AG2-637 Phase I Study Report
v1.00 released 2025-10-29 19:46
Randolph - Hodgin 138 kV
90.0 MW Capacity / 150.0 MW Energy
Introduction
This Phase I System Impact Study Report (PH1) has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, sections 307 and 308 for New Service Requests (projects) in Transition Cycle 2. The Project Developer/Eligible Customer (developer) is ACE Development Company, LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is American Electric Power.
Preface
The Phase I System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle executive summary format and (ii) an individual project-level basis. The Phase I System Impact Study Results (for both the executive summary and individual reports) will be publicly available on PJM’s website. Developers must obtain the results from the website.
In accordance with PJM Manual 14H, section 4.3, PJM takes the following actions during the Phase I System Impact Study:
- PJM studies each New Service Request on a summer peak, winter peak and light load RTEP base case study. The case year is dependent on the new services cycle under study. PJM will identify the base case year to be used in the study of a specific cycle on its website.
- PJM will only perform load flow analysis during the Phase I System Impact Study.
- In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with Affected System impacts and provides each Affected System Operator with a list of New Service Request in the Cycle with potential impacts to their respective system.
- PJM will create both the short circuit and stability base cases to be used in the Phase II System Impact Study.
- The Phase I System Impact Study results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.
The Transmission Owner takes the following actions during the Phase I System Impact Study:
- Identify required Interconnection Facilities to accommodate the New Service Request.
- Identify required Network Upgrades to mitigate system violations from the Phase I System Impact Study.
- Provide planning-level preliminary estimates of Interconnection Facilities and Network Upgrades including scope, cost and elapsed time to complete the work.
Decision Point I Requirements
At the close of Phase I System Impact Study, PJM will initiate Decision Point I (DP1). During DP1, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.A.1. Additional information on these elements is available in PJM Manual 14H sections 4.4, 6, and 7.
Allowable project modifications at Decision Point I are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.
General
The Project Developer has proposed a Solar generating facility located in the American Electric Power zone — Randolph County, Indiana. The installed facilities will have a total capability of 150.0 MW with 90.0 MW of this output being recognized by PJM as Capacity.Project Information
Physical Interconnection Facility Study
Physical Interconnection Facilities Study is not performed as part of the Phase I System Impact Study. Physical Interconnection Facilities Study will commence in the Phase II System Impact Study.
Point of Interconnection
AG2-637 will interconnect on the American Electric Power transmission system by tapping the Randolph - College Corner 138 kV Line.
Cost Summary
The table below shows a summary of the total cost estimates for this New Service Request project. In the Phase I SIS, the costs shown are subject to change as a result of a facility study performed by the TO during the Phase II or Phase III System Impact Study.
Based on the Phase I SIS results, the AG2-637 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit are also shown below.
| Cost Summary | |||
|---|---|---|---|
| Description | Cost Allocated to AG2-637 | Cost Subject to Readiness* | |
| Transmission Owner Interconnection Facilities (TOIF) | $0 | $0 | |
| Other Scope | $0 | $0 | |
| Option To Build Oversight | $0 | $0 | |
| Physical Interconnection Network Upgrades | |||
| Stand Alone Network Upgrades | $16,775,000 | $16,775,000 | |
| Network Upgrades | $0 | $0 | |
| System Reliability Network Upgrades | |||
| Steady State Thermal & Voltage (SP & LL) | $41,208,783 | $41,208,783 | |
| Transient Stability | $0 | $0 | |
| Short Circuit | $0 | $0 | |
| Transmission Owner Analysis | |||
| SubRegional | $305,924 | $305,924 | |
| Distribution | $0 | $0 | |
| Affected System Reinforcements | |||
| AFS - PJM Violatons | $0 | $0 | |
| AFS - Non-PJM Violations | $0 | $0 | |
| Total | $58,289,707 | $58,289,707 | |
* Contributes to calculation for Readiness Deposit #2 (RD2). See Readiness Deposit section of report for additional detail.
Definitions
Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.
Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.
Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.
Notes
Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.
Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.
Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim deliverability study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.
Readiness Deposit
Per Tariff Part VII, Subpart D, section 309 (Decision Point I) A.1.a.i and PJM Manual 14H, section 6.2, Readiness Deposit #2 (RD2) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.
During Decision Point I (DP1), the Project Developer or Eligible Customer is required to submit Readiness Deposit #2, which is calculated as 10% of cost allocation for required Phase I Network Upgrades minus Readiness Deposit #1.
Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.
Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))
Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.
Readiness Deposit #2 Due for Project AG2-637
Readiness Deposit #2 has been calculated for the project based on the Phase I System Impact Study results and is shown in the table below. This Readiness Deposit #2 must be provided at Decision Point I through either a wire transfer or letter of credit per Manual 14H, Section 6.2.
| Readiness Deposit | |||
|---|---|---|---|
| Project ID | 10% of cost allocation for Phase I Network Upgrades | Readiness Deposit #1 Received (RD1) | Readiness Deposit #2 (RD2) for AG2-637 Project due at DP1 |
| A | B | A - B | |
| AG2-637 | $5,828,971 | $600,000 | $5,228,971 |
Note: Failure to provide an acceptable form of Readiness Deposit #2 by the end of Decision Point I will result in withdrawal and termination of the New Service Request.
For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.
Transmission Owner Scope of Work
The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.
| Stand-Alone Network Upgrades | |||
|---|---|---|---|
| RTEP ID | Description | Total Cost ($USD) | Allocated Cost ($USD) |
| (Pending) | AEP will construct a new breaker and a half station, initially populated with 3 breakers and operated as a ring bus as well as the associated facilities required to support the interconnection. | $16,775,000 | $16,775,000 |
Based on the scope of work for the Interconnection Facilities, it is expected to take a range of 24 to 30 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.
The schedule for any required Network Impact Reinforcements will be more clearly identified in the Phase II and Phase III System Impact Studies.
Transmission Owner Analysis
There were no network impacts to Distribution facilities identified by the Transmission Owner.
The Transmission Owner identified network impacts to Sub-Regional facilities as follows:
| Overloaded Element | Contingency | Rating [MVA] | Final Cycle Loading % | Contribution [MW] |
|---|---|---|---|---|
| 246005 053-M 69.0 - 245974 05HARTF CT 69.0 CKT 1 | AEP_P4_#14047_05DESOTO 138_F_SRT-A CONTINGENCY 'AEP_P4_#14047_05DESOTO 138_F_SRT-A' /* OPEN BRANCH FROM BUS 243278 TO BUS 247837 CKT 1 / 243278 05DESOTO 138 247837 05PERCH 138 1 OPEN BRANCH FROM BUS 243278 TO BUS 946030 CKT 1 / 243278 05DESOTO 138 946030 AF1-268 138 1 /* OPEN BRANCH FROM BUS 243319 TO BUS 247837 CKT 1 / 243319 05JAY 138 247837 05PERCH 138 1 OPEN BRANCH FROM BUS 243278 TO BUS 243340 CKT 1 / 243278 05DESOTO 138 243340 05MEDFOR 138 1 END | 71.0 | 156.36 % | 8.92 |
| 246005 053-M 69.0 - 245974 05HARTF CT 69.0 CKT 1 | AEP_P1-2_#15020_SRT-A-1 CONTINGENCY 'AEP_P1-2_#15020_SRT-A-1' OPEN BRANCH FROM BUS 243278 TO BUS 946030 CKT 1 / 243278 05DESOTO 138 946030 AF1-268 TP 138 1 END | 71.0 | 156.35 % | 8.92 |
| 246005 053-M 69.0 - 245974 05HARTF CT 69.0 CKT 1 | AEP_P4_#15019_05DESOTO 138_F1_SRT-A-1 CONTINGENCY 'AEP_P4_#15019_05DESOTO 138_F1_SRT-A-1' OPEN BRANCH FROM BUS 243278 TO BUS 946030 CKT 1 / 243278 05DESOTO 138 946030 AF1-268 TP 138 1 END | 71.0 | 156.35 % | 8.92 |
| 246005 053-M 69.0 - 245974 05HARTF CT 69.0 CKT 1 | AEP_P1-2_#15020_SRT-A-2 CONTINGENCY 'AEP_P1-2_#15020_SRT-A-2' OPEN BRANCH FROM BUS 946030 TO BUS 247837 CKT 1 / 946030 AF1-268 TP 138 247837 05PERCH 138 1 OPEN BRANCH FROM BUS 964610 TO BUS 247837 CKT 1 / 964610 AG1-324 TP 138 247837 05PERCH 138 1 END | 71.0 | 144.04 % | 8.92 |
| 246005 053-M 69.0 - 245974 05HARTF CT 69.0 CKT 1 | AEP_P1-2_#15020_SRT-A-3 CONTINGENCY 'AEP_P1-2_#15020_SRT-A-3' OPEN BRANCH FROM BUS 243319 TO BUS 964610 CKT 1 / 243319 05JAY 138 964610 AG1-324 TP 138 1 END | 71.0 | 134.52 % | 8.92 |
| 246005 053-M 69.0 - 245974 05HARTF CT 69.0 CKT 1 | AEP_P4_#15176_05JAY 138_E2_SRT-A CONTINGENCY 'AEP_P4_#15176_05JAY 138_E2_SRT-A' /* OPEN BRANCH FROM BUS 243278 TO BUS 247837 CKT 1 / 243278 05DESOTO 138 247837 05PERCH 138 1 /* OPEN BRANCH FROM BUS 243319 TO BUS 247837 CKT 1 / 243319 05JAY 138 247837 05PERCH 138 1 OPEN BRANCH FROM BUS 243319 TO BUS 964610 CKT 1 / 243319 05JAY 138 964610 AG1-324 TP 138 1 OPEN BRANCH FROM BUS 243319 TO BUS 290130 CKT 2 / 243319 05JAY 138 290130 05JAY 2EQ 1.00 2 OPEN BRANCH FROM BUS 246016 TO BUS 290130 CKT 2 / 246016 05JAY 69.0 290130 05JAY 2EQ 1.00 2 OPEN BRANCH FROM BUS 290130 TO BUS 290132 CKT 2 / 290130 05JAY 2EQ 1.00 290132 05JAY T2 13.0 2 REMOVE SWSHUNT FROM BUS 243319 / 243319 05JAY 138 END | 71.0 | 126.04 % | 8.56 |
| 246005 053-M 69.0 - 245974 05HARTF CT 69.0 CKT 1 | AEP_P4_#15023_05JAY 138_E_SRT-A CONTINGENCY 'AEP_P4_#15023_05JAY 138_E_SRT-A' OPEN BRANCH FROM BUS 243319 TO BUS 246018 CKT 4 / 243319 05JAY 138 246018 05JAY 4EQ 1.00 4 OPEN BRANCH FROM BUS 246016 TO BUS 246018 CKT 4 / 246016 05JAY 69.0 246018 05JAY 4EQ 1.00 4 OPEN BRANCH FROM BUS 246015 TO BUS 246018 CKT 4 / 246015 05JAY 34.5 246018 05JAY 4EQ 1.00 4 /* OPEN BRANCH FROM BUS 243319 TO BUS 247837 CKT 1 / 243319 05JAY 138 247837 05PERCH 138 1 OPEN BRANCH FROM BUS 243319 TO BUS 964610 CKT 1 / 243319 05JAY 138 964610 AG1-324 TP 138 1 /* OPEN BRANCH FROM BUS 243278 TO BUS 247837 CKT 1 / 243278 05DESOTO 138 247837 05PERCH 138 1 END | 71.0 | 120.49 % | 8.28 |
| 246014 05BLUFFPNT 69.0 - 246022 05PORTLAND 69.0 CKT 1 | AEP_P4_#10531_05JAY 138_D_SRT-A CONTINGENCY 'AEP_P4_#10531_05JAY 138_D_SRT-A' OPEN BRANCH FROM BUS 243237 TO BUS 270019 CKT 1 / 243237 05ADAM 138 270019 AE2-089 TAP 138 1 OPEN BRANCH FROM BUS 270019 TO BUS 243358 CKT 1 / 270019 AE2-089 TAP 138 243358 05PENNVI 138 1 OPEN BRANCH FROM BUS 243319 TO BUS 243358 CKT 1 / 243319 05JAY 138 243358 05PENNVI 138 1 OPEN BRANCH FROM BUS 243253 TO BUS 243319 CKT 1 / 243253 05BLUFFP 138 243319 05JAY 138 1 END | 86.0 | 125.97 % | 29.77 |
| 246014 05BLUFFPNT 69.0 - 246022 05PORTLAND 69.0 CKT 1 | AEP_P4_#15175_05JAY 138_D2_SRT-A CONTINGENCY 'AEP_P4_#15175_05JAY 138_D2_SRT-A' OPEN BRANCH FROM BUS 243253 TO BUS 243319 CKT 1 / 243253 05BLUFFP 138 243319 05JAY 138 1 OPEN BRANCH FROM BUS 243319 TO BUS 290130 CKT 2 / 243319 05JAY 138 290130 05JAY 2EQ 1.00 2 OPEN BRANCH FROM BUS 246016 TO BUS 290130 CKT 2 / 246016 05JAY 69.0 290130 05JAY 2EQ 1.00 2 OPEN BRANCH FROM BUS 290130 TO BUS 290132 CKT 2 / 290130 05JAY 2EQ 1.00 290132 05JAY T2 13.0 2 REMOVE SWSHUNT FROM BUS 243319 / 243319 05JAY 138 END | 86.0 | 123.47 % | 29.29 |
| 246079 05PRICE 69.0 - 246076 05ANCHORHO 69.0 CKT 1 | AEP_P1-2_#17621_SRT-A-3 CONTINGENCY 'AEP_P1-2_#17621_SRT-A-3' OPEN BRANCH FROM BUS 971672 TO BUS 290085 CKT 1 / 971672 AH1-337 TP 138 290085 05HODGIN_BP 138 1 OPEN BRANCH FROM BUS 290084 TO BUS 290085 CKT 1 / 290084 05HAYES 138 290085 05HODGIN_BP 138 1 END | 50.0 | 160.78 % | 15.83 |
| 246079 05PRICE 69.0 - 246076 05ANCHORHO 69.0 CKT 1 | AEP_P4_#17624_05HAYES 138_A_SRT-A CONTINGENCY 'AEP_P4_#17624_05HAYES 138_A_SRT-A' / OPEN BRANCH FROM BUS 244587 TO BUS 290085 CKT 1 / 244587 05RANDOLPH2 138 290085 05HODGIN_BP 138 1 OPEN BRANCH FROM BUS 971672 TO BUS 290085 CKT 1 / 971672 AH1-337 TP(05RANDOLPH2) 138 290085 05HODGIN_BP 138 1 OPEN BRANCH FROM BUS 290084 TO BUS 290085 CKT 1 / 290084 05HAYES 138 290085 05HODGIN_BP 138 1 OPEN BRANCH FROM BUS 243310 TO BUS 290084 CKT 1 / 243310 05HODGIN 138 290084 05HAYES 138 1 OPEN BRANCH FROM BUS 243310 TO BUS 243400 CKT 1 / 243310 05HODGIN 138 243400 05HODGIN 69.0 1 END | 50.0 | 160.63 % | 15.83 |
| 246079 05PRICE 69.0 - 246076 05ANCHORHO 69.0 CKT 1 | AEP_P4_#17625_05HAYES 138_B_SRT-A-1 CONTINGENCY 'AEP_P4_#17625_05HAYES 138_B_SRT-A-1' OPEN BRANCH FROM BUS 971672 TO BUS 290085 CKT 1 / 971672 AH1-337 TP 138 290085 05HODGIN_BP 138 1 OPEN BRANCH FROM BUS 290084 TO BUS 290085 CKT 1 / 290084 05HAYES 138 290085 05HODGIN_BP 138 1 OPEN BRANCH FROM BUS 253290 TO BUS 290084 CKT 1 / 253290 09BLAZER 138 290084 05HAYES 138 1 END | 50.0 | 159.25 % | 15.82 |
| 246079 05PRICE 69.0 - 246076 05ANCHORHO 69.0 CKT 1 | AEP_P1-2_#17621_SRT-A-2 CONTINGENCY 'AEP_P1-2_#17621_SRT-A-2' OPEN BRANCH FROM BUS 971028 TO BUS 971672 CKT 1 / 971028 AG2-637 TP 138 971672 AH1-337 TP 138 1 END | 50.0 | 151.09 % | 15.83 |
| 246079 05PRICE 69.0 - 246076 05ANCHORHO 69.0 CKT 1 | AEP_P1-2_#15020_SRT-A-1 CONTINGENCY 'AEP_P1-2_#15020_SRT-A-1' OPEN BRANCH FROM BUS 243278 TO BUS 946030 CKT 1 / 243278 05DESOTO 138 946030 AF1-268 TP 138 1 END | 50.0 | 131.9 % | 10.92 |
| 246079 05PRICE 69.0 - 246076 05ANCHORHO 69.0 CKT 1 | AEP_P4_#15019_05DESOTO 138_F1_SRT-A-1 CONTINGENCY 'AEP_P4_#15019_05DESOTO 138_F1_SRT-A-1' OPEN BRANCH FROM BUS 243278 TO BUS 946030 CKT 1 / 243278 05DESOTO 138 946030 AF1-268 TP 138 1 END | 50.0 | 131.9 % | 10.92 |
| 246079 05PRICE 69.0 - 246076 05ANCHORHO 69.0 CKT 1 | AEP_P4_#14047_05DESOTO 138_F_SRT-A CONTINGENCY 'AEP_P4_#14047_05DESOTO 138_F_SRT-A' /* OPEN BRANCH FROM BUS 243278 TO BUS 247837 CKT 1 / 243278 05DESOTO 138 247837 05PERCH 138 1 OPEN BRANCH FROM BUS 243278 TO BUS 946030 CKT 1 / 243278 05DESOTO 138 946030 AF1-268 138 1 /* OPEN BRANCH FROM BUS 243319 TO BUS 247837 CKT 1 / 243319 05JAY 138 247837 05PERCH 138 1 OPEN BRANCH FROM BUS 243278 TO BUS 243340 CKT 1 / 243278 05DESOTO 138 243340 05MEDFOR 138 1 END | 50.0 | 131.37 % | 10.91 |
| 246079 05PRICE 69.0 - 246076 05ANCHORHO 69.0 CKT 1 | AEP_P1-2_#15020_SRT-A-2 CONTINGENCY 'AEP_P1-2_#15020_SRT-A-2' OPEN BRANCH FROM BUS 946030 TO BUS 247837 CKT 1 / 946030 AF1-268 TP 138 247837 05PERCH 138 1 OPEN BRANCH FROM BUS 964610 TO BUS 247837 CKT 1 / 964610 AG1-324 TP 138 247837 05PERCH 138 1 END | 50.0 | 124.85 % | 10.92 |
