AG2-646 Phase I Study Report

v1.00 released 2025-10-29 20:42

Chesterfield 230 kV

200.0 MW Capacity / 200.0 MW Energy

Introduction

This Phase I System Impact Study Report (PH1) has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, sections 307 and 308 for New Service Requests (projects) in Transition Cycle 2. The Project Developer/Eligible Customer (developer) is Pine Tree Power Management LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is Virginia Electric and Power Company (d/b/a Dominion Energy Virginia).

Preface

The Phase I System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle executive summary format and (ii) an individual project-level basis. The Phase I System Impact Study Results (for both the executive summary and individual reports) will be publicly available on PJM’s website. Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.3, PJM takes the following actions during the Phase I System Impact Study:
  1. PJM studies each New Service Request on a summer peak, winter peak and light load RTEP base case study. The case year is dependent on the new services cycle under study. PJM will identify the base case year to be used in the study of a specific cycle on its website.
  2. PJM will only perform load flow analysis during the Phase I System Impact Study.
  3. In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with Affected System impacts and provides each Affected System Operator with a list of New Service Request in the Cycle with potential impacts to their respective system.
  4. PJM will create both the short circuit and stability base cases to be used in the Phase II System Impact Study.
  5. The Phase I System Impact Study results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.
The Transmission Owner takes the following actions during the Phase I System Impact Study:
  1. Identify required Interconnection Facilities to accommodate the New Service Request.
  2. Identify required Network Upgrades to mitigate system violations from the Phase I System Impact Study.
  3. Provide planning-level preliminary estimates of Interconnection Facilities and Network Upgrades including scope, cost and elapsed time to complete the work.

Decision Point I Requirements

At the close of Phase I System Impact Study, PJM will initiate Decision Point I (DP1). During DP1, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.A.1. Additional information on these elements is available in PJM Manual 14H sections 4.4, 6, and 7.

Allowable project modifications at Decision Point I are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

General

The Project Developer has proposed a Storage facility located in the Virginia Electric and Power Company (d/b/a Dominion Energy Virginia) zone — Chesterfield County, Virginia. The installed facilities will have a total capability of 200.0 MW with 200.0 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AG2-646
Project Name:
Chesterfield 230 kV
Project Developer Name:
Pine Tree Power Management LLC
State:
Virginia
County:
Chesterfield
Transmission Owner:
Virginia Electric and Power Company (d/b/a Dominion Energy Virginia)
MFO:
200.0
MWE:
200.0
MWC:
200.0
Battery Storage Specification:
2000.0 MWh, 10.0-hr class
Grid Charging:
Yes
Fuel Type:
Storage
Basecase Study Year:
2028

Physical Interconnection Facility Study

Physical Interconnection Facilities Study is not performed as part of the Phase I System Impact Study. Physical Interconnection Facilities Study will commence in the Phase II System Impact Study.

Point of Interconnection

AG2-646 will interconnect on the Virginia Electric and Power Company (d/b/a Dominion Energy Virginia) transmission system at the Chesterfield 230 kV Substation.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In the Phase I SIS, the costs shown are subject to change as a result of a facility study performed by the TO during the Phase II or Phase III System Impact Study.

Based on the Phase I SIS results, the AG2-646 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit are also shown below.

Cost Summary
DescriptionCost Allocated to AG2-646Cost Subject to Readiness*
Transmission Owner Interconnection Facilities (TOIF)$3,500,000$0
Other Scope$0$0
Option To Build Oversight$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$0$0
Network Upgrades$7,000,000$7,000,000
System Reliability Network Upgrades
Steady State Thermal & Voltage (SP & LL)$104,397,510$104,397,510
Transient Stability$0$0
Short Circuit$0$0
Transmission Owner Analysis
SubRegional$0$0
Distribution$0$0
Affected System Reinforcements
AFS - PJM Violatons$0$0
AFS - Non-PJM Violations$0$0
Total$114,897,510$111,397,510

* Contributes to calculation for Readiness Deposit #2 (RD2). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim deliverability study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 309 (Decision Point I) A.1.a.i and PJM Manual 14H, section 6.2, Readiness Deposit #2 (RD2) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point I (DP1), the Project Developer or Eligible Customer is required to submit Readiness Deposit #2, which is calculated as 10% of cost allocation for required Phase I Network Upgrades minus Readiness Deposit #1.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Readiness Deposit #2 Due for Project AG2-646

Readiness Deposit #2 has been calculated for the project based on the Phase I System Impact Study results and is shown in the table below. This Readiness Deposit #2 must be provided at Decision Point I through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit
Project ID10% of cost allocation for Phase I Network UpgradesReadiness Deposit #1 Received (RD1)Readiness Deposit #2 (RD2) for AG2-646 Project due at DP1
ABA - B
AG2-646$11,139,751$800,000$10,339,751

Note: Failure to provide an acceptable form of Readiness Deposit #2 by the end of Decision Point I will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Transmission Owner Interconnection Facilities
RTEP IDDescriptionTotal Cost ($USD)Allocated Cost ($USD)
(Pending)Install the Point of Change in Ownership (PCO) disconnect switch, the overhead line conductor from the PCO to the bus position that serves as the Point of Interconnection (POI), as well as any metering and associated protection equipment.$3,500,000 $3,500,000
Network Upgrades
RTEP IDDescriptionTotal Cost ($USD)Allocated Cost ($USD)
(Pending)Add two (2) new 230 kV breakers to the existing Chesterfield 230 kV Substation. Additional substation modification/expansion cost may be required after detailed design.$7,000,000 $7,000,000

Based on the scope of work for the Interconnection Facilities, it is expected to take a range of 46 to 50 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

The schedule for any required Network Impact Reinforcements will be more clearly identified in the Phase II and Phase III System Impact Studies.

Transmission Owner Analysis

PJM performed a power flow analysis of the transmission system using a 2028 load flow model and the results were verified by Dominion.

 

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. Dominion interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AG2-646 was evaluated as a 200.0 MW (200.0 MW Capacity) injection in the Dominion area.

AG2-646 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 200.0 MW (200.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2DVP
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC122.85 %559.3B687.0911.22
GD2DVP
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line
DVP_P1-2: LN 557_SRT-S
SingleAC103.79 %559.3B580.4710.6
GD2DVP
6BIRCHWD-6FINES 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC138.81 %548.02B760.6811.22
GD2DVP
6BIRCHWD-6FINES 230.0 kV Ckt 1 line
DVP_P1-2: LN 557_SRT-S
SingleAC119.94 %548.02B657.2810.6
GD2DVP
6CHCKAHM-6ELKO 230.0 kV Ckt 1 line
DVP_P1-2: LN 557_SRT-S
SingleAC110.39 %678.68B749.1818.11
GD2DVP
6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer
DVP_P4-2: 56702_SRT-A
BreakerAC125.13 %1107.0C1385.2436.0
GD2DVP
6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer
DVP_P1-2: LN 567_SRT-A
SingleAC119.77 %935.39B1120.3136.0
GD2DVP
6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer
DVP_P4-2: G2T567_SRT-A
BreakerAC117.33 %1107.0C1298.8836.12
GD2DVP
6CHESTF A-3CHESTFLD 230.0/115.0 kV Ckt 1 transformer
DVP_P4-2: 208T287_SRT-A
BreakerAC120.86 %284.0C343.2333.33
GD2DVP
6CHESTF A-3CHESTFLD 230.0/115.0 kV Ckt 1 transformer
DVP_P1-2: LN 208_SRT-A
SingleAC104.74 %250.04B261.8925.25
GD2DVP
6CHESTF A-3CHESTFLD 230.0/115.0 kV Ckt 1 transformer
DVP_P1-2: LN 211_SRT-S
SingleAC103.28 %250.04B258.2421.59
GD2DVP
6CHESTF A-3CHESTFLD 230.0/115.0 kV Ckt 1 transformer
DVP_P4-2: 211T2124_SRT-A
BreakerAC101.39 %284.0C287.9423.38
GD2DVP
6CHESTF A-3CHESTFLD 230.0/115.0 kV Ckt 1 transformer
DVP_P7-1: LN 208-259_SRT-S
TowerAC100.44 %284.0C285.2525.8
GD2DVP
6CHESTF A-6CHCKAHM 230.0 kV Ckt 1 line
DVP_P1-2: LN 2049_SRT-A
SingleAC108.69 %584.68B635.4762.79
GD2DVP
6CHESTF A-6CHCKAHM 230.0 kV Ckt 1 line
DVP_P1-2: LN 2050_SRT-S
SingleAC104.83 %584.68B612.962.79
GD2DVP
6CHESTF A-6IRON208 230.0 kV Ckt 1 line
DVP_P1-2: LN 557_SRT-S
SingleAC111.61 %663.64B740.7145.73
GD2DVP
6CHESTF A-6IRON208 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S
SingleAC108.5 %663.64B720.0542.99
GD2DVP
6CHESTF A-6IRON208 230.0 kV Ckt 1 line
DVP_P4-2: H2T557_SRT-S
BreakerAC102.22 %811.0C828.9945.09
GD2DVP
6COMORN-6BIRCHWD 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC124.42 %548.02B681.8511.22
GD2DVP
6COMORN-6BIRCHWD 230.0 kV Ckt 1 line
DVP_P1-2: LN 557_SRT-S
SingleAC104.98 %548.02B575.310.6
GD2DVP
6FINES-6FREDBRG 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC138.73 %548.02B760.2411.22
GD2DVP
6FINES-6FREDBRG 230.0 kV Ckt 1 line
DVP_P1-2: LN 557_SRT-S
SingleAC119.84 %548.02B656.7310.6
GD2DVP
6IRON208-6SOUWEST 230.0 kV Ckt 1 line
DVP_P1-2: LN 557_SRT-S
SingleAC103.96 %663.64B689.9245.73
GD2DVP
6IRON208-6SOUWEST 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S
SingleAC100.72 %663.64B668.4442.99
GD2DVP
6NORNECK-6SANDERS 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC115.31 %571.52B659.0411.32
GD2DVP
6OAKGROV-AF1-114 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC111.12 %571.52B635.0511.29
GD2DVP
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC113.11 %571.52B646.4411.3
GD2DVP
6WESTMOR-AG2-469 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC111.62 %571.52B637.9611.29
GD2DVP
AF1-114 TP-6DAHLGREN 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC118.84 %571.52B679.211.22
GD2DVP
AF2-013 TP-6ARNOLDS 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC127.21 %559.3B711.4911.22
GD2DVP
AF2-013 TP-6ARNOLDS 230.0 kV Ckt 1 line
DVP_P1-2: LN 557_SRT-S
SingleAC108.1 %559.3B604.610.6
GD2DVP
AG2-469 TP-6OAKGROV 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC115.13 %571.52B657.9711.29

Details for 6ARNOLDS-6COMORN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:122.85 %
Rating:559.3 MVA
Rating Type:B
MVA to Mitigate:687.09
MW Contribution:11.22
Bus #Bus NameTypeMW Contribution
3141316ARNOLDS
50/50
2.018
3150351NORNECKC2
50/50
3.006
970575AG2-366 GEN
50/50
3.66
315749AE2-041 GEN
50/50
4.946
3141843SHACKLE
50/50
0.746
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3150921YORKTN3
50/50
1.929
3144216WINCHST
50/50
0.279
3151161SURRY 1
50/50
2.166
970737AG2-469 GEN
Solar/Wind Harmer
20.178
3141906WESTMOR
Solar/Wind Harmer
0.165
316404AE1-155 C
Solar/Wind Harmer
0.054
970009AG2-005 GEN
Solar/Wind Harmer
1.637
962971AG1-146 GEN
Solar/Wind Harmer
3.294
316156AD2-030 GEN
Solar/Wind Harmer
0.109
3141873WAN 176
Solar/Wind Harmer
2.61
316280AD1-041 GEN
Solar/Wind Harmer
0.003
3141766HARMONY
Solar/Wind Harmer
1.855
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316382AG1-145 C
Solar/Wind Harmer
0.001
3142946ENON
Solar/Wind Harmer
0.023
970293AG2-193 GEN
Solar/Wind Harmer
0.668
3142416OLDCHRC
Solar/Wind Harmer
0.555
3151221GRAVEL6
Adder
4.099
3151171GRAVELC
Adder
0.789
957191AF2-013 GEN
50/50
65.713
3150341NORNECKC1
50/50
3.105
3150341NORNECKC1
50/50
3.08
963611AG1-210 GEN
50/50
0.994
3150621CHESTS7
50/50
0.184
316077AC2-138 C
Solar/Wind Harmer
0.001
958261AF2-120 GEN
Solar/Wind Harmer
7.962
316075AC2-137 C
Solar/Wind Harmer
0.019
3142946ENON
Solar/Wind Harmer
0.007
3150351NORNECKC2
50/50
2.956
966661AG1-536 GEN
50/50
6.849
3141843SHACKLE
50/50
0.746
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
971353AH1-157 GEN
50/50
7.408
970017AG2-010 GEN
50/50
4.699
3150641CHESTS8
50/50
0.203
944631AF1-128 GEN
50/50
31.925
972135AH1-637 GEN
Solar/Wind Harmer
4.389
316337AD2-073 GEN
Solar/Wind Harmer
0.299
3141726DUNNSVL
Solar/Wind Harmer
1.044
962861AG1-135 GEN
Solar/Wind Harmer
7.523
3138133OCRAN
Solar/Wind Harmer
0.103
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.363
3142433PROV 92
Solar/Wind Harmer
0.428
971317AH1-138 GEN
Solar/Wind Harmer
0.613
316159AE1-175 C
Solar/Wind Harmer
0.065
3138126ROCKLANDING
Solar/Wind Harmer
0.032
3142416OLDCHRC
Solar/Wind Harmer
0.149
3142416OLDCHRC
Solar/Wind Harmer
0.057
3151171GRAVELC
Adder
0.6
315759AF1-018 GEN
50/50
4.946
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3150611CHESTG7
50/50
0.401
3150631CHESTG8
50/50
0.394
971047AG2-646 GEN
50/50
11.221
972263AH1-716 GEN
50/50
32.871
944491AF1-114 GEN
Solar/Wind Harmer
0.002
316223AC1-118
Solar/Wind Harmer
0.296
3141813NORNECK
Solar/Wind Harmer
0.279
970327AG2-215 GEN
Solar/Wind Harmer
7.194
962981AG1-147 GEN
Solar/Wind Harmer
7.685
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.073
3138133OCRAN
Solar/Wind Harmer
0.051
3141913WHIT STONE
Solar/Wind Harmer
0.166
3141873WAN 176
Solar/Wind Harmer
0.029
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
4.081
316314AB2-024 C
Solar/Wind Harmer
0
3143873LANEXA
Solar/Wind Harmer
0.075
3138283WHITEMARSH
Solar/Wind Harmer
0.025
971167AH1-042 GEN
Solar/Wind Harmer
9.122
315976AC1-164 GENA
Solar/Wind Harmer
8.292
316169AC1-164_GENC
Solar/Wind Harmer
7.163
315975AC1-164 GENB
Solar/Wind Harmer
0.245
316312AB1-027
Solar/Wind Harmer
0.102
972265AH1-717 GEN
Adder
4.377
3151201GRAVEL4
Adder
4.104
3151191GRAVEL3
Adder
4.052
3151211GRAVEL5
Adder
4.052
3141426STAFORD
Solar/Wind Helper
0.031
CPLELTFEXP_CPLE->PJM
CLTF
1.997
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.895
NYPJM->LTFIMP_NY
CLTF
0.564
LGEELTFEXP_LGEE->PJM
CLTF
0.274
WECLTFEXP_WEC->PJM
CLTF
0.137
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.711
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.577
MECLTFEXP_MEC->PJM
CLTF
0.732
SIGELTFEXP_SIGE->PJM
CLTF
0.022
LAGNLTFEXP_LAGN->PJM
CLTF
1.483
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.388
TVALTFEXP_TVA->PJM
CLTF
0.749

Details for 6ARNOLDS-6COMORN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 557_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.79 %
Rating:559.3 MVA
Rating Type:B
MVA to Mitigate:580.47
MW Contribution:10.6
Bus #Bus NameTypeMW Contribution
315759AF1-018 GEN
50/50
4.976
3142433PROV 92
50/50
0.218
3142433PROV 92
50/50
0.218
972263AH1-716 GEN
50/50
35.649
3150611CHESTG7
50/50
0.379
3150631CHESTG8
50/50
0.372
971047AG2-646 GEN
50/50
10.599
944491AF1-114 GEN
Solar/Wind Harmer
0.002
316223AC1-118
Solar/Wind Harmer
0.297
3141813NORNECK
Solar/Wind Harmer
0.28
970327AG2-215 GEN
Solar/Wind Harmer
7.232
962981AG1-147 GEN
Solar/Wind Harmer
7.729
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.074
3138133OCRAN
Solar/Wind Harmer
0.052
3141913WHIT STONE
Solar/Wind Harmer
0.168
3141873WAN 176
Solar/Wind Harmer
0.03
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
4.097
316314AB2-024 C
Solar/Wind Harmer
0
3143873LANEXA
Solar/Wind Harmer
0.075
3138283WHITEMARSH
Solar/Wind Harmer
0.025
971167AH1-042 GEN
Solar/Wind Harmer
8.942
315976AC1-164 GENA
Solar/Wind Harmer
8.275
316169AC1-164_GENC
Solar/Wind Harmer
7.149
315975AC1-164 GENB
Solar/Wind Harmer
0.245
972265AH1-717 GEN
Adder
4.429
3151201GRAVEL4
Adder
4.152
3151191GRAVEL3
Adder
4.099
3151211GRAVEL5
Adder
4.099
3141426STAFORD
Solar/Wind Helper
0.029
3141316ARNOLDS
50/50
2.026
3150351NORNECKC2
50/50
3.02
970575AG2-366 GEN
50/50
3.68
315749AE2-041 GEN
50/50
4.976
3141843SHACKLE
50/50
0.749
3142433PROV 92
50/50
0.218
3142433PROV 92
50/50
0.218
3150921YORKTN3
50/50
2.003
3144216WINCHST
50/50
0.289
3151161SURRY 1
50/50
2.191
970737AG2-469 GEN
Solar/Wind Harmer
20.26
3141906WESTMOR
Solar/Wind Harmer
0.165
316404AE1-155 C
Solar/Wind Harmer
0.054
970009AG2-005 GEN
Solar/Wind Harmer
1.646
962971AG1-146 GEN
Solar/Wind Harmer
3.312
316156AD2-030 GEN
Solar/Wind Harmer
0.109
3141873WAN 176
Solar/Wind Harmer
2.629
316280AD1-041 GEN
Solar/Wind Harmer
0.003
3141766HARMONY
Solar/Wind Harmer
1.866
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316382AG1-145 C
Solar/Wind Harmer
0.001
3142946ENON
Solar/Wind Harmer
0.022
3151221GRAVEL6
Adder
4.147
3151171GRAVELC
Adder
0.798
970293AG2-193 GEN
Solar/Wind Harmer
0.603
3150351NORNECKC2
50/50
2.97
966661AG1-536 GEN
50/50
6.884
3141843SHACKLE
50/50
0.749
3142433PROV 92
50/50
0.218
3142433PROV 92
50/50
0.218
971353AH1-157 GEN
50/50
7.642
970017AG2-010 GEN
50/50
4.875
3150641CHESTS8
50/50
0.192
944631AF1-128 GEN
50/50
30.156
3152331SURRY 2
50/50
2.455
972135AH1-637 GEN
Solar/Wind Harmer
4.407
316337AD2-073 GEN
Solar/Wind Harmer
0.3
3141726DUNNSVL
Solar/Wind Harmer
1.049
962861AG1-135 GEN
Solar/Wind Harmer
7.561
3138133OCRAN
Solar/Wind Harmer
0.104
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.365
3142433PROV 92
Solar/Wind Harmer
0.422
971317AH1-138 GEN
Solar/Wind Harmer
0.633
316159AE1-175 C
Solar/Wind Harmer
0.067
3138126ROCKLANDING
Solar/Wind Harmer
0.034
3151171GRAVELC
Adder
0.607
957191AF2-013 GEN
50/50
65.968
3150341NORNECKC1
50/50
3.119
3150341NORNECKC1
50/50
3.094
963611AG1-210 GEN
50/50
0.998
3150621CHESTS7
50/50
0.174
316077AC2-138 C
Solar/Wind Harmer
0.001
958261AF2-120 GEN
Solar/Wind Harmer
8.003
316075AC2-137 C
Solar/Wind Harmer
0.018
3142946ENON
Solar/Wind Harmer
0.007
CPLELTFEXP_CPLE->PJM
CLTF
1.912
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.152
NYPJM->LTFIMP_NY
CLTF
0.465
LGEELTFEXP_LGEE->PJM
CLTF
0.185
WECLTFEXP_WEC->PJM
CLTF
0.092
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.061
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.057
MECLTFEXP_MEC->PJM
CLTF
0.525
SIGELTFEXP_SIGE->PJM
CLTF
0.016
LAGNLTFEXP_LAGN->PJM
CLTF
1.213
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.047
TVALTFEXP_TVA->PJM
CLTF
0.609

Details for 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BIRCHWD-6FINES 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:138.81 %
Rating:548.02 MVA
Rating Type:B
MVA to Mitigate:760.68
MW Contribution:11.22
Bus #Bus NameTypeMW Contribution
3150331BIRCHWDA
50/50
158.356
3141316ARNOLDS
50/50
2.018
3150351NORNECKC2
50/50
3.006
970575AG2-366 GEN
50/50
3.66
315749AE2-041 GEN
50/50
4.946
3141843SHACKLE
50/50
0.746
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3150921YORKTN3
50/50
1.929
3144216WINCHST
50/50
0.279
3151161SURRY 1
50/50
2.166
970737AG2-469 GEN
Solar/Wind Harmer
20.178
3141906WESTMOR
Solar/Wind Harmer
0.165
316404AE1-155 C
Solar/Wind Harmer
0.054
970009AG2-005 GEN
Solar/Wind Harmer
1.637
962971AG1-146 GEN
Solar/Wind Harmer
3.294
316156AD2-030 GEN
Solar/Wind Harmer
0.109
3141873WAN 176
Solar/Wind Harmer
2.61
316280AD1-041 GEN
Solar/Wind Harmer
0.003
3141766HARMONY
Solar/Wind Harmer
1.855
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316382AG1-145 C
Solar/Wind Harmer
0.001
3142946ENON
Solar/Wind Harmer
0.023
970293AG2-193 GEN
Solar/Wind Harmer
0.668
3142416OLDCHRC
Solar/Wind Harmer
0.555
3151221GRAVEL6
Adder
4.099
3151171GRAVELC
Adder
0.789
957191AF2-013 GEN
50/50
65.713
3150341NORNECKC1
50/50
3.105
3150341NORNECKC1
50/50
3.08
963611AG1-210 GEN
50/50
0.994
3150621CHESTS7
50/50
0.184
316077AC2-138 C
Solar/Wind Harmer
0.001
958261AF2-120 GEN
Solar/Wind Harmer
7.962
316075AC2-137 C
Solar/Wind Harmer
0.019
3142946ENON
Solar/Wind Harmer
0.007
3150351NORNECKC2
50/50
2.956
966661AG1-536 GEN
50/50
6.849
3141843SHACKLE
50/50
0.746
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
971353AH1-157 GEN
50/50
7.408
970017AG2-010 GEN
50/50
4.699
3150641CHESTS8
50/50
0.203
944631AF1-128 GEN
50/50
31.925
972135AH1-637 GEN
Solar/Wind Harmer
4.389
316337AD2-073 GEN
Solar/Wind Harmer
0.299
3141726DUNNSVL
Solar/Wind Harmer
1.044
962861AG1-135 GEN
Solar/Wind Harmer
7.523
3138133OCRAN
Solar/Wind Harmer
0.103
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.363
3142433PROV 92
Solar/Wind Harmer
0.428
971317AH1-138 GEN
Solar/Wind Harmer
0.613
316159AE1-175 C
Solar/Wind Harmer
0.065
3138126ROCKLANDING
Solar/Wind Harmer
0.032
3142416OLDCHRC
Solar/Wind Harmer
0.149
3142416OLDCHRC
Solar/Wind Harmer
0.057
3151171GRAVELC
Adder
0.6
315759AF1-018 GEN
50/50
4.946
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3150611CHESTG7
50/50
0.401
3150631CHESTG8
50/50
0.394
971047AG2-646 GEN
50/50
11.221
972263AH1-716 GEN
50/50
32.871
944491AF1-114 GEN
Solar/Wind Harmer
0.002
316223AC1-118
Solar/Wind Harmer
0.296
3141813NORNECK
Solar/Wind Harmer
0.279
970327AG2-215 GEN
Solar/Wind Harmer
7.194
962981AG1-147 GEN
Solar/Wind Harmer
7.685
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.073
3138133OCRAN
Solar/Wind Harmer
0.051
3141913WHIT STONE
Solar/Wind Harmer
0.166
3141873WAN 176
Solar/Wind Harmer
0.029
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
4.081
316314AB2-024 C
Solar/Wind Harmer
0
3143873LANEXA
Solar/Wind Harmer
0.075
3138283WHITEMARSH
Solar/Wind Harmer
0.025
971167AH1-042 GEN
Solar/Wind Harmer
9.122
315976AC1-164 GENA
Solar/Wind Harmer
8.292
316169AC1-164_GENC
Solar/Wind Harmer
7.163
315975AC1-164 GENB
Solar/Wind Harmer
0.245
316312AB1-027
Solar/Wind Harmer
0.102
972265AH1-717 GEN
Adder
4.377
3151201GRAVEL4
Adder
4.104
3151191GRAVEL3
Adder
4.052
3151211GRAVEL5
Adder
4.052
3141426STAFORD
Solar/Wind Helper
0.031
CPLELTFEXP_CPLE->PJM
CLTF
1.997
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.895
NYPJM->LTFIMP_NY
CLTF
0.564
LGEELTFEXP_LGEE->PJM
CLTF
0.274
WECLTFEXP_WEC->PJM
CLTF
0.137
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.711
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.577
MECLTFEXP_MEC->PJM
CLTF
0.732
SIGELTFEXP_SIGE->PJM
CLTF
0.022
LAGNLTFEXP_LAGN->PJM
CLTF
1.483
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.388
TVALTFEXP_TVA->PJM
CLTF
0.749

Details for 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BIRCHWD-6FINES 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 557_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.94 %
Rating:548.02 MVA
Rating Type:B
MVA to Mitigate:657.28
MW Contribution:10.6
Bus #Bus NameTypeMW Contribution
3150331BIRCHWDA
50/50
158.961
3141316ARNOLDS
50/50
2.026
3150351NORNECKC2
50/50
3.02
970575AG2-366 GEN
50/50
3.68
315749AE2-041 GEN
50/50
4.976
3141843SHACKLE
50/50
0.749
3142433PROV 92
50/50
0.218
3142433PROV 92
50/50
0.218
3150921YORKTN3
50/50
2.003
3144216WINCHST
50/50
0.289
3151161SURRY 1
50/50
2.191
970737AG2-469 GEN
Solar/Wind Harmer
20.26
3141906WESTMOR
Solar/Wind Harmer
0.165
316404AE1-155 C
Solar/Wind Harmer
0.054
970009AG2-005 GEN
Solar/Wind Harmer
1.646
962971AG1-146 GEN
Solar/Wind Harmer
3.312
316156AD2-030 GEN
Solar/Wind Harmer
0.109
3141873WAN 176
Solar/Wind Harmer
2.629
316280AD1-041 GEN
Solar/Wind Harmer
0.003
3141766HARMONY
Solar/Wind Harmer
1.866
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316382AG1-145 C
Solar/Wind Harmer
0.001
3142946ENON
Solar/Wind Harmer
0.022
3151221GRAVEL6
Adder
4.147
3151171GRAVELC
Adder
0.798
970293AG2-193 GEN
Solar/Wind Harmer
0.603
957191AF2-013 GEN
50/50
65.968
3150341NORNECKC1
50/50
3.119
3150341NORNECKC1
50/50
3.094
963611AG1-210 GEN
50/50
0.998
3150621CHESTS7
50/50
0.174
316077AC2-138 C
Solar/Wind Harmer
0.001
958261AF2-120 GEN
Solar/Wind Harmer
8.003
316075AC2-137 C
Solar/Wind Harmer
0.018
3142946ENON
Solar/Wind Harmer
0.007
3150351NORNECKC2
50/50
2.97
966661AG1-536 GEN
50/50
6.884
3141843SHACKLE
50/50
0.749
3142433PROV 92
50/50
0.218
3142433PROV 92
50/50
0.218
971353AH1-157 GEN
50/50
7.642
970017AG2-010 GEN
50/50
4.875
3150641CHESTS8
50/50
0.192
944631AF1-128 GEN
50/50
30.156
3152331SURRY 2
50/50
2.455
972135AH1-637 GEN
Solar/Wind Harmer
4.407
316337AD2-073 GEN
Solar/Wind Harmer
0.3
3141726DUNNSVL
Solar/Wind Harmer
1.049
962861AG1-135 GEN
Solar/Wind Harmer
7.561
3138133OCRAN
Solar/Wind Harmer
0.104
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.365
3142433PROV 92
Solar/Wind Harmer
0.422
971317AH1-138 GEN
Solar/Wind Harmer
0.633
316159AE1-175 C
Solar/Wind Harmer
0.067
3138126ROCKLANDING
Solar/Wind Harmer
0.034
3151171GRAVELC
Adder
0.607
315759AF1-018 GEN
50/50
4.976
3142433PROV 92
50/50
0.218
3142433PROV 92
50/50
0.218
972263AH1-716 GEN
50/50
35.649
3150611CHESTG7
50/50
0.379
3150631CHESTG8
50/50
0.372
971047AG2-646 GEN
50/50
10.599
944491AF1-114 GEN
Solar/Wind Harmer
0.002
316223AC1-118
Solar/Wind Harmer
0.297
3141813NORNECK
Solar/Wind Harmer
0.28
970327AG2-215 GEN
Solar/Wind Harmer
7.232
962981AG1-147 GEN
Solar/Wind Harmer
7.729
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.074
3138133OCRAN
Solar/Wind Harmer
0.052
3141913WHIT STONE
Solar/Wind Harmer
0.168
3141873WAN 176
Solar/Wind Harmer
0.03
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
4.097
316314AB2-024 C
Solar/Wind Harmer
0
3143873LANEXA
Solar/Wind Harmer
0.075
3138283WHITEMARSH
Solar/Wind Harmer
0.025
971167AH1-042 GEN
Solar/Wind Harmer
8.942
315976AC1-164 GENA
Solar/Wind Harmer
8.275
316169AC1-164_GENC
Solar/Wind Harmer
7.149
315975AC1-164 GENB
Solar/Wind Harmer
0.245
972265AH1-717 GEN
Adder
4.429
3151201GRAVEL4
Adder
4.152
3151191GRAVEL3
Adder
4.099
3151211GRAVEL5
Adder
4.099
3141426STAFORD
Solar/Wind Helper
0.029
CPLELTFEXP_CPLE->PJM
CLTF
1.912
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.152
NYPJM->LTFIMP_NY
CLTF
0.465
LGEELTFEXP_LGEE->PJM
CLTF
0.185
WECLTFEXP_WEC->PJM
CLTF
0.092
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.061
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.057
MECLTFEXP_MEC->PJM
CLTF
0.525
SIGELTFEXP_SIGE->PJM
CLTF
0.016
LAGNLTFEXP_LAGN->PJM
CLTF
1.213
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.047
TVALTFEXP_TVA->PJM
CLTF
0.609

