AH1-075 Phase I Study Report

v1.00 released 2025-10-29 20:43

North Waldo - Wild Creek 138 kV

24.7 MW Capacity / 8.0 MW Energy

Introduction

This Phase I System Impact Study Report (PH1) has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, sections 307 and 308 for New Service Requests (projects) in Transition Cycle 2. The Project Developer/Eligible Customer (developer) is Chestnut Solar, LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is American Electric Power.

Preface

The Phase I System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle executive summary format and (ii) an individual project-level basis. The Phase I System Impact Study Results (for both the executive summary and individual reports) will be publicly available on PJM’s website. Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.3, PJM takes the following actions during the Phase I System Impact Study:
  1. PJM studies each New Service Request on a summer peak, winter peak and light load RTEP base case study. The case year is dependent on the new services cycle under study. PJM will identify the base case year to be used in the study of a specific cycle on its website.
  2. PJM will only perform load flow analysis during the Phase I System Impact Study.
  3. In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with Affected System impacts and provides each Affected System Operator with a list of New Service Request in the Cycle with potential impacts to their respective system.
  4. PJM will create both the short circuit and stability base cases to be used in the Phase II System Impact Study.
  5. The Phase I System Impact Study results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.
The Transmission Owner takes the following actions during the Phase I System Impact Study:
  1. Identify required Interconnection Facilities to accommodate the New Service Request.
  2. Identify required Network Upgrades to mitigate system violations from the Phase I System Impact Study.
  3. Provide planning-level preliminary estimates of Interconnection Facilities and Network Upgrades including scope, cost and elapsed time to complete the work.

Decision Point I Requirements

At the close of Phase I System Impact Study, PJM will initiate Decision Point I (DP1). During DP1, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.A.1. Additional information on these elements is available in PJM Manual 14H sections 4.4, 6, and 7.

Allowable project modifications at Decision Point I are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

General

The Project Developer has proposed an uprate to a planned/existing Solar facility located in the American Electric Power zone — Marion County, Ohio. This project is an increase to the developer’s AD1-106 project(s), which will share the same Point of Interconnection. The AH1-075 project is a 8.0 MW uprate (24.7 MW Capacity uprate) to the previous project(s). The total installed facilities will have a capability of 68.0 MW with 47.5 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AH1-075
Project Name:
North Waldo - Wild Creek 138 kV
Project Developer Name:
Chestnut Solar, LLC
State:
Ohio
County:
Marion
Transmission Owner:
American Electric Power
MFO:
68.0
MWE:
8.0
MWC:
24.7
Fuel Type:
Solar
Basecase Study Year:
2028

Physical Interconnection Facility Study

Physical Interconnection Facilities Study is not performed as part of the Phase I System Impact Study. Physical Interconnection Facilities Study will commence in the Phase II System Impact Study.

Point of Interconnection

AH1-075 will interconnect on the American Electric Power transmission system by tapping the North Waldo - Wild Creek 138 kV Line.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In the Phase I SIS, the costs shown are subject to change as a result of a facility study performed by the TO during the Phase II or Phase III System Impact Study.

Based on the Phase I SIS results, the AH1-075 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit are also shown below.

Cost Summary
DescriptionCost Allocated to AH1-075Cost Subject to Readiness*
Transmission Owner Interconnection Facilities (TOIF)$0$0
Other Scope$352,000$0
Option To Build Oversight$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$0$0
Network Upgrades$0$0
System Reliability Network Upgrades
Steady State Thermal & Voltage (SP & LL)$2,888,407$2,888,407
Transient Stability$0$0
Short Circuit$0$0
Transmission Owner Analysis
SubRegional$652,146$652,146
Distribution$0$0
Affected System Reinforcements
AFS - PJM Violatons$0$0
AFS - Non-PJM Violations$0$0
Total$3,892,553$3,540,553

* Contributes to calculation for Readiness Deposit #2 (RD2). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim deliverability study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 309 (Decision Point I) A.1.a.i and PJM Manual 14H, section 6.2, Readiness Deposit #2 (RD2) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point I (DP1), the Project Developer or Eligible Customer is required to submit Readiness Deposit #2, which is calculated as 10% of cost allocation for required Phase I Network Upgrades minus Readiness Deposit #1.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Readiness Deposit #2 Due for Project AH1-075

Readiness Deposit #2 has been calculated for the project based on the Phase I System Impact Study results and is shown in the table below. This Readiness Deposit #2 must be provided at Decision Point I through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit
Project ID10% of cost allocation for Phase I Network UpgradesReadiness Deposit #1 Received (RD1)Readiness Deposit #2 (RD2) for AH1-075 Project due at DP1
ABA - B
AH1-075$354,055$98,800$255,255

Note: Failure to provide an acceptable form of Readiness Deposit #2 by the end of Decision Point I will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Physical Interconnection
RTEP IDDescriptionTotal Cost ($USD)Allocated Cost ($USD)
(Pending)AEP will procure and install revenue submetering equipment for settlement between the generators behind the Point of Interconnection$352,000 $352,000

Based on the scope of work for the Interconnection Facilities, it is expected to take 6 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

The schedule for any required Network Impact Reinforcements will be more clearly identified in the Phase II and Phase III System Impact Studies.

Transmission Owner Analysis

Transmission Owner Identified Network Impacts

There were no network impacts to Distribution facilities identified by the Transmission Owner.

The Transmission Owner identified network impacts to Sub-Regional facilities as follows:

Transmission Owner Identified System Reinforcements on Sub-Regional Facilities
Overloaded ElementContingencyRating [MVA]Final Cycle Loading %Contribution [MW]
245715 05U SANDSK 69.0 - 247379 05NEVADA SS 69.0 CKT 1 AEP_P2-2_#5710_05WMTVER 138_1_SRT-A
CONTINGENCY 'AEP_P2-2_#5710_05WMTVER 138_1_SRT-A'  

  OPEN BRANCH FROM BUS 242950 TO BUS 243153 CKT 1                  / 242950 05ACADEM 138 243153 05WMTVER 138 1

  OPEN BRANCH FROM BUS 242963 TO BUS 243153 CKT 1                  / 242963 05HEDDSS 138 243153 05WMTVER 138 1

  OPEN BRANCH FROM BUS 243098 TO BUS 243153 CKT 1                  / 243098 05SHARPR 138 243153 05WMTVER 138 1

  OPEN BRANCH FROM BUS 243153 TO BUS 245562 CKT 1                  / 243153 05WMTVER 138 245562 05W MT VER 69.0 1

  REMOVE SWSHUNT FROM BUS 243153                                   / 243153 05WMTVER 138

END
31.0128.31 %0.65
245715 05U SANDSK 69.0 - 247379 05NEVADA SS 69.0 CKT 1 AEP_P4_#5710_05WMTVER 138_B_SRT-A
CONTINGENCY 'AEP_P4_#5710_05WMTVER 138_B_SRT-A'  

  OPEN BRANCH FROM BUS 242950 TO BUS 243153 CKT 1                  / 242950 05ACADEM 138 243153 05WMTVER 138 1

  OPEN BRANCH FROM BUS 242963 TO BUS 243153 CKT 1                  / 242963 05HEDDSS 138 243153 05WMTVER 138 1

  OPEN BRANCH FROM BUS 243098 TO BUS 243153 CKT 1                  / 243098 05SHARPR 138 243153 05WMTVER 138 1

  OPEN BRANCH FROM BUS 243153 TO BUS 245562 CKT 1                  / 243153 05WMTVER 138 245562 05W MT VER 69.0 1

  REMOVE SWSHUNT FROM BUS 243153                                   / 243153 05WMTVER 138

END
31.0128.31 %0.65
245715 05U SANDSK 69.0 - 247379 05NEVADA SS 69.0 CKT 1 ATSI_P7-1_TE-345-027A_SRT-A
CONTINGENCY 'ATSI_P7-1_TE-345-027A_SRT-A'  /* DB - AD1-103 & DB - HAYES 345

  DISCONNECT BRANCH FROM BUS 238654 TO BUS 241877 CKT 1            /* 02DAV-BE 345 AD1-103 345

  DISCONNECT BRANCH FROM BUS 238654 TO BUS 239289 CKT 1            /* 02DAV-BE 345 02HAYES 345

END
31.0120.02 %0.27
245715 05U SANDSK 69.0 - 247379 05NEVADA SS 69.0 CKT 1 AEP_P4_#13372_05N WALDO 69.0_A_SRT-A
CONTINGENCY 'AEP_P4_#13372_05N WALDO 69.0_A_SRT-A'  

  OPEN BRANCH FROM BUS 242963 TO BUS 243011 CKT 1                  / 242963 05HEDDSS 138 243011 05FULTON 138 1

  OPEN BRANCH FROM BUS 242963 TO BUS 243153 CKT 1                  / 242963 05HEDDSS 138 243153 05WMTVER 138 1

  OPEN BRANCH FROM BUS 242963 TO BUS 245540 CKT 1                  / 242963 05HEDDSS 138 245540 05BLOOMFLD8 138 1

  REMOVE LOAD D1 FROM BUS 243011                                   / 243011 05FULTON 138 D1

  REMOVE LOAD T1 FROM BUS 245540                                   / 245540 05BLOOMFLD8 138 T1

  OPEN BRANCH FROM BUS 243011 TO BUS 243148 CKT 1                  / 243011 05FULTON 138 243148 05WINDFL 138 1

  OPEN BRANCH FROM BUS 243048 TO BUS 243148 CKT 1                  / 243048 05N WALD 138 243148 05WINDFL 138 1

  REMOVE LOAD T1 FROM BUS 243148                                   / 243148 05WINDFL 138 T1

  OPEN BRANCH FROM BUS 243048 TO BUS 270372 CKT 1                  / 243048 05N WALD 138 270372 AD1-106 TAP 138 1

  OPEN BRANCH FROM BUS 243048 TO BUS 245708 CKT 1                  / 243048 05N WALD 138 245708 05N WALDO 69.0 1

  OPEN BRANCH FROM BUS 245708 TO BUS 245716 CKT 1                  / 245708 05N WALDO 69.0 245716 05WALDO 69.0 1

  REMOVE LOAD D1 FROM BUS 245716                                   / 245716 05WALDO 69.0 D1

  REMOVE SWSHUNT FROM BUS 245716                                   / 245716 05WALDO 69.0

  OPEN BRANCH FROM BUS 245716 TO BUS 247032 CKT 1                  / 245716 05WALDO 69.0 247032 05UNCAPHSS 69.0 1

  REMOVE LOAD D1 FROM BUS 247032                                   / 247032 05UNCAPHSS 69.0 D1

  OPEN BRANCH FROM BUS 245711 TO BUS 247032 CKT 1                  / 245711 05S MORRAL 69.0 247032 05UNCAPHSS 69.0 1

/*  OPEN BRANCH FROM BUS 972046 TO BUS 247032 CKT 1                  / 972046 AH1-572 TP 69.0 247032 05UNCAPHSS 69.0 1 /* Withdrawn

  REMOVE LOAD D1 FROM BUS 245711                                   / 245711 05S MORRAL 69.0 D1

  OPEN BRANCH FROM BUS 245710 TO BUS 245711 CKT 1                  / 245710 05RIDGEDALEZ69.0 245711 05S MORRAL 69.0 1

  OPEN BRANCH FROM BUS 245710 TO BUS 290079 CKT Z1                 / 245710 05RIDGEDALEZ69.0 290079 05GOODNOW SS69.0 Z1

  OPEN BRANCH FROM BUS 245391 TO BUS 245710 CKT 1                  / 245391 05RIDGEDALE869.0 245710 05RIDGEDALEZ69.0 1

  OPEN BRANCH FROM BUS 245699 TO BUS 290079 CKT 1                  / 245699 05HARPSTER P69.0 290079 05GOODNOW SS69.0 1

  REMOVE LOAD T1 FROM BUS 245391                                   / 245391 05RIDGEDALE869.0 T1

  REMOVE LOAD C1 FROM BUS 245699                                   / 245699 05HARPSTER P69.0 C1

  OPEN BRANCH FROM BUS 245699 TO BUS 245701 CKT 1                  / 245699 05HARPSTER P69.0 245701 05HARPSTER 69.0 1

END
31.0119.56 %0.38
245715 05U SANDSK 69.0 - 247379 05NEVADA SS 69.0 CKT 1 AEP_P4_#13313_05SBERWICK 69.0_B_SRT-A
CONTINGENCY 'AEP_P4_#13313_05SBERWICK 69.0_B_SRT-A'  

  OPEN BRANCH FROM BUS 242917 TO BUS 243180 CKT 1                  / 242917 05SBERW EQ 1.00 243180 05SBERWICK 69.0 1

  OPEN BRANCH FROM BUS 243162 TO BUS 243180 CKT 1                  / 243162 05BERWICK 69.0 243180 05SBERWICK 69.0 1

  OPEN BRANCH FROM BUS 243180 TO BUS 245688 CKT 1                  / 243180 05SBERWICK 69.0 245688 05CAREY 69.0 1

  OPEN BRANCH FROM BUS 243180 TO BUS 244167 CKT 1                  / 243180 05SBERWICK 69.0 244167 05ADRIAN SS 69.0 1

  OPEN BRANCH FROM BUS 244167 TO BUS 247892 CKT Z1                 / 244167 05ADRIAN SS 69.0 247892 05ADRIAN8 69.0 Z1

  OPEN BRANCH FROM BUS 243170 TO BUS 244167 CKT 1                  / 243170 05HURD SS 69.0 244167 05ADRIAN SS 69.0 1

  OPEN BRANCH FROM BUS 243170 TO BUS 245689 CKT Z1                 / 243170 05HURD SS 69.0 245689 05CAREY8 69.0 Z1

  OPEN BRANCH FROM BUS 243170 TO BUS 245721 CKT 1                  / 243170 05HURD SS 69.0 245721 05TYMOCHSS 69.0 1

  OPEN BRANCH FROM BUS 245706 TO BUS 245721 CKT 1                  / 245706 05N UP SAN 69.0 245721 05TYMOCHSS 69.0 1

  OPEN BRANCH FROM BUS 245706 TO BUS 245715 CKT 1                  / 245706 05N UP SAN 69.0 245715 05U SANDSK 69.0 1

END
31.0119.16 %0.33
245715 05U SANDSK 69.0 - 247379 05NEVADA SS 69.0 CKT 1 AEP_P4_#13312_05SBERWICK 69.0_C_SRT-A
CONTINGENCY 'AEP_P4_#13312_05SBERWICK 69.0_C_SRT-A'  

  OPEN BRANCH FROM BUS 242917 TO BUS 243180 CKT 1                  / 242917 05SBERW EQ 1.00 243180 05SBERWICK 69.0 1

  OPEN BRANCH FROM BUS 243180 TO BUS 244167 CKT 1                  / 243180 05SBERWICK 69.0 244167 05ADRIAN SS 69.0 1

  OPEN BRANCH FROM BUS 243162 TO BUS 243180 CKT 1                  / 243162 05BERWICK 69.0 243180 05SBERWICK 69.0 1

  OPEN BRANCH FROM BUS 243180 TO BUS 245688 CKT 1                  / 243180 05SBERWICK 69.0 245688 05CAREY 69.0 1

  OPEN BRANCH FROM BUS 245688 TO BUS 247454 CKT Z1                 / 245688 05CAREY 69.0 247454 05OGG STREET69.0 Z1

  OPEN BRANCH FROM BUS 245688 TO BUS 245717 CKT 1                  / 245688 05CAREY 69.0 245717 05W.CRAWFORD69.0 1

END
31.0118.29 %0.33
245715 05U SANDSK 69.0 - 247379 05NEVADA SS 69.0 CKT 1 AEP_P4_#16865_05SBERWICK 69.0_A_SRT-A
CONTINGENCY 'AEP_P4_#16865_05SBERWICK 69.0_A_SRT-A'  

  OPEN BRANCH FROM BUS 242917 TO BUS 242942 CKT 1                  / 242917 05SBERW EQ 1.00 242942 05SBERWI 345 1

  OPEN BRANCH FROM BUS 242917 TO BUS 243180 CKT 1                  / 242917 05SBERW EQ 1.00 243180 05SBERWICK 69.0 1

  OPEN BRANCH FROM BUS 242917 TO BUS 243199 CKT 1                  / 242917 05SBERW EQ 1.00 243199 05SBERW1-L 12.0 1

/*  OPEN BRANCH FROM BUS 238745 TO BUS 242942 CKT 1                  / 238745 02GALION 345 242942 05SBERWI 345 1

  OPEN BRANCH FROM BUS 945640 TO BUS 242942 CKT 1                  / 945640 AF1-229 TP 345 242942 05SBERWI 345 1

  OPEN BRANCH FROM BUS 242936 TO BUS 242942 CKT 1                  / 242936 05FOSTOR 345 242942 05SBERWI 345 1

  OPEN BRANCH FROM BUS 243180 TO BUS 244167 CKT 1                  / 243180 05SBERWICK 69.0 244167 05ADRIAN SS 69.0 1

  OPEN BRANCH FROM BUS 243162 TO BUS 243180 CKT 1                  / 243162 05BERWICK 69.0 243180 05SBERWICK 69.0 1

  OPEN BRANCH FROM BUS 243180 TO BUS 245688 CKT 1                  / 243180 05SBERWICK 69.0 245688 05CAREY 69.0 1

END
31.0118.26 %0.33
245715 05U SANDSK 69.0 - 247379 05NEVADA SS 69.0 CKT 1 AEP_P2-2_#13311_05SBERWICK 69.0_1_SRT-A
CONTINGENCY 'AEP_P2-2_#13311_05SBERWICK 69.0_1_SRT-A'  

  OPEN BRANCH FROM BUS 242917 TO BUS 243180 CKT 1                  / 242917 05SBERW EQ 1.00 243180 05SBERWICK 69.0 1

  OPEN BRANCH FROM BUS 243180 TO BUS 244167 CKT 1                  / 243180 05SBERWICK 69.0 244167 05ADRIAN SS 69.0 1

  OPEN BRANCH FROM BUS 243162 TO BUS 243180 CKT 1                  / 243162 05BERWICK 69.0 243180 05SBERWICK 69.0 1

  OPEN BRANCH FROM BUS 243180 TO BUS 245688 CKT 1                  / 243180 05SBERWICK 69.0 245688 05CAREY 69.0 1

END
31.0118.13 %0.33
245715 05U SANDSK 69.0 - 247379 05NEVADA SS 69.0 CKT 1 AEP_P4_#13314_05SBERWICK 69.0_D_SRT-A
CONTINGENCY 'AEP_P4_#13314_05SBERWICK 69.0_D_SRT-A'  

  OPEN BRANCH FROM BUS 242917 TO BUS 243180 CKT 1                  / 242917 05SBERW EQ 1.00 243180 05SBERWICK 69.0 1

  OPEN BRANCH FROM BUS 243180 TO BUS 244167 CKT 1                  / 243180 05SBERWICK 69.0 244167 05ADRIAN SS 69.0 1

  OPEN BRANCH FROM BUS 243162 TO BUS 243180 CKT 1                  / 243162 05BERWICK 69.0 243180 05SBERWICK 69.0 1

  OPEN BRANCH FROM BUS 243162 TO BUS 245713 CKT 1                  / 243162 05BERWICK 69.0 245713 05SENECA SS 69.0 1

  OPEN BRANCH FROM BUS 243180 TO BUS 245688 CKT 1                  / 243180 05SBERWICK 69.0 245688 05CAREY 69.0 1

  OPEN BRANCH FROM BUS 245630 TO BUS 245713 CKT 1                  / 245630 05S TIFFIN 69.0 245713 05SENECA SS 69.0 1

END
31.0118.1 %0.33
245715 05U SANDSK 69.0 - 247379 05NEVADA SS 69.0 CKT 1 AEP_P4_#12471_05S TIFFIN 69.0_F_SRT-A
CONTINGENCY 'AEP_P4_#12471_05S TIFFIN 69.0_F_SRT-A'  

  OPEN BRANCH FROM BUS 243162 TO BUS 243180 CKT 1                  / 243162 05BERWICK 69.0 243180 05SBERWICK 69.0 1

  OPEN BRANCH FROM BUS 243162 TO BUS 245713 CKT 1                  / 243162 05BERWICK 69.0 245713 05SENECA SS 69.0 1

  OPEN BRANCH FROM BUS 243032 TO BUS 245630 CKT 1                  / 243032 05E.TIFFIN 69.0 245630 05S TIFFIN 69.0 1

  OPEN BRANCH FROM BUS 245628 TO BUS 245630 CKT 1                  / 245628 05RIVERVIE 69.0 245630 05S TIFFIN 69.0 1

  OPEN BRANCH FROM BUS 245630 TO BUS 245713 CKT 1                  / 245630 05S TIFFIN 69.0 245713 05SENECA SS 69.0 1

END
31.0116.04 %0.27
245715 05U SANDSK 69.0 - 247379 05NEVADA SS 69.0 CKT 1 AEP_P2-2_#14773_05N WALDO 69.0_1_SRT-A
CONTINGENCY 'AEP_P2-2_#14773_05N WALDO 69.0_1_SRT-A'                                                   /Waldo - La Rue line tapped by AD1-106 & AG2-595

  OPEN BRANCH FROM BUS 243048 TO BUS 245708 CKT 1                  / 243048 05N WALD 138 245708 05N WALDO 69.0 1

  OPEN BRANCH FROM BUS 245708 TO BUS 245716 CKT 1                  / 245708 05N WALDO 69.0 245716 05WALDO 69.0 1

  OPEN BRANCH FROM BUS 243048 TO BUS 270372 CKT 1                  / 243048 05N WALD 138 270372 AD1-106 TAP 138 1

  OPEN BRANCH FROM BUS 243048 TO BUS 243148 CKT 1                  / 243048 05N WALD 138 243148 05WINDFL 138 1

  OPEN BRANCH FROM BUS 243011 TO BUS 243148 CKT 1                  / 243011 05FULTON 138 243148 05WINDFL 138 1

  OPEN BRANCH FROM BUS 242963 TO BUS 243011 CKT 1                  / 242963 05HEDDSS 138 243011 05FULTON 138 1

  OPEN BRANCH FROM BUS 242963 TO BUS 245540 CKT 1                  / 242963 05HEDDSS 138 245540 05BLOOMFLD8 138 1

  OPEN BRANCH FROM BUS 242963 TO BUS 243153 CKT 1                  / 242963 05HEDDSS 138 243153 05WMTVER 138 1

  REMOVE LOAD D2 FROM BUS 245708                                   / 245708 05N WALDO 69.0 D2

END
31.0114.3 %0.38
245715 05U SANDSK 69.0 - 247379 05NEVADA SS 69.0 CKT 1 AEP_P2-2_#12469_05S TIFFIN 69.0_1_SRT-A
CONTINGENCY 'AEP_P2-2_#12469_05S TIFFIN 69.0_1_SRT-A'  

  OPEN BRANCH FROM BUS 243110 TO BUS 245630 CKT 1                  / 243110 05STIFFI 138 245630 05S TIFFIN 69.0 1

  OPEN BRANCH FROM BUS 243032 TO BUS 245630 CKT 1                  / 243032 05E.TIFFIN 69.0 245630 05S TIFFIN 69.0 1

  OPEN BRANCH FROM BUS 245628 TO BUS 245630 CKT 1                  / 245628 05RIVERVIE 69.0 245630 05S TIFFIN 69.0 1

  OPEN BRANCH FROM BUS 245630 TO BUS 245713 CKT 1                  / 245630 05S TIFFIN 69.0 245713 05SENECA SS 69.0 1

END
31.0114.2 %0.27
245715 05U SANDSK 69.0 - 247379 05NEVADA SS 69.0 CKT 1 AEP_P4_#12469_05S TIFFIN 69.0_E_SRT-A
CONTINGENCY 'AEP_P4_#12469_05S TIFFIN 69.0_E_SRT-A'  

  OPEN BRANCH FROM BUS 243110 TO BUS 245630 CKT 1                  / 243110 05STIFFI 138 245630 05S TIFFIN 69.0 1

  OPEN BRANCH FROM BUS 243032 TO BUS 245630 CKT 1                  / 243032 05E.TIFFIN 69.0 245630 05S TIFFIN 69.0 1

  OPEN BRANCH FROM BUS 245628 TO BUS 245630 CKT 1                  / 245628 05RIVERVIE 69.0 245630 05S TIFFIN 69.0 1

  OPEN BRANCH FROM BUS 245630 TO BUS 245713 CKT 1                  / 245630 05S TIFFIN 69.0 245713 05SENECA SS 69.0 1

END
31.0114.2 %0.27
245715 05U SANDSK 69.0 - 247379 05NEVADA SS 69.0 CKT 1 AEP_P2-2_#17157_05E.TIFFIN 69.0_1_SRT-A
CONTINGENCY 'AEP_P2-2_#17157_05E.TIFFIN 69.0_1_SRT-A'  

  OPEN BRANCH FROM BUS 243032 TO BUS 245630 CKT 1                  / 243032 05E.TIFFIN 69.0 245630 05S TIFFIN 69.0 1

  OPEN BRANCH FROM BUS 243032 TO BUS 290149 CKT 1                  / 243032 05E.TIFFIN 69.0 290149 05MOUSEY SS 69.0 1

  REMOVE LOAD D1 FROM BUS 243032                                   / 243032 05E.TIFFIN 69.0 D1

END
31.0109.62 %0.25
245715 05U SANDSK 69.0 - 247379 05NEVADA SS 69.0 CKT 1 ATSI_P7-1_TE-345-030_SRT-A
CONTINGENCY 'ATSI_P7-1_TE-345-030_SRT-A'  /* AD1-103 - BEAVER & HAYES - BEAVER 345