| 246079 05PRICE 69.0 - 246076 05ANCHORHO 69.0 CKT 1 | AEP_P4_#15023_05JAY 138_E_SRT-A CONTINGENCY 'AEP_P4_#15023_05JAY 138_E_SRT-A' OPEN BRANCH FROM BUS 243319 TO BUS 246018 CKT 4 / 243319 05JAY 138 246018 05JAY 4EQ 1.00 4 OPEN BRANCH FROM BUS 246016 TO BUS 246018 CKT 4 / 246016 05JAY 69.0 246018 05JAY 4EQ 1.00 4 OPEN BRANCH FROM BUS 246015 TO BUS 246018 CKT 4 / 246015 05JAY 34.5 246018 05JAY 4EQ 1.00 4 /* OPEN BRANCH FROM BUS 243319 TO BUS 247837 CKT 1 / 243319 05JAY 138 247837 05PERCH 138 1 OPEN BRANCH FROM BUS 243319 TO BUS 964610 CKT 1 / 243319 05JAY 138 964610 AG1-324 TP 138 1 /* OPEN BRANCH FROM BUS 243278 TO BUS 247837 CKT 1 / 243278 05DESOTO 138 247837 05PERCH 138 1 END | 50.0 | 121.38 % | 10.99 |
| 246079 05PRICE 69.0 - 246076 05ANCHORHO 69.0 CKT 1 | AEP_P7-1_#11037___SRT-A CONTINGENCY 'AEP_P7-1_#11037___SRT-A' OPEN BRANCH FROM BUS 243278 TO BUS 243373 CKT 1 / 243278 05DESOTO 138 243373 05SELMAP 138 1 OPEN BRANCH FROM BUS 243278 TO BUS 246629 CKT 1 / 243278 05DESOTO 138 246629 05SELMA P_BP 138 1 OPEN BRANCH FROM BUS 246629 TO BUS 270378 CKT 1 / 246629 05SELMA P_BP 138 270378 AD1-128 TAP 138 1 OPEN BRANCH FROM BUS 243344 TO BUS 270378 CKT 1 / 243344 05MODOC 138 270378 AD1-128 TAP 138 1 END | 50.0 | 108.07 % | 6.81 |
| 246087 05RANDOLPH 69.0 - 246079 05PRICE 69.0 CKT 1 | AEP_P4_#10527_05BLUFFP 138_E2_SRT-A CONTINGENCY 'AEP_P4_#10527_05BLUFFP 138_E2_SRT-A' OPEN BRANCH FROM BUS 243253 TO BUS 243319 CKT 1 / 243253 05BLUFFP 138 243319 05JAY 138 1 OPEN BRANCH FROM BUS 243253 TO BUS 246014 CKT 1 / 243253 05BLUFFP 138 246014 05BLUFFPNT 69.0 1 END | 86.0 | 109.1 % | 28.49 |
| 246087 05RANDOLPH 69.0 - 246079 05PRICE 69.0 CKT 1 | AEP_P4_#17624_05HAYES 138_A_SRT-A CONTINGENCY 'AEP_P4_#17624_05HAYES 138_A_SRT-A' / OPEN BRANCH FROM BUS 244587 TO BUS 290085 CKT 1 / 244587 05RANDOLPH2 138 290085 05HODGIN_BP 138 1 OPEN BRANCH FROM BUS 971672 TO BUS 290085 CKT 1 / 971672 AH1-337 TP(05RANDOLPH2) 138 290085 05HODGIN_BP 138 1 OPEN BRANCH FROM BUS 290084 TO BUS 290085 CKT 1 / 290084 05HAYES 138 290085 05HODGIN_BP 138 1 OPEN BRANCH FROM BUS 243310 TO BUS 290084 CKT 1 / 243310 05HODGIN 138 290084 05HAYES 138 1 OPEN BRANCH FROM BUS 243310 TO BUS 243400 CKT 1 / 243310 05HODGIN 138 243400 05HODGIN 69.0 1 END | 86.0 | 103.56 % | 24.33 |
| 246087 05RANDOLPH 69.0 - 246079 05PRICE 69.0 CKT 1 | AEP_P4_#17625_05HAYES 138_B_SRT-A-1 CONTINGENCY 'AEP_P4_#17625_05HAYES 138_B_SRT-A-1' OPEN BRANCH FROM BUS 971672 TO BUS 290085 CKT 1 / 971672 AH1-337 TP 138 290085 05HODGIN_BP 138 1 OPEN BRANCH FROM BUS 290084 TO BUS 290085 CKT 1 / 290084 05HAYES 138 290085 05HODGIN_BP 138 1 OPEN BRANCH FROM BUS 253290 TO BUS 290084 CKT 1 / 253290 09BLAZER 138 290084 05HAYES 138 1 END | 86.0 | 102.47 % | 24.32 |
| 247883 05FULKERSNSS 69.0 - 246005 053-M 69.0 CKT 1 | AEP_P4_#14047_05DESOTO 138_F_SRT-A CONTINGENCY 'AEP_P4_#14047_05DESOTO 138_F_SRT-A' /* OPEN BRANCH FROM BUS 243278 TO BUS 247837 CKT 1 / 243278 05DESOTO 138 247837 05PERCH 138 1 OPEN BRANCH FROM BUS 243278 TO BUS 946030 CKT 1 / 243278 05DESOTO 138 946030 AF1-268 138 1 /* OPEN BRANCH FROM BUS 243319 TO BUS 247837 CKT 1 / 243319 05JAY 138 247837 05PERCH 138 1 OPEN BRANCH FROM BUS 243278 TO BUS 243340 CKT 1 / 243278 05DESOTO 138 243340 05MEDFOR 138 1 END | 71.0 | 163.87 % | 8.92 |
| 247883 05FULKERSNSS 69.0 - 246005 053-M 69.0 CKT 1 | AEP_P4_#15019_05DESOTO 138_F1_SRT-A-1 CONTINGENCY 'AEP_P4_#15019_05DESOTO 138_F1_SRT-A-1' OPEN BRANCH FROM BUS 243278 TO BUS 946030 CKT 1 / 243278 05DESOTO 138 946030 AF1-268 TP 138 1 END | 71.0 | 163.86 % | 8.92 |
| 247883 05FULKERSNSS 69.0 - 246005 053-M 69.0 CKT 1 | AEP_P1-2_#15020_SRT-A-1 CONTINGENCY 'AEP_P1-2_#15020_SRT-A-1' OPEN BRANCH FROM BUS 243278 TO BUS 946030 CKT 1 / 243278 05DESOTO 138 946030 AF1-268 TP 138 1 END | 71.0 | 163.85 % | 8.92 |
| 247883 05FULKERSNSS 69.0 - 246005 053-M 69.0 CKT 1 | AEP_P1-2_#15020_SRT-A-2 CONTINGENCY 'AEP_P1-2_#15020_SRT-A-2' OPEN BRANCH FROM BUS 946030 TO BUS 247837 CKT 1 / 946030 AF1-268 TP 138 247837 05PERCH 138 1 OPEN BRANCH FROM BUS 964610 TO BUS 247837 CKT 1 / 964610 AG1-324 TP 138 247837 05PERCH 138 1 END | 71.0 | 151.56 % | 8.92 |
| 247883 05FULKERSNSS 69.0 - 246005 053-M 69.0 CKT 1 | AEP_P1-2_#15020_SRT-A-3 CONTINGENCY 'AEP_P1-2_#15020_SRT-A-3' OPEN BRANCH FROM BUS 243319 TO BUS 964610 CKT 1 / 243319 05JAY 138 964610 AG1-324 TP 138 1 END | 71.0 | 141.68 % | 8.92 |
| 247883 05FULKERSNSS 69.0 - 246005 053-M 69.0 CKT 1 | AEP_P4_#15176_05JAY 138_E2_SRT-A CONTINGENCY 'AEP_P4_#15176_05JAY 138_E2_SRT-A' /* OPEN BRANCH FROM BUS 243278 TO BUS 247837 CKT 1 / 243278 05DESOTO 138 247837 05PERCH 138 1 /* OPEN BRANCH FROM BUS 243319 TO BUS 247837 CKT 1 / 243319 05JAY 138 247837 05PERCH 138 1 OPEN BRANCH FROM BUS 243319 TO BUS 964610 CKT 1 / 243319 05JAY 138 964610 AG1-324 TP 138 1 OPEN BRANCH FROM BUS 243319 TO BUS 290130 CKT 2 / 243319 05JAY 138 290130 05JAY 2EQ 1.00 2 OPEN BRANCH FROM BUS 246016 TO BUS 290130 CKT 2 / 246016 05JAY 69.0 290130 05JAY 2EQ 1.00 2 OPEN BRANCH FROM BUS 290130 TO BUS 290132 CKT 2 / 290130 05JAY 2EQ 1.00 290132 05JAY T2 13.0 2 REMOVE SWSHUNT FROM BUS 243319 / 243319 05JAY 138 END | 71.0 | 133.0 % | 8.56 |
| 247883 05FULKERSNSS 69.0 - 246005 053-M 69.0 CKT 1 | AEP_P4_#15023_05JAY 138_E_SRT-A CONTINGENCY 'AEP_P4_#15023_05JAY 138_E_SRT-A' OPEN BRANCH FROM BUS 243319 TO BUS 246018 CKT 4 / 243319 05JAY 138 246018 05JAY 4EQ 1.00 4 OPEN BRANCH FROM BUS 246016 TO BUS 246018 CKT 4 / 246016 05JAY 69.0 246018 05JAY 4EQ 1.00 4 OPEN BRANCH FROM BUS 246015 TO BUS 246018 CKT 4 / 246015 05JAY 34.5 246018 05JAY 4EQ 1.00 4 /* OPEN BRANCH FROM BUS 243319 TO BUS 247837 CKT 1 / 243319 05JAY 138 247837 05PERCH 138 1 OPEN BRANCH FROM BUS 243319 TO BUS 964610 CKT 1 / 243319 05JAY 138 964610 AG1-324 TP 138 1 /* OPEN BRANCH FROM BUS 243278 TO BUS 247837 CKT 1 / 243278 05DESOTO 138 247837 05PERCH 138 1 END | 71.0 | 126.71 % | 8.28 |
| TO | RTEP ID / TO ID | Category | Title | MW Impact | Percent Allocation | Allocated Cost ($USD) |
|---|---|---|---|---|---|---|
| AEP | (Pending) / TC2-AEP-191 | SubRegional | Hartford City - 3M: Perform relay upgrades to increase 3M CT thermal limit and relay thermal limit. Replace three 477 AAC 19-Str station conductor at 3M station. | 8.9 MW | 27.4% | $109,616 |
| AEP | (Pending) / TC2-AEP-192 | SubRegional | Bluff Point - Portland: Replace Bluff Point 69 kV 300 MCM CU 37 Str riser, Replace the Portland 69 kV 600 A switch, sag study and mitigation ~7.5 miles of the conductor 556.5 ACSR 26/7 | 29.8 MW | 43.3% | $86,692 |
| AEP | (Pending) / TC2-AEP-203 | SubRegional | Randolph - Price: Summer emergency rating is 142 MVA. | 28.5 MW | 46.2% | $0 |
| AEP | (Pending) / TC2-AEP-194 | SubRegional | Fulkerson Switch - 3M: Perform relay upgrades to increase 3M CT thermal limit and relay thermal limit. Replace three 477 AAC 19-Str station conductor at 3M station. | 8.9 MW | 27.4% | $109,616 |
| Grand Total: | $305,924 | |||||
System Reinforcement
- TO
- AEP
- RTEP ID / TO ID
- (Pending) / TC2-AEP-191
- Category
- SubRegional
- Title
- Hartford City - 3M: Perform relay upgrades to increase 3M CT thermal limit and relay thermal limit. Replace three 477 AAC 19-Str station conductor at 3M station.
- Description
- Hartford City - 3M: Perform relay upgrades to increase 3M CT thermal limit and relay thermal limit. Replace three 477 AAC 19-Str station conductor at 3M station.
- Total Cost
- $400,000
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
|---|---|---|---|
| AG2-550 | 7.4 MW | 22.8% | $91,306 |
| AG2-551 | 6.8 MW | 20.7% | $82,949 |
| AG2-637 | 8.9 MW | 27.4% | $109,616 |
| AH1-308 | 6.9 MW | 21.2% | $84,916 |
| AH1-337 | 2.5 MW | 7.8% | $31,214 |
System Reinforcement
- TO
- AEP
- RTEP ID / TO ID
- (Pending) / TC2-AEP-192
- Category
- SubRegional
- Title
- Bluff Point - Portland: Replace Bluff Point 69 kV 300 MCM CU 37 Str riser, Replace the Portland 69 kV 600 A switch, sag study and mitigation ~7.5 miles of the conductor 556.5 ACSR 26/7
- Description
- Bluff Point - Portland: Replace Bluff Point 69 kV 300 MCM CU 37 Str riser, Replace the Portland 69 kV 600 A switch, sag study and mitigation ~7.5 miles of the conductor 556.5 ACSR 26/7
- Total Cost
- $200,000
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
|---|---|---|---|
| AG2-550 | 24.7 MW | 35.9% | $71,811 |
| AG2-551 | 5.7 MW | 8.4% | $16,715 |
| AG2-637 | 29.8 MW | 43.3% | $86,692 |
| AH1-337 | 8.5 MW | 12.4% | $24,782 |
System Reinforcement: s1508
- TO
- AEP
- RTEP ID / TO ID
- s1508
- Category
- SubRegional
- Title
- s1508 (In service)
- Description
- Rebuild from Structure 1 near Anchor Hocking Station to structure 139A near Price station (~6.5 miles) using 556.5 ACSR 26/7 (SN:102 SE:141 WN:129 WE:159)
- Total Cost
- $0
Note: Although Queue Project AG2-637 may not have cost responsibility for this upgrade, Queue Project AG2-637 may need this upgrade in-service to be deliverable to the PJM system. If Queue Project AG2-637 comes into service prior to completion of the upgrade, Queue Project AG2-637 will need an interim study.
System Reinforcement
- TO
- AEP
- RTEP ID / TO ID
- (Pending) / TC2-AEP-203
- Category
- SubRegional
- Title
- Randolph - Price: Summer emergency rating is 142 MVA.
- Description
- Randolph - Price: Summer emergency rating is 142 MVA.
- Total Cost
- $0
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
|---|---|---|---|
| AG2-550 | 20.4 MW | 33.0% | $0 |
| AG2-551 | 4.7 MW | 7.7% | $0 |
| AG2-637 | 28.5 MW | 46.2% | $0 |
| AH1-337 | 8.1 MW | 13.1% | $0 |
System Reinforcement
- TO
- AEP
- RTEP ID / TO ID
- (Pending) / TC2-AEP-194
- Category
- SubRegional
- Title
- Fulkerson Switch - 3M: Perform relay upgrades to increase 3M CT thermal limit and relay thermal limit. Replace three 477 AAC 19-Str station conductor at 3M station.
- Description
- Fulkerson Switch - 3M: Perform relay upgrades to increase 3M CT thermal limit and relay thermal limit. Replace three 477 AAC 19-Str station conductor at 3M station.
- Total Cost
- $400,000
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
|---|---|---|---|
| AG2-550 | 7.4 MW | 22.8% | $91,306 |
| AG2-551 | 6.8 MW | 20.7% | $82,949 |
| AG2-637 | 8.9 MW | 27.4% | $109,616 |
| AH1-308 | 6.9 MW | 21.2% | $84,916 |
| AH1-337 | 2.5 MW | 7.8% | $31,214 |
Developer Requirements
The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. AEP interconnection requirements can be found here.
To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.
Revenue Metering and SCADA Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.Meteorological Data Reporting Requirement
The solar generation facility shall provide the Transmission Provider with site-specific meteorological data including:Transmission Owner Requirements
- Temperature (degrees Fahrenheit)
- Atmospheric Pressure (hectopascals)
- Irradiance
- Forced outage data
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.
Summer Peak Analysis
The New Service Request AG2-637 was evaluated as a 150.0 MW (90.0 MW Capacity) injection in the AEP area.
AG2-637 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 150.0 MW (150.0 MW under study).
Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.
| Study | Area | Facility Description | Contingency Name | Contingency Type | DC|AC | Final Cycle Loading | Rating (MVA) | Rating Type | MVA to Mitigate | MW Contribution | |
|---|---|---|---|---|---|---|---|---|---|---|---|
| GD2 | AP | 01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line | AP_P2-3_WP-500-DRT10A_SRT-SL | Breaker | AC | 121.47 % | 3792.0 | B | 4606.26 | 14.31 | |
| GD2 | AP | 01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line | AEP_P4_#8975_05KAMMER 765_MM2_SRT-A | Breaker | AC | 121.45 % | 3792.0 | B | 4605.38 | 14.25 | |
| GD2 | AP | 01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line | AP_P2-3_WP-500-DRT7A_SRT-SL | Breaker | AC | 121.43 % | 3792.0 | B | 4604.68 | 14.25 | |
| GD2 | AP | 01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line | AP_P1-2_MP-500-028_SRT-A | Single | AC | 120.65 % | 3792.0 | B | 4574.96 | 9.94 | |
| GD2 | AP | 01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line | AP_P1-3_MP-765-502T_SRT-A | Single | AC | 120.64 % | 3792.0 | B | 4574.63 | 9.94 | |
| GD2 | AP | 01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line | AEP_P4_#8975_05KAMMER 765_MM2_SRT-A | Breaker | AC | 139.97 % | 3792.0 | B | 5307.79 | 13.85 | |
| GD2 | AP | 01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line | AP_P2-3_WP-500-DRT7A_SRT-SL | Breaker | AC | 139.96 % | 3792.0 | B | 5307.1 | 13.85 | |
| GD2 | AP | 01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line | AP_P2-3_WP-500-DRT10A_SRT-SL | Breaker | AC | 139.86 % | 3792.0 | B | 5303.43 | 13.97 | |
| GD2 | AP | 01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line | AP_P1-3_MP-765-502T_SRT-A | Single | AC | 139.36 % | 3792.0 | B | 5284.61 | 9.66 | |
| GD2 | AP | 01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line | AP_P1-2_MP-500-028_SRT-A | Single | AC | 139.32 % | 3792.0 | B | 5282.91 | 9.66 | |
| GD2 | AP | 01KAMMER-01 502 J 500.0 kV Ckt 1 line | AP_P2-3_MP-500-024_SRT-A | Breaker | AC | 132.75 % | 3729.0 | B | 4950.27 | 15.95 | |
| GD2 | AP | 01KAMMER-01 502 J 500.0 kV Ckt 1 line | AP_P2-3_MP-500-025_SRT-A | Breaker | AC | 131.94 % | 3729.0 | B | 4919.93 | 15.91 | |
| GD2 | AP | 01KAMMER-01 502 J 500.0 kV Ckt 1 line | AP_P2-3_MP-500-015_SRT-A | Breaker | AC | 131.63 % | 3729.0 | B | 4908.47 | 15.9 | |
| GD2 | AP | 01KAMMER-01 502 J 500.0 kV Ckt 1 line | AP_P2-3_MP-500-014_SRT-A | Breaker | AC | 131.63 % | 3729.0 | B | 4908.47 | 15.9 | |
| GD2 | AP | 01KAMMER-01 502 J 500.0 kV Ckt 1 line | AP_P1-2_MP-500-007A_SRT-A | Single | AC | 130.62 % | 3729.0 | B | 4870.98 | 11.09 | |
| GD2 | AP | 01KAMMER-01 502 J 500.0 kV Ckt 1 line | AP_P2-3_MP-500-012_SRT-A | Breaker | AC | 130.23 % | 3729.0 | B | 4856.26 | 16.09 | |
| GD2 | AP | 01KAMMER-01 502 J 500.0 kV Ckt 1 line | AP_P1-2_MP-500-008A_SRT-SL | Single | AC | 124.1 % | 3729.0 | B | 4627.6 | 10.69 | |
| GD2 | AEP | 05ALLEN-05RPMONE 345.0 kV Ckt 1 line | AEP_P1-2_#7441_100545_SRT-A | Single | AC | 121.78 % | 1737.0 | B | 2115.3 | 5.47 | |
| GD2 | AEP | 05CHENOWETH-AF1-228 TP 345.0 kV Ckt 1 line | AEP_P4_#XXXX_05BEATTY 345_304W_SRT-A | Breaker | AC | 109.09 % | 1203.0 | B | 1312.32 | 8.49 | |
| GD2 | AEP | 05CHENOWETH-AF1-228 TP 345.0 kV Ckt 1 line | AEP_P4_#16620_05ADKINS 345_A_SRT-A | Breaker | AC | 108.01 % | 1203.0 | B | 1299.36 | 8.54 | |
| GD2 | AEP | 05CHENOWETH-AF1-228 TP 345.0 kV Ckt 1 line | AEP_P4_#16621_05ADKINS 345_A1_SRT-A | Breaker | AC | 108.01 % | 1203.0 | B | 1299.33 | 8.54 | |
| GD2 | AEP | 05CHENOWETH-AF1-228 TP 345.0 kV Ckt 1 line | AEP_P4_#16622_05ADKINS 345_B1_SRT-A | Breaker | AC | 108.01 % | 1203.0 | B | 1299.32 | 8.54 | |
| GD2 | AEP | 05CHENOWETH-AF1-228 TP 345.0 kV Ckt 1 line | AEP_P4_#7445_05MARYSV 765_B_SRT-A | Breaker | AC | 106.27 % | 1203.0 | B | 1278.4 | 8.67 | |
| GD2 | AEP | 05CLOV17_XFL-05CLOVRD 345.0 kV Ckt 17 line | AEP_P1-3_#7421_05CLOVRD 765_14_SRT-A | Single | AC | 106.66 % | 2320.0 | B | 2474.48 | 4.55 | |
| GD2 | AEP/DVP | 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line | AP_P1-3_MP-765-501T_SRT-A | Single | AC | 121.06 % | 3393.4 | B | 4107.97 | 2.8 | |
| GD2 | AEP/DEO&K | 05COLLEGE C-08COLINV 138.0 kV Ckt 1 line | DEOK_P4_1403_MIAMI FORT_SRT-A | Breaker | AC | 114.86 % | 178.0 | B | 204.45 | 12.54 | |