Details for 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6CHCKAHM-6ELKO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 557_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.39 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:749.18
MW Contribution:18.11
Bus #Bus NameTypeMW Contribution
315759AF1-018 GEN
50/50
5.733
3142433PROV 92
50/50
0.237
3142433PROV 92
50/50
0.237
3150611CHESTG7
50/50
0.647
3150631CHESTG8
50/50
0.636
971047AG2-646 GEN
50/50
18.112
972263AH1-716 GEN
50/50
58.57
315976AC1-164 GENA
Solar/Wind Harmer
22.099
316169AC1-164_GENC
Solar/Wind Harmer
19.091
315975AC1-164 GENB
Solar/Wind Harmer
0.654
316314AB2-024 C
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.001
3141873WAN 176
Solar/Wind Harmer
0.03
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
4.4
3143873LANEXA
Solar/Wind Harmer
0.089
3141913WHIT STONE
Solar/Wind Harmer
0.147
3138133OCRAN
Solar/Wind Harmer
0.044
3141783LANCAST
Solar/Wind Harmer
0.088
3141783LANCAST
Solar/Wind Harmer
0.058
962981AG1-147 GEN
Solar/Wind Harmer
5.383
970327AG2-215 GEN
Solar/Wind Harmer
4.699
3141813NORNECK
Solar/Wind Harmer
0.139
3138283WHITEMARSH
Solar/Wind Harmer
0.031
316223AC1-118
Solar/Wind Harmer
0.083
971167AH1-042 GEN
Solar/Wind Harmer
9.459
944491AF1-114 GEN
Solar/Wind Harmer
0
972265AH1-717 GEN
Adder
6.165
3151201GRAVEL4
Adder
5.779
3151191GRAVEL3
Adder
5.706
3151211GRAVEL5
Adder
5.706
971445AH1-216 GEN
Solar/Wind Harmer
5.578
3151081ELIZAR1
Adder
7.23
3151091ELIZAR2
Adder
7.104
3152611GOSPORTB
Adder
1.003
3152621GOSPORTC
Adder
0.851
3152601GOSPORTA
Adder
0.785
957871AF2-081 GEN
Solar/Wind Harmer
3.833
319010AE1-072 C
Solar/Wind Harmer
0.385
3146406KITTY HAWK
Solar/Wind Harmer
0.01
3141843SHACKLE
50/50
0.805
966661AG1-536 GEN
50/50
4.027
3150351NORNECKC2
50/50
1.467
971353AH1-157 GEN
50/50
11.629
3142433PROV 92
50/50
0.237
3142433PROV 92
50/50
0.237
970017AG2-010 GEN
50/50
7.587
3150641CHESTS8
50/50
0.328
944631AF1-128 GEN
50/50
51.528
3152331SURRY 2
50/50
4.05
3141766HARMONY
Solar/Wind Harmer
0.032
316159AE1-175 C
Solar/Wind Harmer
0.131
971777AH1-397 GEN
Solar/Wind Harmer
0.392
3138133OCRAN
Solar/Wind Harmer
0.088
3141726DUNNSVL
Solar/Wind Harmer
0.58
962861AG1-135 GEN
Solar/Wind Harmer
4.544
971317AH1-138 GEN
Solar/Wind Harmer
0.97
316337AD2-073 GEN
Solar/Wind Harmer
0.112
3142433PROV 92
Solar/Wind Harmer
0.459
3138126ROCKLANDING
Solar/Wind Harmer
0.052
972135AH1-637 GEN
Solar/Wind Harmer
0.821
316294AC1-161 GEN
Solar/Wind Harmer
1.466
316072AD1-144
Solar/Wind Harmer
0.029
3151171GRAVELC
Adder
0.845
3145336SMITFLD
Solar/Wind Harmer
0.317
944591AF1-124 GEN
Solar/Wind Harmer
17.87
316375AC2-012 GEN
Solar/Wind Harmer
0.002
3150981CHESPKA
Adder
0.984
316388AE2-253 GEN
Solar/Wind Harmer
0.242
3146456SLIGO L269
Solar/Wind Harmer
0.077
316246AF1-032 C
Solar/Wind Harmer
0.034
961611AG1-000B GEN
Solar/Wind Harmer
3.97
971647AH1-324 GEN
Solar/Wind Harmer
3.105
3146516WINFALL
Solar/Wind Harmer
0.234
3146516WINFALL
Solar/Wind Harmer
0.072
316093AE2-104_GEN
Solar/Wind Harmer
1.204
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
971069AG2-661 GEN
Solar/Wind Harmer
1.201
3130156CHOWAN
Solar/Wind Harmer
0.067
316458AB2-190 GEN2
Solar/Wind Harmer
0.345
970129AG2-093 GEN
Solar/Wind Harmer
1.811
3145663CRESWEL
Solar/Wind Harmer
0.178
971163AH1-040 GEN
Solar/Wind Harmer
5.075
939411AE1-173 GEN
Solar/Wind Harmer
25.398
3146206CASHIE
Solar/Wind Harmer
0.058
971547AH1-271 GEN
Solar/Wind Harmer
1.231
3142416OLDCHRC
Solar/Wind Helper
1.057
3142416OLDCHRC
Solar/Wind Helper
0.405
316305AF2-043 C
Solar/Wind Harmer
0.001
313526AB2-022
Solar/Wind Harmer
0.04
3146486SUNBURY
Solar/Wind Harmer
0.074
3146486SUNBURY
Solar/Wind Harmer
0.074
316321Z2-027
Solar/Wind Harmer
0.014
3146396TANGLEW
Solar/Wind Harmer
0.204
3145176PASQUOTANK
Solar/Wind Harmer
0.046
315835AF2-110_GEN
Solar/Wind Harmer
0.491
316369SG1_INVT
Solar/Wind Harmer
0.003
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.067
3130156CHOWAN
Solar/Wind Harmer
0.067
316132AB2-190 GEN1
Solar/Wind Harmer
0.345
316311AC2-079 GEN
Solar/Wind Harmer
1.828
315833AF1-017_GEN
Solar/Wind Harmer
0
316349AD2-085 GEN
Solar/Wind Harmer
0.044
315816AE2-034 GEN
Solar/Wind Harmer
0.272
3130546PLYMOUTH
Solar/Wind Harmer
0.06
315732AD1-074 GEN1
Solar/Wind Harmer
0.344
315733AD1-074 GEN2
Solar/Wind Harmer
0.344
315735AD1-075 GEN1
Solar/Wind Harmer
0.172
3146206CASHIE
Solar/Wind Harmer
0.058
970601AG2-382 GEN
Solar/Wind Harmer
2.153
316312AB1-027
Solar/Wind Helper
0.774
3150341NORNECKC1
50/50
1.541
3150341NORNECKC1
50/50
1.528
963611AG1-210 GEN
50/50
0.493
3150621CHESTS7
50/50
0.297
958261AF2-120 GEN
Solar/Wind Harmer
4.681
316077AC2-138 C
Solar/Wind Harmer
0.001
3142946ENON
Solar/Wind Harmer
0.013
316236AE1-162_GEN
Solar/Wind Harmer
0.001
316036AC1-147 C
Solar/Wind Harmer
0.015
3150991CHESPKB
Adder
0.825
3150991CHESPKB
Adder
0.805
316316AC1-027 C
Solar/Wind Harmer
0.075
3142956BIRDNECK
Solar/Wind Harmer
0
316185AD1-033 GEN
Solar/Wind Harmer
0.002
3145506HICKORY
Solar/Wind Harmer
0.311
3145506HICKORY
Solar/Wind Harmer
0.187
3145506HICKORY
Solar/Wind Harmer
0.047
316339AD2-160 GEN
Solar/Wind Harmer
0.125
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
316017AA1-139 ULT1
Solar/Wind Harmer
0.043
3137176SLIGO L2192
Solar/Wind Harmer
0.305
3146456SLIGO L269
Solar/Wind Harmer
1.356
3130086AYDLETT
Solar/Wind Harmer
0.305
3146386ELIZ CT
Solar/Wind Harmer
0.075
316431W1029_GEN1
Solar/Wind Harmer
0
316433W1029_GEN2
Solar/Wind Harmer
0
3146516WINFALL
Solar/Wind Harmer
0.072
3146516WINFALL
Solar/Wind Harmer
0.072
3146516WINFALL
Solar/Wind Harmer
0.072
3146626S HERTFORD
Solar/Wind Harmer
0.071
3146626S HERTFORD
Solar/Wind Harmer
0.071
316033AB2-134 GEN
Solar/Wind Harmer
0.004
315697AD1-025 GEN
Solar/Wind Harmer
0.079
3146376EDENTON
Solar/Wind Harmer
0.299
3146376EDENTON
Solar/Wind Harmer
0.299
315742AE1-103 GEN
Solar/Wind Harmer
0.001
316065AD1-022 GEN
Solar/Wind Harmer
2.693
316075AC2-137 C
Solar/Wind Helper
1.022
315749AE2-041 GEN
50/50
5.733
3141843SHACKLE
50/50
0.805
970575AG2-366 GEN
50/50
2.564
3150351NORNECKC2
50/50
1.491
3150921YORKTN3
50/50
3.133
3142433PROV 92
50/50
0.237
3142433PROV 92
50/50
0.237
3144216WINCHST
50/50
0.45
3151161SURRY 1
50/50
3.05
3141766HARMONY
Solar/Wind Harmer
2.15
316382AG1-145 C
Solar/Wind Harmer
0.001
316156AD2-030 GEN
Solar/Wind Harmer
0.11
3141873WAN 176
Solar/Wind Harmer
2.643
316280AD1-041 GEN
Solar/Wind Harmer
0.003
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
962971AG1-146 GEN
Solar/Wind Harmer
2.307
970009AG2-005 GEN
Solar/Wind Harmer
1.069
316404AE1-155 C
Solar/Wind Harmer
0.032
3142946ENON
Solar/Wind Harmer
0.045
3141906WESTMOR
Solar/Wind Harmer
0.046
970737AG2-469 GEN
Solar/Wind Harmer
4.442
315773AC2-141 GEN
Solar/Wind Harmer
3.089
3151221GRAVEL6
Adder
5.773
3151171GRAVELC
Adder
1.111
3145336SMITFLD
Solar/Wind Harmer
0.032
944581AF1-123 GEN
Solar/Wind Harmer
17.807
944601AF1-125 GEN
Solar/Wind Harmer
17.533
3144536CHRHLND
Solar/Wind Harmer
0.012
3151101ELIZAR3
Adder
7.322
3144873MCLAUGH
Solar/Wind Harmer
0.002
3146456SLIGO L269
Solar/Wind Harmer
0.077
971153AH1-033 GEN
Solar/Wind Harmer
0.886
961611AG1-000B GEN
Solar/Wind Harmer
2.019
316320Y1-086
Solar/Wind Harmer
0
316435W1029_GEN3
Solar/Wind Harmer
0
3146516WINFALL
Solar/Wind Harmer
0.072
3146626S HERTFORD
Solar/Wind Harmer
0.071
315778AD1-151 GEN
Solar/Wind Harmer
5.404
3146376EDENTON
Solar/Wind Harmer
0.067
3145273HOLLAND
Solar/Wind Harmer
0.05
970129AG2-093 GEN
Solar/Wind Harmer
3.847
315614AA2-178 GEN
Solar/Wind Harmer
0.363
971157AH1-035 GEN
Solar/Wind Harmer
0.726
315737AD1-076 GEN
Solar/Wind Harmer
0.771
970133AG2-095 GEN
Solar/Wind Harmer
0.559
3146206CASHIE
Solar/Wind Harmer
0.058
CPLELTFEXP_CPLE->PJM
CLTF
2.113
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.142
NYPJM->LTFIMP_NY
CLTF
0.351
LGEELTFEXP_LGEE->PJM
CLTF
0.115
WECLTFEXP_WEC->PJM
CLTF
0.057
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.783
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.778
MECLTFEXP_MEC->PJM
CLTF
0.38
SIGELTFEXP_SIGE->PJM
CLTF
0.011
LAGNLTFEXP_LAGN->PJM
CLTF
1.093
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.265
TVALTFEXP_TVA->PJM
CLTF
0.541

Details for 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: 56702_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer
Contingency Name:
DVP_P4-2: 56702_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:125.13 %
Rating:1107.0 MVA
Rating Type:C
MVA to Mitigate:1385.24
MW Contribution:36.0
Bus #Bus NameTypeMW Contribution
315759AF1-018 GEN
50/50
8.574
3142433PROV 92
50/50
0.435
3142433PROV 92
50/50
0.435
3150611CHESTG7
50/50
1.286
3150631CHESTG8
50/50
1.265
971047AG2-646 GEN
50/50
36.002
315976AC1-164 GENA
Solar/Wind Harmer
37.032
316169AC1-164_GENC
Solar/Wind Harmer
31.992
315975AC1-164 GENB
Solar/Wind Harmer
1.096
3141843SHACKLE
50/50
1.242
966661AG1-536 GEN
50/50
6.058
3142433PROV 92
50/50
0.435
3142433PROV 92
50/50
0.435
3150351NORNECKC2
50/50
2.203
3150641CHESTS8
50/50
0.652
944631AF1-128 GEN
50/50
102.426
971353AH1-157 GEN
50/50
16.966
970017AG2-010 GEN
50/50
11.364
3143096IRON208
50/50
0.7
3150771HOPHCF1
50/50
0.623
3141766HARMONY
Solar/Wind Harmer
-0.005
971777AH1-397 GEN
Solar/Wind Harmer
3.027
3138133OCRAN
Solar/Wind Harmer
-0.015
316159AE1-175 C
Solar/Wind Harmer
0.665
964211AG1-282 GEN
Solar/Wind Harmer
0.733
3141726DUNNSVL
Solar/Wind Harmer
-0.097
961951AG1-038 GEN
Solar/Wind Harmer
3.191
962861AG1-135 GEN
Solar/Wind Harmer
9.003
3142433PROV 92
Solar/Wind Harmer
-0.094
316337AD2-073 GEN
Solar/Wind Harmer
0.586
971317AH1-138 GEN
Solar/Wind Harmer
2.659
3138126ROCKLANDING
Solar/Wind Harmer
0.059
3142416OLDCHRC
Solar/Wind Harmer
-0.045
3142416OLDCHRC
Solar/Wind Harmer
-0.017
970129AG2-093 GEN
Solar/Wind Harmer
3.87
316458AB2-190 GEN2
Solar/Wind Harmer
1.714
971069AG2-661 GEN
Solar/Wind Harmer
2.652
972135AH1-637 GEN
Solar/Wind Harmer
1.651
971647AH1-324 GEN
Solar/Wind Harmer
8.244
961611AG1-000B GEN
Solar/Wind Harmer
8.06
3151171GRAVELC
Adder
1.528
3145336SMITFLD
Solar/Wind Harmer
-0.061
957971AF2-091 GEN
Solar/Wind Harmer
1.473
316072AD1-144
Solar/Wind Harmer
0.294
315671AE2-027_GEN
Solar/Wind Harmer
10.644
315749AE2-041 GEN
50/50
8.574
3141843SHACKLE
50/50
1.242
970575AG2-366 GEN
50/50
3.862
3142433PROV 92
50/50
0.435
3142433PROV 92
50/50
0.435
3150351NORNECKC2
50/50
2.24
3150921YORKTN3
50/50
4.627
3144216WINCHST
50/50
0.678
3143096IRON208
50/50
0.7
3143096IRON208
50/50
0.686
3150801HOPHCF4
50/50
0.906
971211AH1-065 GEN
50/50
1.092
3141766HARMONY
Solar/Wind Harmer
2.412
3142946ENON
Solar/Wind Harmer
-0.009
316203AE2-005 GEN
Solar/Wind Harmer
10.85
316280AD1-041 GEN
Solar/Wind Harmer
1.923
316156AD2-030 GEN
Solar/Wind Harmer
0.673
3141873WAN 176
Solar/Wind Harmer
2.993
316382AG1-145 C
Solar/Wind Harmer
0.746
962971AG1-146 GEN
Solar/Wind Harmer
4.577
316484AD2-074 GEN
Solar/Wind Harmer
6.098
970009AG2-005 GEN
Solar/Wind Harmer
3.028
316404AE1-155 C
Solar/Wind Harmer
4.616
970293AG2-193 GEN
Solar/Wind Harmer
2.767
3141906WESTMOR
Solar/Wind Harmer
-0.008
970737AG2-469 GEN
Solar/Wind Harmer
8.897
3142416OLDCHRC
Solar/Wind Harmer
1.744
970133AG2-095 GEN
Solar/Wind Harmer
1.942
970129AG2-093 GEN
Solar/Wind Harmer
9.555
315778AD1-151 GEN
Solar/Wind Harmer
14.522
961611AG1-000B GEN
Solar/Wind Harmer
3.439
3151221GRAVEL6
Adder
10.443
3151171GRAVELC
Adder
2.009
3145336SMITFLD
Solar/Wind Harmer
-0.006
3144536CHRHLND
Solar/Wind Harmer
-0.002
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
11.542
965281AG1-393 GEN
Solar/Wind Harmer
1.744
315773AC2-141 GEN
Solar/Wind Harmer
5.752
944581AF1-123 GEN
Solar/Wind Harmer
62.362
944601AF1-125 GEN
Solar/Wind Harmer
61.389
315813AE1-149 C
Solar/Wind Harmer
8.496
3146456SLIGO L269
Solar/Wind Harmer
-0.014
971153AH1-033 GEN
Solar/Wind Harmer
1.655
970659AG2-427 GEN
Solar/Wind Harmer
1.277
316083AB2-161 GEN
Solar/Wind Harmer
2.202
970661AG2-428 GEN
Solar/Wind Harmer
2.552
316320Y1-086
Solar/Wind Harmer
0.783
316435W1029_GEN3
Solar/Wind Harmer
2.383
3146516WINFALL
Solar/Wind Harmer
-0.013
3146626S HERTFORD
Solar/Wind Harmer
-0.013
3145273HOLLAND
Solar/Wind Harmer
-0.01
315839AE2-212 C
Solar/Wind Harmer
0.383
3146376EDENTON
Solar/Wind Harmer
-0.012
315614AA2-178 GEN
Solar/Wind Harmer
1.285
3150861SPRUNCD
Adder
0.485
971157AH1-035 GEN
Solar/Wind Harmer
1.439
315737AD1-076 GEN
Solar/Wind Harmer
2.174
3146206CASHIE
Solar/Wind Harmer
-0.011
3156081AA2-088 GEN
Solar/Wind Harmer
3.619
3145893MURPHYS
Solar/Wind Harmer
0.076
3145893MURPHYS
Solar/Wind Harmer
-0.011
957521AF2-046 GEN
Solar/Wind Harmer
8.535
961681AG1-008 GEN
Solar/Wind Harmer
8.535
3156021HOLLOMANSOL
Solar/Wind Harmer
1.456
3146173TUNIS
Solar/Wind Harmer
-0.011
316463AE2-346 GEN
Solar/Wind Harmer
0.172
316140AB2-099
Solar/Wind Harmer
0.072
962331AG1-082 GEN
Solar/Wind Harmer
1.33
3145963POPLR C
Solar/Wind Harmer
-0.01
3146263WOODLND
Solar/Wind Harmer
-0.01
316317KELFORD C
Solar/Wind Harmer
0.478
3145823KELFORD
Solar/Wind Harmer
-0.01
316365GEN2_N
Solar/Wind Harmer
0.678
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
3145933PARMELE
Solar/Wind Harmer
-0.01
966801AG1-551 GEN
Solar/Wind Harmer
1.208
966621AG1-532 GEN
Solar/Wind Harmer
0.194
313506AB2-031 GEN
Solar/Wind Harmer
0.769
3145796HORNRTN
Solar/Wind Harmer
-0.038
3145796HORNRTN
Solar/Wind Harmer
-0.009
316210AC1-098 GEN
Solar/Wind Harmer
1.47
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
970917AG2-570 GEN
Solar/Wind Harmer
22.162
3147043LAWRENC
Solar/Wind Harmer
-0.005
315724AD1-057 GEN
Solar/Wind Harmer
0.507
316327AA2-057 GEN
Solar/Wind Harmer
0.886
3146073TAR RVR
Solar/Wind Harmer
-0.009
3146083TARBORO
Solar/Wind Harmer
-0.009
3146233WITAKRS
Solar/Wind Harmer
0.178
3146233WITAKRS
Solar/Wind Harmer
-0.006
3138543CONSLDL
Solar/Wind Harmer
-0.006
961601AG1-000A GEN
Solar/Wind Harmer
3.293
3145543BTLEBRO
Solar/Wind Harmer
-0.008
3145543BTLEBRO
Solar/Wind Harmer
-0.008
3141316ARNOLDS
Adder
0.161
316375AC2-012 GEN
Solar/Wind Harmer
4.845
3150981CHESPKA
Adder
1.556
316294AC1-161 GEN
Solar/Wind Harmer
4.447
944591AF1-124 GEN
Solar/Wind Harmer
62.587
3142543TWELFTH
Solar/Wind Harmer
-0.001
316246AF1-032 C
Solar/Wind Harmer
0.277
316388AE2-253 GEN
Solar/Wind Harmer
0.92
3146456SLIGO L269
Solar/Wind Harmer
-0.014
970659AG2-427 GEN
Solar/Wind Harmer
7.209
316381AD1-082 GEN
Solar/Wind Harmer
1.244
970661AG2-428 GEN
Solar/Wind Harmer
14.398
316093AE2-104_GEN
Solar/Wind Harmer
3.922
3146516WINFALL
Solar/Wind Harmer
-0.042
3146516WINFALL
Solar/Wind Harmer
-0.013
315800Z1-036_GEN1
Solar/Wind Harmer
3.14
3130156CHOWAN
Solar/Wind Harmer
-0.012
3145663CRESWEL
Solar/Wind Harmer
-0.033
971163AH1-040 GEN
Solar/Wind Harmer
11.163
3150851SPRUNCC
Adder
0.485
939411AE1-173 GEN
Solar/Wind Harmer
57.436
3146206CASHIE
Solar/Wind Harmer
-0.011
971547AH1-271 GEN
Solar/Wind Harmer
2.795
3145893MURPHYS
Solar/Wind Harmer
-0.043
3145893MURPHYS
Solar/Wind Harmer
0.323
940641AE2-051 GEN
Solar/Wind Harmer
10.065
3146173TUNIS
Solar/Wind Harmer
-0.011
3145683EARLEYS
Solar/Wind Harmer
-0.011
3145963POPLR C
Solar/Wind Harmer
-0.01
316174AB2-169 GEN
Solar/Wind Harmer
1.591
3146263WOODLND
Solar/Wind Harmer
-0.01
3145823KELFORD
Solar/Wind Harmer
-0.01
316023GEN1_S
Solar/Wind Harmer
0.678
316190AA2-174 GEN
Solar/Wind Harmer
0.12
316011AB1-132 GEN
Solar/Wind Harmer
2.035
962571AG1-106 GEN
Solar/Wind Harmer
1.398
3146293MARTNCO
Solar/Wind Harmer
0.06
960081AF2-299 GEN
Solar/Wind Harmer
1.076
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.009
3145783HORNRTN
Solar/Wind Harmer
-0.009
3143526WINTERP
Solar/Wind Harmer
-0.049
316212AC1-099_GEN
Solar/Wind Harmer
0.816
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
971795AH1-408 GEN
Solar/Wind Harmer
6.798
316494AC1-189 GEN
Solar/Wind Harmer
0.961
970919AG2-571 GEN
Solar/Wind Harmer
2.805
3147043LAWRENC
Adder
0.711
970087AG2-069 GEN
Solar/Wind Harmer
8.273
315722AD1-056 GEN
Solar/Wind Harmer
0.923
961671AG1-007 GEN
Solar/Wind Harmer
0.109
3146083TARBORO
Solar/Wind Harmer
-0.009
3145493TOT1
Solar/Wind Harmer
0.256
3146233WITAKRS
Solar/Wind Harmer
-0.034
316129AC1-054 GEN
Solar/Wind Harmer
0.725
316359AB2-059 GEN
Solar/Wind Harmer
1.113
316049AB1-081 GEN
Solar/Wind Harmer
0.891
3145543BTLEBRO
Solar/Wind Harmer
-0.008
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3142053HEARTS
Solar/Wind Harmer
0.097
971065AG2-659 GEN
Solar/Wind Harmer
4.078
957481AF2-042 GEN
Solar/Wind Harmer
21.195
316314AB2-024 C
Solar/Wind Harmer
2.414
316059AD1-063 C
Solar/Wind Harmer
0.612
3143873LANEXA
Solar/Wind Harmer
-0.016
315662AE1-191 GEN
Solar/Wind Harmer
3.076
315666AE1-190 GEN
Solar/Wind Harmer
0.769
957601AF2-054 GEN
Solar/Wind Harmer
0.754
3141873WAN 176
Solar/Wind Harmer
-0.005
3141913WHIT STONE
Solar/Wind Harmer
-0.025
3138133OCRAN
Solar/Wind Harmer
-0.007
3141783LANCAST
Solar/Wind Harmer
-0.015
3141783LANCAST
Solar/Wind Harmer
-0.01
962981AG1-147 GEN
Solar/Wind Harmer
10.679
3141813NORNECK
Solar/Wind Harmer
-0.023
971167AH1-042 GEN
Solar/Wind Harmer
22.181
957831AF2-077 GEN
Solar/Wind Harmer
0.668
3138283WHITEMARSH
Solar/Wind Harmer
0.034
316223AC1-118
Solar/Wind Harmer
0.531
316312AB1-027
Solar/Wind Harmer
0.583
316132AB2-190 GEN1
Solar/Wind Harmer
1.714
316369SG1_INVT
Solar/Wind Harmer
2.973
972265AH1-717 GEN
Adder
11.153
3151201GRAVEL4
Adder
10.455
3151191GRAVEL3
Adder
10.323
3151211GRAVEL5
Adder
10.323
971445AH1-216 GEN
Solar/Wind Harmer
9.527
944491AF1-114 GEN
Solar/Wind Harmer
4.333
3152611GOSPORTB
Adder
1.587
3152621GOSPORTC
Adder
1.347
3152601GOSPORTA
Adder
1.242
3151081ELIZAR1
Adder
11.396
3151091ELIZAR2
Adder
11.198
316305AF2-043 C
Solar/Wind Harmer
0.413
957871AF2-081 GEN
Solar/Wind Harmer
6.809
319010AE1-072 C
Solar/Wind Harmer
2.743
3146406KITTY HAWK
Solar/Wind Harmer
0.011
315833AF1-017_GEN
Solar/Wind Harmer
2.567
316349AD2-085 GEN
Solar/Wind Harmer
1.202
316311AC2-079 GEN
Solar/Wind Harmer
6.818
315835AF2-110_GEN
Solar/Wind Harmer
1.686
3146486SUNBURY
Solar/Wind Harmer
-0.013
3146486SUNBURY
Solar/Wind Harmer
-0.013
313526AB2-022
Solar/Wind Harmer
0.36
316321Z2-027
Solar/Wind Harmer
0.358
3146396TANGLEW
Solar/Wind Harmer
0.244
3145176PASQUOTANK
Solar/Wind Harmer
-0.008
315611Z1-036_GEN2
Solar/Wind Harmer
3.14
3130156CHOWAN
Solar/Wind Harmer
-0.012
3130156CHOWAN
Solar/Wind Harmer
-0.012
3143316POE
Solar/Wind Harmer
-0.048
315816AE2-034 GEN
Solar/Wind Harmer
0.963
971285AH1-108 GEN
Adder
0.794
3130546PLYMOUTH
Solar/Wind Harmer
-0.011
315732AD1-074 GEN1
Solar/Wind Harmer
2.314
315733AD1-074 GEN2
Solar/Wind Harmer
2.314
315735AD1-075 GEN1
Solar/Wind Harmer
1.157
3146206CASHIE
Solar/Wind Harmer
-0.011
970601AG2-382 GEN
Solar/Wind Harmer
4.891
965291AG1-394 GEN
Solar/Wind Harmer
0.979
316318V4-068
Solar/Wind Harmer
0.271
3145893MURPHYS
Solar/Wind Harmer
-0.029
3145893MURPHYS
Solar/Wind Harmer
-0.011
316315AB2-025 C
Solar/Wind Harmer
0.293
315814AE2-033 C
Solar/Wind Harmer
10.064
3145513AHOSKIE
Solar/Wind Harmer
0.093
961941AG1-037 GEN
Solar/Wind Harmer
0.08
3145513AHOSKIE
Solar/Wind Harmer
-0.011
3145683EARLEYS
Solar/Wind Harmer
-0.021
3145683EARLEYS
Solar/Wind Harmer
-0.011
3145683EARLEYS
Solar/Wind Harmer
-0.011
3146043SEABORD
Solar/Wind Harmer
-0.01
315607AA1-063A GEN
Solar/Wind Harmer
1.024
315652AC1-086 GEN
Solar/Wind Harmer
10.943
3146033SCOT NK
Solar/Wind Harmer
-0.039
941031AE2-094 GEN
Solar/Wind Harmer
18.106
944011AF1-069 GEN
Solar/Wind Harmer
5.673
946281AF1-292 GEN
Solar/Wind Harmer
0.214
316087AB2-174 GEN
Solar/Wind Harmer
1.364
3137643SOCKMAN
Solar/Wind Harmer
-0.038
3145796HORNRTN
Solar/Wind Harmer
-0.03
3145796HORNRTN
Solar/Wind Harmer
-0.004
316233AE1-074 FULL
Solar/Wind Harmer
0.255
971281AH1-106 GEN
Solar/Wind Harmer
1.542
971283AH1-107 GEN
Solar/Wind Harmer
1.542
970673AG2-436 GEN
Solar/Wind Harmer
19.87
970673AG2-436 GEN
Solar/Wind Harmer
10.061
316005AA1-067
Solar/Wind Harmer
0.188
3145746EVERETS
Solar/Wind Harmer
-0.037
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
970181AG2-120 GEN
Solar/Wind Harmer
1.218
971967AH1-528 GEN
Solar/Wind Harmer
17.421
957861AF2-080 GEN
Solar/Wind Harmer
3.908
970085AG2-068 GEN
Solar/Wind Harmer
5.516
970581AG2-369 GEN
Solar/Wind Harmer
4.743
316420AA1-050 GEN
Solar/Wind Harmer
1.001
3145573BETHELC
Solar/Wind Harmer
-0.009
3145573BETHELC
Solar/Wind Harmer
-0.009
316319Z2-044 C
Solar/Wind Harmer
0.471
970831AG2-522 GEN
Solar/Wind Harmer
4.197
3150341NORNECKC1
50/50
2.314
3150341NORNECKC1
50/50
2.295
963611AG1-210 GEN
50/50
0.74
3150621CHESTS7
50/50
0.591
3150781HOPHCF2
50/50
0.623
3150791HOPHCF3
50/50
0.623
3150761HOPPOLC
50/50
0.395
971213AH1-066 GEN
50/50
0.546
316075AC2-137 C
Solar/Wind Harmer
0.756
3142946ENON
Solar/Wind Harmer
-0.003
316441AF1-014 GEN
Solar/Wind Harmer
1.735
316487AF1-042 GEN
Solar/Wind Harmer
3.191
958261AF2-120 GEN
Solar/Wind Harmer
9.272
316077AC2-138 C
Solar/Wind Harmer
0.493
3150691DARBY 3
Adder
10.705
3150701DARBY 4
Adder
10.68
3150681DARBY 2
Adder
10.668
3150671DARBY 1
Adder
10.655
316033AB2-134 GEN
Solar/Wind Harmer
5.366
315697AD1-025 GEN
Solar/Wind Harmer
3.366
316236AE1-162_GEN
Solar/Wind Harmer
0.462
316036AC1-147 C
Solar/Wind Harmer
0.378
3150991CHESPKB
Adder
1.305
3150991CHESPKB
Adder
1.274
316316AC1-027 C
Solar/Wind Harmer
0.426
3142956BIRDNECK
Solar/Wind Harmer
0.744
316185AD1-033 GEN
Solar/Wind Harmer
1.453
3145506HICKORY
Solar/Wind Harmer
-0.055
3145506HICKORY
Solar/Wind Harmer
-0.033
3145506HICKORY
Solar/Wind Harmer
-0.008
3142366NRTHEST
Adder
0.397
316339AD2-160 GEN
Solar/Wind Harmer
0.92
316018AA1-139 ULT2
Solar/Wind Harmer
1.167
316017AA1-139 ULT1
Solar/Wind Harmer
1.102
3137176SLIGO L2192
Solar/Wind Harmer
-0.054
3146456SLIGO L269
Solar/Wind Harmer
1.603
970657AG2-426 GEN
Solar/Wind Harmer
4.237
970657AG2-426 GEN
Solar/Wind Harmer
0.886
3130086AYDLETT
Solar/Wind Harmer
-0.054
3146386ELIZ CT
Solar/Wind Harmer
-0.013
316431W1029_GEN1
Solar/Wind Harmer
2.383
316433W1029_GEN2
Solar/Wind Harmer
2.383
3146516WINFALL
Solar/Wind Harmer
-0.013
3146516WINFALL
Solar/Wind Harmer
-0.013
3146516WINFALL
Solar/Wind Harmer
-0.013
944641AF1-129 GEN
Adder
55.399
316240AF1-291 C
Solar/Wind Harmer
0.391
3146626S HERTFORD
Solar/Wind Harmer
-0.013
3146626S HERTFORD
Solar/Wind Harmer
-0.013
315742AE1-103 GEN
Solar/Wind Harmer
1.299
3146376EDENTON
Solar/Wind Harmer
0.369
3146376EDENTON
Solar/Wind Harmer
0.369
316065AD1-022 GEN
Solar/Wind Harmer
5.637
3145893MURPHYS
Solar/Wind Harmer
0.304
3145893MURPHYS
Solar/Wind Harmer
-0.02
3144356SAPONY
Solar/Wind Harmer
0.378
3146173TUNIS
Solar/Wind Harmer
-0.011
3146173TUNIS
Solar/Wind Harmer
-0.011
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
316426AA2-053 GEN
Solar/Wind Harmer
0.983
3145933PARMELE
Solar/Wind Harmer
-0.019
3145933PARMELE
Solar/Wind Harmer
-0.01
316181AB2-040 GEN
Solar/Wind Harmer
1.334
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.075
3145593CAROLNA
Solar/Wind Harmer
0.079
3145796HORNRTN
Solar/Wind Harmer
-0.028
3145783HORNRTN
Solar/Wind Harmer
1.127
3145783HORNRTN
Solar/Wind Harmer
0.901
3145783HORNRTN
Solar/Wind Harmer
0.282
3145783HORNRTN
Solar/Wind Harmer
0.113
3143526WINTERP
Solar/Wind Harmer
-0.049
972185AH1-677 GEN
Adder
4.674
972187AH1-678 GEN
Adder
2.339
316274AC1-208 GEN
Solar/Wind Harmer
0.989
970933AG2-581 GEN
Solar/Wind Harmer
8.378
3145493TOT1
Solar/Wind Harmer
0.134
3145453TOT5
Solar/Wind Harmer
0.08
3145603CNETO
Solar/Wind Harmer
0.053
961601AG1-000A GEN
Solar/Wind Harmer
3.252
316263AC1-034 GEN
Solar/Wind Harmer
3.871
970099AG2-077 GEN
Solar/Wind Harmer
8.478
CPLELTFEXP_CPLE->PJM
CLTF
4.035
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.643
NYPJM->LTFIMP_NY
CLTF
0.699
LGEELTFEXP_LGEE->PJM
CLTF
0.151
WECLTFEXP_WEC->PJM
CLTF
0.071
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.999
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.074
MECLTFEXP_MEC->PJM
CLTF
0.569
SIGELTFEXP_SIGE->PJM
CLTF
0.015
LAGNLTFEXP_LAGN->PJM
CLTF
1.924
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.054
TVALTFEXP_TVA->PJM
CLTF
0.95