  DISCONNECT BRANCH FROM BUS 241877 TO BUS 238569 CKT 1            /* AD1-103 345 02BEAVER 345

  DISCONNECT BRANCH FROM BUS 239289 TO BUS 238569 CKT 1            /* 02HAYES 345 02BEAVER 345

END
31.0101.92 %0.27
246873 05FONTAINE 69.0 - 246874 05KENTON 69.0 CKT 1 AEP_P4_#17794_05SKENTO 138_CB4_SRT-A
CONTINGENCY 'AEP_P4_#17794_05SKENTO 138_CB4_SRT-A'  

  OPEN BRANCH FROM BUS 243103 TO BUS 246879 CKT 1                  / 243103 05SKENTO 138 246879 05S KENTN1 69.0 1

  OPEN BRANCH FROM BUS 246874 TO BUS 246879 CKT 1                  / 246874 05KENTON 69.0 246879 05S KENTN1 69.0 1

  OPEN BRANCH FROM BUS 246878 TO BUS 246879 CKT 1                  / 246878 05RT 31 8 69.0 246879 05S KENTN1 69.0 1

  OPEN BRANCH FROM BUS 242989 TO BUS 243155 CKT 1                  / 242989 05E LIMA 138 243155 05W.NEWTONSS 138 1

  OPEN BRANCH FROM BUS 243155 TO BUS 245856 CKT Z1                 / 243155 05W.NEWTONSS 138 245856 05W.NEWTON8 138 Z1

  OPEN BRANCH FROM BUS 243031 TO BUS 270584 CKT 1                  / 243031 05LYNN Z 138 270584 AE1-091_PO1 138 1

  OPEN BRANCH FROM BUS 270584 TO BUS 243155 CKT 1                  / 270584 AE1-091_PO1 138 243155 05W.NEWTONSS 138 1

  OPEN BRANCH FROM BUS 243031 TO BUS 243103 CKT 1                  / 243031 05LYNN Z 138 243103 05SKENTO 138 1

END
50.0123.02 %1.15
246873 05FONTAINE 69.0 - 246874 05KENTON 69.0 CKT 1 AEP_P4_#12466_05S KENTN1 69.0_C_SRT-A
CONTINGENCY 'AEP_P4_#12466_05S KENTN1 69.0_C_SRT-A'  

  OPEN BRANCH FROM BUS 243103 TO BUS 246879 CKT 1                  / 243103 05SKENTO 138 246879 05S KENTN1 69.0 1

  OPEN BRANCH FROM BUS 246874 TO BUS 246879 CKT 1                  / 246874 05KENTON 69.0 246879 05S KENTN1 69.0 1

  OPEN BRANCH FROM BUS 246878 TO BUS 246879 CKT 1                  / 246878 05RT 31 8 69.0 246879 05S KENTN1 69.0 1

END
50.0106.44 %0.44
246873 05FONTAINE 69.0 - 246874 05KENTON 69.0 CKT 1 AEP_P2-2_#11860_05S KENTN1 69.0_1_SRT-A
CONTINGENCY 'AEP_P2-2_#11860_05S KENTN1 69.0_1_SRT-A'  

  OPEN BRANCH FROM BUS 243103 TO BUS 246879 CKT 1                  / 243103 05SKENTO 138 246879 05S KENTN1 69.0 1

  OPEN BRANCH FROM BUS 246874 TO BUS 246879 CKT 1                  / 246874 05KENTON 69.0 246879 05S KENTN1 69.0 1

  OPEN BRANCH FROM BUS 246878 TO BUS 246879 CKT 1                  / 246878 05RT 31 8 69.0 246879 05S KENTN1 69.0 1

END
50.0106.44 %0.44
246879 05S KENTN1 69.0 - 246874 05KENTON 69.0 CKT 1 AEP_P4_#17791_05SKENTO 138_CB1_SRT-A
CONTINGENCY 'AEP_P4_#17791_05SKENTO 138_CB1_SRT-A'  

  OPEN BRANCH FROM BUS 242989 TO BUS 243155 CKT 1                  / 242989 05E LIMA 138 243155 05W.NEWTONSS 138 1

  OPEN BRANCH FROM BUS 243155 TO BUS 245856 CKT Z1                 / 243155 05W.NEWTONSS 138 245856 05W.NEWTON8 138 Z1

  OPEN BRANCH FROM BUS 243031 TO BUS 270584 CKT 1                  / 243031 05LYNN Z 138 270584 AE1-091_PO1 138 1

  OPEN BRANCH FROM BUS 270584 TO BUS 243155 CKT 1                  / 270584 AE1-091_PO1 138 243155 05W.NEWTONSS 138 1

  OPEN BRANCH FROM BUS 243031 TO BUS 243103 CKT 1                  / 243031 05LYNN Z 138 243103 05SKENTO 138 1

  OPEN BRANCH FROM BUS 243103 TO BUS 289012 CKT 2                  / 243103 05SKENTO 138 289012 05S.KENTN2EQ1.00 2

  OPEN BRANCH FROM BUS 246880 TO BUS 289012 CKT 2                  / 246880 05S KENTN2 69.0 289012 05S.KENTN2EQ1.00 2

  OPEN BRANCH FROM BUS 289011 TO BUS 289012 CKT 2                  / 289011 05S.KENTN T213.0 289012 05S.KENTN2EQ1.00 2

  OPEN BRANCH FROM BUS 246873 TO BUS 246880 CKT 1                  / 246873 05FONTAINE 69.0 246880 05S KENTN2 69.0 1

END
35.0168.47 %1.09
246879 05S KENTN1 69.0 - 246874 05KENTON 69.0 CKT 1 AEP_P2-2_#12467_05S KENTN2 69.0_1_SRT-A
CONTINGENCY 'AEP_P2-2_#12467_05S KENTN2 69.0_1_SRT-A'  

  OPEN BRANCH FROM BUS 243103 TO BUS 289012 CKT 2                  / 243103 05SKENTO 138 289012 05S.KENTN2EQ1.00 2

  OPEN BRANCH FROM BUS 246880 TO BUS 289012 CKT 2                  / 246880 05S KENTN2 69.0 289012 05S.KENTN2EQ1.00 2

  OPEN BRANCH FROM BUS 289011 TO BUS 289012 CKT 2                  / 289011 05S.KENTN T213.0 289012 05S.KENTN2EQ1.00 2

  OPEN BRANCH FROM BUS 246873 TO BUS 246880 CKT 1                  / 246873 05FONTAINE 69.0 246880 05S KENTN2 69.0 1

END
35.0142.97 %0.41
246879 05S KENTN1 69.0 - 246874 05KENTON 69.0 CKT 1 AEP_P4_#12468_05S KENTN2 69.0_E_SRT-A
CONTINGENCY 'AEP_P4_#12468_05S KENTN2 69.0_E_SRT-A'  

  OPEN BRANCH FROM BUS 243103 TO BUS 289012 CKT 2                  / 243103 05SKENTO 138 289012 05S.KENTN2EQ1.00 2

  OPEN BRANCH FROM BUS 246880 TO BUS 289012 CKT 2                  / 246880 05S KENTN2 69.0 289012 05S.KENTN2EQ1.00 2

  OPEN BRANCH FROM BUS 289011 TO BUS 289012 CKT 2                  / 289011 05S.KENTN T213.0 289012 05S.KENTN2EQ1.00 2

  OPEN BRANCH FROM BUS 246873 TO BUS 246880 CKT 1                  / 246873 05FONTAINE 69.0 246880 05S KENTN2 69.0 1

  OPEN BRANCH FROM BUS 246873 TO BUS 246874 CKT 1                  / 246873 05FONTAINE 69.0 246874 05KENTON 69.0 1

END
35.0141.54 %0.41
246879 05S KENTN1 69.0 - 246874 05KENTON 69.0 CKT 1 AEP_P4_#17795_05KENTON 69.0_CB1_SRT-A
CONTINGENCY 'AEP_P4_#17795_05KENTON 69.0_CB1_SRT-A'  

  OPEN BRANCH FROM BUS 246873 TO BUS 246880 CKT 1                  / 246873 05FONTAINE 69.0 246880 05S KENTN2 69.0 1

  OPEN BRANCH FROM BUS 246873 TO BUS 246874 CKT 1                  / 246873 05FONTAINE 69.0 246874 05KENTON 69.0 1

  REMOVE SWSHUNT FROM BUS 246874                                   / 246874 05KENTON 69.0

  REMOVE LOAD D1 FROM BUS 246874                                   / 246874 05KENTON 69.0 D1

END
35.0130.83 %0.41
246879 05S KENTN1 69.0 - 246874 05KENTON 69.0 CKT 1 AEP_P2-2_#11811_05KENTON 69.0_1_SRT-A
CONTINGENCY 'AEP_P2-2_#11811_05KENTON 69.0_1_SRT-A'  

  OPEN BRANCH FROM BUS 246873 TO BUS 246874 CKT 1                  / 246873 05FONTAINE 69.0 246874 05KENTON 69.0 1

  REMOVE SWSHUNT FROM BUS 246874                                   / 246874 05KENTON 69.0

  REMOVE LOAD D1 FROM BUS 246874                                   / 246874 05KENTON 69.0 D1

END
35.0130.52 %0.41
246879 05S KENTN1 69.0 - 246874 05KENTON 69.0 CKT 1 AEP_P4_#10732_05WMTVER 138_A_SRT-A
CONTINGENCY 'AEP_P4_#10732_05WMTVER 138_A_SRT-A'  

  OPEN BRANCH FROM BUS 242950 TO BUS 243153 CKT 1                  / 242950 05ACADEM 138 243153 05WMTVER 138 1

  OPEN BRANCH FROM BUS 243098 TO BUS 243153 CKT 1                  / 243098 05SHARPR 138 243153 05WMTVER 138 1

  OPEN BRANCH FROM BUS 243153 TO BUS 245562 CKT 1                  / 243153 05WMTVER 138 245562 05W MT VER 69.0 1

  OPEN BRANCH FROM BUS 242963 TO BUS 245540 CKT 1                  / 242963 05HEDDSS 138 245540 05BLOOMFLD8 138 1

  OPEN BRANCH FROM BUS 242963 TO BUS 243153 CKT 1                  / 242963 05HEDDSS 138 243153 05WMTVER 138 1

  OPEN BRANCH FROM BUS 242963 TO BUS 243011 CKT 1                  / 242963 05HEDDSS 138 243011 05FULTON 138 1

  OPEN BRANCH FROM BUS 243011 TO BUS 243148 CKT 1                  / 243011 05FULTON 138 243148 05WINDFL 138 1

  OPEN BRANCH FROM BUS 243048 TO BUS 243148 CKT 1                  / 243048 05N WALD 138 243148 05WINDFL 138 1

  OPEN BRANCH FROM BUS 243048 TO BUS 245708 CKT 1                  / 243048 05N WALD 138 245708 05N WALDO 69.0 1

/*  OPEN BRANCH FROM BUS 243048 TO BUS 244566 CKT 1                  / 243048 05N WALD 138 244566 05LA RUE 138 1

  OPEN BRANCH FROM BUS 243048 TO BUS 270372 CKT 1                  / 243048 05N WALD 138 270372 AD1-106 TAP 138 1

  REMOVE SWSHUNT FROM BUS 243153                                   / 243153 05WMTVER 138

END
35.0114.68 %0.63
246879 05S KENTN1 69.0 - 246874 05KENTON 69.0 CKT 1 AEP_P2-2_#14773_05N WALDO 69.0_1_SRT-A
CONTINGENCY 'AEP_P2-2_#14773_05N WALDO 69.0_1_SRT-A'                                                   /Waldo - La Rue line tapped by AD1-106 & AG2-595

  OPEN BRANCH FROM BUS 243048 TO BUS 245708 CKT 1                  / 243048 05N WALD 138 245708 05N WALDO 69.0 1

  OPEN BRANCH FROM BUS 245708 TO BUS 245716 CKT 1                  / 245708 05N WALDO 69.0 245716 05WALDO 69.0 1

  OPEN BRANCH FROM BUS 243048 TO BUS 270372 CKT 1                  / 243048 05N WALD 138 270372 AD1-106 TAP 138 1

  OPEN BRANCH FROM BUS 243048 TO BUS 243148 CKT 1                  / 243048 05N WALD 138 243148 05WINDFL 138 1

  OPEN BRANCH FROM BUS 243011 TO BUS 243148 CKT 1                  / 243011 05FULTON 138 243148 05WINDFL 138 1

  OPEN BRANCH FROM BUS 242963 TO BUS 243011 CKT 1                  / 242963 05HEDDSS 138 243011 05FULTON 138 1

  OPEN BRANCH FROM BUS 242963 TO BUS 245540 CKT 1                  / 242963 05HEDDSS 138 245540 05BLOOMFLD8 138 1

  OPEN BRANCH FROM BUS 242963 TO BUS 243153 CKT 1                  / 242963 05HEDDSS 138 243153 05WMTVER 138 1

  REMOVE LOAD D2 FROM BUS 245708                                   / 245708 05N WALDO 69.0 D2

END
35.0114.41 %0.63
246880 05S KENTN2 69.0 - 246873 05FONTAINE 69.0 CKT 1 AEP_P4_#17794_05SKENTO 138_CB4_SRT-A
CONTINGENCY 'AEP_P4_#17794_05SKENTO 138_CB4_SRT-A'  

  OPEN BRANCH FROM BUS 243103 TO BUS 246879 CKT 1                  / 243103 05SKENTO 138 246879 05S KENTN1 69.0 1

  OPEN BRANCH FROM BUS 246874 TO BUS 246879 CKT 1                  / 246874 05KENTON 69.0 246879 05S KENTN1 69.0 1

  OPEN BRANCH FROM BUS 246878 TO BUS 246879 CKT 1                  / 246878 05RT 31 8 69.0 246879 05S KENTN1 69.0 1

  OPEN BRANCH FROM BUS 242989 TO BUS 243155 CKT 1                  / 242989 05E LIMA 138 243155 05W.NEWTONSS 138 1

  OPEN BRANCH FROM BUS 243155 TO BUS 245856 CKT Z1                 / 243155 05W.NEWTONSS 138 245856 05W.NEWTON8 138 Z1

  OPEN BRANCH FROM BUS 243031 TO BUS 270584 CKT 1                  / 243031 05LYNN Z 138 270584 AE1-091_PO1 138 1

  OPEN BRANCH FROM BUS 270584 TO BUS 243155 CKT 1                  / 270584 AE1-091_PO1 138 243155 05W.NEWTONSS 138 1

  OPEN BRANCH FROM BUS 243031 TO BUS 243103 CKT 1                  / 243031 05LYNN Z 138 243103 05SKENTO 138 1

END
50.0124.86 %1.15
246880 05S KENTN2 69.0 - 246873 05FONTAINE 69.0 CKT 1 AEP_P4_#12466_05S KENTN1 69.0_C_SRT-A
CONTINGENCY 'AEP_P4_#12466_05S KENTN1 69.0_C_SRT-A'  

  OPEN BRANCH FROM BUS 243103 TO BUS 246879 CKT 1                  / 243103 05SKENTO 138 246879 05S KENTN1 69.0 1

  OPEN BRANCH FROM BUS 246874 TO BUS 246879 CKT 1                  / 246874 05KENTON 69.0 246879 05S KENTN1 69.0 1

  OPEN BRANCH FROM BUS 246878 TO BUS 246879 CKT 1                  / 246878 05RT 31 8 69.0 246879 05S KENTN1 69.0 1

END
50.0108.28 %0.44
246880 05S KENTN2 69.0 - 246873 05FONTAINE 69.0 CKT 1 AEP_P2-2_#11860_05S KENTN1 69.0_1_SRT-A
CONTINGENCY 'AEP_P2-2_#11860_05S KENTN1 69.0_1_SRT-A'  

  OPEN BRANCH FROM BUS 243103 TO BUS 246879 CKT 1                  / 243103 05SKENTO 138 246879 05S KENTN1 69.0 1

  OPEN BRANCH FROM BUS 246874 TO BUS 246879 CKT 1                  / 246874 05KENTON 69.0 246879 05S KENTN1 69.0 1

  OPEN BRANCH FROM BUS 246878 TO BUS 246879 CKT 1                  / 246878 05RT 31 8 69.0 246879 05S KENTN1 69.0 1

END
50.0108.28 %0.44
246880 05S KENTN2 69.0 - 246873 05FONTAINE 69.0 CKT 1 AEP_P4_#10732_05WMTVER 138_A_SRT-A
CONTINGENCY 'AEP_P4_#10732_05WMTVER 138_A_SRT-A'  

  OPEN BRANCH FROM BUS 242950 TO BUS 243153 CKT 1                  / 242950 05ACADEM 138 243153 05WMTVER 138 1

  OPEN BRANCH FROM BUS 243098 TO BUS 243153 CKT 1                  / 243098 05SHARPR 138 243153 05WMTVER 138 1

  OPEN BRANCH FROM BUS 243153 TO BUS 245562 CKT 1                  / 243153 05WMTVER 138 245562 05W MT VER 69.0 1

  OPEN BRANCH FROM BUS 242963 TO BUS 245540 CKT 1                  / 242963 05HEDDSS 138 245540 05BLOOMFLD8 138 1

  OPEN BRANCH FROM BUS 242963 TO BUS 243153 CKT 1                  / 242963 05HEDDSS 138 243153 05WMTVER 138 1

  OPEN BRANCH FROM BUS 242963 TO BUS 243011 CKT 1                  / 242963 05HEDDSS 138 243011 05FULTON 138 1

  OPEN BRANCH FROM BUS 243011 TO BUS 243148 CKT 1                  / 243011 05FULTON 138 243148 05WINDFL 138 1

  OPEN BRANCH FROM BUS 243048 TO BUS 243148 CKT 1                  / 243048 05N WALD 138 243148 05WINDFL 138 1

  OPEN BRANCH FROM BUS 243048 TO BUS 245708 CKT 1                  / 243048 05N WALD 138 245708 05N WALDO 69.0 1

/*  OPEN BRANCH FROM BUS 243048 TO BUS 244566 CKT 1                  / 243048 05N WALD 138 244566 05LA RUE 138 1

  OPEN BRANCH FROM BUS 243048 TO BUS 270372 CKT 1                  / 243048 05N WALD 138 270372 AD1-106 TAP 138 1

  REMOVE SWSHUNT FROM BUS 243153                                   / 243153 05WMTVER 138

END
50.0100.64 %0.79
246880 05S KENTN2 69.0 - 246873 05FONTAINE 69.0 CKT 1 AEP_P2-2_#14773_05N WALDO 69.0_1_SRT-A
CONTINGENCY 'AEP_P2-2_#14773_05N WALDO 69.0_1_SRT-A'                                                   /Waldo - La Rue line tapped by AD1-106 & AG2-595

  OPEN BRANCH FROM BUS 243048 TO BUS 245708 CKT 1                  / 243048 05N WALD 138 245708 05N WALDO 69.0 1

  OPEN BRANCH FROM BUS 245708 TO BUS 245716 CKT 1                  / 245708 05N WALDO 69.0 245716 05WALDO 69.0 1

  OPEN BRANCH FROM BUS 243048 TO BUS 270372 CKT 1                  / 243048 05N WALD 138 270372 AD1-106 TAP 138 1

  OPEN BRANCH FROM BUS 243048 TO BUS 243148 CKT 1                  / 243048 05N WALD 138 243148 05WINDFL 138 1

  OPEN BRANCH FROM BUS 243011 TO BUS 243148 CKT 1                  / 243011 05FULTON 138 243148 05WINDFL 138 1

  OPEN BRANCH FROM BUS 242963 TO BUS 243011 CKT 1                  / 242963 05HEDDSS 138 243011 05FULTON 138 1

  OPEN BRANCH FROM BUS 242963 TO BUS 245540 CKT 1                  / 242963 05HEDDSS 138 245540 05BLOOMFLD8 138 1

  OPEN BRANCH FROM BUS 242963 TO BUS 243153 CKT 1                  / 242963 05HEDDSS 138 243153 05WMTVER 138 1

  REMOVE LOAD D2 FROM BUS 245708                                   / 245708 05N WALDO 69.0 D2

END
50.0100.25 %0.79
247379 05NEVADA SS 69.0 - 245687 05BROK SWR 69.0 CKT 1 AEP_P4_#5710_05WMTVER 138_B_SRT-A
CONTINGENCY 'AEP_P4_#5710_05WMTVER 138_B_SRT-A'  

  OPEN BRANCH FROM BUS 242950 TO BUS 243153 CKT 1                  / 242950 05ACADEM 138 243153 05WMTVER 138 1

  OPEN BRANCH FROM BUS 242963 TO BUS 243153 CKT 1                  / 242963 05HEDDSS 138 243153 05WMTVER 138 1

  OPEN BRANCH FROM BUS 243098 TO BUS 243153 CKT 1                  / 243098 05SHARPR 138 243153 05WMTVER 138 1

  OPEN BRANCH FROM BUS 243153 TO BUS 245562 CKT 1                  / 243153 05WMTVER 138 245562 05W MT VER 69.0 1

  REMOVE SWSHUNT FROM BUS 243153                                   / 243153 05WMTVER 138

END
31.0124.35 %0.65
247379 05NEVADA SS 69.0 - 245687 05BROK SWR 69.0 CKT 1 AEP_P2-2_#5710_05WMTVER 138_1_SRT-A
CONTINGENCY 'AEP_P2-2_#5710_05WMTVER 138_1_SRT-A'  

  OPEN BRANCH FROM BUS 242950 TO BUS 243153 CKT 1                  / 242950 05ACADEM 138 243153 05WMTVER 138 1

  OPEN BRANCH FROM BUS 242963 TO BUS 243153 CKT 1                  / 242963 05HEDDSS 138 243153 05WMTVER 138 1

  OPEN BRANCH FROM BUS 243098 TO BUS 243153 CKT 1                  / 243098 05SHARPR 138 243153 05WMTVER 138 1

  OPEN BRANCH FROM BUS 243153 TO BUS 245562 CKT 1                  / 243153 05WMTVER 138 245562 05W MT VER 69.0 1

  REMOVE SWSHUNT FROM BUS 243153                                   / 243153 05WMTVER 138

END
31.0124.35 %0.65
247379 05NEVADA SS 69.0 - 245687 05BROK SWR 69.0 CKT 1 AEP_P4_#13313_05SBERWICK 69.0_B_SRT-A
CONTINGENCY 'AEP_P4_#13313_05SBERWICK 69.0_B_SRT-A'  

  OPEN BRANCH FROM BUS 242917 TO BUS 243180 CKT 1                  / 242917 05SBERW EQ 1.00 243180 05SBERWICK 69.0 1

  OPEN BRANCH FROM BUS 243162 TO BUS 243180 CKT 1                  / 243162 05BERWICK 69.0 243180 05SBERWICK 69.0 1

  OPEN BRANCH FROM BUS 243180 TO BUS 245688 CKT 1                  / 243180 05SBERWICK 69.0 245688 05CAREY 69.0 1

  OPEN BRANCH FROM BUS 243180 TO BUS 244167 CKT 1                  / 243180 05SBERWICK 69.0 244167 05ADRIAN SS 69.0 1

  OPEN BRANCH FROM BUS 244167 TO BUS 247892 CKT Z1                 / 244167 05ADRIAN SS 69.0 247892 05ADRIAN8 69.0 Z1

  OPEN BRANCH FROM BUS 243170 TO BUS 244167 CKT 1                  / 243170 05HURD SS 69.0 244167 05ADRIAN SS 69.0 1

  OPEN BRANCH FROM BUS 243170 TO BUS 245689 CKT Z1                 / 243170 05HURD SS 69.0 245689 05CAREY8 69.0 Z1

  OPEN BRANCH FROM BUS 243170 TO BUS 245721 CKT 1                  / 243170 05HURD SS 69.0 245721 05TYMOCHSS 69.0 1

  OPEN BRANCH FROM BUS 245706 TO BUS 245721 CKT 1                  / 245706 05N UP SAN 69.0 245721 05TYMOCHSS 69.0 1

  OPEN BRANCH FROM BUS 245706 TO BUS 245715 CKT 1                  / 245706 05N UP SAN 69.0 245715 05U SANDSK 69.0 1

END
31.0118.16 %0.33
247379 05NEVADA SS 69.0 - 245687 05BROK SWR 69.0 CKT 1 AEP_P4_#16865_05SBERWICK 69.0_A_SRT-A
CONTINGENCY 'AEP_P4_#16865_05SBERWICK 69.0_A_SRT-A'  

  OPEN BRANCH FROM BUS 242917 TO BUS 242942 CKT 1                  / 242917 05SBERW EQ 1.00 242942 05SBERWI 345 1

  OPEN BRANCH FROM BUS 242917 TO BUS 243180 CKT 1                  / 242917 05SBERW EQ 1.00 243180 05SBERWICK 69.0 1

  OPEN BRANCH FROM BUS 242917 TO BUS 243199 CKT 1                  / 242917 05SBERW EQ 1.00 243199 05SBERW1-L 12.0 1

/*  OPEN BRANCH FROM BUS 238745 TO BUS 242942 CKT 1                  / 238745 02GALION 345 242942 05SBERWI 345 1

  OPEN BRANCH FROM BUS 945640 TO BUS 242942 CKT 1                  / 945640 AF1-229 TP 345 242942 05SBERWI 345 1

  OPEN BRANCH FROM BUS 242936 TO BUS 242942 CKT 1                  / 242936 05FOSTOR 345 242942 05SBERWI 345 1

  OPEN BRANCH FROM BUS 243180 TO BUS 244167 CKT 1                  / 243180 05SBERWICK 69.0 244167 05ADRIAN SS 69.0 1

  OPEN BRANCH FROM BUS 243162 TO BUS 243180 CKT 1                  / 243162 05BERWICK 69.0 243180 05SBERWICK 69.0 1

  OPEN BRANCH FROM BUS 243180 TO BUS 245688 CKT 1                  / 243180 05SBERWICK 69.0 245688 05CAREY 69.0 1

END
31.0117.26 %0.33
247379 05NEVADA SS 69.0 - 245687 05BROK SWR 69.0 CKT 1 AEP_P4_#13312_05SBERWICK 69.0_C_SRT-A
CONTINGENCY 'AEP_P4_#13312_05SBERWICK 69.0_C_SRT-A'  

