AH1-065 Phase I Study Report

v1.00 released 2025-10-29 22:24

Hopewell 34.5kV

8.0 MW Capacity / 20.0 MW Energy

Introduction

This Phase I System Impact Study Report (PH1) has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, sections 307 and 308 for New Service Requests (projects) in Transition Cycle 2. The Project Developer/Eligible Customer (developer) is Churchill Storage Solutions LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is Virginia Electric and Power Company (d/b/a Dominion Energy Virginia).

Preface

The Phase I System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle executive summary format and (ii) an individual project-level basis. The Phase I System Impact Study Results (for both the executive summary and individual reports) will be publicly available on PJM’s website. Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.3, PJM takes the following actions during the Phase I System Impact Study:
  1. PJM studies each New Service Request on a summer peak, winter peak and light load RTEP base case study. The case year is dependent on the new services cycle under study. PJM will identify the base case year to be used in the study of a specific cycle on its website.
  2. PJM will only perform load flow analysis during the Phase I System Impact Study.
  3. In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with Affected System impacts and provides each Affected System Operator with a list of New Service Request in the Cycle with potential impacts to their respective system.
  4. PJM will create both the short circuit and stability base cases to be used in the Phase II System Impact Study.
  5. The Phase I System Impact Study results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.
The Transmission Owner takes the following actions during the Phase I System Impact Study:
  1. Identify required Interconnection Facilities to accommodate the New Service Request.
  2. Identify required Network Upgrades to mitigate system violations from the Phase I System Impact Study.
  3. Provide planning-level preliminary estimates of Interconnection Facilities and Network Upgrades including scope, cost and elapsed time to complete the work.

Decision Point I Requirements

At the close of Phase I System Impact Study, PJM will initiate Decision Point I (DP1). During DP1, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.A.1. Additional information on these elements is available in PJM Manual 14H sections 4.4, 6, and 7.

Allowable project modifications at Decision Point I are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

General

The Project Developer has proposed a Storage facility located in the Virginia Electric and Power Company (d/b/a Dominion Energy Virginia) zone — City of Hopewell County, Virginia. The installed facilities will have a total capability of 20.0 MW with 8.0 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AH1-065
Project Name:
Hopewell 34.5kV
Project Developer Name:
Churchill Storage Solutions LLC
State:
Virginia
County:
City of Hopewell
Transmission Owner:
Virginia Electric and Power Company (d/b/a Dominion Energy Virginia)
MFO:
20.0
MWE:
20.0
MWC:
8.0
Battery Storage Specification:
80.0 MWh, 4.0-hr class
Grid Charging:
Yes
Fuel Type:
Storage
Basecase Study Year:
2028

Physical Interconnection Facility Study

Physical Interconnection Facilities Study is not performed as part of the Phase I System Impact Study. Physical Interconnection Facilities Study will commence in the Phase II System Impact Study.

Point of Interconnection

AH1-065 will interconnect on the Virginia Electric and Power Company (d/b/a Dominion Energy Virginia) distribution system at Hopewell 34.5 kV Substation bus number 314303.

 

 

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In the Phase I SIS, the costs shown are subject to change as a result of a facility study performed by the TO during the Phase II or Phase III System Impact Study.

Based on the Phase I SIS results, the AH1-065 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit are also shown below.

Cost Summary
DescriptionCost Allocated to AH1-065Cost Subject to Readiness*
Transmission Owner Interconnection Facilities (TOIF)$0$0
Other Scope$0$0
Option To Build Oversight$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$0$0
Network Upgrades$0$0
System Reliability Network Upgrades
Steady State Thermal & Voltage (SP & LL)$0$0
Transient Stability$0$0
Short Circuit$0$0
Transmission Owner Analysis
SubRegional$0$0
Distribution$0$0
Affected System Reinforcements
AFS - PJM Violatons$0$0
AFS - Non-PJM Violations$0$0
Total$0$0

* Contributes to calculation for Readiness Deposit #2 (RD2). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim deliverability study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 309 (Decision Point I) A.1.a.i and PJM Manual 14H, section 6.2, Readiness Deposit #2 (RD2) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point I (DP1), the Project Developer or Eligible Customer is required to submit Readiness Deposit #2, which is calculated as 10% of cost allocation for required Phase I Network Upgrades minus Readiness Deposit #1.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Readiness Deposit #2 Due for Project AH1-065

Readiness Deposit #2 has been calculated for the project based on the Phase I System Impact Study results and is shown in the table below. This Readiness Deposit #2 must be provided at Decision Point I through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit
Project ID10% of cost allocation for Phase I Network UpgradesReadiness Deposit #1 Received (RD1)Readiness Deposit #2 (RD2) for AH1-065 Project due at DP1
ABA - B
AH1-065$0$80,000$0

Note: Failure to provide an acceptable form of Readiness Deposit #2 by the end of Decision Point I will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

No TO Interconnection Facilities or Physical Network Upgrades are required for this project.

The costs associated with interconnecting to the Dominion distribution system will be documented in the two-party Interconnection Agreement between the Project Developer and the Transmission Owner. The Project Developer will need to coordinate with the Transmission Owner for scope, cost and schedule for this physical interconnection. This PJM report identifies the effects on the transmission system.

Transmission Owner Analysis

PJM performed a power flow analysis of the transmission system using a 2028 load flow model and the results were verified by Dominion.

 

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. Dominion interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AH1-065 was evaluated as a 20.0 MW (8.0 MW Capacity) injection in the Dominion area.

AH1-065 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 20.0 MW (20.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2DVP
6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer
DVP_P4-2: 56702_SRT-A
BreakerAC125.13 %1107.0C1385.241.09
GD2DVP
6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer
DVP_P1-2: LN 567_SRT-A
SingleAC119.77 %935.39B1120.311.09
GD2DVP
6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer
DVP_P4-2: G2T567_SRT-A
BreakerAC117.33 %1107.0C1298.881.1
GD2DVP
6CHESTF A-3CHESTFLD 230.0/115.0 kV Ckt 1 transformer
DVP_P1-2: LN 211_SRT-S
SingleAC103.28 %250.04B258.240.55
GD2DVP
6CHESTF A-6CHCKAHM 230.0 kV Ckt 1 line
DVP_P1-2: LN 2049_SRT-A
SingleAC108.69 %584.68B635.471.27
GD2DVP
6CHESTF A-6CHCKAHM 230.0 kV Ckt 1 line
DVP_P1-2: LN 2050_SRT-S
SingleAC104.83 %584.68B612.91.27
GD2DVP
6CHESTF A-6IRON208 230.0 kV Ckt 1 line
DVP_P1-2: LN 557_SRT-S
SingleAC111.61 %663.64B740.710.98
GD2DVP
6CHESTF A-6IRON208 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S
SingleAC108.5 %663.64B720.050.9
GD2DVP
6CHESTF A-6IRON208 230.0 kV Ckt 1 line
DVP_P4-2: H2T557_SRT-S
BreakerAC102.22 %811.0C828.990.95
GD2DVP
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
DVP_P4-2: 562T563_SRT-S
BreakerAC171.05 %812.0C1388.940.99
GD2DVP
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S
SingleAC170.7 %663.64B1132.821.0
GD2DVP
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
DVP_P4-2: 56372_SRT-S
BreakerAC151.48 %812.0C1230.051.04
GD2DVP
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
DVP_P1-2: LN 217_SRT-S
SingleAC127.8 %663.64B848.141.21
GD2DVP
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
DVP_P4-2: H6T576_SRT-A
BreakerAC126.92 %812.0C1030.570.9
GD2DVP
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
DVP_P4-2: H6T563_SRT-S
BreakerAC126.92 %812.0C1030.570.9
GD2DVP
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
DVP_P4-2: 21712_SRT-S
BreakerAC112.66 %812.0C914.781.21
GD2DVP
6CHESTF B-6VARINA 230.0 kV Ckt 1 line
DVP_P7-1: LN 208-259_SRT-S
TowerAC100.89 %1204.0C1214.751.27
GD2DVP
6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line
DVP_P4-2: 562T563_SRT-S
BreakerAC106.04 %1204.0C1276.772.82
GD2DVP
6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S
SingleAC103.66 %984.18B1020.192.83
GD2DVP
6IRON208-6SOUWEST 230.0 kV Ckt 1 line
DVP_P1-2: LN 557_SRT-S
SingleAC103.96 %663.64B689.920.98
GD2DVP
6IRON208-6SOUWEST 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S
SingleAC100.72 %663.64B668.440.9
GD2DVP
6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer
DVP_P7-1: LN 211-228_SRT-S
TowerAC146.93 %287.5C422.432.54
GD2DVP
6VARINA-6CHARCTY 230.0 kV Ckt 1 line
DVP_P7-1: LN 208-259_SRT-S
TowerAC100.86 %1204.0C1214.41.27
GD2DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P1-2: LN 552_SRT-S
SingleAC172.64 %3220.44B5559.881.71
GD2DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P1-2: LN 581_SRT-S
SingleAC171.66 %3220.44B5528.271.75
GD2DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P4-2: H1T581_SRT-S
BreakerAC150.52 %3940.0C5930.651.74
GD2DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P4-2: H1T552_SRT-S
BreakerAC148.0 %3940.0C5831.041.71
GD2DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P1-2: LN 552_SRT-S
SingleAC179.85 %3220.44B5791.821.71
GD2DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P1-2: LN 581_SRT-S
SingleAC175.06 %3220.44B5637.71.69
GD2DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P4-2: H1T552_SRT-S
BreakerAC154.28 %3940.0C6078.791.71
GD2DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P4-2: H3T552_SRT-S
BreakerAC154.01 %3940.0C6067.891.71

Details for 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: 56702_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer
Contingency Name:
DVP_P4-2: 56702_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:125.13 %
Rating:1107.0 MVA
Rating Type:C
MVA to Mitigate:1385.24
MW Contribution:1.09
Bus #Bus NameTypeMW Contribution
3141843SHACKLE
50/50
1.242
966661AG1-536 GEN
50/50
6.058
3142433PROV 92
50/50
0.435
3142433PROV 92
50/50
0.435
3150351NORNECKC2
50/50
2.203
3150641CHESTS8
50/50
0.652
944631AF1-128 GEN
50/50
102.426
971353AH1-157 GEN
50/50
16.966
970017AG2-010 GEN
50/50
11.364
3143096IRON208
50/50
0.7
3150771HOPHCF1
50/50
0.623
3141766HARMONY
Solar/Wind Harmer
-0.005
971777AH1-397 GEN
Solar/Wind Harmer
3.027
3138133OCRAN
Solar/Wind Harmer
-0.015
316159AE1-175 C
Solar/Wind Harmer
0.665
964211AG1-282 GEN
Solar/Wind Harmer
0.733
3141726DUNNSVL
Solar/Wind Harmer
-0.097
961951AG1-038 GEN
Solar/Wind Harmer
3.191
962861AG1-135 GEN
Solar/Wind Harmer
9.003
3142433PROV 92
Solar/Wind Harmer
-0.094
316337AD2-073 GEN
Solar/Wind Harmer
0.586
971317AH1-138 GEN
Solar/Wind Harmer
2.659
3138126ROCKLANDING
Solar/Wind Harmer
0.059
3142416OLDCHRC
Solar/Wind Harmer
-0.045
3142416OLDCHRC
Solar/Wind Harmer
-0.017
970129AG2-093 GEN
Solar/Wind Harmer
3.87
316458AB2-190 GEN2
Solar/Wind Harmer
1.714
971069AG2-661 GEN
Solar/Wind Harmer
2.652
972135AH1-637 GEN
Solar/Wind Harmer
1.651
971647AH1-324 GEN
Solar/Wind Harmer
8.244
961611AG1-000B GEN
Solar/Wind Harmer
8.06
3151171GRAVELC
Adder
1.528
3145336SMITFLD
Solar/Wind Harmer
-0.061
957971AF2-091 GEN
Solar/Wind Harmer
1.473
316072AD1-144
Solar/Wind Harmer
0.294
315671AE2-027_GEN
Solar/Wind Harmer
10.644
316375AC2-012 GEN
Solar/Wind Harmer
4.845
3150981CHESPKA
Adder
1.556
316294AC1-161 GEN
Solar/Wind Harmer
4.447
944591AF1-124 GEN
Solar/Wind Harmer
62.587
3142543TWELFTH
Solar/Wind Harmer
-0.001
316246AF1-032 C
Solar/Wind Harmer
0.277
316388AE2-253 GEN
Solar/Wind Harmer
0.92
3146456SLIGO L269
Solar/Wind Harmer
-0.014
970659AG2-427 GEN
Solar/Wind Harmer
7.209
316381AD1-082 GEN
Solar/Wind Harmer
1.244
970661AG2-428 GEN
Solar/Wind Harmer
14.398
316093AE2-104_GEN
Solar/Wind Harmer
3.922
3146516WINFALL
Solar/Wind Harmer
-0.042
3146516WINFALL
Solar/Wind Harmer
-0.013
315800Z1-036_GEN1
Solar/Wind Harmer
3.14
3130156CHOWAN
Solar/Wind Harmer
-0.012
3145663CRESWEL
Solar/Wind Harmer
-0.033
971163AH1-040 GEN
Solar/Wind Harmer
11.163
3150851SPRUNCC
Adder
0.485
939411AE1-173 GEN
Solar/Wind Harmer
57.436
3146206CASHIE
Solar/Wind Harmer
-0.011
971547AH1-271 GEN
Solar/Wind Harmer
2.795
3145893MURPHYS
Solar/Wind Harmer
-0.043
3145893MURPHYS
Solar/Wind Harmer
0.323
940641AE2-051 GEN
Solar/Wind Harmer
10.065
3146173TUNIS
Solar/Wind Harmer
-0.011
3145683EARLEYS
Solar/Wind Harmer
-0.011
3145963POPLR C
Solar/Wind Harmer
-0.01
316174AB2-169 GEN
Solar/Wind Harmer
1.591
3146263WOODLND
Solar/Wind Harmer
-0.01
3145823KELFORD
Solar/Wind Harmer
-0.01
316023GEN1_S
Solar/Wind Harmer
0.678
316190AA2-174 GEN
Solar/Wind Harmer
0.12
316011AB1-132 GEN
Solar/Wind Harmer
2.035
962571AG1-106 GEN
Solar/Wind Harmer
1.398
3146293MARTNCO
Solar/Wind Harmer
0.06
960081AF2-299 GEN
Solar/Wind Harmer
1.076
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.009
3145783HORNRTN
Solar/Wind Harmer
-0.009
3143526WINTERP
Solar/Wind Harmer
-0.049
316212AC1-099_GEN
Solar/Wind Harmer
0.816
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
971795AH1-408 GEN
Solar/Wind Harmer
6.798
316494AC1-189 GEN
Solar/Wind Harmer
0.961
970919AG2-571 GEN
Solar/Wind Harmer
2.805
3147043LAWRENC
Adder
0.711
970087AG2-069 GEN
Solar/Wind Harmer
8.273
315722AD1-056 GEN
Solar/Wind Harmer
0.923
315759AF1-018 GEN
50/50
8.574
3142433PROV 92
50/50
0.435
3142433PROV 92
50/50
0.435
3150611CHESTG7
50/50
1.286
3150631CHESTG8
50/50
1.265
971047AG2-646 GEN
50/50
36.002
315976AC1-164 GENA
Solar/Wind Harmer
37.032
316169AC1-164_GENC
Solar/Wind Harmer
31.992
315975AC1-164 GENB
Solar/Wind Harmer
1.096
316314AB2-024 C
Solar/Wind Harmer
2.414
316059AD1-063 C
Solar/Wind Harmer
0.612
3143873LANEXA
Solar/Wind Harmer
-0.016
315662AE1-191 GEN
Solar/Wind Harmer
3.076
315666AE1-190 GEN
Solar/Wind Harmer
0.769
957601AF2-054 GEN
Solar/Wind Harmer
0.754
3141873WAN 176
Solar/Wind Harmer
-0.005
3141913WHIT STONE
Solar/Wind Harmer
-0.025
3138133OCRAN
Solar/Wind Harmer
-0.007
3141783LANCAST
Solar/Wind Harmer
-0.015
3141783LANCAST
Solar/Wind Harmer
-0.01
962981AG1-147 GEN
Solar/Wind Harmer
10.679
3141813NORNECK
Solar/Wind Harmer
-0.023
971167AH1-042 GEN
Solar/Wind Harmer
22.181
957831AF2-077 GEN
Solar/Wind Harmer
0.668
3138283WHITEMARSH
Solar/Wind Harmer
0.034
316223AC1-118
Solar/Wind Harmer
0.531
316312AB1-027
Solar/Wind Harmer
0.583
316132AB2-190 GEN1
Solar/Wind Harmer
1.714
316369SG1_INVT
Solar/Wind Harmer
2.973
972265AH1-717 GEN
Adder
11.153
3151201GRAVEL4
Adder
10.455
3151191GRAVEL3
Adder
10.323
3151211GRAVEL5
Adder
10.323
971445AH1-216 GEN
Solar/Wind Harmer
9.527
944491AF1-114 GEN
Solar/Wind Harmer
4.333
3152611GOSPORTB
Adder
1.587
3152621GOSPORTC
Adder
1.347
3152601GOSPORTA
Adder
1.242
3151081ELIZAR1
Adder
11.396
3151091ELIZAR2
Adder
11.198
316305AF2-043 C
Solar/Wind Harmer
0.413
957871AF2-081 GEN
Solar/Wind Harmer
6.809
319010AE1-072 C
Solar/Wind Harmer
2.743
3146406KITTY HAWK
Solar/Wind Harmer
0.011
315833AF1-017_GEN
Solar/Wind Harmer
2.567
316349AD2-085 GEN
Solar/Wind Harmer
1.202
316311AC2-079 GEN
Solar/Wind Harmer
6.818
315835AF2-110_GEN
Solar/Wind Harmer
1.686
3146486SUNBURY
Solar/Wind Harmer
-0.013
3146486SUNBURY
Solar/Wind Harmer
-0.013
313526AB2-022
Solar/Wind Harmer
0.36
316321Z2-027
Solar/Wind Harmer
0.358
3146396TANGLEW
Solar/Wind Harmer
0.244
3145176PASQUOTANK
Solar/Wind Harmer
-0.008
315611Z1-036_GEN2
Solar/Wind Harmer
3.14
3130156CHOWAN
Solar/Wind Harmer
-0.012
3130156CHOWAN
Solar/Wind Harmer
-0.012
3143316POE
Solar/Wind Harmer
-0.048
315816AE2-034 GEN
Solar/Wind Harmer
0.963
971285AH1-108 GEN
Adder
0.794
3130546PLYMOUTH
Solar/Wind Harmer
-0.011
315732AD1-074 GEN1
Solar/Wind Harmer
2.314
315733AD1-074 GEN2
Solar/Wind Harmer
2.314
315735AD1-075 GEN1
Solar/Wind Harmer
1.157
3146206CASHIE
Solar/Wind Harmer
-0.011
970601AG2-382 GEN
Solar/Wind Harmer
4.891
965291AG1-394 GEN
Solar/Wind Harmer
0.979
316318V4-068
Solar/Wind Harmer
0.271
3145893MURPHYS
Solar/Wind Harmer
-0.029
3145893MURPHYS
Solar/Wind Harmer
-0.011
316315AB2-025 C
Solar/Wind Harmer
0.293
315814AE2-033 C
Solar/Wind Harmer
10.064
3145513AHOSKIE
Solar/Wind Harmer
0.093
961941AG1-037 GEN
Solar/Wind Harmer
0.08
3145513AHOSKIE
Solar/Wind Harmer
-0.011
3145683EARLEYS
Solar/Wind Harmer
-0.021
3145683EARLEYS
Solar/Wind Harmer
-0.011
3145683EARLEYS
Solar/Wind Harmer
-0.011
3146043SEABORD
Solar/Wind Harmer
-0.01
315607AA1-063A GEN
Solar/Wind Harmer
1.024
315652AC1-086 GEN
Solar/Wind Harmer
10.943
3146033SCOT NK
Solar/Wind Harmer
-0.039
941031AE2-094 GEN
Solar/Wind Harmer
18.106
3150341NORNECKC1
50/50
2.314
3150341NORNECKC1
50/50
2.295
963611AG1-210 GEN
50/50
0.74
3150621CHESTS7
50/50
0.591
3150781HOPHCF2
50/50
0.623
3150791HOPHCF3
50/50
0.623
3150761HOPPOLC
50/50
0.395
971213AH1-066 GEN
50/50
0.546
316075AC2-137 C
Solar/Wind Harmer
0.756
3142946ENON
Solar/Wind Harmer
-0.003
316441AF1-014 GEN
Solar/Wind Harmer
1.735
316487AF1-042 GEN
Solar/Wind Harmer
3.191
958261AF2-120 GEN
Solar/Wind Harmer
9.272
316077AC2-138 C
Solar/Wind Harmer
0.493
3150691DARBY 3
Adder
10.705
3150701DARBY 4
Adder
10.68
3150681DARBY 2
Adder
10.668
3150671DARBY 1
Adder
10.655
316033AB2-134 GEN
Solar/Wind Harmer
5.366
315697AD1-025 GEN
Solar/Wind Harmer
3.366
316236AE1-162_GEN
Solar/Wind Harmer
0.462
316036AC1-147 C
Solar/Wind Harmer
0.378
3150991CHESPKB
Adder
1.305
3150991CHESPKB
Adder
1.274
316316AC1-027 C
Solar/Wind Harmer
0.426
3142956BIRDNECK
Solar/Wind Harmer
0.744
316185AD1-033 GEN
Solar/Wind Harmer
1.453
3145506HICKORY
Solar/Wind Harmer
-0.055
3145506HICKORY
Solar/Wind Harmer
-0.033
3145506HICKORY
Solar/Wind Harmer
-0.008
3142366NRTHEST
Adder
0.397
316339AD2-160 GEN
Solar/Wind Harmer
0.92
316018AA1-139 ULT2
Solar/Wind Harmer
1.167
316017AA1-139 ULT1
Solar/Wind Harmer
1.102
315749AE2-041 GEN
50/50
8.574
3141843SHACKLE
50/50
1.242
970575AG2-366 GEN
50/50
3.862
3142433PROV 92
50/50
0.435
3142433PROV 92
50/50
0.435
3150351NORNECKC2
50/50
2.24
3150921YORKTN3
50/50
4.627
3144216WINCHST
50/50
0.678
3143096IRON208
50/50
0.7
3143096IRON208
50/50
0.686
3150801HOPHCF4
50/50
0.906
971211AH1-065 GEN
50/50
1.092
3141766HARMONY
Solar/Wind Harmer
2.412
3142946ENON
Solar/Wind Harmer
-0.009
316203AE2-005 GEN
Solar/Wind Harmer
10.85
316280AD1-041 GEN
Solar/Wind Harmer
1.923
316156AD2-030 GEN
Solar/Wind Harmer
0.673
3141873WAN 176
Solar/Wind Harmer
2.993
316382AG1-145 C
Solar/Wind Harmer
0.746
962971AG1-146 GEN
Solar/Wind Harmer
4.577
316484AD2-074 GEN
Solar/Wind Harmer
6.098
970009AG2-005 GEN
Solar/Wind Harmer
3.028
316404AE1-155 C
Solar/Wind Harmer
4.616
970293AG2-193 GEN
Solar/Wind Harmer
2.767
3141906WESTMOR
Solar/Wind Harmer
-0.008
970737AG2-469 GEN
Solar/Wind Harmer
8.897
3142416OLDCHRC
Solar/Wind Harmer
1.744
970133AG2-095 GEN
Solar/Wind Harmer
1.942
970129AG2-093 GEN
Solar/Wind Harmer
9.555
315778AD1-151 GEN
Solar/Wind Harmer
14.522
961611AG1-000B GEN
Solar/Wind Harmer
3.439
3151221GRAVEL6
Adder
10.443
3151171GRAVELC
Adder
2.009
3145336SMITFLD
Solar/Wind Harmer
-0.006
3144536CHRHLND
Solar/Wind Harmer
-0.002
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
11.542
965281AG1-393 GEN
Solar/Wind Harmer
1.744
315773AC2-141 GEN
Solar/Wind Harmer
5.752
944581AF1-123 GEN
Solar/Wind Harmer
62.362
944601AF1-125 GEN
Solar/Wind Harmer
61.389
315813AE1-149 C
Solar/Wind Harmer
8.496
3146456SLIGO L269
Solar/Wind Harmer
-0.014
971153AH1-033 GEN
Solar/Wind Harmer
1.655
970659AG2-427 GEN
Solar/Wind Harmer
1.277
316083AB2-161 GEN
Solar/Wind Harmer
2.202
970661AG2-428 GEN
Solar/Wind Harmer
2.552
316320Y1-086
Solar/Wind Harmer
0.783
316435W1029_GEN3
Solar/Wind Harmer
2.383
3146516WINFALL
Solar/Wind Harmer
-0.013
3146626S HERTFORD
Solar/Wind Harmer
-0.013
3145273HOLLAND
Solar/Wind Harmer
-0.01
315839AE2-212 C
Solar/Wind Harmer
0.383
3146376EDENTON
Solar/Wind Harmer
-0.012
315614AA2-178 GEN
Solar/Wind Harmer
1.285
3150861SPRUNCD
Adder
0.485
971157AH1-035 GEN
Solar/Wind Harmer
1.439
315737AD1-076 GEN
Solar/Wind Harmer
2.174
3146206CASHIE
Solar/Wind Harmer
-0.011
3156081AA2-088 GEN
Solar/Wind Harmer
3.619
3145893MURPHYS
Solar/Wind Harmer
0.076
3145893MURPHYS
Solar/Wind Harmer
-0.011
957521AF2-046 GEN
Solar/Wind Harmer
8.535
961681AG1-008 GEN
Solar/Wind Harmer
8.535
3156021HOLLOMANSOL
Solar/Wind Harmer
1.456
3146173TUNIS
Solar/Wind Harmer
-0.011
316463AE2-346 GEN
Solar/Wind Harmer
0.172
316140AB2-099
Solar/Wind Harmer
0.072
962331AG1-082 GEN
Solar/Wind Harmer
1.33
3145963POPLR C
Solar/Wind Harmer
-0.01
3146263WOODLND
Solar/Wind Harmer
-0.01
316317KELFORD C
Solar/Wind Harmer
0.478
3145823KELFORD
Solar/Wind Harmer
-0.01
316365GEN2_N
Solar/Wind Harmer
0.678
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
3145933PARMELE
Solar/Wind Harmer
-0.01
966801AG1-551 GEN
Solar/Wind Harmer
1.208
966621AG1-532 GEN
Solar/Wind Harmer
0.194
313506AB2-031 GEN
Solar/Wind Harmer
0.769
3145796HORNRTN
Solar/Wind Harmer
-0.038
3145796HORNRTN
Solar/Wind Harmer
-0.009
316210AC1-098 GEN
Solar/Wind Harmer
1.47
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
970917AG2-570 GEN
Solar/Wind Harmer
22.162
3147043LAWRENC
Solar/Wind Harmer
-0.005
315724AD1-057 GEN
Solar/Wind Harmer
0.507
316327AA2-057 GEN
Solar/Wind Harmer
0.886
3146073TAR RVR
Solar/Wind Harmer
-0.009
3146083TARBORO
Solar/Wind Harmer
-0.009
3146233WITAKRS
Solar/Wind Harmer
0.178
3146233WITAKRS
Solar/Wind Harmer
-0.006
3138543CONSLDL
Solar/Wind Harmer
-0.006
961601AG1-000A GEN
Solar/Wind Harmer
3.293
3145543BTLEBRO
Solar/Wind Harmer
-0.008
3145543BTLEBRO
Solar/Wind Harmer
-0.008
3141316ARNOLDS
Adder
0.161
944011AF1-069 GEN
Solar/Wind Harmer
5.673
946281AF1-292 GEN
Solar/Wind Harmer
0.214
316087AB2-174 GEN
Solar/Wind Harmer
1.364
3137643SOCKMAN
Solar/Wind Harmer
-0.038
3145796HORNRTN
Solar/Wind Harmer
-0.03
3145796HORNRTN
Solar/Wind Harmer
-0.004
316233AE1-074 FULL
Solar/Wind Harmer
0.255
971281AH1-106 GEN
Solar/Wind Harmer
1.542
971283AH1-107 GEN
Solar/Wind Harmer
1.542
970673AG2-436 GEN
Solar/Wind Harmer
19.87
970673AG2-436 GEN
Solar/Wind Harmer
10.061
316005AA1-067
Solar/Wind Harmer
0.188
3145746EVERETS
Solar/Wind Harmer
-0.037
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
970181AG2-120 GEN
Solar/Wind Harmer
1.218
971967AH1-528 GEN
Solar/Wind Harmer
17.421
957861AF2-080 GEN
Solar/Wind Harmer
3.908
970085AG2-068 GEN
Solar/Wind Harmer
5.516
970581AG2-369 GEN
Solar/Wind Harmer
4.743
316420AA1-050 GEN
Solar/Wind Harmer
1.001
3145573BETHELC
Solar/Wind Harmer
-0.009
3145573BETHELC
Solar/Wind Harmer
-0.009
316319Z2-044 C
Solar/Wind Harmer
0.471
970831AG2-522 GEN
Solar/Wind Harmer
4.197
961671AG1-007 GEN
Solar/Wind Harmer
0.109
3146083TARBORO
Solar/Wind Harmer
-0.009
3145493TOT1
Solar/Wind Harmer
0.256
3146233WITAKRS
Solar/Wind Harmer
-0.034
316129AC1-054 GEN
Solar/Wind Harmer
0.725
316359AB2-059 GEN
Solar/Wind Harmer
1.113
316049AB1-081 GEN
Solar/Wind Harmer
0.891
3145543BTLEBRO
Solar/Wind Harmer
-0.008
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3142053HEARTS
Solar/Wind Harmer
0.097
971065AG2-659 GEN
Solar/Wind Harmer
4.078
957481AF2-042 GEN
Solar/Wind Harmer
21.195
3137176SLIGO L2192
Solar/Wind Harmer
-0.054
3146456SLIGO L269
Solar/Wind Harmer
1.603
970657AG2-426 GEN
Solar/Wind Harmer
4.237
970657AG2-426 GEN
Solar/Wind Harmer
0.886
3130086AYDLETT
Solar/Wind Harmer
-0.054
3146386ELIZ CT
Solar/Wind Harmer
-0.013
316431W1029_GEN1
Solar/Wind Harmer
2.383
316433W1029_GEN2
Solar/Wind Harmer
2.383
3146516WINFALL
Solar/Wind Harmer
-0.013
3146516WINFALL
Solar/Wind Harmer
-0.013
3146516WINFALL
Solar/Wind Harmer
-0.013
944641AF1-129 GEN
Adder
55.399
316240AF1-291 C
Solar/Wind Harmer
0.391
3146626S HERTFORD
Solar/Wind Harmer
-0.013
3146626S HERTFORD
Solar/Wind Harmer
-0.013
315742AE1-103 GEN
Solar/Wind Harmer
1.299
3146376EDENTON
Solar/Wind Harmer
0.369
3146376EDENTON
Solar/Wind Harmer
0.369
316065AD1-022 GEN
Solar/Wind Harmer
5.637
3145893MURPHYS
Solar/Wind Harmer
0.304
3145893MURPHYS
Solar/Wind Harmer
-0.02
3144356SAPONY
Solar/Wind Harmer
0.378
3146173TUNIS
Solar/Wind Harmer
-0.011
3146173TUNIS
Solar/Wind Harmer
-0.011
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
316426AA2-053 GEN
Solar/Wind Harmer
0.983
3145933PARMELE
Solar/Wind Harmer
-0.019
3145933PARMELE
Solar/Wind Harmer
-0.01
316181AB2-040 GEN
Solar/Wind Harmer
1.334
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.075
3145593CAROLNA
Solar/Wind Harmer
0.079
3145796HORNRTN
Solar/Wind Harmer
-0.028
3145783HORNRTN
Solar/Wind Harmer
1.127
3145783HORNRTN
Solar/Wind Harmer
0.901
3145783HORNRTN
Solar/Wind Harmer
0.282
3145783HORNRTN
Solar/Wind Harmer
0.113
3143526WINTERP
Solar/Wind Harmer
-0.049
972185AH1-677 GEN
Adder
4.674
972187AH1-678 GEN
Adder
2.339
316274AC1-208 GEN
Solar/Wind Harmer
0.989
970933AG2-581 GEN
Solar/Wind Harmer
8.378
3145493TOT1
Solar/Wind Harmer
0.134
3145453TOT5
Solar/Wind Harmer
0.08
3145603CNETO
Solar/Wind Harmer
0.053
961601AG1-000A GEN
Solar/Wind Harmer
3.252
316263AC1-034 GEN
Solar/Wind Harmer
3.871
970099AG2-077 GEN
Solar/Wind Harmer
8.478
LAGNLTFEXP_LAGN->PJM
CLTF
1.924
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.054
TVALTFEXP_TVA->PJM
CLTF
0.95
CPLELTFEXP_CPLE->PJM
CLTF
4.035
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.643
NYPJM->LTFIMP_NY
CLTF
0.699
LGEELTFEXP_LGEE->PJM
CLTF
0.151
WECLTFEXP_WEC->PJM
CLTF
0.071
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.999
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.074
MECLTFEXP_MEC->PJM
CLTF
0.569
SIGELTFEXP_SIGE->PJM
CLTF
0.015

Details for 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 567_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 567_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.77 %
Rating:935.39 MVA
Rating Type:B
MVA to Mitigate:1120.31
MW Contribution:1.09
Bus #Bus NameTypeMW Contribution
3141843SHACKLE
50/50
1.242
966661AG1-536 GEN
50/50
6.058
3142433PROV 92
50/50
0.435
3142433PROV 92
50/50
0.435
3150351NORNECKC2
50/50
2.203
3150641CHESTS8
50/50
0.652
944631AF1-128 GEN
50/50
102.426
971353AH1-157 GEN
50/50
16.966
970017AG2-010 GEN
50/50
11.364
3143096IRON208
50/50
0.7
3150771HOPHCF1
50/50
0.623
3141766HARMONY
Solar/Wind Harmer
0.048
971777AH1-397 GEN
Solar/Wind Harmer
0.605
3138133OCRAN
Solar/Wind Harmer
0.133
316159AE1-175 C
Solar/Wind Harmer
0.19
3141726DUNNSVL
Solar/Wind Harmer
0.868
962861AG1-135 GEN
Solar/Wind Harmer
6.837
3142433PROV 92
Solar/Wind Harmer
0.844
316337AD2-073 GEN
Solar/Wind Harmer
0.169
315759AF1-018 GEN
50/50
8.574
3142433PROV 92
50/50
0.435
3142433PROV 92
50/50
0.435
3150611CHESTG7
50/50
1.286
3150631CHESTG8
50/50
1.265
971047AG2-646 GEN
50/50
36.002
315976AC1-164 GENA
Solar/Wind Harmer
32.344
316169AC1-164_GENC
Solar/Wind Harmer
27.943
315975AC1-164 GENB
Solar/Wind Harmer
0.957
316314AB2-024 C
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.002
3143873LANEXA
Solar/Wind Harmer
0.141
970189AG2-124 GEN
Solar/Wind Harmer
6.788
315662AE1-191 GEN
Solar/Wind Harmer
0.007
315666AE1-190 GEN
Solar/Wind Harmer
0.002
3141873WAN 176
Solar/Wind Harmer
0.045
3141913WHIT STONE
Solar/Wind Harmer
0.222
3138133OCRAN
Solar/Wind Harmer
0.066
3141783LANCAST
Solar/Wind Harmer
0.132
3141783LANCAST
Solar/Wind Harmer
0.088
962981AG1-147 GEN
Solar/Wind Harmer
8.11
970327AG2-215 GEN
Solar/Wind Harmer
7.076
3141813NORNECK
Solar/Wind Harmer
0.208
971167AH1-042 GEN
Solar/Wind Harmer
18.214
3138283WHITEMARSH
Solar/Wind Harmer
0.046
316223AC1-118
Solar/Wind Harmer
0.126
316312AB1-027
Solar/Wind Harmer
0.275
316132AB2-190 GEN1
Solar/Wind Harmer
0.809
316369SG1_INVT
Solar/Wind Harmer
0.006
972265AH1-717 GEN
Adder
11.153
3151201GRAVEL4
Adder
10.455
3151191GRAVEL3
Adder
10.323
3151211GRAVEL5
Adder
10.323
971445AH1-216 GEN
Solar/Wind Harmer
9.647
944491AF1-114 GEN
Solar/Wind Harmer
0
3152611GOSPORTB
Adder
1.587
3152621GOSPORTC
Adder
1.347
3152601GOSPORTA
Adder
1.242
3151081ELIZAR1
Adder
11.396
3151091ELIZAR2
Adder
11.198
316305AF2-043 C
Solar/Wind Harmer
0.001
957871AF2-081 GEN
Solar/Wind Harmer
6.034
319010AE1-072 C
Solar/Wind Harmer
0.608
3146406KITTY HAWK
Solar/Wind Harmer
0.015
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.082
316311AC2-079 GEN
Solar/Wind Harmer
3.454
315835AF2-110_GEN
Solar/Wind Harmer
0.824
3146486SUNBURY
Solar/Wind Harmer
0.119
3146486SUNBURY
Solar/Wind Harmer
0.119
313526AB2-022
Solar/Wind Harmer
0.064
316321Z2-027
Solar/Wind Harmer
0.022
3146396TANGLEW
Solar/Wind Harmer
0.325
3145176PASQUOTANK
Solar/Wind Harmer
0.073
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.111
3150341NORNECKC1
50/50
2.314
3150341NORNECKC1
50/50
2.295
963611AG1-210 GEN
50/50
0.74
3150621CHESTS7
50/50
0.591
3150781HOPHCF2
50/50
0.623
3150791HOPHCF3
50/50
0.623
3150761HOPPOLC
50/50
0.395
971213AH1-066 GEN
50/50
0.546
316075AC2-137 C
Solar/Wind Harmer
0.069
3142946ENON
Solar/Wind Harmer
0.023
958261AF2-120 GEN
Solar/Wind Harmer
7.042
316077AC2-138 C
Solar/Wind Harmer
0.001
3150691DARBY 3
Adder
10.705
3150701DARBY 4
Adder
10.68
3150681DARBY 2
Adder
10.668
3150671DARBY 1
Adder
10.655
316033AB2-134 GEN
Solar/Wind Harmer
0.009
315697AD1-025 GEN
Solar/Wind Harmer
0.167
316236AE1-162_GEN
Solar/Wind Harmer
0.001
316036AC1-147 C
Solar/Wind Harmer
0.023
3150991CHESPKB
Adder
1.305
3150991CHESPKB
Adder
1.274
316316AC1-027 C
Solar/Wind Harmer
0.119
3142956BIRDNECK
Solar/Wind Harmer
0
316185AD1-033 GEN
Solar/Wind Harmer
0.003
3145506HICKORY
Solar/Wind Harmer
0.488
3145506HICKORY
Solar/Wind Harmer
0.293
3145506HICKORY
Solar/Wind Harmer
0.073
3142366NRTHEST
Adder
0.397
316339AD2-160 GEN
Solar/Wind Harmer
0.197
316018AA1-139 ULT2
Solar/Wind Harmer
0.003
316017AA1-139 ULT1
Solar/Wind Harmer
0.068
3137176SLIGO L2192
Solar/Wind Harmer
0.481
3146456SLIGO L269
Solar/Wind Harmer
2.138
315749AE2-041 GEN
50/50
8.574
3141843SHACKLE
50/50
1.242
970575AG2-366 GEN
50/50
3.862
3142433PROV 92
50/50
0.435
3142433PROV 92
50/50
0.435
3150351NORNECKC2
50/50
2.24
3150921YORKTN3
50/50
4.627
3144216WINCHST
50/50
0.678
3143096IRON208
50/50
0.7
3143096IRON208
50/50
0.686
3150801HOPHCF4
50/50
0.906
971211AH1-065 GEN
50/50
1.092
3141766HARMONY
Solar/Wind Harmer
3.215
3142946ENON
Solar/Wind Harmer
0.078
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316280AD1-041 GEN
Solar/Wind Harmer
0.005
316156AD2-030 GEN
Solar/Wind Harmer
0.166
3141873WAN 176
Solar/Wind Harmer
3.99
316382AG1-145 C
Solar/Wind Harmer
0.002
962971AG1-146 GEN
Solar/Wind Harmer
3.476
970009AG2-005 GEN
Solar/Wind Harmer
1.61
316404AE1-155 C
Solar/Wind Harmer
0.048
970293AG2-193 GEN
Solar/Wind Harmer
2.101
3141906WESTMOR
Solar/Wind Harmer
0.07
970737AG2-469 GEN
Solar/Wind Harmer
6.757
3142416OLDCHRC
Solar/Wind Harmer
1.491
970133AG2-095 GEN
Solar/Wind Harmer
1.475
970129AG2-093 GEN
Solar/Wind Harmer
9.13
315778AD1-151 GEN
Solar/Wind Harmer
11.936
961611AG1-000B GEN
Solar/Wind Harmer
3.876
3151221GRAVEL6
Adder
10.443
3151171GRAVELC
Adder
2.009
3145336SMITFLD
Solar/Wind Harmer
0.055
3144536CHRHLND
Solar/Wind Harmer
0.019
3144873MCLAUGH
Solar/Wind Harmer
0.003
3151101ELIZAR3
Adder
11.542
965281AG1-393 GEN
Solar/Wind Harmer
1.324
315773AC2-141 GEN
Solar/Wind Harmer
4.468
944581AF1-123 GEN
Solar/Wind Harmer
27.472
944601AF1-125 GEN
Solar/Wind Harmer
27.049
315813AE1-149 C
Solar/Wind Harmer
6.453
3146456SLIGO L269
Solar/Wind Harmer
0.121
971153AH1-033 GEN
Solar/Wind Harmer
1.397
970659AG2-427 GEN
Solar/Wind Harmer
1.277
316083AB2-161 GEN
Solar/Wind Harmer
0.002
970661AG2-428 GEN
Solar/Wind Harmer
2.552
316320Y1-086
Solar/Wind Harmer
0.001
316435W1029_GEN3
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.116
3146626S HERTFORD
Solar/Wind Harmer
0.115
3145273HOLLAND
Solar/Wind Harmer
0.085
315839AE2-212 C
Solar/Wind Harmer
0.001
3146376EDENTON
Solar/Wind Harmer
0.11
315614AA2-178 GEN
Solar/Wind Harmer
0.606
3150861SPRUNCD
Adder
0.485
971157AH1-035 GEN
Solar/Wind Harmer
1.23
315737AD1-076 GEN
Solar/Wind Harmer
1.31
3146206CASHIE
Solar/Wind Harmer
0.099
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
3145893MURPHYS
Solar/Wind Harmer
0.162
3145893MURPHYS
Solar/Wind Harmer
0.097
957521AF2-046 GEN
Solar/Wind Harmer
7.177
961681AG1-008 GEN
Solar/Wind Harmer
7.177
3156021HOLLOMANSOL
Solar/Wind Harmer
0.437
3146173TUNIS
Solar/Wind Harmer
0.095
316463AE2-346 GEN
Solar/Wind Harmer
0.081
316140AB2-099
Solar/Wind Harmer
0.034
962331AG1-082 GEN
Solar/Wind Harmer
1.01
3145963POPLR C
Solar/Wind Harmer
0.093
3146263WOODLND
Solar/Wind Harmer
0.091
316317KELFORD C
Solar/Wind Harmer
0.009
3145823KELFORD
Solar/Wind Harmer
0.09
316365GEN2_N
Solar/Wind Harmer
0.201
3142666NORTHAMPTON
Solar/Wind Harmer
0.088
3145933PARMELE
Solar/Wind Harmer
0.086
966801AG1-551 GEN
Solar/Wind Harmer
1.002
313506AB2-031 GEN
Solar/Wind Harmer
0.263
3145796HORNRTN
Solar/Wind Harmer
0.338
3145796HORNRTN
Solar/Wind Harmer
0.085
316210AC1-098 GEN
Solar/Wind Harmer
0.773
3145746EVERETS
Solar/Wind Harmer
0.083
3145746EVERETS
Solar/Wind Harmer
0.083
970917AG2-570 GEN
Solar/Wind Harmer
7.013
3147043LAWRENC
Solar/Wind Harmer
0.047
315724AD1-057 GEN
Solar/Wind Harmer
0.295
3130156CHOWAN
Solar/Wind Harmer
0.111
3143316POE
Solar/Wind Harmer
0.433
315816AE2-034 GEN
Solar/Wind Harmer
0.455
971285AH1-108 GEN
Adder
0.794
3130546PLYMOUTH
Solar/Wind Harmer
0.102
315732AD1-074 GEN1
Solar/Wind Harmer
0.585
315733AD1-074 GEN2
Solar/Wind Harmer
0.585
315735AD1-075 GEN1
Solar/Wind Harmer
0.293
3146206CASHIE
Solar/Wind Harmer
0.099
970601AG2-382 GEN
Solar/Wind Harmer
3.715
965291AG1-394 GEN
Solar/Wind Harmer
0.437
3145893MURPHYS
Solar/Wind Harmer
0.261
3145893MURPHYS
Solar/Wind Harmer
0.097
316315AB2-025 C
Solar/Wind Harmer
0.078
315814AE2-033 C
Solar/Wind Harmer
7.609
3145513AHOSKIE
Solar/Wind Harmer
0.198
3145513AHOSKIE
Solar/Wind Harmer
0.095
3145683EARLEYS
Solar/Wind Harmer
0.188
3145683EARLEYS
Solar/Wind Harmer
0.094
3145683EARLEYS
Solar/Wind Harmer
0.094
3146043SEABORD
Solar/Wind Harmer
0.091
315607AA1-063A GEN
Solar/Wind Harmer
0.184
315652AC1-086 GEN
Solar/Wind Harmer
9.519
3146033SCOT NK
Solar/Wind Harmer
0.346
941031AE2-094 GEN
Solar/Wind Harmer
15.83
944011AF1-069 GEN
Solar/Wind Harmer
5.172
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3137643SOCKMAN
Solar/Wind Harmer
0.34
3145796HORNRTN
Solar/Wind Harmer
0.271
3145796HORNRTN
Solar/Wind Harmer
0.034
316233AE1-074 FULL
Solar/Wind Harmer
0.068
971281AH1-106 GEN
Solar/Wind Harmer
1.171
971283AH1-107 GEN
Solar/Wind Harmer
1.171
970673AG2-436 GEN
Solar/Wind Harmer
17.959
970673AG2-436 GEN
Solar/Wind Harmer
11.973
316005AA1-067
Solar/Wind Harmer
0.089
3145746EVERETS
Solar/Wind Harmer
0.329
3145746EVERETS
Solar/Wind Harmer
0.083
3145746EVERETS
Solar/Wind Harmer
0.083
3145746EVERETS
Solar/Wind Harmer
0.083
970181AG2-120 GEN
Solar/Wind Harmer
1.028
971967AH1-528 GEN
Solar/Wind Harmer
13.196
957861AF2-080 GEN
Solar/Wind Harmer
3.428
970085AG2-068 GEN
Solar/Wind Harmer
4.189
970581AG2-369 GEN
Solar/Wind Harmer
3.603
316420AA1-050 GEN
Solar/Wind Harmer
0.003
3145573BETHELC
Solar/Wind Harmer
0.077
3145573BETHELC
Solar/Wind Harmer
0.077
316319Z2-044 C
Solar/Wind Harmer
0
970831AG2-522 GEN
Solar/Wind Harmer
3.188
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
971443AH1-215 GEN
Solar/Wind Harmer
0.999
3144303KENBRDG
Solar/Wind Harmer
0.047
316118AC1-105 GEN
Solar/Wind Harmer
0.149
970683AG2-441 GEN
Solar/Wind Harmer
3.824
970681AG2-440 GEN
Solar/Wind Harmer
3.059
3147173SINAI
Solar/Wind Harmer
0.056
3147243WELCO
Solar/Wind Harmer
0.035
971317AH1-138 GEN
Solar/Wind Harmer
1.414
3138126ROCKLANDING
Solar/Wind Harmer
0.078
3142416OLDCHRC
Solar/Wind Harmer
0.4
3142416OLDCHRC
Solar/Wind Harmer
0.153
970129AG2-093 GEN
Solar/Wind Harmer
4.296
316458AB2-190 GEN2
Solar/Wind Harmer
0.809
971069AG2-661 GEN
Solar/Wind Harmer
2.652
972135AH1-637 GEN
Solar/Wind Harmer
1.254
971647AH1-324 GEN
Solar/Wind Harmer
6.261
961611AG1-000B GEN
Solar/Wind Harmer
7.623
3151171GRAVELC
Adder
1.528
3145336SMITFLD
Solar/Wind Harmer
0.545
316072AD1-144
Solar/Wind Harmer
0.047
315671AE2-027_GEN
Solar/Wind Harmer
8.084
316375AC2-012 GEN
Solar/Wind Harmer
0.003
3150981CHESPKA
Adder
1.556
316294AC1-161 GEN
Solar/Wind Harmer
2.12
944591AF1-124 GEN
Solar/Wind Harmer
27.57
3142543TWELFTH
Solar/Wind Harmer
0.012
316246AF1-032 C
Solar/Wind Harmer
0.055
316388AE2-253 GEN
Solar/Wind Harmer
0.38
3146456SLIGO L269
Solar/Wind Harmer
0.121
970659AG2-427 GEN
Solar/Wind Harmer
5.84
316381AD1-082 GEN
Solar/Wind Harmer
0.126
970661AG2-428 GEN
Solar/Wind Harmer
11.997
316093AE2-104_GEN
Solar/Wind Harmer
2.019
3146516WINFALL
Solar/Wind Harmer
0.377
3146516WINFALL
Solar/Wind Harmer
0.116
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.111
3145663CRESWEL
Solar/Wind Harmer
0.297
971163AH1-040 GEN
Solar/Wind Harmer
8.478
3150851SPRUNCC
Adder
0.485
939411AE1-173 GEN
Solar/Wind Harmer
43.623
3146206CASHIE
Solar/Wind Harmer
0.099
971547AH1-271 GEN
Solar/Wind Harmer
2.123
3145893MURPHYS
Solar/Wind Harmer
0.387
3145893MURPHYS
Solar/Wind Harmer
0.431
940641AE2-051 GEN
Solar/Wind Harmer
7.644
3146173TUNIS
Solar/Wind Harmer
0.095
3145683EARLEYS
Solar/Wind Harmer
0.094
3145963POPLR C
Solar/Wind Harmer
0.093
316174AB2-169 GEN
Solar/Wind Harmer
0.002
3146263WOODLND
Solar/Wind Harmer
0.091
3145823KELFORD
Solar/Wind Harmer
0.09
316023GEN1_S
Solar/Wind Harmer
0.201
316190AA2-174 GEN
Solar/Wind Harmer
0
316011AB1-132 GEN
Solar/Wind Harmer
1.573
962571AG1-106 GEN
Solar/Wind Harmer
1.231
3146293MARTNCO
Solar/Wind Harmer
0.08
960081AF2-299 GEN
Solar/Wind Harmer
0.817
3145796HORNRTN
Solar/Wind Harmer
0.279
3145796HORNRTN
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
0.084
3143526WINTERP
Solar/Wind Harmer
0.439
316212AC1-099_GEN
Solar/Wind Harmer
0.431
3145746EVERETS
Solar/Wind Harmer
0.083
3145746EVERETS
Solar/Wind Harmer
0.083
971795AH1-408 GEN
Solar/Wind Harmer
5.378
316494AC1-189 GEN
Solar/Wind Harmer
0.269
970919AG2-571 GEN
Solar/Wind Harmer
2.805
3147043LAWRENC
Adder
0.711
970087AG2-069 GEN
Solar/Wind Harmer
6.284
315722AD1-056 GEN
Solar/Wind Harmer
0.497
961671AG1-007 GEN
Solar/Wind Harmer
0.012
3146083TARBORO
Solar/Wind Harmer
0.077
3145493TOT1
Solar/Wind Harmer
0.342
3146233WITAKRS
Solar/Wind Harmer
0.302
316129AC1-054 GEN
Solar/Wind Harmer
0.277
316359AB2-059 GEN
Solar/Wind Harmer
0.264
316049AB1-081 GEN
Solar/Wind Harmer
0.421
3145543BTLEBRO
Solar/Wind Harmer
0.073
3145543BTLEBRO
Solar/Wind Harmer
0.059
3142053HEARTS
Solar/Wind Harmer
0.129
971065AG2-659 GEN
Solar/Wind Harmer
3.097
957481AF2-042 GEN
Solar/Wind Harmer
19.236
315693AD1-088 GEN
Solar/Wind Harmer
3.297
962491AG1-098 GEN
Solar/Wind Harmer
3.883
3143226MDLTHAN
Solar/Wind Harmer
0.067
315687AD1-152 GEN
Solar/Wind Harmer
0.002
316237AB2-079_GEN
Solar/Wind Harmer
0.001
970401AG2-262 GEN
Solar/Wind Harmer
0.348
970685AG2-442 GEN
Solar/Wind Harmer
4.283
970657AG2-426 GEN
Solar/Wind Harmer
4.227
970657AG2-426 GEN
Solar/Wind Harmer
0.886
3130086AYDLETT
Solar/Wind Harmer
0.482
3146386ELIZ CT
Solar/Wind Harmer
0.119
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.116
3146516WINFALL
Solar/Wind Harmer
0.116
3146516WINFALL
Solar/Wind Harmer
0.116
944641AF1-129 GEN
Adder
55.399
316240AF1-291 C
Solar/Wind Harmer
0.001
3146626S HERTFORD
Solar/Wind Harmer
0.115
3146626S HERTFORD
Solar/Wind Harmer
0.115
315742AE1-103 GEN
Solar/Wind Harmer
0.001
3146376EDENTON
Solar/Wind Harmer
0.491
3146376EDENTON
Solar/Wind Harmer
0.491
316065AD1-022 GEN
Solar/Wind Harmer
4.62
3145893MURPHYS
Solar/Wind Harmer
0.648
3145893MURPHYS
Solar/Wind Harmer
0.174
3144356SAPONY
Solar/Wind Harmer
0.808
3146173TUNIS
Solar/Wind Harmer
0.095
3146173TUNIS
Solar/Wind Harmer
0.095
3142666NORTHAMPTON
Solar/Wind Harmer
0.088
3142666NORTHAMPTON
Solar/Wind Harmer
0.088
3142666NORTHAMPTON
Solar/Wind Harmer
0.088
3142666NORTHAMPTON
Solar/Wind Harmer
0.053
316426AA2-053 GEN
Solar/Wind Harmer
0.293
3145933PARMELE
Solar/Wind Harmer
0.172
3145933PARMELE
Solar/Wind Harmer
0.086
316181AB2-040 GEN
Solar/Wind Harmer
0.123
3145593CAROLNA
Solar/Wind Harmer
0.085
3145593CAROLNA
Solar/Wind Harmer
0.085
966811AG1-552 GEN
Solar/Wind Harmer
0.922
3145593CAROLNA
Solar/Wind Harmer
0.106
3145796HORNRTN
Solar/Wind Harmer
0.254
3145783HORNRTN
Solar/Wind Harmer
1.502
3145783HORNRTN
Solar/Wind Harmer
1.202
3145783HORNRTN
Solar/Wind Harmer
0.376
3145783HORNRTN
Solar/Wind Harmer
0.15
3143526WINTERP
Solar/Wind Harmer
0.439
972185AH1-677 GEN
Adder
4.674
972187AH1-678 GEN
Adder
2.339
316274AC1-208 GEN
Solar/Wind Harmer
0.423
970933AG2-581 GEN
Solar/Wind Harmer
6.363
3145493TOT1
Solar/Wind Harmer
0.178
3145453TOT5
Solar/Wind Harmer
0.107
3145603CNETO
Solar/Wind Harmer
0.071
961601AG1-000A GEN
Solar/Wind Harmer
1.309
316263AC1-034 GEN
Solar/Wind Harmer
2.793
970099AG2-077 GEN
Solar/Wind Harmer
7.694
971223AH1-071 GEN
Solar/Wind Harmer
0.72
939181AE1-148 GEN
Solar/Wind Harmer
3.206
313527AB2-043 GEN
Solar/Wind Harmer
0.001
962561AG1-105 GEN
Solar/Wind Harmer
2.881
964791AG1-342 GEN
Solar/Wind Harmer
1.14
3146843MT LREL
Solar/Wind Harmer
0.059
3146843MT LREL
Solar/Wind Harmer
0.059
970323AG2-213 GEN
Solar/Wind Harmer
2.53
971775AH1-396 GEN
Solar/Wind Harmer
0.095
316034AC1-036 C
Solar/Wind Harmer
0.004
971741AH1-377 GEN
Solar/Wind Harmer
5.844
966871AG1-558 GEN
Solar/Wind Harmer
0.065
316327AA2-057 GEN
Solar/Wind Harmer
0.118
3146073TAR RVR
Solar/Wind Harmer
0.077
3146083TARBORO
Solar/Wind Harmer
0.077
3146233WITAKRS
Solar/Wind Harmer
0.38
3146233WITAKRS
Solar/Wind Harmer
0.052
3138543CONSLDL
Solar/Wind Harmer
0.05
961601AG1-000A GEN
Solar/Wind Harmer
5.236
3145543BTLEBRO
Solar/Wind Harmer
0.073
3145543BTLEBRO
Solar/Wind Harmer
0.073
971623AH1-311 GEN
Solar/Wind Harmer
0.147
316478AD1-087 GEN
Solar/Wind Harmer
0.24
316486AD2-202 GEN
Solar/Wind Harmer
0.07
3141316ARNOLDS
Adder
0.161
316131AB2-060 GEN
Solar/Wind Harmer
0.199
964241AG1-285 GEN
Solar/Wind Harmer
4.14
315785AD2-033 C
Solar/Wind Harmer
0.488
970257AG2-171 GEN
Solar/Wind Harmer
1.897
959311AF2-222 GEN
Solar/Wind Harmer
5.222
316473AC1-191 GEN
Solar/Wind Harmer
0.191
316248AF1-058 C
Solar/Wind Harmer
0
960061AF2-297 GEN
Solar/Wind Harmer
2.402
LAGNLTFEXP_LAGN->PJM
CLTF
1.924
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.054
TVALTFEXP_TVA->PJM
CLTF
0.95
CPLELTFEXP_CPLE->PJM
CLTF
4.035
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.643
NYPJM->LTFIMP_NY
CLTF
0.699
LGEELTFEXP_LGEE->PJM
CLTF
0.151
WECLTFEXP_WEC->PJM
CLTF
0.071
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.999
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.074
MECLTFEXP_MEC->PJM
CLTF
0.569
SIGELTFEXP_SIGE->PJM
CLTF
0.015

Details for 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: G2T567_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer
Contingency Name:
DVP_P4-2: G2T567_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.33 %
Rating:1107.0 MVA
Rating Type:C
MVA to Mitigate:1298.88
MW Contribution:1.1
Bus #Bus NameTypeMW Contribution
315749AE2-041 GEN
50/50
8.597
3141843SHACKLE
50/50
1.246
970575AG2-366 GEN
50/50
3.873
3142433PROV 92
50/50
0.437
3142433PROV 92
50/50
0.437
3150351NORNECKC2
50/50
2.247
3150921YORKTN3
50/50
4.644
3144216WINCHST
50/50
0.681
3143096IRON208
50/50
0.703
3143096IRON208
50/50
0.689
3150801HOPHCF4
50/50
0.909
971211AH1-065 GEN
50/50
1.097
3141766HARMONY
Solar/Wind Harmer
2.418
3142946ENON
Solar/Wind Harmer
-0.009
316203AE2-005 GEN
Solar/Wind Harmer
10.88
316280AD1-041 GEN
Solar/Wind Harmer
1.928
316156AD2-030 GEN
Solar/Wind Harmer
0.675
3141873WAN 176
Solar/Wind Harmer
3.001
316382AG1-145 C
Solar/Wind Harmer
0.748
962971AG1-146 GEN
Solar/Wind Harmer
4.59
316484AD2-074 GEN
Solar/Wind Harmer
6.116
970009AG2-005 GEN
Solar/Wind Harmer
3.037
316404AE1-155 C
Solar/Wind Harmer
4.63
970293AG2-193 GEN
Solar/Wind Harmer
2.776
3141906WESTMOR
Solar/Wind Harmer
-0.008
315759AF1-018 GEN
50/50
8.597
3142433PROV 92
50/50
0.437
3142433PROV 92
50/50
0.437
3150611CHESTG7
50/50
1.29
3150631CHESTG8
50/50
1.269
971047AG2-646 GEN
50/50
36.115
315976AC1-164 GENA
Solar/Wind Harmer
37.107
316169AC1-164_GENC
Solar/Wind Harmer
32.057
315975AC1-164 GENB
Solar/Wind Harmer
1.098
316314AB2-024 C
Solar/Wind Harmer
2.42
316059AD1-063 C
Solar/Wind Harmer
0.614
3143873LANEXA
Solar/Wind Harmer
-0.016
315662AE1-191 GEN
Solar/Wind Harmer
3.085
315666AE1-190 GEN
Solar/Wind Harmer
0.771
957601AF2-054 GEN
Solar/Wind Harmer
0.757
3141873WAN 176
Solar/Wind Harmer
-0.005
3141913WHIT STONE
Solar/Wind Harmer
-0.025
3138133OCRAN
Solar/Wind Harmer
-0.008
3141783LANCAST
Solar/Wind Harmer
-0.015
3141783LANCAST
Solar/Wind Harmer
-0.01
962981AG1-147 GEN
Solar/Wind Harmer
10.71
3141813NORNECK
Solar/Wind Harmer
-0.023
971167AH1-042 GEN
Solar/Wind Harmer
22.25
957831AF2-077 GEN
Solar/Wind Harmer
0.67
3138283WHITEMARSH
Solar/Wind Harmer
0.035
316223AC1-118
Solar/Wind Harmer
0.533
316312AB1-027
Solar/Wind Harmer
0.585
316132AB2-190 GEN1
Solar/Wind Harmer
1.721
316369SG1_INVT
Solar/Wind Harmer
2.986
972265AH1-717 GEN
Adder
11.202
3151201GRAVEL4
Adder
10.501
3151191GRAVEL3
Adder
10.368
3151211GRAVEL5
Adder
10.368
971445AH1-216 GEN
Solar/Wind Harmer
9.571
944491AF1-114 GEN
Solar/Wind Harmer
4.354
3152611GOSPORTB
Adder
1.595
3152621GOSPORTC
Adder
1.353
3152601GOSPORTA
Adder
1.249
3151081ELIZAR1
Adder
11.454
3151091ELIZAR2
Adder
11.255
316305AF2-043 C
Solar/Wind Harmer
0.415
957871AF2-081 GEN
Solar/Wind Harmer
6.845
319010AE1-072 C
Solar/Wind Harmer
2.757
3146406KITTY HAWK
Solar/Wind Harmer
0.011
315833AF1-017_GEN
Solar/Wind Harmer
2.581
316349AD2-085 GEN
Solar/Wind Harmer
1.209
316311AC2-079 GEN
Solar/Wind Harmer
6.853
315835AF2-110_GEN
Solar/Wind Harmer
1.695
3146486SUNBURY
Solar/Wind Harmer
-0.013
3146486SUNBURY
Solar/Wind Harmer
-0.013
313526AB2-022
Solar/Wind Harmer
0.362
316321Z2-027
Solar/Wind Harmer
0.36
3146396TANGLEW
Solar/Wind Harmer
0.245
3145176PASQUOTANK
Solar/Wind Harmer
-0.008
315611Z1-036_GEN2
Solar/Wind Harmer
3.157
3130156CHOWAN
Solar/Wind Harmer
-0.012
3130156CHOWAN
Solar/Wind Harmer
-0.012
3143316POE
Solar/Wind Harmer
-0.049
315816AE2-034 GEN
Solar/Wind Harmer
0.969
971285AH1-108 GEN
Adder
0.799
3130546PLYMOUTH
Solar/Wind Harmer
-0.012
315732AD1-074 GEN1
Solar/Wind Harmer
2.328
315733AD1-074 GEN2
Solar/Wind Harmer
2.328
315735AD1-075 GEN1
Solar/Wind Harmer
1.164
3146206CASHIE
Solar/Wind Harmer
-0.011
970601AG2-382 GEN
Solar/Wind Harmer
4.922
965291AG1-394 GEN
Solar/Wind Harmer
0.986
316318V4-068
Solar/Wind Harmer
0.273
3145893MURPHYS
Solar/Wind Harmer
-0.029
3145893MURPHYS
Solar/Wind Harmer
-0.011
316315AB2-025 C
Solar/Wind Harmer
0.295
315814AE2-033 C
Solar/Wind Harmer
10.13
3145513AHOSKIE
Solar/Wind Harmer
0.093
961941AG1-037 GEN
Solar/Wind Harmer
0.081
3145513AHOSKIE
Solar/Wind Harmer
-0.011
3145683EARLEYS
Solar/Wind Harmer
-0.021
3145683EARLEYS
Solar/Wind Harmer
-0.011
3145683EARLEYS
Solar/Wind Harmer
-0.011
3146043SEABORD
Solar/Wind Harmer
-0.01
315607AA1-063A GEN
Solar/Wind Harmer
1.031
3141843SHACKLE
50/50
1.246
966661AG1-536 GEN
50/50
6.076
3142433PROV 92
50/50
0.437
3142433PROV 92
50/50
0.437
3150351NORNECKC2
50/50
2.209
3150641CHESTS8
50/50
0.654
944631AF1-128 GEN
50/50
102.747
971353AH1-157 GEN
50/50
17.022
970017AG2-010 GEN
50/50
11.407
3143096IRON208
50/50
0.703
3150771HOPHCF1
50/50
0.625
3141766HARMONY
Solar/Wind Harmer
-0.005
971777AH1-397 GEN
Solar/Wind Harmer
3.035
3138133OCRAN
Solar/Wind Harmer
-0.015
316159AE1-175 C
Solar/Wind Harmer
0.666
964211AG1-282 GEN
Solar/Wind Harmer
0.735
3141726DUNNSVL
Solar/Wind Harmer
-0.097
961951AG1-038 GEN
Solar/Wind Harmer
3.2
962861AG1-135 GEN
Solar/Wind Harmer
9.029
3142433PROV 92
Solar/Wind Harmer
-0.095
316337AD2-073 GEN
Solar/Wind Harmer
0.587
971317AH1-138 GEN
Solar/Wind Harmer
2.668
3138126ROCKLANDING
Solar/Wind Harmer
0.059
3142416OLDCHRC
Solar/Wind Harmer
-0.045
3142416OLDCHRC
Solar/Wind Harmer
-0.017
970129AG2-093 GEN
Solar/Wind Harmer
3.887
316458AB2-190 GEN2
Solar/Wind Harmer
1.721
971069AG2-661 GEN
Solar/Wind Harmer
2.664
972135AH1-637 GEN
Solar/Wind Harmer
1.659
971647AH1-324 GEN
Solar/Wind Harmer
8.279
961611AG1-000B GEN
Solar/Wind Harmer
8.096
3151171GRAVELC
Adder
1.535
3145336SMITFLD
Solar/Wind Harmer
-0.061
957971AF2-091 GEN
Solar/Wind Harmer
1.48
316072AD1-144
Solar/Wind Harmer
0.296
315671AE2-027_GEN
Solar/Wind Harmer
10.697
316375AC2-012 GEN
Solar/Wind Harmer
4.87
3150981CHESPKA
Adder
1.564
316294AC1-161 GEN
Solar/Wind Harmer
4.47
944591AF1-124 GEN
Solar/Wind Harmer
62.912
3142543TWELFTH
Solar/Wind Harmer
-0.001
316246AF1-032 C
Solar/Wind Harmer
0.279
316388AE2-253 GEN
Solar/Wind Harmer
0.925
3146456SLIGO L269
Solar/Wind Harmer
-0.014
970659AG2-427 GEN
Solar/Wind Harmer
7.247
316381AD1-082 GEN
Solar/Wind Harmer
1.251
970661AG2-428 GEN
Solar/Wind Harmer
14.474
316093AE2-104_GEN
Solar/Wind Harmer
3.942
3146516WINFALL
Solar/Wind Harmer
-0.042
3146516WINFALL
Solar/Wind Harmer
-0.013
315800Z1-036_GEN1
Solar/Wind Harmer
3.157
3130156CHOWAN
Solar/Wind Harmer
-0.012
3145663CRESWEL
Solar/Wind Harmer
-0.033
971163AH1-040 GEN
Solar/Wind Harmer
11.23
3150851SPRUNCC
Adder
0.488
939411AE1-173 GEN
Solar/Wind Harmer
57.793
3146206CASHIE
Solar/Wind Harmer
-0.011
971547AH1-271 GEN
Solar/Wind Harmer
2.813
3145893MURPHYS
Solar/Wind Harmer
-0.044
3145893MURPHYS
Solar/Wind Harmer
0.325
940641AE2-051 GEN
Solar/Wind Harmer
10.131
3146173TUNIS
Solar/Wind Harmer
-0.011
3145683EARLEYS
Solar/Wind Harmer
-0.011
3145963POPLR C
Solar/Wind Harmer
-0.011
316174AB2-169 GEN
Solar/Wind Harmer
1.602
3146263WOODLND
Solar/Wind Harmer
-0.01
3145823KELFORD
Solar/Wind Harmer
-0.01
316023GEN1_S
Solar/Wind Harmer
0.683
316190AA2-174 GEN
Solar/Wind Harmer
0.12
316011AB1-132 GEN
Solar/Wind Harmer
2.05
962571AG1-106 GEN
Solar/Wind Harmer
1.408
3146293MARTNCO
Solar/Wind Harmer
0.06
960081AF2-299 GEN
Solar/Wind Harmer
1.084
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.01
3145783HORNRTN
Solar/Wind Harmer
-0.01
3143526WINTERP
Solar/Wind Harmer
-0.049
316212AC1-099_GEN
Solar/Wind Harmer
0.823
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
971795AH1-408 GEN
Solar/Wind Harmer
6.851
316494AC1-189 GEN
Solar/Wind Harmer
0.969
970919AG2-571 GEN
Solar/Wind Harmer
2.828
3147043LAWRENC
Adder
0.717
970087AG2-069 GEN
Solar/Wind Harmer
8.34
315722AD1-056 GEN
Solar/Wind Harmer
0.93
961671AG1-007 GEN
Solar/Wind Harmer
0.11
3146083TARBORO
Solar/Wind Harmer
-0.009
3145493TOT1
Solar/Wind Harmer
0.258
3146233WITAKRS
Solar/Wind Harmer
-0.034
316129AC1-054 GEN
Solar/Wind Harmer
0.731
316359AB2-059 GEN
Solar/Wind Harmer
1.123
316049AB1-081 GEN
Solar/Wind Harmer
0.899
3145543BTLEBRO
Solar/Wind Harmer
-0.008
3150341NORNECKC1
50/50
2.321
3150341NORNECKC1
50/50
2.302
963611AG1-210 GEN
50/50
0.743
3150621CHESTS7
50/50
0.592
3150781HOPHCF2
50/50
0.625
3150791HOPHCF3
50/50
0.625
3150761HOPPOLC
50/50
0.397
971213AH1-066 GEN
50/50
0.548
316075AC2-137 C
Solar/Wind Harmer
0.758
3142946ENON
Solar/Wind Harmer
-0.003
316441AF1-014 GEN
Solar/Wind Harmer
1.74
316487AF1-042 GEN
Solar/Wind Harmer
3.2
958261AF2-120 GEN
Solar/Wind Harmer
9.3
316077AC2-138 C
Solar/Wind Harmer
0.495
3150691DARBY 3
Adder
10.751
3150701DARBY 4
Adder
10.726
3150681DARBY 2
Adder
10.713
3150671DARBY 1
Adder
10.701
316033AB2-134 GEN
Solar/Wind Harmer
5.389
315697AD1-025 GEN
Solar/Wind Harmer
3.38
316236AE1-162_GEN
Solar/Wind Harmer
0.464
316036AC1-147 C
Solar/Wind Harmer
0.38
3150991CHESPKB
Adder
1.312
3150991CHESPKB
Adder
1.28
316316AC1-027 C
Solar/Wind Harmer
0.428
3142956BIRDNECK
Solar/Wind Harmer
0.748
316185AD1-033 GEN
Solar/Wind Harmer
1.461
3145506HICKORY
Solar/Wind Harmer
-0.055
3145506HICKORY
Solar/Wind Harmer
-0.033
3145506HICKORY
Solar/Wind Harmer
-0.008
3142366NRTHEST
Adder
0.399
316339AD2-160 GEN
Solar/Wind Harmer
0.925
316018AA1-139 ULT2
Solar/Wind Harmer
1.173
316017AA1-139 ULT1
Solar/Wind Harmer
1.108
3137176SLIGO L2192
Solar/Wind Harmer
-0.054
3146456SLIGO L269
Solar/Wind Harmer
1.612
970657AG2-426 GEN
Solar/Wind Harmer
4.26
970657AG2-426 GEN
Solar/Wind Harmer
0.891
3130086AYDLETT
Solar/Wind Harmer
-0.054
3146386ELIZ CT
Solar/Wind Harmer
-0.013
316431W1029_GEN1
Solar/Wind Harmer
2.396
316433W1029_GEN2
Solar/Wind Harmer
2.396
3146516WINFALL
Solar/Wind Harmer
-0.013
3146516WINFALL
Solar/Wind Harmer
-0.013
3146516WINFALL
Solar/Wind Harmer
-0.013
944641AF1-129 GEN
Adder
55.701
316240AF1-291 C
Solar/Wind Harmer
0.393
3146626S HERTFORD
Solar/Wind Harmer
-0.013
3146626S HERTFORD
Solar/Wind Harmer
-0.013
315742AE1-103 GEN
Solar/Wind Harmer
1.307
3146376EDENTON
Solar/Wind Harmer
0.371
3146376EDENTON
Solar/Wind Harmer
0.371
316065AD1-022 GEN
Solar/Wind Harmer
5.673
3145893MURPHYS
Solar/Wind Harmer
0.306
3145893MURPHYS
Solar/Wind Harmer
-0.02
3144356SAPONY
Solar/Wind Harmer
0.381
3146173TUNIS
Solar/Wind Harmer
-0.011
3146173TUNIS
Solar/Wind Harmer
-0.011
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
316426AA2-053 GEN
Solar/Wind Harmer
0.991
3145933PARMELE
Solar/Wind Harmer
-0.019
3145933PARMELE
Solar/Wind Harmer
-0.01
316181AB2-040 GEN
Solar/Wind Harmer
1.344
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.083
3145593CAROLNA
Solar/Wind Harmer
0.08
3145796HORNRTN
Solar/Wind Harmer
-0.029
3145783HORNRTN
Solar/Wind Harmer
1.135
3145783HORNRTN
Solar/Wind Harmer
0.908
3145783HORNRTN
Solar/Wind Harmer
0.284
3145783HORNRTN
Solar/Wind Harmer
0.114
3143526WINTERP
Solar/Wind Harmer
-0.049
972185AH1-677 GEN
Adder
4.71
972187AH1-678 GEN
Adder
2.357
316274AC1-208 GEN
Solar/Wind Harmer
0.997
970933AG2-581 GEN
Solar/Wind Harmer
8.445
3145493TOT1
Solar/Wind Harmer
0.135
3145453TOT5
Solar/Wind Harmer
0.081
3145603CNETO
Solar/Wind Harmer
0.054
961601AG1-000A GEN
Solar/Wind Harmer
3.28
316263AC1-034 GEN
Solar/Wind Harmer
3.905
970099AG2-077 GEN
Solar/Wind Harmer
8.553
970737AG2-469 GEN
Solar/Wind Harmer
8.932
3142416OLDCHRC
Solar/Wind Harmer
1.751
970133AG2-095 GEN
Solar/Wind Harmer
1.95
970129AG2-093 GEN
Solar/Wind Harmer
9.595
315778AD1-151 GEN
Solar/Wind Harmer
14.584
961611AG1-000B GEN
Solar/Wind Harmer
3.454
3151221GRAVEL6
Adder
10.489
3151171GRAVELC
Adder
2.018
3145336SMITFLD
Solar/Wind Harmer
-0.006
3144536CHRHLND
Solar/Wind Harmer
-0.002
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
11.601
965281AG1-393 GEN
Solar/Wind Harmer
1.753
315773AC2-141 GEN
Solar/Wind Harmer
5.781
944581AF1-123 GEN
Solar/Wind Harmer
62.686
944601AF1-125 GEN
Solar/Wind Harmer
61.708
315813AE1-149 C
Solar/Wind Harmer
8.541
3146456SLIGO L269
Solar/Wind Harmer
-0.014
971153AH1-033 GEN
Solar/Wind Harmer
1.664
970659AG2-427 GEN
Solar/Wind Harmer
1.284
316083AB2-161 GEN
Solar/Wind Harmer
2.213
970661AG2-428 GEN
Solar/Wind Harmer
2.565
316320Y1-086
Solar/Wind Harmer
0.787
316435W1029_GEN3
Solar/Wind Harmer
2.396
3146516WINFALL
Solar/Wind Harmer
-0.013
3146626S HERTFORD
Solar/Wind Harmer
-0.013
3145273HOLLAND
Solar/Wind Harmer
-0.01
315839AE2-212 C
Solar/Wind Harmer
0.385
3146376EDENTON
Solar/Wind Harmer
-0.012
315614AA2-178 GEN
Solar/Wind Harmer
1.292
3150861SPRUNCD
Adder
0.488
971157AH1-035 GEN
Solar/Wind Harmer
1.448
315737AD1-076 GEN
Solar/Wind Harmer
2.188
3146206CASHIE
Solar/Wind Harmer
-0.011
3156081AA2-088 GEN
Solar/Wind Harmer
3.642
3145893MURPHYS
Solar/Wind Harmer
0.076
3145893MURPHYS
Solar/Wind Harmer
-0.011
957521AF2-046 GEN
Solar/Wind Harmer
8.591
961681AG1-008 GEN
Solar/Wind Harmer
8.591
3156021HOLLOMANSOL
Solar/Wind Harmer
1.466
3146173TUNIS
Solar/Wind Harmer
-0.011
316463AE2-346 GEN
Solar/Wind Harmer
0.173
316140AB2-099
Solar/Wind Harmer
0.072
962331AG1-082 GEN
Solar/Wind Harmer
1.339
3145963POPLR C
Solar/Wind Harmer
-0.011
3146263WOODLND
Solar/Wind Harmer
-0.01
316317KELFORD C
Solar/Wind Harmer
0.481
3145823KELFORD
Solar/Wind Harmer
-0.01
316365GEN2_N
Solar/Wind Harmer
0.683
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
3145933PARMELE
Solar/Wind Harmer
-0.01
966801AG1-551 GEN
Solar/Wind Harmer
1.217
966621AG1-532 GEN
Solar/Wind Harmer
0.196
313506AB2-031 GEN
Solar/Wind Harmer
0.774
3145796HORNRTN
Solar/Wind Harmer
-0.038
3145796HORNRTN
Solar/Wind Harmer
-0.01
316210AC1-098 GEN
Solar/Wind Harmer
1.481
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
970917AG2-570 GEN
Solar/Wind Harmer
22.341
3147043LAWRENC
Solar/Wind Harmer
-0.005
315724AD1-057 GEN
Solar/Wind Harmer
0.511
316327AA2-057 GEN
Solar/Wind Harmer
0.893
3146073TAR RVR
Solar/Wind Harmer
-0.009
3146083TARBORO
Solar/Wind Harmer
-0.009
3146233WITAKRS
Solar/Wind Harmer
0.18
3146233WITAKRS
Solar/Wind Harmer
-0.006
3138543CONSLDL
Solar/Wind Harmer
-0.006
961601AG1-000A GEN
Solar/Wind Harmer
3.321
3145543BTLEBRO
Solar/Wind Harmer
-0.008
3145543BTLEBRO
Solar/Wind Harmer
-0.008
3141316ARNOLDS
Adder
0.162
315652AC1-086 GEN
Solar/Wind Harmer
11.023
3146033SCOT NK
Solar/Wind Harmer
-0.039
941031AE2-094 GEN
Solar/Wind Harmer
18.24
944011AF1-069 GEN
Solar/Wind Harmer
5.715
946281AF1-292 GEN
Solar/Wind Harmer
0.216
316087AB2-174 GEN
Solar/Wind Harmer
1.374
3137643SOCKMAN
Solar/Wind Harmer
-0.038
3145796HORNRTN
Solar/Wind Harmer
-0.03
3145796HORNRTN
Solar/Wind Harmer
-0.004
316233AE1-074 FULL
Solar/Wind Harmer
0.257
971281AH1-106 GEN
Solar/Wind Harmer
1.554
971283AH1-107 GEN
Solar/Wind Harmer
1.554
970673AG2-436 GEN
Solar/Wind Harmer
20.02
970673AG2-436 GEN
Solar/Wind Harmer
10.137
316005AA1-067
Solar/Wind Harmer
0.189
3145746EVERETS
Solar/Wind Harmer
-0.037
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
970181AG2-120 GEN
Solar/Wind Harmer
1.227
971967AH1-528 GEN
Solar/Wind Harmer
17.555
957861AF2-080 GEN
Solar/Wind Harmer
3.94
970085AG2-068 GEN
Solar/Wind Harmer
5.56
970581AG2-369 GEN
Solar/Wind Harmer
4.782
316420AA1-050 GEN
Solar/Wind Harmer
1.009
3145573BETHELC
Solar/Wind Harmer
-0.009
3145573BETHELC
Solar/Wind Harmer
-0.009
316319Z2-044 C
Solar/Wind Harmer
0.475
970831AG2-522 GEN
Solar/Wind Harmer
4.233
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3142053HEARTS
Solar/Wind Harmer
0.098
971065AG2-659 GEN
Solar/Wind Harmer
4.113
957481AF2-042 GEN
Solar/Wind Harmer
21.381
LAGNLTFEXP_LAGN->PJM
CLTF
2.023
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.202
TVALTFEXP_TVA->PJM
CLTF
0.999
CPLELTFEXP_CPLE->PJM
CLTF
4.088
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.298
NYPJM->LTFIMP_NY
CLTF
0.668
LGEELTFEXP_LGEE->PJM
CLTF
0.185
WECLTFEXP_WEC->PJM
CLTF
0.09
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.709
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.259
MECLTFEXP_MEC->PJM
CLTF
0.651
SIGELTFEXP_SIGE->PJM
CLTF
0.018