Details for 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 567_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 567_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.77 %
Rating:935.39 MVA
Rating Type:B
MVA to Mitigate:1120.31
MW Contribution:36.0
Bus #Bus NameTypeMW Contribution
315749AE2-041 GEN
50/50
8.574
3141843SHACKLE
50/50
1.242
970575AG2-366 GEN
50/50
3.862
3142433PROV 92
50/50
0.435
3142433PROV 92
50/50
0.435
3150351NORNECKC2
50/50
2.24
3150921YORKTN3
50/50
4.627
3144216WINCHST
50/50
0.678
3143096IRON208
50/50
0.7
3143096IRON208
50/50
0.686
3150801HOPHCF4
50/50
0.906
971211AH1-065 GEN
50/50
1.092
3141766HARMONY
Solar/Wind Harmer
3.215
3142946ENON
Solar/Wind Harmer
0.078
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316280AD1-041 GEN
Solar/Wind Harmer
0.005
316156AD2-030 GEN
Solar/Wind Harmer
0.166
3141873WAN 176
Solar/Wind Harmer
3.99
316382AG1-145 C
Solar/Wind Harmer
0.002
962971AG1-146 GEN
Solar/Wind Harmer
3.476
970009AG2-005 GEN
Solar/Wind Harmer
1.61
316404AE1-155 C
Solar/Wind Harmer
0.048
970293AG2-193 GEN
Solar/Wind Harmer
2.101
3141906WESTMOR
Solar/Wind Harmer
0.07
970737AG2-469 GEN
Solar/Wind Harmer
6.757
3142416OLDCHRC
Solar/Wind Harmer
1.491
970133AG2-095 GEN
Solar/Wind Harmer
1.475
970129AG2-093 GEN
Solar/Wind Harmer
9.13
315778AD1-151 GEN
Solar/Wind Harmer
11.936
961611AG1-000B GEN
Solar/Wind Harmer
3.876
3151221GRAVEL6
Adder
10.443
3151171GRAVELC
Adder
2.009
3145336SMITFLD
Solar/Wind Harmer
0.055
3144536CHRHLND
Solar/Wind Harmer
0.019
3144873MCLAUGH
Solar/Wind Harmer
0.003
3151101ELIZAR3
Adder
11.542
965281AG1-393 GEN
Solar/Wind Harmer
1.324
315773AC2-141 GEN
Solar/Wind Harmer
4.468
944581AF1-123 GEN
Solar/Wind Harmer
27.472
944601AF1-125 GEN
Solar/Wind Harmer
27.049
315813AE1-149 C
Solar/Wind Harmer
6.453
3150341NORNECKC1
50/50
2.314
3150341NORNECKC1
50/50
2.295
963611AG1-210 GEN
50/50
0.74
3150621CHESTS7
50/50
0.591
3150781HOPHCF2
50/50
0.623
3150791HOPHCF3
50/50
0.623
3150761HOPPOLC
50/50
0.395
971213AH1-066 GEN
50/50
0.546
316075AC2-137 C
Solar/Wind Harmer
0.069
3142946ENON
Solar/Wind Harmer
0.023
958261AF2-120 GEN
Solar/Wind Harmer
7.042
316077AC2-138 C
Solar/Wind Harmer
0.001
3150691DARBY 3
Adder
10.705
3150701DARBY 4
Adder
10.68
3150681DARBY 2
Adder
10.668
3150671DARBY 1
Adder
10.655
316033AB2-134 GEN
Solar/Wind Harmer
0.009
315697AD1-025 GEN
Solar/Wind Harmer
0.167
316236AE1-162_GEN
Solar/Wind Harmer
0.001
316036AC1-147 C
Solar/Wind Harmer
0.023
3150991CHESPKB
Adder
1.305
3150991CHESPKB
Adder
1.274
316316AC1-027 C
Solar/Wind Harmer
0.119
3142956BIRDNECK
Solar/Wind Harmer
0
316185AD1-033 GEN
Solar/Wind Harmer
0.003
3145506HICKORY
Solar/Wind Harmer
0.488
3145506HICKORY
Solar/Wind Harmer
0.293
3145506HICKORY
Solar/Wind Harmer
0.073
3142366NRTHEST
Adder
0.397
316339AD2-160 GEN
Solar/Wind Harmer
0.197
316018AA1-139 ULT2
Solar/Wind Harmer
0.003
316017AA1-139 ULT1
Solar/Wind Harmer
0.068
3137176SLIGO L2192
Solar/Wind Harmer
0.481
3146456SLIGO L269
Solar/Wind Harmer
2.138
970657AG2-426 GEN
Solar/Wind Harmer
4.227
970657AG2-426 GEN
Solar/Wind Harmer
0.886
3130086AYDLETT
Solar/Wind Harmer
0.482
3146386ELIZ CT
Solar/Wind Harmer
0.119
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.116
3146516WINFALL
Solar/Wind Harmer
0.116
3146516WINFALL
Solar/Wind Harmer
0.116
944641AF1-129 GEN
Adder
55.399
316240AF1-291 C
Solar/Wind Harmer
0.001
3146626S HERTFORD
Solar/Wind Harmer
0.115
3146626S HERTFORD
Solar/Wind Harmer
0.115
315742AE1-103 GEN
Solar/Wind Harmer
0.001
3146376EDENTON
Solar/Wind Harmer
0.491
3146376EDENTON
Solar/Wind Harmer
0.491
3141843SHACKLE
50/50
1.242
966661AG1-536 GEN
50/50
6.058
3142433PROV 92
50/50
0.435
3142433PROV 92
50/50
0.435
3150351NORNECKC2
50/50
2.203
3150641CHESTS8
50/50
0.652
944631AF1-128 GEN
50/50
102.426
971353AH1-157 GEN
50/50
16.966
970017AG2-010 GEN
50/50
11.364
3143096IRON208
50/50
0.7
3150771HOPHCF1
50/50
0.623
3141766HARMONY
Solar/Wind Harmer
0.048
971777AH1-397 GEN
Solar/Wind Harmer
0.605
3138133OCRAN
Solar/Wind Harmer
0.133
316159AE1-175 C
Solar/Wind Harmer
0.19
3141726DUNNSVL
Solar/Wind Harmer
0.868
962861AG1-135 GEN
Solar/Wind Harmer
6.837
3142433PROV 92
Solar/Wind Harmer
0.844
316337AD2-073 GEN
Solar/Wind Harmer
0.169
971317AH1-138 GEN
Solar/Wind Harmer
1.414
3138126ROCKLANDING
Solar/Wind Harmer
0.078
3142416OLDCHRC
Solar/Wind Harmer
0.4
3142416OLDCHRC
Solar/Wind Harmer
0.153
970129AG2-093 GEN
Solar/Wind Harmer
4.296
316458AB2-190 GEN2
Solar/Wind Harmer
0.809
971069AG2-661 GEN
Solar/Wind Harmer
2.652
972135AH1-637 GEN
Solar/Wind Harmer
1.254
971647AH1-324 GEN
Solar/Wind Harmer
6.261
961611AG1-000B GEN
Solar/Wind Harmer
7.623
3151171GRAVELC
Adder
1.528
3145336SMITFLD
Solar/Wind Harmer
0.545
316072AD1-144
Solar/Wind Harmer
0.047
315671AE2-027_GEN
Solar/Wind Harmer
8.084
316375AC2-012 GEN
Solar/Wind Harmer
0.003
3150981CHESPKA
Adder
1.556
316294AC1-161 GEN
Solar/Wind Harmer
2.12
944591AF1-124 GEN
Solar/Wind Harmer
27.57
3142543TWELFTH
Solar/Wind Harmer
0.012
316246AF1-032 C
Solar/Wind Harmer
0.055
316388AE2-253 GEN
Solar/Wind Harmer
0.38
3146456SLIGO L269
Solar/Wind Harmer
0.121
970659AG2-427 GEN
Solar/Wind Harmer
5.84
316381AD1-082 GEN
Solar/Wind Harmer
0.126
970661AG2-428 GEN
Solar/Wind Harmer
11.997
316093AE2-104_GEN
Solar/Wind Harmer
2.019
3146516WINFALL
Solar/Wind Harmer
0.377
3146516WINFALL
Solar/Wind Harmer
0.116
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.111
3145663CRESWEL
Solar/Wind Harmer
0.297
971163AH1-040 GEN
Solar/Wind Harmer
8.478
3150851SPRUNCC
Adder
0.485
939411AE1-173 GEN
Solar/Wind Harmer
43.623
3146206CASHIE
Solar/Wind Harmer
0.099
971547AH1-271 GEN
Solar/Wind Harmer
2.123
3145893MURPHYS
Solar/Wind Harmer
0.387
3145893MURPHYS
Solar/Wind Harmer
0.431
940641AE2-051 GEN
Solar/Wind Harmer
7.644
3146173TUNIS
Solar/Wind Harmer
0.095
3145683EARLEYS
Solar/Wind Harmer
0.094
3145963POPLR C
Solar/Wind Harmer
0.093
316174AB2-169 GEN
Solar/Wind Harmer
0.002
3146263WOODLND
Solar/Wind Harmer
0.091
3145823KELFORD
Solar/Wind Harmer
0.09
316023GEN1_S
Solar/Wind Harmer
0.201
316190AA2-174 GEN
Solar/Wind Harmer
0
316011AB1-132 GEN
Solar/Wind Harmer
1.573
962571AG1-106 GEN
Solar/Wind Harmer
1.231
3146293MARTNCO
Solar/Wind Harmer
0.08
960081AF2-299 GEN
Solar/Wind Harmer
0.817
3145796HORNRTN
Solar/Wind Harmer
0.279
3145796HORNRTN
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
0.084
3143526WINTERP
Solar/Wind Harmer
0.439
316212AC1-099_GEN
Solar/Wind Harmer
0.431
3145746EVERETS
Solar/Wind Harmer
0.083
3145746EVERETS
Solar/Wind Harmer
0.083
971795AH1-408 GEN
Solar/Wind Harmer
5.378
316494AC1-189 GEN
Solar/Wind Harmer
0.269
970919AG2-571 GEN
Solar/Wind Harmer
2.805
3147043LAWRENC
Adder
0.711
970087AG2-069 GEN
Solar/Wind Harmer
6.284
315722AD1-056 GEN
Solar/Wind Harmer
0.497
961671AG1-007 GEN
Solar/Wind Harmer
0.012
3146083TARBORO
Solar/Wind Harmer
0.077
3145493TOT1
Solar/Wind Harmer
0.342
3146233WITAKRS
Solar/Wind Harmer
0.302
316129AC1-054 GEN
Solar/Wind Harmer
0.277
316359AB2-059 GEN
Solar/Wind Harmer
0.264
316049AB1-081 GEN
Solar/Wind Harmer
0.421
3145543BTLEBRO
Solar/Wind Harmer
0.073
3145543BTLEBRO
Solar/Wind Harmer
0.059
3142053HEARTS
Solar/Wind Harmer
0.129
971065AG2-659 GEN
Solar/Wind Harmer
3.097
957481AF2-042 GEN
Solar/Wind Harmer
19.236
315693AD1-088 GEN
Solar/Wind Harmer
3.297
962491AG1-098 GEN
Solar/Wind Harmer
3.883
3143226MDLTHAN
Solar/Wind Harmer
0.067
315687AD1-152 GEN
Solar/Wind Harmer
0.002
316237AB2-079_GEN
Solar/Wind Harmer
0.001
970401AG2-262 GEN
Solar/Wind Harmer
0.348
970685AG2-442 GEN
Solar/Wind Harmer
4.283
315759AF1-018 GEN
50/50
8.574
3142433PROV 92
50/50
0.435
3142433PROV 92
50/50
0.435
3150611CHESTG7
50/50
1.286
3150631CHESTG8
50/50
1.265
971047AG2-646 GEN
50/50
36.002
315976AC1-164 GENA
Solar/Wind Harmer
32.344
316169AC1-164_GENC
Solar/Wind Harmer
27.943
315975AC1-164 GENB
Solar/Wind Harmer
0.957
316314AB2-024 C
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.002
3143873LANEXA
Solar/Wind Harmer
0.141
970189AG2-124 GEN
Solar/Wind Harmer
6.788
315662AE1-191 GEN
Solar/Wind Harmer
0.007
315666AE1-190 GEN
Solar/Wind Harmer
0.002
3141873WAN 176
Solar/Wind Harmer
0.045
3141913WHIT STONE
Solar/Wind Harmer
0.222
3138133OCRAN
Solar/Wind Harmer
0.066
3141783LANCAST
Solar/Wind Harmer
0.132
3141783LANCAST
Solar/Wind Harmer
0.088
962981AG1-147 GEN
Solar/Wind Harmer
8.11
970327AG2-215 GEN
Solar/Wind Harmer
7.076
3141813NORNECK
Solar/Wind Harmer
0.208
971167AH1-042 GEN
Solar/Wind Harmer
18.214
3138283WHITEMARSH
Solar/Wind Harmer
0.046
316223AC1-118
Solar/Wind Harmer
0.126
316312AB1-027
Solar/Wind Harmer
0.275
316132AB2-190 GEN1
Solar/Wind Harmer
0.809
316369SG1_INVT
Solar/Wind Harmer
0.006
972265AH1-717 GEN
Adder
11.153
3151201GRAVEL4
Adder
10.455
3151191GRAVEL3
Adder
10.323
3151211GRAVEL5
Adder
10.323
971445AH1-216 GEN
Solar/Wind Harmer
9.647
944491AF1-114 GEN
Solar/Wind Harmer
0
3152611GOSPORTB
Adder
1.587
3152621GOSPORTC
Adder
1.347
3152601GOSPORTA
Adder
1.242
3151081ELIZAR1
Adder
11.396
3151091ELIZAR2
Adder
11.198
316305AF2-043 C
Solar/Wind Harmer
0.001
957871AF2-081 GEN
Solar/Wind Harmer
6.034
319010AE1-072 C
Solar/Wind Harmer
0.608
3146406KITTY HAWK
Solar/Wind Harmer
0.015
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.082
316311AC2-079 GEN
Solar/Wind Harmer
3.454
315835AF2-110_GEN
Solar/Wind Harmer
0.824
3146486SUNBURY
Solar/Wind Harmer
0.119
3146486SUNBURY
Solar/Wind Harmer
0.119
313526AB2-022
Solar/Wind Harmer
0.064
316321Z2-027
Solar/Wind Harmer
0.022
3146396TANGLEW
Solar/Wind Harmer
0.325
3145176PASQUOTANK
Solar/Wind Harmer
0.073
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.111
3130156CHOWAN
Solar/Wind Harmer
0.111
3143316POE
Solar/Wind Harmer
0.433
315816AE2-034 GEN
Solar/Wind Harmer
0.455
971285AH1-108 GEN
Adder
0.794
3130546PLYMOUTH
Solar/Wind Harmer
0.102
315732AD1-074 GEN1
Solar/Wind Harmer
0.585
315733AD1-074 GEN2
Solar/Wind Harmer
0.585
315735AD1-075 GEN1
Solar/Wind Harmer
0.293
3146206CASHIE
Solar/Wind Harmer
0.099
970601AG2-382 GEN
Solar/Wind Harmer
3.715
965291AG1-394 GEN
Solar/Wind Harmer
0.437
3145893MURPHYS
Solar/Wind Harmer
0.261
3145893MURPHYS
Solar/Wind Harmer
0.097
316315AB2-025 C
Solar/Wind Harmer
0.078
315814AE2-033 C
Solar/Wind Harmer
7.609
3145513AHOSKIE
Solar/Wind Harmer
0.198
3145513AHOSKIE
Solar/Wind Harmer
0.095
3145683EARLEYS
Solar/Wind Harmer
0.188
3145683EARLEYS
Solar/Wind Harmer
0.094
3145683EARLEYS
Solar/Wind Harmer
0.094
3146043SEABORD
Solar/Wind Harmer
0.091
315607AA1-063A GEN
Solar/Wind Harmer
0.184
315652AC1-086 GEN
Solar/Wind Harmer
9.519
3146033SCOT NK
Solar/Wind Harmer
0.346
941031AE2-094 GEN
Solar/Wind Harmer
15.83
944011AF1-069 GEN
Solar/Wind Harmer
5.172
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3137643SOCKMAN
Solar/Wind Harmer
0.34
3145796HORNRTN
Solar/Wind Harmer
0.271
3145796HORNRTN
Solar/Wind Harmer
0.034
316233AE1-074 FULL
Solar/Wind Harmer
0.068
971281AH1-106 GEN
Solar/Wind Harmer
1.171
971283AH1-107 GEN
Solar/Wind Harmer
1.171
970673AG2-436 GEN
Solar/Wind Harmer
17.959
970673AG2-436 GEN
Solar/Wind Harmer
11.973
316005AA1-067
Solar/Wind Harmer
0.089
3145746EVERETS
Solar/Wind Harmer
0.329
3145746EVERETS
Solar/Wind Harmer
0.083
3145746EVERETS
Solar/Wind Harmer
0.083
3145746EVERETS
Solar/Wind Harmer
0.083
970181AG2-120 GEN
Solar/Wind Harmer
1.028
971967AH1-528 GEN
Solar/Wind Harmer
13.196
957861AF2-080 GEN
Solar/Wind Harmer
3.428
970085AG2-068 GEN
Solar/Wind Harmer
4.189
970581AG2-369 GEN
Solar/Wind Harmer
3.603
316420AA1-050 GEN
Solar/Wind Harmer
0.003
3145573BETHELC
Solar/Wind Harmer
0.077
3145573BETHELC
Solar/Wind Harmer
0.077
316319Z2-044 C
Solar/Wind Harmer
0
970831AG2-522 GEN
Solar/Wind Harmer
3.188
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
971443AH1-215 GEN
Solar/Wind Harmer
0.999
3144303KENBRDG
Solar/Wind Harmer
0.047
316118AC1-105 GEN
Solar/Wind Harmer
0.149
970683AG2-441 GEN
Solar/Wind Harmer
3.824
970681AG2-440 GEN
Solar/Wind Harmer
3.059
3147173SINAI
Solar/Wind Harmer
0.056
3147243WELCO
Solar/Wind Harmer
0.035
3146456SLIGO L269
Solar/Wind Harmer
0.121
971153AH1-033 GEN
Solar/Wind Harmer
1.397
970659AG2-427 GEN
Solar/Wind Harmer
1.277
316083AB2-161 GEN
Solar/Wind Harmer
0.002
970661AG2-428 GEN
Solar/Wind Harmer
2.552
316320Y1-086
Solar/Wind Harmer
0.001
316435W1029_GEN3
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.116
3146626S HERTFORD
Solar/Wind Harmer
0.115
3145273HOLLAND
Solar/Wind Harmer
0.085
315839AE2-212 C
Solar/Wind Harmer
0.001
3146376EDENTON
Solar/Wind Harmer
0.11
315614AA2-178 GEN
Solar/Wind Harmer
0.606
3150861SPRUNCD
Adder
0.485
971157AH1-035 GEN
Solar/Wind Harmer
1.23
315737AD1-076 GEN
Solar/Wind Harmer
1.31
3146206CASHIE
Solar/Wind Harmer
0.099
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
3145893MURPHYS
Solar/Wind Harmer
0.162
3145893MURPHYS
Solar/Wind Harmer
0.097
957521AF2-046 GEN
Solar/Wind Harmer
7.177
961681AG1-008 GEN
Solar/Wind Harmer
7.177
3156021HOLLOMANSOL
Solar/Wind Harmer
0.437
3146173TUNIS
Solar/Wind Harmer
0.095
316463AE2-346 GEN
Solar/Wind Harmer
0.081
316140AB2-099
Solar/Wind Harmer
0.034
962331AG1-082 GEN
Solar/Wind Harmer
1.01
3145963POPLR C
Solar/Wind Harmer
0.093
3146263WOODLND
Solar/Wind Harmer
0.091
316317KELFORD C
Solar/Wind Harmer
0.009
3145823KELFORD
Solar/Wind Harmer
0.09
316365GEN2_N
Solar/Wind Harmer
0.201
3142666NORTHAMPTON
Solar/Wind Harmer
0.088
3145933PARMELE
Solar/Wind Harmer
0.086
966801AG1-551 GEN
Solar/Wind Harmer
1.002
313506AB2-031 GEN
Solar/Wind Harmer
0.263
3145796HORNRTN
Solar/Wind Harmer
0.338
3145796HORNRTN
Solar/Wind Harmer
0.085
316210AC1-098 GEN
Solar/Wind Harmer
0.773
3145746EVERETS
Solar/Wind Harmer
0.083
3145746EVERETS
Solar/Wind Harmer
0.083
970917AG2-570 GEN
Solar/Wind Harmer
7.013
3147043LAWRENC
Solar/Wind Harmer
0.047
315724AD1-057 GEN
Solar/Wind Harmer
0.295
316327AA2-057 GEN
Solar/Wind Harmer
0.118
3146073TAR RVR
Solar/Wind Harmer
0.077
3146083TARBORO
Solar/Wind Harmer
0.077
3146233WITAKRS
Solar/Wind Harmer
0.38
3146233WITAKRS
Solar/Wind Harmer
0.052
3138543CONSLDL
Solar/Wind Harmer
0.05
961601AG1-000A GEN
Solar/Wind Harmer
5.236
3145543BTLEBRO
Solar/Wind Harmer
0.073
3145543BTLEBRO
Solar/Wind Harmer
0.073
971623AH1-311 GEN
Solar/Wind Harmer
0.147
316478AD1-087 GEN
Solar/Wind Harmer
0.24
316486AD2-202 GEN
Solar/Wind Harmer
0.07
3141316ARNOLDS
Adder
0.161
316131AB2-060 GEN
Solar/Wind Harmer
0.199
964241AG1-285 GEN
Solar/Wind Harmer
4.14
315785AD2-033 C
Solar/Wind Harmer
0.488
970257AG2-171 GEN
Solar/Wind Harmer
1.897
959311AF2-222 GEN
Solar/Wind Harmer
5.222
316473AC1-191 GEN
Solar/Wind Harmer
0.191
316248AF1-058 C
Solar/Wind Harmer
0
960061AF2-297 GEN
Solar/Wind Harmer
2.402
316065AD1-022 GEN
Solar/Wind Harmer
4.62
3145893MURPHYS
Solar/Wind Harmer
0.648
3145893MURPHYS
Solar/Wind Harmer
0.174
3144356SAPONY
Solar/Wind Harmer
0.808
3146173TUNIS
Solar/Wind Harmer
0.095
3146173TUNIS
Solar/Wind Harmer
0.095
3142666NORTHAMPTON
Solar/Wind Harmer
0.088
3142666NORTHAMPTON
Solar/Wind Harmer
0.088
3142666NORTHAMPTON
Solar/Wind Harmer
0.088
3142666NORTHAMPTON
Solar/Wind Harmer
0.053
316426AA2-053 GEN
Solar/Wind Harmer
0.293
3145933PARMELE
Solar/Wind Harmer
0.172
3145933PARMELE
Solar/Wind Harmer
0.086
316181AB2-040 GEN
Solar/Wind Harmer
0.123
3145593CAROLNA
Solar/Wind Harmer
0.085
3145593CAROLNA
Solar/Wind Harmer
0.085
966811AG1-552 GEN
Solar/Wind Harmer
0.922
3145593CAROLNA
Solar/Wind Harmer
0.106
3145796HORNRTN
Solar/Wind Harmer
0.254
3145783HORNRTN
Solar/Wind Harmer
1.502
3145783HORNRTN
Solar/Wind Harmer
1.202
3145783HORNRTN
Solar/Wind Harmer
0.376
3145783HORNRTN
Solar/Wind Harmer
0.15
3143526WINTERP
Solar/Wind Harmer
0.439
972185AH1-677 GEN
Adder
4.674
972187AH1-678 GEN
Adder
2.339
316274AC1-208 GEN
Solar/Wind Harmer
0.423
970933AG2-581 GEN
Solar/Wind Harmer
6.363
3145493TOT1
Solar/Wind Harmer
0.178
3145453TOT5
Solar/Wind Harmer
0.107
3145603CNETO
Solar/Wind Harmer
0.071
961601AG1-000A GEN
Solar/Wind Harmer
1.309
316263AC1-034 GEN
Solar/Wind Harmer
2.793
970099AG2-077 GEN
Solar/Wind Harmer
7.694
971223AH1-071 GEN
Solar/Wind Harmer
0.72
939181AE1-148 GEN
Solar/Wind Harmer
3.206
313527AB2-043 GEN
Solar/Wind Harmer
0.001
962561AG1-105 GEN
Solar/Wind Harmer
2.881
964791AG1-342 GEN
Solar/Wind Harmer
1.14
3146843MT LREL
Solar/Wind Harmer
0.059
3146843MT LREL
Solar/Wind Harmer
0.059
970323AG2-213 GEN
Solar/Wind Harmer
2.53
971775AH1-396 GEN
Solar/Wind Harmer
0.095
316034AC1-036 C
Solar/Wind Harmer
0.004
971741AH1-377 GEN
Solar/Wind Harmer
5.844
966871AG1-558 GEN
Solar/Wind Harmer
0.065
CPLELTFEXP_CPLE->PJM
CLTF
4.035
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.643
NYPJM->LTFIMP_NY
CLTF
0.699
LGEELTFEXP_LGEE->PJM
CLTF
0.151
WECLTFEXP_WEC->PJM
CLTF
0.071
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.999
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.074
MECLTFEXP_MEC->PJM
CLTF
0.569
SIGELTFEXP_SIGE->PJM
CLTF
0.015
LAGNLTFEXP_LAGN->PJM
CLTF
1.924
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.054
TVALTFEXP_TVA->PJM
CLTF
0.95

Details for 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: G2T567_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer
Contingency Name:
DVP_P4-2: G2T567_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.33 %
Rating:1107.0 MVA
Rating Type:C
MVA to Mitigate:1298.88
MW Contribution:36.12
Bus #Bus NameTypeMW Contribution
315749AE2-041 GEN
50/50
8.597
3141843SHACKLE
50/50
1.246
966661AG1-536 GEN
50/50
6.076
3142433PROV 92
50/50
0.437
3142433PROV 92
50/50
0.437
3150351NORNECKC2
50/50
2.209
3150641CHESTS8
50/50
0.654
944631AF1-128 GEN
50/50
102.747
971353AH1-157 GEN
50/50
17.022
970017AG2-010 GEN
50/50
11.407
3143096IRON208
50/50
0.703
3150771HOPHCF1
50/50
0.625
3141766HARMONY
Solar/Wind Harmer
-0.005
971777AH1-397 GEN
Solar/Wind Harmer
3.035
3138133OCRAN
Solar/Wind Harmer
-0.015
316159AE1-175 C
Solar/Wind Harmer
0.666
964211AG1-282 GEN
Solar/Wind Harmer
0.735
3141726DUNNSVL
Solar/Wind Harmer
-0.097
961951AG1-038 GEN
Solar/Wind Harmer
3.2
962861AG1-135 GEN
Solar/Wind Harmer
9.029
3142433PROV 92
Solar/Wind Harmer
-0.095
316337AD2-073 GEN
Solar/Wind Harmer
0.587
971317AH1-138 GEN
Solar/Wind Harmer
2.668
3138126ROCKLANDING
Solar/Wind Harmer
0.059
3142416OLDCHRC
Solar/Wind Harmer
-0.045
3142416OLDCHRC
Solar/Wind Harmer
-0.017
970129AG2-093 GEN
Solar/Wind Harmer
3.887
316458AB2-190 GEN2
Solar/Wind Harmer
1.721
971069AG2-661 GEN
Solar/Wind Harmer
2.664
972135AH1-637 GEN
Solar/Wind Harmer
1.659
971647AH1-324 GEN
Solar/Wind Harmer
8.279
961611AG1-000B GEN
Solar/Wind Harmer
8.096
3151171GRAVELC
Adder
1.535
3145336SMITFLD
Solar/Wind Harmer
-0.061
957971AF2-091 GEN
Solar/Wind Harmer
1.48
316072AD1-144
Solar/Wind Harmer
0.296
315671AE2-027_GEN
Solar/Wind Harmer
10.697
316375AC2-012 GEN
Solar/Wind Harmer
4.87
315759AF1-018 GEN
50/50
8.597
3142433PROV 92
50/50
0.437
3142433PROV 92
50/50
0.437
3150611CHESTG7
50/50
1.29
3150631CHESTG8
50/50
1.269
971047AG2-646 GEN
50/50
36.115
315976AC1-164 GENA
Solar/Wind Harmer
37.107
316169AC1-164_GENC
Solar/Wind Harmer
32.057
315975AC1-164 GENB
Solar/Wind Harmer
1.098
316314AB2-024 C
Solar/Wind Harmer
2.42
316059AD1-063 C
Solar/Wind Harmer
0.614
3143873LANEXA
Solar/Wind Harmer
-0.016
315662AE1-191 GEN
Solar/Wind Harmer
3.085
315666AE1-190 GEN
Solar/Wind Harmer
0.771
957601AF2-054 GEN
Solar/Wind Harmer
0.757
3141873WAN 176
Solar/Wind Harmer
-0.005
3141913WHIT STONE
Solar/Wind Harmer
-0.025
3138133OCRAN
Solar/Wind Harmer
-0.008
3141783LANCAST
Solar/Wind Harmer
-0.015
3141783LANCAST
Solar/Wind Harmer
-0.01
962981AG1-147 GEN
Solar/Wind Harmer
10.71
3141813NORNECK
Solar/Wind Harmer
-0.023
971167AH1-042 GEN
Solar/Wind Harmer
22.25
957831AF2-077 GEN
Solar/Wind Harmer
0.67
3138283WHITEMARSH
Solar/Wind Harmer
0.035
316223AC1-118
Solar/Wind Harmer
0.533
316312AB1-027
Solar/Wind Harmer
0.585
316132AB2-190 GEN1
Solar/Wind Harmer
1.721
316369SG1_INVT
Solar/Wind Harmer
2.986
972265AH1-717 GEN
Adder
11.202
3151201GRAVEL4
Adder
10.501
3151191GRAVEL3
Adder
10.368
3151211GRAVEL5
Adder
10.368
971445AH1-216 GEN
Solar/Wind Harmer
9.571
944491AF1-114 GEN
Solar/Wind Harmer
4.354
3152611GOSPORTB
Adder
1.595
3152621GOSPORTC
Adder
1.353
3152601GOSPORTA
Adder
1.249
3151081ELIZAR1
Adder
11.454
3151091ELIZAR2
Adder
11.255
316305AF2-043 C
Solar/Wind Harmer
0.415
957871AF2-081 GEN
Solar/Wind Harmer
6.845
319010AE1-072 C
Solar/Wind Harmer
2.757
3146406KITTY HAWK
Solar/Wind Harmer
0.011
315833AF1-017_GEN
Solar/Wind Harmer
2.581
316349AD2-085 GEN
Solar/Wind Harmer
1.209
316311AC2-079 GEN
Solar/Wind Harmer
6.853
315835AF2-110_GEN
Solar/Wind Harmer
1.695
3146486SUNBURY
Solar/Wind Harmer
-0.013
3146486SUNBURY
Solar/Wind Harmer
-0.013
313526AB2-022
Solar/Wind Harmer
0.362
316321Z2-027
Solar/Wind Harmer
0.36
3146396TANGLEW
Solar/Wind Harmer
0.245
3145176PASQUOTANK
Solar/Wind Harmer
-0.008
315611Z1-036_GEN2
Solar/Wind Harmer
3.157
3130156CHOWAN
Solar/Wind Harmer
-0.012
3130156CHOWAN
Solar/Wind Harmer
-0.012
3143316POE
Solar/Wind Harmer
-0.049
315816AE2-034 GEN
Solar/Wind Harmer
0.969
971285AH1-108 GEN
Adder
0.799
3130546PLYMOUTH
Solar/Wind Harmer
-0.012
315732AD1-074 GEN1
Solar/Wind Harmer
2.328
315733AD1-074 GEN2
Solar/Wind Harmer
2.328
315735AD1-075 GEN1
Solar/Wind Harmer
1.164
3146206CASHIE
Solar/Wind Harmer
-0.011
970601AG2-382 GEN
Solar/Wind Harmer
4.922
965291AG1-394 GEN
Solar/Wind Harmer
0.986
316318V4-068
Solar/Wind Harmer
0.273
3145893MURPHYS
Solar/Wind Harmer
-0.029
3145893MURPHYS
Solar/Wind Harmer
-0.011
316315AB2-025 C
Solar/Wind Harmer
0.295
315814AE2-033 C
Solar/Wind Harmer
10.13
3145513AHOSKIE
Solar/Wind Harmer
0.093
961941AG1-037 GEN
Solar/Wind Harmer
0.081
3145513AHOSKIE
Solar/Wind Harmer
-0.011
3145683EARLEYS
Solar/Wind Harmer
-0.021
3145683EARLEYS
Solar/Wind Harmer
-0.011
3145683EARLEYS
Solar/Wind Harmer
-0.011
3146043SEABORD
Solar/Wind Harmer
-0.01
315607AA1-063A GEN
Solar/Wind Harmer
1.031
315652AC1-086 GEN
Solar/Wind Harmer
11.023
3146033SCOT NK
Solar/Wind Harmer
-0.039
941031AE2-094 GEN
Solar/Wind Harmer
18.24
944011AF1-069 GEN
Solar/Wind Harmer
5.715
946281AF1-292 GEN
Solar/Wind Harmer
0.216
316087AB2-174 GEN
Solar/Wind Harmer
1.374
3137643SOCKMAN
Solar/Wind Harmer
-0.038
3145796HORNRTN
Solar/Wind Harmer
-0.03
3145796HORNRTN
Solar/Wind Harmer
-0.004
316233AE1-074 FULL
Solar/Wind Harmer
0.257
971281AH1-106 GEN
Solar/Wind Harmer
1.554
971283AH1-107 GEN
Solar/Wind Harmer
1.554
970673AG2-436 GEN
Solar/Wind Harmer
20.02
970673AG2-436 GEN
Solar/Wind Harmer
10.137
316005AA1-067
Solar/Wind Harmer
0.189
3145746EVERETS
Solar/Wind Harmer
-0.037
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
970181AG2-120 GEN
Solar/Wind Harmer
1.227
971967AH1-528 GEN
Solar/Wind Harmer
17.555
957861AF2-080 GEN
Solar/Wind Harmer
3.94
970085AG2-068 GEN
Solar/Wind Harmer
5.56
970581AG2-369 GEN
Solar/Wind Harmer
4.782
316420AA1-050 GEN
Solar/Wind Harmer
1.009
3145573BETHELC
Solar/Wind Harmer
-0.009
3145573BETHELC
Solar/Wind Harmer
-0.009
316319Z2-044 C
Solar/Wind Harmer
0.475
3150981CHESPKA
Adder
1.564
316294AC1-161 GEN
Solar/Wind Harmer
4.47
944591AF1-124 GEN
Solar/Wind Harmer
62.912
3142543TWELFTH
Solar/Wind Harmer
-0.001
316246AF1-032 C
Solar/Wind Harmer
0.279
316388AE2-253 GEN
Solar/Wind Harmer
0.925
3146456SLIGO L269
Solar/Wind Harmer
-0.014
970659AG2-427 GEN
Solar/Wind Harmer
7.247
316381AD1-082 GEN
Solar/Wind Harmer
1.251
970661AG2-428 GEN
Solar/Wind Harmer
14.474
316093AE2-104_GEN
Solar/Wind Harmer
3.942
3146516WINFALL
Solar/Wind Harmer
-0.042
3146516WINFALL
Solar/Wind Harmer
-0.013
315800Z1-036_GEN1
Solar/Wind Harmer
3.157
3130156CHOWAN
Solar/Wind Harmer
-0.012
3145663CRESWEL
Solar/Wind Harmer
-0.033
971163AH1-040 GEN
Solar/Wind Harmer
11.23
3150851SPRUNCC
Adder
0.488
939411AE1-173 GEN
Solar/Wind Harmer
57.793
3146206CASHIE
Solar/Wind Harmer
-0.011
971547AH1-271 GEN
Solar/Wind Harmer
2.813
3145893MURPHYS
Solar/Wind Harmer
-0.044
3145893MURPHYS
Solar/Wind Harmer
0.325
940641AE2-051 GEN
Solar/Wind Harmer
10.131
3146173TUNIS
Solar/Wind Harmer
-0.011
3145683EARLEYS
Solar/Wind Harmer
-0.011
3145963POPLR C
Solar/Wind Harmer
-0.011
316174AB2-169 GEN
Solar/Wind Harmer
1.602
3146263WOODLND
Solar/Wind Harmer
-0.01
3145823KELFORD
Solar/Wind Harmer
-0.01
316023GEN1_S
Solar/Wind Harmer
0.683
316190AA2-174 GEN
Solar/Wind Harmer
0.12
316011AB1-132 GEN
Solar/Wind Harmer
2.05
962571AG1-106 GEN
Solar/Wind Harmer
1.408
3146293MARTNCO
Solar/Wind Harmer
0.06
960081AF2-299 GEN
Solar/Wind Harmer
1.084
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.01
3145783HORNRTN
Solar/Wind Harmer
-0.01
3143526WINTERP
Solar/Wind Harmer
-0.049
316212AC1-099_GEN
Solar/Wind Harmer
0.823
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
971795AH1-408 GEN
Solar/Wind Harmer
6.851
316494AC1-189 GEN
Solar/Wind Harmer
0.969
970919AG2-571 GEN
Solar/Wind Harmer
2.828
3147043LAWRENC
Adder
0.717
970087AG2-069 GEN
Solar/Wind Harmer
8.34
315722AD1-056 GEN
Solar/Wind Harmer
0.93
961671AG1-007 GEN
Solar/Wind Harmer
0.11
3146083TARBORO
Solar/Wind Harmer
-0.009
3145493TOT1
Solar/Wind Harmer
0.258
3146233WITAKRS
Solar/Wind Harmer
-0.034
316129AC1-054 GEN
Solar/Wind Harmer
0.731
316359AB2-059 GEN
Solar/Wind Harmer
1.123
316049AB1-081 GEN
Solar/Wind Harmer
0.899
3145543BTLEBRO
Solar/Wind Harmer
-0.008
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3142053HEARTS
Solar/Wind Harmer
0.098
971065AG2-659 GEN
Solar/Wind Harmer
4.113
957481AF2-042 GEN
Solar/Wind Harmer
21.381
3150341NORNECKC1
50/50
2.321
3150341NORNECKC1
50/50
2.302
963611AG1-210 GEN
50/50
0.743
3150621CHESTS7
50/50
0.592
3150781HOPHCF2
50/50
0.625
3150791HOPHCF3
50/50
0.625
3150761HOPPOLC
50/50
0.397
971213AH1-066 GEN
50/50
0.548
316075AC2-137 C
Solar/Wind Harmer
0.758
3142946ENON
Solar/Wind Harmer
-0.003
316441AF1-014 GEN
Solar/Wind Harmer
1.74
316487AF1-042 GEN
Solar/Wind Harmer
3.2
958261AF2-120 GEN
Solar/Wind Harmer
9.3
316077AC2-138 C
Solar/Wind Harmer
0.495
3150691DARBY 3
Adder
10.751
3150701DARBY 4
Adder
10.726
3150681DARBY 2
Adder
10.713
3150671DARBY 1
Adder
10.701
316033AB2-134 GEN
Solar/Wind Harmer
5.389
315697AD1-025 GEN
Solar/Wind Harmer
3.38
316236AE1-162_GEN
Solar/Wind Harmer
0.464
316036AC1-147 C
Solar/Wind Harmer
0.38
3150991CHESPKB
Adder
1.312
3150991CHESPKB
Adder
1.28
316316AC1-027 C
Solar/Wind Harmer
0.428
3142956BIRDNECK
Solar/Wind Harmer
0.748
316185AD1-033 GEN
Solar/Wind Harmer
1.461
3145506HICKORY
Solar/Wind Harmer
-0.055
3145506HICKORY
Solar/Wind Harmer
-0.033
3145506HICKORY
Solar/Wind Harmer
-0.008
3142366NRTHEST
Adder
0.399
316339AD2-160 GEN
Solar/Wind Harmer
0.925
316018AA1-139 ULT2
Solar/Wind Harmer
1.173
316017AA1-139 ULT1
Solar/Wind Harmer
1.108
3137176SLIGO L2192
Solar/Wind Harmer
-0.054
3146456SLIGO L269
Solar/Wind Harmer
1.612
970657AG2-426 GEN
Solar/Wind Harmer
4.26
970657AG2-426 GEN
Solar/Wind Harmer
0.891
3130086AYDLETT
Solar/Wind Harmer
-0.054
3146386ELIZ CT
Solar/Wind Harmer
-0.013
316431W1029_GEN1
Solar/Wind Harmer
2.396
316433W1029_GEN2
Solar/Wind Harmer
2.396
3146516WINFALL
Solar/Wind Harmer
-0.013
3146516WINFALL
Solar/Wind Harmer
-0.013
3146516WINFALL
Solar/Wind Harmer
-0.013
944641AF1-129 GEN
Adder
55.701
316240AF1-291 C
Solar/Wind Harmer
0.393
3146626S HERTFORD
Solar/Wind Harmer
-0.013
3146626S HERTFORD
Solar/Wind Harmer
-0.013
315742AE1-103 GEN
Solar/Wind Harmer
1.307
3146376EDENTON
Solar/Wind Harmer
0.371
3146376EDENTON
Solar/Wind Harmer
0.371
316065AD1-022 GEN
Solar/Wind Harmer
5.673
3145893MURPHYS
Solar/Wind Harmer
0.306
3145893MURPHYS
Solar/Wind Harmer
-0.02
3144356SAPONY
Solar/Wind Harmer
0.381
3146173TUNIS
Solar/Wind Harmer
-0.011
3146173TUNIS
Solar/Wind Harmer
-0.011
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
316426AA2-053 GEN
Solar/Wind Harmer
0.991
3145933PARMELE
Solar/Wind Harmer
-0.019
3145933PARMELE
Solar/Wind Harmer
-0.01
316181AB2-040 GEN
Solar/Wind Harmer
1.344
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.083
3145593CAROLNA
Solar/Wind Harmer
0.08
3145796HORNRTN
Solar/Wind Harmer
-0.029
3145783HORNRTN
Solar/Wind Harmer
1.135
3145783HORNRTN
Solar/Wind Harmer
0.908
3145783HORNRTN
Solar/Wind Harmer
0.284
3145783HORNRTN
Solar/Wind Harmer
0.114
3143526WINTERP
Solar/Wind Harmer
-0.049
972185AH1-677 GEN
Adder
4.71
972187AH1-678 GEN
Adder
2.357
316274AC1-208 GEN
Solar/Wind Harmer
0.997
970933AG2-581 GEN
Solar/Wind Harmer
8.445
3145493TOT1
Solar/Wind Harmer
0.135
3145453TOT5
Solar/Wind Harmer
0.081
3145603CNETO
Solar/Wind Harmer
0.054
961601AG1-000A GEN
Solar/Wind Harmer
3.28
316263AC1-034 GEN
Solar/Wind Harmer
3.905
970099AG2-077 GEN
Solar/Wind Harmer
8.553
3141843SHACKLE
50/50
1.246
970575AG2-366 GEN
50/50
3.873
3142433PROV 92
50/50
0.437
3142433PROV 92
50/50
0.437
3150351NORNECKC2
50/50
2.247
3150921YORKTN3
50/50
4.644
3144216WINCHST
50/50
0.681
3143096IRON208
50/50
0.703
3143096IRON208
50/50
0.689
3150801HOPHCF4
50/50
0.909
971211AH1-065 GEN
50/50
1.097
3141766HARMONY
Solar/Wind Harmer
2.418
3142946ENON
Solar/Wind Harmer
-0.009
316203AE2-005 GEN
Solar/Wind Harmer
10.88
316280AD1-041 GEN
Solar/Wind Harmer
1.928
316156AD2-030 GEN
Solar/Wind Harmer
0.675
3141873WAN 176
Solar/Wind Harmer
3.001
316382AG1-145 C
Solar/Wind Harmer
0.748
962971AG1-146 GEN
Solar/Wind Harmer
4.59
316484AD2-074 GEN
Solar/Wind Harmer
6.116
970009AG2-005 GEN
Solar/Wind Harmer
3.037
316404AE1-155 C
Solar/Wind Harmer
4.63
970293AG2-193 GEN
Solar/Wind Harmer
2.776
3141906WESTMOR
Solar/Wind Harmer
-0.008
970737AG2-469 GEN
Solar/Wind Harmer
8.932
3142416OLDCHRC
Solar/Wind Harmer
1.751
970133AG2-095 GEN
Solar/Wind Harmer
1.95
970129AG2-093 GEN
Solar/Wind Harmer
9.595
315778AD1-151 GEN
Solar/Wind Harmer
14.584
961611AG1-000B GEN
Solar/Wind Harmer
3.454
3151221GRAVEL6
Adder
10.489
3151171GRAVELC
Adder
2.018
3145336SMITFLD
Solar/Wind Harmer
-0.006
3144536CHRHLND
Solar/Wind Harmer
-0.002
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
11.601
965281AG1-393 GEN
Solar/Wind Harmer
1.753
315773AC2-141 GEN
Solar/Wind Harmer
5.781
944581AF1-123 GEN
Solar/Wind Harmer
62.686
944601AF1-125 GEN
Solar/Wind Harmer
61.708
315813AE1-149 C
Solar/Wind Harmer
8.541
3146456SLIGO L269
Solar/Wind Harmer
-0.014
971153AH1-033 GEN
Solar/Wind Harmer
1.664
970659AG2-427 GEN
Solar/Wind Harmer
1.284
316083AB2-161 GEN
Solar/Wind Harmer
2.213
970661AG2-428 GEN
Solar/Wind Harmer
2.565
316320Y1-086
Solar/Wind Harmer
0.787
316435W1029_GEN3
Solar/Wind Harmer
2.396
3146516WINFALL
Solar/Wind Harmer
-0.013
3146626S HERTFORD
Solar/Wind Harmer
-0.013
3145273HOLLAND
Solar/Wind Harmer
-0.01
315839AE2-212 C
Solar/Wind Harmer
0.385
3146376EDENTON
Solar/Wind Harmer
-0.012
315614AA2-178 GEN
Solar/Wind Harmer
1.292
3150861SPRUNCD
Adder
0.488
971157AH1-035 GEN
Solar/Wind Harmer
1.448
315737AD1-076 GEN
Solar/Wind Harmer
2.188
3146206CASHIE
Solar/Wind Harmer
-0.011
3156081AA2-088 GEN
Solar/Wind Harmer
3.642
3145893MURPHYS
Solar/Wind Harmer
0.076
3145893MURPHYS
Solar/Wind Harmer
-0.011
957521AF2-046 GEN
Solar/Wind Harmer
8.591
961681AG1-008 GEN
Solar/Wind Harmer
8.591
3156021HOLLOMANSOL
Solar/Wind Harmer
1.466
3146173TUNIS
Solar/Wind Harmer
-0.011
316463AE2-346 GEN
Solar/Wind Harmer
0.173
316140AB2-099
Solar/Wind Harmer
0.072
962331AG1-082 GEN
Solar/Wind Harmer
1.339
3145963POPLR C
Solar/Wind Harmer
-0.011
3146263WOODLND
Solar/Wind Harmer
-0.01
316317KELFORD C
Solar/Wind Harmer
0.481
3145823KELFORD
Solar/Wind Harmer
-0.01
316365GEN2_N
Solar/Wind Harmer
0.683
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
3145933PARMELE
Solar/Wind Harmer
-0.01
966801AG1-551 GEN
Solar/Wind Harmer
1.217
966621AG1-532 GEN
Solar/Wind Harmer
0.196
313506AB2-031 GEN
Solar/Wind Harmer
0.774
3145796HORNRTN
Solar/Wind Harmer
-0.038
3145796HORNRTN
Solar/Wind Harmer
-0.01
316210AC1-098 GEN
Solar/Wind Harmer
1.481
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
970917AG2-570 GEN
Solar/Wind Harmer
22.341
3147043LAWRENC
Solar/Wind Harmer
-0.005
315724AD1-057 GEN
Solar/Wind Harmer
0.511
316327AA2-057 GEN
Solar/Wind Harmer
0.893
3146073TAR RVR
Solar/Wind Harmer
-0.009
3146083TARBORO
Solar/Wind Harmer
-0.009
3146233WITAKRS
Solar/Wind Harmer
0.18
3146233WITAKRS
Solar/Wind Harmer
-0.006
3138543CONSLDL
Solar/Wind Harmer
-0.006
961601AG1-000A GEN
Solar/Wind Harmer
3.321
3145543BTLEBRO
Solar/Wind Harmer
-0.008
3145543BTLEBRO
Solar/Wind Harmer
-0.008
3141316ARNOLDS
Adder
0.162
970831AG2-522 GEN
Solar/Wind Harmer
4.233
CPLELTFEXP_CPLE->PJM
CLTF
4.088
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.298
NYPJM->LTFIMP_NY
CLTF
0.668
LGEELTFEXP_LGEE->PJM
CLTF
0.185
WECLTFEXP_WEC->PJM
CLTF
0.09
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.709
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.259
MECLTFEXP_MEC->PJM
CLTF
0.651
SIGELTFEXP_SIGE->PJM
CLTF
0.018
LAGNLTFEXP_LAGN->PJM
CLTF
2.023
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.202
TVALTFEXP_TVA->PJM
CLTF
0.999