  OPEN BRANCH FROM BUS 242917 TO BUS 243180 CKT 1                  / 242917 05SBERW EQ 1.00 243180 05SBERWICK 69.0 1

  OPEN BRANCH FROM BUS 243180 TO BUS 244167 CKT 1                  / 243180 05SBERWICK 69.0 244167 05ADRIAN SS 69.0 1

  OPEN BRANCH FROM BUS 243162 TO BUS 243180 CKT 1                  / 243162 05BERWICK 69.0 243180 05SBERWICK 69.0 1

  OPEN BRANCH FROM BUS 243180 TO BUS 245688 CKT 1                  / 243180 05SBERWICK 69.0 245688 05CAREY 69.0 1

  OPEN BRANCH FROM BUS 245688 TO BUS 247454 CKT Z1                 / 245688 05CAREY 69.0 247454 05OGG STREET69.0 Z1

  OPEN BRANCH FROM BUS 245688 TO BUS 245717 CKT 1                  / 245688 05CAREY 69.0 245717 05W.CRAWFORD69.0 1

END
31.0117.26 %0.33
247379 05NEVADA SS 69.0 - 245687 05BROK SWR 69.0 CKT 1 AEP_P2-2_#13311_05SBERWICK 69.0_1_SRT-A
CONTINGENCY 'AEP_P2-2_#13311_05SBERWICK 69.0_1_SRT-A'  

  OPEN BRANCH FROM BUS 242917 TO BUS 243180 CKT 1                  / 242917 05SBERW EQ 1.00 243180 05SBERWICK 69.0 1

  OPEN BRANCH FROM BUS 243180 TO BUS 244167 CKT 1                  / 243180 05SBERWICK 69.0 244167 05ADRIAN SS 69.0 1

  OPEN BRANCH FROM BUS 243162 TO BUS 243180 CKT 1                  / 243162 05BERWICK 69.0 243180 05SBERWICK 69.0 1

  OPEN BRANCH FROM BUS 243180 TO BUS 245688 CKT 1                  / 243180 05SBERWICK 69.0 245688 05CAREY 69.0 1

END
31.0117.1 %0.33
247379 05NEVADA SS 69.0 - 245687 05BROK SWR 69.0 CKT 1 AEP_P4_#13314_05SBERWICK 69.0_D_SRT-A
CONTINGENCY 'AEP_P4_#13314_05SBERWICK 69.0_D_SRT-A'  

  OPEN BRANCH FROM BUS 242917 TO BUS 243180 CKT 1                  / 242917 05SBERW EQ 1.00 243180 05SBERWICK 69.0 1

  OPEN BRANCH FROM BUS 243180 TO BUS 244167 CKT 1                  / 243180 05SBERWICK 69.0 244167 05ADRIAN SS 69.0 1

  OPEN BRANCH FROM BUS 243162 TO BUS 243180 CKT 1                  / 243162 05BERWICK 69.0 243180 05SBERWICK 69.0 1

  OPEN BRANCH FROM BUS 243162 TO BUS 245713 CKT 1                  / 243162 05BERWICK 69.0 245713 05SENECA SS 69.0 1

  OPEN BRANCH FROM BUS 243180 TO BUS 245688 CKT 1                  / 243180 05SBERWICK 69.0 245688 05CAREY 69.0 1

  OPEN BRANCH FROM BUS 245630 TO BUS 245713 CKT 1                  / 245630 05S TIFFIN 69.0 245713 05SENECA SS 69.0 1

END
31.0117.06 %0.33
247379 05NEVADA SS 69.0 - 245687 05BROK SWR 69.0 CKT 1 ATSI_P7-1_TE-345-027A_SRT-A
CONTINGENCY 'ATSI_P7-1_TE-345-027A_SRT-A'  /* DB - AD1-103 & DB - HAYES 345

  DISCONNECT BRANCH FROM BUS 238654 TO BUS 241877 CKT 1            /* 02DAV-BE 345 AD1-103 345

  DISCONNECT BRANCH FROM BUS 238654 TO BUS 239289 CKT 1            /* 02DAV-BE 345 02HAYES 345

END
31.0115.85 %0.27
247379 05NEVADA SS 69.0 - 245687 05BROK SWR 69.0 CKT 1 AEP_P4_#13372_05N WALDO 69.0_A_SRT-A
CONTINGENCY 'AEP_P4_#13372_05N WALDO 69.0_A_SRT-A'  

  OPEN BRANCH FROM BUS 242963 TO BUS 243011 CKT 1                  / 242963 05HEDDSS 138 243011 05FULTON 138 1

  OPEN BRANCH FROM BUS 242963 TO BUS 243153 CKT 1                  / 242963 05HEDDSS 138 243153 05WMTVER 138 1

  OPEN BRANCH FROM BUS 242963 TO BUS 245540 CKT 1                  / 242963 05HEDDSS 138 245540 05BLOOMFLD8 138 1

  REMOVE LOAD D1 FROM BUS 243011                                   / 243011 05FULTON 138 D1

  REMOVE LOAD T1 FROM BUS 245540                                   / 245540 05BLOOMFLD8 138 T1

  OPEN BRANCH FROM BUS 243011 TO BUS 243148 CKT 1                  / 243011 05FULTON 138 243148 05WINDFL 138 1

  OPEN BRANCH FROM BUS 243048 TO BUS 243148 CKT 1                  / 243048 05N WALD 138 243148 05WINDFL 138 1

  REMOVE LOAD T1 FROM BUS 243148                                   / 243148 05WINDFL 138 T1

  OPEN BRANCH FROM BUS 243048 TO BUS 270372 CKT 1                  / 243048 05N WALD 138 270372 AD1-106 TAP 138 1

  OPEN BRANCH FROM BUS 243048 TO BUS 245708 CKT 1                  / 243048 05N WALD 138 245708 05N WALDO 69.0 1

  OPEN BRANCH FROM BUS 245708 TO BUS 245716 CKT 1                  / 245708 05N WALDO 69.0 245716 05WALDO 69.0 1

  REMOVE LOAD D1 FROM BUS 245716                                   / 245716 05WALDO 69.0 D1

  REMOVE SWSHUNT FROM BUS 245716                                   / 245716 05WALDO 69.0

  OPEN BRANCH FROM BUS 245716 TO BUS 247032 CKT 1                  / 245716 05WALDO 69.0 247032 05UNCAPHSS 69.0 1

  REMOVE LOAD D1 FROM BUS 247032                                   / 247032 05UNCAPHSS 69.0 D1

  OPEN BRANCH FROM BUS 245711 TO BUS 247032 CKT 1                  / 245711 05S MORRAL 69.0 247032 05UNCAPHSS 69.0 1

/*  OPEN BRANCH FROM BUS 972046 TO BUS 247032 CKT 1                  / 972046 AH1-572 TP 69.0 247032 05UNCAPHSS 69.0 1 /* Withdrawn

  REMOVE LOAD D1 FROM BUS 245711                                   / 245711 05S MORRAL 69.0 D1

  OPEN BRANCH FROM BUS 245710 TO BUS 245711 CKT 1                  / 245710 05RIDGEDALEZ69.0 245711 05S MORRAL 69.0 1

  OPEN BRANCH FROM BUS 245710 TO BUS 290079 CKT Z1                 / 245710 05RIDGEDALEZ69.0 290079 05GOODNOW SS69.0 Z1

  OPEN BRANCH FROM BUS 245391 TO BUS 245710 CKT 1                  / 245391 05RIDGEDALE869.0 245710 05RIDGEDALEZ69.0 1

  OPEN BRANCH FROM BUS 245699 TO BUS 290079 CKT 1                  / 245699 05HARPSTER P69.0 290079 05GOODNOW SS69.0 1

  REMOVE LOAD T1 FROM BUS 245391                                   / 245391 05RIDGEDALE869.0 T1

  REMOVE LOAD C1 FROM BUS 245699                                   / 245699 05HARPSTER P69.0 C1

  OPEN BRANCH FROM BUS 245699 TO BUS 245701 CKT 1                  / 245699 05HARPSTER P69.0 245701 05HARPSTER 69.0 1

END
31.0115.59 %0.38
247379 05NEVADA SS 69.0 - 245687 05BROK SWR 69.0 CKT 1 AEP_P4_#12471_05S TIFFIN 69.0_F_SRT-A
CONTINGENCY 'AEP_P4_#12471_05S TIFFIN 69.0_F_SRT-A'  

  OPEN BRANCH FROM BUS 243162 TO BUS 243180 CKT 1                  / 243162 05BERWICK 69.0 243180 05SBERWICK 69.0 1

  OPEN BRANCH FROM BUS 243162 TO BUS 245713 CKT 1                  / 243162 05BERWICK 69.0 245713 05SENECA SS 69.0 1

  OPEN BRANCH FROM BUS 243032 TO BUS 245630 CKT 1                  / 243032 05E.TIFFIN 69.0 245630 05S TIFFIN 69.0 1

  OPEN BRANCH FROM BUS 245628 TO BUS 245630 CKT 1                  / 245628 05RIVERVIE 69.0 245630 05S TIFFIN 69.0 1

  OPEN BRANCH FROM BUS 245630 TO BUS 245713 CKT 1                  / 245630 05S TIFFIN 69.0 245713 05SENECA SS 69.0 1

END
31.0112.0 %0.27
247379 05NEVADA SS 69.0 - 245687 05BROK SWR 69.0 CKT 1 AEP_P2-2_#14773_05N WALDO 69.0_1_SRT-A
CONTINGENCY 'AEP_P2-2_#14773_05N WALDO 69.0_1_SRT-A'                                                   /Waldo - La Rue line tapped by AD1-106 & AG2-595

  OPEN BRANCH FROM BUS 243048 TO BUS 245708 CKT 1                  / 243048 05N WALD 138 245708 05N WALDO 69.0 1

  OPEN BRANCH FROM BUS 245708 TO BUS 245716 CKT 1                  / 245708 05N WALDO 69.0 245716 05WALDO 69.0 1

  OPEN BRANCH FROM BUS 243048 TO BUS 270372 CKT 1                  / 243048 05N WALD 138 270372 AD1-106 TAP 138 1

  OPEN BRANCH FROM BUS 243048 TO BUS 243148 CKT 1                  / 243048 05N WALD 138 243148 05WINDFL 138 1

  OPEN BRANCH FROM BUS 243011 TO BUS 243148 CKT 1                  / 243011 05FULTON 138 243148 05WINDFL 138 1

  OPEN BRANCH FROM BUS 242963 TO BUS 243011 CKT 1                  / 242963 05HEDDSS 138 243011 05FULTON 138 1

  OPEN BRANCH FROM BUS 242963 TO BUS 245540 CKT 1                  / 242963 05HEDDSS 138 245540 05BLOOMFLD8 138 1

  OPEN BRANCH FROM BUS 242963 TO BUS 243153 CKT 1                  / 242963 05HEDDSS 138 243153 05WMTVER 138 1

  REMOVE LOAD D2 FROM BUS 245708                                   / 245708 05N WALDO 69.0 D2

END
31.0110.49 %0.38
247379 05NEVADA SS 69.0 - 245687 05BROK SWR 69.0 CKT 1 AEP_P4_#12469_05S TIFFIN 69.0_E_SRT-A
CONTINGENCY 'AEP_P4_#12469_05S TIFFIN 69.0_E_SRT-A'  

  OPEN BRANCH FROM BUS 243110 TO BUS 245630 CKT 1                  / 243110 05STIFFI 138 245630 05S TIFFIN 69.0 1

  OPEN BRANCH FROM BUS 243032 TO BUS 245630 CKT 1                  / 243032 05E.TIFFIN 69.0 245630 05S TIFFIN 69.0 1

  OPEN BRANCH FROM BUS 245628 TO BUS 245630 CKT 1                  / 245628 05RIVERVIE 69.0 245630 05S TIFFIN 69.0 1

  OPEN BRANCH FROM BUS 245630 TO BUS 245713 CKT 1                  / 245630 05S TIFFIN 69.0 245713 05SENECA SS 69.0 1

END
31.0110.23 %0.27
247379 05NEVADA SS 69.0 - 245687 05BROK SWR 69.0 CKT 1 AEP_P2-2_#12469_05S TIFFIN 69.0_1_SRT-A
CONTINGENCY 'AEP_P2-2_#12469_05S TIFFIN 69.0_1_SRT-A'  

  OPEN BRANCH FROM BUS 243110 TO BUS 245630 CKT 1                  / 243110 05STIFFI 138 245630 05S TIFFIN 69.0 1

  OPEN BRANCH FROM BUS 243032 TO BUS 245630 CKT 1                  / 243032 05E.TIFFIN 69.0 245630 05S TIFFIN 69.0 1

  OPEN BRANCH FROM BUS 245628 TO BUS 245630 CKT 1                  / 245628 05RIVERVIE 69.0 245630 05S TIFFIN 69.0 1

  OPEN BRANCH FROM BUS 245630 TO BUS 245713 CKT 1                  / 245630 05S TIFFIN 69.0 245713 05SENECA SS 69.0 1

END
31.0110.23 %0.27
247379 05NEVADA SS 69.0 - 245687 05BROK SWR 69.0 CKT 1 AEP_P4_#12472_05S TIFFIN 69.0_G_SRT-A
CONTINGENCY 'AEP_P4_#12472_05S TIFFIN 69.0_G_SRT-A'  

  OPEN BRANCH FROM BUS 243110 TO BUS 245630 CKT 1                  / 243110 05STIFFI 138 245630 05S TIFFIN 69.0 1

  OPEN BRANCH FROM BUS 245628 TO BUS 245630 CKT 1                  / 245628 05RIVERVIE 69.0 245630 05S TIFFIN 69.0 1

  OPEN BRANCH FROM BUS 245630 TO BUS 245713 CKT 1                  / 245630 05S TIFFIN 69.0 245713 05SENECA SS 69.0 1

  OPEN BRANCH FROM BUS 243032 TO BUS 245630 CKT 1                  / 243032 05E.TIFFIN 69.0 245630 05S TIFFIN 69.0 1

  OPEN BRANCH FROM BUS 243032 TO BUS 290149 CKT 1                  / 243032 05E.TIFFIN 69.0 290149 05MOUSEY SS 69.0 1

END
31.0108.0 %0.27
Transmission Owner Identified System Reinforcements
AH1-075 Transmission Owner Identified System Reinforcements Cost Breakdown:
TORTEP ID / TO IDCategoryTitleMW ImpactPercent AllocationAllocated Cost ($USD)
AEP(Pending) / TC2-AEP-154SubRegionalSouth Kenton - Kenton: ~2.83 miles of 69kV single circuit needs rebuilt (existing 1-105.6 COPPER 7 CU 1/0 75/75 °C)1.1 MW4.9%$652,146
Grand Total:$652,146

System Reinforcement
TO
AEP
RTEP ID / TO ID
(Pending) / TC2-AEP-190
Category
SubRegional
Title
Nevada - Sands: ~11.2 miles of 69kV single circuit needs rebuilt.
Description
Nevada - Sands: ~11.2 miles of 69kV single circuit needs rebuilt. Existing conductor 1-4/0 COPPER 19 75/75 °C
Total Cost
$35,840,000
Note: Based on PJM cost allocation criteria, AH1-075 currently does not receive cost allocation towards this upgrade. As changes to the PJM queue process occur (such as prior queued projects withdrawing from the queue, reducing in size, etc.) AH1-075 could receive cost allocation. Although Queue Project AH1-075 may not presently have cost responsibility for this upgrade, Queue Project AH1-075 may need this upgrade in-service to be deliverable to the PJM system. If Queue Project AH1-075 comes into service prior to completion of the upgrade, Queue Project AH1-075 will need an interim study.

System Reinforcement
TO
AEP
RTEP ID / TO ID
(Pending) / TC2-AEP-156
Category
SubRegional
Title
Fontain - Kenton: ~2.41 miles of 69kV single circuit needs to be rebuilt. At Kenton station; replace relay trip limit
Description
Fontain - Kenton: ~2.41 miles of 69kV single circuit needs to be rebuilt. At Kenton station; replace relay trip limit
Total Cost
$9,200,000
Note: Based on PJM cost allocation criteria, AH1-075 currently does not receive cost allocation towards this upgrade. As changes to the PJM queue process occur (such as prior queued projects withdrawing from the queue, reducing in size, etc.) AH1-075 could receive cost allocation. Although Queue Project AH1-075 may not presently have cost responsibility for this upgrade, Queue Project AH1-075 may need this upgrade in-service to be deliverable to the PJM system. If Queue Project AH1-075 comes into service prior to completion of the upgrade, Queue Project AH1-075 will need an interim study.

System Reinforcement
TO
AEP
RTEP ID / TO ID
(Pending) / TC2-AEP-154
Category
SubRegional
Title
South Kenton - Kenton: ~2.83 miles of 69kV single circuit needs rebuilt (existing 1-105.6 COPPER 7 CU 1/0 75/75 °C)
Description
South Kenton - Kenton: ~2.83 miles of 69kV single circuit needs rebuilt (existing 1-105.6 COPPER 7 CU 1/0 75/75 °C)
Total Cost
$13,192,500
Contributor
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AH1-53921.0 MW95.1%$12,540,354
AH1-0751.1 MW4.9%$652,146

System Reinforcement
TO
AEP
RTEP ID / TO ID
(Pending) / TC2-AEP-160
Category
SubRegional
Title
South Kenton - Fontain: ~2.369 miles of 69kV single circuit needs rebuilt. At Fontain station; replace 600A disconnects
Description
South Kenton - Fontain: ~2.369 miles of 69kV single circuit needs rebuilt. At Fontain station; replace 600A disconnects
Total Cost
$8,500,000
Note: Based on PJM cost allocation criteria, AH1-075 currently does not receive cost allocation towards this upgrade. As changes to the PJM queue process occur (such as prior queued projects withdrawing from the queue, reducing in size, etc.) AH1-075 could receive cost allocation. Although Queue Project AH1-075 may not presently have cost responsibility for this upgrade, Queue Project AH1-075 may need this upgrade in-service to be deliverable to the PJM system. If Queue Project AH1-075 comes into service prior to completion of the upgrade, Queue Project AH1-075 will need an interim study.

System Reinforcement
TO
AEP
RTEP ID / TO ID
(Pending) / TC2-AEP-193
Category
SubRegional
Title
Nevada - Brok: ~3 miles of 69kV single circuit needs rebuilt.
Description
Nevada - Brok: ~3 miles of 69kV single circuit needs rebuilt.
Total Cost
$9,600,000
Note: Based on PJM cost allocation criteria, AH1-075 currently does not receive cost allocation towards this upgrade. As changes to the PJM queue process occur (such as prior queued projects withdrawing from the queue, reducing in size, etc.) AH1-075 could receive cost allocation. Although Queue Project AH1-075 may not presently have cost responsibility for this upgrade, Queue Project AH1-075 may need this upgrade in-service to be deliverable to the PJM system. If Queue Project AH1-075 comes into service prior to completion of the upgrade, Queue Project AH1-075 will need an interim study.

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. AEP interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Meteorological Data Reporting Requirement
The solar generation facility shall provide the Transmission Provider with site-specific meteorological data including:
  • Temperature (degrees Fahrenheit)
  • Atmospheric Pressure (hectopascals)
  • Irradiance
  • Forced outage data
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AH1-075 was evaluated as a 8.0 MW (24.7 MW Capacity) injection in the AEP area.

AH1-075 was evaluated as part of a plant. The plant consists of AH1-075. The total Energy output of the plant was evaluated at its maximum seasonal capability of 68.0 MW (8.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P2-3_MP-500-024_SRT-A
BreakerAC132.75 %3729.0B4950.270.86
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P2-3_MP-500-025_SRT-A
BreakerAC131.94 %3729.0B4919.930.86
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P2-3_MP-500-015_SRT-A
BreakerAC131.63 %3729.0B4908.470.86
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P2-3_MP-500-014_SRT-A
BreakerAC131.63 %3729.0B4908.470.86
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P1-2_MP-500-007A_SRT-A
SingleAC130.62 %3729.0B4870.980.86
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P2-3_MP-500-012_SRT-A
BreakerAC130.23 %3729.0B4856.260.91
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P1-2_MP-500-008A_SRT-SL
SingleAC124.1 %3729.0B4627.60.83
GD2ATSI
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line
ATSI_P1-2_TE-345-602_SRT-A
SingleAC142.52 %1683.0B2398.590.38
GD2ATSI
02BEAVER-02CARLIL 345.0 kV Ckt 1 line
ATSI_P7-1_OEC-345-002_SRT-A
TowerAC109.31 %1745.0B1907.450.4
GD2ATSI
02BEAVER-02LAKEAVE 345.0 kV Ckt 1 line
ATSI_P2-3_OEC-345-901_SRT-SL
BreakerAC113.76 %1720.0B1956.70.36
GD2ATSI
02BEAVER-02LAKEAVE 345.0 kV Ckt 1 line
ATSI_P2-3_OEC-345-007A_SRT-SL
BreakerAC104.78 %1878.0B1967.820.35
GD2ATSI
02BEAVER-02LAKEAVE 345.0 kV Ckt 1 line
ATSI_P2-3_OEC-345-031_SRT-A
BreakerAC100.84 %1878.0B1893.720.36
GD2ATSI
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line
ATSI_P2-3_OEC-345-002_SRT-A
BreakerAC174.17 %1878.0B3270.930.51
GD2ATSI
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line
ATSI_P2-3_OEC-345-003_SRT-SL
BreakerAC104.76 %1878.0B1967.480.36
GD2ATSI
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line
ATSI_P2-3_OEC-345-028_SRT-A
BreakerAC101.37 %1878.0B1903.650.37
GD2ATSI
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line
ATSI_P2-3_OEC-345-1152-3_SRT-A
BreakerAC151.55 %1646.0B2494.570.37
GD2ATSI
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line
ATSI_P1-2_OEC-345-809_SRT-A
SingleAC128.94 %1646.0B2122.340.37
GD2ATSI
02HAYES-02BEAVER 345.0 kV Ckt 1 line
ATSI_P2-3_OEC-345-005_SRT-A
BreakerAC146.75 %1878.0B2755.890.42
GD2ATSI
02HAYES-02BEAVER 345.0 kV Ckt 1 line
ATSI_P2-3_OEC-345-006_SRT-SL
BreakerAC144.08 %1878.0B2705.740.44
GD2ATSI
02HAYES-02BEAVER 345.0 kV Ckt 1 line
ATSI_P2-3_TE-345-010A_SRT-SL
BreakerAC142.21 %1878.0B2670.760.43
GD2ATSI
02HAYES-02BEAVER 345.0 kV Ckt 1 line
ATSI_P1-2_OEC-345-825_SRT-A
SingleAC136.05 %1878.0B2554.950.43
GD2ATSI
02HAYES-02BEAVER 345.0 kV Ckt 1 line
ATSI_P1-2_OEC-345-824_SRT-A
SingleAC135.68 %1878.0B2548.090.43
GD2ATSI
02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line
ATSI_P1-2_TE-345-601_SRT-A
SingleAC113.99 %1878.0B2140.730.41
GD2AEP
05BOKESCRK-05MARYSV 345.0 kV Ckt 1 line
AEP_P4_#7445_05MARYSV 765_B_SRT-A
BreakerAC117.99 %1302.0B1536.230.35
GD2AEP
05BOKESCRK-05MARYSV 345.0 kV Ckt 1 line
AEP_P4_#7441_05SORENS 765_J1_SRT-A
BreakerAC110.86 %1302.0B1443.450.4
GD2AEP
05E LIMA-05SW LIM 345.0 kV Ckt 1 line
AEP_P4_#6497_05MARYSV 345_J2_SRT-A
BreakerAC112.9 %971.0B1096.250.41
GD2AEP
05E LIMA-05SW LIM 345.0 kV Ckt 1 line
AEP_P4_#17564_05BOKESCRK 345_CB2_SRT-A
BreakerAC105.18 %971.0B1021.280.42
GD2AEP
05E LIMA-05SW LIM 345.0 kV Ckt 1 line
AEP_P4_#16659_05GUNN RD SW 345_M2_SRT-A
BreakerAC104.18 %971.0B1011.610.42
GD2AEP
05E LIMA-05SW LIM 345.0 kV Ckt 1 line
AEP_P2-2_#16655_05GUNN RD SW 345_2_SRT-A
BusAC104.17 %971.0B1011.540.42
GD2AEP
05GUNN RD SW-05BOKESCRK 345.0 kV Ckt 1 line
AEP_P4_#7445_05MARYSV 765_B_SRT-A
BreakerAC101.83 %1301.0B1324.810.36
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P2-3_MP-500-024_SRT-A
BreakerAC134.01 %3792.0B5081.520.86
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P2-3_MP-500-025_SRT-A
BreakerAC133.21 %3792.0B5051.20.86
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P2-3_MP-500-015_SRT-A
BreakerAC132.9 %3792.0B5039.690.86
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P2-3_MP-500-014_SRT-A
BreakerAC132.9 %3792.0B5039.690.86
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P1-2_MP-500-007A_SRT-A
SingleAC131.92 %3792.0B5002.280.86
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P2-3_MP-500-012_SRT-A
BreakerAC131.49 %3792.0B4985.980.91
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P1-2_MP-500-008A_SRT-SL
SingleAC125.38 %3792.0B4754.330.83
GD2AEP
05W.NEWTONSS-05E LIMA 138.0 kV Ckt 1 line
AEP_P4_#13372_05N WALDO 69.0_A_SRT-A
BreakerAC114.71 %183.0B209.925.09
GD2AEP
05W.NEWTONSS-05E LIMA 138.0 kV Ckt 1 line
AEP_P2-2_#14773_05N WALDO 69.0_1_SRT-A
BusAC114.01 %183.0B208.645.09
GD2AEP
05W.NEWTONSS-05E LIMA 138.0 kV Ckt 1 line
AEP_P4_#10732_05WMTVER 138_A_SRT-A
BreakerAC113.59 %183.0B207.885.09
GD2AEP
05W.NEWTONSS-05E LIMA 138.0 kV Ckt 1 line
AEP_P4_#5710_05WMTVER 138_B_SRT-A
BreakerAC100.86 %183.0B184.574.39
GD2AEP
05W.NEWTONSS-05E LIMA 138.0 kV Ckt 1 line
AEP_P2-2_#5710_05WMTVER 138_1_SRT-A
BusAC100.85 %183.0B184.564.39
GD2ATSI
AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line
ATSI_P2-3_OEC-345-009_SRT-SL
BreakerAC165.39 %1499.0B2479.150.38
GD2ATSI
AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line
ATSI_P2-3_OEC-345-1152-3_SRT-A
BreakerAC142.16 %1798.0B2556.010.37
GD2ATSI
AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line
ATSI_P1-2_OEC-345-809_SRT-A
SingleAC117.76 %1798.0B2117.360.37
GD2AEP
AE1-091_POI-05W.NEWTONSS 138.0 kV Ckt 1 line
AEP_P4_#13372_05N WALDO 69.0_A_SRT-A
BreakerAC116.39 %183.0B213.05.09
GD2AEP
AE1-091_POI-05W.NEWTONSS 138.0 kV Ckt 1 line
AEP_P2-2_#14773_05N WALDO 69.0_1_SRT-A
BusAC115.71 %183.0B211.755.09
GD2AEP
AE1-091_POI-05W.NEWTONSS 138.0 kV Ckt 1 line
AEP_P4_#10732_05WMTVER 138_A_SRT-A
BreakerAC115.3 %183.0B211.015.09
GD2AEP
AE1-091_POI-05W.NEWTONSS 138.0 kV Ckt 1 line
AEP_P4_#5710_05WMTVER 138_B_SRT-A
BreakerAC102.61 %183.0B187.784.39
GD2AEP
AE1-091_POI-05W.NEWTONSS 138.0 kV Ckt 1 line
AEP_P2-2_#5710_05WMTVER 138_1_SRT-A
BusAC102.61 %183.0B187.774.39