Details for 6CHESTF A-3CHESTFLD 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 211_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6CHESTF A-3CHESTFLD 230.0/115.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 211_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.28 %
Rating:250.04 MVA
Rating Type:B
MVA to Mitigate:258.24
MW Contribution:0.55
Bus #Bus NameTypeMW Contribution
3150641CHESTS8
50/50
0.391
944631AF1-128 GEN
50/50
61.418
3150771HOPHCF1
50/50
0.315
3143096IRON208
50/50
0.314
970129AG2-093 GEN
Solar/Wind Harmer
1.899
316458AB2-190 GEN2
Solar/Wind Harmer
0.352
971069AG2-661 GEN
Solar/Wind Harmer
1.049
3142543TWELFTH
Solar/Wind Helper
0.021
3142433PROV 92
Solar/Wind Helper
0.741
3150611CHESTG7
50/50
0.771
3150631CHESTG8
50/50
0.759
971047AG2-646 GEN
50/50
21.588
316132AB2-190 GEN1
Solar/Wind Harmer
0.352
972265AH1-717 GEN
Adder
2.756
3151201GRAVEL4
Adder
2.583
3151191GRAVEL3
Adder
2.551
3151211GRAVEL5
Adder
2.551
3150801HOPHCF4
50/50
0.458
971211AH1-065 GEN
50/50
0.552
3143096IRON208
50/50
0.314
3143096IRON208
50/50
0.308
3142946ENON
Solar/Wind Harmer
0.032
970133AG2-095 GEN
Solar/Wind Harmer
0.745
970129AG2-093 GEN
Solar/Wind Harmer
4.036
315778AD1-151 GEN
Solar/Wind Harmer
4.722
3151221GRAVEL6
Adder
2.58
3150621CHESTS7
50/50
0.354
3150781HOPHCF2
50/50
0.315
3150791HOPHCF3
50/50
0.315
3150761HOPPOLC
50/50
0.2
971213AH1-066 GEN
50/50
0.276
3142946ENON
Solar/Wind Harmer
0.01
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.043
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.134
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.033
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.066
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.037
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.208

Details for 6CHESTF A-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2049_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6CHESTF A-6CHCKAHM 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2049_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.69 %
Rating:584.68 MVA
Rating Type:B
MVA to Mitigate:635.47
MW Contribution:1.27
Bus #Bus NameTypeMW Contribution
3150611CHESTG7
50/50
2.243
3150631CHESTG8
50/50
2.207
971047AG2-646 GEN
50/50
62.791
970603AG2-384 GEN
50/50
1.872
316132AB2-190 GEN1
Solar/Wind Harmer
0.772
316369SG1_INVT
Solar/Wind Harmer
0.004
316233AE1-074 FULL
Solar/Wind Harmer
0.064
971281AH1-106 GEN
Solar/Wind Harmer
1.101
971283AH1-107 GEN
Solar/Wind Harmer
1.101
3143316POE
Solar/Wind Harmer
0.256
316059AD1-063 C
Solar/Wind Helper
0.232
3141813NORNECK
Solar/Wind Helper
0.208
3141783LANCAST
Solar/Wind Helper
0.119
3141783LANCAST
Solar/Wind Helper
0.079
3138133OCRAN
Solar/Wind Helper
0.059
3141913WHIT STONE
Solar/Wind Helper
0.197
957601AF2-054 GEN
Solar/Wind Helper
0.261
3141873WAN 176
Solar/Wind Helper
0.039
315662AE1-191 GEN
Solar/Wind Helper
1.03
315666AE1-190 GEN
Solar/Wind Helper
0.257
316223AC1-118
Solar/Wind Helper
0.278
3143873LANEXA
Solar/Wind Helper
0.109
957831AF2-077 GEN
Solar/Wind Helper
0.182
316312AB1-027
Solar/Wind Helper
0.252
3150621CHESTS7
50/50
1.03
3150641CHESTS8
50/50
1.137
944631AF1-128 GEN
50/50
178.64
3143096IRON208
50/50
1.104
3150771HOPHCF1
50/50
0.725
970129AG2-093 GEN
Solar/Wind Harmer
4.184
316458AB2-190 GEN2
Solar/Wind Harmer
0.772
971069AG2-661 GEN
Solar/Wind Harmer
2.213
315671AE2-027_GEN
Solar/Wind Harmer
6.36
971647AH1-324 GEN
Solar/Wind Harmer
4.018
3143526WINTERP
Solar/Wind Harmer
0.413
3142543TWELFTH
Solar/Wind Harmer
0.007
961611AG1-000B GEN
Solar/Wind Harmer
4.044
970659AG2-427 GEN
Solar/Wind Harmer
3.04
316381AD1-082 GEN
Solar/Wind Harmer
0.063
3141766HARMONY
Solar/Wind Helper
0.046
964211AG1-282 GEN
Solar/Wind Helper
0.298
3141726DUNNSVL
Solar/Wind Helper
0.885
316337AD2-073 GEN
Solar/Wind Helper
0.303
3138133OCRAN
Solar/Wind Helper
0.118
316159AE1-175 C
Solar/Wind Helper
0.281
3142416OLDCHRC
Solar/Wind Helper
0.344
3142416OLDCHRC
Solar/Wind Helper
0.132
3143096IRON208
50/50
1.104
3143096IRON208
50/50
1.082
3150801HOPHCF4
50/50
1.054
971211AH1-065 GEN
50/50
1.272
970133AG2-095 GEN
Solar/Wind Harmer
1.717
970129AG2-093 GEN
Solar/Wind Harmer
8.891
315778AD1-151 GEN
Solar/Wind Harmer
9.957
965281AG1-393 GEN
Solar/Wind Harmer
1.019
315813AE1-149 C
Solar/Wind Harmer
4.138
315839AE2-212 C
Solar/Wind Harmer
0.001
961611AG1-000B GEN
Solar/Wind Harmer
2.056
970659AG2-427 GEN
Solar/Wind Harmer
0.665
316083AB2-161 GEN
Solar/Wind Harmer
0.001
316404AE1-155 C
Solar/Wind Helper
1.724
316484AD2-074 GEN
Solar/Wind Helper
0.39
316156AD2-030 GEN
Solar/Wind Helper
0.294
316280AD1-041 GEN
Solar/Wind Helper
0.643
316382AG1-145 C
Solar/Wind Helper
0.249
3141906WESTMOR
Solar/Wind Helper
0.073
3150781HOPHCF2
50/50
0.725
3150791HOPHCF3
50/50
0.725
3150761HOPPOLC
50/50
0.46
971213AH1-066 GEN
50/50
0.636
944641AF1-129 GEN
50/50
44.379
316033AB2-134 GEN
Solar/Wind Harmer
0.007
315697AD1-025 GEN
Solar/Wind Harmer
0.125
316240AF1-291 C
Solar/Wind Harmer
0.001
3143526WINTERP
Solar/Wind Harmer
0.413
970657AG2-426 GEN
Solar/Wind Harmer
2
970657AG2-426 GEN
Solar/Wind Harmer
0.419
316075AC2-137 C
Solar/Wind Helper
0.396
316077AC2-138 C
Solar/Wind Helper
0.196
316487AF1-042 GEN
Solar/Wind Helper
0.204
LAGNLTFEXP_LAGN->PJM
CLTF
0.295
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.372
TVALTFEXP_TVA->PJM
CLTF
0.147
CPLELTFEXP_CPLE->PJM
CLTF
0.692
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.201
NYPJM->LTFIMP_NY
CLTF
0.188
LGEELTFEXP_LGEE->PJM
CLTF
0.009
WECLTFEXP_WEC->PJM
CLTF
0.002
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.461
MECLTFEXP_MEC->PJM
CLTF
0.055
SIGELTFEXP_SIGE->PJM
CLTF
0.001

Details for 6CHESTF A-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2050_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6CHESTF A-6CHCKAHM 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2050_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.83 %
Rating:584.68 MVA
Rating Type:B
MVA to Mitigate:612.9
MW Contribution:1.27
Bus #Bus NameTypeMW Contribution
3150611CHESTG7
50/50
2.243
3150631CHESTG8
50/50
2.207
971047AG2-646 GEN
50/50
62.79
970603AG2-384 GEN
50/50
1.872
316132AB2-190 GEN1
Solar/Wind Harmer
0.772
316369SG1_INVT
Solar/Wind Harmer
0.004
316233AE1-074 FULL
Solar/Wind Harmer
0.064
971281AH1-106 GEN
Solar/Wind Harmer
1.101
971283AH1-107 GEN
Solar/Wind Harmer
1.101
3143316POE
Solar/Wind Harmer
0.256
316059AD1-063 C
Solar/Wind Helper
0.232
3141813NORNECK
Solar/Wind Helper
0.208
3141783LANCAST
Solar/Wind Helper
0.119
3141783LANCAST
Solar/Wind Helper
0.079
3138133OCRAN
Solar/Wind Helper
0.059
3141913WHIT STONE
Solar/Wind Helper
0.197
957601AF2-054 GEN
Solar/Wind Helper
0.261
3141873WAN 176
Solar/Wind Helper
0.039
315662AE1-191 GEN
Solar/Wind Helper
1.03
315666AE1-190 GEN
Solar/Wind Helper
0.257
316223AC1-118
Solar/Wind Helper
0.278
3143873LANEXA
Solar/Wind Helper
0.109
957831AF2-077 GEN
Solar/Wind Helper
0.182
316312AB1-027
Solar/Wind Helper
0.252
3150641CHESTS8
50/50
1.137
944631AF1-128 GEN
50/50
178.638
3143096IRON208
50/50
1.104
3150771HOPHCF1
50/50
0.725
970129AG2-093 GEN
Solar/Wind Harmer
4.184
316458AB2-190 GEN2
Solar/Wind Harmer
0.772
971069AG2-661 GEN
Solar/Wind Harmer
2.213
315671AE2-027_GEN
Solar/Wind Harmer
6.36
971647AH1-324 GEN
Solar/Wind Harmer
4.018
3143526WINTERP
Solar/Wind Harmer
0.413
3142543TWELFTH
Solar/Wind Harmer
0.007
961611AG1-000B GEN
Solar/Wind Harmer
4.044
970659AG2-427 GEN
Solar/Wind Harmer
3.04
316381AD1-082 GEN
Solar/Wind Harmer
0.063
3141766HARMONY
Solar/Wind Helper
0.046
964211AG1-282 GEN
Solar/Wind Helper
0.298
3141726DUNNSVL
Solar/Wind Helper
0.885
316337AD2-073 GEN
Solar/Wind Helper
0.303
3138133OCRAN
Solar/Wind Helper
0.118
316159AE1-175 C
Solar/Wind Helper
0.281
3142416OLDCHRC
Solar/Wind Helper
0.344
3142416OLDCHRC
Solar/Wind Helper
0.132
3150621CHESTS7
50/50
1.03
3150781HOPHCF2
50/50
0.725
3150791HOPHCF3
50/50
0.725
3150761HOPPOLC
50/50
0.46
971213AH1-066 GEN
50/50
0.636
944641AF1-129 GEN
50/50
44.377
3142946ENON
Solar/Wind Harmer
0.035
316033AB2-134 GEN
Solar/Wind Harmer
0.007
315697AD1-025 GEN
Solar/Wind Harmer
0.125
316240AF1-291 C
Solar/Wind Harmer
0.001
3143526WINTERP
Solar/Wind Harmer
0.413
970657AG2-426 GEN
Solar/Wind Harmer
2
970657AG2-426 GEN
Solar/Wind Harmer
0.419
316075AC2-137 C
Solar/Wind Helper
0.396
316077AC2-138 C
Solar/Wind Helper
0.196
316487AF1-042 GEN
Solar/Wind Helper
0.204
3143096IRON208
50/50
1.104
3143096IRON208
50/50
1.082
3150801HOPHCF4
50/50
1.054
971211AH1-065 GEN
50/50
1.272
3142946ENON
Solar/Wind Harmer
0.118
970133AG2-095 GEN
Solar/Wind Harmer
1.717
970129AG2-093 GEN
Solar/Wind Harmer
8.891
315778AD1-151 GEN
Solar/Wind Harmer
9.957
965281AG1-393 GEN
Solar/Wind Harmer
1.019
315813AE1-149 C
Solar/Wind Harmer
4.138
315839AE2-212 C
Solar/Wind Harmer
0.001
961611AG1-000B GEN
Solar/Wind Harmer
2.056
970659AG2-427 GEN
Solar/Wind Harmer
0.665
316083AB2-161 GEN
Solar/Wind Harmer
0.001
316404AE1-155 C
Solar/Wind Helper
1.724
316484AD2-074 GEN
Solar/Wind Helper
0.39
316156AD2-030 GEN
Solar/Wind Helper
0.294
316280AD1-041 GEN
Solar/Wind Helper
0.644
316382AG1-145 C
Solar/Wind Helper
0.249
3141906WESTMOR
Solar/Wind Helper
0.073
LAGNLTFEXP_LAGN->PJM
CLTF
0.295
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.371
TVALTFEXP_TVA->PJM
CLTF
0.147
CPLELTFEXP_CPLE->PJM
CLTF
0.692
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.197
NYPJM->LTFIMP_NY
CLTF
0.188
LGEELTFEXP_LGEE->PJM
CLTF
0.008
WECLTFEXP_WEC->PJM
CLTF
0.002
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.46
MECLTFEXP_MEC->PJM
CLTF
0.054
SIGELTFEXP_SIGE->PJM
CLTF
0.001

Details for 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6CHESTF A-6IRON208 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 557_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.61 %
Rating:663.64 MVA
Rating Type:B
MVA to Mitigate:740.71
MW Contribution:0.98
Bus #Bus NameTypeMW Contribution
3150611CHESTG7
50/50
1.633
3150631CHESTG8
50/50
1.607
971047AG2-646 GEN
50/50
45.726
315759AF1-018 GEN
50/50
3.414
316132AB2-190 GEN1
Solar/Wind Harmer
0.67
315976AC1-164 GENA
Solar/Wind Harmer
12.162
316169AC1-164_GENC
Solar/Wind Harmer
10.507
315975AC1-164 GENB
Solar/Wind Harmer
0.36
316369SG1_INVT
Solar/Wind Harmer
0.004
316314AB2-024 C
Solar/Wind Harmer
0
316059AD1-063 C
Solar/Wind Harmer
0.001
972265AH1-717 GEN
Adder
7.261
3151201GRAVEL4
Adder
6.807
3151191GRAVEL3
Adder
6.721
3151211GRAVEL5
Adder
6.721
3143873LANEXA
Solar/Wind Harmer
0.056
970189AG2-124 GEN
Solar/Wind Harmer
2.733
315662AE1-191 GEN
Solar/Wind Harmer
0.003
315666AE1-190 GEN
Solar/Wind Harmer
0.001
3141873WAN 176
Solar/Wind Harmer
0.018
3141913WHIT STONE
Solar/Wind Harmer
0.09
3138133OCRAN
Solar/Wind Harmer
0.027
3141783LANCAST
Solar/Wind Harmer
0.053
3141783LANCAST
Solar/Wind Harmer
0.035
3138283WHITEMARSH
Solar/Wind Harmer
0.02
962981AG1-147 GEN
Solar/Wind Harmer
3.244
970327AG2-215 GEN
Solar/Wind Harmer
2.818
3142433PROV 92
Adder
0.165
3142433PROV 92
Adder
0.165
971445AH1-216 GEN
Solar/Wind Harmer
5.957
971167AH1-042 GEN
Solar/Wind Harmer
7.355
3141813NORNECK
Solar/Wind Harmer
0.081
3152611GOSPORTB
Adder
0.865
3152621GOSPORTC
Adder
0.734
3152601GOSPORTA
Adder
0.677
3151081ELIZAR1
Adder
6.186
3151091ELIZAR2
Adder
6.079
316223AC1-118
Solar/Wind Harmer
0.048
315833AF1-017_GEN
Solar/Wind Harmer
0
316349AD2-085 GEN
Solar/Wind Harmer
0.045
316311AC2-079 GEN
Solar/Wind Harmer
1.899
316305AF2-043 C
Solar/Wind Harmer
0.001
957871AF2-081 GEN
Solar/Wind Harmer
3.21
319010AE1-072 C
Solar/Wind Harmer
0.323
315835AF2-110_GEN
Solar/Wind Harmer
0.44
3146406KITTY HAWK
Solar/Wind Harmer
0.008
313526AB2-022
Solar/Wind Harmer
0.034
3150641CHESTS8
50/50
0.828
944631AF1-128 GEN
50/50
130.091
3150771HOPHCF1
50/50
0.557
3152331SURRY 2
50/50
2.862
970129AG2-093 GEN
Solar/Wind Harmer
3.585
316458AB2-190 GEN2
Solar/Wind Harmer
0.67
971069AG2-661 GEN
Solar/Wind Harmer
2.098
971647AH1-324 GEN
Solar/Wind Harmer
4.574
961611AG1-000B GEN
Solar/Wind Harmer
5.304
3141766HARMONY
Solar/Wind Harmer
0.019
316159AE1-175 C
Solar/Wind Harmer
0.081
3151171GRAVELC
Adder
0.995
971777AH1-397 GEN
Solar/Wind Harmer
0.243
3141843SHACKLE
Adder
0.471
3138133OCRAN
Solar/Wind Harmer
0.054
971317AH1-138 GEN
Solar/Wind Harmer
0.639
3142433PROV 92
Solar/Wind Harmer
0.34
3142433PROV 92
Adder
0.165
3142433PROV 92
Adder
0.165
962861AG1-135 GEN
Solar/Wind Harmer
2.709
3141726DUNNSVL
Solar/Wind Harmer
0.337
3138126ROCKLANDING
Solar/Wind Harmer
0.039
3146486SUNBURY
Solar/Wind Harmer
0.063
3146486SUNBURY
Solar/Wind Harmer
0.063
316321Z2-027
Solar/Wind Harmer
0.012
3146396TANGLEW
Solar/Wind Harmer
0.172
3145176PASQUOTANK
Solar/Wind Harmer
0.039
315611Z1-036_GEN2
Solar/Wind Harmer
0
3130156CHOWAN
Solar/Wind Harmer
0.057
3130156CHOWAN
Solar/Wind Harmer
0.057
316233AE1-074 FULL
Solar/Wind Helper
0.475
3150621CHESTS7
50/50
0.75
3150781HOPHCF2
50/50
0.557
3150791HOPHCF3
50/50
0.557
3150761HOPPOLC
50/50
0.353
971213AH1-066 GEN
50/50
0.488
3142946ENON
Solar/Wind Harmer
0.022
316033AB2-134 GEN
Solar/Wind Harmer
0.007
315697AD1-025 GEN
Solar/Wind Harmer
0.127
958261AF2-120 GEN
Solar/Wind Harmer
2.785
316236AE1-162_GEN
Solar/Wind Harmer
0.001
316075AC2-137 C
Solar/Wind Harmer
0.023
316077AC2-138 C
Solar/Wind Harmer
0
3150341NORNECKC1
Adder
0.851
3150341NORNECKC1
Adder
0.845
970657AG2-426 GEN
Solar/Wind Harmer
2.421
970657AG2-426 GEN
Solar/Wind Harmer
0.507
316036AC1-147 C
Solar/Wind Harmer
0.013
3150991CHESPKB
Adder
0.712
3150991CHESPKB
Adder
0.694
316316AC1-027 C
Solar/Wind Harmer
0.064
3142956BIRDNECK
Solar/Wind Harmer
0
316185AD1-033 GEN
Solar/Wind Harmer
0.002
3145506HICKORY
Solar/Wind Harmer
0.26
3145506HICKORY
Solar/Wind Harmer
0.156
3145506HICKORY
Solar/Wind Harmer
0.039
316339AD2-160 GEN
Solar/Wind Harmer
0.105
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
316017AA1-139 ULT1
Solar/Wind Harmer
0.036
3137176SLIGO L2192
Solar/Wind Harmer
0.256
3146456SLIGO L269
Solar/Wind Harmer
1.137
3130086AYDLETT
Solar/Wind Harmer
0.256
3146386ELIZ CT
Solar/Wind Harmer
0.063
316431W1029_GEN1
Solar/Wind Harmer
0
316433W1029_GEN2
Solar/Wind Harmer
0
3146516WINFALL
Solar/Wind Harmer
0.061
3146516WINFALL
Solar/Wind Harmer
0.061
3146516WINFALL
Solar/Wind Harmer
0.061
3146626S HERTFORD
Solar/Wind Harmer
0.06
3146626S HERTFORD
Solar/Wind Harmer
0.06
315742AE1-103 GEN
Solar/Wind Harmer
0.001
3146376EDENTON
Solar/Wind Harmer
0.255
3146376EDENTON
Solar/Wind Harmer
0.255
3143526WINTERP
Solar/Wind Helper
1.618
3145336SMITFLD
Solar/Wind Harmer
0.335
3150351NORNECKC2
Adder
0.811
316337AD2-073 GEN
Solar/Wind Harmer
0.065
316072AD1-144
Solar/Wind Harmer
0.026
970659AG2-427 GEN
Solar/Wind Harmer
3.376
316381AD1-082 GEN
Solar/Wind Harmer
0.072
970661AG2-428 GEN
Solar/Wind Harmer
6.816
316375AC2-012 GEN
Solar/Wind Harmer
0.002
3150981CHESPKA
Adder
0.848
316246AF1-032 C
Solar/Wind Harmer
0.029
316388AE2-253 GEN
Solar/Wind Harmer
0.202
944591AF1-124 GEN
Solar/Wind Harmer
14.529
3146456SLIGO L269
Solar/Wind Harmer
0.064
316093AE2-104_GEN
Solar/Wind Harmer
1.078
316294AC1-161 GEN
Solar/Wind Harmer
1.078
3146516WINFALL
Solar/Wind Harmer
0.198
3146516WINFALL
Solar/Wind Harmer
0.061
315671AE2-027_GEN
Solar/Wind Harmer
3.892
315800Z1-036_GEN1
Solar/Wind Harmer
0
3130156CHOWAN
Solar/Wind Harmer
0.057
3143526WINTERP
Solar/Wind Helper
1.618
3143226MDLTHAN
Solar/Wind Helper
0.118
3150801HOPHCF4
50/50
0.81
971211AH1-065 GEN
50/50
0.977
315749AE2-041 GEN
50/50
3.414
3151161SURRY 1
50/50
3.592
3142946ENON
Solar/Wind Harmer
0.072
970133AG2-095 GEN
Solar/Wind Harmer
1.318
970129AG2-093 GEN
Solar/Wind Harmer
7.619
315778AD1-151 GEN
Solar/Wind Harmer
9.439
961611AG1-000B GEN
Solar/Wind Harmer
2.697
3141766HARMONY
Solar/Wind Harmer
1.28
316382AG1-145 C
Solar/Wind Harmer
0.001
3151221GRAVEL6
Adder
6.799
3151171GRAVELC
Adder
1.308
3141843SHACKLE
Adder
0.471
316203AE2-005 GEN
Solar/Wind Harmer
0
316280AD1-041 GEN
Solar/Wind Harmer
0.002
316156AD2-030 GEN
Solar/Wind Harmer
0.068
3141873WAN 176
Solar/Wind Harmer
1.624
962971AG1-146 GEN
Solar/Wind Harmer
1.39
970009AG2-005 GEN
Solar/Wind Harmer
0.641
3142433PROV 92
Adder
0.165
3142433PROV 92
Adder
0.165
3144216WINCHST
Adder
0.319
316404AE1-155 C
Solar/Wind Harmer
0.019
3145336SMITFLD
Solar/Wind Harmer
0.033
3150921YORKTN3
Adder
2.093
3150351NORNECKC2
Adder
0.824
3144536CHRHLND
Solar/Wind Harmer
0.011
315813AE1-149 C
Solar/Wind Harmer
3.817
970659AG2-427 GEN
Solar/Wind Harmer
0.738
316083AB2-161 GEN
Solar/Wind Harmer
0.001
970661AG2-428 GEN
Solar/Wind Harmer
1.45
3144873MCLAUGH
Solar/Wind Harmer
0.002
3151101ELIZAR3
Adder
6.266
3141906WESTMOR
Solar/Wind Harmer
0.027
944581AF1-123 GEN
Solar/Wind Harmer
14.477
944601AF1-125 GEN
Solar/Wind Harmer
14.254
3146456SLIGO L269
Solar/Wind Harmer
0.064
971153AH1-033 GEN
Solar/Wind Harmer
0.742
316320Y1-086
Solar/Wind Harmer
0
315773AC2-141 GEN
Solar/Wind Harmer
2.272
316435W1029_GEN3
Solar/Wind Harmer
0
3146516WINFALL
Solar/Wind Harmer
0.061
965281AG1-393 GEN
Solar/Wind Harmer
0.649
3146626S HERTFORD
Solar/Wind Harmer
0.06
970737AG2-469 GEN
Solar/Wind Harmer
2.555
3145273HOLLAND
Solar/Wind Harmer
0.045
3146376EDENTON
Solar/Wind Harmer
0.057
LAGNLTFEXP_LAGN->PJM
CLTF
0.804
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.434
TVALTFEXP_TVA->PJM
CLTF
0.397
CPLELTFEXP_CPLE->PJM
CLTF
1.734
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.554
NYPJM->LTFIMP_NY
CLTF
0.33
LGEELTFEXP_LGEE->PJM
CLTF
0.057
WECLTFEXP_WEC->PJM
CLTF
0.026
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.657
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.279
MECLTFEXP_MEC->PJM
CLTF
0.223
SIGELTFEXP_SIGE->PJM
CLTF
0.006

Details for 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6CHESTF A-6IRON208 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.5 %
Rating:663.64 MVA
Rating Type:B
MVA to Mitigate:720.05
MW Contribution:0.9
Bus #Bus NameTypeMW Contribution
3150611CHESTG7
50/50
1.535
3150631CHESTG8
50/50
1.511
971047AG2-646 GEN
50/50
42.989
316132AB2-190 GEN1
Solar/Wind Harmer
0.61
316369SG1_INVT
Solar/Wind Harmer
0.004
315976AC1-164 GENA
Solar/Wind Harmer
9.735
316169AC1-164_GENC
Solar/Wind Harmer
8.41
315975AC1-164 GENB
Solar/Wind Harmer
0.288
972265AH1-717 GEN
Adder
6.312
3151201GRAVEL4
Adder
5.917
3151191GRAVEL3
Adder
5.842
3151211GRAVEL5
Adder
5.842
316314AB2-024 C
Solar/Wind Harmer
0
316059AD1-063 C
Solar/Wind Harmer
0
3143873LANEXA
Solar/Wind Harmer
0.045
970189AG2-124 GEN
Solar/Wind Harmer
2.166
971445AH1-216 GEN
Solar/Wind Harmer
5.125
315662AE1-191 GEN
Solar/Wind Harmer
0.002
315666AE1-190 GEN
Solar/Wind Harmer
0.001
3141873WAN 176
Solar/Wind Harmer
0.014
3141913WHIT STONE
Solar/Wind Harmer
0.071
3138133OCRAN
Solar/Wind Harmer
0.021
3141783LANCAST
Solar/Wind Harmer
0.042
3141783LANCAST
Solar/Wind Harmer
0.028
3138283WHITEMARSH
Solar/Wind Harmer
0.016
962981AG1-147 GEN
Solar/Wind Harmer
2.557
3142433PROV 92
Adder
0.133
3142433PROV 92
Adder
0.133
970327AG2-215 GEN
Solar/Wind Harmer
2.22
971167AH1-042 GEN
Solar/Wind Harmer
5.919
3141813NORNECK
Solar/Wind Harmer
0.064
315833AF1-017_GEN
Solar/Wind Harmer
0
316349AD2-085 GEN
Solar/Wind Harmer
0.04
316311AC2-079 GEN
Solar/Wind Harmer
1.663
3152611GOSPORTB
Adder
0.725
3152621GOSPORTC
Adder
0.615
3152601GOSPORTA
Adder
0.568
3151081ELIZAR1
Adder
5.179
3151091ELIZAR2
Adder
5.089
316233AE1-074 FULL
Solar/Wind Helper
0.525
3150641CHESTS8
50/50
0.778
944631AF1-128 GEN
50/50
122.303
3150771HOPHCF1
50/50
0.513
970129AG2-093 GEN
Solar/Wind Harmer
3.268
316458AB2-190 GEN2
Solar/Wind Harmer
0.61
971069AG2-661 GEN
Solar/Wind Harmer
1.894
971647AH1-324 GEN
Solar/Wind Harmer
4.071
961611AG1-000B GEN
Solar/Wind Harmer
4.675
3151171GRAVELC
Adder
0.865
3141766HARMONY
Solar/Wind Harmer
0.015
316159AE1-175 C
Solar/Wind Harmer
0.063
971777AH1-397 GEN
Solar/Wind Harmer
0.193
3141843SHACKLE
Adder
0.374
3145336SMITFLD
Solar/Wind Harmer
0.288
3138133OCRAN
Solar/Wind Harmer
0.042
3142433PROV 92
Solar/Wind Harmer
0.273
3142433PROV 92
Adder
0.133
3142433PROV 92
Adder
0.133
962861AG1-135 GEN
Solar/Wind Harmer
2.133
3138126ROCKLANDING
Solar/Wind Harmer
0.03
3141726DUNNSVL
Solar/Wind Harmer
0.265
971317AH1-138 GEN
Solar/Wind Harmer
0.495
3150351NORNECKC2
Adder
0.637
970659AG2-427 GEN
Solar/Wind Harmer
3.065
316381AD1-082 GEN
Solar/Wind Harmer
0.066
970661AG2-428 GEN
Solar/Wind Harmer
6.114
316072AD1-144
Solar/Wind Harmer
0.022
316337AD2-073 GEN
Solar/Wind Harmer
0.051
316375AC2-012 GEN
Solar/Wind Harmer
0.001
3150981CHESPKA
Adder
0.711
3143526WINTERP
Solar/Wind Helper
1.788
3143226MDLTHAN
Solar/Wind Helper
0.157
3150801HOPHCF4
50/50
0.746
971211AH1-065 GEN
50/50
0.9
3151161SURRY 1
50/50
3.123
3142946ENON
Solar/Wind Harmer
0.066
970133AG2-095 GEN
Solar/Wind Harmer
1.215
970129AG2-093 GEN
Solar/Wind Harmer
6.944
315778AD1-151 GEN
Solar/Wind Harmer
8.525
961611AG1-000B GEN
Solar/Wind Harmer
2.377
3151221GRAVEL6
Adder
5.91
3151171GRAVELC
Adder
1.137
3141766HARMONY
Solar/Wind Harmer
1.013
316382AG1-145 C
Solar/Wind Harmer
0.001
3141843SHACKLE
Adder
0.374
316203AE2-005 GEN
Solar/Wind Harmer
0
316280AD1-041 GEN
Solar/Wind Harmer
0.001
316156AD2-030 GEN
Solar/Wind Harmer
0.053
3141873WAN 176
Solar/Wind Harmer
1.283
3145336SMITFLD
Solar/Wind Harmer
0.029
962971AG1-146 GEN
Solar/Wind Harmer
1.096
3150621CHESTS7
50/50
0.705
3150781HOPHCF2
50/50
0.513
3150791HOPHCF3
50/50
0.513
3150761HOPPOLC
50/50
0.325
971213AH1-066 GEN
50/50
0.45
3142946ENON
Solar/Wind Harmer
0.02
316033AB2-134 GEN
Solar/Wind Harmer
0.006
315697AD1-025 GEN
Solar/Wind Harmer
0.114
316236AE1-162_GEN
Solar/Wind Harmer
0.001
958261AF2-120 GEN
Solar/Wind Harmer
2.192
316077AC2-138 C
Solar/Wind Harmer
0
3150341NORNECKC1
Adder
0.669
3150341NORNECKC1
Adder
0.663
316075AC2-137 C
Solar/Wind Harmer
0.018
970657AG2-426 GEN
Solar/Wind Harmer
2.184
970657AG2-426 GEN
Solar/Wind Harmer
0.458
316036AC1-147 C
Solar/Wind Harmer
0.011
3150991CHESPKB
Adder
0.596
3150991CHESPKB
Adder
0.582
3143526WINTERP
Solar/Wind Helper
1.788
3142433PROV 92
Adder
0.133
3142433PROV 92
Adder
0.133
970009AG2-005 GEN
Solar/Wind Harmer
0.505
3144216WINCHST
Adder
0.253
316404AE1-155 C
Solar/Wind Harmer
0.015
315813AE1-149 C
Solar/Wind Harmer
3.52
3150921YORKTN3
Adder
1.637
3150351NORNECKC2
Adder
0.647
970659AG2-427 GEN
Solar/Wind Harmer
0.67
316083AB2-161 GEN
Solar/Wind Harmer
0.001
970661AG2-428 GEN
Solar/Wind Harmer
1.3
3144536CHRHLND
Solar/Wind Harmer
0.009
3144873MCLAUGH
Solar/Wind Harmer
0.001
3151101ELIZAR3
Adder
5.246
LAGNLTFEXP_LAGN->PJM
CLTF
1.059
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.936
TVALTFEXP_TVA->PJM
CLTF
0.526
CPLELTFEXP_CPLE->PJM
CLTF
1.919
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.103
NYPJM->LTFIMP_NY
CLTF
0.354
LGEELTFEXP_LGEE->PJM
CLTF
0.127
WECLTFEXP_WEC->PJM
CLTF
0.063
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.024
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.746
MECLTFEXP_MEC->PJM
CLTF
0.397
SIGELTFEXP_SIGE->PJM
CLTF
0.011

Details for 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T557_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6CHESTF A-6IRON208 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T557_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.22 %
Rating:811.0 MVA
Rating Type:C
MVA to Mitigate:828.99
MW Contribution:0.95
Bus #Bus NameTypeMW Contribution
3150611CHESTG7
50/50
1.61
3150631CHESTG8
50/50
1.584
971047AG2-646 GEN
50/50
45.085
316132AB2-190 GEN1
Solar/Wind Harmer
1.382
315976AC1-164 GENA
Solar/Wind Harmer
13.508
316169AC1-164_GENC
Solar/Wind Harmer
11.67
315975AC1-164 GENB
Solar/Wind Harmer
0.4
316369SG1_INVT
Solar/Wind Harmer
2.21
316314AB2-024 C
Solar/Wind Harmer
0.919
316059AD1-063 C
Solar/Wind Harmer
0.236
972265AH1-717 GEN
Adder
7.037
3151201GRAVEL4
Adder
6.597
3151191GRAVEL3
Adder
6.513
3151211GRAVEL5
Adder
6.513
3143873LANEXA
Solar/Wind Harmer
-0.006
315662AE1-191 GEN
Solar/Wind Harmer
1.202
315666AE1-190 GEN
Solar/Wind Harmer
0.301
957601AF2-054 GEN
Solar/Wind Harmer
0.297
3141873WAN 176
Solar/Wind Harmer
-0.002
3141913WHIT STONE
Solar/Wind Harmer
-0.01
3138133OCRAN
Solar/Wind Harmer
-0.003
3141783LANCAST
Solar/Wind Harmer
-0.006
3141783LANCAST
Solar/Wind Harmer
-0.004
957831AF2-077 GEN
Solar/Wind Harmer
0.284
3138283WHITEMARSH
Solar/Wind Harmer
0.015
962981AG1-147 GEN
Solar/Wind Harmer
4.13
971445AH1-216 GEN
Solar/Wind Harmer
5.689
3142433PROV 92
Adder
0.159
3142433PROV 92
Adder
0.159
971167AH1-042 GEN
Solar/Wind Harmer
8.59
3141813NORNECK
Solar/Wind Harmer
-0.009
3152611GOSPORTB
Adder
0.832
3152621GOSPORTC
Adder
0.706
3152601GOSPORTA
Adder
0.652
3151081ELIZAR1
Adder
5.952
3151091ELIZAR2
Adder
5.849
316223AC1-118
Solar/Wind Harmer
0.196
315833AF1-017_GEN
Solar/Wind Harmer
1.355
316349AD2-085 GEN
Solar/Wind Harmer
0.635
316311AC2-079 GEN
Solar/Wind Harmer
3.597
316305AF2-043 C
Solar/Wind Harmer
0.21
957871AF2-081 GEN
Solar/Wind Harmer
3.483
319010AE1-072 C
Solar/Wind Harmer
1.401
315835AF2-110_GEN
Solar/Wind Harmer
0.865
3146406KITTY HAWK
Solar/Wind Harmer
0.006
313526AB2-022
Solar/Wind Harmer
0.183
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
316321Z2-027
Solar/Wind Harmer
0.181
3146396TANGLEW
Solar/Wind Harmer
0.124
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
315611Z1-036_GEN2
Solar/Wind Harmer
1.575
316233AE1-074 FULL
Solar/Wind Helper
0.485
3150801HOPHCF4
50/50
0.79
971211AH1-065 GEN
50/50
0.952
3142946ENON
Solar/Wind Harmer
-0.008
970133AG2-095 GEN
Solar/Wind Harmer
1.693
970129AG2-093 GEN
Solar/Wind Harmer
7.767
315778AD1-151 GEN
Solar/Wind Harmer
11.174
961611AG1-000B GEN
Solar/Wind Harmer
2.322
3141766HARMONY
Solar/Wind Harmer
0.929
316382AG1-145 C
Solar/Wind Harmer
0.308
3151221GRAVEL6
Adder
6.589
3151171GRAVELC
Adder
1.268
3141843SHACKLE
Adder
0.455
3150621CHESTS7
50/50
0.74
3150781HOPHCF2
50/50
0.543
3150791HOPHCF3
50/50
0.543
3150761HOPPOLC
50/50
0.344
971213AH1-066 GEN
50/50
0.476
3142946ENON
Solar/Wind Harmer
-0.002
316033AB2-134 GEN
Solar/Wind Harmer
3.988
315697AD1-025 GEN
Solar/Wind Harmer
2.501
316441AF1-014 GEN
Solar/Wind Harmer
0.675
316487AF1-042 GEN
Solar/Wind Harmer
1.229
958261AF2-120 GEN
Solar/Wind Harmer
3.547
316236AE1-162_GEN
Solar/Wind Harmer
0.274
316077AC2-138 C
Solar/Wind Harmer
0.186
3150341NORNECKC1
Adder
0.823
3150341NORNECKC1
Adder
0.817
316075AC2-137 C
Solar/Wind Harmer
0.238
970657AG2-426 GEN
Solar/Wind Harmer
2.328
970657AG2-426 GEN
Solar/Wind Harmer
0.487
316036AC1-147 C
Solar/Wind Harmer
0.198
3150991CHESPKB
Adder
0.685
3150991CHESPKB
Adder
0.668
316316AC1-027 C
Solar/Wind Harmer
0.221
3142956BIRDNECK
Solar/Wind Harmer
0.386
316185AD1-033 GEN
Solar/Wind Harmer
0.747
3145506HICKORY
Solar/Wind Harmer
-0.028
3145506HICKORY
Solar/Wind Harmer
-0.017
3145506HICKORY
Solar/Wind Harmer
-0.004
316339AD2-160 GEN
Solar/Wind Harmer
0.471
316018AA1-139 ULT2
Solar/Wind Harmer
0.597
316017AA1-139 ULT1
Solar/Wind Harmer
0.564
3137176SLIGO L2192
Solar/Wind Harmer
-0.027
3146456SLIGO L269
Solar/Wind Harmer
0.819
3130086AYDLETT
Solar/Wind Harmer
-0.028
3146386ELIZ CT
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.205
316433W1029_GEN2
Solar/Wind Harmer
1.205
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.006
3146626S HERTFORD
Solar/Wind Harmer
-0.006
3143526WINTERP
Solar/Wind Helper
1.651
3150641CHESTS8
50/50
0.816
944631AF1-128 GEN
50/50
128.267
3150771HOPHCF1
50/50
0.543
970129AG2-093 GEN
Solar/Wind Harmer
3.146
316458AB2-190 GEN2
Solar/Wind Harmer
1.382
971069AG2-661 GEN
Solar/Wind Harmer
2.041
971647AH1-324 GEN
Solar/Wind Harmer
5.851
961611AG1-000B GEN
Solar/Wind Harmer
5.442
3141766HARMONY
Solar/Wind Harmer
-0.002
316159AE1-175 C
Solar/Wind Harmer
0.274
3151171GRAVELC
Adder
0.964
971777AH1-397 GEN
Solar/Wind Harmer
1.177
3141843SHACKLE
Adder
0.455
3138133OCRAN
Solar/Wind Harmer
-0.006
961951AG1-038 GEN
Solar/Wind Harmer
1.229
971317AH1-138 GEN
Solar/Wind Harmer
1.162
962861AG1-135 GEN
Solar/Wind Harmer
3.45
964211AG1-282 GEN
Solar/Wind Harmer
0.276
3141726DUNNSVL
Solar/Wind Harmer
-0.037
3142433PROV 92
Solar/Wind Harmer
-0.036
3142433PROV 92
Adder
0.159
3142433PROV 92
Adder
0.159
3138126ROCKLANDING
Solar/Wind Harmer
0.028
3145336SMITFLD
Solar/Wind Harmer
-0.036
3150351NORNECKC2
Adder
0.784
316337AD2-073 GEN
Solar/Wind Harmer
0.218
316072AD1-144
Solar/Wind Harmer
0.155
970659AG2-427 GEN
Solar/Wind Harmer
3.995
316381AD1-082 GEN
Solar/Wind Harmer
0.687
970661AG2-428 GEN
Solar/Wind Harmer
7.847
316375AC2-012 GEN
Solar/Wind Harmer
2.542
3150981CHESPKA
Adder
0.816
316246AF1-032 C
Solar/Wind Harmer
0.141
316388AE2-253 GEN
Solar/Wind Harmer
0.471
944591AF1-124 GEN
Solar/Wind Harmer
31.694
3146456SLIGO L269
Solar/Wind Harmer
-0.007
316093AE2-104_GEN
Solar/Wind Harmer
2.011
316294AC1-161 GEN
Solar/Wind Harmer
2.17
3146516WINFALL
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.007
315671AE2-027_GEN
Solar/Wind Harmer
4.842
315800Z1-036_GEN1
Solar/Wind Harmer
1.575
3143526WINTERP
Solar/Wind Helper
1.651
3143226MDLTHAN
Solar/Wind Helper
0.123
316203AE2-005 GEN
Solar/Wind Harmer
4.221
316280AD1-041 GEN
Solar/Wind Harmer
0.752
316156AD2-030 GEN
Solar/Wind Harmer
0.265
3141873WAN 176
Solar/Wind Harmer
1.178
962971AG1-146 GEN
Solar/Wind Harmer
1.77
316484AD2-074 GEN
Solar/Wind Harmer
2.349
970009AG2-005 GEN
Solar/Wind Harmer
1.166
3144216WINCHST
Adder
0.308
3142433PROV 92
Adder
0.159
3142433PROV 92
Adder
0.159
316404AE1-155 C
Solar/Wind Harmer
1.766
3145336SMITFLD
Solar/Wind Harmer
-0.004
3150921YORKTN3
Adder
2.021
3150351NORNECKC2
Adder
0.797
3144536CHRHLND
Solar/Wind Harmer
-0.001
315813AE1-149 C
Solar/Wind Harmer
4.817
970659AG2-427 GEN
Solar/Wind Harmer
0.708
316083AB2-161 GEN
Solar/Wind Harmer
1.215
970661AG2-428 GEN
Solar/Wind Harmer
1.391
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
6.029
3141906WESTMOR
Solar/Wind Harmer
-0.003
944581AF1-123 GEN
Solar/Wind Harmer
31.58
944601AF1-125 GEN
Solar/Wind Harmer
31.087
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.846
316320Y1-086
Solar/Wind Harmer
0.398
315773AC2-141 GEN
Solar/Wind Harmer
2.807
316435W1029_GEN3
Solar/Wind Harmer
1.205
3146516WINFALL
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.006
970737AG2-469 GEN
Solar/Wind Harmer
3.247
965281AG1-393 GEN
Solar/Wind Harmer
0.807
3145273HOLLAND
Solar/Wind Harmer
-0.005
LAGNLTFEXP_LAGN->PJM
CLTF
0.763
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.251
TVALTFEXP_TVA->PJM
CLTF
0.377
CPLELTFEXP_CPLE->PJM
CLTF
1.641
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.38
NYPJM->LTFIMP_NY
CLTF
0.314
LGEELTFEXP_LGEE->PJM
CLTF
0.055
WECLTFEXP_WEC->PJM
CLTF
0.025
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.639
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.215
MECLTFEXP_MEC->PJM
CLTF
0.213
SIGELTFEXP_SIGE->PJM
CLTF
0.006

Details for 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:171.05 %
Rating:812.0 MVA
Rating Type:C
MVA to Mitigate:1388.94
MW Contribution:0.99
Bus #Bus NameTypeMW Contribution
970603AG2-384 GEN
50/50
5.836
315779AE2-040
50/50
1.742
3143316POE
Solar/Wind Harmer
-0.079
316315AB2-025 C
Solar/Wind Harmer
0.378
315814AE2-033 C
Solar/Wind Harmer
12.904
316132AB2-190 GEN1
Solar/Wind Harmer
1.401
316369SG1_INVT
Solar/Wind Harmer
2.168
315833AF1-017_GEN
Solar/Wind Harmer
1.93
316349AD2-085 GEN
Solar/Wind Harmer
0.904
316311AC2-079 GEN
Solar/Wind Harmer
5.103
941031AE2-094 GEN
Solar/Wind Harmer
18.91
944011AF1-069 GEN
Solar/Wind Harmer
5.925
970673AG2-436 GEN
Solar/Wind Harmer
20.676
970673AG2-436 GEN
Solar/Wind Harmer
10.469
946281AF1-292 GEN
Solar/Wind Harmer
0.22
971967AH1-528 GEN
Solar/Wind Harmer
17.946
316087AB2-174 GEN
Solar/Wind Harmer
1.339
315652AC1-086 GEN
Solar/Wind Harmer
10.41
972265AH1-717 GEN
Adder
6.391
3151201GRAVEL4
Adder
5.991
3151191GRAVEL3
Adder
5.915
3151211GRAVEL5
Adder
5.915
970085AG2-068 GEN
Solar/Wind Harmer
5.695
970581AG2-369 GEN
Solar/Wind Harmer
4.898
3145796HORNRTN
Solar/Wind Harmer
-0.029
3145796HORNRTN
Solar/Wind Harmer
-0.004
3137643SOCKMAN
Solar/Wind Harmer
-0.035
971445AH1-216 GEN
Solar/Wind Harmer
5.206
315607AA1-063A GEN
Solar/Wind Harmer
0.849
3146043SEABORD
Solar/Wind Harmer
-0.008
965291AG1-394 GEN
Solar/Wind Harmer
0.729
316318V4-068
Solar/Wind Harmer
0.202
3145893MURPHYS
Solar/Wind Harmer
-0.022
3145893MURPHYS
Solar/Wind Harmer
-0.008
315835AF2-110_GEN
Solar/Wind Harmer
0.998
3145513AHOSKIE
Solar/Wind Harmer
0.07
961941AG1-037 GEN
Solar/Wind Harmer
0.06
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3146033SCOT NK
Solar/Wind Harmer
-0.032
3146206CASHIE
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
3.803
970601AG2-382 GEN
Solar/Wind Harmer
3.328
316319Z2-044 C
Solar/Wind Harmer
0.42
315732AD1-074 GEN1
Solar/Wind Harmer
1.51
315733AD1-074 GEN2
Solar/Wind Harmer
1.51
315735AD1-075 GEN1
Solar/Wind Harmer
0.755
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
3150801HOPHCF4
50/50
0.823
971211AH1-065 GEN
50/50
0.992
315839AE2-212 C
Solar/Wind Harmer
0.75
315813AE1-149 C
Solar/Wind Harmer
9.892
970133AG2-095 GEN
Solar/Wind Harmer
1.764
970129AG2-093 GEN
Solar/Wind Harmer
7.894
970659AG2-427 GEN
Solar/Wind Harmer
1.316
316083AB2-161 GEN
Solar/Wind Harmer
2.212
315778AD1-151 GEN
Solar/Wind Harmer
11.121
970661AG2-428 GEN
Solar/Wind Harmer
2.378
965281AG1-393 GEN
Solar/Wind Harmer
1.512
316365GEN2_N
Solar/Wind Harmer
0.733
961611AG1-000B GEN
Solar/Wind Harmer
2.183
966621AG1-532 GEN
Solar/Wind Harmer
0.199
3151221GRAVEL6
Adder
5.984
3151171GRAVELC
Adder
1.151
313506AB2-031 GEN
Solar/Wind Harmer
0.74
970917AG2-570 GEN
Solar/Wind Harmer
22.893
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
3145796HORNRTN
Solar/Wind Harmer
-0.036
3145796HORNRTN
Solar/Wind Harmer
-0.009
3147043LAWRENC
Solar/Wind Harmer
-0.005
3145336SMITFLD
Solar/Wind Harmer
-0.003
3156081AA2-088 GEN
Solar/Wind Harmer
2.663
315724AD1-057 GEN
Solar/Wind Harmer
0.47
3145893MURPHYS
Solar/Wind Harmer
0.057
3145893MURPHYS
Solar/Wind Harmer
-0.008
957521AF2-046 GEN
Solar/Wind Harmer
6.374
961681AG1-008 GEN
Solar/Wind Harmer
6.374
3146263WOODLND
Solar/Wind Harmer
-0.008
3145273HOLLAND
Solar/Wind Harmer
-0.006
3146173TUNIS
Solar/Wind Harmer
-0.008
316463AE2-346 GEN
Solar/Wind Harmer
0.129
316140AB2-099
Solar/Wind Harmer
0.054
962331AG1-082 GEN
Solar/Wind Harmer
0.997
316317KELFORD C
Solar/Wind Harmer
0.373
3145823KELFORD
Solar/Wind Harmer
-0.008
316210AC1-098 GEN
Solar/Wind Harmer
1.243
3156021HOLLOMANSOL
Solar/Wind Harmer
1.052
316327AA2-057 GEN
Solar/Wind Harmer
0.781
3146206CASHIE
Solar/Wind Harmer
-0.008
3146233WITAKRS
Solar/Wind Harmer
0.159
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
961601AG1-000A GEN
Solar/Wind Harmer
2.988
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
315737AD1-076 GEN
Solar/Wind Harmer
1.419
316478AD1-087 GEN
Solar/Wind Harmer
0.645
316486AD2-202 GEN
Solar/Wind Harmer
0.189
971157AH1-035 GEN
Solar/Wind Harmer
0.931
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
3145933PARMELE
Solar/Wind Harmer
-0.007
966801AG1-551 GEN
Solar/Wind Harmer
0.919
315614AA2-178 GEN
Solar/Wind Harmer
0.793
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3144536CHRHLND
Solar/Wind Harmer
-0.001
3146376EDENTON
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
316435W1029_GEN3
Solar/Wind Harmer
1.282
3146516WINFALL
Solar/Wind Harmer
-0.007
316320Y1-086
Solar/Wind Harmer
0.406
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
5.635
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.829
944581AF1-123 GEN
Solar/Wind Harmer
29.417
944601AF1-125 GEN
Solar/Wind Harmer
28.958
316313AB2-026
Solar/Wind Helper
0.204
316258AE1-075 C
Solar/Wind Helper
0.184
316405AF2-144 C
Solar/Wind Helper
0.153
3145573BETHELC
Solar/Wind Harmer
-0.007
316420AA1-050 GEN
Solar/Wind Harmer
0.848
957861AF2-080 GEN
Solar/Wind Harmer
3.234
315816AE2-034 GEN
Solar/Wind Harmer
0.595
316005AA1-067
Solar/Wind Harmer
0.148
3145746EVERETS
Solar/Wind Harmer
-0.029
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
970181AG2-120 GEN
Solar/Wind Harmer
0.962
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.769
316305AF2-043 C
Solar/Wind Harmer
0.215
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
316321Z2-027
Solar/Wind Harmer
0.188
3146396TANGLEW
Solar/Wind Harmer
0.128
313526AB2-022
Solar/Wind Harmer
0.187
3152611GOSPORTB
Adder
0.78
3152621GOSPORTC
Adder
0.662
3152601GOSPORTA
Adder
0.611
3151081ELIZAR1
Adder
5.564
3151091ELIZAR2
Adder
5.467
3146406KITTY HAWK
Solar/Wind Harmer
0.006
319010AE1-072 C
Solar/Wind Harmer
1.378
957871AF2-081 GEN
Solar/Wind Harmer
3.391
316239AB2-077_GEN
Solar/Wind Harmer
0.193
316238AB2-078_GEN
Solar/Wind Harmer
0.193
316233AE1-074 FULL
Solar/Wind Helper
0.222
3150771HOPHCF1
50/50
0.566
970129AG2-093 GEN
Solar/Wind Harmer
3.197
970659AG2-427 GEN
Solar/Wind Harmer
7.425
316458AB2-190 GEN2
Solar/Wind Harmer
1.401
316381AD1-082 GEN
Solar/Wind Harmer
1.25
971069AG2-661 GEN
Solar/Wind Harmer
2.031
970661AG2-428 GEN
Solar/Wind Harmer
13.418
971647AH1-324 GEN
Solar/Wind Harmer
5.628
316023GEN1_S
Solar/Wind Harmer
0.733
961611AG1-000B GEN
Solar/Wind Harmer
5.115
315671AE2-027_GEN
Solar/Wind Harmer
7.708
960081AF2-299 GEN
Solar/Wind Harmer
1.103
316011AB1-132 GEN
Solar/Wind Harmer
1.936
962571AG1-106 GEN
Solar/Wind Harmer
1.33
3151171GRAVELC
Adder
0.876
970919AG2-571 GEN
Solar/Wind Harmer
2.898
970087AG2-069 GEN
Solar/Wind Harmer
8.543
971795AH1-408 GEN
Solar/Wind Harmer
6.821
3145796HORNRTN
Solar/Wind Harmer
-0.03
3145796HORNRTN
Solar/Wind Harmer
-0.009
939411AE1-173 GEN
Solar/Wind Harmer
44.626
3147043LAWRENC
Adder
0.706
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.103
3145336SMITFLD
Solar/Wind Harmer
-0.033
315722AD1-056 GEN
Solar/Wind Harmer
0.855
3145893MURPHYS
Solar/Wind Harmer
-0.032
3145893MURPHYS
Solar/Wind Harmer
0.241
3146263WOODLND
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316093AE2-104_GEN
Solar/Wind Harmer
2.321
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145823KELFORD
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
0.69
957481AF2-042 GEN
Solar/Wind Harmer
24.676
3146206CASHIE
Solar/Wind Harmer
-0.008
971547AH1-271 GEN
Solar/Wind Harmer
1.902
3146233WITAKRS
Solar/Wind Harmer
-0.03
316129AC1-054 GEN
Solar/Wind Harmer
0.658
316359AB2-059 GEN
Solar/Wind Harmer
1.008
316049AB1-081 GEN
Solar/Wind Harmer
0.807
3142053HEARTS
Solar/Wind Harmer
0.088
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
961671AG1-007 GEN
Solar/Wind Harmer
0.094
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.221
971065AG2-659 GEN
Solar/Wind Harmer
3.709
3145963POPLR C
Solar/Wind Harmer
-0.007
316174AB2-169 GEN
Solar/Wind Harmer
1.141
316494AC1-189 GEN
Solar/Wind Harmer
0.795
3146293MARTNCO
Solar/Wind Harmer
0.046
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.893
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315693AD1-088 GEN
Solar/Wind Harmer
3.59
316072AD1-144
Solar/Wind Harmer
0.145
315800Z1-036_GEN1
Solar/Wind Harmer
1.769
316246AF1-032 C
Solar/Wind Harmer
0.144
3146516WINFALL
Solar/Wind Harmer
-0.023
3146516WINFALL
Solar/Wind Harmer
-0.007
962491AG1-098 GEN
Solar/Wind Harmer
4.708
315687AD1-152 GEN
Solar/Wind Harmer
0.843
316375AC2-012 GEN
Solar/Wind Harmer
2.379
3150981CHESPKA
Adder
0.764
3146456SLIGO L269
Solar/Wind Harmer
-0.007
316388AE2-253 GEN
Solar/Wind Harmer
0.457
944591AF1-124 GEN
Solar/Wind Harmer
29.523
316237AB2-079_GEN
Solar/Wind Harmer
0.193
3142543TWELFTH
Solar/Wind Helper
0.04
3143226MDLTHAN
Solar/Wind Helper
0.199
3143526WINTERP
Solar/Wind Helper
0.755
316336AC2-165 C
Solar/Wind Helper
0.633
944641AF1-129 GEN
50/50
138.358
3150781HOPHCF2
50/50
0.566
3150791HOPHCF3
50/50
0.566
3150761HOPPOLC
50/50
0.359
971213AH1-066 GEN
50/50
0.496
316240AF1-291 C
Solar/Wind Harmer
0.89
3144356SAPONY
Solar/Wind Harmer
0.489
970657AG2-426 GEN
Solar/Wind Harmer
4.142
970657AG2-426 GEN
Solar/Wind Harmer
0.866
316033AB2-134 GEN
Solar/Wind Harmer
3.913
315697AD1-025 GEN
Solar/Wind Harmer
2.454
972185AH1-677 GEN
Adder
4.854
972187AH1-678 GEN
Adder
2.422
316181AB2-040 GEN
Solar/Wind Harmer
1.284
970933AG2-581 GEN
Solar/Wind Harmer
8.502
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.959
3145593CAROLNA
Solar/Wind Harmer
0.071
3145783HORNRTN
Solar/Wind Harmer
1.001
3145783HORNRTN
Solar/Wind Harmer
0.801
3145783HORNRTN
Solar/Wind Harmer
0.25
3145783HORNRTN
Solar/Wind Harmer
0.1
316426AA2-053 GEN
Solar/Wind Harmer
0.85
316236AE1-162_GEN
Solar/Wind Harmer
0.251
3145893MURPHYS
Solar/Wind Harmer
0.227
3145893MURPHYS
Solar/Wind Harmer
-0.015
315742AE1-103 GEN
Solar/Wind Harmer
0.845
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316274AC1-208 GEN
Solar/Wind Harmer
0.861
970099AG2-077 GEN
Solar/Wind Harmer
9.87
316065AD1-022 GEN
Solar/Wind Harmer
3.778
961601AG1-000A GEN
Solar/Wind Harmer
2.95
316263AC1-034 GEN
Solar/Wind Harmer
3.504
3145493TOT1
Solar/Wind Harmer
0.115
3145453TOT5
Solar/Wind Harmer
0.069
3145603CNETO
Solar/Wind Harmer
0.046
3145933PARMELE
Solar/Wind Harmer
-0.015
3145933PARMELE
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
0.214
3146376EDENTON
Solar/Wind Harmer
0.214
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.282
316433W1029_GEN2
Solar/Wind Harmer
1.282
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146386ELIZ CT
Solar/Wind Harmer
-0.007
316036AC1-147 C
Solar/Wind Harmer
0.185
3150991CHESPKB
Adder
0.641
3150991CHESPKB
Adder
0.626
939181AE1-148 GEN
Solar/Wind Harmer
3.86
3130086AYDLETT
Solar/Wind Harmer
-0.027
316316AC1-027 C
Solar/Wind Harmer
0.209
3146456SLIGO L269
Solar/Wind Harmer
0.803
3137176SLIGO L2192
Solar/Wind Harmer
-0.027
3142956BIRDNECK
Solar/Wind Harmer
0.365
316018AA1-139 ULT2
Solar/Wind Harmer
0.581
316017AA1-139 ULT1
Solar/Wind Harmer
0.549
316339AD2-160 GEN
Solar/Wind Harmer
0.457
3145506HICKORY
Solar/Wind Harmer
-0.027
3145506HICKORY
Solar/Wind Harmer
-0.016
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.709
313527AB2-043 GEN
Solar/Wind Harmer
1.038
3143526WINTERP
Solar/Wind Helper
0.755
LAGNLTFEXP_LAGN->PJM
CLTF
2.497
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.4
TVALTFEXP_TVA->PJM
CLTF
1.243
CPLELTFEXP_CPLE->PJM
CLTF
3.996
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.742
NYPJM->LTFIMP_NY
CLTF
0.594
LGEELTFEXP_LGEE->PJM
CLTF
0.385
WECLTFEXP_WEC->PJM
CLTF
0.198
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.809
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.207
MECLTFEXP_MEC->PJM
CLTF
1.111
SIGELTFEXP_SIGE->PJM
CLTF
0.033

Details for 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:170.7 %
Rating:663.64 MVA
Rating Type:B
MVA to Mitigate:1132.82
MW Contribution:1.0
Bus #Bus NameTypeMW Contribution
970603AG2-384 GEN
50/50
5.819
315779AE2-040
50/50
1.645
3143316POE
Solar/Wind Harmer
0.686
316132AB2-190 GEN1
Solar/Wind Harmer
0.675
316315AB2-025 C
Solar/Wind Harmer
0.095
315814AE2-033 C
Solar/Wind Harmer
9.215
316369SG1_INVT
Solar/Wind Harmer
0.004
315833AF1-017_GEN
Solar/Wind Harmer
0
316349AD2-085 GEN
Solar/Wind Harmer
0.064
316311AC2-079 GEN
Solar/Wind Harmer
2.655
972265AH1-717 GEN
Adder
6.782
3151201GRAVEL4
Adder
6.358
3151191GRAVEL3
Adder
6.277
3151211GRAVEL5
Adder
6.277
971445AH1-216 GEN
Solar/Wind Harmer
5.676
316087AB2-174 GEN
Solar/Wind Harmer
0.002
315652AC1-086 GEN
Solar/Wind Harmer
8.66
941031AE2-094 GEN
Solar/Wind Harmer
14.261
944011AF1-069 GEN
Solar/Wind Harmer
4.66
3145796HORNRTN
Solar/Wind Harmer
0.245
3145796HORNRTN
Solar/Wind Harmer
0.031
970673AG2-436 GEN
Solar/Wind Harmer
16.134
970673AG2-436 GEN
Solar/Wind Harmer
10.756
315835AF2-110_GEN
Solar/Wind Harmer
0.514
3137643SOCKMAN
Solar/Wind Harmer
0.299
971967AH1-528 GEN
Solar/Wind Harmer
11.737
965291AG1-394 GEN
Solar/Wind Harmer
0.323
3146043SEABORD
Solar/Wind Harmer
0.072
315607AA1-063A GEN
Solar/Wind Harmer
0.148
3145893MURPHYS
Solar/Wind Harmer
0.194
3145893MURPHYS
Solar/Wind Harmer
0.072
970085AG2-068 GEN
Solar/Wind Harmer
3.748
970581AG2-369 GEN
Solar/Wind Harmer
3.224
3145513AHOSKIE
Solar/Wind Harmer
0.147
3145513AHOSKIE
Solar/Wind Harmer
0.07
3145683EARLEYS
Solar/Wind Harmer
0.139
3145683EARLEYS
Solar/Wind Harmer
0.07
3145683EARLEYS
Solar/Wind Harmer
0.07
3146206CASHIE
Solar/Wind Harmer
0.068
970601AG2-382 GEN
Solar/Wind Harmer
2.553
3146033SCOT NK
Solar/Wind Harmer
0.273
316305AF2-043 C
Solar/Wind Harmer
0.001
3152611GOSPORTB
Adder
0.868
3152621GOSPORTC
Adder
0.737
3152601GOSPORTA
Adder
0.68
3146486SUNBURY
Solar/Wind Harmer
0.068
3146486SUNBURY
Solar/Wind Harmer
0.068
315732AD1-074 GEN1
Solar/Wind Harmer
0.389
315733AD1-074 GEN2
Solar/Wind Harmer
0.389
315735AD1-075 GEN1
Solar/Wind Harmer
0.195
3151081ELIZAR1
Adder
6.21
3151091ELIZAR2
Adder
6.102
3130546PLYMOUTH
Solar/Wind Harmer
0.068
315816AE2-034 GEN
Solar/Wind Harmer
0.291
3130156CHOWAN
Solar/Wind Harmer
0.068
3130156CHOWAN
Solar/Wind Harmer
0.068
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
316321Z2-027
Solar/Wind Harmer
0.012
3145176PASQUOTANK
Solar/Wind Harmer
0.042
3146396TANGLEW
Solar/Wind Harmer
0.185
313526AB2-022
Solar/Wind Harmer
0.036
3146406KITTY HAWK
Solar/Wind Harmer
0.008
319010AE1-072 C
Solar/Wind Harmer
0.337
957871AF2-081 GEN
Solar/Wind Harmer
3.324
316319Z2-044 C
Solar/Wind Harmer
0
316005AA1-067
Solar/Wind Harmer
0.068
3145746EVERETS
Solar/Wind Harmer
0.252
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
970181AG2-120 GEN
Solar/Wind Harmer
0.788
957861AF2-080 GEN
Solar/Wind Harmer
2.725
316420AA1-050 GEN
Solar/Wind Harmer
0.002
3145573BETHELC
Solar/Wind Harmer
0.063
3145573BETHELC
Solar/Wind Harmer
0.063
970831AG2-522 GEN
Solar/Wind Harmer
2.677
316233AE1-074 FULL
Solar/Wind Helper
0.217
3150801HOPHCF4
50/50
0.831
971211AH1-065 GEN
50/50
1.003
3151161SURRY 1
50/50
3.355
315839AE2-212 C
Solar/Wind Harmer
0.002
970133AG2-095 GEN
Solar/Wind Harmer
1.354
315813AE1-149 C
Solar/Wind Harmer
7.434
970129AG2-093 GEN
Solar/Wind Harmer
7.687
970659AG2-427 GEN
Solar/Wind Harmer
1.314
316083AB2-161 GEN
Solar/Wind Harmer
0.002
315778AD1-151 GEN
Solar/Wind Harmer
9.385
970661AG2-428 GEN
Solar/Wind Harmer
2.393
965281AG1-393 GEN
Solar/Wind Harmer
1.127
961611AG1-000B GEN
Solar/Wind Harmer
2.578
316365GEN2_N
Solar/Wind Harmer
0.206
3151221GRAVEL6
Adder
6.35
3151171GRAVELC
Adder
1.222
3145336SMITFLD
Solar/Wind Harmer
0.032
313506AB2-031 GEN
Solar/Wind Harmer
0.24
3142666NORTHAMPTON
Solar/Wind Harmer
0.077
3145796HORNRTN
Solar/Wind Harmer
0.306
3145796HORNRTN
Solar/Wind Harmer
0.076
3145273HOLLAND
Solar/Wind Harmer
0.056
3147043LAWRENC
Solar/Wind Harmer
0.044
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
3145893MURPHYS
Solar/Wind Harmer
0.12
3145893MURPHYS
Solar/Wind Harmer
0.072
3144536CHRHLND
Solar/Wind Harmer
0.011
957521AF2-046 GEN
Solar/Wind Harmer
5.314
961681AG1-008 GEN
Solar/Wind Harmer
5.314
3146173TUNIS
Solar/Wind Harmer
0.071
970917AG2-570 GEN
Solar/Wind Harmer
6.276
3146263WOODLND
Solar/Wind Harmer
0.07
316463AE2-346 GEN
Solar/Wind Harmer
0.06
316140AB2-099
Solar/Wind Harmer
0.025
962331AG1-082 GEN
Solar/Wind Harmer
0.749
3156021HOLLOMANSOL
Solar/Wind Harmer
0.315
316317KELFORD C
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.069
315724AD1-057 GEN
Solar/Wind Harmer
0.259
3146206CASHIE
Solar/Wind Harmer
0.068
3144873MCLAUGH
Solar/Wind Harmer
0.002
315737AD1-076 GEN
Solar/Wind Harmer
0.872
3151101ELIZAR3
Adder
6.29
316210AC1-098 GEN
Solar/Wind Harmer
0.629
971157AH1-035 GEN
Solar/Wind Harmer
0.813
315614AA2-178 GEN
Solar/Wind Harmer
0.387
316435W1029_GEN3
Solar/Wind Harmer
0
3146376EDENTON
Solar/Wind Harmer
0.068
3146626S HERTFORD
Solar/Wind Harmer
0.067
3146516WINFALL
Solar/Wind Harmer
0.067
316320Y1-086
Solar/Wind Harmer
0
3146456SLIGO L269
Solar/Wind Harmer
0.067
971153AH1-033 GEN
Solar/Wind Harmer
0.772
3145963POPLR C
Solar/Wind Harmer
0.066
316327AA2-057 GEN
Solar/Wind Harmer
0.099
944581AF1-123 GEN
Solar/Wind Harmer
14.652
944601AF1-125 GEN
Solar/Wind Harmer
14.427
3145933PARMELE
Solar/Wind Harmer
0.064
966801AG1-551 GEN
Solar/Wind Harmer
0.746
3146233WITAKRS
Solar/Wind Harmer
0.322
3146233WITAKRS
Solar/Wind Harmer
0.044
3138543CONSLDL
Solar/Wind Harmer
0.042
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
3146073TAR RVR
Solar/Wind Harmer
0.063
3146083TARBORO
Solar/Wind Harmer
0.063
961601AG1-000A GEN
Solar/Wind Harmer
4.481
971623AH1-311 GEN
Solar/Wind Harmer
0.125
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
315773AC2-141 GEN
Solar/Wind Harmer
2.115
316478AD1-087 GEN
Solar/Wind Harmer
0.201
316486AD2-202 GEN
Solar/Wind Harmer
0.059
316313AB2-026
Solar/Wind Helper
0.203
316258AE1-075 C
Solar/Wind Helper
0.183
316405AF2-144 C
Solar/Wind Helper
0.152
3150771HOPHCF1
50/50
0.572
970129AG2-093 GEN
Solar/Wind Harmer
3.618
316458AB2-190 GEN2
Solar/Wind Harmer
0.675
970659AG2-427 GEN
Solar/Wind Harmer
6.005
316381AD1-082 GEN
Solar/Wind Harmer
0.126
971069AG2-661 GEN
Solar/Wind Harmer
2.086
970661AG2-428 GEN
Solar/Wind Harmer
11.251
971647AH1-324 GEN
Solar/Wind Harmer
4.442
961611AG1-000B GEN
Solar/Wind Harmer
5.07
316023GEN1_S
Solar/Wind Harmer
0.206
315671AE2-027_GEN
Solar/Wind Harmer
5.751
3151171GRAVELC
Adder
0.929
960081AF2-299 GEN
Solar/Wind Harmer
0.792
3145336SMITFLD
Solar/Wind Harmer
0.32
316011AB1-132 GEN
Solar/Wind Harmer
1.431
962571AG1-106 GEN
Solar/Wind Harmer
1.12
940641AE2-051 GEN
Solar/Wind Harmer
6.143
3145796HORNRTN
Solar/Wind Harmer
0.252
3145796HORNRTN
Solar/Wind Harmer
0.076
971795AH1-408 GEN
Solar/Wind Harmer
5.061
316093AE2-104_GEN
Solar/Wind Harmer
1.261
939411AE1-173 GEN
Solar/Wind Harmer
31.612
3147043LAWRENC
Adder
0.659
316190AA2-174 GEN
Solar/Wind Harmer
0
3145783HORNRTN
Solar/Wind Harmer
0.072
3145893MURPHYS
Solar/Wind Harmer
0.287
3145893MURPHYS
Solar/Wind Harmer
0.319
3146173TUNIS
Solar/Wind Harmer
0.071
970919AG2-571 GEN
Solar/Wind Harmer
2.51
3146263WOODLND
Solar/Wind Harmer
0.07
970087AG2-069 GEN
Solar/Wind Harmer
5.623
3145683EARLEYS
Solar/Wind Harmer
0.07
3145823KELFORD
Solar/Wind Harmer
0.069
315722AD1-056 GEN
Solar/Wind Harmer
0.437
316072AD1-144
Solar/Wind Harmer
0.025
3146206CASHIE
Solar/Wind Harmer
0.068
971547AH1-271 GEN
Solar/Wind Harmer
1.459
316246AF1-032 C
Solar/Wind Harmer
0.031
316375AC2-012 GEN
Solar/Wind Harmer
0.002
3150981CHESPKA
Adder
0.851
316212AC1-099_GEN
Solar/Wind Harmer
0.35
3145663CRESWEL
Solar/Wind Harmer
0.189
971163AH1-040 GEN
Solar/Wind Harmer
5.416
3130156CHOWAN
Solar/Wind Harmer
0.068
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.219
3146516WINFALL
Solar/Wind Harmer
0.067
3146456SLIGO L269
Solar/Wind Harmer
0.067
316388AE2-253 GEN
Solar/Wind Harmer
0.209
3145963POPLR C
Solar/Wind Harmer
0.066
316174AB2-169 GEN
Solar/Wind Harmer
0.002
944591AF1-124 GEN
Solar/Wind Harmer
14.705
3146293MARTNCO
Solar/Wind Harmer
0.059
3146233WITAKRS
Solar/Wind Harmer
0.255
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
316494AC1-189 GEN
Solar/Wind Harmer
0.213
961671AG1-007 GEN
Solar/Wind Harmer
0.01
3146083TARBORO
Solar/Wind Harmer
0.063
3145493TOT1
Solar/Wind Harmer
0.281
316359AB2-059 GEN
Solar/Wind Harmer
0.225
316049AB1-081 GEN
Solar/Wind Harmer
0.359
3142053HEARTS
Solar/Wind Harmer
0.11
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.05
316129AC1-054 GEN
Solar/Wind Harmer
0.232
957481AF2-042 GEN
Solar/Wind Harmer
16.224
971065AG2-659 GEN
Solar/Wind Harmer
2.591
316294AC1-161 GEN
Solar/Wind Harmer
1.003
3142543TWELFTH
Solar/Wind Helper
0.04
3143226MDLTHAN
Solar/Wind Helper
0.196
3143526WINTERP
Solar/Wind Helper
0.738
316336AC2-165 C
Solar/Wind Helper
0.631
944641AF1-129 GEN
50/50
137.955
3150781HOPHCF2
50/50
0.572
3150791HOPHCF3
50/50
0.572
3150761HOPPOLC
50/50
0.363
971213AH1-066 GEN
50/50
0.501
316240AF1-291 C
Solar/Wind Harmer
0.002
970657AG2-426 GEN
Solar/Wind Harmer
4.141
970657AG2-426 GEN
Solar/Wind Harmer
0.868
3144356SAPONY
Solar/Wind Harmer
0.986
316033AB2-134 GEN
Solar/Wind Harmer
0.007
315697AD1-025 GEN
Solar/Wind Harmer
0.125
316236AE1-162_GEN
Solar/Wind Harmer
0.001
316181AB2-040 GEN
Solar/Wind Harmer
0.113
3142666NORTHAMPTON
Solar/Wind Harmer
0.077
3142666NORTHAMPTON
Solar/Wind Harmer
0.077
3142666NORTHAMPTON
Solar/Wind Harmer
0.077
3142666NORTHAMPTON
Solar/Wind Harmer
0.046
3145796HORNRTN
Solar/Wind Harmer
0.229
972185AH1-677 GEN
Adder
4.193
315742AE1-103 GEN
Solar/Wind Harmer
0.001
972187AH1-678 GEN
Adder
2.094
3145593CAROLNA
Solar/Wind Harmer
0.072
3145593CAROLNA
Solar/Wind Harmer
0.072
966811AG1-552 GEN
Solar/Wind Harmer
0.786
3145593CAROLNA
Solar/Wind Harmer
0.09
316426AA2-053 GEN
Solar/Wind Harmer
0.243
3145783HORNRTN
Solar/Wind Harmer
1.275
3145783HORNRTN
Solar/Wind Harmer
1.02
3145783HORNRTN
Solar/Wind Harmer
0.319
3145783HORNRTN
Solar/Wind Harmer
0.128
3145893MURPHYS
Solar/Wind Harmer
0.48
3145893MURPHYS
Solar/Wind Harmer
0.129
3146173TUNIS
Solar/Wind Harmer
0.071
3146173TUNIS
Solar/Wind Harmer
0.071
970933AG2-581 GEN
Solar/Wind Harmer
5.578
316036AC1-147 C
Solar/Wind Harmer
0.013
3150991CHESPKB
Adder
0.714
3150991CHESPKB
Adder
0.697
316065AD1-022 GEN
Solar/Wind Harmer
3.139
316274AC1-208 GEN
Solar/Wind Harmer
0.352
316431W1029_GEN1
Solar/Wind Harmer
0
316433W1029_GEN2
Solar/Wind Harmer
0
3146376EDENTON
Solar/Wind Harmer
0.301
3146376EDENTON
Solar/Wind Harmer
0.301
3146626S HERTFORD
Solar/Wind Harmer
0.067
3146626S HERTFORD
Solar/Wind Harmer
0.067
3146516WINFALL
Solar/Wind Harmer
0.067
3146516WINFALL
Solar/Wind Harmer
0.067
3146516WINFALL
Solar/Wind Harmer
0.067
316316AC1-027 C
Solar/Wind Harmer
0.065
3142956BIRDNECK
Solar/Wind Harmer
0
3146386ELIZ CT
Solar/Wind Harmer
0.067
3130086AYDLETT
Solar/Wind Harmer
0.267
3146456SLIGO L269
Solar/Wind Harmer
1.182
3137176SLIGO L2192
Solar/Wind Harmer
0.266
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
316017AA1-139 ULT1
Solar/Wind Harmer
0.037
316339AD2-160 GEN
Solar/Wind Harmer
0.108
316185AD1-033 GEN
Solar/Wind Harmer
0.002
3145506HICKORY
Solar/Wind Harmer
0.266
3145506HICKORY
Solar/Wind Harmer
0.16
3145506HICKORY
Solar/Wind Harmer
0.04
3145933PARMELE
Solar/Wind Harmer
0.128
3145933PARMELE
Solar/Wind Harmer
0.064
3145493TOT1
Solar/Wind Harmer
0.146
3145453TOT5
Solar/Wind Harmer
0.088
3145603CNETO
Solar/Wind Harmer
0.059
961601AG1-000A GEN
Solar/Wind Harmer
1.12
316263AC1-034 GEN
Solar/Wind Harmer
2.384
970099AG2-077 GEN
Solar/Wind Harmer
6.49
3143526WINTERP
Solar/Wind Helper
0.738
LAGNLTFEXP_LAGN->PJM
CLTF
2.199
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.502
TVALTFEXP_TVA->PJM
CLTF
1.094
CPLELTFEXP_CPLE->PJM
CLTF
3.592
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.141
NYPJM->LTFIMP_NY
CLTF
0.55
LGEELTFEXP_LGEE->PJM
CLTF
0.33
WECLTFEXP_WEC->PJM
CLTF
0.169
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.771
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.694
MECLTFEXP_MEC->PJM
CLTF
0.959
SIGELTFEXP_SIGE->PJM
CLTF
0.028