Details for 6CHESTF A-3CHESTFLD 230.0/115.0 kV Ckt 1 transformer l/o DVP_P4-2: 208T287_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6CHESTF A-3CHESTFLD 230.0/115.0 kV Ckt 1 transformer
Contingency Name:
DVP_P4-2: 208T287_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:120.86 %
Rating:284.0 MVA
Rating Type:C
MVA to Mitigate:343.23
MW Contribution:33.33
Bus #Bus NameTypeMW Contribution
3142946ENON
Solar/Wind Harmer
-0.005
970133AG2-095 GEN
Solar/Wind Harmer
0.998
970129AG2-093 GEN
Solar/Wind Harmer
4.316
315778AD1-151 GEN
Solar/Wind Harmer
5.893
3150641CHESTS8
50/50
0.603
944631AF1-128 GEN
50/50
94.821
970129AG2-093 GEN
Solar/Wind Harmer
1.748
316458AB2-190 GEN2
Solar/Wind Harmer
0.763
971069AG2-661 GEN
Solar/Wind Harmer
1.076
3142543TWELFTH
Solar/Wind Helper
0.02
3142433PROV 92
Solar/Wind Helper
0.705
3150611CHESTG7
50/50
1.19
3150631CHESTG8
50/50
1.171
971047AG2-646 GEN
50/50
33.329
316132AB2-190 GEN1
Solar/Wind Harmer
0.763
3150621CHESTS7
50/50
0.547
3142946ENON
Solar/Wind Harmer
-0.002
CPLELTFEXP_CPLE->PJM
CLTF
0.162
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.074
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.079
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.025
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.078
LAGNLTFEXP_LAGN->PJM
CLTF
0.001
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.275
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0

Details for 6CHESTF A-3CHESTFLD 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 208_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6CHESTF A-3CHESTFLD 230.0/115.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 208_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.74 %
Rating:250.04 MVA
Rating Type:B
MVA to Mitigate:261.89
MW Contribution:25.25
Bus #Bus NameTypeMW Contribution
3150641CHESTS8
50/50
0.457
944631AF1-128 GEN
50/50
71.822
3142543TWELFTH
Solar/Wind Helper
0.021
3142433PROV 92
Solar/Wind Helper
0.696
3142946ENON
Solar/Wind Harmer
0.038
3150611CHESTG7
50/50
0.902
3150631CHESTG8
50/50
0.887
971047AG2-646 GEN
50/50
25.245
3150621CHESTS7
50/50
0.414
3142946ENON
Solar/Wind Harmer
0.011
CPLELTFEXP_CPLE->PJM
CLTF
0.058
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.048
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.102
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.026
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.08
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.069
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 6CHESTF A-3CHESTFLD 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 211_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6CHESTF A-3CHESTFLD 230.0/115.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 211_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.28 %
Rating:250.04 MVA
Rating Type:B
MVA to Mitigate:258.24
MW Contribution:21.59
Bus #Bus NameTypeMW Contribution
3150611CHESTG7
50/50
0.771
3150631CHESTG8
50/50
0.759
971047AG2-646 GEN
50/50
21.588
316132AB2-190 GEN1
Solar/Wind Harmer
0.352
972265AH1-717 GEN
Adder
2.756
3151201GRAVEL4
Adder
2.583
3151191GRAVEL3
Adder
2.551
3151211GRAVEL5
Adder
2.551
3150801HOPHCF4
50/50
0.458
971211AH1-065 GEN
50/50
0.552
3143096IRON208
50/50
0.314
3143096IRON208
50/50
0.308
3142946ENON
Solar/Wind Harmer
0.032
970133AG2-095 GEN
Solar/Wind Harmer
0.745
970129AG2-093 GEN
Solar/Wind Harmer
4.036
315778AD1-151 GEN
Solar/Wind Harmer
4.722
3151221GRAVEL6
Adder
2.58
3150641CHESTS8
50/50
0.391
944631AF1-128 GEN
50/50
61.418
3150771HOPHCF1
50/50
0.315
3143096IRON208
50/50
0.314
970129AG2-093 GEN
Solar/Wind Harmer
1.899
316458AB2-190 GEN2
Solar/Wind Harmer
0.352
971069AG2-661 GEN
Solar/Wind Harmer
1.049
3142543TWELFTH
Solar/Wind Helper
0.021
3142433PROV 92
Solar/Wind Helper
0.741
3150621CHESTS7
50/50
0.354
3150781HOPHCF2
50/50
0.315
3150791HOPHCF3
50/50
0.315
3150761HOPPOLC
50/50
0.2
971213AH1-066 GEN
50/50
0.276
3142946ENON
Solar/Wind Harmer
0.01
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.033
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.066
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.037
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.208
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.043
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.134
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 6CHESTF A-3CHESTFLD 230.0/115.0 kV Ckt 1 transformer l/o DVP_P4-2: 211T2124_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6CHESTF A-3CHESTFLD 230.0/115.0 kV Ckt 1 transformer
Contingency Name:
DVP_P4-2: 211T2124_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.39 %
Rating:284.0 MVA
Rating Type:C
MVA to Mitigate:287.94
MW Contribution:23.38
Bus #Bus NameTypeMW Contribution
3150641CHESTS8
50/50
0.423
3150621CHESTS7
50/50
0.383
3142946ENON
Solar/Wind Harmer
-0.001
316033AB2-134 GEN
Solar/Wind Harmer
2.542
315697AD1-025 GEN
Solar/Wind Harmer
1.594
3142946ENON
Solar/Wind Harmer
-0.004
970133AG2-095 GEN
Solar/Wind Harmer
1.28
970129AG2-093 GEN
Solar/Wind Harmer
5.486
3143096IRON208
Adder
0.324
3143096IRON208
Adder
0.317
315778AD1-151 GEN
Solar/Wind Harmer
7.43
3151221GRAVEL6
Adder
3.254
3150611CHESTG7
50/50
0.835
3150631CHESTG8
50/50
0.821
971047AG2-646 GEN
50/50
23.376
316132AB2-190 GEN1
Solar/Wind Harmer
0.969
316369SG1_INVT
Solar/Wind Harmer
1.408
972265AH1-717 GEN
Adder
3.475
3151201GRAVEL4
Adder
3.258
3151191GRAVEL3
Adder
3.217
3151211GRAVEL5
Adder
3.217
944631AF1-128 GEN
50/50
66.505
970129AG2-093 GEN
Solar/Wind Harmer
2.222
316458AB2-190 GEN2
Solar/Wind Harmer
0.969
3143096IRON208
Adder
0.324
971069AG2-661 GEN
Solar/Wind Harmer
1.357
971647AH1-324 GEN
Solar/Wind Harmer
3.507
3142543TWELFTH
Solar/Wind Helper
0.022
3142433PROV 92
Solar/Wind Helper
0.728
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.031
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.115
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.062
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.29
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.058
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.181
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 6CHESTF A-3CHESTFLD 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 208-259_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6CHESTF A-3CHESTFLD 230.0/115.0 kV Ckt 1 transformer
Contingency Name:
DVP_P7-1: LN 208-259_SRT-S
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:100.44 %
Rating:284.0 MVA
Rating Type:C
MVA to Mitigate:285.25
MW Contribution:25.8
Bus #Bus NameTypeMW Contribution
3150621CHESTS7
50/50
0.423
3142946ENON
Solar/Wind Harmer
-0.001
3142946ENON
Solar/Wind Harmer
-0.004
970133AG2-095 GEN
Solar/Wind Harmer
0.811
3150611CHESTG7
50/50
0.921
3150631CHESTG8
50/50
0.906
971047AG2-646 GEN
50/50
25.795
3150641CHESTS8
50/50
0.467
944631AF1-128 GEN
50/50
73.386
3142543TWELFTH
Solar/Wind Helper
0.023
3142433PROV 92
Solar/Wind Helper
0.701
CPLELTFEXP_CPLE->PJM
CLTF
0.176
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.066
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.047
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.015
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.019
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.057
LAGNLTFEXP_LAGN->PJM
CLTF
0.023
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.309
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.011

Details for 6CHESTF A-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2049_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6CHESTF A-6CHCKAHM 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2049_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.69 %
Rating:584.68 MVA
Rating Type:B
MVA to Mitigate:635.47
MW Contribution:62.79
Bus #Bus NameTypeMW Contribution
3150641CHESTS8
50/50
1.137
944631AF1-128 GEN
50/50
178.64
3143096IRON208
50/50
1.104
3150771HOPHCF1
50/50
0.725
970129AG2-093 GEN
Solar/Wind Harmer
4.184
316458AB2-190 GEN2
Solar/Wind Harmer
0.772
971069AG2-661 GEN
Solar/Wind Harmer
2.213
315671AE2-027_GEN
Solar/Wind Harmer
6.36
971647AH1-324 GEN
Solar/Wind Harmer
4.018
3143526WINTERP
Solar/Wind Harmer
0.413
3142543TWELFTH
Solar/Wind Harmer
0.007
961611AG1-000B GEN
Solar/Wind Harmer
4.044
970659AG2-427 GEN
Solar/Wind Harmer
3.04
316381AD1-082 GEN
Solar/Wind Harmer
0.063
3141766HARMONY
Solar/Wind Helper
0.046
964211AG1-282 GEN
Solar/Wind Helper
0.298
3141726DUNNSVL
Solar/Wind Helper
0.885
316337AD2-073 GEN
Solar/Wind Helper
0.303
3138133OCRAN
Solar/Wind Helper
0.118
316159AE1-175 C
Solar/Wind Helper
0.281
3142416OLDCHRC
Solar/Wind Helper
0.344
3142416OLDCHRC
Solar/Wind Helper
0.132
3150611CHESTG7
50/50
2.243
3150631CHESTG8
50/50
2.207
971047AG2-646 GEN
50/50
62.791
970603AG2-384 GEN
50/50
1.872
316132AB2-190 GEN1
Solar/Wind Harmer
0.772
316369SG1_INVT
Solar/Wind Harmer
0.004
316233AE1-074 FULL
Solar/Wind Harmer
0.064
971281AH1-106 GEN
Solar/Wind Harmer
1.101
971283AH1-107 GEN
Solar/Wind Harmer
1.101
3143316POE
Solar/Wind Harmer
0.256
316059AD1-063 C
Solar/Wind Helper
0.232
3141813NORNECK
Solar/Wind Helper
0.208
3141783LANCAST
Solar/Wind Helper
0.119
3141783LANCAST
Solar/Wind Helper
0.079
3138133OCRAN
Solar/Wind Helper
0.059
3141913WHIT STONE
Solar/Wind Helper
0.197
957601AF2-054 GEN
Solar/Wind Helper
0.261
3141873WAN 176
Solar/Wind Helper
0.039
315662AE1-191 GEN
Solar/Wind Helper
1.03
315666AE1-190 GEN
Solar/Wind Helper
0.257
316223AC1-118
Solar/Wind Helper
0.278
3143873LANEXA
Solar/Wind Helper
0.109
957831AF2-077 GEN
Solar/Wind Helper
0.182
316312AB1-027
Solar/Wind Helper
0.252
3150621CHESTS7
50/50
1.03
3150781HOPHCF2
50/50
0.725
3150791HOPHCF3
50/50
0.725
3150761HOPPOLC
50/50
0.46
971213AH1-066 GEN
50/50
0.636
944641AF1-129 GEN
50/50
44.379
316033AB2-134 GEN
Solar/Wind Harmer
0.007
315697AD1-025 GEN
Solar/Wind Harmer
0.125
316240AF1-291 C
Solar/Wind Harmer
0.001
3143526WINTERP
Solar/Wind Harmer
0.413
970657AG2-426 GEN
Solar/Wind Harmer
2
970657AG2-426 GEN
Solar/Wind Harmer
0.419
316075AC2-137 C
Solar/Wind Helper
0.396
316077AC2-138 C
Solar/Wind Helper
0.196
316487AF1-042 GEN
Solar/Wind Helper
0.204
3143096IRON208
50/50
1.104
3143096IRON208
50/50
1.082
3150801HOPHCF4
50/50
1.054
971211AH1-065 GEN
50/50
1.272
970133AG2-095 GEN
Solar/Wind Harmer
1.717
970129AG2-093 GEN
Solar/Wind Harmer
8.891
315778AD1-151 GEN
Solar/Wind Harmer
9.957
965281AG1-393 GEN
Solar/Wind Harmer
1.019
315813AE1-149 C
Solar/Wind Harmer
4.138
315839AE2-212 C
Solar/Wind Harmer
0.001
961611AG1-000B GEN
Solar/Wind Harmer
2.056
970659AG2-427 GEN
Solar/Wind Harmer
0.665
316083AB2-161 GEN
Solar/Wind Harmer
0.001
316404AE1-155 C
Solar/Wind Helper
1.724
316484AD2-074 GEN
Solar/Wind Helper
0.39
316156AD2-030 GEN
Solar/Wind Helper
0.294
316280AD1-041 GEN
Solar/Wind Helper
0.643
316382AG1-145 C
Solar/Wind Helper
0.249
3141906WESTMOR
Solar/Wind Helper
0.073
CPLELTFEXP_CPLE->PJM
CLTF
0.692
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.201
NYPJM->LTFIMP_NY
CLTF
0.188
LGEELTFEXP_LGEE->PJM
CLTF
0.009
WECLTFEXP_WEC->PJM
CLTF
0.002
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.461
MECLTFEXP_MEC->PJM
CLTF
0.055
SIGELTFEXP_SIGE->PJM
CLTF
0.001
LAGNLTFEXP_LAGN->PJM
CLTF
0.295
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.372
TVALTFEXP_TVA->PJM
CLTF
0.147

Details for 6CHESTF A-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2050_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6CHESTF A-6CHCKAHM 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2050_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.83 %
Rating:584.68 MVA
Rating Type:B
MVA to Mitigate:612.9
MW Contribution:62.79
Bus #Bus NameTypeMW Contribution
3150641CHESTS8
50/50
1.137
944631AF1-128 GEN
50/50
178.638
3143096IRON208
50/50
1.104
3150771HOPHCF1
50/50
0.725
970129AG2-093 GEN
Solar/Wind Harmer
4.184
316458AB2-190 GEN2
Solar/Wind Harmer
0.772
971069AG2-661 GEN
Solar/Wind Harmer
2.213
315671AE2-027_GEN
Solar/Wind Harmer
6.36
971647AH1-324 GEN
Solar/Wind Harmer
4.018
3143526WINTERP
Solar/Wind Harmer
0.413
3142543TWELFTH
Solar/Wind Harmer
0.007
961611AG1-000B GEN
Solar/Wind Harmer
4.044
970659AG2-427 GEN
Solar/Wind Harmer
3.04
316381AD1-082 GEN
Solar/Wind Harmer
0.063
3141766HARMONY
Solar/Wind Helper
0.046
964211AG1-282 GEN
Solar/Wind Helper
0.298
3141726DUNNSVL
Solar/Wind Helper
0.885
316337AD2-073 GEN
Solar/Wind Helper
0.303
3138133OCRAN
Solar/Wind Helper
0.118
316159AE1-175 C
Solar/Wind Helper
0.281
3142416OLDCHRC
Solar/Wind Helper
0.344
3142416OLDCHRC
Solar/Wind Helper
0.132
3143096IRON208
50/50
1.104
3143096IRON208
50/50
1.082
3150801HOPHCF4
50/50
1.054
971211AH1-065 GEN
50/50
1.272
3142946ENON
Solar/Wind Harmer
0.118
970133AG2-095 GEN
Solar/Wind Harmer
1.717
970129AG2-093 GEN
Solar/Wind Harmer
8.891
315778AD1-151 GEN
Solar/Wind Harmer
9.957
965281AG1-393 GEN
Solar/Wind Harmer
1.019
315813AE1-149 C
Solar/Wind Harmer
4.138
315839AE2-212 C
Solar/Wind Harmer
0.001
961611AG1-000B GEN
Solar/Wind Harmer
2.056
970659AG2-427 GEN
Solar/Wind Harmer
0.665
316083AB2-161 GEN
Solar/Wind Harmer
0.001
316404AE1-155 C
Solar/Wind Helper
1.724
316484AD2-074 GEN
Solar/Wind Helper
0.39
316156AD2-030 GEN
Solar/Wind Helper
0.294
316280AD1-041 GEN
Solar/Wind Helper
0.644
316382AG1-145 C
Solar/Wind Helper
0.249
3141906WESTMOR
Solar/Wind Helper
0.073
3150611CHESTG7
50/50
2.243
3150631CHESTG8
50/50
2.207
971047AG2-646 GEN
50/50
62.79
970603AG2-384 GEN
50/50
1.872
316132AB2-190 GEN1
Solar/Wind Harmer
0.772
316369SG1_INVT
Solar/Wind Harmer
0.004
316233AE1-074 FULL
Solar/Wind Harmer
0.064
971281AH1-106 GEN
Solar/Wind Harmer
1.101
971283AH1-107 GEN
Solar/Wind Harmer
1.101
3143316POE
Solar/Wind Harmer
0.256
316059AD1-063 C
Solar/Wind Helper
0.232
3141813NORNECK
Solar/Wind Helper
0.208
3141783LANCAST
Solar/Wind Helper
0.119
3141783LANCAST
Solar/Wind Helper
0.079
3138133OCRAN
Solar/Wind Helper
0.059
3141913WHIT STONE
Solar/Wind Helper
0.197
957601AF2-054 GEN
Solar/Wind Helper
0.261
3141873WAN 176
Solar/Wind Helper
0.039
315662AE1-191 GEN
Solar/Wind Helper
1.03
315666AE1-190 GEN
Solar/Wind Helper
0.257
316223AC1-118
Solar/Wind Helper
0.278
3143873LANEXA
Solar/Wind Helper
0.109
957831AF2-077 GEN
Solar/Wind Helper
0.182
316312AB1-027
Solar/Wind Helper
0.252
3150621CHESTS7
50/50
1.03
3150781HOPHCF2
50/50
0.725
3150791HOPHCF3
50/50
0.725
3150761HOPPOLC
50/50
0.46
971213AH1-066 GEN
50/50
0.636
944641AF1-129 GEN
50/50
44.377
3142946ENON
Solar/Wind Harmer
0.035
316033AB2-134 GEN
Solar/Wind Harmer
0.007
315697AD1-025 GEN
Solar/Wind Harmer
0.125
316240AF1-291 C
Solar/Wind Harmer
0.001
3143526WINTERP
Solar/Wind Harmer
0.413
970657AG2-426 GEN
Solar/Wind Harmer
2
970657AG2-426 GEN
Solar/Wind Harmer
0.419
316075AC2-137 C
Solar/Wind Helper
0.396
316077AC2-138 C
Solar/Wind Helper
0.196
316487AF1-042 GEN
Solar/Wind Helper
0.204
CPLELTFEXP_CPLE->PJM
CLTF
0.692
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.197
NYPJM->LTFIMP_NY
CLTF
0.188
LGEELTFEXP_LGEE->PJM
CLTF
0.008
WECLTFEXP_WEC->PJM
CLTF
0.002
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.46
MECLTFEXP_MEC->PJM
CLTF
0.054
SIGELTFEXP_SIGE->PJM
CLTF
0.001
LAGNLTFEXP_LAGN->PJM
CLTF
0.295
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.371
TVALTFEXP_TVA->PJM
CLTF
0.147

Details for 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6CHESTF A-6IRON208 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 557_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.61 %
Rating:663.64 MVA
Rating Type:B
MVA to Mitigate:740.71
MW Contribution:45.73
Bus #Bus NameTypeMW Contribution
3150611CHESTG7
50/50
1.633
3150631CHESTG8
50/50
1.607
971047AG2-646 GEN
50/50
45.726
315759AF1-018 GEN
50/50
3.414
316132AB2-190 GEN1
Solar/Wind Harmer
0.67
315976AC1-164 GENA
Solar/Wind Harmer
12.162
316169AC1-164_GENC
Solar/Wind Harmer
10.507
315975AC1-164 GENB
Solar/Wind Harmer
0.36
316369SG1_INVT
Solar/Wind Harmer
0.004
316314AB2-024 C
Solar/Wind Harmer
0
316059AD1-063 C
Solar/Wind Harmer
0.001
972265AH1-717 GEN
Adder
7.261
3151201GRAVEL4
Adder
6.807
3151191GRAVEL3
Adder
6.721
3151211GRAVEL5
Adder
6.721
3143873LANEXA
Solar/Wind Harmer
0.056
970189AG2-124 GEN
Solar/Wind Harmer
2.733
315662AE1-191 GEN
Solar/Wind Harmer
0.003
315666AE1-190 GEN
Solar/Wind Harmer
0.001
3141873WAN 176
Solar/Wind Harmer
0.018
3141913WHIT STONE
Solar/Wind Harmer
0.09
3138133OCRAN
Solar/Wind Harmer
0.027
3141783LANCAST
Solar/Wind Harmer
0.053
3141783LANCAST
Solar/Wind Harmer
0.035
3138283WHITEMARSH
Solar/Wind Harmer
0.02
962981AG1-147 GEN
Solar/Wind Harmer
3.244
970327AG2-215 GEN
Solar/Wind Harmer
2.818
3142433PROV 92
Adder
0.165
3142433PROV 92
Adder
0.165
971445AH1-216 GEN
Solar/Wind Harmer
5.957
971167AH1-042 GEN
Solar/Wind Harmer
7.355
3141813NORNECK
Solar/Wind Harmer
0.081
3152611GOSPORTB
Adder
0.865
3152621GOSPORTC
Adder
0.734
3152601GOSPORTA
Adder
0.677
3151081ELIZAR1
Adder
6.186
3151091ELIZAR2
Adder
6.079
316223AC1-118
Solar/Wind Harmer
0.048
315833AF1-017_GEN
Solar/Wind Harmer
0
316349AD2-085 GEN
Solar/Wind Harmer
0.045
316311AC2-079 GEN
Solar/Wind Harmer
1.899
316305AF2-043 C
Solar/Wind Harmer
0.001
957871AF2-081 GEN
Solar/Wind Harmer
3.21
319010AE1-072 C
Solar/Wind Harmer
0.323
315835AF2-110_GEN
Solar/Wind Harmer
0.44
3146406KITTY HAWK
Solar/Wind Harmer
0.008
313526AB2-022
Solar/Wind Harmer
0.034
3146486SUNBURY
Solar/Wind Harmer
0.063
3146486SUNBURY
Solar/Wind Harmer
0.063
316321Z2-027
Solar/Wind Harmer
0.012
3146396TANGLEW
Solar/Wind Harmer
0.172
3145176PASQUOTANK
Solar/Wind Harmer
0.039
315611Z1-036_GEN2
Solar/Wind Harmer
0
3130156CHOWAN
Solar/Wind Harmer
0.057
3130156CHOWAN
Solar/Wind Harmer
0.057
316233AE1-074 FULL
Solar/Wind Helper
0.475
3150621CHESTS7
50/50
0.75
3150781HOPHCF2
50/50
0.557
3150791HOPHCF3
50/50
0.557
3150761HOPPOLC
50/50
0.353
971213AH1-066 GEN
50/50
0.488
3142946ENON
Solar/Wind Harmer
0.022
316033AB2-134 GEN
Solar/Wind Harmer
0.007
315697AD1-025 GEN
Solar/Wind Harmer
0.127
958261AF2-120 GEN
Solar/Wind Harmer
2.785
316236AE1-162_GEN
Solar/Wind Harmer
0.001
316075AC2-137 C
Solar/Wind Harmer
0.023
316077AC2-138 C
Solar/Wind Harmer
0
3150341NORNECKC1
Adder
0.851
3150341NORNECKC1
Adder
0.845
970657AG2-426 GEN
Solar/Wind Harmer
2.421
3150801HOPHCF4
50/50
0.81
971211AH1-065 GEN
50/50
0.977
315749AE2-041 GEN
50/50
3.414
3151161SURRY 1
50/50
3.592
3142946ENON
Solar/Wind Harmer
0.072
970133AG2-095 GEN
Solar/Wind Harmer
1.318
970129AG2-093 GEN
Solar/Wind Harmer
7.619
315778AD1-151 GEN
Solar/Wind Harmer
9.439
961611AG1-000B GEN
Solar/Wind Harmer
2.697
3141766HARMONY
Solar/Wind Harmer
1.28
316382AG1-145 C
Solar/Wind Harmer
0.001
3151221GRAVEL6
Adder
6.799
3151171GRAVELC
Adder
1.308
3141843SHACKLE
Adder
0.471
316203AE2-005 GEN
Solar/Wind Harmer
0
316280AD1-041 GEN
Solar/Wind Harmer
0.002
316156AD2-030 GEN
Solar/Wind Harmer
0.068
3141873WAN 176
Solar/Wind Harmer
1.624
962971AG1-146 GEN
Solar/Wind Harmer
1.39
970009AG2-005 GEN
Solar/Wind Harmer
0.641
3142433PROV 92
Adder
0.165
3142433PROV 92
Adder
0.165
3144216WINCHST
Adder
0.319
316404AE1-155 C
Solar/Wind Harmer
0.019
3145336SMITFLD
Solar/Wind Harmer
0.033
3150641CHESTS8
50/50
0.828
944631AF1-128 GEN
50/50
130.091
3150771HOPHCF1
50/50
0.557
3152331SURRY 2
50/50
2.862
970129AG2-093 GEN
Solar/Wind Harmer
3.585
316458AB2-190 GEN2
Solar/Wind Harmer
0.67
971069AG2-661 GEN
Solar/Wind Harmer
2.098
971647AH1-324 GEN
Solar/Wind Harmer
4.574
961611AG1-000B GEN
Solar/Wind Harmer
5.304
3141766HARMONY
Solar/Wind Harmer
0.019
316159AE1-175 C
Solar/Wind Harmer
0.081
3151171GRAVELC
Adder
0.995
971777AH1-397 GEN
Solar/Wind Harmer
0.243
3141843SHACKLE
Adder
0.471
3138133OCRAN
Solar/Wind Harmer
0.054
971317AH1-138 GEN
Solar/Wind Harmer
0.639
3142433PROV 92
Solar/Wind Harmer
0.34
3142433PROV 92
Adder
0.165
3142433PROV 92
Adder
0.165
962861AG1-135 GEN
Solar/Wind Harmer
2.709
3141726DUNNSVL
Solar/Wind Harmer
0.337
3138126ROCKLANDING
Solar/Wind Harmer
0.039
3145336SMITFLD
Solar/Wind Harmer
0.335
3150351NORNECKC2
Adder
0.811
316337AD2-073 GEN
Solar/Wind Harmer
0.065
316072AD1-144
Solar/Wind Harmer
0.026
970659AG2-427 GEN
Solar/Wind Harmer
3.376
316381AD1-082 GEN
Solar/Wind Harmer
0.072
970661AG2-428 GEN
Solar/Wind Harmer
6.816
316375AC2-012 GEN
Solar/Wind Harmer
0.002
3150981CHESPKA
Adder
0.848
316246AF1-032 C
Solar/Wind Harmer
0.029
316388AE2-253 GEN
Solar/Wind Harmer
0.202
944591AF1-124 GEN
Solar/Wind Harmer
14.529
3146456SLIGO L269
Solar/Wind Harmer
0.064
316093AE2-104_GEN
Solar/Wind Harmer
1.078
316294AC1-161 GEN
Solar/Wind Harmer
1.078
3146516WINFALL
Solar/Wind Harmer
0.198
3146516WINFALL
Solar/Wind Harmer
0.061
315671AE2-027_GEN
Solar/Wind Harmer
3.892
315800Z1-036_GEN1
Solar/Wind Harmer
0
3130156CHOWAN
Solar/Wind Harmer
0.057
3143526WINTERP
Solar/Wind Helper
1.618
3143226MDLTHAN
Solar/Wind Helper
0.118
970657AG2-426 GEN
Solar/Wind Harmer
0.507
316036AC1-147 C
Solar/Wind Harmer
0.013
3150991CHESPKB
Adder
0.712
3150991CHESPKB
Adder
0.694
316316AC1-027 C
Solar/Wind Harmer
0.064
3142956BIRDNECK
Solar/Wind Harmer
0
316185AD1-033 GEN
Solar/Wind Harmer
0.002
3145506HICKORY
Solar/Wind Harmer
0.26
3145506HICKORY
Solar/Wind Harmer
0.156
3145506HICKORY
Solar/Wind Harmer
0.039
316339AD2-160 GEN
Solar/Wind Harmer
0.105
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
316017AA1-139 ULT1
Solar/Wind Harmer
0.036
3137176SLIGO L2192
Solar/Wind Harmer
0.256
3146456SLIGO L269
Solar/Wind Harmer
1.137
3130086AYDLETT
Solar/Wind Harmer
0.256
3146386ELIZ CT
Solar/Wind Harmer
0.063
316431W1029_GEN1
Solar/Wind Harmer
0
316433W1029_GEN2
Solar/Wind Harmer
0
3146516WINFALL
Solar/Wind Harmer
0.061
3146516WINFALL
Solar/Wind Harmer
0.061
3146516WINFALL
Solar/Wind Harmer
0.061
3146626S HERTFORD
Solar/Wind Harmer
0.06
3146626S HERTFORD
Solar/Wind Harmer
0.06
315742AE1-103 GEN
Solar/Wind Harmer
0.001
3146376EDENTON
Solar/Wind Harmer
0.255
3146376EDENTON
Solar/Wind Harmer
0.255
3143526WINTERP
Solar/Wind Helper
1.618
3150921YORKTN3
Adder
2.093
3150351NORNECKC2
Adder
0.824
3144536CHRHLND
Solar/Wind Harmer
0.011
315813AE1-149 C
Solar/Wind Harmer
3.817
970659AG2-427 GEN
Solar/Wind Harmer
0.738
316083AB2-161 GEN
Solar/Wind Harmer
0.001
970661AG2-428 GEN
Solar/Wind Harmer
1.45
3144873MCLAUGH
Solar/Wind Harmer
0.002
3151101ELIZAR3
Adder
6.266
3141906WESTMOR
Solar/Wind Harmer
0.027
944581AF1-123 GEN
Solar/Wind Harmer
14.477
944601AF1-125 GEN
Solar/Wind Harmer
14.254
3146456SLIGO L269
Solar/Wind Harmer
0.064
971153AH1-033 GEN
Solar/Wind Harmer
0.742
316320Y1-086
Solar/Wind Harmer
0
315773AC2-141 GEN
Solar/Wind Harmer
2.272
316435W1029_GEN3
Solar/Wind Harmer
0
3146516WINFALL
Solar/Wind Harmer
0.061
965281AG1-393 GEN
Solar/Wind Harmer
0.649
3146626S HERTFORD
Solar/Wind Harmer
0.06
970737AG2-469 GEN
Solar/Wind Harmer
2.555
3145273HOLLAND
Solar/Wind Harmer
0.045
3146376EDENTON
Solar/Wind Harmer
0.057
CPLELTFEXP_CPLE->PJM
CLTF
1.734
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.554
NYPJM->LTFIMP_NY
CLTF
0.33
LGEELTFEXP_LGEE->PJM
CLTF
0.057
WECLTFEXP_WEC->PJM
CLTF
0.026
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.657
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.279
MECLTFEXP_MEC->PJM
CLTF
0.223
SIGELTFEXP_SIGE->PJM
CLTF
0.006
LAGNLTFEXP_LAGN->PJM
CLTF
0.804
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.434
TVALTFEXP_TVA->PJM
CLTF
0.397