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-024_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-024_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:132.75 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4950.27
MW Contribution:0.86
Bus #Bus NameTypeMW Contribution
270119AB2-067 GEN1
50/50
7.1
270120AB2-067 GEN2
50/50
7.1
24318905MLG2
50/50
7.059
270471AD2-092_GEN
Solar/Wind Harmer
4.477
946101AF1-275 GEN
Solar/Wind Harmer
1.818
942861AE2-305 GEN
Solar/Wind Harmer
9.105
970077AG2-063 GEN
Solar/Wind Harmer
6.25
270224U2-072_GEN2
Solar/Wind Harmer
2.287
270227U2-072_GEN3
Solar/Wind Harmer
2.287
270228U2-072_GEN4
Solar/Wind Harmer
2.287
270231U2-072_GEN5
Solar/Wind Harmer
2.287
938701AE1-092 GEN
Solar/Wind Harmer
23.86
964601AG1-323 GEN
Solar/Wind Harmer
3.665
964601AG1-323 GEN
Solar/Wind Harmer
1.705
270518AE2-148 GEN
Solar/Wind Harmer
13.911
253378AE2-206_GEN
Solar/Wind Harmer
4.016
276820AF1-078_GEN
Solar/Wind Harmer
1.784
972159AH1-661 GEN
Adder
1.111
972269AH1-719 GEN
Adder
2.557
25326509SID D
Adder
1.455
971199AH1-059 GEN
Solar/Wind Harmer
4.424
241960AC2-195 GEN
Solar/Wind Harmer
3.074
970879AG2-548 GEN
Solar/Wind Harmer
6.788
971073AG2-665 GEN
Solar/Wind Harmer
6.788
971073AG2-665 GEN
Solar/Wind Harmer
4.736
25326109MON D
Adder
1.447
25322209TAIT E
Adder
10.679
25322209TAIT E
Adder
10.439
253370AE2-315 SEC1
Adder
2.189
971201AH1-060 GEN
Solar/Wind Harmer
2.181
253394AE2-221_GEN
Solar/Wind Harmer
4.93
253398AE2-221_GEN2
Solar/Wind Harmer
4.93
246938BC-WTG3
Solar/Wind Harmer
4.31
246937BC-WTG2
Solar/Wind Harmer
4.237
253317AC1-085 GEN4
Solar/Wind Harmer
9.037
970611AG2-400 GEN
Solar/Wind Harmer
10.775
971231AH1-075 GEN
Solar/Wind Harmer
0.862
270007AE1-245 C
Solar/Wind Harmer
6.374
942801AE2-298 GEN
Solar/Wind Harmer
1.626
962581AG1-107 GEN
Solar/Wind Harmer
5.38
961491AF2-440 GEN
Solar/Wind Harmer
2.236
25183208HLCRTG
Solar/Wind Harmer
6.467
944541AF1-119 GEN
Solar/Wind Harmer
4.468
960971AF2-388 GEN
Solar/Wind Harmer
11.659
942221AE2-234 GEN
Solar/Wind Harmer
0.781
252519AF1-045_GEN
Solar/Wind Harmer
6.466
252516AE2-318_GEN
Solar/Wind Harmer
4.932
247621Y3-024
Adder
0.256
970883AG2-550 GEN
Solar/Wind Harmer
10.634
970885AG2-551 GEN
Solar/Wind Harmer
2.473
270201AC2-176 GEN
Solar/Wind Harmer
5.466
25194408D.CRK1
Adder
8.037
25194508D.CRK3
Adder
1.502
964611AG1-324 GEN
Solar/Wind Harmer
1.252
964611AG1-324 GEN
Solar/Wind Harmer
0.556
252509AD1-136 GEN
Solar/Wind Harmer
0.272
247620Y3-023
Adder
0.486
24728805RICHG1
Adder
3.981
24728905RICHG2
Adder
3.981
274770LINCOLN ;1U
Adder
8.715
274771LINCOLN ;2U
Adder
8.715
274808UNIV PK N;4U
Adder
5.14
274803UNIV PARK;6U
Adder
5.997
972259AH1-714 GEN
Adder
19.596
274674JOLIET 9 ;6U
Adder
15.776
274696ROCKY RD ;4P
Adder
11.59
274695ROCKY RD ;2P
Adder
11.323
274693ROCKY RD ;1P
Adder
11.211
274697ROCKY RD ;3P
Adder
3.076
23585401KL_K28_T16
Solar/Wind Helper
1.493
238120AE2-309 GEN
Solar/Wind Helper
0.528
238175AF1-290_GEN
Solar/Wind Helper
0.153
238169AE2-226 GEN1
Solar/Wind Helper
0.703
238170AE2-226 GEN2
Solar/Wind Helper
0.703
235020AA1-095 C
Solar/Wind Helper
0.053
23777901MDS_W4-102
Solar/Wind Helper
0.177
237002AB1-128_GEN
Solar/Wind Helper
0.445
237034AC2-136 C
Solar/Wind Helper
0.228
235063AE1-101 C2
Solar/Wind Helper
1.665
237001AB1-127_GEN
Solar/Wind Helper
0.443
23777801MSM_W1-116
Solar/Wind Helper
0.115
237025AB1-124 C
Solar/Wind Helper
0.165
237006AB1-125 GEN
Solar/Wind Helper
0.123
226929AD2-058 GEN
Solar/Wind Helper
0.099
205916AD1-020 GEN
Solar/Wind Helper
1.72
962771AG1-126 GEN
Solar/Wind Harmer
41.173
270459AD2-067 GEN
Solar/Wind Harmer
10.252
961821AG1-024 GEN
Solar/Wind Harmer
10.408
270054AF2-122 C O1
Solar/Wind Harmer
3.995
972239AH1-704 GEN
Adder
2.671
270284AF1-227 GEN1
Solar/Wind Harmer
6.806
270286AF1-227 GEN2
Solar/Wind Harmer
2.518
270287AF1-227 GEN3
Solar/Wind Harmer
2.518
270520AE2-214 GEN
Solar/Wind Harmer
7.284
253383AE2-342_GEN
Solar/Wind Harmer
1.047
241973AD2-163_GEN1
Solar/Wind Harmer
2.334
943861AF1-054 GEN
Solar/Wind Harmer
4.494
943851AF1-053 GEN
Solar/Wind Harmer
2.172
945631AF1-228 GEN
Solar/Wind Harmer
5.47
270156DARBY CT1
Adder
10.432
270157DARBY CT2
Adder
10.407
270158DARBY CT3
Adder
10.24
270578AF1-285 GEN2
Solar/Wind Harmer
0.538
970689AG2-444 GEN
Solar/Wind Harmer
18.845
270432AC2-029 GEN
Solar/Wind Harmer
8.059
270302AB2-170 GEN
Solar/Wind Harmer
9.566
270317AD1-130_GEN
Solar/Wind Harmer
3.667
270269AC2-059
Solar/Wind Harmer
10.62
940611AE2-048 GEN
Solar/Wind Harmer
24.866
941391AE2-136 GEN
Solar/Wind Harmer
12.885
241972AD1-140 GEN
Solar/Wind Harmer
5.031
270340AC2-060 GEN
Solar/Wind Harmer
3.353
958581AF2-149 GEN
Solar/Wind Harmer
4.732
970179AG2-119 GEN
Solar/Wind Harmer
8.844
970879AG2-548 GEN
Solar/Wind Harmer
4.736
253372AE2-315 SEC3
Adder
2.071
253372AE2-315 SEC3
Adder
2.071
25306009OHH W.
Adder
3.141
253349AC2-067 GEN
Solar/Wind Harmer
5.421
253400AC2-068 GEN
Solar/Wind Harmer
2.18
957201AF2-014 GEN
Solar/Wind Harmer
4.91
270435AC2-044 GEN
Solar/Wind Harmer
2.165
965051AG1-369 GEN
Solar/Wind Harmer
5.38
965041AG1-368 GEN
Solar/Wind Harmer
10.749
247607V1-011 GEN
Solar/Wind Harmer
4.249
24318805MLG1
50/50
10.158
23559001PLEAS1
50/50
6.365
270051AF1-062 GEN
50/50
11.843
270475AD2-096_GEN
50/50
7.165
970153AG2-106 GEN
Solar/Wind Harmer
17.953
961921AG1-034 GEN
Solar/Wind Harmer
15.612
24721905FLATG4
Adder
24.144
241955AC1-078 GEN
Solar/Wind Harmer
8.824
241974AD2-163_GEN2
Solar/Wind Harmer
2.334
942051AE2-217 GEN
Solar/Wind Harmer
21.08
960801AF2-371 GEN
Solar/Wind Harmer
2.95
964871AG1-351 GEN
Solar/Wind Harmer
2.037
970605AG2-385 GEN
Solar/Wind Harmer
6.25
942871AE2-306 GEN
Solar/Wind Harmer
1.049
270391AF1-285 GEN3
Solar/Wind Harmer
0.538
253338AC1-165 GEN
Solar/Wind Harmer
1.243
253333AC1-068 GEN
Solar/Wind Harmer
1.199
270485AE1-090_GEN
Solar/Wind Harmer
0.692
270273AD2-016 GEN
Solar/Wind Harmer
3.037
972173AH1-669 GEN
Solar/Wind Harmer
5.679
253415AE1-040 GEN
Solar/Wind Harmer
1.251
270291AC1-194 GEN
Solar/Wind Harmer
11.751
253303V4-073 C
Solar/Wind Harmer
0.127
253370AE2-315 SEC1
Adder
2.189
253371AE2-315 SEC2
Adder
2.071
957541AF2-048 GEN
Solar/Wind Harmer
1.724
970065AG2-057 GEN
Solar/Wind Harmer
1.09
253406AD2-031_GEN
Solar/Wind Harmer
1.391
270491AE1-102 GEN2
Solar/Wind Harmer
1.407
971191AH1-055 GEN
Solar/Wind Harmer
23.759
253316AC1-085 GEN3
Solar/Wind Harmer
9.037
253433AC1-085 GEN1
Solar/Wind Harmer
5.737
946181AF1-283 GEN
Solar/Wind Harmer
14.025
270191TR4_S_V150
Solar/Wind Harmer
3.232
270247TR4_N_V136
Solar/Wind Harmer
0.916
959331AF2-224 GEN
Solar/Wind Harmer
10.775
965021AG1-366 GEN
Solar/Wind Harmer
2.506
270377AD1-106 GEN
Solar/Wind Harmer
6.65
958091AF2-103 GEN
Solar/Wind Harmer
0.174
270588AE1-091_GEN
Solar/Wind Harmer
11.804
944531AF1-118 GEN
Solar/Wind Harmer
37.541
270043AE2-236 GEN
Solar/Wind Harmer
5.893
971617AH1-308 GEN
Solar/Wind Harmer
6.198
270258AD1-119 GEN
Solar/Wind Harmer
2.97
25196608WSDLE5
Adder
9.114
962031AG1-047 GEN
Solar/Wind Harmer
3.214
957741AF2-068 GEN
Solar/Wind Harmer
15.949
252510AF1-249 C
Solar/Wind Harmer
0.444
25194608D.CRK4
Adder
1.747
270222AC2-111 GEN
Solar/Wind Harmer
8.657
970031AG2-029 GEN
Solar/Wind Harmer
31.849
270044AE2-322 C
Solar/Wind Harmer
1.394
270404AC1-167 GEN
Solar/Wind Harmer
1.161
24642205MAYFLWER
Adder
0.667
25196008MFTGT1
Adder
1.411
247604X1-042
Adder
0.435
274752CRETE EC ;2U
Adder
8.515
274753CRETE EC ;3U
Adder
8.515
274772LINCOLN ;3U
Adder
8.715
274724RIVER EC ;11
Adder
18.285
274802UNIV PARK;5U
Adder
5.997
24728705AND G3
Adder
8.251
24728505AND G1
Adder
3.945
274826FISK ;BP
Adder
11.256
274800UNIV PARK;3U
Adder
5.993
972038AH1-567 GEN2
Adder
0.375
972228AH1-698 GEN2
Adder
3.807
274676JOLIET 29;8U
Adder
30.322
274729ELWOOD EC;1P
Adder
16.844
274730ELWOOD EC;6P
Adder
16.844
274734ELWOOD EC;8P
Adder
16.844
274736ELWOOD EC;9P
Adder
16.844
274682WAUKEGAN ;7U
Adder
9.773
964991AG1-363 GEN
Solar/Wind Helper
5.152
316097T157 G90
Solar/Wind Helper
1.508
23750701CROSSCHOOL
Solar/Wind Helper
1.51
238118U2-030_1
Solar/Wind Helper
0.344
238127S14_GEN_2
Solar/Wind Helper
0.832
238148AE2-230_GEN2
Solar/Wind Helper
0.498
237080AD1-060 GEN
Solar/Wind Helper
0.343
270166AC1-044 GEN3
50/50
7.1
23559101PLEAS2
50/50
6.365
962761AG1-125 GEN
Solar/Wind Harmer
41.173
970149AG2-104 GEN
Solar/Wind Harmer
50.849
970155AG2-107 GEN
Solar/Wind Harmer
17.953
270349AD2-093_GEN
Solar/Wind Harmer
4.477
24721705FLATG2
Adder
24.144
270159DARBY CT4
Adder
10.266
970593AG2-378 GEN
Solar/Wind Harmer
2.315
270223U2-072_GEN1
Solar/Wind Harmer
2.287
270578AF1-285 GEN2
Solar/Wind Harmer
1.399
270391AF1-285 GEN3
Solar/Wind Harmer
1.399
253343AC1-166 GEN
Solar/Wind Harmer
1.243
253325AC1-069 GEN
Solar/Wind Harmer
1.199
270462AD2-086
Solar/Wind Harmer
7.958
971995AH1-542 GEN
Solar/Wind Harmer
12.515
270263AC1-001 GEN
Solar/Wind Harmer
1.179
25326309TAIT D
Adder
1.2
960071AF2-298 GEN
Solar/Wind Harmer
5.454
253370AE2-315 SEC1
Adder
2.189
253371AE2-315 SEC2
Adder
2.071
927014AC1-188 GEN
Solar/Wind Harmer
1.729
241813AF1-122_GEN
Solar/Wind Harmer
6.978
246936BC-WTG1
Solar/Wind Harmer
4.237
270489AE1-102 GEN1
Solar/Wind Harmer
1.407
965421AG1-410 GEN
Solar/Wind Harmer
32.464
960001AF2-291 GEN
Solar/Wind Harmer
3.264
253432AC1-085 GEN2
Solar/Wind Harmer
0.289
946171AF1-282 GEN
Solar/Wind Harmer
10.789
247521TR3_G114
Solar/Wind Harmer
3.623
270246TR4_N_V150
Solar/Wind Harmer
0.916
965011AG1-365 GEN
Solar/Wind Harmer
10.775
24695305TIMB G C
Solar/Wind Harmer
5.916
965651AG1-433 GEN
Solar/Wind Harmer
5.83
958861AF2-177 GEN
Solar/Wind Harmer
11.644
247536S-71 GEN
Solar/Wind Harmer
4.305
25194608D.CRK4
Adder
1.747
945371AF1-202 GEN
Solar/Wind Harmer
7.414
252507AC2-088 GEN
Solar/Wind Harmer
1.904
270063AE2-323 C
Solar/Wind Harmer
2.336
25196808ZIMRHP
Adder
80.055
24639705ELKHART HY
Adder
0.162
25196008MFTGT1
Adder
1.456
274751CRETE EC ;1U
Adder
8.515
274754CRETE EC ;4U
Adder
8.515
274773LINCOLN ;4U
Adder
8.715
274774LINCOLN ;5U
Adder
8.715
274723RIVER EC ;12
Adder
18.501
274812UNIV PK N;8U
Adder
5.162
24728605AND G2
Adder
3.945
274801UNIV PARK;4U
Adder
5.993
274676JOLIET 29;8U
Adder
31.445
274732ELWOOD EC;7P
Adder
16.844
274674JOLIET 9 ;6U
Adder
15.776
274745AC1-111 GEN9
Adder
5.705
970091AG2-072 GEN
Adder
78.03
316095T157 G97
Solar/Wind Helper
1.508
23583801GRNGAP
Solar/Wind Helper
5.618
238185AF2-356 C
Solar/Wind Helper
2.662
238108AE1-109 GEN1
Solar/Wind Helper
0.114
235054AD2-180 GEN
Solar/Wind Helper
2.043
235531U2-073 GEN
Solar/Wind Helper
3.301
238117U2-030
Solar/Wind Helper
0.344
238147AE2-230_GEN1
Solar/Wind Helper
0.496
238149AF1-291A_GEN
Solar/Wind Helper
0.142
23751201ROTHROCK
Solar/Wind Helper
0.832
23562501BACKB
Solar/Wind Helper
1.017
237061AD1-155 GEN
Solar/Wind Helper
0.053
238221AF1-254 C O1
Solar/Wind Helper
0.275
235067AD1-061 GEN
Solar/Wind Helper
0.498
23751101LEADS_P59
Solar/Wind Helper
1.424
237030AB1-096 C
Solar/Wind Helper
0.071
3141196NOKESVL
Solar/Wind Helper
1.034
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.347
223402AF1-300 C
Solar/Wind Helper
0.369
205917AD1-020 ES
Solar/Wind Helper
0.37
233918AB1-142 GEN
Solar/Wind Helper
0.504
233982AB2-133 GEN
Solar/Wind Helper
0.359
233994AC2-023 GEN
Solar/Wind Helper
0.965
233996TM1833_GEN
Solar/Wind Helper
0.262
233997TMININ_4.2
Solar/Wind Helper
0.262
232406W1-004 FULL
Solar/Wind Helper
0.509
233940AF2-379 C
Solar/Wind Helper
0.062
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.233
233971AC1-093 C
Solar/Wind Helper
0.359
230430AE1-229_GEN
Solar/Wind Helper
3.385
316044AC1-158 PL1
Solar/Wind Helper
1.296
316450AC1-158 RIC
Solar/Wind Helper
0.346
230415AB2-049 C
Solar/Wind Helper
0.03
228729W2-030 C
Solar/Wind Helper
0.111
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.15
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
219348LDSOLAR C
Solar/Wind Helper
0.115
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.063
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.354
219276PARKLANDSO C
Solar/Wind Helper
0.09
20714528FRN_Y2-051
Solar/Wind Helper
0.057
20720528MAN_W1-024
Solar/Wind Helper
0.028
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.027
219249CENTRALDIV C
Solar/Wind Helper
0.01
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.089
963161AG1-165 GEN
Solar/Wind Helper
0.441
970245AG2-165 GEN
Solar/Wind Harmer
4.981
20390526W1-045 C
Solar/Wind Helper
0.351
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
233987AB2-037 GEN
Solar/Wind Helper
2.35
233933AB2-153 GEN
Solar/Wind Helper
0.233
232424Y1-079 C
Solar/Wind Helper
0.117
233944AB2-135 GEN
Solar/Wind Helper
0.591
233946AB2-136 GEN
Solar/Wind Helper
0.57
234036AF2-325 C
Solar/Wind Helper
0.042
233901CHERRYDALE C
Solar/Wind Helper
0.233
232408W1-005 C
Solar/Wind Helper
0.509
232410W1-006 C
Solar/Wind Helper
0.509
233939AC1-091 C
Solar/Wind Helper
0.351
233970AC1-092 C
Solar/Wind Helper
0.351
315651AD1-115 GEN
Solar/Wind Helper
0.787
316447AC1-158 HLD
Solar/Wind Helper
2.853
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.04
219921AF1-264
Solar/Wind Helper
0.051
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.083
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.19
20716928W4-060COL
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.016
20673828FLE_V3-070
Solar/Wind Helper
0.091
207442AE1-156 GEN
Solar/Wind Helper
0.327
20676128MHD_W3-029
Solar/Wind Helper
0.096
20671828STAW2-080
Solar/Wind Helper
0.027
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
207471AF2-354 C
Solar/Wind Helper
0.169
20674928WA_W3-044
Solar/Wind Helper
0.099
964851AG1-348 GEN
Solar/Wind Helper
0.081
20676228FRD_X1-012
Solar/Wind Helper
0.092
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.045
211065PSPA IPP
Solar/Wind Helper
0.152
211065PSPA IPP
Solar/Wind Helper
0.152
203955AF1-039 C O1
Solar/Wind Helper
0.33
970321AG2-212 GEN
Solar/Wind Harmer
4.981
24729505KEY G4
Adder
6.948
963791AG1-232 GEN
Solar/Wind Harmer
14.455
971567AH1-282 GEN
Solar/Wind Harmer
16.053
966831AG1-554 GEN
Solar/Wind Harmer
1.28
971989AH1-539 GEN
Solar/Wind Harmer
13.846
270071AF1-092 GEN
Solar/Wind Harmer
16.048
971985AH1-537 GEN
Solar/Wind Harmer
19.051
958711AF2-162 GEN
Solar/Wind Harmer
1.079
270024AE2-089 GEN
Solar/Wind Harmer
5.004
965101AG1-375 GEN
Solar/Wind Harmer
10.653
270367AC2-061_GEN
Solar/Wind Harmer
3.388
971673AH1-337 GEN
Solar/Wind Harmer
4.893
971029AG2-637 GEN
Solar/Wind Harmer
15.954
252524AE2-267 GEN
Solar/Wind Harmer
1.677
25196408WSDLE3
Adder
9.382
25196308WSDLE2
Adder
9.3
25196208WSDLE1
Adder
9.277
25196708WSDLE6
Adder
9.254
25196508WSDLE4
Adder
9.021
270543AE2-219 C
Solar/Wind Harmer
5.445
961761AG1-017 GEN
Solar/Wind Harmer
0.455
945581AF1-223 GEN
Solar/Wind Harmer
4.819
944031AF1-071 GEN
Solar/Wind Harmer
1.067
270297AD1-101 GEN
Solar/Wind Harmer
2.953
25196108MFTGT2
Adder
1.605
25196108MFTGT2
Adder
1.491
274775LINCOLN ;6U
Adder
8.715
274776LINCOLN ;7U
Adder
8.715
274777LINCOLN ;8U
Adder
8.715
274814UNIV PK N;0U
Adder
5.208
274807UNIV PK N;3U
Adder
5.196
274805UNIV PK N;1U
Adder
5.174
274811UNIV PK N;7U
Adder
5.162
972037AH1-567 GEN1
Adder
0.188
274827FISK ;RP
Adder
7.977
972227AH1-698 GEN1
Adder
2.681
274687WILL CNTY;4U
Adder
28.653
274687WILL CNTY;4U
Adder
28.653
274675JOLIET 29;7U
Adder
31.445
274675JOLIET 29;7U
Adder
30.322
274731ELWOOD EC;2P
Adder
16.844
274733ELWOOD EC;3P
Adder
16.844
274735ELWOOD EC;4P
Adder
16.844
274728ELWOOD EC;5P
Adder
16.844
972203AH1-686 GEN
Adder
2.356
274746AC1-111 G10
Adder
5.705
274744AC1-111 GEN8
Adder
5.705
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238126S14_GEN_1
Solar/Wind Helper
0.832
238152AF2-075_GEN
Solar/Wind Helper
0.709
238208AF1-136 C
Solar/Wind Helper
0.221
23546401DTGZ2-030
Solar/Wind Helper
0.089
237085AD2-009_GEN
Solar/Wind Helper
1.655
3138216PACIFIC
Solar/Wind Helper
0.044
316411AF1-147_GEN1
Solar/Wind Helper
0.891
316415AF1-147_GEN2
Solar/Wind Helper
0.891
23750501ELLIOTTS
Solar/Wind Helper
0.644
959381AF2-229 GEN
Solar/Wind Helper
0.359
3141426STAFORD
Solar/Wind Helper
0.052
960921AF2-383 GEN
Solar/Wind Helper
0.182
205943AE1-185 GEN
Solar/Wind Helper
0.511
205932AD2-116_GEN
Solar/Wind Helper
0.511
205956AE1-196_GEN
Solar/Wind Helper
0.511
233935AB2-179 C
Solar/Wind Helper
1.273
232436AB1-176 C
Solar/Wind Helper
0.045
233923SMA
Solar/Wind Helper
0.962
233990AG1-397 GEN
Solar/Wind Helper
0.031
232432Z2-076 GEN
Solar/Wind Helper
0.067
234033AF1-007_GEN
Solar/Wind Helper
7.046
964001AG1-254 GEN
Solar/Wind Helper
0.959
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.115
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.08
203975AE1-071-GEN
Solar/Wind Helper
2.508
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.291
219620RIDERU C
Solar/Wind Helper
0.001
316164AC1-076 GEN
Solar/Wind Helper
1.099
20675528CPH_W2-050
Solar/Wind Helper
0.087
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
218524CNTRALGAS1 C
Solar/Wind Helper
0.161
966261AG1-495 GEN
Solar/Wind Helper
0.082
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20675928HOL_W4-097
Solar/Wind Helper
0.05
207484AF2-139 C O1
Solar/Wind Helper
0.084
20674828DL_W4-046
Solar/Wind Helper
0.008
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.137
20675128HRM_W1-127
Solar/Wind Helper
0.03
209116AE2-175 GEN
Solar/Wind Helper
1.786
237038AE2-054 C
Solar/Wind Helper
0.273
235062AE1-101 C1
Solar/Wind Helper
1.665
23779801AA1-109
Solar/Wind Helper
0.194
237048AF1-022 C
Solar/Wind Helper
0.179
223401AF1-299 GEN
Solar/Wind Helper
0.369
316006AB2-029 C
Solar/Wind Helper
0.117
966131AG1-482 GEN
Solar/Wind Helper
0.078
233930AB2-032 GEN
Solar/Wind Helper
0.382
233915AB1-141 GEN
Solar/Wind Helper
0.504
232422X3-066 FULL
Solar/Wind Helper
0.115
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
233998TM1NIN_3.36
Solar/Wind Helper
0.262
232404W1-003 C
Solar/Wind Helper
0.509
232428Y3-058 C
Solar/Wind Helper
0.339
232434Z2-077 GEN
Solar/Wind Helper
0.127
233954AC2-188 GEN
Solar/Wind Helper
0.233
233950AC2-186 GEN
Solar/Wind Helper
0.117
233972AC1-094 C
Solar/Wind Helper
0.303
230511AF1-262
Solar/Wind Helper
0.015
316045AC1-158 PL2
Solar/Wind Helper
4.149
230434AG1-499 GEN
Solar/Wind Helper
0.231
228728W1-130C
Solar/Wind Helper
0.054
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219904AC1-010 C
Solar/Wind Helper
0.061
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.132
20720728JCB_W1-129
Solar/Wind Helper
0.057
207445AB1-138_GEN
Solar/Wind Helper
0.105
316254AC1-120 GEN1
Solar/Wind Helper
1.062
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.311
20715228NPK_W1-113
Solar/Wind Helper
0.078
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.497
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.023
207439AE1-081 C O1
Solar/Wind Helper
0.019
207437AD2-070 GEN
Solar/Wind Helper
0.138
207518AF1-320_GEN
Solar/Wind Helper
1.577
20671928W4-073
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.03
202652Y1-033 WT C
Solar/Wind Helper
0.5
961301AF2-421 GEN
Solar/Wind Helper
0.441
963151AG1-164 GEN
Solar/Wind Helper
0.441
970513AG2-328 GEN
Solar/Wind Harmer
4.981
970517AG2-330 GEN
Solar/Wind Harmer
4.518
LAGNLTFEXP_LAGN->PJM
CLTF
14.924
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.891
TVALTFEXP_TVA->PJM
CLTF
7.337
CPLELTFEXP_CPLE->PJM
CLTF
0.647
CBM West 2LTFEXP_CBM-W2->PJM
CBM
113.418
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.671
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.268
MECLTFEXP_MEC->PJM
CLTF
15.978
SIGELTFEXP_SIGE->PJM
CLTF
0.507
NYPJM->LTFIMP_NY
CLTF
4.819
LGEELTFEXP_LGEE->PJM
CLTF
6.781
WECLTFEXP_WEC->PJM
CLTF
3.842
AG2-052LTFEXP_AG2-052->PJM
LTF
0.241
AH1-155LTFEXP_AH1-155->PJM
LTF
0.361