Details for 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 56372_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:151.48 %
Rating:812.0 MVA
Rating Type:C
MVA to Mitigate:1230.05
MW Contribution:1.04
Bus #Bus NameTypeMW Contribution
3150801HOPHCF4
50/50
0.862
971211AH1-065 GEN
50/50
1.039
315839AE2-212 C
Solar/Wind Harmer
0.779
315813AE1-149 C
Solar/Wind Harmer
10.424
970133AG2-095 GEN
Solar/Wind Harmer
1.847
970129AG2-093 GEN
Solar/Wind Harmer
8.29
970659AG2-427 GEN
Solar/Wind Harmer
1.384
316083AB2-161 GEN
Solar/Wind Harmer
2.327
315778AD1-151 GEN
Solar/Wind Harmer
11.708
970661AG2-428 GEN
Solar/Wind Harmer
2.498
965281AG1-393 GEN
Solar/Wind Harmer
1.628
316365GEN2_N
Solar/Wind Harmer
0.759
961611AG1-000B GEN
Solar/Wind Harmer
2.314
966621AG1-532 GEN
Solar/Wind Harmer
0.201
3151221GRAVEL6
Adder
6.371
3151171GRAVELC
Adder
1.226
313506AB2-031 GEN
Solar/Wind Harmer
0.741
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
3145796HORNRTN
Solar/Wind Harmer
-0.036
3145796HORNRTN
Solar/Wind Harmer
-0.009
3145336SMITFLD
Solar/Wind Harmer
-0.004
3147043LAWRENC
Solar/Wind Harmer
-0.005
3145273HOLLAND
Solar/Wind Harmer
-0.006
3156081AA2-088 GEN
Solar/Wind Harmer
2.685
3145893MURPHYS
Solar/Wind Harmer
0.057
3145893MURPHYS
Solar/Wind Harmer
-0.008
957521AF2-046 GEN
Solar/Wind Harmer
6.399
961681AG1-008 GEN
Solar/Wind Harmer
6.399
3146263WOODLND
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315724AD1-057 GEN
Solar/Wind Harmer
0.46
316463AE2-346 GEN
Solar/Wind Harmer
0.129
316140AB2-099
Solar/Wind Harmer
0.054
962331AG1-082 GEN
Solar/Wind Harmer
0.998
316317KELFORD C
Solar/Wind Harmer
0.371
3145823KELFORD
Solar/Wind Harmer
-0.008
3156021HOLLOMANSOL
Solar/Wind Harmer
1.057
3144536CHRHLND
Solar/Wind Harmer
-0.001
316210AC1-098 GEN
Solar/Wind Harmer
1.215
3146206CASHIE
Solar/Wind Harmer
-0.008
315737AD1-076 GEN
Solar/Wind Harmer
1.437
971157AH1-035 GEN
Solar/Wind Harmer
0.944
315614AA2-178 GEN
Solar/Wind Harmer
0.81
316327AA2-057 GEN
Solar/Wind Harmer
0.754
3146376EDENTON
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
316435W1029_GEN3
Solar/Wind Harmer
1.336
3146516WINFALL
Solar/Wind Harmer
-0.007
3144873MCLAUGH
Solar/Wind Harmer
0
3145963POPLR C
Solar/Wind Harmer
-0.007
3151101ELIZAR3
Adder
6.035
3146233WITAKRS
Solar/Wind Harmer
0.152
3146233WITAKRS
Solar/Wind Harmer
-0.005
316320Y1-086
Solar/Wind Harmer
0.427
3138543CONSLDL
Solar/Wind Harmer
-0.005
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.88
3145933PARMELE
Solar/Wind Harmer
-0.007
970917AG2-570 GEN
Solar/Wind Harmer
17.97
966801AG1-551 GEN
Solar/Wind Harmer
0.898
961601AG1-000A GEN
Solar/Wind Harmer
2.848
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
944581AF1-123 GEN
Solar/Wind Harmer
31.627
944601AF1-125 GEN
Solar/Wind Harmer
31.133
316313AB2-026
Solar/Wind Helper
0.199
316258AE1-075 C
Solar/Wind Helper
0.179
316405AF2-144 C
Solar/Wind Helper
0.149
3150771HOPHCF1
50/50
0.592
970129AG2-093 GEN
Solar/Wind Harmer
3.358
970659AG2-427 GEN
Solar/Wind Harmer
7.812
316458AB2-190 GEN2
Solar/Wind Harmer
1.472
316381AD1-082 GEN
Solar/Wind Harmer
1.315
971069AG2-661 GEN
Solar/Wind Harmer
2.139
970661AG2-428 GEN
Solar/Wind Harmer
14.096
971647AH1-324 GEN
Solar/Wind Harmer
5.949
316023GEN1_S
Solar/Wind Harmer
0.759
315671AE2-027_GEN
Solar/Wind Harmer
8.385
961611AG1-000B GEN
Solar/Wind Harmer
5.423
960081AF2-299 GEN
Solar/Wind Harmer
1.117
3151171GRAVELC
Adder
0.932
316011AB1-132 GEN
Solar/Wind Harmer
1.955
962571AG1-106 GEN
Solar/Wind Harmer
1.343
3145796HORNRTN
Solar/Wind Harmer
-0.03
3145796HORNRTN
Solar/Wind Harmer
-0.009
971795AH1-408 GEN
Solar/Wind Harmer
6.761
3145336SMITFLD
Solar/Wind Harmer
-0.035
3147043LAWRENC
Adder
0.692
316190AA2-174 GEN
Solar/Wind Harmer
0.102
3145783HORNRTN
Solar/Wind Harmer
-0.008
316093AE2-104_GEN
Solar/Wind Harmer
2.417
3145893MURPHYS
Solar/Wind Harmer
-0.032
3145893MURPHYS
Solar/Wind Harmer
0.242
3146263WOODLND
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315722AD1-056 GEN
Solar/Wind Harmer
0.836
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145823KELFORD
Solar/Wind Harmer
-0.008
940641AE2-051 GEN
Solar/Wind Harmer
7.3
316212AC1-099_GEN
Solar/Wind Harmer
0.675
3146206CASHIE
Solar/Wind Harmer
-0.008
971547AH1-271 GEN
Solar/Wind Harmer
1.919
939411AE1-173 GEN
Solar/Wind Harmer
38.069
316072AD1-144
Solar/Wind Harmer
0.153
3145663CRESWEL
Solar/Wind Harmer
-0.021
971163AH1-040 GEN
Solar/Wind Harmer
7.035
3130156CHOWAN
Solar/Wind Harmer
-0.007
316246AF1-032 C
Solar/Wind Harmer
0.15
315800Z1-036_GEN1
Solar/Wind Harmer
1.831
3146516WINFALL
Solar/Wind Harmer
-0.024
3146516WINFALL
Solar/Wind Harmer
-0.007
316375AC2-012 GEN
Solar/Wind Harmer
2.546
3145963POPLR C
Solar/Wind Harmer
-0.007
3150981CHESPKA
Adder
0.818
316174AB2-169 GEN
Solar/Wind Harmer
1.129
3146233WITAKRS
Solar/Wind Harmer
-0.029
3146456SLIGO L269
Solar/Wind Harmer
-0.007
316388AE2-253 GEN
Solar/Wind Harmer
0.485
970919AG2-571 GEN
Solar/Wind Harmer
2.275
3146293MARTNCO
Solar/Wind Harmer
0.044
970087AG2-069 GEN
Solar/Wind Harmer
6.711
961671AG1-007 GEN
Solar/Wind Harmer
0.09
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.212
316494AC1-189 GEN
Solar/Wind Harmer
0.767
316359AB2-059 GEN
Solar/Wind Harmer
0.959
316049AB1-081 GEN
Solar/Wind Harmer
0.768
3142053HEARTS
Solar/Wind Harmer
0.084
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
944591AF1-124 GEN
Solar/Wind Harmer
31.741
316129AC1-054 GEN
Solar/Wind Harmer
0.605
971065AG2-659 GEN
Solar/Wind Harmer
3.382
3142543TWELFTH
Solar/Wind Helper
0.039
3143226MDLTHAN
Solar/Wind Helper
0.191
3143526WINTERP
Solar/Wind Helper
0.709
316336AC2-165 C
Solar/Wind Helper
0.619
970603AG2-384 GEN
50/50
5.995
315779AE2-040
50/50
1.868
3143316POE
Solar/Wind Harmer
-0.083
316315AB2-025 C
Solar/Wind Harmer
0.406
315814AE2-033 C
Solar/Wind Harmer
13.816
316132AB2-190 GEN1
Solar/Wind Harmer
1.472
316369SG1_INVT
Solar/Wind Harmer
2.286
315833AF1-017_GEN
Solar/Wind Harmer
2.02
316349AD2-085 GEN
Solar/Wind Harmer
0.946
316311AC2-079 GEN
Solar/Wind Harmer
5.341
946281AF1-292 GEN
Solar/Wind Harmer
0.222
972265AH1-717 GEN
Adder
6.804
3151201GRAVEL4
Adder
6.378
3151191GRAVEL3
Adder
6.298
3151211GRAVEL5
Adder
6.298
316087AB2-174 GEN
Solar/Wind Harmer
1.345
315652AC1-086 GEN
Solar/Wind Harmer
10.514
3145796HORNRTN
Solar/Wind Harmer
-0.029
3145796HORNRTN
Solar/Wind Harmer
-0.004
971445AH1-216 GEN
Solar/Wind Harmer
5.552
3137643SOCKMAN
Solar/Wind Harmer
-0.035
315607AA1-063A GEN
Solar/Wind Harmer
0.844
3146043SEABORD
Solar/Wind Harmer
-0.008
315835AF2-110_GEN
Solar/Wind Harmer
1.039
965291AG1-394 GEN
Solar/Wind Harmer
0.734
316318V4-068
Solar/Wind Harmer
0.203
3145893MURPHYS
Solar/Wind Harmer
-0.022
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145513AHOSKIE
Solar/Wind Harmer
0.07
961941AG1-037 GEN
Solar/Wind Harmer
0.06
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
941031AE2-094 GEN
Solar/Wind Harmer
14.686
944011AF1-069 GEN
Solar/Wind Harmer
4.602
3146033SCOT NK
Solar/Wind Harmer
-0.031
3146206CASHIE
Solar/Wind Harmer
-0.008
970601AG2-382 GEN
Solar/Wind Harmer
3.358
970673AG2-436 GEN
Solar/Wind Harmer
16.094
970673AG2-436 GEN
Solar/Wind Harmer
8.149
315732AD1-074 GEN1
Solar/Wind Harmer
1.529
315733AD1-074 GEN2
Solar/Wind Harmer
1.529
315735AD1-075 GEN1
Solar/Wind Harmer
0.765
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
315816AE2-034 GEN
Solar/Wind Harmer
0.607
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
971967AH1-528 GEN
Solar/Wind Harmer
13.984
316305AF2-043 C
Solar/Wind Harmer
0.224
315611Z1-036_GEN2
Solar/Wind Harmer
1.831
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
3152611GOSPORTB
Adder
0.834
3152621GOSPORTC
Adder
0.708
3152601GOSPORTA
Adder
0.653
316321Z2-027
Solar/Wind Harmer
0.197
3145176PASQUOTANK
Solar/Wind Harmer
-0.005
3146396TANGLEW
Solar/Wind Harmer
0.135
3151081ELIZAR1
Adder
5.959
3151091ELIZAR2
Adder
5.855
316319Z2-044 C
Solar/Wind Harmer
0.403
313526AB2-022
Solar/Wind Harmer
0.196
3146406KITTY HAWK
Solar/Wind Harmer
0.006
319010AE1-072 C
Solar/Wind Harmer
1.461
957871AF2-081 GEN
Solar/Wind Harmer
3.603
970085AG2-068 GEN
Solar/Wind Harmer
4.474
970581AG2-369 GEN
Solar/Wind Harmer
3.847
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
316420AA1-050 GEN
Solar/Wind Harmer
0.815
957861AF2-080 GEN
Solar/Wind Harmer
3.117
316005AA1-067
Solar/Wind Harmer
0.144
3145746EVERETS
Solar/Wind Harmer
-0.028
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
970181AG2-120 GEN
Solar/Wind Harmer
0.933
970831AG2-522 GEN
Solar/Wind Harmer
3.523
316233AE1-074 FULL
Solar/Wind Helper
0.208
944641AF1-129 GEN
50/50
142.125
3150781HOPHCF2
50/50
0.592
3150791HOPHCF3
50/50
0.592
3150761HOPPOLC
50/50
0.376
971213AH1-066 GEN
50/50
0.52
316240AF1-291 C
Solar/Wind Harmer
0.916
3144356SAPONY
Solar/Wind Harmer
0.524
970657AG2-426 GEN
Solar/Wind Harmer
4.354
970657AG2-426 GEN
Solar/Wind Harmer
0.91
316033AB2-134 GEN
Solar/Wind Harmer
4.127
315697AD1-025 GEN
Solar/Wind Harmer
2.588
316181AB2-040 GEN
Solar/Wind Harmer
1.285
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145796HORNRTN
Solar/Wind Harmer
-0.027
316236AE1-162_GEN
Solar/Wind Harmer
0.268
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.946
3145593CAROLNA
Solar/Wind Harmer
0.07
316426AA2-053 GEN
Solar/Wind Harmer
0.841
3145783HORNRTN
Solar/Wind Harmer
0.986
3145783HORNRTN
Solar/Wind Harmer
0.789
3145783HORNRTN
Solar/Wind Harmer
0.247
3145783HORNRTN
Solar/Wind Harmer
0.099
315742AE1-103 GEN
Solar/Wind Harmer
0.867
3145893MURPHYS
Solar/Wind Harmer
0.228
3145893MURPHYS
Solar/Wind Harmer
-0.015
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316274AC1-208 GEN
Solar/Wind Harmer
0.84
316065AD1-022 GEN
Solar/Wind Harmer
3.817
972185AH1-677 GEN
Adder
3.783
972187AH1-678 GEN
Adder
1.891
3146376EDENTON
Solar/Wind Harmer
0.221
3146376EDENTON
Solar/Wind Harmer
0.221
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.336
316433W1029_GEN2
Solar/Wind Harmer
1.336
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316036AC1-147 C
Solar/Wind Harmer
0.198
3150991CHESPKB
Adder
0.686
3150991CHESPKB
Adder
0.669
3146386ELIZ CT
Solar/Wind Harmer
-0.007
316316AC1-027 C
Solar/Wind Harmer
0.223
3142956BIRDNECK
Solar/Wind Harmer
0.389
3130086AYDLETT
Solar/Wind Harmer
-0.029
3137176SLIGO L2192
Solar/Wind Harmer
-0.029
3146456SLIGO L269
Solar/Wind Harmer
0.852
316018AA1-139 ULT2
Solar/Wind Harmer
0.617
316017AA1-139 ULT1
Solar/Wind Harmer
0.583
316339AD2-160 GEN
Solar/Wind Harmer
0.485
3145933PARMELE
Solar/Wind Harmer
-0.014
3145933PARMELE
Solar/Wind Harmer
-0.007
316185AD1-033 GEN
Solar/Wind Harmer
0.757
3145506HICKORY
Solar/Wind Harmer
-0.029
3145506HICKORY
Solar/Wind Harmer
-0.017
3145506HICKORY
Solar/Wind Harmer
-0.004
961601AG1-000A GEN
Solar/Wind Harmer
2.813
3145493TOT1
Solar/Wind Harmer
0.11
3145453TOT5
Solar/Wind Harmer
0.066
3145603CNETO
Solar/Wind Harmer
0.044
316263AC1-034 GEN
Solar/Wind Harmer
3.335
970933AG2-581 GEN
Solar/Wind Harmer
6.643
3143526WINTERP
Solar/Wind Helper
0.709
LAGNLTFEXP_LAGN->PJM
CLTF
2.063
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.093
TVALTFEXP_TVA->PJM
CLTF
1.027
CPLELTFEXP_CPLE->PJM
CLTF
3.413
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.422
NYPJM->LTFIMP_NY
CLTF
0.527
LGEELTFEXP_LGEE->PJM
CLTF
0.305
WECLTFEXP_WEC->PJM
CLTF
0.156
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.322
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.462
MECLTFEXP_MEC->PJM
CLTF
0.892
SIGELTFEXP_SIGE->PJM
CLTF
0.026

Details for 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 217_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:127.8 %
Rating:663.64 MVA
Rating Type:B
MVA to Mitigate:848.14
MW Contribution:1.21
Bus #Bus NameTypeMW Contribution
970603AG2-384 GEN
50/50
7.264
315779AE2-040
50/50
1.674
3143316POE
Solar/Wind Harmer
0.789
316132AB2-190 GEN1
Solar/Wind Harmer
0.795
316369SG1_INVT
Solar/Wind Harmer
0.005
316315AB2-025 C
Solar/Wind Harmer
0.097
3150801HOPHCF4
50/50
1.007
971211AH1-065 GEN
50/50
1.214
3151161SURRY 1
50/50
3.505
315839AE2-212 C
Solar/Wind Harmer
0.002
970133AG2-095 GEN
Solar/Wind Harmer
1.639
315813AE1-149 C
Solar/Wind Harmer
8.459
970129AG2-093 GEN
Solar/Wind Harmer
9.083
970659AG2-427 GEN
Solar/Wind Harmer
1.452
315778AD1-151 GEN
Solar/Wind Harmer
10.852
316083AB2-161 GEN
Solar/Wind Harmer
0.002
965281AG1-393 GEN
Solar/Wind Harmer
1.358
970661AG2-428 GEN
Solar/Wind Harmer
2.575
961611AG1-000B GEN
Solar/Wind Harmer
2.802
3151221GRAVEL6
Adder
6.634
3151171GRAVELC
Adder
1.276
316365GEN2_N
Solar/Wind Harmer
0.199
3145336SMITFLD
Solar/Wind Harmer
0.031
313506AB2-031 GEN
Solar/Wind Harmer
0.222
3142666NORTHAMPTON
Solar/Wind Harmer
0.071
3145796HORNRTN
Solar/Wind Harmer
0.281
3145796HORNRTN
Solar/Wind Harmer
0.07
3145273HOLLAND
Solar/Wind Harmer
0.05
3147043LAWRENC
Solar/Wind Harmer
0.04
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
3145893MURPHYS
Solar/Wind Harmer
0.107
3145893MURPHYS
Solar/Wind Harmer
0.064
3144536CHRHLND
Solar/Wind Harmer
0.01
957521AF2-046 GEN
Solar/Wind Harmer
4.751
961681AG1-008 GEN
Solar/Wind Harmer
4.751
3146173TUNIS
Solar/Wind Harmer
0.063
3146263WOODLND
Solar/Wind Harmer
0.063
316463AE2-346 GEN
Solar/Wind Harmer
0.054
316140AB2-099
Solar/Wind Harmer
0.022
3150771HOPHCF1
50/50
0.692
970129AG2-093 GEN
Solar/Wind Harmer
4.274
316458AB2-190 GEN2
Solar/Wind Harmer
0.795
970659AG2-427 GEN
Solar/Wind Harmer
6.637
971069AG2-661 GEN
Solar/Wind Harmer
2.412
316381AD1-082 GEN
Solar/Wind Harmer
0.139
970661AG2-428 GEN
Solar/Wind Harmer
12.106
971647AH1-324 GEN
Solar/Wind Harmer
4.953
315671AE2-027_GEN
Solar/Wind Harmer
7.008
961611AG1-000B GEN
Solar/Wind Harmer
5.51
3151171GRAVELC
Adder
0.971
316023GEN1_S
Solar/Wind Harmer
0.199
3145336SMITFLD
Solar/Wind Harmer
0.314
960081AF2-299 GEN
Solar/Wind Harmer
0.746
316011AB1-132 GEN
Solar/Wind Harmer
1.326
962571AG1-106 GEN
Solar/Wind Harmer
1.038
3145796HORNRTN
Solar/Wind Harmer
0.232
3145796HORNRTN
Solar/Wind Harmer
0.07
971795AH1-408 GEN
Solar/Wind Harmer
4.663
316093AE2-104_GEN
Solar/Wind Harmer
1.146
3147043LAWRENC
Adder
0.601
316190AA2-174 GEN
Solar/Wind Harmer
0
3145783HORNRTN
Solar/Wind Harmer
0.064
3145893MURPHYS
Solar/Wind Harmer
0.257
3145893MURPHYS
Solar/Wind Harmer
0.285
3146173TUNIS
Solar/Wind Harmer
0.063
3146263WOODLND
Solar/Wind Harmer
0.063
3145683EARLEYS
Solar/Wind Harmer
0.062
316072AD1-144
Solar/Wind Harmer
0.022
315722AD1-056 GEN
Solar/Wind Harmer
0.39
3145823KELFORD
Solar/Wind Harmer
0.061
3146206CASHIE
Solar/Wind Harmer
0.06
971547AH1-271 GEN
Solar/Wind Harmer
1.276
316212AC1-099_GEN
Solar/Wind Harmer
0.309
316246AF1-032 C
Solar/Wind Harmer
0.026
316375AC2-012 GEN
Solar/Wind Harmer
0.001
3150981CHESPKA
Adder
0.731
3145663CRESWEL
Solar/Wind Harmer
0.164
971163AH1-040 GEN
Solar/Wind Harmer
4.686
3130156CHOWAN
Solar/Wind Harmer
0.058
315800Z1-036_GEN1
Solar/Wind Harmer
0
3146516WINFALL
Solar/Wind Harmer
0.187
3146516WINFALL
Solar/Wind Harmer
0.058
3145963POPLR C
Solar/Wind Harmer
0.057
316174AB2-169 GEN
Solar/Wind Harmer
0.002
3146456SLIGO L269
Solar/Wind Harmer
0.056
3142543TWELFTH
Solar/Wind Helper
0.038
3143226MDLTHAN
Solar/Wind Helper
0.156
3143526WINTERP
Solar/Wind Helper
0.642
315814AE2-033 C
Solar/Wind Harmer
9.36
315833AF1-017_GEN
Solar/Wind Harmer
0
316349AD2-085 GEN
Solar/Wind Harmer
0.064
316311AC2-079 GEN
Solar/Wind Harmer
2.663
972265AH1-717 GEN
Adder
7.085
3151201GRAVEL4
Adder
6.641
3151191GRAVEL3
Adder
6.557
3151211GRAVEL5
Adder
6.557
971445AH1-216 GEN
Solar/Wind Harmer
5.618
316087AB2-174 GEN
Solar/Wind Harmer
0.002
315652AC1-086 GEN
Solar/Wind Harmer
8.025
3145796HORNRTN
Solar/Wind Harmer
0.225
3145796HORNRTN
Solar/Wind Harmer
0.028
3137643SOCKMAN
Solar/Wind Harmer
0.273
315835AF2-110_GEN
Solar/Wind Harmer
0.468
965291AG1-394 GEN
Solar/Wind Harmer
0.291
3146043SEABORD
Solar/Wind Harmer
0.065
315607AA1-063A GEN
Solar/Wind Harmer
0.133
3145893MURPHYS
Solar/Wind Harmer
0.173
3145893MURPHYS
Solar/Wind Harmer
0.064
3145513AHOSKIE
Solar/Wind Harmer
0.13
3145513AHOSKIE
Solar/Wind Harmer
0.062
3145683EARLEYS
Solar/Wind Harmer
0.123
3145683EARLEYS
Solar/Wind Harmer
0.062
3145683EARLEYS
Solar/Wind Harmer
0.062
3146033SCOT NK
Solar/Wind Harmer
0.241
3146206CASHIE
Solar/Wind Harmer
0.06
970601AG2-382 GEN
Solar/Wind Harmer
2.233
315732AD1-074 GEN1
Solar/Wind Harmer
0.338
315733AD1-074 GEN2
Solar/Wind Harmer
0.338
315735AD1-075 GEN1
Solar/Wind Harmer
0.169
3130546PLYMOUTH
Solar/Wind Harmer
0.059
316305AF2-043 C
Solar/Wind Harmer
0
3152611GOSPORTB
Adder
0.746
3152621GOSPORTC
Adder
0.633
3152601GOSPORTA
Adder
0.584
315816AE2-034 GEN
Solar/Wind Harmer
0.251
3130156CHOWAN
Solar/Wind Harmer
0.058
3130156CHOWAN
Solar/Wind Harmer
0.058
3146486SUNBURY
Solar/Wind Harmer
0.058
3146486SUNBURY
Solar/Wind Harmer
0.058
315611Z1-036_GEN2
Solar/Wind Harmer
0
3151081ELIZAR1
Adder
5.305
3151091ELIZAR2
Adder
5.213
316321Z2-027
Solar/Wind Harmer
0.011
3145176PASQUOTANK
Solar/Wind Harmer
0.035
3146396TANGLEW
Solar/Wind Harmer
0.158
313526AB2-022
Solar/Wind Harmer
0.031
3146406KITTY HAWK
Solar/Wind Harmer
0.007
319010AE1-072 C
Solar/Wind Harmer
0.284
957871AF2-081 GEN
Solar/Wind Harmer
2.802
316233AE1-074 FULL
Solar/Wind Helper
0.189
944641AF1-129 GEN
50/50
172.228
3150781HOPHCF2
50/50
0.692
3150791HOPHCF3
50/50
0.692
3150761HOPPOLC
50/50
0.439
971213AH1-066 GEN
50/50
0.607
316240AF1-291 C
Solar/Wind Harmer
0.003
970657AG2-426 GEN
Solar/Wind Harmer
4.515
970657AG2-426 GEN
Solar/Wind Harmer
0.946
316033AB2-134 GEN
Solar/Wind Harmer
0.007
315697AD1-025 GEN
Solar/Wind Harmer
0.143
3144356SAPONY
Solar/Wind Harmer
1.003
316236AE1-162_GEN
Solar/Wind Harmer
0.001
316181AB2-040 GEN
Solar/Wind Harmer
0.104
3142666NORTHAMPTON
Solar/Wind Harmer
0.071
3142666NORTHAMPTON
Solar/Wind Harmer
0.071
3142666NORTHAMPTON
Solar/Wind Harmer
0.071
3142666NORTHAMPTON
Solar/Wind Harmer
0.043
3145796HORNRTN
Solar/Wind Harmer
0.211
315742AE1-103 GEN
Solar/Wind Harmer
0.001
3145593CAROLNA
Solar/Wind Harmer
0.065
3145593CAROLNA
Solar/Wind Harmer
0.065
966811AG1-552 GEN
Solar/Wind Harmer
0.708
3145593CAROLNA
Solar/Wind Harmer
0.081
316426AA2-053 GEN
Solar/Wind Harmer
0.218
3145783HORNRTN
Solar/Wind Harmer
1.146
3145783HORNRTN
Solar/Wind Harmer
0.916
3145783HORNRTN
Solar/Wind Harmer
0.286
3145783HORNRTN
Solar/Wind Harmer
0.115
3145893MURPHYS
Solar/Wind Harmer
0.43
3145893MURPHYS
Solar/Wind Harmer
0.115
3146173TUNIS
Solar/Wind Harmer
0.063
3146173TUNIS
Solar/Wind Harmer
0.063
316274AC1-208 GEN
Solar/Wind Harmer
0.311
316065AD1-022 GEN
Solar/Wind Harmer
2.738
316036AC1-147 C
Solar/Wind Harmer
0.011
3150991CHESPKB
Adder
0.613
3150991CHESPKB
Adder
0.599
3146376EDENTON
Solar/Wind Harmer
0.259
3146376EDENTON
Solar/Wind Harmer
0.259
316431W1029_GEN1
Solar/Wind Harmer
0
316433W1029_GEN2
Solar/Wind Harmer
0
3146626S HERTFORD
Solar/Wind Harmer
0.058
3146626S HERTFORD
Solar/Wind Harmer
0.058
3146516WINFALL
Solar/Wind Harmer
0.058
3146516WINFALL
Solar/Wind Harmer
0.058
3146516WINFALL
Solar/Wind Harmer
0.058
316316AC1-027 C
Solar/Wind Harmer
0.055
3142956BIRDNECK
Solar/Wind Harmer
0
3146386ELIZ CT
Solar/Wind Harmer
0.057
3130086AYDLETT
Solar/Wind Harmer
0.226
3146456SLIGO L269
Solar/Wind Harmer
0.998
3137176SLIGO L2192
Solar/Wind Harmer
0.224
316018AA1-139 ULT2
Solar/Wind Harmer
0.001
316017AA1-139 ULT1
Solar/Wind Harmer
0.031
3143526WINTERP
Solar/Wind Helper
0.642
966871AG1-558 GEN
Solar/Wind Helper
0.164
962331AG1-082 GEN
Solar/Wind Harmer
0.665
315724AD1-057 GEN
Solar/Wind Harmer
0.231
3156021HOLLOMANSOL
Solar/Wind Harmer
0.277
316317KELFORD C
Solar/Wind Harmer
0.006
3145823KELFORD
Solar/Wind Harmer
0.061
3146206CASHIE
Solar/Wind Harmer
0.06
316210AC1-098 GEN
Solar/Wind Harmer
0.554
315737AD1-076 GEN
Solar/Wind Harmer
0.758
971157AH1-035 GEN
Solar/Wind Harmer
0.706
3144873MCLAUGH
Solar/Wind Harmer
0.001
315614AA2-178 GEN
Solar/Wind Harmer
0.335
3146376EDENTON
Solar/Wind Harmer
0.058
316435W1029_GEN3
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
5.373
3146626S HERTFORD
Solar/Wind Harmer
0.058
3146516WINFALL
Solar/Wind Harmer
0.058
316327AA2-057 GEN
Solar/Wind Harmer
0.086
316320Y1-086
Solar/Wind Harmer
0
3145963POPLR C
Solar/Wind Harmer
0.057
3146456SLIGO L269
Solar/Wind Harmer
0.056
971153AH1-033 GEN
Solar/Wind Harmer
0.652
316473AC1-191 GEN
Solar/Wind Helper
0.741
LAGNLTFEXP_LAGN->PJM
CLTF
1.583
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.669
TVALTFEXP_TVA->PJM
CLTF
0.786
CPLELTFEXP_CPLE->PJM
CLTF
2.766
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.843
NYPJM->LTFIMP_NY
CLTF
0.415
LGEELTFEXP_LGEE->PJM
CLTF
0.215
WECLTFEXP_WEC->PJM
CLTF
0.11
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.689
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.63
MECLTFEXP_MEC->PJM
CLTF
0.648
SIGELTFEXP_SIGE->PJM
CLTF
0.019

Details for 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T576_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T576_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:126.92 %
Rating:812.0 MVA
Rating Type:C
MVA to Mitigate:1030.57
MW Contribution:0.9
Bus #Bus NameTypeMW Contribution
3150771HOPHCF1
50/50
0.514
970129AG2-093 GEN
Solar/Wind Harmer
2.914
316458AB2-190 GEN2
Solar/Wind Harmer
1.277
970659AG2-427 GEN
Solar/Wind Harmer
6.687
316381AD1-082 GEN
Solar/Wind Harmer
1.126
971069AG2-661 GEN
Solar/Wind Harmer
1.855
970661AG2-428 GEN
Solar/Wind Harmer
12.101
971647AH1-324 GEN
Solar/Wind Harmer
5.156
961611AG1-000B GEN
Solar/Wind Harmer
4.697
316023GEN1_S
Solar/Wind Harmer
0.619
3151171GRAVELC
Adder
0.807
315671AE2-027_GEN
Solar/Wind Harmer
6.365
960081AF2-299 GEN
Solar/Wind Harmer
0.917
316011AB1-132 GEN
Solar/Wind Harmer
1.627
962571AG1-106 GEN
Solar/Wind Harmer
1.118
3145336SMITFLD
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.008
940641AE2-051 GEN
Solar/Wind Harmer
7.023
971795AH1-408 GEN
Solar/Wind Harmer
5.557
316093AE2-104_GEN
Solar/Wind Harmer
2.111
939411AE1-173 GEN
Solar/Wind Harmer
35.95
3147043LAWRENC
Adder
0.569
316190AA2-174 GEN
Solar/Wind Harmer
0.086
3145783HORNRTN
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
-0.028
3145893MURPHYS
Solar/Wind Harmer
0.207
3146173TUNIS
Solar/Wind Harmer
-0.007
970919AG2-571 GEN
Solar/Wind Harmer
2.175
3146263WOODLND
Solar/Wind Harmer
-0.007
970087AG2-069 GEN
Solar/Wind Harmer
6.413
3145683EARLEYS
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.707
3145823KELFORD
Solar/Wind Harmer
-0.007
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.655
316212AC1-099_GEN
Solar/Wind Harmer
0.575
316072AD1-144
Solar/Wind Harmer
0.133
316246AF1-032 C
Solar/Wind Harmer
0.132
3145663CRESWEL
Solar/Wind Harmer
-0.018
971163AH1-040 GEN
Solar/Wind Harmer
6.116
316375AC2-012 GEN
Solar/Wind Harmer
2.253
3150981CHESPKA
Adder
0.723
3130156CHOWAN
Solar/Wind Harmer
-0.006
315800Z1-036_GEN1
Solar/Wind Harmer
1.603
3146516WINFALL
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.006
3146456SLIGO L269
Solar/Wind Harmer
-0.006
316388AE2-253 GEN
Solar/Wind Harmer
0.43
3145963POPLR C
Solar/Wind Harmer
-0.006
316174AB2-169 GEN
Solar/Wind Harmer
0.977
3142543TWELFTH
Solar/Wind Helper
0.044
3143226MDLTHAN
Solar/Wind Helper
0.286
3143526WINTERP
Solar/Wind Helper
1.113
316336AC2-165 C
Solar/Wind Helper
0.958
970603AG2-384 GEN
50/50
5.498
3143316POE
Solar/Wind Harmer
-0.071
316132AB2-190 GEN1
Solar/Wind Harmer
1.277
316315AB2-025 C
Solar/Wind Harmer
0.323
315814AE2-033 C
Solar/Wind Harmer
11.018
316369SG1_INVT
Solar/Wind Harmer
1.982
315833AF1-017_GEN
Solar/Wind Harmer
1.746
316349AD2-085 GEN
Solar/Wind Harmer
0.818
316311AC2-079 GEN
Solar/Wind Harmer
4.618
972265AH1-717 GEN
Adder
5.888
3151201GRAVEL4
Adder
5.519
3151191GRAVEL3
Adder
5.449
3151211GRAVEL5
Adder
5.449
946281AF1-292 GEN
Solar/Wind Harmer
0.182
971445AH1-216 GEN
Solar/Wind Harmer
4.836
316087AB2-174 GEN
Solar/Wind Harmer
1.112
315652AC1-086 GEN
Solar/Wind Harmer
8.747
941031AE2-094 GEN
Solar/Wind Harmer
14.21
944011AF1-069 GEN
Solar/Wind Harmer
4.452
3145796HORNRTN
Solar/Wind Harmer
-0.024
3145796HORNRTN
Solar/Wind Harmer
-0.003
970673AG2-436 GEN
Solar/Wind Harmer
15.521
970673AG2-436 GEN
Solar/Wind Harmer
7.859
3137643SOCKMAN
Solar/Wind Harmer
-0.029
315835AF2-110_GEN
Solar/Wind Harmer
0.908
971967AH1-528 GEN
Solar/Wind Harmer
13.4
315607AA1-063A GEN
Solar/Wind Harmer
0.714
3146043SEABORD
Solar/Wind Harmer
-0.007
965291AG1-394 GEN
Solar/Wind Harmer
0.627
316318V4-068
Solar/Wind Harmer
0.174
3145893MURPHYS
Solar/Wind Harmer
-0.019
3145893MURPHYS
Solar/Wind Harmer
-0.007
970085AG2-068 GEN
Solar/Wind Harmer
4.275
970581AG2-369 GEN
Solar/Wind Harmer
3.677
3145513AHOSKIE
Solar/Wind Harmer
0.059
961941AG1-037 GEN
Solar/Wind Harmer
0.051
3145513AHOSKIE
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.013
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
3146033SCOT NK
Solar/Wind Harmer
-0.026
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
2.896
315732AD1-074 GEN1
Solar/Wind Harmer
1.324
315733AD1-074 GEN2
Solar/Wind Harmer
1.324
315735AD1-075 GEN1
Solar/Wind Harmer
0.662
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
316305AF2-043 C
Solar/Wind Harmer
0.197
315816AE2-034 GEN
Solar/Wind Harmer
0.528
3152611GOSPORTB
Adder
0.738
3152621GOSPORTC
Adder
0.626
3152601GOSPORTA
Adder
0.578
3130156CHOWAN
Solar/Wind Harmer
-0.006
3130156CHOWAN
Solar/Wind Harmer
-0.006
3146486SUNBURY
Solar/Wind Harmer
-0.006
3146486SUNBURY
Solar/Wind Harmer
-0.006
315611Z1-036_GEN2
Solar/Wind Harmer
1.603
3151081ELIZAR1
Adder
5.276
3151091ELIZAR2
Adder
5.184
316321Z2-027
Solar/Wind Harmer
0.174
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.118
313526AB2-022
Solar/Wind Harmer
0.173
3146406KITTY HAWK
Solar/Wind Harmer
0.005
319010AE1-072 C
Solar/Wind Harmer
1.291
957871AF2-081 GEN
Solar/Wind Harmer
3.187
316233AE1-074 FULL
Solar/Wind Helper
0.327
944641AF1-129 GEN
50/50
130.338
3150781HOPHCF2
50/50
0.514
3150791HOPHCF3
50/50
0.514
3150761HOPPOLC
50/50
0.326
971213AH1-066 GEN
50/50
0.451
316240AF1-291 C
Solar/Wind Harmer
0.835
3144356SAPONY
Solar/Wind Harmer
0.418
970657AG2-426 GEN
Solar/Wind Harmer
3.732
970657AG2-426 GEN
Solar/Wind Harmer
0.78
316033AB2-134 GEN
Solar/Wind Harmer
3.578
315697AD1-025 GEN
Solar/Wind Harmer
2.244
316236AE1-162_GEN
Solar/Wind Harmer
0.233
316181AB2-040 GEN
Solar/Wind Harmer
1.066
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145796HORNRTN
Solar/Wind Harmer
-0.022
972185AH1-677 GEN
Adder
3.642
315742AE1-103 GEN
Solar/Wind Harmer
0.75
972187AH1-678 GEN
Adder
1.816
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.796
3145593CAROLNA
Solar/Wind Harmer
0.059
316426AA2-053 GEN
Solar/Wind Harmer
0.709
3145783HORNRTN
Solar/Wind Harmer
0.831
3145783HORNRTN
Solar/Wind Harmer
0.664
3145783HORNRTN
Solar/Wind Harmer
0.208
3145783HORNRTN
Solar/Wind Harmer
0.083
3145893MURPHYS
Solar/Wind Harmer
0.195
3145893MURPHYS
Solar/Wind Harmer
-0.013
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
970933AG2-581 GEN
Solar/Wind Harmer
6.3
316274AC1-208 GEN
Solar/Wind Harmer
0.714
316065AD1-022 GEN
Solar/Wind Harmer
3.296
316036AC1-147 C
Solar/Wind Harmer
0.176
3150991CHESPKB
Adder
0.607
3150991CHESPKB
Adder
0.592
3146376EDENTON
Solar/Wind Harmer
0.193
3146376EDENTON
Solar/Wind Harmer
0.193
316431W1029_GEN1
Solar/Wind Harmer
1.174
316433W1029_GEN2
Solar/Wind Harmer
1.174
3146626S HERTFORD
Solar/Wind Harmer
-0.006
3146626S HERTFORD
Solar/Wind Harmer
-0.006
3146516WINFALL
Solar/Wind Harmer
-0.006
3146516WINFALL
Solar/Wind Harmer
-0.006
3146516WINFALL
Solar/Wind Harmer
-0.006
316316AC1-027 C
Solar/Wind Harmer
0.198
3142956BIRDNECK
Solar/Wind Harmer
0.345
3146386ELIZ CT
Solar/Wind Harmer
-0.006
3130086AYDLETT
Solar/Wind Harmer
-0.025
3137176SLIGO L2192
Solar/Wind Harmer
-0.025
3146456SLIGO L269
Solar/Wind Harmer
0.753
316018AA1-139 ULT2
Solar/Wind Harmer
0.546
316017AA1-139 ULT1
Solar/Wind Harmer
0.516
316339AD2-160 GEN
Solar/Wind Harmer
0.43
316185AD1-033 GEN
Solar/Wind Harmer
0.671
3145506HICKORY
Solar/Wind Harmer
-0.025
3145506HICKORY
Solar/Wind Harmer
-0.015
3145506HICKORY
Solar/Wind Harmer
-0.004
3143526WINTERP
Solar/Wind Helper
1.113
3150801HOPHCF4
50/50
0.748
971211AH1-065 GEN
50/50
0.902
315839AE2-212 C
Solar/Wind Harmer
0.693
970133AG2-095 GEN
Solar/Wind Harmer
1.604
315813AE1-149 C
Solar/Wind Harmer
8.895
970129AG2-093 GEN
Solar/Wind Harmer
7.195
970659AG2-427 GEN
Solar/Wind Harmer
1.185
316083AB2-161 GEN
Solar/Wind Harmer
1.993
315778AD1-151 GEN
Solar/Wind Harmer
10.156
970661AG2-428 GEN
Solar/Wind Harmer
2.144
965281AG1-393 GEN
Solar/Wind Harmer
1.286
961611AG1-000B GEN
Solar/Wind Harmer
2.004
316365GEN2_N
Solar/Wind Harmer
0.619
3151221GRAVEL6
Adder
5.513
3151171GRAVELC
Adder
1.061
966621AG1-532 GEN
Solar/Wind Harmer
0.165
3145336SMITFLD
Solar/Wind Harmer
-0.003
313506AB2-031 GEN
Solar/Wind Harmer
0.614
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.03
3145796HORNRTN
Solar/Wind Harmer
-0.008
3145273HOLLAND
Solar/Wind Harmer
-0.005
3156081AA2-088 GEN
Solar/Wind Harmer
2.296
3147043LAWRENC
Solar/Wind Harmer
-0.004
3145893MURPHYS
Solar/Wind Harmer
0.049
3145893MURPHYS
Solar/Wind Harmer
-0.007
957521AF2-046 GEN
Solar/Wind Harmer
5.468
961681AG1-008 GEN
Solar/Wind Harmer
5.468
3146173TUNIS
Solar/Wind Harmer
-0.007
970917AG2-570 GEN
Solar/Wind Harmer
17.182
3146263WOODLND
Solar/Wind Harmer
-0.007
3144536CHRHLND
Solar/Wind Harmer
-0.001
316463AE2-346 GEN
Solar/Wind Harmer
0.11
316140AB2-099
Solar/Wind Harmer
0.046
962331AG1-082 GEN
Solar/Wind Harmer
0.853
315724AD1-057 GEN
Solar/Wind Harmer
0.389
3156021HOLLOMANSOL
Solar/Wind Harmer
0.906
316317KELFORD C
Solar/Wind Harmer
0.316
3145823KELFORD
Solar/Wind Harmer
-0.007
3146206CASHIE
Solar/Wind Harmer
-0.007
316210AC1-098 GEN
Solar/Wind Harmer
1.035
315737AD1-076 GEN
Solar/Wind Harmer
1.244
971157AH1-035 GEN
Solar/Wind Harmer
0.818
315614AA2-178 GEN
Solar/Wind Harmer
0.704
3144873MCLAUGH
Solar/Wind Harmer
0
3146376EDENTON
Solar/Wind Harmer
-0.006
316435W1029_GEN3
Solar/Wind Harmer
1.174
3146626S HERTFORD
Solar/Wind Harmer
-0.006
3146516WINFALL
Solar/Wind Harmer
-0.006
3151101ELIZAR3
Adder
5.343
316320Y1-086
Solar/Wind Harmer
0.376
3146456SLIGO L269
Solar/Wind Harmer
-0.006
971153AH1-033 GEN
Solar/Wind Harmer
0.778
316327AA2-057 GEN
Solar/Wind Harmer
0.644
3145963POPLR C
Solar/Wind Harmer
-0.006
316313AB2-026
Solar/Wind Helper
0.305
316258AE1-075 C
Solar/Wind Helper
0.274
316405AF2-144 C
Solar/Wind Helper
0.228
LAGNLTFEXP_LAGN->PJM
CLTF
1.798
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.316
TVALTFEXP_TVA->PJM
CLTF
0.892
CPLELTFEXP_CPLE->PJM
CLTF
3.052
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.003
NYPJM->LTFIMP_NY
CLTF
0.426
LGEELTFEXP_LGEE->PJM
CLTF
0.255
WECLTFEXP_WEC->PJM
CLTF
0.131
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.47
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.998
MECLTFEXP_MEC->PJM
CLTF
0.759
SIGELTFEXP_SIGE->PJM
CLTF
0.022

Details for 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:126.92 %
Rating:812.0 MVA
Rating Type:C
MVA to Mitigate:1030.57
MW Contribution:0.9
Bus #Bus NameTypeMW Contribution
3150771HOPHCF1
50/50
0.514
970129AG2-093 GEN
Solar/Wind Harmer
2.914
316458AB2-190 GEN2
Solar/Wind Harmer
1.277
970659AG2-427 GEN
Solar/Wind Harmer
6.687
316381AD1-082 GEN
Solar/Wind Harmer
1.126
971069AG2-661 GEN
Solar/Wind Harmer
1.855
970661AG2-428 GEN
Solar/Wind Harmer
12.101
971647AH1-324 GEN
Solar/Wind Harmer
5.156
961611AG1-000B GEN
Solar/Wind Harmer
4.697
316023GEN1_S
Solar/Wind Harmer
0.619
3151171GRAVELC
Adder
0.807
315671AE2-027_GEN
Solar/Wind Harmer
6.365
960081AF2-299 GEN
Solar/Wind Harmer
0.917
316011AB1-132 GEN
Solar/Wind Harmer
1.627
962571AG1-106 GEN
Solar/Wind Harmer
1.118
3145336SMITFLD
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.008
940641AE2-051 GEN
Solar/Wind Harmer
7.023
971795AH1-408 GEN
Solar/Wind Harmer
5.557
316093AE2-104_GEN
Solar/Wind Harmer
2.111
939411AE1-173 GEN
Solar/Wind Harmer
35.95
3147043LAWRENC
Adder
0.569
316190AA2-174 GEN
Solar/Wind Harmer
0.086
3145783HORNRTN
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
-0.028
3145893MURPHYS
Solar/Wind Harmer
0.207
3146173TUNIS
Solar/Wind Harmer
-0.007
970919AG2-571 GEN
Solar/Wind Harmer
2.175
3146263WOODLND
Solar/Wind Harmer
-0.007
970087AG2-069 GEN
Solar/Wind Harmer
6.413
3145683EARLEYS
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.707
3145823KELFORD
Solar/Wind Harmer
-0.007
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.655
316212AC1-099_GEN
Solar/Wind Harmer
0.575
316072AD1-144
Solar/Wind Harmer
0.133
316246AF1-032 C
Solar/Wind Harmer
0.132
3145663CRESWEL
Solar/Wind Harmer
-0.018
971163AH1-040 GEN
Solar/Wind Harmer
6.116
316375AC2-012 GEN
Solar/Wind Harmer
2.253
3150981CHESPKA
Adder
0.723
3130156CHOWAN
Solar/Wind Harmer
-0.006
315800Z1-036_GEN1
Solar/Wind Harmer
1.603
3146516WINFALL
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.006
3146456SLIGO L269
Solar/Wind Harmer
-0.006
316388AE2-253 GEN
Solar/Wind Harmer
0.43
3145963POPLR C
Solar/Wind Harmer
-0.006
316174AB2-169 GEN
Solar/Wind Harmer
0.977
3142543TWELFTH
Solar/Wind Helper
0.044
3143226MDLTHAN
Solar/Wind Helper
0.286
3143526WINTERP
Solar/Wind Helper
1.113
316336AC2-165 C
Solar/Wind Helper
0.958
970603AG2-384 GEN
50/50
5.498
3143316POE
Solar/Wind Harmer
-0.071
316132AB2-190 GEN1
Solar/Wind Harmer
1.277
316315AB2-025 C
Solar/Wind Harmer
0.323
315814AE2-033 C
Solar/Wind Harmer
11.018
316369SG1_INVT
Solar/Wind Harmer
1.982
315833AF1-017_GEN
Solar/Wind Harmer
1.746
316349AD2-085 GEN
Solar/Wind Harmer
0.818
316311AC2-079 GEN
Solar/Wind Harmer
4.618
972265AH1-717 GEN
Adder
5.888
3151201GRAVEL4
Adder
5.519
3151191GRAVEL3
Adder
5.449
3151211GRAVEL5
Adder
5.449
946281AF1-292 GEN
Solar/Wind Harmer
0.182
971445AH1-216 GEN
Solar/Wind Harmer
4.836
316087AB2-174 GEN
Solar/Wind Harmer
1.112
315652AC1-086 GEN
Solar/Wind Harmer
8.747
941031AE2-094 GEN
Solar/Wind Harmer
14.21
944011AF1-069 GEN
Solar/Wind Harmer
4.452
3145796HORNRTN
Solar/Wind Harmer
-0.024
3145796HORNRTN
Solar/Wind Harmer
-0.003
970673AG2-436 GEN
Solar/Wind Harmer
15.521
970673AG2-436 GEN
Solar/Wind Harmer
7.859
3137643SOCKMAN
Solar/Wind Harmer
-0.029
315835AF2-110_GEN
Solar/Wind Harmer
0.908
971967AH1-528 GEN
Solar/Wind Harmer
13.4
315607AA1-063A GEN
Solar/Wind Harmer
0.714
3146043SEABORD
Solar/Wind Harmer
-0.007
965291AG1-394 GEN
Solar/Wind Harmer
0.627
316318V4-068
Solar/Wind Harmer
0.174
3145893MURPHYS
Solar/Wind Harmer
-0.019
3145893MURPHYS
Solar/Wind Harmer
-0.007
970085AG2-068 GEN
Solar/Wind Harmer
4.275
970581AG2-369 GEN
Solar/Wind Harmer
3.677
3145513AHOSKIE
Solar/Wind Harmer
0.059
961941AG1-037 GEN
Solar/Wind Harmer
0.051
3145513AHOSKIE
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.013
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
3146033SCOT NK
Solar/Wind Harmer
-0.026
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
2.896
315732AD1-074 GEN1
Solar/Wind Harmer
1.324
315733AD1-074 GEN2
Solar/Wind Harmer
1.324
315735AD1-075 GEN1
Solar/Wind Harmer
0.662
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
316305AF2-043 C
Solar/Wind Harmer
0.197
315816AE2-034 GEN
Solar/Wind Harmer
0.528
3152611GOSPORTB
Adder
0.738
3152621GOSPORTC
Adder
0.626
3152601GOSPORTA
Adder
0.578
3130156CHOWAN
Solar/Wind Harmer
-0.006
3130156CHOWAN
Solar/Wind Harmer
-0.006
3146486SUNBURY
Solar/Wind Harmer
-0.006
3146486SUNBURY
Solar/Wind Harmer
-0.006
315611Z1-036_GEN2
Solar/Wind Harmer
1.603
3151081ELIZAR1
Adder
5.276
3151091ELIZAR2
Adder
5.184
316321Z2-027
Solar/Wind Harmer
0.174
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.118
313526AB2-022
Solar/Wind Harmer
0.173
3146406KITTY HAWK
Solar/Wind Harmer
0.005
319010AE1-072 C
Solar/Wind Harmer
1.291
957871AF2-081 GEN
Solar/Wind Harmer
3.187
316233AE1-074 FULL
Solar/Wind Helper
0.327
944641AF1-129 GEN
50/50
130.338
3150781HOPHCF2
50/50
0.514
3150791HOPHCF3
50/50
0.514
3150761HOPPOLC
50/50
0.326
971213AH1-066 GEN
50/50
0.451
316240AF1-291 C
Solar/Wind Harmer
0.835
3144356SAPONY
Solar/Wind Harmer
0.418
970657AG2-426 GEN
Solar/Wind Harmer
3.732
970657AG2-426 GEN
Solar/Wind Harmer
0.78
316033AB2-134 GEN
Solar/Wind Harmer
3.578
315697AD1-025 GEN
Solar/Wind Harmer
2.244
316236AE1-162_GEN
Solar/Wind Harmer
0.233
316181AB2-040 GEN
Solar/Wind Harmer
1.066
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145796HORNRTN
Solar/Wind Harmer
-0.022
972185AH1-677 GEN
Adder
3.642
315742AE1-103 GEN
Solar/Wind Harmer
0.75
972187AH1-678 GEN
Adder
1.816
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.796
3145593CAROLNA
Solar/Wind Harmer
0.059
316426AA2-053 GEN
Solar/Wind Harmer
0.709
3145783HORNRTN
Solar/Wind Harmer
0.831
3145783HORNRTN
Solar/Wind Harmer
0.664
3145783HORNRTN
Solar/Wind Harmer
0.208
3145783HORNRTN
Solar/Wind Harmer
0.083
3145893MURPHYS
Solar/Wind Harmer
0.195
3145893MURPHYS
Solar/Wind Harmer
-0.013
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
970933AG2-581 GEN
Solar/Wind Harmer
6.3
316274AC1-208 GEN
Solar/Wind Harmer
0.714
316065AD1-022 GEN
Solar/Wind Harmer
3.296
316036AC1-147 C
Solar/Wind Harmer
0.176
3150991CHESPKB
Adder
0.607
3150991CHESPKB
Adder
0.592
3146376EDENTON
Solar/Wind Harmer
0.193
3146376EDENTON
Solar/Wind Harmer
0.193
316431W1029_GEN1
Solar/Wind Harmer
1.174
316433W1029_GEN2
Solar/Wind Harmer
1.174
3146626S HERTFORD
Solar/Wind Harmer
-0.006
3146626S HERTFORD
Solar/Wind Harmer
-0.006
3146516WINFALL
Solar/Wind Harmer
-0.006
3146516WINFALL
Solar/Wind Harmer
-0.006
3146516WINFALL
Solar/Wind Harmer
-0.006
316316AC1-027 C
Solar/Wind Harmer
0.198
3142956BIRDNECK
Solar/Wind Harmer
0.345
3146386ELIZ CT
Solar/Wind Harmer
-0.006
3150801HOPHCF4
50/50
0.748
971211AH1-065 GEN
50/50
0.902
315839AE2-212 C
Solar/Wind Harmer
0.693
970133AG2-095 GEN
Solar/Wind Harmer
1.604
315813AE1-149 C
Solar/Wind Harmer
8.895
970129AG2-093 GEN
Solar/Wind Harmer
7.195
970659AG2-427 GEN
Solar/Wind Harmer
1.185
316083AB2-161 GEN
Solar/Wind Harmer
1.993
315778AD1-151 GEN
Solar/Wind Harmer
10.156
970661AG2-428 GEN
Solar/Wind Harmer
2.144
965281AG1-393 GEN
Solar/Wind Harmer
1.286
961611AG1-000B GEN
Solar/Wind Harmer
2.004
316365GEN2_N
Solar/Wind Harmer
0.619
3151221GRAVEL6
Adder
5.513
3151171GRAVELC
Adder
1.061
966621AG1-532 GEN
Solar/Wind Harmer
0.165
3145336SMITFLD
Solar/Wind Harmer
-0.003
313506AB2-031 GEN
Solar/Wind Harmer
0.614
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.03
3145796HORNRTN
Solar/Wind Harmer
-0.008
3145273HOLLAND
Solar/Wind Harmer
-0.005
3156081AA2-088 GEN
Solar/Wind Harmer
2.296
3147043LAWRENC
Solar/Wind Harmer
-0.004
3130086AYDLETT
Solar/Wind Harmer
-0.025
3137176SLIGO L2192
Solar/Wind Harmer
-0.025
3146456SLIGO L269
Solar/Wind Harmer
0.753
316018AA1-139 ULT2
Solar/Wind Harmer
0.546
316017AA1-139 ULT1
Solar/Wind Harmer
0.516
316339AD2-160 GEN
Solar/Wind Harmer
0.43
316185AD1-033 GEN
Solar/Wind Harmer
0.671
3145506HICKORY
Solar/Wind Harmer
-0.025
3145506HICKORY
Solar/Wind Harmer
-0.015
3145506HICKORY
Solar/Wind Harmer
-0.004
3143526WINTERP
Solar/Wind Helper
1.113
3145893MURPHYS
Solar/Wind Harmer
0.049
3145893MURPHYS
Solar/Wind Harmer
-0.007
957521AF2-046 GEN
Solar/Wind Harmer
5.468
961681AG1-008 GEN
Solar/Wind Harmer
5.468
3146173TUNIS
Solar/Wind Harmer
-0.007
970917AG2-570 GEN
Solar/Wind Harmer
17.182
3146263WOODLND
Solar/Wind Harmer
-0.007
3144536CHRHLND
Solar/Wind Harmer
-0.001
316463AE2-346 GEN
Solar/Wind Harmer
0.11
316140AB2-099
Solar/Wind Harmer
0.046
962331AG1-082 GEN
Solar/Wind Harmer
0.853
315724AD1-057 GEN
Solar/Wind Harmer
0.389
3156021HOLLOMANSOL
Solar/Wind Harmer
0.906
316317KELFORD C
Solar/Wind Harmer
0.316
3145823KELFORD
Solar/Wind Harmer
-0.007
3146206CASHIE
Solar/Wind Harmer
-0.007
316210AC1-098 GEN
Solar/Wind Harmer
1.035
315737AD1-076 GEN
Solar/Wind Harmer
1.244
971157AH1-035 GEN
Solar/Wind Harmer
0.818
315614AA2-178 GEN
Solar/Wind Harmer
0.704
3144873MCLAUGH
Solar/Wind Harmer
0
3146376EDENTON
Solar/Wind Harmer
-0.006
316435W1029_GEN3
Solar/Wind Harmer
1.174
3146626S HERTFORD
Solar/Wind Harmer
-0.006
3146516WINFALL
Solar/Wind Harmer
-0.006
3151101ELIZAR3
Adder
5.343
316320Y1-086
Solar/Wind Harmer
0.376
3146456SLIGO L269
Solar/Wind Harmer
-0.006
971153AH1-033 GEN
Solar/Wind Harmer
0.778
316327AA2-057 GEN
Solar/Wind Harmer
0.644
3145963POPLR C
Solar/Wind Harmer
-0.006
316313AB2-026
Solar/Wind Helper
0.305
316258AE1-075 C
Solar/Wind Helper
0.274
316405AF2-144 C
Solar/Wind Helper
0.228
LAGNLTFEXP_LAGN->PJM
CLTF
1.798
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.316
TVALTFEXP_TVA->PJM
CLTF
0.892
CPLELTFEXP_CPLE->PJM
CLTF
3.052
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.003
NYPJM->LTFIMP_NY
CLTF
0.426
LGEELTFEXP_LGEE->PJM
CLTF
0.255
WECLTFEXP_WEC->PJM
CLTF
0.131
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.47
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.998
MECLTFEXP_MEC->PJM
CLTF
0.759
SIGELTFEXP_SIGE->PJM
CLTF
0.022

Details for 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P4-2: 21712_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 21712_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.66 %
Rating:812.0 MVA
Rating Type:C
MVA to Mitigate:914.78
MW Contribution:1.21
Bus #Bus NameTypeMW Contribution
944641AF1-129 GEN
50/50
172.228
3150781HOPHCF2
50/50
0.692
3150791HOPHCF3
50/50
0.692
3150761HOPPOLC
50/50
0.439
971213AH1-066 GEN
50/50
0.607
316240AF1-291 C
Solar/Wind Harmer
1.099
970657AG2-426 GEN
Solar/Wind Harmer
4.526
970657AG2-426 GEN
Solar/Wind Harmer
0.946
316033AB2-134 GEN
Solar/Wind Harmer
4.6
315697AD1-025 GEN
Solar/Wind Harmer
2.885
3144356SAPONY
Solar/Wind Harmer
0.47
316236AE1-162_GEN
Solar/Wind Harmer
0.266
316181AB2-040 GEN
Solar/Wind Harmer
1.126
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145796HORNRTN
Solar/Wind Harmer
-0.024
315742AE1-103 GEN
Solar/Wind Harmer
0.786
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.825
3145593CAROLNA
Solar/Wind Harmer
0.061
316426AA2-053 GEN
Solar/Wind Harmer
0.734
3145783HORNRTN
Solar/Wind Harmer
0.859
3145783HORNRTN
Solar/Wind Harmer
0.687
3145783HORNRTN
Solar/Wind Harmer
0.215
3145783HORNRTN
Solar/Wind Harmer
0.086
3145893MURPHYS
Solar/Wind Harmer
0.201
3145893MURPHYS
Solar/Wind Harmer
-0.013
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
316274AC1-208 GEN
Solar/Wind Harmer
0.728
316065AD1-022 GEN
Solar/Wind Harmer
3.341
316036AC1-147 C
Solar/Wind Harmer
0.178
3150991CHESPKB
Adder
0.613
3150991CHESPKB
Adder
0.599
3146376EDENTON
Solar/Wind Harmer
0.194
3146376EDENTON
Solar/Wind Harmer
0.194
316431W1029_GEN1
Solar/Wind Harmer
1.178
316433W1029_GEN2
Solar/Wind Harmer
1.178
3146626S HERTFORD
Solar/Wind Harmer
-0.006
3146626S HERTFORD
Solar/Wind Harmer
-0.006
3146516WINFALL
Solar/Wind Harmer
-0.006
3146516WINFALL
Solar/Wind Harmer
-0.006
3146516WINFALL
Solar/Wind Harmer
-0.006
316316AC1-027 C
Solar/Wind Harmer
0.198
3142956BIRDNECK
Solar/Wind Harmer
0.345
3146386ELIZ CT
Solar/Wind Harmer
-0.006
3130086AYDLETT
Solar/Wind Harmer
-0.025
3146456SLIGO L269
Solar/Wind Harmer
0.748
3137176SLIGO L2192
Solar/Wind Harmer
-0.025
316018AA1-139 ULT2
Solar/Wind Harmer
0.542
316017AA1-139 ULT1
Solar/Wind Harmer
0.512
3143526WINTERP
Solar/Wind Helper
0.642
966871AG1-558 GEN
Solar/Wind Helper
0.164
3150801HOPHCF4
50/50
1.007
971211AH1-065 GEN
50/50
1.214
315839AE2-212 C
Solar/Wind Harmer
0.899
970133AG2-095 GEN
Solar/Wind Harmer
2.159
315813AE1-149 C
Solar/Wind Harmer
11.138
970129AG2-093 GEN
Solar/Wind Harmer
9.507
970659AG2-427 GEN
Solar/Wind Harmer
1.452
315778AD1-151 GEN
Solar/Wind Harmer
13.204
316083AB2-161 GEN
Solar/Wind Harmer
2.43
965281AG1-393 GEN
Solar/Wind Harmer
1.788
970661AG2-428 GEN
Solar/Wind Harmer
2.575
961611AG1-000B GEN
Solar/Wind Harmer
2.486
3151221GRAVEL6
Adder
6.634
3151171GRAVELC
Adder
1.276
316365GEN2_N
Solar/Wind Harmer
0.672
3145336SMITFLD
Solar/Wind Harmer
-0.003
966621AG1-532 GEN
Solar/Wind Harmer
0.177
313506AB2-031 GEN
Solar/Wind Harmer
0.649
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.008
3145273HOLLAND
Solar/Wind Harmer
-0.006
3147043LAWRENC
Solar/Wind Harmer
-0.004
3156081AA2-088 GEN
Solar/Wind Harmer
2.389
3145893MURPHYS
Solar/Wind Harmer
0.05
3145893MURPHYS
Solar/Wind Harmer
-0.007
3144536CHRHLND
Solar/Wind Harmer
-0.001
957521AF2-046 GEN
Solar/Wind Harmer
5.65
961681AG1-008 GEN
Solar/Wind Harmer
5.65
3146173TUNIS
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
316463AE2-346 GEN
Solar/Wind Harmer
0.113
316140AB2-099
Solar/Wind Harmer
0.047
970603AG2-384 GEN
50/50
7.264
315779AE2-040
50/50
1.674
3143316POE
Solar/Wind Harmer
-0.088
316132AB2-190 GEN1
Solar/Wind Harmer
1.684
316369SG1_INVT
Solar/Wind Harmer
2.549
316315AB2-025 C
Solar/Wind Harmer
0.364
315814AE2-033 C
Solar/Wind Harmer
12.38
315833AF1-017_GEN
Solar/Wind Harmer
1.99
316349AD2-085 GEN
Solar/Wind Harmer
0.932
316311AC2-079 GEN
Solar/Wind Harmer
5.256
972265AH1-717 GEN
Adder
7.085
3151201GRAVEL4
Adder
6.641
3151191GRAVEL3
Adder
6.557
3151211GRAVEL5
Adder
6.557
971445AH1-216 GEN
Solar/Wind Harmer
5.548
946281AF1-292 GEN
Solar/Wind Harmer
0.195
316087AB2-174 GEN
Solar/Wind Harmer
1.18
315652AC1-086 GEN
Solar/Wind Harmer
9.225
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.003
3137643SOCKMAN
Solar/Wind Harmer
-0.03
315835AF2-110_GEN
Solar/Wind Harmer
0.957
965291AG1-394 GEN
Solar/Wind Harmer
0.652
3146043SEABORD
Solar/Wind Harmer
-0.007
315607AA1-063A GEN
Solar/Wind Harmer
0.741
316318V4-068
Solar/Wind Harmer
0.18
3145893MURPHYS
Solar/Wind Harmer
-0.019
3145893MURPHYS
Solar/Wind Harmer
-0.007
3145513AHOSKIE
Solar/Wind Harmer
0.061
961941AG1-037 GEN
Solar/Wind Harmer
0.053
3145513AHOSKIE
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.014
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
3146033SCOT NK
Solar/Wind Harmer
-0.027
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
2.94
315732AD1-074 GEN1
Solar/Wind Harmer
1.338
315733AD1-074 GEN2
Solar/Wind Harmer
1.338
315735AD1-075 GEN1
Solar/Wind Harmer
0.669
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
316305AF2-043 C
Solar/Wind Harmer
0.199
3152611GOSPORTB
Adder
0.746
3152621GOSPORTC
Adder
0.633
3152601GOSPORTA
Adder
0.584
315816AE2-034 GEN
Solar/Wind Harmer
0.533
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.611
3151081ELIZAR1
Adder
5.305
3151091ELIZAR2
Adder
5.213
316321Z2-027
Solar/Wind Harmer
0.174
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.118
313526AB2-022
Solar/Wind Harmer
0.173
3146406KITTY HAWK
Solar/Wind Harmer
0.005
319010AE1-072 C
Solar/Wind Harmer
1.283
957871AF2-081 GEN
Solar/Wind Harmer
3.163
316233AE1-074 FULL
Solar/Wind Helper
0.189
3150771HOPHCF1
50/50
0.692
970129AG2-093 GEN
Solar/Wind Harmer
3.851
316458AB2-190 GEN2
Solar/Wind Harmer
1.684
970659AG2-427 GEN
Solar/Wind Harmer
8.193
971069AG2-661 GEN
Solar/Wind Harmer
2.412
316381AD1-082 GEN
Solar/Wind Harmer
1.373
970661AG2-428 GEN
Solar/Wind Harmer
14.53
971647AH1-324 GEN
Solar/Wind Harmer
6.521
315671AE2-027_GEN
Solar/Wind Harmer
9.228
961611AG1-000B GEN
Solar/Wind Harmer
5.826
3151171GRAVELC
Adder
0.971
316023GEN1_S
Solar/Wind Harmer
0.672
3145336SMITFLD
Solar/Wind Harmer
-0.035
960081AF2-299 GEN
Solar/Wind Harmer
0.982
316011AB1-132 GEN
Solar/Wind Harmer
1.716
962571AG1-106 GEN
Solar/Wind Harmer
1.179
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.008
971795AH1-408 GEN
Solar/Wind Harmer
5.894
316093AE2-104_GEN
Solar/Wind Harmer
2.226
3147043LAWRENC
Adder
0.601
316190AA2-174 GEN
Solar/Wind Harmer
0.089
3145783HORNRTN
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
-0.029
3145893MURPHYS
Solar/Wind Harmer
0.214
3146173TUNIS
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
316072AD1-144
Solar/Wind Harmer
0.14
315722AD1-056 GEN
Solar/Wind Harmer
0.724
3145823KELFORD
Solar/Wind Harmer
-0.007
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.68
316212AC1-099_GEN
Solar/Wind Harmer
0.585
316246AF1-032 C
Solar/Wind Harmer
0.133
316375AC2-012 GEN
Solar/Wind Harmer
2.277
3150981CHESPKA
Adder
0.731
3145663CRESWEL
Solar/Wind Harmer
-0.018
971163AH1-040 GEN
Solar/Wind Harmer
6.17
3130156CHOWAN
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
1.611
3146516WINFALL
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.006
3145963POPLR C
Solar/Wind Harmer
-0.006
316174AB2-169 GEN
Solar/Wind Harmer
0.981
3146456SLIGO L269
Solar/Wind Harmer
-0.006
3142543TWELFTH
Solar/Wind Helper
0.038
3143226MDLTHAN
Solar/Wind Helper
0.156
3143526WINTERP
Solar/Wind Helper
0.642
962331AG1-082 GEN
Solar/Wind Harmer
0.875
315724AD1-057 GEN
Solar/Wind Harmer
0.398
3156021HOLLOMANSOL
Solar/Wind Harmer
0.925
316317KELFORD C
Solar/Wind Harmer
0.323
3145823KELFORD
Solar/Wind Harmer
-0.007
3146206CASHIE
Solar/Wind Harmer
-0.007
316210AC1-098 GEN
Solar/Wind Harmer
1.054
315737AD1-076 GEN
Solar/Wind Harmer
1.258
971157AH1-035 GEN
Solar/Wind Harmer
0.826
3144873MCLAUGH
Solar/Wind Harmer
0
315614AA2-178 GEN
Solar/Wind Harmer
0.71
3146376EDENTON
Solar/Wind Harmer
-0.007
316435W1029_GEN3
Solar/Wind Harmer
1.178
3151101ELIZAR3
Adder
5.373
3146626S HERTFORD
Solar/Wind Harmer
-0.006
3146516WINFALL
Solar/Wind Harmer
-0.006
316327AA2-057 GEN
Solar/Wind Harmer
0.649
316320Y1-086
Solar/Wind Harmer
0.375
3145963POPLR C
Solar/Wind Harmer
-0.006
3146456SLIGO L269
Solar/Wind Harmer
-0.006
971153AH1-033 GEN
Solar/Wind Harmer
0.772
316473AC1-191 GEN
Solar/Wind Helper
0.741
LAGNLTFEXP_LAGN->PJM
CLTF
1.583
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.669
TVALTFEXP_TVA->PJM
CLTF
0.786
CPLELTFEXP_CPLE->PJM
CLTF
2.766
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.843
NYPJM->LTFIMP_NY
CLTF
0.415
LGEELTFEXP_LGEE->PJM
CLTF
0.215
WECLTFEXP_WEC->PJM
CLTF
0.11
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.689
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.63
MECLTFEXP_MEC->PJM
CLTF
0.648
SIGELTFEXP_SIGE->PJM
CLTF
0.019

