AG2-665 Phase I Study Report

v1.00 released 2025-10-29 22:14

Corwin - Elk 138 kV

54.0 MW Capacity / 90.0 MW Energy

Introduction

This Phase I System Impact Study Report (PH1) has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, sections 307 and 308 for New Service Requests (projects) in Transition Cycle 2. The Project Developer/Eligible Customer (developer) is Hamden Energy LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is American Electric Power.

Preface

The Phase I System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle executive summary format and (ii) an individual project-level basis. The Phase I System Impact Study Results (for both the executive summary and individual reports) will be publicly available on PJM’s website. Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.3, PJM takes the following actions during the Phase I System Impact Study:
  1. PJM studies each New Service Request on a summer peak, winter peak and light load RTEP base case study. The case year is dependent on the new services cycle under study. PJM will identify the base case year to be used in the study of a specific cycle on its website.
  2. PJM will only perform load flow analysis during the Phase I System Impact Study.
  3. In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with Affected System impacts and provides each Affected System Operator with a list of New Service Request in the Cycle with potential impacts to their respective system.
  4. PJM will create both the short circuit and stability base cases to be used in the Phase II System Impact Study.
  5. The Phase I System Impact Study results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.
The Transmission Owner takes the following actions during the Phase I System Impact Study:
  1. Identify required Interconnection Facilities to accommodate the New Service Request.
  2. Identify required Network Upgrades to mitigate system violations from the Phase I System Impact Study.
  3. Provide planning-level preliminary estimates of Interconnection Facilities and Network Upgrades including scope, cost and elapsed time to complete the work.

Decision Point I Requirements

At the close of Phase I System Impact Study, PJM will initiate Decision Point I (DP1). During DP1, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.A.1. Additional information on these elements is available in PJM Manual 14H sections 4.4, 6, and 7.

Allowable project modifications at Decision Point I are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

General

The Project Developer has proposed an uprate to a planned/existing Solar/Storage facility located in the American Electric Power zone — Jackson County, Ohio. This project is an increase to the developer’s AG2-548 project(s), which will share the same Point of Interconnection. The AG2-665 project is a 90.0 MW uprate (54.0 MW Capacity uprate) to the previous project(s). The total installed facilities will have a capability of 180.0 MW with 108.0 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AG2-665
Project Name:
Corwin - Elk 138 kV
Project Developer Name:
Hamden Energy LLC
State:
Ohio
County:
Jackson
Transmission Owner:
American Electric Power
MFO:
180.0
MWE:
90.0
MWC:
54.0
Battery Storage Specification:
360.0 MWh, 4.0-hr class
Grid Charging:
Yes
Fuel Type:
Solar/Storage
Basecase Study Year:
2028

Physical Interconnection Facility Study

Physical Interconnection Facilities Study is not performed as part of the Phase I System Impact Study. Physical Interconnection Facilities Study will commence in the Phase II System Impact Study.

Point of Interconnection

AG2-665 will interconnect on the American Electric Power transmission system by tapping the Corwin-Elk 138 kV Line.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In the Phase I SIS, the costs shown are subject to change as a result of a facility study performed by the TO during the Phase II or Phase III System Impact Study.

Based on the Phase I SIS results, the AG2-665 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit are also shown below.

Cost Summary
DescriptionCost Allocated to AG2-665Cost Subject to Readiness*
Transmission Owner Interconnection Facilities (TOIF)$0$0
Other Scope$352,000$0
Option To Build Oversight$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$7,417,500$7,417,500
Network Upgrades$0$0
System Reliability Network Upgrades
Steady State Thermal & Voltage (SP & LL)$12,074,648$12,074,648
Transient Stability$0$0
Short Circuit$0$0
Transmission Owner Analysis
SubRegional$0$0
Distribution$0$0
Affected System Reinforcements
AFS - PJM Violatons$0$0
AFS - Non-PJM Violations$0$0
Total$19,844,148$19,492,148

* Contributes to calculation for Readiness Deposit #2 (RD2). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim deliverability study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 309 (Decision Point I) A.1.a.i and PJM Manual 14H, section 6.2, Readiness Deposit #2 (RD2) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point I (DP1), the Project Developer or Eligible Customer is required to submit Readiness Deposit #2, which is calculated as 10% of cost allocation for required Phase I Network Upgrades minus Readiness Deposit #1.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Readiness Deposit #2 Due for Project AG2-665

Readiness Deposit #2 has been calculated for the project based on the Phase I System Impact Study results and is shown in the table below. This Readiness Deposit #2 must be provided at Decision Point I through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit
Project ID10% of cost allocation for Phase I Network UpgradesReadiness Deposit #1 Received (RD1)Readiness Deposit #2 (RD2) for AG2-665 Project due at DP1
ABA - B
AG2-665$1,949,215$360,000$1,589,215

Note: Failure to provide an acceptable form of Readiness Deposit #2 by the end of Decision Point I will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Stand-Alone Network Upgrades
RTEP IDDescriptionTotal Cost ($USD)Allocated Cost ($USD)
(Pending)AEP will construct a new ring bus station, initially populated with 3 breakers$14,835,000 $7,417,500 (See Note 1)
Physical Interconnection
RTEP IDDescriptionTotal Cost ($USD)Allocated Cost ($USD)
(Pending)AEP will procure and install revenue submetering equipment for settlement between the generators behind the Point of Interconnection$352,000 $352,000

Based on the scope of work for the Interconnection Facilities, it is expected to take a range of 24 to 30 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

The schedule for any required Network Impact Reinforcements will be more clearly identified in the Phase II and Phase III System Impact Studies.

Note 1: A Common Use Upgrade is a Network Upgrade that is needed for the interconnection of Generating Facilities or Merchant Transmission Facilities of more than one Project Developer or Eligible Customer and which is the shared responsibility of each Project Developer or Eligible Customer. If multiple Project Developers request to connect to the same interconnection substation, the Transmission Owner will determine the cost to accommodate all the requests at the substation. The cost for the interconnection will be allocated in proportion to the number of required terminations into the substation.

Transmission Owner Analysis

No Transmission Owner impacts identified.

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. AEP interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Meteorological Data Reporting Requirement
The solar generation facility shall provide the Transmission Provider with site-specific meteorological data including:
  • Temperature (degrees Fahrenheit)
  • Atmospheric Pressure (hectopascals)
  • Irradiance
  • Forced outage data
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AG2-665 was evaluated as a 90.0 MW (54.0 MW Capacity) injection in the AEP area.

AG2-665 was evaluated as part of a plant. The plant consists of AG2-548, AG2-665. The total Energy output of the plant was evaluated at its maximum seasonal capability of 180.0 MW (197.26 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AP
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
AP_P2-3_WP-500-DRT10A_SRT-SL
BreakerAC121.47 %3792.0B4606.2610.79
GD2AP
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
AEP_P4_#8975_05KAMMER 765_MM2_SRT-A
BreakerAC121.45 %3792.0B4605.3810.75
GD2AP
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
AP_P2-3_WP-500-DRT7A_SRT-SL
BreakerAC121.43 %3792.0B4604.6810.75
GD2AP
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
AP_P1-2_MP-500-028_SRT-A
SingleAC120.65 %3792.0B4574.966.45
GD2AP
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
AP_P1-3_MP-765-502T_SRT-A
SingleAC120.64 %3792.0B4574.636.45
GD2AP
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
AEP_P4_#8975_05KAMMER 765_MM2_SRT-A
BreakerAC139.97 %3792.0B5307.7910.51
GD2AP
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
AP_P2-3_WP-500-DRT7A_SRT-SL
BreakerAC139.96 %3792.0B5307.110.51
GD2AP
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
AP_P2-3_WP-500-DRT10A_SRT-SL
BreakerAC139.86 %3792.0B5303.4310.59
GD2AP
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
AP_P1-3_MP-765-502T_SRT-A
SingleAC139.36 %3792.0B5284.616.3
GD2AP
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
AP_P1-2_MP-500-028_SRT-A
SingleAC139.32 %3792.0B5282.916.3
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P2-3_MP-500-024_SRT-A
BreakerAC132.75 %3729.0B4950.2711.52
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P2-3_MP-500-025_SRT-A
BreakerAC131.94 %3729.0B4919.9311.51
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P2-3_MP-500-014_SRT-A
BreakerAC131.63 %3729.0B4908.4711.51
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P2-3_MP-500-015_SRT-A
BreakerAC131.63 %3729.0B4908.4711.51
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P1-2_MP-500-007A_SRT-A
SingleAC130.62 %3729.0B4870.986.9
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P2-3_MP-500-012_SRT-A
BreakerAC130.23 %3729.0B4856.2611.59
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P1-2_MP-500-008A_SRT-SL
SingleAC124.1 %3729.0B4627.66.64
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AP_P1-3_MP-765-501T_SRT-A
SingleAC121.06 %3393.4B4107.975.76
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AP_P2-3_MP-500-020_SRT-SL
BreakerAC117.02 %3610.0B4224.559.68
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AP_P2-3_MP-500-021_SRT-SL
BreakerAC116.77 %3610.0B4215.439.63
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AEP_P4_#37_05MOUNTN 765_B1_SRT-A
BreakerAC116.68 %3610.0B4211.989.6
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AEP_P4_#2942_05KAMMER 765_PP_SRT-A
BreakerAC116.36 %3610.0B4200.439.61
GD2AEP
05HARRISON-05OBETZ 138.0 kV Ckt 1 line
AEP_P4_#9672_05HARRISON 138_2W_SRT-A
BreakerAC100.01 %223.0B223.035.27
GD2AEP
05HARRISON-05ZUBER 138.0 kV Ckt 1 line
AEP_P4_#9679_05HARRISON 138_2E_SRT-A
BreakerAC129.23 %180.0B232.626.38
GD2AEP
05HARRISON-05ZUBER 138.0 kV Ckt 1 line
AEP_P7-1_#10921___SRT-A
TowerAC116.96 %180.0B210.536.18
GD2AEP
05HARRISON-05ZUBER 138.0 kV Ckt 1 line
AEP_P4_#9737_05MARION RD 138_4_SRT-A
BreakerAC116.0 %180.0B208.86.17
GD2AEP
05HARRISON-05ZUBER 138.0 kV Ckt 1 line
AEP_P4_#9738_05MARION RD 138_5_SRT-A
BreakerAC115.73 %180.0B208.326.17
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P2-3_MP-500-024_SRT-A
BreakerAC134.01 %3792.0B5081.5211.52
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P2-3_MP-500-025_SRT-A
BreakerAC133.21 %3792.0B5051.211.51
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P2-3_MP-500-015_SRT-A
BreakerAC132.9 %3792.0B5039.6911.51
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P2-3_MP-500-014_SRT-A
BreakerAC132.9 %3792.0B5039.6911.51
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P1-2_MP-500-007A_SRT-A
SingleAC131.92 %3792.0B5002.286.9
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P2-3_MP-500-012_SRT-A
BreakerAC131.49 %3792.0B4985.9811.59
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P1-2_MP-500-008A_SRT-SL
SingleAC125.38 %3792.0B4754.336.64
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P4_#8980_05KAMMER 765_QQ2_SRT-A
BreakerAC116.66 %5523.0B6443.1115.32
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P1-2_#17217_SRT-A
SingleAC115.67 %5523.0B6388.329.19
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P4_#7445_05MARYSV 765_B_SRT-A
BreakerAC113.05 %5523.0B6243.5311.74
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P4_#17219_05GUERNSEY 765_A_SRT-A
BreakerAC112.12 %5523.0B6192.1715.46
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Base Case
SingleAC108.86 %4558.0A4961.857.21
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A
BreakerAC108.47 %5523.0B5991.0214.08
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P1-2_#7422_16_SRT-A
SingleAC106.56 %5523.0B5885.348.45
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P7-1_#10944___SRT-A
TowerAC106.16 %5523.0B5863.4713.74
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P7-1_#10856___SRT-A
TowerAC102.19 %5523.0B5644.1413.87
GD2AEP
AG2-548 TP-05CORWIN 138.0 kV Ckt 1 line
AEP_P4_#9758_05LEMASTER 138_A1_SRT-A
BreakerAC118.99 %255.0B303.4290.0
GD2AEP
AG2-548 TP-05CORWIN 138.0 kV Ckt 1 line
AEP_P4_#11182_05LEMASTER 138_A_SRT-A
BreakerAC118.99 %255.0B303.4290.0

Details for 01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line l/o AP_P2-3_WP-500-DRT10A_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-500-DRT10A_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.47 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4606.26
MW Contribution:10.79
Bus #Bus NameTypeMW Contribution
23559101PLEAS2
50/50
11.904
23684101S70BUS1
50/50
0.301
23562301OGROV1
50/50
2.301
24721705FLATG2
Adder
24.275
962761AG1-125 GEN
Solar/Wind Harmer
36.289
970149AG2-104 GEN
Solar/Wind Harmer
44.817
970155AG2-107 GEN
Solar/Wind Harmer
15.824
270510AE1-227 GEN1
Solar/Wind Harmer
2.641
960001AF2-291 GEN
Solar/Wind Harmer
3.22
970947AG2-589 GEN
Solar/Wind Harmer
2.097
270331AC1-082 GEN3
Solar/Wind Harmer
0.474
270349AD2-093_GEN
Solar/Wind Harmer
3.8
927014AC1-188 GEN
Solar/Wind Harmer
1.647
270263AC1-001 GEN
Solar/Wind Harmer
1.075
270159DARBY CT4
Adder
8.977
24686105CER G3
Adder
8.446
24686505CER G6
Adder
8.435
253343AC1-166 GEN
Solar/Wind Harmer
1.099
253325AC1-069 GEN
Solar/Wind Harmer
1.06
24723205RIVRG3
Adder
18.943
24318905MLG2
50/50
4.888
270471AD2-092_GEN
Solar/Wind Harmer
3.8
946101AF1-275 GEN
Solar/Wind Harmer
1.564
970879AG2-548 GEN
Solar/Wind Harmer
6.355
971073AG2-665 GEN
Solar/Wind Harmer
6.355
971073AG2-665 GEN
Solar/Wind Harmer
4.434
24685805CER G1
Adder
8.39
24685905CER G2
Adder
8.39
942861AE2-305 GEN
Solar/Wind Harmer
7.89
270518AE2-148 GEN
Solar/Wind Harmer
12.226
24723005RIVRG1
Adder
18.943
24723105RIVRG2
Adder
18.943
970077AG2-063 GEN
Solar/Wind Harmer
5.44
972269AH1-719 GEN
Adder
2.314
962581AG1-107 GEN
Solar/Wind Harmer
4.971
961491AF2-440 GEN
Solar/Wind Harmer
2.066
253394AE2-221_GEN
Solar/Wind Harmer
4.473
253398AE2-221_GEN2
Solar/Wind Harmer
4.473
253317AC1-085 GEN4
Solar/Wind Harmer
8.238
25326109MON D
Adder
1.293
964601AG1-323 GEN
Solar/Wind Harmer
3.12
964601AG1-323 GEN
Solar/Wind Harmer
1.451
253370AE2-315 SEC1
Adder
1.967
270224U2-072_GEN2
Solar/Wind Harmer
1.941
270227U2-072_GEN3
Solar/Wind Harmer
1.941
270228U2-072_GEN4
Solar/Wind Harmer
1.941
270231U2-072_GEN5
Solar/Wind Harmer
1.941
25322209TAIT E
Adder
9.568
25322209TAIT E
Adder
9.353
270186AC1-089 GEN
Solar/Wind Harmer
5.991
972159AH1-661 GEN
Adder
0.977
938701AE1-092 GEN
Solar/Wind Harmer
20.234
25183208HLCRTG
Solar/Wind Harmer
5.927
252509AD1-136 GEN
Solar/Wind Harmer
0.25
252519AF1-045_GEN
Solar/Wind Harmer
5.924
252516AE2-318_GEN
Solar/Wind Harmer
4.519
253378AE2-206_GEN
Solar/Wind Harmer
3.5
276820AF1-078_GEN
Solar/Wind Harmer
1.555
25194408D.CRK1
Adder
7.352
25194508D.CRK3
Adder
1.375
25326509SID D
Adder
1.274
970239AG2-162 GEN
Solar/Wind Harmer
10.505
24728805RICHG1
Adder
3.601
24728905RICHG2
Adder
3.601
970883AG2-550 GEN
Solar/Wind Harmer
9.522
970885AG2-551 GEN
Solar/Wind Harmer
2.214
270383AD1-128 GEN
Solar/Wind Harmer
5.808
24379505HDWTR1G C
Solar/Wind Harmer
7.516
270209AC1-174_GEN
Solar/Wind Harmer
5.304
926881AC1-175 GEN
Solar/Wind Harmer
5.304
944541AF1-119 GEN
Solar/Wind Harmer
3.977
960971AF2-388 GEN
Solar/Wind Harmer
10.38
247621Y3-024
Adder
0.229
270201AC2-176 GEN
Solar/Wind Harmer
4.876
964611AG1-324 GEN
Solar/Wind Harmer
1.118
964611AG1-324 GEN
Solar/Wind Harmer
0.496
970825AG2-519 GEN
Solar/Wind Harmer
9.992
960441AF2-335 GEN
Solar/Wind Harmer
9.465
247620Y3-023
Adder
0.427
274770LINCOLN ;1U
Adder
7.771
274771LINCOLN ;2U
Adder
7.771
274808UNIV PK N;4U
Adder
4.582
274803UNIV PARK;6U
Adder
5.35
972259AH1-714 GEN
Adder
17.495
23585401KL_K28_T16
Solar/Wind Helper
1.401
238120AE2-309 GEN
Solar/Wind Helper
0.474
238175AF1-290_GEN
Solar/Wind Helper
0.131
238169AE2-226 GEN1
Solar/Wind Helper
0.604
238170AE2-226 GEN2
Solar/Wind Helper
0.604
235020AA1-095 C
Solar/Wind Helper
0.045
23777901MDS_W4-102
Solar/Wind Helper
0.152
235063AE1-101 C2
Solar/Wind Helper
1.439
237002AB1-128_GEN
Solar/Wind Helper
0.384
237001AB1-127_GEN
Solar/Wind Helper
0.383
237034AC2-136 C
Solar/Wind Helper
0.196
23777801MSM_W1-116
Solar/Wind Helper
0.099
237025AB1-124 C
Solar/Wind Helper
0.143
237006AB1-125 GEN
Solar/Wind Helper
0.107
23559001PLEAS1
50/50
11.904
23684201S70BUS2
50/50
0.306
23562401OGROV2
50/50
2.286
24318805MLG1
50/50
6.661
24721905FLATG4
Adder
24.275
970153AG2-106 GEN
Solar/Wind Harmer
15.824
270512AE1-227 GEN2
Solar/Wind Harmer
2.242
971191AH1-055 GEN
Solar/Wind Harmer
22.996
957541AF2-048 GEN
Solar/Wind Harmer
1.643
961921AG1-034 GEN
Solar/Wind Harmer
13.176
270291AC1-194 GEN
Solar/Wind Harmer
10.919
960801AF2-371 GEN
Solar/Wind Harmer
2.612
964871AG1-351 GEN
Solar/Wind Harmer
1.804
270273AD2-016 GEN
Solar/Wind Harmer
2.741
972173AH1-669 GEN
Solar/Wind Harmer
5.136
241955AC1-078 GEN
Solar/Wind Harmer
7.631
942051AE2-217 GEN
Solar/Wind Harmer
18.255
24686205CER G4
Adder
8.402
24686405CER G5
Adder
8.368
241974AD2-163_GEN2
Solar/Wind Harmer
2.012
253338AC1-165 GEN
Solar/Wind Harmer
1.099
253333AC1-068 GEN
Solar/Wind Harmer
1.06
970605AG2-385 GEN
Solar/Wind Harmer
5.44
253415AE1-040 GEN
Solar/Wind Harmer
1.134
253406AD2-031_GEN
Solar/Wind Harmer
1.265
253316AC1-085 GEN3
Solar/Wind Harmer
8.238
253433AC1-085 GEN1
Solar/Wind Harmer
5.23
946181AF1-283 GEN
Solar/Wind Harmer
12.786
253303V4-073 C
Solar/Wind Harmer
0.114
253370AE2-315 SEC1
Adder
1.967
253371AE2-315 SEC2
Adder
1.861
942871AE2-306 GEN
Solar/Wind Harmer
0.89
270391AF1-285 GEN3
Solar/Wind Harmer
0.457
252510AF1-249 C
Solar/Wind Harmer
0.407
25196608WSDLE5
Adder
8.333
25194608D.CRK4
Adder
1.598
270485AE1-090_GEN
Solar/Wind Harmer
0.587
270222AC2-111 GEN
Solar/Wind Harmer
7.836
25196008MFTGT1
Adder
1.294
970243AG2-164 GEN
Solar/Wind Harmer
24.663
970519AG2-331 GEN
Solar/Wind Harmer
16.569
970699AG2-449 GEN
Solar/Wind Harmer
10.961
972167AH1-666 GEN
Solar/Wind Harmer
7.633
958171AF2-111 GEN
Solar/Wind Harmer
23.849
944531AF1-118 GEN
Solar/Wind Harmer
33.274
270437AC2-090 C
Solar/Wind Harmer
5.307
962031AG1-047 GEN
Solar/Wind Harmer
2.867
957741AF2-068 GEN
Solar/Wind Harmer
14.228
946031AF1-268 GEN
Solar/Wind Harmer
7.867
958821AF2-173 GEN
Solar/Wind Harmer
13.269
270004AE1-209 GEN
Solar/Wind Harmer
5.18
270356AE2-297 GEN
Solar/Wind Harmer
4.32
24728705AND G3
Adder
7.484
24728505AND G1
Adder
3.578
24642205MAYFLWER
Adder
0.588
274772LINCOLN ;3U
Adder
7.771
274752CRETE EC ;2U
Adder
7.583
274753CRETE EC ;3U
Adder
7.583
274724RIVER EC ;11
Adder
16.291
274802UNIV PARK;5U
Adder
5.35
972228AH1-698 GEN2
Adder
3.398
274826FISK ;BP
Adder
10.043
274800UNIV PARK;3U
Adder
5.348
972038AH1-567 GEN2
Adder
0.335
274729ELWOOD EC;1P
Adder
15.046
274730ELWOOD EC;6P
Adder
15.046
316097T157 G90
Solar/Wind Helper
1.335
964991AG1-363 GEN
Solar/Wind Helper
4.295
23750701CROSSCHOOL
Solar/Wind Helper
1.345
238127S14_GEN_2
Solar/Wind Helper
0.75
238118U2-030_1
Solar/Wind Helper
0.309
238148AE2-230_GEN2
Solar/Wind Helper
0.432
237080AD1-060 GEN
Solar/Wind Helper
0.295
237038AE2-054 C
Solar/Wind Helper
0.236
235062AE1-101 C1
Solar/Wind Helper
1.439
23779801AA1-109
Solar/Wind Helper
0.167
962771AG1-126 GEN
Solar/Wind Harmer
36.289
270330AC1-082 GEN2
Solar/Wind Harmer
0.803
270329AC1-082 GEN1
Solar/Wind Harmer
0.473
270054AF2-122 C O1
Solar/Wind Harmer
3.4
270520AE2-214 GEN
Solar/Wind Harmer
6.265
270459AD2-067 GEN
Solar/Wind Harmer
8.652
961821AG1-024 GEN
Solar/Wind Harmer
8.784
970879AG2-548 GEN
Solar/Wind Harmer
4.434
970689AG2-444 GEN
Solar/Wind Harmer
16.764
270432AC2-029 GEN
Solar/Wind Harmer
7.199
270269AC2-059
Solar/Wind Harmer
9.583
972203AH1-686 GEN
Adder
2.36
940611AE2-048 GEN
Solar/Wind Harmer
22.51
941391AE2-136 GEN
Solar/Wind Harmer
11.664
270284AF1-227 GEN1
Solar/Wind Harmer
5.777
270286AF1-227 GEN2
Solar/Wind Harmer
2.137
270287AF1-227 GEN3
Solar/Wind Harmer
2.137
270156DARBY CT1
Adder
9.122
270157DARBY CT2
Adder
9.1
270158DARBY CT3
Adder
8.955
945631AF1-228 GEN
Solar/Wind Harmer
4.774
253383AE2-342_GEN
Solar/Wind Harmer
0.9
241973AD2-163_GEN1
Solar/Wind Harmer
2.012
943861AF1-054 GEN
Solar/Wind Harmer
3.894
943851AF1-053 GEN
Solar/Wind Harmer
1.882
971985AH1-537 GEN
Solar/Wind Harmer
18.016
270340AC2-060 GEN
Solar/Wind Harmer
3.05
241972AD1-140 GEN
Solar/Wind Harmer
4.451
270367AC2-061_GEN
Solar/Wind Harmer
3.138
253372AE2-315 SEC3
Adder
1.861
253372AE2-315 SEC3
Adder
1.861
270578AF1-285 GEN2
Solar/Wind Harmer
0.457
25306009OHH W.
Adder
2.823
253349AC2-067 GEN
Solar/Wind Harmer
4.865
253400AC2-068 GEN
Solar/Wind Harmer
1.956
252524AE2-267 GEN
Solar/Wind Harmer
1.533
25196408WSDLE3
Adder
8.578
25196308WSDLE2
Adder
8.503
25196208WSDLE1
Adder
8.482
25196708WSDLE6
Adder
8.461
25196508WSDLE4
Adder
8.248
270302AB2-170 GEN
Solar/Wind Harmer
8.119
270317AD1-130_GEN
Solar/Wind Harmer
3.113
944031AF1-071 GEN
Solar/Wind Harmer
0.966
25196108MFTGT2
Adder
1.473
25196108MFTGT2
Adder
1.368
971673AH1-337 GEN
Solar/Wind Harmer
4.391
971029AG2-637 GEN
Solar/Wind Harmer
14.309
972163AH1-664 GEN
Solar/Wind Harmer
9.523
972165AH1-665 GEN
Solar/Wind Harmer
7.618
270543AE2-219 C
Solar/Wind Harmer
4.876
24729505KEY G4
Adder
6.165
270240V3-007_GEN2
Solar/Wind Harmer
5.881
958711AF2-162 GEN
Solar/Wind Harmer
0.961
965101AG1-375 GEN
Solar/Wind Harmer
9.494
945581AF1-223 GEN
Solar/Wind Harmer
4.304
961761AG1-017 GEN
Solar/Wind Harmer
0.406
970115AG2-085 GEN
Solar/Wind Harmer
3.786
24477305BRIDGE
Adder
0.323
274775LINCOLN ;6U
Adder
7.771
274776LINCOLN ;7U
Adder
7.771
274777LINCOLN ;8U
Adder
7.771
274814UNIV PK N;0U
Adder
4.642
274807UNIV PK N;3U
Adder
4.632
274805UNIV PK N;1U
Adder
4.612
274811UNIV PK N;7U
Adder
4.602
972037AH1-567 GEN1
Adder
0.168
972227AH1-698 GEN1
Adder
2.393
274827FISK ;RP
Adder
7.117
274687WILL CNTY;4U
Adder
25.585
274687WILL CNTY;4U
Adder
25.585
274731ELWOOD EC;2P
Adder
15.046
274733ELWOOD EC;3P
Adder
15.046
274735ELWOOD EC;4P
Adder
15.046
274728ELWOOD EC;5P
Adder
15.046
238109AE1-109 GEN2
Solar/Wind Helper
0.101
238110AE1-109 GEN3
Solar/Wind Helper
0.101
238126S14_GEN_1
Solar/Wind Helper
0.75
238152AF2-075_GEN
Solar/Wind Helper
0.615
23546401DTGZ2-030
Solar/Wind Helper
0.077
238208AF1-136 C
Solar/Wind Helper
0.191
23750501ELLIOTTS
Solar/Wind Helper
0.607
237085AD2-009_GEN
Solar/Wind Helper
1.43
3138216PACIFIC
Solar/Wind Helper
0.038
316411AF1-147_GEN1
Solar/Wind Helper
0.761
316415AF1-147_GEN2
Solar/Wind Helper
0.761
270024AE2-089 GEN
Solar/Wind Harmer
0.702
971617AH1-308 GEN
Solar/Wind Harmer
0.869
970593AG2-378 GEN
Solar/Wind Harmer
2.015
253432AC1-085 GEN2
Solar/Wind Harmer
0.263
946171AF1-282 GEN
Solar/Wind Harmer
9.835
253370AE2-315 SEC1
Adder
1.967
253371AE2-315 SEC2
Adder
1.861
270223U2-072_GEN1
Solar/Wind Harmer
1.941
270578AF1-285 GEN2
Solar/Wind Harmer
1.187
270391AF1-285 GEN3
Solar/Wind Harmer
1.187
25326309TAIT D
Adder
1.075
960071AF2-298 GEN
Solar/Wind Harmer
4.886
252507AC2-088 GEN
Solar/Wind Harmer
1.752
25194608D.CRK4
Adder
1.598
270462AD2-086
Solar/Wind Harmer
6.754
25196808ZIMRHP
Adder
73.524
25196008MFTGT1
Adder
1.336
970333AG2-219 GEN
Solar/Wind Harmer
30.143
945681AF1-233 GEN
Solar/Wind Harmer
17.979
971995AH1-542 GEN
Solar/Wind Harmer
10.473
247536S-71 GEN
Solar/Wind Harmer
3.848
942081AE2-220 GEN
Solar/Wind Harmer
6.077
270239V3-007_GEN1
Solar/Wind Harmer
1.636
965651AG1-433 GEN
Solar/Wind Harmer
5.19
958861AF2-177 GEN
Solar/Wind Harmer
10.377
945371AF1-202 GEN
Solar/Wind Harmer
6.621
270005AE1-210 C O1
Solar/Wind Harmer
5.18
965031AG1-367 GEN
Solar/Wind Harmer
9.478
970825AG2-519 GEN
Solar/Wind Harmer
2.23
970091AG2-072 GEN
Adder
72.371
24728605AND G2
Adder
3.578
24639705ELKHART HY
Adder
0.142
274773LINCOLN ;4U
Adder
7.771
274774LINCOLN ;5U
Adder
7.771
274751CRETE EC ;1U
Adder
7.583
274754CRETE EC ;4U
Adder
7.583
274723RIVER EC ;12
Adder
16.483
274812UNIV PK N;8U
Adder
4.602
274801UNIV PARK;4U
Adder
5.348
274732ELWOOD EC;7P
Adder
8.785
23751101LEADS_P59
Solar/Wind Helper
1.563
23583801GRNGAP
Solar/Wind Helper
4.994
316095T157 G97
Solar/Wind Helper
1.335
23751201ROTHROCK
Solar/Wind Helper
0.822
238185AF2-356 C
Solar/Wind Helper
2.423
23562501BACKB
Solar/Wind Helper
1.01
235054AD2-180 GEN
Solar/Wind Helper
1.889
238108AE1-109 GEN1
Solar/Wind Helper
0.101
235531U2-073 GEN
Solar/Wind Helper
2.957
238117U2-030
Solar/Wind Helper
0.309
238147AE2-230_GEN1
Solar/Wind Helper
0.431
238149AF1-291A_GEN
Solar/Wind Helper
0.123
237061AD1-155 GEN
Solar/Wind Helper
0.046
238221AF1-254 C O1
Solar/Wind Helper
0.237
235067AD1-061 GEN
Solar/Wind Helper
0.429
237030AB1-096 C
Solar/Wind Helper
0.061
944201AF1-088_MTX
Adder
106.917
957141AF2-008_MTX
Adder
53.458
CBM West 1LTFEXP_CBM-W1->PJM
CBM
126.934
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.919
MECLTFEXP_MEC->PJM
CLTF
14.518
SIGELTFEXP_SIGE->PJM
CLTF
0.468
LAGNLTFEXP_LAGN->PJM
CLTF
14.208
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.03
TVALTFEXP_TVA->PJM
CLTF
7.054
CPLELTFEXP_CPLE->PJM
CLTF
1.268
CBM West 2LTFEXP_CBM-W2->PJM
CBM
105.814
NYPJM->LTFIMP_NY
CLTF
4.499
LGEELTFEXP_LGEE->PJM
CLTF
6.294
WECLTFEXP_WEC->PJM
CLTF
3.447
AG2-052LTFEXP_AG2-052->PJM
LTF
0.215
AH1-155LTFEXP_AH1-155->PJM
LTF
0.322

Details for 01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line l/o AEP_P4_#8975_05KAMMER 765_MM2_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#8975_05KAMMER 765_MM2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.45 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4605.38
MW Contribution:10.75
Bus #Bus NameTypeMW Contribution
24318905MLG2
50/50
4.855
270471AD2-092_GEN
Solar/Wind Harmer
3.785
946101AF1-275 GEN
Solar/Wind Harmer
1.557
970879AG2-548 GEN
Solar/Wind Harmer
6.331
971073AG2-665 GEN
Solar/Wind Harmer
6.331
971073AG2-665 GEN
Solar/Wind Harmer
4.417
24685805CER G1
Adder
8.364
24685905CER G2
Adder
8.364
942861AE2-305 GEN
Solar/Wind Harmer
7.857
270518AE2-148 GEN
Solar/Wind Harmer
12.175
24723005RIVRG1
Adder
18.885
24723105RIVRG2
Adder
18.885
970077AG2-063 GEN
Solar/Wind Harmer
5.418
972269AH1-719 GEN
Adder
2.302
962581AG1-107 GEN
Solar/Wind Harmer
4.952
961491AF2-440 GEN
Solar/Wind Harmer
2.058
253394AE2-221_GEN
Solar/Wind Harmer
4.456
253398AE2-221_GEN2
Solar/Wind Harmer
4.456
253317AC1-085 GEN4
Solar/Wind Harmer
8.207
25326109MON D
Adder
1.288
964601AG1-323 GEN
Solar/Wind Harmer
3.106
964601AG1-323 GEN
Solar/Wind Harmer
1.445
253370AE2-315 SEC1
Adder
1.959
270224U2-072_GEN2
Solar/Wind Harmer
1.932
270227U2-072_GEN3
Solar/Wind Harmer
1.932
270228U2-072_GEN4
Solar/Wind Harmer
1.932
270231U2-072_GEN5
Solar/Wind Harmer
1.932
25322209TAIT E
Adder
9.53
25322209TAIT E
Adder
9.316
270186AC1-089 GEN
Solar/Wind Harmer
5.968
938701AE1-092 GEN
Solar/Wind Harmer
20.142
25183208HLCRTG
Solar/Wind Harmer
5.905
972159AH1-661 GEN
Adder
0.972
252509AD1-136 GEN
Solar/Wind Harmer
0.249
252519AF1-045_GEN
Solar/Wind Harmer
5.902
252516AE2-318_GEN
Solar/Wind Harmer
4.502
253378AE2-206_GEN
Solar/Wind Harmer
3.485
276820AF1-078_GEN
Solar/Wind Harmer
1.548
25194408D.CRK1
Adder
7.324
25194508D.CRK3
Adder
1.369
25326509SID D
Adder
1.268
970239AG2-162 GEN
Solar/Wind Harmer
10.466
24728805RICHG1
Adder
3.587
24728905RICHG2
Adder
3.587
970883AG2-550 GEN
Solar/Wind Harmer
9.484
970885AG2-551 GEN
Solar/Wind Harmer
2.206
270383AD1-128 GEN
Solar/Wind Harmer
5.785
24379505HDWTR1G C
Solar/Wind Harmer
7.487
270209AC1-174_GEN
Solar/Wind Harmer
5.284
926881AC1-175 GEN
Solar/Wind Harmer
5.284
944541AF1-119 GEN
Solar/Wind Harmer
3.962
960971AF2-388 GEN
Solar/Wind Harmer
10.338
247621Y3-024
Adder
0.228
270201AC2-176 GEN
Solar/Wind Harmer
4.857
964611AG1-324 GEN
Solar/Wind Harmer
1.114
964611AG1-324 GEN
Solar/Wind Harmer
0.494
970825AG2-519 GEN
Solar/Wind Harmer
9.953
960441AF2-335 GEN
Solar/Wind Harmer
9.427
247620Y3-023
Adder
0.425
274770LINCOLN ;1U
Adder
7.74
274771LINCOLN ;2U
Adder
7.74
274808UNIV PK N;4U
Adder
4.563
274803UNIV PARK;6U
Adder
5.329
972259AH1-714 GEN
Adder
17.426
23585401KL_K28_T16
Solar/Wind Helper
1.442
238120AE2-309 GEN
Solar/Wind Helper
0.483
238175AF1-290_GEN
Solar/Wind Helper
0.13
238169AE2-226 GEN1
Solar/Wind Helper
0.6
238170AE2-226 GEN2
Solar/Wind Helper
0.6
235020AA1-095 C
Solar/Wind Helper
0.045
23777901MDS_W4-102
Solar/Wind Helper
0.151
235063AE1-101 C2
Solar/Wind Helper
1.433
237002AB1-128_GEN
Solar/Wind Helper
0.382
237001AB1-127_GEN
Solar/Wind Helper
0.381
237034AC2-136 C
Solar/Wind Helper
0.194
23777801MSM_W1-116
Solar/Wind Helper
0.098
237025AB1-124 C
Solar/Wind Helper
0.142
237006AB1-125 GEN
Solar/Wind Helper
0.106
962771AG1-126 GEN
Solar/Wind Harmer
36.157
270330AC1-082 GEN2
Solar/Wind Harmer
0.8
270329AC1-082 GEN1
Solar/Wind Harmer
0.471
270054AF2-122 C O1
Solar/Wind Harmer
3.386
270520AE2-214 GEN
Solar/Wind Harmer
6.239
270459AD2-067 GEN
Solar/Wind Harmer
8.614
961821AG1-024 GEN
Solar/Wind Harmer
8.746
970879AG2-548 GEN
Solar/Wind Harmer
4.417
23559001PLEAS1
50/50
11.891
23684201S70BUS2
50/50
0.305
23562401OGROV2
50/50
2.277
24318805MLG1
50/50
6.637
24721905FLATG4
Adder
24.202
970153AG2-106 GEN
Solar/Wind Harmer
15.766
270512AE1-227 GEN2
Solar/Wind Harmer
2.228
971191AH1-055 GEN
Solar/Wind Harmer
22.913
957541AF2-048 GEN
Solar/Wind Harmer
1.637
961921AG1-034 GEN
Solar/Wind Harmer
13.119
270291AC1-194 GEN
Solar/Wind Harmer
10.875
960801AF2-371 GEN
Solar/Wind Harmer
2.601
964871AG1-351 GEN
Solar/Wind Harmer
1.796
270273AD2-016 GEN
Solar/Wind Harmer
2.73
972173AH1-669 GEN
Solar/Wind Harmer
5.115
241955AC1-078 GEN
Solar/Wind Harmer
7.599
942051AE2-217 GEN
Solar/Wind Harmer
18.179
24686205CER G4
Adder
8.375
24686405CER G5
Adder
8.342
241974AD2-163_GEN2
Solar/Wind Harmer
2.003
253338AC1-165 GEN
Solar/Wind Harmer
1.094
253333AC1-068 GEN
Solar/Wind Harmer
1.056
970605AG2-385 GEN
Solar/Wind Harmer
5.418
253415AE1-040 GEN
Solar/Wind Harmer
1.129
253406AD2-031_GEN
Solar/Wind Harmer
1.261
253316AC1-085 GEN3
Solar/Wind Harmer
8.207
253433AC1-085 GEN1
Solar/Wind Harmer
5.21
946181AF1-283 GEN
Solar/Wind Harmer
12.737
253303V4-073 C
Solar/Wind Harmer
0.113
253370AE2-315 SEC1
Adder
1.959
253371AE2-315 SEC2
Adder
1.853
942871AE2-306 GEN
Solar/Wind Harmer
0.886
270391AF1-285 GEN3
Solar/Wind Harmer
0.455
252510AF1-249 C
Solar/Wind Harmer
0.405
25196608WSDLE5
Adder
8.301
25194608D.CRK4
Adder
1.592
270485AE1-090_GEN
Solar/Wind Harmer
0.584
270222AC2-111 GEN
Solar/Wind Harmer
7.805
25196008MFTGT1
Adder
1.289
970243AG2-164 GEN
Solar/Wind Harmer
24.571
970519AG2-331 GEN
Solar/Wind Harmer
16.508
970699AG2-449 GEN
Solar/Wind Harmer
10.921
972167AH1-666 GEN
Solar/Wind Harmer
7.605
958171AF2-111 GEN
Solar/Wind Harmer
23.761
944531AF1-118 GEN
Solar/Wind Harmer
33.14
270437AC2-090 C
Solar/Wind Harmer
5.286
962031AG1-047 GEN
Solar/Wind Harmer
2.855
957741AF2-068 GEN
Solar/Wind Harmer
14.171
958821AF2-173 GEN
Solar/Wind Harmer
13.216
270004AE1-209 GEN
Solar/Wind Harmer
5.159
946031AF1-268 GEN
Solar/Wind Harmer
7.836
270356AE2-297 GEN
Solar/Wind Harmer
4.303
24728705AND G3
Adder
7.455
24728505AND G1
Adder
3.565
24642205MAYFLWER
Adder
0.585
274772LINCOLN ;3U
Adder
7.74
274752CRETE EC ;2U
Adder
7.553
274753CRETE EC ;3U
Adder
7.553
274724RIVER EC ;11
Adder
16.226
274802UNIV PARK;5U
Adder
5.329
972228AH1-698 GEN2
Adder
3.385
274826FISK ;BP
Adder
10.003
274800UNIV PARK;3U
Adder
5.327
972038AH1-567 GEN2
Adder
0.333
274729ELWOOD EC;1P
Adder
14.987
274730ELWOOD EC;6P
Adder
14.987
964991AG1-363 GEN
Solar/Wind Helper
4.266
316097T157 G90
Solar/Wind Helper
1.323
23750701CROSSCHOOL
Solar/Wind Helper
1.364
238118U2-030_1
Solar/Wind Helper
0.318
238127S14_GEN_2
Solar/Wind Helper
0.764
238148AE2-230_GEN2
Solar/Wind Helper
0.429
237048AF1-022 C
Solar/Wind Helper
0.17
237080AD1-060 GEN
Solar/Wind Helper
0.294
237038AE2-054 C
Solar/Wind Helper
0.235
235062AE1-101 C1
Solar/Wind Helper
1.433
23779801AA1-109
Solar/Wind Helper
0.166
971617AH1-308 GEN
Solar/Wind Harmer
0.866
970689AG2-444 GEN
Solar/Wind Harmer
16.696
270432AC2-029 GEN
Solar/Wind Harmer
7.17
270269AC2-059
Solar/Wind Harmer
9.545
972203AH1-686 GEN
Adder
2.352
940611AE2-048 GEN
Solar/Wind Harmer
22.396
941391AE2-136 GEN
Solar/Wind Harmer
11.605
270284AF1-227 GEN1
Solar/Wind Harmer
5.752
270286AF1-227 GEN2
Solar/Wind Harmer
2.128
270287AF1-227 GEN3
Solar/Wind Harmer
2.128
270156DARBY CT1
Adder
9.085
270157DARBY CT2
Adder
9.063
270158DARBY CT3
Adder
8.918
945631AF1-228 GEN
Solar/Wind Harmer
4.754
253383AE2-342_GEN
Solar/Wind Harmer
0.896
241973AD2-163_GEN1
Solar/Wind Harmer
2.003
943861AF1-054 GEN
Solar/Wind Harmer
3.878
943851AF1-053 GEN
Solar/Wind Harmer
1.874
971985AH1-537 GEN
Solar/Wind Harmer
17.95
270340AC2-060 GEN
Solar/Wind Harmer
3.039
241972AD1-140 GEN
Solar/Wind Harmer
4.433
270367AC2-061_GEN
Solar/Wind Harmer
3.127
253372AE2-315 SEC3
Adder
1.853
253372AE2-315 SEC3
Adder
1.853
270578AF1-285 GEN2
Solar/Wind Harmer
0.455
25306009OHH W.
Adder
2.812
253349AC2-067 GEN
Solar/Wind Harmer
4.845
253400AC2-068 GEN
Solar/Wind Harmer
1.948
252524AE2-267 GEN
Solar/Wind Harmer
1.528
25196408WSDLE3
Adder
8.545
25196308WSDLE2
Adder
8.471
25196208WSDLE1
Adder
8.45
25196708WSDLE6
Adder
8.428
25196508WSDLE4
Adder
8.216
270302AB2-170 GEN
Solar/Wind Harmer
8.082
270317AD1-130_GEN
Solar/Wind Harmer
3.098
944031AF1-071 GEN
Solar/Wind Harmer
0.962
25196108MFTGT2
Adder
1.467
25196108MFTGT2
Adder
1.362
971673AH1-337 GEN
Solar/Wind Harmer
4.374
971029AG2-637 GEN
Solar/Wind Harmer
14.252
972163AH1-664 GEN
Solar/Wind Harmer
9.488
972165AH1-665 GEN
Solar/Wind Harmer
7.591
270543AE2-219 C
Solar/Wind Harmer
4.856
270240V3-007_GEN2
Solar/Wind Harmer
5.858
24729505KEY G4
Adder
6.141
958711AF2-162 GEN
Solar/Wind Harmer
0.957
965101AG1-375 GEN
Solar/Wind Harmer
9.456
945581AF1-223 GEN
Solar/Wind Harmer
4.286
961761AG1-017 GEN
Solar/Wind Harmer
0.404
970115AG2-085 GEN
Solar/Wind Harmer
3.771
24477305BRIDGE
Adder
0.321
274775LINCOLN ;6U
Adder
7.74
274776LINCOLN ;7U
Adder
7.74
274777LINCOLN ;8U
Adder
7.74
274814UNIV PK N;0U
Adder
4.624
274807UNIV PK N;3U
Adder
4.614
274805UNIV PK N;1U
Adder
4.594
274811UNIV PK N;7U
Adder
4.584
972037AH1-567 GEN1
Adder
0.167
972227AH1-698 GEN1
Adder
2.383
274827FISK ;RP
Adder
7.089
274687WILL CNTY;4U
Adder
25.484
274687WILL CNTY;4U
Adder
25.484
274731ELWOOD EC;2P
Adder
14.987
274733ELWOOD EC;3P
Adder
14.987
274735ELWOOD EC;4P
Adder
14.987
274728ELWOOD EC;5P
Adder
14.987
238109AE1-109 GEN2
Solar/Wind Helper
0.102
238110AE1-109 GEN3
Solar/Wind Helper
0.102
238126S14_GEN_1
Solar/Wind Helper
0.764
23750501ELLIOTTS
Solar/Wind Helper
0.636
238152AF2-075_GEN
Solar/Wind Helper
0.611
238208AF1-136 C
Solar/Wind Helper
0.19
23546401DTGZ2-030
Solar/Wind Helper
0.077
237085AD2-009_GEN
Solar/Wind Helper
1.425
3138216PACIFIC
Solar/Wind Helper
0.038
316411AF1-147_GEN1
Solar/Wind Helper
0.754
316415AF1-147_GEN2
Solar/Wind Helper
0.754
270024AE2-089 GEN
Solar/Wind Harmer
0.699
23559101PLEAS2
50/50
11.891
23684101S70BUS1
50/50
0.299
23562301OGROV1
50/50
2.291
24721705FLATG2
Adder
24.202
962761AG1-125 GEN
Solar/Wind Harmer
36.157
970149AG2-104 GEN
Solar/Wind Harmer
44.654
970155AG2-107 GEN
Solar/Wind Harmer
15.766
960001AF2-291 GEN
Solar/Wind Harmer
3.209
270510AE1-227 GEN1
Solar/Wind Harmer
2.625
970947AG2-589 GEN
Solar/Wind Harmer
2.09
270331AC1-082 GEN3
Solar/Wind Harmer
0.472
270349AD2-093_GEN
Solar/Wind Harmer
3.785
927014AC1-188 GEN
Solar/Wind Harmer
1.641
270263AC1-001 GEN
Solar/Wind Harmer
1.071
270159DARBY CT4
Adder
8.94
24686105CER G3
Adder
8.419
24686505CER G6
Adder
8.408
253343AC1-166 GEN
Solar/Wind Harmer
1.094
253325AC1-069 GEN
Solar/Wind Harmer
1.056
24723205RIVRG3
Adder
18.885
970593AG2-378 GEN
Solar/Wind Harmer
2.007
253432AC1-085 GEN2
Solar/Wind Harmer
0.262
946171AF1-282 GEN
Solar/Wind Harmer
9.798
253370AE2-315 SEC1
Adder
1.959
253371AE2-315 SEC2
Adder
1.853
270223U2-072_GEN1
Solar/Wind Harmer
1.932
270578AF1-285 GEN2
Solar/Wind Harmer
1.182
270391AF1-285 GEN3
Solar/Wind Harmer
1.182
25326309TAIT D
Adder
1.071
960071AF2-298 GEN
Solar/Wind Harmer
4.866
252507AC2-088 GEN
Solar/Wind Harmer
1.745
25194608D.CRK4
Adder
1.592
25196808ZIMRHP
Adder
73.247
270462AD2-086
Solar/Wind Harmer
6.724
25196008MFTGT1
Adder
1.331
970333AG2-219 GEN
Solar/Wind Harmer
30.032
945681AF1-233 GEN
Solar/Wind Harmer
17.913
971995AH1-542 GEN
Solar/Wind Harmer
10.422
247536S-71 GEN
Solar/Wind Harmer
3.833
942081AE2-220 GEN
Solar/Wind Harmer
6.053
270239V3-007_GEN1
Solar/Wind Harmer
1.629
965651AG1-433 GEN
Solar/Wind Harmer
5.169
958861AF2-177 GEN
Solar/Wind Harmer
10.335
945371AF1-202 GEN
Solar/Wind Harmer
6.594
270005AE1-210 C O1
Solar/Wind Harmer
5.159
965031AG1-367 GEN
Solar/Wind Harmer
9.44
970825AG2-519 GEN
Solar/Wind Harmer
2.221
970091AG2-072 GEN
Adder
72.107
24728605AND G2
Adder
3.565
24639705ELKHART HY
Adder
0.142
274773LINCOLN ;4U
Adder
7.74
274774LINCOLN ;5U
Adder
7.74
274751CRETE EC ;1U
Adder
7.553
274754CRETE EC ;4U
Adder
7.553
274723RIVER EC ;12
Adder
16.418
274812UNIV PK N;8U
Adder
4.584
274801UNIV PARK;4U
Adder
5.327
274732ELWOOD EC;7P
Adder
8.75
23751101LEADS_P59
Solar/Wind Helper
1.597
23751201ROTHROCK
Solar/Wind Helper
0.849
23562501BACKB
Solar/Wind Helper
1.042
23583801GRNGAP
Solar/Wind Helper
4.948
316095T157 G97
Solar/Wind Helper
1.323
238185AF2-356 C
Solar/Wind Helper
2.474
235054AD2-180 GEN
Solar/Wind Helper
1.935
238117U2-030
Solar/Wind Helper
0.318
238108AE1-109 GEN1
Solar/Wind Helper
0.102
235531U2-073 GEN
Solar/Wind Helper
3.033
238147AE2-230_GEN1
Solar/Wind Helper
0.427
238149AF1-291A_GEN
Solar/Wind Helper
0.122
237061AD1-155 GEN
Solar/Wind Helper
0.046
238221AF1-254 C O1
Solar/Wind Helper
0.235
235067AD1-061 GEN
Solar/Wind Helper
0.427
237030AB1-096 C
Solar/Wind Helper
0.061
944201AF1-088_MTX
Adder
106.522
957141AF2-008_MTX
Adder
53.261
CBM West 1LTFEXP_CBM-W1->PJM
CBM
126.393
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.84
MECLTFEXP_MEC->PJM
CLTF
14.465
SIGELTFEXP_SIGE->PJM
CLTF
0.467
LAGNLTFEXP_LAGN->PJM
CLTF
14.169
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.052
TVALTFEXP_TVA->PJM
CLTF
7.036
CPLELTFEXP_CPLE->PJM
CLTF
1.288
CBM West 2LTFEXP_CBM-W2->PJM
CBM
105.476
NYPJM->LTFIMP_NY
CLTF
4.491
LGEELTFEXP_LGEE->PJM
CLTF
6.272
WECLTFEXP_WEC->PJM
CLTF
3.434
AG2-052LTFEXP_AG2-052->PJM
LTF
0.214
AH1-155LTFEXP_AH1-155->PJM
LTF
0.321

Details for 01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line l/o AP_P2-3_WP-500-DRT7A_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-500-DRT7A_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.43 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4604.68
MW Contribution:10.75
Bus #Bus NameTypeMW Contribution
24318905MLG2
50/50
4.855
270471AD2-092_GEN
Solar/Wind Harmer
3.785
23559001PLEAS1
50/50
11.891
23684201S70BUS2
50/50
0.305
23562401OGROV2
50/50
2.277
24318805MLG1
50/50
6.637
24721905FLATG4
Adder
24.202
970153AG2-106 GEN
Solar/Wind Harmer
15.766
270512AE1-227 GEN2
Solar/Wind Harmer
2.228
971191AH1-055 GEN
Solar/Wind Harmer
22.913
957541AF2-048 GEN
Solar/Wind Harmer
1.637
961921AG1-034 GEN
Solar/Wind Harmer
13.119
270291AC1-194 GEN
Solar/Wind Harmer
10.875
960801AF2-371 GEN
Solar/Wind Harmer
2.601
964871AG1-351 GEN
Solar/Wind Harmer
1.796
270273AD2-016 GEN
Solar/Wind Harmer
2.73
972173AH1-669 GEN
Solar/Wind Harmer
5.115
241955AC1-078 GEN
Solar/Wind Harmer
7.599
942051AE2-217 GEN
Solar/Wind Harmer
18.179
24686205CER G4
Adder
8.375
24686405CER G5
Adder
8.342
241974AD2-163_GEN2
Solar/Wind Harmer
2.003
253338AC1-165 GEN
Solar/Wind Harmer
1.094
253333AC1-068 GEN
Solar/Wind Harmer
1.056
970605AG2-385 GEN
Solar/Wind Harmer
5.418
253415AE1-040 GEN
Solar/Wind Harmer
1.129
253406AD2-031_GEN
Solar/Wind Harmer
1.261
253316AC1-085 GEN3
Solar/Wind Harmer
8.207
253433AC1-085 GEN1
Solar/Wind Harmer
5.21
946181AF1-283 GEN
Solar/Wind Harmer
12.737
253303V4-073 C
Solar/Wind Harmer
0.113
962771AG1-126 GEN
Solar/Wind Harmer
36.157
270330AC1-082 GEN2
Solar/Wind Harmer
0.8
270329AC1-082 GEN1
Solar/Wind Harmer
0.471
270054AF2-122 C O1
Solar/Wind Harmer
3.386
270520AE2-214 GEN
Solar/Wind Harmer
6.239
270459AD2-067 GEN
Solar/Wind Harmer
8.614
961821AG1-024 GEN
Solar/Wind Harmer
8.746
970879AG2-548 GEN
Solar/Wind Harmer
4.417
970689AG2-444 GEN
Solar/Wind Harmer
16.696
270432AC2-029 GEN
Solar/Wind Harmer
7.17
270269AC2-059
Solar/Wind Harmer
9.545
972203AH1-686 GEN
Adder
2.352
940611AE2-048 GEN
Solar/Wind Harmer
22.396
941391AE2-136 GEN
Solar/Wind Harmer
11.605
270284AF1-227 GEN1
Solar/Wind Harmer
5.752
270286AF1-227 GEN2
Solar/Wind Harmer
2.128
270287AF1-227 GEN3
Solar/Wind Harmer
2.128
270156DARBY CT1
Adder
9.085
270157DARBY CT2
Adder
9.063
270158DARBY CT3
Adder
8.918
945631AF1-228 GEN
Solar/Wind Harmer
4.754
253383AE2-342_GEN
Solar/Wind Harmer
0.896
241973AD2-163_GEN1
Solar/Wind Harmer
2.003
943861AF1-054 GEN
Solar/Wind Harmer
3.878
943851AF1-053 GEN
Solar/Wind Harmer
1.874
971985AH1-537 GEN
Solar/Wind Harmer
17.95
270340AC2-060 GEN
Solar/Wind Harmer
3.039
241972AD1-140 GEN
Solar/Wind Harmer
4.433
270367AC2-061_GEN
Solar/Wind Harmer
3.127
23559101PLEAS2
50/50
11.891
23684101S70BUS1
50/50
0.299
23562301OGROV1
50/50
2.291
24721705FLATG2
Adder
24.202
962761AG1-125 GEN
Solar/Wind Harmer
36.157
970149AG2-104 GEN
Solar/Wind Harmer
44.654
970155AG2-107 GEN
Solar/Wind Harmer
15.766
960001AF2-291 GEN
Solar/Wind Harmer
3.209
270510AE1-227 GEN1
Solar/Wind Harmer
2.625
970947AG2-589 GEN
Solar/Wind Harmer
2.09
270331AC1-082 GEN3
Solar/Wind Harmer
0.472
270349AD2-093_GEN
Solar/Wind Harmer
3.785
927014AC1-188 GEN
Solar/Wind Harmer
1.641
270263AC1-001 GEN
Solar/Wind Harmer
1.071
270159DARBY CT4
Adder
8.94
24686105CER G3
Adder
8.419
24686505CER G6
Adder
8.408
253343AC1-166 GEN
Solar/Wind Harmer
1.094
253325AC1-069 GEN
Solar/Wind Harmer
1.056
24723205RIVRG3
Adder
18.885
970593AG2-378 GEN
Solar/Wind Harmer
2.007
253432AC1-085 GEN2
Solar/Wind Harmer
0.262
946171AF1-282 GEN
Solar/Wind Harmer
9.798
253370AE2-315 SEC1
Adder
1.959
253371AE2-315 SEC2
Adder
1.853
270223U2-072_GEN1
Solar/Wind Harmer
1.932
270578AF1-285 GEN2
Solar/Wind Harmer
1.182
270391AF1-285 GEN3
Solar/Wind Harmer
1.182
25326309TAIT D
Adder
1.071
960071AF2-298 GEN
Solar/Wind Harmer
4.866
252507AC2-088 GEN
Solar/Wind Harmer
1.745
25194608D.CRK4
Adder
1.592
25196808ZIMRHP
Adder
73.247
270462AD2-086
Solar/Wind Harmer
6.724
25196008MFTGT1
Adder
1.331
970333AG2-219 GEN
Solar/Wind Harmer
30.032
945681AF1-233 GEN
Solar/Wind Harmer
17.913
971995AH1-542 GEN
Solar/Wind Harmer
10.422
247536S-71 GEN
Solar/Wind Harmer
3.833
942081AE2-220 GEN
Solar/Wind Harmer
6.053
270239V3-007_GEN1
Solar/Wind Harmer
1.629
965651AG1-433 GEN
Solar/Wind Harmer
5.169
958861AF2-177 GEN
Solar/Wind Harmer
10.335
945371AF1-202 GEN
Solar/Wind Harmer
6.594
270005AE1-210 C O1
Solar/Wind Harmer
5.159
965031AG1-367 GEN
Solar/Wind Harmer
9.44
970825AG2-519 GEN
Solar/Wind Harmer
2.221
970091AG2-072 GEN
Adder
72.107
24728605AND G2
Adder
3.565
24639705ELKHART HY
Adder
0.142
274773LINCOLN ;4U
Adder
7.74
274774LINCOLN ;5U
Adder
7.74
274751CRETE EC ;1U
Adder
7.553
274754CRETE EC ;4U
Adder
7.553
274723RIVER EC ;12
Adder
16.418
274812UNIV PK N;8U
Adder
4.584
274801UNIV PARK;4U
Adder
5.327
274732ELWOOD EC;7P
Adder
8.75
23751101LEADS_P59
Solar/Wind Helper
1.597
23751201ROTHROCK
Solar/Wind Helper
0.849
23562501BACKB
Solar/Wind Helper
1.042
23583801GRNGAP
Solar/Wind Helper
4.948
316095T157 G97
Solar/Wind Helper
1.323
238185AF2-356 C
Solar/Wind Helper
2.474
235054AD2-180 GEN
Solar/Wind Helper
1.935
238117U2-030
Solar/Wind Helper
0.318
238108AE1-109 GEN1
Solar/Wind Helper
0.102
235531U2-073 GEN
Solar/Wind Helper
3.033
238147AE2-230_GEN1
Solar/Wind Helper
0.427
238149AF1-291A_GEN
Solar/Wind Helper
0.122
237061AD1-155 GEN
Solar/Wind Helper
0.046
238221AF1-254 C O1
Solar/Wind Helper
0.235
235067AD1-061 GEN
Solar/Wind Helper
0.427
237030AB1-096 C
Solar/Wind Helper
0.061
946101AF1-275 GEN
Solar/Wind Harmer
1.557
970879AG2-548 GEN
Solar/Wind Harmer
6.331
971073AG2-665 GEN
Solar/Wind Harmer
6.331
971073AG2-665 GEN
Solar/Wind Harmer
4.417
24685805CER G1
Adder
8.364
24685905CER G2
Adder
8.364
942861AE2-305 GEN
Solar/Wind Harmer
7.857
270518AE2-148 GEN
Solar/Wind Harmer
12.175
24723005RIVRG1
Adder
18.885
24723105RIVRG2
Adder
18.885
970077AG2-063 GEN
Solar/Wind Harmer
5.418
972269AH1-719 GEN
Adder
2.302
962581AG1-107 GEN
Solar/Wind Harmer
4.952
961491AF2-440 GEN
Solar/Wind Harmer
2.058
253394AE2-221_GEN
Solar/Wind Harmer
4.456
253398AE2-221_GEN2
Solar/Wind Harmer
4.456
253317AC1-085 GEN4
Solar/Wind Harmer
8.207
25326109MON D
Adder
1.288
964601AG1-323 GEN
Solar/Wind Harmer
3.106
964601AG1-323 GEN
Solar/Wind Harmer
1.445
253370AE2-315 SEC1
Adder
1.959
270224U2-072_GEN2
Solar/Wind Harmer
1.932
270227U2-072_GEN3
Solar/Wind Harmer
1.932
270228U2-072_GEN4
Solar/Wind Harmer
1.932
270231U2-072_GEN5
Solar/Wind Harmer
1.932
25322209TAIT E
Adder
9.53
25322209TAIT E
Adder
9.316
270186AC1-089 GEN
Solar/Wind Harmer
5.968
938701AE1-092 GEN
Solar/Wind Harmer
20.142
25183208HLCRTG
Solar/Wind Harmer
5.905
972159AH1-661 GEN
Adder
0.972
252509AD1-136 GEN
Solar/Wind Harmer
0.249
252519AF1-045_GEN
Solar/Wind Harmer
5.902
252516AE2-318_GEN
Solar/Wind Harmer
4.502
253378AE2-206_GEN
Solar/Wind Harmer
3.485
276820AF1-078_GEN
Solar/Wind Harmer
1.548
25194408D.CRK1
Adder
7.324
25194508D.CRK3
Adder
1.369
25326509SID D
Adder
1.268
970239AG2-162 GEN
Solar/Wind Harmer
10.466
24728805RICHG1
Adder
3.587
24728905RICHG2
Adder
3.587
970883AG2-550 GEN
Solar/Wind Harmer
9.484
970885AG2-551 GEN
Solar/Wind Harmer
2.206
270383AD1-128 GEN
Solar/Wind Harmer
5.785
24379505HDWTR1G C
Solar/Wind Harmer
7.487
270209AC1-174_GEN
Solar/Wind Harmer
5.284
926881AC1-175 GEN
Solar/Wind Harmer
5.284
944541AF1-119 GEN
Solar/Wind Harmer
3.962
960971AF2-388 GEN
Solar/Wind Harmer
10.338
247621Y3-024
Adder
0.228
270201AC2-176 GEN
Solar/Wind Harmer
4.857
964611AG1-324 GEN
Solar/Wind Harmer
1.114
964611AG1-324 GEN
Solar/Wind Harmer
0.494
970825AG2-519 GEN
Solar/Wind Harmer
9.953
960441AF2-335 GEN
Solar/Wind Harmer
9.427
247620Y3-023
Adder
0.425
274770LINCOLN ;1U
Adder
7.74
274771LINCOLN ;2U
Adder
7.74
274808UNIV PK N;4U
Adder
4.563
274803UNIV PARK;6U
Adder
5.329
972259AH1-714 GEN
Adder
17.426
23585401KL_K28_T16
Solar/Wind Helper
1.442
238120AE2-309 GEN
Solar/Wind Helper
0.483
238175AF1-290_GEN
Solar/Wind Helper
0.13
238169AE2-226 GEN1
Solar/Wind Helper
0.6
238170AE2-226 GEN2
Solar/Wind Helper
0.6
235020AA1-095 C
Solar/Wind Helper
0.045
23777901MDS_W4-102
Solar/Wind Helper
0.151
235063AE1-101 C2
Solar/Wind Helper
1.433
237002AB1-128_GEN
Solar/Wind Helper
0.382
237001AB1-127_GEN
Solar/Wind Helper
0.381
237034AC2-136 C
Solar/Wind Helper
0.194
23777801MSM_W1-116
Solar/Wind Helper
0.098
237025AB1-124 C
Solar/Wind Helper
0.142
237006AB1-125 GEN
Solar/Wind Helper
0.106
253370AE2-315 SEC1
Adder
1.959
253371AE2-315 SEC2
Adder
1.853
942871AE2-306 GEN
Solar/Wind Harmer
0.886
270391AF1-285 GEN3
Solar/Wind Harmer
0.455
252510AF1-249 C
Solar/Wind Harmer
0.405
25196608WSDLE5
Adder
8.301
25194608D.CRK4
Adder
1.592
270485AE1-090_GEN
Solar/Wind Harmer
0.584
270222AC2-111 GEN
Solar/Wind Harmer
7.805
25196008MFTGT1
Adder
1.289
970243AG2-164 GEN
Solar/Wind Harmer
24.571
970519AG2-331 GEN
Solar/Wind Harmer
16.508
970699AG2-449 GEN
Solar/Wind Harmer
10.921
972167AH1-666 GEN
Solar/Wind Harmer
7.605
958171AF2-111 GEN
Solar/Wind Harmer
23.761
944531AF1-118 GEN
Solar/Wind Harmer
33.14
270437AC2-090 C
Solar/Wind Harmer
5.286
962031AG1-047 GEN
Solar/Wind Harmer
2.855
957741AF2-068 GEN
Solar/Wind Harmer
14.171
958821AF2-173 GEN
Solar/Wind Harmer
13.216
270004AE1-209 GEN
Solar/Wind Harmer
5.159
946031AF1-268 GEN
Solar/Wind Harmer
7.836
270356AE2-297 GEN
Solar/Wind Harmer
4.303
24728705AND G3
Adder
7.455
24728505AND G1
Adder
3.565
24642205MAYFLWER
Adder
0.585
274772LINCOLN ;3U
Adder
7.74
274752CRETE EC ;2U
Adder
7.553
274753CRETE EC ;3U
Adder
7.553
274724RIVER EC ;11
Adder
16.226
274802UNIV PARK;5U
Adder
5.329
972228AH1-698 GEN2
Adder
3.385
274826FISK ;BP
Adder
10.003
274800UNIV PARK;3U
Adder
5.327
972038AH1-567 GEN2
Adder
0.333
274729ELWOOD EC;1P
Adder
14.987
274730ELWOOD EC;6P
Adder
14.987
964991AG1-363 GEN
Solar/Wind Helper
4.266
316097T157 G90
Solar/Wind Helper
1.323
23750701CROSSCHOOL
Solar/Wind Helper
1.364
238118U2-030_1
Solar/Wind Helper
0.318
238127S14_GEN_2
Solar/Wind Helper
0.764
238148AE2-230_GEN2
Solar/Wind Helper
0.429
237048AF1-022 C
Solar/Wind Helper
0.17
237080AD1-060 GEN
Solar/Wind Helper
0.294
237038AE2-054 C
Solar/Wind Helper
0.235
235062AE1-101 C1
Solar/Wind Helper
1.433
23779801AA1-109
Solar/Wind Helper
0.166
971617AH1-308 GEN
Solar/Wind Harmer
0.866
253372AE2-315 SEC3
Adder
1.853
253372AE2-315 SEC3
Adder
1.853
270578AF1-285 GEN2
Solar/Wind Harmer
0.455
25306009OHH W.
Adder
2.812
253349AC2-067 GEN
Solar/Wind Harmer
4.845
253400AC2-068 GEN
Solar/Wind Harmer
1.948
252524AE2-267 GEN
Solar/Wind Harmer
1.528
25196408WSDLE3
Adder
8.545
25196308WSDLE2
Adder
8.471
25196208WSDLE1
Adder
8.45
25196708WSDLE6
Adder
8.428
25196508WSDLE4
Adder
8.216
270302AB2-170 GEN
Solar/Wind Harmer
8.082
270317AD1-130_GEN
Solar/Wind Harmer
3.098
944031AF1-071 GEN
Solar/Wind Harmer
0.962
25196108MFTGT2
Adder
1.467
25196108MFTGT2
Adder
1.362
971673AH1-337 GEN
Solar/Wind Harmer
4.374
971029AG2-637 GEN
Solar/Wind Harmer
14.252
972163AH1-664 GEN
Solar/Wind Harmer
9.488
972165AH1-665 GEN
Solar/Wind Harmer
7.591
270543AE2-219 C
Solar/Wind Harmer
4.856
270240V3-007_GEN2
Solar/Wind Harmer
5.858
24729505KEY G4
Adder
6.141
958711AF2-162 GEN
Solar/Wind Harmer
0.957
965101AG1-375 GEN
Solar/Wind Harmer
9.456
945581AF1-223 GEN
Solar/Wind Harmer
4.286
961761AG1-017 GEN
Solar/Wind Harmer
0.404
970115AG2-085 GEN
Solar/Wind Harmer
3.771
24477305BRIDGE
Adder
0.321
274775LINCOLN ;6U
Adder
7.74
274776LINCOLN ;7U
Adder
7.74
274777LINCOLN ;8U
Adder
7.74
274814UNIV PK N;0U
Adder
4.624
274807UNIV PK N;3U
Adder
4.614
274805UNIV PK N;1U
Adder
4.594
274811UNIV PK N;7U
Adder
4.584
972037AH1-567 GEN1
Adder
0.167
972227AH1-698 GEN1
Adder
2.383
274827FISK ;RP
Adder
7.089
274687WILL CNTY;4U
Adder
25.484
274687WILL CNTY;4U
Adder
25.484
274731ELWOOD EC;2P
Adder
14.987
274733ELWOOD EC;3P
Adder
14.987
274735ELWOOD EC;4P
Adder
14.987
274728ELWOOD EC;5P
Adder
14.987
238109AE1-109 GEN2
Solar/Wind Helper
0.102
238110AE1-109 GEN3
Solar/Wind Helper
0.102
238126S14_GEN_1
Solar/Wind Helper
0.764
23750501ELLIOTTS
Solar/Wind Helper
0.636
238152AF2-075_GEN
Solar/Wind Helper
0.611
238208AF1-136 C
Solar/Wind Helper
0.19
23546401DTGZ2-030
Solar/Wind Helper
0.077
237085AD2-009_GEN
Solar/Wind Helper
1.425
3138216PACIFIC
Solar/Wind Helper
0.038
316411AF1-147_GEN1
Solar/Wind Helper
0.754
316415AF1-147_GEN2
Solar/Wind Helper
0.754
270024AE2-089 GEN
Solar/Wind Harmer
0.699
944201AF1-088_MTX
Adder
106.522
957141AF2-008_MTX
Adder
53.261
CBM West 1LTFEXP_CBM-W1->PJM
CBM
126.393
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.84
MECLTFEXP_MEC->PJM
CLTF
14.465
SIGELTFEXP_SIGE->PJM
CLTF
0.467
LAGNLTFEXP_LAGN->PJM
CLTF
14.169
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.052
TVALTFEXP_TVA->PJM
CLTF
7.036
CPLELTFEXP_CPLE->PJM
CLTF
1.288
CBM West 2LTFEXP_CBM-W2->PJM
CBM
105.476
NYPJM->LTFIMP_NY
CLTF
4.491
LGEELTFEXP_LGEE->PJM
CLTF
6.272
WECLTFEXP_WEC->PJM
CLTF
3.434
AG2-052LTFEXP_AG2-052->PJM
LTF
0.214
AH1-155LTFEXP_AH1-155->PJM
LTF
0.321

Details for 01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-028_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-028_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.65 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4574.96
MW Contribution:6.45
Bus #Bus NameTypeMW Contribution
23559001PLEAS1
50/50
11.891
23684201S70BUS2
50/50
0.305
23562401OGROV2
50/50
2.277
24318805MLG1
50/50
6.637
24721905FLATG4
Adder
24.202
970153AG2-106 GEN
Solar/Wind Harmer
19.471
270512AE1-227 GEN2
Solar/Wind Harmer
1.892
971191AH1-055 GEN
Solar/Wind Harmer
18.65
961921AG1-034 GEN
Solar/Wind Harmer
6.407
270291AC1-194 GEN
Solar/Wind Harmer
5.661
270273AD2-016 GEN
Solar/Wind Harmer
0.74
972173AH1-669 GEN
Solar/Wind Harmer
3.569
241955AC1-078 GEN
Solar/Wind Harmer
0.006
942051AE2-217 GEN
Solar/Wind Harmer
12.683
24686205CER G4
Adder
8.375
24686405CER G5
Adder
8.342
241974AD2-163_GEN2
Solar/Wind Harmer
0.005
253338AC1-165 GEN
Solar/Wind Harmer
0.003
253333AC1-068 GEN
Solar/Wind Harmer
0.011
24318905MLG2
50/50
4.855
270471AD2-092_GEN
Solar/Wind Harmer
0.005
971073AG2-665 GEN
Solar/Wind Harmer
6.448
24685805CER G1
Adder
8.364
24685905CER G2
Adder
8.364
942861AE2-305 GEN
Solar/Wind Harmer
5.482
270518AE2-148 GEN
Solar/Wind Harmer
0.606
24723005RIVRG1
Adder
18.885
24723105RIVRG2
Adder
18.885
970077AG2-063 GEN
Solar/Wind Harmer
4.025
972269AH1-719 GEN
Adder
2.302
962581AG1-107 GEN
Solar/Wind Harmer
0.001
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
25326109MON D
Adder
1.288
964601AG1-323 GEN
Solar/Wind Harmer
2.731
964601AG1-323 GEN
Solar/Wind Harmer
1.82
253370AE2-315 SEC1
Adder
1.959
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
25322209TAIT E
Adder
9.53
25322209TAIT E
Adder
9.316
270186AC1-089 GEN
Solar/Wind Harmer
0.004
938701AE1-092 GEN
Solar/Wind Harmer
10.928
971655AH1-328 GEN
Solar/Wind Harmer
2.415
25183208HLCRTG
Solar/Wind Harmer
0.011
972159AH1-661 GEN
Adder
0.972
252509AD1-136 GEN
Solar/Wind Harmer
0.034
252519AF1-045_GEN
Solar/Wind Harmer
5.902
252516AE2-318_GEN
Solar/Wind Harmer
5.235
253378AE2-206_GEN
Solar/Wind Harmer
0.004
276820AF1-078_GEN
Solar/Wind Harmer
0.002
970329AG2-216 GEN
Solar/Wind Harmer
2.92
25194408D.CRK1
Adder
7.324
25194508D.CRK3
Adder
1.369
25326509SID D
Adder
1.268
970239AG2-162 GEN
Solar/Wind Harmer
1.662
24728805RICHG1
Adder
3.587
24728905RICHG2
Adder
3.587
970883AG2-550 GEN
Solar/Wind Harmer
6.617
970885AG2-551 GEN
Solar/Wind Harmer
2.206
270383AD1-128 GEN
Solar/Wind Harmer
0.004
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
944541AF1-119 GEN
Solar/Wind Harmer
0.442
960971AF2-388 GEN
Solar/Wind Harmer
3.871
247621Y3-024
Adder
0.228
270201AC2-176 GEN
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
0.494
970825AG2-519 GEN
Solar/Wind Harmer
7.293
960441AF2-335 GEN
Solar/Wind Harmer
6.577
270599AE1-208 GEN
Solar/Wind Harmer
6.026
270031AE2-169
Solar/Wind Harmer
3.616
942221AE2-234 GEN
Solar/Wind Harmer
0.033
971613AH1-306 GEN
Solar/Wind Harmer
3.153
970321AG2-212 GEN
Solar/Wind Harmer
2.844
970611AG2-400 GEN
Solar/Wind Harmer
6.533
970627AG2-408 GEN
Solar/Wind Harmer
1.96
246938BC-WTG3
Solar/Wind Harmer
0.235
246937BC-WTG2
Solar/Wind Harmer
0.263
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
970235AG2-159 GEN
Solar/Wind Harmer
3.948
970235AG2-159 GEN
Solar/Wind Harmer
2.265
971199AH1-059 GEN
Solar/Wind Harmer
2.587
339221AD2-048_GEN
Solar/Wind Harmer
0.004
966841AG1-555 GEN
Solar/Wind Harmer
0.73
965681AG1-436 GEN
Solar/Wind Harmer
8.059
965791AG1-447 GEN
Solar/Wind Harmer
5.91
270007AE1-245 C
Solar/Wind Harmer
0.002
270216AD2-079_GEN
Solar/Wind Harmer
0.001
247620Y3-023
Adder
0.425
270526AF1-158 GEN
Solar/Wind Harmer
0.008
972043AH1-570 GEN
Solar/Wind Harmer
1.674
972045AH1-571 GEN
Solar/Wind Harmer
1.341
24441505OLIV SLR
Solar/Wind Harmer
0
970241AG2-163 GEN
Solar/Wind Harmer
3.747
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
12.817
961051AF2-396 GEN
Solar/Wind Harmer
8.545
274770LINCOLN ;1U
Adder
7.74
274771LINCOLN ;2U
Adder
7.74
270444AC2-157 GEN1
Solar/Wind Harmer
0.003
971587AH1-292 GEN
Solar/Wind Harmer
4.687
970623AG2-406 GEN
Solar/Wind Harmer
1.169
274808UNIV PK N;4U
Adder
4.563
274803UNIV PARK;6U
Adder
5.329
274888KELLY CRK;1U
Solar/Wind Harmer
0.375
274887GEN-1.85
Solar/Wind Harmer
0.168
276843GEN-1.7
Solar/Wind Harmer
0.206
945391AF1-204 GEN
Solar/Wind Harmer
6.775
958011AF2-095 GEN
Solar/Wind Harmer
9.182
972259AH1-714 GEN
Adder
17.426
241960AC2-195 GEN
Solar/Wind Harmer
0.005
971125AH1-004 GEN
Solar/Wind Harmer
2.546
970107AG2-081 GEN
Solar/Wind Harmer
1.909
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
960161AF2-307 GEN
Solar/Wind Harmer
4.195
944971AF1-162 GEN
Solar/Wind Harmer
6.345
958481AF2-142 GEN
Solar/Wind Harmer
9.506
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.857
971573AH1-285 GEN
Solar/Wind Harmer
1.18
958491AF2-143 GEN
Solar/Wind Harmer
9.485
274879MINONK ;1U
Solar/Wind Harmer
0.267
23585401KL_K28_T16
Solar/Wind Helper
1.442
238120AE2-309 GEN
Solar/Wind Helper
0.483
238175AF1-290_GEN
Solar/Wind Helper
0.13
238169AE2-226 GEN1
Solar/Wind Helper
0.6
238170AE2-226 GEN2
Solar/Wind Helper
0.6
235020AA1-095 C
Solar/Wind Helper
0.045
23777901MDS_W4-102
Solar/Wind Helper
0.151
235063AE1-101 C2
Solar/Wind Helper
1.433
237002AB1-128_GEN
Solar/Wind Helper
0.382
237001AB1-127_GEN
Solar/Wind Helper
0.381
237034AC2-136 C
Solar/Wind Helper
0.194
23777801MSM_W1-116
Solar/Wind Helper
0.098
237025AB1-124 C
Solar/Wind Helper
0.142
237006AB1-125 GEN
Solar/Wind Helper
0.106
962691AG1-118 GEN
Solar/Wind Harmer
7.548
23559101PLEAS2
50/50
11.891
23684101S70BUS1
50/50
0.299
23562301OGROV1
50/50
2.291
24721705FLATG2
Adder
24.202
962761AG1-125 GEN
Solar/Wind Harmer
30.492
970149AG2-104 GEN
Solar/Wind Harmer
32.932
970155AG2-107 GEN
Solar/Wind Harmer
19.471
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
270510AE1-227 GEN1
Solar/Wind Harmer
1.892
970947AG2-589 GEN
Solar/Wind Harmer
0.243
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
270349AD2-093_GEN
Solar/Wind Harmer
0.005
927014AC1-188 GEN
Solar/Wind Harmer
0.004
270263AC1-001 GEN
Solar/Wind Harmer
0.716
270159DARBY CT4
Adder
8.94
24686105CER G3
Adder
8.419
24686505CER G6
Adder
8.408
253343AC1-166 GEN
Solar/Wind Harmer
0.003
253325AC1-069 GEN
Solar/Wind Harmer
0.011
24723205RIVRG3
Adder
18.885
970593AG2-378 GEN
Solar/Wind Harmer
1.575
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.836
253370AE2-315 SEC1
Adder
1.959
970605AG2-385 GEN
Solar/Wind Harmer
4.258
253415AE1-040 GEN
Solar/Wind Harmer
0.003
253406AD2-031_GEN
Solar/Wind Harmer
0.512
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
8.886
253370AE2-315 SEC1
Adder
1.959
253371AE2-315 SEC2
Adder
1.853
270391AF1-285 GEN3
Solar/Wind Harmer
0.455
970191AG2-125 GEN
Solar/Wind Harmer
1.745
252510AF1-249 C
Solar/Wind Harmer
0.052
25196608WSDLE5
Adder
8.301
25194608D.CRK4
Adder
1.592
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270222AC2-111 GEN
Solar/Wind Harmer
3.385
25196008MFTGT1
Adder
1.289
970243AG2-164 GEN
Solar/Wind Harmer
3.888
970519AG2-331 GEN
Solar/Wind Harmer
17.281
970699AG2-449 GEN
Solar/Wind Harmer
1.662
972167AH1-666 GEN
Solar/Wind Harmer
5.306
958171AF2-111 GEN
Solar/Wind Harmer
16.577
944531AF1-118 GEN
Solar/Wind Harmer
29.606
270437AC2-090 C
Solar/Wind Harmer
0.003
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
9.887
958821AF2-173 GEN
Solar/Wind Harmer
9.221
270004AE1-209 GEN
Solar/Wind Harmer
1.427
946031AF1-268 GEN
Solar/Wind Harmer
6.268
270356AE2-297 GEN
Solar/Wind Harmer
0.009
971617AH1-308 GEN
Solar/Wind Harmer
5.478
970513AG2-328 GEN
Solar/Wind Harmer
2.844
970517AG2-330 GEN
Solar/Wind Harmer
17.067
970289AG2-191 GEN
Solar/Wind Harmer
0.722
970291AG2-192 GEN
Solar/Wind Harmer
0.656
247642Z2-115 C
Solar/Wind Harmer
0.003
270043AE2-236 GEN
Solar/Wind Harmer
4.199
959331AF2-224 GEN
Solar/Wind Harmer
4.573
965021AG1-366 GEN
Solar/Wind Harmer
2.178
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.042
970349AG2-230 GEN
Solar/Wind Harmer
9.745
24728705AND G3
Adder
7.455
24728505AND G1
Adder
3.565
270491AE1-102 GEN2
Solar/Wind Harmer
0.843
970031AG2-029 GEN
Solar/Wind Harmer
4.207
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.466
964401AG1-302 GEN
Solar/Wind Harmer
0.001
270535AF1-215 GEN1
Solar/Wind Harmer
0.008
247643Z2-116 C
Solar/Wind Harmer
0
24642205MAYFLWER
Adder
0.585
945111AF1-176 GEN
Solar/Wind Harmer
5.203
274772LINCOLN ;3U
Adder
7.74
274752CRETE EC ;2U
Adder
7.553
274753CRETE EC ;3U
Adder
7.553
274724RIVER EC ;11
Adder
16.226
270258AD1-119 GEN
Solar/Wind Harmer
0.002
274802UNIV PARK;5U
Adder
5.329
276806AD2-047 C O1
Solar/Wind Harmer
3.613
970193AG2-126 GEN
Solar/Wind Harmer
9.564
970941AG2-585 GEN
Solar/Wind Harmer
7.971
972228AH1-698 GEN2
Adder
3.385
274826FISK ;BP
Adder
10.003
276897AD1-100 C
Solar/Wind Harmer
0.008
939351AE1-166 GEN
Solar/Wind Harmer
0
274800UNIV PARK;3U
Adder
5.327
972038AH1-567 GEN2
Adder
0.333
970707AG2-453 GEN
Solar/Wind Harmer
20.817
24441205WTRV SLR C
Solar/Wind Harmer
0
276893AG1-478 C
Solar/Wind Harmer
0.252
274729ELWOOD EC;1P
Adder
14.987
274730ELWOOD EC;6P
Adder
14.987
270404AC1-167 GEN
Solar/Wind Harmer
0.003
270053AF1-130 C
Solar/Wind Harmer
1.432
943121AE2-341 GEN
Solar/Wind Harmer
10.635
943591AF1-030 GEN
Solar/Wind Harmer
7.072
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
276805AD2-038 GEN
Solar/Wind Harmer
0.002
964991AG1-363 GEN
Solar/Wind Helper
4.266
316097T157 G90
Solar/Wind Helper
1.323
23750701CROSSCHOOL
Solar/Wind Helper
1.364
238118U2-030_1
Solar/Wind Helper
0.318
238127S14_GEN_2
Solar/Wind Helper
0.764
238148AE2-230_GEN2
Solar/Wind Helper
0.429
237048AF1-022 C
Solar/Wind Helper
0.17
237080AD1-060 GEN
Solar/Wind Helper
0.294
237038AE2-054 C
Solar/Wind Helper
0.235
235062AE1-101 C1
Solar/Wind Helper
1.433
23779801AA1-109
Solar/Wind Helper
0.166
962771AG1-126 GEN
Solar/Wind Harmer
30.492
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Harmer
0.006
270520AE2-214 GEN
Solar/Wind Harmer
0.011
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
4.271
970879AG2-548 GEN
Solar/Wind Harmer
6.448
970689AG2-444 GEN
Solar/Wind Harmer
14.59
270432AC2-029 GEN
Solar/Wind Harmer
3.168
270269AC2-059
Solar/Wind Harmer
0.004
972203AH1-686 GEN
Adder
2.352
940611AE2-048 GEN
Solar/Wind Harmer
17.483
941391AE2-136 GEN
Solar/Wind Harmer
9.848
270284AF1-227 GEN1
Solar/Wind Harmer
0.009
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
270156DARBY CT1
Adder
9.085
270157DARBY CT2
Adder
9.063
270158DARBY CT3
Adder
8.918
945631AF1-228 GEN
Solar/Wind Harmer
0
253383AE2-342_GEN
Solar/Wind Harmer
0.002
241973AD2-163_GEN1
Solar/Wind Harmer
0.005
943861AF1-054 GEN
Solar/Wind Harmer
2.706
943851AF1-053 GEN
Solar/Wind Harmer
1.874
971985AH1-537 GEN
Solar/Wind Harmer
2.087
270340AC2-060 GEN
Solar/Wind Harmer
0.008
241972AD1-140 GEN
Solar/Wind Harmer
0.755
270367AC2-061_GEN
Solar/Wind Harmer
0.005
253372AE2-315 SEC3
Adder
1.853
253372AE2-315 SEC3
Adder
1.853
270578AF1-285 GEN2
Solar/Wind Harmer
0.455
25306009OHH W.
Adder
2.812
253349AC2-067 GEN
Solar/Wind Harmer
2.136
253400AC2-068 GEN
Solar/Wind Harmer
0.859
252524AE2-267 GEN
Solar/Wind Harmer
0.002
25196408WSDLE3
Adder
8.545
25196308WSDLE2
Adder
8.471
25196208WSDLE1
Adder
8.45
25196708WSDLE6
Adder
8.428
25196508WSDLE4
Adder
8.216
270302AB2-170 GEN
Solar/Wind Harmer
0.004
270317AD1-130_GEN
Solar/Wind Harmer
0.01
971653AH1-327 GEN
Solar/Wind Harmer
0.947
25196108MFTGT2
Adder
1.467
25196108MFTGT2
Adder
1.362
971673AH1-337 GEN
Solar/Wind Harmer
4.312
971029AG2-637 GEN
Solar/Wind Harmer
9.944
972163AH1-664 GEN
Solar/Wind Harmer
7.37
972165AH1-665 GEN
Solar/Wind Harmer
5.903
270543AE2-219 C
Solar/Wind Harmer
0.004
270240V3-007_GEN2
Solar/Wind Harmer
0.002
24729505KEY G4
Adder
6.141
965101AG1-375 GEN
Solar/Wind Harmer
6.597
945581AF1-223 GEN
Solar/Wind Harmer
0
970115AG2-085 GEN
Solar/Wind Harmer
2.631
270024AE2-089 GEN
Solar/Wind Harmer
0.007
971609AH1-304 GEN
Solar/Wind Harmer
1.074
270071AF1-092 GEN
Solar/Wind Harmer
12.598
270594AE1-207 GEN
Solar/Wind Harmer
7.357
970289AG2-191 GEN
Solar/Wind Harmer
1.247
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
8.837
965051AG1-369 GEN
Solar/Wind Harmer
3.247
971347AH1-153 GEN
Solar/Wind Harmer
9.745
965041AG1-368 GEN
Solar/Wind Harmer
6.496
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.821
971611AH1-305 GEN
Solar/Wind Harmer
3.852
958391AF2-133 GEN
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0.008
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
247607V1-011 GEN
Solar/Wind Harmer
0.001
971771AH1-392 GEN
Solar/Wind Harmer
6.442
971769AH1-391 GEN
Solar/Wind Harmer
7.189
963841AG1-237 GEN
Solar/Wind Harmer
2.789
24477305BRIDGE
Adder
0.321
971619AH1-309 GEN
Solar/Wind Harmer
2.888
274775LINCOLN ;6U
Adder
7.74
274776LINCOLN ;7U
Adder
7.74
274777LINCOLN ;8U
Adder
7.74
274814UNIV PK N;0U
Adder
4.624
274807UNIV PK N;3U
Adder
4.614
274805UNIV PK N;1U
Adder
4.594
274811UNIV PK N;7U
Adder
4.584
972037AH1-567 GEN1
Adder
0.167
960591AF2-350 GEN
Solar/Wind Harmer
6.377
972227AH1-698 GEN1
Adder
2.383
274827FISK ;RP
Adder
7.089
970179AG2-119 GEN
Solar/Wind Harmer
5.69
274687WILL CNTY;4U
Adder
25.484
274687WILL CNTY;4U
Adder
25.484
274731ELWOOD EC;2P
Adder
14.987
274733ELWOOD EC;3P
Adder
14.987
274735ELWOOD EC;4P
Adder
14.987
274728ELWOOD EC;5P
Adder
14.987
970833AG2-524 GEN
Solar/Wind Harmer
6.995
970833AG2-524 GEN
Solar/Wind Harmer
4.664
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
970169AG2-114 GEN
Solar/Wind Harmer
6.327
276868AE1-113 GEN
Solar/Wind Harmer
1.267
276882AE2-255 GEN
Solar/Wind Harmer
0.739
238109AE1-109 GEN2
Solar/Wind Helper
0.102
238110AE1-109 GEN3
Solar/Wind Helper
0.102
238126S14_GEN_1
Solar/Wind Helper
0.764
23750501ELLIOTTS
Solar/Wind Helper
0.636
238152AF2-075_GEN
Solar/Wind Helper
0.611
238208AF1-136 C
Solar/Wind Helper
0.19
23546401DTGZ2-030
Solar/Wind Helper
0.077
237085AD2-009_GEN
Solar/Wind Helper
1.425
3138216PACIFIC
Solar/Wind Helper
0.038
316411AF1-147_GEN1
Solar/Wind Helper
0.754
316415AF1-147_GEN2
Solar/Wind Helper
0.754
253371AE2-315 SEC2
Adder
1.853
270223U2-072_GEN1
Solar/Wind Harmer
0.001
25326309TAIT D
Adder
1.071
960071AF2-298 GEN
Solar/Wind Harmer
3.39
252507AC2-088 GEN
Solar/Wind Harmer
0.308
25194608D.CRK4
Adder
1.592
25196808ZIMRHP
Adder
73.247
270462AD2-086
Solar/Wind Harmer
0.014
25196008MFTGT1
Adder
1.331
970333AG2-219 GEN
Solar/Wind Harmer
4.752
945681AF1-233 GEN
Solar/Wind Harmer
12.498
971995AH1-542 GEN
Solar/Wind Harmer
2.424
247536S-71 GEN
Solar/Wind Harmer
0.266
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.843
965651AG1-433 GEN
Solar/Wind Harmer
1.936
958861AF2-177 GEN
Solar/Wind Harmer
2.859
945371AF1-202 GEN
Solar/Wind Harmer
0.001
270005AE1-210 C O1
Solar/Wind Harmer
1.427
965031AG1-367 GEN
Solar/Wind Harmer
6.586
970773AG2-487 GEN
Solar/Wind Harmer
1.163
970825AG2-519 GEN
Solar/Wind Harmer
2.336
270032AE2-172
Solar/Wind Harmer
4.379
970245AG2-165 GEN
Solar/Wind Harmer
2.844
970291AG2-192 GEN
Solar/Wind Harmer
0.853
970091AG2-072 GEN
Adder
72.107
276903AD2-071 C
Solar/Wind Harmer
7.32
965011AG1-365 GEN
Solar/Wind Harmer
6.533
247521TR3_G114
Solar/Wind Harmer
0.237
270246TR4_N_V150
Solar/Wind Harmer
0.042
965421AG1-410 GEN
Solar/Wind Harmer
19.465
24728605AND G2
Adder
3.565
246936BC-WTG1
Solar/Wind Harmer
0.263
270489AE1-102 GEN1
Solar/Wind Harmer
0.843
24695305TIMB G C
Solar/Wind Harmer
0.002
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.087
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
24791305MDL-5G
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.406
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270063AE2-323 C
Solar/Wind Harmer
0.005
270055AF2-134 C O1
Solar/Wind Harmer
0.005
970373AG2-245 GEN
Solar/Wind Harmer
13.568
339216AC1-074 GEN
Solar/Wind Harmer
0.177
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.002
24639705ELKHART HY
Adder
0.142
963741AG1-226 GEN
Solar/Wind Harmer
15.2
945111AF1-176 GEN
Solar/Wind Harmer
11.453
270505AE1-170 C O1
Solar/Wind Harmer
6.739
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.342
274773LINCOLN ;4U
Adder
7.74
274774LINCOLN ;5U
Adder
7.74
274751CRETE EC ;1U
Adder
7.553
274754CRETE EC ;4U
Adder
7.553
274723RIVER EC ;12
Adder
16.418
270445AC2-157 GEN2
Solar/Wind Harmer
0.003
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.584
276776AD2-060 GEN
Solar/Wind Harmer
0.666
941551AE2-152 GEN
Solar/Wind Harmer
0
274801UNIV PARK;4U
Adder
5.327
274732ELWOOD EC;7P
Adder
8.75
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
939401AE1-172 GEN
Solar/Wind Harmer
4.75
276691AA1-018 GEN1
Solar/Wind Harmer
0.768
944231AF1-091 GEN
Solar/Wind Harmer
1.688
276901AD2-066 C O1
Solar/Wind Harmer
0.006
971997AH1-543 GEN
Solar/Wind Harmer
3.315
23751101LEADS_P59
Solar/Wind Helper
1.597
23751201ROTHROCK
Solar/Wind Helper
0.849
23562501BACKB
Solar/Wind Helper
1.042
23583801GRNGAP
Solar/Wind Helper
4.948
316095T157 G97
Solar/Wind Helper
1.323
238185AF2-356 C
Solar/Wind Helper
2.474
235054AD2-180 GEN
Solar/Wind Helper
1.935
238117U2-030
Solar/Wind Helper
0.318
238108AE1-109 GEN1
Solar/Wind Helper
0.102
235531U2-073 GEN
Solar/Wind Helper
3.033
238147AE2-230_GEN1
Solar/Wind Helper
0.427
238149AF1-291A_GEN
Solar/Wind Helper
0.122
237061AD1-155 GEN
Solar/Wind Helper
0.046
238221AF1-254 C O1
Solar/Wind Helper
0.235
235067AD1-061 GEN
Solar/Wind Helper
0.427
237030AB1-096 C
Solar/Wind Helper
0.061
944201AF1-088_MTX
Adder
106.522
957141AF2-008_MTX
Adder
53.261
CBM West 1LTFEXP_CBM-W1->PJM
CBM
126.393
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.84
MECLTFEXP_MEC->PJM
CLTF
14.465
SIGELTFEXP_SIGE->PJM
CLTF
0.467
LAGNLTFEXP_LAGN->PJM
CLTF
14.169
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.052
TVALTFEXP_TVA->PJM
CLTF
7.036
CPLELTFEXP_CPLE->PJM
CLTF
1.288
CBM West 2LTFEXP_CBM-W2->PJM
CBM
105.476
NYPJM->LTFIMP_NY
CLTF
4.491
LGEELTFEXP_LGEE->PJM
CLTF
6.272
WECLTFEXP_WEC->PJM
CLTF
3.434
AG2-052LTFEXP_AG2-052->PJM
LTF
0.214
AH1-155LTFEXP_AH1-155->PJM
LTF
0.321

Details for 01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line l/o AP_P1-3_MP-765-502T_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-502T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.64 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4574.63
MW Contribution:6.45
Bus #Bus NameTypeMW Contribution
24318905MLG2
50/50
4.855
270471AD2-092_GEN
Solar/Wind Harmer
0.005
971073AG2-665 GEN
Solar/Wind Harmer
6.448
24685805CER G1
Adder
8.364
24685905CER G2
Adder
8.364
942861AE2-305 GEN
Solar/Wind Harmer
5.482
270518AE2-148 GEN
Solar/Wind Harmer
0.606
24723005RIVRG1
Adder
18.885
24723105RIVRG2
Adder
18.885
970077AG2-063 GEN
Solar/Wind Harmer
4.025
972269AH1-719 GEN
Adder
2.302
962581AG1-107 GEN
Solar/Wind Harmer
0.001
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
25326109MON D
Adder
1.288
964601AG1-323 GEN
Solar/Wind Harmer
2.731
964601AG1-323 GEN
Solar/Wind Harmer
1.82
253370AE2-315 SEC1
Adder
1.959
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
25322209TAIT E
Adder
9.53
25322209TAIT E
Adder
9.316
270186AC1-089 GEN
Solar/Wind Harmer
0.004
938701AE1-092 GEN
Solar/Wind Harmer
10.928
971655AH1-328 GEN
Solar/Wind Harmer
2.415
25183208HLCRTG
Solar/Wind Harmer
0.011
972159AH1-661 GEN
Adder
0.972
252509AD1-136 GEN
Solar/Wind Harmer
0.034
252519AF1-045_GEN
Solar/Wind Harmer
5.902
252516AE2-318_GEN
Solar/Wind Harmer
5.235
253378AE2-206_GEN
Solar/Wind Harmer
0.004
276820AF1-078_GEN
Solar/Wind Harmer
0.002
970329AG2-216 GEN
Solar/Wind Harmer
2.92
25194408D.CRK1
Adder
7.324
25194508D.CRK3
Adder
1.369
25326509SID D
Adder
1.268
970239AG2-162 GEN
Solar/Wind Harmer
1.662
24728805RICHG1
Adder
3.587
24728905RICHG2
Adder
3.587
970883AG2-550 GEN
Solar/Wind Harmer
6.617
970885AG2-551 GEN
Solar/Wind Harmer
2.206
270383AD1-128 GEN
Solar/Wind Harmer
0.004
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
944541AF1-119 GEN
Solar/Wind Harmer
0.442
960971AF2-388 GEN
Solar/Wind Harmer
3.871
247621Y3-024
Adder
0.228
270201AC2-176 GEN
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
0.494
970825AG2-519 GEN
Solar/Wind Harmer
7.293
960441AF2-335 GEN
Solar/Wind Harmer
6.577
270599AE1-208 GEN
Solar/Wind Harmer
6.026
270031AE2-169
Solar/Wind Harmer
3.616
942221AE2-234 GEN
Solar/Wind Harmer
0.033
971613AH1-306 GEN
Solar/Wind Harmer
3.153
970321AG2-212 GEN
Solar/Wind Harmer
2.844
970611AG2-400 GEN
Solar/Wind Harmer
6.533
970627AG2-408 GEN
Solar/Wind Harmer
1.96
246938BC-WTG3
Solar/Wind Harmer
0.235
246937BC-WTG2
Solar/Wind Harmer
0.263
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
970235AG2-159 GEN
Solar/Wind Harmer
3.948
970235AG2-159 GEN
Solar/Wind Harmer
2.265
971199AH1-059 GEN
Solar/Wind Harmer
2.587
23559001PLEAS1
50/50
11.891
23684201S70BUS2
50/50
0.305
23562401OGROV2
50/50
2.277
24318805MLG1
50/50
6.637
24721905FLATG4
Adder
24.202
970153AG2-106 GEN
Solar/Wind Harmer
19.471
270512AE1-227 GEN2
Solar/Wind Harmer
1.892
971191AH1-055 GEN
Solar/Wind Harmer
18.65
961921AG1-034 GEN
Solar/Wind Harmer
6.407
270291AC1-194 GEN
Solar/Wind Harmer
5.661
270273AD2-016 GEN
Solar/Wind Harmer
0.74
972173AH1-669 GEN
Solar/Wind Harmer
3.569
241955AC1-078 GEN
Solar/Wind Harmer
0.006
942051AE2-217 GEN
Solar/Wind Harmer
12.683
24686205CER G4
Adder
8.375
24686405CER G5
Adder
8.342
241974AD2-163_GEN2
Solar/Wind Harmer
0.005
253338AC1-165 GEN
Solar/Wind Harmer
0.003
253333AC1-068 GEN
Solar/Wind Harmer
0.011
970605AG2-385 GEN
Solar/Wind Harmer
4.258
253415AE1-040 GEN
Solar/Wind Harmer
0.003
253406AD2-031_GEN
Solar/Wind Harmer
0.512
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
8.886
253370AE2-315 SEC1
Adder
1.959
253371AE2-315 SEC2
Adder
1.853
270391AF1-285 GEN3
Solar/Wind Harmer
0.455
970191AG2-125 GEN
Solar/Wind Harmer
1.745
252510AF1-249 C
Solar/Wind Harmer
0.052
25196608WSDLE5
Adder
8.301
25194608D.CRK4
Adder
1.592
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270222AC2-111 GEN
Solar/Wind Harmer
3.385
25196008MFTGT1
Adder
1.289
970243AG2-164 GEN
Solar/Wind Harmer
3.888
970519AG2-331 GEN
Solar/Wind Harmer
17.281
970699AG2-449 GEN
Solar/Wind Harmer
1.662
972167AH1-666 GEN
Solar/Wind Harmer
5.306
958171AF2-111 GEN
Solar/Wind Harmer
16.577
944531AF1-118 GEN
Solar/Wind Harmer
29.606
270437AC2-090 C
Solar/Wind Harmer
0.003
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
9.887
958821AF2-173 GEN
Solar/Wind Harmer
9.221
270004AE1-209 GEN
Solar/Wind Harmer
1.427
946031AF1-268 GEN
Solar/Wind Harmer
6.268
270356AE2-297 GEN
Solar/Wind Harmer
0.009
971617AH1-308 GEN
Solar/Wind Harmer
5.478
970513AG2-328 GEN
Solar/Wind Harmer
2.844
970517AG2-330 GEN
Solar/Wind Harmer
17.067
970289AG2-191 GEN
Solar/Wind Harmer
0.722
970291AG2-192 GEN
Solar/Wind Harmer
0.656
247642Z2-115 C
Solar/Wind Harmer
0.003
270043AE2-236 GEN
Solar/Wind Harmer
4.199
959331AF2-224 GEN
Solar/Wind Harmer
4.573
965021AG1-366 GEN
Solar/Wind Harmer
2.178
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.042
970349AG2-230 GEN
Solar/Wind Harmer
9.745
24728705AND G3
Adder
7.455
24728505AND G1
Adder
3.565
270491AE1-102 GEN2
Solar/Wind Harmer
0.843
970031AG2-029 GEN
Solar/Wind Harmer
4.207
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.466
964401AG1-302 GEN
Solar/Wind Harmer
0.001
270535AF1-215 GEN1
Solar/Wind Harmer
0.008
247643Z2-116 C
Solar/Wind Harmer
0
24642205MAYFLWER
Adder
0.585
945111AF1-176 GEN
Solar/Wind Harmer
5.203
274772LINCOLN ;3U
Adder
7.74
274752CRETE EC ;2U
Adder
7.553
274753CRETE EC ;3U
Adder
7.553
274724RIVER EC ;11
Adder
16.226
270258AD1-119 GEN
Solar/Wind Harmer
0.002
274802UNIV PARK;5U
Adder
5.329
276806AD2-047 C O1
Solar/Wind Harmer
3.613
970193AG2-126 GEN
Solar/Wind Harmer
9.564
970941AG2-585 GEN
Solar/Wind Harmer
7.971
972228AH1-698 GEN2
Adder
3.385
274826FISK ;BP
Adder
10.003
276897AD1-100 C
Solar/Wind Harmer
0.008
939351AE1-166 GEN
Solar/Wind Harmer
0
274800UNIV PARK;3U
Adder
5.327
972038AH1-567 GEN2
Adder
0.333
970707AG2-453 GEN
Solar/Wind Harmer
20.817
24441205WTRV SLR C
Solar/Wind Harmer
0
276893AG1-478 C
Solar/Wind Harmer
0.252
274729ELWOOD EC;1P
Adder
14.987
274730ELWOOD EC;6P
Adder
14.987
270404AC1-167 GEN
Solar/Wind Harmer
0.003
270053AF1-130 C
Solar/Wind Harmer
1.432
943121AE2-341 GEN
Solar/Wind Harmer
10.635
943591AF1-030 GEN
Solar/Wind Harmer
7.072
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
276805AD2-038 GEN
Solar/Wind Harmer
0.002
964991AG1-363 GEN
Solar/Wind Helper
4.266
316097T157 G90
Solar/Wind Helper
1.323
23750701CROSSCHOOL
Solar/Wind Helper
1.364
238118U2-030_1
Solar/Wind Helper
0.318
238127S14_GEN_2
Solar/Wind Helper
0.764
238148AE2-230_GEN2
Solar/Wind Helper
0.429
237048AF1-022 C
Solar/Wind Helper
0.17
237080AD1-060 GEN
Solar/Wind Helper
0.294
237038AE2-054 C
Solar/Wind Helper
0.235
235062AE1-101 C1
Solar/Wind Helper
1.433
23779801AA1-109
Solar/Wind Helper
0.166
962771AG1-126 GEN
Solar/Wind Harmer
30.492
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Harmer
0.006
270520AE2-214 GEN
Solar/Wind Harmer
0.011
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
4.271
970879AG2-548 GEN
Solar/Wind Harmer
6.448
970689AG2-444 GEN
Solar/Wind Harmer
14.59
270432AC2-029 GEN
Solar/Wind Harmer
3.168
270269AC2-059
Solar/Wind Harmer
0.004
972203AH1-686 GEN
Adder
2.352
940611AE2-048 GEN
Solar/Wind Harmer
17.483
941391AE2-136 GEN
Solar/Wind Harmer
9.848
270284AF1-227 GEN1
Solar/Wind Harmer
0.009
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
270156DARBY CT1
Adder
9.085
270157DARBY CT2
Adder
9.063
270158DARBY CT3
Adder
8.918
945631AF1-228 GEN
Solar/Wind Harmer
0
253383AE2-342_GEN
Solar/Wind Harmer
0.002
241973AD2-163_GEN1
Solar/Wind Harmer
0.005
943861AF1-054 GEN
Solar/Wind Harmer
2.706
943851AF1-053 GEN
Solar/Wind Harmer
1.874
971985AH1-537 GEN
Solar/Wind Harmer
2.087
270340AC2-060 GEN
Solar/Wind Harmer
0.008
241972AD1-140 GEN
Solar/Wind Harmer
0.755
270367AC2-061_GEN
Solar/Wind Harmer
0.005
253372AE2-315 SEC3
Adder
1.853
253372AE2-315 SEC3
Adder
1.853
270578AF1-285 GEN2
Solar/Wind Harmer
0.455
25306009OHH W.
Adder
2.812
253349AC2-067 GEN
Solar/Wind Harmer
2.136
253400AC2-068 GEN
Solar/Wind Harmer
0.859
252524AE2-267 GEN
Solar/Wind Harmer
0.002
25196408WSDLE3
Adder
8.545
25196308WSDLE2
Adder
8.471
25196208WSDLE1
Adder
8.45
25196708WSDLE6
Adder
8.428
25196508WSDLE4
Adder
8.216
270302AB2-170 GEN
Solar/Wind Harmer
0.004
270317AD1-130_GEN
Solar/Wind Harmer
0.01
23559101PLEAS2
50/50
11.891
23684101S70BUS1
50/50
0.299
23562301OGROV1
50/50
2.291
24721705FLATG2
Adder
24.202
962761AG1-125 GEN
Solar/Wind Harmer
30.492
970149AG2-104 GEN
Solar/Wind Harmer
32.932
970155AG2-107 GEN
Solar/Wind Harmer
19.471
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
270510AE1-227 GEN1
Solar/Wind Harmer
1.892
970947AG2-589 GEN
Solar/Wind Harmer
0.243
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
270349AD2-093_GEN
Solar/Wind Harmer
0.005
927014AC1-188 GEN
Solar/Wind Harmer
0.004
270263AC1-001 GEN
Solar/Wind Harmer
0.716
270159DARBY CT4
Adder
8.94
24686105CER G3
Adder
8.419
24686505CER G6
Adder
8.408
253343AC1-166 GEN
Solar/Wind Harmer
0.003
339221AD2-048_GEN
Solar/Wind Harmer
0.004
966841AG1-555 GEN
Solar/Wind Harmer
0.73
965681AG1-436 GEN
Solar/Wind Harmer
8.059
965791AG1-447 GEN
Solar/Wind Harmer
5.91
270007AE1-245 C
Solar/Wind Harmer
0.002
270216AD2-079_GEN
Solar/Wind Harmer
0.001
247620Y3-023
Adder
0.425
270526AF1-158 GEN
Solar/Wind Harmer
0.008
972043AH1-570 GEN
Solar/Wind Harmer
1.674
972045AH1-571 GEN
Solar/Wind Harmer
1.341
24441505OLIV SLR
Solar/Wind Harmer
0
970241AG2-163 GEN
Solar/Wind Harmer
3.747
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
12.817
961051AF2-396 GEN
Solar/Wind Harmer
8.545
274770LINCOLN ;1U
Adder
7.74
274771LINCOLN ;2U
Adder
7.74
270444AC2-157 GEN1
Solar/Wind Harmer
0.003
971587AH1-292 GEN
Solar/Wind Harmer
4.687
970623AG2-406 GEN
Solar/Wind Harmer
1.169
274808UNIV PK N;4U
Adder
4.563
274803UNIV PARK;6U
Adder
5.329
274888KELLY CRK;1U
Solar/Wind Harmer
0.375
274887GEN-1.85
Solar/Wind Harmer
0.168
276843GEN-1.7
Solar/Wind Harmer
0.206
945391AF1-204 GEN
Solar/Wind Harmer
6.775
958011AF2-095 GEN
Solar/Wind Harmer
9.182
972259AH1-714 GEN
Adder
17.426
241960AC2-195 GEN
Solar/Wind Harmer
0.005
971125AH1-004 GEN
Solar/Wind Harmer
2.546
970107AG2-081 GEN
Solar/Wind Harmer
1.909
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
960161AF2-307 GEN
Solar/Wind Harmer
4.195
944971AF1-162 GEN
Solar/Wind Harmer
6.345
958481AF2-142 GEN
Solar/Wind Harmer
9.506
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.857
971573AH1-285 GEN
Solar/Wind Harmer
1.18
958491AF2-143 GEN
Solar/Wind Harmer
9.485
274879MINONK ;1U
Solar/Wind Harmer
0.267
23585401KL_K28_T16
Solar/Wind Helper
1.442
238120AE2-309 GEN
Solar/Wind Helper
0.483
238175AF1-290_GEN
Solar/Wind Helper
0.13
238169AE2-226 GEN1
Solar/Wind Helper
0.6
238170AE2-226 GEN2
Solar/Wind Helper
0.6
235020AA1-095 C
Solar/Wind Helper
0.045
23777901MDS_W4-102
Solar/Wind Helper
0.151
235063AE1-101 C2
Solar/Wind Helper
1.433
237002AB1-128_GEN
Solar/Wind Helper
0.382
237001AB1-127_GEN
Solar/Wind Helper
0.381
237034AC2-136 C
Solar/Wind Helper
0.194
23777801MSM_W1-116
Solar/Wind Helper
0.098
237025AB1-124 C
Solar/Wind Helper
0.142
237006AB1-125 GEN
Solar/Wind Helper
0.106
962691AG1-118 GEN
Solar/Wind Harmer
7.548
971653AH1-327 GEN
Solar/Wind Harmer
0.947
25196108MFTGT2
Adder
1.467
25196108MFTGT2
Adder
1.362
971673AH1-337 GEN
Solar/Wind Harmer
4.312
971029AG2-637 GEN
Solar/Wind Harmer
9.944
972163AH1-664 GEN
Solar/Wind Harmer
7.37
972165AH1-665 GEN
Solar/Wind Harmer
5.903
270543AE2-219 C
Solar/Wind Harmer
0.004
270240V3-007_GEN2
Solar/Wind Harmer
0.002
24729505KEY G4
Adder
6.141
965101AG1-375 GEN
Solar/Wind Harmer
6.597
945581AF1-223 GEN
Solar/Wind Harmer
0
970115AG2-085 GEN
Solar/Wind Harmer
2.631
270024AE2-089 GEN
Solar/Wind Harmer
0.007
971609AH1-304 GEN
Solar/Wind Harmer
1.074
270071AF1-092 GEN
Solar/Wind Harmer
12.598
270594AE1-207 GEN
Solar/Wind Harmer
7.357
970289AG2-191 GEN
Solar/Wind Harmer
1.247
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
8.837
965051AG1-369 GEN
Solar/Wind Harmer
3.247
971347AH1-153 GEN
Solar/Wind Harmer
9.745
965041AG1-368 GEN
Solar/Wind Harmer
6.496
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.821
971611AH1-305 GEN
Solar/Wind Harmer
3.852
958391AF2-133 GEN
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0.008
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
247607V1-011 GEN
Solar/Wind Harmer
0.001
971771AH1-392 GEN
Solar/Wind Harmer
6.442
971769AH1-391 GEN
Solar/Wind Harmer
7.189
963841AG1-237 GEN
Solar/Wind Harmer
2.789
24477305BRIDGE
Adder
0.321
971619AH1-309 GEN
Solar/Wind Harmer
2.888
274775LINCOLN ;6U
Adder
7.74
274776LINCOLN ;7U
Adder
7.74
274777LINCOLN ;8U
Adder
7.74
274814UNIV PK N;0U
Adder
4.624
274807UNIV PK N;3U
Adder
4.614
274805UNIV PK N;1U
Adder
4.594
274811UNIV PK N;7U
Adder
4.584
972037AH1-567 GEN1
Adder
0.167
960591AF2-350 GEN
Solar/Wind Harmer
6.377
972227AH1-698 GEN1
Adder
2.383
274827FISK ;RP
Adder
7.089
970179AG2-119 GEN
Solar/Wind Harmer
5.69
274687WILL CNTY;4U
Adder
25.484
274687WILL CNTY;4U
Adder
25.484
274731ELWOOD EC;2P
Adder
14.987
274733ELWOOD EC;3P
Adder
14.987
274735ELWOOD EC;4P
Adder
14.987
274728ELWOOD EC;5P
Adder
14.987
970833AG2-524 GEN
Solar/Wind Harmer
6.995
970833AG2-524 GEN
Solar/Wind Harmer
4.664
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
970169AG2-114 GEN
Solar/Wind Harmer
6.327
276868AE1-113 GEN
Solar/Wind Harmer
1.267
276882AE2-255 GEN
Solar/Wind Harmer
0.739
238109AE1-109 GEN2
Solar/Wind Helper
0.102
238110AE1-109 GEN3
Solar/Wind Helper
0.102
238126S14_GEN_1
Solar/Wind Helper
0.764
23750501ELLIOTTS
Solar/Wind Helper
0.636
238152AF2-075_GEN
Solar/Wind Helper
0.611
238208AF1-136 C
Solar/Wind Helper
0.19
23546401DTGZ2-030
Solar/Wind Helper
0.077
237085AD2-009_GEN
Solar/Wind Helper
1.425
3138216PACIFIC
Solar/Wind Helper
0.038
316411AF1-147_GEN1
Solar/Wind Helper
0.754
316415AF1-147_GEN2
Solar/Wind Helper
0.754
253325AC1-069 GEN
Solar/Wind Harmer
0.011
24723205RIVRG3
Adder
18.885
970593AG2-378 GEN
Solar/Wind Harmer
1.575
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.836
253370AE2-315 SEC1
Adder
1.959
253371AE2-315 SEC2
Adder
1.853
270223U2-072_GEN1
Solar/Wind Harmer
0.001
25326309TAIT D
Adder
1.071
960071AF2-298 GEN
Solar/Wind Harmer
3.39
252507AC2-088 GEN
Solar/Wind Harmer
0.308
25194608D.CRK4
Adder
1.592
25196808ZIMRHP
Adder
73.247
270462AD2-086
Solar/Wind Harmer
0.014
25196008MFTGT1
Adder
1.331
970333AG2-219 GEN
Solar/Wind Harmer
4.752
945681AF1-233 GEN
Solar/Wind Harmer
12.498
971995AH1-542 GEN
Solar/Wind Harmer
2.424
247536S-71 GEN
Solar/Wind Harmer
0.266
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.843
965651AG1-433 GEN
Solar/Wind Harmer
1.936
958861AF2-177 GEN
Solar/Wind Harmer
2.859
945371AF1-202 GEN
Solar/Wind Harmer
0.001
270005AE1-210 C O1
Solar/Wind Harmer
1.427
965031AG1-367 GEN
Solar/Wind Harmer
6.586
970773AG2-487 GEN
Solar/Wind Harmer
1.163
970825AG2-519 GEN
Solar/Wind Harmer
2.336
270032AE2-172
Solar/Wind Harmer
4.379
970245AG2-165 GEN
Solar/Wind Harmer
2.844
970291AG2-192 GEN
Solar/Wind Harmer
0.853
970091AG2-072 GEN
Adder
72.107
276903AD2-071 C
Solar/Wind Harmer
7.32
965011AG1-365 GEN
Solar/Wind Harmer
6.533
247521TR3_G114
Solar/Wind Harmer
0.237
270246TR4_N_V150
Solar/Wind Harmer
0.042
965421AG1-410 GEN
Solar/Wind Harmer
19.465
24728605AND G2
Adder
3.565
246936BC-WTG1
Solar/Wind Harmer
0.263
270489AE1-102 GEN1
Solar/Wind Harmer
0.843
24695305TIMB G C
Solar/Wind Harmer
0.002
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.087
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
24791305MDL-5G
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.406
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270063AE2-323 C
Solar/Wind Harmer
0.005
270055AF2-134 C O1
Solar/Wind Harmer
0.005
970373AG2-245 GEN
Solar/Wind Harmer
13.568
339216AC1-074 GEN
Solar/Wind Harmer
0.177
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.002
24639705ELKHART HY
Adder
0.142
963741AG1-226 GEN
Solar/Wind Harmer
15.2
945111AF1-176 GEN
Solar/Wind Harmer
11.453
270505AE1-170 C O1
Solar/Wind Harmer
6.739
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.342
274773LINCOLN ;4U
Adder
7.74
274774LINCOLN ;5U
Adder
7.74
274751CRETE EC ;1U
Adder
7.553
274754CRETE EC ;4U
Adder
7.553
274723RIVER EC ;12
Adder
16.418
270445AC2-157 GEN2
Solar/Wind Harmer
0.003
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.584
276776AD2-060 GEN
Solar/Wind Harmer
0.666
941551AE2-152 GEN
Solar/Wind Harmer
0
274801UNIV PARK;4U
Adder
5.327
274732ELWOOD EC;7P
Adder
8.75
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
939401AE1-172 GEN
Solar/Wind Harmer
4.75
276691AA1-018 GEN1
Solar/Wind Harmer
0.768
944231AF1-091 GEN
Solar/Wind Harmer
1.688
276901AD2-066 C O1
Solar/Wind Harmer
0.006
971997AH1-543 GEN
Solar/Wind Harmer
3.315
23751101LEADS_P59
Solar/Wind Helper
1.597
23751201ROTHROCK
Solar/Wind Helper
0.849
23562501BACKB
Solar/Wind Helper
1.042
23583801GRNGAP
Solar/Wind Helper
4.948
316095T157 G97
Solar/Wind Helper
1.323
238185AF2-356 C
Solar/Wind Helper
2.474
235054AD2-180 GEN
Solar/Wind Helper
1.935
238117U2-030
Solar/Wind Helper
0.318
238108AE1-109 GEN1
Solar/Wind Helper
0.102
235531U2-073 GEN
Solar/Wind Helper
3.033
238147AE2-230_GEN1
Solar/Wind Helper
0.427
238149AF1-291A_GEN
Solar/Wind Helper
0.122
237061AD1-155 GEN
Solar/Wind Helper
0.046
238221AF1-254 C O1
Solar/Wind Helper
0.235
235067AD1-061 GEN
Solar/Wind Helper
0.427
237030AB1-096 C
Solar/Wind Helper
0.061
944201AF1-088_MTX
Adder
106.522
957141AF2-008_MTX
Adder
53.261
CBM West 1LTFEXP_CBM-W1->PJM
CBM
126.393
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.84
MECLTFEXP_MEC->PJM
CLTF
14.465
SIGELTFEXP_SIGE->PJM
CLTF
0.467
LAGNLTFEXP_LAGN->PJM
CLTF
14.169
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.052
TVALTFEXP_TVA->PJM
CLTF
7.036
CPLELTFEXP_CPLE->PJM
CLTF
1.288
CBM West 2LTFEXP_CBM-W2->PJM
CBM
105.476
NYPJM->LTFIMP_NY
CLTF
4.491
LGEELTFEXP_LGEE->PJM
CLTF
6.272
WECLTFEXP_WEC->PJM
CLTF
3.434
AG2-052LTFEXP_AG2-052->PJM
LTF
0.214
AH1-155LTFEXP_AH1-155->PJM
LTF
0.321

