C O1
Solar/Wind Helper
0.501
253303V4-073 C
Solar/Wind Helper
0.01
247536S-71 GEN
Solar/Wind Helper
1.081
964611AG1-324 GEN
Solar/Wind Helper
0.195
944541AF1-119 GEN
Solar/Wind Helper
1.001
958711AF2-162 GEN
Solar/Wind Helper
0.225
270201AC2-176 GEN
Solar/Wind Helper
0.26
962031AG1-047 GEN
Solar/Wind Helper
0.5
961761AG1-017 GEN
Solar/Wind Helper
0.354
944201AF1-088_MTX
Adder
0
G-007ALTFEXP_G-007A->PJM
CMTX
66.749
HAMLETPJM->LTFIMP_HAMLET
CLTF
7.006
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
4.125
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
26.817
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
5.694
BlueGrassPJM->LTFIMP_BlueG
CLTF
17.743
CBM NorthLTFEXP_CBM-N->PJM
CBM
91.166
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
173.501

Details for PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line l/o AP_P1-2_PE-500-3835T_SRT-A


Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-500-3835T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:180.55 %
Rating:3700.0 MVA
Rating Type:B
MVA to Mitigate:6680.42
MW Contribution:0.63
Bus #Bus NameTypeMW Contribution
200202DELTA2 ST
50/50
10.231
200200DELTA2 CT1
50/50
5.727
200201DELTA2 CT2
50/50
5.727
200195DELTA ST
50/50
5.062
200192DELTA CT1
50/50
3.036
200193DELTA CT2
50/50
3.036
200194DELTA CT3
50/50
3.036
200034PCHBTM 2
50/50
200.531
200035PCHBTM 3
50/50
32.799
200203Y1-065-STG
50/50
11.435
200204Y1-065-CTG1
50/50
7.201
200205Y1-065-CTG2
50/50
7.201
200052ROCKSP 1
50/50
85.432
200053ROCKSP 2
50/50
85.432
200054ROCKSP 3
50/50
84.565
200055ROCKSP 4
50/50
84.565
971149AH1-027 GEN
Solar/Wind Harmer
0.443
233972AC1-094 C
Solar/Wind Harmer
-0.002
970695AG2-447 GEN
Solar/Wind Harmer
0.354
234033AF1-007_GEN
Solar/Wind Harmer
36.983
970545AG2-347 GEN
Solar/Wind Harmer
152.344
972133AH1-634 GEN
Solar/Wind Harmer
23.082
233987AB2-037 GEN
Solar/Wind Harmer
0
972177AH1-672 GEN
Solar/Wind Harmer
1.326
972069AH1-584 GEN
Solar/Wind Harmer
0.884
972071AH1-585 GEN
Solar/Wind Harmer
0.884
972073AH1-586 GEN
Solar/Wind Harmer
15.904
971747AH1-380 GEN
Solar/Wind Harmer
0.353
233923SMA
Solar/Wind Harmer
-0.002
233998TM1NIN_3.36
Solar/Wind Harmer
-0.002
233997TMININ_4.2
Solar/Wind Harmer
-0.002
233996TM1833_GEN
Solar/Wind Harmer
-0.002
233990AG1-397 GEN
Solar/Wind Harmer
-0.001
233990AG1-397 GEN
Solar/Wind Harmer
2.827
233940AF2-379 C
Solar/Wind Harmer
-0.002
234015AF2-250 C
Solar/Wind Harmer
-0.001
971195AH1-057 GEN
Solar/Wind Harmer
0.127
960671AF2-358 GEN
Solar/Wind Harmer
1.764
965821AG1-450 GEN
Solar/Wind Harmer
8.822
232426Y1-080 FULL
Solar/Wind Harmer
0
970277AG2-181 GEN
Solar/Wind Harmer
0.494
233946AB2-136 GEN
Solar/Wind Harmer
-0.002
233964AF2-378 GEN
Solar/Wind Harmer
0.001
234041AC1-190 GEN
Solar/Wind Harmer
0.881
233984AB2-036 GEN
Solar/Wind Harmer
1.608
233968AD2-076_GEN
Solar/Wind Harmer
0.852
234014AF1-036_GEN
Solar/Wind Harmer
0.348
970597AG2-380 GEN
Solar/Wind Harmer
6.958
234012AE2-112_GEN
Solar/Wind Harmer
0.296
971983AH1-536 GEN
Solar/Wind Harmer
0.724
970453AG2-297 GEN
Solar/Wind Harmer
0.307
971553AH1-274 GEN
Solar/Wind Harmer
0.268
945431AF1-208 GEN
Solar/Wind Harmer
0.719
970997AG2-616 GEN
Solar/Wind Harmer
0.797
972141AH1-641 GEN
Solar/Wind Harmer
0.239
230422AE1-104_GEN1
Solar/Wind Harmer
66.116
230425AE1-104_GEN2
Solar/Wind Harmer
66.116
230430AE1-229_GEN
Solar/Wind Harmer
-0.002
230433AD2-135 GEN
Solar/Wind Harmer
0
228351V2-046C
Solar/Wind Harmer
-0.002
971535AH1-265 GEN
Solar/Wind Harmer
0.466
971011AG2-627 GEN
Solar/Wind Harmer
0.634
228754AB1-001 C
Solar/Wind Harmer
-0.002
230407AD2-065 C
Solar/Wind Harmer
0
219137THOSOLAR C
Solar/Wind Harmer
0.001
219623KINSLEYBEA C
Solar/Wind Harmer
-0.001
219258KINSLEYDEP C
Solar/Wind Harmer
-0.001
218660EHAMPSOLAR C
Solar/Wind Harmer
-0.002
219766PARADISE C
Solar/Wind Harmer
-0.002
219907AC1-030 C
Solar/Wind Harmer
-0.002
219236SOUTHERNHQ C
Solar/Wind Harmer
-0.001
219906AC1-017 C
Solar/Wind Harmer
-0.002
219615MILLCREEK C
Solar/Wind Harmer
-0.002
214067T20SOLAR
Solar/Wind Harmer
-0.001
207522AF2-254 C
Solar/Wind Harmer
0.149
207500AE2-000G1
Solar/Wind Harmer
58.158
207497AE2-000G2
Solar/Wind Harmer
58.158
207507AE2-000G3
Solar/Wind Harmer
58.158
207487AE2-000G4
Solar/Wind Harmer
58.158
970025AG2-016 GEN
Solar/Wind Harmer
0.293
971189AH1-054 GEN
Solar/Wind Harmer
0.122
971667AH1-334 GEN
Solar/Wind Harmer
0.283
219727YARDVSOLFA C
Solar/Wind Harmer
0.001
219276PARKLANDSO C
Solar/Wind Harmer
0.001
219817TRENTONSOL C
Solar/Wind Harmer
0.001
219620RIDERU C
Solar/Wind Harmer
-0.001
20714328BYD_X4-031
Solar/Wind Harmer
0.029
20714428HOW_X1-037
Solar/Wind Harmer
-0.001
20720628TIN_W1-124
Solar/Wind Harmer
-0.001
219918AC2-009 C
Solar/Wind Harmer
0
20742028HF_AC1-207
Solar/Wind Harmer
-0.001
971521AH1-258 GEN
Solar/Wind Harmer
0.274
967451AG2-055 C O1
Solar/Wind Harmer
313.097
219612MATRIX C
Solar/Wind Harmer
0.001
218438BLK ROCK C
Solar/Wind Harmer
-0.001
218526CNTRALGAS2 C
Solar/Wind Harmer
0.001
218524CNTRALGAS1 C
Solar/Wind Harmer
0.001
218428ETC SOLAR C
Solar/Wind Harmer
0
217213AMBOY SO C
Solar/Wind Harmer
-0.001
219249CENTRALDIV C
Solar/Wind Harmer
-0.001
20673828FLE_V3-070
Solar/Wind Harmer
0.098
218449LINSOLAR C
Solar/Wind Harmer
0.001
20675428EAM_W2-061
Solar/Wind Harmer
-0.001
217081WEATEXAS C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
217206BARNGR HS C
Solar/Wind Harmer
-0.001
217208PARK ELE C
Solar/Wind Harmer
0
207439AE1-081 C O1
Solar/Wind Harmer
0.001
20676328BVR_Y1-020
Solar/Wind Harmer
-0.001
20674628WNG_W3-110
Solar/Wind Harmer
-0.001
207511W3-106 GEN
Solar/Wind Harmer
0.063
971009AG2-626 GEN
Solar/Wind Harmer
0.155
971007AG2-625 GEN
Solar/Wind Harmer
0.243
971519AH1-257 GEN
Solar/Wind Harmer
0.239
207437AD2-070 GEN
Solar/Wind Harmer
-0.001
966181AG1-487 GEN
Solar/Wind Harmer
0
966181AG1-487 GEN
Solar/Wind Harmer
4.639
966111AG1-480 GEN
Solar/Wind Harmer
0
966111AG1-480 GEN
Solar/Wind Harmer
4.12
970095AG2-074 GEN
Solar/Wind Harmer
0.412
208972BECR K09
Solar/Wind Harmer
3.021
209029WAYMART-WD
Solar/Wind Harmer
8.089
209027LOR2_Q27
Solar/Wind Harmer
11.883
212266LOR1
Solar/Wind Harmer
0.222
970237AG2-161 GEN
Solar/Wind Harmer
0.261
961541AF2-445A GEN
Solar/Wind Harmer
0.207
209142AF1-226 GEN
Solar/Wind Harmer
0.361
209093AE2-110 GEN
Solar/Wind Harmer
0.206
209120AE2-241 GEN
Solar/Wind Harmer
0.206
209045AE2-271 GEN
Solar/Wind Harmer
1.039
209059AE2-084 GEN
Solar/Wind Harmer
0.201
970665AG2-430 GEN
Solar/Wind Harmer
0.596
209130AF1-271A GEN
Solar/Wind Harmer
0.169
208862AG1-362 C
Solar/Wind Harmer
0.039
970679AG2-439 GEN
Solar/Wind Harmer
0.067
200917MEHOOPANY_G
Solar/Wind Harmer
9.207
226910AB2-157 C
Solar/Wind Helper
0.023
227287AC2-120 GEN
Solar/Wind Helper
0.246
226929AD2-058 GEN
Solar/Wind Helper
0.049
223401AF1-299 GEN
Solar/Wind Helper
0.127
223402AF1-300 C
Solar/Wind Helper
0.127
3138216PACIFIC
Solar/Wind Helper
0.08
316411AF1-147_GEN1
Solar/Wind Helper
0.383
316415AF1-147_GEN2
Solar/Wind Helper
0.383
3141426STAFORD
Solar/Wind Helper
0.104
3141196NOKESVL
Solar/Wind Helper
1.882
316006AB2-029 C
Solar/Wind Helper
0.147
316045AC1-158 PL2
Solar/Wind Helper
1.717
316447AC1-158 HLD
Solar/Wind Helper
1.18
316044AC1-158 PL1
Solar/Wind Helper
0.537
316450AC1-158 RIC
Solar/Wind Helper
0.143
315651AD1-115 GEN
Solar/Wind Helper
1.102
316164AC1-076 GEN
Solar/Wind Helper
0.46
316254AC1-120 GEN1
Solar/Wind Helper
0.44
316170AC1-121 GEN2
Solar/Wind Helper
0.147
944491AF1-114 GEN
Solar/Wind Helper
0.728
957971AF2-091 GEN
Solar/Wind Helper
0.247
966881AG1-559 GEN
Solar/Wind Helper
0.145
3132273ORANGE
Solar/Wind Helper
0.09
3147666LOUISA
Solar/Wind Helper
1.794
3147666LOUISA
Solar/Wind Helper
1.032
316192AB2-158 GEN
Solar/Wind Helper
0.635
316468AD1-105 GEN
Solar/Wind Helper
0.533
316223AC1-118
Solar/Wind Helper
0.144
3141906WESTMOR
Solar/Wind Helper
0.179
316337AD2-073 GEN
Solar/Wind Helper
0.143
966001AG1-469 GEN
Solar/Wind Helper
0.1
316077AC2-138 C
Solar/Wind Helper
0.1
3141813NORNECK
Solar/Wind Helper
0.444
964211AG1-282 GEN
Solar/Wind Helper
0.142
3141726DUNNSVL
Solar/Wind Helper
1.773
316404AE1-155 C
Solar/Wind Helper
0.903
316473AC1-191 GEN
Solar/Wind Helper
0.568
966871AG1-558 GEN
Solar/Wind Helper
0.142
316484AD2-074 GEN
Solar/Wind Helper
0.61
316487AF1-042 GEN
Solar/Wind Helper
0.319
961951AG1-038 GEN
Solar/Wind Helper
0.319
238175AF1-290_GEN
Solar/Wind Helper
0.566
3141783LANCAST
Solar/Wind Helper
0.264
3141783LANCAST
Solar/Wind Helper
0.176
316312AB1-027
Solar/Wind Helper
0.177
3142416OLDCHRC
Solar/Wind Helper
1.144
3142416OLDCHRC
Solar/Wind Helper
0.438
3138133OCRAN
Solar/Wind Helper
0.264
3138133OCRAN
Solar/Wind Helper
0.132
3141913WHIT STONE
Solar/Wind Helper
0.44
316314AB2-024 C
Solar/Wind Helper
0.141
316059AD1-063 C
Solar/Wind Helper
0.106
3141766HARMONY
Solar/Wind Helper
0.088
957601AF2-054 GEN
Solar/Wind Helper
0.14
316156AD2-030 GEN
Solar/Wind Helper
0.14
3141873WAN 176
Solar/Wind Helper
0.088
316203AE2-005 GEN
Solar/Wind Helper
0.917
315662AE1-191 GEN
Solar/Wind Helper
0.564
316280AD1-041 GEN
Solar/Wind Helper
0.353
315666AE1-190 GEN
Solar/Wind Helper
0.141
316441AF1-014 GEN
Solar/Wind Helper
0.14
316075AC2-137 C
Solar/Wind Helper
0.141
3143873LANEXA
Solar/Wind Helper
0.263
3142433PROV 92
Solar/Wind Helper
1.754
316233AE1-074 FULL
Solar/Wind Helper
0.141
3143526WINTERP
Solar/Wind Helper
2.277
3143526WINTERP
Solar/Wind Helper
2.277
238169AE2-226 GEN1
Solar/Wind Helper
0.349
238170AE2-226 GEN2
Solar/Wind Helper
0.349
3142946ENON
Solar/Wind Helper
0.146
3142946ENON
Solar/Wind Helper
0.044
3142543TWELFTH
Solar/Wind Helper
0.042
3143226MDLTHAN
Solar/Wind Helper
0.437
957831AF2-077 GEN
Solar/Wind Helper
0.14
964441AG1-307 GEN
Solar/Wind Helper
0.561
316382AG1-145 C
Solar/Wind Helper
0.14
316159AE1-175 C
Solar/Wind Helper
0.14
316240AF1-291 C
Solar/Wind Helper
0.14
316132AB2-190 GEN1
Solar/Wind Helper
0.524
316458AB2-190 GEN2
Solar/Wind Helper
0.524
315697AD1-025 GEN
Solar/Wind Helper
1.046
316033AB2-134 GEN
Solar/Wind Helper
0.993
316369SG1_INVT
Solar/Wind Helper
0.683
315839AE2-212 C
Solar/Wind Helper
0.139
961611AG1-000B GEN
Solar/Wind Helper
0.62
316236AE1-162_GEN
Solar/Wind Helper
0.139
3145336SMITFLD
Solar/Wind Helper
1.728
3145336SMITFLD
Solar/Wind Helper
0.173
3143316POE
Solar/Wind Helper
1.71
316294AC1-161 GEN
Solar/Wind Helper
1.665
315773AC2-141 GEN
Solar/Wind Helper
1.665
3144536CHRHLND
Solar/Wind Helper
0.065
316381AD1-082 GEN
Solar/Wind Helper
0.471
316083AB2-161 GEN
Solar/Wind Helper
0.346
316375AC2-012 GEN
Solar/Wind Helper
0.817
316036AC1-147 C
Solar/Wind Helper
0.138
3144873MCLAUGH
Solar/Wind Helper
0.011
316316AC1-027 C
Solar/Wind Helper
0.122
316185AD1-033 GEN
Solar/Wind Helper
0.484
316072AD1-144
Solar/Wind Helper
0.104
316313AB2-026
Solar/Wind Helper
0.138
316258AE1-075 C
Solar/Wind Helper
0.124
316405AF2-144 C
Solar/Wind Helper
0.118
3145506HICKORY
Solar/Wind Helper
1.72
3145506HICKORY
Solar/Wind Helper
1.032
3145506HICKORY
Solar/Wind Helper
0.258
316349AD2-085 GEN
Solar/Wind Helper
0.352
315833AF1-017_GEN
Solar/Wind Helper
0.276
316339AD2-160 GEN
Solar/Wind Helper
0.345
316388AE2-253 GEN
Solar/Wind Helper
0.345
316017AA1-139 ULT1
Solar/Wind Helper
0.414
316018AA1-139 ULT2
Solar/Wind Helper
0.414
3137176SLIGO L2192
Solar/Wind Helper
1.709
3146456SLIGO L269
Solar/Wind Helper
0.429
3146456SLIGO L269
Solar/Wind Helper
0.429
319010AE1-072 C
Solar/Wind Helper
1.035
316305AF2-043 C
Solar/Wind Helper
0.138
316246AF1-032 C
Solar/Wind Helper
0.103
3130086AYDLETT
Solar/Wind Helper
1.717
316336AC2-165 C
Solar/Wind Helper
0.688
316320Y1-086
Solar/Wind Helper
0.138
313526AB2-022
Solar/Wind Helper
0.138
3146386ELIZ CT
Solar/Wind Helper
0.428
3146486SUNBURY
Solar/Wind Helper
0.428
3146486SUNBURY
Solar/Wind Helper
0.428
316321Z2-027
Solar/Wind Helper
0.137
3145176PASQUOTANK
Solar/Wind Helper
0.265
238152AF2-075_GEN
Solar/Wind Helper
0.343
238147AE2-230_GEN1
Solar/Wind Helper
0.48
238148AE2-230_GEN2
Solar/Wind Helper
0.48
238149AF1-291A_GEN
Solar/Wind Helper
0.069
23546401DTGZ2-030
Solar/Wind Helper
0.069
3146516WINFALL
Solar/Wind Helper
1.383
3146516WINFALL
Solar/Wind Helper
0.427
3146516WINFALL
Solar/Wind Helper
0.427
3146516WINFALL
Solar/Wind Helper
0.427
3146516WINFALL
Solar/Wind Helper
0.427
3146516WINFALL
Solar/Wind Helper
0.427
3146626S HERTFORD
Solar/Wind Helper
0.426
3146626S HERTFORD
Solar/Wind Helper
0.426
3146626S HERTFORD
Solar/Wind Helper
0.426
3145273HOLLAND
Solar/Wind Helper
0.319
316315AB2-025 C
Solar/Wind Helper
0.137
237061AD1-155 GEN
Solar/Wind Helper
0.512
315742AE1-103 GEN
Solar/Wind Helper
0.273
3130156CHOWAN
Solar/Wind Helper
0.424
3130156CHOWAN
Solar/Wind Helper
0.424
3130156CHOWAN
Solar/Wind Helper
0.424
3146376EDENTON
Solar/Wind Helper
0.424
315614AA2-178 GEN
Solar/Wind Helper
0.542
315816AE2-034 GEN
Solar/Wind Helper
0.406
3145663CRESWEL
Solar/Wind Helper
1.181
3130546PLYMOUTH
Solar/Wind Helper
0.42
3156081AA2-088 GEN
Solar/Wind Helper
0.674
315732AD1-074 GEN1
Solar/Wind Helper
1.011
315733AD1-074 GEN2
Solar/Wind Helper
1.011
315737AD1-076 GEN
Solar/Wind Helper
0.735
315735AD1-075 GEN1
Solar/Wind Helper
0.505
316065AD1-022 GEN
Solar/Wind Helper
0.538
316023GEN1_S
Solar/Wind Helper
0.336
316365GEN2_N
Solar/Wind Helper
0.336
3146206CASHIE
Solar/Wind Helper
0.418
3146206CASHIE
Solar/Wind Helper
0.418
3146206CASHIE
Solar/Wind Helper
0.418
3145893MURPHYS
Solar/Wind Helper
1.674
3145893MURPHYS
Solar/Wind Helper
1.339
3145893MURPHYS
Solar/Wind Helper
1.13
316318V4-068
Solar/Wind Helper
0.031
3145893MURPHYS
Solar/Wind Helper
0.753
3145893MURPHYS
Solar/Wind Helper
0.418
3145893MURPHYS
Solar/Wind Helper
0.418
3145893MURPHYS
Solar/Wind Helper
0.335
316322AB2-045
Solar/Wind Helper
0.133
3146776BUCKING
Solar/Wind Helper
1.673
3146776BUCKING
Solar/Wind Helper
0.167
3146776BUCKING
Solar/Wind Helper
0.151
3146776BUCKING
Solar/Wind Helper
0.135
3146173TUNIS
Solar/Wind Helper
0.417
3146173TUNIS
Solar/Wind Helper
0.417
3146173TUNIS
Solar/Wind Helper
0.417
3146173TUNIS
Solar/Wind Helper
0.417
3146926FARMVIL
Solar/Wind Helper
0.25
3146926FARMVIL
Solar/Wind Helper
0.25
3156021HOLLOMANSOL
Solar/Wind Helper
0.669
316463AE2-346 GEN
Solar/Wind Helper
0.08
316140AB2-099
Solar/Wind Helper
0.033
961941AG1-037 GEN
Solar/Wind Helper
0.033
3145513AHOSKIE
Solar/Wind Helper
0.417
3145513AHOSKIE
Solar/Wind Helper
0.417
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
946281AF1-292 GEN
Solar/Wind Helper
0.1
966621AG1-532 GEN
Solar/Wind Helper
0.09
3146043SEABORD
Solar/Wind Helper
0.417
3145683EARLEYS
Solar/Wind Helper
0.833
3145683EARLEYS
Solar/Wind Helper
0.416
3145683EARLEYS
Solar/Wind Helper
0.416
3145683EARLEYS
Solar/Wind Helper
0.416
315607AA1-063A GEN
Solar/Wind Helper
0.501
316087AB2-174 GEN
Solar/Wind Helper
0.534
3146263WOODLND
Solar/Wind Helper
0.416
3146263WOODLND
Solar/Wind Helper
0.416
316181AB2-040 GEN
Solar/Wind Helper
0.534
313506AB2-031 GEN
Solar/Wind Helper
0.398
942461AE2-259 GEN
Solar/Wind Helper
0.667
3142666NORTHAMPTON
Solar/Wind Helper
0.415
3142666NORTHAMPTON
Solar/Wind Helper
0.415
3142666NORTHAMPTON
Solar/Wind Helper
0.415
3142666NORTHAMPTON
Solar/Wind Helper
0.415
3142666NORTHAMPTON
Solar/Wind Helper
0.249
3137643SOCKMAN
Solar/Wind Helper
1.657
3145963POPLR C
Solar/Wind Helper
0.415
3145963POPLR C
Solar/Wind Helper
0.415
316426AA2-053 GEN
Solar/Wind Helper
0.5
316190AA2-174 GEN
Solar/Wind Helper
0.033
3147043LAWRENC
Solar/Wind Helper
0.249
316011AB1-132 GEN
Solar/Wind Helper
9.95
316317KELFORD C
Solar/Wind Helper
0.154
3145823KELFORD
Solar/Wind Helper
0.414
3145823KELFORD
Solar/Wind Helper
0.414
3145593CAROLNA
Solar/Wind Helper
0.414
3145593CAROLNA
Solar/Wind Helper
0.414
3147133PAMPLIN
Solar/Wind Helper
1.3
3147133PAMPLIN
Solar/Wind Helper
0.414
3147133PAMPLIN
Solar/Wind Helper
0.331
316174AB2-169 GEN
Solar/Wind Helper
0.492
3145783HORNRTN
Solar/Wind Helper
0.414
315821AE2-092 GEN
Solar/Wind Helper
0.917
316478AD1-087 GEN
Solar/Wind Helper
0.426
316486AD2-202 GEN
Solar/Wind Helper
0.125
3145796HORNRTN
Solar/Wind Helper
1.652
3145796HORNRTN
Solar/Wind Helper
1.363
3145796HORNRTN
Solar/Wind Helper
1.322
3145796HORNRTN
Solar/Wind Helper
1.239
3145796HORNRTN
Solar/Wind Helper
0.413
3145796HORNRTN
Solar/Wind Helper
0.413
3145796HORNRTN
Solar/Wind Helper
0.165
3132123MT JACKSON
Solar/Wind Helper
1.291
3146033SCOT NK
Solar/Wind Helper
1.65
23777901MDS_W4-102
Solar/Wind Helper
0.132
316034AC1-036 C
Solar/Wind Helper
0.091
3144303KENBRDG
Solar/Wind Helper
0.329
315785AD2-033 C
Solar/Wind Helper
0.859
316210AC1-098 GEN
Solar/Wind Helper
0.594
316212AC1-099_GEN
Solar/Wind Helper
0.33
316129AC1-054 GEN
Solar/Wind Helper
0.429
235020AA1-095 C
Solar/Wind Helper
0.028
3145933PARMELE
Solar/Wind Helper
0.821
3145933PARMELE
Solar/Wind Helper
0.411
3145933PARMELE
Solar/Wind Helper
0.411
316274AC1-208 GEN
Solar/Wind Helper
0.527
316131AB2-060 GEN
Solar/Wind Helper
0.527
313527AB2-043 GEN
Solar/Wind Helper
0.329
316239AB2-077_GEN
Solar/Wind Helper
0.132
316238AB2-078_GEN
Solar/Wind Helper
0.132
316237AB2-079_GEN
Solar/Wind Helper
0.132
3147983MERCK5
Solar/Wind Helper
0.164
316499AE2-029_GEN
Solar/Wind Helper
0.328
316005AA1-067
Solar/Wind Helper
0.098
3145746EVERETS
Solar/Wind Helper
1.626
3145746EVERETS
Solar/Wind Helper
0.409
3145746EVERETS
Solar/Wind Helper
0.409
3145746EVERETS
Solar/Wind Helper
0.409
3145746EVERETS
Solar/Wind Helper
0.409
3145746EVERETS
Solar/Wind Helper
0.409
3145746EVERETS
Solar/Wind Helper
0.409
3145746EVERETS
Solar/Wind Helper
0.409
3148013FISHERV
Solar/Wind Helper
0.408
3148133STUARTS
Solar/Wind Helper
0.245
3148013FISHERV
Solar/Wind Helper
0.235
315722AD1-056 GEN
Solar/Wind Helper
0.393
315724AD1-057 GEN
Solar/Wind Helper
0.216
315687AD1-152 GEN
Solar/Wind Helper
0.525
316327AA2-057 GEN
Solar/Wind Helper
0.491
316494AC1-189 GEN
Solar/Wind Helper
0.523
316420AA1-050 GEN
Solar/Wind Helper
0.522
316319Z2-044 C
Solar/Wind Helper
0.078
3146233WITAKRS
Solar/Wind Helper
1.616
3146233WITAKRS
Solar/Wind Helper
0.276
961671AG1-007 GEN
Solar/Wind Helper
0.061
3145573BETHELC
Solar/Wind Helper
0.406
3145573BETHELC
Solar/Wind Helper
0.406
3146073TAR RVR
Solar/Wind Helper
0.406
3146083TARBORO
Solar/Wind Helper
0.406
3146083TARBORO
Solar/Wind Helper
0.406
3138543CONSLDL
Solar/Wind Helper
0.268
3146843MT LREL
Solar/Wind Helper
0.405
3146843MT LREL
Solar/Wind Helper
0.405
270494AE1-108_GEN
Solar/Wind Helper
0.972
316359AB2-059 GEN
Solar/Wind Helper
0.65
316049AB1-081 GEN
Solar/Wind Helper
0.52
3145543BTLEBRO
Solar/Wind Helper
0.404
3145543BTLEBRO
Solar/Wind Helper
0.404
3145543BTLEBRO
Solar/Wind Helper
0.404
3145543BTLEBRO
Solar/Wind Helper
0.323
316118AC1-105 GEN
Solar/Wind Helper
0.33
237034AC2-136 C
Solar/Wind Helper
0.076
316248AF1-058 C
Solar/Wind Helper
0.129
3147173SINAI
Solar/Wind Helper
0.401
3147243WELCO
Solar/Wind Helper
0.251
316097T157 G90
Solar/Wind Helper
0.263
316095T157 G97
Solar/Wind Helper
0.263
316003AC1-222 GEN
Solar/Wind Helper
0.415
3148463FAIRFLD
Solar/Wind Helper
0.398
23583801GRNGAP
Solar/Wind Helper
0.66
238221AF1-254 C O1
Solar/Wind Helper
0.126
316222AC1-221 GEN
Solar/Wind Helper
0.473
316283AC2-100 C
Solar/Wind Helper
0.44
316123AC1-075 GEN
Solar/Wind Helper
0.5
238208AF1-136 C
Solar/Wind Helper
0.098
270455AD2-022 GEN
Solar/Wind Helper
0.592
270457AD2-023 GEN
Solar/Wind Helper
0.333
238108AE1-109 GEN1
Solar/Wind Helper
0.041
238109AE1-109 GEN2
Solar/Wind Helper
0.041
238110AE1-109 GEN3
Solar/Wind Helper
0.041
23779801AA1-109
Solar/Wind Helper
0.055
237080AD1-060 GEN
Solar/Wind Helper
0.092
3147123OTTER R
Solar/Wind Helper
0.226
270016AE1-250 BESS
Solar/Wind Helper
0.451
270013AE1-250 PV
Solar/Wind Helper
0.451
316217AC1-145 GEN
Solar/Wind Helper
0.3
316197AC1-042 GEN
Solar/Wind Helper
0.252
3147312GRETNA
Solar/Wind Helper
0.299
3146802CHATHAM
Solar/Wind Helper
0.28
3147312GRETNA
Solar/Wind Helper
0.075
23777801MSM_W1-116
Solar/Wind Helper
0.084
270197AD1-017 GEN1
Solar/Wind Helper
0.359
270574AD1-017 GEN2
Solar/Wind Helper
0.359
237038AE2-054 C
Solar/Wind Helper
0.119
235067AD1-061 GEN
Solar/Wind Helper
0.119
270173AC1-122 GEN
Solar/Wind Helper
0.45
270018AE2-047 C O1
Solar/Wind Helper
0.295
943811AF1-049 GEN
Solar/Wind Helper
0.73
237002AB1-128_GEN
Solar/Wind Helper
0.117
237085AD2-009_GEN
Solar/Wind Helper
0.408
964991AG1-363 GEN
Solar/Wind Helper
1.744
270069AE2-166 C O1
Solar/Wind Helper
0.521
270336AE1-100 GEN
Solar/Wind Helper
0.382
237001AB1-127_GEN
Solar/Wind Helper
0.116
235062AE1-101 C1
Solar/Wind Helper
0.428
235063AE1-101 C2
Solar/Wind Helper
0.428
958121AF2-106 GEN
Solar/Wind Helper
0.844
23750701CROSSCHOOL
Solar/Wind Helper
0.151
237030AB1-096 C
Solar/Wind Helper
0.056
270214AC2-123 GEN
Solar/Wind Helper
0.418
966391AG1-508 GEN
Solar/Wind Helper
1.975
237025AB1-124 C
Solar/Wind Helper
0.111
237006AB1-125 GEN
Solar/Wind Helper
0.084
238120AE2-309 GEN
Solar/Wind Helper
0.11
235531U2-073 GEN
Solar/Wind Helper
0.322
238126S14_GEN_1
Solar/Wind Helper
0.345
238127S14_GEN_2
Solar/Wind Helper
0.345
235054AD2-180 GEN
Solar/Wind Helper
0.325
238118U2-030_1
Solar/Wind Helper
0.043
238185AF2-356 C
Solar/Wind Helper
0.948
960911AF2-382 GEN
Solar/Wind Helper
0.404
962211AG1-066 GEN
Solar/Wind Helper
0.424
23585401KL_K28_T16
Solar/Wind Helper
0.012
339255AE2-071 GEN
Solar/Wind Helper
0.185
339250AF1-203 GEN
Solar/Wind Helper
0.105
339231AF1-038_GEN
Solar/Wind Helper
0.316
957241AF2-018 GEN
Solar/Wind Helper
1.052
270053AF1-130 C
Solar/Wind Helper
0.999
339236AF1-050_GEN
Solar/Wind Helper
0.315
339241AF1-083 GEN
Solar/Wind Helper
0.288
235780M24_1
Solar/Wind Helper
1.056
237033AB1-150 GEN
Solar/Wind Helper
0.124
339206AE1-143 GEN
Solar/Wind Helper
0.501
339211AE2-254 GEN
Solar/Wind Helper
0.26
23751101LEADS_P59
Solar/Wind Helper
0.1
23562501BACKB
Solar/Wind Helper
0.076
943111AE2-339 GEN
Solar/Wind Helper
0.206
23751201ROTHROCK
Solar/Wind Helper
0.103
339216AC1-074 GEN
Solar/Wind Helper
0.409
339243AC2-075 GEN1
Solar/Wind Helper
0.102
339221AD2-048_GEN
Solar/Wind Helper
0.358
270330AC1-082 GEN2
Solar/Wind Helper
0.097
270329AC1-082 GEN1
Solar/Wind Helper
0.081
270331AC1-082 GEN3
Solar/Wind Helper
0.081
957381AF2-032 GEN
Solar/Wind Helper
0.102
270444AC2-157 GEN1
Solar/Wind Helper
0.509
270445AC2-157 GEN2
Solar/Wind Helper
0.509
276621W2-048 GEN
Solar/Wind Helper
1.622
276615X2-022 GEN
Solar/Wind Helper
0.477
276838X2-022 GEN2
Solar/Wind Helper
0.057
276763AC1-053 GEN1
Solar/Wind Helper
0.203
276764AC1-053 GEN2
Solar/Wind Helper
0.203
276785W4-005 GEN1
Solar/Wind Helper
0.156
276174W4-005 GEN2
Solar/Wind Helper
0.156
276686W4-005 GEN3
Solar/Wind Helper
0.156
274880W4-005 GEN4
Solar/Wind Helper
0.156
276848AB2-070 GEN3
Solar/Wind Helper
0.694
276668AB2-070 GEN1
Solar/Wind Helper
0.696
276849AB2-070 GEN2
Solar/Wind Helper
0.696
274848CAMPGROVE;RU
Solar/Wind Helper
0.963
276157O29GEN1
Solar/Wind Helper
0.262
276158O29GEN2
Solar/Wind Helper
0.262
276741O09 GEN1
Solar/Wind Helper
0.967
276708O09 GEN2
Solar/Wind Helper
0.967
276782AC1-033 GEN
Solar/Wind Helper
0.204
274877BISHOP HL;1U
Solar/Wind Helper
0.912
274878BISHOP HL;2U
Solar/Wind Helper
0.912
274857EASY ROAD;U1
Solar/Wind Helper
0.203
274858EASY ROAD;U2
Solar/Wind Helper
0.203
960001AF2-291 GEN
Solar/Wind Helper
0.507
276603SUBLETTE C
Solar/Wind Helper
0.034
274853TWINGROVE;U1
Solar/Wind Helper
0.944
274854TWINGROVE;U2
Solar/Wind Helper
1.076
274851PROVIDENC;RU
Solar/Wind Helper
0.219
274849CRESCENT ;1U
Solar/Wind Helper
0.376
276645AC1-214 GEN1
Solar/Wind Helper
0.52
276646AC1-214 GEN2
Solar/Wind Helper
0.52
274856ECOGROVE ;U1
Solar/Wind Helper
0.85
276611AD2-172 GEN
Solar/Wind Helper
0.253
276612AE2-035 GEN
Solar/Wind Helper
0.253
270186AC1-089 GEN
Solar/Wind Helper
0.759
276726Z2-087_GEN
Solar/Wind Helper
0.405
276655WTG1_EQ
Solar/Wind Helper
6.256
276656WTG2_EQ
Solar/Wind Helper
0.828
274855GSG-6 ;RU
Solar/Wind Helper
0.996
274850MENDOTA H;RU
Solar/Wind Helper
0.609
276602WESTBROOK C
Solar/Wind Helper
0.117
276863AD2-134 GEN
Solar/Wind Helper
0.483
276861AD2-134 GEN
Solar/Wind Helper
0.483
276799AD1-013 GEN
Solar/Wind Helper
0.202
946671AF1-331 GEN
Solar/Wind Helper
0.101
276872AE1-163_GEN1
Solar/Wind Helper
0.531
276876AE1-163_GEN2
Solar/Wind Helper
0.531
276889AE2-281 GEN
Solar/Wind Helper
0.152
270367AC2-061_GEN
Solar/Wind Helper
0.591
274872LEEDK;1U
Solar/Wind Helper
1.596
252507AC2-088 GEN
Solar/Wind Helper
0.353
252509AD1-136 GEN
Solar/Wind Helper
0.05
960751AF2-366 GEN
Solar/Wind Helper
0.479
276868AE1-113 GEN
Solar/Wind Helper
3.332
274879MINONK ;1U
Solar/Wind Helper
1.666
276882AE2-255 GEN
Solar/Wind Helper
1.413
962581AG1-107 GEN
Solar/Wind Helper
0.757
274863CRW1-WTG
Solar/Wind Helper
0.606
274864CRW2-WTG
Solar/Wind Helper
0.606
961491AF2-440 GEN
Solar/Wind Helper
0.252
276805AD2-038 GEN
Solar/Wind Helper
0.999
276901AD2-066 C O1
Solar/Wind Helper
0.585
25183208HLCRTG
Solar/Wind Helper
1.009
252510AF1-249 C
Solar/Wind Helper
0.101
274861TOP CROP ;1U
Solar/Wind Helper
0.192
274862TOP CROP ;2U
Solar/Wind Helper
1.875
276691AA1-018 GEN1
Solar/Wind Helper
0.389
252524AE2-267 GEN
Solar/Wind Helper
0.247
270356AE2-297 GEN
Solar/Wind Helper
0.769
927014AC1-188 GEN
Solar/Wind Helper
0.353
957541AF2-048 GEN
Solar/Wind Helper
0.353
274847GR RIDGE ;BU
Solar/Wind Helper
0.966
24385905FR-11G C
Solar/Wind Helper
5.544
966841AG1-555 GEN
Solar/Wind Helper
0.604
24387305FR-4G C
Solar/Wind Helper
4.229
24386205FR-12G C
Solar/Wind Helper
2.944
24386405FR-21G C
Solar/Wind Helper
2.82
24386605FR-22G C
Solar/Wind Helper
2.82
24387005FR-3G C
Solar/Wind Helper
2.791
276893AG1-478 C
Solar/Wind Helper
0.101
276897AD1-100 C
Solar/Wind Helper
5.687
253316AC1-085 GEN3
Solar/Wind Helper
0.755
253317AC1-085 GEN4
Solar/Wind Helper
0.755
939351AE1-166 GEN
Solar/Wind Helper
0.755
941551AE2-152 GEN
Solar/Wind Helper
0.755
253433AC1-085 GEN1
Solar/Wind Helper
0.478
253432AC1-085 GEN2
Solar/Wind Helper
0.025
274888KELLY CRK;1U
Solar/Wind Helper
1.584
274887GEN-1.85
Solar/Wind Helper
1.269
276772AC2-154 GEN
Solar/Wind Helper
0.251
276776AD2-060 GEN
Solar/Wind Helper
0.102
276843GEN-1.7
Solar/Wind Helper
0.315
944031AF1-071 GEN
Solar/Wind Helper
0.09
946581AF1-322 GEN
Solar/Wind Helper
1.005
24690905MDL-1G C
Solar/Wind Helper
0.37
270180AB1-006 GEN1
Solar/Wind Helper
0.297
24725505WLD G2 C
Solar/Wind Helper
0.181
24699105WLD G1 C
Solar/Wind Helper
0.221
24691005MDL-2G C
Solar/Wind Helper
0.422
24697605MDL-3G C
Solar/Wind Helper
0.432
24697905MDL-4G C
Solar/Wind Helper
0.328
24791305MDL-5G
Solar/Wind Helper
0.328
24755605MDL-5G
Solar/Wind Helper
0.328
270181AB1-006 GEN2
Solar/Wind Helper
0.563
276164X3-005 C
Solar/Wind Helper
0.045
24379505HDWTR1G C
Solar/Wind Helper
0.402
270240V3-007_GEN2
Solar/Wind Helper
0.319
942081AE2-220 GEN
Solar/Wind Helper
0.628
270209AC1-174_GEN
Solar/Wind Helper
0.502
270437AC2-090 C
Solar/Wind Helper
0.502
926881AC1-175 GEN
Solar/Wind Helper
0.502
270239V3-007_GEN1
Solar/Wind Helper
0.083
253394AE2-221_GEN
Solar/Wind Helper
0.753
253398AE2-221_GEN2
Solar/Wind Helper
0.753
957841AF2-078 GEN
Solar/Wind Helper
1.004
945421AF1-207 GEN
Solar/Wind Helper
0.904
253406AD2-031_GEN
Solar/Wind Helper
0.251
270383AD1-128 GEN
Solar/Wind Helper
0.753
965461AG1-414 GEN
Solar/Wind Helper
0.376
247642Z2-115 C
Solar/Wind Helper
0.013
940581AE2-045 GEN
Solar/Wind Helper
1.003
959141AF2-205 GEN
Solar/Wind Helper
1.003
958391AF2-133 GEN
Solar/Wind Helper
1.504
964861AG1-349 GEN
Solar/Wind Helper
1.303
270340AC2-060 GEN
Solar/Wind Helper
0.601
958381AF2-132 GEN
Solar/Wind Helper
1.503
964401AG1-302 GEN
Solar/Wind Helper
1.503
945581AF1-223 GEN
Solar/Wind Helper
0.751
945371AF1-202 GEN
Solar/Wind Helper
5.608
253415AE1-040 GEN
Solar/Wind Helper
0.24
270543AE2-219 C
Solar/Wind Helper
0.501
270535AF1-215 GEN1
Solar/Wind Helper
0.751
270536AF1-215 GEN2
Solar/Wind Helper
0.751
270055AF2-134 C O1
Solar/Wind Helper
0.501
247536S-71 GEN
Solar/Wind Helper
1.08
253303V4-073 C
Solar/Wind Helper
0.01
964611AG1-324 GEN
Solar/Wind Helper
0.195
G-007ALTFEXP_G-007A->PJM
CMTX
66.724
HAMLETPJM->LTFIMP_HAMLET
CLTF
7.002
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
4.123
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
26.803
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
5.691
BlueGrassPJM->LTFIMP_BlueG
CLTF
17.733
CBM NorthLTFEXP_CBM-N->PJM
CBM
91.126
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
173.434

Details for PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line l/o PECO_P4_PEACH035_SRT-A/* $ CHESCO $ PECO_P4_PEACH035 $ STBK


Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
Contingency Name:
PECO_P4_PEACH035_SRT-A/* $ CHESCO $ PECO_P4_PEACH035 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:170.51 %
Rating:3700.0 MVA
Rating Type:B
MVA to Mitigate:6308.69
MW Contribution:0.62
Bus #Bus NameTypeMW Contribution
200202DELTA2 ST
50/50
12.396
200200DELTA2 CT1
50/50
6.939
200201DELTA2 CT2
50/50
6.939
200195DELTA ST
50/50
6.133
200192DELTA CT1
50/50
3.679
200193DELTA CT2
50/50
3.679
200194DELTA CT3
50/50
3.679
200034PCHBTM 2
50/50
242.875
200035PCHBTM 3
50/50
40.134
200203Y1-065-STG
50/50
13.619
200204Y1-065-CTG1
50/50
8.576
200205Y1-065-CTG2
50/50
8.576
200052ROCKSP 1
50/50
101.751
200053ROCKSP 2
50/50
101.751
200054ROCKSP 3
50/50
100.718
200055ROCKSP 4
50/50
100.718
231914HR8
50/50
4.009
231911HR5
50/50
2.739
231912HR6
50/50
2.739
231913HR7
50/50
2.739
233920W3-032A-CTG1
50/50
4.179
233921W3-032A-STG1
50/50
2.412
232616GEN FOOD
50/50
0.316
232901NORTHST
50/50
17.469
232904IR4
50/50
166.003
232920IR10
50/50
6.302
232921TASLEY2G
50/50
0.683
232905CHERITON_25
50/50
0.259
232912OH NUG1
50/50
17.046
232913OH NUG2
50/50
17.046
232914OH NUG3
50/50
17.046
232915OH NUG4
50/50
17.046
232916OH NUG5
50/50
17.046
232917OH NUG6
50/50
17.046
232918OH NUG7
50/50
17.046
234034AF2-060
50/50
3.409
232926CRISFLD1
50/50
0.207
232910NRG_G1
50/50
0.903
232911NRG_G2
50/50
0.903
971149AH1-027 GEN
Solar/Wind Harmer
0.475
233972AC1-094 C
Solar/Wind Harmer
-0.002
970695AG2-447 GEN
Solar/Wind Harmer
0.38
233987AB2-037 GEN
Solar/Wind Harmer
0
234033AF1-007_GEN
Solar/Wind Harmer
39.641
970545AG2-347 GEN
Solar/Wind Harmer
163.292
972133AH1-634 GEN
Solar/Wind Harmer
24.741
972069AH1-584 GEN
Solar/Wind Harmer
0.947
972071AH1-585 GEN
Solar/Wind Harmer
0.947
972073AH1-586 GEN
Solar/Wind Harmer
17.047
971747AH1-380 GEN
Solar/Wind Harmer
0.379
233923SMA
Solar/Wind Harmer
-0.002
233998TM1NIN_3.36
Solar/Wind Harmer
-0.002
233997TMININ_4.2
Solar/Wind Harmer
-0.002
233996TM1833_GEN
Solar/Wind Harmer
-0.002
972177AH1-672 GEN
Solar/Wind Harmer
1.42
233990AG1-397 GEN
Solar/Wind Harmer
-0.001
233990AG1-397 GEN
Solar/Wind Harmer
3.03
233940AF2-379 C
Solar/Wind Harmer
-0.002
234015AF2-250 C
Solar/Wind Harmer
-0.001
971195AH1-057 GEN
Solar/Wind Harmer
0.136
960671AF2-358 GEN
Solar/Wind Harmer
1.891
965821AG1-450 GEN
Solar/Wind Harmer
9.455
232426Y1-080 FULL
Solar/Wind Harmer
0
970277AG2-181 GEN
Solar/Wind Harmer
0.529
233946AB2-136 GEN
Solar/Wind Harmer
-0.002
233964AF2-378 GEN
Solar/Wind Harmer
0.001
234041AC1-190 GEN
Solar/Wind Harmer
0.944
233984AB2-036 GEN
Solar/Wind Harmer
1.72
233968AD2-076_GEN
Solar/Wind Harmer
0.91
234014AF1-036_GEN
Solar/Wind Harmer
0.372
970597AG2-380 GEN
Solar/Wind Harmer
7.431
234012AE2-112_GEN
Solar/Wind Harmer
0.316
971983AH1-536 GEN
Solar/Wind Harmer
0.772
970453AG2-297 GEN
Solar/Wind Harmer
0.305
971553AH1-274 GEN
Solar/Wind Harmer
0.265
945431AF1-208 GEN
Solar/Wind Harmer
0.71
230422AE1-104_GEN1
Solar/Wind Harmer
65.179
230425AE1-104_GEN2
Solar/Wind Harmer
65.179
970997AG2-616 GEN
Solar/Wind Harmer
0.785
972141AH1-641 GEN
Solar/Wind Harmer
0.236
230430AE1-229_GEN
Solar/Wind Harmer
-0.002
230433AD2-135 GEN
Solar/Wind Harmer
0
228351V2-046C
Solar/Wind Harmer
-0.002
971535AH1-265 GEN
Solar/Wind Harmer
0.458
971011AG2-627 GEN
Solar/Wind Harmer
0.622
228754AB1-001 C
Solar/Wind Harmer
-0.002
230407AD2-065 C
Solar/Wind Harmer
0
219137THOSOLAR C
Solar/Wind Harmer
0.001
219623KINSLEYBEA C
Solar/Wind Harmer
-0.001
219258KINSLEYDEP C
Solar/Wind Harmer
-0.001
218660EHAMPSOLAR C
Solar/Wind Harmer
-0.001
219766PARADISE C
Solar/Wind Harmer
-0.001
219907AC1-030 C
Solar/Wind Harmer
-0.001
219236SOUTHERNHQ C
Solar/Wind Harmer
-0.001
219906AC1-017 C
Solar/Wind Harmer
-0.001
219615MILLCREEK C
Solar/Wind Harmer
-0.001
207522AF2-254 C
Solar/Wind Harmer
0.138
214067T20SOLAR
Solar/Wind Harmer
-0.001
207500AE2-000G1
Solar/Wind Harmer
54.021
207497AE2-000G2
Solar/Wind Harmer
54.021
207507AE2-000G3
Solar/Wind Harmer
54.021
207487AE2-000G4
Solar/Wind Harmer
54.021
970025AG2-016 GEN
Solar/Wind Harmer
0.271
971189AH1-054 GEN
Solar/Wind Harmer
0.113
971667AH1-334 GEN
Solar/Wind Harmer
0.261
219727YARDVSOLFA C
Solar/Wind Harmer
0.001
219276PARKLANDSO C
Solar/Wind Harmer
0.001
20714328BYD_X4-031
Solar/Wind Harmer
0.026
219620RIDERU C
Solar/Wind Harmer
-0.001
219817TRENTONSOL C
Solar/Wind Harmer
0.001
20714428HOW_X1-037
Solar/Wind Harmer
-0.001
20720628TIN_W1-124
Solar/Wind Harmer
-0.001
219918AC2-009 C
Solar/Wind Harmer
0
20742028HF_AC1-207
Solar/Wind Harmer
-0.001
971521AH1-258 GEN
Solar/Wind Harmer
0.245
967451AG2-055 C O1
Solar/Wind Harmer
278.802
219612MATRIX C
Solar/Wind Harmer
0.001
218438BLK ROCK C
Solar/Wind Harmer
-0.001
218526CNTRALGAS2 C
Solar/Wind Harmer
0.001
218524CNTRALGAS1 C
Solar/Wind Harmer
0.001
218428ETC SOLAR C
Solar/Wind Harmer
0
217213AMBOY SO C
Solar/Wind Harmer
-0.001
219249CENTRALDIV C
Solar/Wind Harmer
-0.001
20673828FLE_V3-070
Solar/Wind Harmer
0.084
218449LINSOLAR C
Solar/Wind Harmer
0.001
20675428EAM_W2-061
Solar/Wind Harmer
0
217081WEATEXAS C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
217206BARNGR HS C
Solar/Wind Harmer
-0.001
217208PARK ELE C
Solar/Wind Harmer
0
207439AE1-081 C O1
Solar/Wind Harmer
0.001
20676328BVR_Y1-020
Solar/Wind Harmer
-0.001
20674628WNG_W3-110
Solar/Wind Harmer
-0.001
207511W3-106 GEN
Solar/Wind Harmer
0.051
971009AG2-626 GEN
Solar/Wind Harmer
0.121
971007AG2-625 GEN
Solar/Wind Harmer
0.19
971519AH1-257 GEN
Solar/Wind Harmer
0.186
207437AD2-070 GEN
Solar/Wind Harmer
-0.001
966111AG1-480 GEN
Solar/Wind Harmer
0
966111AG1-480 GEN
Solar/Wind Harmer
3.159
966181AG1-487 GEN
Solar/Wind Harmer
0
966181AG1-487 GEN
Solar/Wind Harmer
3.546
970095AG2-074 GEN
Solar/Wind Harmer
0.287
209029WAYMART-WD
Solar/Wind Harmer
5.709
208972BECR K09
Solar/Wind Harmer
2.074
209027LOR2_Q27
Solar/Wind Harmer
7.678
212266LOR1
Solar/Wind Harmer
0.143
970237AG2-161 GEN
Solar/Wind Harmer
0.169
961541AF2-445A GEN
Solar/Wind Harmer
0.134
209142AF1-226 GEN
Solar/Wind Harmer
0.229
209093AE2-110 GEN
Solar/Wind Harmer
0.131
209120AE2-241 GEN
Solar/Wind Harmer
0.131
209045AE2-271 GEN
Solar/Wind Harmer
0.653
209059AE2-084 GEN
Solar/Wind Harmer
0.123
970665AG2-430 GEN
Solar/Wind Harmer
0.356
209130AF1-271A GEN
Solar/Wind Harmer
0.101
223401AF1-299 GEN
Solar/Wind Helper
0.113
223402AF1-300 C
Solar/Wind Helper
0.113
226910AB2-157 C
Solar/Wind Helper
0.019
227287AC2-120 GEN
Solar/Wind Helper
0.198
226929AD2-058 GEN
Solar/Wind Helper
0.039
3141426STAFORD
Solar/Wind Helper
0.081
3138216PACIFIC
Solar/Wind Helper
0.061
316411AF1-147_GEN1
Solar/Wind Helper
0.293
316415AF1-147_GEN2
Solar/Wind Helper
0.293
3141196NOKESVL
Solar/Wind Helper
1.453
316006AB2-029 C
Solar/Wind Helper
0.114
316045AC1-158 PL2
Solar/Wind Helper
1.342
316447AC1-158 HLD
Solar/Wind Helper
0.922
316044AC1-158 PL1
Solar/Wind Helper
0.42
316450AC1-158 RIC
Solar/Wind Helper
0.112
316164AC1-076 GEN
Solar/Wind Helper
0.36
944491AF1-114 GEN
Solar/Wind Helper
0.574
957971AF2-091 GEN
Solar/Wind Helper
0.195
315651AD1-115 GEN
Solar/Wind Helper
0.861
966881AG1-559 GEN
Solar/Wind Helper
0.115
316254AC1-120 GEN1
Solar/Wind Helper
0.344
316170AC1-121 GEN2
Solar/Wind Helper
0.115
316223AC1-118
Solar/Wind Helper
0.114
3141906WESTMOR
Solar/Wind Helper
0.142
316468AD1-105 GEN
Solar/Wind Helper
0.421
3132273ORANGE
Solar/Wind Helper
0.071
3147666LOUISA
Solar/Wind Helper
1.413
3147666LOUISA
Solar/Wind Helper
0.813
316192AB2-158 GEN
Solar/Wind Helper
0.5
316337AD2-073 GEN
Solar/Wind Helper
0.113
316077AC2-138 C
Solar/Wind Helper
0.079
3141813NORNECK
Solar/Wind Helper
0.352
964211AG1-282 GEN
Solar/Wind Helper
0.113
3141726DUNNSVL
Solar/Wind Helper
1.407
316404AE1-155 C
Solar/Wind Helper
0.716
316473AC1-191 GEN
Solar/Wind Helper
0.451
966871AG1-558 GEN
Solar/Wind Helper
0.113
966001AG1-469 GEN
Solar/Wind Helper
0.079
316484AD2-074 GEN
Solar/Wind Helper
0.485
316487AF1-042 GEN
Solar/Wind Helper
0.254
961951AG1-038 GEN
Solar/Wind Helper
0.254
3141783LANCAST
Solar/Wind Helper
0.21
3141783LANCAST
Solar/Wind Helper
0.14
316312AB1-027
Solar/Wind Helper
0.14
3142416OLDCHRC
Solar/Wind Helper
0.909
3142416OLDCHRC
Solar/Wind Helper
0.348
3138133OCRAN
Solar/Wind Helper
0.21
3138133OCRAN
Solar/Wind Helper
0.105
3141913WHIT STONE
Solar/Wind Helper
0.35
316314AB2-024 C
Solar/Wind Helper
0.112
316059AD1-063 C
Solar/Wind Helper
0.084
3141766HARMONY
Solar/Wind Helper
0.07
957601AF2-054 GEN
Solar/Wind Helper
0.112
316156AD2-030 GEN
Solar/Wind Helper
0.111
3141873WAN 176
Solar/Wind Helper
0.07
316203AE2-005 GEN
Solar/Wind Helper
0.729
315662AE1-191 GEN
Solar/Wind Helper
0.449
316280AD1-041 GEN
Solar/Wind Helper
0.28
315666AE1-190 GEN
Solar/Wind Helper
0.112
316441AF1-014 GEN
Solar/Wind Helper
0.112
3143873LANEXA
Solar/Wind Helper
0.209
316075AC2-137 C
Solar/Wind Helper
0.112
3142433PROV 92
Solar/Wind Helper
1.395
3142946ENON
Solar/Wind Helper
0.116
3142946ENON
Solar/Wind Helper
0.035
316233AE1-074 FULL
Solar/Wind Helper
0.112
3143526WINTERP
Solar/Wind Helper
1.811
3143526WINTERP
Solar/Wind Helper
1.811
3142543TWELFTH
Solar/Wind Helper
0.033
3143226MDLTHAN
Solar/Wind Helper
0.348
957831AF2-077 GEN
Solar/Wind Helper
0.112
316382AG1-145 C
Solar/Wind Helper
0.112
316159AE1-175 C
Solar/Wind Helper
0.112
316240AF1-291 C
Solar/Wind Helper
0.111
316132AB2-190 GEN1
Solar/Wind Helper
0.418
316458AB2-190 GEN2
Solar/Wind Helper
0.418
315697AD1-025 GEN
Solar/Wind Helper
0.835
316033AB2-134 GEN
Solar/Wind Helper
0.792
316369SG1_INVT
Solar/Wind Helper
0.545
315839AE2-212 C
Solar/Wind Helper
0.111
961611AG1-000B GEN
Solar/Wind Helper
0.495
316236AE1-162_GEN
Solar/Wind Helper
0.111
3145336SMITFLD
Solar/Wind Helper
1.381
3145336SMITFLD
Solar/Wind Helper
0.138
3143316POE
Solar/Wind Helper
1.367
316294AC1-161 GEN
Solar/Wind Helper
1.331
315773AC2-141 GEN
Solar/Wind Helper
1.331
238175AF1-290_GEN
Solar/Wind Helper
0.443
316381AD1-082 GEN
Solar/Wind Helper
0.377
316083AB2-161 GEN
Solar/Wind Helper
0.277
3144536CHRHLND
Solar/Wind Helper
0.052
316375AC2-012 GEN
Solar/Wind Helper
0.653
316036AC1-147 C
Solar/Wind Helper
0.111
3144873MCLAUGH
Solar/Wind Helper
0.009
316316AC1-027 C
Solar/Wind Helper
0.097
316185AD1-033 GEN
Solar/Wind Helper
0.387
316072AD1-144
Solar/Wind Helper
0.083
3145506HICKORY
Solar/Wind Helper
1.377
3145506HICKORY
Solar/Wind Helper
0.826
3145506HICKORY
Solar/Wind Helper
0.206
238169AE2-226 GEN1
Solar/Wind Helper
0.274
238170AE2-226 GEN2
Solar/Wind Helper
0.274
316349AD2-085 GEN
Solar/Wind Helper
0.282
316339AD2-160 GEN
Solar/Wind Helper
0.276
316388AE2-253 GEN
Solar/Wind Helper
0.276
315833AF1-017_GEN
Solar/Wind Helper
0.221
316313AB2-026
Solar/Wind Helper
0.111
316258AE1-075 C
Solar/Wind Helper
0.099
316405AF2-144 C
Solar/Wind Helper
0.094
316017AA1-139 ULT1
Solar/Wind Helper
0.332
316018AA1-139 ULT2
Solar/Wind Helper
0.332
3137176SLIGO L2192
Solar/Wind Helper
1.368
3146456SLIGO L269
Solar/Wind Helper
0.344
3146456SLIGO L269
Solar/Wind Helper
0.344
319010AE1-072 C
Solar/Wind Helper
0.828
316305AF2-043 C
Solar/Wind Helper
0.11
316246AF1-032 C
Solar/Wind Helper
0.083
3130086AYDLETT
Solar/Wind Helper
1.375
964441AG1-307 GEN
Solar/Wind Helper
0.441
316320Y1-086
Solar/Wind Helper
0.11
313526AB2-022
Solar/Wind Helper
0.11
3146386ELIZ CT
Solar/Wind Helper
0.343
3146486SUNBURY
Solar/Wind Helper
0.343
3146486SUNBURY
Solar/Wind Helper
0.343
316321Z2-027
Solar/Wind Helper
0.11
3145176PASQUOTANK
Solar/Wind Helper
0.213
316336AC2-165 C
Solar/Wind Helper
0.551
3146516WINFALL
Solar/Wind Helper
1.109
3146516WINFALL
Solar/Wind Helper
0.342
3146516WINFALL
Solar/Wind Helper
0.342
3146516WINFALL
Solar/Wind Helper
0.342
3146516WINFALL
Solar/Wind Helper
0.342
3146516WINFALL
Solar/Wind Helper
0.342
3146626S HERTFORD
Solar/Wind Helper
0.342
3146626S HERTFORD
Solar/Wind Helper
0.342
3146626S HERTFORD
Solar/Wind Helper
0.342
3145273HOLLAND
Solar/Wind Helper
0.256
316315AB2-025 C
Solar/Wind Helper
0.11
315742AE1-103 GEN
Solar/Wind Helper
0.219
3146376EDENTON
Solar/Wind Helper
0.341
3130156CHOWAN
Solar/Wind Helper
0.341
3130156CHOWAN
Solar/Wind Helper
0.341
3130156CHOWAN
Solar/Wind Helper
0.341
315614AA2-178 GEN
Solar/Wind Helper
0.436
315816AE2-034 GEN
Solar/Wind Helper
0.327
3145663CRESWEL
Solar/Wind Helper
0.951
23546401DTGZ2-030
Solar/Wind Helper
0.054
238152AF2-075_GEN
Solar/Wind Helper
0.272
238147AE2-230_GEN1
Solar/Wind Helper
0.381
238148AE2-230_GEN2
Solar/Wind Helper
0.381
238149AF1-291A_GEN
Solar/Wind Helper
0.054
3130546PLYMOUTH
Solar/Wind Helper
0.339
3156081AA2-088 GEN
Solar/Wind Helper
0.544
315732AD1-074 GEN1
Solar/Wind Helper
0.816
315733AD1-074 GEN2
Solar/Wind Helper
0.816
315737AD1-076 GEN
Solar/Wind Helper
0.593
315735AD1-075 GEN1
Solar/Wind Helper
0.408
316065AD1-022 GEN
Solar/Wind Helper
0.435
237061AD1-155 GEN
Solar/Wind Helper
0.407
316023GEN1_S
Solar/Wind Helper
0.271
316365GEN2_N
Solar/Wind Helper
0.271
3146206CASHIE
Solar/Wind Helper
0.338
3146206CASHIE
Solar/Wind Helper
0.338
3146206CASHIE
Solar/Wind Helper
0.338
3145893MURPHYS
Solar/Wind Helper
1.352
3145893MURPHYS
Solar/Wind Helper
1.081
3145893MURPHYS
Solar/Wind Helper
0.912
316318V4-068
Solar/Wind Helper
0.025
3145893MURPHYS
Solar/Wind Helper
0.608
3145893MURPHYS
Solar/Wind Helper
0.338
3145893MURPHYS
Solar/Wind Helper
0.338
3145893MURPHYS
Solar/Wind Helper
0.27
3146173TUNIS
Solar/Wind Helper
0.337
3146173TUNIS
Solar/Wind Helper
0.337
3146173TUNIS
Solar/Wind Helper
0.337
3146173TUNIS
Solar/Wind Helper
0.337
316322AB2-045
Solar/Wind Helper
0.107
3146776BUCKING
Solar/Wind Helper
1.349
3146776BUCKING
Solar/Wind Helper
0.135
3146776BUCKING
Solar/Wind Helper
0.121
3146776BUCKING
Solar/Wind Helper
0.109
3156021HOLLOMANSOL
Solar/Wind Helper
0.541
316463AE2-346 GEN
Solar/Wind Helper
0.065
316140AB2-099
Solar/Wind Helper
0.027
961941AG1-037 GEN
Solar/Wind Helper
0.027
3145513AHOSKIE
Solar/Wind Helper
0.337
3145513AHOSKIE
Solar/Wind Helper
0.337
946281AF1-292 GEN
Solar/Wind Helper
0.081
966621AG1-532 GEN
Solar/Wind Helper
0.073
3146043SEABORD
Solar/Wind Helper
0.337
3146926FARMVIL
Solar/Wind Helper
0.202
3146926FARMVIL
Solar/Wind Helper
0.202
3145683EARLEYS
Solar/Wind Helper
0.674
3145683EARLEYS
Solar/Wind Helper
0.337
3145683EARLEYS
Solar/Wind Helper
0.337
3145683EARLEYS
Solar/Wind Helper
0.337
315607AA1-063A GEN
Solar/Wind Helper
0.406
316087AB2-174 GEN
Solar/Wind Helper
0.432
3146263WOODLND
Solar/Wind Helper
0.336
3146263WOODLND
Solar/Wind Helper
0.336
316181AB2-040 GEN
Solar/Wind Helper
0.432
313506AB2-031 GEN
Solar/Wind Helper
0.322
3138266HYDRAULIC
Solar/Wind Helper
0.015
3138266HYDRAULIC
Solar/Wind Helper
0.009
942461AE2-259 GEN
Solar/Wind Helper
0.54
3142666NORTHAMPTON
Solar/Wind Helper
0.336
3142666NORTHAMPTON
Solar/Wind Helper
0.336
3142666NORTHAMPTON
Solar/Wind Helper
0.336
3142666NORTHAMPTON
Solar/Wind Helper
0.336
3142666NORTHAMPTON
Solar/Wind Helper
0.202
3137643SOCKMAN
Solar/Wind Helper
1.342
3145963POPLR C
Solar/Wind Helper
0.336
3145963POPLR C
Solar/Wind Helper
0.336
316426AA2-053 GEN
Solar/Wind Helper
0.405
316190AA2-174 GEN
Solar/Wind Helper
0.027
316011AB1-132 GEN
Solar/Wind Helper
8.059
316317KELFORD C
Solar/Wind Helper
0.125
3145823KELFORD
Solar/Wind Helper
0.336
3145823KELFORD
Solar/Wind Helper
0.336
3147043LAWRENC
Solar/Wind Helper
0.201
3145593CAROLNA
Solar/Wind Helper
0.336
3145593CAROLNA
Solar/Wind Helper
0.336
316174AB2-169 GEN
Solar/Wind Helper
0.399
3145783HORNRTN
Solar/Wind Helper
0.335
3147133PAMPLIN
Solar/Wind Helper
1.053
3147133PAMPLIN
Solar/Wind Helper
0.335
3147133PAMPLIN
Solar/Wind Helper
0.268
316478AD1-087 GEN
Solar/Wind Helper
0.346
316486AD2-202 GEN
Solar/Wind Helper
0.101
3145796HORNRTN
Solar/Wind Helper
1.34
3145796HORNRTN
Solar/Wind Helper
1.105
3145796HORNRTN
Solar/Wind Helper
1.072
3145796HORNRTN
Solar/Wind Helper
1.005
3145796HORNRTN
Solar/Wind Helper
0.335
3145796HORNRTN
Solar/Wind Helper
0.335
3145796HORNRTN
Solar/Wind Helper
0.134
3146033SCOT NK
Solar/Wind Helper
1.339
315821AE2-092 GEN
Solar/Wind Helper
0.741
316034AC1-036 C
Solar/Wind Helper
0.074
3144303KENBRDG
Solar/Wind Helper
0.267
315785AD2-033 C
Solar/Wind Helper
0.698
23777901MDS_W4-102
Solar/Wind Helper
0.107
316210AC1-098 GEN
Solar/Wind Helper
0.483
316212AC1-099_GEN
Solar/Wind Helper
0.268
237034AC2-136 C
Solar/Wind Helper
0.063
316129AC1-054 GEN
Solar/Wind Helper
0.348
3145933PARMELE
Solar/Wind Helper
0.667
3145933PARMELE
Solar/Wind Helper
0.334
3145933PARMELE
Solar/Wind Helper
0.334
316274AC1-208 GEN
Solar/Wind Helper
0.429
23779801AA1-109
Solar/Wind Helper
0.048
316131AB2-060 GEN
Solar/Wind Helper
0.428
313527AB2-043 GEN
Solar/Wind Helper
0.268
316239AB2-077_GEN
Solar/Wind Helper
0.107
316238AB2-078_GEN
Solar/Wind Helper
0.107
316237AB2-079_GEN
Solar/Wind Helper
0.107
3132123MT JACKSON
Solar/Wind Helper
1.041
316005AA1-067
Solar/Wind Helper
0.08
3145746EVERETS
Solar/Wind Helper
1.324
3145746EVERETS
Solar/Wind Helper
0.333
3145746EVERETS
Solar/Wind Helper
0.333
3145746EVERETS
Solar/Wind Helper
0.333
3145746EVERETS
Solar/Wind Helper
0.333
3145746EVERETS
Solar/Wind Helper
0.333
3145746EVERETS
Solar/Wind Helper
0.333
3145746EVERETS
Solar/Wind Helper
0.333
235020AA1-095 C
Solar/Wind Helper
0.022
315722AD1-056 GEN
Solar/Wind Helper
0.32
315724AD1-057 GEN
Solar/Wind Helper
0.176
315687AD1-152 GEN
Solar/Wind Helper
0.427
316327AA2-057 GEN
Solar/Wind Helper
0.4
316494AC1-189 GEN
Solar/Wind Helper
0.426
3147983MERCK5
Solar/Wind Helper
0.133
316420AA1-050 GEN
Solar/Wind Helper
0.426
3148013FISHERV
Solar/Wind Helper
0.331
3148133STUARTS
Solar/Wind Helper
0.199
3148013FISHERV
Solar/Wind Helper
0.19
23777801MSM_W1-116
Solar/Wind Helper
0.075
316319Z2-044 C
Solar/Wind Helper
0.064
3146233WITAKRS
Solar/Wind Helper
1.318
3146233WITAKRS
Solar/Wind Helper
0.225
961671AG1-007 GEN
Solar/Wind Helper
0.05
3145573BETHELC
Solar/Wind Helper
0.331
3145573BETHELC
Solar/Wind Helper
0.331
3146073TAR RVR
Solar/Wind Helper
0.331
3146083TARBORO
Solar/Wind Helper
0.331
3146083TARBORO
Solar/Wind Helper
0.331
316499AE2-029_GEN
Solar/Wind Helper
0.266
3138543CONSLDL
Solar/Wind Helper
0.218
3146843MT LREL
Solar/Wind Helper
0.33
3146843MT LREL
Solar/Wind Helper
0.33
316359AB2-059 GEN
Solar/Wind Helper
0.531
316049AB1-081 GEN
Solar/Wind Helper
0.424
3145543BTLEBRO
Solar/Wind Helper
0.33
3145543BTLEBRO
Solar/Wind Helper
0.33
3145543BTLEBRO
Solar/Wind Helper
0.33
3145543BTLEBRO
Solar/Wind Helper
0.264
270494AE1-108_GEN
Solar/Wind Helper
0.793
316118AC1-105 GEN
Solar/Wind Helper
0.27
316248AF1-058 C
Solar/Wind Helper
0.106
3147173SINAI
Solar/Wind Helper
0.328
3147243WELCO
Solar/Wind Helper
0.205
316003AC1-222 GEN
Solar/Wind Helper
0.34
237030AB1-096 C
Solar/Wind Helper
0.052
237025AB1-124 C
Solar/Wind Helper
0.105
237006AB1-125 GEN
Solar/Wind Helper
0.079
3148463FAIRFLD
Solar/Wind Helper
0.326
238221AF1-254 C O1
Solar/Wind Helper
0.105
316097T157 G90
Solar/Wind Helper
0.213
316095T157 G97
Solar/Wind Helper
0.213
316222AC1-221 GEN
Solar/Wind Helper
0.39
316283AC2-100 C
Solar/Wind Helper
0.364
23583801GRNGAP
Solar/Wind Helper
0.538
316123AC1-075 GEN
Solar/Wind Helper
0.414
237080AD1-060 GEN
Solar/Wind Helper
0.077
238208AF1-136 C
Solar/Wind Helper
0.081
270455AD2-022 GEN
Solar/Wind Helper
0.492
270457AD2-023 GEN
Solar/Wind Helper
0.277
3147123OTTER R
Solar/Wind Helper
0.189
237038AE2-054 C
Solar/Wind Helper
0.101
235067AD1-061 GEN
Solar/Wind Helper
0.101
270016AE1-250 BESS
Solar/Wind Helper
0.378
270013AE1-250 PV
Solar/Wind Helper
0.378
238108AE1-109 GEN1
Solar/Wind Helper
0.033
238109AE1-109 GEN2
Solar/Wind Helper
0.033
238110AE1-109 GEN3
Solar/Wind Helper
0.033
316217AC1-145 GEN
Solar/Wind Helper
0.252
316197AC1-042 GEN
Solar/Wind Helper
0.212
3147312GRETNA
Solar/Wind Helper
0.251
3146802CHATHAM
Solar/Wind Helper
0.235
3147312GRETNA
Solar/Wind Helper
0.063
270197AD1-017 GEN1
Solar/Wind Helper
0.302
270574AD1-017 GEN2
Solar/Wind Helper
0.302
237002AB1-128_GEN
Solar/Wind Helper
0.1
208923BUSO V4-027
Solar/Wind Helper
0.025
G-007ALTFEXP_G-007A->PJM
CMTX
58.409
HAMLETPJM->LTFIMP_HAMLET
CLTF
5.859
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.486
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
23.802
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
5.084
BlueGrassPJM->LTFIMP_BlueG
CLTF
15.834
CBM NorthLTFEXP_CBM-N->PJM
CBM
71.16
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
147.111