| GD2 | AEP/DEO&K | 05COLLEGE C-08COLINV 138.0 kV Ckt 1 line | AEP_P4_#2812_05TANNER 345_T2_SRT-A | Breaker | AC | 108.71 % | 178.0 | B | 193.5 | 12.55 | |
| GD2 | AEP/DEO&K | 05COLLEGE C-08COLINV 138.0 kV Ckt 1 line | DEOK_P4_1401_MIAMI FORT_SRT-A | Breaker | AC | 108.59 % | 178.0 | B | 193.29 | 12.55 | |
| GD2 | AEP/DEO&K | 05COLLEGE C-08COLINV 138.0 kV Ckt 1 line | DEOK_P_4561TODWOOD14562TODWOOD2_SRT-A | Tower | AC | 105.05 % | 178.0 | B | 186.99 | 12.35 | |
| GD2 | AEP/DEO&K | 05COLLEGE C-08COLINV 138.0 kV Ckt 1 line | DEOK_P4_1301_TERMINAL_SRT-A | Breaker | AC | 102.92 % | 178.0 | B | 183.2 | 12.44 | |
| GD2 | AEP | 05HANGRCK_RJ-05HANG R 765.0 kV Ckt Z1 line | AEP_P1-2_#7441_100545_SRT-A | Single | AC | 106.88 % | 4571.0 | B | 4885.66 | 9.99 | |
| GD2 | AEP | 05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line | AEP_P4_#10527_05BLUFFP 138_E2_SRT-A | Breaker | AC | 123.24 % | 255.0 | B | 314.27 | 100.46 | |
| GD2 | AEP | 05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line | AEP_P4_#10528_05BLUFFP 138_D_SRT-A | Breaker | AC | 106.65 % | 255.0 | B | 271.96 | 100.47 | |
| GD2 | AEP | 05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line | AEP_P4_#14047_05DESOTO 138_F_SRT-A | Breaker | AC | 106.59 % | 255.0 | B | 271.81 | 61.29 | |
| GD2 | AEP | 05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line | AEP_P4_#11242_05BLUFFP 138_D1_SRT-A | Breaker | AC | 106.59 % | 255.0 | B | 271.8 | 100.47 | |
| GD2 | AEP | 05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line | AEP_P4_#15019_05DESOTO 138_F1_SRT-A-1 | Breaker | AC | 106.56 % | 255.0 | B | 271.74 | 61.28 | |
| GD2 | AEP | 05HYATT-05VASSEL 345.0 kV Ckt 1 line | AEP_P4_#9728_05MALIS 138_L1_SRT-A | Breaker | AC | 124.65 % | 1409.0 | B | 1756.35 | 6.78 | |
| GD2 | AEP | 05HYATT-05VASSEL 345.0 kV Ckt 1 line | AEP_P4_#9730_05MALIS 138_P1_SRT-A | Breaker | AC | 124.16 % | 1409.0 | B | 1749.36 | 6.77 | |
| GD2 | AEP | 05HYATT-05VASSEL 345.0 kV Ckt 1 line | AEP_P4_#9729_05MALIS 138_M1_SRT-A | Breaker | AC | 124.05 % | 1409.0 | B | 1747.91 | 6.76 | |
| GD2 | AEP | 05HYATT-05VASSEL 345.0 kV Ckt 1 line | AEP_P2-2_#7222_05MALIS 765_1_SRT-A | Bus | AC | 112.44 % | 1409.0 | B | 1584.27 | 6.74 | |
| GD2 | AEP | 05HYATT-05VASSEL 345.0 kV Ckt 1 line | AEP_P4_#7222_05MALIS 765_D_SRT-A | Breaker | AC | 112.42 % | 1409.0 | B | 1584.05 | 6.74 | |
| GD2 | AEP | 05HYATT-05VASSEL 345.0 kV Ckt 1 line | AEP_P4_#7216_05VASSEL 765_B1_SRT-A | Breaker | AC | 102.74 % | 1409.0 | B | 1447.54 | 6.7 | |
| GD2 | AEP/AP | 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer | AP_P2-3_MP-500-024_SRT-A | Breaker | AC | 134.01 % | 3792.0 | B | 5081.52 | 15.95 | |
| GD2 | AEP/AP | 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer | AP_P2-3_MP-500-025_SRT-A | Breaker | AC | 133.21 % | 3792.0 | B | 5051.2 | 15.91 | |
| GD2 | AEP/AP | 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer | AP_P2-3_MP-500-015_SRT-A | Breaker | AC | 132.9 % | 3792.0 | B | 5039.69 | 15.9 | |
| GD2 | AEP/AP | 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer | AP_P2-3_MP-500-014_SRT-A | Breaker | AC | 132.9 % | 3792.0 | B | 5039.69 | 15.9 | |
| GD2 | AEP/AP | 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer | AP_P1-2_MP-500-007A_SRT-A | Single | AC | 131.92 % | 3792.0 | B | 5002.28 | 11.09 | |
| GD2 | AEP/AP | 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer | AP_P2-3_MP-500-012_SRT-A | Breaker | AC | 131.49 % | 3792.0 | B | 4985.98 | 16.09 | |
| GD2 | AEP/AP | 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer | AP_P1-2_MP-500-008A_SRT-SL | Single | AC | 125.38 % | 3792.0 | B | 4754.33 | 10.69 | |
| GD2 | AEP | 05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line | AEP_P4_#2942_05KAMMER 765_PP_SRT-A | Breaker | AC | 124.95 % | 4142.0 | B | 5175.39 | 18.39 | |
| GD2 | AEP | 05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line | AP_P2-3_MP-500-020_SRT-SL | Breaker | AC | 120.6 % | 4142.0 | B | 4995.09 | 18.65 | |
| GD2 | AEP | 05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line | AP_P2-3_MP-500-021_SRT-SL | Breaker | AC | 120.39 % | 4142.0 | B | 4986.37 | 18.59 | |
| GD2 | AEP | 05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line | AEP_P4_#37_05MOUNTN 765_B1_SRT-A | Breaker | AC | 120.3 % | 4142.0 | B | 4982.82 | 18.56 | |
| GD2 | AEP | 05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line | AP_P1-3_MP-765-501T_SRT-A | Single | AC | 118.76 % | 4142.0 | B | 4919.18 | 12.95 | |
| GD2 | AEP | 05MADDOX-05E LIMA 345.0 kV Ckt 1 line | AEP_P1-2_#7441_100545_SRT-A | Single | AC | 120.12 % | 2246.0 | B | 2697.98 | 5.16 | |
| GD2 | AEP | 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line | AEP_P1-2_#709_546_SRT-A | Single | AC | 145.65 % | 4142.0 | B | 6032.93 | 11.66 | |
| GD2 | AEP | 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line | AEP_P1-2_#6463_16757_SRT-A | Single | AC | 140.14 % | 4142.0 | B | 5804.66 | 10.94 | |
| GD2 | AEP | 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line | Base Case | Single | AC | 130.5 % | 4047.0 | A | 5281.19 | 9.93 | |
| GD2 | AEP | 05MOUNTN-05BELMON 765.0 kV Ckt 1 line | AEP_P1-2_#17217_SRT-A | Single | AC | 115.67 % | 5523.0 | B | 6388.32 | 14.1 | |
| GD2 | AEP | 05MOUNTN-05BELMON 765.0 kV Ckt 1 line | Base Case | Single | AC | 108.86 % | 4558.0 | A | 4961.85 | 9.66 | |
| GD2 | AEP | 05MOUNTN-05BELMON 765.0 kV Ckt 1 line | AEP_P1-2_#7422_16_SRT-A | Single | AC | 106.56 % | 5523.0 | B | 5885.34 | 11.67 | |
| GD2 | AEP | 05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line | AEP_P1-2_#7441_100545_SRT-A | Single | AC | 132.35 % | 1868.0 | B | 2472.27 | 5.24 | |
| GD2 | AEP | 05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer | AEP_P1-2_#7442_200545_SRT-A | Single | AC | 111.07 % | 3097.0 | B | 3439.74 | 10.39 | |
| GD2 | AEP | 05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line | AEP_P1-2_#709_546_SRT-A | Single | AC | 109.05 % | 5523.0 | B | 6022.77 | 11.66 | |
| GD2 | AEP | 05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line | AEP_P1-2_#6463_16757_SRT-A | Single | AC | 104.68 % | 5523.0 | B | 5781.3 | 10.94 | |
| GD2 | AEP/DEO&K | 05TANNER-08M.FORT 345.0 kV Ckt 1 line | AEP_P2-2_#9456_06DEARB1 345_1_SRT-A | Bus | AC | 128.08 % | 2317.0 | B | 2967.71 | 17.3 | |
| GD2 | AEP/DEO&K | 05TANNER-08M.FORT 345.0 kV Ckt 1 line | AEP_P4_#9456_06DEARB1 345_DC_SRT-A | Breaker | AC | 128.08 % | 2317.0 | B | 2967.55 | 17.3 | |
| GD2 | AEP/DEO&K | 05TANNER-08M.FORT 345.0 kV Ckt 1 line | AEP_P4_#7445_05MARYSV 765_B_SRT-A | Breaker | AC | 127.06 % | 2317.0 | B | 2944.05 | 8.18 | |
| GD2 | AEP/DEO&K | 05TANNER-08M.FORT 345.0 kV Ckt 1 line | AEP_P4_#7441_05SORENS 765_J1_SRT-A | Breaker | AC | 124.93 % | 2317.0 | B | 2894.55 | 8.28 | |
| GD2 | AEP/DEO&K | 05TANNER-08M.FORT 345.0 kV Ckt 1 line | AEP_P4_#7446_05MARYSV 765_B2_SRT-A | Breaker | AC | 124.59 % | 2317.0 | B | 2886.84 | 8.16 | |
| GD2 | AEP/DEO&K | 05TANNER-08M.FORT 345.0 kV Ckt 1 line | AEP_P1-2_#7441_100545_SRT-A | Single | AC | 118.23 % | 2317.0 | B | 2739.4 | 5.78 | |
| GD2 | AEP/DEO&K | 05TANNER-08M.FORT 345.0 kV Ckt 1 line | DEOK_P_4519BUFFCLIFTYPIERCEDEAR1OVEC_SRT-A | Tower | AC | 115.91 % | 2317.0 | B | 2685.57 | 10.11 | |
| GD2 | AEP/DEO&K | 05TANNER-08M.FORT 345.0 kV Ckt 1 line | AEP_P7-1_#485___SRT-A | Tower | AC | 115.9 % | 2317.0 | B | 2685.44 | 10.11 | |
| GD2 | AEP/DEO&K | 05TANNER-08M.FORT 345.0 kV Ckt 1 line | DEOK_P4_1579_EASTBEND_SRT-A | Breaker | AC | 110.77 % | 2317.0 | B | 2566.43 | 8.3 | |
| GD2 | AEP/DEO&K | 05TANNER-08M.FORT 345.0 kV Ckt 1 line | DEOK_P1_EAST BEND-TERMINAL 4516_SRT-A | Single | AC | 100.05 % | 2317.0 | B | 2318.24 | 5.79 | |
| GD2 | OVEC | 06DEARB1-06PIERCE 345.0 kV Ckt 1 line | DEOK_P4_1403_MIAMI FORT_SRT-A | Breaker | AC | 104.32 % | 942.0 | B | 982.66 | 8.11 | |
| GD2 | OVEC | 06DEARB1-06PIERCE 345.0 kV Ckt 1 line | DEOK_P4_1401_MIAMI FORT_SRT-A | Breaker | AC | 103.8 % | 942.0 | B | 977.75 | 8.12 | |
| GD2 | OVEC | 06DEARB1-06PIERCE 345.0 kV Ckt 1 line | AEP_P4_#2812_05TANNER 345_T2_SRT-A | Breaker | AC | 103.75 % | 942.0 | B | 977.33 | 8.12 | |
| GD2 | AEP/OVEC | 06KYGER-05SPORN 345.0 kV Ckt 1 line | AEP_P4_#7446_05MARYSV 765_B2_SRT-A | Breaker | AC | 156.15 % | 1540.0 | B | 2404.66 | 11.09 | |
| GD2 | AEP/OVEC | 06KYGER-05SPORN 345.0 kV Ckt 1 line | AEP_P4_#7441_05SORENS 765_J1_SRT-A | Breaker | AC | 154.73 % | 1540.0 | B | 2382.87 | 10.74 | |
| GD2 | AEP/OVEC | 06KYGER-05SPORN 345.0 kV Ckt 1 line | AEP_P4_#1558_05BAKER 765_Q_SRT-A | Breaker | AC | 153.9 % | 1540.0 | B | 2370.07 | 10.7 | |
| GD2 | AEP/OVEC | 06KYGER-05SPORN 345.0 kV Ckt 1 line | AEP_P4_#309_05HANG R 765_B2_SRT-A | Breaker | AC | 153.46 % | 1540.0 | B | 2363.36 | 10.69 | |
| GD2 | AEP/OVEC | 06KYGER-05SPORN 345.0 kV Ckt 1 line | AEP_P4_#1560_05BAKER 765_Q2_SRT-A | Breaker | AC | 153.34 % | 1540.0 | B | 2361.46 | 10.68 | |
| GD2 | AEP/OVEC | 06KYGER-05SPORN 345.0 kV Ckt 1 line | AEP_P1-2_#7441_100545_SRT-A | Single | AC | 145.41 % | 1540.0 | B | 2239.27 | 7.5 | |
| GD2 | AEP/OVEC | 06KYGER-05SPORN 345.0 kV Ckt 1 line | AEP_P1-2_#309_15_SRT-A | Single | AC | 141.78 % | 1540.0 | B | 2183.34 | 7.46 | |
| GD2 | AEP/OVEC | 06KYGER-05SPORN 345.0 kV Ckt 1 line | AEP_P2-2_#6763_05BIERSR 345_2_SRT-A | Bus | AC | 135.59 % | 1540.0 | B | 2088.16 | 9.82 | |
| GD2 | AEP/OVEC | 06KYGER-05SPORN 345.0 kV Ckt 1 line | 34569 34598 34524_SRT-A | Tower | AC | 132.73 % | 1540.0 | B | 2044.01 | 9.78 | |
| GD2 | AEP/OVEC | 06KYGER-05SPORN 345.0 kV Ckt 1 line | 34524 34598_SRT-A | Tower | AC | 132.58 % | 1540.0 | B | 2041.73 | 9.74 | |
| GD2 | AEP/OVEC | 06KYGER-05SPORN 345.0 kV Ckt 1 line | Base Case | Single | AC | 131.72 % | 1189.0 | A | 1566.09 | 6.78 | |
| GD2 | AEP/OVEC | 06KYGER-05SPORN 345.0 kV Ckt 1 line | AP_P2-2_WP-500-DRT14_SRT-SL | Bus | AC | 130.87 % | 1540.0 | B | 2015.35 | 9.7 | |
| GD2 | AEP/OVEC | 06PIERCE-05MARQUI 345.0 kV Ckt 1 line | AEP_P4_#6189_05HANG R 765_D1_SRT-A | Breaker | AC | 112.42 % | 1540.0 | B | 1731.23 | 9.94 | |
| GD2 | AEP/OVEC | 06PIERCE-05MARQUI 345.0 kV Ckt 1 line | AEP_P4_#709_05HANG R 765_D2_SRT-A | Breaker | AC | 108.09 % | 1540.0 | B | 1664.56 | 10.01 | |
| GD2 | AEP/OVEC | 06PIERCE-05MARQUI 345.0 kV Ckt 1 line | AEP_P1-2_#709_546_SRT-A | Single | AC | 101.36 % | 1540.0 | B | 1561.02 | 6.98 | |
| GD2 | DEO&K | 08MCGFY1-08LOCST1 69.0 kV Ckt 1 line | DEOK_P_CIRCUIT3281&13803_SRT-A | Tower | AC | 129.22 % | 54.0 | B | 69.78 | 4.45 | |
| GD2 | DEO&K | 08MCGFY1-08LOCST1 69.0 kV Ckt 1 line | DEOK_P4_808_TRENTON_SRT-A | Breaker | AC | 111.08 % | 54.0 | B | 59.98 | 3.81 | |
| GD2 | DEO&K | 08MCGFY1-08LOCST1 69.0 kV Ckt 1 line | DEOK_P4_806_TRENTON_SRT-A | Breaker | AC | 110.59 % | 54.0 | B | 59.72 | 3.81 | |
| GD2 | DEO&K | 08MCGFY1-08LOCST1 69.0 kV Ckt 1 line | DEOK_P2.2_TRENTON1_SRT-A | Bus | AC | 110.59 % | 54.0 | B | 59.72 | 3.81 | |
| GD2 | DEO&K | 08MCGFY1-08LOCST1 69.0 kV Ckt 1 line | DEOK_P2.2_HUSTON_SRT-A | Bus | AC | 102.69 % | 54.0 | B | 55.45 | 3.84 | |
| GD2 | AEP | AE2-089 TAP-05ADAM 138.0 kV Ckt 1 line | AEP_P4_#14047_05DESOTO 138_F_SRT-A | Breaker | AC | 121.36 % | 205.0 | B | 248.78 | 20.46 | |
| GD2 | AEP | AE2-089 TAP-05ADAM 138.0 kV Ckt 1 line | AEP_P4_#15019_05DESOTO 138_F1_SRT-A-1 | Breaker | AC | 121.32 % | 205.0 | B | 248.71 | 20.46 | |
| GD2 | AEP | AE2-089 TAP-05ADAM 138.0 kV Ckt 1 line | AEP_P4_#15023_05JAY 138_E_SRT-A | Breaker | AC | 110.69 % | 205.0 | B | 226.91 | 21.07 | |
| GD2 | AEP | AE2-089 TAP-05ADAM 138.0 kV Ckt 1 line | AEP_P4_#15176_05JAY 138_E2_SRT-A | Breaker | AC | 108.84 % | 205.0 | B | 223.12 | 20.81 | |
| GD2 | AEP | AE2-089 TAP-05ADAM 138.0 kV Ckt 1 line | AEP_P7-1_#11019___SRT-A-2 | Tower | AC | 104.07 % | 205.0 | B | 213.35 | 11.46 | |
| GD2 | AEP | AE2-089 TAP-05ADAM 138.0 kV Ckt 1 line | AEP_P7-1_#11019___SRT-A-1 | Tower | AC | 104.07 % | 205.0 | B | 213.34 | 11.46 | |
| GD2 | AEP | AE2-089 TAP-05ADAM 138.0 kV Ckt 1 line | AEP_P4_#17625_05HAYES 138_B_SRT-A-1 | Breaker | AC | 103.86 % | 205.0 | B | 212.92 | 16.64 | |
| GD2 | AEP | AE2-089 TAP-05ADAM 138.0 kV Ckt 1 line | AEP_P2-2_#13951_05N PORTLN 69.0_2_SRT-A | Bus | AC | 102.02 % | 205.0 | B | 209.13 | 12.48 | |
| GD2 | AEP | AF1-118 TP-05SORENS 345.0 kV Ckt 2 line | AEP_P4_#4817_05SORENS 345_B2_SRT-A | Breaker | AC | 107.66 % | 971.0 | B | 1045.34 | 14.32 | |
| GD2 | AEP | AF1-118 TP-05SORENS 345.0 kV Ckt 2 line | AEP_P4_#7449_05SORENS 345_B_SRT-A | Breaker | AC | 106.32 % | 971.0 | B | 1032.36 | 14.11 | |
| GD2 | AEP | AF1-118 TP-05SORENS 345.0 kV Ckt 2 line | AEP_P4_#2896_05KEYSTN 345_A_SRT-A | Breaker | AC | 101.91 % | 971.0 | B | 989.54 | 14.35 | |
| GD2 | AEP | AF1-228 TP-05BEATTY 345.0 kV Ckt 1 line | AEP_P4_#XXXX_05BEATTY 345_304W_SRT-A | Breaker | AC | 118.45 % | 1203.0 | B | 1424.98 | 8.41 | |
| GD2 | AEP | AF1-228 TP-05BEATTY 345.0 kV Ckt 1 line | AEP_P4_#16622_05ADKINS 345_B1_SRT-A | Breaker | AC | 116.03 % | 1203.0 | B | 1395.78 | 8.46 | |
| GD2 | AEP | AF1-228 TP-05BEATTY 345.0 kV Ckt 1 line | AEP_P4_#16620_05ADKINS 345_A_SRT-A | Breaker | AC | 115.99 % | 1203.0 | B | 1395.31 | 8.46 | |
| GD2 | AEP | AF1-228 TP-05BEATTY 345.0 kV Ckt 1 line | AEP_P4_#16621_05ADKINS 345_A1_SRT-A | Breaker | AC | 115.99 % | 1203.0 | B | 1395.3 | 8.46 | |
| GD2 | AEP | AF1-228 TP-05BEATTY 345.0 kV Ckt 1 line | AEP_P4_#7445_05MARYSV 765_B_SRT-A | Breaker | AC | 115.08 % | 1203.0 | B | 1384.41 | 8.6 | |
| GD2 | AEP | AF1-228 TP-05BEATTY 345.0 kV Ckt 1 line | AEP_P7-1_#11019___SRT-A-2 | Tower | AC | 103.58 % | 1203.0 | B | 1246.02 | 8.78 | |
| GD2 | AEP | AF1-228 TP-05BEATTY 345.0 kV Ckt 1 line | AEP_P1-2_#762_8072_SRT-A | Single | AC | 102.19 % | 1203.0 | B | 1229.31 | 5.9 | |
| GD2 | AEP | AF1-228 TP-05BEATTY 345.0 kV Ckt 1 line | AEP_P7-1_#11019___SRT-A-1 | Tower | AC | 102.16 % | 1203.0 | B | 1229.04 | 8.78 | |
| GD2 | AEP | AF1-228 TP-05BEATTY 345.0 kV Ckt 1 line | AEP_P2-2_#7222_05MALIS 765_1_SRT-A | Bus | AC | 101.86 % | 1203.0 | B | 1225.43 | 8.17 | |
| GD2 | AEP | AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line | AEP_P1-2_#7441_100545_SRT-A | Single | AC | 138.82 % | 1868.0 | B | 2593.18 | 5.24 | |
| GD2 | AEP | AH1-337 TP-05HODGIN_BP 138.0 kV Ckt 1 line | AEP_P4_#10527_05BLUFFP 138_E2_SRT-A | Breaker | AC | 123.32 % | 255.0 | B | 314.46 | 100.46 | |
| GD2 | AEP | AH1-337 TP-05HODGIN_BP 138.0 kV Ckt 1 line | AEP_P4_#10528_05BLUFFP 138_D_SRT-A | Breaker | AC | 106.68 % | 255.0 | B | 272.02 | 100.47 | |
| GD2 | AEP | AH1-337 TP-05HODGIN_BP 138.0 kV Ckt 1 line | AEP_P4_#14047_05DESOTO 138_F_SRT-A | Breaker | AC | 106.64 % | 255.0 | B | 271.94 | 61.29 | |
| GD2 | AEP | AH1-337 TP-05HODGIN_BP 138.0 kV Ckt 1 line | AEP_P4_#15019_05DESOTO 138_F1_SRT-A-1 | Breaker | AC | 106.62 % | 255.0 | B | 271.87 | 61.28 | |
| GD2 | AEP | AH1-337 TP-05HODGIN_BP 138.0 kV Ckt 1 line | AEP_P4_#11242_05BLUFFP 138_D1_SRT-A | Breaker | AC | 106.61 % | 255.0 | B | 271.86 | 100.47 |
Winter Peak Analysis
The New Service Request AG2-637 was evaluated as a 150.0 MW (90.0 MW Capacity) injection in the AEP area.
AG2-637 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 150.0 MW (150.0 MW under study).
Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.
| Study | Area | Facility Description | Contingency Name | Contingency Type | DC|AC | Final Cycle Loading | Rating (MVA) | Rating Type | MVA to Mitigate | MW Contribution | |
|---|---|---|---|---|---|---|---|---|---|---|---|
| GD2 | AEP/DEO&K | 05TANNER-08M.FORT 345.0 kV Ckt 1 line | AEP_P4_#7445_05MARYSV 765_B_SRT-A | Breaker | AC | 110.3 % | 2317.0 | B | 2555.59 | 0.47 | |
| GD2 | AEP/DEO&K | 05TANNER-08M.FORT 345.0 kV Ckt 1 line | AEP_P1-2_#7441_100545_SRT-A | Single | AC | 109.35 % | 2317.0 | B | 2533.64 | 0.48 | |
| GD2 | AEP/DEO&K | 05TANNER-08M.FORT 345.0 kV Ckt 1 line | AEP_P4_#7441_05SORENS 765_J1_SRT-A | Breaker | AC | 108.51 % | 2317.0 | B | 2514.08 | 0.48 | |
| GD2 | AEP/DEO&K | 05TANNER-08M.FORT 345.0 kV Ckt 1 line | AEP_P4_#7446_05MARYSV 765_B2_SRT-A | Breaker | AC | 108.5 % | 2317.0 | B | 2514.0 | 0.47 | |
| GD2 | AEP/DEO&K | 05TANNER-08M.FORT 345.0 kV Ckt 1 line | AEP_P4_#9456_06DEARB1 345_DC_SRT-A | Breaker | AC | 107.9 % | 2317.0 | B | 2499.97 | 1.0 | |
| GD2 | AEP/DEO&K | 05TANNER-08M.FORT 345.0 kV Ckt 1 line | AEP_P2-2_#9456_06DEARB1 345_1_SRT-A | Bus | AC | 107.9 % | 2317.0 | B | 2499.96 | 1.0 | |
| GD2 | AEP/DEO&K | 05TANNER-08M.FORT 345.0 kV Ckt 1 line | DEOK_P_4519BUFFCLIFTYPIERCEDEAR1OVEC_SRT-A | Tower | AC | 105.96 % | 2317.0 | B | 2455.15 | 0.58 | |
| GD2 | AEP/DEO&K | 05TANNER-08M.FORT 345.0 kV Ckt 1 line | AEP_P7-1_#485___SRT-A | Tower | AC | 105.96 % | 2317.0 | B | 2455.01 | 0.58 |
Light Load Analysis
The New Service Request AG2-637 was evaluated as a 150.0 MW injection
AG2-637 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 150.0 MW (150.0 MW under study).
Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.
| Study | Area | Facility Description | Contingency Name | Contingency Type | DC|AC | Final Cycle Loading | Rating (MVA) | Rating Type | MVA to Mitigate | MW Contribution | |
|---|---|---|---|---|---|---|---|---|---|---|---|
| GD2 | AEP | 05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line | AEP_P4_#14047_05DESOTO 138_F_SRT-A | Breaker | AC | 134.87 % | 255.0 | B | 343.92 | 41.5 | |
| GD2 | AEP | 05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line | AEP_P1-2_#15020_SRT-A-1 | Single | AC | 134.83 % | 255.0 | B | 343.81 | 41.5 | |
| GD2 | AEP | 05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line | AEP_P4_#15019_05DESOTO 138_F1_SRT-A | Breaker | AC | 134.83 % | 255.0 | B | 343.81 | 41.5 | |
| GD2 | AEP | 05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line | AEP_P1-2_#15020_SRT-A-2 | Single | AC | 130.16 % | 255.0 | B | 331.9 | 41.5 | |
| GD2 | AEP | 05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line | AEP_P4_#15023_05JAY 138_E_SRT-A | Breaker | AC | 128.18 % | 255.0 | B | 326.87 | 41.71 | |
| GD2 | AEP | 05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line | AEP_P4_#15176_05JAY 138_E2_SRT-A | Breaker | AC | 127.58 % | 255.0 | B | 325.34 | 41.62 | |
| GD2 | AEP | 05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line | AEP_P4_#10527_05BLUFFP 138_E2_SRT-A | Breaker | AC | 117.44 % | 255.0 | B | 299.47 | 64.32 | |
| GD2 | AEP | 05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line | AEP_P7-1_#11036___SRT-A | Tower | AC | 113.5 % | 255.0 | B | 289.42 | 34.42 | |
| GD2 | AEP | 05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line | Base Case | Single | AC | 112.68 % | 219.0 | A | 246.77 | 35.28 | |
| GD2 | AEP | 05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line | AEP_P7-1_#11035___SRT-A | Tower | AC | 105.43 % | 255.0 | B | 268.84 | 34.91 | |
| GD2 | AEP | 05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line | AEP_P2-2_#15669_05RANDOLPH 69.0_1_SRT-A | Bus | AC | 103.94 % | 255.0 | B | 265.04 | 39.11 | |
| GD2 | AEP | 05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line | AEP_P2-2_#15671_05ANCHORHO 69.0_2_SRT-A | Bus | AC | 103.75 % | 255.0 | B | 264.56 | 39.11 | |
| GD2 | DEO&K | 08MCGFY1-08LOCST1 69.0 kV Ckt 1 line | DEOK_P_CIRCUIT3281&13803_SRT-A | Tower | AC | 115.47 % | 54.0 | B | 62.35 | 2.89 | |
| GD2 | AEP | AE2-089 TAP-05ADAM 138.0 kV Ckt 1 line | AEP_P4_#14047_05DESOTO 138_F_SRT-A | Breaker | AC | 121.86 % | 205.0 | B | 249.81 | 16.23 | |
| GD2 | AEP | AE2-089 TAP-05ADAM 138.0 kV Ckt 1 line | AEP_P4_#15019_05DESOTO 138_F1_SRT-A | Breaker | AC | 121.82 % | 205.0 | B | 249.73 | 16.22 | |
| GD2 | AEP | AE2-089 TAP-05ADAM 138.0 kV Ckt 1 line | AEP_P1-2_#15020_SRT-A-1 | Single | AC | 121.81 % | 205.0 | B | 249.72 | 16.22 | |
| GD2 | AEP | AE2-089 TAP-05ADAM 138.0 kV Ckt 1 line | AEP_P1-2_#15020_SRT-A-2 | Single | AC | 113.55 % | 205.0 | B | 232.78 | 16.22 | |
| GD2 | AEP | AE2-089 TAP-05ADAM 138.0 kV Ckt 1 line | AEP_P4_#15023_05JAY 138_E_SRT-A | Breaker | AC | 112.49 % | 205.0 | B | 230.61 | 16.87 | |
| GD2 | AEP | AE2-089 TAP-05ADAM 138.0 kV Ckt 1 line | AEP_P4_#15176_05JAY 138_E2_SRT-A | Breaker | AC | 110.25 % | 205.0 | B | 226.02 | 16.59 | |
| GD2 | AEP | AF1-268 TP-05DESOTO 138.0 kV Ckt 1 line | Base Case | Single | AC | 111.33 % | 323.0 | A | 359.58 | 23.7 | |
| GD2 | AEP | AF1-268 TP-05DESOTO 138.0 kV Ckt 1 line | AEP_P1-2_#17621_SRT-A-3 | Single | AC | 108.94 % | 449.0 | B | 489.15 | 42.26 | |
| GD2 | AEP | AF1-268 TP-05DESOTO 138.0 kV Ckt 1 line | AEP_P4_#17624_05HAYES 138_A_SRT-A | Breaker | AC | 108.93 % | 449.0 | B | 489.09 | 42.25 | |
| GD2 | AEP | AF1-268 TP-05DESOTO 138.0 kV Ckt 1 line | AEP_P4_#17625_05HAYES 138_B_SRT-A | Breaker | AC | 108.74 % | 449.0 | B | 488.26 | 42.24 | |
| GD2 | AEP | AF1-268 TP-05DESOTO 138.0 kV Ckt 1 line | AEP_P1-2_#17621_SRT-A-2 | Single | AC | 106.06 % | 449.0 | B | 476.2 | 42.26 | |
| GD2 | AEP | AH1-337 TP-05HODGIN_BP 138.0 kV Ckt 1 line | AEP_P4_#14047_05DESOTO 138_F_SRT-A | Breaker | AC | 134.99 % | 255.0 | B | 344.22 | 41.5 | |
| GD2 | AEP | AH1-337 TP-05HODGIN_BP 138.0 kV Ckt 1 line | AEP_P4_#15019_05DESOTO 138_F1_SRT-A | Breaker | AC | 134.95 % | 255.0 | B | 344.12 | 41.5 | |
| GD2 | AEP | AH1-337 TP-05HODGIN_BP 138.0 kV Ckt 1 line | AEP_P1-2_#15020_SRT-A-1 | Single | AC | 134.94 % | 255.0 | B | 344.11 | 41.5 | |
| GD2 | AEP | AH1-337 TP-05HODGIN_BP 138.0 kV Ckt 1 line | AEP_P1-2_#15020_SRT-A-2 | Single | AC | 130.28 % | 255.0 | B | 332.21 | 41.5 | |
| GD2 | AEP | AH1-337 TP-05HODGIN_BP 138.0 kV Ckt 1 line | AEP_P4_#15023_05JAY 138_E_SRT-A | Breaker | AC | 128.3 % | 255.0 | B | 327.17 | 41.71 | |
| GD2 | AEP | AH1-337 TP-05HODGIN_BP 138.0 kV Ckt 1 line | AEP_P4_#15176_05JAY 138_E2_SRT-A | Breaker | AC | 127.7 % | 255.0 | B | 325.64 | 41.62 | |
| GD2 | AEP | AH1-337 TP-05HODGIN_BP 138.0 kV Ckt 1 line | AEP_P4_#10527_05BLUFFP 138_E2_SRT-A | Breaker | AC | 117.44 % | 255.0 | B | 299.47 | 64.32 | |
| GD2 | AEP | AH1-337 TP-05HODGIN_BP 138.0 kV Ckt 1 line | AEP_P7-1_#11036___SRT-A | Tower | AC | 113.61 % | 255.0 | B | 289.71 | 34.42 | |
| GD2 | AEP | AH1-337 TP-05HODGIN_BP 138.0 kV Ckt 1 line | Base Case | Single | AC | 112.8 % | 219.0 | A | 247.04 | 35.28 | |
| GD2 | AEP | AH1-337 TP-05HODGIN_BP 138.0 kV Ckt 1 line | AEP_P7-1_#11035___SRT-A | Tower | AC | 105.53 % | 255.0 | B | 269.11 | 34.91 | |
| GD2 | AEP | AH1-337 TP-05HODGIN_BP 138.0 kV Ckt 1 line | AEP_P2-2_#15669_05RANDOLPH 69.0_1_SRT-A | Bus | AC | 104.05 % | 255.0 | B | 265.33 | 39.11 | |
| GD2 | AEP | AH1-337 TP-05HODGIN_BP 138.0 kV Ckt 1 line | AEP_P2-2_#15671_05ANCHORHO 69.0_2_SRT-A | Bus | AC | 103.86 % | 255.0 | B | 264.85 | 39.11 |
Short Circuit Analysis
Short Circuit analysis is not performed as part of the Phase I System Impact Study. Short Circuit analysis will commence in the Phase II System Impact Study.
Stability Analysis
Stability analysis is not performed as part of the Phase I System Impact Study. Stability analysis will commence in the Phase II System Impact Study.
Reactive Power Analysis
Reactive Power analysis is not performed as part of the Phase I System Impact Study. Reactive Power analysis will commence in the Phase II System Impact Study.
Steady-State Voltage Analysis
Steady State Voltage Analysis is Not Required.
New Service Request Dependencies
The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.
| New Service Requests Dependencies | ||
|---|---|---|
| Project ID | Project Name | Status |
| AA1-018 | Powerton-Goodings Grove | In Service |
| AA1-038 | Lexington-Low Moor 230kV | Under Construction |
| AA1-095 | Halfway-Marlowe 34.5kV | In Service |
| AA2-184 | Atlantic-Red Bank 34kV | In Service |
| AB1-001 | Absecon 12 kV | In Service |
| AB1-006 | Meadow Lake 345kV | In Service |
| AB1-027 | Old Church 34.5 KV | In Service |
| AB1-087 | Sullivan 345kV #1 | Under Construction |
| AB1-088 | Sullivan 345kV #2 | Engineering & Procurement |
| AB1-096 | Carroll-Mt. Airy 34.5kV | In Service |
| AB1-124 | Carroll-Monocacy 34.5kV | Partially in Service - Under Construction |
| AB1-125 | Carroll-Monocacy 34.5kV | In Service |
| AB1-127 | St. Thomas-Guilford 34.5kV | In Service |
| AB1-128 | St. Thomas-Mercersburg 34.5kV | In Service |
| AB1-138 | Navy 34.5kV | In Service |
| AB1-139 | Metuchen 26kV | In Service |
| AB1-141 | Church-Wye Mills 138 kV I | In Service |
| AB1-142 | Church-Wye Mills 138 kV II | In Service |
| AB1-150 | Grassy Falls 138kV | In Service |
| AB1-176 | Price 25kV II | Engineering & Procurement |
| AB1-180 | Pine View 12kV | In Service |
| AB2-026 | Powhatan 34.5kV | In Service |
| AB2-029 | Remington 34.5kV | In Service |
| AB2-032 | Church-Wye Mills 138 kV | In Service |
| AB2-037 | Keeney-Steele 230kV | Under Construction |
| AB2-045 | Buckingham 34.5kV | In Service |
| AB2-049 | Gloucester Township 12kV | In Service |
| AB2-067 | Kammer-Vassell 765kV | In Service |
| AB2-070 | Mt. Pulaski-Brokaw | In Service |
| AB2-093 | Ormet 138kV | In Service |
| AB2-133 | Chestertown 69kV | Under Construction |
| AB2-135 | Church-Kent 69kV | In Service |
| AB2-136 | Cambridge-West Cambridge 69kV | Under Construction |
| AB2-153 | Church-Wye Mills 138 kV | In Service |
| AB2-157 | Prince George's County 12kV | In Service |
| AB2-158 | Louisa-South Anna 230kV | In Service |
| AB2-170 | East Lima-Marysville 345kV | In Service |
| AB2-179 | Townsend 138kV | In Service |
| AC1-001 | Delano 138kV | In Service |
| AC1-010 | Gloucester 26kV | Under Construction |
| AC1-017 | Levittown 13 kV | In Service |
| AC1-030 | Cinnaminson 13kV | In Service |
| AC1-033 | Kewanee 138 kV | In Service |
| AC1-042 | Altavista-Mt. Airy 69kV | In Service |
| AC1-044 | Kammer-Vassell 765kV | In Service |
| AC1-053 | Lanesville-Brokaw | Partially in Service - Under Construction |
| AC1-068 | Atlanta 69kV I | In Service |
| AC1-069 | Atlanta 69kV II | In Service |
| AC1-074 | Jacksonville-Renaker 138kV I | In Service |
| AC1-075 | Perth-Hickory Grove 115kV | In Service |
| AC1-076 | Locust Grove-Paytes 115kV | In Service |
| AC1-078 | Beatty-London 138kV | In Service |
| AC1-082 | Ravenswood-Hemlock 69kV | Under Construction |
| AC1-085 | Stuart-Clinton 345kV | In Service |
| AC1-089 | Hillsboro-Wildcat 138kV | In Service |
| AC1-091 | Cedar Creek 138kV I | Engineering & Procurement |
| AC1-092 | Cedar Creek 138kV II | Engineering & Procurement |
| AC1-093 | Cedar Creek 138kV III | Engineering & Procurement |
| AC1-094 | Cedar Creek 138kV IV | Engineering & Procurement |
| AC1-101 | Johns Creek-Excel 138kV I | Suspended |
| AC1-102 | Johns Creek-Excel 138kV II | Suspended |
| AC1-111 | Aurora 138kV | In Service |
| AC1-118 | Westmoreland 34.5kV | In Service |
| AC1-120 | Mitchell-Mountain Run 115kV | Engineering & Procurement |
| AC1-121 | Mitchell-Mountain Run 115kV | Engineering & Procurement |
| AC1-122 | Smith Mountain-Candler's Mountain 138kV | In Service |
| AC1-141 | Cook-East Elkhart 345kV | In Service |
| AC1-145 | Gretna DP 69 kV | In Service |
| AC1-158 | Spotsylvania 500kV | In Service |
| AC1-165 | Atlanta 69kV III | In Service |
| AC1-166 | Atlanta 69kV IV | In Service |
| AC1-167 | Mark Center 69kV | Under Construction |
| AC1-168 | Kewanee-Streator | Suspended |
| AC1-174 | Losantville 345kV | In Service |
| AC1-175 | Losantville 345kV | In Service |
| AC1-188 | Rio-Lick 138kV | Engineering & Procurement |
| AC1-191 | Elmont 115kV | Engineering & Procurement |
| AC1-194 | Elk 138kV | Active |
| AC1-214 | Crescent Ridge | In Service |
| AC2-023 | Hebron 69kV | Engineering & Procurement |
| AC2-029 | Circleville 138kV | Suspended |
| AC2-044 | Maddox Creek 345kV | Suspended |
| AC2-059 | Biers Run-Circleville 138kV | In Service |
| AC2-060 | Buckskin 69kV | In Service |
| AC2-061 | Hillsboro-Clinton 138kV | In Service |
| AC2-067 | Camden-Crystal I 69kV | Engineering & Procurement |
| AC2-068 | Camden-Crystal II 69kV | Engineering & Procurement |
| AC2-075 | Jacksonville-Renaker 138 kV | In Service |
| AC2-088 | S. Bethel-Brown 69kV | In Service |
| AC2-090 | Losantville 345kV | In Service |
| AC2-111 | College Corner 138kV | Engineering & Procurement |
| AC2-120 | Ripley 69kV | In Service |
| AC2-136 | East Hagerstown 12kV | Under Construction |
| AC2-137 | Elko 34.5kV | In Service |
| AC2-138 | Northern Neck 34.5kV | In Service |
| AC2-157 | Sullivan 345 kV | Under Construction |
| AC2-165 | Bremo-Powhatan 230kV | Suspended |
| AC2-168 | Clinton 23kV | In Service |
| AC2-176 | Jay 138 kV | In Service |
| AC2-186 | Harrington 25kV | Under Construction |
| AC2-187 | Harrington 69kV | Under Construction |
| AC2-188 | Harrington 69 kV | Under Construction |
| AC2-195 | Galion-Roberts South 138 kV | Under Construction |
| AD1-013 | Twombly Road 138kV | Engineering & Procurement |
| AD1-017 | Smith Mountain-Bearskin 138 kV | In Service |
| AD1-020 | Hunterstown-Lincoln 115 kV | In Service |
| AD1-060 | Mercersburg-Milnor 34.5 kV | In Service |
| AD1-061 | McConnelsburg-Mercersburg 34 kV | In Service |
| AD1-063 | Harmony Village 34.5 kV | In Service |
| AD1-100 | Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kV | Under Construction |
| AD1-101 | Continental 69 kV | In Service |
| AD1-105 | Kings Dominion DP 115 kV | Under Construction |
| AD1-106 | North Waldo-Wild Creek 138 kV | Suspended |
| AD1-115 | Mountain Run-Mitchell 115 kV | Engineering & Procurement |
| AD1-119 | Payne 69 kV | In Service |
| AD1-128 | Modoc-Delaware 138 kV | Partially in Service - Under Construction |
| AD1-130 | Hardin Switch 345 kV | In Service |
| AD1-136 | South Bethel-Brown 69 kV | In Service |
| AD1-140 | Greene-Clark 138 kV | Engineering & Procurement |
| AD1-155 | Meadow Brook-Strasburg 138 kV | In Service |
| AD2-009 | McConnellsburg 138 kV | In Service |
| AD2-016 | Biers Run-Circleville 138 kV | In Service |
| AD2-020 | Valley 138 kV | Engineering & Procurement |
| AD2-027 | Camden Switch 26 kV | In Service |
| AD2-031 | Martinsville-Wilmington 69 kV | In Service |
| AD2-038 | Powerton-Nevada 345 kV | Under Construction |
| AD2-042 | Camden Switch 26 kV II | In Service |
| AD2-047 | Davis Creek 138 kV | Suspended |
| AD2-048 | Cynthia-Headquarters 69 kV | Under Construction |
| AD2-058 | St. Barnabas 13 kV | In Service |
| AD2-060 | Davis Creek 138kV | Engineering & Procurement |
| AD2-065 | Atco 12 kV | In Service |
| AD2-066 | Mazon-Crescent Ridge 138 kV | Engineering & Procurement |
| AD2-067 | Centerburg 138kV | Engineering & Procurement |
| AD2-070 | Gilbert-Morris Park 34.5kV | In Service |
| AD2-071 | Strawton-Deer Creek 138 kV | Suspended |
| AD2-073 | Sanders DP 230 kV | In Service |
| AD2-074 | Garner DP-Lancaster 115 kV | Engineering & Procurement |
| AD2-079 | Capitol Ave 34.5kV | In Service |
| AD2-086 | Hardin Switch 345 kV | In Service |
| AD2-091 | Hardin Tap 345kV | Suspended |
| AD2-092 | Marysville 345kV | Under Construction |
| AD2-093 | Marysville 345kV | Under Construction |
| AD2-096 | Marysville 345kV | Suspended |
| AD2-100 | Kincaid-Pana 345 kV | Suspended |
| AD2-115 | Lyons-Moselem 69kV | In Service |
| AD2-116 | Hokes-Grantley 69 kV | In Service |
| AD2-131 | Kincaid-Pana 345kV | Suspended |
| AD2-133 | Eagle Valley 115kV | In Service |
| AD2-134 | Shady Oaks | Partially in Service - Under Construction |
| AD2-135 | Williamstown 12kV | Partially in Service - Under Construction |
| AD2-163 | Broadview-Tangy 138 kV | In Service |
| AD2-172 | Lena 138kV | In Service |
| AD2-179 | Morgans Cut-Glen Lyn 138kV | Suspended |
| AD2-180 | Elk Garden-Parr Run 138kV | In Service |
| AE1-040 | Greenfield 69 kV | In Service |
| AE1-041 | Edison 4kV | In Service |
| AE1-071 | Shade Gap-Roxbury 115 kV | In Service |
| AE1-074 | Winterpock 34.5 kV | Under Construction |