Details for 01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line l/o AEP_P4_#8975_05KAMMER 765_MM2_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#8975_05KAMMER 765_MM2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:139.97 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5307.79
MW Contribution:10.51
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
50/50
1217.062
24318905MLG2
50/50
4.656
270471AD2-092_GEN
Solar/Wind Harmer
3.665
970879AG2-548 GEN
Solar/Wind Harmer
6.188
971073AG2-665 GEN
Solar/Wind Harmer
6.188
971073AG2-665 GEN
Solar/Wind Harmer
4.317
946101AF1-275 GEN
Solar/Wind Harmer
1.512
24685805CER G1
Adder
8.199
24685905CER G2
Adder
8.199
972269AH1-719 GEN
Adder
2.268
24723005RIVRG1
Adder
18.473
24723105RIVRG2
Adder
18.473
942861AE2-305 GEN
Solar/Wind Harmer
7.629
270518AE2-148 GEN
Solar/Wind Harmer
11.837
970077AG2-063 GEN
Solar/Wind Harmer
5.262
962581AG1-107 GEN
Solar/Wind Harmer
4.827
961491AF2-440 GEN
Solar/Wind Harmer
2.006
972159AH1-661 GEN
Adder
0.952
253394AE2-221_GEN
Solar/Wind Harmer
4.338
253398AE2-221_GEN2
Solar/Wind Harmer
4.338
253317AC1-085 GEN4
Solar/Wind Harmer
7.992
270186AC1-089 GEN
Solar/Wind Harmer
5.819
25326109MON D
Adder
1.252
253370AE2-315 SEC1
Adder
1.906
25322209TAIT E
Adder
9.269
25322209TAIT E
Adder
9.061
25183208HLCRTG
Solar/Wind Harmer
5.751
964601AG1-323 GEN
Solar/Wind Harmer
3.011
964601AG1-323 GEN
Solar/Wind Harmer
1.401
252509AD1-136 GEN
Solar/Wind Harmer
0.243
252519AF1-045_GEN
Solar/Wind Harmer
5.748
252516AE2-318_GEN
Solar/Wind Harmer
4.385
270224U2-072_GEN2
Solar/Wind Harmer
1.871
270227U2-072_GEN3
Solar/Wind Harmer
1.871
270228U2-072_GEN4
Solar/Wind Harmer
1.871
270231U2-072_GEN5
Solar/Wind Harmer
1.871
938701AE1-092 GEN
Solar/Wind Harmer
19.52
25194408D.CRK1
Adder
7.132
25194508D.CRK3
Adder
1.333
253378AE2-206_GEN
Solar/Wind Harmer
3.382
276820AF1-078_GEN
Solar/Wind Harmer
1.502
25326509SID D
Adder
1.231
970239AG2-162 GEN
Solar/Wind Harmer
10.183
24728805RICHG1
Adder
3.489
24728905RICHG2
Adder
3.489
970883AG2-550 GEN
Solar/Wind Harmer
9.215
970885AG2-551 GEN
Solar/Wind Harmer
2.143
270383AD1-128 GEN
Solar/Wind Harmer
5.623
24379505HDWTR1G C
Solar/Wind Harmer
7.277
270209AC1-174_GEN
Solar/Wind Harmer
5.136
926881AC1-175 GEN
Solar/Wind Harmer
5.136
247621Y3-024
Adder
0.222
944541AF1-119 GEN
Solar/Wind Harmer
3.847
960971AF2-388 GEN
Solar/Wind Harmer
10.038
270201AC2-176 GEN
Solar/Wind Harmer
4.717
964611AG1-324 GEN
Solar/Wind Harmer
1.082
964611AG1-324 GEN
Solar/Wind Harmer
0.48
970825AG2-519 GEN
Solar/Wind Harmer
9.671
960441AF2-335 GEN
Solar/Wind Harmer
9.16
247620Y3-023
Adder
0.412
274770LINCOLN ;1U
Adder
7.514
274771LINCOLN ;2U
Adder
7.514
238175AF1-290_GEN
Solar/Wind Helper
0.126
238169AE2-226 GEN1
Solar/Wind Helper
0.582
238170AE2-226 GEN2
Solar/Wind Helper
0.582
235020AA1-095 C
Solar/Wind Helper
0.044
23777901MDS_W4-102
Solar/Wind Helper
0.146
238120AE2-309 GEN
Solar/Wind Helper
0.406
237034AC2-136 C
Solar/Wind Helper
0.189
237002AB1-128_GEN
Solar/Wind Helper
0.369
235063AE1-101 C2
Solar/Wind Helper
1.38
237001AB1-127_GEN
Solar/Wind Helper
0.368
23777801MSM_W1-116
Solar/Wind Helper
0.096
270599AE1-208 GEN
Solar/Wind Harmer
0.76
270031AE2-169
Solar/Wind Harmer
0.76
962771AG1-126 GEN
Solar/Wind Harmer
34.974
270330AC1-082 GEN2
Solar/Wind Harmer
0.789
270329AC1-082 GEN1
Solar/Wind Harmer
0.465
270054AF2-122 C O1
Solar/Wind Harmer
3.29
970879AG2-548 GEN
Solar/Wind Harmer
4.317
940611AE2-048 GEN
Solar/Wind Harmer
22.053
941391AE2-136 GEN
Solar/Wind Harmer
11.427
270520AE2-214 GEN
Solar/Wind Harmer
6.059
270459AD2-067 GEN
Solar/Wind Harmer
8.36
961821AG1-024 GEN
Solar/Wind Harmer
8.487
972203AH1-686 GEN
Adder
2.298
270432AC2-029 GEN
Solar/Wind Harmer
6.982
970689AG2-444 GEN
Solar/Wind Harmer
16.256
270269AC2-059
Solar/Wind Harmer
9.3
270156DARBY CT1
Adder
8.832
270157DARBY CT2
Adder
8.81
270158DARBY CT3
Adder
8.67
945631AF1-228 GEN
Solar/Wind Harmer
4.621
270284AF1-227 GEN1
Solar/Wind Harmer
5.57
270286AF1-227 GEN2
Solar/Wind Harmer
2.061
270287AF1-227 GEN3
Solar/Wind Harmer
2.061
971985AH1-537 GEN
Solar/Wind Harmer
17.522
253383AE2-342_GEN
Solar/Wind Harmer
0.869
241973AD2-163_GEN1
Solar/Wind Harmer
1.944
943861AF1-054 GEN
Solar/Wind Harmer
3.765
943851AF1-053 GEN
Solar/Wind Harmer
1.82
270340AC2-060 GEN
Solar/Wind Harmer
2.96
24477305BRIDGE
Adder
0.338
241972AD1-140 GEN
Solar/Wind Harmer
4.309
270367AC2-061_GEN
Solar/Wind Harmer
3.048
253372AE2-315 SEC3
Adder
1.803
253372AE2-315 SEC3
Adder
1.803
25306009OHH W.
Adder
2.735
270578AF1-285 GEN2
Solar/Wind Harmer
0.44
253349AC2-067 GEN
Solar/Wind Harmer
4.712
253400AC2-068 GEN
Solar/Wind Harmer
1.895
252524AE2-267 GEN
Solar/Wind Harmer
1.487
25196408WSDLE3
Adder
8.32
25196308WSDLE2
Adder
8.248
25196208WSDLE1
Adder
8.227
25196708WSDLE6
Adder
8.207
25196508WSDLE4
Adder
8
270302AB2-170 GEN
Solar/Wind Harmer
7.824
270317AD1-130_GEN
Solar/Wind Harmer
3
944031AF1-071 GEN
Solar/Wind Harmer
0.936
25196108MFTGT2
Adder
1.429
25196108MFTGT2
Adder
1.327
972163AH1-664 GEN
Solar/Wind Harmer
9.252
972165AH1-665 GEN
Solar/Wind Harmer
7.402
971673AH1-337 GEN
Solar/Wind Harmer
4.251
971029AG2-637 GEN
Solar/Wind Harmer
13.852
270543AE2-219 C
Solar/Wind Harmer
4.719
270240V3-007_GEN2
Solar/Wind Harmer
5.693
24729505KEY G4
Adder
5.961
958711AF2-162 GEN
Solar/Wind Harmer
0.929
965101AG1-375 GEN
Solar/Wind Harmer
9.182
945581AF1-223 GEN
Solar/Wind Harmer
4.163
961761AG1-017 GEN
Solar/Wind Harmer
0.393
970115AG2-085 GEN
Solar/Wind Harmer
3.664
274775LINCOLN ;6U
Adder
7.514
274776LINCOLN ;7U
Adder
7.514
274777LINCOLN ;8U
Adder
7.514
274814UNIV PK N;0U
Adder
4.489
274807UNIV PK N;3U
Adder
4.479
274805UNIV PK N;1U
Adder
4.459
274811UNIV PK N;7U
Adder
0.697
238152AF2-075_GEN
Solar/Wind Helper
0.593
23546401DTGZ2-030
Solar/Wind Helper
0.075
238109AE1-109 GEN2
Solar/Wind Helper
0.088
238110AE1-109 GEN3
Solar/Wind Helper
0.088
238208AF1-136 C
Solar/Wind Helper
0.18
237085AD2-009_GEN
Solar/Wind Helper
1.367
238126S14_GEN_1
Solar/Wind Helper
0.641
23559101PLEAS2
50/50
11.213
23684101S70BUS1
50/50
0.313
23562301OGROV1
50/50
2.427
24721705FLATG2
Adder
23.442
962761AG1-125 GEN
Solar/Wind Harmer
34.974
970149AG2-104 GEN
Solar/Wind Harmer
43.193
970155AG2-107 GEN
Solar/Wind Harmer
15.25
270510AE1-227 GEN1
Solar/Wind Harmer
2.645
960001AF2-291 GEN
Solar/Wind Harmer
3.152
970947AG2-589 GEN
Solar/Wind Harmer
2.059
270331AC1-082 GEN3
Solar/Wind Harmer
0.466
927014AC1-188 GEN
Solar/Wind Harmer
1.606
270349AD2-093_GEN
Solar/Wind Harmer
3.665
270263AC1-001 GEN
Solar/Wind Harmer
1.044
24686105CER G3
Adder
8.253
24686505CER G6
Adder
8.242
270159DARBY CT4
Adder
8.691
24723205RIVRG3
Adder
18.473
253343AC1-166 GEN
Solar/Wind Harmer
1.064
253325AC1-069 GEN
Solar/Wind Harmer
1.027
970593AG2-378 GEN
Solar/Wind Harmer
1.949
253432AC1-085 GEN2
Solar/Wind Harmer
0.255
946171AF1-282 GEN
Solar/Wind Harmer
9.541
253370AE2-315 SEC1
Adder
1.906
253371AE2-315 SEC2
Adder
1.803
25326309TAIT D
Adder
1.041
960071AF2-298 GEN
Solar/Wind Harmer
4.732
252507AC2-088 GEN
Solar/Wind Harmer
1.7
270223U2-072_GEN1
Solar/Wind Harmer
1.871
270578AF1-285 GEN2
Solar/Wind Harmer
1.144
270391AF1-285 GEN3
Solar/Wind Harmer
1.144
25194608D.CRK4
Adder
1.55
25196808ZIMRHP
Adder
71.347
270462AD2-086
Solar/Wind Harmer
6.509
25196008MFTGT1
Adder
1.296
970333AG2-219 GEN
Solar/Wind Harmer
29.222
945681AF1-233 GEN
Solar/Wind Harmer
17.467
942081AE2-220 GEN
Solar/Wind Harmer
5.883
270239V3-007_GEN1
Solar/Wind Harmer
1.584
247536S-71 GEN
Solar/Wind Harmer
3.724
965651AG1-433 GEN
Solar/Wind Harmer
5.019
958861AF2-177 GEN
Solar/Wind Harmer
10.036
945371AF1-202 GEN
Solar/Wind Harmer
6.405
971995AH1-542 GEN
Solar/Wind Harmer
10.093
270005AE1-210 C O1
Solar/Wind Harmer
5.013
965031AG1-367 GEN
Solar/Wind Harmer
9.173
970825AG2-519 GEN
Solar/Wind Harmer
2.158
970091AG2-072 GEN
Adder
70.193
24728605AND G2
Adder
3.466
24639705ELKHART HY
Adder
0.137
274773LINCOLN ;4U
Adder
7.514
274774LINCOLN ;5U
Adder
7.514
274751CRETE EC ;1U
Adder
7.332
274754CRETE EC ;4U
Adder
7.332
274723RIVER EC ;12
Adder
15.938
274812UNIV PK N;8U
Adder
4.45
23583801GRNGAP
Solar/Wind Helper
4.858
316095T157 G97
Solar/Wind Helper
1.299
238147AE2-230_GEN1
Solar/Wind Helper
0.415
238149AF1-291A_GEN
Solar/Wind Helper
0.119
238108AE1-109 GEN1
Solar/Wind Helper
0.088
237061AD1-155 GEN
Solar/Wind Helper
0.045
238185AF2-356 C
Solar/Wind Helper
1.996
238221AF1-254 C O1
Solar/Wind Helper
0.228
235067AD1-061 GEN
Solar/Wind Helper
0.412
235531U2-073 GEN
Solar/Wind Helper
2.523
238117U2-030
Solar/Wind Helper
0.26
23559001PLEAS1
50/50
11.213
23684201S70BUS2
50/50
0.319
23562401OGROV2
50/50
2.411
24318805MLG1
50/50
6.319
24721905FLATG4
Adder
23.442
970153AG2-106 GEN
Solar/Wind Harmer
15.25
270512AE1-227 GEN2
Solar/Wind Harmer
2.245
971191AH1-055 GEN
Solar/Wind Harmer
22.406
957541AF2-048 GEN
Solar/Wind Harmer
1.601
270291AC1-194 GEN
Solar/Wind Harmer
10.629
961921AG1-034 GEN
Solar/Wind Harmer
12.731
960801AF2-371 GEN
Solar/Wind Harmer
2.533
964871AG1-351 GEN
Solar/Wind Harmer
1.749
270273AD2-016 GEN
Solar/Wind Harmer
2.659
972173AH1-669 GEN
Solar/Wind Harmer
4.984
241955AC1-078 GEN
Solar/Wind Harmer
7.382
24686205CER G4
Adder
8.21
24686405CER G5
Adder
8.177
942051AE2-217 GEN
Solar/Wind Harmer
17.654
253338AC1-165 GEN
Solar/Wind Harmer
1.064
253333AC1-068 GEN
Solar/Wind Harmer
1.027
241974AD2-163_GEN2
Solar/Wind Harmer
1.944
253415AE1-040 GEN
Solar/Wind Harmer
1.1
970605AG2-385 GEN
Solar/Wind Harmer
5.262
253406AD2-031_GEN
Solar/Wind Harmer
1.228
253316AC1-085 GEN3
Solar/Wind Harmer
7.992
253433AC1-085 GEN1
Solar/Wind Harmer
5.073
946181AF1-283 GEN
Solar/Wind Harmer
12.404
253303V4-073 C
Solar/Wind Harmer
0.11
253370AE2-315 SEC1
Adder
1.906
253371AE2-315 SEC2
Adder
1.803
942871AE2-306 GEN
Solar/Wind Harmer
0.858
270391AF1-285 GEN3
Solar/Wind Harmer
0.44
252510AF1-249 C
Solar/Wind Harmer
0.395
25196608WSDLE5
Adder
8.083
25194608D.CRK4
Adder
1.55
270485AE1-090_GEN
Solar/Wind Harmer
0.566
270222AC2-111 GEN
Solar/Wind Harmer
7.593
25196008MFTGT1
Adder
1.255
970243AG2-164 GEN
Solar/Wind Harmer
23.909
970519AG2-331 GEN
Solar/Wind Harmer
16.063
970699AG2-449 GEN
Solar/Wind Harmer
10.626
972167AH1-666 GEN
Solar/Wind Harmer
7.416
958171AF2-111 GEN
Solar/Wind Harmer
23.159
270437AC2-090 C
Solar/Wind Harmer
5.138
944531AF1-118 GEN
Solar/Wind Harmer
32.165
962031AG1-047 GEN
Solar/Wind Harmer
2.774
957741AF2-068 GEN
Solar/Wind Harmer
13.765
270356AE2-297 GEN
Solar/Wind Harmer
4.184
946031AF1-268 GEN
Solar/Wind Harmer
7.613
958821AF2-173 GEN
Solar/Wind Harmer
12.842
270004AE1-209 GEN
Solar/Wind Harmer
5.013
24728705AND G3
Adder
7.25
24728505AND G1
Adder
3.466
24642205MAYFLWER
Adder
0.568
274772LINCOLN ;3U
Adder
7.514
274752CRETE EC ;2U
Adder
7.332
274753CRETE EC ;3U
Adder
7.332
274724RIVER EC ;11
Adder
15.751
316097T157 G90
Solar/Wind Helper
1.299
964991AG1-363 GEN
Solar/Wind Helper
4.135
238148AE2-230_GEN2
Solar/Wind Helper
0.417
23750701CROSSCHOOL
Solar/Wind Helper
1.155
237080AD1-060 GEN
Solar/Wind Helper
0.284
237038AE2-054 C
Solar/Wind Helper
0.226
235062AE1-101 C1
Solar/Wind Helper
1.38
238127S14_GEN_2
Solar/Wind Helper
0.641
23779801AA1-109
Solar/Wind Helper
0.162
238118U2-030_1
Solar/Wind Helper
0.26
944201AF1-088_MTX
Adder
103.64
957141AF2-008_MTX
Adder
51.82
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.614
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.188
MECLTFEXP_MEC->PJM
CLTF
14.066
SIGELTFEXP_SIGE->PJM
CLTF
0.455
LAGNLTFEXP_LAGN->PJM
CLTF
13.832
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.925
TVALTFEXP_TVA->PJM
CLTF
6.876
CPLELTFEXP_CPLE->PJM
CLTF
1.286
CBM West 2LTFEXP_CBM-W2->PJM
CBM
102.798
NYPJM->LTFIMP_NY
CLTF
4.417
LGEELTFEXP_LGEE->PJM
CLTF
6.111
WECLTFEXP_WEC->PJM
CLTF
3.336
AG2-052LTFEXP_AG2-052->PJM
LTF
0.208
AH1-155LTFEXP_AH1-155->PJM
LTF
0.312

Details for 01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line l/o AP_P2-3_WP-500-DRT7A_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-500-DRT7A_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:139.96 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5307.1
MW Contribution:10.51
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
50/50
1217.062
962771AG1-126 GEN
Solar/Wind Harmer
34.974
270330AC1-082 GEN2
Solar/Wind Harmer
0.789
270329AC1-082 GEN1
Solar/Wind Harmer
0.465
270054AF2-122 C O1
Solar/Wind Harmer
3.29
970879AG2-548 GEN
Solar/Wind Harmer
4.317
940611AE2-048 GEN
Solar/Wind Harmer
22.053
941391AE2-136 GEN
Solar/Wind Harmer
11.427
270520AE2-214 GEN
Solar/Wind Harmer
6.059
23559101PLEAS2
50/50
11.213
23684101S70BUS1
50/50
0.313
23562301OGROV1
50/50
2.427
24721705FLATG2
Adder
23.442
962761AG1-125 GEN
Solar/Wind Harmer
34.974
970149AG2-104 GEN
Solar/Wind Harmer
43.193
970155AG2-107 GEN
Solar/Wind Harmer
15.25
270510AE1-227 GEN1
Solar/Wind Harmer
2.645
960001AF2-291 GEN
Solar/Wind Harmer
3.152
970947AG2-589 GEN
Solar/Wind Harmer
2.059
270331AC1-082 GEN3
Solar/Wind Harmer
0.466
927014AC1-188 GEN
Solar/Wind Harmer
1.606
270349AD2-093_GEN
Solar/Wind Harmer
3.665
270263AC1-001 GEN
Solar/Wind Harmer
1.044
24686105CER G3
Adder
8.253
24686505CER G6
Adder
8.242
270159DARBY CT4
Adder
8.691
24723205RIVRG3
Adder
18.473
253343AC1-166 GEN
Solar/Wind Harmer
1.064
253325AC1-069 GEN
Solar/Wind Harmer
1.027
970593AG2-378 GEN
Solar/Wind Harmer
1.949
253432AC1-085 GEN2
Solar/Wind Harmer
0.255
946171AF1-282 GEN
Solar/Wind Harmer
9.541
253370AE2-315 SEC1
Adder
1.906
253371AE2-315 SEC2
Adder
1.803
25326309TAIT D
Adder
1.041
960071AF2-298 GEN
Solar/Wind Harmer
4.732
252507AC2-088 GEN
Solar/Wind Harmer
1.7
270223U2-072_GEN1
Solar/Wind Harmer
1.871
270578AF1-285 GEN2
Solar/Wind Harmer
1.144
270391AF1-285 GEN3
Solar/Wind Harmer
1.144
25194608D.CRK4
Adder
1.55
25196808ZIMRHP
Adder
71.347
270462AD2-086
Solar/Wind Harmer
6.509
25196008MFTGT1
Adder
1.296
970333AG2-219 GEN
Solar/Wind Harmer
29.222
945681AF1-233 GEN
Solar/Wind Harmer
17.467
942081AE2-220 GEN
Solar/Wind Harmer
5.883
270239V3-007_GEN1
Solar/Wind Harmer
1.584
247536S-71 GEN
Solar/Wind Harmer
3.724
965651AG1-433 GEN
Solar/Wind Harmer
5.019
958861AF2-177 GEN
Solar/Wind Harmer
10.036
945371AF1-202 GEN
Solar/Wind Harmer
6.405
971995AH1-542 GEN
Solar/Wind Harmer
10.093
270005AE1-210 C O1
Solar/Wind Harmer
5.013
965031AG1-367 GEN
Solar/Wind Harmer
9.173
970825AG2-519 GEN
Solar/Wind Harmer
2.158
970091AG2-072 GEN
Adder
70.193
24728605AND G2
Adder
3.466
24639705ELKHART HY
Adder
0.137
274773LINCOLN ;4U
Adder
7.514
274774LINCOLN ;5U
Adder
7.514
274751CRETE EC ;1U
Adder
7.332
274754CRETE EC ;4U
Adder
7.332
274723RIVER EC ;12
Adder
15.938
274812UNIV PK N;8U
Adder
4.45
23583801GRNGAP
Solar/Wind Helper
4.858
316095T157 G97
Solar/Wind Helper
1.299
238147AE2-230_GEN1
Solar/Wind Helper
0.415
238149AF1-291A_GEN
Solar/Wind Helper
0.119
238108AE1-109 GEN1
Solar/Wind Helper
0.088
237061AD1-155 GEN
Solar/Wind Helper
0.045
238185AF2-356 C
Solar/Wind Helper
1.996
238221AF1-254 C O1
Solar/Wind Helper
0.228
235067AD1-061 GEN
Solar/Wind Helper
0.412
235531U2-073 GEN
Solar/Wind Helper
2.523
238117U2-030
Solar/Wind Helper
0.26
23559001PLEAS1
50/50
11.213
23684201S70BUS2
50/50
0.319
23562401OGROV2
50/50
2.411
24318805MLG1
50/50
6.319
24721905FLATG4
Adder
23.442
970153AG2-106 GEN
Solar/Wind Harmer
15.25
270512AE1-227 GEN2
Solar/Wind Harmer
2.245
971191AH1-055 GEN
Solar/Wind Harmer
22.406
957541AF2-048 GEN
Solar/Wind Harmer
1.601
270291AC1-194 GEN
Solar/Wind Harmer
10.629
961921AG1-034 GEN
Solar/Wind Harmer
12.731
960801AF2-371 GEN
Solar/Wind Harmer
2.533
964871AG1-351 GEN
Solar/Wind Harmer
1.749
270273AD2-016 GEN
Solar/Wind Harmer
2.659
972173AH1-669 GEN
Solar/Wind Harmer
4.984
241955AC1-078 GEN
Solar/Wind Harmer
7.382
24686205CER G4
Adder
8.21
24686405CER G5
Adder
8.177
942051AE2-217 GEN
Solar/Wind Harmer
17.654
253338AC1-165 GEN
Solar/Wind Harmer
1.064
253333AC1-068 GEN
Solar/Wind Harmer
1.027
241974AD2-163_GEN2
Solar/Wind Harmer
1.944
253415AE1-040 GEN
Solar/Wind Harmer
1.1
970605AG2-385 GEN
Solar/Wind Harmer
5.262
253406AD2-031_GEN
Solar/Wind Harmer
1.228
253316AC1-085 GEN3
Solar/Wind Harmer
7.992
253433AC1-085 GEN1
Solar/Wind Harmer
5.073
946181AF1-283 GEN
Solar/Wind Harmer
12.404
253303V4-073 C
Solar/Wind Harmer
0.11
253370AE2-315 SEC1
Adder
1.906
253371AE2-315 SEC2
Adder
1.803
942871AE2-306 GEN
Solar/Wind Harmer
0.858
270391AF1-285 GEN3
Solar/Wind Harmer
0.44
252510AF1-249 C
Solar/Wind Harmer
0.395
25196608WSDLE5
Adder
8.083
25194608D.CRK4
Adder
1.55
270485AE1-090_GEN
Solar/Wind Harmer
0.566
270222AC2-111 GEN
Solar/Wind Harmer
7.593
25196008MFTGT1
Adder
1.255
970243AG2-164 GEN
Solar/Wind Harmer
23.909
970519AG2-331 GEN
Solar/Wind Harmer
16.063
970699AG2-449 GEN
Solar/Wind Harmer
10.626
972167AH1-666 GEN
Solar/Wind Harmer
7.416
958171AF2-111 GEN
Solar/Wind Harmer
23.159
270437AC2-090 C
Solar/Wind Harmer
5.138
944531AF1-118 GEN
Solar/Wind Harmer
32.165
962031AG1-047 GEN
Solar/Wind Harmer
2.774
957741AF2-068 GEN
Solar/Wind Harmer
13.765
270356AE2-297 GEN
Solar/Wind Harmer
4.184
946031AF1-268 GEN
Solar/Wind Harmer
7.613
958821AF2-173 GEN
Solar/Wind Harmer
12.842
270004AE1-209 GEN
Solar/Wind Harmer
5.013
24728705AND G3
Adder
7.25
24728505AND G1
Adder
3.466
24642205MAYFLWER
Adder
0.568
274772LINCOLN ;3U
Adder
7.514
274752CRETE EC ;2U
Adder
7.332
274753CRETE EC ;3U
Adder
7.332
274724RIVER EC ;11
Adder
15.751
316097T157 G90
Solar/Wind Helper
1.299
964991AG1-363 GEN
Solar/Wind Helper
4.135
238148AE2-230_GEN2
Solar/Wind Helper
0.417
23750701CROSSCHOOL
Solar/Wind Helper
1.155
237080AD1-060 GEN
Solar/Wind Helper
0.284
237038AE2-054 C
Solar/Wind Helper
0.226
235062AE1-101 C1
Solar/Wind Helper
1.38
238127S14_GEN_2
Solar/Wind Helper
0.641
23779801AA1-109
Solar/Wind Helper
0.162
238118U2-030_1
Solar/Wind Helper
0.26
24318905MLG2
50/50
4.656
270471AD2-092_GEN
Solar/Wind Harmer
3.665
970879AG2-548 GEN
Solar/Wind Harmer
6.188
971073AG2-665 GEN
Solar/Wind Harmer
6.188
971073AG2-665 GEN
Solar/Wind Harmer
4.317
946101AF1-275 GEN
Solar/Wind Harmer
1.512
24685805CER G1
Adder
8.199
24685905CER G2
Adder
8.199
972269AH1-719 GEN
Adder
2.268
24723005RIVRG1
Adder
18.473
24723105RIVRG2
Adder
18.473
942861AE2-305 GEN
Solar/Wind Harmer
7.629
270518AE2-148 GEN
Solar/Wind Harmer
11.837
970077AG2-063 GEN
Solar/Wind Harmer
5.262
962581AG1-107 GEN
Solar/Wind Harmer
4.827
961491AF2-440 GEN
Solar/Wind Harmer
2.006
972159AH1-661 GEN
Adder
0.952
253394AE2-221_GEN
Solar/Wind Harmer
4.338
253398AE2-221_GEN2
Solar/Wind Harmer
4.338
253317AC1-085 GEN4
Solar/Wind Harmer
7.992
270186AC1-089 GEN
Solar/Wind Harmer
5.819
25326109MON D
Adder
1.252
253370AE2-315 SEC1
Adder
1.906
25322209TAIT E
Adder
9.269
25322209TAIT E
Adder
9.061
25183208HLCRTG
Solar/Wind Harmer
5.751
964601AG1-323 GEN
Solar/Wind Harmer
3.011
964601AG1-323 GEN
Solar/Wind Harmer
1.401
252509AD1-136 GEN
Solar/Wind Harmer
0.243
252519AF1-045_GEN
Solar/Wind Harmer
5.748
252516AE2-318_GEN
Solar/Wind Harmer
4.385
270224U2-072_GEN2
Solar/Wind Harmer
1.871
270227U2-072_GEN3
Solar/Wind Harmer
1.871
270228U2-072_GEN4
Solar/Wind Harmer
1.871
270231U2-072_GEN5
Solar/Wind Harmer
1.871
938701AE1-092 GEN
Solar/Wind Harmer
19.52
25194408D.CRK1
Adder
7.132
25194508D.CRK3
Adder
1.333
253378AE2-206_GEN
Solar/Wind Harmer
3.382
276820AF1-078_GEN
Solar/Wind Harmer
1.502
25326509SID D
Adder
1.231
970239AG2-162 GEN
Solar/Wind Harmer
10.183
24728805RICHG1
Adder
3.489
24728905RICHG2
Adder
3.489
970883AG2-550 GEN
Solar/Wind Harmer
9.215
970885AG2-551 GEN
Solar/Wind Harmer
2.143
270383AD1-128 GEN
Solar/Wind Harmer
5.623
24379505HDWTR1G C
Solar/Wind Harmer
7.277
270209AC1-174_GEN
Solar/Wind Harmer
5.136
926881AC1-175 GEN
Solar/Wind Harmer
5.136
247621Y3-024
Adder
0.222
944541AF1-119 GEN
Solar/Wind Harmer
3.847
960971AF2-388 GEN
Solar/Wind Harmer
10.038
270201AC2-176 GEN
Solar/Wind Harmer
4.717
964611AG1-324 GEN
Solar/Wind Harmer
1.082
964611AG1-324 GEN
Solar/Wind Harmer
0.48
970825AG2-519 GEN
Solar/Wind Harmer
9.671
960441AF2-335 GEN
Solar/Wind Harmer
9.16
247620Y3-023
Adder
0.412
274770LINCOLN ;1U
Adder
7.514
274771LINCOLN ;2U
Adder
7.514
238175AF1-290_GEN
Solar/Wind Helper
0.126
238169AE2-226 GEN1
Solar/Wind Helper
0.582
238170AE2-226 GEN2
Solar/Wind Helper
0.582
235020AA1-095 C
Solar/Wind Helper
0.044
23777901MDS_W4-102
Solar/Wind Helper
0.146
238120AE2-309 GEN
Solar/Wind Helper
0.406
237034AC2-136 C
Solar/Wind Helper
0.189
237002AB1-128_GEN
Solar/Wind Helper
0.369
235063AE1-101 C2
Solar/Wind Helper
1.38
237001AB1-127_GEN
Solar/Wind Helper
0.368
23777801MSM_W1-116
Solar/Wind Helper
0.096
270599AE1-208 GEN
Solar/Wind Harmer
0.76
270031AE2-169
Solar/Wind Harmer
0.76
270459AD2-067 GEN
Solar/Wind Harmer
8.36
961821AG1-024 GEN
Solar/Wind Harmer
8.487
972203AH1-686 GEN
Adder
2.298
270432AC2-029 GEN
Solar/Wind Harmer
6.982
970689AG2-444 GEN
Solar/Wind Harmer
16.256
270269AC2-059
Solar/Wind Harmer
9.3
270156DARBY CT1
Adder
8.832
270157DARBY CT2
Adder
8.81
270158DARBY CT3
Adder
8.67
945631AF1-228 GEN
Solar/Wind Harmer
4.621
270284AF1-227 GEN1
Solar/Wind Harmer
5.57
270286AF1-227 GEN2
Solar/Wind Harmer
2.061
270287AF1-227 GEN3
Solar/Wind Harmer
2.061
971985AH1-537 GEN
Solar/Wind Harmer
17.522
253383AE2-342_GEN
Solar/Wind Harmer
0.869
241973AD2-163_GEN1
Solar/Wind Harmer
1.944
943861AF1-054 GEN
Solar/Wind Harmer
3.765
943851AF1-053 GEN
Solar/Wind Harmer
1.82
270340AC2-060 GEN
Solar/Wind Harmer
2.96
24477305BRIDGE
Adder
0.338
241972AD1-140 GEN
Solar/Wind Harmer
4.309
270367AC2-061_GEN
Solar/Wind Harmer
3.048
253372AE2-315 SEC3
Adder
1.803
253372AE2-315 SEC3
Adder
1.803
25306009OHH W.
Adder
2.735
270578AF1-285 GEN2
Solar/Wind Harmer
0.44
253349AC2-067 GEN
Solar/Wind Harmer
4.712
253400AC2-068 GEN
Solar/Wind Harmer
1.895
252524AE2-267 GEN
Solar/Wind Harmer
1.487
25196408WSDLE3
Adder
8.32
25196308WSDLE2
Adder
8.248
25196208WSDLE1
Adder
8.227
25196708WSDLE6
Adder
8.207
25196508WSDLE4
Adder
8
270302AB2-170 GEN
Solar/Wind Harmer
7.824
270317AD1-130_GEN
Solar/Wind Harmer
3
944031AF1-071 GEN
Solar/Wind Harmer
0.936
25196108MFTGT2
Adder
1.429
25196108MFTGT2
Adder
1.327
972163AH1-664 GEN
Solar/Wind Harmer
9.252
972165AH1-665 GEN
Solar/Wind Harmer
7.402
971673AH1-337 GEN
Solar/Wind Harmer
4.251
971029AG2-637 GEN
Solar/Wind Harmer
13.852
270543AE2-219 C
Solar/Wind Harmer
4.719
270240V3-007_GEN2
Solar/Wind Harmer
5.693
24729505KEY G4
Adder
5.961
958711AF2-162 GEN
Solar/Wind Harmer
0.929
965101AG1-375 GEN
Solar/Wind Harmer
9.182
945581AF1-223 GEN
Solar/Wind Harmer
4.163
961761AG1-017 GEN
Solar/Wind Harmer
0.393
970115AG2-085 GEN
Solar/Wind Harmer
3.664
274775LINCOLN ;6U
Adder
7.514
274776LINCOLN ;7U
Adder
7.514
274777LINCOLN ;8U
Adder
7.514
274814UNIV PK N;0U
Adder
4.489
274807UNIV PK N;3U
Adder
4.479
274805UNIV PK N;1U
Adder
4.459
274811UNIV PK N;7U
Adder
0.697
238152AF2-075_GEN
Solar/Wind Helper
0.593
23546401DTGZ2-030
Solar/Wind Helper
0.075
238109AE1-109 GEN2
Solar/Wind Helper
0.088
238110AE1-109 GEN3
Solar/Wind Helper
0.088
238208AF1-136 C
Solar/Wind Helper
0.18
237085AD2-009_GEN
Solar/Wind Helper
1.367
238126S14_GEN_1
Solar/Wind Helper
0.641
944201AF1-088_MTX
Adder
103.64
957141AF2-008_MTX
Adder
51.82
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.614
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.188
MECLTFEXP_MEC->PJM
CLTF
14.066
SIGELTFEXP_SIGE->PJM
CLTF
0.455
LAGNLTFEXP_LAGN->PJM
CLTF
13.832
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.925
TVALTFEXP_TVA->PJM
CLTF
6.876
CPLELTFEXP_CPLE->PJM
CLTF
1.286
CBM West 2LTFEXP_CBM-W2->PJM
CBM
102.798
NYPJM->LTFIMP_NY
CLTF
4.417
LGEELTFEXP_LGEE->PJM
CLTF
6.111
WECLTFEXP_WEC->PJM
CLTF
3.336
AG2-052LTFEXP_AG2-052->PJM
LTF
0.208
AH1-155LTFEXP_AH1-155->PJM
LTF
0.312

Details for 01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line l/o AP_P2-3_WP-500-DRT10A_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-500-DRT10A_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:139.86 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5303.43
MW Contribution:10.59
Bus #Bus NameTypeMW Contribution
23559101PLEAS2
50/50
11.24
23684101S70BUS1
50/50
0.316
23562301OGROV1
50/50
2.447
24721705FLATG2
Adder
23.592
962761AG1-125 GEN
Solar/Wind Harmer
35.245
970149AG2-104 GEN
Solar/Wind Harmer
43.528
970155AG2-107 GEN
Solar/Wind Harmer
15.368
270510AE1-227 GEN1
Solar/Wind Harmer
2.678
960001AF2-291 GEN
Solar/Wind Harmer
3.176
970947AG2-589 GEN
Solar/Wind Harmer
2.074
270331AC1-082 GEN3
Solar/Wind Harmer
0.469
927014AC1-188 GEN
Solar/Wind Harmer
1.618
270349AD2-093_GEN
Solar/Wind Harmer
3.698
270263AC1-001 GEN
Solar/Wind Harmer
1.052
270159DARBY CT4
Adder
8.767
24686105CER G3
Adder
8.308
24686505CER G6
Adder
8.298
24723205RIVRG3
Adder
18.592
253343AC1-166 GEN
Solar/Wind Harmer
1.074
253325AC1-069 GEN
Solar/Wind Harmer
1.035
970593AG2-378 GEN
Solar/Wind Harmer
1.966
253432AC1-085 GEN2
Solar/Wind Harmer
0.257
946171AF1-282 GEN
Solar/Wind Harmer
9.619
253370AE2-315 SEC1
Adder
1.922
253371AE2-315 SEC2
Adder
1.818
25326309TAIT D
Adder
1.05
23559001PLEAS1
50/50
11.24
23684201S70BUS2
50/50
0.322
23562401OGROV2
50/50
2.431
24318805MLG1
50/50
6.369
23534401HANNIB
50/50
0.15
24721905FLATG4
Adder
23.592
970153AG2-106 GEN
Solar/Wind Harmer
15.368
270512AE1-227 GEN2
Solar/Wind Harmer
2.273
971191AH1-055 GEN
Solar/Wind Harmer
22.576
957541AF2-048 GEN
Solar/Wind Harmer
1.614
270291AC1-194 GEN
Solar/Wind Harmer
10.719
961921AG1-034 GEN
Solar/Wind Harmer
12.85
960801AF2-371 GEN
Solar/Wind Harmer
2.556
964871AG1-351 GEN
Solar/Wind Harmer
1.765
270273AD2-016 GEN
Solar/Wind Harmer
2.682
972173AH1-669 GEN
Solar/Wind Harmer
5.026
241955AC1-078 GEN
Solar/Wind Harmer
7.448
24686205CER G4
Adder
8.265
24686405CER G5
Adder
8.232
942051AE2-217 GEN
Solar/Wind Harmer
17.81
253338AC1-165 GEN
Solar/Wind Harmer
1.074
253333AC1-068 GEN
Solar/Wind Harmer
1.035
241974AD2-163_GEN2
Solar/Wind Harmer
1.962
253415AE1-040 GEN
Solar/Wind Harmer
1.109
970605AG2-385 GEN
Solar/Wind Harmer
5.308
253406AD2-031_GEN
Solar/Wind Harmer
1.238
970935AG2-582 GEN
50/50
1215.723
24318905MLG2
50/50
4.724
270471AD2-092_GEN
Solar/Wind Harmer
3.698
970879AG2-548 GEN
Solar/Wind Harmer
6.239
971073AG2-665 GEN
Solar/Wind Harmer
6.239
971073AG2-665 GEN
Solar/Wind Harmer
4.353
946101AF1-275 GEN
Solar/Wind Harmer
1.525
972269AH1-719 GEN
Adder
2.293
24685805CER G1
Adder
8.254
24685905CER G2
Adder
8.254
24723005RIVRG1
Adder
18.592
24723105RIVRG2
Adder
18.592
942861AE2-305 GEN
Solar/Wind Harmer
7.696
270518AE2-148 GEN
Solar/Wind Harmer
11.94
970077AG2-063 GEN
Solar/Wind Harmer
5.308
962581AG1-107 GEN
Solar/Wind Harmer
4.865
961491AF2-440 GEN
Solar/Wind Harmer
2.022
972159AH1-661 GEN
Adder
0.962
253394AE2-221_GEN
Solar/Wind Harmer
4.373
253398AE2-221_GEN2
Solar/Wind Harmer
4.373
253317AC1-085 GEN4
Solar/Wind Harmer
8.057
25326109MON D
Adder
1.263
270186AC1-089 GEN
Solar/Wind Harmer
5.865
253370AE2-315 SEC1
Adder
1.922
25322209TAIT E
Adder
9.347
25322209TAIT E
Adder
9.137
964601AG1-323 GEN
Solar/Wind Harmer
3.04
964601AG1-323 GEN
Solar/Wind Harmer
1.414
25183208HLCRTG
Solar/Wind Harmer
5.797
270224U2-072_GEN2
Solar/Wind Harmer
1.889
270227U2-072_GEN3
Solar/Wind Harmer
1.889
270228U2-072_GEN4
Solar/Wind Harmer
1.889
270231U2-072_GEN5
Solar/Wind Harmer
1.889
252509AD1-136 GEN
Solar/Wind Harmer
0.245
252519AF1-045_GEN
Solar/Wind Harmer
5.794
252516AE2-318_GEN
Solar/Wind Harmer
4.42
938701AE1-092 GEN
Solar/Wind Harmer
19.71
25194408D.CRK1
Adder
7.189
25194508D.CRK3
Adder
1.344
253378AE2-206_GEN
Solar/Wind Harmer
3.413
276820AF1-078_GEN
Solar/Wind Harmer
1.516
25326509SID D
Adder
1.242
970239AG2-162 GEN
Solar/Wind Harmer
10.263
24728805RICHG1
Adder
3.517
24728905RICHG2
Adder
3.517
970883AG2-550 GEN
Solar/Wind Harmer
9.293
970885AG2-551 GEN
Solar/Wind Harmer
2.161
270383AD1-128 GEN
Solar/Wind Harmer
5.669
24379505HDWTR1G C
Solar/Wind Harmer
7.337
270209AC1-174_GEN
Solar/Wind Harmer
5.178
926881AC1-175 GEN
Solar/Wind Harmer
5.178
247621Y3-024
Adder
0.223
944541AF1-119 GEN
Solar/Wind Harmer
3.879
960971AF2-388 GEN
Solar/Wind Harmer
10.123
270201AC2-176 GEN
Solar/Wind Harmer
4.758
964611AG1-324 GEN
Solar/Wind Harmer
1.091
964611AG1-324 GEN
Solar/Wind Harmer
0.484
970825AG2-519 GEN
Solar/Wind Harmer
9.752
960441AF2-335 GEN
Solar/Wind Harmer
9.237
247620Y3-023
Adder
0.416
274770LINCOLN ;1U
Adder
7.577
274771LINCOLN ;2U
Adder
7.577
238175AF1-290_GEN
Solar/Wind Helper
0.128
238169AE2-226 GEN1
Solar/Wind Helper
0.591
238170AE2-226 GEN2
Solar/Wind Helper
0.591
235020AA1-095 C
Solar/Wind Helper
0.044
23777901MDS_W4-102
Solar/Wind Helper
0.148
237034AC2-136 C
Solar/Wind Helper
0.192
237002AB1-128_GEN
Solar/Wind Helper
0.372
237001AB1-127_GEN
Solar/Wind Helper
0.372
235063AE1-101 C2
Solar/Wind Helper
1.393
23777801MSM_W1-116
Solar/Wind Helper
0.097
237025AB1-124 C
Solar/Wind Helper
0.14
237006AB1-125 GEN
Solar/Wind Helper
0.105
270599AE1-208 GEN
Solar/Wind Harmer
0.766
270031AE2-169
Solar/Wind Harmer
0.766
962771AG1-126 GEN
Solar/Wind Harmer
35.245
270330AC1-082 GEN2
Solar/Wind Harmer
0.795
270329AC1-082 GEN1
Solar/Wind Harmer
0.468
270054AF2-122 C O1
Solar/Wind Harmer
3.32
940611AE2-048 GEN
Solar/Wind Harmer
22.287
941391AE2-136 GEN
Solar/Wind Harmer
11.549
970879AG2-548 GEN
Solar/Wind Harmer
4.353
270520AE2-214 GEN
Solar/Wind Harmer
6.113
270459AD2-067 GEN
Solar/Wind Harmer
8.438
961821AG1-024 GEN
Solar/Wind Harmer
8.566
270432AC2-029 GEN
Solar/Wind Harmer
7.042
970689AG2-444 GEN
Solar/Wind Harmer
16.397
270269AC2-059
Solar/Wind Harmer
9.378
972203AH1-686 GEN
Adder
2.313
270156DARBY CT1
Adder
8.909
270157DARBY CT2
Adder
8.887
270158DARBY CT3
Adder
8.745
945631AF1-228 GEN
Solar/Wind Harmer
4.662
270284AF1-227 GEN1
Solar/Wind Harmer
5.621
270286AF1-227 GEN2
Solar/Wind Harmer
2.079
270287AF1-227 GEN3
Solar/Wind Harmer
2.079
253383AE2-342_GEN
Solar/Wind Harmer
0.877
971985AH1-537 GEN
Solar/Wind Harmer
17.658
241973AD2-163_GEN1
Solar/Wind Harmer
1.962
943861AF1-054 GEN
Solar/Wind Harmer
3.799
943851AF1-053 GEN
Solar/Wind Harmer
1.836
270340AC2-060 GEN
Solar/Wind Harmer
2.985
24477305BRIDGE
Adder
0.341
241972AD1-140 GEN
Solar/Wind Harmer
4.346
270367AC2-061_GEN
Solar/Wind Harmer
3.072
253372AE2-315 SEC3
Adder
1.818
253372AE2-315 SEC3
Adder
1.818
25306009OHH W.
Adder
2.758
270578AF1-285 GEN2
Solar/Wind Harmer
0.444
253349AC2-067 GEN
Solar/Wind Harmer
4.752
253400AC2-068 GEN
Solar/Wind Harmer
1.911
252524AE2-267 GEN
Solar/Wind Harmer
1.499
25196408WSDLE3
Adder
8.387
25196308WSDLE2
Adder
8.314
25196208WSDLE1
Adder
8.294
25196708WSDLE6
Adder
8.273
25196508WSDLE4
Adder
8.064
270302AB2-170 GEN
Solar/Wind Harmer
7.9
270317AD1-130_GEN
Solar/Wind Harmer
3.028
944031AF1-071 GEN
Solar/Wind Harmer
0.944
25196108MFTGT2
Adder
1.44
25196108MFTGT2
Adder
1.337
972163AH1-664 GEN
Solar/Wind Harmer
9.324
972165AH1-665 GEN
Solar/Wind Harmer
7.459
971673AH1-337 GEN
Solar/Wind Harmer
4.287
971029AG2-637 GEN
Solar/Wind Harmer
13.968
270543AE2-219 C
Solar/Wind Harmer
4.759
270240V3-007_GEN2
Solar/Wind Harmer
5.741
24729505KEY G4
Adder
6.012
958711AF2-162 GEN
Solar/Wind Harmer
0.937
965101AG1-375 GEN
Solar/Wind Harmer
9.26
945581AF1-223 GEN
Solar/Wind Harmer
4.198
961761AG1-017 GEN
Solar/Wind Harmer
0.396
970115AG2-085 GEN
Solar/Wind Harmer
3.695
274775LINCOLN ;6U
Adder
7.577
274776LINCOLN ;7U
Adder
7.577
274777LINCOLN ;8U
Adder
7.577
274814UNIV PK N;0U
Adder
4.526
274807UNIV PK N;3U
Adder
4.517
274805UNIV PK N;1U
Adder
4.497
274811UNIV PK N;7U
Adder
0.593
238152AF2-075_GEN
Solar/Wind Helper
0.602
23546401DTGZ2-030
Solar/Wind Helper
0.076
238208AF1-136 C
Solar/Wind Helper
0.181
238109AE1-109 GEN2
Solar/Wind Helper
0.087
238110AE1-109 GEN3
Solar/Wind Helper
0.087
237085AD2-009_GEN
Solar/Wind Helper
1.378
3138216PACIFIC
Solar/Wind Helper
0.038
316411AF1-147_GEN1
Solar/Wind Helper
0.751
316415AF1-147_GEN2
Solar/Wind Helper
0.751
960071AF2-298 GEN
Solar/Wind Harmer
4.772
270223U2-072_GEN1
Solar/Wind Harmer
1.889
252507AC2-088 GEN
Solar/Wind Harmer
1.713
270578AF1-285 GEN2
Solar/Wind Harmer
1.155
270391AF1-285 GEN3
Solar/Wind Harmer
1.155
25194608D.CRK4
Adder
1.563
25196808ZIMRHP
Adder
71.915
270462AD2-086
Solar/Wind Harmer
6.572
25196008MFTGT1
Adder
1.306
970333AG2-219 GEN
Solar/Wind Harmer
29.451
945681AF1-233 GEN
Solar/Wind Harmer
17.602
247536S-71 GEN
Solar/Wind Harmer
3.755
942081AE2-220 GEN
Solar/Wind Harmer
5.932
270239V3-007_GEN1
Solar/Wind Harmer
1.597
971995AH1-542 GEN
Solar/Wind Harmer
10.198
965651AG1-433 GEN
Solar/Wind Harmer
5.062
958861AF2-177 GEN
Solar/Wind Harmer
10.121
945371AF1-202 GEN
Solar/Wind Harmer
6.459
270005AE1-210 C O1
Solar/Wind Harmer
5.055
965031AG1-367 GEN
Solar/Wind Harmer
9.249
970825AG2-519 GEN
Solar/Wind Harmer
2.176
970091AG2-072 GEN
Adder
70.733
24728605AND G2
Adder
3.494
24639705ELKHART HY
Adder
0.139
274773LINCOLN ;4U
Adder
7.577
274774LINCOLN ;5U
Adder
7.577
274751CRETE EC ;1U
Adder
7.394
274754CRETE EC ;4U
Adder
7.394
274723RIVER EC ;12
Adder
16.072
274812UNIV PK N;8U
Adder
4.487
23583801GRNGAP
Solar/Wind Helper
4.952
316095T157 G97
Solar/Wind Helper
1.324
238147AE2-230_GEN1
Solar/Wind Helper
0.422
238149AF1-291A_GEN
Solar/Wind Helper
0.12
237061AD1-155 GEN
Solar/Wind Helper
0.045
238221AF1-254 C O1
Solar/Wind Helper
0.23
238108AE1-109 GEN1
Solar/Wind Helper
0.087
235067AD1-061 GEN
Solar/Wind Helper
0.416
237030AB1-096 C
Solar/Wind Helper
0.06
253316AC1-085 GEN3
Solar/Wind Harmer
8.057
253433AC1-085 GEN1
Solar/Wind Harmer
5.115
946181AF1-283 GEN
Solar/Wind Harmer
12.504
253303V4-073 C
Solar/Wind Harmer
0.111
253370AE2-315 SEC1
Adder
1.922
253371AE2-315 SEC2
Adder
1.818
942871AE2-306 GEN
Solar/Wind Harmer
0.866
270391AF1-285 GEN3
Solar/Wind Harmer
0.444
252510AF1-249 C
Solar/Wind Harmer
0.398
25194608D.CRK4
Adder
1.563
25196608WSDLE5
Adder
8.148
270485AE1-090_GEN
Solar/Wind Harmer
0.571
270222AC2-111 GEN
Solar/Wind Harmer
7.655
25196008MFTGT1
Adder
1.265
970243AG2-164 GEN
Solar/Wind Harmer
24.096
970519AG2-331 GEN
Solar/Wind Harmer
16.189
970699AG2-449 GEN
Solar/Wind Harmer
10.709
972167AH1-666 GEN
Solar/Wind Harmer
7.473
958171AF2-111 GEN
Solar/Wind Harmer
23.339
270437AC2-090 C
Solar/Wind Harmer
5.18
944531AF1-118 GEN
Solar/Wind Harmer
32.44
962031AG1-047 GEN
Solar/Wind Harmer
2.797
957741AF2-068 GEN
Solar/Wind Harmer
13.882
946031AF1-268 GEN
Solar/Wind Harmer
7.677
958821AF2-173 GEN
Solar/Wind Harmer
12.949
270004AE1-209 GEN
Solar/Wind Harmer
5.055
270356AE2-297 GEN
Solar/Wind Harmer
4.219
24728705AND G3
Adder
7.308
24728505AND G1
Adder
3.494
24642205MAYFLWER
Adder
0.573
274772LINCOLN ;3U
Adder
7.577
274752CRETE EC ;2U
Adder
7.394
274753CRETE EC ;3U
Adder
7.394
274724RIVER EC ;11
Adder
15.884
316097T157 G90
Solar/Wind Helper
1.324
964991AG1-363 GEN
Solar/Wind Helper
4.195
238148AE2-230_GEN2
Solar/Wind Helper
0.423
237080AD1-060 GEN
Solar/Wind Helper
0.287
23750701CROSSCHOOL
Solar/Wind Helper
1.116
237038AE2-054 C
Solar/Wind Helper
0.228
235062AE1-101 C1
Solar/Wind Helper
1.393
23779801AA1-109
Solar/Wind Helper
0.164
944201AF1-088_MTX
Adder
104.45
957141AF2-008_MTX
Adder
52.225
CBM West 1LTFEXP_CBM-W1->PJM
CBM
123.724
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.351
MECLTFEXP_MEC->PJM
CLTF
14.175
SIGELTFEXP_SIGE->PJM
CLTF
0.458
LAGNLTFEXP_LAGN->PJM
CLTF
13.912
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.88
TVALTFEXP_TVA->PJM
CLTF
6.914
CPLELTFEXP_CPLE->PJM
CLTF
1.246
CBM West 2LTFEXP_CBM-W2->PJM
CBM
103.491
NYPJM->LTFIMP_NY
CLTF
4.434
LGEELTFEXP_LGEE->PJM
CLTF
6.157
WECLTFEXP_WEC->PJM
CLTF
3.363
AG2-052LTFEXP_AG2-052->PJM
LTF
0.21
AH1-155LTFEXP_AH1-155->PJM
LTF
0.314

Details for 01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line l/o AP_P1-3_MP-765-502T_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-502T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:139.36 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5284.61
MW Contribution:6.3
Bus #Bus NameTypeMW Contribution
23559101PLEAS2
50/50
11.213
23684101S70BUS1
50/50
0.313
23562301OGROV1
50/50
2.427
24721705FLATG2
Adder
23.442
962761AG1-125 GEN
Solar/Wind Harmer
29.494
970149AG2-104 GEN
Solar/Wind Harmer
31.855
970155AG2-107 GEN
Solar/Wind Harmer
18.834
270510AE1-227 GEN1
Solar/Wind Harmer
1.907
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
970947AG2-589 GEN
Solar/Wind Harmer
0.239
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
927014AC1-188 GEN
Solar/Wind Harmer
0.004
270349AD2-093_GEN
Solar/Wind Harmer
0.005
270263AC1-001 GEN
Solar/Wind Harmer
0.698
24686105CER G3
Adder
8.253
24686505CER G6
Adder
8.242
270159DARBY CT4
Adder
8.691
24723205RIVRG3
Adder
18.473
253343AC1-166 GEN
Solar/Wind Harmer
0.003
253325AC1-069 GEN
Solar/Wind Harmer
0.011
970593AG2-378 GEN
Solar/Wind Harmer
1.53
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.657
253370AE2-315 SEC1
Adder
1.906
253371AE2-315 SEC2
Adder
1.803
25326309TAIT D
Adder
1.041
960071AF2-298 GEN
Solar/Wind Harmer
3.297
252507AC2-088 GEN
Solar/Wind Harmer
0.3
270223U2-072_GEN1
Solar/Wind Harmer
0.001
25194608D.CRK4
Adder
1.55
25196808ZIMRHP
Adder
71.347
270462AD2-086
Solar/Wind Harmer
0.014
25196008MFTGT1
Adder
1.296
970333AG2-219 GEN
Solar/Wind Harmer
4.624
945681AF1-233 GEN
Solar/Wind Harmer
12.186
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.707
247536S-71 GEN
Solar/Wind Harmer
0.258
965651AG1-433 GEN
Solar/Wind Harmer
1.879
958861AF2-177 GEN
Solar/Wind Harmer
2.776
945371AF1-202 GEN
Solar/Wind Harmer
0.001
971995AH1-542 GEN
Solar/Wind Harmer
2.347
970773AG2-487 GEN
Solar/Wind Harmer
1.131
270005AE1-210 C O1
Solar/Wind Harmer
1.387
965031AG1-367 GEN
Solar/Wind Harmer
6.4
970825AG2-519 GEN
Solar/Wind Harmer
2.27
970091AG2-072 GEN
Adder
70.193
270032AE2-172
Solar/Wind Harmer
4.254
970291AG2-192 GEN
Solar/Wind Harmer
0.829
970245AG2-165 GEN
Solar/Wind Harmer
2.761
276903AD2-071 C
Solar/Wind Harmer
7.113
965011AG1-365 GEN
Solar/Wind Harmer
6.333
247521TR3_G114
Solar/Wind Harmer
0.23
270246TR4_N_V150
Solar/Wind Harmer
0.041
24728605AND G2
Adder
3.466
339216AC1-074 GEN
Solar/Wind Harmer
0.172
965421AG1-410 GEN
Solar/Wind Harmer
18.858
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
7.853
246936BC-WTG1
Solar/Wind Harmer
0.255
24791305MDL-5G
Solar/Wind Harmer
0.001
270489AE1-102 GEN1
Solar/Wind Harmer
0.817
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.162
24695305TIMB G C
Solar/Wind Harmer
0.002
270055AF2-134 C O1
Solar/Wind Harmer
0.005
970373AG2-245 GEN
Solar/Wind Harmer
13.169
270063AE2-323 C
Solar/Wind Harmer
0.005
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.002
24639705ELKHART HY
Adder
0.137
963741AG1-226 GEN
Solar/Wind Harmer
14.772
945111AF1-176 GEN
Solar/Wind Harmer
11.105
270505AE1-170 C O1
Solar/Wind Harmer
6.535
270445AC2-157 GEN2
Solar/Wind Harmer
0.003
274773LINCOLN ;4U
Adder
7.514
274774LINCOLN ;5U
Adder
7.514
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.241
274751CRETE EC ;1U
Adder
7.332
274754CRETE EC ;4U
Adder
7.332
274723RIVER EC ;12
Adder
15.938
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.45
276776AD2-060 GEN
Solar/Wind Harmer
0.646
941551AE2-152 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
939401AE1-172 GEN
Solar/Wind Harmer
4.613
276691AA1-018 GEN1
Solar/Wind Harmer
0.745
276901AD2-066 C O1
Solar/Wind Harmer
0.006
944231AF1-091 GEN
Solar/Wind Harmer
1.635
971997AH1-543 GEN
Solar/Wind Harmer
3.22
23583801GRNGAP
Solar/Wind Helper
4.858
316095T157 G97
Solar/Wind Helper
1.299
238147AE2-230_GEN1
Solar/Wind Helper
0.415
238149AF1-291A_GEN
Solar/Wind Helper
0.119
238108AE1-109 GEN1
Solar/Wind Helper
0.088
237061AD1-155 GEN
Solar/Wind Helper
0.045
238185AF2-356 C
Solar/Wind Helper
1.996
238221AF1-254 C O1
Solar/Wind Helper
0.228
235067AD1-061 GEN
Solar/Wind Helper
0.412
235531U2-073 GEN
Solar/Wind Helper
2.523
238117U2-030
Solar/Wind Helper
0.26
962771AG1-126 GEN
Solar/Wind Harmer
29.494
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Harmer
0.006
970879AG2-548 GEN
Solar/Wind Harmer
6.304
940611AE2-048 GEN
Solar/Wind Harmer
17.215
941391AE2-136 GEN
Solar/Wind Harmer
9.698
270520AE2-214 GEN
Solar/Wind Harmer
0.011
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
4.145
972203AH1-686 GEN
Adder
2.298
270432AC2-029 GEN
Solar/Wind Harmer
3.085
970689AG2-444 GEN
Solar/Wind Harmer
14.206
270269AC2-059
Solar/Wind Harmer
0.004
270156DARBY CT1
Adder
8.832
270157DARBY CT2
Adder
8.81
270158DARBY CT3
Adder
8.67
945631AF1-228 GEN
Solar/Wind Harmer
0
270284AF1-227 GEN1
Solar/Wind Harmer
0.009
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
971985AH1-537 GEN
Solar/Wind Harmer
2.037
253383AE2-342_GEN
Solar/Wind Harmer
0.002
241973AD2-163_GEN1
Solar/Wind Harmer
0.005
943861AF1-054 GEN
Solar/Wind Harmer
2.627
943851AF1-053 GEN
Solar/Wind Harmer
1.82
270340AC2-060 GEN
Solar/Wind Harmer
0.008
24477305BRIDGE
Adder
0.338
241972AD1-140 GEN
Solar/Wind Harmer
0.734
270367AC2-061_GEN
Solar/Wind Harmer
0.005
253372AE2-315 SEC3
Adder
1.803
253372AE2-315 SEC3
Adder
1.803
25306009OHH W.
Adder
2.735
270578AF1-285 GEN2
Solar/Wind Harmer
0.44
253349AC2-067 GEN
Solar/Wind Harmer
2.077
253400AC2-068 GEN
Solar/Wind Harmer
0.835
252524AE2-267 GEN
Solar/Wind Harmer
0.002
25196408WSDLE3
Adder
8.32
25196308WSDLE2
Adder
8.248
25196208WSDLE1
Adder
8.227
25196708WSDLE6
Adder
8.207
25196508WSDLE4
Adder
8
270302AB2-170 GEN
Solar/Wind Harmer
0.004
270317AD1-130_GEN
Solar/Wind Harmer
0.009
971653AH1-327 GEN
Solar/Wind Harmer
0.917
25196108MFTGT2
Adder
1.429
25196108MFTGT2
Adder
1.327
972163AH1-664 GEN
Solar/Wind Harmer
7.187
972165AH1-665 GEN
Solar/Wind Harmer
5.756
971673AH1-337 GEN
Solar/Wind Harmer
4.191
971029AG2-637 GEN
Solar/Wind Harmer
9.664
270543AE2-219 C
Solar/Wind Harmer
0.004
270240V3-007_GEN2
Solar/Wind Harmer
0.002
24729505KEY G4
Adder
5.961
965101AG1-375 GEN
Solar/Wind Harmer
6.406
945581AF1-223 GEN
Solar/Wind Harmer
0
970115AG2-085 GEN
Solar/Wind Harmer
2.556
971609AH1-304 GEN
Solar/Wind Harmer
1.043
270024AE2-089 GEN
Solar/Wind Harmer
0.007
270594AE1-207 GEN
Solar/Wind Harmer
7.147
270071AF1-092 GEN
Solar/Wind Harmer
12.224
970289AG2-191 GEN
Solar/Wind Harmer
1.211
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
8.573
965051AG1-369 GEN
Solar/Wind Harmer
3.147
971347AH1-153 GEN
Solar/Wind Harmer
9.454
965041AG1-368 GEN
Solar/Wind Harmer
6.297
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
3.74
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.796
958391AF2-133 GEN
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.008
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
963841AG1-237 GEN
Solar/Wind Harmer
2.71
971771AH1-392 GEN
Solar/Wind Harmer
6.248
971769AH1-391 GEN
Solar/Wind Harmer
6.974
247607V1-011 GEN
Solar/Wind Harmer
0.001
971619AH1-309 GEN
Solar/Wind Harmer
2.801
274775LINCOLN ;6U
Adder
7.514
274776LINCOLN ;7U
Adder
7.514
274777LINCOLN ;8U
Adder
7.514
274814UNIV PK N;0U
Adder
4.489
274807UNIV PK N;3U
Adder
4.479
274805UNIV PK N;1U
Adder
4.459
274811UNIV PK N;7U
Adder
0.697
960591AF2-350 GEN
Solar/Wind Harmer
6.191
270399AC1-101 GEN
Solar/Wind Harmer
1.957
270400AC1-102 GEN
Solar/Wind Harmer
1.957
970833AG2-524 GEN
Solar/Wind Harmer
6.792
970833AG2-524 GEN
Solar/Wind Harmer
4.528
970179AG2-119 GEN
Solar/Wind Harmer
5.506
274863CRW1-WTG
Solar/Wind Harmer
0.002
970935AG2-582 GEN
50/50
1217.062
24318905MLG2
50/50
4.656
270471AD2-092_GEN
Solar/Wind Harmer
0.005
971073AG2-665 GEN
Solar/Wind Harmer
6.304
24685805CER G1
Adder
8.199
24685905CER G2
Adder
8.199
972269AH1-719 GEN
Adder
2.268
24723005RIVRG1
Adder
18.473
24723105RIVRG2
Adder
18.473
942861AE2-305 GEN
Solar/Wind Harmer
5.322
270518AE2-148 GEN
Solar/Wind Harmer
0.589
970077AG2-063 GEN
Solar/Wind Harmer
3.909
962581AG1-107 GEN
Solar/Wind Harmer
0.001
972159AH1-661 GEN
Adder
0.952
253394AE2-221_GEN
Solar/Wind Harmer
0.008
253398AE2-221_GEN2
Solar/Wind Harmer
0.008
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
270186AC1-089 GEN
Solar/Wind Harmer
0.004
25326109MON D
Adder
1.252
253370AE2-315 SEC1
Adder
1.906
25322209TAIT E
Adder
9.269
25322209TAIT E
Adder
9.061
25183208HLCRTG
Solar/Wind Harmer
0.01
964601AG1-323 GEN
Solar/Wind Harmer
2.647
964601AG1-323 GEN
Solar/Wind Harmer
1.765
252509AD1-136 GEN
Solar/Wind Harmer
0.033
252519AF1-045_GEN
Solar/Wind Harmer
5.748
252516AE2-318_GEN
Solar/Wind Harmer
5.098
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
938701AE1-092 GEN
Solar/Wind Harmer
10.591
971655AH1-328 GEN
Solar/Wind Harmer
2.34
25194408D.CRK1
Adder
7.132
25194508D.CRK3
Adder
1.333
253378AE2-206_GEN
Solar/Wind Harmer
0.003
276820AF1-078_GEN
Solar/Wind Harmer
0.002
970329AG2-216 GEN
Solar/Wind Harmer
2.833
25326509SID D
Adder
1.231
970239AG2-162 GEN
Solar/Wind Harmer
1.617
24728805RICHG1
Adder
3.489
24728905RICHG2
Adder
3.489
970883AG2-550 GEN
Solar/Wind Harmer
6.429
970885AG2-551 GEN
Solar/Wind Harmer
2.143
270383AD1-128 GEN
Solar/Wind Harmer
0.004
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
247621Y3-024
Adder
0.222
944541AF1-119 GEN
Solar/Wind Harmer
0.429
960971AF2-388 GEN
Solar/Wind Harmer
3.759
270201AC2-176 GEN
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
0.48
970825AG2-519 GEN
Solar/Wind Harmer
7.086
960441AF2-335 GEN
Solar/Wind Harmer
6.391
270599AE1-208 GEN
Solar/Wind Harmer
5.854
270031AE2-169
Solar/Wind Harmer
3.512
971613AH1-306 GEN
Solar/Wind Harmer
3.063
942221AE2-234 GEN
Solar/Wind Harmer
0.032
970321AG2-212 GEN
Solar/Wind Harmer
2.761
970611AG2-400 GEN
Solar/Wind Harmer
6.333
970627AG2-408 GEN
Solar/Wind Harmer
1.9
970235AG2-159 GEN
Solar/Wind Harmer
3.847
970235AG2-159 GEN
Solar/Wind Harmer
2.207
339221AD2-048_GEN
Solar/Wind Harmer
0.004
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
971199AH1-059 GEN
Solar/Wind Harmer
2.513
246938BC-WTG3
Solar/Wind Harmer
0.228
246937BC-WTG2
Solar/Wind Harmer
0.255
972043AH1-570 GEN
Solar/Wind Harmer
1.633
972045AH1-571 GEN
Solar/Wind Harmer
1.308
966841AG1-555 GEN
Solar/Wind Harmer
0.709
944971AF1-162 GEN
Solar/Wind Harmer
6.265
965681AG1-436 GEN
Solar/Wind Harmer
7.82
965791AG1-447 GEN
Solar/Wind Harmer
5.734
270216AD2-079_GEN
Solar/Wind Harmer
0.001
247620Y3-023
Adder
0.412
270526AF1-158 GEN
Solar/Wind Harmer
0.008
24441505OLIV SLR
Solar/Wind Harmer
0
270007AE1-245 C
Solar/Wind Harmer
0.002
970241AG2-163 GEN
Solar/Wind Harmer
3.641
957891AF2-083 GEN
Solar/Wind Harmer
0.001
270444AC2-157 GEN1
Solar/Wind Harmer
0.003
971587AH1-292 GEN
Solar/Wind Harmer
4.56
961051AF2-396 GEN
Solar/Wind Harmer
12.428
961051AF2-396 GEN
Solar/Wind Harmer
8.285
274770LINCOLN ;1U
Adder
7.514
274771LINCOLN ;2U
Adder
7.514
971125AH1-004 GEN
Solar/Wind Harmer
2.483
970107AG2-081 GEN
Solar/Wind Harmer
1.862
960161AF2-307 GEN
Solar/Wind Harmer
4.096
945391AF1-204 GEN
Solar/Wind Harmer
6.587
274888KELLY CRK;1U
Solar/Wind Harmer
0.364
274887GEN-1.85
Solar/Wind Harmer
0.163
276843GEN-1.7
Solar/Wind Harmer
0.2
958011AF2-095 GEN
Solar/Wind Harmer
8.915
970623AG2-406 GEN
Solar/Wind Harmer
1.132
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
241960AC2-195 GEN
Solar/Wind Harmer
0.005
958481AF2-142 GEN
Solar/Wind Harmer
9.231
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.833
971573AH1-285 GEN
Solar/Wind Harmer
1.146
23559001PLEAS1
50/50
11.213
23684201S70BUS2
50/50
0.319
23562401OGROV2
50/50
2.411
24318805MLG1
50/50
6.319
24721905FLATG4
Adder
23.442
970153AG2-106 GEN
Solar/Wind Harmer
18.834
270512AE1-227 GEN2
Solar/Wind Harmer
1.907
971191AH1-055 GEN
Solar/Wind Harmer
18.237
270291AC1-194 GEN
Solar/Wind Harmer
5.533
961921AG1-034 GEN
Solar/Wind Harmer
6.218
270273AD2-016 GEN
Solar/Wind Harmer
0.721
972173AH1-669 GEN
Solar/Wind Harmer
3.478
241955AC1-078 GEN
Solar/Wind Harmer
0.006
24686205CER G4
Adder
8.21
24686405CER G5
Adder
8.177
942051AE2-217 GEN
Solar/Wind Harmer
12.316
253338AC1-165 GEN
Solar/Wind Harmer
0.003
253333AC1-068 GEN
Solar/Wind Harmer
0.011
241974AD2-163_GEN2
Solar/Wind Harmer
0.005
253415AE1-040 GEN
Solar/Wind Harmer
0.003
970605AG2-385 GEN
Solar/Wind Harmer
4.136
253406AD2-031_GEN
Solar/Wind Harmer
0.499
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
8.654
253370AE2-315 SEC1
Adder
1.906
253371AE2-315 SEC2
Adder
1.803
270391AF1-285 GEN3
Solar/Wind Harmer
0.44
970191AG2-125 GEN
Solar/Wind Harmer
1.697
252510AF1-249 C
Solar/Wind Harmer
0.051
25196608WSDLE5
Adder
8.083
25194608D.CRK4
Adder
1.55
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270222AC2-111 GEN
Solar/Wind Harmer
3.293
25196008MFTGT1
Adder
1.255
970243AG2-164 GEN
Solar/Wind Harmer
3.783
970519AG2-331 GEN
Solar/Wind Harmer
16.815
970699AG2-449 GEN
Solar/Wind Harmer
1.617
972167AH1-666 GEN
Solar/Wind Harmer
5.174
958171AF2-111 GEN
Solar/Wind Harmer
16.157
270437AC2-090 C
Solar/Wind Harmer
0.003
944531AF1-118 GEN
Solar/Wind Harmer
28.735
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
9.603
270356AE2-297 GEN
Solar/Wind Harmer
0.009
946031AF1-268 GEN
Solar/Wind Harmer
6.09
958821AF2-173 GEN
Solar/Wind Harmer
8.959
270004AE1-209 GEN
Solar/Wind Harmer
1.387
971617AH1-308 GEN
Solar/Wind Harmer
5.319
970289AG2-191 GEN
Solar/Wind Harmer
0.701
970291AG2-192 GEN
Solar/Wind Harmer
0.638
970513AG2-328 GEN
Solar/Wind Harmer
2.761
970517AG2-330 GEN
Solar/Wind Harmer
16.566
247642Z2-115 C
Solar/Wind Harmer
0.003
270043AE2-236 GEN
Solar/Wind Harmer
4.072
959331AF2-224 GEN
Solar/Wind Harmer
4.433
965021AG1-366 GEN
Solar/Wind Harmer
2.111
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.041
24728705AND G3
Adder
7.25
24728505AND G1
Adder
3.466
970349AG2-230 GEN
Solar/Wind Harmer
9.454
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.281
270491AE1-102 GEN2
Solar/Wind Harmer
0.817
964401AG1-302 GEN
Solar/Wind Harmer
0.001
970031AG2-029 GEN
Solar/Wind Harmer
4.079
270535AF1-215 GEN1
Solar/Wind Harmer
0.008
270053AF1-130 C
Solar/Wind Harmer
1.414
247643Z2-116 C
Solar/Wind Harmer
0
24642205MAYFLWER
Adder
0.568
945111AF1-176 GEN
Solar/Wind Harmer
5.045
274772LINCOLN ;3U
Adder
7.514
274752CRETE EC ;2U
Adder
7.332
274753CRETE EC ;3U
Adder
7.332
274724RIVER EC ;11
Adder
15.751
970193AG2-126 GEN
Solar/Wind Harmer
9.3
276806AD2-047 C O1
Solar/Wind Harmer
3.508
970941AG2-585 GEN
Solar/Wind Harmer
7.739
276897AD1-100 C
Solar/Wind Harmer
0.008
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
20.212
270258AD1-119 GEN
Solar/Wind Harmer
0.002
276893AG1-478 C
Solar/Wind Harmer
0.245
24441205WTRV SLR C
Solar/Wind Harmer
0
943121AE2-341 GEN
Solar/Wind Harmer
10.327
943591AF1-030 GEN
Solar/Wind Harmer
6.867
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
270404AC1-167 GEN
Solar/Wind Harmer
0.003
276805AD2-038 GEN
Solar/Wind Harmer
0.002
316097T157 G90
Solar/Wind Helper
1.299
964991AG1-363 GEN
Solar/Wind Helper
4.135
238148AE2-230_GEN2
Solar/Wind Helper
0.417
23750701CROSSCHOOL
Solar/Wind Helper
1.155
237080AD1-060 GEN
Solar/Wind Helper
0.284
237038AE2-054 C
Solar/Wind Helper
0.226
235062AE1-101 C1
Solar/Wind Helper
1.38
238127S14_GEN_2
Solar/Wind Helper
0.641
23779801AA1-109
Solar/Wind Helper
0.162
238118U2-030_1
Solar/Wind Helper
0.26
274864CRW2-WTG
Solar/Wind Harmer
0.002
970169AG2-114 GEN
Solar/Wind Harmer
6.145
276868AE1-113 GEN
Solar/Wind Harmer
1.231
276882AE2-255 GEN
Solar/Wind Harmer
0.717
238152AF2-075_GEN
Solar/Wind Helper
0.593
23546401DTGZ2-030
Solar/Wind Helper
0.075
238109AE1-109 GEN2
Solar/Wind Helper
0.088
238110AE1-109 GEN3
Solar/Wind Helper
0.088
238208AF1-136 C
Solar/Wind Helper
0.18
237085AD2-009_GEN
Solar/Wind Helper
1.367
238126S14_GEN_1
Solar/Wind Helper
0.641
958491AF2-143 GEN
Solar/Wind Harmer
9.212
274879MINONK ;1U
Solar/Wind Harmer
0.259
238175AF1-290_GEN
Solar/Wind Helper
0.126
238169AE2-226 GEN1
Solar/Wind Helper
0.582
238170AE2-226 GEN2
Solar/Wind Helper
0.582
235020AA1-095 C
Solar/Wind Helper
0.044
23777901MDS_W4-102
Solar/Wind Helper
0.146
238120AE2-309 GEN
Solar/Wind Helper
0.406
237034AC2-136 C
Solar/Wind Helper
0.189
237002AB1-128_GEN
Solar/Wind Helper
0.369
235063AE1-101 C2
Solar/Wind Helper
1.38
237001AB1-127_GEN
Solar/Wind Helper
0.368
23777801MSM_W1-116
Solar/Wind Helper
0.096
962691AG1-118 GEN
Solar/Wind Harmer
3.447
944201AF1-088_MTX
Adder
103.64
957141AF2-008_MTX
Adder
51.82
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.614
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.188
MECLTFEXP_MEC->PJM
CLTF
14.066
SIGELTFEXP_SIGE->PJM
CLTF
0.455
LAGNLTFEXP_LAGN->PJM
CLTF
13.832
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.925
TVALTFEXP_TVA->PJM
CLTF
6.876
CPLELTFEXP_CPLE->PJM
CLTF
1.286
CBM West 2LTFEXP_CBM-W2->PJM
CBM
102.798
NYPJM->LTFIMP_NY
CLTF
4.417
LGEELTFEXP_LGEE->PJM
CLTF
6.111
WECLTFEXP_WEC->PJM
CLTF
3.336
AG2-052LTFEXP_AG2-052->PJM
LTF
0.208
AH1-155LTFEXP_AH1-155->PJM
LTF
0.312

Details for 01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-028_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-028_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:139.32 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5282.91
MW Contribution:6.3
Bus #Bus NameTypeMW Contribution
23559101PLEAS2
50/50
11.213
23559001PLEAS1
50/50
11.213
23684201S70BUS2
50/50
0.319
23562401OGROV2
50/50
2.411
24318805MLG1
50/50
6.319
24721905FLATG4
Adder
23.442
962771AG1-126 GEN
Solar/Wind Harmer
29.494
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Harmer
0.006
970879AG2-548 GEN
Solar/Wind Harmer
6.304
940611AE2-048 GEN
Solar/Wind Harmer
17.215
941391AE2-136 GEN
Solar/Wind Harmer
9.698
270520AE2-214 GEN
Solar/Wind Harmer
0.011
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
4.145
972203AH1-686 GEN
Adder
2.298
270432AC2-029 GEN
Solar/Wind Harmer
3.085
970689AG2-444 GEN
Solar/Wind Harmer
14.206
270269AC2-059
Solar/Wind Harmer
0.004
270156DARBY CT1
Adder
8.832
270157DARBY CT2
Adder
8.81
270158DARBY CT3
Adder
8.67
945631AF1-228 GEN
Solar/Wind Harmer
0
270284AF1-227 GEN1
Solar/Wind Harmer
0.009
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
971985AH1-537 GEN
Solar/Wind Harmer
2.037
253383AE2-342_GEN
Solar/Wind Harmer
0.002
241973AD2-163_GEN1
Solar/Wind Harmer
0.005
943861AF1-054 GEN
Solar/Wind Harmer
2.627
943851AF1-053 GEN
Solar/Wind Harmer
1.82
270340AC2-060 GEN
Solar/Wind Harmer
0.008
24477305BRIDGE
Adder
0.338
241972AD1-140 GEN
Solar/Wind Harmer
0.734
270367AC2-061_GEN
Solar/Wind Harmer
0.005
253372AE2-315 SEC3
Adder
1.803
253372AE2-315 SEC3
Adder
1.803
25306009OHH W.
Adder
2.735
270578AF1-285 GEN2
Solar/Wind Harmer
0.44
253349AC2-067 GEN
Solar/Wind Harmer
2.077
253400AC2-068 GEN
Solar/Wind Harmer
0.835
252524AE2-267 GEN
Solar/Wind Harmer
0.002
25196408WSDLE3
Adder
8.32
25196308WSDLE2
Adder
8.248
25196208WSDLE1
Adder
8.227
25196708WSDLE6
Adder
8.207
25196508WSDLE4
Adder
8
270302AB2-170 GEN
Solar/Wind Harmer
0.004
270317AD1-130_GEN
Solar/Wind Harmer
0.009
971653AH1-327 GEN
Solar/Wind Harmer
0.917
25196108MFTGT2
Adder
1.429
25196108MFTGT2
Adder
1.327
972163AH1-664 GEN
Solar/Wind Harmer
7.187
972165AH1-665 GEN
Solar/Wind Harmer
5.756
971673AH1-337 GEN
Solar/Wind Harmer
4.191
971029AG2-637 GEN
Solar/Wind Harmer
9.664
270543AE2-219 C
Solar/Wind Harmer
0.004
270240V3-007_GEN2
Solar/Wind Harmer
0.002
24729505KEY G4
Adder
5.961
965101AG1-375 GEN
Solar/Wind Harmer
6.406
945581AF1-223 GEN
Solar/Wind Harmer
0
970115AG2-085 GEN
Solar/Wind Harmer
2.556
971609AH1-304 GEN
Solar/Wind Harmer
1.043
270024AE2-089 GEN
Solar/Wind Harmer
0.007
270594AE1-207 GEN
Solar/Wind Harmer
7.147
270071AF1-092 GEN
Solar/Wind Harmer
12.224
970289AG2-191 GEN
Solar/Wind Harmer
1.211
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
8.573
965051AG1-369 GEN
Solar/Wind Harmer
3.147
971347AH1-153 GEN
Solar/Wind Harmer
9.454
965041AG1-368 GEN
Solar/Wind Harmer
6.297
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
3.74
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.796
958391AF2-133 GEN
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.008
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
963841AG1-237 GEN
Solar/Wind Harmer
2.71
971771AH1-392 GEN
Solar/Wind Harmer
6.248
971769AH1-391 GEN
Solar/Wind Harmer
6.974
247607V1-011 GEN
Solar/Wind Harmer
0.001
971619AH1-309 GEN
Solar/Wind Harmer
2.801
274775LINCOLN ;6U
Adder
7.514
274776LINCOLN ;7U
Adder
7.514
274777LINCOLN ;8U
Adder
7.514
274814UNIV PK N;0U
Adder
4.489
274807UNIV PK N;3U
Adder
4.479
274805UNIV PK N;1U
Adder
4.459
274811UNIV PK N;7U
Adder
0.697
960591AF2-350 GEN
Solar/Wind Harmer
6.191
270399AC1-101 GEN
Solar/Wind Harmer
1.957
270400AC1-102 GEN
Solar/Wind Harmer
1.957
970833AG2-524 GEN
Solar/Wind Harmer
6.792
970833AG2-524 GEN
Solar/Wind Harmer
4.528
970179AG2-119 GEN
Solar/Wind Harmer
5.506
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
970169AG2-114 GEN
Solar/Wind Harmer
6.145
276868AE1-113 GEN
Solar/Wind Harmer
1.231
276882AE2-255 GEN
Solar/Wind Harmer
0.717
238152AF2-075_GEN
Solar/Wind Helper
0.593
23546401DTGZ2-030
Solar/Wind Helper
0.075
238109AE1-109 GEN2
Solar/Wind Helper
0.088
238110AE1-109 GEN3
Solar/Wind Helper
0.088
238208AF1-136 C
Solar/Wind Helper
0.18
237085AD2-009_GEN
Solar/Wind Helper
1.367
238126S14_GEN_1
Solar/Wind Helper
0.641
970153AG2-106 GEN
Solar/Wind Harmer
18.834
270512AE1-227 GEN2
Solar/Wind Harmer
1.907
971191AH1-055 GEN
Solar/Wind Harmer
18.237
270291AC1-194 GEN
Solar/Wind Harmer
5.533
961921AG1-034 GEN
Solar/Wind Harmer
6.218
270273AD2-016 GEN
Solar/Wind Harmer
0.721
972173AH1-669 GEN
Solar/Wind Harmer
3.478
241955AC1-078 GEN
Solar/Wind Harmer
0.006
24686205CER G4
Adder
8.21
24686405CER G5
Adder
8.177
942051AE2-217 GEN
Solar/Wind Harmer
12.316
253338AC1-165 GEN
Solar/Wind Harmer
0.003
253333AC1-068 GEN
Solar/Wind Harmer
0.011
241974AD2-163_GEN2
Solar/Wind Harmer
0.005
253415AE1-040 GEN
Solar/Wind Harmer
0.003
970605AG2-385 GEN
Solar/Wind Harmer
4.136
253406AD2-031_GEN
Solar/Wind Harmer
0.499
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
8.654
253370AE2-315 SEC1
Adder
1.906
253371AE2-315 SEC2
Adder
1.803
270391AF1-285 GEN3
Solar/Wind Harmer
0.44
970191AG2-125 GEN
Solar/Wind Harmer
1.697
252510AF1-249 C
Solar/Wind Harmer
0.051
25196608WSDLE5
Adder
8.083
25194608D.CRK4
Adder
1.55
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270222AC2-111 GEN
Solar/Wind Harmer
3.293
25196008MFTGT1
Adder
1.255
970243AG2-164 GEN
Solar/Wind Harmer
3.783
970519AG2-331 GEN
Solar/Wind Harmer
16.815
970699AG2-449 GEN
Solar/Wind Harmer
1.617
972167AH1-666 GEN
Solar/Wind Harmer
5.174
958171AF2-111 GEN
Solar/Wind Harmer
16.157
270437AC2-090 C
Solar/Wind Harmer
0.003
944531AF1-118 GEN
Solar/Wind Harmer
28.735
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
9.603
270356AE2-297 GEN
Solar/Wind Harmer
0.009
946031AF1-268 GEN
Solar/Wind Harmer
6.09
958821AF2-173 GEN
Solar/Wind Harmer
8.959
270004AE1-209 GEN
Solar/Wind Harmer
1.387
971617AH1-308 GEN
Solar/Wind Harmer
5.319
970289AG2-191 GEN
Solar/Wind Harmer
0.701
970291AG2-192 GEN
Solar/Wind Harmer
0.638
970513AG2-328 GEN
Solar/Wind Harmer
2.761
970517AG2-330 GEN
Solar/Wind Harmer
16.566
247642Z2-115 C
Solar/Wind Harmer
0.003
270043AE2-236 GEN
Solar/Wind Harmer
4.072
959331AF2-224 GEN
Solar/Wind Harmer
4.433
965021AG1-366 GEN
Solar/Wind Harmer
2.111
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.041
24728705AND G3
Adder
7.25
24728505AND G1
Adder
3.466
970349AG2-230 GEN
Solar/Wind Harmer
9.454
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.281
270491AE1-102 GEN2
Solar/Wind Harmer
0.817
964401AG1-302 GEN
Solar/Wind Harmer
0.001
970031AG2-029 GEN
Solar/Wind Harmer
4.079
270535AF1-215 GEN1
Solar/Wind Harmer
0.008
270053AF1-130 C
Solar/Wind Harmer
1.414
247643Z2-116 C
Solar/Wind Harmer
0
24642205MAYFLWER
Adder
0.568
945111AF1-176 GEN
Solar/Wind Harmer
5.045
274772LINCOLN ;3U
Adder
7.514
274752CRETE EC ;2U
Adder
7.332
274753CRETE EC ;3U
Adder
7.332
274724RIVER EC ;11
Adder
15.751
970193AG2-126 GEN
Solar/Wind Harmer
9.3
276806AD2-047 C O1
Solar/Wind Harmer
3.508
970941AG2-585 GEN
Solar/Wind Harmer
7.739
276897AD1-100 C
Solar/Wind Harmer
0.008
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
20.212
270258AD1-119 GEN
Solar/Wind Harmer
0.002
276893AG1-478 C
Solar/Wind Harmer
0.245
24441205WTRV SLR C
Solar/Wind Harmer
0
943121AE2-341 GEN
Solar/Wind Harmer
10.327
943591AF1-030 GEN
Solar/Wind Harmer
6.867
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
270404AC1-167 GEN
Solar/Wind Harmer
0.003
276805AD2-038 GEN
Solar/Wind Harmer
0.002
316097T157 G90
Solar/Wind Helper
1.299
964991AG1-363 GEN
Solar/Wind Helper
4.135
238148AE2-230_GEN2
Solar/Wind Helper
0.417
23750701CROSSCHOOL
Solar/Wind Helper
1.155
237080AD1-060 GEN
Solar/Wind Helper
0.284
237038AE2-054 C
Solar/Wind Helper
0.226
235062AE1-101 C1
Solar/Wind Helper
1.38
238127S14_GEN_2
Solar/Wind Helper
0.641
23779801AA1-109
Solar/Wind Helper
0.162
238118U2-030_1
Solar/Wind Helper
0.26
970935AG2-582 GEN
50/50
1217.062
24318905MLG2
50/50
4.656
270471AD2-092_GEN
Solar/Wind Harmer
0.005
971073AG2-665 GEN
Solar/Wind Harmer
6.304
24685805CER G1
Adder
8.199
24685905CER G2
Adder
8.199
972269AH1-719 GEN
Adder
2.268
24723005RIVRG1
Adder
18.473
24723105RIVRG2
Adder
18.473
942861AE2-305 GEN
Solar/Wind Harmer
5.322
270518AE2-148 GEN
Solar/Wind Harmer
0.589
970077AG2-063 GEN
Solar/Wind Harmer
3.909
962581AG1-107 GEN
Solar/Wind Harmer
0.001
972159AH1-661 GEN
Adder
0.952
253394AE2-221_GEN
Solar/Wind Harmer
0.008
253398AE2-221_GEN2
Solar/Wind Harmer
0.008
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
270186AC1-089 GEN
Solar/Wind Harmer
0.004
25326109MON D
Adder
1.252
253370AE2-315 SEC1
Adder
1.906
25322209TAIT E
Adder
9.269
25322209TAIT E
Adder
9.061
25183208HLCRTG
Solar/Wind Harmer
0.01
964601AG1-323 GEN
Solar/Wind Harmer
2.647
964601AG1-323 GEN
Solar/Wind Harmer
1.765
252509AD1-136 GEN
Solar/Wind Harmer
0.033
252519AF1-045_GEN
Solar/Wind Harmer
5.748
252516AE2-318_GEN
Solar/Wind Harmer
5.098
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
938701AE1-092 GEN
Solar/Wind Harmer
10.591
971655AH1-328 GEN
Solar/Wind Harmer
2.34
25194408D.CRK1
Adder
7.132
25194508D.CRK3
Adder
1.333
253378AE2-206_GEN
Solar/Wind Harmer
0.003
276820AF1-078_GEN
Solar/Wind Harmer
0.002
970329AG2-216 GEN
Solar/Wind Harmer
2.833
25326509SID D
Adder
1.231
970239AG2-162 GEN
Solar/Wind Harmer
1.617
24728805RICHG1
Adder
3.489
24728905RICHG2
Adder
3.489
970883AG2-550 GEN
Solar/Wind Harmer
6.429
970885AG2-551 GEN
Solar/Wind Harmer
2.143
270383AD1-128 GEN
Solar/Wind Harmer
0.004
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
247621Y3-024
Adder
0.222
944541AF1-119 GEN
Solar/Wind Harmer
0.429
960971AF2-388 GEN
Solar/Wind Harmer
3.759
270201AC2-176 GEN
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
0.48
970825AG2-519 GEN
Solar/Wind Harmer
7.086
960441AF2-335 GEN
Solar/Wind Harmer
6.391
270599AE1-208 GEN
Solar/Wind Harmer
5.854
270031AE2-169
Solar/Wind Harmer
3.512
971613AH1-306 GEN
Solar/Wind Harmer
3.063
942221AE2-234 GEN
Solar/Wind Harmer
0.032
970321AG2-212 GEN
Solar/Wind Harmer
2.761
970611AG2-400 GEN
Solar/Wind Harmer
6.333
970627AG2-408 GEN
Solar/Wind Harmer
1.9
970235AG2-159 GEN
Solar/Wind Harmer
3.847
970235AG2-159 GEN
Solar/Wind Harmer
2.207
339221AD2-048_GEN
Solar/Wind Harmer
0.004
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
971199AH1-059 GEN
Solar/Wind Harmer
2.513
246938BC-WTG3
Solar/Wind Harmer
0.228
246937BC-WTG2
Solar/Wind Harmer
0.255
972043AH1-570 GEN
Solar/Wind Harmer
1.633
972045AH1-571 GEN
Solar/Wind Harmer
1.308
966841AG1-555 GEN
Solar/Wind Harmer
0.709
944971AF1-162 GEN
Solar/Wind Harmer
6.265
965681AG1-436 GEN
Solar/Wind Harmer
7.82
965791AG1-447 GEN
Solar/Wind Harmer
5.734
270216AD2-079_GEN
Solar/Wind Harmer
0.001
247620Y3-023
Adder
0.412
270526AF1-158 GEN
Solar/Wind Harmer
0.008
24441505OLIV SLR
Solar/Wind Harmer
0
270007AE1-245 C
Solar/Wind Harmer
0.002
970241AG2-163 GEN
Solar/Wind Harmer
3.641
957891AF2-083 GEN
Solar/Wind Harmer
0.001
270444AC2-157 GEN1
Solar/Wind Harmer
0.003
971587AH1-292 GEN
Solar/Wind Harmer
4.56
961051AF2-396 GEN
Solar/Wind Harmer
12.428
961051AF2-396 GEN
Solar/Wind Harmer
8.285
274770LINCOLN ;1U
Adder
7.514
274771LINCOLN ;2U
Adder
7.514
971125AH1-004 GEN
Solar/Wind Harmer
2.483
23684101S70BUS1
50/50
0.313
23562301OGROV1
50/50
2.427
24721705FLATG2
Adder
23.442
962761AG1-125 GEN
Solar/Wind Harmer
29.494
970149AG2-104 GEN
Solar/Wind Harmer
31.855
970155AG2-107 GEN
Solar/Wind Harmer
18.834
270510AE1-227 GEN1
Solar/Wind Harmer
1.907
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
970947AG2-589 GEN
Solar/Wind Harmer
0.239
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
927014AC1-188 GEN
Solar/Wind Harmer
0.004
270349AD2-093_GEN
Solar/Wind Harmer
0.005
270263AC1-001 GEN
Solar/Wind Harmer
0.698
24686105CER G3
Adder
8.253
24686505CER G6
Adder
8.242
270159DARBY CT4
Adder
8.691
24723205RIVRG3
Adder
18.473
253343AC1-166 GEN
Solar/Wind Harmer
0.003
253325AC1-069 GEN
Solar/Wind Harmer
0.011
970593AG2-378 GEN
Solar/Wind Harmer
1.53
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.657
253370AE2-315 SEC1
Adder
1.906
253371AE2-315 SEC2
Adder
1.803
25326309TAIT D
Adder
1.041
960071AF2-298 GEN
Solar/Wind Harmer
3.297
252507AC2-088 GEN
Solar/Wind Harmer
0.3
270223U2-072_GEN1
Solar/Wind Harmer
0.001
25194608D.CRK4
Adder
1.55
25196808ZIMRHP
Adder
71.347
270462AD2-086
Solar/Wind Harmer
0.014
25196008MFTGT1
Adder
1.296
970333AG2-219 GEN
Solar/Wind Harmer
4.624
945681AF1-233 GEN
Solar/Wind Harmer
12.186
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.707
247536S-71 GEN
Solar/Wind Harmer
0.258
965651AG1-433 GEN
Solar/Wind Harmer
1.879
958861AF2-177 GEN
Solar/Wind Harmer
2.776
945371AF1-202 GEN
Solar/Wind Harmer
0.001
971995AH1-542 GEN
Solar/Wind Harmer
2.347
970773AG2-487 GEN
Solar/Wind Harmer
1.131
270005AE1-210 C O1
Solar/Wind Harmer
1.387
965031AG1-367 GEN
Solar/Wind Harmer
6.4
970825AG2-519 GEN
Solar/Wind Harmer
2.27
970091AG2-072 GEN
Adder
70.193
270032AE2-172
Solar/Wind Harmer
4.254
970291AG2-192 GEN
Solar/Wind Harmer
0.829
970245AG2-165 GEN
Solar/Wind Harmer
2.761
276903AD2-071 C
Solar/Wind Harmer
7.113
965011AG1-365 GEN
Solar/Wind Harmer
6.333
247521TR3_G114
Solar/Wind Harmer
0.23
270246TR4_N_V150
Solar/Wind Harmer
0.041
24728605AND G2
Adder
3.466
339216AC1-074 GEN
Solar/Wind Harmer
0.172
965421AG1-410 GEN
Solar/Wind Harmer
18.858
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
7.853
246936BC-WTG1
Solar/Wind Harmer
0.255
24791305MDL-5G
Solar/Wind Harmer
0.001
270489AE1-102 GEN1
Solar/Wind Harmer
0.817
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.162
24695305TIMB G C
Solar/Wind Harmer
0.002
270055AF2-134 C O1
Solar/Wind Harmer
0.005
970373AG2-245 GEN
Solar/Wind Harmer
13.169
270063AE2-323 C
Solar/Wind Harmer
0.005
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.002
24639705ELKHART HY
Adder
0.137
963741AG1-226 GEN
Solar/Wind Harmer
14.772
945111AF1-176 GEN
Solar/Wind Harmer
11.105
270505AE1-170 C O1
Solar/Wind Harmer
6.535
270445AC2-157 GEN2
Solar/Wind Harmer
0.003
274773LINCOLN ;4U
Adder
7.514
274774LINCOLN ;5U
Adder
7.514
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.241
274751CRETE EC ;1U
Adder
7.332
274754CRETE EC ;4U
Adder
7.332
274723RIVER EC ;12
Adder
15.938
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.45
276776AD2-060 GEN
Solar/Wind Harmer
0.646
941551AE2-152 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
939401AE1-172 GEN
Solar/Wind Harmer
4.613
276691AA1-018 GEN1
Solar/Wind Harmer
0.745
276901AD2-066 C O1
Solar/Wind Harmer
0.006
944231AF1-091 GEN
Solar/Wind Harmer
1.635
971997AH1-543 GEN
Solar/Wind Harmer
3.22
23583801GRNGAP
Solar/Wind Helper
4.858
316095T157 G97
Solar/Wind Helper
1.299
238147AE2-230_GEN1
Solar/Wind Helper
0.415
238149AF1-291A_GEN
Solar/Wind Helper
0.119
238108AE1-109 GEN1
Solar/Wind Helper
0.088
237061AD1-155 GEN
Solar/Wind Helper
0.045
238185AF2-356 C
Solar/Wind Helper
1.996
238221AF1-254 C O1
Solar/Wind Helper
0.228
235067AD1-061 GEN
Solar/Wind Helper
0.412
235531U2-073 GEN
Solar/Wind Helper
2.523
238117U2-030
Solar/Wind Helper
0.26
970107AG2-081 GEN
Solar/Wind Harmer
1.862
960161AF2-307 GEN
Solar/Wind Harmer
4.096
945391AF1-204 GEN
Solar/Wind Harmer
6.587
274888KELLY CRK;1U
Solar/Wind Harmer
0.364
274887GEN-1.85
Solar/Wind Harmer
0.163
276843GEN-1.7
Solar/Wind Harmer
0.2
958011AF2-095 GEN
Solar/Wind Harmer
8.915
970623AG2-406 GEN
Solar/Wind Harmer
1.132
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
241960AC2-195 GEN
Solar/Wind Harmer
0.005
958481AF2-142 GEN
Solar/Wind Harmer
9.231
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.833
971573AH1-285 GEN
Solar/Wind Harmer
1.146
958491AF2-143 GEN
Solar/Wind Harmer
9.212
274879MINONK ;1U
Solar/Wind Harmer
0.259
238175AF1-290_GEN
Solar/Wind Helper
0.126
238169AE2-226 GEN1
Solar/Wind Helper
0.582
238170AE2-226 GEN2
Solar/Wind Helper
0.582
235020AA1-095 C
Solar/Wind Helper
0.044
23777901MDS_W4-102
Solar/Wind Helper
0.146
238120AE2-309 GEN
Solar/Wind Helper
0.406
237034AC2-136 C
Solar/Wind Helper
0.189
237002AB1-128_GEN
Solar/Wind Helper
0.369
235063AE1-101 C2
Solar/Wind Helper
1.38
237001AB1-127_GEN
Solar/Wind Helper
0.368
23777801MSM_W1-116
Solar/Wind Helper
0.096
962691AG1-118 GEN
Solar/Wind Harmer
3.447
944201AF1-088_MTX
Adder
103.64
957141AF2-008_MTX
Adder
51.82
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.614
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.188
MECLTFEXP_MEC->PJM
CLTF
14.066
SIGELTFEXP_SIGE->PJM
CLTF
0.455
LAGNLTFEXP_LAGN->PJM
CLTF
13.832
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.925
TVALTFEXP_TVA->PJM
CLTF
6.876
CPLELTFEXP_CPLE->PJM
CLTF
1.286
CBM West 2LTFEXP_CBM-W2->PJM
CBM
102.798
NYPJM->LTFIMP_NY
CLTF
4.417
LGEELTFEXP_LGEE->PJM
CLTF
6.111
WECLTFEXP_WEC->PJM
CLTF
3.336
AG2-052LTFEXP_AG2-052->PJM
LTF
0.208
AH1-155LTFEXP_AH1-155->PJM
LTF
0.312

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-024_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-024_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:132.75 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4950.27
MW Contribution:11.52
Bus #Bus NameTypeMW Contribution
270119AB2-067 GEN1
50/50
7.1
270120AB2-067 GEN2
50/50
7.1
24318905MLG2
50/50
7.059
270471AD2-092_GEN
Solar/Wind Harmer
4.477
946101AF1-275 GEN
Solar/Wind Harmer
1.818
942861AE2-305 GEN
Solar/Wind Harmer
9.105
970077AG2-063 GEN
Solar/Wind Harmer
6.25
270224U2-072_GEN2
Solar/Wind Harmer
2.287
270227U2-072_GEN3
Solar/Wind Harmer
2.287
270228U2-072_GEN4
Solar/Wind Harmer
2.287
270231U2-072_GEN5
Solar/Wind Harmer
2.287
938701AE1-092 GEN
Solar/Wind Harmer
23.86
964601AG1-323 GEN
Solar/Wind Harmer
3.665
964601AG1-323 GEN
Solar/Wind Harmer
1.705
270518AE2-148 GEN
Solar/Wind Harmer
13.911
253378AE2-206_GEN
Solar/Wind Harmer
4.016
276820AF1-078_GEN
Solar/Wind Harmer
1.784
972159AH1-661 GEN
Adder
1.111
972269AH1-719 GEN
Adder
2.557
25326509SID D
Adder
1.455
971199AH1-059 GEN
Solar/Wind Harmer
4.424
241960AC2-195 GEN
Solar/Wind Harmer
3.074
970879AG2-548 GEN
Solar/Wind Harmer
6.788
971073AG2-665 GEN
Solar/Wind Harmer
6.788
971073AG2-665 GEN
Solar/Wind Harmer
4.736
25326109MON D
Adder
1.447
25322209TAIT E
Adder
10.679
25322209TAIT E
Adder
10.439
253370AE2-315 SEC1
Adder
2.189
971201AH1-060 GEN
Solar/Wind Harmer
2.181
253394AE2-221_GEN
Solar/Wind Harmer
4.93
253398AE2-221_GEN2
Solar/Wind Harmer
4.93
246938BC-WTG3
Solar/Wind Harmer
4.31
246937BC-WTG2
Solar/Wind Harmer
4.237
253317AC1-085 GEN4
Solar/Wind Harmer
9.037
970611AG2-400 GEN
Solar/Wind Harmer
10.775
971231AH1-075 GEN
Solar/Wind Harmer
0.862
270007AE1-245 C
Solar/Wind Harmer
6.374
942801AE2-298 GEN
Solar/Wind Harmer
1.626
962581AG1-107 GEN
Solar/Wind Harmer
5.38
961491AF2-440 GEN
Solar/Wind Harmer
2.236
25183208HLCRTG
Solar/Wind Harmer
6.467
944541AF1-119 GEN
Solar/Wind Harmer
4.468
960971AF2-388 GEN
Solar/Wind Harmer
11.659
942221AE2-234 GEN
Solar/Wind Harmer
0.781
252519AF1-045_GEN
Solar/Wind Harmer
6.466
252516AE2-318_GEN
Solar/Wind Harmer
4.932
247621Y3-024
Adder
0.256
970883AG2-550 GEN
Solar/Wind Harmer
10.634
970885AG2-551 GEN
Solar/Wind Harmer
2.473
270201AC2-176 GEN
Solar/Wind Harmer
5.466
25194408D.CRK1
Adder
8.037
25194508D.CRK3
Adder
1.502
964611AG1-324 GEN
Solar/Wind Harmer
1.252
964611AG1-324 GEN
Solar/Wind Harmer
0.556
252509AD1-136 GEN
Solar/Wind Harmer
0.272
247620Y3-023
Adder
0.486
24728805RICHG1
Adder
3.981
24728905RICHG2
Adder
3.981
274770LINCOLN ;1U
Adder
8.715
274771LINCOLN ;2U
Adder
8.715
274808UNIV PK N;4U
Adder
5.14
274803UNIV PARK;6U
Adder
5.997
972259AH1-714 GEN
Adder
19.596
274674JOLIET 9 ;6U
Adder
15.776
274696ROCKY RD ;4P
Adder
11.59
274695ROCKY RD ;2P
Adder
11.323
274693ROCKY RD ;1P
Adder
11.211
274697ROCKY RD ;3P
Adder
3.076
23585401KL_K28_T16
Solar/Wind Helper
1.493
238120AE2-309 GEN
Solar/Wind Helper
0.528
238175AF1-290_GEN
Solar/Wind Helper
0.153
238169AE2-226 GEN1
Solar/Wind Helper
0.703
238170AE2-226 GEN2
Solar/Wind Helper
0.703
235020AA1-095 C
Solar/Wind Helper
0.053
962771AG1-126 GEN
Solar/Wind Harmer
41.173
270459AD2-067 GEN
Solar/Wind Harmer
10.252
961821AG1-024 GEN
Solar/Wind Harmer
10.408
270054AF2-122 C O1
Solar/Wind Harmer
3.995
972239AH1-704 GEN
Adder
2.671
270284AF1-227 GEN1
Solar/Wind Harmer
6.806
270286AF1-227 GEN2
Solar/Wind Harmer
2.518
270287AF1-227 GEN3
Solar/Wind Harmer
2.518
270520AE2-214 GEN
Solar/Wind Harmer
7.284
253383AE2-342_GEN
Solar/Wind Harmer
1.047
241973AD2-163_GEN1
Solar/Wind Harmer
2.334
943861AF1-054 GEN
Solar/Wind Harmer
4.494
943851AF1-053 GEN
Solar/Wind Harmer
2.172
945631AF1-228 GEN
Solar/Wind Harmer
5.47
270156DARBY CT1
Adder
10.432
270157DARBY CT2
Adder
10.407
270158DARBY CT3
Adder
10.24
270578AF1-285 GEN2
Solar/Wind Harmer
0.538
970689AG2-444 GEN
Solar/Wind Harmer
18.845
270432AC2-029 GEN
Solar/Wind Harmer
8.059
270302AB2-170 GEN
Solar/Wind Harmer
9.566
270317AD1-130_GEN
Solar/Wind Harmer
3.667
270269AC2-059
Solar/Wind Harmer
10.62
940611AE2-048 GEN
Solar/Wind Harmer
24.866
941391AE2-136 GEN
Solar/Wind Harmer
12.885
241972AD1-140 GEN
Solar/Wind Harmer
5.031
270340AC2-060 GEN
Solar/Wind Harmer
3.353
958581AF2-149 GEN
Solar/Wind Harmer
4.732
970179AG2-119 GEN
Solar/Wind Harmer
8.844
970879AG2-548 GEN
Solar/Wind Harmer
4.736
253372AE2-315 SEC3
Adder
2.071
253372AE2-315 SEC3
Adder
2.071
25306009OHH W.
Adder
3.141
253349AC2-067 GEN
Solar/Wind Harmer
5.421
253400AC2-068 GEN
Solar/Wind Harmer
2.18
957201AF2-014 GEN
Solar/Wind Harmer
4.91
270435AC2-044 GEN
Solar/Wind Harmer
2.165
965051AG1-369 GEN
Solar/Wind Harmer
5.38
965041AG1-368 GEN
Solar/Wind Harmer
10.749
247607V1-011 GEN
Solar/Wind Harmer
4.249
24729505KEY G4
Adder
6.948
963791AG1-232 GEN
Solar/Wind Harmer
14.455
971567AH1-282 GEN
Solar/Wind Harmer
16.053
966831AG1-554 GEN
Solar/Wind Harmer
1.28
971989AH1-539 GEN
Solar/Wind Harmer
13.846
270071AF1-092 GEN
Solar/Wind Harmer
16.048
971985AH1-537 GEN
Solar/Wind Harmer
19.051
958711AF2-162 GEN
Solar/Wind Harmer
1.079
270024AE2-089 GEN
Solar/Wind Harmer
5.004
965101AG1-375 GEN
Solar/Wind Harmer
10.653
270367AC2-061_GEN
Solar/Wind Harmer
3.388
971673AH1-337 GEN
Solar/Wind Harmer
4.893
971029AG2-637 GEN
Solar/Wind Harmer
15.954
252524AE2-267 GEN
Solar/Wind Harmer
1.677
25196408WSDLE3
Adder
9.382
25196308WSDLE2
Adder
9.3
25196208WSDLE1
Adder
9.277
25196708WSDLE6
Adder
9.254
270166AC1-044 GEN3
50/50
7.1
23559101PLEAS2
50/50
6.365
962761AG1-125 GEN
Solar/Wind Harmer
41.173
970149AG2-104 GEN
Solar/Wind Harmer
50.849
970155AG2-107 GEN
Solar/Wind Harmer
17.953
270349AD2-093_GEN
Solar/Wind Harmer
4.477
24721705FLATG2
Adder
24.144
270159DARBY CT4
Adder
10.266
970593AG2-378 GEN
Solar/Wind Harmer
2.315
270223U2-072_GEN1
Solar/Wind Harmer
2.287
270578AF1-285 GEN2
Solar/Wind Harmer
1.399
270391AF1-285 GEN3
Solar/Wind Harmer
1.399
253343AC1-166 GEN
Solar/Wind Harmer
1.243
253325AC1-069 GEN
Solar/Wind Harmer
1.199
270462AD2-086
Solar/Wind Harmer
7.958
971995AH1-542 GEN
Solar/Wind Harmer
12.515
270263AC1-001 GEN
Solar/Wind Harmer
1.179
25326309TAIT D
Adder
1.2
960071AF2-298 GEN
Solar/Wind Harmer
5.454
253370AE2-315 SEC1
Adder
2.189
253371AE2-315 SEC2
Adder
2.071
927014AC1-188 GEN
Solar/Wind Harmer
1.729
241813AF1-122_GEN
Solar/Wind Harmer
6.978
246936BC-WTG1
Solar/Wind Harmer
4.237
270489AE1-102 GEN1
Solar/Wind Harmer
1.407
965421AG1-410 GEN
Solar/Wind Harmer
32.464
960001AF2-291 GEN
Solar/Wind Harmer
3.264
253432AC1-085 GEN2
Solar/Wind Harmer
0.289
946171AF1-282 GEN
Solar/Wind Harmer
10.789
247521TR3_G114
Solar/Wind Harmer
3.623
270246TR4_N_V150
Solar/Wind Harmer
0.916
965011AG1-365 GEN
Solar/Wind Harmer
10.775
24695305TIMB G C
Solar/Wind Harmer
5.916
965651AG1-433 GEN
Solar/Wind Harmer
5.83
958861AF2-177 GEN
Solar/Wind Harmer
11.644
247536S-71 GEN
Solar/Wind Harmer
4.305
25194608D.CRK4
Adder
1.747
945371AF1-202 GEN
Solar/Wind Harmer
7.414
252507AC2-088 GEN
Solar/Wind Harmer
1.904
270063AE2-323 C
Solar/Wind Harmer
2.336
25196808ZIMRHP
Adder
80.055
24639705ELKHART HY
Adder
0.162
25196008MFTGT1
Adder
1.456
274751CRETE EC ;1U
Adder
8.515
274754CRETE EC ;4U
Adder
8.515
274773LINCOLN ;4U
Adder
8.715
274774LINCOLN ;5U
Adder
8.715
274723RIVER EC ;12
Adder
18.501
274812UNIV PK N;8U
Adder
5.162
24728605AND G2
Adder
3.945
274801UNIV PARK;4U
Adder
5.993
274676JOLIET 29;8U
Adder
31.445
274732ELWOOD EC;7P
Adder
16.844
274674JOLIET 9 ;6U
Adder
15.776
274745AC1-111 GEN9
Adder
5.705
970091AG2-072 GEN
Adder
78.03
316095T157 G97
Solar/Wind Helper
1.508
23583801GRNGAP
Solar/Wind Helper
5.618
238185AF2-356 C
Solar/Wind Helper
2.662
238108AE1-109 GEN1
Solar/Wind Helper
0.114
235054AD2-180 GEN
Solar/Wind Helper
2.043
235531U2-073 GEN
Solar/Wind Helper
3.301
238117U2-030
Solar/Wind Helper
0.344
238147AE2-230_GEN1
Solar/Wind Helper
0.496
238149AF1-291A_GEN
Solar/Wind Helper
0.142
23751201ROTHROCK
Solar/Wind Helper
0.832
23562501BACKB
Solar/Wind Helper
1.017
237061AD1-155 GEN
Solar/Wind Helper
0.053
238221AF1-254 C O1
Solar/Wind Helper
0.275
235067AD1-061 GEN
Solar/Wind Helper
0.498
23751101LEADS_P59
Solar/Wind Helper
1.424
237030AB1-096 C
Solar/Wind Helper
0.071
3141196NOKESVL
Solar/Wind Helper
1.034
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.347
223402AF1-300 C
Solar/Wind Helper
0.369
205917AD1-020 ES
Solar/Wind Helper
0.37
233918AB1-142 GEN
Solar/Wind Helper
0.504
233982AB2-133 GEN
Solar/Wind Helper
0.359
233994AC2-023 GEN
Solar/Wind Helper
0.965
233996TM1833_GEN
Solar/Wind Helper
0.262
233997TMININ_4.2
Solar/Wind Helper
0.262
232406W1-004 FULL
Solar/Wind Helper
0.509
233940AF2-379 C
Solar/Wind Helper
0.062
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.233
233971AC1-093 C
Solar/Wind Helper
0.359
230430AE1-229_GEN
Solar/Wind Helper
3.385
316044AC1-158 PL1
Solar/Wind Helper
1.296
316450AC1-158 RIC
Solar/Wind Helper
0.346
230415AB2-049 C
Solar/Wind Helper
0.03
228729W2-030 C
Solar/Wind Helper
0.111
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.15
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
219348LDSOLAR C
Solar/Wind Helper
0.115
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.063
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.354
219276PARKLANDSO C
Solar/Wind Helper
0.09
20714528FRN_Y2-051
Solar/Wind Helper
0.057
20720528MAN_W1-024
Solar/Wind Helper
0.028
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.027
219249CENTRALDIV C
Solar/Wind Helper
0.01
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
23777901MDS_W4-102
Solar/Wind Helper
0.177
237002AB1-128_GEN
Solar/Wind Helper
0.445
237034AC2-136 C
Solar/Wind Helper
0.228
235063AE1-101 C2
Solar/Wind Helper
1.665
237001AB1-127_GEN
Solar/Wind Helper
0.443
23777801MSM_W1-116
Solar/Wind Helper
0.115
237025AB1-124 C
Solar/Wind Helper
0.165
237006AB1-125 GEN
Solar/Wind Helper
0.123
226929AD2-058 GEN
Solar/Wind Helper
0.099
205916AD1-020 GEN
Solar/Wind Helper
1.72
20390526W1-045 C
Solar/Wind Helper
0.351
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
233987AB2-037 GEN
Solar/Wind Helper
2.35
233933AB2-153 GEN
Solar/Wind Helper
0.233
232424Y1-079 C
Solar/Wind Helper
0.117
233944AB2-135 GEN
Solar/Wind Helper
0.591
233946AB2-136 GEN
Solar/Wind Helper
0.57
234036AF2-325 C
Solar/Wind Helper
0.042
233901CHERRYDALE C
Solar/Wind Helper
0.233
232408W1-005 C
Solar/Wind Helper
0.509
232410W1-006 C
Solar/Wind Helper
0.509
233939AC1-091 C
Solar/Wind Helper
0.351
233970AC1-092 C
Solar/Wind Helper
0.351
315651AD1-115 GEN
Solar/Wind Helper
0.787
316447AC1-158 HLD
Solar/Wind Helper
2.853
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.04
219921AF1-264
Solar/Wind Helper
0.051
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.083
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.19
20716928W4-060COL
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.016
20673828FLE_V3-070
Solar/Wind Helper
0.091
207442AE1-156 GEN
Solar/Wind Helper
0.327
20676128MHD_W3-029
Solar/Wind Helper
0.096
20671828STAW2-080
Solar/Wind Helper
0.027
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
207471AF2-354 C
Solar/Wind Helper
0.169
20674928WA_W3-044
Solar/Wind Helper
0.099
964851AG1-348 GEN
Solar/Wind Helper
0.081
20676228FRD_X1-012
Solar/Wind Helper
0.092
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.045
211065PSPA IPP
Solar/Wind Helper
0.152
211065PSPA IPP
Solar/Wind Helper
0.152
203955AF1-039 C O1
Solar/Wind Helper
0.33
970321AG2-212 GEN
Solar/Wind Harmer
4.981
24318805MLG1
50/50
10.158
23559001PLEAS1
50/50
6.365
270051AF1-062 GEN
50/50
11.843
270475AD2-096_GEN
50/50
7.165
970153AG2-106 GEN
Solar/Wind Harmer
17.953
961921AG1-034 GEN
Solar/Wind Harmer
15.612
24721905FLATG4
Adder
24.144
241955AC1-078 GEN
Solar/Wind Harmer
8.824
241974AD2-163_GEN2
Solar/Wind Harmer
2.334
942051AE2-217 GEN
Solar/Wind Harmer
21.08
960801AF2-371 GEN
Solar/Wind Harmer
2.95
964871AG1-351 GEN
Solar/Wind Harmer
2.037
970605AG2-385 GEN
Solar/Wind Harmer
6.25
942871AE2-306 GEN
Solar/Wind Harmer
1.049
270391AF1-285 GEN3
Solar/Wind Harmer
0.538
253338AC1-165 GEN
Solar/Wind Harmer
1.243
253333AC1-068 GEN
Solar/Wind Harmer
1.199
270485AE1-090_GEN
Solar/Wind Harmer
0.692
270273AD2-016 GEN
Solar/Wind Harmer
3.037
972173AH1-669 GEN
Solar/Wind Harmer
5.679
253415AE1-040 GEN
Solar/Wind Harmer
1.251
270291AC1-194 GEN
Solar/Wind Harmer
11.751
253303V4-073 C
Solar/Wind Harmer
0.127
253370AE2-315 SEC1
Adder
2.189
253371AE2-315 SEC2
Adder
2.071
957541AF2-048 GEN
Solar/Wind Harmer
1.724
970065AG2-057 GEN
Solar/Wind Harmer
1.09
253406AD2-031_GEN
Solar/Wind Harmer
1.391
270491AE1-102 GEN2
Solar/Wind Harmer
1.407
971191AH1-055 GEN
Solar/Wind Harmer
23.759
253316AC1-085 GEN3
Solar/Wind Harmer
9.037
253433AC1-085 GEN1
Solar/Wind Harmer
5.737
946181AF1-283 GEN
Solar/Wind Harmer
14.025
270191TR4_S_V150
Solar/Wind Harmer
3.232
270247TR4_N_V136
Solar/Wind Harmer
0.916
959331AF2-224 GEN
Solar/Wind Harmer
10.775
965021AG1-366 GEN
Solar/Wind Harmer
2.506
270377AD1-106 GEN
Solar/Wind Harmer
6.65
958091AF2-103 GEN
Solar/Wind Harmer
0.174
270588AE1-091_GEN
Solar/Wind Harmer
11.804
944531AF1-118 GEN
Solar/Wind Harmer
37.541
270043AE2-236 GEN
Solar/Wind Harmer
5.893
971617AH1-308 GEN
Solar/Wind Harmer
6.198
270258AD1-119 GEN
Solar/Wind Harmer
2.97
25196608WSDLE5
Adder
9.114
962031AG1-047 GEN
Solar/Wind Harmer
3.214
25196508WSDLE4
Adder
9.021
270543AE2-219 C
Solar/Wind Harmer
5.445
961761AG1-017 GEN
Solar/Wind Harmer
0.455
945581AF1-223 GEN
Solar/Wind Harmer
4.819
944031AF1-071 GEN
Solar/Wind Harmer
1.067
270297AD1-101 GEN
Solar/Wind Harmer
2.953
25196108MFTGT2
Adder
1.605
25196108MFTGT2
Adder
1.491
274775LINCOLN ;6U
Adder
8.715
274776LINCOLN ;7U
Adder
8.715
274777LINCOLN ;8U
Adder
8.715
274814UNIV PK N;0U
Adder
5.208
274807UNIV PK N;3U
Adder
5.196
274805UNIV PK N;1U
Adder
5.174
274811UNIV PK N;7U
Adder
5.162
972037AH1-567 GEN1
Adder
0.188
274827FISK ;RP
Adder
7.977
972227AH1-698 GEN1
Adder
2.681
274687WILL CNTY;4U
Adder
28.653
274687WILL CNTY;4U
Adder
28.653
274675JOLIET 29;7U
Adder
31.445
274675JOLIET 29;7U
Adder
30.322
274731ELWOOD EC;2P
Adder
16.844
274733ELWOOD EC;3P
Adder
16.844
274735ELWOOD EC;4P
Adder
16.844
274728ELWOOD EC;5P
Adder
16.844
972203AH1-686 GEN
Adder
2.356
274746AC1-111 G10
Adder
5.705
274744AC1-111 GEN8
Adder
5.705
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238126S14_GEN_1
Solar/Wind Helper
0.832
238152AF2-075_GEN
Solar/Wind Helper
0.709
238208AF1-136 C
Solar/Wind Helper
0.221
23546401DTGZ2-030
Solar/Wind Helper
0.089
237085AD2-009_GEN
Solar/Wind Helper
1.655
3138216PACIFIC
Solar/Wind Helper
0.044
316411AF1-147_GEN1
Solar/Wind Helper
0.891
316415AF1-147_GEN2
Solar/Wind Helper
0.891
23750501ELLIOTTS
Solar/Wind Helper
0.644
959381AF2-229 GEN
Solar/Wind Helper
0.359
3141426STAFORD
Solar/Wind Helper
0.052
960921AF2-383 GEN
Solar/Wind Helper
0.182
205943AE1-185 GEN
Solar/Wind Helper
0.511
205932AD2-116_GEN
Solar/Wind Helper
0.511
205956AE1-196_GEN
Solar/Wind Helper
0.511
233935AB2-179 C
Solar/Wind Helper
1.273
232436AB1-176 C
Solar/Wind Helper
0.045
233923SMA
Solar/Wind Helper
0.962
233990AG1-397 GEN
Solar/Wind Helper
0.031
232432Z2-076 GEN
Solar/Wind Helper
0.067
234033AF1-007_GEN
Solar/Wind Helper
7.046
964001AG1-254 GEN
Solar/Wind Helper
0.959
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.115
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.08
203975AE1-071-GEN
Solar/Wind Helper
2.508
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.291
219620RIDERU C
Solar/Wind Helper
0.001
316164AC1-076 GEN
Solar/Wind Helper
1.099
20675528CPH_W2-050
Solar/Wind Helper
0.087
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
218524CNTRALGAS1 C
Solar/Wind Helper
0.161
966261AG1-495 GEN
Solar/Wind Helper
0.082
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20675928HOL_W4-097
Solar/Wind Helper
0.05
207484AF2-139 C O1
Solar/Wind Helper
0.084
20674828DL_W4-046
Solar/Wind Helper
0.008
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.137
20675128HRM_W1-127
Solar/Wind Helper
0.03
209116AE2-175 GEN
Solar/Wind Helper
1.786
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.089
963161AG1-165 GEN
Solar/Wind Helper
0.441
970245AG2-165 GEN
Solar/Wind Harmer
4.981
957741AF2-068 GEN
Solar/Wind Harmer
15.949
252510AF1-249 C
Solar/Wind Harmer
0.444
25194608D.CRK4
Adder
1.747
270222AC2-111 GEN
Solar/Wind Harmer
8.657
970031AG2-029 GEN
Solar/Wind Harmer
31.849
270044AE2-322 C
Solar/Wind Harmer
1.394
270404AC1-167 GEN
Solar/Wind Harmer
1.161
24642205MAYFLWER
Adder
0.667
25196008MFTGT1
Adder
1.411
247604X1-042
Adder
0.435
274752CRETE EC ;2U
Adder
8.515
274753CRETE EC ;3U
Adder
8.515
274772LINCOLN ;3U
Adder
8.715
274724RIVER EC ;11
Adder
18.285
274802UNIV PARK;5U
Adder
5.997
24728705AND G3
Adder
8.251
24728505AND G1
Adder
3.945
274826FISK ;BP
Adder
11.256
274800UNIV PARK;3U
Adder
5.993
972038AH1-567 GEN2
Adder
0.375
972228AH1-698 GEN2
Adder
3.807
274676JOLIET 29;8U
Adder
30.322
274729ELWOOD EC;1P
Adder
16.844
274730ELWOOD EC;6P
Adder
16.844
274734ELWOOD EC;8P
Adder
16.844
274736ELWOOD EC;9P
Adder
16.844
274682WAUKEGAN ;7U
Adder
9.773
964991AG1-363 GEN
Solar/Wind Helper
5.152
316097T157 G90
Solar/Wind Helper
1.508
23750701CROSSCHOOL
Solar/Wind Helper
1.51
238118U2-030_1
Solar/Wind Helper
0.344
238127S14_GEN_2
Solar/Wind Helper
0.832
238148AE2-230_GEN2
Solar/Wind Helper
0.498
237080AD1-060 GEN
Solar/Wind Helper
0.343
237038AE2-054 C
Solar/Wind Helper
0.273
235062AE1-101 C1
Solar/Wind Helper
1.665
23779801AA1-109
Solar/Wind Helper
0.194
237048AF1-022 C
Solar/Wind Helper
0.179
223401AF1-299 GEN
Solar/Wind Helper
0.369
316006AB2-029 C
Solar/Wind Helper
0.117
966131AG1-482 GEN
Solar/Wind Helper
0.078
233930AB2-032 GEN
Solar/Wind Helper
0.382
233915AB1-141 GEN
Solar/Wind Helper
0.504
232422X3-066 FULL
Solar/Wind Helper
0.115
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
233998TM1NIN_3.36
Solar/Wind Helper
0.262
232404W1-003 C
Solar/Wind Helper
0.509
232428Y3-058 C
Solar/Wind Helper
0.339
232434Z2-077 GEN
Solar/Wind Helper
0.127
233954AC2-188 GEN
Solar/Wind Helper
0.233
233950AC2-186 GEN
Solar/Wind Helper
0.117
233972AC1-094 C
Solar/Wind Helper
0.303
230511AF1-262
Solar/Wind Helper
0.015
316045AC1-158 PL2
Solar/Wind Helper
4.149
230434AG1-499 GEN
Solar/Wind Helper
0.231
228728W1-130C
Solar/Wind Helper
0.054
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219904AC1-010 C
Solar/Wind Helper
0.061
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.132
20720728JCB_W1-129
Solar/Wind Helper
0.057
207445AB1-138_GEN
Solar/Wind Helper
0.105
316254AC1-120 GEN1
Solar/Wind Helper
1.062
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.311
20715228NPK_W1-113
Solar/Wind Helper
0.078
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.497
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.023
207439AE1-081 C O1
Solar/Wind Helper
0.019
207437AD2-070 GEN
Solar/Wind Helper
0.138
207518AF1-320_GEN
Solar/Wind Helper
1.577
20671928W4-073
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.03
202652Y1-033 WT C
Solar/Wind Helper
0.5
961301AF2-421 GEN
Solar/Wind Helper
0.441
963151AG1-164 GEN
Solar/Wind Helper
0.441
970513AG2-328 GEN
Solar/Wind Harmer
4.981
970517AG2-330 GEN
Solar/Wind Harmer
4.518
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.671
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.268
MECLTFEXP_MEC->PJM
CLTF
15.978
SIGELTFEXP_SIGE->PJM
CLTF
0.507
LAGNLTFEXP_LAGN->PJM
CLTF
14.924
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.891
TVALTFEXP_TVA->PJM
CLTF
7.337
CPLELTFEXP_CPLE->PJM
CLTF
0.647
CBM West 2LTFEXP_CBM-W2->PJM
CBM
113.418
NYPJM->LTFIMP_NY
CLTF
4.819
LGEELTFEXP_LGEE->PJM
CLTF
6.781
WECLTFEXP_WEC->PJM
CLTF
3.842
AG2-052LTFEXP_AG2-052->PJM
LTF
0.241
AH1-155LTFEXP_AH1-155->PJM
LTF
0.361