Details for 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6CHESTF A-6IRON208 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.5 %
Rating:663.64 MVA
Rating Type:B
MVA to Mitigate:720.05
MW Contribution:42.99
Bus #Bus NameTypeMW Contribution
3150641CHESTS8
50/50
0.778
944631AF1-128 GEN
50/50
122.303
3150771HOPHCF1
50/50
0.513
970129AG2-093 GEN
Solar/Wind Harmer
3.268
316458AB2-190 GEN2
Solar/Wind Harmer
0.61
971069AG2-661 GEN
Solar/Wind Harmer
1.894
971647AH1-324 GEN
Solar/Wind Harmer
4.071
961611AG1-000B GEN
Solar/Wind Harmer
4.675
3151171GRAVELC
Adder
0.865
3141766HARMONY
Solar/Wind Harmer
0.015
316159AE1-175 C
Solar/Wind Harmer
0.063
971777AH1-397 GEN
Solar/Wind Harmer
0.193
3141843SHACKLE
Adder
0.374
3145336SMITFLD
Solar/Wind Harmer
0.288
3138133OCRAN
Solar/Wind Harmer
0.042
3142433PROV 92
Solar/Wind Harmer
0.273
3142433PROV 92
Adder
0.133
3142433PROV 92
Adder
0.133
962861AG1-135 GEN
Solar/Wind Harmer
2.133
3138126ROCKLANDING
Solar/Wind Harmer
0.03
3141726DUNNSVL
Solar/Wind Harmer
0.265
971317AH1-138 GEN
Solar/Wind Harmer
0.495
3150351NORNECKC2
Adder
0.637
970659AG2-427 GEN
Solar/Wind Harmer
3.065
316381AD1-082 GEN
Solar/Wind Harmer
0.066
970661AG2-428 GEN
Solar/Wind Harmer
6.114
316072AD1-144
Solar/Wind Harmer
0.022
3150611CHESTG7
50/50
1.535
3150631CHESTG8
50/50
1.511
971047AG2-646 GEN
50/50
42.989
316132AB2-190 GEN1
Solar/Wind Harmer
0.61
316369SG1_INVT
Solar/Wind Harmer
0.004
315976AC1-164 GENA
Solar/Wind Harmer
9.735
316169AC1-164_GENC
Solar/Wind Harmer
8.41
315975AC1-164 GENB
Solar/Wind Harmer
0.288
972265AH1-717 GEN
Adder
6.312
3151201GRAVEL4
Adder
5.917
3151191GRAVEL3
Adder
5.842
3151211GRAVEL5
Adder
5.842
316314AB2-024 C
Solar/Wind Harmer
0
316059AD1-063 C
Solar/Wind Harmer
0
3143873LANEXA
Solar/Wind Harmer
0.045
970189AG2-124 GEN
Solar/Wind Harmer
2.166
971445AH1-216 GEN
Solar/Wind Harmer
5.125
315662AE1-191 GEN
Solar/Wind Harmer
0.002
315666AE1-190 GEN
Solar/Wind Harmer
0.001
3141873WAN 176
Solar/Wind Harmer
0.014
3141913WHIT STONE
Solar/Wind Harmer
0.071
3138133OCRAN
Solar/Wind Harmer
0.021
3141783LANCAST
Solar/Wind Harmer
0.042
3141783LANCAST
Solar/Wind Harmer
0.028
3138283WHITEMARSH
Solar/Wind Harmer
0.016
962981AG1-147 GEN
Solar/Wind Harmer
2.557
3142433PROV 92
Adder
0.133
3142433PROV 92
Adder
0.133
970327AG2-215 GEN
Solar/Wind Harmer
2.22
971167AH1-042 GEN
Solar/Wind Harmer
5.919
3141813NORNECK
Solar/Wind Harmer
0.064
315833AF1-017_GEN
Solar/Wind Harmer
0
316349AD2-085 GEN
Solar/Wind Harmer
0.04
316311AC2-079 GEN
Solar/Wind Harmer
1.663
3152611GOSPORTB
Adder
0.725
3152621GOSPORTC
Adder
0.615
3152601GOSPORTA
Adder
0.568
3151081ELIZAR1
Adder
5.179
3151091ELIZAR2
Adder
5.089
316233AE1-074 FULL
Solar/Wind Helper
0.525
316337AD2-073 GEN
Solar/Wind Harmer
0.051
316375AC2-012 GEN
Solar/Wind Harmer
0.001
3150981CHESPKA
Adder
0.711
3143526WINTERP
Solar/Wind Helper
1.788
3143226MDLTHAN
Solar/Wind Helper
0.157
3150621CHESTS7
50/50
0.705
3150781HOPHCF2
50/50
0.513
3150791HOPHCF3
50/50
0.513
3150761HOPPOLC
50/50
0.325
971213AH1-066 GEN
50/50
0.45
3142946ENON
Solar/Wind Harmer
0.02
316033AB2-134 GEN
Solar/Wind Harmer
0.006
315697AD1-025 GEN
Solar/Wind Harmer
0.114
316236AE1-162_GEN
Solar/Wind Harmer
0.001
958261AF2-120 GEN
Solar/Wind Harmer
2.192
316077AC2-138 C
Solar/Wind Harmer
0
3150341NORNECKC1
Adder
0.669
3150341NORNECKC1
Adder
0.663
316075AC2-137 C
Solar/Wind Harmer
0.018
970657AG2-426 GEN
Solar/Wind Harmer
2.184
970657AG2-426 GEN
Solar/Wind Harmer
0.458
316036AC1-147 C
Solar/Wind Harmer
0.011
3150801HOPHCF4
50/50
0.746
971211AH1-065 GEN
50/50
0.9
3151161SURRY 1
50/50
3.123
3142946ENON
Solar/Wind Harmer
0.066
970133AG2-095 GEN
Solar/Wind Harmer
1.215
970129AG2-093 GEN
Solar/Wind Harmer
6.944
315778AD1-151 GEN
Solar/Wind Harmer
8.525
961611AG1-000B GEN
Solar/Wind Harmer
2.377
3151221GRAVEL6
Adder
5.91
3151171GRAVELC
Adder
1.137
3141766HARMONY
Solar/Wind Harmer
1.013
316382AG1-145 C
Solar/Wind Harmer
0.001
3141843SHACKLE
Adder
0.374
316203AE2-005 GEN
Solar/Wind Harmer
0
316280AD1-041 GEN
Solar/Wind Harmer
0.001
316156AD2-030 GEN
Solar/Wind Harmer
0.053
3141873WAN 176
Solar/Wind Harmer
1.283
3145336SMITFLD
Solar/Wind Harmer
0.029
962971AG1-146 GEN
Solar/Wind Harmer
1.096
3142433PROV 92
Adder
0.133
3142433PROV 92
Adder
0.133
970009AG2-005 GEN
Solar/Wind Harmer
0.505
3144216WINCHST
Adder
0.253
316404AE1-155 C
Solar/Wind Harmer
0.015
315813AE1-149 C
Solar/Wind Harmer
3.52
3150921YORKTN3
Adder
1.637
3150351NORNECKC2
Adder
0.647
970659AG2-427 GEN
Solar/Wind Harmer
0.67
316083AB2-161 GEN
Solar/Wind Harmer
0.001
970661AG2-428 GEN
Solar/Wind Harmer
1.3
3144536CHRHLND
Solar/Wind Harmer
0.009
3144873MCLAUGH
Solar/Wind Harmer
0.001
3151101ELIZAR3
Adder
5.246
3150991CHESPKB
Adder
0.596
3150991CHESPKB
Adder
0.582
3143526WINTERP
Solar/Wind Helper
1.788
CPLELTFEXP_CPLE->PJM
CLTF
1.919
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.103
NYPJM->LTFIMP_NY
CLTF
0.354
LGEELTFEXP_LGEE->PJM
CLTF
0.127
WECLTFEXP_WEC->PJM
CLTF
0.063
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.024
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.746
MECLTFEXP_MEC->PJM
CLTF
0.397
SIGELTFEXP_SIGE->PJM
CLTF
0.011
LAGNLTFEXP_LAGN->PJM
CLTF
1.059
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.936
TVALTFEXP_TVA->PJM
CLTF
0.526

Details for 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T557_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6CHESTF A-6IRON208 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T557_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.22 %
Rating:811.0 MVA
Rating Type:C
MVA to Mitigate:828.99
MW Contribution:45.09
Bus #Bus NameTypeMW Contribution
3150641CHESTS8
50/50
0.816
944631AF1-128 GEN
50/50
128.267
3150771HOPHCF1
50/50
0.543
970129AG2-093 GEN
Solar/Wind Harmer
3.146
316458AB2-190 GEN2
Solar/Wind Harmer
1.382
971069AG2-661 GEN
Solar/Wind Harmer
2.041
971647AH1-324 GEN
Solar/Wind Harmer
5.851
961611AG1-000B GEN
Solar/Wind Harmer
5.442
3141766HARMONY
Solar/Wind Harmer
-0.002
316159AE1-175 C
Solar/Wind Harmer
0.274
3151171GRAVELC
Adder
0.964
971777AH1-397 GEN
Solar/Wind Harmer
1.177
3141843SHACKLE
Adder
0.455
3138133OCRAN
Solar/Wind Harmer
-0.006
961951AG1-038 GEN
Solar/Wind Harmer
1.229
971317AH1-138 GEN
Solar/Wind Harmer
1.162
962861AG1-135 GEN
Solar/Wind Harmer
3.45
964211AG1-282 GEN
Solar/Wind Harmer
0.276
3141726DUNNSVL
Solar/Wind Harmer
-0.037
3142433PROV 92
Solar/Wind Harmer
-0.036
3142433PROV 92
Adder
0.159
3142433PROV 92
Adder
0.159
3138126ROCKLANDING
Solar/Wind Harmer
0.028
3145336SMITFLD
Solar/Wind Harmer
-0.036
3150351NORNECKC2
Adder
0.784
316337AD2-073 GEN
Solar/Wind Harmer
0.218
316072AD1-144
Solar/Wind Harmer
0.155
970659AG2-427 GEN
Solar/Wind Harmer
3.995
316381AD1-082 GEN
Solar/Wind Harmer
0.687
970661AG2-428 GEN
Solar/Wind Harmer
7.847
316375AC2-012 GEN
Solar/Wind Harmer
2.542
3150981CHESPKA
Adder
0.816
316246AF1-032 C
Solar/Wind Harmer
0.141
316388AE2-253 GEN
Solar/Wind Harmer
0.471
944591AF1-124 GEN
Solar/Wind Harmer
31.694
3146456SLIGO L269
Solar/Wind Harmer
-0.007
316093AE2-104_GEN
Solar/Wind Harmer
2.011
316294AC1-161 GEN
Solar/Wind Harmer
2.17
3146516WINFALL
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.007
315671AE2-027_GEN
Solar/Wind Harmer
4.842
315800Z1-036_GEN1
Solar/Wind Harmer
1.575
3143526WINTERP
Solar/Wind Helper
1.651
3143226MDLTHAN
Solar/Wind Helper
0.123
3150621CHESTS7
50/50
0.74
3150781HOPHCF2
50/50
0.543
3150791HOPHCF3
50/50
0.543
3150761HOPPOLC
50/50
0.344
971213AH1-066 GEN
50/50
0.476
3142946ENON
Solar/Wind Harmer
-0.002
316033AB2-134 GEN
Solar/Wind Harmer
3.988
315697AD1-025 GEN
Solar/Wind Harmer
2.501
316441AF1-014 GEN
Solar/Wind Harmer
0.675
316487AF1-042 GEN
Solar/Wind Harmer
1.229
958261AF2-120 GEN
Solar/Wind Harmer
3.547
316236AE1-162_GEN
Solar/Wind Harmer
0.274
316077AC2-138 C
Solar/Wind Harmer
0.186
3150341NORNECKC1
Adder
0.823
3150341NORNECKC1
Adder
0.817
316075AC2-137 C
Solar/Wind Harmer
0.238
970657AG2-426 GEN
Solar/Wind Harmer
2.328
970657AG2-426 GEN
Solar/Wind Harmer
0.487
316036AC1-147 C
Solar/Wind Harmer
0.198
3150991CHESPKB
Adder
0.685
3150991CHESPKB
Adder
0.668
316316AC1-027 C
Solar/Wind Harmer
0.221
3142956BIRDNECK
Solar/Wind Harmer
0.386
316185AD1-033 GEN
Solar/Wind Harmer
0.747
3145506HICKORY
Solar/Wind Harmer
-0.028
3145506HICKORY
Solar/Wind Harmer
-0.017
3145506HICKORY
Solar/Wind Harmer
-0.004
316339AD2-160 GEN
Solar/Wind Harmer
0.471
316018AA1-139 ULT2
Solar/Wind Harmer
0.597
316017AA1-139 ULT1
Solar/Wind Harmer
0.564
3137176SLIGO L2192
Solar/Wind Harmer
-0.027
3146456SLIGO L269
Solar/Wind Harmer
0.819
3130086AYDLETT
Solar/Wind Harmer
-0.028
3146386ELIZ CT
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.205
316433W1029_GEN2
Solar/Wind Harmer
1.205
3146516WINFALL
Solar/Wind Harmer
-0.007
3150801HOPHCF4
50/50
0.79
971211AH1-065 GEN
50/50
0.952
3142946ENON
Solar/Wind Harmer
-0.008
970133AG2-095 GEN
Solar/Wind Harmer
1.693
970129AG2-093 GEN
Solar/Wind Harmer
7.767
315778AD1-151 GEN
Solar/Wind Harmer
11.174
961611AG1-000B GEN
Solar/Wind Harmer
2.322
3141766HARMONY
Solar/Wind Harmer
0.929
316382AG1-145 C
Solar/Wind Harmer
0.308
3151221GRAVEL6
Adder
6.589
3151171GRAVELC
Adder
1.268
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.006
3146626S HERTFORD
Solar/Wind Harmer
-0.006
3143526WINTERP
Solar/Wind Helper
1.651
3141843SHACKLE
Adder
0.455
316203AE2-005 GEN
Solar/Wind Harmer
4.221
316280AD1-041 GEN
Solar/Wind Harmer
0.752
316156AD2-030 GEN
Solar/Wind Harmer
0.265
3141873WAN 176
Solar/Wind Harmer
1.178
962971AG1-146 GEN
Solar/Wind Harmer
1.77
316484AD2-074 GEN
Solar/Wind Harmer
2.349
970009AG2-005 GEN
Solar/Wind Harmer
1.166
3144216WINCHST
Adder
0.308
3142433PROV 92
Adder
0.159
3142433PROV 92
Adder
0.159
316404AE1-155 C
Solar/Wind Harmer
1.766
3145336SMITFLD
Solar/Wind Harmer
-0.004
3150921YORKTN3
Adder
2.021
3150351NORNECKC2
Adder
0.797
3144536CHRHLND
Solar/Wind Harmer
-0.001
315813AE1-149 C
Solar/Wind Harmer
4.817
970659AG2-427 GEN
Solar/Wind Harmer
0.708
316083AB2-161 GEN
Solar/Wind Harmer
1.215
970661AG2-428 GEN
Solar/Wind Harmer
1.391
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
6.029
3141906WESTMOR
Solar/Wind Harmer
-0.003
944581AF1-123 GEN
Solar/Wind Harmer
31.58
944601AF1-125 GEN
Solar/Wind Harmer
31.087
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.846
316320Y1-086
Solar/Wind Harmer
0.398
315773AC2-141 GEN
Solar/Wind Harmer
2.807
316435W1029_GEN3
Solar/Wind Harmer
1.205
3146516WINFALL
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.006
970737AG2-469 GEN
Solar/Wind Harmer
3.247
965281AG1-393 GEN
Solar/Wind Harmer
0.807
3145273HOLLAND
Solar/Wind Harmer
-0.005
3150611CHESTG7
50/50
1.61
3150631CHESTG8
50/50
1.584
971047AG2-646 GEN
50/50
45.085
316132AB2-190 GEN1
Solar/Wind Harmer
1.382
315976AC1-164 GENA
Solar/Wind Harmer
13.508
316169AC1-164_GENC
Solar/Wind Harmer
11.67
315975AC1-164 GENB
Solar/Wind Harmer
0.4
316369SG1_INVT
Solar/Wind Harmer
2.21
316314AB2-024 C
Solar/Wind Harmer
0.919
316059AD1-063 C
Solar/Wind Harmer
0.236
972265AH1-717 GEN
Adder
7.037
3151201GRAVEL4
Adder
6.597
3151191GRAVEL3
Adder
6.513
3151211GRAVEL5
Adder
6.513
3143873LANEXA
Solar/Wind Harmer
-0.006
315662AE1-191 GEN
Solar/Wind Harmer
1.202
315666AE1-190 GEN
Solar/Wind Harmer
0.301
957601AF2-054 GEN
Solar/Wind Harmer
0.297
3141873WAN 176
Solar/Wind Harmer
-0.002
3141913WHIT STONE
Solar/Wind Harmer
-0.01
3138133OCRAN
Solar/Wind Harmer
-0.003
3141783LANCAST
Solar/Wind Harmer
-0.006
3141783LANCAST
Solar/Wind Harmer
-0.004
957831AF2-077 GEN
Solar/Wind Harmer
0.284
3138283WHITEMARSH
Solar/Wind Harmer
0.015
962981AG1-147 GEN
Solar/Wind Harmer
4.13
971445AH1-216 GEN
Solar/Wind Harmer
5.689
3142433PROV 92
Adder
0.159
3142433PROV 92
Adder
0.159
971167AH1-042 GEN
Solar/Wind Harmer
8.59
3141813NORNECK
Solar/Wind Harmer
-0.009
3152611GOSPORTB
Adder
0.832
3152621GOSPORTC
Adder
0.706
3152601GOSPORTA
Adder
0.652
3151081ELIZAR1
Adder
5.952
3151091ELIZAR2
Adder
5.849
316223AC1-118
Solar/Wind Harmer
0.196
315833AF1-017_GEN
Solar/Wind Harmer
1.355
316349AD2-085 GEN
Solar/Wind Harmer
0.635
316311AC2-079 GEN
Solar/Wind Harmer
3.597
316305AF2-043 C
Solar/Wind Harmer
0.21
957871AF2-081 GEN
Solar/Wind Harmer
3.483
319010AE1-072 C
Solar/Wind Harmer
1.401
315835AF2-110_GEN
Solar/Wind Harmer
0.865
3146406KITTY HAWK
Solar/Wind Harmer
0.006
313526AB2-022
Solar/Wind Harmer
0.183
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
316321Z2-027
Solar/Wind Harmer
0.181
3146396TANGLEW
Solar/Wind Harmer
0.124
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
315611Z1-036_GEN2
Solar/Wind Harmer
1.575
316233AE1-074 FULL
Solar/Wind Helper
0.485
CPLELTFEXP_CPLE->PJM
CLTF
1.641
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.38
NYPJM->LTFIMP_NY
CLTF
0.314
LGEELTFEXP_LGEE->PJM
CLTF
0.055
WECLTFEXP_WEC->PJM
CLTF
0.025
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.639
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.215
MECLTFEXP_MEC->PJM
CLTF
0.213
SIGELTFEXP_SIGE->PJM
CLTF
0.006
LAGNLTFEXP_LAGN->PJM
CLTF
0.763
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.251
TVALTFEXP_TVA->PJM
CLTF
0.377

Details for 6COMORN-6BIRCHWD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6COMORN-6BIRCHWD 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:124.42 %
Rating:548.02 MVA
Rating Type:B
MVA to Mitigate:681.85
MW Contribution:11.22
Bus #Bus NameTypeMW Contribution
3141316ARNOLDS
50/50
2.018
3150351NORNECKC2
50/50
3.006
970575AG2-366 GEN
50/50
3.66
315749AE2-041 GEN
50/50
4.946
3141843SHACKLE
50/50
0.746
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3150921YORKTN3
50/50
1.929
3144216WINCHST
50/50
0.279
3151161SURRY 1
50/50
2.166
970737AG2-469 GEN
Solar/Wind Harmer
20.178
3141906WESTMOR
Solar/Wind Harmer
0.165
316404AE1-155 C
Solar/Wind Harmer
0.054
970009AG2-005 GEN
Solar/Wind Harmer
1.637
962971AG1-146 GEN
Solar/Wind Harmer
3.294
316156AD2-030 GEN
Solar/Wind Harmer
0.109
3141873WAN 176
Solar/Wind Harmer
2.61
316280AD1-041 GEN
Solar/Wind Harmer
0.003
3141766HARMONY
Solar/Wind Harmer
1.855
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316382AG1-145 C
Solar/Wind Harmer
0.001
3142946ENON
Solar/Wind Harmer
0.023
970293AG2-193 GEN
Solar/Wind Harmer
0.668
3142416OLDCHRC
Solar/Wind Harmer
0.555
3151221GRAVEL6
Adder
4.099
3151171GRAVELC
Adder
0.789
957191AF2-013 GEN
50/50
65.713
3150341NORNECKC1
50/50
3.105
3150341NORNECKC1
50/50
3.08
963611AG1-210 GEN
50/50
0.994
3150621CHESTS7
50/50
0.184
316077AC2-138 C
Solar/Wind Harmer
0.001
958261AF2-120 GEN
Solar/Wind Harmer
7.962
316075AC2-137 C
Solar/Wind Harmer
0.019
3142946ENON
Solar/Wind Harmer
0.007
3150351NORNECKC2
50/50
2.956
966661AG1-536 GEN
50/50
6.849
3141843SHACKLE
50/50
0.746
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
971353AH1-157 GEN
50/50
7.408
970017AG2-010 GEN
50/50
4.699
3150641CHESTS8
50/50
0.203
944631AF1-128 GEN
50/50
31.925
972135AH1-637 GEN
Solar/Wind Harmer
4.389
316337AD2-073 GEN
Solar/Wind Harmer
0.299
3141726DUNNSVL
Solar/Wind Harmer
1.044
962861AG1-135 GEN
Solar/Wind Harmer
7.523
3138133OCRAN
Solar/Wind Harmer
0.103
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.363
3142433PROV 92
Solar/Wind Harmer
0.428
971317AH1-138 GEN
Solar/Wind Harmer
0.613
316159AE1-175 C
Solar/Wind Harmer
0.065
3138126ROCKLANDING
Solar/Wind Harmer
0.032
3142416OLDCHRC
Solar/Wind Harmer
0.149
3142416OLDCHRC
Solar/Wind Harmer
0.057
3151171GRAVELC
Adder
0.6
315759AF1-018 GEN
50/50
4.946
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3150611CHESTG7
50/50
0.401
3150631CHESTG8
50/50
0.394
971047AG2-646 GEN
50/50
11.221
972263AH1-716 GEN
50/50
32.871
944491AF1-114 GEN
Solar/Wind Harmer
0.002
316223AC1-118
Solar/Wind Harmer
0.296
3141813NORNECK
Solar/Wind Harmer
0.279
970327AG2-215 GEN
Solar/Wind Harmer
7.194
962981AG1-147 GEN
Solar/Wind Harmer
7.685
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.073
3138133OCRAN
Solar/Wind Harmer
0.051
3141913WHIT STONE
Solar/Wind Harmer
0.166
3141873WAN 176
Solar/Wind Harmer
0.029
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
4.081
316314AB2-024 C
Solar/Wind Harmer
0
3143873LANEXA
Solar/Wind Harmer
0.075
3138283WHITEMARSH
Solar/Wind Harmer
0.025
971167AH1-042 GEN
Solar/Wind Harmer
9.122
315976AC1-164 GENA
Solar/Wind Harmer
8.292
316169AC1-164_GENC
Solar/Wind Harmer
7.163
315975AC1-164 GENB
Solar/Wind Harmer
0.245
316312AB1-027
Solar/Wind Harmer
0.102
972265AH1-717 GEN
Adder
4.377
3151201GRAVEL4
Adder
4.104
3151191GRAVEL3
Adder
4.052
3151211GRAVEL5
Adder
4.052
3141426STAFORD
Solar/Wind Helper
0.031
CPLELTFEXP_CPLE->PJM
CLTF
1.997
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.895
NYPJM->LTFIMP_NY
CLTF
0.564
LGEELTFEXP_LGEE->PJM
CLTF
0.274
WECLTFEXP_WEC->PJM
CLTF
0.137
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.711
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.577
MECLTFEXP_MEC->PJM
CLTF
0.732
SIGELTFEXP_SIGE->PJM
CLTF
0.022
LAGNLTFEXP_LAGN->PJM
CLTF
1.483
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.388
TVALTFEXP_TVA->PJM
CLTF
0.749

Details for 6COMORN-6BIRCHWD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6COMORN-6BIRCHWD 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 557_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.98 %
Rating:548.02 MVA
Rating Type:B
MVA to Mitigate:575.3
MW Contribution:10.6
Bus #Bus NameTypeMW Contribution
3150351NORNECKC2
50/50
2.97
966661AG1-536 GEN
50/50
6.884
3141843SHACKLE
50/50
0.749
3142433PROV 92
50/50
0.218
3142433PROV 92
50/50
0.218
971353AH1-157 GEN
50/50
7.642
970017AG2-010 GEN
50/50
4.875
3150641CHESTS8
50/50
0.192
944631AF1-128 GEN
50/50
30.156
3152331SURRY 2
50/50
2.455
972135AH1-637 GEN
Solar/Wind Harmer
4.407
316337AD2-073 GEN
Solar/Wind Harmer
0.3
3141726DUNNSVL
Solar/Wind Harmer
1.049
962861AG1-135 GEN
Solar/Wind Harmer
7.561
3138133OCRAN
Solar/Wind Harmer
0.104
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.365
3142433PROV 92
Solar/Wind Harmer
0.422
971317AH1-138 GEN
Solar/Wind Harmer
0.633
316159AE1-175 C
Solar/Wind Harmer
0.067
3138126ROCKLANDING
Solar/Wind Harmer
0.034
3151171GRAVELC
Adder
0.607
3141316ARNOLDS
50/50
2.026
3150351NORNECKC2
50/50
3.02
970575AG2-366 GEN
50/50
3.68
315749AE2-041 GEN
50/50
4.976
3141843SHACKLE
50/50
0.749
3142433PROV 92
50/50
0.218
3142433PROV 92
50/50
0.218
3150921YORKTN3
50/50
2.003
3144216WINCHST
50/50
0.289
3151161SURRY 1
50/50
2.191
970737AG2-469 GEN
Solar/Wind Harmer
20.26
3141906WESTMOR
Solar/Wind Harmer
0.165
316404AE1-155 C
Solar/Wind Harmer
0.054
970009AG2-005 GEN
Solar/Wind Harmer
1.646
962971AG1-146 GEN
Solar/Wind Harmer
3.312
316156AD2-030 GEN
Solar/Wind Harmer
0.109
3141873WAN 176
Solar/Wind Harmer
2.629
316280AD1-041 GEN
Solar/Wind Harmer
0.003
3141766HARMONY
Solar/Wind Harmer
1.866
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316382AG1-145 C
Solar/Wind Harmer
0.001
3142946ENON
Solar/Wind Harmer
0.022
3151221GRAVEL6
Adder
4.147
3151171GRAVELC
Adder
0.798
970293AG2-193 GEN
Solar/Wind Harmer
0.603
315759AF1-018 GEN
50/50
4.976
3142433PROV 92
50/50
0.218
3142433PROV 92
50/50
0.218
972263AH1-716 GEN
50/50
35.649
3150611CHESTG7
50/50
0.379
3150631CHESTG8
50/50
0.372
971047AG2-646 GEN
50/50
10.599
944491AF1-114 GEN
Solar/Wind Harmer
0.002
316223AC1-118
Solar/Wind Harmer
0.297
3141813NORNECK
Solar/Wind Harmer
0.28
970327AG2-215 GEN
Solar/Wind Harmer
7.232
962981AG1-147 GEN
Solar/Wind Harmer
7.729
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.074
3138133OCRAN
Solar/Wind Harmer
0.052
3141913WHIT STONE
Solar/Wind Harmer
0.168
3141873WAN 176
Solar/Wind Harmer
0.03
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
4.097
316314AB2-024 C
Solar/Wind Harmer
0
3143873LANEXA
Solar/Wind Harmer
0.075
3138283WHITEMARSH
Solar/Wind Harmer
0.025
971167AH1-042 GEN
Solar/Wind Harmer
8.942
315976AC1-164 GENA
Solar/Wind Harmer
8.275
316169AC1-164_GENC
Solar/Wind Harmer
7.149
315975AC1-164 GENB
Solar/Wind Harmer
0.245
972265AH1-717 GEN
Adder
4.429
3151201GRAVEL4
Adder
4.152
3151191GRAVEL3
Adder
4.099
3151211GRAVEL5
Adder
4.099
3141426STAFORD
Solar/Wind Helper
0.029
957191AF2-013 GEN
50/50
65.968
3150341NORNECKC1
50/50
3.119
3150341NORNECKC1
50/50
3.094
963611AG1-210 GEN
50/50
0.998
3150621CHESTS7
50/50
0.174
316077AC2-138 C
Solar/Wind Harmer
0.001
958261AF2-120 GEN
Solar/Wind Harmer
8.003
316075AC2-137 C
Solar/Wind Harmer
0.018
3142946ENON
Solar/Wind Harmer
0.007
CPLELTFEXP_CPLE->PJM
CLTF
1.912
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.152
NYPJM->LTFIMP_NY
CLTF
0.465
LGEELTFEXP_LGEE->PJM
CLTF
0.185
WECLTFEXP_WEC->PJM
CLTF
0.092
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.061
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.057
MECLTFEXP_MEC->PJM
CLTF
0.525
SIGELTFEXP_SIGE->PJM
CLTF
0.016
LAGNLTFEXP_LAGN->PJM
CLTF
1.213
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.047
TVALTFEXP_TVA->PJM
CLTF
0.609

Details for 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6FINES-6FREDBRG 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:138.73 %
Rating:548.02 MVA
Rating Type:B
MVA to Mitigate:760.24
MW Contribution:11.22
Bus #Bus NameTypeMW Contribution
3150331BIRCHWDA
50/50
158.356
3141316ARNOLDS
50/50
2.018
3150351NORNECKC2
50/50
3.006
970575AG2-366 GEN
50/50
3.66
315749AE2-041 GEN
50/50
4.946
3141843SHACKLE
50/50
0.746
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3150921YORKTN3
50/50
1.929
3144216WINCHST
50/50
0.279
3151161SURRY 1
50/50
2.166
970737AG2-469 GEN
Solar/Wind Harmer
20.178
3141906WESTMOR
Solar/Wind Harmer
0.165
316404AE1-155 C
Solar/Wind Harmer
0.054
970009AG2-005 GEN
Solar/Wind Harmer
1.637
962971AG1-146 GEN
Solar/Wind Harmer
3.294
316156AD2-030 GEN
Solar/Wind Harmer
0.109
3141873WAN 176
Solar/Wind Harmer
2.61
316280AD1-041 GEN
Solar/Wind Harmer
0.003
3141766HARMONY
Solar/Wind Harmer
1.855
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316382AG1-145 C
Solar/Wind Harmer
0.001
3142946ENON
Solar/Wind Harmer
0.023
970293AG2-193 GEN
Solar/Wind Harmer
0.668
3142416OLDCHRC
Solar/Wind Harmer
0.555
3151221GRAVEL6
Adder
4.099
3151171GRAVELC
Adder
0.789
957191AF2-013 GEN
50/50
65.713
3150341NORNECKC1
50/50
3.105
3150341NORNECKC1
50/50
3.08
963611AG1-210 GEN
50/50
0.994
3150621CHESTS7
50/50
0.184
316077AC2-138 C
Solar/Wind Harmer
0.001
958261AF2-120 GEN
Solar/Wind Harmer
7.962
316075AC2-137 C
Solar/Wind Harmer
0.019
3142946ENON
Solar/Wind Harmer
0.007
3150351NORNECKC2
50/50
2.956
966661AG1-536 GEN
50/50
6.849
3141843SHACKLE
50/50
0.746
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
971353AH1-157 GEN
50/50
7.408
970017AG2-010 GEN
50/50
4.699
3150641CHESTS8
50/50
0.203
944631AF1-128 GEN
50/50
31.925
972135AH1-637 GEN
Solar/Wind Harmer
4.389
316337AD2-073 GEN
Solar/Wind Harmer
0.299
3141726DUNNSVL
Solar/Wind Harmer
1.044
962861AG1-135 GEN
Solar/Wind Harmer
7.523
3138133OCRAN
Solar/Wind Harmer
0.103
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.363
3142433PROV 92
Solar/Wind Harmer
0.428
971317AH1-138 GEN
Solar/Wind Harmer
0.613
316159AE1-175 C
Solar/Wind Harmer
0.065
3138126ROCKLANDING
Solar/Wind Harmer
0.032
3142416OLDCHRC
Solar/Wind Harmer
0.149
3142416OLDCHRC
Solar/Wind Harmer
0.057
3151171GRAVELC
Adder
0.6
315759AF1-018 GEN
50/50
4.946
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3150611CHESTG7
50/50
0.401
3150631CHESTG8
50/50
0.394
971047AG2-646 GEN
50/50
11.221
972263AH1-716 GEN
50/50
32.871
944491AF1-114 GEN
Solar/Wind Harmer
0.002
316223AC1-118
Solar/Wind Harmer
0.296
3141813NORNECK
Solar/Wind Harmer
0.279
970327AG2-215 GEN
Solar/Wind Harmer
7.194
962981AG1-147 GEN
Solar/Wind Harmer
7.685
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.073
3138133OCRAN
Solar/Wind Harmer
0.051
3141913WHIT STONE
Solar/Wind Harmer
0.166
3141873WAN 176
Solar/Wind Harmer
0.029
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
4.081
316314AB2-024 C
Solar/Wind Harmer
0
3143873LANEXA
Solar/Wind Harmer
0.075
3138283WHITEMARSH
Solar/Wind Harmer
0.025
971167AH1-042 GEN
Solar/Wind Harmer
9.122
315976AC1-164 GENA
Solar/Wind Harmer
8.292
316169AC1-164_GENC
Solar/Wind Harmer
7.163
315975AC1-164 GENB
Solar/Wind Harmer
0.245
316312AB1-027
Solar/Wind Harmer
0.102
972265AH1-717 GEN
Adder
4.377
3151201GRAVEL4
Adder
4.104
3151191GRAVEL3
Adder
4.052
3151211GRAVEL5
Adder
4.052
3141426STAFORD
Solar/Wind Helper
0.031
CPLELTFEXP_CPLE->PJM
CLTF
1.997
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.895
NYPJM->LTFIMP_NY
CLTF
0.564
LGEELTFEXP_LGEE->PJM
CLTF
0.274
WECLTFEXP_WEC->PJM
CLTF
0.137
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.711
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.577
MECLTFEXP_MEC->PJM
CLTF
0.732
SIGELTFEXP_SIGE->PJM
CLTF
0.022
LAGNLTFEXP_LAGN->PJM
CLTF
1.483
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.388
TVALTFEXP_TVA->PJM
CLTF
0.749