Details for PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line l/o PECO_P1-2_5007_SRT-A/* $ CHESCO $ PECO_P1-2_5007 $ L


Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
Contingency Name:
PECO_P1-2_5007_SRT-A/* $ CHESCO $ PECO_P1-2_5007 $ L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:167.58 %
Rating:3700.0 MVA
Rating Type:B
MVA to Mitigate:6200.51
MW Contribution:0.64
Bus #Bus NameTypeMW Contribution
200202DELTA2 ST
50/50
12.039
200200DELTA2 CT1
50/50
6.739
200201DELTA2 CT2
50/50
6.739
200195DELTA ST
50/50
5.956
200192DELTA CT1
50/50
3.573
200193DELTA CT2
50/50
3.573
200194DELTA CT3
50/50
3.573
200034PCHBTM 2
50/50
235.894
200035PCHBTM 3
50/50
38.918
200203Y1-065-STG
50/50
13.284
200204Y1-065-CTG1
50/50
8.365
200205Y1-065-CTG2
50/50
8.365
200052ROCKSP 1
50/50
99.245
200053ROCKSP 2
50/50
99.245
200054ROCKSP 3
50/50
98.237
200055ROCKSP 4
50/50
98.237
233987AB2-037 GEN
Solar/Wind Harmer
0
971149AH1-027 GEN
Solar/Wind Harmer
0.477
233972AC1-094 C
Solar/Wind Harmer
-0.002
970695AG2-447 GEN
Solar/Wind Harmer
0.381
234033AF1-007_GEN
Solar/Wind Harmer
39.876
970545AG2-347 GEN
Solar/Wind Harmer
164.261
972133AH1-634 GEN
Solar/Wind Harmer
24.888
972069AH1-584 GEN
Solar/Wind Harmer
0.953
972071AH1-585 GEN
Solar/Wind Harmer
0.953
972073AH1-586 GEN
Solar/Wind Harmer
17.153
233923SMA
Solar/Wind Harmer
-0.002
233998TM1NIN_3.36
Solar/Wind Harmer
-0.002
233997TMININ_4.2
Solar/Wind Harmer
-0.002
233996TM1833_GEN
Solar/Wind Harmer
-0.002
971747AH1-380 GEN
Solar/Wind Harmer
0.381
233940AF2-379 C
Solar/Wind Harmer
-0.002
233990AG1-397 GEN
Solar/Wind Harmer
-0.001
233990AG1-397 GEN
Solar/Wind Harmer
3.049
234015AF2-250 C
Solar/Wind Harmer
-0.001
971195AH1-057 GEN
Solar/Wind Harmer
0.137
972177AH1-672 GEN
Solar/Wind Harmer
1.429
960671AF2-358 GEN
Solar/Wind Harmer
1.904
965821AG1-450 GEN
Solar/Wind Harmer
9.519
232426Y1-080 FULL
Solar/Wind Harmer
0
970277AG2-181 GEN
Solar/Wind Harmer
0.533
233946AB2-136 GEN
Solar/Wind Harmer
-0.002
233964AF2-378 GEN
Solar/Wind Harmer
0.001
234041AC1-190 GEN
Solar/Wind Harmer
0.951
233984AB2-036 GEN
Solar/Wind Harmer
1.735
233968AD2-076_GEN
Solar/Wind Harmer
0.919
234014AF1-036_GEN
Solar/Wind Harmer
0.375
970597AG2-380 GEN
Solar/Wind Harmer
7.505
234012AE2-112_GEN
Solar/Wind Harmer
0.319
971983AH1-536 GEN
Solar/Wind Harmer
0.78
970453AG2-297 GEN
Solar/Wind Harmer
0.31
971553AH1-274 GEN
Solar/Wind Harmer
0.27
945431AF1-208 GEN
Solar/Wind Harmer
0.723
970997AG2-616 GEN
Solar/Wind Harmer
0.801
972141AH1-641 GEN
Solar/Wind Harmer
0.24
230430AE1-229_GEN
Solar/Wind Harmer
-0.002
228351V2-046C
Solar/Wind Harmer
-0.002
230422AE1-104_GEN1
Solar/Wind Harmer
66.257
230425AE1-104_GEN2
Solar/Wind Harmer
66.257
230433AD2-135 GEN
Solar/Wind Harmer
0
971011AG2-627 GEN
Solar/Wind Harmer
0.636
971535AH1-265 GEN
Solar/Wind Harmer
0.467
230407AD2-065 C
Solar/Wind Harmer
0
228754AB1-001 C
Solar/Wind Harmer
-0.002
219137THOSOLAR C
Solar/Wind Harmer
0.001
219623KINSLEYBEA C
Solar/Wind Harmer
-0.001
219258KINSLEYDEP C
Solar/Wind Harmer
-0.001
219766PARADISE C
Solar/Wind Harmer
-0.002
218660EHAMPSOLAR C
Solar/Wind Harmer
-0.002
219907AC1-030 C
Solar/Wind Harmer
-0.001
219236SOUTHERNHQ C
Solar/Wind Harmer
-0.001
219906AC1-017 C
Solar/Wind Harmer
-0.001
219615MILLCREEK C
Solar/Wind Harmer
-0.001
214067T20SOLAR
Solar/Wind Harmer
-0.001
207522AF2-254 C
Solar/Wind Harmer
0.141
207500AE2-000G1
Solar/Wind Harmer
55.007
207497AE2-000G2
Solar/Wind Harmer
55.007
207507AE2-000G3
Solar/Wind Harmer
55.007
207487AE2-000G4
Solar/Wind Harmer
55.007
970025AG2-016 GEN
Solar/Wind Harmer
0.276
971189AH1-054 GEN
Solar/Wind Harmer
0.115
971667AH1-334 GEN
Solar/Wind Harmer
0.265
219727YARDVSOLFA C
Solar/Wind Harmer
0.001
219276PARKLANDSO C
Solar/Wind Harmer
0.001
219620RIDERU C
Solar/Wind Harmer
-0.001
219817TRENTONSOL C
Solar/Wind Harmer
0.001
20714328BYD_X4-031
Solar/Wind Harmer
0.026
20714428HOW_X1-037
Solar/Wind Harmer
-0.001
20720628TIN_W1-124
Solar/Wind Harmer
-0.001
219918AC2-009 C
Solar/Wind Harmer
0
20742028HF_AC1-207
Solar/Wind Harmer
-0.001
971521AH1-258 GEN
Solar/Wind Harmer
0.249
967451AG2-055 C O1
Solar/Wind Harmer
283.611
219612MATRIX C
Solar/Wind Harmer
0.001
218438BLK ROCK C
Solar/Wind Harmer
-0.001
218526CNTRALGAS2 C
Solar/Wind Harmer
0.001
218524CNTRALGAS1 C
Solar/Wind Harmer
0.001
218428ETC SOLAR C
Solar/Wind Harmer
0
217213AMBOY SO C
Solar/Wind Harmer
-0.001
219249CENTRALDIV C
Solar/Wind Harmer
-0.001
20673828FLE_V3-070
Solar/Wind Harmer
0.086
218449LINSOLAR C
Solar/Wind Harmer
0.001
20675428EAM_W2-061
Solar/Wind Harmer
0
217081WEATEXAS C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
217206BARNGR HS C
Solar/Wind Harmer
-0.001
217208PARK ELE C
Solar/Wind Harmer
0
207439AE1-081 C O1
Solar/Wind Harmer
0.001
20676328BVR_Y1-020
Solar/Wind Harmer
-0.001
20674628WNG_W3-110
Solar/Wind Harmer
-0.001
207511W3-106 GEN
Solar/Wind Harmer
0.052
971009AG2-626 GEN
Solar/Wind Harmer
0.124
971007AG2-625 GEN
Solar/Wind Harmer
0.194
971519AH1-257 GEN
Solar/Wind Harmer
0.19
207437AD2-070 GEN
Solar/Wind Harmer
-0.001
966111AG1-480 GEN
Solar/Wind Harmer
0
966111AG1-480 GEN
Solar/Wind Harmer
3.212
966181AG1-487 GEN
Solar/Wind Harmer
0
966181AG1-487 GEN
Solar/Wind Harmer
3.61
970095AG2-074 GEN
Solar/Wind Harmer
0.291
209029WAYMART-WD
Solar/Wind Harmer
5.79
208972BECR K09
Solar/Wind Harmer
2.103
209027LOR2_Q27
Solar/Wind Harmer
7.78
212266LOR1
Solar/Wind Harmer
0.145
970237AG2-161 GEN
Solar/Wind Harmer
0.171
961541AF2-445A GEN
Solar/Wind Harmer
0.136
209142AF1-226 GEN
Solar/Wind Harmer
0.232
209093AE2-110 GEN
Solar/Wind Harmer
0.132
209120AE2-241 GEN
Solar/Wind Harmer
0.132
209045AE2-271 GEN
Solar/Wind Harmer
0.661
209059AE2-084 GEN
Solar/Wind Harmer
0.124
970665AG2-430 GEN
Solar/Wind Harmer
0.361
209130AF1-271A GEN
Solar/Wind Harmer
0.102
223401AF1-299 GEN
Solar/Wind Helper
0.116
223402AF1-300 C
Solar/Wind Helper
0.116
226910AB2-157 C
Solar/Wind Helper
0.019
227287AC2-120 GEN
Solar/Wind Helper
0.205
226929AD2-058 GEN
Solar/Wind Helper
0.041
3141426STAFORD
Solar/Wind Helper
0.084
3138216PACIFIC
Solar/Wind Helper
0.063
316411AF1-147_GEN1
Solar/Wind Helper
0.305
316415AF1-147_GEN2
Solar/Wind Helper
0.305
3141196NOKESVL
Solar/Wind Helper
1.509
316006AB2-029 C
Solar/Wind Helper
0.119
316045AC1-158 PL2
Solar/Wind Helper
1.394
316447AC1-158 HLD
Solar/Wind Helper
0.958
316044AC1-158 PL1
Solar/Wind Helper
0.436
316450AC1-158 RIC
Solar/Wind Helper
0.116
316164AC1-076 GEN
Solar/Wind Helper
0.374
944491AF1-114 GEN
Solar/Wind Helper
0.596
957971AF2-091 GEN
Solar/Wind Helper
0.203
315651AD1-115 GEN
Solar/Wind Helper
0.894
316254AC1-120 GEN1
Solar/Wind Helper
0.357
316170AC1-121 GEN2
Solar/Wind Helper
0.119
966881AG1-559 GEN
Solar/Wind Helper
0.119
316223AC1-118
Solar/Wind Helper
0.118
3141906WESTMOR
Solar/Wind Helper
0.147
316468AD1-105 GEN
Solar/Wind Helper
0.438
3132273ORANGE
Solar/Wind Helper
0.073
3147666LOUISA
Solar/Wind Helper
1.469
3147666LOUISA
Solar/Wind Helper
0.844
316192AB2-158 GEN
Solar/Wind Helper
0.52
316337AD2-073 GEN
Solar/Wind Helper
0.118
316077AC2-138 C
Solar/Wind Helper
0.082
3141813NORNECK
Solar/Wind Helper
0.366
964211AG1-282 GEN
Solar/Wind Helper
0.117
3141726DUNNSVL
Solar/Wind Helper
1.462
316404AE1-155 C
Solar/Wind Helper
0.744
316473AC1-191 GEN
Solar/Wind Helper
0.469
966871AG1-558 GEN
Solar/Wind Helper
0.117
966001AG1-469 GEN
Solar/Wind Helper
0.082
316484AD2-074 GEN
Solar/Wind Helper
0.504
316487AF1-042 GEN
Solar/Wind Helper
0.263
961951AG1-038 GEN
Solar/Wind Helper
0.263
3141783LANCAST
Solar/Wind Helper
0.218
3141783LANCAST
Solar/Wind Helper
0.145
316312AB1-027
Solar/Wind Helper
0.146
3142416OLDCHRC
Solar/Wind Helper
0.945
3142416OLDCHRC
Solar/Wind Helper
0.362
3138133OCRAN
Solar/Wind Helper
0.218
3138133OCRAN
Solar/Wind Helper
0.109
3141913WHIT STONE
Solar/Wind Helper
0.363
316314AB2-024 C
Solar/Wind Helper
0.117
316059AD1-063 C
Solar/Wind Helper
0.087
3141766HARMONY
Solar/Wind Helper
0.073
315662AE1-191 GEN
Solar/Wind Helper
0.466
316280AD1-041 GEN
Solar/Wind Helper
0.292
315666AE1-190 GEN
Solar/Wind Helper
0.117
957601AF2-054 GEN
Solar/Wind Helper
0.116
316156AD2-030 GEN
Solar/Wind Helper
0.115
3141873WAN 176
Solar/Wind Helper
0.073
316203AE2-005 GEN
Solar/Wind Helper
0.758
316441AF1-014 GEN
Solar/Wind Helper
0.116
3143873LANEXA
Solar/Wind Helper
0.218
316075AC2-137 C
Solar/Wind Helper
0.117
3142433PROV 92
Solar/Wind Helper
1.45
3142946ENON
Solar/Wind Helper
0.121
3142946ENON
Solar/Wind Helper
0.036
316233AE1-074 FULL
Solar/Wind Helper
0.116
3143526WINTERP
Solar/Wind Helper
1.883
3143526WINTERP
Solar/Wind Helper
1.883
3142543TWELFTH
Solar/Wind Helper
0.035
3143226MDLTHAN
Solar/Wind Helper
0.362
957831AF2-077 GEN
Solar/Wind Helper
0.116
316382AG1-145 C
Solar/Wind Helper
0.116
316159AE1-175 C
Solar/Wind Helper
0.116
316240AF1-291 C
Solar/Wind Helper
0.116
316132AB2-190 GEN1
Solar/Wind Helper
0.434
316458AB2-190 GEN2
Solar/Wind Helper
0.434
315697AD1-025 GEN
Solar/Wind Helper
0.868
316033AB2-134 GEN
Solar/Wind Helper
0.824
316369SG1_INVT
Solar/Wind Helper
0.567
315839AE2-212 C
Solar/Wind Helper
0.116
961611AG1-000B GEN
Solar/Wind Helper
0.514
316236AE1-162_GEN
Solar/Wind Helper
0.115
3145336SMITFLD
Solar/Wind Helper
1.436
3145336SMITFLD
Solar/Wind Helper
0.144
3143316POE
Solar/Wind Helper
1.421
316294AC1-161 GEN
Solar/Wind Helper
1.383
315773AC2-141 GEN
Solar/Wind Helper
1.383
238175AF1-290_GEN
Solar/Wind Helper
0.461
316381AD1-082 GEN
Solar/Wind Helper
0.392
316083AB2-161 GEN
Solar/Wind Helper
0.288
3144536CHRHLND
Solar/Wind Helper
0.054
316375AC2-012 GEN
Solar/Wind Helper
0.679
316036AC1-147 C
Solar/Wind Helper
0.115
3144873MCLAUGH
Solar/Wind Helper
0.009
316316AC1-027 C
Solar/Wind Helper
0.101
316185AD1-033 GEN
Solar/Wind Helper
0.403
316072AD1-144
Solar/Wind Helper
0.086
3145506HICKORY
Solar/Wind Helper
1.431
3145506HICKORY
Solar/Wind Helper
0.859
3145506HICKORY
Solar/Wind Helper
0.215
238169AE2-226 GEN1
Solar/Wind Helper
0.285
238170AE2-226 GEN2
Solar/Wind Helper
0.285
316349AD2-085 GEN
Solar/Wind Helper
0.293
316339AD2-160 GEN
Solar/Wind Helper
0.287
316388AE2-253 GEN
Solar/Wind Helper
0.287
315833AF1-017_GEN
Solar/Wind Helper
0.23
316313AB2-026
Solar/Wind Helper
0.115
316258AE1-075 C
Solar/Wind Helper
0.103
316405AF2-144 C
Solar/Wind Helper
0.098
316017AA1-139 ULT1
Solar/Wind Helper
0.345
316018AA1-139 ULT2
Solar/Wind Helper
0.345
3137176SLIGO L2192
Solar/Wind Helper
1.422
3146456SLIGO L269
Solar/Wind Helper
0.357
3146456SLIGO L269
Solar/Wind Helper
0.357
319010AE1-072 C
Solar/Wind Helper
0.861
316305AF2-043 C
Solar/Wind Helper
0.115
316246AF1-032 C
Solar/Wind Helper
0.086
3130086AYDLETT
Solar/Wind Helper
1.429
964441AG1-307 GEN
Solar/Wind Helper
0.459
316320Y1-086
Solar/Wind Helper
0.115
313526AB2-022
Solar/Wind Helper
0.115
3146386ELIZ CT
Solar/Wind Helper
0.357
3146486SUNBURY
Solar/Wind Helper
0.357
3146486SUNBURY
Solar/Wind Helper
0.357
316321Z2-027
Solar/Wind Helper
0.115
3145176PASQUOTANK
Solar/Wind Helper
0.221
316336AC2-165 C
Solar/Wind Helper
0.573
3146516WINFALL
Solar/Wind Helper
1.153
3146516WINFALL
Solar/Wind Helper
0.356
3146516WINFALL
Solar/Wind Helper
0.356
3146516WINFALL
Solar/Wind Helper
0.356
3146516WINFALL
Solar/Wind Helper
0.356
3146516WINFALL
Solar/Wind Helper
0.356
3146626S HERTFORD
Solar/Wind Helper
0.356
3146626S HERTFORD
Solar/Wind Helper
0.356
3146626S HERTFORD
Solar/Wind Helper
0.356
3145273HOLLAND
Solar/Wind Helper
0.267
316315AB2-025 C
Solar/Wind Helper
0.114
315742AE1-103 GEN
Solar/Wind Helper
0.228
3130156CHOWAN
Solar/Wind Helper
0.354
3130156CHOWAN
Solar/Wind Helper
0.354
3130156CHOWAN
Solar/Wind Helper
0.354
3146376EDENTON
Solar/Wind Helper
0.354
315614AA2-178 GEN
Solar/Wind Helper
0.454
315816AE2-034 GEN
Solar/Wind Helper
0.34
3145663CRESWEL
Solar/Wind Helper
0.989
23546401DTGZ2-030
Solar/Wind Helper
0.057
238152AF2-075_GEN
Solar/Wind Helper
0.283
238147AE2-230_GEN1
Solar/Wind Helper
0.396
238148AE2-230_GEN2
Solar/Wind Helper
0.396
238149AF1-291A_GEN
Solar/Wind Helper
0.057
3130546PLYMOUTH
Solar/Wind Helper
0.352
3156081AA2-088 GEN
Solar/Wind Helper
0.566
315732AD1-074 GEN1
Solar/Wind Helper
0.848
315733AD1-074 GEN2
Solar/Wind Helper
0.848
315737AD1-076 GEN
Solar/Wind Helper
0.616
315735AD1-075 GEN1
Solar/Wind Helper
0.424
316065AD1-022 GEN
Solar/Wind Helper
0.452
237061AD1-155 GEN
Solar/Wind Helper
0.424
316023GEN1_S
Solar/Wind Helper
0.282
316365GEN2_N
Solar/Wind Helper
0.282
3146206CASHIE
Solar/Wind Helper
0.351
3146206CASHIE
Solar/Wind Helper
0.351
3146206CASHIE
Solar/Wind Helper
0.351
3145893MURPHYS
Solar/Wind Helper
1.405
3145893MURPHYS
Solar/Wind Helper
1.124
3145893MURPHYS
Solar/Wind Helper
0.949
316318V4-068
Solar/Wind Helper
0.026
3145893MURPHYS
Solar/Wind Helper
0.632
3145893MURPHYS
Solar/Wind Helper
0.351
3145893MURPHYS
Solar/Wind Helper
0.351
3145893MURPHYS
Solar/Wind Helper
0.281
3146173TUNIS
Solar/Wind Helper
0.351
3146173TUNIS
Solar/Wind Helper
0.351
3146173TUNIS
Solar/Wind Helper
0.351
3146173TUNIS
Solar/Wind Helper
0.351
316322AB2-045
Solar/Wind Helper
0.112
3146776BUCKING
Solar/Wind Helper
1.403
3146776BUCKING
Solar/Wind Helper
0.14
3146776BUCKING
Solar/Wind Helper
0.126
3146776BUCKING
Solar/Wind Helper
0.114
3156021HOLLOMANSOL
Solar/Wind Helper
0.563
316463AE2-346 GEN
Solar/Wind Helper
0.068
316140AB2-099
Solar/Wind Helper
0.028
961941AG1-037 GEN
Solar/Wind Helper
0.028
3145513AHOSKIE
Solar/Wind Helper
0.35
3145513AHOSKIE
Solar/Wind Helper
0.35
946281AF1-292 GEN
Solar/Wind Helper
0.084
966621AG1-532 GEN
Solar/Wind Helper
0.076
3146043SEABORD
Solar/Wind Helper
0.35
3146926FARMVIL
Solar/Wind Helper
0.21
3146926FARMVIL
Solar/Wind Helper
0.21
3145683EARLEYS
Solar/Wind Helper
0.7
3145683EARLEYS
Solar/Wind Helper
0.35
3145683EARLEYS
Solar/Wind Helper
0.35
3145683EARLEYS
Solar/Wind Helper
0.35
315607AA1-063A GEN
Solar/Wind Helper
0.422
316087AB2-174 GEN
Solar/Wind Helper
0.45
3146263WOODLND
Solar/Wind Helper
0.35
3146263WOODLND
Solar/Wind Helper
0.35
316181AB2-040 GEN
Solar/Wind Helper
0.449
313506AB2-031 GEN
Solar/Wind Helper
0.335
3138266HYDRAULIC
Solar/Wind Helper
0.016
3138266HYDRAULIC
Solar/Wind Helper
0.01
942461AE2-259 GEN
Solar/Wind Helper
0.561
3142666NORTHAMPTON
Solar/Wind Helper
0.349
3142666NORTHAMPTON
Solar/Wind Helper
0.349
3142666NORTHAMPTON
Solar/Wind Helper
0.349
3142666NORTHAMPTON
Solar/Wind Helper
0.349
3142666NORTHAMPTON
Solar/Wind Helper
0.21
3137643SOCKMAN
Solar/Wind Helper
1.396
3145963POPLR C
Solar/Wind Helper
0.349
3145963POPLR C
Solar/Wind Helper
0.349
316426AA2-053 GEN
Solar/Wind Helper
0.421
316011AB1-132 GEN
Solar/Wind Helper
8.381
316190AA2-174 GEN
Solar/Wind Helper
0.028
316317KELFORD C
Solar/Wind Helper
0.13
3145823KELFORD
Solar/Wind Helper
0.349
3145823KELFORD
Solar/Wind Helper
0.349
3147043LAWRENC
Solar/Wind Helper
0.209
3145593CAROLNA
Solar/Wind Helper
0.349
3145593CAROLNA
Solar/Wind Helper
0.349
316174AB2-169 GEN
Solar/Wind Helper
0.415
3145783HORNRTN
Solar/Wind Helper
0.349
3147133PAMPLIN
Solar/Wind Helper
1.095
3147133PAMPLIN
Solar/Wind Helper
0.349
3147133PAMPLIN
Solar/Wind Helper
0.279
316478AD1-087 GEN
Solar/Wind Helper
0.359
316486AD2-202 GEN
Solar/Wind Helper
0.105
3145796HORNRTN
Solar/Wind Helper
1.394
3145796HORNRTN
Solar/Wind Helper
1.15
3145796HORNRTN
Solar/Wind Helper
1.115
3145796HORNRTN
Solar/Wind Helper
1.045
3145796HORNRTN
Solar/Wind Helper
0.348
3145796HORNRTN
Solar/Wind Helper
0.348
3145796HORNRTN
Solar/Wind Helper
0.139
3146033SCOT NK
Solar/Wind Helper
1.392
315821AE2-092 GEN
Solar/Wind Helper
0.771
316034AC1-036 C
Solar/Wind Helper
0.077
3144303KENBRDG
Solar/Wind Helper
0.278
315785AD2-033 C
Solar/Wind Helper
0.725
23777901MDS_W4-102
Solar/Wind Helper
0.112
316210AC1-098 GEN
Solar/Wind Helper
0.502
316212AC1-099_GEN
Solar/Wind Helper
0.279
316129AC1-054 GEN
Solar/Wind Helper
0.362
237034AC2-136 C
Solar/Wind Helper
0.066
3145933PARMELE
Solar/Wind Helper
0.694
3145933PARMELE
Solar/Wind Helper
0.347
3145933PARMELE
Solar/Wind Helper
0.347
316274AC1-208 GEN
Solar/Wind Helper
0.446
316131AB2-060 GEN
Solar/Wind Helper
0.445
23779801AA1-109
Solar/Wind Helper
0.05
313527AB2-043 GEN
Solar/Wind Helper
0.278
316239AB2-077_GEN
Solar/Wind Helper
0.111
316238AB2-078_GEN
Solar/Wind Helper
0.111
316237AB2-079_GEN
Solar/Wind Helper
0.111
3132123MT JACKSON
Solar/Wind Helper
1.083
316005AA1-067
Solar/Wind Helper
0.083
3145746EVERETS
Solar/Wind Helper
1.377
3145746EVERETS
Solar/Wind Helper
0.346
3145746EVERETS
Solar/Wind Helper
0.346
3145746EVERETS
Solar/Wind Helper
0.346
3145746EVERETS
Solar/Wind Helper
0.346
3145746EVERETS
Solar/Wind Helper
0.346
3145746EVERETS
Solar/Wind Helper
0.346
3145746EVERETS
Solar/Wind Helper
0.346
235020AA1-095 C
Solar/Wind Helper
0.023
315722AD1-056 GEN
Solar/Wind Helper
0.333
315724AD1-057 GEN
Solar/Wind Helper
0.183
315687AD1-152 GEN
Solar/Wind Helper
0.444
316327AA2-057 GEN
Solar/Wind Helper
0.416
316494AC1-189 GEN
Solar/Wind Helper
0.444
3147983MERCK5
Solar/Wind Helper
0.138
316420AA1-050 GEN
Solar/Wind Helper
0.443
3148013FISHERV
Solar/Wind Helper
0.345
3148133STUARTS
Solar/Wind Helper
0.207
3148013FISHERV
Solar/Wind Helper
0.198
23777801MSM_W1-116
Solar/Wind Helper
0.077
316319Z2-044 C
Solar/Wind Helper
0.066
3146233WITAKRS
Solar/Wind Helper
1.371
3146233WITAKRS
Solar/Wind Helper
0.234
316499AE2-029_GEN
Solar/Wind Helper
0.277
961671AG1-007 GEN
Solar/Wind Helper
0.052
3145573BETHELC
Solar/Wind Helper
0.344
3145573BETHELC
Solar/Wind Helper
0.344
3146073TAR RVR
Solar/Wind Helper
0.344
3146083TARBORO
Solar/Wind Helper
0.344
3146083TARBORO
Solar/Wind Helper
0.344
3138543CONSLDL
Solar/Wind Helper
0.227
3146843MT LREL
Solar/Wind Helper
0.344
3146843MT LREL
Solar/Wind Helper
0.344
316359AB2-059 GEN
Solar/Wind Helper
0.552
316049AB1-081 GEN
Solar/Wind Helper
0.442
3145543BTLEBRO
Solar/Wind Helper
0.344
3145543BTLEBRO
Solar/Wind Helper
0.344
3145543BTLEBRO
Solar/Wind Helper
0.344
3145543BTLEBRO
Solar/Wind Helper
0.275
270494AE1-108_GEN
Solar/Wind Helper
0.825
316118AC1-105 GEN
Solar/Wind Helper
0.281
316248AF1-058 C
Solar/Wind Helper
0.11
3147173SINAI
Solar/Wind Helper
0.342
3147243WELCO
Solar/Wind Helper
0.214
316003AC1-222 GEN
Solar/Wind Helper
0.354
237030AB1-096 C
Solar/Wind Helper
0.054
237025AB1-124 C
Solar/Wind Helper
0.109
237006AB1-125 GEN
Solar/Wind Helper
0.082
3148463FAIRFLD
Solar/Wind Helper
0.339
238221AF1-254 C O1
Solar/Wind Helper
0.109
316097T157 G90
Solar/Wind Helper
0.222
316095T157 G97
Solar/Wind Helper
0.222
316222AC1-221 GEN
Solar/Wind Helper
0.406
316283AC2-100 C
Solar/Wind Helper
0.378
23583801GRNGAP
Solar/Wind Helper
0.56
316123AC1-075 GEN
Solar/Wind Helper
0.431
237080AD1-060 GEN
Solar/Wind Helper
0.08
238208AF1-136 C
Solar/Wind Helper
0.084
270455AD2-022 GEN
Solar/Wind Helper
0.512
270457AD2-023 GEN
Solar/Wind Helper
0.288
3147123OTTER R
Solar/Wind Helper
0.197
237038AE2-054 C
Solar/Wind Helper
0.105
270016AE1-250 BESS
Solar/Wind Helper
0.394
270013AE1-250 PV
Solar/Wind Helper
0.394
235067AD1-061 GEN
Solar/Wind Helper
0.105
238108AE1-109 GEN1
Solar/Wind Helper
0.035
238109AE1-109 GEN2
Solar/Wind Helper
0.035
238110AE1-109 GEN3
Solar/Wind Helper
0.035
316217AC1-145 GEN
Solar/Wind Helper
0.262
316197AC1-042 GEN
Solar/Wind Helper
0.22
3147312GRETNA
Solar/Wind Helper
0.261
3146802CHATHAM
Solar/Wind Helper
0.245
3147312GRETNA
Solar/Wind Helper
0.065
270197AD1-017 GEN1
Solar/Wind Helper
0.314
270574AD1-017 GEN2
Solar/Wind Helper
0.314
237002AB1-128_GEN
Solar/Wind Helper
0.104
270173AC1-122 GEN
Solar/Wind Helper
0.395
237001AB1-127_GEN
Solar/Wind Helper
0.104
237085AD2-009_GEN
Solar/Wind Helper
0.364
270018AE2-047 C O1
Solar/Wind Helper
0.26
943811AF1-049 GEN
Solar/Wind Helper
0.644
208923BUSO V4-027
Solar/Wind Helper
0.026
235062AE1-101 C1
Solar/Wind Helper
0.385
235063AE1-101 C2
Solar/Wind Helper
0.385
270069AE2-166 C O1
Solar/Wind Helper
0.462
270336AE1-100 GEN
Solar/Wind Helper
0.339
964991AG1-363 GEN
Solar/Wind Helper
1.521
958121AF2-106 GEN
Solar/Wind Helper
0.756
270214AC2-123 GEN
Solar/Wind Helper
0.376
966391AG1-508 GEN
Solar/Wind Helper
1.776
G-007ALTFEXP_G-007A->PJM
CMTX
59.487
HAMLETPJM->LTFIMP_HAMLET
CLTF
6.1
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.63
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
24.822
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
5.302
BlueGrassPJM->LTFIMP_BlueG
CLTF
16.516
CBM NorthLTFEXP_CBM-N->PJM
CBM
72.137
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
149.8

Details for PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:129.51 %
Rating:3464.0 MVA
Rating Type:A
MVA to Mitigate:4486.18
MW Contribution:0.46
Bus #Bus NameTypeMW Contribution
200202DELTA2 ST
50/50
7.98
200200DELTA2 CT1
50/50
4.467
200201DELTA2 CT2
50/50
4.467
200195DELTA ST
50/50
3.948
200192DELTA CT1
50/50
2.368
200193DELTA CT2
50/50
2.368
200194DELTA CT3
50/50
2.368
200034PCHBTM 2
50/50
156.384
200035PCHBTM 3
50/50
25.265
200203Y1-065-STG
50/50
8.859
200204Y1-065-CTG1
50/50
5.579
200205Y1-065-CTG2
50/50
5.579
200052ROCKSP 1
50/50
66.186
200053ROCKSP 2
50/50
66.186
200054ROCKSP 3
50/50
65.515
200055ROCKSP 4
50/50
65.515
971149AH1-027 GEN
Solar/Wind Harmer
0.329
233972AC1-094 C
Solar/Wind Harmer
-0.001
970695AG2-447 GEN
Solar/Wind Harmer
0.264
234033AF1-007_GEN
Solar/Wind Harmer
27.496
970545AG2-347 GEN
Solar/Wind Harmer
113.265
972133AH1-634 GEN
Solar/Wind Harmer
17.161
233987AB2-037 GEN
Solar/Wind Harmer
0
972177AH1-672 GEN
Solar/Wind Harmer
0.985
972069AH1-584 GEN
Solar/Wind Harmer
0.657
972071AH1-585 GEN
Solar/Wind Harmer
0.657
972073AH1-586 GEN
Solar/Wind Harmer
11.823
971747AH1-380 GEN
Solar/Wind Harmer
0.263
233923SMA
Solar/Wind Harmer
-0.001
233998TM1NIN_3.36
Solar/Wind Harmer
-0.001
233997TMININ_4.2
Solar/Wind Harmer
-0.001
233996TM1833_GEN
Solar/Wind Harmer
-0.001
233990AG1-397 GEN
Solar/Wind Harmer
0
233990AG1-397 GEN
Solar/Wind Harmer
2.102
233940AF2-379 C
Solar/Wind Harmer
-0.001
234015AF2-250 C
Solar/Wind Harmer
-0.001
971195AH1-057 GEN
Solar/Wind Harmer
0.095
960671AF2-358 GEN
Solar/Wind Harmer
1.311
965821AG1-450 GEN
Solar/Wind Harmer
6.557
232426Y1-080 FULL
Solar/Wind Harmer
0
970277AG2-181 GEN
Solar/Wind Harmer
0.367
233946AB2-136 GEN
Solar/Wind Harmer
-0.001
233964AF2-378 GEN
Solar/Wind Harmer
0.001
234041AC1-190 GEN
Solar/Wind Harmer
0.655
233984AB2-036 GEN
Solar/Wind Harmer
1.193
233968AD2-076_GEN
Solar/Wind Harmer
0.632
234014AF1-036_GEN
Solar/Wind Harmer
0.258
970597AG2-380 GEN
Solar/Wind Harmer
5.156
234012AE2-112_GEN
Solar/Wind Harmer
0.219
971983AH1-536 GEN
Solar/Wind Harmer
0.536
970453AG2-297 GEN
Solar/Wind Harmer
0.223
971553AH1-274 GEN
Solar/Wind Harmer
0.194
945431AF1-208 GEN
Solar/Wind Harmer
0.521
230422AE1-104_GEN1
Solar/Wind Harmer
47.91
230425AE1-104_GEN2
Solar/Wind Harmer
47.91
970997AG2-616 GEN
Solar/Wind Harmer
0.578
972141AH1-641 GEN
Solar/Wind Harmer
0.173
230430AE1-229_GEN
Solar/Wind Harmer
-0.001
230433AD2-135 GEN
Solar/Wind Harmer
0
228351V2-046C
Solar/Wind Harmer
-0.001
971535AH1-265 GEN
Solar/Wind Harmer
0.338
971011AG2-627 GEN
Solar/Wind Harmer
0.459
228754AB1-001 C
Solar/Wind Harmer
-0.001
230407AD2-065 C
Solar/Wind Harmer
0
219137THOSOLAR C
Solar/Wind Harmer
0.001
219623KINSLEYBEA C
Solar/Wind Harmer
-0.001
219258KINSLEYDEP C
Solar/Wind Harmer
0
218660EHAMPSOLAR C
Solar/Wind Harmer
-0.001
219766PARADISE C
Solar/Wind Harmer
-0.001
219907AC1-030 C
Solar/Wind Harmer
-0.001
219236SOUTHERNHQ C
Solar/Wind Harmer
-0.001
219906AC1-017 C
Solar/Wind Harmer
-0.001
219615MILLCREEK C
Solar/Wind Harmer
-0.001
214067T20SOLAR
Solar/Wind Harmer
-0.001
207522AF2-254 C
Solar/Wind Harmer
0.106
207500AE2-000G1
Solar/Wind Harmer
41.355
207497AE2-000G2
Solar/Wind Harmer
41.355
207507AE2-000G3
Solar/Wind Harmer
41.355
207487AE2-000G4
Solar/Wind Harmer
41.355
970025AG2-016 GEN
Solar/Wind Harmer
0.208
971189AH1-054 GEN
Solar/Wind Harmer
0.086
971667AH1-334 GEN
Solar/Wind Harmer
0.201
219727YARDVSOLFA C
Solar/Wind Harmer
0.001
219276PARKLANDSO C
Solar/Wind Harmer
0
219817TRENTONSOL C
Solar/Wind Harmer
0.001
219620RIDERU C
Solar/Wind Harmer
-0.001
20714328BYD_X4-031
Solar/Wind Harmer
0.02
20714428HOW_X1-037
Solar/Wind Harmer
-0.001
20720628TIN_W1-124
Solar/Wind Harmer
-0.001
219918AC2-009 C
Solar/Wind Harmer
0
20742028HF_AC1-207
Solar/Wind Harmer
-0.001
971521AH1-258 GEN
Solar/Wind Harmer
0.193
967451AG2-055 C O1
Solar/Wind Harmer
219.805
219612MATRIX C
Solar/Wind Harmer
0
218438BLK ROCK C
Solar/Wind Harmer
0
218526CNTRALGAS2 C
Solar/Wind Harmer
0.001
218524CNTRALGAS1 C
Solar/Wind Harmer
0.001
218428ETC SOLAR C
Solar/Wind Harmer
0
217213AMBOY SO C
Solar/Wind Harmer
-0.001
219249CENTRALDIV C
Solar/Wind Harmer
0
20673828FLE_V3-070
Solar/Wind Harmer
0.068
218449LINSOLAR C
Solar/Wind Harmer
0.001
20675428EAM_W2-061
Solar/Wind Harmer
0
217081WEATEXAS C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
217206BARNGR HS C
Solar/Wind Harmer
0
217208PARK ELE C
Solar/Wind Harmer
0
207439AE1-081 C O1
Solar/Wind Harmer
0
20676328BVR_Y1-020
Solar/Wind Harmer
0
20674628WNG_W3-110
Solar/Wind Harmer
-0.001
207511W3-106 GEN
Solar/Wind Harmer
0.043
971009AG2-626 GEN
Solar/Wind Harmer
0.105
971007AG2-625 GEN
Solar/Wind Harmer
0.164
971519AH1-257 GEN
Solar/Wind Harmer
0.161
207437AD2-070 GEN
Solar/Wind Harmer
-0.001
966111AG1-480 GEN
Solar/Wind Harmer
0
966111AG1-480 GEN
Solar/Wind Harmer
2.765
966181AG1-487 GEN
Solar/Wind Harmer
0
966181AG1-487 GEN
Solar/Wind Harmer
3.1
970095AG2-074 GEN
Solar/Wind Harmer
0.27
209029WAYMART-WD
Solar/Wind Harmer
5.302
208972BECR K09
Solar/Wind Harmer
1.969
209027LOR2_Q27
Solar/Wind Harmer
7.641
212266LOR1
Solar/Wind Harmer
0.143
970237AG2-161 GEN
Solar/Wind Harmer
0.168
961541AF2-445A GEN
Solar/Wind Harmer
0.133
209142AF1-226 GEN
Solar/Wind Harmer
0.231
209093AE2-110 GEN
Solar/Wind Harmer
0.132
209120AE2-241 GEN
Solar/Wind Harmer
0.132
209045AE2-271 GEN
Solar/Wind Harmer
0.664
209059AE2-084 GEN
Solar/Wind Harmer
0.127
970665AG2-430 GEN
Solar/Wind Harmer
0.376
209130AF1-271A GEN
Solar/Wind Harmer
0.107
223401AF1-299 GEN
Solar/Wind Helper
0.139
223402AF1-300 C
Solar/Wind Helper
0.139
226910AB2-157 C
Solar/Wind Helper
0.019
227287AC2-120 GEN
Solar/Wind Helper
0.196
226929AD2-058 GEN
Solar/Wind Helper
0.038
208923BUSO V4-027
Solar/Wind Helper
0.03
G-007ALTFEXP_G-007A->PJM
CMTX
46.587
HAMLETPJM->LTFIMP_HAMLET
CLTF
4.459
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.641
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
17.734
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
3.779
BlueGrassPJM->LTFIMP_BlueG
CLTF
11.773
CBM NorthLTFEXP_CBM-N->PJM
CBM
60.553
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
119.936

Details for PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line l/o PECO_P2-2_NOTT230B_SRT-A/* $ CHESCO $ PECO_P2-2_NOTT230B $ B


Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
Contingency Name:
PECO_P2-2_NOTT230B_SRT-A/* $ CHESCO $ PECO_P2-2_NOTT230B $ B
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:128.48 %
Rating:3700.0 MVA
Rating Type:B
MVA to Mitigate:4753.65
MW Contribution:0.5
Bus #Bus NameTypeMW Contribution
200202DELTA2 ST
50/50
8.088
200200DELTA2 CT1
50/50
4.528
200201DELTA2 CT2
50/50
4.528
200195DELTA ST
50/50
4.002
200192DELTA CT1
50/50
2.4
200193DELTA CT2
50/50
2.4
200194DELTA CT3
50/50
2.4
200034PCHBTM 2
50/50
158.541
200035PCHBTM 3
50/50
25.638
200203Y1-065-STG
50/50
9.061
200204Y1-065-CTG1
50/50
5.706
200205Y1-065-CTG2
50/50
5.706
200052ROCKSP 1
50/50
67.695
200053ROCKSP 2
50/50
67.695
200054ROCKSP 3
50/50
67.008
200055ROCKSP 4
50/50
67.008
233987AB2-037 GEN
Solar/Wind Harmer
0
233946AB2-136 GEN
Solar/Wind Harmer
-0.001
232426Y1-080 FULL
Solar/Wind Harmer
0
233964AF2-378 GEN
Solar/Wind Harmer
0.001
960671AF2-358 GEN
Solar/Wind Harmer
1.436
234041AC1-190 GEN
Solar/Wind Harmer
0.718
970277AG2-181 GEN
Solar/Wind Harmer
0.402
965821AG1-450 GEN
Solar/Wind Harmer
7.179
233923SMA
Solar/Wind Harmer
-0.001
233998TM1NIN_3.36
Solar/Wind Harmer
-0.001
233997TMININ_4.2
Solar/Wind Harmer
-0.001
233996TM1833_GEN
Solar/Wind Harmer
-0.001
233940AF2-379 C
Solar/Wind Harmer
-0.001
234015AF2-250 C
Solar/Wind Harmer
-0.001
972069AH1-584 GEN
Solar/Wind Harmer
0.718
972071AH1-585 GEN
Solar/Wind Harmer
0.718
972073AH1-586 GEN
Solar/Wind Harmer
12.917
971747AH1-380 GEN
Solar/Wind Harmer
0.287
971195AH1-057 GEN
Solar/Wind Harmer
0.103
233990AG1-397 GEN
Solar/Wind Harmer
0
233990AG1-397 GEN
Solar/Wind Harmer
2.296
234033AF1-007_GEN
Solar/Wind Harmer
30.01
970545AG2-347 GEN
Solar/Wind Harmer
123.619
972133AH1-634 GEN
Solar/Wind Harmer
18.73
233984AB2-036 GEN
Solar/Wind Harmer
1.32
972177AH1-672 GEN
Solar/Wind Harmer
1.075
233968AD2-076_GEN
Solar/Wind Harmer
0.702
234014AF1-036_GEN
Solar/Wind Harmer
0.286
970597AG2-380 GEN
Solar/Wind Harmer
5.73
234012AE2-112_GEN
Solar/Wind Harmer
0.244
971149AH1-027 GEN
Solar/Wind Harmer
0.358
971983AH1-536 GEN
Solar/Wind Harmer
0.598
233972AC1-094 C
Solar/Wind Harmer
-0.001
970695AG2-447 GEN
Solar/Wind Harmer
0.286
970453AG2-297 GEN
Solar/Wind Harmer
0.242
971553AH1-274 GEN
Solar/Wind Harmer
0.212
945431AF1-208 GEN
Solar/Wind Harmer
0.569
970997AG2-616 GEN
Solar/Wind Harmer
0.631
972141AH1-641 GEN
Solar/Wind Harmer
0.189
230430AE1-229_GEN
Solar/Wind Harmer
-0.001
228351V2-046C
Solar/Wind Harmer
-0.001
230433AD2-135 GEN
Solar/Wind Harmer
0
971011AG2-627 GEN
Solar/Wind Harmer
0.502
230422AE1-104_GEN1
Solar/Wind Harmer
52.073
230425AE1-104_GEN2
Solar/Wind Harmer
52.073
971535AH1-265 GEN
Solar/Wind Harmer
0.368
230407AD2-065 C
Solar/Wind Harmer
0
228754AB1-001 C
Solar/Wind Harmer
-0.001
219137THOSOLAR C
Solar/Wind Harmer
0.001
219258KINSLEYDEP C
Solar/Wind Harmer
0
219623KINSLEYBEA C
Solar/Wind Harmer
-0.001
219766PARADISE C
Solar/Wind Harmer
-0.001
218660EHAMPSOLAR C
Solar/Wind Harmer
-0.001
219907AC1-030 C
Solar/Wind Harmer
-0.001
219236SOUTHERNHQ C
Solar/Wind Harmer
-0.001
219906AC1-017 C
Solar/Wind Harmer
-0.001
219615MILLCREEK C
Solar/Wind Harmer
-0.001
214067T20SOLAR
Solar/Wind Harmer
-0.001
207522AF2-254 C
Solar/Wind Harmer
0.115
207500AE2-000G1
Solar/Wind Harmer
44.855
207497AE2-000G2
Solar/Wind Harmer
44.855
207507AE2-000G3
Solar/Wind Harmer
44.855
207487AE2-000G4
Solar/Wind Harmer
44.855
970025AG2-016 GEN
Solar/Wind Harmer
0.226
971189AH1-054 GEN
Solar/Wind Harmer
0.094
971667AH1-334 GEN
Solar/Wind Harmer
0.218
219727YARDVSOLFA C
Solar/Wind Harmer
0.001
219276PARKLANDSO C
Solar/Wind Harmer
0
219620RIDERU C
Solar/Wind Harmer
-0.001
219817TRENTONSOL C
Solar/Wind Harmer
0.001
20714328BYD_X4-031
Solar/Wind Harmer
0.022
20714428HOW_X1-037
Solar/Wind Harmer
-0.001
219918AC2-009 C
Solar/Wind Harmer
0
20720628TIN_W1-124
Solar/Wind Harmer
-0.001
20742028HF_AC1-207
Solar/Wind Harmer
-0.001
971521AH1-258 GEN
Solar/Wind Harmer
0.208
967451AG2-055 C O1
Solar/Wind Harmer
237.457
219612MATRIX C
Solar/Wind Harmer
0.001
218438BLK ROCK C
Solar/Wind Harmer
0
218526CNTRALGAS2 C
Solar/Wind Harmer
0.001
218524CNTRALGAS1 C
Solar/Wind Harmer
0.001
218428ETC SOLAR C
Solar/Wind Harmer
0
217213AMBOY SO C
Solar/Wind Harmer
-0.001
219249CENTRALDIV C
Solar/Wind Harmer
-0.001
20673828FLE_V3-070
Solar/Wind Harmer
0.074
218449LINSOLAR C
Solar/Wind Harmer
0.001
20675428EAM_W2-061
Solar/Wind Harmer
0
217081WEATEXAS C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
217206BARNGR HS C
Solar/Wind Harmer
-0.001
217208PARK ELE C
Solar/Wind Harmer
0
207439AE1-081 C O1
Solar/Wind Harmer
0
20676328BVR_Y1-020
Solar/Wind Harmer
0
20674628WNG_W3-110
Solar/Wind Harmer
-0.001
207511W3-106 GEN
Solar/Wind Harmer
0.046
971009AG2-626 GEN
Solar/Wind Harmer
0.112
971007AG2-625 GEN
Solar/Wind Harmer
0.176
971519AH1-257 GEN
Solar/Wind Harmer
0.172
207437AD2-070 GEN
Solar/Wind Harmer
-0.001
966111AG1-480 GEN
Solar/Wind Harmer
0
966111AG1-480 GEN
Solar/Wind Harmer
2.964
966181AG1-487 GEN
Solar/Wind Harmer
0
966181AG1-487 GEN
Solar/Wind Harmer
3.323
970095AG2-074 GEN
Solar/Wind Harmer
0.288
209029WAYMART-WD
Solar/Wind Harmer
5.664
208972BECR K09
Solar/Wind Harmer
2.1
209027LOR2_Q27
Solar/Wind Harmer
8.127
212266LOR1
Solar/Wind Harmer
0.152
970237AG2-161 GEN
Solar/Wind Harmer
0.179
961541AF2-445A GEN
Solar/Wind Harmer
0.142
209142AF1-226 GEN
Solar/Wind Harmer
0.245
209093AE2-110 GEN
Solar/Wind Harmer
0.14
209120AE2-241 GEN
Solar/Wind Harmer
0.14
209045AE2-271 GEN
Solar/Wind Harmer
0.705
209059AE2-084 GEN
Solar/Wind Harmer
0.135
970665AG2-430 GEN
Solar/Wind Harmer
0.399
209130AF1-271A GEN
Solar/Wind Harmer
0.113
223401AF1-299 GEN
Solar/Wind Helper
0.164
223402AF1-300 C
Solar/Wind Helper
0.164
226910AB2-157 C
Solar/Wind Helper
0.02
227287AC2-120 GEN
Solar/Wind Helper
0.212
226929AD2-058 GEN
Solar/Wind Helper
0.041
208923BUSO V4-027
Solar/Wind Helper
0.036
208835TUHI V3-051
Solar/Wind Helper
0.041
208835TUHI V3-051
Solar/Wind Helper
0.041
3141426STAFORD
Solar/Wind Helper
0.07
G-007ALTFEXP_G-007A->PJM
CMTX
50.35
HAMLETPJM->LTFIMP_HAMLET
CLTF
4.809
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.847
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
19.071
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
4.063
BlueGrassPJM->LTFIMP_BlueG
CLTF
12.658
CBM NorthLTFEXP_CBM-N->PJM
CBM
65.229
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
129.37

Details for PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line l/o PL_04_P71_001014_SRT-A


Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
Contingency Name:
PL_04_P71_001014_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:125.36 %
Rating:3700.0 MVA
Rating Type:B
MVA to Mitigate:4638.19
MW Contribution:0.47
Bus #Bus NameTypeMW Contribution
200202DELTA2 ST
50/50
7.999
200200DELTA2 CT1
50/50
4.478
200201DELTA2 CT2
50/50
4.478
200195DELTA ST
50/50
3.958
200192DELTA CT1
50/50
2.374
200193DELTA CT2
50/50
2.374
200194DELTA CT3
50/50
2.374
200034PCHBTM 2
50/50
156.77
200035PCHBTM 3
50/50
25.34
200203Y1-065-STG
50/50
8.896
200204Y1-065-CTG1
50/50
5.602
200205Y1-065-CTG2
50/50
5.602
200052ROCKSP 1
50/50
66.462
200053ROCKSP 2
50/50
66.462
200054ROCKSP 3
50/50
65.788
200055ROCKSP 4
50/50
65.788
233972AC1-094 C
Solar/Wind Harmer
-0.001
971149AH1-027 GEN
Solar/Wind Harmer
0.334
970695AG2-447 GEN
Solar/Wind Harmer
0.267
234033AF1-007_GEN
Solar/Wind Harmer
27.885
970545AG2-347 GEN
Solar/Wind Harmer
114.865
972133AH1-634 GEN
Solar/Wind Harmer
17.404
972177AH1-672 GEN
Solar/Wind Harmer
0.999
233987AB2-037 GEN
Solar/Wind Harmer
0
972069AH1-584 GEN
Solar/Wind Harmer
0.666
972071AH1-585 GEN
Solar/Wind Harmer
0.666
972073AH1-586 GEN
Solar/Wind Harmer
11.989
971747AH1-380 GEN
Solar/Wind Harmer
0.266
233923SMA
Solar/Wind Harmer
-0.001
233998TM1NIN_3.36
Solar/Wind Harmer
-0.001
233997TMININ_4.2
Solar/Wind Harmer
-0.001
233996TM1833_GEN
Solar/Wind Harmer
-0.001
233990AG1-397 GEN
Solar/Wind Harmer
0
233990AG1-397 GEN
Solar/Wind Harmer
2.131
233940AF2-379 C
Solar/Wind Harmer
-0.001
234015AF2-250 C
Solar/Wind Harmer
-0.001
971195AH1-057 GEN
Solar/Wind Harmer
0.096
960671AF2-358 GEN
Solar/Wind Harmer
1.33
965821AG1-450 GEN
Solar/Wind Harmer
6.648
232426Y1-080 FULL
Solar/Wind Harmer
0
970277AG2-181 GEN
Solar/Wind Harmer
0.372
233946AB2-136 GEN
Solar/Wind Harmer
-0.001
233964AF2-378 GEN
Solar/Wind Harmer
0.001
234041AC1-190 GEN
Solar/Wind Harmer
0.664
233984AB2-036 GEN
Solar/Wind Harmer
1.209
233968AD2-076_GEN
Solar/Wind Harmer
0.64
234014AF1-036_GEN
Solar/Wind Harmer
0.261
970597AG2-380 GEN
Solar/Wind Harmer
5.227
234012AE2-112_GEN
Solar/Wind Harmer
0.222
971983AH1-536 GEN
Solar/Wind Harmer
0.543
970453AG2-297 GEN
Solar/Wind Harmer
0.228
971553AH1-274 GEN
Solar/Wind Harmer
0.199
945431AF1-208 GEN
Solar/Wind Harmer
0.534
230422AE1-104_GEN1
Solar/Wind Harmer
49.093
230425AE1-104_GEN2
Solar/Wind Harmer
49.093
970997AG2-616 GEN
Solar/Wind Harmer
0.592
972141AH1-641 GEN
Solar/Wind Harmer
0.178
230430AE1-229_GEN
Solar/Wind Harmer
-0.001
230433AD2-135 GEN
Solar/Wind Harmer
0
228351V2-046C
Solar/Wind Harmer
-0.001
971535AH1-265 GEN
Solar/Wind Harmer
0.346
971011AG2-627 GEN
Solar/Wind Harmer
0.47
228754AB1-001 C
Solar/Wind Harmer
-0.001
230407AD2-065 C
Solar/Wind Harmer
0
219137THOSOLAR C
Solar/Wind Harmer
0.001
219623KINSLEYBEA C
Solar/Wind Harmer
-0.001
219258KINSLEYDEP C
Solar/Wind Harmer
0
218660EHAMPSOLAR C
Solar/Wind Harmer
-0.001
219766PARADISE C
Solar/Wind Harmer
-0.001
219907AC1-030 C
Solar/Wind Harmer
-0.001
219236SOUTHERNHQ C
Solar/Wind Harmer
-0.001
219906AC1-017 C
Solar/Wind Harmer
-0.001
219615MILLCREEK C
Solar/Wind Harmer
-0.001
207522AF2-254 C
Solar/Wind Harmer
0.109
214067T20SOLAR
Solar/Wind Harmer
-0.001
207500AE2-000G1
Solar/Wind Harmer
42.691
207497AE2-000G2
Solar/Wind Harmer
42.691
207507AE2-000G3
Solar/Wind Harmer
42.691
207487AE2-000G4
Solar/Wind Harmer
42.691
970025AG2-016 GEN
Solar/Wind Harmer
0.215
971189AH1-054 GEN
Solar/Wind Harmer
0.089
971667AH1-334 GEN
Solar/Wind Harmer
0.207
219727YARDVSOLFA C
Solar/Wind Harmer
0.001
219276PARKLANDSO C
Solar/Wind Harmer
0
219817TRENTONSOL C
Solar/Wind Harmer
0.001
219620RIDERU C
Solar/Wind Harmer
-0.001
20714328BYD_X4-031
Solar/Wind Harmer
0.021
20714428HOW_X1-037
Solar/Wind Harmer
-0.001
20720628TIN_W1-124
Solar/Wind Harmer
-0.001
219918AC2-009 C
Solar/Wind Harmer
0
20742028HF_AC1-207
Solar/Wind Harmer
-0.001
971521AH1-258 GEN
Solar/Wind Harmer
0.2
967451AG2-055 C O1
Solar/Wind Harmer
228.081
219612MATRIX C
Solar/Wind Harmer
0.001
218438BLK ROCK C
Solar/Wind Harmer
0
218526CNTRALGAS2 C
Solar/Wind Harmer
0.001
218524CNTRALGAS1 C
Solar/Wind Harmer
0.001
218428ETC SOLAR C
Solar/Wind Harmer
0
217213AMBOY SO C
Solar/Wind Harmer
-0.001
219249CENTRALDIV C
Solar/Wind Harmer
-0.001
20673828FLE_V3-070
Solar/Wind Harmer
0.071
218449LINSOLAR C
Solar/Wind Harmer
0.001
20675428EAM_W2-061
Solar/Wind Harmer
0
217081WEATEXAS C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
217206BARNGR HS C
Solar/Wind Harmer
0
217208PARK ELE C
Solar/Wind Harmer
0
207439AE1-081 C O1
Solar/Wind Harmer
0
20676328BVR_Y1-020
Solar/Wind Harmer
0
20674628WNG_W3-110
Solar/Wind Harmer
-0.001
207511W3-106 GEN
Solar/Wind Harmer
0.045
971009AG2-626 GEN
Solar/Wind Harmer
0.111
971007AG2-625 GEN
Solar/Wind Harmer
0.174
971519AH1-257 GEN
Solar/Wind Harmer
0.17
207437AD2-070 GEN
Solar/Wind Harmer
-0.001
966181AG1-487 GEN
Solar/Wind Harmer
0
966181AG1-487 GEN
Solar/Wind Harmer
3.307
966111AG1-480 GEN
Solar/Wind Harmer
0
966111AG1-480 GEN
Solar/Wind Harmer
2.919
970095AG2-074 GEN
Solar/Wind Harmer
0.284
209029WAYMART-WD
Solar/Wind Harmer
5.578
208972BECR K09
Solar/Wind Harmer
2.073
209027LOR2_Q27
Solar/Wind Harmer
8.051
212266LOR1
Solar/Wind Harmer
0.15
970237AG2-161 GEN
Solar/Wind Harmer
0.177
961541AF2-445A GEN
Solar/Wind Harmer
0.141
209142AF1-226 GEN
Solar/Wind Harmer
0.243
209093AE2-110 GEN
Solar/Wind Harmer
0.139
209120AE2-241 GEN
Solar/Wind Harmer
0.139
209045AE2-271 GEN
Solar/Wind Harmer
0.699
209059AE2-084 GEN
Solar/Wind Harmer
0.134
208862AG1-362 C
Solar/Wind Harmer
0.033
970665AG2-430 GEN
Solar/Wind Harmer
0.396
209130AF1-271A GEN
Solar/Wind Harmer
0.112
223401AF1-299 GEN
Solar/Wind Helper
0.148
223402AF1-300 C
Solar/Wind Helper
0.148
208923BUSO V4-027
Solar/Wind Helper
0.038
226910AB2-157 C
Solar/Wind Helper
0.019
227287AC2-120 GEN
Solar/Wind Helper
0.202
226929AD2-058 GEN
Solar/Wind Helper
0.039
208835TUHI V3-051
Solar/Wind Helper
0.045
208835TUHI V3-051
Solar/Wind Helper
0.045
G-007ALTFEXP_G-007A->PJM
CMTX
48.447
HAMLETPJM->LTFIMP_HAMLET
CLTF
4.587
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.716
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
18.193
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
3.876
BlueGrassPJM->LTFIMP_BlueG
CLTF
12.075
CBM NorthLTFEXP_CBM-N->PJM
CBM
63.45
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
125.188

Details for PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line l/o PL_05_P71_000906_SRT-A


Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
Contingency Name:
PL_05_P71_000906_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:125.04 %
Rating:3700.0 MVA
Rating Type:B
MVA to Mitigate:4626.31
MW Contribution:0.47
Bus #Bus NameTypeMW Contribution
200202DELTA2 ST
50/50
7.947
200200DELTA2 CT1
50/50
4.449
200201DELTA2 CT2
50/50
4.449
200195DELTA ST
50/50
3.932
200192DELTA CT1
50/50
2.358
200193DELTA CT2
50/50
2.358
200194DELTA CT3
50/50
2.358
200034PCHBTM 2
50/50
155.741
200035PCHBTM 3
50/50
25.181
200203Y1-065-STG
50/50
8.835
200204Y1-065-CTG1
50/50
5.564
200205Y1-065-CTG2
50/50
5.564
200052ROCKSP 1
50/50
66.009
200053ROCKSP 2
50/50
66.009
200054ROCKSP 3
50/50
65.339
200055ROCKSP 4
50/50
65.339
233972AC1-094 C
Solar/Wind Harmer
-0.001
970695AG2-447 GEN
Solar/Wind Harmer
0.265
971149AH1-027 GEN
Solar/Wind Harmer
0.331
234033AF1-007_GEN
Solar/Wind Harmer
27.63
970545AG2-347 GEN
Solar/Wind Harmer
113.818
972133AH1-634 GEN
Solar/Wind Harmer
17.245
972177AH1-672 GEN
Solar/Wind Harmer
0.99
233987AB2-037 GEN
Solar/Wind Harmer
0
972069AH1-584 GEN
Solar/Wind Harmer
0.66
972071AH1-585 GEN
Solar/Wind Harmer
0.66
972073AH1-586 GEN
Solar/Wind Harmer
11.879
971747AH1-380 GEN
Solar/Wind Harmer
0.264
233923SMA
Solar/Wind Harmer
-0.001
233998TM1NIN_3.36
Solar/Wind Harmer
-0.001
233997TMININ_4.2
Solar/Wind Harmer
-0.001
233996TM1833_GEN
Solar/Wind Harmer
-0.001
233990AG1-397 GEN
Solar/Wind Harmer
0
233990AG1-397 GEN
Solar/Wind Harmer
2.112
233940AF2-379 C
Solar/Wind Harmer
-0.001
234015AF2-250 C
Solar/Wind Harmer
-0.001
971195AH1-057 GEN
Solar/Wind Harmer
0.095
960671AF2-358 GEN
Solar/Wind Harmer
1.317
965821AG1-450 GEN
Solar/Wind Harmer
6.586
232426Y1-080 FULL
Solar/Wind Harmer
0
970277AG2-181 GEN
Solar/Wind Harmer
0.369
233946AB2-136 GEN
Solar/Wind Harmer
-0.001
233964AF2-378 GEN
Solar/Wind Harmer
0.001
234041AC1-190 GEN
Solar/Wind Harmer
0.658
233984AB2-036 GEN
Solar/Wind Harmer
1.197
233968AD2-076_GEN
Solar/Wind Harmer
0.634
234014AF1-036_GEN
Solar/Wind Harmer
0.259
970597AG2-380 GEN
Solar/Wind Harmer
5.173
234012AE2-112_GEN
Solar/Wind Harmer
0.22
971983AH1-536 GEN
Solar/Wind Harmer
0.537
970453AG2-297 GEN
Solar/Wind Harmer
0.226
971553AH1-274 GEN
Solar/Wind Harmer
0.197
945431AF1-208 GEN
Solar/Wind Harmer
0.53
230422AE1-104_GEN1
Solar/Wind Harmer
48.725
230425AE1-104_GEN2
Solar/Wind Harmer
48.725
970997AG2-616 GEN
Solar/Wind Harmer
0.587
972141AH1-641 GEN
Solar/Wind Harmer
0.176
230430AE1-229_GEN
Solar/Wind Harmer
-0.001
230433AD2-135 GEN
Solar/Wind Harmer
0
228351V2-046C
Solar/Wind Harmer
-0.001
971535AH1-265 GEN
Solar/Wind Harmer
0.343
971011AG2-627 GEN
Solar/Wind Harmer
0.467
228754AB1-001 C
Solar/Wind Harmer
-0.001
230407AD2-065 C
Solar/Wind Harmer
0
219137THOSOLAR C
Solar/Wind Harmer
0.001
219623KINSLEYBEA C
Solar/Wind Harmer
-0.001
219258KINSLEYDEP C
Solar/Wind Harmer
0
218660EHAMPSOLAR C
Solar/Wind Harmer
-0.001
219766PARADISE C
Solar/Wind Harmer
-0.001
219907AC1-030 C
Solar/Wind Harmer
-0.001
219236SOUTHERNHQ C
Solar/Wind Harmer
-0.001
219906AC1-017 C
Solar/Wind Harmer
-0.001
219615MILLCREEK C
Solar/Wind Harmer
-0.001
207522AF2-254 C
Solar/Wind Harmer
0.109
214067T20SOLAR
Solar/Wind Harmer
-0.001
207500AE2-000G1
Solar/Wind Harmer
42.427
207497AE2-000G2
Solar/Wind Harmer
42.427
207507AE2-000G3
Solar/Wind Harmer
42.427
207487AE2-000G4
Solar/Wind Harmer
42.427
970025AG2-016 GEN
Solar/Wind Harmer
0.213
971189AH1-054 GEN
Solar/Wind Harmer
0.089
971667AH1-334 GEN
Solar/Wind Harmer
0.206
219727YARDVSOLFA C
Solar/Wind Harmer
0.001
219276PARKLANDSO C
Solar/Wind Harmer
0
20714328BYD_X4-031
Solar/Wind Harmer
0.021
219817TRENTONSOL C
Solar/Wind Harmer
0.001
219620RIDERU C
Solar/Wind Harmer
-0.001
20714428HOW_X1-037
Solar/Wind Harmer
-0.001
20720628TIN_W1-124
Solar/Wind Harmer
-0.001
219918AC2-009 C
Solar/Wind Harmer
0
20742028HF_AC1-207
Solar/Wind Harmer
-0.001
971521AH1-258 GEN
Solar/Wind Harmer
0.199
967451AG2-055 C O1
Solar/Wind Harmer
226.923
219612MATRIX C
Solar/Wind Harmer
0.001
218438BLK ROCK C
Solar/Wind Harmer
0
218526CNTRALGAS2 C
Solar/Wind Harmer
0.001
218524CNTRALGAS1 C
Solar/Wind Harmer
0.001
218428ETC SOLAR C
Solar/Wind Harmer
0
217213AMBOY SO C
Solar/Wind Harmer
-0.001
219249CENTRALDIV C
Solar/Wind Harmer
-0.001
20673828FLE_V3-070
Solar/Wind Harmer
0.071
218449LINSOLAR C
Solar/Wind Harmer
0.001
20675428EAM_W2-061
Solar/Wind Harmer
0
217081WEATEXAS C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
217206BARNGR HS C
Solar/Wind Harmer
0
217208PARK ELE C
Solar/Wind Harmer
0
207439AE1-081 C O1
Solar/Wind Harmer
0
20676328BVR_Y1-020
Solar/Wind Harmer
0
20674628WNG_W3-110
Solar/Wind Harmer
-0.001
207511W3-106 GEN
Solar/Wind Harmer
0.045
971009AG2-626 GEN
Solar/Wind Harmer
0.11
971007AG2-625 GEN
Solar/Wind Harmer
0.173
971519AH1-257 GEN
Solar/Wind Harmer
0.17
207437AD2-070 GEN
Solar/Wind Harmer
-0.001
966181AG1-487 GEN
Solar/Wind Harmer
0
966181AG1-487 GEN
Solar/Wind Harmer
3.298
966111AG1-480 GEN
Solar/Wind Harmer
0
966111AG1-480 GEN
Solar/Wind Harmer
2.918
970095AG2-074 GEN
Solar/Wind Harmer
0.286
209029WAYMART-WD
Solar/Wind Harmer
5.613
208972BECR K09
Solar/Wind Harmer
2.089
209027LOR2_Q27
Solar/Wind Harmer
8.143
212266LOR1
Solar/Wind Harmer
0.152
970237AG2-161 GEN
Solar/Wind Harmer
0.179
961541AF2-445A GEN
Solar/Wind Harmer
0.142
209142AF1-226 GEN
Solar/Wind Harmer
0.246
209093AE2-110 GEN
Solar/Wind Harmer
0.141
209120AE2-241 GEN
Solar/Wind Harmer
0.141
209045AE2-271 GEN
Solar/Wind Harmer
0.708
209059AE2-084 GEN
Solar/Wind Harmer
0.136
970665AG2-430 GEN
Solar/Wind Harmer
0.402
209130AF1-271A GEN
Solar/Wind Harmer
0.114
208862AG1-362 C
Solar/Wind Harmer
0.029
223401AF1-299 GEN
Solar/Wind Helper
0.159
223402AF1-300 C
Solar/Wind Helper
0.159
226910AB2-157 C
Solar/Wind Helper
0.02
227287AC2-120 GEN
Solar/Wind Helper
0.209
226929AD2-058 GEN
Solar/Wind Helper
0.041
3141426STAFORD
Solar/Wind Helper
0.069
G-007ALTFEXP_G-007A->PJM
CMTX
48.219
HAMLETPJM->LTFIMP_HAMLET
CLTF
4.674
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.764
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
18.433
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
3.925
BlueGrassPJM->LTFIMP_BlueG
CLTF
12.227
CBM NorthLTFEXP_CBM-N->PJM
CBM
63.534
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
124.716

Details for PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line l/o PL_04_P22_102817_SRT-A


Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
Contingency Name:
PL_04_P22_102817_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:123.71 %
Rating:3700.0 MVA
Rating Type:B
MVA to Mitigate:4577.25
MW Contribution:0.47
Bus #Bus NameTypeMW Contribution
200202DELTA2 ST
50/50
7.985
200200DELTA2 CT1
50/50
4.47
200201DELTA2 CT2
50/50
4.47
200195DELTA ST
50/50
3.95
200192DELTA CT1
50/50
2.37
200193DELTA CT2
50/50
2.37
200194DELTA CT3
50/50
2.37
200034PCHBTM 2
50/50
156.483
200035PCHBTM 3
50/50
25.296
200203Y1-065-STG
50/50
8.877
200204Y1-065-CTG1
50/50
5.59
200205Y1-065-CTG2
50/50
5.59
200052ROCKSP 1
50/50
66.321
200053ROCKSP 2
50/50
66.321
200054ROCKSP 3
50/50
65.648
200055ROCKSP 4
50/50
65.648
233972AC1-094 C
Solar/Wind Harmer
-0.001
971149AH1-027 GEN
Solar/Wind Harmer
0.333
970695AG2-447 GEN
Solar/Wind Harmer
0.266
234033AF1-007_GEN
Solar/Wind Harmer
27.772
970545AG2-347 GEN
Solar/Wind Harmer
114.402
972133AH1-634 GEN
Solar/Wind Harmer
17.334
972177AH1-672 GEN
Solar/Wind Harmer
0.995
233987AB2-037 GEN
Solar/Wind Harmer
0
972069AH1-584 GEN
Solar/Wind Harmer
0.663
972071AH1-585 GEN
Solar/Wind Harmer
0.663
972073AH1-586 GEN
Solar/Wind Harmer
11.941
971747AH1-380 GEN
Solar/Wind Harmer
0.265
233923SMA
Solar/Wind Harmer
-0.001
233998TM1NIN_3.36
Solar/Wind Harmer
-0.001
233997TMININ_4.2
Solar/Wind Harmer
-0.001
233996TM1833_GEN
Solar/Wind Harmer
-0.001
233990AG1-397 GEN
Solar/Wind Harmer
0
233990AG1-397 GEN
Solar/Wind Harmer
2.122
233940AF2-379 C
Solar/Wind Harmer
-0.001
234015AF2-250 C
Solar/Wind Harmer
-0.001
971195AH1-057 GEN
Solar/Wind Harmer
0.095
960671AF2-358 GEN
Solar/Wind Harmer
1.324
965821AG1-450 GEN
Solar/Wind Harmer
6.621
232426Y1-080 FULL
Solar/Wind Harmer
0
970277AG2-181 GEN
Solar/Wind Harmer
0.371
233946AB2-136 GEN
Solar/Wind Harmer
-0.001
233964AF2-378 GEN
Solar/Wind Harmer
0.001
234041AC1-190 GEN
Solar/Wind Harmer
0.661
233984AB2-036 GEN
Solar/Wind Harmer
1.204
233968AD2-076_GEN
Solar/Wind Harmer
0.638
234014AF1-036_GEN
Solar/Wind Harmer
0.26
970597AG2-380 GEN
Solar/Wind Harmer
5.204
234012AE2-112_GEN
Solar/Wind Harmer
0.221
971983AH1-536 GEN
Solar/Wind Harmer
0.541
970453AG2-297 GEN
Solar/Wind Harmer
0.227
971553AH1-274 GEN
Solar/Wind Harmer
0.198
945431AF1-208 GEN
Solar/Wind Harmer
0.531
230422AE1-104_GEN1
Solar/Wind Harmer
48.852
230425AE1-104_GEN2
Solar/Wind Harmer
48.852
970997AG2-616 GEN
Solar/Wind Harmer
0.589
972141AH1-641 GEN
Solar/Wind Harmer
0.177
230430AE1-229_GEN
Solar/Wind Harmer
-0.001
230433AD2-135 GEN
Solar/Wind Harmer
0
228351V2-046C
Solar/Wind Harmer
-0.001
971535AH1-265 GEN
Solar/Wind Harmer
0.344
971011AG2-627 GEN
Solar/Wind Harmer
0.468
228754AB1-001 C
Solar/Wind Harmer
-0.001
230407AD2-065 C
Solar/Wind Harmer
0
219137THOSOLAR C
Solar/Wind Harmer
0.001
219623KINSLEYBEA C
Solar/Wind Harmer
-0.001
219258KINSLEYDEP C
Solar/Wind Harmer
0
218660EHAMPSOLAR C
Solar/Wind Harmer
-0.001
219766PARADISE C
Solar/Wind Harmer
-0.001
219907AC1-030 C
Solar/Wind Harmer
-0.001
219236SOUTHERNHQ C
Solar/Wind Harmer
-0.001
219906AC1-017 C
Solar/Wind Harmer
-0.001
219615MILLCREEK C
Solar/Wind Harmer
-0.001
207522AF2-254 C
Solar/Wind Harmer
0.109
214067T20SOLAR
Solar/Wind Harmer
-0.001
207500AE2-000G1
Solar/Wind Harmer
42.459
207497AE2-000G2
Solar/Wind Harmer
42.459
207507AE2-000G3
Solar/Wind Harmer
42.459
207487AE2-000G4
Solar/Wind Harmer
42.459
970025AG2-016 GEN
Solar/Wind Harmer
0.214
971189AH1-054 GEN
Solar/Wind Harmer
0.089
971667AH1-334 GEN
Solar/Wind Harmer
0.206
219727YARDVSOLFA C
Solar/Wind Harmer
0.001
219276PARKLANDSO C
Solar/Wind Harmer
0
219620RIDERU C
Solar/Wind Harmer
-0.001
219817TRENTONSOL C
Solar/Wind Harmer
0.001
20714328BYD_X4-031
Solar/Wind Harmer
0.021
20714428HOW_X1-037
Solar/Wind Harmer
-0.001
20720628TIN_W1-124
Solar/Wind Harmer
-0.001
219918AC2-009 C
Solar/Wind Harmer
0
20742028HF_AC1-207
Solar/Wind Harmer
-0.001
971521AH1-258 GEN
Solar/Wind Harmer
0.199
967451AG2-055 C O1
Solar/Wind Harmer
226.772
219612MATRIX C
Solar/Wind Harmer
0.001
218438BLK ROCK C
Solar/Wind Harmer
0
218526CNTRALGAS2 C
Solar/Wind Harmer
0.001
218524CNTRALGAS1 C
Solar/Wind Harmer
0.001
218428ETC SOLAR C
Solar/Wind Harmer
0
217213AMBOY SO C
Solar/Wind Harmer
-0.001
219249CENTRALDIV C
Solar/Wind Harmer
-0.001
20673828FLE_V3-070
Solar/Wind Harmer
0.071
218449LINSOLAR C
Solar/Wind Harmer
0.001
20675428EAM_W2-061
Solar/Wind Harmer
0
217081WEATEXAS C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
217206BARNGR HS C
Solar/Wind Harmer
0
217208PARK ELE C
Solar/Wind Harmer
0
207439AE1-081 C O1
Solar/Wind Harmer
0
20676328BVR_Y1-020
Solar/Wind Harmer
0
20674628WNG_W3-110
Solar/Wind Harmer
-0.001
207511W3-106 GEN
Solar/Wind Harmer
0.045
971009AG2-626 GEN
Solar/Wind Harmer
0.11
971007AG2-625 GEN
Solar/Wind Harmer
0.172
971519AH1-257 GEN
Solar/Wind Harmer
0.169
207437AD2-070 GEN
Solar/Wind Harmer
-0.001
966181AG1-487 GEN
Solar/Wind Harmer
0
966181AG1-487 GEN
Solar/Wind Harmer
3.278
966111AG1-480 GEN
Solar/Wind Harmer
0
966111AG1-480 GEN
Solar/Wind Harmer
2.901
970095AG2-074 GEN
Solar/Wind Harmer
0.283
209029WAYMART-WD
Solar/Wind Harmer
5.564
208972BECR K09
Solar/Wind Harmer
2.069
209027LOR2_Q27
Solar/Wind Harmer
8.047
212266LOR1
Solar/Wind Harmer
0.15
970237AG2-161 GEN
Solar/Wind Harmer
0.177
961541AF2-445A GEN
Solar/Wind Harmer
0.141
209142AF1-226 GEN
Solar/Wind Harmer
0.243
209093AE2-110 GEN
Solar/Wind Harmer
0.139
209120AE2-241 GEN
Solar/Wind Harmer
0.139
209045AE2-271 GEN
Solar/Wind Harmer
0.699
209059AE2-084 GEN
Solar/Wind Harmer
0.134
970665AG2-430 GEN
Solar/Wind Harmer
0.396
209130AF1-271A GEN
Solar/Wind Harmer
0.112
208862AG1-362 C
Solar/Wind Harmer
0.029
223401AF1-299 GEN
Solar/Wind Helper
0.15
223402AF1-300 C
Solar/Wind Helper
0.15
208923BUSO V4-027
Solar/Wind Helper
0.041
226910AB2-157 C
Solar/Wind Helper
0.02
227287AC2-120 GEN
Solar/Wind Helper
0.204
226929AD2-058 GEN
Solar/Wind Helper
0.04
208835TUHI V3-051
Solar/Wind Helper
0.049
208835TUHI V3-051
Solar/Wind Helper
0.049
G-007ALTFEXP_G-007A->PJM
CMTX
48.162
HAMLETPJM->LTFIMP_HAMLET
CLTF
4.587
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.715
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
18.148
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
3.865
BlueGrassPJM->LTFIMP_BlueG
CLTF
12.042
CBM NorthLTFEXP_CBM-N->PJM
CBM
63.221
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
124.433

Details for [AG2-627] PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line l/o AP_P1-2_PE-500-3835T_SRT-A


Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-500-3835T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.17 %
Rating:3700.0 MVA
Rating Type:B
MVA to Mitigate:4372.3
MW Contribution:12.69
IPD Plant:AG2-627
Bus #Bus NameTypeMW Contribution
971011AG2-627 GEN
PJM_IPD
12.689

Details for [AG2-627] PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line l/o AP_P2-3_PE-500-019E_SRT-W


Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-500-019E_SRT-W
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:118.13 %
Rating:3700.0 MVA
Rating Type:B
MVA to Mitigate:4370.97
MW Contribution:12.69
IPD Plant:AG2-627
Bus #Bus NameTypeMW Contribution
971011AG2-627 GEN
PJM_IPD
12.693

Details for [AG2-627] PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line l/o AP_P2-3_PE-500-019B_SRT-A


Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-500-019B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.1 %
Rating:3700.0 MVA
Rating Type:B
MVA to Mitigate:4221.76
MW Contribution:11.95
IPD Plant:AG2-627
Bus #Bus NameTypeMW Contribution
971011AG2-627 GEN
PJM_IPD
11.945

Details for [AG2-627] PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line l/o PECO_P1-2_5007_SRT-A/* $ CHESCO $ PECO_P1-2_5007 $ L


Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
Contingency Name:
PECO_P1-2_5007_SRT-A/* $ CHESCO $ PECO_P1-2_5007 $ L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:109.27 %
Rating:3700.0 MVA
Rating Type:B
MVA to Mitigate:4043.06
MW Contribution:12.72
IPD Plant:AG2-627
Bus #Bus NameTypeMW Contribution
971011AG2-627 GEN
PJM_IPD
12.725

Details for PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line l/o PJM_500_BG_P4_5_CNSTN_C_SRT-A


Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line
Contingency Name:
PJM_500_BG_P4_5_CNSTN_C_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:163.3 %
Rating:3022.0 MVA
Rating Type:B
MVA to Mitigate:4934.9
MW Contribution:0.45
Bus #Bus NameTypeMW Contribution
200202DELTA2 ST
50/50
18.076
200200DELTA2 CT1
50/50
10.119
200201DELTA2 CT2
50/50
10.119
200195DELTA ST
50/50
8.943
200192DELTA CT1
50/50
5.364
200193DELTA CT2
50/50
5.364
200194DELTA CT3
50/50
5.364
200034PCHBTM 2
50/50
353.87
200203Y1-065-STG
50/50
19.152
200204Y1-065-CTG1
50/50
12.06
200205Y1-065-CTG2
50/50
12.06
200052ROCKSP 1
50/50
143.086
200053ROCKSP 2
50/50
143.086
200054ROCKSP 3
50/50
141.634
200055ROCKSP 4
50/50
141.634
231914HR8
50/50
4.351
231911HR5
50/50
2.973
231912HR6
50/50
2.973
231913HR7
50/50
2.973
233920W3-032A-CTG1
50/50
4.453
233921W3-032A-STG1
50/50
2.57
232616GEN FOOD
50/50
0.336
232901NORTHST
50/50
18.614
232904IR4
50/50
176.785
232920IR10
50/50
6.711
232921TASLEY2G
50/50
0.728
232905CHERITON_25
50/50
0.276
232912OH NUG1
50/50
18.152
232913OH NUG2
50/50
18.152
232914OH NUG3
50/50
18.152
232915OH NUG4
50/50
18.152
232916OH NUG5
50/50
18.152
232917OH NUG6
50/50
18.152
232918OH NUG7
50/50
18.152
234034AF2-060
50/50
3.63
232926CRISFLD1
50/50
0.221
232910NRG_G1
50/50
0.955
232911NRG_G2
50/50
0.955
200035PCHBTM 3
50/50
-14.443
971149AH1-027 GEN
Solar/Wind Harmer
0.506
233987AB2-037 GEN
Solar/Wind Harmer
0
233972AC1-094 C
Solar/Wind Harmer
-0.002
970695AG2-447 GEN
Solar/Wind Harmer
0.404
234033AF1-007_GEN
Solar/Wind Harmer
42.216
970545AG2-347 GEN
Solar/Wind Harmer
173.899
972133AH1-634 GEN
Solar/Wind Harmer
26.348
972069AH1-584 GEN
Solar/Wind Harmer
1.008
972071AH1-585 GEN
Solar/Wind Harmer
1.008
972073AH1-586 GEN
Solar/Wind Harmer
18.152
971747AH1-380 GEN
Solar/Wind Harmer
0.403
233923SMA
Solar/Wind Harmer
-0.002
233998TM1NIN_3.36
Solar/Wind Harmer
-0.002
233997TMININ_4.2
Solar/Wind Harmer
-0.002
233996TM1833_GEN
Solar/Wind Harmer
-0.002
233940AF2-379 C
Solar/Wind Harmer
-0.002
233990AG1-397 GEN
Solar/Wind Harmer
-0.001
233990AG1-397 GEN
Solar/Wind Harmer
3.226
972177AH1-672 GEN
Solar/Wind Harmer
1.512
234015AF2-250 C
Solar/Wind Harmer
-0.001
971195AH1-057 GEN
Solar/Wind Harmer
0.145
960671AF2-358 GEN
Solar/Wind Harmer
2.012
965821AG1-450 GEN
Solar/Wind Harmer
10.06
232426Y1-080 FULL
Solar/Wind Harmer
0
970277AG2-181 GEN
Solar/Wind Harmer
0.563
233946AB2-136 GEN
Solar/Wind Harmer
-0.002
233964AF2-378 GEN
Solar/Wind Harmer
0.001
234041AC1-190 GEN
Solar/Wind Harmer
1.004
233984AB2-036 GEN
Solar/Wind Harmer
1.817
233968AD2-076_GEN
Solar/Wind Harmer
0.958
234014AF1-036_GEN
Solar/Wind Harmer
0.391
970597AG2-380 GEN
Solar/Wind Harmer
7.817
234012AE2-112_GEN
Solar/Wind Harmer
0.332
971983AH1-536 GEN
Solar/Wind Harmer
0.809
970453AG2-297 GEN
Solar/Wind Harmer
0.245
971553AH1-274 GEN
Solar/Wind Harmer
0.207
230422AE1-104_GEN1
Solar/Wind Harmer
50.369
230425AE1-104_GEN2
Solar/Wind Harmer
50.369
945431AF1-208 GEN
Solar/Wind Harmer
0.54
230433AD2-135 GEN
Solar/Wind Harmer
0
970997AG2-616 GEN
Solar/Wind Harmer
0.591
972141AH1-641 GEN
Solar/Wind Harmer
0.177
230430AE1-229_GEN
Solar/Wind Harmer
-0.001
228754AB1-001 C
Solar/Wind Harmer
-0.001
228351V2-046C
Solar/Wind Harmer
-0.001
971535AH1-265 GEN
Solar/Wind Harmer
0.34
230407AD2-065 C
Solar/Wind Harmer
0
971011AG2-627 GEN
Solar/Wind Harmer
0.453
218660EHAMPSOLAR C
Solar/Wind Harmer
-0.001
219137THOSOLAR C
Solar/Wind Harmer
0.001
219623KINSLEYBEA C
Solar/Wind Harmer
-0.001
219258KINSLEYDEP C
Solar/Wind Harmer
0
219766PARADISE C
Solar/Wind Harmer
-0.001
219907AC1-030 C
Solar/Wind Harmer
-0.001
219236SOUTHERNHQ C
Solar/Wind Harmer
-0.001
207500AE2-000G1
Solar/Wind Harmer
32.687
207497AE2-000G2
Solar/Wind Harmer
32.687
207507AE2-000G3
Solar/Wind Harmer
32.687
207487AE2-000G4
Solar/Wind Harmer
32.687
207522AF2-254 C
Solar/Wind Harmer
0.082
219906AC1-017 C
Solar/Wind Harmer
-0.001
219615MILLCREEK C
Solar/Wind Harmer
-0.001
970025AG2-016 GEN
Solar/Wind Harmer
0.161
971189AH1-054 GEN
Solar/Wind Harmer
0.066
971667AH1-334 GEN
Solar/Wind Harmer
0.15
214067T20SOLAR
Solar/Wind Harmer
-0.001
20714328BYD_X4-031
Solar/Wind Harmer
0.014
20714428HOW_X1-037
Solar/Wind Harmer
0
219727YARDVSOLFA C
Solar/Wind Harmer
0
20720628TIN_W1-124
Solar/Wind Harmer
-0.001
20742028HF_AC1-207
Solar/Wind Harmer
-0.001
971521AH1-258 GEN
Solar/Wind Harmer
0.124
219276PARKLANDSO C
Solar/Wind Harmer
0
967451AG2-055 C O1
Solar/Wind Harmer
137.036
219620RIDERU C
Solar/Wind Harmer
-0.001
219817TRENTONSOL C
Solar/Wind Harmer
0
219918AC2-009 C
Solar/Wind Harmer
0
219612MATRIX C
Solar/Wind Harmer
0
218438BLK ROCK C
Solar/Wind Harmer
0
218526CNTRALGAS2 C
Solar/Wind Harmer
0
218524CNTRALGAS1 C
Solar/Wind Harmer
0
218428ETC SOLAR C
Solar/Wind Harmer
0
217213AMBOY SO C
Solar/Wind Harmer
-0.001
G-007ALTFEXP_G-007A->PJM
CMTX
26.726
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.493
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.099
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
14.929
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
3.204
BlueGrassPJM->LTFIMP_BlueG
CLTF
9.977
CBM NorthLTFEXP_CBM-N->PJM
CBM
21.412
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
58.553

Details for PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line l/o PECO_P1-2_5012_SRT-A


Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line
Contingency Name:
PECO_P1-2_5012_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:163.21 %
Rating:3022.0 MVA
Rating Type:B
MVA to Mitigate:4932.26
MW Contribution:0.45
Bus #Bus NameTypeMW Contribution
200202DELTA2 ST
50/50
18.076
200200DELTA2 CT1
50/50
10.119
200201DELTA2 CT2
50/50
10.119
200195DELTA ST
50/50
8.943
200192DELTA CT1
50/50
5.364
200193DELTA CT2
50/50
5.364
200194DELTA CT3
50/50
5.364
200034PCHBTM 2
50/50
353.87
200203Y1-065-STG
50/50
19.152
200204Y1-065-CTG1
50/50
12.06
200205Y1-065-CTG2
50/50
12.06
200052ROCKSP 1
50/50
143.086
200053ROCKSP 2
50/50
143.086
200054ROCKSP 3
50/50
141.634
200055ROCKSP 4
50/50
141.634
231914HR8
50/50
4.351
231911HR5
50/50
2.973
231912HR6
50/50
2.973
231913HR7
50/50
2.973
233920W3-032A-CTG1
50/50
4.453
233921W3-032A-STG1
50/50
2.57
232616GEN FOOD
50/50
0.336
232901NORTHST
50/50
18.614
232904IR4
50/50
176.785
232920IR10
50/50
6.711
232921TASLEY2G
50/50
0.728
232905CHERITON_25
50/50
0.276
232912OH NUG1
50/50
18.152
232913OH NUG2
50/50
18.152
232914OH NUG3
50/50
18.152
232915OH NUG4
50/50
18.152
232916OH NUG5
50/50
18.152
232917OH NUG6
50/50
18.152
232918OH NUG7
50/50
18.152
234034AF2-060
50/50
3.63
232926CRISFLD1
50/50
0.221
232910NRG_G1
50/50
0.955
232911NRG_G2
50/50
0.955
200035PCHBTM 3
50/50
-14.443
971149AH1-027 GEN
Solar/Wind Harmer
0.506
233987AB2-037 GEN
Solar/Wind Harmer
0
233972AC1-094 C
Solar/Wind Harmer
-0.002
970695AG2-447 GEN
Solar/Wind Harmer
0.404
234033AF1-007_GEN
Solar/Wind Harmer
42.216
970545AG2-347 GEN
Solar/Wind Harmer
173.899
972133AH1-634 GEN
Solar/Wind Harmer
26.348
972069AH1-584 GEN
Solar/Wind Harmer
1.008
972071AH1-585 GEN
Solar/Wind Harmer
1.008
972073AH1-586 GEN
Solar/Wind Harmer
18.152
971747AH1-380 GEN
Solar/Wind Harmer
0.403
233923SMA
Solar/Wind Harmer
-0.002
233998TM1NIN_3.36
Solar/Wind Harmer
-0.002
233997TMININ_4.2
Solar/Wind Harmer
-0.002
233996TM1833_GEN
Solar/Wind Harmer
-0.002
233940AF2-379 C
Solar/Wind Harmer
-0.002
233990AG1-397 GEN
Solar/Wind Harmer
-0.001
233990AG1-397 GEN
Solar/Wind Harmer
3.226
972177AH1-672 GEN
Solar/Wind Harmer
1.512
234015AF2-250 C
Solar/Wind Harmer
-0.001
971195AH1-057 GEN
Solar/Wind Harmer
0.145
960671AF2-358 GEN
Solar/Wind Harmer
2.012
965821AG1-450 GEN
Solar/Wind Harmer
10.06
232426Y1-080 FULL
Solar/Wind Harmer
0
970277AG2-181 GEN
Solar/Wind Harmer
0.563
233946AB2-136 GEN
Solar/Wind Harmer
-0.002
233964AF2-378 GEN
Solar/Wind Harmer
0.001
234041AC1-190 GEN
Solar/Wind Harmer
1.004
233984AB2-036 GEN
Solar/Wind Harmer
1.817
233968AD2-076_GEN
Solar/Wind Harmer
0.958
234014AF1-036_GEN
Solar/Wind Harmer
0.391
970597AG2-380 GEN
Solar/Wind Harmer
7.817
234012AE2-112_GEN
Solar/Wind Harmer
0.332
971983AH1-536 GEN
Solar/Wind Harmer
0.809
970453AG2-297 GEN
Solar/Wind Harmer
0.245
971553AH1-274 GEN
Solar/Wind Harmer
0.207
230422AE1-104_GEN1
Solar/Wind Harmer
50.369
230425AE1-104_GEN2
Solar/Wind Harmer
50.369
945431AF1-208 GEN
Solar/Wind Harmer
0.54
230433AD2-135 GEN
Solar/Wind Harmer
0
970997AG2-616 GEN
Solar/Wind Harmer
0.591
972141AH1-641 GEN
Solar/Wind Harmer
0.177
230430AE1-229_GEN
Solar/Wind Harmer
-0.001
228754AB1-001 C
Solar/Wind Harmer
-0.001
228351V2-046C
Solar/Wind Harmer
-0.001
971535AH1-265 GEN
Solar/Wind Harmer
0.34
230407AD2-065 C
Solar/Wind Harmer
0
971011AG2-627 GEN
Solar/Wind Harmer
0.453
218660EHAMPSOLAR C
Solar/Wind Harmer
-0.001
219137THOSOLAR C
Solar/Wind Harmer
0.001
219623KINSLEYBEA C
Solar/Wind Harmer
-0.001
219258KINSLEYDEP C
Solar/Wind Harmer
0
219766PARADISE C
Solar/Wind Harmer
-0.001
219907AC1-030 C
Solar/Wind Harmer
-0.001
219236SOUTHERNHQ C
Solar/Wind Harmer
-0.001
207500AE2-000G1
Solar/Wind Harmer
32.687
207497AE2-000G2
Solar/Wind Harmer
32.687
207507AE2-000G3
Solar/Wind Harmer
32.687
207487AE2-000G4
Solar/Wind Harmer
32.687
207522AF2-254 C
Solar/Wind Harmer
0.082
219906AC1-017 C
Solar/Wind Harmer
-0.001
219615MILLCREEK C
Solar/Wind Harmer
-0.001
970025AG2-016 GEN
Solar/Wind Harmer
0.161
971189AH1-054 GEN
Solar/Wind Harmer
0.066
971667AH1-334 GEN
Solar/Wind Harmer
0.15
214067T20SOLAR
Solar/Wind Harmer
-0.001
20714328BYD_X4-031
Solar/Wind Harmer
0.014
20714428HOW_X1-037
Solar/Wind Harmer
0
219727YARDVSOLFA C
Solar/Wind Harmer
0
20720628TIN_W1-124
Solar/Wind Harmer
-0.001
20742028HF_AC1-207
Solar/Wind Harmer
-0.001
971521AH1-258 GEN
Solar/Wind Harmer
0.124
219276PARKLANDSO C
Solar/Wind Harmer
0
967451AG2-055 C O1
Solar/Wind Harmer
137.036
219620RIDERU C
Solar/Wind Harmer
-0.001
219817TRENTONSOL C
Solar/Wind Harmer
0
219918AC2-009 C
Solar/Wind Harmer
0
219612MATRIX C
Solar/Wind Harmer
0
218438BLK ROCK C
Solar/Wind Harmer
0
218526CNTRALGAS2 C
Solar/Wind Harmer
0
218524CNTRALGAS1 C
Solar/Wind Harmer
0
218428ETC SOLAR C
Solar/Wind Harmer
0
217213AMBOY SO C
Solar/Wind Harmer
-0.001
G-007ALTFEXP_G-007A->PJM
CMTX
26.726
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.493
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.099
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
14.929
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
3.204
BlueGrassPJM->LTFIMP_BlueG
CLTF
9.977
CBM NorthLTFEXP_CBM-N->PJM
CBM
21.412
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
58.553

Details for PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line l/o BGE_P4_GRACETON_51_SRT-A


Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line
Contingency Name:
BGE_P4_GRACETON_51_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:163.21 %
Rating:3022.0 MVA
Rating Type:B
MVA to Mitigate:4932.21
MW Contribution:0.45
Bus #Bus NameTypeMW Contribution
200202DELTA2 ST
50/50
18.076
200200DELTA2 CT1
50/50
10.119
200201DELTA2 CT2
50/50
10.119
200195DELTA ST
50/50
8.943
200192DELTA CT1
50/50
5.364
200193DELTA CT2
50/50
5.364
200194DELTA CT3
50/50
5.364
200034PCHBTM 2
50/50
353.87
200203Y1-065-STG
50/50
19.152
200204Y1-065-CTG1
50/50
12.06
200205Y1-065-CTG2
50/50
12.06
200052ROCKSP 1
50/50
143.086
200053ROCKSP 2
50/50
143.086
200054ROCKSP 3
50/50
141.634
200055ROCKSP 4
50/50
141.634
231914HR8
50/50
4.351
231911HR5
50/50
2.973
231912HR6
50/50
2.973
231913HR7
50/50
2.973
233920W3-032A-CTG1
50/50
4.453
233921W3-032A-STG1
50/50
2.57
232616GEN FOOD
50/50
0.336
232901NORTHST
50/50
18.614
232904IR4
50/50
176.785
232920IR10
50/50
6.711
232921TASLEY2G
50/50
0.728
232905CHERITON_25
50/50
0.276
232912OH NUG1
50/50
18.152
232913OH NUG2
50/50
18.152
232914OH NUG3
50/50
18.152
232915OH NUG4
50/50
18.152
232916OH NUG5
50/50
18.152
232917OH NUG6
50/50
18.152
232918OH NUG7
50/50
18.152
234034AF2-060
50/50
3.63
232926CRISFLD1
50/50
0.221
232910NRG_G1
50/50
0.955
232911NRG_G2
50/50
0.955
200035PCHBTM 3
50/50
-14.443
971149AH1-027 GEN
Solar/Wind Harmer
0.506
233987AB2-037 GEN
Solar/Wind Harmer
0
233972AC1-094 C
Solar/Wind Harmer
-0.002
970695AG2-447 GEN
Solar/Wind Harmer
0.404
234033AF1-007_GEN
Solar/Wind Harmer
42.216
970545AG2-347 GEN
Solar/Wind Harmer
173.899
972133AH1-634 GEN
Solar/Wind Harmer
26.348
972069AH1-584 GEN
Solar/Wind Harmer
1.008
972071AH1-585 GEN
Solar/Wind Harmer
1.008
972073AH1-586 GEN
Solar/Wind Harmer
18.152
971747AH1-380 GEN
Solar/Wind Harmer
0.403
233923SMA
Solar/Wind Harmer
-0.002
233998TM1NIN_3.36
Solar/Wind Harmer
-0.002
233997TMININ_4.2
Solar/Wind Harmer
-0.002
233996TM1833_GEN
Solar/Wind Harmer
-0.002
233940AF2-379 C
Solar/Wind Harmer
-0.002
233990AG1-397 GEN
Solar/Wind Harmer
-0.001
233990AG1-397 GEN
Solar/Wind Harmer
3.226
972177AH1-672 GEN
Solar/Wind Harmer
1.512
234015AF2-250 C
Solar/Wind Harmer
-0.001
971195AH1-057 GEN
Solar/Wind Harmer
0.145
960671AF2-358 GEN
Solar/Wind Harmer
2.012
965821AG1-450 GEN
Solar/Wind Harmer
10.06
232426Y1-080 FULL
Solar/Wind Harmer
0
970277AG2-181 GEN
Solar/Wind Harmer
0.563
233946AB2-136 GEN
Solar/Wind Harmer
-0.002
233964AF2-378 GEN
Solar/Wind Harmer
0.001
234041AC1-190 GEN
Solar/Wind Harmer
1.004
233984AB2-036 GEN
Solar/Wind Harmer
1.817
233968AD2-076_GEN
Solar/Wind Harmer
0.958
234014AF1-036_GEN
Solar/Wind Harmer
0.391
970597AG2-380 GEN
Solar/Wind Harmer
7.817
234012AE2-112_GEN
Solar/Wind Harmer
0.332
971983AH1-536 GEN
Solar/Wind Harmer
0.809
970453AG2-297 GEN
Solar/Wind Harmer
0.245
971553AH1-274 GEN
Solar/Wind Harmer
0.207
230422AE1-104_GEN1
Solar/Wind Harmer
50.369
230425AE1-104_GEN2
Solar/Wind Harmer
50.369
945431AF1-208 GEN
Solar/Wind Harmer
0.54
230433AD2-135 GEN
Solar/Wind Harmer
0
970997AG2-616 GEN
Solar/Wind Harmer
0.591
972141AH1-641 GEN
Solar/Wind Harmer
0.177
230430AE1-229_GEN
Solar/Wind Harmer
-0.001
228754AB1-001 C
Solar/Wind Harmer
-0.001
228351V2-046C
Solar/Wind Harmer
-0.001
971535AH1-265 GEN
Solar/Wind Harmer
0.34
230407AD2-065 C
Solar/Wind Harmer
0
971011AG2-627 GEN
Solar/Wind Harmer
0.453
218660EHAMPSOLAR C
Solar/Wind Harmer
-0.001
219137THOSOLAR C
Solar/Wind Harmer
0.001
219623KINSLEYBEA C
Solar/Wind Harmer
-0.001
219258KINSLEYDEP C
Solar/Wind Harmer
0
219766PARADISE C
Solar/Wind Harmer
-0.001
219907AC1-030 C
Solar/Wind Harmer
-0.001
219236SOUTHERNHQ C
Solar/Wind Harmer
-0.001
207500AE2-000G1
Solar/Wind Harmer
32.687
207497AE2-000G2
Solar/Wind Harmer
32.687
207507AE2-000G3
Solar/Wind Harmer
32.687
207487AE2-000G4
Solar/Wind Harmer
32.687
207522AF2-254 C
Solar/Wind Harmer
0.082
219906AC1-017 C
Solar/Wind Harmer
-0.001
219615MILLCREEK C
Solar/Wind Harmer
-0.001
970025AG2-016 GEN
Solar/Wind Harmer
0.161
971189AH1-054 GEN
Solar/Wind Harmer
0.066
971667AH1-334 GEN
Solar/Wind Harmer
0.15
214067T20SOLAR
Solar/Wind Harmer
-0.001
20714328BYD_X4-031
Solar/Wind Harmer
0.014
20714428HOW_X1-037
Solar/Wind Harmer
0
219727YARDVSOLFA C
Solar/Wind Harmer
0
20720628TIN_W1-124
Solar/Wind Harmer
-0.001
20742028HF_AC1-207
Solar/Wind Harmer
-0.001
971521AH1-258 GEN
Solar/Wind Harmer
0.124
219276PARKLANDSO C
Solar/Wind Harmer
0
967451AG2-055 C O1
Solar/Wind Harmer
137.036
219620RIDERU C
Solar/Wind Harmer
-0.001
219817TRENTONSOL C
Solar/Wind Harmer
0
219918AC2-009 C
Solar/Wind Harmer
0
219612MATRIX C
Solar/Wind Harmer
0
218438BLK ROCK C
Solar/Wind Harmer
0
218526CNTRALGAS2 C
Solar/Wind Harmer
0
218524CNTRALGAS1 C
Solar/Wind Harmer
0
218428ETC SOLAR C
Solar/Wind Harmer
0
217213AMBOY SO C
Solar/Wind Harmer
-0.001
G-007ALTFEXP_G-007A->PJM
CMTX
26.726
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.493
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.099
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
14.929
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
3.204
BlueGrassPJM->LTFIMP_BlueG
CLTF
9.977
CBM NorthLTFEXP_CBM-N->PJM
CBM
21.412
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
58.553

Details for PCHBTM2S-PCHBTM1S 500.0 kV Ckt Z1 line l/o PECO_P4_PEACH255_SRT-A/* $ CHESCO $ PECO_P4_PEACH255 $ STBK


Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM2S-PCHBTM1S 500.0 kV Ckt Z1 line
Contingency Name:
PECO_P4_PEACH255_SRT-A/* $ CHESCO $ PECO_P4_PEACH255 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:134.81 %
Rating:3277.0 MVA
Rating Type:B
MVA to Mitigate:4417.81
MW Contribution:0.51
Bus #Bus NameTypeMW Contribution
200034PCHBTM 2
50/50
293.172
200203Y1-065-STG
50/50
16.076
200204Y1-065-CTG1
50/50
10.123
200205Y1-065-CTG2
50/50
10.123
200052ROCKSP 1
50/50
120.102
200053ROCKSP 2
50/50
120.102
200054ROCKSP 3
50/50
118.883
200055ROCKSP 4
50/50
118.883
231914HR8
50/50
4.053
231911HR5
50/50
2.769
231912HR6
50/50
2.769
231913HR7
50/50
2.769
233920W3-032A-CTG1
50/50
4.181
233921W3-032A-STG1
50/50
2.414
232616GEN FOOD
50/50
0.316
232901NORTHST
50/50
17.48
232904IR4
50/50
166.022
232920IR10
50/50
6.302
232921TASLEY2G
50/50
0.683
232905CHERITON_25
50/50
0.259
232912OH NUG1
50/50
17.047
232913OH NUG2
50/50
17.047
232914OH NUG3
50/50
17.047
232915OH NUG4
50/50
17.047
232916OH NUG5
50/50
17.047
232917OH NUG6
50/50
17.047
232918OH NUG7
50/50
17.047
234034AF2-060
50/50
3.409
232926CRISFLD1
50/50
0.207
233900O-025 C
50/50
0.124
232907VN8
50/50
44.523
231940T-011
50/50
0.103
232919VN10
50/50
5.854
232910NRG_G1
50/50
0.899
232911NRG_G2
50/50
0.899
971149AH1-027 GEN
Solar/Wind Harmer
0.475
233972AC1-094 C
Solar/Wind Harmer
-0.002
970695AG2-447 GEN
Solar/Wind Harmer
0.38
233987AB2-037 GEN
Solar/Wind Harmer
0
234033AF1-007_GEN
Solar/Wind Harmer
39.645
970545AG2-347 GEN
Solar/Wind Harmer
163.311
972133AH1-634 GEN
Solar/Wind Harmer
24.744
972069AH1-584 GEN
Solar/Wind Harmer
0.947
972071AH1-585 GEN
Solar/Wind Harmer
0.947
972073AH1-586 GEN
Solar/Wind Harmer
17.047
971747AH1-380 GEN
Solar/Wind Harmer
0.379
233923SMA
Solar/Wind Harmer
-0.002
233998TM1NIN_3.36
Solar/Wind Harmer
-0.002
233997TMININ_4.2
Solar/Wind Harmer
-0.002
233996TM1833_GEN
Solar/Wind Harmer
-0.002
233990AG1-397 GEN
Solar/Wind Harmer
-0.001
233940AF2-379 C
Solar/Wind Harmer
-0.002
233990AG1-397 GEN
Solar/Wind Harmer
3.03
972177AH1-672 GEN
Solar/Wind Harmer
1.42
234015AF2-250 C
Solar/Wind Harmer
-0.001
971195AH1-057 GEN
Solar/Wind Harmer
0.136
960671AF2-358 GEN
Solar/Wind Harmer
1.89
965821AG1-450 GEN
Solar/Wind Harmer
9.45
232426Y1-080 FULL
Solar/Wind Harmer
0
970277AG2-181 GEN
Solar/Wind Harmer
0.529
233946AB2-136 GEN
Solar/Wind Harmer
-0.002
233964AF2-378 GEN
Solar/Wind Harmer
0.001
234041AC1-190 GEN
Solar/Wind Harmer
0.943
233984AB2-036 GEN
Solar/Wind Harmer
1.711
233968AD2-076_GEN
Solar/Wind Harmer
0.904
234014AF1-036_GEN
Solar/Wind Harmer
0.369
970597AG2-380 GEN
Solar/Wind Harmer
7.377
234012AE2-112_GEN
Solar/Wind Harmer
0.314
971983AH1-536 GEN
Solar/Wind Harmer
0.764
970453AG2-297 GEN
Solar/Wind Harmer
0.263
971553AH1-274 GEN
Solar/Wind Harmer
0.226
230422AE1-104_GEN1
Solar/Wind Harmer
55.25
230425AE1-104_GEN2
Solar/Wind Harmer
55.25
945431AF1-208 GEN
Solar/Wind Harmer
0.596
230433AD2-135 GEN
Solar/Wind Harmer
0
970997AG2-616 GEN
Solar/Wind Harmer
0.656
972141AH1-641 GEN
Solar/Wind Harmer
0.197
230430AE1-229_GEN
Solar/Wind Harmer
-0.001
228754AB1-001 C
Solar/Wind Harmer
-0.001
228351V2-046C
Solar/Wind Harmer
-0.001
971535AH1-265 GEN
Solar/Wind Harmer
0.381
230407AD2-065 C
Solar/Wind Harmer
0
971011AG2-627 GEN
Solar/Wind Harmer
0.512
218660EHAMPSOLAR C
Solar/Wind Harmer
-0.001
219137THOSOLAR C
Solar/Wind Harmer
0.001
219623KINSLEYBEA C
Solar/Wind Harmer
-0.001
219258KINSLEYDEP C
Solar/Wind Harmer
0
219766PARADISE C
Solar/Wind Harmer
-0.001
219907AC1-030 C
Solar/Wind Harmer
-0.001
219236SOUTHERNHQ C
Solar/Wind Harmer
-0.001
219906AC1-017 C
Solar/Wind Harmer
-0.001
219615MILLCREEK C
Solar/Wind Harmer
-0.001
207500AE2-000G1
Solar/Wind Harmer
41.286
207497AE2-000G2
Solar/Wind Harmer
41.286
207507AE2-000G3
Solar/Wind Harmer
41.286
207487AE2-000G4
Solar/Wind Harmer
41.286
207522AF2-254 C
Solar/Wind Harmer
0.105
970025AG2-016 GEN
Solar/Wind Harmer
0.205
971189AH1-054 GEN
Solar/Wind Harmer
0.085
971667AH1-334 GEN
Solar/Wind Harmer
0.195
214067T20SOLAR
Solar/Wind Harmer
-0.001
219727YARDVSOLFA C
Solar/Wind Harmer
0.001
20714328BYD_X4-031
Solar/Wind Harmer
0.019
20714428HOW_X1-037
Solar/Wind Harmer
-0.001
20720628TIN_W1-124
Solar/Wind Harmer
-0.001
219276PARKLANDSO C
Solar/Wind Harmer
0
20742028HF_AC1-207
Solar/Wind Harmer
-0.001
971521AH1-258 GEN
Solar/Wind Harmer
0.175
219620RIDERU C
Solar/Wind Harmer
-0.001
219817TRENTONSOL C
Solar/Wind Harmer
0.001
967451AG2-055 C O1
Solar/Wind Harmer
197.688
219918AC2-009 C
Solar/Wind Harmer
0
219612MATRIX C
Solar/Wind Harmer
0
218438BLK ROCK C
Solar/Wind Harmer
0
218526CNTRALGAS2 C
Solar/Wind Harmer
0.001
218524CNTRALGAS1 C
Solar/Wind Harmer
0.001
218428ETC SOLAR C
Solar/Wind Harmer
0
217213AMBOY SO C
Solar/Wind Harmer
-0.001
219249CENTRALDIV C
Solar/Wind Harmer
0
218449LINSOLAR C
Solar/Wind Harmer
0.001
217081WEATEXAS C
Solar/Wind Harmer
0
20673828FLE_V3-070
Solar/Wind Harmer
0.055
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
20675428EAM_W2-061
Solar/Wind Harmer
0
217206BARNGR HS C
Solar/Wind Harmer
0
217208PARK ELE C
Solar/Wind Harmer
0
207439AE1-081 C O1
Solar/Wind Harmer
0
20676328BVR_Y1-020
Solar/Wind Harmer
0
20674628WNG_W3-110
Solar/Wind Harmer
-0.001
207511W3-106 GEN
Solar/Wind Harmer
0.033
971009AG2-626 GEN
Solar/Wind Harmer
0.077
971007AG2-625 GEN
Solar/Wind Harmer
0.12
971519AH1-257 GEN
Solar/Wind Harmer
0.117
207437AD2-070 GEN
Solar/Wind Harmer
-0.001
966111AG1-480 GEN
Solar/Wind Harmer
0
966111AG1-480 GEN
Solar/Wind Harmer
1.979
966181AG1-487 GEN
Solar/Wind Harmer
0
966181AG1-487 GEN
Solar/Wind Harmer
2.202
223401AF1-299 GEN
Solar/Wind Helper
0.082
223402AF1-300 C
Solar/Wind Helper
0.082
226910AB2-157 C
Solar/Wind Helper
0.013
G-007ALTFEXP_G-007A->PJM
CMTX
40.539
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.95
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.353
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
16.16
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
3.454
BlueGrassPJM->LTFIMP_BlueG
CLTF
10.757
CBM NorthLTFEXP_CBM-N->PJM
CBM
45.748
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
98.354