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-025_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-025_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:131.94 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4919.93
MW Contribution:11.51
Bus #Bus NameTypeMW Contribution
270119AB2-067 GEN1
50/50
7.072
270120AB2-067 GEN2
50/50
7.072
24318905MLG2
50/50
7.067
270471AD2-092_GEN
Solar/Wind Harmer
4.467
946101AF1-275 GEN
Solar/Wind Harmer
1.815
942861AE2-305 GEN
Solar/Wind Harmer
9.088
970077AG2-063 GEN
Solar/Wind Harmer
6.239
270224U2-072_GEN2
Solar/Wind Harmer
2.282
270227U2-072_GEN3
Solar/Wind Harmer
2.282
270228U2-072_GEN4
Solar/Wind Harmer
2.282
270231U2-072_GEN5
Solar/Wind Harmer
2.282
938701AE1-092 GEN
Solar/Wind Harmer
23.824
964601AG1-323 GEN
Solar/Wind Harmer
3.66
964601AG1-323 GEN
Solar/Wind Harmer
1.702
270518AE2-148 GEN
Solar/Wind Harmer
13.886
972269AH1-719 GEN
Adder
2.575
972159AH1-661 GEN
Adder
1.116
253378AE2-206_GEN
Solar/Wind Harmer
4.007
276820AF1-078_GEN
Solar/Wind Harmer
1.78
971199AH1-059 GEN
Solar/Wind Harmer
4.428
241960AC2-195 GEN
Solar/Wind Harmer
3.072
25326509SID D
Adder
1.452
970879AG2-548 GEN
Solar/Wind Harmer
6.777
971073AG2-665 GEN
Solar/Wind Harmer
6.777
971073AG2-665 GEN
Solar/Wind Harmer
4.728
25326109MON D
Adder
1.444
25322209TAIT E
Adder
10.654
25322209TAIT E
Adder
10.414
253370AE2-315 SEC1
Adder
2.184
971201AH1-060 GEN
Solar/Wind Harmer
2.179
253394AE2-221_GEN
Solar/Wind Harmer
4.918
253398AE2-221_GEN2
Solar/Wind Harmer
4.918
246938BC-WTG3
Solar/Wind Harmer
4.299
246937BC-WTG2
Solar/Wind Harmer
4.226
971231AH1-075 GEN
Solar/Wind Harmer
0.861
253317AC1-085 GEN4
Solar/Wind Harmer
9.014
970611AG2-400 GEN
Solar/Wind Harmer
10.746
270007AE1-245 C
Solar/Wind Harmer
6.359
942801AE2-298 GEN
Solar/Wind Harmer
1.622
962581AG1-107 GEN
Solar/Wind Harmer
5.366
961491AF2-440 GEN
Solar/Wind Harmer
2.23
25183208HLCRTG
Solar/Wind Harmer
6.45
944541AF1-119 GEN
Solar/Wind Harmer
4.455
960971AF2-388 GEN
Solar/Wind Harmer
11.625
942221AE2-234 GEN
Solar/Wind Harmer
0.779
252519AF1-045_GEN
Solar/Wind Harmer
6.448
252516AE2-318_GEN
Solar/Wind Harmer
4.919
247621Y3-024
Adder
0.256
970883AG2-550 GEN
Solar/Wind Harmer
10.605
970885AG2-551 GEN
Solar/Wind Harmer
2.466
270201AC2-176 GEN
Solar/Wind Harmer
5.45
25194408D.CRK1
Adder
8.014
25194508D.CRK3
Adder
1.498
964611AG1-324 GEN
Solar/Wind Harmer
1.249
964611AG1-324 GEN
Solar/Wind Harmer
0.554
252509AD1-136 GEN
Solar/Wind Harmer
0.271
247620Y3-023
Adder
0.484
24728805RICHG1
Adder
3.969
24728905RICHG2
Adder
3.969
274770LINCOLN ;1U
Adder
8.688
274771LINCOLN ;2U
Adder
8.688
274808UNIV PK N;4U
Adder
5.124
274803UNIV PARK;6U
Adder
5.978
972259AH1-714 GEN
Adder
19.535
274674JOLIET 9 ;6U
Adder
15.727
274696ROCKY RD ;4P
Adder
11.554
274695ROCKY RD ;2P
Adder
11.287
274693ROCKY RD ;1P
Adder
11.176
274697ROCKY RD ;3P
Adder
3.066
23585401KL_K28_T16
Solar/Wind Helper
1.485
238120AE2-309 GEN
Solar/Wind Helper
0.526
238175AF1-290_GEN
Solar/Wind Helper
0.153
238169AE2-226 GEN1
Solar/Wind Helper
0.702
238170AE2-226 GEN2
Solar/Wind Helper
0.702
235020AA1-095 C
Solar/Wind Helper
0.053
23777901MDS_W4-102
Solar/Wind Helper
0.177
237002AB1-128_GEN
Solar/Wind Helper
0.444
237034AC2-136 C
Solar/Wind Helper
0.227
235063AE1-101 C2
Solar/Wind Helper
1.661
237001AB1-127_GEN
Solar/Wind Helper
0.442
23777801MSM_W1-116
Solar/Wind Helper
0.114
237025AB1-124 C
Solar/Wind Helper
0.164
237006AB1-125 GEN
Solar/Wind Helper
0.123
226929AD2-058 GEN
Solar/Wind Helper
0.099
205916AD1-020 GEN
Solar/Wind Helper
1.715
20390526W1-045 C
Solar/Wind Helper
0.35
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
233987AB2-037 GEN
Solar/Wind Helper
2.344
233933AB2-153 GEN
Solar/Wind Helper
0.233
232424Y1-079 C
Solar/Wind Helper
0.116
233944AB2-135 GEN
Solar/Wind Helper
0.589
233946AB2-136 GEN
Solar/Wind Helper
0.569
234036AF2-325 C
Solar/Wind Helper
0.042
233901CHERRYDALE C
Solar/Wind Helper
0.233
232408W1-005 C
Solar/Wind Helper
0.508
232410W1-006 C
Solar/Wind Helper
0.508
233939AC1-091 C
Solar/Wind Helper
0.35
233970AC1-092 C
Solar/Wind Helper
0.35
315651AD1-115 GEN
Solar/Wind Helper
0.785
316447AC1-158 HLD
Solar/Wind Helper
2.848
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.04
219921AF1-264
Solar/Wind Helper
0.051
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.082
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.19
20716928W4-060COL
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.016
20673828FLE_V3-070
Solar/Wind Helper
0.091
207442AE1-156 GEN
Solar/Wind Helper
0.326
20676128MHD_W3-029
Solar/Wind Helper
0.096
20671828STAW2-080
Solar/Wind Helper
0.027
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
207471AF2-354 C
Solar/Wind Helper
0.169
20674928WA_W3-044
Solar/Wind Helper
0.098
20676228FRD_X1-012
Solar/Wind Helper
0.092
964851AG1-348 GEN
Solar/Wind Helper
0.081
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.045
211065PSPA IPP
Solar/Wind Helper
0.152
211065PSPA IPP
Solar/Wind Helper
0.152
970321AG2-212 GEN
Solar/Wind Harmer
3.728
962771AG1-126 GEN
Solar/Wind Harmer
41.012
972239AH1-704 GEN
Adder
2.683
270459AD2-067 GEN
Solar/Wind Harmer
10.243
961821AG1-024 GEN
Solar/Wind Harmer
10.399
270054AF2-122 C O1
Solar/Wind Harmer
3.993
270520AE2-214 GEN
Solar/Wind Harmer
7.274
270284AF1-227 GEN1
Solar/Wind Harmer
6.791
270286AF1-227 GEN2
Solar/Wind Harmer
2.512
270287AF1-227 GEN3
Solar/Wind Harmer
2.512
253383AE2-342_GEN
Solar/Wind Harmer
1.045
241973AD2-163_GEN1
Solar/Wind Harmer
2.33
945631AF1-228 GEN
Solar/Wind Harmer
5.461
943861AF1-054 GEN
Solar/Wind Harmer
4.486
943851AF1-053 GEN
Solar/Wind Harmer
2.168
270156DARBY CT1
Adder
10.416
270157DARBY CT2
Adder
10.391
270158DARBY CT3
Adder
10.225
970689AG2-444 GEN
Solar/Wind Harmer
18.82
270578AF1-285 GEN2
Solar/Wind Harmer
0.537
270432AC2-029 GEN
Solar/Wind Harmer
8.046
270302AB2-170 GEN
Solar/Wind Harmer
9.546
270317AD1-130_GEN
Solar/Wind Harmer
3.66
940611AE2-048 GEN
Solar/Wind Harmer
25.033
941391AE2-136 GEN
Solar/Wind Harmer
12.972
270269AC2-059
Solar/Wind Harmer
10.602
241972AD1-140 GEN
Solar/Wind Harmer
5.021
958581AF2-149 GEN
Solar/Wind Harmer
4.736
970179AG2-119 GEN
Solar/Wind Harmer
8.837
270340AC2-060 GEN
Solar/Wind Harmer
3.346
970879AG2-548 GEN
Solar/Wind Harmer
4.728
253372AE2-315 SEC3
Adder
2.066
253372AE2-315 SEC3
Adder
2.066
25306009OHH W.
Adder
3.134
253349AC2-067 GEN
Solar/Wind Harmer
5.408
253400AC2-068 GEN
Solar/Wind Harmer
2.175
957201AF2-014 GEN
Solar/Wind Harmer
4.898
270435AC2-044 GEN
Solar/Wind Harmer
2.16
965051AG1-369 GEN
Solar/Wind Harmer
5.366
965041AG1-368 GEN
Solar/Wind Harmer
10.722
247607V1-011 GEN
Solar/Wind Harmer
4.239
971567AH1-282 GEN
Solar/Wind Harmer
16.059
966831AG1-554 GEN
Solar/Wind Harmer
1.279
971989AH1-539 GEN
Solar/Wind Harmer
13.833
24729505KEY G4
Adder
6.928
963791AG1-232 GEN
Solar/Wind Harmer
14.415
270071AF1-092 GEN
Solar/Wind Harmer
16.001
971985AH1-537 GEN
Solar/Wind Harmer
18.998
958711AF2-162 GEN
Solar/Wind Harmer
1.076
270024AE2-089 GEN
Solar/Wind Harmer
4.99
270367AC2-061_GEN
Solar/Wind Harmer
3.379
965101AG1-375 GEN
Solar/Wind Harmer
10.622
971673AH1-337 GEN
Solar/Wind Harmer
4.88
252524AE2-267 GEN
Solar/Wind Harmer
1.673
971029AG2-637 GEN
Solar/Wind Harmer
15.909
25196408WSDLE3
Adder
9.356
25196308WSDLE2
Adder
9.275
25196208WSDLE1
Adder
9.252
25196708WSDLE6
Adder
9.228
25196508WSDLE4
Adder
8.996
270543AE2-219 C
Solar/Wind Harmer
5.43
961761AG1-017 GEN
Solar/Wind Harmer
0.454
945581AF1-223 GEN
Solar/Wind Harmer
4.805
270297AD1-101 GEN
Solar/Wind Harmer
2.947
944031AF1-071 GEN
Solar/Wind Harmer
1.064
25196108MFTGT2
Adder
1.601
25196108MFTGT2
Adder
1.486
274775LINCOLN ;6U
Adder
8.688
274776LINCOLN ;7U
Adder
8.688
274777LINCOLN ;8U
Adder
8.688
274814UNIV PK N;0U
Adder
5.192
274807UNIV PK N;3U
Adder
5.18
274805UNIV PK N;1U
Adder
5.158
274811UNIV PK N;7U
Adder
5.147
972037AH1-567 GEN1
Adder
0.188
274827FISK ;RP
Adder
7.953
972227AH1-698 GEN1
Adder
2.673
274687WILL CNTY;4U
Adder
28.564
274687WILL CNTY;4U
Adder
28.564
274675JOLIET 29;7U
Adder
31.348
274675JOLIET 29;7U
Adder
30.228
274731ELWOOD EC;2P
Adder
16.792
274733ELWOOD EC;3P
Adder
16.792
274735ELWOOD EC;4P
Adder
16.792
274728ELWOOD EC;5P
Adder
16.792
972203AH1-686 GEN
Adder
2.344
274746AC1-111 G10
Adder
5.687
274744AC1-111 GEN8
Adder
5.687
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238126S14_GEN_1
Solar/Wind Helper
0.829
238152AF2-075_GEN
Solar/Wind Helper
0.708
238208AF1-136 C
Solar/Wind Helper
0.22
23546401DTGZ2-030
Solar/Wind Helper
0.089
237085AD2-009_GEN
Solar/Wind Helper
1.651
3138216PACIFIC
Solar/Wind Helper
0.044
316411AF1-147_GEN1
Solar/Wind Helper
0.889
316415AF1-147_GEN2
Solar/Wind Helper
0.889
23750501ELLIOTTS
Solar/Wind Helper
0.64
959381AF2-229 GEN
Solar/Wind Helper
0.358
3141426STAFORD
Solar/Wind Helper
0.052
960921AF2-383 GEN
Solar/Wind Helper
0.182
205943AE1-185 GEN
Solar/Wind Helper
0.51
205932AD2-116_GEN
Solar/Wind Helper
0.509
205956AE1-196_GEN
Solar/Wind Helper
0.509
233935AB2-179 C
Solar/Wind Helper
1.27
232436AB1-176 C
Solar/Wind Helper
0.044
233923SMA
Solar/Wind Helper
0.959
233990AG1-397 GEN
Solar/Wind Helper
0.03
234033AF1-007_GEN
Solar/Wind Helper
7.028
232432Z2-076 GEN
Solar/Wind Helper
0.067
964001AG1-254 GEN
Solar/Wind Helper
0.957
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.115
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.08
203975AE1-071-GEN
Solar/Wind Helper
2.501
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.29
219620RIDERU C
Solar/Wind Helper
0.001
316164AC1-076 GEN
Solar/Wind Helper
1.097
20675528CPH_W2-050
Solar/Wind Helper
0.087
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
218524CNTRALGAS1 C
Solar/Wind Helper
0.161
966261AG1-495 GEN
Solar/Wind Helper
0.081
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20675928HOL_W4-097
Solar/Wind Helper
0.05
207484AF2-139 C O1
Solar/Wind Helper
0.084
20674828DL_W4-046
Solar/Wind Helper
0.008
207408W3-077 C
Solar/Wind Helper
0.084
270166AC1-044 GEN3
50/50
7.072
23559101PLEAS2
50/50
6.183
962761AG1-125 GEN
Solar/Wind Harmer
41.012
970149AG2-104 GEN
Solar/Wind Harmer
50.65
970155AG2-107 GEN
Solar/Wind Harmer
17.883
270349AD2-093_GEN
Solar/Wind Harmer
4.467
24721705FLATG2
Adder
23.989
270159DARBY CT4
Adder
10.25
970593AG2-378 GEN
Solar/Wind Harmer
2.311
270223U2-072_GEN1
Solar/Wind Harmer
2.282
270578AF1-285 GEN2
Solar/Wind Harmer
1.396
270391AF1-285 GEN3
Solar/Wind Harmer
1.396
253343AC1-166 GEN
Solar/Wind Harmer
1.241
253325AC1-069 GEN
Solar/Wind Harmer
1.197
270462AD2-086
Solar/Wind Harmer
7.941
971995AH1-542 GEN
Solar/Wind Harmer
12.502
270263AC1-001 GEN
Solar/Wind Harmer
1.177
25326309TAIT D
Adder
1.197
960071AF2-298 GEN
Solar/Wind Harmer
5.441
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.066
241813AF1-122_GEN
Solar/Wind Harmer
6.974
927014AC1-188 GEN
Solar/Wind Harmer
1.725
270510AE1-227 GEN1
Solar/Wind Harmer
2.689
246936BC-WTG1
Solar/Wind Harmer
4.226
270489AE1-102 GEN1
Solar/Wind Harmer
1.404
965421AG1-410 GEN
Solar/Wind Harmer
32.386
960001AF2-291 GEN
Solar/Wind Harmer
3.255
253432AC1-085 GEN2
Solar/Wind Harmer
0.288
946171AF1-282 GEN
Solar/Wind Harmer
10.761
247521TR3_G114
Solar/Wind Harmer
3.613
270246TR4_N_V150
Solar/Wind Harmer
0.914
965011AG1-365 GEN
Solar/Wind Harmer
10.746
24695305TIMB G C
Solar/Wind Harmer
5.901
965651AG1-433 GEN
Solar/Wind Harmer
5.813
958861AF2-177 GEN
Solar/Wind Harmer
11.61
247536S-71 GEN
Solar/Wind Harmer
4.293
25194608D.CRK4
Adder
1.742
945371AF1-202 GEN
Solar/Wind Harmer
7.392
252507AC2-088 GEN
Solar/Wind Harmer
1.899
270063AE2-323 C
Solar/Wind Harmer
2.33
25196808ZIMRHP
Adder
79.831
24639705ELKHART HY
Adder
0.161
25196008MFTGT1
Adder
1.452
274751CRETE EC ;1U
Adder
8.489
274754CRETE EC ;4U
Adder
8.489
274773LINCOLN ;4U
Adder
8.688
274774LINCOLN ;5U
Adder
8.688
274723RIVER EC ;12
Adder
18.445
274812UNIV PK N;8U
Adder
5.147
24728605AND G2
Adder
3.933
274801UNIV PARK;4U
Adder
5.975
274676JOLIET 29;8U
Adder
31.348
274732ELWOOD EC;7P
Adder
16.792
274674JOLIET 9 ;6U
Adder
15.727
274745AC1-111 GEN9
Adder
5.687
970091AG2-072 GEN
Adder
77.755
316095T157 G97
Solar/Wind Helper
1.505
23583801GRNGAP
Solar/Wind Helper
5.606
238185AF2-356 C
Solar/Wind Helper
2.651
238108AE1-109 GEN1
Solar/Wind Helper
0.114
235054AD2-180 GEN
Solar/Wind Helper
2.034
235531U2-073 GEN
Solar/Wind Helper
3.288
238117U2-030
Solar/Wind Helper
0.342
238147AE2-230_GEN1
Solar/Wind Helper
0.495
238149AF1-291A_GEN
Solar/Wind Helper
0.141
23751201ROTHROCK
Solar/Wind Helper
0.826
23562501BACKB
Solar/Wind Helper
1.01
237061AD1-155 GEN
Solar/Wind Helper
0.053
238221AF1-254 C O1
Solar/Wind Helper
0.275
235067AD1-061 GEN
Solar/Wind Helper
0.496
23751101LEADS_P59
Solar/Wind Helper
1.41
237030AB1-096 C
Solar/Wind Helper
0.071
3141196NOKESVL
Solar/Wind Helper
1.032
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.346
223402AF1-300 C
Solar/Wind Helper
0.368
205917AD1-020 ES
Solar/Wind Helper
0.369
233982AB2-133 GEN
Solar/Wind Helper
0.358
233918AB1-142 GEN
Solar/Wind Helper
0.503
233994AC2-023 GEN
Solar/Wind Helper
0.962
233996TM1833_GEN
Solar/Wind Helper
0.262
233997TMININ_4.2
Solar/Wind Helper
0.262
232406W1-004 FULL
Solar/Wind Helper
0.508
233940AF2-379 C
Solar/Wind Helper
0.062
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.233
233971AC1-093 C
Solar/Wind Helper
0.358
316044AC1-158 PL1
Solar/Wind Helper
1.294
316450AC1-158 RIC
Solar/Wind Helper
0.345
230430AE1-229_GEN
Solar/Wind Helper
3.376
230415AB2-049 C
Solar/Wind Helper
0.03
228729W2-030 C
Solar/Wind Helper
0.111
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.15
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
219348LDSOLAR C
Solar/Wind Helper
0.115
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.063
20716028EGP_W2-019
Solar/Wind Helper
0.019
24318805MLG1
50/50
10.115
23559001PLEAS1
50/50
6.183
270051AF1-062 GEN
50/50
11.828
270475AD2-096_GEN
50/50
7.148
970153AG2-106 GEN
Solar/Wind Harmer
17.883
961921AG1-034 GEN
Solar/Wind Harmer
15.599
24721905FLATG4
Adder
23.989
241955AC1-078 GEN
Solar/Wind Harmer
8.811
241974AD2-163_GEN2
Solar/Wind Harmer
2.33
942051AE2-217 GEN
Solar/Wind Harmer
21.044
960801AF2-371 GEN
Solar/Wind Harmer
2.947
964871AG1-351 GEN
Solar/Wind Harmer
2.035
970605AG2-385 GEN
Solar/Wind Harmer
6.239
942871AE2-306 GEN
Solar/Wind Harmer
1.047
270391AF1-285 GEN3
Solar/Wind Harmer
0.537
253338AC1-165 GEN
Solar/Wind Harmer
1.241
253333AC1-068 GEN
Solar/Wind Harmer
1.197
270485AE1-090_GEN
Solar/Wind Harmer
0.69
270273AD2-016 GEN
Solar/Wind Harmer
3.032
972173AH1-669 GEN
Solar/Wind Harmer
5.669
253415AE1-040 GEN
Solar/Wind Harmer
1.248
270291AC1-194 GEN
Solar/Wind Harmer
11.736
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.066
970065AG2-057 GEN
Solar/Wind Harmer
1.09
957541AF2-048 GEN
Solar/Wind Harmer
1.72
270512AE1-227 GEN2
Solar/Wind Harmer
2.283
253406AD2-031_GEN
Solar/Wind Harmer
1.388
270491AE1-102 GEN2
Solar/Wind Harmer
1.404
971191AH1-055 GEN
Solar/Wind Harmer
23.693
270377AD1-106 GEN
Solar/Wind Harmer
6.649
253316AC1-085 GEN3
Solar/Wind Harmer
9.014
253433AC1-085 GEN1
Solar/Wind Harmer
5.722
946181AF1-283 GEN
Solar/Wind Harmer
13.99
270191TR4_S_V150
Solar/Wind Harmer
3.224
270247TR4_N_V136
Solar/Wind Harmer
0.914
959331AF2-224 GEN
Solar/Wind Harmer
10.746
965021AG1-366 GEN
Solar/Wind Harmer
2.499
958091AF2-103 GEN
Solar/Wind Harmer
0.173
270588AE1-091_GEN
Solar/Wind Harmer
11.789
944531AF1-118 GEN
Solar/Wind Harmer
37.432
270043AE2-236 GEN
Solar/Wind Harmer
5.876
270258AD1-119 GEN
Solar/Wind Harmer
2.963
971617AH1-308 GEN
Solar/Wind Harmer
6.181
25196608WSDLE5
Adder
9.089
962031AG1-047 GEN
Solar/Wind Harmer
3.205
252510AF1-249 C
Solar/Wind Harmer
0.443
957741AF2-068 GEN
Solar/Wind Harmer
15.904
25194608D.CRK4
Adder
1.742
270222AC2-111 GEN
Solar/Wind Harmer
8.632
970031AG2-029 GEN
Solar/Wind Harmer
31.759
270044AE2-322 C
Solar/Wind Harmer
1.391
270404AC1-167 GEN
Solar/Wind Harmer
1.158
24642205MAYFLWER
Adder
0.665
25196008MFTGT1
Adder
1.406
247604X1-042
Adder
0.434
274752CRETE EC ;2U
Adder
8.489
274753CRETE EC ;3U
Adder
8.489
274772LINCOLN ;3U
Adder
8.688
274724RIVER EC ;11
Adder
18.229
24728705AND G3
Adder
8.226
274802UNIV PARK;5U
Adder
5.978
24728505AND G1
Adder
3.933
274826FISK ;BP
Adder
11.221
274800UNIV PARK;3U
Adder
5.975
972038AH1-567 GEN2
Adder
0.374
972228AH1-698 GEN2
Adder
3.796
274676JOLIET 29;8U
Adder
30.228
274729ELWOOD EC;1P
Adder
16.792
274730ELWOOD EC;6P
Adder
16.792
274734ELWOOD EC;8P
Adder
16.792
274736ELWOOD EC;9P
Adder
16.792
274682WAUKEGAN ;7U
Adder
9.742
964991AG1-363 GEN
Solar/Wind Helper
5.141
316097T157 G90
Solar/Wind Helper
1.505
23750701CROSSCHOOL
Solar/Wind Helper
1.505
238118U2-030_1
Solar/Wind Helper
0.342
238127S14_GEN_2
Solar/Wind Helper
0.829
238148AE2-230_GEN2
Solar/Wind Helper
0.497
237080AD1-060 GEN
Solar/Wind Helper
0.342
237038AE2-054 C
Solar/Wind Helper
0.272
235062AE1-101 C1
Solar/Wind Helper
1.661
23779801AA1-109
Solar/Wind Helper
0.193
237048AF1-022 C
Solar/Wind Helper
0.178
223401AF1-299 GEN
Solar/Wind Helper
0.368
316006AB2-029 C
Solar/Wind Helper
0.117
966131AG1-482 GEN
Solar/Wind Helper
0.077
233930AB2-032 GEN
Solar/Wind Helper
0.381
233915AB1-141 GEN
Solar/Wind Helper
0.503
232422X3-066 FULL
Solar/Wind Helper
0.114
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
233998TM1NIN_3.36
Solar/Wind Helper
0.262
232404W1-003 C
Solar/Wind Helper
0.508
232428Y3-058 C
Solar/Wind Helper
0.338
233954AC2-188 GEN
Solar/Wind Helper
0.233
233950AC2-186 GEN
Solar/Wind Helper
0.116
232434Z2-077 GEN
Solar/Wind Helper
0.127
233972AC1-094 C
Solar/Wind Helper
0.303
316045AC1-158 PL2
Solar/Wind Helper
4.142
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.23
228728W1-130C
Solar/Wind Helper
0.054
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219904AC1-010 C
Solar/Wind Helper
0.061
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.131
20720728JCB_W1-129
Solar/Wind Helper
0.057
316254AC1-120 GEN1
Solar/Wind Helper
1.06
207445AB1-138_GEN
Solar/Wind Helper
0.104
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.31
20715228NPK_W1-113
Solar/Wind Helper
0.078
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.496
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
207437AD2-070 GEN
Solar/Wind Helper
0.138
207518AF1-320_GEN
Solar/Wind Helper
1.573
20671928W4-073
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.03
970513AG2-328 GEN
Solar/Wind Harmer
3.728
970517AG2-330 GEN
Solar/Wind Harmer
3.381
20675728RH_W2-091
Solar/Wind Helper
0.137
20675128HRM_W1-127
Solar/Wind Helper
0.03
209116AE2-175 GEN
Solar/Wind Helper
1.781
20715028HAN_X4-015
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.353
219276PARKLANDSO C
Solar/Wind Helper
0.089
20714528FRN_Y2-051
Solar/Wind Helper
0.057
20720528MAN_W1-024
Solar/Wind Helper
0.028
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.027
219249CENTRALDIV C
Solar/Wind Helper
0.01
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.089
970245AG2-165 GEN
Solar/Wind Harmer
3.728
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.265
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.153
MECLTFEXP_MEC->PJM
CLTF
15.925
SIGELTFEXP_SIGE->PJM
CLTF
0.506
LAGNLTFEXP_LAGN->PJM
CLTF
14.864
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.83
TVALTFEXP_TVA->PJM
CLTF
7.306
CPLELTFEXP_CPLE->PJM
CLTF
0.632
CBM West 2LTFEXP_CBM-W2->PJM
CBM
113.005
NYPJM->LTFIMP_NY
CLTF
4.803
LGEELTFEXP_LGEE->PJM
CLTF
6.759
WECLTFEXP_WEC->PJM
CLTF
3.83
AG2-052LTFEXP_AG2-052->PJM
LTF
0.24
AH1-155LTFEXP_AH1-155->PJM
LTF
0.36

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-014_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:131.63 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4908.47
MW Contribution:11.51
Bus #Bus NameTypeMW Contribution
24318805MLG1
50/50
10.098
23559001PLEAS1
50/50
6.112
270051AF1-062 GEN
50/50
11.831
23684201S70BUS2
50/50
0.171
270475AD2-096_GEN
50/50
7.147
970153AG2-106 GEN
Solar/Wind Harmer
17.867
961921AG1-034 GEN
Solar/Wind Harmer
15.607
241955AC1-078 GEN
Solar/Wind Harmer
8.813
24721905FLATG4
Adder
23.946
241974AD2-163_GEN2
Solar/Wind Harmer
2.331
942051AE2-217 GEN
Solar/Wind Harmer
21.048
960801AF2-371 GEN
Solar/Wind Harmer
2.948
964871AG1-351 GEN
Solar/Wind Harmer
2.036
970605AG2-385 GEN
Solar/Wind Harmer
6.24
942871AE2-306 GEN
Solar/Wind Harmer
1.047
270391AF1-285 GEN3
Solar/Wind Harmer
0.537
253338AC1-165 GEN
Solar/Wind Harmer
1.242
253333AC1-068 GEN
Solar/Wind Harmer
1.197
270485AE1-090_GEN
Solar/Wind Harmer
0.69
270273AD2-016 GEN
Solar/Wind Harmer
3.033
972173AH1-669 GEN
Solar/Wind Harmer
5.671
270291AC1-194 GEN
Solar/Wind Harmer
11.744
253415AE1-040 GEN
Solar/Wind Harmer
1.248
270512AE1-227 GEN2
Solar/Wind Harmer
2.315
970065AG2-057 GEN
Solar/Wind Harmer
1.09
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.065
957541AF2-048 GEN
Solar/Wind Harmer
1.721
253406AD2-031_GEN
Solar/Wind Harmer
1.388
270491AE1-102 GEN2
Solar/Wind Harmer
1.404
270377AD1-106 GEN
Solar/Wind Harmer
6.655
971191AH1-055 GEN
Solar/Wind Harmer
23.692
253316AC1-085 GEN3
Solar/Wind Harmer
9.013
253433AC1-085 GEN1
Solar/Wind Harmer
5.721
946181AF1-283 GEN
Solar/Wind Harmer
13.988
270191TR4_S_V150
Solar/Wind Harmer
3.223
270247TR4_N_V136
Solar/Wind Harmer
0.914
959331AF2-224 GEN
Solar/Wind Harmer
10.743
965021AG1-366 GEN
Solar/Wind Harmer
2.498
270588AE1-091_GEN
Solar/Wind Harmer
11.792
958091AF2-103 GEN
Solar/Wind Harmer
0.173
944531AF1-118 GEN
Solar/Wind Harmer
37.418
270043AE2-236 GEN
Solar/Wind Harmer
5.874
270258AD1-119 GEN
Solar/Wind Harmer
2.962
971617AH1-308 GEN
Solar/Wind Harmer
6.179
25196608WSDLE5
Adder
9.087
252510AF1-249 C
Solar/Wind Harmer
0.443
962031AG1-047 GEN
Solar/Wind Harmer
3.204
957741AF2-068 GEN
Solar/Wind Harmer
15.899
25194608D.CRK4
Adder
1.742
270222AC2-111 GEN
Solar/Wind Harmer
8.63
970031AG2-029 GEN
Solar/Wind Harmer
31.748
270044AE2-322 C
Solar/Wind Harmer
1.39
270404AC1-167 GEN
Solar/Wind Harmer
1.158
24642205MAYFLWER
Adder
0.665
25196008MFTGT1
Adder
1.406
247604X1-042
Adder
0.433
274752CRETE EC ;2U
Adder
8.485
274753CRETE EC ;3U
Adder
8.485
274772LINCOLN ;3U
Adder
8.684
274724RIVER EC ;11
Adder
18.221
24728705AND G3
Adder
8.223
274802UNIV PARK;5U
Adder
5.976
24728505AND G1
Adder
3.932
274826FISK ;BP
Adder
11.216
274800UNIV PARK;3U
Adder
5.972
972038AH1-567 GEN2
Adder
0.374
972228AH1-698 GEN2
Adder
3.794
274676JOLIET 29;8U
Adder
30.215
274729ELWOOD EC;1P
Adder
16.784
274730ELWOOD EC;6P
Adder
16.784
274734ELWOOD EC;8P
Adder
16.784
274736ELWOOD EC;9P
Adder
16.784
274682WAUKEGAN ;7U
Adder
9.459
964991AG1-363 GEN
Solar/Wind Helper
5.14
316097T157 G90
Solar/Wind Helper
1.505
23750701CROSSCHOOL
Solar/Wind Helper
1.501
238118U2-030_1
Solar/Wind Helper
0.341
238127S14_GEN_2
Solar/Wind Helper
0.826
238148AE2-230_GEN2
Solar/Wind Helper
0.497
237080AD1-060 GEN
Solar/Wind Helper
0.342
237038AE2-054 C
Solar/Wind Helper
0.272
235062AE1-101 C1
Solar/Wind Helper
1.661
23779801AA1-109
Solar/Wind Helper
0.193
237048AF1-022 C
Solar/Wind Helper
0.177
223401AF1-299 GEN
Solar/Wind Helper
0.368
316006AB2-029 C
Solar/Wind Helper
0.117
966131AG1-482 GEN
Solar/Wind Helper
0.077
233930AB2-032 GEN
Solar/Wind Helper
0.381
233915AB1-141 GEN
Solar/Wind Helper
0.503
232422X3-066 FULL
Solar/Wind Helper
0.114
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
233998TM1NIN_3.36
Solar/Wind Helper
0.262
232404W1-003 C
Solar/Wind Helper
0.508
232428Y3-058 C
Solar/Wind Helper
0.338
232434Z2-077 GEN
Solar/Wind Helper
0.127
233954AC2-188 GEN
Solar/Wind Helper
0.233
233950AC2-186 GEN
Solar/Wind Helper
0.116
233972AC1-094 C
Solar/Wind Helper
0.303
316045AC1-158 PL2
Solar/Wind Helper
4.142
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.23
228728W1-130C
Solar/Wind Helper
0.054
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219904AC1-010 C
Solar/Wind Helper
0.06
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.131
20720728JCB_W1-129
Solar/Wind Helper
0.057
316254AC1-120 GEN1
Solar/Wind Helper
1.061
207445AB1-138_GEN
Solar/Wind Helper
0.104
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.31
20715228NPK_W1-113
Solar/Wind Helper
0.078
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.496
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
207437AD2-070 GEN
Solar/Wind Helper
0.138
207518AF1-320_GEN
Solar/Wind Helper
1.573
20671928W4-073
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.03
970513AG2-328 GEN
Solar/Wind Harmer
3.726
970517AG2-330 GEN
Solar/Wind Harmer
3.379
270166AC1-044 GEN3
50/50
7.063
23559101PLEAS2
50/50
6.112
23684101S70BUS1
50/50
0.168
962761AG1-125 GEN
Solar/Wind Harmer
40.976
970149AG2-104 GEN
Solar/Wind Harmer
50.605
970155AG2-107 GEN
Solar/Wind Harmer
17.867
270349AD2-093_GEN
Solar/Wind Harmer
4.466
24721705FLATG2
Adder
23.946
270159DARBY CT4
Adder
10.253
970593AG2-378 GEN
Solar/Wind Harmer
2.311
270223U2-072_GEN1
Solar/Wind Harmer
2.282
270578AF1-285 GEN2
Solar/Wind Harmer
1.396
270391AF1-285 GEN3
Solar/Wind Harmer
1.396
253343AC1-166 GEN
Solar/Wind Harmer
1.242
253325AC1-069 GEN
Solar/Wind Harmer
1.197
270462AD2-086
Solar/Wind Harmer
7.941
971995AH1-542 GEN
Solar/Wind Harmer
12.507
270263AC1-001 GEN
Solar/Wind Harmer
1.177
270510AE1-227 GEN1
Solar/Wind Harmer
2.727
25326309TAIT D
Adder
1.197
241813AF1-122_GEN
Solar/Wind Harmer
6.978
960071AF2-298 GEN
Solar/Wind Harmer
5.44
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.065
927014AC1-188 GEN
Solar/Wind Harmer
1.725
246936BC-WTG1
Solar/Wind Harmer
4.226
270489AE1-102 GEN1
Solar/Wind Harmer
1.404
965421AG1-410 GEN
Solar/Wind Harmer
32.379
960001AF2-291 GEN
Solar/Wind Harmer
3.256
253432AC1-085 GEN2
Solar/Wind Harmer
0.288
946171AF1-282 GEN
Solar/Wind Harmer
10.76
247521TR3_G114
Solar/Wind Harmer
3.612
270246TR4_N_V150
Solar/Wind Harmer
0.914
965011AG1-365 GEN
Solar/Wind Harmer
10.743
24695305TIMB G C
Solar/Wind Harmer
5.899
965651AG1-433 GEN
Solar/Wind Harmer
5.811
958861AF2-177 GEN
Solar/Wind Harmer
11.606
247536S-71 GEN
Solar/Wind Harmer
4.292
25194608D.CRK4
Adder
1.742
945371AF1-202 GEN
Solar/Wind Harmer
7.39
252507AC2-088 GEN
Solar/Wind Harmer
1.898
270063AE2-323 C
Solar/Wind Harmer
2.329
25196808ZIMRHP
Adder
79.816
24639705ELKHART HY
Adder
0.161
25196008MFTGT1
Adder
1.452
274751CRETE EC ;1U
Adder
8.485
274754CRETE EC ;4U
Adder
8.485
274773LINCOLN ;4U
Adder
8.684
274774LINCOLN ;5U
Adder
8.684
274723RIVER EC ;12
Adder
18.437
274812UNIV PK N;8U
Adder
5.144
24728605AND G2
Adder
3.932
274801UNIV PARK;4U
Adder
5.972
274676JOLIET 29;8U
Adder
31.334
274732ELWOOD EC;7P
Adder
16.784
274674JOLIET 9 ;6U
Adder
15.72
274745AC1-111 GEN9
Adder
5.685
970091AG2-072 GEN
Adder
77.715
316095T157 G97
Solar/Wind Helper
1.505
23583801GRNGAP
Solar/Wind Helper
5.607
238185AF2-356 C
Solar/Wind Helper
2.642
238108AE1-109 GEN1
Solar/Wind Helper
0.114
235054AD2-180 GEN
Solar/Wind Helper
2.025
235531U2-073 GEN
Solar/Wind Helper
3.278
238117U2-030
Solar/Wind Helper
0.341
238147AE2-230_GEN1
Solar/Wind Helper
0.495
238149AF1-291A_GEN
Solar/Wind Helper
0.141
237061AD1-155 GEN
Solar/Wind Helper
0.053
23751201ROTHROCK
Solar/Wind Helper
0.819
238221AF1-254 C O1
Solar/Wind Helper
0.275
23562501BACKB
Solar/Wind Helper
1.001
235067AD1-061 GEN
Solar/Wind Helper
0.496
23751101LEADS_P59
Solar/Wind Helper
1.388
237030AB1-096 C
Solar/Wind Helper
0.071
3141196NOKESVL
Solar/Wind Helper
1.033
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.346
223402AF1-300 C
Solar/Wind Helper
0.368
205917AD1-020 ES
Solar/Wind Helper
0.369
233982AB2-133 GEN
Solar/Wind Helper
0.358
233918AB1-142 GEN
Solar/Wind Helper
0.503
233994AC2-023 GEN
Solar/Wind Helper
0.962
233996TM1833_GEN
Solar/Wind Helper
0.262
233997TMININ_4.2
Solar/Wind Helper
0.262
232406W1-004 FULL
Solar/Wind Helper
0.508
233940AF2-379 C
Solar/Wind Helper
0.062
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.233
233971AC1-093 C
Solar/Wind Helper
0.358
316044AC1-158 PL1
Solar/Wind Helper
1.294
316450AC1-158 RIC
Solar/Wind Helper
0.345
230430AE1-229_GEN
Solar/Wind Helper
3.376
230415AB2-049 C
Solar/Wind Helper
0.03
228729W2-030 C
Solar/Wind Helper
0.111
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.15
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
219348LDSOLAR C
Solar/Wind Helper
0.115
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.063
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.354
219276PARKLANDSO C
Solar/Wind Helper
0.089
20714528FRN_Y2-051
Solar/Wind Helper
0.057
20720528MAN_W1-024
Solar/Wind Helper
0.028
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.027
219249CENTRALDIV C
Solar/Wind Helper
0.01
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.089
970245AG2-165 GEN
Solar/Wind Harmer
3.726
270119AB2-067 GEN1
50/50
7.063
270120AB2-067 GEN2
50/50
7.063
24318905MLG2
50/50
7.074
270471AD2-092_GEN
Solar/Wind Harmer
4.466
946101AF1-275 GEN
Solar/Wind Harmer
1.816
942861AE2-305 GEN
Solar/Wind Harmer
9.089
970077AG2-063 GEN
Solar/Wind Harmer
6.24
270224U2-072_GEN2
Solar/Wind Harmer
2.282
270227U2-072_GEN3
Solar/Wind Harmer
2.282
270228U2-072_GEN4
Solar/Wind Harmer
2.282
270231U2-072_GEN5
Solar/Wind Harmer
2.282
938701AE1-092 GEN
Solar/Wind Harmer
23.829
964601AG1-323 GEN
Solar/Wind Harmer
3.66
964601AG1-323 GEN
Solar/Wind Harmer
1.702
270518AE2-148 GEN
Solar/Wind Harmer
13.889
972269AH1-719 GEN
Adder
2.587
972159AH1-661 GEN
Adder
1.119
253378AE2-206_GEN
Solar/Wind Harmer
4.007
276820AF1-078_GEN
Solar/Wind Harmer
1.78
971199AH1-059 GEN
Solar/Wind Harmer
4.433
241960AC2-195 GEN
Solar/Wind Harmer
3.073
25326509SID D
Adder
1.452
970879AG2-548 GEN
Solar/Wind Harmer
6.78
971073AG2-665 GEN
Solar/Wind Harmer
6.78
971073AG2-665 GEN
Solar/Wind Harmer
4.73
25326109MON D
Adder
1.444
25322209TAIT E
Adder
10.653
25322209TAIT E
Adder
10.414
971201AH1-060 GEN
Solar/Wind Harmer
2.181
253370AE2-315 SEC1
Adder
2.184
253394AE2-221_GEN
Solar/Wind Harmer
4.918
253398AE2-221_GEN2
Solar/Wind Harmer
4.918
246938BC-WTG3
Solar/Wind Harmer
4.299
246937BC-WTG2
Solar/Wind Harmer
4.226
971231AH1-075 GEN
Solar/Wind Harmer
0.862
253317AC1-085 GEN4
Solar/Wind Harmer
9.013
970611AG2-400 GEN
Solar/Wind Harmer
10.743
270007AE1-245 C
Solar/Wind Harmer
6.358
942801AE2-298 GEN
Solar/Wind Harmer
1.622
962581AG1-107 GEN
Solar/Wind Harmer
5.365
961491AF2-440 GEN
Solar/Wind Harmer
2.229
25183208HLCRTG
Solar/Wind Harmer
6.449
944541AF1-119 GEN
Solar/Wind Harmer
4.453
960971AF2-388 GEN
Solar/Wind Harmer
11.621
942221AE2-234 GEN
Solar/Wind Harmer
0.778
252519AF1-045_GEN
Solar/Wind Harmer
6.447
252516AE2-318_GEN
Solar/Wind Harmer
4.918
247621Y3-024
Adder
0.256
970883AG2-550 GEN
Solar/Wind Harmer
10.602
970885AG2-551 GEN
Solar/Wind Harmer
2.465
270201AC2-176 GEN
Solar/Wind Harmer
5.449
25194408D.CRK1
Adder
8.013
25194508D.CRK3
Adder
1.498
964611AG1-324 GEN
Solar/Wind Harmer
1.248
964611AG1-324 GEN
Solar/Wind Harmer
0.554
252509AD1-136 GEN
Solar/Wind Harmer
0.271
247620Y3-023
Adder
0.484
24728805RICHG1
Adder
3.968
24728905RICHG2
Adder
3.968
274770LINCOLN ;1U
Adder
8.684
274771LINCOLN ;2U
Adder
8.684
274808UNIV PK N;4U
Adder
5.122
274803UNIV PARK;6U
Adder
5.976
972259AH1-714 GEN
Adder
19.527
274674JOLIET 9 ;6U
Adder
15.72
274696ROCKY RD ;4P
Adder
11.549
274695ROCKY RD ;2P
Adder
11.282
274693ROCKY RD ;1P
Adder
11.171
274697ROCKY RD ;3P
Adder
3.065
23585401KL_K28_T16
Solar/Wind Helper
1.478
238120AE2-309 GEN
Solar/Wind Helper
0.524
238175AF1-290_GEN
Solar/Wind Helper
0.153
238169AE2-226 GEN1
Solar/Wind Helper
0.702
238170AE2-226 GEN2
Solar/Wind Helper
0.702
235020AA1-095 C
Solar/Wind Helper
0.053
23777901MDS_W4-102
Solar/Wind Helper
0.177
237034AC2-136 C
Solar/Wind Helper
0.227
237002AB1-128_GEN
Solar/Wind Helper
0.443
235063AE1-101 C2
Solar/Wind Helper
1.661
237001AB1-127_GEN
Solar/Wind Helper
0.442
23777801MSM_W1-116
Solar/Wind Helper
0.114
237025AB1-124 C
Solar/Wind Helper
0.164
237006AB1-125 GEN
Solar/Wind Helper
0.123
226929AD2-058 GEN
Solar/Wind Helper
0.099
205916AD1-020 GEN
Solar/Wind Helper
1.715
20390526W1-045 C
Solar/Wind Helper
0.35
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
233987AB2-037 GEN
Solar/Wind Helper
2.344
233933AB2-153 GEN
Solar/Wind Helper
0.233
232424Y1-079 C
Solar/Wind Helper
0.116
233944AB2-135 GEN
Solar/Wind Helper
0.589
233946AB2-136 GEN
Solar/Wind Helper
0.569
234036AF2-325 C
Solar/Wind Helper
0.042
233901CHERRYDALE C
Solar/Wind Helper
0.233
232408W1-005 C
Solar/Wind Helper
0.508
232410W1-006 C
Solar/Wind Helper
0.508
233939AC1-091 C
Solar/Wind Helper
0.35
233970AC1-092 C
Solar/Wind Helper
0.35
315651AD1-115 GEN
Solar/Wind Helper
0.785
316447AC1-158 HLD
Solar/Wind Helper
2.848
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.04
219921AF1-264
Solar/Wind Helper
0.051
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.082
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.19
20716928W4-060COL
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.016
20673828FLE_V3-070
Solar/Wind Helper
0.091
207442AE1-156 GEN
Solar/Wind Helper
0.326
20676128MHD_W3-029
Solar/Wind Helper
0.096
20671828STAW2-080
Solar/Wind Helper
0.027
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
207471AF2-354 C
Solar/Wind Helper
0.169
20674928WA_W3-044
Solar/Wind Helper
0.098
964851AG1-348 GEN
Solar/Wind Helper
0.081
20676228FRD_X1-012
Solar/Wind Helper
0.092
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.045
211065PSPA IPP
Solar/Wind Helper
0.152
211065PSPA IPP
Solar/Wind Helper
0.152
970321AG2-212 GEN
Solar/Wind Harmer
3.726
962771AG1-126 GEN
Solar/Wind Harmer
40.976
972239AH1-704 GEN
Adder
2.69
270054AF2-122 C O1
Solar/Wind Harmer
3.996
270459AD2-067 GEN
Solar/Wind Harmer
10.248
961821AG1-024 GEN
Solar/Wind Harmer
10.404
270520AE2-214 GEN
Solar/Wind Harmer
7.276
270284AF1-227 GEN1
Solar/Wind Harmer
6.79
270286AF1-227 GEN2
Solar/Wind Harmer
2.512
270287AF1-227 GEN3
Solar/Wind Harmer
2.512
253383AE2-342_GEN
Solar/Wind Harmer
1.045
241973AD2-163_GEN1
Solar/Wind Harmer
2.331
945631AF1-228 GEN
Solar/Wind Harmer
5.463
943861AF1-054 GEN
Solar/Wind Harmer
4.486
943851AF1-053 GEN
Solar/Wind Harmer
2.168
270156DARBY CT1
Adder
10.419
270157DARBY CT2
Adder
10.393
270158DARBY CT3
Adder
10.228
970689AG2-444 GEN
Solar/Wind Harmer
18.827
270578AF1-285 GEN2
Solar/Wind Harmer
0.537
270432AC2-029 GEN
Solar/Wind Harmer
8.049
940611AE2-048 GEN
Solar/Wind Harmer
25.14
941391AE2-136 GEN
Solar/Wind Harmer
13.027
270302AB2-170 GEN
Solar/Wind Harmer
9.546
270317AD1-130_GEN
Solar/Wind Harmer
3.659
270269AC2-059
Solar/Wind Harmer
10.605
241972AD1-140 GEN
Solar/Wind Harmer
5.021
958581AF2-149 GEN
Solar/Wind Harmer
4.743
970179AG2-119 GEN
Solar/Wind Harmer
8.842
270340AC2-060 GEN
Solar/Wind Harmer
3.346
970879AG2-548 GEN
Solar/Wind Harmer
4.73
253372AE2-315 SEC3
Adder
2.065
253372AE2-315 SEC3
Adder
2.065
25306009OHH W.
Adder
3.133
253349AC2-067 GEN
Solar/Wind Harmer
5.407
253400AC2-068 GEN
Solar/Wind Harmer
2.174
957201AF2-014 GEN
Solar/Wind Harmer
4.898
270435AC2-044 GEN
Solar/Wind Harmer
2.16
965051AG1-369 GEN
Solar/Wind Harmer
5.365
965041AG1-368 GEN
Solar/Wind Harmer
10.719
247607V1-011 GEN
Solar/Wind Harmer
4.239
971567AH1-282 GEN
Solar/Wind Harmer
16.075
966831AG1-554 GEN
Solar/Wind Harmer
1.28
971989AH1-539 GEN
Solar/Wind Harmer
13.838
24729505KEY G4
Adder
6.925
963791AG1-232 GEN
Solar/Wind Harmer
14.411
270071AF1-092 GEN
Solar/Wind Harmer
15.995
971985AH1-537 GEN
Solar/Wind Harmer
18.996
958711AF2-162 GEN
Solar/Wind Harmer
1.076
270024AE2-089 GEN
Solar/Wind Harmer
4.988
270367AC2-061_GEN
Solar/Wind Harmer
3.378
965101AG1-375 GEN
Solar/Wind Harmer
10.618
971673AH1-337 GEN
Solar/Wind Harmer
4.878
252524AE2-267 GEN
Solar/Wind Harmer
1.672
25196408WSDLE3
Adder
9.354
25196308WSDLE2
Adder
9.273
25196208WSDLE1
Adder
9.25
25196708WSDLE6
Adder
9.227
25196508WSDLE4
Adder
8.994
971029AG2-637 GEN
Solar/Wind Harmer
15.905
270543AE2-219 C
Solar/Wind Harmer
5.429
961761AG1-017 GEN
Solar/Wind Harmer
0.454
945581AF1-223 GEN
Solar/Wind Harmer
4.803
270297AD1-101 GEN
Solar/Wind Harmer
2.947
944031AF1-071 GEN
Solar/Wind Harmer
1.064
25196108MFTGT2
Adder
1.6
25196108MFTGT2
Adder
1.486
274775LINCOLN ;6U
Adder
8.684
274776LINCOLN ;7U
Adder
8.684
274777LINCOLN ;8U
Adder
8.684
274814UNIV PK N;0U
Adder
5.189
274807UNIV PK N;3U
Adder
5.178
274805UNIV PK N;1U
Adder
5.156
274811UNIV PK N;7U
Adder
5.144
972037AH1-567 GEN1
Adder
0.188
274827FISK ;RP
Adder
7.949
972227AH1-698 GEN1
Adder
2.671
274687WILL CNTY;4U
Adder
28.551
274687WILL CNTY;4U
Adder
28.551
274675JOLIET 29;7U
Adder
31.334
274675JOLIET 29;7U
Adder
30.215
274731ELWOOD EC;2P
Adder
16.784
274733ELWOOD EC;3P
Adder
16.784
274735ELWOOD EC;4P
Adder
16.784
274728ELWOOD EC;5P
Adder
16.784
972203AH1-686 GEN
Adder
2.341
274746AC1-111 G10
Adder
5.685
274744AC1-111 GEN8
Adder
5.685
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238126S14_GEN_1
Solar/Wind Helper
0.826
238152AF2-075_GEN
Solar/Wind Helper
0.708
238208AF1-136 C
Solar/Wind Helper
0.22
23546401DTGZ2-030
Solar/Wind Helper
0.089
237085AD2-009_GEN
Solar/Wind Helper
1.65
3138216PACIFIC
Solar/Wind Helper
0.044
316411AF1-147_GEN1
Solar/Wind Helper
0.889
316415AF1-147_GEN2
Solar/Wind Helper
0.889
23750501ELLIOTTS
Solar/Wind Helper
0.637
959381AF2-229 GEN
Solar/Wind Helper
0.358
3141426STAFORD
Solar/Wind Helper
0.052
960921AF2-383 GEN
Solar/Wind Helper
0.182
205943AE1-185 GEN
Solar/Wind Helper
0.51
205932AD2-116_GEN
Solar/Wind Helper
0.509
205956AE1-196_GEN
Solar/Wind Helper
0.509
233935AB2-179 C
Solar/Wind Helper
1.27
232436AB1-176 C
Solar/Wind Helper
0.044
233923SMA
Solar/Wind Helper
0.959
234033AF1-007_GEN
Solar/Wind Helper
7.028
233990AG1-397 GEN
Solar/Wind Helper
0.03
232432Z2-076 GEN
Solar/Wind Helper
0.067
964001AG1-254 GEN
Solar/Wind Helper
0.956
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.115
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.08
203975AE1-071-GEN
Solar/Wind Helper
2.5
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.29
219620RIDERU C
Solar/Wind Helper
0.001
316164AC1-076 GEN
Solar/Wind Helper
1.097
20675528CPH_W2-050
Solar/Wind Helper
0.087
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
218524CNTRALGAS1 C
Solar/Wind Helper
0.161
966261AG1-495 GEN
Solar/Wind Helper
0.081
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20675928HOL_W4-097
Solar/Wind Helper
0.05
20674828DL_W4-046
Solar/Wind Helper
0.008
207484AF2-139 C O1
Solar/Wind Helper
0.084
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.137
20675128HRM_W1-127
Solar/Wind Helper
0.03
209116AE2-175 GEN
Solar/Wind Helper
1.781
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.216
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.135
MECLTFEXP_MEC->PJM
CLTF
15.918
SIGELTFEXP_SIGE->PJM
CLTF
0.506
LAGNLTFEXP_LAGN->PJM
CLTF
14.855
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.816
TVALTFEXP_TVA->PJM
CLTF
7.302
CPLELTFEXP_CPLE->PJM
CLTF
0.627
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.944
NYPJM->LTFIMP_NY
CLTF
4.803
LGEELTFEXP_LGEE->PJM
CLTF
6.756
WECLTFEXP_WEC->PJM
CLTF
3.828
AG2-052LTFEXP_AG2-052->PJM
LTF
0.24
AH1-155LTFEXP_AH1-155->PJM
LTF
0.36

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-015_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-015_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:131.63 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4908.47
MW Contribution:11.51
Bus #Bus NameTypeMW Contribution
270119AB2-067 GEN1
50/50
7.063
270120AB2-067 GEN2
50/50
7.063
24318905MLG2
50/50
7.074
270471AD2-092_GEN
Solar/Wind Harmer
4.466
946101AF1-275 GEN
Solar/Wind Harmer
1.816
942861AE2-305 GEN
Solar/Wind Harmer
9.089
970077AG2-063 GEN
Solar/Wind Harmer
6.24
270224U2-072_GEN2
Solar/Wind Harmer
2.282
270227U2-072_GEN3
Solar/Wind Harmer
2.282
270228U2-072_GEN4
Solar/Wind Harmer
2.282
270231U2-072_GEN5
Solar/Wind Harmer
2.282
938701AE1-092 GEN
Solar/Wind Harmer
23.829
964601AG1-323 GEN
Solar/Wind Harmer
3.66
964601AG1-323 GEN
Solar/Wind Harmer
1.702
270518AE2-148 GEN
Solar/Wind Harmer
13.889
972269AH1-719 GEN
Adder
2.587
972159AH1-661 GEN
Adder
1.119
253378AE2-206_GEN
Solar/Wind Harmer
4.007
276820AF1-078_GEN
Solar/Wind Harmer
1.78
971199AH1-059 GEN
Solar/Wind Harmer
4.433
241960AC2-195 GEN
Solar/Wind Harmer
3.073
25326509SID D
Adder
1.452
970879AG2-548 GEN
Solar/Wind Harmer
6.78
971073AG2-665 GEN
Solar/Wind Harmer
6.78
971073AG2-665 GEN
Solar/Wind Harmer
4.73
24318805MLG1
50/50
10.098
23559001PLEAS1
50/50
6.112
270051AF1-062 GEN
50/50
11.831
23684201S70BUS2
50/50
0.171
270475AD2-096_GEN
50/50
7.147
970153AG2-106 GEN
Solar/Wind Harmer
17.867
961921AG1-034 GEN
Solar/Wind Harmer
15.607
241955AC1-078 GEN
Solar/Wind Harmer
8.813
24721905FLATG4
Adder
23.946
241974AD2-163_GEN2
Solar/Wind Harmer
2.331
942051AE2-217 GEN
Solar/Wind Harmer
21.048
960801AF2-371 GEN
Solar/Wind Harmer
2.948
964871AG1-351 GEN
Solar/Wind Harmer
2.036
970605AG2-385 GEN
Solar/Wind Harmer
6.24
942871AE2-306 GEN
Solar/Wind Harmer
1.047
270391AF1-285 GEN3
Solar/Wind Harmer
0.537
253338AC1-165 GEN
Solar/Wind Harmer
1.242
253333AC1-068 GEN
Solar/Wind Harmer
1.197
270485AE1-090_GEN
Solar/Wind Harmer
0.69
270273AD2-016 GEN
Solar/Wind Harmer
3.033
972173AH1-669 GEN
Solar/Wind Harmer
5.671
270291AC1-194 GEN
Solar/Wind Harmer
11.744
253415AE1-040 GEN
Solar/Wind Harmer
1.248
270512AE1-227 GEN2
Solar/Wind Harmer
2.315
970065AG2-057 GEN
Solar/Wind Harmer
1.09
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.065
957541AF2-048 GEN
Solar/Wind Harmer
1.721
253406AD2-031_GEN
Solar/Wind Harmer
1.388
270491AE1-102 GEN2
Solar/Wind Harmer
1.404
270377AD1-106 GEN
Solar/Wind Harmer
6.655
971191AH1-055 GEN
Solar/Wind Harmer
23.692
253316AC1-085 GEN3
Solar/Wind Harmer
9.013
253433AC1-085 GEN1
Solar/Wind Harmer
5.721
946181AF1-283 GEN
Solar/Wind Harmer
13.988
270191TR4_S_V150
Solar/Wind Harmer
3.223
270247TR4_N_V136
Solar/Wind Harmer
0.914
959331AF2-224 GEN
Solar/Wind Harmer
10.743
965021AG1-366 GEN
Solar/Wind Harmer
2.498
270588AE1-091_GEN
Solar/Wind Harmer
11.792
958091AF2-103 GEN
Solar/Wind Harmer
0.173
944531AF1-118 GEN
Solar/Wind Harmer
37.418
270043AE2-236 GEN
Solar/Wind Harmer
5.874
270258AD1-119 GEN
Solar/Wind Harmer
2.962
971617AH1-308 GEN
Solar/Wind Harmer
6.179
25196608WSDLE5
Adder
9.087
252510AF1-249 C
Solar/Wind Harmer
0.443
962031AG1-047 GEN
Solar/Wind Harmer
3.204
957741AF2-068 GEN
Solar/Wind Harmer
15.899
25194608D.CRK4
Adder
1.742
270222AC2-111 GEN
Solar/Wind Harmer
8.63
970031AG2-029 GEN
Solar/Wind Harmer
31.748
270044AE2-322 C
Solar/Wind Harmer
1.39
270404AC1-167 GEN
Solar/Wind Harmer
1.158
24642205MAYFLWER
Adder
0.665
25196008MFTGT1
Adder
1.406
247604X1-042
Adder
0.433
274752CRETE EC ;2U
Adder
8.485
274753CRETE EC ;3U
Adder
8.485
274772LINCOLN ;3U
Adder
8.684
274724RIVER EC ;11
Adder
18.221
24728705AND G3
Adder
8.223
274802UNIV PARK;5U
Adder
5.976
24728505AND G1
Adder
3.932
274826FISK ;BP
Adder
11.216
274800UNIV PARK;3U
Adder
5.972
972038AH1-567 GEN2
Adder
0.374
972228AH1-698 GEN2
Adder
3.794
274676JOLIET 29;8U
Adder
30.215
274729ELWOOD EC;1P
Adder
16.784
274730ELWOOD EC;6P
Adder
16.784
274734ELWOOD EC;8P
Adder
16.784
274736ELWOOD EC;9P
Adder
16.784
274682WAUKEGAN ;7U
Adder
9.459
964991AG1-363 GEN
Solar/Wind Helper
5.14
316097T157 G90
Solar/Wind Helper
1.505
23750701CROSSCHOOL
Solar/Wind Helper
1.501
238118U2-030_1
Solar/Wind Helper
0.341
238127S14_GEN_2
Solar/Wind Helper
0.826
238148AE2-230_GEN2
Solar/Wind Helper
0.497
237080AD1-060 GEN
Solar/Wind Helper
0.342
237038AE2-054 C
Solar/Wind Helper
0.272
235062AE1-101 C1
Solar/Wind Helper
1.661
23779801AA1-109
Solar/Wind Helper
0.193
237048AF1-022 C
Solar/Wind Helper
0.177
223401AF1-299 GEN
Solar/Wind Helper
0.368
316006AB2-029 C
Solar/Wind Helper
0.117
966131AG1-482 GEN
Solar/Wind Helper
0.077
233930AB2-032 GEN
Solar/Wind Helper
0.381
233915AB1-141 GEN
Solar/Wind Helper
0.503
232422X3-066 FULL
Solar/Wind Helper
0.114
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
233998TM1NIN_3.36
Solar/Wind Helper
0.262
232404W1-003 C
Solar/Wind Helper
0.508
232428Y3-058 C
Solar/Wind Helper
0.338
232434Z2-077 GEN
Solar/Wind Helper
0.127
233954AC2-188 GEN
Solar/Wind Helper
0.233
233950AC2-186 GEN
Solar/Wind Helper
0.116
233972AC1-094 C
Solar/Wind Helper
0.303
316045AC1-158 PL2
Solar/Wind Helper
4.142
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.23
228728W1-130C
Solar/Wind Helper
0.054
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219904AC1-010 C
Solar/Wind Helper
0.06
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.131
20720728JCB_W1-129
Solar/Wind Helper
0.057
316254AC1-120 GEN1
Solar/Wind Helper
1.061
207445AB1-138_GEN
Solar/Wind Helper
0.104
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.31
20715228NPK_W1-113
Solar/Wind Helper
0.078
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.496
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
207437AD2-070 GEN
Solar/Wind Helper
0.138
207518AF1-320_GEN
Solar/Wind Helper
1.573
20671928W4-073
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.03
970513AG2-328 GEN
Solar/Wind Harmer
3.726
970517AG2-330 GEN
Solar/Wind Harmer
3.379
962771AG1-126 GEN
Solar/Wind Harmer
40.976
972239AH1-704 GEN
Adder
2.69
270054AF2-122 C O1
Solar/Wind Harmer
3.996
270459AD2-067 GEN
Solar/Wind Harmer
10.248
961821AG1-024 GEN
Solar/Wind Harmer
10.404
270520AE2-214 GEN
Solar/Wind Harmer
7.276
270284AF1-227 GEN1
Solar/Wind Harmer
6.79
270286AF1-227 GEN2
Solar/Wind Harmer
2.512
270287AF1-227 GEN3
Solar/Wind Harmer
2.512
253383AE2-342_GEN
Solar/Wind Harmer
1.045
241973AD2-163_GEN1
Solar/Wind Harmer
2.331
945631AF1-228 GEN
Solar/Wind Harmer
5.463
943861AF1-054 GEN
Solar/Wind Harmer
4.486
943851AF1-053 GEN
Solar/Wind Harmer
2.168
270156DARBY CT1
Adder
10.419
270157DARBY CT2
Adder
10.393
270158DARBY CT3
Adder
10.228
970689AG2-444 GEN
Solar/Wind Harmer
18.827
270578AF1-285 GEN2
Solar/Wind Harmer
0.537
270432AC2-029 GEN
Solar/Wind Harmer
8.049
940611AE2-048 GEN
Solar/Wind Harmer
25.14
941391AE2-136 GEN
Solar/Wind Harmer
13.027
270302AB2-170 GEN
Solar/Wind Harmer
9.546
270317AD1-130_GEN
Solar/Wind Harmer
3.659
270269AC2-059
Solar/Wind Harmer
10.605
241972AD1-140 GEN
Solar/Wind Harmer
5.021
958581AF2-149 GEN
Solar/Wind Harmer
4.743
970179AG2-119 GEN
Solar/Wind Harmer
8.842
270340AC2-060 GEN
Solar/Wind Harmer
3.346
970879AG2-548 GEN
Solar/Wind Harmer
4.73
253372AE2-315 SEC3
Adder
2.065
253372AE2-315 SEC3
Adder
2.065
25306009OHH W.
Adder
3.133
253349AC2-067 GEN
Solar/Wind Harmer
5.407
253400AC2-068 GEN
Solar/Wind Harmer
2.174
957201AF2-014 GEN
Solar/Wind Harmer
4.898
270435AC2-044 GEN
Solar/Wind Harmer
2.16
965051AG1-369 GEN
Solar/Wind Harmer
5.365
965041AG1-368 GEN
Solar/Wind Harmer
10.719
247607V1-011 GEN
Solar/Wind Harmer
4.239
971567AH1-282 GEN
Solar/Wind Harmer
16.075
966831AG1-554 GEN
Solar/Wind Harmer
1.28
971989AH1-539 GEN
Solar/Wind Harmer
13.838
24729505KEY G4
Adder
6.925
963791AG1-232 GEN
Solar/Wind Harmer
14.411
270071AF1-092 GEN
Solar/Wind Harmer
15.995
971985AH1-537 GEN
Solar/Wind Harmer
18.996
958711AF2-162 GEN
Solar/Wind Harmer
1.076
270024AE2-089 GEN
Solar/Wind Harmer
4.988
270367AC2-061_GEN
Solar/Wind Harmer
3.378
965101AG1-375 GEN
Solar/Wind Harmer
10.618
971673AH1-337 GEN
Solar/Wind Harmer
4.878
252524AE2-267 GEN
Solar/Wind Harmer
1.672
25196408WSDLE3
Adder
9.354
25196308WSDLE2
Adder
9.273
25196208WSDLE1
Adder
9.25
25196708WSDLE6
Adder
9.227
25196508WSDLE4
Adder
8.994
971029AG2-637 GEN
Solar/Wind Harmer
15.905
270543AE2-219 C
Solar/Wind Harmer
5.429
961761AG1-017 GEN
Solar/Wind Harmer
0.454
945581AF1-223 GEN
Solar/Wind Harmer
4.803
270297AD1-101 GEN
Solar/Wind Harmer
2.947
944031AF1-071 GEN
Solar/Wind Harmer
1.064
25196108MFTGT2
Adder
1.6
25196108MFTGT2
Adder
1.486
274775LINCOLN ;6U
Adder
8.684
274776LINCOLN ;7U
Adder
8.684
274777LINCOLN ;8U
Adder
8.684
274814UNIV PK N;0U
Adder
5.189
274807UNIV PK N;3U
Adder
5.178
274805UNIV PK N;1U
Adder
5.156
274811UNIV PK N;7U
Adder
5.144
972037AH1-567 GEN1
Adder
0.188
274827FISK ;RP
Adder
7.949
972227AH1-698 GEN1
Adder
2.671
274687WILL CNTY;4U
Adder
28.551
274687WILL CNTY;4U
Adder
28.551
274675JOLIET 29;7U
Adder
31.334
274675JOLIET 29;7U
Adder
30.215
274731ELWOOD EC;2P
Adder
16.784
274733ELWOOD EC;3P
Adder
16.784
274735ELWOOD EC;4P
Adder
16.784
274728ELWOOD EC;5P
Adder
16.784
972203AH1-686 GEN
Adder
2.341
274746AC1-111 G10
Adder
5.685
274744AC1-111 GEN8
Adder
5.685
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238126S14_GEN_1
Solar/Wind Helper
0.826
238152AF2-075_GEN
Solar/Wind Helper
0.708
238208AF1-136 C
Solar/Wind Helper
0.22
23546401DTGZ2-030
Solar/Wind Helper
0.089
237085AD2-009_GEN
Solar/Wind Helper
1.65
3138216PACIFIC
Solar/Wind Helper
0.044
316411AF1-147_GEN1
Solar/Wind Helper
0.889
316415AF1-147_GEN2
Solar/Wind Helper
0.889
23750501ELLIOTTS
Solar/Wind Helper
0.637
959381AF2-229 GEN
Solar/Wind Helper
0.358
3141426STAFORD
Solar/Wind Helper
0.052
960921AF2-383 GEN
Solar/Wind Helper
0.182
205943AE1-185 GEN
Solar/Wind Helper
0.51
205932AD2-116_GEN
Solar/Wind Helper
0.509
205956AE1-196_GEN
Solar/Wind Helper
0.509
270166AC1-044 GEN3
50/50
7.063
23559101PLEAS2
50/50
6.112
23684101S70BUS1
50/50
0.168
962761AG1-125 GEN
Solar/Wind Harmer
40.976
970149AG2-104 GEN
Solar/Wind Harmer
50.605
970155AG2-107 GEN
Solar/Wind Harmer
17.867
270349AD2-093_GEN
Solar/Wind Harmer
4.466
24721705FLATG2
Adder
23.946
270159DARBY CT4
Adder
10.253
970593AG2-378 GEN
Solar/Wind Harmer
2.311
270223U2-072_GEN1
Solar/Wind Harmer
2.282
270578AF1-285 GEN2
Solar/Wind Harmer
1.396
270391AF1-285 GEN3
Solar/Wind Harmer
1.396
253343AC1-166 GEN
Solar/Wind Harmer
1.242
253325AC1-069 GEN
Solar/Wind Harmer
1.197
270462AD2-086
Solar/Wind Harmer
7.941
971995AH1-542 GEN
Solar/Wind Harmer
12.507
270263AC1-001 GEN
Solar/Wind Harmer
1.177
270510AE1-227 GEN1
Solar/Wind Harmer
2.727
25326309TAIT D
Adder
1.197
241813AF1-122_GEN
Solar/Wind Harmer
6.978
960071AF2-298 GEN
Solar/Wind Harmer
5.44
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.065
927014AC1-188 GEN
Solar/Wind Harmer
1.725
246936BC-WTG1
Solar/Wind Harmer
4.226
270489AE1-102 GEN1
Solar/Wind Harmer
1.404
965421AG1-410 GEN
Solar/Wind Harmer
32.379
960001AF2-291 GEN
Solar/Wind Harmer
3.256
253432AC1-085 GEN2
Solar/Wind Harmer
0.288
946171AF1-282 GEN
Solar/Wind Harmer
10.76
247521TR3_G114
Solar/Wind Harmer
3.612
270246TR4_N_V150
Solar/Wind Harmer
0.914
965011AG1-365 GEN
Solar/Wind Harmer
10.743
24695305TIMB G C
Solar/Wind Harmer
5.899
965651AG1-433 GEN
Solar/Wind Harmer
5.811
958861AF2-177 GEN
Solar/Wind Harmer
11.606
247536S-71 GEN
Solar/Wind Harmer
4.292
25194608D.CRK4
Adder
1.742
945371AF1-202 GEN
Solar/Wind Harmer
7.39
252507AC2-088 GEN
Solar/Wind Harmer
1.898
270063AE2-323 C
Solar/Wind Harmer
2.329
25196808ZIMRHP
Adder
79.816
24639705ELKHART HY
Adder
0.161
25196008MFTGT1
Adder
1.452
274751CRETE EC ;1U
Adder
8.485
274754CRETE EC ;4U
Adder
8.485
274773LINCOLN ;4U
Adder
8.684
274774LINCOLN ;5U
Adder
8.684
274723RIVER EC ;12
Adder
18.437
274812UNIV PK N;8U
Adder
5.144
24728605AND G2
Adder
3.932
274801UNIV PARK;4U
Adder
5.972
274676JOLIET 29;8U
Adder
31.334
274732ELWOOD EC;7P
Adder
16.784
274674JOLIET 9 ;6U
Adder
15.72
274745AC1-111 GEN9
Adder
5.685
970091AG2-072 GEN
Adder
77.715
316095T157 G97
Solar/Wind Helper
1.505
23583801GRNGAP
Solar/Wind Helper
5.607
238185AF2-356 C
Solar/Wind Helper
2.642
238108AE1-109 GEN1
Solar/Wind Helper
0.114
235054AD2-180 GEN
Solar/Wind Helper
2.025
235531U2-073 GEN
Solar/Wind Helper
3.278
238117U2-030
Solar/Wind Helper
0.341
238147AE2-230_GEN1
Solar/Wind Helper
0.495
238149AF1-291A_GEN
Solar/Wind Helper
0.141
237061AD1-155 GEN
Solar/Wind Helper
0.053
23751201ROTHROCK
Solar/Wind Helper
0.819
238221AF1-254 C O1
Solar/Wind Helper
0.275
23562501BACKB
Solar/Wind Helper
1.001
235067AD1-061 GEN
Solar/Wind Helper
0.496
23751101LEADS_P59
Solar/Wind Helper
1.388
237030AB1-096 C
Solar/Wind Helper
0.071
3141196NOKESVL
Solar/Wind Helper
1.033
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.346
223402AF1-300 C
Solar/Wind Helper
0.368
205917AD1-020 ES
Solar/Wind Helper
0.369
233982AB2-133 GEN
Solar/Wind Helper
0.358
233918AB1-142 GEN
Solar/Wind Helper
0.503
233994AC2-023 GEN
Solar/Wind Helper
0.962
233996TM1833_GEN
Solar/Wind Helper
0.262
233997TMININ_4.2
Solar/Wind Helper
0.262
232406W1-004 FULL
Solar/Wind Helper
0.508
233940AF2-379 C
Solar/Wind Helper
0.062
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.233
233971AC1-093 C
Solar/Wind Helper
0.358
316044AC1-158 PL1
Solar/Wind Helper
1.294
316450AC1-158 RIC
Solar/Wind Helper
0.345
230430AE1-229_GEN
Solar/Wind Helper
3.376
230415AB2-049 C
Solar/Wind Helper
0.03
228729W2-030 C
Solar/Wind Helper
0.111
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.15
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
219348LDSOLAR C
Solar/Wind Helper
0.115
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.063
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.354
219276PARKLANDSO C
Solar/Wind Helper
0.089
20714528FRN_Y2-051
Solar/Wind Helper
0.057
20720528MAN_W1-024
Solar/Wind Helper
0.028
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.027
219249CENTRALDIV C
Solar/Wind Helper
0.01
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.089
970245AG2-165 GEN
Solar/Wind Harmer
3.726
25326109MON D
Adder
1.444
25322209TAIT E
Adder
10.653
25322209TAIT E
Adder
10.414
971201AH1-060 GEN
Solar/Wind Harmer
2.181
253370AE2-315 SEC1
Adder
2.184
253394AE2-221_GEN
Solar/Wind Harmer
4.918
253398AE2-221_GEN2
Solar/Wind Harmer
4.918
246938BC-WTG3
Solar/Wind Harmer
4.299
246937BC-WTG2
Solar/Wind Harmer
4.226
971231AH1-075 GEN
Solar/Wind Harmer
0.862
253317AC1-085 GEN4
Solar/Wind Harmer
9.013
970611AG2-400 GEN
Solar/Wind Harmer
10.743
270007AE1-245 C
Solar/Wind Harmer
6.358
942801AE2-298 GEN
Solar/Wind Harmer
1.622
962581AG1-107 GEN
Solar/Wind Harmer
5.365
961491AF2-440 GEN
Solar/Wind Harmer
2.229
25183208HLCRTG
Solar/Wind Harmer
6.449
944541AF1-119 GEN
Solar/Wind Harmer
4.453
960971AF2-388 GEN
Solar/Wind Harmer
11.621
942221AE2-234 GEN
Solar/Wind Harmer
0.778
252519AF1-045_GEN
Solar/Wind Harmer
6.447
252516AE2-318_GEN
Solar/Wind Harmer
4.918
247621Y3-024
Adder
0.256
970883AG2-550 GEN
Solar/Wind Harmer
10.602
970885AG2-551 GEN
Solar/Wind Harmer
2.465
270201AC2-176 GEN
Solar/Wind Harmer
5.449
25194408D.CRK1
Adder
8.013
25194508D.CRK3
Adder
1.498
964611AG1-324 GEN
Solar/Wind Harmer
1.248
964611AG1-324 GEN
Solar/Wind Harmer
0.554
252509AD1-136 GEN
Solar/Wind Harmer
0.271
247620Y3-023
Adder
0.484
24728805RICHG1
Adder
3.968
24728905RICHG2
Adder
3.968
274770LINCOLN ;1U
Adder
8.684
274771LINCOLN ;2U
Adder
8.684
274808UNIV PK N;4U
Adder
5.122
274803UNIV PARK;6U
Adder
5.976
972259AH1-714 GEN
Adder
19.527
274674JOLIET 9 ;6U
Adder
15.72
274696ROCKY RD ;4P
Adder
11.549
274695ROCKY RD ;2P
Adder
11.282
274693ROCKY RD ;1P
Adder
11.171
274697ROCKY RD ;3P
Adder
3.065
23585401KL_K28_T16
Solar/Wind Helper
1.478
238120AE2-309 GEN
Solar/Wind Helper
0.524
238175AF1-290_GEN
Solar/Wind Helper
0.153
238169AE2-226 GEN1
Solar/Wind Helper
0.702
238170AE2-226 GEN2
Solar/Wind Helper
0.702
235020AA1-095 C
Solar/Wind Helper
0.053
23777901MDS_W4-102
Solar/Wind Helper
0.177
237034AC2-136 C
Solar/Wind Helper
0.227
237002AB1-128_GEN
Solar/Wind Helper
0.443
235063AE1-101 C2
Solar/Wind Helper
1.661
237001AB1-127_GEN
Solar/Wind Helper
0.442
23777801MSM_W1-116
Solar/Wind Helper
0.114
237025AB1-124 C
Solar/Wind Helper
0.164
237006AB1-125 GEN
Solar/Wind Helper
0.123
226929AD2-058 GEN
Solar/Wind Helper
0.099
205916AD1-020 GEN
Solar/Wind Helper
1.715
20390526W1-045 C
Solar/Wind Helper
0.35
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
233987AB2-037 GEN
Solar/Wind Helper
2.344
233933AB2-153 GEN
Solar/Wind Helper
0.233
232424Y1-079 C
Solar/Wind Helper
0.116
233944AB2-135 GEN
Solar/Wind Helper
0.589
233946AB2-136 GEN
Solar/Wind Helper
0.569
234036AF2-325 C
Solar/Wind Helper
0.042
233901CHERRYDALE C
Solar/Wind Helper
0.233
232408W1-005 C
Solar/Wind Helper
0.508
232410W1-006 C
Solar/Wind Helper
0.508
233939AC1-091 C
Solar/Wind Helper
0.35
233970AC1-092 C
Solar/Wind Helper
0.35
315651AD1-115 GEN
Solar/Wind Helper
0.785
316447AC1-158 HLD
Solar/Wind Helper
2.848
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.04
219921AF1-264
Solar/Wind Helper
0.051
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.082
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.19
20716928W4-060COL
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.016
20673828FLE_V3-070
Solar/Wind Helper
0.091
207442AE1-156 GEN
Solar/Wind Helper
0.326
20676128MHD_W3-029
Solar/Wind Helper
0.096
20671828STAW2-080
Solar/Wind Helper
0.027
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
207471AF2-354 C
Solar/Wind Helper
0.169
20674928WA_W3-044
Solar/Wind Helper
0.098
964851AG1-348 GEN
Solar/Wind Helper
0.081
20676228FRD_X1-012
Solar/Wind Helper
0.092
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.045
211065PSPA IPP
Solar/Wind Helper
0.152
211065PSPA IPP
Solar/Wind Helper
0.152
970321AG2-212 GEN
Solar/Wind Harmer
3.726
233935AB2-179 C
Solar/Wind Helper
1.27
232436AB1-176 C
Solar/Wind Helper
0.044
233923SMA
Solar/Wind Helper
0.959
234033AF1-007_GEN
Solar/Wind Helper
7.028
233990AG1-397 GEN
Solar/Wind Helper
0.03
232432Z2-076 GEN
Solar/Wind Helper
0.067
964001AG1-254 GEN
Solar/Wind Helper
0.956
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.115
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.08
203975AE1-071-GEN
Solar/Wind Helper
2.5
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.29
219620RIDERU C
Solar/Wind Helper
0.001
316164AC1-076 GEN
Solar/Wind Helper
1.097
20675528CPH_W2-050
Solar/Wind Helper
0.087
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
218524CNTRALGAS1 C
Solar/Wind Helper
0.161
966261AG1-495 GEN
Solar/Wind Helper
0.081
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20675928HOL_W4-097
Solar/Wind Helper
0.05
20674828DL_W4-046
Solar/Wind Helper
0.008
207484AF2-139 C O1
Solar/Wind Helper
0.084
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.137
20675128HRM_W1-127
Solar/Wind Helper
0.03
209116AE2-175 GEN
Solar/Wind Helper
1.781
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.216
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.135
MECLTFEXP_MEC->PJM
CLTF
15.918
SIGELTFEXP_SIGE->PJM
CLTF
0.506
LAGNLTFEXP_LAGN->PJM
CLTF
14.855
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.816
TVALTFEXP_TVA->PJM
CLTF
7.302
CPLELTFEXP_CPLE->PJM
CLTF
0.627
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.944
NYPJM->LTFIMP_NY
CLTF
4.803
LGEELTFEXP_LGEE->PJM
CLTF
6.756
WECLTFEXP_WEC->PJM
CLTF
3.828
AG2-052LTFEXP_AG2-052->PJM
LTF
0.24
AH1-155LTFEXP_AH1-155->PJM
LTF
0.36

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-007A_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-007A_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:130.62 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4870.98
MW Contribution:6.9
Bus #Bus NameTypeMW Contribution
24318805MLG1
50/50
10.095
23559001PLEAS1
50/50
6.1
270051AF1-062 GEN
50/50
11.821
270475AD2-096_GEN
50/50
7.141
970153AG2-106 GEN
Solar/Wind Harmer
22.046
961921AG1-034 GEN
Solar/Wind Harmer
7.615
241955AC1-078 GEN
Solar/Wind Harmer
0.007
24721905FLATG4
Adder
23.918
241974AD2-163_GEN2
Solar/Wind Harmer
0.006
942051AE2-217 GEN
Solar/Wind Harmer
14.671
970605AG2-385 GEN
Solar/Wind Harmer
4.899
270391AF1-285 GEN3
Solar/Wind Harmer
0.536
253338AC1-165 GEN
Solar/Wind Harmer
0.003
253333AC1-068 GEN
Solar/Wind Harmer
0.012
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270273AD2-016 GEN
Solar/Wind Harmer
0.821
972173AH1-669 GEN
Solar/Wind Harmer
3.952
270291AC1-194 GEN
Solar/Wind Harmer
6.106
253415AE1-040 GEN
Solar/Wind Harmer
0.003
270512AE1-227 GEN2
Solar/Wind Harmer
1.963
970065AG2-057 GEN
Solar/Wind Harmer
0.76
253370AE2-315 SEC1
Adder
2.182
253371AE2-315 SEC2
Adder
2.063
253406AD2-031_GEN
Solar/Wind Harmer
0.563
970191AG2-125 GEN
Solar/Wind Harmer
1.945
270491AE1-102 GEN2
Solar/Wind Harmer
0.979
270377AD1-106 GEN
Solar/Wind Harmer
2.855
971191AH1-055 GEN
Solar/Wind Harmer
19.26
253316AC1-085 GEN3
Solar/Wind Harmer
0.005
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
9.749
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.048
959331AF2-224 GEN
Solar/Wind Harmer
5.242
965021AG1-366 GEN
Solar/Wind Harmer
2.496
270588AE1-091_GEN
Solar/Wind Harmer
5.845
944531AF1-118 GEN
Solar/Wind Harmer
33.395
270043AE2-236 GEN
Solar/Wind Harmer
4.777
270258AD1-119 GEN
Solar/Wind Harmer
0.002
971617AH1-308 GEN
Solar/Wind Harmer
6.173
25196608WSDLE5
Adder
9.077
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
252510AF1-249 C
Solar/Wind Harmer
0.057
957741AF2-068 GEN
Solar/Wind Harmer
11.081
25194608D.CRK4
Adder
1.74
270222AC2-111 GEN
Solar/Wind Harmer
3.739
970031AG2-029 GEN
Solar/Wind Harmer
4.795
270404AC1-167 GEN
Solar/Wind Harmer
0.003
970513AG2-328 GEN
Solar/Wind Harmer
3.191
970517AG2-330 GEN
Solar/Wind Harmer
19.146
970349AG2-230 GEN
Solar/Wind Harmer
11.025
946031AF1-268 GEN
Solar/Wind Harmer
6.992
958821AF2-173 GEN
Solar/Wind Harmer
10.273
270004AE1-209 GEN
Solar/Wind Harmer
1.59
962771AG1-126 GEN
Solar/Wind Harmer
34.524
972239AH1-704 GEN
Adder
2.689
270054AF2-122 C O1
Solar/Wind Harmer
0.007
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
5.077
270520AE2-214 GEN
Solar/Wind Harmer
0.013
270284AF1-227 GEN1
Solar/Wind Harmer
0.011
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
253383AE2-342_GEN
Solar/Wind Harmer
0.003
241973AD2-163_GEN1
Solar/Wind Harmer
0.006
945631AF1-228 GEN
Solar/Wind Harmer
0
943861AF1-054 GEN
Solar/Wind Harmer
3.127
943851AF1-053 GEN
Solar/Wind Harmer
2.166
270156DARBY CT1
Adder
10.409
270157DARBY CT2
Adder
10.383
270158DARBY CT3
Adder
10.218
970689AG2-444 GEN
Solar/Wind Harmer
16.436
270578AF1-285 GEN2
Solar/Wind Harmer
0.536
270432AC2-029 GEN
Solar/Wind Harmer
3.553
940611AE2-048 GEN
Solar/Wind Harmer
19.602
941391AE2-136 GEN
Solar/Wind Harmer
11.042
270302AB2-170 GEN
Solar/Wind Harmer
0.005
270317AD1-130_GEN
Solar/Wind Harmer
0.011
971653AH1-327 GEN
Solar/Wind Harmer
1.117
270269AC2-059
Solar/Wind Harmer
0.005
241972AD1-140 GEN
Solar/Wind Harmer
0.854
970179AG2-119 GEN
Solar/Wind Harmer
6.883
270340AC2-060 GEN
Solar/Wind Harmer
0.009
970879AG2-548 GEN
Solar/Wind Harmer
6.898
253372AE2-315 SEC3
Adder
2.063
253372AE2-315 SEC3
Adder
2.063
25306009OHH W.
Adder
3.13
253349AC2-067 GEN
Solar/Wind Harmer
2.381
253400AC2-068 GEN
Solar/Wind Harmer
0.958
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
0.953
965051AG1-369 GEN
Solar/Wind Harmer
3.739
965041AG1-368 GEN
Solar/Wind Harmer
7.471
247607V1-011 GEN
Solar/Wind Harmer
0.001
971567AH1-282 GEN
Solar/Wind Harmer
11.206
971989AH1-539 GEN
Solar/Wind Harmer
3.215
963791AG1-232 GEN
Solar/Wind Harmer
10.044
24729505KEY G4
Adder
6.919
270071AF1-092 GEN
Solar/Wind Harmer
14.245
971985AH1-537 GEN
Solar/Wind Harmer
2.206
270024AE2-089 GEN
Solar/Wind Harmer
0.008
270367AC2-061_GEN
Solar/Wind Harmer
0.006
965101AG1-375 GEN
Solar/Wind Harmer
7.401
971673AH1-337 GEN
Solar/Wind Harmer
4.804
252524AE2-267 GEN
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
9.344
25196308WSDLE2
Adder
9.263
25196208WSDLE1
Adder
9.24
25196708WSDLE6
Adder
9.217
25196508WSDLE4
Adder
8.984
971029AG2-637 GEN
Solar/Wind Harmer
11.085
270543AE2-219 C
Solar/Wind Harmer
0.004
945581AF1-223 GEN
Solar/Wind Harmer
0.001
270297AD1-101 GEN
Solar/Wind Harmer
0.002
971347AH1-153 GEN
Solar/Wind Harmer
11.025
971609AH1-304 GEN
Solar/Wind Harmer
1.2
270240V3-007_GEN2
Solar/Wind Harmer
0.002
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
970115AG2-085 GEN
Solar/Wind Harmer
2.932
270594AE1-207 GEN
Solar/Wind Harmer
8.194
970289AG2-191 GEN
Solar/Wind Harmer
1.389
971771AH1-392 GEN
Solar/Wind Harmer
7.306
971619AH1-309 GEN
Solar/Wind Harmer
3.285
971769AH1-391 GEN
Solar/Wind Harmer
8.134
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
25196108MFTGT2
Adder
1.599
25196108MFTGT2
Adder
1.484
270536AF1-215 GEN2
Solar/Wind Harmer
0.009
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
4.302
971549AH1-272 GEN
Solar/Wind Harmer
14.865
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
8.676
274776LINCOLN ;7U
Adder
8.676
274777LINCOLN ;8U
Adder
8.676
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
274814UNIV PK N;0U
Adder
5.184
274807UNIV PK N;3U
Adder
5.173
274805UNIV PK N;1U
Adder
5.15
274811UNIV PK N;7U
Adder
5.139
972037AH1-567 GEN1
Adder
0.187
960591AF2-350 GEN
Solar/Wind Harmer
7.141
274827FISK ;RP
Adder
7.941
972227AH1-698 GEN1
Adder
2.669
963841AG1-237 GEN
Solar/Wind Harmer
3.09
972163AH1-664 GEN
Solar/Wind Harmer
7.933
972165AH1-665 GEN
Solar/Wind Harmer
6.354
274687WILL CNTY;4U
Adder
28.523
274687WILL CNTY;4U
Adder
28.523
274675JOLIET 29;7U
Adder
31.303
274675JOLIET 29;7U
Adder
30.185
274731ELWOOD EC;2P
Adder
16.768
274733ELWOOD EC;3P
Adder
16.768
274735ELWOOD EC;4P
Adder
16.768
274728ELWOOD EC;5P
Adder
16.768
970833AG2-524 GEN
Solar/Wind Harmer
7.824
970833AG2-524 GEN
Solar/Wind Harmer
5.216
274746AC1-111 G10
Adder
5.679
274744AC1-111 GEN8
Adder
5.679
972203AH1-686 GEN
Adder
2.338
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
276868AE1-113 GEN
Solar/Wind Harmer
1.414
276882AE2-255 GEN
Solar/Wind Harmer
0.824
238109AE1-109 GEN2
Solar/Wind Helper
0.114
270437AC2-090 C
Solar/Wind Harmer
0.003
247643Z2-116 C
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.804
970291AG2-192 GEN
Solar/Wind Harmer
0.731
247642Z2-115 C
Solar/Wind Harmer
0.003
945111AF1-176 GEN
Solar/Wind Harmer
5.919
24642205MAYFLWER
Adder
0.665
25196008MFTGT1
Adder
1.405
270356AE2-297 GEN
Solar/Wind Harmer
0.01
24441205WTRV SLR C
Solar/Wind Harmer
0
247604X1-042
Adder
0.433
270535AF1-215 GEN1
Solar/Wind Harmer
0.009
964401AG1-302 GEN
Solar/Wind Harmer
0.001
970217AG2-149 GEN
Solar/Wind Harmer
6.268
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
7.196
970243AG2-164 GEN
Solar/Wind Harmer
4.205
970519AG2-331 GEN
Solar/Wind Harmer
18.687
970699AG2-449 GEN
Solar/Wind Harmer
1.797
274752CRETE EC ;2U
Adder
8.477
274753CRETE EC ;3U
Adder
8.477
958171AF2-111 GEN
Solar/Wind Harmer
17.94
274772LINCOLN ;3U
Adder
8.676
274724RIVER EC ;11
Adder
18.203
972167AH1-666 GEN
Solar/Wind Harmer
5.717
24728705AND G3
Adder
8.214
274802UNIV PARK;5U
Adder
5.97
24728505AND G1
Adder
3.927
276806AD2-047 C O1
Solar/Wind Harmer
4.047
970941AG2-585 GEN
Solar/Wind Harmer
8.927
274826FISK ;BP
Adder
11.205
274800UNIV PARK;3U
Adder
5.966
972038AH1-567 GEN2
Adder
0.373
972228AH1-698 GEN2
Adder
3.79
276897AD1-100 C
Solar/Wind Harmer
0.009
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
970707AG2-453 GEN
Solar/Wind Harmer
23.303
274676JOLIET 29;8U
Adder
30.185
276893AG1-478 C
Solar/Wind Harmer
0.282
274729ELWOOD EC;1P
Adder
16.768
274730ELWOOD EC;6P
Adder
16.768
274734ELWOOD EC;8P
Adder
16.768
274736ELWOOD EC;9P
Adder
16.768
943121AE2-341 GEN
Solar/Wind Harmer
11.888
943591AF1-030 GEN
Solar/Wind Harmer
7.906
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
270541AE2-072 C
Solar/Wind Harmer
0.009
274682WAUKEGAN ;7U
Adder
9.728
276805AD2-038 GEN
Solar/Wind Harmer
0.002
964991AG1-363 GEN
Solar/Wind Helper
5.136
316097T157 G90
Solar/Wind Helper
1.504
23750701CROSSCHOOL
Solar/Wind Helper
1.502
238118U2-030_1
Solar/Wind Helper
0.341
238127S14_GEN_2
Solar/Wind Helper
0.827
238148AE2-230_GEN2
Solar/Wind Helper
0.497
237080AD1-060 GEN
Solar/Wind Helper
0.342
237038AE2-054 C
Solar/Wind Helper
0.272
235062AE1-101 C1
Solar/Wind Helper
1.659
23779801AA1-109
Solar/Wind Helper
0.193
237048AF1-022 C
Solar/Wind Helper
0.177
223401AF1-299 GEN
Solar/Wind Helper
0.367
316006AB2-029 C
Solar/Wind Helper
0.117
966131AG1-482 GEN
Solar/Wind Helper
0.137
233930AB2-032 GEN
Solar/Wind Helper
0.381
233915AB1-141 GEN
Solar/Wind Helper
0.502
232422X3-066 FULL
Solar/Wind Helper
0.114
232428Y3-058 C
Solar/Wind Helper
0.338
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
233998TM1NIN_3.36
Solar/Wind Helper
0.261
232404W1-003 C
Solar/Wind Helper
0.507
232434Z2-077 GEN
Solar/Wind Helper
0.127
233954AC2-188 GEN
Solar/Wind Helper
0.232
233950AC2-186 GEN
Solar/Wind Helper
0.116
233972AC1-094 C
Solar/Wind Helper
0.302
316045AC1-158 PL2
Solar/Wind Helper
4.138
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.23
228728W1-130C
Solar/Wind Helper
0.054
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219904AC1-010 C
Solar/Wind Helper
0.06
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.131
20720728JCB_W1-129
Solar/Wind Helper
0.057
316254AC1-120 GEN1
Solar/Wind Helper
1.059
207445AB1-138_GEN
Solar/Wind Helper
0.104
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.13
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.31
20715228NPK_W1-113
Solar/Wind Helper
0.078
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.495
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
207437AD2-070 GEN
Solar/Wind Helper
0.138
207518AF1-320_GEN
Solar/Wind Helper
1.571
20671928W4-073
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.029
270119AB2-067 GEN1
50/50
7.059
270120AB2-067 GEN2
50/50
7.059
24318905MLG2
50/50
7.071
270471AD2-092_GEN
Solar/Wind Harmer
0.006
942861AE2-305 GEN
Solar/Wind Harmer
6.335
970077AG2-063 GEN
Solar/Wind Harmer
4.631
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
938701AE1-092 GEN
Solar/Wind Harmer
12.917
971655AH1-328 GEN
Solar/Wind Harmer
2.854
964601AG1-323 GEN
Solar/Wind Harmer
3.215
964601AG1-323 GEN
Solar/Wind Harmer
2.143
270518AE2-148 GEN
Solar/Wind Harmer
0.691
972269AH1-719 GEN
Adder
2.584
972159AH1-661 GEN
Adder
1.118
253378AE2-206_GEN
Solar/Wind Harmer
0.004
276820AF1-078_GEN
Solar/Wind Harmer
0.002
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238126S14_GEN_1
Solar/Wind Helper
0.827
238152AF2-075_GEN
Solar/Wind Helper
0.707
238208AF1-136 C
Solar/Wind Helper
0.22
23546401DTGZ2-030
Solar/Wind Helper
0.089
237085AD2-009_GEN
Solar/Wind Helper
1.649
3138216PACIFIC
Solar/Wind Helper
0.044
316411AF1-147_GEN1
Solar/Wind Helper
0.888
316415AF1-147_GEN2
Solar/Wind Helper
0.888
23750501ELLIOTTS
Solar/Wind Helper
0.638
959381AF2-229 GEN
Solar/Wind Helper
0.357
3141426STAFORD
Solar/Wind Helper
0.052
960921AF2-383 GEN
Solar/Wind Helper
0.364
205943AE1-185 GEN
Solar/Wind Helper
0.509
205932AD2-116_GEN
Solar/Wind Helper
0.509
205956AE1-196_GEN
Solar/Wind Helper
0.509
233935AB2-179 C
Solar/Wind Helper
1.269
232436AB1-176 C
Solar/Wind Helper
0.044
233923SMA
Solar/Wind Helper
0.958
233990AG1-397 GEN
Solar/Wind Helper
0.27
232432Z2-076 GEN
Solar/Wind Helper
0.067
234033AF1-007_GEN
Solar/Wind Helper
7.02
964001AG1-254 GEN
Solar/Wind Helper
0.955
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.115
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.08
203975AE1-071-GEN
Solar/Wind Helper
2.498
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.29
219620RIDERU C
Solar/Wind Helper
0.001
316164AC1-076 GEN
Solar/Wind Helper
1.096
20675528CPH_W2-050
Solar/Wind Helper
0.087
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
218524CNTRALGAS1 C
Solar/Wind Helper
0.16
966261AG1-495 GEN
Solar/Wind Helper
0.081
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20675928HOL_W4-097
Solar/Wind Helper
0.05
207484AF2-139 C O1
Solar/Wind Helper
0.084
20674828DL_W4-046
Solar/Wind Helper
0.008
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.136
20675128HRM_W1-127
Solar/Wind Helper
0.029
209116AE2-175 GEN
Solar/Wind Helper
1.778
970329AG2-216 GEN
Solar/Wind Harmer
3.354
971199AH1-059 GEN
Solar/Wind Harmer
3.09
241960AC2-195 GEN
Solar/Wind Harmer
0.006
25326509SID D
Adder
1.451
971073AG2-665 GEN
Solar/Wind Harmer
6.898
25326109MON D
Adder
1.443
25322209TAIT E
Adder
10.642
25322209TAIT E
Adder
10.403
971201AH1-060 GEN
Solar/Wind Harmer
1.52
253370AE2-315 SEC1
Adder
2.182
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
246938BC-WTG3
Solar/Wind Harmer
0.273
246937BC-WTG2
Solar/Wind Harmer
0.305
971231AH1-075 GEN
Solar/Wind Harmer
0.861
253317AC1-085 GEN4
Solar/Wind Harmer
0.005
970611AG2-400 GEN
Solar/Wind Harmer
7.488
970627AG2-408 GEN
Solar/Wind Harmer
2.246
270007AE1-245 C
Solar/Wind Harmer
0.002
962581AG1-107 GEN
Solar/Wind Harmer
0.002
25183208HLCRTG
Solar/Wind Harmer
0.012
944541AF1-119 GEN
Solar/Wind Harmer
0.497
960971AF2-388 GEN
Solar/Wind Harmer
4.347
970623AG2-406 GEN
Solar/Wind Harmer
1.356
942221AE2-234 GEN
Solar/Wind Harmer
0.037
252519AF1-045_GEN
Solar/Wind Harmer
6.44
252516AE2-318_GEN
Solar/Wind Harmer
5.712
247621Y3-024
Adder
0.255
970883AG2-550 GEN
Solar/Wind Harmer
7.389
970885AG2-551 GEN
Solar/Wind Harmer
2.463
270201AC2-176 GEN
Solar/Wind Harmer
0.001
25194408D.CRK1
Adder
8.004
25194508D.CRK3
Adder
1.496
970621AG2-405 GEN
Solar/Wind Harmer
1.351
964611AG1-324 GEN
Solar/Wind Harmer
0.553
252509AD1-136 GEN
Solar/Wind Harmer
0.037
970321AG2-212 GEN
Solar/Wind Harmer
3.191
270599AE1-208 GEN
Solar/Wind Harmer
6.737
270031AE2-169
Solar/Wind Harmer
4.042
270186AC1-089 GEN
Solar/Wind Harmer
0.004
270383AD1-128 GEN
Solar/Wind Harmer
0.004
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
970825AG2-519 GEN
Solar/Wind Harmer
8.127
247620Y3-023
Adder
0.484
960441AF2-335 GEN
Solar/Wind Harmer
7.33
270216AD2-079_GEN
Solar/Wind Harmer
0.001
971613AH1-306 GEN
Solar/Wind Harmer
3.512
24728805RICHG1
Adder
3.964
24728905RICHG2
Adder
3.964
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
14.589
961051AF2-396 GEN
Solar/Wind Harmer
9.726
270526AF1-158 GEN
Solar/Wind Harmer
0.009
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
9.095
965791AG1-447 GEN
Solar/Wind Harmer
6.67
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
970239AG2-162 GEN
Solar/Wind Harmer
1.797
274770LINCOLN ;1U
Adder
8.676
274771LINCOLN ;2U
Adder
8.676
966841AG1-555 GEN
Solar/Wind Harmer
0.81
274808UNIV PK N;4U
Adder
5.117
274803UNIV PARK;6U
Adder
5.97
274888KELLY CRK;1U
Solar/Wind Harmer
0.419
274887GEN-1.85
Solar/Wind Harmer
0.188
276843GEN-1.7
Solar/Wind Harmer
0.231
958011AF2-095 GEN
Solar/Wind Harmer
10.284
972259AH1-714 GEN
Adder
19.507
274674JOLIET 9 ;6U
Adder
15.704
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
970241AG2-163 GEN
Solar/Wind Harmer
4.144
958481AF2-142 GEN
Solar/Wind Harmer
10.621
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.958
971573AH1-285 GEN
Solar/Wind Harmer
1.319
274696ROCKY RD ;4P
Adder
11.537
274695ROCKY RD ;2P
Adder
11.271
274693ROCKY RD ;1P
Adder
11.16
274697ROCKY RD ;3P
Adder
3.062
958491AF2-143 GEN
Solar/Wind Harmer
10.588
274879MINONK ;1U
Solar/Wind Harmer
0.297
23585401KL_K28_T16
Solar/Wind Helper
1.482
238120AE2-309 GEN
Solar/Wind Helper
0.525
238175AF1-290_GEN
Solar/Wind Helper
0.153
238169AE2-226 GEN1
Solar/Wind Helper
0.701
238170AE2-226 GEN2
Solar/Wind Helper
0.701
235020AA1-095 C
Solar/Wind Helper
0.053
23777901MDS_W4-102
Solar/Wind Helper
0.177
237002AB1-128_GEN
Solar/Wind Helper
0.443
237034AC2-136 C
Solar/Wind Helper
0.227
235063AE1-101 C2
Solar/Wind Helper
1.659
237001AB1-127_GEN
Solar/Wind Helper
0.442
23777801MSM_W1-116
Solar/Wind Helper
0.114
237025AB1-124 C
Solar/Wind Helper
0.164
237006AB1-125 GEN
Solar/Wind Helper
0.123
226929AD2-058 GEN
Solar/Wind Helper
0.099
205916AD1-020 GEN
Solar/Wind Helper
1.713
20390526W1-045 C
Solar/Wind Helper
0.35
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
233987AB2-037 GEN
Solar/Wind Helper
2.342
233933AB2-153 GEN
Solar/Wind Helper
0.232
233944AB2-135 GEN
Solar/Wind Helper
0.588
232424Y1-079 C
Solar/Wind Helper
0.116
234036AF2-325 C
Solar/Wind Helper
0.042
233946AB2-136 GEN
Solar/Wind Helper
0.568
233901CHERRYDALE C
Solar/Wind Helper
0.232
232408W1-005 C
Solar/Wind Helper
0.507
232410W1-006 C
Solar/Wind Helper
0.507
233939AC1-091 C
Solar/Wind Helper
0.35
233970AC1-092 C
Solar/Wind Helper
0.35
315651AD1-115 GEN
Solar/Wind Helper
0.785
316447AC1-158 HLD
Solar/Wind Helper
2.845
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.04
219921AF1-264
Solar/Wind Helper
0.051
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.082
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.19
20716928W4-060COL
Solar/Wind Helper
0.051
218440SUMMTASSOC C
Solar/Wind Helper
0.016
20673828FLE_V3-070
Solar/Wind Helper
0.09
207442AE1-156 GEN
Solar/Wind Helper
0.326
20676128MHD_W3-029
Solar/Wind Helper
0.096
20671828STAW2-080
Solar/Wind Helper
0.027
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
207471AF2-354 C
Solar/Wind Helper
0.168
20674928WA_W3-044
Solar/Wind Helper
0.098
20676228FRD_X1-012
Solar/Wind Helper
0.092
964851AG1-348 GEN
Solar/Wind Helper
0.081
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.074
211065PSPA IPP
Solar/Wind Helper
0.151
211065PSPA IPP
Solar/Wind Helper
0.151
270166AC1-044 GEN3
50/50
7.059
23559101PLEAS2
50/50
6.1
962761AG1-125 GEN
Solar/Wind Harmer
34.524
970149AG2-104 GEN
Solar/Wind Harmer
37.287
970155AG2-107 GEN
Solar/Wind Harmer
22.046
270349AD2-093_GEN
Solar/Wind Harmer
0.006
24721705FLATG2
Adder
23.918
270159DARBY CT4
Adder
10.243
970593AG2-378 GEN
Solar/Wind Harmer
1.812
270223U2-072_GEN1
Solar/Wind Harmer
0.001
253343AC1-166 GEN
Solar/Wind Harmer
0.003
253325AC1-069 GEN
Solar/Wind Harmer
0.012
270462AD2-086
Solar/Wind Harmer
0.017
971995AH1-542 GEN
Solar/Wind Harmer
2.906
270263AC1-001 GEN
Solar/Wind Harmer
0.786
270510AE1-227 GEN1
Solar/Wind Harmer
1.963
25326309TAIT D
Adder
1.196
241813AF1-122_GEN
Solar/Wind Harmer
3.405
960071AF2-298 GEN
Solar/Wind Harmer
3.786
253370AE2-315 SEC1
Adder
2.182
253371AE2-315 SEC2
Adder
2.063
927014AC1-188 GEN
Solar/Wind Harmer
0.005
246936BC-WTG1
Solar/Wind Harmer
0.305
270489AE1-102 GEN1
Solar/Wind Harmer
0.979
965421AG1-410 GEN
Solar/Wind Harmer
22.57
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.499
247521TR3_G114
Solar/Wind Harmer
0.273
270246TR4_N_V150
Solar/Wind Harmer
0.048
965011AG1-365 GEN
Solar/Wind Harmer
7.488
24695305TIMB G C
Solar/Wind Harmer
0.002
965651AG1-433 GEN
Solar/Wind Harmer
2.174
958861AF2-177 GEN
Solar/Wind Harmer
3.207
247536S-71 GEN
Solar/Wind Harmer
0.297
25194608D.CRK4
Adder
1.74
945371AF1-202 GEN
Solar/Wind Harmer
0.001
252507AC2-088 GEN
Solar/Wind Harmer
0.335
270063AE2-323 C
Solar/Wind Harmer
0.006
970245AG2-165 GEN
Solar/Wind Harmer
3.191
970947AG2-589 GEN
Solar/Wind Harmer
0.245
270005AE1-210 C O1
Solar/Wind Harmer
1.59
965031AG1-367 GEN
Solar/Wind Harmer
7.338
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.378
970825AG2-519 GEN
Solar/Wind Harmer
2.603
25196808ZIMRHP
Adder
79.729
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
944231AF1-091 GEN
Solar/Wind Harmer
1.953
24639705ELKHART HY
Adder
0.161
270032AE2-172
Solar/Wind Harmer
4.877
970291AG2-192 GEN
Solar/Wind Harmer
0.95
945111AF1-176 GEN
Solar/Wind Harmer
13.03
270505AE1-170 C O1
Solar/Wind Harmer
7.665
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.805
276903AD2-071 C
Solar/Wind Harmer
8.137
25196008MFTGT1
Adder
1.45
247522W1-056 GEN
Solar/Wind Harmer
0.001
970773AG2-487 GEN
Solar/Wind Harmer
1.284
970373AG2-245 GEN
Solar/Wind Harmer
15.247
270055AF2-134 C O1
Solar/Wind Harmer
0.006
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.41
970515AG2-329 GEN
Solar/Wind Harmer
18.805
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
9.032
24791305MDL-5G
Solar/Wind Harmer
0.001
970333AG2-219 GEN
Solar/Wind Harmer
5.139
274751CRETE EC ;1U
Adder
8.477
274754CRETE EC ;4U
Adder
8.477
274773LINCOLN ;4U
Adder
8.676
274774LINCOLN ;5U
Adder
8.676
274723RIVER EC ;12
Adder
18.418
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
5.139
24728605AND G2
Adder
3.927
276776AD2-060 GEN
Solar/Wind Harmer
0.746
945681AF1-233 GEN
Solar/Wind Harmer
13.461
274801UNIV PARK;4U
Adder
5.966
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
31.303
274732ELWOOD EC;7P
Adder
16.768
274674JOLIET 9 ;6U
Adder
15.704
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
963741AG1-226 GEN
Solar/Wind Harmer
16.815
274745AC1-111 GEN9
Adder
5.679
939401AE1-172 GEN
Solar/Wind Harmer
5.301
276691AA1-018 GEN1
Solar/Wind Harmer
0.858
970091AG2-072 GEN
Adder
77.629
276901AD2-066 C O1
Solar/Wind Harmer
0.007
316095T157 G97
Solar/Wind Helper
1.504
23583801GRNGAP
Solar/Wind Helper
5.601
238185AF2-356 C
Solar/Wind Helper
2.646
238108AE1-109 GEN1
Solar/Wind Helper
0.114
235054AD2-180 GEN
Solar/Wind Helper
2.03
235531U2-073 GEN
Solar/Wind Helper
3.282
238117U2-030
Solar/Wind Helper
0.341
238147AE2-230_GEN1
Solar/Wind Helper
0.495
238149AF1-291A_GEN
Solar/Wind Helper
0.141
23751201ROTHROCK
Solar/Wind Helper
0.824
237061AD1-155 GEN
Solar/Wind Helper
0.053
23562501BACKB
Solar/Wind Helper
1.007
238221AF1-254 C O1
Solar/Wind Helper
0.274
235067AD1-061 GEN
Solar/Wind Helper
0.496
23751101LEADS_P59
Solar/Wind Helper
1.404
237030AB1-096 C
Solar/Wind Helper
0.071
3141196NOKESVL
Solar/Wind Helper
1.032
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.346
223402AF1-300 C
Solar/Wind Helper
0.367
205917AD1-020 ES
Solar/Wind Helper
0.368
233918AB1-142 GEN
Solar/Wind Helper
0.502
233982AB2-133 GEN
Solar/Wind Helper
0.358
233994AC2-023 GEN
Solar/Wind Helper
0.961
233996TM1833_GEN
Solar/Wind Helper
0.261
233997TMININ_4.2
Solar/Wind Helper
0.261
232406W1-004 FULL
Solar/Wind Helper
0.507
233940AF2-379 C
Solar/Wind Helper
0.062
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.232
233971AC1-093 C
Solar/Wind Helper
0.357
316044AC1-158 PL1
Solar/Wind Helper
1.293
316450AC1-158 RIC
Solar/Wind Helper
0.345
230430AE1-229_GEN
Solar/Wind Helper
3.372
230415AB2-049 C
Solar/Wind Helper
0.03
228729W2-030 C
Solar/Wind Helper
0.11
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.15
219291REEVESSOUT C
Solar/Wind Helper
0.011
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
219348LDSOLAR C
Solar/Wind Helper
0.114
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.063
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.353
219276PARKLANDSO C
Solar/Wind Helper
0.089
20714528FRN_Y2-051
Solar/Wind Helper
0.057
20720528MAN_W1-024
Solar/Wind Helper
0.028
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.027
219908AB1-139 C
Solar/Wind Helper
0.074
219249CENTRALDIV C
Solar/Wind Helper
0.01
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.089
971997AH1-543 GEN
Solar/Wind Harmer
2.724
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.078
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.1
MECLTFEXP_MEC->PJM
CLTF
15.901
SIGELTFEXP_SIGE->PJM
CLTF
0.505
LAGNLTFEXP_LAGN->PJM
CLTF
14.837
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.802
TVALTFEXP_TVA->PJM
CLTF
7.293
CPLELTFEXP_CPLE->PJM
CLTF
0.624
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.816
NYPJM->LTFIMP_NY
CLTF
4.797
LGEELTFEXP_LGEE->PJM
CLTF
6.749
WECLTFEXP_WEC->PJM
CLTF
3.825
AG2-052LTFEXP_AG2-052->PJM
LTF
0.24
AH1-155LTFEXP_AH1-155->PJM
LTF
0.359

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-012_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-012_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:130.23 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4856.26
MW Contribution:11.59
Bus #Bus NameTypeMW Contribution
270166AC1-044 GEN3
50/50
7.033
23559101PLEAS2
50/50
5.443
270122AB2-093 CT
50/50
4.116
962761AG1-125 GEN
Solar/Wind Harmer
40.965
970149AG2-104 GEN
Solar/Wind Harmer
50.592
970155AG2-107 GEN
Solar/Wind Harmer
17.863
270349AD2-093_GEN
Solar/Wind Harmer
4.529
270223U2-072_GEN1
Solar/Wind Harmer
2.339
270578AF1-285 GEN2
Solar/Wind Harmer
1.43
270391AF1-285 GEN3
Solar/Wind Harmer
1.43
270159DARBY CT4
Adder
10.388
971995AH1-542 GEN
Solar/Wind Harmer
12.974
970593AG2-378 GEN
Solar/Wind Harmer
2.345
270462AD2-086
Solar/Wind Harmer
8.157
270510AE1-227 GEN1
Solar/Wind Harmer
2.893
24721705FLATG2
Adder
23.506
253343AC1-166 GEN
Solar/Wind Harmer
1.256
253325AC1-069 GEN
Solar/Wind Harmer
1.211
241813AF1-122_GEN
Solar/Wind Harmer
7.346
270263AC1-001 GEN
Solar/Wind Harmer
1.187
241847AF2-150_GEN
Solar/Wind Harmer
4.622
246936BC-WTG1
Solar/Wind Harmer
4.343
270489AE1-102 GEN1
Solar/Wind Harmer
1.443
965421AG1-410 GEN
Solar/Wind Harmer
33.256
970515AG2-329 GEN
Solar/Wind Harmer
16.033
25326309TAIT D
Adder
1.21
960071AF2-298 GEN
Solar/Wind Harmer
5.501
253370AE2-315 SEC1
Adder
2.206
253371AE2-315 SEC2
Adder
2.086
247521TR3_G114
Solar/Wind Harmer
3.699
270246TR4_N_V150
Solar/Wind Harmer
0.936
247522W1-056 GEN
Solar/Wind Harmer
2.477
24695305TIMB G C
Solar/Wind Harmer
6.051
965011AG1-365 GEN
Solar/Wind Harmer
10.972
927014AC1-188 GEN
Solar/Wind Harmer
1.729
944231AF1-091 GEN
Solar/Wind Harmer
4.078
253432AC1-085 GEN2
Solar/Wind Harmer
0.29
946171AF1-282 GEN
Solar/Wind Harmer
10.828
270063AE2-323 C
Solar/Wind Harmer
2.376
965651AG1-433 GEN
Solar/Wind Harmer
5.885
24318805MLG1
50/50
10.022
23559001PLEAS1
50/50
5.443
972239AH1-704 GEN
50/50
3.102
962771AG1-126 GEN
Solar/Wind Harmer
40.965
270459AD2-067 GEN
Solar/Wind Harmer
10.453
961821AG1-024 GEN
Solar/Wind Harmer
10.613
270054AF2-122 C O1
Solar/Wind Harmer
4.071
270284AF1-227 GEN1
Solar/Wind Harmer
6.912
270286AF1-227 GEN2
Solar/Wind Harmer
2.557
270287AF1-227 GEN3
Solar/Wind Harmer
2.557
270520AE2-214 GEN
Solar/Wind Harmer
7.382
253383AE2-342_GEN
Solar/Wind Harmer
1.062
241973AD2-163_GEN1
Solar/Wind Harmer
2.37
940611AE2-048 GEN
Solar/Wind Harmer
26.074
941391AE2-136 GEN
Solar/Wind Harmer
13.511
270578AF1-285 GEN2
Solar/Wind Harmer
0.55
943861AF1-054 GEN
Solar/Wind Harmer
4.552
943851AF1-053 GEN
Solar/Wind Harmer
2.2
945631AF1-228 GEN
Solar/Wind Harmer
5.537
270156DARBY CT1
Adder
10.556
270157DARBY CT2
Adder
10.53
270158DARBY CT3
Adder
10.362
270302AB2-170 GEN
Solar/Wind Harmer
9.805
270317AD1-130_GEN
Solar/Wind Harmer
3.759
970689AG2-444 GEN
Solar/Wind Harmer
19.055
270432AC2-029 GEN
Solar/Wind Harmer
8.138
958581AF2-149 GEN
Solar/Wind Harmer
4.968
970179AG2-119 GEN
Solar/Wind Harmer
9.26
270269AC2-059
Solar/Wind Harmer
10.704
241972AD1-140 GEN
Solar/Wind Harmer
5.084
971567AH1-282 GEN
Solar/Wind Harmer
16.984
966831AG1-554 GEN
Solar/Wind Harmer
1.34
971989AH1-539 GEN
Solar/Wind Harmer
14.49
270340AC2-060 GEN
Solar/Wind Harmer
3.371
957201AF2-014 GEN
Solar/Wind Harmer
5.033
270435AC2-044 GEN
Solar/Wind Harmer
2.219
970879AG2-548 GEN
Solar/Wind Harmer
4.763
247607V1-011 GEN
Solar/Wind Harmer
4.359
253372AE2-315 SEC3
Adder
2.086
253372AE2-315 SEC3
Adder
2.086
965051AG1-369 GEN
Solar/Wind Harmer
5.494
25306009OHH W.
Adder
3.166
270297AD1-101 GEN
Solar/Wind Harmer
3.056
965041AG1-368 GEN
Solar/Wind Harmer
10.974
253349AC2-067 GEN
Solar/Wind Harmer
5.466
253400AC2-068 GEN
Solar/Wind Harmer
2.198
963791AG1-232 GEN
Solar/Wind Harmer
14.679
270071AF1-092 GEN
Solar/Wind Harmer
16.242
24729505KEY G4
Adder
7.02
945641AF1-229 GEN
Solar/Wind Harmer
3.923
270024AE2-089 GEN
Solar/Wind Harmer
5.065
958711AF2-162 GEN
Solar/Wind Harmer
1.089
965101AG1-375 GEN
Solar/Wind Harmer
10.752
961761AG1-017 GEN
Solar/Wind Harmer
0.46
270543AE2-219 C
Solar/Wind Harmer
5.494
971029AG2-637 GEN
Solar/Wind Harmer
16.089
971673AH1-337 GEN
Solar/Wind Harmer
4.934
25196408WSDLE3
Adder
9.412
25196308WSDLE2
Adder
9.33
25196208WSDLE1
Adder
9.306
25196708WSDLE6
Adder
9.283
25196508WSDLE4
Adder
9.049
25196108MFTGT2
Adder
1.608
25196108MFTGT2
Adder
1.494
274775LINCOLN ;6U
Adder
8.792
274776LINCOLN ;7U
Adder
8.792
274777LINCOLN ;8U
Adder
8.792
274814UNIV PK N;0U
Adder
5.256
274807UNIV PK N;3U
Adder
5.245
274805UNIV PK N;1U
Adder
5.222
274811UNIV PK N;7U
Adder
5.21
972037AH1-567 GEN1
Adder
0.19
274827FISK ;RP
Adder
8.047
972227AH1-698 GEN1
Adder
2.704
274687WILL CNTY;4U
Adder
28.893
274687WILL CNTY;4U
Adder
28.893
274675JOLIET 29;7U
Adder
31.706
274675JOLIET 29;7U
Adder
30.574
274731ELWOOD EC;2P
Adder
16.983
274733ELWOOD EC;3P
Adder
16.983
274735ELWOOD EC;4P
Adder
16.983
274728ELWOOD EC;5P
Adder
16.983
238109AE1-109 GEN2
Solar/Wind Helper
0.121
238110AE1-109 GEN3
Solar/Wind Helper
0.121
238152AF2-075_GEN
Solar/Wind Helper
0.789
23546401DTGZ2-030
Solar/Wind Helper
0.099
238126S14_GEN_1
Solar/Wind Helper
0.867
238208AF1-136 C
Solar/Wind Helper
0.236
237085AD2-009_GEN
Solar/Wind Helper
1.767
3138216PACIFIC
Solar/Wind Helper
0.049
316411AF1-147_GEN1
Solar/Wind Helper
0.978
316415AF1-147_GEN2
Solar/Wind Helper
0.978
3141426STAFORD
Solar/Wind Helper
0.058
316164AC1-076 GEN
Solar/Wind Helper
1.225
23750501ELLIOTTS
Solar/Wind Helper
0.629
959381AF2-229 GEN
Solar/Wind Helper
0.367
960921AF2-383 GEN
Solar/Wind Helper
0.185
205943AE1-185 GEN
Solar/Wind Helper
0.518
205932AD2-116_GEN
Solar/Wind Helper
0.518
205956AE1-196_GEN
Solar/Wind Helper
0.518
233935AB2-179 C
Solar/Wind Helper
1.29
232436AB1-176 C
Solar/Wind Helper
0.045
233923SMA
Solar/Wind Helper
0.974
233990AG1-397 GEN
Solar/Wind Helper
0.031
232432Z2-076 GEN
Solar/Wind Helper
0.068
234033AF1-007_GEN
Solar/Wind Helper
7.137
964001AG1-254 GEN
Solar/Wind Helper
0.966
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.116
203975AE1-071-GEN
Solar/Wind Helper
2.53
219272CLEANLIGHT C
Solar/Wind Helper
0.026
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.081
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.292
219620RIDERU C
Solar/Wind Helper
0.001
20675528CPH_W2-050
Solar/Wind Helper
0.087
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
218524CNTRALGAS1 C
Solar/Wind Helper
0.161
966261AG1-495 GEN
Solar/Wind Helper
0.081
207530AG1-191 GEN
Solar/Wind Helper
0.066
958861AF2-177 GEN
Solar/Wind Harmer
11.752
247536S-71 GEN
Solar/Wind Harmer
4.346
960001AF2-291 GEN
Solar/Wind Harmer
3.244
945371AF1-202 GEN
Solar/Wind Harmer
7.479
24639705ELKHART HY
Adder
0.164
25194608D.CRK4
Adder
1.752
25196808ZIMRHP
Adder
80.188
23906502RICHG2&3
Adder
1.272
972301AH1-735 GEN
Adder
6.357
23906402RICHG1
Adder
1.271
25196008MFTGT1
Adder
1.459
274751CRETE EC ;1U
Adder
8.598
274754CRETE EC ;4U
Adder
8.598
274723RIVER EC ;12
Adder
18.677
274773LINCOLN ;4U
Adder
8.792
274774LINCOLN ;5U
Adder
8.792
274812UNIV PK N;8U
Adder
5.21
23920202STRYCT
Adder
1.444
274801UNIV PARK;4U
Adder
6.045
274676JOLIET 29;8U
Adder
31.706
274732ELWOOD EC;7P
Adder
2.004
23583801GRNGAP
Solar/Wind Helper
6.365
316095T157 G97
Solar/Wind Helper
1.705
238108AE1-109 GEN1
Solar/Wind Helper
0.121
238185AF2-356 C
Solar/Wind Helper
2.767
238147AE2-230_GEN1
Solar/Wind Helper
0.552
238149AF1-291A_GEN
Solar/Wind Helper
0.158
237061AD1-155 GEN
Solar/Wind Helper
0.06
235054AD2-180 GEN
Solar/Wind Helper
2.111
235531U2-073 GEN
Solar/Wind Helper
3.439
238117U2-030
Solar/Wind Helper
0.356
238221AF1-254 C O1
Solar/Wind Helper
0.295
235067AD1-061 GEN
Solar/Wind Helper
0.532
3141196NOKESVL
Solar/Wind Helper
1.141
23751201ROTHROCK
Solar/Wind Helper
0.819
237030AB1-096 C
Solar/Wind Helper
0.075
23562501BACKB
Solar/Wind Helper
0.997
226910AB2-157 C
Solar/Wind Helper
0.015
227287AC2-120 GEN
Solar/Wind Helper
0.375
223402AF1-300 C
Solar/Wind Helper
0.387
316044AC1-158 PL1
Solar/Wind Helper
1.443
316450AC1-158 RIC
Solar/Wind Helper
0.385
316170AC1-121 GEN2
Solar/Wind Helper
0.395
23751101LEADS_P59
Solar/Wind Helper
1.316
205917AD1-020 ES
Solar/Wind Helper
0.379
3132273ORANGE
Solar/Wind Helper
0.049
233918AB1-142 GEN
Solar/Wind Helper
0.511
233982AB2-133 GEN
Solar/Wind Helper
0.364
233994AC2-023 GEN
Solar/Wind Helper
0.977
233996TM1833_GEN
Solar/Wind Helper
0.266
233997TMININ_4.2
Solar/Wind Helper
0.266
232406W1-004 FULL
Solar/Wind Helper
0.516
3147666LOUISA
Solar/Wind Helper
0.551
233940AF2-379 C
Solar/Wind Helper
0.063
234015AF2-250 C
Solar/Wind Helper
0.039
233952AC2-187 GEN
Solar/Wind Helper
0.236
233971AC1-093 C
Solar/Wind Helper
0.363
230430AE1-229_GEN
Solar/Wind Helper
3.409
230415AB2-049 C
Solar/Wind Helper
0.031
228729W2-030 C
Solar/Wind Helper
0.112
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.151
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
219348LDSOLAR C
Solar/Wind Helper
0.115
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.064
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.057
219276PARKLANDSO C
Solar/Wind Helper
0.09
20714528FRN_Y2-051
Solar/Wind Helper
0.057
20720528MAN_W1-024
Solar/Wind Helper
0.028
966881AG1-559 GEN
Solar/Wind Helper
0.312
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.027
219249CENTRALDIV C
Solar/Wind Helper
0.01
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.089
270119AB2-067 GEN1
50/50
7.033
270120AB2-067 GEN2
50/50
7.033
24318905MLG2
50/50
7.475
270471AD2-092_GEN
Solar/Wind Harmer
4.529
946101AF1-275 GEN
Solar/Wind Harmer
1.842
938701AE1-092 GEN
Solar/Wind Harmer
24.483
270224U2-072_GEN2
Solar/Wind Harmer
2.339
270227U2-072_GEN3
Solar/Wind Harmer
2.339
270228U2-072_GEN4
Solar/Wind Harmer
2.339
270231U2-072_GEN5
Solar/Wind Harmer
2.339
942861AE2-305 GEN
Solar/Wind Harmer
9.223
964601AG1-323 GEN
Solar/Wind Harmer
3.753
964601AG1-323 GEN
Solar/Wind Harmer
1.746
972269AH1-719 GEN
Adder
2.7
970077AG2-063 GEN
Solar/Wind Harmer
6.332
972159AH1-661 GEN
Adder
1.166
270518AE2-148 GEN
Solar/Wind Harmer
14.068
971199AH1-059 GEN
Solar/Wind Harmer
4.644
241960AC2-195 GEN
Solar/Wind Harmer
3.219
971201AH1-060 GEN
Solar/Wind Harmer
2.296
253378AE2-206_GEN
Solar/Wind Harmer
4.086
276820AF1-078_GEN
Solar/Wind Harmer
1.815
971231AH1-075 GEN
Solar/Wind Harmer
0.905
25326509SID D
Adder
1.48
25326109MON D
Adder
1.461
246938BC-WTG3
Solar/Wind Harmer
4.418
246937BC-WTG2
Solar/Wind Harmer
4.343
970879AG2-548 GEN
Solar/Wind Harmer
6.827
971073AG2-665 GEN
Solar/Wind Harmer
6.827
971073AG2-665 GEN
Solar/Wind Harmer
4.763
25322209TAIT E
Adder
10.77
25322209TAIT E
Adder
10.528
270007AE1-245 C
Solar/Wind Harmer
6.539
942801AE2-298 GEN
Solar/Wind Harmer
1.667
253370AE2-315 SEC1
Adder
2.206
970611AG2-400 GEN
Solar/Wind Harmer
10.972
253394AE2-221_GEN
Solar/Wind Harmer
4.954
253398AE2-221_GEN2
Solar/Wind Harmer
4.954
253317AC1-085 GEN4
Solar/Wind Harmer
9.07
971677AH1-339 GEN
Solar/Wind Harmer
8.643
942221AE2-234 GEN
Solar/Wind Harmer
0.79
944541AF1-119 GEN
Solar/Wind Harmer
4.511
960971AF2-388 GEN
Solar/Wind Harmer
11.771
247621Y3-024
Adder
0.259
270201AC2-176 GEN
Solar/Wind Harmer
5.522
970883AG2-550 GEN
Solar/Wind Harmer
10.73
970885AG2-551 GEN
Solar/Wind Harmer
2.495
247620Y3-023
Adder
0.494
964611AG1-324 GEN
Solar/Wind Harmer
1.264
964611AG1-324 GEN
Solar/Wind Harmer
0.561
25194408D.CRK1
Adder
8.061
25194508D.CRK3
Adder
1.507
24728805RICHG1
Adder
4.003
24728905RICHG2
Adder
4.003
970935AG2-582 GEN
Adder
239.406
274770LINCOLN ;1U
Adder
8.792
274771LINCOLN ;2U
Adder
8.792
274808UNIV PK N;4U
Adder
5.188
274803UNIV PARK;6U
Adder
6.05
972259AH1-714 GEN
Adder
19.76
238175AF1-290_GEN
Solar/Wind Helper
0.168
238169AE2-226 GEN1
Solar/Wind Helper
0.772
238170AE2-226 GEN2
Solar/Wind Helper
0.772
238120AE2-309 GEN
Solar/Wind Helper
0.552
23585401KL_K28_T16
Solar/Wind Helper
1.529
235020AA1-095 C
Solar/Wind Helper
0.057
23777901MDS_W4-102
Solar/Wind Helper
0.191
237034AC2-136 C
Solar/Wind Helper
0.244
237002AB1-128_GEN
Solar/Wind Helper
0.475
235063AE1-101 C2
Solar/Wind Helper
1.776
237001AB1-127_GEN
Solar/Wind Helper
0.473
23777801MSM_W1-116
Solar/Wind Helper
0.122
237025AB1-124 C
Solar/Wind Helper
0.175
237006AB1-125 GEN
Solar/Wind Helper
0.131
226929AD2-058 GEN
Solar/Wind Helper
0.108
315651AD1-115 GEN
Solar/Wind Helper
0.876
316447AC1-158 HLD
Solar/Wind Helper
3.175
205916AD1-020 GEN
Solar/Wind Helper
1.761
20390526W1-045 C
Solar/Wind Helper
0.36
208835TUHI V3-051
Solar/Wind Helper
0.025
208835TUHI V3-051
Solar/Wind Helper
0.025
3132123MT JACKSON
Solar/Wind Helper
0.764
233987AB2-037 GEN
Solar/Wind Helper
2.381
233933AB2-153 GEN
Solar/Wind Helper
0.236
232424Y1-079 C
Solar/Wind Helper
0.118
233944AB2-135 GEN
Solar/Wind Helper
0.598
233946AB2-136 GEN
Solar/Wind Helper
0.577
234036AF2-325 C
Solar/Wind Helper
0.043
233901CHERRYDALE C
Solar/Wind Helper
0.236
232408W1-005 C
Solar/Wind Helper
0.516
232410W1-006 C
Solar/Wind Helper
0.516
233939AC1-091 C
Solar/Wind Helper
0.356
233970AC1-092 C
Solar/Wind Helper
0.356
966001AG1-469 GEN
Solar/Wind Helper
0.255
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.041
219921AF1-264
Solar/Wind Helper
0.052
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.083
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.19
20716928W4-060COL
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.016
20673828FLE_V3-070
Solar/Wind Helper
0.091
207442AE1-156 GEN
Solar/Wind Helper
0.326
20676128MHD_W3-029
Solar/Wind Helper
0.096
20671828STAW2-080
Solar/Wind Helper
0.027
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
207471AF2-354 C
Solar/Wind Helper
0.168
20674928WA_W3-044
Solar/Wind Helper
0.098
20676228FRD_X1-012
Solar/Wind Helper
0.091
964851AG1-348 GEN
Solar/Wind Helper
0.081
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.044
211065PSPA IPP
Solar/Wind Helper
0.15
211065PSPA IPP
Solar/Wind Helper
0.15
270051AF1-062 GEN
50/50
11.999
970153AG2-106 GEN
Solar/Wind Harmer
17.863
961921AG1-034 GEN
Solar/Wind Harmer
15.919
241955AC1-078 GEN
Solar/Wind Harmer
8.948
241974AD2-163_GEN2
Solar/Wind Harmer
2.37
942051AE2-217 GEN
Solar/Wind Harmer
21.374
942871AE2-306 GEN
Solar/Wind Harmer
1.073
270391AF1-285 GEN3
Solar/Wind Harmer
0.55
960801AF2-371 GEN
Solar/Wind Harmer
2.991
964871AG1-351 GEN
Solar/Wind Harmer
2.065
970605AG2-385 GEN
Solar/Wind Harmer
6.332
270485AE1-090_GEN
Solar/Wind Harmer
0.709
270512AE1-227 GEN2
Solar/Wind Harmer
2.455
24721905FLATG4
Adder
23.506
253338AC1-165 GEN
Solar/Wind Harmer
1.256
253333AC1-068 GEN
Solar/Wind Harmer
1.211
970065AG2-057 GEN
Solar/Wind Harmer
1.148
270273AD2-016 GEN
Solar/Wind Harmer
3.061
972173AH1-669 GEN
Solar/Wind Harmer
5.721
270377AD1-106 GEN
Solar/Wind Harmer
6.988
270588AE1-091_GEN
Solar/Wind Harmer
12.311
270291AC1-194 GEN
Solar/Wind Harmer
11.854
253415AE1-040 GEN
Solar/Wind Harmer
1.258
961961AG1-039 GEN
Solar/Wind Harmer
3.188
270491AE1-102 GEN2
Solar/Wind Harmer
1.443
970217AG2-149 GEN
Solar/Wind Harmer
35.355
958091AF2-103 GEN
Solar/Wind Harmer
0.178
253303V4-073 C
Solar/Wind Harmer
0.128
253370AE2-315 SEC1
Adder
2.206
253371AE2-315 SEC2
Adder
2.086
270191TR4_S_V150
Solar/Wind Harmer
3.3
270247TR4_N_V136
Solar/Wind Harmer
0.936
959331AF2-224 GEN
Solar/Wind Harmer
10.972
965021AG1-366 GEN
Solar/Wind Harmer
2.552
270258AD1-119 GEN
Solar/Wind Harmer
3.051
253406AD2-031_GEN
Solar/Wind Harmer
1.398
270044AE2-322 C
Solar/Wind Harmer
1.435
270404AC1-167 GEN
Solar/Wind Harmer
1.194
957541AF2-048 GEN
Solar/Wind Harmer
1.725
270043AE2-236 GEN
Solar/Wind Harmer
5.98
944531AF1-118 GEN
Solar/Wind Harmer
37.943
253316AC1-085 GEN3
Solar/Wind Harmer
9.07
253433AC1-085 GEN1
Solar/Wind Harmer
5.758
946181AF1-283 GEN
Solar/Wind Harmer
14.077
970031AG2-029 GEN
Solar/Wind Harmer
32.394
971617AH1-308 GEN
Solar/Wind Harmer
6.274
270541AE2-072 C
Solar/Wind Harmer
4.881
971191AH1-055 GEN
Solar/Wind Harmer
23.635
962031AG1-047 GEN
Solar/Wind Harmer
3.246
957741AF2-068 GEN
Solar/Wind Harmer
16.111
25196608WSDLE5
Adder
9.143
24642205MAYFLWER
Adder
0.678
25194608D.CRK4
Adder
1.752
247604X1-042
Adder
0.444
23906502RICHG2&3
Adder
1.272
25196008MFTGT1
Adder
1.413
274752CRETE EC ;2U
Adder
8.598
274753CRETE EC ;3U
Adder
8.598
274724RIVER EC ;11
Adder
18.459
274772LINCOLN ;3U
Adder
8.792
274802UNIV PARK;5U
Adder
6.05
274826FISK ;BP
Adder
11.355
274800UNIV PARK;3U
Adder
6.045
972038AH1-567 GEN2
Adder
0.378
972228AH1-698 GEN2
Adder
3.84
274676JOLIET 29;8U
Adder
30.573
274729ELWOOD EC;1P
Adder
16.983
274730ELWOOD EC;6P
Adder
16.983
964991AG1-363 GEN
Solar/Wind Helper
5.557
316097T157 G90
Solar/Wind Helper
1.705
23750701CROSSCHOOL
Solar/Wind Helper
1.586
238148AE2-230_GEN2
Solar/Wind Helper
0.555
238127S14_GEN_2
Solar/Wind Helper
0.867
238118U2-030_1
Solar/Wind Helper
0.356
237080AD1-060 GEN
Solar/Wind Helper
0.367
237038AE2-054 C
Solar/Wind Helper
0.292
235062AE1-101 C1
Solar/Wind Helper
1.776
23779801AA1-109
Solar/Wind Helper
0.207
316006AB2-029 C
Solar/Wind Helper
0.13
223401AF1-299 GEN
Solar/Wind Helper
0.387
316045AC1-158 PL2
Solar/Wind Helper
4.618
316254AC1-120 GEN1
Solar/Wind Helper
1.184
237048AF1-022 C
Solar/Wind Helper
0.173
966131AG1-482 GEN
Solar/Wind Helper
0.079
233930AB2-032 GEN
Solar/Wind Helper
0.387
233915AB1-141 GEN
Solar/Wind Helper
0.511
232422X3-066 FULL
Solar/Wind Helper
0.116
233964AF2-378 GEN
Solar/Wind Helper
0.042
232426Y1-080 FULL
Solar/Wind Helper
0.039
233998TM1NIN_3.36
Solar/Wind Helper
0.266
232404W1-003 C
Solar/Wind Helper
0.516
232428Y3-058 C
Solar/Wind Helper
0.344
3147666LOUISA
Solar/Wind Helper
0.958
232434Z2-077 GEN
Solar/Wind Helper
0.129
233954AC2-188 GEN
Solar/Wind Helper
0.236
233950AC2-186 GEN
Solar/Wind Helper
0.118
233972AC1-094 C
Solar/Wind Helper
0.307
316192AB2-158 GEN
Solar/Wind Helper
1.608
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.232
228728W1-130C
Solar/Wind Helper
0.054
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219904AC1-010 C
Solar/Wind Helper
0.061
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.132
20720728JCB_W1-129
Solar/Wind Helper
0.057
207445AB1-138_GEN
Solar/Wind Helper
0.105
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20715228NPK_W1-113
Solar/Wind Helper
0.078
207454AA2-184 E
Solar/Wind Helper
0.311
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.497
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
207437AD2-070 GEN
Solar/Wind Helper
0.137
207518AF1-320_GEN
Solar/Wind Helper
1.568
20671928W4-073
Solar/Wind Helper
0.089
20675828AU_W4-064
Solar/Wind Helper
0.029
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20675928HOL_W4-097
Solar/Wind Helper
0.05
20674828DL_W4-046
Solar/Wind Helper
0.008
207484AF2-139 C O1
Solar/Wind Helper
0.084
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.136
20675128HRM_W1-127
Solar/Wind Helper
0.029
209116AE2-175 GEN
Solar/Wind Helper
1.768
945581AF1-223 GEN
Solar/Wind Harmer
0.763
CBM West 1LTFEXP_CBM-W1->PJM
CBM
146.579
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.544
MECLTFEXP_MEC->PJM
CLTF
15.979
SIGELTFEXP_SIGE->PJM
CLTF
0.506
LAGNLTFEXP_LAGN->PJM
CLTF
14.521
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.32
TVALTFEXP_TVA->PJM
CLTF
7.111
CBM West 2LTFEXP_CBM-W2->PJM
CBM
111.893
NYPJM->LTFIMP_NY
CLTF
4.554
LGEELTFEXP_LGEE->PJM
CLTF
6.753
WECLTFEXP_WEC->PJM
CLTF
3.866
AG2-052LTFEXP_AG2-052->PJM
LTF
0.243
AH1-155LTFEXP_AH1-155->PJM
LTF
0.364