Details for 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6FINES-6FREDBRG 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 557_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.84 %
Rating:548.02 MVA
Rating Type:B
MVA to Mitigate:656.73
MW Contribution:10.6
Bus #Bus NameTypeMW Contribution
3150331BIRCHWDA
50/50
158.961
3141316ARNOLDS
50/50
2.026
3150351NORNECKC2
50/50
3.02
970575AG2-366 GEN
50/50
3.68
315749AE2-041 GEN
50/50
4.976
3141843SHACKLE
50/50
0.749
3142433PROV 92
50/50
0.218
3142433PROV 92
50/50
0.218
3150921YORKTN3
50/50
2.003
3144216WINCHST
50/50
0.289
3151161SURRY 1
50/50
2.191
970737AG2-469 GEN
Solar/Wind Harmer
20.26
3141906WESTMOR
Solar/Wind Harmer
0.165
316404AE1-155 C
Solar/Wind Harmer
0.054
970009AG2-005 GEN
Solar/Wind Harmer
1.646
962971AG1-146 GEN
Solar/Wind Harmer
3.312
316156AD2-030 GEN
Solar/Wind Harmer
0.109
3141873WAN 176
Solar/Wind Harmer
2.629
316280AD1-041 GEN
Solar/Wind Harmer
0.003
3141766HARMONY
Solar/Wind Harmer
1.866
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316382AG1-145 C
Solar/Wind Harmer
0.001
3142946ENON
Solar/Wind Harmer
0.022
3151221GRAVEL6
Adder
4.147
3151171GRAVELC
Adder
0.798
970293AG2-193 GEN
Solar/Wind Harmer
0.603
957191AF2-013 GEN
50/50
65.968
3150341NORNECKC1
50/50
3.119
3150341NORNECKC1
50/50
3.094
963611AG1-210 GEN
50/50
0.998
3150621CHESTS7
50/50
0.174
316077AC2-138 C
Solar/Wind Harmer
0.001
958261AF2-120 GEN
Solar/Wind Harmer
8.003
316075AC2-137 C
Solar/Wind Harmer
0.018
3142946ENON
Solar/Wind Harmer
0.007
3150351NORNECKC2
50/50
2.97
966661AG1-536 GEN
50/50
6.884
3141843SHACKLE
50/50
0.749
3142433PROV 92
50/50
0.218
3142433PROV 92
50/50
0.218
971353AH1-157 GEN
50/50
7.642
970017AG2-010 GEN
50/50
4.875
3150641CHESTS8
50/50
0.192
944631AF1-128 GEN
50/50
30.156
3152331SURRY 2
50/50
2.455
972135AH1-637 GEN
Solar/Wind Harmer
4.407
316337AD2-073 GEN
Solar/Wind Harmer
0.3
3141726DUNNSVL
Solar/Wind Harmer
1.049
962861AG1-135 GEN
Solar/Wind Harmer
7.561
3138133OCRAN
Solar/Wind Harmer
0.104
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.365
3142433PROV 92
Solar/Wind Harmer
0.422
971317AH1-138 GEN
Solar/Wind Harmer
0.633
316159AE1-175 C
Solar/Wind Harmer
0.067
3138126ROCKLANDING
Solar/Wind Harmer
0.034
3151171GRAVELC
Adder
0.607
315759AF1-018 GEN
50/50
4.976
3142433PROV 92
50/50
0.218
3142433PROV 92
50/50
0.218
972263AH1-716 GEN
50/50
35.649
3150611CHESTG7
50/50
0.379
3150631CHESTG8
50/50
0.372
971047AG2-646 GEN
50/50
10.599
944491AF1-114 GEN
Solar/Wind Harmer
0.002
316223AC1-118
Solar/Wind Harmer
0.297
3141813NORNECK
Solar/Wind Harmer
0.28
970327AG2-215 GEN
Solar/Wind Harmer
7.232
962981AG1-147 GEN
Solar/Wind Harmer
7.729
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.074
3138133OCRAN
Solar/Wind Harmer
0.052
3141913WHIT STONE
Solar/Wind Harmer
0.168
3141873WAN 176
Solar/Wind Harmer
0.03
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
4.097
316314AB2-024 C
Solar/Wind Harmer
0
3143873LANEXA
Solar/Wind Harmer
0.075
3138283WHITEMARSH
Solar/Wind Harmer
0.025
971167AH1-042 GEN
Solar/Wind Harmer
8.942
315976AC1-164 GENA
Solar/Wind Harmer
8.275
316169AC1-164_GENC
Solar/Wind Harmer
7.149
315975AC1-164 GENB
Solar/Wind Harmer
0.245
972265AH1-717 GEN
Adder
4.429
3151201GRAVEL4
Adder
4.152
3151191GRAVEL3
Adder
4.099
3151211GRAVEL5
Adder
4.099
3141426STAFORD
Solar/Wind Helper
0.029
CPLELTFEXP_CPLE->PJM
CLTF
1.912
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.152
NYPJM->LTFIMP_NY
CLTF
0.465
LGEELTFEXP_LGEE->PJM
CLTF
0.185
WECLTFEXP_WEC->PJM
CLTF
0.092
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.061
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.057
MECLTFEXP_MEC->PJM
CLTF
0.525
SIGELTFEXP_SIGE->PJM
CLTF
0.016
LAGNLTFEXP_LAGN->PJM
CLTF
1.213
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.047
TVALTFEXP_TVA->PJM
CLTF
0.609

Details for 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6IRON208-6SOUWEST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 557_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.96 %
Rating:663.64 MVA
Rating Type:B
MVA to Mitigate:689.92
MW Contribution:45.73
Bus #Bus NameTypeMW Contribution
3143096IRON208
50/50
2.365
3150641CHESTS8
50/50
0.828
944631AF1-128 GEN
50/50
130.091
3150771HOPHCF1
50/50
0.557
3152331SURRY 2
50/50
2.862
970129AG2-093 GEN
Solar/Wind Harmer
3.585
316458AB2-190 GEN2
Solar/Wind Harmer
0.67
971069AG2-661 GEN
Solar/Wind Harmer
2.098
971647AH1-324 GEN
Solar/Wind Harmer
4.574
961611AG1-000B GEN
Solar/Wind Harmer
5.304
3141766HARMONY
Solar/Wind Harmer
0.019
316159AE1-175 C
Solar/Wind Harmer
0.081
3151171GRAVELC
Adder
0.995
971777AH1-397 GEN
Solar/Wind Harmer
0.243
3141843SHACKLE
Adder
0.471
3138133OCRAN
Solar/Wind Harmer
0.054
971317AH1-138 GEN
Solar/Wind Harmer
0.639
3142433PROV 92
Solar/Wind Harmer
0.34
3142433PROV 92
Adder
0.165
3142433PROV 92
Adder
0.165
962861AG1-135 GEN
Solar/Wind Harmer
2.709
3141726DUNNSVL
Solar/Wind Harmer
0.337
3138126ROCKLANDING
Solar/Wind Harmer
0.039
3145336SMITFLD
Solar/Wind Harmer
0.335
3150351NORNECKC2
Adder
0.811
316337AD2-073 GEN
Solar/Wind Harmer
0.065
316072AD1-144
Solar/Wind Harmer
0.026
970659AG2-427 GEN
Solar/Wind Harmer
3.376
316381AD1-082 GEN
Solar/Wind Harmer
0.072
970661AG2-428 GEN
Solar/Wind Harmer
6.816
316375AC2-012 GEN
Solar/Wind Harmer
0.002
3150981CHESPKA
Adder
0.848
316246AF1-032 C
Solar/Wind Harmer
0.029
316388AE2-253 GEN
Solar/Wind Harmer
0.202
944591AF1-124 GEN
Solar/Wind Harmer
14.529
3143096IRON208
50/50
2.365
3143096IRON208
50/50
2.318
3150801HOPHCF4
50/50
0.81
3150611CHESTG7
50/50
1.633
3150631CHESTG8
50/50
1.607
971047AG2-646 GEN
50/50
45.726
315759AF1-018 GEN
50/50
3.414
316132AB2-190 GEN1
Solar/Wind Harmer
0.67
315976AC1-164 GENA
Solar/Wind Harmer
12.162
316169AC1-164_GENC
Solar/Wind Harmer
10.507
315975AC1-164 GENB
Solar/Wind Harmer
0.36
316369SG1_INVT
Solar/Wind Harmer
0.004
316314AB2-024 C
Solar/Wind Harmer
0
316059AD1-063 C
Solar/Wind Harmer
0.001
972265AH1-717 GEN
Adder
7.261
3151201GRAVEL4
Adder
6.807
3151191GRAVEL3
Adder
6.721
3151211GRAVEL5
Adder
6.721
3143873LANEXA
Solar/Wind Harmer
0.056
970189AG2-124 GEN
Solar/Wind Harmer
2.733
315662AE1-191 GEN
Solar/Wind Harmer
0.003
315666AE1-190 GEN
Solar/Wind Harmer
0.001
3141873WAN 176
Solar/Wind Harmer
0.018
3141913WHIT STONE
Solar/Wind Harmer
0.09
3138133OCRAN
Solar/Wind Harmer
0.027
3141783LANCAST
Solar/Wind Harmer
0.053
3141783LANCAST
Solar/Wind Harmer
0.035
3138283WHITEMARSH
Solar/Wind Harmer
0.02
962981AG1-147 GEN
Solar/Wind Harmer
3.244
970327AG2-215 GEN
Solar/Wind Harmer
2.818
3142433PROV 92
Adder
0.165
3142433PROV 92
Adder
0.165
971445AH1-216 GEN
Solar/Wind Harmer
5.957
971167AH1-042 GEN
Solar/Wind Harmer
7.355
3141813NORNECK
Solar/Wind Harmer
0.081
3152611GOSPORTB
Adder
0.865
3152621GOSPORTC
Adder
0.734
3152601GOSPORTA
Adder
0.677
3151081ELIZAR1
Adder
6.186
3151091ELIZAR2
Adder
6.079
316223AC1-118
Solar/Wind Harmer
0.048
315833AF1-017_GEN
Solar/Wind Harmer
0
316349AD2-085 GEN
Solar/Wind Harmer
0.045
316311AC2-079 GEN
Solar/Wind Harmer
1.899
316305AF2-043 C
Solar/Wind Harmer
0.001
957871AF2-081 GEN
Solar/Wind Harmer
3.21
319010AE1-072 C
Solar/Wind Harmer
0.323
315835AF2-110_GEN
Solar/Wind Harmer
0.44
3146406KITTY HAWK
Solar/Wind Harmer
0.008
313526AB2-022
Solar/Wind Harmer
0.034
3146486SUNBURY
Solar/Wind Harmer
0.063
3146486SUNBURY
Solar/Wind Harmer
0.063
316321Z2-027
Solar/Wind Harmer
0.012
3146396TANGLEW
Solar/Wind Harmer
0.172
3145176PASQUOTANK
Solar/Wind Harmer
0.039
315611Z1-036_GEN2
Solar/Wind Harmer
0
3130156CHOWAN
Solar/Wind Harmer
0.057
3130156CHOWAN
Solar/Wind Harmer
0.057
316233AE1-074 FULL
Solar/Wind Helper
0.475
971211AH1-065 GEN
50/50
0.977
315749AE2-041 GEN
50/50
3.414
3151161SURRY 1
50/50
3.592
3142946ENON
Solar/Wind Harmer
0.072
970133AG2-095 GEN
Solar/Wind Harmer
1.318
970129AG2-093 GEN
Solar/Wind Harmer
7.619
315778AD1-151 GEN
Solar/Wind Harmer
9.439
961611AG1-000B GEN
Solar/Wind Harmer
2.697
3141766HARMONY
Solar/Wind Harmer
1.28
316382AG1-145 C
Solar/Wind Harmer
0.001
3151221GRAVEL6
Adder
6.799
3151171GRAVELC
Adder
1.308
3141843SHACKLE
Adder
0.471
316203AE2-005 GEN
Solar/Wind Harmer
0
316280AD1-041 GEN
Solar/Wind Harmer
0.002
316156AD2-030 GEN
Solar/Wind Harmer
0.068
3141873WAN 176
Solar/Wind Harmer
1.624
962971AG1-146 GEN
Solar/Wind Harmer
1.39
970009AG2-005 GEN
Solar/Wind Harmer
0.641
3142433PROV 92
Adder
0.165
3142433PROV 92
Adder
0.165
3144216WINCHST
Adder
0.319
316404AE1-155 C
Solar/Wind Harmer
0.019
3145336SMITFLD
Solar/Wind Harmer
0.033
3150921YORKTN3
Adder
2.093
3150351NORNECKC2
Adder
0.824
3144536CHRHLND
Solar/Wind Harmer
0.011
315813AE1-149 C
Solar/Wind Harmer
3.817
970659AG2-427 GEN
Solar/Wind Harmer
0.738
316083AB2-161 GEN
Solar/Wind Harmer
0.001
970661AG2-428 GEN
Solar/Wind Harmer
1.45
3144873MCLAUGH
Solar/Wind Harmer
0.002
3151101ELIZAR3
Adder
6.266
3141906WESTMOR
Solar/Wind Harmer
0.027
944581AF1-123 GEN
Solar/Wind Harmer
14.477
944601AF1-125 GEN
Solar/Wind Harmer
14.254
3146456SLIGO L269
Solar/Wind Harmer
0.064
971153AH1-033 GEN
Solar/Wind Harmer
0.742
316320Y1-086
Solar/Wind Harmer
0
315773AC2-141 GEN
Solar/Wind Harmer
2.272
316435W1029_GEN3
Solar/Wind Harmer
0
3146516WINFALL
Solar/Wind Harmer
0.061
965281AG1-393 GEN
Solar/Wind Harmer
0.649
3146626S HERTFORD
Solar/Wind Harmer
0.06
970737AG2-469 GEN
Solar/Wind Harmer
2.555
3145273HOLLAND
Solar/Wind Harmer
0.045
3146376EDENTON
Solar/Wind Harmer
0.057
3146456SLIGO L269
Solar/Wind Harmer
0.064
316093AE2-104_GEN
Solar/Wind Harmer
1.078
316294AC1-161 GEN
Solar/Wind Harmer
1.078
3146516WINFALL
Solar/Wind Harmer
0.198
3146516WINFALL
Solar/Wind Harmer
0.061
315671AE2-027_GEN
Solar/Wind Harmer
3.892
315800Z1-036_GEN1
Solar/Wind Harmer
0
3130156CHOWAN
Solar/Wind Harmer
0.057
3143526WINTERP
Solar/Wind Helper
1.618
3143226MDLTHAN
Solar/Wind Helper
0.118
3150621CHESTS7
50/50
0.75
3150781HOPHCF2
50/50
0.557
3150791HOPHCF3
50/50
0.557
3150761HOPPOLC
50/50
0.353
971213AH1-066 GEN
50/50
0.488
3142946ENON
Solar/Wind Harmer
0.022
316033AB2-134 GEN
Solar/Wind Harmer
0.007
315697AD1-025 GEN
Solar/Wind Harmer
0.127
958261AF2-120 GEN
Solar/Wind Harmer
2.785
316236AE1-162_GEN
Solar/Wind Harmer
0.001
316075AC2-137 C
Solar/Wind Harmer
0.023
316077AC2-138 C
Solar/Wind Harmer
0
3150341NORNECKC1
Adder
0.851
3150341NORNECKC1
Adder
0.845
970657AG2-426 GEN
Solar/Wind Harmer
2.421
970657AG2-426 GEN
Solar/Wind Harmer
0.507
316036AC1-147 C
Solar/Wind Harmer
0.013
3150991CHESPKB
Adder
0.712
3150991CHESPKB
Adder
0.694
316316AC1-027 C
Solar/Wind Harmer
0.064
3142956BIRDNECK
Solar/Wind Harmer
0
316185AD1-033 GEN
Solar/Wind Harmer
0.002
3145506HICKORY
Solar/Wind Harmer
0.26
3145506HICKORY
Solar/Wind Harmer
0.156
3145506HICKORY
Solar/Wind Harmer
0.039
316339AD2-160 GEN
Solar/Wind Harmer
0.105
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
316017AA1-139 ULT1
Solar/Wind Harmer
0.036
3137176SLIGO L2192
Solar/Wind Harmer
0.256
3146456SLIGO L269
Solar/Wind Harmer
1.137
3130086AYDLETT
Solar/Wind Harmer
0.256
3146386ELIZ CT
Solar/Wind Harmer
0.063
316431W1029_GEN1
Solar/Wind Harmer
0
316433W1029_GEN2
Solar/Wind Harmer
0
3146516WINFALL
Solar/Wind Harmer
0.061
3146516WINFALL
Solar/Wind Harmer
0.061
3146516WINFALL
Solar/Wind Harmer
0.061
3146626S HERTFORD
Solar/Wind Harmer
0.06
3146626S HERTFORD
Solar/Wind Harmer
0.06
315742AE1-103 GEN
Solar/Wind Harmer
0.001
3146376EDENTON
Solar/Wind Harmer
0.255
3146376EDENTON
Solar/Wind Harmer
0.255
3143526WINTERP
Solar/Wind Helper
1.618
CPLELTFEXP_CPLE->PJM
CLTF
1.734
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.554
NYPJM->LTFIMP_NY
CLTF
0.33
LGEELTFEXP_LGEE->PJM
CLTF
0.057
WECLTFEXP_WEC->PJM
CLTF
0.026
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.657
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.279
MECLTFEXP_MEC->PJM
CLTF
0.223
SIGELTFEXP_SIGE->PJM
CLTF
0.006
LAGNLTFEXP_LAGN->PJM
CLTF
0.804
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.434
TVALTFEXP_TVA->PJM
CLTF
0.397

Details for 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6IRON208-6SOUWEST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.72 %
Rating:663.64 MVA
Rating Type:B
MVA to Mitigate:668.44
MW Contribution:42.99
Bus #Bus NameTypeMW Contribution
3150611CHESTG7
50/50
1.535
3150631CHESTG8
50/50
1.511
971047AG2-646 GEN
50/50
42.989
316132AB2-190 GEN1
Solar/Wind Harmer
0.61
316369SG1_INVT
Solar/Wind Harmer
0.004
315976AC1-164 GENA
Solar/Wind Harmer
9.735
316169AC1-164_GENC
Solar/Wind Harmer
8.41
315975AC1-164 GENB
Solar/Wind Harmer
0.288
972265AH1-717 GEN
Adder
6.312
3151201GRAVEL4
Adder
5.917
3151191GRAVEL3
Adder
5.842
3151211GRAVEL5
Adder
5.842
316314AB2-024 C
Solar/Wind Harmer
0
316059AD1-063 C
Solar/Wind Harmer
0
3143873LANEXA
Solar/Wind Harmer
0.045
970189AG2-124 GEN
Solar/Wind Harmer
2.166
971445AH1-216 GEN
Solar/Wind Harmer
5.125
315662AE1-191 GEN
Solar/Wind Harmer
0.002
315666AE1-190 GEN
Solar/Wind Harmer
0.001
3141873WAN 176
Solar/Wind Harmer
0.014
3141913WHIT STONE
Solar/Wind Harmer
0.071
3138133OCRAN
Solar/Wind Harmer
0.021
3141783LANCAST
Solar/Wind Harmer
0.042
3141783LANCAST
Solar/Wind Harmer
0.028
3138283WHITEMARSH
Solar/Wind Harmer
0.016
962981AG1-147 GEN
Solar/Wind Harmer
2.557
3142433PROV 92
Adder
0.133
3142433PROV 92
Adder
0.133
970327AG2-215 GEN
Solar/Wind Harmer
2.22
971167AH1-042 GEN
Solar/Wind Harmer
5.919
3141813NORNECK
Solar/Wind Harmer
0.064
315833AF1-017_GEN
Solar/Wind Harmer
0
316349AD2-085 GEN
Solar/Wind Harmer
0.04
316311AC2-079 GEN
Solar/Wind Harmer
1.663
3152611GOSPORTB
Adder
0.725
3152621GOSPORTC
Adder
0.615
3152601GOSPORTA
Adder
0.568
3151081ELIZAR1
Adder
5.179
3151091ELIZAR2
Adder
5.089
316233AE1-074 FULL
Solar/Wind Helper
0.525
3143096IRON208
50/50
2.307
3143096IRON208
50/50
2.26
3150801HOPHCF4
50/50
0.746
971211AH1-065 GEN
50/50
0.9
3151161SURRY 1
50/50
3.123
3142946ENON
Solar/Wind Harmer
0.066
970133AG2-095 GEN
Solar/Wind Harmer
1.215
970129AG2-093 GEN
Solar/Wind Harmer
6.944
315778AD1-151 GEN
Solar/Wind Harmer
8.525
961611AG1-000B GEN
Solar/Wind Harmer
2.377
3151221GRAVEL6
Adder
5.91
3151171GRAVELC
Adder
1.137
3141766HARMONY
Solar/Wind Harmer
1.013
316382AG1-145 C
Solar/Wind Harmer
0.001
3141843SHACKLE
Adder
0.374
316203AE2-005 GEN
Solar/Wind Harmer
0
316280AD1-041 GEN
Solar/Wind Harmer
0.001
316156AD2-030 GEN
Solar/Wind Harmer
0.053
3141873WAN 176
Solar/Wind Harmer
1.283
3145336SMITFLD
Solar/Wind Harmer
0.029
962971AG1-146 GEN
Solar/Wind Harmer
1.096
3142433PROV 92
Adder
0.133
3142433PROV 92
Adder
0.133
970009AG2-005 GEN
Solar/Wind Harmer
0.505
3144216WINCHST
Adder
0.253
316404AE1-155 C
Solar/Wind Harmer
0.015
315813AE1-149 C
Solar/Wind Harmer
3.52
3150921YORKTN3
Adder
1.637
3150351NORNECKC2
Adder
0.647
970659AG2-427 GEN
Solar/Wind Harmer
0.67
3143096IRON208
50/50
2.307
3150641CHESTS8
50/50
0.778
944631AF1-128 GEN
50/50
122.303
3150771HOPHCF1
50/50
0.513
970129AG2-093 GEN
Solar/Wind Harmer
3.268
316458AB2-190 GEN2
Solar/Wind Harmer
0.61
971069AG2-661 GEN
Solar/Wind Harmer
1.894
971647AH1-324 GEN
Solar/Wind Harmer
4.071
961611AG1-000B GEN
Solar/Wind Harmer
4.675
3151171GRAVELC
Adder
0.865
3141766HARMONY
Solar/Wind Harmer
0.015
316159AE1-175 C
Solar/Wind Harmer
0.063
971777AH1-397 GEN
Solar/Wind Harmer
0.193
3141843SHACKLE
Adder
0.374
3145336SMITFLD
Solar/Wind Harmer
0.288
3138133OCRAN
Solar/Wind Harmer
0.042
3142433PROV 92
Solar/Wind Harmer
0.273
3142433PROV 92
Adder
0.133
3142433PROV 92
Adder
0.133
962861AG1-135 GEN
Solar/Wind Harmer
2.133
3138126ROCKLANDING
Solar/Wind Harmer
0.03
3141726DUNNSVL
Solar/Wind Harmer
0.265
971317AH1-138 GEN
Solar/Wind Harmer
0.495
3150351NORNECKC2
Adder
0.637
970659AG2-427 GEN
Solar/Wind Harmer
3.065
316381AD1-082 GEN
Solar/Wind Harmer
0.066
970661AG2-428 GEN
Solar/Wind Harmer
6.114
316072AD1-144
Solar/Wind Harmer
0.022
316337AD2-073 GEN
Solar/Wind Harmer
0.051
316375AC2-012 GEN
Solar/Wind Harmer
0.001
3150981CHESPKA
Adder
0.711
3143526WINTERP
Solar/Wind Helper
1.788
3143226MDLTHAN
Solar/Wind Helper
0.157
316083AB2-161 GEN
Solar/Wind Harmer
0.001
970661AG2-428 GEN
Solar/Wind Harmer
1.3
3144536CHRHLND
Solar/Wind Harmer
0.009
3144873MCLAUGH
Solar/Wind Harmer
0.001
3151101ELIZAR3
Adder
5.246
3150621CHESTS7
50/50
0.705
3150781HOPHCF2
50/50
0.513
3150791HOPHCF3
50/50
0.513
3150761HOPPOLC
50/50
0.325
971213AH1-066 GEN
50/50
0.45
3142946ENON
Solar/Wind Harmer
0.02
316033AB2-134 GEN
Solar/Wind Harmer
0.006
315697AD1-025 GEN
Solar/Wind Harmer
0.114
316236AE1-162_GEN
Solar/Wind Harmer
0.001
958261AF2-120 GEN
Solar/Wind Harmer
2.192
316077AC2-138 C
Solar/Wind Harmer
0
3150341NORNECKC1
Adder
0.669
3150341NORNECKC1
Adder
0.663
316075AC2-137 C
Solar/Wind Harmer
0.018
970657AG2-426 GEN
Solar/Wind Harmer
2.184
970657AG2-426 GEN
Solar/Wind Harmer
0.458
316036AC1-147 C
Solar/Wind Harmer
0.011
3150991CHESPKB
Adder
0.596
3150991CHESPKB
Adder
0.582
3143526WINTERP
Solar/Wind Helper
1.788
CPLELTFEXP_CPLE->PJM
CLTF
1.919
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.103
NYPJM->LTFIMP_NY
CLTF
0.354
LGEELTFEXP_LGEE->PJM
CLTF
0.127
WECLTFEXP_WEC->PJM
CLTF
0.063
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.024
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.746
MECLTFEXP_MEC->PJM
CLTF
0.397
SIGELTFEXP_SIGE->PJM
CLTF
0.011
LAGNLTFEXP_LAGN->PJM
CLTF
1.059
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.936
TVALTFEXP_TVA->PJM
CLTF
0.526

Details for 6NORNECK-6SANDERS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6NORNECK-6SANDERS 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:115.31 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:659.04
MW Contribution:11.32
Bus #Bus NameTypeMW Contribution
3150351NORNECKC2
50/50
2.962
966661AG1-536 GEN
50/50
6.865
3141843SHACKLE
50/50
0.749
3142433PROV 92
50/50
0.222
3142433PROV 92
50/50
0.222
971353AH1-157 GEN
50/50
7.457
970017AG2-010 GEN
50/50
4.736
3150641CHESTS8
50/50
0.205
944631AF1-128 GEN
50/50
32.202
3141726DUNNSVL
Solar/Wind Harmer
1.046
962861AG1-135 GEN
Solar/Wind Harmer
7.54
3138133OCRAN
Solar/Wind Harmer
0.103
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.365
3142433PROV 92
Solar/Wind Harmer
0.43
971317AH1-138 GEN
Solar/Wind Harmer
0.617
316159AE1-175 C
Solar/Wind Harmer
0.065
3138126ROCKLANDING
Solar/Wind Harmer
0.033
3142416OLDCHRC
Solar/Wind Harmer
0.15
3142416OLDCHRC
Solar/Wind Harmer
0.058
3151171GRAVELC
Adder
0.606
961611AG1-000B GEN
Solar/Wind Harmer
2.976
971647AH1-324 GEN
Solar/Wind Harmer
2.415
971069AG2-661 GEN
Solar/Wind Harmer
1.002
316337AD2-073 GEN
Solar/Wind Helper
2.345
315759AF1-018 GEN
50/50
4.965
3142433PROV 92
50/50
0.222
3142433PROV 92
50/50
0.222
3150611CHESTG7
50/50
0.404
3150631CHESTG8
50/50
0.398
971047AG2-646 GEN
50/50
11.319
972263AH1-716 GEN
50/50
33.189
3141813NORNECK
Solar/Wind Harmer
0.28
970327AG2-215 GEN
Solar/Wind Harmer
7.212
962981AG1-147 GEN
Solar/Wind Harmer
7.706
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.073
3138133OCRAN
Solar/Wind Harmer
0.052
3141913WHIT STONE
Solar/Wind Harmer
0.167
3141873WAN 176
Solar/Wind Harmer
0.029
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
4.097
316314AB2-024 C
Solar/Wind Harmer
0
3143873LANEXA
Solar/Wind Harmer
0.075
3138283WHITEMARSH
Solar/Wind Harmer
0.025
971167AH1-042 GEN
Solar/Wind Harmer
9.171
315976AC1-164 GENA
Solar/Wind Harmer
8.348
316169AC1-164_GENC
Solar/Wind Harmer
7.212
315975AC1-164 GENB
Solar/Wind Harmer
0.247
316312AB1-027
Solar/Wind Harmer
0.103
972265AH1-717 GEN
Adder
4.42
3151201GRAVEL4
Adder
4.144
3151191GRAVEL3
Adder
4.091
3151211GRAVEL5
Adder
4.091
316369SG1_INVT
Solar/Wind Harmer
0.002
316223AC1-118
Solar/Wind Helper
2.149
3141426STAFORD
Solar/Wind Helper
0.031
3150351NORNECKC2
50/50
3.012
970575AG2-366 GEN
50/50
3.67
315749AE2-041 GEN
50/50
4.965
3141843SHACKLE
50/50
0.749
3142433PROV 92
50/50
0.222
3142433PROV 92
50/50
0.222
3150921YORKTN3
50/50
1.944
3144216WINCHST
50/50
0.281
3151161SURRY 1
50/50
2.187
316404AE1-155 C
Solar/Wind Harmer
0.054
970009AG2-005 GEN
Solar/Wind Harmer
1.641
962971AG1-146 GEN
Solar/Wind Harmer
3.303
316156AD2-030 GEN
Solar/Wind Harmer
0.109
3141873WAN 176
Solar/Wind Harmer
2.62
316280AD1-041 GEN
Solar/Wind Harmer
0.003
3141766HARMONY
Solar/Wind Harmer
1.862
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
3150341NORNECKC1
50/50
3.111
3150341NORNECKC1
50/50
3.086
963611AG1-210 GEN
50/50
0.996
3150621CHESTS7
50/50
0.186
316077AC2-138 C
Solar/Wind Harmer
0.001
958261AF2-120 GEN
Solar/Wind Harmer
7.981
316075AC2-137 C
Solar/Wind Harmer
0.02
3142946ENON
Solar/Wind Harmer
0.007
316033AB2-134 GEN
Solar/Wind Harmer
0.003
315697AD1-025 GEN
Solar/Wind Harmer
0.063
316382AG1-145 C
Solar/Wind Harmer
0.001
3142946ENON
Solar/Wind Harmer
0.023
970293AG2-193 GEN
Solar/Wind Harmer
0.674
3142416OLDCHRC
Solar/Wind Harmer
0.56
3151221GRAVEL6
Adder
4.139
3151171GRAVELC
Adder
0.796
961611AG1-000B GEN
Solar/Wind Harmer
1.513
315778AD1-151 GEN
Solar/Wind Harmer
4.508
3141906WESTMOR
Solar/Wind Helper
0.564
CPLELTFEXP_CPLE->PJM
CLTF
2.043
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.462
NYPJM->LTFIMP_NY
CLTF
0.537
LGEELTFEXP_LGEE->PJM
CLTF
0.304
WECLTFEXP_WEC->PJM
CLTF
0.153
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.326
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.737
MECLTFEXP_MEC->PJM
CLTF
0.803
SIGELTFEXP_SIGE->PJM
CLTF
0.025
LAGNLTFEXP_LAGN->PJM
CLTF
1.568
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.516
TVALTFEXP_TVA->PJM
CLTF
0.792

Details for 6OAKGROV-AF1-114 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6OAKGROV-AF1-114 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.12 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:635.05
MW Contribution:11.29
Bus #Bus NameTypeMW Contribution
315759AF1-018 GEN
50/50
4.959
3142433PROV 92
50/50
0.222
3142433PROV 92
50/50
0.222
3150611CHESTG7
50/50
0.403
3150631CHESTG8
50/50
0.397
971047AG2-646 GEN
50/50
11.288
972263AH1-716 GEN
50/50
33.088
316223AC1-118
Solar/Wind Harmer
0.296
3141813NORNECK
Solar/Wind Harmer
0.28
970327AG2-215 GEN
Solar/Wind Harmer
7.206
962981AG1-147 GEN
Solar/Wind Harmer
7.699
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.073
3138133OCRAN
Solar/Wind Harmer
0.052
3141913WHIT STONE
Solar/Wind Harmer
0.167
3141873WAN 176
Solar/Wind Harmer
0.029
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
4.092
316314AB2-024 C
Solar/Wind Harmer
0
3143873LANEXA
Solar/Wind Harmer
0.075
3138283WHITEMARSH
Solar/Wind Harmer
0.025
971167AH1-042 GEN
Solar/Wind Harmer
9.155
315976AC1-164 GENA
Solar/Wind Harmer
8.33
316169AC1-164_GENC
Solar/Wind Harmer
7.197
315975AC1-164 GENB
Solar/Wind Harmer
0.246
316312AB1-027
Solar/Wind Harmer
0.103
972265AH1-717 GEN
Adder
4.406
3151201GRAVEL4
Adder
4.131
3151191GRAVEL3
Adder
4.078
3151211GRAVEL5
Adder
4.078
316369SG1_INVT
Solar/Wind Harmer
0.002
3141426STAFORD
Solar/Wind Helper
0.031
3150351NORNECKC2
50/50
2.96
966661AG1-536 GEN
50/50
6.86
3141843SHACKLE
50/50
0.748
3142433PROV 92
50/50
0.222
3142433PROV 92
50/50
0.222
971353AH1-157 GEN
50/50
7.442
970017AG2-010 GEN
50/50
4.725
3150641CHESTS8
50/50
0.204
944631AF1-128 GEN
50/50
32.114
972135AH1-637 GEN
Solar/Wind Harmer
4.393
316337AD2-073 GEN
Solar/Wind Harmer
0.299
3141726DUNNSVL
Solar/Wind Harmer
1.045
962861AG1-135 GEN
Solar/Wind Harmer
7.535
3138133OCRAN
Solar/Wind Harmer
0.103
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.364
3142433PROV 92
Solar/Wind Harmer
0.43
971317AH1-138 GEN
Solar/Wind Harmer
0.616
316159AE1-175 C
Solar/Wind Harmer
0.065
3138126ROCKLANDING
Solar/Wind Harmer
0.033
3142416OLDCHRC
Solar/Wind Harmer
0.15
3142416OLDCHRC
Solar/Wind Harmer
0.057
3151171GRAVELC
Adder
0.604
961611AG1-000B GEN
Solar/Wind Harmer
2.967
971647AH1-324 GEN
Solar/Wind Harmer
2.407
3150341NORNECKC1
50/50
3.109
3150341NORNECKC1
50/50
3.084
963611AG1-210 GEN
50/50
0.995
3150621CHESTS7
50/50
0.185
316077AC2-138 C
Solar/Wind Harmer
0.001
958261AF2-120 GEN
Solar/Wind Harmer
7.975
316075AC2-137 C
Solar/Wind Harmer
0.02
3142946ENON
Solar/Wind Harmer
0.007
316033AB2-134 GEN
Solar/Wind Harmer
0.003
315697AD1-025 GEN
Solar/Wind Harmer
0.063
3150351NORNECKC2
50/50
3.01
970575AG2-366 GEN
50/50
3.666
315749AE2-041 GEN
50/50
4.959
3141843SHACKLE
50/50
0.748
3142433PROV 92
50/50
0.222
3142433PROV 92
50/50
0.222
3150921YORKTN3
50/50
1.939
3144216WINCHST
50/50
0.281
3151161SURRY 1
50/50
2.18
970737AG2-469 GEN
Solar/Wind Harmer
20.194
3141906WESTMOR
Solar/Wind Harmer
0.165
316404AE1-155 C
Solar/Wind Harmer
0.054
970009AG2-005 GEN
Solar/Wind Harmer
1.64
962971AG1-146 GEN
Solar/Wind Harmer
3.3
316156AD2-030 GEN
Solar/Wind Harmer
0.109
3141873WAN 176
Solar/Wind Harmer
2.617
316280AD1-041 GEN
Solar/Wind Harmer
0.003
3141766HARMONY
Solar/Wind Harmer
1.86
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316382AG1-145 C
Solar/Wind Harmer
0.001
3142946ENON
Solar/Wind Harmer
0.023
970293AG2-193 GEN
Solar/Wind Harmer
0.672
3142416OLDCHRC
Solar/Wind Harmer
0.558
3151221GRAVEL6
Adder
4.126
3151171GRAVELC
Adder
0.794
961611AG1-000B GEN
Solar/Wind Harmer
1.508
CPLELTFEXP_CPLE->PJM
CLTF
2.028
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.282
NYPJM->LTFIMP_NY
CLTF
0.546
LGEELTFEXP_LGEE->PJM
CLTF
0.294
WECLTFEXP_WEC->PJM
CLTF
0.148
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.13
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.686
MECLTFEXP_MEC->PJM
CLTF
0.78
SIGELTFEXP_SIGE->PJM
CLTF
0.024
LAGNLTFEXP_LAGN->PJM
CLTF
1.541
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.475
TVALTFEXP_TVA->PJM
CLTF
0.778