Details for PCHBTM2S-PCHBTM1S 500.0 kV Ckt Z1 line l/o PECO_P4_PEACH225_SRT-A/* $ CHESCO $ PECO_P4_PEACH225 $ STBK


Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM2S-PCHBTM1S 500.0 kV Ckt Z1 line
Contingency Name:
PECO_P4_PEACH225_SRT-A/* $ CHESCO $ PECO_P4_PEACH225 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.06 %
Rating:3277.0 MVA
Rating Type:B
MVA to Mitigate:3278.92
MW Contribution:0.55
Bus #Bus NameTypeMW Contribution
200203Y1-065-STG
50/50
20.788
200204Y1-065-CTG1
50/50
13.09
200205Y1-065-CTG2
50/50
13.09
200052ROCKSP 1
50/50
155.304
200053ROCKSP 2
50/50
155.304
200054ROCKSP 3
50/50
153.727
200055ROCKSP 4
50/50
153.727
231914HR8
50/50
4.886
231911HR5
50/50
3.338
231912HR6
50/50
3.338
231913HR7
50/50
3.338
233920W3-032A-CTG1
50/50
5.014
233921W3-032A-STG1
50/50
2.894
232616GEN FOOD
50/50
0.379
232901NORTHST
50/50
20.959
232904IR4
50/50
199.062
232920IR10
50/50
7.557
232921TASLEY2G
50/50
0.819
232905CHERITON_25
50/50
0.311
232912OH NUG1
50/50
20.439
232913OH NUG2
50/50
20.439
232914OH NUG3
50/50
20.439
232915OH NUG4
50/50
20.439
232916OH NUG5
50/50
20.439
232917OH NUG6
50/50
20.439
232918OH NUG7
50/50
20.439
234034AF2-060
50/50
4.088
232926CRISFLD1
50/50
0.248
232907VN8
50/50
53.387
233900O-025 C
50/50
0.149
231940T-011
50/50
0.124
232919VN10
50/50
7.019
232910NRG_G1
50/50
1.076
232911NRG_G2
50/50
1.076
971149AH1-027 GEN
Solar/Wind Harmer
0.57
233987AB2-037 GEN
Solar/Wind Harmer
0
233972AC1-094 C
Solar/Wind Harmer
-0.002
970695AG2-447 GEN
Solar/Wind Harmer
0.455
234033AF1-007_GEN
Solar/Wind Harmer
47.535
970545AG2-347 GEN
Solar/Wind Harmer
195.812
972133AH1-634 GEN
Solar/Wind Harmer
29.668
972069AH1-584 GEN
Solar/Wind Harmer
1.136
972071AH1-585 GEN
Solar/Wind Harmer
1.136
972073AH1-586 GEN
Solar/Wind Harmer
20.44
971747AH1-380 GEN
Solar/Wind Harmer
0.454
233923SMA
Solar/Wind Harmer
-0.002
233998TM1NIN_3.36
Solar/Wind Harmer
-0.002
233997TMININ_4.2
Solar/Wind Harmer
-0.002
233996TM1833_GEN
Solar/Wind Harmer
-0.002
233940AF2-379 C
Solar/Wind Harmer
-0.002
233990AG1-397 GEN
Solar/Wind Harmer
-0.001
233990AG1-397 GEN
Solar/Wind Harmer
3.633
972177AH1-672 GEN
Solar/Wind Harmer
1.703
234015AF2-250 C
Solar/Wind Harmer
-0.001
971195AH1-057 GEN
Solar/Wind Harmer
0.163
960671AF2-358 GEN
Solar/Wind Harmer
2.266
965821AG1-450 GEN
Solar/Wind Harmer
11.329
232426Y1-080 FULL
Solar/Wind Harmer
0
970277AG2-181 GEN
Solar/Wind Harmer
0.634
233946AB2-136 GEN
Solar/Wind Harmer
-0.002
233964AF2-378 GEN
Solar/Wind Harmer
0.001
234041AC1-190 GEN
Solar/Wind Harmer
1.131
233984AB2-036 GEN
Solar/Wind Harmer
2.048
233968AD2-076_GEN
Solar/Wind Harmer
1.08
234014AF1-036_GEN
Solar/Wind Harmer
0.441
970597AG2-380 GEN
Solar/Wind Harmer
8.818
234012AE2-112_GEN
Solar/Wind Harmer
0.375
971983AH1-536 GEN
Solar/Wind Harmer
0.913
970453AG2-297 GEN
Solar/Wind Harmer
0.289
971553AH1-274 GEN
Solar/Wind Harmer
0.246
230422AE1-104_GEN1
Solar/Wind Harmer
59.915
230425AE1-104_GEN2
Solar/Wind Harmer
59.915
945431AF1-208 GEN
Solar/Wind Harmer
0.644
230433AD2-135 GEN
Solar/Wind Harmer
0
970997AG2-616 GEN
Solar/Wind Harmer
0.706
972141AH1-641 GEN
Solar/Wind Harmer
0.212
230430AE1-229_GEN
Solar/Wind Harmer
-0.001
228754AB1-001 C
Solar/Wind Harmer
-0.001
228351V2-046C
Solar/Wind Harmer
-0.001
971535AH1-265 GEN
Solar/Wind Harmer
0.408
230407AD2-065 C
Solar/Wind Harmer
0
971011AG2-627 GEN
Solar/Wind Harmer
0.545
218660EHAMPSOLAR C
Solar/Wind Harmer
-0.001
219137THOSOLAR C
Solar/Wind Harmer
0.001
219623KINSLEYBEA C
Solar/Wind Harmer
-0.001
219258KINSLEYDEP C
Solar/Wind Harmer
0
219766PARADISE C
Solar/Wind Harmer
-0.001
219907AC1-030 C
Solar/Wind Harmer
-0.001
219236SOUTHERNHQ C
Solar/Wind Harmer
-0.001
207500AE2-000G1
Solar/Wind Harmer
41.104
207497AE2-000G2
Solar/Wind Harmer
41.104
207507AE2-000G3
Solar/Wind Harmer
41.104
207487AE2-000G4
Solar/Wind Harmer
41.104
207522AF2-254 C
Solar/Wind Harmer
0.104
219906AC1-017 C
Solar/Wind Harmer
-0.001
219615MILLCREEK C
Solar/Wind Harmer
-0.001
970025AG2-016 GEN
Solar/Wind Harmer
0.203
971189AH1-054 GEN
Solar/Wind Harmer
0.083
971667AH1-334 GEN
Solar/Wind Harmer
0.191
214067T20SOLAR
Solar/Wind Harmer
-0.001
20714328BYD_X4-031
Solar/Wind Harmer
0.018
20714428HOW_X1-037
Solar/Wind Harmer
-0.001
219727YARDVSOLFA C
Solar/Wind Harmer
0.001
20720628TIN_W1-124
Solar/Wind Harmer
-0.001
20742028HF_AC1-207
Solar/Wind Harmer
-0.001
219276PARKLANDSO C
Solar/Wind Harmer
0
971521AH1-258 GEN
Solar/Wind Harmer
0.164
967451AG2-055 C O1
Solar/Wind Harmer
182.412
219620RIDERU C
Solar/Wind Harmer
-0.001
219817TRENTONSOL C
Solar/Wind Harmer
0.001
219918AC2-009 C
Solar/Wind Harmer
0
219612MATRIX C
Solar/Wind Harmer
0
218438BLK ROCK C
Solar/Wind Harmer
0
218526CNTRALGAS2 C
Solar/Wind Harmer
0.001
218524CNTRALGAS1 C
Solar/Wind Harmer
0.001
218428ETC SOLAR C
Solar/Wind Harmer
0
217213AMBOY SO C
Solar/Wind Harmer
-0.001
219249CENTRALDIV C
Solar/Wind Harmer
0
218449LINSOLAR C
Solar/Wind Harmer
0
217081WEATEXAS C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
20673828FLE_V3-070
Solar/Wind Harmer
0.046
217206BARNGR HS C
Solar/Wind Harmer
0
217208PARK ELE C
Solar/Wind Harmer
0
20675428EAM_W2-061
Solar/Wind Harmer
0
207439AE1-081 C O1
Solar/Wind Harmer
0
20676328BVR_Y1-020
Solar/Wind Harmer
0
20674628WNG_W3-110
Solar/Wind Harmer
-0.001
207511W3-106 GEN
Solar/Wind Harmer
0.026
G-007ALTFEXP_G-007A->PJM
CMTX
36.405
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.662
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.191
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
15.329
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
3.283
BlueGrassPJM->LTFIMP_BlueG
CLTF
10.226
CBM NorthLTFEXP_CBM-N->PJM
CBM
35.689
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
83.75

Details for PCHBTM2S-PCHBTM1S 500.0 kV Ckt Z2 line l/o PECO_P4_PEACH235_SRT-A/* $ CHESCO $ PECO_P4_PEACH235 $ STBK


Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM2S-PCHBTM1S 500.0 kV Ckt Z2 line
Contingency Name:
PECO_P4_PEACH235_SRT-A/* $ CHESCO $ PECO_P4_PEACH235 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:118.38 %
Rating:3022.0 MVA
Rating Type:B
MVA to Mitigate:3577.59
MW Contribution:0.47
Bus #Bus NameTypeMW Contribution
200034PCHBTM 2
50/50
357.435
200203Y1-065-STG
50/50
19.367
200204Y1-065-CTG1
50/50
12.195
200205Y1-065-CTG2
50/50
12.195
200052ROCKSP 1
50/50
144.687
200053ROCKSP 2
50/50
144.687
200054ROCKSP 3
50/50
143.218
200055ROCKSP 4
50/50
143.218
231914HR8
50/50
4.441
231911HR5
50/50
3.034
231912HR6
50/50
3.034
231913HR7
50/50
3.034
233920W3-032A-CTG1
50/50
4.548
233921W3-032A-STG1
50/50
2.626
232616GEN FOOD
50/50
0.343
232901NORTHST
50/50
19.013
232904IR4
50/50
180.587
232920IR10
50/50
6.855
232921TASLEY2G
50/50
0.743
232905CHERITON_25
50/50
0.282
232912OH NUG1
50/50
18.542
232913OH NUG2
50/50
18.542
232914OH NUG3
50/50
18.542
232915OH NUG4
50/50
18.542
232916OH NUG5
50/50
18.542
232917OH NUG6
50/50
18.542
232918OH NUG7
50/50
18.542
234034AF2-060
50/50
3.708
232926CRISFLD1
50/50
0.225
232907VN8
50/50
48.434
233900O-025 C
50/50
0.135
231940T-011
50/50
0.112
232919VN10
50/50
6.367
232910NRG_G1
50/50
0.976
232911NRG_G2
50/50
0.976
200035PCHBTM 3
50/50
-13.724
971149AH1-027 GEN
Solar/Wind Harmer
0.517
233987AB2-037 GEN
Solar/Wind Harmer
0
233972AC1-094 C
Solar/Wind Harmer
-0.002
970695AG2-447 GEN
Solar/Wind Harmer
0.413
234033AF1-007_GEN
Solar/Wind Harmer
43.123
970545AG2-347 GEN
Solar/Wind Harmer
177.638
972133AH1-634 GEN
Solar/Wind Harmer
26.915
972069AH1-584 GEN
Solar/Wind Harmer
1.03
972071AH1-585 GEN
Solar/Wind Harmer
1.03
972073AH1-586 GEN
Solar/Wind Harmer
18.543
971747AH1-380 GEN
Solar/Wind Harmer
0.412
233923SMA
Solar/Wind Harmer
-0.002
233998TM1NIN_3.36
Solar/Wind Harmer
-0.002
233997TMININ_4.2
Solar/Wind Harmer
-0.002
233996TM1833_GEN
Solar/Wind Harmer
-0.002
233940AF2-379 C
Solar/Wind Harmer
-0.002
233990AG1-397 GEN
Solar/Wind Harmer
-0.001
233990AG1-397 GEN
Solar/Wind Harmer
3.296
972177AH1-672 GEN
Solar/Wind Harmer
1.544
234015AF2-250 C
Solar/Wind Harmer
-0.001
971195AH1-057 GEN
Solar/Wind Harmer
0.148
960671AF2-358 GEN
Solar/Wind Harmer
2.055
965821AG1-450 GEN
Solar/Wind Harmer
10.277
232426Y1-080 FULL
Solar/Wind Harmer
0
970277AG2-181 GEN
Solar/Wind Harmer
0.575
233946AB2-136 GEN
Solar/Wind Harmer
-0.002
233964AF2-378 GEN
Solar/Wind Harmer
0.001
234041AC1-190 GEN
Solar/Wind Harmer
1.026
233984AB2-036 GEN
Solar/Wind Harmer
1.857
233968AD2-076_GEN
Solar/Wind Harmer
0.979
234014AF1-036_GEN
Solar/Wind Harmer
0.4
970597AG2-380 GEN
Solar/Wind Harmer
7.991
234012AE2-112_GEN
Solar/Wind Harmer
0.34
971983AH1-536 GEN
Solar/Wind Harmer
0.827
970453AG2-297 GEN
Solar/Wind Harmer
0.254
971553AH1-274 GEN
Solar/Wind Harmer
0.214
230422AE1-104_GEN1
Solar/Wind Harmer
52.227
230425AE1-104_GEN2
Solar/Wind Harmer
52.227
945431AF1-208 GEN
Solar/Wind Harmer
0.56
230433AD2-135 GEN
Solar/Wind Harmer
0
970997AG2-616 GEN
Solar/Wind Harmer
0.613
972141AH1-641 GEN
Solar/Wind Harmer
0.184
230430AE1-229_GEN
Solar/Wind Harmer
-0.001
228754AB1-001 C
Solar/Wind Harmer
-0.001
228351V2-046C
Solar/Wind Harmer
-0.001
971535AH1-265 GEN
Solar/Wind Harmer
0.354
230407AD2-065 C
Solar/Wind Harmer
0
971011AG2-627 GEN
Solar/Wind Harmer
0.471
218660EHAMPSOLAR C
Solar/Wind Harmer
-0.001
219137THOSOLAR C
Solar/Wind Harmer
0.001
219623KINSLEYBEA C
Solar/Wind Harmer
-0.001
219258KINSLEYDEP C
Solar/Wind Harmer
0
219766PARADISE C
Solar/Wind Harmer
-0.001
219907AC1-030 C
Solar/Wind Harmer
-0.001
219236SOUTHERNHQ C
Solar/Wind Harmer
-0.001
207500AE2-000G1
Solar/Wind Harmer
34.466
207497AE2-000G2
Solar/Wind Harmer
34.466
207507AE2-000G3
Solar/Wind Harmer
34.466
207487AE2-000G4
Solar/Wind Harmer
34.466
207522AF2-254 C
Solar/Wind Harmer
0.087
219906AC1-017 C
Solar/Wind Harmer
-0.001
219615MILLCREEK C
Solar/Wind Harmer
-0.001
970025AG2-016 GEN
Solar/Wind Harmer
0.17
971189AH1-054 GEN
Solar/Wind Harmer
0.069
971667AH1-334 GEN
Solar/Wind Harmer
0.159
214067T20SOLAR
Solar/Wind Harmer
-0.001
20714328BYD_X4-031
Solar/Wind Harmer
0.015
20714428HOW_X1-037
Solar/Wind Harmer
0
219727YARDVSOLFA C
Solar/Wind Harmer
0.001
20720628TIN_W1-124
Solar/Wind Harmer
-0.001
20742028HF_AC1-207
Solar/Wind Harmer
-0.001
971521AH1-258 GEN
Solar/Wind Harmer
0.133
219276PARKLANDSO C
Solar/Wind Harmer
0
967451AG2-055 C O1
Solar/Wind Harmer
147.131
219620RIDERU C
Solar/Wind Harmer
-0.001
219817TRENTONSOL C
Solar/Wind Harmer
0
219918AC2-009 C
Solar/Wind Harmer
0
219612MATRIX C
Solar/Wind Harmer
0
218438BLK ROCK C
Solar/Wind Harmer
0
218526CNTRALGAS2 C
Solar/Wind Harmer
0
218524CNTRALGAS1 C
Solar/Wind Harmer
0
218428ETC SOLAR C
Solar/Wind Harmer
0
217213AMBOY SO C
Solar/Wind Harmer
-0.001
219249CENTRALDIV C
Solar/Wind Harmer
0
218449LINSOLAR C
Solar/Wind Harmer
0
217081WEATEXAS C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
G-007ALTFEXP_G-007A->PJM
CMTX
28.927
HAMLETPJM->LTFIMP_HAMLET
CLTF
2.946
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.767
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
12.482
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
2.677
BlueGrassPJM->LTFIMP_BlueG
CLTF
8.336
CBM NorthLTFEXP_CBM-N->PJM
CBM
25.968
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
64.498

Details for PCHBTMTP-COOPER2 230.0 kV Ckt 1 line l/o PECO_P1-2_5012_SRT-A


Base Case Flowgate

Area:PECO
Facility Description:
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line
Contingency Name:
PECO_P1-2_5012_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:145.16 %
Rating:639.0 MVA
Rating Type:B
MVA to Mitigate:927.56
MW Contribution:0.13
Bus #Bus NameTypeMW Contribution
213508CON10-11
50/50
0.991
213508CON10-11
50/50
0.991
213518CONOW8-9
50/50
0.991
213518CONOW8-9
50/50
0.991
213515CONOW3-4
50/50
1.041
213517CONOW7
50/50
1.041
213515CONOW3-4
50/50
0.949
213516CONOW5-6
50/50
0.949
213514CONOW1-2
50/50
0.778
213516CONOW5-6
50/50
0.778
213514CONOW1-2
50/50
0.739
231918WEST 1
50/50
0.098
213893PHLISST1
50/50
1.432
213890PHLISCT3
50/50
0.992
213888PHLISCT1
50/50
0.992
213889PHLISCT2
50/50
0.992
231909HR2
50/50
0.598
231916EM3
50/50
0.412
231917EM10
50/50
0.087
231919CHRIST1
50/50
2.327
231920CHRIST2
50/50
2.327
231901EM4
50/50
0.829
231908HR1
50/50
0.595
231910HR3
50/50
0.595
213740LIBE_ST1
50/50
1.193
213738LIBE_CT1
50/50
0.916
213739LIBE_CT2
50/50
0.916
231505HR4
50/50
0.934
971983AH1-536 GEN
Solar/Wind Harmer
0.175
233968AD2-076_GEN
Solar/Wind Harmer
0.2
234014AF1-036_GEN
Solar/Wind Harmer
0.082
970597AG2-380 GEN
Solar/Wind Harmer
1.636
234012AE2-112_GEN
Solar/Wind Harmer
0.07
233984AB2-036 GEN
Solar/Wind Harmer
0.367
234041AC1-190 GEN
Solar/Wind Harmer
0.188
233987AB2-037 GEN
Solar/Wind Harmer
0
233964AF2-378 GEN
Solar/Wind Harmer
0
233946AB2-136 GEN
Solar/Wind Harmer
0
232426Y1-080 FULL
Solar/Wind Harmer
0
970277AG2-181 GEN
Solar/Wind Harmer
0.105
960671AF2-358 GEN
Solar/Wind Harmer
0.374
965821AG1-450 GEN
Solar/Wind Harmer
1.869
233940AF2-379 C
Solar/Wind Harmer
0
234015AF2-250 C
Solar/Wind Harmer
0
971195AH1-057 GEN
Solar/Wind Harmer
0.027
233923SMA
Solar/Wind Harmer
0
233998TM1NIN_3.36
Solar/Wind Harmer
0
233997TMININ_4.2
Solar/Wind Harmer
0
233996TM1833_GEN
Solar/Wind Harmer
0
233990AG1-397 GEN
Solar/Wind Harmer
0
971747AH1-380 GEN
Solar/Wind Harmer
0.074
233990AG1-397 GEN
Solar/Wind Harmer
0.59
972069AH1-584 GEN
Solar/Wind Harmer
0.184
972071AH1-585 GEN
Solar/Wind Harmer
0.184
972073AH1-586 GEN
Solar/Wind Harmer
3.315
234033AF1-007_GEN
Solar/Wind Harmer
7.648
970545AG2-347 GEN
Solar/Wind Harmer
31.505
972133AH1-634 GEN
Solar/Wind Harmer
4.773
972177AH1-672 GEN
Solar/Wind Harmer
0.274
971149AH1-027 GEN
Solar/Wind Harmer
0.089
233972AC1-094 C
Solar/Wind Harmer
0
970695AG2-447 GEN
Solar/Wind Harmer
0.07
219137THOSOLAR C
Solar/Wind Harmer
0
219258KINSLEYDEP C
Solar/Wind Harmer
0
219766PARADISE C
Solar/Wind Harmer
0
219623KINSLEYBEA C
Solar/Wind Harmer
0
971011AG2-627 GEN
Solar/Wind Harmer
0.131
219907AC1-030 C
Solar/Wind Harmer
0
228351V2-046C
Solar/Wind Harmer
0
219236SOUTHERNHQ C
Solar/Wind Harmer
0
970997AG2-616 GEN
Solar/Wind Harmer
0.162
972141AH1-641 GEN
Solar/Wind Harmer
0.049
230430AE1-229_GEN
Solar/Wind Harmer
0
945431AF1-208 GEN
Solar/Wind Harmer
0.145
219906AC1-017 C
Solar/Wind Harmer
0
219615MILLCREEK C
Solar/Wind Harmer
0
971535AH1-265 GEN
Solar/Wind Harmer
0.094
971553AH1-274 GEN
Solar/Wind Harmer
0.053
230433AD2-135 GEN
Solar/Wind Harmer
0
230407AD2-065 C
Solar/Wind Harmer
0
970453AG2-297 GEN
Solar/Wind Harmer
0.06
218660EHAMPSOLAR C
Solar/Wind Harmer
0
230422AE1-104_GEN1
Solar/Wind Harmer
12.966
230425AE1-104_GEN2
Solar/Wind Harmer
12.966
228754AB1-001 C
Solar/Wind Harmer
0
214067T20SOLAR
Solar/Wind Harmer
0
219727YARDVSOLFA C
Solar/Wind Harmer
0
207522AF2-254 C
Solar/Wind Harmer
0.029
207500AE2-000G1
Solar/Wind Harmer
11.012
207497AE2-000G2
Solar/Wind Harmer
11.012
207507AE2-000G3
Solar/Wind Harmer
11.012
207487AE2-000G4
Solar/Wind Harmer
11.012
971189AH1-054 GEN
Solar/Wind Harmer
0.023
219276PARKLANDSO C
Solar/Wind Harmer
0
970025AG2-016 GEN
Solar/Wind Harmer
0.055
971667AH1-334 GEN
Solar/Wind Harmer
0.053
219620RIDERU C
Solar/Wind Harmer
0
219817TRENTONSOL C
Solar/Wind Harmer
0
219918AC2-009 C
Solar/Wind Harmer
0
20714328BYD_X4-031
Solar/Wind Harmer
0.005
20714428HOW_X1-037
Solar/Wind Harmer
0
20720628TIN_W1-124
Solar/Wind Harmer
0
219612MATRIX C
Solar/Wind Harmer
0
218438BLK ROCK C
Solar/Wind Harmer
0
20742028HF_AC1-207
Solar/Wind Harmer
0
971521AH1-258 GEN
Solar/Wind Harmer
0.05
967451AG2-055 C O1
Solar/Wind Harmer
56.631
218526CNTRALGAS2 C
Solar/Wind Harmer
0
223401AF1-299 GEN
Solar/Wind Helper
0.063
223402AF1-300 C
Solar/Wind Helper
0.063
208923BUSO V4-027
Solar/Wind Helper
0.015
G-007ALTFEXP_G-007A->PJM
CMTX
12.048
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.129
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.666
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.379
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.931
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.9
CBM NorthLTFEXP_CBM-N->PJM
CBM
15.238
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
30.513

Details for PCHBTMTP-COOPER2 230.0 kV Ckt 1 line l/o PJM_500_BG_P4_5_CNSTN_C_SRT-A


Base Case Flowgate

Area:PECO
Facility Description:
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line
Contingency Name:
PJM_500_BG_P4_5_CNSTN_C_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:142.58 %
Rating:639.0 MVA
Rating Type:B
MVA to Mitigate:911.08
MW Contribution:0.13
Bus #Bus NameTypeMW Contribution
213508CON10-11
50/50
0.991
213508CON10-11
50/50
0.991
213518CONOW8-9
50/50
0.991
213518CONOW8-9
50/50
0.991
213515CONOW3-4
50/50
1.041
213517CONOW7
50/50
1.041
213515CONOW3-4
50/50
0.949
213516CONOW5-6
50/50
0.949
213514CONOW1-2
50/50
0.778
213516CONOW5-6
50/50
0.778
213514CONOW1-2
50/50
0.739
971983AH1-536 GEN
Solar/Wind Harmer
0.175
233968AD2-076_GEN
Solar/Wind Harmer
0.2
234014AF1-036_GEN
Solar/Wind Harmer
0.082
970597AG2-380 GEN
Solar/Wind Harmer
1.636
234012AE2-112_GEN
Solar/Wind Harmer
0.07
233984AB2-036 GEN
Solar/Wind Harmer
0.367
234041AC1-190 GEN
Solar/Wind Harmer
0.188
233987AB2-037 GEN
Solar/Wind Harmer
0
233964AF2-378 GEN
Solar/Wind Harmer
0
233946AB2-136 GEN
Solar/Wind Harmer
0
232426Y1-080 FULL
Solar/Wind Harmer
0
970277AG2-181 GEN
Solar/Wind Harmer
0.105
960671AF2-358 GEN
Solar/Wind Harmer
0.374
965821AG1-450 GEN
Solar/Wind Harmer
1.869
233940AF2-379 C
Solar/Wind Harmer
0
234015AF2-250 C
Solar/Wind Harmer
0
971195AH1-057 GEN
Solar/Wind Harmer
0.027
233923SMA
Solar/Wind Harmer
0
233998TM1NIN_3.36
Solar/Wind Harmer
0
233997TMININ_4.2
Solar/Wind Harmer
0
233996TM1833_GEN
Solar/Wind Harmer
0
233990AG1-397 GEN
Solar/Wind Harmer
0
971747AH1-380 GEN
Solar/Wind Harmer
0.074
233990AG1-397 GEN
Solar/Wind Harmer
0.59
972069AH1-584 GEN
Solar/Wind Harmer
0.184
972071AH1-585 GEN
Solar/Wind Harmer
0.184
972073AH1-586 GEN
Solar/Wind Harmer
3.315
234033AF1-007_GEN
Solar/Wind Harmer
7.648
970545AG2-347 GEN
Solar/Wind Harmer
31.505
972133AH1-634 GEN
Solar/Wind Harmer
4.773
972177AH1-672 GEN
Solar/Wind Harmer
0.274
971149AH1-027 GEN
Solar/Wind Harmer
0.089
233972AC1-094 C
Solar/Wind Harmer
0
970695AG2-447 GEN
Solar/Wind Harmer
0.07
219137THOSOLAR C
Solar/Wind Harmer
0
219258KINSLEYDEP C
Solar/Wind Harmer
0
219766PARADISE C
Solar/Wind Harmer
0
219623KINSLEYBEA C
Solar/Wind Harmer
0
971011AG2-627 GEN
Solar/Wind Harmer
0.131
219907AC1-030 C
Solar/Wind Harmer
0
228351V2-046C
Solar/Wind Harmer
0
219236SOUTHERNHQ C
Solar/Wind Harmer
0
970997AG2-616 GEN
Solar/Wind Harmer
0.162
972141AH1-641 GEN
Solar/Wind Harmer
0.049
230430AE1-229_GEN
Solar/Wind Harmer
0
945431AF1-208 GEN
Solar/Wind Harmer
0.145
219906AC1-017 C
Solar/Wind Harmer
0
219615MILLCREEK C
Solar/Wind Harmer
0
971535AH1-265 GEN
Solar/Wind Harmer
0.094
971553AH1-274 GEN
Solar/Wind Harmer
0.053
230433AD2-135 GEN
Solar/Wind Harmer
0
230407AD2-065 C
Solar/Wind Harmer
0
970453AG2-297 GEN
Solar/Wind Harmer
0.06
218660EHAMPSOLAR C
Solar/Wind Harmer
0
230422AE1-104_GEN1
Solar/Wind Harmer
12.966
230425AE1-104_GEN2
Solar/Wind Harmer
12.966
228754AB1-001 C
Solar/Wind Harmer
0
214067T20SOLAR
Solar/Wind Harmer
0
219727YARDVSOLFA C
Solar/Wind Harmer
0
207522AF2-254 C
Solar/Wind Harmer
0.029
207500AE2-000G1
Solar/Wind Harmer
11.012
207497AE2-000G2
Solar/Wind Harmer
11.012
207507AE2-000G3
Solar/Wind Harmer
11.012
207487AE2-000G4
Solar/Wind Harmer
11.012
971189AH1-054 GEN
Solar/Wind Harmer
0.023
219276PARKLANDSO C
Solar/Wind Harmer
0
970025AG2-016 GEN
Solar/Wind Harmer
0.055
971667AH1-334 GEN
Solar/Wind Harmer
0.053
219620RIDERU C
Solar/Wind Harmer
0
219817TRENTONSOL C
Solar/Wind Harmer
0
219918AC2-009 C
Solar/Wind Harmer
0
20714328BYD_X4-031
Solar/Wind Harmer
0.005
20714428HOW_X1-037
Solar/Wind Harmer
0
20720628TIN_W1-124
Solar/Wind Harmer
0
219612MATRIX C
Solar/Wind Harmer
0
218438BLK ROCK C
Solar/Wind Harmer
0
20742028HF_AC1-207
Solar/Wind Harmer
0
971521AH1-258 GEN
Solar/Wind Harmer
0.05
967451AG2-055 C O1
Solar/Wind Harmer
56.631
218526CNTRALGAS2 C
Solar/Wind Harmer
0
223401AF1-299 GEN
Solar/Wind Helper
0.063
223402AF1-300 C
Solar/Wind Helper
0.063
208923BUSO V4-027
Solar/Wind Helper
0.015
G-007ALTFEXP_G-007A->PJM
CMTX
12.048
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.129
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.666
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.379
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.931
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.9
CBM NorthLTFEXP_CBM-N->PJM
CBM
15.238
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
30.513

Details for PCHBTMTP-COOPER2 230.0 kV Ckt 1 line l/o PECO_P4_PEACH235_SRT-A/* $ CHESCO $ PECO_P4_PEACH235 $ STBK


Base Case Flowgate

Area:PECO
Facility Description:
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line
Contingency Name:
PECO_P4_PEACH235_SRT-A/* $ CHESCO $ PECO_P4_PEACH235 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:142.56 %
Rating:639.0 MVA
Rating Type:B
MVA to Mitigate:910.96
MW Contribution:0.13
Bus #Bus NameTypeMW Contribution
213508CON10-11
50/50
0.991
213508CON10-11
50/50
0.991
213518CONOW8-9
50/50
0.991
213518CONOW8-9
50/50
0.991
213515CONOW3-4
50/50
1.041
213517CONOW7
50/50
1.041
213515CONOW3-4
50/50
0.949
213516CONOW5-6
50/50
0.949
213514CONOW1-2
50/50
0.778
213516CONOW5-6
50/50
0.778
213514CONOW1-2
50/50
0.739
971983AH1-536 GEN
Solar/Wind Harmer
0.175
233968AD2-076_GEN
Solar/Wind Harmer
0.201
234014AF1-036_GEN
Solar/Wind Harmer
0.082
970597AG2-380 GEN
Solar/Wind Harmer
1.637
234012AE2-112_GEN
Solar/Wind Harmer
0.07
233984AB2-036 GEN
Solar/Wind Harmer
0.367
234041AC1-190 GEN
Solar/Wind Harmer
0.188
233987AB2-037 GEN
Solar/Wind Harmer
0
233964AF2-378 GEN
Solar/Wind Harmer
0
233946AB2-136 GEN
Solar/Wind Harmer
0
232426Y1-080 FULL
Solar/Wind Harmer
0
970277AG2-181 GEN
Solar/Wind Harmer
0.105
960671AF2-358 GEN
Solar/Wind Harmer
0.374
965821AG1-450 GEN
Solar/Wind Harmer
1.87
233940AF2-379 C
Solar/Wind Harmer
0
234015AF2-250 C
Solar/Wind Harmer
0
971195AH1-057 GEN
Solar/Wind Harmer
0.027
233923SMA
Solar/Wind Harmer
0
233998TM1NIN_3.36
Solar/Wind Harmer
0
233997TMININ_4.2
Solar/Wind Harmer
0
233996TM1833_GEN
Solar/Wind Harmer
0
233990AG1-397 GEN
Solar/Wind Harmer
0
971747AH1-380 GEN
Solar/Wind Harmer
0.074
233990AG1-397 GEN
Solar/Wind Harmer
0.59
972069AH1-584 GEN
Solar/Wind Harmer
0.184
972071AH1-585 GEN
Solar/Wind Harmer
0.184
972073AH1-586 GEN
Solar/Wind Harmer
3.317
234033AF1-007_GEN
Solar/Wind Harmer
7.652
970545AG2-347 GEN
Solar/Wind Harmer
31.523
972133AH1-634 GEN
Solar/Wind Harmer
4.776
972177AH1-672 GEN
Solar/Wind Harmer
0.274
971149AH1-027 GEN
Solar/Wind Harmer
0.089
233972AC1-094 C
Solar/Wind Harmer
0
970695AG2-447 GEN
Solar/Wind Harmer
0.07
219137THOSOLAR C
Solar/Wind Harmer
0
219258KINSLEYDEP C
Solar/Wind Harmer
0
219766PARADISE C
Solar/Wind Harmer
0
219623KINSLEYBEA C
Solar/Wind Harmer
0
971011AG2-627 GEN
Solar/Wind Harmer
0.132
219907AC1-030 C
Solar/Wind Harmer
0
228351V2-046C
Solar/Wind Harmer
0
219236SOUTHERNHQ C
Solar/Wind Harmer
0
970997AG2-616 GEN
Solar/Wind Harmer
0.162
972141AH1-641 GEN
Solar/Wind Harmer
0.049
230430AE1-229_GEN
Solar/Wind Harmer
0
945431AF1-208 GEN
Solar/Wind Harmer
0.145
219906AC1-017 C
Solar/Wind Harmer
0
219615MILLCREEK C
Solar/Wind Harmer
0
971535AH1-265 GEN
Solar/Wind Harmer
0.094
971553AH1-274 GEN
Solar/Wind Harmer
0.053
230433AD2-135 GEN
Solar/Wind Harmer
0
230407AD2-065 C
Solar/Wind Harmer
0
970453AG2-297 GEN
Solar/Wind Harmer
0.06
218660EHAMPSOLAR C
Solar/Wind Harmer
0
230422AE1-104_GEN1
Solar/Wind Harmer
12.971
230425AE1-104_GEN2
Solar/Wind Harmer
12.971
228754AB1-001 C
Solar/Wind Harmer
0
214067T20SOLAR
Solar/Wind Harmer
0
219727YARDVSOLFA C
Solar/Wind Harmer
0
207522AF2-254 C
Solar/Wind Harmer
0.029
207500AE2-000G1
Solar/Wind Harmer
11.015
207497AE2-000G2
Solar/Wind Harmer
11.015
207507AE2-000G3
Solar/Wind Harmer
11.015
207487AE2-000G4
Solar/Wind Harmer
11.015
971189AH1-054 GEN
Solar/Wind Harmer
0.023
219276PARKLANDSO C
Solar/Wind Harmer
0
970025AG2-016 GEN
Solar/Wind Harmer
0.055
971667AH1-334 GEN
Solar/Wind Harmer
0.053
219817TRENTONSOL C
Solar/Wind Harmer
0
219620RIDERU C
Solar/Wind Harmer
0
219918AC2-009 C
Solar/Wind Harmer
0
20714328BYD_X4-031
Solar/Wind Harmer
0.005
20714428HOW_X1-037
Solar/Wind Harmer
0
20720628TIN_W1-124
Solar/Wind Harmer
0
219612MATRIX C
Solar/Wind Harmer
0
218438BLK ROCK C
Solar/Wind Harmer
0
20742028HF_AC1-207
Solar/Wind Harmer
0
971521AH1-258 GEN
Solar/Wind Harmer
0.05
967451AG2-055 C O1
Solar/Wind Harmer
56.646
218526CNTRALGAS2 C
Solar/Wind Harmer
0
223401AF1-299 GEN
Solar/Wind Helper
0.063
223402AF1-300 C
Solar/Wind Helper
0.063
208923BUSO V4-027
Solar/Wind Helper
0.015
G-007ALTFEXP_G-007A->PJM
CMTX
12.051
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.129
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.666
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.38
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.931
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.901
CBM NorthLTFEXP_CBM-N->PJM
CBM
15.241
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
30.52

Details for PCHBTMTP-COOPER2 230.0 kV Ckt 1 line l/o PECO_P1-2_5014_SRT-A/* $ CHESCO $ PECO_P1-2_5012 $ L


Base Case Flowgate

Area:PECO
Facility Description:
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line
Contingency Name:
PECO_P1-2_5014_SRT-A/* $ CHESCO $ PECO_P1-2_5012 $ L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:107.87 %
Rating:639.0 MVA
Rating Type:B
MVA to Mitigate:689.32
MW Contribution:0.13
Bus #Bus NameTypeMW Contribution
213508CON10-11
50/50
0.988
213508CON10-11
50/50
0.988
213518CONOW8-9
50/50
0.988
213518CONOW8-9
50/50
0.988
213515CONOW3-4
50/50
1.038
213517CONOW7
50/50
1.038
213515CONOW3-4
50/50
0.946
213516CONOW5-6
50/50
0.946
213514CONOW1-2
50/50
0.776
213516CONOW5-6
50/50
0.776
213514CONOW1-2
50/50
0.737
970431AG2-281 GEN
50/50
4.747
231918WEST 1
50/50
0.104
232416X2-083
50/50
0.015
231919CHRIST1
50/50
2.482
231920CHRIST2
50/50
2.482
231909HR2
50/50
0.632
231916EM3
50/50
0.435
231917EM10
50/50
0.092
231901EM4
50/50
0.877
231908HR1
50/50
0.629
231910HR3
50/50
0.629
231902DC CT7
50/50
0.443
231915DC CT6
50/50
0.443
231906DC3 NUG
50/50
0.355
231907DC10
50/50
0.115
231131BLOOM ENRGY
50/50
0.122
231505HR4
50/50
0.951
971983AH1-536 GEN
Solar/Wind Harmer
0.195
233968AD2-076_GEN
Solar/Wind Harmer
0.224
234014AF1-036_GEN
Solar/Wind Harmer
0.092
970597AG2-380 GEN
Solar/Wind Harmer
1.831
234012AE2-112_GEN
Solar/Wind Harmer
0.078
233984AB2-036 GEN
Solar/Wind Harmer
0.412
234041AC1-190 GEN
Solar/Wind Harmer
0.214
233987AB2-037 GEN
Solar/Wind Harmer
0
233964AF2-378 GEN
Solar/Wind Harmer
0
233946AB2-136 GEN
Solar/Wind Harmer
0
232426Y1-080 FULL
Solar/Wind Harmer
0
970277AG2-181 GEN
Solar/Wind Harmer
0.119
960671AF2-358 GEN
Solar/Wind Harmer
0.425
965821AG1-450 GEN
Solar/Wind Harmer
2.125
233940AF2-379 C
Solar/Wind Harmer
0
234015AF2-250 C
Solar/Wind Harmer
0
971195AH1-057 GEN
Solar/Wind Harmer
0.03
233923SMA
Solar/Wind Harmer
0
233998TM1NIN_3.36
Solar/Wind Harmer
0
233997TMININ_4.2
Solar/Wind Harmer
0
233996TM1833_GEN
Solar/Wind Harmer
0
971747AH1-380 GEN
Solar/Wind Harmer
0.084
233990AG1-397 GEN
Solar/Wind Harmer
0
233990AG1-397 GEN
Solar/Wind Harmer
0.672
972069AH1-584 GEN
Solar/Wind Harmer
0.21
972071AH1-585 GEN
Solar/Wind Harmer
0.21
972073AH1-586 GEN
Solar/Wind Harmer
3.778
234033AF1-007_GEN
Solar/Wind Harmer
8.724
970545AG2-347 GEN
Solar/Wind Harmer
35.936
972133AH1-634 GEN
Solar/Wind Harmer
5.445
972177AH1-672 GEN
Solar/Wind Harmer
0.312
971149AH1-027 GEN
Solar/Wind Harmer
0.102
233972AC1-094 C
Solar/Wind Harmer
0
970695AG2-447 GEN
Solar/Wind Harmer
0.081
971011AG2-627 GEN
Solar/Wind Harmer
0.13
228351V2-046C
Solar/Wind Harmer
0
970997AG2-616 GEN
Solar/Wind Harmer
0.162
972141AH1-641 GEN
Solar/Wind Harmer
0.049
945431AF1-208 GEN
Solar/Wind Harmer
0.146
230430AE1-229_GEN
Solar/Wind Harmer
0
219137THOSOLAR C
Solar/Wind Harmer
0
970453AG2-297 GEN
Solar/Wind Harmer
0.061
971553AH1-274 GEN
Solar/Wind Harmer
0.054
219258KINSLEYDEP C
Solar/Wind Harmer
0
230433AD2-135 GEN
Solar/Wind Harmer
0
971535AH1-265 GEN
Solar/Wind Harmer
0.094
230407AD2-065 C
Solar/Wind Harmer
0
219623KINSLEYBEA C
Solar/Wind Harmer
0
230422AE1-104_GEN1
Solar/Wind Harmer
13.092
230425AE1-104_GEN2
Solar/Wind Harmer
13.092
219766PARADISE C
Solar/Wind Harmer
0
228754AB1-001 C
Solar/Wind Harmer
0
219907AC1-030 C
Solar/Wind Harmer
0
219236SOUTHERNHQ C
Solar/Wind Harmer
0
218660EHAMPSOLAR C
Solar/Wind Harmer
0
219906AC1-017 C
Solar/Wind Harmer
0
219615MILLCREEK C
Solar/Wind Harmer
0
214067T20SOLAR
Solar/Wind Harmer
0
207522AF2-254 C
Solar/Wind Harmer
0.027
207500AE2-000G1
Solar/Wind Harmer
10.314
207497AE2-000G2
Solar/Wind Harmer
10.314
207507AE2-000G3
Solar/Wind Harmer
10.314
207487AE2-000G4
Solar/Wind Harmer
10.314
970025AG2-016 GEN
Solar/Wind Harmer
0.052
971189AH1-054 GEN
Solar/Wind Harmer
0.021
219727YARDVSOLFA C
Solar/Wind Harmer
0
971667AH1-334 GEN
Solar/Wind Harmer
0.049
219276PARKLANDSO C
Solar/Wind Harmer
0
967451AG2-055 C O1
Solar/Wind Harmer
50.18
223401AF1-299 GEN
Solar/Wind Helper
0.053
223402AF1-300 C
Solar/Wind Helper
0.053
208923BUSO V4-027
Solar/Wind Helper
0.013
G-007ALTFEXP_G-007A->PJM
CMTX
10.511
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.959
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.567
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
3.752
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.798
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.487
CBM NorthLTFEXP_CBM-N->PJM
CBM
12.425
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
25.801

Details for [AG2-627] PCHBTMTP-COOPER2 230.0 kV Ckt 1 line l/o PJM_500_BG_P4_5_CNSTN_C_SRT-A


Base Case Flowgate

Area:PECO
Facility Description:
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line
Contingency Name:
PJM_500_BG_P4_5_CNSTN_C_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.53 %
Rating:639.0 MVA
Rating Type:B
MVA to Mitigate:655.17
MW Contribution:2.63
IPD Plant:AG2-627
Bus #Bus NameTypeMW Contribution
971011AG2-627 GEN
PJM_IPD
2.63

Details for [AG2-627] PCHBTMTP-COOPER2 230.0 kV Ckt 1 line l/o PECO_P4_PEACH235_SRT-A/* $ CHESCO $ PECO_P4_PEACH235 $ STBK


Base Case Flowgate

Area:PECO
Facility Description:
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line
Contingency Name:
PECO_P4_PEACH235_SRT-A/* $ CHESCO $ PECO_P4_PEACH235 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.49 %
Rating:639.0 MVA
Rating Type:B
MVA to Mitigate:654.89
MW Contribution:2.63
IPD Plant:AG2-627
Bus #Bus NameTypeMW Contribution
971011AG2-627 GEN
PJM_IPD
2.631

Details for [AG2-627] PCHBTMTP-COOPER2 230.0 kV Ckt 1 line l/o PECO_P1-2_5012_SRT-A


Base Case Flowgate

Area:PECO
Facility Description:
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line
Contingency Name:
PECO_P1-2_5012_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.46 %
Rating:639.0 MVA
Rating Type:B
MVA to Mitigate:654.72
MW Contribution:2.63
IPD Plant:AG2-627
Bus #Bus NameTypeMW Contribution
971011AG2-627 GEN
PJM_IPD
2.63

Details for [AG2-627] PCHBTMTP-COOPER2 230.0 kV Ckt 1 line l/o BGE_P4_GRACETON_51_SRT-A


Base Case Flowgate

Area:PECO
Facility Description:
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line
Contingency Name:
BGE_P4_GRACETON_51_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.46 %
Rating:639.0 MVA
Rating Type:B
MVA to Mitigate:654.72
MW Contribution:2.63
IPD Plant:AG2-627
Bus #Bus NameTypeMW Contribution
971011AG2-627 GEN
PJM_IPD
2.63

Details for RICHMOND35-WANEETA3 230.0 kV Ckt 1 line l/o PECO_P4_CHICH045_SRT-A/* $ DELCO $ PECO_P4_CHICH045 $ STBK


Base Case Flowgate

Area:PECO
Facility Description:
RICHMOND35-WANEETA3 230.0 kV Ckt 1 line
Contingency Name:
PECO_P4_CHICH045_SRT-A/* $ DELCO $ PECO_P4_CHICH045 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.65 %
Rating:1201.0 MVA
Rating Type:B
MVA to Mitigate:1232.79
MW Contribution:0.48
Bus #Bus NameTypeMW Contribution
213918RICHMD91
50/50
22.534
213919RICHMD92
50/50
22.534
219126CAMDEN_CTG
50/50
1.514
219267WHEELBRDEPTF
50/50
1.316
219124CAMDEN_STG
50/50
1.235
219286CAMD CO RR
50/50
0.452
219240MANTUACREK E
50/50
0.675
219726BAT.STORG E
50/50
0.33
219230EAGLE PT CT1
50/50
1.596
219229EAGLE PT ST
50/50
0.798
219235Y2-105
50/50
0.475
219231EAGLE PT CT2
50/50
1.596
230406ST-CC
50/50
5.392
230404GT1-CC
50/50
3.996
230405GT2-CC
50/50
3.996
228304LOGAN
50/50
29.745
228304LOGAN
50/50
26.753
228307PCLP GT
50/50
14.456
213400COVANTA DELA
50/50
3.621
219766PARADISE C
Solar/Wind Harmer
-0.002
219258KINSLEYDEP C
Solar/Wind Harmer
-0.001
219623KINSLEYBEA C
Solar/Wind Harmer
-0.001
219907AC1-030 C
Solar/Wind Harmer
-0.002
219236SOUTHERNHQ C
Solar/Wind Harmer
-0.001
219137THOSOLAR C
Solar/Wind Harmer
0.001
219906AC1-017 C
Solar/Wind Harmer
-0.001
219615MILLCREEK C
Solar/Wind Harmer
-0.001
971011AG2-627 GEN
Solar/Wind Harmer
0.48
228351V2-046C
Solar/Wind Harmer
-0.001
218660EHAMPSOLAR C
Solar/Wind Harmer
-0.001
970997AG2-616 GEN
Solar/Wind Harmer
0.558
972141AH1-641 GEN
Solar/Wind Harmer
0.167
230430AE1-229_GEN
Solar/Wind Harmer
-0.001
230407AD2-065 C
Solar/Wind Harmer
0
945431AF1-208 GEN
Solar/Wind Harmer
0.488
971535AH1-265 GEN
Solar/Wind Harmer
0.316
230433AD2-135 GEN
Solar/Wind Harmer
0
971553AH1-274 GEN
Solar/Wind Harmer
0.168
970453AG2-297 GEN
Solar/Wind Harmer
0.178
230422AE1-104_GEN1
Solar/Wind Harmer
38.53
230425AE1-104_GEN2
Solar/Wind Harmer
38.53
228754AB1-001 C
Solar/Wind Harmer
-0.001
214067T20SOLAR
Solar/Wind Harmer
-0.001
207522AF2-254 C
Solar/Wind Harmer
0.073
219727YARDVSOLFA C
Solar/Wind Harmer
0.001
971189AH1-054 GEN
Solar/Wind Harmer
0.052
207500AE2-000G1
Solar/Wind Harmer
23.806
207497AE2-000G2
Solar/Wind Harmer
23.806
207507AE2-000G3
Solar/Wind Harmer
23.806
207487AE2-000G4
Solar/Wind Harmer
23.806
970025AG2-016 GEN
Solar/Wind Harmer
0.118
219276PARKLANDSO C
Solar/Wind Harmer
0
971667AH1-334 GEN
Solar/Wind Harmer
0.111
233972AC1-094 C
Solar/Wind Harmer
0
970695AG2-447 GEN
Solar/Wind Harmer
0.1
971149AH1-027 GEN
Solar/Wind Harmer
0.124
972177AH1-672 GEN
Solar/Wind Harmer
0.364
234033AF1-007_GEN
Solar/Wind Harmer
10.127
970545AG2-347 GEN
Solar/Wind Harmer
41.716
972133AH1-634 GEN
Solar/Wind Harmer
6.321
972069AH1-584 GEN
Solar/Wind Harmer
0.241
972071AH1-585 GEN
Solar/Wind Harmer
0.241
972073AH1-586 GEN
Solar/Wind Harmer
4.332
233990AG1-397 GEN
Solar/Wind Harmer
0
233990AG1-397 GEN
Solar/Wind Harmer
0.77
971747AH1-380 GEN
Solar/Wind Harmer
0.096
234015AF2-250 C
Solar/Wind Harmer
0
971195AH1-057 GEN
Solar/Wind Harmer
0.035
233923SMA
Solar/Wind Harmer
0
233998TM1NIN_3.36
Solar/Wind Harmer
0
233997TMININ_4.2
Solar/Wind Harmer
0
233996TM1833_GEN
Solar/Wind Harmer
0
233940AF2-379 C
Solar/Wind Harmer
0
960671AF2-358 GEN
Solar/Wind Harmer
0.477
965821AG1-450 GEN
Solar/Wind Harmer
2.383
232426Y1-080 FULL
Solar/Wind Harmer
0
970277AG2-181 GEN
Solar/Wind Harmer
0.133
233946AB2-136 GEN
Solar/Wind Harmer
0
233964AF2-378 GEN
Solar/Wind Harmer
0
234041AC1-190 GEN
Solar/Wind Harmer
0.237
233987AB2-037 GEN
Solar/Wind Harmer
0
233984AB2-036 GEN
Solar/Wind Harmer
0.422
233968AD2-076_GEN
Solar/Wind Harmer
0.222
234014AF1-036_GEN
Solar/Wind Harmer
0.091
970597AG2-380 GEN
Solar/Wind Harmer
1.81
234012AE2-112_GEN
Solar/Wind Harmer
0.077
971983AH1-536 GEN
Solar/Wind Harmer
0.187
20714328BYD_X4-031
Solar/Wind Harmer
0.009
20714428HOW_X1-037
Solar/Wind Harmer
0
20720628TIN_W1-124
Solar/Wind Harmer
0
219612MATRIX C
Solar/Wind Harmer
0
218438BLK ROCK C
Solar/Wind Harmer
0
971521AH1-258 GEN
Solar/Wind Harmer
0.075
20742028HF_AC1-207
Solar/Wind Harmer
0
219918AC2-009 C
Solar/Wind Harmer
0
219620RIDERU C
Solar/Wind Harmer
0
219817TRENTONSOL C
Solar/Wind Harmer
0
967451AG2-055 C O1
Solar/Wind Harmer
66.527
218526CNTRALGAS2 C
Solar/Wind Harmer
0
218524CNTRALGAS1 C
Solar/Wind Harmer
0
218428ETC SOLAR C
Solar/Wind Harmer
0
217213AMBOY SO C
Solar/Wind Harmer
0
G-007ALTFEXP_G-007A->PJM
CMTX
14.347
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.659
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.399
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
2.954
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.637
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.982
CBM NorthLTFEXP_CBM-N->PJM
CBM
7.697
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
26.06

Details for RICHMOND35-WANEETA3 230.0 kV Ckt 1 line l/o PECO_P4_CHICH195_SRT-A/* $ DELCO $ PECO_P4_CHICH195 $ STBK


Base Case Flowgate

Area:PECO
Facility Description:
RICHMOND35-WANEETA3 230.0 kV Ckt 1 line
Contingency Name:
PECO_P4_CHICH195_SRT-A/* $ DELCO $ PECO_P4_CHICH195 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.65 %
Rating:1201.0 MVA
Rating Type:B
MVA to Mitigate:1232.77
MW Contribution:0.48
Bus #Bus NameTypeMW Contribution
213918RICHMD91
50/50
22.534
213919RICHMD92
50/50
22.534
219126CAMDEN_CTG
50/50
1.514
219267WHEELBRDEPTF
50/50
1.316
219124CAMDEN_STG
50/50
1.235
219286CAMD CO RR
50/50
0.452
219240MANTUACREK E
50/50
0.675
219726BAT.STORG E
50/50
0.33
219230EAGLE PT CT1
50/50
1.596
219229EAGLE PT ST
50/50
0.798
219235Y2-105
50/50
0.475
219231EAGLE PT CT2
50/50
1.596
230406ST-CC
50/50
5.392
230404GT1-CC
50/50
3.996
230405GT2-CC
50/50
3.996
228304LOGAN
50/50
29.745
228304LOGAN
50/50
26.753
228307PCLP GT
50/50
14.456
213400COVANTA DELA
50/50
3.621
219766PARADISE C
Solar/Wind Harmer
-0.002
219258KINSLEYDEP C
Solar/Wind Harmer
-0.001
219623KINSLEYBEA C
Solar/Wind Harmer
-0.001
219907AC1-030 C
Solar/Wind Harmer
-0.002
219236SOUTHERNHQ C
Solar/Wind Harmer
-0.001
219137THOSOLAR C
Solar/Wind Harmer
0.001
219906AC1-017 C
Solar/Wind Harmer
-0.001
219615MILLCREEK C
Solar/Wind Harmer
-0.001
971011AG2-627 GEN
Solar/Wind Harmer
0.48
228351V2-046C
Solar/Wind Harmer
-0.001
218660EHAMPSOLAR C
Solar/Wind Harmer
-0.001
970997AG2-616 GEN
Solar/Wind Harmer
0.558
972141AH1-641 GEN
Solar/Wind Harmer
0.167
230430AE1-229_GEN
Solar/Wind Harmer
-0.001
230407AD2-065 C
Solar/Wind Harmer
0
945431AF1-208 GEN
Solar/Wind Harmer
0.488
971535AH1-265 GEN
Solar/Wind Harmer
0.316
230433AD2-135 GEN
Solar/Wind Harmer
0
971553AH1-274 GEN
Solar/Wind Harmer
0.168
970453AG2-297 GEN
Solar/Wind Harmer
0.178
230422AE1-104_GEN1
Solar/Wind Harmer
38.53
230425AE1-104_GEN2
Solar/Wind Harmer
38.53
228754AB1-001 C
Solar/Wind Harmer
-0.001
214067T20SOLAR
Solar/Wind Harmer
-0.001
207522AF2-254 C
Solar/Wind Harmer
0.073
219727YARDVSOLFA C
Solar/Wind Harmer
0.001
971189AH1-054 GEN
Solar/Wind Harmer
0.052
207500AE2-000G1
Solar/Wind Harmer
23.806
207497AE2-000G2
Solar/Wind Harmer
23.806
207507AE2-000G3
Solar/Wind Harmer
23.806
207487AE2-000G4
Solar/Wind Harmer
23.806
970025AG2-016 GEN
Solar/Wind Harmer
0.118
219276PARKLANDSO C
Solar/Wind Harmer
0
971667AH1-334 GEN
Solar/Wind Harmer
0.111
233972AC1-094 C
Solar/Wind Harmer
0
970695AG2-447 GEN
Solar/Wind Harmer
0.1
971149AH1-027 GEN
Solar/Wind Harmer
0.124
972177AH1-672 GEN
Solar/Wind Harmer
0.364
234033AF1-007_GEN
Solar/Wind Harmer
10.127
970545AG2-347 GEN
Solar/Wind Harmer
41.716
972133AH1-634 GEN
Solar/Wind Harmer
6.321
972069AH1-584 GEN
Solar/Wind Harmer
0.241
972071AH1-585 GEN
Solar/Wind Harmer
0.241
972073AH1-586 GEN
Solar/Wind Harmer
4.332
233990AG1-397 GEN
Solar/Wind Harmer
0
233990AG1-397 GEN
Solar/Wind Harmer
0.77
971747AH1-380 GEN
Solar/Wind Harmer
0.096
234015AF2-250 C
Solar/Wind Harmer
0
971195AH1-057 GEN
Solar/Wind Harmer
0.035
233923SMA
Solar/Wind Harmer
0
233998TM1NIN_3.36
Solar/Wind Harmer
0
233997TMININ_4.2
Solar/Wind Harmer
0
233996TM1833_GEN
Solar/Wind Harmer
0
233940AF2-379 C
Solar/Wind Harmer
0
960671AF2-358 GEN
Solar/Wind Harmer
0.477
965821AG1-450 GEN
Solar/Wind Harmer
2.383
232426Y1-080 FULL
Solar/Wind Harmer
0
970277AG2-181 GEN
Solar/Wind Harmer
0.133
233946AB2-136 GEN
Solar/Wind Harmer
0
233964AF2-378 GEN
Solar/Wind Harmer
0
234041AC1-190 GEN
Solar/Wind Harmer
0.237
233987AB2-037 GEN
Solar/Wind Harmer
0
233984AB2-036 GEN
Solar/Wind Harmer
0.422
233968AD2-076_GEN
Solar/Wind Harmer
0.222
234014AF1-036_GEN
Solar/Wind Harmer
0.091
970597AG2-380 GEN
Solar/Wind Harmer
1.81
234012AE2-112_GEN
Solar/Wind Harmer
0.077
971983AH1-536 GEN
Solar/Wind Harmer
0.187
20714328BYD_X4-031
Solar/Wind Harmer
0.009
20714428HOW_X1-037
Solar/Wind Harmer
0
20720628TIN_W1-124
Solar/Wind Harmer
0
219612MATRIX C
Solar/Wind Harmer
0
218438BLK ROCK C
Solar/Wind Harmer
0
971521AH1-258 GEN
Solar/Wind Harmer
0.075
20742028HF_AC1-207
Solar/Wind Harmer
0
219918AC2-009 C
Solar/Wind Harmer
0
219620RIDERU C
Solar/Wind Harmer
0
219817TRENTONSOL C
Solar/Wind Harmer
0
967451AG2-055 C O1
Solar/Wind Harmer
66.527
218526CNTRALGAS2 C
Solar/Wind Harmer
0
218524CNTRALGAS1 C
Solar/Wind Harmer
0
218428ETC SOLAR C
Solar/Wind Harmer
0
217213AMBOY SO C
Solar/Wind Harmer
0
G-007ALTFEXP_G-007A->PJM
CMTX
14.347
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.659
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.399
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
2.954
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.637
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.982
CBM NorthLTFEXP_CBM-N->PJM
CBM
7.697
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
26.06

Details for RICHMOND35-WANEETA3 230.0 kV Ckt 1 line l/o PECO_P2-2_CHI230B1_SRT-A/* $ DELCO $ PECO_P2-2_CHI230B1 $ B