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-008A_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-008A_SRT-SL
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:124.1 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4627.6
MW Contribution:6.64
Bus #Bus NameTypeMW Contribution
24318805MLG1
50/50
9.842
23559001PLEAS1
50/50
5.385
270051AF1-062 GEN
50/50
11.434
970153AG2-106 GEN
Solar/Wind Harmer
21.245
961921AG1-034 GEN
Solar/Wind Harmer
7.364
241955AC1-078 GEN
Solar/Wind Harmer
0.007
241974AD2-163_GEN2
Solar/Wind Harmer
0.006
942051AE2-217 GEN
Solar/Wind Harmer
14.169
24721905FLATG4
Adder
22.865
970605AG2-385 GEN
Solar/Wind Harmer
4.731
270391AF1-285 GEN3
Solar/Wind Harmer
0.518
253338AC1-165 GEN
Solar/Wind Harmer
0.003
253333AC1-068 GEN
Solar/Wind Harmer
0.012
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270273AD2-016 GEN
Solar/Wind Harmer
0.792
972173AH1-669 GEN
Solar/Wind Harmer
3.811
270512AE1-227 GEN2
Solar/Wind Harmer
1.904
270291AC1-194 GEN
Solar/Wind Harmer
5.884
253415AE1-040 GEN
Solar/Wind Harmer
0.003
970065AG2-057 GEN
Solar/Wind Harmer
0.735
253370AE2-315 SEC1
Adder
2.103
253371AE2-315 SEC2
Adder
1.989
970191AG2-125 GEN
Solar/Wind Harmer
1.876
253406AD2-031_GEN
Solar/Wind Harmer
0.543
270491AE1-102 GEN2
Solar/Wind Harmer
0.945
270377AD1-106 GEN
Solar/Wind Harmer
2.761
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.047
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
9.394
959331AF2-224 GEN
Solar/Wind Harmer
5.057
965021AG1-366 GEN
Solar/Wind Harmer
2.408
270588AE1-091_GEN
Solar/Wind Harmer
5.649
971191AH1-055 GEN
Solar/Wind Harmer
18.515
944531AF1-118 GEN
Solar/Wind Harmer
32.203
270043AE2-236 GEN
Solar/Wind Harmer
4.607
270258AD1-119 GEN
Solar/Wind Harmer
0.002
971617AH1-308 GEN
Solar/Wind Harmer
5.953
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
10.684
270404AC1-167 GEN
Solar/Wind Harmer
0.003
25196608WSDLE5
Adder
8.745
252510AF1-249 C
Solar/Wind Harmer
0.055
970031AG2-029 GEN
Solar/Wind Harmer
4.625
25194608D.CRK4
Adder
1.676
270222AC2-111 GEN
Solar/Wind Harmer
3.603
970513AG2-328 GEN
Solar/Wind Harmer
3.076
970517AG2-330 GEN
Solar/Wind Harmer
18.457
970349AG2-230 GEN
Solar/Wind Harmer
10.632
946031AF1-268 GEN
Solar/Wind Harmer
6.74
958821AF2-173 GEN
Solar/Wind Harmer
9.902
270004AE1-209 GEN
Solar/Wind Harmer
1.532
270437AC2-090 C
Solar/Wind Harmer
0.003
247643Z2-116 C
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.775
970291AG2-192 GEN
Solar/Wind Harmer
0.705
945111AF1-176 GEN
Solar/Wind Harmer
5.709
247642Z2-115 C
Solar/Wind Harmer
0.003
24642205MAYFLWER
Adder
0.641
24441205WTRV SLR C
Solar/Wind Harmer
0
25196008MFTGT1
Adder
1.353
972239AH1-704 GEN
50/50
2.78
962771AG1-126 GEN
Solar/Wind Harmer
33.269
270459AD2-067 GEN
Solar/Wind Harmer
0
270054AF2-122 C O1
Solar/Wind Harmer
0.007
961821AG1-024 GEN
Solar/Wind Harmer
4.91
270520AE2-214 GEN
Solar/Wind Harmer
0.013
270284AF1-227 GEN1
Solar/Wind Harmer
0.01
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
253383AE2-342_GEN
Solar/Wind Harmer
0.003
241973AD2-163_GEN1
Solar/Wind Harmer
0.006
945631AF1-228 GEN
Solar/Wind Harmer
0
943861AF1-054 GEN
Solar/Wind Harmer
3.02
943851AF1-053 GEN
Solar/Wind Harmer
2.092
270156DARBY CT1
Adder
10.05
270157DARBY CT2
Adder
10.026
270158DARBY CT3
Adder
9.866
270578AF1-285 GEN2
Solar/Wind Harmer
0.518
970689AG2-444 GEN
Solar/Wind Harmer
15.861
270432AC2-029 GEN
Solar/Wind Harmer
3.428
940611AE2-048 GEN
Solar/Wind Harmer
18.967
941391AE2-136 GEN
Solar/Wind Harmer
10.684
270302AB2-170 GEN
Solar/Wind Harmer
0.005
270317AD1-130_GEN
Solar/Wind Harmer
0.011
971653AH1-327 GEN
Solar/Wind Harmer
1.08
270269AC2-059
Solar/Wind Harmer
0.004
241972AD1-140 GEN
Solar/Wind Harmer
0.824
970179AG2-119 GEN
Solar/Wind Harmer
6.658
270340AC2-060 GEN
Solar/Wind Harmer
0.009
970879AG2-548 GEN
Solar/Wind Harmer
6.645
253372AE2-315 SEC3
Adder
1.989
253372AE2-315 SEC3
Adder
1.989
25306009OHH W.
Adder
3.018
253349AC2-067 GEN
Solar/Wind Harmer
2.296
253400AC2-068 GEN
Solar/Wind Harmer
0.923
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
0.92
965051AG1-369 GEN
Solar/Wind Harmer
3.609
971567AH1-282 GEN
Solar/Wind Harmer
10.843
247607V1-011 GEN
Solar/Wind Harmer
0.001
965041AG1-368 GEN
Solar/Wind Harmer
7.21
971989AH1-539 GEN
Solar/Wind Harmer
3.109
963791AG1-232 GEN
Solar/Wind Harmer
9.689
24729505KEY G4
Adder
6.671
270071AF1-092 GEN
Solar/Wind Harmer
13.737
270024AE2-089 GEN
Solar/Wind Harmer
0.008
971985AH1-537 GEN
Solar/Wind Harmer
2.123
965101AG1-375 GEN
Solar/Wind Harmer
7.135
270297AD1-101 GEN
Solar/Wind Harmer
0.002
270367AC2-061_GEN
Solar/Wind Harmer
0.006
971673AH1-337 GEN
Solar/Wind Harmer
4.631
971029AG2-637 GEN
Solar/Wind Harmer
10.686
270543AE2-219 C
Solar/Wind Harmer
0.004
252524AE2-267 GEN
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
9.002
25196308WSDLE2
Adder
8.924
25196208WSDLE1
Adder
8.902
25196708WSDLE6
Adder
8.879
25196508WSDLE4
Adder
8.656
945581AF1-223 GEN
Solar/Wind Harmer
0.001
971347AH1-153 GEN
Solar/Wind Harmer
10.632
971609AH1-304 GEN
Solar/Wind Harmer
1.157
270240V3-007_GEN2
Solar/Wind Harmer
0.002
970115AG2-085 GEN
Solar/Wind Harmer
2.826
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
270594AE1-207 GEN
Solar/Wind Harmer
7.898
971771AH1-392 GEN
Solar/Wind Harmer
7.046
970289AG2-191 GEN
Solar/Wind Harmer
1.339
971619AH1-309 GEN
Solar/Wind Harmer
3.169
971769AH1-391 GEN
Solar/Wind Harmer
7.844
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
25196108MFTGT2
Adder
1.54
25196108MFTGT2
Adder
1.43
270536AF1-215 GEN2
Solar/Wind Harmer
0.009
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
4.146
971549AH1-272 GEN
Solar/Wind Harmer
14.344
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
8.364
274776LINCOLN ;7U
Adder
8.364
274777LINCOLN ;8U
Adder
8.364
274814UNIV PK N;0U
Adder
4.998
274807UNIV PK N;3U
Adder
4.987
274805UNIV PK N;1U
Adder
4.965
274811UNIV PK N;7U
Adder
4.954
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
972037AH1-567 GEN1
Adder
0.181
960591AF2-350 GEN
Solar/Wind Harmer
6.884
274827FISK ;RP
Adder
7.655
972227AH1-698 GEN1
Adder
2.573
963841AG1-237 GEN
Solar/Wind Harmer
2.978
274687WILL CNTY;4U
Adder
27.495
274687WILL CNTY;4U
Adder
27.495
274675JOLIET 29;7U
Adder
30.175
274675JOLIET 29;7U
Adder
29.097
972163AH1-664 GEN
Solar/Wind Harmer
7.639
972165AH1-665 GEN
Solar/Wind Harmer
6.118
274731ELWOOD EC;2P
Adder
16.163
274733ELWOOD EC;3P
Adder
16.163
270119AB2-067 GEN1
50/50
6.869
270120AB2-067 GEN2
50/50
6.869
24318905MLG2
50/50
6.89
270471AD2-092_GEN
Solar/Wind Harmer
0.006
942861AE2-305 GEN
Solar/Wind Harmer
6.118
970077AG2-063 GEN
Solar/Wind Harmer
4.471
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
938701AE1-092 GEN
Solar/Wind Harmer
12.484
971655AH1-328 GEN
Solar/Wind Harmer
2.758
964601AG1-323 GEN
Solar/Wind Harmer
3.106
964601AG1-323 GEN
Solar/Wind Harmer
2.071
270518AE2-148 GEN
Solar/Wind Harmer
0.667
972269AH1-719 GEN
Adder
2.501
972159AH1-661 GEN
Adder
1.082
253378AE2-206_GEN
Solar/Wind Harmer
0.004
276820AF1-078_GEN
Solar/Wind Harmer
0.002
970329AG2-216 GEN
Solar/Wind Harmer
3.237
971199AH1-059 GEN
Solar/Wind Harmer
2.99
241960AC2-195 GEN
Solar/Wind Harmer
0.006
970935AG2-582 GEN
Adder
242.403
25326509SID D
Adder
1.4
971073AG2-665 GEN
Solar/Wind Harmer
6.645
25326109MON D
Adder
1.391
971201AH1-060 GEN
Solar/Wind Harmer
1.471
25322209TAIT E
Adder
10.262
25322209TAIT E
Adder
10.031
253370AE2-315 SEC1
Adder
2.103
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
246938BC-WTG3
Solar/Wind Harmer
0.263
246937BC-WTG2
Solar/Wind Harmer
0.295
971231AH1-075 GEN
Solar/Wind Harmer
0.833
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
970611AG2-400 GEN
Solar/Wind Harmer
7.225
970627AG2-408 GEN
Solar/Wind Harmer
2.167
270007AE1-245 C
Solar/Wind Harmer
0.002
970623AG2-406 GEN
Solar/Wind Harmer
1.309
962581AG1-107 GEN
Solar/Wind Harmer
0.001
25183208HLCRTG
Solar/Wind Harmer
0.011
944541AF1-119 GEN
Solar/Wind Harmer
0.479
960971AF2-388 GEN
Solar/Wind Harmer
4.192
942221AE2-234 GEN
Solar/Wind Harmer
0.036
252519AF1-045_GEN
Solar/Wind Harmer
6.204
252516AE2-318_GEN
Solar/Wind Harmer
5.503
970621AG2-405 GEN
Solar/Wind Harmer
1.305
247621Y3-024
Adder
0.246
970883AG2-550 GEN
Solar/Wind Harmer
7.123
970885AG2-551 GEN
Solar/Wind Harmer
2.374
270201AC2-176 GEN
Solar/Wind Harmer
0.001
25194408D.CRK1
Adder
7.711
25194508D.CRK3
Adder
1.442
964611AG1-324 GEN
Solar/Wind Harmer
0.534
252509AD1-136 GEN
Solar/Wind Harmer
0.036
970321AG2-212 GEN
Solar/Wind Harmer
3.076
270599AE1-208 GEN
Solar/Wind Harmer
6.495
270031AE2-169
Solar/Wind Harmer
3.897
270383AD1-128 GEN
Solar/Wind Harmer
0.004
270186AC1-089 GEN
Solar/Wind Harmer
0.004
247620Y3-023
Adder
0.466
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
970825AG2-519 GEN
Solar/Wind Harmer
7.834
960441AF2-335 GEN
Solar/Wind Harmer
7.065
270216AD2-079_GEN
Solar/Wind Harmer
0.001
971613AH1-306 GEN
Solar/Wind Harmer
3.385
24728805RICHG1
Adder
3.82
24728905RICHG2
Adder
3.82
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
14.072
961051AF2-396 GEN
Solar/Wind Harmer
9.381
270526AF1-158 GEN
Solar/Wind Harmer
0.009
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
8.77
965791AG1-447 GEN
Solar/Wind Harmer
6.431
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
970239AG2-162 GEN
Solar/Wind Harmer
1.73
274770LINCOLN ;1U
Adder
8.364
274771LINCOLN ;2U
Adder
8.364
274808UNIV PK N;4U
Adder
4.933
966841AG1-555 GEN
Solar/Wind Harmer
0.781
274803UNIV PARK;6U
Adder
5.755
274888KELLY CRK;1U
Solar/Wind Harmer
0.404
274887GEN-1.85
Solar/Wind Harmer
0.181
276843GEN-1.7
Solar/Wind Harmer
0.223
958011AF2-095 GEN
Solar/Wind Harmer
9.913
972259AH1-714 GEN
Adder
18.805
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
970241AG2-163 GEN
Solar/Wind Harmer
3.993
958481AF2-142 GEN
Solar/Wind Harmer
10.238
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.923
971573AH1-285 GEN
Solar/Wind Harmer
1.271
971677AH1-339 GEN
Solar/Wind Harmer
0.768
958491AF2-143 GEN
Solar/Wind Harmer
10.205
274879MINONK ;1U
Solar/Wind Harmer
0.287
238175AF1-290_GEN
Solar/Wind Helper
0.148
238169AE2-226 GEN1
Solar/Wind Helper
0.677
238170AE2-226 GEN2
Solar/Wind Helper
0.677
238120AE2-309 GEN
Solar/Wind Helper
0.487
235020AA1-095 C
Solar/Wind Helper
0.051
23777901MDS_W4-102
Solar/Wind Helper
0.171
23585401KL_K28_T16
Solar/Wind Helper
1.328
237034AC2-136 C
Solar/Wind Helper
0.219
237002AB1-128_GEN
Solar/Wind Helper
0.427
235063AE1-101 C2
Solar/Wind Helper
1.6
237001AB1-127_GEN
Solar/Wind Helper
0.426
23777801MSM_W1-116
Solar/Wind Helper
0.11
237025AB1-124 C
Solar/Wind Helper
0.159
237006AB1-125 GEN
Solar/Wind Helper
0.119
226929AD2-058 GEN
Solar/Wind Helper
0.096
205916AD1-020 GEN
Solar/Wind Helper
1.656
20390526W1-045 C
Solar/Wind Helper
0.338
208835TUHI V3-051
Solar/Wind Helper
0.023
208835TUHI V3-051
Solar/Wind Helper
0.023
233987AB2-037 GEN
Solar/Wind Helper
2.264
233933AB2-153 GEN
Solar/Wind Helper
0.225
232424Y1-079 C
Solar/Wind Helper
0.112
233944AB2-135 GEN
Solar/Wind Helper
0.569
233946AB2-136 GEN
Solar/Wind Helper
0.549
234036AF2-325 C
Solar/Wind Helper
0.041
233901CHERRYDALE C
Solar/Wind Helper
0.225
232408W1-005 C
Solar/Wind Helper
0.49
232410W1-006 C
Solar/Wind Helper
0.49
233939AC1-091 C
Solar/Wind Helper
0.338
233970AC1-092 C
Solar/Wind Helper
0.338
315651AD1-115 GEN
Solar/Wind Helper
0.76
316447AC1-158 HLD
Solar/Wind Helper
2.756
230433AD2-135 GEN
Solar/Wind Helper
0.016
230407AD2-065 C
Solar/Wind Helper
0.039
219921AF1-264
Solar/Wind Helper
0.049
219615MILLCREEK C
Solar/Wind Helper
0.026
270356AE2-297 GEN
Solar/Wind Harmer
0.009
970217AG2-149 GEN
Solar/Wind Harmer
6.066
247604X1-042
Adder
0.418
270535AF1-215 GEN1
Solar/Wind Harmer
0.009
964401AG1-302 GEN
Solar/Wind Harmer
0.001
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.935
970243AG2-164 GEN
Solar/Wind Harmer
4.047
970519AG2-331 GEN
Solar/Wind Harmer
17.988
970699AG2-449 GEN
Solar/Wind Harmer
1.73
274752CRETE EC ;2U
Adder
8.172
274753CRETE EC ;3U
Adder
8.172
274772LINCOLN ;3U
Adder
8.364
274724RIVER EC ;11
Adder
17.549
958171AF2-111 GEN
Solar/Wind Harmer
17.278
274802UNIV PARK;5U
Adder
5.755
276806AD2-047 C O1
Solar/Wind Harmer
3.901
970941AG2-585 GEN
Solar/Wind Harmer
8.605
274826FISK ;BP
Adder
10.802
24728705AND G3
Adder
7.914
24728505AND G1
Adder
3.784
274800UNIV PARK;3U
Adder
5.751
972038AH1-567 GEN2
Adder
0.36
972228AH1-698 GEN2
Adder
3.654
972167AH1-666 GEN
Solar/Wind Harmer
5.505
276897AD1-100 C
Solar/Wind Harmer
0.009
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
22.464
274676JOLIET 29;8U
Adder
29.097
274729ELWOOD EC;1P
Adder
16.163
274730ELWOOD EC;6P
Adder
13.491
276893AG1-478 C
Solar/Wind Harmer
0.272
270541AE2-072 C
Solar/Wind Harmer
0.009
943121AE2-341 GEN
Solar/Wind Harmer
11.459
943591AF1-030 GEN
Solar/Wind Harmer
7.62
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
276805AD2-038 GEN
Solar/Wind Harmer
0.002
964991AG1-363 GEN
Solar/Wind Helper
4.969
316097T157 G90
Solar/Wind Helper
1.455
23750701CROSSCHOOL
Solar/Wind Helper
1.397
238148AE2-230_GEN2
Solar/Wind Helper
0.48
238127S14_GEN_2
Solar/Wind Helper
0.766
238118U2-030_1
Solar/Wind Helper
0.314
237080AD1-060 GEN
Solar/Wind Helper
0.33
237038AE2-054 C
Solar/Wind Helper
0.262
235062AE1-101 C1
Solar/Wind Helper
1.6
23779801AA1-109
Solar/Wind Helper
0.187
223401AF1-299 GEN
Solar/Wind Helper
0.355
316006AB2-029 C
Solar/Wind Helper
0.113
966131AG1-482 GEN
Solar/Wind Helper
0.132
237048AF1-022 C
Solar/Wind Helper
0.159
233930AB2-032 GEN
Solar/Wind Helper
0.368
233915AB1-141 GEN
Solar/Wind Helper
0.486
232422X3-066 FULL
Solar/Wind Helper
0.11
232426Y1-080 FULL
Solar/Wind Helper
0.038
233964AF2-378 GEN
Solar/Wind Helper
0.04
233998TM1NIN_3.36
Solar/Wind Helper
0.253
232404W1-003 C
Solar/Wind Helper
0.49
232428Y3-058 C
Solar/Wind Helper
0.327
232434Z2-077 GEN
Solar/Wind Helper
0.123
233954AC2-188 GEN
Solar/Wind Helper
0.225
233950AC2-186 GEN
Solar/Wind Helper
0.112
233972AC1-094 C
Solar/Wind Helper
0.292
316045AC1-158 PL2
Solar/Wind Helper
4.009
230511AF1-262
Solar/Wind Helper
0.014
230434AG1-499 GEN
Solar/Wind Helper
0.222
228728W1-130C
Solar/Wind Helper
0.052
219258KINSLEYDEP C
Solar/Wind Helper
0.074
219904AC1-010 C
Solar/Wind Helper
0.058
218660EHAMPSOLAR C
Solar/Wind Helper
0.032
219907AC1-030 C
Solar/Wind Helper
0.033
219686LUMSOLAR_N C
Solar/Wind Helper
0.038
219304NAMERICA C
Solar/Wind Helper
0.127
316254AC1-120 GEN1
Solar/Wind Helper
1.026
20720728JCB_W1-129
Solar/Wind Helper
0.055
207445AB1-138_GEN
Solar/Wind Helper
0.101
963711AG1-223 GEN
Solar/Wind Helper
0.062
20714828MDF_W3-079
Solar/Wind Helper
0.126
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.299
20715228NPK_W1-113
Solar/Wind Helper
0.075
270166AC1-044 GEN3
50/50
6.869
23559101PLEAS2
50/50
5.385
270122AB2-093 CT
50/50
3.689
962761AG1-125 GEN
Solar/Wind Harmer
33.269
970149AG2-104 GEN
Solar/Wind Harmer
35.932
970155AG2-107 GEN
Solar/Wind Harmer
21.245
270349AD2-093_GEN
Solar/Wind Harmer
0.006
24721705FLATG2
Adder
22.865
270159DARBY CT4
Adder
9.89
970593AG2-378 GEN
Solar/Wind Harmer
1.75
270223U2-072_GEN1
Solar/Wind Harmer
0.001
253343AC1-166 GEN
Solar/Wind Harmer
0.003
253325AC1-069 GEN
Solar/Wind Harmer
0.012
270462AD2-086
Solar/Wind Harmer
0.016
971995AH1-542 GEN
Solar/Wind Harmer
2.81
270263AC1-001 GEN
Solar/Wind Harmer
0.758
270510AE1-227 GEN1
Solar/Wind Harmer
1.904
241813AF1-122_GEN
Solar/Wind Harmer
3.294
25326309TAIT D
Adder
1.153
960071AF2-298 GEN
Solar/Wind Harmer
3.651
253370AE2-315 SEC1
Adder
2.103
253371AE2-315 SEC2
Adder
1.989
927014AC1-188 GEN
Solar/Wind Harmer
0.004
246936BC-WTG1
Solar/Wind Harmer
0.295
270489AE1-102 GEN1
Solar/Wind Harmer
0.945
965421AG1-410 GEN
Solar/Wind Harmer
21.788
247521TR3_G114
Solar/Wind Harmer
0.263
270246TR4_N_V150
Solar/Wind Harmer
0.047
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.226
965011AG1-365 GEN
Solar/Wind Harmer
7.225
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
24695305TIMB G C
Solar/Wind Harmer
0.002
965651AG1-433 GEN
Solar/Wind Harmer
2.096
958861AF2-177 GEN
Solar/Wind Harmer
3.092
247536S-71 GEN
Solar/Wind Harmer
0.287
945371AF1-202 GEN
Solar/Wind Harmer
0.001
25194608D.CRK4
Adder
1.676
270063AE2-323 C
Solar/Wind Harmer
0.006
252507AC2-088 GEN
Solar/Wind Harmer
0.323
970245AG2-165 GEN
Solar/Wind Harmer
3.076
944231AF1-091 GEN
Solar/Wind Harmer
1.885
270005AE1-210 C O1
Solar/Wind Harmer
1.532
965031AG1-367 GEN
Solar/Wind Harmer
7.073
970947AG2-589 GEN
Solar/Wind Harmer
0.236
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.183
970825AG2-519 GEN
Solar/Wind Harmer
2.509
24639705ELKHART HY
Adder
0.155
25196808ZIMRHP
Adder
76.799
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
270032AE2-172
Solar/Wind Harmer
4.701
970291AG2-192 GEN
Solar/Wind Harmer
0.916
945111AF1-176 GEN
Solar/Wind Harmer
12.568
270505AE1-170 C O1
Solar/Wind Harmer
7.393
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.67
247522W1-056 GEN
Solar/Wind Harmer
0.001
276903AD2-071 C
Solar/Wind Harmer
7.842
25196008MFTGT1
Adder
1.397
970773AG2-487 GEN
Solar/Wind Harmer
1.237
970373AG2-245 GEN
Solar/Wind Harmer
14.699
970515AG2-329 GEN
Solar/Wind Harmer
18.197
270055AF2-134 C O1
Solar/Wind Harmer
0.005
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.071
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.706
24791305MDL-5G
Solar/Wind Harmer
0.001
970333AG2-219 GEN
Solar/Wind Harmer
4.947
274751CRETE EC ;1U
Adder
8.172
274754CRETE EC ;4U
Adder
8.172
274773LINCOLN ;4U
Adder
8.364
274774LINCOLN ;5U
Adder
8.364
274723RIVER EC ;12
Adder
17.756
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.954
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
276776AD2-060 GEN
Solar/Wind Harmer
0.719
24728605AND G2
Adder
3.784
274801UNIV PARK;4U
Adder
5.751
941551AE2-152 GEN
Solar/Wind Harmer
0.001
945681AF1-233 GEN
Solar/Wind Harmer
12.962
274676JOLIET 29;8U
Adder
30.175
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
963741AG1-226 GEN
Solar/Wind Harmer
16.202
939401AE1-172 GEN
Solar/Wind Harmer
5.109
276691AA1-018 GEN1
Solar/Wind Harmer
0.827
276901AD2-066 C O1
Solar/Wind Harmer
0.007
316095T157 G97
Solar/Wind Helper
1.455
23583801GRNGAP
Solar/Wind Helper
5.418
238108AE1-109 GEN1
Solar/Wind Helper
0.106
238185AF2-356 C
Solar/Wind Helper
2.425
238147AE2-230_GEN1
Solar/Wind Helper
0.478
238149AF1-291A_GEN
Solar/Wind Helper
0.137
235531U2-073 GEN
Solar/Wind Helper
3.034
235054AD2-180 GEN
Solar/Wind Helper
1.839
237061AD1-155 GEN
Solar/Wind Helper
0.051
238117U2-030
Solar/Wind Helper
0.314
238221AF1-254 C O1
Solar/Wind Helper
0.265
235067AD1-061 GEN
Solar/Wind Helper
0.478
237030AB1-096 C
Solar/Wind Helper
0.068
3141196NOKESVL
Solar/Wind Helper
0.999
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.335
223402AF1-300 C
Solar/Wind Helper
0.355
23751201ROTHROCK
Solar/Wind Helper
0.694
23562501BACKB
Solar/Wind Helper
0.842
205917AD1-020 ES
Solar/Wind Helper
0.356
233982AB2-133 GEN
Solar/Wind Helper
0.346
233918AB1-142 GEN
Solar/Wind Helper
0.486
233994AC2-023 GEN
Solar/Wind Helper
0.929
233996TM1833_GEN
Solar/Wind Helper
0.253
233997TMININ_4.2
Solar/Wind Helper
0.253
232406W1-004 FULL
Solar/Wind Helper
0.49
233940AF2-379 C
Solar/Wind Helper
0.06
234015AF2-250 C
Solar/Wind Helper
0.037
233952AC2-187 GEN
Solar/Wind Helper
0.225
233971AC1-093 C
Solar/Wind Helper
0.346
316044AC1-158 PL1
Solar/Wind Helper
1.252
316450AC1-158 RIC
Solar/Wind Helper
0.334
230430AE1-229_GEN
Solar/Wind Helper
3.26
230415AB2-049 C
Solar/Wind Helper
0.029
228729W2-030 C
Solar/Wind Helper
0.107
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.053
219912AD2-042 GEN
Solar/Wind Helper
0.145
219291REEVESSOUT C
Solar/Wind Helper
0.011
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.111
316170AC1-121 GEN2
Solar/Wind Helper
0.342
959561AF2-247 GEN
Solar/Wind Helper
0.02
20720828JCB_W4-025
Solar/Wind Helper
0.061
20716028EGP_W2-019
Solar/Wind Helper
0.018
20715028HAN_X4-015
Solar/Wind Helper
0.055
219276PARKLANDSO C
Solar/Wind Helper
0.086
20714528FRN_Y2-051
Solar/Wind Helper
0.055
20720528MAN_W1-024
Solar/Wind Helper
0.027
971997AH1-543 GEN
Solar/Wind Harmer
1.86
963401AG1-189 GEN
Solar/Wind Helper
0.054
963391AG1-188 GEN
Solar/Wind Helper
0.079
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.183
274735ELWOOD EC;4P
Adder
16.163
274728ELWOOD EC;5P
Adder
16.163
970833AG2-524 GEN
Solar/Wind Harmer
7.542
970833AG2-524 GEN
Solar/Wind Harmer
5.028
945641AF1-229 GEN
Solar/Wind Harmer
0.001
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
276868AE1-113 GEN
Solar/Wind Harmer
1.363
276882AE2-255 GEN
Solar/Wind Harmer
0.794
238109AE1-109 GEN2
Solar/Wind Helper
0.106
238110AE1-109 GEN3
Solar/Wind Helper
0.106
238152AF2-075_GEN
Solar/Wind Helper
0.683
23546401DTGZ2-030
Solar/Wind Helper
0.086
238208AF1-136 C
Solar/Wind Helper
0.211
238126S14_GEN_1
Solar/Wind Helper
0.766
237085AD2-009_GEN
Solar/Wind Helper
1.588
3138216PACIFIC
Solar/Wind Helper
0.043
316411AF1-147_GEN1
Solar/Wind Helper
0.86
316415AF1-147_GEN2
Solar/Wind Helper
0.86
959381AF2-229 GEN
Solar/Wind Helper
0.345
23750501ELLIOTTS
Solar/Wind Helper
0.571
3141426STAFORD
Solar/Wind Helper
0.051
960921AF2-383 GEN
Solar/Wind Helper
0.352
205943AE1-185 GEN
Solar/Wind Helper
0.492
205956AE1-196_GEN
Solar/Wind Helper
0.492
205932AD2-116_GEN
Solar/Wind Helper
0.492
233935AB2-179 C
Solar/Wind Helper
1.227
232436AB1-176 C
Solar/Wind Helper
0.043
233923SMA
Solar/Wind Helper
0.927
233990AG1-397 GEN
Solar/Wind Helper
0.261
234033AF1-007_GEN
Solar/Wind Helper
6.787
232432Z2-076 GEN
Solar/Wind Helper
0.065
964001AG1-254 GEN
Solar/Wind Helper
0.924
228754AB1-001 C
Solar/Wind Helper
0.025
227927V4-067C
Solar/Wind Helper
0.01
219914AD2-027 C
Solar/Wind Helper
0.111
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.038
219607WPEMNERT C
Solar/Wind Helper
0.077
214067T20SOLAR
Solar/Wind Helper
0.011
203975AE1-071-GEN
Solar/Wind Helper
2.41
20715728PEM_W1-119
Solar/Wind Helper
0.093
20715828PEM_W1-120
Solar/Wind Helper
0.093
207459AE1-142 C O1
Solar/Wind Helper
0.28
316164AC1-076 GEN
Solar/Wind Helper
1.062
219620RIDERU C
Solar/Wind Helper
0.001
CBM West 1LTFEXP_CBM-W1->PJM
CBM
137.982
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.984
MECLTFEXP_MEC->PJM
CLTF
15.319
SIGELTFEXP_SIGE->PJM
CLTF
0.486
LAGNLTFEXP_LAGN->PJM
CLTF
14.268
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.432
TVALTFEXP_TVA->PJM
CLTF
7.011
CPLELTFEXP_CPLE->PJM
CLTF
0.567
CBM West 2LTFEXP_CBM-W2->PJM
CBM
108.576
NYPJM->LTFIMP_NY
CLTF
4.628
LGEELTFEXP_LGEE->PJM
CLTF
6.497
WECLTFEXP_WEC->PJM
CLTF
3.686
AG2-052LTFEXP_AG2-052->PJM
LTF
0.231
AH1-155LTFEXP_AH1-155->PJM
LTF
0.346

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AP_P1-3_MP-765-501T_SRT-A


Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-501T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:121.06 %
Rating:3393.4 MVA
Rating Type:B
MVA to Mitigate:4107.97
MW Contribution:5.76
Bus #Bus NameTypeMW Contribution
970823AG2-518 GEN
50/50
8.384
247619Y1-049
50/50
0.913
24684705SMG5
50/50
0.856
970481AG2-311 GEN
50/50
11.937
24728405LEESVG
50/50
0.295
24416005BYLLESBY
50/50
0.031
3151561HALLBR1
50/50
0.57
970563AG2-360 GEN
50/50
45.829
962751AG1-124 GEN
Solar/Wind Harmer
12.893
958121AF2-106 GEN
Solar/Wind Harmer
0.001
270173AC1-122 GEN
Solar/Wind Harmer
0.677
971331AH1-145 GEN
Solar/Wind Harmer
18.361
943031AE2-326 GEN
Solar/Wind Harmer
6.784
3147312GRETNA
Solar/Wind Harmer
0.186
3146802CHATHAM
Solar/Wind Harmer
0.175
941801AE2-185 GEN
Solar/Wind Harmer
7.452
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
3147123OTTER R
Solar/Wind Harmer
0.13
270346AE1-212 GEN
Solar/Wind Harmer
9.542
270030AE2-140 GEN
Solar/Wind Harmer
21.578
960911AF2-382 GEN
Solar/Wind Harmer
7.638
270016AE1-250 BESS
Solar/Wind Harmer
0.006
970913AG2-568 GEN
Solar/Wind Harmer
7.677
971461AH1-227 GEN
Solar/Wind Harmer
4.886
970479AG2-310 GEN
50/50
20.255
270205AE1-176
50/50
0.006
24288905REUSENS
50/50
0.057
24684605SMG4
50/50
2.239
966251AG1-494 GEN
50/50
4.388
24728405LEESVG
50/50
0.297
24415905BUCK
50/50
0.034
971367AH1-164 GEN
Solar/Wind Harmer
4.886
971329AH1-144 GEN
Solar/Wind Harmer
11.568
3147312GRETNA
Solar/Wind Harmer
0.047
941821AE2-187 GEN
Solar/Wind Harmer
7.452
270197AD1-017 GEN1
Solar/Wind Harmer
1.429
270336AE1-100 GEN
Solar/Wind Harmer
0.006
943811AF1-049 GEN
Solar/Wind Harmer
-0.002
24728305BUCHG2
Adder
6.75
270018AE2-047 C O1
Solar/Wind Harmer
0.004
958131AF2-107 GEN
Solar/Wind Harmer
5.339
24735205WLF2G2
Adder
8.023
971687AH1-348 GEN
Solar/Wind Harmer
0.948
971403AH1-188 GEN
Solar/Wind Harmer
13.153
24723205RIVRG3
Adder
22.954
971315AH1-136 GEN
Solar/Wind Harmer
1.695
24686105CER G3
Adder
9.887
24686505CER G6
Adder
9.874
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
24721705FLATG2
Adder
21.686
970947AG2-589 GEN
Solar/Wind Harmer
0.249
970273AG2-179 GEN
Solar/Wind Harmer
2.581
971821AH1-427 GEN
Solar/Wind Harmer
7.218
964901AG1-354 GEN
Solar/Wind Harmer
10.814
962241AG1-070 GEN
Solar/Wind Harmer
3.92
970223AG2-152 GEN
Solar/Wind Harmer
12.358
270053AF1-130 C
Solar/Wind Harmer
2.047
972103AH1-617 GEN
Solar/Wind Harmer
18.024
24686205CER G4
Adder
9.835
24686405CER G5
Adder
9.796
972273AH1-721 GEN
Adder
89.316
24721905FLATG4
Adder
21.686
970273AG2-179 GEN
Solar/Wind Harmer
4.425
339250AF1-203 GEN
Solar/Wind Harmer
0.001
971155AH1-034 GEN
Solar/Wind Harmer
8.427
962251AG1-071 GEN
Solar/Wind Harmer
4.496
966571AG1-526 GEN
Solar/Wind Harmer
15.967
970093AG2-073 GEN
Solar/Wind Harmer
7.166
960741AF2-365 GEN
Solar/Wind Harmer
3.563
3429391JKCT 9G
Adder
8.402
971191AH1-055 GEN
Solar/Wind Harmer
18.055
972167AH1-666 GEN
Solar/Wind Harmer
5.419
958171AF2-111 GEN
Solar/Wind Harmer
16.681
970243AG2-164 GEN
Solar/Wind Harmer
3.891
970519AG2-331 GEN
Solar/Wind Harmer
17.292
970699AG2-449 GEN
Solar/Wind Harmer
1.663
25196008MFTGT1
Adder
1.252
252510AF1-249 C
Solar/Wind Harmer
0.05
25194608D.CRK4
Adder
1.508
25196608WSDLE5
Adder
7.849
970193AG2-126 GEN
Solar/Wind Harmer
9.55
942481AE2-261 GEN
Solar/Wind Harmer
18.997
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
8.231
24728705AND G3
Adder
7.277
24728505AND G1
Adder
3.48
276621W2-048 GEN
Solar/Wind Harmer
0.318
276838X2-022 GEN2
Solar/Wind Harmer
0.355
276686W4-005 GEN3
Solar/Wind Harmer
0.001
276668AB2-070 GEN1
Solar/Wind Harmer
0.229
971993AH1-541 GEN
Solar/Wind Harmer
2.905
270356AE2-297 GEN
Solar/Wind Harmer
0.008
253406AD2-031_GEN
Solar/Wind Harmer
0.467
270222AC2-111 GEN
Solar/Wind Harmer
3.158
965931AG1-462 GEN
Solar/Wind Harmer
15.879
270291AC1-194 GEN
Solar/Wind Harmer
4.924
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
965091AG1-374 GEN
Solar/Wind Harmer
18.654
959611AF2-252 GEN
Solar/Wind Harmer
2.073
942111AE2-223 GEN
Solar/Wind Harmer
2.013
274878BISHOP HL;2U
Solar/Wind Harmer
0.208
276157O29GEN1
Solar/Wind Harmer
0.999
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
8.222
274767LEE CO EC;8U
Adder
8.125
270437AC2-090 C
Solar/Wind Harmer
0.003
970571AG2-364 GEN
Solar/Wind Harmer
12.296
253415AE1-040 GEN
Solar/Wind Harmer
0.002
972236AH1-702 GEN2
Adder
1.93
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.144
959091AF2-200 GEN
Solar/Wind Harmer
12.273
276889AE2-281 GEN
Solar/Wind Harmer
0.001
274855GSG-6 ;RU
Solar/Wind Harmer
0.225
274850MENDOTA H;RU
Solar/Wind Harmer
0.072
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.11
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.654
247642Z2-115 C
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
0.673
970291AG2-192 GEN
Solar/Wind Harmer
0.612
274872LEEDK;1U
Solar/Wind Harmer
0.224
958821AF2-173 GEN
Solar/Wind Harmer
8.556
270004AE1-209 GEN
Solar/Wind Harmer
1.324
276805AD2-038 GEN
Solar/Wind Harmer
0.002
274682WAUKEGAN ;7U
Adder
15.703
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
946031AF1-268 GEN
Solar/Wind Harmer
5.79
943121AE2-341 GEN
Solar/Wind Harmer
10.192
943591AF1-030 GEN
Solar/Wind Harmer
6.778
274729ELWOOD EC;1P
Adder
13.481
3147983MERCK5
Solar/Wind Helper
0.198
316192AB2-158 GEN
Solar/Wind Helper
1.838
3147666LOUISA
Solar/Wind Helper
1.088
316254AC1-120 GEN1
Solar/Wind Helper
1.159
316097T157 G90
Solar/Wind Helper
1.125
238148AE2-230_GEN2
Solar/Wind Helper
0.423
316336AC2-165 C
Solar/Wind Helper
1.285
316006AB2-029 C
Solar/Wind Helper
0.112
316045AC1-158 PL2
Solar/Wind Helper
4.023
24290605CLAY-1
50/50
0.255
24290605CLAY-1
50/50
0.255
24290705CLAY-2
50/50
0.255
24290705CLAY-2
50/50
0.255
24684405SMG2
50/50
2.224
24684505SMG3
50/50
1.376
24684305SMG1
50/50
0.806
270583AD2-179 GEN
Solar/Wind Harmer
14.457
971277AH1-098 GEN
Solar/Wind Harmer
5.177
316217AC1-145 GEN
Solar/Wind Harmer
0.003
316197AC1-042 GEN
Solar/Wind Harmer
0.002
942671AE2-283 GEN
Solar/Wind Harmer
5.796
24728205BUCHG1
Adder
6.75
270013AE1-250 PV
Solar/Wind Harmer
0.006
971225AH1-072 GEN
Solar/Wind Harmer
1.905
971227AH1-073 GEN
Solar/Wind Harmer
1.905
944971AF1-162 GEN
Solar/Wind Harmer
9.068
24723005RIVRG1
Adder
22.954
24723105RIVRG2
Adder
22.954
24685805CER G1
Adder
9.822
24685905CER G2
Adder
9.822
942751AE2-291 GEN
Solar/Wind Harmer
7.887
966021AG1-471 GEN
Solar/Wind Harmer
4.013
971485AH1-239 GEN
Solar/Wind Harmer
5.928
960161AF2-307 GEN
Solar/Wind Harmer
4.775
339255AE2-071 GEN
Solar/Wind Harmer
-0.119
964781AG1-341 GEN
Solar/Wind Harmer
7.653
971081AG2-670 GEN
Solar/Wind Harmer
5.396
942891AE2-308 GEN
Solar/Wind Harmer
7.099
970653AG2-424 GEN
Solar/Wind Harmer
3.405
970653AG2-424 GEN
Solar/Wind Harmer
1.764
964571AG1-320 GEN
Solar/Wind Harmer
6.361
971125AH1-004 GEN
Solar/Wind Harmer
2.777
970107AG2-081 GEN
Solar/Wind Harmer
2.083
972043AH1-570 GEN
Solar/Wind Harmer
1.796
972045AH1-571 GEN
Solar/Wind Harmer
1.439
339221AD2-048_GEN
Solar/Wind Harmer
0.004
970235AG2-159 GEN
Solar/Wind Harmer
4.126
970235AG2-159 GEN
Solar/Wind Harmer
2.367
270186AC1-089 GEN
Solar/Wind Harmer
0.004
970239AG2-162 GEN
Solar/Wind Harmer
1.663
962581AG1-107 GEN
Solar/Wind Harmer
0.001
270444AC2-157 GEN1
Solar/Wind Harmer
0.003
971587AH1-292 GEN
Solar/Wind Harmer
4.8
252509AD1-136 GEN
Solar/Wind Harmer
0.033
25183208HLCRTG
Solar/Wind Harmer
0.01
252519AF1-045_GEN
Solar/Wind Harmer
5.589
252516AE2-318_GEN
Solar/Wind Harmer
4.958
25194408D.CRK1
Adder
6.938
25194508D.CRK3
Adder
1.297
971073AG2-665 GEN
Solar/Wind Harmer
5.761
945391AF1-204 GEN
Solar/Wind Harmer
6.765
276916AD2-100_GEN
Solar/Wind Harmer
13.364
276911AD2-131_GEN
Solar/Wind Harmer
0.88
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
970241AG2-163 GEN
Solar/Wind Harmer
3.651
24728805RICHG1
Adder
3.384
24728905RICHG2
Adder
3.384
253394AE2-221_GEN
Solar/Wind Harmer
0.008
253398AE2-221_GEN2
Solar/Wind Harmer
0.008
960251AF2-316 GEN
Solar/Wind Harmer
8.583
960201AF2-311 GEN
Solar/Wind Harmer
5.708
960611AF2-352 GEN
Solar/Wind Harmer
2.073
966841AG1-555 GEN
Solar/Wind Harmer
0.701
276782AC1-033 GEN
Solar/Wind Harmer
0.001
276741O09 GEN1
Solar/Wind Harmer
0.22
276708O09 GEN2
Solar/Wind Harmer
0.22
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.243
276646AC1-214 GEN2
Solar/Wind Harmer
0.243
972267AH1-718 GEN
Adder
3.688
276603SUBLETTE C
Solar/Wind Harmer
0
274764LEE CO EC;5U
Adder
8.241
274765LEE CO EC;6U
Adder
8.241
274762LEE CO EC;3U
Adder
8.222
274763LEE CO EC;4U
Adder
8.144
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
938861AE1-114 GEN
Solar/Wind Harmer
3.491
274856ECOGROVE ;U1
Solar/Wind Harmer
0.145
276611AD2-172 GEN
Solar/Wind Harmer
0.002
270383AD1-128 GEN
Solar/Wind Harmer
0.004
971341AH1-150 GEN
Solar/Wind Harmer
12.273
971343AH1-151 GEN
Solar/Wind Harmer
12.273
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
971333AH1-146 GEN
Solar/Wind Harmer
12.256
971335AH1-147 GEN
Solar/Wind Harmer
12.256
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
942991AE2-321 GEN
Solar/Wind Harmer
6.834
971613AH1-306 GEN
Solar/Wind Harmer
2.937
274879MINONK ;1U
Solar/Wind Harmer
0.258
970921AG2-575 GEN
Solar/Wind Harmer
6.111
970921AG2-575 GEN
Solar/Wind Harmer
2.037
962691AG1-118 GEN
Solar/Wind Harmer
18.322
958491AF2-143 GEN
Solar/Wind Harmer
9.158
960441AF2-335 GEN
Solar/Wind Harmer
6.106
970825AG2-519 GEN
Solar/Wind Harmer
6.767
274683WAUKEGAN ;8U
Adder
18.419
274683WAUKEGAN ;8U
Adder
15.526
274696ROCKY RD ;4P
Adder
9.957
274695ROCKY RD ;2P
Adder
9.727
274693ROCKY RD ;1P
Adder
9.632
274697ROCKY RD ;3P
Adder
2.642
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.824
958481AF2-142 GEN
Solar/Wind Harmer
9.131
971573AH1-285 GEN
Solar/Wind Harmer
1.134
3132123MT JACKSON
Solar/Wind Helper
1.389
315821AE2-092 GEN
Solar/Wind Helper
3.216
966001AG1-469 GEN
Solar/Wind Helper
0.32
315651AD1-115 GEN
Solar/Wind Helper
0.837
966871AG1-558 GEN
Solar/Wind Helper
0.306
316447AC1-158 HLD
Solar/Wind Helper
2.766
316468AD1-105 GEN
Solar/Wind Helper
1.124
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
3429241JKCT 3G
Adder
12.029
3429421JKCT 10G
Adder
8.402
971565AH1-281 GEN
Solar/Wind Harmer
1.396
339216AC1-074 GEN
Solar/Wind Harmer
0.187
945681AF1-233 GEN
Solar/Wind Harmer
12.782
927014AC1-188 GEN
Solar/Wind Harmer
0.004
970091AG2-072 GEN
Adder
74.012
970333AG2-219 GEN
Solar/Wind Harmer
4.755
270445AC2-157 GEN2
Solar/Wind Harmer
0.003
25196808ZIMRHP
Adder
70.616
252507AC2-088 GEN
Solar/Wind Harmer
0.295
25196008MFTGT1
Adder
1.293
25194608D.CRK4
Adder
1.508
965911AG1-460 GEN
Solar/Wind Harmer
1.271
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.331
24728605AND G2
Adder
3.48
276615X2-022 GEN
Solar/Wind Harmer
0.066
963831AG1-236 GEN
Solar/Wind Harmer
2.455
274880W4-005 GEN4
Solar/Wind Harmer
0.001
970773AG2-487 GEN
Solar/Wind Harmer
1.107
963741AG1-226 GEN
Solar/Wind Harmer
14.811
972175AH1-670 GEN
Solar/Wind Harmer
5.171
274854TWINGROVE;U2
Solar/Wind Harmer
0.003
276726Z2-087_GEN
Solar/Wind Harmer
0.002
939741AE1-205 GEN
Solar/Wind Harmer
8.673
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.002
274877BISHOP HL;1U
Solar/Wind Harmer
0.208
276158O29GEN2
Solar/Wind Harmer
0.001
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
8.222
274766LEE CO EC;7U
Adder
8.125
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.519
276903AD2-071 C
Solar/Wind Harmer
6.874
971475AH1-234 GEN
Solar/Wind Harmer
2.986
970819AG2-516 GEN
Solar/Wind Harmer
7.379
970569AG2-363 GEN
Solar/Wind Harmer
18.444
972235AH1-702 GEN1
Adder
2.22
24791305MDL-5G
Solar/Wind Harmer
0.001
274822ROCKFORD ;11
Adder
17.275
957471AF2-041 GEN
Solar/Wind Harmer
18.409
959081AF2-199 GEN
Solar/Wind Harmer
6.136
971067AG2-660 GEN
Solar/Wind Harmer
2.045
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
276861AD2-134 GEN
Solar/Wind Harmer
0.11
970291AG2-192 GEN
Solar/Wind Harmer
0.796
971997AH1-543 GEN
Solar/Wind Harmer
3.211
270032AE2-172
Solar/Wind Harmer
4.079
270263AC1-001 GEN
Solar/Wind Harmer
0.614
274872LEEDK;1U
Solar/Wind Harmer
0.004
270005AE1-210 C O1
Solar/Wind Harmer
1.324
965031AG1-367 GEN
Solar/Wind Harmer
6.111
962781AG1-127 GEN
Solar/Wind Harmer
5.815
276901AD2-066 C O1
Solar/Wind Harmer
0.006
939401AE1-172 GEN
Solar/Wind Harmer
4.568
970825AG2-519 GEN
Solar/Wind Harmer
2.167
274828WAUKEGAN ;BP
Adder
9.655
274682WAUKEGAN ;7U
Adder
15.703
276691AA1-018 GEN1
Solar/Wind Harmer
0.737
274745AC1-111 GEN9
Adder
4.87
315616AA1-038_C
Solar/Wind Helper
3.293
3148013FISHERV
Solar/Wind Helper
0.523
316499AE2-029_GEN
Solar/Wind Helper
1.725
3132273ORANGE
Solar/Wind Helper
0.056
3147666LOUISA
Solar/Wind Helper
0.625
237061AD1-155 GEN
Solar/Wind Helper
0.05
316170AC1-121 GEN2
Solar/Wind Helper
0.386
23583801GRNGAP
Solar/Wind Helper
4.287
316095T157 G97
Solar/Wind Helper
1.125
238147AE2-230_GEN1
Solar/Wind Helper
0.421
238149AF1-291A_GEN
Solar/Wind Helper
0.12
316313AB2-026
Solar/Wind Helper
0.354
316258AE1-075 C
Solar/Wind Helper
0.319
316405AF2-144 C
Solar/Wind Helper
0.265
966881AG1-559 GEN
Solar/Wind Helper
0.313
316473AC1-191 GEN
Solar/Wind Helper
1.387
316044AC1-158 PL1
Solar/Wind Helper
1.257
316450AC1-158 RIC
Solar/Wind Helper
0.335
971543AH1-269 GEN
50/50
12.247
966391AG1-508 GEN
Solar/Wind Harmer
1.993
270069AE2-166 C O1
Solar/Wind Harmer
0.008
971313AH1-133 GEN
Solar/Wind Harmer
10.952
24734705WLF1G3
Adder
8.194
24734805WLF1G4
Adder
8.194
24734905WLF1G5
Adder
8.194
270132AB1-180 C
Adder
0.169
24735105WLF2G1
Adder
8.023
270399AC1-101 GEN
Solar/Wind Harmer
2.892
270400AC1-102 GEN
Solar/Wind Harmer
2.892
941621AE2-160 GEN
Adder
4.285
957241AF2-018 GEN
Solar/Wind Harmer
-0.002
970281AG2-184 GEN
Solar/Wind Harmer
18.925
972143AH1-644 GEN
Solar/Wind Harmer
9.763
971981AH1-535 GEN
Solar/Wind Harmer
5.843
971061AG2-657 GEN
Solar/Wind Harmer
5.368
24477305BRIDGE
Adder
0.419
972203AH1-686 GEN
Adder
2.704
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
965401AG1-405 GEN
Solar/Wind Harmer
4.227
965411AG1-406 GEN
Solar/Wind Harmer
2.719
339211AE2-254 GEN
Solar/Wind Harmer
0.003
3429211JKCT 2G
Adder
11.873
970455AG2-298 GEN
Solar/Wind Harmer
4.677
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
972163AH1-664 GEN
Solar/Wind Harmer
7.568
972165AH1-665 GEN
Solar/Wind Harmer
6.061
971985AH1-537 GEN
Solar/Wind Harmer
2.011
270367AC2-061_GEN
Solar/Wind Harmer
0.005
316123AC1-075 GEN
Solar/Wind Harmer
0.168
970165AG2-112 GEN
Solar/Wind Harmer
0.998
970163AG2-111 GEN
Solar/Wind Harmer
0.952
25196108MFTGT2
Adder
1.425
25196108MFTGT2
Adder
1.324
970879AG2-548 GEN
Solar/Wind Harmer
5.761
944221AF1-090 GEN
Solar/Wind Harmer
3.754
252524AE2-267 GEN
Solar/Wind Harmer
0.002
25196408WSDLE3
Adder
8.08
25196308WSDLE2
Adder
8.01
25196208WSDLE1
Adder
7.99
25196708WSDLE6
Adder
7.97
25196508WSDLE4
Adder
7.769
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.229
276848AB2-070 GEN3
Solar/Wind Harmer
0.228
963841AG1-237 GEN
Solar/Wind Harmer
2.698
946321AF1-296 GEN
Solar/Wind Harmer
3.483
270340AC2-060 GEN
Solar/Wind Harmer
0.007
276655WTG1_EQ
Solar/Wind Harmer
0.002
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
6.505
941731AE2-173 GEN
Solar/Wind Harmer
5.162
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
957751AF2-069 GEN
Solar/Wind Harmer
0.204
961011AF2-392 GEN
Solar/Wind Harmer
3.623
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
270240V3-007_GEN2
Solar/Wind Harmer
0.002
971681AH1-341 GEN
Solar/Wind Harmer
9.917
276612AE2-035 GEN
Solar/Wind Harmer
0.002
926823AC1-168 GEN
Solar/Wind Harmer
1.045
970169AG2-114 GEN
Solar/Wind Harmer
6.149
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274823ROCKFORD ;21
Adder
17.15
971171AH1-044 GEN
Solar/Wind Harmer
12.273
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
971675AH1-338 GEN
Solar/Wind Harmer
2.39
971411AH1-196 GEN
Solar/Wind Harmer
9.19
970289AG2-191 GEN
Solar/Wind Harmer
1.163
971177AH1-047 GEN
Solar/Wind Harmer
3.774
270594AE1-207 GEN
Solar/Wind Harmer
6.853
276868AE1-113 GEN
Solar/Wind Harmer
1.227
276882AE2-255 GEN
Solar/Wind Harmer
0.715
970115AG2-085 GEN
Solar/Wind Harmer
2.442
971673AH1-337 GEN
Solar/Wind Harmer
3.956
274746AC1-111 G10
Adder
4.87
274744AC1-111 GEN8
Adder
4.87
25306009OHH W.
Adder
2.505
3148463FAIRFLD
Solar/Wind Helper
0.726
3148133STUARTS
Solar/Wind Helper
0.313
3148013FISHERV
Solar/Wind Helper
0.3
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
23546401DTGZ2-030
Solar/Wind Helper
0.078
316164AC1-076 GEN
Solar/Wind Helper
1.172
238152AF2-075_GEN
Solar/Wind Helper
0.602
971029AG2-637 GEN
Solar/Wind Harmer
2.803
944201AF1-088_MTX
Adder
109.09
957141AF2-008_MTX
Adder
54.545
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.415
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.315
MECLTFEXP_MEC->PJM
CLTF
15.415
SIGELTFEXP_SIGE->PJM
CLTF
0.508
LAGNLTFEXP_LAGN->PJM
CLTF
20.28
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.555
TVALTFEXP_TVA->PJM
CLTF
10.606
CPLELTFEXP_CPLE->PJM
CLTF
6.226
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.111
NYPJM->LTFIMP_NY
CLTF
3.248
LGEELTFEXP_LGEE->PJM
CLTF
6.763
WECLTFEXP_WEC->PJM
CLTF
3.371
AG2-052LTFEXP_AG2-052->PJM
LTF
0.202
AH1-155LTFEXP_AH1-155->PJM
LTF
0.303

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-020_SRT-SL


Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-020_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.02 %
Rating:3610.0 MVA
Rating Type:B
MVA to Mitigate:4224.55
MW Contribution:9.68
Bus #Bus NameTypeMW Contribution
970479AG2-310 GEN
50/50
20.278
270205AE1-176
50/50
0.006
24288905REUSENS
50/50
0.057
24684605SMG4
50/50
2.241
966251AG1-494 GEN
50/50
4.391
24728405LEESVG
50/50
0.297
24415905BUCK
50/50
0.034
971367AH1-164 GEN
Solar/Wind Harmer
7.012
971329AH1-144 GEN
Solar/Wind Harmer
23.734
3147312GRETNA
Solar/Wind Harmer
-0.005
941821AE2-187 GEN
Solar/Wind Harmer
9.82
270197AD1-017 GEN1
Solar/Wind Harmer
2.549
270336AE1-100 GEN
Solar/Wind Harmer
2.762
943811AF1-049 GEN
Solar/Wind Harmer
5.705
24728305BUCHG2
Adder
6.772
270018AE2-047 C O1
Solar/Wind Harmer
1.828
958131AF2-107 GEN
Solar/Wind Harmer
7.112
24735205WLF2G2
Adder
8.049
971687AH1-348 GEN
Solar/Wind Harmer
1.364
971403AH1-188 GEN
Solar/Wind Harmer
18.932
24723205RIVRG3
Adder
23.068
971315AH1-136 GEN
Solar/Wind Harmer
2.441
24686105CER G3
Adder
9.94
24686505CER G6
Adder
9.927
270331AC1-082 GEN3
Solar/Wind Harmer
0.49
970947AG2-589 GEN
Solar/Wind Harmer
2.153
24721705FLATG2
Adder
21.813
970273AG2-179 GEN
Solar/Wind Harmer
2.594
971821AH1-427 GEN
Solar/Wind Harmer
10.401
964901AG1-354 GEN
Solar/Wind Harmer
15.577
960001AF2-291 GEN
Solar/Wind Harmer
3.136
339241AF1-083 GEN
Solar/Wind Harmer
1.723
962241AG1-070 GEN
Solar/Wind Harmer
4.662
3429241JKCT 3G
Adder
12.097
3429421JKCT 10G
Adder
8.45
971565AH1-281 GEN
Solar/Wind Harmer
2.012
943111AE2-339 GEN
Solar/Wind Harmer
0.888
339216AC1-074 GEN
Solar/Wind Harmer
1.659
945681AF1-233 GEN
Solar/Wind Harmer
18.436
927014AC1-188 GEN
Solar/Wind Harmer
1.543
970091AG2-072 GEN
Adder
74.457
970333AG2-219 GEN
Solar/Wind Harmer
30.235
270445AC2-157 GEN2
Solar/Wind Harmer
5.271
25196808ZIMRHP
Adder
71.09
252507AC2-088 GEN
Solar/Wind Harmer
1.681
25196008MFTGT1
Adder
1.302
25194608D.CRK4
Adder
1.519
965911AG1-460 GEN
Solar/Wind Harmer
1.278
253432AC1-085 GEN2
Solar/Wind Harmer
0.245
946171AF1-282 GEN
Solar/Wind Harmer
9.139
24728605AND G2
Adder
3.502
276615X2-022 GEN
Solar/Wind Harmer
1.783
963831AG1-236 GEN
Solar/Wind Harmer
8.931
274880W4-005 GEN4
Solar/Wind Harmer
2.743
963741AG1-226 GEN
Solar/Wind Harmer
40.621
274761LEE CO EC;2U
Adder
8.273
274766LEE CO EC;7U
Adder
8.175
972235AH1-702 GEN1
Adder
2.234
274822ROCKFORD ;11
Adder
17.383
274828WAUKEGAN ;BP
Adder
9.716
274682WAUKEGAN ;7U
Adder
15.803
274745AC1-111 GEN9
Adder
4.901
253370AE2-315 SEC1
Adder
1.753
253371AE2-315 SEC2
Adder
1.658
315616AA1-038_C
Solar/Wind Helper
3.295
3148013FISHERV
Solar/Wind Helper
0.523
316499AE2-029_GEN
Solar/Wind Helper
1.727
3132273ORANGE
Solar/Wind Helper
0.056
3147666LOUISA
Solar/Wind Helper
0.628
237061AD1-155 GEN
Solar/Wind Helper
0.05
316170AC1-121 GEN2
Solar/Wind Helper
0.388
23583801GRNGAP
Solar/Wind Helper
4.315
316095T157 G97
Solar/Wind Helper
1.133
238147AE2-230_GEN1
Solar/Wind Helper
0.423
238149AF1-291A_GEN
Solar/Wind Helper
0.121
966881AG1-559 GEN
Solar/Wind Helper
0.314
316313AB2-026
Solar/Wind Helper
0.355
316258AE1-075 C
Solar/Wind Helper
0.319
316405AF2-144 C
Solar/Wind Helper
0.266
316044AC1-158 PL1
Solar/Wind Helper
1.263
316450AC1-158 RIC
Solar/Wind Helper
0.337
316473AC1-191 GEN
Solar/Wind Helper
1.391
972175AH1-670 GEN
Solar/Wind Harmer
4.749
24290605CLAY-1
50/50
0.256
24290605CLAY-1
50/50
0.256
24290705CLAY-2
50/50
0.256
24290705CLAY-2
50/50
0.256
24684405SMG2
50/50
2.226
24684505SMG3
50/50
1.377
24684305SMG1
50/50
0.807
270583AD2-179 GEN
Solar/Wind Harmer
20.758
270214AC2-123 GEN
Solar/Wind Harmer
4.319
971277AH1-098 GEN
Solar/Wind Harmer
7.435
316217AC1-145 GEN
Solar/Wind Harmer
4.25
316197AC1-042 GEN
Solar/Wind Harmer
3.222
942671AE2-283 GEN
Solar/Wind Harmer
8.674
24728205BUCHG1
Adder
6.772
270013AE1-250 PV
Solar/Wind Harmer
3.259
971225AH1-072 GEN
Solar/Wind Harmer
2.74
971227AH1-073 GEN
Solar/Wind Harmer
2.74
944971AF1-162 GEN
Solar/Wind Harmer
9.108
24723005RIVRG1
Adder
23.068
24723105RIVRG2
Adder
23.068
24685805CER G1
Adder
9.875
24685905CER G2
Adder
9.875
942751AE2-291 GEN
Solar/Wind Harmer
10.391
966021AG1-471 GEN
Solar/Wind Harmer
5.779
971485AH1-239 GEN
Solar/Wind Harmer
8.537
339231AF1-038_GEN
Solar/Wind Harmer
1.927
970823AG2-518 GEN
50/50
8.396
247619Y1-049
50/50
0.915
24684705SMG5
50/50
0.857
970481AG2-311 GEN
50/50
11.948
24728405LEESVG
50/50
0.296
24416005BYLLESBY
50/50
0.031
3151561HALLBR1
50/50
0.57
970563AG2-360 GEN
50/50
45.959
962751AG1-124 GEN
Solar/Wind Harmer
18.84
958121AF2-106 GEN
Solar/Wind Harmer
9.423
270173AC1-122 GEN
Solar/Wind Harmer
3.281
971331AH1-145 GEN
Solar/Wind Harmer
18.398
943031AE2-326 GEN
Solar/Wind Harmer
6.798
3147312GRETNA
Solar/Wind Harmer
-0.021
3146802CHATHAM
Solar/Wind Harmer
-0.02
941801AE2-185 GEN
Solar/Wind Harmer
9.82
270574AD1-017 GEN2
Solar/Wind Harmer
8.482
3147123OTTER R
Solar/Wind Harmer
-0.014
270346AE1-212 GEN
Solar/Wind Harmer
13.986
270030AE2-140 GEN
Solar/Wind Harmer
30.98
960911AF2-382 GEN
Solar/Wind Harmer
10.985
270016AE1-250 BESS
Solar/Wind Harmer
3.259
970913AG2-568 GEN
Solar/Wind Harmer
11.054
971461AH1-227 GEN
Solar/Wind Harmer
7.029
970223AG2-152 GEN
Solar/Wind Harmer
17.643
270053AF1-130 C
Solar/Wind Harmer
4.837
972103AH1-617 GEN
Solar/Wind Harmer
25.94
24686205CER G4
Adder
9.888
24686405CER G5
Adder
9.849
972273AH1-721 GEN
Adder
89.748
24721905FLATG4
Adder
21.813
970273AG2-179 GEN
Solar/Wind Harmer
4.143
339250AF1-203 GEN
Solar/Wind Harmer
0.631
971155AH1-034 GEN
Solar/Wind Harmer
10.404
966571AG1-526 GEN
Solar/Wind Harmer
23.009
962251AG1-071 GEN
Solar/Wind Harmer
5.699
970093AG2-073 GEN
Solar/Wind Harmer
10.328
960741AF2-365 GEN
Solar/Wind Harmer
5.133
971191AH1-055 GEN
Solar/Wind Harmer
22.339
3429391JKCT 9G
Adder
8.45
972167AH1-666 GEN
Solar/Wind Harmer
7.817
957541AF2-048 GEN
Solar/Wind Harmer
1.539
958171AF2-111 GEN
Solar/Wind Harmer
24.064
970243AG2-164 GEN
Solar/Wind Harmer
24.738
970519AG2-331 GEN
Solar/Wind Harmer
16.62
970699AG2-449 GEN
Solar/Wind Harmer
10.995
25196008MFTGT1
Adder
1.261
252510AF1-249 C
Solar/Wind Harmer
0.387
25194608D.CRK4
Adder
1.519
25196608WSDLE5
Adder
7.903
970193AG2-126 GEN
Solar/Wind Harmer
13.773
942481AE2-261 GEN
Solar/Wind Harmer
27.393
253316AC1-085 GEN3
Solar/Wind Harmer
7.655
253433AC1-085 GEN1
Solar/Wind Harmer
4.859
946181AF1-283 GEN
Solar/Wind Harmer
11.881
24728705AND G3
Adder
7.324
24728505AND G1
Adder
3.502
960161AF2-307 GEN
Solar/Wind Harmer
6.695
339255AE2-071 GEN
Solar/Wind Harmer
1.104
964781AG1-341 GEN
Solar/Wind Harmer
11.023
339236AF1-050_GEN
Solar/Wind Harmer
1.882
971081AG2-670 GEN
Solar/Wind Harmer
7.773
942891AE2-308 GEN
Solar/Wind Harmer
10.233
970653AG2-424 GEN
Solar/Wind Harmer
4.906
970653AG2-424 GEN
Solar/Wind Harmer
1.774
964571AG1-320 GEN
Solar/Wind Harmer
8.231
971125AH1-004 GEN
Solar/Wind Harmer
4.003
970107AG2-081 GEN
Solar/Wind Harmer
3.003
972043AH1-570 GEN
Solar/Wind Harmer
2.49
972045AH1-571 GEN
Solar/Wind Harmer
1.992
339221AD2-048_GEN
Solar/Wind Harmer
1.523
970235AG2-159 GEN
Solar/Wind Harmer
3.901
970235AG2-159 GEN
Solar/Wind Harmer
2.382
270186AC1-089 GEN
Solar/Wind Harmer
5.863
970239AG2-162 GEN
Solar/Wind Harmer
10.536
962581AG1-107 GEN
Solar/Wind Harmer
4.763
961491AF2-440 GEN
Solar/Wind Harmer
1.98
270444AC2-157 GEN1
Solar/Wind Harmer
5.271
252509AD1-136 GEN
Solar/Wind Harmer
0.24
25183208HLCRTG
Solar/Wind Harmer
5.62
252519AF1-045_GEN
Solar/Wind Harmer
5.628
252516AE2-318_GEN
Solar/Wind Harmer
4.293
970879AG2-548 GEN
Solar/Wind Harmer
5.702
971073AG2-665 GEN
Solar/Wind Harmer
5.702
971073AG2-665 GEN
Solar/Wind Harmer
3.978
25194408D.CRK1
Adder
6.985
25194508D.CRK3
Adder
1.306
945391AF1-204 GEN
Solar/Wind Harmer
12.796
276916AD2-100_GEN
Solar/Wind Harmer
19.269
276911AD2-131_GEN
Solar/Wind Harmer
3.894
957381AF2-032 GEN
Solar/Wind Harmer
0.383
253317AC1-085 GEN4
Solar/Wind Harmer
7.655
276763AC1-053 GEN1
Solar/Wind Harmer
3.59
276764AC1-053 GEN2
Solar/Wind Harmer
3.59
970241AG2-163 GEN
Solar/Wind Harmer
22.567
24728805RICHG1
Adder
3.406
24728905RICHG2
Adder
3.406
972267AH1-718 GEN
Adder
3.711
274764LEE CO EC;5U
Adder
8.292
274765LEE CO EC;6U
Adder
8.292
274762LEE CO EC;3U
Adder
8.273
274763LEE CO EC;4U
Adder
8.195
274683WAUKEGAN ;8U
Adder
18.536
274683WAUKEGAN ;8U
Adder
15.625
274696ROCKY RD ;4P
Adder
10.02
274695ROCKY RD ;2P
Adder
9.789
274693ROCKY RD ;1P
Adder
9.693
274697ROCKY RD ;3P
Adder
2.659
253370AE2-315 SEC1
Adder
1.753
3132123MT JACKSON
Solar/Wind Helper
1.392
315821AE2-092 GEN
Solar/Wind Helper
3.222
966001AG1-469 GEN
Solar/Wind Helper
0.321
315651AD1-115 GEN
Solar/Wind Helper
0.841
316447AC1-158 HLD
Solar/Wind Helper
2.779
966871AG1-558 GEN
Solar/Wind Helper
0.307
316468AD1-105 GEN
Solar/Wind Helper
1.129
276621W2-048 GEN
Solar/Wind Harmer
5.679
276838X2-022 GEN2
Solar/Wind Harmer
0.212
276686W4-005 GEN3
Solar/Wind Harmer
2.743
276668AB2-070 GEN1
Solar/Wind Harmer
2.04
971993AH1-541 GEN
Solar/Wind Harmer
8.379
253406AD2-031_GEN
Solar/Wind Harmer
1.157
270356AE2-297 GEN
Solar/Wind Harmer
4.125
274760LEE CO EC;1U
Adder
8.273
274767LEE CO EC;8U
Adder
8.175
972236AH1-702 GEN2
Adder
1.942
274682WAUKEGAN ;7U
Adder
15.803
253370AE2-315 SEC1
Adder
1.753
253371AE2-315 SEC2
Adder
1.658
274729ELWOOD EC;1P
Adder
1.688
3147983MERCK5
Solar/Wind Helper
0.199
316192AB2-158 GEN
Solar/Wind Helper
1.845
3147666LOUISA
Solar/Wind Helper
1.091
316254AC1-120 GEN1
Solar/Wind Helper
1.164
316097T157 G90
Solar/Wind Helper
1.133
238148AE2-230_GEN2
Solar/Wind Helper
0.425
316336AC2-165 C
Solar/Wind Helper
1.289
316006AB2-029 C
Solar/Wind Helper
0.113
316045AC1-158 PL2
Solar/Wind Helper
4.042
3142416OLDCHRC
Solar/Wind Helper
0.58
3142416OLDCHRC
Solar/Wind Helper
0.222
971543AH1-269 GEN
50/50
12.267
966391AG1-508 GEN
Solar/Wind Harmer
6.388
270069AE2-166 C O1
Solar/Wind Harmer
4.514
971313AH1-133 GEN
Solar/Wind Harmer
15.745
24734705WLF1G3
Adder
8.22
24734805WLF1G4
Adder
8.22
24734905WLF1G5
Adder
8.22
270132AB1-180 C
Adder
0.169
24735105WLF2G1
Adder
8.049
270399AC1-101 GEN
Solar/Wind Harmer
5.58
270400AC1-102 GEN
Solar/Wind Harmer
5.58
941621AE2-160 GEN
Adder
4.308
957241AF2-018 GEN
Solar/Wind Harmer
5.782
970281AG2-184 GEN
Solar/Wind Harmer
27.237
972143AH1-644 GEN
Solar/Wind Harmer
12.97
971981AH1-535 GEN
Solar/Wind Harmer
12.604
962211AG1-066 GEN
Solar/Wind Harmer
3.014
971061AG2-657 GEN
Solar/Wind Harmer
11.059
24477305BRIDGE
Adder
0.422
972203AH1-686 GEN
Adder
2.718
270330AC1-082 GEN2
Solar/Wind Harmer
0.83
270329AC1-082 GEN1
Solar/Wind Harmer
0.489
965401AG1-405 GEN
Solar/Wind Harmer
6.089
965411AG1-406 GEN
Solar/Wind Harmer
2.733
339211AE2-254 GEN
Solar/Wind Harmer
1.572
3429211JKCT 2G
Adder
11.941
970455AG2-298 GEN
Solar/Wind Harmer
6.067
339243AC2-075 GEN1
Solar/Wind Harmer
0.449
972163AH1-664 GEN
Solar/Wind Harmer
9.805
972165AH1-665 GEN
Solar/Wind Harmer
7.844
971985AH1-537 GEN
Solar/Wind Harmer
17.415
270367AC2-061_GEN
Solar/Wind Harmer
3.029
316123AC1-075 GEN
Solar/Wind Harmer
1.494
970165AG2-112 GEN
Solar/Wind Harmer
1.315
970163AG2-111 GEN
Solar/Wind Harmer
1.255
25196108MFTGT2
Adder
1.435
25196108MFTGT2
Adder
1.332
970879AG2-548 GEN
Solar/Wind Harmer
3.978
944221AF1-090 GEN
Solar/Wind Harmer
10.083
252524AE2-267 GEN
Solar/Wind Harmer
1.454
25196408WSDLE3
Adder
8.135
25196308WSDLE2
Adder
8.064
25196208WSDLE1
Adder
8.044
25196708WSDLE6
Adder
8.024
25196508WSDLE4
Adder
7.822
276785W4-005 GEN1
Solar/Wind Harmer
2.743
276174W4-005 GEN2
Solar/Wind Harmer
2.743
276849AB2-070 GEN2
Solar/Wind Harmer
2.04
276848AB2-070 GEN3
Solar/Wind Harmer
2.04
274823ROCKFORD ;21
Adder
17.257
274746AC1-111 G10
Adder
4.901
274744AC1-111 GEN8
Adder
4.901
25306009OHH W.
Adder
2.523
253372AE2-315 SEC3
Adder
1.658
253372AE2-315 SEC3
Adder
1.658
3148463FAIRFLD
Solar/Wind Helper
0.727
3148133STUARTS
Solar/Wind Helper
0.314
3148013FISHERV
Solar/Wind Helper
0.301
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
23546401DTGZ2-030
Solar/Wind Helper
0.079
316164AC1-076 GEN
Solar/Wind Helper
1.177
238152AF2-075_GEN
Solar/Wind Helper
0.605
316312AB1-027
Solar/Wind Helper
0.425
3141426STAFORD
Solar/Wind Helper
0.049
944201AF1-088_MTX
Adder
109.749
957141AF2-008_MTX
Adder
54.874
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.199
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.491
MECLTFEXP_MEC->PJM
CLTF
15.504
SIGELTFEXP_SIGE->PJM
CLTF
0.511
LAGNLTFEXP_LAGN->PJM
CLTF
20.369
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.617
TVALTFEXP_TVA->PJM
CLTF
10.651
CPLELTFEXP_CPLE->PJM
CLTF
6.237
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.77
NYPJM->LTFIMP_NY
CLTF
3.272
LGEELTFEXP_LGEE->PJM
CLTF
6.802
WECLTFEXP_WEC->PJM
CLTF
3.393
AG2-052LTFEXP_AG2-052->PJM
LTF
0.203
AH1-155LTFEXP_AH1-155->PJM
LTF
0.304

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-021_SRT-SL


Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-021_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.77 %
Rating:3610.0 MVA
Rating Type:B
MVA to Mitigate:4215.43
MW Contribution:9.63
Bus #Bus NameTypeMW Contribution
970479AG2-310 GEN
50/50
20.262
270205AE1-176
50/50
0.006
24288905REUSENS
50/50
0.057
24684605SMG4
50/50
2.239
966251AG1-494 GEN
50/50
4.389
24728405LEESVG
50/50
0.297
24415905BUCK
50/50
0.034
971367AH1-164 GEN
Solar/Wind Harmer
7.006
971329AH1-144 GEN
Solar/Wind Harmer
23.701
3147312GRETNA
Solar/Wind Harmer
-0.005
941821AE2-187 GEN
Solar/Wind Harmer
9.814
270197AD1-017 GEN1
Solar/Wind Harmer
2.547
270336AE1-100 GEN
Solar/Wind Harmer
2.759
943811AF1-049 GEN
Solar/Wind Harmer
5.698
24728305BUCHG2
Adder
6.757
270018AE2-047 C O1
Solar/Wind Harmer
1.826
958131AF2-107 GEN
Solar/Wind Harmer
7.109
24735205WLF2G2
Adder
8.031
971687AH1-348 GEN
Solar/Wind Harmer
1.36
971403AH1-188 GEN
Solar/Wind Harmer
18.877
24723205RIVRG3
Adder
22.989
971315AH1-136 GEN
Solar/Wind Harmer
2.433
24686105CER G3
Adder
9.903
24686505CER G6
Adder
9.89
270331AC1-082 GEN3
Solar/Wind Harmer
0.488
24721705FLATG2
Adder
21.725
970947AG2-589 GEN
Solar/Wind Harmer
2.143
970273AG2-179 GEN
Solar/Wind Harmer
2.585
971821AH1-427 GEN
Solar/Wind Harmer
10.363
964901AG1-354 GEN
Solar/Wind Harmer
15.523
339241AF1-083 GEN
Solar/Wind Harmer
1.717
962241AG1-070 GEN
Solar/Wind Harmer
4.647
960001AF2-291 GEN
Solar/Wind Harmer
3.12
3429241JKCT 3G
Adder
12.05
3429421JKCT 10G
Adder
8.417
971565AH1-281 GEN
Solar/Wind Harmer
2.004
943111AE2-339 GEN
Solar/Wind Harmer
0.884
339216AC1-074 GEN
Solar/Wind Harmer
1.652
945681AF1-233 GEN
Solar/Wind Harmer
18.356
927014AC1-188 GEN
Solar/Wind Harmer
1.535
970091AG2-072 GEN
Adder
74.149
970333AG2-219 GEN
Solar/Wind Harmer
30.107
270445AC2-157 GEN2
Solar/Wind Harmer
5.249
25196808ZIMRHP
Adder
70.761
252507AC2-088 GEN
Solar/Wind Harmer
1.673
25196008MFTGT1
Adder
1.296
25194608D.CRK4
Adder
1.511
965911AG1-460 GEN
Solar/Wind Harmer
1.273
253432AC1-085 GEN2
Solar/Wind Harmer
0.243
946171AF1-282 GEN
Solar/Wind Harmer
9.095
24728605AND G2
Adder
3.486
276615X2-022 GEN
Solar/Wind Harmer
1.776
963831AG1-236 GEN
Solar/Wind Harmer
8.893
274880W4-005 GEN4
Solar/Wind Harmer
2.731
963741AG1-226 GEN
Solar/Wind Harmer
40.444
274761LEE CO EC;2U
Adder
8.237
274766LEE CO EC;7U
Adder
8.14
972235AH1-702 GEN1
Adder
2.224
274822ROCKFORD ;11
Adder
17.308
274828WAUKEGAN ;BP
Adder
9.674
274682WAUKEGAN ;7U
Adder
15.734
274745AC1-111 GEN9
Adder
4.879
253370AE2-315 SEC1
Adder
1.744
253371AE2-315 SEC2
Adder
1.649
315616AA1-038_C
Solar/Wind Helper
3.294
3148013FISHERV
Solar/Wind Helper
0.523
316499AE2-029_GEN
Solar/Wind Helper
1.725
3132273ORANGE
Solar/Wind Helper
0.056
3147666LOUISA
Solar/Wind Helper
0.626
237061AD1-155 GEN
Solar/Wind Helper
0.05
316170AC1-121 GEN2
Solar/Wind Helper
0.387
23583801GRNGAP
Solar/Wind Helper
4.296
316095T157 G97
Solar/Wind Helper
1.128
238147AE2-230_GEN1
Solar/Wind Helper
0.422
238149AF1-291A_GEN
Solar/Wind Helper
0.12
966881AG1-559 GEN
Solar/Wind Helper
0.314
316313AB2-026
Solar/Wind Helper
0.354
316258AE1-075 C
Solar/Wind Helper
0.319
316405AF2-144 C
Solar/Wind Helper
0.266
316473AC1-191 GEN
Solar/Wind Helper
1.388
316044AC1-158 PL1
Solar/Wind Helper
1.259
316450AC1-158 RIC
Solar/Wind Helper
0.336
972175AH1-670 GEN
Solar/Wind Harmer
4.729
24290605CLAY-1
50/50
0.255
24290605CLAY-1
50/50
0.255
24290705CLAY-2
50/50
0.255
24290705CLAY-2
50/50
0.255
24684405SMG2
50/50
2.225
24684505SMG3
50/50
1.376
24684305SMG1
50/50
0.806
270583AD2-179 GEN
Solar/Wind Harmer
20.732
270214AC2-123 GEN
Solar/Wind Harmer
4.313
971277AH1-098 GEN
Solar/Wind Harmer
7.425
316217AC1-145 GEN
Solar/Wind Harmer
4.248
316197AC1-042 GEN
Solar/Wind Harmer
3.22
942671AE2-283 GEN
Solar/Wind Harmer
8.669
24728205BUCHG1
Adder
6.757
270013AE1-250 PV
Solar/Wind Harmer
3.257
971225AH1-072 GEN
Solar/Wind Harmer
2.733
971227AH1-073 GEN
Solar/Wind Harmer
2.733
944971AF1-162 GEN
Solar/Wind Harmer
9.08
24723005RIVRG1
Adder
22.989
24723105RIVRG2
Adder
22.989
24685805CER G1
Adder
9.838
24685905CER G2
Adder
9.838
942751AE2-291 GEN
Solar/Wind Harmer
10.387
966021AG1-471 GEN
Solar/Wind Harmer
5.761
971485AH1-239 GEN
Solar/Wind Harmer
8.509
339231AF1-038_GEN
Solar/Wind Harmer
1.921
960161AF2-307 GEN
Solar/Wind Harmer
6.669
339255AE2-071 GEN
Solar/Wind Harmer
1.1
964781AG1-341 GEN
Solar/Wind Harmer
10.986
339236AF1-050_GEN
Solar/Wind Harmer
1.875
971081AG2-670 GEN
Solar/Wind Harmer
7.746
942891AE2-308 GEN
Solar/Wind Harmer
10.193
970653AG2-424 GEN
Solar/Wind Harmer
4.888
970653AG2-424 GEN
Solar/Wind Harmer
1.767
964571AG1-320 GEN
Solar/Wind Harmer
8.199
971125AH1-004 GEN
Solar/Wind Harmer
3.987
970107AG2-081 GEN
Solar/Wind Harmer
2.99
972043AH1-570 GEN
Solar/Wind Harmer
2.479
972045AH1-571 GEN
Solar/Wind Harmer
1.983
339221AD2-048_GEN
Solar/Wind Harmer
1.517
970235AG2-159 GEN
Solar/Wind Harmer
3.885
970235AG2-159 GEN
Solar/Wind Harmer
2.372
270186AC1-089 GEN
Solar/Wind Harmer
5.836
970239AG2-162 GEN
Solar/Wind Harmer
10.492
962581AG1-107 GEN
Solar/Wind Harmer
4.741
961491AF2-440 GEN
Solar/Wind Harmer
1.97
270444AC2-157 GEN1
Solar/Wind Harmer
5.249
252509AD1-136 GEN
Solar/Wind Harmer
0.239
25183208HLCRTG
Solar/Wind Harmer
5.594
252519AF1-045_GEN
Solar/Wind Harmer
5.601
252516AE2-318_GEN
Solar/Wind Harmer
4.272
970879AG2-548 GEN
Solar/Wind Harmer
5.67
971073AG2-665 GEN
Solar/Wind Harmer
5.67
971073AG2-665 GEN
Solar/Wind Harmer
3.956
25194408D.CRK1
Adder
6.953
25194508D.CRK3
Adder
1.3
945391AF1-204 GEN
Solar/Wind Harmer
12.742
276916AD2-100_GEN
Solar/Wind Harmer
19.19
276911AD2-131_GEN
Solar/Wind Harmer
3.878
957381AF2-032 GEN
Solar/Wind Harmer
0.382
253317AC1-085 GEN4
Solar/Wind Harmer
7.618
276763AC1-053 GEN1
Solar/Wind Harmer
3.575
276764AC1-053 GEN2
Solar/Wind Harmer
3.575
970241AG2-163 GEN
Solar/Wind Harmer
22.469
24728805RICHG1
Adder
3.391
24728905RICHG2
Adder
3.391
972267AH1-718 GEN
Adder
3.695
274764LEE CO EC;5U
Adder
8.257
274765LEE CO EC;6U
Adder
8.257
274762LEE CO EC;3U
Adder
8.237
274763LEE CO EC;4U
Adder
8.16
274683WAUKEGAN ;8U
Adder
18.455
274683WAUKEGAN ;8U
Adder
15.556
274696ROCKY RD ;4P
Adder
9.976
274695ROCKY RD ;2P
Adder
9.746
274693ROCKY RD ;1P
Adder
9.65
274697ROCKY RD ;3P
Adder
2.648
253370AE2-315 SEC1
Adder
1.744
3132123MT JACKSON
Solar/Wind Helper
1.39
315821AE2-092 GEN
Solar/Wind Helper
3.218
966001AG1-469 GEN
Solar/Wind Helper
0.32
315651AD1-115 GEN
Solar/Wind Helper
0.839
966871AG1-558 GEN
Solar/Wind Helper
0.306
316447AC1-158 HLD
Solar/Wind Helper
2.77
316468AD1-105 GEN
Solar/Wind Helper
1.126
970823AG2-518 GEN
50/50
8.387
247619Y1-049
50/50
0.914
24684705SMG5
50/50
0.857
970481AG2-311 GEN
50/50
11.94
24728405LEESVG
50/50
0.296
24416005BYLLESBY
50/50
0.031
3151561HALLBR1
50/50
0.57
970563AG2-360 GEN
50/50
45.869
962751AG1-124 GEN
Solar/Wind Harmer
18.829
958121AF2-106 GEN
Solar/Wind Harmer
9.412
270173AC1-122 GEN
Solar/Wind Harmer
3.279
971331AH1-145 GEN
Solar/Wind Harmer
18.373
943031AE2-326 GEN
Solar/Wind Harmer
6.789
3147312GRETNA
Solar/Wind Harmer
-0.021
3146802CHATHAM
Solar/Wind Harmer
-0.02
941801AE2-185 GEN
Solar/Wind Harmer
9.814
270574AD1-017 GEN2
Solar/Wind Harmer
8.476
3147123OTTER R
Solar/Wind Harmer
-0.014
270346AE1-212 GEN
Solar/Wind Harmer
13.951
270030AE2-140 GEN
Solar/Wind Harmer
30.945
960911AF2-382 GEN
Solar/Wind Harmer
10.959
270016AE1-250 BESS
Solar/Wind Harmer
3.257
970913AG2-568 GEN
Solar/Wind Harmer
11.019
971461AH1-227 GEN
Solar/Wind Harmer
7.011
970223AG2-152 GEN
Solar/Wind Harmer
17.629
270053AF1-130 C
Solar/Wind Harmer
4.822
972103AH1-617 GEN
Solar/Wind Harmer
25.867
24686205CER G4
Adder
9.851
24686405CER G5
Adder
9.812
972273AH1-721 GEN
Adder
89.448
24721905FLATG4
Adder
21.725
970273AG2-179 GEN
Solar/Wind Harmer
4.129
339250AF1-203 GEN
Solar/Wind Harmer
0.629
971155AH1-034 GEN
Solar/Wind Harmer
10.369
966571AG1-526 GEN
Solar/Wind Harmer
22.923
962251AG1-071 GEN
Solar/Wind Harmer
5.679
970093AG2-073 GEN
Solar/Wind Harmer
10.289
960741AF2-365 GEN
Solar/Wind Harmer
5.115
3429391JKCT 9G
Adder
8.417
971191AH1-055 GEN
Solar/Wind Harmer
22.23
972167AH1-666 GEN
Solar/Wind Harmer
7.783
957541AF2-048 GEN
Solar/Wind Harmer
1.531
958171AF2-111 GEN
Solar/Wind Harmer
23.957
970243AG2-164 GEN
Solar/Wind Harmer
24.633
970519AG2-331 GEN
Solar/Wind Harmer
16.549
970699AG2-449 GEN
Solar/Wind Harmer
10.948
25196008MFTGT1
Adder
1.255
252510AF1-249 C
Solar/Wind Harmer
0.385
25194608D.CRK4
Adder
1.511
25196608WSDLE5
Adder
7.866
970193AG2-126 GEN
Solar/Wind Harmer
13.715
942481AE2-261 GEN
Solar/Wind Harmer
27.279
253316AC1-085 GEN3
Solar/Wind Harmer
7.618
253433AC1-085 GEN1
Solar/Wind Harmer
4.836
946181AF1-283 GEN
Solar/Wind Harmer
11.823
24728705AND G3
Adder
7.292
24728505AND G1
Adder
3.486
276621W2-048 GEN
Solar/Wind Harmer
5.656
276838X2-022 GEN2
Solar/Wind Harmer
0.211
276668AB2-070 GEN1
Solar/Wind Harmer
2.031
276686W4-005 GEN3
Solar/Wind Harmer
2.731
971993AH1-541 GEN
Solar/Wind Harmer
8.344
270356AE2-297 GEN
Solar/Wind Harmer
4.106
253406AD2-031_GEN
Solar/Wind Harmer
1.151
274760LEE CO EC;1U
Adder
8.237
274767LEE CO EC;8U
Adder
8.14
972236AH1-702 GEN2
Adder
1.934
274682WAUKEGAN ;7U
Adder
15.734
253370AE2-315 SEC1
Adder
1.744
253371AE2-315 SEC2
Adder
1.649
274729ELWOOD EC;1P
Adder
1.681
3147983MERCK5
Solar/Wind Helper
0.198
316192AB2-158 GEN
Solar/Wind Helper
1.84
3147666LOUISA
Solar/Wind Helper
1.089
316254AC1-120 GEN1
Solar/Wind Helper
1.161
316097T157 G90
Solar/Wind Helper
1.128
238148AE2-230_GEN2
Solar/Wind Helper
0.424
316336AC2-165 C
Solar/Wind Helper
1.286
316006AB2-029 C
Solar/Wind Helper
0.113
316045AC1-158 PL2
Solar/Wind Helper
4.029
971543AH1-269 GEN
50/50
12.253
966391AG1-508 GEN
Solar/Wind Harmer
6.379
270069AE2-166 C O1
Solar/Wind Harmer
4.509
971313AH1-133 GEN
Solar/Wind Harmer
15.712
24734705WLF1G3
Adder
8.202
24734805WLF1G4
Adder
8.202
24734905WLF1G5
Adder
8.202
270132AB1-180 C
Adder
0.169
24735105WLF2G1
Adder
8.031
270399AC1-101 GEN
Solar/Wind Harmer
5.563
270400AC1-102 GEN
Solar/Wind Harmer
5.563
941621AE2-160 GEN
Adder
4.292
957241AF2-018 GEN
Solar/Wind Harmer
5.764
970281AG2-184 GEN
Solar/Wind Harmer
27.16
972143AH1-644 GEN
Solar/Wind Harmer
12.933
971981AH1-535 GEN
Solar/Wind Harmer
12.575
962211AG1-066 GEN
Solar/Wind Harmer
3.005
971061AG2-657 GEN
Solar/Wind Harmer
11.012
24477305BRIDGE
Adder
0.42
972203AH1-686 GEN
Adder
2.709
270330AC1-082 GEN2
Solar/Wind Harmer
0.826
270329AC1-082 GEN1
Solar/Wind Harmer
0.486
965401AG1-405 GEN
Solar/Wind Harmer
6.068
965411AG1-406 GEN
Solar/Wind Harmer
2.724
339211AE2-254 GEN
Solar/Wind Harmer
1.566
3429211JKCT 2G
Adder
11.894
970455AG2-298 GEN
Solar/Wind Harmer
6.044
339243AC2-075 GEN1
Solar/Wind Harmer
0.447
972163AH1-664 GEN
Solar/Wind Harmer
9.762
972165AH1-665 GEN
Solar/Wind Harmer
7.81
971985AH1-537 GEN
Solar/Wind Harmer
17.332
270367AC2-061_GEN
Solar/Wind Harmer
3.015
316123AC1-075 GEN
Solar/Wind Harmer
1.493
970165AG2-112 GEN
Solar/Wind Harmer
1.315
970163AG2-111 GEN
Solar/Wind Harmer
1.254
25196108MFTGT2
Adder
1.428
25196108MFTGT2
Adder
1.326
970879AG2-548 GEN
Solar/Wind Harmer
3.956
944221AF1-090 GEN
Solar/Wind Harmer
10.042
252524AE2-267 GEN
Solar/Wind Harmer
1.447
25196408WSDLE3
Adder
8.097
25196308WSDLE2
Adder
8.027
25196208WSDLE1
Adder
8.006
25196708WSDLE6
Adder
7.986
25196508WSDLE4
Adder
7.785
276849AB2-070 GEN2
Solar/Wind Harmer
2.031
276848AB2-070 GEN3
Solar/Wind Harmer
2.031
276785W4-005 GEN1
Solar/Wind Harmer
2.731
276174W4-005 GEN2
Solar/Wind Harmer
2.731
274823ROCKFORD ;21
Adder
17.182
274746AC1-111 G10
Adder
4.879
274744AC1-111 GEN8
Adder
4.879
25306009OHH W.
Adder
2.51
253372AE2-315 SEC3
Adder
1.649
253372AE2-315 SEC3
Adder
1.649
3148463FAIRFLD
Solar/Wind Helper
0.726
3148133STUARTS
Solar/Wind Helper
0.314
3148013FISHERV
Solar/Wind Helper
0.3
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
23546401DTGZ2-030
Solar/Wind Helper
0.079
316164AC1-076 GEN
Solar/Wind Helper
1.173
238152AF2-075_GEN
Solar/Wind Helper
0.603
944201AF1-088_MTX
Adder
109.291
957141AF2-008_MTX
Adder
54.646
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.655
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.369
MECLTFEXP_MEC->PJM
CLTF
15.442
SIGELTFEXP_SIGE->PJM
CLTF
0.509
LAGNLTFEXP_LAGN->PJM
CLTF
20.308
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.574
TVALTFEXP_TVA->PJM
CLTF
10.62
CPLELTFEXP_CPLE->PJM
CLTF
6.229
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.312
NYPJM->LTFIMP_NY
CLTF
3.255
LGEELTFEXP_LGEE->PJM
CLTF
6.775
WECLTFEXP_WEC->PJM
CLTF
3.378
AG2-052LTFEXP_AG2-052->PJM
LTF
0.202
AH1-155LTFEXP_AH1-155->PJM
LTF
0.303

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AEP_P4_#37_05MOUNTN 765_B1_SRT-A


Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#37_05MOUNTN 765_B1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.68 %
Rating:3610.0 MVA
Rating Type:B
MVA to Mitigate:4211.98
MW Contribution:9.6
Bus #Bus NameTypeMW Contribution
970479AG2-310 GEN
50/50
20.255
270205AE1-176
50/50
0.006
24288905REUSENS
50/50
0.057
24684605SMG4
50/50
2.239
966251AG1-494 GEN
50/50
4.388
24728405LEESVG
50/50
0.297
24415905BUCK
50/50
0.034
971367AH1-164 GEN
Solar/Wind Harmer
7.003
971329AH1-144 GEN
Solar/Wind Harmer
23.686
3147312GRETNA
Solar/Wind Harmer
-0.005
941821AE2-187 GEN
Solar/Wind Harmer
9.812
270197AD1-017 GEN1
Solar/Wind Harmer
2.546
270336AE1-100 GEN
Solar/Wind Harmer
2.757
943811AF1-049 GEN
Solar/Wind Harmer
5.695
24728305BUCHG2
Adder
6.75
270018AE2-047 C O1
Solar/Wind Harmer
1.826
958131AF2-107 GEN
Solar/Wind Harmer
7.108
24735205WLF2G2
Adder
8.023
971687AH1-348 GEN
Solar/Wind Harmer
1.359
971403AH1-188 GEN
Solar/Wind Harmer
18.852
24723205RIVRG3
Adder
22.954
971315AH1-136 GEN
Solar/Wind Harmer
2.43
24686105CER G3
Adder
9.887
24686505CER G6
Adder
9.874
270331AC1-082 GEN3
Solar/Wind Harmer
0.487
24721705FLATG2
Adder
21.686
970947AG2-589 GEN
Solar/Wind Harmer
2.139
970273AG2-179 GEN
Solar/Wind Harmer
2.581
971821AH1-427 GEN
Solar/Wind Harmer
10.346
964901AG1-354 GEN
Solar/Wind Harmer
15.5
339241AF1-083 GEN
Solar/Wind Harmer
1.715
962241AG1-070 GEN
Solar/Wind Harmer
4.64
960001AF2-291 GEN
Solar/Wind Harmer
3.113
3429241JKCT 3G
Adder
12.029
3429421JKCT 10G
Adder
8.402
971565AH1-281 GEN
Solar/Wind Harmer
2.001
943111AE2-339 GEN
Solar/Wind Harmer
0.883
339216AC1-074 GEN
Solar/Wind Harmer
1.649
945681AF1-233 GEN
Solar/Wind Harmer
18.32
927014AC1-188 GEN
Solar/Wind Harmer
1.532
970091AG2-072 GEN
Adder
74.012
970333AG2-219 GEN
Solar/Wind Harmer
30.05
270445AC2-157 GEN2
Solar/Wind Harmer
5.239
25196808ZIMRHP
Adder
70.616
252507AC2-088 GEN
Solar/Wind Harmer
1.669
25196008MFTGT1
Adder
1.293
25194608D.CRK4
Adder
1.508
965911AG1-460 GEN
Solar/Wind Harmer
1.271
253432AC1-085 GEN2
Solar/Wind Harmer
0.243
946171AF1-282 GEN
Solar/Wind Harmer
9.075
24728605AND G2
Adder
3.48
276615X2-022 GEN
Solar/Wind Harmer
1.772
963831AG1-236 GEN
Solar/Wind Harmer
8.877
274880W4-005 GEN4
Solar/Wind Harmer
2.726
963741AG1-226 GEN
Solar/Wind Harmer
40.366
274761LEE CO EC;2U
Adder
8.222
274766LEE CO EC;7U
Adder
8.125
972235AH1-702 GEN1
Adder
2.22
274822ROCKFORD ;11
Adder
17.275
274828WAUKEGAN ;BP
Adder
9.655
274682WAUKEGAN ;7U
Adder
15.703
274745AC1-111 GEN9
Adder
4.87
315616AA1-038_C
Solar/Wind Helper
3.293
3148013FISHERV
Solar/Wind Helper
0.523
316499AE2-029_GEN
Solar/Wind Helper
1.725
3132273ORANGE
Solar/Wind Helper
0.056
3147666LOUISA
Solar/Wind Helper
0.625
237061AD1-155 GEN
Solar/Wind Helper
0.05
316170AC1-121 GEN2
Solar/Wind Helper
0.386
23583801GRNGAP
Solar/Wind Helper
4.287
316095T157 G97
Solar/Wind Helper
1.125
238147AE2-230_GEN1
Solar/Wind Helper
0.421
238149AF1-291A_GEN
Solar/Wind Helper
0.12
316313AB2-026
Solar/Wind Helper
0.354
316258AE1-075 C
Solar/Wind Helper
0.319
316405AF2-144 C
Solar/Wind Helper
0.265
966881AG1-559 GEN
Solar/Wind Helper
0.313
316473AC1-191 GEN
Solar/Wind Helper
1.387
316044AC1-158 PL1
Solar/Wind Helper
1.257
316450AC1-158 RIC
Solar/Wind Helper
0.335
972175AH1-670 GEN
Solar/Wind Harmer
4.72
24290605CLAY-1
50/50
0.255
24290605CLAY-1
50/50
0.255
24290705CLAY-2
50/50
0.255
24290705CLAY-2
50/50
0.255
24684405SMG2
50/50
2.224
24684505SMG3
50/50
1.376
24684305SMG1
50/50
0.806
270583AD2-179 GEN
Solar/Wind Harmer
20.721
270214AC2-123 GEN
Solar/Wind Harmer
4.311
971277AH1-098 GEN
Solar/Wind Harmer
7.42
316217AC1-145 GEN
Solar/Wind Harmer
4.247
316197AC1-042 GEN
Solar/Wind Harmer
3.219
942671AE2-283 GEN
Solar/Wind Harmer
8.667
24728205BUCHG1
Adder
6.75
270013AE1-250 PV
Solar/Wind Harmer
3.256
971225AH1-072 GEN
Solar/Wind Harmer
2.73
971227AH1-073 GEN
Solar/Wind Harmer
2.73
944971AF1-162 GEN
Solar/Wind Harmer
9.068
24723005RIVRG1
Adder
22.954
24723105RIVRG2
Adder
22.954
24685805CER G1
Adder
9.822
24685905CER G2
Adder
9.822
942751AE2-291 GEN
Solar/Wind Harmer
10.385
966021AG1-471 GEN
Solar/Wind Harmer
5.753
971485AH1-239 GEN
Solar/Wind Harmer
8.497
339231AF1-038_GEN
Solar/Wind Harmer
1.918
960161AF2-307 GEN
Solar/Wind Harmer
6.658
339255AE2-071 GEN
Solar/Wind Harmer
1.099
964781AG1-341 GEN
Solar/Wind Harmer
10.97
339236AF1-050_GEN
Solar/Wind Harmer
1.872
971081AG2-670 GEN
Solar/Wind Harmer
7.734
942891AE2-308 GEN
Solar/Wind Harmer
10.176
970653AG2-424 GEN
Solar/Wind Harmer
4.88
970653AG2-424 GEN
Solar/Wind Harmer
1.764
964571AG1-320 GEN
Solar/Wind Harmer
8.186
971125AH1-004 GEN
Solar/Wind Harmer
3.98
970107AG2-081 GEN
Solar/Wind Harmer
2.985
972043AH1-570 GEN
Solar/Wind Harmer
2.475
972045AH1-571 GEN
Solar/Wind Harmer
1.98
339221AD2-048_GEN
Solar/Wind Harmer
1.514
970235AG2-159 GEN
Solar/Wind Harmer
3.878
970235AG2-159 GEN
Solar/Wind Harmer
2.367
270186AC1-089 GEN
Solar/Wind Harmer
5.824
970239AG2-162 GEN
Solar/Wind Harmer
10.472
962581AG1-107 GEN
Solar/Wind Harmer
4.731
961491AF2-440 GEN
Solar/Wind Harmer
1.966
270444AC2-157 GEN1
Solar/Wind Harmer
5.239
252509AD1-136 GEN
Solar/Wind Harmer
0.238
25183208HLCRTG
Solar/Wind Harmer
5.582
252519AF1-045_GEN
Solar/Wind Harmer
5.589
252516AE2-318_GEN
Solar/Wind Harmer
4.263
25194408D.CRK1
Adder
6.938
25194508D.CRK3
Adder
1.297
970879AG2-548 GEN
Solar/Wind Harmer
5.656
971073AG2-665 GEN
Solar/Wind Harmer
5.656
971073AG2-665 GEN
Solar/Wind Harmer
3.946
945391AF1-204 GEN
Solar/Wind Harmer
12.718
276916AD2-100_GEN
Solar/Wind Harmer
19.154
276911AD2-131_GEN
Solar/Wind Harmer
3.871
957381AF2-032 GEN
Solar/Wind Harmer
0.381
253317AC1-085 GEN4
Solar/Wind Harmer
7.601
276763AC1-053 GEN1
Solar/Wind Harmer
3.568
276764AC1-053 GEN2
Solar/Wind Harmer
3.568
970241AG2-163 GEN
Solar/Wind Harmer
22.426
24728805RICHG1
Adder
3.384
24728905RICHG2
Adder
3.384
972267AH1-718 GEN
Adder
3.688
274764LEE CO EC;5U
Adder
8.241
274765LEE CO EC;6U
Adder
8.241
274762LEE CO EC;3U
Adder
8.222
274763LEE CO EC;4U
Adder
8.144
274683WAUKEGAN ;8U
Adder
18.419
274683WAUKEGAN ;8U
Adder
15.526
274696ROCKY RD ;4P
Adder
9.957
274695ROCKY RD ;2P
Adder
9.727
274693ROCKY RD ;1P
Adder
9.632
274697ROCKY RD ;3P
Adder
2.642
3132123MT JACKSON
Solar/Wind Helper
1.389
315821AE2-092 GEN
Solar/Wind Helper
3.216
966001AG1-469 GEN
Solar/Wind Helper
0.32
315651AD1-115 GEN
Solar/Wind Helper
0.837
966871AG1-558 GEN
Solar/Wind Helper
0.306
316447AC1-158 HLD
Solar/Wind Helper
2.766
316468AD1-105 GEN
Solar/Wind Helper
1.124
970823AG2-518 GEN
50/50
8.384
247619Y1-049
50/50
0.913
24684705SMG5
50/50
0.856
970481AG2-311 GEN
50/50
11.937
24728405LEESVG
50/50
0.295
24416005BYLLESBY
50/50
0.031
3151561HALLBR1
50/50
0.57
970563AG2-360 GEN
50/50
45.829
962751AG1-124 GEN
Solar/Wind Harmer
18.825
958121AF2-106 GEN
Solar/Wind Harmer
9.407
270173AC1-122 GEN
Solar/Wind Harmer
3.278
971331AH1-145 GEN
Solar/Wind Harmer
18.361
943031AE2-326 GEN
Solar/Wind Harmer
6.784
3147312GRETNA
Solar/Wind Harmer
-0.021
3146802CHATHAM
Solar/Wind Harmer
-0.02
941801AE2-185 GEN
Solar/Wind Harmer
9.812
270574AD1-017 GEN2
Solar/Wind Harmer
8.473
3147123OTTER R
Solar/Wind Harmer
-0.014
270346AE1-212 GEN
Solar/Wind Harmer
13.936
270030AE2-140 GEN
Solar/Wind Harmer
30.929
960911AF2-382 GEN
Solar/Wind Harmer
10.948
270016AE1-250 BESS
Solar/Wind Harmer
3.256
970913AG2-568 GEN
Solar/Wind Harmer
11.004
971461AH1-227 GEN
Solar/Wind Harmer
7.003
970223AG2-152 GEN
Solar/Wind Harmer
17.623
270053AF1-130 C
Solar/Wind Harmer
4.815
972103AH1-617 GEN
Solar/Wind Harmer
25.835
24686205CER G4
Adder
9.835
24686405CER G5
Adder
9.796
972273AH1-721 GEN
Adder
89.316
24721905FLATG4
Adder
21.686
970273AG2-179 GEN
Solar/Wind Harmer
4.123
339250AF1-203 GEN
Solar/Wind Harmer
0.628
971155AH1-034 GEN
Solar/Wind Harmer
10.354
962251AG1-071 GEN
Solar/Wind Harmer
5.671
966571AG1-526 GEN
Solar/Wind Harmer
22.886
970093AG2-073 GEN
Solar/Wind Harmer
10.271
960741AF2-365 GEN
Solar/Wind Harmer
5.107
3429391JKCT 9G
Adder
8.402
971191AH1-055 GEN
Solar/Wind Harmer
22.182
972167AH1-666 GEN
Solar/Wind Harmer
7.768
957541AF2-048 GEN
Solar/Wind Harmer
1.528
958171AF2-111 GEN
Solar/Wind Harmer
23.91
970243AG2-164 GEN
Solar/Wind Harmer
24.587
970519AG2-331 GEN
Solar/Wind Harmer
16.518
970699AG2-449 GEN
Solar/Wind Harmer
10.927
25196008MFTGT1
Adder
1.252
252510AF1-249 C
Solar/Wind Harmer
0.384
25194608D.CRK4
Adder
1.508
25196608WSDLE5
Adder
7.849
970193AG2-126 GEN
Solar/Wind Harmer
13.689
942481AE2-261 GEN
Solar/Wind Harmer
27.229
253316AC1-085 GEN3
Solar/Wind Harmer
7.601
253433AC1-085 GEN1
Solar/Wind Harmer
4.825
946181AF1-283 GEN
Solar/Wind Harmer
11.797
24728705AND G3
Adder
7.277
24728505AND G1
Adder
3.48
276621W2-048 GEN
Solar/Wind Harmer
5.645
276838X2-022 GEN2
Solar/Wind Harmer
0.211
276686W4-005 GEN3
Solar/Wind Harmer
2.726
276668AB2-070 GEN1
Solar/Wind Harmer
2.027
971993AH1-541 GEN
Solar/Wind Harmer
8.328
270356AE2-297 GEN
Solar/Wind Harmer
4.098
253406AD2-031_GEN
Solar/Wind Harmer
1.149
274760LEE CO EC;1U
Adder
8.222
274767LEE CO EC;8U
Adder
8.125
972236AH1-702 GEN2
Adder
1.93
274682WAUKEGAN ;7U
Adder
15.703
274729ELWOOD EC;1P
Adder
13.481
3147983MERCK5
Solar/Wind Helper
0.198
316192AB2-158 GEN
Solar/Wind Helper
1.838
3147666LOUISA
Solar/Wind Helper
1.088
316254AC1-120 GEN1
Solar/Wind Helper
1.159
316097T157 G90
Solar/Wind Helper
1.125
238148AE2-230_GEN2
Solar/Wind Helper
0.423
316336AC2-165 C
Solar/Wind Helper
1.285
316006AB2-029 C
Solar/Wind Helper
0.112
316045AC1-158 PL2
Solar/Wind Helper
4.023
971543AH1-269 GEN
50/50
12.247
966391AG1-508 GEN
Solar/Wind Harmer
6.374
270069AE2-166 C O1
Solar/Wind Harmer
4.507
971313AH1-133 GEN
Solar/Wind Harmer
15.698
24734705WLF1G3
Adder
8.194
24734805WLF1G4
Adder
8.194
24734905WLF1G5
Adder
8.194
270132AB1-180 C
Adder
0.169
24735105WLF2G1
Adder
8.023
270399AC1-101 GEN
Solar/Wind Harmer
5.556
270400AC1-102 GEN
Solar/Wind Harmer
5.556
941621AE2-160 GEN
Adder
4.285
957241AF2-018 GEN
Solar/Wind Harmer
5.757
970281AG2-184 GEN
Solar/Wind Harmer
27.126
972143AH1-644 GEN
Solar/Wind Harmer
12.917
971981AH1-535 GEN
Solar/Wind Harmer
12.563
962211AG1-066 GEN
Solar/Wind Harmer
3.001
971061AG2-657 GEN
Solar/Wind Harmer
10.991
24477305BRIDGE
Adder
0.419
972203AH1-686 GEN
Adder
2.704
270330AC1-082 GEN2
Solar/Wind Harmer
0.824
270329AC1-082 GEN1
Solar/Wind Harmer
0.485
965401AG1-405 GEN
Solar/Wind Harmer
6.059
965411AG1-406 GEN
Solar/Wind Harmer
2.719
339211AE2-254 GEN
Solar/Wind Harmer
1.563
3429211JKCT 2G
Adder
11.873
970455AG2-298 GEN
Solar/Wind Harmer
6.034
339243AC2-075 GEN1
Solar/Wind Harmer
0.446
972163AH1-664 GEN
Solar/Wind Harmer
9.743
972165AH1-665 GEN
Solar/Wind Harmer
7.794
971985AH1-537 GEN
Solar/Wind Harmer
17.295
270367AC2-061_GEN
Solar/Wind Harmer
3.009
316123AC1-075 GEN
Solar/Wind Harmer
1.493
970165AG2-112 GEN
Solar/Wind Harmer
1.315
970163AG2-111 GEN
Solar/Wind Harmer
1.254
25196108MFTGT2
Adder
1.425
25196108MFTGT2
Adder
1.324
970879AG2-548 GEN
Solar/Wind Harmer
3.946
944221AF1-090 GEN
Solar/Wind Harmer
10.024
252524AE2-267 GEN
Solar/Wind Harmer
1.444
25196408WSDLE3
Adder
8.08
25196308WSDLE2
Adder
8.01
25196208WSDLE1
Adder
7.99
25196708WSDLE6
Adder
7.97
25196508WSDLE4
Adder
7.769
276785W4-005 GEN1
Solar/Wind Harmer
2.726
276174W4-005 GEN2
Solar/Wind Harmer
2.726
276849AB2-070 GEN2
Solar/Wind Harmer
2.027
276848AB2-070 GEN3
Solar/Wind Harmer
2.027
274823ROCKFORD ;21
Adder
17.15
274746AC1-111 G10
Adder
4.87
274744AC1-111 GEN8
Adder
4.87
25306009OHH W.
Adder
2.505
3148463FAIRFLD
Solar/Wind Helper
0.726
3148133STUARTS
Solar/Wind Helper
0.313
3148013FISHERV
Solar/Wind Helper
0.3
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
23546401DTGZ2-030
Solar/Wind Helper
0.078
316164AC1-076 GEN
Solar/Wind Helper
1.172
238152AF2-075_GEN
Solar/Wind Helper
0.602
944201AF1-088_MTX
Adder
109.09
957141AF2-008_MTX
Adder
54.545
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.415
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.315
MECLTFEXP_MEC->PJM
CLTF
15.415
SIGELTFEXP_SIGE->PJM
CLTF
0.508
LAGNLTFEXP_LAGN->PJM
CLTF
20.28
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.555
TVALTFEXP_TVA->PJM
CLTF
10.606
CPLELTFEXP_CPLE->PJM
CLTF
6.226
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.111
NYPJM->LTFIMP_NY
CLTF
3.248
LGEELTFEXP_LGEE->PJM
CLTF
6.763
WECLTFEXP_WEC->PJM
CLTF
3.371
AG2-052LTFEXP_AG2-052->PJM
LTF
0.202
AH1-155LTFEXP_AH1-155->PJM
LTF
0.303

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AEP_P4_#2942_05KAMMER 765_PP_SRT-A


Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2942_05KAMMER 765_PP_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.36 %
Rating:3610.0 MVA
Rating Type:B
MVA to Mitigate:4200.43
MW Contribution:9.61
Bus #Bus NameTypeMW Contribution
24290605CLAY-1
50/50
0.255
24290605CLAY-1
50/50
0.255
24290705CLAY-2
50/50
0.255
24290705CLAY-2
50/50
0.255
24684405SMG2
50/50
2.225
24684505SMG3
50/50
1.376
24684305SMG1
50/50
0.806
270583AD2-179 GEN
Solar/Wind Harmer
20.728
270214AC2-123 GEN
Solar/Wind Harmer
4.312
971277AH1-098 GEN
Solar/Wind Harmer
7.423
316217AC1-145 GEN
Solar/Wind Harmer
4.248
316197AC1-042 GEN
Solar/Wind Harmer
3.22
942671AE2-283 GEN
Solar/Wind Harmer
8.67
24728205BUCHG1
Adder
6.753
270013AE1-250 PV
Solar/Wind Harmer
3.257
971225AH1-072 GEN
Solar/Wind Harmer
2.732
971227AH1-073 GEN
Solar/Wind Harmer
2.732
944971AF1-162 GEN
Solar/Wind Harmer
9.072
24723005RIVRG1
Adder
22.966
24723105RIVRG2
Adder
22.966
24685805CER G1
Adder
9.828
24685905CER G2
Adder
9.828
942751AE2-291 GEN
Solar/Wind Harmer
10.391
966021AG1-471 GEN
Solar/Wind Harmer
5.756
971485AH1-239 GEN
Solar/Wind Harmer
8.502
339231AF1-038_GEN
Solar/Wind Harmer
1.919
960161AF2-307 GEN
Solar/Wind Harmer
6.662
339255AE2-071 GEN
Solar/Wind Harmer
1.099
964781AG1-341 GEN
Solar/Wind Harmer
10.976
339236AF1-050_GEN
Solar/Wind Harmer
1.873
971081AG2-670 GEN
Solar/Wind Harmer
7.739
942891AE2-308 GEN
Solar/Wind Harmer
10.182
970653AG2-424 GEN
Solar/Wind Harmer
4.883
970653AG2-424 GEN
Solar/Wind Harmer
1.765
964571AG1-320 GEN
Solar/Wind Harmer
8.191
971125AH1-004 GEN
Solar/Wind Harmer
3.983
970107AG2-081 GEN
Solar/Wind Harmer
2.987
972043AH1-570 GEN
Solar/Wind Harmer
2.476
972045AH1-571 GEN
Solar/Wind Harmer
1.981
339221AD2-048_GEN
Solar/Wind Harmer
1.515
970235AG2-159 GEN
Solar/Wind Harmer
3.88
970235AG2-159 GEN
Solar/Wind Harmer
2.369
270186AC1-089 GEN
Solar/Wind Harmer
5.828
970239AG2-162 GEN
Solar/Wind Harmer
10.479
962581AG1-107 GEN
Solar/Wind Harmer
4.734
961491AF2-440 GEN
Solar/Wind Harmer
1.967
970823AG2-518 GEN
50/50
8.386
247619Y1-049
50/50
0.913
24684705SMG5
50/50
0.857
970481AG2-311 GEN
50/50
11.941
24728405LEESVG
50/50
0.296
24416005BYLLESBY
50/50
0.031
3151561HALLBR1
50/50
0.57
970563AG2-360 GEN
50/50
45.847
962751AG1-124 GEN
Solar/Wind Harmer
18.831
958121AF2-106 GEN
Solar/Wind Harmer
9.409
270173AC1-122 GEN
Solar/Wind Harmer
3.279
971331AH1-145 GEN
Solar/Wind Harmer
18.367
943031AE2-326 GEN
Solar/Wind Harmer
6.787
3147312GRETNA
Solar/Wind Harmer
-0.021
3146802CHATHAM
Solar/Wind Harmer
-0.02
941801AE2-185 GEN
Solar/Wind Harmer
9.815
270574AD1-017 GEN2
Solar/Wind Harmer
8.476
3147123OTTER R
Solar/Wind Harmer
-0.014
270346AE1-212 GEN
Solar/Wind Harmer
13.941
270030AE2-140 GEN
Solar/Wind Harmer
30.942
960911AF2-382 GEN
Solar/Wind Harmer
10.952
270016AE1-250 BESS
Solar/Wind Harmer
3.257
970913AG2-568 GEN
Solar/Wind Harmer
11.009
971461AH1-227 GEN
Solar/Wind Harmer
7.007
970223AG2-152 GEN
Solar/Wind Harmer
17.631
270053AF1-130 C
Solar/Wind Harmer
4.818
972103AH1-617 GEN
Solar/Wind Harmer
25.847
24686205CER G4
Adder
9.841
24686405CER G5
Adder
9.802
972273AH1-721 GEN
Adder
89.369
24721905FLATG4
Adder
21.699
970273AG2-179 GEN
Solar/Wind Harmer
4.125
339250AF1-203 GEN
Solar/Wind Harmer
0.628
971155AH1-034 GEN
Solar/Wind Harmer
10.36
962251AG1-071 GEN
Solar/Wind Harmer
5.674
966571AG1-526 GEN
Solar/Wind Harmer
22.9
970093AG2-073 GEN
Solar/Wind Harmer
10.278
960741AF2-365 GEN
Solar/Wind Harmer
5.111
3429391JKCT 9G
Adder
8.407
971191AH1-055 GEN
Solar/Wind Harmer
22.196
972167AH1-666 GEN
Solar/Wind Harmer
7.773
957541AF2-048 GEN
Solar/Wind Harmer
1.529
958171AF2-111 GEN
Solar/Wind Harmer
23.926
970243AG2-164 GEN
Solar/Wind Harmer
24.603
970519AG2-331 GEN
Solar/Wind Harmer
16.529
970699AG2-449 GEN
Solar/Wind Harmer
10.935
25196008MFTGT1
Adder
1.253
252510AF1-249 C
Solar/Wind Harmer
0.385
25194608D.CRK4
Adder
1.509
25196608WSDLE5
Adder
7.855
970193AG2-126 GEN
Solar/Wind Harmer
13.698
942481AE2-261 GEN
Solar/Wind Harmer
27.248
253316AC1-085 GEN3
Solar/Wind Harmer
7.607
253433AC1-085 GEN1
Solar/Wind Harmer
4.829
946181AF1-283 GEN
Solar/Wind Harmer
11.806
24728705AND G3
Adder
7.283
24728505AND G1
Adder
3.482
276621W2-048 GEN
Solar/Wind Harmer
5.649
276838X2-022 GEN2
Solar/Wind Harmer
0.211
276668AB2-070 GEN1
Solar/Wind Harmer
2.029
276686W4-005 GEN3
Solar/Wind Harmer
2.728
971993AH1-541 GEN
Solar/Wind Harmer
8.334
270356AE2-297 GEN
Solar/Wind Harmer
4.101
253406AD2-031_GEN
Solar/Wind Harmer
1.149
274760LEE CO EC;1U
Adder
8.227
274767LEE CO EC;8U
Adder
8.131
972236AH1-702 GEN2
Adder
1.932
274682WAUKEGAN ;7U
Adder
15.715
274729ELWOOD EC;1P
Adder
13.491
3147983MERCK5
Solar/Wind Helper
0.198
316192AB2-158 GEN
Solar/Wind Helper
1.837
3147666LOUISA
Solar/Wind Helper
1.087
316254AC1-120 GEN1
Solar/Wind Helper
1.158
316097T157 G90
Solar/Wind Helper
1.124
238148AE2-230_GEN2
Solar/Wind Helper
0.423
316336AC2-165 C
Solar/Wind Helper
1.284
316006AB2-029 C
Solar/Wind Helper
0.112
316045AC1-158 PL2
Solar/Wind Helper
4.02
971543AH1-269 GEN
50/50
12.251
966391AG1-508 GEN
Solar/Wind Harmer
6.377
270069AE2-166 C O1
Solar/Wind Harmer
4.508
971313AH1-133 GEN
Solar/Wind Harmer
15.705
24734705WLF1G3
Adder
8.198
24734805WLF1G4
Adder
8.198
24734905WLF1G5
Adder
8.198
270132AB1-180 C
Adder
0.169
24735105WLF2G1
Adder
8.027
270399AC1-101 GEN
Solar/Wind Harmer
5.558
270400AC1-102 GEN
Solar/Wind Harmer
5.558
941621AE2-160 GEN
Adder
4.287
957241AF2-018 GEN
Solar/Wind Harmer
5.759
970281AG2-184 GEN
Solar/Wind Harmer
27.14
972143AH1-644 GEN
Solar/Wind Harmer
12.924
971981AH1-535 GEN
Solar/Wind Harmer
12.569
962211AG1-066 GEN
Solar/Wind Harmer
3.003
971061AG2-657 GEN
Solar/Wind Harmer
10.996
24477305BRIDGE
Adder
0.419
972203AH1-686 GEN
Adder
2.706
270330AC1-082 GEN2
Solar/Wind Harmer
0.824
270329AC1-082 GEN1
Solar/Wind Harmer
0.486
965401AG1-405 GEN
Solar/Wind Harmer
6.063
965411AG1-406 GEN
Solar/Wind Harmer
2.721
339211AE2-254 GEN
Solar/Wind Harmer
1.564
3429211JKCT 2G
Adder
11.881
970455AG2-298 GEN
Solar/Wind Harmer
6.038
339243AC2-075 GEN1
Solar/Wind Harmer
0.447
972163AH1-664 GEN
Solar/Wind Harmer
9.749
972165AH1-665 GEN
Solar/Wind Harmer
7.8
971985AH1-537 GEN
Solar/Wind Harmer
17.306
270367AC2-061_GEN
Solar/Wind Harmer
3.011
316123AC1-075 GEN
Solar/Wind Harmer
1.494
970165AG2-112 GEN
Solar/Wind Harmer
1.315
970163AG2-111 GEN
Solar/Wind Harmer
1.255
25196108MFTGT2
Adder
1.426
25196108MFTGT2
Adder
1.325
970879AG2-548 GEN
Solar/Wind Harmer
3.949
944221AF1-090 GEN
Solar/Wind Harmer
10.031
252524AE2-267 GEN
Solar/Wind Harmer
1.445
25196408WSDLE3
Adder
8.086
25196308WSDLE2
Adder
8.015
25196208WSDLE1
Adder
7.995
25196708WSDLE6
Adder
7.975
25196508WSDLE4
Adder
7.774
276849AB2-070 GEN2
Solar/Wind Harmer
2.029
276848AB2-070 GEN3
Solar/Wind Harmer
2.029
276785W4-005 GEN1
Solar/Wind Harmer
2.728
276174W4-005 GEN2
Solar/Wind Harmer
2.728
274823ROCKFORD ;21
Adder
17.162
274746AC1-111 G10
Adder
4.873
274744AC1-111 GEN8
Adder
4.873
25306009OHH W.
Adder
2.506
3148463FAIRFLD
Solar/Wind Helper
0.726
3148133STUARTS
Solar/Wind Helper
0.313
3148013FISHERV
Solar/Wind Helper
0.3
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
23546401DTGZ2-030
Solar/Wind Helper
0.078
316164AC1-076 GEN
Solar/Wind Helper
1.171
238152AF2-075_GEN
Solar/Wind Helper
0.601
270444AC2-157 GEN1
Solar/Wind Harmer
5.243
252509AD1-136 GEN
Solar/Wind Harmer
0.239
25183208HLCRTG
Solar/Wind Harmer
5.586
252519AF1-045_GEN
Solar/Wind Harmer
5.593
252516AE2-318_GEN
Solar/Wind Harmer
4.266
25194408D.CRK1
Adder
6.943
25194508D.CRK3
Adder
1.298
970879AG2-548 GEN
Solar/Wind Harmer
5.66
971073AG2-665 GEN
Solar/Wind Harmer
5.66
971073AG2-665 GEN
Solar/Wind Harmer
3.949
945391AF1-204 GEN
Solar/Wind Harmer
12.727
276916AD2-100_GEN
Solar/Wind Harmer
19.168
276911AD2-131_GEN
Solar/Wind Harmer
3.874
957381AF2-032 GEN
Solar/Wind Harmer
0.381
253317AC1-085 GEN4
Solar/Wind Harmer
7.607
276763AC1-053 GEN1
Solar/Wind Harmer
3.571
276764AC1-053 GEN2
Solar/Wind Harmer
3.571
970241AG2-163 GEN
Solar/Wind Harmer
22.442
24728805RICHG1
Adder
3.386
24728905RICHG2
Adder
3.386
972267AH1-718 GEN
Adder
3.691
274764LEE CO EC;5U
Adder
8.247
274765LEE CO EC;6U
Adder
8.247
274762LEE CO EC;3U
Adder
8.227
274763LEE CO EC;4U
Adder
8.15
274683WAUKEGAN ;8U
Adder
18.432
274683WAUKEGAN ;8U
Adder
15.538
274696ROCKY RD ;4P
Adder
9.964
274695ROCKY RD ;2P
Adder
9.734
274693ROCKY RD ;1P
Adder
9.639
274697ROCKY RD ;3P
Adder
2.644
3132123MT JACKSON
Solar/Wind Helper
1.388
315821AE2-092 GEN
Solar/Wind Helper
3.215
966001AG1-469 GEN
Solar/Wind Helper
0.32
315651AD1-115 GEN
Solar/Wind Helper
0.837
966871AG1-558 GEN
Solar/Wind Helper
0.306
316447AC1-158 HLD
Solar/Wind Helper
2.764
316468AD1-105 GEN
Solar/Wind Helper
1.124
970479AG2-310 GEN
50/50
20.26
270205AE1-176
50/50
0.006
24288905REUSENS
50/50
0.057
24684605SMG4
50/50
2.239
966251AG1-494 GEN
50/50
4.39
24728405LEESVG
50/50
0.297
24415905BUCK
50/50
0.034
971367AH1-164 GEN
Solar/Wind Harmer
7.005
971329AH1-144 GEN
Solar/Wind Harmer
23.694
3147312GRETNA
Solar/Wind Harmer
-0.005
941821AE2-187 GEN
Solar/Wind Harmer
9.815
270197AD1-017 GEN1
Solar/Wind Harmer
2.547
270336AE1-100 GEN
Solar/Wind Harmer
2.758
943811AF1-049 GEN
Solar/Wind Harmer
5.698
24728305BUCHG2
Adder
6.753
270018AE2-047 C O1
Solar/Wind Harmer
1.826
958131AF2-107 GEN
Solar/Wind Harmer
7.111
24735205WLF2G2
Adder
8.027
971687AH1-348 GEN
Solar/Wind Harmer
1.359
971403AH1-188 GEN
Solar/Wind Harmer
18.861
24723205RIVRG3
Adder
22.966
971315AH1-136 GEN
Solar/Wind Harmer
2.431
24686105CER G3
Adder
9.893
24686505CER G6
Adder
9.88
270331AC1-082 GEN3
Solar/Wind Harmer
0.487
24721705FLATG2
Adder
21.699
970947AG2-589 GEN
Solar/Wind Harmer
2.14
970273AG2-179 GEN
Solar/Wind Harmer
2.583
971821AH1-427 GEN
Solar/Wind Harmer
10.353
964901AG1-354 GEN
Solar/Wind Harmer
15.509
339241AF1-083 GEN
Solar/Wind Harmer
1.716
962241AG1-070 GEN
Solar/Wind Harmer
4.643
960001AF2-291 GEN
Solar/Wind Harmer
3.115
3429241JKCT 3G
Adder
12.037
3429421JKCT 10G
Adder
8.407
971565AH1-281 GEN
Solar/Wind Harmer
2.002
943111AE2-339 GEN
Solar/Wind Harmer
0.883
339216AC1-074 GEN
Solar/Wind Harmer
1.65
945681AF1-233 GEN
Solar/Wind Harmer
18.332
927014AC1-188 GEN
Solar/Wind Harmer
1.533
970091AG2-072 GEN
Adder
74.061
970333AG2-219 GEN
Solar/Wind Harmer
30.071
270445AC2-157 GEN2
Solar/Wind Harmer
5.243
25196808ZIMRHP
Adder
70.665
252507AC2-088 GEN
Solar/Wind Harmer
1.671
25196008MFTGT1
Adder
1.294
25194608D.CRK4
Adder
1.509
965911AG1-460 GEN
Solar/Wind Harmer
1.272
253432AC1-085 GEN2
Solar/Wind Harmer
0.243
946171AF1-282 GEN
Solar/Wind Harmer
9.081
24728605AND G2
Adder
3.482
276615X2-022 GEN
Solar/Wind Harmer
1.774
963831AG1-236 GEN
Solar/Wind Harmer
8.883
274880W4-005 GEN4
Solar/Wind Harmer
2.728
963741AG1-226 GEN
Solar/Wind Harmer
40.395
274761LEE CO EC;2U
Adder
8.227
274766LEE CO EC;7U
Adder
8.131
972235AH1-702 GEN1
Adder
2.221
274822ROCKFORD ;11
Adder
17.288
274828WAUKEGAN ;BP
Adder
9.662
274682WAUKEGAN ;7U
Adder
15.715
274745AC1-111 GEN9
Adder
4.873
315616AA1-038_C
Solar/Wind Helper
3.292
3148013FISHERV
Solar/Wind Helper
0.522
316499AE2-029_GEN
Solar/Wind Helper
1.724
3132273ORANGE
Solar/Wind Helper
0.056
3147666LOUISA
Solar/Wind Helper
0.625
237061AD1-155 GEN
Solar/Wind Helper
0.05
316170AC1-121 GEN2
Solar/Wind Helper
0.386
23583801GRNGAP
Solar/Wind Helper
4.284
316095T157 G97
Solar/Wind Helper
1.124
238147AE2-230_GEN1
Solar/Wind Helper
0.421
238149AF1-291A_GEN
Solar/Wind Helper
0.12
316313AB2-026
Solar/Wind Helper
0.354
316258AE1-075 C
Solar/Wind Helper
0.318
316405AF2-144 C
Solar/Wind Helper
0.265
966881AG1-559 GEN
Solar/Wind Helper
0.313
316473AC1-191 GEN
Solar/Wind Helper
1.386
316044AC1-158 PL1
Solar/Wind Helper
1.256
316450AC1-158 RIC
Solar/Wind Helper
0.335
972175AH1-670 GEN
Solar/Wind Harmer
4.723
944201AF1-088_MTX
Adder
109.164
957141AF2-008_MTX
Adder
54.582
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.508
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.339
MECLTFEXP_MEC->PJM
CLTF
15.425
SIGELTFEXP_SIGE->PJM
CLTF
0.508
LAGNLTFEXP_LAGN->PJM
CLTF
20.293
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.574
TVALTFEXP_TVA->PJM
CLTF
10.613
CPLELTFEXP_CPLE->PJM
CLTF
6.233
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.197
NYPJM->LTFIMP_NY
CLTF
3.243
LGEELTFEXP_LGEE->PJM
CLTF
6.767
WECLTFEXP_WEC->PJM
CLTF
3.374
AG2-052LTFEXP_AG2-052->PJM
LTF
0.202
AH1-155LTFEXP_AH1-155->PJM
LTF
0.303

Details for 05HARRISON-05OBETZ 138.0 kV Ckt 1 line l/o AEP_P4_#9672_05HARRISON 138_2W_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05HARRISON-05OBETZ 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#9672_05HARRISON 138_2W_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.01 %
Rating:223.0 MVA
Rating Type:B
MVA to Mitigate:223.03
MW Contribution:5.27
Bus #Bus NameTypeMW Contribution
970879AG2-548 GEN
Solar/Wind Harmer
3.104
971073AG2-665 GEN
Solar/Wind Harmer
3.104
971073AG2-665 GEN
Solar/Wind Harmer
2.166
270263AC1-001 GEN
Solar/Wind Harmer
1.374
960801AF2-371 GEN
Solar/Wind Harmer
8.544
964871AG1-351 GEN
Solar/Wind Harmer
5.9
270273AD2-016 GEN
Solar/Wind Harmer
4.779
972173AH1-669 GEN
Solar/Wind Harmer
7.89
270291AC1-194 GEN
Solar/Wind Harmer
5.968
270432AC2-029 GEN
Solar/Wind Harmer
19.44
270269AC2-059
Solar/Wind Harmer
16.711
970879AG2-548 GEN
Solar/Wind Harmer
2.166
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.494
SIGELTFEXP_SIGE->PJM
CLTF
0.005
LAGNLTFEXP_LAGN->PJM
CLTF
0.198
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.46
TVALTFEXP_TVA->PJM
CLTF
0.128
CPLELTFEXP_CPLE->PJM
CLTF
0.147
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.917
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.046
LGEELTFEXP_LGEE->PJM
CLTF
0.101

Details for 05HARRISON-05ZUBER 138.0 kV Ckt 1 line l/o AEP_P4_#9679_05HARRISON 138_2E_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05HARRISON-05ZUBER 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#9679_05HARRISON 138_2E_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:129.23 %
Rating:180.0 MVA
Rating Type:B
MVA to Mitigate:232.62
MW Contribution:6.38
Bus #Bus NameTypeMW Contribution
270263AC1-001 GEN
Solar/Wind Harmer
1.635
970879AG2-548 GEN
Solar/Wind Harmer
3.758
971073AG2-665 GEN
Solar/Wind Harmer
3.758
971073AG2-665 GEN
Solar/Wind Harmer
2.622
960801AF2-371 GEN
Solar/Wind Harmer
10.115
964871AG1-351 GEN
Solar/Wind Harmer
6.984
270273AD2-016 GEN
Solar/Wind Harmer
5.675
972173AH1-669 GEN
Solar/Wind Harmer
9.383
270291AC1-194 GEN
Solar/Wind Harmer
7.251
241955AC1-078 GEN
Solar/Wind Helper
1.051
270432AC2-029 GEN
Solar/Wind Harmer
23.01
270269AC2-059
Solar/Wind Harmer
19.846
970879AG2-548 GEN
Solar/Wind Harmer
2.622
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.112
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.274
LAGNLTFEXP_LAGN->PJM
CLTF
0.101
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.502
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.084
CPLELTFEXP_CPLE->PJM
CLTF
0.172
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.019
LGEELTFEXP_LGEE->PJM
CLTF
0.018

Details for 05HARRISON-05ZUBER 138.0 kV Ckt 1 line l/o AEP_P7-1_#10921___SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05HARRISON-05ZUBER 138.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10921___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:116.96 %
Rating:180.0 MVA
Rating Type:B
MVA to Mitigate:210.53
MW Contribution:6.18
Bus #Bus NameTypeMW Contribution
970879AG2-548 GEN
Solar/Wind Harmer
3.639
971073AG2-665 GEN
Solar/Wind Harmer
3.639
971073AG2-665 GEN
Solar/Wind Harmer
2.539
270263AC1-001 GEN
Solar/Wind Harmer
1.582
960801AF2-371 GEN
Solar/Wind Harmer
9.786
964871AG1-351 GEN
Solar/Wind Harmer
6.757
270273AD2-016 GEN
Solar/Wind Harmer
5.491
972173AH1-669 GEN
Solar/Wind Harmer
9.079
270291AC1-194 GEN
Solar/Wind Harmer
7.022
241955AC1-078 GEN
Solar/Wind Helper
1.041
270432AC2-029 GEN
Solar/Wind Harmer
22.262
270269AC2-059
Solar/Wind Harmer
19.202
970879AG2-548 GEN
Solar/Wind Harmer
2.539
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.116
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.256
LAGNLTFEXP_LAGN->PJM
CLTF
0.093
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.484
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.079
CPLELTFEXP_CPLE->PJM
CLTF
0.166
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.018
LGEELTFEXP_LGEE->PJM
CLTF
0.014

Details for 05HARRISON-05ZUBER 138.0 kV Ckt 1 line l/o AEP_P4_#9737_05MARION RD 138_4_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05HARRISON-05ZUBER 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#9737_05MARION RD 138_4_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.0 %
Rating:180.0 MVA
Rating Type:B
MVA to Mitigate:208.8
MW Contribution:6.17
Bus #Bus NameTypeMW Contribution
960801AF2-371 GEN
Solar/Wind Harmer
9.789
964871AG1-351 GEN
Solar/Wind Harmer
6.759
270273AD2-016 GEN
Solar/Wind Harmer
5.491
972173AH1-669 GEN
Solar/Wind Harmer
9.078
270291AC1-194 GEN
Solar/Wind Harmer
7.015
241955AC1-078 GEN
Solar/Wind Helper
1.035
270432AC2-029 GEN
Solar/Wind Harmer
22.268
270269AC2-059
Solar/Wind Harmer
19.203
970879AG2-548 GEN
Solar/Wind Harmer
2.536
970879AG2-548 GEN
Solar/Wind Harmer
3.635
971073AG2-665 GEN
Solar/Wind Harmer
3.635
971073AG2-665 GEN
Solar/Wind Harmer
2.536
270263AC1-001 GEN
Solar/Wind Harmer
1.582
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.112
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.259
LAGNLTFEXP_LAGN->PJM
CLTF
0.095
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.484
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.079
CPLELTFEXP_CPLE->PJM
CLTF
0.166
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.018
LGEELTFEXP_LGEE->PJM
CLTF
0.015

Details for 05HARRISON-05ZUBER 138.0 kV Ckt 1 line l/o AEP_P4_#9738_05MARION RD 138_5_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05HARRISON-05ZUBER 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#9738_05MARION RD 138_5_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.73 %
Rating:180.0 MVA
Rating Type:B
MVA to Mitigate:208.32
MW Contribution:6.17
Bus #Bus NameTypeMW Contribution
960801AF2-371 GEN
Solar/Wind Harmer
9.789
964871AG1-351 GEN
Solar/Wind Harmer
6.759
270273AD2-016 GEN
Solar/Wind Harmer
5.491
972173AH1-669 GEN
Solar/Wind Harmer
9.078
270291AC1-194 GEN
Solar/Wind Harmer
7.015
241955AC1-078 GEN
Solar/Wind Helper
1.035
270432AC2-029 GEN
Solar/Wind Harmer
22.268
270269AC2-059
Solar/Wind Harmer
19.203
970879AG2-548 GEN
Solar/Wind Harmer
2.536
970879AG2-548 GEN
Solar/Wind Harmer
3.635
971073AG2-665 GEN
Solar/Wind Harmer
3.635
971073AG2-665 GEN
Solar/Wind Harmer
2.536
270263AC1-001 GEN
Solar/Wind Harmer
1.582
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.112
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.259
LAGNLTFEXP_LAGN->PJM
CLTF
0.095
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.484
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.079
CPLELTFEXP_CPLE->PJM
CLTF
0.166
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.018
LGEELTFEXP_LGEE->PJM
CLTF
0.015

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P2-3_MP-500-024_SRT-A


Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-024_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:134.01 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5081.52
MW Contribution:11.52
Bus #Bus NameTypeMW Contribution
270119AB2-067 GEN1
50/50
7.1
270120AB2-067 GEN2
50/50
7.1
24318905MLG2
50/50
7.059
270471AD2-092_GEN
Solar/Wind Harmer
4.477
946101AF1-275 GEN
Solar/Wind Harmer
1.818
942861AE2-305 GEN
Solar/Wind Harmer
9.105
970077AG2-063 GEN
Solar/Wind Harmer
6.25
270224U2-072_GEN2
Solar/Wind Harmer
2.287
270227U2-072_GEN3
Solar/Wind Harmer
2.287
270228U2-072_GEN4
Solar/Wind Harmer
2.287
270231U2-072_GEN5
Solar/Wind Harmer
2.287
938701AE1-092 GEN
Solar/Wind Harmer
23.86
964601AG1-323 GEN
Solar/Wind Harmer
3.665
964601AG1-323 GEN
Solar/Wind Harmer
1.705
270518AE2-148 GEN
Solar/Wind Harmer
13.911
253378AE2-206_GEN
Solar/Wind Harmer
4.016
276820AF1-078_GEN
Solar/Wind Harmer
1.784
972159AH1-661 GEN
Adder
1.111
972269AH1-719 GEN
Adder
2.557
25326509SID D
Adder
1.455
971199AH1-059 GEN
Solar/Wind Harmer
4.424
241960AC2-195 GEN
Solar/Wind Harmer
3.074
970879AG2-548 GEN
Solar/Wind Harmer
6.788
971073AG2-665 GEN
Solar/Wind Harmer
6.788
971073AG2-665 GEN
Solar/Wind Harmer
4.736
25326109MON D
Adder
1.447
25322209TAIT E
Adder
10.679
25322209TAIT E
Adder
10.439
253370AE2-315 SEC1
Adder
2.189
971201AH1-060 GEN
Solar/Wind Harmer
2.181
253394AE2-221_GEN
Solar/Wind Harmer
4.93
253398AE2-221_GEN2
Solar/Wind Harmer
4.93
246938BC-WTG3
Solar/Wind Harmer
4.31
246937BC-WTG2
Solar/Wind Harmer
4.237
253317AC1-085 GEN4
Solar/Wind Harmer
9.037
970611AG2-400 GEN
Solar/Wind Harmer
10.775
971231AH1-075 GEN
Solar/Wind Harmer
0.862
270007AE1-245 C
Solar/Wind Harmer
6.374
942801AE2-298 GEN
Solar/Wind Harmer
1.626
962581AG1-107 GEN
Solar/Wind Harmer
5.38
961491AF2-440 GEN
Solar/Wind Harmer
2.236
25183208HLCRTG
Solar/Wind Harmer
6.467
944541AF1-119 GEN
Solar/Wind Harmer
4.468
960971AF2-388 GEN
Solar/Wind Harmer
11.659
942221AE2-234 GEN
Solar/Wind Harmer
0.781
252519AF1-045_GEN
Solar/Wind Harmer
6.466
252516AE2-318_GEN
Solar/Wind Harmer
4.932
247621Y3-024
Adder
0.256
970883AG2-550 GEN
Solar/Wind Harmer
10.634
970885AG2-551 GEN
Solar/Wind Harmer
2.473
270201AC2-176 GEN
Solar/Wind Harmer
5.466
25194408D.CRK1
Adder
8.037
25194508D.CRK3
Adder
1.502
964611AG1-324 GEN
Solar/Wind Harmer
1.252
964611AG1-324 GEN
Solar/Wind Harmer
0.556
252509AD1-136 GEN
Solar/Wind Harmer
0.272
247620Y3-023
Adder
0.486
24728805RICHG1
Adder
3.981
24728905RICHG2
Adder
3.981
274770LINCOLN ;1U
Adder
8.715
274771LINCOLN ;2U
Adder
8.715
274808UNIV PK N;4U
Adder
5.14
274803UNIV PARK;6U
Adder
5.997
972259AH1-714 GEN
Adder
19.596
274674JOLIET 9 ;6U
Adder
15.776
274696ROCKY RD ;4P
Adder
11.59
274695ROCKY RD ;2P
Adder
11.323
274693ROCKY RD ;1P
Adder
11.211
274697ROCKY RD ;3P
Adder
3.076
23585401KL_K28_T16
Solar/Wind Helper
1.493
238120AE2-309 GEN
Solar/Wind Helper
0.528
238175AF1-290_GEN
Solar/Wind Helper
0.153
238169AE2-226 GEN1
Solar/Wind Helper
0.703
238170AE2-226 GEN2
Solar/Wind Helper
0.703
235020AA1-095 C
Solar/Wind Helper
0.053
23777901MDS_W4-102
Solar/Wind Helper
0.177
237002AB1-128_GEN
Solar/Wind Helper
0.445
237034AC2-136 C
Solar/Wind Helper
0.228
235063AE1-101 C2
Solar/Wind Helper
1.665
237001AB1-127_GEN
Solar/Wind Helper
0.443
23777801MSM_W1-116
Solar/Wind Helper
0.115
237025AB1-124 C
Solar/Wind Helper
0.165
237006AB1-125 GEN
Solar/Wind Helper
0.123
226929AD2-058 GEN
Solar/Wind Helper
0.099
205916AD1-020 GEN
Solar/Wind Helper
1.72
20390526W1-045 C
Solar/Wind Helper
0.351
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
233987AB2-037 GEN
Solar/Wind Helper
2.35
233933AB2-153 GEN
Solar/Wind Helper
0.233
232424Y1-079 C
Solar/Wind Helper
0.117
233944AB2-135 GEN
Solar/Wind Helper
0.591
233946AB2-136 GEN
Solar/Wind Helper
0.57
234036AF2-325 C
Solar/Wind Helper
0.042
233901CHERRYDALE C
Solar/Wind Helper
0.233
232408W1-005 C
Solar/Wind Helper
0.509
232410W1-006 C
Solar/Wind Helper
0.509
233939AC1-091 C
Solar/Wind Helper
0.351
233970AC1-092 C
Solar/Wind Helper
0.351
315651AD1-115 GEN
Solar/Wind Helper
0.787
316447AC1-158 HLD
Solar/Wind Helper
2.853
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.04
219921AF1-264
Solar/Wind Helper
0.051
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.083
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.19
20716928W4-060COL
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.016
20673828FLE_V3-070
Solar/Wind Helper
0.091
207442AE1-156 GEN
Solar/Wind Helper
0.327
20676128MHD_W3-029
Solar/Wind Helper
0.096
20671828STAW2-080
Solar/Wind Helper
0.027
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
207471AF2-354 C
Solar/Wind Helper
0.169
20674928WA_W3-044
Solar/Wind Helper
0.099
964851AG1-348 GEN
Solar/Wind Helper
0.081
20676228FRD_X1-012
Solar/Wind Helper
0.092
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.045
211065PSPA IPP
Solar/Wind Helper
0.152
211065PSPA IPP
Solar/Wind Helper
0.152
203955AF1-039 C O1
Solar/Wind Helper
0.33
970321AG2-212 GEN
Solar/Wind Harmer
4.981
962771AG1-126 GEN
Solar/Wind Harmer
41.173
270459AD2-067 GEN
Solar/Wind Harmer
10.252
961821AG1-024 GEN
Solar/Wind Harmer
10.408
270054AF2-122 C O1
Solar/Wind Harmer
3.995
972239AH1-704 GEN
Adder
2.671
270284AF1-227 GEN1
Solar/Wind Harmer
6.806
270286AF1-227 GEN2
Solar/Wind Harmer
2.518
270287AF1-227 GEN3
Solar/Wind Harmer
2.518
270520AE2-214 GEN
Solar/Wind Harmer
7.284
253383AE2-342_GEN
Solar/Wind Harmer
1.047
241973AD2-163_GEN1
Solar/Wind Harmer
2.334
943861AF1-054 GEN
Solar/Wind Harmer
4.494
943851AF1-053 GEN
Solar/Wind Harmer
2.172
945631AF1-228 GEN
Solar/Wind Harmer
5.47
270156DARBY CT1
Adder
10.432
270157DARBY CT2
Adder
10.407
270158DARBY CT3
Adder
10.24
270578AF1-285 GEN2
Solar/Wind Harmer
0.538
970689AG2-444 GEN
Solar/Wind Harmer
18.845
270432AC2-029 GEN
Solar/Wind Harmer
8.059
270302AB2-170 GEN
Solar/Wind Harmer
9.566
270317AD1-130_GEN
Solar/Wind Harmer
3.667
270269AC2-059
Solar/Wind Harmer
10.62
940611AE2-048 GEN
Solar/Wind Harmer
24.866
941391AE2-136 GEN
Solar/Wind Harmer
12.885
241972AD1-140 GEN
Solar/Wind Harmer
5.031
270340AC2-060 GEN
Solar/Wind Harmer
3.353
958581AF2-149 GEN
Solar/Wind Harmer
4.732
970179AG2-119 GEN
Solar/Wind Harmer
8.844
970879AG2-548 GEN
Solar/Wind Harmer
4.736
253372AE2-315 SEC3
Adder
2.071
253372AE2-315 SEC3
Adder
2.071
25306009OHH W.
Adder
3.141
253349AC2-067 GEN
Solar/Wind Harmer
5.421
253400AC2-068 GEN
Solar/Wind Harmer
2.18
957201AF2-014 GEN
Solar/Wind Harmer
4.91
270435AC2-044 GEN
Solar/Wind Harmer
2.165
965051AG1-369 GEN
Solar/Wind Harmer
5.38
965041AG1-368 GEN
Solar/Wind Harmer
10.749
247607V1-011 GEN
Solar/Wind Harmer
4.249
24729505KEY G4
Adder
6.948
963791AG1-232 GEN
Solar/Wind Harmer
14.455
971567AH1-282 GEN
Solar/Wind Harmer
16.053
966831AG1-554 GEN
Solar/Wind Harmer
1.28
971989AH1-539 GEN
Solar/Wind Harmer
13.846
270071AF1-092 GEN
Solar/Wind Harmer
16.048
971985AH1-537 GEN
Solar/Wind Harmer
19.051
958711AF2-162 GEN
Solar/Wind Harmer
1.079
270024AE2-089 GEN
Solar/Wind Harmer
5.004
965101AG1-375 GEN
Solar/Wind Harmer
10.653
270367AC2-061_GEN
Solar/Wind Harmer
3.388
971673AH1-337 GEN
Solar/Wind Harmer
4.893
971029AG2-637 GEN
Solar/Wind Harmer
15.954
252524AE2-267 GEN
Solar/Wind Harmer
1.677
25196408WSDLE3
Adder
9.382
25196308WSDLE2
Adder
9.3
25196208WSDLE1
Adder
9.277
25196708WSDLE6
Adder
9.254
25196508WSDLE4
Adder
9.021
270543AE2-219 C
Solar/Wind Harmer
5.445
961761AG1-017 GEN
Solar/Wind Harmer
0.455
945581AF1-223 GEN
Solar/Wind Harmer
4.819
944031AF1-071 GEN
Solar/Wind Harmer
1.067
270297AD1-101 GEN
Solar/Wind Harmer
2.953
25196108MFTGT2
Adder
1.605
25196108MFTGT2
Adder
1.491
274775LINCOLN ;6U
Adder
8.715
274776LINCOLN ;7U
Adder
8.715
274777LINCOLN ;8U
Adder
8.715
274814UNIV PK N;0U
Adder
5.208
274807UNIV PK N;3U
Adder
5.196
274805UNIV PK N;1U
Adder
5.174
274811UNIV PK N;7U
Adder
5.162
972037AH1-567 GEN1
Adder
0.188
274827FISK ;RP
Adder
7.977
972227AH1-698 GEN1
Adder
2.681
274687WILL CNTY;4U
Adder
28.653
274687WILL CNTY;4U
Adder
28.653
274675JOLIET 29;7U
Adder
31.445
274675JOLIET 29;7U
Adder
30.322
274731ELWOOD EC;2P
Adder
16.844
274733ELWOOD EC;3P
Adder
16.844
274735ELWOOD EC;4P
Adder
16.844
274728ELWOOD EC;5P
Adder
16.844
972203AH1-686 GEN
Adder
2.356
274746AC1-111 G10
Adder
5.705
274744AC1-111 GEN8
Adder
5.705
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238126S14_GEN_1
Solar/Wind Helper
0.832
238152AF2-075_GEN
Solar/Wind Helper
0.709
238208AF1-136 C
Solar/Wind Helper
0.221
23546401DTGZ2-030
Solar/Wind Helper
0.089
237085AD2-009_GEN
Solar/Wind Helper
1.655
3138216PACIFIC
Solar/Wind Helper
0.044
316411AF1-147_GEN1
Solar/Wind Helper
0.891
316415AF1-147_GEN2
Solar/Wind Helper
0.891
23750501ELLIOTTS
Solar/Wind Helper
0.644
959381AF2-229 GEN
Solar/Wind Helper
0.359
3141426STAFORD
Solar/Wind Helper
0.052
960921AF2-383 GEN
Solar/Wind Helper
0.182
205943AE1-185 GEN
Solar/Wind Helper
0.511
205932AD2-116_GEN
Solar/Wind Helper
0.511
205956AE1-196_GEN
Solar/Wind Helper
0.511
233935AB2-179 C
Solar/Wind Helper
1.273
232436AB1-176 C
Solar/Wind Helper
0.045
233923SMA
Solar/Wind Helper
0.962
233990AG1-397 GEN
Solar/Wind Helper
0.031
232432Z2-076 GEN
Solar/Wind Helper
0.067
234033AF1-007_GEN
Solar/Wind Helper
7.046
964001AG1-254 GEN
Solar/Wind Helper
0.959
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.115
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.08
203975AE1-071-GEN
Solar/Wind Helper
2.508
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.291
219620RIDERU C
Solar/Wind Helper
0.001
316164AC1-076 GEN
Solar/Wind Helper
1.099
20675528CPH_W2-050
Solar/Wind Helper
0.087
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
218524CNTRALGAS1 C
Solar/Wind Helper
0.161
966261AG1-495 GEN
Solar/Wind Helper
0.082
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20675928HOL_W4-097
Solar/Wind Helper
0.05
207484AF2-139 C O1
Solar/Wind Helper
0.084
20674828DL_W4-046
Solar/Wind Helper
0.008
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.137
20675128HRM_W1-127
Solar/Wind Helper
0.03
209116AE2-175 GEN
Solar/Wind Helper
1.786
270166AC1-044 GEN3
50/50
7.1
23559101PLEAS2
50/50
6.365
962761AG1-125 GEN
Solar/Wind Harmer
41.173
970149AG2-104 GEN
Solar/Wind Harmer
50.849
970155AG2-107 GEN
Solar/Wind Harmer
17.953
270349AD2-093_GEN
Solar/Wind Harmer
4.477
24721705FLATG2
Adder
24.144
270159DARBY CT4
Adder
10.266
970593AG2-378 GEN
Solar/Wind Harmer
2.315
270223U2-072_GEN1
Solar/Wind Harmer
2.287
270578AF1-285 GEN2
Solar/Wind Harmer
1.399
270391AF1-285 GEN3
Solar/Wind Harmer
1.399
253343AC1-166 GEN
Solar/Wind Harmer
1.243
253325AC1-069 GEN
Solar/Wind Harmer
1.199
270462AD2-086
Solar/Wind Harmer
7.958
971995AH1-542 GEN
Solar/Wind Harmer
12.515
270263AC1-001 GEN
Solar/Wind Harmer
1.179
25326309TAIT D
Adder
1.2
960071AF2-298 GEN
Solar/Wind Harmer
5.454
253370AE2-315 SEC1
Adder
2.189
253371AE2-315 SEC2
Adder
2.071
927014AC1-188 GEN
Solar/Wind Harmer
1.729
241813AF1-122_GEN
Solar/Wind Harmer
6.978
246936BC-WTG1
Solar/Wind Harmer
4.237
270489AE1-102 GEN1
Solar/Wind Harmer
1.407
965421AG1-410 GEN
Solar/Wind Harmer
32.464
960001AF2-291 GEN
Solar/Wind Harmer
3.264
253432AC1-085 GEN2
Solar/Wind Harmer
0.289
946171AF1-282 GEN
Solar/Wind Harmer
10.789
247521TR3_G114
Solar/Wind Harmer
3.623
270246TR4_N_V150
Solar/Wind Harmer
0.916
965011AG1-365 GEN
Solar/Wind Harmer
10.775
24695305TIMB G C
Solar/Wind Harmer
5.916
965651AG1-433 GEN
Solar/Wind Harmer
5.83
958861AF2-177 GEN
Solar/Wind Harmer
11.644
247536S-71 GEN
Solar/Wind Harmer
4.305
25194608D.CRK4
Adder
1.747
945371AF1-202 GEN
Solar/Wind Harmer
7.414
252507AC2-088 GEN
Solar/Wind Harmer
1.904
270063AE2-323 C
Solar/Wind Harmer
2.336
25196808ZIMRHP
Adder
80.055
24639705ELKHART HY
Adder
0.162
25196008MFTGT1
Adder
1.456
274751CRETE EC ;1U
Adder
8.515
274754CRETE EC ;4U
Adder
8.515
274773LINCOLN ;4U
Adder
8.715
274774LINCOLN ;5U
Adder
8.715
274723RIVER EC ;12
Adder
18.501
274812UNIV PK N;8U
Adder
5.162
24728605AND G2
Adder
3.945
274801UNIV PARK;4U
Adder
5.993
274676JOLIET 29;8U
Adder
31.445
274732ELWOOD EC;7P
Adder
16.844
274674JOLIET 9 ;6U
Adder
15.776
274745AC1-111 GEN9
Adder
5.705
970091AG2-072 GEN
Adder
78.03
316095T157 G97
Solar/Wind Helper
1.508
23583801GRNGAP
Solar/Wind Helper
5.618
238185AF2-356 C
Solar/Wind Helper
2.662
238108AE1-109 GEN1
Solar/Wind Helper
0.114
235054AD2-180 GEN
Solar/Wind Helper
2.043
235531U2-073 GEN
Solar/Wind Helper
3.301
238117U2-030
Solar/Wind Helper
0.344
238147AE2-230_GEN1
Solar/Wind Helper
0.496
238149AF1-291A_GEN
Solar/Wind Helper
0.142
23751201ROTHROCK
Solar/Wind Helper
0.832
23562501BACKB
Solar/Wind Helper
1.017
237061AD1-155 GEN
Solar/Wind Helper
0.053
238221AF1-254 C O1
Solar/Wind Helper
0.275
24318805MLG1
50/50
10.158
23559001PLEAS1
50/50
6.365
270051AF1-062 GEN
50/50
11.843
270475AD2-096_GEN
50/50
7.165
970153AG2-106 GEN
Solar/Wind Harmer
17.953
961921AG1-034 GEN
Solar/Wind Harmer
15.612
24721905FLATG4
Adder
24.144
241955AC1-078 GEN
Solar/Wind Harmer
8.824
241974AD2-163_GEN2
Solar/Wind Harmer
2.334
942051AE2-217 GEN
Solar/Wind Harmer
21.08
960801AF2-371 GEN
Solar/Wind Harmer
2.95
964871AG1-351 GEN
Solar/Wind Harmer
2.037
970605AG2-385 GEN
Solar/Wind Harmer
6.25
942871AE2-306 GEN
Solar/Wind Harmer
1.049
270391AF1-285 GEN3
Solar/Wind Harmer
0.538
253338AC1-165 GEN
Solar/Wind Harmer
1.243
253333AC1-068 GEN
Solar/Wind Harmer
1.199
270485AE1-090_GEN
Solar/Wind Harmer
0.692
270273AD2-016 GEN
Solar/Wind Harmer
3.037
972173AH1-669 GEN
Solar/Wind Harmer
5.679
253415AE1-040 GEN
Solar/Wind Harmer
1.251
270291AC1-194 GEN
Solar/Wind Harmer
11.751
253303V4-073 C
Solar/Wind Harmer
0.127
253370AE2-315 SEC1
Adder
2.189
253371AE2-315 SEC2
Adder
2.071
957541AF2-048 GEN
Solar/Wind Harmer
1.724
970065AG2-057 GEN
Solar/Wind Harmer
1.09
253406AD2-031_GEN
Solar/Wind Harmer
1.391
270491AE1-102 GEN2
Solar/Wind Harmer
1.407
971191AH1-055 GEN
Solar/Wind Harmer
23.759
253316AC1-085 GEN3
Solar/Wind Harmer
9.037
253433AC1-085 GEN1
Solar/Wind Harmer
5.737
946181AF1-283 GEN
Solar/Wind Harmer
14.025
270191TR4_S_V150
Solar/Wind Harmer
3.232
270247TR4_N_V136
Solar/Wind Harmer
0.916
959331AF2-224 GEN
Solar/Wind Harmer
10.775
965021AG1-366 GEN
Solar/Wind Harmer
2.506
270377AD1-106 GEN
Solar/Wind Harmer
6.65
958091AF2-103 GEN
Solar/Wind Harmer
0.174
270588AE1-091_GEN
Solar/Wind Harmer
11.804
944531AF1-118 GEN
Solar/Wind Harmer
37.541
270043AE2-236 GEN
Solar/Wind Harmer
5.893
971617AH1-308 GEN
Solar/Wind Harmer
6.198
270258AD1-119 GEN
Solar/Wind Harmer
2.97
25196608WSDLE5
Adder
9.114
962031AG1-047 GEN
Solar/Wind Harmer
3.214
957741AF2-068 GEN
Solar/Wind Harmer
15.949
252510AF1-249 C
Solar/Wind Harmer
0.444
25194608D.CRK4
Adder
1.747
270222AC2-111 GEN
Solar/Wind Harmer
8.657
970031AG2-029 GEN
Solar/Wind Harmer
31.849
270044AE2-322 C
Solar/Wind Harmer
1.394
270404AC1-167 GEN
Solar/Wind Harmer
1.161
24642205MAYFLWER
Adder
0.667
25196008MFTGT1
Adder
1.411
247604X1-042
Adder
0.435
274752CRETE EC ;2U
Adder
8.515
274753CRETE EC ;3U
Adder
8.515
274772LINCOLN ;3U
Adder
8.715
274724RIVER EC ;11
Adder
18.285
274802UNIV PARK;5U
Adder
5.997
24728705AND G3
Adder
8.251
24728505AND G1
Adder
3.945
274826FISK ;BP
Adder
11.256
274800UNIV PARK;3U
Adder
5.993
235067AD1-061 GEN
Solar/Wind Helper
0.498
23751101LEADS_P59
Solar/Wind Helper
1.424
237030AB1-096 C
Solar/Wind Helper
0.071
3141196NOKESVL
Solar/Wind Helper
1.034
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.347
223402AF1-300 C
Solar/Wind Helper
0.369
205917AD1-020 ES
Solar/Wind Helper
0.37
233918AB1-142 GEN
Solar/Wind Helper
0.504
233982AB2-133 GEN
Solar/Wind Helper
0.359
233994AC2-023 GEN
Solar/Wind Helper
0.965
233996TM1833_GEN
Solar/Wind Helper
0.262
233997TMININ_4.2
Solar/Wind Helper
0.262
232406W1-004 FULL
Solar/Wind Helper
0.509
233940AF2-379 C
Solar/Wind Helper
0.062
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.233
233971AC1-093 C
Solar/Wind Helper
0.359
230430AE1-229_GEN
Solar/Wind Helper
3.385
316044AC1-158 PL1
Solar/Wind Helper
1.296
316450AC1-158 RIC
Solar/Wind Helper
0.346
230415AB2-049 C
Solar/Wind Helper
0.03
228729W2-030 C
Solar/Wind Helper
0.111
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.15
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
219348LDSOLAR C
Solar/Wind Helper
0.115
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.063
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.354
219276PARKLANDSO C
Solar/Wind Helper
0.09
20714528FRN_Y2-051
Solar/Wind Helper
0.057
20720528MAN_W1-024
Solar/Wind Helper
0.028
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.027
219249CENTRALDIV C
Solar/Wind Helper
0.01
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.089
963161AG1-165 GEN
Solar/Wind Helper
0.441
970245AG2-165 GEN
Solar/Wind Harmer
4.981
972038AH1-567 GEN2
Adder
0.375
972228AH1-698 GEN2
Adder
3.807
274676JOLIET 29;8U
Adder
30.322
274729ELWOOD EC;1P
Adder
16.844
274730ELWOOD EC;6P
Adder
16.844
274734ELWOOD EC;8P
Adder
16.844
274736ELWOOD EC;9P
Adder
16.844
274682WAUKEGAN ;7U
Adder
9.773
964991AG1-363 GEN
Solar/Wind Helper
5.152
316097T157 G90
Solar/Wind Helper
1.508
23750701CROSSCHOOL
Solar/Wind Helper
1.51
238118U2-030_1
Solar/Wind Helper
0.344
238127S14_GEN_2
Solar/Wind Helper
0.832
238148AE2-230_GEN2
Solar/Wind Helper
0.498
237080AD1-060 GEN
Solar/Wind Helper
0.343
237038AE2-054 C
Solar/Wind Helper
0.273
235062AE1-101 C1
Solar/Wind Helper
1.665
23779801AA1-109
Solar/Wind Helper
0.194
237048AF1-022 C
Solar/Wind Helper
0.179
223401AF1-299 GEN
Solar/Wind Helper
0.369
316006AB2-029 C
Solar/Wind Helper
0.117
966131AG1-482 GEN
Solar/Wind Helper
0.078
233930AB2-032 GEN
Solar/Wind Helper
0.382
233915AB1-141 GEN
Solar/Wind Helper
0.504
232422X3-066 FULL
Solar/Wind Helper
0.115
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
233998TM1NIN_3.36
Solar/Wind Helper
0.262
232404W1-003 C
Solar/Wind Helper
0.509
232428Y3-058 C
Solar/Wind Helper
0.339
232434Z2-077 GEN
Solar/Wind Helper
0.127
233954AC2-188 GEN
Solar/Wind Helper
0.233
233950AC2-186 GEN
Solar/Wind Helper
0.117
233972AC1-094 C
Solar/Wind Helper
0.303
230511AF1-262
Solar/Wind Helper
0.015
316045AC1-158 PL2
Solar/Wind Helper
4.149
230434AG1-499 GEN
Solar/Wind Helper
0.231
228728W1-130C
Solar/Wind Helper
0.054
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219904AC1-010 C
Solar/Wind Helper
0.061
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.132
20720728JCB_W1-129
Solar/Wind Helper
0.057
207445AB1-138_GEN
Solar/Wind Helper
0.105
316254AC1-120 GEN1
Solar/Wind Helper
1.062
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.311
20715228NPK_W1-113
Solar/Wind Helper
0.078
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.497
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.023
207439AE1-081 C O1
Solar/Wind Helper
0.019
207437AD2-070 GEN
Solar/Wind Helper
0.138
207518AF1-320_GEN
Solar/Wind Helper
1.577
20671928W4-073
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.03
202652Y1-033 WT C
Solar/Wind Helper
0.5
961301AF2-421 GEN
Solar/Wind Helper
0.441
963151AG1-164 GEN
Solar/Wind Helper
0.441
970513AG2-328 GEN
Solar/Wind Harmer
4.981
970517AG2-330 GEN
Solar/Wind Harmer
4.518
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.671
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.268
MECLTFEXP_MEC->PJM
CLTF
15.978
SIGELTFEXP_SIGE->PJM
CLTF
0.507
LAGNLTFEXP_LAGN->PJM
CLTF
14.924
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.891
TVALTFEXP_TVA->PJM
CLTF
7.337
CPLELTFEXP_CPLE->PJM
CLTF
0.647
CBM West 2LTFEXP_CBM-W2->PJM
CBM
113.418
NYPJM->LTFIMP_NY
CLTF
4.819
LGEELTFEXP_LGEE->PJM
CLTF
6.781
WECLTFEXP_WEC->PJM
CLTF
3.842
AG2-052LTFEXP_AG2-052->PJM
LTF
0.241
AH1-155LTFEXP_AH1-155->PJM
LTF
0.361

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P2-3_MP-500-025_SRT-A


Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-025_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:133.21 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5051.2
MW Contribution:11.51
Bus #Bus NameTypeMW Contribution
270119AB2-067 GEN1
50/50
7.072
270120AB2-067 GEN2
50/50
7.072
24318905MLG2
50/50
7.067
270471AD2-092_GEN
Solar/Wind Harmer
4.467
946101AF1-275 GEN
Solar/Wind Harmer
1.815
942861AE2-305 GEN
Solar/Wind Harmer
9.088
970077AG2-063 GEN
Solar/Wind Harmer
6.239
270224U2-072_GEN2
Solar/Wind Harmer
2.282
270227U2-072_GEN3
Solar/Wind Harmer
2.282
270228U2-072_GEN4
Solar/Wind Harmer
2.282
270231U2-072_GEN5
Solar/Wind Harmer
2.282
938701AE1-092 GEN
Solar/Wind Harmer
23.824
964601AG1-323 GEN
Solar/Wind Harmer
3.66
964601AG1-323 GEN
Solar/Wind Harmer
1.702
270518AE2-148 GEN
Solar/Wind Harmer
13.886
972269AH1-719 GEN
Adder
2.575
972159AH1-661 GEN
Adder
1.116
253378AE2-206_GEN
Solar/Wind Harmer
4.007
276820AF1-078_GEN
Solar/Wind Harmer
1.78
971199AH1-059 GEN
Solar/Wind Harmer
4.428
241960AC2-195 GEN
Solar/Wind Harmer
3.072
25326509SID D
Adder
1.452
970879AG2-548 GEN
Solar/Wind Harmer
6.777
971073AG2-665 GEN
Solar/Wind Harmer
6.777
971073AG2-665 GEN
Solar/Wind Harmer
4.728
25326109MON D
Adder
1.444
25322209TAIT E
Adder
10.654
25322209TAIT E
Adder
10.414
253370AE2-315 SEC1
Adder
2.184
971201AH1-060 GEN
Solar/Wind Harmer
2.179
253394AE2-221_GEN
Solar/Wind Harmer
4.918
253398AE2-221_GEN2
Solar/Wind Harmer
4.918
246938BC-WTG3
Solar/Wind Harmer
4.299
246937BC-WTG2
Solar/Wind Harmer
4.226
971231AH1-075 GEN
Solar/Wind Harmer
0.861
253317AC1-085 GEN4
Solar/Wind Harmer
9.014
970611AG2-400 GEN
Solar/Wind Harmer
10.746
270007AE1-245 C
Solar/Wind Harmer
6.359
942801AE2-298 GEN
Solar/Wind Harmer
1.622
962581AG1-107 GEN
Solar/Wind Harmer
5.366
961491AF2-440 GEN
Solar/Wind Harmer
2.23
25183208HLCRTG
Solar/Wind Harmer
6.45
944541AF1-119 GEN
Solar/Wind Harmer
4.455
960971AF2-388 GEN
Solar/Wind Harmer
11.625
942221AE2-234 GEN
Solar/Wind Harmer
0.779
252519AF1-045_GEN
Solar/Wind Harmer
6.448
252516AE2-318_GEN
Solar/Wind Harmer
4.919
247621Y3-024
Adder
0.256
970883AG2-550 GEN
Solar/Wind Harmer
10.605
970885AG2-551 GEN
Solar/Wind Harmer
2.466
270201AC2-176 GEN
Solar/Wind Harmer
5.45
25194408D.CRK1
Adder
8.014
25194508D.CRK3
Adder
1.498
964611AG1-324 GEN
Solar/Wind Harmer
1.249
964611AG1-324 GEN
Solar/Wind Harmer
0.554
252509AD1-136 GEN
Solar/Wind Harmer
0.271
247620Y3-023
Adder
0.484
24728805RICHG1
Adder
3.969
24728905RICHG2
Adder
3.969
274770LINCOLN ;1U
Adder
8.688
274771LINCOLN ;2U
Adder
8.688
274808UNIV PK N;4U
Adder
5.124
274803UNIV PARK;6U
Adder
5.978
972259AH1-714 GEN
Adder
19.535
274674JOLIET 9 ;6U
Adder
15.727
274696ROCKY RD ;4P
Adder
11.554
274695ROCKY RD ;2P
Adder
11.287
274693ROCKY RD ;1P
Adder
11.176
274697ROCKY RD ;3P
Adder
3.066
23585401KL_K28_T16
Solar/Wind Helper
1.485
238120AE2-309 GEN
Solar/Wind Helper
0.526
238175AF1-290_GEN
Solar/Wind Helper
0.153
238169AE2-226 GEN1
Solar/Wind Helper
0.702
238170AE2-226 GEN2
Solar/Wind Helper
0.702
235020AA1-095 C
Solar/Wind Helper
0.053
23777901MDS_W4-102
Solar/Wind Helper
0.177
237002AB1-128_GEN
Solar/Wind Helper
0.444
237034AC2-136 C
Solar/Wind Helper
0.227
235063AE1-101 C2
Solar/Wind Helper
1.661
237001AB1-127_GEN
Solar/Wind Helper
0.442
23777801MSM_W1-116
Solar/Wind Helper
0.114
237025AB1-124 C
Solar/Wind Helper
0.164
237006AB1-125 GEN
Solar/Wind Helper
0.123
226929AD2-058 GEN
Solar/Wind Helper
0.099
205916AD1-020 GEN
Solar/Wind Helper
1.715
20390526W1-045 C
Solar/Wind Helper
0.35
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
233987AB2-037 GEN
Solar/Wind Helper
2.344
233933AB2-153 GEN
Solar/Wind Helper
0.233
232424Y1-079 C
Solar/Wind Helper
0.116
233944AB2-135 GEN
Solar/Wind Helper
0.589
233946AB2-136 GEN
Solar/Wind Helper
0.569
234036AF2-325 C
Solar/Wind Helper
0.042
233901CHERRYDALE C
Solar/Wind Helper
0.233
232408W1-005 C
Solar/Wind Helper
0.508
232410W1-006 C
Solar/Wind Helper
0.508
233939AC1-091 C
Solar/Wind Helper
0.35
233970AC1-092 C
Solar/Wind Helper
0.35
315651AD1-115 GEN
Solar/Wind Helper
0.785
316447AC1-158 HLD
Solar/Wind Helper
2.848
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.04
219921AF1-264
Solar/Wind Helper
0.051
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.082
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.19
20716928W4-060COL
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.016
20673828FLE_V3-070
Solar/Wind Helper
0.091
207442AE1-156 GEN
Solar/Wind Helper
0.326
20676128MHD_W3-029
Solar/Wind Helper
0.096
20671828STAW2-080
Solar/Wind Helper
0.027
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
207471AF2-354 C
Solar/Wind Helper
0.169
20674928WA_W3-044
Solar/Wind Helper
0.098
20676228FRD_X1-012
Solar/Wind Helper
0.092
964851AG1-348 GEN
Solar/Wind Helper
0.081
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.045
211065PSPA IPP
Solar/Wind Helper
0.152
211065PSPA IPP
Solar/Wind Helper
0.152
970321AG2-212 GEN
Solar/Wind Harmer
3.728
962771AG1-126 GEN
Solar/Wind Harmer
41.012
972239AH1-704 GEN
Adder
2.683
270459AD2-067 GEN
Solar/Wind Harmer
10.243
961821AG1-024 GEN
Solar/Wind Harmer
10.399
270054AF2-122 C O1
Solar/Wind Harmer
3.993
270520AE2-214 GEN
Solar/Wind Harmer
7.274
270284AF1-227 GEN1
Solar/Wind Harmer
6.791
270286AF1-227 GEN2
Solar/Wind Harmer
2.512
270287AF1-227 GEN3
Solar/Wind Harmer
2.512
253383AE2-342_GEN
Solar/Wind Harmer
1.045
241973AD2-163_GEN1
Solar/Wind Harmer
2.33
945631AF1-228 GEN
Solar/Wind Harmer
5.461
943861AF1-054 GEN
Solar/Wind Harmer
4.486
943851AF1-053 GEN
Solar/Wind Harmer
2.168
270156DARBY CT1
Adder
10.416
270157DARBY CT2
Adder
10.391
270158DARBY CT3
Adder
10.225
970689AG2-444 GEN
Solar/Wind Harmer
18.82
270578AF1-285 GEN2
Solar/Wind Harmer
0.537
270432AC2-029 GEN
Solar/Wind Harmer
8.046
270302AB2-170 GEN
Solar/Wind Harmer
9.546
270317AD1-130_GEN
Solar/Wind Harmer
3.66
940611AE2-048 GEN
Solar/Wind Harmer
25.033
941391AE2-136 GEN
Solar/Wind Harmer
12.972
270269AC2-059
Solar/Wind Harmer
10.602
241972AD1-140 GEN
Solar/Wind Harmer
5.021
958581AF2-149 GEN
Solar/Wind Harmer
4.736
970179AG2-119 GEN
Solar/Wind Harmer
8.837
270340AC2-060 GEN
Solar/Wind Harmer
3.346
970879AG2-548 GEN
Solar/Wind Harmer
4.728
253372AE2-315 SEC3
Adder
2.066
253372AE2-315 SEC3
Adder
2.066
25306009OHH W.
Adder
3.134
253349AC2-067 GEN
Solar/Wind Harmer
5.408
253400AC2-068 GEN
Solar/Wind Harmer
2.175
957201AF2-014 GEN
Solar/Wind Harmer
4.898
270435AC2-044 GEN
Solar/Wind Harmer
2.16
965051AG1-369 GEN
Solar/Wind Harmer
5.366
965041AG1-368 GEN
Solar/Wind Harmer
10.722
247607V1-011 GEN
Solar/Wind Harmer
4.239
971567AH1-282 GEN
Solar/Wind Harmer
16.059
966831AG1-554 GEN
Solar/Wind Harmer
1.279
971989AH1-539 GEN
Solar/Wind Harmer
13.833
24729505KEY G4
Adder
6.928
963791AG1-232 GEN
Solar/Wind Harmer
14.415
270071AF1-092 GEN
Solar/Wind Harmer
16.001
971985AH1-537 GEN
Solar/Wind Harmer
18.998
958711AF2-162 GEN
Solar/Wind Harmer
1.076
270024AE2-089 GEN
Solar/Wind Harmer
4.99
270367AC2-061_GEN
Solar/Wind Harmer
3.379
965101AG1-375 GEN
Solar/Wind Harmer
10.622
971673AH1-337 GEN
Solar/Wind Harmer
4.88
252524AE2-267 GEN
Solar/Wind Harmer
1.673
971029AG2-637 GEN
Solar/Wind Harmer
15.909
25196408WSDLE3
Adder
9.356
25196308WSDLE2
Adder
9.275
25196208WSDLE1
Adder
9.252
25196708WSDLE6
Adder
9.228
25196508WSDLE4
Adder
8.996
270543AE2-219 C
Solar/Wind Harmer
5.43
961761AG1-017 GEN
Solar/Wind Harmer
0.454
945581AF1-223 GEN
Solar/Wind Harmer
4.805
270297AD1-101 GEN
Solar/Wind Harmer
2.947
944031AF1-071 GEN
Solar/Wind Harmer
1.064
25196108MFTGT2
Adder
1.601
25196108MFTGT2
Adder
1.486
274775LINCOLN ;6U
Adder
8.688
274776LINCOLN ;7U
Adder
8.688
274777LINCOLN ;8U
Adder
8.688
274814UNIV PK N;0U
Adder
5.192
274807UNIV PK N;3U
Adder
5.18
274805UNIV PK N;1U
Adder
5.158
274811UNIV PK N;7U
Adder
5.147
972037AH1-567 GEN1
Adder
0.188
274827FISK ;RP
Adder
7.953
972227AH1-698 GEN1
Adder
2.673
274687WILL CNTY;4U
Adder
28.564
274687WILL CNTY;4U
Adder
28.564
274675JOLIET 29;7U
Adder
31.348
274675JOLIET 29;7U
Adder
30.228
274731ELWOOD EC;2P
Adder
16.792
274733ELWOOD EC;3P
Adder
16.792
274735ELWOOD EC;4P
Adder
16.792
274728ELWOOD EC;5P
Adder
16.792
972203AH1-686 GEN
Adder
2.344
274746AC1-111 G10
Adder
5.687
274744AC1-111 GEN8
Adder
5.687
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238126S14_GEN_1
Solar/Wind Helper
0.829
238152AF2-075_GEN
Solar/Wind Helper
0.708
238208AF1-136 C
Solar/Wind Helper
0.22
23546401DTGZ2-030
Solar/Wind Helper
0.089
237085AD2-009_GEN
Solar/Wind Helper
1.651
3138216PACIFIC
Solar/Wind Helper
0.044
316411AF1-147_GEN1
Solar/Wind Helper
0.889
316415AF1-147_GEN2
Solar/Wind Helper
0.889
23750501ELLIOTTS
Solar/Wind Helper
0.64
959381AF2-229 GEN
Solar/Wind Helper
0.358
3141426STAFORD
Solar/Wind Helper
0.052
960921AF2-383 GEN
Solar/Wind Helper
0.182
205943AE1-185 GEN
Solar/Wind Helper
0.51
205932AD2-116_GEN
Solar/Wind Helper
0.509
205956AE1-196_GEN
Solar/Wind Helper
0.509
233935AB2-179 C
Solar/Wind Helper
1.27
232436AB1-176 C
Solar/Wind Helper
0.044
233923SMA
Solar/Wind Helper
0.959
233990AG1-397 GEN
Solar/Wind Helper
0.03
234033AF1-007_GEN
Solar/Wind Helper
7.028
232432Z2-076 GEN
Solar/Wind Helper
0.067
964001AG1-254 GEN
Solar/Wind Helper
0.957
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.115
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.08
203975AE1-071-GEN
Solar/Wind Helper
2.501
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.29
219620RIDERU C
Solar/Wind Helper
0.001
316164AC1-076 GEN
Solar/Wind Helper
1.097
20675528CPH_W2-050
Solar/Wind Helper
0.087
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
218524CNTRALGAS1 C
Solar/Wind Helper
0.161
966261AG1-495 GEN
Solar/Wind Helper
0.081
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20675928HOL_W4-097
Solar/Wind Helper
0.05
207484AF2-139 C O1
Solar/Wind Helper
0.084
20674828DL_W4-046
Solar/Wind Helper
0.008
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.137
20675128HRM_W1-127
Solar/Wind Helper
0.03
209116AE2-175 GEN
Solar/Wind Helper
1.781
270166AC1-044 GEN3
50/50
7.072
23559101PLEAS2
50/50
6.183
962761AG1-125 GEN
Solar/Wind Harmer
41.012
970149AG2-104 GEN
Solar/Wind Harmer
50.65
970155AG2-107 GEN
Solar/Wind Harmer
17.883
270349AD2-093_GEN
Solar/Wind Harmer
4.467
24721705FLATG2
Adder
23.989
270159DARBY CT4
Adder
10.25
970593AG2-378 GEN
Solar/Wind Harmer
2.311
270223U2-072_GEN1
Solar/Wind Harmer
2.282
270578AF1-285 GEN2
Solar/Wind Harmer
1.396
270391AF1-285 GEN3
Solar/Wind Harmer
1.396
253343AC1-166 GEN
Solar/Wind Harmer
1.241
253325AC1-069 GEN
Solar/Wind Harmer
1.197
270462AD2-086
Solar/Wind Harmer
7.941
971995AH1-542 GEN
Solar/Wind Harmer
12.502
270263AC1-001 GEN
Solar/Wind Harmer
1.177
25326309TAIT D
Adder
1.197
960071AF2-298 GEN
Solar/Wind Harmer
5.441
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.066
241813AF1-122_GEN
Solar/Wind Harmer
6.974
927014AC1-188 GEN
Solar/Wind Harmer
1.725
270510AE1-227 GEN1
Solar/Wind Harmer
2.689
246936BC-WTG1
Solar/Wind Harmer
4.226
270489AE1-102 GEN1
Solar/Wind Harmer
1.404
965421AG1-410 GEN
Solar/Wind Harmer
32.386
960001AF2-291 GEN
Solar/Wind Harmer
3.255
253432AC1-085 GEN2
Solar/Wind Harmer
0.288
946171AF1-282 GEN
Solar/Wind Harmer
10.761
247521TR3_G114
Solar/Wind Harmer
3.613
270246TR4_N_V150
Solar/Wind Harmer
0.914
965011AG1-365 GEN
Solar/Wind Harmer
10.746
24695305TIMB G C
Solar/Wind Harmer
5.901
965651AG1-433 GEN
Solar/Wind Harmer
5.813
958861AF2-177 GEN
Solar/Wind Harmer
11.61
247536S-71 GEN
Solar/Wind Harmer
4.293
25194608D.CRK4
Adder
1.742
945371AF1-202 GEN
Solar/Wind Harmer
7.392
252507AC2-088 GEN
Solar/Wind Harmer
1.899
270063AE2-323 C
Solar/Wind Harmer
2.33
25196808ZIMRHP
Adder
79.831
24639705ELKHART HY
Adder
0.161
25196008MFTGT1
Adder
1.452
274751CRETE EC ;1U
Adder
8.489
274754CRETE EC ;4U
Adder
8.489
274773LINCOLN ;4U
Adder
8.688
274774LINCOLN ;5U
Adder
8.688
274723RIVER EC ;12
Adder
18.445
274812UNIV PK N;8U
Adder
5.147
24728605AND G2
Adder
3.933
274801UNIV PARK;4U
Adder
5.975
274676JOLIET 29;8U
Adder
31.348
274732ELWOOD EC;7P
Adder
16.792
274674JOLIET 9 ;6U
Adder
15.727
274745AC1-111 GEN9
Adder
5.687
970091AG2-072 GEN
Adder
77.755
316095T157 G97
Solar/Wind Helper
1.505
23583801GRNGAP
Solar/Wind Helper
5.606
238185AF2-356 C
Solar/Wind Helper
2.651
238108AE1-109 GEN1
Solar/Wind Helper
0.114
235054AD2-180 GEN
Solar/Wind Helper
2.034
235531U2-073 GEN
Solar/Wind Helper
3.288
238117U2-030
Solar/Wind Helper
0.342
238147AE2-230_GEN1
Solar/Wind Helper
0.495
238149AF1-291A_GEN
Solar/Wind Helper
0.141
23751201ROTHROCK
Solar/Wind Helper
0.826
23562501BACKB
Solar/Wind Helper
1.01
237061AD1-155 GEN
Solar/Wind Helper
0.053
238221AF1-254 C O1
Solar/Wind Helper
0.275
235067AD1-061 GEN
Solar/Wind Helper
0.496
23751101LEADS_P59
Solar/Wind Helper
1.41
237030AB1-096 C
Solar/Wind Helper
0.071
3141196NOKESVL
Solar/Wind Helper
1.032
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.346
223402AF1-300 C
Solar/Wind Helper
0.368
205917AD1-020 ES
Solar/Wind Helper
0.369
233982AB2-133 GEN
Solar/Wind Helper
0.358
233918AB1-142 GEN
Solar/Wind Helper
0.503
233994AC2-023 GEN
Solar/Wind Helper
0.962
233996TM1833_GEN
Solar/Wind Helper
0.262
233997TMININ_4.2
Solar/Wind Helper
0.262
232406W1-004 FULL
Solar/Wind Helper
0.508
233940AF2-379 C
Solar/Wind Helper
0.062
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.233
233971AC1-093 C
Solar/Wind Helper
0.358
316044AC1-158 PL1
Solar/Wind Helper
1.294
316450AC1-158 RIC
Solar/Wind Helper
0.345
230430AE1-229_GEN
Solar/Wind Helper
3.376
230415AB2-049 C
Solar/Wind Helper
0.03
228729W2-030 C
Solar/Wind Helper
0.111
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.15
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
219348LDSOLAR C
Solar/Wind Helper
0.115
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.063
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.353
219276PARKLANDSO C
Solar/Wind Helper
0.089
20714528FRN_Y2-051
Solar/Wind Helper
0.057
20720528MAN_W1-024
Solar/Wind Helper
0.028
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.027
219249CENTRALDIV C
Solar/Wind Helper
0.01
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.089
970245AG2-165 GEN
Solar/Wind Harmer
3.728
24318805MLG1
50/50
10.115
23559001PLEAS1
50/50
6.183
270051AF1-062 GEN
50/50
11.828
270475AD2-096_GEN
50/50
7.148
970153AG2-106 GEN
Solar/Wind Harmer
17.883
961921AG1-034 GEN
Solar/Wind Harmer
15.599
24721905FLATG4
Adder
23.989
241955AC1-078 GEN
Solar/Wind Harmer
8.811
241974AD2-163_GEN2
Solar/Wind Harmer
2.33
942051AE2-217 GEN
Solar/Wind Harmer
21.044
960801AF2-371 GEN
Solar/Wind Harmer
2.947
964871AG1-351 GEN
Solar/Wind Harmer
2.035
970605AG2-385 GEN
Solar/Wind Harmer
6.239
942871AE2-306 GEN
Solar/Wind Harmer
1.047
270391AF1-285 GEN3
Solar/Wind Harmer
0.537
253338AC1-165 GEN
Solar/Wind Harmer
1.241
253333AC1-068 GEN
Solar/Wind Harmer
1.197
270485AE1-090_GEN
Solar/Wind Harmer
0.69
270273AD2-016 GEN
Solar/Wind Harmer
3.032
972173AH1-669 GEN
Solar/Wind Harmer
5.669
253415AE1-040 GEN
Solar/Wind Harmer
1.248
270291AC1-194 GEN
Solar/Wind Harmer
11.736
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.066
970065AG2-057 GEN
Solar/Wind Harmer
1.09
957541AF2-048 GEN
Solar/Wind Harmer
1.72
270512AE1-227 GEN2
Solar/Wind Harmer
2.283
253406AD2-031_GEN
Solar/Wind Harmer
1.388
270491AE1-102 GEN2
Solar/Wind Harmer
1.404
971191AH1-055 GEN
Solar/Wind Harmer
23.693
270377AD1-106 GEN
Solar/Wind Harmer
6.649
253316AC1-085 GEN3
Solar/Wind Harmer
9.014
253433AC1-085 GEN1
Solar/Wind Harmer
5.722
946181AF1-283 GEN
Solar/Wind Harmer
13.99
270191TR4_S_V150
Solar/Wind Harmer
3.224
270247TR4_N_V136
Solar/Wind Harmer
0.914
959331AF2-224 GEN
Solar/Wind Harmer
10.746
965021AG1-366 GEN
Solar/Wind Harmer
2.499
958091AF2-103 GEN
Solar/Wind Harmer
0.173
270588AE1-091_GEN
Solar/Wind Harmer
11.789
944531AF1-118 GEN
Solar/Wind Harmer
37.432
270043AE2-236 GEN
Solar/Wind Harmer
5.876
270258AD1-119 GEN
Solar/Wind Harmer
2.963
971617AH1-308 GEN
Solar/Wind Harmer
6.181
25196608WSDLE5
Adder
9.089
962031AG1-047 GEN
Solar/Wind Harmer
3.205
252510AF1-249 C
Solar/Wind Harmer
0.443
957741AF2-068 GEN
Solar/Wind Harmer
15.904
25194608D.CRK4
Adder
1.742
270222AC2-111 GEN
Solar/Wind Harmer
8.632
970031AG2-029 GEN
Solar/Wind Harmer
31.759
270044AE2-322 C
Solar/Wind Harmer
1.391
270404AC1-167 GEN
Solar/Wind Harmer
1.158
24642205MAYFLWER
Adder
0.665
25196008MFTGT1
Adder
1.406
247604X1-042
Adder
0.434
274752CRETE EC ;2U
Adder
8.489
274753CRETE EC ;3U
Adder
8.489
274772LINCOLN ;3U
Adder
8.688
274724RIVER EC ;11
Adder
18.229
24728705AND G3
Adder
8.226
274802UNIV PARK;5U
Adder
5.978
24728505AND G1
Adder
3.933
274826FISK ;BP
Adder
11.221
274800UNIV PARK;3U
Adder
5.975
972038AH1-567 GEN2
Adder
0.374
972228AH1-698 GEN2
Adder
3.796
274676JOLIET 29;8U
Adder
30.228
274729ELWOOD EC;1P
Adder
16.792
274730ELWOOD EC;6P
Adder
16.792
274734ELWOOD EC;8P
Adder
16.792
274736ELWOOD EC;9P
Adder
16.792
274682WAUKEGAN ;7U
Adder
9.742
964991AG1-363 GEN
Solar/Wind Helper
5.141
316097T157 G90
Solar/Wind Helper
1.505
23750701CROSSCHOOL
Solar/Wind Helper
1.505
238118U2-030_1
Solar/Wind Helper
0.342
238127S14_GEN_2
Solar/Wind Helper
0.829
238148AE2-230_GEN2
Solar/Wind Helper
0.497
237080AD1-060 GEN
Solar/Wind Helper
0.342
237038AE2-054 C
Solar/Wind Helper
0.272
235062AE1-101 C1
Solar/Wind Helper
1.661
23779801AA1-109
Solar/Wind Helper
0.193
237048AF1-022 C
Solar/Wind Helper
0.178
223401AF1-299 GEN
Solar/Wind Helper
0.368
316006AB2-029 C
Solar/Wind Helper
0.117
966131AG1-482 GEN
Solar/Wind Helper
0.077
233930AB2-032 GEN
Solar/Wind Helper
0.381
233915AB1-141 GEN
Solar/Wind Helper
0.503
232422X3-066 FULL
Solar/Wind Helper
0.114
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
233998TM1NIN_3.36
Solar/Wind Helper
0.262
232404W1-003 C
Solar/Wind Helper
0.508
232428Y3-058 C
Solar/Wind Helper
0.338
233954AC2-188 GEN
Solar/Wind Helper
0.233
233950AC2-186 GEN
Solar/Wind Helper
0.116
232434Z2-077 GEN
Solar/Wind Helper
0.127
233972AC1-094 C
Solar/Wind Helper
0.303
316045AC1-158 PL2
Solar/Wind Helper
4.142
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.23
228728W1-130C
Solar/Wind Helper
0.054
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219904AC1-010 C
Solar/Wind Helper
0.061
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.131
20720728JCB_W1-129
Solar/Wind Helper
0.057
316254AC1-120 GEN1
Solar/Wind Helper
1.06
207445AB1-138_GEN
Solar/Wind Helper
0.104
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.31
20715228NPK_W1-113
Solar/Wind Helper
0.078
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.496
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
207437AD2-070 GEN
Solar/Wind Helper
0.138
207518AF1-320_GEN
Solar/Wind Helper
1.573
20671928W4-073
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.03
970513AG2-328 GEN
Solar/Wind Harmer
3.728
970517AG2-330 GEN
Solar/Wind Harmer
3.381
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.265
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.153
MECLTFEXP_MEC->PJM
CLTF
15.925
SIGELTFEXP_SIGE->PJM
CLTF
0.506
LAGNLTFEXP_LAGN->PJM
CLTF
14.864
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.83
TVALTFEXP_TVA->PJM
CLTF
7.306
CPLELTFEXP_CPLE->PJM
CLTF
0.632
CBM West 2LTFEXP_CBM-W2->PJM
CBM
113.005
NYPJM->LTFIMP_NY
CLTF
4.803
LGEELTFEXP_LGEE->PJM
CLTF
6.759
WECLTFEXP_WEC->PJM
CLTF
3.83
AG2-052LTFEXP_AG2-052->PJM
LTF
0.24
AH1-155LTFEXP_AH1-155->PJM
LTF
0.36

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P2-3_MP-500-015_SRT-A


Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-015_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:132.9 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5039.69
MW Contribution:11.51
Bus #Bus NameTypeMW Contribution
270119AB2-067 GEN1
50/50
7.063
270120AB2-067 GEN2
50/50
7.063
24318905MLG2
50/50
7.074
270471AD2-092_GEN
Solar/Wind Harmer
4.466
946101AF1-275 GEN
Solar/Wind Harmer
1.816
942861AE2-305 GEN
Solar/Wind Harmer
9.089
970077AG2-063 GEN
Solar/Wind Harmer
6.24
270224U2-072_GEN2
Solar/Wind Harmer
2.282
270227U2-072_GEN3
Solar/Wind Harmer
2.282
270228U2-072_GEN4
Solar/Wind Harmer
2.282
270231U2-072_GEN5
Solar/Wind Harmer
2.282
938701AE1-092 GEN
Solar/Wind Harmer
23.829
964601AG1-323 GEN
Solar/Wind Harmer
3.66
964601AG1-323 GEN
Solar/Wind Harmer
1.702
270518AE2-148 GEN
Solar/Wind Harmer
13.889
962771AG1-126 GEN
Solar/Wind Harmer
40.976
972239AH1-704 GEN
Adder
2.69
270054AF2-122 C O1
Solar/Wind Harmer
3.996
270459AD2-067 GEN
Solar/Wind Harmer
10.248
961821AG1-024 GEN
Solar/Wind Harmer
10.404
270520AE2-214 GEN
Solar/Wind Harmer
7.276
270284AF1-227 GEN1
Solar/Wind Harmer
6.79
270286AF1-227 GEN2
Solar/Wind Harmer
2.512
270287AF1-227 GEN3
Solar/Wind Harmer
2.512
253383AE2-342_GEN
Solar/Wind Harmer
1.045
241973AD2-163_GEN1
Solar/Wind Harmer
2.331
945631AF1-228 GEN
Solar/Wind Harmer
5.463
943861AF1-054 GEN
Solar/Wind Harmer
4.486
972269AH1-719 GEN
Adder
2.587
972159AH1-661 GEN
Adder
1.119
253378AE2-206_GEN
Solar/Wind Harmer
4.007
276820AF1-078_GEN
Solar/Wind Harmer
1.78
971199AH1-059 GEN
Solar/Wind Harmer
4.433
241960AC2-195 GEN
Solar/Wind Harmer
3.073
25326509SID D
Adder
1.452
970879AG2-548 GEN
Solar/Wind Harmer
6.78
971073AG2-665 GEN
Solar/Wind Harmer
6.78
971073AG2-665 GEN
Solar/Wind Harmer
4.73
25326109MON D
Adder
1.444
25322209TAIT E
Adder
10.653
25322209TAIT E
Adder
10.414
971201AH1-060 GEN
Solar/Wind Harmer
2.181
253370AE2-315 SEC1
Adder
2.184
253394AE2-221_GEN
Solar/Wind Harmer
4.918
253398AE2-221_GEN2
Solar/Wind Harmer
4.918
246938BC-WTG3
Solar/Wind Harmer
4.299
246937BC-WTG2
Solar/Wind Harmer
4.226
971231AH1-075 GEN
Solar/Wind Harmer
0.862
253317AC1-085 GEN4
Solar/Wind Harmer
9.013
970611AG2-400 GEN
Solar/Wind Harmer
10.743
270007AE1-245 C
Solar/Wind Harmer
6.358
942801AE2-298 GEN
Solar/Wind Harmer
1.622
962581AG1-107 GEN
Solar/Wind Harmer
5.365
961491AF2-440 GEN
Solar/Wind Harmer
2.229
25183208HLCRTG
Solar/Wind Harmer
6.449
944541AF1-119 GEN
Solar/Wind Harmer
4.453
960971AF2-388 GEN
Solar/Wind Harmer
11.621
942221AE2-234 GEN
Solar/Wind Harmer
0.778
252519AF1-045_GEN
Solar/Wind Harmer
6.447
252516AE2-318_GEN
Solar/Wind Harmer
4.918
247621Y3-024
Adder
0.256
970883AG2-550 GEN
Solar/Wind Harmer
10.602
970885AG2-551 GEN
Solar/Wind Harmer
2.465
270201AC2-176 GEN
Solar/Wind Harmer
5.449
25194408D.CRK1
Adder
8.013
25194508D.CRK3
Adder
1.498
964611AG1-324 GEN
Solar/Wind Harmer
1.248
964611AG1-324 GEN
Solar/Wind Harmer
0.554
252509AD1-136 GEN
Solar/Wind Harmer
0.271
247620Y3-023
Adder
0.484
24728805RICHG1
Adder
3.968
24728905RICHG2
Adder
3.968
274770LINCOLN ;1U
Adder
8.684
274771LINCOLN ;2U
Adder
8.684
274808UNIV PK N;4U
Adder
5.122
274803UNIV PARK;6U
Adder
5.976
972259AH1-714 GEN
Adder
19.527
274674JOLIET 9 ;6U
Adder
15.72
274696ROCKY RD ;4P
Adder
11.549
274695ROCKY RD ;2P
Adder
11.282
274693ROCKY RD ;1P
Adder
11.171
274697ROCKY RD ;3P
Adder
3.065
23585401KL_K28_T16
Solar/Wind Helper
1.478
238120AE2-309 GEN
Solar/Wind Helper
0.524
238175AF1-290_GEN
Solar/Wind Helper
0.153
238169AE2-226 GEN1
Solar/Wind Helper
0.702
238170AE2-226 GEN2
Solar/Wind Helper
0.702
235020AA1-095 C
Solar/Wind Helper
0.053
23777901MDS_W4-102
Solar/Wind Helper
0.177
237034AC2-136 C
Solar/Wind Helper
0.227
237002AB1-128_GEN
Solar/Wind Helper
0.443
235063AE1-101 C2
Solar/Wind Helper
1.661
237001AB1-127_GEN
Solar/Wind Helper
0.442
23777801MSM_W1-116
Solar/Wind Helper
0.114
237025AB1-124 C
Solar/Wind Helper
0.164
237006AB1-125 GEN
Solar/Wind Helper
0.123
226929AD2-058 GEN
Solar/Wind Helper
0.099
205916AD1-020 GEN
Solar/Wind Helper
1.715
20390526W1-045 C
Solar/Wind Helper
0.35
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
233987AB2-037 GEN
Solar/Wind Helper
2.344
233933AB2-153 GEN
Solar/Wind Helper
0.233
232424Y1-079 C
Solar/Wind Helper
0.116
233944AB2-135 GEN
Solar/Wind Helper
0.589
233946AB2-136 GEN
Solar/Wind Helper
0.569
234036AF2-325 C
Solar/Wind Helper
0.042
233901CHERRYDALE C
Solar/Wind Helper
0.233
232408W1-005 C
Solar/Wind Helper
0.508
232410W1-006 C
Solar/Wind Helper
0.508
233939AC1-091 C
Solar/Wind Helper
0.35
233970AC1-092 C
Solar/Wind Helper
0.35
315651AD1-115 GEN
Solar/Wind Helper
0.785
316447AC1-158 HLD
Solar/Wind Helper
2.848
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.04
219921AF1-264
Solar/Wind Helper
0.051
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.082
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.19
20716928W4-060COL
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.016
20673828FLE_V3-070
Solar/Wind Helper
0.091
207442AE1-156 GEN
Solar/Wind Helper
0.326
20676128MHD_W3-029
Solar/Wind Helper
0.096
20671828STAW2-080
Solar/Wind Helper
0.027
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
207471AF2-354 C
Solar/Wind Helper
0.169
20674928WA_W3-044
Solar/Wind Helper
0.098
964851AG1-348 GEN
Solar/Wind Helper
0.081
20676228FRD_X1-012
Solar/Wind Helper
0.092
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.045
211065PSPA IPP
Solar/Wind Helper
0.152
211065PSPA IPP
Solar/Wind Helper
0.152
970321AG2-212 GEN
Solar/Wind Harmer
3.726
270166AC1-044 GEN3
50/50
7.063
23559101PLEAS2
50/50
6.112
23684101S70BUS1
50/50
0.168
962761AG1-125 GEN
Solar/Wind Harmer
40.976
970149AG2-104 GEN
Solar/Wind Harmer
50.605
970155AG2-107 GEN
Solar/Wind Harmer
17.867
270349AD2-093_GEN
Solar/Wind Harmer
4.466
24721705FLATG2
Adder
23.946
270159DARBY CT4
Adder
10.253
970593AG2-378 GEN
Solar/Wind Harmer
2.311
270223U2-072_GEN1
Solar/Wind Harmer
2.282
270578AF1-285 GEN2
Solar/Wind Harmer
1.396
270391AF1-285 GEN3
Solar/Wind Harmer
1.396
253343AC1-166 GEN
Solar/Wind Harmer
1.242
253325AC1-069 GEN
Solar/Wind Harmer
1.197
270462AD2-086
Solar/Wind Harmer
7.941
971995AH1-542 GEN
Solar/Wind Harmer
12.507
270263AC1-001 GEN
Solar/Wind Harmer
1.177
270510AE1-227 GEN1
Solar/Wind Harmer
2.727
25326309TAIT D
Adder
1.197
241813AF1-122_GEN
Solar/Wind Harmer
6.978
960071AF2-298 GEN
Solar/Wind Harmer
5.44
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.065
927014AC1-188 GEN
Solar/Wind Harmer
1.725
246936BC-WTG1
Solar/Wind Harmer
4.226
270489AE1-102 GEN1
Solar/Wind Harmer
1.404
965421AG1-410 GEN
Solar/Wind Harmer
32.379
960001AF2-291 GEN
Solar/Wind Harmer
3.256
253432AC1-085 GEN2
Solar/Wind Harmer
0.288
946171AF1-282 GEN
Solar/Wind Harmer
10.76
247521TR3_G114
Solar/Wind Harmer
3.612
270246TR4_N_V150
Solar/Wind Harmer
0.914
965011AG1-365 GEN
Solar/Wind Harmer
10.743
24695305TIMB G C
Solar/Wind Harmer
5.899
965651AG1-433 GEN
Solar/Wind Harmer
5.811
958861AF2-177 GEN
Solar/Wind Harmer
11.606
247536S-71 GEN
Solar/Wind Harmer
4.292
25194608D.CRK4
Adder
1.742
945371AF1-202 GEN
Solar/Wind Harmer
7.39
252507AC2-088 GEN
Solar/Wind Harmer
1.898
270063AE2-323 C
Solar/Wind Harmer
2.329
25196808ZIMRHP
Adder
79.816
24639705ELKHART HY
Adder
0.161
25196008MFTGT1
Adder
1.452
274751CRETE EC ;1U
Adder
8.485
274754CRETE EC ;4U
Adder
8.485
274773LINCOLN ;4U
Adder
8.684
274774LINCOLN ;5U
Adder
8.684
274723RIVER EC ;12
Adder
18.437
274812UNIV PK N;8U
Adder
5.144
24728605AND G2
Adder
3.932
274801UNIV PARK;4U
Adder
5.972
274676JOLIET 29;8U
Adder
31.334
274732ELWOOD EC;7P
Adder
16.784
274674JOLIET 9 ;6U
Adder
15.72
274745AC1-111 GEN9
Adder
5.685
970091AG2-072 GEN
Adder
77.715
316095T157 G97
Solar/Wind Helper
1.505
23583801GRNGAP
Solar/Wind Helper
5.607
238185AF2-356 C
Solar/Wind Helper
2.642
238108AE1-109 GEN1
Solar/Wind Helper
0.114
235054AD2-180 GEN
Solar/Wind Helper
2.025
235531U2-073 GEN
Solar/Wind Helper
3.278
238117U2-030
Solar/Wind Helper
0.341
238147AE2-230_GEN1
Solar/Wind Helper
0.495
238149AF1-291A_GEN
Solar/Wind Helper
0.141
237061AD1-155 GEN
Solar/Wind Helper
0.053
23751201ROTHROCK
Solar/Wind Helper
0.819
238221AF1-254 C O1
Solar/Wind Helper
0.275
23562501BACKB
Solar/Wind Helper
1.001
235067AD1-061 GEN
Solar/Wind Helper
0.496
23751101LEADS_P59
Solar/Wind Helper
1.388
237030AB1-096 C
Solar/Wind Helper
0.071
3141196NOKESVL
Solar/Wind Helper
1.033
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.346
223402AF1-300 C
Solar/Wind Helper
0.368
205917AD1-020 ES
Solar/Wind Helper
0.369
233982AB2-133 GEN
Solar/Wind Helper
0.358
233918AB1-142 GEN
Solar/Wind Helper
0.503
233994AC2-023 GEN
Solar/Wind Helper
0.962
233996TM1833_GEN
Solar/Wind Helper
0.262
233997TMININ_4.2
Solar/Wind Helper
0.262
232406W1-004 FULL
Solar/Wind Helper
0.508
233940AF2-379 C
Solar/Wind Helper
0.062
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.233
233971AC1-093 C
Solar/Wind Helper
0.358
316044AC1-158 PL1
Solar/Wind Helper
1.294
316450AC1-158 RIC
Solar/Wind Helper
0.345
230430AE1-229_GEN
Solar/Wind Helper
3.376
230415AB2-049 C
Solar/Wind Helper
0.03
228729W2-030 C
Solar/Wind Helper
0.111
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.15
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
219348LDSOLAR C
Solar/Wind Helper
0.115
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.063
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.354
219276PARKLANDSO C
Solar/Wind Helper
0.089
20714528FRN_Y2-051
Solar/Wind Helper
0.057
20720528MAN_W1-024
Solar/Wind Helper
0.028
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.027
219249CENTRALDIV C
Solar/Wind Helper
0.01
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.089
970245AG2-165 GEN
Solar/Wind Harmer
3.726
943851AF1-053 GEN
Solar/Wind Harmer
2.168
270156DARBY CT1
Adder
10.419
270157DARBY CT2
Adder
10.393
270158DARBY CT3
Adder
10.228
970689AG2-444 GEN
Solar/Wind Harmer
18.827
270578AF1-285 GEN2
Solar/Wind Harmer
0.537
270432AC2-029 GEN
Solar/Wind Harmer
8.049
940611AE2-048 GEN
Solar/Wind Harmer
25.14
941391AE2-136 GEN
Solar/Wind Harmer
13.027
270302AB2-170 GEN
Solar/Wind Harmer
9.546
270317AD1-130_GEN
Solar/Wind Harmer
3.659
270269AC2-059
Solar/Wind Harmer
10.605
241972AD1-140 GEN
Solar/Wind Harmer
5.021
958581AF2-149 GEN
Solar/Wind Harmer
4.743
970179AG2-119 GEN
Solar/Wind Harmer
8.842
270340AC2-060 GEN
Solar/Wind Harmer
3.346
970879AG2-548 GEN
Solar/Wind Harmer
4.73
253372AE2-315 SEC3
Adder
2.065
253372AE2-315 SEC3
Adder
2.065
25306009OHH W.
Adder
3.133
253349AC2-067 GEN
Solar/Wind Harmer
5.407
253400AC2-068 GEN
Solar/Wind Harmer
2.174
957201AF2-014 GEN
Solar/Wind Harmer
4.898
270435AC2-044 GEN
Solar/Wind Harmer
2.16
965051AG1-369 GEN
Solar/Wind Harmer
5.365
965041AG1-368 GEN
Solar/Wind Harmer
10.719
247607V1-011 GEN
Solar/Wind Harmer
4.239
971567AH1-282 GEN
Solar/Wind Harmer
16.075
966831AG1-554 GEN
Solar/Wind Harmer
1.28
971989AH1-539 GEN
Solar/Wind Harmer
13.838
24729505KEY G4
Adder
6.925
963791AG1-232 GEN
Solar/Wind Harmer
14.411
270071AF1-092 GEN
Solar/Wind Harmer
15.995
971985AH1-537 GEN
Solar/Wind Harmer
18.996
958711AF2-162 GEN
Solar/Wind Harmer
1.076
270024AE2-089 GEN
Solar/Wind Harmer
4.988
270367AC2-061_GEN
Solar/Wind Harmer
3.378
965101AG1-375 GEN
Solar/Wind Harmer
10.618
971673AH1-337 GEN
Solar/Wind Harmer
4.878
252524AE2-267 GEN
Solar/Wind Harmer
1.672
25196408WSDLE3
Adder
9.354
25196308WSDLE2
Adder
9.273
25196208WSDLE1
Adder
9.25
25196708WSDLE6
Adder
9.227
25196508WSDLE4
Adder
8.994
971029AG2-637 GEN
Solar/Wind Harmer
15.905
270543AE2-219 C
Solar/Wind Harmer
5.429
961761AG1-017 GEN
Solar/Wind Harmer
0.454
945581AF1-223 GEN
Solar/Wind Harmer
4.803
270297AD1-101 GEN
Solar/Wind Harmer
2.947
944031AF1-071 GEN
Solar/Wind Harmer
1.064
25196108MFTGT2
Adder
1.6
25196108MFTGT2
Adder
1.486
274775LINCOLN ;6U
Adder
8.684
274776LINCOLN ;7U
Adder
8.684
274777LINCOLN ;8U
Adder
8.684
274814UNIV PK N;0U
Adder
5.189
274807UNIV PK N;3U
Adder
5.178
274805UNIV PK N;1U
Adder
5.156
274811UNIV PK N;7U
Adder
5.144
972037AH1-567 GEN1
Adder
0.188
274827FISK ;RP
Adder
7.949
972227AH1-698 GEN1
Adder
2.671
274687WILL CNTY;4U
Adder
28.551
274687WILL CNTY;4U
Adder
28.551
274675JOLIET 29;7U
Adder
31.334
274675JOLIET 29;7U
Adder
30.215
274731ELWOOD EC;2P
Adder
16.784
274733ELWOOD EC;3P
Adder
16.784
274735ELWOOD EC;4P
Adder
16.784
274728ELWOOD EC;5P
Adder
16.784
972203AH1-686 GEN
Adder
2.341
274746AC1-111 G10
Adder
5.685
274744AC1-111 GEN8
Adder
5.685
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238126S14_GEN_1
Solar/Wind Helper
0.826
238152AF2-075_GEN
Solar/Wind Helper
0.708
238208AF1-136 C
Solar/Wind Helper
0.22
23546401DTGZ2-030
Solar/Wind Helper
0.089
237085AD2-009_GEN
Solar/Wind Helper
1.65
3138216PACIFIC
Solar/Wind Helper
0.044
316411AF1-147_GEN1
Solar/Wind Helper
0.889
316415AF1-147_GEN2
Solar/Wind Helper
0.889
23750501ELLIOTTS
Solar/Wind Helper
0.637
959381AF2-229 GEN
Solar/Wind Helper
0.358
3141426STAFORD
Solar/Wind Helper
0.052
960921AF2-383 GEN
Solar/Wind Helper
0.182
205943AE1-185 GEN
Solar/Wind Helper
0.51
205932AD2-116_GEN
Solar/Wind Helper
0.509
205956AE1-196_GEN
Solar/Wind Helper
0.509
233935AB2-179 C
Solar/Wind Helper
1.27
232436AB1-176 C
Solar/Wind Helper
0.044
233923SMA
Solar/Wind Helper
0.959
234033AF1-007_GEN
Solar/Wind Helper
7.028
233990AG1-397 GEN
Solar/Wind Helper
0.03
232432Z2-076 GEN
Solar/Wind Helper
0.067
964001AG1-254 GEN
Solar/Wind Helper
0.956
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.115
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.08
203975AE1-071-GEN
Solar/Wind Helper
2.5
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.29
219620RIDERU C
Solar/Wind Helper
0.001
316164AC1-076 GEN
Solar/Wind Helper
1.097
20675528CPH_W2-050
Solar/Wind Helper
0.087
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
218524CNTRALGAS1 C
Solar/Wind Helper
0.161
966261AG1-495 GEN
Solar/Wind Helper
0.081
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20675928HOL_W4-097
Solar/Wind Helper
0.05
20674828DL_W4-046
Solar/Wind Helper
0.008
207484AF2-139 C O1
Solar/Wind Helper
0.084
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.137
20675128HRM_W1-127
Solar/Wind Helper
0.03
209116AE2-175 GEN
Solar/Wind Helper
1.781
24318805MLG1
50/50
10.098
23559001PLEAS1
50/50
6.112
270051AF1-062 GEN
50/50
11.831
23684201S70BUS2
50/50
0.171
270475AD2-096_GEN
50/50
7.147
970153AG2-106 GEN
Solar/Wind Harmer
17.867
961921AG1-034 GEN
Solar/Wind Harmer
15.607
241955AC1-078 GEN
Solar/Wind Harmer
8.813
24721905FLATG4
Adder
23.946
241974AD2-163_GEN2
Solar/Wind Harmer
2.331
942051AE2-217 GEN
Solar/Wind Harmer
21.048
960801AF2-371 GEN
Solar/Wind Harmer
2.948
964871AG1-351 GEN
Solar/Wind Harmer
2.036
970605AG2-385 GEN
Solar/Wind Harmer
6.24
942871AE2-306 GEN
Solar/Wind Harmer
1.047
270391AF1-285 GEN3
Solar/Wind Harmer
0.537
253338AC1-165 GEN
Solar/Wind Harmer
1.242
253333AC1-068 GEN
Solar/Wind Harmer
1.197
270485AE1-090_GEN
Solar/Wind Harmer
0.69
270273AD2-016 GEN
Solar/Wind Harmer
3.033
972173AH1-669 GEN
Solar/Wind Harmer
5.671
270291AC1-194 GEN
Solar/Wind Harmer
11.744
253415AE1-040 GEN
Solar/Wind Harmer
1.248
270512AE1-227 GEN2
Solar/Wind Harmer
2.315
970065AG2-057 GEN
Solar/Wind Harmer
1.09
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.065
957541AF2-048 GEN
Solar/Wind Harmer
1.721
253406AD2-031_GEN
Solar/Wind Harmer
1.388
270491AE1-102 GEN2
Solar/Wind Harmer
1.404
270377AD1-106 GEN
Solar/Wind Harmer
6.655
971191AH1-055 GEN
Solar/Wind Harmer
23.692
253316AC1-085 GEN3
Solar/Wind Harmer
9.013
253433AC1-085 GEN1
Solar/Wind Harmer
5.721
946181AF1-283 GEN
Solar/Wind Harmer
13.988
270191TR4_S_V150
Solar/Wind Harmer
3.223
270247TR4_N_V136
Solar/Wind Harmer
0.914
959331AF2-224 GEN
Solar/Wind Harmer
10.743
965021AG1-366 GEN
Solar/Wind Harmer
2.498
270588AE1-091_GEN
Solar/Wind Harmer
11.792
958091AF2-103 GEN
Solar/Wind Harmer
0.173
944531AF1-118 GEN
Solar/Wind Harmer
37.418
270043AE2-236 GEN
Solar/Wind Harmer
5.874
270258AD1-119 GEN
Solar/Wind Harmer
2.962
971617AH1-308 GEN
Solar/Wind Harmer
6.179
25196608WSDLE5
Adder
9.087
252510AF1-249 C
Solar/Wind Harmer
0.443
962031AG1-047 GEN
Solar/Wind Harmer
3.204
957741AF2-068 GEN
Solar/Wind Harmer
15.899
25194608D.CRK4
Adder
1.742
270222AC2-111 GEN
Solar/Wind Harmer
8.63
970031AG2-029 GEN
Solar/Wind Harmer
31.748
270044AE2-322 C
Solar/Wind Harmer
1.39
270404AC1-167 GEN
Solar/Wind Harmer
1.158
24642205MAYFLWER
Adder
0.665
25196008MFTGT1
Adder
1.406
247604X1-042
Adder
0.433
274752CRETE EC ;2U
Adder
8.485
274753CRETE EC ;3U
Adder
8.485
274772LINCOLN ;3U
Adder
8.684
274724RIVER EC ;11
Adder
18.221
24728705AND G3
Adder
8.223
274802UNIV PARK;5U
Adder
5.976
24728505AND G1
Adder
3.932
274826FISK ;BP
Adder
11.216
274800UNIV PARK;3U
Adder
5.972
972038AH1-567 GEN2
Adder
0.374
972228AH1-698 GEN2
Adder
3.794
274676JOLIET 29;8U
Adder
30.215
274729ELWOOD EC;1P
Adder
16.784
274730ELWOOD EC;6P
Adder
16.784
274734ELWOOD EC;8P
Adder
16.784
274736ELWOOD EC;9P
Adder
16.784
274682WAUKEGAN ;7U
Adder
9.459
964991AG1-363 GEN
Solar/Wind Helper
5.14
316097T157 G90
Solar/Wind Helper
1.505
23750701CROSSCHOOL
Solar/Wind Helper
1.501
238118U2-030_1
Solar/Wind Helper
0.341
238127S14_GEN_2
Solar/Wind Helper
0.826
238148AE2-230_GEN2
Solar/Wind Helper
0.497
237080AD1-060 GEN
Solar/Wind Helper
0.342
237038AE2-054 C
Solar/Wind Helper
0.272
235062AE1-101 C1
Solar/Wind Helper
1.661
23779801AA1-109
Solar/Wind Helper
0.193
237048AF1-022 C
Solar/Wind Helper
0.177
223401AF1-299 GEN
Solar/Wind Helper
0.368
316006AB2-029 C
Solar/Wind Helper
0.117
966131AG1-482 GEN
Solar/Wind Helper
0.077
233930AB2-032 GEN
Solar/Wind Helper
0.381
233915AB1-141 GEN
Solar/Wind Helper
0.503
232422X3-066 FULL
Solar/Wind Helper
0.114
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
233998TM1NIN_3.36
Solar/Wind Helper
0.262
232404W1-003 C
Solar/Wind Helper
0.508
232428Y3-058 C
Solar/Wind Helper
0.338
232434Z2-077 GEN
Solar/Wind Helper
0.127
233954AC2-188 GEN
Solar/Wind Helper
0.233
233950AC2-186 GEN
Solar/Wind Helper
0.116
233972AC1-094 C
Solar/Wind Helper
0.303
316045AC1-158 PL2
Solar/Wind Helper
4.142
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.23
228728W1-130C
Solar/Wind Helper
0.054
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219904AC1-010 C
Solar/Wind Helper
0.06
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.131
20720728JCB_W1-129
Solar/Wind Helper
0.057
316254AC1-120 GEN1
Solar/Wind Helper
1.061
207445AB1-138_GEN
Solar/Wind Helper
0.104
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.31
20715228NPK_W1-113
Solar/Wind Helper
0.078
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.496
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
207437AD2-070 GEN
Solar/Wind Helper
0.138
207518AF1-320_GEN
Solar/Wind Helper
1.573
20671928W4-073
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.03
970513AG2-328 GEN
Solar/Wind Harmer
3.726
970517AG2-330 GEN
Solar/Wind Harmer
3.379
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.216
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.135
MECLTFEXP_MEC->PJM
CLTF
15.918
SIGELTFEXP_SIGE->PJM
CLTF
0.506
LAGNLTFEXP_LAGN->PJM
CLTF
14.855
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.816
TVALTFEXP_TVA->PJM
CLTF
7.302
CPLELTFEXP_CPLE->PJM
CLTF
0.627
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.944
NYPJM->LTFIMP_NY
CLTF
4.803
LGEELTFEXP_LGEE->PJM
CLTF
6.756
WECLTFEXP_WEC->PJM
CLTF
3.828
AG2-052LTFEXP_AG2-052->PJM
LTF
0.24
AH1-155LTFEXP_AH1-155->PJM
LTF
0.36

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P2-3_MP-500-014_SRT-A


Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:132.9 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5039.69
MW Contribution:11.51
Bus #Bus NameTypeMW Contribution
270119AB2-067 GEN1
50/50
7.063
270120AB2-067 GEN2
50/50
7.063
24318905MLG2
50/50
7.074
270471AD2-092_GEN
Solar/Wind Harmer
4.466
946101AF1-275 GEN
Solar/Wind Harmer
1.816
942861AE2-305 GEN
Solar/Wind Harmer
9.089
970077AG2-063 GEN
Solar/Wind Harmer
6.24
270224U2-072_GEN2
Solar/Wind Harmer
2.282
270227U2-072_GEN3
Solar/Wind Harmer
2.282
270228U2-072_GEN4
Solar/Wind Harmer
2.282
270231U2-072_GEN5
Solar/Wind Harmer
2.282
938701AE1-092 GEN
Solar/Wind Harmer
23.829
964601AG1-323 GEN
Solar/Wind Harmer
3.66
964601AG1-323 GEN
Solar/Wind Harmer
1.702
270518AE2-148 GEN
Solar/Wind Harmer
13.889
972269AH1-719 GEN
Adder
2.587
972159AH1-661 GEN
Adder
1.119
253378AE2-206_GEN
Solar/Wind Harmer
4.007
276820AF1-078_GEN
Solar/Wind Harmer
1.78
971199AH1-059 GEN
Solar/Wind Harmer
4.433
241960AC2-195 GEN
Solar/Wind Harmer
3.073
25326509SID D
Adder
1.452
970879AG2-548 GEN
Solar/Wind Harmer
6.78
971073AG2-665 GEN
Solar/Wind Harmer
6.78
971073AG2-665 GEN
Solar/Wind Harmer
4.73
25326109MON D
Adder
1.444
25322209TAIT E
Adder
10.653
25322209TAIT E
Adder
10.414
971201AH1-060 GEN
Solar/Wind Harmer
2.181
253370AE2-315 SEC1
Adder
2.184
253394AE2-221_GEN
Solar/Wind Harmer
4.918
253398AE2-221_GEN2
Solar/Wind Harmer
4.918
246938BC-WTG3
Solar/Wind Harmer
4.299
246937BC-WTG2
Solar/Wind Harmer
4.226
971231AH1-075 GEN
Solar/Wind Harmer
0.862
253317AC1-085 GEN4
Solar/Wind Harmer
9.013
970611AG2-400 GEN
Solar/Wind Harmer
10.743
270007AE1-245 C
Solar/Wind Harmer
6.358
942801AE2-298 GEN
Solar/Wind Harmer
1.622
962581AG1-107 GEN
Solar/Wind Harmer
5.365
961491AF2-440 GEN
Solar/Wind Harmer
2.229
25183208HLCRTG
Solar/Wind Harmer
6.449
944541AF1-119 GEN
Solar/Wind Harmer
4.453
960971AF2-388 GEN
Solar/Wind Harmer
11.621
942221AE2-234 GEN
Solar/Wind Harmer
0.778
252519AF1-045_GEN
Solar/Wind Harmer
6.447
252516AE2-318_GEN
Solar/Wind Harmer
4.918
247621Y3-024
Adder
0.256
970883AG2-550 GEN
Solar/Wind Harmer
10.602
970885AG2-551 GEN
Solar/Wind Harmer
2.465
270201AC2-176 GEN
Solar/Wind Harmer
5.449
25194408D.CRK1
Adder
8.013
25194508D.CRK3
Adder
1.498
964611AG1-324 GEN
Solar/Wind Harmer
1.248
964611AG1-324 GEN
Solar/Wind Harmer
0.554
252509AD1-136 GEN
Solar/Wind Harmer
0.271
247620Y3-023
Adder
0.484
24728805RICHG1
Adder
3.968
24728905RICHG2
Adder
3.968
274770LINCOLN ;1U
Adder
8.684
274771LINCOLN ;2U
Adder
8.684
274808UNIV PK N;4U
Adder
5.122
274803UNIV PARK;6U
Adder
5.976
972259AH1-714 GEN
Adder
19.527
274674JOLIET 9 ;6U
Adder
15.72
274696ROCKY RD ;4P
Adder
11.549
274695ROCKY RD ;2P
Adder
11.282
274693ROCKY RD ;1P
Adder
11.171
274697ROCKY RD ;3P
Adder
3.065
23585401KL_K28_T16
Solar/Wind Helper
1.478
238120AE2-309 GEN
Solar/Wind Helper
0.524
238175AF1-290_GEN
Solar/Wind Helper
0.153
238169AE2-226 GEN1
Solar/Wind Helper
0.702
238170AE2-226 GEN2
Solar/Wind Helper
0.702
235020AA1-095 C
Solar/Wind Helper
0.053
23777901MDS_W4-102
Solar/Wind Helper
0.177
237034AC2-136 C
Solar/Wind Helper
0.227
237002AB1-128_GEN
Solar/Wind Helper
0.443
235063AE1-101 C2
Solar/Wind Helper
1.661
237001AB1-127_GEN
Solar/Wind Helper
0.442
23777801MSM_W1-116
Solar/Wind Helper
0.114
237025AB1-124 C
Solar/Wind Helper
0.164
237006AB1-125 GEN
Solar/Wind Helper
0.123
226929AD2-058 GEN
Solar/Wind Helper
0.099
205916AD1-020 GEN
Solar/Wind Helper
1.715
20390526W1-045 C
Solar/Wind Helper
0.35
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
233987AB2-037 GEN
Solar/Wind Helper
2.344
233933AB2-153 GEN
Solar/Wind Helper
0.233
232424Y1-079 C
Solar/Wind Helper
0.116
233944AB2-135 GEN
Solar/Wind Helper
0.589
233946AB2-136 GEN
Solar/Wind Helper
0.569
234036AF2-325 C
Solar/Wind Helper
0.042
233901CHERRYDALE C
Solar/Wind Helper
0.233
232408W1-005 C
Solar/Wind Helper
0.508
232410W1-006 C
Solar/Wind Helper
0.508
233939AC1-091 C
Solar/Wind Helper
0.35
233970AC1-092 C
Solar/Wind Helper
0.35
315651AD1-115 GEN
Solar/Wind Helper
0.785
316447AC1-158 HLD
Solar/Wind Helper
2.848
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.04
219921AF1-264
Solar/Wind Helper
0.051
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.082
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.19
20716928W4-060COL
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.016
20673828FLE_V3-070
Solar/Wind Helper
0.091
207442AE1-156 GEN
Solar/Wind Helper
0.326
20676128MHD_W3-029
Solar/Wind Helper
0.096
20671828STAW2-080
Solar/Wind Helper
0.027
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
207471AF2-354 C
Solar/Wind Helper
0.169
20674928WA_W3-044
Solar/Wind Helper
0.098
964851AG1-348 GEN
Solar/Wind Helper
0.081
20676228FRD_X1-012
Solar/Wind Helper
0.092
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.045
211065PSPA IPP
Solar/Wind Helper
0.152
211065PSPA IPP
Solar/Wind Helper
0.152
970321AG2-212 GEN
Solar/Wind Harmer
3.726
270166AC1-044 GEN3
50/50
7.063
23559101PLEAS2
50/50
6.112
23684101S70BUS1
50/50
0.168
962761AG1-125 GEN
Solar/Wind Harmer
40.976
970149AG2-104 GEN
Solar/Wind Harmer
50.605
970155AG2-107 GEN
Solar/Wind Harmer
17.867
270349AD2-093_GEN
Solar/Wind Harmer
4.466
24721705FLATG2
Adder
23.946
270159DARBY CT4
Adder
10.253
970593AG2-378 GEN
Solar/Wind Harmer
2.311
270223U2-072_GEN1
Solar/Wind Harmer
2.282
270578AF1-285 GEN2
Solar/Wind Harmer
1.396
270391AF1-285 GEN3
Solar/Wind Harmer
1.396
253343AC1-166 GEN
Solar/Wind Harmer
1.242
253325AC1-069 GEN
Solar/Wind Harmer
1.197
270462AD2-086
Solar/Wind Harmer
7.941
971995AH1-542 GEN
Solar/Wind Harmer
12.507
270263AC1-001 GEN
Solar/Wind Harmer
1.177
270510AE1-227 GEN1
Solar/Wind Harmer
2.727
25326309TAIT D
Adder
1.197
241813AF1-122_GEN
Solar/Wind Harmer
6.978
960071AF2-298 GEN
Solar/Wind Harmer
5.44
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.065
927014AC1-188 GEN
Solar/Wind Harmer
1.725
962771AG1-126 GEN
Solar/Wind Harmer
40.976
972239AH1-704 GEN
Adder
2.69
270054AF2-122 C O1
Solar/Wind Harmer
3.996
270459AD2-067 GEN
Solar/Wind Harmer
10.248
961821AG1-024 GEN
Solar/Wind Harmer
10.404
270520AE2-214 GEN
Solar/Wind Harmer
7.276
270284AF1-227 GEN1
Solar/Wind Harmer
6.79
270286AF1-227 GEN2
Solar/Wind Harmer
2.512
270287AF1-227 GEN3
Solar/Wind Harmer
2.512
253383AE2-342_GEN
Solar/Wind Harmer
1.045
241973AD2-163_GEN1
Solar/Wind Harmer
2.331
945631AF1-228 GEN
Solar/Wind Harmer
5.463
943861AF1-054 GEN
Solar/Wind Harmer
4.486
943851AF1-053 GEN
Solar/Wind Harmer
2.168
270156DARBY CT1
Adder
10.419
270157DARBY CT2
Adder
10.393
270158DARBY CT3
Adder
10.228
970689AG2-444 GEN
Solar/Wind Harmer
18.827
270578AF1-285 GEN2
Solar/Wind Harmer
0.537
270432AC2-029 GEN
Solar/Wind Harmer
8.049
940611AE2-048 GEN
Solar/Wind Harmer
25.14
941391AE2-136 GEN
Solar/Wind Harmer
13.027
270302AB2-170 GEN
Solar/Wind Harmer
9.546
270317AD1-130_GEN
Solar/Wind Harmer
3.659
270269AC2-059
Solar/Wind Harmer
10.605
241972AD1-140 GEN
Solar/Wind Harmer
5.021
958581AF2-149 GEN
Solar/Wind Harmer
4.743
970179AG2-119 GEN
Solar/Wind Harmer
8.842
270340AC2-060 GEN
Solar/Wind Harmer
3.346
970879AG2-548 GEN
Solar/Wind Harmer
4.73
253372AE2-315 SEC3
Adder
2.065
253372AE2-315 SEC3
Adder
2.065
25306009OHH W.
Adder
3.133
253349AC2-067 GEN
Solar/Wind Harmer
5.407
253400AC2-068 GEN
Solar/Wind Harmer
2.174
957201AF2-014 GEN
Solar/Wind Harmer
4.898
270435AC2-044 GEN
Solar/Wind Harmer
2.16
965051AG1-369 GEN
Solar/Wind Harmer
5.365
965041AG1-368 GEN
Solar/Wind Harmer
10.719
247607V1-011 GEN
Solar/Wind Harmer
4.239
971567AH1-282 GEN
Solar/Wind Harmer
16.075
966831AG1-554 GEN
Solar/Wind Harmer
1.28
971989AH1-539 GEN
Solar/Wind Harmer
13.838
24729505KEY G4
Adder
6.925
963791AG1-232 GEN
Solar/Wind Harmer
14.411
270071AF1-092 GEN
Solar/Wind Harmer
15.995
971985AH1-537 GEN
Solar/Wind Harmer
18.996
958711AF2-162 GEN
Solar/Wind Harmer
1.076
270024AE2-089 GEN
Solar/Wind Harmer
4.988
270367AC2-061_GEN
Solar/Wind Harmer
3.378
965101AG1-375 GEN
Solar/Wind Harmer
10.618
971673AH1-337 GEN
Solar/Wind Harmer
4.878
252524AE2-267 GEN
Solar/Wind Harmer
1.672
25196408WSDLE3
Adder
9.354
25196308WSDLE2
Adder
9.273
25196208WSDLE1
Adder
9.25
25196708WSDLE6
Adder
9.227
25196508WSDLE4
Adder
8.994
971029AG2-637 GEN
Solar/Wind Harmer
15.905
270543AE2-219 C
Solar/Wind Harmer
5.429
961761AG1-017 GEN
Solar/Wind Harmer
0.454
945581AF1-223 GEN
Solar/Wind Harmer
4.803
270297AD1-101 GEN
Solar/Wind Harmer
2.947
944031AF1-071 GEN
Solar/Wind Harmer
1.064
25196108MFTGT2
Adder
1.6
25196108MFTGT2
Adder
1.486
274775LINCOLN ;6U
Adder
8.684
274776LINCOLN ;7U
Adder
8.684
274777LINCOLN ;8U
Adder
8.684
274814UNIV PK N;0U
Adder
5.189
274807UNIV PK N;3U
Adder
5.178
274805UNIV PK N;1U
Adder
5.156
274811UNIV PK N;7U
Adder
5.144
972037AH1-567 GEN1
Adder
0.188
274827FISK ;RP
Adder
7.949
972227AH1-698 GEN1
Adder
2.671
274687WILL CNTY;4U
Adder
28.551
274687WILL CNTY;4U
Adder
28.551
274675JOLIET 29;7U
Adder
31.334
274675JOLIET 29;7U
Adder
30.215
274731ELWOOD EC;2P
Adder
16.784
274733ELWOOD EC;3P
Adder
16.784
274735ELWOOD EC;4P
Adder
16.784
274728ELWOOD EC;5P
Adder
16.784
972203AH1-686 GEN
Adder
2.341
274746AC1-111 G10
Adder
5.685
274744AC1-111 GEN8
Adder
5.685
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238126S14_GEN_1
Solar/Wind Helper
0.826
238152AF2-075_GEN
Solar/Wind Helper
0.708
238208AF1-136 C
Solar/Wind Helper
0.22
23546401DTGZ2-030
Solar/Wind Helper
0.089
237085AD2-009_GEN
Solar/Wind Helper
1.65
3138216PACIFIC
Solar/Wind Helper
0.044
316411AF1-147_GEN1
Solar/Wind Helper
0.889
316415AF1-147_GEN2
Solar/Wind Helper
0.889
23750501ELLIOTTS
Solar/Wind Helper
0.637
959381AF2-229 GEN
Solar/Wind Helper
0.358
3141426STAFORD
Solar/Wind Helper
0.052
960921AF2-383 GEN
Solar/Wind Helper
0.182
205943AE1-185 GEN
Solar/Wind Helper
0.51
205932AD2-116_GEN
Solar/Wind Helper
0.509
205956AE1-196_GEN
Solar/Wind Helper
0.509
233935AB2-179 C
Solar/Wind Helper
1.27
232436AB1-176 C
Solar/Wind Helper
0.044
233923SMA
Solar/Wind Helper
0.959
234033AF1-007_GEN
Solar/Wind Helper
7.028
233990AG1-397 GEN
Solar/Wind Helper
0.03
232432Z2-076 GEN
Solar/Wind Helper
0.067
964001AG1-254 GEN
Solar/Wind Helper
0.956
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.115
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.08
203975AE1-071-GEN
Solar/Wind Helper
2.5
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.29
219620RIDERU C
Solar/Wind Helper
0.001
316164AC1-076 GEN
Solar/Wind Helper
1.097
20675528CPH_W2-050
Solar/Wind Helper
0.087
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
218524CNTRALGAS1 C
Solar/Wind Helper
0.161
966261AG1-495 GEN
Solar/Wind Helper
0.081
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20675928HOL_W4-097
Solar/Wind Helper
0.05
20674828DL_W4-046
Solar/Wind Helper
0.008
207484AF2-139 C O1
Solar/Wind Helper
0.084
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.137
20675128HRM_W1-127
Solar/Wind Helper
0.03
209116AE2-175 GEN
Solar/Wind Helper
1.781
246936BC-WTG1
Solar/Wind Harmer
4.226
270489AE1-102 GEN1
Solar/Wind Harmer
1.404
965421AG1-410 GEN
Solar/Wind Harmer
32.379
960001AF2-291 GEN
Solar/Wind Harmer
3.256
253432AC1-085 GEN2
Solar/Wind Harmer
0.288
946171AF1-282 GEN
Solar/Wind Harmer
10.76
247521TR3_G114
Solar/Wind Harmer
3.612
270246TR4_N_V150
Solar/Wind Harmer
0.914
965011AG1-365 GEN
Solar/Wind Harmer
10.743
24695305TIMB G C
Solar/Wind Harmer
5.899
965651AG1-433 GEN
Solar/Wind Harmer
5.811
958861AF2-177 GEN
Solar/Wind Harmer
11.606
247536S-71 GEN
Solar/Wind Harmer
4.292
25194608D.CRK4
Adder
1.742
945371AF1-202 GEN
Solar/Wind Harmer
7.39
252507AC2-088 GEN
Solar/Wind Harmer
1.898
270063AE2-323 C
Solar/Wind Harmer
2.329
25196808ZIMRHP
Adder
79.816
24639705ELKHART HY
Adder
0.161
25196008MFTGT1
Adder
1.452
274751CRETE EC ;1U
Adder
8.485
274754CRETE EC ;4U
Adder
8.485
274773LINCOLN ;4U
Adder
8.684
274774LINCOLN ;5U
Adder
8.684
274723RIVER EC ;12
Adder
18.437
274812UNIV PK N;8U
Adder
5.144
24728605AND G2
Adder
3.932
274801UNIV PARK;4U
Adder
5.972
274676JOLIET 29;8U
Adder
31.334
274732ELWOOD EC;7P
Adder
16.784
274674JOLIET 9 ;6U
Adder
15.72
274745AC1-111 GEN9
Adder
5.685
970091AG2-072 GEN
Adder
77.715
316095T157 G97
Solar/Wind Helper
1.505
23583801GRNGAP
Solar/Wind Helper
5.607
238185AF2-356 C
Solar/Wind Helper
2.642
238108AE1-109 GEN1
Solar/Wind Helper
0.114
235054AD2-180 GEN
Solar/Wind Helper
2.025
235531U2-073 GEN
Solar/Wind Helper
3.278
238117U2-030
Solar/Wind Helper
0.341
238147AE2-230_GEN1
Solar/Wind Helper
0.495
238149AF1-291A_GEN
Solar/Wind Helper
0.141
237061AD1-155 GEN
Solar/Wind Helper
0.053
23751201ROTHROCK
Solar/Wind Helper
0.819
238221AF1-254 C O1
Solar/Wind Helper
0.275
23562501BACKB
Solar/Wind Helper
1.001
235067AD1-061 GEN
Solar/Wind Helper
0.496
23751101LEADS_P59
Solar/Wind Helper
1.388
237030AB1-096 C
Solar/Wind Helper
0.071
3141196NOKESVL
Solar/Wind Helper
1.033
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.346
223402AF1-300 C
Solar/Wind Helper
0.368
205917AD1-020 ES
Solar/Wind Helper
0.369
233982AB2-133 GEN
Solar/Wind Helper
0.358
233918AB1-142 GEN
Solar/Wind Helper
0.503
233994AC2-023 GEN
Solar/Wind Helper
0.962
233996TM1833_GEN
Solar/Wind Helper
0.262
233997TMININ_4.2
Solar/Wind Helper
0.262
232406W1-004 FULL
Solar/Wind Helper
0.508
233940AF2-379 C
Solar/Wind Helper
0.062
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.233
233971AC1-093 C
Solar/Wind Helper
0.358
316044AC1-158 PL1
Solar/Wind Helper
1.294
316450AC1-158 RIC
Solar/Wind Helper
0.345
230430AE1-229_GEN
Solar/Wind Helper
3.376
230415AB2-049 C
Solar/Wind Helper
0.03
228729W2-030 C
Solar/Wind Helper
0.111
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.15
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
219348LDSOLAR C
Solar/Wind Helper
0.115
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.063
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.354
219276PARKLANDSO C
Solar/Wind Helper
0.089
20714528FRN_Y2-051
Solar/Wind Helper
0.057
20720528MAN_W1-024
Solar/Wind Helper
0.028
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.027
219249CENTRALDIV C
Solar/Wind Helper
0.01
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.089
970245AG2-165 GEN
Solar/Wind Harmer
3.726
24318805MLG1
50/50
10.098
23559001PLEAS1
50/50
6.112
270051AF1-062 GEN
50/50
11.831
23684201S70BUS2
50/50
0.171
270475AD2-096_GEN
50/50
7.147
970153AG2-106 GEN
Solar/Wind Harmer
17.867
961921AG1-034 GEN
Solar/Wind Harmer
15.607
241955AC1-078 GEN
Solar/Wind Harmer
8.813
24721905FLATG4
Adder
23.946
241974AD2-163_GEN2
Solar/Wind Harmer
2.331
942051AE2-217 GEN
Solar/Wind Harmer
21.048
960801AF2-371 GEN
Solar/Wind Harmer
2.948
964871AG1-351 GEN
Solar/Wind Harmer
2.036
970605AG2-385 GEN
Solar/Wind Harmer
6.24
942871AE2-306 GEN
Solar/Wind Harmer
1.047
270391AF1-285 GEN3
Solar/Wind Harmer
0.537
253338AC1-165 GEN
Solar/Wind Harmer
1.242
253333AC1-068 GEN
Solar/Wind Harmer
1.197
270485AE1-090_GEN
Solar/Wind Harmer
0.69
270273AD2-016 GEN
Solar/Wind Harmer
3.033
972173AH1-669 GEN
Solar/Wind Harmer
5.671
270291AC1-194 GEN
Solar/Wind Harmer
11.744
253415AE1-040 GEN
Solar/Wind Harmer
1.248
270512AE1-227 GEN2
Solar/Wind Harmer
2.315
970065AG2-057 GEN
Solar/Wind Harmer
1.09
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.065
957541AF2-048 GEN
Solar/Wind Harmer
1.721
253406AD2-031_GEN
Solar/Wind Harmer
1.388
270491AE1-102 GEN2
Solar/Wind Harmer
1.404
270377AD1-106 GEN
Solar/Wind Harmer
6.655
971191AH1-055 GEN
Solar/Wind Harmer
23.692
253316AC1-085 GEN3
Solar/Wind Harmer
9.013
253433AC1-085 GEN1
Solar/Wind Harmer
5.721
946181AF1-283 GEN
Solar/Wind Harmer
13.988
270191TR4_S_V150
Solar/Wind Harmer
3.223
270247TR4_N_V136
Solar/Wind Harmer
0.914
959331AF2-224 GEN
Solar/Wind Harmer
10.743
965021AG1-366 GEN
Solar/Wind Harmer
2.498
270588AE1-091_GEN
Solar/Wind Harmer
11.792
958091AF2-103 GEN
Solar/Wind Harmer
0.173
944531AF1-118 GEN
Solar/Wind Harmer
37.418
270043AE2-236 GEN
Solar/Wind Harmer
5.874
270258AD1-119 GEN
Solar/Wind Harmer
2.962
971617AH1-308 GEN
Solar/Wind Harmer
6.179
25196608WSDLE5
Adder
9.087
252510AF1-249 C
Solar/Wind Harmer
0.443
962031AG1-047 GEN
Solar/Wind Harmer
3.204
957741AF2-068 GEN
Solar/Wind Harmer
15.899
25194608D.CRK4
Adder
1.742
270222AC2-111 GEN
Solar/Wind Harmer
8.63
970031AG2-029 GEN
Solar/Wind Harmer
31.748
270044AE2-322 C
Solar/Wind Harmer
1.39
270404AC1-167 GEN
Solar/Wind Harmer
1.158
24642205MAYFLWER
Adder
0.665
25196008MFTGT1
Adder
1.406
247604X1-042
Adder
0.433
274752CRETE EC ;2U
Adder
8.485
274753CRETE EC ;3U
Adder
8.485
274772LINCOLN ;3U
Adder
8.684
274724RIVER EC ;11
Adder
18.221
24728705AND G3
Adder
8.223
274802UNIV PARK;5U
Adder
5.976
24728505AND G1
Adder
3.932
274826FISK ;BP
Adder
11.216
274800UNIV PARK;3U
Adder
5.972
972038AH1-567 GEN2
Adder
0.374
972228AH1-698 GEN2
Adder
3.794
274676JOLIET 29;8U
Adder
30.215
274729ELWOOD EC;1P
Adder
16.784
274730ELWOOD EC;6P
Adder
16.784
274734ELWOOD EC;8P
Adder
16.784
274736ELWOOD EC;9P
Adder
16.784
274682WAUKEGAN ;7U
Adder
9.459
964991AG1-363 GEN
Solar/Wind Helper
5.14
316097T157 G90
Solar/Wind Helper
1.505
23750701CROSSCHOOL
Solar/Wind Helper
1.501
238118U2-030_1
Solar/Wind Helper
0.341
238127S14_GEN_2
Solar/Wind Helper
0.826
238148AE2-230_GEN2
Solar/Wind Helper
0.497
237080AD1-060 GEN
Solar/Wind Helper
0.342
237038AE2-054 C
Solar/Wind Helper
0.272
235062AE1-101 C1
Solar/Wind Helper
1.661
23779801AA1-109
Solar/Wind Helper
0.193
237048AF1-022 C
Solar/Wind Helper
0.177
223401AF1-299 GEN
Solar/Wind Helper
0.368
316006AB2-029 C
Solar/Wind Helper
0.117
966131AG1-482 GEN
Solar/Wind Helper
0.077
233930AB2-032 GEN
Solar/Wind Helper
0.381
233915AB1-141 GEN
Solar/Wind Helper
0.503
232422X3-066 FULL
Solar/Wind Helper
0.114
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
233998TM1NIN_3.36
Solar/Wind Helper
0.262
232404W1-003 C
Solar/Wind Helper
0.508
232428Y3-058 C
Solar/Wind Helper
0.338
232434Z2-077 GEN
Solar/Wind Helper
0.127
233954AC2-188 GEN
Solar/Wind Helper
0.233
233950AC2-186 GEN
Solar/Wind Helper
0.116
233972AC1-094 C
Solar/Wind Helper
0.303
316045AC1-158 PL2
Solar/Wind Helper
4.142
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.23
228728W1-130C
Solar/Wind Helper
0.054
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219904AC1-010 C
Solar/Wind Helper
0.06
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.131
20720728JCB_W1-129
Solar/Wind Helper
0.057
316254AC1-120 GEN1
Solar/Wind Helper
1.061
207445AB1-138_GEN
Solar/Wind Helper
0.104
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.31
20715228NPK_W1-113
Solar/Wind Helper
0.078
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.496
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
207437AD2-070 GEN
Solar/Wind Helper
0.138
207518AF1-320_GEN
Solar/Wind Helper
1.573
20671928W4-073
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.03
970513AG2-328 GEN
Solar/Wind Harmer
3.726
970517AG2-330 GEN
Solar/Wind Harmer
3.379
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.216
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.135
MECLTFEXP_MEC->PJM
CLTF
15.918
SIGELTFEXP_SIGE->PJM
CLTF
0.506
LAGNLTFEXP_LAGN->PJM
CLTF
14.855
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.816
TVALTFEXP_TVA->PJM
CLTF
7.302
CPLELTFEXP_CPLE->PJM
CLTF
0.627
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.944
NYPJM->LTFIMP_NY
CLTF
4.803
LGEELTFEXP_LGEE->PJM
CLTF
6.756
WECLTFEXP_WEC->PJM
CLTF
3.828
AG2-052LTFEXP_AG2-052->PJM
LTF
0.24
AH1-155LTFEXP_AH1-155->PJM
LTF
0.36