Details for 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 208-259_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6CHESTF B-6VARINA 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 208-259_SRT-S
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:100.89 %
Rating:1204.0 MVA
Rating Type:C
MVA to Mitigate:1214.75
MW Contribution:1.27
Bus #Bus NameTypeMW Contribution
970603AG2-384 GEN
50/50
6.703
315779AE2-040
50/50
1.679
3143316POE
Solar/Wind Harmer
-0.085
316132AB2-190 GEN1
Solar/Wind Harmer
1.784
316369SG1_INVT
Solar/Wind Harmer
2.73
316315AB2-025 C
Solar/Wind Harmer
0.365
315814AE2-033 C
Solar/Wind Harmer
12.431
972265AH1-717 GEN
Adder
7.812
3151201GRAVEL4
Adder
7.323
3151191GRAVEL3
Adder
7.23
3151211GRAVEL5
Adder
7.23
315833AF1-017_GEN
Solar/Wind Harmer
2.103
316349AD2-085 GEN
Solar/Wind Harmer
0.985
316311AC2-079 GEN
Solar/Wind Harmer
5.558
971445AH1-216 GEN
Solar/Wind Harmer
6.169
946281AF1-292 GEN
Solar/Wind Harmer
0.204
316087AB2-174 GEN
Solar/Wind Harmer
1.242
315652AC1-086 GEN
Solar/Wind Harmer
9.71
315835AF2-110_GEN
Solar/Wind Harmer
1.056
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.003
3137643SOCKMAN
Solar/Wind Harmer
-0.032
965291AG1-394 GEN
Solar/Wind Harmer
0.707
3146043SEABORD
Solar/Wind Harmer
-0.008
315607AA1-063A GEN
Solar/Wind Harmer
0.798
316318V4-068
Solar/Wind Harmer
0.195
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145513AHOSKIE
Solar/Wind Harmer
0.066
961941AG1-037 GEN
Solar/Wind Harmer
0.057
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3152611GOSPORTB
Adder
0.85
3152621GOSPORTC
Adder
0.721
3152601GOSPORTA
Adder
0.665
316305AF2-043 C
Solar/Wind Harmer
0.225
3151081ELIZAR1
Adder
6.048
3151091ELIZAR2
Adder
5.943
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
3.232
3146033SCOT NK
Solar/Wind Harmer
-0.029
315611Z1-036_GEN2
Solar/Wind Harmer
1.809
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315816AE2-034 GEN
Solar/Wind Harmer
0.592
315732AD1-074 GEN1
Solar/Wind Harmer
1.479
315733AD1-074 GEN2
Solar/Wind Harmer
1.479
315735AD1-075 GEN1
Solar/Wind Harmer
0.74
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
316321Z2-027
Solar/Wind Harmer
0.196
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.134
313526AB2-022
Solar/Wind Harmer
0.196
3146406KITTY HAWK
Solar/Wind Harmer
0.006
319010AE1-072 C
Solar/Wind Harmer
1.46
957871AF2-081 GEN
Solar/Wind Harmer
3.604
941031AE2-094 GEN
Solar/Wind Harmer
12.896
944011AF1-069 GEN
Solar/Wind Harmer
4.041
316319Z2-044 C
Solar/Wind Harmer
0.373
970673AG2-436 GEN
Solar/Wind Harmer
14.16
970673AG2-436 GEN
Solar/Wind Harmer
7.17
316005AA1-067
Solar/Wind Harmer
0.135
3145746EVERETS
Solar/Wind Harmer
-0.026
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
970181AG2-120 GEN
Solar/Wind Harmer
0.878
957861AF2-080 GEN
Solar/Wind Harmer
2.915
316420AA1-050 GEN
Solar/Wind Harmer
0.759
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
970831AG2-522 GEN
Solar/Wind Harmer
3.291
971967AH1-528 GEN
Solar/Wind Harmer
12.369
970085AG2-068 GEN
Solar/Wind Harmer
3.953
970581AG2-369 GEN
Solar/Wind Harmer
3.399
944641AF1-129 GEN
50/50
158.905
3150781HOPHCF2
50/50
0.727
3150791HOPHCF3
50/50
0.727
3150761HOPPOLC
50/50
0.461
971213AH1-066 GEN
50/50
0.638
316240AF1-291 C
Solar/Wind Harmer
1.017
3150771HOPHCF1
50/50
0.727
970129AG2-093 GEN
Solar/Wind Harmer
4.076
316458AB2-190 GEN2
Solar/Wind Harmer
1.784
971069AG2-661 GEN
Solar/Wind Harmer
2.57
970659AG2-427 GEN
Solar/Wind Harmer
8.328
316381AD1-082 GEN
Solar/Wind Harmer
1.399
315671AE2-027_GEN
Solar/Wind Harmer
10.881
971647AH1-324 GEN
Solar/Wind Harmer
7.034
970661AG2-428 GEN
Solar/Wind Harmer
14.929
961611AG1-000B GEN
Solar/Wind Harmer
6.338
3151171GRAVELC
Adder
1.07
316023GEN1_S
Solar/Wind Harmer
0.693
944631AF1-128 GEN
Adder
42.519
3145336SMITFLD
Solar/Wind Harmer
-0.039
960081AF2-299 GEN
Solar/Wind Harmer
1.027
316011AB1-132 GEN
Solar/Wind Harmer
1.806
962571AG1-106 GEN
Solar/Wind Harmer
1.241
316093AE2-104_GEN
Solar/Wind Harmer
2.456
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.008
971795AH1-408 GEN
Solar/Wind Harmer
6.247
3147043LAWRENC
Adder
0.641
316072AD1-144
Solar/Wind Harmer
0.16
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
0.232
316190AA2-174 GEN
Solar/Wind Harmer
0.096
3145783HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
3146263WOODLND
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
316375AC2-012 GEN
Solar/Wind Harmer
2.593
3150981CHESPKA
Adder
0.833
316246AF1-032 C
Solar/Wind Harmer
0.151
3145823KELFORD
Solar/Wind Harmer
-0.007
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.847
315722AD1-056 GEN
Solar/Wind Harmer
0.772
3146516WINFALL
Solar/Wind Harmer
-0.024
3150801HOPHCF4
50/50
1.058
971211AH1-065 GEN
50/50
1.275
315839AE2-212 C
Solar/Wind Harmer
0.847
970133AG2-095 GEN
Solar/Wind Harmer
2.267
315813AE1-149 C
Solar/Wind Harmer
11.193
970129AG2-093 GEN
Solar/Wind Harmer
10.063
315778AD1-151 GEN
Solar/Wind Harmer
14.073
965281AG1-393 GEN
Solar/Wind Harmer
1.997
970659AG2-427 GEN
Solar/Wind Harmer
1.476
316083AB2-161 GEN
Solar/Wind Harmer
2.477
970661AG2-428 GEN
Solar/Wind Harmer
2.646
961611AG1-000B GEN
Solar/Wind Harmer
2.704
3151221GRAVEL6
Adder
7.315
3151171GRAVELC
Adder
1.407
316365GEN2_N
Solar/Wind Harmer
0.693
3145336SMITFLD
Solar/Wind Harmer
-0.004
966621AG1-532 GEN
Solar/Wind Harmer
0.185
313506AB2-031 GEN
Solar/Wind Harmer
0.685
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.033
3145796HORNRTN
Solar/Wind Harmer
-0.008
3145273HOLLAND
Solar/Wind Harmer
-0.006
3144536CHRHLND
Solar/Wind Harmer
-0.001
3156081AA2-088 GEN
Solar/Wind Harmer
2.594
3147043LAWRENC
Solar/Wind Harmer
-0.005
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
957521AF2-046 GEN
Solar/Wind Harmer
6.136
961681AG1-008 GEN
Solar/Wind Harmer
6.136
3142946ENON
Solar/Wind Harmer
-0.003
3146173TUNIS
Solar/Wind Harmer
-0.008
3146263WOODLND
Solar/Wind Harmer
-0.008
316463AE2-346 GEN
Solar/Wind Harmer
0.123
316140AB2-099
Solar/Wind Harmer
0.051
962331AG1-082 GEN
Solar/Wind Harmer
0.952
3144873MCLAUGH
Solar/Wind Harmer
0
3156021HOLLOMANSOL
Solar/Wind Harmer
1.009
316317KELFORD C
Solar/Wind Harmer
0.351
3145823KELFORD
Solar/Wind Harmer
-0.007
3151101ELIZAR3
Adder
6.126
3146206CASHIE
Solar/Wind Harmer
-0.007
315724AD1-057 GEN
Solar/Wind Harmer
0.425
316435W1029_GEN3
Solar/Wind Harmer
1.33
3146516WINFALL
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
315614AA2-178 GEN
Solar/Wind Harmer
0.789
315737AD1-076 GEN
Solar/Wind Harmer
1.39
971157AH1-035 GEN
Solar/Wind Harmer
0.914
316320Y1-086
Solar/Wind Harmer
0.426
316210AC1-098 GEN
Solar/Wind Harmer
1.138
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.879
3145963POPLR C
Solar/Wind Harmer
-0.007
316327AA2-057 GEN
Solar/Wind Harmer
0.701
944581AF1-123 GEN
Solar/Wind Harmer
31.333
944601AF1-125 GEN
Solar/Wind Harmer
30.844
3145933PARMELE
Solar/Wind Harmer
-0.007
966801AG1-551 GEN
Solar/Wind Harmer
0.85
316033AB2-134 GEN
Solar/Wind Harmer
4.927
315697AD1-025 GEN
Solar/Wind Harmer
3.09
970657AG2-426 GEN
Solar/Wind Harmer
4.626
970657AG2-426 GEN
Solar/Wind Harmer
0.967
3144356SAPONY
Solar/Wind Harmer
0.472
316236AE1-162_GEN
Solar/Wind Harmer
0.296
316181AB2-040 GEN
Solar/Wind Harmer
1.19
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145796HORNRTN
Solar/Wind Harmer
-0.025
315742AE1-103 GEN
Solar/Wind Harmer
0.861
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.883
3145593CAROLNA
Solar/Wind Harmer
0.065
3145893MURPHYS
Solar/Wind Harmer
0.219
3145893MURPHYS
Solar/Wind Harmer
-0.014
316426AA2-053 GEN
Solar/Wind Harmer
0.788
3145783HORNRTN
Solar/Wind Harmer
0.921
3145783HORNRTN
Solar/Wind Harmer
0.737
3145783HORNRTN
Solar/Wind Harmer
0.23
3145783HORNRTN
Solar/Wind Harmer
0.092
3142946ENON
Solar/Wind Harmer
-0.001
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316036AC1-147 C
Solar/Wind Harmer
0.202
3150991CHESPKB
Adder
0.698
3150991CHESPKB
Adder
0.682
316065AD1-022 GEN
Solar/Wind Harmer
3.68
316316AC1-027 C
Solar/Wind Harmer
0.226
316431W1029_GEN1
Solar/Wind Harmer
1.33
316433W1029_GEN2
Solar/Wind Harmer
1.33
3142956BIRDNECK
Solar/Wind Harmer
0.393
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
0.217
3146376EDENTON
Solar/Wind Harmer
0.217
3146386ELIZ CT
Solar/Wind Harmer
-0.007
316274AC1-208 GEN
Solar/Wind Harmer
0.784
3130086AYDLETT
Solar/Wind Harmer
-0.029
3137176SLIGO L2192
Solar/Wind Harmer
-0.029
3146456SLIGO L269
Solar/Wind Harmer
0.852
316018AA1-139 ULT2
Solar/Wind Harmer
0.617
316017AA1-139 ULT1
Solar/Wind Harmer
0.583
316339AD2-160 GEN
Solar/Wind Harmer
0.486
316185AD1-033 GEN
Solar/Wind Harmer
0.759
3145506HICKORY
Solar/Wind Harmer
-0.029
3145506HICKORY
Solar/Wind Harmer
-0.017
3145506HICKORY
Solar/Wind Harmer
-0.004
3145933PARMELE
Solar/Wind Harmer
-0.014
3145933PARMELE
Solar/Wind Harmer
-0.007
972185AH1-677 GEN
Adder
3.332
3145493TOT1
Solar/Wind Harmer
0.103
3145453TOT5
Solar/Wind Harmer
0.062
3145603CNETO
Solar/Wind Harmer
0.041
961601AG1-000A GEN
Solar/Wind Harmer
2.599
972187AH1-678 GEN
Adder
1.668
316263AC1-034 GEN
Solar/Wind Harmer
3.083
966871AG1-558 GEN
Solar/Wind Helper
0.264
316468AD1-105 GEN
Solar/Wind Helper
0.799
3146516WINFALL
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
1.809
3130156CHOWAN
Solar/Wind Harmer
-0.007
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.858
316212AC1-099_GEN
Solar/Wind Harmer
0.632
3146456SLIGO L269
Solar/Wind Harmer
-0.007
316388AE2-253 GEN
Solar/Wind Harmer
0.486
3145963POPLR C
Solar/Wind Harmer
-0.007
316174AB2-169 GEN
Solar/Wind Harmer
1.078
939411AE1-173 GEN
Solar/Wind Harmer
34.71
940641AE2-051 GEN
Solar/Wind Harmer
6.466
944591AF1-124 GEN
Solar/Wind Harmer
31.446
3146293MARTNCO
Solar/Wind Harmer
0.042
3146233WITAKRS
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
316494AC1-189 GEN
Solar/Wind Harmer
0.717
961671AG1-007 GEN
Solar/Wind Harmer
0.084
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.197
316359AB2-059 GEN
Solar/Wind Harmer
0.887
316049AB1-081 GEN
Solar/Wind Harmer
0.71
3142053HEARTS
Solar/Wind Harmer
0.077
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316129AC1-054 GEN
Solar/Wind Harmer
0.565
970919AG2-571 GEN
Solar/Wind Harmer
2.009
970087AG2-069 GEN
Solar/Wind Harmer
5.929
971065AG2-659 GEN
Solar/Wind Harmer
3.161
3146233WITAKRS
Solar/Wind Harmer
0.141
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.004
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.632
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3144216WINCHST
Adder
0.213
970917AG2-570 GEN
Solar/Wind Harmer
15.874
316473AC1-191 GEN
Solar/Wind Helper
1.195
LAGNLTFEXP_LAGN->PJM
CLTF
1.785
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.34
TVALTFEXP_TVA->PJM
CLTF
0.887
CPLELTFEXP_CPLE->PJM
CLTF
3.081
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.877
NYPJM->LTFIMP_NY
CLTF
0.472
LGEELTFEXP_LGEE->PJM
CLTF
0.247
WECLTFEXP_WEC->PJM
CLTF
0.126
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.235
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.973
MECLTFEXP_MEC->PJM
CLTF
0.738
SIGELTFEXP_SIGE->PJM
CLTF
0.021

Details for 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.04 %
Rating:1204.0 MVA
Rating Type:C
MVA to Mitigate:1276.77
MW Contribution:2.82
Bus #Bus NameTypeMW Contribution
3150781HOPHCF2
50/50
1.606
3150791HOPHCF3
50/50
1.606
3150761HOPPOLC
50/50
1.018
971213AH1-066 GEN
50/50
1.408
316033AB2-134 GEN
Solar/Wind Harmer
9.833
315697AD1-025 GEN
Solar/Wind Harmer
6.167
944641AF1-129 GEN
Adder
75.309
316240AF1-291 C
Solar/Wind Harmer
0.525
316236AE1-162_GEN
Solar/Wind Harmer
0.452
970657AG2-426 GEN
Solar/Wind Harmer
4.677
970657AG2-426 GEN
Solar/Wind Harmer
0.978
3144356SAPONY
Solar/Wind Harmer
0.355
316036AC1-147 C
Solar/Wind Harmer
0.228
3150991CHESPKB
Adder
0.788
3150991CHESPKB
Adder
0.769
315742AE1-103 GEN
Solar/Wind Harmer
0.867
316316AC1-027 C
Solar/Wind Harmer
0.246
3142956BIRDNECK
Solar/Wind Harmer
0.427
316431W1029_GEN1
Solar/Wind Harmer
1.378
316433W1029_GEN2
Solar/Wind Harmer
1.378
316132AB2-190 GEN1
Solar/Wind Harmer
3.771
316369SG1_INVT
Solar/Wind Harmer
5.448
972265AH1-717 GEN
Adder
13.177
3151201GRAVEL4
Adder
12.352
3151191GRAVEL3
Adder
12.196
3151211GRAVEL5
Adder
12.196
971445AH1-216 GEN
Solar/Wind Harmer
9.504
3143316POE
Solar/Wind Harmer
-0.058
315833AF1-017_GEN
Solar/Wind Harmer
2.15
316349AD2-085 GEN
Solar/Wind Harmer
1.007
316311AC2-079 GEN
Solar/Wind Harmer
5.684
316315AB2-025 C
Solar/Wind Harmer
0.275
315814AE2-033 C
Solar/Wind Harmer
9.394
315835AF2-110_GEN
Solar/Wind Harmer
1.094
3152611GOSPORTB
Adder
0.958
3152621GOSPORTC
Adder
0.813
3152601GOSPORTA
Adder
0.75
3150771HOPHCF1
50/50
1.606
970129AG2-093 GEN
Solar/Wind Harmer
8.655
316458AB2-190 GEN2
Solar/Wind Harmer
3.771
971069AG2-661 GEN
Solar/Wind Harmer
5.265
971647AH1-324 GEN
Solar/Wind Harmer
13.507
961611AG1-000B GEN
Solar/Wind Harmer
11.592
3151171GRAVELC
Adder
1.805
970659AG2-427 GEN
Solar/Wind Harmer
8.405
316381AD1-082 GEN
Solar/Wind Harmer
1.413
3145336SMITFLD
Solar/Wind Harmer
-0.06
970661AG2-428 GEN
Solar/Wind Harmer
15.121
316072AD1-144
Solar/Wind Harmer
0.183
316093AE2-104_GEN
Solar/Wind Harmer
2.545
316375AC2-012 GEN
Solar/Wind Harmer
2.926
3150981CHESPKA
Adder
0.94
316023GEN1_S
Solar/Wind Harmer
0.569
316246AF1-032 C
Solar/Wind Harmer
0.159
960081AF2-299 GEN
Solar/Wind Harmer
0.875
3146516WINFALL
Solar/Wind Harmer
-0.024
3146516WINFALL
Solar/Wind Harmer
-0.008
316011AB1-132 GEN
Solar/Wind Harmer
1.584
962571AG1-106 GEN
Solar/Wind Harmer
1.088
3145893MURPHYS
Solar/Wind Harmer
-0.03
3145893MURPHYS
Solar/Wind Harmer
0.224
3146456SLIGO L269
Solar/Wind Harmer
-0.008
316388AE2-253 GEN
Solar/Wind Harmer
0.509
315800Z1-036_GEN1
Solar/Wind Harmer
1.854
3130156CHOWAN
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.024
3145796HORNRTN
Solar/Wind Harmer
-0.007
939411AE1-173 GEN
Solar/Wind Harmer
36.811
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.89
971795AH1-408 GEN
Solar/Wind Harmer
5.452
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.813
3145683EARLEYS
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
316190AA2-174 GEN
Solar/Wind Harmer
0.088
3145783HORNRTN
Solar/Wind Harmer
-0.007
970919AG2-571 GEN
Solar/Wind Harmer
2.248
3145823KELFORD
Solar/Wind Harmer
-0.007
970087AG2-069 GEN
Solar/Wind Harmer
6.629
3147043LAWRENC
Adder
0.567
3145963POPLR C
Solar/Wind Harmer
-0.007
316174AB2-169 GEN
Solar/Wind Harmer
1.06
944591AF1-124 GEN
Solar/Wind Harmer
31.206
316212AC1-099_GEN
Solar/Wind Harmer
0.596
315722AD1-056 GEN
Solar/Wind Harmer
0.707
3146293MARTNCO
Solar/Wind Harmer
0.041
3145746EVERETS
Solar/Wind Harmer
-0.006
3151081ELIZAR1
Adder
6.728
3151091ELIZAR2
Adder
6.611
316305AF2-043 C
Solar/Wind Harmer
0.237
946281AF1-292 GEN
Solar/Wind Harmer
0.174
941031AE2-094 GEN
Solar/Wind Harmer
14.564
944011AF1-069 GEN
Solar/Wind Harmer
4.563
3146486SUNBURY
Solar/Wind Harmer
-0.008
3146486SUNBURY
Solar/Wind Harmer
-0.008
965291AG1-394 GEN
Solar/Wind Harmer
0.683
970673AG2-436 GEN
Solar/Wind Harmer
15.957
970673AG2-436 GEN
Solar/Wind Harmer
8.08
316087AB2-174 GEN
Solar/Wind Harmer
1.082
315652AC1-086 GEN
Solar/Wind Harmer
8.519
316321Z2-027
Solar/Wind Harmer
0.204
3145176PASQUOTANK
Solar/Wind Harmer
-0.005
3146396TANGLEW
Solar/Wind Harmer
0.139
313526AB2-022
Solar/Wind Harmer
0.204
316318V4-068
Solar/Wind Harmer
0.188
3145893MURPHYS
Solar/Wind Harmer
-0.02
3145893MURPHYS
Solar/Wind Harmer
-0.008
319010AE1-072 C
Solar/Wind Harmer
1.526
3146406KITTY HAWK
Solar/Wind Harmer
0.006
957871AF2-081 GEN
Solar/Wind Harmer
3.771
315611Z1-036_GEN2
Solar/Wind Harmer
1.854
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
3146043SEABORD
Solar/Wind Harmer
-0.007
971967AH1-528 GEN
Solar/Wind Harmer
13.912
315607AA1-063A GEN
Solar/Wind Harmer
0.747
3145796HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.003
315816AE2-034 GEN
Solar/Wind Harmer
0.595
3137643SOCKMAN
Solar/Wind Harmer
-0.029
3145513AHOSKIE
Solar/Wind Harmer
0.064
961941AG1-037 GEN
Solar/Wind Harmer
0.055
3145513AHOSKIE
Solar/Wind Harmer
-0.007
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315732AD1-074 GEN1
Solar/Wind Harmer
1.468
315733AD1-074 GEN2
Solar/Wind Harmer
1.468
315735AD1-075 GEN1
Solar/Wind Harmer
0.734
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
3.173
3145683EARLEYS
Solar/Wind Harmer
-0.014
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
970085AG2-068 GEN
Solar/Wind Harmer
4.419
970581AG2-369 GEN
Solar/Wind Harmer
3.801
3146033SCOT NK
Solar/Wind Harmer
-0.028
316005AA1-067
Solar/Wind Harmer
0.132
3145746EVERETS
Solar/Wind Harmer
-0.026
3145746EVERETS
Solar/Wind Harmer
-0.006
3145746EVERETS
Solar/Wind Harmer
-0.006
3145746EVERETS
Solar/Wind Harmer
-0.006
970181AG2-120 GEN
Solar/Wind Harmer
0.855
957861AF2-080 GEN
Solar/Wind Harmer
2.812
316319Z2-044 C
Solar/Wind Harmer
0.353
316420AA1-050 GEN
Solar/Wind Harmer
0.729
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
970831AG2-522 GEN
Solar/Wind Harmer
3.173
3143873LANEXA
Solar/Wind Helper
0.088
316059AD1-063 C
Solar/Wind Helper
0.133
316233AE1-074 FULL
Solar/Wind Helper
0.201
3141813NORNECK
Solar/Wind Helper
0.126
316312AB1-027
Solar/Wind Helper
0.233
316223AC1-118
Solar/Wind Helper
0.179
315662AE1-191 GEN
Solar/Wind Helper
0.622
315666AE1-190 GEN
Solar/Wind Helper
0.156
3141783LANCAST
Solar/Wind Helper
0.067
3141783LANCAST
Solar/Wind Helper
0.045
3150801HOPHCF4
50/50
2.336
971211AH1-065 GEN
50/50
2.817
3151161SURRY 1
50/50
6.519
970133AG2-095 GEN
Solar/Wind Harmer
5.007
970129AG2-093 GEN
Solar/Wind Harmer
21.368
315778AD1-151 GEN
Solar/Wind Harmer
28.825
961611AG1-000B GEN
Solar/Wind Harmer
4.946
3151221GRAVEL6
Adder
12.338
3151171GRAVELC
Adder
2.374
315813AE1-149 C
Solar/Wind Harmer
11.253
970659AG2-427 GEN
Solar/Wind Harmer
1.49
316083AB2-161 GEN
Solar/Wind Harmer
2.502
315839AE2-212 C
Solar/Wind Harmer
0.452
3145336SMITFLD
Solar/Wind Harmer
-0.006
970661AG2-428 GEN
Solar/Wind Harmer
2.68
3144536CHRHLND
Solar/Wind Harmer
-0.002
3144873MCLAUGH
Solar/Wind Harmer
0
3145273HOLLAND
Solar/Wind Harmer
-0.006
316365GEN2_N
Solar/Wind Harmer
0.569
3151101ELIZAR3
Adder
6.814
965281AG1-393 GEN
Solar/Wind Harmer
1.006
966621AG1-532 GEN
Solar/Wind Harmer
0.158
3156081AA2-088 GEN
Solar/Wind Harmer
2.515
316435W1029_GEN3
Solar/Wind Harmer
1.378
3146516WINFALL
Solar/Wind Harmer
-0.008
316320Y1-086
Solar/Wind Harmer
0.443
3145893MURPHYS
Solar/Wind Harmer
0.053
3145893MURPHYS
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146456SLIGO L269
Solar/Wind Harmer
-0.008
971153AH1-033 GEN
Solar/Wind Harmer
0.919
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
957521AF2-046 GEN
Solar/Wind Harmer
5.91
961681AG1-008 GEN
Solar/Wind Harmer
5.91
313506AB2-031 GEN
Solar/Wind Harmer
0.603
3146376EDENTON
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.029
3145796HORNRTN
Solar/Wind Harmer
-0.007
315614AA2-178 GEN
Solar/Wind Harmer
0.793
316463AE2-346 GEN
Solar/Wind Harmer
0.118
316140AB2-099
Solar/Wind Harmer
0.049
962331AG1-082 GEN
Solar/Wind Harmer
0.914
971157AH1-035 GEN
Solar/Wind Harmer
0.909
315737AD1-076 GEN
Solar/Wind Harmer
1.38
3146206CASHIE
Solar/Wind Harmer
-0.007
3156021HOLLOMANSOL
Solar/Wind Harmer
0.976
3146263WOODLND
Solar/Wind Harmer
-0.007
970917AG2-570 GEN
Solar/Wind Harmer
17.758
316317KELFORD C
Solar/Wind Harmer
0.334
3145823KELFORD
Solar/Wind Harmer
-0.007
3147043LAWRENC
Solar/Wind Harmer
-0.004
3145963POPLR C
Solar/Wind Harmer
-0.007
944581AF1-123 GEN
Solar/Wind Harmer
31.094
944601AF1-125 GEN
Solar/Wind Harmer
30.609
316210AC1-098 GEN
Solar/Wind Harmer
1.073
315724AD1-057 GEN
Solar/Wind Harmer
0.389
3145933PARMELE
Solar/Wind Harmer
-0.007
966801AG1-551 GEN
Solar/Wind Harmer
0.83
316327AA2-057 GEN
Solar/Wind Harmer
0.661
3145746EVERETS
Solar/Wind Harmer
-0.006
3145746EVERETS
Solar/Wind Harmer
-0.006
3146233WITAKRS
Solar/Wind Harmer
0.134
3146233WITAKRS
Solar/Wind Harmer
-0.004
3138543CONSLDL
Solar/Wind Harmer
-0.004
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3142946ENON
Solar/Wind Helper
0.172
316404AE1-155 C
Solar/Wind Helper
1.017
3141906WESTMOR
Solar/Wind Helper
0.047
316484AD2-074 GEN
Solar/Wind Helper
0.226
316280AD1-041 GEN
Solar/Wind Helper
0.389
316185AD1-033 GEN
Solar/Wind Harmer
0.801
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3146386ELIZ CT
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.211
3145893MURPHYS
Solar/Wind Harmer
-0.014
3130086AYDLETT
Solar/Wind Harmer
-0.03
3137176SLIGO L2192
Solar/Wind Harmer
-0.03
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146456SLIGO L269
Solar/Wind Harmer
0.891
316018AA1-139 ULT2
Solar/Wind Harmer
0.646
316017AA1-139 ULT1
Solar/Wind Harmer
0.61
316339AD2-160 GEN
Solar/Wind Harmer
0.509
3145506HICKORY
Solar/Wind Harmer
-0.03
3145506HICKORY
Solar/Wind Harmer
-0.018
3145506HICKORY
Solar/Wind Harmer
-0.004
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
972185AH1-677 GEN
Adder
3.75
316181AB2-040 GEN
Solar/Wind Harmer
1.047
3146376EDENTON
Solar/Wind Harmer
0.221
3146376EDENTON
Solar/Wind Harmer
0.221
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
972187AH1-678 GEN
Adder
1.874
3145796HORNRTN
Solar/Wind Harmer
-0.022
316065AD1-022 GEN
Solar/Wind Harmer
3.628
316426AA2-053 GEN
Solar/Wind Harmer
0.727
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.809
3145593CAROLNA
Solar/Wind Harmer
0.06
3145783HORNRTN
Solar/Wind Harmer
0.846
3145783HORNRTN
Solar/Wind Harmer
0.677
3145783HORNRTN
Solar/Wind Harmer
0.212
3145783HORNRTN
Solar/Wind Harmer
0.085
970933AG2-581 GEN
Solar/Wind Harmer
6.637
316274AC1-208 GEN
Solar/Wind Harmer
0.734
3145933PARMELE
Solar/Wind Harmer
-0.013
3145933PARMELE
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.098
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.039
3142946ENON
Solar/Wind Helper
0.052
316075AC2-137 C
Solar/Wind Helper
0.267
3143526WINTERP
Solar/Wind Helper
0.684
316077AC2-138 C
Solar/Wind Helper
0.119
316487AF1-042 GEN
Solar/Wind Helper
0.118
3145746EVERETS
Solar/Wind Harmer
-0.006
316494AC1-189 GEN
Solar/Wind Harmer
0.692
3146233WITAKRS
Solar/Wind Harmer
-0.025
961671AG1-007 GEN
Solar/Wind Harmer
0.08
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.189
3142433PROV 92
Solar/Wind Helper
0.589
964211AG1-282 GEN
Solar/Wind Helper
0.182
3141726DUNNSVL
Solar/Wind Helper
0.54
3141766HARMONY
Solar/Wind Helper
0.026
3143526WINTERP
Solar/Wind Helper
0.684
316337AD2-073 GEN
Solar/Wind Helper
0.19
3142416OLDCHRC
Solar/Wind Helper
0.318
3142416OLDCHRC
Solar/Wind Helper
0.122
LAGNLTFEXP_LAGN->PJM
CLTF
1.933
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.715
TVALTFEXP_TVA->PJM
CLTF
0.962
CPLELTFEXP_CPLE->PJM
CLTF
3.225
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.697
NYPJM->LTFIMP_NY
CLTF
0.526
LGEELTFEXP_LGEE->PJM
CLTF
0.278
WECLTFEXP_WEC->PJM
CLTF
0.141
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.782
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.236
MECLTFEXP_MEC->PJM
CLTF
0.818
SIGELTFEXP_SIGE->PJM
CLTF
0.024

Details for 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.66 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:1020.19
MW Contribution:2.83
Bus #Bus NameTypeMW Contribution
3150781HOPHCF2
50/50
1.611
3150791HOPHCF3
50/50
1.611
3150761HOPPOLC
50/50
1.021
971213AH1-066 GEN
50/50
1.413
316033AB2-134 GEN
Solar/Wind Harmer
0.016
315697AD1-025 GEN
Solar/Wind Harmer
0.308
944641AF1-129 GEN
Adder
75.02
316240AF1-291 C
Solar/Wind Harmer
0.001
316236AE1-162_GEN
Solar/Wind Harmer
0.001
970657AG2-426 GEN
Solar/Wind Harmer
4.673
970657AG2-426 GEN
Solar/Wind Harmer
0.98
3144356SAPONY
Solar/Wind Harmer
0.713
316036AC1-147 C
Solar/Wind Harmer
0.015
3150991CHESPKB
Adder
0.844
3150991CHESPKB
Adder
0.823
316316AC1-027 C
Solar/Wind Harmer
0.073
3142956BIRDNECK
Solar/Wind Harmer
0
3150801HOPHCF4
50/50
2.342
971211AH1-065 GEN
50/50
2.825
3151161SURRY 1
50/50
6.666
970133AG2-095 GEN
Solar/Wind Harmer
3.814
970129AG2-093 GEN
Solar/Wind Harmer
20.526
315778AD1-151 GEN
Solar/Wind Harmer
23.877
961611AG1-000B GEN
Solar/Wind Harmer
5.664
3151221GRAVEL6
Adder
12.617
3151171GRAVELC
Adder
2.427
315813AE1-149 C
Solar/Wind Harmer
8.487
970659AG2-427 GEN
Solar/Wind Harmer
1.488
3145336SMITFLD
Solar/Wind Harmer
0.055
316083AB2-161 GEN
Solar/Wind Harmer
0.002
315839AE2-212 C
Solar/Wind Harmer
0.001
970661AG2-428 GEN
Solar/Wind Harmer
2.691
3144536CHRHLND
Solar/Wind Harmer
0.014
3144873MCLAUGH
Solar/Wind Harmer
0.002
3151101ELIZAR3
Adder
7.311
3145273HOLLAND
Solar/Wind Harmer
0.058
3146456SLIGO L269
Solar/Wind Harmer
0.072
971153AH1-033 GEN
Solar/Wind Harmer
0.831
316320Y1-086
Solar/Wind Harmer
0
316365GEN2_N
Solar/Wind Harmer
0.16
316435W1029_GEN3
Solar/Wind Harmer
0
3146516WINFALL
Solar/Wind Harmer
0.071
3150771HOPHCF1
50/50
1.611
970129AG2-093 GEN
Solar/Wind Harmer
9.659
316458AB2-190 GEN2
Solar/Wind Harmer
1.79
971069AG2-661 GEN
Solar/Wind Harmer
5.306
971647AH1-324 GEN
Solar/Wind Harmer
10.386
961611AG1-000B GEN
Solar/Wind Harmer
11.14
3151171GRAVELC
Adder
1.846
970659AG2-427 GEN
Solar/Wind Harmer
6.802
3145336SMITFLD
Solar/Wind Harmer
0.551
316381AD1-082 GEN
Solar/Wind Harmer
0.143
970661AG2-428 GEN
Solar/Wind Harmer
12.653
316072AD1-144
Solar/Wind Harmer
0.031
316093AE2-104_GEN
Solar/Wind Harmer
1.36
316375AC2-012 GEN
Solar/Wind Harmer
0.002
3150981CHESPKA
Adder
1.006
316246AF1-032 C
Solar/Wind Harmer
0.033
316388AE2-253 GEN
Solar/Wind Harmer
0.226
3146456SLIGO L269
Solar/Wind Harmer
0.072
316023GEN1_S
Solar/Wind Harmer
0.16
3146516WINFALL
Solar/Wind Harmer
0.23
3146516WINFALL
Solar/Wind Harmer
0.071
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.069
3145663CRESWEL
Solar/Wind Harmer
0.188
971163AH1-040 GEN
Solar/Wind Harmer
5.37
3145893MURPHYS
Solar/Wind Harmer
0.267
3145893MURPHYS
Solar/Wind Harmer
0.297
944591AF1-124 GEN
Solar/Wind Harmer
15.038
960081AF2-299 GEN
Solar/Wind Harmer
0.63
3146173TUNIS
Solar/Wind Harmer
0.065
3146206CASHIE
Solar/Wind Harmer
0.065
971547AH1-271 GEN
Solar/Wind Harmer
1.388
316011AB1-132 GEN
Solar/Wind Harmer
1.175
962571AG1-106 GEN
Solar/Wind Harmer
0.92
3145683EARLEYS
Solar/Wind Harmer
0.064
3146263WOODLND
Solar/Wind Harmer
0.063
3145796HORNRTN
Solar/Wind Harmer
0.208
3145796HORNRTN
Solar/Wind Harmer
0.063
3145823KELFORD
Solar/Wind Harmer
0.062
316190AA2-174 GEN
Solar/Wind Harmer
0
3145963POPLR C
Solar/Wind Harmer
0.062
939411AE1-173 GEN
Solar/Wind Harmer
26.224
3145783HORNRTN
Solar/Wind Harmer
0.061
316174AB2-169 GEN
Solar/Wind Harmer
0.002
971795AH1-408 GEN
Solar/Wind Harmer
4.059
940641AE2-051 GEN
Solar/Wind Harmer
4.722
316212AC1-099_GEN
Solar/Wind Harmer
0.304
3147043LAWRENC
Adder
0.531
3146293MARTNCO
Solar/Wind Harmer
0.054
315722AD1-056 GEN
Solar/Wind Harmer
0.363
3145746EVERETS
Solar/Wind Harmer
0.056
3145746EVERETS
Solar/Wind Harmer
0.056
3142433PROV 92
Solar/Wind Helper
0.567
3143526WINTERP
Solar/Wind Helper
0.671
964211AG1-282 GEN
Solar/Wind Helper
0.172
3141726DUNNSVL
Solar/Wind Helper
0.512
3141766HARMONY
Solar/Wind Helper
0.025
316337AD2-073 GEN
Solar/Wind Helper
0.179
3142416OLDCHRC
Solar/Wind Helper
0.306
3142416OLDCHRC
Solar/Wind Helper
0.117
316132AB2-190 GEN1
Solar/Wind Harmer
1.79
316369SG1_INVT
Solar/Wind Harmer
0.01
972265AH1-717 GEN
Adder
13.474
3151201GRAVEL4
Adder
12.631
3151191GRAVEL3
Adder
12.471
3151211GRAVEL5
Adder
12.471
971445AH1-216 GEN
Solar/Wind Harmer
9.931
3143316POE
Solar/Wind Harmer
0.506
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.07
316311AC2-079 GEN
Solar/Wind Harmer
2.933
316315AB2-025 C
Solar/Wind Harmer
0.069
315814AE2-033 C
Solar/Wind Harmer
6.691
315835AF2-110_GEN
Solar/Wind Harmer
0.555
3152611GOSPORTB
Adder
1.025
3152621GOSPORTC
Adder
0.87
3152601GOSPORTA
Adder
0.803
3151081ELIZAR1
Adder
7.219
3151091ELIZAR2
Adder
7.094
316305AF2-043 C
Solar/Wind Harmer
0.001
3146486SUNBURY
Solar/Wind Harmer
0.072
3146486SUNBURY
Solar/Wind Harmer
0.072
957871AF2-081 GEN
Solar/Wind Harmer
3.584
319010AE1-072 C
Solar/Wind Harmer
0.362
3146406KITTY HAWK
Solar/Wind Harmer
0.009
313526AB2-022
Solar/Wind Harmer
0.039
316321Z2-027
Solar/Wind Harmer
0.013
3145176PASQUOTANK
Solar/Wind Harmer
0.044
3146396TANGLEW
Solar/Wind Harmer
0.196
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.069
3130156CHOWAN
Solar/Wind Harmer
0.069
965291AG1-394 GEN
Solar/Wind Harmer
0.303
315816AE2-034 GEN
Solar/Wind Harmer
0.288
3145893MURPHYS
Solar/Wind Harmer
0.18
3145893MURPHYS
Solar/Wind Harmer
0.067
3130546PLYMOUTH
Solar/Wind Harmer
0.066
315732AD1-074 GEN1
Solar/Wind Harmer
0.377
315733AD1-074 GEN2
Solar/Wind Harmer
0.377
315735AD1-075 GEN1
Solar/Wind Harmer
0.189
3146206CASHIE
Solar/Wind Harmer
0.065
970601AG2-382 GEN
Solar/Wind Harmer
2.429
315652AC1-086 GEN
Solar/Wind Harmer
7.109
3145513AHOSKIE
Solar/Wind Harmer
0.135
3145513AHOSKIE
Solar/Wind Harmer
0.064
3146043SEABORD
Solar/Wind Harmer
0.064
316087AB2-174 GEN
Solar/Wind Harmer
0.002
315607AA1-063A GEN
Solar/Wind Harmer
0.131
3145683EARLEYS
Solar/Wind Harmer
0.128
3145683EARLEYS
Solar/Wind Harmer
0.064
3145683EARLEYS
Solar/Wind Harmer
0.064
3145796HORNRTN
Solar/Wind Harmer
0.201
3145796HORNRTN
Solar/Wind Harmer
0.025
3137643SOCKMAN
Solar/Wind Harmer
0.249
3146033SCOT NK
Solar/Wind Harmer
0.241
941031AE2-094 GEN
Solar/Wind Harmer
11.006
944011AF1-069 GEN
Solar/Wind Harmer
3.596
970673AG2-436 GEN
Solar/Wind Harmer
12.481
970673AG2-436 GEN
Solar/Wind Harmer
8.321
971967AH1-528 GEN
Solar/Wind Harmer
9.126
316005AA1-067
Solar/Wind Harmer
0.061
3145746EVERETS
Solar/Wind Harmer
0.225
3145746EVERETS
Solar/Wind Harmer
0.056
3145746EVERETS
Solar/Wind Harmer
0.056
3145746EVERETS
Solar/Wind Harmer
0.056
970181AG2-120 GEN
Solar/Wind Harmer
0.703
3143873LANEXA
Solar/Wind Helper
0.084
316233AE1-074 FULL
Solar/Wind Helper
0.197
316059AD1-063 C
Solar/Wind Helper
0.125
3141813NORNECK
Solar/Wind Helper
0.119
316312AB1-027
Solar/Wind Helper
0.224
3146626S HERTFORD
Solar/Wind Harmer
0.07
965281AG1-393 GEN
Solar/Wind Harmer
0.748
3146376EDENTON
Solar/Wind Harmer
0.069
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
315614AA2-178 GEN
Solar/Wind Harmer
0.384
3145893MURPHYS
Solar/Wind Harmer
0.112
3145893MURPHYS
Solar/Wind Harmer
0.067
944581AF1-123 GEN
Solar/Wind Harmer
14.985
944601AF1-125 GEN
Solar/Wind Harmer
14.754
957521AF2-046 GEN
Solar/Wind Harmer
4.935
961681AG1-008 GEN
Solar/Wind Harmer
4.935
971157AH1-035 GEN
Solar/Wind Harmer
0.79
315737AD1-076 GEN
Solar/Wind Harmer
0.844
3146173TUNIS
Solar/Wind Harmer
0.065
3146206CASHIE
Solar/Wind Harmer
0.065
316463AE2-346 GEN
Solar/Wind Harmer
0.055
316140AB2-099
Solar/Wind Harmer
0.023
962331AG1-082 GEN
Solar/Wind Harmer
0.688
3142666NORTHAMPTON
Solar/Wind Harmer
0.064
3156021HOLLOMANSOL
Solar/Wind Harmer
0.292
313506AB2-031 GEN
Solar/Wind Harmer
0.197
3146263WOODLND
Solar/Wind Harmer
0.063
3145796HORNRTN
Solar/Wind Harmer
0.252
3145796HORNRTN
Solar/Wind Harmer
0.063
316317KELFORD C
Solar/Wind Harmer
0.006
3145823KELFORD
Solar/Wind Harmer
0.062
3145963POPLR C
Solar/Wind Harmer
0.062
316210AC1-098 GEN
Solar/Wind Harmer
0.545
3147043LAWRENC
Solar/Wind Harmer
0.035
3145933PARMELE
Solar/Wind Harmer
0.058
966801AG1-551 GEN
Solar/Wind Harmer
0.677
315724AD1-057 GEN
Solar/Wind Harmer
0.215
3145746EVERETS
Solar/Wind Harmer
0.056
3145746EVERETS
Solar/Wind Harmer
0.056
3142946ENON
Solar/Wind Helper
0.171
316404AE1-155 C
Solar/Wind Helper
0.955
315742AE1-103 GEN
Solar/Wind Harmer
0.001
316185AD1-033 GEN
Solar/Wind Harmer
0.002
3145506HICKORY
Solar/Wind Harmer
0.289
3145506HICKORY
Solar/Wind Harmer
0.173
3145506HICKORY
Solar/Wind Harmer
0.043
316339AD2-160 GEN
Solar/Wind Harmer
0.117
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
316017AA1-139 ULT1
Solar/Wind Harmer
0.04
3137176SLIGO L2192
Solar/Wind Harmer
0.286
3146456SLIGO L269
Solar/Wind Harmer
1.272
3130086AYDLETT
Solar/Wind Harmer
0.287
3146386ELIZ CT
Solar/Wind Harmer
0.071
316431W1029_GEN1
Solar/Wind Harmer
0
316433W1029_GEN2
Solar/Wind Harmer
0
3146516WINFALL
Solar/Wind Harmer
0.071
3146516WINFALL
Solar/Wind Harmer
0.071
3146516WINFALL
Solar/Wind Harmer
0.071
3146626S HERTFORD
Solar/Wind Harmer
0.07
3146626S HERTFORD
Solar/Wind Harmer
0.07
3146376EDENTON
Solar/Wind Harmer
0.306
3146376EDENTON
Solar/Wind Harmer
0.306
3145893MURPHYS
Solar/Wind Harmer
0.447
3145893MURPHYS
Solar/Wind Harmer
0.12
3146173TUNIS
Solar/Wind Harmer
0.065
3146173TUNIS
Solar/Wind Harmer
0.065
316065AD1-022 GEN
Solar/Wind Harmer
3.005
3142666NORTHAMPTON
Solar/Wind Harmer
0.064
3142666NORTHAMPTON
Solar/Wind Harmer
0.064
3142666NORTHAMPTON
Solar/Wind Harmer
0.064
3142666NORTHAMPTON
Solar/Wind Harmer
0.039
316181AB2-040 GEN
Solar/Wind Harmer
0.092
3145796HORNRTN
Solar/Wind Harmer
0.189
316426AA2-053 GEN
Solar/Wind Harmer
0.209
3145593CAROLNA
Solar/Wind Harmer
0.061
3145593CAROLNA
Solar/Wind Harmer
0.061
966811AG1-552 GEN
Solar/Wind Harmer
0.666
3145593CAROLNA
Solar/Wind Harmer
0.076
3145783HORNRTN
Solar/Wind Harmer
1.083
3145783HORNRTN
Solar/Wind Harmer
0.867
3145783HORNRTN
Solar/Wind Harmer
0.271
3145783HORNRTN
Solar/Wind Harmer
0.108
316274AC1-208 GEN
Solar/Wind Harmer
0.302
3145933PARMELE
Solar/Wind Harmer
0.116
3145933PARMELE
Solar/Wind Harmer
0.058
972185AH1-677 GEN
Adder
3.248
972187AH1-678 GEN
Adder
1.624
3142946ENON
Solar/Wind Helper
0.051
316075AC2-137 C
Solar/Wind Helper
0.259
3143526WINTERP
Solar/Wind Helper
0.671
316077AC2-138 C
Solar/Wind Helper
0.112
LAGNLTFEXP_LAGN->PJM
CLTF
1.706
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.033
TVALTFEXP_TVA->PJM
CLTF
0.849
CPLELTFEXP_CPLE->PJM
CLTF
2.918
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.48
NYPJM->LTFIMP_NY
CLTF
0.492
LGEELTFEXP_LGEE->PJM
CLTF
0.236
WECLTFEXP_WEC->PJM
CLTF
0.119
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.993
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.847
MECLTFEXP_MEC->PJM
CLTF
0.703
SIGELTFEXP_SIGE->PJM
CLTF
0.02

Details for 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6IRON208-6SOUWEST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 557_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.96 %
Rating:663.64 MVA
Rating Type:B
MVA to Mitigate:689.92
MW Contribution:0.98
Bus #Bus NameTypeMW Contribution
3150611CHESTG7
50/50
1.633
3150631CHESTG8
50/50
1.607
971047AG2-646 GEN
50/50
45.726
315759AF1-018 GEN
50/50
3.414
316132AB2-190 GEN1
Solar/Wind Harmer
0.67
315976AC1-164 GENA
Solar/Wind Harmer
12.162
316169AC1-164_GENC
Solar/Wind Harmer
10.507
315975AC1-164 GENB
Solar/Wind Harmer
0.36
316369SG1_INVT
Solar/Wind Harmer
0.004
316314AB2-024 C
Solar/Wind Harmer
0
316059AD1-063 C
Solar/Wind Harmer
0.001
3143096IRON208
50/50
2.365
3150641CHESTS8
50/50
0.828
944631AF1-128 GEN
50/50
130.091
3150771HOPHCF1
50/50
0.557
3152331SURRY 2
50/50
2.862
970129AG2-093 GEN
Solar/Wind Harmer
3.585
316458AB2-190 GEN2
Solar/Wind Harmer
0.67
971069AG2-661 GEN
Solar/Wind Harmer
2.098
971647AH1-324 GEN
Solar/Wind Harmer
4.574
3150621CHESTS7
50/50
0.75
3150781HOPHCF2
50/50
0.557
3150791HOPHCF3
50/50
0.557
3150761HOPPOLC
50/50
0.353
971213AH1-066 GEN
50/50
0.488
3142946ENON
Solar/Wind Harmer
0.022
316033AB2-134 GEN
Solar/Wind Harmer
0.007
315697AD1-025 GEN
Solar/Wind Harmer
0.127
958261AF2-120 GEN
Solar/Wind Harmer
2.785
316236AE1-162_GEN
Solar/Wind Harmer
0.001
316075AC2-137 C
Solar/Wind Harmer
0.023
316077AC2-138 C
Solar/Wind Harmer
0
3150341NORNECKC1
Adder
0.851
3150341NORNECKC1
Adder
0.845
970657AG2-426 GEN
Solar/Wind Harmer
2.421
970657AG2-426 GEN
Solar/Wind Harmer
0.507
316036AC1-147 C
Solar/Wind Harmer
0.013
3150991CHESPKB
Adder
0.712
3150991CHESPKB
Adder
0.694
316316AC1-027 C
Solar/Wind Harmer
0.064
3142956BIRDNECK
Solar/Wind Harmer
0
316185AD1-033 GEN
Solar/Wind Harmer
0.002
3145506HICKORY
Solar/Wind Harmer
0.26
3145506HICKORY
Solar/Wind Harmer
0.156
3145506HICKORY
Solar/Wind Harmer
0.039
316339AD2-160 GEN
Solar/Wind Harmer
0.105
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
316017AA1-139 ULT1
Solar/Wind Harmer
0.036
3137176SLIGO L2192
Solar/Wind Harmer
0.256
3146456SLIGO L269
Solar/Wind Harmer
1.137
3130086AYDLETT
Solar/Wind Harmer
0.256
3146386ELIZ CT
Solar/Wind Harmer
0.063
316431W1029_GEN1
Solar/Wind Harmer
0
316433W1029_GEN2
Solar/Wind Harmer
0
3146516WINFALL
Solar/Wind Harmer
0.061
3146516WINFALL
Solar/Wind Harmer
0.061
3146516WINFALL
Solar/Wind Harmer
0.061
3146626S HERTFORD
Solar/Wind Harmer
0.06
3146626S HERTFORD
Solar/Wind Harmer
0.06
315742AE1-103 GEN
Solar/Wind Harmer
0.001
3146376EDENTON
Solar/Wind Harmer
0.255
3146376EDENTON
Solar/Wind Harmer
0.255
3143526WINTERP
Solar/Wind Helper
1.618
3143096IRON208
50/50
2.365
3143096IRON208
50/50
2.318
3150801HOPHCF4
50/50
0.81
971211AH1-065 GEN
50/50
0.977
315749AE2-041 GEN
50/50
3.414
3151161SURRY 1
50/50
3.592
3142946ENON
Solar/Wind Harmer
0.072
970133AG2-095 GEN
Solar/Wind Harmer
1.318
970129AG2-093 GEN
Solar/Wind Harmer
7.619
315778AD1-151 GEN
Solar/Wind Harmer
9.439
961611AG1-000B GEN
Solar/Wind Harmer
2.697
3141766HARMONY
Solar/Wind Harmer
1.28
316382AG1-145 C
Solar/Wind Harmer
0.001
3151221GRAVEL6
Adder
6.799
3151171GRAVELC
Adder
1.308
3141843SHACKLE
Adder
0.471
316203AE2-005 GEN
Solar/Wind Harmer
0
316280AD1-041 GEN
Solar/Wind Harmer
0.002
316156AD2-030 GEN
Solar/Wind Harmer
0.068
3141873WAN 176
Solar/Wind Harmer
1.624
962971AG1-146 GEN
Solar/Wind Harmer
1.39
970009AG2-005 GEN
Solar/Wind Harmer
0.641
3142433PROV 92
Adder
0.165
3142433PROV 92
Adder
0.165
3144216WINCHST
Adder
0.319
316404AE1-155 C
Solar/Wind Harmer
0.019
3145336SMITFLD
Solar/Wind Harmer
0.033
3150921YORKTN3
Adder
2.093
3150351NORNECKC2
Adder
0.824
3144536CHRHLND
Solar/Wind Harmer
0.011
315813AE1-149 C
Solar/Wind Harmer
3.817
970659AG2-427 GEN
Solar/Wind Harmer
0.738
316083AB2-161 GEN
Solar/Wind Harmer
0.001
970661AG2-428 GEN
Solar/Wind Harmer
1.45
3144873MCLAUGH
Solar/Wind Harmer
0.002
3151101ELIZAR3
Adder
6.266
3141906WESTMOR
Solar/Wind Harmer
0.027
944581AF1-123 GEN
Solar/Wind Harmer
14.477
944601AF1-125 GEN
Solar/Wind Harmer
14.254
3146456SLIGO L269
Solar/Wind Harmer
0.064
971153AH1-033 GEN
Solar/Wind Harmer
0.742
316320Y1-086
Solar/Wind Harmer
0
315773AC2-141 GEN
Solar/Wind Harmer
2.272
316435W1029_GEN3
Solar/Wind Harmer
0
3146516WINFALL
Solar/Wind Harmer
0.061
965281AG1-393 GEN
Solar/Wind Harmer
0.649
3146626S HERTFORD
Solar/Wind Harmer
0.06
970737AG2-469 GEN
Solar/Wind Harmer
2.555
3145273HOLLAND
Solar/Wind Harmer
0.045
3146376EDENTON
Solar/Wind Harmer
0.057
961611AG1-000B GEN
Solar/Wind Harmer
5.304
3141766HARMONY
Solar/Wind Harmer
0.019
316159AE1-175 C
Solar/Wind Harmer
0.081
3151171GRAVELC
Adder
0.995
971777AH1-397 GEN
Solar/Wind Harmer
0.243
3141843SHACKLE
Adder
0.471
3138133OCRAN
Solar/Wind Harmer
0.054
971317AH1-138 GEN
Solar/Wind Harmer
0.639
3142433PROV 92
Solar/Wind Harmer
0.34
3142433PROV 92
Adder
0.165
3142433PROV 92
Adder
0.165
962861AG1-135 GEN
Solar/Wind Harmer
2.709
3141726DUNNSVL
Solar/Wind Harmer
0.337
3138126ROCKLANDING
Solar/Wind Harmer
0.039
3145336SMITFLD
Solar/Wind Harmer
0.335
3150351NORNECKC2
Adder
0.811
316337AD2-073 GEN
Solar/Wind Harmer
0.065
316072AD1-144
Solar/Wind Harmer
0.026
970659AG2-427 GEN
Solar/Wind Harmer
3.376
316381AD1-082 GEN
Solar/Wind Harmer
0.072
970661AG2-428 GEN
Solar/Wind Harmer
6.816
316375AC2-012 GEN
Solar/Wind Harmer
0.002
3150981CHESPKA
Adder
0.848
316246AF1-032 C
Solar/Wind Harmer
0.029
316388AE2-253 GEN
Solar/Wind Harmer
0.202
944591AF1-124 GEN
Solar/Wind Harmer
14.529
3146456SLIGO L269
Solar/Wind Harmer
0.064
316093AE2-104_GEN
Solar/Wind Harmer
1.078
316294AC1-161 GEN
Solar/Wind Harmer
1.078
3146516WINFALL
Solar/Wind Harmer
0.198
3146516WINFALL
Solar/Wind Harmer
0.061
315671AE2-027_GEN
Solar/Wind Harmer
3.892
315800Z1-036_GEN1
Solar/Wind Harmer
0
3130156CHOWAN
Solar/Wind Harmer
0.057
3143526WINTERP
Solar/Wind Helper
1.618
3143226MDLTHAN
Solar/Wind Helper
0.118
972265AH1-717 GEN
Adder
7.261
3151201GRAVEL4
Adder
6.807
3151191GRAVEL3
Adder
6.721
3151211GRAVEL5
Adder
6.721
3143873LANEXA
Solar/Wind Harmer
0.056
970189AG2-124 GEN
Solar/Wind Harmer
2.733
315662AE1-191 GEN
Solar/Wind Harmer
0.003
315666AE1-190 GEN
Solar/Wind Harmer
0.001
3141873WAN 176
Solar/Wind Harmer
0.018
3141913WHIT STONE
Solar/Wind Harmer
0.09
3138133OCRAN
Solar/Wind Harmer
0.027
3141783LANCAST
Solar/Wind Harmer
0.053
3141783LANCAST
Solar/Wind Harmer
0.035
3138283WHITEMARSH
Solar/Wind Harmer
0.02
962981AG1-147 GEN
Solar/Wind Harmer
3.244
970327AG2-215 GEN
Solar/Wind Harmer
2.818
3142433PROV 92
Adder
0.165
3142433PROV 92
Adder
0.165
971445AH1-216 GEN
Solar/Wind Harmer
5.957
971167AH1-042 GEN
Solar/Wind Harmer
7.355
3141813NORNECK
Solar/Wind Harmer
0.081
3152611GOSPORTB
Adder
0.865
3152621GOSPORTC
Adder
0.734
3152601GOSPORTA
Adder
0.677
3151081ELIZAR1
Adder
6.186
3151091ELIZAR2
Adder
6.079
316223AC1-118
Solar/Wind Harmer
0.048
315833AF1-017_GEN
Solar/Wind Harmer
0
316349AD2-085 GEN
Solar/Wind Harmer
0.045
316311AC2-079 GEN
Solar/Wind Harmer
1.899
316305AF2-043 C
Solar/Wind Harmer
0.001
957871AF2-081 GEN
Solar/Wind Harmer
3.21
319010AE1-072 C
Solar/Wind Harmer
0.323
315835AF2-110_GEN
Solar/Wind Harmer
0.44
3146406KITTY HAWK
Solar/Wind Harmer
0.008
313526AB2-022
Solar/Wind Harmer
0.034
3146486SUNBURY
Solar/Wind Harmer
0.063
3146486SUNBURY
Solar/Wind Harmer
0.063
316321Z2-027
Solar/Wind Harmer
0.012
3146396TANGLEW
Solar/Wind Harmer
0.172
3145176PASQUOTANK
Solar/Wind Harmer
0.039
315611Z1-036_GEN2
Solar/Wind Harmer
0
3130156CHOWAN
Solar/Wind Harmer
0.057
3130156CHOWAN
Solar/Wind Harmer
0.057
316233AE1-074 FULL
Solar/Wind Helper
0.475
LAGNLTFEXP_LAGN->PJM
CLTF
0.804
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.434
TVALTFEXP_TVA->PJM
CLTF
0.397
CPLELTFEXP_CPLE->PJM
CLTF
1.734
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.554
NYPJM->LTFIMP_NY
CLTF
0.33
LGEELTFEXP_LGEE->PJM
CLTF
0.057
WECLTFEXP_WEC->PJM
CLTF
0.026
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.657
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.279
MECLTFEXP_MEC->PJM
CLTF
0.223
SIGELTFEXP_SIGE->PJM
CLTF
0.006

Details for 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6IRON208-6SOUWEST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.72 %
Rating:663.64 MVA
Rating Type:B
MVA to Mitigate:668.44
MW Contribution:0.9
Bus #Bus NameTypeMW Contribution
3143096IRON208
50/50
2.307
3150611CHESTG7
50/50
1.535
3150631CHESTG8
50/50
1.511
971047AG2-646 GEN
50/50
42.989
316132AB2-190 GEN1
Solar/Wind Harmer
0.61
316369SG1_INVT
Solar/Wind Harmer
0.004
315976AC1-164 GENA
Solar/Wind Harmer
9.735
316169AC1-164_GENC
Solar/Wind Harmer
8.41
315975AC1-164 GENB
Solar/Wind Harmer
0.288
972265AH1-717 GEN
Adder
6.312
3151201GRAVEL4
Adder
5.917
3151191GRAVEL3
Adder
5.842
3151211GRAVEL5
Adder
5.842
316314AB2-024 C
Solar/Wind Harmer
0
316059AD1-063 C
Solar/Wind Harmer
0
3143873LANEXA
Solar/Wind Harmer
0.045
970189AG2-124 GEN
Solar/Wind Harmer
2.166
971445AH1-216 GEN
Solar/Wind Harmer
5.125
315662AE1-191 GEN
Solar/Wind Harmer
0.002
315666AE1-190 GEN
Solar/Wind Harmer
0.001
3141873WAN 176
Solar/Wind Harmer
0.014
3141913WHIT STONE
Solar/Wind Harmer
0.071
3138133OCRAN
Solar/Wind Harmer
0.021
3141783LANCAST
Solar/Wind Harmer
0.042
3141783LANCAST
Solar/Wind Harmer
0.028
3138283WHITEMARSH
Solar/Wind Harmer
0.016
962981AG1-147 GEN
Solar/Wind Harmer
2.557
3142433PROV 92
Adder
0.133
3142433PROV 92
Adder
0.133
970327AG2-215 GEN
Solar/Wind Harmer
2.22
971167AH1-042 GEN
Solar/Wind Harmer
5.919
3141813NORNECK
Solar/Wind Harmer
0.064
315833AF1-017_GEN
Solar/Wind Harmer
0
316349AD2-085 GEN
Solar/Wind Harmer
0.04
316311AC2-079 GEN
Solar/Wind Harmer
1.663
3152611GOSPORTB
Adder
0.725
3152621GOSPORTC
Adder
0.615
3152601GOSPORTA
Adder
0.568
3151081ELIZAR1
Adder
5.179
3151091ELIZAR2
Adder
5.089
316233AE1-074 FULL
Solar/Wind Helper
0.525
3143096IRON208
50/50
2.307
3143096IRON208
50/50
2.26
3150801HOPHCF4
50/50
0.746
971211AH1-065 GEN
50/50
0.9
3151161SURRY 1
50/50
3.123
3142946ENON
Solar/Wind Harmer
0.066
970133AG2-095 GEN
Solar/Wind Harmer
1.215
970129AG2-093 GEN
Solar/Wind Harmer
6.944
315778AD1-151 GEN
Solar/Wind Harmer
8.525
961611AG1-000B GEN
Solar/Wind Harmer
2.377
3151221GRAVEL6
Adder
5.91
3151171GRAVELC
Adder
1.137
3141766HARMONY
Solar/Wind Harmer
1.013
316382AG1-145 C
Solar/Wind Harmer
0.001
3141843SHACKLE
Adder
0.374
316203AE2-005 GEN
Solar/Wind Harmer
0
316280AD1-041 GEN
Solar/Wind Harmer
0.001
316156AD2-030 GEN
Solar/Wind Harmer
0.053
3141873WAN 176
Solar/Wind Harmer
1.283
3145336SMITFLD
Solar/Wind Harmer
0.029
962971AG1-146 GEN
Solar/Wind Harmer
1.096
3142433PROV 92
Adder
0.133
3142433PROV 92
Adder
0.133
970009AG2-005 GEN
Solar/Wind Harmer
0.505
3144216WINCHST
Adder
0.253
316404AE1-155 C
Solar/Wind Harmer
0.015
315813AE1-149 C
Solar/Wind Harmer
3.52
3150921YORKTN3
Adder
1.637
3150351NORNECKC2
Adder
0.647
970659AG2-427 GEN
Solar/Wind Harmer
0.67
316083AB2-161 GEN
Solar/Wind Harmer
0.001
970661AG2-428 GEN
Solar/Wind Harmer
1.3
3144536CHRHLND
Solar/Wind Harmer
0.009
3144873MCLAUGH
Solar/Wind Harmer
0.001
3151101ELIZAR3
Adder
5.246
3150641CHESTS8
50/50
0.778
944631AF1-128 GEN
50/50
122.303
3150771HOPHCF1
50/50
0.513
970129AG2-093 GEN
Solar/Wind Harmer
3.268
316458AB2-190 GEN2
Solar/Wind Harmer
0.61
971069AG2-661 GEN
Solar/Wind Harmer
1.894
971647AH1-324 GEN
Solar/Wind Harmer
4.071
961611AG1-000B GEN
Solar/Wind Harmer
4.675
3151171GRAVELC
Adder
0.865
3141766HARMONY
Solar/Wind Harmer
0.015
316159AE1-175 C
Solar/Wind Harmer
0.063
971777AH1-397 GEN
Solar/Wind Harmer
0.193
3141843SHACKLE
Adder
0.374
3145336SMITFLD
Solar/Wind Harmer
0.288
3138133OCRAN
Solar/Wind Harmer
0.042
3142433PROV 92
Solar/Wind Harmer
0.273
3142433PROV 92
Adder
0.133
3142433PROV 92
Adder
0.133
962861AG1-135 GEN
Solar/Wind Harmer
2.133
3138126ROCKLANDING
Solar/Wind Harmer
0.03
3141726DUNNSVL
Solar/Wind Harmer
0.265
971317AH1-138 GEN
Solar/Wind Harmer
0.495
3150351NORNECKC2
Adder
0.637
970659AG2-427 GEN
Solar/Wind Harmer
3.065
316381AD1-082 GEN
Solar/Wind Harmer
0.066
970661AG2-428 GEN
Solar/Wind Harmer
6.114
316072AD1-144
Solar/Wind Harmer
0.022
316337AD2-073 GEN
Solar/Wind Harmer
0.051
316375AC2-012 GEN
Solar/Wind Harmer
0.001
3150981CHESPKA
Adder
0.711
3143526WINTERP
Solar/Wind Helper
1.788
3143226MDLTHAN
Solar/Wind Helper
0.157
3150621CHESTS7
50/50
0.705
3150781HOPHCF2
50/50
0.513
3150791HOPHCF3
50/50
0.513
3150761HOPPOLC
50/50
0.325
971213AH1-066 GEN
50/50
0.45
3142946ENON
Solar/Wind Harmer
0.02
316033AB2-134 GEN
Solar/Wind Harmer
0.006
315697AD1-025 GEN
Solar/Wind Harmer
0.114
316236AE1-162_GEN
Solar/Wind Harmer
0.001
958261AF2-120 GEN
Solar/Wind Harmer
2.192
316077AC2-138 C
Solar/Wind Harmer
0
3150341NORNECKC1
Adder
0.669
3150341NORNECKC1
Adder
0.663
316075AC2-137 C
Solar/Wind Harmer
0.018
970657AG2-426 GEN
Solar/Wind Harmer
2.184
970657AG2-426 GEN
Solar/Wind Harmer
0.458
316036AC1-147 C
Solar/Wind Harmer
0.011
3150991CHESPKB
Adder
0.596
3150991CHESPKB
Adder
0.582
3143526WINTERP
Solar/Wind Helper
1.788
LAGNLTFEXP_LAGN->PJM
CLTF
1.059
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.936
TVALTFEXP_TVA->PJM
CLTF
0.526
CPLELTFEXP_CPLE->PJM
CLTF
1.919
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.103
NYPJM->LTFIMP_NY
CLTF
0.354
LGEELTFEXP_LGEE->PJM
CLTF
0.127
WECLTFEXP_WEC->PJM
CLTF
0.063
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.024
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.746
MECLTFEXP_MEC->PJM
CLTF
0.397
SIGELTFEXP_SIGE->PJM
CLTF
0.011

Details for 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer
Contingency Name:
DVP_P7-1: LN 211-228_SRT-S
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:146.93 %
Rating:287.5 MVA
Rating Type:C
MVA to Mitigate:422.43
MW Contribution:2.54
Bus #Bus NameTypeMW Contribution
316132AB2-190 GEN1
Solar/Wind Harmer
3.37
316369SG1_INVT
Solar/Wind Harmer
4.82
972265AH1-717 GEN
Adder
11.28
3151201GRAVEL4
Adder
10.575
3151191GRAVEL3
Adder
10.441
3151211GRAVEL5
Adder
10.441
971445AH1-216 GEN
Solar/Wind Harmer
7.714
3143316POE
Solar/Wind Helper
0.574
3150781HOPHCF2
50/50
1.445
3150791HOPHCF3
50/50
1.445
3150761HOPPOLC
50/50
0.916
971213AH1-066 GEN
50/50
1.268
316033AB2-134 GEN
Solar/Wind Harmer
8.701
315697AD1-025 GEN
Solar/Wind Harmer
5.457
316236AE1-162_GEN
Solar/Wind Harmer
0.364
3150771HOPHCF1
50/50
1.445
970129AG2-093 GEN
Solar/Wind Harmer
7.74
316458AB2-190 GEN2
Solar/Wind Harmer
3.37
971069AG2-661 GEN
Solar/Wind Harmer
4.68
971647AH1-324 GEN
Solar/Wind Harmer
11.868
961611AG1-000B GEN
Solar/Wind Harmer
10.091
3151171GRAVELC
Adder
1.545
3145336SMITFLD
Solar/Wind Harmer
-0.048
944591AF1-124 GEN
Solar/Wind Harmer
16.821
316381AD1-082 GEN
Solar/Wind Helper
1.297
3150801HOPHCF4
50/50
2.102
971211AH1-065 GEN
50/50
2.535
3151161SURRY 1
50/50
5.581
970133AG2-095 GEN
Solar/Wind Harmer
4.506
970129AG2-093 GEN
Solar/Wind Harmer
19.108
315778AD1-151 GEN
Solar/Wind Harmer
25.62
961611AG1-000B GEN
Solar/Wind Harmer
4.306
3151221GRAVEL6
Adder
10.562
3151171GRAVELC
Adder
2.032
3145336SMITFLD
Solar/Wind Harmer
-0.005
3144536CHRHLND
Solar/Wind Harmer
-0.001
944581AF1-123 GEN
Solar/Wind Harmer
16.761
944601AF1-125 GEN
Solar/Wind Harmer
16.499
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.097
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.302
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.125
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.038
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.034
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.429