| AE1-075 | Powhatan 34.5 kV | In Service |
| AE1-079 | Maysville-Sharon 69 kV | Under Construction |
| AE1-081 | Landing 12.47 kV | In Service |
| AE1-090 | Hardin Switch 345 kV | In Service |
| AE1-091 | West Newton-Lynn 138 kV | Suspended |
| AE1-092 | Blue Jacket-Kirby 138 kV | Active |
| AE1-100 | Axton 138 kV | In Service |
| AE1-101 | McConnellsburg-Texas Eastern 138 kV | In Service |
| AE1-102 | Maddox Creek 345 kV | Suspended |
| AE1-109 | Frenchs Mill 34 kV | In Service |
| AE1-113 | Mole Creek 345 kV | Engineering & Procurement |
| AE1-114 | Maryland-Lancaster 138 kV | Active |
| AE1-142 | Manitou-Pleasant Plains 34.5 kV | In Service |
| AE1-146 | Ebersole #2-Fostoria Central 138 kV | Under Construction |
| AE1-155 | Garner-Northern Neck 115 kV | In Service |
| AE1-156 | Quakertown Solar II 34.5 kV | Partially in Service - Under Construction |
| AE1-163 | Powerton-Nevada 345 kV | Engineering & Procurement |
| AE1-166 | Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kV | Engineering & Procurement |
| AE1-170 | Kenzie Creek-Colby 138 kV | Suspended |
| AE1-172 | Loretto-Wilton Center | Active |
| AE1-176 | Roanoke-Vinton 12 kV (Niagara Hydro) | In Service |
| AE1-183 | Maysville-McDowell 69 kV | Engineering & Procurement |
| AE1-185 | Hokes-Jackson 69 kV | In Service |
| AE1-196 | Hokes-Jackson 69 kV II | In Service |
| AE1-205 | McLean 345 kV | Engineering & Procurement |
| AE1-207 | Mississinewa-Gaston 138 kV | Suspended |
| AE1-208 | Delaware-Van Buren 138 kV | Suspended |
| AE1-209 | Desoto 345 kV | Suspended |
| AE1-210 | Desoto 345 kV | Suspended |
| AE1-212 | Grandview-Clifftop 138 kV | Suspended |
| AE1-227 | South Cumberland 69 kV | Suspended |
| AE1-229 | Deepwater-Upper Pittsgrove 138 kV | Suspended |
| AE1-237 | Andover (Maysville) 69kV I | Under Construction |
| AE1-245 | Haviland 138 kV | Under Construction |
| AE1-250 | Smith Mountain-E. Danville 138 kV | Engineering & Procurement |
| AE2-029 | Grottoes-Merck 115kV | Under Construction |
| AE2-035 | Lena 138 kV | In Service |
| AE2-042 | Milton 69 kV | In Service |
| AE2-045 | Olive-Reynolds 345 kV | Engineering & Procurement |
| AE2-047 | Ridgeway-Solite 69 kV | Engineering & Procurement |
| AE2-048 | Muskingum-W. Millersport 345 kV | Engineering & Procurement |
| AE2-054 | Warfordsburg 34 kV | In Service |
| AE2-059 | Derry Tap-Derry Bus 69 kV | In Service |
| AE2-060 | Mifflintown Bus-Mifflintown Tap 69 kV | In Service |
| AE2-071 | Patton Rd-Summer Shade 69 kV | In Service |
| AE2-072 | East Leipsic-Richland 138 kV | In Service |
| AE2-089 | Pennville-Adams 138 kV | Engineering & Procurement |
| AE2-092 | Kidds Store-Sherwood 115 kV | Engineering & Procurement |
| AE2-113 | Farmers Valley-Ridgeway 115 kV | Under Construction |
| AE2-114 | Midland 23 kV I | In Service |
| AE2-115 | Midland 23 kV II | In Service |
| AE2-117 | ABW Tap-Alexandria 46 kV | Suspended |
| AE2-125 | Stahlstown-Ligonier 25 kV | In Service |
| AE2-126 | Dubois-Curwensville 34.5 kV | In Service |
| AE2-129 | Philipsburg-Clarence 34.5 kV | In Service |
| AE2-131 | Philipsburg-Karthaus 34.5 | Under Construction |
| AE2-133 | Penns Tap-Richfield Tie 69 kV | In Service |
| AE2-136 | Muskingum River-W. Millersport 345 kV | Engineering & Procurement |
| AE2-139 | East Towanda-Grover 230 kV | Engineering & Procurement |
| AE2-140 | Axton-Danville 138 kV | Suspended |
| AE2-148 | Beatty-Greene 345 kV | In Service |
| AE2-152 | Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kV | Engineering & Procurement |
| AE2-160 | Kanawha River 138 kV | Engineering & Procurement |
| AE2-166 | Stockton 138 kV | Suspended |
| AE2-169 | Delaware-Van Buren 138 kV | Suspended |
| AE2-172 | Mississinewa-Gaston 138 kV | Suspended |
| AE2-173 | McLean 345 kV | Active |
| AE2-175 | Jackson-Long Pond 69 kV | Partially in Service - Under Construction |
| AE2-181 | Snyder 69kV | Under Construction |
| AE2-185 | Gladys DP-Stonemill Switching Station 69 kV | Active |
| AE2-187 | Shockoe DP-Chatham 69 kV | Active |
| AE2-206 | East Sidney-Quincy 138 kV | In Service |
| AE2-214 | Cole 345 kV | Engineering & Procurement |
| AE2-216 | Hardin Switch 345 kV | Engineering & Procurement |
| AE2-217 | East Springfield-London 138 kV | Engineering & Procurement |
| AE2-219 | Bluff Point-Randolph 138 kV | Suspended |
| AE2-220 | Losantville 345 kV | Engineering & Procurement |
| AE2-221 | Clinton-Stuart 345 kV | Under Construction |
| AE2-223 | McLean 345 kV | Active |
| AE2-224 | Bear Rock-Johnstown 230 kV | In Service |
| AE2-226 | Millville-Old Chapel 138 kV | Engineering & Procurement |
| AE2-230 | Bartonsville-Meadow Brook 138 kV | In Service |
| AE2-234 | Liberty Center-Buckeye Tap 69 kV | Engineering & Procurement |
| AE2-236 | Columbia-Northeast 138 kV | Suspended |
| AE2-254 | Garrard County-Tommy-Gooch 69 kV | In Service |
| AE2-255 | Molecreek 345 kV | Engineering & Procurement |
| AE2-261 | Kincaid-Pana 345 kV | Active |
| AE2-262 | Moshannon-Milesburg 230 kV | Engineering & Procurement |
| AE2-263 | Moshannon-Milesburg 230 kV II | Engineering & Procurement |
| AE2-267 | Woodsdale 345 kV | Engineering & Procurement |
| AE2-276 | Sullivan 345kV | Engineering & Procurement |
| AE2-281 | Powerton-Nevada 345 kV | Engineering & Procurement |
| AE2-282 | East Fayette 138 kV | In Service |
| AE2-283 | Gladys-Stone Mill 69 kV | Active |
| AE2-285 | Maysville 69 kV | Engineering & Procurement |
| AE2-291 | Grit DP-Perth 115 kV | Active |
| AE2-297 | Madison-Tanners Creek 138 kV | In Service |
| AE2-298 | Cavett Switch - West Van Wert 69 kV | Engineering & Procurement |
| AE2-305 | Givens-Mechanicsburg 138 kV | Engineering & Procurement |
| AE2-306 | Gunn Road 345 kV | Under Construction |
| AE2-308 | Three Forks-Dale 138 kV | Active |
| AE2-309 | Carlos Junction-Lonaconing 34.5 kV | In Service |
| AE2-315 | Yankee Tap 69 kV | In Service |
| AE2-318 | Ford-Cedarville 138 kV | Suspended |
| AE2-321 | Belvidere-Marengo 138 kV | Active |
| AE2-322 | Mark Center 69 kV | Under Construction |
| AE2-323 | Twin Branch-Guardian 138 kV | Under Construction |
| AE2-325 | Valley 138 kV | Active |
| AE2-326 | Jacksons Ferry 138 kV | Engineering & Procurement |
| AE2-339 | Avon 138 kV | Engineering & Procurement |
| AE2-341 | Sandwich-Plano 138 kV | Active |
| AE2-342 | Woodstock 69 kV | Engineering & Procurement |
| AE2-343 | Andover (Maysville) 69 kV II | Under Construction |
| AF1-006 | Fairview East 34.5 kV | In Service |
| AF1-007 | Indian River 230 kV I | Suspended |
| AF1-021 | Bethelboro-Connellsville #1 25 kV | In Service |
| AF1-022 | Lake Lynn-Uniontown 25 kV | In Service |
| AF1-030 | Sandwich-Plano 138 kV | Active |
| AF1-038 | Sewellton Jct-Webbs Crossroads 69 kV | Engineering & Procurement |
| AF1-039 | Listonburg-Highpoint 24.9 kV | In Service |
| AF1-042 | Garner DP-Lancaster 115 kV | Engineering & Procurement |
| AF1-045 | Cedarville-Ford 138 kV | Suspended |
| AF1-049 | Berry Hill 138 kV | Under Construction |
| AF1-050 | Summer Shade - Green County 161 kV | Engineering & Procurement |
| AF1-051 | Gavin 765 kV | In Service |
| AF1-053 | Givens-Mechanicsburg 138 kV | Engineering & Procurement |
| AF1-054 | Givens-Mechanicsburg 138 kV | Engineering & Procurement |
| AF1-062 | Jug Street 138 kV | Engineering & Procurement |
| AF1-064 | Weston 69 kV | Under Construction |
| AF1-071 | College Corner 138 kV | Engineering & Procurement |
| AF1-078 | East Sidney-Quincy 138 kV | In Service |
| AF1-083 | Green County-Saloma 161 kV | Engineering & Procurement |
| AF1-084 | Hartford-Almena 69 kV | Engineering & Procurement |
| AF1-086 | Madera-Westover South 115 kV | Under Construction |
| AF1-088 | Sullivan 345 kV | Active |
| AF1-090 | Kincaid-Pana | Engineering & Procurement |
| AF1-091 | Varner - Sowers 138 kV | Engineering & Procurement |
| AF1-092 | Huntington Jct. 138 kV | Suspended |
| AF1-093 | Henderson-Stoneboro 69 kV | Engineering & Procurement |
| AF1-094 | Union City-Cambridge Springs 34.5 kV | Engineering & Procurement |
| AF1-098 | Four Mile Jct-Corry East 115 kV | Engineering & Procurement |
| AF1-118 | Sorenson-Desoto 345 kV | Engineering & Procurement |
| AF1-119 | Keystone-Desoto 345 kV | Engineering & Procurement |
| AF1-120 | East Fayette 2 138 kV | In Service |
| AF1-122 | Cardington-Liberty 69 kV | Suspended |
| AF1-130 | Inez 138 kV | Suspended |
| AF1-134 | Philipsburg-Madera 34.5 kV | Engineering & Procurement |
| AF1-136 | Warfordsburg-Purcell Junction 34.5 kV | Engineering & Procurement |
| AF1-140 | Claysburg 23 kV | Engineering & Procurement |
| AF1-143 | Lick Run 115 kV | Engineering & Procurement |
| AF1-147 | Poland Rd-Runway DP 230kV | Under Construction |
| AF1-153 | Motion-Ridgeway 46 kV | Suspended |
| AF1-158 | Edison-Gravel Pit 138 kV | In Service |
| AF1-161 | Valley 138 kV | Active |
| AF1-162 | Inez 138 kV | Engineering & Procurement |
| AF1-176 | Corey 138 kV | Active |
| AF1-202 | Keystone-Desoto 345 kV | Under Construction |
| AF1-203 | Patton Rd-Summer Shade 69 kV | In Service |
| AF1-204 | Eugene 345 kV | Active |
| AF1-205 | Napoleon Muni 138 kV | Suspended |
| AF1-206 | East Fayette 138 kV | Engineering & Procurement |
| AF1-207 | Reynolds-Olive #1 345 kV | Engineering & Procurement |
| AF1-215 | Olive-Reynolds 345 kV | In Service |
| AF1-223 | Keystone-Desoto 345 kV | Under Construction |
| AF1-227 | Marysville – Gunn Road 345 kV | In Service |
| AF1-228 | Beatty-Greene 345 kV | Engineering & Procurement |
| AF1-229 | Galion-South Berwick 345 kV | Engineering & Procurement |
| AF1-233 | Flemingsburg – Spurlock 138kV | Active |
| AF1-249 | Nickel 12.47 kV | In Service |
| AF1-254 | Milnor-Huyetts 34.5 kV | Under Construction |
| AF1-262 | Upper Pittsgrove 12 kV | In Service |
| AF1-264 | Runnemede 13 kV | In Service |
| AF1-268 | Desoto-Jay 138 kV | Engineering & Procurement |
| AF1-272 | Lucerne 115 kV | Engineering & Procurement |
| AF1-275 | Cole 345 kV | Engineering & Procurement |
| AF1-282 | Stuart-Clinton 345 kV | Engineering & Procurement |
| AF1-283 | Stuart-Clinton 345 kV | Engineering & Procurement |
| AF1-285 | Gunn Road 345 kV | Under Construction |
| AF1-290 | Feagans Mill-Millville 138 kV | In Service |
| AF1-291A | Bartonsville-Meadow Brook 138 kV | In Service |
| AF1-296 | Garden Plain 138 kV | Active |
| AF1-299 | Otter Point 34.5 kV I | In Service |
| AF1-300 | Otter Point 34.5 kV II | In Service |
| AF1-302 | Brookville-Squab Hollow 138 kV | Engineering & Procurement |
| AF1-320 | Merrill Creek 115 kV | Engineering & Procurement |
| AF1-322 | Meadow Lake 345 kV | Engineering & Procurement |
| AF1-331 | Twombley Road | Engineering & Procurement |
| AF1-333 | Laurelton-Mifflinburg 69 kV | Engineering & Procurement |
| AF1-337 | Laurelton-Mifflinburg 69 kV | Engineering & Procurement |
| AF1-338 | Laurelton-Mifflinburg 69 kV | Engineering & Procurement |
| AF1-339 | Laurelton-Mifflinburg 69 kV | Engineering & Procurement |
| AF2-008 | Sullivan 345 kV | Active |
| AF2-014 | Maddox Creek 345 kV | Engineering & Procurement |
| AF2-018 | Inez 138 kV | Engineering & Procurement |
| AF2-032 | Kincaid 345 kV | Engineering & Procurement |
| AF2-039 | Shawville-Clearfield 34.5 kV | Engineering & Procurement |
| AF2-041 | Nelson-Electric Junction 345 kV | Active |
| AF2-048 | Rio-Lick 138 kV | Engineering & Procurement |
| AF2-068 | Jay 138 kV | Active |
| AF2-069 | Crescent Ridge 138 kV | Active |
| AF2-075 | Bartonsville-Meadow Brook 138 kV III | In Service |
| AF2-078 | Reynolds-Olive #1 345 kV | Engineering & Procurement |
| AF2-083 | Kenzie Creek-Stone Lake 69 kV | Under Construction |
| AF2-086 | Scott Tap-Bowmans Mill Tap 69 kV | Engineering & Procurement |
| AF2-088 | Shawville-Clearfield 34.5 kV II | Engineering & Procurement |
| AF2-095 | Davis Creek 138 kV | Active |
| AF2-103 | Haviland 138 kV | In Service |
| AF2-106 | Hazel Hollow-Glen Lyn #1 138 kV | Engineering & Procurement |
| AF2-107 | Clifford 138 kV | Engineering & Procurement |
| AF2-111 | North Clark-Spurlock 345 kV | Active |
| AF2-122 | Kirk 138 kV | Under Construction |
| AF2-126 | Weston 69 kV II | Active |
| AF2-130 | Cobalt Corners 34.5 kV | In Service |
| AF2-132 | Reynolds-Olive #1 345 kV | Under Construction |
| AF2-133 | Reynolds-Olive #2 345 kV | Under Construction |
| AF2-134 | Olive-Reynolds #2 345 kV | In Service |
| AF2-138 | Flanders-West Wharton 34.5 kV | In Service |
| AF2-139 | Gilbert-Warren Glen 34.5 kV | In Service |
| AF2-142 | Nevada 345 kV | Active |
| AF2-143 | Powerton-Nevada 345 kV | Active |
| AF2-144 | Powhatan 34.5 kV | In Service |
| AF2-149 | Sharp Road 69 kV | Engineering & Procurement |
| AF2-150 | Galion 138 kV | Under Construction |
| AF2-162 | Keystone-Desoto 345 kV | Engineering & Procurement |
| AF2-173 | Desoto 345 kV | Active |
| AF2-177 | Sorenson-DeSoto #2 345 kV | Active |
| AF2-192 | Frenchtown Solar-West Flemington 34.5 kV | Suspended |
| AF2-199 | Nelson-Electric Junction 345 kV | Active |
| AF2-200 | Nelson-Electric Junction 345 kV | Active |
| AF2-205 | Olive-Reynolds #2 345 kV | Engineering & Procurement |
| AF2-224 | Allen 345 kV | Engineering & Procurement |
| AF2-225 | McLean 345 kV | Active |
| AF2-229 | Roxbury 23 kV | Engineering & Procurement |
| AF2-233 | Penns-Richfield Tie #1 69 kV | Engineering & Procurement |
| AF2-234 | Sunbury Yard #1-Richfield Tie #2 69 kV | Engineering & Procurement |
| AF2-235 | Titusville-Oil Creek 34.5 kV | Withdrawn |
| AF2-238 | Mansfield-South Troy 34.5 kV | Engineering & Procurement |
| AF2-247 | Bustleton 13.2 kV | In Service |
| AF2-250 | Edgewood 12 kV III | In Service |
| AF2-252 | Blue Mound 345 kV | Engineering & Procurement |
| AF2-291 | Sporn South-Leon 138 kV | Engineering & Procurement |
| AF2-298 | Crown-New Lebanon 69 kV | Engineering & Procurement |
| AF2-307 | Hope-Belvins Valley Tap 69 kV | Active |
| AF2-311 | Gilboa-Jones Branch 138 kV | Engineering & Procurement |
| AF2-316 | Gilboa-Jones Branch 138 kV II | Engineering & Procurement |
| AF2-325 | Jacktown 12 kV | Engineering & Procurement |
| AF2-335 | Delaware-Royerton 138 kV | Active |
| AF2-350 | Kensington 138 kV | Active |
| AF2-352 | Blue Mound 345 kV | Engineering & Procurement |
| AF2-354 | Washington 34.5 kV II | Engineering & Procurement |
| AF2-356 | Albright-Mt. Zion 138 kV | Under Construction |
| AF2-359 | Olive-University Park 345 kV | Engineering & Procurement |
| AF2-361 | Mifflintown Tap 69 kV | Engineering & Procurement |
| AF2-365 | Munfordville KU Tap-Horse Cave Jct. 69 kV | Active |
| AF2-370 | Delaware-Royerton 138 kV | Active |
| AF2-371 | Harrison-Good Hope 138 kV | Engineering & Procurement |
| AF2-375 | Ebersole-Fostoria 138 kV | Engineering & Procurement |
| AF2-376 | Timber Switch 138 kV | Active |
| AF2-377 | Logtown 138 kV | Engineering & Procurement |
| AF2-378 | Cambridge 12 kV | Engineering & Procurement |
| AF2-379 | Princess Anne 25 kV | Under Construction |
| AF2-382 | Hurley 69 kV | Engineering & Procurement |
| AF2-383 | Tolna 115 kV | Withdrawn |
| AF2-388 | Keystone-Desoto 345 kV | Active |
| AF2-389 | Kenzie Creek-Stone Lake 69 kV | Withdrawn |
| AF2-392 | Nelson-Dixon 138 kV | Active |
| AF2-396 | Stinger 138 kV | Active |
| AF2-407 | Fall Creek 345 kV | Active |
| AF2-408 | Fall Creek 138 kV | Engineering & Procurement |
| AF2-417 | West Damascus Tap-West Damascus 69 kV | Engineering & Procurement |
| AF2-421 | East Hazelton-Weatherly Tap 69 | Engineering & Procurement |
| AF2-424 | Reed-Reed Tap #1 69 kV | Engineering & Procurement |
| AF2-425 | Reed-Reed Tap#1 69 kV | Engineering & Procurement |
| AF2-433 | Columbia-Geisinger Tap #1 69 kV | Engineering & Procurement |
| AF2-434 | Columbia-Geisinger Tap #1 69 kV | Engineering & Procurement |
| AF2-440 | Hillsboro-Middleboro 138 kV | Engineering & Procurement |
| AG1-017 | Jay 138 kV | Under Construction |
| AG1-024 | Centerburg 138 kV | Engineering & Procurement |
| AG1-034 | Centerburg 138 kV | Engineering & Procurement |
| AG1-039 | Galion 138 kV II | Under Construction |
| AG1-040 | Morgan Street-Mount Hope 34.5 kV | Engineering & Procurement |
| AG1-047 | Jay 138 kV | Engineering & Procurement |
| AG1-054 | Potter-Harlan 69 kV | Engineering & Procurement |
| AG1-070 | Bon Ayr 69 kV | Active |
| AG1-071 | Bon Ayr 69 kV | Active |
| AG1-100 | Venango-Saegertown 34.5 kV | Engineering & Procurement |
| AG1-107 | Hillsboro-Middleboro 138 kV | Engineering & Procurement |
| AG1-109 | Valley 138 kV | Active |