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P1-2_MP-500-007A_SRT-A


Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P1-2_MP-500-007A_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:131.92 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5002.28
MW Contribution:6.9
Bus #Bus NameTypeMW Contribution
962771AG1-126 GEN
Solar/Wind Harmer
34.524
972239AH1-704 GEN
Adder
2.689
270054AF2-122 C O1
Solar/Wind Harmer
0.007
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
5.077
270520AE2-214 GEN
Solar/Wind Harmer
0.013
270284AF1-227 GEN1
Solar/Wind Harmer
0.011
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
253383AE2-342_GEN
Solar/Wind Harmer
0.003
241973AD2-163_GEN1
Solar/Wind Harmer
0.006
945631AF1-228 GEN
Solar/Wind Harmer
0
943861AF1-054 GEN
Solar/Wind Harmer
3.127
943851AF1-053 GEN
Solar/Wind Harmer
2.166
270156DARBY CT1
Adder
10.409
270157DARBY CT2
Adder
10.383
270158DARBY CT3
Adder
10.218
970689AG2-444 GEN
Solar/Wind Harmer
16.436
270578AF1-285 GEN2
Solar/Wind Harmer
0.536
270432AC2-029 GEN
Solar/Wind Harmer
3.553
940611AE2-048 GEN
Solar/Wind Harmer
19.602
941391AE2-136 GEN
Solar/Wind Harmer
11.042
270302AB2-170 GEN
Solar/Wind Harmer
0.005
270317AD1-130_GEN
Solar/Wind Harmer
0.011
971653AH1-327 GEN
Solar/Wind Harmer
1.117
270269AC2-059
Solar/Wind Harmer
0.005
241972AD1-140 GEN
Solar/Wind Harmer
0.854
970179AG2-119 GEN
Solar/Wind Harmer
6.883
270340AC2-060 GEN
Solar/Wind Harmer
0.009
970879AG2-548 GEN
Solar/Wind Harmer
6.898
253372AE2-315 SEC3
Adder
2.063
253372AE2-315 SEC3
Adder
2.063
25306009OHH W.
Adder
3.13
253349AC2-067 GEN
Solar/Wind Harmer
2.381
253400AC2-068 GEN
Solar/Wind Harmer
0.958
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
0.953
965051AG1-369 GEN
Solar/Wind Harmer
3.739
965041AG1-368 GEN
Solar/Wind Harmer
7.471
247607V1-011 GEN
Solar/Wind Harmer
0.001
971567AH1-282 GEN
Solar/Wind Harmer
11.206
971989AH1-539 GEN
Solar/Wind Harmer
3.215
963791AG1-232 GEN
Solar/Wind Harmer
10.044
24729505KEY G4
Adder
6.919
270071AF1-092 GEN
Solar/Wind Harmer
14.245
971985AH1-537 GEN
Solar/Wind Harmer
2.206
270024AE2-089 GEN
Solar/Wind Harmer
0.008
270367AC2-061_GEN
Solar/Wind Harmer
0.006
965101AG1-375 GEN
Solar/Wind Harmer
7.401
971673AH1-337 GEN
Solar/Wind Harmer
4.804
252524AE2-267 GEN
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
9.344
25196308WSDLE2
Adder
9.263
25196208WSDLE1
Adder
9.24
25196708WSDLE6
Adder
9.217
25196508WSDLE4
Adder
8.984
971029AG2-637 GEN
Solar/Wind Harmer
11.085
270543AE2-219 C
Solar/Wind Harmer
0.004
945581AF1-223 GEN
Solar/Wind Harmer
0.001
270297AD1-101 GEN
Solar/Wind Harmer
0.002
971347AH1-153 GEN
Solar/Wind Harmer
11.025
971609AH1-304 GEN
Solar/Wind Harmer
1.2
270240V3-007_GEN2
Solar/Wind Harmer
0.002
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
970115AG2-085 GEN
Solar/Wind Harmer
2.932
270594AE1-207 GEN
Solar/Wind Harmer
8.194
970289AG2-191 GEN
Solar/Wind Harmer
1.389
971771AH1-392 GEN
Solar/Wind Harmer
7.306
971619AH1-309 GEN
Solar/Wind Harmer
3.285
971769AH1-391 GEN
Solar/Wind Harmer
8.134
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
25196108MFTGT2
Adder
1.599
25196108MFTGT2
Adder
1.484
270536AF1-215 GEN2
Solar/Wind Harmer
0.009
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
4.302
971549AH1-272 GEN
Solar/Wind Harmer
14.865
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
24318805MLG1
50/50
10.095
23559001PLEAS1
50/50
6.1
270051AF1-062 GEN
50/50
11.821
270475AD2-096_GEN
50/50
7.141
970153AG2-106 GEN
Solar/Wind Harmer
22.046
961921AG1-034 GEN
Solar/Wind Harmer
7.615
241955AC1-078 GEN
Solar/Wind Harmer
0.007
24721905FLATG4
Adder
23.918
241974AD2-163_GEN2
Solar/Wind Harmer
0.006
942051AE2-217 GEN
Solar/Wind Harmer
14.671
970605AG2-385 GEN
Solar/Wind Harmer
4.899
270391AF1-285 GEN3
Solar/Wind Harmer
0.536
253338AC1-165 GEN
Solar/Wind Harmer
0.003
253333AC1-068 GEN
Solar/Wind Harmer
0.012
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270273AD2-016 GEN
Solar/Wind Harmer
0.821
972173AH1-669 GEN
Solar/Wind Harmer
3.952
270291AC1-194 GEN
Solar/Wind Harmer
6.106
253415AE1-040 GEN
Solar/Wind Harmer
0.003
270512AE1-227 GEN2
Solar/Wind Harmer
1.963
970065AG2-057 GEN
Solar/Wind Harmer
0.76
253370AE2-315 SEC1
Adder
2.182
253371AE2-315 SEC2
Adder
2.063
253406AD2-031_GEN
Solar/Wind Harmer
0.563
970191AG2-125 GEN
Solar/Wind Harmer
1.945
270491AE1-102 GEN2
Solar/Wind Harmer
0.979
270377AD1-106 GEN
Solar/Wind Harmer
2.855
971191AH1-055 GEN
Solar/Wind Harmer
19.26
253316AC1-085 GEN3
Solar/Wind Harmer
0.005
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
9.749
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.048
959331AF2-224 GEN
Solar/Wind Harmer
5.242
965021AG1-366 GEN
Solar/Wind Harmer
2.496
270588AE1-091_GEN
Solar/Wind Harmer
5.845
944531AF1-118 GEN
Solar/Wind Harmer
33.395
270043AE2-236 GEN
Solar/Wind Harmer
4.777
270258AD1-119 GEN
Solar/Wind Harmer
0.002
971617AH1-308 GEN
Solar/Wind Harmer
6.173
25196608WSDLE5
Adder
9.077
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
252510AF1-249 C
Solar/Wind Harmer
0.057
957741AF2-068 GEN
Solar/Wind Harmer
11.081
25194608D.CRK4
Adder
1.74
270222AC2-111 GEN
Solar/Wind Harmer
3.739
970031AG2-029 GEN
Solar/Wind Harmer
4.795
270404AC1-167 GEN
Solar/Wind Harmer
0.003
970513AG2-328 GEN
Solar/Wind Harmer
3.191
970517AG2-330 GEN
Solar/Wind Harmer
19.146
970349AG2-230 GEN
Solar/Wind Harmer
11.025
946031AF1-268 GEN
Solar/Wind Harmer
6.992
958821AF2-173 GEN
Solar/Wind Harmer
10.273
270004AE1-209 GEN
Solar/Wind Harmer
1.59
270437AC2-090 C
Solar/Wind Harmer
0.003
247643Z2-116 C
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.804
970291AG2-192 GEN
Solar/Wind Harmer
0.731
247642Z2-115 C
Solar/Wind Harmer
0.003
945111AF1-176 GEN
Solar/Wind Harmer
5.919
24642205MAYFLWER
Adder
0.665
25196008MFTGT1
Adder
1.405
270356AE2-297 GEN
Solar/Wind Harmer
0.01
24441205WTRV SLR C
Solar/Wind Harmer
0
247604X1-042
Adder
0.433
270535AF1-215 GEN1
Solar/Wind Harmer
0.009
964401AG1-302 GEN
Solar/Wind Harmer
0.001
970217AG2-149 GEN
Solar/Wind Harmer
6.268
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
7.196
970243AG2-164 GEN
Solar/Wind Harmer
4.205
970519AG2-331 GEN
Solar/Wind Harmer
18.687
970699AG2-449 GEN
Solar/Wind Harmer
1.797
274752CRETE EC ;2U
Adder
8.477
274753CRETE EC ;3U
Adder
8.477
958171AF2-111 GEN
Solar/Wind Harmer
17.94
274772LINCOLN ;3U
Adder
8.676
274724RIVER EC ;11
Adder
18.203
972167AH1-666 GEN
Solar/Wind Harmer
5.717
24728705AND G3
Adder
8.214
274802UNIV PARK;5U
Adder
5.97
24728505AND G1
Adder
3.927
276806AD2-047 C O1
Solar/Wind Harmer
4.047
970941AG2-585 GEN
Solar/Wind Harmer
8.927
274826FISK ;BP
Adder
11.205
274800UNIV PARK;3U
Adder
5.966
972038AH1-567 GEN2
Adder
0.373
972228AH1-698 GEN2
Adder
3.79
276897AD1-100 C
Solar/Wind Harmer
0.009
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
970707AG2-453 GEN
Solar/Wind Harmer
23.303
274676JOLIET 29;8U
Adder
30.185
276893AG1-478 C
Solar/Wind Harmer
0.282
274729ELWOOD EC;1P
Adder
16.768
274730ELWOOD EC;6P
Adder
16.768
274734ELWOOD EC;8P
Adder
16.768
274736ELWOOD EC;9P
Adder
16.768
943121AE2-341 GEN
Solar/Wind Harmer
11.888
943591AF1-030 GEN
Solar/Wind Harmer
7.906
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
270541AE2-072 C
Solar/Wind Harmer
0.009
274682WAUKEGAN ;7U
Adder
9.728
276805AD2-038 GEN
Solar/Wind Harmer
0.002
964991AG1-363 GEN
Solar/Wind Helper
5.136
316097T157 G90
Solar/Wind Helper
1.504
23750701CROSSCHOOL
Solar/Wind Helper
1.502
238118U2-030_1
Solar/Wind Helper
0.341
238127S14_GEN_2
Solar/Wind Helper
0.827
238148AE2-230_GEN2
Solar/Wind Helper
0.497
237080AD1-060 GEN
Solar/Wind Helper
0.342
237038AE2-054 C
Solar/Wind Helper
0.272
235062AE1-101 C1
Solar/Wind Helper
1.659
23779801AA1-109
Solar/Wind Helper
0.193
237048AF1-022 C
Solar/Wind Helper
0.177
223401AF1-299 GEN
Solar/Wind Helper
0.367
316006AB2-029 C
Solar/Wind Helper
0.117
966131AG1-482 GEN
Solar/Wind Helper
0.137
233930AB2-032 GEN
Solar/Wind Helper
0.381
233915AB1-141 GEN
Solar/Wind Helper
0.502
232422X3-066 FULL
Solar/Wind Helper
0.114
232428Y3-058 C
Solar/Wind Helper
0.338
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
233998TM1NIN_3.36
Solar/Wind Helper
0.261
232404W1-003 C
Solar/Wind Helper
0.507
232434Z2-077 GEN
Solar/Wind Helper
0.127
233954AC2-188 GEN
Solar/Wind Helper
0.232
233950AC2-186 GEN
Solar/Wind Helper
0.116
233972AC1-094 C
Solar/Wind Helper
0.302
316045AC1-158 PL2
Solar/Wind Helper
4.138
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.23
228728W1-130C
Solar/Wind Helper
0.054
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219904AC1-010 C
Solar/Wind Helper
0.06
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.131
20720728JCB_W1-129
Solar/Wind Helper
0.057
316254AC1-120 GEN1
Solar/Wind Helper
1.059
207445AB1-138_GEN
Solar/Wind Helper
0.104
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.13
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.31
20715228NPK_W1-113
Solar/Wind Helper
0.078
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.495
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
207437AD2-070 GEN
Solar/Wind Helper
0.138
207518AF1-320_GEN
Solar/Wind Helper
1.571
20671928W4-073
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.029
270166AC1-044 GEN3
50/50
7.059
23559101PLEAS2
50/50
6.1
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
8.676
274776LINCOLN ;7U
Adder
8.676
274777LINCOLN ;8U
Adder
8.676
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
274814UNIV PK N;0U
Adder
5.184
274807UNIV PK N;3U
Adder
5.173
274805UNIV PK N;1U
Adder
5.15
274811UNIV PK N;7U
Adder
5.139
972037AH1-567 GEN1
Adder
0.187
960591AF2-350 GEN
Solar/Wind Harmer
7.141
274827FISK ;RP
Adder
7.941
972227AH1-698 GEN1
Adder
2.669
963841AG1-237 GEN
Solar/Wind Harmer
3.09
972163AH1-664 GEN
Solar/Wind Harmer
7.933
972165AH1-665 GEN
Solar/Wind Harmer
6.354
274687WILL CNTY;4U
Adder
28.523
274687WILL CNTY;4U
Adder
28.523
274675JOLIET 29;7U
Adder
31.303
274675JOLIET 29;7U
Adder
30.185
274731ELWOOD EC;2P
Adder
16.768
274733ELWOOD EC;3P
Adder
16.768
274735ELWOOD EC;4P
Adder
16.768
274728ELWOOD EC;5P
Adder
16.768
970833AG2-524 GEN
Solar/Wind Harmer
7.824
970833AG2-524 GEN
Solar/Wind Harmer
5.216
274746AC1-111 G10
Adder
5.679
274744AC1-111 GEN8
Adder
5.679
972203AH1-686 GEN
Adder
2.338
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
276868AE1-113 GEN
Solar/Wind Harmer
1.414
276882AE2-255 GEN
Solar/Wind Harmer
0.824
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238126S14_GEN_1
Solar/Wind Helper
0.827
238152AF2-075_GEN
Solar/Wind Helper
0.707
238208AF1-136 C
Solar/Wind Helper
0.22
23546401DTGZ2-030
Solar/Wind Helper
0.089
237085AD2-009_GEN
Solar/Wind Helper
1.649
3138216PACIFIC
Solar/Wind Helper
0.044
316411AF1-147_GEN1
Solar/Wind Helper
0.888
316415AF1-147_GEN2
Solar/Wind Helper
0.888
23750501ELLIOTTS
Solar/Wind Helper
0.638
959381AF2-229 GEN
Solar/Wind Helper
0.357
3141426STAFORD
Solar/Wind Helper
0.052
960921AF2-383 GEN
Solar/Wind Helper
0.364
205943AE1-185 GEN
Solar/Wind Helper
0.509
205932AD2-116_GEN
Solar/Wind Helper
0.509
205956AE1-196_GEN
Solar/Wind Helper
0.509
233935AB2-179 C
Solar/Wind Helper
1.269
232436AB1-176 C
Solar/Wind Helper
0.044
233923SMA
Solar/Wind Helper
0.958
233990AG1-397 GEN
Solar/Wind Helper
0.27
232432Z2-076 GEN
Solar/Wind Helper
0.067
234033AF1-007_GEN
Solar/Wind Helper
7.02
964001AG1-254 GEN
Solar/Wind Helper
0.955
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.115
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.08
203975AE1-071-GEN
Solar/Wind Helper
2.498
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.29
219620RIDERU C
Solar/Wind Helper
0.001
316164AC1-076 GEN
Solar/Wind Helper
1.096
20675528CPH_W2-050
Solar/Wind Helper
0.087
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
218524CNTRALGAS1 C
Solar/Wind Helper
0.16
966261AG1-495 GEN
Solar/Wind Helper
0.081
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20675928HOL_W4-097
Solar/Wind Helper
0.05
207484AF2-139 C O1
Solar/Wind Helper
0.084
20674828DL_W4-046
Solar/Wind Helper
0.008
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.136
20675128HRM_W1-127
Solar/Wind Helper
0.029
209116AE2-175 GEN
Solar/Wind Helper
1.778
270119AB2-067 GEN1
50/50
7.059
270120AB2-067 GEN2
50/50
7.059
24318905MLG2
50/50
7.071
270471AD2-092_GEN
Solar/Wind Harmer
0.006
942861AE2-305 GEN
Solar/Wind Harmer
6.335
970077AG2-063 GEN
Solar/Wind Harmer
4.631
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
938701AE1-092 GEN
Solar/Wind Harmer
12.917
971655AH1-328 GEN
Solar/Wind Harmer
2.854
964601AG1-323 GEN
Solar/Wind Harmer
3.215
964601AG1-323 GEN
Solar/Wind Harmer
2.143
270518AE2-148 GEN
Solar/Wind Harmer
0.691
972269AH1-719 GEN
Adder
2.584
972159AH1-661 GEN
Adder
1.118
253378AE2-206_GEN
Solar/Wind Harmer
0.004
276820AF1-078_GEN
Solar/Wind Harmer
0.002
970329AG2-216 GEN
Solar/Wind Harmer
3.354
971199AH1-059 GEN
Solar/Wind Harmer
3.09
241960AC2-195 GEN
Solar/Wind Harmer
0.006
25326509SID D
Adder
1.451
971073AG2-665 GEN
Solar/Wind Harmer
6.898
25326109MON D
Adder
1.443
25322209TAIT E
Adder
10.642
25322209TAIT E
Adder
10.403
971201AH1-060 GEN
Solar/Wind Harmer
1.52
253370AE2-315 SEC1
Adder
2.182
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
246938BC-WTG3
Solar/Wind Harmer
0.273
246937BC-WTG2
Solar/Wind Harmer
0.305
971231AH1-075 GEN
Solar/Wind Harmer
0.861
253317AC1-085 GEN4
Solar/Wind Harmer
0.005
970611AG2-400 GEN
Solar/Wind Harmer
7.488
970627AG2-408 GEN
Solar/Wind Harmer
2.246
270007AE1-245 C
Solar/Wind Harmer
0.002
962581AG1-107 GEN
Solar/Wind Harmer
0.002
25183208HLCRTG
Solar/Wind Harmer
0.012
944541AF1-119 GEN
Solar/Wind Harmer
0.497
960971AF2-388 GEN
Solar/Wind Harmer
4.347
970623AG2-406 GEN
Solar/Wind Harmer
1.356
942221AE2-234 GEN
Solar/Wind Harmer
0.037
252519AF1-045_GEN
Solar/Wind Harmer
6.44
252516AE2-318_GEN
Solar/Wind Harmer
5.712
247621Y3-024
Adder
0.255
970883AG2-550 GEN
Solar/Wind Harmer
7.389
970885AG2-551 GEN
Solar/Wind Harmer
2.463
270201AC2-176 GEN
Solar/Wind Harmer
0.001
25194408D.CRK1
Adder
8.004
25194508D.CRK3
Adder
1.496
970621AG2-405 GEN
Solar/Wind Harmer
1.351
964611AG1-324 GEN
Solar/Wind Harmer
0.553
252509AD1-136 GEN
Solar/Wind Harmer
0.037
970321AG2-212 GEN
Solar/Wind Harmer
3.191
270599AE1-208 GEN
Solar/Wind Harmer
6.737
270031AE2-169
Solar/Wind Harmer
4.042
270186AC1-089 GEN
Solar/Wind Harmer
0.004
270383AD1-128 GEN
Solar/Wind Harmer
0.004
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
970825AG2-519 GEN
Solar/Wind Harmer
8.127
247620Y3-023
Adder
0.484
960441AF2-335 GEN
Solar/Wind Harmer
7.33
270216AD2-079_GEN
Solar/Wind Harmer
0.001
971613AH1-306 GEN
Solar/Wind Harmer
3.512
24728805RICHG1
Adder
3.964
24728905RICHG2
Adder
3.964
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
14.589
961051AF2-396 GEN
Solar/Wind Harmer
9.726
270526AF1-158 GEN
Solar/Wind Harmer
0.009
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
9.095
965791AG1-447 GEN
Solar/Wind Harmer
6.67
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
970239AG2-162 GEN
Solar/Wind Harmer
1.797
274770LINCOLN ;1U
Adder
8.676
274771LINCOLN ;2U
Adder
8.676
966841AG1-555 GEN
Solar/Wind Harmer
0.81
274808UNIV PK N;4U
Adder
5.117
274803UNIV PARK;6U
Adder
5.97
274888KELLY CRK;1U
Solar/Wind Harmer
0.419
274887GEN-1.85
Solar/Wind Harmer
0.188
276843GEN-1.7
Solar/Wind Harmer
0.231
958011AF2-095 GEN
Solar/Wind Harmer
10.284
972259AH1-714 GEN
Adder
19.507
274674JOLIET 9 ;6U
Adder
15.704
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
970241AG2-163 GEN
Solar/Wind Harmer
4.144
958481AF2-142 GEN
Solar/Wind Harmer
10.621
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.958
971573AH1-285 GEN
Solar/Wind Harmer
1.319
274696ROCKY RD ;4P
Adder
11.537
274695ROCKY RD ;2P
Adder
11.271
274693ROCKY RD ;1P
Adder
11.16
274697ROCKY RD ;3P
Adder
3.062
958491AF2-143 GEN
Solar/Wind Harmer
10.588
274879MINONK ;1U
Solar/Wind Harmer
0.297
23585401KL_K28_T16
Solar/Wind Helper
1.482
238120AE2-309 GEN
Solar/Wind Helper
0.525
238175AF1-290_GEN
Solar/Wind Helper
0.153
238169AE2-226 GEN1
Solar/Wind Helper
0.701
238170AE2-226 GEN2
Solar/Wind Helper
0.701
235020AA1-095 C
Solar/Wind Helper
0.053
23777901MDS_W4-102
Solar/Wind Helper
0.177
237002AB1-128_GEN
Solar/Wind Helper
0.443
237034AC2-136 C
Solar/Wind Helper
0.227
235063AE1-101 C2
Solar/Wind Helper
1.659
237001AB1-127_GEN
Solar/Wind Helper
0.442
23777801MSM_W1-116
Solar/Wind Helper
0.114
237025AB1-124 C
Solar/Wind Helper
0.164
237006AB1-125 GEN
Solar/Wind Helper
0.123
226929AD2-058 GEN
Solar/Wind Helper
0.099
205916AD1-020 GEN
Solar/Wind Helper
1.713
20390526W1-045 C
Solar/Wind Helper
0.35
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
233987AB2-037 GEN
Solar/Wind Helper
2.342
233933AB2-153 GEN
Solar/Wind Helper
0.232
233944AB2-135 GEN
Solar/Wind Helper
0.588
232424Y1-079 C
Solar/Wind Helper
0.116
234036AF2-325 C
Solar/Wind Helper
0.042
233946AB2-136 GEN
Solar/Wind Helper
0.568
233901CHERRYDALE C
Solar/Wind Helper
0.232
232408W1-005 C
Solar/Wind Helper
0.507
232410W1-006 C
Solar/Wind Helper
0.507
233939AC1-091 C
Solar/Wind Helper
0.35
233970AC1-092 C
Solar/Wind Helper
0.35
315651AD1-115 GEN
Solar/Wind Helper
0.785
316447AC1-158 HLD
Solar/Wind Helper
2.845
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.04
219921AF1-264
Solar/Wind Helper
0.051
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.082
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.19
20716928W4-060COL
Solar/Wind Helper
0.051
218440SUMMTASSOC C
Solar/Wind Helper
0.016
20673828FLE_V3-070
Solar/Wind Helper
0.09
207442AE1-156 GEN
Solar/Wind Helper
0.326
20676128MHD_W3-029
Solar/Wind Helper
0.096
20671828STAW2-080
Solar/Wind Helper
0.027
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
207471AF2-354 C
Solar/Wind Helper
0.168
20674928WA_W3-044
Solar/Wind Helper
0.098
20676228FRD_X1-012
Solar/Wind Helper
0.092
964851AG1-348 GEN
Solar/Wind Helper
0.081
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.074
211065PSPA IPP
Solar/Wind Helper
0.151
211065PSPA IPP
Solar/Wind Helper
0.151
962761AG1-125 GEN
Solar/Wind Harmer
34.524
970149AG2-104 GEN
Solar/Wind Harmer
37.287
970155AG2-107 GEN
Solar/Wind Harmer
22.046
270349AD2-093_GEN
Solar/Wind Harmer
0.006
24721705FLATG2
Adder
23.918
270159DARBY CT4
Adder
10.243
970593AG2-378 GEN
Solar/Wind Harmer
1.812
270223U2-072_GEN1
Solar/Wind Harmer
0.001
253343AC1-166 GEN
Solar/Wind Harmer
0.003
253325AC1-069 GEN
Solar/Wind Harmer
0.012
270462AD2-086
Solar/Wind Harmer
0.017
971995AH1-542 GEN
Solar/Wind Harmer
2.906
270263AC1-001 GEN
Solar/Wind Harmer
0.786
270510AE1-227 GEN1
Solar/Wind Harmer
1.963
25326309TAIT D
Adder
1.196
241813AF1-122_GEN
Solar/Wind Harmer
3.405
960071AF2-298 GEN
Solar/Wind Harmer
3.786
253370AE2-315 SEC1
Adder
2.182
253371AE2-315 SEC2
Adder
2.063
927014AC1-188 GEN
Solar/Wind Harmer
0.005
246936BC-WTG1
Solar/Wind Harmer
0.305
270489AE1-102 GEN1
Solar/Wind Harmer
0.979
965421AG1-410 GEN
Solar/Wind Harmer
22.57
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.499
247521TR3_G114
Solar/Wind Harmer
0.273
270246TR4_N_V150
Solar/Wind Harmer
0.048
965011AG1-365 GEN
Solar/Wind Harmer
7.488
24695305TIMB G C
Solar/Wind Harmer
0.002
965651AG1-433 GEN
Solar/Wind Harmer
2.174
958861AF2-177 GEN
Solar/Wind Harmer
3.207
247536S-71 GEN
Solar/Wind Harmer
0.297
25194608D.CRK4
Adder
1.74
945371AF1-202 GEN
Solar/Wind Harmer
0.001
252507AC2-088 GEN
Solar/Wind Harmer
0.335
270063AE2-323 C
Solar/Wind Harmer
0.006
970245AG2-165 GEN
Solar/Wind Harmer
3.191
970947AG2-589 GEN
Solar/Wind Harmer
0.245
270005AE1-210 C O1
Solar/Wind Harmer
1.59
965031AG1-367 GEN
Solar/Wind Harmer
7.338
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.378
970825AG2-519 GEN
Solar/Wind Harmer
2.603
25196808ZIMRHP
Adder
79.729
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
944231AF1-091 GEN
Solar/Wind Harmer
1.953
24639705ELKHART HY
Adder
0.161
270032AE2-172
Solar/Wind Harmer
4.877
970291AG2-192 GEN
Solar/Wind Harmer
0.95
945111AF1-176 GEN
Solar/Wind Harmer
13.03
270505AE1-170 C O1
Solar/Wind Harmer
7.665
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.805
276903AD2-071 C
Solar/Wind Harmer
8.137
25196008MFTGT1
Adder
1.45
247522W1-056 GEN
Solar/Wind Harmer
0.001
970773AG2-487 GEN
Solar/Wind Harmer
1.284
970373AG2-245 GEN
Solar/Wind Harmer
15.247
270055AF2-134 C O1
Solar/Wind Harmer
0.006
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.41
970515AG2-329 GEN
Solar/Wind Harmer
18.805
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
9.032
24791305MDL-5G
Solar/Wind Harmer
0.001
970333AG2-219 GEN
Solar/Wind Harmer
5.139
274751CRETE EC ;1U
Adder
8.477
274754CRETE EC ;4U
Adder
8.477
274773LINCOLN ;4U
Adder
8.676
274774LINCOLN ;5U
Adder
8.676
274723RIVER EC ;12
Adder
18.418
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
5.139
24728605AND G2
Adder
3.927
276776AD2-060 GEN
Solar/Wind Harmer
0.746
945681AF1-233 GEN
Solar/Wind Harmer
13.461
274801UNIV PARK;4U
Adder
5.966
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
31.303
274732ELWOOD EC;7P
Adder
16.768
274674JOLIET 9 ;6U
Adder
15.704
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
963741AG1-226 GEN
Solar/Wind Harmer
16.815
274745AC1-111 GEN9
Adder
5.679
939401AE1-172 GEN
Solar/Wind Harmer
5.301
276691AA1-018 GEN1
Solar/Wind Harmer
0.858
970091AG2-072 GEN
Adder
77.629
276901AD2-066 C O1
Solar/Wind Harmer
0.007
316095T157 G97
Solar/Wind Helper
1.504
23583801GRNGAP
Solar/Wind Helper
5.601
238185AF2-356 C
Solar/Wind Helper
2.646
238108AE1-109 GEN1
Solar/Wind Helper
0.114
235054AD2-180 GEN
Solar/Wind Helper
2.03
235531U2-073 GEN
Solar/Wind Helper
3.282
238117U2-030
Solar/Wind Helper
0.341
238147AE2-230_GEN1
Solar/Wind Helper
0.495
238149AF1-291A_GEN
Solar/Wind Helper
0.141
23751201ROTHROCK
Solar/Wind Helper
0.824
237061AD1-155 GEN
Solar/Wind Helper
0.053
23562501BACKB
Solar/Wind Helper
1.007
238221AF1-254 C O1
Solar/Wind Helper
0.274
235067AD1-061 GEN
Solar/Wind Helper
0.496
23751101LEADS_P59
Solar/Wind Helper
1.404
237030AB1-096 C
Solar/Wind Helper
0.071
3141196NOKESVL
Solar/Wind Helper
1.032
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.346
223402AF1-300 C
Solar/Wind Helper
0.367
205917AD1-020 ES
Solar/Wind Helper
0.368
233918AB1-142 GEN
Solar/Wind Helper
0.502
233982AB2-133 GEN
Solar/Wind Helper
0.358
233994AC2-023 GEN
Solar/Wind Helper
0.961
233996TM1833_GEN
Solar/Wind Helper
0.261
233997TMININ_4.2
Solar/Wind Helper
0.261
232406W1-004 FULL
Solar/Wind Helper
0.507
233940AF2-379 C
Solar/Wind Helper
0.062
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.232
233971AC1-093 C
Solar/Wind Helper
0.357
316044AC1-158 PL1
Solar/Wind Helper
1.293
316450AC1-158 RIC
Solar/Wind Helper
0.345
230430AE1-229_GEN
Solar/Wind Helper
3.372
230415AB2-049 C
Solar/Wind Helper
0.03
228729W2-030 C
Solar/Wind Helper
0.11
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.15
219291REEVESSOUT C
Solar/Wind Helper
0.011
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
219348LDSOLAR C
Solar/Wind Helper
0.114
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.063
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.353
219276PARKLANDSO C
Solar/Wind Helper
0.089
20714528FRN_Y2-051
Solar/Wind Helper
0.057
20720528MAN_W1-024
Solar/Wind Helper
0.028
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.027
219908AB1-139 C
Solar/Wind Helper
0.074
219249CENTRALDIV C
Solar/Wind Helper
0.01
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.089
971997AH1-543 GEN
Solar/Wind Harmer
2.724
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.078
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.1
MECLTFEXP_MEC->PJM
CLTF
15.901
SIGELTFEXP_SIGE->PJM
CLTF
0.505
LAGNLTFEXP_LAGN->PJM
CLTF
14.837
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.802
TVALTFEXP_TVA->PJM
CLTF
7.293
CPLELTFEXP_CPLE->PJM
CLTF
0.624
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.816
NYPJM->LTFIMP_NY
CLTF
4.797
LGEELTFEXP_LGEE->PJM
CLTF
6.749
WECLTFEXP_WEC->PJM
CLTF
3.825
AG2-052LTFEXP_AG2-052->PJM
LTF
0.24
AH1-155LTFEXP_AH1-155->PJM
LTF
0.359

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P2-3_MP-500-012_SRT-A


Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-012_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:131.49 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4985.98
MW Contribution:11.59
Bus #Bus NameTypeMW Contribution
24318805MLG1
50/50
10.022
23559001PLEAS1
50/50
5.443
270051AF1-062 GEN
50/50
11.999
970153AG2-106 GEN
Solar/Wind Harmer
17.863
961921AG1-034 GEN
Solar/Wind Harmer
15.919
241955AC1-078 GEN
Solar/Wind Harmer
8.948
241974AD2-163_GEN2
Solar/Wind Harmer
2.37
942051AE2-217 GEN
Solar/Wind Harmer
21.374
942871AE2-306 GEN
Solar/Wind Harmer
1.073
270391AF1-285 GEN3
Solar/Wind Harmer
0.55
960801AF2-371 GEN
Solar/Wind Harmer
2.991
964871AG1-351 GEN
Solar/Wind Harmer
2.065
970605AG2-385 GEN
Solar/Wind Harmer
6.332
270485AE1-090_GEN
Solar/Wind Harmer
0.709
270512AE1-227 GEN2
Solar/Wind Harmer
2.455
24721905FLATG4
Adder
23.506
253338AC1-165 GEN
Solar/Wind Harmer
1.256
253333AC1-068 GEN
Solar/Wind Harmer
1.211
970065AG2-057 GEN
Solar/Wind Harmer
1.148
270273AD2-016 GEN
Solar/Wind Harmer
3.061
972173AH1-669 GEN
Solar/Wind Harmer
5.721
270377AD1-106 GEN
Solar/Wind Harmer
6.988
270588AE1-091_GEN
Solar/Wind Harmer
12.311
270291AC1-194 GEN
Solar/Wind Harmer
11.854
253415AE1-040 GEN
Solar/Wind Harmer
1.258
961961AG1-039 GEN
Solar/Wind Harmer
3.188
270491AE1-102 GEN2
Solar/Wind Harmer
1.443
970217AG2-149 GEN
Solar/Wind Harmer
35.355
270166AC1-044 GEN3
50/50
7.033
23559101PLEAS2
50/50
5.443
270122AB2-093 CT
50/50
4.116
962761AG1-125 GEN
Solar/Wind Harmer
40.965
970149AG2-104 GEN
Solar/Wind Harmer
50.592
970155AG2-107 GEN
Solar/Wind Harmer
17.863
270349AD2-093_GEN
Solar/Wind Harmer
4.529
270223U2-072_GEN1
Solar/Wind Harmer
2.339
270578AF1-285 GEN2
Solar/Wind Harmer
1.43
270391AF1-285 GEN3
Solar/Wind Harmer
1.43
270159DARBY CT4
Adder
10.388
971995AH1-542 GEN
Solar/Wind Harmer
12.974
970593AG2-378 GEN
Solar/Wind Harmer
2.345
270462AD2-086
Solar/Wind Harmer
8.157
270510AE1-227 GEN1
Solar/Wind Harmer
2.893
24721705FLATG2
Adder
23.506
253343AC1-166 GEN
Solar/Wind Harmer
1.256
253325AC1-069 GEN
Solar/Wind Harmer
1.211
241813AF1-122_GEN
Solar/Wind Harmer
7.346
270263AC1-001 GEN
Solar/Wind Harmer
1.187
241847AF2-150_GEN
Solar/Wind Harmer
4.622
246936BC-WTG1
Solar/Wind Harmer
4.343
270489AE1-102 GEN1
Solar/Wind Harmer
1.443
965421AG1-410 GEN
Solar/Wind Harmer
33.256
970515AG2-329 GEN
Solar/Wind Harmer
16.033
25326309TAIT D
Adder
1.21
960071AF2-298 GEN
Solar/Wind Harmer
5.501
253370AE2-315 SEC1
Adder
2.206
253371AE2-315 SEC2
Adder
2.086
247521TR3_G114
Solar/Wind Harmer
3.699
270246TR4_N_V150
Solar/Wind Harmer
0.936
247522W1-056 GEN
Solar/Wind Harmer
2.477
24695305TIMB G C
Solar/Wind Harmer
6.051
965011AG1-365 GEN
Solar/Wind Harmer
10.972
927014AC1-188 GEN
Solar/Wind Harmer
1.729
944231AF1-091 GEN
Solar/Wind Harmer
4.078
253432AC1-085 GEN2
Solar/Wind Harmer
0.29
946171AF1-282 GEN
Solar/Wind Harmer
10.828
270063AE2-323 C
Solar/Wind Harmer
2.376
965651AG1-433 GEN
Solar/Wind Harmer
5.885
958861AF2-177 GEN
Solar/Wind Harmer
11.752
247536S-71 GEN
Solar/Wind Harmer
4.346
960001AF2-291 GEN
Solar/Wind Harmer
3.244
945371AF1-202 GEN
Solar/Wind Harmer
7.479
24639705ELKHART HY
Adder
0.164
25194608D.CRK4
Adder
1.752
25196808ZIMRHP
Adder
80.188
23906502RICHG2&3
Adder
1.272
972301AH1-735 GEN
Adder
6.357
23906402RICHG1
Adder
1.271
25196008MFTGT1
Adder
1.459
274751CRETE EC ;1U
Adder
8.598
274754CRETE EC ;4U
Adder
8.598
274723RIVER EC ;12
Adder
18.677
274773LINCOLN ;4U
Adder
8.792
274774LINCOLN ;5U
Adder
8.792
274812UNIV PK N;8U
Adder
5.21
23920202STRYCT
Adder
1.444
274801UNIV PARK;4U
Adder
6.045
274676JOLIET 29;8U
Adder
31.706
274732ELWOOD EC;7P
Adder
2.004
23583801GRNGAP
Solar/Wind Helper
6.365
316095T157 G97
Solar/Wind Helper
1.705
238108AE1-109 GEN1
Solar/Wind Helper
0.121
238185AF2-356 C
Solar/Wind Helper
2.767
238147AE2-230_GEN1
Solar/Wind Helper
0.552
238149AF1-291A_GEN
Solar/Wind Helper
0.158
237061AD1-155 GEN
Solar/Wind Helper
0.06
235054AD2-180 GEN
Solar/Wind Helper
2.111
235531U2-073 GEN
Solar/Wind Helper
3.439
238117U2-030
Solar/Wind Helper
0.356
238221AF1-254 C O1
Solar/Wind Helper
0.295
235067AD1-061 GEN
Solar/Wind Helper
0.532
3141196NOKESVL
Solar/Wind Helper
1.141
23751201ROTHROCK
Solar/Wind Helper
0.819
237030AB1-096 C
Solar/Wind Helper
0.075
23562501BACKB
Solar/Wind Helper
0.997
226910AB2-157 C
Solar/Wind Helper
0.015
227287AC2-120 GEN
Solar/Wind Helper
0.375
223402AF1-300 C
Solar/Wind Helper
0.387
316044AC1-158 PL1
Solar/Wind Helper
1.443
316450AC1-158 RIC
Solar/Wind Helper
0.385
316170AC1-121 GEN2
Solar/Wind Helper
0.395
23751101LEADS_P59
Solar/Wind Helper
1.316
205917AD1-020 ES
Solar/Wind Helper
0.379
3132273ORANGE
Solar/Wind Helper
0.049
233918AB1-142 GEN
Solar/Wind Helper
0.511
233982AB2-133 GEN
Solar/Wind Helper
0.364
233994AC2-023 GEN
Solar/Wind Helper
0.977
233996TM1833_GEN
Solar/Wind Helper
0.266
233997TMININ_4.2
Solar/Wind Helper
0.266
232406W1-004 FULL
Solar/Wind Helper
0.516
3147666LOUISA
Solar/Wind Helper
0.551
233940AF2-379 C
Solar/Wind Helper
0.063
234015AF2-250 C
Solar/Wind Helper
0.039
233952AC2-187 GEN
Solar/Wind Helper
0.236
233971AC1-093 C
Solar/Wind Helper
0.363
230430AE1-229_GEN
Solar/Wind Helper
3.409
230415AB2-049 C
Solar/Wind Helper
0.031
228729W2-030 C
Solar/Wind Helper
0.112
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.151
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
219348LDSOLAR C
Solar/Wind Helper
0.115
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.064
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.057
219276PARKLANDSO C
Solar/Wind Helper
0.09
20714528FRN_Y2-051
Solar/Wind Helper
0.057
20720528MAN_W1-024
Solar/Wind Helper
0.028
966881AG1-559 GEN
Solar/Wind Helper
0.312
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.027
219249CENTRALDIV C
Solar/Wind Helper
0.01
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.089
270119AB2-067 GEN1
50/50
7.033
270120AB2-067 GEN2
50/50
7.033
24318905MLG2
50/50
7.475
270471AD2-092_GEN
Solar/Wind Harmer
4.529
946101AF1-275 GEN
Solar/Wind Harmer
1.842
938701AE1-092 GEN
Solar/Wind Harmer
24.483
270224U2-072_GEN2
Solar/Wind Harmer
2.339
270227U2-072_GEN3
Solar/Wind Harmer
2.339
270228U2-072_GEN4
Solar/Wind Harmer
2.339
270231U2-072_GEN5
Solar/Wind Harmer
2.339
942861AE2-305 GEN
Solar/Wind Harmer
9.223
964601AG1-323 GEN
Solar/Wind Harmer
3.753
964601AG1-323 GEN
Solar/Wind Harmer
1.746
972269AH1-719 GEN
Adder
2.7
970077AG2-063 GEN
Solar/Wind Harmer
6.332
972159AH1-661 GEN
Adder
1.166
270518AE2-148 GEN
Solar/Wind Harmer
14.068
971199AH1-059 GEN
Solar/Wind Harmer
4.644
241960AC2-195 GEN
Solar/Wind Harmer
3.219
971201AH1-060 GEN
Solar/Wind Harmer
2.296
253378AE2-206_GEN
Solar/Wind Harmer
4.086
276820AF1-078_GEN
Solar/Wind Harmer
1.815
971231AH1-075 GEN
Solar/Wind Harmer
0.905
25326509SID D
Adder
1.48
25326109MON D
Adder
1.461
246938BC-WTG3
Solar/Wind Harmer
4.418
246937BC-WTG2
Solar/Wind Harmer
4.343
970879AG2-548 GEN
Solar/Wind Harmer
6.827
971073AG2-665 GEN
Solar/Wind Harmer
6.827
971073AG2-665 GEN
Solar/Wind Harmer
4.763
25322209TAIT E
Adder
10.77
25322209TAIT E
Adder
10.528
270007AE1-245 C
Solar/Wind Harmer
6.539
942801AE2-298 GEN
Solar/Wind Harmer
1.667
253370AE2-315 SEC1
Adder
2.206
970611AG2-400 GEN
Solar/Wind Harmer
10.972
253394AE2-221_GEN
Solar/Wind Harmer
4.954
253398AE2-221_GEN2
Solar/Wind Harmer
4.954
253317AC1-085 GEN4
Solar/Wind Harmer
9.07
971677AH1-339 GEN
Solar/Wind Harmer
8.643
942221AE2-234 GEN
Solar/Wind Harmer
0.79
944541AF1-119 GEN
Solar/Wind Harmer
4.511
960971AF2-388 GEN
Solar/Wind Harmer
11.771
247621Y3-024
Adder
0.259
270201AC2-176 GEN
Solar/Wind Harmer
5.522
970883AG2-550 GEN
Solar/Wind Harmer
10.73
970885AG2-551 GEN
Solar/Wind Harmer
2.495
247620Y3-023
Adder
0.494
964611AG1-324 GEN
Solar/Wind Harmer
1.264
964611AG1-324 GEN
Solar/Wind Harmer
0.561
25194408D.CRK1
Adder
8.061
25194508D.CRK3
Adder
1.507
24728805RICHG1
Adder
4.003
24728905RICHG2
Adder
4.003
970935AG2-582 GEN
Adder
239.406
274770LINCOLN ;1U
Adder
8.792
274771LINCOLN ;2U
Adder
8.792
274808UNIV PK N;4U
Adder
5.188
274803UNIV PARK;6U
Adder
6.05
972259AH1-714 GEN
Adder
19.76
238175AF1-290_GEN
Solar/Wind Helper
0.168
238169AE2-226 GEN1
Solar/Wind Helper
0.772
238170AE2-226 GEN2
Solar/Wind Helper
0.772
238120AE2-309 GEN
Solar/Wind Helper
0.552
23585401KL_K28_T16
Solar/Wind Helper
1.529
235020AA1-095 C
Solar/Wind Helper
0.057
23777901MDS_W4-102
Solar/Wind Helper
0.191
237034AC2-136 C
Solar/Wind Helper
0.244
237002AB1-128_GEN
Solar/Wind Helper
0.475
235063AE1-101 C2
Solar/Wind Helper
1.776
237001AB1-127_GEN
Solar/Wind Helper
0.473
23777801MSM_W1-116
Solar/Wind Helper
0.122
237025AB1-124 C
Solar/Wind Helper
0.175
237006AB1-125 GEN
Solar/Wind Helper
0.131
226929AD2-058 GEN
Solar/Wind Helper
0.108
315651AD1-115 GEN
Solar/Wind Helper
0.876
316447AC1-158 HLD
Solar/Wind Helper
3.175
205916AD1-020 GEN
Solar/Wind Helper
1.761
20390526W1-045 C
Solar/Wind Helper
0.36
208835TUHI V3-051
Solar/Wind Helper
0.025
208835TUHI V3-051
Solar/Wind Helper
0.025
3132123MT JACKSON
Solar/Wind Helper
0.764
233987AB2-037 GEN
Solar/Wind Helper
2.381
233933AB2-153 GEN
Solar/Wind Helper
0.236
232424Y1-079 C
Solar/Wind Helper
0.118
958091AF2-103 GEN
Solar/Wind Harmer
0.178
253303V4-073 C
Solar/Wind Harmer
0.128
253370AE2-315 SEC1
Adder
2.206
253371AE2-315 SEC2
Adder
2.086
270191TR4_S_V150
Solar/Wind Harmer
3.3
270247TR4_N_V136
Solar/Wind Harmer
0.936
959331AF2-224 GEN
Solar/Wind Harmer
10.972
965021AG1-366 GEN
Solar/Wind Harmer
2.552
270258AD1-119 GEN
Solar/Wind Harmer
3.051
253406AD2-031_GEN
Solar/Wind Harmer
1.398
270044AE2-322 C
Solar/Wind Harmer
1.435
270404AC1-167 GEN
Solar/Wind Harmer
1.194
957541AF2-048 GEN
Solar/Wind Harmer
1.725
270043AE2-236 GEN
Solar/Wind Harmer
5.98
944531AF1-118 GEN
Solar/Wind Harmer
37.943
253316AC1-085 GEN3
Solar/Wind Harmer
9.07
253433AC1-085 GEN1
Solar/Wind Harmer
5.758
946181AF1-283 GEN
Solar/Wind Harmer
14.077
970031AG2-029 GEN
Solar/Wind Harmer
32.394
971617AH1-308 GEN
Solar/Wind Harmer
6.274
270541AE2-072 C
Solar/Wind Harmer
4.881
971191AH1-055 GEN
Solar/Wind Harmer
23.635
962031AG1-047 GEN
Solar/Wind Harmer
3.246
957741AF2-068 GEN
Solar/Wind Harmer
16.111
25196608WSDLE5
Adder
9.143
24642205MAYFLWER
Adder
0.678
25194608D.CRK4
Adder
1.752
247604X1-042
Adder
0.444
23906502RICHG2&3
Adder
1.272
25196008MFTGT1
Adder
1.413
274752CRETE EC ;2U
Adder
8.598
274753CRETE EC ;3U
Adder
8.598
274724RIVER EC ;11
Adder
18.459
274772LINCOLN ;3U
Adder
8.792
274802UNIV PARK;5U
Adder
6.05
274826FISK ;BP
Adder
11.355
274800UNIV PARK;3U
Adder
6.045
972038AH1-567 GEN2
Adder
0.378
972228AH1-698 GEN2
Adder
3.84
274676JOLIET 29;8U
Adder
30.573
274729ELWOOD EC;1P
Adder
16.983
274730ELWOOD EC;6P
Adder
16.983
964991AG1-363 GEN
Solar/Wind Helper
5.557
316097T157 G90
Solar/Wind Helper
1.705
23750701CROSSCHOOL
Solar/Wind Helper
1.586
238148AE2-230_GEN2
Solar/Wind Helper
0.555
238127S14_GEN_2
Solar/Wind Helper
0.867
238118U2-030_1
Solar/Wind Helper
0.356
237080AD1-060 GEN
Solar/Wind Helper
0.367
237038AE2-054 C
Solar/Wind Helper
0.292
235062AE1-101 C1
Solar/Wind Helper
1.776
23779801AA1-109
Solar/Wind Helper
0.207
316006AB2-029 C
Solar/Wind Helper
0.13
223401AF1-299 GEN
Solar/Wind Helper
0.387
316045AC1-158 PL2
Solar/Wind Helper
4.618
316254AC1-120 GEN1
Solar/Wind Helper
1.184
237048AF1-022 C
Solar/Wind Helper
0.173
966131AG1-482 GEN
Solar/Wind Helper
0.079
233930AB2-032 GEN
Solar/Wind Helper
0.387
233915AB1-141 GEN
Solar/Wind Helper
0.511
232422X3-066 FULL
Solar/Wind Helper
0.116
233964AF2-378 GEN
Solar/Wind Helper
0.042
232426Y1-080 FULL
Solar/Wind Helper
0.039
233998TM1NIN_3.36
Solar/Wind Helper
0.266
232404W1-003 C
Solar/Wind Helper
0.516
232428Y3-058 C
Solar/Wind Helper
0.344
3147666LOUISA
Solar/Wind Helper
0.958
232434Z2-077 GEN
Solar/Wind Helper
0.129
233954AC2-188 GEN
Solar/Wind Helper
0.236
233950AC2-186 GEN
Solar/Wind Helper
0.118
233972AC1-094 C
Solar/Wind Helper
0.307
316192AB2-158 GEN
Solar/Wind Helper
1.608
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.232
228728W1-130C
Solar/Wind Helper
0.054
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219904AC1-010 C
Solar/Wind Helper
0.061
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.132
20720728JCB_W1-129
Solar/Wind Helper
0.057
207445AB1-138_GEN
Solar/Wind Helper
0.105
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20715228NPK_W1-113
Solar/Wind Helper
0.078
207454AA2-184 E
Solar/Wind Helper
0.311
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.497
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
207437AD2-070 GEN
Solar/Wind Helper
0.137
207518AF1-320_GEN
Solar/Wind Helper
1.568
20671928W4-073
Solar/Wind Helper
0.089
20675828AU_W4-064
Solar/Wind Helper
0.029
972239AH1-704 GEN
50/50
3.102
962771AG1-126 GEN
Solar/Wind Harmer
40.965
270459AD2-067 GEN
Solar/Wind Harmer
10.453
961821AG1-024 GEN
Solar/Wind Harmer
10.613
270054AF2-122 C O1
Solar/Wind Harmer
4.071
270284AF1-227 GEN1
Solar/Wind Harmer
6.912
270286AF1-227 GEN2
Solar/Wind Harmer
2.557
270287AF1-227 GEN3
Solar/Wind Harmer
2.557
270520AE2-214 GEN
Solar/Wind Harmer
7.382
253383AE2-342_GEN
Solar/Wind Harmer
1.062
241973AD2-163_GEN1
Solar/Wind Harmer
2.37
940611AE2-048 GEN
Solar/Wind Harmer
26.074
941391AE2-136 GEN
Solar/Wind Harmer
13.511
270578AF1-285 GEN2
Solar/Wind Harmer
0.55
943861AF1-054 GEN
Solar/Wind Harmer
4.552
943851AF1-053 GEN
Solar/Wind Harmer
2.2
945631AF1-228 GEN
Solar/Wind Harmer
5.537
270156DARBY CT1
Adder
10.556
270157DARBY CT2
Adder
10.53
270158DARBY CT3
Adder
10.362
270302AB2-170 GEN
Solar/Wind Harmer
9.805
270317AD1-130_GEN
Solar/Wind Harmer
3.759
970689AG2-444 GEN
Solar/Wind Harmer
19.055
270432AC2-029 GEN
Solar/Wind Harmer
8.138
958581AF2-149 GEN
Solar/Wind Harmer
4.968
970179AG2-119 GEN
Solar/Wind Harmer
9.26
270269AC2-059
Solar/Wind Harmer
10.704
241972AD1-140 GEN
Solar/Wind Harmer
5.084
971567AH1-282 GEN
Solar/Wind Harmer
16.984
966831AG1-554 GEN
Solar/Wind Harmer
1.34
971989AH1-539 GEN
Solar/Wind Harmer
14.49
270340AC2-060 GEN
Solar/Wind Harmer
3.371
957201AF2-014 GEN
Solar/Wind Harmer
5.033
270435AC2-044 GEN
Solar/Wind Harmer
2.219
970879AG2-548 GEN
Solar/Wind Harmer
4.763
247607V1-011 GEN
Solar/Wind Harmer
4.359
253372AE2-315 SEC3
Adder
2.086
253372AE2-315 SEC3
Adder
2.086
965051AG1-369 GEN
Solar/Wind Harmer
5.494
25306009OHH W.
Adder
3.166
270297AD1-101 GEN
Solar/Wind Harmer
3.056
965041AG1-368 GEN
Solar/Wind Harmer
10.974
253349AC2-067 GEN
Solar/Wind Harmer
5.466
253400AC2-068 GEN
Solar/Wind Harmer
2.198
963791AG1-232 GEN
Solar/Wind Harmer
14.679
270071AF1-092 GEN
Solar/Wind Harmer
16.242
24729505KEY G4
Adder
7.02
945641AF1-229 GEN
Solar/Wind Harmer
3.923
270024AE2-089 GEN
Solar/Wind Harmer
5.065
958711AF2-162 GEN
Solar/Wind Harmer
1.089
965101AG1-375 GEN
Solar/Wind Harmer
10.752
961761AG1-017 GEN
Solar/Wind Harmer
0.46
270543AE2-219 C
Solar/Wind Harmer
5.494
971029AG2-637 GEN
Solar/Wind Harmer
16.089
971673AH1-337 GEN
Solar/Wind Harmer
4.934
25196408WSDLE3
Adder
9.412
25196308WSDLE2
Adder
9.33
25196208WSDLE1
Adder
9.306
25196708WSDLE6
Adder
9.283
25196508WSDLE4
Adder
9.049
25196108MFTGT2
Adder
1.608
25196108MFTGT2
Adder
1.494
274775LINCOLN ;6U
Adder
8.792
274776LINCOLN ;7U
Adder
8.792
274777LINCOLN ;8U
Adder
8.792
274814UNIV PK N;0U
Adder
5.256
274807UNIV PK N;3U
Adder
5.245
274805UNIV PK N;1U
Adder
5.222
274811UNIV PK N;7U
Adder
5.21
972037AH1-567 GEN1
Adder
0.19
274827FISK ;RP
Adder
8.047
972227AH1-698 GEN1
Adder
2.704
274687WILL CNTY;4U
Adder
28.893
274687WILL CNTY;4U
Adder
28.893
274675JOLIET 29;7U
Adder
31.706
274675JOLIET 29;7U
Adder
30.574
274731ELWOOD EC;2P
Adder
16.983
274733ELWOOD EC;3P
Adder
16.983
274735ELWOOD EC;4P
Adder
16.983
274728ELWOOD EC;5P
Adder
16.983
238109AE1-109 GEN2
Solar/Wind Helper
0.121
238110AE1-109 GEN3
Solar/Wind Helper
0.121
238152AF2-075_GEN
Solar/Wind Helper
0.789
23546401DTGZ2-030
Solar/Wind Helper
0.099
238126S14_GEN_1
Solar/Wind Helper
0.867
238208AF1-136 C
Solar/Wind Helper
0.236
237085AD2-009_GEN
Solar/Wind Helper
1.767
3138216PACIFIC
Solar/Wind Helper
0.049
316411AF1-147_GEN1
Solar/Wind Helper
0.978
316415AF1-147_GEN2
Solar/Wind Helper
0.978
3141426STAFORD
Solar/Wind Helper
0.058
316164AC1-076 GEN
Solar/Wind Helper
1.225
23750501ELLIOTTS
Solar/Wind Helper
0.629
959381AF2-229 GEN
Solar/Wind Helper
0.367
960921AF2-383 GEN
Solar/Wind Helper
0.185
205943AE1-185 GEN
Solar/Wind Helper
0.518
205932AD2-116_GEN
Solar/Wind Helper
0.518
205956AE1-196_GEN
Solar/Wind Helper
0.518
233935AB2-179 C
Solar/Wind Helper
1.29
232436AB1-176 C
Solar/Wind Helper
0.045
233923SMA
Solar/Wind Helper
0.974
233990AG1-397 GEN
Solar/Wind Helper
0.031
232432Z2-076 GEN
Solar/Wind Helper
0.068
234033AF1-007_GEN
Solar/Wind Helper
7.137
964001AG1-254 GEN
Solar/Wind Helper
0.966
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.116
203975AE1-071-GEN
Solar/Wind Helper
2.53
219272CLEANLIGHT C
Solar/Wind Helper
0.026
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.081
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.292
219620RIDERU C
Solar/Wind Helper
0.001
20675528CPH_W2-050
Solar/Wind Helper
0.087
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
218524CNTRALGAS1 C
Solar/Wind Helper
0.161
966261AG1-495 GEN
Solar/Wind Helper
0.081
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20675928HOL_W4-097
Solar/Wind Helper
0.05
20674828DL_W4-046
Solar/Wind Helper
0.008
207484AF2-139 C O1
Solar/Wind Helper
0.084
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.136
20675128HRM_W1-127
Solar/Wind Helper
0.029
209116AE2-175 GEN
Solar/Wind Helper
1.768
945581AF1-223 GEN
Solar/Wind Harmer
0.763
233944AB2-135 GEN
Solar/Wind Helper
0.598
233946AB2-136 GEN
Solar/Wind Helper
0.577
234036AF2-325 C
Solar/Wind Helper
0.043
233901CHERRYDALE C
Solar/Wind Helper
0.236
232408W1-005 C
Solar/Wind Helper
0.516
232410W1-006 C
Solar/Wind Helper
0.516
233939AC1-091 C
Solar/Wind Helper
0.356
233970AC1-092 C
Solar/Wind Helper
0.356
966001AG1-469 GEN
Solar/Wind Helper
0.255
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.041
219921AF1-264
Solar/Wind Helper
0.052
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.083
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.19
20716928W4-060COL
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.016
20673828FLE_V3-070
Solar/Wind Helper
0.091
207442AE1-156 GEN
Solar/Wind Helper
0.326
20676128MHD_W3-029
Solar/Wind Helper
0.096
20671828STAW2-080
Solar/Wind Helper
0.027
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
207471AF2-354 C
Solar/Wind Helper
0.168
20674928WA_W3-044
Solar/Wind Helper
0.098
20676228FRD_X1-012
Solar/Wind Helper
0.091
964851AG1-348 GEN
Solar/Wind Helper
0.081
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.044
211065PSPA IPP
Solar/Wind Helper
0.15
211065PSPA IPP
Solar/Wind Helper
0.15
CBM West 1LTFEXP_CBM-W1->PJM
CBM
146.579
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.544
MECLTFEXP_MEC->PJM
CLTF
15.979
SIGELTFEXP_SIGE->PJM
CLTF
0.506
LAGNLTFEXP_LAGN->PJM
CLTF
14.521
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.32
TVALTFEXP_TVA->PJM
CLTF
7.111
CBM West 2LTFEXP_CBM-W2->PJM
CBM
111.893
NYPJM->LTFIMP_NY
CLTF
4.554
LGEELTFEXP_LGEE->PJM
CLTF
6.753
WECLTFEXP_WEC->PJM
CLTF
3.866
AG2-052LTFEXP_AG2-052->PJM
LTF
0.243
AH1-155LTFEXP_AH1-155->PJM
LTF
0.364

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P1-2_MP-500-008A_SRT-SL


Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P1-2_MP-500-008A_SRT-SL
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:125.38 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4754.33
MW Contribution:6.64
Bus #Bus NameTypeMW Contribution
24318805MLG1
50/50
9.842
23559001PLEAS1
50/50
5.385
270051AF1-062 GEN
50/50
11.434
970153AG2-106 GEN
Solar/Wind Harmer
21.245
961921AG1-034 GEN
Solar/Wind Harmer
7.364
241955AC1-078 GEN
Solar/Wind Harmer
0.007
241974AD2-163_GEN2
Solar/Wind Harmer
0.006
942051AE2-217 GEN
Solar/Wind Harmer
14.169
24721905FLATG4
Adder
22.865
970605AG2-385 GEN
Solar/Wind Harmer
4.731
270391AF1-285 GEN3
Solar/Wind Harmer
0.518
253338AC1-165 GEN
Solar/Wind Harmer
0.003
253333AC1-068 GEN
Solar/Wind Harmer
0.012
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270273AD2-016 GEN
Solar/Wind Harmer
0.792
972173AH1-669 GEN
Solar/Wind Harmer
3.811
270512AE1-227 GEN2
Solar/Wind Harmer
1.904
270291AC1-194 GEN
Solar/Wind Harmer
5.884
253415AE1-040 GEN
Solar/Wind Harmer
0.003
970065AG2-057 GEN
Solar/Wind Harmer
0.735
253370AE2-315 SEC1
Adder
2.103
253371AE2-315 SEC2
Adder
1.989
970191AG2-125 GEN
Solar/Wind Harmer
1.876
253406AD2-031_GEN
Solar/Wind Harmer
0.543
270491AE1-102 GEN2
Solar/Wind Harmer
0.945
270377AD1-106 GEN
Solar/Wind Harmer
2.761
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.047
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
9.394
959331AF2-224 GEN
Solar/Wind Harmer
5.057
965021AG1-366 GEN
Solar/Wind Harmer
2.408
270588AE1-091_GEN
Solar/Wind Harmer
5.649
971191AH1-055 GEN
Solar/Wind Harmer
18.515
944531AF1-118 GEN
Solar/Wind Harmer
32.203
270043AE2-236 GEN
Solar/Wind Harmer
4.607
270258AD1-119 GEN
Solar/Wind Harmer
0.002
971617AH1-308 GEN
Solar/Wind Harmer
5.953
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
10.684
270404AC1-167 GEN
Solar/Wind Harmer
0.003
25196608WSDLE5
Adder
8.745
252510AF1-249 C
Solar/Wind Harmer
0.055
970031AG2-029 GEN
Solar/Wind Harmer
4.625
25194608D.CRK4
Adder
1.676
270222AC2-111 GEN
Solar/Wind Harmer
3.603
970513AG2-328 GEN
Solar/Wind Harmer
3.076
970517AG2-330 GEN
Solar/Wind Harmer
18.457
970349AG2-230 GEN
Solar/Wind Harmer
10.632
946031AF1-268 GEN
Solar/Wind Harmer
6.74
958821AF2-173 GEN
Solar/Wind Harmer
9.902
270004AE1-209 GEN
Solar/Wind Harmer
1.532
270437AC2-090 C
Solar/Wind Harmer
0.003
247643Z2-116 C
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.775
970291AG2-192 GEN
Solar/Wind Harmer
0.705
945111AF1-176 GEN
Solar/Wind Harmer
5.709
247642Z2-115 C
Solar/Wind Harmer
0.003
24642205MAYFLWER
Adder
0.641
24441205WTRV SLR C
Solar/Wind Harmer
0
25196008MFTGT1
Adder
1.353
270356AE2-297 GEN
Solar/Wind Harmer
0.009
970217AG2-149 GEN
Solar/Wind Harmer
6.066
247604X1-042
Adder
0.418
270535AF1-215 GEN1
Solar/Wind Harmer
0.009
964401AG1-302 GEN
Solar/Wind Harmer
0.001
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.935
970243AG2-164 GEN
Solar/Wind Harmer
4.047
970519AG2-331 GEN
Solar/Wind Harmer
17.988
970699AG2-449 GEN
Solar/Wind Harmer
1.73
274752CRETE EC ;2U
Adder
8.172
274753CRETE EC ;3U
Adder
8.172
274772LINCOLN ;3U
Adder
8.364
274724RIVER EC ;11
Adder
17.549
958171AF2-111 GEN
Solar/Wind Harmer
17.278
274802UNIV PARK;5U
Adder
5.755
276806AD2-047 C O1
Solar/Wind Harmer
3.901
970941AG2-585 GEN
Solar/Wind Harmer
8.605
274826FISK ;BP
Adder
10.802
24728705AND G3
Adder
7.914
24728505AND G1
Adder
3.784
274800UNIV PARK;3U
Adder
5.751
972038AH1-567 GEN2
Adder
0.36
972228AH1-698 GEN2
Adder
3.654
972167AH1-666 GEN
Solar/Wind Harmer
5.505
276897AD1-100 C
Solar/Wind Harmer
0.009
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
22.464
274676JOLIET 29;8U
Adder
29.097
274729ELWOOD EC;1P
Adder
16.163
274730ELWOOD EC;6P
Adder
13.491
276893AG1-478 C
Solar/Wind Harmer
0.272
270541AE2-072 C
Solar/Wind Harmer
0.009
943121AE2-341 GEN
Solar/Wind Harmer
11.459
943591AF1-030 GEN
Solar/Wind Harmer
7.62
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
276805AD2-038 GEN
Solar/Wind Harmer
0.002
964991AG1-363 GEN
Solar/Wind Helper
4.969
316097T157 G90
Solar/Wind Helper
1.455
23750701CROSSCHOOL
Solar/Wind Helper
1.397
238148AE2-230_GEN2
Solar/Wind Helper
0.48
238127S14_GEN_2
Solar/Wind Helper
0.766
238118U2-030_1
Solar/Wind Helper
0.314
237080AD1-060 GEN
Solar/Wind Helper
0.33
237038AE2-054 C
Solar/Wind Helper
0.262
235062AE1-101 C1
Solar/Wind Helper
1.6
23779801AA1-109
Solar/Wind Helper
0.187
223401AF1-299 GEN
Solar/Wind Helper
0.355
316006AB2-029 C
Solar/Wind Helper
0.113
966131AG1-482 GEN
Solar/Wind Helper
0.132
237048AF1-022 C
Solar/Wind Helper
0.159
233930AB2-032 GEN
Solar/Wind Helper
0.368
233915AB1-141 GEN
Solar/Wind Helper
0.486
232422X3-066 FULL
Solar/Wind Helper
0.11
232426Y1-080 FULL
Solar/Wind Helper
0.038
233964AF2-378 GEN
Solar/Wind Helper
0.04
233998TM1NIN_3.36
Solar/Wind Helper
0.253
232404W1-003 C
Solar/Wind Helper
0.49
232428Y3-058 C
Solar/Wind Helper
0.327
232434Z2-077 GEN
Solar/Wind Helper
0.123
233954AC2-188 GEN
Solar/Wind Helper
0.225
233950AC2-186 GEN
Solar/Wind Helper
0.112
233972AC1-094 C
Solar/Wind Helper
0.292
316045AC1-158 PL2
Solar/Wind Helper
4.009
230511AF1-262
Solar/Wind Helper
0.014
230434AG1-499 GEN
Solar/Wind Helper
0.222
228728W1-130C
Solar/Wind Helper
0.052
219258KINSLEYDEP C
Solar/Wind Helper
0.074
219904AC1-010 C
Solar/Wind Helper
0.058
218660EHAMPSOLAR C
Solar/Wind Helper
0.032
219907AC1-030 C
Solar/Wind Helper
0.033
219686LUMSOLAR_N C
Solar/Wind Helper
0.038
219304NAMERICA C
Solar/Wind Helper
0.127
316254AC1-120 GEN1
Solar/Wind Helper
1.026
20720728JCB_W1-129
Solar/Wind Helper
0.055
207445AB1-138_GEN
Solar/Wind Helper
0.101
963711AG1-223 GEN
Solar/Wind Helper
0.062
20714828MDF_W3-079
Solar/Wind Helper
0.126
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.299
20715228NPK_W1-113
Solar/Wind Helper
0.075
972239AH1-704 GEN
50/50
2.78
962771AG1-126 GEN
Solar/Wind Harmer
33.269
270459AD2-067 GEN
Solar/Wind Harmer
0
270054AF2-122 C O1
Solar/Wind Harmer
0.007
961821AG1-024 GEN
Solar/Wind Harmer
4.91
270520AE2-214 GEN
Solar/Wind Harmer
0.013
270284AF1-227 GEN1
Solar/Wind Harmer
0.01
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
253383AE2-342_GEN
Solar/Wind Harmer
0.003
241973AD2-163_GEN1
Solar/Wind Harmer
0.006
945631AF1-228 GEN
Solar/Wind Harmer
0
943861AF1-054 GEN
Solar/Wind Harmer
3.02
943851AF1-053 GEN
Solar/Wind Harmer
2.092
270156DARBY CT1
Adder
10.05
270157DARBY CT2
Adder
10.026
270158DARBY CT3
Adder
9.866
270578AF1-285 GEN2
Solar/Wind Harmer
0.518
970689AG2-444 GEN
Solar/Wind Harmer
15.861
270432AC2-029 GEN
Solar/Wind Harmer
3.428
940611AE2-048 GEN
Solar/Wind Harmer
18.967
941391AE2-136 GEN
Solar/Wind Harmer
10.684
270302AB2-170 GEN
Solar/Wind Harmer
0.005
270317AD1-130_GEN
Solar/Wind Harmer
0.011
971653AH1-327 GEN
Solar/Wind Harmer
1.08
270269AC2-059
Solar/Wind Harmer
0.004
241972AD1-140 GEN
Solar/Wind Harmer
0.824
970179AG2-119 GEN
Solar/Wind Harmer
6.658
270340AC2-060 GEN
Solar/Wind Harmer
0.009
970879AG2-548 GEN
Solar/Wind Harmer
6.645
253372AE2-315 SEC3
Adder
1.989
253372AE2-315 SEC3
Adder
1.989
25306009OHH W.
Adder
3.018
253349AC2-067 GEN
Solar/Wind Harmer
2.296
253400AC2-068 GEN
Solar/Wind Harmer
0.923
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
0.92
965051AG1-369 GEN
Solar/Wind Harmer
3.609
971567AH1-282 GEN
Solar/Wind Harmer
10.843
247607V1-011 GEN
Solar/Wind Harmer
0.001
965041AG1-368 GEN
Solar/Wind Harmer
7.21
971989AH1-539 GEN
Solar/Wind Harmer
3.109
963791AG1-232 GEN
Solar/Wind Harmer
9.689
24729505KEY G4
Adder
6.671
270071AF1-092 GEN
Solar/Wind Harmer
13.737
270024AE2-089 GEN
Solar/Wind Harmer
0.008
971985AH1-537 GEN
Solar/Wind Harmer
2.123
965101AG1-375 GEN
Solar/Wind Harmer
7.135
270297AD1-101 GEN
Solar/Wind Harmer
0.002
270367AC2-061_GEN
Solar/Wind Harmer
0.006
971673AH1-337 GEN
Solar/Wind Harmer
4.631
971029AG2-637 GEN
Solar/Wind Harmer
10.686
270543AE2-219 C
Solar/Wind Harmer
0.004
252524AE2-267 GEN
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
9.002
25196308WSDLE2
Adder
8.924
25196208WSDLE1
Adder
8.902
25196708WSDLE6
Adder
8.879
25196508WSDLE4
Adder
8.656
945581AF1-223 GEN
Solar/Wind Harmer
0.001
971347AH1-153 GEN
Solar/Wind Harmer
10.632
971609AH1-304 GEN
Solar/Wind Harmer
1.157
270240V3-007_GEN2
Solar/Wind Harmer
0.002
970115AG2-085 GEN
Solar/Wind Harmer
2.826
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
270594AE1-207 GEN
Solar/Wind Harmer
7.898
971771AH1-392 GEN
Solar/Wind Harmer
7.046
970289AG2-191 GEN
Solar/Wind Harmer
1.339
971619AH1-309 GEN
Solar/Wind Harmer
3.169
971769AH1-391 GEN
Solar/Wind Harmer
7.844
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
25196108MFTGT2
Adder
1.54
25196108MFTGT2
Adder
1.43
270536AF1-215 GEN2
Solar/Wind Harmer
0.009
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
4.146
971549AH1-272 GEN
Solar/Wind Harmer
14.344
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
8.364
274776LINCOLN ;7U
Adder
8.364
274777LINCOLN ;8U
Adder
8.364
274814UNIV PK N;0U
Adder
4.998
274807UNIV PK N;3U
Adder
4.987
274805UNIV PK N;1U
Adder
4.965
274811UNIV PK N;7U
Adder
4.954
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
972037AH1-567 GEN1
Adder
0.181
960591AF2-350 GEN
Solar/Wind Harmer
6.884
274827FISK ;RP
Adder
7.655
972227AH1-698 GEN1
Adder
2.573
963841AG1-237 GEN
Solar/Wind Harmer
2.978
274687WILL CNTY;4U
Adder
27.495
274687WILL CNTY;4U
Adder
27.495
274675JOLIET 29;7U
Adder
30.175
274675JOLIET 29;7U
Adder
29.097
972163AH1-664 GEN
Solar/Wind Harmer
7.639
972165AH1-665 GEN
Solar/Wind Harmer
6.118
274731ELWOOD EC;2P
Adder
16.163
274733ELWOOD EC;3P
Adder
16.163
274735ELWOOD EC;4P
Adder
16.163
274728ELWOOD EC;5P
Adder
16.163
970833AG2-524 GEN
Solar/Wind Harmer
7.542
970833AG2-524 GEN
Solar/Wind Harmer
5.028
945641AF1-229 GEN
Solar/Wind Harmer
0.001
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
276868AE1-113 GEN
Solar/Wind Harmer
1.363
276882AE2-255 GEN
Solar/Wind Harmer
0.794
238109AE1-109 GEN2
Solar/Wind Helper
0.106
238110AE1-109 GEN3
Solar/Wind Helper
0.106
238152AF2-075_GEN
Solar/Wind Helper
0.683
23546401DTGZ2-030
Solar/Wind Helper
0.086
238208AF1-136 C
Solar/Wind Helper
0.211
238126S14_GEN_1
Solar/Wind Helper
0.766
237085AD2-009_GEN
Solar/Wind Helper
1.588
3138216PACIFIC
Solar/Wind Helper
0.043
316411AF1-147_GEN1
Solar/Wind Helper
0.86
316415AF1-147_GEN2
Solar/Wind Helper
0.86
959381AF2-229 GEN
Solar/Wind Helper
0.345
23750501ELLIOTTS
Solar/Wind Helper
0.571
3141426STAFORD
Solar/Wind Helper
0.051
960921AF2-383 GEN
Solar/Wind Helper
0.352
205943AE1-185 GEN
Solar/Wind Helper
0.492
205956AE1-196_GEN
Solar/Wind Helper
0.492
205932AD2-116_GEN
Solar/Wind Helper
0.492
233935AB2-179 C
Solar/Wind Helper
1.227
232436AB1-176 C
Solar/Wind Helper
0.043
233923SMA
Solar/Wind Helper
0.927
233990AG1-397 GEN
Solar/Wind Helper
0.261
234033AF1-007_GEN
Solar/Wind Helper
6.787
232432Z2-076 GEN
Solar/Wind Helper
0.065
964001AG1-254 GEN
Solar/Wind Helper
0.924
228754AB1-001 C
Solar/Wind Helper
0.025
227927V4-067C
Solar/Wind Helper
0.01
219914AD2-027 C
Solar/Wind Helper
0.111
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.038
219607WPEMNERT C
Solar/Wind Helper
0.077
214067T20SOLAR
Solar/Wind Helper
0.011
203975AE1-071-GEN
Solar/Wind Helper
2.41
20715728PEM_W1-119
Solar/Wind Helper
0.093
20715828PEM_W1-120
Solar/Wind Helper
0.093
207459AE1-142 C O1
Solar/Wind Helper
0.28
316164AC1-076 GEN
Solar/Wind Helper
1.062
219620RIDERU C
Solar/Wind Helper
0.001
270119AB2-067 GEN1
50/50
6.869
270120AB2-067 GEN2
50/50
6.869
24318905MLG2
50/50
6.89
270471AD2-092_GEN
Solar/Wind Harmer
0.006
942861AE2-305 GEN
Solar/Wind Harmer
6.118
970077AG2-063 GEN
Solar/Wind Harmer
4.471
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
938701AE1-092 GEN
Solar/Wind Harmer
12.484
971655AH1-328 GEN
Solar/Wind Harmer
2.758
964601AG1-323 GEN
Solar/Wind Harmer
3.106
964601AG1-323 GEN
Solar/Wind Harmer
2.071
270518AE2-148 GEN
Solar/Wind Harmer
0.667
972269AH1-719 GEN
Adder
2.501
972159AH1-661 GEN
Adder
1.082
253378AE2-206_GEN
Solar/Wind Harmer
0.004
276820AF1-078_GEN
Solar/Wind Harmer
0.002
970329AG2-216 GEN
Solar/Wind Harmer
3.237
971199AH1-059 GEN
Solar/Wind Harmer
2.99
241960AC2-195 GEN
Solar/Wind Harmer
0.006
970935AG2-582 GEN
Adder
242.403
25326509SID D
Adder
1.4
971073AG2-665 GEN
Solar/Wind Harmer
6.645
25326109MON D
Adder
1.391
971201AH1-060 GEN
Solar/Wind Harmer
1.471
25322209TAIT E
Adder
10.262
25322209TAIT E
Adder
10.031
253370AE2-315 SEC1
Adder
2.103
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
246938BC-WTG3
Solar/Wind Harmer
0.263
246937BC-WTG2
Solar/Wind Harmer
0.295
971231AH1-075 GEN
Solar/Wind Harmer
0.833
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
970611AG2-400 GEN
Solar/Wind Harmer
7.225
970627AG2-408 GEN
Solar/Wind Harmer
2.167
270007AE1-245 C
Solar/Wind Harmer
0.002
970623AG2-406 GEN
Solar/Wind Harmer
1.309
962581AG1-107 GEN
Solar/Wind Harmer
0.001
25183208HLCRTG
Solar/Wind Harmer
0.011
944541AF1-119 GEN
Solar/Wind Harmer
0.479
960971AF2-388 GEN
Solar/Wind Harmer
4.192
942221AE2-234 GEN
Solar/Wind Harmer
0.036
252519AF1-045_GEN
Solar/Wind Harmer
6.204
252516AE2-318_GEN
Solar/Wind Harmer
5.503
970621AG2-405 GEN
Solar/Wind Harmer
1.305
247621Y3-024
Adder
0.246
970883AG2-550 GEN
Solar/Wind Harmer
7.123
970885AG2-551 GEN
Solar/Wind Harmer
2.374
270201AC2-176 GEN
Solar/Wind Harmer
0.001
25194408D.CRK1
Adder
7.711
25194508D.CRK3
Adder
1.442
964611AG1-324 GEN
Solar/Wind Harmer
0.534
252509AD1-136 GEN
Solar/Wind Harmer
0.036
970321AG2-212 GEN
Solar/Wind Harmer
3.076
270599AE1-208 GEN
Solar/Wind Harmer
6.495
270031AE2-169
Solar/Wind Harmer
3.897
270383AD1-128 GEN
Solar/Wind Harmer
0.004
270186AC1-089 GEN
Solar/Wind Harmer
0.004
247620Y3-023
Adder
0.466
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
970825AG2-519 GEN
Solar/Wind Harmer
7.834
960441AF2-335 GEN
Solar/Wind Harmer
7.065
270216AD2-079_GEN
Solar/Wind Harmer
0.001
971613AH1-306 GEN
Solar/Wind Harmer
3.385
24728805RICHG1
Adder
3.82
24728905RICHG2
Adder
3.82
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
14.072
961051AF2-396 GEN
Solar/Wind Harmer
9.381
270526AF1-158 GEN
Solar/Wind Harmer
0.009
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
8.77
965791AG1-447 GEN
Solar/Wind Harmer
6.431
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
970239AG2-162 GEN
Solar/Wind Harmer
1.73
274770LINCOLN ;1U
Adder
8.364
274771LINCOLN ;2U
Adder
8.364
274808UNIV PK N;4U
Adder
4.933
966841AG1-555 GEN
Solar/Wind Harmer
0.781
274803UNIV PARK;6U
Adder
5.755
274888KELLY CRK;1U
Solar/Wind Harmer
0.404
274887GEN-1.85
Solar/Wind Harmer
0.181
276843GEN-1.7
Solar/Wind Harmer
0.223
958011AF2-095 GEN
Solar/Wind Harmer
9.913
972259AH1-714 GEN
Adder
18.805
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
970241AG2-163 GEN
Solar/Wind Harmer
3.993
958481AF2-142 GEN
Solar/Wind Harmer
10.238
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.923
971573AH1-285 GEN
Solar/Wind Harmer
1.271
971677AH1-339 GEN
Solar/Wind Harmer
0.768
958491AF2-143 GEN
Solar/Wind Harmer
10.205
274879MINONK ;1U
Solar/Wind Harmer
0.287
238175AF1-290_GEN
Solar/Wind Helper
0.148
238169AE2-226 GEN1
Solar/Wind Helper
0.677
238170AE2-226 GEN2
Solar/Wind Helper
0.677
238120AE2-309 GEN
Solar/Wind Helper
0.487
235020AA1-095 C
Solar/Wind Helper
0.051
23777901MDS_W4-102
Solar/Wind Helper
0.171
23585401KL_K28_T16
Solar/Wind Helper
1.328
237034AC2-136 C
Solar/Wind Helper
0.219
237002AB1-128_GEN
Solar/Wind Helper
0.427
235063AE1-101 C2
Solar/Wind Helper
1.6
237001AB1-127_GEN
Solar/Wind Helper
0.426
23777801MSM_W1-116
Solar/Wind Helper
0.11
237025AB1-124 C
Solar/Wind Helper
0.159
237006AB1-125 GEN
Solar/Wind Helper
0.119
226929AD2-058 GEN
Solar/Wind Helper
0.096
205916AD1-020 GEN
Solar/Wind Helper
1.656
20390526W1-045 C
Solar/Wind Helper
0.338
208835TUHI V3-051
Solar/Wind Helper
0.023
208835TUHI V3-051
Solar/Wind Helper
0.023
233987AB2-037 GEN
Solar/Wind Helper
2.264
233933AB2-153 GEN
Solar/Wind Helper
0.225
232424Y1-079 C
Solar/Wind Helper
0.112
233944AB2-135 GEN
Solar/Wind Helper
0.569
233946AB2-136 GEN
Solar/Wind Helper
0.549
234036AF2-325 C
Solar/Wind Helper
0.041
233901CHERRYDALE C
Solar/Wind Helper
0.225
232408W1-005 C
Solar/Wind Helper
0.49
232410W1-006 C
Solar/Wind Helper
0.49
233939AC1-091 C
Solar/Wind Helper
0.338
233970AC1-092 C
Solar/Wind Helper
0.338
315651AD1-115 GEN
Solar/Wind Helper
0.76
316447AC1-158 HLD
Solar/Wind Helper
2.756
230433AD2-135 GEN
Solar/Wind Helper
0.016
230407AD2-065 C
Solar/Wind Helper
0.039
219921AF1-264
Solar/Wind Helper
0.049
219615MILLCREEK C
Solar/Wind Helper
0.026
963401AG1-189 GEN
Solar/Wind Helper
0.054
963391AG1-188 GEN
Solar/Wind Helper
0.079
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.183
270166AC1-044 GEN3
50/50
6.869
23559101PLEAS2
50/50
5.385
270122AB2-093 CT
50/50
3.689
962761AG1-125 GEN
Solar/Wind Harmer
33.269
970149AG2-104 GEN
Solar/Wind Harmer
35.932
970155AG2-107 GEN
Solar/Wind Harmer
21.245
270349AD2-093_GEN
Solar/Wind Harmer
0.006
24721705FLATG2
Adder
22.865
270159DARBY CT4
Adder
9.89
970593AG2-378 GEN
Solar/Wind Harmer
1.75
270223U2-072_GEN1
Solar/Wind Harmer
0.001
253343AC1-166 GEN
Solar/Wind Harmer
0.003
253325AC1-069 GEN
Solar/Wind Harmer
0.012
270462AD2-086
Solar/Wind Harmer
0.016
971995AH1-542 GEN
Solar/Wind Harmer
2.81
270263AC1-001 GEN
Solar/Wind Harmer
0.758
270510AE1-227 GEN1
Solar/Wind Harmer
1.904
241813AF1-122_GEN
Solar/Wind Harmer
3.294
25326309TAIT D
Adder
1.153
960071AF2-298 GEN
Solar/Wind Harmer
3.651
253370AE2-315 SEC1
Adder
2.103
253371AE2-315 SEC2
Adder
1.989
927014AC1-188 GEN
Solar/Wind Harmer
0.004
246936BC-WTG1
Solar/Wind Harmer
0.295
270489AE1-102 GEN1
Solar/Wind Harmer
0.945
965421AG1-410 GEN
Solar/Wind Harmer
21.788
247521TR3_G114
Solar/Wind Harmer
0.263
270246TR4_N_V150
Solar/Wind Harmer
0.047
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.226
965011AG1-365 GEN
Solar/Wind Harmer
7.225
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
24695305TIMB G C
Solar/Wind Harmer
0.002
965651AG1-433 GEN
Solar/Wind Harmer
2.096
958861AF2-177 GEN
Solar/Wind Harmer
3.092
247536S-71 GEN
Solar/Wind Harmer
0.287
945371AF1-202 GEN
Solar/Wind Harmer
0.001
25194608D.CRK4
Adder
1.676
270063AE2-323 C
Solar/Wind Harmer
0.006
252507AC2-088 GEN
Solar/Wind Harmer
0.323
970245AG2-165 GEN
Solar/Wind Harmer
3.076
944231AF1-091 GEN
Solar/Wind Harmer
1.885
270005AE1-210 C O1
Solar/Wind Harmer
1.532
965031AG1-367 GEN
Solar/Wind Harmer
7.073
970947AG2-589 GEN
Solar/Wind Harmer
0.236
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.183
970825AG2-519 GEN
Solar/Wind Harmer
2.509
24639705ELKHART HY
Adder
0.155
25196808ZIMRHP
Adder
76.799
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
270032AE2-172
Solar/Wind Harmer
4.701
970291AG2-192 GEN
Solar/Wind Harmer
0.916
945111AF1-176 GEN
Solar/Wind Harmer
12.568
270505AE1-170 C O1
Solar/Wind Harmer
7.393
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.67
247522W1-056 GEN
Solar/Wind Harmer
0.001
276903AD2-071 C
Solar/Wind Harmer
7.842
25196008MFTGT1
Adder
1.397
970773AG2-487 GEN
Solar/Wind Harmer
1.237
970373AG2-245 GEN
Solar/Wind Harmer
14.699
970515AG2-329 GEN
Solar/Wind Harmer
18.197
270055AF2-134 C O1
Solar/Wind Harmer
0.005
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.071
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.706
24791305MDL-5G
Solar/Wind Harmer
0.001
970333AG2-219 GEN
Solar/Wind Harmer
4.947
274751CRETE EC ;1U
Adder
8.172
274754CRETE EC ;4U
Adder
8.172
274773LINCOLN ;4U
Adder
8.364
274774LINCOLN ;5U
Adder
8.364
274723RIVER EC ;12
Adder
17.756
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.954
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
276776AD2-060 GEN
Solar/Wind Harmer
0.719
24728605AND G2
Adder
3.784
274801UNIV PARK;4U
Adder
5.751
941551AE2-152 GEN
Solar/Wind Harmer
0.001
945681AF1-233 GEN
Solar/Wind Harmer
12.962
274676JOLIET 29;8U
Adder
30.175
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
963741AG1-226 GEN
Solar/Wind Harmer
16.202
939401AE1-172 GEN
Solar/Wind Harmer
5.109
276691AA1-018 GEN1
Solar/Wind Harmer
0.827
276901AD2-066 C O1
Solar/Wind Harmer
0.007
316095T157 G97
Solar/Wind Helper
1.455
23583801GRNGAP
Solar/Wind Helper
5.418
238108AE1-109 GEN1
Solar/Wind Helper
0.106
238185AF2-356 C
Solar/Wind Helper
2.425
238147AE2-230_GEN1
Solar/Wind Helper
0.478
238149AF1-291A_GEN
Solar/Wind Helper
0.137
235531U2-073 GEN
Solar/Wind Helper
3.034
235054AD2-180 GEN
Solar/Wind Helper
1.839
237061AD1-155 GEN
Solar/Wind Helper
0.051
238117U2-030
Solar/Wind Helper
0.314
238221AF1-254 C O1
Solar/Wind Helper
0.265
235067AD1-061 GEN
Solar/Wind Helper
0.478
237030AB1-096 C
Solar/Wind Helper
0.068
3141196NOKESVL
Solar/Wind Helper
0.999
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.335
223402AF1-300 C
Solar/Wind Helper
0.355
23751201ROTHROCK
Solar/Wind Helper
0.694
23562501BACKB
Solar/Wind Helper
0.842
205917AD1-020 ES
Solar/Wind Helper
0.356
233982AB2-133 GEN
Solar/Wind Helper
0.346
233918AB1-142 GEN
Solar/Wind Helper
0.486
233994AC2-023 GEN
Solar/Wind Helper
0.929
233996TM1833_GEN
Solar/Wind Helper
0.253
233997TMININ_4.2
Solar/Wind Helper
0.253
232406W1-004 FULL
Solar/Wind Helper
0.49
233940AF2-379 C
Solar/Wind Helper
0.06
234015AF2-250 C
Solar/Wind Helper
0.037
233952AC2-187 GEN
Solar/Wind Helper
0.225
233971AC1-093 C
Solar/Wind Helper
0.346
316044AC1-158 PL1
Solar/Wind Helper
1.252
316450AC1-158 RIC
Solar/Wind Helper
0.334
230430AE1-229_GEN
Solar/Wind Helper
3.26
230415AB2-049 C
Solar/Wind Helper
0.029
228729W2-030 C
Solar/Wind Helper
0.107
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.053
219912AD2-042 GEN
Solar/Wind Helper
0.145
219291REEVESSOUT C
Solar/Wind Helper
0.011
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.111
316170AC1-121 GEN2
Solar/Wind Helper
0.342
959561AF2-247 GEN
Solar/Wind Helper
0.02
20720828JCB_W4-025
Solar/Wind Helper
0.061
20716028EGP_W2-019
Solar/Wind Helper
0.018
20715028HAN_X4-015
Solar/Wind Helper
0.055
219276PARKLANDSO C
Solar/Wind Helper
0.086
20714528FRN_Y2-051
Solar/Wind Helper
0.055
20720528MAN_W1-024
Solar/Wind Helper
0.027
971997AH1-543 GEN
Solar/Wind Harmer
1.86
CBM West 1LTFEXP_CBM-W1->PJM
CBM
137.982
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.984
MECLTFEXP_MEC->PJM
CLTF
15.319
SIGELTFEXP_SIGE->PJM
CLTF
0.486
LAGNLTFEXP_LAGN->PJM
CLTF
14.268
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.432
TVALTFEXP_TVA->PJM
CLTF
7.011
CPLELTFEXP_CPLE->PJM
CLTF
0.567
CBM West 2LTFEXP_CBM-W2->PJM
CBM
108.576
NYPJM->LTFIMP_NY
CLTF
4.628
LGEELTFEXP_LGEE->PJM
CLTF
6.497
WECLTFEXP_WEC->PJM
CLTF
3.686
AG2-052LTFEXP_AG2-052->PJM
LTF
0.231
AH1-155LTFEXP_AH1-155->PJM
LTF
0.346

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P4_#8980_05KAMMER 765_QQ2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#8980_05KAMMER 765_QQ2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.66 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6443.11
MW Contribution:15.32
Bus #Bus NameTypeMW Contribution
24289405MTG1
50/50
11.351
243186AF1-051 GEN
50/50
12.478
24318705GVG2
50/50
11.615
24721805FLATG3
50/50
2.756
24721705FLATG2
50/50
50.519
24723205RIVRG3
Adder
36.021
24686105CER G3
Adder
15.629
24686505CER G6
Adder
15.608
270331AC1-082 GEN3
Solar/Wind Harmer
0.804
970947AG2-589 GEN
Solar/Wind Harmer
3.539
960001AF2-291 GEN
Solar/Wind Harmer
5.242
971403AH1-188 GEN
Solar/Wind Harmer
24.059
962761AG1-125 GEN
Solar/Wind Harmer
54.777
970149AG2-104 GEN
Solar/Wind Harmer
67.649
970155AG2-107 GEN
Solar/Wind Harmer
23.885
971315AH1-136 GEN
Solar/Wind Harmer
3.199
927014AC1-188 GEN
Solar/Wind Harmer
2.494
971687AH1-348 GEN
Solar/Wind Harmer
1.529
24728305BUCHG2
Adder
6.831
970333AG2-219 GEN
Solar/Wind Harmer
46.803
970091AG2-072 GEN
Adder
113.581
945681AF1-233 GEN
Solar/Wind Harmer
27.516
252507AC2-088 GEN
Solar/Wind Harmer
2.603
25196808ZIMRHP
Adder
109.116
339216AC1-074 GEN
Solar/Wind Harmer
2.413
25196008MFTGT1
Adder
1.989
943111AE2-339 GEN
Solar/Wind Harmer
1.263
25194608D.CRK4
Adder
2.348
3429241JKCT 3G
Adder
16.894
3429421JKCT 10G
Adder
11.865
253432AC1-085 GEN2
Solar/Wind Harmer
0.38
946171AF1-282 GEN
Solar/Wind Harmer
14.195
270263AC1-001 GEN
Solar/Wind Harmer
1.475
270445AC2-157 GEN2
Solar/Wind Harmer
7.855
971565AH1-281 GEN
Solar/Wind Harmer
2.807
971821AH1-427 GEN
Solar/Wind Harmer
14.027
24735205WLF2G2
Adder
8.08
24728605AND G2
Adder
5.27
339241AF1-083 GEN
Solar/Wind Harmer
2.279
942081AE2-220 GEN
Solar/Wind Harmer
8.729
270239V3-007_GEN1
Solar/Wind Harmer
2.35
253370AE2-315 SEC1
Adder
2.733
253371AE2-315 SEC2
Adder
2.585
970273AG2-179 GEN
Solar/Wind Harmer
3.322
276903AD2-071 C
Solar/Wind Harmer
13.573
963741AG1-226 GEN
Solar/Wind Harmer
61.007
970291AG2-192 GEN
Solar/Wind Harmer
1.76
270005AE1-210 C O1
Solar/Wind Harmer
7.396
965031AG1-367 GEN
Solar/Wind Harmer
13.534
270032AE2-172
Solar/Wind Harmer
6.293
25326309TAIT D
Adder
1.481
964901AG1-354 GEN
Solar/Wind Harmer
20.265
960071AF2-298 GEN
Solar/Wind Harmer
6.737
274773LINCOLN ;4U
Adder
11.055
274774LINCOLN ;5U
Adder
11.055
274745AC1-111 GEN9
Adder
7.316
274761LEE CO EC;2U
Adder
12.175
274766LEE CO EC;7U
Adder
12.032
237046AF1-021 C
Solar/Wind Helper
0.577
238185AF2-356 C
Solar/Wind Helper
2.612
23751201ROTHROCK
Solar/Wind Helper
0.878
235054AD2-180 GEN
Solar/Wind Helper
2.032
23562501BACKB
Solar/Wind Helper
1.07
238117U2-030
Solar/Wind Helper
0.343
235531U2-073 GEN
Solar/Wind Helper
3.23
20089226LOOKOUT
Solar/Wind Helper
0.665
254303AC2-168 GEN
Solar/Wind Helper
0.173
241966AE1-183 GEN
Solar/Wind Helper
0.28
23751101LEADS_P59
Solar/Wind Helper
1.483
20088826HIGHLAND
Solar/Wind Helper
1.011
20094526CT_V3-030
Solar/Wind Helper
0.53
964201AG1-281 GEN
Solar/Wind Helper
0.544
238108AE1-109 GEN1
Solar/Wind Helper
0.102
964391AG1-301 GEN
Solar/Wind Helper
0.529
203954AE2-126 C
Solar/Wind Helper
0.522
238206AE2-263_GEN
Solar/Wind Helper
1.011
959471AF2-238 GEN
Solar/Wind Helper
0.517
203860AG1-193 C
Solar/Wind Helper
0.254
209067AE2-060 GEN
Solar/Wind Helper
0.091
946691AF1-333 GEN
Solar/Wind Helper
0.5
946741AF1-338 GEN
Solar/Wind Helper
0.5
961421AF2-433 GEN
Solar/Wind Helper
0.499
957921AF2-086 GEN
Solar/Wind Helper
0.493
961331AF2-424 GEN
Solar/Wind Helper
0.499
209027LOR2_Q27
Solar/Wind Helper
1.165
963071AG1-156 GEN
Solar/Wind Helper
1.625
963161AG1-165 GEN
Solar/Wind Helper
0.496
316095T157 G97
Solar/Wind Helper
1.154
23583801GRNGAP
Solar/Wind Helper
4.282
961971AG1-040 GEN
Solar/Wind Helper
0.492
243186AF1-051 GEN
50/50
12.478
24723005RIVRG1
Adder
36.021
24723105RIVRG2
Adder
36.021
24685805CER G1
Adder
15.526
24685905CER G2
Adder
15.526
944971AF1-162 GEN
Solar/Wind Harmer
12.174
971225AH1-072 GEN
Solar/Wind Harmer
3.053
971227AH1-073 GEN
Solar/Wind Harmer
3.053
24728205BUCHG1
Adder
6.831
970239AG2-162 GEN
Solar/Wind Harmer
16.31
270186AC1-089 GEN
Solar/Wind Harmer
9.06
962581AG1-107 GEN
Solar/Wind Harmer
7.424
961491AF2-440 GEN
Solar/Wind Harmer
3.085
960161AF2-307 GEN
Solar/Wind Harmer
9.441
970879AG2-548 GEN
Solar/Wind Harmer
9.023
971073AG2-665 GEN
Solar/Wind Harmer
9.023
971073AG2-665 GEN
Solar/Wind Harmer
6.295
252509AD1-136 GEN
Solar/Wind Harmer
0.372
339221AD2-048_GEN
Solar/Wind Harmer
2.218
972043AH1-570 GEN
Solar/Wind Harmer
3.602
972045AH1-571 GEN
Solar/Wind Harmer
2.882
25183208HLCRTG
Solar/Wind Harmer
8.709
252519AF1-045_GEN
Solar/Wind Harmer
8.714
252516AE2-318_GEN
Solar/Wind Harmer
6.647
970235AG2-159 GEN
Solar/Wind Harmer
5.741
970235AG2-159 GEN
Solar/Wind Harmer
3.504
971125AH1-004 GEN
Solar/Wind Harmer
5.722
970107AG2-081 GEN
Solar/Wind Harmer
4.291
25194408D.CRK1
Adder
10.799
25194508D.CRK3
Adder
2.019
942891AE2-308 GEN
Solar/Wind Harmer
14.268
253317AC1-085 GEN4
Solar/Wind Harmer
11.89
270444AC2-157 GEN1
Solar/Wind Harmer
7.855
253394AE2-221_GEN
Solar/Wind Harmer
6.369
253398AE2-221_GEN2
Solar/Wind Harmer
6.369
964571AG1-320 GEN
Solar/Wind Harmer
11.394
970653AG2-424 GEN
Solar/Wind Harmer
6.671
970653AG2-424 GEN
Solar/Wind Harmer
2.412
24728805RICHG1
Adder
5.204
24728905RICHG2
Adder
5.204
971081AG2-670 GEN
Solar/Wind Harmer
10.253
945391AF1-204 GEN
Solar/Wind Harmer
19.047
24379505HDWTR1G C
Solar/Wind Harmer
10.797
270209AC1-174_GEN
Solar/Wind Harmer
7.62
926881AC1-175 GEN
Solar/Wind Harmer
7.62
253370AE2-315 SEC1
Adder
2.733
339231AF1-038_GEN
Solar/Wind Harmer
2.469
270383AD1-128 GEN
Solar/Wind Harmer
8.302
339236AF1-050_GEN
Solar/Wind Harmer
2.463
970241AG2-163 GEN
Solar/Wind Harmer
33.893
25322209TAIT E
Adder
13.187
25322209TAIT E
Adder
12.891
25326109MON D
Adder
1.763
247621Y3-024
Adder
0.32
274770LINCOLN ;1U
Adder
11.055
274771LINCOLN ;2U
Adder
11.055
972259AH1-714 GEN
Adder
24.976
972267AH1-718 GEN
Adder
5.45
274696ROCKY RD ;4P
Adder
14.914
274695ROCKY RD ;2P
Adder
14.57
274693ROCKY RD ;1P
Adder
14.427
274764LEE CO EC;5U
Adder
12.204
274765LEE CO EC;6U
Adder
12.204
274762LEE CO EC;3U
Adder
12.175
274763LEE CO EC;4U
Adder
12.06
274697ROCKY RD ;3P
Adder
3.958
23652301WDPWR_K20
Solar/Wind Helper
0.168
23585401KL_K28_T16
Solar/Wind Helper
1.53
203955AF1-039 C O1
Solar/Wind Helper
0.432
944781AF1-143 GEN
Solar/Wind Helper
2.836
238120AE2-309 GEN
Solar/Wind Helper
0.507
962101AG1-054 GEN
Solar/Wind Helper
0.715
20083426SW_E13_K22
Solar/Wind Helper
0.064
241985AE1-237 GEN
Solar/Wind Helper
0.271
241967AE2-285_GEN
Solar/Wind Helper
0.696
241801AE1-079 GEN
Solar/Wind Helper
0.271
20088926STNY CRK
Solar/Wind Helper
0.928
946071AF1-272 GEN
Solar/Wind Helper
3.051
20084626FORWARD
Solar/Wind Helper
0.402
203940AF1-140 C
Solar/Wind Helper
0.446
20088626ARWF_N39
Solar/Wind Helper
1.362
20303426NA_O38_P22
Solar/Wind Helper
1.117
203853AF1-134 C O1
Solar/Wind Helper
0.534
946381AF1-302 GEN
Solar/Wind Helper
0.246
203952AE2-129 C
Solar/Wind Helper
0.529
203946AE2-131 C
Solar/Wind Helper
0.53
238217AF1-153 C O1
Solar/Wind Helper
0.262
20398826ARMNA MT
Solar/Wind Helper
1.656
209137AF2-361 C
Solar/Wind Helper
1.531
946751AF1-339 GEN
Solar/Wind Helper
0.5
209054AE2-059 GEN
Solar/Wind Helper
0.09
961431AF2-434 GEN
Solar/Wind Helper
0.499
208972BECR K09
Solar/Wind Helper
0.372
209029WAYMART-WD
Solar/Wind Helper
0.937
203979AG1-198 GEN
Solar/Wind Helper
0.297
211065PSPA IPP
Solar/Wind Helper
0.168
211065PSPA IPP
Solar/Wind Helper
0.168
203980AG1-197 GEN
Solar/Wind Helper
0.369
966111AG1-480 GEN
Solar/Wind Helper
0.049
20674128FR_U2-059
Solar/Wind Helper
0.004
964851AG1-348 GEN
Solar/Wind Helper
0.088
207471AF2-354 C
Solar/Wind Helper
0.184
20674928WA_W3-044
Solar/Wind Helper
0.107
20676228FRD_X1-012
Solar/Wind Helper
0.1
217204WCALDSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217081WEATEXAS C
Solar/Wind Helper
0.014
20671828STAW2-080
Solar/Wind Helper
0.029
207442AE1-156 GEN
Solar/Wind Helper
0.351
20676128MHD_W3-029
Solar/Wind Helper
0.103
20673828FLE_V3-070
Solar/Wind Helper
0.097
218440SUMMTASSOC C
Solar/Wind Helper
0.018
20716928W4-060COL
Solar/Wind Helper
0.055
20720628TIN_W1-124
Solar/Wind Helper
0.203
963391AG1-188 GEN
Solar/Wind Helper
0.088
20714928UPF_X1-085
Solar/Wind Helper
0.005
963401AG1-189 GEN
Solar/Wind Helper
0.06
20390526W1-045 C
Solar/Wind Helper
0.357
219615MILLCREEK C
Solar/Wind Helper
0.028
219921AF1-264
Solar/Wind Helper
0.054
203947AF1-006 C
Solar/Wind Helper
0.527
230407AD2-065 C
Solar/Wind Helper
0.042
230433AD2-135 GEN
Solar/Wind Helper
0.018
233939AC1-091 C
Solar/Wind Helper
0.361
233970AC1-092 C
Solar/Wind Helper
0.361
233901CHERRYDALE C
Solar/Wind Helper
0.24
232408W1-005 C
Solar/Wind Helper
0.523
232410W1-006 C
Solar/Wind Helper
0.523
233946AB2-136 GEN
Solar/Wind Helper
0.586
234036AF2-325 C
Solar/Wind Helper
0.043
233987AB2-037 GEN
Solar/Wind Helper
2.415
233944AB2-135 GEN
Solar/Wind Helper
0.607
232424Y1-079 C
Solar/Wind Helper
0.12
233933AB2-153 GEN
Solar/Wind Helper
0.24
235063AE1-101 C2
Solar/Wind Helper
1.463
205916AD1-020 GEN
Solar/Wind Helper
1.711
237002AB1-128_GEN
Solar/Wind Helper
0.388
237001AB1-127_GEN
Solar/Wind Helper
0.388
235020AA1-095 C
Solar/Wind Helper
0.045
23777901MDS_W4-102
Solar/Wind Helper
0.15
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
237034AC2-136 C
Solar/Wind Helper
0.194
238175AF1-290_GEN
Solar/Wind Helper
0.123
237025AB1-124 C
Solar/Wind Helper
0.145
237006AB1-125 GEN
Solar/Wind Helper
0.109
23777801MSM_W1-116
Solar/Wind Helper
0.1
238169AE2-226 GEN1
Solar/Wind Helper
0.555
238170AE2-226 GEN2
Solar/Wind Helper
0.555
970825AG2-519 GEN
Solar/Wind Harmer
8.467
24289405MTG1
50/50
11.351
24318705GVG2
50/50
11.615
24722005FLATG5
50/50
2.756
24721905FLATG4
50/50
50.519
24686205CER G4
Adder
15.547
24686405CER G5
Adder
15.485
270053AF1-130 C
Solar/Wind Harmer
6.465
970153AG2-106 GEN
Solar/Wind Harmer
23.885
971191AH1-055 GEN
Solar/Wind Harmer
36.863
957541AF2-048 GEN
Solar/Wind Harmer
2.488
970913AG2-568 GEN
Solar/Wind Harmer
12.569
972103AH1-617 GEN
Solar/Wind Harmer
31.296
960911AF2-382 GEN
Solar/Wind Harmer
11.517
971461AH1-227 GEN
Solar/Wind Harmer
7.832
970243AG2-164 GEN
Solar/Wind Harmer
38.293
970519AG2-331 GEN
Solar/Wind Harmer
25.727
970699AG2-449 GEN
Solar/Wind Harmer
17.019
972167AH1-666 GEN
Solar/Wind Harmer
11.674
958171AF2-111 GEN
Solar/Wind Harmer
36.017
252510AF1-249 C
Solar/Wind Harmer
0.598
25196008MFTGT1
Adder
1.926
25194608D.CRK4
Adder
2.348
25196608WSDLE5
Adder
12.22
3429391JKCT 9G
Adder
11.865
970093AG2-073 GEN
Solar/Wind Harmer
14.232
253316AC1-085 GEN3
Solar/Wind Harmer
11.89
253433AC1-085 GEN1
Solar/Wind Harmer
7.548
946181AF1-283 GEN
Solar/Wind Harmer
18.454
253406AD2-031_GEN
Solar/Wind Harmer
1.808
966571AG1-526 GEN
Solar/Wind Harmer
31.338
270291AC1-194 GEN
Solar/Wind Harmer
14.929
253415AE1-040 GEN
Solar/Wind Harmer
1.582
24721605FLATG1
50/50
2.756
972203AH1-686 GEN
Adder
4.425
270330AC1-082 GEN2
Solar/Wind Harmer
1.362
270329AC1-082 GEN1
Solar/Wind Harmer
0.802
957241AF2-018 GEN
Solar/Wind Harmer
7.728
270399AC1-101 GEN
Solar/Wind Harmer
7.31
270400AC1-102 GEN
Solar/Wind Harmer
7.31
962771AG1-126 GEN
Solar/Wind Harmer
54.777
24477305BRIDGE
Adder
0.588
970281AG2-184 GEN
Solar/Wind Harmer
32.861
972143AH1-644 GEN
Solar/Wind Harmer
15.648
971985AH1-537 GEN
Solar/Wind Harmer
27.909
941621AE2-160 GEN
Adder
5.057
962211AG1-066 GEN
Solar/Wind Harmer
3.665
971313AH1-133 GEN
Solar/Wind Harmer
14.875
270367AC2-061_GEN
Solar/Wind Harmer
4.719
970879AG2-548 GEN
Solar/Wind Harmer
6.295
972163AH1-664 GEN
Solar/Wind Harmer
14.604
972165AH1-665 GEN
Solar/Wind Harmer
11.684
339243AC2-075 GEN1
Solar/Wind Harmer
0.653
25196108MFTGT2
Adder
2.193
25196108MFTGT2
Adder
2.036
3429211JKCT 2G
Adder
16.676
252524AE2-267 GEN
Solar/Wind Harmer
2.249
25196408WSDLE3
Adder
12.579
25196308WSDLE2
Adder
12.47
25196208WSDLE1
Adder
12.439
25196708WSDLE6
Adder
12.407
25196508WSDLE4
Adder
12.095
24734705WLF1G3
Adder
8.198
24734805WLF1G4
Adder
8.198
24734905WLF1G5
Adder
8.198
270340AC2-060 GEN
Solar/Wind Harmer
4.288
270132AB1-180 C
Adder
0.17
339211AE2-254 GEN
Solar/Wind Harmer
2.129
24735105WLF2G1
Adder
8.08
970455AG2-298 GEN
Solar/Wind Harmer
8.379
965401AG1-405 GEN
Solar/Wind Harmer
7.914
965411AG1-406 GEN
Solar/Wind Harmer
3.552
944031AF1-071 GEN
Solar/Wind Harmer
1.391
270269AC2-059
Solar/Wind Harmer
12.868
971061AG2-657 GEN
Solar/Wind Harmer
12.35
270240V3-007_GEN2
Solar/Wind Harmer
8.448
253372AE2-315 SEC3
Adder
2.585
253372AE2-315 SEC3
Adder
2.585
25306009OHH W.
Adder
3.927
24725505WLD G2 C
Solar/Wind Harmer
5.403
24699105WLD G1 C
Solar/Wind Harmer
5.339
253349AC2-067 GEN
Solar/Wind Harmer
6.756
253400AC2-068 GEN
Solar/Wind Harmer
2.717
965461AG1-414 GEN
Solar/Wind Harmer
3.069
970289AG2-191 GEN
Solar/Wind Harmer
2.572
270594AE1-207 GEN
Solar/Wind Harmer
19.886
963841AG1-237 GEN
Solar/Wind Harmer
14.783
24729505KEY G4
Adder
8.586
274775LINCOLN ;6U
Adder
11.055
274776LINCOLN ;7U
Adder
11.055
274777LINCOLN ;8U
Adder
11.055
274746AC1-111 G10
Adder
7.316
274744AC1-111 GEN8
Adder
7.316
274731ELWOOD EC;2P
Adder
21.509
274733ELWOOD EC;3P
Adder
13.442
23750501ELLIOTTS
Solar/Wind Helper
0.788
238126S14_GEN_1
Solar/Wind Helper
0.81
254304AE2-114 C
Solar/Wind Helper
0.239
241997AF1-093 GEN
Solar/Wind Helper
0.28
241982AE2-343 S C
Solar/Wind Helper
0.243
20092526R32
Solar/Wind Helper
1.311
203961AE2-224 GEN
Solar/Wind Helper
2.707
20091526CHSTN_FL
Solar/Wind Helper
0.654
238109AE1-109 GEN2
Solar/Wind Helper
0.102
238110AE1-109 GEN3
Solar/Wind Helper
0.102
20090526Q36
Solar/Wind Helper
1.167
203993AD2-133_GEN1
Solar/Wind Helper
1.167
941231AE2-117 GEN
Solar/Wind Helper
0.53
203846AF2-130 C
Solar/Wind Helper
0.497
203855AF2-088 C
Solar/Wind Helper
0.17
203804AE2-113_GEN
Solar/Wind Helper
1.924
972173AH1-669 GEN
Solar/Wind Harmer
6.941
270222AC2-111 GEN
Solar/Wind Harmer
11.283
972273AH1-721 GEN
Adder
114.731
270273AD2-016 GEN
Solar/Wind Harmer
3.68
270356AE2-297 GEN
Solar/Wind Harmer
6.29
24728705AND G3
Adder
11.022
24728505AND G1
Adder
5.27
970193AG2-126 GEN
Solar/Wind Harmer
20.501
270437AC2-090 C
Solar/Wind Harmer
7.623
253303V4-073 C
Solar/Wind Harmer
0.158
253370AE2-315 SEC1
Adder
2.733
253371AE2-315 SEC2
Adder
2.585
270346AE1-212 GEN
Solar/Wind Harmer
12.267
970273AG2-179 GEN
Solar/Wind Harmer
5.305
960741AF2-365 GEN
Solar/Wind Harmer
6.78
247642Z2-115 C
Solar/Wind Harmer
0.087
970289AG2-191 GEN
Solar/Wind Harmer
1.039
970291AG2-192 GEN
Solar/Wind Harmer
0.944
958821AF2-173 GEN
Solar/Wind Harmer
18.947
270004AE1-209 GEN
Solar/Wind Harmer
7.396
274772LINCOLN ;3U
Adder
11.055
274760LEE CO EC;1U
Adder
12.175
274767LEE CO EC;8U
Adder
12.032
274729ELWOOD EC;1P
Adder
21.509
237048AF1-022 C
Solar/Wind Helper
0.228
237043AE2-125 C
Solar/Wind Helper
0.207
235058AG1-386 C
Solar/Wind Helper
0.514
964991AG1-363 GEN
Solar/Wind Helper
4.415
23750701CROSSCHOOL
Solar/Wind Helper
1.427
238118U2-030_1
Solar/Wind Helper
0.343
202652Y1-033 WT C
Solar/Wind Helper
0.655
20089126CSLMN_L13
Solar/Wind Helper
0.683
20089026BF_G21_K23
Solar/Wind Helper
0.541
238127S14_GEN_2
Solar/Wind Helper
0.81
254305AE2-115 C
Solar/Wind Helper
0.239
203818AF1-086 GEN
Solar/Wind Helper
1.887
203854AF2-039 C
Solar/Wind Helper
0.354
20334926Z1-069 C
Solar/Wind Helper
1.49
238202AE2-262_GEN
Solar/Wind Helper
1.063
941421AE2-139 GEN
Solar/Wind Helper
2.573
959441AF2-235 GEN
Solar/Wind Helper
0.255
200917MEHOOPANY_G
Solar/Wind Helper
2.428
209071AE2-133 GEN
Solar/Wind Helper
0.09
946731AF1-337 GEN
Solar/Wind Helper
0.5
212507AE2-042_GEN
Solar/Wind Helper
1.772
961341AF2-425 GEN
Solar/Wind Helper
0.499
212266LOR1
Solar/Wind Helper
0.054
961301AF2-421 GEN
Solar/Wind Helper
0.496
963151AG1-164 GEN
Solar/Wind Helper
0.496
316097T157 G90
Solar/Wind Helper
1.154
203830AF1-094 GEN
Solar/Wind Helper
0.495
20671928W4-073
Solar/Wind Helper
0.098
207518AF1-320_GEN
Solar/Wind Helper
1.718
207437AD2-070 GEN
Solar/Wind Helper
0.15
20675828AU_W4-064
Solar/Wind Helper
0.032
207439AE1-081 C O1
Solar/Wind Helper
0.02
20674328GAR_V4-001
Solar/Wind Helper
0.024
217208PARK ELE C
Solar/Wind Helper
0.005
217209CENTRL HS C
Solar/Wind Helper
0.009
20676428JCR_X2-075
Solar/Wind Helper
0.073
207528AF2-192 GEN
Solar/Wind Helper
0.082
20673628F1S_V4-069
Solar/Wind Helper
0.032
20675428EAM_W2-061
Solar/Wind Helper
0.017
962511AG1-100 GEN
Solar/Wind Helper
0.488
217213AMBOY SO C
Solar/Wind Helper
0.031
218428ETC SOLAR C
Solar/Wind Helper
0.005
205941AD2-115 GEN
Solar/Wind Helper
0.531
20742028HF_AC1-207
Solar/Wind Helper
0.15
20715228NPK_W1-113
Solar/Wind Helper
0.083
207454AA2-184 E
Solar/Wind Helper
0.331
219680HOPEWELLV C1
Solar/Wind Helper
0.003
963711AG1-223 GEN
Solar/Wind Helper
0.068
20714828MDF_W3-079
Solar/Wind Helper
0.139
207445AB1-138_GEN
Solar/Wind Helper
0.111
20720728JCB_W1-129
Solar/Wind Helper
0.061
219304NAMERICA C
Solar/Wind Helper
0.139
219686LUMSOLAR_N C
Solar/Wind Helper
0.042
219907AC1-030 C
Solar/Wind Helper
0.036
218660EHAMPSOLAR C
Solar/Wind Helper
0.035
219904AC1-010 C
Solar/Wind Helper
0.064
219258KINSLEYDEP C
Solar/Wind Helper
0.081
228728W1-130C
Solar/Wind Helper
0.057
230434AG1-499 GEN
Solar/Wind Helper
0.241
230511AF1-262
Solar/Wind Helper
0.015
233972AC1-094 C
Solar/Wind Helper
0.312
233998TM1NIN_3.36
Solar/Wind Helper
0.27
233954AC2-188 GEN
Solar/Wind Helper
0.24
232404W1-003 C
Solar/Wind Helper
0.523
233950AC2-186 GEN
Solar/Wind Helper
0.12
232428Y3-058 C
Solar/Wind Helper
0.349
232434Z2-077 GEN
Solar/Wind Helper
0.131
232426Y1-080 FULL
Solar/Wind Helper
0.04
233964AF2-378 GEN
Solar/Wind Helper
0.043
232422X3-066 FULL
Solar/Wind Helper
0.118
233930AB2-032 GEN
Solar/Wind Helper
0.392
233915AB1-141 GEN
Solar/Wind Helper
0.518
966131AG1-482 GEN
Solar/Wind Helper
0.078
235062AE1-101 C1
Solar/Wind Helper
1.463
237038AE2-054 C
Solar/Wind Helper
0.238
237080AD1-060 GEN
Solar/Wind Helper
0.296
23779801AA1-109
Solar/Wind Helper
0.168
223401AF1-299 GEN
Solar/Wind Helper
0.338
959431AF2-234 GEN
Solar/Wind Helper
1
964051AG1-259 GEN
Solar/Wind Helper
0.075
964061AG1-260 GEN
Solar/Wind Helper
0.075
959421AF2-233 GEN
Solar/Wind Helper
0.5
961261AF2-417 GEN
Solar/Wind Helper
0.495
209116AE2-175 GEN
Solar/Wind Helper
1.966
20675128HRM_W1-127
Solar/Wind Helper
0.032
207408W3-077 C
Solar/Wind Helper
0.092
20675728RH_W2-091
Solar/Wind Helper
0.149
207484AF2-139 C O1
Solar/Wind Helper
0.092
203975AE1-071-GEN
Solar/Wind Helper
2.674
20674828DL_W4-046
Solar/Wind Helper
0.008
20675928HOL_W4-097
Solar/Wind Helper
0.055
20676328BVR_Y1-020
Solar/Wind Helper
0.029
238208AF1-136 C
Solar/Wind Helper
0.192
207530AG1-191 GEN
Solar/Wind Helper
0.072
966261AG1-495 GEN
Solar/Wind Helper
0.088
218524CNTRALGAS1 C
Solar/Wind Helper
0.173
20675528CPH_W2-050
Solar/Wind Helper
0.093
218526CNTRALGAS2 C
Solar/Wind Helper
0.173
219620RIDERU C
Solar/Wind Helper
0.001
207459AE1-142 C O1
Solar/Wind Helper
0.309
20715728PEM_W1-119
Solar/Wind Helper
0.102
20715828PEM_W1-120
Solar/Wind Helper
0.102
214067T20SOLAR
Solar/Wind Helper
0.012
959381AF2-229 GEN
Solar/Wind Helper
0.364
219607WPEMNERT C
Solar/Wind Helper
0.085
219688LUMSOLAR_S C
Solar/Wind Helper
0.042
219272CLEANLIGHT C
Solar/Wind Helper
0.027
219914AD2-027 C
Solar/Wind Helper
0.121
227927V4-067C
Solar/Wind Helper
0.011
228754AB1-001 C
Solar/Wind Helper
0.027
964001AG1-254 GEN
Solar/Wind Helper
1.003
234033AF1-007_GEN
Solar/Wind Helper
7.245
233923SMA
Solar/Wind Helper
0.989
233990AG1-397 GEN
Solar/Wind Helper
0.031
232432Z2-076 GEN
Solar/Wind Helper
0.069
237085AD2-009_GEN
Solar/Wind Helper
1.449
205932AD2-116_GEN
Solar/Wind Helper
0.523
205956AE1-196_GEN
Solar/Wind Helper
0.523
205943AE1-185 GEN
Solar/Wind Helper
0.523
232436AB1-176 C
Solar/Wind Helper
0.046
233935AB2-179 C
Solar/Wind Helper
1.307
960921AF2-383 GEN
Solar/Wind Helper
0.186
203835AF1-098 GEN
Solar/Wind Helper
1.958
20674628WNG_W3-110
Solar/Wind Helper
0.097
207510AF2-138 C
Solar/Wind Helper
0.088
20676728BRNX1-095
Solar/Wind Helper
0.032
217169METRODIV C
Solar/Wind Helper
0.004
217211CAMDEN ST C
Solar/Wind Helper
0.005
20673728F2S_V4-070
Solar/Wind Helper
0.032
219249CENTRALDIV C
Solar/Wind Helper
0.011
219908AB1-139 C
Solar/Wind Helper
0.079
219919AE1-041 FULL
Solar/Wind Helper
0.004
218438BLK ROCK C
Solar/Wind Helper
0.029
219612MATRIX C
Solar/Wind Helper
0.025
20720528MAN_W1-024
Solar/Wind Helper
0.03
20714528FRN_Y2-051
Solar/Wind Helper
0.061
219276PARKLANDSO C
Solar/Wind Helper
0.095
20720828JCB_W4-025
Solar/Wind Helper
0.067
20715028HAN_X4-015
Solar/Wind Helper
0.061
20716028EGP_W2-019
Solar/Wind Helper
0.02
959561AF2-247 GEN
Solar/Wind Helper
0.022
219348LDSOLAR C
Solar/Wind Helper
0.121
219906AC1-017 C
Solar/Wind Helper
0.044
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219291REEVESSOUT C
Solar/Wind Helper
0.012
219912AD2-042 GEN
Solar/Wind Helper
0.158
219766PARADISE C
Solar/Wind Helper
0.057
219623KINSLEYBEA C
Solar/Wind Helper
0.002
228729W2-030 C
Solar/Wind Helper
0.116
230415AB2-049 C
Solar/Wind Helper
0.032
230430AE1-229_GEN
Solar/Wind Helper
3.539
233971AC1-093 C
Solar/Wind Helper
0.369
233996TM1833_GEN
Solar/Wind Helper
0.27
233997TMININ_4.2
Solar/Wind Helper
0.27
233952AC2-187 GEN
Solar/Wind Helper
0.24
232406W1-004 FULL
Solar/Wind Helper
0.523
233940AF2-379 C
Solar/Wind Helper
0.064
234015AF2-250 C
Solar/Wind Helper
0.039
233994AC2-023 GEN
Solar/Wind Helper
0.992
233982AB2-133 GEN
Solar/Wind Helper
0.369
233918AB1-142 GEN
Solar/Wind Helper
0.518
235067AD1-061 GEN
Solar/Wind Helper
0.433
205917AD1-020 ES
Solar/Wind Helper
0.368
238221AF1-254 C O1
Solar/Wind Helper
0.236
237030AB1-096 C
Solar/Wind Helper
0.063
223402AF1-300 C
Solar/Wind Helper
0.338
970825AG2-519 GEN
Solar/Wind Harmer
1.889
944201AF1-088_MTX
Adder
163.563
957141AF2-008_MTX
Adder
81.782
CBM West 1LTFEXP_CBM-W1->PJM
CBM
170.264
CBM South 1LTFEXP_CBM-S1->PJM
CBM
48.581
MECLTFEXP_MEC->PJM
CLTF
21.939
SIGELTFEXP_SIGE->PJM
CLTF
0.729
LAGNLTFEXP_LAGN->PJM
CLTF
24.864
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.24
TVALTFEXP_TVA->PJM
CLTF
12.63
CPLELTFEXP_CPLE->PJM
CLTF
6.557
CBM West 2LTFEXP_CBM-W2->PJM
CBM
173.156
NYPJM->LTFIMP_NY
CLTF
6.276
LGEELTFEXP_LGEE->PJM
CLTF
9.844
WECLTFEXP_WEC->PJM
CLTF
5.002
AG2-052LTFEXP_AG2-052->PJM
LTF
0.306
AH1-155LTFEXP_AH1-155->PJM
LTF
0.459