Base Case Flowgate

Area:PECO
Facility Description:
RICHMOND35-WANEETA3 230.0 kV Ckt 1 line
Contingency Name:
PECO_P2-2_CHI230B1_SRT-A/* $ DELCO $ PECO_P2-2_CHI230B1 $ B
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:102.65 %
Rating:1201.0 MVA
Rating Type:B
MVA to Mitigate:1232.77
MW Contribution:0.48
Bus #Bus NameTypeMW Contribution
213918RICHMD91
50/50
22.534
213919RICHMD92
50/50
22.534
219126CAMDEN_CTG
50/50
1.514
219267WHEELBRDEPTF
50/50
1.316
219124CAMDEN_STG
50/50
1.235
219286CAMD CO RR
50/50
0.452
219240MANTUACREK E
50/50
0.675
219726BAT.STORG E
50/50
0.33
219230EAGLE PT CT1
50/50
1.596
219229EAGLE PT ST
50/50
0.798
219235Y2-105
50/50
0.475
219231EAGLE PT CT2
50/50
1.596
230406ST-CC
50/50
5.392
230404GT1-CC
50/50
3.996
230405GT2-CC
50/50
3.996
228304LOGAN
50/50
29.745
228304LOGAN
50/50
26.753
228307PCLP GT
50/50
14.456
213400COVANTA DELA
50/50
3.621
219766PARADISE C
Solar/Wind Harmer
-0.002
219258KINSLEYDEP C
Solar/Wind Harmer
-0.001
219623KINSLEYBEA C
Solar/Wind Harmer
-0.001
219907AC1-030 C
Solar/Wind Harmer
-0.002
219236SOUTHERNHQ C
Solar/Wind Harmer
-0.001
219137THOSOLAR C
Solar/Wind Harmer
0.001
219906AC1-017 C
Solar/Wind Harmer
-0.001
219615MILLCREEK C
Solar/Wind Harmer
-0.001
971011AG2-627 GEN
Solar/Wind Harmer
0.48
228351V2-046C
Solar/Wind Harmer
-0.001
218660EHAMPSOLAR C
Solar/Wind Harmer
-0.001
970997AG2-616 GEN
Solar/Wind Harmer
0.558
972141AH1-641 GEN
Solar/Wind Harmer
0.167
230430AE1-229_GEN
Solar/Wind Harmer
-0.001
230407AD2-065 C
Solar/Wind Harmer
0
945431AF1-208 GEN
Solar/Wind Harmer
0.488
971535AH1-265 GEN
Solar/Wind Harmer
0.316
230433AD2-135 GEN
Solar/Wind Harmer
0
971553AH1-274 GEN
Solar/Wind Harmer
0.168
970453AG2-297 GEN
Solar/Wind Harmer
0.178
230422AE1-104_GEN1
Solar/Wind Harmer
38.53
230425AE1-104_GEN2
Solar/Wind Harmer
38.53
228754AB1-001 C
Solar/Wind Harmer
-0.001
214067T20SOLAR
Solar/Wind Harmer
-0.001
207522AF2-254 C
Solar/Wind Harmer
0.073
219727YARDVSOLFA C
Solar/Wind Harmer
0.001
971189AH1-054 GEN
Solar/Wind Harmer
0.052
207500AE2-000G1
Solar/Wind Harmer
23.806
207497AE2-000G2
Solar/Wind Harmer
23.806
207507AE2-000G3
Solar/Wind Harmer
23.806
207487AE2-000G4
Solar/Wind Harmer
23.806
970025AG2-016 GEN
Solar/Wind Harmer
0.118
219276PARKLANDSO C
Solar/Wind Harmer
0
971667AH1-334 GEN
Solar/Wind Harmer
0.111
233972AC1-094 C
Solar/Wind Harmer
0
970695AG2-447 GEN
Solar/Wind Harmer
0.1
971149AH1-027 GEN
Solar/Wind Harmer
0.124
972177AH1-672 GEN
Solar/Wind Harmer
0.364
234033AF1-007_GEN
Solar/Wind Harmer
10.127
970545AG2-347 GEN
Solar/Wind Harmer
41.716
972133AH1-634 GEN
Solar/Wind Harmer
6.321
972069AH1-584 GEN
Solar/Wind Harmer
0.241
972071AH1-585 GEN
Solar/Wind Harmer
0.241
972073AH1-586 GEN
Solar/Wind Harmer
4.332
233990AG1-397 GEN
Solar/Wind Harmer
0
233990AG1-397 GEN
Solar/Wind Harmer
0.77
971747AH1-380 GEN
Solar/Wind Harmer
0.096
234015AF2-250 C
Solar/Wind Harmer
0
971195AH1-057 GEN
Solar/Wind Harmer
0.035
233923SMA
Solar/Wind Harmer
0
233998TM1NIN_3.36
Solar/Wind Harmer
0
233997TMININ_4.2
Solar/Wind Harmer
0
233996TM1833_GEN
Solar/Wind Harmer
0
233940AF2-379 C
Solar/Wind Harmer
0
960671AF2-358 GEN
Solar/Wind Harmer
0.477
965821AG1-450 GEN
Solar/Wind Harmer
2.383
232426Y1-080 FULL
Solar/Wind Harmer
0
970277AG2-181 GEN
Solar/Wind Harmer
0.133
233946AB2-136 GEN
Solar/Wind Harmer
0
233964AF2-378 GEN
Solar/Wind Harmer
0
234041AC1-190 GEN
Solar/Wind Harmer
0.237
233987AB2-037 GEN
Solar/Wind Harmer
0
233984AB2-036 GEN
Solar/Wind Harmer
0.422
233968AD2-076_GEN
Solar/Wind Harmer
0.222
234014AF1-036_GEN
Solar/Wind Harmer
0.091
970597AG2-380 GEN
Solar/Wind Harmer
1.81
234012AE2-112_GEN
Solar/Wind Harmer
0.077
971983AH1-536 GEN
Solar/Wind Harmer
0.187
20714328BYD_X4-031
Solar/Wind Harmer
0.009
20714428HOW_X1-037
Solar/Wind Harmer
0
20720628TIN_W1-124
Solar/Wind Harmer
0
219612MATRIX C
Solar/Wind Harmer
0
218438BLK ROCK C
Solar/Wind Harmer
0
971521AH1-258 GEN
Solar/Wind Harmer
0.075
20742028HF_AC1-207
Solar/Wind Harmer
0
219918AC2-009 C
Solar/Wind Harmer
0
219620RIDERU C
Solar/Wind Harmer
0
219817TRENTONSOL C
Solar/Wind Harmer
0
967451AG2-055 C O1
Solar/Wind Harmer
66.527
218526CNTRALGAS2 C
Solar/Wind Harmer
0
218524CNTRALGAS1 C
Solar/Wind Harmer
0
218428ETC SOLAR C
Solar/Wind Harmer
0
217213AMBOY SO C
Solar/Wind Harmer
0
G-007ALTFEXP_G-007A->PJM
CMTX
14.347
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.659
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.399
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
2.954
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.637
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.982
CBM NorthLTFEXP_CBM-N->PJM
CBM
7.697
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
26.06

Details for RICHMOND35-WANEETA3 230.0 kV Ckt 1 line l/o PECO_P4_CHICH435_SRT-A/* $ DELCO $ PECO_P4_CHICH435 $ STBK


Base Case Flowgate

Area:PECO
Facility Description:
RICHMOND35-WANEETA3 230.0 kV Ckt 1 line
Contingency Name:
PECO_P4_CHICH435_SRT-A/* $ DELCO $ PECO_P4_CHICH435 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.64 %
Rating:1201.0 MVA
Rating Type:B
MVA to Mitigate:1232.76
MW Contribution:0.48
Bus #Bus NameTypeMW Contribution
213918RICHMD91
50/50
22.534
213919RICHMD92
50/50
22.534
219126CAMDEN_CTG
50/50
1.514
219267WHEELBRDEPTF
50/50
1.316
219124CAMDEN_STG
50/50
1.235
219286CAMD CO RR
50/50
0.452
219240MANTUACREK E
50/50
0.675
219726BAT.STORG E
50/50
0.33
219230EAGLE PT CT1
50/50
1.596
219229EAGLE PT ST
50/50
0.798
219235Y2-105
50/50
0.475
219231EAGLE PT CT2
50/50
1.596
230406ST-CC
50/50
5.392
230404GT1-CC
50/50
3.996
230405GT2-CC
50/50
3.996
228304LOGAN
50/50
29.747
228304LOGAN
50/50
26.754
228307PCLP GT
50/50
14.457
213400COVANTA DELA
50/50
3.622
219766PARADISE C
Solar/Wind Harmer
-0.002
219258KINSLEYDEP C
Solar/Wind Harmer
-0.001
219623KINSLEYBEA C
Solar/Wind Harmer
-0.001
219907AC1-030 C
Solar/Wind Harmer
-0.002
219236SOUTHERNHQ C
Solar/Wind Harmer
-0.001
219137THOSOLAR C
Solar/Wind Harmer
0.001
219906AC1-017 C
Solar/Wind Harmer
-0.001
219615MILLCREEK C
Solar/Wind Harmer
-0.001
971011AG2-627 GEN
Solar/Wind Harmer
0.48
228351V2-046C
Solar/Wind Harmer
-0.001
218660EHAMPSOLAR C
Solar/Wind Harmer
-0.001
970997AG2-616 GEN
Solar/Wind Harmer
0.558
972141AH1-641 GEN
Solar/Wind Harmer
0.167
230430AE1-229_GEN
Solar/Wind Harmer
-0.001
230407AD2-065 C
Solar/Wind Harmer
0
945431AF1-208 GEN
Solar/Wind Harmer
0.488
971535AH1-265 GEN
Solar/Wind Harmer
0.316
230433AD2-135 GEN
Solar/Wind Harmer
0
971553AH1-274 GEN
Solar/Wind Harmer
0.168
970453AG2-297 GEN
Solar/Wind Harmer
0.178
230422AE1-104_GEN1
Solar/Wind Harmer
38.531
230425AE1-104_GEN2
Solar/Wind Harmer
38.531
228754AB1-001 C
Solar/Wind Harmer
-0.001
214067T20SOLAR
Solar/Wind Harmer
-0.001
207522AF2-254 C
Solar/Wind Harmer
0.073
219727YARDVSOLFA C
Solar/Wind Harmer
0.001
971189AH1-054 GEN
Solar/Wind Harmer
0.052
207500AE2-000G1
Solar/Wind Harmer
23.806
207497AE2-000G2
Solar/Wind Harmer
23.806
207507AE2-000G3
Solar/Wind Harmer
23.806
207487AE2-000G4
Solar/Wind Harmer
23.806
970025AG2-016 GEN
Solar/Wind Harmer
0.118
219276PARKLANDSO C
Solar/Wind Harmer
0
971667AH1-334 GEN
Solar/Wind Harmer
0.111
233972AC1-094 C
Solar/Wind Harmer
0
970695AG2-447 GEN
Solar/Wind Harmer
0.1
971149AH1-027 GEN
Solar/Wind Harmer
0.124
972177AH1-672 GEN
Solar/Wind Harmer
0.364
234033AF1-007_GEN
Solar/Wind Harmer
10.126
970545AG2-347 GEN
Solar/Wind Harmer
41.713
972133AH1-634 GEN
Solar/Wind Harmer
6.32
972069AH1-584 GEN
Solar/Wind Harmer
0.241
972071AH1-585 GEN
Solar/Wind Harmer
0.241
972073AH1-586 GEN
Solar/Wind Harmer
4.331
233990AG1-397 GEN
Solar/Wind Harmer
0
233990AG1-397 GEN
Solar/Wind Harmer
0.77
971747AH1-380 GEN
Solar/Wind Harmer
0.096
234015AF2-250 C
Solar/Wind Harmer
0
971195AH1-057 GEN
Solar/Wind Harmer
0.035
233923SMA
Solar/Wind Harmer
0
233998TM1NIN_3.36
Solar/Wind Harmer
0
233997TMININ_4.2
Solar/Wind Harmer
0
233996TM1833_GEN
Solar/Wind Harmer
0
233940AF2-379 C
Solar/Wind Harmer
0
960671AF2-358 GEN
Solar/Wind Harmer
0.477
965821AG1-450 GEN
Solar/Wind Harmer
2.383
232426Y1-080 FULL
Solar/Wind Harmer
0
970277AG2-181 GEN
Solar/Wind Harmer
0.133
233946AB2-136 GEN
Solar/Wind Harmer
0
233964AF2-378 GEN
Solar/Wind Harmer
0
234041AC1-190 GEN
Solar/Wind Harmer
0.237
233987AB2-037 GEN
Solar/Wind Harmer
0
233984AB2-036 GEN
Solar/Wind Harmer
0.422
233968AD2-076_GEN
Solar/Wind Harmer
0.222
234014AF1-036_GEN
Solar/Wind Harmer
0.09
970597AG2-380 GEN
Solar/Wind Harmer
1.81
234012AE2-112_GEN
Solar/Wind Harmer
0.077
971983AH1-536 GEN
Solar/Wind Harmer
0.187
20714328BYD_X4-031
Solar/Wind Harmer
0.009
20714428HOW_X1-037
Solar/Wind Harmer
0
20720628TIN_W1-124
Solar/Wind Harmer
0
219612MATRIX C
Solar/Wind Harmer
0
218438BLK ROCK C
Solar/Wind Harmer
0
971521AH1-258 GEN
Solar/Wind Harmer
0.075
20742028HF_AC1-207
Solar/Wind Harmer
0
219918AC2-009 C
Solar/Wind Harmer
0
219620RIDERU C
Solar/Wind Harmer
0
219817TRENTONSOL C
Solar/Wind Harmer
0
967451AG2-055 C O1
Solar/Wind Harmer
66.529
218526CNTRALGAS2 C
Solar/Wind Harmer
0
218524CNTRALGAS1 C
Solar/Wind Harmer
0
218428ETC SOLAR C
Solar/Wind Harmer
0
217213AMBOY SO C
Solar/Wind Harmer
0
G-007ALTFEXP_G-007A->PJM
CMTX
14.348
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.659
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.399
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
2.954
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.637
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.982
CBM NorthLTFEXP_CBM-N->PJM
CBM
7.698
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
26.061

Details for RL_230-KEEN_230 230.0 kV Ckt 1 line l/o DPL_P1_2_CKT 5036_SRT-A


Base Case Flowgate

Area:DP&L
Facility Description:
RL_230-KEEN_230 230.0 kV Ckt 1 line
Contingency Name:
DPL_P1_2_CKT 5036_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.73 %
Rating:1171.0 MVA
Rating Type:B
MVA to Mitigate:1214.64
MW Contribution:0.26
Bus #Bus NameTypeMW Contribution
231914HR8
50/50
4.614
231911HR5
50/50
3.152
231912HR6
50/50
3.152
231913HR7
50/50
3.152
232899W1-062
50/50
0.738
232900DEMECSMY
50/50
0.724
233920W3-032A-CTG1
50/50
2.853
233921W3-032A-STG1
50/50
1.647
232616GEN FOOD
50/50
0.215
232901NORTHST
50/50
11.928
231902DC CT7
50/50
1.27
231915DC CT6
50/50
1.27
231906DC3 NUG
50/50
1.016
231907DC10
50/50
0.329
200039HOPE CG1
50/50
24.84
200036SALEM-G1
50/50
18.002
200037SALEM-G2
50/50
17.873
972251AH1-710 GEN
50/50
65.642
231131BLOOM ENRGY
50/50
0.342
232813VAUGHN
50/50
0.711
232910NRG_G1
50/50
0.398
232911NRG_G2
50/50
0.398
228203P06
50/50
16.332
228202CUMB CT
50/50
14.954
228206SHRMN CT
50/50
14.697
228732V1-021 C
50/50
0.299
957251AF2-019 GEN
50/50
1.255
945731AF1-238 GEN
50/50
3.066
945741AF1-239 GEN
50/50
1.839
233972AC1-094 C
Solar/Wind Harmer
-0.002
970695AG2-447 GEN
Solar/Wind Harmer
0.312
971149AH1-027 GEN
Solar/Wind Harmer
0.324
972177AH1-672 GEN
Solar/Wind Harmer
0.644
970453AG2-297 GEN
Solar/Wind Harmer
0.155
971553AH1-274 GEN
Solar/Wind Harmer
0.128
230422AE1-104_GEN1
Solar/Wind Harmer
31.669
230425AE1-104_GEN2
Solar/Wind Harmer
31.669
228754AB1-001 C
Solar/Wind Harmer
-0.001
234033AF1-007_GEN
Solar/Wind Harmer
15.323
970545AG2-347 GEN
Solar/Wind Harmer
63.12
972133AH1-634 GEN
Solar/Wind Harmer
9.564
230433AD2-135 GEN
Solar/Wind Harmer
0
945431AF1-208 GEN
Solar/Wind Harmer
0.324
970997AG2-616 GEN
Solar/Wind Harmer
0.35
972141AH1-641 GEN
Solar/Wind Harmer
0.105
230430AE1-229_GEN
Solar/Wind Harmer
-0.001
971535AH1-265 GEN
Solar/Wind Harmer
0.205
230407AD2-065 C
Solar/Wind Harmer
0
228351V2-046C
Solar/Wind Harmer
-0.001
971011AG2-627 GEN
Solar/Wind Harmer
0.258
233990AG1-397 GEN
Solar/Wind Harmer
0
233990AG1-397 GEN
Solar/Wind Harmer
0.947
972069AH1-584 GEN
Solar/Wind Harmer
0.292
972071AH1-585 GEN
Solar/Wind Harmer
0.292
972073AH1-586 GEN
Solar/Wind Harmer
5.251
971747AH1-380 GEN
Solar/Wind Harmer
0.115
218660EHAMPSOLAR C
Solar/Wind Harmer
-0.001
234015AF2-250 C
Solar/Wind Harmer
0
971195AH1-057 GEN
Solar/Wind Harmer
0.04
233923SMA
Solar/Wind Harmer
-0.001
233998TM1NIN_3.36
Solar/Wind Harmer
-0.001
233997TMININ_4.2
Solar/Wind Harmer
-0.001
233996TM1833_GEN
Solar/Wind Harmer
-0.001
207500AE2-000G1
Solar/Wind Harmer
20.957
207497AE2-000G2
Solar/Wind Harmer
20.957
207507AE2-000G3
Solar/Wind Harmer
20.957
207487AE2-000G4
Solar/Wind Harmer
20.957
233940AF2-379 C
Solar/Wind Harmer
-0.001
970025AG2-016 GEN
Solar/Wind Harmer
0.103
207522AF2-254 C
Solar/Wind Harmer
0.051
219623KINSLEYBEA C
Solar/Wind Harmer
0
971189AH1-054 GEN
Solar/Wind Harmer
0.042
971667AH1-334 GEN
Solar/Wind Harmer
0.096
219137THOSOLAR C
Solar/Wind Harmer
0
219258KINSLEYDEP C
Solar/Wind Harmer
0
219766PARADISE C
Solar/Wind Harmer
0
20714328BYD_X4-031
Solar/Wind Harmer
0.009
20714428HOW_X1-037
Solar/Wind Harmer
0
20720628TIN_W1-124
Solar/Wind Harmer
0
219907AC1-030 C
Solar/Wind Harmer
0
219236SOUTHERNHQ C
Solar/Wind Harmer
0
219906AC1-017 C
Solar/Wind Harmer
0
219615MILLCREEK C
Solar/Wind Harmer
0
20742028HF_AC1-207
Solar/Wind Harmer
0
971521AH1-258 GEN
Solar/Wind Harmer
0.082
967451AG2-055 C O1
Solar/Wind Harmer
92.962
219727YARDVSOLFA C
Solar/Wind Harmer
0
960671AF2-358 GEN
Solar/Wind Harmer
0.394
965821AG1-450 GEN
Solar/Wind Harmer
1.968
219817TRENTONSOL C
Solar/Wind Harmer
0
219620RIDERU C
Solar/Wind Harmer
0
219276PARKLANDSO C
Solar/Wind Harmer
0
232426Y1-080 FULL
Solar/Wind Harmer
0
970277AG2-181 GEN
Solar/Wind Harmer
0.108
214067T20SOLAR
Solar/Wind Harmer
0
219918AC2-009 C
Solar/Wind Harmer
0
219612MATRIX C
Solar/Wind Harmer
0
218438BLK ROCK C
Solar/Wind Harmer
0
233946AB2-136 GEN
Solar/Wind Harmer
0
233964AF2-378 GEN
Solar/Wind Harmer
0
218524CNTRALGAS1 C
Solar/Wind Harmer
0
218526CNTRALGAS2 C
Solar/Wind Harmer
0
218428ETC SOLAR C
Solar/Wind Harmer
0
217213AMBOY SO C
Solar/Wind Harmer
0
234041AC1-190 GEN
Solar/Wind Harmer
0.168
219249CENTRALDIV C
Solar/Wind Harmer
0
218449LINSOLAR C
Solar/Wind Harmer
0
217081WEATEXAS C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
217206BARNGR HS C
Solar/Wind Harmer
0
217208PARK ELE C
Solar/Wind Harmer
0
20673828FLE_V3-070
Solar/Wind Harmer
0.022
20675428EAM_W2-061
Solar/Wind Harmer
0
207439AE1-081 C O1
Solar/Wind Harmer
0
20676328BVR_Y1-020
Solar/Wind Harmer
0
20674628WNG_W3-110
Solar/Wind Harmer
0
207511W3-106 GEN
Solar/Wind Harmer
0.013
G-007ALTFEXP_G-007A->PJM
CMTX
18.03
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.182
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.705
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.852
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
1.037
BlueGrassPJM->LTFIMP_BlueG
CLTF
3.231
CBM NorthLTFEXP_CBM-N->PJM
CBM
18.614
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
40.997

Details for RL_230-KEEN_230 230.0 kV Ckt 1 line l/o DPL_P4_2_REDLION-KEENEY AT50_SRT-A


Base Case Flowgate

Area:DP&L
Facility Description:
RL_230-KEEN_230 230.0 kV Ckt 1 line
Contingency Name:
DPL_P4_2_REDLION-KEENEY AT50_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.37 %
Rating:1171.0 MVA
Rating Type:B
MVA to Mitigate:1210.44
MW Contribution:0.24
Bus #Bus NameTypeMW Contribution
231914HR8
50/50
4.861
231911HR5
50/50
3.321
231912HR6
50/50
3.321
231913HR7
50/50
3.321
232899W1-062
50/50
0.775
232900DEMECSMY
50/50
0.76
231902DC CT7
50/50
1.366
231915DC CT6
50/50
1.366
231906DC3 NUG
50/50
1.092
231907DC10
50/50
0.354
233920W3-032A-CTG1
50/50
3
233921W3-032A-STG1
50/50
1.732
232616GEN FOOD
50/50
0.227
232901NORTHST
50/50
12.543
231131BLOOM ENRGY
50/50
0.368
200039HOPE CG1
50/50
23.047
200036SALEM-G1
50/50
16.702
200037SALEM-G2
50/50
16.583
972251AH1-710 GEN
50/50
60.904
232813VAUGHN
50/50
0.769
232910NRG_G1
50/50
0.431
232911NRG_G2
50/50
0.431
232904IR4
50/50
70.147
232920IR10
50/50
2.616
228203P06
50/50
15.164
228202CUMB CT
50/50
13.885
233972AC1-094 C
Solar/Wind Harmer
-0.002
970695AG2-447 GEN
Solar/Wind Harmer
0.325
971149AH1-027 GEN
Solar/Wind Harmer
0.341
972177AH1-672 GEN
Solar/Wind Harmer
0.695
234033AF1-007_GEN
Solar/Wind Harmer
16.751
970545AG2-347 GEN
Solar/Wind Harmer
69.002
972133AH1-634 GEN
Solar/Wind Harmer
10.455
970453AG2-297 GEN
Solar/Wind Harmer
0.144
971553AH1-274 GEN
Solar/Wind Harmer
0.119
230422AE1-104_GEN1
Solar/Wind Harmer
29.404
230425AE1-104_GEN2
Solar/Wind Harmer
29.404
228754AB1-001 C
Solar/Wind Harmer
-0.001
230433AD2-135 GEN
Solar/Wind Harmer
0
945431AF1-208 GEN
Solar/Wind Harmer
0.301
233990AG1-397 GEN
Solar/Wind Harmer
0
233990AG1-397 GEN
Solar/Wind Harmer
1.057
972069AH1-584 GEN
Solar/Wind Harmer
0.326
972071AH1-585 GEN
Solar/Wind Harmer
0.326
972073AH1-586 GEN
Solar/Wind Harmer
5.869
970997AG2-616 GEN
Solar/Wind Harmer
0.325
972141AH1-641 GEN
Solar/Wind Harmer
0.097
230430AE1-229_GEN
Solar/Wind Harmer
-0.001
971535AH1-265 GEN
Solar/Wind Harmer
0.191
971747AH1-380 GEN
Solar/Wind Harmer
0.129
230407AD2-065 C
Solar/Wind Harmer
0
234015AF2-250 C
Solar/Wind Harmer
0
971195AH1-057 GEN
Solar/Wind Harmer
0.045
228351V2-046C
Solar/Wind Harmer
-0.001
233923SMA
Solar/Wind Harmer
-0.001
233998TM1NIN_3.36
Solar/Wind Harmer
-0.001
233997TMININ_4.2
Solar/Wind Harmer
-0.001
233996TM1833_GEN
Solar/Wind Harmer
-0.001
233940AF2-379 C
Solar/Wind Harmer
-0.001
971011AG2-627 GEN
Solar/Wind Harmer
0.24
218660EHAMPSOLAR C
Solar/Wind Harmer
-0.001
207500AE2-000G1
Solar/Wind Harmer
19.446
207497AE2-000G2
Solar/Wind Harmer
19.446
207507AE2-000G3
Solar/Wind Harmer
19.446
207487AE2-000G4
Solar/Wind Harmer
19.446
970025AG2-016 GEN
Solar/Wind Harmer
0.095
207522AF2-254 C
Solar/Wind Harmer
0.048
219623KINSLEYBEA C
Solar/Wind Harmer
0
971189AH1-054 GEN
Solar/Wind Harmer
0.039
971667AH1-334 GEN
Solar/Wind Harmer
0.089
960671AF2-358 GEN
Solar/Wind Harmer
0.463
965821AG1-450 GEN
Solar/Wind Harmer
2.314
232426Y1-080 FULL
Solar/Wind Harmer
0
970277AG2-181 GEN
Solar/Wind Harmer
0.128
219137THOSOLAR C
Solar/Wind Harmer
0
219258KINSLEYDEP C
Solar/Wind Harmer
0
233946AB2-136 GEN
Solar/Wind Harmer
0
233964AF2-378 GEN
Solar/Wind Harmer
0
219766PARADISE C
Solar/Wind Harmer
0
20714328BYD_X4-031
Solar/Wind Harmer
0.008
20714428HOW_X1-037
Solar/Wind Harmer
0
219907AC1-030 C
Solar/Wind Harmer
0
219236SOUTHERNHQ C
Solar/Wind Harmer
0
20720628TIN_W1-124
Solar/Wind Harmer
0
219906AC1-017 C
Solar/Wind Harmer
0
219615MILLCREEK C
Solar/Wind Harmer
0
234041AC1-190 GEN
Solar/Wind Harmer
0.203
20742028HF_AC1-207
Solar/Wind Harmer
0
971521AH1-258 GEN
Solar/Wind Harmer
0.076
967451AG2-055 C O1
Solar/Wind Harmer
86.175
219727YARDVSOLFA C
Solar/Wind Harmer
0
219276PARKLANDSO C
Solar/Wind Harmer
0
219817TRENTONSOL C
Solar/Wind Harmer
0
219620RIDERU C
Solar/Wind Harmer
0
214067T20SOLAR
Solar/Wind Harmer
0
219918AC2-009 C
Solar/Wind Harmer
0
219612MATRIX C
Solar/Wind Harmer
0
218438BLK ROCK C
Solar/Wind Harmer
0
218524CNTRALGAS1 C
Solar/Wind Harmer
0
218526CNTRALGAS2 C
Solar/Wind Harmer
0
218428ETC SOLAR C
Solar/Wind Harmer
0
217213AMBOY SO C
Solar/Wind Harmer
0
219249CENTRALDIV C
Solar/Wind Harmer
0
218449LINSOLAR C
Solar/Wind Harmer
0
217081WEATEXAS C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
217206BARNGR HS C
Solar/Wind Harmer
0
217208PARK ELE C
Solar/Wind Harmer
0
20673828FLE_V3-070
Solar/Wind Harmer
0.02
20675428EAM_W2-061
Solar/Wind Harmer
0
G-007ALTFEXP_G-007A->PJM
CMTX
16.71
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.132
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.675
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.654
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.995
BlueGrassPJM->LTFIMP_BlueG
CLTF
3.1
CBM NorthLTFEXP_CBM-N->PJM
CBM
17.148
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
37.966

Details for RL_230-KEEN_230 230.0 kV Ckt 1 line l/o DPL_P4_2_REDLION-KEENEY AT51_SRT-A


Base Case Flowgate

Area:DP&L
Facility Description:
RL_230-KEEN_230 230.0 kV Ckt 1 line
Contingency Name:
DPL_P4_2_REDLION-KEENEY AT51_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.73 %
Rating:1171.0 MVA
Rating Type:B
MVA to Mitigate:1179.49
MW Contribution:0.23
Bus #Bus NameTypeMW Contribution
231914HR8
50/50
5.003
231911HR5
50/50
3.418
231912HR6
50/50
3.418
231913HR7
50/50
3.418
231902DC CT7
50/50
1.42
231915DC CT6
50/50
1.42
231906DC3 NUG
50/50
1.136
231907DC10
50/50
0.368
232899W1-062
50/50
0.797
232900DEMECSMY
50/50
0.781
231131BLOOM ENRGY
50/50
0.383
233920W3-032A-CTG1
50/50
3.085
233921W3-032A-STG1
50/50
1.781
232616GEN FOOD
50/50
0.233
232901NORTHST
50/50
12.897
200039HOPE CG1
50/50
22.014
200036SALEM-G1
50/50
15.954
200037SALEM-G2
50/50
15.839
972251AH1-710 GEN
50/50
58.174
232813VAUGHN
50/50
0.802
232910NRG_G1
50/50
0.45
232911NRG_G2
50/50
0.45
232904IR4
50/50
73.594
232920IR10
50/50
2.747
231940T-011
50/50
0.042
228203P06
50/50
14.49
228202CUMB CT
50/50
13.269
233972AC1-094 C
Solar/Wind Harmer
-0.002
970695AG2-447 GEN
Solar/Wind Harmer
0.333
971149AH1-027 GEN
Solar/Wind Harmer
0.35
972177AH1-672 GEN
Solar/Wind Harmer
0.724
234033AF1-007_GEN
Solar/Wind Harmer
17.574
970545AG2-347 GEN
Solar/Wind Harmer
72.392
972133AH1-634 GEN
Solar/Wind Harmer
10.968
970453AG2-297 GEN
Solar/Wind Harmer
0.138
233990AG1-397 GEN
Solar/Wind Harmer
0
233990AG1-397 GEN
Solar/Wind Harmer
1.12
972069AH1-584 GEN
Solar/Wind Harmer
0.346
972071AH1-585 GEN
Solar/Wind Harmer
0.346
972073AH1-586 GEN
Solar/Wind Harmer
6.225
971747AH1-380 GEN
Solar/Wind Harmer
0.137
971553AH1-274 GEN
Solar/Wind Harmer
0.114
230422AE1-104_GEN1
Solar/Wind Harmer
28.098
230425AE1-104_GEN2
Solar/Wind Harmer
28.098
234015AF2-250 C
Solar/Wind Harmer
0
971195AH1-057 GEN
Solar/Wind Harmer
0.048
228754AB1-001 C
Solar/Wind Harmer
-0.001
230433AD2-135 GEN
Solar/Wind Harmer
0
233923SMA
Solar/Wind Harmer
-0.001
233998TM1NIN_3.36
Solar/Wind Harmer
-0.001
233997TMININ_4.2
Solar/Wind Harmer
-0.001
233996TM1833_GEN
Solar/Wind Harmer
-0.001
233940AF2-379 C
Solar/Wind Harmer
-0.001
945431AF1-208 GEN
Solar/Wind Harmer
0.287
970997AG2-616 GEN
Solar/Wind Harmer
0.311
972141AH1-641 GEN
Solar/Wind Harmer
0.093
230430AE1-229_GEN
Solar/Wind Harmer
-0.001
971535AH1-265 GEN
Solar/Wind Harmer
0.182
230407AD2-065 C
Solar/Wind Harmer
0
228351V2-046C
Solar/Wind Harmer
-0.001
971011AG2-627 GEN
Solar/Wind Harmer
0.229
218660EHAMPSOLAR C
Solar/Wind Harmer
-0.001
960671AF2-358 GEN
Solar/Wind Harmer
0.503
965821AG1-450 GEN
Solar/Wind Harmer
2.513
232426Y1-080 FULL
Solar/Wind Harmer
0
970277AG2-181 GEN
Solar/Wind Harmer
0.139
233946AB2-136 GEN
Solar/Wind Harmer
0
207500AE2-000G1
Solar/Wind Harmer
18.575
207497AE2-000G2
Solar/Wind Harmer
18.575
207507AE2-000G3
Solar/Wind Harmer
18.575
207487AE2-000G4
Solar/Wind Harmer
18.575
233964AF2-378 GEN
Solar/Wind Harmer
0
970025AG2-016 GEN
Solar/Wind Harmer
0.091
207522AF2-254 C
Solar/Wind Harmer
0.046
219623KINSLEYBEA C
Solar/Wind Harmer
0
971189AH1-054 GEN
Solar/Wind Harmer
0.037
234041AC1-190 GEN
Solar/Wind Harmer
0.223
971667AH1-334 GEN
Solar/Wind Harmer
0.085
219137THOSOLAR C
Solar/Wind Harmer
0
219258KINSLEYDEP C
Solar/Wind Harmer
0
219766PARADISE C
Solar/Wind Harmer
0
20714328BYD_X4-031
Solar/Wind Harmer
0.008
20714428HOW_X1-037
Solar/Wind Harmer
0
219907AC1-030 C
Solar/Wind Harmer
0
219236SOUTHERNHQ C
Solar/Wind Harmer
0
20720628TIN_W1-124
Solar/Wind Harmer
0
219906AC1-017 C
Solar/Wind Harmer
0
219615MILLCREEK C
Solar/Wind Harmer
0
20742028HF_AC1-207
Solar/Wind Harmer
0
971521AH1-258 GEN
Solar/Wind Harmer
0.072
967451AG2-055 C O1
Solar/Wind Harmer
82.263
219727YARDVSOLFA C
Solar/Wind Harmer
0
219276PARKLANDSO C
Solar/Wind Harmer
0
219817TRENTONSOL C
Solar/Wind Harmer
0
219620RIDERU C
Solar/Wind Harmer
0
214067T20SOLAR
Solar/Wind Harmer
0
219918AC2-009 C
Solar/Wind Harmer
0
219612MATRIX C
Solar/Wind Harmer
0
218438BLK ROCK C
Solar/Wind Harmer
0
218524CNTRALGAS1 C
Solar/Wind Harmer
0
218526CNTRALGAS2 C
Solar/Wind Harmer
0
218428ETC SOLAR C
Solar/Wind Harmer
0
217213AMBOY SO C
Solar/Wind Harmer
0
219249CENTRALDIV C
Solar/Wind Harmer
0
218449LINSOLAR C
Solar/Wind Harmer
0
217081WEATEXAS C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
217206BARNGR HS C
Solar/Wind Harmer
0
217208PARK ELE C
Solar/Wind Harmer
0
971983AH1-536 GEN
Solar/Wind Harmer
0.114
20673828FLE_V3-070
Solar/Wind Harmer
0.019
20675428EAM_W2-061
Solar/Wind Harmer
0
G-007ALTFEXP_G-007A->PJM
CMTX
15.95
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.103
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.658
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.541
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.971
BlueGrassPJM->LTFIMP_BlueG
CLTF
3.025
CBM NorthLTFEXP_CBM-N->PJM
CBM
16.303
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
36.219

Details for ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line l/o PECO_P2-2_CHI230B1_SRT-A/* $ DELCO $ PECO_P2-2_CHI230B1 $ B


Base Case Flowgate

Area:PJM
Facility Description:
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line
Contingency Name:
PECO_P2-2_CHI230B1_SRT-A/* $ DELCO $ PECO_P2-2_CHI230B1 $ B
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:115.06 %
Rating:3106.0 MVA
Rating Type:B
MVA to Mitigate:3573.91
MW Contribution:0.6
Bus #Bus NameTypeMW Contribution
200203Y1-065-STG
50/50
21.182
200204Y1-065-CTG1
50/50
13.338
200205Y1-065-CTG2
50/50
13.338
200052ROCKSP 1
50/50
158.247
200053ROCKSP 2
50/50
158.247
200054ROCKSP 3
50/50
156.641
200055ROCKSP 4
50/50
156.641
231914HR8
50/50
5.384
231911HR5
50/50
3.678
231912HR6
50/50
3.678
231913HR7
50/50
3.678
232907VN8
50/50
59.454
232926CRISFLD1
50/50
0.276
232921TASLEY2G
50/50
0.911
232905CHERITON_25
50/50
0.345
232912OH NUG1
50/50
22.714
232913OH NUG2
50/50
22.714
232914OH NUG3
50/50
22.714
232915OH NUG4
50/50
22.714
232916OH NUG5
50/50
22.714
232917OH NUG6
50/50
22.714
232918OH NUG7
50/50
22.714
232919VN10
50/50
7.814
234034AF2-060
50/50
4.543
233900O-025 C
50/50
0.166
232904IR4
50/50
220.83
232920IR10
50/50
8.384
231940T-011
50/50
0.138
233920W3-032A-CTG1
50/50
5.529
233921W3-032A-STG1
50/50
3.192
232616GEN FOOD
50/50
0.418
232901NORTHST
50/50
23.112
232910NRG_G1
50/50
1.196
232911NRG_G2
50/50
1.196
233987AB2-037 GEN
Solar/Wind Harmer
0
233923SMA
Solar/Wind Harmer
-0.003
233998TM1NIN_3.36
Solar/Wind Harmer
-0.003
233997TMININ_4.2
Solar/Wind Harmer
-0.003
233996TM1833_GEN
Solar/Wind Harmer
-0.003
233940AF2-379 C
Solar/Wind Harmer
-0.003
971747AH1-380 GEN
Solar/Wind Harmer
0.505
972069AH1-584 GEN
Solar/Wind Harmer
1.262
972071AH1-585 GEN
Solar/Wind Harmer
1.262
972073AH1-586 GEN
Solar/Wind Harmer
22.71
960671AF2-358 GEN
Solar/Wind Harmer
2.523
965821AG1-450 GEN
Solar/Wind Harmer
12.616
234015AF2-250 C
Solar/Wind Harmer
-0.001
971195AH1-057 GEN
Solar/Wind Harmer
0.182
232426Y1-080 FULL
Solar/Wind Harmer
-0.001
970277AG2-181 GEN
Solar/Wind Harmer
0.706
233990AG1-397 GEN
Solar/Wind Harmer
-0.001
233990AG1-397 GEN
Solar/Wind Harmer
4.036
233946AB2-136 GEN
Solar/Wind Harmer
-0.003
233964AF2-378 GEN
Solar/Wind Harmer
0.001
234033AF1-007_GEN
Solar/Wind Harmer
52.733
970545AG2-347 GEN
Solar/Wind Harmer
217.224
972133AH1-634 GEN
Solar/Wind Harmer
32.913
234041AC1-190 GEN
Solar/Wind Harmer
1.26
972177AH1-672 GEN
Solar/Wind Harmer
1.887
971149AH1-027 GEN
Solar/Wind Harmer
0.628
233972AC1-094 C
Solar/Wind Harmer
-0.003
970695AG2-447 GEN
Solar/Wind Harmer
0.501
233984AB2-036 GEN
Solar/Wind Harmer
2.294
233968AD2-076_GEN
Solar/Wind Harmer
1.211
234014AF1-036_GEN
Solar/Wind Harmer
0.494
970597AG2-380 GEN
Solar/Wind Harmer
9.888
234012AE2-112_GEN
Solar/Wind Harmer
0.42
971983AH1-536 GEN
Solar/Wind Harmer
1.025
970453AG2-297 GEN
Solar/Wind Harmer
0.313
971553AH1-274 GEN
Solar/Wind Harmer
0.266
945431AF1-208 GEN
Solar/Wind Harmer
0.704
230422AE1-104_GEN1
Solar/Wind Harmer
64.615
230425AE1-104_GEN2
Solar/Wind Harmer
64.615
970997AG2-616 GEN
Solar/Wind Harmer
0.773
972141AH1-641 GEN
Solar/Wind Harmer
0.232
230430AE1-229_GEN
Solar/Wind Harmer
-0.001
228351V2-046C
Solar/Wind Harmer
-0.002
230433AD2-135 GEN
Solar/Wind Harmer
0
228754AB1-001 C
Solar/Wind Harmer
-0.002
971535AH1-265 GEN
Solar/Wind Harmer
0.442
971011AG2-627 GEN
Solar/Wind Harmer
0.601
230407AD2-065 C
Solar/Wind Harmer
0
219137THOSOLAR C
Solar/Wind Harmer
0.001
218660EHAMPSOLAR C
Solar/Wind Harmer
-0.001
219258KINSLEYDEP C
Solar/Wind Harmer
0
219623KINSLEYBEA C
Solar/Wind Harmer
-0.001
219766PARADISE C
Solar/Wind Harmer
-0.001
207500AE2-000G1
Solar/Wind Harmer
43.24
207497AE2-000G2
Solar/Wind Harmer
43.24
207507AE2-000G3
Solar/Wind Harmer
43.24
207487AE2-000G4
Solar/Wind Harmer
43.24
219907AC1-030 C
Solar/Wind Harmer
-0.001
219236SOUTHERNHQ C
Solar/Wind Harmer
-0.001
207522AF2-254 C
Solar/Wind Harmer
0.109
970025AG2-016 GEN
Solar/Wind Harmer
0.213
219906AC1-017 C
Solar/Wind Harmer
-0.001
219615MILLCREEK C
Solar/Wind Harmer
-0.001
971189AH1-054 GEN
Solar/Wind Harmer
0.087
971667AH1-334 GEN
Solar/Wind Harmer
0.2
214067T20SOLAR
Solar/Wind Harmer
-0.001
20714328BYD_X4-031
Solar/Wind Harmer
0.019
20714428HOW_X1-037
Solar/Wind Harmer
-0.001
20720628TIN_W1-124
Solar/Wind Harmer
-0.001
219727YARDVSOLFA C
Solar/Wind Harmer
0.001
20742028HF_AC1-207
Solar/Wind Harmer
-0.001
971521AH1-258 GEN
Solar/Wind Harmer
0.169
219276PARKLANDSO C
Solar/Wind Harmer
0
967451AG2-055 C O1
Solar/Wind Harmer
188.443
219620RIDERU C
Solar/Wind Harmer
-0.001
219817TRENTONSOL C
Solar/Wind Harmer
0.001
219918AC2-009 C
Solar/Wind Harmer
0
219612MATRIX C
Solar/Wind Harmer
0
218438BLK ROCK C
Solar/Wind Harmer
0
218526CNTRALGAS2 C
Solar/Wind Harmer
0.001
218524CNTRALGAS1 C
Solar/Wind Harmer
0.001
218428ETC SOLAR C
Solar/Wind Harmer
0
217213AMBOY SO C
Solar/Wind Harmer
-0.001
219249CENTRALDIV C
Solar/Wind Harmer
0
218449LINSOLAR C
Solar/Wind Harmer
0
217081WEATEXAS C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
217206BARNGR HS C
Solar/Wind Harmer
0
217208PARK ELE C
Solar/Wind Harmer
0
20673828FLE_V3-070
Solar/Wind Harmer
0.046
20675428EAM_W2-061
Solar/Wind Harmer
0
207439AE1-081 C O1
Solar/Wind Harmer
0
20676328BVR_Y1-020
Solar/Wind Harmer
0
20674628WNG_W3-110
Solar/Wind Harmer
-0.001
207511W3-106 GEN
Solar/Wind Harmer
0.026
G-007ALTFEXP_G-007A->PJM
CMTX
37.447
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.466
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.074
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
14.486
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
3.102
BlueGrassPJM->LTFIMP_BlueG
CLTF
9.662
CBM NorthLTFEXP_CBM-N->PJM
CBM
36.667
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
85.4

Details for ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line l/o PECO_P4_CHICH435_SRT-A/* $ DELCO $ PECO_P4_CHICH435 $ STBK


Base Case Flowgate

Area:PJM
Facility Description:
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line
Contingency Name:
PECO_P4_CHICH435_SRT-A/* $ DELCO $ PECO_P4_CHICH435 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.06 %
Rating:3106.0 MVA
Rating Type:B
MVA to Mitigate:3573.85
MW Contribution:0.6
Bus #Bus NameTypeMW Contribution
200203Y1-065-STG
50/50
21.182
200204Y1-065-CTG1
50/50
13.338
200205Y1-065-CTG2
50/50
13.338
200052ROCKSP 1
50/50
158.248
200053ROCKSP 2
50/50
158.248
200054ROCKSP 3
50/50
156.641
200055ROCKSP 4
50/50
156.641
231914HR8
50/50
5.384
231911HR5
50/50
3.678
231912HR6
50/50
3.678
231913HR7
50/50
3.678
232907VN8
50/50
59.455
232926CRISFLD1
50/50
0.276
232921TASLEY2G
50/50
0.911
232905CHERITON_25
50/50
0.345
232912OH NUG1
50/50
22.715
232913OH NUG2
50/50
22.715
232914OH NUG3
50/50
22.715
232915OH NUG4
50/50
22.715
232916OH NUG5
50/50
22.715
232917OH NUG6
50/50
22.715
232918OH NUG7
50/50
22.715
232919VN10
50/50
7.814
234034AF2-060
50/50
4.543
233900O-025 C
50/50
0.166
232904IR4
50/50
220.834
232920IR10
50/50
8.384
231940T-011
50/50
0.138
233920W3-032A-CTG1
50/50
5.529
233921W3-032A-STG1
50/50
3.192
232616GEN FOOD
50/50
0.418
232901NORTHST
50/50
23.113
232910NRG_G1
50/50
1.196
232911NRG_G2
50/50
1.196
233987AB2-037 GEN
Solar/Wind Harmer
0
233923SMA
Solar/Wind Harmer
-0.003
233998TM1NIN_3.36
Solar/Wind Harmer
-0.003
233997TMININ_4.2
Solar/Wind Harmer
-0.003
233996TM1833_GEN
Solar/Wind Harmer
-0.003
233940AF2-379 C
Solar/Wind Harmer
-0.003
971747AH1-380 GEN
Solar/Wind Harmer
0.505
972069AH1-584 GEN
Solar/Wind Harmer
1.262
972071AH1-585 GEN
Solar/Wind Harmer
1.262
972073AH1-586 GEN
Solar/Wind Harmer
22.711
960671AF2-358 GEN
Solar/Wind Harmer
2.523
965821AG1-450 GEN
Solar/Wind Harmer
12.616
234015AF2-250 C
Solar/Wind Harmer
-0.001
971195AH1-057 GEN
Solar/Wind Harmer
0.182
232426Y1-080 FULL
Solar/Wind Harmer
-0.001
970277AG2-181 GEN
Solar/Wind Harmer
0.706
233990AG1-397 GEN
Solar/Wind Harmer
-0.001
233990AG1-397 GEN
Solar/Wind Harmer
4.036
233946AB2-136 GEN
Solar/Wind Harmer
-0.003
233964AF2-378 GEN
Solar/Wind Harmer
0.001
234033AF1-007_GEN
Solar/Wind Harmer
52.734
970545AG2-347 GEN
Solar/Wind Harmer
217.228
972133AH1-634 GEN
Solar/Wind Harmer
32.913
234041AC1-190 GEN
Solar/Wind Harmer
1.26
972177AH1-672 GEN
Solar/Wind Harmer
1.887
971149AH1-027 GEN
Solar/Wind Harmer
0.628
233972AC1-094 C
Solar/Wind Harmer
-0.003
970695AG2-447 GEN
Solar/Wind Harmer
0.501
233984AB2-036 GEN
Solar/Wind Harmer
2.294
233968AD2-076_GEN
Solar/Wind Harmer
1.211
234014AF1-036_GEN
Solar/Wind Harmer
0.494
970597AG2-380 GEN
Solar/Wind Harmer
9.889
234012AE2-112_GEN
Solar/Wind Harmer
0.42
971983AH1-536 GEN
Solar/Wind Harmer
1.025
970453AG2-297 GEN
Solar/Wind Harmer
0.313
971553AH1-274 GEN
Solar/Wind Harmer
0.266
945431AF1-208 GEN
Solar/Wind Harmer
0.704
230422AE1-104_GEN1
Solar/Wind Harmer
64.614
230425AE1-104_GEN2
Solar/Wind Harmer
64.614
970997AG2-616 GEN
Solar/Wind Harmer
0.773
972141AH1-641 GEN
Solar/Wind Harmer
0.232
230430AE1-229_GEN
Solar/Wind Harmer
-0.001
228351V2-046C
Solar/Wind Harmer
-0.002
230433AD2-135 GEN
Solar/Wind Harmer
0
228754AB1-001 C
Solar/Wind Harmer
-0.002
971535AH1-265 GEN
Solar/Wind Harmer
0.442
971011AG2-627 GEN
Solar/Wind Harmer
0.601
230407AD2-065 C
Solar/Wind Harmer
0
219137THOSOLAR C
Solar/Wind Harmer
0.001
218660EHAMPSOLAR C
Solar/Wind Harmer
-0.001
219258KINSLEYDEP C
Solar/Wind Harmer
0
219623KINSLEYBEA C
Solar/Wind Harmer
-0.001
219766PARADISE C
Solar/Wind Harmer
-0.001
207500AE2-000G1
Solar/Wind Harmer
43.239
207497AE2-000G2
Solar/Wind Harmer
43.239
207507AE2-000G3
Solar/Wind Harmer
43.239
207487AE2-000G4
Solar/Wind Harmer
43.239
219907AC1-030 C
Solar/Wind Harmer
-0.001
219236SOUTHERNHQ C
Solar/Wind Harmer
-0.001
207522AF2-254 C
Solar/Wind Harmer
0.109
970025AG2-016 GEN
Solar/Wind Harmer
0.213
219906AC1-017 C
Solar/Wind Harmer
-0.001
219615MILLCREEK C
Solar/Wind Harmer
-0.001
971189AH1-054 GEN
Solar/Wind Harmer
0.087
971667AH1-334 GEN
Solar/Wind Harmer
0.2
214067T20SOLAR
Solar/Wind Harmer
-0.001
20714328BYD_X4-031
Solar/Wind Harmer
0.019
20714428HOW_X1-037
Solar/Wind Harmer
-0.001
20720628TIN_W1-124
Solar/Wind Harmer
-0.001
219727YARDVSOLFA C
Solar/Wind Harmer
0.001
20742028HF_AC1-207
Solar/Wind Harmer
-0.001
971521AH1-258 GEN
Solar/Wind Harmer
0.169
219276PARKLANDSO C
Solar/Wind Harmer
0
967451AG2-055 C O1
Solar/Wind Harmer
188.44
219620RIDERU C
Solar/Wind Harmer
-0.001
219817TRENTONSOL C
Solar/Wind Harmer
0.001
219918AC2-009 C
Solar/Wind Harmer
0
219612MATRIX C
Solar/Wind Harmer
0
218438BLK ROCK C
Solar/Wind Harmer
0
218526CNTRALGAS2 C
Solar/Wind Harmer
0.001
218524CNTRALGAS1 C
Solar/Wind Harmer
0.001
218428ETC SOLAR C
Solar/Wind Harmer
0
217213AMBOY SO C
Solar/Wind Harmer
-0.001
219249CENTRALDIV C
Solar/Wind Harmer
0
218449LINSOLAR C
Solar/Wind Harmer
0
217081WEATEXAS C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
217206BARNGR HS C
Solar/Wind Harmer
0
217208PARK ELE C
Solar/Wind Harmer
0
20673828FLE_V3-070
Solar/Wind Harmer
0.046
20675428EAM_W2-061
Solar/Wind Harmer
0
207439AE1-081 C O1
Solar/Wind Harmer
0
20676328BVR_Y1-020
Solar/Wind Harmer
0
20674628WNG_W3-110
Solar/Wind Harmer
-0.001
207511W3-106 GEN
Solar/Wind Harmer
0.026
G-007ALTFEXP_G-007A->PJM
CMTX
37.446
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.466
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.074
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
14.486
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
3.102
BlueGrassPJM->LTFIMP_BlueG
CLTF
9.662
CBM NorthLTFEXP_CBM-N->PJM
CBM
36.666
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
85.399

Details for ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line l/o PECO_P4_CHICH195_SRT-A/* $ DELCO $ PECO_P4_CHICH195 $ STBK


Base Case Flowgate

Area:PJM
Facility Description:
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line
Contingency Name:
PECO_P4_CHICH195_SRT-A/* $ DELCO $ PECO_P4_CHICH195 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.06 %
Rating:3106.0 MVA
Rating Type:B
MVA to Mitigate:3573.84
MW Contribution:0.6
Bus #Bus NameTypeMW Contribution
200203Y1-065-STG
50/50
21.182
200204Y1-065-CTG1
50/50
13.338
200205Y1-065-CTG2
50/50
13.338
200052ROCKSP 1
50/50
158.247
200053ROCKSP 2
50/50
158.247
200054ROCKSP 3
50/50
156.641
200055ROCKSP 4
50/50
156.641
231914HR8
50/50
5.384
231911HR5
50/50
3.678
231912HR6
50/50
3.678
231913HR7
50/50
3.678
232907VN8
50/50
59.454
232926CRISFLD1
50/50
0.276
232921TASLEY2G
50/50
0.911
232905CHERITON_25
50/50
0.345
232912OH NUG1
50/50
22.714
232913OH NUG2
50/50
22.714
232914OH NUG3
50/50
22.714
232915OH NUG4
50/50
22.714
232916OH NUG5
50/50
22.714
232917OH NUG6
50/50
22.714
232918OH NUG7
50/50
22.714
232919VN10
50/50
7.814
234034AF2-060
50/50
4.543
233900O-025 C
50/50
0.166
232904IR4
50/50
220.83
232920IR10
50/50
8.384
231940T-011
50/50
0.138
233920W3-032A-CTG1
50/50
5.529
233921W3-032A-STG1
50/50
3.192
232616GEN FOOD
50/50
0.418
232901NORTHST
50/50
23.112
232910NRG_G1
50/50
1.196
232911NRG_G2
50/50
1.196
233987AB2-037 GEN
Solar/Wind Harmer
0
233923SMA
Solar/Wind Harmer
-0.003
233998TM1NIN_3.36
Solar/Wind Harmer
-0.003
233997TMININ_4.2
Solar/Wind Harmer
-0.003
233996TM1833_GEN
Solar/Wind Harmer
-0.003
233940AF2-379 C
Solar/Wind Harmer
-0.003
971747AH1-380 GEN
Solar/Wind Harmer
0.505
972069AH1-584 GEN
Solar/Wind Harmer
1.262
972071AH1-585 GEN
Solar/Wind Harmer
1.262
972073AH1-586 GEN
Solar/Wind Harmer
22.71
960671AF2-358 GEN
Solar/Wind Harmer
2.523
965821AG1-450 GEN
Solar/Wind Harmer
12.616
234015AF2-250 C
Solar/Wind Harmer
-0.001
971195AH1-057 GEN
Solar/Wind Harmer
0.182
232426Y1-080 FULL
Solar/Wind Harmer
-0.001
970277AG2-181 GEN
Solar/Wind Harmer
0.706
233990AG1-397 GEN
Solar/Wind Harmer
-0.001
233990AG1-397 GEN
Solar/Wind Harmer
4.036
233946AB2-136 GEN
Solar/Wind Harmer
-0.003
233964AF2-378 GEN
Solar/Wind Harmer
0.001
234033AF1-007_GEN
Solar/Wind Harmer
52.733
970545AG2-347 GEN
Solar/Wind Harmer
217.224
972133AH1-634 GEN
Solar/Wind Harmer
32.913
234041AC1-190 GEN
Solar/Wind Harmer
1.26
972177AH1-672 GEN
Solar/Wind Harmer
1.887
971149AH1-027 GEN
Solar/Wind Harmer
0.628
233972AC1-094 C
Solar/Wind Harmer
-0.003
970695AG2-447 GEN
Solar/Wind Harmer
0.501
233984AB2-036 GEN
Solar/Wind Harmer
2.294
233968AD2-076_GEN
Solar/Wind Harmer
1.211
234014AF1-036_GEN
Solar/Wind Harmer
0.494
970597AG2-380 GEN
Solar/Wind Harmer
9.888
234012AE2-112_GEN
Solar/Wind Harmer
0.42
971983AH1-536 GEN
Solar/Wind Harmer
1.025
970453AG2-297 GEN
Solar/Wind Harmer
0.313
971553AH1-274 GEN
Solar/Wind Harmer
0.266
945431AF1-208 GEN
Solar/Wind Harmer
0.704
230422AE1-104_GEN1
Solar/Wind Harmer
64.615
230425AE1-104_GEN2
Solar/Wind Harmer
64.615
970997AG2-616 GEN
Solar/Wind Harmer
0.773
972141AH1-641 GEN
Solar/Wind Harmer
0.232
230430AE1-229_GEN
Solar/Wind Harmer
-0.001
228351V2-046C
Solar/Wind Harmer
-0.002
230433AD2-135 GEN
Solar/Wind Harmer
0
228754AB1-001 C
Solar/Wind Harmer
-0.002
971535AH1-265 GEN
Solar/Wind Harmer
0.442
971011AG2-627 GEN
Solar/Wind Harmer
0.601
230407AD2-065 C
Solar/Wind Harmer
0
219137THOSOLAR C
Solar/Wind Harmer
0.001
218660EHAMPSOLAR C
Solar/Wind Harmer
-0.001
219258KINSLEYDEP C
Solar/Wind Harmer
0
219623KINSLEYBEA C
Solar/Wind Harmer
-0.001
219766PARADISE C
Solar/Wind Harmer
-0.001
207500AE2-000G1
Solar/Wind Harmer
43.24
207497AE2-000G2
Solar/Wind Harmer
43.24
207507AE2-000G3
Solar/Wind Harmer
43.24
207487AE2-000G4
Solar/Wind Harmer
43.24
219907AC1-030 C
Solar/Wind Harmer
-0.001
219236SOUTHERNHQ C
Solar/Wind Harmer
-0.001
207522AF2-254 C
Solar/Wind Harmer
0.109
970025AG2-016 GEN
Solar/Wind Harmer
0.213
219906AC1-017 C
Solar/Wind Harmer
-0.001
219615MILLCREEK C
Solar/Wind Harmer
-0.001
971189AH1-054 GEN
Solar/Wind Harmer
0.087
971667AH1-334 GEN
Solar/Wind Harmer
0.2
214067T20SOLAR
Solar/Wind Harmer
-0.001
20714328BYD_X4-031
Solar/Wind Harmer
0.019
20714428HOW_X1-037
Solar/Wind Harmer
-0.001
20720628TIN_W1-124
Solar/Wind Harmer
-0.001
219727YARDVSOLFA C
Solar/Wind Harmer
0.001
20742028HF_AC1-207
Solar/Wind Harmer
-0.001
971521AH1-258 GEN
Solar/Wind Harmer
0.169
219276PARKLANDSO C
Solar/Wind Harmer
0
967451AG2-055 C O1
Solar/Wind Harmer
188.443
219620RIDERU C
Solar/Wind Harmer
-0.001
219817TRENTONSOL C
Solar/Wind Harmer
0.001
219918AC2-009 C
Solar/Wind Harmer
0
219612MATRIX C
Solar/Wind Harmer
0
218438BLK ROCK C
Solar/Wind Harmer
0
218526CNTRALGAS2 C
Solar/Wind Harmer
0.001
218524CNTRALGAS1 C
Solar/Wind Harmer
0.001
218428ETC SOLAR C
Solar/Wind Harmer
0
217213AMBOY SO C
Solar/Wind Harmer
-0.001
219249CENTRALDIV C
Solar/Wind Harmer
0
218449LINSOLAR C
Solar/Wind Harmer
0
217081WEATEXAS C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
217206BARNGR HS C
Solar/Wind Harmer
0
217208PARK ELE C
Solar/Wind Harmer
0
20673828FLE_V3-070
Solar/Wind Harmer
0.046
20675428EAM_W2-061
Solar/Wind Harmer
0
207439AE1-081 C O1
Solar/Wind Harmer
0
20676328BVR_Y1-020
Solar/Wind Harmer
0
20674628WNG_W3-110
Solar/Wind Harmer
-0.001
207511W3-106 GEN
Solar/Wind Harmer
0.026
G-007ALTFEXP_G-007A->PJM
CMTX
37.447
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.466
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.074
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
14.486
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
3.102
BlueGrassPJM->LTFIMP_BlueG
CLTF
9.662
CBM NorthLTFEXP_CBM-N->PJM
CBM
36.667
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
85.4

Details for ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line l/o PECO_P4_CHICH045_SRT-A/* $ DELCO $ PECO_P4_CHICH045 $ STBK