| AG1-118 | Sugar Grove-Waterman 138kV | Active |
| AG1-124 | Gladstone 138 kV | Active |
| AG1-125 | Marysville-Flatlick 765 kV | Engineering & Procurement |
| AG1-126 | Marysville-Flatlick 765 kV | Engineering & Procurement |
| AG1-127 | Crego Rd 138 kV | Active |
| AG1-156 | Jack Frost-Lake Harmony 69 kV | Engineering & Procurement |
| AG1-164 | East Hazelton-Weatherly Tap 69 kV | Engineering & Procurement |
| AG1-165 | East Hazelton-Weatherly Tap 69 kV | Engineering & Procurement |
| AG1-188 | Manitou-Oyster Creek 34.5 kV | Engineering & Procurement |
| AG1-189 | Oyster Creek-Bamber Lake 34.5 | Engineering & Procurement |
| AG1-191 | Chester-Pohatcong Mountain 34.5 kV | Partially in Service - Under Construction |
| AG1-193 | Utica Junction 34.5 kV | Suspended |
| AG1-197 | Morgan Street-Cochranton 34.5 kV | Suspended |
| AG1-198 | Union City 34.5 kV | Under Construction |
| AG1-207 | Vandalia 69 kV | Engineering & Procurement |
| AG1-223 | Larrabee-Allaire 34.5 kV | Under Construction |
| AG1-226 | Dequine-Eugene 345 kV | Active |
| AG1-232 | Magley 138 kV | Engineering & Procurement |
| AG1-236 | Lanesville-Brokaw 345 kV | Active |
| AG1-237 | Dequine-Eugene 345 kV | Engineering & Procurement |
| AG1-254 | Salem-Woodstown 69 kV | Engineering & Procurement |
| AG1-259 | Sunbury-Dalmatia 69 kV | Engineering & Procurement |
| AG1-260 | Sunbury-Dalmatia 69 kV | Engineering & Procurement |
| AG1-281 | Claysburg-HCR Tap 46 kV | Engineering & Procurement |
| AG1-282 | Dunnsville 34.5 kV | Engineering & Procurement |
| AG1-297 | Hanna-Tanners Creek 345 kV | Active |
| AG1-301 | Miller REC-Warrior Ridge 46 kV | Engineering & Procurement |
| AG1-302 | Olive-Reynolds #1 345 kV | Under Construction |
| AG1-320 | Glendale-Stephensburg 69 kV | Active |
| AG1-323 | Blue Jacket 138 kV | Active |
| AG1-324 | Jay-Desoto 138 kV | Engineering & Procurement |
| AG1-341 | Summer Shade 161 kV | Active |
| AG1-348 | Pequest River-Washington 34.5 kV | In Service |
| AG1-349 | Olive-Reynolds #2 345 kV | Engineering & Procurement |
| AG1-351 | Harrison-Good Hope 138 kV | Engineering & Procurement |
| AG1-354 | Summershade-Green County 161 kV | Active |
| AG1-363 | Black Oak-Hatfield 500 kV | Engineering & Procurement |
| AG1-365 | Allen 345 kV | Engineering & Procurement |
| AG1-366 | Allen 345 kV | Engineering & Procurement |
| AG1-367 | DeSoto 345 kV | Active |
| AG1-368 | Tillman 138 kV | Engineering & Procurement |
| AG1-369 | Logtown 138 kV | Engineering & Procurement |
| AG1-374 | Blue Mound 345 kV | Active |
| AG1-375 | Sorenson-Desoto 345 kV | Active |
| AG1-386 | Smith-Francis Junction 25 kV | In Service |
| AG1-397 | Walston 12 kV | Withdrawn |
| AG1-405 | Walnut Grove-Asahi 69 kV | Active |
| AG1-406 | Walnut Grove-Asahi 69 kV | Active |
| AG1-410 | Maddox Creek-RP Mone 345 kV | Active |
| AG1-411 | Maddox Creek-RP Mone 345 kV | Active |
| AG1-414 | Mississinewa 138 kV | Engineering & Procurement |
| AG1-433 | Keystone-DeSoto 345 kV | Active |
| AG1-436 | Olive-University Park 345 kV | Active |
| AG1-447 | Olive-University Park 345 kV | Active |
| AG1-460 | Kincaid-Pana 345 kV | Active |
| AG1-462 | Cordova 345 kV | Active |
| AG1-469 | Gordonsville 34.5 kV | Engineering & Procurement |
| AG1-471 | Up Church-Wayne County 69 kV | Active |
| AG1-478 | Wilmington 34.5 kV | Engineering & Procurement |
| AG1-480 | Shawnee 34.5 kV | Engineering & Procurement |
| AG1-482 | Hamilton 115 kV | Withdrawn |
| AG1-494 | Boxwood-Riverville 138 kV | Active |
| AG1-495 | Gilbert-Rocktown 34.5 kV | Engineering & Procurement |
| AG1-499 | Lambs 12.47 kV | Under Construction |
| AG1-508 | Point Lookout 69 kV | Engineering & Procurement |
| AG1-526 | West Garrard 345 kV | Active |
| AG1-554 | South Kenton 138 kV | Engineering & Procurement |
| AG1-555 | Dequine 345 kV | Engineering & Procurement |
| AG1-558 | Buckner 34.5 kV | Engineering & Procurement |
| AG1-559 | Caroline Pines 22 kV | Engineering & Procurement |
| AG2-029 | Forest G. Hipple-Collingwood 345 kV | Active |
| AG2-057 | Cardington-Liberty 69 kV II | Active |
| AG2-063 | North Hampton 69 kV | Active |
| AG2-072 | Rockport 765 kV | Active |
| AG2-073 | Crooksville 69 kV | Active |
| AG2-081 | Mt. Sterling-Fogg Pike 69 kV | Active |
| AG2-085 | Delaware-Royerton 138 kV | Active |
| AG2-104 | Marysville-Flatlick 765 kV | Active |
| AG2-106 | Marysville-Flatlick 765 kV | Active |
| AG2-107 | Marysville-Flatlick 765 kV | Active |
| AG2-111 | Perth 34.5 kV Substation (Circuit 408) | Active |
| AG2-112 | Perth 34.5 kV Substation (Circuit 404) | Active |
| AG2-114 | Dresden-Pontiac Midpoint 345 kV | Active |
| AG2-119 | Galion-Roberts South 138 kV II | Active |
| AG2-125 | Camden-Crystal 69 kV | Active |
| AG2-126 | Eugene 345 kV | Active |
| AG2-149 | Galion-South Berwick 345 kV | Active |
| AG2-152 | Banister-Bear Skin 138 kV | Active |
| AG2-159 | Williamstown 69 kV | Active |
| AG2-162 | Jefferson-Greentown 765 kV | Active |
| AG2-163 | Dequine-Eugene 345 kV | Active |
| AG2-164 | Jefferson-Greentown 765 kV | Active |
| AG2-165 | Dumont-Greentown 765 kV | Active |
| AG2-179 | Sewellton Junction 69 kV | Active |
| AG2-184 | Harbert Metering 138 kV | Active |
| AG2-191 | Mississinewa 138 kV | Active |
| AG2-192 | Mississinewa 138 kV | Active |
| AG2-212 | Dumont-Greentown 765 kV | Active |
| AG2-216 | East Sidney-Quincy 138 kV | Active |
| AG2-219 | Jefferson-Greentown 765 kV | Active |
| AG2-230 | Dumont 345 kV | Active |
| AG2-245 | Olive - Reynolds #1 345 kV | Active |
| AG2-298 | Sulphur Creek-Loretto 69 kV | Active |
| AG2-310 | Matt Funk 138 kV | Active |
| AG2-311 | Smith Mountain 138 kV | Active |
| AG2-328 | Dumont - Greentown 765 kV | Active |
| AG2-329 | S Berwick - Galion 345 kV | Active |
| AG2-330 | Dumont - Greentown 765 kV | Active |
| AG2-331 | Jefferson-Greentown 765 kV | Active |
| AG2-332 | East Elkhart – Elcona Tap 138 kV | Active |
| AG2-360 | Broadford 138 kV | Active |
| AG2-363 | Powerton 345 kV | Active |
| AG2-364 | Powerton 345 kV | Active |
| AG2-370 | Tillman 138 kV | Active |
| AG2-378 | North Hampton – Medway 69 kV | Active |
| AG2-385 | North Hampton 69 kV | Active |
| AG2-400 | Allen 345 kV | Active |
| AG2-401 | Losantville 345 kV | Active |
| AG2-402 | Allen 345 kV | Active |
| AG2-405 | Continental 69 kV | Active |
| AG2-406 | Payne 69 kV | Active |
| AG2-408 | Allen 345 kV | Active |
| AG2-424 | Magnolia - Summersville 69 kV | Active |
| AG2-444 | Bixby - Biers Run 345 kV | Active |
| AG2-449 | Jefferson-Greentown 765 kV | Active |
| AG2-453 | Lasalle - Plano 345 kV | Active |
| AG2-487 | Madison - Tanners Creek 138 kV | Active |
| AG2-491 | Meadow Lake 345 kV | Active |
| AG2-516 | Pecatonica 138kV | Active |
| AG2-518 | Tech Drive 138 kV | Active |
| AG2-519 | Royerton - Desoto 138 kV | Active |
| AG2-524 | LaSalle Station - Mazon 138 kV | Active |
| AG2-548 | Corwin - Elk 138 kV | Active |
| AG2-550 | Bluff Point - Randolph 138 kV | Active |
| AG2-551 | Bluff Point - Randolph 138 kV | Active |
| AG2-568 | Stink Run – Sundial 138 kV | Active |
| AG2-575 | Crego Rd. 138 kV | Active |
| AG2-582 | Flint Run 500 kV | Active |
| AG2-585 | Kensington 138kV | Active |
| AG2-589 | Ravenswood - Hemlock 69 kV | Active |
| AG2-657 | Kanawha River - Carbondale 138 kV | Active |
| AG2-660 | Nelson-Electric Junction 345 kV | Active |
| AG2-665 | Corwin - Elk 138 kV | Active |
| AG2-670 | Green County -Taylor County Junction 161 kV | Active |
| AH1-004 | Avon - Renaker 138 kV | Active |
| AH1-034 | Patton Road Junction - Summer Shade 69 kV | Active |
| AH1-044 | Nelson - Electric Junction 345 kV | Active |
| AH1-047 | Marengo - Belvidere 138 kV | Active |
| AH1-055 | Kyger Creek - Don Marquis 345 kV | Active |
| AH1-059 | Sharp Road 69 kV | Active |
| AH1-060 | Cardington-Liberty 69 kV III | Active |
| AH1-072 | Red Onion - VC5 69 kV | Active |
| AH1-073 | Red Onion - VC5 69 kV | Active |
| AH1-075 | North Waldo - Wild Creek 138 kV | Active |
| AH1-098 | Wolf Glade-West Carroll 138 kV | Active |
| AH1-133 | Saltville - Tazewell 138 kV | Active |
| AH1-136 | Falcon - Middle Creek 46 kV | Active |
| AH1-144 | Peter's Mountain 138 kV | Active |
| AH1-145 | Peter's Mountain 138 kV | Active |
| AH1-146 | White Rock - Wayne 345 kV | Active |
| AH1-147 | White Rock - Wayne 345 kV | Active |
| AH1-150 | Nelson-Electric Junction 345 kV | Active |
| AH1-151 | Nelson-Electric Junction 345 kV | Active |
| AH1-153 | Dumont 345 kV | Active |
| AH1-164 | Oak Level - Tank Hill 138 kV | Active |
| AH1-188 | Pigeon Creek 138 kV | Active |
| AH1-196 | Prairie 345 kV | Active |
| AH1-227 | Flemming - Fremont 69 kV | Active |
| AH1-234 | Wempletown - Paddock 345 kV | Active |
| AH1-239 | Upchurch - Zula 69 kV | Active |
| AH1-269 | Claytor 138 kV | Active |
| AH1-272 | Argenta - Twin Branch 345 kV | Active |
| AH1-281 | Bluegrass Parkway Tap - Woodlawn 69 kV | Active |
| AH1-282 | Galion - Ohio Central 345 kV | Active |
| AH1-285 | Sandwich 138 kV | Active |
| AH1-292 | Sullivan 345 kV | Active |
| AH1-298 | Meridian 345 kV | Active |
| AH1-302 | Olive - Reynolds 345 kV | Active |
| AH1-304 | Delaware-Van Buren 138 kV | Active |
| AH1-305 | Olive - Reynolds 345 kV | Active |
| AH1-306 | Mississinewa-Gaston 138 kV | Active |
| AH1-308 | Pennville - Adams 138 kV | Active |
| AH1-309 | Kenzie Creek-Colby 138 kV | Active |
| AH1-327 | Hardin Switch 345 kV | Active |
| AH1-328 | Blue Jacket - Kirby 138 kV | Active |
| AH1-337 | Randolph - Hodgin 138 kV | Active |
| AH1-338 | McGirr Rd - Ritchie Road 138kV | Active |
| AH1-339 | West Crawford 69 kV | Active |
| AH1-341 | Stillman - Dixon 138KV | Active |
| AH1-348 | Pound 34.5 kV | Active |
| AH1-391 | Olive 138 kV | Active |
| AH1-392 | Gravel Pit-Kankakee 138 kV | Active |
| AH1-427 | Tommy Gooch - Garrard County 69 kV | Active |
| AH1-482 | Olive - Reynolds #2 345 kV | Active |
| AH1-535 | Nagel - Cane River 230 kV | Active |
| AH1-537 | Pierce - Kyger Creek 345 kV | Active |
| AH1-539 | South Kenton 138 kV | Active |
| AH1-541 | Chestnut 345 kV | Active |
| AH1-542 | Crissinger-Kirby 138kV | Active |
| AH1-543 | Mulberry – Tazewell 345 kV | Active |
| AH1-567 | University Park 138 kV | Active |
| AH1-570 | Headquarters - Millersburg Junction 69 kV | Active |
| AH1-571 | Headquarters - Millersburg Junction 69 kV | Active |
| AH1-617 | Harbert Metering 138 kV | Active |
| AH1-644 | Spicewood Metering 138 kV | Active |
| AH1-661 | Cannelville 12.47 kV | Active |
| AH1-664 | Goddard-Plumville 138 kV | Active |
| AH1-665 | Goddard-Plumsville 138 kV II | Active |
| AH1-666 | Flemingsburg - Spurlock 138 kV | Active |
| AH1-669 | Circleville-Biers Run 138 kV | Active |
| AH1-670 | Blue Mound-Chestnut 345 kV | Active |
| AH1-686 | Hanging Rock 765 kV | Active |
| AH1-698 | Braidwood 345 kV | Active |
| AH1-702 | Byron 345 kV | Active |
| AH1-704 | Hannibal 138 kV | Active |
| AH1-714 | Lasalle 345 kV | Active |
| AH1-718 | Nelson 345 kV | Active |
| AH1-719 | Beverly 345 kV | Active |
| AH1-721 | Laurel-Cooper 161 kV | Active |
| AH1-735 | Richland 138 kV | Active |
| U2-030 | Four Mile Ridge Wind 138kV | In Service |
| U2-072 | East Lima-Marysville 345kV | In Service |
| U2-073 | Frostburg 138kV II | In Service |
| V1-011 | Haviland 138kV | In Service |
| V3-007 | Desoto-Tanners Creek #1 345kV | In Service |
| V4-067 | Cates Road Egg Harbor Township 12kV | Deactivated |
| V4-073 | Yankee 12.5kV | In Service |
| W1-003 | Oak Hall | In Service |
| W1-004 | Oak Hall | In Service |
| W1-005 | Oak Hall | In Service |
| W1-006 | Oak Hall | In Service |
| W1-056 | Ada-Dunkirk 69kV | In Service |
| W1-130 | Vine Road 12kV | In Service |
| W2-030 | Egg Harbor Township | In Service |
| W2-048 | Brokaw-Lanesville | In Service |
| W3-077 | Broadway-Stewartsville 34.5kV | In Service |
| W4-005 | Blue Mound-Latham | In Service |
| X1-042 | Watervliet | In Service |
| X2-022 | Brokaw-Lanesville | In Service |
| X2-052 | Dumont-Olive 345kV | In Service |
| X3-005 | Wildwood 12kV | In Service |
| X3-066 | Church Hill 69kV | In Service |
| Y1-033 | Penn Mar-Rock Wood 115kV | In Service |
| Y1-049 | Wurno 34.5kV | In Service |
| Y1-079 | Wye Mills 69kV | In Service |
| Y1-080 | Dorchester 12kV | In Service |
| Y3-023 | Country Side 12kV | In Service |
| Y3-024 | Bluff Point 12kV | In Service |
| Y3-058 | Rockawalkin 69kV | In Service |
| Z2-076 | Worcester South 25kV | In Service |
| Z2-077 | Worcester North 25kV | In Service |
| Z2-087 | Pontiac MidPoint-Brokaw 345kV | In Service |
| Z2-115 | Deer Creek 12.47kV | In Service |
| Z2-116 | Twin Branch 12.47kV | In Service |
Affected System - PJM Identified Violations
As part of PJM's analysis, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.
Affected System - Non-PJM Identified Violations
In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with potential Affected System impacts. PJM initiates coordination with each Affected System Operator by providing a list of New Service Requests in the Cycle with potential impacts to their respective system. If the Affected System Operator indicates an Affected System Study is required, PJM will notify the Project Developer or Eligible Customer of the need for an Affected System Study. See below if any Affected System Operator requires a study for this project:
System Reinforcements
Based on the Phase I analysis results, this project may have a cost responsibility for the following System Reinforcements:
| TO | RTEP ID | Title | Allocated Cost ($USD) |
|---|---|---|---|
| DEOK | n9187.0 / M220257 | Rebuild 11.9 mile DEOK portion of College Corner-Collinsville line with new structures and 954ACSS/TW Cardinal, 200C | $37,733,384 |
| DEOK | n9176.0 / M240124 | Rebuild the 1.4 mile long feeder from McGuffey to Locust. | $2,844,629 |
| AEP | (Pending) / AEPSERG03 | AF1-268 TP 138 KV to 05DESOTO 138 KV ckt 1 - Rebuild | $542,877 |
| AEP | (Pending) / AEP-TC2-18625 | 05HODGIN_BP 138.0 kV to 05HAYES 138.0 kV ckt 1 - Replace Conductor | $43,946 |
| AEP | (Pending) / AEP-TC2-18633 | AH1-337 TP 138.0 kV to 05HODGIN_BP 138.0 kV ckt 1 - Replace conductor | $43,946 |
| Grand Total: | $41,208,782 | ||
Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.
System Reinforcement: n9187.0
- Type
- Load Flow
- TO
- DEOK
- RTEP ID / TO ID
- n9187.0 / M220257
- Title
- Rebuild 11.9 mile DEOK portion of College Corner-Collinsville line with new structures and 954ACSS/TW Cardinal, 200C
- Description
- Rebuild the 11.9 mile DEOK portion of the College Corner-Collinsville line with new structures and 954ACSS/TW, 1 conductor per phase, 200 deg C. This line is on shared structures with College Corner-Trenton. College Corner-Trenton will be rebuilt from College Corner to just outside Collinsville with 954ACSS/TW, 1 conductor per phase, 200 deg C. DEOK's rebuild sections will be built to 480/480/520/520 MVA (SN/SE/WN/WE). Following the DEOK rebuild, AEP's 0.1 mile section will limit the College Corner - Collinsville circuit, but the violation will be alleviated. New Overall circuit ratings: 167/245/210/271 (SN/SE/WN/WE).
- Total Cost ($USD)
- $58,406,862
- Allocated Cost ($USD)
- $37,733,384
- Time Estimate
- 48 Months
Contributor
| Facility | Contingency | |
|---|---|---|
| 05COLLEGE C-08COLINV 138.0 kV Ckt 1 line | DEOK_P4_1403_MIAMI FORT_SRT-A | |
| 05COLLEGE C-08COLINV 138.0 kV Ckt 1 line | DEOK_P4_1301_TERMINAL_SRT-A | |
| 05COLLEGE C-08COLINV 138.0 kV Ckt 1 line | AEP_P4_#2812_05TANNER 345_T2_SRT-A | |
| 05COLLEGE C-08COLINV 138.0 kV Ckt 1 line | DEOK_P_4561TODWOOD14562TODWOOD2_SRT-A | |
| 05COLLEGE C-08COLINV 138.0 kV Ckt 1 line | DEOK_P4_1401_MIAMI FORT_SRT-A |
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
|---|---|---|---|
AG2-550 | 6.9 MW | 35.4% | $20,673,478 |
AG2-637 | 12.5 MW | 64.6% | $37,733,384 |
System Reinforcement: n9176.0
- Type
- Load Flow
- TO
- DEOK
- RTEP ID / TO ID
- n9176.0 / M240124
- Title
- Rebuild the 1.4 mile long feeder from McGuffey to Locust.
- Description
- Rebuild the 1.4 mile long feeder from McGuffey to Locust. Retire 54 wood poles. Retire 7,200ft of static. Retire 21,600ft of 4/0ACSR conductor. Install 54 light duty, steel poles. Install two engineered stub poles with foundations. Install 10,000ft of OPGW. Install 25,000ft of 954ACSR Rail conductor. Restore distribution underbuild on 44 poles. Perform two LiDAR flights, one for design engineering and one for post construction facility rating verification.