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-025_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-025_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:131.94 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4919.93
MW Contribution:0.86
Bus #Bus NameTypeMW Contribution
270166AC1-044 GEN3
50/50
7.072
23559101PLEAS2
50/50
6.183
962761AG1-125 GEN
Solar/Wind Harmer
41.012
970149AG2-104 GEN
Solar/Wind Harmer
50.65
970155AG2-107 GEN
Solar/Wind Harmer
17.883
270349AD2-093_GEN
Solar/Wind Harmer
4.467
24721705FLATG2
Adder
23.989
270159DARBY CT4
Adder
10.25
970593AG2-378 GEN
Solar/Wind Harmer
2.311
270223U2-072_GEN1
Solar/Wind Harmer
2.282
270578AF1-285 GEN2
Solar/Wind Harmer
1.396
270391AF1-285 GEN3
Solar/Wind Harmer
1.396
253343AC1-166 GEN
Solar/Wind Harmer
1.241
253325AC1-069 GEN
Solar/Wind Harmer
1.197
270462AD2-086
Solar/Wind Harmer
7.941
971995AH1-542 GEN
Solar/Wind Harmer
12.502
270263AC1-001 GEN
Solar/Wind Harmer
1.177
25326309TAIT D
Adder
1.197
960071AF2-298 GEN
Solar/Wind Harmer
5.441
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.066
241813AF1-122_GEN
Solar/Wind Harmer
6.974
927014AC1-188 GEN
Solar/Wind Harmer
1.725
270510AE1-227 GEN1
Solar/Wind Harmer
2.689
246936BC-WTG1
Solar/Wind Harmer
4.226
270489AE1-102 GEN1
Solar/Wind Harmer
1.404
965421AG1-410 GEN
Solar/Wind Harmer
32.386
960001AF2-291 GEN
Solar/Wind Harmer
3.255
253432AC1-085 GEN2
Solar/Wind Harmer
0.288
946171AF1-282 GEN
Solar/Wind Harmer
10.761
247521TR3_G114
Solar/Wind Harmer
3.613
270246TR4_N_V150
Solar/Wind Harmer
0.914
965011AG1-365 GEN
Solar/Wind Harmer
10.746
24695305TIMB G C
Solar/Wind Harmer
5.901
965651AG1-433 GEN
Solar/Wind Harmer
5.813
958861AF2-177 GEN
Solar/Wind Harmer
11.61
247536S-71 GEN
Solar/Wind Harmer
4.293
25194608D.CRK4
Adder
1.742
945371AF1-202 GEN
Solar/Wind Harmer
7.392
252507AC2-088 GEN
Solar/Wind Harmer
1.899
270063AE2-323 C
Solar/Wind Harmer
2.33
25196808ZIMRHP
Adder
79.831
24639705ELKHART HY
Adder
0.161
25196008MFTGT1
Adder
1.452
274751CRETE EC ;1U
Adder
8.489
274754CRETE EC ;4U
Adder
8.489
274773LINCOLN ;4U
Adder
8.688
274774LINCOLN ;5U
Adder
8.688
274723RIVER EC ;12
Adder
18.445
274812UNIV PK N;8U
Adder
5.147
24728605AND G2
Adder
3.933
274801UNIV PARK;4U
Adder
5.975
274676JOLIET 29;8U
Adder
31.348
274732ELWOOD EC;7P
Adder
16.792
274674JOLIET 9 ;6U
Adder
15.727
274745AC1-111 GEN9
Adder
5.687
970091AG2-072 GEN
Adder
77.755
316095T157 G97
Solar/Wind Helper
1.505
23583801GRNGAP
Solar/Wind Helper
5.606
238185AF2-356 C
Solar/Wind Helper
2.651
238108AE1-109 GEN1
Solar/Wind Helper
0.114
235054AD2-180 GEN
Solar/Wind Helper
2.034
235531U2-073 GEN
Solar/Wind Helper
3.288
238117U2-030
Solar/Wind Helper
0.342
238147AE2-230_GEN1
Solar/Wind Helper
0.495
238149AF1-291A_GEN
Solar/Wind Helper
0.141
23751201ROTHROCK
Solar/Wind Helper
0.826
23562501BACKB
Solar/Wind Helper
1.01
237061AD1-155 GEN
Solar/Wind Helper
0.053
238221AF1-254 C O1
Solar/Wind Helper
0.275
235067AD1-061 GEN
Solar/Wind Helper
0.496
23751101LEADS_P59
Solar/Wind Helper
1.41
237030AB1-096 C
Solar/Wind Helper
0.071
3141196NOKESVL
Solar/Wind Helper
1.032
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.346
223402AF1-300 C
Solar/Wind Helper
0.368
205917AD1-020 ES
Solar/Wind Helper
0.369
233982AB2-133 GEN
Solar/Wind Helper
0.358
233918AB1-142 GEN
Solar/Wind Helper
0.503
233994AC2-023 GEN
Solar/Wind Helper
0.962
233996TM1833_GEN
Solar/Wind Helper
0.262
233997TMININ_4.2
Solar/Wind Helper
0.262
232406W1-004 FULL
Solar/Wind Helper
0.508
233940AF2-379 C
Solar/Wind Helper
0.062
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.233
233971AC1-093 C
Solar/Wind Helper
0.358
316044AC1-158 PL1
Solar/Wind Helper
1.294
316450AC1-158 RIC
Solar/Wind Helper
0.345
230430AE1-229_GEN
Solar/Wind Helper
3.376
230415AB2-049 C
Solar/Wind Helper
0.03
228729W2-030 C
Solar/Wind Helper
0.111
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.15
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
219348LDSOLAR C
Solar/Wind Helper
0.115
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.063
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.353
219276PARKLANDSO C
Solar/Wind Helper
0.089
20714528FRN_Y2-051
Solar/Wind Helper
0.057
20720528MAN_W1-024
Solar/Wind Helper
0.028
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.027
219249CENTRALDIV C
Solar/Wind Helper
0.01
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.089
970245AG2-165 GEN
Solar/Wind Harmer
3.728
270119AB2-067 GEN1
50/50
7.072
270120AB2-067 GEN2
50/50
7.072
24318905MLG2
50/50
7.067
270471AD2-092_GEN
Solar/Wind Harmer
4.467
946101AF1-275 GEN
Solar/Wind Harmer
1.815
942861AE2-305 GEN
Solar/Wind Harmer
9.088
970077AG2-063 GEN
Solar/Wind Harmer
6.239
270224U2-072_GEN2
Solar/Wind Harmer
2.282
270227U2-072_GEN3
Solar/Wind Harmer
2.282
270228U2-072_GEN4
Solar/Wind Harmer
2.282
270231U2-072_GEN5
Solar/Wind Harmer
2.282
938701AE1-092 GEN
Solar/Wind Harmer
23.824
964601AG1-323 GEN
Solar/Wind Harmer
3.66
964601AG1-323 GEN
Solar/Wind Harmer
1.702
270518AE2-148 GEN
Solar/Wind Harmer
13.886
972269AH1-719 GEN
Adder
2.575
972159AH1-661 GEN
Adder
1.116
253378AE2-206_GEN
Solar/Wind Harmer
4.007
276820AF1-078_GEN
Solar/Wind Harmer
1.78
971199AH1-059 GEN
Solar/Wind Harmer
4.428
241960AC2-195 GEN
Solar/Wind Harmer
3.072
25326509SID D
Adder
1.452
970879AG2-548 GEN
Solar/Wind Harmer
6.777
971073AG2-665 GEN
Solar/Wind Harmer
6.777
971073AG2-665 GEN
Solar/Wind Harmer
4.728
25326109MON D
Adder
1.444
25322209TAIT E
Adder
10.654
25322209TAIT E
Adder
10.414
253370AE2-315 SEC1
Adder
2.184
971201AH1-060 GEN
Solar/Wind Harmer
2.179
253394AE2-221_GEN
Solar/Wind Harmer
4.918
253398AE2-221_GEN2
Solar/Wind Harmer
4.918
246938BC-WTG3
Solar/Wind Harmer
4.299
246937BC-WTG2
Solar/Wind Harmer
4.226
971231AH1-075 GEN
Solar/Wind Harmer
0.861
253317AC1-085 GEN4
Solar/Wind Harmer
9.014
970611AG2-400 GEN
Solar/Wind Harmer
10.746
270007AE1-245 C
Solar/Wind Harmer
6.359
942801AE2-298 GEN
Solar/Wind Harmer
1.622
962581AG1-107 GEN
Solar/Wind Harmer
5.366
961491AF2-440 GEN
Solar/Wind Harmer
2.23
25183208HLCRTG
Solar/Wind Harmer
6.45
944541AF1-119 GEN
Solar/Wind Harmer
4.455
960971AF2-388 GEN
Solar/Wind Harmer
11.625
942221AE2-234 GEN
Solar/Wind Harmer
0.779
252519AF1-045_GEN
Solar/Wind Harmer
6.448
252516AE2-318_GEN
Solar/Wind Harmer
4.919
247621Y3-024
Adder
0.256
970883AG2-550 GEN
Solar/Wind Harmer
10.605
970885AG2-551 GEN
Solar/Wind Harmer
2.466
270201AC2-176 GEN
Solar/Wind Harmer
5.45
25194408D.CRK1
Adder
8.014
25194508D.CRK3
Adder
1.498
964611AG1-324 GEN
Solar/Wind Harmer
1.249
964611AG1-324 GEN
Solar/Wind Harmer
0.554
252509AD1-136 GEN
Solar/Wind Harmer
0.271
247620Y3-023
Adder
0.484
24728805RICHG1
Adder
3.969
24728905RICHG2
Adder
3.969
274770LINCOLN ;1U
Adder
8.688
962771AG1-126 GEN
Solar/Wind Harmer
41.012
972239AH1-704 GEN
Adder
2.683
270459AD2-067 GEN
Solar/Wind Harmer
10.243
961821AG1-024 GEN
Solar/Wind Harmer
10.399
270054AF2-122 C O1
Solar/Wind Harmer
3.993
270520AE2-214 GEN
Solar/Wind Harmer
7.274
270284AF1-227 GEN1
Solar/Wind Harmer
6.791
270286AF1-227 GEN2
Solar/Wind Harmer
2.512
270287AF1-227 GEN3
Solar/Wind Harmer
2.512
253383AE2-342_GEN
Solar/Wind Harmer
1.045
24318805MLG1
50/50
10.115
23559001PLEAS1
50/50
6.183
270051AF1-062 GEN
50/50
11.828
270475AD2-096_GEN
50/50
7.148
970153AG2-106 GEN
Solar/Wind Harmer
17.883
961921AG1-034 GEN
Solar/Wind Harmer
15.599
24721905FLATG4
Adder
23.989
241955AC1-078 GEN
Solar/Wind Harmer
8.811
241974AD2-163_GEN2
Solar/Wind Harmer
2.33
942051AE2-217 GEN
Solar/Wind Harmer
21.044
960801AF2-371 GEN
Solar/Wind Harmer
2.947
964871AG1-351 GEN
Solar/Wind Harmer
2.035
970605AG2-385 GEN
Solar/Wind Harmer
6.239
942871AE2-306 GEN
Solar/Wind Harmer
1.047
270391AF1-285 GEN3
Solar/Wind Harmer
0.537
253338AC1-165 GEN
Solar/Wind Harmer
1.241
253333AC1-068 GEN
Solar/Wind Harmer
1.197
270485AE1-090_GEN
Solar/Wind Harmer
0.69
270273AD2-016 GEN
Solar/Wind Harmer
3.032
972173AH1-669 GEN
Solar/Wind Harmer
5.669
253415AE1-040 GEN
Solar/Wind Harmer
1.248
270291AC1-194 GEN
Solar/Wind Harmer
11.736
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.066
970065AG2-057 GEN
Solar/Wind Harmer
1.09
957541AF2-048 GEN
Solar/Wind Harmer
1.72
270512AE1-227 GEN2
Solar/Wind Harmer
2.283
253406AD2-031_GEN
Solar/Wind Harmer
1.388
270491AE1-102 GEN2
Solar/Wind Harmer
1.404
971191AH1-055 GEN
Solar/Wind Harmer
23.693
270377AD1-106 GEN
Solar/Wind Harmer
6.649
253316AC1-085 GEN3
Solar/Wind Harmer
9.014
253433AC1-085 GEN1
Solar/Wind Harmer
5.722
946181AF1-283 GEN
Solar/Wind Harmer
13.99
270191TR4_S_V150
Solar/Wind Harmer
3.224
270247TR4_N_V136
Solar/Wind Harmer
0.914
959331AF2-224 GEN
Solar/Wind Harmer
10.746
965021AG1-366 GEN
Solar/Wind Harmer
2.499
958091AF2-103 GEN
Solar/Wind Harmer
0.173
270588AE1-091_GEN
Solar/Wind Harmer
11.789
944531AF1-118 GEN
Solar/Wind Harmer
37.432
270043AE2-236 GEN
Solar/Wind Harmer
5.876
270258AD1-119 GEN
Solar/Wind Harmer
2.963
971617AH1-308 GEN
Solar/Wind Harmer
6.181
25196608WSDLE5
Adder
9.089
962031AG1-047 GEN
Solar/Wind Harmer
3.205
252510AF1-249 C
Solar/Wind Harmer
0.443
957741AF2-068 GEN
Solar/Wind Harmer
15.904
25194608D.CRK4
Adder
1.742
270222AC2-111 GEN
Solar/Wind Harmer
8.632
970031AG2-029 GEN
Solar/Wind Harmer
31.759
270044AE2-322 C
Solar/Wind Harmer
1.391
270404AC1-167 GEN
Solar/Wind Harmer
1.158
24642205MAYFLWER
Adder
0.665
25196008MFTGT1
Adder
1.406
247604X1-042
Adder
0.434
274752CRETE EC ;2U
Adder
8.489
274753CRETE EC ;3U
Adder
8.489
274772LINCOLN ;3U
Adder
8.688
274724RIVER EC ;11
Adder
18.229
24728705AND G3
Adder
8.226
274802UNIV PARK;5U
Adder
5.978
24728505AND G1
Adder
3.933
274826FISK ;BP
Adder
11.221
274800UNIV PARK;3U
Adder
5.975
972038AH1-567 GEN2
Adder
0.374
972228AH1-698 GEN2
Adder
3.796
274676JOLIET 29;8U
Adder
30.228
274729ELWOOD EC;1P
Adder
16.792
274730ELWOOD EC;6P
Adder
16.792
274734ELWOOD EC;8P
Adder
16.792
274736ELWOOD EC;9P
Adder
16.792
274682WAUKEGAN ;7U
Adder
9.742
964991AG1-363 GEN
Solar/Wind Helper
5.141
316097T157 G90
Solar/Wind Helper
1.505
23750701CROSSCHOOL
Solar/Wind Helper
1.505
238118U2-030_1
Solar/Wind Helper
0.342
238127S14_GEN_2
Solar/Wind Helper
0.829
238148AE2-230_GEN2
Solar/Wind Helper
0.497
237080AD1-060 GEN
Solar/Wind Helper
0.342
237038AE2-054 C
Solar/Wind Helper
0.272
235062AE1-101 C1
Solar/Wind Helper
1.661
23779801AA1-109
Solar/Wind Helper
0.193
237048AF1-022 C
Solar/Wind Helper
0.178
223401AF1-299 GEN
Solar/Wind Helper
0.368
316006AB2-029 C
Solar/Wind Helper
0.117
966131AG1-482 GEN
Solar/Wind Helper
0.077
233930AB2-032 GEN
Solar/Wind Helper
0.381
233915AB1-141 GEN
Solar/Wind Helper
0.503
232422X3-066 FULL
Solar/Wind Helper
0.114
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
233998TM1NIN_3.36
Solar/Wind Helper
0.262
232404W1-003 C
Solar/Wind Helper
0.508
232428Y3-058 C
Solar/Wind Helper
0.338
233954AC2-188 GEN
Solar/Wind Helper
0.233
233950AC2-186 GEN
Solar/Wind Helper
0.116
232434Z2-077 GEN
Solar/Wind Helper
0.127
233972AC1-094 C
Solar/Wind Helper
0.303
316045AC1-158 PL2
Solar/Wind Helper
4.142
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.23
228728W1-130C
Solar/Wind Helper
0.054
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219904AC1-010 C
Solar/Wind Helper
0.061
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.131
20720728JCB_W1-129
Solar/Wind Helper
0.057
316254AC1-120 GEN1
Solar/Wind Helper
1.06
207445AB1-138_GEN
Solar/Wind Helper
0.104
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.31
20715228NPK_W1-113
Solar/Wind Helper
0.078
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.496
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
207437AD2-070 GEN
Solar/Wind Helper
0.138
207518AF1-320_GEN
Solar/Wind Helper
1.573
20671928W4-073
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.03
970513AG2-328 GEN
Solar/Wind Harmer
3.728
970517AG2-330 GEN
Solar/Wind Harmer
3.381
274771LINCOLN ;2U
Adder
8.688
274808UNIV PK N;4U
Adder
5.124
274803UNIV PARK;6U
Adder
5.978
972259AH1-714 GEN
Adder
19.535
274674JOLIET 9 ;6U
Adder
15.727
274696ROCKY RD ;4P
Adder
11.554
274695ROCKY RD ;2P
Adder
11.287
274693ROCKY RD ;1P
Adder
11.176
274697ROCKY RD ;3P
Adder
3.066
23585401KL_K28_T16
Solar/Wind Helper
1.485
238120AE2-309 GEN
Solar/Wind Helper
0.526
238175AF1-290_GEN
Solar/Wind Helper
0.153
238169AE2-226 GEN1
Solar/Wind Helper
0.702
238170AE2-226 GEN2
Solar/Wind Helper
0.702
235020AA1-095 C
Solar/Wind Helper
0.053
23777901MDS_W4-102
Solar/Wind Helper
0.177
237002AB1-128_GEN
Solar/Wind Helper
0.444
237034AC2-136 C
Solar/Wind Helper
0.227
235063AE1-101 C2
Solar/Wind Helper
1.661
237001AB1-127_GEN
Solar/Wind Helper
0.442
23777801MSM_W1-116
Solar/Wind Helper
0.114
237025AB1-124 C
Solar/Wind Helper
0.164
237006AB1-125 GEN
Solar/Wind Helper
0.123
226929AD2-058 GEN
Solar/Wind Helper
0.099
205916AD1-020 GEN
Solar/Wind Helper
1.715
20390526W1-045 C
Solar/Wind Helper
0.35
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
233987AB2-037 GEN
Solar/Wind Helper
2.344
233933AB2-153 GEN
Solar/Wind Helper
0.233
232424Y1-079 C
Solar/Wind Helper
0.116
233944AB2-135 GEN
Solar/Wind Helper
0.589
233946AB2-136 GEN
Solar/Wind Helper
0.569
234036AF2-325 C
Solar/Wind Helper
0.042
233901CHERRYDALE C
Solar/Wind Helper
0.233
232408W1-005 C
Solar/Wind Helper
0.508
232410W1-006 C
Solar/Wind Helper
0.508
233939AC1-091 C
Solar/Wind Helper
0.35
233970AC1-092 C
Solar/Wind Helper
0.35
315651AD1-115 GEN
Solar/Wind Helper
0.785
316447AC1-158 HLD
Solar/Wind Helper
2.848
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.04
219921AF1-264
Solar/Wind Helper
0.051
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.082
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.19
20716928W4-060COL
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.016
20673828FLE_V3-070
Solar/Wind Helper
0.091
207442AE1-156 GEN
Solar/Wind Helper
0.326
20676128MHD_W3-029
Solar/Wind Helper
0.096
20671828STAW2-080
Solar/Wind Helper
0.027
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
207471AF2-354 C
Solar/Wind Helper
0.169
20674928WA_W3-044
Solar/Wind Helper
0.098
20676228FRD_X1-012
Solar/Wind Helper
0.092
964851AG1-348 GEN
Solar/Wind Helper
0.081
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.045
211065PSPA IPP
Solar/Wind Helper
0.152
211065PSPA IPP
Solar/Wind Helper
0.152
970321AG2-212 GEN
Solar/Wind Harmer
3.728
241973AD2-163_GEN1
Solar/Wind Harmer
2.33
945631AF1-228 GEN
Solar/Wind Harmer
5.461
943861AF1-054 GEN
Solar/Wind Harmer
4.486
943851AF1-053 GEN
Solar/Wind Harmer
2.168
270156DARBY CT1
Adder
10.416
270157DARBY CT2
Adder
10.391
270158DARBY CT3
Adder
10.225
970689AG2-444 GEN
Solar/Wind Harmer
18.82
270578AF1-285 GEN2
Solar/Wind Harmer
0.537
270432AC2-029 GEN
Solar/Wind Harmer
8.046
270302AB2-170 GEN
Solar/Wind Harmer
9.546
270317AD1-130_GEN
Solar/Wind Harmer
3.66
940611AE2-048 GEN
Solar/Wind Harmer
25.033
941391AE2-136 GEN
Solar/Wind Harmer
12.972
270269AC2-059
Solar/Wind Harmer
10.602
241972AD1-140 GEN
Solar/Wind Harmer
5.021
958581AF2-149 GEN
Solar/Wind Harmer
4.736
970179AG2-119 GEN
Solar/Wind Harmer
8.837
270340AC2-060 GEN
Solar/Wind Harmer
3.346
970879AG2-548 GEN
Solar/Wind Harmer
4.728
253372AE2-315 SEC3
Adder
2.066
253372AE2-315 SEC3
Adder
2.066
25306009OHH W.
Adder
3.134
253349AC2-067 GEN
Solar/Wind Harmer
5.408
253400AC2-068 GEN
Solar/Wind Harmer
2.175
957201AF2-014 GEN
Solar/Wind Harmer
4.898
270435AC2-044 GEN
Solar/Wind Harmer
2.16
965051AG1-369 GEN
Solar/Wind Harmer
5.366
965041AG1-368 GEN
Solar/Wind Harmer
10.722
247607V1-011 GEN
Solar/Wind Harmer
4.239
971567AH1-282 GEN
Solar/Wind Harmer
16.059
966831AG1-554 GEN
Solar/Wind Harmer
1.279
971989AH1-539 GEN
Solar/Wind Harmer
13.833
24729505KEY G4
Adder
6.928
963791AG1-232 GEN
Solar/Wind Harmer
14.415
270071AF1-092 GEN
Solar/Wind Harmer
16.001
971985AH1-537 GEN
Solar/Wind Harmer
18.998
958711AF2-162 GEN
Solar/Wind Harmer
1.076
270024AE2-089 GEN
Solar/Wind Harmer
4.99
270367AC2-061_GEN
Solar/Wind Harmer
3.379
965101AG1-375 GEN
Solar/Wind Harmer
10.622
971673AH1-337 GEN
Solar/Wind Harmer
4.88
252524AE2-267 GEN
Solar/Wind Harmer
1.673
971029AG2-637 GEN
Solar/Wind Harmer
15.909
25196408WSDLE3
Adder
9.356
25196308WSDLE2
Adder
9.275
25196208WSDLE1
Adder
9.252
25196708WSDLE6
Adder
9.228
25196508WSDLE4
Adder
8.996
270543AE2-219 C
Solar/Wind Harmer
5.43
961761AG1-017 GEN
Solar/Wind Harmer
0.454
945581AF1-223 GEN
Solar/Wind Harmer
4.805
270297AD1-101 GEN
Solar/Wind Harmer
2.947
944031AF1-071 GEN
Solar/Wind Harmer
1.064
25196108MFTGT2
Adder
1.601
25196108MFTGT2
Adder
1.486
274775LINCOLN ;6U
Adder
8.688
274776LINCOLN ;7U
Adder
8.688
274777LINCOLN ;8U
Adder
8.688
274814UNIV PK N;0U
Adder
5.192
274807UNIV PK N;3U
Adder
5.18
274805UNIV PK N;1U
Adder
5.158
274811UNIV PK N;7U
Adder
5.147
972037AH1-567 GEN1
Adder
0.188
274827FISK ;RP
Adder
7.953
972227AH1-698 GEN1
Adder
2.673
274687WILL CNTY;4U
Adder
28.564
274687WILL CNTY;4U
Adder
28.564
274675JOLIET 29;7U
Adder
31.348
274675JOLIET 29;7U
Adder
30.228
274731ELWOOD EC;2P
Adder
16.792
274733ELWOOD EC;3P
Adder
16.792
274735ELWOOD EC;4P
Adder
16.792
274728ELWOOD EC;5P
Adder
16.792
972203AH1-686 GEN
Adder
2.344
274746AC1-111 G10
Adder
5.687
274744AC1-111 GEN8
Adder
5.687
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238126S14_GEN_1
Solar/Wind Helper
0.829
238152AF2-075_GEN
Solar/Wind Helper
0.708
238208AF1-136 C
Solar/Wind Helper
0.22
23546401DTGZ2-030
Solar/Wind Helper
0.089
237085AD2-009_GEN
Solar/Wind Helper
1.651
3138216PACIFIC
Solar/Wind Helper
0.044
316411AF1-147_GEN1
Solar/Wind Helper
0.889
316415AF1-147_GEN2
Solar/Wind Helper
0.889
23750501ELLIOTTS
Solar/Wind Helper
0.64
959381AF2-229 GEN
Solar/Wind Helper
0.358
3141426STAFORD
Solar/Wind Helper
0.052
960921AF2-383 GEN
Solar/Wind Helper
0.182
205943AE1-185 GEN
Solar/Wind Helper
0.51
205932AD2-116_GEN
Solar/Wind Helper
0.509
205956AE1-196_GEN
Solar/Wind Helper
0.509
233935AB2-179 C
Solar/Wind Helper
1.27
232436AB1-176 C
Solar/Wind Helper
0.044
233923SMA
Solar/Wind Helper
0.959
233990AG1-397 GEN
Solar/Wind Helper
0.03
234033AF1-007_GEN
Solar/Wind Helper
7.028
232432Z2-076 GEN
Solar/Wind Helper
0.067
964001AG1-254 GEN
Solar/Wind Helper
0.957
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.115
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.08
203975AE1-071-GEN
Solar/Wind Helper
2.501
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.29
219620RIDERU C
Solar/Wind Helper
0.001
316164AC1-076 GEN
Solar/Wind Helper
1.097
20675528CPH_W2-050
Solar/Wind Helper
0.087
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
218524CNTRALGAS1 C
Solar/Wind Helper
0.161
966261AG1-495 GEN
Solar/Wind Helper
0.081
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20675928HOL_W4-097
Solar/Wind Helper
0.05
207484AF2-139 C O1
Solar/Wind Helper
0.084
20674828DL_W4-046
Solar/Wind Helper
0.008
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.137
20675128HRM_W1-127
Solar/Wind Helper
0.03
209116AE2-175 GEN
Solar/Wind Helper
1.781
LAGNLTFEXP_LAGN->PJM
CLTF
14.864
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.83
TVALTFEXP_TVA->PJM
CLTF
7.306
CPLELTFEXP_CPLE->PJM
CLTF
0.632
CBM West 2LTFEXP_CBM-W2->PJM
CBM
113.005
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.265
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.153
MECLTFEXP_MEC->PJM
CLTF
15.925
SIGELTFEXP_SIGE->PJM
CLTF
0.506
NYPJM->LTFIMP_NY
CLTF
4.803
LGEELTFEXP_LGEE->PJM
CLTF
6.759
WECLTFEXP_WEC->PJM
CLTF
3.83
AG2-052LTFEXP_AG2-052->PJM
LTF
0.24
AH1-155LTFEXP_AH1-155->PJM
LTF
0.36