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P1-2_#17217_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#17217_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:115.67 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6388.32
MW Contribution:9.19
Bus #Bus NameTypeMW Contribution
24289405MTG1
50/50
11.351
24318705GVG2
50/50
11.615
24722005FLATG5
50/50
2.756
24721905FLATG4
50/50
50.519
24686205CER G4
Adder
15.547
24686405CER G5
Adder
15.485
270053AF1-130 C
Solar/Wind Harmer
2.748
970153AG2-106 GEN
Solar/Wind Harmer
29.498
971191AH1-055 GEN
Solar/Wind Harmer
30.005
970913AG2-568 GEN
Solar/Wind Harmer
8.769
972103AH1-617 GEN
Solar/Wind Harmer
21.835
960911AF2-382 GEN
Solar/Wind Harmer
8.035
971461AH1-227 GEN
Solar/Wind Harmer
5.464
970243AG2-164 GEN
Solar/Wind Harmer
6.06
970519AG2-331 GEN
Solar/Wind Harmer
26.931
970699AG2-449 GEN
Solar/Wind Harmer
2.59
972167AH1-666 GEN
Solar/Wind Harmer
8.145
958171AF2-111 GEN
Solar/Wind Harmer
25.128
252510AF1-249 C
Solar/Wind Harmer
0.077
25196008MFTGT1
Adder
1.926
25194608D.CRK4
Adder
2.348
25196608WSDLE5
Adder
12.22
3429391JKCT 9G
Adder
11.865
970093AG2-073 GEN
Solar/Wind Harmer
9.929
253316AC1-085 GEN3
Solar/Wind Harmer
0.006
253433AC1-085 GEN1
Solar/Wind Harmer
0.005
946181AF1-283 GEN
Solar/Wind Harmer
12.875
253406AD2-031_GEN
Solar/Wind Harmer
0.735
966571AG1-526 GEN
Solar/Wind Harmer
21.864
270291AC1-194 GEN
Solar/Wind Harmer
7.771
253415AE1-040 GEN
Solar/Wind Harmer
0.004
972173AH1-669 GEN
Solar/Wind Harmer
4.843
270222AC2-111 GEN
Solar/Wind Harmer
4.893
972273AH1-721 GEN
Adder
114.731
270273AD2-016 GEN
Solar/Wind Harmer
0.998
270356AE2-297 GEN
Solar/Wind Harmer
0.013
24728705AND G3
Adder
11.022
24728505AND G1
Adder
5.27
970193AG2-126 GEN
Solar/Wind Harmer
14.303
270437AC2-090 C
Solar/Wind Harmer
0.004
253370AE2-315 SEC1
Adder
2.733
253371AE2-315 SEC2
Adder
2.585
270346AE1-212 GEN
Solar/Wind Harmer
8.4
970273AG2-179 GEN
Solar/Wind Harmer
5.694
960741AF2-365 GEN
Solar/Wind Harmer
4.731
970191AG2-125 GEN
Solar/Wind Harmer
2.433
247642Z2-115 C
Solar/Wind Harmer
0.004
970289AG2-191 GEN
Solar/Wind Harmer
1.039
970291AG2-192 GEN
Solar/Wind Harmer
0.944
958821AF2-173 GEN
Solar/Wind Harmer
13.219
270004AE1-209 GEN
Solar/Wind Harmer
2.046
946031AF1-268 GEN
Solar/Wind Harmer
8.936
339250AF1-203 GEN
Solar/Wind Harmer
0.001
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
9.369
971155AH1-034 GEN
Solar/Wind Harmer
10.922
970513AG2-328 GEN
Solar/Wind Harmer
4.056
970517AG2-330 GEN
Solar/Wind Harmer
24.338
962251AG1-071 GEN
Solar/Wind Harmer
5.847
942481AE2-261 GEN
Solar/Wind Harmer
27.825
276621W2-048 GEN
Solar/Wind Harmer
0.469
276838X2-022 GEN2
Solar/Wind Harmer
0.523
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
4.291
276668AB2-070 GEN1
Solar/Wind Harmer
0.339
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
943031AE2-326 GEN
Solar/Wind Harmer
4.828
274853TWINGROVE;U1
Solar/Wind Harmer
0.004
965091AG1-374 GEN
Solar/Wind Harmer
27.736
959611AF2-252 GEN
Solar/Wind Harmer
3.082
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
13.864
942111AE2-223 GEN
Solar/Wind Harmer
3.001
964401AG1-302 GEN
Solar/Wind Harmer
0.001
944531AF1-118 GEN
Solar/Wind Harmer
41.286
270535AF1-215 GEN1
Solar/Wind Harmer
0.011
274878BISHOP HL;2U
Solar/Wind Harmer
0.308
253338AC1-165 GEN
Solar/Wind Harmer
0.004
253333AC1-068 GEN
Solar/Wind Harmer
0.014
970571AG2-364 GEN
Solar/Wind Harmer
18.307
276889AE2-281 GEN
Solar/Wind Harmer
0.001
276897AD1-100 C
Solar/Wind Harmer
0.012
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
274772LINCOLN ;3U
Adder
11.055
276805AD2-038 GEN
Solar/Wind Harmer
0.003
276157O29GEN1
Solar/Wind Harmer
1.478
970707AG2-453 GEN
Solar/Wind Harmer
29.848
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
943121AE2-341 GEN
Solar/Wind Harmer
15.314
943591AF1-030 GEN
Solar/Wind Harmer
10.184
274855GSG-6 ;RU
Solar/Wind Harmer
0.335
274850MENDOTA H;RU
Solar/Wind Harmer
0.108
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.164
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
0.974
274760LEE CO EC;1U
Adder
12.175
274767LEE CO EC;8U
Adder
12.032
274729ELWOOD EC;1P
Adder
21.509
237048AF1-022 C
Solar/Wind Helper
0.228
237043AE2-125 C
Solar/Wind Helper
0.207
235058AG1-386 C
Solar/Wind Helper
0.514
964991AG1-363 GEN
Solar/Wind Helper
4.415
23750701CROSSCHOOL
Solar/Wind Helper
1.427
238118U2-030_1
Solar/Wind Helper
0.343
202652Y1-033 WT C
Solar/Wind Helper
0.655
20089126CSLMN_L13
Solar/Wind Helper
0.683
20089026BF_G21_K23
Solar/Wind Helper
0.541
238127S14_GEN_2
Solar/Wind Helper
0.81
254305AE2-115 C
Solar/Wind Helper
0.239
203818AF1-086 GEN
Solar/Wind Helper
1.887
203854AF2-039 C
Solar/Wind Helper
0.354
20334926Z1-069 C
Solar/Wind Helper
1.49
238202AE2-262_GEN
Solar/Wind Helper
1.063
941421AE2-139 GEN
Solar/Wind Helper
2.573
959441AF2-235 GEN
Solar/Wind Helper
0.255
200917MEHOOPANY_G
Solar/Wind Helper
2.428
243186AF1-051 GEN
50/50
12.478
24723005RIVRG1
Adder
36.021
24723105RIVRG2
Adder
36.021
24685805CER G1
Adder
15.526
24685905CER G2
Adder
15.526
944971AF1-162 GEN
Solar/Wind Harmer
12.174
971225AH1-072 GEN
Solar/Wind Harmer
2.13
971227AH1-073 GEN
Solar/Wind Harmer
2.13
24728205BUCHG1
Adder
6.831
970239AG2-162 GEN
Solar/Wind Harmer
2.59
270186AC1-089 GEN
Solar/Wind Harmer
0.006
962581AG1-107 GEN
Solar/Wind Harmer
0.002
960161AF2-307 GEN
Solar/Wind Harmer
6.771
971073AG2-665 GEN
Solar/Wind Harmer
9.191
252509AD1-136 GEN
Solar/Wind Harmer
0.051
339221AD2-048_GEN
Solar/Wind Harmer
0.006
972043AH1-570 GEN
Solar/Wind Harmer
2.614
972045AH1-571 GEN
Solar/Wind Harmer
2.094
25183208HLCRTG
Solar/Wind Harmer
0.016
252519AF1-045_GEN
Solar/Wind Harmer
8.714
252516AE2-318_GEN
Solar/Wind Harmer
7.729
970235AG2-159 GEN
Solar/Wind Harmer
6.108
970235AG2-159 GEN
Solar/Wind Harmer
3.504
971125AH1-004 GEN
Solar/Wind Harmer
3.992
970107AG2-081 GEN
Solar/Wind Harmer
2.994
25194408D.CRK1
Adder
10.799
25194508D.CRK3
Adder
2.019
942891AE2-308 GEN
Solar/Wind Harmer
9.954
253317AC1-085 GEN4
Solar/Wind Harmer
0.006
270444AC2-157 GEN1
Solar/Wind Harmer
0.004
971587AH1-292 GEN
Solar/Wind Harmer
7.197
253394AE2-221_GEN
Solar/Wind Harmer
0.012
253398AE2-221_GEN2
Solar/Wind Harmer
0.012
964571AG1-320 GEN
Solar/Wind Harmer
8.854
970653AG2-424 GEN
Solar/Wind Harmer
4.654
970653AG2-424 GEN
Solar/Wind Harmer
2.412
24728805RICHG1
Adder
5.204
24728905RICHG2
Adder
5.204
971081AG2-670 GEN
Solar/Wind Harmer
7.154
945391AF1-204 GEN
Solar/Wind Harmer
10.131
24379505HDWTR1G C
Solar/Wind Harmer
0.003
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
253370AE2-315 SEC1
Adder
2.733
270383AD1-128 GEN
Solar/Wind Harmer
0.006
970241AG2-163 GEN
Solar/Wind Harmer
5.517
971613AH1-306 GEN
Solar/Wind Harmer
4.531
25322209TAIT E
Adder
13.187
25322209TAIT E
Adder
12.891
970825AG2-519 GEN
Solar/Wind Harmer
10.439
24721605FLATG1
50/50
2.756
972203AH1-686 GEN
Adder
4.425
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
957241AF2-018 GEN
Solar/Wind Harmer
-0.002
270399AC1-101 GEN
Solar/Wind Harmer
3.805
270400AC1-102 GEN
Solar/Wind Harmer
3.805
962771AG1-126 GEN
Solar/Wind Harmer
46.194
24477305BRIDGE
Adder
0.588
970281AG2-184 GEN
Solar/Wind Harmer
22.926
972143AH1-644 GEN
Solar/Wind Harmer
11.827
971985AH1-537 GEN
Solar/Wind Harmer
3.245
941621AE2-160 GEN
Adder
5.057
971313AH1-133 GEN
Solar/Wind Harmer
10.378
270367AC2-061_GEN
Solar/Wind Harmer
0.008
970879AG2-548 GEN
Solar/Wind Harmer
9.191
972163AH1-664 GEN
Solar/Wind Harmer
11.344
972165AH1-665 GEN
Solar/Wind Harmer
9.085
339243AC2-075 GEN1
Solar/Wind Harmer
0.002
25196108MFTGT2
Adder
2.193
25196108MFTGT2
Adder
2.036
24289405MTG1
50/50
11.351
243186AF1-051 GEN
50/50
12.478
24318705GVG2
50/50
11.615
24721805FLATG3
50/50
2.756
24721705FLATG2
50/50
50.519
24723205RIVRG3
Adder
36.021
24686105CER G3
Adder
15.629
24686505CER G6
Adder
15.608
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
970947AG2-589 GEN
Solar/Wind Harmer
0.412
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
971403AH1-188 GEN
Solar/Wind Harmer
16.785
962761AG1-125 GEN
Solar/Wind Harmer
46.194
970149AG2-104 GEN
Solar/Wind Harmer
49.891
970155AG2-107 GEN
Solar/Wind Harmer
29.498
971315AH1-136 GEN
Solar/Wind Harmer
2.232
927014AC1-188 GEN
Solar/Wind Harmer
0.007
971687AH1-348 GEN
Solar/Wind Harmer
1.067
24728305BUCHG2
Adder
6.831
970333AG2-219 GEN
Solar/Wind Harmer
7.406
970091AG2-072 GEN
Adder
113.581
945681AF1-233 GEN
Solar/Wind Harmer
19.197
252507AC2-088 GEN
Solar/Wind Harmer
0.46
25196808ZIMRHP
Adder
109.116
339216AC1-074 GEN
Solar/Wind Harmer
0.274
25196008MFTGT1
Adder
1.989
25194608D.CRK4
Adder
2.348
3429241JKCT 3G
Adder
16.894
3429421JKCT 10G
Adder
11.865
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
9.904
270263AC1-001 GEN
Solar/Wind Harmer
0.987
270445AC2-157 GEN2
Solar/Wind Harmer
0.004
971565AH1-281 GEN
Solar/Wind Harmer
1.958
971821AH1-427 GEN
Solar/Wind Harmer
9.786
24735205WLF2G2
Adder
8.08
970773AG2-487 GEN
Solar/Wind Harmer
1.7
24728605AND G2
Adder
5.27
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0.001
970613AG2-401 GEN
Solar/Wind Harmer
6.984
253370AE2-315 SEC1
Adder
2.733
253371AE2-315 SEC2
Adder
2.585
970273AG2-179 GEN
Solar/Wind Harmer
3.322
276903AD2-071 C
Solar/Wind Harmer
10.574
963741AG1-226 GEN
Solar/Wind Harmer
22.385
970291AG2-192 GEN
Solar/Wind Harmer
1.228
270005AE1-210 C O1
Solar/Wind Harmer
2.046
965031AG1-367 GEN
Solar/Wind Harmer
9.442
270032AE2-172
Solar/Wind Harmer
6.293
25326309TAIT D
Adder
1.481
964901AG1-354 GEN
Solar/Wind Harmer
14.138
960071AF2-298 GEN
Solar/Wind Harmer
4.694
970825AG2-519 GEN
Solar/Wind Harmer
3.343
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.004
24791305MDL-5G
Solar/Wind Harmer
0.001
970245AG2-165 GEN
Solar/Wind Harmer
4.056
962241AG1-070 GEN
Solar/Wind Harmer
5.098
945371AF1-202 GEN
Solar/Wind Harmer
0.001
958861AF2-177 GEN
Solar/Wind Harmer
4.037
965911AG1-460 GEN
Solar/Wind Harmer
1.861
247536S-71 GEN
Solar/Wind Harmer
0.374
965651AG1-433 GEN
Solar/Wind Harmer
2.727
276615X2-022 GEN
Solar/Wind Harmer
0.098
963831AG1-236 GEN
Solar/Wind Harmer
3.623
274880W4-005 GEN4
Solar/Wind Harmer
0.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
11.601
972175AH1-670 GEN
Solar/Wind Harmer
7.662
274854TWINGROVE;U2
Solar/Wind Harmer
0.004
276726Z2-087_GEN
Solar/Wind Harmer
0.003
939741AE1-205 GEN
Solar/Wind Harmer
12.928
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
11.983
958381AF2-132 GEN
Solar/Wind Harmer
0.001
939401AE1-172 GEN
Solar/Wind Harmer
6.864
270055AF2-134 C O1
Solar/Wind Harmer
0.007
274877BISHOP HL;1U
Solar/Wind Harmer
0.308
253343AC1-166 GEN
Solar/Wind Harmer
0.004
253325AC1-069 GEN
Solar/Wind Harmer
0.014
970569AG2-363 GEN
Solar/Wind Harmer
27.46
971997AH1-543 GEN
Solar/Wind Harmer
4.802
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
276901AD2-066 C O1
Solar/Wind Harmer
0.009
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274773LINCOLN ;4U
Adder
11.055
274774LINCOLN ;5U
Adder
11.055
276158O29GEN2
Solar/Wind Harmer
0.001
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
276691AA1-018 GEN1
Solar/Wind Harmer
1.106
274745AC1-111 GEN9
Adder
7.316
276861AD2-134 GEN
Solar/Wind Harmer
0.164
274872LEEDK;1U
Solar/Wind Harmer
0.006
274761LEE CO EC;2U
Adder
12.175
274766LEE CO EC;7U
Adder
12.032
237046AF1-021 C
Solar/Wind Helper
0.577
238185AF2-356 C
Solar/Wind Helper
2.612
23751201ROTHROCK
Solar/Wind Helper
0.878
235054AD2-180 GEN
Solar/Wind Helper
2.032
23562501BACKB
Solar/Wind Helper
1.07
238117U2-030
Solar/Wind Helper
0.343
235531U2-073 GEN
Solar/Wind Helper
3.23
20089226LOOKOUT
Solar/Wind Helper
0.665
254303AC2-168 GEN
Solar/Wind Helper
0.173
241966AE1-183 GEN
Solar/Wind Helper
0.28
23751101LEADS_P59
Solar/Wind Helper
1.483
20088826HIGHLAND
Solar/Wind Helper
1.011
20094526CT_V3-030
Solar/Wind Helper
0.53
964201AG1-281 GEN
Solar/Wind Helper
0.544
238108AE1-109 GEN1
Solar/Wind Helper
0.102
964391AG1-301 GEN
Solar/Wind Helper
0.529
203954AE2-126 C
Solar/Wind Helper
0.522
238206AE2-263_GEN
Solar/Wind Helper
1.011
959471AF2-238 GEN
Solar/Wind Helper
0.517
203860AG1-193 C
Solar/Wind Helper
0.254
209067AE2-060 GEN
Solar/Wind Helper
0.091
946691AF1-333 GEN
Solar/Wind Helper
0.5
960441AF2-335 GEN
Solar/Wind Harmer
9.416
966841AG1-555 GEN
Solar/Wind Harmer
1.065
339255AE2-071 GEN
Solar/Wind Harmer
-0.154
970321AG2-212 GEN
Solar/Wind Harmer
4.056
971485AH1-239 GEN
Solar/Wind Harmer
7.489
964781AG1-341 GEN
Solar/Wind Harmer
9.922
966021AG1-471 GEN
Solar/Wind Harmer
5.054
25326109MON D
Adder
1.763
970883AG2-550 GEN
Solar/Wind Harmer
9.347
970885AG2-551 GEN
Solar/Wind Harmer
3.116
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
270599AE1-208 GEN
Solar/Wind Harmer
8.564
270031AE2-169
Solar/Wind Harmer
5.138
276916AD2-100_GEN
Solar/Wind Harmer
19.555
276911AD2-131_GEN
Solar/Wind Harmer
1.288
944541AF1-119 GEN
Solar/Wind Harmer
0.623
960971AF2-388 GEN
Solar/Wind Harmer
5.453
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
0.696
247621Y3-024
Adder
0.32
960611AF2-352 GEN
Solar/Wind Harmer
3.082
270201AC2-176 GEN
Solar/Wind Harmer
0.002
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.36
276646AC1-214 GEN2
Solar/Wind Harmer
0.36
276782AC1-033 GEN
Solar/Wind Harmer
0.001
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
274879MINONK ;1U
Solar/Wind Harmer
0.386
274770LINCOLN ;1U
Adder
11.055
274771LINCOLN ;2U
Adder
11.055
276741O09 GEN1
Solar/Wind Harmer
0.325
276708O09 GEN2
Solar/Wind Harmer
0.325
958491AF2-143 GEN
Solar/Wind Harmer
13.709
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
1.236
972259AH1-714 GEN
Adder
24.976
958481AF2-142 GEN
Solar/Wind Harmer
13.701
971573AH1-285 GEN
Solar/Wind Harmer
1.702
276603SUBLETTE C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
5.45
274696ROCKY RD ;4P
Adder
14.914
274695ROCKY RD ;2P
Adder
14.57
274693ROCKY RD ;1P
Adder
14.427
274764LEE CO EC;5U
Adder
12.204
274765LEE CO EC;6U
Adder
12.204
274762LEE CO EC;3U
Adder
12.175
274763LEE CO EC;4U
Adder
12.06
274697ROCKY RD ;3P
Adder
3.958
23652301WDPWR_K20
Solar/Wind Helper
0.168
23585401KL_K28_T16
Solar/Wind Helper
1.53
203955AF1-039 C O1
Solar/Wind Helper
0.432
944781AF1-143 GEN
Solar/Wind Helper
2.836
238120AE2-309 GEN
Solar/Wind Helper
0.507
962101AG1-054 GEN
Solar/Wind Helper
0.715
20083426SW_E13_K22
Solar/Wind Helper
0.064
241985AE1-237 GEN
Solar/Wind Helper
0.271
241967AE2-285_GEN
Solar/Wind Helper
0.696
241801AE1-079 GEN
Solar/Wind Helper
0.271
20088926STNY CRK
Solar/Wind Helper
0.928
946071AF1-272 GEN
Solar/Wind Helper
3.051
20084626FORWARD
Solar/Wind Helper
0.402
203940AF1-140 C
Solar/Wind Helper
0.446
20088626ARWF_N39
Solar/Wind Helper
1.362
20303426NA_O38_P22
Solar/Wind Helper
1.117
203853AF1-134 C O1
Solar/Wind Helper
0.534
946381AF1-302 GEN
Solar/Wind Helper
0.246
203952AE2-129 C
Solar/Wind Helper
0.529
203946AE2-131 C
Solar/Wind Helper
0.53
238217AF1-153 C O1
Solar/Wind Helper
0.262
20398826ARMNA MT
Solar/Wind Helper
1.656
209137AF2-361 C
Solar/Wind Helper
1.531
946751AF1-339 GEN
Solar/Wind Helper
0.5
209054AE2-059 GEN
Solar/Wind Helper
0.09
961431AF2-434 GEN
Solar/Wind Helper
0.499
208972BECR K09
Solar/Wind Helper
0.372
209029WAYMART-WD
Solar/Wind Helper
0.937
203979AG1-198 GEN
Solar/Wind Helper
0.297
211065PSPA IPP
Solar/Wind Helper
0.168
211065PSPA IPP
Solar/Wind Helper
0.168
203980AG1-197 GEN
Solar/Wind Helper
0.369
966111AG1-480 GEN
Solar/Wind Helper
0.082
20674128FR_U2-059
Solar/Wind Helper
0.004
964851AG1-348 GEN
Solar/Wind Helper
0.088
207471AF2-354 C
Solar/Wind Helper
0.184
20674928WA_W3-044
Solar/Wind Helper
0.107
20676228FRD_X1-012
Solar/Wind Helper
0.1
217204WCALDSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217081WEATEXAS C
Solar/Wind Helper
0.014
20671828STAW2-080
Solar/Wind Helper
0.029
207442AE1-156 GEN
Solar/Wind Helper
0.351
20676128MHD_W3-029
Solar/Wind Helper
0.103
20673828FLE_V3-070
Solar/Wind Helper
0.097
218440SUMMTASSOC C
Solar/Wind Helper
0.018
20716928W4-060COL
Solar/Wind Helper
0.055
20720628TIN_W1-124
Solar/Wind Helper
0.203
963391AG1-188 GEN
Solar/Wind Helper
0.088
20714928UPF_X1-085
Solar/Wind Helper
0.005
3429211JKCT 2G
Adder
16.676
252524AE2-267 GEN
Solar/Wind Harmer
0.004
25196408WSDLE3
Adder
12.579
25196308WSDLE2
Adder
12.47
25196208WSDLE1
Adder
12.439
25196708WSDLE6
Adder
12.407
25196508WSDLE4
Adder
12.095
24734705WLF1G3
Adder
8.198
24734805WLF1G4
Adder
8.198
24734905WLF1G5
Adder
8.198
270340AC2-060 GEN
Solar/Wind Harmer
0.011
270132AB1-180 C
Adder
0.17
339211AE2-254 GEN
Solar/Wind Harmer
0.004
24735105WLF2G1
Adder
8.08
970455AG2-298 GEN
Solar/Wind Harmer
6.495
965401AG1-405 GEN
Solar/Wind Harmer
5.522
965411AG1-406 GEN
Solar/Wind Harmer
3.552
270269AC2-059
Solar/Wind Harmer
0.006
971061AG2-657 GEN
Solar/Wind Harmer
6.031
270240V3-007_GEN2
Solar/Wind Harmer
0.003
253372AE2-315 SEC3
Adder
2.585
253372AE2-315 SEC3
Adder
2.585
25306009OHH W.
Adder
3.927
24725505WLD G2 C
Solar/Wind Harmer
0.002
24699105WLD G1 C
Solar/Wind Harmer
0.001
253349AC2-067 GEN
Solar/Wind Harmer
2.978
253400AC2-068 GEN
Solar/Wind Harmer
1.198
970289AG2-191 GEN
Solar/Wind Harmer
1.794
270594AE1-207 GEN
Solar/Wind Harmer
10.572
963841AG1-237 GEN
Solar/Wind Harmer
4.089
970115AG2-085 GEN
Solar/Wind Harmer
3.766
971673AH1-337 GEN
Solar/Wind Harmer
6.118
24386205FR-12G C
Solar/Wind Harmer
0.002
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.002
971029AG2-637 GEN
Solar/Wind Harmer
14.095
24690905MDL-1G C
Solar/Wind Harmer
0.003
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0.001
270543AE2-219 C
Solar/Wind Harmer
0.006
971609AH1-304 GEN
Solar/Wind Harmer
1.526
270432AC2-029 GEN
Solar/Wind Harmer
4.141
944221AF1-090 GEN
Solar/Wind Harmer
5.475
965101AG1-375 GEN
Solar/Wind Harmer
9.315
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.339
276848AB2-070 GEN3
Solar/Wind Harmer
0.337
971611AH1-305 GEN
Solar/Wind Harmer
5.525
958391AF2-133 GEN
Solar/Wind Harmer
0.001
276655WTG1_EQ
Solar/Wind Harmer
0.004
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
9.696
24729505KEY G4
Adder
8.586
941731AE2-173 GEN
Solar/Wind Harmer
7.695
966391AG1-508 GEN
Solar/Wind Harmer
1.427
970169AG2-114 GEN
Solar/Wind Harmer
9.2
274863CRW1-WTG
Solar/Wind Harmer
0.003
274864CRW2-WTG
Solar/Wind Harmer
0.003
241972AD1-140 GEN
Solar/Wind Harmer
1.003
274848CAMPGROVE;RU
Solar/Wind Harmer
0.002
957751AF2-069 GEN
Solar/Wind Harmer
0.302
270536AF1-215 GEN2
Solar/Wind Harmer
0.011
926823AC1-168 GEN
Solar/Wind Harmer
1.557
276868AE1-113 GEN
Solar/Wind Harmer
1.835
276882AE2-255 GEN
Solar/Wind Harmer
1.069
274775LINCOLN ;6U
Adder
11.055
274776LINCOLN ;7U
Adder
11.055
274777LINCOLN ;8U
Adder
11.055
970833AG2-524 GEN
Solar/Wind Harmer
10.052
970833AG2-524 GEN
Solar/Wind Harmer
6.701
274746AC1-111 G10
Adder
7.316
274744AC1-111 GEN8
Adder
7.316
961011AF2-392 GEN
Solar/Wind Harmer
5.358
971675AH1-338 GEN
Solar/Wind Harmer
3.562
274731ELWOOD EC;2P
Adder
21.509
274733ELWOOD EC;3P
Adder
13.442
23750501ELLIOTTS
Solar/Wind Helper
0.788
238126S14_GEN_1
Solar/Wind Helper
0.81
254304AE2-114 C
Solar/Wind Helper
0.239
241997AF1-093 GEN
Solar/Wind Helper
0.28
241982AE2-343 S C
Solar/Wind Helper
0.243
20092526R32
Solar/Wind Helper
1.311
203961AE2-224 GEN
Solar/Wind Helper
2.707
20091526CHSTN_FL
Solar/Wind Helper
0.654
238109AE1-109 GEN2
Solar/Wind Helper
0.102
238110AE1-109 GEN3
Solar/Wind Helper
0.102
20090526Q36
Solar/Wind Helper
1.167
203993AD2-133_GEN1
Solar/Wind Helper
1.167
941231AE2-117 GEN
Solar/Wind Helper
0.53
203846AF2-130 C
Solar/Wind Helper
0.497
203855AF2-088 C
Solar/Wind Helper
0.17
203804AE2-113_GEN
Solar/Wind Helper
1.924
959431AF2-234 GEN
Solar/Wind Helper
1
964051AG1-259 GEN
Solar/Wind Helper
0.075
964061AG1-260 GEN
Solar/Wind Helper
0.075
959421AF2-233 GEN
Solar/Wind Helper
0.5
961261AF2-417 GEN
Solar/Wind Helper
0.495
209116AE2-175 GEN
Solar/Wind Helper
1.966
20675128HRM_W1-127
Solar/Wind Helper
0.032
963401AG1-189 GEN
Solar/Wind Helper
0.06
20390526W1-045 C
Solar/Wind Helper
0.357
219615MILLCREEK C
Solar/Wind Helper
0.028
219921AF1-264
Solar/Wind Helper
0.054
203947AF1-006 C
Solar/Wind Helper
0.527
230407AD2-065 C
Solar/Wind Helper
0.042
230433AD2-135 GEN
Solar/Wind Helper
0.018
233939AC1-091 C
Solar/Wind Helper
0.361
233970AC1-092 C
Solar/Wind Helper
0.361
233901CHERRYDALE C
Solar/Wind Helper
0.24
232408W1-005 C
Solar/Wind Helper
0.523
232410W1-006 C
Solar/Wind Helper
0.523
233946AB2-136 GEN
Solar/Wind Helper
0.586
234036AF2-325 C
Solar/Wind Helper
0.043
233987AB2-037 GEN
Solar/Wind Helper
2.415
233944AB2-135 GEN
Solar/Wind Helper
0.607
232424Y1-079 C
Solar/Wind Helper
0.12
233933AB2-153 GEN
Solar/Wind Helper
0.24
235063AE1-101 C2
Solar/Wind Helper
1.463
205916AD1-020 GEN
Solar/Wind Helper
1.711
237002AB1-128_GEN
Solar/Wind Helper
0.388
237001AB1-127_GEN
Solar/Wind Helper
0.388
235020AA1-095 C
Solar/Wind Helper
0.045
23777901MDS_W4-102
Solar/Wind Helper
0.15
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
237034AC2-136 C
Solar/Wind Helper
0.194
238175AF1-290_GEN
Solar/Wind Helper
0.123
237025AB1-124 C
Solar/Wind Helper
0.145
237006AB1-125 GEN
Solar/Wind Helper
0.109
23777801MSM_W1-116
Solar/Wind Helper
0.1
238169AE2-226 GEN1
Solar/Wind Helper
0.555
238170AE2-226 GEN2
Solar/Wind Helper
0.555
971341AH1-150 GEN
Solar/Wind Harmer
3.998
971343AH1-151 GEN
Solar/Wind Harmer
3.998
209071AE2-133 GEN
Solar/Wind Helper
0.09
946731AF1-337 GEN
Solar/Wind Helper
0.5
212507AE2-042_GEN
Solar/Wind Helper
1.772
961341AF2-425 GEN
Solar/Wind Helper
0.499
212266LOR1
Solar/Wind Helper
0.054
961301AF2-421 GEN
Solar/Wind Helper
0.496
963151AG1-164 GEN
Solar/Wind Helper
0.496
316097T157 G90
Solar/Wind Helper
1.154
203830AF1-094 GEN
Solar/Wind Helper
0.495
20671928W4-073
Solar/Wind Helper
0.098
207518AF1-320_GEN
Solar/Wind Helper
1.718
207437AD2-070 GEN
Solar/Wind Helper
0.15
20675828AU_W4-064
Solar/Wind Helper
0.032
207439AE1-081 C O1
Solar/Wind Helper
0.02
20674328GAR_V4-001
Solar/Wind Helper
0.024
217208PARK ELE C
Solar/Wind Helper
0.005
217209CENTRL HS C
Solar/Wind Helper
0.009
20676428JCR_X2-075
Solar/Wind Helper
0.073
207528AF2-192 GEN
Solar/Wind Helper
0.082
20673628F1S_V4-069
Solar/Wind Helper
0.032
20675428EAM_W2-061
Solar/Wind Helper
0.017
962511AG1-100 GEN
Solar/Wind Helper
0.488
217213AMBOY SO C
Solar/Wind Helper
0.031
218428ETC SOLAR C
Solar/Wind Helper
0.005
205941AD2-115 GEN
Solar/Wind Helper
0.531
20742028HF_AC1-207
Solar/Wind Helper
0.15
20715228NPK_W1-113
Solar/Wind Helper
0.083
207454AA2-184 E
Solar/Wind Helper
0.331
219680HOPEWELLV C1
Solar/Wind Helper
0.003
963711AG1-223 GEN
Solar/Wind Helper
0.068
20714828MDF_W3-079
Solar/Wind Helper
0.139
207445AB1-138_GEN
Solar/Wind Helper
0.111
20720728JCB_W1-129
Solar/Wind Helper
0.061
219304NAMERICA C
Solar/Wind Helper
0.139
219686LUMSOLAR_N C
Solar/Wind Helper
0.042
219907AC1-030 C
Solar/Wind Helper
0.036
218660EHAMPSOLAR C
Solar/Wind Helper
0.035
219904AC1-010 C
Solar/Wind Helper
0.064
219258KINSLEYDEP C
Solar/Wind Helper
0.081
228728W1-130C
Solar/Wind Helper
0.057
230434AG1-499 GEN
Solar/Wind Helper
0.241
230511AF1-262
Solar/Wind Helper
0.015
233972AC1-094 C
Solar/Wind Helper
0.312
233998TM1NIN_3.36
Solar/Wind Helper
0.27
233954AC2-188 GEN
Solar/Wind Helper
0.24
232404W1-003 C
Solar/Wind Helper
0.523
233950AC2-186 GEN
Solar/Wind Helper
0.12
232428Y3-058 C
Solar/Wind Helper
0.349
232434Z2-077 GEN
Solar/Wind Helper
0.131
232426Y1-080 FULL
Solar/Wind Helper
0.04
233964AF2-378 GEN
Solar/Wind Helper
0.043
232422X3-066 FULL
Solar/Wind Helper
0.118
233930AB2-032 GEN
Solar/Wind Helper
0.392
233915AB1-141 GEN
Solar/Wind Helper
0.518
966131AG1-482 GEN
Solar/Wind Helper
0.139
235062AE1-101 C1
Solar/Wind Helper
1.463
237038AE2-054 C
Solar/Wind Helper
0.238
237080AD1-060 GEN
Solar/Wind Helper
0.296
23779801AA1-109
Solar/Wind Helper
0.168
223401AF1-299 GEN
Solar/Wind Helper
0.338
959091AF2-200 GEN
Solar/Wind Harmer
3.998
207408W3-077 C
Solar/Wind Helper
0.092
20675728RH_W2-091
Solar/Wind Helper
0.149
207484AF2-139 C O1
Solar/Wind Helper
0.092
203975AE1-071-GEN
Solar/Wind Helper
2.674
20674828DL_W4-046
Solar/Wind Helper
0.008
20675928HOL_W4-097
Solar/Wind Helper
0.055
20676328BVR_Y1-020
Solar/Wind Helper
0.029
238208AF1-136 C
Solar/Wind Helper
0.192
207530AG1-191 GEN
Solar/Wind Helper
0.072
966261AG1-495 GEN
Solar/Wind Helper
0.088
218524CNTRALGAS1 C
Solar/Wind Helper
0.173
20675528CPH_W2-050
Solar/Wind Helper
0.093
218526CNTRALGAS2 C
Solar/Wind Helper
0.173
219620RIDERU C
Solar/Wind Helper
0.001
207459AE1-142 C O1
Solar/Wind Helper
0.309
20715728PEM_W1-119
Solar/Wind Helper
0.102
20715828PEM_W1-120
Solar/Wind Helper
0.102
214067T20SOLAR
Solar/Wind Helper
0.012
959381AF2-229 GEN
Solar/Wind Helper
0.364
219607WPEMNERT C
Solar/Wind Helper
0.085
219688LUMSOLAR_S C
Solar/Wind Helper
0.042
219272CLEANLIGHT C
Solar/Wind Helper
0.027
219914AD2-027 C
Solar/Wind Helper
0.121
227927V4-067C
Solar/Wind Helper
0.011
228754AB1-001 C
Solar/Wind Helper
0.027
964001AG1-254 GEN
Solar/Wind Helper
1.003
234033AF1-007_GEN
Solar/Wind Helper
7.245
233923SMA
Solar/Wind Helper
0.989
233990AG1-397 GEN
Solar/Wind Helper
0.279
232432Z2-076 GEN
Solar/Wind Helper
0.069
237085AD2-009_GEN
Solar/Wind Helper
1.449
205932AD2-116_GEN
Solar/Wind Helper
0.523
205956AE1-196_GEN
Solar/Wind Helper
0.523
205943AE1-185 GEN
Solar/Wind Helper
0.523
232436AB1-176 C
Solar/Wind Helper
0.046
233935AB2-179 C
Solar/Wind Helper
1.307
960921AF2-383 GEN
Solar/Wind Helper
0.373
971171AH1-044 GEN
Solar/Wind Harmer
3.998
946741AF1-338 GEN
Solar/Wind Helper
0.5
961421AF2-433 GEN
Solar/Wind Helper
0.499
957921AF2-086 GEN
Solar/Wind Helper
0.493
961331AF2-424 GEN
Solar/Wind Helper
0.499
209027LOR2_Q27
Solar/Wind Helper
1.165
963071AG1-156 GEN
Solar/Wind Helper
1.625
963161AG1-165 GEN
Solar/Wind Helper
0.496
316095T157 G97
Solar/Wind Helper
1.154
23583801GRNGAP
Solar/Wind Helper
4.282
961971AG1-040 GEN
Solar/Wind Helper
0.492
203835AF1-098 GEN
Solar/Wind Helper
1.958
20674628WNG_W3-110
Solar/Wind Helper
0.097
207510AF2-138 C
Solar/Wind Helper
0.088
20676728BRNX1-095
Solar/Wind Helper
0.032
217169METRODIV C
Solar/Wind Helper
0.004
217211CAMDEN ST C
Solar/Wind Helper
0.005
20673728F2S_V4-070
Solar/Wind Helper
0.032
219249CENTRALDIV C
Solar/Wind Helper
0.011
219908AB1-139 C
Solar/Wind Helper
0.079
219919AE1-041 FULL
Solar/Wind Helper
0.004
218438BLK ROCK C
Solar/Wind Helper
0.029
219612MATRIX C
Solar/Wind Helper
0.025
20720528MAN_W1-024
Solar/Wind Helper
0.03
20714528FRN_Y2-051
Solar/Wind Helper
0.061
219276PARKLANDSO C
Solar/Wind Helper
0.095
20720828JCB_W4-025
Solar/Wind Helper
0.067
20715028HAN_X4-015
Solar/Wind Helper
0.061
20716028EGP_W2-019
Solar/Wind Helper
0.02
959561AF2-247 GEN
Solar/Wind Helper
0.022
219348LDSOLAR C
Solar/Wind Helper
0.121
219906AC1-017 C
Solar/Wind Helper
0.044
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219291REEVESSOUT C
Solar/Wind Helper
0.012
219912AD2-042 GEN
Solar/Wind Helper
0.158
219766PARADISE C
Solar/Wind Helper
0.057
219623KINSLEYBEA C
Solar/Wind Helper
0.002
228729W2-030 C
Solar/Wind Helper
0.116
230415AB2-049 C
Solar/Wind Helper
0.032
230430AE1-229_GEN
Solar/Wind Helper
3.539
233971AC1-093 C
Solar/Wind Helper
0.369
233996TM1833_GEN
Solar/Wind Helper
0.27
233997TMININ_4.2
Solar/Wind Helper
0.27
233952AC2-187 GEN
Solar/Wind Helper
0.24
232406W1-004 FULL
Solar/Wind Helper
0.523
233940AF2-379 C
Solar/Wind Helper
0.064
234015AF2-250 C
Solar/Wind Helper
0.039
233994AC2-023 GEN
Solar/Wind Helper
0.992
233982AB2-133 GEN
Solar/Wind Helper
0.369
233918AB1-142 GEN
Solar/Wind Helper
0.518
235067AD1-061 GEN
Solar/Wind Helper
0.433
205917AD1-020 ES
Solar/Wind Helper
0.368
238221AF1-254 C O1
Solar/Wind Helper
0.236
237030AB1-096 C
Solar/Wind Helper
0.063
223402AF1-300 C
Solar/Wind Helper
0.338
957471AF2-041 GEN
Solar/Wind Harmer
5.997
959081AF2-199 GEN
Solar/Wind Harmer
1.999
971067AG2-660 GEN
Solar/Wind Harmer
0.666
944201AF1-088_MTX
Adder
163.563
957141AF2-008_MTX
Adder
81.782
CBM West 1LTFEXP_CBM-W1->PJM
CBM
170.264
CBM South 1LTFEXP_CBM-S1->PJM
CBM
48.581
MECLTFEXP_MEC->PJM
CLTF
21.939
SIGELTFEXP_SIGE->PJM
CLTF
0.729
LAGNLTFEXP_LAGN->PJM
CLTF
24.864
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.24
TVALTFEXP_TVA->PJM
CLTF
12.63
CPLELTFEXP_CPLE->PJM
CLTF
6.557
CBM West 2LTFEXP_CBM-W2->PJM
CBM
173.156
NYPJM->LTFIMP_NY
CLTF
6.276
LGEELTFEXP_LGEE->PJM
CLTF
9.844
WECLTFEXP_WEC->PJM
CLTF
5.002
AG2-052LTFEXP_AG2-052->PJM
LTF
0.306
AH1-155LTFEXP_AH1-155->PJM
LTF
0.459

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7445_05MARYSV 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.05 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6243.53
MW Contribution:11.74
Bus #Bus NameTypeMW Contribution
24289405MTG1
50/50
12.693
24722005FLATG5
50/50
3.32
24721905FLATG4
50/50
60.871
24318705GVG2
50/50
13.293
970153AG2-106 GEN
Solar/Wind Harmer
40.072
24686205CER G4
Adder
16.091
24686405CER G5
Adder
16.028
270053AF1-130 C
Solar/Wind Harmer
6.738
970913AG2-568 GEN
Solar/Wind Harmer
13.608
960911AF2-382 GEN
Solar/Wind Harmer
12.052
972103AH1-617 GEN
Solar/Wind Harmer
31.009
971461AH1-227 GEN
Solar/Wind Harmer
7.917
971191AH1-055 GEN
Solar/Wind Harmer
33.8
270346AE1-212 GEN
Solar/Wind Harmer
13.484
943031AE2-326 GEN
Solar/Wind Harmer
5.284
971331AH1-145 GEN
Solar/Wind Harmer
12.895
247619Y1-049
Adder
0.586
958121AF2-106 GEN
Solar/Wind Harmer
6.061
957541AF2-048 GEN
Solar/Wind Harmer
2.113
24721605FLATG1
50/50
3.32
962771AG1-126 GEN
Solar/Wind Harmer
91.898
972203AH1-686 GEN
Adder
4.552
24477305BRIDGE
Adder
0.636
957241AF2-018 GEN
Solar/Wind Harmer
8.055
270399AC1-101 GEN
Solar/Wind Harmer
7.605
270400AC1-102 GEN
Solar/Wind Harmer
7.605
270330AC1-082 GEN2
Solar/Wind Harmer
1.366
270329AC1-082 GEN1
Solar/Wind Harmer
0.805
941621AE2-160 GEN
Adder
5.471
971313AH1-133 GEN
Solar/Wind Harmer
15.802
970281AG2-184 GEN
Solar/Wind Harmer
32.56
972143AH1-644 GEN
Solar/Wind Harmer
15.505
270132AB1-180 C
Adder
0.187
971061AG2-657 GEN
Solar/Wind Harmer
13.568
24734705WLF1G3
Adder
8.349
24734805WLF1G4
Adder
8.349
24734905WLF1G5
Adder
8.349
962211AG1-066 GEN
Solar/Wind Harmer
3.499
966391AG1-508 GEN
Solar/Wind Harmer
4.988
24735105WLF2G1
Adder
8.16
971985AH1-537 GEN
Solar/Wind Harmer
23.222
971981AH1-535 GEN
Solar/Wind Harmer
12.796
270069AE2-166 C O1
Solar/Wind Harmer
3.217
965401AG1-405 GEN
Solar/Wind Harmer
6.573
965411AG1-406 GEN
Solar/Wind Harmer
2.95
339211AE2-254 GEN
Solar/Wind Harmer
1.711
970879AG2-548 GEN
Solar/Wind Harmer
4.825
3429211JKCT 2G
Adder
13.038
970455AG2-298 GEN
Solar/Wind Harmer
6.646
972163AH1-664 GEN
Solar/Wind Harmer
10.872
972165AH1-665 GEN
Solar/Wind Harmer
8.697
270367AC2-061_GEN
Solar/Wind Harmer
3.448
339243AC2-075 GEN1
Solar/Wind Harmer
0.493
25196108MFTGT2
Adder
1.552
25196108MFTGT2
Adder
1.441
944221AF1-090 GEN
Solar/Wind Harmer
10.676
252524AE2-267 GEN
Solar/Wind Harmer
1.53
25196408WSDLE3
Adder
8.556
25196308WSDLE2
Adder
8.482
25196208WSDLE1
Adder
8.46
25196708WSDLE6
Adder
8.439
25196508WSDLE4
Adder
8.227
963841AG1-237 GEN
Solar/Wind Harmer
10.394
274823ROCKFORD ;21
Adder
17.536
274746AC1-111 G10
Adder
4.954
274744AC1-111 GEN8
Adder
4.954
274731ELWOOD EC;2P
Adder
14.499
274733ELWOOD EC;3P
Adder
10.298
23750501ELLIOTTS
Solar/Wind Helper
0.613
254304AE2-114 C
Solar/Wind Helper
0.199
241997AF1-093 GEN
Solar/Wind Helper
0.233
241982AE2-343 S C
Solar/Wind Helper
0.203
243186AF1-051 GEN
50/50
14.281
24723005RIVRG1
Adder
37.861
24723105RIVRG2
Adder
37.861
24685805CER G1
Adder
16.07
24685905CER G2
Adder
16.07
944971AF1-162 GEN
Solar/Wind Harmer
12.689
24728205BUCHG1
Adder
7.204
971225AH1-072 GEN
Solar/Wind Harmer
3.087
971227AH1-073 GEN
Solar/Wind Harmer
3.087
270214AC2-123 GEN
Solar/Wind Harmer
3.357
971277AH1-098 GEN
Solar/Wind Harmer
5.729
270583AD2-179 GEN
Solar/Wind Harmer
13.373
960161AF2-307 GEN
Solar/Wind Harmer
7.621
970239AG2-162 GEN
Solar/Wind Harmer
12.849
966021AG1-471 GEN
Solar/Wind Harmer
6.166
339231AF1-038_GEN
Solar/Wind Harmer
2.069
971485AH1-239 GEN
Solar/Wind Harmer
9.113
970879AG2-548 GEN
Solar/Wind Harmer
6.915
971073AG2-665 GEN
Solar/Wind Harmer
6.915
971073AG2-665 GEN
Solar/Wind Harmer
4.825
942891AE2-308 GEN
Solar/Wind Harmer
11.21
971081AG2-670 GEN
Solar/Wind Harmer
8.401
339236AF1-050_GEN
Solar/Wind Harmer
2.029
339255AE2-071 GEN
Solar/Wind Harmer
1.185
964781AG1-341 GEN
Solar/Wind Harmer
11.836
970653AG2-424 GEN
Solar/Wind Harmer
5.35
970653AG2-424 GEN
Solar/Wind Harmer
1.934
964571AG1-320 GEN
Solar/Wind Harmer
9.018
972043AH1-570 GEN
Solar/Wind Harmer
2.743
972045AH1-571 GEN
Solar/Wind Harmer
2.195
971125AH1-004 GEN
Solar/Wind Harmer
4.377
970107AG2-081 GEN
Solar/Wind Harmer
3.283
270186AC1-089 GEN
Solar/Wind Harmer
6.681
339221AD2-048_GEN
Solar/Wind Harmer
1.68
970235AG2-159 GEN
Solar/Wind Harmer
4.336
970235AG2-159 GEN
Solar/Wind Harmer
2.647
270444AC2-157 GEN1
Solar/Wind Harmer
5.954
962581AG1-107 GEN
Solar/Wind Harmer
5.324
961491AF2-440 GEN
Solar/Wind Harmer
2.213
252509AD1-136 GEN
Solar/Wind Harmer
0.262
945391AF1-204 GEN
Solar/Wind Harmer
13.769
252519AF1-045_GEN
Solar/Wind Harmer
5.968
252516AE2-318_GEN
Solar/Wind Harmer
4.552
25183208HLCRTG
Solar/Wind Harmer
5.931
25194408D.CRK1
Adder
7.379
25194508D.CRK3
Adder
1.38
276916AD2-100_GEN
Solar/Wind Harmer
20.308
276911AD2-131_GEN
Solar/Wind Harmer
4.104
957381AF2-032 GEN
Solar/Wind Harmer
0.403
970241AG2-163 GEN
Solar/Wind Harmer
23.985
276763AC1-053 GEN1
Solar/Wind Harmer
3.755
276764AC1-053 GEN2
Solar/Wind Harmer
3.755
24728805RICHG1
Adder
3.448
24728905RICHG2
Adder
3.448
972267AH1-718 GEN
Adder
3.785
274764LEE CO EC;5U
Adder
8.446
274765LEE CO EC;6U
Adder
8.446
274762LEE CO EC;3U
Adder
8.426
274763LEE CO EC;4U
Adder
8.346
274683WAUKEGAN ;8U
Adder
18.761
274683WAUKEGAN ;8U
Adder
15.814
274696ROCKY RD ;4P
Adder
10.143
274695ROCKY RD ;2P
Adder
9.908
970243AG2-164 GEN
Solar/Wind Harmer
30.166
970519AG2-331 GEN
Solar/Wind Harmer
20.267
970699AG2-449 GEN
Solar/Wind Harmer
13.407
972273AH1-721 GEN
Adder
96.475
270030AE2-140 GEN
Solar/Wind Harmer
23.108
970273AG2-179 GEN
Solar/Wind Harmer
4.447
970093AG2-073 GEN
Solar/Wind Harmer
11.307
966571AG1-526 GEN
Solar/Wind Harmer
25.008
339250AF1-203 GEN
Solar/Wind Harmer
0.677
971155AH1-034 GEN
Solar/Wind Harmer
11.167
962251AG1-071 GEN
Solar/Wind Harmer
6.119
960741AF2-365 GEN
Solar/Wind Harmer
5.543
3429391JKCT 9G
Adder
9.194
972167AH1-666 GEN
Solar/Wind Harmer
8.642
958171AF2-111 GEN
Solar/Wind Harmer
25.894
270291AC1-194 GEN
Solar/Wind Harmer
10.843
25196008MFTGT1
Adder
1.363
970193AG2-126 GEN
Solar/Wind Harmer
14.82
252510AF1-249 C
Solar/Wind Harmer
0.411
270173AC1-122 GEN
Solar/Wind Harmer
1.562
25194608D.CRK4
Adder
1.604
25196608WSDLE5
Adder
8.312
942481AE2-261 GEN
Solar/Wind Harmer
28.829
24728705AND G3
Adder
7.718
24728505AND G1
Adder
3.69
962751AG1-124 GEN
Solar/Wind Harmer
8.642
276621W2-048 GEN
Solar/Wind Harmer
5.949
276838X2-022 GEN2
Solar/Wind Harmer
0.222
274760LEE CO EC;1U
Adder
8.426
274767LEE CO EC;8U
Adder
8.327
972236AH1-702 GEN2
Adder
1.974
274682WAUKEGAN ;7U
Adder
15.992
274729ELWOOD EC;1P
Adder
14.499
237048AF1-022 C
Solar/Wind Helper
0.178
235058AG1-386 C
Solar/Wind Helper
0.421
237043AE2-125 C
Solar/Wind Helper
0.164
254305AE2-115 C
Solar/Wind Helper
0.199
202652Y1-033 WT C
Solar/Wind Helper
0.509
23750701CROSSCHOOL
Solar/Wind Helper
1.078
20089126CSLMN_L13
Solar/Wind Helper
0.533
20089026BF_G21_K23
Solar/Wind Helper
0.422
964991AG1-363 GEN
Solar/Wind Helper
3.317
24289405MTG1
50/50
12.693
24721805FLATG3
50/50
3.32
24721705FLATG2
50/50
60.871
243186AF1-051 GEN
50/50
14.281
24318705GVG2
50/50
13.293
962761AG1-125 GEN
Solar/Wind Harmer
91.898
970149AG2-104 GEN
Solar/Wind Harmer
113.494
970155AG2-107 GEN
Solar/Wind Harmer
40.072
24723205RIVRG3
Adder
37.861
24686105CER G3
Adder
16.176
24686505CER G6
Adder
16.155
971403AH1-188 GEN
Solar/Wind Harmer
25.361
270331AC1-082 GEN3
Solar/Wind Harmer
0.807
970947AG2-589 GEN
Solar/Wind Harmer
3.533
960001AF2-291 GEN
Solar/Wind Harmer
5.186
24728305BUCHG2
Adder
7.204
971687AH1-348 GEN
Solar/Wind Harmer
1.543
971315AH1-136 GEN
Solar/Wind Harmer
3.067
24735205WLF2G2
Adder
8.16
971329AH1-144 GEN
Solar/Wind Harmer
16.634
927014AC1-188 GEN
Solar/Wind Harmer
2.118
270336AE1-100 GEN
Solar/Wind Harmer
2.043
970091AG2-072 GEN
Adder
90.557
970333AG2-219 GEN
Solar/Wind Harmer
36.87
971367AH1-164 GEN
Solar/Wind Harmer
3.994
970273AG2-179 GEN
Solar/Wind Harmer
2.784
971821AH1-427 GEN
Solar/Wind Harmer
11.315
943811AF1-049 GEN
Solar/Wind Harmer
4.273
339241AF1-083 GEN
Solar/Wind Harmer
1.864
964901AG1-354 GEN
Solar/Wind Harmer
16.766
3429241JKCT 3G
Adder
13.209
962241AG1-070 GEN
Solar/Wind Harmer
5.006
971565AH1-281 GEN
Solar/Wind Harmer
2.213
3429421JKCT 10G
Adder
9.194
943111AE2-339 GEN
Solar/Wind Harmer
0.969
339216AC1-074 GEN
Solar/Wind Harmer
1.819
945681AF1-233 GEN
Solar/Wind Harmer
20.401
270445AC2-157 GEN2
Solar/Wind Harmer
5.954
270018AE2-047 C O1
Solar/Wind Harmer
1.277
252507AC2-088 GEN
Solar/Wind Harmer
1.836
25196008MFTGT1
Adder
1.408
25196808ZIMRHP
Adder
76.262
25194608D.CRK4
Adder
1.604
965911AG1-460 GEN
Solar/Wind Harmer
1.345
24728605AND G2
Adder
3.69
963741AG1-226 GEN
Solar/Wind Harmer
43.173
276615X2-022 GEN
Solar/Wind Harmer
1.868
274761LEE CO EC;2U
Adder
8.426
274766LEE CO EC;7U
Adder
8.327
972235AH1-702 GEN1
Adder
2.27
274822ROCKFORD ;11
Adder
17.664
274828WAUKEGAN ;BP
Adder
9.834
274682WAUKEGAN ;7U
Adder
15.992
274745AC1-111 GEN9
Adder
4.954
237046AF1-021 C
Solar/Wind Helper
0.454
254303AC2-168 GEN
Solar/Wind Helper
0.144
241966AE1-183 GEN
Solar/Wind Helper
0.233
238185AF2-356 C
Solar/Wind Helper
1.986
23751201ROTHROCK
Solar/Wind Helper
0.666
235054AD2-180 GEN
Solar/Wind Helper
1.542
23562501BACKB
Solar/Wind Helper
0.81
20089226LOOKOUT
Solar/Wind Helper
0.519
963831AG1-236 GEN
Solar/Wind Harmer
2.691
274693ROCKY RD ;1P
Adder
9.811
274697ROCKY RD ;3P
Adder
2.692
23652301WDPWR_K20
Solar/Wind Helper
0.133
962101AG1-054 GEN
Solar/Wind Helper
0.594
241967AE2-285_GEN
Solar/Wind Helper
0.583
241801AE1-079 GEN
Solar/Wind Helper
0.227
241985AE1-237 GEN
Solar/Wind Helper
0.227
23585401KL_K28_T16
Solar/Wind Helper
1.167
203955AF1-039 C O1
Solar/Wind Helper
0.335
944781AF1-143 GEN
Solar/Wind Helper
2.213
944201AF1-088_MTX
Adder
123.966
957141AF2-008_MTX
Adder
61.983
CBM West 1LTFEXP_CBM-W1->PJM
CBM
111.704
CBM South 1LTFEXP_CBM-S1->PJM
CBM
41.73
MECLTFEXP_MEC->PJM
CLTF
16.018
SIGELTFEXP_SIGE->PJM
CLTF
0.557
LAGNLTFEXP_LAGN->PJM
CLTF
21.271
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.975
TVALTFEXP_TVA->PJM
CLTF
11.116
CPLELTFEXP_CPLE->PJM
CLTF
7.658
CBM West 2LTFEXP_CBM-W2->PJM
CBM
139.058
NYPJM->LTFIMP_NY
CLTF
4.768
LGEELTFEXP_LGEE->PJM
CLTF
7.621
WECLTFEXP_WEC->PJM
CLTF
3.448
AG2-052LTFEXP_AG2-052->PJM
LTF
0.206
AH1-155LTFEXP_AH1-155->PJM
LTF
0.308

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P4_#17219_05GUERNSEY 765_A_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#17219_05GUERNSEY 765_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.12 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6192.17
MW Contribution:15.46
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
2.772
972203AH1-686 GEN
Adder
4.457
270330AC1-082 GEN2
Solar/Wind Harmer
1.373
270329AC1-082 GEN1
Solar/Wind Harmer
0.808
957241AF2-018 GEN
Solar/Wind Harmer
7.79
270399AC1-101 GEN
Solar/Wind Harmer
7.37
270400AC1-102 GEN
Solar/Wind Harmer
7.37
962771AG1-126 GEN
Solar/Wind Harmer
55.23
24477305BRIDGE
Adder
0.593
970281AG2-184 GEN
Solar/Wind Harmer
33.155
972143AH1-644 GEN
Solar/Wind Harmer
15.788
971985AH1-537 GEN
Solar/Wind Harmer
28.159
941621AE2-160 GEN
Adder
5.103
962211AG1-066 GEN
Solar/Wind Harmer
3.699
971313AH1-133 GEN
Solar/Wind Harmer
15.015
270367AC2-061_GEN
Solar/Wind Harmer
4.764
970879AG2-548 GEN
Solar/Wind Harmer
6.355
972163AH1-664 GEN
Solar/Wind Harmer
14.744
972165AH1-665 GEN
Solar/Wind Harmer
11.796
339243AC2-075 GEN1
Solar/Wind Harmer
0.66
25196108MFTGT2
Adder
2.214
25196108MFTGT2
Adder
2.056
3429211JKCT 2G
Adder
16.839
252524AE2-267 GEN
Solar/Wind Harmer
2.271
25196408WSDLE3
Adder
12.703
25196308WSDLE2
Adder
12.592
25196208WSDLE1
Adder
12.561
25196708WSDLE6
Adder
12.529
25196508WSDLE4
Adder
12.214
24734705WLF1G3
Adder
8.278
24734805WLF1G4
Adder
8.278
24734905WLF1G5
Adder
8.278
270340AC2-060 GEN
Solar/Wind Harmer
4.33
270132AB1-180 C
Adder
0.172
339211AE2-254 GEN
Solar/Wind Harmer
2.15
24735105WLF2G1
Adder
8.161
970455AG2-298 GEN
Solar/Wind Harmer
8.463
965401AG1-405 GEN
Solar/Wind Harmer
7.994
965411AG1-406 GEN
Solar/Wind Harmer
3.588
944031AF1-071 GEN
Solar/Wind Harmer
1.405
270269AC2-059
Solar/Wind Harmer
12.998
971061AG2-657 GEN
Solar/Wind Harmer
12.476
270240V3-007_GEN2
Solar/Wind Harmer
8.534
253372AE2-315 SEC3
Adder
2.611
253372AE2-315 SEC3
Adder
2.611
25306009OHH W.
Adder
3.967
24725505WLD G2 C
Solar/Wind Harmer
5.459
24699105WLD G1 C
Solar/Wind Harmer
5.394
253349AC2-067 GEN
Solar/Wind Harmer
6.826
253400AC2-068 GEN
Solar/Wind Harmer
2.745
965461AG1-414 GEN
Solar/Wind Harmer
3.101
24289405MTG1
50/50
11.412
24318705GVG2
50/50
11.681
24722005FLATG5
50/50
2.772
24721905FLATG4
50/50
50.82
24686205CER G4
Adder
15.663
24686405CER G5
Adder
15.601
270053AF1-130 C
Solar/Wind Harmer
6.517
970153AG2-106 GEN
Solar/Wind Harmer
24.083
971191AH1-055 GEN
Solar/Wind Harmer
37.171
957541AF2-048 GEN
Solar/Wind Harmer
2.51
970913AG2-568 GEN
Solar/Wind Harmer
12.681
972103AH1-617 GEN
Solar/Wind Harmer
31.576
960911AF2-382 GEN
Solar/Wind Harmer
11.622
971461AH1-227 GEN
Solar/Wind Harmer
7.904
970243AG2-164 GEN
Solar/Wind Harmer
38.654
970519AG2-331 GEN
Solar/Wind Harmer
25.969
970699AG2-449 GEN
Solar/Wind Harmer
17.18
972167AH1-666 GEN
Solar/Wind Harmer
11.786
958171AF2-111 GEN
Solar/Wind Harmer
36.367
252510AF1-249 C
Solar/Wind Harmer
0.604
25196008MFTGT1
Adder
1.945
25194608D.CRK4
Adder
2.371
25196608WSDLE5
Adder
12.34
3429391JKCT 9G
Adder
11.981
970093AG2-073 GEN
Solar/Wind Harmer
14.372
253316AC1-085 GEN3
Solar/Wind Harmer
12.008
253433AC1-085 GEN1
Solar/Wind Harmer
7.622
946181AF1-283 GEN
Solar/Wind Harmer
18.636
253406AD2-031_GEN
Solar/Wind Harmer
1.826
966571AG1-526 GEN
Solar/Wind Harmer
31.649
270291AC1-194 GEN
Solar/Wind Harmer
15.077
253415AE1-040 GEN
Solar/Wind Harmer
1.598
972173AH1-669 GEN
Solar/Wind Harmer
7.011
270222AC2-111 GEN
Solar/Wind Harmer
11.397
270273AD2-016 GEN
Solar/Wind Harmer
3.717
972273AH1-721 GEN
Adder
115.895
270356AE2-297 GEN
Solar/Wind Harmer
6.354
24728705AND G3
Adder
11.134
24728505AND G1
Adder
5.324
970193AG2-126 GEN
Solar/Wind Harmer
20.711
270437AC2-090 C
Solar/Wind Harmer
7.702
253303V4-073 C
Solar/Wind Harmer
0.16
253370AE2-315 SEC1
Adder
2.761
253371AE2-315 SEC2
Adder
2.611
270346AE1-212 GEN
Solar/Wind Harmer
12.393
970273AG2-179 GEN
Solar/Wind Harmer
5.36
960741AF2-365 GEN
Solar/Wind Harmer
6.85
247642Z2-115 C
Solar/Wind Harmer
0.088
970289AG2-191 GEN
Solar/Wind Harmer
1.05
970291AG2-192 GEN
Solar/Wind Harmer
0.954
958821AF2-173 GEN
Solar/Wind Harmer
19.143
270004AE1-209 GEN
Solar/Wind Harmer
7.473
274772LINCOLN ;3U
Adder
11.173
274760LEE CO EC;1U
Adder
12.305
274767LEE CO EC;8U
Adder
12.16
274729ELWOOD EC;1P
Adder
21.74
237048AF1-022 C
Solar/Wind Helper
0.225
237043AE2-125 C
Solar/Wind Helper
0.205
235058AG1-386 C
Solar/Wind Helper
0.508
964991AG1-363 GEN
Solar/Wind Helper
4.361
23750701CROSSCHOOL
Solar/Wind Helper
1.41
238118U2-030_1
Solar/Wind Helper
0.339
202652Y1-033 WT C
Solar/Wind Helper
0.647
20089126CSLMN_L13
Solar/Wind Helper
0.675
20089026BF_G21_K23
Solar/Wind Helper
0.534
24289405MTG1
50/50
11.412
243186AF1-051 GEN
50/50
12.549
24318705GVG2
50/50
11.681
24721805FLATG3
50/50
2.772
24721705FLATG2
50/50
50.82
24723205RIVRG3
Adder
36.284
24686105CER G3
Adder
15.746
24686505CER G6
Adder
15.725
270331AC1-082 GEN3
Solar/Wind Harmer
0.811
970947AG2-589 GEN
Solar/Wind Harmer
3.567
960001AF2-291 GEN
Solar/Wind Harmer
5.284
971403AH1-188 GEN
Solar/Wind Harmer
24.255
962761AG1-125 GEN
Solar/Wind Harmer
55.23
970149AG2-104 GEN
Solar/Wind Harmer
68.21
970155AG2-107 GEN
Solar/Wind Harmer
24.083
971315AH1-136 GEN
Solar/Wind Harmer
3.227
927014AC1-188 GEN
Solar/Wind Harmer
2.517
971687AH1-348 GEN
Solar/Wind Harmer
1.543
24728305BUCHG2
Adder
6.894
970333AG2-219 GEN
Solar/Wind Harmer
47.244
970091AG2-072 GEN
Adder
114.655
945681AF1-233 GEN
Solar/Wind Harmer
27.78
252507AC2-088 GEN
Solar/Wind Harmer
2.628
25196808ZIMRHP
Adder
110.178
339216AC1-074 GEN
Solar/Wind Harmer
2.436
25196008MFTGT1
Adder
2.009
943111AE2-339 GEN
Solar/Wind Harmer
1.275
25194608D.CRK4
Adder
2.371
3429241JKCT 3G
Adder
17.06
3429421JKCT 10G
Adder
11.981
253432AC1-085 GEN2
Solar/Wind Harmer
0.384
946171AF1-282 GEN
Solar/Wind Harmer
14.335
270263AC1-001 GEN
Solar/Wind Harmer
1.49
270445AC2-157 GEN2
Solar/Wind Harmer
7.934
971565AH1-281 GEN
Solar/Wind Harmer
2.835
971821AH1-427 GEN
Solar/Wind Harmer
14.167
24735205WLF2G2
Adder
8.161
24728605AND G2
Adder
5.324
339241AF1-083 GEN
Solar/Wind Harmer
2.303
942081AE2-220 GEN
Solar/Wind Harmer
8.819
270239V3-007_GEN1
Solar/Wind Harmer
2.374
253370AE2-315 SEC1
Adder
2.761
253371AE2-315 SEC2
Adder
2.611
970273AG2-179 GEN
Solar/Wind Harmer
3.356
276903AD2-071 C
Solar/Wind Harmer
13.713
963741AG1-226 GEN
Solar/Wind Harmer
61.637
970291AG2-192 GEN
Solar/Wind Harmer
1.778
270005AE1-210 C O1
Solar/Wind Harmer
7.473
965031AG1-367 GEN
Solar/Wind Harmer
13.674
270032AE2-172
Solar/Wind Harmer
6.358
25326309TAIT D
Adder
1.497
964901AG1-354 GEN
Solar/Wind Harmer
20.475
960071AF2-298 GEN
Solar/Wind Harmer
6.807
274773LINCOLN ;4U
Adder
11.173
274774LINCOLN ;5U
Adder
11.173
274745AC1-111 GEN9
Adder
7.394
274761LEE CO EC;2U
Adder
12.305
274766LEE CO EC;7U
Adder
12.16
237046AF1-021 C
Solar/Wind Helper
0.57
238185AF2-356 C
Solar/Wind Helper
2.581
23751201ROTHROCK
Solar/Wind Helper
0.868
235054AD2-180 GEN
Solar/Wind Helper
2.007
23562501BACKB
Solar/Wind Helper
1.057
238117U2-030
Solar/Wind Helper
0.339
235531U2-073 GEN
Solar/Wind Helper
3.19
20089226LOOKOUT
Solar/Wind Helper
0.657
254303AC2-168 GEN
Solar/Wind Helper
0.171
241966AE1-183 GEN
Solar/Wind Helper
0.277
23751101LEADS_P59
Solar/Wind Helper
1.464
20088826HIGHLAND
Solar/Wind Helper
0.998
20094526CT_V3-030
Solar/Wind Helper
0.523
964201AG1-281 GEN
Solar/Wind Helper
0.537
238108AE1-109 GEN1
Solar/Wind Helper
0.101
964391AG1-301 GEN
Solar/Wind Helper
0.522
203954AE2-126 C
Solar/Wind Helper
0.514
238206AE2-263_GEN
Solar/Wind Helper
0.997
959471AF2-238 GEN
Solar/Wind Helper
0.51
203860AG1-193 C
Solar/Wind Helper
0.25
209067AE2-060 GEN
Solar/Wind Helper
0.09
946691AF1-333 GEN
Solar/Wind Helper
0.493
946741AF1-338 GEN
Solar/Wind Helper
0.493
961421AF2-433 GEN
Solar/Wind Helper
0.491
957921AF2-086 GEN
Solar/Wind Helper
0.486
961331AF2-424 GEN
Solar/Wind Helper
0.491
209027LOR2_Q27
Solar/Wind Helper
1.148
963071AG1-156 GEN
Solar/Wind Helper
1.601
963161AG1-165 GEN
Solar/Wind Helper
0.489
316095T157 G97
Solar/Wind Helper
1.137
23583801GRNGAP
Solar/Wind Helper
4.22
961971AG1-040 GEN
Solar/Wind Helper
0.485
203835AF1-098 GEN
Solar/Wind Helper
1.929
20674628WNG_W3-110
Solar/Wind Helper
0.096
207510AF2-138 C
Solar/Wind Helper
0.087
20676728BRNX1-095
Solar/Wind Helper
0.032
217169METRODIV C
Solar/Wind Helper
0.004
217211CAMDEN ST C
Solar/Wind Helper
0.005
20673728F2S_V4-070
Solar/Wind Helper
0.032
219249CENTRALDIV C
Solar/Wind Helper
0.011
219908AB1-139 C
Solar/Wind Helper
0.078
219919AE1-041 FULL
Solar/Wind Helper
0.004
219612MATRIX C
Solar/Wind Helper
0.025
218438BLK ROCK C
Solar/Wind Helper
0.029
20720528MAN_W1-024
Solar/Wind Helper
0.03
20714528FRN_Y2-051
Solar/Wind Helper
0.06
219276PARKLANDSO C
Solar/Wind Helper
0.094
20720828JCB_W4-025
Solar/Wind Helper
0.066
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.06
959561AF2-247 GEN
Solar/Wind Helper
0.022
219348LDSOLAR C
Solar/Wind Helper
0.119
219906AC1-017 C
Solar/Wind Helper
0.043
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219291REEVESSOUT C
Solar/Wind Helper
0.012
219912AD2-042 GEN
Solar/Wind Helper
0.155
219766PARADISE C
Solar/Wind Helper
0.057
219623KINSLEYBEA C
Solar/Wind Helper
0.002
228729W2-030 C
Solar/Wind Helper
0.114
230415AB2-049 C
Solar/Wind Helper
0.031
230430AE1-229_GEN
Solar/Wind Helper
3.487
233971AC1-093 C
Solar/Wind Helper
0.364
233952AC2-187 GEN
Solar/Wind Helper
0.236
233994AC2-023 GEN
Solar/Wind Helper
0.977
233996TM1833_GEN
Solar/Wind Helper
0.266
233997TMININ_4.2
Solar/Wind Helper
0.266
232406W1-004 FULL
Solar/Wind Helper
0.516
233940AF2-379 C
Solar/Wind Helper
0.063
234015AF2-250 C
Solar/Wind Helper
0.039
233982AB2-133 GEN
Solar/Wind Helper
0.363
233918AB1-142 GEN
Solar/Wind Helper
0.51
243186AF1-051 GEN
50/50
12.549
24723005RIVRG1
Adder
36.284
24723105RIVRG2
Adder
36.284
24685805CER G1
Adder
15.642
24685905CER G2
Adder
15.642
944971AF1-162 GEN
Solar/Wind Harmer
12.272
971225AH1-072 GEN
Solar/Wind Harmer
3.081
971227AH1-073 GEN
Solar/Wind Harmer
3.081
24728205BUCHG1
Adder
6.894
970239AG2-162 GEN
Solar/Wind Harmer
16.464
270186AC1-089 GEN
Solar/Wind Harmer
9.145
962581AG1-107 GEN
Solar/Wind Harmer
7.495
961491AF2-440 GEN
Solar/Wind Harmer
3.115
960161AF2-307 GEN
Solar/Wind Harmer
9.531
970879AG2-548 GEN
Solar/Wind Harmer
9.109
971073AG2-665 GEN
Solar/Wind Harmer
9.109
971073AG2-665 GEN
Solar/Wind Harmer
6.355
252509AD1-136 GEN
Solar/Wind Harmer
0.375
339221AD2-048_GEN
Solar/Wind Harmer
2.24
972043AH1-570 GEN
Solar/Wind Harmer
3.637
972045AH1-571 GEN
Solar/Wind Harmer
2.91
25183208HLCRTG
Solar/Wind Harmer
8.794
252519AF1-045_GEN
Solar/Wind Harmer
8.799
252516AE2-318_GEN
Solar/Wind Harmer
6.712
970235AG2-159 GEN
Solar/Wind Harmer
5.797
970235AG2-159 GEN
Solar/Wind Harmer
3.539
971125AH1-004 GEN
Solar/Wind Harmer
5.778
970107AG2-081 GEN
Solar/Wind Harmer
4.333
25194408D.CRK1
Adder
10.905
25194508D.CRK3
Adder
2.039
942891AE2-308 GEN
Solar/Wind Harmer
14.408
253317AC1-085 GEN4
Solar/Wind Harmer
12.008
270444AC2-157 GEN1
Solar/Wind Harmer
7.934
253394AE2-221_GEN
Solar/Wind Harmer
6.433
253398AE2-221_GEN2
Solar/Wind Harmer
6.433
964571AG1-320 GEN
Solar/Wind Harmer
11.509
970653AG2-424 GEN
Solar/Wind Harmer
6.739
970653AG2-424 GEN
Solar/Wind Harmer
2.436
24728805RICHG1
Adder
5.257
24728905RICHG2
Adder
5.257
971081AG2-670 GEN
Solar/Wind Harmer
10.358
945391AF1-204 GEN
Solar/Wind Harmer
19.242
24379505HDWTR1G C
Solar/Wind Harmer
10.908
270209AC1-174_GEN
Solar/Wind Harmer
7.698
926881AC1-175 GEN
Solar/Wind Harmer
7.698
253370AE2-315 SEC1
Adder
2.761
339231AF1-038_GEN
Solar/Wind Harmer
2.495
270383AD1-128 GEN
Solar/Wind Harmer
8.387
339236AF1-050_GEN
Solar/Wind Harmer
2.488
970241AG2-163 GEN
Solar/Wind Harmer
34.243
25322209TAIT E
Adder
13.324
25322209TAIT E
Adder
13.025
25326109MON D
Adder
1.782
247621Y3-024
Adder
0.324
274770LINCOLN ;1U
Adder
11.173
274771LINCOLN ;2U
Adder
11.173
972259AH1-714 GEN
Adder
25.243
972267AH1-718 GEN
Adder
5.508
274696ROCKY RD ;4P
Adder
15.074
274695ROCKY RD ;2P
Adder
14.726
274693ROCKY RD ;1P
Adder
14.581
274697ROCKY RD ;3P
Adder
4
274764LEE CO EC;5U
Adder
12.334
274765LEE CO EC;6U
Adder
12.334
274762LEE CO EC;3U
Adder
12.305
274763LEE CO EC;4U
Adder
12.189
23652301WDPWR_K20
Solar/Wind Helper
0.166
23585401KL_K28_T16
Solar/Wind Helper
1.512
203955AF1-039 C O1
Solar/Wind Helper
0.427
944781AF1-143 GEN
Solar/Wind Helper
2.801
238120AE2-309 GEN
Solar/Wind Helper
0.501
962101AG1-054 GEN
Solar/Wind Helper
0.706
20083426SW_E13_K22
Solar/Wind Helper
0.063
241985AE1-237 GEN
Solar/Wind Helper
0.267
241967AE2-285_GEN
Solar/Wind Helper
0.687
241801AE1-079 GEN
Solar/Wind Helper
0.267
20088926STNY CRK
Solar/Wind Helper
0.916
946071AF1-272 GEN
Solar/Wind Helper
3.012
20084626FORWARD
Solar/Wind Helper
0.397
203940AF1-140 C
Solar/Wind Helper
0.44
20088626ARWF_N39
Solar/Wind Helper
1.344
20303426NA_O38_P22
Solar/Wind Helper
1.102
203853AF1-134 C O1
Solar/Wind Helper
0.526
946381AF1-302 GEN
Solar/Wind Helper
0.243
203952AE2-129 C
Solar/Wind Helper
0.521
203946AE2-131 C
Solar/Wind Helper
0.522
238217AF1-153 C O1
Solar/Wind Helper
0.259
20398826ARMNA MT
Solar/Wind Helper
1.633
209137AF2-361 C
Solar/Wind Helper
1.509
946751AF1-339 GEN
Solar/Wind Helper
0.493
209054AE2-059 GEN
Solar/Wind Helper
0.089
961431AF2-434 GEN
Solar/Wind Helper
0.491
208972BECR K09
Solar/Wind Helper
0.367
209029WAYMART-WD
Solar/Wind Helper
0.923
203979AG1-198 GEN
Solar/Wind Helper
0.292
211065PSPA IPP
Solar/Wind Helper
0.165
211065PSPA IPP
Solar/Wind Helper
0.165
238127S14_GEN_2
Solar/Wind Helper
0.8
254305AE2-115 C
Solar/Wind Helper
0.235
203818AF1-086 GEN
Solar/Wind Helper
1.862
203854AF2-039 C
Solar/Wind Helper
0.349
20334926Z1-069 C
Solar/Wind Helper
1.47
238202AE2-262_GEN
Solar/Wind Helper
1.048
941421AE2-139 GEN
Solar/Wind Helper
2.537
959441AF2-235 GEN
Solar/Wind Helper
0.252
200917MEHOOPANY_G
Solar/Wind Helper
2.394
209071AE2-133 GEN
Solar/Wind Helper
0.089
946731AF1-337 GEN
Solar/Wind Helper
0.493
212507AE2-042_GEN
Solar/Wind Helper
1.746
961341AF2-425 GEN
Solar/Wind Helper
0.491
212266LOR1
Solar/Wind Helper
0.053
961301AF2-421 GEN
Solar/Wind Helper
0.489
963151AG1-164 GEN
Solar/Wind Helper
0.489
316097T157 G90
Solar/Wind Helper
1.137
203830AF1-094 GEN
Solar/Wind Helper
0.488
20671928W4-073
Solar/Wind Helper
0.097
207518AF1-320_GEN
Solar/Wind Helper
1.692
207437AD2-070 GEN
Solar/Wind Helper
0.148
20675828AU_W4-064
Solar/Wind Helper
0.032
207439AE1-081 C O1
Solar/Wind Helper
0.02
20674328GAR_V4-001
Solar/Wind Helper
0.024
217208PARK ELE C
Solar/Wind Helper
0.005
217209CENTRL HS C
Solar/Wind Helper
0.009
20676428JCR_X2-075
Solar/Wind Helper
0.072
207528AF2-192 GEN
Solar/Wind Helper
0.081
20673628F1S_V4-069
Solar/Wind Helper
0.032
20675428EAM_W2-061
Solar/Wind Helper
0.017
962511AG1-100 GEN
Solar/Wind Helper
0.481
217213AMBOY SO C
Solar/Wind Helper
0.03
218428ETC SOLAR C
Solar/Wind Helper
0.005
205941AD2-115 GEN
Solar/Wind Helper
0.524
20742028HF_AC1-207
Solar/Wind Helper
0.148
20715228NPK_W1-113
Solar/Wind Helper
0.082
207454AA2-184 E
Solar/Wind Helper
0.327
219680HOPEWELLV C1
Solar/Wind Helper
0.003
963711AG1-223 GEN
Solar/Wind Helper
0.067
20714828MDF_W3-079
Solar/Wind Helper
0.137
207445AB1-138_GEN
Solar/Wind Helper
0.109
20720728JCB_W1-129
Solar/Wind Helper
0.06
219304NAMERICA C
Solar/Wind Helper
0.137
219686LUMSOLAR_N C
Solar/Wind Helper
0.041
219907AC1-030 C
Solar/Wind Helper
0.035
218660EHAMPSOLAR C
Solar/Wind Helper
0.034
219904AC1-010 C
Solar/Wind Helper
0.063
219258KINSLEYDEP C
Solar/Wind Helper
0.079
228728W1-130C
Solar/Wind Helper
0.056
230434AG1-499 GEN
Solar/Wind Helper
0.238
230511AF1-262
Solar/Wind Helper
0.015
233972AC1-094 C
Solar/Wind Helper
0.308
233954AC2-188 GEN
Solar/Wind Helper
0.236
233950AC2-186 GEN
Solar/Wind Helper
0.118
233998TM1NIN_3.36
Solar/Wind Helper
0.266
232404W1-003 C
Solar/Wind Helper
0.516
232428Y3-058 C
Solar/Wind Helper
0.344
232434Z2-077 GEN
Solar/Wind Helper
0.129
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
232422X3-066 FULL
Solar/Wind Helper
0.116
233930AB2-032 GEN
Solar/Wind Helper
0.387
233915AB1-141 GEN
Solar/Wind Helper
0.51
966131AG1-482 GEN
Solar/Wind Helper
0.077
235062AE1-101 C1
Solar/Wind Helper
1.441
237038AE2-054 C
Solar/Wind Helper
0.234
237080AD1-060 GEN
Solar/Wind Helper
0.292
23779801AA1-109
Solar/Wind Helper
0.165
223401AF1-299 GEN
Solar/Wind Helper
0.332
203980AG1-197 GEN
Solar/Wind Helper
0.363
966111AG1-480 GEN
Solar/Wind Helper
0.048
20674128FR_U2-059
Solar/Wind Helper
0.004
964851AG1-348 GEN
Solar/Wind Helper
0.087
20676228FRD_X1-012
Solar/Wind Helper
0.099
207471AF2-354 C
Solar/Wind Helper
0.181
20674928WA_W3-044
Solar/Wind Helper
0.106
217204WCALDSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217081WEATEXAS C
Solar/Wind Helper
0.013
20671828STAW2-080
Solar/Wind Helper
0.028
207442AE1-156 GEN
Solar/Wind Helper
0.346
20676128MHD_W3-029
Solar/Wind Helper
0.102
20673828FLE_V3-070
Solar/Wind Helper
0.096
218440SUMMTASSOC C
Solar/Wind Helper
0.017
20716928W4-060COL
Solar/Wind Helper
0.054
20720628TIN_W1-124
Solar/Wind Helper
0.2
20714928UPF_X1-085
Solar/Wind Helper
0.005
963391AG1-188 GEN
Solar/Wind Helper
0.086
963401AG1-189 GEN
Solar/Wind Helper
0.059
20390526W1-045 C
Solar/Wind Helper
0.351
219615MILLCREEK C
Solar/Wind Helper
0.028
219921AF1-264
Solar/Wind Helper
0.053
203947AF1-006 C
Solar/Wind Helper
0.519
230407AD2-065 C
Solar/Wind Helper
0.042
230433AD2-135 GEN
Solar/Wind Helper
0.018
233939AC1-091 C
Solar/Wind Helper
0.356
233970AC1-092 C
Solar/Wind Helper
0.356
233901CHERRYDALE C
Solar/Wind Helper
0.236
232408W1-005 C
Solar/Wind Helper
0.516
232410W1-006 C
Solar/Wind Helper
0.516
233946AB2-136 GEN
Solar/Wind Helper
0.577
234036AF2-325 C
Solar/Wind Helper
0.043
233987AB2-037 GEN
Solar/Wind Helper
2.379
232424Y1-079 C
Solar/Wind Helper
0.118
233944AB2-135 GEN
Solar/Wind Helper
0.598
233933AB2-153 GEN
Solar/Wind Helper
0.236
235063AE1-101 C2
Solar/Wind Helper
1.441
205916AD1-020 GEN
Solar/Wind Helper
1.685
237002AB1-128_GEN
Solar/Wind Helper
0.382
237001AB1-127_GEN
Solar/Wind Helper
0.382
235020AA1-095 C
Solar/Wind Helper
0.044
23777901MDS_W4-102
Solar/Wind Helper
0.148
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
237034AC2-136 C
Solar/Wind Helper
0.191
238175AF1-290_GEN
Solar/Wind Helper
0.121
237025AB1-124 C
Solar/Wind Helper
0.143
237006AB1-125 GEN
Solar/Wind Helper
0.107
23777801MSM_W1-116
Solar/Wind Helper
0.098
238169AE2-226 GEN1
Solar/Wind Helper
0.546
238170AE2-226 GEN2
Solar/Wind Helper
0.546
970825AG2-519 GEN
Solar/Wind Harmer
8.555
235067AD1-061 GEN
Solar/Wind Helper
0.427
205917AD1-020 ES
Solar/Wind Helper
0.362
238221AF1-254 C O1
Solar/Wind Helper
0.232
237030AB1-096 C
Solar/Wind Helper
0.062
223402AF1-300 C
Solar/Wind Helper
0.332
970825AG2-519 GEN
Solar/Wind Harmer
1.909
970289AG2-191 GEN
Solar/Wind Harmer
2.598
270594AE1-207 GEN
Solar/Wind Harmer
20.092
963841AG1-237 GEN
Solar/Wind Harmer
14.936
24729505KEY G4
Adder
8.677
274775LINCOLN ;6U
Adder
11.173
274776LINCOLN ;7U
Adder
11.173
274777LINCOLN ;8U
Adder
11.173
274746AC1-111 G10
Adder
7.394
274744AC1-111 GEN8
Adder
7.394
274731ELWOOD EC;2P
Adder
21.74
274733ELWOOD EC;3P
Adder
13.586
23750501ELLIOTTS
Solar/Wind Helper
0.779
238126S14_GEN_1
Solar/Wind Helper
0.8
254304AE2-114 C
Solar/Wind Helper
0.235
241997AF1-093 GEN
Solar/Wind Helper
0.277
241982AE2-343 S C
Solar/Wind Helper
0.24
20092526R32
Solar/Wind Helper
1.294
203961AE2-224 GEN
Solar/Wind Helper
2.672
20091526CHSTN_FL
Solar/Wind Helper
0.646
238109AE1-109 GEN2
Solar/Wind Helper
0.101
238110AE1-109 GEN3
Solar/Wind Helper
0.101
20090526Q36
Solar/Wind Helper
1.152
203993AD2-133_GEN1
Solar/Wind Helper
1.152
941231AE2-117 GEN
Solar/Wind Helper
0.523
203846AF2-130 C
Solar/Wind Helper
0.491
203855AF2-088 C
Solar/Wind Helper
0.168
203804AE2-113_GEN
Solar/Wind Helper
1.898
959431AF2-234 GEN
Solar/Wind Helper
0.986
964051AG1-259 GEN
Solar/Wind Helper
0.074
964061AG1-260 GEN
Solar/Wind Helper
0.074
959421AF2-233 GEN
Solar/Wind Helper
0.493
961261AF2-417 GEN
Solar/Wind Helper
0.488
209116AE2-175 GEN
Solar/Wind Helper
1.938
20675128HRM_W1-127
Solar/Wind Helper
0.032
207408W3-077 C
Solar/Wind Helper
0.09
20675728RH_W2-091
Solar/Wind Helper
0.147
207484AF2-139 C O1
Solar/Wind Helper
0.09
203975AE1-071-GEN
Solar/Wind Helper
2.635
20674828DL_W4-046
Solar/Wind Helper
0.008
20675928HOL_W4-097
Solar/Wind Helper
0.054
238208AF1-136 C
Solar/Wind Helper
0.189
20676328BVR_Y1-020
Solar/Wind Helper
0.029
207530AG1-191 GEN
Solar/Wind Helper
0.071
966261AG1-495 GEN
Solar/Wind Helper
0.087
218524CNTRALGAS1 C
Solar/Wind Helper
0.17
218526CNTRALGAS2 C
Solar/Wind Helper
0.17
20675528CPH_W2-050
Solar/Wind Helper
0.092
219620RIDERU C
Solar/Wind Helper
0.001
207459AE1-142 C O1
Solar/Wind Helper
0.304
20715728PEM_W1-119
Solar/Wind Helper
0.1
20715828PEM_W1-120
Solar/Wind Helper
0.1
214067T20SOLAR
Solar/Wind Helper
0.012
959381AF2-229 GEN
Solar/Wind Helper
0.359
219607WPEMNERT C
Solar/Wind Helper
0.083
219688LUMSOLAR_S C
Solar/Wind Helper
0.041
219272CLEANLIGHT C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.119
227927V4-067C
Solar/Wind Helper
0.011
228754AB1-001 C
Solar/Wind Helper
0.027
964001AG1-254 GEN
Solar/Wind Helper
0.988
234033AF1-007_GEN
Solar/Wind Helper
7.137
233923SMA
Solar/Wind Helper
0.974
233990AG1-397 GEN
Solar/Wind Helper
0.031
232432Z2-076 GEN
Solar/Wind Helper
0.068
237085AD2-009_GEN
Solar/Wind Helper
1.427
205932AD2-116_GEN
Solar/Wind Helper
0.516
205956AE1-196_GEN
Solar/Wind Helper
0.516
205943AE1-185 GEN
Solar/Wind Helper
0.515
232436AB1-176 C
Solar/Wind Helper
0.045
233935AB2-179 C
Solar/Wind Helper
1.288
960921AF2-383 GEN
Solar/Wind Helper
0.183
944201AF1-088_MTX
Adder
165.192
957141AF2-008_MTX
Adder
82.596
CBM West 1LTFEXP_CBM-W1->PJM
CBM
172.314
CBM South 1LTFEXP_CBM-S1->PJM
CBM
49.115
MECLTFEXP_MEC->PJM
CLTF
22.175
SIGELTFEXP_SIGE->PJM
CLTF
0.736
LAGNLTFEXP_LAGN->PJM
CLTF
25.149
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.665
TVALTFEXP_TVA->PJM
CLTF
12.772
CPLELTFEXP_CPLE->PJM
CLTF
6.71
CBM West 2LTFEXP_CBM-W2->PJM
CBM
175.047
NYPJM->LTFIMP_NY
CLTF
6.186
LGEELTFEXP_LGEE->PJM
CLTF
9.94
WECLTFEXP_WEC->PJM
CLTF
5.055
AG2-052LTFEXP_AG2-052->PJM
LTF
0.309
AH1-155LTFEXP_AH1-155->PJM
LTF
0.464

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.86 %
Rating:4558.0 MVA
Rating Type:A
MVA to Mitigate:4961.85
MW Contribution:7.21
Bus #Bus NameTypeMW Contribution
243186AF1-051 GEN
50/50
11.679
24723005RIVRG1
Adder
32.794
24723105RIVRG2
Adder
32.794
24685805CER G1
Adder
14.046
24685905CER G2
Adder
14.046
944971AF1-162 GEN
Solar/Wind Harmer
11.031
24728205BUCHG1
Adder
6.221
971225AH1-072 GEN
Solar/Wind Harmer
1.893
971227AH1-073 GEN
Solar/Wind Harmer
1.893
971277AH1-098 GEN
Solar/Wind Harmer
3.403
960161AF2-307 GEN
Solar/Wind Harmer
5.337
971073AG2-665 GEN
Solar/Wind Harmer
7.21
270583AD2-179 GEN
Solar/Wind Harmer
7.911
270186AC1-089 GEN
Solar/Wind Harmer
0.005
970239AG2-162 GEN
Solar/Wind Harmer
1.961
962581AG1-107 GEN
Solar/Wind Harmer
0.002
942891AE2-308 GEN
Solar/Wind Harmer
7.714
972043AH1-570 GEN
Solar/Wind Harmer
1.999
972045AH1-571 GEN
Solar/Wind Harmer
1.602
339221AD2-048_GEN
Solar/Wind Harmer
0.005
971125AH1-004 GEN
Solar/Wind Harmer
3.056
970107AG2-081 GEN
Solar/Wind Harmer
2.292
970235AG2-159 GEN
Solar/Wind Harmer
4.628
970235AG2-159 GEN
Solar/Wind Harmer
2.656
966021AG1-471 GEN
Solar/Wind Harmer
4.054
252509AD1-136 GEN
Solar/Wind Harmer
0.038
971485AH1-239 GEN
Solar/Wind Harmer
5.998
971081AG2-670 GEN
Solar/Wind Harmer
5.621
970653AG2-424 GEN
Solar/Wind Harmer
3.613
970653AG2-424 GEN
Solar/Wind Harmer
1.872
964571AG1-320 GEN
Solar/Wind Harmer
6.819
339255AE2-071 GEN
Solar/Wind Harmer
-0.122
964781AG1-341 GEN
Solar/Wind Harmer
7.848
25183208HLCRTG
Solar/Wind Harmer
0.011
252519AF1-045_GEN
Solar/Wind Harmer
6.373
252516AE2-318_GEN
Solar/Wind Harmer
5.653
270444AC2-157 GEN1
Solar/Wind Harmer
0.003
971587AH1-292 GEN
Solar/Wind Harmer
5.336
25194408D.CRK1
Adder
7.868
25194508D.CRK3
Adder
1.471
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
945391AF1-204 GEN
Solar/Wind Harmer
7.288
24728805RICHG1
Adder
3.669
24728905RICHG2
Adder
3.669
970241AG2-163 GEN
Solar/Wind Harmer
3.905
276916AD2-100_GEN
Solar/Wind Harmer
14.016
276911AD2-131_GEN
Solar/Wind Harmer
0.923
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
966841AG1-555 GEN
Solar/Wind Harmer
0.746
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
270383AD1-128 GEN
Solar/Wind Harmer
0.004
971613AH1-306 GEN
Solar/Wind Harmer
3.122
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
970825AG2-519 GEN
Solar/Wind Harmer
7.169
960441AF2-335 GEN
Solar/Wind Harmer
6.468
960611AF2-352 GEN
Solar/Wind Harmer
2.156
253370AE2-315 SEC1
Adder
1.856
970883AG2-550 GEN
Solar/Wind Harmer
6.374
970885AG2-551 GEN
Solar/Wind Harmer
2.125
276782AC1-033 GEN
Solar/Wind Harmer
0.001
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.25
276646AC1-214 GEN2
Solar/Wind Harmer
0.25
270599AE1-208 GEN
Solar/Wind Harmer
5.819
270031AE2-169
Solar/Wind Harmer
3.492
276741O09 GEN1
Solar/Wind Harmer
0.226
276708O09 GEN2
Solar/Wind Harmer
0.226
972267AH1-718 GEN
Adder
3.783
25322209TAIT E
Adder
8.86
25322209TAIT E
Adder
8.661
276603SUBLETTE C
Solar/Wind Harmer
0
274764LEE CO EC;5U
Adder
8.452
274765LEE CO EC;6U
Adder
8.452
274762LEE CO EC;3U
Adder
8.432
274763LEE CO EC;4U
Adder
8.352
938861AE1-114 GEN
Solar/Wind Harmer
3.58
274856ECOGROVE ;U1
Solar/Wind Harmer
0.149
276611AD2-172 GEN
Solar/Wind Harmer
0.002
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
971341AH1-150 GEN
Solar/Wind Harmer
12.585
971343AH1-151 GEN
Solar/Wind Harmer
12.585
247621Y3-024
Adder
0.216
274683WAUKEGAN ;8U
Adder
18.876
274683WAUKEGAN ;8U
Adder
15.912
274696ROCKY RD ;4P
Adder
10.207
274695ROCKY RD ;2P
Adder
9.971
274693ROCKY RD ;1P
Adder
9.873
274697ROCKY RD ;3P
Adder
2.709
23652301WDPWR_K20
Solar/Wind Helper
0.126
23585401KL_K28_T16
Solar/Wind Helper
1.149
970321AG2-212 GEN
Solar/Wind Harmer
1.358
24289405MTG1
50/50
10.907
24318705GVG2
50/50
10.872
24722005FLATG5
50/50
2.473
24721905FLATG4
50/50
45.331
24686205CER G4
Adder
14.065
24686405CER G5
Adder
14.009
270053AF1-130 C
Solar/Wind Harmer
2.49
970913AG2-568 GEN
Solar/Wind Harmer
8.136
971191AH1-055 GEN
Solar/Wind Harmer
25.624
960911AF2-382 GEN
Solar/Wind Harmer
7.284
972103AH1-617 GEN
Solar/Wind Harmer
19.189
971461AH1-227 GEN
Solar/Wind Harmer
4.855
270346AE1-212 GEN
Solar/Wind Harmer
7.86
943031AE2-326 GEN
Solar/Wind Harmer
4.498
971331AH1-145 GEN
Solar/Wind Harmer
10.953
247619Y1-049
Adder
0.497
958121AF2-106 GEN
Solar/Wind Harmer
0.001
970243AG2-164 GEN
Solar/Wind Harmer
4.588
970519AG2-331 GEN
Solar/Wind Harmer
20.392
970699AG2-449 GEN
Solar/Wind Harmer
1.961
970093AG2-073 GEN
Solar/Wind Harmer
7.734
972167AH1-666 GEN
Solar/Wind Harmer
6.174
972273AH1-721 GEN
Adder
91.659
966571AG1-526 GEN
Solar/Wind Harmer
17.032
3429391JKCT 9G
Adder
9.139
970273AG2-179 GEN
Solar/Wind Harmer
4.533
270291AC1-194 GEN
Solar/Wind Harmer
5.957
958171AF2-111 GEN
Solar/Wind Harmer
18.792
339250AF1-203 GEN
Solar/Wind Harmer
0.001
960741AF2-365 GEN
Solar/Wind Harmer
3.705
971155AH1-034 GEN
Solar/Wind Harmer
8.639
962251AG1-071 GEN
Solar/Wind Harmer
4.615
25196008MFTGT1
Adder
1.418
252510AF1-249 C
Solar/Wind Harmer
0.056
25194608D.CRK4
Adder
1.71
25196608WSDLE5
Adder
8.886
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
9.211
970153AG2-106 GEN
Solar/Wind Harmer
17.538
253406AD2-031_GEN
Solar/Wind Harmer
0.522
970193AG2-126 GEN
Solar/Wind Harmer
10.289
24728705AND G3
Adder
7.865
24728505AND G1
Adder
3.761
24721605FLATG1
50/50
2.473
972203AH1-686 GEN
Adder
3.978
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
957241AF2-018 GEN
Solar/Wind Harmer
-0.002
24477305BRIDGE
Adder
0.546
270399AC1-101 GEN
Solar/Wind Harmer
3.444
270400AC1-102 GEN
Solar/Wind Harmer
3.444
941621AE2-160 GEN
Adder
4.703
970281AG2-184 GEN
Solar/Wind Harmer
20.149
972143AH1-644 GEN
Solar/Wind Harmer
10.394
971313AH1-133 GEN
Solar/Wind Harmer
9.492
270132AB1-180 C
Adder
0.159
971061AG2-657 GEN
Solar/Wind Harmer
5.654
24734705WLF1G3
Adder
7.306
24734805WLF1G4
Adder
7.306
24734905WLF1G5
Adder
7.306
971985AH1-537 GEN
Solar/Wind Harmer
2.617
24735105WLF2G1
Adder
7.162
966391AG1-508 GEN
Solar/Wind Harmer
1.328
970879AG2-548 GEN
Solar/Wind Harmer
7.21
971981AH1-535 GEN
Solar/Wind Harmer
5.272
270367AC2-061_GEN
Solar/Wind Harmer
0.006
972163AH1-664 GEN
Solar/Wind Harmer
8.62
972165AH1-665 GEN
Solar/Wind Harmer
6.904
3429211JKCT 2G
Adder
12.898
965401AG1-405 GEN
Solar/Wind Harmer
4.386
965411AG1-406 GEN
Solar/Wind Harmer
2.821
339211AE2-254 GEN
Solar/Wind Harmer
0.003
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
970455AG2-298 GEN
Solar/Wind Harmer
5.018
25196108MFTGT2
Adder
1.614
25196108MFTGT2
Adder
1.499
252524AE2-267 GEN
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
9.147
25196308WSDLE2
Adder
9.067
25196208WSDLE1
Adder
9.045
25196708WSDLE6
Adder
9.022
25196508WSDLE4
Adder
8.795
962771AG1-126 GEN
Solar/Wind Harmer
27.465
270340AC2-060 GEN
Solar/Wind Harmer
0.008
270069AE2-166 C O1
Solar/Wind Harmer
0.005
944221AF1-090 GEN
Solar/Wind Harmer
3.946
963841AG1-237 GEN
Solar/Wind Harmer
2.88
270240V3-007_GEN2
Solar/Wind Harmer
0.002
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.24
276848AB2-070 GEN3
Solar/Wind Harmer
0.239
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
270269AC2-059
Solar/Wind Harmer
0.004
970289AG2-191 GEN
Solar/Wind Harmer
1.237
270594AE1-207 GEN
Solar/Wind Harmer
7.284
25306009OHH W.
Adder
2.673
970115AG2-085 GEN
Solar/Wind Harmer
2.587
253372AE2-315 SEC3
Adder
1.755
253372AE2-315 SEC3
Adder
1.755
971673AH1-337 GEN
Solar/Wind Harmer
4.2
971029AG2-637 GEN
Solar/Wind Harmer
9.661
276655WTG1_EQ
Solar/Wind Harmer
0.003
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
6.757
941731AE2-173 GEN
Solar/Wind Harmer
5.363
253349AC2-067 GEN
Solar/Wind Harmer
2.02
253400AC2-068 GEN
Solar/Wind Harmer
0.812
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
946321AF1-296 GEN
Solar/Wind Harmer
3.573
971611AH1-305 GEN
Solar/Wind Harmer
3.799
270543AE2-219 C
Solar/Wind Harmer
0.004
957751AF2-069 GEN
Solar/Wind Harmer
0.21
970169AG2-114 GEN
Solar/Wind Harmer
6.359
971609AH1-304 GEN
Solar/Wind Harmer
1.037
961011AF2-392 GEN
Solar/Wind Harmer
3.717
926823AC1-168 GEN
Solar/Wind Harmer
1.076
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971681AH1-341 GEN
Solar/Wind Harmer
10.171
945581AF1-223 GEN
Solar/Wind Harmer
0
276612AE2-035 GEN
Solar/Wind Harmer
0.002
274823ROCKFORD ;21
Adder
17.581
971171AH1-044 GEN
Solar/Wind Harmer
12.585
274746AC1-111 G10
Adder
4.992
274744AC1-111 GEN8
Adder
4.992
23750501ELLIOTTS
Solar/Wind Helper
0.594
24289405MTG1
50/50
10.907
243186AF1-051 GEN
50/50
11.679
24318705GVG2
50/50
10.872
24721805FLATG3
50/50
2.473
24721705FLATG2
50/50
45.331
24723205RIVRG3
Adder
32.794
24686105CER G3
Adder
14.139
24686505CER G6
Adder
14.12
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
970947AG2-589 GEN
Solar/Wind Harmer
0.368
971403AH1-188 GEN
Solar/Wind Harmer
15.305
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
24728305BUCHG2
Adder
6.221
971315AH1-136 GEN
Solar/Wind Harmer
1.928
971687AH1-348 GEN
Solar/Wind Harmer
0.947
927014AC1-188 GEN
Solar/Wind Harmer
0.005
24735205WLF2G2
Adder
7.162
971329AH1-144 GEN
Solar/Wind Harmer
6.901
970091AG2-072 GEN
Adder
86.947
970333AG2-219 GEN
Solar/Wind Harmer
5.608
945681AF1-233 GEN
Solar/Wind Harmer
14.563
3429241JKCT 3G
Adder
13.068
971821AH1-427 GEN
Solar/Wind Harmer
7.658
3429421JKCT 10G
Adder
9.139
339216AC1-074 GEN
Solar/Wind Harmer
0.209
970273AG2-179 GEN
Solar/Wind Harmer
2.644
971565AH1-281 GEN
Solar/Wind Harmer
1.508
252507AC2-088 GEN
Solar/Wind Harmer
0.341
964901AG1-354 GEN
Solar/Wind Harmer
11.154
25196808ZIMRHP
Adder
80.408
962241AG1-070 GEN
Solar/Wind Harmer
4.025
25196008MFTGT1
Adder
1.465
270445AC2-157 GEN2
Solar/Wind Harmer
0.003
25194608D.CRK4
Adder
1.71
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.086
962761AG1-125 GEN
Solar/Wind Harmer
27.465
970149AG2-104 GEN
Solar/Wind Harmer
29.663
970155AG2-107 GEN
Solar/Wind Harmer
17.538
270336AE1-100 GEN
Solar/Wind Harmer
0.004
270263AC1-001 GEN
Solar/Wind Harmer
0.699
24728605AND G2
Adder
3.761
970773AG2-487 GEN
Solar/Wind Harmer
1.204
971367AH1-164 GEN
Solar/Wind Harmer
2.344
963741AG1-226 GEN
Solar/Wind Harmer
15.844
965911AG1-460 GEN
Solar/Wind Harmer
1.332
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.849
276615X2-022 GEN
Solar/Wind Harmer
0.069
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.002
963831AG1-236 GEN
Solar/Wind Harmer
2.568
274880W4-005 GEN4
Solar/Wind Harmer
0.001
276903AD2-071 C
Solar/Wind Harmer
7.334
972175AH1-670 GEN
Solar/Wind Harmer
5.394
24791305MDL-5G
Solar/Wind Harmer
0.001
970291AG2-192 GEN
Solar/Wind Harmer
0.846
270032AE2-172
Solar/Wind Harmer
4.336
270005AE1-210 C O1
Solar/Wind Harmer
1.405
965031AG1-367 GEN
Solar/Wind Harmer
6.485
970825AG2-519 GEN
Solar/Wind Harmer
2.296
274854TWINGROVE;U2
Solar/Wind Harmer
0.003
253370AE2-315 SEC1
Adder
1.856
253371AE2-315 SEC2
Adder
1.755
276726Z2-087_GEN
Solar/Wind Harmer
0.002
939741AE1-205 GEN
Solar/Wind Harmer
9.009
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
7.976
274877BISHOP HL;1U
Solar/Wind Harmer
0.214
276158O29GEN2
Solar/Wind Harmer
0.001
960071AF2-298 GEN
Solar/Wind Harmer
3.157
25326309TAIT D
Adder
0.995
970569AG2-363 GEN
Solar/Wind Harmer
18.972
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
8.432
274766LEE CO EC;7U
Adder
8.332
945371AF1-202 GEN
Solar/Wind Harmer
0.001
247536S-71 GEN
Solar/Wind Harmer
0.254
971475AH1-234 GEN
Solar/Wind Harmer
3.061
970819AG2-516 GEN
Solar/Wind Harmer
7.565
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
972235AH1-702 GEN1
Adder
2.276
939401AE1-172 GEN
Solar/Wind Harmer
4.71
274822ROCKFORD ;11
Adder
17.71
957471AF2-041 GEN
Solar/Wind Harmer
18.878
959081AF2-199 GEN
Solar/Wind Harmer
6.293
971067AG2-660 GEN
Solar/Wind Harmer
2.098
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.18
971997AH1-543 GEN
Solar/Wind Harmer
3.301
274828WAUKEGAN ;BP
Adder
9.895
274682WAUKEGAN ;7U
Adder
16.093
274745AC1-111 GEN9
Adder
4.992
237046AF1-021 C
Solar/Wind Helper
0.433
238185AF2-356 C
Solar/Wind Helper
1.954
23751201ROTHROCK
Solar/Wind Helper
0.662
235054AD2-180 GEN
Solar/Wind Helper
1.52
23562501BACKB
Solar/Wind Helper
0.806
970245AG2-165 GEN
Solar/Wind Harmer
1.358
270356AE2-297 GEN
Solar/Wind Harmer
0.009
270222AC2-111 GEN
Solar/Wind Harmer
3.451
253415AE1-040 GEN
Solar/Wind Harmer
0.003
270030AE2-140 GEN
Solar/Wind Harmer
13.595
942481AE2-261 GEN
Solar/Wind Harmer
19.91
972173AH1-669 GEN
Solar/Wind Harmer
3.31
270437AC2-090 C
Solar/Wind Harmer
0.003
276621W2-048 GEN
Solar/Wind Harmer
0.333
276838X2-022 GEN2
Solar/Wind Harmer
0.372
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
3.038
276668AB2-070 GEN1
Solar/Wind Harmer
0.24
247642Z2-115 C
Solar/Wind Harmer
0.003
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.514
270273AD2-016 GEN
Solar/Wind Harmer
0.675
970289AG2-191 GEN
Solar/Wind Harmer
0.716
970291AG2-192 GEN
Solar/Wind Harmer
0.651
958821AF2-173 GEN
Solar/Wind Harmer
9.079
270004AE1-209 GEN
Solar/Wind Harmer
1.405
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
965091AG1-374 GEN
Solar/Wind Harmer
19.404
959611AF2-252 GEN
Solar/Wind Harmer
2.156
253370AE2-315 SEC1
Adder
1.856
253371AE2-315 SEC2
Adder
1.755
942111AE2-223 GEN
Solar/Wind Harmer
2.091
946031AF1-268 GEN
Solar/Wind Harmer
6.117
970191AG2-125 GEN
Solar/Wind Harmer
1.65
965931AG1-462 GEN
Solar/Wind Harmer
16.291
274878BISHOP HL;2U
Solar/Wind Harmer
0.214
276157O29GEN1
Solar/Wind Harmer
1.026
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
970571AG2-364 GEN
Solar/Wind Harmer
12.648
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
8.432
274767LEE CO EC;8U
Adder
8.332
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
1.979
959091AF2-200 GEN
Solar/Wind Harmer
12.585
274682WAUKEGAN ;7U
Adder
16.093
274729ELWOOD EC;1P
Adder
6.64
237048AF1-022 C
Solar/Wind Helper
0.172
237043AE2-125 C
Solar/Wind Helper
0.155
235058AG1-386 C
Solar/Wind Helper
0.383
970513AG2-328 GEN
Solar/Wind Harmer
1.358
970517AG2-330 GEN
Solar/Wind Harmer
8.151
944201AF1-088_MTX
Adder
121.273
957141AF2-008_MTX
Adder
60.637
CBM West 1LTFEXP_CBM-W1->PJM
CBM
116.498
CBM South 1LTFEXP_CBM-S1->PJM
CBM
38.98
MECLTFEXP_MEC->PJM
CLTF
15.75
SIGELTFEXP_SIGE->PJM
CLTF
0.547
LAGNLTFEXP_LAGN->PJM
CLTF
19.803
CBM South 2LTFEXP_CBM-S2->PJM
CBM
23.164
TVALTFEXP_TVA->PJM
CLTF
10.26
CPLELTFEXP_CPLE->PJM
CLTF
6.38
CBM West 2LTFEXP_CBM-W2->PJM
CBM
132.776
NYPJM->LTFIMP_NY
CLTF
4.59
LGEELTFEXP_LGEE->PJM
CLTF
7.503
WECLTFEXP_WEC->PJM
CLTF
3.454
AG2-052LTFEXP_AG2-052->PJM
LTF
0.209
AH1-155LTFEXP_AH1-155->PJM
LTF
0.313

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.47 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5991.02
MW Contribution:14.08
Bus #Bus NameTypeMW Contribution
24289405MTG1
50/50
11.79
24318705GVG2
50/50
11.866
24722005FLATG5
50/50
2.714
24721905FLATG4
50/50
49.755
24686205CER G4
Adder
16.139
24686405CER G5
Adder
16.075
270053AF1-130 C
Solar/Wind Harmer
6.909
970913AG2-568 GEN
Solar/Wind Harmer
14.13
960911AF2-382 GEN
Solar/Wind Harmer
12.931
943031AE2-326 GEN
Solar/Wind Harmer
6.109
971461AH1-227 GEN
Solar/Wind Harmer
8.54
972103AH1-617 GEN
Solar/Wind Harmer
33.271
971331AH1-145 GEN
Solar/Wind Harmer
15.359
247619Y1-049
Adder
0.704
971191AH1-055 GEN
Solar/Wind Harmer
36.143
270346AE1-212 GEN
Solar/Wind Harmer
14.72
958121AF2-106 GEN
Solar/Wind Harmer
7.412
957541AF2-048 GEN
Solar/Wind Harmer
2.373
972273AH1-721 GEN
Adder
111.61
270030AE2-140 GEN
Solar/Wind Harmer
26.875
970093AG2-073 GEN
Solar/Wind Harmer
13.356
970243AG2-164 GEN
Solar/Wind Harmer
34.33
970519AG2-331 GEN
Solar/Wind Harmer
23.064
970699AG2-449 GEN
Solar/Wind Harmer
15.258
966571AG1-526 GEN
Solar/Wind Harmer
29.484
270173AC1-122 GEN
Solar/Wind Harmer
2.108
3429391JKCT 9G
Adder
10.993
970273AG2-179 GEN
Solar/Wind Harmer
5.144
972167AH1-666 GEN
Solar/Wind Harmer
10.547
962751AG1-124 GEN
Solar/Wind Harmer
11.816
339250AF1-203 GEN
Solar/Wind Harmer
0.784
971155AH1-034 GEN
Solar/Wind Harmer
12.926
960741AF2-365 GEN
Solar/Wind Harmer
6.448
962251AG1-071 GEN
Solar/Wind Harmer
7.087
958171AF2-111 GEN
Solar/Wind Harmer
32.167
243186AF1-051 GEN
50/50
12.748
24723005RIVRG1
Adder
37.637
24723105RIVRG2
Adder
37.637
24685805CER G1
Adder
16.117
24685905CER G2
Adder
16.117
944971AF1-162 GEN
Solar/Wind Harmer
13.01
24728205BUCHG1
Adder
7.763
270214AC2-123 GEN
Solar/Wind Harmer
3.882
971225AH1-072 GEN
Solar/Wind Harmer
3.33
971227AH1-073 GEN
Solar/Wind Harmer
3.33
971277AH1-098 GEN
Solar/Wind Harmer
6.642
270583AD2-179 GEN
Solar/Wind Harmer
16.345
960161AF2-307 GEN
Solar/Wind Harmer
8.906
970879AG2-548 GEN
Solar/Wind Harmer
8.293
971073AG2-665 GEN
Solar/Wind Harmer
8.293
971073AG2-665 GEN
Solar/Wind Harmer
5.786
270186AC1-089 GEN
Solar/Wind Harmer
8.143
970239AG2-162 GEN
Solar/Wind Harmer
14.622
942891AE2-308 GEN
Solar/Wind Harmer
13.304
339231AF1-038_GEN
Solar/Wind Harmer
2.394
972043AH1-570 GEN
Solar/Wind Harmer
3.299
972045AH1-571 GEN
Solar/Wind Harmer
2.639
339221AD2-048_GEN
Solar/Wind Harmer
2.024
966021AG1-471 GEN
Solar/Wind Harmer
7.099
971125AH1-004 GEN
Solar/Wind Harmer
5.257
970107AG2-081 GEN
Solar/Wind Harmer
3.942
971485AH1-239 GEN
Solar/Wind Harmer
10.499
962581AG1-107 GEN
Solar/Wind Harmer
6.599
961491AF2-440 GEN
Solar/Wind Harmer
2.742
971081AG2-670 GEN
Solar/Wind Harmer
9.778
970235AG2-159 GEN
Solar/Wind Harmer
5.2
970235AG2-159 GEN
Solar/Wind Harmer
3.174
339236AF1-050_GEN
Solar/Wind Harmer
2.357
970653AG2-424 GEN
Solar/Wind Harmer
6.261
970653AG2-424 GEN
Solar/Wind Harmer
2.263
339255AE2-071 GEN
Solar/Wind Harmer
1.372
964781AG1-341 GEN
Solar/Wind Harmer
13.698
964571AG1-320 GEN
Solar/Wind Harmer
10.586
252509AD1-136 GEN
Solar/Wind Harmer
0.327
25183208HLCRTG
Solar/Wind Harmer
7.582
252519AF1-045_GEN
Solar/Wind Harmer
7.591
252516AE2-318_GEN
Solar/Wind Harmer
5.79
270444AC2-157 GEN1
Solar/Wind Harmer
6.973
25194408D.CRK1
Adder
9.381
25194508D.CRK3
Adder
1.754
253317AC1-085 GEN4
Solar/Wind Harmer
10.168
945391AF1-204 GEN
Solar/Wind Harmer
16.499
253394AE2-221_GEN
Solar/Wind Harmer
5.367
253398AE2-221_GEN2
Solar/Wind Harmer
5.367
316217AC1-145 GEN
Solar/Wind Harmer
2.806
316197AC1-042 GEN
Solar/Wind Harmer
2.127
942671AE2-283 GEN
Solar/Wind Harmer
5.728
24728805RICHG1
Adder
4.412
24728905RICHG2
Adder
4.412
276916AD2-100_GEN
Solar/Wind Harmer
24.323
276911AD2-131_GEN
Solar/Wind Harmer
4.916
253370AE2-315 SEC1
Adder
2.238
972267AH1-718 GEN
Adder
4.6
274764LEE CO EC;5U
Adder
10.276
274765LEE CO EC;6U
Adder
10.276
274762LEE CO EC;3U
Adder
10.252
274763LEE CO EC;4U
Adder
10.155
25322209TAIT E
Adder
10.707
25322209TAIT E
Adder
10.466
274683WAUKEGAN ;8U
Adder
22.951
274683WAUKEGAN ;8U
Adder
19.347
274696ROCKY RD ;4P
Adder
12.409
274695ROCKY RD ;2P
Adder
12.123
274693ROCKY RD ;1P
Adder
12.003
274697ROCKY RD ;3P
Adder
3.293
247621Y3-024
Adder
0.262
23585401KL_K28_T16
Solar/Wind Helper
1.267
23652301WDPWR_K20
Solar/Wind Helper
0.133
238120AE2-309 GEN
Solar/Wind Helper
0.43
203955AF1-039 C O1
Solar/Wind Helper
0.352
944781AF1-143 GEN
Solar/Wind Helper
2.298
20083426SW_E13_K22
Solar/Wind Helper
0.051
20088926STNY CRK
Solar/Wind Helper
0.747
20084626FORWARD
Solar/Wind Helper
0.323
946071AF1-272 GEN
Solar/Wind Helper
2.428
203940AF1-140 C
Solar/Wind Helper
0.359
970241AG2-163 GEN
Solar/Wind Harmer
12.594
24289405MTG1
50/50
11.79
243186AF1-051 GEN
50/50
12.748
24318705GVG2
50/50
11.866
24721805FLATG3
50/50
2.714
24721705FLATG2
50/50
49.755
24723205RIVRG3
Adder
37.637
24686105CER G3
Adder
16.224
24686505CER G6
Adder
16.203
971403AH1-188 GEN
Solar/Wind Harmer
26.09
270331AC1-082 GEN3
Solar/Wind Harmer
0.823
970947AG2-589 GEN
Solar/Wind Harmer
3.612
960001AF2-291 GEN
Solar/Wind Harmer
5.329
24728305BUCHG2
Adder
7.763
971687AH1-348 GEN
Solar/Wind Harmer
1.664
971329AH1-144 GEN
Solar/Wind Harmer
19.813
971315AH1-136 GEN
Solar/Wind Harmer
3.299
24735205WLF2G2
Adder
9.002
927014AC1-188 GEN
Solar/Wind Harmer
2.379
971367AH1-164 GEN
Solar/Wind Harmer
5.069
270336AE1-100 GEN
Solar/Wind Harmer
2.384
970091AG2-072 GEN
Adder
103.033
970333AG2-219 GEN
Solar/Wind Harmer
41.959
3429241JKCT 3G
Adder
15.723
971821AH1-427 GEN
Solar/Wind Harmer
13.272
3429421JKCT 10G
Adder
10.993
945681AF1-233 GEN
Solar/Wind Harmer
24.878
970273AG2-179 GEN
Solar/Wind Harmer
3.221
943111AE2-339 GEN
Solar/Wind Harmer
1.163
943811AF1-049 GEN
Solar/Wind Harmer
4.961
339216AC1-074 GEN
Solar/Wind Harmer
2.198
339241AF1-083 GEN
Solar/Wind Harmer
2.171
971565AH1-281 GEN
Solar/Wind Harmer
2.604
964901AG1-354 GEN
Solar/Wind Harmer
19.445
962241AG1-070 GEN
Solar/Wind Harmer
5.799
252507AC2-088 GEN
Solar/Wind Harmer
2.292
25196808ZIMRHP
Adder
95.812
25196008MFTGT1
Adder
1.747
270445AC2-157 GEN2
Solar/Wind Harmer
6.973
25194608D.CRK4
Adder
2.039
270018AE2-047 C O1
Solar/Wind Harmer
1.511
253432AC1-085 GEN2
Solar/Wind Harmer
0.325
946171AF1-282 GEN
Solar/Wind Harmer
12.138
270263AC1-001 GEN
Solar/Wind Harmer
1.245
24728605AND G2
Adder
4.525
962761AG1-125 GEN
Solar/Wind Harmer
38.198
970149AG2-104 GEN
Solar/Wind Harmer
47.174
970155AG2-107 GEN
Solar/Wind Harmer
16.656
270197AD1-017 GEN1
Solar/Wind Harmer
1.81
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
6.484
253370AE2-315 SEC1
Adder
2.238
253371AE2-315 SEC2
Adder
2.117
274761LEE CO EC;2U
Adder
10.252
274766LEE CO EC;7U
Adder
10.131
972235AH1-702 GEN1
Adder
2.767
25326309TAIT D
Adder
1.202
274822ROCKFORD ;11
Adder
21.533
274828WAUKEGAN ;BP
Adder
12.03
274682WAUKEGAN ;7U
Adder
19.567
274745AC1-111 GEN9
Adder
6.069
238185AF2-356 C
Solar/Wind Helper
2.176
237046AF1-021 C
Solar/Wind Helper
0.457
235054AD2-180 GEN
Solar/Wind Helper
1.695
238117U2-030
Solar/Wind Helper
0.288
235531U2-073 GEN
Solar/Wind Helper
2.733
23751201ROTHROCK
Solar/Wind Helper
0.71
23562501BACKB
Solar/Wind Helper
0.864
23583801GRNGAP
Solar/Wind Helper
4.088
316095T157 G97
Solar/Wind Helper
1.094
238108AE1-109 GEN1
Solar/Wind Helper
0.088
20089226LOOKOUT
Solar/Wind Helper
0.539
20088826HIGHLAND
Solar/Wind Helper
0.812
963741AG1-226 GEN
Solar/Wind Harmer
22.669
24721605FLATG1
50/50
2.714
972203AH1-686 GEN
Adder
4.544
957241AF2-018 GEN
Solar/Wind Harmer
8.259
270399AC1-101 GEN
Solar/Wind Harmer
7.833
270400AC1-102 GEN
Solar/Wind Harmer
7.833
24477305BRIDGE
Adder
0.637
270330AC1-082 GEN2
Solar/Wind Harmer
1.393
270329AC1-082 GEN1
Solar/Wind Harmer
0.821
971313AH1-133 GEN
Solar/Wind Harmer
17.224
941621AE2-160 GEN
Adder
5.66
966391AG1-508 GEN
Solar/Wind Harmer
5.763
970281AG2-184 GEN
Solar/Wind Harmer
34.934
972143AH1-644 GEN
Solar/Wind Harmer
16.635
270132AB1-180 C
Adder
0.198
24734705WLF1G3
Adder
9.185
24734805WLF1G4
Adder
9.185
24734905WLF1G5
Adder
9.185
962211AG1-066 GEN
Solar/Wind Harmer
3.823
24735105WLF2G1
Adder
9.002
971061AG2-657 GEN
Solar/Wind Harmer
14.056
971985AH1-537 GEN
Solar/Wind Harmer
26.201
971981AH1-535 GEN
Solar/Wind Harmer
14.209
270069AE2-166 C O1
Solar/Wind Harmer
3.796
970879AG2-548 GEN
Solar/Wind Harmer
5.786
965401AG1-405 GEN
Solar/Wind Harmer
7.637
965411AG1-406 GEN
Solar/Wind Harmer
3.428
270367AC2-061_GEN
Solar/Wind Harmer
4.222
3429211JKCT 2G
Adder
15.52
339211AE2-254 GEN
Solar/Wind Harmer
2.01
972163AH1-664 GEN
Solar/Wind Harmer
13.228
972165AH1-665 GEN
Solar/Wind Harmer
10.582
339243AC2-075 GEN1
Solar/Wind Harmer
0.595
970455AG2-298 GEN
Solar/Wind Harmer
7.809
25196108MFTGT2
Adder
1.926
270291AC1-194 GEN
Solar/Wind Harmer
13.485
25196008MFTGT1
Adder
1.692
252510AF1-249 C
Solar/Wind Harmer
0.521
25194608D.CRK4
Adder
2.039
25196608WSDLE5
Adder
10.598
253316AC1-085 GEN3
Solar/Wind Harmer
10.168
253433AC1-085 GEN1
Solar/Wind Harmer
6.454
946181AF1-283 GEN
Solar/Wind Harmer
15.78
253406AD2-031_GEN
Solar/Wind Harmer
1.534
970193AG2-126 GEN
Solar/Wind Harmer
17.759
24728705AND G3
Adder
9.464
24728505AND G1
Adder
4.525
970153AG2-106 GEN
Solar/Wind Harmer
16.656
270574AD1-017 GEN2
Solar/Wind Harmer
6.023
3147312GRETNA
Solar/Wind Harmer
-0.014
3146802CHATHAM
Solar/Wind Harmer
-0.013
941801AE2-185 GEN
Solar/Wind Harmer
6.484
270356AE2-297 GEN
Solar/Wind Harmer
5.354
270222AC2-111 GEN
Solar/Wind Harmer
9.554
253415AE1-040 GEN
Solar/Wind Harmer
1.318
253370AE2-315 SEC1
Adder
2.238
253371AE2-315 SEC2
Adder
2.117
274760LEE CO EC;1U
Adder
10.252
274767LEE CO EC;8U
Adder
10.131
972236AH1-702 GEN2
Adder
2.406
274682WAUKEGAN ;7U
Adder
19.567
274729ELWOOD EC;1P
Adder
8.072
237048AF1-022 C
Solar/Wind Helper
0.182
964991AG1-363 GEN
Solar/Wind Helper
3.709
23750701CROSSCHOOL
Solar/Wind Helper
1.197
238118U2-030_1
Solar/Wind Helper
0.288
238127S14_GEN_2
Solar/Wind Helper
0.687
237043AE2-125 C
Solar/Wind Helper
0.163
202652Y1-033 WT C
Solar/Wind Helper
0.534
316097T157 G90
Solar/Wind Helper
1.094
20089126CSLMN_L13
Solar/Wind Helper
0.554
20089026BF_G21_K23
Solar/Wind Helper
0.438
25196108MFTGT2
Adder
1.788
252524AE2-267 GEN
Solar/Wind Harmer
1.95
25196408WSDLE3
Adder
10.91
25196308WSDLE2
Adder
10.815
25196208WSDLE1
Adder
10.788
25196708WSDLE6
Adder
10.761
25196508WSDLE4
Adder
10.49
270340AC2-060 GEN
Solar/Wind Harmer
3.615
962771AG1-126 GEN
Solar/Wind Harmer
38.198
944031AF1-071 GEN
Solar/Wind Harmer
1.178
944221AF1-090 GEN
Solar/Wind Harmer
12.754
25306009OHH W.
Adder
3.223
253372AE2-315 SEC3
Adder
2.117
253372AE2-315 SEC3
Adder
2.117
274823ROCKFORD ;21
Adder
21.377
274746AC1-111 G10
Adder
6.069
274744AC1-111 GEN8
Adder
6.069
23750501ELLIOTTS
Solar/Wind Helper
0.635
238126S14_GEN_1
Solar/Wind Helper
0.687
238109AE1-109 GEN2
Solar/Wind Helper
0.088
238110AE1-109 GEN3
Solar/Wind Helper
0.088
20092526R32
Solar/Wind Helper
1.053
944201AF1-088_MTX
Adder
145.184
957141AF2-008_MTX
Adder
72.592
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.592
CBM South 1LTFEXP_CBM-S1->PJM
CBM
47.815
MECLTFEXP_MEC->PJM
CLTF
19.173
SIGELTFEXP_SIGE->PJM
CLTF
0.659
LAGNLTFEXP_LAGN->PJM
CLTF
24.37
CBM South 2LTFEXP_CBM-S2->PJM
CBM
29.03
TVALTFEXP_TVA->PJM
CLTF
12.655
CPLELTFEXP_CPLE->PJM
CLTF
7.791
CBM West 2LTFEXP_CBM-W2->PJM
CBM
162.06
NYPJM->LTFIMP_NY
CLTF
5.271
LGEELTFEXP_LGEE->PJM
CLTF
8.989
WECLTFEXP_WEC->PJM
CLTF
4.2
AG2-052LTFEXP_AG2-052->PJM
LTF
0.253
AH1-155LTFEXP_AH1-155->PJM
LTF
0.38