- Total Cost ($USD)
- $5,315,554
- Allocated Cost ($USD)
- $2,844,629
- Time Estimate
- 36 to 39 Months
Aggregate Contributor
| Facility | Contingency | |
|---|---|---|
| 08LOCST1-08MCGFY1 69.0 kV Ckt 1 line | DEOK_P7_CIRCUIT3281&13803_SRT-A | |
| 08LOCST1-08MCGFY1 69.0 kV Ckt 1 line | DEOK_P4_806_TRENTON_SRT-A | |
| 08LOCST1-08MCGFY1 69.0 kV Ckt 1 line | DEOK_P_CIRCUIT3281&13803_SRT-A | |
| 08LOCST1-08MCGFY1 69.0 kV Ckt 1 line | DEOK_P2.2_HUSTON_SRT-A | |
| 08LOCST1-08MCGFY1 69.0 kV Ckt 1 line | DEOK_P2.2_TRENTON1_SRT-A | |
| 08LOCST1-08MCGFY1 69.0 kV Ckt 1 line | DEOK_P4_808_TRENTON_SRT-A |
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
|---|---|---|---|
AG2-550 | 2.4 MW | 29.1% | $1,549,119 |
AG2-551 | 1.4 MW | 17.3% | $921,806 |
AG2-637 | 4.5 MW | 53.5% | $2,844,629 |
System Reinforcement
- Type
- Load Flow
- TO
- AEP
- RTEP ID / TO ID
- (Pending) / AEPSERG03
- Title
- AF1-268 TP 138 KV to 05DESOTO 138 KV ckt 1 - Rebuild
- Description
- Rebuild 138 kV line from Desoto to AF1-268 ~1.05 miles. Line conductor overloaded size is 1233.6 ACSR/TW 38/19.
- Total Cost ($USD)
- $2,047,500
- Allocated Cost ($USD)
- $542,877
- Time Estimate
- 18 to 24 Months
Contributor
| Facility | Contingency | |
|---|---|---|
| 05DESOTO-AF1-268 TP 138.0 kV Ckt 1 line | (Any) |
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
|---|---|---|---|
AG2-550 | 20.0 MW | 22.3% | $457,372 |
AG2-551 | 18.2 MW | 20.3% | $415,776 |
AG2-637 | 23.7 MW | 26.5% | $542,877 |
AH1-308 | 20.8 MW | 23.3% | $477,070 |
AH1-337 | 6.7 MW | 7.5% | $154,404 |
System Reinforcement
- Type
- Load Flow
- TO
- AEP
- RTEP ID / TO ID
- (Pending) / AEP-TC2-18625
- Title
- 05HODGIN_BP 138.0 kV to 05HAYES 138.0 kV ckt 1 - Replace Conductor
- Description
- Replace at Hodgin 138 kV 795kCM AAC 37-Str bus conductor
- Total Cost ($USD)
- $100,000
- Allocated Cost ($USD)
- $43,946
- Time Estimate
- 30 to 36 Months
Contributor
| Facility | Contingency | |
|---|---|---|
| 05HAYES-05HODGIN_BP 138.0 kV Ckt 1 line | (Any) |
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
|---|---|---|---|
AG2-550 | 65.6 MW | 28.7% | $28,703 |
AG2-551 | 21.1 MW | 9.2% | $9,222 |
AG2-637 | 100.5 MW | 43.9% | $43,946 |
AH1-308 | 10.0 MW | 4.4% | $4,378 |
AH1-337 | 31.4 MW | 13.8% | $13,751 |
System Reinforcement
- Type
- Load Flow
- TO
- AEP
- RTEP ID / TO ID
- (Pending) / AEP-TC2-18633
- Title
- AH1-337 TP 138.0 kV to 05HODGIN_BP 138.0 kV ckt 1 - Replace conductor
- Description
- Replace at Hodgin 138 kV 795kCM AAC 37-Str bus conductor
- Total Cost ($USD)
- $100,000
- Allocated Cost ($USD)
- $43,946
- Time Estimate
- 12 to 18 Months
Contributor
| Facility | Contingency | |
|---|---|---|
| 05HODGIN_BP-AH1-337 TP 138.0 kV Ckt 1 line | (Any) |
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
|---|---|---|---|
AG2-550 | 65.6 MW | 28.7% | $28,703 |
AG2-551 | 21.1 MW | 9.2% | $9,222 |
AG2-637 | 100.5 MW | 43.9% | $43,946 |
AH1-308 | 10.0 MW | 4.4% | $4,378 |
AH1-337 | 31.4 MW | 13.8% | $13,751 |
System Reinforcement: b4000.11
- Type
- Load Flow
- TO
- APS
- RTEP ID / TO ID
- b4000.11
- Title
- Expand Black Oak Substation & Loop in the 502 Jct-Woodside 500 kV line (Projected ISD 6/1/2029)
- Description
- Expand Black Oak Substation to accommodate the connection of the 502 Jct-Woodside 500 kV line and loop the 502 Jct-Woodside 500 kV line into the Black Oak substation by constructing ~0.85 miles of new 500 kV line into and out of Black Oak 500 kV substation
- Cost Information
- Time Estimate
- Jun 01 2029
Not Contingent Note: AG2-637 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-637 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.
| Facility | Contingency | |
|---|---|---|
| 05MOUNTN-05BELMON 765.0 kV Ckt 1 line | (Any) | |
| 01 502 J-01KAMMER 500.0 kV Ckt 1 line | (Any) | |
| 01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer | (Any) | |
| 01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line | (Any) | |
| 01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line | (Any) | |
| 05HYATT-05VASSEL 345.0 kV Ckt 1 line | (Any) | |
| 05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line | (Any) | |
| 05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line | (Any) |
System Reinforcement: b4000.3
- Type
- Load Flow
- TO
- APS
- RTEP ID / TO ID
- b4000.3
- Title
- Construct a new 175 miles Amos to Welton Spring 765 kV line - APS/FE Section of the line is 145 miles (Projected ISD 6/1/2029)
- Description
- 765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
- Cost Information
- Time Estimate
- Jun 01 2029
Not Contingent Note: AG2-637 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-637 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.
| Facility | Contingency | |
|---|---|---|
| 05MOUNTN-05BELMON 765.0 kV Ckt 1 line | (Any) | |
| 01 502 J-01KAMMER 500.0 kV Ckt 1 line | (Any) | |
| 01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer | (Any) | |
| 01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line | (Any) | |
| 01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line | (Any) | |
| 05HYATT-05VASSEL 345.0 kV Ckt 1 line | (Any) | |
| 05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line | (Any) | |
| 05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line | (Any) |
System Reinforcement: b4000.1
- Type
- Load Flow
- TO
- AEP
- RTEP ID / TO ID
- b4000.1
- Title
- Add two 765 kV breakers at Amos Substation to expand the breaker and a half scheme to accommodate the new Amos-Welton Spring 765 kV line (Projected ISD 6/1/2029)
- Description
- 765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
- Cost Information
- Time Estimate
- Jun 01 2029
Not Contingent Note: AG2-637 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-637 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.
| Facility | Contingency | |
|---|---|---|
| 05MOUNTN-05BELMON 765.0 kV Ckt 1 line | (Any) | |
| 01 502 J-01KAMMER 500.0 kV Ckt 1 line | (Any) | |
| 01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer | (Any) | |
| 01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line | (Any) | |
| 01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line | (Any) | |
| 05HYATT-05VASSEL 345.0 kV Ckt 1 line | (Any) | |
| 05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line | (Any) | |
| 05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line | (Any) |
System Reinforcement: b4000.7
- Type
- Load Flow
- TO
- APS
- RTEP ID / TO ID
- b4000.7
- Title
- Construct a new 86 miles Welton Spring to Rocky Point 765 kV line - in DVP local area/Millville to Lovettsville section, roughly 10.5 miles (Projected ISD 6/1/2029)
- Description
- 765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
- Cost Information
- Time Estimate
- Jun 01 2029
Not Contingent Note: AG2-637 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-637 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.
| Facility | Contingency | |
|---|---|---|
| 05MOUNTN-05BELMON 765.0 kV Ckt 1 line | (Any) | |
| 01 502 J-01KAMMER 500.0 kV Ckt 1 line | (Any) | |
| 01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer | (Any) | |
| 01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line | (Any) | |
| 01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line | (Any) | |
| 05HYATT-05VASSEL 345.0 kV Ckt 1 line | (Any) | |
| 05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line | (Any) | |
| 05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line | (Any) |
System Reinforcement: b4000.10
- Type
- Load Flow
- TO
- APS
- RTEP ID / TO ID
- b4000.10
- Title
- Install four 250 MVAR cap banks (two on 765 and two on 500 kV side) and a +/-500 MVAR STATCOM on the 765 kV Rocky Point yard
- Description
- 765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
- Cost Information
- Time Estimate
- Jun 01 2029
Not Contingent Note: AG2-637 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-637 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.
| Facility | Contingency | |
|---|---|---|
| 05MOUNTN-05BELMON 765.0 kV Ckt 1 line | (Any) | |
| 01 502 J-01KAMMER 500.0 kV Ckt 1 line | (Any) | |
| 01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer | (Any) | |
| 01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line | (Any) | |
| 01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line | (Any) | |
| 05HYATT-05VASSEL 345.0 kV Ckt 1 line | (Any) | |
| 05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line | (Any) | |
| 05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line | (Any) |
System Reinforcement: b4000.6
- Type
- Load Flow
- TO
- APS
- RTEP ID / TO ID
- b4000.6
- Title
- Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (Welton Spring to DVP local area, roughly 21 miles) (VA Portion)
- Description
- 765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
- Cost Information
- Time Estimate
- Jun 01 2029
Not Contingent Note: AG2-637 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-637 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.
| Facility | Contingency | |
|---|---|---|
| 05MOUNTN-05BELMON 765.0 kV Ckt 1 line | (Any) | |
| 01 502 J-01KAMMER 500.0 kV Ckt 1 line | (Any) | |
| 01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer | (Any) | |
| 01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line | (Any) | |
| 01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line | (Any) | |
| 05HYATT-05VASSEL 345.0 kV Ckt 1 line | (Any) | |
| 05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line | (Any) | |
| 05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line | (Any) |
System Reinforcement: b4000.5
- Type
- Load Flow
- TO
- APS
- RTEP ID / TO ID
- b4000.5
- Title
- Install four 250 MVAR shunt capacitors, and a +/-500 MVAR STATCOM at Welton Spring 765 kV substation
- Description
- 765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
- Cost Information
- Time Estimate
- Jun 01 2029
Not Contingent Note: AG2-637 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-637 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.
| Facility | Contingency | |
|---|---|---|
| 05MOUNTN-05BELMON 765.0 kV Ckt 1 line | (Any) | |
| 01 502 J-01KAMMER 500.0 kV Ckt 1 line | (Any) | |
| 01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer | (Any) | |
| 01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line | (Any) | |
| 01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line | (Any) | |
| 05HYATT-05VASSEL 345.0 kV Ckt 1 line | (Any) | |
| 05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line | (Any) | |
| 05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line | (Any) |
System Reinforcement: b4000.9
- Type
- Load Flow
- TO
- APS
- RTEP ID / TO ID
- b4000.9
- Title
- Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard (Projected ISD 6/1/2029)
- Description
- Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard. Loop in the Doubs-Goose Creek 500 kV line, the Doubs-Aspen 500 kV line, and the Woodside-Goose Creek 500 kV line. Install two 765/500 kV transformer at Rocky Point substation. 765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
- Cost Information
- Time Estimate
- Jun 01 2029
Not Contingent Note: AG2-637 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-637 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.
| Facility | Contingency | |
|---|---|---|
| 05MOUNTN-05BELMON 765.0 kV Ckt 1 line | (Any) | |
| 01 502 J-01KAMMER 500.0 kV Ckt 1 line | (Any) | |
| 01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer | (Any) | |
| 01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line | (Any) | |
| 01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line | (Any) | |
| 05HYATT-05VASSEL 345.0 kV Ckt 1 line | (Any) | |
| 05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line | (Any) | |
| 05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line | (Any) |
System Reinforcement: b4000.2
- Type
- Load Flow
- TO
- APS
- RTEP ID / TO ID
- b4000.2
- Title
- Construct a new 175 miles Amos to Welton Spring 765 kV line - AEP Section of the line is 30 miles (Projected ISD 6/1/2029)
- Description
- 765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
- Cost Information
- Time Estimate
- Jun 01 2029
Not Contingent Note: AG2-637 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-637 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.
| Facility | Contingency | |
|---|---|---|
| 05MOUNTN-05BELMON 765.0 kV Ckt 1 line | (Any) | |
| 01 502 J-01KAMMER 500.0 kV Ckt 1 line | (Any) | |
| 01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer | (Any) | |
| 01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line | (Any) | |
| 01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line | (Any) | |
| 05HYATT-05VASSEL 345.0 kV Ckt 1 line | (Any) | |
| 05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line | (Any) | |
| 05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line | (Any) |
System Reinforcement: b4000.8
- Type
- Load Flow
- TO
- APS
- RTEP ID / TO ID
- b4000.8
- Title
- Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (DVP local area to Rocky Point, roughly 4.8 miles)
- Description
- 765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
- Cost Information
- Time Estimate
- Jun 01 2029
Not Contingent Note: AG2-637 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-637 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.
| Facility | Contingency | |
|---|---|---|
| 05MOUNTN-05BELMON 765.0 kV Ckt 1 line | (Any) | |
| 01 502 J-01KAMMER 500.0 kV Ckt 1 line | (Any) | |
| 01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer | (Any) | |
| 01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line | (Any) | |
| 01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line | (Any) | |
| 05HYATT-05VASSEL 345.0 kV Ckt 1 line | (Any) | |
| 05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line | (Any) | |
| 05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line | (Any) |
System Reinforcement: b4000.4
- Type
- Load Flow
- TO
- APS
- RTEP ID / TO ID
- b4000.4
- Title
- Construct a new 765 kV switchyard - Welton Spring (Projected ISD 6/1/2029)
- Description
- 765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
- Cost Information
- Time Estimate
- Jun 01 2029
Not Contingent Note: AG2-637 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-637 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.
| Facility | Contingency | |
|---|---|---|
| 05MOUNTN-05BELMON 765.0 kV Ckt 1 line | (Any) | |
| 01 502 J-01KAMMER 500.0 kV Ckt 1 line | (Any) | |
| 01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer | (Any) | |
| 01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line | (Any) | |
| 01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line | (Any) | |
| 05HYATT-05VASSEL 345.0 kV Ckt 1 line | (Any) | |
| 05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line | (Any) | |
| 05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line | (Any) |
System Reinforcement: s2021.3
- Type
- Load Flow
- TO
- AEP
- RTEP ID / TO ID
- s2021.3
- Title
- Rebuild the ~38.5 mile Jay – Allen 138 kV line from Pennville to the juncture west of Allen station
- Description
- Rebuild the ~38.5 mile Jay – Allen 138 kV line from Pennville to the juncture west of Allen station. This line is a single circuit 138 kV line using 795 ACSR.
- Cost Information
- Time Estimate
- Dec 20 2023
Not Contingent Note: AG2-637 contributes to the loading of an overloaded facility that is being mitigated by a planned supplemental project. AG2-637 is not contingent on this supplemental project as it is already in-service.
| Facility | Contingency | |
|---|---|---|
| 05ADAM-AE2-089 TAP 138.0 kV Ckt 1 line | (Any) |
System Reinforcement: b3877.1
- Type
- Load Flow
- TO
- AEP
- RTEP ID / TO ID
- b3877.1
- Title
- Replace station conductor and switches in the 345 kV yard at Beatty
- Description
- Replace station conductor and switches in the 345 kV yard at Beatty that are currently limiting the 345 kV lines to Adkins and Chenoweth.
- Cost Information
- Time Estimate
- Jun 01 2029
Not Contingent Note: AG2-637 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-637 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.
| Facility | Contingency | |
|---|---|---|
| 05CHENOWETH-AF1-228 TP 345.0 kV Ckt 1 line | (Any) | |
| 05BEATTY-AF1-228 TP 345.0 kV Ckt 1 line | (Any) |
System Reinforcement
- Type
- Load Flow
- TO
- AEP
- RTEP ID / TO ID
- (Pending)
- Title
- AEP End Rating 245 MVA Rate B
- Description
- AEP End Rating 245 MVA Rate B
- Total Cost ($USD)
- $0
- Allocated Cost ($USD)
- $0
- Time Estimate
- TBD
Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.
| Facility | Contingency | |
|---|---|---|
| 05COLLEGE C-08COLINV 138.0 kV Ckt 1 line | (Any) |
System Reinforcement
- Type
- Load Flow
- TO
- AEP
- RTEP ID / TO ID
- (Pending) / AEP-TC2-18686
- Title
- 05MADDOX 345.0 kV to 05E LIMA 345.0 kV ckt 1 - String the 2nd conductor
- Description
- AEP owned line; string the 2nd conductor (2-bundle 954 ACSS) ~30.28 miles on the double circuit line & six wire, At East Lima station replace sub conductor & relay trip limit and at Maddox Creek replace 5.0 IPS Sch. 40 bus work, sub conductor & relay trip limit
- Total Cost ($USD)
- $48,000,000
- Allocated Cost ($USD)
- $0
- Time Estimate
- 24 to 36 Months
Potential Aggregate Contributor Note: Based on PJM cost allocation criteria, AG2-637 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-637 could receive cost allocation. Although AG2-637 may not presently have cost responsibility for this upgrade, AG2-637 is a potential Aggregate Pool Contributor.
| Facility | Contingency | |
|---|---|---|
| 05E LIMA-05MADDOX 345.0 kV Ckt 1 line | (Any) |
System Reinforcement
- Type
- Load Flow
- TO
- AEP
- RTEP ID / TO ID
- (Pending) / AEP-TC2-18687
- Title
- 05HANGRCK_RJ 765.0 kV to 05HANG R 765.0 kV ckt Z1 - Replace Equipment
- Description
- At Hanging Rock Station replace the following equipment: D1S1 PH A, D1S1 PH B, D1S1 PH C, D1S2 PH A, D1S2 PH B, D1S2 PH C, D2S1 PH A, D2S1 PH B, D2S1 PH C, D2S2 PH A, D2S2 PH B, D2S2 PH C, Jefferson Trap PH A, Jefferson Trap PH B, Jefferson Trap PH C
- Total Cost ($USD)
- $500,000
- Allocated Cost ($USD)
- $0
- Time Estimate
- 30 to 36 Months
Potential Aggregate Contributor Note: Based on PJM cost allocation criteria, AG2-637 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-637 could receive cost allocation. Although AG2-637 may not presently have cost responsibility for this upgrade, AG2-637 is a potential Aggregate Pool Contributor.
| Facility | Contingency | |
|---|---|---|
| 05HANG R-05HANGRCK_RJ 765.0 kV Ckt Z1 line | (Any) |
System Reinforcement: s3148.1
- Type
- Load Flow
- TO
- AEP
- RTEP ID / TO ID
- s3148.1 / s3148
- Title
- Reinforcement for AF1-118 TP 345 KV to 05SORENS 345 KV ckt 2
- Description
- Rebuild Sorenson-Keystone 345kV, Keystone-Desoto 345kV, Sorenson-Desoto 345kV
- Cost Information
- Time Estimate
- Jun 10 2027
Contingent Note: Although AG2-637 may not presently have cost responsibility for this upgrade, AG2-637 may need this upgrade in-service to be deliverable to the PJM system. If AG2-637 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.
| Facility | Contingency | |
|---|---|---|
| 05SORENS-AF1-118 TP 345.0 kV Ckt 2 line | (Any) |
System Reinforcement: n7683
- Type
- Load Flow
- TO
- AEP
- RTEP ID / TO ID
- n7683
- Title
- Rebuild/reconductor 3.05 mi. of the 1275 ACSR/PE 54/19 conductor with 2-954 ACSR 54/7 conductor size with a SN rating of 1410 MVA.
- Description
- Rebuild/reconductor 3.05 mi. of the 1275 ACSR/PE 54/19 conductor with 2-954 ACSR 54/7 conductor size with a SN rating of 1410 MVA.
- Total Cost ($USD)
- $18,460,000
- Allocated Cost ($USD)
- $0
- Time Estimate
- 24 to 36 Months
Potential Aggregate Contributor Note: Based on PJM cost allocation criteria, AG2-637 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-637 could receive cost allocation. Although AG2-637 may not presently have cost responsibility for this upgrade, AG2-637 is a potential Aggregate Pool Contributor.
| Facility | Contingency | |
|---|---|---|
| 05MADDOX-AG1-410 TP 345.0 kV Ckt 1 line | (Any) |
System Reinforcement
- Type
- Load Flow
- TO
- AEP
- RTEP ID / TO ID
- (Pending) / AEP-TC2-18689
- Title
- AG1-410 TP 345.0 kV to 05MADDOX 345.0 kV ckt 1 - string the 2nd circuit
- Description
- AEP owned line; string the 2nd circuit on the rebuilt double circuit line, ~ 2.85 miles of 2-bundle 1590 ACSR conductor. At Maddox Creek: Replace 345kV circuit breaker B2, subconductor, disconnect switches.
- Total Cost ($USD)
- $7,250,000
- Allocated Cost ($USD)
- $0
- Time Estimate
- 24 to 36 Months
Potential Aggregate Contributor Note: Based on PJM cost allocation criteria, AG2-637 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-637 could receive cost allocation. Although AG2-637 may not presently have cost responsibility for this upgrade, AG2-637 is a potential Aggregate Pool Contributor.
| Facility | Contingency | |
|---|---|---|
| 05MADDOX-AG1-410 TP 345.0 kV Ckt 1 line | (Any) |
System Reinforcement
- Type
- Load Flow
- TO
- AEP
- RTEP ID / TO ID
- (Pending) / AEP-TC2-18819
- Title
- 06PIERCE 345kV to 05MARQUIS 345kV ckt 1 - Replace Equipment
- Description
- At Pierce replace the following equipment: Switch 444, 446, 447, and 449, Bus, Risers, Jumpers, Wave Trap, and Line Relay At Don Marquis 345kV replace the following equipment: Circuit Breaker B2, Risers, and Line Reactor.