Details for 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 208-259_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6VARINA-6CHARCTY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 208-259_SRT-S
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:100.86 %
Rating:1204.0 MVA
Rating Type:C
MVA to Mitigate:1214.4
MW Contribution:1.27
Bus #Bus NameTypeMW Contribution
970603AG2-384 GEN
50/50
6.703
315779AE2-040
50/50
1.679
3143316POE
Solar/Wind Harmer
-0.085
316132AB2-190 GEN1
Solar/Wind Harmer
1.784
944641AF1-129 GEN
50/50
158.905
3150781HOPHCF2
50/50
0.727
3150791HOPHCF3
50/50
0.727
3150761HOPPOLC
50/50
0.461
971213AH1-066 GEN
50/50
0.638
316240AF1-291 C
Solar/Wind Harmer
1.017
316033AB2-134 GEN
Solar/Wind Harmer
4.927
315697AD1-025 GEN
Solar/Wind Harmer
3.09
970657AG2-426 GEN
Solar/Wind Harmer
4.626
970657AG2-426 GEN
Solar/Wind Harmer
0.967
3144356SAPONY
Solar/Wind Harmer
0.472
316236AE1-162_GEN
Solar/Wind Harmer
0.296
316181AB2-040 GEN
Solar/Wind Harmer
1.19
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145796HORNRTN
Solar/Wind Harmer
-0.025
315742AE1-103 GEN
Solar/Wind Harmer
0.861
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.883
3145593CAROLNA
Solar/Wind Harmer
0.065
3145893MURPHYS
Solar/Wind Harmer
0.219
3145893MURPHYS
Solar/Wind Harmer
-0.014
316426AA2-053 GEN
Solar/Wind Harmer
0.788
3145783HORNRTN
Solar/Wind Harmer
0.921
3145783HORNRTN
Solar/Wind Harmer
0.737
3145783HORNRTN
Solar/Wind Harmer
0.23
3145783HORNRTN
Solar/Wind Harmer
0.092
3142946ENON
Solar/Wind Harmer
-0.001
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316036AC1-147 C
Solar/Wind Harmer
0.202
3150991CHESPKB
Adder
0.698
3150991CHESPKB
Adder
0.682
316065AD1-022 GEN
Solar/Wind Harmer
3.68
316316AC1-027 C
Solar/Wind Harmer
0.226
316431W1029_GEN1
Solar/Wind Harmer
1.33
316433W1029_GEN2
Solar/Wind Harmer
1.33
3142956BIRDNECK
Solar/Wind Harmer
0.393
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
0.217
3146376EDENTON
Solar/Wind Harmer
0.217
3146386ELIZ CT
Solar/Wind Harmer
-0.007
316274AC1-208 GEN
Solar/Wind Harmer
0.784
3130086AYDLETT
Solar/Wind Harmer
-0.029
3137176SLIGO L2192
Solar/Wind Harmer
-0.029
3146456SLIGO L269
Solar/Wind Harmer
0.852
316018AA1-139 ULT2
Solar/Wind Harmer
0.617
316017AA1-139 ULT1
Solar/Wind Harmer
0.583
316339AD2-160 GEN
Solar/Wind Harmer
0.486
316185AD1-033 GEN
Solar/Wind Harmer
0.759
3145506HICKORY
Solar/Wind Harmer
-0.029
3145506HICKORY
Solar/Wind Harmer
-0.017
3145506HICKORY
Solar/Wind Harmer
-0.004
3145933PARMELE
Solar/Wind Harmer
-0.014
3145933PARMELE
Solar/Wind Harmer
-0.007
972185AH1-677 GEN
Adder
3.332
3145493TOT1
Solar/Wind Harmer
0.103
3145453TOT5
Solar/Wind Harmer
0.062
3145603CNETO
Solar/Wind Harmer
0.041
961601AG1-000A GEN
Solar/Wind Harmer
2.599
972187AH1-678 GEN
Adder
1.668
316263AC1-034 GEN
Solar/Wind Harmer
3.083
966871AG1-558 GEN
Solar/Wind Helper
0.264
316468AD1-105 GEN
Solar/Wind Helper
0.799
3150771HOPHCF1
50/50
0.727
970129AG2-093 GEN
Solar/Wind Harmer
4.076
316458AB2-190 GEN2
Solar/Wind Harmer
1.784
971069AG2-661 GEN
Solar/Wind Harmer
2.57
970659AG2-427 GEN
Solar/Wind Harmer
8.328
316381AD1-082 GEN
Solar/Wind Harmer
1.399
315671AE2-027_GEN
Solar/Wind Harmer
10.881
971647AH1-324 GEN
Solar/Wind Harmer
7.034
970661AG2-428 GEN
Solar/Wind Harmer
14.929
961611AG1-000B GEN
Solar/Wind Harmer
6.338
3151171GRAVELC
Adder
1.07
316023GEN1_S
Solar/Wind Harmer
0.693
944631AF1-128 GEN
Adder
42.519
3145336SMITFLD
Solar/Wind Harmer
-0.039
960081AF2-299 GEN
Solar/Wind Harmer
1.027
316011AB1-132 GEN
Solar/Wind Harmer
1.806
962571AG1-106 GEN
Solar/Wind Harmer
1.241
316093AE2-104_GEN
Solar/Wind Harmer
2.456
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.008
971795AH1-408 GEN
Solar/Wind Harmer
6.247
3147043LAWRENC
Adder
0.641
316072AD1-144
Solar/Wind Harmer
0.16
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
0.232
316190AA2-174 GEN
Solar/Wind Harmer
0.096
3145783HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
3146263WOODLND
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
316375AC2-012 GEN
Solar/Wind Harmer
2.593
3150981CHESPKA
Adder
0.833
316246AF1-032 C
Solar/Wind Harmer
0.151
3145823KELFORD
Solar/Wind Harmer
-0.007
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.847
315722AD1-056 GEN
Solar/Wind Harmer
0.772
3146516WINFALL
Solar/Wind Harmer
-0.024
3146516WINFALL
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
1.809
3130156CHOWAN
Solar/Wind Harmer
-0.007
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.858
316212AC1-099_GEN
Solar/Wind Harmer
0.632
3146456SLIGO L269
Solar/Wind Harmer
-0.007
316388AE2-253 GEN
Solar/Wind Harmer
0.486
3145963POPLR C
Solar/Wind Harmer
-0.007
316174AB2-169 GEN
Solar/Wind Harmer
1.078
939411AE1-173 GEN
Solar/Wind Harmer
34.71
940641AE2-051 GEN
Solar/Wind Harmer
6.466
944591AF1-124 GEN
Solar/Wind Harmer
31.446
3146293MARTNCO
Solar/Wind Harmer
0.042
3146233WITAKRS
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
316494AC1-189 GEN
Solar/Wind Harmer
0.717
961671AG1-007 GEN
Solar/Wind Harmer
0.084
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.197
316359AB2-059 GEN
Solar/Wind Harmer
0.887
316049AB1-081 GEN
Solar/Wind Harmer
0.71
3142053HEARTS
Solar/Wind Harmer
0.077
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316129AC1-054 GEN
Solar/Wind Harmer
0.565
970919AG2-571 GEN
Solar/Wind Harmer
2.009
970087AG2-069 GEN
Solar/Wind Harmer
5.929
971065AG2-659 GEN
Solar/Wind Harmer
3.161
3150801HOPHCF4
50/50
1.058
971211AH1-065 GEN
50/50
1.275
315839AE2-212 C
Solar/Wind Harmer
0.847
970133AG2-095 GEN
Solar/Wind Harmer
2.267
315813AE1-149 C
Solar/Wind Harmer
11.193
970129AG2-093 GEN
Solar/Wind Harmer
10.063
315778AD1-151 GEN
Solar/Wind Harmer
14.073
965281AG1-393 GEN
Solar/Wind Harmer
1.997
970659AG2-427 GEN
Solar/Wind Harmer
1.476
316083AB2-161 GEN
Solar/Wind Harmer
2.477
970661AG2-428 GEN
Solar/Wind Harmer
2.646
961611AG1-000B GEN
Solar/Wind Harmer
2.704
3151221GRAVEL6
Adder
7.315
3151171GRAVELC
Adder
1.407
316365GEN2_N
Solar/Wind Harmer
0.693
3145336SMITFLD
Solar/Wind Harmer
-0.004
966621AG1-532 GEN
Solar/Wind Harmer
0.185
313506AB2-031 GEN
Solar/Wind Harmer
0.685
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.033
3145796HORNRTN
Solar/Wind Harmer
-0.008
3145273HOLLAND
Solar/Wind Harmer
-0.006
3144536CHRHLND
Solar/Wind Harmer
-0.001
3156081AA2-088 GEN
Solar/Wind Harmer
2.594
3147043LAWRENC
Solar/Wind Harmer
-0.005
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
957521AF2-046 GEN
Solar/Wind Harmer
6.136
961681AG1-008 GEN
Solar/Wind Harmer
6.136
3142946ENON
Solar/Wind Harmer
-0.003
3146173TUNIS
Solar/Wind Harmer
-0.008
3146263WOODLND
Solar/Wind Harmer
-0.008
316463AE2-346 GEN
Solar/Wind Harmer
0.123
316140AB2-099
Solar/Wind Harmer
0.051
962331AG1-082 GEN
Solar/Wind Harmer
0.952
3144873MCLAUGH
Solar/Wind Harmer
0
3156021HOLLOMANSOL
Solar/Wind Harmer
1.009
316317KELFORD C
Solar/Wind Harmer
0.351
3145823KELFORD
Solar/Wind Harmer
-0.007
3151101ELIZAR3
Adder
6.126
3146206CASHIE
Solar/Wind Harmer
-0.007
315724AD1-057 GEN
Solar/Wind Harmer
0.425
316435W1029_GEN3
Solar/Wind Harmer
1.33
3146516WINFALL
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
315614AA2-178 GEN
Solar/Wind Harmer
0.789
315737AD1-076 GEN
Solar/Wind Harmer
1.39
971157AH1-035 GEN
Solar/Wind Harmer
0.914
316320Y1-086
Solar/Wind Harmer
0.426
316210AC1-098 GEN
Solar/Wind Harmer
1.138
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.879
3145963POPLR C
Solar/Wind Harmer
-0.007
316327AA2-057 GEN
Solar/Wind Harmer
0.701
944581AF1-123 GEN
Solar/Wind Harmer
31.333
944601AF1-125 GEN
Solar/Wind Harmer
30.844
3145933PARMELE
Solar/Wind Harmer
-0.007
966801AG1-551 GEN
Solar/Wind Harmer
0.85
3146233WITAKRS
Solar/Wind Harmer
0.141
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.004
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.632
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3144216WINCHST
Adder
0.213
970917AG2-570 GEN
Solar/Wind Harmer
15.874
316473AC1-191 GEN
Solar/Wind Helper
1.195
316369SG1_INVT
Solar/Wind Harmer
2.73
316315AB2-025 C
Solar/Wind Harmer
0.365
315814AE2-033 C
Solar/Wind Harmer
12.431
972265AH1-717 GEN
Adder
7.812
3151201GRAVEL4
Adder
7.323
3151191GRAVEL3
Adder
7.23
3151211GRAVEL5
Adder
7.23
315833AF1-017_GEN
Solar/Wind Harmer
2.103
316349AD2-085 GEN
Solar/Wind Harmer
0.985
316311AC2-079 GEN
Solar/Wind Harmer
5.558
971445AH1-216 GEN
Solar/Wind Harmer
6.169
946281AF1-292 GEN
Solar/Wind Harmer
0.204
316087AB2-174 GEN
Solar/Wind Harmer
1.242
315652AC1-086 GEN
Solar/Wind Harmer
9.71
315835AF2-110_GEN
Solar/Wind Harmer
1.056
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.003
3137643SOCKMAN
Solar/Wind Harmer
-0.032
965291AG1-394 GEN
Solar/Wind Harmer
0.707
3146043SEABORD
Solar/Wind Harmer
-0.008
315607AA1-063A GEN
Solar/Wind Harmer
0.798
316318V4-068
Solar/Wind Harmer
0.195
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145513AHOSKIE
Solar/Wind Harmer
0.066
961941AG1-037 GEN
Solar/Wind Harmer
0.057
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3152611GOSPORTB
Adder
0.85
3152621GOSPORTC
Adder
0.721
3152601GOSPORTA
Adder
0.665
316305AF2-043 C
Solar/Wind Harmer
0.225
3151081ELIZAR1
Adder
6.048
3151091ELIZAR2
Adder
5.943
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
3.232
3146033SCOT NK
Solar/Wind Harmer
-0.029
315611Z1-036_GEN2
Solar/Wind Harmer
1.809
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315816AE2-034 GEN
Solar/Wind Harmer
0.592
315732AD1-074 GEN1
Solar/Wind Harmer
1.479
315733AD1-074 GEN2
Solar/Wind Harmer
1.479
315735AD1-075 GEN1
Solar/Wind Harmer
0.74
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
316321Z2-027
Solar/Wind Harmer
0.196
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.134
313526AB2-022
Solar/Wind Harmer
0.196
3146406KITTY HAWK
Solar/Wind Harmer
0.006
319010AE1-072 C
Solar/Wind Harmer
1.46
957871AF2-081 GEN
Solar/Wind Harmer
3.604
941031AE2-094 GEN
Solar/Wind Harmer
12.896
944011AF1-069 GEN
Solar/Wind Harmer
4.041
316319Z2-044 C
Solar/Wind Harmer
0.373
970673AG2-436 GEN
Solar/Wind Harmer
14.16
970673AG2-436 GEN
Solar/Wind Harmer
7.17
316005AA1-067
Solar/Wind Harmer
0.135
3145746EVERETS
Solar/Wind Harmer
-0.026
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
970181AG2-120 GEN
Solar/Wind Harmer
0.878
957861AF2-080 GEN
Solar/Wind Harmer
2.915
316420AA1-050 GEN
Solar/Wind Harmer
0.759
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
970831AG2-522 GEN
Solar/Wind Harmer
3.291
971967AH1-528 GEN
Solar/Wind Harmer
12.369
970085AG2-068 GEN
Solar/Wind Harmer
3.953
970581AG2-369 GEN
Solar/Wind Harmer
3.399
LAGNLTFEXP_LAGN->PJM
CLTF
1.785
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.34
TVALTFEXP_TVA->PJM
CLTF
0.887
CPLELTFEXP_CPLE->PJM
CLTF
3.081
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.877
NYPJM->LTFIMP_NY
CLTF
0.472
LGEELTFEXP_LGEE->PJM
CLTF
0.247
WECLTFEXP_WEC->PJM
CLTF
0.126
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.235
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.973
MECLTFEXP_MEC->PJM
CLTF
0.738
SIGELTFEXP_SIGE->PJM
CLTF
0.021

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 552_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:172.64 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:5559.88
MW Contribution:1.71
Bus #Bus NameTypeMW Contribution
3152261N ANNA2
50/50
20.32
3150861SPRUNCD
50/50
1.216
3143096IRON208
50/50
1.078
3143096IRON208
50/50
1.056
3150801HOPHCF4
50/50
1.421
971211AH1-065 GEN
50/50
1.714
3151101ELIZAR3
50/50
23.68
3151161SURRY 1
50/50
9.205
3147666LOUISA
Solar/Wind Harmer
0.591
315839AE2-212 C
Solar/Wind Harmer
0.002
315773AC2-141 GEN
Solar/Wind Harmer
8.876
965281AG1-393 GEN
Solar/Wind Harmer
2.585
315813AE1-149 C
Solar/Wind Harmer
12.873
970133AG2-095 GEN
Solar/Wind Harmer
2.314
944581AF1-123 GEN
Solar/Wind Harmer
54.216
944601AF1-125 GEN
Solar/Wind Harmer
53.381
970129AG2-093 GEN
Solar/Wind Harmer
14.547
315778AD1-151 GEN
Solar/Wind Harmer
19.233
3144536CHRHLND
Solar/Wind Harmer
0.036
3144873MCLAUGH
Solar/Wind Harmer
0.006
970659AG2-427 GEN
Solar/Wind Harmer
2.54
3145336SMITFLD
Solar/Wind Harmer
0.096
316083AB2-161 GEN
Solar/Wind Harmer
0.003
961611AG1-000B GEN
Solar/Wind Harmer
6.396
3151221GRAVEL6
Adder
17.422
3151171GRAVELC
Adder
3.352
970661AG2-428 GEN
Solar/Wind Harmer
5.062
970293AG2-193 GEN
Solar/Wind Harmer
2.548
3142946ENON
Solar/Wind Harmer
0.08
3146456SLIGO L269
Solar/Wind Harmer
0.238
971153AH1-033 GEN
Solar/Wind Harmer
2.749
3142416OLDCHRC
Solar/Wind Harmer
2.305
3144216WINCHST
Adder
0.896
3150921YORKTN3
Adder
5.966
316382AG1-145 C
Solar/Wind Harmer
0.002
316320Y1-086
Solar/Wind Harmer
0.001
316435W1029_GEN3
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.233
3142433PROV 92
Adder
0.451
3142433PROV 92
Adder
0.451
3146626S HERTFORD
Solar/Wind Harmer
0.231
3145273HOLLAND
Solar/Wind Harmer
0.173
316473AC1-191 GEN
Solar/Wind Harmer
0.778
3141843SHACKLE
Adder
1.16
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316313AB2-026
Solar/Wind Harmer
0.143
316258AE1-075 C
Solar/Wind Harmer
0.171
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.429
3146376EDENTON
Solar/Wind Harmer
0.227
3141766HARMONY
Solar/Wind Harmer
3.024
316280AD1-041 GEN
Solar/Wind Harmer
0.005
316156AD2-030 GEN
Solar/Wind Harmer
0.167
3141873WAN 176
Solar/Wind Harmer
4.011
970917AG2-570 GEN
Solar/Wind Harmer
20.009
315614AA2-178 GEN
Solar/Wind Harmer
1.271
971157AH1-035 GEN
Solar/Wind Harmer
2.623
3156081AA2-088 GEN
Solar/Wind Harmer
0.005
316365GEN2_N
Solar/Wind Harmer
0.489
315737AD1-076 GEN
Solar/Wind Harmer
2.804
3150401LDYSMT4
Adder
29.156
3150371LDYSMT1
Adder
28.172
962971AG1-146 GEN
Solar/Wind Harmer
3.461
3146206CASHIE
Solar/Wind Harmer
0.216
3145893MURPHYS
Solar/Wind Harmer
0.361
3145893MURPHYS
Solar/Wind Harmer
0.215
957521AF2-046 GEN
Solar/Wind Harmer
15.996
961681AG1-008 GEN
Solar/Wind Harmer
15.996
970009AG2-005 GEN
Solar/Wind Harmer
1.599
3146173TUNIS
Solar/Wind Harmer
0.213
3156021HOLLOMANSOL
Solar/Wind Harmer
0.967
316463AE2-346 GEN
Solar/Wind Harmer
0.183
316140AB2-099
Solar/Wind Harmer
0.076
962331AG1-082 GEN
Solar/Wind Harmer
2.268
316404AE1-155 C
Solar/Wind Harmer
0.047
3146263WOODLND
Solar/Wind Harmer
0.21
313506AB2-031 GEN
Solar/Wind Harmer
0.649
3142666NORTHAMPTON
Solar/Wind Harmer
0.209
3145963POPLR C
Solar/Wind Harmer
0.208
316317KELFORD C
Solar/Wind Harmer
0.02
3145823KELFORD
Solar/Wind Harmer
0.208
316478AD1-087 GEN
Solar/Wind Harmer
0.721
316486AD2-202 GEN
Solar/Wind Harmer
0.212
3147043LAWRENC
Solar/Wind Harmer
0.124
3145796HORNRTN
Solar/Wind Harmer
0.822
3145796HORNRTN
Solar/Wind Harmer
0.206
3150351NORNECKC2
Adder
2.075
316210AC1-098 GEN
Solar/Wind Harmer
1.861
3145933PARMELE
Solar/Wind Harmer
0.2
966801AG1-551 GEN
Solar/Wind Harmer
2.326
971781AH1-399 GEN
Solar/Wind Harmer
0.26
970909AG2-566 GEN
Solar/Wind Harmer
2.105
3145746EVERETS
Solar/Wind Harmer
0.196
3145746EVERETS
Solar/Wind Harmer
0.196
315724AD1-057 GEN
Solar/Wind Harmer
0.733
316327AA2-057 GEN
Solar/Wind Harmer
0.292
316131AB2-060 GEN
Solar/Wind Harmer
0.604
964241AG1-285 GEN
Solar/Wind Harmer
12.793
315785AD2-033 C
Solar/Wind Harmer
1.556
970257AG2-171 GEN
Solar/Wind Harmer
6.117
959311AF2-222 GEN
Solar/Wind Harmer
16.978
3146233WITAKRS
Solar/Wind Harmer
0.955
3146233WITAKRS
Solar/Wind Harmer
0.129
3146073TAR RVR
Solar/Wind Harmer
0.19
3146083TARBORO
Solar/Wind Harmer
0.19
963181AG1-167 GEN
Solar/Wind Harmer
0.761
3144293JTRSVLE
Adder
0.605
3138543CONSLDL
Solar/Wind Harmer
0.125
3147133PAMPLIN
Solar/Wind Harmer
0.596
971193AH1-056 GEN
Solar/Wind Harmer
11.558
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146926FARMVIL
Solar/Wind Harmer
0.113
961601AG1-000A GEN
Solar/Wind Harmer
13.299
3145543BTLEBRO
Solar/Wind Harmer
0.187
3145543BTLEBRO
Solar/Wind Harmer
0.187
971623AH1-311 GEN
Solar/Wind Harmer
0.374
3141906WESTMOR
Solar/Wind Harmer
0.074
3146776BUCKING
Solar/Wind Harmer
0.064
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
7.491
970737AG2-469 GEN
Solar/Wind Harmer
7.435
971683AH1-343 GEN
Solar/Wind Harmer
5.965
316283AC2-100 C
Solar/Wind Harmer
0.31
970221AG2-151 GEN
Solar/Wind Harmer
8.416
972255AH1-712 GEN
Adder
74.962
3151761LOISA E
Adder
17.688
972183AH1-676 GEN
Adder
136.298
3141316ARNOLDS
Adder
0.29
316044AC1-158 PL1
Solar/Wind Helper
5.216
316450AC1-158 RIC
Solar/Wind Helper
1.391
3141196NOKESVL
Solar/Wind Helper
1.131
971133AH1-012 GEN
50/50
5.491
944641AF1-129 GEN
50/50
122.767
970533AG2-339 GEN
50/50
21.564
970531AG2-338 GEN
50/50
8.626
3142366NRTHEST
50/50
0.836
3150781HOPHCF2
50/50
0.977
3150791HOPHCF3
50/50
0.977
3150761HOPPOLC
50/50
0.62
971213AH1-066 GEN
50/50
0.857
971223AH1-071 GEN
Solar/Wind Harmer
2.834
3143526WINTERP
Solar/Wind Harmer
1.342
316240AF1-291 C
Solar/Wind Harmer
0.002
3150691DARBY 3
Adder
17.296
3150701DARBY 4
Adder
17.255
3150681DARBY 2
Adder
17.235
3150671DARBY 1
Adder
17.215
316036AC1-147 C
Solar/Wind Harmer
0.045
3150991CHESPKB
Adder
2.516
3150991CHESPKB
Adder
2.456
316033AB2-134 GEN
Solar/Wind Harmer
0.014
315697AD1-025 GEN
Solar/Wind Harmer
0.27
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.23
316236AE1-162_GEN
Solar/Wind Harmer
0.002
316185AD1-033 GEN
Solar/Wind Harmer
0.007
970657AG2-426 GEN
Solar/Wind Harmer
8.395
970657AG2-426 GEN
Solar/Wind Harmer
1.76
3142296MT RD221
Adder
0.763
3145506HICKORY
Solar/Wind Harmer
0.957
3145506HICKORY
Solar/Wind Harmer
0.574
3145506HICKORY
Solar/Wind Harmer
0.144
3142946ENON
Solar/Wind Harmer
0.024
316339AD2-160 GEN
Solar/Wind Harmer
0.387
316018AA1-139 ULT2
Solar/Wind Harmer
0.006
316017AA1-139 ULT1
Solar/Wind Harmer
0.133
3137176SLIGO L2192
Solar/Wind Harmer
0.946
3146456SLIGO L269
Solar/Wind Harmer
4.208
3130086AYDLETT
Solar/Wind Harmer
0.95
316075AC2-137 C
Solar/Wind Harmer
0.065
972185AH1-677 GEN
Adder
13.26
3144356SAPONY
Solar/Wind Harmer
1.973
3146386ELIZ CT
Solar/Wind Harmer
0.235
972187AH1-678 GEN
Adder
6.65
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.233
3146516WINFALL
Solar/Wind Harmer
0.233
3146516WINFALL
Solar/Wind Harmer
0.233
3146626S HERTFORD
Solar/Wind Harmer
0.231
3146626S HERTFORD
Solar/Wind Harmer
0.231
966871AG1-558 GEN
Solar/Wind Harmer
0.266
970933AG2-581 GEN
Solar/Wind Harmer
18.37
315742AE1-103 GEN
Solar/Wind Harmer
0.003
3146376EDENTON
Solar/Wind Harmer
1.008
3146376EDENTON
Solar/Wind Harmer
1.008
957411AF2-035 GEN
Solar/Wind Harmer
9.597
970317AG2-208 GEN
Solar/Wind Harmer
8.892
315673AE1-157 GEN
Solar/Wind Harmer
15.364
3150391LDYSMT3
Adder
29.101
972195AH1-682 GEN
Adder
3.824
316065AD1-022 GEN
Solar/Wind Harmer
9.976
3145893MURPHYS
Solar/Wind Harmer
1.442
3145893MURPHYS
Solar/Wind Harmer
0.388
970099AG2-077 GEN
Solar/Wind Harmer
22.899
3146173TUNIS
Solar/Wind Harmer
0.213
3146173TUNIS
Solar/Wind Harmer
0.213
958261AF2-120 GEN
Solar/Wind Harmer
6.97
316181AB2-040 GEN
Solar/Wind Harmer
0.305
3142666NORTHAMPTON
Solar/Wind Harmer
0.209
3142666NORTHAMPTON
Solar/Wind Harmer
0.209
3142666NORTHAMPTON
Solar/Wind Harmer
0.209
3142666NORTHAMPTON
Solar/Wind Harmer
0.126
316426AA2-053 GEN
Solar/Wind Harmer
0.702
3145593CAROLNA
Solar/Wind Harmer
0.207
3145593CAROLNA
Solar/Wind Harmer
0.207
966811AG1-552 GEN
Solar/Wind Harmer
2.246
3145593CAROLNA
Solar/Wind Harmer
0.258
3145783HORNRTN
Solar/Wind Harmer
3.66
3145783HORNRTN
Solar/Wind Harmer
2.928
3145783HORNRTN
Solar/Wind Harmer
0.915
3145783HORNRTN
Solar/Wind Harmer
0.366
3145796HORNRTN
Solar/Wind Harmer
0.617
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
2.143
3150341NORNECKC1
Adder
2.126
971741AH1-377 GEN
Solar/Wind Harmer
19.869
3145933PARMELE
Solar/Wind Harmer
0.399
3145933PARMELE
Solar/Wind Harmer
0.2
316274AC1-208 GEN
Solar/Wind Harmer
1.034
316468AD1-105 GEN
Solar/Wind Harmer
-0.064
970301AG2-198 GEN
Solar/Wind Harmer
8.419
939181AE1-148 GEN
Solar/Wind Harmer
9.29
313527AB2-043 GEN
Solar/Wind Harmer
0.002
316034AC1-036 C
Solar/Wind Harmer
0.014
970323AG2-213 GEN
Solar/Wind Harmer
8.155
971775AH1-396 GEN
Solar/Wind Harmer
0.306
3145493TOT1
Solar/Wind Harmer
0.441
3145453TOT5
Solar/Wind Harmer
0.264
3145603CNETO
Solar/Wind Harmer
0.176
958211AF2-115 GEN
Solar/Wind Harmer
2.282
963191AG1-168 GEN
Solar/Wind Harmer
0.761
3144293JTRSVLE
Adder
0.605
3144293JTRSVLE
Adder
0.51
3147133PAMPLIN
Solar/Wind Harmer
0.19
3147133PAMPLIN
Solar/Wind Harmer
0.152
961601AG1-000A GEN
Solar/Wind Harmer
3.325
316263AC1-034 GEN
Solar/Wind Harmer
7.104
962561AG1-105 GEN
Solar/Wind Harmer
8.835
964791AG1-342 GEN
Solar/Wind Harmer
3.505
3146843MT LREL
Solar/Wind Harmer
0.182
3146843MT LREL
Solar/Wind Harmer
0.182
3146776BUCKING
Solar/Wind Harmer
0.716
3146776BUCKING
Solar/Wind Harmer
0.058
316222AC1-221 GEN
Solar/Wind Harmer
0.661
971489AH1-241 GEN
Solar/Wind Harmer
8.416
315821AE2-092 GEN
Solar/Wind Harmer
0.008
942751AE2-291 GEN
Solar/Wind Harmer
7.289
3151731LOISA B
Adder
8.676
3151721LOISA A
Adder
8.631
316447AC1-158 HLD
Solar/Wind Helper
11.481
316303AF2-085
50/50
4.723
971285AH1-108 GEN
50/50
1.99
970603AG2-384 GEN
50/50
5.178
972263AH1-716 GEN
50/50
139.063
316233AE1-074 FULL
Solar/Wind Harmer
0.207
971281AH1-106 GEN
Solar/Wind Harmer
3.58
971283AH1-107 GEN
Solar/Wind Harmer
3.58
3143316POE
Solar/Wind Harmer
0.964
941031AE2-094 GEN
Solar/Wind Harmer
44.68
944011AF1-069 GEN
Solar/Wind Harmer
14.599
316132AB2-190 GEN1
Solar/Wind Harmer
1.291
3151081ELIZAR1
Adder
22.034
3151091ELIZAR2
Adder
21.652
3152611GOSPORTB
Adder
3.059
3152621GOSPORTC
Adder
2.596
3152601GOSPORTA
Adder
2.395
316369SG1_INVT
Solar/Wind Harmer
0.009
971445AH1-216 GEN
Solar/Wind Harmer
16.89
972265AH1-717 GEN
Adder
18.606
3151201GRAVEL4
Adder
17.442
3151191GRAVEL3
Adder
17.221
3151211GRAVEL5
Adder
17.221
970673AG2-436 GEN
Solar/Wind Harmer
50.858
970673AG2-436 GEN
Solar/Wind Harmer
33.905
957871AF2-081 GEN
Solar/Wind Harmer
11.862
316312AB1-027
Solar/Wind Harmer
0.425
319010AE1-072 C
Solar/Wind Harmer
1.197
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.163
316311AC2-079 GEN
Solar/Wind Harmer
6.823
3146406KITTY HAWK
Solar/Wind Harmer
0.03
316305AF2-043 C
Solar/Wind Harmer
0.002
315835AF2-110_GEN
Solar/Wind Harmer
1.621
316315AB2-025 C
Solar/Wind Harmer
0.191
315976AC1-164 GENA
Solar/Wind Harmer
24.444
316169AC1-164_GENC
Solar/Wind Harmer
21.117
315975AC1-164 GENB
Solar/Wind Harmer
0.723
313526AB2-022
Solar/Wind Harmer
0.128
971967AH1-528 GEN
Solar/Wind Harmer
37.658
315814AE2-033 C
Solar/Wind Harmer
18.587
3146486SUNBURY
Solar/Wind Harmer
0.235
3146486SUNBURY
Solar/Wind Harmer
0.235
316321Z2-027
Solar/Wind Harmer
0.044
3146396TANGLEW
Solar/Wind Harmer
0.646
3145176PASQUOTANK
Solar/Wind Harmer
0.145
972189AH1-679 GEN
Adder
3.913
971167AH1-042 GEN
Solar/Wind Harmer
20.686
3142433PROV 92
Adder
0.451
3142433PROV 92
Adder
0.451
3138283WHITEMARSH
Solar/Wind Harmer
0.054
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
3143873LANEXA
Solar/Wind Harmer
0.137
316314AB2-024 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
6.729
3130156CHOWAN
Solar/Wind Harmer
0.227
3130156CHOWAN
Solar/Wind Harmer
0.227
316059AD1-063 C
Solar/Wind Harmer
0.001
315662AE1-191 GEN
Solar/Wind Harmer
0.007
315666AE1-190 GEN
Solar/Wind Harmer
0.002
3141873WAN 176
Solar/Wind Harmer
0.045
970085AG2-068 GEN
Solar/Wind Harmer
11.956
970581AG2-369 GEN
Solar/Wind Harmer
10.282
3141913WHIT STONE
Solar/Wind Harmer
0.222
315816AE2-034 GEN
Solar/Wind Harmer
0.953
3138133OCRAN
Solar/Wind Harmer
0.066
3141783LANCAST
Solar/Wind Harmer
0.132
3141783LANCAST
Solar/Wind Harmer
0.088
3130546PLYMOUTH
Solar/Wind Harmer
0.218
315732AD1-074 GEN1
Solar/Wind Harmer
1.252
315733AD1-074 GEN2
Solar/Wind Harmer
1.252
315735AD1-075 GEN1
Solar/Wind Harmer
0.627
965291AG1-394 GEN
Solar/Wind Harmer
0.966
3150411LDYSMT5
Adder
29.247
3150381LDYSMT2
Adder
27.99
972213AH1-691 GEN
Adder
4.735
972215AH1-692 GEN
Adder
4.735
962981AG1-147 GEN
Solar/Wind Harmer
8.075
3146206CASHIE
Solar/Wind Harmer
0.216
970601AG2-382 GEN
Solar/Wind Harmer
8.061
3145893MURPHYS
Solar/Wind Harmer
0.582
3145893MURPHYS
Solar/Wind Harmer
0.215
970327AG2-215 GEN
Solar/Wind Harmer
7.029
3145513AHOSKIE
Solar/Wind Harmer
0.444
3145513AHOSKIE
Solar/Wind Harmer
0.212
3146043SEABORD
Solar/Wind Harmer
0.212
3145683EARLEYS
Solar/Wind Harmer
0.423
3145683EARLEYS
Solar/Wind Harmer
0.211
3145683EARLEYS
Solar/Wind Harmer
0.211
315607AA1-063A GEN
Solar/Wind Harmer
0.431
316087AB2-174 GEN
Solar/Wind Harmer
0.006
315652AC1-086 GEN
Solar/Wind Harmer
22.967
3137643SOCKMAN
Solar/Wind Harmer
0.832
3145796HORNRTN
Solar/Wind Harmer
0.658
3145796HORNRTN
Solar/Wind Harmer
0.082
3141813NORNECK
Solar/Wind Harmer
0.205
3146033SCOT NK
Solar/Wind Harmer
0.815
970831AG2-522 GEN
Solar/Wind Harmer
8.503
316005AA1-067
Solar/Wind Harmer
0.21
3145746EVERETS
Solar/Wind Harmer
0.779
3145746EVERETS
Solar/Wind Harmer
0.196
3145746EVERETS
Solar/Wind Harmer
0.196
3145746EVERETS
Solar/Wind Harmer
0.196
970181AG2-120 GEN
Solar/Wind Harmer
2.436
957861AF2-080 GEN
Solar/Wind Harmer
8.31
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316420AA1-050 GEN
Solar/Wind Harmer
0.006
971443AH1-215 GEN
Solar/Wind Harmer
3.212
3144303KENBRDG
Solar/Wind Harmer
0.153
970683AG2-441 GEN
Solar/Wind Harmer
12.709
970681AG2-440 GEN
Solar/Wind Harmer
10.167
316319Z2-044 C
Solar/Wind Harmer
0
3145573BETHELC
Solar/Wind Harmer
0.19
3145573BETHELC
Solar/Wind Harmer
0.19
946301AF1-294 GEN
Solar/Wind Harmer
3.752
961791AG1-021 GEN
Solar/Wind Harmer
1.825
315657AE1-056 GEN
Solar/Wind Harmer
6.547
316223AC1-118
Solar/Wind Harmer
0.132
970285AG2-188 GEN
Solar/Wind Harmer
14.341
971845AH1-439 GEN
Solar/Wind Harmer
8.154
316118AC1-105 GEN
Solar/Wind Harmer
0.462
3147173SINAI
Solar/Wind Harmer
0.175
3147243WELCO
Solar/Wind Harmer
0.11
972205AH1-687 GEN
Adder
7.204
944491AF1-114 GEN
Solar/Wind Harmer
0.001
970865AG2-541 GEN
Solar/Wind Harmer
5.394
971447AH1-217 GEN
Solar/Wind Harmer
4.654
972193AH1-681 GEN
Adder
3.349
316123AC1-075 GEN
Solar/Wind Harmer
0.195
970165AG2-112 GEN
Solar/Wind Harmer
1.154
970163AG2-111 GEN
Solar/Wind Harmer
1.101
270494AE1-108_GEN
Solar/Wind Harmer
1.672
3147346CASHSCORNER
Solar/Wind Harmer
0.293
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316164AC1-076 GEN
Solar/Wind Helper
1.38
316411AF1-147_GEN1
Solar/Wind Helper
0.79
316415AF1-147_GEN2
Solar/Wind Helper
0.79
3138216PACIFIC
Solar/Wind Helper
0.038
3152251N ANNA1
50/50
20.321
970119AG2-088 GEN
50/50
35.422
3150851SPRUNCC
50/50
1.216
3143096IRON208
50/50
1.078
3152331SURRY 2
50/50
9.99
3150771HOPHCF1
50/50
0.977
3143226MDLTHAN
Solar/Wind Harmer
0.265
3143526WINTERP
Solar/Wind Harmer
1.342
3147666LOUISA
Solar/Wind Harmer
1.028
316192AB2-158 GEN
Solar/Wind Harmer
1.415
940641AE2-051 GEN
Solar/Wind Harmer
19.964
939411AE1-173 GEN
Solar/Wind Harmer
105.426
3142543TWELFTH
Solar/Wind Harmer
0.023
316294AC1-161 GEN
Solar/Wind Harmer
4.211
315671AE2-027_GEN
Solar/Wind Harmer
15.496
944591AF1-124 GEN
Solar/Wind Harmer
54.408
970129AG2-093 GEN
Solar/Wind Harmer
6.846
316458AB2-190 GEN2
Solar/Wind Harmer
1.291
971069AG2-661 GEN
Solar/Wind Harmer
4.274
316375AC2-012 GEN
Solar/Wind Harmer
0.006
3150981CHESPKA
Adder
3
970659AG2-427 GEN
Solar/Wind Harmer
11.613
971647AH1-324 GEN
Solar/Wind Harmer
10.242
3145336SMITFLD
Solar/Wind Harmer
0.959
316381AD1-082 GEN
Solar/Wind Harmer
0.25
944631AF1-128 GEN
Adder
114.357
961611AG1-000B GEN
Solar/Wind Harmer
12.579
3151171GRAVELC
Adder
2.549
970661AG2-428 GEN
Solar/Wind Harmer
23.801
316388AE2-253 GEN
Solar/Wind Harmer
0.747
3146456SLIGO L269
Solar/Wind Harmer
0.238
3142416OLDCHRC
Solar/Wind Harmer
0.618
3142416OLDCHRC
Solar/Wind Harmer
0.237
316072AD1-144
Solar/Wind Harmer
0.086
3138126ROCKLANDING
Solar/Wind Harmer
0.109
316246AF1-032 C
Solar/Wind Harmer
0.107
316159AE1-175 C
Solar/Wind Harmer
0.205
316093AE2-104_GEN
Solar/Wind Harmer
3.974
971317AH1-138 GEN
Solar/Wind Harmer
1.762
3146516WINFALL
Solar/Wind Harmer
0.754
3146516WINFALL
Solar/Wind Harmer
0.233
3142433PROV 92
Solar/Wind Harmer
0.928
3142433PROV 92
Adder
0.451
3142433PROV 92
Adder
0.451
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
971777AH1-397 GEN
Solar/Wind Harmer
0.6
3141843SHACKLE
Adder
1.16
3143336POWHATN
Solar/Wind Harmer
4.034
3130156CHOWAN
Solar/Wind Harmer
0.227
3141766HARMONY
Solar/Wind Harmer
0.045
970919AG2-571 GEN
Solar/Wind Harmer
8.004
966881AG1-559 GEN
Solar/Wind Harmer
0.26
970087AG2-069 GEN
Solar/Wind Harmer
17.934
3145663CRESWEL
Solar/Wind Harmer
0.622
971163AH1-040 GEN
Solar/Wind Harmer
17.772
3138133OCRAN
Solar/Wind Harmer
0.133
316023GEN1_S
Solar/Wind Harmer
0.489
972197AH1-683 GEN
Adder
4.553
972219AH1-694 GEN
Adder
3.278
316336AC2-165 C
Solar/Wind Harmer
0.008
3146206CASHIE
Solar/Wind Harmer
0.216
971547AH1-271 GEN
Solar/Wind Harmer
4.607
3145893MURPHYS
Solar/Wind Harmer
0.862
3145893MURPHYS
Solar/Wind Harmer
0.958
957481AF2-042 GEN
Solar/Wind Harmer
57.247
3146173TUNIS
Solar/Wind Harmer
0.213
960081AF2-299 GEN
Solar/Wind Harmer
2.041
962861AG1-135 GEN
Solar/Wind Harmer
6.774
3145683EARLEYS
Solar/Wind Harmer
0.211
3146263WOODLND
Solar/Wind Harmer
0.21
315693AD1-088 GEN
Solar/Wind Harmer
10.091
962491AG1-098 GEN
Solar/Wind Harmer
11.959
316011AB1-132 GEN
Solar/Wind Harmer
3.796
962571AG1-106 GEN
Solar/Wind Harmer
2.971
971795AH1-408 GEN
Solar/Wind Harmer
13.893
3145963POPLR C
Solar/Wind Harmer
0.208
316190AA2-174 GEN
Solar/Wind Harmer
0
3145823KELFORD
Solar/Wind Harmer
0.208
3141726DUNNSVL
Solar/Wind Harmer
0.83
316174AB2-169 GEN
Solar/Wind Harmer
0.006
3147043LAWRENC
Adder
1.868
3145783HORNRTN
Solar/Wind Harmer
0.206
3145796HORNRTN
Solar/Wind Harmer
0.678
3145796HORNRTN
Solar/Wind Harmer
0.206
3150351NORNECKC2
Adder
2.04
316212AC1-099_GEN
Solar/Wind Harmer
1.038
3146293MARTNCO
Solar/Wind Harmer
0.185
316129AC1-054 GEN
Solar/Wind Harmer
0.746
971065AG2-659 GEN
Solar/Wind Harmer
8.434
3145746EVERETS
Solar/Wind Harmer
0.196
3145746EVERETS
Solar/Wind Harmer
0.196
315722AD1-056 GEN
Solar/Wind Harmer
1.237
316337AD2-073 GEN
Solar/Wind Harmer
0.169
315687AD1-152 GEN
Solar/Wind Harmer
0.006
316494AC1-189 GEN
Solar/Wind Harmer
0.651
316237AB2-079_GEN
Solar/Wind Harmer
0.002
970937AG2-583 GEN
Solar/Wind Harmer
11.696
970685AG2-442 GEN
Solar/Wind Harmer
14.234
3146233WITAKRS
Solar/Wind Harmer
0.757
961671AG1-007 GEN
Solar/Wind Harmer
0.029
3146083TARBORO
Solar/Wind Harmer
0.19
3145493TOT1
Solar/Wind Harmer
0.845
963171AG1-166 GEN
Solar/Wind Harmer
1.014
971563AH1-280 GEN
Solar/Wind Harmer
2.028
3144293JTRSVLE
Adder
0.605
3146926FARMVIL
Solar/Wind Harmer
0.113
3145543BTLEBRO
Solar/Wind Harmer
0.187
3145543BTLEBRO
Solar/Wind Harmer
0.149
316359AB2-059 GEN
Solar/Wind Harmer
0.672
316049AB1-081 GEN
Solar/Wind Harmer
1.07
3142053HEARTS
Solar/Wind Harmer
0.329
970401AG2-262 GEN
Solar/Wind Harmer
1.071
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.072
972003AH1-546 GEN
Solar/Wind Harmer
7.247
316003AC1-222 GEN
Solar/Wind Harmer
0.004
972135AH1-637 GEN
Solar/Wind Harmer
1.431
971377AH1-170 GEN
Solar/Wind Harmer
1.683
3147623JAMES R
Solar/Wind Harmer
0.366
972277AH1-723 GEN
Adder
87.353
3151751LOISA D
Adder
8.676
970223AG2-152 GEN
Solar/Wind Harmer
7.908
316045AC1-158 PL2
Solar/Wind Helper
16.699
316006AB2-029 C
Solar/Wind Helper
0.14
LAGNLTFEXP_LAGN->PJM
CLTF
8.398
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.505
TVALTFEXP_TVA->PJM
CLTF
4.252
CPLELTFEXP_CPLE->PJM
CLTF
12.136
CBM West 2LTFEXP_CBM-W2->PJM
CBM
43.163
NYPJM->LTFIMP_NY
CLTF
3.266
LGEELTFEXP_LGEE->PJM
CLTF
1.371
WECLTFEXP_WEC->PJM
CLTF
0.662
CBM West 1LTFEXP_CBM-W1->PJM
CBM
22.027
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.441
MECLTFEXP_MEC->PJM
CLTF
3.751
SIGELTFEXP_SIGE->PJM
CLTF
0.114

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 581_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:171.66 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:5528.27
MW Contribution:1.75
Bus #Bus NameTypeMW Contribution
3152261N ANNA2
50/50
20.433
3150861SPRUNCD
50/50
1.238
3143096IRON208
50/50
1.099
3143096IRON208
50/50
1.077
3150801HOPHCF4
50/50
1.448
971211AH1-065 GEN
50/50
1.746
3151161SURRY 1
50/50
9.371
3147666LOUISA
Solar/Wind Harmer
0.585
315839AE2-212 C
Solar/Wind Harmer
0.002
315773AC2-141 GEN
Solar/Wind Harmer
9.03
965281AG1-393 GEN
Solar/Wind Harmer
2.631
315813AE1-149 C
Solar/Wind Harmer
13.098
970133AG2-095 GEN
Solar/Wind Harmer
2.358
970129AG2-093 GEN
Solar/Wind Harmer
14.818
944581AF1-123 GEN
Solar/Wind Harmer
55.15
944601AF1-125 GEN
Solar/Wind Harmer
54.301
315778AD1-151 GEN
Solar/Wind Harmer
19.588
3151101ELIZAR3
Adder
22.703
3144536CHRHLND
Solar/Wind Harmer
0.037
3144873MCLAUGH
Solar/Wind Harmer
0.006
970659AG2-427 GEN
Solar/Wind Harmer
2.585
3145336SMITFLD
Solar/Wind Harmer
0.098
961611AG1-000B GEN
Solar/Wind Harmer
6.513
316083AB2-161 GEN
Solar/Wind Harmer
0.003
3151221GRAVEL6
Adder
17.737
3151171GRAVELC
Adder
3.413
970293AG2-193 GEN
Solar/Wind Harmer
2.6
3142946ENON
Solar/Wind Harmer
0.081
970661AG2-428 GEN
Solar/Wind Harmer
5.15
3142416OLDCHRC
Solar/Wind Harmer
2.354
3144216WINCHST
Adder
0.913
971133AH1-012 GEN
50/50
5.467
944641AF1-129 GEN
50/50
125.042
3142366NRTHEST
50/50
0.853
970533AG2-339 GEN
50/50
21.877
970531AG2-338 GEN
50/50
8.751
3150781HOPHCF2
50/50
0.996
3150791HOPHCF3
50/50
0.996
3150761HOPPOLC
50/50
0.631
971213AH1-066 GEN
50/50
0.873
3150691DARBY 3
50/50
18.729
3150701DARBY 4
50/50
18.685
971223AH1-071 GEN
Solar/Wind Harmer
2.875
3143526WINTERP
Solar/Wind Harmer
1.363
316240AF1-291 C
Solar/Wind Harmer
0.002
3150681DARBY 2
Adder
17.588
3150671DARBY 1
Adder
17.568
3142296MT RD221
Adder
0.779
316033AB2-134 GEN
Solar/Wind Harmer
0.014
315697AD1-025 GEN
Solar/Wind Harmer
0.275
316036AC1-147 C
Solar/Wind Harmer
0.045
3150991CHESPKB
Adder
2.56
3150991CHESPKB
Adder
2.499
316236AE1-162_GEN
Solar/Wind Harmer
0.002
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.234
316185AD1-033 GEN
Solar/Wind Harmer
0.007
970657AG2-426 GEN
Solar/Wind Harmer
8.541
970657AG2-426 GEN
Solar/Wind Harmer
1.79
3142946ENON
Solar/Wind Harmer
0.024
3145506HICKORY
Solar/Wind Harmer
0.973
3145506HICKORY
Solar/Wind Harmer
0.584
3145506HICKORY
Solar/Wind Harmer
0.146
316339AD2-160 GEN
Solar/Wind Harmer
0.393
316018AA1-139 ULT2
Solar/Wind Harmer
0.006
316017AA1-139 ULT1
Solar/Wind Harmer
0.135
316075AC2-137 C
Solar/Wind Harmer
0.066
3137176SLIGO L2192
Solar/Wind Harmer
0.963
3146456SLIGO L269
Solar/Wind Harmer
4.28
3130086AYDLETT
Solar/Wind Harmer
0.966
972185AH1-677 GEN
Adder
13.452
3144356SAPONY
Solar/Wind Harmer
2.004
3146386ELIZ CT
Solar/Wind Harmer
0.239
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
972187AH1-678 GEN
Adder
6.746
3146516WINFALL
Solar/Wind Harmer
0.236
3146516WINFALL
Solar/Wind Harmer
0.236
3146516WINFALL
Solar/Wind Harmer
0.236
966871AG1-558 GEN
Solar/Wind Harmer
0.272
3146626S HERTFORD
Solar/Wind Harmer
0.235
3146626S HERTFORD
Solar/Wind Harmer
0.235
970933AG2-581 GEN
Solar/Wind Harmer
18.633
315742AE1-103 GEN
Solar/Wind Harmer
0.003
957411AF2-035 GEN
Solar/Wind Harmer
9.864
970317AG2-208 GEN
Solar/Wind Harmer
9.139
3146376EDENTON
Solar/Wind Harmer
1.025
3146376EDENTON
Solar/Wind Harmer
1.025
315673AE1-157 GEN
Solar/Wind Harmer
15.809
3150391LDYSMT3
Adder
30.003
972195AH1-682 GEN
Adder
3.943
316065AD1-022 GEN
Solar/Wind Harmer
10.141
3145893MURPHYS
Solar/Wind Harmer
1.466
3145893MURPHYS
Solar/Wind Harmer
0.394
970099AG2-077 GEN
Solar/Wind Harmer
23.222
3146173TUNIS
Solar/Wind Harmer
0.217
3146173TUNIS
Solar/Wind Harmer
0.217
958261AF2-120 GEN
Solar/Wind Harmer
7.118
316181AB2-040 GEN
Solar/Wind Harmer
0.309
316303AF2-085
50/50
4.791
971285AH1-108 GEN
50/50
2.026
970603AG2-384 GEN
50/50
5.274
316233AE1-074 FULL
Solar/Wind Harmer
0.21
971281AH1-106 GEN
Solar/Wind Harmer
3.638
971283AH1-107 GEN
Solar/Wind Harmer
3.638
3143316POE
Solar/Wind Harmer
0.98
941031AE2-094 GEN
Solar/Wind Harmer
45.33
944011AF1-069 GEN
Solar/Wind Harmer
14.811
3152251N ANNA1
50/50
20.435
970119AG2-088 GEN
50/50
35.934
3150851SPRUNCC
50/50
1.238
3143096IRON208
50/50
1.099
3152331SURRY 2
50/50
10.173
3150771HOPHCF1
50/50
0.996
3143226MDLTHAN
Solar/Wind Harmer
0.269
3143526WINTERP
Solar/Wind Harmer
1.363
3147666LOUISA
Solar/Wind Harmer
1.017
940641AE2-051 GEN
Solar/Wind Harmer
20.264
939411AE1-173 GEN
Solar/Wind Harmer
107.071
3142543TWELFTH
Solar/Wind Harmer
0.024
316192AB2-158 GEN
Solar/Wind Harmer
1.397
316294AC1-161 GEN
Solar/Wind Harmer
4.284
315671AE2-027_GEN
Solar/Wind Harmer
15.779
970129AG2-093 GEN
Solar/Wind Harmer
6.973
316458AB2-190 GEN2
Solar/Wind Harmer
1.315
944591AF1-124 GEN
Solar/Wind Harmer
55.346
971069AG2-661 GEN
Solar/Wind Harmer
4.353
944631AF1-128 GEN
Adder
116.602
316375AC2-012 GEN
Solar/Wind Harmer
0.006
3150981CHESPKA
Adder
3.052
971647AH1-324 GEN
Solar/Wind Harmer
10.43
970659AG2-427 GEN
Solar/Wind Harmer
11.815
3145336SMITFLD
Solar/Wind Harmer
0.976
961611AG1-000B GEN
Solar/Wind Harmer
12.808
316381AD1-082 GEN
Solar/Wind Harmer
0.254
3151171GRAVELC
Adder
2.595
970661AG2-428 GEN
Solar/Wind Harmer
24.214
3142416OLDCHRC
Solar/Wind Harmer
0.631
3142416OLDCHRC
Solar/Wind Harmer
0.242
316388AE2-253 GEN
Solar/Wind Harmer
0.76
3138126ROCKLANDING
Solar/Wind Harmer
0.111
3146456SLIGO L269
Solar/Wind Harmer
0.242
316072AD1-144
Solar/Wind Harmer
0.088
316159AE1-175 C
Solar/Wind Harmer
0.209
316246AF1-032 C
Solar/Wind Harmer
0.109
971317AH1-138 GEN
Solar/Wind Harmer
1.796
316093AE2-104_GEN
Solar/Wind Harmer
4.042
3142433PROV 92
Solar/Wind Harmer
0.947
3142433PROV 92
Adder
0.46
3142433PROV 92
Adder
0.46
3146516WINFALL
Solar/Wind Harmer
0.766
3146516WINFALL
Solar/Wind Harmer
0.236
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
971777AH1-397 GEN
Solar/Wind Harmer
0.612
3141843SHACKLE
Adder
1.184
3141766HARMONY
Solar/Wind Harmer
0.046
966881AG1-559 GEN
Solar/Wind Harmer
0.267
3130156CHOWAN
Solar/Wind Harmer
0.23
3143336POWHATN
Solar/Wind Harmer
4.084
970919AG2-571 GEN
Solar/Wind Harmer
8.12
970087AG2-069 GEN
Solar/Wind Harmer
18.195
3138133OCRAN
Solar/Wind Harmer
0.136
316132AB2-190 GEN1
Solar/Wind Harmer
1.315
316369SG1_INVT
Solar/Wind Harmer
0.009
3151081ELIZAR1
Adder
22.416
3151091ELIZAR2
Adder
22.027
3152611GOSPORTB
Adder
3.112
3152621GOSPORTC
Adder
2.641
3152601GOSPORTA
Adder
2.437
971445AH1-216 GEN
Solar/Wind Harmer
17.191
972265AH1-717 GEN
Adder
18.943
3151201GRAVEL4
Adder
17.758
3151191GRAVEL3
Adder
17.533
3151211GRAVEL5
Adder
17.533
316312AB1-027
Solar/Wind Harmer
0.435
957871AF2-081 GEN
Solar/Wind Harmer
12.066
970673AG2-436 GEN
Solar/Wind Harmer
51.597
970673AG2-436 GEN
Solar/Wind Harmer
34.398
319010AE1-072 C
Solar/Wind Harmer
1.218
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.166
316311AC2-079 GEN
Solar/Wind Harmer
6.941
3146406KITTY HAWK
Solar/Wind Harmer
0.03
316305AF2-043 C
Solar/Wind Harmer
0.002
315976AC1-164 GENA
Solar/Wind Harmer
24.95
316169AC1-164_GENC
Solar/Wind Harmer
21.555
315975AC1-164 GENB
Solar/Wind Harmer
0.738
315835AF2-110_GEN
Solar/Wind Harmer
1.649
316315AB2-025 C
Solar/Wind Harmer
0.194
313526AB2-022
Solar/Wind Harmer
0.13
972189AH1-679 GEN
Adder
4.009
3146486SUNBURY
Solar/Wind Harmer
0.239
3146486SUNBURY
Solar/Wind Harmer
0.239
971967AH1-528 GEN
Solar/Wind Harmer
38.202
315814AE2-033 C
Solar/Wind Harmer
18.884
316321Z2-027
Solar/Wind Harmer
0.044
3146396TANGLEW
Solar/Wind Harmer
0.658
3145176PASQUOTANK
Solar/Wind Harmer
0.148
971167AH1-042 GEN
Solar/Wind Harmer
21.1
3142433PROV 92
Adder
0.46
3142433PROV 92
Adder
0.46
3138283WHITEMARSH
Solar/Wind Harmer
0.055
3143873LANEXA
Solar/Wind Harmer
0.14
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
316314AB2-024 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
6.866
316059AD1-063 C
Solar/Wind Harmer
0.001
315662AE1-191 GEN
Solar/Wind Harmer
0.008
315666AE1-190 GEN
Solar/Wind Harmer
0.002
3130156CHOWAN
Solar/Wind Harmer
0.23
3130156CHOWAN
Solar/Wind Harmer
0.23
3141873WAN 176
Solar/Wind Harmer
0.046
970085AG2-068 GEN
Solar/Wind Harmer
12.13
970581AG2-369 GEN
Solar/Wind Harmer
10.432
3141913WHIT STONE
Solar/Wind Harmer
0.227
3138133OCRAN
Solar/Wind Harmer
0.068
315816AE2-034 GEN
Solar/Wind Harmer
0.969
3141783LANCAST
Solar/Wind Harmer
0.135
3141783LANCAST
Solar/Wind Harmer
0.09
3150411LDYSMT5
Adder
30.153
3150381LDYSMT2
Adder
28.858
972213AH1-691 GEN
Adder
4.882
972215AH1-692 GEN
Adder
4.882
3130546PLYMOUTH
Solar/Wind Harmer
0.222
315732AD1-074 GEN1
Solar/Wind Harmer
1.273
315733AD1-074 GEN2
Solar/Wind Harmer
1.273
315735AD1-075 GEN1
Solar/Wind Harmer
0.637
965291AG1-394 GEN
Solar/Wind Harmer
0.982
962981AG1-147 GEN
Solar/Wind Harmer
8.243
3146206CASHIE
Solar/Wind Harmer
0.219
970601AG2-382 GEN
Solar/Wind Harmer
8.195
3145893MURPHYS
Solar/Wind Harmer
0.591
3145893MURPHYS
Solar/Wind Harmer
0.219
970327AG2-215 GEN
Solar/Wind Harmer
7.177
3145513AHOSKIE
Solar/Wind Harmer
0.452
3145513AHOSKIE
Solar/Wind Harmer
0.216
3146043SEABORD
Solar/Wind Harmer
0.215
3145683EARLEYS
Solar/Wind Harmer
0.43
3145683EARLEYS
Solar/Wind Harmer
0.215
3145683EARLEYS
Solar/Wind Harmer
0.215
315607AA1-063A GEN
Solar/Wind Harmer
0.438
316087AB2-174 GEN
Solar/Wind Harmer
0.006
315652AC1-086 GEN
Solar/Wind Harmer
23.331
3137643SOCKMAN
Solar/Wind Harmer
0.845
3141813NORNECK
Solar/Wind Harmer
0.209
3145796HORNRTN
Solar/Wind Harmer
0.668
3145796HORNRTN
Solar/Wind Harmer
0.084
3146033SCOT NK
Solar/Wind Harmer
0.828
970831AG2-522 GEN
Solar/Wind Harmer
8.631
316005AA1-067
Solar/Wind Harmer
0.213
3145746EVERETS
Solar/Wind Harmer
0.791
3145746EVERETS
Solar/Wind Harmer
0.199
3145746EVERETS
Solar/Wind Harmer
0.199
3145746EVERETS
Solar/Wind Harmer
0.199
970181AG2-120 GEN
Solar/Wind Harmer
2.475
957861AF2-080 GEN
Solar/Wind Harmer
8.442
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316420AA1-050 GEN
Solar/Wind Harmer
0.006
971443AH1-215 GEN
Solar/Wind Harmer
3.255
3144303KENBRDG
Solar/Wind Harmer
0.155
316319Z2-044 C
Solar/Wind Harmer
0
3145573BETHELC
Solar/Wind Harmer
0.193
3145573BETHELC
Solar/Wind Harmer
0.193
970683AG2-441 GEN
Solar/Wind Harmer
12.874
970681AG2-440 GEN
Solar/Wind Harmer
10.299
946301AF1-294 GEN
Solar/Wind Harmer
3.8
961791AG1-021 GEN
Solar/Wind Harmer
1.849
315657AE1-056 GEN
Solar/Wind Harmer
6.628
316223AC1-118
Solar/Wind Harmer
0.135
970285AG2-188 GEN
Solar/Wind Harmer
14.487
971845AH1-439 GEN
Solar/Wind Harmer
8.236
316118AC1-105 GEN
Solar/Wind Harmer
0.469
3147173SINAI
Solar/Wind Harmer
0.178
3147243WELCO
Solar/Wind Harmer
0.111
972205AH1-687 GEN
Adder
7.261
944491AF1-114 GEN
Solar/Wind Harmer
0.001
970865AG2-541 GEN
Solar/Wind Harmer
5.471
971447AH1-217 GEN
Solar/Wind Harmer
4.69
972193AH1-681 GEN
Adder
3.425
316123AC1-075 GEN
Solar/Wind Harmer
0.197
970165AG2-112 GEN
Solar/Wind Harmer
1.171
970163AG2-111 GEN
Solar/Wind Harmer
1.117
270494AE1-108_GEN
Solar/Wind Harmer
1.686
3147346CASHSCORNER
Solar/Wind Harmer
0.279
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316164AC1-076 GEN
Solar/Wind Helper
2.196
316411AF1-147_GEN1
Solar/Wind Helper
0.801
316415AF1-147_GEN2
Solar/Wind Helper
0.801
3138216PACIFIC
Solar/Wind Helper
0.039
3146456SLIGO L269
Solar/Wind Harmer
0.242
971153AH1-033 GEN
Solar/Wind Harmer
2.796
3150921YORKTN3
Adder
6.079
316382AG1-145 C
Solar/Wind Harmer
0.002
316320Y1-086
Solar/Wind Harmer
0.001
316435W1029_GEN3
Solar/Wind Harmer
0.001
3142433PROV 92
Adder
0.46
3142433PROV 92
Adder
0.46
3146516WINFALL
Solar/Wind Harmer
0.236
316473AC1-191 GEN
Solar/Wind Harmer
0.795
3146626S HERTFORD
Solar/Wind Harmer
0.235
3145273HOLLAND
Solar/Wind Harmer
0.176
3141843SHACKLE
Adder
1.184
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
3141766HARMONY
Solar/Wind Harmer
3.085
316280AD1-041 GEN
Solar/Wind Harmer
0.005
3146376EDENTON
Solar/Wind Harmer
0.23
316156AD2-030 GEN
Solar/Wind Harmer
0.17
3141873WAN 176
Solar/Wind Harmer
4.092
316313AB2-026
Solar/Wind Harmer
0.145
316258AE1-075 C
Solar/Wind Harmer
0.173
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.472
970917AG2-570 GEN
Solar/Wind Harmer
20.3
315614AA2-178 GEN
Solar/Wind Harmer
1.293
3150401LDYSMT4
Adder
30.059
3150371LDYSMT1
Adder
29.045
971157AH1-035 GEN
Solar/Wind Harmer
2.667
3156081AA2-088 GEN
Solar/Wind Harmer
0.005
315737AD1-076 GEN
Solar/Wind Harmer
2.851
316365GEN2_N
Solar/Wind Harmer
0.497
962971AG1-146 GEN
Solar/Wind Harmer
3.533
3146206CASHIE
Solar/Wind Harmer
0.219
3145893MURPHYS
Solar/Wind Harmer
0.367
3145893MURPHYS
Solar/Wind Harmer
0.219
970009AG2-005 GEN
Solar/Wind Harmer
1.633
957521AF2-046 GEN
Solar/Wind Harmer
16.257
961681AG1-008 GEN
Solar/Wind Harmer
16.257
3146173TUNIS
Solar/Wind Harmer
0.217
3156021HOLLOMANSOL
Solar/Wind Harmer
0.983
316463AE2-346 GEN
Solar/Wind Harmer
0.186
316140AB2-099
Solar/Wind Harmer
0.077
962331AG1-082 GEN
Solar/Wind Harmer
2.305
316404AE1-155 C
Solar/Wind Harmer
0.048
3146263WOODLND
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.659
3142666NORTHAMPTON
Solar/Wind Harmer
0.212
3145963POPLR C
Solar/Wind Harmer
0.211
316317KELFORD C
Solar/Wind Harmer
0.02
3145823KELFORD
Solar/Wind Harmer
0.211
3147043LAWRENC
Solar/Wind Harmer
0.126
316478AD1-087 GEN
Solar/Wind Harmer
0.731
316486AD2-202 GEN
Solar/Wind Harmer
0.215
3150351NORNECKC2
Adder
2.12
3145796HORNRTN
Solar/Wind Harmer
0.835
3145796HORNRTN
Solar/Wind Harmer
0.209
316210AC1-098 GEN
Solar/Wind Harmer
1.891
3145933PARMELE
Solar/Wind Harmer
0.203
966801AG1-551 GEN
Solar/Wind Harmer
2.363
971781AH1-399 GEN
Solar/Wind Harmer
0.266
970909AG2-566 GEN
Solar/Wind Harmer
2.131
3145746EVERETS
Solar/Wind Harmer
0.199
3145746EVERETS
Solar/Wind Harmer
0.199
315724AD1-057 GEN
Solar/Wind Harmer
0.745
316327AA2-057 GEN
Solar/Wind Harmer
0.297
316131AB2-060 GEN
Solar/Wind Harmer
0.613
964241AG1-285 GEN
Solar/Wind Harmer
12.969
315785AD2-033 C
Solar/Wind Harmer
1.576
970257AG2-171 GEN
Solar/Wind Harmer
6.198
959311AF2-222 GEN
Solar/Wind Harmer
17.202
3146233WITAKRS
Solar/Wind Harmer
0.97
3146233WITAKRS
Solar/Wind Harmer
0.131
3146073TAR RVR
Solar/Wind Harmer
0.193
3146083TARBORO
Solar/Wind Harmer
0.193
3138543CONSLDL
Solar/Wind Harmer
0.127
963181AG1-167 GEN
Solar/Wind Harmer
0.77
3144293JTRSVLE
Adder
0.613
3147133PAMPLIN
Solar/Wind Harmer
0.603
971193AH1-056 GEN
Solar/Wind Harmer
11.702
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
961601AG1-000A GEN
Solar/Wind Harmer
13.507
3146926FARMVIL
Solar/Wind Harmer
0.114
3145543BTLEBRO
Solar/Wind Harmer
0.19
3145543BTLEBRO
Solar/Wind Harmer
0.19
971623AH1-311 GEN
Solar/Wind Harmer
0.38
3141906WESTMOR
Solar/Wind Harmer
0.075
3146776BUCKING
Solar/Wind Harmer
0.065
970737AG2-469 GEN
Solar/Wind Harmer
7.61
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
7.598
971683AH1-343 GEN
Solar/Wind Harmer
6.05
316283AC2-100 C
Solar/Wind Harmer
0.314
970221AG2-151 GEN
Solar/Wind Harmer
8.483
972255AH1-712 GEN
Adder
76.646
3151761LOISA E
Adder
16.829
3141316ARNOLDS
Adder
0.299
972183AH1-676 GEN
Adder
129.168
3150331BIRCHWDA
Adder
19.249
316044AC1-158 PL1
Solar/Wind Helper
5.254
316450AC1-158 RIC
Solar/Wind Helper
1.401
316170AC1-121 GEN2
Solar/Wind Helper
0.463
3141196NOKESVL
Solar/Wind Helper
1.151
3145663CRESWEL
Solar/Wind Harmer
0.632
971163AH1-040 GEN
Solar/Wind Harmer
18.07
972197AH1-683 GEN
Adder
4.694
972219AH1-694 GEN
Adder
3.38
316023GEN1_S
Solar/Wind Harmer
0.497
3146206CASHIE
Solar/Wind Harmer
0.219
971547AH1-271 GEN
Solar/Wind Harmer
4.683
316336AC2-165 C
Solar/Wind Harmer
0.009
3145893MURPHYS
Solar/Wind Harmer
0.876
3145893MURPHYS
Solar/Wind Harmer
0.974
957481AF2-042 GEN
Solar/Wind Harmer
58.056
3146173TUNIS
Solar/Wind Harmer
0.217
962861AG1-135 GEN
Solar/Wind Harmer
6.917
960081AF2-299 GEN
Solar/Wind Harmer
2.073
3145683EARLEYS
Solar/Wind Harmer
0.215
3146263WOODLND
Solar/Wind Harmer
0.214
315693AD1-088 GEN
Solar/Wind Harmer
10.231
962491AG1-098 GEN
Solar/Wind Harmer
12.124
316011AB1-132 GEN
Solar/Wind Harmer
3.856
962571AG1-106 GEN
Solar/Wind Harmer
3.018
3141726DUNNSVL
Solar/Wind Harmer
0.847
3145963POPLR C
Solar/Wind Harmer
0.211
971795AH1-408 GEN
Solar/Wind Harmer
14.105
316190AA2-174 GEN
Solar/Wind Harmer
0
3145823KELFORD
Solar/Wind Harmer
0.211
316174AB2-169 GEN
Solar/Wind Harmer
0.006
3147043LAWRENC
Adder
1.896
3145783HORNRTN
Solar/Wind Harmer
0.209
3150351NORNECKC2
Adder
2.084
3145796HORNRTN
Solar/Wind Harmer
0.689
3145796HORNRTN
Solar/Wind Harmer
0.209
316212AC1-099_GEN
Solar/Wind Harmer
1.054
3146293MARTNCO
Solar/Wind Harmer
0.188
316129AC1-054 GEN
Solar/Wind Harmer
0.758
971065AG2-659 GEN
Solar/Wind Harmer
8.56
316337AD2-073 GEN
Solar/Wind Harmer
0.173
3145746EVERETS
Solar/Wind Harmer
0.199
3145746EVERETS
Solar/Wind Harmer
0.199
315722AD1-056 GEN
Solar/Wind Harmer
1.256
315687AD1-152 GEN
Solar/Wind Harmer
0.006
316494AC1-189 GEN
Solar/Wind Harmer
0.661
316237AB2-079_GEN
Solar/Wind Harmer
0.002
3146233WITAKRS
Solar/Wind Harmer
0.769
961671AG1-007 GEN
Solar/Wind Harmer
0.03
3146083TARBORO
Solar/Wind Harmer
0.193
3145493TOT1
Solar/Wind Harmer
0.859
970685AG2-442 GEN
Solar/Wind Harmer
14.419
970937AG2-583 GEN
Solar/Wind Harmer
11.813
963171AG1-166 GEN
Solar/Wind Harmer
1.027
971563AH1-280 GEN
Solar/Wind Harmer
2.054
3144293JTRSVLE
Adder
0.613
3146926FARMVIL
Solar/Wind Harmer
0.114
3145543BTLEBRO
Solar/Wind Harmer
0.19
3145543BTLEBRO
Solar/Wind Harmer
0.152
316359AB2-059 GEN
Solar/Wind Harmer
0.682
316049AB1-081 GEN
Solar/Wind Harmer
1.086
3142053HEARTS
Solar/Wind Harmer
0.334
970401AG2-262 GEN
Solar/Wind Harmer
1.086
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.072
972003AH1-546 GEN
Solar/Wind Harmer
7.307
972135AH1-637 GEN
Solar/Wind Harmer
1.466
316003AC1-222 GEN
Solar/Wind Harmer
0.005
971377AH1-170 GEN
Solar/Wind Harmer
1.697
3147623JAMES R
Solar/Wind Harmer
0.369
972277AH1-723 GEN
Adder
89.316
3151751LOISA D
Adder
8.255
970223AG2-152 GEN
Solar/Wind Harmer
8.023
316045AC1-158 PL2
Solar/Wind Helper
16.818
316006AB2-029 C
Solar/Wind Helper
0.152
316254AC1-120 GEN1
Solar/Wind Helper
1.388
3142666NORTHAMPTON
Solar/Wind Harmer
0.212
3142666NORTHAMPTON
Solar/Wind Harmer
0.212
3142666NORTHAMPTON
Solar/Wind Harmer
0.212
3142666NORTHAMPTON
Solar/Wind Harmer
0.128
316426AA2-053 GEN
Solar/Wind Harmer
0.713
3145593CAROLNA
Solar/Wind Harmer
0.21
3145593CAROLNA
Solar/Wind Harmer
0.21
966811AG1-552 GEN
Solar/Wind Harmer
2.282
3145593CAROLNA
Solar/Wind Harmer
0.262
3145783HORNRTN
Solar/Wind Harmer
3.718
3145783HORNRTN
Solar/Wind Harmer
2.974
3145783HORNRTN
Solar/Wind Harmer
0.93
3145783HORNRTN
Solar/Wind Harmer
0.372
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
2.19
3150341NORNECKC1
Adder
2.172
3145796HORNRTN
Solar/Wind Harmer
0.626
3145933PARMELE
Solar/Wind Harmer
0.406
3145933PARMELE
Solar/Wind Harmer
0.203
971741AH1-377 GEN
Solar/Wind Harmer
20.122
316274AC1-208 GEN
Solar/Wind Harmer
1.051
316468AD1-105 GEN
Solar/Wind Harmer
-0.066
970301AG2-198 GEN
Solar/Wind Harmer
8.524
939181AE1-148 GEN
Solar/Wind Harmer
9.423
313527AB2-043 GEN
Solar/Wind Harmer
0.002
316034AC1-036 C
Solar/Wind Harmer
0.014
970323AG2-213 GEN
Solar/Wind Harmer
8.264
971775AH1-396 GEN
Solar/Wind Harmer
0.31
3145493TOT1
Solar/Wind Harmer
0.448
3145453TOT5
Solar/Wind Harmer
0.269
3145603CNETO
Solar/Wind Harmer
0.179
958211AF2-115 GEN
Solar/Wind Harmer
2.311
963191AG1-168 GEN
Solar/Wind Harmer
0.77
3144293JTRSVLE
Adder
0.613
3144293JTRSVLE
Adder
0.516
3147133PAMPLIN
Solar/Wind Harmer
0.192
3147133PAMPLIN
Solar/Wind Harmer
0.154
961601AG1-000A GEN
Solar/Wind Harmer
3.377
316263AC1-034 GEN
Solar/Wind Harmer
7.215
962561AG1-105 GEN
Solar/Wind Harmer
8.959
964791AG1-342 GEN
Solar/Wind Harmer
3.555
3146843MT LREL
Solar/Wind Harmer
0.185
3146843MT LREL
Solar/Wind Harmer
0.185
3146776BUCKING
Solar/Wind Harmer
0.723
3146776BUCKING
Solar/Wind Harmer
0.059
316222AC1-221 GEN
Solar/Wind Harmer
0.67
971489AH1-241 GEN
Solar/Wind Harmer
8.483
942751AE2-291 GEN
Solar/Wind Harmer
7.393
315821AE2-092 GEN
Solar/Wind Harmer
0.008
3151731LOISA B
Adder
8.255
3151721LOISA A
Adder
8.212
316447AC1-158 HLD
Solar/Wind Helper
11.564
315651AD1-115 GEN
Solar/Wind Helper
1.026
LAGNLTFEXP_LAGN->PJM
CLTF
8.524
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.899
TVALTFEXP_TVA->PJM
CLTF
4.316
CPLELTFEXP_CPLE->PJM
CLTF
12.317
CBM West 2LTFEXP_CBM-W2->PJM
CBM
43.813
NYPJM->LTFIMP_NY
CLTF
3.309
LGEELTFEXP_LGEE->PJM
CLTF
1.392
WECLTFEXP_WEC->PJM
CLTF
0.673
CBM West 1LTFEXP_CBM-W1->PJM
CBM
22.369
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.657
MECLTFEXP_MEC->PJM
CLTF
3.808
SIGELTFEXP_SIGE->PJM
CLTF
0.116