Base Case Flowgate

Area:PJM
Facility Description:
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line
Contingency Name:
PECO_P4_CHICH045_SRT-A/* $ DELCO $ PECO_P4_CHICH045 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.06 %
Rating:3106.0 MVA
Rating Type:B
MVA to Mitigate:3573.81
MW Contribution:0.6
Bus #Bus NameTypeMW Contribution
200203Y1-065-STG
50/50
21.182
200204Y1-065-CTG1
50/50
13.338
200205Y1-065-CTG2
50/50
13.338
200052ROCKSP 1
50/50
158.247
200053ROCKSP 2
50/50
158.247
200054ROCKSP 3
50/50
156.641
200055ROCKSP 4
50/50
156.641
231914HR8
50/50
5.384
231911HR5
50/50
3.678
231912HR6
50/50
3.678
231913HR7
50/50
3.678
232907VN8
50/50
59.454
232926CRISFLD1
50/50
0.276
232921TASLEY2G
50/50
0.911
232905CHERITON_25
50/50
0.345
232912OH NUG1
50/50
22.714
232913OH NUG2
50/50
22.714
232914OH NUG3
50/50
22.714
232915OH NUG4
50/50
22.714
232916OH NUG5
50/50
22.714
232917OH NUG6
50/50
22.714
232918OH NUG7
50/50
22.714
232919VN10
50/50
7.814
234034AF2-060
50/50
4.543
233900O-025 C
50/50
0.166
232904IR4
50/50
220.83
232920IR10
50/50
8.384
231940T-011
50/50
0.138
233920W3-032A-CTG1
50/50
5.529
233921W3-032A-STG1
50/50
3.192
232616GEN FOOD
50/50
0.418
232901NORTHST
50/50
23.112
232910NRG_G1
50/50
1.196
232911NRG_G2
50/50
1.196
233987AB2-037 GEN
Solar/Wind Harmer
0
233923SMA
Solar/Wind Harmer
-0.003
233998TM1NIN_3.36
Solar/Wind Harmer
-0.003
233997TMININ_4.2
Solar/Wind Harmer
-0.003
233996TM1833_GEN
Solar/Wind Harmer
-0.003
233940AF2-379 C
Solar/Wind Harmer
-0.003
971747AH1-380 GEN
Solar/Wind Harmer
0.505
972069AH1-584 GEN
Solar/Wind Harmer
1.262
972071AH1-585 GEN
Solar/Wind Harmer
1.262
972073AH1-586 GEN
Solar/Wind Harmer
22.71
960671AF2-358 GEN
Solar/Wind Harmer
2.523
965821AG1-450 GEN
Solar/Wind Harmer
12.616
234015AF2-250 C
Solar/Wind Harmer
-0.001
971195AH1-057 GEN
Solar/Wind Harmer
0.182
232426Y1-080 FULL
Solar/Wind Harmer
-0.001
970277AG2-181 GEN
Solar/Wind Harmer
0.706
233990AG1-397 GEN
Solar/Wind Harmer
-0.001
233990AG1-397 GEN
Solar/Wind Harmer
4.036
233946AB2-136 GEN
Solar/Wind Harmer
-0.003
233964AF2-378 GEN
Solar/Wind Harmer
0.001
234033AF1-007_GEN
Solar/Wind Harmer
52.733
970545AG2-347 GEN
Solar/Wind Harmer
217.224
972133AH1-634 GEN
Solar/Wind Harmer
32.913
234041AC1-190 GEN
Solar/Wind Harmer
1.26
972177AH1-672 GEN
Solar/Wind Harmer
1.887
971149AH1-027 GEN
Solar/Wind Harmer
0.628
233972AC1-094 C
Solar/Wind Harmer
-0.003
970695AG2-447 GEN
Solar/Wind Harmer
0.501
233984AB2-036 GEN
Solar/Wind Harmer
2.294
233968AD2-076_GEN
Solar/Wind Harmer
1.211
234014AF1-036_GEN
Solar/Wind Harmer
0.494
970597AG2-380 GEN
Solar/Wind Harmer
9.888
234012AE2-112_GEN
Solar/Wind Harmer
0.42
971983AH1-536 GEN
Solar/Wind Harmer
1.025
970453AG2-297 GEN
Solar/Wind Harmer
0.313
971553AH1-274 GEN
Solar/Wind Harmer
0.266
945431AF1-208 GEN
Solar/Wind Harmer
0.704
230422AE1-104_GEN1
Solar/Wind Harmer
64.615
230425AE1-104_GEN2
Solar/Wind Harmer
64.615
970997AG2-616 GEN
Solar/Wind Harmer
0.773
972141AH1-641 GEN
Solar/Wind Harmer
0.232
230430AE1-229_GEN
Solar/Wind Harmer
-0.001
228351V2-046C
Solar/Wind Harmer
-0.002
230433AD2-135 GEN
Solar/Wind Harmer
0
228754AB1-001 C
Solar/Wind Harmer
-0.002
971535AH1-265 GEN
Solar/Wind Harmer
0.442
971011AG2-627 GEN
Solar/Wind Harmer
0.601
230407AD2-065 C
Solar/Wind Harmer
0
219137THOSOLAR C
Solar/Wind Harmer
0.001
218660EHAMPSOLAR C
Solar/Wind Harmer
-0.001
219258KINSLEYDEP C
Solar/Wind Harmer
0
219623KINSLEYBEA C
Solar/Wind Harmer
-0.001
219766PARADISE C
Solar/Wind Harmer
-0.001
207500AE2-000G1
Solar/Wind Harmer
43.24
207497AE2-000G2
Solar/Wind Harmer
43.24
207507AE2-000G3
Solar/Wind Harmer
43.24
207487AE2-000G4
Solar/Wind Harmer
43.24
219907AC1-030 C
Solar/Wind Harmer
-0.001
219236SOUTHERNHQ C
Solar/Wind Harmer
-0.001
207522AF2-254 C
Solar/Wind Harmer
0.109
970025AG2-016 GEN
Solar/Wind Harmer
0.213
219906AC1-017 C
Solar/Wind Harmer
-0.001
219615MILLCREEK C
Solar/Wind Harmer
-0.001
971189AH1-054 GEN
Solar/Wind Harmer
0.087
971667AH1-334 GEN
Solar/Wind Harmer
0.2
214067T20SOLAR
Solar/Wind Harmer
-0.001
20714328BYD_X4-031
Solar/Wind Harmer
0.019
20714428HOW_X1-037
Solar/Wind Harmer
-0.001
20720628TIN_W1-124
Solar/Wind Harmer
-0.001
219727YARDVSOLFA C
Solar/Wind Harmer
0.001
20742028HF_AC1-207
Solar/Wind Harmer
-0.001
971521AH1-258 GEN
Solar/Wind Harmer
0.169
219276PARKLANDSO C
Solar/Wind Harmer
0
967451AG2-055 C O1
Solar/Wind Harmer
188.443
219620RIDERU C
Solar/Wind Harmer
-0.001
219817TRENTONSOL C
Solar/Wind Harmer
0.001
219918AC2-009 C
Solar/Wind Harmer
0
219612MATRIX C
Solar/Wind Harmer
0
218438BLK ROCK C
Solar/Wind Harmer
0
218526CNTRALGAS2 C
Solar/Wind Harmer
0.001
218524CNTRALGAS1 C
Solar/Wind Harmer
0.001
218428ETC SOLAR C
Solar/Wind Harmer
0
217213AMBOY SO C
Solar/Wind Harmer
-0.001
219249CENTRALDIV C
Solar/Wind Harmer
0
218449LINSOLAR C
Solar/Wind Harmer
0
217081WEATEXAS C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
217206BARNGR HS C
Solar/Wind Harmer
0
217208PARK ELE C
Solar/Wind Harmer
0
20673828FLE_V3-070
Solar/Wind Harmer
0.046
20675428EAM_W2-061
Solar/Wind Harmer
0
207439AE1-081 C O1
Solar/Wind Harmer
0
20676328BVR_Y1-020
Solar/Wind Harmer
0
20674628WNG_W3-110
Solar/Wind Harmer
-0.001
207511W3-106 GEN
Solar/Wind Harmer
0.026
G-007ALTFEXP_G-007A->PJM
CMTX
37.447
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.466
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.074
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
14.486
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
3.102
BlueGrassPJM->LTFIMP_BlueG
CLTF
9.662
CBM NorthLTFEXP_CBM-N->PJM
CBM
36.667
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
85.4

Details for ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line l/o PECO_P4_PEACH065_SRT-A/* $ CHESCO $ PECO_P4_PEACH065 $ STBK


Base Case Flowgate

Area:PJM
Facility Description:
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line
Contingency Name:
PECO_P4_PEACH065_SRT-A/* $ CHESCO $ PECO_P4_PEACH065 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.58 %
Rating:3106.0 MVA
Rating Type:B
MVA to Mitigate:3558.7
MW Contribution:0.63
Bus #Bus NameTypeMW Contribution
200203Y1-065-STG
50/50
20.185
200204Y1-065-CTG1
50/50
12.71
200205Y1-065-CTG2
50/50
12.71
200052ROCKSP 1
50/50
150.801
200053ROCKSP 2
50/50
150.801
200054ROCKSP 3
50/50
149.27
200055ROCKSP 4
50/50
149.27
231914HR8
50/50
5.031
231911HR5
50/50
3.437
231912HR6
50/50
3.437
231913HR7
50/50
3.437
233920W3-032A-CTG1
50/50
5.186
233921W3-032A-STG1
50/50
2.994
232616GEN FOOD
50/50
0.392
232901NORTHST
50/50
21.681
232904IR4
50/50
205.889
232920IR10
50/50
7.816
232921TASLEY2G
50/50
0.847
232905CHERITON_25
50/50
0.321
232912OH NUG1
50/50
21.139
232913OH NUG2
50/50
21.139
232914OH NUG3
50/50
21.139
232915OH NUG4
50/50
21.139
232916OH NUG5
50/50
21.139
232917OH NUG6
50/50
21.139
232918OH NUG7
50/50
21.139
234034AF2-060
50/50
4.228
232926CRISFLD1
50/50
0.257
233900O-025 C
50/50
0.154
231940T-011
50/50
0.128
232907VN8
50/50
55.208
232919VN10
50/50
7.259
232910NRG_G1
50/50
1.115
232911NRG_G2
50/50
1.115
971149AH1-027 GEN
Solar/Wind Harmer
0.589
233972AC1-094 C
Solar/Wind Harmer
-0.002
970695AG2-447 GEN
Solar/Wind Harmer
0.471
233987AB2-037 GEN
Solar/Wind Harmer
0
234033AF1-007_GEN
Solar/Wind Harmer
49.165
970545AG2-347 GEN
Solar/Wind Harmer
202.527
972133AH1-634 GEN
Solar/Wind Harmer
30.686
972069AH1-584 GEN
Solar/Wind Harmer
1.174
972071AH1-585 GEN
Solar/Wind Harmer
1.174
972073AH1-586 GEN
Solar/Wind Harmer
21.14
971747AH1-380 GEN
Solar/Wind Harmer
0.47
233923SMA
Solar/Wind Harmer
-0.002
233998TM1NIN_3.36
Solar/Wind Harmer
-0.002
233997TMININ_4.2
Solar/Wind Harmer
-0.002
233996TM1833_GEN
Solar/Wind Harmer
-0.002
972177AH1-672 GEN
Solar/Wind Harmer
1.761
233990AG1-397 GEN
Solar/Wind Harmer
-0.001
233990AG1-397 GEN
Solar/Wind Harmer
3.757
233940AF2-379 C
Solar/Wind Harmer
-0.002
234015AF2-250 C
Solar/Wind Harmer
-0.001
971195AH1-057 GEN
Solar/Wind Harmer
0.169
960671AF2-358 GEN
Solar/Wind Harmer
2.344
965821AG1-450 GEN
Solar/Wind Harmer
11.718
232426Y1-080 FULL
Solar/Wind Harmer
0
970277AG2-181 GEN
Solar/Wind Harmer
0.656
233946AB2-136 GEN
Solar/Wind Harmer
-0.002
233964AF2-378 GEN
Solar/Wind Harmer
0.001
234041AC1-190 GEN
Solar/Wind Harmer
1.17
233984AB2-036 GEN
Solar/Wind Harmer
2.121
233968AD2-076_GEN
Solar/Wind Harmer
1.12
234014AF1-036_GEN
Solar/Wind Harmer
0.457
970597AG2-380 GEN
Solar/Wind Harmer
9.142
234012AE2-112_GEN
Solar/Wind Harmer
0.389
971983AH1-536 GEN
Solar/Wind Harmer
0.947
970453AG2-297 GEN
Solar/Wind Harmer
0.324
971553AH1-274 GEN
Solar/Wind Harmer
0.277
230422AE1-104_GEN1
Solar/Wind Harmer
67.768
230425AE1-104_GEN2
Solar/Wind Harmer
67.768
945431AF1-208 GEN
Solar/Wind Harmer
0.731
230433AD2-135 GEN
Solar/Wind Harmer
0
970997AG2-616 GEN
Solar/Wind Harmer
0.804
972141AH1-641 GEN
Solar/Wind Harmer
0.241
230430AE1-229_GEN
Solar/Wind Harmer
-0.002
228754AB1-001 C
Solar/Wind Harmer
-0.002
228351V2-046C
Solar/Wind Harmer
-0.002
971535AH1-265 GEN
Solar/Wind Harmer
0.466
230407AD2-065 C
Solar/Wind Harmer
0
971011AG2-627 GEN
Solar/Wind Harmer
0.626
218660EHAMPSOLAR C
Solar/Wind Harmer
-0.001
219137THOSOLAR C
Solar/Wind Harmer
0.001
219623KINSLEYBEA C
Solar/Wind Harmer
-0.001
219258KINSLEYDEP C
Solar/Wind Harmer
-0.001
219766PARADISE C
Solar/Wind Harmer
-0.001
219907AC1-030 C
Solar/Wind Harmer
-0.001
219236SOUTHERNHQ C
Solar/Wind Harmer
-0.001
219906AC1-017 C
Solar/Wind Harmer
-0.001
219615MILLCREEK C
Solar/Wind Harmer
-0.001
207500AE2-000G1
Solar/Wind Harmer
50.139
207497AE2-000G2
Solar/Wind Harmer
50.139
207507AE2-000G3
Solar/Wind Harmer
50.139
207487AE2-000G4
Solar/Wind Harmer
50.139
207522AF2-254 C
Solar/Wind Harmer
0.127
970025AG2-016 GEN
Solar/Wind Harmer
0.249
971189AH1-054 GEN
Solar/Wind Harmer
0.103
971667AH1-334 GEN
Solar/Wind Harmer
0.237
214067T20SOLAR
Solar/Wind Harmer
-0.001
219727YARDVSOLFA C
Solar/Wind Harmer
0.001
20714328BYD_X4-031
Solar/Wind Harmer
0.023
20714428HOW_X1-037
Solar/Wind Harmer
-0.001
20720628TIN_W1-124
Solar/Wind Harmer
-0.001
219276PARKLANDSO C
Solar/Wind Harmer
0
20742028HF_AC1-207
Solar/Wind Harmer
-0.001
971521AH1-258 GEN
Solar/Wind Harmer
0.211
219620RIDERU C
Solar/Wind Harmer
-0.001
219817TRENTONSOL C
Solar/Wind Harmer
0.001
967451AG2-055 C O1
Solar/Wind Harmer
238.055
219918AC2-009 C
Solar/Wind Harmer
0
219612MATRIX C
Solar/Wind Harmer
0.001
218438BLK ROCK C
Solar/Wind Harmer
0
218526CNTRALGAS2 C
Solar/Wind Harmer
0.001
218524CNTRALGAS1 C
Solar/Wind Harmer
0.001
218428ETC SOLAR C
Solar/Wind Harmer
0
217213AMBOY SO C
Solar/Wind Harmer
-0.001
219249CENTRALDIV C
Solar/Wind Harmer
0
218449LINSOLAR C
Solar/Wind Harmer
0.001
217081WEATEXAS C
Solar/Wind Harmer
0
20673828FLE_V3-070
Solar/Wind Harmer
0.066
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
20675428EAM_W2-061
Solar/Wind Harmer
0
217206BARNGR HS C
Solar/Wind Harmer
0
217208PARK ELE C
Solar/Wind Harmer
0
207439AE1-081 C O1
Solar/Wind Harmer
0
20676328BVR_Y1-020
Solar/Wind Harmer
0
20674628WNG_W3-110
Solar/Wind Harmer
-0.001
207511W3-106 GEN
Solar/Wind Harmer
0.038
971009AG2-626 GEN
Solar/Wind Harmer
0.088
971007AG2-625 GEN
Solar/Wind Harmer
0.138
971519AH1-257 GEN
Solar/Wind Harmer
0.135
207437AD2-070 GEN
Solar/Wind Harmer
-0.001
966111AG1-480 GEN
Solar/Wind Harmer
0
966111AG1-480 GEN
Solar/Wind Harmer
2.258
966181AG1-487 GEN
Solar/Wind Harmer
0
966181AG1-487 GEN
Solar/Wind Harmer
2.513
209029WAYMART-WD
Solar/Wind Harmer
3.876
970095AG2-074 GEN
Solar/Wind Harmer
0.192
G-007ALTFEXP_G-007A->PJM
CMTX
48.562
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.988
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.377
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
16.328
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
3.49
BlueGrassPJM->LTFIMP_BlueG
CLTF
10.871
CBM NorthLTFEXP_CBM-N->PJM
CBM
54.599
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
116.702

Details for ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:PJM
Facility Description:
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.42 %
Rating:2863.0 MVA
Rating Type:A
MVA to Mitigate:3189.86
MW Contribution:0.56
Bus #Bus NameTypeMW Contribution
200203Y1-065-STG
50/50
20.977
200204Y1-065-CTG1
50/50
13.209
200205Y1-065-CTG2
50/50
13.209
200052ROCKSP 1
50/50
156.715
200053ROCKSP 2
50/50
156.715
200054ROCKSP 3
50/50
155.124
200055ROCKSP 4
50/50
155.124
231914HR8
50/50
4.954
231911HR5
50/50
3.385
231912HR6
50/50
3.385
231913HR7
50/50
3.385
233920W3-032A-CTG1
50/50
5.086
233921W3-032A-STG1
50/50
2.936
232616GEN FOOD
50/50
0.384
232901NORTHST
50/50
21.261
232904IR4
50/50
201.939
232920IR10
50/50
7.666
232921TASLEY2G
50/50
0.831
232905CHERITON_25
50/50
0.315
232912OH NUG1
50/50
20.735
232913OH NUG2
50/50
20.735
232914OH NUG3
50/50
20.735
232915OH NUG4
50/50
20.735
232916OH NUG5
50/50
20.735
232917OH NUG6
50/50
20.735
232918OH NUG7
50/50
20.735
234034AF2-060
50/50
4.147
232926CRISFLD1
50/50
0.252
232907VN8
50/50
54.159
233900O-025 C
50/50
0.151
231940T-011
50/50
0.126
232919VN10
50/50
7.12
232910NRG_G1
50/50
1.092
232911NRG_G2
50/50
1.092
971149AH1-027 GEN
Solar/Wind Harmer
0.578
233987AB2-037 GEN
Solar/Wind Harmer
0
233972AC1-094 C
Solar/Wind Harmer
-0.002
970695AG2-447 GEN
Solar/Wind Harmer
0.462
234033AF1-007_GEN
Solar/Wind Harmer
48.222
970545AG2-347 GEN
Solar/Wind Harmer
198.641
972133AH1-634 GEN
Solar/Wind Harmer
30.097
972069AH1-584 GEN
Solar/Wind Harmer
1.152
972071AH1-585 GEN
Solar/Wind Harmer
1.152
972073AH1-586 GEN
Solar/Wind Harmer
20.735
971747AH1-380 GEN
Solar/Wind Harmer
0.461
233923SMA
Solar/Wind Harmer
-0.002
233998TM1NIN_3.36
Solar/Wind Harmer
-0.002
233997TMININ_4.2
Solar/Wind Harmer
-0.002
233996TM1833_GEN
Solar/Wind Harmer
-0.002
233940AF2-379 C
Solar/Wind Harmer
-0.002
233990AG1-397 GEN
Solar/Wind Harmer
-0.001
233990AG1-397 GEN
Solar/Wind Harmer
3.685
972177AH1-672 GEN
Solar/Wind Harmer
1.727
234015AF2-250 C
Solar/Wind Harmer
-0.001
971195AH1-057 GEN
Solar/Wind Harmer
0.166
960671AF2-358 GEN
Solar/Wind Harmer
2.299
965821AG1-450 GEN
Solar/Wind Harmer
11.493
232426Y1-080 FULL
Solar/Wind Harmer
0
970277AG2-181 GEN
Solar/Wind Harmer
0.643
233946AB2-136 GEN
Solar/Wind Harmer
-0.002
233964AF2-378 GEN
Solar/Wind Harmer
0.001
234041AC1-190 GEN
Solar/Wind Harmer
1.147
233984AB2-036 GEN
Solar/Wind Harmer
2.078
233968AD2-076_GEN
Solar/Wind Harmer
1.096
234014AF1-036_GEN
Solar/Wind Harmer
0.447
970597AG2-380 GEN
Solar/Wind Harmer
8.949
234012AE2-112_GEN
Solar/Wind Harmer
0.38
971983AH1-536 GEN
Solar/Wind Harmer
0.927
970453AG2-297 GEN
Solar/Wind Harmer
0.295
971553AH1-274 GEN
Solar/Wind Harmer
0.251
230422AE1-104_GEN1
Solar/Wind Harmer
61.216
230425AE1-104_GEN2
Solar/Wind Harmer
61.216
945431AF1-208 GEN
Solar/Wind Harmer
0.658
230433AD2-135 GEN
Solar/Wind Harmer
0
970997AG2-616 GEN
Solar/Wind Harmer
0.722
972141AH1-641 GEN
Solar/Wind Harmer
0.216
230430AE1-229_GEN
Solar/Wind Harmer
-0.001
228754AB1-001 C
Solar/Wind Harmer
-0.001
228351V2-046C
Solar/Wind Harmer
-0.001
971535AH1-265 GEN
Solar/Wind Harmer
0.417
230407AD2-065 C
Solar/Wind Harmer
0
971011AG2-627 GEN
Solar/Wind Harmer
0.557
218660EHAMPSOLAR C
Solar/Wind Harmer
-0.001
219137THOSOLAR C
Solar/Wind Harmer
0.001
219623KINSLEYBEA C
Solar/Wind Harmer
-0.001
219258KINSLEYDEP C
Solar/Wind Harmer
0
219766PARADISE C
Solar/Wind Harmer
-0.001
219907AC1-030 C
Solar/Wind Harmer
-0.001
219236SOUTHERNHQ C
Solar/Wind Harmer
-0.001
207500AE2-000G1
Solar/Wind Harmer
42.304
207497AE2-000G2
Solar/Wind Harmer
42.304
207507AE2-000G3
Solar/Wind Harmer
42.304
207487AE2-000G4
Solar/Wind Harmer
42.304
207522AF2-254 C
Solar/Wind Harmer
0.107
219906AC1-017 C
Solar/Wind Harmer
-0.001
219615MILLCREEK C
Solar/Wind Harmer
-0.001
970025AG2-016 GEN
Solar/Wind Harmer
0.209
971189AH1-054 GEN
Solar/Wind Harmer
0.086
971667AH1-334 GEN
Solar/Wind Harmer
0.197
214067T20SOLAR
Solar/Wind Harmer
-0.001
20714328BYD_X4-031
Solar/Wind Harmer
0.018
20714428HOW_X1-037
Solar/Wind Harmer
-0.001
219727YARDVSOLFA C
Solar/Wind Harmer
0.001
20720628TIN_W1-124
Solar/Wind Harmer
-0.001
20742028HF_AC1-207
Solar/Wind Harmer
-0.001
219276PARKLANDSO C
Solar/Wind Harmer
0
971521AH1-258 GEN
Solar/Wind Harmer
0.169
967451AG2-055 C O1
Solar/Wind Harmer
189.08
219620RIDERU C
Solar/Wind Harmer
-0.001
219817TRENTONSOL C
Solar/Wind Harmer
0.001
219918AC2-009 C
Solar/Wind Harmer
0
219612MATRIX C
Solar/Wind Harmer
0
218438BLK ROCK C
Solar/Wind Harmer
0
218526CNTRALGAS2 C
Solar/Wind Harmer
0.001
218524CNTRALGAS1 C
Solar/Wind Harmer
0.001
218428ETC SOLAR C
Solar/Wind Harmer
0
217213AMBOY SO C
Solar/Wind Harmer
-0.001
219249CENTRALDIV C
Solar/Wind Harmer
0
218449LINSOLAR C
Solar/Wind Harmer
0
217081WEATEXAS C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
20673828FLE_V3-070
Solar/Wind Harmer
0.048
217206BARNGR HS C
Solar/Wind Harmer
0
217208PARK ELE C
Solar/Wind Harmer
0
20675428EAM_W2-061
Solar/Wind Harmer
0
207439AE1-081 C O1
Solar/Wind Harmer
0
20676328BVR_Y1-020
Solar/Wind Harmer
0
20674628WNG_W3-110
Solar/Wind Harmer
-0.001
207511W3-106 GEN
Solar/Wind Harmer
0.027
G-007ALTFEXP_G-007A->PJM
CMTX
37.85
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.336
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.994
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
13.87
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
2.969
BlueGrassPJM->LTFIMP_BlueG
CLTF
9.247
CBM NorthLTFEXP_CBM-N->PJM
CBM
38.572
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
87.612

Details for ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line l/o DPL_P7_1_DBL_5NC_SRT-A


Base Case Flowgate

Area:PJM
Facility Description:
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line
Contingency Name:
DPL_P7_1_DBL_5NC_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:109.52 %
Rating:3106.0 MVA
Rating Type:B
MVA to Mitigate:3401.81
MW Contribution:0.53
Bus #Bus NameTypeMW Contribution
200203Y1-065-STG
50/50
21.258
200204Y1-065-CTG1
50/50
13.386
200205Y1-065-CTG2
50/50
13.386
200052ROCKSP 1
50/50
158.818
200053ROCKSP 2
50/50
158.818
200054ROCKSP 3
50/50
157.205
200055ROCKSP 4
50/50
157.205
231914HR8
50/50
5.432
231911HR5
50/50
3.711
231912HR6
50/50
3.711
231913HR7
50/50
3.711
232907VN8
50/50
60.194
232919VN10
50/50
7.909
232926CRISFLD1
50/50
0.279
232921TASLEY2G
50/50
0.921
232905CHERITON_25
50/50
0.349
232912OH NUG1
50/50
22.975
232913OH NUG2
50/50
22.975
232914OH NUG3
50/50
22.975
232915OH NUG4
50/50
22.975
232916OH NUG5
50/50
22.975
232917OH NUG6
50/50
22.975
232918OH NUG7
50/50
22.975
234034AF2-060
50/50
4.595
233900O-025 C
50/50
0.167
231940T-011
50/50
0.139
232920IR10
50/50
8.474
232904IR4
50/50
223.175
233920W3-032A-CTG1
50/50
5.572
233921W3-032A-STG1
50/50
3.217
232616GEN FOOD
50/50
0.421
232901NORTHST
50/50
23.293
232910NRG_G1
50/50
1.208
232911NRG_G2
50/50
1.208
233987AB2-037 GEN
Solar/Wind Harmer
0
960671AF2-358 GEN
Solar/Wind Harmer
2.554
965821AG1-450 GEN
Solar/Wind Harmer
12.771
232426Y1-080 FULL
Solar/Wind Harmer
-0.001
970277AG2-181 GEN
Solar/Wind Harmer
0.715
233923SMA
Solar/Wind Harmer
-0.003
233998TM1NIN_3.36
Solar/Wind Harmer
-0.003
233997TMININ_4.2
Solar/Wind Harmer
-0.003
233996TM1833_GEN
Solar/Wind Harmer
-0.003
233946AB2-136 GEN
Solar/Wind Harmer
-0.003
233940AF2-379 C
Solar/Wind Harmer
-0.003
233964AF2-378 GEN
Solar/Wind Harmer
0.001
234041AC1-190 GEN
Solar/Wind Harmer
1.276
971747AH1-380 GEN
Solar/Wind Harmer
0.51
972069AH1-584 GEN
Solar/Wind Harmer
1.276
972071AH1-585 GEN
Solar/Wind Harmer
1.276
972073AH1-586 GEN
Solar/Wind Harmer
22.968
234015AF2-250 C
Solar/Wind Harmer
-0.001
971195AH1-057 GEN
Solar/Wind Harmer
0.184
233990AG1-397 GEN
Solar/Wind Harmer
-0.001
233990AG1-397 GEN
Solar/Wind Harmer
4.082
234033AF1-007_GEN
Solar/Wind Harmer
53.293
970545AG2-347 GEN
Solar/Wind Harmer
219.531
972133AH1-634 GEN
Solar/Wind Harmer
33.262
972177AH1-672 GEN
Solar/Wind Harmer
1.906
971149AH1-027 GEN
Solar/Wind Harmer
0.633
233984AB2-036 GEN
Solar/Wind Harmer
2.327
233972AC1-094 C
Solar/Wind Harmer
-0.003
970695AG2-447 GEN
Solar/Wind Harmer
0.504
233968AD2-076_GEN
Solar/Wind Harmer
1.229
234014AF1-036_GEN
Solar/Wind Harmer
0.502
970597AG2-380 GEN
Solar/Wind Harmer
10.031
234012AE2-112_GEN
Solar/Wind Harmer
0.426
971983AH1-536 GEN
Solar/Wind Harmer
1.04
970453AG2-297 GEN
Solar/Wind Harmer
0.294
971553AH1-274 GEN
Solar/Wind Harmer
0.247
230422AE1-104_GEN1
Solar/Wind Harmer
60.55
230425AE1-104_GEN2
Solar/Wind Harmer
60.55
945431AF1-208 GEN
Solar/Wind Harmer
0.641
230433AD2-135 GEN
Solar/Wind Harmer
0
228754AB1-001 C
Solar/Wind Harmer
-0.001
970997AG2-616 GEN
Solar/Wind Harmer
0.7
972141AH1-641 GEN
Solar/Wind Harmer
0.21
230430AE1-229_GEN
Solar/Wind Harmer
-0.001
971535AH1-265 GEN
Solar/Wind Harmer
0.406
228351V2-046C
Solar/Wind Harmer
-0.001
230407AD2-065 C
Solar/Wind Harmer
0
971011AG2-627 GEN
Solar/Wind Harmer
0.534
218660EHAMPSOLAR C
Solar/Wind Harmer
-0.001
219137THOSOLAR C
Solar/Wind Harmer
0.001
219623KINSLEYBEA C
Solar/Wind Harmer
-0.001
219258KINSLEYDEP C
Solar/Wind Harmer
0
219766PARADISE C
Solar/Wind Harmer
-0.001
207500AE2-000G1
Solar/Wind Harmer
41.118
207497AE2-000G2
Solar/Wind Harmer
41.118
207507AE2-000G3
Solar/Wind Harmer
41.118
207487AE2-000G4
Solar/Wind Harmer
41.118
207522AF2-254 C
Solar/Wind Harmer
0.103
970025AG2-016 GEN
Solar/Wind Harmer
0.203
971189AH1-054 GEN
Solar/Wind Harmer
0.083
219907AC1-030 C
Solar/Wind Harmer
-0.001
219236SOUTHERNHQ C
Solar/Wind Harmer
-0.001
971667AH1-334 GEN
Solar/Wind Harmer
0.191
219906AC1-017 C
Solar/Wind Harmer
-0.001
219615MILLCREEK C
Solar/Wind Harmer
-0.001
20714328BYD_X4-031
Solar/Wind Harmer
0.018
20714428HOW_X1-037
Solar/Wind Harmer
-0.001
214067T20SOLAR
Solar/Wind Harmer
-0.001
20720628TIN_W1-124
Solar/Wind Harmer
-0.001
219727YARDVSOLFA C
Solar/Wind Harmer
0.001
20742028HF_AC1-207
Solar/Wind Harmer
-0.001
971521AH1-258 GEN
Solar/Wind Harmer
0.163
967451AG2-055 C O1
Solar/Wind Harmer
182.443
219276PARKLANDSO C
Solar/Wind Harmer
0
219620RIDERU C
Solar/Wind Harmer
-0.001
219817TRENTONSOL C
Solar/Wind Harmer
0.001
219918AC2-009 C
Solar/Wind Harmer
0
219612MATRIX C
Solar/Wind Harmer
0
218438BLK ROCK C
Solar/Wind Harmer
0
218526CNTRALGAS2 C
Solar/Wind Harmer
0.001
218524CNTRALGAS1 C
Solar/Wind Harmer
0.001
218428ETC SOLAR C
Solar/Wind Harmer
0
217213AMBOY SO C
Solar/Wind Harmer
-0.001
219249CENTRALDIV C
Solar/Wind Harmer
0
218449LINSOLAR C
Solar/Wind Harmer
0
217081WEATEXAS C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
217206BARNGR HS C
Solar/Wind Harmer
0
20673828FLE_V3-070
Solar/Wind Harmer
0.045
217208PARK ELE C
Solar/Wind Harmer
0
20675428EAM_W2-061
Solar/Wind Harmer
0
207439AE1-081 C O1
Solar/Wind Harmer
0
20676328BVR_Y1-020
Solar/Wind Harmer
0
20674628WNG_W3-110
Solar/Wind Harmer
-0.001
207511W3-106 GEN
Solar/Wind Harmer
0.026
G-007ALTFEXP_G-007A->PJM
CMTX
36.119
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.321
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.986
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
13.863
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
2.969
BlueGrassPJM->LTFIMP_BlueG
CLTF
9.245
CBM NorthLTFEXP_CBM-N->PJM
CBM
35.815
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
82.806

Details for ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line l/o PECO_P4_NOTTI785_SRT-A


Base Case Flowgate

Area:PJM
Facility Description:
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line
Contingency Name:
PECO_P4_NOTTI785_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.6 %
Rating:3106.0 MVA
Rating Type:B
MVA to Mitigate:3373.03
MW Contribution:0.58
Bus #Bus NameTypeMW Contribution
200203Y1-065-STG
50/50
21.097
200204Y1-065-CTG1
50/50
13.285
200205Y1-065-CTG2
50/50
13.285
200052ROCKSP 1
50/50
157.618
200053ROCKSP 2
50/50
157.618
200054ROCKSP 3
50/50
156.018
200055ROCKSP 4
50/50
156.018
231914HR8
50/50
5.11
231911HR5
50/50
3.491
231912HR6
50/50
3.491
231913HR7
50/50
3.491
232907VN8
50/50
56.161
233920W3-032A-CTG1
50/50
5.255
233921W3-032A-STG1
50/50
3.034
232616GEN FOOD
50/50
0.397
232901NORTHST
50/50
21.969
232926CRISFLD1
50/50
0.261
232921TASLEY2G
50/50
0.861
232905CHERITON_25
50/50
0.327
232912OH NUG1
50/50
21.487
232913OH NUG2
50/50
21.487
232914OH NUG3
50/50
21.487
232915OH NUG4
50/50
21.487
232916OH NUG5
50/50
21.487
232917OH NUG6
50/50
21.487
232918OH NUG7
50/50
21.487
234034AF2-060
50/50
4.297
232904IR4
50/50
209.133
232920IR10
50/50
7.94
233900O-025 C
50/50
0.157
231940T-011
50/50
0.13
232919VN10
50/50
7.385
232910NRG_G1
50/50
1.136
232911NRG_G2
50/50
1.136
233987AB2-037 GEN
Solar/Wind Harmer
0
971149AH1-027 GEN
Solar/Wind Harmer
0.597
233923SMA
Solar/Wind Harmer
-0.002
233998TM1NIN_3.36
Solar/Wind Harmer
-0.002
233997TMININ_4.2
Solar/Wind Harmer
-0.002
233996TM1833_GEN
Solar/Wind Harmer
-0.002
234033AF1-007_GEN
Solar/Wind Harmer
49.94
970545AG2-347 GEN
Solar/Wind Harmer
205.718
972133AH1-634 GEN
Solar/Wind Harmer
31.169
972069AH1-584 GEN
Solar/Wind Harmer
1.194
972071AH1-585 GEN
Solar/Wind Harmer
1.194
972073AH1-586 GEN
Solar/Wind Harmer
21.486
971747AH1-380 GEN
Solar/Wind Harmer
0.477
233940AF2-379 C
Solar/Wind Harmer
-0.002
233990AG1-397 GEN
Solar/Wind Harmer
-0.001
233990AG1-397 GEN
Solar/Wind Harmer
3.819
234015AF2-250 C
Solar/Wind Harmer
-0.001
971195AH1-057 GEN
Solar/Wind Harmer
0.172
972177AH1-672 GEN
Solar/Wind Harmer
1.789
233972AC1-094 C
Solar/Wind Harmer
-0.002
970695AG2-447 GEN
Solar/Wind Harmer
0.477
960671AF2-358 GEN
Solar/Wind Harmer
2.385
965821AG1-450 GEN
Solar/Wind Harmer
11.923
232426Y1-080 FULL
Solar/Wind Harmer
0
970277AG2-181 GEN
Solar/Wind Harmer
0.668
233946AB2-136 GEN
Solar/Wind Harmer
-0.002
233964AF2-378 GEN
Solar/Wind Harmer
0.001
234041AC1-190 GEN
Solar/Wind Harmer
1.191
233984AB2-036 GEN
Solar/Wind Harmer
2.169
233968AD2-076_GEN
Solar/Wind Harmer
1.147
234014AF1-036_GEN
Solar/Wind Harmer
0.468
970597AG2-380 GEN
Solar/Wind Harmer
9.366
234012AE2-112_GEN
Solar/Wind Harmer
0.398
971983AH1-536 GEN
Solar/Wind Harmer
0.972
970453AG2-297 GEN
Solar/Wind Harmer
0.307
971553AH1-274 GEN
Solar/Wind Harmer
0.261
230422AE1-104_GEN1
Solar/Wind Harmer
63.622
230425AE1-104_GEN2
Solar/Wind Harmer
63.622
945431AF1-208 GEN
Solar/Wind Harmer
0.685
230433AD2-135 GEN
Solar/Wind Harmer
0
970997AG2-616 GEN
Solar/Wind Harmer
0.752
972141AH1-641 GEN
Solar/Wind Harmer
0.226
230430AE1-229_GEN
Solar/Wind Harmer
-0.001
228754AB1-001 C
Solar/Wind Harmer
-0.001
228351V2-046C
Solar/Wind Harmer
-0.001
971535AH1-265 GEN
Solar/Wind Harmer
0.435
230407AD2-065 C
Solar/Wind Harmer
0
971011AG2-627 GEN
Solar/Wind Harmer
0.582
218660EHAMPSOLAR C
Solar/Wind Harmer
-0.001
219137THOSOLAR C
Solar/Wind Harmer
0.001
219623KINSLEYBEA C
Solar/Wind Harmer
-0.001
219258KINSLEYDEP C
Solar/Wind Harmer
0
219766PARADISE C
Solar/Wind Harmer
-0.001
219907AC1-030 C
Solar/Wind Harmer
-0.001
219236SOUTHERNHQ C
Solar/Wind Harmer
-0.001
207500AE2-000G1
Solar/Wind Harmer
44.274
207497AE2-000G2
Solar/Wind Harmer
44.274
207507AE2-000G3
Solar/Wind Harmer
44.274
207487AE2-000G4
Solar/Wind Harmer
44.274
219906AC1-017 C
Solar/Wind Harmer
-0.001
219615MILLCREEK C
Solar/Wind Harmer
-0.001
207522AF2-254 C
Solar/Wind Harmer
0.112
970025AG2-016 GEN
Solar/Wind Harmer
0.219
971189AH1-054 GEN
Solar/Wind Harmer
0.09
971667AH1-334 GEN
Solar/Wind Harmer
0.207
214067T20SOLAR
Solar/Wind Harmer
-0.001
20714328BYD_X4-031
Solar/Wind Harmer
0.019
219727YARDVSOLFA C
Solar/Wind Harmer
0.001
20714428HOW_X1-037
Solar/Wind Harmer
-0.001
20720628TIN_W1-124
Solar/Wind Harmer
-0.001
219276PARKLANDSO C
Solar/Wind Harmer
0
20742028HF_AC1-207
Solar/Wind Harmer
-0.001
971521AH1-258 GEN
Solar/Wind Harmer
0.178
967451AG2-055 C O1
Solar/Wind Harmer
198.871
219620RIDERU C
Solar/Wind Harmer
-0.001
219817TRENTONSOL C
Solar/Wind Harmer
0.001
219918AC2-009 C
Solar/Wind Harmer
0
219612MATRIX C
Solar/Wind Harmer
0
218438BLK ROCK C
Solar/Wind Harmer
0
218526CNTRALGAS2 C
Solar/Wind Harmer
0.001
218524CNTRALGAS1 C
Solar/Wind Harmer
0.001
218428ETC SOLAR C
Solar/Wind Harmer
0
217213AMBOY SO C
Solar/Wind Harmer
-0.001
219249CENTRALDIV C
Solar/Wind Harmer
0
218449LINSOLAR C
Solar/Wind Harmer
0.001
217081WEATEXAS C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
20673828FLE_V3-070
Solar/Wind Harmer
0.051
217206BARNGR HS C
Solar/Wind Harmer
0
20675428EAM_W2-061
Solar/Wind Harmer
0
217208PARK ELE C
Solar/Wind Harmer
0
207439AE1-081 C O1
Solar/Wind Harmer
0
20676328BVR_Y1-020
Solar/Wind Harmer
0
20674628WNG_W3-110
Solar/Wind Harmer
-0.001
207511W3-106 GEN
Solar/Wind Harmer
0.029
971009AG2-626 GEN
Solar/Wind Harmer
0.065
971007AG2-625 GEN
Solar/Wind Harmer
0.103
971519AH1-257 GEN
Solar/Wind Harmer
0.1
G-007ALTFEXP_G-007A->PJM
CMTX
39.922
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.55
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.12
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
14.7
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
3.145
BlueGrassPJM->LTFIMP_BlueG
CLTF
9.797
CBM NorthLTFEXP_CBM-N->PJM
CBM
41.064
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
92.762

Details for ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line l/o PECO_P2-2_NOTT230B_SRT-A/* $ CHESCO $ PECO_P2-2_NOTT230B $ B


Base Case Flowgate

Area:PJM
Facility Description:
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line
Contingency Name:
PECO_P2-2_NOTT230B_SRT-A/* $ CHESCO $ PECO_P2-2_NOTT230B $ B
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:108.46 %
Rating:3106.0 MVA
Rating Type:B
MVA to Mitigate:3368.69
MW Contribution:0.58
Bus #Bus NameTypeMW Contribution
200203Y1-065-STG
50/50
21.097
200204Y1-065-CTG1
50/50
13.285
200205Y1-065-CTG2
50/50
13.285
200052ROCKSP 1
50/50
157.618
200053ROCKSP 2
50/50
157.618
200054ROCKSP 3
50/50
156.017
200055ROCKSP 4
50/50
156.017
231914HR8
50/50
5.108
231911HR5
50/50
3.489
231912HR6
50/50
3.489
231913HR7
50/50
3.489
233920W3-032A-CTG1
50/50
5.253
233921W3-032A-STG1
50/50
3.032
232616GEN FOOD
50/50
0.397
232901NORTHST
50/50
21.96
232907VN8
50/50
56.13
232926CRISFLD1
50/50
0.261
232921TASLEY2G
50/50
0.861
232905CHERITON_25
50/50
0.326
232912OH NUG1
50/50
21.476
232913OH NUG2
50/50
21.476
232914OH NUG3
50/50
21.476
232915OH NUG4
50/50
21.476
232916OH NUG5
50/50
21.476
232917OH NUG6
50/50
21.476
232918OH NUG7
50/50
21.476
234034AF2-060
50/50
4.295
232904IR4
50/50
209.026
232920IR10
50/50
7.936
233900O-025 C
50/50
0.156
231940T-011
50/50
0.13
232919VN10
50/50
7.381
232910NRG_G1
50/50
1.135
232911NRG_G2
50/50
1.135
233987AB2-037 GEN
Solar/Wind Harmer
0
971149AH1-027 GEN
Solar/Wind Harmer
0.597
233923SMA
Solar/Wind Harmer
-0.002
233998TM1NIN_3.36
Solar/Wind Harmer
-0.002
233997TMININ_4.2
Solar/Wind Harmer
-0.002
233996TM1833_GEN
Solar/Wind Harmer
-0.002
234033AF1-007_GEN
Solar/Wind Harmer
49.915
970545AG2-347 GEN
Solar/Wind Harmer
205.613
972133AH1-634 GEN
Solar/Wind Harmer
31.154
972069AH1-584 GEN
Solar/Wind Harmer
1.193
972071AH1-585 GEN
Solar/Wind Harmer
1.193
972073AH1-586 GEN
Solar/Wind Harmer
21.475
971747AH1-380 GEN
Solar/Wind Harmer
0.477
233940AF2-379 C
Solar/Wind Harmer
-0.002
233990AG1-397 GEN
Solar/Wind Harmer
-0.001
233990AG1-397 GEN
Solar/Wind Harmer
3.817
234015AF2-250 C
Solar/Wind Harmer
-0.001
971195AH1-057 GEN
Solar/Wind Harmer
0.172
233972AC1-094 C
Solar/Wind Harmer
-0.002
970695AG2-447 GEN
Solar/Wind Harmer
0.477
972177AH1-672 GEN
Solar/Wind Harmer
1.788
960671AF2-358 GEN
Solar/Wind Harmer
2.383
965821AG1-450 GEN
Solar/Wind Harmer
11.916
232426Y1-080 FULL
Solar/Wind Harmer
0
970277AG2-181 GEN
Solar/Wind Harmer
0.667
233946AB2-136 GEN
Solar/Wind Harmer
-0.002
233964AF2-378 GEN
Solar/Wind Harmer
0.001
234041AC1-190 GEN
Solar/Wind Harmer
1.19
233984AB2-036 GEN
Solar/Wind Harmer
2.167
233968AD2-076_GEN
Solar/Wind Harmer
1.146
234014AF1-036_GEN
Solar/Wind Harmer
0.468
970597AG2-380 GEN
Solar/Wind Harmer
9.358
234012AE2-112_GEN
Solar/Wind Harmer
0.398
971983AH1-536 GEN
Solar/Wind Harmer
0.971
970453AG2-297 GEN
Solar/Wind Harmer
0.307
971553AH1-274 GEN
Solar/Wind Harmer
0.261
230422AE1-104_GEN1
Solar/Wind Harmer
63.624
230425AE1-104_GEN2
Solar/Wind Harmer
63.624
945431AF1-208 GEN
Solar/Wind Harmer
0.685
230433AD2-135 GEN
Solar/Wind Harmer
0
970997AG2-616 GEN
Solar/Wind Harmer
0.752
972141AH1-641 GEN
Solar/Wind Harmer
0.226
230430AE1-229_GEN
Solar/Wind Harmer
-0.001
228754AB1-001 C
Solar/Wind Harmer
-0.001
228351V2-046C
Solar/Wind Harmer
-0.001
971535AH1-265 GEN
Solar/Wind Harmer
0.435
230407AD2-065 C
Solar/Wind Harmer
0
971011AG2-627 GEN
Solar/Wind Harmer
0.582
218660EHAMPSOLAR C
Solar/Wind Harmer
-0.001
219137THOSOLAR C
Solar/Wind Harmer
0.001
219623KINSLEYBEA C
Solar/Wind Harmer
-0.001
219258KINSLEYDEP C
Solar/Wind Harmer
0
219766PARADISE C
Solar/Wind Harmer
-0.001
219907AC1-030 C
Solar/Wind Harmer
-0.001
219236SOUTHERNHQ C
Solar/Wind Harmer
-0.001
207500AE2-000G1
Solar/Wind Harmer
44.28
207497AE2-000G2
Solar/Wind Harmer
44.28
207507AE2-000G3
Solar/Wind Harmer
44.28
207487AE2-000G4
Solar/Wind Harmer
44.28
219906AC1-017 C
Solar/Wind Harmer
-0.001
219615MILLCREEK C
Solar/Wind Harmer
-0.001
207522AF2-254 C
Solar/Wind Harmer
0.112
970025AG2-016 GEN
Solar/Wind Harmer
0.219
971189AH1-054 GEN
Solar/Wind Harmer
0.09
971667AH1-334 GEN
Solar/Wind Harmer
0.207
214067T20SOLAR
Solar/Wind Harmer
-0.001
20714328BYD_X4-031
Solar/Wind Harmer
0.019
219727YARDVSOLFA C
Solar/Wind Harmer
0.001
20714428HOW_X1-037
Solar/Wind Harmer
-0.001
20720628TIN_W1-124
Solar/Wind Harmer
-0.001
219276PARKLANDSO C
Solar/Wind Harmer
0
20742028HF_AC1-207
Solar/Wind Harmer
-0.001
971521AH1-258 GEN
Solar/Wind Harmer
0.178
967451AG2-055 C O1
Solar/Wind Harmer
198.92
219620RIDERU C
Solar/Wind Harmer
-0.001
219817TRENTONSOL C
Solar/Wind Harmer
0.001
219918AC2-009 C
Solar/Wind Harmer
0
219612MATRIX C
Solar/Wind Harmer
0
218438BLK ROCK C
Solar/Wind Harmer
0
218526CNTRALGAS2 C
Solar/Wind Harmer
0.001
218524CNTRALGAS1 C
Solar/Wind Harmer
0.001
218428ETC SOLAR C
Solar/Wind Harmer
0
217213AMBOY SO C
Solar/Wind Harmer
-0.001
219249CENTRALDIV C
Solar/Wind Harmer
0
218449LINSOLAR C
Solar/Wind Harmer
0.001
217081WEATEXAS C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
20673828FLE_V3-070
Solar/Wind Harmer
0.051
217206BARNGR HS C
Solar/Wind Harmer
0
20675428EAM_W2-061
Solar/Wind Harmer
0
217208PARK ELE C
Solar/Wind Harmer
0
207439AE1-081 C O1
Solar/Wind Harmer
0
20676328BVR_Y1-020
Solar/Wind Harmer
0
20674628WNG_W3-110
Solar/Wind Harmer
-0.001
207511W3-106 GEN
Solar/Wind Harmer
0.029
971009AG2-626 GEN
Solar/Wind Harmer
0.065
971007AG2-625 GEN
Solar/Wind Harmer
0.103
971519AH1-257 GEN
Solar/Wind Harmer
0.1
G-007ALTFEXP_G-007A->PJM
CMTX
39.934
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.548
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.119
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
14.689
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
3.143
BlueGrassPJM->LTFIMP_BlueG
CLTF
9.79
CBM NorthLTFEXP_CBM-N->PJM
CBM
41.09
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
92.797

Details for ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line l/o PECO_P1-2_PBS-NDELTA_SRT-A/* $ CHESCO $ PECO_P1-2_PBS-NDELTA $ L


Base Case Flowgate

Area:PJM
Facility Description:
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line
Contingency Name:
PECO_P1-2_PBS-NDELTA_SRT-A/* $ CHESCO $ PECO_P1-2_PBS-NDELTA $ L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.36 %
Rating:3106.0 MVA
Rating Type:B
MVA to Mitigate:3365.65
MW Contribution:0.56
Bus #Bus NameTypeMW Contribution
200203Y1-065-STG
50/50
20.942
200204Y1-065-CTG1
50/50
13.187
200205Y1-065-CTG2
50/50
13.187
200052ROCKSP 1
50/50
156.455
200053ROCKSP 2
50/50
156.455
200054ROCKSP 3
50/50
154.867
200055ROCKSP 4
50/50
154.867
231914HR8
50/50
4.94
231911HR5
50/50
3.375
231912HR6
50/50
3.375
231913HR7
50/50
3.375
233920W3-032A-CTG1
50/50
5.071
233921W3-032A-STG1
50/50
2.928
232616GEN FOOD
50/50
0.383
232901NORTHST
50/50
21.2
232904IR4
50/50
201.36
232920IR10
50/50
7.644
232921TASLEY2G
50/50
0.829
232905CHERITON_25
50/50
0.314
232912OH NUG1
50/50
20.675
232913OH NUG2
50/50
20.675
232914OH NUG3
50/50
20.675
232915OH NUG4
50/50
20.675
232916OH NUG5
50/50
20.675
232917OH NUG6
50/50
20.675
232918OH NUG7
50/50
20.675
234034AF2-060
50/50
4.135
232926CRISFLD1
50/50
0.251
232907VN8
50/50
54.004
233900O-025 C
50/50
0.151
231940T-011
50/50
0.125
232919VN10
50/50
7.1
232910NRG_G1
50/50
1.089
232911NRG_G2
50/50
1.089
971149AH1-027 GEN
Solar/Wind Harmer
0.576
233987AB2-037 GEN
Solar/Wind Harmer
0
233972AC1-094 C
Solar/Wind Harmer
-0.002
970695AG2-447 GEN
Solar/Wind Harmer
0.46
234033AF1-007_GEN
Solar/Wind Harmer
48.084
970545AG2-347 GEN
Solar/Wind Harmer
198.072
972133AH1-634 GEN
Solar/Wind Harmer
30.011
972069AH1-584 GEN
Solar/Wind Harmer
1.149
972071AH1-585 GEN
Solar/Wind Harmer
1.149
972073AH1-586 GEN
Solar/Wind Harmer
20.676
971747AH1-380 GEN
Solar/Wind Harmer
0.459
233923SMA
Solar/Wind Harmer
-0.002
233998TM1NIN_3.36
Solar/Wind Harmer
-0.002
233997TMININ_4.2
Solar/Wind Harmer
-0.002
233996TM1833_GEN
Solar/Wind Harmer
-0.002
233940AF2-379 C
Solar/Wind Harmer
-0.002
233990AG1-397 GEN
Solar/Wind Harmer
-0.001
233990AG1-397 GEN
Solar/Wind Harmer
3.675
972177AH1-672 GEN
Solar/Wind Harmer
1.722
234015AF2-250 C
Solar/Wind Harmer
-0.001
971195AH1-057 GEN
Solar/Wind Harmer
0.165
960671AF2-358 GEN
Solar/Wind Harmer
2.292
965821AG1-450 GEN
Solar/Wind Harmer
11.46
232426Y1-080 FULL
Solar/Wind Harmer
0
970277AG2-181 GEN
Solar/Wind Harmer
0.642
233946AB2-136 GEN
Solar/Wind Harmer
-0.002
233964AF2-378 GEN
Solar/Wind Harmer
0.001
234041AC1-190 GEN
Solar/Wind Harmer
1.144
233984AB2-036 GEN
Solar/Wind Harmer
2.072
233968AD2-076_GEN
Solar/Wind Harmer
1.093
234014AF1-036_GEN
Solar/Wind Harmer
0.446
970597AG2-380 GEN
Solar/Wind Harmer
8.923
234012AE2-112_GEN
Solar/Wind Harmer
0.379
971983AH1-536 GEN
Solar/Wind Harmer
0.924
970453AG2-297 GEN
Solar/Wind Harmer
0.294
971553AH1-274 GEN
Solar/Wind Harmer
0.25
230422AE1-104_GEN1
Solar/Wind Harmer
60.942
230425AE1-104_GEN2
Solar/Wind Harmer
60.942
945431AF1-208 GEN
Solar/Wind Harmer
0.655
230433AD2-135 GEN
Solar/Wind Harmer
0
970997AG2-616 GEN
Solar/Wind Harmer
0.718
972141AH1-641 GEN
Solar/Wind Harmer
0.215
230430AE1-229_GEN
Solar/Wind Harmer
-0.001
228754AB1-001 C
Solar/Wind Harmer
-0.001
228351V2-046C
Solar/Wind Harmer
-0.001
971535AH1-265 GEN
Solar/Wind Harmer
0.415
230407AD2-065 C
Solar/Wind Harmer
0
971011AG2-627 GEN
Solar/Wind Harmer
0.555
218660EHAMPSOLAR C
Solar/Wind Harmer
-0.001
219137THOSOLAR C
Solar/Wind Harmer
0.001
219623KINSLEYBEA C
Solar/Wind Harmer
-0.001
219258KINSLEYDEP C
Solar/Wind Harmer
0
219766PARADISE C
Solar/Wind Harmer
-0.001
219907AC1-030 C
Solar/Wind Harmer
-0.001
219236SOUTHERNHQ C
Solar/Wind Harmer
-0.001
207500AE2-000G1
Solar/Wind Harmer
42.045
207497AE2-000G2
Solar/Wind Harmer
42.045
207507AE2-000G3
Solar/Wind Harmer
42.045
207487AE2-000G4
Solar/Wind Harmer
42.045
207522AF2-254 C
Solar/Wind Harmer
0.106
219906AC1-017 C
Solar/Wind Harmer
-0.001
219615MILLCREEK C
Solar/Wind Harmer
-0.001
970025AG2-016 GEN
Solar/Wind Harmer
0.208
971189AH1-054 GEN
Solar/Wind Harmer
0.085
971667AH1-334 GEN
Solar/Wind Harmer
0.196
214067T20SOLAR
Solar/Wind Harmer
-0.001
20714328BYD_X4-031
Solar/Wind Harmer
0.018
20714428HOW_X1-037
Solar/Wind Harmer
-0.001
219727YARDVSOLFA C
Solar/Wind Harmer
0.001
20720628TIN_W1-124
Solar/Wind Harmer
-0.001
20742028HF_AC1-207
Solar/Wind Harmer
-0.001
219276PARKLANDSO C
Solar/Wind Harmer
0
971521AH1-258 GEN
Solar/Wind Harmer
0.168
967451AG2-055 C O1
Solar/Wind Harmer
187.624
219620RIDERU C
Solar/Wind Harmer
-0.001
219817TRENTONSOL C
Solar/Wind Harmer
0.001
219918AC2-009 C
Solar/Wind Harmer
0
219612MATRIX C
Solar/Wind Harmer
0
218438BLK ROCK C
Solar/Wind Harmer
0
218526CNTRALGAS2 C
Solar/Wind Harmer
0.001
218524CNTRALGAS1 C
Solar/Wind Harmer
0.001
218428ETC SOLAR C
Solar/Wind Harmer
0
217213AMBOY SO C
Solar/Wind Harmer
-0.001
219249CENTRALDIV C
Solar/Wind Harmer
0
218449LINSOLAR C
Solar/Wind Harmer
0
217081WEATEXAS C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
20673828FLE_V3-070
Solar/Wind Harmer
0.048
217206BARNGR HS C
Solar/Wind Harmer
0
217208PARK ELE C
Solar/Wind Harmer
0
20675428EAM_W2-061
Solar/Wind Harmer
0
207439AE1-081 C O1
Solar/Wind Harmer
0
20676328BVR_Y1-020
Solar/Wind Harmer
0
20674628WNG_W3-110
Solar/Wind Harmer
-0.001
207511W3-106 GEN
Solar/Wind Harmer
0.027
G-007ALTFEXP_G-007A->PJM
CMTX
37.533
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.412
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.04
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
14.211
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
3.043
BlueGrassPJM->LTFIMP_BlueG
CLTF
9.476
CBM NorthLTFEXP_CBM-N->PJM
CBM
37.925
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
86.76

Details for ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line l/o PECO_P1-2_5034_SRT-A/* $ CHESCO $ PECO_P1-2_5034 $ L


Base Case Flowgate

Area:PJM
Facility Description:
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line
Contingency Name:
PECO_P1-2_5034_SRT-A/* $ CHESCO $ PECO_P1-2_5034 $ L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.36 %
Rating:3106.0 MVA
Rating Type:B
MVA to Mitigate:3365.65
MW Contribution:0.56
Bus #Bus NameTypeMW Contribution
200203Y1-065-STG
50/50
20.942
200204Y1-065-CTG1
50/50
13.187
200205Y1-065-CTG2
50/50
13.187
200052ROCKSP 1
50/50
156.455
200053ROCKSP 2
50/50
156.455
200054ROCKSP 3
50/50
154.867
200055ROCKSP 4
50/50
154.867
231914HR8
50/50
4.94
231911HR5
50/50
3.375
231912HR6
50/50
3.375
231913HR7
50/50
3.375
233920W3-032A-CTG1
50/50
5.071
233921W3-032A-STG1
50/50
2.928
232616GEN FOOD
50/50
0.383
232901NORTHST
50/50
21.2
232904IR4
50/50
201.36
232920IR10
50/50
7.644
232921TASLEY2G
50/50
0.829
232905CHERITON_25
50/50
0.314
232912OH NUG1
50/50
20.675
232913OH NUG2
50/50
20.675
232914OH NUG3
50/50
20.675
232915OH NUG4
50/50
20.675
232916OH NUG5
50/50
20.675
232917OH NUG6
50/50
20.675
232918OH NUG7
50/50
20.675
234034AF2-060
50/50
4.135
232926CRISFLD1
50/50
0.251
232907VN8
50/50
54.004
233900O-025 C
50/50
0.151
231940T-011
50/50
0.125
232919VN10
50/50
7.1
232910NRG_G1
50/50
1.089
232911NRG_G2
50/50
1.089
971149AH1-027 GEN
Solar/Wind Harmer
0.576
233987AB2-037 GEN
Solar/Wind Harmer
0
233972AC1-094 C
Solar/Wind Harmer
-0.002
970695AG2-447 GEN
Solar/Wind Harmer
0.46
234033AF1-007_GEN
Solar/Wind Harmer
48.084
970545AG2-347 GEN
Solar/Wind Harmer
198.072
972133AH1-634 GEN
Solar/Wind Harmer
30.011
972069AH1-584 GEN
Solar/Wind Harmer
1.149
972071AH1-585 GEN
Solar/Wind Harmer
1.149
972073AH1-586 GEN
Solar/Wind Harmer
20.676
971747AH1-380 GEN
Solar/Wind Harmer
0.459
233923SMA
Solar/Wind Harmer
-0.002
233998TM1NIN_3.36
Solar/Wind Harmer
-0.002
233997TMININ_4.2
Solar/Wind Harmer
-0.002
233996TM1833_GEN
Solar/Wind Harmer
-0.002
233940AF2-379 C
Solar/Wind Harmer
-0.002
233990AG1-397 GEN
Solar/Wind Harmer
-0.001
233990AG1-397 GEN
Solar/Wind Harmer
3.675
972177AH1-672 GEN
Solar/Wind Harmer
1.722
234015AF2-250 C
Solar/Wind Harmer
-0.001
971195AH1-057 GEN
Solar/Wind Harmer
0.165
960671AF2-358 GEN
Solar/Wind Harmer
2.292
965821AG1-450 GEN
Solar/Wind Harmer
11.46
232426Y1-080 FULL
Solar/Wind Harmer
0
970277AG2-181 GEN
Solar/Wind Harmer
0.642
233946AB2-136 GEN
Solar/Wind Harmer
-0.002
233964AF2-378 GEN
Solar/Wind Harmer
0.001
234041AC1-190 GEN
Solar/Wind Harmer
1.144
233984AB2-036 GEN
Solar/Wind Harmer
2.072
233968AD2-076_GEN
Solar/Wind Harmer
1.093
234014AF1-036_GEN
Solar/Wind Harmer
0.446
970597AG2-380 GEN
Solar/Wind Harmer
8.923
234012AE2-112_GEN
Solar/Wind Harmer
0.379
971983AH1-536 GEN
Solar/Wind Harmer
0.924
970453AG2-297 GEN
Solar/Wind Harmer
0.294
971553AH1-274 GEN
Solar/Wind Harmer
0.25
230422AE1-104_GEN1
Solar/Wind Harmer
60.942
230425AE1-104_GEN2
Solar/Wind Harmer
60.942
945431AF1-208 GEN
Solar/Wind Harmer
0.655
230433AD2-135 GEN
Solar/Wind Harmer
0
970997AG2-616 GEN
Solar/Wind Harmer
0.718
972141AH1-641 GEN
Solar/Wind Harmer
0.215
230430AE1-229_GEN
Solar/Wind Harmer
-0.001
228754AB1-001 C
Solar/Wind Harmer
-0.001
228351V2-046C
Solar/Wind Harmer
-0.001
971535AH1-265 GEN
Solar/Wind Harmer
0.415
230407AD2-065 C
Solar/Wind Harmer
0
971011AG2-627 GEN
Solar/Wind Harmer
0.555
218660EHAMPSOLAR C
Solar/Wind Harmer
-0.001
219137THOSOLAR C
Solar/Wind Harmer
0.001
219623KINSLEYBEA C
Solar/Wind Harmer
-0.001
219258KINSLEYDEP C
Solar/Wind Harmer
0
219766PARADISE C
Solar/Wind Harmer
-0.001
219907AC1-030 C
Solar/Wind Harmer
-0.001
219236SOUTHERNHQ C
Solar/Wind Harmer
-0.001
207500AE2-000G1
Solar/Wind Harmer
42.045
207497AE2-000G2
Solar/Wind Harmer
42.045
207507AE2-000G3
Solar/Wind Harmer
42.045
207487AE2-000G4
Solar/Wind Harmer
42.045
207522AF2-254 C
Solar/Wind Harmer
0.106
219906AC1-017 C
Solar/Wind Harmer
-0.001
219615MILLCREEK C
Solar/Wind Harmer
-0.001
970025AG2-016 GEN
Solar/Wind Harmer
0.208
971189AH1-054 GEN
Solar/Wind Harmer
0.085
971667AH1-334 GEN
Solar/Wind Harmer
0.196
214067T20SOLAR
Solar/Wind Harmer
-0.001
20714328BYD_X4-031
Solar/Wind Harmer
0.018
20714428HOW_X1-037
Solar/Wind Harmer
-0.001
219727YARDVSOLFA C
Solar/Wind Harmer
0.001
20720628TIN_W1-124
Solar/Wind Harmer
-0.001
20742028HF_AC1-207
Solar/Wind Harmer
-0.001
219276PARKLANDSO C
Solar/Wind Harmer
0
971521AH1-258 GEN
Solar/Wind Harmer
0.168
967451AG2-055 C O1
Solar/Wind Harmer
187.624
219620RIDERU C
Solar/Wind Harmer
-0.001
219817TRENTONSOL C
Solar/Wind Harmer
0.001
219918AC2-009 C
Solar/Wind Harmer
0
219612MATRIX C
Solar/Wind Harmer
0
218438BLK ROCK C
Solar/Wind Harmer
0
218526CNTRALGAS2 C
Solar/Wind Harmer
0.001
218524CNTRALGAS1 C
Solar/Wind Harmer
0.001
218428ETC SOLAR C
Solar/Wind Harmer
0
217213AMBOY SO C
Solar/Wind Harmer
-0.001
219249CENTRALDIV C
Solar/Wind Harmer
0
218449LINSOLAR C
Solar/Wind Harmer
0
217081WEATEXAS C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
20673828FLE_V3-070
Solar/Wind Harmer
0.048
217206BARNGR HS C
Solar/Wind Harmer
0
217208PARK ELE C
Solar/Wind Harmer
0
20675428EAM_W2-061
Solar/Wind Harmer
0
207439AE1-081 C O1
Solar/Wind Harmer
0
20676328BVR_Y1-020
Solar/Wind Harmer
0
20674628WNG_W3-110
Solar/Wind Harmer
-0.001
207511W3-106 GEN
Solar/Wind Harmer
0.027
G-007ALTFEXP_G-007A->PJM
CMTX
37.533
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.412
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.04
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
14.211
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
3.043
BlueGrassPJM->LTFIMP_BlueG
CLTF
9.476
CBM NorthLTFEXP_CBM-N->PJM
CBM
37.925
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
86.76