Details for 6SANDERS-6WESTMOR 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.11 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:646.44
MW Contribution:11.3
Bus #Bus NameTypeMW Contribution
315759AF1-018 GEN
50/50
4.962
3142433PROV 92
50/50
0.222
3142433PROV 92
50/50
0.222
3150611CHESTG7
50/50
0.404
3150631CHESTG8
50/50
0.397
971047AG2-646 GEN
50/50
11.304
972263AH1-716 GEN
50/50
33.141
3141813NORNECK
Solar/Wind Harmer
0.28
970327AG2-215 GEN
Solar/Wind Harmer
7.209
962981AG1-147 GEN
Solar/Wind Harmer
7.703
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.073
3138133OCRAN
Solar/Wind Harmer
0.052
3141913WHIT STONE
Solar/Wind Harmer
0.167
3141873WAN 176
Solar/Wind Harmer
0.029
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
4.094
316314AB2-024 C
Solar/Wind Harmer
0
3143873LANEXA
Solar/Wind Harmer
0.075
3138283WHITEMARSH
Solar/Wind Harmer
0.025
971167AH1-042 GEN
Solar/Wind Harmer
9.163
315976AC1-164 GENA
Solar/Wind Harmer
8.34
316169AC1-164_GENC
Solar/Wind Harmer
7.205
315975AC1-164 GENB
Solar/Wind Harmer
0.247
316312AB1-027
Solar/Wind Harmer
0.103
972265AH1-717 GEN
Adder
4.414
3151201GRAVEL4
Adder
4.138
3151191GRAVEL3
Adder
4.085
3151211GRAVEL5
Adder
4.085
316369SG1_INVT
Solar/Wind Harmer
0.002
316223AC1-118
Solar/Wind Helper
2.149
3141426STAFORD
Solar/Wind Helper
0.031
3150341NORNECKC1
50/50
3.11
3150341NORNECKC1
50/50
3.085
963611AG1-210 GEN
50/50
0.995
3150621CHESTS7
50/50
0.185
316077AC2-138 C
Solar/Wind Harmer
0.001
958261AF2-120 GEN
Solar/Wind Harmer
7.978
316075AC2-137 C
Solar/Wind Harmer
0.02
3142946ENON
Solar/Wind Harmer
0.007
316033AB2-134 GEN
Solar/Wind Harmer
0.003
315697AD1-025 GEN
Solar/Wind Harmer
0.063
3150351NORNECKC2
50/50
3.011
970575AG2-366 GEN
50/50
3.668
315749AE2-041 GEN
50/50
4.962
3141843SHACKLE
50/50
0.749
3142433PROV 92
50/50
0.222
3142433PROV 92
50/50
0.222
3150921YORKTN3
50/50
1.942
3144216WINCHST
50/50
0.281
3151161SURRY 1
50/50
2.184
316404AE1-155 C
Solar/Wind Harmer
0.054
970009AG2-005 GEN
Solar/Wind Harmer
1.64
962971AG1-146 GEN
Solar/Wind Harmer
3.301
316156AD2-030 GEN
Solar/Wind Harmer
0.109
3141873WAN 176
Solar/Wind Harmer
2.619
316280AD1-041 GEN
Solar/Wind Harmer
0.003
3141766HARMONY
Solar/Wind Harmer
1.861
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316382AG1-145 C
Solar/Wind Harmer
0.001
3142946ENON
Solar/Wind Harmer
0.023
970293AG2-193 GEN
Solar/Wind Harmer
0.673
3142416OLDCHRC
Solar/Wind Harmer
0.559
3151221GRAVEL6
Adder
4.133
3151171GRAVELC
Adder
0.795
961611AG1-000B GEN
Solar/Wind Harmer
1.511
315778AD1-151 GEN
Solar/Wind Harmer
4.501
3141906WESTMOR
Solar/Wind Helper
0.564
3150351NORNECKC2
50/50
2.961
966661AG1-536 GEN
50/50
6.863
3141843SHACKLE
50/50
0.749
3142433PROV 92
50/50
0.222
3142433PROV 92
50/50
0.222
971353AH1-157 GEN
50/50
7.45
970017AG2-010 GEN
50/50
4.731
3150641CHESTS8
50/50
0.205
944631AF1-128 GEN
50/50
32.161
316337AD2-073 GEN
Solar/Wind Harmer
0.299
3141726DUNNSVL
Solar/Wind Harmer
1.046
962861AG1-135 GEN
Solar/Wind Harmer
7.538
3138133OCRAN
Solar/Wind Harmer
0.103
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.364
3142433PROV 92
Solar/Wind Harmer
0.43
971317AH1-138 GEN
Solar/Wind Harmer
0.617
316159AE1-175 C
Solar/Wind Harmer
0.065
3138126ROCKLANDING
Solar/Wind Harmer
0.033
3142416OLDCHRC
Solar/Wind Harmer
0.15
3142416OLDCHRC
Solar/Wind Harmer
0.057
3151171GRAVELC
Adder
0.605
961611AG1-000B GEN
Solar/Wind Harmer
2.971
971647AH1-324 GEN
Solar/Wind Harmer
2.411
971069AG2-661 GEN
Solar/Wind Harmer
1
CPLELTFEXP_CPLE->PJM
CLTF
2.036
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.378
NYPJM->LTFIMP_NY
CLTF
0.541
LGEELTFEXP_LGEE->PJM
CLTF
0.299
WECLTFEXP_WEC->PJM
CLTF
0.151
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.234
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.714
MECLTFEXP_MEC->PJM
CLTF
0.792
SIGELTFEXP_SIGE->PJM
CLTF
0.024
LAGNLTFEXP_LAGN->PJM
CLTF
1.555
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.497
TVALTFEXP_TVA->PJM
CLTF
0.786

Details for 6WESTMOR-AG2-469 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6WESTMOR-AG2-469 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.62 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:637.96
MW Contribution:11.29
Bus #Bus NameTypeMW Contribution
315759AF1-018 GEN
50/50
4.959
3142433PROV 92
50/50
0.222
3142433PROV 92
50/50
0.222
3150611CHESTG7
50/50
0.403
3150631CHESTG8
50/50
0.397
971047AG2-646 GEN
50/50
11.288
972263AH1-716 GEN
50/50
33.088
316223AC1-118
Solar/Wind Harmer
0.296
3141813NORNECK
Solar/Wind Harmer
0.28
970327AG2-215 GEN
Solar/Wind Harmer
7.206
962981AG1-147 GEN
Solar/Wind Harmer
7.699
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.073
3138133OCRAN
Solar/Wind Harmer
0.052
3141913WHIT STONE
Solar/Wind Harmer
0.167
3141873WAN 176
Solar/Wind Harmer
0.029
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
4.092
316314AB2-024 C
Solar/Wind Harmer
0
3143873LANEXA
Solar/Wind Harmer
0.075
3138283WHITEMARSH
Solar/Wind Harmer
0.025
971167AH1-042 GEN
Solar/Wind Harmer
9.155
315976AC1-164 GENA
Solar/Wind Harmer
8.33
316169AC1-164_GENC
Solar/Wind Harmer
7.197
315975AC1-164 GENB
Solar/Wind Harmer
0.246
316312AB1-027
Solar/Wind Harmer
0.103
972265AH1-717 GEN
Adder
4.406
3151201GRAVEL4
Adder
4.131
3151191GRAVEL3
Adder
4.078
3151211GRAVEL5
Adder
4.078
316369SG1_INVT
Solar/Wind Harmer
0.002
3141426STAFORD
Solar/Wind Helper
0.031
3150341NORNECKC1
50/50
3.109
3150341NORNECKC1
50/50
3.084
963611AG1-210 GEN
50/50
0.995
3150621CHESTS7
50/50
0.185
316077AC2-138 C
Solar/Wind Harmer
0.001
958261AF2-120 GEN
Solar/Wind Harmer
7.975
316075AC2-137 C
Solar/Wind Harmer
0.02
3142946ENON
Solar/Wind Harmer
0.007
316033AB2-134 GEN
Solar/Wind Harmer
0.003
315697AD1-025 GEN
Solar/Wind Harmer
0.063
3150351NORNECKC2
50/50
3.01
970575AG2-366 GEN
50/50
3.666
315749AE2-041 GEN
50/50
4.959
3141843SHACKLE
50/50
0.748
3142433PROV 92
50/50
0.222
3142433PROV 92
50/50
0.222
3150921YORKTN3
50/50
1.939
3144216WINCHST
50/50
0.281
3151161SURRY 1
50/50
2.18
3141906WESTMOR
Solar/Wind Harmer
0.165
316404AE1-155 C
Solar/Wind Harmer
0.054
970009AG2-005 GEN
Solar/Wind Harmer
1.64
962971AG1-146 GEN
Solar/Wind Harmer
3.3
316156AD2-030 GEN
Solar/Wind Harmer
0.109
3141873WAN 176
Solar/Wind Harmer
2.617
316280AD1-041 GEN
Solar/Wind Harmer
0.003
3141766HARMONY
Solar/Wind Harmer
1.86
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316382AG1-145 C
Solar/Wind Harmer
0.001
3142946ENON
Solar/Wind Harmer
0.023
970293AG2-193 GEN
Solar/Wind Harmer
0.672
3142416OLDCHRC
Solar/Wind Harmer
0.558
3151221GRAVEL6
Adder
4.126
3151171GRAVELC
Adder
0.794
961611AG1-000B GEN
Solar/Wind Harmer
1.508
3150351NORNECKC2
50/50
2.96
966661AG1-536 GEN
50/50
6.86
3141843SHACKLE
50/50
0.748
3142433PROV 92
50/50
0.222
3142433PROV 92
50/50
0.222
971353AH1-157 GEN
50/50
7.442
970017AG2-010 GEN
50/50
4.725
3150641CHESTS8
50/50
0.204
944631AF1-128 GEN
50/50
32.114
316337AD2-073 GEN
Solar/Wind Harmer
0.299
3141726DUNNSVL
Solar/Wind Harmer
1.045
962861AG1-135 GEN
Solar/Wind Harmer
7.535
3138133OCRAN
Solar/Wind Harmer
0.103
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.364
3142433PROV 92
Solar/Wind Harmer
0.43
971317AH1-138 GEN
Solar/Wind Harmer
0.616
316159AE1-175 C
Solar/Wind Harmer
0.065
3138126ROCKLANDING
Solar/Wind Harmer
0.033
3142416OLDCHRC
Solar/Wind Harmer
0.15
3142416OLDCHRC
Solar/Wind Harmer
0.057
3151171GRAVELC
Adder
0.604
961611AG1-000B GEN
Solar/Wind Harmer
2.967
971647AH1-324 GEN
Solar/Wind Harmer
2.407
CPLELTFEXP_CPLE->PJM
CLTF
2.028
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.282
NYPJM->LTFIMP_NY
CLTF
0.546
LGEELTFEXP_LGEE->PJM
CLTF
0.294
WECLTFEXP_WEC->PJM
CLTF
0.148
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.13
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.686
MECLTFEXP_MEC->PJM
CLTF
0.78
SIGELTFEXP_SIGE->PJM
CLTF
0.024
LAGNLTFEXP_LAGN->PJM
CLTF
1.541
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.475
TVALTFEXP_TVA->PJM
CLTF
0.778

Details for AF1-114 TP-6DAHLGREN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AF1-114 TP-6DAHLGREN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.84 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:679.2
MW Contribution:11.22
Bus #Bus NameTypeMW Contribution
3150351NORNECKC2
50/50
2.956
966661AG1-536 GEN
50/50
6.849
3141843SHACKLE
50/50
0.746
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
971353AH1-157 GEN
50/50
7.408
970017AG2-010 GEN
50/50
4.699
3150641CHESTS8
50/50
0.203
944631AF1-128 GEN
50/50
31.925
972135AH1-637 GEN
Solar/Wind Harmer
4.389
316337AD2-073 GEN
Solar/Wind Harmer
0.299
3141726DUNNSVL
Solar/Wind Harmer
1.044
962861AG1-135 GEN
Solar/Wind Harmer
7.523
3138133OCRAN
Solar/Wind Harmer
0.103
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.363
3142433PROV 92
Solar/Wind Harmer
0.428
971317AH1-138 GEN
Solar/Wind Harmer
0.613
316159AE1-175 C
Solar/Wind Harmer
0.065
3138126ROCKLANDING
Solar/Wind Harmer
0.032
3142416OLDCHRC
Solar/Wind Harmer
0.149
3142416OLDCHRC
Solar/Wind Harmer
0.057
3151171GRAVELC
Adder
0.6
315759AF1-018 GEN
50/50
4.946
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3150611CHESTG7
50/50
0.401
3150631CHESTG8
50/50
0.394
971047AG2-646 GEN
50/50
11.221
972263AH1-716 GEN
50/50
32.871
944491AF1-114 GEN
Solar/Wind Harmer
0.002
316223AC1-118
Solar/Wind Harmer
0.296
3141813NORNECK
Solar/Wind Harmer
0.279
970327AG2-215 GEN
Solar/Wind Harmer
7.194
962981AG1-147 GEN
Solar/Wind Harmer
7.685
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.073
3138133OCRAN
Solar/Wind Harmer
0.051
3141913WHIT STONE
Solar/Wind Harmer
0.166
3141873WAN 176
Solar/Wind Harmer
0.029
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
4.081
316314AB2-024 C
Solar/Wind Harmer
0
3143873LANEXA
Solar/Wind Harmer
0.075
3138283WHITEMARSH
Solar/Wind Harmer
0.025
971167AH1-042 GEN
Solar/Wind Harmer
9.122
315976AC1-164 GENA
Solar/Wind Harmer
8.292
316169AC1-164_GENC
Solar/Wind Harmer
7.163
315975AC1-164 GENB
Solar/Wind Harmer
0.245
316312AB1-027
Solar/Wind Harmer
0.102
972265AH1-717 GEN
Adder
4.377
3151201GRAVEL4
Adder
4.104
3151191GRAVEL3
Adder
4.052
3151211GRAVEL5
Adder
4.052
3141426STAFORD
Solar/Wind Helper
0.031
3150351NORNECKC2
50/50
3.006
970575AG2-366 GEN
50/50
3.66
315749AE2-041 GEN
50/50
4.946
3141843SHACKLE
50/50
0.746
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3150921YORKTN3
50/50
1.929
3144216WINCHST
50/50
0.279
3151161SURRY 1
50/50
2.166
970737AG2-469 GEN
Solar/Wind Harmer
20.178
3141906WESTMOR
Solar/Wind Harmer
0.165
316404AE1-155 C
Solar/Wind Harmer
0.054
970009AG2-005 GEN
Solar/Wind Harmer
1.637
962971AG1-146 GEN
Solar/Wind Harmer
3.294
316156AD2-030 GEN
Solar/Wind Harmer
0.109
3141873WAN 176
Solar/Wind Harmer
2.61
316280AD1-041 GEN
Solar/Wind Harmer
0.003
3141766HARMONY
Solar/Wind Harmer
1.855
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316382AG1-145 C
Solar/Wind Harmer
0.001
3142946ENON
Solar/Wind Harmer
0.023
970293AG2-193 GEN
Solar/Wind Harmer
0.668
3142416OLDCHRC
Solar/Wind Harmer
0.555
3151221GRAVEL6
Adder
4.099
3151171GRAVELC
Adder
0.789
3150341NORNECKC1
50/50
3.105
3150341NORNECKC1
50/50
3.08
963611AG1-210 GEN
50/50
0.994
3150621CHESTS7
50/50
0.184
316077AC2-138 C
Solar/Wind Harmer
0.001
958261AF2-120 GEN
Solar/Wind Harmer
7.962
316075AC2-137 C
Solar/Wind Harmer
0.019
3142946ENON
Solar/Wind Harmer
0.007
CPLELTFEXP_CPLE->PJM
CLTF
1.997
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.895
NYPJM->LTFIMP_NY
CLTF
0.564
LGEELTFEXP_LGEE->PJM
CLTF
0.274
WECLTFEXP_WEC->PJM
CLTF
0.137
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.711
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.577
MECLTFEXP_MEC->PJM
CLTF
0.732
SIGELTFEXP_SIGE->PJM
CLTF
0.022
LAGNLTFEXP_LAGN->PJM
CLTF
1.483
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.388
TVALTFEXP_TVA->PJM
CLTF
0.749

Details for AF2-013 TP-6ARNOLDS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AF2-013 TP-6ARNOLDS 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:127.21 %
Rating:559.3 MVA
Rating Type:B
MVA to Mitigate:711.49
MW Contribution:11.22
Bus #Bus NameTypeMW Contribution
3150351NORNECKC2
50/50
3.006
970575AG2-366 GEN
50/50
3.66
315749AE2-041 GEN
50/50
4.946
3141843SHACKLE
50/50
0.746
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3150921YORKTN3
50/50
1.929
3144216WINCHST
50/50
0.279
3151161SURRY 1
50/50
2.166
970737AG2-469 GEN
Solar/Wind Harmer
20.178
3141906WESTMOR
Solar/Wind Harmer
0.165
316404AE1-155 C
Solar/Wind Harmer
0.054
970009AG2-005 GEN
Solar/Wind Harmer
1.637
962971AG1-146 GEN
Solar/Wind Harmer
3.294
316156AD2-030 GEN
Solar/Wind Harmer
0.109
3141873WAN 176
Solar/Wind Harmer
2.61
316280AD1-041 GEN
Solar/Wind Harmer
0.003
3141766HARMONY
Solar/Wind Harmer
1.855
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316382AG1-145 C
Solar/Wind Harmer
0.001
3142946ENON
Solar/Wind Harmer
0.023
970293AG2-193 GEN
Solar/Wind Harmer
0.668
3142416OLDCHRC
Solar/Wind Harmer
0.555
3151221GRAVEL6
Adder
4.099
3151171GRAVELC
Adder
0.789
957191AF2-013 GEN
50/50
65.713
3150341NORNECKC1
50/50
3.105
3150341NORNECKC1
50/50
3.08
963611AG1-210 GEN
50/50
0.994
3150621CHESTS7
50/50
0.184
316077AC2-138 C
Solar/Wind Harmer
0.001
958261AF2-120 GEN
Solar/Wind Harmer
7.962
316075AC2-137 C
Solar/Wind Harmer
0.019
3142946ENON
Solar/Wind Harmer
0.007
3150351NORNECKC2
50/50
2.956
966661AG1-536 GEN
50/50
6.849
3141843SHACKLE
50/50
0.746
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
971353AH1-157 GEN
50/50
7.408
970017AG2-010 GEN
50/50
4.699
3150641CHESTS8
50/50
0.203
944631AF1-128 GEN
50/50
31.925
972135AH1-637 GEN
Solar/Wind Harmer
4.389
316337AD2-073 GEN
Solar/Wind Harmer
0.299
3141726DUNNSVL
Solar/Wind Harmer
1.044
962861AG1-135 GEN
Solar/Wind Harmer
7.523
3138133OCRAN
Solar/Wind Harmer
0.103
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.363
3142433PROV 92
Solar/Wind Harmer
0.428
971317AH1-138 GEN
Solar/Wind Harmer
0.613
316159AE1-175 C
Solar/Wind Harmer
0.065
3138126ROCKLANDING
Solar/Wind Harmer
0.032
3142416OLDCHRC
Solar/Wind Harmer
0.149
3142416OLDCHRC
Solar/Wind Harmer
0.057
3151171GRAVELC
Adder
0.6
315759AF1-018 GEN
50/50
4.946
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3150611CHESTG7
50/50
0.401
3150631CHESTG8
50/50
0.394
971047AG2-646 GEN
50/50
11.221
972263AH1-716 GEN
50/50
32.871
944491AF1-114 GEN
Solar/Wind Harmer
0.002
316223AC1-118
Solar/Wind Harmer
0.296
3141813NORNECK
Solar/Wind Harmer
0.279
970327AG2-215 GEN
Solar/Wind Harmer
7.194
962981AG1-147 GEN
Solar/Wind Harmer
7.685
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.073
3138133OCRAN
Solar/Wind Harmer
0.051
3141913WHIT STONE
Solar/Wind Harmer
0.166
3141873WAN 176
Solar/Wind Harmer
0.029
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
4.081
316314AB2-024 C
Solar/Wind Harmer
0
3143873LANEXA
Solar/Wind Harmer
0.075
3138283WHITEMARSH
Solar/Wind Harmer
0.025
971167AH1-042 GEN
Solar/Wind Harmer
9.122
315976AC1-164 GENA
Solar/Wind Harmer
8.292
316169AC1-164_GENC
Solar/Wind Harmer
7.163
315975AC1-164 GENB
Solar/Wind Harmer
0.245
316312AB1-027
Solar/Wind Harmer
0.102
972265AH1-717 GEN
Adder
4.377
3151201GRAVEL4
Adder
4.104
3151191GRAVEL3
Adder
4.052
3151211GRAVEL5
Adder
4.052
3141426STAFORD
Solar/Wind Helper
0.031
CPLELTFEXP_CPLE->PJM
CLTF
1.997
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.895
NYPJM->LTFIMP_NY
CLTF
0.564
LGEELTFEXP_LGEE->PJM
CLTF
0.274
WECLTFEXP_WEC->PJM
CLTF
0.137
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.711
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.577
MECLTFEXP_MEC->PJM
CLTF
0.732
SIGELTFEXP_SIGE->PJM
CLTF
0.022
LAGNLTFEXP_LAGN->PJM
CLTF
1.483
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.388
TVALTFEXP_TVA->PJM
CLTF
0.749

Details for AF2-013 TP-6ARNOLDS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AF2-013 TP-6ARNOLDS 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 557_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.1 %
Rating:559.3 MVA
Rating Type:B
MVA to Mitigate:604.6
MW Contribution:10.6
Bus #Bus NameTypeMW Contribution
315759AF1-018 GEN
50/50
4.976
3142433PROV 92
50/50
0.218
3142433PROV 92
50/50
0.218
972263AH1-716 GEN
50/50
35.649
3150611CHESTG7
50/50
0.379
3150631CHESTG8
50/50
0.372
971047AG2-646 GEN
50/50
10.599
944491AF1-114 GEN
Solar/Wind Harmer
0.002
316223AC1-118
Solar/Wind Harmer
0.297
3141813NORNECK
Solar/Wind Harmer
0.28
970327AG2-215 GEN
Solar/Wind Harmer
7.232
962981AG1-147 GEN
Solar/Wind Harmer
7.729
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.074
3138133OCRAN
Solar/Wind Harmer
0.052
3141913WHIT STONE
Solar/Wind Harmer
0.168
3141873WAN 176
Solar/Wind Harmer
0.03
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.001
3150351NORNECKC2
50/50
2.97
966661AG1-536 GEN
50/50
6.884
3141843SHACKLE
50/50
0.749
3142433PROV 92
50/50
0.218
3142433PROV 92
50/50
0.218
971353AH1-157 GEN
50/50
7.642
970017AG2-010 GEN
50/50
4.875
3150641CHESTS8
50/50
0.192
944631AF1-128 GEN
50/50
30.156
3152331SURRY 2
50/50
2.455
972135AH1-637 GEN
Solar/Wind Harmer
4.407
316337AD2-073 GEN
Solar/Wind Harmer
0.3
3141726DUNNSVL
Solar/Wind Harmer
1.049
962861AG1-135 GEN
Solar/Wind Harmer
7.561
3138133OCRAN
Solar/Wind Harmer
0.104
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.365
3142433PROV 92
Solar/Wind Harmer
0.422
971317AH1-138 GEN
Solar/Wind Harmer
0.633
316159AE1-175 C
Solar/Wind Harmer
0.067
3138126ROCKLANDING
Solar/Wind Harmer
0.034
3151171GRAVELC
Adder
0.607
3150351NORNECKC2
50/50
3.02
970575AG2-366 GEN
50/50
3.68
315749AE2-041 GEN
50/50
4.976
3141843SHACKLE
50/50
0.749
3142433PROV 92
50/50
0.218
3142433PROV 92
50/50
0.218
3150921YORKTN3
50/50
2.003
3144216WINCHST
50/50
0.289
3151161SURRY 1
50/50
2.191
970737AG2-469 GEN
Solar/Wind Harmer
20.26
3141906WESTMOR
Solar/Wind Harmer
0.165
316404AE1-155 C
Solar/Wind Harmer
0.054
970009AG2-005 GEN
Solar/Wind Harmer
1.646
962971AG1-146 GEN
Solar/Wind Harmer
3.312
316156AD2-030 GEN
Solar/Wind Harmer
0.109
3141873WAN 176
Solar/Wind Harmer
2.629
316280AD1-041 GEN
Solar/Wind Harmer
0.003
3141766HARMONY
Solar/Wind Harmer
1.866
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316382AG1-145 C
Solar/Wind Harmer
0.001
3142946ENON
Solar/Wind Harmer
0.022
3151221GRAVEL6
Adder
4.147
3151171GRAVELC
Adder
0.798
970293AG2-193 GEN
Solar/Wind Harmer
0.603
970189AG2-124 GEN
Solar/Wind Harmer
4.097
316314AB2-024 C
Solar/Wind Harmer
0
3143873LANEXA
Solar/Wind Harmer
0.075
3138283WHITEMARSH
Solar/Wind Harmer
0.025
971167AH1-042 GEN
Solar/Wind Harmer
8.942
315976AC1-164 GENA
Solar/Wind Harmer
8.275
316169AC1-164_GENC
Solar/Wind Harmer
7.149
315975AC1-164 GENB
Solar/Wind Harmer
0.245
972265AH1-717 GEN
Adder
4.429
3151201GRAVEL4
Adder
4.152
3151191GRAVEL3
Adder
4.099
3151211GRAVEL5
Adder
4.099
3141426STAFORD
Solar/Wind Helper
0.029
957191AF2-013 GEN
50/50
65.968
3150341NORNECKC1
50/50
3.119
3150341NORNECKC1
50/50
3.094
963611AG1-210 GEN
50/50
0.998
3150621CHESTS7
50/50
0.174
316077AC2-138 C
Solar/Wind Harmer
0.001
958261AF2-120 GEN
Solar/Wind Harmer
8.003
316075AC2-137 C
Solar/Wind Harmer
0.018
3142946ENON
Solar/Wind Harmer
0.007
CPLELTFEXP_CPLE->PJM
CLTF
1.912
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.152
NYPJM->LTFIMP_NY
CLTF
0.465
LGEELTFEXP_LGEE->PJM
CLTF
0.185
WECLTFEXP_WEC->PJM
CLTF
0.092
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.061
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.057
MECLTFEXP_MEC->PJM
CLTF
0.525
SIGELTFEXP_SIGE->PJM
CLTF
0.016
LAGNLTFEXP_LAGN->PJM
CLTF
1.213
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.047
TVALTFEXP_TVA->PJM
CLTF
0.609

Details for AG2-469 TP-6OAKGROV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AG2-469 TP-6OAKGROV 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:115.13 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:657.97
MW Contribution:11.29
Bus #Bus NameTypeMW Contribution
3150351NORNECKC2
50/50
2.96
966661AG1-536 GEN
50/50
6.86
3141843SHACKLE
50/50
0.748
3142433PROV 92
50/50
0.222
3142433PROV 92
50/50
0.222
971353AH1-157 GEN
50/50
7.442
970017AG2-010 GEN
50/50
4.725
3150641CHESTS8
50/50
0.204
944631AF1-128 GEN
50/50
32.114
316337AD2-073 GEN
Solar/Wind Harmer
0.299
3141726DUNNSVL
Solar/Wind Harmer
1.045
962861AG1-135 GEN
Solar/Wind Harmer
7.535
3138133OCRAN
Solar/Wind Harmer
0.103
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.364
3142433PROV 92
Solar/Wind Harmer
0.43
971317AH1-138 GEN
Solar/Wind Harmer
0.616
316159AE1-175 C
Solar/Wind Harmer
0.065
3138126ROCKLANDING
Solar/Wind Harmer
0.033
3142416OLDCHRC
Solar/Wind Harmer
0.15
3142416OLDCHRC
Solar/Wind Harmer
0.057
315759AF1-018 GEN
50/50
4.959
3142433PROV 92
50/50
0.222
3142433PROV 92
50/50
0.222
3150611CHESTG7
50/50
0.403
3150631CHESTG8
50/50
0.397
971047AG2-646 GEN
50/50
11.288
972263AH1-716 GEN
50/50
33.088
316223AC1-118
Solar/Wind Harmer
0.296
3141813NORNECK
Solar/Wind Harmer
0.28
970327AG2-215 GEN
Solar/Wind Harmer
7.206
962981AG1-147 GEN
Solar/Wind Harmer
7.699
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.073
3138133OCRAN
Solar/Wind Harmer
0.052
3141913WHIT STONE
Solar/Wind Harmer
0.167
3141873WAN 176
Solar/Wind Harmer
0.029
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
4.092
316314AB2-024 C
Solar/Wind Harmer
0
3143873LANEXA
Solar/Wind Harmer
0.075
3138283WHITEMARSH
Solar/Wind Harmer
0.025
971167AH1-042 GEN
Solar/Wind Harmer
9.155
315976AC1-164 GENA
Solar/Wind Harmer
8.33
316169AC1-164_GENC
Solar/Wind Harmer
7.197
315975AC1-164 GENB
Solar/Wind Harmer
0.246
316312AB1-027
Solar/Wind Harmer
0.103
972265AH1-717 GEN
Adder
4.406
3151201GRAVEL4
Adder
4.131
3151191GRAVEL3
Adder
4.078
3151211GRAVEL5
Adder
4.078
316369SG1_INVT
Solar/Wind Harmer
0.002
3141426STAFORD
Solar/Wind Helper
0.031
3150341NORNECKC1
50/50
3.109
3150341NORNECKC1
50/50
3.084
963611AG1-210 GEN
50/50
0.995
3150621CHESTS7
50/50
0.185
316077AC2-138 C
Solar/Wind Harmer
0.001
958261AF2-120 GEN
Solar/Wind Harmer
7.975
316075AC2-137 C
Solar/Wind Harmer
0.02
3142946ENON
Solar/Wind Harmer
0.007
316033AB2-134 GEN
Solar/Wind Harmer
0.003
315697AD1-025 GEN
Solar/Wind Harmer
0.063
3150351NORNECKC2
50/50
3.01
970575AG2-366 GEN
50/50
3.666
315749AE2-041 GEN
50/50
4.959
3141843SHACKLE
50/50
0.748
3142433PROV 92
50/50
0.222
3142433PROV 92
50/50
0.222
3150921YORKTN3
50/50
1.939
3144216WINCHST
50/50
0.281
3151161SURRY 1
50/50
2.18
970737AG2-469 GEN
Solar/Wind Harmer
20.194
3141906WESTMOR
Solar/Wind Harmer
0.165
316404AE1-155 C
Solar/Wind Harmer
0.054
970009AG2-005 GEN
Solar/Wind Harmer
1.64
962971AG1-146 GEN
Solar/Wind Harmer
3.3
316156AD2-030 GEN
Solar/Wind Harmer
0.109
3141873WAN 176
Solar/Wind Harmer
2.617
316280AD1-041 GEN
Solar/Wind Harmer
0.003
3141766HARMONY
Solar/Wind Harmer
1.86
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316382AG1-145 C
Solar/Wind Harmer
0.001
3142946ENON
Solar/Wind Harmer
0.023
970293AG2-193 GEN
Solar/Wind Harmer
0.672
3142416OLDCHRC
Solar/Wind Harmer
0.558
3151221GRAVEL6
Adder
4.126
3151171GRAVELC
Adder
0.794
961611AG1-000B GEN
Solar/Wind Harmer
1.508
3151171GRAVELC
Adder
0.604
961611AG1-000B GEN
Solar/Wind Harmer
2.967
971647AH1-324 GEN
Solar/Wind Harmer
2.407
CPLELTFEXP_CPLE->PJM
CLTF
2.028
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.282
NYPJM->LTFIMP_NY
CLTF
0.546
LGEELTFEXP_LGEE->PJM
CLTF
0.294
WECLTFEXP_WEC->PJM
CLTF
0.148
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.13
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.686
MECLTFEXP_MEC->PJM
CLTF
0.78
SIGELTFEXP_SIGE->PJM
CLTF
0.024
LAGNLTFEXP_LAGN->PJM
CLTF
1.541
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.475
TVALTFEXP_TVA->PJM
CLTF
0.778
CONTINGENCY 'DVP_P1-2: LN 574_SRT-S'
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3966 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 3572 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P1-2: LN 557_SRT-S'
 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1                /*8CHCKAHM     500.0 - 8ELMONT      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: 56702_SRT-A'
 OPEN BRANCH FROM BUS 314903 TO BUS 314924 CKT 1   /*8CHCKAHM     500.0 - 8SURRY       500.0
END
CONTINGENCY 'DVP_P1-2: LN 567_SRT-A'
 OPEN BRANCH FROM BUS 314903 TO BUS 314924 CKT 1   /*8CHCKAHM     500.0 - 8SURRY       500.0
END
CONTINGENCY 'DVP_P4-2: G2T567_SRT-A'
 OPEN BRANCH FROM BUS 314903 TO BUS 314924 CKT 1   /*8CHCKAHM     500.0 - 8SURRY       500.0
 OPEN BRANCH FROM BUS 314924 TO BUS 315233 CKT 1   /*8SURRY       500.0 - 1SURRY 2      22.0
 OPEN BUS 315233                                   /*1SURRY 2      22.0
END
CONTINGENCY 'DVP_P4-2: 208T287_SRT-A'
 OPEN BRANCH FROM BUS 314214 TO BUS 314286 CKT 1   /*6CHCKAHM     230.0 - 6CHESTF A    230.0
 OPEN BRANCH FROM BUS 314286 TO BUS 314309 CKT 1   /*6CHESTF A    230.0 - 6IRON208     230.0
 OPEN BRANCH FROM BUS 314309 TO BUS 314338 CKT 1   /*6IRON208     230.0 - 6SOUWEST     230.0
 OPEN BUS 314309                                   /*6IRON208     230.0
END
CONTINGENCY 'DVP_P1-2: LN 208_SRT-A'
 OPEN BRANCH FROM BUS 314286 TO BUS 314309 CKT 1   /*6CHESTF A    230.0 - 6IRON208     230.0
 OPEN BRANCH FROM BUS 314309 TO BUS 314338 CKT 1   /*6IRON208     230.0 - 6SOUWEST     230.0
 OPEN BUS 314309                                   /*6IRON208     230.0
END
CONTINGENCY 'DVP_P1-2: LN 211_SRT-S'
 OPEN BRANCH FROM BUS 314287 TO BUS 314303 CKT 1                /*6CHESTF B    230.0 - 6HOPEWLL     230.0
 SET POSTCONTRATING 876 BRANCH FROM BUS 314269 TO BUS 314303 CKT 1 /*6PRGEORG     230.0 - 6HOPEWLL     230.0
 SET PRECONTRATING 813 BRANCH FROM BUS 314269 TO BUS 314303 CKT 1 /*6PRGEORG     230.0 - 6HOPEWLL     230.0
END
CONTINGENCY 'DVP_P4-2: 211T2124_SRT-A'
 OPEN BRANCH FROM BUS 314269 TO BUS 314291 CKT 1   /*6PRGEORG     230.0 - 3PRGEORG     115.0
 OPEN BRANCH FROM BUS 314269 TO BUS 314303 CKT 1   /*6PRGEORG     230.0 - 6HOPEWLL     230.0
 OPEN BRANCH FROM BUS 314287 TO BUS 314303 CKT 1   /*6CHESTF B    230.0 - 6HOPEWLL     230.0
 OPEN BUS 314269                                   /*6PRGEORG     230.0
END
CONTINGENCY 'DVP_P7-1: LN 208-259_SRT-S'
 OPEN BRANCH FROM BUS 314276 TO BUS 314287 CKT 1                /*6BASIN       230.0 - 6CHESTF B    230.0
 OPEN BRANCH FROM BUS 314286 TO BUS 314309 CKT 1                /*6CHESTF A    230.0 - 6IRON208     230.0
 OPEN BRANCH FROM BUS 314309 TO BUS 314338 CKT 1                /*6IRON208     230.0 - 6SOUWEST     230.0
 OPEN BUS 314309                                                /*6IRON208     230.0
 SET POSTCONTRATING 876 BRANCH FROM BUS 314263 TO BUS 314287 CKT 1 /*6TYLER1      230.0 - 6CHESTF B    230.0
 SET PRECONTRATING 813 BRANCH FROM BUS 314263 TO BUS 314287 CKT 1 /*6TYLER1      230.0 - 6CHESTF B    230.0
END
CONTINGENCY 'DVP_P1-2: LN 2049_SRT-A'
 OPEN BRANCH FROM BUS 314271 TO BUS 314281 CKT 1   /*6ALLIED      230.0 - 6BURDET      230.0
 OPEN BRANCH FROM BUS 314281 TO BUS 314294 CKT 1   /*6BURDET      230.0 - 6ENON        230.0
 OPEN BRANCH FROM BUS 314286 TO BUS 314294 CKT 1   /*6CHESTF A    230.0 - 6ENON        230.0
 OPEN BUS 314281                                   /*6BURDET      230.0
 OPEN BUS 314294                                   /*6ENON        230.0
END
CONTINGENCY 'DVP_P1-2: LN 2050_SRT-S'
 OPEN BRANCH FROM BUS 314214 TO BUS 314308 CKT 1                /*6CHCKAHM     230.0 - 6ICI         230.0
 OPEN BRANCH FROM BUS 314271 TO BUS 314272 CKT 1                /*6ALLIED      230.0 - 6ALPINE      230.0
 OPEN BRANCH FROM BUS 314272 TO BUS 314308 CKT 1                /*6ALPINE      230.0 - 6ICI         230.0
 OPEN BUS 314272                                                /*6ALPINE      230.0
 OPEN BUS 314308                                                /*6ICI         230.0
 SET POSTCONTRATING 956 BRANCH FROM BUS 314271 TO BUS 314281 CKT 1 /*6ALLIED      230.0 - 6BURDET      230.0
 SET PRECONTRATING 876 BRANCH FROM BUS 314271 TO BUS 314281 CKT 1 /*6ALLIED      230.0 - 6BURDET      230.0
END
CONTINGENCY 'DVP_P1-2: LN 563_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P4-2: H2T557_SRT-S'
 OPEN BRANCH FROM BUS 314218 TO BUS 314908 CKT 2                /*6ELMONT      230.0 - 8ELMONT      500.0
 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1                /*8CHCKAHM     500.0 - 8ELMONT      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 4149 BRANCH FROM BUS 314908 TO BUS 314910 CKT 1 /*8ELMONT      500.0 - 8CUNINGHAM   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 3221 BRANCH FROM BUS 314908 TO BUS 314910 CKT 1 /*8ELMONT      500.0 - 8CUNINGHAM   500.0
END
314131 to 314175 ckt 1
314132 to 314163 ckt 1
314214 to 314258 ckt 1
314214 to 314903 ckt 1
314286 to 314284 ckt 1
314286 to 314214 ckt 1
314286 to 314309 ckt 1
314175 to 314132 ckt 1
314163 to 314137 ckt 1
314309 to 314338 ckt 1
314182 to 314183 ckt 1
314139 to 944490 ckt 1
314183 to 314190 ckt 1
314190 to 970736 ckt 1
944490 to 313810 ckt 1
957190 to 314131 ckt 1
970736 to 314139 ckt 1

Winter Peak Analysis

The New Service Request AG2-646 was evaluated as a 200.0 MW (200.0 MW Capacity) injection in the Dominion area.