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T581_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T581_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:150.52 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:5930.65
MW Contribution:1.74
Bus #Bus NameTypeMW Contribution
3152261N ANNA2
50/50
20.538
3150861SPRUNCD
50/50
1.233
3143096IRON208
50/50
1.093
3143096IRON208
50/50
1.071
3150801HOPHCF4
50/50
1.442
971211AH1-065 GEN
50/50
1.739
3151101ELIZAR3
50/50
24.061
3151161SURRY 1
50/50
9.348
3147666LOUISA
Solar/Wind Harmer
-0.066
315773AC2-141 GEN
Solar/Wind Harmer
11.614
315839AE2-212 C
Solar/Wind Harmer
0.835
965281AG1-393 GEN
Solar/Wind Harmer
3.451
315813AE1-149 C
Solar/Wind Harmer
17.198
944581AF1-123 GEN
Solar/Wind Harmer
125.059
944601AF1-125 GEN
Solar/Wind Harmer
123.108
970133AG2-095 GEN
Solar/Wind Harmer
3.091
970129AG2-093 GEN
Solar/Wind Harmer
15.452
3144536CHRHLND
Solar/Wind Harmer
-0.004
3144873MCLAUGH
Solar/Wind Harmer
-0.001
315778AD1-151 GEN
Solar/Wind Harmer
23.752
970659AG2-427 GEN
Solar/Wind Harmer
2.578
3145336SMITFLD
Solar/Wind Harmer
-0.011
961611AG1-000B GEN
Solar/Wind Harmer
5.762
316083AB2-161 GEN
Solar/Wind Harmer
4.441
3151221GRAVEL6
Adder
17.693
3151171GRAVELC
Adder
3.404
970661AG2-428 GEN
Solar/Wind Harmer
5.139
3142946ENON
Solar/Wind Harmer
-0.009
970293AG2-193 GEN
Solar/Wind Harmer
3.403
3146456SLIGO L269
Solar/Wind Harmer
-0.027
971153AH1-033 GEN
Solar/Wind Harmer
3.31
3144216WINCHST
Adder
0.911
3150921YORKTN3
Adder
6.062
3142416OLDCHRC
Solar/Wind Harmer
2.734
316382AG1-145 C
Solar/Wind Harmer
0.815
316320Y1-086
Solar/Wind Harmer
1.576
316435W1029_GEN3
Solar/Wind Harmer
4.824
3146516WINFALL
Solar/Wind Harmer
-0.026
3142433PROV 92
Adder
0.457
3142433PROV 92
Adder
0.457
3146626S HERTFORD
Solar/Wind Harmer
-0.026
3145273HOLLAND
Solar/Wind Harmer
-0.02
316473AC1-191 GEN
Solar/Wind Harmer
2.815
3146376EDENTON
Solar/Wind Harmer
-0.026
3141843SHACKLE
Adder
1.176
316203AE2-005 GEN
Solar/Wind Harmer
10.898
3141766HARMONY
Solar/Wind Harmer
2.298
316313AB2-026
Solar/Wind Harmer
0.695
316258AE1-075 C
Solar/Wind Harmer
0.626
316405AF2-144 C
Solar/Wind Harmer
0.66
3143336POWHATN
Solar/Wind Harmer
2.601
316280AD1-041 GEN
Solar/Wind Harmer
1.942
316156AD2-030 GEN
Solar/Wind Harmer
0.685
3141873WAN 176
Solar/Wind Harmer
3.046
970917AG2-570 GEN
Solar/Wind Harmer
64.143
315614AA2-178 GEN
Solar/Wind Harmer
2.735
971157AH1-035 GEN
Solar/Wind Harmer
3.118
3156081AA2-088 GEN
Solar/Wind Harmer
8.083
315737AD1-076 GEN
Solar/Wind Harmer
4.727
316365GEN2_N
Solar/Wind Harmer
1.677
3146206CASHIE
Solar/Wind Harmer
-0.025
3145893MURPHYS
Solar/Wind Harmer
0.172
3145893MURPHYS
Solar/Wind Harmer
-0.025
962971AG1-146 GEN
Solar/Wind Harmer
4.602
957521AF2-046 GEN
Solar/Wind Harmer
19.314
961681AG1-008 GEN
Solar/Wind Harmer
19.314
3146173TUNIS
Solar/Wind Harmer
-0.024
3156021HOLLOMANSOL
Solar/Wind Harmer
3.275
316484AD2-074 GEN
Solar/Wind Harmer
6.115
970009AG2-005 GEN
Solar/Wind Harmer
3.036
316463AE2-346 GEN
Solar/Wind Harmer
0.393
316140AB2-099
Solar/Wind Harmer
0.163
962331AG1-082 GEN
Solar/Wind Harmer
3.031
966621AG1-532 GEN
Solar/Wind Harmer
0.492
966881AG1-559 GEN
Solar/Wind Harmer
0.724
3146263WOODLND
Solar/Wind Harmer
-0.024
313506AB2-031 GEN
Solar/Wind Harmer
1.925
316404AE1-155 C
Solar/Wind Harmer
4.606
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3145963POPLR C
Solar/Wind Harmer
-0.024
316317KELFORD C
Solar/Wind Harmer
1.117
3145823KELFORD
Solar/Wind Harmer
-0.024
316478AD1-087 GEN
Solar/Wind Harmer
2.037
316486AD2-202 GEN
Solar/Wind Harmer
0.597
3147043LAWRENC
Solar/Wind Harmer
-0.014
3145796HORNRTN
Solar/Wind Harmer
-0.093
3145796HORNRTN
Solar/Wind Harmer
-0.023
3150351NORNECKC2
Adder
2.088
316210AC1-098 GEN
Solar/Wind Harmer
3.591
3150401LDYSMT4
Adder
26.739
3150371LDYSMT1
Adder
25.837
3144293JTRSVLE
Adder
0.613
972255AH1-712 GEN
Adder
76.926
3151761LOISA E
Adder
16.965
972183AH1-676 GEN
Adder
130.241
3141316ARNOLDS
Adder
0.278
316044AC1-158 PL1
Solar/Wind Helper
5.238
316450AC1-158 RIC
Solar/Wind Helper
1.397
316170AC1-121 GEN2
Solar/Wind Helper
0.46
3141196NOKESVL
Solar/Wind Helper
1.151
3152251N ANNA1
50/50
20.54
970119AG2-088 GEN
50/50
35.865
3150851SPRUNCC
50/50
1.233
3143096IRON208
50/50
1.093
3152331SURRY 2
50/50
10.164
3150771HOPHCF1
50/50
0.992
3143226MDLTHAN
Solar/Wind Harmer
-0.03
3143526WINTERP
Solar/Wind Harmer
-0.152
3147666LOUISA
Solar/Wind Harmer
-0.114
940641AE2-051 GEN
Solar/Wind Harmer
26.675
939411AE1-173 GEN
Solar/Wind Harmer
140.912
316192AB2-158 GEN
Solar/Wind Harmer
3.325
3142543TWELFTH
Solar/Wind Harmer
-0.003
316294AC1-161 GEN
Solar/Wind Harmer
8.98
315671AE2-027_GEN
Solar/Wind Harmer
20.692
944591AF1-124 GEN
Solar/Wind Harmer
125.51
970129AG2-093 GEN
Solar/Wind Harmer
6.259
316458AB2-190 GEN2
Solar/Wind Harmer
2.776
316375AC2-012 GEN
Solar/Wind Harmer
9.491
3150981CHESPKA
Adder
3.048
971069AG2-661 GEN
Solar/Wind Harmer
4.338
970659AG2-427 GEN
Solar/Wind Harmer
14.549
3145336SMITFLD
Solar/Wind Harmer
-0.109
971647AH1-324 GEN
Solar/Wind Harmer
13.692
961611AG1-000B GEN
Solar/Wind Harmer
13.505
316381AD1-082 GEN
Solar/Wind Harmer
2.509
944631AF1-128 GEN
Adder
116.045
3151171GRAVELC
Adder
2.589
970661AG2-428 GEN
Solar/Wind Harmer
28.997
316388AE2-253 GEN
Solar/Wind Harmer
1.836
3146456SLIGO L269
Solar/Wind Harmer
-0.027
316072AD1-144
Solar/Wind Harmer
0.549
3138126ROCKLANDING
Solar/Wind Harmer
0.083
316246AF1-032 C
Solar/Wind Harmer
0.548
3142416OLDCHRC
Solar/Wind Harmer
-0.07
3142416OLDCHRC
Solar/Wind Harmer
-0.027
316159AE1-175 C
Solar/Wind Harmer
0.726
316093AE2-104_GEN
Solar/Wind Harmer
7.84
971317AH1-138 GEN
Solar/Wind Harmer
3.367
3146516WINFALL
Solar/Wind Harmer
-0.086
3146516WINFALL
Solar/Wind Harmer
-0.026
3142433PROV 92
Solar/Wind Harmer
-0.105
3142433PROV 92
Adder
0.457
3142433PROV 92
Adder
0.457
315800Z1-036_GEN1
Solar/Wind Harmer
6.468
3130156CHOWAN
Solar/Wind Harmer
-0.026
971777AH1-397 GEN
Solar/Wind Harmer
3.039
3141843SHACKLE
Adder
1.176
3141766HARMONY
Solar/Wind Harmer
-0.005
3143336POWHATN
Solar/Wind Harmer
3.06
970919AG2-571 GEN
Solar/Wind Harmer
8.119
970087AG2-069 GEN
Solar/Wind Harmer
23.954
3145663CRESWEL
Solar/Wind Harmer
-0.071
971163AH1-040 GEN
Solar/Wind Harmer
23.766
3138133OCRAN
Solar/Wind Harmer
-0.015
316023GEN1_S
Solar/Wind Harmer
1.677
3146206CASHIE
Solar/Wind Harmer
-0.025
971547AH1-271 GEN
Solar/Wind Harmer
6.159
316336AC2-165 C
Solar/Wind Harmer
4.278
3145893MURPHYS
Solar/Wind Harmer
-0.098
3145893MURPHYS
Solar/Wind Harmer
0.73
957481AF2-042 GEN
Solar/Wind Harmer
76.436
3146173TUNIS
Solar/Wind Harmer
-0.024
961951AG1-038 GEN
Solar/Wind Harmer
3.2
971133AH1-012 GEN
50/50
5.498
944641AF1-129 GEN
50/50
124.495
970533AG2-339 GEN
50/50
21.875
970531AG2-338 GEN
50/50
8.75
3150781HOPHCF2
50/50
0.992
3150791HOPHCF3
50/50
0.992
3150761HOPPOLC
50/50
0.629
971213AH1-066 GEN
50/50
0.87
3142366NRTHEST
50/50
0.848
971223AH1-071 GEN
Solar/Wind Harmer
3.778
3143526WINTERP
Solar/Wind Harmer
-0.152
316240AF1-291 C
Solar/Wind Harmer
0.834
316036AC1-147 C
Solar/Wind Harmer
0.74
3150991CHESPKB
Adder
2.557
3150991CHESPKB
Adder
2.496
316033AB2-134 GEN
Solar/Wind Harmer
8.837
315697AD1-025 GEN
Solar/Wind Harmer
5.542
316316AC1-027 C
Solar/Wind Harmer
0.841
3142956BIRDNECK
Solar/Wind Harmer
1.47
316236AE1-162_GEN
Solar/Wind Harmer
0.825
3150691DARBY 3
Adder
17.538
3150701DARBY 4
Adder
17.497
3150681DARBY 2
Adder
17.476
3150671DARBY 1
Adder
17.456
316185AD1-033 GEN
Solar/Wind Harmer
2.888
970657AG2-426 GEN
Solar/Wind Harmer
8.542
970657AG2-426 GEN
Solar/Wind Harmer
1.786
3145506HICKORY
Solar/Wind Harmer
-0.109
3145506HICKORY
Solar/Wind Harmer
-0.065
3145506HICKORY
Solar/Wind Harmer
-0.016
3142296MT RD221
Adder
0.773
316339AD2-160 GEN
Solar/Wind Harmer
1.836
3142946ENON
Solar/Wind Harmer
-0.003
316018AA1-139 ULT2
Solar/Wind Harmer
2.33
316017AA1-139 ULT1
Solar/Wind Harmer
2.201
3137176SLIGO L2192
Solar/Wind Harmer
-0.107
3146456SLIGO L269
Solar/Wind Harmer
3.207
3130086AYDLETT
Solar/Wind Harmer
-0.108
316075AC2-137 C
Solar/Wind Harmer
0.73
972185AH1-677 GEN
Adder
13.451
3146386ELIZ CT
Solar/Wind Harmer
-0.027
3144356SAPONY
Solar/Wind Harmer
0.938
316431W1029_GEN1
Solar/Wind Harmer
4.824
316433W1029_GEN2
Solar/Wind Harmer
4.824
972187AH1-678 GEN
Adder
6.746
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
3146626S HERTFORD
Solar/Wind Harmer
-0.026
3146626S HERTFORD
Solar/Wind Harmer
-0.026
970933AG2-581 GEN
Solar/Wind Harmer
24.532
966871AG1-558 GEN
Solar/Wind Harmer
0.787
966871AG1-558 GEN
Solar/Wind Harmer
0.269
315742AE1-103 GEN
Solar/Wind Harmer
2.721
3146376EDENTON
Solar/Wind Harmer
0.768
3146376EDENTON
Solar/Wind Harmer
0.768
316441AF1-014 GEN
Solar/Wind Harmer
1.742
316065AD1-022 GEN
Solar/Wind Harmer
12.361
3145893MURPHYS
Solar/Wind Harmer
0.686
3145893MURPHYS
Solar/Wind Harmer
-0.044
970099AG2-077 GEN
Solar/Wind Harmer
30.574
3146173TUNIS
Solar/Wind Harmer
-0.024
3146173TUNIS
Solar/Wind Harmer
-0.024
316487AF1-042 GEN
Solar/Wind Harmer
3.2
957411AF2-035 GEN
Solar/Wind Harmer
10.838
970317AG2-208 GEN
Solar/Wind Harmer
10.537
316181AB2-040 GEN
Solar/Wind Harmer
3.34
958261AF2-120 GEN
Solar/Wind Harmer
9.253
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
316426AA2-053 GEN
Solar/Wind Harmer
2.396
3145593CAROLNA
Solar/Wind Harmer
-0.024
3145593CAROLNA
Solar/Wind Harmer
-0.024
966811AG1-552 GEN
Solar/Wind Harmer
2.657
3145593CAROLNA
Solar/Wind Harmer
0.196
3145783HORNRTN
Solar/Wind Harmer
2.786
3145783HORNRTN
Solar/Wind Harmer
2.229
3145783HORNRTN
Solar/Wind Harmer
0.697
3145783HORNRTN
Solar/Wind Harmer
0.279
315673AE1-157 GEN
Solar/Wind Harmer
17.6
3145796HORNRTN
Solar/Wind Harmer
-0.07
316077AC2-138 C
Solar/Wind Harmer
0.488
3150341NORNECKC1
Adder
2.157
3150341NORNECKC1
Adder
2.139
3150391LDYSMT3
Adder
26.689
972195AH1-682 GEN
Adder
3.507
3144293JTRSVLE
Adder
0.613
3144293JTRSVLE
Adder
0.516
3151731LOISA B
Adder
8.322
3151721LOISA A
Adder
8.279
316447AC1-158 HLD
Solar/Wind Helper
11.529
315651AD1-115 GEN
Solar/Wind Helper
1.021
971741AH1-377 GEN
Solar/Wind Harmer
12.626
960081AF2-299 GEN
Solar/Wind Harmer
2.727
3145683EARLEYS
Solar/Wind Harmer
-0.024
966881AG1-559 GEN
Solar/Wind Harmer
0.248
3146263WOODLND
Solar/Wind Harmer
-0.024
962861AG1-135 GEN
Solar/Wind Harmer
8.995
315693AD1-088 GEN
Solar/Wind Harmer
11.973
962491AG1-098 GEN
Solar/Wind Harmer
15.963
316011AB1-132 GEN
Solar/Wind Harmer
4.983
962571AG1-106 GEN
Solar/Wind Harmer
3.424
971795AH1-408 GEN
Solar/Wind Harmer
17.814
3145963POPLR C
Solar/Wind Harmer
-0.024
316190AA2-174 GEN
Solar/Wind Harmer
0.291
3145823KELFORD
Solar/Wind Harmer
-0.024
316174AB2-169 GEN
Solar/Wind Harmer
3.632
3147043LAWRENC
Adder
1.895
964211AG1-282 GEN
Solar/Wind Harmer
0.706
3141726DUNNSVL
Solar/Wind Harmer
-0.093
3145783HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.077
3145796HORNRTN
Solar/Wind Harmer
-0.023
3150351NORNECKC2
Adder
2.053
316212AC1-099_GEN
Solar/Wind Harmer
1.995
972197AH1-683 GEN
Adder
4.175
972219AH1-694 GEN
Adder
3.006
3144293JTRSVLE
Adder
0.613
972277AH1-723 GEN
Adder
89.642
3151751LOISA D
Adder
8.322
316045AC1-158 PL2
Solar/Wind Helper
16.768
316006AB2-029 C
Solar/Wind Helper
0.152
316254AC1-120 GEN1
Solar/Wind Helper
1.381
316303AF2-085
50/50
4.782
971285AH1-108 GEN
50/50
2.017
970603AG2-384 GEN
50/50
5.251
972263AH1-716 GEN
50/50
141.451
316233AE1-074 FULL
Solar/Wind Harmer
0.79
971281AH1-106 GEN
Solar/Wind Harmer
4.774
971283AH1-107 GEN
Solar/Wind Harmer
4.774
3143316POE
Solar/Wind Harmer
-0.109
941031AE2-094 GEN
Solar/Wind Harmer
51.844
944011AF1-069 GEN
Solar/Wind Harmer
16.245
3151081ELIZAR1
Adder
22.389
3151091ELIZAR2
Adder
22
316132AB2-190 GEN1
Solar/Wind Harmer
2.776
3152611GOSPORTB
Adder
3.108
3152621GOSPORTC
Adder
2.638
3152601GOSPORTA
Adder
2.434
316369SG1_INVT
Solar/Wind Harmer
4.896
971445AH1-216 GEN
Solar/Wind Harmer
16.942
972265AH1-717 GEN
Adder
18.896
3151201GRAVEL4
Adder
17.714
3151191GRAVEL3
Adder
17.489
3151211GRAVEL5
Adder
17.489
957871AF2-081 GEN
Solar/Wind Harmer
13.602
970673AG2-436 GEN
Solar/Wind Harmer
57.084
970673AG2-436 GEN
Solar/Wind Harmer
28.903
319010AE1-072 C
Solar/Wind Harmer
5.488
3146406KITTY HAWK
Solar/Wind Harmer
0.023
315833AF1-017_GEN
Solar/Wind Harmer
5.15
316349AD2-085 GEN
Solar/Wind Harmer
2.412
316311AC2-079 GEN
Solar/Wind Harmer
13.676
316305AF2-043 C
Solar/Wind Harmer
0.817
316312AB1-027
Solar/Wind Harmer
0.914
315835AF2-110_GEN
Solar/Wind Harmer
3.371
315976AC1-164 GENA
Solar/Wind Harmer
28.429
316169AC1-164_GENC
Solar/Wind Harmer
24.56
315975AC1-164 GENB
Solar/Wind Harmer
0.841
313526AB2-022
Solar/Wind Harmer
0.725
316315AB2-025 C
Solar/Wind Harmer
0.725
971967AH1-528 GEN
Solar/Wind Harmer
50.429
3146486SUNBURY
Solar/Wind Harmer
-0.027
3146486SUNBURY
Solar/Wind Harmer
-0.027
315814AE2-033 C
Solar/Wind Harmer
24.939
316321Z2-027
Solar/Wind Harmer
0.722
3146396TANGLEW
Solar/Wind Harmer
0.493
3145176PASQUOTANK
Solar/Wind Harmer
-0.017
971167AH1-042 GEN
Solar/Wind Harmer
25.534
3142433PROV 92
Adder
0.457
3142433PROV 92
Adder
0.457
957831AF2-077 GEN
Solar/Wind Harmer
0.794
3138283WHITEMARSH
Solar/Wind Harmer
0.041
315611Z1-036_GEN2
Solar/Wind Harmer
6.468
3143873LANEXA
Solar/Wind Harmer
-0.015
972189AH1-679 GEN
Adder
3.879
316314AB2-024 C
Solar/Wind Harmer
2.214
3130156CHOWAN
Solar/Wind Harmer
-0.026
3130156CHOWAN
Solar/Wind Harmer
-0.026
316059AD1-063 C
Solar/Wind Harmer
0.583
315662AE1-191 GEN
Solar/Wind Harmer
3.107
315666AE1-190 GEN
Solar/Wind Harmer
0.777
957601AF2-054 GEN
Solar/Wind Harmer
0.768
3141873WAN 176
Solar/Wind Harmer
-0.005
970085AG2-068 GEN
Solar/Wind Harmer
15.97
970581AG2-369 GEN
Solar/Wind Harmer
13.734
315816AE2-034 GEN
Solar/Wind Harmer
2.051
3141913WHIT STONE
Solar/Wind Harmer
-0.025
3138133OCRAN
Solar/Wind Harmer
-0.008
3141783LANCAST
Solar/Wind Harmer
-0.015
3141783LANCAST
Solar/Wind Harmer
-0.01
3130546PLYMOUTH
Solar/Wind Harmer
-0.025
315732AD1-074 GEN1
Solar/Wind Harmer
5.029
315733AD1-074 GEN2
Solar/Wind Harmer
5.029
315735AD1-075 GEN1
Solar/Wind Harmer
2.515
965291AG1-394 GEN
Solar/Wind Harmer
2.201
3146206CASHIE
Solar/Wind Harmer
-0.025
970601AG2-382 GEN
Solar/Wind Harmer
10.779
316318V4-068
Solar/Wind Harmer
0.613
3145893MURPHYS
Solar/Wind Harmer
-0.066
3145893MURPHYS
Solar/Wind Harmer
-0.025
962981AG1-147 GEN
Solar/Wind Harmer
10.738
3145513AHOSKIE
Solar/Wind Harmer
0.211
961941AG1-037 GEN
Solar/Wind Harmer
0.182
3145513AHOSKIE
Solar/Wind Harmer
-0.024
946281AF1-292 GEN
Solar/Wind Harmer
0.543
3146043SEABORD
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.048
3145683EARLEYS
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.024
315607AA1-063A GEN
Solar/Wind Harmer
2.433
316087AB2-174 GEN
Solar/Wind Harmer
3.429
315652AC1-086 GEN
Solar/Wind Harmer
26.795
3137643SOCKMAN
Solar/Wind Harmer
-0.094
3145796HORNRTN
Solar/Wind Harmer
-0.075
3145796HORNRTN
Solar/Wind Harmer
-0.009
3146033SCOT NK
Solar/Wind Harmer
-0.093
3141813NORNECK
Solar/Wind Harmer
-0.023
3150411LDYSMT5
Adder
26.823
3150381LDYSMT2
Adder
25.67
972213AH1-691 GEN
Adder
4.342
972215AH1-692 GEN
Adder
4.342
972205AH1-687 GEN
Adder
7.266
972193AH1-681 GEN
Adder
3.437
316164AC1-076 GEN
Solar/Wind Helper
2.187
316411AF1-147_GEN1
Solar/Wind Helper
0.802
316415AF1-147_GEN2
Solar/Wind Helper
0.802
3138216PACIFIC
Solar/Wind Helper
0.039
LAGNLTFEXP_LAGN->PJM
CLTF
8.538
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.91
TVALTFEXP_TVA->PJM
CLTF
4.323
CPLELTFEXP_CPLE->PJM
CLTF
12.318
CBM West 2LTFEXP_CBM-W2->PJM
CBM
43.908
NYPJM->LTFIMP_NY
CLTF
3.309
LGEELTFEXP_LGEE->PJM
CLTF
1.397
WECLTFEXP_WEC->PJM
CLTF
0.676
CBM West 1LTFEXP_CBM-W1->PJM
CBM
22.478
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.684
MECLTFEXP_MEC->PJM
CLTF
3.82
SIGELTFEXP_SIGE->PJM
CLTF
0.116

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T552_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T552_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:148.0 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:5831.04
MW Contribution:1.71
Bus #Bus NameTypeMW Contribution
3152261N ANNA2
50/50
20.32
3150861SPRUNCD
50/50
1.216
3143096IRON208
50/50
1.078
3143096IRON208
50/50
1.056
3150801HOPHCF4
50/50
1.421
971211AH1-065 GEN
50/50
1.714
3151101ELIZAR3
50/50
23.68
3151161SURRY 1
50/50
9.205
3147666LOUISA
Solar/Wind Harmer
-0.066
315839AE2-212 C
Solar/Wind Harmer
0.823
315773AC2-141 GEN
Solar/Wind Harmer
11.425
965281AG1-393 GEN
Solar/Wind Harmer
3.403
315813AE1-149 C
Solar/Wind Harmer
16.949
970133AG2-095 GEN
Solar/Wind Harmer
3.047
944581AF1-123 GEN
Solar/Wind Harmer
123.071
944601AF1-125 GEN
Solar/Wind Harmer
121.15
971133AH1-012 GEN
50/50
5.491
944641AF1-129 GEN
50/50
122.767
970533AG2-339 GEN
50/50
21.564
970531AG2-338 GEN
50/50
8.626
3142366NRTHEST
50/50
0.836
3150781HOPHCF2
50/50
0.977
3150791HOPHCF3
50/50
0.977
3150761HOPPOLC
50/50
0.62
971213AH1-066 GEN
50/50
0.857
971223AH1-071 GEN
Solar/Wind Harmer
3.731
3143526WINTERP
Solar/Wind Harmer
-0.15
316240AF1-291 C
Solar/Wind Harmer
0.822
3150691DARBY 3
Adder
17.296
3150701DARBY 4
Adder
17.255
3150681DARBY 2
Adder
17.235
3150671DARBY 1
Adder
17.215
316036AC1-147 C
Solar/Wind Harmer
0.728
3150991CHESPKB
Adder
2.516
3150991CHESPKB
Adder
2.456
316033AB2-134 GEN
Solar/Wind Harmer
8.705
315697AD1-025 GEN
Solar/Wind Harmer
5.46
3142956BIRDNECK
Solar/Wind Harmer
1.447
316316AC1-027 C
Solar/Wind Harmer
0.828
316236AE1-162_GEN
Solar/Wind Harmer
0.812
316185AD1-033 GEN
Solar/Wind Harmer
2.842
970657AG2-426 GEN
Solar/Wind Harmer
8.416
970657AG2-426 GEN
Solar/Wind Harmer
1.76
3142296MT RD221
Adder
0.763
3145506HICKORY
Solar/Wind Harmer
-0.107
3145506HICKORY
Solar/Wind Harmer
-0.064
3145506HICKORY
Solar/Wind Harmer
-0.016
3142946ENON
Solar/Wind Harmer
-0.003
316339AD2-160 GEN
Solar/Wind Harmer
1.807
316018AA1-139 ULT2
Solar/Wind Harmer
2.294
316017AA1-139 ULT1
Solar/Wind Harmer
2.166
3137176SLIGO L2192
Solar/Wind Harmer
-0.106
3146456SLIGO L269
Solar/Wind Harmer
3.156
3130086AYDLETT
Solar/Wind Harmer
-0.106
316075AC2-137 C
Solar/Wind Harmer
0.719
3152251N ANNA1
50/50
20.321
970119AG2-088 GEN
50/50
35.422
3150851SPRUNCC
50/50
1.216
3143096IRON208
50/50
1.078
3152331SURRY 2
50/50
9.99
3150771HOPHCF1
50/50
0.977
3143226MDLTHAN
Solar/Wind Harmer
-0.03
3143526WINTERP
Solar/Wind Harmer
-0.15
3147666LOUISA
Solar/Wind Harmer
-0.115
316192AB2-158 GEN
Solar/Wind Harmer
3.345
940641AE2-051 GEN
Solar/Wind Harmer
26.285
939411AE1-173 GEN
Solar/Wind Harmer
138.811
3142543TWELFTH
Solar/Wind Harmer
-0.003
316294AC1-161 GEN
Solar/Wind Harmer
8.834
315671AE2-027_GEN
Solar/Wind Harmer
20.403
944591AF1-124 GEN
Solar/Wind Harmer
123.514
970129AG2-093 GEN
Solar/Wind Harmer
6.167
316458AB2-190 GEN2
Solar/Wind Harmer
2.735
971069AG2-661 GEN
Solar/Wind Harmer
4.274
316375AC2-012 GEN
Solar/Wind Harmer
9.341
3150981CHESPKA
Adder
3
970659AG2-427 GEN
Solar/Wind Harmer
14.335
971647AH1-324 GEN
Solar/Wind Harmer
13.486
3145336SMITFLD
Solar/Wind Harmer
-0.107
316381AD1-082 GEN
Solar/Wind Harmer
2.472
944631AF1-128 GEN
Adder
114.357
961611AG1-000B GEN
Solar/Wind Harmer
13.3
3151171GRAVELC
Adder
2.549
970661AG2-428 GEN
Solar/Wind Harmer
28.566
316388AE2-253 GEN
Solar/Wind Harmer
1.807
3146456SLIGO L269
Solar/Wind Harmer
-0.027
3142416OLDCHRC
Solar/Wind Harmer
-0.069
3142416OLDCHRC
Solar/Wind Harmer
-0.026
316072AD1-144
Solar/Wind Harmer
0.54
3138126ROCKLANDING
Solar/Wind Harmer
0.082
316246AF1-032 C
Solar/Wind Harmer
0.54
316159AE1-175 C
Solar/Wind Harmer
0.715
316093AE2-104_GEN
Solar/Wind Harmer
7.718
971317AH1-138 GEN
Solar/Wind Harmer
3.315
3146516WINFALL
Solar/Wind Harmer
-0.084
3146516WINFALL
Solar/Wind Harmer
-0.026
3142433PROV 92
Solar/Wind Harmer
-0.104
3142433PROV 92
Adder
0.451
3142433PROV 92
Adder
0.451
315800Z1-036_GEN1
Solar/Wind Harmer
6.367
971777AH1-397 GEN
Solar/Wind Harmer
3
3141843SHACKLE
Adder
1.16
3143336POWHATN
Solar/Wind Harmer
3.025
3130156CHOWAN
Solar/Wind Harmer
-0.025
3141766HARMONY
Solar/Wind Harmer
-0.005
970919AG2-571 GEN
Solar/Wind Harmer
8.004
966881AG1-559 GEN
Solar/Wind Harmer
0.26
970087AG2-069 GEN
Solar/Wind Harmer
23.613
3145663CRESWEL
Solar/Wind Harmer
-0.07
971163AH1-040 GEN
Solar/Wind Harmer
23.4
3138133OCRAN
Solar/Wind Harmer
-0.015
316023GEN1_S
Solar/Wind Harmer
1.652
972197AH1-683 GEN
Adder
4.553
972219AH1-694 GEN
Adder
3.278
316336AC2-165 C
Solar/Wind Harmer
4.232
3146206CASHIE
Solar/Wind Harmer
-0.024
971547AH1-271 GEN
Solar/Wind Harmer
6.065
3145893MURPHYS
Solar/Wind Harmer
-0.096
3145893MURPHYS
Solar/Wind Harmer
0.719
957481AF2-042 GEN
Solar/Wind Harmer
75.375
961951AG1-038 GEN
Solar/Wind Harmer
3.17
3146173TUNIS
Solar/Wind Harmer
-0.024
960081AF2-299 GEN
Solar/Wind Harmer
2.688
962861AG1-135 GEN
Solar/Wind Harmer
8.919
3145683EARLEYS
Solar/Wind Harmer
-0.024
3146263WOODLND
Solar/Wind Harmer
-0.024
315693AD1-088 GEN
Solar/Wind Harmer
11.811
962491AG1-098 GEN
Solar/Wind Harmer
15.746
316011AB1-132 GEN
Solar/Wind Harmer
4.91
962571AG1-106 GEN
Solar/Wind Harmer
3.374
971795AH1-408 GEN
Solar/Wind Harmer
17.56
3145963POPLR C
Solar/Wind Harmer
-0.023
316190AA2-174 GEN
Solar/Wind Harmer
0.287
3145823KELFORD
Solar/Wind Harmer
-0.023
964211AG1-282 GEN
Solar/Wind Harmer
0.701
3141726DUNNSVL
Solar/Wind Harmer
-0.093
316174AB2-169 GEN
Solar/Wind Harmer
3.577
3147043LAWRENC
Adder
1.868
3145783HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.076
3145796HORNRTN
Solar/Wind Harmer
-0.023
3150351NORNECKC2
Adder
2.04
316212AC1-099_GEN
Solar/Wind Harmer
1.965
3144293JTRSVLE
Adder
0.605
972277AH1-723 GEN
Adder
87.353
3151751LOISA D
Adder
8.676
316045AC1-158 PL2
Solar/Wind Helper
16.699
316006AB2-029 C
Solar/Wind Helper
0.14
316303AF2-085
50/50
4.723
971285AH1-108 GEN
50/50
1.99
970603AG2-384 GEN
50/50
5.178
972263AH1-716 GEN
50/50
139.063
316233AE1-074 FULL
Solar/Wind Harmer
0.78
971281AH1-106 GEN
Solar/Wind Harmer
4.714
971283AH1-107 GEN
Solar/Wind Harmer
4.714
3143316POE
Solar/Wind Harmer
-0.108
941031AE2-094 GEN
Solar/Wind Harmer
51.106
944011AF1-069 GEN
Solar/Wind Harmer
16.013
316132AB2-190 GEN1
Solar/Wind Harmer
2.735
3151081ELIZAR1
Adder
22.034
3151091ELIZAR2
Adder
21.652
3152611GOSPORTB
Adder
3.059
3152621GOSPORTC
Adder
2.596
3152601GOSPORTA
Adder
2.395
316369SG1_INVT
Solar/Wind Harmer
4.823
971445AH1-216 GEN
Solar/Wind Harmer
16.679
972265AH1-717 GEN
Adder
18.606
3151201GRAVEL4
Adder
17.442
3151191GRAVEL3
Adder
17.221
3151211GRAVEL5
Adder
17.221
970673AG2-436 GEN
Solar/Wind Harmer
56.272
970673AG2-436 GEN
Solar/Wind Harmer
28.492
957871AF2-081 GEN
Solar/Wind Harmer
13.387
316312AB1-027
Solar/Wind Harmer
0.901
319010AE1-072 C
Solar/Wind Harmer
5.402
315833AF1-017_GEN
Solar/Wind Harmer
5.072
316349AD2-085 GEN
Solar/Wind Harmer
2.375
316311AC2-079 GEN
Solar/Wind Harmer
13.467
3146406KITTY HAWK
Solar/Wind Harmer
0.022
316305AF2-043 C
Solar/Wind Harmer
0.804
315835AF2-110_GEN
Solar/Wind Harmer
3.318
316315AB2-025 C
Solar/Wind Harmer
0.715
315976AC1-164 GENA
Solar/Wind Harmer
27.987
316169AC1-164_GENC
Solar/Wind Harmer
24.178
315975AC1-164 GENB
Solar/Wind Harmer
0.828
313526AB2-022
Solar/Wind Harmer
0.714
971967AH1-528 GEN
Solar/Wind Harmer
49.715
315814AE2-033 C
Solar/Wind Harmer
24.583
3146486SUNBURY
Solar/Wind Harmer
-0.026
3146486SUNBURY
Solar/Wind Harmer
-0.026
316321Z2-027
Solar/Wind Harmer
0.711
3146396TANGLEW
Solar/Wind Harmer
0.485
3145176PASQUOTANK
Solar/Wind Harmer
-0.016
972189AH1-679 GEN
Adder
3.913
971167AH1-042 GEN
Solar/Wind Harmer
25.191
3142433PROV 92
Adder
0.451
3142433PROV 92
Adder
0.451
957831AF2-077 GEN
Solar/Wind Harmer
0.783
3138283WHITEMARSH
Solar/Wind Harmer
0.04
315611Z1-036_GEN2
Solar/Wind Harmer
6.367
3143873LANEXA
Solar/Wind Harmer
-0.015
316314AB2-024 C
Solar/Wind Harmer
2.185
3130156CHOWAN
Solar/Wind Harmer
-0.025
3130156CHOWAN
Solar/Wind Harmer
-0.025
316059AD1-063 C
Solar/Wind Harmer
0.576
315662AE1-191 GEN
Solar/Wind Harmer
3.067
315666AE1-190 GEN
Solar/Wind Harmer
0.767
957601AF2-054 GEN
Solar/Wind Harmer
0.758
3141873WAN 176
Solar/Wind Harmer
-0.005
970085AG2-068 GEN
Solar/Wind Harmer
15.742
970581AG2-369 GEN
Solar/Wind Harmer
13.538
3141913WHIT STONE
Solar/Wind Harmer
-0.025
315816AE2-034 GEN
Solar/Wind Harmer
2.02
3138133OCRAN
Solar/Wind Harmer
-0.007
3141783LANCAST
Solar/Wind Harmer
-0.015
3141783LANCAST
Solar/Wind Harmer
-0.01
3130546PLYMOUTH
Solar/Wind Harmer
-0.024
315732AD1-074 GEN1
Solar/Wind Harmer
4.952
315733AD1-074 GEN2
Solar/Wind Harmer
4.952
315735AD1-075 GEN1
Solar/Wind Harmer
2.477
965291AG1-394 GEN
Solar/Wind Harmer
2.168
3150411LDYSMT5
Adder
29.247
3150381LDYSMT2
Adder
27.99
972213AH1-691 GEN
Adder
4.735
972215AH1-692 GEN
Adder
4.735
962981AG1-147 GEN
Solar/Wind Harmer
10.632
3146206CASHIE
Solar/Wind Harmer
-0.024
970601AG2-382 GEN
Solar/Wind Harmer
10.614
316318V4-068
Solar/Wind Harmer
0.603
3145893MURPHYS
Solar/Wind Harmer
-0.065
3145893MURPHYS
Solar/Wind Harmer
-0.024
946281AF1-292 GEN
Solar/Wind Harmer
0.535
3145513AHOSKIE
Solar/Wind Harmer
0.208
961941AG1-037 GEN
Solar/Wind Harmer
0.18
3145513AHOSKIE
Solar/Wind Harmer
-0.024
3146043SEABORD
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.047
3145683EARLEYS
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.024
315607AA1-063A GEN
Solar/Wind Harmer
2.397
316087AB2-174 GEN
Solar/Wind Harmer
3.379
315652AC1-086 GEN
Solar/Wind Harmer
26.401
3137643SOCKMAN
Solar/Wind Harmer
-0.093
3145796HORNRTN
Solar/Wind Harmer
-0.073
3145796HORNRTN
Solar/Wind Harmer
-0.009
3141813NORNECK
Solar/Wind Harmer
-0.023
3146033SCOT NK
Solar/Wind Harmer
-0.091
972205AH1-687 GEN
Adder
7.204
972193AH1-681 GEN
Adder
3.349
316164AC1-076 GEN
Solar/Wind Helper
1.38
316411AF1-147_GEN1
Solar/Wind Helper
0.79
316415AF1-147_GEN2
Solar/Wind Helper
0.79
3138216PACIFIC
Solar/Wind Helper
0.038
972185AH1-677 GEN
Adder
13.26
3144356SAPONY
Solar/Wind Harmer
0.924
3146386ELIZ CT
Solar/Wind Harmer
-0.026
972187AH1-678 GEN
Adder
6.65
316431W1029_GEN1
Solar/Wind Harmer
4.748
316433W1029_GEN2
Solar/Wind Harmer
4.748
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
3146626S HERTFORD
Solar/Wind Harmer
-0.026
3146626S HERTFORD
Solar/Wind Harmer
-0.026
966871AG1-558 GEN
Solar/Wind Harmer
0.778
966871AG1-558 GEN
Solar/Wind Harmer
0.266
970933AG2-581 GEN
Solar/Wind Harmer
24.187
315742AE1-103 GEN
Solar/Wind Harmer
2.679
316441AF1-014 GEN
Solar/Wind Harmer
1.72
3146376EDENTON
Solar/Wind Harmer
0.756
3146376EDENTON
Solar/Wind Harmer
0.756
957411AF2-035 GEN
Solar/Wind Harmer
11.373
970317AG2-208 GEN
Solar/Wind Harmer
11.057
315673AE1-157 GEN
Solar/Wind Harmer
18.722
3150391LDYSMT3
Adder
29.101
972195AH1-682 GEN
Adder
3.824
316065AD1-022 GEN
Solar/Wind Harmer
12.172
3145893MURPHYS
Solar/Wind Harmer
0.676
3145893MURPHYS
Solar/Wind Harmer
-0.043
970099AG2-077 GEN
Solar/Wind Harmer
30.15
316487AF1-042 GEN
Solar/Wind Harmer
3.17
3146173TUNIS
Solar/Wind Harmer
-0.024
3146173TUNIS
Solar/Wind Harmer
-0.024
958261AF2-120 GEN
Solar/Wind Harmer
9.177
316181AB2-040 GEN
Solar/Wind Harmer
3.292
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
316426AA2-053 GEN
Solar/Wind Harmer
2.36
3145593CAROLNA
Solar/Wind Harmer
-0.023
3145593CAROLNA
Solar/Wind Harmer
-0.023
966811AG1-552 GEN
Solar/Wind Harmer
2.618
3145593CAROLNA
Solar/Wind Harmer
0.193
3145783HORNRTN
Solar/Wind Harmer
2.745
3145783HORNRTN
Solar/Wind Harmer
2.196
3145783HORNRTN
Solar/Wind Harmer
0.686
3145783HORNRTN
Solar/Wind Harmer
0.275
3145796HORNRTN
Solar/Wind Harmer
-0.069
316077AC2-138 C
Solar/Wind Harmer
0.485
3150341NORNECKC1
Adder
2.143
3150341NORNECKC1
Adder
2.126
3144293JTRSVLE
Adder
0.605
3144293JTRSVLE
Adder
0.51
3151731LOISA B
Adder
8.676
3151721LOISA A
Adder
8.631
316447AC1-158 HLD
Solar/Wind Helper
11.481
971741AH1-377 GEN
Solar/Wind Harmer
12.466
970129AG2-093 GEN
Solar/Wind Harmer
15.226
315778AD1-151 GEN
Solar/Wind Harmer
23.4
3144536CHRHLND
Solar/Wind Harmer
-0.004
3144873MCLAUGH
Solar/Wind Harmer
-0.001
970659AG2-427 GEN
Solar/Wind Harmer
2.54
3145336SMITFLD
Solar/Wind Harmer
-0.011
316083AB2-161 GEN
Solar/Wind Harmer
4.375
961611AG1-000B GEN
Solar/Wind Harmer
5.675
3151221GRAVEL6
Adder
17.422
3151171GRAVELC
Adder
3.352
970661AG2-428 GEN
Solar/Wind Harmer
5.062
970293AG2-193 GEN
Solar/Wind Harmer
3.354
3142946ENON
Solar/Wind Harmer
-0.009
3146456SLIGO L269
Solar/Wind Harmer
-0.027
971153AH1-033 GEN
Solar/Wind Harmer
3.257
3142416OLDCHRC
Solar/Wind Harmer
2.696
3144216WINCHST
Adder
0.896
3150921YORKTN3
Adder
5.966
316382AG1-145 C
Solar/Wind Harmer
0.802
316320Y1-086
Solar/Wind Harmer
1.551
316435W1029_GEN3
Solar/Wind Harmer
4.748
3146516WINFALL
Solar/Wind Harmer
-0.026
3142433PROV 92
Adder
0.451
3142433PROV 92
Adder
0.451
3146626S HERTFORD
Solar/Wind Harmer
-0.026
3145273HOLLAND
Solar/Wind Harmer
-0.019
316473AC1-191 GEN
Solar/Wind Harmer
2.785
3141843SHACKLE
Adder
1.16
316203AE2-005 GEN
Solar/Wind Harmer
10.757
316313AB2-026
Solar/Wind Harmer
0.688
316258AE1-075 C
Solar/Wind Harmer
0.619
316405AF2-144 C
Solar/Wind Harmer
0.653
3143336POWHATN
Solar/Wind Harmer
2.572
3146376EDENTON
Solar/Wind Harmer
-0.025
3141766HARMONY
Solar/Wind Harmer
2.268
316280AD1-041 GEN
Solar/Wind Harmer
1.917
316156AD2-030 GEN
Solar/Wind Harmer
0.677
3141873WAN 176
Solar/Wind Harmer
3.008
970917AG2-570 GEN
Solar/Wind Harmer
63.229
966881AG1-559 GEN
Solar/Wind Harmer
0.76
315614AA2-178 GEN
Solar/Wind Harmer
2.693
971157AH1-035 GEN
Solar/Wind Harmer
3.07
3156081AA2-088 GEN
Solar/Wind Harmer
7.961
316365GEN2_N
Solar/Wind Harmer
1.652
315737AD1-076 GEN
Solar/Wind Harmer
4.654
3150401LDYSMT4
Adder
29.156
3150371LDYSMT1
Adder
28.172
962971AG1-146 GEN
Solar/Wind Harmer
4.557
3146206CASHIE
Solar/Wind Harmer
-0.024
3145893MURPHYS
Solar/Wind Harmer
0.169
3145893MURPHYS
Solar/Wind Harmer
-0.024
957521AF2-046 GEN
Solar/Wind Harmer
19.023
961681AG1-008 GEN
Solar/Wind Harmer
19.023
316484AD2-074 GEN
Solar/Wind Harmer
6.058
970009AG2-005 GEN
Solar/Wind Harmer
3.008
3146173TUNIS
Solar/Wind Harmer
-0.024
3156021HOLLOMANSOL
Solar/Wind Harmer
3.225
966621AG1-532 GEN
Solar/Wind Harmer
0.485
316463AE2-346 GEN
Solar/Wind Harmer
0.387
316140AB2-099
Solar/Wind Harmer
0.161
962331AG1-082 GEN
Solar/Wind Harmer
2.986
316404AE1-155 C
Solar/Wind Harmer
4.568
3146263WOODLND
Solar/Wind Harmer
-0.024
313506AB2-031 GEN
Solar/Wind Harmer
1.897
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3145963POPLR C
Solar/Wind Harmer
-0.023
316317KELFORD C
Solar/Wind Harmer
1.1
3145823KELFORD
Solar/Wind Harmer
-0.023
316478AD1-087 GEN
Solar/Wind Harmer
2.009
316486AD2-202 GEN
Solar/Wind Harmer
0.588
3147043LAWRENC
Solar/Wind Harmer
-0.014
3145796HORNRTN
Solar/Wind Harmer
-0.092
3145796HORNRTN
Solar/Wind Harmer
-0.023
3150351NORNECKC2
Adder
2.075
316210AC1-098 GEN
Solar/Wind Harmer
3.537
3144293JTRSVLE
Adder
0.605
972255AH1-712 GEN
Adder
74.962
3151761LOISA E
Adder
17.688
972183AH1-676 GEN
Adder
136.298
3141316ARNOLDS
Adder
0.29
316044AC1-158 PL1
Solar/Wind Helper
5.216
316450AC1-158 RIC
Solar/Wind Helper
1.391
3141196NOKESVL
Solar/Wind Helper
1.131
LAGNLTFEXP_LAGN->PJM
CLTF
8.398
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.505
TVALTFEXP_TVA->PJM
CLTF
4.252
CPLELTFEXP_CPLE->PJM
CLTF
12.136
CBM West 2LTFEXP_CBM-W2->PJM
CBM
43.163
NYPJM->LTFIMP_NY
CLTF
3.266
LGEELTFEXP_LGEE->PJM
CLTF
1.371
WECLTFEXP_WEC->PJM
CLTF
0.662
CBM West 1LTFEXP_CBM-W1->PJM
CBM
22.027
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.441
MECLTFEXP_MEC->PJM
CLTF
3.751
SIGELTFEXP_SIGE->PJM
CLTF
0.114

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 552_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:179.85 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:5791.82
MW Contribution:1.71
Bus #Bus NameTypeMW Contribution
3152261N ANNA2
50/50
19.95
3150861SPRUNCD
50/50
1.216
3143096IRON208
50/50
1.079
3143096IRON208
50/50
1.057
3150801HOPHCF4
50/50
1.421
971211AH1-065 GEN
50/50
1.714
3151161SURRY 1
50/50
9.199
316044AC1-158 PL1
Solar/Wind Harmer
3.047
316450AC1-158 RIC
Solar/Wind Harmer
0.812
3147666LOUISA
Solar/Wind Harmer
0.63
315839AE2-212 C
Solar/Wind Harmer
0.002
315773AC2-141 GEN
Solar/Wind Harmer
8.863
965281AG1-393 GEN
Solar/Wind Harmer
2.583
970133AG2-095 GEN
Solar/Wind Harmer
2.314
315813AE1-149 C
Solar/Wind Harmer
12.857
970129AG2-093 GEN
Solar/Wind Harmer
14.547
944581AF1-123 GEN
Solar/Wind Harmer
54.129
944601AF1-125 GEN
Solar/Wind Harmer
53.295
315778AD1-151 GEN
Solar/Wind Harmer
19.229
3151101ELIZAR3
Adder
22.283
3144536CHRHLND
Solar/Wind Harmer
0.036
3144873MCLAUGH
Solar/Wind Harmer
0.006
970659AG2-427 GEN
Solar/Wind Harmer
2.537
961611AG1-000B GEN
Solar/Wind Harmer
6.393
3145336SMITFLD
Solar/Wind Harmer
0.096
316083AB2-161 GEN
Solar/Wind Harmer
0.003
3151221GRAVEL6
Adder
17.41
3151171GRAVELC
Adder
3.35
970293AG2-193 GEN
Solar/Wind Harmer
2.553
3142946ENON
Solar/Wind Harmer
0.08
970661AG2-428 GEN
Solar/Wind Harmer
5.055
3142416OLDCHRC
Solar/Wind Harmer
2.311
3144216WINCHST
Adder
0.896
3146456SLIGO L269
Solar/Wind Harmer
0.237
971153AH1-033 GEN
Solar/Wind Harmer
2.744
3150921YORKTN3
Adder
5.966
316382AG1-145 C
Solar/Wind Harmer
0.002
316320Y1-086
Solar/Wind Harmer
0.001
316435W1029_GEN3
Solar/Wind Harmer
0.001
3142433PROV 92
Adder
0.452
3142433PROV 92
Adder
0.452
3146516WINFALL
Solar/Wind Harmer
0.232
316473AC1-191 GEN
Solar/Wind Harmer
0.781
3146626S HERTFORD
Solar/Wind Harmer
0.231
3145273HOLLAND
Solar/Wind Harmer
0.173
316313AB2-026
Solar/Wind Harmer
0.144
316258AE1-075 C
Solar/Wind Harmer
0.172
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.453
3141843SHACKLE
Adder
1.161
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
3141766HARMONY
Solar/Wind Harmer
3.026
316280AD1-041 GEN
Solar/Wind Harmer
0.005
3146376EDENTON
Solar/Wind Harmer
0.226
316156AD2-030 GEN
Solar/Wind Harmer
0.167
3141873WAN 176
Solar/Wind Harmer
4.013
970917AG2-570 GEN
Solar/Wind Harmer
19.927
315614AA2-178 GEN
Solar/Wind Harmer
1.269
3150401LDYSMT4
Adder
29.389
3150371LDYSMT1
Adder
28.398
971157AH1-035 GEN
Solar/Wind Harmer
2.618
3156081AA2-088 GEN
Solar/Wind Harmer
0.005
316365GEN2_N
Solar/Wind Harmer
0.488
315737AD1-076 GEN
Solar/Wind Harmer
2.798
962971AG1-146 GEN
Solar/Wind Harmer
3.462
3146206CASHIE
Solar/Wind Harmer
0.215
3145893MURPHYS
Solar/Wind Harmer
0.36
3145893MURPHYS
Solar/Wind Harmer
0.215
957521AF2-046 GEN
Solar/Wind Harmer
15.963
961681AG1-008 GEN
Solar/Wind Harmer
15.963
970009AG2-005 GEN
Solar/Wind Harmer
1.6
3146173TUNIS
Solar/Wind Harmer
0.213
3156021HOLLOMANSOL
Solar/Wind Harmer
0.965
316463AE2-346 GEN
Solar/Wind Harmer
0.182
316140AB2-099
Solar/Wind Harmer
0.076
962331AG1-082 GEN
Solar/Wind Harmer
2.263
316404AE1-155 C
Solar/Wind Harmer
0.047
3146263WOODLND
Solar/Wind Harmer
0.21
313506AB2-031 GEN
Solar/Wind Harmer
0.648
3142666NORTHAMPTON
Solar/Wind Harmer
0.209
3145963POPLR C
Solar/Wind Harmer
0.207
316317KELFORD C
Solar/Wind Harmer
0.02
3145823KELFORD
Solar/Wind Harmer
0.207
316478AD1-087 GEN
Solar/Wind Harmer
0.72
316486AD2-202 GEN
Solar/Wind Harmer
0.211
3147043LAWRENC
Solar/Wind Harmer
0.124
3145796HORNRTN
Solar/Wind Harmer
0.82
3145796HORNRTN
Solar/Wind Harmer
0.205
3150351NORNECKC2
Adder
2.075
316210AC1-098 GEN
Solar/Wind Harmer
1.857
3145933PARMELE
Solar/Wind Harmer
0.199
966801AG1-551 GEN
Solar/Wind Harmer
2.319
970909AG2-566 GEN
Solar/Wind Harmer
2.12
971781AH1-399 GEN
Solar/Wind Harmer
0.26
3145746EVERETS
Solar/Wind Harmer
0.195
3145746EVERETS
Solar/Wind Harmer
0.195
315724AD1-057 GEN
Solar/Wind Harmer
0.731
316327AA2-057 GEN
Solar/Wind Harmer
0.292
316131AB2-060 GEN
Solar/Wind Harmer
0.605
964241AG1-285 GEN
Solar/Wind Harmer
12.823
315785AD2-033 C
Solar/Wind Harmer
1.561
970257AG2-171 GEN
Solar/Wind Harmer
6.143
959311AF2-222 GEN
Solar/Wind Harmer
17.057
963181AG1-167 GEN
Solar/Wind Harmer
0.766
3144293JTRSVLE
Adder
0.609
3147133PAMPLIN
Solar/Wind Harmer
0.6
971193AH1-056 GEN
Solar/Wind Harmer
11.648
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146926FARMVIL
Solar/Wind Harmer
0.114
3146233WITAKRS
Solar/Wind Harmer
0.953
3146233WITAKRS
Solar/Wind Harmer
0.129
3146073TAR RVR
Solar/Wind Harmer
0.189
3146083TARBORO
Solar/Wind Harmer
0.189
3138543CONSLDL
Solar/Wind Harmer
0.125
3132273ORANGE
Solar/Wind Harmer
0.038
961601AG1-000A GEN
Solar/Wind Harmer
13.257
3145543BTLEBRO
Solar/Wind Harmer
0.186
3145543BTLEBRO
Solar/Wind Harmer
0.186
971623AH1-311 GEN
Solar/Wind Harmer
0.373
3141906WESTMOR
Solar/Wind Harmer
0.074
3146776BUCKING
Solar/Wind Harmer
0.066
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
7.481
970737AG2-469 GEN
Solar/Wind Harmer
7.427
316170AC1-121 GEN2
Solar/Wind Harmer
0.183
3151761LOISA E
Adder
22.218
972183AH1-676 GEN
Adder
173.787
970221AG2-151 GEN
Solar/Wind Harmer
8.67
971683AH1-343 GEN
Solar/Wind Harmer
5.958
316283AC2-100 C
Solar/Wind Harmer
0.309
972255AH1-712 GEN
Adder
76.037
3141316ARNOLDS
Adder
0.289
3141196NOKESVL
Solar/Wind Helper
1.164
971133AH1-012 GEN
50/50
5.665
944641AF1-129 GEN
50/50
122.768
3142366NRTHEST
50/50
0.838
970533AG2-339 GEN
50/50
21.472
970531AG2-338 GEN
50/50
8.589
3150781HOPHCF2
50/50
0.977
3150791HOPHCF3
50/50
0.977
3150761HOPPOLC
50/50
0.62
971213AH1-066 GEN
50/50
0.857
3150691DARBY 3
50/50
18.39
316447AC1-158 HLD
Solar/Wind Harmer
6.696
971223AH1-071 GEN
Solar/Wind Harmer
2.827
3143526WINTERP
Solar/Wind Harmer
1.34
316240AF1-291 C
Solar/Wind Harmer
0.002
3150701DARBY 4
Adder
17.29
3150681DARBY 2
Adder
17.27
3150671DARBY 1
Adder
17.25
3142296MT RD221
Adder
0.765
316033AB2-134 GEN
Solar/Wind Harmer
0.014
315697AD1-025 GEN
Solar/Wind Harmer
0.27
316036AC1-147 C
Solar/Wind Harmer
0.045
3150991CHESPKB
Adder
2.513
3150991CHESPKB
Adder
2.452
316236AE1-162_GEN
Solar/Wind Harmer
0.002
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.23
316185AD1-033 GEN
Solar/Wind Harmer
0.007
970657AG2-426 GEN
Solar/Wind Harmer
8.383
970657AG2-426 GEN
Solar/Wind Harmer
1.758
3142946ENON
Solar/Wind Harmer
0.024
3145506HICKORY
Solar/Wind Harmer
0.955
3145506HICKORY
Solar/Wind Harmer
0.573
3145506HICKORY
Solar/Wind Harmer
0.143
316339AD2-160 GEN
Solar/Wind Harmer
0.386
316018AA1-139 ULT2
Solar/Wind Harmer
0.006
316017AA1-139 ULT1
Solar/Wind Harmer
0.133
316075AC2-137 C
Solar/Wind Harmer
0.065
3137176SLIGO L2192
Solar/Wind Harmer
0.945
3146456SLIGO L269
Solar/Wind Harmer
4.201
3130086AYDLETT
Solar/Wind Harmer
0.948
972185AH1-677 GEN
Adder
13.205
3144356SAPONY
Solar/Wind Harmer
1.967
3146386ELIZ CT
Solar/Wind Harmer
0.235
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
972187AH1-678 GEN
Adder
6.623
3146516WINFALL
Solar/Wind Harmer
0.232
3146516WINFALL
Solar/Wind Harmer
0.232
3146516WINFALL
Solar/Wind Harmer
0.232
966871AG1-558 GEN
Solar/Wind Harmer
0.267
3146626S HERTFORD
Solar/Wind Harmer
0.231
3146626S HERTFORD
Solar/Wind Harmer
0.231
970933AG2-581 GEN
Solar/Wind Harmer
18.312
315742AE1-103 GEN
Solar/Wind Harmer
0.003
957411AF2-035 GEN
Solar/Wind Harmer
9.66
970317AG2-208 GEN
Solar/Wind Harmer
8.949
3146376EDENTON
Solar/Wind Harmer
1.006
3146376EDENTON
Solar/Wind Harmer
1.006
315673AE1-157 GEN
Solar/Wind Harmer
15.472
3150391LDYSMT3
Adder
29.334
972195AH1-682 GEN
Adder
3.855
316065AD1-022 GEN
Solar/Wind Harmer
9.955
3145893MURPHYS
Solar/Wind Harmer
1.439
3145893MURPHYS
Solar/Wind Harmer
0.387
970099AG2-077 GEN
Solar/Wind Harmer
22.861
3146173TUNIS
Solar/Wind Harmer
0.213
3146173TUNIS
Solar/Wind Harmer
0.213
958261AF2-120 GEN
Solar/Wind Harmer
6.972
316181AB2-040 GEN
Solar/Wind Harmer
0.304
3142666NORTHAMPTON
Solar/Wind Harmer
0.209
3142666NORTHAMPTON
Solar/Wind Harmer
0.209
3142666NORTHAMPTON
Solar/Wind Harmer
0.209
3142666NORTHAMPTON
Solar/Wind Harmer
0.125
316426AA2-053 GEN
Solar/Wind Harmer
0.701
3145593CAROLNA
Solar/Wind Harmer
0.207
3145593CAROLNA
Solar/Wind Harmer
0.207
966811AG1-552 GEN
Solar/Wind Harmer
2.242
3145593CAROLNA
Solar/Wind Harmer
0.257
3145783HORNRTN
Solar/Wind Harmer
3.653
3145783HORNRTN
Solar/Wind Harmer
2.922
3145783HORNRTN
Solar/Wind Harmer
0.913
3145783HORNRTN
Solar/Wind Harmer
0.365
3145796HORNRTN
Solar/Wind Harmer
0.615
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
2.144
3150341NORNECKC1
Adder
2.127
971741AH1-377 GEN
Solar/Wind Harmer
19.978
3145933PARMELE
Solar/Wind Harmer
0.398
3145933PARMELE
Solar/Wind Harmer
0.199
316274AC1-208 GEN
Solar/Wind Harmer
1.032
970301AG2-198 GEN
Solar/Wind Harmer
8.48
316468AD1-105 GEN
Solar/Wind Harmer
-0.064
939181AE1-148 GEN
Solar/Wind Harmer
9.287
313527AB2-043 GEN
Solar/Wind Harmer
0.002
316034AC1-036 C
Solar/Wind Harmer
0.014
970323AG2-213 GEN
Solar/Wind Harmer
8.19
971775AH1-396 GEN
Solar/Wind Harmer
0.307
958211AF2-115 GEN
Solar/Wind Harmer
2.298
963191AG1-168 GEN
Solar/Wind Harmer
0.766
3144293JTRSVLE
Adder
0.609
3144293JTRSVLE
Adder
0.513
3147133PAMPLIN
Solar/Wind Harmer
0.191
3147133PAMPLIN
Solar/Wind Harmer
0.153
3145493TOT1
Solar/Wind Harmer
0.439
3145453TOT5
Solar/Wind Harmer
0.264
3145603CNETO
Solar/Wind Harmer
0.176
961601AG1-000A GEN
Solar/Wind Harmer
3.314
316263AC1-034 GEN
Solar/Wind Harmer
7.082
962561AG1-105 GEN
Solar/Wind Harmer
8.835
3146776BUCKING
Solar/Wind Harmer
0.73
3146776BUCKING
Solar/Wind Harmer
0.059
964791AG1-342 GEN
Solar/Wind Harmer
3.505
3146843MT LREL
Solar/Wind Harmer
0.182
3146843MT LREL
Solar/Wind Harmer
0.182
966001AG1-469 GEN
Solar/Wind Harmer
0.098
3151731LOISA B
Adder
10.898
3151721LOISA A
Adder
10.842
971489AH1-241 GEN
Solar/Wind Harmer
8.67
316222AC1-221 GEN
Solar/Wind Harmer
0.658
315821AE2-092 GEN
Solar/Wind Harmer
0.008
942751AE2-291 GEN
Solar/Wind Harmer
7.283
315651AD1-115 GEN
Solar/Wind Harmer
0.004
971531AH1-263 GEN
50/50
60.398
316303AF2-085
50/50
4.712
971285AH1-108 GEN
50/50
1.991
970603AG2-384 GEN
50/50
5.178
316164AC1-076 GEN
Solar/Wind Harmer
0.448
316233AE1-074 FULL
Solar/Wind Harmer
0.206
971281AH1-106 GEN
Solar/Wind Harmer
3.576
971283AH1-107 GEN
Solar/Wind Harmer
3.576
3143316POE
Solar/Wind Harmer
0.962
941031AE2-094 GEN
Solar/Wind Harmer
44.489
944011AF1-069 GEN
Solar/Wind Harmer
14.536
316132AB2-190 GEN1
Solar/Wind Harmer
1.291
316369SG1_INVT
Solar/Wind Harmer
0.009
3151081ELIZAR1
Adder
22.001
3151091ELIZAR2
Adder
21.619
3152611GOSPORTB
Adder
3.055
3152621GOSPORTC
Adder
2.593
3152601GOSPORTA
Adder
2.392
971445AH1-216 GEN
Solar/Wind Harmer
16.874
972265AH1-717 GEN
Adder
18.594
3151201GRAVEL4
Adder
17.43
3151191GRAVEL3
Adder
17.21
3151211GRAVEL5
Adder
17.21
316312AB1-027
Solar/Wind Harmer
0.427
957871AF2-081 GEN
Solar/Wind Harmer
11.843
970673AG2-436 GEN
Solar/Wind Harmer
50.646
970673AG2-436 GEN
Solar/Wind Harmer
33.764
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.163
319010AE1-072 C
Solar/Wind Harmer
1.195
316311AC2-079 GEN
Solar/Wind Harmer
6.813
3146406KITTY HAWK
Solar/Wind Harmer
0.03
316305AF2-043 C
Solar/Wind Harmer
0.002
315976AC1-164 GENA
Solar/Wind Harmer
24.491
316169AC1-164_GENC
Solar/Wind Harmer
21.158
315975AC1-164 GENB
Solar/Wind Harmer
0.725
315835AF2-110_GEN
Solar/Wind Harmer
1.619
316315AB2-025 C
Solar/Wind Harmer
0.19
313526AB2-022
Solar/Wind Harmer
0.127
972189AH1-679 GEN
Adder
3.932
3146486SUNBURY
Solar/Wind Harmer
0.234
3146486SUNBURY
Solar/Wind Harmer
0.234
971967AH1-528 GEN
Solar/Wind Harmer
37.517
315814AE2-033 C
Solar/Wind Harmer
18.537
316321Z2-027
Solar/Wind Harmer
0.044
3146396TANGLEW
Solar/Wind Harmer
0.645
3145176PASQUOTANK
Solar/Wind Harmer
0.145
971167AH1-042 GEN
Solar/Wind Harmer
20.705
3142433PROV 92
Adder
0.452
3142433PROV 92
Adder
0.452
3138283WHITEMARSH
Solar/Wind Harmer
0.054
3143873LANEXA
Solar/Wind Harmer
0.138
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
316314AB2-024 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
6.735
316059AD1-063 C
Solar/Wind Harmer
0.001
315662AE1-191 GEN
Solar/Wind Harmer
0.007
315666AE1-190 GEN
Solar/Wind Harmer
0.002
3130156CHOWAN
Solar/Wind Harmer
0.226
3130156CHOWAN
Solar/Wind Harmer
0.226
3141873WAN 176
Solar/Wind Harmer
0.045
970085AG2-068 GEN
Solar/Wind Harmer
11.907
970581AG2-369 GEN
Solar/Wind Harmer
10.24
3141913WHIT STONE
Solar/Wind Harmer
0.222
3138133OCRAN
Solar/Wind Harmer
0.066
315816AE2-034 GEN
Solar/Wind Harmer
0.951
3141783LANCAST
Solar/Wind Harmer
0.132
3141783LANCAST
Solar/Wind Harmer
0.088
3150411LDYSMT5
Adder
29.481
3150381LDYSMT2
Adder
28.214
972213AH1-691 GEN
Adder
4.773
972215AH1-692 GEN
Adder
4.773
3130546PLYMOUTH
Solar/Wind Harmer
0.218
315732AD1-074 GEN1
Solar/Wind Harmer
1.25
315733AD1-074 GEN2
Solar/Wind Harmer
1.25
315735AD1-075 GEN1
Solar/Wind Harmer
0.626
965291AG1-394 GEN
Solar/Wind Harmer
0.964
962981AG1-147 GEN
Solar/Wind Harmer
8.079
3146206CASHIE
Solar/Wind Harmer
0.215
970601AG2-382 GEN
Solar/Wind Harmer
8.044
3145893MURPHYS
Solar/Wind Harmer
0.581
3145893MURPHYS
Solar/Wind Harmer
0.215
970327AG2-215 GEN
Solar/Wind Harmer
7.032
3145513AHOSKIE
Solar/Wind Harmer
0.443
3145513AHOSKIE
Solar/Wind Harmer
0.212
3146043SEABORD
Solar/Wind Harmer
0.211
3145683EARLEYS
Solar/Wind Harmer
0.422
3145683EARLEYS
Solar/Wind Harmer
0.211
3145683EARLEYS
Solar/Wind Harmer
0.211
315607AA1-063A GEN
Solar/Wind Harmer
0.431
316087AB2-174 GEN
Solar/Wind Harmer
0.006
315652AC1-086 GEN
Solar/Wind Harmer
22.91
3137643SOCKMAN
Solar/Wind Harmer
0.831
3145796HORNRTN
Solar/Wind Harmer
0.656
3145796HORNRTN
Solar/Wind Harmer
0.082
3141813NORNECK
Solar/Wind Harmer
0.205
3146033SCOT NK
Solar/Wind Harmer
0.813
970831AG2-522 GEN
Solar/Wind Harmer
8.493
316005AA1-067
Solar/Wind Harmer
0.209
3145746EVERETS
Solar/Wind Harmer
0.776
3145746EVERETS
Solar/Wind Harmer
0.195
3145746EVERETS
Solar/Wind Harmer
0.195
3145746EVERETS
Solar/Wind Harmer
0.195
970181AG2-120 GEN
Solar/Wind Harmer
2.429
957861AF2-080 GEN
Solar/Wind Harmer
8.286
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
971443AH1-215 GEN
Solar/Wind Harmer
3.225
3144303KENBRDG
Solar/Wind Harmer
0.153
970683AG2-441 GEN
Solar/Wind Harmer
12.781
970681AG2-440 GEN
Solar/Wind Harmer
10.225
946301AF1-294 GEN
Solar/Wind Harmer
3.778
961791AG1-021 GEN
Solar/Wind Harmer
1.838
315657AE1-056 GEN
Solar/Wind Harmer
6.598
316420AA1-050 GEN
Solar/Wind Harmer
0.006
316319Z2-044 C
Solar/Wind Harmer
0
3145573BETHELC
Solar/Wind Harmer
0.189
3145573BETHELC
Solar/Wind Harmer
0.189
970285AG2-188 GEN
Solar/Wind Harmer
14.603
316223AC1-118
Solar/Wind Harmer
0.132
971845AH1-439 GEN
Solar/Wind Harmer
8.313
316118AC1-105 GEN
Solar/Wind Harmer
0.462
3147173SINAI
Solar/Wind Harmer
0.175
3147243WELCO
Solar/Wind Harmer
0.11
972205AH1-687 GEN
Adder
7.416
3147346CASHSCORNER
Solar/Wind Harmer
0.37
944491AF1-114 GEN
Solar/Wind Harmer
0.001
971447AH1-217 GEN
Solar/Wind Harmer
4.798
970865AG2-541 GEN
Solar/Wind Harmer
5.388
972193AH1-681 GEN
Adder
3.397
270494AE1-108_GEN
Solar/Wind Harmer
1.716
316123AC1-075 GEN
Solar/Wind Harmer
0.194
970165AG2-112 GEN
Solar/Wind Harmer
1.153
970163AG2-111 GEN
Solar/Wind Harmer
1.1
3138266HYDRAULIC
Solar/Wind Harmer
0.006
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316411AF1-147_GEN1
Solar/Wind Helper
0.82
316415AF1-147_GEN2
Solar/Wind Helper
0.82
3138216PACIFIC
Solar/Wind Helper
0.04
3152251N ANNA1
50/50
19.951
971507AH1-251 GEN
50/50
16.627
970119AG2-088 GEN
50/50
35.342
3150851SPRUNCC
50/50
1.216
3143096IRON208
50/50
1.079
3152331SURRY 2
50/50
9.986
3150771HOPHCF1
50/50
0.977
316045AC1-158 PL2
Solar/Wind Harmer
9.742
3147666LOUISA
Solar/Wind Harmer
1.096
316192AB2-158 GEN
Solar/Wind Harmer
1.516
3143226MDLTHAN
Solar/Wind Harmer
0.265
3143526WINTERP
Solar/Wind Harmer
1.34
940641AE2-051 GEN
Solar/Wind Harmer
19.885
939411AE1-173 GEN
Solar/Wind Harmer
105.071
3142543TWELFTH
Solar/Wind Harmer
0.023
316294AC1-161 GEN
Solar/Wind Harmer
4.205
315671AE2-027_GEN
Solar/Wind Harmer
15.49
970129AG2-093 GEN
Solar/Wind Harmer
6.846
316458AB2-190 GEN2
Solar/Wind Harmer
1.291
944591AF1-124 GEN
Solar/Wind Harmer
54.321
971069AG2-661 GEN
Solar/Wind Harmer
4.273
944631AF1-128 GEN
Adder
114.478
316375AC2-012 GEN
Solar/Wind Harmer
0.006
3150981CHESPKA
Adder
2.995
971647AH1-324 GEN
Solar/Wind Harmer
10.238
970659AG2-427 GEN
Solar/Wind Harmer
11.598
961611AG1-000B GEN
Solar/Wind Harmer
12.573
3145336SMITFLD
Solar/Wind Harmer
0.958
316381AD1-082 GEN
Solar/Wind Harmer
0.25
3151171GRAVELC
Adder
2.547
970661AG2-428 GEN
Solar/Wind Harmer
23.769
3142416OLDCHRC
Solar/Wind Harmer
0.62
3142416OLDCHRC
Solar/Wind Harmer
0.237
316388AE2-253 GEN
Solar/Wind Harmer
0.746
3138126ROCKLANDING
Solar/Wind Harmer
0.109
3146456SLIGO L269
Solar/Wind Harmer
0.237
316072AD1-144
Solar/Wind Harmer
0.086
316159AE1-175 C
Solar/Wind Harmer
0.205
316246AF1-032 C
Solar/Wind Harmer
0.107
971317AH1-138 GEN
Solar/Wind Harmer
1.763
316093AE2-104_GEN
Solar/Wind Harmer
3.967
3142433PROV 92
Solar/Wind Harmer
0.929
3142433PROV 92
Adder
0.452
3142433PROV 92
Adder
0.452
3146516WINFALL
Solar/Wind Harmer
0.752
3146516WINFALL
Solar/Wind Harmer
0.232
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
4.063
971777AH1-397 GEN
Solar/Wind Harmer
0.6
3141843SHACKLE
Adder
1.161
3141766HARMONY
Solar/Wind Harmer
0.045
3130156CHOWAN
Solar/Wind Harmer
0.226
966881AG1-559 GEN
Solar/Wind Harmer
0.262
970919AG2-571 GEN
Solar/Wind Harmer
7.971
970087AG2-069 GEN
Solar/Wind Harmer
17.86
3138133OCRAN
Solar/Wind Harmer
0.133
3145663CRESWEL
Solar/Wind Harmer
0.62
971163AH1-040 GEN
Solar/Wind Harmer
17.736
972197AH1-683 GEN
Adder
4.589
972219AH1-694 GEN
Adder
3.304
316336AC2-165 C
Solar/Wind Harmer
0.009
316023GEN1_S
Solar/Wind Harmer
0.488
3146206CASHIE
Solar/Wind Harmer
0.215
971547AH1-271 GEN
Solar/Wind Harmer
4.597
3145893MURPHYS
Solar/Wind Harmer
0.86
3145893MURPHYS
Solar/Wind Harmer
0.956
957481AF2-042 GEN
Solar/Wind Harmer
57.154
3146173TUNIS
Solar/Wind Harmer
0.213
960081AF2-299 GEN
Solar/Wind Harmer
2.037
962861AG1-135 GEN
Solar/Wind Harmer
6.776
3145683EARLEYS
Solar/Wind Harmer
0.211
315693AD1-088 GEN
Solar/Wind Harmer
10.092
3146263WOODLND
Solar/Wind Harmer
0.21
962491AG1-098 GEN
Solar/Wind Harmer
11.964
316011AB1-132 GEN
Solar/Wind Harmer
3.787
962571AG1-106 GEN
Solar/Wind Harmer
2.963
971795AH1-408 GEN
Solar/Wind Harmer
13.875
3145963POPLR C
Solar/Wind Harmer
0.207
3141726DUNNSVL
Solar/Wind Harmer
0.83
316190AA2-174 GEN
Solar/Wind Harmer
0
3145823KELFORD
Solar/Wind Harmer
0.207
3147043LAWRENC
Adder
1.866
316174AB2-169 GEN
Solar/Wind Harmer
0.005
3145783HORNRTN
Solar/Wind Harmer
0.205
3145796HORNRTN
Solar/Wind Harmer
0.677
3145796HORNRTN
Solar/Wind Harmer
0.205
3150351NORNECKC2
Adder
2.041
316212AC1-099_GEN
Solar/Wind Harmer
1.035
3146293MARTNCO
Solar/Wind Harmer
0.185
316129AC1-054 GEN
Solar/Wind Harmer
0.746
971065AG2-659 GEN
Solar/Wind Harmer
8.425
3145746EVERETS
Solar/Wind Harmer
0.195
3145746EVERETS
Solar/Wind Harmer
0.195
315722AD1-056 GEN
Solar/Wind Harmer
1.233
316337AD2-073 GEN
Solar/Wind Harmer
0.169
970937AG2-583 GEN
Solar/Wind Harmer
11.922
315687AD1-152 GEN
Solar/Wind Harmer
0.006
316494AC1-189 GEN
Solar/Wind Harmer
0.649
316237AB2-079_GEN
Solar/Wind Harmer
0.002
970685AG2-442 GEN
Solar/Wind Harmer
14.314
963171AG1-166 GEN
Solar/Wind Harmer
1.021
971563AH1-280 GEN
Solar/Wind Harmer
2.042
3144293JTRSVLE
Adder
0.609
3146926FARMVIL
Solar/Wind Harmer
0.114
3146233WITAKRS
Solar/Wind Harmer
0.755
961671AG1-007 GEN
Solar/Wind Harmer
0.029
3146083TARBORO
Solar/Wind Harmer
0.189
3145493TOT1
Solar/Wind Harmer
0.843
3145543BTLEBRO
Solar/Wind Harmer
0.186
3145543BTLEBRO
Solar/Wind Harmer
0.149
316359AB2-059 GEN
Solar/Wind Harmer
0.669
316049AB1-081 GEN
Solar/Wind Harmer
1.066
3142053HEARTS
Solar/Wind Harmer
0.328
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.073
970401AG2-262 GEN
Solar/Wind Harmer
1.071
972003AH1-546 GEN
Solar/Wind Harmer
7.446
316254AC1-120 GEN1
Solar/Wind Harmer
0.366
316003AC1-222 GEN
Solar/Wind Harmer
0.004
3151751LOISA D
Adder
10.898
972135AH1-637 GEN
Solar/Wind Harmer
1.429
971377AH1-170 GEN
Solar/Wind Harmer
1.734
3147623JAMES R
Solar/Wind Harmer
0.377
972277AH1-723 GEN
Adder
88.606
LAGNLTFEXP_LAGN->PJM
CLTF
8.202
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.311
TVALTFEXP_TVA->PJM
CLTF
4.157
CPLELTFEXP_CPLE->PJM
CLTF
12.074
CBM West 2LTFEXP_CBM-W2->PJM
CBM
41.739
NYPJM->LTFIMP_NY
CLTF
3.433
LGEELTFEXP_LGEE->PJM
CLTF
1.291
WECLTFEXP_WEC->PJM
CLTF
0.616
CBM West 1LTFEXP_CBM-W1->PJM
CBM
20.192
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.068
MECLTFEXP_MEC->PJM
CLTF
3.555
SIGELTFEXP_SIGE->PJM
CLTF
0.108