Details for ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line l/o PECO_P2-2_NOTT230B2_SRT-A/* $ CHESCO $ PECO_P2-2_NOTT230B2 $ B


Base Case Flowgate

Area:PJM
Facility Description:
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line
Contingency Name:
PECO_P2-2_NOTT230B2_SRT-A/* $ CHESCO $ PECO_P2-2_NOTT230B2 $ B
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:105.37 %
Rating:3106.0 MVA
Rating Type:B
MVA to Mitigate:3272.9
MW Contribution:0.56
Bus #Bus NameTypeMW Contribution
200203Y1-065-STG
50/50
21.018
200204Y1-065-CTG1
50/50
13.235
200205Y1-065-CTG2
50/50
13.235
200052ROCKSP 1
50/50
157.025
200053ROCKSP 2
50/50
157.025
200054ROCKSP 3
50/50
155.43
200055ROCKSP 4
50/50
155.43
231914HR8
50/50
5.027
231911HR5
50/50
3.434
231912HR6
50/50
3.434
231913HR7
50/50
3.434
233920W3-032A-CTG1
50/50
5.166
233921W3-032A-STG1
50/50
2.982
232616GEN FOOD
50/50
0.39
232901NORTHST
50/50
21.596
232904IR4
50/50
205.457
232907VN8
50/50
55.155
232920IR10
50/50
7.8
232921TASLEY2G
50/50
0.846
232905CHERITON_25
50/50
0.321
232926CRISFLD1
50/50
0.257
232912OH NUG1
50/50
21.106
232913OH NUG2
50/50
21.106
232914OH NUG3
50/50
21.106
232915OH NUG4
50/50
21.106
232916OH NUG5
50/50
21.106
232917OH NUG6
50/50
21.106
232918OH NUG7
50/50
21.106
234034AF2-060
50/50
4.221
233900O-025 C
50/50
0.154
231940T-011
50/50
0.128
232919VN10
50/50
7.253
232910NRG_G1
50/50
1.115
232911NRG_G2
50/50
1.115
233987AB2-037 GEN
Solar/Wind Harmer
0
971149AH1-027 GEN
Solar/Wind Harmer
0.587
234033AF1-007_GEN
Solar/Wind Harmer
49.062
970545AG2-347 GEN
Solar/Wind Harmer
202.102
972133AH1-634 GEN
Solar/Wind Harmer
30.621
233923SMA
Solar/Wind Harmer
-0.002
233998TM1NIN_3.36
Solar/Wind Harmer
-0.002
233997TMININ_4.2
Solar/Wind Harmer
-0.002
233996TM1833_GEN
Solar/Wind Harmer
-0.002
972069AH1-584 GEN
Solar/Wind Harmer
1.173
972071AH1-585 GEN
Solar/Wind Harmer
1.173
972073AH1-586 GEN
Solar/Wind Harmer
21.105
971747AH1-380 GEN
Solar/Wind Harmer
0.469
233940AF2-379 C
Solar/Wind Harmer
-0.002
233972AC1-094 C
Solar/Wind Harmer
-0.002
970695AG2-447 GEN
Solar/Wind Harmer
0.469
233990AG1-397 GEN
Solar/Wind Harmer
-0.001
233990AG1-397 GEN
Solar/Wind Harmer
3.751
234015AF2-250 C
Solar/Wind Harmer
-0.001
971195AH1-057 GEN
Solar/Wind Harmer
0.169
972177AH1-672 GEN
Solar/Wind Harmer
1.757
960671AF2-358 GEN
Solar/Wind Harmer
2.342
965821AG1-450 GEN
Solar/Wind Harmer
11.709
232426Y1-080 FULL
Solar/Wind Harmer
0
970277AG2-181 GEN
Solar/Wind Harmer
0.656
233946AB2-136 GEN
Solar/Wind Harmer
-0.002
233964AF2-378 GEN
Solar/Wind Harmer
0.001
234041AC1-190 GEN
Solar/Wind Harmer
1.169
233984AB2-036 GEN
Solar/Wind Harmer
2.127
233968AD2-076_GEN
Solar/Wind Harmer
1.124
234014AF1-036_GEN
Solar/Wind Harmer
0.459
970597AG2-380 GEN
Solar/Wind Harmer
9.179
234012AE2-112_GEN
Solar/Wind Harmer
0.39
971983AH1-536 GEN
Solar/Wind Harmer
0.952
970453AG2-297 GEN
Solar/Wind Harmer
0.299
971553AH1-274 GEN
Solar/Wind Harmer
0.254
230422AE1-104_GEN1
Solar/Wind Harmer
61.937
230425AE1-104_GEN2
Solar/Wind Harmer
61.937
945431AF1-208 GEN
Solar/Wind Harmer
0.666
230433AD2-135 GEN
Solar/Wind Harmer
0
970997AG2-616 GEN
Solar/Wind Harmer
0.73
972141AH1-641 GEN
Solar/Wind Harmer
0.219
230430AE1-229_GEN
Solar/Wind Harmer
-0.001
228754AB1-001 C
Solar/Wind Harmer
-0.001
228351V2-046C
Solar/Wind Harmer
-0.001
971535AH1-265 GEN
Solar/Wind Harmer
0.422
230407AD2-065 C
Solar/Wind Harmer
0
971011AG2-627 GEN
Solar/Wind Harmer
0.564
218660EHAMPSOLAR C
Solar/Wind Harmer
-0.001
219137THOSOLAR C
Solar/Wind Harmer
0.001
219623KINSLEYBEA C
Solar/Wind Harmer
-0.001
219258KINSLEYDEP C
Solar/Wind Harmer
0
219766PARADISE C
Solar/Wind Harmer
-0.001
219907AC1-030 C
Solar/Wind Harmer
-0.001
219236SOUTHERNHQ C
Solar/Wind Harmer
-0.001
207500AE2-000G1
Solar/Wind Harmer
42.829
207497AE2-000G2
Solar/Wind Harmer
42.829
207507AE2-000G3
Solar/Wind Harmer
42.829
207487AE2-000G4
Solar/Wind Harmer
42.829
207522AF2-254 C
Solar/Wind Harmer
0.108
219906AC1-017 C
Solar/Wind Harmer
-0.001
219615MILLCREEK C
Solar/Wind Harmer
-0.001
970025AG2-016 GEN
Solar/Wind Harmer
0.212
971189AH1-054 GEN
Solar/Wind Harmer
0.087
971667AH1-334 GEN
Solar/Wind Harmer
0.2
214067T20SOLAR
Solar/Wind Harmer
-0.001
20714328BYD_X4-031
Solar/Wind Harmer
0.019
20714428HOW_X1-037
Solar/Wind Harmer
-0.001
219727YARDVSOLFA C
Solar/Wind Harmer
0.001
20720628TIN_W1-124
Solar/Wind Harmer
-0.001
20742028HF_AC1-207
Solar/Wind Harmer
-0.001
219276PARKLANDSO C
Solar/Wind Harmer
0
971521AH1-258 GEN
Solar/Wind Harmer
0.172
967451AG2-055 C O1
Solar/Wind Harmer
191.506
219620RIDERU C
Solar/Wind Harmer
-0.001
219817TRENTONSOL C
Solar/Wind Harmer
0.001
219918AC2-009 C
Solar/Wind Harmer
0
219612MATRIX C
Solar/Wind Harmer
0
218438BLK ROCK C
Solar/Wind Harmer
0
218526CNTRALGAS2 C
Solar/Wind Harmer
0.001
218524CNTRALGAS1 C
Solar/Wind Harmer
0.001
218428ETC SOLAR C
Solar/Wind Harmer
0
217213AMBOY SO C
Solar/Wind Harmer
-0.001
219249CENTRALDIV C
Solar/Wind Harmer
0
218449LINSOLAR C
Solar/Wind Harmer
0
217081WEATEXAS C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
20673828FLE_V3-070
Solar/Wind Harmer
0.049
217206BARNGR HS C
Solar/Wind Harmer
0
217208PARK ELE C
Solar/Wind Harmer
0
20675428EAM_W2-061
Solar/Wind Harmer
0
207439AE1-081 C O1
Solar/Wind Harmer
0
20676328BVR_Y1-020
Solar/Wind Harmer
0
20674628WNG_W3-110
Solar/Wind Harmer
-0.001
207511W3-106 GEN
Solar/Wind Harmer
0.028
G-007ALTFEXP_G-007A->PJM
CMTX
38.344
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.414
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.04
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
14.186
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
3.037
BlueGrassPJM->LTFIMP_BlueG
CLTF
9.457
CBM NorthLTFEXP_CBM-N->PJM
CBM
39.062
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
88.783

Details for ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line l/o PECO_P2-2_CONC230B_SRT-A/* $ DELCO $ PECO_P2-2_CONC230B $ B


Base Case Flowgate

Area:PJM
Facility Description:
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line
Contingency Name:
PECO_P2-2_CONC230B_SRT-A/* $ DELCO $ PECO_P2-2_CONC230B $ B
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:105.32 %
Rating:3106.0 MVA
Rating Type:B
MVA to Mitigate:3271.12
MW Contribution:0.58
Bus #Bus NameTypeMW Contribution
200203Y1-065-STG
50/50
21
200204Y1-065-CTG1
50/50
13.224
200205Y1-065-CTG2
50/50
13.224
200052ROCKSP 1
50/50
156.889
200053ROCKSP 2
50/50
156.889
200054ROCKSP 3
50/50
155.296
200055ROCKSP 4
50/50
155.296
231914HR8
50/50
5.056
231911HR5
50/50
3.454
231912HR6
50/50
3.454
231913HR7
50/50
3.454
233920W3-032A-CTG1
50/50
5.192
233921W3-032A-STG1
50/50
2.997
232616GEN FOOD
50/50
0.392
232901NORTHST
50/50
21.706
232904IR4
50/50
206.335
232920IR10
50/50
7.833
232921TASLEY2G
50/50
0.85
232905CHERITON_25
50/50
0.322
232912OH NUG1
50/50
21.192
232913OH NUG2
50/50
21.192
232914OH NUG3
50/50
21.192
232915OH NUG4
50/50
21.192
232916OH NUG5
50/50
21.192
232917OH NUG6
50/50
21.192
232918OH NUG7
50/50
21.192
234034AF2-060
50/50
4.238
232926CRISFLD1
50/50
0.258
232907VN8
50/50
55.37
233900O-025 C
50/50
0.154
231940T-011
50/50
0.128
232919VN10
50/50
7.279
232910NRG_G1
50/50
1.115
232911NRG_G2
50/50
1.115
233987AB2-037 GEN
Solar/Wind Harmer
0
971149AH1-027 GEN
Solar/Wind Harmer
0.59
233972AC1-094 C
Solar/Wind Harmer
-0.002
970695AG2-447 GEN
Solar/Wind Harmer
0.471
234033AF1-007_GEN
Solar/Wind Harmer
49.272
970545AG2-347 GEN
Solar/Wind Harmer
202.966
972133AH1-634 GEN
Solar/Wind Harmer
30.752
972069AH1-584 GEN
Solar/Wind Harmer
1.177
972071AH1-585 GEN
Solar/Wind Harmer
1.177
972073AH1-586 GEN
Solar/Wind Harmer
21.191
233923SMA
Solar/Wind Harmer
-0.002
233998TM1NIN_3.36
Solar/Wind Harmer
-0.002
233997TMININ_4.2
Solar/Wind Harmer
-0.002
233996TM1833_GEN
Solar/Wind Harmer
-0.002
971747AH1-380 GEN
Solar/Wind Harmer
0.471
233940AF2-379 C
Solar/Wind Harmer
-0.002
233990AG1-397 GEN
Solar/Wind Harmer
-0.001
233990AG1-397 GEN
Solar/Wind Harmer
3.766
234015AF2-250 C
Solar/Wind Harmer
-0.001
971195AH1-057 GEN
Solar/Wind Harmer
0.169
972177AH1-672 GEN
Solar/Wind Harmer
1.764
960671AF2-358 GEN
Solar/Wind Harmer
2.35
965821AG1-450 GEN
Solar/Wind Harmer
11.749
232426Y1-080 FULL
Solar/Wind Harmer
0
970277AG2-181 GEN
Solar/Wind Harmer
0.658
233946AB2-136 GEN
Solar/Wind Harmer
-0.002
233964AF2-378 GEN
Solar/Wind Harmer
0.001
234041AC1-190 GEN
Solar/Wind Harmer
1.173
233984AB2-036 GEN
Solar/Wind Harmer
2.125
233968AD2-076_GEN
Solar/Wind Harmer
1.121
234014AF1-036_GEN
Solar/Wind Harmer
0.457
970597AG2-380 GEN
Solar/Wind Harmer
9.148
234012AE2-112_GEN
Solar/Wind Harmer
0.389
971983AH1-536 GEN
Solar/Wind Harmer
0.947
970453AG2-297 GEN
Solar/Wind Harmer
0.304
971553AH1-274 GEN
Solar/Wind Harmer
0.258
230422AE1-104_GEN1
Solar/Wind Harmer
62.959
230425AE1-104_GEN2
Solar/Wind Harmer
62.959
945431AF1-208 GEN
Solar/Wind Harmer
0.68
970997AG2-616 GEN
Solar/Wind Harmer
0.747
972141AH1-641 GEN
Solar/Wind Harmer
0.224
230430AE1-229_GEN
Solar/Wind Harmer
-0.001
230433AD2-135 GEN
Solar/Wind Harmer
0
228754AB1-001 C
Solar/Wind Harmer
-0.001
228351V2-046C
Solar/Wind Harmer
-0.001
971535AH1-265 GEN
Solar/Wind Harmer
0.43
971011AG2-627 GEN
Solar/Wind Harmer
0.579
230407AD2-065 C
Solar/Wind Harmer
0
219137THOSOLAR C
Solar/Wind Harmer
0.001
218660EHAMPSOLAR C
Solar/Wind Harmer
-0.001
219623KINSLEYBEA C
Solar/Wind Harmer
-0.001
219258KINSLEYDEP C
Solar/Wind Harmer
0
219766PARADISE C
Solar/Wind Harmer
-0.001
219907AC1-030 C
Solar/Wind Harmer
-0.001
219236SOUTHERNHQ C
Solar/Wind Harmer
-0.001
207500AE2-000G1
Solar/Wind Harmer
43.391
207497AE2-000G2
Solar/Wind Harmer
43.391
207507AE2-000G3
Solar/Wind Harmer
43.391
207487AE2-000G4
Solar/Wind Harmer
43.391
219906AC1-017 C
Solar/Wind Harmer
-0.001
219615MILLCREEK C
Solar/Wind Harmer
-0.001
207522AF2-254 C
Solar/Wind Harmer
0.11
970025AG2-016 GEN
Solar/Wind Harmer
0.214
971189AH1-054 GEN
Solar/Wind Harmer
0.088
971667AH1-334 GEN
Solar/Wind Harmer
0.202
214067T20SOLAR
Solar/Wind Harmer
-0.001
20714328BYD_X4-031
Solar/Wind Harmer
0.019
219727YARDVSOLFA C
Solar/Wind Harmer
0.001
20714428HOW_X1-037
Solar/Wind Harmer
-0.001
20720628TIN_W1-124
Solar/Wind Harmer
-0.001
219276PARKLANDSO C
Solar/Wind Harmer
0
20742028HF_AC1-207
Solar/Wind Harmer
-0.001
971521AH1-258 GEN
Solar/Wind Harmer
0.173
967451AG2-055 C O1
Solar/Wind Harmer
193.096
219620RIDERU C
Solar/Wind Harmer
-0.001
219817TRENTONSOL C
Solar/Wind Harmer
0.001
219918AC2-009 C
Solar/Wind Harmer
0
219612MATRIX C
Solar/Wind Harmer
0
218438BLK ROCK C
Solar/Wind Harmer
0
218526CNTRALGAS2 C
Solar/Wind Harmer
0.001
218524CNTRALGAS1 C
Solar/Wind Harmer
0.001
218428ETC SOLAR C
Solar/Wind Harmer
0
217213AMBOY SO C
Solar/Wind Harmer
-0.001
219249CENTRALDIV C
Solar/Wind Harmer
0
218449LINSOLAR C
Solar/Wind Harmer
0.001
217081WEATEXAS C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
20673828FLE_V3-070
Solar/Wind Harmer
0.049
217206BARNGR HS C
Solar/Wind Harmer
0
217208PARK ELE C
Solar/Wind Harmer
0
20675428EAM_W2-061
Solar/Wind Harmer
0
207439AE1-081 C O1
Solar/Wind Harmer
0
20676328BVR_Y1-020
Solar/Wind Harmer
0
20674628WNG_W3-110
Solar/Wind Harmer
-0.001
207511W3-106 GEN
Solar/Wind Harmer
0.028
G-007ALTFEXP_G-007A->PJM
CMTX
38.681
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.421
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.045
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
14.224
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
3.045
BlueGrassPJM->LTFIMP_BlueG
CLTF
9.483
CBM NorthLTFEXP_CBM-N->PJM
CBM
39.266
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
89.404

Details for ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line l/o PECO_CBO_NOTT785_SRT-A/* $ CHESCO $ PECO_CBO_NOTT785 $ K


Base Case Flowgate

Area:PJM
Facility Description:
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line
Contingency Name:
PECO_CBO_NOTT785_SRT-A/* $ CHESCO $ PECO_CBO_NOTT785 $ K
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:105.2 %
Rating:3106.0 MVA
Rating Type:B
MVA to Mitigate:3267.53
MW Contribution:0.56
Bus #Bus NameTypeMW Contribution
200203Y1-065-STG
50/50
21.018
200204Y1-065-CTG1
50/50
13.235
200205Y1-065-CTG2
50/50
13.235
200052ROCKSP 1
50/50
157.022
200053ROCKSP 2
50/50
157.022
200054ROCKSP 3
50/50
155.428
200055ROCKSP 4
50/50
155.428
231914HR8
50/50
5.024
231911HR5
50/50
3.432
231912HR6
50/50
3.432
231913HR7
50/50
3.432
233920W3-032A-CTG1
50/50
5.163
233921W3-032A-STG1
50/50
2.981
232616GEN FOOD
50/50
0.39
232901NORTHST
50/50
21.584
232904IR4
50/50
205.324
232907VN8
50/50
55.117
232920IR10
50/50
7.795
232921TASLEY2G
50/50
0.846
232905CHERITON_25
50/50
0.321
232912OH NUG1
50/50
21.092
232913OH NUG2
50/50
21.092
232914OH NUG3
50/50
21.092
232915OH NUG4
50/50
21.092
232916OH NUG5
50/50
21.092
232917OH NUG6
50/50
21.092
232918OH NUG7
50/50
21.092
234034AF2-060
50/50
4.218
232926CRISFLD1
50/50
0.256
233900O-025 C
50/50
0.154
231940T-011
50/50
0.128
232919VN10
50/50
7.248
232910NRG_G1
50/50
1.114
232911NRG_G2
50/50
1.114
233987AB2-037 GEN
Solar/Wind Harmer
0
971149AH1-027 GEN
Solar/Wind Harmer
0.587
234033AF1-007_GEN
Solar/Wind Harmer
49.03
970545AG2-347 GEN
Solar/Wind Harmer
201.971
972133AH1-634 GEN
Solar/Wind Harmer
30.602
233923SMA
Solar/Wind Harmer
-0.002
233998TM1NIN_3.36
Solar/Wind Harmer
-0.002
233997TMININ_4.2
Solar/Wind Harmer
-0.002
233996TM1833_GEN
Solar/Wind Harmer
-0.002
972069AH1-584 GEN
Solar/Wind Harmer
1.172
972071AH1-585 GEN
Solar/Wind Harmer
1.172
972073AH1-586 GEN
Solar/Wind Harmer
21.091
971747AH1-380 GEN
Solar/Wind Harmer
0.469
233972AC1-094 C
Solar/Wind Harmer
-0.002
233940AF2-379 C
Solar/Wind Harmer
-0.002
970695AG2-447 GEN
Solar/Wind Harmer
0.469
233990AG1-397 GEN
Solar/Wind Harmer
-0.001
233990AG1-397 GEN
Solar/Wind Harmer
3.749
234015AF2-250 C
Solar/Wind Harmer
-0.001
971195AH1-057 GEN
Solar/Wind Harmer
0.169
972177AH1-672 GEN
Solar/Wind Harmer
1.756
960671AF2-358 GEN
Solar/Wind Harmer
2.34
965821AG1-450 GEN
Solar/Wind Harmer
11.7
232426Y1-080 FULL
Solar/Wind Harmer
0
970277AG2-181 GEN
Solar/Wind Harmer
0.655
233946AB2-136 GEN
Solar/Wind Harmer
-0.002
233964AF2-378 GEN
Solar/Wind Harmer
0.001
234041AC1-190 GEN
Solar/Wind Harmer
1.168
233984AB2-036 GEN
Solar/Wind Harmer
2.125
233968AD2-076_GEN
Solar/Wind Harmer
1.123
234014AF1-036_GEN
Solar/Wind Harmer
0.458
970597AG2-380 GEN
Solar/Wind Harmer
9.169
234012AE2-112_GEN
Solar/Wind Harmer
0.39
971983AH1-536 GEN
Solar/Wind Harmer
0.951
970453AG2-297 GEN
Solar/Wind Harmer
0.299
971553AH1-274 GEN
Solar/Wind Harmer
0.254
230422AE1-104_GEN1
Solar/Wind Harmer
61.933
230425AE1-104_GEN2
Solar/Wind Harmer
61.933
945431AF1-208 GEN
Solar/Wind Harmer
0.666
230433AD2-135 GEN
Solar/Wind Harmer
0
970997AG2-616 GEN
Solar/Wind Harmer
0.73
972141AH1-641 GEN
Solar/Wind Harmer
0.219
230430AE1-229_GEN
Solar/Wind Harmer
-0.001
228754AB1-001 C
Solar/Wind Harmer
-0.001
228351V2-046C
Solar/Wind Harmer
-0.001
971535AH1-265 GEN
Solar/Wind Harmer
0.422
230407AD2-065 C
Solar/Wind Harmer
0
971011AG2-627 GEN
Solar/Wind Harmer
0.564
218660EHAMPSOLAR C
Solar/Wind Harmer
-0.001
219137THOSOLAR C
Solar/Wind Harmer
0.001
219623KINSLEYBEA C
Solar/Wind Harmer
-0.001
219258KINSLEYDEP C
Solar/Wind Harmer
0
219766PARADISE C
Solar/Wind Harmer
-0.001
219907AC1-030 C
Solar/Wind Harmer
-0.001
219236SOUTHERNHQ C
Solar/Wind Harmer
-0.001
207500AE2-000G1
Solar/Wind Harmer
42.832
207497AE2-000G2
Solar/Wind Harmer
42.832
207507AE2-000G3
Solar/Wind Harmer
42.832
207487AE2-000G4
Solar/Wind Harmer
42.832
207522AF2-254 C
Solar/Wind Harmer
0.108
219906AC1-017 C
Solar/Wind Harmer
-0.001
219615MILLCREEK C
Solar/Wind Harmer
-0.001
970025AG2-016 GEN
Solar/Wind Harmer
0.212
971189AH1-054 GEN
Solar/Wind Harmer
0.087
971667AH1-334 GEN
Solar/Wind Harmer
0.2
214067T20SOLAR
Solar/Wind Harmer
-0.001
20714328BYD_X4-031
Solar/Wind Harmer
0.019
20714428HOW_X1-037
Solar/Wind Harmer
-0.001
219727YARDVSOLFA C
Solar/Wind Harmer
0.001
20720628TIN_W1-124
Solar/Wind Harmer
-0.001
20742028HF_AC1-207
Solar/Wind Harmer
-0.001
219276PARKLANDSO C
Solar/Wind Harmer
0
971521AH1-258 GEN
Solar/Wind Harmer
0.172
967451AG2-055 C O1
Solar/Wind Harmer
191.54
219620RIDERU C
Solar/Wind Harmer
-0.001
219817TRENTONSOL C
Solar/Wind Harmer
0.001
219918AC2-009 C
Solar/Wind Harmer
0
219612MATRIX C
Solar/Wind Harmer
0
218438BLK ROCK C
Solar/Wind Harmer
0
218526CNTRALGAS2 C
Solar/Wind Harmer
0.001
218524CNTRALGAS1 C
Solar/Wind Harmer
0.001
218428ETC SOLAR C
Solar/Wind Harmer
0
217213AMBOY SO C
Solar/Wind Harmer
-0.001
219249CENTRALDIV C
Solar/Wind Harmer
0
218449LINSOLAR C
Solar/Wind Harmer
0
217081WEATEXAS C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
20673828FLE_V3-070
Solar/Wind Harmer
0.049
217206BARNGR HS C
Solar/Wind Harmer
0
217208PARK ELE C
Solar/Wind Harmer
0
20675428EAM_W2-061
Solar/Wind Harmer
0
207439AE1-081 C O1
Solar/Wind Harmer
0
20676328BVR_Y1-020
Solar/Wind Harmer
0
20674628WNG_W3-110
Solar/Wind Harmer
-0.001
207511W3-106 GEN
Solar/Wind Harmer
0.028
G-007ALTFEXP_G-007A->PJM
CMTX
38.353
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.411
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.039
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
14.173
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
3.034
BlueGrassPJM->LTFIMP_BlueG
CLTF
9.448
CBM NorthLTFEXP_CBM-N->PJM
CBM
39.085
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
88.811

Details for ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line l/o PS_P7-1_P2242+V2274_LT_SRT-A


Base Case Flowgate

Area:PJM
Facility Description:
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line
Contingency Name:
PS_P7-1_P2242+V2274_LT_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:104.51 %
Rating:3106.0 MVA
Rating Type:B
MVA to Mitigate:3246.0
MW Contribution:0.61
Bus #Bus NameTypeMW Contribution
200203Y1-065-STG
50/50
20.999
200204Y1-065-CTG1
50/50
13.223
200205Y1-065-CTG2
50/50
13.223
200052ROCKSP 1
50/50
156.88
200053ROCKSP 2
50/50
156.88
200054ROCKSP 3
50/50
155.288
200055ROCKSP 4
50/50
155.288
231914HR8
50/50
4.989
231911HR5
50/50
3.408
231912HR6
50/50
3.408
231913HR7
50/50
3.408
233920W3-032A-CTG1
50/50
5.124
233921W3-032A-STG1
50/50
2.958
232616GEN FOOD
50/50
0.387
232901NORTHST
50/50
21.421
232904IR4
50/50
203.453
232920IR10
50/50
7.723
232921TASLEY2G
50/50
0.837
232905CHERITON_25
50/50
0.318
232912OH NUG1
50/50
20.89
232913OH NUG2
50/50
20.89
232914OH NUG3
50/50
20.89
232915OH NUG4
50/50
20.89
232916OH NUG5
50/50
20.89
232917OH NUG6
50/50
20.89
232918OH NUG7
50/50
20.89
234034AF2-060
50/50
4.178
232926CRISFLD1
50/50
0.254
232907VN8
50/50
54.564
233900O-025 C
50/50
0.152
231940T-011
50/50
0.127
232919VN10
50/50
7.174
232910NRG_G1
50/50
1.1
232911NRG_G2
50/50
1.1
971149AH1-027 GEN
Solar/Wind Harmer
0.582
233987AB2-037 GEN
Solar/Wind Harmer
0
233972AC1-094 C
Solar/Wind Harmer
-0.002
970695AG2-447 GEN
Solar/Wind Harmer
0.465
234033AF1-007_GEN
Solar/Wind Harmer
48.584
970545AG2-347 GEN
Solar/Wind Harmer
200.131
972133AH1-634 GEN
Solar/Wind Harmer
30.323
972069AH1-584 GEN
Solar/Wind Harmer
1.161
972071AH1-585 GEN
Solar/Wind Harmer
1.161
972073AH1-586 GEN
Solar/Wind Harmer
20.891
971747AH1-380 GEN
Solar/Wind Harmer
0.464
233923SMA
Solar/Wind Harmer
-0.002
233998TM1NIN_3.36
Solar/Wind Harmer
-0.002
233997TMININ_4.2
Solar/Wind Harmer
-0.002
233996TM1833_GEN
Solar/Wind Harmer
-0.002
233940AF2-379 C
Solar/Wind Harmer
-0.002
233990AG1-397 GEN
Solar/Wind Harmer
-0.001
233990AG1-397 GEN
Solar/Wind Harmer
3.713
972177AH1-672 GEN
Solar/Wind Harmer
1.74
234015AF2-250 C
Solar/Wind Harmer
-0.001
971195AH1-057 GEN
Solar/Wind Harmer
0.167
960671AF2-358 GEN
Solar/Wind Harmer
2.316
965821AG1-450 GEN
Solar/Wind Harmer
11.579
232426Y1-080 FULL
Solar/Wind Harmer
0
970277AG2-181 GEN
Solar/Wind Harmer
0.648
233946AB2-136 GEN
Solar/Wind Harmer
-0.002
233964AF2-378 GEN
Solar/Wind Harmer
0.001
234041AC1-190 GEN
Solar/Wind Harmer
1.156
233984AB2-036 GEN
Solar/Wind Harmer
2.094
233968AD2-076_GEN
Solar/Wind Harmer
1.105
234014AF1-036_GEN
Solar/Wind Harmer
0.451
970597AG2-380 GEN
Solar/Wind Harmer
9.017
234012AE2-112_GEN
Solar/Wind Harmer
0.383
971983AH1-536 GEN
Solar/Wind Harmer
0.934
970453AG2-297 GEN
Solar/Wind Harmer
0.309
971553AH1-274 GEN
Solar/Wind Harmer
0.264
945431AF1-208 GEN
Solar/Wind Harmer
0.707
970997AG2-616 GEN
Solar/Wind Harmer
0.78
972141AH1-641 GEN
Solar/Wind Harmer
0.234
228351V2-046C
Solar/Wind Harmer
-0.002
230430AE1-229_GEN
Solar/Wind Harmer
-0.001
971011AG2-627 GEN
Solar/Wind Harmer
0.615
230422AE1-104_GEN1
Solar/Wind Harmer
63.676
230425AE1-104_GEN2
Solar/Wind Harmer
63.676
971535AH1-265 GEN
Solar/Wind Harmer
0.439
228754AB1-001 C
Solar/Wind Harmer
-0.001
230433AD2-135 GEN
Solar/Wind Harmer
0
219258KINSLEYDEP C
Solar/Wind Harmer
-0.001
219137THOSOLAR C
Solar/Wind Harmer
0.001
230407AD2-065 C
Solar/Wind Harmer
0
218660EHAMPSOLAR C
Solar/Wind Harmer
-0.001
219623KINSLEYBEA C
Solar/Wind Harmer
-0.001
207500AE2-000G1
Solar/Wind Harmer
42.593
207497AE2-000G2
Solar/Wind Harmer
42.593
207507AE2-000G3
Solar/Wind Harmer
42.593
207487AE2-000G4
Solar/Wind Harmer
42.593
207522AF2-254 C
Solar/Wind Harmer
0.106
970025AG2-016 GEN
Solar/Wind Harmer
0.21
219766PARADISE C
Solar/Wind Harmer
-0.001
971189AH1-054 GEN
Solar/Wind Harmer
0.086
971667AH1-334 GEN
Solar/Wind Harmer
0.197
219907AC1-030 C
Solar/Wind Harmer
-0.001
219236SOUTHERNHQ C
Solar/Wind Harmer
-0.001
219906AC1-017 C
Solar/Wind Harmer
-0.001
219615MILLCREEK C
Solar/Wind Harmer
-0.001
20714328BYD_X4-031
Solar/Wind Harmer
0.018
214067T20SOLAR
Solar/Wind Harmer
-0.001
20714428HOW_X1-037
Solar/Wind Harmer
-0.001
20720628TIN_W1-124
Solar/Wind Harmer
-0.001
219727YARDVSOLFA C
Solar/Wind Harmer
0.001
20742028HF_AC1-207
Solar/Wind Harmer
-0.001
971521AH1-258 GEN
Solar/Wind Harmer
0.168
219276PARKLANDSO C
Solar/Wind Harmer
0
967451AG2-055 C O1
Solar/Wind Harmer
187.849
219620RIDERU C
Solar/Wind Harmer
-0.001
219817TRENTONSOL C
Solar/Wind Harmer
0.001
219918AC2-009 C
Solar/Wind Harmer
0
219612MATRIX C
Solar/Wind Harmer
0
218438BLK ROCK C
Solar/Wind Harmer
0
218526CNTRALGAS2 C
Solar/Wind Harmer
0.001
218524CNTRALGAS1 C
Solar/Wind Harmer
0.001
218428ETC SOLAR C
Solar/Wind Harmer
0
217213AMBOY SO C
Solar/Wind Harmer
-0.001
219249CENTRALDIV C
Solar/Wind Harmer
0
218449LINSOLAR C
Solar/Wind Harmer
0
217081WEATEXAS C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
20673828FLE_V3-070
Solar/Wind Harmer
0.048
217206BARNGR HS C
Solar/Wind Harmer
0
217208PARK ELE C
Solar/Wind Harmer
0
20675428EAM_W2-061
Solar/Wind Harmer
0
207439AE1-081 C O1
Solar/Wind Harmer
0
20676328BVR_Y1-020
Solar/Wind Harmer
0
20674628WNG_W3-110
Solar/Wind Harmer
-0.001
207511W3-106 GEN
Solar/Wind Harmer
0.027
G-007ALTFEXP_G-007A->PJM
CMTX
37.503
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.354
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.005
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
13.963
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
2.989
BlueGrassPJM->LTFIMP_BlueG
CLTF
9.31
CBM NorthLTFEXP_CBM-N->PJM
CBM
37.873
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
86.379
CONTINGENCY 'DVP_P1-2: LN 9354_SRT-A'
 OPEN BRANCH FROM BUS 313400 TO BUS 313403 CKT 1   /*8GOLDEN      500.0 - 8ASPEN       500.0
END
CONTINGENCY 'PJM_500_BG_P4_5_CNSTN_C_SRT-A'
 OPEN BRANCH FROM BUS 200004 TO BUS 200064 CKT 1    /*CNASTONE     500.0 - PCHBTM1S     500.0
 OPEN BRANCH FROM BUS 200004 TO BUS 200100 CKT ZC   /*CNASTONE     500.0 - CNASTCAP     500.0
END
CONTINGENCY 'PECO_P1-2_5012_SRT-A'
 TRIP BRANCH FROM BUS 200064 TO BUS 200004 CKT 1   /*PCHBTM1S     500.0 - CNASTONE     500.0
END
CONTINGENCY 'BGE_P4_GRACETON_51_SRT-A'
 OPEN BRANCH FROM BUS 200004 TO BUS 200064 CKT 1   /*CNASTONE     500.0 - PCHBTM1S     500.0
END
CONTINGENCY 'PJM_500_BG_P1_5011_SRT-A'
 OPEN BRANCH FROM BUS 200003 TO BUS 200004 CKT 1   /*BRIGHTON     500.0 - CNASTONE     500.0
END
CONTINGENCY 'AP_P1-2_PE-500-3835T_SRT-A'
 DISCONNECT BRANCH FROM BUS 270095 TO BUS 235105 CKT 1   /*CHAN         500.0 - 01DOUBS      500.0
END
CONTINGENCY 'AP_P2-3_PE-500-019E_SRT-W'
 DISCONNECT BRANCH FROM BUS 235105 TO BUS 235459 CKT 1   /*01DOUBS      500.0 - 01DOUBS      230.0
 DISCONNECT BRANCH FROM BUS 235105 TO BUS 235459 CKT 3   /*01DOUBS      500.0 - 01DOUBS      230.0
 DISCONNECT BRANCH FROM BUS 270095 TO BUS 235105 CKT 1   /*CHAN         500.0 - 01DOUBS      500.0
 REMOVE SWSHUNT FROM BUS 235105 BLOCK 1 STEP 2           /*01DOUBS      500.0
END
CONTINGENCY 'AP_P2-3_PE-500-019B_SRT-A'
 DISCONNECT BRANCH FROM BUS 235105 TO BUS 200003 CKT 1   /*01DOUBS      500.0 - BRIGHTON     500.0
 DISCONNECT BRANCH FROM BUS 270095 TO BUS 235105 CKT 1   /*CHAN         500.0 - 01DOUBS      500.0
END
CONTINGENCY 'PECO_P1-2_5007_SRT-A
 TRIP BRANCH FROM BUS 200066 TO BUS 270095 CKT 1   /*PCHBTM1N     500.0 - CHAN         500.0
END
CONTINGENCY 'BG_P7_CNSTN_NWEST2_SRT-A'
 OPEN BRANCH FROM BUS 220961 TO BUS 220963 CKT 1   /*NWEST326     230.0 - CONASTON     230.0
 OPEN BRANCH FROM BUS 220962 TO BUS 220963 CKT 1   /*NWEST311     230.0 - CONASTON     230.0
END
CONTINGENCY 'BG_P7_GRCTN_RAPHEL_SRT-A'
 OPEN BRANCH FROM BUS 220964 TO BUS 220999 CKT 13   /*GRACETON     230.0 - BAGLEY2      230.0
 OPEN BRANCH FROM BUS 220964 TO BUS 221000 CKT 5    /*GRACETON     230.0 - BAGLEY       230.0
 OPEN BRANCH FROM BUS 220980 TO BUS 220999 CKT 13   /*RAPHAEL      230.0 - BAGLEY2      230.0
 OPEN BRANCH FROM BUS 220980 TO BUS 221000 CKT 5    /*RAPHAEL      230.0 - BAGLEY       230.0
END
CONTINGENCY 'PJM_500_BG_P2_CNSTN_230-S_SRT-A'
 OPEN BRANCH FROM BUS 200004 TO BUS 220963 CKT 2   /*CNASTONE     500.0 - CONASTON     230.0
END
CONTINGENCY 'PJM_500_BG_P2_CNSTN_230-N_SRT-A'
 OPEN BRANCH FROM BUS 200004 TO BUS 220963 CKT 1   /*CNASTONE     500.0 - CONASTON     230.0
END
CONTINGENCY 'PECO_P4_PEACH235_SRT-A
 TRIP BRANCH FROM BUS 200064 TO BUS 200004 CKT 1    /*PCHBTM1S     500.0 - CNASTONE     500.0
 TRIP BRANCH FROM BUS 200064 TO BUS 200065 CKT Z1   /*PCHBTM1S     500.0 - PCHBTM2S     500.0
END
CONTINGENCY 'PECO_P1-2_5014_SRT-A
 TRIP BRANCH FROM BUS 200065 TO BUS 200051 CKT 1   /*PCHBTM2S     500.0 - ROCKSPGS     500.0
END
CONTINGENCY 'PJM500_PS_P1-2_5015_SRT-A'
 TRIP LINE FROM BUS 200027 TO BUS 200029 CKT 1   /*REDLION      500.0 - HOPE CRK     500.0
END
CONTINGENCY 'PJM500_PS_P2-3_HOPC_3-4_SRT-A'
 TRIP LINE FROM BUS 200027 TO BUS 200029 CKT 1   /*REDLION      500.0 - HOPE CRK     500.0
END
CONTINGENCY 'DPL_P4_2_REDLION-HOPE AT50_SRT-A'
 OPEN LINE FROM BUS 200027 TO BUS 200029 CIRCUIT 1   /*REDLION      500.0 - HOPE CRK     500.0
 OPEN LINE FROM BUS 200027 TO BUS 231004 CIRCUIT 1   /*REDLION      500.0 - RL_230       230.0
END
CONTINGENCY 'PECO_P4_PEACH035_SRT-A
 DISCONNECT BUS 213791                             /*MDDYRN07     230.0
 DISCONNECT BUS 213794                             /*MDYRN5-6      13.8
 DISCONNECT BUS 213795                             /*MDYRN7-8      13.8
 DISCONNECT BUS 213866                             /*PCHBTM       230.0
 DISCONNECT BUS 213867                             /*PCHBTM        35.0
 TRIP BRANCH FROM BUS 200066 TO BUS 270095 CKT 1   /*PCHBTM1N     500.0 - CHAN         500.0
END
CONTINGENCY 'PECO_P2-2_NOTT230B_SRT-A
 DISCONNECT BUS 213844   /*NOTTNGHM     230.0
END
CONTINGENCY 'PL_04_P71_001014_SRT-A'
 DISCONNECT BRANCH FROM BUS 208045 TO BUS 208078 CKT 3   /*LAUS         230.0 - SAKR         230.0
 DISCONNECT BRANCH FROM BUS 208045 TO BUS 208078 CKT 4   /*LAUS         230.0 - SAKR         230.0
END
CONTINGENCY 'PL_05_P71_000906_SRT-A'
 DISCONNECT BRANCH FROM BUS 208019 TO BUS 208020 CKT 1   /*MANO         230.0 - MANO TR3     230.0
 DISCONNECT BRANCH FROM BUS 208019 TO BUS 208021 CKT 1   /*MANO         230.0 - MANO TR4     230.0
 DISCONNECT BRANCH FROM BUS 208066 TO BUS 208914 CKT 1   /*SAHA0102     230.0 - SAHA 34       13.8
 DISCONNECT BRANCH FROM BUS 208066 TO BUS 208915 CKT 1   /*SAHA0102     230.0 - SAHA 567      13.8
 DISCONNECT BRANCH FROM BUS 208067 TO BUS 208916 CKT 1   /*SAHA0304     230.0 - SAHA8910      13.8
 DISCONNECT BRANCH FROM BUS 208067 TO BUS 208917 CKT 1   /*SAHA0304     230.0 - SAHA1112      13.8
 DISCONNECT BRANCH FROM BUS 208070 TO BUS 208019 CKT 1   /*SAHA12TP     230.0 - MANO         230.0
 DISCONNECT BRANCH FROM BUS 208070 TO BUS 208048 CKT 1   /*SAHA12TP     230.0 - OTCR         230.0
 DISCONNECT BRANCH FROM BUS 208070 TO BUS 208066 CKT 1   /*SAHA12TP     230.0 - SAHA0102     230.0
 DISCONNECT BRANCH FROM BUS 208071 TO BUS 208019 CKT 1   /*SAHA34TP     230.0 - MANO         230.0
 DISCONNECT BRANCH FROM BUS 208071 TO BUS 208067 CKT 1   /*SAHA34TP     230.0 - SAHA0304     230.0
 DISCONNECT BRANCH FROM BUS 208071 TO BUS 220964 CKT 1   /*SAHA34TP     230.0 - GRACETON     230.0
END
CONTINGENCY 'PL_04_P22_102817_SRT-A'
 DISCONNECT BUS 208030   /*MLWD TR1     230.0
END
CONTINGENCY 'PECO_P4_PEACH255_SRT-A
 DISCONNECT BUS 200122                              /*DELTA        500.0
 DISCONNECT BUS 200192                              /*DELTA CT1     13.8
 DISCONNECT BUS 200193                              /*DELTA CT2     13.8
 DISCONNECT BUS 200194                              /*DELTA CT3     13.8
 DISCONNECT BUS 200195                              /*DELTA ST      18.0
 DISCONNECT BUS 200199                              /*DELTA2 POI   500.0
 DISCONNECT BUS 200200                              /*DELTA2 CT1    18.0
 DISCONNECT BUS 200201                              /*DELTA2 CT2    18.0
 DISCONNECT BUS 200202                              /*DELTA2 ST     19.5
 TRIP BRANCH FROM BUS 200064 TO BUS 200065 CKT Z2   /*PCHBTM1S     500.0 - PCHBTM2S     500.0
 TRIP BRANCH FROM BUS 214347 TO BUS 200064 CKT 2    /*PBN_EXP_BAY  500.0 - PCHBTM1S     500.0
END
CONTINGENCY 'PECO_P4_PEACH225_SRT-A
 REMOVE MACHINE 1 FROM BUS 200034                   /*PCHBTM 2      22.0
 TRIP BRANCH FROM BUS 200064 TO BUS 200065 CKT Z2   /*PCHBTM1S     500.0 - PCHBTM2S     500.0
END
CONTINGENCY 'PECO_P4_CHICH045_SRT-A
 DISCONNECT BUS 213489   /*CHICHST1     230.0
 DISCONNECT BUS 213627   /*FOULK8       230.0
END
CONTINGENCY 'PECO_P4_CHICH195_SRT-A
 DISCONNECT BUS 213489   /*CHICHST1     230.0
 DISCONNECT BUS 214203   /*CHICHST1     138.0
 DISCONNECT BUS 214340   /*CHI9AB HS LD 230.0
END
CONTINGENCY 'PECO_P2-2_CHI230B1_SRT-A
 DISCONNECT BUS 213489   /*CHICHST1     230.0
END
CONTINGENCY 'PECO_P4_CHICH435_SRT-A
 DISCONNECT BUS 213489   /*CHICHST1     230.0
 DISCONNECT BUS 213750   /*LINWOOD43    230.0
 DISCONNECT BUS 214221   /*CHIREACT_43  230.0
END
CONTINGENCY 'DPL_P1_2_CKT 5036_SRT-A'
 OPEN LINE FROM BUS 200010 TO BUS 200027 CIRCUIT 1   /*KEENEY       500.0 - REDLION      500.0
END
CONTINGENCY 'DPL_P4_2_REDLION-KEENEY AT50_SRT-A'
 OPEN LINE FROM BUS 200010 TO BUS 200027 CIRCUIT 1   /*KEENEY       500.0 - REDLION      500.0
 OPEN LINE FROM BUS 200027 TO BUS 231004 CIRCUIT 1   /*REDLION      500.0 - RL_230       230.0
END
CONTINGENCY 'DPL_P4_2_REDLION-KEENEY AT51_SRT-A'
 OPEN LINE FROM BUS 200010 TO BUS 200027 CIRCUIT 1   /*KEENEY       500.0 - REDLION      500.0
 OPEN LINE FROM BUS 200027 TO BUS 231004 CIRCUIT 2   /*REDLION      500.0 - RL_230       230.0
END
CONTINGENCY 'PECO_P4_PEACH065_SRT-A
 REMOVE MACHINE 1 FROM BUS 200035                  /*PCHBTM 3      22.0
 TRIP BRANCH FROM BUS 200013 TO BUS 200024 CKT 1   /*PCHBTM2N     500.0 - LIMERICK     500.0
END
CONTINGENCY 'DPL_P7_1_DBL_5NC_SRT-A'
 OPEN LINE FROM BUS 231001 TO BUS 214236 CKT 1   /*EDGEMR 5     230.0 - LINWOOD85    230.0
 OPEN LINE FROM BUS 231001 TO BUS 231000 CKT 1   /*EDGEMR 5     230.0 - CLAY_230     230.0
END
CONTINGENCY 'PECO_P4_NOTTI785_SRT-A'
 DISCONNECT BUS 213844   /*NOTTNGHM     230.0
 DISCONNECT BUS 214218   /*NOTTNGH2     230.0
END
CONTINGENCY 'PECO_P1-2_PBS-NDELTA_SRT-A
 TRIP BRANCH FROM BUS 200064 TO BUS 200122 CKT 1   /*PCHBTM1S     500.0 - DELTA        500.0
END
CONTINGENCY 'PECO_P1-2_5034_SRT-A
 DISCONNECT BUS 200122   /*DELTA        500.0
 DISCONNECT BUS 200192   /*DELTA CT1     13.8
 DISCONNECT BUS 200193   /*DELTA CT2     13.8
 DISCONNECT BUS 200194   /*DELTA CT3     13.8
 DISCONNECT BUS 200195   /*DELTA ST      18.0
 DISCONNECT BUS 200199   /*DELTA2 POI   500.0
 DISCONNECT BUS 200200   /*DELTA2 CT1    18.0
 DISCONNECT BUS 200201   /*DELTA2 CT2    18.0
 DISCONNECT BUS 200202   /*DELTA2 ST     19.5
END
CONTINGENCY 'PECO_P2-2_NOTT230B2_SRT-A
 DISCONNECT BUS 214218   /*NOTTNGH2     230.0
END
CONTINGENCY 'PECO_P2-2_CONC230B_SRT-A
 DISCONNECT BUS 213509   /*CONCORD      230.0
END
CONTINGENCY 'PECO_CBO_NOTT785_SRT-A
 TRIP BRANCH FROM BUS 213844 TO BUS 214218 CKT Z   /*NOTTNGHM     230.0 - NOTTNGH2     230.0
END
CONTINGENCY 'PS_P7-1_P2242+V2274_LT_SRT-A'
 CLOSE LINE FROM BUS 219180 TO BUS 219181 CKT Z          /*DEPTFORD_L1   13.2 - DEPTFORD_L2   13.2
 CLOSE LINE FROM BUS 219255 TO BUS 219256 CKT Z          /*DEPTFORD_L3   13.2 - DEPTFORD_L4   13.2
 DISCONNECT BRANCH FROM BUS 219110 TO BUS 219128 CKT 1   /*GLOUCSTR     230.0 - GLOUCSTR_26   26.4
 DISCONNECT BUS 219757                                   /*DEPTFORD_2   230.0
 DISCONNECT BUS 219760                                   /*EAGLEPT_4    230.0
 MOVE 8 MW LOAD FROM BUS 219255 TO BUS 219163            /*DEPTFORD_L3   13.2 - BEAVERBK_L2   13.2
 MOVE 8 MW LOAD FROM BUS 219256 TO BUS 219162            /*DEPTFORD_L4   13.2 - BEAVERBK_L1   13.2
END
972284 to 314933 ckt 1
270095 to 235105 ckt 1
200004 to 200003 ckt 1
214084 to 220964 ckt 1
232012 to 232013 ckt 1
213844 to 213846 ckt 1
213846 to 213869 ckt 1
200066 to 270095 ckt 1
200064 to 200004 ckt 1
200064 to 214347 ckt 2
200065 to 200064 ckt Z1
200065 to 200064 ckt Z2
213869 to 214087 ckt 1
214277 to 214012 ckt 1
231004 to 231003 ckt 1
200051 to 200065 ckt 1

Light Load Analysis

The New Service Request AG2-627 was evaluated as a 40.0 MW injection

AG2-627 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 40.0 MW (40.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

(No impacts were found for this analysis)

Short Circuit Analysis

Short Circuit analysis is not performed as part of the Phase I System Impact Study. Short Circuit analysis will commence in the Phase II System Impact Study.

Stability Analysis

Stability analysis is not performed as part of the Phase I System Impact Study. Stability analysis will commence in the Phase II System Impact Study.

Reactive Power Analysis

Reactive Power analysis is not performed as part of the Phase I System Impact Study. Reactive Power analysis will commence in the Phase II System Impact Study.