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-015_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-015_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:131.63 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4908.47
MW Contribution:0.86
Bus #Bus NameTypeMW Contribution
270166AC1-044 GEN3
50/50
7.063
23559101PLEAS2
50/50
6.112
23684101S70BUS1
50/50
0.168
962761AG1-125 GEN
Solar/Wind Harmer
40.976
970149AG2-104 GEN
Solar/Wind Harmer
50.605
970155AG2-107 GEN
Solar/Wind Harmer
17.867
270349AD2-093_GEN
Solar/Wind Harmer
4.466
24721705FLATG2
Adder
23.946
270159DARBY CT4
Adder
10.253
970593AG2-378 GEN
Solar/Wind Harmer
2.311
270223U2-072_GEN1
Solar/Wind Harmer
2.282
270578AF1-285 GEN2
Solar/Wind Harmer
1.396
270391AF1-285 GEN3
Solar/Wind Harmer
1.396
253343AC1-166 GEN
Solar/Wind Harmer
1.242
253325AC1-069 GEN
Solar/Wind Harmer
1.197
270462AD2-086
Solar/Wind Harmer
7.941
971995AH1-542 GEN
Solar/Wind Harmer
12.507
270263AC1-001 GEN
Solar/Wind Harmer
1.177
270510AE1-227 GEN1
Solar/Wind Harmer
2.727
25326309TAIT D
Adder
1.197
241813AF1-122_GEN
Solar/Wind Harmer
6.978
960071AF2-298 GEN
Solar/Wind Harmer
5.44
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.065
927014AC1-188 GEN
Solar/Wind Harmer
1.725
246936BC-WTG1
Solar/Wind Harmer
4.226
270489AE1-102 GEN1
Solar/Wind Harmer
1.404
965421AG1-410 GEN
Solar/Wind Harmer
32.379
960001AF2-291 GEN
Solar/Wind Harmer
3.256
253432AC1-085 GEN2
Solar/Wind Harmer
0.288
946171AF1-282 GEN
Solar/Wind Harmer
10.76
247521TR3_G114
Solar/Wind Harmer
3.612
270246TR4_N_V150
Solar/Wind Harmer
0.914
965011AG1-365 GEN
Solar/Wind Harmer
10.743
24695305TIMB G C
Solar/Wind Harmer
5.899
965651AG1-433 GEN
Solar/Wind Harmer
5.811
958861AF2-177 GEN
Solar/Wind Harmer
11.606
247536S-71 GEN
Solar/Wind Harmer
4.292
25194608D.CRK4
Adder
1.742
945371AF1-202 GEN
Solar/Wind Harmer
7.39
252507AC2-088 GEN
Solar/Wind Harmer
1.898
270063AE2-323 C
Solar/Wind Harmer
2.329
25196808ZIMRHP
Adder
79.816
24639705ELKHART HY
Adder
0.161
25196008MFTGT1
Adder
1.452
274751CRETE EC ;1U
Adder
8.485
274754CRETE EC ;4U
Adder
8.485
274773LINCOLN ;4U
Adder
8.684
274774LINCOLN ;5U
Adder
8.684
274723RIVER EC ;12
Adder
18.437
274812UNIV PK N;8U
Adder
5.144
24728605AND G2
Adder
3.932
274801UNIV PARK;4U
Adder
5.972
274676JOLIET 29;8U
Adder
31.334
274732ELWOOD EC;7P
Adder
16.784
274674JOLIET 9 ;6U
Adder
15.72
274745AC1-111 GEN9
Adder
5.685
970091AG2-072 GEN
Adder
77.715
316095T157 G97
Solar/Wind Helper
1.505
23583801GRNGAP
Solar/Wind Helper
5.607
238185AF2-356 C
Solar/Wind Helper
2.642
238108AE1-109 GEN1
Solar/Wind Helper
0.114
235054AD2-180 GEN
Solar/Wind Helper
2.025
235531U2-073 GEN
Solar/Wind Helper
3.278
238117U2-030
Solar/Wind Helper
0.341
238147AE2-230_GEN1
Solar/Wind Helper
0.495
238149AF1-291A_GEN
Solar/Wind Helper
0.141
237061AD1-155 GEN
Solar/Wind Helper
0.053
23751201ROTHROCK
Solar/Wind Helper
0.819
238221AF1-254 C O1
Solar/Wind Helper
0.275
23562501BACKB
Solar/Wind Helper
1.001
235067AD1-061 GEN
Solar/Wind Helper
0.496
23751101LEADS_P59
Solar/Wind Helper
1.388
237030AB1-096 C
Solar/Wind Helper
0.071
3141196NOKESVL
Solar/Wind Helper
1.033
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.346
223402AF1-300 C
Solar/Wind Helper
0.368
205917AD1-020 ES
Solar/Wind Helper
0.369
233982AB2-133 GEN
Solar/Wind Helper
0.358
233918AB1-142 GEN
Solar/Wind Helper
0.503
233994AC2-023 GEN
Solar/Wind Helper
0.962
233996TM1833_GEN
Solar/Wind Helper
0.262
233997TMININ_4.2
Solar/Wind Helper
0.262
232406W1-004 FULL
Solar/Wind Helper
0.508
233940AF2-379 C
Solar/Wind Helper
0.062
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.233
233971AC1-093 C
Solar/Wind Helper
0.358
316044AC1-158 PL1
Solar/Wind Helper
1.294
316450AC1-158 RIC
Solar/Wind Helper
0.345
230430AE1-229_GEN
Solar/Wind Helper
3.376
230415AB2-049 C
Solar/Wind Helper
0.03
228729W2-030 C
Solar/Wind Helper
0.111
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.15
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
219348LDSOLAR C
Solar/Wind Helper
0.115
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.063
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.354
219276PARKLANDSO C
Solar/Wind Helper
0.089
20714528FRN_Y2-051
Solar/Wind Helper
0.057
20720528MAN_W1-024
Solar/Wind Helper
0.028
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.027
219249CENTRALDIV C
Solar/Wind Helper
0.01
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.089
970245AG2-165 GEN
Solar/Wind Harmer
3.726
24318805MLG1
50/50
10.098
23559001PLEAS1
50/50
6.112
270051AF1-062 GEN
50/50
11.831
23684201S70BUS2
50/50
0.171
270475AD2-096_GEN
50/50
7.147
970153AG2-106 GEN
Solar/Wind Harmer
17.867
961921AG1-034 GEN
Solar/Wind Harmer
15.607
241955AC1-078 GEN
Solar/Wind Harmer
8.813
24721905FLATG4
Adder
23.946
241974AD2-163_GEN2
Solar/Wind Harmer
2.331
942051AE2-217 GEN
Solar/Wind Harmer
21.048
960801AF2-371 GEN
Solar/Wind Harmer
2.948
964871AG1-351 GEN
Solar/Wind Harmer
2.036
970605AG2-385 GEN
Solar/Wind Harmer
6.24
942871AE2-306 GEN
Solar/Wind Harmer
1.047
270391AF1-285 GEN3
Solar/Wind Harmer
0.537
253338AC1-165 GEN
Solar/Wind Harmer
1.242
253333AC1-068 GEN
Solar/Wind Harmer
1.197
270485AE1-090_GEN
Solar/Wind Harmer
0.69
270273AD2-016 GEN
Solar/Wind Harmer
3.033
972173AH1-669 GEN
Solar/Wind Harmer
5.671
270291AC1-194 GEN
Solar/Wind Harmer
11.744
253415AE1-040 GEN
Solar/Wind Harmer
1.248
270512AE1-227 GEN2
Solar/Wind Harmer
2.315
970065AG2-057 GEN
Solar/Wind Harmer
1.09
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.065
957541AF2-048 GEN
Solar/Wind Harmer
1.721
253406AD2-031_GEN
Solar/Wind Harmer
1.388
270491AE1-102 GEN2
Solar/Wind Harmer
1.404
270377AD1-106 GEN
Solar/Wind Harmer
6.655
971191AH1-055 GEN
Solar/Wind Harmer
23.692
253316AC1-085 GEN3
Solar/Wind Harmer
9.013
253433AC1-085 GEN1
Solar/Wind Harmer
5.721
946181AF1-283 GEN
Solar/Wind Harmer
13.988
270191TR4_S_V150
Solar/Wind Harmer
3.223
270247TR4_N_V136
Solar/Wind Harmer
0.914
959331AF2-224 GEN
Solar/Wind Harmer
10.743
965021AG1-366 GEN
Solar/Wind Harmer
2.498
270588AE1-091_GEN
Solar/Wind Harmer
11.792
958091AF2-103 GEN
Solar/Wind Harmer
0.173
944531AF1-118 GEN
Solar/Wind Harmer
37.418
270043AE2-236 GEN
Solar/Wind Harmer
5.874
270258AD1-119 GEN
Solar/Wind Harmer
2.962
971617AH1-308 GEN
Solar/Wind Harmer
6.179
25196608WSDLE5
Adder
9.087
252510AF1-249 C
Solar/Wind Harmer
0.443
962031AG1-047 GEN
Solar/Wind Harmer
3.204
957741AF2-068 GEN
Solar/Wind Harmer
15.899
25194608D.CRK4
Adder
1.742
270222AC2-111 GEN
Solar/Wind Harmer
8.63
970031AG2-029 GEN
Solar/Wind Harmer
31.748
270044AE2-322 C
Solar/Wind Harmer
1.39
270404AC1-167 GEN
Solar/Wind Harmer
1.158
24642205MAYFLWER
Adder
0.665
25196008MFTGT1
Adder
1.406
247604X1-042
Adder
0.433
274752CRETE EC ;2U
Adder
8.485
274753CRETE EC ;3U
Adder
8.485
274772LINCOLN ;3U
Adder
8.684
274724RIVER EC ;11
Adder
18.221
24728705AND G3
Adder
8.223
274802UNIV PARK;5U
Adder
5.976
24728505AND G1
Adder
3.932
274826FISK ;BP
Adder
11.216
274800UNIV PARK;3U
Adder
5.972
972038AH1-567 GEN2
Adder
0.374
972228AH1-698 GEN2
Adder
3.794
274676JOLIET 29;8U
Adder
30.215
274729ELWOOD EC;1P
Adder
16.784
274730ELWOOD EC;6P
Adder
16.784
274734ELWOOD EC;8P
Adder
16.784
274736ELWOOD EC;9P
Adder
16.784
274682WAUKEGAN ;7U
Adder
9.459
964991AG1-363 GEN
Solar/Wind Helper
5.14
316097T157 G90
Solar/Wind Helper
1.505
23750701CROSSCHOOL
Solar/Wind Helper
1.501
238118U2-030_1
Solar/Wind Helper
0.341
238127S14_GEN_2
Solar/Wind Helper
0.826
238148AE2-230_GEN2
Solar/Wind Helper
0.497
237080AD1-060 GEN
Solar/Wind Helper
0.342
237038AE2-054 C
Solar/Wind Helper
0.272
235062AE1-101 C1
Solar/Wind Helper
1.661
23779801AA1-109
Solar/Wind Helper
0.193
237048AF1-022 C
Solar/Wind Helper
0.177
223401AF1-299 GEN
Solar/Wind Helper
0.368
316006AB2-029 C
Solar/Wind Helper
0.117
966131AG1-482 GEN
Solar/Wind Helper
0.077
233930AB2-032 GEN
Solar/Wind Helper
0.381
233915AB1-141 GEN
Solar/Wind Helper
0.503
232422X3-066 FULL
Solar/Wind Helper
0.114
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
233998TM1NIN_3.36
Solar/Wind Helper
0.262
232404W1-003 C
Solar/Wind Helper
0.508
232428Y3-058 C
Solar/Wind Helper
0.338
232434Z2-077 GEN
Solar/Wind Helper
0.127
233954AC2-188 GEN
Solar/Wind Helper
0.233
233950AC2-186 GEN
Solar/Wind Helper
0.116
233972AC1-094 C
Solar/Wind Helper
0.303
316045AC1-158 PL2
Solar/Wind Helper
4.142
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.23
228728W1-130C
Solar/Wind Helper
0.054
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219904AC1-010 C
Solar/Wind Helper
0.06
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.131
20720728JCB_W1-129
Solar/Wind Helper
0.057
316254AC1-120 GEN1
Solar/Wind Helper
1.061
207445AB1-138_GEN
Solar/Wind Helper
0.104
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.31
20715228NPK_W1-113
Solar/Wind Helper
0.078
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.496
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
207437AD2-070 GEN
Solar/Wind Helper
0.138
207518AF1-320_GEN
Solar/Wind Helper
1.573
20671928W4-073
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.03
970513AG2-328 GEN
Solar/Wind Harmer
3.726
970517AG2-330 GEN
Solar/Wind Harmer
3.379
270119AB2-067 GEN1
50/50
7.063
270120AB2-067 GEN2
50/50
7.063
24318905MLG2
50/50
7.074
270471AD2-092_GEN
Solar/Wind Harmer
4.466
946101AF1-275 GEN
Solar/Wind Harmer
1.816
942861AE2-305 GEN
Solar/Wind Harmer
9.089
970077AG2-063 GEN
Solar/Wind Harmer
6.24
270224U2-072_GEN2
Solar/Wind Harmer
2.282
270227U2-072_GEN3
Solar/Wind Harmer
2.282
270228U2-072_GEN4
Solar/Wind Harmer
2.282
270231U2-072_GEN5
Solar/Wind Harmer
2.282
938701AE1-092 GEN
Solar/Wind Harmer
23.829
964601AG1-323 GEN
Solar/Wind Harmer
3.66
964601AG1-323 GEN
Solar/Wind Harmer
1.702
270518AE2-148 GEN
Solar/Wind Harmer
13.889
972269AH1-719 GEN
Adder
2.587
972159AH1-661 GEN
Adder
1.119
253378AE2-206_GEN
Solar/Wind Harmer
4.007
276820AF1-078_GEN
Solar/Wind Harmer
1.78
971199AH1-059 GEN
Solar/Wind Harmer
4.433
241960AC2-195 GEN
Solar/Wind Harmer
3.073
25326509SID D
Adder
1.452
970879AG2-548 GEN
Solar/Wind Harmer
6.78
971073AG2-665 GEN
Solar/Wind Harmer
6.78
971073AG2-665 GEN
Solar/Wind Harmer
4.73
25326109MON D
Adder
1.444
25322209TAIT E
Adder
10.653
25322209TAIT E
Adder
10.414
971201AH1-060 GEN
Solar/Wind Harmer
2.181
253370AE2-315 SEC1
Adder
2.184
253394AE2-221_GEN
Solar/Wind Harmer
4.918
253398AE2-221_GEN2
Solar/Wind Harmer
4.918
246938BC-WTG3
Solar/Wind Harmer
4.299
246937BC-WTG2
Solar/Wind Harmer
4.226
971231AH1-075 GEN
Solar/Wind Harmer
0.862
253317AC1-085 GEN4
Solar/Wind Harmer
9.013
970611AG2-400 GEN
Solar/Wind Harmer
10.743
270007AE1-245 C
Solar/Wind Harmer
6.358
942801AE2-298 GEN
Solar/Wind Harmer
1.622
962581AG1-107 GEN
Solar/Wind Harmer
5.365
961491AF2-440 GEN
Solar/Wind Harmer
2.229
25183208HLCRTG
Solar/Wind Harmer
6.449
944541AF1-119 GEN
Solar/Wind Harmer
4.453
960971AF2-388 GEN
Solar/Wind Harmer
11.621
942221AE2-234 GEN
Solar/Wind Harmer
0.778
252519AF1-045_GEN
Solar/Wind Harmer
6.447
252516AE2-318_GEN
Solar/Wind Harmer
4.918
247621Y3-024
Adder
0.256
970883AG2-550 GEN
Solar/Wind Harmer
10.602
970885AG2-551 GEN
Solar/Wind Harmer
2.465
270201AC2-176 GEN
Solar/Wind Harmer
5.449
25194408D.CRK1
Adder
8.013
25194508D.CRK3
Adder
1.498
964611AG1-324 GEN
Solar/Wind Harmer
1.248
964611AG1-324 GEN
Solar/Wind Harmer
0.554
252509AD1-136 GEN
Solar/Wind Harmer
0.271
247620Y3-023
Adder
0.484
24728805RICHG1
Adder
3.968
24728905RICHG2
Adder
3.968
274770LINCOLN ;1U
Adder
8.684
274771LINCOLN ;2U
Adder
8.684
274808UNIV PK N;4U
Adder
5.122
274803UNIV PARK;6U
Adder
5.976
972259AH1-714 GEN
Adder
19.527
274674JOLIET 9 ;6U
Adder
15.72
274696ROCKY RD ;4P
Adder
11.549
274695ROCKY RD ;2P
Adder
11.282
274693ROCKY RD ;1P
Adder
11.171
274697ROCKY RD ;3P
Adder
3.065
23585401KL_K28_T16
Solar/Wind Helper
1.478
238120AE2-309 GEN
Solar/Wind Helper
0.524
238175AF1-290_GEN
Solar/Wind Helper
0.153
238169AE2-226 GEN1
Solar/Wind Helper
0.702
238170AE2-226 GEN2
Solar/Wind Helper
0.702
235020AA1-095 C
Solar/Wind Helper
0.053
23777901MDS_W4-102
Solar/Wind Helper
0.177
237034AC2-136 C
Solar/Wind Helper
0.227
237002AB1-128_GEN
Solar/Wind Helper
0.443
235063AE1-101 C2
Solar/Wind Helper
1.661
237001AB1-127_GEN
Solar/Wind Helper
0.442
23777801MSM_W1-116
Solar/Wind Helper
0.114
237025AB1-124 C
Solar/Wind Helper
0.164
237006AB1-125 GEN
Solar/Wind Helper
0.123
226929AD2-058 GEN
Solar/Wind Helper
0.099
205916AD1-020 GEN
Solar/Wind Helper
1.715
20390526W1-045 C
Solar/Wind Helper
0.35
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
233987AB2-037 GEN
Solar/Wind Helper
2.344
233933AB2-153 GEN
Solar/Wind Helper
0.233
232424Y1-079 C
Solar/Wind Helper
0.116
233944AB2-135 GEN
Solar/Wind Helper
0.589
233946AB2-136 GEN
Solar/Wind Helper
0.569
234036AF2-325 C
Solar/Wind Helper
0.042
233901CHERRYDALE C
Solar/Wind Helper
0.233
232408W1-005 C
Solar/Wind Helper
0.508
232410W1-006 C
Solar/Wind Helper
0.508
233939AC1-091 C
Solar/Wind Helper
0.35
233970AC1-092 C
Solar/Wind Helper
0.35
315651AD1-115 GEN
Solar/Wind Helper
0.785
316447AC1-158 HLD
Solar/Wind Helper
2.848
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.04
219921AF1-264
Solar/Wind Helper
0.051
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.082
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.19
20716928W4-060COL
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.016
20673828FLE_V3-070
Solar/Wind Helper
0.091
207442AE1-156 GEN
Solar/Wind Helper
0.326
20676128MHD_W3-029
Solar/Wind Helper
0.096
20671828STAW2-080
Solar/Wind Helper
0.027
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
207471AF2-354 C
Solar/Wind Helper
0.169
20674928WA_W3-044
Solar/Wind Helper
0.098
964851AG1-348 GEN
Solar/Wind Helper
0.081
20676228FRD_X1-012
Solar/Wind Helper
0.092
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.045
211065PSPA IPP
Solar/Wind Helper
0.152
211065PSPA IPP
Solar/Wind Helper
0.152
970321AG2-212 GEN
Solar/Wind Harmer
3.726
962771AG1-126 GEN
Solar/Wind Harmer
40.976
972239AH1-704 GEN
Adder
2.69
270054AF2-122 C O1
Solar/Wind Harmer
3.996
270459AD2-067 GEN
Solar/Wind Harmer
10.248
961821AG1-024 GEN
Solar/Wind Harmer
10.404
270520AE2-214 GEN
Solar/Wind Harmer
7.276
270284AF1-227 GEN1
Solar/Wind Harmer
6.79
270286AF1-227 GEN2
Solar/Wind Harmer
2.512
270287AF1-227 GEN3
Solar/Wind Harmer
2.512
253383AE2-342_GEN
Solar/Wind Harmer
1.045
241973AD2-163_GEN1
Solar/Wind Harmer
2.331
945631AF1-228 GEN
Solar/Wind Harmer
5.463
943861AF1-054 GEN
Solar/Wind Harmer
4.486
943851AF1-053 GEN
Solar/Wind Harmer
2.168
270156DARBY CT1
Adder
10.419
270157DARBY CT2
Adder
10.393
270158DARBY CT3
Adder
10.228
970689AG2-444 GEN
Solar/Wind Harmer
18.827
270578AF1-285 GEN2
Solar/Wind Harmer
0.537
270432AC2-029 GEN
Solar/Wind Harmer
8.049
940611AE2-048 GEN
Solar/Wind Harmer
25.14
941391AE2-136 GEN
Solar/Wind Harmer
13.027
270302AB2-170 GEN
Solar/Wind Harmer
9.546
270317AD1-130_GEN
Solar/Wind Harmer
3.659
270269AC2-059
Solar/Wind Harmer
10.605
241972AD1-140 GEN
Solar/Wind Harmer
5.021
958581AF2-149 GEN
Solar/Wind Harmer
4.743
970179AG2-119 GEN
Solar/Wind Harmer
8.842
270340AC2-060 GEN
Solar/Wind Harmer
3.346
970879AG2-548 GEN
Solar/Wind Harmer
4.73
253372AE2-315 SEC3
Adder
2.065
253372AE2-315 SEC3
Adder
2.065
25306009OHH W.
Adder
3.133
253349AC2-067 GEN
Solar/Wind Harmer
5.407
253400AC2-068 GEN
Solar/Wind Harmer
2.174
957201AF2-014 GEN
Solar/Wind Harmer
4.898
270435AC2-044 GEN
Solar/Wind Harmer
2.16
965051AG1-369 GEN
Solar/Wind Harmer
5.365
965041AG1-368 GEN
Solar/Wind Harmer
10.719
247607V1-011 GEN
Solar/Wind Harmer
4.239
971567AH1-282 GEN
Solar/Wind Harmer
16.075
966831AG1-554 GEN
Solar/Wind Harmer
1.28
971989AH1-539 GEN
Solar/Wind Harmer
13.838
24729505KEY G4
Adder
6.925
963791AG1-232 GEN
Solar/Wind Harmer
14.411
270071AF1-092 GEN
Solar/Wind Harmer
15.995
971985AH1-537 GEN
Solar/Wind Harmer
18.996
958711AF2-162 GEN
Solar/Wind Harmer
1.076
270024AE2-089 GEN
Solar/Wind Harmer
4.988
270367AC2-061_GEN
Solar/Wind Harmer
3.378
965101AG1-375 GEN
Solar/Wind Harmer
10.618
971673AH1-337 GEN
Solar/Wind Harmer
4.878
252524AE2-267 GEN
Solar/Wind Harmer
1.672
25196408WSDLE3
Adder
9.354
25196308WSDLE2
Adder
9.273
25196208WSDLE1
Adder
9.25
25196708WSDLE6
Adder
9.227
25196508WSDLE4
Adder
8.994
971029AG2-637 GEN
Solar/Wind Harmer
15.905
270543AE2-219 C
Solar/Wind Harmer
5.429
961761AG1-017 GEN
Solar/Wind Harmer
0.454
945581AF1-223 GEN
Solar/Wind Harmer
4.803
270297AD1-101 GEN
Solar/Wind Harmer
2.947
944031AF1-071 GEN
Solar/Wind Harmer
1.064
25196108MFTGT2
Adder
1.6
25196108MFTGT2
Adder
1.486
274775LINCOLN ;6U
Adder
8.684
274776LINCOLN ;7U
Adder
8.684
274777LINCOLN ;8U
Adder
8.684
274814UNIV PK N;0U
Adder
5.189
274807UNIV PK N;3U
Adder
5.178
274805UNIV PK N;1U
Adder
5.156
274811UNIV PK N;7U
Adder
5.144
972037AH1-567 GEN1
Adder
0.188
274827FISK ;RP
Adder
7.949
972227AH1-698 GEN1
Adder
2.671
274687WILL CNTY;4U
Adder
28.551
274687WILL CNTY;4U
Adder
28.551
274675JOLIET 29;7U
Adder
31.334
274675JOLIET 29;7U
Adder
30.215
274731ELWOOD EC;2P
Adder
16.784
274733ELWOOD EC;3P
Adder
16.784
274735ELWOOD EC;4P
Adder
16.784
274728ELWOOD EC;5P
Adder
16.784
972203AH1-686 GEN
Adder
2.341
274746AC1-111 G10
Adder
5.685
274744AC1-111 GEN8
Adder
5.685
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238126S14_GEN_1
Solar/Wind Helper
0.826
238152AF2-075_GEN
Solar/Wind Helper
0.708
238208AF1-136 C
Solar/Wind Helper
0.22
23546401DTGZ2-030
Solar/Wind Helper
0.089
237085AD2-009_GEN
Solar/Wind Helper
1.65
3138216PACIFIC
Solar/Wind Helper
0.044
316411AF1-147_GEN1
Solar/Wind Helper
0.889
316415AF1-147_GEN2
Solar/Wind Helper
0.889
23750501ELLIOTTS
Solar/Wind Helper
0.637
959381AF2-229 GEN
Solar/Wind Helper
0.358
3141426STAFORD
Solar/Wind Helper
0.052
960921AF2-383 GEN
Solar/Wind Helper
0.182
205943AE1-185 GEN
Solar/Wind Helper
0.51
205932AD2-116_GEN
Solar/Wind Helper
0.509
205956AE1-196_GEN
Solar/Wind Helper
0.509
233935AB2-179 C
Solar/Wind Helper
1.27
232436AB1-176 C
Solar/Wind Helper
0.044
233923SMA
Solar/Wind Helper
0.959
234033AF1-007_GEN
Solar/Wind Helper
7.028
233990AG1-397 GEN
Solar/Wind Helper
0.03
232432Z2-076 GEN
Solar/Wind Helper
0.067
964001AG1-254 GEN
Solar/Wind Helper
0.956
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.115
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.08
203975AE1-071-GEN
Solar/Wind Helper
2.5
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.29
219620RIDERU C
Solar/Wind Helper
0.001
316164AC1-076 GEN
Solar/Wind Helper
1.097
20675528CPH_W2-050
Solar/Wind Helper
0.087
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
218524CNTRALGAS1 C
Solar/Wind Helper
0.161
966261AG1-495 GEN
Solar/Wind Helper
0.081
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20675928HOL_W4-097
Solar/Wind Helper
0.05
20674828DL_W4-046
Solar/Wind Helper
0.008
207484AF2-139 C O1
Solar/Wind Helper
0.084
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.137
20675128HRM_W1-127
Solar/Wind Helper
0.03
209116AE2-175 GEN
Solar/Wind Helper
1.781
LAGNLTFEXP_LAGN->PJM
CLTF
14.855
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.816
TVALTFEXP_TVA->PJM
CLTF
7.302
CPLELTFEXP_CPLE->PJM
CLTF
0.627
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.944
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.216
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.135
MECLTFEXP_MEC->PJM
CLTF
15.918
SIGELTFEXP_SIGE->PJM
CLTF
0.506
NYPJM->LTFIMP_NY
CLTF
4.803
LGEELTFEXP_LGEE->PJM
CLTF
6.756
WECLTFEXP_WEC->PJM
CLTF
3.828
AG2-052LTFEXP_AG2-052->PJM
LTF
0.24
AH1-155LTFEXP_AH1-155->PJM
LTF
0.36