AG2-646 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 200.0 MW (200.0 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

(No impacts were found for this analysis)

Light Load Analysis

The New Service Request AG2-646 was evaluated as a 200.0 MW injection and 200.0 MW withdrawal in the Dominion area.

AG2-646 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 200.0 MW (200.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2DVP
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer
DVP_P4-2: H2T557_SRT-L
BreakerAC122.76 %1212.0C1487.8346.85

Details for 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-L


Base Case Flowgate

Area:DVP
Facility Description:
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer
Contingency Name:
DVP_P4-2: H2T557_SRT-L
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:122.76 %
Rating:1212.0 MVA
Rating Type:C
MVA to Mitigate:1487.83
MW Contribution:46.85
Bus #Bus NameTypeMW Contribution
3142416OLDCHRC
Solar/Wind Harmer
2.939
3142416OLDCHRC
Solar/Wind Harmer
2.247
3142416OLDCHRC
Solar/Wind Harmer
0.861
3142433PROV 92
Solar/Wind Harmer
2.528
3143316POE
Solar/Wind Harmer
2.196
3138133OCRAN
Solar/Wind Harmer
0.333
3138133OCRAN
Solar/Wind Harmer
0.166
3138283WHITEMARSH
Solar/Wind Harmer
0.029
3141766HARMONY
Solar/Wind Harmer
1.748
3141766HARMONY
Solar/Wind Harmer
0.117
3141783LANCAST
Solar/Wind Harmer
0.33
3141783LANCAST
Solar/Wind Harmer
0.22
3141913WHIT STONE
Solar/Wind Harmer
0.557
3143873LANEXA
Solar/Wind Harmer
0.363
3141873WAN 176
Solar/Wind Harmer
2.268
3141873WAN 176
Solar/Wind Harmer
0.113
3143526WINTERP
Solar/Wind Harmer
3.187
3143526WINTERP
Solar/Wind Harmer
3.187
316033AB2-134 GEN
Solar/Wind Harmer
0
3142543TWELFTH
Solar/Wind Harmer
0.069
316203AE2-005 GEN
Solar/Wind Harmer
0.001
316312AB1-027
Solar/Wind Harmer
-0.126
315671AE2-027_GEN
Solar/Wind Harmer
15.189
315813AE1-149 C
Solar/Wind Harmer
11.197
315697AD1-025 GEN
Solar/Wind Harmer
-0.001
315778AD1-151 GEN
Solar/Wind Harmer
16.098
316083AB2-161 GEN
Solar/Wind Harmer
1.846
315975AC1-164 GENB
Solar/Wind Harmer
0.661
315976AC1-164 GENA
Solar/Wind Harmer
22.332
316169AC1-164_GENC
Solar/Wind Harmer
19.293
3138126ROCKLANDING
Solar/Wind Harmer
0.055
3142946ENON
Solar/Wind Harmer
0.225
3142946ENON
Solar/Wind Harmer
0.067
944631AF1-128 GEN
50/50
133.288
944641AF1-129 GEN
50/50
72.673
961611AG1-000B GEN
Solar/Wind Harmer
7.008
961611AG1-000B GEN
Solar/Wind Harmer
10.182
962971AG1-146 GEN
Solar/Wind Harmer
3.23
962981AG1-147 GEN
Solar/Wind Harmer
7.537
966871AG1-558 GEN
Solar/Wind Harmer
3.356
966871AG1-558 GEN
Solar/Wind Harmer
-0.717
970009AG2-005 GEN
Solar/Wind Harmer
2.128
970129AG2-093 GEN
Solar/Wind Harmer
8.94
970129AG2-093 GEN
Solar/Wind Harmer
12.331
970133AG2-095 GEN
Solar/Wind Harmer
2.313
970293AG2-193 GEN
Solar/Wind Harmer
3.053
970657AG2-426 GEN
Solar/Wind Harmer
4.299
970657AG2-426 GEN
Solar/Wind Harmer
3.061
970659AG2-427 GEN
Solar/Wind Harmer
9.165
970659AG2-427 GEN
Solar/Wind Harmer
5.531
971047AG2-646 GEN
50/50
46.85
971069AG2-661 GEN
Solar/Wind Harmer
10.319
971167AH1-042 GEN
Solar/Wind Harmer
19.668
971281AH1-106 GEN
Solar/Wind Harmer
3.187
971283AH1-107 GEN
Solar/Wind Harmer
3.187
971317AH1-138 GEN
Solar/Wind Harmer
2.179
971645AH1-323 GEN
50/50
35.287
971647AH1-324 GEN
Solar/Wind Harmer
9.184
965281AG1-393 GEN
Solar/Wind Harmer
2.492
971777AH1-397 GEN
Solar/Wind Harmer
2.312
971781AH1-399 GEN
Solar/Wind Harmer
1.413
970365AG2-240 GEN
Solar/Wind Harmer
3.256
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.362
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.913
CBM South 2LTFEXP_CBM-S2->PJM
CBM
11.906
NYPJM->LTFIMP_NY
CLTF
1.373
CPLELTFEXP_CPLE->PJM
CLTF
6.26
TVALTFEXP_TVA->PJM
CLTF
1.277
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.069
MECLTFEXP_MEC->PJM
CLTF
0.296
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.172
LAGNLTFEXP_LAGN->PJM
CLTF
2.467
SIGELTFEXP_SIGE->PJM
CLTF
0.004
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
17.005
CONTINGENCY 'DVP_P4-2: H2T557_SRT-L'
 OPEN BRANCH FROM BUS 314218 TO BUS 314908 CKT 2                /*6ELMONT      230.0 - 8ELMONT      500.0
 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1                /*8CHCKAHM     500.0 - 8ELMONT      500.0
 SET POSTCONTRATING 3300 BRANCH FROM BUS 314908 TO BUS 314910 CKT 1 /*8ELMONT      500.0 - 8CUNINGHAM   500.0
 SET POSTCONTRATING 3300 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 3118 BRANCH FROM BUS 314908 TO BUS 314910 CKT 1 /*8ELMONT      500.0 - 8CUNINGHAM   500.0
 SET PRECONTRATING 3118 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
314218 to 314908 ckt 1

Short Circuit Analysis

Short Circuit analysis is not performed as part of the Phase I System Impact Study. Short Circuit analysis will commence in the Phase II System Impact Study.

Stability Analysis

Stability analysis is not performed as part of the Phase I System Impact Study. Stability analysis will commence in the Phase II System Impact Study.

Reactive Power Analysis

Reactive Power analysis is not performed as part of the Phase I System Impact Study. Reactive Power analysis will commence in the Phase II System Impact Study.

Steady-State Voltage Analysis

Steady State Voltage analysis is not performed as part of the Phase I System Impact Study. Steady State Voltage analysis will commence in the Phase II System Impact Study.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-050Tarboro-Everetts 230kVIn Service
AA1-063ACarolina–Seaboard 115kVIn Service
AA1-067Everetts 34.5kVIn Service
AA1-139Hickory-Shawboro 230kVIn Service
AA2-053Carolina-Jackson 115kVIn Service
AA2-057Hornertown-Whitakers 115kVIn Service
AA2-174Carolina-Jackson 115kVIn Service
AA2-178Mackeys 230kVIn Service
AB1-027Old Church 34.5 KVIn Service
AB1-081Anaconda-Mayo Dunbar 115kVIn Service
AB1-132Thelma 230kVIn Service
AB2-022Elizabeth City 34.5kVIn Service
AB2-024Correctional 34.5kVIn Service
AB2-025Sapony 34.5kVIn Service
AB2-031Brink-Trego 115kVIn Service
AB2-040Brink 115kVIn Service
AB2-043Chase City 115kVIn Service
AB2-059Benson-Dunbar 115kVIn Service
AB2-060Chase City-Lunenburg 115kVIn Service
AB2-077Buggs Island-Chase City 115kVIn Service
AB2-078Buggs Island-Chase City 115kVIn Service
AB2-079Buggs Island-Chase City 115kVIn Service
AB2-099Ahoskie 34.5kVIn Service
AB2-134Hopewell-Surry 230kVIn Service
AB2-161Waverly #2 DP 115kVIn Service
AB2-169Pantago-Five Points 115kVIn Service
AB2-174Emporia-Trego 115kVIn Service
AB2-190Hopewell-Surry 230kVIn Service
AC1-027Pendleton 34.5kVIn Service
AC1-034Heartsease DP - Mayo Dunbar 115kVSuspended
AC1-036Twittys Creek 34.5kVIn Service
AC1-054Kerr Dam–Eatons Ferry 115 kVIn Service
AC1-086Thelma 230kVSuspended
AC1-098Dawson-South Justice 115kVPartially in Service - Under Construction
AC1-099Dawson-South Justice 115kVPartially in Service - Under Construction
AC1-105Halifax-Mt. Laurel 115kVIn Service
AC1-118Westmoreland 34.5kVIn Service
AC1-147Grassfield 34.5kVIn Service
AC1-161Septa 500kVIn Service
AC1-164Chickahominy 230kVPartially in Service - Under Construction
AC1-189Chinquapin-Everetts 230kVUnder Construction
AC1-191Elmont 115kVEngineering & Procurement
AC1-208Cox-Whitakers 115kVUnder Construction
AC2-012Grassfield-Great Bridge 115kVIn Service
AC2-079Ivor-Oak Ridge 115kVSuspended
AC2-137Elko 34.5kVIn Service
AC2-138Northern Neck 34.5kVIn Service
AC2-141Septa 500kVEngineering & Procurement
AD1-022Cashie-Trowbridge 230 kVEngineering & Procurement
AD1-025Hopewell-Surry 230 kVUnder Construction
AD1-033Fentress-Landstown 230 kVIn Service
AD1-041Harmony Village-Shackleford 115 kVIn Service
AD1-056Hornertown-Hathaway 230 kVSuspended
AD1-057Hornertown-Hathaway 230 kVSuspended
AD1-063Harmony Village 34.5 kVIn Service
AD1-074Trowbridge 230 kVEngineering & Procurement
AD1-075Trowbridge 230 kVEngineering & Procurement
AD1-076Trowbridge 230 kVEngineering & Procurement
AD1-082Bakers Pond-Ivor 115kVIn Service
AD1-087Clover-Sedge Hill 230 kVIn Service
AD1-088Briery-Clover 230 kVSuspended
AD1-144Kings Fork 34.5 kVIn Service
AD1-151Hopewell-Surry 230 kVSuspended
AD1-152Clover-Sedge Hill 230 kVIn Service
AD2-030Wan 34.5 kVIn Service
AD2-033Chase City-Lunenburg 115 kVUnder Construction
AD2-073Sanders DP 230 kVIn Service
AD2-074Garner DP-Lancaster 115 kVEngineering & Procurement
AD2-085Myrtle-Windsor DP 115kVEngineering & Procurement
AD2-160Hickory-Moyock 230kVIn Service
AD2-202Clover-Sedge Hill 230kVIn Service
AE1-072Shawboro-Sligo 230 kVUnder Construction
AE1-074Winterpock 34.5 kVUnder Construction
AE1-103Holland-Union Camp 115 kVUnder Construction
AE1-148Kerr Dam-Ridge Rd 115 kVActive
AE1-149Disputanta-Poe 115 kVSuspended
AE1-155Garner-Northern Neck 115 kVIn Service
AE1-162Smithfield 34.5 kVIn Service
AE1-173Carson-Suffolk 500 kVUnder Construction
AE1-175Light Foot 34.5 kVIn Service
AE1-190Harmony Village-Shackleford 115 kVPartially in Service - Under Construction
AE1-191Harmony Village-Shackleford 115 kVPartially in Service - Under Construction
AE2-005Harmony Village-Shackleford 115 kVUnder Construction
AE2-027Harrowgate-Locks 115kVUnder Construction
AE2-033Clubhouse-Sapony 230 kVSuspended
AE2-034Mackeys 230 kVPartially in Service - Under Construction
AE2-041Harmony Village 230 kVEngineering & Procurement
AE2-051Carson-Septa 500 kVEngineering & Procurement
AE2-094Carson-Rogers Road 500 kVEngineering & Procurement
AE2-104Suffolk 115 kVSuspended
AE2-212Harrowgate 34 kVEngineering & Procurement
AE2-253Hickory-Moyock 230 kVIn Service
AE2-346Ahoskie 34.5 kVIn Service
AF1-014Harmony Village-Shackleford 115 kVUnder Construction
AF1-017Myrtle-Windsor 115 kVEngineering & Procurement
AF1-018Harmony Village 230 kVEngineering & Procurement
AF1-032Suffolk 34.5 kVIn Service
AF1-042Garner DP-Lancaster 115 kVEngineering & Procurement
AF1-058Welco 34.5 kVIn Service
AF1-069Carson-Rogers Rd 500 kVEngineering & Procurement
AF1-114Oak Grove-Dahlgren 230 kVEngineering & Procurement
AF1-123Harper 230 kVActive
AF1-124Harper 230 kVActive
AF1-125Harper 230 kVActive
AF1-128Chesterfield 230 kVActive
AF1-129Chesterfield 230 kVEngineering & Procurement
AF1-291Tyler 34.5 kVEngineering & Procurement
AF1-292Fields 34.5kVEngineering & Procurement
AF2-013Arnold's Corner-Dahlgren 230 kVEngineering & Procurement
AF2-042Clover-Rawlings 500 kVActive
AF2-043Suffolk 34.5 kVIn Service
AF2-046Tunis-Mapleton 115 kVActive
AF2-054Wan 34.5 kVIn Service
AF2-077White Marsh 34.5 kVIn Service
AF2-080Chinquapin-Everetts 230 kVActive
AF2-081Moyock 230 kVActive
AF2-091Oak Grove-Dahlgren 230 kVEngineering & Procurement
AF2-110Suffolk 115 kVSuspended
AF2-120Garner-Northern Neck 115 kVActive
AF2-222Madisonville DP-Twitty's Creek 115 kVActive
AF2-297Sedge Hill 115 kVActive
AF2-299Fields 34.5 kVActive
AG1-007Tar River 12.5 kVEngineering & Procurement
AG1-008Tunis-Mapleton 115 kVActive
AG1-037Ahoskie 34.5 kVEngineering & Procurement
AG1-038Garner DP-Lancaster 115 kVEngineering & Procurement
AG1-082Ahoskie 34.5 kVActive
AG1-098Briery-Clover 230 kVActive
AG1-105Mount Laurel-Barnes Junction 115 kVActive
AG1-106Thelma 230 kVActive
AG1-135Garner-Lancaster 115 kVActive
AG1-145Lightfoot 34.5 kVIn Service
AG1-146Garner DP-Lancaster 115 kVActive
AG1-147Garner DP-Lancaster 115 kVActive
AG1-210Northern Neck 34.5 kVEngineering & Procurement
AG1-282Dunnsville 34.5 kVEngineering & Procurement
AG1-285Chase City-Central 115 kVActive
AG1-342Dryburg 115 kVActive
AG1-393Sapony 34.5 kVActive
AG1-394Boykins 34.5 kVActive
AG1-532Fields 34.5 kVEngineering & Procurement
AG1-536Garner-Northern Neck 115 kVActive
AG1-551Parmele 34.5 kVActive
AG1-552Carolina 34.5 kVActive
AG1-558Buckner 34.5 kVEngineering & Procurement
AG2-005Garner DP-Lancaster 115 kVActive
AG2-010Peninsula-Whealton 115 kVActive
AG2-068Heritage - Wake 500 kVActive
AG2-069Heritage - Wake 500 kVActive
AG2-077Clover-Rawlings 500 kVActive
AG2-093Colonial Trail-Hopewell 230 kVActive
AG2-095Hopewell 34.5 kV (Circuit 313)Active
AG2-120Everetts 34.5 kVActive
AG2-124Shackleford-Harmony 115 kVActive
AG2-171Lunenburg-Nutbush 115 kVActive
AG2-193Turner 34.5 kVActive
AG2-213Gary D.P Tap - Gary D.P 115 kVActive
AG2-215Garner DP-Lancaster 115 kVActive
AG2-240Old Church 34.5 kVActive
AG2-262Dryburg 115 kVActive
AG2-366Garner Delivery Point - Lancaster 115 kVActive
AG2-369Heritage - Wake 500 kVActive
AG2-382Cashie 230 kVActive
AG2-384Chesterfield 230 kVActive
AG2-426Wakefield - Waverly 115 kVActive
AG2-427Waverly 115 kVActive
AG2-428Wakefield 115 kVActive
AG2-436Carson - Rogers Road 500 kVActive
AG2-440Twittys Creek - Madisonville 115 kVActive
AG2-441Twittys Creek - Madisonville 115 kVActive
AG2-442Twittys Creek - Madisonville 115 kVActive
AG2-469Westmoreland – Oak Grove 230 kVActive
AG2-522Five Forks DP 115 kVActive
AG2-570Heritage - Wake 500 kVActive
AG2-571Heritage - Wake 500 kVActive
AG2-581Rawlings-Clover 500 kVActive
AG2-659Kerr Dam – Hawtree 115 kVActive
AG2-661Hopewell - Colonial Trail 230 kVActive
AH1-033Sligo 34.5 kVActive
AH1-035Plymouth 34.5 kVActive
AH1-040Mackeys - Creswell 115 kVActive
AH1-042Providence Forge-Turner 115kVActive
AH1-065Hopewell 34.5kVActive
AH1-066Hopewell 34.5kVActive
AH1-071Midlothian 34.5 kVActive
AH1-106Winterpock 34.5kVActive
AH1-107Winterpock 34.5kVActive
AH1-108Spruance NUG 230 kVActive
AH1-138Penniman 34.5 kVActive
AH1-157Penniman - Waller 230 kVActive
AH1-215Central VA-Twitty 115 kVActive
AH1-216Smithfield-Surry 230 kVActive
AH1-271Cashie 230 kVActive
AH1-311Heartsease DP - Mayo Dunbar 115kVActive
AH1-323Elmont 230 kVActive
AH1-324Colonial Trail – Surry 230 kVActive
AH1-377Clover- Farmville 230kVActive
AH1-396Gary 24.94 kVActive
AH1-397Shacklesford 34.5 kVActive
AH1-399North Doswell 12.5 kVActive
AH1-408Freeman DP – Lawrenceville 115 kVActive
AH1-528Rawlings - Unity 500 kVActive
AH1-637Oak Grove 34.5 kVActive
AH1-677Rogers Road 500 kVActive
AH1-678Heritage 500 kVActive
AH1-716Surry-Skiffes Creek 500kVActive
AH1-717Surry 230kVActive
V4-068Murphy's 34.5kVIn Service
Y1-086Morgans CornerIn Service
Z1-036WinFall-Chowan 230kVIn Service
Z2-027Pasquotank 34.5kVIn Service
Z2-044Whitakers 34.5kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with potential Affected System impacts. PJM initiates coordination with each Affected System Operator by providing a list of New Service Requests in the Cycle with potential impacts to their respective system. If the Affected System Operator indicates an Affected System Study is required, PJM will notify the Project Developer or Eligible Customer of the need for an Affected System Study. See below if any Affected System Operator requires a study for this project:

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

Based on the Phase I analysis results, this project may have a cost responsibility for the following System Reinforcements:

AG2-646 System Reinforcements:
TORTEP IDTitleAllocated Cost ($USD)
Dominion(Pending) / TC2-PH1-DOM-0050Wreck and rebuild 13.78 miles of 230 kV Line 287 between Chesterfield and Chickahominy with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.$43,339,413
Dominionn6551 / dom-159Wreck and rebuild 7.32 miles of 230 kV Line 208 between Chesterfield and Ironbridge with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.$15,936,381
Dominion(Pending) / dom-164Wreck and rebuild 7.08 miles of 230 kV Line 208 between Ironbridge and Southwest with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.$15,413,876
Dominionn7643 / dom-480Add a 2nd new 224 MVA 115/230 kV Transformer at Chesterfield substation between Bus A and 115 kV station.$9,306,704
Dominionn9261.0 / TC1-PH2-DOM-060Replace Existing Chickahominy XFRM 1 with 3-480 MVA Single Phase XFRM.$6,931,960
Dominionn7576 / dom-281-TC2Rebuild 7.91 miles of 230 kV Line 2083 from Birchwood to Fines with (2) 768.2 ACSS/TW (20/7) ""MAUMEE"" conductor 250 degrees C.$3,706,710
Dominion(Pending) / TC2-PH1-DOM-2090Add a 3rd new 3-480 MVA 230/500 kV Transformer at Elmont substation. Add one (1) 500 kV breaker and one (1) 230 kV breaker as required for the new transformer$3,573,758
Dominionn7575 / dom-286-TC2Rebuild 6.46 mi miles of 2-545.6 ACAR (15/7) 90 MOT 230 kV Line 2083 from Fredericksburg to Fines with (2) 768.2 ACSS/TW (20/7) ""MAUMEE"" conductor @ 250 degrees C.$3,480,988
Dominion(Pending) / TC2-PH1-DOM-0043Wreck and rebuild 3.62 miles of 230 kV Line 2091 between Chickahominy and Elko with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.$2,364,804
Dominion(Pending) / TC2-PH1-DOM-1007Wreck and rebuild 0.87 miles of 230 kV Line 2083 between Fredericksburg to Fines with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor @ 250 Deg. C.$342,916
Grand Total:$104,397,510

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0050
Title
Wreck and rebuild 13.78 miles of 230 kV Line 287 between Chesterfield and Chickahominy with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Description
Wreck and rebuild 13.78 miles of 230 kV Line 287 between Chesterfield and Chickahominy with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Total Cost ($USD)
$52,364,000
Allocated Cost ($USD)
$43,339,413
Time Estimate
42 to 48 Months

Contributor

FacilityContingency
6CHCKAHM-6CHESTF A 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-093
13.1 MW17.2%$9,024,587
AG2-646
62.8 MW82.8%$43,339,413

System Reinforcement: n6551
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n6551 / dom-159
Title
Wreck and rebuild 7.32 miles of 230 kV Line 208 between Chesterfield and Ironbridge with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Description
Wreck and rebuild 7.32 miles of 230 kV Line 208 between Chesterfield and Ironbridge with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Total Cost ($USD)
$27,816,000
Allocated Cost ($USD)
$15,936,381
Time Estimate
36 to 42 Months

Contributor

FacilityContingency
6CHESTF A-6IRON208 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-093
11.2 MW14.0%$3,904,807
AG2-428
8.3 MW10.4%$2,880,858
AG2-646
45.7 MW57.3%$15,936,381
AH1-042
7.4 MW9.2%$2,563,357
AH1-717
7.3 MW9.1%$2,530,597

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / dom-164
Title
Wreck and rebuild 7.08 miles of 230 kV Line 208 between Ironbridge and Southwest with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Description
Wreck and rebuild 7.08 miles of 230 kV Line 208 between Ironbridge and Southwest with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Total Cost ($USD)
$26,904,000
Allocated Cost ($USD)
$15,413,876
Time Estimate
36 to 42 Months

Contributor

FacilityContingency
6IRON208-6SOUWEST 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-093
11.2 MW14.0%$3,776,781
AG2-428
8.3 MW10.4%$2,786,404
AG2-646
45.7 MW57.3%$15,413,876
AH1-042
7.4 MW9.2%$2,479,313
AH1-717
7.3 MW9.1%$2,447,626

System Reinforcement: n7643
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n7643 / dom-480
Title
Add a 2nd new 224 MVA 115/230 kV Transformer at Chesterfield substation between Bus A and 115 kV station.
Description
Add a 2nd new 224 MVA 115/230 kV Transformer at Chesterfield substation between Bus A and 115 kV station. Expand 230 kV station to add a new rung and two breakers for XFRM Connection. Connect 115 kV Bus 1 and Bus 2 and add two breakers.
Total Cost ($USD)
$11,000,000
Allocated Cost ($USD)
$9,306,704
Time Estimate
42 to 48 Months

Contributor

FacilityContingency
3CHESTFLD-6CHESTF A 115.0/230.0 kV Ckt 1 transformer(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-093
6.1 MW15.4%$1,693,296
AG2-646
33.3 MW84.6%$9,306,704

System Reinforcement: n9261.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9261.0 / TC1-PH2-DOM-060
Title
Replace Existing Chickahominy XFRM 1 with 3-480 MVA Single Phase XFRM.
Description
Replace Existing Chickahominy XFRM 1 with 3-480 MVA Single Phase XFRM.
Total Cost ($USD)
$40,000,000
Allocated Cost ($USD)
$6,931,960
Time Estimate
42 to 48 Months

Contributor

FacilityContingency
6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-010
11.4 MW5.5%$2,188,067
AG2-428
16.9 MW8.2%$3,263,616
AG2-436
29.9 MW14.4%$5,763,027
AG2-570
22.2 MW10.7%$4,267,154
AG2-571
2.8 MW1.4%$540,085
AG2-646
36.0 MW17.3%$6,931,960
AH1-040
11.2 MW5.4%$2,149,366
AH1-042
22.2 MW10.7%$4,270,813
AH1-157
17.0 MW8.2%$3,266,697
AH1-216
9.6 MW4.6%$1,857,469
AH1-528
17.4 MW8.4%$3,354,305
AH1-717
11.2 MW5.4%$2,147,440

System Reinforcement: n7576
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n7576 / dom-281-TC2
Title
Rebuild 7.91 miles of 230 kV Line 2083 from Birchwood to Fines with (2) 768.2 ACSS/TW (20/7) ""MAUMEE"" conductor 250 degrees C.
Description
Rebuild 7.91 miles of 230 kV Line 2083 from Birchwood to Fines with (2) 768.2 ACSS/TW (20/7) ""MAUMEE"" conductor 250 degrees C.
Total Cost ($USD)
$35,735,843
Allocated Cost ($USD)
$3,706,710
Time Estimate
43 to 44 Months

Contributor

FacilityContingency
6BIRCHWD-6FINES 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-005
1.6 MW1.5%$540,761
AG2-215
7.2 MW6.7%$2,376,443
AG2-366
9.1 MW8.5%$3,020,931
AG2-469
26.8 MW24.8%$8,868,884
AG2-646
11.2 MW10.4%$3,706,710
AH1-042
11.7 MW10.8%$3,876,834
AH1-157
7.5 MW7.0%$2,486,776
AH1-716
32.9 MW30.4%$10,858,503

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2090
Title
Add a 3rd new 3-480 MVA 230/500 kV Transformer at Elmont substation. Add one (1) 500 kV breaker and one (1) 230 kV breaker as required for the new transformer
Description
Add a 3rd new 3-480 MVA 230/500 kV Transformer at Elmont substation. Add one (1) 500 kV breaker and one (1) 230 kV breaker as required for the new transformer
Total Cost ($USD)
$40,000,000
Allocated Cost ($USD)
$3,573,758
Time Estimate
42 to 48 Months

Contributor

FacilityContingency
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-382
7.8 MW1.5%$595,372
AG2-427
14.9 MW2.9%$1,140,094
AG2-428
45.2 MW8.6%$3,450,641
AG2-436
86.0 MW16.4%$6,557,254
AG2-570
46.5 MW8.9%$3,545,687
AG2-571
8.0 MW1.5%$613,832
AG2-581
14.7 MW2.8%$1,120,642
AG2-646
46.9 MW8.9%$3,573,758
AH1-040
28.4 MW5.4%$2,167,139
AH1-042
41.6 MW7.9%$3,175,648
AH1-216
23.7 MW4.5%$1,805,263
AH1-271
4.5 MW0.9%$340,213
AH1-323
58.7 MW11.2%$4,475,550
AH1-324
12.7 MW2.4%$969,377
AH1-408
12.0 MW2.3%$917,659
AH1-528
45.4 MW8.7%$3,461,778
AH1-717
27.4 MW5.2%$2,090,095

System Reinforcement: n7575
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n7575 / dom-286-TC2
Title
Rebuild 6.46 mi miles of 2-545.6 ACAR (15/7) 90 MOT 230 kV Line 2083 from Fredericksburg to Fines with (2) 768.2 ACSS/TW (20/7) ""MAUMEE"" conductor @ 250 degrees C.
Description
Rebuild 6.46 mi miles of 2-545.6 ACAR (15/7) 90 MOT 230 kV Line 2083 from Fredericksburg to Fines with (2) 768.2 ACSS/TW (20/7) ""MAUMEE"" conductor @ 250 degrees C.
Total Cost ($USD)
$33,559,690
Allocated Cost ($USD)
$3,480,988
Time Estimate
43 to 44 Months

Contributor

FacilityContingency
6FREDBRG-6FINES 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-005
1.6 MW1.5%$507,832
AG2-215
7.2 MW6.7%$2,231,729
AG2-366
9.1 MW8.5%$2,836,970
AG2-469
26.8 MW24.8%$8,328,809
AG2-646
11.2 MW10.4%$3,480,988
AH1-042
11.7 MW10.8%$3,640,752
AH1-157
7.5 MW7.0%$2,335,342
AH1-716
32.9 MW30.4%$10,197,269

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0043
Title
Wreck and rebuild 3.62 miles of 230 kV Line 2091 between Chickahominy and Elko with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Description
Wreck and rebuild 3.62 miles of 230 kV Line 2091 between Chickahominy and Elko with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Total Cost ($USD)
$13,756,000
Allocated Cost ($USD)
$2,364,804
Time Estimate
36 to 42 Months

Contributor

FacilityContingency
6CHCKAHM-6ELKO 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-010
7.6 MW7.2%$990,601
AG2-646
18.1 MW17.2%$2,364,804
AH1-042
9.5 MW9.0%$1,235,020
AH1-157
11.6 MW11.0%$1,518,347
AH1-716
58.6 MW55.6%$7,647,227

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-1007
Title
Wreck and rebuild 0.87 miles of 230 kV Line 2083 between Fredericksburg to Fines with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor @ 250 Deg. C.
Description
Wreck and rebuild 0.87 miles of 230 kV Line 2083 between Fredericksburg to Fines with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor @ 250 Deg. C.
Total Cost ($USD)
$3,306,000
Allocated Cost ($USD)
$342,916
Time Estimate
36 to 42 Months

Contributor

FacilityContingency
6FREDBRG-6FINES 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-005
1.6 MW1.5%$50,027
AG2-215
7.2 MW6.7%$219,850
AG2-366
9.1 MW8.5%$279,473
AG2-469
26.8 MW24.8%$820,480
AG2-646
11.2 MW10.4%$342,916
AH1-042
11.7 MW10.8%$358,654
AH1-157
7.5 MW7.0%$230,057
AH1-716
32.9 MW30.4%$1,004,544

System Reinforcement: b4000.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.357
Title
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Description
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AG2-646 may not presently have cost responsibility for this upgrade, AG2-646 may need this upgrade in-service to be deliverable to the PJM system. If AG2-646 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
6WESTMOR-AG2-469 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
6OAKGROV-AG2-469 TP 230.0 kV Ckt 1 line(Any)
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.355
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.355
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AG2-646 may not presently have cost responsibility for this upgrade, AG2-646 may need this upgrade in-service to be deliverable to the PJM system. If AG2-646 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6OAKGROV-AG2-469 TP 230.0 kV Ckt 1 line(Any)
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
6WESTMOR-AG2-469 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.342
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.342
Title
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Description
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Cost Information
Time Estimate
Jul 13 2029

Contingent

Note: Although AG2-646 may not presently have cost responsibility for this upgrade, AG2-646 may need this upgrade in-service to be deliverable to the PJM system. If AG2-646 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6OAKGROV-AG2-469 TP 230.0 kV Ckt 1 line(Any)
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
6WESTMOR-AG2-469 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.341
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.341
Title
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.
Description
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV substation and extend approximately 0.2 miles of conductor to fly-over the site.
Cost Information
Time Estimate
Jul 13 2029

Contingent

Note: Although AG2-646 may not presently have cost responsibility for this upgrade, AG2-646 may need this upgrade in-service to be deliverable to the PJM system. If AG2-646 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6OAKGROV-AG2-469 TP 230.0 kV Ckt 1 line(Any)
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
6WESTMOR-AG2-469 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.325
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.325
Title
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Description
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Cost Information
Time Estimate
Feb 24 2029

Contingent

Note: Although AG2-646 may not presently have cost responsibility for this upgrade, AG2-646 may need this upgrade in-service to be deliverable to the PJM system. If AG2-646 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6OAKGROV-AG2-469 TP 230.0 kV Ckt 1 line(Any)
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
6WESTMOR-AG2-469 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.326
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.326
Title
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Description
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Cost Information
Time Estimate
Feb 24 2029

Contingent

Note: Although AG2-646 may not presently have cost responsibility for this upgrade, AG2-646 may need this upgrade in-service to be deliverable to the PJM system. If AG2-646 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
6WESTMOR-AG2-469 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
6OAKGROV-AG2-469 TP 230.0 kV Ckt 1 line(Any)
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.327
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.327
Title
Upgrade/install equipment at Ladysmith Substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230 kV strings of breaker and a half scheme.
Description
Upgrade/install equipment at Ladysmith substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230kV strings of breaker and a half scheme.
Cost Information
Time Estimate
Feb 24 2029

Contingent

Note: Although AG2-646 may not presently have cost responsibility for this upgrade, AG2-646 may need this upgrade in-service to be deliverable to the PJM system. If AG2-646 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
6WESTMOR-AG2-469 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
6OAKGROV-AG2-469 TP 230.0 kV Ckt 1 line(Any)
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.344
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.344
Title
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Contingent

Note: Although AG2-646 may not presently have cost responsibility for this upgrade, AG2-646 may need this upgrade in-service to be deliverable to the PJM system. If AG2-646 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
6WESTMOR-AG2-469 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
6OAKGROV-AG2-469 TP 230.0 kV Ckt 1 line(Any)
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.352
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.352
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Cost Information
Time Estimate
Sep 16 2030

Contingent

Note: Although AG2-646 may not presently have cost responsibility for this upgrade, AG2-646 may need this upgrade in-service to be deliverable to the PJM system. If AG2-646 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
6WESTMOR-AG2-469 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
6OAKGROV-AG2-469 TP 230.0 kV Ckt 1 line(Any)
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.351
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.351
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Contingent

Note: Although AG2-646 may not presently have cost responsibility for this upgrade, AG2-646 may need this upgrade in-service to be deliverable to the PJM system. If AG2-646 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6WESTMOR-AG2-469 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AG2-469 TP 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.349
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.349
Title
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Description
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Contingent

Note: Although AG2-646 may not presently have cost responsibility for this upgrade, AG2-646 may need this upgrade in-service to be deliverable to the PJM system. If AG2-646 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
6WESTMOR-AG2-469 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
6OAKGROV-AG2-469 TP 230.0 kV Ckt 1 line(Any)
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.348
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.348
Title
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.
Description
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers. A new redundant breaker ring will be added at Kraken to accommodate the new 500kV line from North Anna to Kraken.
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AG2-646 may not presently have cost responsibility for this upgrade, AG2-646 may need this upgrade in-service to be deliverable to the PJM system. If AG2-646 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
6WESTMOR-AG2-469 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
6OAKGROV-AG2-469 TP 230.0 kV Ckt 1 line(Any)
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.346
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.346
Title
Cut-in 500kV line from Kraken substation into Yeat substation
Description
Cut-in 500kV line from Kraken substation into Yeat substation
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AG2-646 may not presently have cost responsibility for this upgrade, AG2-646 may need this upgrade in-service to be deliverable to the PJM system. If AG2-646 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
6WESTMOR-AG2-469 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
6OAKGROV-AG2-469 TP 230.0 kV Ckt 1 line(Any)
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.345
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.345
Title
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Contingent

Note: Although AG2-646 may not presently have cost responsibility for this upgrade, AG2-646 may need this upgrade in-service to be deliverable to the PJM system. If AG2-646 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
6WESTMOR-AG2-469 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
6OAKGROV-AG2-469 TP 230.0 kV Ckt 1 line(Any)
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.350
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.350
Title
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Description
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Contingent

Note: Although AG2-646 may not presently have cost responsibility for this upgrade, AG2-646 may need this upgrade in-service to be deliverable to the PJM system. If AG2-646 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
6WESTMOR-AG2-469 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AG2-469 TP 230.0 kV Ckt 1 line(Any)
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.356
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.356
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AG2-646 may not presently have cost responsibility for this upgrade, AG2-646 may need this upgrade in-service to be deliverable to the PJM system. If AG2-646 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
6WESTMOR-AG2-469 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
6OAKGROV-AG2-469 TP 230.0 kV Ckt 1 line(Any)
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
          AG2-570 500 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AG2-570, AG2-571
        
          AD2-074 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AG2-005, AG2-215
        
          Cashie 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AG2-382, AH1-271
        

Attachments

AG2-646 One Line Diagram

AG2-646 One Line Diagram.pdf
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.