Steady-State Voltage Analysis

Steady State Voltage Analysis is Not Required.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-018Powerton-Goodings GroveIn Service
AA1-038Lexington-Low Moor 230kVUnder Construction
AA1-050Tarboro-Everetts 230kVIn Service
AA1-063ACarolina–Seaboard 115kVIn Service
AA1-067Everetts 34.5kVIn Service
AA1-076Hunterstown-Conemaugh 500kVIn Service
AA1-095Halfway-Marlowe 34.5kVIn Service
AA1-139Hickory-Shawboro 230kVIn Service
AA2-053Carolina-Jackson 115kVIn Service
AA2-057Hornertown-Whitakers 115kVIn Service
AA2-133Wyalusing 34.5kVIn Service
AA2-174Carolina-Jackson 115kVIn Service
AA2-178Mackeys 230kVIn Service
AA2-184Atlantic-Red Bank 34kVIn Service
AB1-001Absecon 12 kVIn Service
AB1-006Meadow Lake 345kVIn Service
AB1-027Old Church 34.5 KVIn Service
AB1-081Anaconda-Mayo Dunbar 115kVIn Service
AB1-096Carroll-Mt. Airy 34.5kVIn Service
AB1-124Carroll-Monocacy 34.5kVPartially in Service - Under Construction
AB1-125Carroll-Monocacy 34.5kVIn Service
AB1-127St. Thomas-Guilford 34.5kVIn Service
AB1-128St. Thomas-Mercersburg 34.5kVIn Service
AB1-132Thelma 230kVIn Service
AB1-138Navy 34.5kVIn Service
AB1-139Metuchen 26kVIn Service
AB1-141Church-Wye Mills 138 kV IIn Service
AB1-142Church-Wye Mills 138 kV IIIn Service
AB1-150Grassy Falls 138kVIn Service
AB1-176Price 25kV IIEngineering & Procurement
AB2-022Elizabeth City 34.5kVIn Service
AB2-024Correctional 34.5kVIn Service
AB2-025Sapony 34.5kVIn Service
AB2-026Powhatan 34.5kVIn Service
AB2-029Remington 34.5kVIn Service
AB2-031Brink-Trego 115kVIn Service
AB2-032Church-Wye Mills 138 kVIn Service
AB2-036Church - Oil City 138kVSuspended
AB2-037Keeney-Steele 230kVUnder Construction
AB2-040Brink 115kVIn Service
AB2-043Chase City 115kVIn Service
AB2-045Buckingham 34.5kVIn Service
AB2-049Gloucester Township 12kVIn Service
AB2-057Brunswick 26kVIn Service
AB2-059Benson-Dunbar 115kVIn Service
AB2-060Chase City-Lunenburg 115kVIn Service
AB2-070Mt. Pulaski-BrokawIn Service
AB2-077Buggs Island-Chase City 115kVIn Service
AB2-078Buggs Island-Chase City 115kVIn Service
AB2-079Buggs Island-Chase City 115kVIn Service
AB2-099Ahoskie 34.5kVIn Service
AB2-133Chestertown 69kVUnder Construction
AB2-134Hopewell-Surry 230kVIn Service
AB2-135Church-Kent 69kVIn Service
AB2-136Cambridge-West Cambridge 69kVUnder Construction
AB2-153Church-Wye Mills 138 kVIn Service
AB2-157Prince George's County 12kVIn Service
AB2-158Louisa-South Anna 230kVIn Service
AB2-161Waverly #2 DP 115kVIn Service
AB2-169Pantago-Five Points 115kVIn Service
AB2-172Todd 69kVIn Service
AB2-174Emporia-Trego 115kVIn Service
AB2-179Townsend 138kVIn Service
AB2-190Hopewell-Surry 230kVIn Service
AC1-010Gloucester 26kVUnder Construction
AC1-017Levittown 13 kVIn Service
AC1-027Pendleton 34.5kVIn Service
AC1-030Cinnaminson 13kVIn Service
AC1-033Kewanee 138 kVIn Service
AC1-036Twittys Creek 34.5kVIn Service
AC1-042Altavista-Mt. Airy 69kVIn Service
AC1-053Lanesville-BrokawPartially in Service - Under Construction
AC1-054Kerr Dam–Eatons Ferry 115 kVIn Service
AC1-074Jacksonville-Renaker 138kV IIn Service
AC1-075Perth-Hickory Grove 115kVIn Service
AC1-076Locust Grove-Paytes 115kVIn Service
AC1-078Beatty-London 138kVIn Service
AC1-082Ravenswood-Hemlock 69kVUnder Construction
AC1-085Stuart-Clinton 345kVIn Service
AC1-089Hillsboro-Wildcat 138kVIn Service
AC1-091Cedar Creek 138kV IEngineering & Procurement
AC1-092Cedar Creek 138kV IIEngineering & Procurement
AC1-093Cedar Creek 138kV IIIEngineering & Procurement
AC1-094Cedar Creek 138kV IVEngineering & Procurement
AC1-098Dawson-South Justice 115kVPartially in Service - Under Construction
AC1-099Dawson-South Justice 115kVPartially in Service - Under Construction
AC1-105Halifax-Mt. Laurel 115kVIn Service
AC1-118Westmoreland 34.5kVIn Service
AC1-120Mitchell-Mountain Run 115kVEngineering & Procurement
AC1-121Mitchell-Mountain Run 115kVEngineering & Procurement
AC1-122Smith Mountain-Candler's Mountain 138kVIn Service
AC1-145Gretna DP 69 kVIn Service
AC1-147Grassfield 34.5kVIn Service
AC1-158Spotsylvania 500kVIn Service
AC1-161Septa 500kVIn Service
AC1-167Mark Center 69kVUnder Construction
AC1-174Losantville 345kVIn Service
AC1-175Losantville 345kVIn Service
AC1-188Rio-Lick 138kVEngineering & Procurement
AC1-189Chinquapin-Everetts 230kVUnder Construction
AC1-190East New Market 69kVSuspended
AC1-191Elmont 115kVEngineering & Procurement
AC1-208Cox-Whitakers 115kVUnder Construction
AC1-214Crescent RidgeIn Service
AC1-221Halifax-Person 230kVIn Service
AC1-222Crystal Hill-Halifax 115kVIn Service
AC2-009Pennington 13 kVIn Service
AC2-012Grassfield-Great Bridge 115kVIn Service
AC2-023Hebron 69kVEngineering & Procurement
AC2-060Buckskin 69kVIn Service
AC2-061Hillsboro-Clinton 138kVIn Service
AC2-075Jacksonville-Renaker 138 kVIn Service
AC2-088S. Bethel-Brown 69kVIn Service
AC2-090Losantville 345kVIn Service
AC2-100Halifax-Person 230kVIn Service
AC2-103Beaver-Davis Besse 345 kV IEngineering & Procurement
AC2-120Ripley 69kVIn Service
AC2-123Jacksons Ferry 138kVIn Service
AC2-136East Hagerstown 12kVUnder Construction
AC2-137Elko 34.5kVIn Service
AC2-138Northern Neck 34.5kVIn Service
AC2-141Septa 500kVEngineering & Procurement
AC2-154Davis Creek 138kVEngineering & Procurement
AC2-157Sullivan 345 kVUnder Construction
AC2-165Bremo-Powhatan 230kVSuspended
AC2-168Clinton 23kVIn Service
AC2-176Jay 138 kVIn Service
AC2-185Cedar Creek 138kV IIEngineering & Procurement
AC2-186Harrington 25kVUnder Construction
AC2-187Harrington 69kVUnder Construction
AC2-188Harrington 69 kVUnder Construction
AC2-195Galion-Roberts South 138 kVUnder Construction
AD1-013Twombly Road 138kVEngineering & Procurement
AD1-017Smith Mountain-Bearskin 138 kVIn Service
AD1-020Hunterstown-Lincoln 115 kVIn Service
AD1-022Cashie-Trowbridge 230 kVEngineering & Procurement
AD1-025Hopewell-Surry 230 kVUnder Construction
AD1-033Fentress-Landstown 230 kVIn Service
AD1-041Harmony Village-Shackleford 115 kVIn Service
AD1-056Hornertown-Hathaway 230 kVSuspended
AD1-057Hornertown-Hathaway 230 kVSuspended
AD1-060Mercersburg-Milnor 34.5 kVIn Service
AD1-061McConnelsburg-Mercersburg 34 kVIn Service
AD1-063Harmony Village 34.5 kVIn Service
AD1-074Trowbridge 230 kVEngineering & Procurement
AD1-075Trowbridge 230 kVEngineering & Procurement
AD1-076Trowbridge 230 kVEngineering & Procurement
AD1-082Bakers Pond-Ivor 115kVIn Service
AD1-087Clover-Sedge Hill 230 kVIn Service
AD1-100Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVUnder Construction
AD1-105Kings Dominion DP 115 kVUnder Construction
AD1-115Mountain Run-Mitchell 115 kVEngineering & Procurement
AD1-128Modoc-Delaware 138 kVPartially in Service - Under Construction
AD1-130Hardin Switch 345 kVIn Service
AD1-136South Bethel-Brown 69 kVIn Service
AD1-144Kings Fork 34.5 kVIn Service
AD1-152Clover-Sedge Hill 230 kVIn Service
AD1-155Meadow Brook-Strasburg 138 kVIn Service
AD2-009McConnellsburg 138 kVIn Service
AD2-022East Danville - Roxborough 230 kVEngineering & Procurement
AD2-023East Danville - Roxborough 230 kVEngineering & Procurement
AD2-027Camden Switch 26 kVIn Service
AD2-030Wan 34.5 kVIn Service
AD2-031Martinsville-Wilmington 69 kVIn Service
AD2-033Chase City-Lunenburg 115 kVUnder Construction
AD2-038Powerton-Nevada 345 kVUnder Construction
AD2-042Camden Switch 26 kV IIIn Service
AD2-048Cynthia-Headquarters 69 kVUnder Construction
AD2-058St. Barnabas 13 kVIn Service
AD2-060Davis Creek 138kVEngineering & Procurement
AD2-062Roxbury-Greene 138 kVSuspended
AD2-065Atco 12 kVIn Service
AD2-066Mazon-Crescent Ridge 138 kVEngineering & Procurement
AD2-070Gilbert-Morris Park 34.5kVIn Service
AD2-073Sanders DP 230 kVIn Service
AD2-074Garner DP-Lancaster 115 kVEngineering & Procurement
AD2-076Carville 138 kVSuspended
AD2-085Myrtle-Windsor DP 115kVEngineering & Procurement
AD2-086Hardin Switch 345 kVIn Service
AD2-092Marysville 345kVUnder Construction
AD2-093Marysville 345kVUnder Construction
AD2-113South Bend 500kVIn Service
AD2-115Lyons-Moselem 69kVIn Service
AD2-116Hokes-Grantley 69 kVIn Service
AD2-133Eagle Valley 115kVIn Service
AD2-134Shady OaksPartially in Service - Under Construction
AD2-135Williamstown 12kVPartially in Service - Under Construction
AD2-160Hickory-Moyock 230kVIn Service
AD2-163Broadview-Tangy 138 kVIn Service
AD2-172Lena 138kVIn Service
AD2-180Elk Garden-Parr Run 138kVIn Service
AD2-202Clover-Sedge Hill 230kVIn Service
AE1-040Greenfield 69 kVIn Service
AE1-041Edison 4kVIn Service
AE1-071Shade Gap-Roxbury 115 kVIn Service
AE1-072Shawboro-Sligo 230 kVUnder Construction
AE1-074Winterpock 34.5 kVUnder Construction
AE1-075Powhatan 34.5 kVIn Service
AE1-079Maysville-Sharon 69 kVUnder Construction
AE1-081Landing 12.47 kVIn Service
AE1-090Hardin Switch 345 kVIn Service
AE1-100Axton 138 kVIn Service
AE1-101McConnellsburg-Texas Eastern 138 kVIn Service
AE1-103Holland-Union Camp 115 kVUnder Construction
AE1-104BL England 138 kVSuspended
AE1-108Bremo-Scottsville 138 kVEngineering & Procurement
AE1-109Frenchs Mill 34 kVIn Service
AE1-113Mole Creek 345 kVEngineering & Procurement
AE1-129Zion View - Middletown 115 kVSuspended
AE1-142Manitou-Pleasant Plains 34.5 kVIn Service
AE1-143Marion County 161 kVEngineering & Procurement
AE1-146Ebersole #2-Fostoria Central 138 kVUnder Construction
AE1-155Garner-Northern Neck 115 kVIn Service
AE1-156Quakertown Solar II 34.5 kVPartially in Service - Under Construction
AE1-162Smithfield 34.5 kVIn Service
AE1-163Powerton-Nevada 345 kVEngineering & Procurement
AE1-166Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE1-175Light Foot 34.5 kVIn Service
AE1-183Maysville-McDowell 69 kVEngineering & Procurement
AE1-185Hokes-Jackson 69 kVIn Service
AE1-190Harmony Village-Shackleford 115 kVPartially in Service - Under Construction
AE1-191Harmony Village-Shackleford 115 kVPartially in Service - Under Construction
AE1-196Hokes-Jackson 69 kV IIIn Service
AE1-226Face Rock-Kinzer #13 69 kVWithdrawn
AE1-229Deepwater-Upper Pittsgrove 138 kVSuspended
AE1-237Andover (Maysville) 69kV IUnder Construction
AE1-245Haviland 138 kVUnder Construction
AE1-250Smith Mountain-E. Danville 138 kVEngineering & Procurement
AE2-001Nittany-Zion 46 kVSuspended
AE2-005Harmony Village-Shackleford 115 kVUnder Construction
AE2-029Grottoes-Merck 115kVUnder Construction
AE2-034Mackeys 230 kVPartially in Service - Under Construction
AE2-035Lena 138 kVIn Service
AE2-042Milton 69 kVIn Service
AE2-045Olive-Reynolds 345 kVEngineering & Procurement
AE2-047Ridgeway-Solite 69 kVEngineering & Procurement
AE2-054Warfordsburg 34 kVIn Service
AE2-059Derry Tap-Derry Bus 69 kVIn Service
AE2-060Mifflintown Bus-Mifflintown Tap 69 kVIn Service
AE2-071Patton Rd-Summer Shade 69 kVIn Service
AE2-072East Leipsic-Richland 138 kVIn Service
AE2-074Potter 46 kVUnder Construction
AE2-084Derry Tap-Derry Bus 69 kVEngineering & Procurement
AE2-092Kidds Store-Sherwood 115 kVEngineering & Procurement
AE2-110Columbia-West Bloomsburg 69 kVSuspended
AE2-112Carville 138 kV IISuspended
AE2-113Farmers Valley-Ridgeway 115 kVUnder Construction
AE2-114Midland 23 kV IIn Service
AE2-115Midland 23 kV IIIn Service
AE2-117ABW Tap-Alexandria 46 kVSuspended
AE2-118ABW Tap-Williamsburg 46 kVSuspended
AE2-125Stahlstown-Ligonier 25 kVIn Service
AE2-126Dubois-Curwensville 34.5 kVIn Service
AE2-129Philipsburg-Clarence 34.5 kVIn Service
AE2-131Philipsburg-Karthaus 34.5Under Construction
AE2-133Penns Tap-Richfield Tie 69 kVIn Service
AE2-139East Towanda-Grover 230 kVEngineering & Procurement
AE2-148Beatty-Greene 345 kVIn Service
AE2-152Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE2-166Stockton 138 kVSuspended
AE2-175Jackson-Long Pond 69 kVPartially in Service - Under Construction
AE2-176Groton 138 kV SolarIn Service
AE2-181Snyder 69kVUnder Construction
AE2-206East Sidney-Quincy 138 kVIn Service
AE2-211Jackson-Three Mile Island 230 kVSuspended
AE2-212Harrowgate 34 kVEngineering & Procurement
AE2-214Cole 345 kVEngineering & Procurement
AE2-219Bluff Point-Randolph 138 kVSuspended
AE2-220Losantville 345 kVEngineering & Procurement
AE2-221Clinton-Stuart 345 kVUnder Construction
AE2-224Bear Rock-Johnstown 230 kVIn Service
AE2-226Millville-Old Chapel 138 kVEngineering & Procurement
AE2-230Bartonsville-Meadow Brook 138 kVIn Service
AE2-241Bloomsburg-Columbia 69 kVSuspended
AE2-248Fillmore-Thompson Farm 46 kVSuspended
AE2-253Hickory-Moyock 230 kVIn Service
AE2-254Garrard County-Tommy-Gooch 69 kVIn Service
AE2-255Molecreek 345 kVEngineering & Procurement
AE2-259Curdsville-Willis Mtn 115 kVEngineering & Procurement
AE2-262Moshannon-Milesburg 230 kVEngineering & Procurement
AE2-263Moshannon-Milesburg 230 kV IIEngineering & Procurement
AE2-267Woodsdale 345 kVEngineering & Procurement
AE2-271Montour 230 kVWithdrawn
AE2-281Powerton-Nevada 345 kVEngineering & Procurement
AE2-282East Fayette 138 kVIn Service
AE2-285Maysville 69 kVEngineering & Procurement
AE2-297Madison-Tanners Creek 138 kVIn Service
AE2-298Cavett Switch - West Van Wert 69 kVEngineering & Procurement
AE2-306Gunn Road 345 kVUnder Construction
AE2-309Carlos Junction-Lonaconing 34.5 kVIn Service
AE2-322Mark Center 69 kVUnder Construction
AE2-333Bedington 138 kVSuspended
AE2-339Avon 138 kVEngineering & Procurement
AE2-342Woodstock 69 kVEngineering & Procurement
AE2-343Andover (Maysville) 69 kV IIUnder Construction
AE2-345Hunterstown-Texas Eastern Tap 115 kVSuspended
AE2-346Ahoskie 34.5 kVIn Service
AF1-007Indian River 230 kV ISuspended
AF1-014Harmony Village-Shackleford 115 kVUnder Construction
AF1-017Myrtle-Windsor 115 kVEngineering & Procurement
AF1-021Bethelboro-Connellsville #1 25 kVIn Service
AF1-022Lake Lynn-Uniontown 25 kVIn Service
AF1-032Suffolk 34.5 kVIn Service
AF1-036Carville 138 kV IIISuspended
AF1-038Sewellton Jct-Webbs Crossroads 69 kVEngineering & Procurement
AF1-042Garner DP-Lancaster 115 kVEngineering & Procurement
AF1-049Berry Hill 138 kVUnder Construction
AF1-050Summer Shade - Green County 161 kVEngineering & Procurement
AF1-058Welco 34.5 kVIn Service
AF1-064Weston 69 kVUnder Construction
AF1-071College Corner 138 kVEngineering & Procurement
AF1-078East Sidney-Quincy 138 kVIn Service
AF1-083Green County-Saloma 161 kVEngineering & Procurement
AF1-086Madera-Westover South 115 kVUnder Construction
AF1-088Sullivan 345 kVActive
AF1-091Varner - Sowers 138 kVEngineering & Procurement
AF1-093Henderson-Stoneboro 69 kVEngineering & Procurement
AF1-106East Sayre 34.5 kVWithdrawn
AF1-114Oak Grove-Dahlgren 230 kVEngineering & Procurement
AF1-119Keystone-Desoto 345 kVEngineering & Procurement
AF1-120East Fayette 2 138 kVIn Service
AF1-130Inez 138 kVSuspended
AF1-134Philipsburg-Madera 34.5 kVEngineering & Procurement
AF1-136Warfordsburg-Purcell Junction 34.5 kVEngineering & Procurement
AF1-140Claysburg 23 kVEngineering & Procurement
AF1-143Lick Run 115 kVEngineering & Procurement
AF1-147Poland Rd-Runway DP 230kVUnder Construction
AF1-153Motion-Ridgeway 46 kVSuspended
AF1-202Keystone-Desoto 345 kVUnder Construction
AF1-203Patton Rd-Summer Shade 69 kVIn Service
AF1-206East Fayette 138 kVEngineering & Procurement
AF1-207Reynolds-Olive #1 345 kVEngineering & Procurement
AF1-208Laurel-Roadstown 69 kVWithdrawn
AF1-215Olive-Reynolds 345 kVIn Service
AF1-223Keystone-Desoto 345 kVUnder Construction
AF1-226Bowmans Mill-Scott 69 kVSuspended
AF1-227Marysville – Gunn Road 345 kVIn Service
AF1-228Beatty-Greene 345 kVEngineering & Procurement
AF1-229Galion-South Berwick 345 kVEngineering & Procurement
AF1-238Sherman Ave - West Vineland 69 kVActive
AF1-239Sherman Ave - West Vineland 69 kVEngineering & Procurement
AF1-249Nickel 12.47 kVIn Service
AF1-254Milnor-Huyetts 34.5 kVUnder Construction
AF1-262Upper Pittsgrove 12 kVIn Service
AF1-264Runnemede 13 kVIn Service
AF1-271AGratz 69 kVSuspended
AF1-272Lucerne 115 kVEngineering & Procurement
AF1-275Cole 345 kVEngineering & Procurement
AF1-285Gunn Road 345 kVUnder Construction
AF1-290Feagans Mill-Millville 138 kVIn Service
AF1-291Tyler 34.5 kVEngineering & Procurement
AF1-291ABartonsville-Meadow Brook 138 kVIn Service
AF1-292Fields 34.5kVEngineering & Procurement
AF1-299Otter Point 34.5 kV IIn Service
AF1-300Otter Point 34.5 kV IIIn Service
AF1-320Merrill Creek 115 kVEngineering & Procurement
AF1-321Hooversville 115 kV ISuspended
AF1-322Meadow Lake 345 kVEngineering & Procurement
AF1-331Twombley RoadEngineering & Procurement
AF1-333Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF1-337Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF1-338Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF1-339Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF2-001Hooversville 115 kV IISuspended
AF2-002Hooversville 115 kV IIISuspended
AF2-014Maddox Creek 345 kVEngineering & Procurement
AF2-018Inez 138 kVEngineering & Procurement
AF2-019Middle 69 kVEngineering & Procurement
AF2-025Ontario 69 kVEngineering & Procurement
AF2-032Kincaid 345 kVEngineering & Procurement
AF2-039Shawville-Clearfield 34.5 kVEngineering & Procurement
AF2-043Suffolk 34.5 kVIn Service
AF2-048Rio-Lick 138 kVEngineering & Procurement
AF2-050Bear Rock-Johnstown 230 kVActive
AF2-054Wan 34.5 kVIn Service
AF2-060Wattsville 12 kVEngineering & Procurement
AF2-075Bartonsville-Meadow Brook 138 kV IIIIn Service
AF2-077White Marsh 34.5 kVIn Service
AF2-078Reynolds-Olive #1 345 kVEngineering & Procurement
AF2-086Scott Tap-Bowmans Mill Tap 69 kVEngineering & Procurement
AF2-088Shawville-Clearfield 34.5 kV IIEngineering & Procurement
AF2-091Oak Grove-Dahlgren 230 kVEngineering & Procurement
AF2-092Snake Spring-Bedford Area 23 kVSuspended
AF2-106Hazel Hollow-Glen Lyn #1 138 kVEngineering & Procurement
AF2-122Kirk 138 kVUnder Construction
AF2-132Reynolds-Olive #1 345 kVUnder Construction
AF2-133Reynolds-Olive #2 345 kVUnder Construction
AF2-134Olive-Reynolds #2 345 kVIn Service
AF2-138Flanders-West Wharton 34.5 kVIn Service
AF2-139Gilbert-Warren Glen 34.5 kVIn Service
AF2-144Powhatan 34.5 kVIn Service
AF2-162Keystone-Desoto 345 kVEngineering & Procurement
AF2-187Brookside-Cloverdale 138 kVEngineering & Procurement
AF2-192Frenchtown Solar-West Flemington 34.5 kVSuspended
AF2-205Olive-Reynolds #2 345 kVEngineering & Procurement
AF2-221Scalp Level 22.9 kVSuspended
AF2-229Roxbury 23 kVEngineering & Procurement
AF2-233Penns-Richfield Tie #1 69 kVEngineering & Procurement
AF2-234Sunbury Yard #1-Richfield Tie #2 69 kVEngineering & Procurement
AF2-238Mansfield-South Troy 34.5 kVEngineering & Procurement
AF2-247Bustleton 13.2 kVIn Service
AF2-250Edgewood 12 kV IIIIn Service
AF2-254Cookstown-New Lisbon 34.5 kVSuspended
AF2-291Sporn South-Leon 138 kVEngineering & Procurement
AF2-294Thompson 34.5 kVSuspended
AF2-296Madera 34.5 kVActive
AF2-325Jacktown 12 kVEngineering & Procurement
AF2-354Washington 34.5 kV IIEngineering & Procurement
AF2-356Albright-Mt. Zion 138 kVUnder Construction
AF2-358Airey-Vienna 69 kVActive
AF2-361Mifflintown Tap 69 kVEngineering & Procurement
AF2-366Crego Rd 138 kVEngineering & Procurement
AF2-371Harrison-Good Hope 138 kVEngineering & Procurement
AF2-375Ebersole-Fostoria 138 kVEngineering & Procurement
AF2-378Cambridge 12 kVEngineering & Procurement
AF2-379Princess Anne 25 kVUnder Construction
AF2-382Hurley 69 kVEngineering & Procurement
AF2-383Tolna 115 kVWithdrawn
AF2-417West Damascus Tap-West Damascus 69 kVEngineering & Procurement
AF2-421East Hazelton-Weatherly Tap 69Engineering & Procurement
AF2-424Reed-Reed Tap #1 69 kVEngineering & Procurement
AF2-425Reed-Reed Tap#1 69 kVEngineering & Procurement
AF2-433Columbia-Geisinger Tap #1 69 kVEngineering & Procurement
AF2-434Columbia-Geisinger Tap #1 69 kVEngineering & Procurement
AF2-440Hillsboro-Middleboro 138 kVEngineering & Procurement
AF2-445AFishbach-Port Carbon 69 kVSuspended
AG1-007Tar River 12.5 kVEngineering & Procurement
AG1-017Jay 138 kVUnder Construction
AG1-037Ahoskie 34.5 kVEngineering & Procurement
AG1-038Garner DP-Lancaster 115 kVEngineering & Procurement
AG1-041Osterburg-Bedford North 23 kVWithdrawn
AG1-047Jay 138 kVEngineering & Procurement
AG1-054Potter-Harlan 69 kVEngineering & Procurement
AG1-066Bonnyman 69 kVEngineering & Procurement
AG1-090Philipsburg 115 kVActive
AG1-107Hillsboro-Middleboro 138 kVEngineering & Procurement
AG1-130Burlington 26 kVEngineering & Procurement
AG1-145Lightfoot 34.5 kVIn Service
AG1-156Jack Frost-Lake Harmony 69 kVEngineering & Procurement
AG1-164East Hazelton-Weatherly Tap 69 kVEngineering & Procurement
AG1-165East Hazelton-Weatherly Tap 69 kVEngineering & Procurement
AG1-188Manitou-Oyster Creek 34.5 kVEngineering & Procurement
AG1-189Oyster Creek-Bamber Lake 34.5Engineering & Procurement
AG1-191Chester-Pohatcong Mountain 34.5 kVPartially in Service - Under Construction
AG1-223Larrabee-Allaire 34.5 kVUnder Construction
AG1-254Salem-Woodstown 69 kVEngineering & Procurement
AG1-259Sunbury-Dalmatia 69 kVEngineering & Procurement
AG1-260Sunbury-Dalmatia 69 kVEngineering & Procurement
AG1-281Claysburg-HCR Tap 46 kVEngineering & Procurement
AG1-282Dunnsville 34.5 kVEngineering & Procurement
AG1-301Miller REC-Warrior Ridge 46 kVEngineering & Procurement
AG1-302Olive-Reynolds #1 345 kVUnder Construction
AG1-307Old Chapel-Millville 138 kVEngineering & Procurement
AG1-324Jay-Desoto 138 kVEngineering & Procurement
AG1-348Pequest River-Washington 34.5 kVIn Service
AG1-349Olive-Reynolds #2 345 kVEngineering & Procurement
AG1-351Harrison-Good Hope 138 kVEngineering & Procurement
AG1-362Wernersville 12.47 kVSuspended
AG1-363Black Oak-Hatfield 500 kVEngineering & Procurement
AG1-377Philipsburg 115 kVActive
AG1-378Philipsburg 115 kVActive
AG1-386Smith-Francis Junction 25 kVIn Service
AG1-397Walston 12 kVWithdrawn
AG1-414Mississinewa 138 kVEngineering & Procurement
AG1-450Airey-Vienna 69 kV IIActive
AG1-469Gordonsville 34.5 kVEngineering & Procurement
AG1-478Wilmington 34.5 kVEngineering & Procurement
AG1-480Shawnee 34.5 kVEngineering & Procurement
AG1-482Hamilton 115 kVWithdrawn
AG1-483Dickerson 230 kVEngineering & Procurement
AG1-487Gilbert 230 kVWithdrawn
AG1-495Gilbert-Rocktown 34.5 kVEngineering & Procurement
AG1-499Lambs 12.47 kVUnder Construction
AG1-508Point Lookout 69 kVEngineering & Procurement
AG1-511Kittatinny 230 kVEngineering & Procurement
AG1-515Guilford 138 kVWithdrawn
AG1-532Fields 34.5 kVEngineering & Procurement
AG1-554South Kenton 138 kVEngineering & Procurement
AG1-555Dequine 345 kVEngineering & Procurement
AG1-558Buckner 34.5 kVEngineering & Procurement
AG1-559Caroline Pines 22 kVEngineering & Procurement
AG2-016Oyster Creek-Whitings 34.5 kVActive
AG2-055Deans 500 kVWithdrawn
AG2-074Meckesville Tap 69kVActive
AG2-090Scalp Level 23 kV IVActive
AG2-091Scalp Level 23 kV VActive
AG2-161Wheelabrator Frackville-Gilberton 69 kVActive
AG2-181Airey - Golden Hill 69 kVActive
AG2-182Doubs-Bismark 500 kVActive
AG2-206Tennessee Gas-East Towanda 115 kVActive
AG2-220East Towanda-South Troy 115 kVActive
AG2-221South Troy - North Towanda 34.5 kVActive
AG2-279Hagerstown-Conservit 34.5 kVActive
AG2-281Church 138 kVActive
AG2-288Stonewall 138 kVActive
AG2-297Cumberland 230 kVActive
AG2-327Tennessee Gas-East Towanda 115 kVActive
AG2-347Indian River 230 kV IIActive
AG2-356South Troy - Canton 34.5 kVActive
AG2-380Carville 138 kV IVActive
AG2-411Statler Hill 115 kVActive
AG2-418Blain 115 kVActive
AG2-423Cherry Run–Harmony 138 kVActive
AG2-430Sunbury-Dalmatia 69 kV IIActive
AG2-439Oxbow 34.5 kVActive
AG2-447Cedar Creek 138 kV VIIActive
AG2-456Pierce Brook-Lewis Run 230 kVActive
AG2-457Pierce Brook - Lewis Run 230 kVActive
AG2-477Hokes-Jackson 69 kV IIIActive
AG2-478Hokes-Jackson 69 kV IVActive
AG2-479Penns Tap-Richfield Tie 69 kV IIActive
AG2-481Derry Tap-Derry Bus 69 kV IIIActive
AG2-484Mifflintown Bus-Mifflintown Tap 69 kV IIActive
AG2-561Glory - Glen Campbell 34.5 kVActive
AG2-616Churchtown - Upper Pittsgrove 138 kVActive
AG2-617Waugh Chapel 115 kVActive
AG2-625Pequest River-Furnace Brook Tap 34.5 kV IIActive
AG2-626Pequest River-Furnace Brook Tap 34.5 kV IIIActive
AH1-005East Towanda-South Troy 115 kV IIActive
AH1-027Cartanza 230 kVActive
AH1-054Upton-Whitings 34.5 kVActive
AH1-057Edgewood 12.47 kVActive
AH1-102Seward-Glory 115 kVActive
AH1-201Allegheny-New Baltimore 115kVActive
AH1-203Allegheny-Somerset 115 kVActive
AH1-205Allegheny-New Baltimore 115kVActive
AH1-212Bethlehem - Lilly 46 kVActive
AH1-257Broadway - Washington 34.5 kVActive
AH1-258Belford - Keansburg 34.5 kVActive
AH1-260New Freedom - Monroe 230 kVActive
AH1-265Winslow - Monroe 69kVActive
AH1-268Seward-Glory 115 kV IIActive
AH1-274Butler 69 kVActive
AH1-313Moshannon-Milesburg 230 kV VIIActive
AH1-334Lakehurst - Whitings 34.5 kVActive
AH1-357Pierce Brook-Lewis Run 230kVActive
AH1-358Pierce Brook-Lewis Run 230kVActive
AH1-359Pierce Brook - Lewis Run 230 kVActive
AH1-360Pierce Brook - Lewis Run 230 kVActive
AH1-380Mt Olive - Kenny 69kVActive
AH1-460Hooversville - Scalp Level 115 kVActive
AH1-536Church-Oil City 138kVActive
AH1-584Nelson-Indian River 138kVActive
AH1-585Nelson-Indian River 138kVActive
AH1-586Nelson-Indian River 138kVActive
AH1-587Farmers Valley – Ridgeway 115 kVActive
AH1-588Lewis Run - Pierce Brook 230 kVActive
AH1-589Lewis Run - Pierce Brook 230 kVActive
AH1-634Indian River 230kV IActive
AH1-641Churchtown - Upper Pittsgrove 138kVActive
AH1-667Philipsburg-Shawville 34.5 kVActive
AH1-672Farmview 138 kVActive
AH1-695Three Mile Island 230 kVActive
AH1-701Valero 69 kVActive
AH1-703Bergen 230kVActive
AH1-705Sunbury #1 500kVActive
AH1-707Saegers 230 kVActive
AH1-710Salem 500kVActive
AH1-715Linden 230kVActive
AH1-720East Towanda 230 kVActive
AH1-722Linden 230kVActive
AH1-725Conastone 500 kVActive
AH1-727Brambleton-Goose Creek 500kVActive
AH1-734South Bend 500 kVActive
U2-030Four Mile Ridge Wind 138kVIn Service
U2-072East Lima-Marysville 345kVIn Service
U2-073Frostburg 138kV IIIn Service
V1-011Haviland 138kVIn Service
V1-021Cape May County 12kVIn Service
V2-041Clayville 12kVIn Service
V2-046Pilesgrove Township 12kVIn Service
V3-007Desoto-Tanners Creek #1 345kVIn Service
V3-037Naval Academy Junction 13kVIn Service
V4-054Fairfield Township 12kVIn Service
V4-067Cates Road Egg Harbor Township 12kVDeactivated
V4-068Murphy's 34.5kVIn Service
V4-073Yankee 12.5kVIn Service
W1-003Oak HallIn Service
W1-004Oak HallIn Service
W1-005Oak HallIn Service
W1-006Oak HallIn Service
W1-056Ada-Dunkirk 69kVIn Service
W1-062Clayton 138kVIn Service
W1-130Vine Road 12kVIn Service
W2-030Egg Harbor TownshipIn Service
W2-039Clayville 69kVIn Service
W2-048Brokaw-LanesvilleIn Service
W3-032ACartanza 230kVIn Service
W3-077Broadway-Stewartsville 34.5kVIn Service
W3-106Sussex-Wykertown 34.5kVIn Service
W4-005Blue Mound-LathamIn Service
X2-022Brokaw-LanesvilleIn Service
X2-083Newark 12kVIn Service
X3-005Wildwood 12kVIn Service
X3-008Todd 69kVIn Service
X3-066Church Hill 69kVIn Service
Y1-065Rock Springs 500kVIn Service
Y1-079Wye Mills 69kVIn Service
Y1-080Dorchester 12kVIn Service
Y1-086Morgans CornerIn Service
Y2-105Eagle Point 230kVIn Service
Y3-058Rockawalkin 69kVIn Service
Z1-036WinFall-Chowan 230kVIn Service
Z2-027Pasquotank 34.5kVIn Service
Z2-044Whitakers 34.5kVIn Service
Z2-076Worcester South 25kVIn Service
Z2-077Worcester North 25kVIn Service
Z2-087Pontiac MidPoint-Brokaw 345kVIn Service
Z2-115Deer Creek 12.47kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with potential Affected System impacts. PJM initiates coordination with each Affected System Operator by providing a list of New Service Requests in the Cycle with potential impacts to their respective system. If the Affected System Operator indicates an Affected System Study is required, PJM will notify the Project Developer or Eligible Customer of the need for an Affected System Study. See below if any Affected System Operator requires a study for this project:

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

No cost allocated system reinforcements were identified for this project in the Phase I System Impact Study load flow analysis.

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement: b4000.11
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.11
Title
Expand Black Oak Substation & Loop in the 502 Jct-Woodside 500 kV line (Projected ISD 6/1/2029)
Description
Expand Black Oak Substation to accommodate the connection of the 502 Jct-Woodside 500 kV line and loop the 502 Jct-Woodside 500 kV line into the Black Oak substation by constructing ~0.85 miles of new 500 kV line into and out of Black Oak 500 kV substation
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-627 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-627 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
01DOUBS-8GOOSE CREEK 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.7
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.7
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line - in DVP local area/Millville to Lovettsville section, roughly 10.5 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-627 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-627 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01DOUBS-8GOOSE CREEK 500.0 kV Ckt 1 line(Any)
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.6
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.6
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (Welton Spring to DVP local area, roughly 21 miles) (VA Portion)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-627 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-627 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01DOUBS-8GOOSE CREEK 500.0 kV Ckt 1 line(Any)
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.10
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.10
Title
Install four 250 MVAR cap banks (two on 765 and two on 500 kV side) and a +/-500 MVAR STATCOM on the 765 kV Rocky Point yard
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-627 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-627 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01DOUBS-8GOOSE CREEK 500.0 kV Ckt 1 line(Any)
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.3
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.3
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - APS/FE Section of the line is 145 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-627 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-627 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01DOUBS-8GOOSE CREEK 500.0 kV Ckt 1 line(Any)
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.5
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.5
Title
Install four 250 MVAR shunt capacitors, and a +/-500 MVAR STATCOM at Welton Spring 765 kV substation
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-627 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-627 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01DOUBS-8GOOSE CREEK 500.0 kV Ckt 1 line(Any)
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.9
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.9
Title
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard (Projected ISD 6/1/2029)
Description
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard. Loop in the Doubs-Goose Creek 500 kV line, the Doubs-Aspen 500 kV line, and the Woodside-Goose Creek 500 kV line. Install two 765/500 kV transformer at Rocky Point substation. 765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-627 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-627 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01DOUBS-8GOOSE CREEK 500.0 kV Ckt 1 line(Any)
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.2
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.2
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - AEP Section of the line is 30 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-627 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-627 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01DOUBS-8GOOSE CREEK 500.0 kV Ckt 1 line(Any)
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.4
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.4
Title
Construct a new 765 kV switchyard - Welton Spring (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-627 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-627 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01DOUBS-8GOOSE CREEK 500.0 kV Ckt 1 line(Any)
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.8
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.8
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (DVP local area to Rocky Point, roughly 4.8 miles)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-627 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-627 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01DOUBS-8GOOSE CREEK 500.0 kV Ckt 1 line(Any)
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.1
Title
Add two 765 kV breakers at Amos Substation to expand the breaker and a half scheme to accommodate the new Amos-Welton Spring 765 kV line (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-627 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-627 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
01DOUBS-8GOOSE CREEK 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3780.11
Type
Load Flow
TO
PEPCO
RTEP ID / TO ID
b3780.11
Title
Brighton Statcom and Capacitor (Projected ISD 12/31/2028)
Description
Brighton Statcom and capacitor New STATCOM rating: 350 MVAR New capacitor rating: 350 MVAR
Cost Information
Time Estimate
Dec 31 2028

Not Contingent

Note: AG2-627 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-627 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line(Any)
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line(Any)
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line(Any)
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z2 line(Any)
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line(Any)
WANEETA2-WANEETA3 230.0 kV Ckt Z line(Any)
COOPER-GRACETON 230.0 kV Ckt 1 line(Any)
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.46
Type
Load Flow
TO
PEPCO
RTEP ID / TO ID
b3800.46
Title
North Delta 500 kV termination for the new Peach Bottom-North Delta 500 kV line (PECO work).
Description
Loops in the 500kV line from Peach Bottom to Rock Springs into the new North Delta (Bramah) sub
Cost Information
Time Estimate
Dec 01 2030

Not Contingent

Note: AG2-627 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-627 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line(Any)
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line(Any)
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line(Any)
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z2 line(Any)
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line(Any)
WANEETA2-WANEETA3 230.0 kV Ckt Z line(Any)
COOPER-GRACETON 230.0 kV Ckt 1 line(Any)
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.343
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.343
Title
Uprate bus at Brambleton to support 500kV Line #558 (Aspen to Brambleton) uprate.
Description
Uprate bus at Brambleton to support 500kV Line #558 (Aspen to Brambleton) uprate.
Cost Information
Time Estimate
Nov 28 2025

Not Contingent

Note: AG2-627 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-627 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8BRAMBLETON-AH1-727 TP 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.346
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.346
Title
Cut-in 500kV line from Kraken substation into Yeat substation
Description
Cut-in 500kV line from Kraken substation into Yeat substation
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-627 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-627 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01DOUBS-8GOOSE CREEK 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.325
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.325
Title
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Description
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Cost Information
Time Estimate
Feb 24 2029

Not Contingent

Note: AG2-627 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-627 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01DOUBS-8GOOSE CREEK 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.344
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.344
Title
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AG2-627 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-627 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01DOUBS-8GOOSE CREEK 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.356
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.356
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-627 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-627 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01DOUBS-8GOOSE CREEK 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.345
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.345
Title
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AG2-627 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-627 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01DOUBS-8GOOSE CREEK 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.351
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.351
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AG2-627 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-627 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01DOUBS-8GOOSE CREEK 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.357
Title
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Description
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-627 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-627 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01DOUBS-8GOOSE CREEK 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.349
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.349
Title
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Description
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AG2-627 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-627 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01DOUBS-8GOOSE CREEK 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.352
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.352
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AG2-627 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-627 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01DOUBS-8GOOSE CREEK 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.341
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.341
Title
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.
Description
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV substation and extend approximately 0.2 miles of conductor to fly-over the site.
Cost Information
Time Estimate
Jul 13 2029

Not Contingent

Note: AG2-627 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-627 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01DOUBS-8GOOSE CREEK 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.348
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.348
Title
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.
Description
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers. A new redundant breaker ring will be added at Kraken to accommodate the new 500kV line from North Anna to Kraken.
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-627 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-627 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01DOUBS-8GOOSE CREEK 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.327
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.327
Title
Upgrade/install equipment at Ladysmith Substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230 kV strings of breaker and a half scheme.
Description
Upgrade/install equipment at Ladysmith substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230kV strings of breaker and a half scheme.
Cost Information
Time Estimate
Feb 24 2029

Not Contingent

Note: AG2-627 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-627 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01DOUBS-8GOOSE CREEK 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.342
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.342
Title
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Description
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Cost Information
Time Estimate
Jul 13 2029

Not Contingent

Note: AG2-627 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-627 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01DOUBS-8GOOSE CREEK 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.326
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.326
Title
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Description
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Cost Information
Time Estimate
Feb 24 2029

Not Contingent

Note: AG2-627 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-627 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01DOUBS-8GOOSE CREEK 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.350
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.350
Title
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Description
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AG2-627 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-627 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01DOUBS-8GOOSE CREEK 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.355
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.355
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-627 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-627 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01DOUBS-8GOOSE CREEK 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.41
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3800.41
Title
Conastone-Brighton 500 kV (5011 circuit) - Replace terminal equipment limitations at Conastone 500 kV.
Description
Requires terminal equipment upgrades under b3800.40 to achieve higher line ratings.
Cost Information
Time Estimate
Dec 31 2030

Not Contingent

Note: AG2-627 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-627 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.40
Type
Load Flow
TO
PEPCO
RTEP ID / TO ID
b3800.40
Title
Conastone-Brighton 500 kV (5011 circuit) - Replace terminal equipment limitations at Brighton 500 kV.
Description
Conastone-Brighton 500 kV (5011 circuit) - Replace terminal equipment limitations at Brighton 500 kV. Requires terminal equipment upgrades under b3800.41 to achieve higher line ratings.
Cost Information
Time Estimate
Dec 31 2030

Not Contingent

Note: AG2-627 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-627 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3737.37
Type
Load Flow
TO
LS Power
RTEP ID / TO ID
b3737.37
Title
Silver Run-Hope Creek 230kV Expansion (Projected ISD 6/1/2029)
Description
Add a third set of submarine cables, rerate the overhead segment, and upgrade terminal equipment to achieve a higher rating for the Silver Run-Hope Creek 230 kV line.
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-627 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-627 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
HOPE CREEK-SILVER RUN 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
DPL
RTEP ID / TO ID
(Pending) / (Pending)
Title
Replace terminal equipment at Keeney and Red Lion West Substation (Keeney - Red Lion West 230 kV Line)
Description
To mitigate the (DPL) Keeney - Red Lion West 230 kV Line(23011)(from bus 231003 to 231004) overload, it will require increasing the emergency rating of the Keeney - Red Lion West 230 kV Line by replacing terminal equipment at both Keeney Substation and Red Lion Substation. A- Keeney Substation 1-Upgrade 4" AL Rigid Bus Conductor. 2-Upgrade (4) 2000 A Disconnect Switches. 3-Upgrade (2) 3000 A Breakers. B- Red Lion Substation 1-Upgrade (2) 3000 A Breakers.
Total Cost ($USD)
$8,500,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 60 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-627 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-627 could receive cost allocation. Although AG2-627 may not presently have cost responsibility for this upgrade, AG2-627 is a potential Aggregate Pool Contributor.

FacilityContingency
KEEN_230-RL_230 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
APS
RTEP ID / TO ID
(Pending) / WP-AF1-F-0001
Title
Replace Wave Trap at Keystone
Description
Upgrade/Replace Wave Trap at Keystone on the Keystone-Cabot 500kV line.
Total Cost ($USD)
$364,562
Allocated Cost ($USD)
$0
Time Estimate
19 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-627 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-627 could receive cost allocation. Although AG2-627 may not presently have cost responsibility for this upgrade, AG2-627 is a potential Aggregate Pool Contributor.

FacilityContingency
KEYSTONE-01CABOT 500.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
(Pending)
Title
Single Element Derate - Eliminated by end of 2025
Description
FirstEnergy has an active internal project that will address the single element derate on the Keystone-South Bend 500kV line. This impacts the following contignencies: PN_P2-3_PN-500-DRT32_SRT-A [Breaker] and PN_P2-3_PN-500-004-DRT-002_SRT-SL [Breaker]
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
KEYSTONE-01SOBEND 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3907.1
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3907.1
Title
Reconductor entire 2.5 miles of North Philadelphia to Master 230 kV line
Description
Reconductor entire 2.5 miles of North Philadelphia to Master 230 kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-627 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-627 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
MASTER-N PHILA8 230.0 kV Ckt 1 line(Any)

System Reinforcement: b3907.3
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3907.3
Title
Reconductor 2.12 miles of North Philadelphia to Waneeta 230 kV line including terminal equipment
Description
Reconductor 2.12 miles of North Philadelphia to Waneeta 230 kV line including terminal equipment
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-627 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-627 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
N PHILA-WANEETA2 230.0 kV Ckt 1 line(Any)

System Reinforcement: b3780.13
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3780.13
Title
Batavia Road to Riverside 230 kV reconductor
Description
Batavia Road to Riverside 230 kV reconductor New rating: 1941 MVA SN / 2181 MVA SE
Cost Information
Time Estimate
Dec 31 2027

Not Contingent

Note: AG2-627 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-627 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line(Any)
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line(Any)
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line(Any)
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z2 line(Any)
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line(Any)
WANEETA2-WANEETA3 230.0 kV Ckt Z line(Any)
COOPER-GRACETON 230.0 kV Ckt 1 line(Any)
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.32
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3800.32
Title
Build new North Delta-High Ridge 500 kV line - BGE Portion (Projected ISD 12/31/2030)
Description
Build new North Delta-High Ridge 500 kV line. (~59 miles)
Cost Information
Time Estimate
Dec 31 2030

Not Contingent

Note: AG2-627 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-627 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line(Any)
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line(Any)
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line(Any)
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z2 line(Any)
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line(Any)
WANEETA2-WANEETA3 230.0 kV Ckt Z line(Any)
COOPER-GRACETON 230.0 kV Ckt 1 line(Any)
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.34
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3800.34
Title
Rebuild 5012 (existing Peach Bottom-Conastone) (new Graceton-Conastone) 500 kV and cut into North Delta 500kV (Projected ISD 12/31/2030)
Description
Rebuild 5012 (existing Peach Bottom-Conastone) (new Graceton-Conastone) 500 kV line on single circuit structures within existing ROW and cut into North Delta 500 kV and Gracetone 500 kV stations.
Cost Information
Time Estimate
Dec 31 2030

Not Contingent

Note: AG2-627 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-627 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line(Any)
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line(Any)
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line(Any)
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z2 line(Any)
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line(Any)
WANEETA2-WANEETA3 230.0 kV Ckt Z line(Any)
COOPER-GRACETON 230.0 kV Ckt 1 line(Any)
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3780.8
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3780.8
Title
Graceton 500 kV substation expansion (Projected ISD 12/31/2028)
Description
Add 3x 500 kV breaker bays, 2x 500/230 kV auto transformer, 1x 500 kV caps
Cost Information
Time Estimate
Dec 31 2028

Not Contingent

Note: AG2-627 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-627 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line(Any)
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line(Any)
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line(Any)
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z2 line(Any)
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line(Any)
WANEETA2-WANEETA3 230.0 kV Ckt Z line(Any)
COOPER-GRACETON 230.0 kV Ckt 1 line(Any)
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.27
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3800.27
Title
High Ridge 500 kV substation (cut into Brighton-Waugh Chapel 500 kV line) - Waugh Chapel side (Projected ISD 12/31/2030)
Description
None
Cost Information
Time Estimate
Dec 31 2030

Not Contingent

Note: AG2-627 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-627 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line(Any)
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line(Any)
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line(Any)
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z2 line(Any)
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line(Any)
WANEETA2-WANEETA3 230.0 kV Ckt Z line(Any)
COOPER-GRACETON 230.0 kV Ckt 1 line(Any)
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.50
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3800.50
Title
North Delta 500 kV termination for the Rock Springs 500 kV line (5034/5014 line) (Transource work).
Description
Loops in the 500kV line from Peach Bottom to Rock Springs into the new North Delta (Bramah) sub
Cost Information
Time Estimate
Jan 23 2028

Not Contingent

Note: AG2-627 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-627 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
COOPER-GRACETON 230.0 kV Ckt 1 line(Any)
WANEETA2-WANEETA3 230.0 kV Ckt Z line(Any)
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line(Any)
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z2 line(Any)
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line(Any)
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line(Any)
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line(Any)
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3780.14
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3780.14
Title
Reconfigure Cooper transmission feeds by establishing new Cooper-North Delta 230 kV line and rerouting existing transmissions lines by Cooper.
Description
None
Cost Information
Time Estimate
Dec 31 2028

Not Contingent

Note: AG2-627 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-627 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
COOPER-GRACETON 230.0 kV Ckt 1 line(Any)
WANEETA2-WANEETA3 230.0 kV Ckt Z line(Any)
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line(Any)
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z2 line(Any)
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line(Any)
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line(Any)
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line(Any)
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3780.1
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3780.1
Title
Peach Bottom North upgrades – substation work (Projected ISD 12/31/2028)
Description
Add 3x 500 kV breakers to form a breaker-and-a-half bay.
Cost Information
Time Estimate
Dec 31 2028

Not Contingent

Note: AG2-627 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-627 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
COOPER-GRACETON 230.0 kV Ckt 1 line(Any)
WANEETA2-WANEETA3 230.0 kV Ckt Z line(Any)
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line(Any)
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z2 line(Any)
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line(Any)
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line(Any)
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line(Any)
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.31
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3800.31
Title
Build new North Delta-High Ridge 500 kV line - PECO Portion (Projected ISD 12/1/2030)
Description
None
Cost Information
Time Estimate
Dec 01 2030

Not Contingent

Note: AG2-627 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-627 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
COOPER-GRACETON 230.0 kV Ckt 1 line(Any)
WANEETA2-WANEETA3 230.0 kV Ckt Z line(Any)
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line(Any)
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z2 line(Any)
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line(Any)
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line(Any)
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.47
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3800.47
Title
Build new Peach Bottom South-North Delta 500 kV line (Projected ISD 12/1/2030)
Description
Build new Peach Bottom South-North Delta 500 kV line – cut in to Peach Bottom tie No. 1 and extending line to North Delta (~1.25 miles new ROW).
Cost Information
Time Estimate
Dec 01 2030

Not Contingent

Note: AG2-627 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-627 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
COOPER-GRACETON 230.0 kV Ckt 1 line(Any)
WANEETA2-WANEETA3 230.0 kV Ckt Z line(Any)
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line(Any)
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line(Any)
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z2 line(Any)
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line(Any)
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line(Any)
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3737.50
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3737.50
Title
Bring the Peach Bottom-Delta Power Plant 500 kV line “in and out” of North Delta
Description
Bring the Peach Bottom-Delta Power Plant 500 kV line “in and out” of North Delta by constructing a new Peach Bottom-North Delta 500 kV (0.3 miles) cut-in and cut-out lines.
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-627 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-627 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
COOPER-GRACETON 230.0 kV Ckt 1 line(Any)
WANEETA2-WANEETA3 230.0 kV Ckt Z line(Any)
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line(Any)
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z2 line(Any)
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line(Any)
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line(Any)
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line(Any)
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.52
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3800.52
Title
Reconfigure Peach Bottom North and South 500 kV yards (Projected ISD 12/1/2030)
Description
Reconfigure Peach Bottom North and South yards to allow for termination of 500 kV lines from Peach Bottom to North Delta. North Delta 500 kV termination for the new Peach Bottom-North Delta 500 kV line.
Cost Information
Time Estimate
Dec 01 2030

Not Contingent

Note: AG2-627 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-627 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
COOPER-GRACETON 230.0 kV Ckt 1 line(Any)
WANEETA2-WANEETA3 230.0 kV Ckt Z line(Any)
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line(Any)
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z2 line(Any)
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line(Any)
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line(Any)
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.45
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3800.45
Title
North Delta 500 kV termination for the Rock Springs 500 kV line (5034/5014 line) (PECO work).
Description
Loops in the 500kV line from Peach Bottom to Rock Springs into the new North Delta (Bramah) sub
Cost Information
Time Estimate
Dec 01 2030

Not Contingent

Note: AG2-627 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-627 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
COOPER-GRACETON 230.0 kV Ckt 1 line(Any)
WANEETA2-WANEETA3 230.0 kV Ckt Z line(Any)
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line(Any)
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z2 line(Any)
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line(Any)
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line(Any)
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line(Any)
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3780.16
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3780.16
Title
Terminate new Cooper-North Delta 230 kV line (Transource Scope) at North Delta 230 kV
Description
None
Cost Information
Time Estimate
Oct 15 2028

Not Contingent

Note: AG2-627 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-627 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
COOPER-GRACETON 230.0 kV Ckt 1 line(Any)
WANEETA2-WANEETA3 230.0 kV Ckt Z line(Any)
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line(Any)
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z2 line(Any)
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line(Any)
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line(Any)
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3780.17
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3780.17
Title
Cut in 5012 Peach Bottom-Conastone 500 kV line into North Delta 500/230 kV sub (Transource)
Description
Cut in 5012 Peach Bottom-Conastone 500 kV line into North Delta 500/230 kV substation by rebuilding 5012 between new terminal at Peach Bottom South and North Delta on single circuit structures and terminating at North Delta (Transource Scope).
Cost Information
Time Estimate
May 31 2028

Not Contingent

Note: AG2-627 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-627 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
COOPER-GRACETON 230.0 kV Ckt 1 line(Any)
WANEETA2-WANEETA3 230.0 kV Ckt Z line(Any)
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line(Any)
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z2 line(Any)
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line(Any)
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line(Any)
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.49
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3800.49
Title
North Delta 500 kV termination for the Calpine generator (Calpine/Transource work).
Description
None
Cost Information
Time Estimate
Oct 06 2027

Not Contingent

Note: AG2-627 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-627 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
COOPER-GRACETON 230.0 kV Ckt 1 line(Any)
WANEETA2-WANEETA3 230.0 kV Ckt Z line(Any)
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line(Any)
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z2 line(Any)
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line(Any)
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line(Any)
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line(Any)
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.48
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3800.48
Title
North Delta termination for the North Delta-High Ridge 500 line (Transource work).
Description
None
Cost Information
Time Estimate
Dec 15 2030

Not Contingent

Note: AG2-627 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-627 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
COOPER-GRACETON 230.0 kV Ckt 1 line(Any)
WANEETA2-WANEETA3 230.0 kV Ckt Z line(Any)
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line(Any)
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z2 line(Any)
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line(Any)
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line(Any)
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3780.15
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3780.15
Title
Cut in 5012 Peach Bottom-Conastone 500 kV line into North Delta 500/230 kV sub
Description
Cut in 5012 Peach Bottom-Conastone 500 kV line into North Delta 500/230 kV substation by rebuilding 5012 between new terminal at Peach Bottom South and North Delta on single circuit structures and terminating at North Delta.
Cost Information
Time Estimate
Dec 31 2028

Not Contingent

Note: AG2-627 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-627 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
COOPER-GRACETON 230.0 kV Ckt 1 line(Any)
WANEETA2-WANEETA3 230.0 kV Ckt Z line(Any)
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line(Any)
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z2 line(Any)
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line(Any)
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line(Any)
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line(Any)
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.51
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3800.51
Title
North Delta 500 kV termination for the new Peach Bottom-North Delta 500 kV line (Transource work).
Description
Loops in the 500kV line from Peach Bottom to Rock Springs into the new North Delta (Bramah) sub
Cost Information
Time Estimate
May 31 2028

Not Contingent

Note: AG2-627 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-627 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
COOPER-GRACETON 230.0 kV Ckt 1 line(Any)
WANEETA2-WANEETA3 230.0 kV Ckt Z line(Any)
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line(Any)
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z2 line(Any)
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line(Any)
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line(Any)
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line(Any)
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.44
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3800.44
Title
North Delta termination for the North Delta-High Ridge 500 line (PECO work).
Description
None
Cost Information
Time Estimate
Dec 01 2030

Not Contingent

Note: AG2-627 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-627 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
COOPER-GRACETON 230.0 kV Ckt 1 line(Any)
WANEETA2-WANEETA3 230.0 kV Ckt Z line(Any)
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line(Any)
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z2 line(Any)
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line(Any)
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line(Any)
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line(Any)
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3737.47
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3737.47
Title
Build New North Delta 500 kV substation (Four bay breaker and half configuration)
Description
Build New North Delta 500 kV substation (four bay breaker and half configuration) - the substation will include 12 - 500kV breakers and one 500/230 kV transformer, will allow the termination of six - 500 kV lines
Cost Information
Time Estimate
Oct 15 2027

Not Contingent

Note: AG2-627 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-627 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
COOPER-GRACETON 230.0 kV Ckt 1 line(Any)
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line(Any)
WANEETA2-WANEETA3 230.0 kV Ckt Z line(Any)
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z2 line(Any)
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line(Any)
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line(Any)
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line(Any)
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3780.2
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3780.2
Title
Peach Bottom to Graceton (PECO Portion) – New 500kV Line
Description
Peach Bottom to Graceton (PECO Portion) – New 500kV Line. New rating: 4503 MVA SN/ 5022 MVA SE. This is a baseline identified for the announced Brandon Shores deactivation.
Cost Information
Time Estimate
Dec 31 2028

Not Contingent

Note: AG2-627 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-627 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
COOPER-GRACETON 230.0 kV Ckt 1 line(Any)
WANEETA2-WANEETA3 230.0 kV Ckt Z line(Any)
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line(Any)
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z2 line(Any)
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line(Any)
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line(Any)
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line(Any)
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.35
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3800.35
Title
Rebuild 5012 (existing Peach Bottom-Conastone) (new North Delta-Graceton PECO) 500 kV (Projected ISD 12/1/2030)
Description
Rebuild 5012 (existing Peach Bottom-Conastone) (new North Delta-Graceton PECO) 500 kV line on single circuit structures within existing ROW and cut into North Delta 500 kV and Gracetone 500 kV stations.
Cost Information
Time Estimate
Dec 01 2030

Not Contingent

Note: AG2-627 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-627 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
COOPER-GRACETON 230.0 kV Ckt 1 line(Any)
WANEETA2-WANEETA3 230.0 kV Ckt Z line(Any)
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line(Any)
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z2 line(Any)
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line(Any)
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line(Any)
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line(Any)
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.28
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3800.28
Title
High Ridge 500 kV substation (cut into Brighton-Waugh Chapel 500 kV line) -Brighton side (Projected ISD 12/31/2030)
Description
None
Cost Information
Time Estimate
Dec 31 2030

Not Contingent

Note: AG2-627 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-627 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z2 line(Any)
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line(Any)
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line(Any)
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line(Any)
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line(Any)
WANEETA2-WANEETA3 230.0 kV Ckt Z line(Any)
COOPER-GRACETON 230.0 kV Ckt 1 line(Any)
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3780.9
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3780.9
Title
Graceton to Batavia Road 230 kV double circuit pole line (Projected ISD 12/31/2028)
Description
Graceton to Batavia Road 230 kV double circuit pole line New rating: 1331 MVA SN/ 1594 MVA SE
Cost Information
Time Estimate
Dec 31 2028

Not Contingent

Note: AG2-627 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-627 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z2 line(Any)
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line(Any)
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line(Any)
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line(Any)
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line(Any)
WANEETA2-WANEETA3 230.0 kV Ckt Z line(Any)
COOPER-GRACETON 230.0 kV Ckt 1 line(Any)
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3780.6
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3780.6
Title
Build Granite substation + Statcom (Projected ISD 12/31/2028)
Description
Build Granite substation + Statcom. New STATCOM rating: 350 MVAR. Add 4x 230 kV breaker bays.
Cost Information
Time Estimate
Dec 31 2028

Not Contingent

Note: AG2-627 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-627 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z2 line(Any)
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line(Any)
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line(Any)
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line(Any)
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line(Any)
WANEETA2-WANEETA3 230.0 kV Ckt Z line(Any)
COOPER-GRACETON 230.0 kV Ckt 1 line(Any)
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.37
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3800.37
Title
Replace terminal equipment limitations at Conastone 500 kV - on the (existing Peach Bottom-Conastone) or (new Graceton-Conastone) 500 kV line (Projected ISD 12/31/2030)
Description
None
Cost Information
Time Estimate
Dec 31 2030

Not Contingent

Note: AG2-627 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-627 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z2 line(Any)
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line(Any)
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line(Any)
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line(Any)
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line(Any)
WANEETA2-WANEETA3 230.0 kV Ckt Z line(Any)
COOPER-GRACETON 230.0 kV Ckt 1 line(Any)
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3780.7
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3780.7
Title
Build new Batavia Road substation (Projected ISD 12/31/2028)
Description
Build Batavia Road substation. Add 4 x 230kV breaker bays
Cost Information
Time Estimate
Dec 31 2028

Not Contingent

Note: AG2-627 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-627 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z2 line(Any)
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line(Any)
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line(Any)
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line(Any)
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line(Any)
WANEETA2-WANEETA3 230.0 kV Ckt Z line(Any)
COOPER-GRACETON 230.0 kV Ckt 1 line(Any)
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.29
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3800.29
Title
High Ridge termination for the North Delta-High Ridge 500 kV line (Projected ISD 12/31/2030)
Description
None
Cost Information
Time Estimate
Dec 31 2030

Not Contingent

Note: AG2-627 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-627 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z2 line(Any)
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line(Any)
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line(Any)
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line(Any)
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line(Any)
WANEETA2-WANEETA3 230.0 kV Ckt Z line(Any)
COOPER-GRACETON 230.0 kV Ckt 1 line(Any)
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3780.5
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3780.5
Title
Build Solley Road substation + Statcom (Projected ISD 12/31/2028)
Description
Build Solley Road substation + Statcom. New STATCOM rating: 350 MVAR Add 4x 230 kV breakers bays.
Cost Information
Time Estimate
Dec 31 2028

Not Contingent

Note: AG2-627 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-627 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z2 line(Any)
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line(Any)
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line(Any)
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line(Any)
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line(Any)
WANEETA2-WANEETA3 230.0 kV Ckt Z line(Any)
COOPER-GRACETON 230.0 kV Ckt 1 line(Any)
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.33
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3800.33
Title
Replace terminal equipment limitations at Brighton 500 kV - on the existing Brighton-Waugh Chapel 500 kV (5053) or new Brighton-High Ridge 500 kV.
Description
None
Cost Information
Time Estimate
Dec 31 2030

Not Contingent

Note: AG2-627 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-627 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z2 line(Any)
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line(Any)
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line(Any)
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line(Any)
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line(Any)
WANEETA2-WANEETA3 230.0 kV Ckt Z line(Any)
COOPER-GRACETON 230.0 kV Ckt 1 line(Any)
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.36
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3800.36
Title
Rebuild 5012 (existing Peach Bottom-Conastone) (new North Delta-Graceton BGE) 500 kV (Projected ISD 12/31/2030)
Description
Rebuild 5012 (existing Peach Bottom-Conastone) (new North Delta-Graceton BGE) 500 kV line on single circuit structures within existing ROW and cut into North Delta 500 kV and Gracetone 500 kV stations.
Cost Information
Time Estimate
Dec 31 2030

Not Contingent

Note: AG2-627 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-627 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z2 line(Any)
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line(Any)
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line(Any)
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line(Any)
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line(Any)
WANEETA2-WANEETA3 230.0 kV Ckt Z line(Any)
COOPER-GRACETON 230.0 kV Ckt 1 line(Any)
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.26
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3800.26
Title
Build High Ridge 500 kV substation - Three bay breaker and half configuration (Projected ISD 12/31/2030)
Description
None
Cost Information
Time Estimate
Dec 31 2030

Not Contingent

Note: AG2-627 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-627 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z2 line(Any)
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line(Any)
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line(Any)
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line(Any)
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line(Any)
WANEETA2-WANEETA3 230.0 kV Ckt Z line(Any)
COOPER-GRACETON 230.0 kV Ckt 1 line(Any)
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.30
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3800.30
Title
High Ridge - Install two 500/230 kV transformers (Projected ISD 12/31/2030)
Description
None
Cost Information
Time Estimate
Dec 31 2030

Not Contingent

Note: AG2-627 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-627 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z2 line(Any)
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line(Any)
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line(Any)
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line(Any)
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line(Any)
WANEETA2-WANEETA3 230.0 kV Ckt Z line(Any)
COOPER-GRACETON 230.0 kV Ckt 1 line(Any)
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.42
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3800.42
Title
Peach Bottom 500kV North bus upgrade (Projected ISD 12/1/2030)
Description
Peach Bottom 500kV North bus upgrade - Replace 11 – Instances of strain bus conductor used for breaker drops or CT drops, 7 – 500 kV disconnect switches, 7 – Free Standing CTs, 1 – 500 kV breaker, 2 – Breaker relays or meters.
Cost Information
Time Estimate
Dec 01 2030

Not Contingent

Note: AG2-627 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-627 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
COOPER-GRACETON 230.0 kV Ckt 1 line(Any)
WANEETA2-WANEETA3 230.0 kV Ckt Z line(Any)
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line(Any)
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z2 line(Any)
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line(Any)
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line(Any)
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line(Any)
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3780.4
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3780.4
Title
Peach Bottom to Graceton (BGE Portion) – New 500kV Line
Description
New rating: 4503 MVA SN/ 5022 MVA SE. This is a baseline identified for the announced Brandon Shores deactivation.
Cost Information
Time Estimate
Dec 31 2028

Not Contingent

Note: AG2-627 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-627 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z2 line(Any)
NOTTNGHM-NOTTREAC 230.0 kV Ckt 1 line(Any)
NOTTREAC-PCHBTMTP 230.0 kV Ckt 1 line(Any)
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
ROCKSPGS-PCHBTM2S 500.0 kV Ckt 1 line(Any)
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
PCHBTM1S-PBN_EXP_BAY 500.0 kV Ckt 2 line(Any)
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
PCHBTMTP-COOPER2 230.0 kV Ckt 1 line(Any)
WANEETA2-WANEETA3 230.0 kV Ckt Z line(Any)
COOPER-GRACETON 230.0 kV Ckt 1 line(Any)
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)

System Reinforcement: n6471
Type
Load Flow
TO
PECO
RTEP ID / TO ID
n6471 / pe002
Title
Replace 1 piece of station cable in Richmond substation on Richmond-Camden tie line
Description
Replace 1 piece of station cable in Richmond substation on Richmond-Camden tie line
Total Cost ($USD)
$45,000
Allocated Cost ($USD)
$0
Time Estimate
24 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-627 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-627 could receive cost allocation. Although AG2-627 may not presently have cost responsibility for this upgrade, AG2-627 is a potential Aggregate Pool Contributor.

FacilityContingency
RICHRE29-CAMDEN 230.0 kV Ckt 1 line(Any)
RICHRE29-RICHMOND29 230.0 kV Ckt 1 line(Any)

System Reinforcement: n6474
Type
Load Flow
TO
PECO
RTEP ID / TO ID
n6474 / pe004
Title
Replace 2 circuit breakers in Richmond substation on Richmond-Camden tie line
Description
Replace 2 circuit breakers in Richmond substation on Richmond-Camden tie line
Total Cost ($USD)
$752,000
Allocated Cost ($USD)
$0
Time Estimate
36 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-627 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-627 could receive cost allocation. Although AG2-627 may not presently have cost responsibility for this upgrade, AG2-627 is a potential Aggregate Pool Contributor.

FacilityContingency
RICHRE29-CAMDEN 230.0 kV Ckt 1 line(Any)
RICHRE29-RICHMOND29 230.0 kV Ckt 1 line(Any)

System Reinforcement: n6473
Type
Load Flow
TO
PECO
RTEP ID / TO ID
n6473 / pe003
Title
Replace reactor in Richmond substation on Richmond-Camden tie line
Description
Replace reactor in Richmond substation on Richmond-Camden tie line
Total Cost ($USD)
$2,254,000
Allocated Cost ($USD)
$0
Time Estimate
36 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-627 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-627 could receive cost allocation. Although AG2-627 may not presently have cost responsibility for this upgrade, AG2-627 is a potential Aggregate Pool Contributor.

FacilityContingency
RICHRE29-CAMDEN 230.0 kV Ckt 1 line(Any)
RICHRE29-RICHMOND29 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
PSEG
RTEP ID / TO ID
(Pending) / r_PS_AE2_SIS_Camdn0
Title
No PSEG Violation. PSEG emergency rating 1891 MVA.
Description
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
RICHRE29-CAMDEN 230.0 kV Ckt 1 line(Any)

System Reinforcement: b3737.23
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3737.23
Title
Rebuild the underground portion of Richmond-Waneeta 230 kV (Projected ISD 6/1/2029)
Description
NJ OSW SAA baseline
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-627 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-627 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
WANEETA3-RICHMOND35 230.0 kV Ckt 1 line(Any)

System Reinforcement: b3907.2
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3907.2
Title
Rebuild Richmond - Waneeta 230 kV line
Description
Richmond to Waneeta 230kV Line: Rebuild entire 0.95 miles of existing UGT, and rebuild entire 2.23 miles of existing OHT
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-627 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-627 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
WANEETA3-RICHMOND35 230.0 kV Ckt 1 line(Any)

Attachments

AG2-627 One Line Diagram

AG2-627 One Line Diagram.jpg
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.