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-014_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:131.63 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4908.47
MW Contribution:0.86
Bus #Bus NameTypeMW Contribution
270166AC1-044 GEN3
50/50
7.063
23559101PLEAS2
50/50
6.112
23684101S70BUS1
50/50
0.168
962761AG1-125 GEN
Solar/Wind Harmer
40.976
970149AG2-104 GEN
Solar/Wind Harmer
50.605
970155AG2-107 GEN
Solar/Wind Harmer
17.867
270349AD2-093_GEN
Solar/Wind Harmer
4.466
24721705FLATG2
Adder
23.946
270159DARBY CT4
Adder
10.253
970593AG2-378 GEN
Solar/Wind Harmer
2.311
270223U2-072_GEN1
Solar/Wind Harmer
2.282
270578AF1-285 GEN2
Solar/Wind Harmer
1.396
270391AF1-285 GEN3
Solar/Wind Harmer
1.396
253343AC1-166 GEN
Solar/Wind Harmer
1.242
253325AC1-069 GEN
Solar/Wind Harmer
1.197
270462AD2-086
Solar/Wind Harmer
7.941
971995AH1-542 GEN
Solar/Wind Harmer
12.507
270263AC1-001 GEN
Solar/Wind Harmer
1.177
270510AE1-227 GEN1
Solar/Wind Harmer
2.727
25326309TAIT D
Adder
1.197
241813AF1-122_GEN
Solar/Wind Harmer
6.978
960071AF2-298 GEN
Solar/Wind Harmer
5.44
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.065
927014AC1-188 GEN
Solar/Wind Harmer
1.725
246936BC-WTG1
Solar/Wind Harmer
4.226
270489AE1-102 GEN1
Solar/Wind Harmer
1.404
965421AG1-410 GEN
Solar/Wind Harmer
32.379
960001AF2-291 GEN
Solar/Wind Harmer
3.256
253432AC1-085 GEN2
Solar/Wind Harmer
0.288
946171AF1-282 GEN
Solar/Wind Harmer
10.76
247521TR3_G114
Solar/Wind Harmer
3.612
270246TR4_N_V150
Solar/Wind Harmer
0.914
965011AG1-365 GEN
Solar/Wind Harmer
10.743
24695305TIMB G C
Solar/Wind Harmer
5.899
965651AG1-433 GEN
Solar/Wind Harmer
5.811
958861AF2-177 GEN
Solar/Wind Harmer
11.606
247536S-71 GEN
Solar/Wind Harmer
4.292
25194608D.CRK4
Adder
1.742
945371AF1-202 GEN
Solar/Wind Harmer
7.39
252507AC2-088 GEN
Solar/Wind Harmer
1.898
270063AE2-323 C
Solar/Wind Harmer
2.329
25196808ZIMRHP
Adder
79.816
24639705ELKHART HY
Adder
0.161
25196008MFTGT1
Adder
1.452
274751CRETE EC ;1U
Adder
8.485
274754CRETE EC ;4U
Adder
8.485
274773LINCOLN ;4U
Adder
8.684
274774LINCOLN ;5U
Adder
8.684
274723RIVER EC ;12
Adder
18.437
274812UNIV PK N;8U
Adder
5.144
24728605AND G2
Adder
3.932
274801UNIV PARK;4U
Adder
5.972
274676JOLIET 29;8U
Adder
31.334
274732ELWOOD EC;7P
Adder
16.784
274674JOLIET 9 ;6U
Adder
15.72
274745AC1-111 GEN9
Adder
5.685
970091AG2-072 GEN
Adder
77.715
316095T157 G97
Solar/Wind Helper
1.505
23583801GRNGAP
Solar/Wind Helper
5.607
238185AF2-356 C
Solar/Wind Helper
2.642
238108AE1-109 GEN1
Solar/Wind Helper
0.114
235054AD2-180 GEN
Solar/Wind Helper
2.025
235531U2-073 GEN
Solar/Wind Helper
3.278
238117U2-030
Solar/Wind Helper
0.341
238147AE2-230_GEN1
Solar/Wind Helper
0.495
238149AF1-291A_GEN
Solar/Wind Helper
0.141
237061AD1-155 GEN
Solar/Wind Helper
0.053
23751201ROTHROCK
Solar/Wind Helper
0.819
238221AF1-254 C O1
Solar/Wind Helper
0.275
23562501BACKB
Solar/Wind Helper
1.001
235067AD1-061 GEN
Solar/Wind Helper
0.496
23751101LEADS_P59
Solar/Wind Helper
1.388
237030AB1-096 C
Solar/Wind Helper
0.071
3141196NOKESVL
Solar/Wind Helper
1.033
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.346
223402AF1-300 C
Solar/Wind Helper
0.368
205917AD1-020 ES
Solar/Wind Helper
0.369
233982AB2-133 GEN
Solar/Wind Helper
0.358
233918AB1-142 GEN
Solar/Wind Helper
0.503
233994AC2-023 GEN
Solar/Wind Helper
0.962
233996TM1833_GEN
Solar/Wind Helper
0.262
233997TMININ_4.2
Solar/Wind Helper
0.262
232406W1-004 FULL
Solar/Wind Helper
0.508
233940AF2-379 C
Solar/Wind Helper
0.062
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.233
233971AC1-093 C
Solar/Wind Helper
0.358
316044AC1-158 PL1
Solar/Wind Helper
1.294
316450AC1-158 RIC
Solar/Wind Helper
0.345
230430AE1-229_GEN
Solar/Wind Helper
3.376
230415AB2-049 C
Solar/Wind Helper
0.03
228729W2-030 C
Solar/Wind Helper
0.111
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.15
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
219348LDSOLAR C
Solar/Wind Helper
0.115
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.063
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.354
219276PARKLANDSO C
Solar/Wind Helper
0.089
20714528FRN_Y2-051
Solar/Wind Helper
0.057
20720528MAN_W1-024
Solar/Wind Helper
0.028
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.027
219249CENTRALDIV C
Solar/Wind Helper
0.01
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.089
970245AG2-165 GEN
Solar/Wind Harmer
3.726
24318805MLG1
50/50
10.098
23559001PLEAS1
50/50
6.112
270051AF1-062 GEN
50/50
11.831
23684201S70BUS2
50/50
0.171
270475AD2-096_GEN
50/50
7.147
970153AG2-106 GEN
Solar/Wind Harmer
17.867
961921AG1-034 GEN
Solar/Wind Harmer
15.607
241955AC1-078 GEN
Solar/Wind Harmer
8.813
24721905FLATG4
Adder
23.946
241974AD2-163_GEN2
Solar/Wind Harmer
2.331
942051AE2-217 GEN
Solar/Wind Harmer
21.048
960801AF2-371 GEN
Solar/Wind Harmer
2.948
964871AG1-351 GEN
Solar/Wind Harmer
2.036
970605AG2-385 GEN
Solar/Wind Harmer
6.24
942871AE2-306 GEN
Solar/Wind Harmer
1.047
270391AF1-285 GEN3
Solar/Wind Harmer
0.537
253338AC1-165 GEN
Solar/Wind Harmer
1.242
253333AC1-068 GEN
Solar/Wind Harmer
1.197
270485AE1-090_GEN
Solar/Wind Harmer
0.69
270273AD2-016 GEN
Solar/Wind Harmer
3.033
972173AH1-669 GEN
Solar/Wind Harmer
5.671
270291AC1-194 GEN
Solar/Wind Harmer
11.744
253415AE1-040 GEN
Solar/Wind Harmer
1.248
270512AE1-227 GEN2
Solar/Wind Harmer
2.315
970065AG2-057 GEN
Solar/Wind Harmer
1.09
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.065
957541AF2-048 GEN
Solar/Wind Harmer
1.721
253406AD2-031_GEN
Solar/Wind Harmer
1.388
270491AE1-102 GEN2
Solar/Wind Harmer
1.404
270377AD1-106 GEN
Solar/Wind Harmer
6.655
971191AH1-055 GEN
Solar/Wind Harmer
23.692
253316AC1-085 GEN3
Solar/Wind Harmer
9.013
253433AC1-085 GEN1
Solar/Wind Harmer
5.721
946181AF1-283 GEN
Solar/Wind Harmer
13.988
270191TR4_S_V150
Solar/Wind Harmer
3.223
270247TR4_N_V136
Solar/Wind Harmer
0.914
959331AF2-224 GEN
Solar/Wind Harmer
10.743
965021AG1-366 GEN
Solar/Wind Harmer
2.498
270588AE1-091_GEN
Solar/Wind Harmer
11.792
958091AF2-103 GEN
Solar/Wind Harmer
0.173
944531AF1-118 GEN
Solar/Wind Harmer
37.418
270043AE2-236 GEN
Solar/Wind Harmer
5.874
270258AD1-119 GEN
Solar/Wind Harmer
2.962
971617AH1-308 GEN
Solar/Wind Harmer
6.179
25196608WSDLE5
Adder
9.087
252510AF1-249 C
Solar/Wind Harmer
0.443
962031AG1-047 GEN
Solar/Wind Harmer
3.204
957741AF2-068 GEN
Solar/Wind Harmer
15.899
25194608D.CRK4
Adder
1.742
270222AC2-111 GEN
Solar/Wind Harmer
8.63
970031AG2-029 GEN
Solar/Wind Harmer
31.748
270044AE2-322 C
Solar/Wind Harmer
1.39
270404AC1-167 GEN
Solar/Wind Harmer
1.158
24642205MAYFLWER
Adder
0.665
25196008MFTGT1
Adder
1.406
247604X1-042
Adder
0.433
274752CRETE EC ;2U
Adder
8.485
274753CRETE EC ;3U
Adder
8.485
274772LINCOLN ;3U
Adder
8.684
274724RIVER EC ;11
Adder
18.221
24728705AND G3
Adder
8.223
274802UNIV PARK;5U
Adder
5.976
24728505AND G1
Adder
3.932
274826FISK ;BP
Adder
11.216
274800UNIV PARK;3U
Adder
5.972
972038AH1-567 GEN2
Adder
0.374
972228AH1-698 GEN2
Adder
3.794
274676JOLIET 29;8U
Adder
30.215
274729ELWOOD EC;1P
Adder
16.784
274730ELWOOD EC;6P
Adder
16.784
274734ELWOOD EC;8P
Adder
16.784
274736ELWOOD EC;9P
Adder
16.784
274682WAUKEGAN ;7U
Adder
9.459
964991AG1-363 GEN
Solar/Wind Helper
5.14
316097T157 G90
Solar/Wind Helper
1.505
23750701CROSSCHOOL
Solar/Wind Helper
1.501
238118U2-030_1
Solar/Wind Helper
0.341
238127S14_GEN_2
Solar/Wind Helper
0.826
238148AE2-230_GEN2
Solar/Wind Helper
0.497
237080AD1-060 GEN
Solar/Wind Helper
0.342
237038AE2-054 C
Solar/Wind Helper
0.272
235062AE1-101 C1
Solar/Wind Helper
1.661
23779801AA1-109
Solar/Wind Helper
0.193
237048AF1-022 C
Solar/Wind Helper
0.177
223401AF1-299 GEN
Solar/Wind Helper
0.368
316006AB2-029 C
Solar/Wind Helper
0.117
966131AG1-482 GEN
Solar/Wind Helper
0.077
233930AB2-032 GEN
Solar/Wind Helper
0.381
233915AB1-141 GEN
Solar/Wind Helper
0.503
232422X3-066 FULL
Solar/Wind Helper
0.114
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
233998TM1NIN_3.36
Solar/Wind Helper
0.262
232404W1-003 C
Solar/Wind Helper
0.508
232428Y3-058 C
Solar/Wind Helper
0.338
232434Z2-077 GEN
Solar/Wind Helper
0.127
233954AC2-188 GEN
Solar/Wind Helper
0.233
233950AC2-186 GEN
Solar/Wind Helper
0.116
233972AC1-094 C
Solar/Wind Helper
0.303
316045AC1-158 PL2
Solar/Wind Helper
4.142
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.23
228728W1-130C
Solar/Wind Helper
0.054
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219904AC1-010 C
Solar/Wind Helper
0.06
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.131
20720728JCB_W1-129
Solar/Wind Helper
0.057
316254AC1-120 GEN1
Solar/Wind Helper
1.061
207445AB1-138_GEN
Solar/Wind Helper
0.104
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.31
20715228NPK_W1-113
Solar/Wind Helper
0.078
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.496
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
207437AD2-070 GEN
Solar/Wind Helper
0.138
207518AF1-320_GEN
Solar/Wind Helper
1.573
20671928W4-073
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.03
970513AG2-328 GEN
Solar/Wind Harmer
3.726
970517AG2-330 GEN
Solar/Wind Harmer
3.379
270119AB2-067 GEN1
50/50
7.063
270120AB2-067 GEN2
50/50
7.063
24318905MLG2
50/50
7.074
270471AD2-092_GEN
Solar/Wind Harmer
4.466
946101AF1-275 GEN
Solar/Wind Harmer
1.816
942861AE2-305 GEN
Solar/Wind Harmer
9.089
970077AG2-063 GEN
Solar/Wind Harmer
6.24
270224U2-072_GEN2
Solar/Wind Harmer
2.282
270227U2-072_GEN3
Solar/Wind Harmer
2.282
270228U2-072_GEN4
Solar/Wind Harmer
2.282
270231U2-072_GEN5
Solar/Wind Harmer
2.282
938701AE1-092 GEN
Solar/Wind Harmer
23.829
964601AG1-323 GEN
Solar/Wind Harmer
3.66
964601AG1-323 GEN
Solar/Wind Harmer
1.702
270518AE2-148 GEN
Solar/Wind Harmer
13.889
972269AH1-719 GEN
Adder
2.587
972159AH1-661 GEN
Adder
1.119
253378AE2-206_GEN
Solar/Wind Harmer
4.007
276820AF1-078_GEN
Solar/Wind Harmer
1.78
971199AH1-059 GEN
Solar/Wind Harmer
4.433
241960AC2-195 GEN
Solar/Wind Harmer
3.073
25326509SID D
Adder
1.452
970879AG2-548 GEN
Solar/Wind Harmer
6.78
971073AG2-665 GEN
Solar/Wind Harmer
6.78
971073AG2-665 GEN
Solar/Wind Harmer
4.73
25326109MON D
Adder
1.444
25322209TAIT E
Adder
10.653
25322209TAIT E
Adder
10.414
971201AH1-060 GEN
Solar/Wind Harmer
2.181
253370AE2-315 SEC1
Adder
2.184
253394AE2-221_GEN
Solar/Wind Harmer
4.918
253398AE2-221_GEN2
Solar/Wind Harmer
4.918
246938BC-WTG3
Solar/Wind Harmer
4.299
246937BC-WTG2
Solar/Wind Harmer
4.226
971231AH1-075 GEN
Solar/Wind Harmer
0.862
253317AC1-085 GEN4
Solar/Wind Harmer
9.013
970611AG2-400 GEN
Solar/Wind Harmer
10.743
270007AE1-245 C
Solar/Wind Harmer
6.358
942801AE2-298 GEN
Solar/Wind Harmer
1.622
962581AG1-107 GEN
Solar/Wind Harmer
5.365
961491AF2-440 GEN
Solar/Wind Harmer
2.229
25183208HLCRTG
Solar/Wind Harmer
6.449
944541AF1-119 GEN
Solar/Wind Harmer
4.453
960971AF2-388 GEN
Solar/Wind Harmer
11.621
942221AE2-234 GEN
Solar/Wind Harmer
0.778
252519AF1-045_GEN
Solar/Wind Harmer
6.447
252516AE2-318_GEN
Solar/Wind Harmer
4.918
247621Y3-024
Adder
0.256
970883AG2-550 GEN
Solar/Wind Harmer
10.602
970885AG2-551 GEN
Solar/Wind Harmer
2.465
270201AC2-176 GEN
Solar/Wind Harmer
5.449
25194408D.CRK1
Adder
8.013
25194508D.CRK3
Adder
1.498
964611AG1-324 GEN
Solar/Wind Harmer
1.248
964611AG1-324 GEN
Solar/Wind Harmer
0.554
252509AD1-136 GEN
Solar/Wind Harmer
0.271
247620Y3-023
Adder
0.484
24728805RICHG1
Adder
3.968
24728905RICHG2
Adder
3.968
274770LINCOLN ;1U
Adder
8.684
274771LINCOLN ;2U
Adder
8.684
274808UNIV PK N;4U
Adder
5.122
274803UNIV PARK;6U
Adder
5.976
972259AH1-714 GEN
Adder
19.527
274674JOLIET 9 ;6U
Adder
15.72
274696ROCKY RD ;4P
Adder
11.549
274695ROCKY RD ;2P
Adder
11.282
274693ROCKY RD ;1P
Adder
11.171
274697ROCKY RD ;3P
Adder
3.065
23585401KL_K28_T16
Solar/Wind Helper
1.478
238120AE2-309 GEN
Solar/Wind Helper
0.524
238175AF1-290_GEN
Solar/Wind Helper
0.153
238169AE2-226 GEN1
Solar/Wind Helper
0.702
238170AE2-226 GEN2
Solar/Wind Helper
0.702
235020AA1-095 C
Solar/Wind Helper
0.053
23777901MDS_W4-102
Solar/Wind Helper
0.177
237034AC2-136 C
Solar/Wind Helper
0.227
237002AB1-128_GEN
Solar/Wind Helper
0.443
235063AE1-101 C2
Solar/Wind Helper
1.661
237001AB1-127_GEN
Solar/Wind Helper
0.442
23777801MSM_W1-116
Solar/Wind Helper
0.114
237025AB1-124 C
Solar/Wind Helper
0.164
237006AB1-125 GEN
Solar/Wind Helper
0.123
226929AD2-058 GEN
Solar/Wind Helper
0.099
205916AD1-020 GEN
Solar/Wind Helper
1.715
20390526W1-045 C
Solar/Wind Helper
0.35
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
233987AB2-037 GEN
Solar/Wind Helper
2.344
233933AB2-153 GEN
Solar/Wind Helper
0.233
232424Y1-079 C
Solar/Wind Helper
0.116
233944AB2-135 GEN
Solar/Wind Helper
0.589
233946AB2-136 GEN
Solar/Wind Helper
0.569
234036AF2-325 C
Solar/Wind Helper
0.042
233901CHERRYDALE C
Solar/Wind Helper
0.233
232408W1-005 C
Solar/Wind Helper
0.508
232410W1-006 C
Solar/Wind Helper
0.508
233939AC1-091 C
Solar/Wind Helper
0.35
233970AC1-092 C
Solar/Wind Helper
0.35
315651AD1-115 GEN
Solar/Wind Helper
0.785
316447AC1-158 HLD
Solar/Wind Helper
2.848
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.04
219921AF1-264
Solar/Wind Helper
0.051
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.082
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.19
20716928W4-060COL
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.016
20673828FLE_V3-070
Solar/Wind Helper
0.091
207442AE1-156 GEN
Solar/Wind Helper
0.326
20676128MHD_W3-029
Solar/Wind Helper
0.096
20671828STAW2-080
Solar/Wind Helper
0.027
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
207471AF2-354 C
Solar/Wind Helper
0.169
20674928WA_W3-044
Solar/Wind Helper
0.098
964851AG1-348 GEN
Solar/Wind Helper
0.081
20676228FRD_X1-012
Solar/Wind Helper
0.092
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.045
211065PSPA IPP
Solar/Wind Helper
0.152
211065PSPA IPP
Solar/Wind Helper
0.152
970321AG2-212 GEN
Solar/Wind Harmer
3.726
962771AG1-126 GEN
Solar/Wind Harmer
40.976
972239AH1-704 GEN
Adder
2.69
270054AF2-122 C O1
Solar/Wind Harmer
3.996
270459AD2-067 GEN
Solar/Wind Harmer
10.248
961821AG1-024 GEN
Solar/Wind Harmer
10.404
270520AE2-214 GEN
Solar/Wind Harmer
7.276
270284AF1-227 GEN1
Solar/Wind Harmer
6.79
270286AF1-227 GEN2
Solar/Wind Harmer
2.512
270287AF1-227 GEN3
Solar/Wind Harmer
2.512
253383AE2-342_GEN
Solar/Wind Harmer
1.045
241973AD2-163_GEN1
Solar/Wind Harmer
2.331
945631AF1-228 GEN
Solar/Wind Harmer
5.463
943861AF1-054 GEN
Solar/Wind Harmer
4.486
943851AF1-053 GEN
Solar/Wind Harmer
2.168
270156DARBY CT1
Adder
10.419
270157DARBY CT2
Adder
10.393
270158DARBY CT3
Adder
10.228
970689AG2-444 GEN
Solar/Wind Harmer
18.827
270578AF1-285 GEN2
Solar/Wind Harmer
0.537
270432AC2-029 GEN
Solar/Wind Harmer
8.049
940611AE2-048 GEN
Solar/Wind Harmer
25.14
941391AE2-136 GEN
Solar/Wind Harmer
13.027
270302AB2-170 GEN
Solar/Wind Harmer
9.546
270317AD1-130_GEN
Solar/Wind Harmer
3.659
270269AC2-059
Solar/Wind Harmer
10.605
241972AD1-140 GEN
Solar/Wind Harmer
5.021
958581AF2-149 GEN
Solar/Wind Harmer
4.743
970179AG2-119 GEN
Solar/Wind Harmer
8.842
270340AC2-060 GEN
Solar/Wind Harmer
3.346
970879AG2-548 GEN
Solar/Wind Harmer
4.73
253372AE2-315 SEC3
Adder
2.065
253372AE2-315 SEC3
Adder
2.065
25306009OHH W.
Adder
3.133
253349AC2-067 GEN
Solar/Wind Harmer
5.407
253400AC2-068 GEN
Solar/Wind Harmer
2.174
957201AF2-014 GEN
Solar/Wind Harmer
4.898
270435AC2-044 GEN
Solar/Wind Harmer
2.16
965051AG1-369 GEN
Solar/Wind Harmer
5.365
965041AG1-368 GEN
Solar/Wind Harmer
10.719
247607V1-011 GEN
Solar/Wind Harmer
4.239
971567AH1-282 GEN
Solar/Wind Harmer
16.075
966831AG1-554 GEN
Solar/Wind Harmer
1.28
971989AH1-539 GEN
Solar/Wind Harmer
13.838
24729505KEY G4
Adder
6.925
963791AG1-232 GEN
Solar/Wind Harmer
14.411
270071AF1-092 GEN
Solar/Wind Harmer
15.995
971985AH1-537 GEN
Solar/Wind Harmer
18.996
958711AF2-162 GEN
Solar/Wind Harmer
1.076
270024AE2-089 GEN
Solar/Wind Harmer
4.988
270367AC2-061_GEN
Solar/Wind Harmer
3.378
965101AG1-375 GEN
Solar/Wind Harmer
10.618
971673AH1-337 GEN
Solar/Wind Harmer
4.878
252524AE2-267 GEN
Solar/Wind Harmer
1.672
25196408WSDLE3
Adder
9.354
25196308WSDLE2
Adder
9.273
25196208WSDLE1
Adder
9.25
25196708WSDLE6
Adder
9.227
25196508WSDLE4
Adder
8.994
971029AG2-637 GEN
Solar/Wind Harmer
15.905
270543AE2-219 C
Solar/Wind Harmer
5.429
961761AG1-017 GEN
Solar/Wind Harmer
0.454
945581AF1-223 GEN
Solar/Wind Harmer
4.803
270297AD1-101 GEN
Solar/Wind Harmer
2.947
944031AF1-071 GEN
Solar/Wind Harmer
1.064
25196108MFTGT2
Adder
1.6
25196108MFTGT2
Adder
1.486
274775LINCOLN ;6U
Adder
8.684
274776LINCOLN ;7U
Adder
8.684
274777LINCOLN ;8U
Adder
8.684
274814UNIV PK N;0U
Adder
5.189
274807UNIV PK N;3U
Adder
5.178
274805UNIV PK N;1U
Adder
5.156
274811UNIV PK N;7U
Adder
5.144
972037AH1-567 GEN1
Adder
0.188
274827FISK ;RP
Adder
7.949
972227AH1-698 GEN1
Adder
2.671
274687WILL CNTY;4U
Adder
28.551
274687WILL CNTY;4U
Adder
28.551
274675JOLIET 29;7U
Adder
31.334
274675JOLIET 29;7U
Adder
30.215
274731ELWOOD EC;2P
Adder
16.784
274733ELWOOD EC;3P
Adder
16.784
274735ELWOOD EC;4P
Adder
16.784
274728ELWOOD EC;5P
Adder
16.784
972203AH1-686 GEN
Adder
2.341
274746AC1-111 G10
Adder
5.685
274744AC1-111 GEN8
Adder
5.685
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238126S14_GEN_1
Solar/Wind Helper
0.826
238152AF2-075_GEN
Solar/Wind Helper
0.708
238208AF1-136 C
Solar/Wind Helper
0.22
23546401DTGZ2-030
Solar/Wind Helper
0.089
237085AD2-009_GEN
Solar/Wind Helper
1.65
3138216PACIFIC
Solar/Wind Helper
0.044
316411AF1-147_GEN1
Solar/Wind Helper
0.889
316415AF1-147_GEN2
Solar/Wind Helper
0.889
23750501ELLIOTTS
Solar/Wind Helper
0.637
959381AF2-229 GEN
Solar/Wind Helper
0.358
3141426STAFORD
Solar/Wind Helper
0.052
960921AF2-383 GEN
Solar/Wind Helper
0.182
205943AE1-185 GEN
Solar/Wind Helper
0.51
205932AD2-116_GEN
Solar/Wind Helper
0.509
205956AE1-196_GEN
Solar/Wind Helper
0.509
233935AB2-179 C
Solar/Wind Helper
1.27
232436AB1-176 C
Solar/Wind Helper
0.044
233923SMA
Solar/Wind Helper
0.959
234033AF1-007_GEN
Solar/Wind Helper
7.028
233990AG1-397 GEN
Solar/Wind Helper
0.03
232432Z2-076 GEN
Solar/Wind Helper
0.067
964001AG1-254 GEN
Solar/Wind Helper
0.956
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.115
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.08
203975AE1-071-GEN
Solar/Wind Helper
2.5
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.29
219620RIDERU C
Solar/Wind Helper
0.001
316164AC1-076 GEN
Solar/Wind Helper
1.097
20675528CPH_W2-050
Solar/Wind Helper
0.087
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
218524CNTRALGAS1 C
Solar/Wind Helper
0.161
966261AG1-495 GEN
Solar/Wind Helper
0.081
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20675928HOL_W4-097
Solar/Wind Helper
0.05
20674828DL_W4-046
Solar/Wind Helper
0.008
207484AF2-139 C O1
Solar/Wind Helper
0.084
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.137
20675128HRM_W1-127
Solar/Wind Helper
0.03
209116AE2-175 GEN
Solar/Wind Helper
1.781
LAGNLTFEXP_LAGN->PJM
CLTF
14.855
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.816
TVALTFEXP_TVA->PJM
CLTF
7.302
CPLELTFEXP_CPLE->PJM
CLTF
0.627
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.944
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.216
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.135
MECLTFEXP_MEC->PJM
CLTF
15.918
SIGELTFEXP_SIGE->PJM
CLTF
0.506
NYPJM->LTFIMP_NY
CLTF
4.803
LGEELTFEXP_LGEE->PJM
CLTF
6.756
WECLTFEXP_WEC->PJM
CLTF
3.828
AG2-052LTFEXP_AG2-052->PJM
LTF
0.24
AH1-155LTFEXP_AH1-155->PJM
LTF
0.36