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 581_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:175.06 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:5637.7
MW Contribution:1.69
Bus #Bus NameTypeMW Contribution
3152261N ANNA2
50/50
19.717
3150861SPRUNCD
50/50
1.197
3143096IRON208
50/50
1.062
3143096IRON208
50/50
1.041
3150801HOPHCF4
50/50
1.399
971211AH1-065 GEN
50/50
1.687
3151161SURRY 1
50/50
9.055
316044AC1-158 PL1
Solar/Wind Harmer
3.023
316450AC1-158 RIC
Solar/Wind Harmer
0.806
3147666LOUISA
Solar/Wind Harmer
0.614
315839AE2-212 C
Solar/Wind Harmer
0.002
315773AC2-141 GEN
Solar/Wind Harmer
8.726
965281AG1-393 GEN
Solar/Wind Harmer
2.543
315813AE1-149 C
Solar/Wind Harmer
12.658
970133AG2-095 GEN
Solar/Wind Harmer
2.278
970129AG2-093 GEN
Solar/Wind Harmer
14.319
944581AF1-123 GEN
Solar/Wind Harmer
53.293
944601AF1-125 GEN
Solar/Wind Harmer
52.472
315778AD1-151 GEN
Solar/Wind Harmer
18.928
3151101ELIZAR3
Adder
21.938
3144536CHRHLND
Solar/Wind Harmer
0.035
3144873MCLAUGH
Solar/Wind Harmer
0.006
970659AG2-427 GEN
Solar/Wind Harmer
2.498
3145336SMITFLD
Solar/Wind Harmer
0.094
961611AG1-000B GEN
Solar/Wind Harmer
6.293
316083AB2-161 GEN
Solar/Wind Harmer
0.003
3151221GRAVEL6
Adder
17.139
3151171GRAVELC
Adder
3.297
970293AG2-193 GEN
Solar/Wind Harmer
2.512
970661AG2-428 GEN
Solar/Wind Harmer
4.977
3142946ENON
Solar/Wind Harmer
0.079
3142416OLDCHRC
Solar/Wind Harmer
2.274
3144216WINCHST
Adder
0.882
3146456SLIGO L269
Solar/Wind Harmer
0.234
971153AH1-033 GEN
Solar/Wind Harmer
2.702
3150921YORKTN3
Adder
5.872
316382AG1-145 C
Solar/Wind Harmer
0.002
316320Y1-086
Solar/Wind Harmer
0.001
316435W1029_GEN3
Solar/Wind Harmer
0.001
3142433PROV 92
Adder
0.445
3142433PROV 92
Adder
0.445
3146516WINFALL
Solar/Wind Harmer
0.229
316473AC1-191 GEN
Solar/Wind Harmer
0.768
3146626S HERTFORD
Solar/Wind Harmer
0.227
3145273HOLLAND
Solar/Wind Harmer
0.17
316313AB2-026
Solar/Wind Harmer
0.142
316258AE1-075 C
Solar/Wind Harmer
0.17
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.394
3141843SHACKLE
Adder
1.143
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
3141766HARMONY
Solar/Wind Harmer
2.978
316280AD1-041 GEN
Solar/Wind Harmer
0.005
3146376EDENTON
Solar/Wind Harmer
0.223
316156AD2-030 GEN
Solar/Wind Harmer
0.165
3141873WAN 176
Solar/Wind Harmer
3.95
970917AG2-570 GEN
Solar/Wind Harmer
19.626
315614AA2-178 GEN
Solar/Wind Harmer
1.249
3150401LDYSMT4
Adder
28.893
3150371LDYSMT1
Adder
27.918
971157AH1-035 GEN
Solar/Wind Harmer
2.577
3156081AA2-088 GEN
Solar/Wind Harmer
0.005
316365GEN2_N
Solar/Wind Harmer
0.481
315737AD1-076 GEN
Solar/Wind Harmer
2.755
962971AG1-146 GEN
Solar/Wind Harmer
3.408
3146206CASHIE
Solar/Wind Harmer
0.212
3145893MURPHYS
Solar/Wind Harmer
0.354
3145893MURPHYS
Solar/Wind Harmer
0.212
957521AF2-046 GEN
Solar/Wind Harmer
15.715
961681AG1-008 GEN
Solar/Wind Harmer
15.715
970009AG2-005 GEN
Solar/Wind Harmer
1.575
3146173TUNIS
Solar/Wind Harmer
0.21
3156021HOLLOMANSOL
Solar/Wind Harmer
0.95
316463AE2-346 GEN
Solar/Wind Harmer
0.179
316140AB2-099
Solar/Wind Harmer
0.075
962331AG1-082 GEN
Solar/Wind Harmer
2.227
316404AE1-155 C
Solar/Wind Harmer
0.047
3146263WOODLND
Solar/Wind Harmer
0.207
313506AB2-031 GEN
Solar/Wind Harmer
0.638
3142666NORTHAMPTON
Solar/Wind Harmer
0.205
3145963POPLR C
Solar/Wind Harmer
0.204
316317KELFORD C
Solar/Wind Harmer
0.02
3145823KELFORD
Solar/Wind Harmer
0.204
316478AD1-087 GEN
Solar/Wind Harmer
0.708
316486AD2-202 GEN
Solar/Wind Harmer
0.208
3147043LAWRENC
Solar/Wind Harmer
0.122
3145796HORNRTN
Solar/Wind Harmer
0.807
3145796HORNRTN
Solar/Wind Harmer
0.202
3150351NORNECKC2
Adder
2.043
316210AC1-098 GEN
Solar/Wind Harmer
1.828
3145933PARMELE
Solar/Wind Harmer
0.196
966801AG1-551 GEN
Solar/Wind Harmer
2.283
970909AG2-566 GEN
Solar/Wind Harmer
2.083
971781AH1-399 GEN
Solar/Wind Harmer
0.256
3145746EVERETS
Solar/Wind Harmer
0.192
3145746EVERETS
Solar/Wind Harmer
0.192
315724AD1-057 GEN
Solar/Wind Harmer
0.72
316327AA2-057 GEN
Solar/Wind Harmer
0.287
316131AB2-060 GEN
Solar/Wind Harmer
0.595
964241AG1-285 GEN
Solar/Wind Harmer
12.61
315785AD2-033 C
Solar/Wind Harmer
1.535
970257AG2-171 GEN
Solar/Wind Harmer
6.039
959311AF2-222 GEN
Solar/Wind Harmer
16.767
963181AG1-167 GEN
Solar/Wind Harmer
0.752
3144293JTRSVLE
Adder
0.599
3147133PAMPLIN
Solar/Wind Harmer
0.59
971193AH1-056 GEN
Solar/Wind Harmer
11.443
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146233WITAKRS
Solar/Wind Harmer
0.938
3146233WITAKRS
Solar/Wind Harmer
0.127
3146926FARMVIL
Solar/Wind Harmer
0.112
3146073TAR RVR
Solar/Wind Harmer
0.186
3146083TARBORO
Solar/Wind Harmer
0.186
3138543CONSLDL
Solar/Wind Harmer
0.123
961601AG1-000A GEN
Solar/Wind Harmer
13.049
3145543BTLEBRO
Solar/Wind Harmer
0.183
3145543BTLEBRO
Solar/Wind Harmer
0.183
971623AH1-311 GEN
Solar/Wind Harmer
0.367
3141906WESTMOR
Solar/Wind Harmer
0.072
3146776BUCKING
Solar/Wind Harmer
0.064
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
7.36
970737AG2-469 GEN
Solar/Wind Harmer
7.314
971683AH1-343 GEN
Solar/Wind Harmer
5.86
3151761LOISA E
Adder
21.054
970221AG2-151 GEN
Solar/Wind Harmer
8.48
3132273ORANGE
Solar/Wind Harmer
0.031
316283AC2-100 C
Solar/Wind Harmer
0.304
972183AH1-676 GEN
Adder
164.313
972255AH1-712 GEN
Adder
74.545
316170AC1-121 GEN2
Solar/Wind Harmer
0.13
3141316ARNOLDS
Adder
0.285
3141196NOKESVL
Solar/Wind Helper
1.139
971133AH1-012 GEN
50/50
5.548
944641AF1-129 GEN
50/50
120.841
970533AG2-339 GEN
50/50
21.15
970531AG2-338 GEN
50/50
8.46
3142366NRTHEST
50/50
0.824
3150781HOPHCF2
50/50
0.962
3150791HOPHCF3
50/50
0.962
3150761HOPPOLC
50/50
0.61
971213AH1-066 GEN
50/50
0.844
3150691DARBY 3
50/50
18.094
3150701DARBY 4
50/50
18.052
316447AC1-158 HLD
Solar/Wind Harmer
6.644
971223AH1-071 GEN
Solar/Wind Harmer
2.784
3143526WINTERP
Solar/Wind Harmer
1.319
316240AF1-291 C
Solar/Wind Harmer
0.002
3150681DARBY 2
Adder
16.992
3150671DARBY 1
Adder
16.973
3142296MT RD221
Adder
0.753
316033AB2-134 GEN
Solar/Wind Harmer
0.014
315697AD1-025 GEN
Solar/Wind Harmer
0.266
316036AC1-147 C
Solar/Wind Harmer
0.044
3150991CHESPKB
Adder
2.474
3150991CHESPKB
Adder
2.414
316236AE1-162_GEN
Solar/Wind Harmer
0.002
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.226
316185AD1-033 GEN
Solar/Wind Harmer
0.007
970657AG2-426 GEN
Solar/Wind Harmer
8.254
970657AG2-426 GEN
Solar/Wind Harmer
1.73
3145506HICKORY
Solar/Wind Harmer
0.94
3145506HICKORY
Solar/Wind Harmer
0.564
3145506HICKORY
Solar/Wind Harmer
0.141
3142946ENON
Solar/Wind Harmer
0.023
316339AD2-160 GEN
Solar/Wind Harmer
0.38
316018AA1-139 ULT2
Solar/Wind Harmer
0.006
316017AA1-139 ULT1
Solar/Wind Harmer
0.131
3137176SLIGO L2192
Solar/Wind Harmer
0.93
316075AC2-137 C
Solar/Wind Harmer
0.064
3146456SLIGO L269
Solar/Wind Harmer
4.136
3130086AYDLETT
Solar/Wind Harmer
0.933
972185AH1-677 GEN
Adder
13.007
3144356SAPONY
Solar/Wind Harmer
1.937
3146386ELIZ CT
Solar/Wind Harmer
0.231
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
972187AH1-678 GEN
Adder
6.523
3146516WINFALL
Solar/Wind Harmer
0.229
3146516WINFALL
Solar/Wind Harmer
0.229
3146516WINFALL
Solar/Wind Harmer
0.229
966871AG1-558 GEN
Solar/Wind Harmer
0.263
3146626S HERTFORD
Solar/Wind Harmer
0.227
3146626S HERTFORD
Solar/Wind Harmer
0.227
970933AG2-581 GEN
Solar/Wind Harmer
18.033
315742AE1-103 GEN
Solar/Wind Harmer
0.003
3146376EDENTON
Solar/Wind Harmer
0.99
3146376EDENTON
Solar/Wind Harmer
0.99
957411AF2-035 GEN
Solar/Wind Harmer
9.498
970317AG2-208 GEN
Solar/Wind Harmer
8.8
315673AE1-157 GEN
Solar/Wind Harmer
15.213
3150391LDYSMT3
Adder
28.839
972195AH1-682 GEN
Adder
3.79
316065AD1-022 GEN
Solar/Wind Harmer
9.8
3145893MURPHYS
Solar/Wind Harmer
1.417
3145893MURPHYS
Solar/Wind Harmer
0.381
970099AG2-077 GEN
Solar/Wind Harmer
22.503
3146173TUNIS
Solar/Wind Harmer
0.21
3146173TUNIS
Solar/Wind Harmer
0.21
958261AF2-120 GEN
Solar/Wind Harmer
6.863
316181AB2-040 GEN
Solar/Wind Harmer
0.299
3142666NORTHAMPTON
Solar/Wind Harmer
0.205
3142666NORTHAMPTON
Solar/Wind Harmer
0.205
3142666NORTHAMPTON
Solar/Wind Harmer
0.205
3142666NORTHAMPTON
Solar/Wind Harmer
0.123
316426AA2-053 GEN
Solar/Wind Harmer
0.69
3145593CAROLNA
Solar/Wind Harmer
0.203
3145593CAROLNA
Solar/Wind Harmer
0.203
966811AG1-552 GEN
Solar/Wind Harmer
2.207
3145593CAROLNA
Solar/Wind Harmer
0.253
3145783HORNRTN
Solar/Wind Harmer
3.596
3145783HORNRTN
Solar/Wind Harmer
2.876
3145783HORNRTN
Solar/Wind Harmer
0.899
3145783HORNRTN
Solar/Wind Harmer
0.36
3145796HORNRTN
Solar/Wind Harmer
0.606
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
2.11
3150341NORNECKC1
Adder
2.093
971741AH1-377 GEN
Solar/Wind Harmer
19.637
3145933PARMELE
Solar/Wind Harmer
0.392
3145933PARMELE
Solar/Wind Harmer
0.196
316274AC1-208 GEN
Solar/Wind Harmer
1.016
970301AG2-198 GEN
Solar/Wind Harmer
8.333
316468AD1-105 GEN
Solar/Wind Harmer
-0.063
939181AE1-148 GEN
Solar/Wind Harmer
9.137
313527AB2-043 GEN
Solar/Wind Harmer
0.002
316034AC1-036 C
Solar/Wind Harmer
0.014
970323AG2-213 GEN
Solar/Wind Harmer
8.051
971775AH1-396 GEN
Solar/Wind Harmer
0.302
958211AF2-115 GEN
Solar/Wind Harmer
2.257
963191AG1-168 GEN
Solar/Wind Harmer
0.752
3144293JTRSVLE
Adder
0.599
3144293JTRSVLE
Adder
0.504
3147133PAMPLIN
Solar/Wind Harmer
0.188
3147133PAMPLIN
Solar/Wind Harmer
0.15
3145493TOT1
Solar/Wind Harmer
0.432
3145453TOT5
Solar/Wind Harmer
0.259
3145603CNETO
Solar/Wind Harmer
0.173
961601AG1-000A GEN
Solar/Wind Harmer
3.262
316263AC1-034 GEN
Solar/Wind Harmer
6.97
962561AG1-105 GEN
Solar/Wind Harmer
8.691
964791AG1-342 GEN
Solar/Wind Harmer
3.448
3146843MT LREL
Solar/Wind Harmer
0.179
3146843MT LREL
Solar/Wind Harmer
0.179
3146776BUCKING
Solar/Wind Harmer
0.716
3146776BUCKING
Solar/Wind Harmer
0.058
3151731LOISA B
Adder
10.327
3151721LOISA A
Adder
10.274
971489AH1-241 GEN
Solar/Wind Harmer
8.48
316222AC1-221 GEN
Solar/Wind Harmer
0.648
966001AG1-469 GEN
Solar/Wind Harmer
0.09
315821AE2-092 GEN
Solar/Wind Harmer
0.008
942751AE2-291 GEN
Solar/Wind Harmer
7.158
316303AF2-085
50/50
4.641
971285AH1-108 GEN
50/50
1.959
970603AG2-384 GEN
50/50
5.097
316233AE1-074 FULL
Solar/Wind Harmer
0.203
971281AH1-106 GEN
Solar/Wind Harmer
3.521
971283AH1-107 GEN
Solar/Wind Harmer
3.521
3143316POE
Solar/Wind Harmer
0.947
941031AE2-094 GEN
Solar/Wind Harmer
43.824
944011AF1-069 GEN
Solar/Wind Harmer
14.319
316132AB2-190 GEN1
Solar/Wind Harmer
1.271
316369SG1_INVT
Solar/Wind Harmer
0.009
3151081ELIZAR1
Adder
21.661
3151091ELIZAR2
Adder
21.285
3152611GOSPORTB
Adder
3.008
3152621GOSPORTC
Adder
2.552
3152601GOSPORTA
Adder
2.355
971445AH1-216 GEN
Solar/Wind Harmer
16.611
972265AH1-717 GEN
Adder
18.304
3151201GRAVEL4
Adder
17.158
3151191GRAVEL3
Adder
16.941
3151211GRAVEL5
Adder
16.941
316312AB1-027
Solar/Wind Harmer
0.42
957871AF2-081 GEN
Solar/Wind Harmer
11.66
316164AC1-076 GEN
Solar/Wind Harmer
0.329
970673AG2-436 GEN
Solar/Wind Harmer
49.886
970673AG2-436 GEN
Solar/Wind Harmer
33.257
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.16
319010AE1-072 C
Solar/Wind Harmer
1.177
316311AC2-079 GEN
Solar/Wind Harmer
6.708
3146406KITTY HAWK
Solar/Wind Harmer
0.029
316305AF2-043 C
Solar/Wind Harmer
0.002
315976AC1-164 GENA
Solar/Wind Harmer
24.098
316169AC1-164_GENC
Solar/Wind Harmer
20.818
315975AC1-164 GENB
Solar/Wind Harmer
0.713
315835AF2-110_GEN
Solar/Wind Harmer
1.594
316315AB2-025 C
Solar/Wind Harmer
0.187
313526AB2-022
Solar/Wind Harmer
0.125
971967AH1-528 GEN
Solar/Wind Harmer
36.95
3146486SUNBURY
Solar/Wind Harmer
0.231
3146486SUNBURY
Solar/Wind Harmer
0.231
972189AH1-679 GEN
Adder
3.867
315814AE2-033 C
Solar/Wind Harmer
18.254
316321Z2-027
Solar/Wind Harmer
0.043
3146396TANGLEW
Solar/Wind Harmer
0.635
3145176PASQUOTANK
Solar/Wind Harmer
0.143
971167AH1-042 GEN
Solar/Wind Harmer
20.377
3142433PROV 92
Adder
0.445
3142433PROV 92
Adder
0.445
3138283WHITEMARSH
Solar/Wind Harmer
0.053
3143873LANEXA
Solar/Wind Harmer
0.135
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
316314AB2-024 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
6.628
316059AD1-063 C
Solar/Wind Harmer
0.001
315662AE1-191 GEN
Solar/Wind Harmer
0.007
315666AE1-190 GEN
Solar/Wind Harmer
0.002
3130156CHOWAN
Solar/Wind Harmer
0.223
3130156CHOWAN
Solar/Wind Harmer
0.223
3141873WAN 176
Solar/Wind Harmer
0.044
970085AG2-068 GEN
Solar/Wind Harmer
11.727
970581AG2-369 GEN
Solar/Wind Harmer
10.085
3141913WHIT STONE
Solar/Wind Harmer
0.219
3138133OCRAN
Solar/Wind Harmer
0.065
315816AE2-034 GEN
Solar/Wind Harmer
0.937
3141783LANCAST
Solar/Wind Harmer
0.13
3141783LANCAST
Solar/Wind Harmer
0.087
3150411LDYSMT5
Adder
28.983
3150381LDYSMT2
Adder
27.738
972213AH1-691 GEN
Adder
4.692
972215AH1-692 GEN
Adder
4.692
3130546PLYMOUTH
Solar/Wind Harmer
0.215
315732AD1-074 GEN1
Solar/Wind Harmer
1.23
315733AD1-074 GEN2
Solar/Wind Harmer
1.23
315735AD1-075 GEN1
Solar/Wind Harmer
0.616
965291AG1-394 GEN
Solar/Wind Harmer
0.949
962981AG1-147 GEN
Solar/Wind Harmer
7.952
3146206CASHIE
Solar/Wind Harmer
0.212
970601AG2-382 GEN
Solar/Wind Harmer
7.919
3145893MURPHYS
Solar/Wind Harmer
0.572
3145893MURPHYS
Solar/Wind Harmer
0.212
970327AG2-215 GEN
Solar/Wind Harmer
6.922
3145513AHOSKIE
Solar/Wind Harmer
0.437
3145513AHOSKIE
Solar/Wind Harmer
0.209
3146043SEABORD
Solar/Wind Harmer
0.208
3145683EARLEYS
Solar/Wind Harmer
0.416
3145683EARLEYS
Solar/Wind Harmer
0.208
3145683EARLEYS
Solar/Wind Harmer
0.208
315607AA1-063A GEN
Solar/Wind Harmer
0.424
316087AB2-174 GEN
Solar/Wind Harmer
0.006
315652AC1-086 GEN
Solar/Wind Harmer
22.553
3137643SOCKMAN
Solar/Wind Harmer
0.818
3145796HORNRTN
Solar/Wind Harmer
0.646
3145796HORNRTN
Solar/Wind Harmer
0.081
3141813NORNECK
Solar/Wind Harmer
0.201
3146033SCOT NK
Solar/Wind Harmer
0.8
970831AG2-522 GEN
Solar/Wind Harmer
8.358
316005AA1-067
Solar/Wind Harmer
0.206
3145746EVERETS
Solar/Wind Harmer
0.764
3145746EVERETS
Solar/Wind Harmer
0.192
3145746EVERETS
Solar/Wind Harmer
0.192
3145746EVERETS
Solar/Wind Harmer
0.192
970181AG2-120 GEN
Solar/Wind Harmer
2.391
957861AF2-080 GEN
Solar/Wind Harmer
8.156
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
971443AH1-215 GEN
Solar/Wind Harmer
3.171
3144303KENBRDG
Solar/Wind Harmer
0.151
970683AG2-441 GEN
Solar/Wind Harmer
12.561
970681AG2-440 GEN
Solar/Wind Harmer
10.049
946301AF1-294 GEN
Solar/Wind Harmer
3.712
961791AG1-021 GEN
Solar/Wind Harmer
1.806
315657AE1-056 GEN
Solar/Wind Harmer
6.482
316420AA1-050 GEN
Solar/Wind Harmer
0.006
316319Z2-044 C
Solar/Wind Harmer
0
3145573BETHELC
Solar/Wind Harmer
0.186
3145573BETHELC
Solar/Wind Harmer
0.186
970285AG2-188 GEN
Solar/Wind Harmer
14.319
316223AC1-118
Solar/Wind Harmer
0.13
971845AH1-439 GEN
Solar/Wind Harmer
8.149
316118AC1-105 GEN
Solar/Wind Harmer
0.454
3147173SINAI
Solar/Wind Harmer
0.172
3147243WELCO
Solar/Wind Harmer
0.108
972205AH1-687 GEN
Adder
7.256
944491AF1-114 GEN
Solar/Wind Harmer
0.001
971447AH1-217 GEN
Solar/Wind Harmer
4.692
970865AG2-541 GEN
Solar/Wind Harmer
5.299
3147346CASHSCORNER
Solar/Wind Harmer
0.35
972193AH1-681 GEN
Adder
3.331
316123AC1-075 GEN
Solar/Wind Harmer
0.191
970165AG2-112 GEN
Solar/Wind Harmer
1.134
970163AG2-111 GEN
Solar/Wind Harmer
1.081
270494AE1-108_GEN
Solar/Wind Harmer
1.679
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316411AF1-147_GEN1
Solar/Wind Helper
0.804
316415AF1-147_GEN2
Solar/Wind Helper
0.804
3138216PACIFIC
Solar/Wind Helper
0.039
3152251N ANNA1
50/50
19.719
970119AG2-088 GEN
50/50
34.806
3150851SPRUNCC
50/50
1.197
3143096IRON208
50/50
1.062
3152331SURRY 2
50/50
9.829
3150771HOPHCF1
50/50
0.962
316045AC1-158 PL2
Solar/Wind Harmer
9.665
3147666LOUISA
Solar/Wind Harmer
1.067
3143226MDLTHAN
Solar/Wind Harmer
0.261
316192AB2-158 GEN
Solar/Wind Harmer
1.475
3143526WINTERP
Solar/Wind Harmer
1.319
940641AE2-051 GEN
Solar/Wind Harmer
19.587
939411AE1-173 GEN
Solar/Wind Harmer
103.486
3142543TWELFTH
Solar/Wind Harmer
0.023
316294AC1-161 GEN
Solar/Wind Harmer
4.14
315671AE2-027_GEN
Solar/Wind Harmer
15.248
970129AG2-093 GEN
Solar/Wind Harmer
6.738
316458AB2-190 GEN2
Solar/Wind Harmer
1.271
944591AF1-124 GEN
Solar/Wind Harmer
53.482
971069AG2-661 GEN
Solar/Wind Harmer
4.206
944631AF1-128 GEN
Adder
112.66
316375AC2-012 GEN
Solar/Wind Harmer
0.006
3150981CHESPKA
Adder
2.949
971647AH1-324 GEN
Solar/Wind Harmer
10.078
970659AG2-427 GEN
Solar/Wind Harmer
11.419
3145336SMITFLD
Solar/Wind Harmer
0.943
961611AG1-000B GEN
Solar/Wind Harmer
12.376
316381AD1-082 GEN
Solar/Wind Harmer
0.246
3151171GRAVELC
Adder
2.508
970661AG2-428 GEN
Solar/Wind Harmer
23.401
3142416OLDCHRC
Solar/Wind Harmer
0.61
3142416OLDCHRC
Solar/Wind Harmer
0.234
316388AE2-253 GEN
Solar/Wind Harmer
0.734
3138126ROCKLANDING
Solar/Wind Harmer
0.107
3146456SLIGO L269
Solar/Wind Harmer
0.234
316072AD1-144
Solar/Wind Harmer
0.085
316159AE1-175 C
Solar/Wind Harmer
0.201
316246AF1-032 C
Solar/Wind Harmer
0.105
971317AH1-138 GEN
Solar/Wind Harmer
1.735
316093AE2-104_GEN
Solar/Wind Harmer
3.906
3142433PROV 92
Solar/Wind Harmer
0.914
3142433PROV 92
Adder
0.445
3142433PROV 92
Adder
0.445
3146516WINFALL
Solar/Wind Harmer
0.741
3146516WINFALL
Solar/Wind Harmer
0.229
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.993
971777AH1-397 GEN
Solar/Wind Harmer
0.591
3141843SHACKLE
Adder
1.143
3141766HARMONY
Solar/Wind Harmer
0.045
3130156CHOWAN
Solar/Wind Harmer
0.223
966881AG1-559 GEN
Solar/Wind Harmer
0.257
970919AG2-571 GEN
Solar/Wind Harmer
7.85
970087AG2-069 GEN
Solar/Wind Harmer
17.59
3138133OCRAN
Solar/Wind Harmer
0.131
3145663CRESWEL
Solar/Wind Harmer
0.611
971163AH1-040 GEN
Solar/Wind Harmer
17.461
972197AH1-683 GEN
Adder
4.512
972219AH1-694 GEN
Adder
3.248
316336AC2-165 C
Solar/Wind Harmer
0.008
316023GEN1_S
Solar/Wind Harmer
0.481
3146206CASHIE
Solar/Wind Harmer
0.212
971547AH1-271 GEN
Solar/Wind Harmer
4.525
3145893MURPHYS
Solar/Wind Harmer
0.847
3145893MURPHYS
Solar/Wind Harmer
0.941
957481AF2-042 GEN
Solar/Wind Harmer
56.258
3146173TUNIS
Solar/Wind Harmer
0.21
960081AF2-299 GEN
Solar/Wind Harmer
2.005
962861AG1-135 GEN
Solar/Wind Harmer
6.67
3145683EARLEYS
Solar/Wind Harmer
0.208
315693AD1-088 GEN
Solar/Wind Harmer
9.93
3146263WOODLND
Solar/Wind Harmer
0.207
962491AG1-098 GEN
Solar/Wind Harmer
11.772
316011AB1-132 GEN
Solar/Wind Harmer
3.728
962571AG1-106 GEN
Solar/Wind Harmer
2.917
971795AH1-408 GEN
Solar/Wind Harmer
13.656
3145963POPLR C
Solar/Wind Harmer
0.204
3141726DUNNSVL
Solar/Wind Harmer
0.817
316190AA2-174 GEN
Solar/Wind Harmer
0
3145823KELFORD
Solar/Wind Harmer
0.204
3147043LAWRENC
Adder
1.836
316174AB2-169 GEN
Solar/Wind Harmer
0.005
3145783HORNRTN
Solar/Wind Harmer
0.202
3145796HORNRTN
Solar/Wind Harmer
0.666
3145796HORNRTN
Solar/Wind Harmer
0.202
3150351NORNECKC2
Adder
2.009
316212AC1-099_GEN
Solar/Wind Harmer
1.019
3146293MARTNCO
Solar/Wind Harmer
0.182
316129AC1-054 GEN
Solar/Wind Harmer
0.734
971065AG2-659 GEN
Solar/Wind Harmer
8.291
3145746EVERETS
Solar/Wind Harmer
0.192
3145746EVERETS
Solar/Wind Harmer
0.192
315722AD1-056 GEN
Solar/Wind Harmer
1.214
316337AD2-073 GEN
Solar/Wind Harmer
0.167
315687AD1-152 GEN
Solar/Wind Harmer
0.006
970937AG2-583 GEN
Solar/Wind Harmer
11.689
316494AC1-189 GEN
Solar/Wind Harmer
0.639
316237AB2-079_GEN
Solar/Wind Harmer
0.002
970685AG2-442 GEN
Solar/Wind Harmer
14.068
963171AG1-166 GEN
Solar/Wind Harmer
1.003
971563AH1-280 GEN
Solar/Wind Harmer
2.007
3144293JTRSVLE
Adder
0.599
3146233WITAKRS
Solar/Wind Harmer
0.743
3146926FARMVIL
Solar/Wind Harmer
0.112
961671AG1-007 GEN
Solar/Wind Harmer
0.029
3146083TARBORO
Solar/Wind Harmer
0.186
3145493TOT1
Solar/Wind Harmer
0.829
3145543BTLEBRO
Solar/Wind Harmer
0.183
3145543BTLEBRO
Solar/Wind Harmer
0.147
316359AB2-059 GEN
Solar/Wind Harmer
0.659
316049AB1-081 GEN
Solar/Wind Harmer
1.05
3142053HEARTS
Solar/Wind Harmer
0.323
970401AG2-262 GEN
Solar/Wind Harmer
1.053
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.072
972003AH1-546 GEN
Solar/Wind Harmer
7.289
316003AC1-222 GEN
Solar/Wind Harmer
0.004
972135AH1-637 GEN
Solar/Wind Harmer
1.408
3151751LOISA D
Adder
10.327
971377AH1-170 GEN
Solar/Wind Harmer
1.696
3147623JAMES R
Solar/Wind Harmer
0.368
972277AH1-723 GEN
Adder
86.868
316254AC1-120 GEN1
Solar/Wind Harmer
0.26
LAGNLTFEXP_LAGN->PJM
CLTF
8.056
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.878
TVALTFEXP_TVA->PJM
CLTF
4.082
CPLELTFEXP_CPLE->PJM
CLTF
11.88
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.966
NYPJM->LTFIMP_NY
CLTF
3.369
LGEELTFEXP_LGEE->PJM
CLTF
1.264
WECLTFEXP_WEC->PJM
CLTF
0.603
CBM West 1LTFEXP_CBM-W1->PJM
CBM
19.76
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.813
MECLTFEXP_MEC->PJM
CLTF
3.485
SIGELTFEXP_SIGE->PJM
CLTF
0.106

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T552_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T552_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:154.28 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:6078.79
MW Contribution:1.71
Bus #Bus NameTypeMW Contribution
3152261N ANNA2
50/50
19.95
3150861SPRUNCD
50/50
1.216
3143096IRON208
50/50
1.079
3143096IRON208
50/50
1.057
3150801HOPHCF4
50/50
1.421
971211AH1-065 GEN
50/50
1.714
3151161SURRY 1
50/50
9.199
316044AC1-158 PL1
Solar/Wind Harmer
6.895
316450AC1-158 RIC
Solar/Wind Harmer
1.839
3147666LOUISA
Solar/Wind Harmer
-0.07
315839AE2-212 C
Solar/Wind Harmer
0.822
315773AC2-141 GEN
Solar/Wind Harmer
11.408
965281AG1-393 GEN
Solar/Wind Harmer
3.401
970133AG2-095 GEN
Solar/Wind Harmer
3.047
315813AE1-149 C
Solar/Wind Harmer
16.929
970129AG2-093 GEN
Solar/Wind Harmer
15.225
944581AF1-123 GEN
Solar/Wind Harmer
122.873
944601AF1-125 GEN
Solar/Wind Harmer
120.955
315778AD1-151 GEN
Solar/Wind Harmer
23.395
3151101ELIZAR3
Adder
22.283
3144536CHRHLND
Solar/Wind Harmer
-0.004
3144873MCLAUGH
Solar/Wind Harmer
-0.001
970659AG2-427 GEN
Solar/Wind Harmer
2.537
961611AG1-000B GEN
Solar/Wind Harmer
5.672
3145336SMITFLD
Solar/Wind Harmer
-0.011
316083AB2-161 GEN
Solar/Wind Harmer
4.37
3151221GRAVEL6
Adder
17.41
3151171GRAVELC
Adder
3.35
970293AG2-193 GEN
Solar/Wind Harmer
3.361
3142946ENON
Solar/Wind Harmer
-0.009
970661AG2-428 GEN
Solar/Wind Harmer
5.055
3142416OLDCHRC
Solar/Wind Harmer
2.704
3144216WINCHST
Adder
0.896
3146456SLIGO L269
Solar/Wind Harmer
-0.027
971153AH1-033 GEN
Solar/Wind Harmer
3.252
3150921YORKTN3
Adder
5.966
316382AG1-145 C
Solar/Wind Harmer
0.803
316320Y1-086
Solar/Wind Harmer
1.548
316435W1029_GEN3
Solar/Wind Harmer
4.74
3142433PROV 92
Adder
0.452
3142433PROV 92
Adder
0.452
3146516WINFALL
Solar/Wind Harmer
-0.026
316473AC1-191 GEN
Solar/Wind Harmer
2.794
3146626S HERTFORD
Solar/Wind Harmer
-0.026
3145273HOLLAND
Solar/Wind Harmer
-0.019
316313AB2-026
Solar/Wind Harmer
0.692
316258AE1-075 C
Solar/Wind Harmer
0.623
316405AF2-144 C
Solar/Wind Harmer
0.658
3143336POWHATN
Solar/Wind Harmer
2.59
3141843SHACKLE
Adder
1.161
316203AE2-005 GEN
Solar/Wind Harmer
10.766
3141766HARMONY
Solar/Wind Harmer
2.27
316280AD1-041 GEN
Solar/Wind Harmer
1.918
966881AG1-559 GEN
Solar/Wind Harmer
0.765
3146376EDENTON
Solar/Wind Harmer
-0.025
316156AD2-030 GEN
Solar/Wind Harmer
0.677
3141873WAN 176
Solar/Wind Harmer
3.01
970917AG2-570 GEN
Solar/Wind Harmer
62.97
315614AA2-178 GEN
Solar/Wind Harmer
2.688
3150401LDYSMT4
Adder
29.389
3150371LDYSMT1
Adder
28.398
971531AH1-263 GEN
50/50
60.398
316303AF2-085
50/50
4.712
971285AH1-108 GEN
50/50
1.991
970603AG2-384 GEN
50/50
5.178
316164AC1-076 GEN
Solar/Wind Harmer
3.019
316233AE1-074 FULL
Solar/Wind Harmer
0.779
971281AH1-106 GEN
Solar/Wind Harmer
4.708
971283AH1-107 GEN
Solar/Wind Harmer
4.708
3143316POE
Solar/Wind Harmer
-0.107
941031AE2-094 GEN
Solar/Wind Harmer
50.888
944011AF1-069 GEN
Solar/Wind Harmer
15.945
316132AB2-190 GEN1
Solar/Wind Harmer
2.735
316369SG1_INVT
Solar/Wind Harmer
4.821
3151081ELIZAR1
Adder
22.001
3151091ELIZAR2
Adder
21.619
3152611GOSPORTB
Adder
3.055
3152621GOSPORTC
Adder
2.593
3152601GOSPORTA
Adder
2.392
971445AH1-216 GEN
Solar/Wind Harmer
16.663
972265AH1-717 GEN
Adder
18.594
3151201GRAVEL4
Adder
17.43
3151191GRAVEL3
Adder
17.21
3151211GRAVEL5
Adder
17.21
316312AB1-027
Solar/Wind Harmer
0.904
957871AF2-081 GEN
Solar/Wind Harmer
13.366
970673AG2-436 GEN
Solar/Wind Harmer
56.037
970673AG2-436 GEN
Solar/Wind Harmer
28.373
315833AF1-017_GEN
Solar/Wind Harmer
5.064
316349AD2-085 GEN
Solar/Wind Harmer
2.371
319010AE1-072 C
Solar/Wind Harmer
5.393
316311AC2-079 GEN
Solar/Wind Harmer
13.447
3146406KITTY HAWK
Solar/Wind Harmer
0.022
316305AF2-043 C
Solar/Wind Harmer
0.803
315976AC1-164 GENA
Solar/Wind Harmer
28.04
316169AC1-164_GENC
Solar/Wind Harmer
24.224
315975AC1-164 GENB
Solar/Wind Harmer
0.83
315835AF2-110_GEN
Solar/Wind Harmer
3.313
316315AB2-025 C
Solar/Wind Harmer
0.713
313526AB2-022
Solar/Wind Harmer
0.713
972189AH1-679 GEN
Adder
3.932
3146486SUNBURY
Solar/Wind Harmer
-0.026
3146486SUNBURY
Solar/Wind Harmer
-0.026
971967AH1-528 GEN
Solar/Wind Harmer
49.529
315814AE2-033 C
Solar/Wind Harmer
24.517
316321Z2-027
Solar/Wind Harmer
0.71
3146396TANGLEW
Solar/Wind Harmer
0.484
3145176PASQUOTANK
Solar/Wind Harmer
-0.016
971167AH1-042 GEN
Solar/Wind Harmer
25.215
3142433PROV 92
Adder
0.452
3142433PROV 92
Adder
0.452
957831AF2-077 GEN
Solar/Wind Harmer
0.783
3138283WHITEMARSH
Solar/Wind Harmer
0.04
3143873LANEXA
Solar/Wind Harmer
-0.015
315611Z1-036_GEN2
Solar/Wind Harmer
6.355
316314AB2-024 C
Solar/Wind Harmer
2.187
316059AD1-063 C
Solar/Wind Harmer
0.576
315662AE1-191 GEN
Solar/Wind Harmer
3.069
315666AE1-190 GEN
Solar/Wind Harmer
0.767
3130156CHOWAN
Solar/Wind Harmer
-0.025
3130156CHOWAN
Solar/Wind Harmer
-0.025
957601AF2-054 GEN
Solar/Wind Harmer
0.759
3141873WAN 176
Solar/Wind Harmer
-0.005
970085AG2-068 GEN
Solar/Wind Harmer
15.677
970581AG2-369 GEN
Solar/Wind Harmer
13.482
3141913WHIT STONE
Solar/Wind Harmer
-0.025
3138133OCRAN
Solar/Wind Harmer
-0.007
315816AE2-034 GEN
Solar/Wind Harmer
2.016
3141783LANCAST
Solar/Wind Harmer
-0.015
3141783LANCAST
Solar/Wind Harmer
-0.01
3150411LDYSMT5
Adder
29.481
3150381LDYSMT2
Adder
28.214
972213AH1-691 GEN
Adder
4.773
972215AH1-692 GEN
Adder
4.773
3130546PLYMOUTH
Solar/Wind Harmer
-0.024
315732AD1-074 GEN1
Solar/Wind Harmer
4.942
315733AD1-074 GEN2
Solar/Wind Harmer
4.942
315735AD1-075 GEN1
Solar/Wind Harmer
2.472
971157AH1-035 GEN
Solar/Wind Harmer
3.064
3156081AA2-088 GEN
Solar/Wind Harmer
7.946
316365GEN2_N
Solar/Wind Harmer
1.648
315737AD1-076 GEN
Solar/Wind Harmer
4.644
962971AG1-146 GEN
Solar/Wind Harmer
4.559
3146206CASHIE
Solar/Wind Harmer
-0.024
3145893MURPHYS
Solar/Wind Harmer
0.169
3145893MURPHYS
Solar/Wind Harmer
-0.024
957521AF2-046 GEN
Solar/Wind Harmer
18.984
961681AG1-008 GEN
Solar/Wind Harmer
18.984
316484AD2-074 GEN
Solar/Wind Harmer
6.061
970009AG2-005 GEN
Solar/Wind Harmer
3.009
3146173TUNIS
Solar/Wind Harmer
-0.024
3156021HOLLOMANSOL
Solar/Wind Harmer
3.218
966621AG1-532 GEN
Solar/Wind Harmer
0.484
316463AE2-346 GEN
Solar/Wind Harmer
0.386
316140AB2-099
Solar/Wind Harmer
0.161
962331AG1-082 GEN
Solar/Wind Harmer
2.979
316404AE1-155 C
Solar/Wind Harmer
4.57
3146263WOODLND
Solar/Wind Harmer
-0.024
313506AB2-031 GEN
Solar/Wind Harmer
1.893
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3145963POPLR C
Solar/Wind Harmer
-0.023
316317KELFORD C
Solar/Wind Harmer
1.098
3145823KELFORD
Solar/Wind Harmer
-0.023
316478AD1-087 GEN
Solar/Wind Harmer
2.006
316486AD2-202 GEN
Solar/Wind Harmer
0.588
3147043LAWRENC
Solar/Wind Harmer
-0.014
3145796HORNRTN
Solar/Wind Harmer
-0.092
3145796HORNRTN
Solar/Wind Harmer
-0.023
3150351NORNECKC2
Adder
2.075
3144293JTRSVLE
Adder
0.609
3151761LOISA E
Adder
22.218
972183AH1-676 GEN
Adder
173.787
972255AH1-712 GEN
Adder
76.037
3141316ARNOLDS
Adder
0.289
3141196NOKESVL
Solar/Wind Helper
1.164
3152251N ANNA1
50/50
19.951
971507AH1-251 GEN
50/50
16.627
970119AG2-088 GEN
50/50
35.342
3150851SPRUNCC
50/50
1.216
3143096IRON208
50/50
1.079
3152331SURRY 2
50/50
9.986
3150771HOPHCF1
50/50
0.977
316045AC1-158 PL2
Solar/Wind Harmer
22.057
3147666LOUISA
Solar/Wind Harmer
-0.123
316192AB2-158 GEN
Solar/Wind Harmer
3.585
3143226MDLTHAN
Solar/Wind Harmer
-0.03
3143526WINTERP
Solar/Wind Harmer
-0.15
940641AE2-051 GEN
Solar/Wind Harmer
26.182
939411AE1-173 GEN
Solar/Wind Harmer
138.344
3142543TWELFTH
Solar/Wind Harmer
-0.003
316294AC1-161 GEN
Solar/Wind Harmer
8.821
315671AE2-027_GEN
Solar/Wind Harmer
20.395
970129AG2-093 GEN
Solar/Wind Harmer
6.167
316458AB2-190 GEN2
Solar/Wind Harmer
2.735
944591AF1-124 GEN
Solar/Wind Harmer
123.316
971069AG2-661 GEN
Solar/Wind Harmer
4.273
944631AF1-128 GEN
Adder
114.478
316375AC2-012 GEN
Solar/Wind Harmer
9.327
3150981CHESPKA
Adder
2.995
971647AH1-324 GEN
Solar/Wind Harmer
13.48
970659AG2-427 GEN
Solar/Wind Harmer
14.317
961611AG1-000B GEN
Solar/Wind Harmer
13.293
3145336SMITFLD
Solar/Wind Harmer
-0.107
316381AD1-082 GEN
Solar/Wind Harmer
2.469
3151171GRAVELC
Adder
2.547
970661AG2-428 GEN
Solar/Wind Harmer
28.527
3142416OLDCHRC
Solar/Wind Harmer
-0.069
3142416OLDCHRC
Solar/Wind Harmer
-0.027
316388AE2-253 GEN
Solar/Wind Harmer
1.804
3138126ROCKLANDING
Solar/Wind Harmer
0.082
3146456SLIGO L269
Solar/Wind Harmer
-0.027
316072AD1-144
Solar/Wind Harmer
0.54
316159AE1-175 C
Solar/Wind Harmer
0.715
316246AF1-032 C
Solar/Wind Harmer
0.539
971317AH1-138 GEN
Solar/Wind Harmer
3.316
316093AE2-104_GEN
Solar/Wind Harmer
7.706
3142433PROV 92
Solar/Wind Harmer
-0.104
3142433PROV 92
Adder
0.452
3142433PROV 92
Adder
0.452
3146516WINFALL
Solar/Wind Harmer
-0.084
3146516WINFALL
Solar/Wind Harmer
-0.026
315800Z1-036_GEN1
Solar/Wind Harmer
6.355
3143336POWHATN
Solar/Wind Harmer
3.047
971777AH1-397 GEN
Solar/Wind Harmer
3.003
3141843SHACKLE
Adder
1.161
3141766HARMONY
Solar/Wind Harmer
-0.005
3130156CHOWAN
Solar/Wind Harmer
-0.025
966881AG1-559 GEN
Solar/Wind Harmer
0.262
970919AG2-571 GEN
Solar/Wind Harmer
7.971
970087AG2-069 GEN
Solar/Wind Harmer
23.516
3138133OCRAN
Solar/Wind Harmer
-0.015
3145663CRESWEL
Solar/Wind Harmer
-0.069
971163AH1-040 GEN
Solar/Wind Harmer
23.353
972197AH1-683 GEN
Adder
4.589
972219AH1-694 GEN
Adder
3.304
316336AC2-165 C
Solar/Wind Harmer
4.275
316023GEN1_S
Solar/Wind Harmer
1.648
3146206CASHIE
Solar/Wind Harmer
-0.024
971547AH1-271 GEN
Solar/Wind Harmer
6.052
3145893MURPHYS
Solar/Wind Harmer
-0.096
3145893MURPHYS
Solar/Wind Harmer
0.717
957481AF2-042 GEN
Solar/Wind Harmer
75.252
961951AG1-038 GEN
Solar/Wind Harmer
3.171
3146173TUNIS
Solar/Wind Harmer
-0.024
960081AF2-299 GEN
Solar/Wind Harmer
2.682
962861AG1-135 GEN
Solar/Wind Harmer
8.922
3145683EARLEYS
Solar/Wind Harmer
-0.024
315693AD1-088 GEN
Solar/Wind Harmer
11.811
3146263WOODLND
Solar/Wind Harmer
-0.024
962491AG1-098 GEN
Solar/Wind Harmer
15.753
316011AB1-132 GEN
Solar/Wind Harmer
4.898
962571AG1-106 GEN
Solar/Wind Harmer
3.365
971795AH1-408 GEN
Solar/Wind Harmer
17.538
3145963POPLR C
Solar/Wind Harmer
-0.023
964211AG1-282 GEN
Solar/Wind Harmer
0.701
3141726DUNNSVL
Solar/Wind Harmer
-0.093
316190AA2-174 GEN
Solar/Wind Harmer
0.286
3145823KELFORD
Solar/Wind Harmer
-0.023
3147043LAWRENC
Adder
1.866
316174AB2-169 GEN
Solar/Wind Harmer
3.568
3145783HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.076
3145796HORNRTN
Solar/Wind Harmer
-0.023
3150351NORNECKC2
Adder
2.041
3144293JTRSVLE
Adder
0.609
3151751LOISA D
Adder
10.898
972277AH1-723 GEN
Adder
88.606
965291AG1-394 GEN
Solar/Wind Harmer
2.164
962981AG1-147 GEN
Solar/Wind Harmer
10.637
3146206CASHIE
Solar/Wind Harmer
-0.024
970601AG2-382 GEN
Solar/Wind Harmer
10.591
316318V4-068
Solar/Wind Harmer
0.602
3145893MURPHYS
Solar/Wind Harmer
-0.065
3145893MURPHYS
Solar/Wind Harmer
-0.024
946281AF1-292 GEN
Solar/Wind Harmer
0.534
3145513AHOSKIE
Solar/Wind Harmer
0.208
961941AG1-037 GEN
Solar/Wind Harmer
0.179
3145513AHOSKIE
Solar/Wind Harmer
-0.024
3146043SEABORD
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.047
3145683EARLEYS
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.024
315607AA1-063A GEN
Solar/Wind Harmer
2.392
316087AB2-174 GEN
Solar/Wind Harmer
3.373
315652AC1-086 GEN
Solar/Wind Harmer
26.336
3137643SOCKMAN
Solar/Wind Harmer
-0.093
3145796HORNRTN
Solar/Wind Harmer
-0.073
3145796HORNRTN
Solar/Wind Harmer
-0.009
3141813NORNECK
Solar/Wind Harmer
-0.023
3146033SCOT NK
Solar/Wind Harmer
-0.091
972205AH1-687 GEN
Adder
7.416
972193AH1-681 GEN
Adder
3.397
316411AF1-147_GEN1
Solar/Wind Helper
0.82
316415AF1-147_GEN2
Solar/Wind Helper
0.82
3138216PACIFIC
Solar/Wind Helper
0.04
971133AH1-012 GEN
50/50
5.665
944641AF1-129 GEN
50/50
122.768
3142366NRTHEST
50/50
0.838
970533AG2-339 GEN
50/50
21.472
970531AG2-338 GEN
50/50
8.589
3150781HOPHCF2
50/50
0.977
3150791HOPHCF3
50/50
0.977
3150761HOPPOLC
50/50
0.62
971213AH1-066 GEN
50/50
0.857
3150691DARBY 3
50/50
18.39
316447AC1-158 HLD
Solar/Wind Harmer
15.163
971223AH1-071 GEN
Solar/Wind Harmer
3.723
3143526WINTERP
Solar/Wind Harmer
-0.15
316240AF1-291 C
Solar/Wind Harmer
0.822
3150701DARBY 4
Adder
17.29
3150681DARBY 2
Adder
17.27
3150671DARBY 1
Adder
17.25
3142296MT RD221
Adder
0.765
316033AB2-134 GEN
Solar/Wind Harmer
8.703
315697AD1-025 GEN
Solar/Wind Harmer
5.458
316036AC1-147 C
Solar/Wind Harmer
0.727
3150991CHESPKB
Adder
2.513
3150991CHESPKB
Adder
2.452
316236AE1-162_GEN
Solar/Wind Harmer
0.812
3142956BIRDNECK
Solar/Wind Harmer
1.444
316316AC1-027 C
Solar/Wind Harmer
0.826
316185AD1-033 GEN
Solar/Wind Harmer
2.837
970657AG2-426 GEN
Solar/Wind Harmer
8.405
970657AG2-426 GEN
Solar/Wind Harmer
1.758
3142946ENON
Solar/Wind Harmer
-0.003
3145506HICKORY
Solar/Wind Harmer
-0.107
3145506HICKORY
Solar/Wind Harmer
-0.064
3145506HICKORY
Solar/Wind Harmer
-0.016
316339AD2-160 GEN
Solar/Wind Harmer
1.804
316018AA1-139 ULT2
Solar/Wind Harmer
2.29
316017AA1-139 ULT1
Solar/Wind Harmer
2.163
316075AC2-137 C
Solar/Wind Harmer
0.72
3137176SLIGO L2192
Solar/Wind Harmer
-0.106
3146456SLIGO L269
Solar/Wind Harmer
3.151
3130086AYDLETT
Solar/Wind Harmer
-0.106
972185AH1-677 GEN
Adder
13.205
3144356SAPONY
Solar/Wind Harmer
0.922
3146386ELIZ CT
Solar/Wind Harmer
-0.026
316431W1029_GEN1
Solar/Wind Harmer
4.74
316433W1029_GEN2
Solar/Wind Harmer
4.74
972187AH1-678 GEN
Adder
6.623
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
966871AG1-558 GEN
Solar/Wind Harmer
0.781
966871AG1-558 GEN
Solar/Wind Harmer
0.267
3146626S HERTFORD
Solar/Wind Harmer
-0.026
3146626S HERTFORD
Solar/Wind Harmer
-0.026
970933AG2-581 GEN
Solar/Wind Harmer
24.111
315742AE1-103 GEN
Solar/Wind Harmer
2.675
316441AF1-014 GEN
Solar/Wind Harmer
1.721
957411AF2-035 GEN
Solar/Wind Harmer
11.447
970317AG2-208 GEN
Solar/Wind Harmer
11.129
3146376EDENTON
Solar/Wind Harmer
0.755
3146376EDENTON
Solar/Wind Harmer
0.755
315673AE1-157 GEN
Solar/Wind Harmer
18.853
3150391LDYSMT3
Adder
29.334
972195AH1-682 GEN
Adder
3.855
316065AD1-022 GEN
Solar/Wind Harmer
12.145
3145893MURPHYS
Solar/Wind Harmer
0.674
3145893MURPHYS
Solar/Wind Harmer
-0.043
970099AG2-077 GEN
Solar/Wind Harmer
30.101
316487AF1-042 GEN
Solar/Wind Harmer
3.171
3146173TUNIS
Solar/Wind Harmer
-0.024
3146173TUNIS
Solar/Wind Harmer
-0.024
958261AF2-120 GEN
Solar/Wind Harmer
9.18
316181AB2-040 GEN
Solar/Wind Harmer
3.285
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
316426AA2-053 GEN
Solar/Wind Harmer
2.355
3145593CAROLNA
Solar/Wind Harmer
-0.023
3145593CAROLNA
Solar/Wind Harmer
-0.023
966811AG1-552 GEN
Solar/Wind Harmer
2.613
3145593CAROLNA
Solar/Wind Harmer
0.193
3145783HORNRTN
Solar/Wind Harmer
2.74
3145783HORNRTN
Solar/Wind Harmer
2.192
3145783HORNRTN
Solar/Wind Harmer
0.685
3145783HORNRTN
Solar/Wind Harmer
0.274
3145796HORNRTN
Solar/Wind Harmer
-0.069
316077AC2-138 C
Solar/Wind Harmer
0.485
3150341NORNECKC1
Adder
2.144
3150341NORNECKC1
Adder
2.127
3144293JTRSVLE
Adder
0.609
3144293JTRSVLE
Adder
0.513
3151731LOISA B
Adder
10.898
3151721LOISA A
Adder
10.842
971741AH1-377 GEN
Solar/Wind Harmer
1.355
LAGNLTFEXP_LAGN->PJM
CLTF
8.202
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.311
TVALTFEXP_TVA->PJM
CLTF
4.157
CPLELTFEXP_CPLE->PJM
CLTF
12.074
CBM West 2LTFEXP_CBM-W2->PJM
CBM
41.739
NYPJM->LTFIMP_NY
CLTF
3.433
LGEELTFEXP_LGEE->PJM
CLTF
1.291
WECLTFEXP_WEC->PJM
CLTF
0.616
CBM West 1LTFEXP_CBM-W1->PJM
CBM
20.192
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.068
MECLTFEXP_MEC->PJM
CLTF
3.555
SIGELTFEXP_SIGE->PJM
CLTF
0.108

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H3T552_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H3T552_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:154.01 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:6067.89
MW Contribution:1.71
Bus #Bus NameTypeMW Contribution
3152261N ANNA2
50/50
19.936
3150861SPRUNCD
50/50
1.216
3143096IRON208
50/50
1.078
3143096IRON208
50/50
1.057
3150801HOPHCF4
50/50
1.42
971211AH1-065 GEN
50/50
1.713
3151161SURRY 1
50/50
9.192
316044AC1-158 PL1
Solar/Wind Harmer
6.891
316450AC1-158 RIC
Solar/Wind Harmer
1.837
3147666LOUISA
Solar/Wind Harmer
-0.07
315839AE2-212 C
Solar/Wind Harmer
0.822
315773AC2-141 GEN
Solar/Wind Harmer
11.4
965281AG1-393 GEN
Solar/Wind Harmer
3.399
970133AG2-095 GEN
Solar/Wind Harmer
3.045
315813AE1-149 C
Solar/Wind Harmer
16.916
970129AG2-093 GEN
Solar/Wind Harmer
15.214
944581AF1-123 GEN
Solar/Wind Harmer
122.781
944601AF1-125 GEN
Solar/Wind Harmer
120.864
315778AD1-151 GEN
Solar/Wind Harmer
23.378
3151101ELIZAR3
Adder
22.266
3144536CHRHLND
Solar/Wind Harmer
-0.004
3144873MCLAUGH
Solar/Wind Harmer
-0.001
970659AG2-427 GEN
Solar/Wind Harmer
2.535
961611AG1-000B GEN
Solar/Wind Harmer
5.668
3145336SMITFLD
Solar/Wind Harmer
-0.011
316083AB2-161 GEN
Solar/Wind Harmer
4.366
3151221GRAVEL6
Adder
17.397
3151171GRAVELC
Adder
3.347
970293AG2-193 GEN
Solar/Wind Harmer
3.359
3142946ENON
Solar/Wind Harmer
-0.009
970661AG2-428 GEN
Solar/Wind Harmer
5.052
3142416OLDCHRC
Solar/Wind Harmer
2.702
3144216WINCHST
Adder
0.896
3146456SLIGO L269
Solar/Wind Harmer
-0.027
971153AH1-033 GEN
Solar/Wind Harmer
3.25
3150921YORKTN3
Adder
5.961
316382AG1-145 C
Solar/Wind Harmer
0.802
316320Y1-086
Solar/Wind Harmer
1.547
316435W1029_GEN3
Solar/Wind Harmer
4.736
3142433PROV 92
Adder
0.451
3142433PROV 92
Adder
0.451
3146516WINFALL
Solar/Wind Harmer
-0.026
316473AC1-191 GEN
Solar/Wind Harmer
2.792
3146626S HERTFORD
Solar/Wind Harmer
-0.026
3145273HOLLAND
Solar/Wind Harmer
-0.019
316313AB2-026
Solar/Wind Harmer
0.692
316258AE1-075 C
Solar/Wind Harmer
0.623
316405AF2-144 C
Solar/Wind Harmer
0.657
3143336POWHATN
Solar/Wind Harmer
2.588
3141843SHACKLE
Adder
1.16
316203AE2-005 GEN
Solar/Wind Harmer
10.758
3141766HARMONY
Solar/Wind Harmer
2.268
316280AD1-041 GEN
Solar/Wind Harmer
1.917
966881AG1-559 GEN
Solar/Wind Harmer
0.764
3146376EDENTON
Solar/Wind Harmer
-0.025
316156AD2-030 GEN
Solar/Wind Harmer
0.677
3141873WAN 176
Solar/Wind Harmer
3.008
970917AG2-570 GEN
Solar/Wind Harmer
62.922
315614AA2-178 GEN
Solar/Wind Harmer
2.686
3150401LDYSMT4
Adder
29.367
3150371LDYSMT1
Adder
28.377
971157AH1-035 GEN
Solar/Wind Harmer
3.061
3156081AA2-088 GEN
Solar/Wind Harmer
7.94
316365GEN2_N
Solar/Wind Harmer
1.647
315737AD1-076 GEN
Solar/Wind Harmer
4.641
962971AG1-146 GEN
Solar/Wind Harmer
4.555
3146206CASHIE
Solar/Wind Harmer
-0.024
3145893MURPHYS
Solar/Wind Harmer
0.169
3145893MURPHYS
Solar/Wind Harmer
-0.024
957521AF2-046 GEN
Solar/Wind Harmer
18.97
961681AG1-008 GEN
Solar/Wind Harmer
18.97
316484AD2-074 GEN
Solar/Wind Harmer
6.056
970009AG2-005 GEN
Solar/Wind Harmer
3.007
3146173TUNIS
Solar/Wind Harmer
-0.024
3156021HOLLOMANSOL
Solar/Wind Harmer
3.215
966621AG1-532 GEN
Solar/Wind Harmer
0.483
316463AE2-346 GEN
Solar/Wind Harmer
0.385
316140AB2-099
Solar/Wind Harmer
0.161
962331AG1-082 GEN
Solar/Wind Harmer
2.977
316404AE1-155 C
Solar/Wind Harmer
4.567
3146263WOODLND
Solar/Wind Harmer
-0.023
313506AB2-031 GEN
Solar/Wind Harmer
1.892
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3145963POPLR C
Solar/Wind Harmer
-0.023
316317KELFORD C
Solar/Wind Harmer
1.097
3145823KELFORD
Solar/Wind Harmer
-0.023
3147043LAWRENC
Solar/Wind Harmer
-0.014
316478AD1-087 GEN
Solar/Wind Harmer
2.005
316486AD2-202 GEN
Solar/Wind Harmer
0.587
3145796HORNRTN
Solar/Wind Harmer
-0.092
3145796HORNRTN
Solar/Wind Harmer
-0.023
3150351NORNECKC2
Adder
2.074
3144293JTRSVLE
Adder
0.609
3151761LOISA E
Adder
22.198
972183AH1-676 GEN
Adder
173.63
972255AH1-712 GEN
Adder
75.968
3141316ARNOLDS
Adder
0.289
3141196NOKESVL
Solar/Wind Helper
1.139
3152251N ANNA1
50/50
19.938
971507AH1-251 GEN
50/50
16.616
970119AG2-088 GEN
50/50
35.315
3150851SPRUNCC
50/50
1.216
3143096IRON208
50/50
1.078
3152331SURRY 2
50/50
9.978
3150771HOPHCF1
50/50
0.977
316045AC1-158 PL2
Solar/Wind Harmer
22.043
3147666LOUISA
Solar/Wind Harmer
-0.123
316192AB2-158 GEN
Solar/Wind Harmer
3.583
3143226MDLTHAN
Solar/Wind Harmer
-0.03
3143526WINTERP
Solar/Wind Harmer
-0.15
940641AE2-051 GEN
Solar/Wind Harmer
26.162
939411AE1-173 GEN
Solar/Wind Harmer
138.24
3142543TWELFTH
Solar/Wind Harmer
-0.003
316294AC1-161 GEN
Solar/Wind Harmer
8.814
315671AE2-027_GEN
Solar/Wind Harmer
20.38
970129AG2-093 GEN
Solar/Wind Harmer
6.163
316458AB2-190 GEN2
Solar/Wind Harmer
2.733
944591AF1-124 GEN
Solar/Wind Harmer
123.223
971069AG2-661 GEN
Solar/Wind Harmer
4.27
944631AF1-128 GEN
Adder
114.392
316375AC2-012 GEN
Solar/Wind Harmer
9.32
3150981CHESPKA
Adder
2.993
971647AH1-324 GEN
Solar/Wind Harmer
13.47
970659AG2-427 GEN
Solar/Wind Harmer
14.306
961611AG1-000B GEN
Solar/Wind Harmer
13.283
3145336SMITFLD
Solar/Wind Harmer
-0.107
316381AD1-082 GEN
Solar/Wind Harmer
2.467
3151171GRAVELC
Adder
2.545
970661AG2-428 GEN
Solar/Wind Harmer
28.505
3142416OLDCHRC
Solar/Wind Harmer
-0.069
3142416OLDCHRC
Solar/Wind Harmer
-0.026
316388AE2-253 GEN
Solar/Wind Harmer
1.803
3138126ROCKLANDING
Solar/Wind Harmer
0.082
3146456SLIGO L269
Solar/Wind Harmer
-0.027
316072AD1-144
Solar/Wind Harmer
0.539
316159AE1-175 C
Solar/Wind Harmer
0.714
316246AF1-032 C
Solar/Wind Harmer
0.538
971317AH1-138 GEN
Solar/Wind Harmer
3.313
316093AE2-104_GEN
Solar/Wind Harmer
7.7
3142433PROV 92
Solar/Wind Harmer
-0.104
3142433PROV 92
Adder
0.451
3142433PROV 92
Adder
0.451
3146516WINFALL
Solar/Wind Harmer
-0.084
3146516WINFALL
Solar/Wind Harmer
-0.026
315800Z1-036_GEN1
Solar/Wind Harmer
6.351
3143336POWHATN
Solar/Wind Harmer
3.045
971777AH1-397 GEN
Solar/Wind Harmer
3
3141843SHACKLE
Adder
1.16
3141766HARMONY
Solar/Wind Harmer
-0.005
3130156CHOWAN
Solar/Wind Harmer
-0.025
966881AG1-559 GEN
Solar/Wind Harmer
0.261
970919AG2-571 GEN
Solar/Wind Harmer
7.965
970087AG2-069 GEN
Solar/Wind Harmer
23.498
3138133OCRAN
Solar/Wind Harmer
-0.015
3145663CRESWEL
Solar/Wind Harmer
-0.069
971163AH1-040 GEN
Solar/Wind Harmer
23.335
972197AH1-683 GEN
Adder
4.586
972219AH1-694 GEN
Adder
3.302
316336AC2-165 C
Solar/Wind Harmer
4.272
316023GEN1_S
Solar/Wind Harmer
1.647
3146206CASHIE
Solar/Wind Harmer
-0.024
971547AH1-271 GEN
Solar/Wind Harmer
6.047
3145893MURPHYS
Solar/Wind Harmer
-0.096
3145893MURPHYS
Solar/Wind Harmer
0.717
957481AF2-042 GEN
Solar/Wind Harmer
75.195
961951AG1-038 GEN
Solar/Wind Harmer
3.169
3146173TUNIS
Solar/Wind Harmer
-0.024
960081AF2-299 GEN
Solar/Wind Harmer
2.68
962861AG1-135 GEN
Solar/Wind Harmer
8.916
3145683EARLEYS
Solar/Wind Harmer
-0.024
315693AD1-088 GEN
Solar/Wind Harmer
11.802
3146263WOODLND
Solar/Wind Harmer
-0.023
962491AG1-098 GEN
Solar/Wind Harmer
15.74
316011AB1-132 GEN
Solar/Wind Harmer
4.894
962571AG1-106 GEN
Solar/Wind Harmer
3.363
971795AH1-408 GEN
Solar/Wind Harmer
17.524
3145963POPLR C
Solar/Wind Harmer
-0.023
964211AG1-282 GEN
Solar/Wind Harmer
0.701
3141726DUNNSVL
Solar/Wind Harmer
-0.093
316190AA2-174 GEN
Solar/Wind Harmer
0.286
3145823KELFORD
Solar/Wind Harmer
-0.023
3147043LAWRENC
Adder
1.864
316174AB2-169 GEN
Solar/Wind Harmer
3.565
3145783HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.076
3145796HORNRTN
Solar/Wind Harmer
-0.023
3150351NORNECKC2
Adder
2.039
3144293JTRSVLE
Adder
0.609
3151751LOISA D
Adder
10.888
972277AH1-723 GEN
Adder
88.526
971531AH1-263 GEN
50/50
60.354
316303AF2-085
50/50
4.709
971285AH1-108 GEN
50/50
1.989
970603AG2-384 GEN
50/50
5.174
316164AC1-076 GEN
Solar/Wind Harmer
3.016
316233AE1-074 FULL
Solar/Wind Harmer
0.779
971281AH1-106 GEN
Solar/Wind Harmer
4.705
971283AH1-107 GEN
Solar/Wind Harmer
4.705
3143316POE
Solar/Wind Harmer
-0.107
941031AE2-094 GEN
Solar/Wind Harmer
50.85
944011AF1-069 GEN
Solar/Wind Harmer
15.933
316132AB2-190 GEN1
Solar/Wind Harmer
2.733
316369SG1_INVT
Solar/Wind Harmer
4.818
3151081ELIZAR1
Adder
21.985
3151091ELIZAR2
Adder
21.603
3152611GOSPORTB
Adder
3.052
3152621GOSPORTC
Adder
2.591
3152601GOSPORTA
Adder
2.39
971445AH1-216 GEN
Solar/Wind Harmer
16.65
972265AH1-717 GEN
Adder
18.58
3151201GRAVEL4
Adder
17.417
3151191GRAVEL3
Adder
17.197
3151211GRAVEL5
Adder
17.197
316312AB1-027
Solar/Wind Harmer
0.903
957871AF2-081 GEN
Solar/Wind Harmer
13.355
970673AG2-436 GEN
Solar/Wind Harmer
55.995
970673AG2-436 GEN
Solar/Wind Harmer
28.352
315833AF1-017_GEN
Solar/Wind Harmer
5.061
316349AD2-085 GEN
Solar/Wind Harmer
2.37
319010AE1-072 C
Solar/Wind Harmer
5.389
316311AC2-079 GEN
Solar/Wind Harmer
13.437
3146406KITTY HAWK
Solar/Wind Harmer
0.022
316305AF2-043 C
Solar/Wind Harmer
0.802
315976AC1-164 GENA
Solar/Wind Harmer
28.019
316169AC1-164_GENC
Solar/Wind Harmer
24.206
315975AC1-164 GENB
Solar/Wind Harmer
0.829
315835AF2-110_GEN
Solar/Wind Harmer
3.311
316315AB2-025 C
Solar/Wind Harmer
0.712
313526AB2-022
Solar/Wind Harmer
0.712
972189AH1-679 GEN
Adder
3.929
3146486SUNBURY
Solar/Wind Harmer
-0.026
3146486SUNBURY
Solar/Wind Harmer
-0.026
971967AH1-528 GEN
Solar/Wind Harmer
49.492
315814AE2-033 C
Solar/Wind Harmer
24.499
316321Z2-027
Solar/Wind Harmer
0.709
3146396TANGLEW
Solar/Wind Harmer
0.484
3145176PASQUOTANK
Solar/Wind Harmer
-0.016
971167AH1-042 GEN
Solar/Wind Harmer
25.196
3142433PROV 92
Adder
0.451
3142433PROV 92
Adder
0.451
957831AF2-077 GEN
Solar/Wind Harmer
0.782
3138283WHITEMARSH
Solar/Wind Harmer
0.04
3143873LANEXA
Solar/Wind Harmer
-0.015
315611Z1-036_GEN2
Solar/Wind Harmer
6.351
316314AB2-024 C
Solar/Wind Harmer
2.185
316059AD1-063 C
Solar/Wind Harmer
0.576
315662AE1-191 GEN
Solar/Wind Harmer
3.067
315666AE1-190 GEN
Solar/Wind Harmer
0.767
3130156CHOWAN
Solar/Wind Harmer
-0.025
3130156CHOWAN
Solar/Wind Harmer
-0.025
957601AF2-054 GEN
Solar/Wind Harmer
0.758
3141873WAN 176
Solar/Wind Harmer
-0.005
970085AG2-068 GEN
Solar/Wind Harmer
15.665
970581AG2-369 GEN
Solar/Wind Harmer
13.472
3141913WHIT STONE
Solar/Wind Harmer
-0.025
3138133OCRAN
Solar/Wind Harmer
-0.007
315816AE2-034 GEN
Solar/Wind Harmer
2.014
3141783LANCAST
Solar/Wind Harmer
-0.015
3141783LANCAST
Solar/Wind Harmer
-0.01
3150411LDYSMT5
Adder
29.459
3150381LDYSMT2
Adder
28.193
972213AH1-691 GEN
Adder
4.769
972215AH1-692 GEN
Adder
4.769
3130546PLYMOUTH
Solar/Wind Harmer
-0.024
315732AD1-074 GEN1
Solar/Wind Harmer
4.938
315733AD1-074 GEN2
Solar/Wind Harmer
4.938
315735AD1-075 GEN1
Solar/Wind Harmer
2.47
965291AG1-394 GEN
Solar/Wind Harmer
2.162
962981AG1-147 GEN
Solar/Wind Harmer
10.629
3146206CASHIE
Solar/Wind Harmer
-0.024
970601AG2-382 GEN
Solar/Wind Harmer
10.583
316318V4-068
Solar/Wind Harmer
0.602
3145893MURPHYS
Solar/Wind Harmer
-0.065
3145893MURPHYS
Solar/Wind Harmer
-0.024
946281AF1-292 GEN
Solar/Wind Harmer
0.534
3145513AHOSKIE
Solar/Wind Harmer
0.208
961941AG1-037 GEN
Solar/Wind Harmer
0.179
3145513AHOSKIE
Solar/Wind Harmer
-0.024
3146043SEABORD
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.047
3145683EARLEYS
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.024
315607AA1-063A GEN
Solar/Wind Harmer
2.391
316087AB2-174 GEN
Solar/Wind Harmer
3.37
315652AC1-086 GEN
Solar/Wind Harmer
26.316
3137643SOCKMAN
Solar/Wind Harmer
-0.093
3145796HORNRTN
Solar/Wind Harmer
-0.073
3145796HORNRTN
Solar/Wind Harmer
-0.009
3141813NORNECK
Solar/Wind Harmer
-0.023
3146033SCOT NK
Solar/Wind Harmer
-0.091
972205AH1-687 GEN
Adder
7.409
972193AH1-681 GEN
Adder
3.394
316411AF1-147_GEN1
Solar/Wind Helper
0.818
316415AF1-147_GEN2
Solar/Wind Helper
0.818
3138216PACIFIC
Solar/Wind Helper
0.04
971133AH1-012 GEN
50/50
5.661
944641AF1-129 GEN
50/50
122.675
3142366NRTHEST
50/50
0.837
970533AG2-339 GEN
50/50
21.455
970531AG2-338 GEN
50/50
8.582
3150781HOPHCF2
50/50
0.977
3150791HOPHCF3
50/50
0.977
3150761HOPPOLC
50/50
0.619
971213AH1-066 GEN
50/50
0.857
3150691DARBY 3
50/50
18.376
316447AC1-158 HLD
Solar/Wind Harmer
15.154
971223AH1-071 GEN
Solar/Wind Harmer
3.72
3143526WINTERP
Solar/Wind Harmer
-0.15
316240AF1-291 C
Solar/Wind Harmer
0.821
3150701DARBY 4
Adder
17.277
3150681DARBY 2
Adder
17.257
3150671DARBY 1
Adder
17.237
3142296MT RD221
Adder
0.765
316033AB2-134 GEN
Solar/Wind Harmer
8.696
315697AD1-025 GEN
Solar/Wind Harmer
5.454
316036AC1-147 C
Solar/Wind Harmer
0.727
3150991CHESPKB
Adder
2.511
3150991CHESPKB
Adder
2.451
316236AE1-162_GEN
Solar/Wind Harmer
0.811
3142956BIRDNECK
Solar/Wind Harmer
1.443
316316AC1-027 C
Solar/Wind Harmer
0.826
316185AD1-033 GEN
Solar/Wind Harmer
2.835
970657AG2-426 GEN
Solar/Wind Harmer
8.398
970657AG2-426 GEN
Solar/Wind Harmer
1.756
3142946ENON
Solar/Wind Harmer
-0.003
3145506HICKORY
Solar/Wind Harmer
-0.107
3145506HICKORY
Solar/Wind Harmer
-0.064
3145506HICKORY
Solar/Wind Harmer
-0.016
316339AD2-160 GEN
Solar/Wind Harmer
1.803
316018AA1-139 ULT2
Solar/Wind Harmer
2.288
316017AA1-139 ULT1
Solar/Wind Harmer
2.161
316075AC2-137 C
Solar/Wind Harmer
0.72
3137176SLIGO L2192
Solar/Wind Harmer
-0.105
3146456SLIGO L269
Solar/Wind Harmer
3.148
3130086AYDLETT
Solar/Wind Harmer
-0.106
972185AH1-677 GEN
Adder
13.195
3144356SAPONY
Solar/Wind Harmer
0.921
3146386ELIZ CT
Solar/Wind Harmer
-0.026
316431W1029_GEN1
Solar/Wind Harmer
4.736
316433W1029_GEN2
Solar/Wind Harmer
4.736
972187AH1-678 GEN
Adder
6.618
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
966871AG1-558 GEN
Solar/Wind Harmer
0.78
966871AG1-558 GEN
Solar/Wind Harmer
0.267
3146626S HERTFORD
Solar/Wind Harmer
-0.026
3146626S HERTFORD
Solar/Wind Harmer
-0.026
970933AG2-581 GEN
Solar/Wind Harmer
24.093
315742AE1-103 GEN
Solar/Wind Harmer
2.673
316441AF1-014 GEN
Solar/Wind Harmer
1.72
957411AF2-035 GEN
Solar/Wind Harmer
11.438
970317AG2-208 GEN
Solar/Wind Harmer
11.12
3146376EDENTON
Solar/Wind Harmer
0.754
3146376EDENTON
Solar/Wind Harmer
0.754
315673AE1-157 GEN
Solar/Wind Harmer
18.839
3150391LDYSMT3
Adder
29.312
972195AH1-682 GEN
Adder
3.852
316065AD1-022 GEN
Solar/Wind Harmer
12.136
3145893MURPHYS
Solar/Wind Harmer
0.674
3145893MURPHYS
Solar/Wind Harmer
-0.043
970099AG2-077 GEN
Solar/Wind Harmer
30.078
316487AF1-042 GEN
Solar/Wind Harmer
3.169
3146173TUNIS
Solar/Wind Harmer
-0.024
3146173TUNIS
Solar/Wind Harmer
-0.024
958261AF2-120 GEN
Solar/Wind Harmer
9.173
316181AB2-040 GEN
Solar/Wind Harmer
3.283
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
316426AA2-053 GEN
Solar/Wind Harmer
2.354
3145593CAROLNA
Solar/Wind Harmer
-0.023
3145593CAROLNA
Solar/Wind Harmer
-0.023
966811AG1-552 GEN
Solar/Wind Harmer
2.611
3145593CAROLNA
Solar/Wind Harmer
0.193
3145783HORNRTN
Solar/Wind Harmer
2.737
3145783HORNRTN
Solar/Wind Harmer
2.19
3145783HORNRTN
Solar/Wind Harmer
0.684
3145783HORNRTN
Solar/Wind Harmer
0.274
3145796HORNRTN
Solar/Wind Harmer
-0.069
316077AC2-138 C
Solar/Wind Harmer
0.485
3150341NORNECKC1
Adder
2.142
3150341NORNECKC1
Adder
2.125
3144293JTRSVLE
Adder
0.609
3144293JTRSVLE
Adder
0.513
3151731LOISA B
Adder
10.888
3151721LOISA A
Adder
10.832
971741AH1-377 GEN
Solar/Wind Harmer
1.353
LAGNLTFEXP_LAGN->PJM
CLTF
8.194
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.289
TVALTFEXP_TVA->PJM
CLTF
4.152
CPLELTFEXP_CPLE->PJM
CLTF
12.064
CBM West 2LTFEXP_CBM-W2->PJM
CBM
41.692
NYPJM->LTFIMP_NY
CLTF
3.429
LGEELTFEXP_LGEE->PJM
CLTF
1.289
WECLTFEXP_WEC->PJM
CLTF
0.615
CBM West 1LTFEXP_CBM-W1->PJM
CBM
20.16
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.053
MECLTFEXP_MEC->PJM
CLTF
3.551
SIGELTFEXP_SIGE->PJM
CLTF
0.108
CONTINGENCY 'DVP_P4-2: 56702_SRT-A'
 OPEN BRANCH FROM BUS 314903 TO BUS 314924 CKT 1   /*8CHCKAHM     500.0 - 8SURRY       500.0
END
CONTINGENCY 'DVP_P1-2: LN 567_SRT-A'
 OPEN BRANCH FROM BUS 314903 TO BUS 314924 CKT 1   /*8CHCKAHM     500.0 - 8SURRY       500.0
END
CONTINGENCY 'DVP_P4-2: G2T567_SRT-A'
 OPEN BRANCH FROM BUS 314903 TO BUS 314924 CKT 1   /*8CHCKAHM     500.0 - 8SURRY       500.0
 OPEN BRANCH FROM BUS 314924 TO BUS 315233 CKT 1   /*8SURRY       500.0 - 1SURRY 2      22.0
 OPEN BUS 315233                                   /*1SURRY 2      22.0
END
CONTINGENCY 'DVP_P1-2: LN 211_SRT-S'
 OPEN BRANCH FROM BUS 314287 TO BUS 314303 CKT 1                /*6CHESTF B    230.0 - 6HOPEWLL     230.0
 SET POSTCONTRATING 876 BRANCH FROM BUS 314269 TO BUS 314303 CKT 1 /*6PRGEORG     230.0 - 6HOPEWLL     230.0
 SET PRECONTRATING 813 BRANCH FROM BUS 314269 TO BUS 314303 CKT 1 /*6PRGEORG     230.0 - 6HOPEWLL     230.0
END
CONTINGENCY 'DVP_P1-2: LN 2049_SRT-A'
 OPEN BRANCH FROM BUS 314271 TO BUS 314281 CKT 1   /*6ALLIED      230.0 - 6BURDET      230.0
 OPEN BRANCH FROM BUS 314281 TO BUS 314294 CKT 1   /*6BURDET      230.0 - 6ENON        230.0
 OPEN BRANCH FROM BUS 314286 TO BUS 314294 CKT 1   /*6CHESTF A    230.0 - 6ENON        230.0
 OPEN BUS 314281                                   /*6BURDET      230.0
 OPEN BUS 314294                                   /*6ENON        230.0
END
CONTINGENCY 'DVP_P1-2: LN 2050_SRT-S'
 OPEN BRANCH FROM BUS 314214 TO BUS 314308 CKT 1                /*6CHCKAHM     230.0 - 6ICI         230.0
 OPEN BRANCH FROM BUS 314271 TO BUS 314272 CKT 1                /*6ALLIED      230.0 - 6ALPINE      230.0
 OPEN BRANCH FROM BUS 314272 TO BUS 314308 CKT 1                /*6ALPINE      230.0 - 6ICI         230.0
 OPEN BUS 314272                                                /*6ALPINE      230.0
 OPEN BUS 314308                                                /*6ICI         230.0
 SET POSTCONTRATING 956 BRANCH FROM BUS 314271 TO BUS 314281 CKT 1 /*6ALLIED      230.0 - 6BURDET      230.0
 SET PRECONTRATING 876 BRANCH FROM BUS 314271 TO BUS 314281 CKT 1 /*6ALLIED      230.0 - 6BURDET      230.0
END
CONTINGENCY 'DVP_P1-2: LN 557_SRT-S'
 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1                /*8CHCKAHM     500.0 - 8ELMONT      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P1-2: LN 563_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P4-2: H2T557_SRT-S'
 OPEN BRANCH FROM BUS 314218 TO BUS 314908 CKT 2                /*6ELMONT      230.0 - 8ELMONT      500.0
 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1                /*8CHCKAHM     500.0 - 8ELMONT      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 4149 BRANCH FROM BUS 314908 TO BUS 314910 CKT 1 /*8ELMONT      500.0 - 8CUNINGHAM   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 3221 BRANCH FROM BUS 314908 TO BUS 314910 CKT 1 /*8ELMONT      500.0 - 8CUNINGHAM   500.0
END
CONTINGENCY 'DVP_P4-2: 562T563_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1   /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 940640 CKT 1   /*8CARSON      500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P4-2: 56372_SRT-S'
 OPEN BRANCH FROM BUS 314282 TO BUS 314902 CKT 1                /*6CARSON      230.0 - 8CARSON      500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 217_SRT-S'
 OPEN BRANCH FROM BUS 314225 TO BUS 314227 CKT 1                /*6CHARCTY     230.0 - 6LAKESIDE    230.0
 OPEN BRANCH FROM BUS 314225 TO BUS 314260 CKT 1                /*6CHARCTY     230.0 - 6VARINA      230.0
 OPEN BRANCH FROM BUS 314260 TO BUS 314287 CKT 1                /*6VARINA      230.0 - 6CHESTF B    230.0
 OPEN BUS 314225                                                /*6CHARCTY     230.0
 OPEN BUS 314260                                                /*6VARINA      230.0
 SET POSTCONTRATING 956 BRANCH FROM BUS 314287 TO BUS 314346 CKT 1 /*6CHESTF B    230.0 - 6TYLER       230.0
 SET PRECONTRATING 876 BRANCH FROM BUS 314287 TO BUS 314346 CKT 1 /*6CHESTF B    230.0 - 6TYLER       230.0
END
CONTINGENCY 'DVP_P4-2: H6T576_SRT-A'
 OPEN BRANCH FROM BUS 314322 TO BUS 314914 CKT 1   /*6MDLTHAN     230.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1   /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1   /*8MDLTHAN     500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P4-2: H6T563_SRT-S'
 OPEN BRANCH FROM BUS 314322 TO BUS 314914 CKT 1                /*6MDLTHAN     230.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1                /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P4-2: 21712_SRT-S'
 OPEN BRANCH FROM BUS 314225 TO BUS 314227 CKT 1                /*6CHARCTY     230.0 - 6LAKESIDE    230.0
 OPEN BRANCH FROM BUS 314225 TO BUS 314260 CKT 1                /*6CHARCTY     230.0 - 6VARINA      230.0
 OPEN BRANCH FROM BUS 314260 TO BUS 314287 CKT 1                /*6VARINA      230.0 - 6CHESTF B    230.0
 OPEN BUS 314225                                                /*6CHARCTY     230.0
 OPEN BUS 314260                                                /*6VARINA      230.0
 SET POSTCONTRATING 956 BRANCH FROM BUS 314287 TO BUS 314346 CKT 1 /*6CHESTF B    230.0 - 6TYLER       230.0
 SET PRECONTRATING 876 BRANCH FROM BUS 314287 TO BUS 314346 CKT 1 /*6CHESTF B    230.0 - 6TYLER       230.0
END
CONTINGENCY 'DVP_P7-1: LN 208-259_SRT-S'
 OPEN BRANCH FROM BUS 314276 TO BUS 314287 CKT 1                /*6BASIN       230.0 - 6CHESTF B    230.0
 OPEN BRANCH FROM BUS 314286 TO BUS 314309 CKT 1                /*6CHESTF A    230.0 - 6IRON208     230.0
 OPEN BRANCH FROM BUS 314309 TO BUS 314338 CKT 1                /*6IRON208     230.0 - 6SOUWEST     230.0
 OPEN BUS 314309                                                /*6IRON208     230.0
 SET POSTCONTRATING 876 BRANCH FROM BUS 314263 TO BUS 314287 CKT 1 /*6TYLER1      230.0 - 6CHESTF B    230.0
 SET PRECONTRATING 813 BRANCH FROM BUS 314263 TO BUS 314287 CKT 1 /*6TYLER1      230.0 - 6CHESTF B    230.0
END
CONTINGENCY 'DVP_P7-1: LN 211-228_SRT-S'
 OPEN BRANCH FROM BUS 314286 TO BUS 314303 CKT 1                /*6CHESTF A    230.0 - 6HOPEWLL     230.0
 OPEN BRANCH FROM BUS 314287 TO BUS 314303 CKT 1                /*6CHESTF B    230.0 - 6HOPEWLL     230.0
 SET POSTCONTRATING 876 BRANCH FROM BUS 314269 TO BUS 314303 CKT 1 /*6PRGEORG     230.0 - 6HOPEWLL     230.0
 SET PRECONTRATING 813 BRANCH FROM BUS 314269 TO BUS 314303 CKT 1 /*6PRGEORG     230.0 - 6HOPEWLL     230.0
END
CONTINGENCY 'DVP_P1-2: LN 552_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 1                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314900 TO BUS 314905 CKT 1                /*8BRISTER     500.0 - 8CHANCE      500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'DVP_P1-2: LN 581_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 2                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314905 TO BUS 314911 CKT 1                /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2913 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: H1T581_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 2                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314196 TO BUS 314911 CKT 1                /*6LADYSMITH   230.0 - 8LADYSMITH   500.0
 OPEN BRANCH FROM BUS 314905 TO BUS 314911 CKT 1                /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2913 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P4-2: H1T552_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 1                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314900 TO BUS 314905 CKT 1                /*8BRISTER     500.0 - 8CHANCE      500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'DVP_P4-2: H3T552_SRT-S'
 OPEN BRANCH FROM BUS 314130 TO BUS 314900 CKT 2                /*6BRISTER     230.0 - 8BRISTER     500.0
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 1                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314900 TO BUS 314905 CKT 1                /*8BRISTER     500.0 - 8CHANCE      500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
314214 to 314903 ckt 1
314286 to 314284 ckt 1
314286 to 314214 ckt 1
314286 to 314309 ckt 1
314287 to 314276 ckt 1
314287 to 314260 ckt 1
314303 to 314286 ckt 1
314309 to 314338 ckt 1
314269 to 314291 ckt 1
314260 to 314225 ckt 1
314918 to 314934 ckt 1
314934 to 314916 ckt 1

Winter Peak Analysis

The New Service Request AH1-065 was evaluated as a 20.0 MW (8.0 MW Capacity) injection in the Dominion area.