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P1-2_#7422_16_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7422_16_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.56 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5885.34
MW Contribution:8.45
Bus #Bus NameTypeMW Contribution
243186AF1-051 GEN
50/50
12.748
24723005RIVRG1
Adder
37.637
24723105RIVRG2
Adder
37.637
24685805CER G1
Adder
16.117
24685905CER G2
Adder
16.117
944971AF1-162 GEN
Solar/Wind Harmer
13.01
24728205BUCHG1
Adder
7.763
971225AH1-072 GEN
Solar/Wind Harmer
2.323
971227AH1-073 GEN
Solar/Wind Harmer
2.323
971277AH1-098 GEN
Solar/Wind Harmer
4.634
270583AD2-179 GEN
Solar/Wind Harmer
11.403
960161AF2-307 GEN
Solar/Wind Harmer
6.387
971073AG2-665 GEN
Solar/Wind Harmer
8.448
270186AC1-089 GEN
Solar/Wind Harmer
0.006
970239AG2-162 GEN
Solar/Wind Harmer
2.322
942891AE2-308 GEN
Solar/Wind Harmer
9.282
972043AH1-570 GEN
Solar/Wind Harmer
2.394
972045AH1-571 GEN
Solar/Wind Harmer
1.918
339221AD2-048_GEN
Solar/Wind Harmer
0.006
966021AG1-471 GEN
Solar/Wind Harmer
4.953
971125AH1-004 GEN
Solar/Wind Harmer
3.667
970107AG2-081 GEN
Solar/Wind Harmer
2.751
971485AH1-239 GEN
Solar/Wind Harmer
7.325
962581AG1-107 GEN
Solar/Wind Harmer
0.002
971081AG2-670 GEN
Solar/Wind Harmer
6.822
970235AG2-159 GEN
Solar/Wind Harmer
5.533
970235AG2-159 GEN
Solar/Wind Harmer
3.174
970653AG2-424 GEN
Solar/Wind Harmer
4.368
970653AG2-424 GEN
Solar/Wind Harmer
2.263
339255AE2-071 GEN
Solar/Wind Harmer
-0.148
964781AG1-341 GEN
Solar/Wind Harmer
9.557
964571AG1-320 GEN
Solar/Wind Harmer
8.226
252509AD1-136 GEN
Solar/Wind Harmer
0.045
25183208HLCRTG
Solar/Wind Harmer
0.014
252519AF1-045_GEN
Solar/Wind Harmer
7.591
252516AE2-318_GEN
Solar/Wind Harmer
6.733
270444AC2-157 GEN1
Solar/Wind Harmer
0.004
971587AH1-292 GEN
Solar/Wind Harmer
6.388
25194408D.CRK1
Adder
9.381
25194508D.CRK3
Adder
1.754
253317AC1-085 GEN4
Solar/Wind Harmer
0.005
945391AF1-204 GEN
Solar/Wind Harmer
8.776
253394AE2-221_GEN
Solar/Wind Harmer
0.01
253398AE2-221_GEN2
Solar/Wind Harmer
0.01
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.002
942671AE2-283 GEN
Solar/Wind Harmer
3.83
24728805RICHG1
Adder
4.412
24728905RICHG2
Adder
4.412
276916AD2-100_GEN
Solar/Wind Harmer
16.969
276911AD2-131_GEN
Solar/Wind Harmer
1.118
970241AG2-163 GEN
Solar/Wind Harmer
4.709
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
24379505HDWTR1G C
Solar/Wind Harmer
0.003
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
966841AG1-555 GEN
Solar/Wind Harmer
0.9
270383AD1-128 GEN
Solar/Wind Harmer
0.005
971613AH1-306 GEN
Solar/Wind Harmer
3.767
960611AF2-352 GEN
Solar/Wind Harmer
2.614
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
970825AG2-519 GEN
Solar/Wind Harmer
8.658
960441AF2-335 GEN
Solar/Wind Harmer
7.811
253370AE2-315 SEC1
Adder
2.238
276782AC1-033 GEN
Solar/Wind Harmer
0.001
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.304
276646AC1-214 GEN2
Solar/Wind Harmer
0.304
276741O09 GEN1
Solar/Wind Harmer
0.275
276708O09 GEN2
Solar/Wind Harmer
0.275
972267AH1-718 GEN
Adder
4.6
970883AG2-550 GEN
Solar/Wind Harmer
7.705
970885AG2-551 GEN
Solar/Wind Harmer
2.568
276603SUBLETTE C
Solar/Wind Harmer
0
24721605FLATG1
50/50
2.714
972203AH1-686 GEN
Adder
4.544
957241AF2-018 GEN
Solar/Wind Harmer
-0.002
270399AC1-101 GEN
Solar/Wind Harmer
4.077
270400AC1-102 GEN
Solar/Wind Harmer
4.077
24477305BRIDGE
Adder
0.637
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
971313AH1-133 GEN
Solar/Wind Harmer
12.016
941621AE2-160 GEN
Adder
5.66
966391AG1-508 GEN
Solar/Wind Harmer
1.802
970281AG2-184 GEN
Solar/Wind Harmer
24.373
972143AH1-644 GEN
Solar/Wind Harmer
12.573
270132AB1-180 C
Adder
0.198
24734705WLF1G3
Adder
9.185
24734805WLF1G4
Adder
9.185
24734905WLF1G5
Adder
9.185
24735105WLF2G1
Adder
9.002
971061AG2-657 GEN
Solar/Wind Harmer
6.864
971985AH1-537 GEN
Solar/Wind Harmer
3.047
971981AH1-535 GEN
Solar/Wind Harmer
6.609
270069AE2-166 C O1
Solar/Wind Harmer
0.007
970879AG2-548 GEN
Solar/Wind Harmer
8.448
965401AG1-405 GEN
Solar/Wind Harmer
5.328
965411AG1-406 GEN
Solar/Wind Harmer
3.428
270367AC2-061_GEN
Solar/Wind Harmer
0.007
3429211JKCT 2G
Adder
15.52
339211AE2-254 GEN
Solar/Wind Harmer
0.004
972163AH1-664 GEN
Solar/Wind Harmer
10.275
972165AH1-665 GEN
Solar/Wind Harmer
8.229
339243AC2-075 GEN1
Solar/Wind Harmer
0.002
970455AG2-298 GEN
Solar/Wind Harmer
6.053
25196108MFTGT2
Adder
1.926
25196108MFTGT2
Adder
1.788
252524AE2-267 GEN
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
10.91
25196308WSDLE2
Adder
10.815
25196208WSDLE1
Adder
10.788
25196708WSDLE6
Adder
10.761
25196508WSDLE4
Adder
10.49
270340AC2-060 GEN
Solar/Wind Harmer
0.01
962771AG1-126 GEN
Solar/Wind Harmer
32.213
944221AF1-090 GEN
Solar/Wind Harmer
4.776
963841AG1-237 GEN
Solar/Wind Harmer
3.474
270240V3-007_GEN2
Solar/Wind Harmer
0.002
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.29
276848AB2-070 GEN3
Solar/Wind Harmer
0.289
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
1.493
270594AE1-207 GEN
Solar/Wind Harmer
8.791
270269AC2-059
Solar/Wind Harmer
0.004
970115AG2-085 GEN
Solar/Wind Harmer
3.124
276655WTG1_EQ
Solar/Wind Harmer
0.003
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
8.194
941731AE2-173 GEN
Solar/Wind Harmer
6.503
25306009OHH W.
Adder
3.223
971673AH1-337 GEN
Solar/Wind Harmer
5.07
253372AE2-315 SEC3
Adder
2.117
253372AE2-315 SEC3
Adder
2.117
971029AG2-637 GEN
Solar/Wind Harmer
11.666
946321AF1-296 GEN
Solar/Wind Harmer
4.345
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
274764LEE CO EC;5U
Adder
10.276
274765LEE CO EC;6U
Adder
10.276
274762LEE CO EC;3U
Adder
10.252
274763LEE CO EC;4U
Adder
10.155
938861AE1-114 GEN
Solar/Wind Harmer
4.353
270599AE1-208 GEN
Solar/Wind Harmer
7.04
270031AE2-169
Solar/Wind Harmer
4.224
274856ECOGROVE ;U1
Solar/Wind Harmer
0.181
276611AD2-172 GEN
Solar/Wind Harmer
0.002
25322209TAIT E
Adder
10.707
25322209TAIT E
Adder
10.466
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
270013AE1-250 PV
Solar/Wind Harmer
0.004
971341AH1-150 GEN
Solar/Wind Harmer
15.301
971343AH1-151 GEN
Solar/Wind Harmer
15.301
274683WAUKEGAN ;8U
Adder
22.951
274683WAUKEGAN ;8U
Adder
19.347
274696ROCKY RD ;4P
Adder
12.409
274695ROCKY RD ;2P
Adder
12.123
274693ROCKY RD ;1P
Adder
12.003
274697ROCKY RD ;3P
Adder
3.293
247621Y3-024
Adder
0.262
23585401KL_K28_T16
Solar/Wind Helper
1.267
23652301WDPWR_K20
Solar/Wind Helper
0.133
238120AE2-309 GEN
Solar/Wind Helper
0.43
203955AF1-039 C O1
Solar/Wind Helper
0.352
944781AF1-143 GEN
Solar/Wind Helper
2.298
20083426SW_E13_K22
Solar/Wind Helper
0.051
20088926STNY CRK
Solar/Wind Helper
0.747
20084626FORWARD
Solar/Wind Helper
0.323
946071AF1-272 GEN
Solar/Wind Helper
2.428
203940AF1-140 C
Solar/Wind Helper
0.359
253349AC2-067 GEN
Solar/Wind Harmer
2.438
253400AC2-068 GEN
Solar/Wind Harmer
0.981
957751AF2-069 GEN
Solar/Wind Harmer
0.255
971611AH1-305 GEN
Solar/Wind Harmer
4.596
970169AG2-114 GEN
Solar/Wind Harmer
7.718
270543AE2-219 C
Solar/Wind Harmer
0.005
961011AF2-392 GEN
Solar/Wind Harmer
4.519
926823AC1-168 GEN
Solar/Wind Harmer
1.307
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
971681AH1-341 GEN
Solar/Wind Harmer
12.366
971609AH1-304 GEN
Solar/Wind Harmer
1.254
276612AE2-035 GEN
Solar/Wind Harmer
0.002
274823ROCKFORD ;21
Adder
21.377
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971171AH1-044 GEN
Solar/Wind Harmer
15.301
971675AH1-338 GEN
Solar/Wind Harmer
2.979
945581AF1-223 GEN
Solar/Wind Harmer
0.001
274746AC1-111 G10
Adder
6.069
274744AC1-111 GEN8
Adder
6.069
23750501ELLIOTTS
Solar/Wind Helper
0.635
238126S14_GEN_1
Solar/Wind Helper
0.687
238109AE1-109 GEN2
Solar/Wind Helper
0.088
238110AE1-109 GEN3
Solar/Wind Helper
0.088
20092526R32
Solar/Wind Helper
1.053
24289405MTG1
50/50
11.79
243186AF1-051 GEN
50/50
12.748
24318705GVG2
50/50
11.866
24721805FLATG3
50/50
2.714
24721705FLATG2
50/50
49.755
24723205RIVRG3
Adder
37.637
24686105CER G3
Adder
16.224
24686505CER G6
Adder
16.203
971403AH1-188 GEN
Solar/Wind Harmer
18.202
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
970947AG2-589 GEN
Solar/Wind Harmer
0.42
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
24728305BUCHG2
Adder
7.763
971687AH1-348 GEN
Solar/Wind Harmer
1.161
971329AH1-144 GEN
Solar/Wind Harmer
9.676
971315AH1-136 GEN
Solar/Wind Harmer
2.301
24735205WLF2G2
Adder
9.002
927014AC1-188 GEN
Solar/Wind Harmer
0.006
971367AH1-164 GEN
Solar/Wind Harmer
3.536
270336AE1-100 GEN
Solar/Wind Harmer
0.005
970091AG2-072 GEN
Adder
103.033
970333AG2-219 GEN
Solar/Wind Harmer
6.64
3429241JKCT 3G
Adder
15.723
971821AH1-427 GEN
Solar/Wind Harmer
9.259
3429421JKCT 10G
Adder
10.993
945681AF1-233 GEN
Solar/Wind Harmer
17.357
970273AG2-179 GEN
Solar/Wind Harmer
3.221
943811AF1-049 GEN
Solar/Wind Harmer
-0.002
339216AC1-074 GEN
Solar/Wind Harmer
0.25
971565AH1-281 GEN
Solar/Wind Harmer
1.817
964901AG1-354 GEN
Solar/Wind Harmer
13.566
962241AG1-070 GEN
Solar/Wind Harmer
4.9
252507AC2-088 GEN
Solar/Wind Harmer
0.405
25196808ZIMRHP
Adder
95.812
25196008MFTGT1
Adder
1.747
270445AC2-157 GEN2
Solar/Wind Harmer
0.004
25194608D.CRK4
Adder
2.039
270018AE2-047 C O1
Solar/Wind Harmer
0.004
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
8.469
270263AC1-001 GEN
Solar/Wind Harmer
0.833
24728605AND G2
Adder
4.525
962761AG1-125 GEN
Solar/Wind Harmer
32.213
970149AG2-104 GEN
Solar/Wind Harmer
34.791
970155AG2-107 GEN
Solar/Wind Harmer
20.57
270197AD1-017 GEN1
Solar/Wind Harmer
1.016
3147312GRETNA
Solar/Wind Harmer
0.031
941821AE2-187 GEN
Solar/Wind Harmer
4.925
970773AG2-487 GEN
Solar/Wind Harmer
1.447
963741AG1-226 GEN
Solar/Wind Harmer
19.103
965911AG1-460 GEN
Solar/Wind Harmer
1.613
276615X2-022 GEN
Solar/Wind Harmer
0.084
963831AG1-236 GEN
Solar/Wind Harmer
3.11
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0.001
970613AG2-401 GEN
Solar/Wind Harmer
5.842
274880W4-005 GEN4
Solar/Wind Harmer
0.001
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
276903AD2-071 C
Solar/Wind Harmer
8.845
972175AH1-670 GEN
Solar/Wind Harmer
6.537
24791305MDL-5G
Solar/Wind Harmer
0.001
970291AG2-192 GEN
Solar/Wind Harmer
1.021
270032AE2-172
Solar/Wind Harmer
5.233
274854TWINGROVE;U2
Solar/Wind Harmer
0.003
270005AE1-210 C O1
Solar/Wind Harmer
1.696
965031AG1-367 GEN
Solar/Wind Harmer
7.829
970825AG2-519 GEN
Solar/Wind Harmer
2.773
276726Z2-087_GEN
Solar/Wind Harmer
0.003
939741AE1-205 GEN
Solar/Wind Harmer
10.926
253370AE2-315 SEC1
Adder
2.238
253371AE2-315 SEC2
Adder
2.117
274877BISHOP HL;1U
Solar/Wind Harmer
0.26
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
9.649
276158O29GEN2
Solar/Wind Harmer
0.001
274857EASY ROAD;U1
Solar/Wind Harmer
0.002
274761LEE CO EC;2U
Adder
10.252
274766LEE CO EC;7U
Adder
10.131
970569AG2-363 GEN
Solar/Wind Harmer
23.052
971475AH1-234 GEN
Solar/Wind Harmer
3.722
970819AG2-516 GEN
Solar/Wind Harmer
9.198
972235AH1-702 GEN1
Adder
2.767
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
960071AF2-298 GEN
Solar/Wind Harmer
3.815
25326309TAIT D
Adder
1.202
274822ROCKFORD ;11
Adder
21.533
957471AF2-041 GEN
Solar/Wind Harmer
22.952
959081AF2-199 GEN
Solar/Wind Harmer
7.651
971067AG2-660 GEN
Solar/Wind Harmer
2.55
939401AE1-172 GEN
Solar/Wind Harmer
5.72
971997AH1-543 GEN
Solar/Wind Harmer
4.011
276861AD2-134 GEN
Solar/Wind Harmer
0.137
945371AF1-202 GEN
Solar/Wind Harmer
0.001
274828WAUKEGAN ;BP
Adder
12.03
274682WAUKEGAN ;7U
Adder
19.567
274745AC1-111 GEN9
Adder
6.069
238185AF2-356 C
Solar/Wind Helper
2.176
237046AF1-021 C
Solar/Wind Helper
0.457
235054AD2-180 GEN
Solar/Wind Helper
1.695
238117U2-030
Solar/Wind Helper
0.288
235531U2-073 GEN
Solar/Wind Helper
2.733
23751201ROTHROCK
Solar/Wind Helper
0.71
23562501BACKB
Solar/Wind Helper
0.864
23583801GRNGAP
Solar/Wind Helper
4.088
316095T157 G97
Solar/Wind Helper
1.094
238108AE1-109 GEN1
Solar/Wind Helper
0.088
20089226LOOKOUT
Solar/Wind Helper
0.539
20088826HIGHLAND
Solar/Wind Helper
0.812
24289405MTG1
50/50
11.79
24318705GVG2
50/50
11.866
24722005FLATG5
50/50
2.714
24721905FLATG4
50/50
49.755
24686205CER G4
Adder
16.139
24686405CER G5
Adder
16.075
270053AF1-130 C
Solar/Wind Harmer
2.937
970913AG2-568 GEN
Solar/Wind Harmer
9.858
960911AF2-382 GEN
Solar/Wind Harmer
9.021
943031AE2-326 GEN
Solar/Wind Harmer
6.109
971461AH1-227 GEN
Solar/Wind Harmer
5.958
972103AH1-617 GEN
Solar/Wind Harmer
23.212
971331AH1-145 GEN
Solar/Wind Harmer
15.359
247619Y1-049
Adder
0.704
971191AH1-055 GEN
Solar/Wind Harmer
29.418
270346AE1-212 GEN
Solar/Wind Harmer
10.08
958121AF2-106 GEN
Solar/Wind Harmer
0.001
972273AH1-721 GEN
Adder
111.61
270030AE2-140 GEN
Solar/Wind Harmer
18.75
970093AG2-073 GEN
Solar/Wind Harmer
9.318
970243AG2-164 GEN
Solar/Wind Harmer
5.432
970519AG2-331 GEN
Solar/Wind Harmer
24.144
970699AG2-449 GEN
Solar/Wind Harmer
2.322
966571AG1-526 GEN
Solar/Wind Harmer
20.57
270173AC1-122 GEN
Solar/Wind Harmer
0.435
3429391JKCT 9G
Adder
10.993
970273AG2-179 GEN
Solar/Wind Harmer
5.522
972167AH1-666 GEN
Solar/Wind Harmer
7.359
962751AG1-124 GEN
Solar/Wind Harmer
8.092
339250AF1-203 GEN
Solar/Wind Harmer
0.001
971155AH1-034 GEN
Solar/Wind Harmer
10.521
960741AF2-365 GEN
Solar/Wind Harmer
4.499
962251AG1-071 GEN
Solar/Wind Harmer
5.619
958171AF2-111 GEN
Solar/Wind Harmer
22.442
270291AC1-194 GEN
Solar/Wind Harmer
7.02
25196008MFTGT1
Adder
1.692
252510AF1-249 C
Solar/Wind Harmer
0.067
25194608D.CRK4
Adder
2.039
25196608WSDLE5
Adder
10.598
253316AC1-085 GEN3
Solar/Wind Harmer
0.005
253433AC1-085 GEN1
Solar/Wind Harmer
0.004
946181AF1-283 GEN
Solar/Wind Harmer
11.009
253406AD2-031_GEN
Solar/Wind Harmer
0.624
970193AG2-126 GEN
Solar/Wind Harmer
12.39
24728705AND G3
Adder
9.464
24728505AND G1
Adder
4.525
970153AG2-106 GEN
Solar/Wind Harmer
20.57
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
3147312GRETNA
Solar/Wind Harmer
0.123
3146802CHATHAM
Solar/Wind Harmer
0.115
941801AE2-185 GEN
Solar/Wind Harmer
4.925
270356AE2-297 GEN
Solar/Wind Harmer
0.011
270222AC2-111 GEN
Solar/Wind Harmer
4.144
253415AE1-040 GEN
Solar/Wind Harmer
0.003
942481AE2-261 GEN
Solar/Wind Harmer
24.109
276621W2-048 GEN
Solar/Wind Harmer
0.403
276838X2-022 GEN2
Solar/Wind Harmer
0.45
270437AC2-090 C
Solar/Wind Harmer
0.004
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
3.68
276668AB2-070 GEN1
Solar/Wind Harmer
0.29
972173AH1-669 GEN
Solar/Wind Harmer
3.965
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
7.866
247642Z2-115 C
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
0.864
970291AG2-192 GEN
Solar/Wind Harmer
0.786
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
965091AG1-374 GEN
Solar/Wind Harmer
23.525
959611AF2-252 GEN
Solar/Wind Harmer
2.614
958821AF2-173 GEN
Solar/Wind Harmer
10.961
270004AE1-209 GEN
Solar/Wind Harmer
1.696
270273AD2-016 GEN
Solar/Wind Harmer
0.81
942111AE2-223 GEN
Solar/Wind Harmer
2.536
253370AE2-315 SEC1
Adder
2.238
253371AE2-315 SEC2
Adder
2.117
965931AG1-462 GEN
Solar/Wind Harmer
19.808
946031AF1-268 GEN
Solar/Wind Harmer
7.391
3147123OTTER R
Solar/Wind Harmer
0.087
274878BISHOP HL;2U
Solar/Wind Harmer
0.26
970191AG2-125 GEN
Solar/Wind Harmer
1.992
276157O29GEN1
Solar/Wind Harmer
1.248
274858EASY ROAD;U2
Solar/Wind Harmer
0.002
274760LEE CO EC;1U
Adder
10.252
274767LEE CO EC;8U
Adder
10.131
970571AG2-364 GEN
Solar/Wind Harmer
15.368
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
972236AH1-702 GEN2
Adder
2.406
276889AE2-281 GEN
Solar/Wind Harmer
0.001
270016AE1-250 BESS
Solar/Wind Harmer
0.004
959091AF2-200 GEN
Solar/Wind Harmer
15.301
274855GSG-6 ;RU
Solar/Wind Harmer
0.28
274850MENDOTA H;RU
Solar/Wind Harmer
0.09
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.137
274682WAUKEGAN ;7U
Adder
19.567
274729ELWOOD EC;1P
Adder
8.072
237048AF1-022 C
Solar/Wind Helper
0.182
964991AG1-363 GEN
Solar/Wind Helper
3.709
23750701CROSSCHOOL
Solar/Wind Helper
1.197
238118U2-030_1
Solar/Wind Helper
0.288
238127S14_GEN_2
Solar/Wind Helper
0.687
237043AE2-125 C
Solar/Wind Helper
0.163
202652Y1-033 WT C
Solar/Wind Helper
0.534
316097T157 G90
Solar/Wind Helper
1.094
20089126CSLMN_L13
Solar/Wind Helper
0.554
20089026BF_G21_K23
Solar/Wind Helper
0.438
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
0.329
944201AF1-088_MTX
Adder
145.184
957141AF2-008_MTX
Adder
72.592
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.592
CBM South 1LTFEXP_CBM-S1->PJM
CBM
47.815
MECLTFEXP_MEC->PJM
CLTF
19.173
SIGELTFEXP_SIGE->PJM
CLTF
0.659
LAGNLTFEXP_LAGN->PJM
CLTF
24.37
CBM South 2LTFEXP_CBM-S2->PJM
CBM
29.03
TVALTFEXP_TVA->PJM
CLTF
12.655
CPLELTFEXP_CPLE->PJM
CLTF
7.791
CBM West 2LTFEXP_CBM-W2->PJM
CBM
162.06
NYPJM->LTFIMP_NY
CLTF
5.271
LGEELTFEXP_LGEE->PJM
CLTF
8.989
WECLTFEXP_WEC->PJM
CLTF
4.2
AG2-052LTFEXP_AG2-052->PJM
LTF
0.253
AH1-155LTFEXP_AH1-155->PJM
LTF
0.38

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P7-1_#10944___SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10944___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:106.16 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5863.47
MW Contribution:13.74
Bus #Bus NameTypeMW Contribution
243186AF1-051 GEN
50/50
12.611
24723005RIVRG1
Adder
37.09
24723105RIVRG2
Adder
37.09
24685805CER G1
Adder
16.156
24685905CER G2
Adder
16.156
944971AF1-162 GEN
Solar/Wind Harmer
12.489
24728205BUCHG1
Adder
6.985
971225AH1-072 GEN
Solar/Wind Harmer
3.044
971227AH1-073 GEN
Solar/Wind Harmer
3.044
270214AC2-123 GEN
Solar/Wind Harmer
3.214
971277AH1-098 GEN
Solar/Wind Harmer
5.494
970879AG2-548 GEN
Solar/Wind Harmer
8.094
971073AG2-665 GEN
Solar/Wind Harmer
8.094
971073AG2-665 GEN
Solar/Wind Harmer
5.647
270583AD2-179 GEN
Solar/Wind Harmer
12.914
960161AF2-307 GEN
Solar/Wind Harmer
8.235
270186AC1-089 GEN
Solar/Wind Harmer
7.622
962581AG1-107 GEN
Solar/Wind Harmer
6.151
961491AF2-440 GEN
Solar/Wind Harmer
2.556
970239AG2-162 GEN
Solar/Wind Harmer
13.403
942891AE2-308 GEN
Solar/Wind Harmer
12.168
972043AH1-570 GEN
Solar/Wind Harmer
3.032
972045AH1-571 GEN
Solar/Wind Harmer
2.426
339221AD2-048_GEN
Solar/Wind Harmer
1.861
971125AH1-004 GEN
Solar/Wind Harmer
4.815
970107AG2-081 GEN
Solar/Wind Harmer
3.611
970235AG2-159 GEN
Solar/Wind Harmer
4.78
970235AG2-159 GEN
Solar/Wind Harmer
2.918
339231AF1-038_GEN
Solar/Wind Harmer
2.165
966021AG1-471 GEN
Solar/Wind Harmer
6.404
971485AH1-239 GEN
Solar/Wind Harmer
9.472
252509AD1-136 GEN
Solar/Wind Harmer
0.303
971081AG2-670 GEN
Solar/Wind Harmer
8.855
970653AG2-424 GEN
Solar/Wind Harmer
5.682
970653AG2-424 GEN
Solar/Wind Harmer
2.054
339236AF1-050_GEN
Solar/Wind Harmer
2.132
964571AG1-320 GEN
Solar/Wind Harmer
9.614
339255AE2-071 GEN
Solar/Wind Harmer
1.239
964781AG1-341 GEN
Solar/Wind Harmer
12.366
25183208HLCRTG
Solar/Wind Harmer
6.95
252519AF1-045_GEN
Solar/Wind Harmer
6.963
252516AE2-318_GEN
Solar/Wind Harmer
5.311
25194408D.CRK1
Adder
8.581
25194508D.CRK3
Adder
1.604
270444AC2-157 GEN1
Solar/Wind Harmer
6.293
253317AC1-085 GEN4
Solar/Wind Harmer
9.175
945391AF1-204 GEN
Solar/Wind Harmer
14.686
253394AE2-221_GEN
Solar/Wind Harmer
4.786
253398AE2-221_GEN2
Solar/Wind Harmer
4.786
24728805RICHG1
Adder
3.931
24728905RICHG2
Adder
3.931
276916AD2-100_GEN
Solar/Wind Harmer
21.483
276911AD2-131_GEN
Solar/Wind Harmer
4.342
970241AG2-163 GEN
Solar/Wind Harmer
25.567
957381AF2-032 GEN
Solar/Wind Harmer
0.427
253370AE2-315 SEC1
Adder
1.951
972267AH1-718 GEN
Adder
4.004
274764LEE CO EC;5U
Adder
8.939
274765LEE CO EC;6U
Adder
8.939
274762LEE CO EC;3U
Adder
8.918
274763LEE CO EC;4U
Adder
8.834
25322209TAIT E
Adder
9.264
25322209TAIT E
Adder
9.056
247621Y3-024
Adder
0.228
274683WAUKEGAN ;8U
Adder
19.896
274683WAUKEGAN ;8U
Adder
16.771
274696ROCKY RD ;4P
Adder
10.757
274695ROCKY RD ;2P
Adder
10.508
24289405MTG1
50/50
11.76
243186AF1-051 GEN
50/50
12.611
24318705GVG2
50/50
11.739
24721805FLATG3
50/50
2.658
24721705FLATG2
50/50
48.723
960001AF2-291 GEN
Solar/Wind Harmer
6.065
24723205RIVRG3
Adder
37.09
270331AC1-082 GEN3
Solar/Wind Harmer
0.892
970947AG2-589 GEN
Solar/Wind Harmer
3.922
24686105CER G3
Adder
16.263
24686505CER G6
Adder
16.242
971403AH1-188 GEN
Solar/Wind Harmer
24.803
24728305BUCHG2
Adder
6.985
971315AH1-136 GEN
Solar/Wind Harmer
3.105
927014AC1-188 GEN
Solar/Wind Harmer
2.455
971687AH1-348 GEN
Solar/Wind Harmer
1.523
24735205WLF2G2
Adder
7.999
971329AH1-144 GEN
Solar/Wind Harmer
16.096
970091AG2-072 GEN
Adder
94.679
970333AG2-219 GEN
Solar/Wind Harmer
38.461
945681AF1-233 GEN
Solar/Wind Harmer
22.966
3429241JKCT 3G
Adder
14.375
971821AH1-427 GEN
Solar/Wind Harmer
12.078
3429421JKCT 10G
Adder
10.046
943111AE2-339 GEN
Solar/Wind Harmer
1.064
339216AC1-074 GEN
Solar/Wind Harmer
2.018
970273AG2-179 GEN
Solar/Wind Harmer
2.912
971565AH1-281 GEN
Solar/Wind Harmer
2.371
24289405MTG1
50/50
11.76
24318705GVG2
50/50
11.739
24722005FLATG5
50/50
2.658
24721905FLATG4
50/50
48.723
24686205CER G4
Adder
16.177
24686405CER G5
Adder
16.113
270053AF1-130 C
Solar/Wind Harmer
6.632
971191AH1-055 GEN
Solar/Wind Harmer
39.064
970913AG2-568 GEN
Solar/Wind Harmer
13.469
960911AF2-382 GEN
Solar/Wind Harmer
11.728
957541AF2-048 GEN
Solar/Wind Harmer
2.449
972103AH1-617 GEN
Solar/Wind Harmer
30.886
971461AH1-227 GEN
Solar/Wind Harmer
7.809
270346AE1-212 GEN
Solar/Wind Harmer
13.257
943031AE2-326 GEN
Solar/Wind Harmer
5.058
971331AH1-145 GEN
Solar/Wind Harmer
12.477
247619Y1-049
Adder
0.564
958121AF2-106 GEN
Solar/Wind Harmer
5.853
970093AG2-073 GEN
Solar/Wind Harmer
12.205
970243AG2-164 GEN
Solar/Wind Harmer
31.468
970519AG2-331 GEN
Solar/Wind Harmer
21.141
970699AG2-449 GEN
Solar/Wind Harmer
13.986
972167AH1-666 GEN
Solar/Wind Harmer
9.735
972273AH1-721 GEN
Adder
101.075
966571AG1-526 GEN
Solar/Wind Harmer
26.852
270291AC1-194 GEN
Solar/Wind Harmer
12.828
3429391JKCT 9G
Adder
10.046
970273AG2-179 GEN
Solar/Wind Harmer
4.651
958171AF2-111 GEN
Solar/Wind Harmer
29.515
339250AF1-203 GEN
Solar/Wind Harmer
0.708
971155AH1-034 GEN
Solar/Wind Harmer
11.668
960741AF2-365 GEN
Solar/Wind Harmer
5.83
962251AG1-071 GEN
Solar/Wind Harmer
6.397
25196008MFTGT1
Adder
1.55
252510AF1-249 C
Solar/Wind Harmer
0.477
25194608D.CRK4
Adder
1.865
25196608WSDLE5
Adder
9.681
270030AE2-140 GEN
Solar/Wind Harmer
22.032
253316AC1-085 GEN3
Solar/Wind Harmer
9.175
253433AC1-085 GEN1
Solar/Wind Harmer
5.824
946181AF1-283 GEN
Solar/Wind Harmer
14.239
253406AD2-031_GEN
Solar/Wind Harmer
1.378
970193AG2-126 GEN
Solar/Wind Harmer
15.807
24728705AND G3
Adder
8.441
24728505AND G1
Adder
4.036
270356AE2-297 GEN
Solar/Wind Harmer
4.782
270222AC2-111 GEN
Solar/Wind Harmer
8.539
253415AE1-040 GEN
Solar/Wind Harmer
1.167
942481AE2-261 GEN
Solar/Wind Harmer
30.502
253370AE2-315 SEC1
Adder
1.951
253371AE2-315 SEC2
Adder
1.845
274760LEE CO EC;1U
Adder
8.918
274767LEE CO EC;8U
Adder
8.813
972236AH1-702 GEN2
Adder
2.091
274682WAUKEGAN ;7U
Adder
16.961
274729ELWOOD EC;1P
Adder
6.986
237048AF1-022 C
Solar/Wind Helper
0.187
235058AG1-386 C
Solar/Wind Helper
0.451
237043AE2-125 C
Solar/Wind Helper
0.173
254305AE2-115 C
Solar/Wind Helper
0.211
339241AF1-083 GEN
Solar/Wind Harmer
1.967
252507AC2-088 GEN
Solar/Wind Harmer
2.122
964901AG1-354 GEN
Solar/Wind Harmer
17.575
962241AG1-070 GEN
Solar/Wind Harmer
5.234
25196808ZIMRHP
Adder
88.001
25196008MFTGT1
Adder
1.601
25194608D.CRK4
Adder
1.865
270336AE1-100 GEN
Solar/Wind Harmer
1.949
270445AC2-157 GEN2
Solar/Wind Harmer
6.293
253432AC1-085 GEN2
Solar/Wind Harmer
0.293
946171AF1-282 GEN
Solar/Wind Harmer
10.953
971367AH1-164 GEN
Solar/Wind Harmer
3.823
943811AF1-049 GEN
Solar/Wind Harmer
4.073
270263AC1-001 GEN
Solar/Wind Harmer
1.114
24728605AND G2
Adder
4.036
963741AG1-226 GEN
Solar/Wind Harmer
46.021
965911AG1-460 GEN
Solar/Wind Harmer
1.423
962761AG1-125 GEN
Solar/Wind Harmer
40.758
253370AE2-315 SEC1
Adder
1.951
253371AE2-315 SEC2
Adder
1.845
274761LEE CO EC;2U
Adder
8.918
274766LEE CO EC;7U
Adder
8.813
972235AH1-702 GEN1
Adder
2.404
274822ROCKFORD ;11
Adder
18.707
25326309TAIT D
Adder
1.04
274828WAUKEGAN ;BP
Adder
10.429
274682WAUKEGAN ;7U
Adder
16.961
274745AC1-111 GEN9
Adder
5.257
237046AF1-021 C
Solar/Wind Helper
0.476
254303AC2-168 GEN
Solar/Wind Helper
0.153
241966AE1-183 GEN
Solar/Wind Helper
0.245
238185AF2-356 C
Solar/Wind Helper
2.079
23751201ROTHROCK
Solar/Wind Helper
0.699
235054AD2-180 GEN
Solar/Wind Helper
1.616
23562501BACKB
Solar/Wind Helper
0.85
20089226LOOKOUT
Solar/Wind Helper
0.545
238117U2-030
Solar/Wind Helper
0.272
20088826HIGHLAND
Solar/Wind Helper
0.835
235531U2-073 GEN
Solar/Wind Helper
2.555
20094526CT_V3-030
Solar/Wind Helper
0.44
964201AG1-281 GEN
Solar/Wind Helper
0.449
970149AG2-104 GEN
Solar/Wind Harmer
20.717
24721605FLATG1
50/50
2.658
270330AC1-082 GEN2
Solar/Wind Harmer
1.51
270329AC1-082 GEN1
Solar/Wind Harmer
0.889
972203AH1-686 GEN
Adder
4.44
24477305BRIDGE
Adder
0.635
957241AF2-018 GEN
Solar/Wind Harmer
7.929
270399AC1-101 GEN
Solar/Wind Harmer
7.483
270400AC1-102 GEN
Solar/Wind Harmer
7.483
941621AE2-160 GEN
Adder
5.566
970281AG2-184 GEN
Solar/Wind Harmer
32.43
972143AH1-644 GEN
Solar/Wind Harmer
15.443
270132AB1-180 C
Adder
0.184
971313AH1-133 GEN
Solar/Wind Harmer
15.282
971061AG2-657 GEN
Solar/Wind Harmer
13.752
971985AH1-537 GEN
Solar/Wind Harmer
26.909
962211AG1-066 GEN
Solar/Wind Harmer
3.527
24734705WLF1G3
Adder
8.169
24734805WLF1G4
Adder
8.169
24734905WLF1G5
Adder
8.169
24735105WLF2G1
Adder
7.999
966391AG1-508 GEN
Solar/Wind Harmer
4.787
970879AG2-548 GEN
Solar/Wind Harmer
5.647
971981AH1-535 GEN
Solar/Wind Harmer
12.632
270367AC2-061_GEN
Solar/Wind Harmer
3.956
972163AH1-664 GEN
Solar/Wind Harmer
12.214
972165AH1-665 GEN
Solar/Wind Harmer
9.771
965401AG1-405 GEN
Solar/Wind Harmer
6.93
965411AG1-406 GEN
Solar/Wind Harmer
3.11
3429211JKCT 2G
Adder
14.189
339211AE2-254 GEN
Solar/Wind Harmer
1.83
339243AC2-075 GEN1
Solar/Wind Harmer
0.546
970455AG2-298 GEN
Solar/Wind Harmer
7.102
25196108MFTGT2
Adder
1.765
25196108MFTGT2
Adder
1.639
252524AE2-267 GEN
Solar/Wind Harmer
1.782
25196408WSDLE3
Adder
9.966
25196308WSDLE2
Adder
9.88
25196208WSDLE1
Adder
9.855
25196708WSDLE6
Adder
9.83
25196508WSDLE4
Adder
9.582
270069AE2-166 C O1
Solar/Wind Harmer
3.07
270340AC2-060 GEN
Solar/Wind Harmer
3.233
944031AF1-071 GEN
Solar/Wind Harmer
1.053
944221AF1-090 GEN
Solar/Wind Harmer
11.289
962771AG1-126 GEN
Solar/Wind Harmer
40.758
25306009OHH W.
Adder
2.813
253372AE2-315 SEC3
Adder
1.845
253372AE2-315 SEC3
Adder
1.845
274823ROCKFORD ;21
Adder
18.572
274746AC1-111 G10
Adder
5.257
274744AC1-111 GEN8
Adder
5.257
23750501ELLIOTTS
Solar/Wind Helper
0.642
254304AE2-114 C
Solar/Wind Helper
0.211
241997AF1-093 GEN
Solar/Wind Helper
0.245
241982AE2-343 S C
Solar/Wind Helper
0.214
20092526R32
Solar/Wind Helper
1.083
203846AF2-130 C
Solar/Wind Helper
0.425
238126S14_GEN_1
Solar/Wind Helper
0.64
203961AE2-224 GEN
Solar/Wind Helper
2.23
20091526CHSTN_FL
Solar/Wind Helper
0.54
20090526Q36
Solar/Wind Helper
0.964
203993AD2-133_GEN1
Solar/Wind Helper
0.964
202652Y1-033 WT C
Solar/Wind Helper
0.534
23750701CROSSCHOOL
Solar/Wind Helper
1.129
20089126CSLMN_L13
Solar/Wind Helper
0.56
20089026BF_G21_K23
Solar/Wind Helper
0.443
964991AG1-363 GEN
Solar/Wind Helper
3.463
238118U2-030_1
Solar/Wind Helper
0.272
203818AF1-086 GEN
Solar/Wind Helper
1.57
238127S14_GEN_2
Solar/Wind Helper
0.64
959441AF2-235 GEN
Solar/Wind Helper
0.22
274693ROCKY RD ;1P
Adder
10.405
274697ROCKY RD ;3P
Adder
2.855
23652301WDPWR_K20
Solar/Wind Helper
0.139
962101AG1-054 GEN
Solar/Wind Helper
0.626
241967AE2-285_GEN
Solar/Wind Helper
0.613
241801AE1-079 GEN
Solar/Wind Helper
0.238
241985AE1-237 GEN
Solar/Wind Helper
0.238
23585401KL_K28_T16
Solar/Wind Helper
1.223
203955AF1-039 C O1
Solar/Wind Helper
0.352
944781AF1-143 GEN
Solar/Wind Helper
2.323
946071AF1-272 GEN
Solar/Wind Helper
2.537
20083426SW_E13_K22
Solar/Wind Helper
0.052
20088926STNY CRK
Solar/Wind Helper
0.764
20084626FORWARD
Solar/Wind Helper
0.332
203940AF1-140 C
Solar/Wind Helper
0.368
238120AE2-309 GEN
Solar/Wind Helper
0.4
946381AF1-302 GEN
Solar/Wind Helper
0.207
20088626ARWF_N39
Solar/Wind Helper
1.121
20303426NA_O38_P22
Solar/Wind Helper
0.919
203853AF1-134 C O1
Solar/Wind Helper
0.443
944201AF1-088_MTX
Adder
131.041
957141AF2-008_MTX
Adder
65.52
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.529
CBM South 1LTFEXP_CBM-S1->PJM
CBM
42.883
MECLTFEXP_MEC->PJM
CLTF
16.832
SIGELTFEXP_SIGE->PJM
CLTF
0.595
LAGNLTFEXP_LAGN->PJM
CLTF
21.71
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.108
TVALTFEXP_TVA->PJM
CLTF
11.299
CPLELTFEXP_CPLE->PJM
CLTF
7.285
CBM West 2LTFEXP_CBM-W2->PJM
CBM
144.471
NYPJM->LTFIMP_NY
CLTF
5.029
LGEELTFEXP_LGEE->PJM
CLTF
8.22
WECLTFEXP_WEC->PJM
CLTF
3.65
AG2-052LTFEXP_AG2-052->PJM
LTF
0.22
AH1-155LTFEXP_AH1-155->PJM
LTF
0.329

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P7-1_#10856___SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10856___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:102.19 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5644.14
MW Contribution:13.87
Bus #Bus NameTypeMW Contribution
24289405MTG1
50/50
11.814
243186AF1-051 GEN
50/50
12.674
24318705GVG2
50/50
11.798
24721805FLATG3
50/50
2.672
24721705FLATG2
50/50
48.99
960001AF2-291 GEN
Solar/Wind Harmer
6.103
24723205RIVRG3
Adder
37.324
270331AC1-082 GEN3
Solar/Wind Harmer
0.897
970947AG2-589 GEN
Solar/Wind Harmer
3.947
24686105CER G3
Adder
16.366
24686505CER G6
Adder
16.345
971403AH1-188 GEN
Solar/Wind Harmer
24.977
24728305BUCHG2
Adder
7.041
971315AH1-136 GEN
Solar/Wind Harmer
3.129
927014AC1-188 GEN
Solar/Wind Harmer
2.475
971687AH1-348 GEN
Solar/Wind Harmer
1.535
24735205WLF2G2
Adder
8.071
971329AH1-144 GEN
Solar/Wind Harmer
16.245
970091AG2-072 GEN
Adder
95.631
970333AG2-219 GEN
Solar/Wind Harmer
38.852
945681AF1-233 GEN
Solar/Wind Harmer
23.2
3429241JKCT 3G
Adder
14.522
971821AH1-427 GEN
Solar/Wind Harmer
12.202
3429421JKCT 10G
Adder
10.15
943111AE2-339 GEN
Solar/Wind Harmer
1.075
339216AC1-074 GEN
Solar/Wind Harmer
2.039
970273AG2-179 GEN
Solar/Wind Harmer
2.943
971565AH1-281 GEN
Solar/Wind Harmer
2.396
339241AF1-083 GEN
Solar/Wind Harmer
1.988
252507AC2-088 GEN
Solar/Wind Harmer
2.144
964901AG1-354 GEN
Solar/Wind Harmer
17.761
962241AG1-070 GEN
Solar/Wind Harmer
5.29
25196808ZIMRHP
Adder
88.943
25196008MFTGT1
Adder
1.618
25194608D.CRK4
Adder
1.886
270336AE1-100 GEN
Solar/Wind Harmer
1.97
270445AC2-157 GEN2
Solar/Wind Harmer
6.363
253432AC1-085 GEN2
Solar/Wind Harmer
0.297
946171AF1-282 GEN
Solar/Wind Harmer
11.077
971367AH1-164 GEN
Solar/Wind Harmer
3.867
943811AF1-049 GEN
Solar/Wind Harmer
4.12
270263AC1-001 GEN
Solar/Wind Harmer
1.127
24728605AND G2
Adder
4.084
963741AG1-226 GEN
Solar/Wind Harmer
46.579
965911AG1-460 GEN
Solar/Wind Harmer
1.441
962761AG1-125 GEN
Solar/Wind Harmer
41.255
253370AE2-315 SEC1
Adder
1.976
253371AE2-315 SEC2
Adder
1.869
274761LEE CO EC;2U
Adder
9.033
274766LEE CO EC;7U
Adder
8.927
972235AH1-702 GEN1
Adder
2.436
274822ROCKFORD ;11
Adder
18.951
25326309TAIT D
Adder
1.054
274828WAUKEGAN ;BP
Adder
10.566
274682WAUKEGAN ;7U
Adder
17.184
274745AC1-111 GEN9
Adder
5.326
237046AF1-021 C
Solar/Wind Helper
0.471
254303AC2-168 GEN
Solar/Wind Helper
0.151
241966AE1-183 GEN
Solar/Wind Helper
0.242
238185AF2-356 C
Solar/Wind Helper
2.051
23751201ROTHROCK
Solar/Wind Helper
0.69
235054AD2-180 GEN
Solar/Wind Helper
1.594
23562501BACKB
Solar/Wind Helper
0.838
20089226LOOKOUT
Solar/Wind Helper
0.537
238117U2-030
Solar/Wind Helper
0.268
20088826HIGHLAND
Solar/Wind Helper
0.824
235531U2-073 GEN
Solar/Wind Helper
2.519
24721605FLATG1
50/50
2.672
270330AC1-082 GEN2
Solar/Wind Harmer
1.52
270329AC1-082 GEN1
Solar/Wind Harmer
0.895
972203AH1-686 GEN
Adder
4.469
24477305BRIDGE
Adder
0.639
957241AF2-018 GEN
Solar/Wind Harmer
7.983
270399AC1-101 GEN
Solar/Wind Harmer
7.536
270400AC1-102 GEN
Solar/Wind Harmer
7.536
941621AE2-160 GEN
Adder
5.607
970281AG2-184 GEN
Solar/Wind Harmer
32.691
972143AH1-644 GEN
Solar/Wind Harmer
15.567
270132AB1-180 C
Adder
0.186
971313AH1-133 GEN
Solar/Wind Harmer
15.406
971061AG2-657 GEN
Solar/Wind Harmer
13.864
971985AH1-537 GEN
Solar/Wind Harmer
27.131
962211AG1-066 GEN
Solar/Wind Harmer
3.557
24734705WLF1G3
Adder
8.24
24734805WLF1G4
Adder
8.24
24734905WLF1G5
Adder
8.24
24735105WLF2G1
Adder
8.071
966391AG1-508 GEN
Solar/Wind Harmer
4.83
970879AG2-548 GEN
Solar/Wind Harmer
5.701
971981AH1-535 GEN
Solar/Wind Harmer
12.756
270367AC2-061_GEN
Solar/Wind Harmer
3.995
972163AH1-664 GEN
Solar/Wind Harmer
12.338
972165AH1-665 GEN
Solar/Wind Harmer
9.871
965401AG1-405 GEN
Solar/Wind Harmer
7.001
965411AG1-406 GEN
Solar/Wind Harmer
3.142
3429211JKCT 2G
Adder
14.334
339211AE2-254 GEN
Solar/Wind Harmer
1.849
339243AC2-075 GEN1
Solar/Wind Harmer
0.552
970455AG2-298 GEN
Solar/Wind Harmer
7.176
25196108MFTGT2
Adder
1.784
25196108MFTGT2
Adder
1.656
252524AE2-267 GEN
Solar/Wind Harmer
1.801
25196408WSDLE3
Adder
10.076
25196308WSDLE2
Adder
9.988
25196208WSDLE1
Adder
9.963
25196708WSDLE6
Adder
9.938
25196508WSDLE4
Adder
9.688
270069AE2-166 C O1
Solar/Wind Harmer
3.104
270340AC2-060 GEN
Solar/Wind Harmer
3.271
944031AF1-071 GEN
Solar/Wind Harmer
1.065
944221AF1-090 GEN
Solar/Wind Harmer
11.424
962771AG1-126 GEN
Solar/Wind Harmer
41.255
25306009OHH W.
Adder
2.849
253372AE2-315 SEC3
Adder
1.869
253372AE2-315 SEC3
Adder
1.869
274823ROCKFORD ;21
Adder
18.813
274746AC1-111 G10
Adder
5.326
274744AC1-111 GEN8
Adder
5.326
23750501ELLIOTTS
Solar/Wind Helper
0.635
254304AE2-114 C
Solar/Wind Helper
0.208
241997AF1-093 GEN
Solar/Wind Helper
0.242
241982AE2-343 S C
Solar/Wind Helper
0.211
20092526R32
Solar/Wind Helper
1.068
203846AF2-130 C
Solar/Wind Helper
0.419
238126S14_GEN_1
Solar/Wind Helper
0.631
203961AE2-224 GEN
Solar/Wind Helper
2.198
20091526CHSTN_FL
Solar/Wind Helper
0.532
20094526CT_V3-030
Solar/Wind Helper
0.433
964201AG1-281 GEN
Solar/Wind Helper
0.442
970149AG2-104 GEN
Solar/Wind Harmer
20.97
24289405MTG1
50/50
11.814
24318705GVG2
50/50
11.798
24722005FLATG5
50/50
2.672
24721905FLATG4
50/50
48.99
24686205CER G4
Adder
16.28
24686405CER G5
Adder
16.216
270053AF1-130 C
Solar/Wind Harmer
6.678
971191AH1-055 GEN
Solar/Wind Harmer
39.337
970913AG2-568 GEN
Solar/Wind Harmer
13.568
960911AF2-382 GEN
Solar/Wind Harmer
11.821
957541AF2-048 GEN
Solar/Wind Harmer
2.468
972103AH1-617 GEN
Solar/Wind Harmer
31.134
971461AH1-227 GEN
Solar/Wind Harmer
7.872
270346AE1-212 GEN
Solar/Wind Harmer
13.369
943031AE2-326 GEN
Solar/Wind Harmer
5.103
971331AH1-145 GEN
Solar/Wind Harmer
12.593
247619Y1-049
Adder
0.569
958121AF2-106 GEN
Solar/Wind Harmer
5.909
970093AG2-073 GEN
Solar/Wind Harmer
12.329
970243AG2-164 GEN
Solar/Wind Harmer
31.788
970519AG2-331 GEN
Solar/Wind Harmer
21.356
970699AG2-449 GEN
Solar/Wind Harmer
14.128
972167AH1-666 GEN
Solar/Wind Harmer
9.834
972273AH1-721 GEN
Adder
102.108
966571AG1-526 GEN
Solar/Wind Harmer
27.128
270291AC1-194 GEN
Solar/Wind Harmer
12.959
3429391JKCT 9G
Adder
10.15
970273AG2-179 GEN
Solar/Wind Harmer
4.7
958171AF2-111 GEN
Solar/Wind Harmer
29.825
339250AF1-203 GEN
Solar/Wind Harmer
0.715
971155AH1-034 GEN
Solar/Wind Harmer
11.792
960741AF2-365 GEN
Solar/Wind Harmer
5.892
962251AG1-071 GEN
Solar/Wind Harmer
6.465
25196008MFTGT1
Adder
1.567
252510AF1-249 C
Solar/Wind Harmer
0.482
25194608D.CRK4
Adder
1.886
25196608WSDLE5
Adder
9.788
270030AE2-140 GEN
Solar/Wind Harmer
22.282
253316AC1-085 GEN3
Solar/Wind Harmer
9.279
253433AC1-085 GEN1
Solar/Wind Harmer
5.89
946181AF1-283 GEN
Solar/Wind Harmer
14.4
253406AD2-031_GEN
Solar/Wind Harmer
1.394
970193AG2-126 GEN
Solar/Wind Harmer
15.993
24728705AND G3
Adder
8.541
24728505AND G1
Adder
4.084
270356AE2-297 GEN
Solar/Wind Harmer
4.839
270222AC2-111 GEN
Solar/Wind Harmer
8.641
253415AE1-040 GEN
Solar/Wind Harmer
1.181
942481AE2-261 GEN
Solar/Wind Harmer
30.873
253370AE2-315 SEC1
Adder
1.976
253371AE2-315 SEC2
Adder
1.869
274760LEE CO EC;1U
Adder
9.033
274767LEE CO EC;8U
Adder
8.927
972236AH1-702 GEN2
Adder
2.118
274682WAUKEGAN ;7U
Adder
17.184
274729ELWOOD EC;1P
Adder
7.078
237048AF1-022 C
Solar/Wind Helper
0.185
235058AG1-386 C
Solar/Wind Helper
0.446
237043AE2-125 C
Solar/Wind Helper
0.171
254305AE2-115 C
Solar/Wind Helper
0.208
202652Y1-033 WT C
Solar/Wind Helper
0.526
23750701CROSSCHOOL
Solar/Wind Helper
1.114
20089126CSLMN_L13
Solar/Wind Helper
0.552
20089026BF_G21_K23
Solar/Wind Helper
0.437
964991AG1-363 GEN
Solar/Wind Helper
3.415
238118U2-030_1
Solar/Wind Helper
0.268
203818AF1-086 GEN
Solar/Wind Helper
1.548
238127S14_GEN_2
Solar/Wind Helper
0.631
243186AF1-051 GEN
50/50
12.674
24723005RIVRG1
Adder
37.324
24723105RIVRG2
Adder
37.324
24685805CER G1
Adder
16.259
24685905CER G2
Adder
16.259
944971AF1-162 GEN
Solar/Wind Harmer
12.576
24728205BUCHG1
Adder
7.041
971225AH1-072 GEN
Solar/Wind Harmer
3.069
971227AH1-073 GEN
Solar/Wind Harmer
3.069
270214AC2-123 GEN
Solar/Wind Harmer
3.243
971277AH1-098 GEN
Solar/Wind Harmer
5.544
970879AG2-548 GEN
Solar/Wind Harmer
8.171
971073AG2-665 GEN
Solar/Wind Harmer
8.171
971073AG2-665 GEN
Solar/Wind Harmer
5.701
270583AD2-179 GEN
Solar/Wind Harmer
13.038
960161AF2-307 GEN
Solar/Wind Harmer
8.314
270186AC1-089 GEN
Solar/Wind Harmer
7.697
962581AG1-107 GEN
Solar/Wind Harmer
6.214
961491AF2-440 GEN
Solar/Wind Harmer
2.582
970239AG2-162 GEN
Solar/Wind Harmer
13.539
942891AE2-308 GEN
Solar/Wind Harmer
12.292
972043AH1-570 GEN
Solar/Wind Harmer
3.063
972045AH1-571 GEN
Solar/Wind Harmer
2.45
339221AD2-048_GEN
Solar/Wind Harmer
1.88
971125AH1-004 GEN
Solar/Wind Harmer
4.864
970107AG2-081 GEN
Solar/Wind Harmer
3.648
970235AG2-159 GEN
Solar/Wind Harmer
4.83
970235AG2-159 GEN
Solar/Wind Harmer
2.948
339231AF1-038_GEN
Solar/Wind Harmer
2.187
966021AG1-471 GEN
Solar/Wind Harmer
6.471
971485AH1-239 GEN
Solar/Wind Harmer
9.571
252509AD1-136 GEN
Solar/Wind Harmer
0.306
971081AG2-670 GEN
Solar/Wind Harmer
8.948
970653AG2-424 GEN
Solar/Wind Harmer
5.742
970653AG2-424 GEN
Solar/Wind Harmer
2.076
339236AF1-050_GEN
Solar/Wind Harmer
2.155
964571AG1-320 GEN
Solar/Wind Harmer
9.715
339255AE2-071 GEN
Solar/Wind Harmer
1.252
964781AG1-341 GEN
Solar/Wind Harmer
12.498
25183208HLCRTG
Solar/Wind Harmer
7.025
252519AF1-045_GEN
Solar/Wind Harmer
7.038
252516AE2-318_GEN
Solar/Wind Harmer
5.369
25194408D.CRK1
Adder
8.675
25194508D.CRK3
Adder
1.622
270444AC2-157 GEN1
Solar/Wind Harmer
6.363
253317AC1-085 GEN4
Solar/Wind Harmer
9.279
945391AF1-204 GEN
Solar/Wind Harmer
14.859
253394AE2-221_GEN
Solar/Wind Harmer
4.843
253398AE2-221_GEN2
Solar/Wind Harmer
4.843
24728805RICHG1
Adder
3.978
24728905RICHG2
Adder
3.978
276916AD2-100_GEN
Solar/Wind Harmer
21.743
276911AD2-131_GEN
Solar/Wind Harmer
4.394
970241AG2-163 GEN
Solar/Wind Harmer
25.877
957381AF2-032 GEN
Solar/Wind Harmer
0.432
253370AE2-315 SEC1
Adder
1.976
972267AH1-718 GEN
Adder
4.056
274764LEE CO EC;5U
Adder
9.055
274765LEE CO EC;6U
Adder
9.055
274762LEE CO EC;3U
Adder
9.033
274763LEE CO EC;4U
Adder
8.948
25322209TAIT E
Adder
9.385
25322209TAIT E
Adder
9.175
247621Y3-024
Adder
0.231
274683WAUKEGAN ;8U
Adder
20.157
274683WAUKEGAN ;8U
Adder
16.992
274696ROCKY RD ;4P
Adder
10.898
274695ROCKY RD ;2P
Adder
10.646
274693ROCKY RD ;1P
Adder
10.542
274697ROCKY RD ;3P
Adder
2.892
23652301WDPWR_K20
Solar/Wind Helper
0.138
962101AG1-054 GEN
Solar/Wind Helper
0.618
241985AE1-237 GEN
Solar/Wind Helper
0.235
241967AE2-285_GEN
Solar/Wind Helper
0.605
241801AE1-079 GEN
Solar/Wind Helper
0.235
23585401KL_K28_T16
Solar/Wind Helper
1.207
203955AF1-039 C O1
Solar/Wind Helper
0.347
944781AF1-143 GEN
Solar/Wind Helper
2.291
946071AF1-272 GEN
Solar/Wind Helper
2.502
20083426SW_E13_K22
Solar/Wind Helper
0.052
20088926STNY CRK
Solar/Wind Helper
0.754
20084626FORWARD
Solar/Wind Helper
0.327
203940AF1-140 C
Solar/Wind Helper
0.363
238120AE2-309 GEN
Solar/Wind Helper
0.394
944201AF1-088_MTX
Adder
132.484
957141AF2-008_MTX
Adder
66.242
CBM West 1LTFEXP_CBM-W1->PJM
CBM
123.346
CBM South 1LTFEXP_CBM-S1->PJM
CBM
43.356
MECLTFEXP_MEC->PJM
CLTF
17.041
SIGELTFEXP_SIGE->PJM
CLTF
0.602
LAGNLTFEXP_LAGN->PJM
CLTF
21.962
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.485
TVALTFEXP_TVA->PJM
CLTF
11.425
CPLELTFEXP_CPLE->PJM
CLTF
7.421
CBM West 2LTFEXP_CBM-W2->PJM
CBM
146.148
NYPJM->LTFIMP_NY
CLTF
4.949
LGEELTFEXP_LGEE->PJM
CLTF
8.306
WECLTFEXP_WEC->PJM
CLTF
3.698
AG2-052LTFEXP_AG2-052->PJM
LTF
0.222
AH1-155LTFEXP_AH1-155->PJM
LTF
0.334

Details for AG2-548 TP-05CORWIN 138.0 kV Ckt 1 line l/o AEP_P4_#9758_05LEMASTER 138_A1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AG2-548 TP-05CORWIN 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#9758_05LEMASTER 138_A1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:118.99 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:303.42
MW Contribution:90.0
Bus #Bus NameTypeMW Contribution
938711AE1-093 GEN
50/50
42
970879AG2-548 GEN
Solar/Wind Harmer
53.014
971073AG2-665 GEN
Solar/Wind Harmer
53.014
971073AG2-665 GEN
Solar/Wind Harmer
36.986
270291AC1-194 GEN
Solar/Wind Harmer
91.25
970879AG2-548 GEN
Solar/Wind Harmer
36.986

Details for AG2-548 TP-05CORWIN 138.0 kV Ckt 1 line l/o AEP_P4_#11182_05LEMASTER 138_A_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AG2-548 TP-05CORWIN 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#11182_05LEMASTER 138_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:118.99 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:303.42
MW Contribution:90.0
Bus #Bus NameTypeMW Contribution
938711AE1-093 GEN
50/50
42
970879AG2-548 GEN
Solar/Wind Harmer
53.014
971073AG2-665 GEN
Solar/Wind Harmer
53.014
971073AG2-665 GEN
Solar/Wind Harmer
36.986
270291AC1-194 GEN
Solar/Wind Harmer
91.25
970879AG2-548 GEN
Solar/Wind Harmer
36.986
CONTINGENCY 'AP_P2-3_WP-500-DRT10A_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235111 TO BUS 235117 CKT 1          /*01 502 J     500.0 - 01KAMMER     500.0
 OPEN BRANCH FROM BUS 235111 TO BUS 235113 CKT 2                /*01 502 J     500.0 - 01 502JCT    138.0
 SET POSTCONTRATING 4289 BRANCH FROM BUS 235111 TO BUS 314917 CKT 1 /*01 502 J     500.0 - 8MT STM      500.0
 SET PRECONTRATING 3546 BRANCH FROM BUS 235111 TO BUS 314917 CKT 1 /*01 502 J     500.0 - 8MT STM      500.0
 SET PRECONTRATING 3753 BRANCH FROM BUS 235111 TO BUS 235098 CKT 1 /*01 502 J     500.0 - WOODSIDE     500.0
END
CONTINGENCY 'AEP_P4_#8975_05KAMMER 765_MM2_SRT-A'
 OPEN BRANCH FROM BUS 235111 TO BUS 235117 CKT 1   /*01 502 J     500.0 - 01KAMMER     500.0
 OPEN BRANCH FROM BUS 235117 TO BUS 242925 CKT 1   /*01KAMMER     500.0 - 05KAMMER     765.0
END
CONTINGENCY 'AP_P2-3_WP-500-DRT7A_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235111 TO BUS 235117 CKT 1          /*01 502 J     500.0 - 01KAMMER     500.0
 SET POSTCONTRATING 4289 BRANCH FROM BUS 235111 TO BUS 314917 CKT 1 /*01 502 J     500.0 - 8MT STM      500.0
 SET PRECONTRATING 3546 BRANCH FROM BUS 235111 TO BUS 314917 CKT 1 /*01 502 J     500.0 - 8MT STM      500.0
 SET PRECONTRATING 3753 BRANCH FROM BUS 235111 TO BUS 235098 CKT 1 /*01 502 J     500.0 - WOODSIDE     500.0
END
CONTINGENCY 'AP_P1-2_MP-500-028_SRT-A'
 DISCONNECT BRANCH FROM BUS 235111 TO BUS 235117 CKT 1   /*01 502 J     500.0 - 01KAMMER     500.0
 DISCONNECT BRANCH FROM BUS 235117 TO BUS 242925 CKT 1   /*01KAMMER     500.0 - 05KAMMER     765.0
END
CONTINGENCY 'AP_P1-3_MP-765-502T_SRT-A'
 DISCONNECT BRANCH FROM BUS 235117 TO BUS 242925 CKT 1   /*01KAMMER     500.0 - 05KAMMER     765.0
END
CONTINGENCY 'AP_P2-3_MP-500-024_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235235 CKT 1   /*01BELMNT     500.0 - 01FLINTRUN   500.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 1   /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 2   /*01BELMNT     500.0 - 01BELMNT     138.0
END
CONTINGENCY 'AP_P2-3_MP-500-025_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235235 CKT 1   /*01BELMNT     500.0 - 01FLINTRUN   500.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 3   /*01BELMNT     500.0 - 01BELMNT     138.0
END
CONTINGENCY 'AP_P2-3_MP-500-014_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235235 CKT 1   /*01BELMNT     500.0 - 01FLINTRUN   500.0
 DISCONNECT BRANCH FROM BUS 235235 TO BUS 235100 CKT 1   /*01FLINTRUN   500.0 - 01FLINTRN    138.0
END
CONTINGENCY 'AP_P2-3_MP-500-015_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235235 CKT 1   /*01BELMNT     500.0 - 01FLINTRUN   500.0
 DISCONNECT BRANCH FROM BUS 235235 TO BUS 235100 CKT 2   /*01FLINTRUN   500.0 - 01FLINTRN    138.0
END
CONTINGENCY 'AP_P1-2_MP-500-007A_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235235 CKT 1   /*01BELMNT     500.0 - 01FLINTRUN   500.0
END
CONTINGENCY 'AP_P2-3_MP-500-012_SRT-A'
 DISCONNECT BRANCH FROM BUS 235107 TO BUS 235235 CKT 1   /*01HARRSN     500.0 - 01FLINTRUN   500.0
 DISCONNECT BRANCH FROM BUS 235107 TO BUS 235703 CKT 1   /*01HARRSN     500.0 - 01WYLIE R    500.0
END
CONTINGENCY 'AP_P1-2_MP-500-008A_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235235 TO BUS 235107 CKT 1          /*01FLINTRUN   500.0 - 01HARRSN     500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235107 TO BUS 235703 CKT 1 /*01HARRSN     500.0 - 01WYLIE R    500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235107 TO BUS 235703 CKT 1 /*01HARRSN     500.0 - 01WYLIE R    500.0
END
CONTINGENCY 'AP_P1-3_MP-765-501T_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1   /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                   /*05BELMON     765.0
END
CONTINGENCY 'AP_P2-3_MP-500-020_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 1          /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 2          /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5          /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1          /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1          /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                          /*05BELMON     765.0
 SET POSTCONTRATING 2492 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
 SET PRECONTRATING 1986 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
END
CONTINGENCY 'AP_P2-3_MP-500-021_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 3          /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5          /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1          /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1          /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                          /*05BELMON     765.0
 SET POSTCONTRATING 2492 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
 SET PRECONTRATING 1986 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
END
CONTINGENCY 'AEP_P4_#37_05MOUNTN 765_B1_SRT-A'
 OPEN BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242516 TO BUS 242920 CKT 1   /*05MOUNTN     765.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
END
CONTINGENCY 'AEP_P4_#2942_05KAMMER 765_PP_SRT-A'
 OPEN BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242516 TO BUS 242920 CKT 1   /*05MOUNTN     765.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
 OPEN BRANCH FROM BUS 242925 TO BUS 243188 CKT 1   /*05KAMMER     765.0 - 05MLG1        26.0
 REMOVE UNIT 1 FROM BUS 243188                     /*05MLG1        26.0
END
CONTINGENCY 'AEP_P4_#9672_05HARRISON 138_2W_SRT-A'
 OPEN BRANCH FROM BUS 243522 TO BUS 243593 CKT 1   /*05HARRISON   138.0 - 05ZUBER      138.0
END
CONTINGENCY 'AEP_P4_#9679_05HARRISON 138_2E_SRT-A'
 OPEN BRANCH FROM BUS 243522 TO BUS 243550 CKT 1   /*05HARRISON   138.0 - 05OBETZ      138.0
 OPEN BRANCH FROM BUS 243522 TO BUS 290162 CKT 2   /*05HARRISON   138.0 - 05HARRIS 2EQ   1.0
 OPEN BRANCH FROM BUS 243539 TO BUS 243550 CKT 1   /*05MARION RD  138.0 - 05OBETZ      138.0
END
CONTINGENCY 'AEP_P7-1_#10921___SRT-A'
 OPEN BRANCH FROM BUS 243522 TO BUS 243550 CKT 1   /*05HARRISON   138.0 - 05OBETZ      138.0
 OPEN BRANCH FROM BUS 243536 TO BUS 243539 CKT 1   /*05LS-II      138.0 - 05MARION RD  138.0
 OPEN BRANCH FROM BUS 243539 TO BUS 243550 CKT 1   /*05MARION RD  138.0 - 05OBETZ      138.0
END
CONTINGENCY 'AEP_P4_#9737_05MARION RD 138_4_SRT-A'
 OPEN BRANCH FROM BUS 243522 TO BUS 243550 CKT 1   /*05HARRISON   138.0 - 05OBETZ      138.0
 OPEN BRANCH FROM BUS 243539 TO BUS 243550 CKT 1   /*05MARION RD  138.0 - 05OBETZ      138.0
 OPEN BRANCH FROM BUS 243539 TO BUS 246714 CKT 6   /*05MARION RD  138.0 - 05MARN EQ6     1.0
 OPEN BRANCH FROM BUS 246708 TO BUS 246714 CKT 6   /*05MARION6L    13.8 - 05MARN EQ6     1.0
 OPEN BRANCH FROM BUS 246710 TO BUS 246714 CKT 6   /*05MARION 6    39.4 - 05MARN EQ6     1.0
END
CONTINGENCY 'AEP_P4_#9738_05MARION RD 138_5_SRT-A'
 OPEN BRANCH FROM BUS 243522 TO BUS 243550 CKT 1   /*05HARRISON   138.0 - 05OBETZ      138.0
 OPEN BRANCH FROM BUS 243539 TO BUS 243550 CKT 1   /*05MARION RD  138.0 - 05OBETZ      138.0
 OPEN BRANCH FROM BUS 243539 TO BUS 246713 CKT 5   /*05MARION RD  138.0 - 05MARN EQ5     1.0
 OPEN BRANCH FROM BUS 246709 TO BUS 246713 CKT 5   /*05MARION 5    39.4 - 05MARN EQ5     1.0
 OPEN BRANCH FROM BUS 246712 TO BUS 246713 CKT 5   /*05MARION5L    13.8 - 05MARN EQ5     1.0
END
CONTINGENCY 'AEP_P4_#8980_05KAMMER 765_QQ2_SRT-A'
 OPEN BRANCH FROM BUS 242925 TO BUS 290623 CKT Z1   /*05KAMMER     765.0 - 05KAMMER_RG  765.0
 OPEN BRANCH FROM BUS 246526 TO BUS 290623 CKT 1    /*05GUERNSEY   765.0 - 05KAMMER_RG  765.0
END
CONTINGENCY 'AEP_P1-2_#17217_SRT-A'
 OPEN BRANCH FROM BUS 242925 TO BUS 290623 CKT Z1   /*05KAMMER     765.0 - 05KAMMER_RG  765.0
 OPEN BRANCH FROM BUS 246526 TO BUS 290623 CKT 1    /*05GUERNSEY   765.0 - 05KAMMER_RG  765.0
END
CONTINGENCY 'AEP_P4_#7445_05MARYSV 765_B_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290621 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RF 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 962760 TO BUS 290621 CKT 1    /*AG1-125 TP   765.0 - 05MARYSVL_RF 765.0
END
CONTINGENCY 'AEP_P4_#17219_05GUERNSEY 765_A_SRT-A'
 OPEN BRANCH FROM BUS 242925 TO BUS 290623 CKT Z1   /*05KAMMER     765.0 - 05KAMMER_RG  765.0
 OPEN BRANCH FROM BUS 246526 TO BUS 246751 CKT 1    /*05GUERNSEY   765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 246526 TO BUS 290623 CKT 1    /*05GUERNSEY   765.0 - 05KAMMER_RG  765.0
END
CONTINGENCY 'AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1   /*05CLOVRD     500.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'AEP_P1-2_#7422_16_SRT-A'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1   /*05CLOVRD     500.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'AEP_P7-1_#10944___SRT-A'
 OPEN BRANCH FROM BUS 242528 TO BUS 242940 CKT 1   /*05SPORN      345.0 - 05MUSKNG     345.0
 OPEN BRANCH FROM BUS 242940 TO BUS 242947 CKT 1   /*05MUSKNG     345.0 - 05WATERFORD  345.0
END
CONTINGENCY 'AEP_P7-1_#10856___SRT-A'
 OPEN BRANCH FROM BUS 242528 TO BUS 242940 CKT 1   /*05SPORN      345.0 - 05MUSKNG     345.0
 OPEN BRANCH FROM BUS 242528 TO BUS 242947 CKT 1   /*05SPORN      345.0 - 05WATERFORD  345.0
END
CONTINGENCY 'AEP_P4_#9758_05LEMASTER 138_A1_SRT-A'
 OPEN BRANCH FROM BUS 242812 TO BUS 244283 CKT Z1   /*05MINERAL8   138.0 - 05MINERAL SS 138.0
 OPEN BRANCH FROM BUS 243476 TO BUS 244283 CKT 1    /*05BOLINSMLSS 138.0 - 05MINERAL SS 138.0
 OPEN BRANCH FROM BUS 243476 TO BUS 246684 CKT Z1   /*05BOLINSMLSS 138.0 - 05BOLINS ML8 138.0
 OPEN BRANCH FROM BUS 243476 TO BUS 247791 CKT 1    /*05BOLINSMLSS 138.0 - 05ELK        138.0
 OPEN BRANCH FROM BUS 244198 TO BUS 244283 CKT 1    /*05LEMASTER   138.0 - 05MINERAL SS 138.0
 OPEN BRANCH FROM BUS 244198 TO BUS 244569 CKT Z1   /*05LEMASTER   138.0 - 05LEMAST_CAP 138.0
END
CONTINGENCY 'AEP_P4_#11182_05LEMASTER 138_A_SRT-A'
 OPEN BRANCH FROM BUS 242812 TO BUS 244283 CKT Z1   /*05MINERAL8   138.0 - 05MINERAL SS 138.0
 OPEN BRANCH FROM BUS 243476 TO BUS 244283 CKT 1    /*05BOLINSMLSS 138.0 - 05MINERAL SS 138.0
 OPEN BRANCH FROM BUS 243476 TO BUS 246684 CKT Z1   /*05BOLINSMLSS 138.0 - 05BOLINS ML8 138.0
 OPEN BRANCH FROM BUS 243476 TO BUS 247791 CKT 1    /*05BOLINSMLSS 138.0 - 05ELK        138.0
 OPEN BRANCH FROM BUS 244198 TO BUS 244283 CKT 1    /*05LEMASTER   138.0 - 05MINERAL SS 138.0
 OPEN BRANCH FROM BUS 244198 TO BUS 247097 CKT Z1   /*05LEMASTER   138.0 - 05LEMASTERT1 138.0
 REMOVE LOAD D1 FROM BUS 247097                     /*05LEMASTERT1 138.0
END
235102 to 235235 ckt 1
235235 to 235107 ckt 1
235117 to 235111 ckt 1
242519 to 314912 ckt 1
243522 to 243550 ckt 1
243522 to 243593 ckt 1
242925 to 235117 ckt 1
242516 to 242920 ckt 1
970878 to 243492 ckt 1

Winter Peak Analysis

The New Service Request AG2-665 was evaluated as a 90.0 MW (54.0 MW Capacity) injection in the AEP area.

AG2-665 was evaluated as part of a plant. The plant consists of AG2-548, AG2-665. The total Energy output of the plant was evaluated at its maximum seasonal capability of 180.0 MW (288.0 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

(No impacts were found for this analysis)

Light Load Analysis

The New Service Request AG2-665 was evaluated as a 90.0 MW injection and 90.0 MW withdrawal in the AEP area.

AG2-665 was evaluated as part of a plant. The plant consists of AG2-548, AG2-665. The total Energy output of the plant was evaluated at its maximum seasonal capability of 180.0 MW (232.26 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AEP
05CORWIN-05MILTON SS 138.0 kV Ckt 1 line
AEP_P4_#9758_05LEMASTER 138_A1_SRT-A
BreakerAC106.02 %255.0B270.3690.0
GD2AEP
05CORWIN-05MILTON SS 138.0 kV Ckt 1 line
AEP_P4_#11182_05LEMASTER 138_A_SRT-A
BreakerAC106.02 %255.0B270.3690.0
GD2AEP
AG2-548 TP-05CORWIN 138.0 kV Ckt 1 line
AEP_P4_#9758_05LEMASTER 138_A1_SRT-A
BreakerAC112.94 %255.0B287.9990.0
GD2AEP
AG2-548 TP-05CORWIN 138.0 kV Ckt 1 line
AEP_P4_#11182_05LEMASTER 138_A_SRT-A
BreakerAC112.94 %255.0B287.9990.0

Details for 05CORWIN-05MILTON SS 138.0 kV Ckt 1 line l/o AEP_P4_#9758_05LEMASTER 138_A1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05CORWIN-05MILTON SS 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#9758_05LEMASTER 138_A1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.02 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:270.36
MW Contribution:90.0
Bus #Bus NameTypeMW Contribution
270291AC1-194 GEN
Solar/Wind Harmer
65
970879AG2-548 GEN
Solar/Wind Harmer
31.935
970879AG2-548 GEN
Solar/Wind Harmer
58.065
971073AG2-665 GEN
Solar/Wind Harmer
31.935
971073AG2-665 GEN
Solar/Wind Harmer
58.065
938711AE1-093 GEN
50/50
42

Details for 05CORWIN-05MILTON SS 138.0 kV Ckt 1 line l/o AEP_P4_#11182_05LEMASTER 138_A_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05CORWIN-05MILTON SS 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#11182_05LEMASTER 138_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.02 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:270.36
MW Contribution:90.0
Bus #Bus NameTypeMW Contribution
270291AC1-194 GEN
Solar/Wind Harmer
65
970879AG2-548 GEN
Solar/Wind Harmer
31.935
970879AG2-548 GEN
Solar/Wind Harmer
58.065
971073AG2-665 GEN
Solar/Wind Harmer
31.935
971073AG2-665 GEN
Solar/Wind Harmer
58.065
938711AE1-093 GEN
50/50
42

Details for AG2-548 TP-05CORWIN 138.0 kV Ckt 1 line l/o AEP_P4_#9758_05LEMASTER 138_A1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AG2-548 TP-05CORWIN 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#9758_05LEMASTER 138_A1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.94 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:287.99
MW Contribution:90.0
Bus #Bus NameTypeMW Contribution
270291AC1-194 GEN
Solar/Wind Harmer
65
970879AG2-548 GEN
Solar/Wind Harmer
31.935
970879AG2-548 GEN
Solar/Wind Harmer
58.065
971073AG2-665 GEN
Solar/Wind Harmer
31.935
971073AG2-665 GEN
Solar/Wind Harmer
58.065
938711AE1-093 GEN
50/50
42

Details for AG2-548 TP-05CORWIN 138.0 kV Ckt 1 line l/o AEP_P4_#11182_05LEMASTER 138_A_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AG2-548 TP-05CORWIN 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#11182_05LEMASTER 138_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.94 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:287.99
MW Contribution:90.0
Bus #Bus NameTypeMW Contribution
270291AC1-194 GEN
Solar/Wind Harmer
65
970879AG2-548 GEN
Solar/Wind Harmer
31.935
970879AG2-548 GEN
Solar/Wind Harmer
58.065
971073AG2-665 GEN
Solar/Wind Harmer
31.935
971073AG2-665 GEN
Solar/Wind Harmer
58.065
938711AE1-093 GEN
50/50
42
CONTINGENCY 'AEP_P4_#9758_05LEMASTER 138_A1_SRT-A'
 OPEN BRANCH FROM BUS 242812 TO BUS 244283 CKT Z1   /*05MINERAL8   138.0 - 05MINERAL SS 138.0
 OPEN BRANCH FROM BUS 243476 TO BUS 244283 CKT 1    /*05BOLINSMLSS 138.0 - 05MINERAL SS 138.0
 OPEN BRANCH FROM BUS 243476 TO BUS 246684 CKT Z1   /*05BOLINSMLSS 138.0 - 05BOLINS ML8 138.0
 OPEN BRANCH FROM BUS 243476 TO BUS 247791 CKT 1    /*05BOLINSMLSS 138.0 - 05ELK        138.0
 OPEN BRANCH FROM BUS 244198 TO BUS 244283 CKT 1    /*05LEMASTER   138.0 - 05MINERAL SS 138.0
 OPEN BRANCH FROM BUS 244198 TO BUS 244569 CKT Z1   /*05LEMASTER   138.0 - 05LEMAST_CAP 138.0
END
CONTINGENCY 'AEP_P4_#11182_05LEMASTER 138_A_SRT-A'
 OPEN BRANCH FROM BUS 242812 TO BUS 244283 CKT Z1   /*05MINERAL8   138.0 - 05MINERAL SS 138.0
 OPEN BRANCH FROM BUS 243476 TO BUS 244283 CKT 1    /*05BOLINSMLSS 138.0 - 05MINERAL SS 138.0
 OPEN BRANCH FROM BUS 243476 TO BUS 246684 CKT Z1   /*05BOLINSMLSS 138.0 - 05BOLINS ML8 138.0
 OPEN BRANCH FROM BUS 243476 TO BUS 247791 CKT 1    /*05BOLINSMLSS 138.0 - 05ELK        138.0
 OPEN BRANCH FROM BUS 244198 TO BUS 244283 CKT 1    /*05LEMASTER   138.0 - 05MINERAL SS 138.0
 OPEN BRANCH FROM BUS 244198 TO BUS 247097 CKT Z1   /*05LEMASTER   138.0 - 05LEMASTERT1 138.0
 REMOVE LOAD D1 FROM BUS 247097                     /*05LEMASTERT1 138.0
END
243492 to 243545 ckt 1
970878 to 243492 ckt 1

Short Circuit Analysis

Short Circuit analysis is not performed as part of the Phase I System Impact Study. Short Circuit analysis will commence in the Phase II System Impact Study.

Stability Analysis

Stability analysis is not performed as part of the Phase I System Impact Study. Stability analysis will commence in the Phase II System Impact Study.

Reactive Power Analysis

Reactive Power analysis is not performed as part of the Phase I System Impact Study. Reactive Power analysis will commence in the Phase II System Impact Study.

Steady-State Voltage Analysis

Steady State Voltage Analysis is Not Required.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-018Powerton-Goodings GroveIn Service
AA1-038Lexington-Low Moor 230kVUnder Construction
AA1-095Halfway-Marlowe 34.5kVIn Service
AA2-184Atlantic-Red Bank 34kVIn Service
AB1-001Absecon 12 kVIn Service
AB1-006Meadow Lake 345kVIn Service
AB1-027Old Church 34.5 KVIn Service
AB1-096Carroll-Mt. Airy 34.5kVIn Service
AB1-124Carroll-Monocacy 34.5kVPartially in Service - Under Construction
AB1-125Carroll-Monocacy 34.5kVIn Service
AB1-127St. Thomas-Guilford 34.5kVIn Service
AB1-128St. Thomas-Mercersburg 34.5kVIn Service
AB1-138Navy 34.5kVIn Service
AB1-139Metuchen 26kVIn Service
AB1-141Church-Wye Mills 138 kV IIn Service
AB1-142Church-Wye Mills 138 kV IIIn Service
AB1-176Price 25kV IIEngineering & Procurement
AB1-180Pine View 12kVIn Service
AB2-026Powhatan 34.5kVIn Service
AB2-029Remington 34.5kVIn Service
AB2-032Church-Wye Mills 138 kVIn Service
AB2-037Keeney-Steele 230kVUnder Construction
AB2-049Gloucester Township 12kVIn Service
AB2-067Kammer-Vassell 765kVIn Service
AB2-070Mt. Pulaski-BrokawIn Service
AB2-093Ormet 138kVIn Service
AB2-133Chestertown 69kVUnder Construction
AB2-135Church-Kent 69kVIn Service
AB2-136Cambridge-West Cambridge 69kVUnder Construction
AB2-153Church-Wye Mills 138 kVIn Service
AB2-157Prince George's County 12kVIn Service
AB2-158Louisa-South Anna 230kVIn Service
AB2-170East Lima-Marysville 345kVIn Service
AB2-179Townsend 138kVIn Service
AC1-001Delano 138kVIn Service
AC1-010Gloucester 26kVUnder Construction
AC1-017Levittown 13 kVIn Service
AC1-030Cinnaminson 13kVIn Service
AC1-033Kewanee 138 kVIn Service
AC1-042Altavista-Mt. Airy 69kVIn Service
AC1-044Kammer-Vassell 765kVIn Service
AC1-053Lanesville-BrokawPartially in Service - Under Construction
AC1-068Atlanta 69kV IIn Service
AC1-069Atlanta 69kV IIIn Service
AC1-074Jacksonville-Renaker 138kV IIn Service
AC1-075Perth-Hickory Grove 115kVIn Service
AC1-076Locust Grove-Paytes 115kVIn Service
AC1-078Beatty-London 138kVIn Service
AC1-082Ravenswood-Hemlock 69kVUnder Construction
AC1-085Stuart-Clinton 345kVIn Service
AC1-089Hillsboro-Wildcat 138kVIn Service
AC1-091Cedar Creek 138kV IEngineering & Procurement
AC1-092Cedar Creek 138kV IIEngineering & Procurement
AC1-093Cedar Creek 138kV IIIEngineering & Procurement
AC1-094Cedar Creek 138kV IVEngineering & Procurement
AC1-101Johns Creek-Excel 138kV ISuspended
AC1-102Johns Creek-Excel 138kV IISuspended
AC1-111Aurora 138kVIn Service
AC1-120Mitchell-Mountain Run 115kVEngineering & Procurement
AC1-121Mitchell-Mountain Run 115kVEngineering & Procurement
AC1-122Smith Mountain-Candler's Mountain 138kVIn Service
AC1-145Gretna DP 69 kVIn Service
AC1-158Spotsylvania 500kVIn Service
AC1-165Atlanta 69kV IIIIn Service
AC1-166Atlanta 69kV IVIn Service
AC1-167Mark Center 69kVUnder Construction
AC1-168Kewanee-StreatorSuspended
AC1-174Losantville 345kVIn Service
AC1-175Losantville 345kVIn Service
AC1-188Rio-Lick 138kVEngineering & Procurement
AC1-191Elmont 115kVEngineering & Procurement
AC1-194Elk 138kVActive
AC1-214Crescent RidgeIn Service
AC2-023Hebron 69kVEngineering & Procurement
AC2-029Circleville 138kVSuspended
AC2-044Maddox Creek 345kVSuspended
AC2-059Biers Run-Circleville 138kVIn Service
AC2-060Buckskin 69kVIn Service
AC2-061Hillsboro-Clinton 138kVIn Service
AC2-067Camden-Crystal I 69kVEngineering & Procurement
AC2-068Camden-Crystal II 69kVEngineering & Procurement
AC2-075Jacksonville-Renaker 138 kVIn Service
AC2-088S. Bethel-Brown 69kVIn Service
AC2-090Losantville 345kVIn Service
AC2-111College Corner 138kVEngineering & Procurement
AC2-120Ripley 69kVIn Service
AC2-123Jacksons Ferry 138kVIn Service
AC2-136East Hagerstown 12kVUnder Construction
AC2-157Sullivan 345 kVUnder Construction
AC2-165Bremo-Powhatan 230kVSuspended
AC2-168Clinton 23kVIn Service
AC2-176Jay 138 kVIn Service
AC2-186Harrington 25kVUnder Construction
AC2-187Harrington 69kVUnder Construction
AC2-188Harrington 69 kVUnder Construction
AC2-195Galion-Roberts South 138 kVUnder Construction
AD1-013Twombly Road 138kVEngineering & Procurement
AD1-017Smith Mountain-Bearskin 138 kVIn Service
AD1-020Hunterstown-Lincoln 115 kVIn Service
AD1-060Mercersburg-Milnor 34.5 kVIn Service
AD1-061McConnelsburg-Mercersburg 34 kVIn Service
AD1-100Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVUnder Construction
AD1-101Continental 69 kVIn Service
AD1-105Kings Dominion DP 115 kVUnder Construction
AD1-106North Waldo-Wild Creek 138 kVSuspended
AD1-115Mountain Run-Mitchell 115 kVEngineering & Procurement
AD1-119Payne 69 kVIn Service
AD1-128Modoc-Delaware 138 kVPartially in Service - Under Construction
AD1-130Hardin Switch 345 kVIn Service
AD1-136South Bethel-Brown 69 kVIn Service
AD1-140Greene-Clark 138 kVEngineering & Procurement
AD1-155Meadow Brook-Strasburg 138 kVIn Service
AD2-009McConnellsburg 138 kVIn Service
AD2-016Biers Run-Circleville 138 kVIn Service
AD2-020Valley 138 kVEngineering & Procurement
AD2-027Camden Switch 26 kVIn Service
AD2-031Martinsville-Wilmington 69 kVIn Service
AD2-038Powerton-Nevada 345 kVUnder Construction
AD2-042Camden Switch 26 kV IIIn Service
AD2-047Davis Creek 138 kVSuspended
AD2-048Cynthia-Headquarters 69 kVUnder Construction
AD2-058St. Barnabas 13 kVIn Service
AD2-060Davis Creek 138kVEngineering & Procurement
AD2-065Atco 12 kVIn Service
AD2-066Mazon-Crescent Ridge 138 kVEngineering & Procurement
AD2-067Centerburg 138kVEngineering & Procurement
AD2-070Gilbert-Morris Park 34.5kVIn Service
AD2-071Strawton-Deer Creek 138 kVSuspended
AD2-079Capitol Ave 34.5kVIn Service
AD2-086Hardin Switch 345 kVIn Service
AD2-092Marysville 345kVUnder Construction
AD2-093Marysville 345kVUnder Construction
AD2-096Marysville 345kVSuspended
AD2-100Kincaid-Pana 345 kVSuspended
AD2-115Lyons-Moselem 69kVIn Service
AD2-116Hokes-Grantley 69 kVIn Service
AD2-131Kincaid-Pana 345kVSuspended
AD2-133Eagle Valley 115kVIn Service
AD2-134Shady OaksPartially in Service - Under Construction
AD2-135Williamstown 12kVPartially in Service - Under Construction
AD2-163Broadview-Tangy 138 kVIn Service
AD2-172Lena 138kVIn Service
AD2-179Morgans Cut-Glen Lyn 138kVSuspended
AD2-180Elk Garden-Parr Run 138kVIn Service
AE1-040Greenfield 69 kVIn Service
AE1-041Edison 4kVIn Service
AE1-071Shade Gap-Roxbury 115 kVIn Service
AE1-075Powhatan 34.5 kVIn Service
AE1-079Maysville-Sharon 69 kVUnder Construction
AE1-081Landing 12.47 kVIn Service
AE1-090Hardin Switch 345 kVIn Service
AE1-091West Newton-Lynn 138 kVSuspended
AE1-092Blue Jacket-Kirby 138 kVActive
AE1-093Elk 138 kVSuspended
AE1-100Axton 138 kVIn Service
AE1-101McConnellsburg-Texas Eastern 138 kVIn Service
AE1-102Maddox Creek 345 kVSuspended
AE1-109Frenchs Mill 34 kVIn Service
AE1-113Mole Creek 345 kVEngineering & Procurement
AE1-114Maryland-Lancaster 138 kVActive
AE1-142Manitou-Pleasant Plains 34.5 kVIn Service
AE1-156Quakertown Solar II 34.5 kVPartially in Service - Under Construction
AE1-163Powerton-Nevada 345 kVEngineering & Procurement
AE1-166Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE1-170Kenzie Creek-Colby 138 kVSuspended
AE1-172Loretto-Wilton CenterActive
AE1-176Roanoke-Vinton 12 kV (Niagara Hydro)In Service
AE1-183Maysville-McDowell 69 kVEngineering & Procurement
AE1-185Hokes-Jackson 69 kVIn Service
AE1-196Hokes-Jackson 69 kV IIIn Service
AE1-205McLean 345 kVEngineering & Procurement
AE1-207Mississinewa-Gaston 138 kVSuspended
AE1-208Delaware-Van Buren 138 kVSuspended
AE1-209Desoto 345 kVSuspended
AE1-210Desoto 345 kVSuspended
AE1-212Grandview-Clifftop 138 kVSuspended
AE1-227South Cumberland 69 kVSuspended
AE1-229Deepwater-Upper Pittsgrove 138 kVSuspended
AE1-237Andover (Maysville) 69kV IUnder Construction
AE1-245Haviland 138 kVUnder Construction
AE1-250Smith Mountain-E. Danville 138 kVEngineering & Procurement
AE2-029Grottoes-Merck 115kVUnder Construction
AE2-035Lena 138 kVIn Service
AE2-042Milton 69 kVIn Service
AE2-045Olive-Reynolds 345 kVEngineering & Procurement
AE2-047Ridgeway-Solite 69 kVEngineering & Procurement
AE2-048Muskingum-W. Millersport 345 kVEngineering & Procurement
AE2-054Warfordsburg 34 kVIn Service
AE2-059Derry Tap-Derry Bus 69 kVIn Service
AE2-060Mifflintown Bus-Mifflintown Tap 69 kVIn Service
AE2-071Patton Rd-Summer Shade 69 kVIn Service
AE2-072East Leipsic-Richland 138 kVIn Service
AE2-089Pennville-Adams 138 kVEngineering & Procurement
AE2-092Kidds Store-Sherwood 115 kVEngineering & Procurement
AE2-113Farmers Valley-Ridgeway 115 kVUnder Construction
AE2-114Midland 23 kV IIn Service
AE2-115Midland 23 kV IIIn Service
AE2-117ABW Tap-Alexandria 46 kVSuspended
AE2-125Stahlstown-Ligonier 25 kVIn Service
AE2-126Dubois-Curwensville 34.5 kVIn Service
AE2-129Philipsburg-Clarence 34.5 kVIn Service
AE2-131Philipsburg-Karthaus 34.5Under Construction
AE2-133Penns Tap-Richfield Tie 69 kVIn Service
AE2-136Muskingum River-W. Millersport 345 kVEngineering & Procurement
AE2-139East Towanda-Grover 230 kVEngineering & Procurement
AE2-140Axton-Danville 138 kVSuspended
AE2-148Beatty-Greene 345 kVIn Service
AE2-152Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE2-160Kanawha River 138 kVEngineering & Procurement
AE2-166Stockton 138 kVSuspended
AE2-169Delaware-Van Buren 138 kVSuspended
AE2-172Mississinewa-Gaston 138 kVSuspended
AE2-173McLean 345 kVActive
AE2-175Jackson-Long Pond 69 kVPartially in Service - Under Construction
AE2-185Gladys DP-Stonemill Switching Station 69 kVActive
AE2-187Shockoe DP-Chatham 69 kVActive
AE2-206East Sidney-Quincy 138 kVIn Service
AE2-214Cole 345 kVEngineering & Procurement
AE2-217East Springfield-London 138 kVEngineering & Procurement
AE2-219Bluff Point-Randolph 138 kVSuspended
AE2-220Losantville 345 kVEngineering & Procurement
AE2-221Clinton-Stuart 345 kVUnder Construction
AE2-223McLean 345 kVActive
AE2-224Bear Rock-Johnstown 230 kVIn Service
AE2-226Millville-Old Chapel 138 kVEngineering & Procurement
AE2-230Bartonsville-Meadow Brook 138 kVIn Service
AE2-234Liberty Center-Buckeye Tap 69 kVEngineering & Procurement
AE2-236Columbia-Northeast 138 kVSuspended
AE2-254Garrard County-Tommy-Gooch 69 kVIn Service
AE2-255Molecreek 345 kVEngineering & Procurement
AE2-261Kincaid-Pana 345 kVActive
AE2-262Moshannon-Milesburg 230 kVEngineering & Procurement
AE2-263Moshannon-Milesburg 230 kV IIEngineering & Procurement
AE2-267Woodsdale 345 kVEngineering & Procurement
AE2-281Powerton-Nevada 345 kVEngineering & Procurement
AE2-283Gladys-Stone Mill 69 kVActive
AE2-285Maysville 69 kVEngineering & Procurement
AE2-291Grit DP-Perth 115 kVActive
AE2-297Madison-Tanners Creek 138 kVIn Service
AE2-298Cavett Switch - West Van Wert 69 kVEngineering & Procurement
AE2-305Givens-Mechanicsburg 138 kVEngineering & Procurement
AE2-306Gunn Road 345 kVUnder Construction
AE2-308Three Forks-Dale 138 kVActive
AE2-309Carlos Junction-Lonaconing 34.5 kVIn Service
AE2-315Yankee Tap 69 kVIn Service
AE2-318Ford-Cedarville 138 kVSuspended
AE2-321Belvidere-Marengo 138 kVActive
AE2-322Mark Center 69 kVUnder Construction
AE2-323Twin Branch-Guardian 138 kVUnder Construction
AE2-325Valley 138 kVActive
AE2-326Jacksons Ferry 138 kVEngineering & Procurement
AE2-339Avon 138 kVEngineering & Procurement
AE2-341Sandwich-Plano 138 kVActive
AE2-342Woodstock 69 kVEngineering & Procurement
AE2-343Andover (Maysville) 69 kV IIUnder Construction
AF1-006Fairview East 34.5 kVIn Service
AF1-007Indian River 230 kV ISuspended
AF1-021Bethelboro-Connellsville #1 25 kVIn Service
AF1-022Lake Lynn-Uniontown 25 kVIn Service
AF1-030Sandwich-Plano 138 kVActive
AF1-038Sewellton Jct-Webbs Crossroads 69 kVEngineering & Procurement
AF1-039Listonburg-Highpoint 24.9 kVIn Service
AF1-045Cedarville-Ford 138 kVSuspended
AF1-049Berry Hill 138 kVUnder Construction
AF1-050Summer Shade - Green County 161 kVEngineering & Procurement
AF1-051Gavin 765 kVIn Service
AF1-053Givens-Mechanicsburg 138 kVEngineering & Procurement
AF1-054Givens-Mechanicsburg 138 kVEngineering & Procurement
AF1-062Jug Street 138 kVEngineering & Procurement
AF1-071College Corner 138 kVEngineering & Procurement
AF1-078East Sidney-Quincy 138 kVIn Service
AF1-083Green County-Saloma 161 kVEngineering & Procurement
AF1-086Madera-Westover South 115 kVUnder Construction
AF1-088Sullivan 345 kVActive
AF1-090Kincaid-PanaEngineering & Procurement
AF1-091Varner - Sowers 138 kVEngineering & Procurement
AF1-092Huntington Jct. 138 kVSuspended
AF1-093Henderson-Stoneboro 69 kVEngineering & Procurement
AF1-094Union City-Cambridge Springs 34.5 kVEngineering & Procurement
AF1-098Four Mile Jct-Corry East 115 kVEngineering & Procurement
AF1-118Sorenson-Desoto 345 kVEngineering & Procurement
AF1-119Keystone-Desoto 345 kVEngineering & Procurement
AF1-122Cardington-Liberty 69 kVSuspended
AF1-130Inez 138 kVSuspended
AF1-134Philipsburg-Madera 34.5 kVEngineering & Procurement
AF1-136Warfordsburg-Purcell Junction 34.5 kVEngineering & Procurement
AF1-140Claysburg 23 kVEngineering & Procurement
AF1-143Lick Run 115 kVEngineering & Procurement
AF1-147Poland Rd-Runway DP 230kVUnder Construction
AF1-153Motion-Ridgeway 46 kVSuspended
AF1-158Edison-Gravel Pit 138 kVIn Service
AF1-162Inez 138 kVEngineering & Procurement
AF1-176Corey 138 kVActive
AF1-202Keystone-Desoto 345 kVUnder Construction
AF1-203Patton Rd-Summer Shade 69 kVIn Service
AF1-204Eugene 345 kVActive
AF1-207Reynolds-Olive #1 345 kVEngineering & Procurement
AF1-215Olive-Reynolds 345 kVIn Service
AF1-223Keystone-Desoto 345 kVUnder Construction
AF1-227Marysville – Gunn Road 345 kVIn Service
AF1-228Beatty-Greene 345 kVEngineering & Procurement
AF1-229Galion-South Berwick 345 kVEngineering & Procurement
AF1-233Flemingsburg – Spurlock 138kVActive
AF1-249Nickel 12.47 kVIn Service
AF1-254Milnor-Huyetts 34.5 kVUnder Construction
AF1-262Upper Pittsgrove 12 kVIn Service
AF1-264Runnemede 13 kVIn Service
AF1-268Desoto-Jay 138 kVEngineering & Procurement
AF1-272Lucerne 115 kVEngineering & Procurement
AF1-275Cole 345 kVEngineering & Procurement
AF1-282Stuart-Clinton 345 kVEngineering & Procurement
AF1-283Stuart-Clinton 345 kVEngineering & Procurement
AF1-285Gunn Road 345 kVUnder Construction
AF1-290Feagans Mill-Millville 138 kVIn Service
AF1-291ABartonsville-Meadow Brook 138 kVIn Service
AF1-296Garden Plain 138 kVActive
AF1-299Otter Point 34.5 kV IIn Service
AF1-300Otter Point 34.5 kV IIIn Service
AF1-302Brookville-Squab Hollow 138 kVEngineering & Procurement
AF1-320Merrill Creek 115 kVEngineering & Procurement
AF1-322Meadow Lake 345 kVEngineering & Procurement
AF1-331Twombley RoadEngineering & Procurement
AF1-333Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF1-337Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF1-338Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF1-339Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF2-008Sullivan 345 kVActive
AF2-014Maddox Creek 345 kVEngineering & Procurement
AF2-018Inez 138 kVEngineering & Procurement
AF2-032Kincaid 345 kVEngineering & Procurement
AF2-039Shawville-Clearfield 34.5 kVEngineering & Procurement
AF2-041Nelson-Electric Junction 345 kVActive
AF2-048Rio-Lick 138 kVEngineering & Procurement
AF2-068Jay 138 kVActive
AF2-069Crescent Ridge 138 kVActive
AF2-075Bartonsville-Meadow Brook 138 kV IIIIn Service
AF2-078Reynolds-Olive #1 345 kVEngineering & Procurement
AF2-083Kenzie Creek-Stone Lake 69 kVUnder Construction
AF2-086Scott Tap-Bowmans Mill Tap 69 kVEngineering & Procurement
AF2-088Shawville-Clearfield 34.5 kV IIEngineering & Procurement
AF2-095Davis Creek 138 kVActive
AF2-103Haviland 138 kVIn Service
AF2-106Hazel Hollow-Glen Lyn #1 138 kVEngineering & Procurement
AF2-107Clifford 138 kVEngineering & Procurement
AF2-111North Clark-Spurlock 345 kVActive
AF2-122Kirk 138 kVUnder Construction
AF2-130Cobalt Corners 34.5 kVIn Service
AF2-132Reynolds-Olive #1 345 kVUnder Construction
AF2-133Reynolds-Olive #2 345 kVUnder Construction
AF2-134Olive-Reynolds #2 345 kVIn Service
AF2-138Flanders-West Wharton 34.5 kVIn Service
AF2-139Gilbert-Warren Glen 34.5 kVIn Service
AF2-142Nevada 345 kVActive
AF2-143Powerton-Nevada 345 kVActive
AF2-144Powhatan 34.5 kVIn Service
AF2-149Sharp Road 69 kVEngineering & Procurement
AF2-150Galion 138 kVUnder Construction
AF2-162Keystone-Desoto 345 kVEngineering & Procurement
AF2-173Desoto 345 kVActive
AF2-177Sorenson-DeSoto #2 345 kVActive
AF2-192Frenchtown Solar-West Flemington 34.5 kVSuspended
AF2-199Nelson-Electric Junction 345 kVActive
AF2-200Nelson-Electric Junction 345 kVActive
AF2-205Olive-Reynolds #2 345 kVEngineering & Procurement
AF2-224Allen 345 kVEngineering & Procurement
AF2-225McLean 345 kVActive
AF2-229Roxbury 23 kVEngineering & Procurement
AF2-233Penns-Richfield Tie #1 69 kVEngineering & Procurement
AF2-234Sunbury Yard #1-Richfield Tie #2 69 kVEngineering & Procurement
AF2-235Titusville-Oil Creek 34.5 kVWithdrawn
AF2-238Mansfield-South Troy 34.5 kVEngineering & Procurement
AF2-247Bustleton 13.2 kVIn Service
AF2-250Edgewood 12 kV IIIIn Service
AF2-252Blue Mound 345 kVEngineering & Procurement
AF2-291Sporn South-Leon 138 kVEngineering & Procurement
AF2-298Crown-New Lebanon 69 kVEngineering & Procurement
AF2-307Hope-Belvins Valley Tap 69 kVActive
AF2-311Gilboa-Jones Branch 138 kVEngineering & Procurement
AF2-316Gilboa-Jones Branch 138 kV IIEngineering & Procurement
AF2-325Jacktown 12 kVEngineering & Procurement
AF2-335Delaware-Royerton 138 kVActive
AF2-350Kensington 138 kVActive
AF2-352Blue Mound 345 kVEngineering & Procurement
AF2-354Washington 34.5 kV IIEngineering & Procurement
AF2-356Albright-Mt. Zion 138 kVUnder Construction
AF2-359Olive-University Park 345 kVEngineering & Procurement
AF2-361Mifflintown Tap 69 kVEngineering & Procurement
AF2-365Munfordville KU Tap-Horse Cave Jct. 69 kVActive
AF2-371Harrison-Good Hope 138 kVEngineering & Procurement
AF2-378Cambridge 12 kVEngineering & Procurement
AF2-379Princess Anne 25 kVUnder Construction
AF2-382Hurley 69 kVEngineering & Procurement
AF2-383Tolna 115 kVWithdrawn
AF2-388Keystone-Desoto 345 kVActive
AF2-392Nelson-Dixon 138 kVActive
AF2-396Stinger 138 kVActive
AF2-417West Damascus Tap-West Damascus 69 kVEngineering & Procurement
AF2-421East Hazelton-Weatherly Tap 69Engineering & Procurement
AF2-424Reed-Reed Tap #1 69 kVEngineering & Procurement
AF2-425Reed-Reed Tap#1 69 kVEngineering & Procurement
AF2-433Columbia-Geisinger Tap #1 69 kVEngineering & Procurement
AF2-434Columbia-Geisinger Tap #1 69 kVEngineering & Procurement
AF2-440Hillsboro-Middleboro 138 kVEngineering & Procurement
AG1-017Jay 138 kVUnder Construction
AG1-024Centerburg 138 kVEngineering & Procurement
AG1-034Centerburg 138 kVEngineering & Procurement
AG1-039Galion 138 kV IIUnder Construction
AG1-040Morgan Street-Mount Hope 34.5 kVEngineering & Procurement
AG1-047Jay 138 kVEngineering & Procurement
AG1-054Potter-Harlan 69 kVEngineering & Procurement
AG1-066Bonnyman 69 kVEngineering & Procurement
AG1-070Bon Ayr 69 kVActive
AG1-071Bon Ayr 69 kVActive
AG1-100Venango-Saegertown 34.5 kVEngineering & Procurement
AG1-107Hillsboro-Middleboro 138 kVEngineering & Procurement
AG1-118Sugar Grove-Waterman 138kVActive
AG1-124Gladstone 138 kVActive
AG1-125Marysville-Flatlick 765 kVEngineering & Procurement
AG1-126Marysville-Flatlick 765 kVEngineering & Procurement
AG1-127Crego Rd 138 kVActive
AG1-156Jack Frost-Lake Harmony 69 kVEngineering & Procurement
AG1-164East Hazelton-Weatherly Tap 69 kVEngineering & Procurement
AG1-165East Hazelton-Weatherly Tap 69 kVEngineering & Procurement
AG1-188Manitou-Oyster Creek 34.5 kVEngineering & Procurement
AG1-189Oyster Creek-Bamber Lake 34.5Engineering & Procurement
AG1-191Chester-Pohatcong Mountain 34.5 kVPartially in Service - Under Construction
AG1-193Utica Junction 34.5 kVSuspended
AG1-197Morgan Street-Cochranton 34.5 kVSuspended
AG1-198Union City 34.5 kVUnder Construction
AG1-223Larrabee-Allaire 34.5 kVUnder Construction
AG1-226Dequine-Eugene 345 kVActive
AG1-232Magley 138 kVEngineering & Procurement
AG1-236Lanesville-Brokaw 345 kVActive
AG1-237Dequine-Eugene 345 kVEngineering & Procurement
AG1-254Salem-Woodstown 69 kVEngineering & Procurement
AG1-259Sunbury-Dalmatia 69 kVEngineering & Procurement
AG1-260Sunbury-Dalmatia 69 kVEngineering & Procurement
AG1-281Claysburg-HCR Tap 46 kVEngineering & Procurement
AG1-301Miller REC-Warrior Ridge 46 kVEngineering & Procurement
AG1-302Olive-Reynolds #1 345 kVUnder Construction
AG1-320Glendale-Stephensburg 69 kVActive
AG1-323Blue Jacket 138 kVActive
AG1-324Jay-Desoto 138 kVEngineering & Procurement
AG1-341Summer Shade 161 kVActive
AG1-348Pequest River-Washington 34.5 kVIn Service
AG1-349Olive-Reynolds #2 345 kVEngineering & Procurement
AG1-351Harrison-Good Hope 138 kVEngineering & Procurement
AG1-354Summershade-Green County 161 kVActive
AG1-363Black Oak-Hatfield 500 kVEngineering & Procurement
AG1-365Allen 345 kVEngineering & Procurement
AG1-366Allen 345 kVEngineering & Procurement
AG1-367DeSoto 345 kVActive
AG1-368Tillman 138 kVEngineering & Procurement
AG1-369Logtown 138 kVEngineering & Procurement
AG1-374Blue Mound 345 kVActive
AG1-375Sorenson-Desoto 345 kVActive
AG1-386Smith-Francis Junction 25 kVIn Service
AG1-397Walston 12 kVWithdrawn
AG1-405Walnut Grove-Asahi 69 kVActive
AG1-406Walnut Grove-Asahi 69 kVActive
AG1-410Maddox Creek-RP Mone 345 kVActive
AG1-414Mississinewa 138 kVEngineering & Procurement
AG1-433Keystone-DeSoto 345 kVActive
AG1-436Olive-University Park 345 kVActive
AG1-447Olive-University Park 345 kVActive
AG1-460Kincaid-Pana 345 kVActive
AG1-462Cordova 345 kVActive
AG1-469Gordonsville 34.5 kVEngineering & Procurement
AG1-471Up Church-Wayne County 69 kVActive
AG1-478Wilmington 34.5 kVEngineering & Procurement
AG1-480Shawnee 34.5 kVEngineering & Procurement
AG1-482Hamilton 115 kVWithdrawn
AG1-494Boxwood-Riverville 138 kVActive
AG1-495Gilbert-Rocktown 34.5 kVEngineering & Procurement
AG1-499Lambs 12.47 kVUnder Construction
AG1-508Point Lookout 69 kVEngineering & Procurement
AG1-526West Garrard 345 kVActive
AG1-554South Kenton 138 kVEngineering & Procurement
AG1-555Dequine 345 kVEngineering & Procurement
AG1-558Buckner 34.5 kVEngineering & Procurement
AG1-559Caroline Pines 22 kVEngineering & Procurement
AG2-029Forest G. Hipple-Collingwood 345 kVActive
AG2-057Cardington-Liberty 69 kV IIActive
AG2-063North Hampton 69 kVActive
AG2-072Rockport 765 kVActive
AG2-073Crooksville 69 kVActive
AG2-081Mt. Sterling-Fogg Pike 69 kVActive
AG2-085Delaware-Royerton 138 kVActive
AG2-104Marysville-Flatlick 765 kVActive
AG2-106Marysville-Flatlick 765 kVActive
AG2-107Marysville-Flatlick 765 kVActive
AG2-111Perth 34.5 kV Substation (Circuit 408)Active
AG2-112Perth 34.5 kV Substation (Circuit 404)Active
AG2-114Dresden-Pontiac Midpoint 345 kVActive
AG2-119Galion-Roberts South 138 kV IIActive
AG2-125Camden-Crystal 69 kVActive
AG2-126Eugene 345 kVActive
AG2-149Galion-South Berwick 345 kVActive
AG2-152Banister-Bear Skin 138 kVActive
AG2-159Williamstown 69 kVActive
AG2-162Jefferson-Greentown 765 kVActive
AG2-163Dequine-Eugene 345 kVActive
AG2-164Jefferson-Greentown 765 kVActive
AG2-165Dumont-Greentown 765 kVActive
AG2-179Sewellton Junction 69 kVActive
AG2-184Harbert Metering 138 kVActive
AG2-191Mississinewa 138 kVActive
AG2-192Mississinewa 138 kVActive
AG2-212Dumont-Greentown 765 kVActive
AG2-216East Sidney-Quincy 138 kVActive
AG2-219Jefferson-Greentown 765 kVActive
AG2-230Dumont 345 kVActive
AG2-245Olive - Reynolds #1 345 kVActive
AG2-298Sulphur Creek-Loretto 69 kVActive
AG2-310Matt Funk 138 kVActive
AG2-311Smith Mountain 138 kVActive
AG2-328Dumont - Greentown 765 kVActive
AG2-329S Berwick - Galion 345 kVActive
AG2-330Dumont - Greentown 765 kVActive
AG2-331Jefferson-Greentown 765 kVActive
AG2-360Broadford 138 kVActive
AG2-363Powerton 345 kVActive
AG2-364Powerton 345 kVActive
AG2-378North Hampton – Medway 69 kVActive
AG2-385North Hampton 69 kVActive
AG2-400Allen 345 kVActive
AG2-401Losantville 345 kVActive
AG2-405Continental 69 kVActive
AG2-406Payne 69 kVActive
AG2-408Allen 345 kVActive
AG2-424Magnolia - Summersville 69 kVActive
AG2-444Bixby - Biers Run 345 kVActive
AG2-449Jefferson-Greentown 765 kVActive
AG2-453Lasalle - Plano 345 kVActive
AG2-487Madison - Tanners Creek 138 kVActive
AG2-491Meadow Lake 345 kVActive
AG2-516Pecatonica 138kVActive
AG2-518Tech Drive 138 kVActive
AG2-519Royerton - Desoto 138 kVActive
AG2-524LaSalle Station - Mazon 138 kVActive
AG2-548Corwin - Elk 138 kVActive
AG2-550Bluff Point - Randolph 138 kVActive
AG2-551Bluff Point - Randolph 138 kVActive
AG2-568Stink Run – Sundial 138 kVActive
AG2-575Crego Rd. 138 kVActive
AG2-582Flint Run 500 kVActive
AG2-585Kensington 138kVActive
AG2-589Ravenswood - Hemlock 69 kVActive
AG2-637Randolph - Hodgin 138 kVActive
AG2-657Kanawha River - Carbondale 138 kVActive
AG2-660Nelson-Electric Junction 345 kVActive
AG2-670Green County -Taylor County Junction 161 kVActive
AH1-004Avon - Renaker 138 kVActive
AH1-034Patton Road Junction - Summer Shade 69 kVActive
AH1-044Nelson - Electric Junction 345 kVActive
AH1-047Marengo - Belvidere 138 kVActive
AH1-055Kyger Creek - Don Marquis 345 kVActive
AH1-059Sharp Road 69 kVActive
AH1-060Cardington-Liberty 69 kV IIIActive
AH1-072Red Onion - VC5 69 kVActive
AH1-073Red Onion - VC5 69 kVActive
AH1-075North Waldo - Wild Creek 138 kVActive
AH1-098Wolf Glade-West Carroll 138 kVActive
AH1-133Saltville - Tazewell 138 kVActive
AH1-136Falcon - Middle Creek 46 kVActive
AH1-144Peter's Mountain 138 kVActive
AH1-145Peter's Mountain 138 kVActive
AH1-146White Rock - Wayne 345 kVActive
AH1-147White Rock - Wayne 345 kVActive
AH1-150Nelson-Electric Junction 345 kVActive
AH1-151Nelson-Electric Junction 345 kVActive
AH1-153Dumont 345 kVActive
AH1-164Oak Level - Tank Hill 138 kVActive
AH1-188Pigeon Creek 138 kVActive
AH1-196Prairie 345 kVActive
AH1-227Flemming - Fremont 69 kVActive
AH1-234Wempletown - Paddock 345 kVActive
AH1-239Upchurch - Zula 69 kVActive
AH1-269Claytor 138 kVActive
AH1-272Argenta - Twin Branch 345 kVActive
AH1-281Bluegrass Parkway Tap - Woodlawn 69 kVActive
AH1-282Galion - Ohio Central 345 kVActive
AH1-285Sandwich 138 kVActive
AH1-292Sullivan 345 kVActive
AH1-302Olive - Reynolds 345 kVActive
AH1-304Delaware-Van Buren 138 kVActive
AH1-305Olive - Reynolds 345 kVActive
AH1-306Mississinewa-Gaston 138 kVActive
AH1-308Pennville - Adams 138 kVActive
AH1-309Kenzie Creek-Colby 138 kVActive
AH1-327Hardin Switch 345 kVActive
AH1-328Blue Jacket - Kirby 138 kVActive
AH1-337Randolph - Hodgin 138 kVActive
AH1-338McGirr Rd - Ritchie Road 138kVActive
AH1-339West Crawford 69 kVActive
AH1-341Stillman - Dixon 138KVActive
AH1-348Pound 34.5 kVActive
AH1-391Olive 138 kVActive
AH1-392Gravel Pit-Kankakee 138 kVActive
AH1-427Tommy Gooch - Garrard County 69 kVActive
AH1-482Olive - Reynolds #2 345 kVActive
AH1-535Nagel - Cane River 230 kVActive
AH1-537Pierce - Kyger Creek 345 kVActive
AH1-539South Kenton 138 kVActive
AH1-541Chestnut 345 kVActive
AH1-542Crissinger-Kirby 138kVActive
AH1-543Mulberry – Tazewell 345 kVActive
AH1-567University Park 138 kVActive
AH1-570Headquarters - Millersburg Junction 69 kVActive
AH1-571Headquarters - Millersburg Junction 69 kVActive
AH1-617Harbert Metering 138 kVActive
AH1-644Spicewood Metering 138 kVActive
AH1-661Cannelville 12.47 kVActive
AH1-664Goddard-Plumville 138 kVActive
AH1-665Goddard-Plumsville 138 kV IIActive
AH1-666Flemingsburg - Spurlock 138 kVActive
AH1-669Circleville-Biers Run 138 kVActive
AH1-670Blue Mound-Chestnut 345 kVActive
AH1-686Hanging Rock 765 kVActive
AH1-698Braidwood 345 kVActive
AH1-702Byron 345 kVActive
AH1-704Hannibal 138 kVActive
AH1-714Lasalle 345 kVActive
AH1-718Nelson 345 kVActive
AH1-719Beverly 345 kVActive
AH1-721Laurel-Cooper 161 kVActive
AH1-735Richland 138 kVActive
U2-030Four Mile Ridge Wind 138kVIn Service
U2-072East Lima-Marysville 345kVIn Service
U2-073Frostburg 138kV IIIn Service
V1-011Haviland 138kVIn Service
V3-007Desoto-Tanners Creek #1 345kVIn Service
V4-067Cates Road Egg Harbor Township 12kVDeactivated
V4-073Yankee 12.5kVIn Service
W1-003Oak HallIn Service
W1-004Oak HallIn Service
W1-005Oak HallIn Service
W1-006Oak HallIn Service
W1-056Ada-Dunkirk 69kVIn Service
W1-130Vine Road 12kVIn Service
W2-030Egg Harbor TownshipIn Service
W2-048Brokaw-LanesvilleIn Service
W3-077Broadway-Stewartsville 34.5kVIn Service
W4-005Blue Mound-LathamIn Service
X1-042WatervlietIn Service
X2-022Brokaw-LanesvilleIn Service
X3-005Wildwood 12kVIn Service
X3-066Church Hill 69kVIn Service
Y1-033Penn Mar-Rock Wood 115kVIn Service
Y1-049Wurno 34.5kVIn Service
Y1-079Wye Mills 69kVIn Service
Y1-080Dorchester 12kVIn Service
Y3-023Country Side 12kVIn Service
Y3-024Bluff Point 12kVIn Service
Y3-058Rockawalkin 69kVIn Service
Z2-076Worcester South 25kVIn Service
Z2-077Worcester North 25kVIn Service
Z2-087Pontiac MidPoint-Brokaw 345kVIn Service
Z2-115Deer Creek 12.47kVIn Service
Z2-116Twin Branch 12.47kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with potential Affected System impacts. PJM initiates coordination with each Affected System Operator by providing a list of New Service Requests in the Cycle with potential impacts to their respective system. If the Affected System Operator indicates an Affected System Study is required, PJM will notify the Project Developer or Eligible Customer of the need for an Affected System Study. See below if any Affected System Operator requires a study for this project:

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

Based on the Phase I analysis results, this project may have a cost responsibility for the following System Reinforcements:

AG2-665 System Reinforcements:
TORTEP IDTitleAllocated Cost ($USD)
AEP(Pending) / AEP-TC2-1867805HARRISON 138.0 kV to 05OBETZ 138.0 kV ckt 1 - Sag Study + Rebuild$7,112,320
AEP(Pending) / AEP-TC2-1867505HARRISON 138.0 kV to 05ZUBER 138.0 kV ckt 1 - Rebuild Line$4,687,328
AEP(Pending) / AEP-TC2-18699AG2-548 TP 138.0 kV to 05CORWIN 138.0 kV ckt 1 - Replace Equipment$150,000
AEP(Pending) / AEP-TC2-1872905CORWIN 138kV – 05MILTON SS 138kV - Replace Equipment$125,000
Grand Total:$12,074,648

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18678
Title
05HARRISON 138.0 kV to 05OBETZ 138.0 kV ckt 1 - Sag Study + Rebuild
Description
Sag study and re rate Harrison - Obetz - Marion Rd 138kV 10.6 miles. Replace 795 KCM ACSR (26/7) at Obetz 138kV Rebuild option was also submitted to PJM
Total Cost ($USD)
$31,000,000
Allocated Cost ($USD)
$7,112,320
Time Estimate
24 to 36 Months

Contributor

FacilityContingency
05HARRISON-05OBETZ 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-444
7.1 MW30.9%$9,582,064
AG2-548
5.3 MW22.9%$7,112,320
AG2-665
5.3 MW22.9%$7,112,320
AH1-669
5.3 MW23.2%$7,193,296

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18675
Title
05HARRISON 138.0 kV to 05ZUBER 138.0 kV ckt 1 - Rebuild Line
Description
Rebuild Harrison - Zuber 4.39 mile 138kV line
Total Cost ($USD)
$16,269,340
Allocated Cost ($USD)
$4,687,328
Time Estimate
24 to 36 Months

Contributor

FacilityContingency
05HARRISON-05ZUBER 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-548
6.4 MW28.8%$4,687,328
AG2-665
6.4 MW28.8%$4,687,328
AH1-669
9.4 MW42.4%$6,894,685

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18699
Title
AG2-548 TP 138.0 kV to 05CORWIN 138.0 kV ckt 1 - Replace Equipment
Description
At Corwin station replace the following equipment: 795 KCM AAC 37-Str, 795 KCM AAC, 37-Str (2i), 795 KCM AAC 37-Str (5i), 795 KCM AAC 37-Str. PH-A
Total Cost ($USD)
$300,000
Allocated Cost ($USD)
$150,000
Time Estimate
6 to 12 Months

Contributor

FacilityContingency
05CORWIN-AG2-548 TP 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-548
90.0 MW50.0%$150,000
AG2-665
90.0 MW50.0%$150,000

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18729
Title
05CORWIN 138kV – 05MILTON SS 138kV - Replace Equipment
Description
At Corwin station replace the following equipment: 795 KCM AAC, 37-Str., 795 KCM AAC, 37-Str. PH-A
Total Cost ($USD)
$250,000
Allocated Cost ($USD)
$125,000
Time Estimate
24 to 36 Months

Contributor

FacilityContingency
05CORWIN-05MILTON SS 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-548
90.0 MW50.0%$125,000
AG2-665
90.0 MW50.0%$125,000

System Reinforcement: b4000.10
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.10
Title
Install four 250 MVAR cap banks (two on 765 and two on 500 kV side) and a +/-500 MVAR STATCOM on the 765 kV Rocky Point yard
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-665 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-665 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.7
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.7
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line - in DVP local area/Millville to Lovettsville section, roughly 10.5 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-665 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-665 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.9
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.9
Title
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard (Projected ISD 6/1/2029)
Description
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard. Loop in the Doubs-Goose Creek 500 kV line, the Doubs-Aspen 500 kV line, and the Woodside-Goose Creek 500 kV line. Install two 765/500 kV transformer at Rocky Point substation. 765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-665 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-665 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.5
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.5
Title
Install four 250 MVAR shunt capacitors, and a +/-500 MVAR STATCOM at Welton Spring 765 kV substation
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-665 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-665 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.6
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.6
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (Welton Spring to DVP local area, roughly 21 miles) (VA Portion)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-665 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-665 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.2
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.2
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - AEP Section of the line is 30 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-665 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-665 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.8
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.8
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (DVP local area to Rocky Point, roughly 4.8 miles)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-665 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-665 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.4
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.4
Title
Construct a new 765 kV switchyard - Welton Spring (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-665 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-665 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.11
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.11
Title
Expand Black Oak Substation & Loop in the 502 Jct-Woodside 500 kV line (Projected ISD 6/1/2029)
Description
Expand Black Oak Substation to accommodate the connection of the 502 Jct-Woodside 500 kV line and loop the 502 Jct-Woodside 500 kV line into the Black Oak substation by constructing ~0.85 miles of new 500 kV line into and out of Black Oak 500 kV substation
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-665 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-665 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.1
Title
Add two 765 kV breakers at Amos Substation to expand the breaker and a half scheme to accommodate the new Amos-Welton Spring 765 kV line (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-665 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-665 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)

System Reinforcement: n6263.2
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n6263.2 / AEPO0015b
Title
Replace 600 Amp Sw at Harrison
Description
Replace 600 Amp Sw at Harrison Cost revised to $72,618 from Facility Study report.
Total Cost ($USD)
$72,618
Allocated Cost ($USD)
$0
Time Estimate
18 to 24 Months

Contingent

Note: Based on PJM cost allocation criteria, AG2-665 does not receive cost allocation towards this upgrade which has been securitized by a prior Queue/Cycle. Although AG2-665 may not have cost responsibility for this upgrade, AG2-665 may need this upgrade in-service to be deliverable for the reliability to the PJM system. If AG2-665 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
05HARRISON-05ZUBER 138.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.3
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.3
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - APS/FE Section of the line is 145 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-665 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-665 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.325
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.325
Title
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Description
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Cost Information
Time Estimate
Feb 24 2029

Not Contingent

Note: AG2-665 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-665 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.344
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.344
Title
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AG2-665 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-665 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.346
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.346
Title
Cut-in 500kV line from Kraken substation into Yeat substation
Description
Cut-in 500kV line from Kraken substation into Yeat substation
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-665 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-665 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.352
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.352
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AG2-665 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-665 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.356
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.356
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-665 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-665 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.345
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.345
Title
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AG2-665 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-665 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.327
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.327
Title
Upgrade/install equipment at Ladysmith Substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230 kV strings of breaker and a half scheme.
Description
Upgrade/install equipment at Ladysmith substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230kV strings of breaker and a half scheme.
Cost Information
Time Estimate
Feb 24 2029

Not Contingent

Note: AG2-665 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-665 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.348
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.348
Title
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.
Description
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers. A new redundant breaker ring will be added at Kraken to accommodate the new 500kV line from North Anna to Kraken.
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-665 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-665 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.341
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.341
Title
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.
Description
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV substation and extend approximately 0.2 miles of conductor to fly-over the site.
Cost Information
Time Estimate
Jul 13 2029

Not Contingent

Note: AG2-665 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-665 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.357
Title
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Description
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-665 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-665 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.349
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.349
Title
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Description
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AG2-665 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-665 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.350
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.350
Title
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Description
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AG2-665 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-665 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.355
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.355
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-665 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-665 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.351
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.351
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AG2-665 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-665 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.326
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.326
Title
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Description
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Cost Information
Time Estimate
Feb 24 2029

Not Contingent

Note: AG2-665 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-665 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.342
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.342
Title
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Description
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Cost Information
Time Estimate
Jul 13 2029

Not Contingent

Note: AG2-665 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-665 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

Attachments

AG2-665 One Line Diagram

AG2-665 One Line Diagram.jpg
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.