- Total Cost ($USD)
- $3,300,000
- Allocated Cost ($USD)
- $0
- Time Estimate
- 36 to 48 Months
Potential Aggregate Contributor Note: Based on PJM cost allocation criteria, AG2-637 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-637 could receive cost allocation. Although AG2-637 may not presently have cost responsibility for this upgrade, AG2-637 is a potential Aggregate Pool Contributor.
| Facility | Contingency | |
|---|---|---|
| 05MARQUI-06PIERCE 345.0 kV Ckt 1 line | (Any) |
System Reinforcement: s2213.9
- Type
- Load Flow
- TO
- AEP
- RTEP ID / TO ID
- s2213.9 / (Pending)
- Title
- Six-wire 71.5 miles of the Pierce-Don Marquis line. Construct 0.13 miles of line to tie into Don Marquis station.
- Description
- Six-wire 71.5 miles of the Pierce-Don Marquis line. Construct 0.13 miles of line to tie into Don Marquis station.
- Cost Information
- Time Estimate
- Jun 01 2027
Not Contingent Note: AG2-637 contributes to the loading of an overloaded facility that is being mitigated by a planned supplemental project. AG2-637 is not contingent on this supplemental project as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.
| Facility | Contingency | |
|---|---|---|
| 05MARQUI-06PIERCE 345.0 kV Ckt 1 line | (Any) |
System Reinforcement
- Type
- Load Flow
- TO
- AEP
- RTEP ID / TO ID
- (Pending) / AEP-TC2-18659
- Title
- 05MARYSVL_RS 765.0 kV to 05MARYSV 765.0 kV ckt Z1 - Replace Equipment
- Description
- Replace wave trap, CB-B, and disconnect swiches at Marysville.
- Total Cost ($USD)
- $9,500,000
- Allocated Cost ($USD)
- $0
- Time Estimate
- 24 to 36 Months
Potential Aggregate Contributor Note: Based on PJM cost allocation criteria, AG2-637 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-637 could receive cost allocation. Although AG2-637 may not presently have cost responsibility for this upgrade, AG2-637 is a potential Aggregate Pool Contributor.
| Facility | Contingency | |
|---|---|---|
| 05MARYSV-05MARYSVL_RS 765.0 kV Ckt Z1 line | (Any) |
System Reinforcement: b3878.1
- Type
- Load Flow
- TO
- AEP
- RTEP ID / TO ID
- b3878.1
- Title
- Upgrade 765 kV circuit breakers 'B' and 'B2' to 5000A 50kA breakers at Marysville Station
- Description
- Upgrade 765 kV circuit breakers 'B' and 'B2' to 5000A 50kA breakers at Marysville Station. In addition, the project will upgrade the existing wavetrap towards Sorenson.
- Cost Information
- Time Estimate
- Jun 01 2029
Not Contingent Note: AG2-637 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-637 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.
| Facility | Contingency | |
|---|---|---|
| 05MARYSV-05MARYSVL_RS 765.0 kV Ckt Z1 line | (Any) |
System Reinforcement: b3775.1
- Type
- Load Flow
- TO
- ComEd
- RTEP ID / TO ID
- b3775.1
- Title
- Swap the NIPSCO Green Acre Tap towers from the St. John-Green Acres-Olive 345 kV line
- Description
- Outside of the Green Acres substation, swap the NIPSCO Green Acre Tap towers from the St. John-Green Acres-Olive 345 kV line to the University Park N-Olive 345 kV line to create a University Park N-Green Acres-Olive and St. John-Olive 345 kV lines.
- Cost Information
- Time Estimate
- Dec 01 2026
Not Contingent Note: AG2-637 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-637 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.
| Facility | Contingency | |
|---|---|---|
| 05MADDOX-AG1-410 TP 345.0 kV Ckt 1 line | (Any) |
System Reinforcement: b3851.1
- Type
- Load Flow
- TO
- AEP
- RTEP ID / TO ID
- b3851.1 / B3851.1
- Title
- Rebuild Allen-RP Mone 345kV
- Description
- Rebuild Allen –R.P. Mone 345kV line (18.6 miles).
- Cost Information
- Time Estimate
- Jun 01 2027
Not Contingent Note: AG2-637 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-637 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.
| Facility | Contingency | |
|---|---|---|
| 05RPMONE-05ALLEN 345.0 kV Ckt 1 line | (Any) |
System Reinforcement
- Type
- Load Flow
- TO
- AEP
- RTEP ID / TO ID
- (Pending) / AEP-TC2-18707
- Title
- 05ALLEN 345.0 kV to 05RPMONE 345.0 kV ckt 1 - Replace Equipment
- Description
- At RP Mone: Replace CB B and B2 and associated disconnect switches. Replace 2 - 1700 KCM AAC station conductor. At Allen: Replace the disconnect switches for CBs C and C2 at Allen. Replace 2 - 2000 KCM AAC station conductor. B3851.1 to rebuild the Allen - RP Mone line needs to be completed. CB B is also be proposed to be replaced on another flowgate
- Total Cost ($USD)
- $5,000,000
- Allocated Cost ($USD)
- $0
- Time Estimate
- 36 to 48 Months
Potential Aggregate Contributor Note: Based on PJM cost allocation criteria, AG2-637 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-637 could receive cost allocation. Although AG2-637 may not presently have cost responsibility for this upgrade, AG2-637 is a potential Aggregate Pool Contributor.
| Facility | Contingency | |
|---|---|---|
| 05RPMONE-05ALLEN 345.0 kV Ckt 1 line | (Any) |
System Reinforcement
- Type
- Load Flow
- TO
- AEP
- RTEP ID / TO ID
- (Pending) / AEP-TC2-18732
- Title
- 05RPMONE 345kV to AG1-410 TP 345kV ckt 1 - Replace Equipment
- Description
- At R.P. Mone: Replace 345kV circuit breakers B & B1, Bus bar 4 x 3/4 Ph C, angle bus buar 4x4x1/4 Ph B, sub conductor, disconnect switches on B and B1 breakers
- Total Cost ($USD)
- $4,500,000
- Allocated Cost ($USD)
- $0
- Time Estimate
- 36 to 48 Months
Potential Aggregate Contributor Note: Based on PJM cost allocation criteria, AG2-637 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-637 could receive cost allocation. Although AG2-637 may not presently have cost responsibility for this upgrade, AG2-637 is a potential Aggregate Pool Contributor.
| Facility | Contingency | |
|---|---|---|
| 05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line | (Any) |
System Reinforcement
- Type
- Load Flow
- TO
- AEP
- RTEP ID / TO ID
- (Pending) / AEP-TC2-18693
- Title
- Greentown 765 kV to Marysville 765 kV - Greenfield Line
- Description
- Construct a new greenfield 765kV line from Greentown to Marysville (~160 miles). Install 2 new 765kV breakers at Marysville and 2 new 765kV breakers at Greentown. Install 765kV shunt reactors at both Marysville and Greentown The new 765kV line reduces equipment at Dumont to be replaced to CB A2 and switch A2S2. s3442.26 replaces Dumont 765kV CB A2 and A2S2 "CONTINGENCY 'AEP_P1-2_GREENTOWN TO MARYSVILLE 765_SRT-A' OPEN BRANCH FROM BUS 242928 TO BUS 243207 CKT 1 / 242928 05MARYSV 765 243207 05GRNTWN 765 1 END CONTINGENCY 'AEP_P4_GREENTOWN CB 765_SRT-A' OPEN BRANCH FROM BUS 242928 TO BUS 243207 CKT 1 / 242928 05MARYSV 765 243207 05GRNTWN 765 1 END CONTINGENCY 'AEP_P4_MARYSVILLE CB 765_SRT-A' OPEN BRANCH FROM BUS 242928 TO BUS 243207 CKT 1 / 242928 05MARYSV 765 243207 05GRNTWN 765 1 END"
- Total Cost ($USD)
- $1,000,000,000
- Allocated Cost ($USD)
- $0
- Time Estimate
- 72 to 120 Months
Potential Aggregate Contributor Note: Based on PJM cost allocation criteria, AG2-637 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-637 could receive cost allocation. Although AG2-637 may not presently have cost responsibility for this upgrade, AG2-637 is a potential Aggregate Pool Contributor.
| Facility | Contingency | |
|---|---|---|
| 05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer | (Any) | |
| 05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line | (Any) |
System Reinforcement
- Type
- Load Flow
- TO
- AEP
- RTEP ID / TO ID
- (Pending) / AEP-TC2-18751
- Title
- 05KYGER 345kV to 05SPORN 345kV ckt 1 - Replace Equipment and Sag Study
- Description
- Sag study Sporn - Kyger Creek line and at Kyger Creek Replace the following equipment: 2156.0 KCM ACSR (84/19), 3000A Switch, CB-BB, 2870 MCM ACSR (Bus), GCB AA, Wave Trap, Line Relay/CT, Meters, Switch 104, and Switch 10
- Total Cost ($USD)
- $5,052,000
- Allocated Cost ($USD)
- $0
- Time Estimate
- 48 to 60 Months
Potential Aggregate Contributor Note: Based on PJM cost allocation criteria, AG2-637 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-637 could receive cost allocation. Although AG2-637 may not presently have cost responsibility for this upgrade, AG2-637 is a potential Aggregate Pool Contributor.
| Facility | Contingency | |
|---|---|---|
| 05SPORN-06KYGER 345.0 kV Ckt 1 line | (Any) |
System Reinforcement: b3788.2
- Type
- Load Flow
- TO
- OVEC
- RTEP ID / TO ID
- b3788.2 / B3788.2
- Title
- Replace limiting station elements at Kyger Creek
- Description
- Upgrade existing 345 kV terminal equipment at Kyger Creek on the Kyger Creek-Sporn 345 kV line. Projected in-service date 6/1/2028 Replace OVEC-owned breaker AA risers, bus work, and breaker AA disconnect switches at OVEC-owned Kyger Creek station.
- Cost Information
- Time Estimate
- Jun 01 2028
Not Contingent Note: AG2-637 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-637 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.
| Facility | Contingency | |
|---|---|---|
| 05SPORN-06KYGER 345.0 kV Ckt 1 line | (Any) |
System Reinforcement: b3788.1
- Type
- Load Flow
- TO
- AEP
- RTEP ID / TO ID
- b3788.1 / B3788.1
- Title
- Replace limiting station elements at Kyger Creek
- Description
- Upgrade existing 345 kV terminal equipment at Kyger Creek on the Kyger Creek-Sporn 345 kV line. Projected in-service date 6/1/2028 Replace AEP-owned station takeoff riser and breaker BB risers at OVEC-owned Kyger Creek station.
- Cost Information
- Time Estimate
- Nov 18 2027
Not Contingent Note: AG2-637 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-637 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.
| Facility | Contingency | |
|---|---|---|
| 05SPORN-06KYGER 345.0 kV Ckt 1 line | (Any) |
System Reinforcement
- Type
- Load Flow
- TO
- DEOK
- RTEP ID / TO ID
- (Pending) / F4504
- Title
- DEOK New Sub and New 345kV Line from Tanner's Creek
- Description
- This Network Upgrade will be joint effort between DEOK & AEP to mitigate the Miami Fort - Tanner's Creek 345kV violations. DEOK Scope of Work: - DEOK will construct a new 5-breaker Ring Bus, 345kV Switching Station in Northern Kentucky called 'Idlewild'(Lat: 39° 5'15.11"N, Long: 84°49'10.14"W) - DEOK will loop the Tanner's Creek (AEP) - East Bend (DEOK) and Miami Fort (DEOK) - Terminal (DEOK) 345kV circuits into Idlewild Substation - In order to loop the Miami Fort - Terminal circuit into Idlewild Substation, DEOK will retire ~0.68 miles of the Miami Fort - Terminal circuit and add ~0.95 miles of new 345kV conductor (954ACSR 45x7, 2cond/ph, 100C). The new conductor will be built on existing DEOK easement. - DEOK will construct a new 345kV circuit from Idlewild substation to a pole that is just outside AEP's Tanner's Creek Substation. This circuit will be ~2.48 miles long with (1) Ohio River Crossing. The new 345kV circuit will be built will 954ACSS/TW, 2-conductor/phase, 200C conductor. Part of the new 345kV circuit will be built on existing DEOK easement, but DEOK will need to obtain ~1.0 mile of new easement. Line ownership for this new circuit will change at the tower which is just outside AEP's Tanner's Creek Substation in Lawrenceburg, Indiana.
- Total Cost ($USD)
- $72,000,000
- Allocated Cost ($USD)
- $0
- Time Estimate
- 72 to 84 Months
Potential Aggregate Contributor Note: Based on PJM cost allocation criteria, AG2-637 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-637 could receive cost allocation. Although AG2-637 may not presently have cost responsibility for this upgrade, AG2-637 is a potential Aggregate Pool Contributor.
| Facility | Contingency | |
|---|---|---|
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line | AEP_P1-2_#7441_100545_SRT-A | |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line | AEP_P4_#7445_05MARYSV 765_B_SRT-A | |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line | AEP_P4_#7441_05SORENS 765_J1_SRT-A | |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line | AEP_P2-2_#9456_06DEARB1 345_1_SRT-A | |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line | AEP_P7-1_#485___SRT-A | |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line | AEP_P4_#7446_05MARYSV 765_B2_SRT-A | |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line | DEOK_P_4519BUFFCLIFTYPIERCEDEAR1OVEC_SRT-A | |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line | AEP_P4_#9456_06DEARB1 345_DC_SRT-A | |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line | DEOK_P4_1579_EASTBEND_SRT-A | |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line | (Any) |
System Reinforcement
- Type
- Load Flow
- TO
- AEP
- RTEP ID / TO ID
- (Pending) / AEP-TC2-18821
- Title
- AEP Reinforcements for DEOK New Sub and New 345kV Line from Tanner's Creek
- Description
- AEP Scope of Work: At Tanners Creek station- install a 345 kV circuit breaker "T", relocate Lawrenceburg #1 345 kV line (between breakers T and T2), relocate Miami Fort 345 kV line (between breakers T and T1), relocate formerly East Bend 345 kV line (to Idlewild Duke station) (between breakers S and S1), and install new Tanners Creek - Idlewild 345 kV line #2 (between breakers R and R1), ~0.35 miles of AEP install and ~2.48 miles of Duke install.
- Total Cost ($USD)
- $6,700,000
- Allocated Cost ($USD)
- $0
- Time Estimate
- 72 to 84 Months
Potential Aggregate Contributor Note: Based on PJM cost allocation criteria, AG2-637 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-637 could receive cost allocation. Although AG2-637 may not presently have cost responsibility for this upgrade, AG2-637 is a potential Aggregate Pool Contributor.
| Facility | Contingency | |
|---|---|---|
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line | (Any) |
System Reinforcement: n9680.0
- Type
- Load Flow
- TO
- OVEC
- RTEP ID / TO ID
- n9680.0 / OVEC0001a
- Title
- Sag mitigations to bring the Dearborn – Pierce 345 kV line up to a maximum operating temperature of 311° F
- Description
- •Remove and replace sixteen (16) existing double circuit towers with taller double circuit custom steel poles. (Towers 11, 14, 45, 47, 52, 57, 59, 61, 63, 66, 67, 71, 77, 84, 91, and 96) •Remove and replace two (2) existing river crossing lattice towers with taller lattice structures. (Towers 2 and 140)
- Total Cost ($USD)
- $24,006,000
- Allocated Cost ($USD)
- $0
- Time Estimate
- 38 Months
Potential Aggregate Contributor Note: Based on PJM cost allocation criteria, AG2-637 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-637 could receive cost allocation. Although AG2-637 may not presently have cost responsibility for this upgrade, AG2-637 is a potential Aggregate Pool Contributor.
| Facility | Contingency | |
|---|---|---|
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line | (Any) |
System Reinforcement: b4000.351
- Type
- Load Flow
- TO
- Dominion
- RTEP ID / TO ID
- b4000.351
- Title
- Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
- Description
- Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
- Cost Information
- Time Estimate
- Sep 16 2030
Not Contingent Note: AG2-637 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-637 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.
| Facility | Contingency | |
|---|---|---|
| 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line | (Any) |
System Reinforcement: b4000.326
- Type
- Load Flow
- TO
- Dominion
- RTEP ID / TO ID
- b4000.326
- Title
- At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
- Description
- At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
- Cost Information
- Time Estimate
- Feb 24 2029
Not Contingent Note: AG2-637 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-637 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.
| Facility | Contingency | |
|---|---|---|
| 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line | (Any) |
System Reinforcement: b4000.350
- Type
- Load Flow
- TO
- Dominion
- RTEP ID / TO ID
- b4000.350
- Title
- Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
- Description
- Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
- Cost Information
- Time Estimate
- Sep 16 2030
Not Contingent Note: AG2-637 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-637 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.
| Facility | Contingency | |
|---|---|---|
| 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line | (Any) |
System Reinforcement: b4000.342
- Type
- Load Flow
- TO
- Dominion
- RTEP ID / TO ID
- b4000.342
- Title
- Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
- Description
- Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
- Cost Information
- Time Estimate
- Jul 13 2029
Not Contingent Note: AG2-637 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-637 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.
| Facility | Contingency | |
|---|---|---|
| 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line | (Any) |
System Reinforcement: b4000.355
- Type
- Load Flow
- TO
- Dominion
- RTEP ID / TO ID
- b4000.355
- Title
- Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
- Description
- Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
- Cost Information
- Time Estimate
- Jun 01 2029
Not Contingent Note: AG2-637 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-637 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.
| Facility | Contingency | |
|---|---|---|
| 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line | (Any) |
System Reinforcement: b4000.341
- Type
- Load Flow
- TO
- Dominion
- RTEP ID / TO ID
- b4000.341
- Title
- Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.
- Description
- Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV substation and extend approximately 0.2 miles of conductor to fly-over the site.
- Cost Information
- Time Estimate
- Jul 13 2029
Not Contingent Note: AG2-637 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-637 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.
| Facility | Contingency | |
|---|---|---|
| 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line | (Any) |
System Reinforcement: b4000.327
- Type
- Load Flow
- TO
- Dominion
- RTEP ID / TO ID
- b4000.327
- Title
- Upgrade/install equipment at Ladysmith Substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230 kV strings of breaker and a half scheme.
- Description
- Upgrade/install equipment at Ladysmith substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230kV strings of breaker and a half scheme.
- Cost Information
- Time Estimate
- Feb 24 2029
Not Contingent Note: AG2-637 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-637 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.
| Facility | Contingency | |
|---|---|---|
| 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line | (Any) |
System Reinforcement: b4000.348
- Type
- Load Flow
- TO
- Dominion
- RTEP ID / TO ID
- b4000.348
- Title
- Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.
- Description
- Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers. A new redundant breaker ring will be added at Kraken to accommodate the new 500kV line from North Anna to Kraken.
- Cost Information
- Time Estimate
- Jun 01 2029
Not Contingent Note: AG2-637 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-637 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.
| Facility | Contingency | |
|---|---|---|
| 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line | (Any) |
System Reinforcement: b4000.357
- Type
- Load Flow
- TO
- Dominion
- RTEP ID / TO ID
- b4000.357
- Title
- Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
- Description
- Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
- Cost Information
- Time Estimate
- Jun 01 2029
Not Contingent Note: AG2-637 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-637 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.
| Facility | Contingency | |
|---|---|---|
| 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line | (Any) |
System Reinforcement: b4000.352
- Type
- Load Flow
- TO
- Dominion
- RTEP ID / TO ID
- b4000.352
- Title
- Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
- Description
- Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
- Cost Information
- Time Estimate
- Sep 16 2030
Not Contingent Note: AG2-637 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-637 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.
| Facility | Contingency | |
|---|---|---|
| 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line | (Any) |
System Reinforcement: b4000.349
- Type
- Load Flow
- TO
- Dominion
- RTEP ID / TO ID
- b4000.349
- Title
- Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
- Description
- Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
- Cost Information
- Time Estimate
- Sep 16 2030
Not Contingent Note: AG2-637 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-637 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.
| Facility | Contingency | |
|---|---|---|
| 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line | (Any) |
System Reinforcement: b4000.345
- Type
- Load Flow
- TO
- Dominion
- RTEP ID / TO ID
- b4000.345
- Title
- Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
- Description
- Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
- Cost Information
- Time Estimate
- Sep 16 2030
Not Contingent Note: AG2-637 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-637 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.
| Facility | Contingency | |
|---|---|---|
| 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line | (Any) |
System Reinforcement: b4000.356
- Type
- Load Flow
- TO
- Dominion
- RTEP ID / TO ID
- b4000.356
- Title
- Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
- Description
- Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
- Cost Information
- Time Estimate
- Jun 01 2029
Not Contingent Note: AG2-637 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-637 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.
| Facility | Contingency | |
|---|---|---|
| 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line | (Any) |
System Reinforcement: b4000.344
- Type
- Load Flow
- TO
- Dominion
- RTEP ID / TO ID
- b4000.344
- Title
- Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
- Description
- Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
- Cost Information
- Time Estimate
- Sep 16 2030
Not Contingent Note: AG2-637 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-637 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.
| Facility | Contingency | |
|---|---|---|
| 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line | (Any) |
System Reinforcement: b4000.346
- Type
- Load Flow
- TO
- Dominion
- RTEP ID / TO ID
- b4000.346
- Title
- Cut-in 500kV line from Kraken substation into Yeat substation
- Description
- Cut-in 500kV line from Kraken substation into Yeat substation
- Cost Information
- Time Estimate
- Jun 01 2029
Not Contingent Note: AG2-637 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-637 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.
| Facility | Contingency | |
|---|---|---|
| 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line | (Any) |
System Reinforcement: b4000.325
- Type
- Load Flow
- TO
- Dominion
- RTEP ID / TO ID
- b4000.325
- Title
- Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
- Description
- Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
- Cost Information
- Time Estimate
- Feb 24 2029
Not Contingent Note: AG2-637 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-637 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.
| Facility | Contingency | |
|---|---|---|
| 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line | (Any) |