AH1-065 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 20.0 MW (20.0 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

(No impacts were found for this analysis)

Light Load Analysis

The New Service Request AH1-065 was evaluated as a 20.0 MW injection and 20.0 MW withdrawal in the Dominion area.

AH1-065 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 20.0 MW (20.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P1-2: LN 534_SRT-L
SingleAC110.81 %830.96B920.760.53
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P1-2: LN 553_SRT-L
SingleAC105.8 %830.96B879.140.54
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P1-2: LN 534_SRT-L
SingleAC110.63 %830.96B919.260.53
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P1-2: LN 553_SRT-L
SingleAC105.62 %830.96B877.650.54
GD2DVP
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-L
SingleAC111.19 %722.86B803.752.49
GD2DVP
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
DVP_P1-2: LN 217_SRT-L
SingleAC104.04 %722.86B752.043.01
GD2DVP
6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer
DVP_P7-1: LN 211-228_SRT-L
TowerAC102.41 %335.6C343.696.33

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L


Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 534_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.81 %
Rating:830.96 MVA
Rating Type:B
MVA to Mitigate:920.76
MW Contribution:0.53
Bus #Bus NameTypeMW Contribution
3147043LAWRENC
50/50
0.859
3147133PAMPLIN
Solar/Wind Harmer
1.765
3147133PAMPLIN
Solar/Wind Harmer
0.562
3147133PAMPLIN
Solar/Wind Harmer
0.45
3143336POWHATN
Solar/Wind Harmer
2.592
3143336POWHATN
Solar/Wind Harmer
2.203
3146776BUCKING
Solar/Wind Harmer
3.848
3146776BUCKING
Solar/Wind Harmer
0.385
3146776BUCKING
Solar/Wind Harmer
0.346
3146776BUCKING
Solar/Wind Harmer
0.312
3146926FARMVIL
Solar/Wind Harmer
0.456
3146926FARMVIL
Solar/Wind Harmer
0.456
316303AF2-085
50/50
1.901
3144303KENBRDG
Solar/Wind Harmer
0.346
315616AA1-038_C
Solar/Wind Helper
1.61
315760AF1-028 GEN
50/50
Charging
15.637
315779AE2-040
50/50
0.908
316499AE2-029_GEN
Solar/Wind Helper
1.253
315657AE1-056 GEN
Solar/Wind Harmer
6.745
315785AD2-033 C
Solar/Wind Harmer
0
316322AB2-045
Solar/Wind Harmer
0.028
942461AE2-259 GEN
Solar/Wind Harmer
0
944641AF1-129 GEN
50/50
32.292
946301AF1-294 GEN
Solar/Wind Harmer
4.339
959311AF2-222 GEN
Solar/Wind Harmer
14.907
961791AG1-021 GEN
Solar/Wind Harmer
2.117
962491AG1-098 GEN
Solar/Wind Harmer
5.333
963041AG1-153 GEN
50/50
4.555
963171AG1-166 GEN
Solar/Wind Harmer
2.117
963181AG1-167 GEN
Solar/Wind Harmer
1.587
963191AG1-168 GEN
Solar/Wind Harmer
1.587
970117AG2-086 GEN
50/50
Charging
1.232
970119AG2-088 GEN
50/50
14.256
970257AG2-171 GEN
Solar/Wind Harmer
5.183
970285AG2-188 GEN
Solar/Wind Harmer
25.543
970301AG2-198 GEN
Solar/Wind Harmer
9.152
970323AG2-213 GEN
Solar/Wind Harmer
6.911
970413AG2-270 GEN
50/50
13.231
970531AG2-338 GEN
50/50
2.376
970533AG2-339 GEN
50/50
5.94
970535AG2-341 GEN
50/50
4.866
970603AG2-384 GEN
50/50
3.405
970681AG2-440 GEN
Solar/Wind Harmer
9.64
970683AG2-441 GEN
Solar/Wind Harmer
12.05
970685AG2-442 GEN
Solar/Wind Harmer
13.496
970909AG2-566 GEN
Solar/Wind Harmer
5.918
970937AG2-583 GEN
Solar/Wind Harmer
22.906
971193AH1-056 GEN
Solar/Wind Harmer
11.241
971211AH1-065 GEN
50/50
0.534
971563AH1-280 GEN
Solar/Wind Harmer
2.117
958211AF2-115 GEN
Solar/Wind Harmer
2.646
964241AG1-285 GEN
Solar/Wind Harmer
8.987
966001AG1-469 GEN
Solar/Wind Helper
0.283
971741AH1-377 GEN
Solar/Wind Harmer
19.11
971775AH1-396 GEN
Solar/Wind Harmer
1.037
971845AH1-439 GEN
Solar/Wind Harmer
16.063
972003AH1-546 GEN
Solar/Wind Harmer
18.559
972185AH1-677 GEN
50/50
4.042
972187AH1-678 GEN
50/50
2.065
972205AH1-687 GEN
50/50
21.244
NYPJM->LTFIMP_NY
CLTF
0.415
CPLELTFEXP_CPLE->PJM
CLTF
2.798
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.62
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.509
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.564
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.514
GibsonPJM->LTFIMP_GIBSON
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
7.706

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553_SRT-L


Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 553_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.8 %
Rating:830.96 MVA
Rating Type:B
MVA to Mitigate:879.14
MW Contribution:0.54
Bus #Bus NameTypeMW Contribution
3147043LAWRENC
50/50
0.864
3147133PAMPLIN
Solar/Wind Harmer
1.77
3147133PAMPLIN
Solar/Wind Harmer
0.564
3147133PAMPLIN
Solar/Wind Harmer
0.451
3143336POWHATN
Solar/Wind Harmer
2.598
3143336POWHATN
Solar/Wind Harmer
2.208
3146776BUCKING
Solar/Wind Harmer
3.854
3146776BUCKING
Solar/Wind Harmer
0.385
3146776BUCKING
Solar/Wind Harmer
0.347
3146776BUCKING
Solar/Wind Harmer
0.312
3146926FARMVIL
Solar/Wind Harmer
0.457
3146926FARMVIL
Solar/Wind Harmer
0.457
316303AF2-085
50/50
1.911
3144303KENBRDG
Solar/Wind Harmer
0.347
315616AA1-038_C
Solar/Wind Helper
1.6
315760AF1-028 GEN
50/50
Charging
15.534
315779AE2-040
50/50
0.916
316499AE2-029_GEN
Solar/Wind Helper
1.246
315657AE1-056 GEN
Solar/Wind Harmer
6.762
315785AD2-033 C
Solar/Wind Harmer
0
316322AB2-045
Solar/Wind Harmer
0.028
942461AE2-259 GEN
Solar/Wind Harmer
0
944641AF1-129 GEN
50/50
32.584
946301AF1-294 GEN
Solar/Wind Harmer
4.351
959311AF2-222 GEN
Solar/Wind Harmer
14.957
961791AG1-021 GEN
Solar/Wind Harmer
2.123
962491AG1-098 GEN
Solar/Wind Harmer
5.357
963041AG1-153 GEN
50/50
4.594
963171AG1-166 GEN
Solar/Wind Harmer
2.123
963181AG1-167 GEN
Solar/Wind Harmer
1.592
963191AG1-168 GEN
Solar/Wind Harmer
1.592
970117AG2-086 GEN
50/50
Charging
1.223
970119AG2-088 GEN
50/50
14.333
970257AG2-171 GEN
Solar/Wind Harmer
5.201
970285AG2-188 GEN
Solar/Wind Harmer
25.585
970301AG2-198 GEN
Solar/Wind Harmer
9.176
970323AG2-213 GEN
Solar/Wind Harmer
6.935
970413AG2-270 GEN
50/50
13.308
970531AG2-338 GEN
50/50
2.397
970533AG2-339 GEN
50/50
5.992
970535AG2-341 GEN
50/50
4.892
970603AG2-384 GEN
50/50
3.436
970681AG2-440 GEN
Solar/Wind Harmer
9.67
970683AG2-441 GEN
Solar/Wind Harmer
12.087
970685AG2-442 GEN
Solar/Wind Harmer
13.538
970909AG2-566 GEN
Solar/Wind Harmer
5.933
970937AG2-583 GEN
Solar/Wind Harmer
22.94
971193AH1-056 GEN
Solar/Wind Harmer
11.271
971211AH1-065 GEN
50/50
0.539
971563AH1-280 GEN
Solar/Wind Harmer
2.123
958211AF2-115 GEN
Solar/Wind Harmer
2.653
964241AG1-285 GEN
Solar/Wind Harmer
9.024
966001AG1-469 GEN
Solar/Wind Helper
0.281
971741AH1-377 GEN
Solar/Wind Harmer
19.165
971775AH1-396 GEN
Solar/Wind Harmer
1.04
971845AH1-439 GEN
Solar/Wind Harmer
16.088
972003AH1-546 GEN
Solar/Wind Harmer
18.583
972185AH1-677 GEN
50/50
4.077
972187AH1-678 GEN
50/50
2.083
972205AH1-687 GEN
50/50
21.27
NYPJM->LTFIMP_NY
CLTF
0.387
CPLELTFEXP_CPLE->PJM
CLTF
2.847
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.487
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.481
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.475
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.649
GibsonPJM->LTFIMP_GIBSON
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
7.706

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L


Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 534_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.63 %
Rating:830.96 MVA
Rating Type:B
MVA to Mitigate:919.26
MW Contribution:0.53
Bus #Bus NameTypeMW Contribution
3147043LAWRENC
50/50
0.859
3147133PAMPLIN
Solar/Wind Harmer
1.765
3147133PAMPLIN
Solar/Wind Harmer
0.562
3147133PAMPLIN
Solar/Wind Harmer
0.45
3143336POWHATN
Solar/Wind Harmer
2.592
3143336POWHATN
Solar/Wind Harmer
2.203
3146776BUCKING
Solar/Wind Harmer
3.848
3146776BUCKING
Solar/Wind Harmer
0.385
3146776BUCKING
Solar/Wind Harmer
0.346
3146776BUCKING
Solar/Wind Harmer
0.312
3146926FARMVIL
Solar/Wind Harmer
0.456
3146926FARMVIL
Solar/Wind Harmer
0.456
316303AF2-085
50/50
1.901
3144303KENBRDG
Solar/Wind Harmer
0.346
315616AA1-038_C
Solar/Wind Helper
1.61
315760AF1-028 GEN
50/50
Charging
15.637
315779AE2-040
50/50
0.908
316499AE2-029_GEN
Solar/Wind Helper
1.253
315657AE1-056 GEN
Solar/Wind Harmer
6.745
315785AD2-033 C
Solar/Wind Harmer
0
316322AB2-045
Solar/Wind Harmer
0.028
942461AE2-259 GEN
Solar/Wind Harmer
0
944641AF1-129 GEN
50/50
32.292
946301AF1-294 GEN
Solar/Wind Harmer
4.339
959311AF2-222 GEN
Solar/Wind Harmer
14.907
961791AG1-021 GEN
Solar/Wind Harmer
2.117
962491AG1-098 GEN
Solar/Wind Harmer
5.333
963041AG1-153 GEN
50/50
4.555
963171AG1-166 GEN
Solar/Wind Harmer
2.117
963181AG1-167 GEN
Solar/Wind Harmer
1.587
963191AG1-168 GEN
Solar/Wind Harmer
1.587
970117AG2-086 GEN
50/50
Charging
1.232
970119AG2-088 GEN
50/50
14.256
970257AG2-171 GEN
Solar/Wind Harmer
5.183
970285AG2-188 GEN
Solar/Wind Harmer
25.543
970301AG2-198 GEN
Solar/Wind Harmer
9.152
970323AG2-213 GEN
Solar/Wind Harmer
6.911
970413AG2-270 GEN
50/50
13.231
970531AG2-338 GEN
50/50
2.376
970533AG2-339 GEN
50/50
5.94
970535AG2-341 GEN
50/50
4.866
970603AG2-384 GEN
50/50
3.405
970681AG2-440 GEN
Solar/Wind Harmer
9.64
970683AG2-441 GEN
Solar/Wind Harmer
12.05
970685AG2-442 GEN
Solar/Wind Harmer
13.496
970909AG2-566 GEN
Solar/Wind Harmer
5.918
970937AG2-583 GEN
Solar/Wind Harmer
22.906
971193AH1-056 GEN
Solar/Wind Harmer
11.241
971211AH1-065 GEN
50/50
0.534
971563AH1-280 GEN
Solar/Wind Harmer
2.117
958211AF2-115 GEN
Solar/Wind Harmer
2.646
964241AG1-285 GEN
Solar/Wind Harmer
8.987
966001AG1-469 GEN
Solar/Wind Helper
0.283
971741AH1-377 GEN
Solar/Wind Harmer
19.11
971775AH1-396 GEN
Solar/Wind Harmer
1.037
971845AH1-439 GEN
Solar/Wind Harmer
16.063
972003AH1-546 GEN
Solar/Wind Harmer
18.559
972185AH1-677 GEN
50/50
4.042
972187AH1-678 GEN
50/50
2.065
972205AH1-687 GEN
50/50
21.244
NYPJM->LTFIMP_NY
CLTF
0.415
CPLELTFEXP_CPLE->PJM
CLTF
2.798
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.62
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.509
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.564
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.514
GibsonPJM->LTFIMP_GIBSON
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
7.706

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553_SRT-L


Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 553_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.62 %
Rating:830.96 MVA
Rating Type:B
MVA to Mitigate:877.65
MW Contribution:0.54
Bus #Bus NameTypeMW Contribution
3147043LAWRENC
50/50
0.864
3147133PAMPLIN
Solar/Wind Harmer
1.77
3147133PAMPLIN
Solar/Wind Harmer
0.564
3147133PAMPLIN
Solar/Wind Harmer
0.451
3143336POWHATN
Solar/Wind Harmer
2.598
3143336POWHATN
Solar/Wind Harmer
2.208
3146776BUCKING
Solar/Wind Harmer
3.854
3146776BUCKING
Solar/Wind Harmer
0.385
3146776BUCKING
Solar/Wind Harmer
0.347
3146776BUCKING
Solar/Wind Harmer
0.312
3146926FARMVIL
Solar/Wind Harmer
0.457
3146926FARMVIL
Solar/Wind Harmer
0.457
316303AF2-085
50/50
1.911
3144303KENBRDG
Solar/Wind Harmer
0.347
315616AA1-038_C
Solar/Wind Helper
1.6
315760AF1-028 GEN
50/50
Charging
15.534
315779AE2-040
50/50
0.916
316499AE2-029_GEN
Solar/Wind Helper
1.246
315657AE1-056 GEN
Solar/Wind Harmer
6.762
315785AD2-033 C
Solar/Wind Harmer
0
316322AB2-045
Solar/Wind Harmer
0.028
942461AE2-259 GEN
Solar/Wind Harmer
0
944641AF1-129 GEN
50/50
32.584
946301AF1-294 GEN
Solar/Wind Harmer
4.351
959311AF2-222 GEN
Solar/Wind Harmer
14.957
961791AG1-021 GEN
Solar/Wind Harmer
2.123
962491AG1-098 GEN
Solar/Wind Harmer
5.357
963041AG1-153 GEN
50/50
4.594
963171AG1-166 GEN
Solar/Wind Harmer
2.123
963181AG1-167 GEN
Solar/Wind Harmer
1.592
963191AG1-168 GEN
Solar/Wind Harmer
1.592
970117AG2-086 GEN
50/50
Charging
1.223
970119AG2-088 GEN
50/50
14.333
970257AG2-171 GEN
Solar/Wind Harmer
5.201
970285AG2-188 GEN
Solar/Wind Harmer
25.585
970301AG2-198 GEN
Solar/Wind Harmer
9.176
970323AG2-213 GEN
Solar/Wind Harmer
6.935
970413AG2-270 GEN
50/50
13.308
970531AG2-338 GEN
50/50
2.397
970533AG2-339 GEN
50/50
5.992
970535AG2-341 GEN
50/50
4.892
970603AG2-384 GEN
50/50
3.436
970681AG2-440 GEN
Solar/Wind Harmer
9.67
970683AG2-441 GEN
Solar/Wind Harmer
12.087
970685AG2-442 GEN
Solar/Wind Harmer
13.538
970909AG2-566 GEN
Solar/Wind Harmer
5.933
970937AG2-583 GEN
Solar/Wind Harmer
22.94
971193AH1-056 GEN
Solar/Wind Harmer
11.271
971211AH1-065 GEN
50/50
0.539
971563AH1-280 GEN
Solar/Wind Harmer
2.123
958211AF2-115 GEN
Solar/Wind Harmer
2.653
964241AG1-285 GEN
Solar/Wind Harmer
9.024
966001AG1-469 GEN
Solar/Wind Helper
0.281
971741AH1-377 GEN
Solar/Wind Harmer
19.165
971775AH1-396 GEN
Solar/Wind Harmer
1.04
971845AH1-439 GEN
Solar/Wind Harmer
16.088
972003AH1-546 GEN
Solar/Wind Harmer
18.583
972185AH1-677 GEN
50/50
4.077
972187AH1-678 GEN
50/50
2.083
972205AH1-687 GEN
50/50
21.27
NYPJM->LTFIMP_NY
CLTF
0.387
CPLELTFEXP_CPLE->PJM
CLTF
2.847
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.487
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.481
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.475
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.649
GibsonPJM->LTFIMP_GIBSON
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
7.706

Details for 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L


Base Case Flowgate

Area:DVP
Facility Description:
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.19 %
Rating:722.86 MVA
Rating Type:B
MVA to Mitigate:803.75
MW Contribution:2.49
Bus #Bus NameTypeMW Contribution
3147043LAWRENC
50/50
0.689
3143316POE
Solar/Wind Harmer
1.758
3144356SAPONY
Solar/Wind Harmer
1.204
316258AE1-075 C
Solar/Wind Helper
0.296
316303AF2-085
50/50
Charging
1.778
316336AC2-165 C
Solar/Wind Helper
1.446
316405AF2-144 C
50/50
Charging
0.67
3145336SMITFLD
Solar/Wind Harmer
0.813
3145336SMITFLD
Solar/Wind Harmer
0.081
316033AB2-134 GEN
Solar/Wind Harmer
0
315779AE2-040
50/50
1.629
315814AE2-033 C
Solar/Wind Harmer
8.863
315671AE2-027_GEN
Solar/Wind Harmer
5.491
315813AE1-149 C
Solar/Wind Harmer
7.13
315697AD1-025 GEN
Solar/Wind Harmer
0
315778AD1-151 GEN
Solar/Wind Harmer
8.057
316313AB2-026
Solar/Wind Helper
0.329
315652AC1-086 GEN
Solar/Wind Harmer
7.206
316083AB2-161 GEN
Solar/Wind Harmer
1.069
316311AC2-079 GEN
Solar/Wind Harmer
4.004
316233AE1-074 FULL
Solar/Wind Helper
0.35
944011AF1-069 GEN
Solar/Wind Harmer
2.029
944011AF1-069 GEN
Solar/Wind Harmer
2.52
944641AF1-129 GEN
50/50
137.395
960081AF2-299 GEN
Solar/Wind Harmer
0.756
963041AG1-153 GEN
50/50
4.827
970119AG2-088 GEN
50/50
Charging
13.335
970133AG2-095 GEN
Solar/Wind Harmer
1.298
970413AG2-270 GEN
50/50
7.54
970531AG2-338 GEN
50/50
2.714
970533AG2-339 GEN
50/50
6.785
970603AG2-384 GEN
50/50
14.488
970657AG2-426 GEN
Solar/Wind Harmer
3.02
970657AG2-426 GEN
Solar/Wind Harmer
2.15
970659AG2-427 GEN
Solar/Wind Harmer
5.394
970659AG2-427 GEN
Solar/Wind Harmer
3.255
970661AG2-428 GEN
Solar/Wind Harmer
9.817
970661AG2-428 GEN
Solar/Wind Harmer
5.924
971069AG2-661 GEN
Solar/Wind Harmer
5.165
971211AH1-065 GEN
50/50
2.487
971213AH1-066 GEN
50/50
1.244
971647AH1-324 GEN
Solar/Wind Harmer
4.248
941031AE2-094 GEN
Solar/Wind Harmer
6.476
941031AE2-094 GEN
Solar/Wind Harmer
7.712
941591AE2-156 GEN
50/50
5.949
965281AG1-393 GEN
Solar/Wind Harmer
1.078
972185AH1-677 GEN
50/50
4.383
972187AH1-678 GEN
50/50
2.188
972265AH1-717 GEN
50/50
7.106
NYPJM->LTFIMP_NY
CLTF
0.604
LGEELTFEXP_LGEE->PJM
CLTF
0.263
WECLTFEXP_WEC->PJM
CLTF
0.137
CPLELTFEXP_CPLE->PJM
CLTF
3.375
LAGNLTFEXP_LAGN->PJM
CLTF
2.026
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.674
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.052
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.475
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.888
TVALTFEXP_TVA->PJM
CLTF
1.04
MECLTFEXP_MEC->PJM
CLTF
0.825
SIGELTFEXP_SIGE->PJM
CLTF
0.024
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
8.583

Details for 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217_SRT-L


Base Case Flowgate

Area:DVP
Facility Description:
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 217_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.04 %
Rating:722.86 MVA
Rating Type:B
MVA to Mitigate:752.04
MW Contribution:3.01
Bus #Bus NameTypeMW Contribution
3147043LAWRENC
Solar/Wind Harmer
0.047
3147043LAWRENC
50/50
0.625
3147133PAMPLIN
Solar/Wind Harmer
0.087
3147133PAMPLIN
Solar/Wind Harmer
0.028
3147133PAMPLIN
Solar/Wind Harmer
0.022
3137176SLIGO L2192
Solar/Wind Harmer
0.262
3143316POE
Solar/Wind Harmer
0.935
3144356SAPONY
Solar/Wind Harmer
0.566
3145506HICKORY
Solar/Wind Harmer
0.261
3145506HICKORY
Solar/Wind Harmer
0.157
3145506HICKORY
Solar/Wind Harmer
0.039
3146386ELIZ CT
Solar/Wind Harmer
0.067
3146396TANGLEW
Solar/Wind Harmer
0.041
3138133OCRAN
Solar/Wind Harmer
0.003
3138133OCRAN
Solar/Wind Harmer
0.001
3141766HARMONY
Solar/Wind Harmer
0.005
3141766HARMONY
Solar/Wind Harmer
0.001
3141783LANCAST
Solar/Wind Harmer
0.002
3141783LANCAST
Solar/Wind Harmer
0.001
3141913WHIT STONE
Solar/Wind Harmer
0.005
3143226MDLTHAN
Solar/Wind Harmer
-0.096
3145273HOLLAND
Solar/Wind Harmer
0.059
3146376EDENTON
Solar/Wind Harmer
0.068
3146376EDENTON
Solar/Wind Harmer
0.068
3146376EDENTON
Solar/Wind Harmer
0.068
3146456SLIGO L269
Solar/Wind Harmer
0.262
3146456SLIGO L269
Solar/Wind Harmer
0.066
3146456SLIGO L269
Solar/Wind Harmer
0.066
3146486SUNBURY
Solar/Wind Harmer
0.068
3146486SUNBURY
Solar/Wind Harmer
0.068
3146516WINFALL
Solar/Wind Harmer
0.218
3146516WINFALL
Solar/Wind Harmer
0.067
3146516WINFALL
Solar/Wind Harmer
0.067
3146516WINFALL
Solar/Wind Harmer
0.067
3146516WINFALL
Solar/Wind Harmer
0.067
3146516WINFALL
Solar/Wind Harmer
0.067
3146626S HERTFORD
Solar/Wind Harmer
0.068
3146626S HERTFORD
Solar/Wind Harmer
0.068
3146626S HERTFORD
Solar/Wind Harmer
0.068
3146843MT LREL
Solar/Wind Harmer
0.044
3146843MT LREL
Solar/Wind Harmer
0.044
3146926FARMVIL
Solar/Wind Harmer
0.007
3146926FARMVIL
Solar/Wind Harmer
0.007
3147123OTTER R
Solar/Wind Harmer
0.01
3147312GRETNA
Solar/Wind Harmer
0.011
3147312GRETNA
Solar/Wind Harmer
0.003
3145663CRESWEL
Solar/Wind Harmer
0.191
316303AF2-085
50/50
Charging
1.424
316316AC1-027 C
Solar/Wind Harmer
0
3130156CHOWAN
Solar/Wind Harmer
0.068
3130156CHOWAN
Solar/Wind Harmer
0.068
3130156CHOWAN
Solar/Wind Harmer
0.068
3145336SMITFLD
Solar/Wind Harmer
0.369
3145336SMITFLD
Solar/Wind Harmer
0.037
3146802CHATHAM
Solar/Wind Harmer
0.011
3147243WELCO
Solar/Wind Harmer
0.026
3141873WAN 176
Solar/Wind Harmer
0.025
3141873WAN 176
Solar/Wind Harmer
0.001
3143526WINTERP
Solar/Wind Harmer
-0.395
3143526WINTERP
Solar/Wind Harmer
-0.395
316033AB2-134 GEN
Solar/Wind Harmer
0
3145176PASQUOTANK
Solar/Wind Harmer
0.041
3142543TWELFTH
Solar/Wind Harmer
-0.023
3144303KENBRDG
Solar/Wind Harmer
0.03
3147173SINAI
Solar/Wind Harmer
0.041
3156081AA2-088 GEN
Solar/Wind Harmer
0
315835AF2-110_GEN
Solar/Wind Harmer
0.69
315779AE2-040
50/50
1.657
315814AE2-033 C
Solar/Wind Harmer
8.993
315671AE2-027_GEN
Solar/Wind Harmer
6.698
315813AE1-149 C
Solar/Wind Harmer
8.113
315697AD1-025 GEN
Solar/Wind Harmer
0
316473AC1-191 GEN
Solar/Wind Helper
1.201
315778AD1-151 GEN
Solar/Wind Harmer
9.319
3145513AHOSKIE
Solar/Wind Harmer
0.073
3145513AHOSKIE
Solar/Wind Harmer
0.073
3145746EVERETS
Solar/Wind Harmer
0.253
3145746EVERETS
Solar/Wind Harmer
0.064
3145746EVERETS
Solar/Wind Harmer
0.064
3145746EVERETS
Solar/Wind Harmer
0.064
3145746EVERETS
Solar/Wind Harmer
0.064
3145746EVERETS
Solar/Wind Harmer
0.064
3145746EVERETS
Solar/Wind Harmer
0.064
3145746EVERETS
Solar/Wind Harmer
0.064
3146206CASHIE
Solar/Wind Harmer
0.07
3146206CASHIE
Solar/Wind Harmer
0.07
3146206CASHIE
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.084
3142666NORTHAMPTON
Solar/Wind Harmer
0.084
3142666NORTHAMPTON
Solar/Wind Harmer
0.084
3142666NORTHAMPTON
Solar/Wind Harmer
0.084
3142666NORTHAMPTON
Solar/Wind Harmer
0.05
315652AC1-086 GEN
Solar/Wind Harmer
6.657
316083AB2-161 GEN
Solar/Wind Harmer
1.173
316311AC2-079 GEN
Solar/Wind Harmer
4.01
316233AE1-074 FULL
Solar/Wind Helper
0.305
316093AE2-104_GEN
Solar/Wind Harmer
1.69
3130546PLYMOUTH
Solar/Wind Harmer
0.069
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.05
3145593CAROLNA
Solar/Wind Harmer
0.076
3145593CAROLNA
Solar/Wind Harmer
0.076
3145593CAROLNA
Solar/Wind Harmer
0.021
3145683EARLEYS
Solar/Wind Harmer
0.144
3145683EARLEYS
Solar/Wind Harmer
0.072
3145683EARLEYS
Solar/Wind Harmer
0.072
3145683EARLEYS
Solar/Wind Harmer
0.072
3130086AYDLETT
Solar/Wind Harmer
0.264
3137643SOCKMAN
Solar/Wind Harmer
0.319
3138543CONSLDL
Solar/Wind Harmer
0.043
3142946ENON
Solar/Wind Harmer
0.011
3142946ENON
Solar/Wind Harmer
0.003
3144536CHRHLND
Solar/Wind Harmer
0.011
3144873MCLAUGH
Solar/Wind Harmer
0.002
3145493TOT1
Solar/Wind Harmer
0.064
3145573BETHELC
Solar/Wind Harmer
0.064
3145573BETHELC
Solar/Wind Harmer
0.064
3145783HORNRTN
Solar/Wind Harmer
0.301
3145783HORNRTN
Solar/Wind Harmer
0.241
3145783HORNRTN
Solar/Wind Harmer
0.075
3145783HORNRTN
Solar/Wind Harmer
0.075
3145783HORNRTN
Solar/Wind Harmer
0.03
3145796HORNRTN
Solar/Wind Harmer
0.329
3145796HORNRTN
Solar/Wind Harmer
0.272
3145796HORNRTN
Solar/Wind Harmer
0.264
3145796HORNRTN
Solar/Wind Harmer
0.247
3145796HORNRTN
Solar/Wind Harmer
0.082
3145796HORNRTN
Solar/Wind Harmer
0.082
3145796HORNRTN
Solar/Wind Harmer
0.033
3145823KELFORD
Solar/Wind Harmer
0.071
3145823KELFORD
Solar/Wind Harmer
0.071
3145893MURPHYS
Solar/Wind Harmer
0.3
3145893MURPHYS
Solar/Wind Harmer
0.519
3145893MURPHYS
Solar/Wind Harmer
0.203
3145893MURPHYS
Solar/Wind Harmer
0.135
3145893MURPHYS
Solar/Wind Harmer
0.075
3145893MURPHYS
Solar/Wind Harmer
0.075
3145893MURPHYS
Solar/Wind Harmer
0.075
3145933PARMELE
Solar/Wind Harmer
0.129
3145933PARMELE
Solar/Wind Harmer
0.064
3145933PARMELE
Solar/Wind Harmer
0.064
3145963POPLR C
Solar/Wind Harmer
0.066
3145963POPLR C
Solar/Wind Harmer
0.066
3146033SCOT NK
Solar/Wind Harmer
0.282
3146043SEABORD
Solar/Wind Harmer
0.076
3146073TAR RVR
Solar/Wind Harmer
0.064
3146083TARBORO
Solar/Wind Harmer
0.064
3146083TARBORO
Solar/Wind Harmer
0.064
3146173TUNIS
Solar/Wind Harmer
0.074
3146173TUNIS
Solar/Wind Harmer
0.074
3146173TUNIS
Solar/Wind Harmer
0.074
3146173TUNIS
Solar/Wind Harmer
0.074
3146233WITAKRS
Solar/Wind Harmer
0.258
3146233WITAKRS
Solar/Wind Harmer
0.156
3146233WITAKRS
Solar/Wind Harmer
0.044
3146263WOODLND
Solar/Wind Harmer
0.073
3146263WOODLND
Solar/Wind Harmer
0.073
3146406KITTY HAWK
Solar/Wind Harmer
0.002
316318V4-068
Solar/Wind Harmer
0
944641AF1-129 GEN
50/50
171.597
960081AF2-299 GEN
Solar/Wind Harmer
0.709
966811AG1-552 GEN
Solar/Wind Harmer
0.594
970119AG2-088 GEN
50/50
Charging
10.679
970133AG2-095 GEN
Solar/Wind Harmer
1.573
970603AG2-384 GEN
50/50
18.095
970657AG2-426 GEN
Solar/Wind Harmer
3.291
970657AG2-426 GEN
Solar/Wind Harmer
2.343
970659AG2-427 GEN
Solar/Wind Harmer
5.961
970659AG2-427 GEN
Solar/Wind Harmer
3.597
970661AG2-428 GEN
Solar/Wind Harmer
10.558
970661AG2-428 GEN
Solar/Wind Harmer
6.371
971069AG2-661 GEN
Solar/Wind Harmer
5.974
971211AH1-065 GEN
50/50
3.014
971213AH1-066 GEN
50/50
1.507
971645AH1-323 GEN
50/50
Charging
5.587
971647AH1-324 GEN
Solar/Wind Harmer
4.736
941591AE2-156 GEN
50/50
5.075
965281AG1-393 GEN
Solar/Wind Harmer
1.3
965291AG1-394 GEN
Solar/Wind Harmer
0.47
971795AH1-408 GEN
Solar/Wind Harmer
4.25
972265AH1-717 GEN
50/50
7.415
NYPJM->LTFIMP_NY
CLTF
0.476
LGEELTFEXP_LGEE->PJM
CLTF
0.143
WECLTFEXP_WEC->PJM
CLTF
0.074
CPLELTFEXP_CPLE->PJM
CLTF
2.563
LAGNLTFEXP_LAGN->PJM
CLTF
1.388
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.403
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.596
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.347
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.094
TVALTFEXP_TVA->PJM
CLTF
0.713
MECLTFEXP_MEC->PJM
CLTF
0.494
SIGELTFEXP_SIGE->PJM
CLTF
0.014
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
6.528

Details for 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228_SRT-L


Base Case Flowgate

Area:DVP
Facility Description:
6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer
Contingency Name:
DVP_P7-1: LN 211-228_SRT-L
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:102.41 %
Rating:335.6 MVA
Rating Type:C
MVA to Mitigate:343.69
MW Contribution:6.33
Bus #Bus NameTypeMW Contribution
3145336SMITFLD
Solar/Wind Harmer
1.101
3145336SMITFLD
Solar/Wind Harmer
0.11
316033AB2-134 GEN
Solar/Wind Harmer
0
315697AD1-025 GEN
Solar/Wind Harmer
-0.001
315778AD1-151 GEN
Solar/Wind Harmer
18.202
316083AB2-161 GEN
Solar/Wind Helper
0.396
316381AD1-082 GEN
Solar/Wind Helper
2.077
3144536CHRHLND
Solar/Wind Harmer
0.025
944591AF1-124 GEN
Solar/Wind Harmer
19.909
961611AG1-000B GEN
Solar/Wind Harmer
5.847
961611AG1-000B GEN
Solar/Wind Harmer
8.495
970129AG2-093 GEN
Solar/Wind Harmer
11.258
970129AG2-093 GEN
Solar/Wind Harmer
15.529
970133AG2-095 GEN
Solar/Wind Harmer
3.302
970657AG2-426 GEN
50/50
Charging
2.167
970659AG2-427 GEN
50/50
Charging
3.588
971069AG2-661 GEN
Solar/Wind Harmer
11.668
971211AH1-065 GEN
50/50
6.325
971213AH1-066 GEN
50/50
3.163
971445AH1-216 GEN
Solar/Wind Harmer
4.079
971445AH1-216 GEN
Solar/Wind Harmer
5.626
971647AH1-324 GEN
Solar/Wind Harmer
8.685
972265AH1-717 GEN
50/50
11.913
NYPJM->LTFIMP_NY
CLTF
0.159
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.074
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.056
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.587
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.132
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.409
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.314
CONTINGENCY 'DVP_P1-2: LN 534_SRT-L'
 OPEN BRANCH FROM BUS 314907 TO BUS 314910 CKT 1                /*8DOOMS       500.0 - 8CUNINGHAM   500.0
 SET POSTCONTRATING 3326 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAEAS 500.0
 SET POSTCONTRATING 3326 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAWES 500.0
 SET POSTCONTRATING 4399 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS       500.0 - 8VALLEY      500.0
 SET PRECONTRATING 2962 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAEAS 500.0
 SET PRECONTRATING 2962 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAWES 500.0
 SET PRECONTRATING 4157 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS       500.0 - 8VALLEY      500.0
END
CONTINGENCY 'DVP_P1-2: LN 553_SRT-L'
 OPEN BRANCH FROM BUS 314908 TO BUS 314910 CKT 1                /*8ELMONT      500.0 - 8CUNINGHAM   500.0
 SET POSTCONTRATING 3326 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAEAS 500.0
 SET POSTCONTRATING 3326 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAWES 500.0
 SET PRECONTRATING 2962 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAEAS 500.0
 SET PRECONTRATING 2962 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAWES 500.0
END
CONTINGENCY 'DVP_P1-2: LN 563_SRT-L'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 3359 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 3377 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 217_SRT-L'
 OPEN BRANCH FROM BUS 314225 TO BUS 314227 CKT 1                /*6CHARCTY     230.0 - 6LAKESIDE    230.0
 OPEN BRANCH FROM BUS 314225 TO BUS 314260 CKT 1                /*6CHARCTY     230.0 - 6VARINA      230.0
 OPEN BRANCH FROM BUS 314260 TO BUS 314287 CKT 1                /*6VARINA      230.0 - 6CHESTF B    230.0
 OPEN BUS 314225                                                /*6CHARCTY     230.0
 OPEN BUS 314260                                                /*6VARINA      230.0
 SET POSTCONTRATING 1092 BRANCH FROM BUS 314287 TO BUS 314346 CKT 1 /*6CHESTF B    230.0 - 6TYLER       230.0
 SET PRECONTRATING 1036 BRANCH FROM BUS 314287 TO BUS 314346 CKT 1 /*6CHESTF B    230.0 - 6TYLER       230.0
END
CONTINGENCY 'DVP_P7-1: LN 211-228_SRT-L'
 OPEN BRANCH FROM BUS 314286 TO BUS 314303 CKT 1                /*6CHESTF A    230.0 - 6HOPEWLL     230.0
 OPEN BRANCH FROM BUS 314287 TO BUS 314303 CKT 1                /*6CHESTF B    230.0 - 6HOPEWLL     230.0
 SET POSTCONTRATING 1012 BRANCH FROM BUS 314269 TO BUS 314303 CKT 1 /*6PRGEORG     230.0 - 6HOPEWLL     230.0
 SET PRECONTRATING 956 BRANCH FROM BUS 314269 TO BUS 314303 CKT 1 /*6PRGEORG     230.0 - 6HOPEWLL     230.0
END
314747 to 313867 ckt 1
313867 to 313707 ckt 1
314287 to 314276 ckt 1
314269 to 314291 ckt 1

Short Circuit Analysis

Short Circuit analysis is not performed as part of the Phase I System Impact Study. Short Circuit analysis will commence in the Phase II System Impact Study.

Stability Analysis

Stability Analysis is Not Required.

Reactive Power Analysis

Reactive Power analysis is not performed as part of the Phase I System Impact Study. Reactive Power analysis will commence in the Phase II System Impact Study.

Steady-State Voltage Analysis

Steady State Voltage Analysis is Not Required.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-038Lexington-Low Moor 230kVUnder Construction
AA1-050Tarboro-Everetts 230kVIn Service
AA1-063ACarolina–Seaboard 115kVIn Service
AA1-067Everetts 34.5kVIn Service
AA1-139Hickory-Shawboro 230kVIn Service
AA2-053Carolina-Jackson 115kVIn Service
AA2-057Hornertown-Whitakers 115kVIn Service
AA2-174Carolina-Jackson 115kVIn Service
AA2-178Mackeys 230kVIn Service
AB1-027Old Church 34.5 KVIn Service
AB1-081Anaconda-Mayo Dunbar 115kVIn Service
AB1-132Thelma 230kVIn Service
AB2-022Elizabeth City 34.5kVIn Service
AB2-024Correctional 34.5kVIn Service
AB2-025Sapony 34.5kVIn Service
AB2-026Powhatan 34.5kVIn Service
AB2-029Remington 34.5kVIn Service
AB2-031Brink-Trego 115kVIn Service
AB2-040Brink 115kVIn Service
AB2-043Chase City 115kVIn Service
AB2-045Buckingham 34.5kVIn Service
AB2-059Benson-Dunbar 115kVIn Service
AB2-060Chase City-Lunenburg 115kVIn Service
AB2-077Buggs Island-Chase City 115kVIn Service
AB2-078Buggs Island-Chase City 115kVIn Service
AB2-079Buggs Island-Chase City 115kVIn Service
AB2-099Ahoskie 34.5kVIn Service
AB2-134Hopewell-Surry 230kVIn Service
AB2-158Louisa-South Anna 230kVIn Service
AB2-161Waverly #2 DP 115kVIn Service
AB2-169Pantago-Five Points 115kVIn Service
AB2-174Emporia-Trego 115kVIn Service
AB2-190Hopewell-Surry 230kVIn Service
AC1-027Pendleton 34.5kVIn Service
AC1-034Heartsease DP - Mayo Dunbar 115kVSuspended
AC1-036Twittys Creek 34.5kVIn Service
AC1-054Kerr Dam–Eatons Ferry 115 kVIn Service
AC1-075Perth-Hickory Grove 115kVIn Service
AC1-076Locust Grove-Paytes 115kVIn Service
AC1-086Thelma 230kVSuspended
AC1-098Dawson-South Justice 115kVPartially in Service - Under Construction
AC1-099Dawson-South Justice 115kVPartially in Service - Under Construction
AC1-105Halifax-Mt. Laurel 115kVIn Service
AC1-118Westmoreland 34.5kVIn Service
AC1-120Mitchell-Mountain Run 115kVEngineering & Procurement
AC1-121Mitchell-Mountain Run 115kVEngineering & Procurement
AC1-147Grassfield 34.5kVIn Service
AC1-158Spotsylvania 500kVIn Service
AC1-161Septa 500kVIn Service
AC1-164Chickahominy 230kVPartially in Service - Under Construction
AC1-189Chinquapin-Everetts 230kVUnder Construction
AC1-191Elmont 115kVEngineering & Procurement
AC1-208Cox-Whitakers 115kVUnder Construction
AC1-221Halifax-Person 230kVIn Service
AC1-222Crystal Hill-Halifax 115kVIn Service
AC2-012Grassfield-Great Bridge 115kVIn Service
AC2-079Ivor-Oak Ridge 115kVSuspended
AC2-100Halifax-Person 230kVIn Service
AC2-137Elko 34.5kVIn Service
AC2-138Northern Neck 34.5kVIn Service
AC2-141Septa 500kVEngineering & Procurement
AC2-165Bremo-Powhatan 230kVSuspended
AD1-022Cashie-Trowbridge 230 kVEngineering & Procurement
AD1-025Hopewell-Surry 230 kVUnder Construction
AD1-033Fentress-Landstown 230 kVIn Service
AD1-041Harmony Village-Shackleford 115 kVIn Service
AD1-056Hornertown-Hathaway 230 kVSuspended
AD1-057Hornertown-Hathaway 230 kVSuspended
AD1-063Harmony Village 34.5 kVIn Service
AD1-074Trowbridge 230 kVEngineering & Procurement
AD1-075Trowbridge 230 kVEngineering & Procurement
AD1-076Trowbridge 230 kVEngineering & Procurement
AD1-082Bakers Pond-Ivor 115kVIn Service
AD1-087Clover-Sedge Hill 230 kVIn Service
AD1-088Briery-Clover 230 kVSuspended
AD1-105Kings Dominion DP 115 kVUnder Construction
AD1-115Mountain Run-Mitchell 115 kVEngineering & Procurement
AD1-144Kings Fork 34.5 kVIn Service
AD1-151Hopewell-Surry 230 kVSuspended
AD1-152Clover-Sedge Hill 230 kVIn Service
AD2-030Wan 34.5 kVIn Service
AD2-033Chase City-Lunenburg 115 kVUnder Construction
AD2-073Sanders DP 230 kVIn Service
AD2-074Garner DP-Lancaster 115 kVEngineering & Procurement
AD2-085Myrtle-Windsor DP 115kVEngineering & Procurement
AD2-160Hickory-Moyock 230kVIn Service
AD2-202Clover-Sedge Hill 230kVIn Service
AE1-056Red House-South Creek 115 kVWithdrawn
AE1-072Shawboro-Sligo 230 kVUnder Construction
AE1-074Winterpock 34.5 kVUnder Construction
AE1-075Powhatan 34.5 kVIn Service
AE1-103Holland-Union Camp 115 kVUnder Construction
AE1-108Bremo-Scottsville 138 kVEngineering & Procurement
AE1-148Kerr Dam-Ridge Rd 115 kVActive
AE1-149Disputanta-Poe 115 kVSuspended
AE1-155Garner-Northern Neck 115 kVIn Service
AE1-157Ladysmith CT-St. Johns 230 kVSuspended
AE1-162Smithfield 34.5 kVIn Service
AE1-173Carson-Suffolk 500 kVUnder Construction
AE1-175Light Foot 34.5 kVIn Service
AE1-190Harmony Village-Shackleford 115 kVPartially in Service - Under Construction
AE1-191Harmony Village-Shackleford 115 kVPartially in Service - Under Construction
AE2-005Harmony Village-Shackleford 115 kVUnder Construction
AE2-027Harrowgate-Locks 115kVUnder Construction
AE2-029Grottoes-Merck 115kVUnder Construction
AE2-033Clubhouse-Sapony 230 kVSuspended
AE2-034Mackeys 230 kVPartially in Service - Under Construction
AE2-040Sapony 34.5 kVPartially in Service - Under Construction
AE2-041Harmony Village 230 kVEngineering & Procurement
AE2-051Carson-Septa 500 kVEngineering & Procurement
AE2-092Kidds Store-Sherwood 115 kVEngineering & Procurement
AE2-094Carson-Rogers Road 500 kVEngineering & Procurement
AE2-104Suffolk 115 kVSuspended
AE2-156Yadkin 115 kVActive
AE2-212Harrowgate 34 kVEngineering & Procurement
AE2-253Hickory-Moyock 230 kVIn Service
AE2-259Curdsville-Willis Mtn 115 kVEngineering & Procurement
AE2-291Grit DP-Perth 115 kVActive
AE2-346Ahoskie 34.5 kVIn Service
AF1-014Harmony Village-Shackleford 115 kVUnder Construction
AF1-017Myrtle-Windsor 115 kVEngineering & Procurement
AF1-018Harmony Village 230 kVEngineering & Procurement
AF1-028Endless Caverns 115 kVUnder Construction
AF1-032Suffolk 34.5 kVIn Service
AF1-042Garner DP-Lancaster 115 kVEngineering & Procurement
AF1-058Welco 34.5 kVIn Service
AF1-069Carson-Rogers Rd 500 kVEngineering & Procurement
AF1-114Oak Grove-Dahlgren 230 kVEngineering & Procurement
AF1-123Harper 230 kVActive
AF1-124Harper 230 kVActive
AF1-125Harper 230 kVActive
AF1-128Chesterfield 230 kVActive
AF1-129Chesterfield 230 kVEngineering & Procurement
AF1-147Poland Rd-Runway DP 230kVUnder Construction
AF1-291Tyler 34.5 kVEngineering & Procurement
AF1-292Fields 34.5kVEngineering & Procurement
AF1-294Jetersville-Ponton 115 kVActive
AF2-035St. Johns 115 kVActive
AF2-042Clover-Rawlings 500 kVActive
AF2-043Suffolk 34.5 kVIn Service
AF2-046Tunis-Mapleton 115 kVActive
AF2-054Wan 34.5 kVIn Service
AF2-077White Marsh 34.5 kVIn Service
AF2-080Chinquapin-Everetts 230 kVActive
AF2-081Moyock 230 kVActive
AF2-085Midlothian 34.5 kVIn Service
AF2-091Oak Grove-Dahlgren 230 kVEngineering & Procurement
AF2-110Suffolk 115 kVSuspended
AF2-115Jetersville-Ponton 115 kVActive
AF2-120Garner-Northern Neck 115 kVActive
AF2-144Powhatan 34.5 kVIn Service
AF2-222Madisonville DP-Twitty's Creek 115 kVActive
AF2-297Sedge Hill 115 kVActive
AF2-299Fields 34.5 kVActive
AG1-007Tar River 12.5 kVEngineering & Procurement
AG1-008Tunis-Mapleton 115 kVActive
AG1-021Jetersville-Ponton 115 kVActive
AG1-037Ahoskie 34.5 kVEngineering & Procurement
AG1-038Garner DP-Lancaster 115 kVEngineering & Procurement
AG1-082Ahoskie 34.5 kVActive
AG1-098Briery-Clover 230 kVActive
AG1-105Mount Laurel-Barnes Junction 115 kVActive
AG1-106Thelma 230 kVActive
AG1-135Garner-Lancaster 115 kVActive
AG1-145Lightfoot 34.5 kVIn Service
AG1-146Garner DP-Lancaster 115 kVActive
AG1-147Garner DP-Lancaster 115 kVActive
AG1-153Heritage 500 kVActive
AG1-166Lone Pine 115 kVActive
AG1-167Lone Pine 115 kVActive
AG1-168Lone Pine 115 kVActive
AG1-210Northern Neck 34.5 kVEngineering & Procurement
AG1-282Dunnsville 34.5 kVEngineering & Procurement
AG1-285Chase City-Central 115 kVActive
AG1-342Dryburg 115 kVActive
AG1-393Sapony 34.5 kVActive
AG1-394Boykins 34.5 kVActive
AG1-469Gordonsville 34.5 kVEngineering & Procurement
AG1-532Fields 34.5 kVEngineering & Procurement
AG1-536Garner-Northern Neck 115 kVActive
AG1-551Parmele 34.5 kVActive
AG1-552Carolina 34.5 kVActive
AG1-558Buckner 34.5 kVEngineering & Procurement
AG1-559Caroline Pines 22 kVEngineering & Procurement
AG2-005Garner DP-Lancaster 115 kVActive
AG2-010Peninsula-Whealton 115 kVActive
AG2-068Heritage - Wake 500 kVActive
AG2-069Heritage - Wake 500 kVActive
AG2-077Clover-Rawlings 500 kVActive
AG2-086Mt. Jackson DP-Mt. Jackson 115 kVActive
AG2-088Midlothian 230 kVActive
AG2-093Colonial Trail-Hopewell 230 kVActive
AG2-095Hopewell 34.5 kV (Circuit 313)Active
AG2-111Perth 34.5 kV Substation (Circuit 408)Active
AG2-112Perth 34.5 kV Substation (Circuit 404)Active
AG2-120Everetts 34.5 kVActive
AG2-124Shackleford-Harmony 115 kVActive
AG2-151Trices Lake - James River Tap 115 kVActive
AG2-152Banister-Bear Skin 138 kVActive
AG2-171Lunenburg-Nutbush 115 kVActive
AG2-188Farmville - Buckingham 230 kVActive
AG2-193Turner 34.5 kVActive
AG2-198Briery - Finneywood 230 kVActive
AG2-208Greenwood DP - St. Johns DP 115 kVActive
AG2-213Gary D.P Tap - Gary D.P 115 kVActive
AG2-215Garner DP-Lancaster 115 kVActive
AG2-262Dryburg 115 kVActive
AG2-270Clover 230 kVActive
AG2-338Rogers Road - Carson 500 kVActive
AG2-339Rogers Road - Carson 500 kVActive
AG2-341Ridge Road 115 kVActive
AG2-366Garner Delivery Point - Lancaster 115 kVActive
AG2-369Heritage - Wake 500 kVActive
AG2-382Cashie 230 kVActive
AG2-384Chesterfield 230 kVActive
AG2-426Wakefield - Waverly 115 kVActive
AG2-427Waverly 115 kVActive
AG2-428Wakefield 115 kVActive
AG2-436Carson - Rogers Road 500 kVActive
AG2-440Twittys Creek - Madisonville 115 kVActive
AG2-441Twittys Creek - Madisonville 115 kVActive
AG2-442Twittys Creek - Madisonville 115 kVActive
AG2-469Westmoreland – Oak Grove 230 kVActive
AG2-522Five Forks DP 115 kVActive
AG2-541Perth - Crystal Hill 115 kVActive
AG2-566Briery - Finneywood 230 kVActive
AG2-570Heritage - Wake 500 kVActive
AG2-571Heritage - Wake 500 kVActive
AG2-581Rawlings-Clover 500 kVActive
AG2-583Bremo - Cartersville 230 kVActive
AG2-646Chesterfield 230 kVActive
AG2-659Kerr Dam – Hawtree 115 kVActive
AG2-661Hopewell - Colonial Trail 230 kVActive
AH1-012Louisa - North Anna 230 kVActive
AH1-033Sligo 34.5 kVActive
AH1-035Plymouth 34.5 kVActive
AH1-040Mackeys - Creswell 115 kVActive
AH1-042Providence Forge-Turner 115kVActive
AH1-056Red House DP 115kVActive
AH1-066Hopewell 34.5kVActive
AH1-071Midlothian 34.5 kVActive
AH1-106Winterpock 34.5kVActive
AH1-107Winterpock 34.5kVActive
AH1-108Spruance NUG 230 kVActive
AH1-138Penniman 34.5 kVActive
AH1-157Penniman - Waller 230 kVActive
AH1-170Columbia DP 115kVActive
AH1-215Central VA-Twitty 115 kVActive
AH1-216Smithfield-Surry 230 kVActive
AH1-217Kidds Store - Fork Union 115 kV IIActive
AH1-241Cobbs Creek - James River Industrial 115kVActive
AH1-251Todds Tavern- Spotsylvania/Goldsdale 115kVActive
AH1-263Chancellor 115 kVActive
AH1-271Cashie 230 kVActive
AH1-280Jetersville-Ponton 115 kVActive
AH1-311Heartsease DP - Mayo Dunbar 115kVActive
AH1-323Elmont 230 kVActive
AH1-324Colonial Trail – Surry 230 kVActive
AH1-343Crystal Hill DP- Perth 115kVActive
AH1-377Clover- Farmville 230kVActive
AH1-396Gary 24.94 kVActive
AH1-397Shacklesford 34.5 kVActive
AH1-399North Doswell 12.5 kVActive
AH1-408Freeman DP – Lawrenceville 115 kVActive
AH1-439Buckingham- Farmville 230kVActive
AH1-528Rawlings - Unity 500 kVActive
AH1-546Bremo - Buckingham 230 kVActive
AH1-637Oak Grove 34.5 kVActive
AH1-676Gordonsville 230 kVActive
AH1-677Rogers Road 500 kVActive
AH1-678Heritage 500 kVActive
AH1-679Four Rivers 230 kVActive
AH1-681Cunningham 500 kVActive
AH1-682Ladysmith CT 230 kVActive
AH1-683Ladysmith CT 230 kVActive
AH1-687Bear Garden 230kVActive
AH1-691Ladysmith CT 230 kVActive
AH1-692Ladysmith CT 230 kVActive
AH1-694Ladysmith CT 230 kVActive
AH1-712Cunningham 500 kVActive
AH1-716Surry-Skiffes Creek 500kVActive
AH1-717Surry 230kVActive
AH1-723Cunningham 500 kVActive
V4-068Murphy's 34.5kVIn Service
Y1-086Morgans CornerIn Service
Z1-036WinFall-Chowan 230kVIn Service
Z2-027Pasquotank 34.5kVIn Service
Z2-044Whitakers 34.5kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with potential Affected System impacts. PJM initiates coordination with each Affected System Operator by providing a list of New Service Requests in the Cycle with potential impacts to their respective system. If the Affected System Operator indicates an Affected System Study is required, PJM will notify the Project Developer or Eligible Customer of the need for an Affected System Study. See below if any Affected System Operator requires a study for this project:

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

No cost allocated system reinforcements were identified for this project in the Phase I System Impact Study load flow analysis.

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement: n7643
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n7643 / dom-480
Title
Add a 2nd new 224 MVA 115/230 kV Transformer at Chesterfield substation between Bus A and 115 kV station.
Description
Add a 2nd new 224 MVA 115/230 kV Transformer at Chesterfield substation between Bus A and 115 kV station. Expand 230 kV station to add a new rung and two breakers for XFRM Connection. Connect 115 kV Bus 1 and Bus 2 and add two breakers.
Total Cost ($USD)
$11,000,000
Allocated Cost ($USD)
$0
Time Estimate
42 to 48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-065 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-065 could receive cost allocation. Although AH1-065 may not presently have cost responsibility for this upgrade, AH1-065 is a potential Aggregate Pool Contributor.

FacilityContingency
3CHESTFLD-6CHESTF A 115.0/230.0 kV Ckt 1 transformer(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0048
Title
Replace 2-1590 AAC line lead on Line 259 at Basin 230 kV
Description
Replace 2-1590 AAC line lead on Line 259 at Basin 230 kV
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$0
Time Estimate
12 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-065 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-065 could receive cost allocation. Although AH1-065 may not presently have cost responsibility for this upgrade, AH1-065 is a potential Aggregate Pool Contributor.

FacilityContingency
6BASIN-6CHESTF B 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9265.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9265.0 / TC1-PH2-DOM-064
Title
Replace 230 kV wave trap 259WT at Basin 230 kV (Basin - Chesterfield B).
Description
Replace 230 kV wave trap 259WT at Basin 230 kV (Basin - Chesterfield B).
Total Cost ($USD)
$396,021
Allocated Cost ($USD)
$0
Time Estimate
14 to 15 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-065 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-065 could receive cost allocation. Although AH1-065 may not presently have cost responsibility for this upgrade, AH1-065 is a potential Aggregate Pool Contributor.

FacilityContingency
6BASIN-6CHESTF B 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9266.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9266.0 / TC1-PH2-DOM-065
Title
Replace switches 25944 and 25945 at Basin 230 kV (Basin - Chesterfield B).
Description
Replace switches 25944 and 25945 at Basin 230 kV (Basin - Chesterfield B).
Total Cost ($USD)
$701,120
Allocated Cost ($USD)
$0
Time Estimate
38 to 39 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-065 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-065 could receive cost allocation. Although AH1-065 may not presently have cost responsibility for this upgrade, AH1-065 is a potential Aggregate Pool Contributor.

FacilityContingency
6BASIN-6CHESTF B 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9112.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9112.0 / TC1-PH2-DOM-063
Title
Wreck and Rebuild 12.4 miles of 230 kV line 259 with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor @ 250 degrees C and replace line lead at Chesterfield.
Description
Wreck and Rebuild 12.4 miles of 230 kV line 259 with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor @ 250 degrees C and replace line lead at Chesterfield.
Total Cost ($USD)
$87,030,447
Allocated Cost ($USD)
$0
Time Estimate
46 to 47 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-065 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-065 could receive cost allocation. Although AH1-065 may not presently have cost responsibility for this upgrade, AH1-065 is a potential Aggregate Pool Contributor.

FacilityContingency
6BASIN-6CHESTF B 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2065
Title
Replace switches 219324 and 219325 at Bremo 230 kV
Description
Replace switches 219324 and 219325 at Bremo 230 kV
Total Cost ($USD)
$800,000
Allocated Cost ($USD)
$0
Time Estimate
12 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-065 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-065 could receive cost allocation. Although AH1-065 may not presently have cost responsibility for this upgrade, AH1-065 is a potential Aggregate Pool Contributor.

FacilityContingency
6BREMODIST-6BREMO 230.0 kV Ckt 1 line(Any)

System Reinforcement: n8238
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n8238 / dom-294
Title
Wreck and rebuild 1.41 miles of 230 kV Line 217 between Charles City Road and Varina with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Description
Wreck and rebuild 1.41 miles of 230 kV Line 217 between Charles City Road and Varina with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Total Cost ($USD)
$5,358,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 42 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-065 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-065 could receive cost allocation. Although AH1-065 may not presently have cost responsibility for this upgrade, AH1-065 is a potential Aggregate Pool Contributor.

FacilityContingency
6CHARCTY-6VARINA 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0050
Title
Wreck and rebuild 13.78 miles of 230 kV Line 287 between Chesterfield and Chickahominy with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Description
Wreck and rebuild 13.78 miles of 230 kV Line 287 between Chesterfield and Chickahominy with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Total Cost ($USD)
$52,364,000
Allocated Cost ($USD)
$0
Time Estimate
42 to 48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-065 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-065 could receive cost allocation. Although AH1-065 may not presently have cost responsibility for this upgrade, AH1-065 is a potential Aggregate Pool Contributor.

FacilityContingency
6CHCKAHM-6CHESTF A 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9261.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9261.0 / TC1-PH2-DOM-060
Title
Replace Existing Chickahominy XFRM 1 with 3-480 MVA Single Phase XFRM.
Description
Replace Existing Chickahominy XFRM 1 with 3-480 MVA Single Phase XFRM.
Total Cost ($USD)
$40,000,000
Allocated Cost ($USD)
$0
Time Estimate
42 to 48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-065 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-065 could receive cost allocation. Although AH1-065 may not presently have cost responsibility for this upgrade, AH1-065 is a potential Aggregate Pool Contributor.

FacilityContingency
6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0047
Title
Wreck and rebuild 0.88 miles of 230 kV Line 228 between Chesterfield and Hopewell with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C
Description
Wreck and rebuild 0.88 miles of 230 kV Line 228 between Chesterfield and Hopewell with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Total Cost ($USD)
$3,344,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 42 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-065 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-065 could receive cost allocation. Although AH1-065 may not presently have cost responsibility for this upgrade, AH1-065 is a potential Aggregate Pool Contributor.

FacilityContingency
6CHESTF A-6HOPEWLL 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0046
Title
Wreck and rebuild 7.28 miles of 230 kV Line 228 between Chesterfield and Hopewell with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Description
Wreck and rebuild 7.28 miles of 230 kV Line 228 between Chesterfield and Hopewell with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Total Cost ($USD)
$27,664,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 42 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-065 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-065 could receive cost allocation. Although AH1-065 may not presently have cost responsibility for this upgrade, AH1-065 is a potential Aggregate Pool Contributor.

FacilityContingency
6CHESTF A-6HOPEWLL 230.0 kV Ckt 1 line(Any)

System Reinforcement: n6551
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n6551 / dom-159
Title
Wreck and rebuild 7.32 miles of 230 kV Line 208 between Chesterfield and Ironbridge with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Description
Wreck and rebuild 7.32 miles of 230 kV Line 208 between Chesterfield and Ironbridge with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Total Cost ($USD)
$27,816,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 42 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-065 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-065 could receive cost allocation. Although AH1-065 may not presently have cost responsibility for this upgrade, AH1-065 is a potential Aggregate Pool Contributor.

FacilityContingency
6CHESTF A-6IRON208 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9199.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9199.0 / TC1-PH2-DOM-004
Title
Wreck and rebuild 1.63 miles of line 2193 between Fork Union and Bremo with (2) 768.2 ACSS/TW (20/7) "MAUMEE" @ 250C and replace line lead at Bremo.
Description
Wreck and rebuild 1.63 miles of line 2193 between Fork Union and Bremo with (2) 768.2 ACSS/TW (20/7) "MAUMEE" @ 250C and replace line lead at Bremo.
Total Cost ($USD)
$7,947,612
Allocated Cost ($USD)
$0
Time Estimate
42 to 43 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-065 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-065 could receive cost allocation. Although AH1-065 may not presently have cost responsibility for this upgrade, AH1-065 is a potential Aggregate Pool Contributor.

FacilityContingency
6FORK UNION-6BREMODIST 230.0 kV Ckt 1 line(Any)
6BREMODIST-6BREMO 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9198.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9198.0 / TC1-PH2-DOM-003-TC2
Title
Replace Circuit Breaker 219322 and Circuit Breaker Lead at Bremo 230 kV (Bremo - Fork Union).
Description
Replace Circuit Breaker 219322 and Circuit Breaker Lead at Bremo 230 kV (Bremo - Fork Union).
Total Cost ($USD)
$2,113,879
Allocated Cost ($USD)
$0
Time Estimate
40 to 41 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-065 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-065 could receive cost allocation. Although AH1-065 may not presently have cost responsibility for this upgrade, AH1-065 is a potential Aggregate Pool Contributor.

FacilityContingency
6FORK UNION-6BREMODIST 230.0 kV Ckt 1 line(Any)
6BREMODIST-6BREMO 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / dom-164
Title
Wreck and rebuild 7.08 miles of 230 kV Line 208 between Ironbridge and Southwest with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Description
Wreck and rebuild 7.08 miles of 230 kV Line 208 between Ironbridge and Southwest with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Total Cost ($USD)
$26,904,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 42 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-065 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-065 could receive cost allocation. Although AH1-065 may not presently have cost responsibility for this upgrade, AH1-065 is a potential Aggregate Pool Contributor.

FacilityContingency
6IRON208-6SOUWEST 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.336
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.336
Title
Build a new 230-115kV Prince George substation along the existing 115 or 230kV corridor.
Description
Build a new 230-115kV Prince George substation along the existing 115 or 230kV corridor. The substation scope includes the installation of 230kV breakers & 1-115kV breaker along with its associated terminal equipment initially but will have provision for making it a 6-breaker ring (both 230 & 115kV) in future. The existing 230-115kV transformer at Prince George will be relocated to serve this new substation.
Cost Information
Time Estimate
Jan 10 2030

Contingent

Note: Although AH1-065 may not presently have cost responsibility for this upgrade, AH1-065 may need this upgrade in-service to be deliverable to the PJM system. If AH1-065 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer(Any)

System Reinforcement: b4000.335
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.335
Title
At Poe substation, install a new 230kV six breaker ultimate ring bus which will fit the station to current 230kV standards.
Description
At Poe substation, install a new 230kV six breaker ultimate ring bus which will fit the station to current 230kV standards. The substation scope includes the installation of 230kV breaker and half GIS bus. Work at Poe subsation is associated with line #121 reconductor.
Cost Information
Time Estimate
Jan 10 2030

Contingent

Note: Although AH1-065 may not presently have cost responsibility for this upgrade, AH1-065 may need this upgrade in-service to be deliverable to the PJM system. If AH1-065 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer(Any)

System Reinforcement: b4000.334
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.334
Title
Reconductor 115kV line #121 from Poe - Prince George. Specifically, line #121 will be reconductored and converted to 230kV from Poe substation to Prince George substation.
Description
Reconductor 115kV line #121 from Poe - Prince George. Specifically, line #121 will be reconductored and converted to 230kV from Poe substation to Prince George substation.
Cost Information
Time Estimate
Jan 10 2030

Contingent

Note: Although AH1-065 may not presently have cost responsibility for this upgrade, AH1-065 may need this upgrade in-service to be deliverable to the PJM system. If AH1-065 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer(Any)

System Reinforcement: b4000.350
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.350
Title
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Description
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AH1-065 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-065 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.355
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.355
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-065 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-065 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.327
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.327
Title
Upgrade/install equipment at Ladysmith Substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230 kV strings of breaker and a half scheme.
Description
Upgrade/install equipment at Ladysmith substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230kV strings of breaker and a half scheme.
Cost Information
Time Estimate
Feb 24 2029

Not Contingent

Note: AH1-065 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-065 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.348
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.348
Title
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.
Description
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers. A new redundant breaker ring will be added at Kraken to accommodate the new 500kV line from North Anna to Kraken.
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-065 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-065 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.341
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.341
Title
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.
Description
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV substation and extend approximately 0.2 miles of conductor to fly-over the site.
Cost Information
Time Estimate
Jul 13 2029

Not Contingent

Note: AH1-065 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-065 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.357
Title
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Description
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-065 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-065 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.349
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.349
Title
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Description
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AH1-065 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-065 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.352
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.352
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AH1-065 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-065 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.344
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.344
Title
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AH1-065 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-065 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.325
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.325
Title
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Description
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Cost Information
Time Estimate
Feb 24 2029

Not Contingent

Note: AH1-065 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-065 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.346
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.346
Title
Cut-in 500kV line from Kraken substation into Yeat substation
Description
Cut-in 500kV line from Kraken substation into Yeat substation
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-065 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-065 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.356
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.356
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-065 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-065 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.345
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.345
Title
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AH1-065 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-065 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.351
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.351
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AH1-065 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-065 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.326
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.326
Title
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Description
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Cost Information
Time Estimate
Feb 24 2029

Not Contingent

Note: AH1-065 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-065 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.342
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.342
Title
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Description
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Cost Information
Time Estimate
Jul 13 2029

Not Contingent

Note: AH1-065 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-065 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)

System Reinforcement: n8239
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n8239 / dom-300
Title
Wreck and rebuild 8.84 miles of 230 kV Line 217 between Chesterfield and Varina with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Description
Wreck and rebuild 8.84 miles of 230 kV Line 217 between Chesterfield and Varina with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Total Cost ($USD)
$33,592,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 42 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-065 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-065 could receive cost allocation. Although AH1-065 may not presently have cost responsibility for this upgrade, AH1-065 is a potential Aggregate Pool Contributor.

FacilityContingency
6VARINA-6CHESTF B 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0075
Title
Wreck and rebuild 18.75 miles of 500 kV Line 594 between Spotsylvania and Morrisville with (3) 1351.5 ACSS TW/HS285 (42/19) "MARTIN"
Description
Wreck and rebuild 18.75 miles of 500 kV Line 594 between Spotsylvania and Morrisville with (3) 1351.5 ACSS TW/HS285 (42/19) "MARTIN"
Total Cost ($USD)
$110,625,000
Allocated Cost ($USD)
$0
Time Estimate
18 to 60 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-065 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-065 could receive cost allocation. Although AH1-065 may not presently have cost responsibility for this upgrade, AH1-065 is a potential Aggregate Pool Contributor.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P2-2: MORRISVILLE B1_SRT-S
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P4-2: 545T552_SRT-S
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 552_SRT-S
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 581_SRT-S
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P4-2: H1T552_SRT-S
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P4-2: H3T552_SRT-S
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 550_SRT-A

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0076
Title
Replace Wave Trap 594WT at Morrisville 500 KV
Description
Replace Wave Trap 594WT at Morrisville 500 KV
Total Cost ($USD)
$600,000
Allocated Cost ($USD)
$0
Time Estimate
16 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-065 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-065 could receive cost allocation. Although AH1-065 may not presently have cost responsibility for this upgrade, AH1-065 is a potential Aggregate Pool Contributor.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 552_SRT-S
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 581_SRT-S

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0077
Title
Replace Wave Trap 594WT at Spotsylvania 500 KV
Description
Replace Wave Trap 594WT at Spotsylvania 500 KV
Total Cost ($USD)
$600,000
Allocated Cost ($USD)
$0
Time Estimate
16 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-065 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-065 could receive cost allocation. Although AH1-065 may not presently have cost responsibility for this upgrade, AH1-065 is a potential Aggregate Pool Contributor.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 552_SRT-S
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 581_SRT-S

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0078
Title
Replace 3-1590 AAC 61 line lead on Line 594 at Morrisville 500 kV
Description
Replace 3-1590 AAC 61 line lead on Line 594 at Morrisville 500 kV
Total Cost ($USD)
$600,000
Allocated Cost ($USD)
$0
Time Estimate
12 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-065 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-065 could receive cost allocation. Although AH1-065 may not presently have cost responsibility for this upgrade, AH1-065 is a potential Aggregate Pool Contributor.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 552_SRT-S
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 581_SRT-S

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0071
Title
Wreck and rebuild 14.02 miles of 500 kV Line 573 between Spotsylvania and North Anna with (3) 1351.5 ACSS TW/HS285 (42/19) "MARTIN".
Description
Wreck and rebuild 14.02 miles of 500 kV Line 573 between Spotsylvania and North Anna with (3) 1351.5 ACSS TW/HS285 (42/19) "MARTIN".
Total Cost ($USD)
$82,718,000
Allocated Cost ($USD)
$0
Time Estimate
18 to 48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-065 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-065 could receive cost allocation. Although AH1-065 may not presently have cost responsibility for this upgrade, AH1-065 is a potential Aggregate Pool Contributor.

FacilityContingency
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 552_SRT-S
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 581_SRT-S

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0072
Title
Replace 2-2500 ACAR 84/7 line lead on Line 573 at North Anna 500 kV
Description
Replace 2-2500 ACAR 84/7 line lead on Line 573 at North Anna 500 kV
Total Cost ($USD)
$600,000
Allocated Cost ($USD)
$0
Time Estimate
12 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-065 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-065 could receive cost allocation. Although AH1-065 may not presently have cost responsibility for this upgrade, AH1-065 is a potential Aggregate Pool Contributor.

FacilityContingency
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 581_SRT-S

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0073
Title
Replace Wave Trap 573WT at Spotsylvania 500 KV
Description
Replace Wave Trap 573WT at Spotsylvania 500 KV
Total Cost ($USD)
$600,000
Allocated Cost ($USD)
$0
Time Estimate
16 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-065 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-065 could receive cost allocation. Although AH1-065 may not presently have cost responsibility for this upgrade, AH1-065 is a potential Aggregate Pool Contributor.

FacilityContingency
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 581_SRT-S

Attachments

AH1-065 One Line Diagram

AH1-065 One Line Diagram.pdf
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.