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-007A_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-007A_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:130.62 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4870.98
MW Contribution:0.86
Bus #Bus NameTypeMW Contribution
270119AB2-067 GEN1
50/50
7.059
270120AB2-067 GEN2
50/50
7.059
24318905MLG2
50/50
7.071
270471AD2-092_GEN
Solar/Wind Harmer
0.006
942861AE2-305 GEN
Solar/Wind Harmer
6.335
970077AG2-063 GEN
Solar/Wind Harmer
4.631
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
938701AE1-092 GEN
Solar/Wind Harmer
12.917
971655AH1-328 GEN
Solar/Wind Harmer
2.854
964601AG1-323 GEN
Solar/Wind Harmer
3.215
964601AG1-323 GEN
Solar/Wind Harmer
2.143
270518AE2-148 GEN
Solar/Wind Harmer
0.691
972269AH1-719 GEN
Adder
2.584
972159AH1-661 GEN
Adder
1.118
253378AE2-206_GEN
Solar/Wind Harmer
0.004
276820AF1-078_GEN
Solar/Wind Harmer
0.002
970329AG2-216 GEN
Solar/Wind Harmer
3.354
971199AH1-059 GEN
Solar/Wind Harmer
3.09
241960AC2-195 GEN
Solar/Wind Harmer
0.006
25326509SID D
Adder
1.451
971073AG2-665 GEN
Solar/Wind Harmer
6.898
25326109MON D
Adder
1.443
25322209TAIT E
Adder
10.642
25322209TAIT E
Adder
10.403
971201AH1-060 GEN
Solar/Wind Harmer
1.52
253370AE2-315 SEC1
Adder
2.182
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
246938BC-WTG3
Solar/Wind Harmer
0.273
246937BC-WTG2
Solar/Wind Harmer
0.305
971231AH1-075 GEN
Solar/Wind Harmer
0.861
253317AC1-085 GEN4
Solar/Wind Harmer
0.005
970611AG2-400 GEN
Solar/Wind Harmer
7.488
970627AG2-408 GEN
Solar/Wind Harmer
2.246
270007AE1-245 C
Solar/Wind Harmer
0.002
962581AG1-107 GEN
Solar/Wind Harmer
0.002
25183208HLCRTG
Solar/Wind Harmer
0.012
944541AF1-119 GEN
Solar/Wind Harmer
0.497
960971AF2-388 GEN
Solar/Wind Harmer
4.347
970623AG2-406 GEN
Solar/Wind Harmer
1.356
942221AE2-234 GEN
Solar/Wind Harmer
0.037
252519AF1-045_GEN
Solar/Wind Harmer
6.44
252516AE2-318_GEN
Solar/Wind Harmer
5.712
247621Y3-024
Adder
0.255
970883AG2-550 GEN
Solar/Wind Harmer
7.389
970885AG2-551 GEN
Solar/Wind Harmer
2.463
270201AC2-176 GEN
Solar/Wind Harmer
0.001
25194408D.CRK1
Adder
8.004
25194508D.CRK3
Adder
1.496
970621AG2-405 GEN
Solar/Wind Harmer
1.351
964611AG1-324 GEN
Solar/Wind Harmer
0.553
252509AD1-136 GEN
Solar/Wind Harmer
0.037
970321AG2-212 GEN
Solar/Wind Harmer
3.191
270599AE1-208 GEN
Solar/Wind Harmer
6.737
270031AE2-169
Solar/Wind Harmer
4.042
270186AC1-089 GEN
Solar/Wind Harmer
0.004
270383AD1-128 GEN
Solar/Wind Harmer
0.004
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
970825AG2-519 GEN
Solar/Wind Harmer
8.127
247620Y3-023
Adder
0.484
960441AF2-335 GEN
Solar/Wind Harmer
7.33
24318805MLG1
50/50
10.095
23559001PLEAS1
50/50
6.1
270051AF1-062 GEN
50/50
11.821
270475AD2-096_GEN
50/50
7.141
970153AG2-106 GEN
Solar/Wind Harmer
22.046
961921AG1-034 GEN
Solar/Wind Harmer
7.615
241955AC1-078 GEN
Solar/Wind Harmer
0.007
24721905FLATG4
Adder
23.918
241974AD2-163_GEN2
Solar/Wind Harmer
0.006
942051AE2-217 GEN
Solar/Wind Harmer
14.671
970605AG2-385 GEN
Solar/Wind Harmer
4.899
270391AF1-285 GEN3
Solar/Wind Harmer
0.536
253338AC1-165 GEN
Solar/Wind Harmer
0.003
253333AC1-068 GEN
Solar/Wind Harmer
0.012
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270273AD2-016 GEN
Solar/Wind Harmer
0.821
972173AH1-669 GEN
Solar/Wind Harmer
3.952
270291AC1-194 GEN
Solar/Wind Harmer
6.106
253415AE1-040 GEN
Solar/Wind Harmer
0.003
270512AE1-227 GEN2
Solar/Wind Harmer
1.963
970065AG2-057 GEN
Solar/Wind Harmer
0.76
253370AE2-315 SEC1
Adder
2.182
253371AE2-315 SEC2
Adder
2.063
253406AD2-031_GEN
Solar/Wind Harmer
0.563
970191AG2-125 GEN
Solar/Wind Harmer
1.945
270491AE1-102 GEN2
Solar/Wind Harmer
0.979
270377AD1-106 GEN
Solar/Wind Harmer
2.855
971191AH1-055 GEN
Solar/Wind Harmer
19.26
253316AC1-085 GEN3
Solar/Wind Harmer
0.005
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
9.749
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.048
959331AF2-224 GEN
Solar/Wind Harmer
5.242
965021AG1-366 GEN
Solar/Wind Harmer
2.496
270588AE1-091_GEN
Solar/Wind Harmer
5.845
944531AF1-118 GEN
Solar/Wind Harmer
33.395
270043AE2-236 GEN
Solar/Wind Harmer
4.777
270258AD1-119 GEN
Solar/Wind Harmer
0.002
971617AH1-308 GEN
Solar/Wind Harmer
6.173
25196608WSDLE5
Adder
9.077
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
252510AF1-249 C
Solar/Wind Harmer
0.057
957741AF2-068 GEN
Solar/Wind Harmer
11.081
25194608D.CRK4
Adder
1.74
270222AC2-111 GEN
Solar/Wind Harmer
3.739
970031AG2-029 GEN
Solar/Wind Harmer
4.795
270404AC1-167 GEN
Solar/Wind Harmer
0.003
970513AG2-328 GEN
Solar/Wind Harmer
3.191
970517AG2-330 GEN
Solar/Wind Harmer
19.146
970349AG2-230 GEN
Solar/Wind Harmer
11.025
946031AF1-268 GEN
Solar/Wind Harmer
6.992
958821AF2-173 GEN
Solar/Wind Harmer
10.273
270004AE1-209 GEN
Solar/Wind Harmer
1.59
270437AC2-090 C
Solar/Wind Harmer
0.003
247643Z2-116 C
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.804
970291AG2-192 GEN
Solar/Wind Harmer
0.731
247642Z2-115 C
Solar/Wind Harmer
0.003
945111AF1-176 GEN
Solar/Wind Harmer
5.919
24642205MAYFLWER
Adder
0.665
25196008MFTGT1
Adder
1.405
270356AE2-297 GEN
Solar/Wind Harmer
0.01
24441205WTRV SLR C
Solar/Wind Harmer
0
247604X1-042
Adder
0.433
270535AF1-215 GEN1
Solar/Wind Harmer
0.009
964401AG1-302 GEN
Solar/Wind Harmer
0.001
970217AG2-149 GEN
Solar/Wind Harmer
6.268
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
7.196
970243AG2-164 GEN
Solar/Wind Harmer
4.205
970519AG2-331 GEN
Solar/Wind Harmer
18.687
970699AG2-449 GEN
Solar/Wind Harmer
1.797
274752CRETE EC ;2U
Adder
8.477
274753CRETE EC ;3U
Adder
8.477
958171AF2-111 GEN
Solar/Wind Harmer
17.94
274772LINCOLN ;3U
Adder
8.676
274724RIVER EC ;11
Adder
18.203
972167AH1-666 GEN
Solar/Wind Harmer
5.717
24728705AND G3
Adder
8.214
274802UNIV PARK;5U
Adder
5.97
24728505AND G1
Adder
3.927
276806AD2-047 C O1
Solar/Wind Harmer
4.047
970941AG2-585 GEN
Solar/Wind Harmer
8.927
274826FISK ;BP
Adder
11.205
274800UNIV PARK;3U
Adder
5.966
962771AG1-126 GEN
Solar/Wind Harmer
34.524
972239AH1-704 GEN
Adder
2.689
270054AF2-122 C O1
Solar/Wind Harmer
0.007
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
5.077
270520AE2-214 GEN
Solar/Wind Harmer
0.013
270284AF1-227 GEN1
Solar/Wind Harmer
0.011
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
253383AE2-342_GEN
Solar/Wind Harmer
0.003
241973AD2-163_GEN1
Solar/Wind Harmer
0.006
945631AF1-228 GEN
Solar/Wind Harmer
0
943861AF1-054 GEN
Solar/Wind Harmer
3.127
943851AF1-053 GEN
Solar/Wind Harmer
2.166
270156DARBY CT1
Adder
10.409
270157DARBY CT2
Adder
10.383
270158DARBY CT3
Adder
10.218
970689AG2-444 GEN
Solar/Wind Harmer
16.436
270578AF1-285 GEN2
Solar/Wind Harmer
0.536
270432AC2-029 GEN
Solar/Wind Harmer
3.553
940611AE2-048 GEN
Solar/Wind Harmer
19.602
941391AE2-136 GEN
Solar/Wind Harmer
11.042
270302AB2-170 GEN
Solar/Wind Harmer
0.005
270317AD1-130_GEN
Solar/Wind Harmer
0.011
971653AH1-327 GEN
Solar/Wind Harmer
1.117
270269AC2-059
Solar/Wind Harmer
0.005
241972AD1-140 GEN
Solar/Wind Harmer
0.854
970179AG2-119 GEN
Solar/Wind Harmer
6.883
270340AC2-060 GEN
Solar/Wind Harmer
0.009
970879AG2-548 GEN
Solar/Wind Harmer
6.898
253372AE2-315 SEC3
Adder
2.063
253372AE2-315 SEC3
Adder
2.063
25306009OHH W.
Adder
3.13
253349AC2-067 GEN
Solar/Wind Harmer
2.381
253400AC2-068 GEN
Solar/Wind Harmer
0.958
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
0.953
965051AG1-369 GEN
Solar/Wind Harmer
3.739
965041AG1-368 GEN
Solar/Wind Harmer
7.471
247607V1-011 GEN
Solar/Wind Harmer
0.001
971567AH1-282 GEN
Solar/Wind Harmer
11.206
971989AH1-539 GEN
Solar/Wind Harmer
3.215
963791AG1-232 GEN
Solar/Wind Harmer
10.044
24729505KEY G4
Adder
6.919
270071AF1-092 GEN
Solar/Wind Harmer
14.245
971985AH1-537 GEN
Solar/Wind Harmer
2.206
270024AE2-089 GEN
Solar/Wind Harmer
0.008
270367AC2-061_GEN
Solar/Wind Harmer
0.006
965101AG1-375 GEN
Solar/Wind Harmer
7.401
971673AH1-337 GEN
Solar/Wind Harmer
4.804
252524AE2-267 GEN
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
9.344
25196308WSDLE2
Adder
9.263
25196208WSDLE1
Adder
9.24
25196708WSDLE6
Adder
9.217
25196508WSDLE4
Adder
8.984
971029AG2-637 GEN
Solar/Wind Harmer
11.085
270543AE2-219 C
Solar/Wind Harmer
0.004
945581AF1-223 GEN
Solar/Wind Harmer
0.001
270297AD1-101 GEN
Solar/Wind Harmer
0.002
971347AH1-153 GEN
Solar/Wind Harmer
11.025
971609AH1-304 GEN
Solar/Wind Harmer
1.2
270240V3-007_GEN2
Solar/Wind Harmer
0.002
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
970115AG2-085 GEN
Solar/Wind Harmer
2.932
270594AE1-207 GEN
Solar/Wind Harmer
8.194
970289AG2-191 GEN
Solar/Wind Harmer
1.389
971771AH1-392 GEN
Solar/Wind Harmer
7.306
971619AH1-309 GEN
Solar/Wind Harmer
3.285
971769AH1-391 GEN
Solar/Wind Harmer
8.134
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
25196108MFTGT2
Adder
1.599
25196108MFTGT2
Adder
1.484
270536AF1-215 GEN2
Solar/Wind Harmer
0.009
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
4.302
971549AH1-272 GEN
Solar/Wind Harmer
14.865
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
8.676
274776LINCOLN ;7U
Adder
8.676
274777LINCOLN ;8U
Adder
8.676
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
274814UNIV PK N;0U
Adder
5.184
274807UNIV PK N;3U
Adder
5.173
274805UNIV PK N;1U
Adder
5.15
274811UNIV PK N;7U
Adder
5.139
972037AH1-567 GEN1
Adder
0.187
960591AF2-350 GEN
Solar/Wind Harmer
7.141
274827FISK ;RP
Adder
7.941
972227AH1-698 GEN1
Adder
2.669
963841AG1-237 GEN
Solar/Wind Harmer
3.09
972163AH1-664 GEN
Solar/Wind Harmer
7.933
972165AH1-665 GEN
Solar/Wind Harmer
6.354
274687WILL CNTY;4U
Adder
28.523
274687WILL CNTY;4U
Adder
28.523
274675JOLIET 29;7U
Adder
31.303
274675JOLIET 29;7U
Adder
30.185
274731ELWOOD EC;2P
Adder
16.768
274733ELWOOD EC;3P
Adder
16.768
274735ELWOOD EC;4P
Adder
16.768
274728ELWOOD EC;5P
Adder
16.768
970833AG2-524 GEN
Solar/Wind Harmer
7.824
970833AG2-524 GEN
Solar/Wind Harmer
5.216
274746AC1-111 G10
Adder
5.679
274744AC1-111 GEN8
Adder
5.679
972203AH1-686 GEN
Adder
2.338
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
276868AE1-113 GEN
Solar/Wind Harmer
1.414
276882AE2-255 GEN
Solar/Wind Harmer
0.824
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238126S14_GEN_1
Solar/Wind Helper
0.827
238152AF2-075_GEN
Solar/Wind Helper
0.707
238208AF1-136 C
Solar/Wind Helper
0.22
23546401DTGZ2-030
Solar/Wind Helper
0.089
237085AD2-009_GEN
Solar/Wind Helper
1.649
3138216PACIFIC
Solar/Wind Helper
0.044
316411AF1-147_GEN1
Solar/Wind Helper
0.888
316415AF1-147_GEN2
Solar/Wind Helper
0.888
23750501ELLIOTTS
Solar/Wind Helper
0.638
959381AF2-229 GEN
Solar/Wind Helper
0.357
3141426STAFORD
Solar/Wind Helper
0.052
960921AF2-383 GEN
Solar/Wind Helper
0.364
205943AE1-185 GEN
Solar/Wind Helper
0.509
205932AD2-116_GEN
Solar/Wind Helper
0.509
205956AE1-196_GEN
Solar/Wind Helper
0.509
233935AB2-179 C
Solar/Wind Helper
1.269
232436AB1-176 C
Solar/Wind Helper
0.044
233923SMA
Solar/Wind Helper
0.958
233990AG1-397 GEN
Solar/Wind Helper
0.27
232432Z2-076 GEN
Solar/Wind Helper
0.067
234033AF1-007_GEN
Solar/Wind Helper
7.02
964001AG1-254 GEN
Solar/Wind Helper
0.955
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.115
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.08
203975AE1-071-GEN
Solar/Wind Helper
2.498
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.096
270216AD2-079_GEN
Solar/Wind Harmer
0.001
971613AH1-306 GEN
Solar/Wind Harmer
3.512
24728805RICHG1
Adder
3.964
24728905RICHG2
Adder
3.964
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
14.589
961051AF2-396 GEN
Solar/Wind Harmer
9.726
270526AF1-158 GEN
Solar/Wind Harmer
0.009
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
9.095
965791AG1-447 GEN
Solar/Wind Harmer
6.67
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
970239AG2-162 GEN
Solar/Wind Harmer
1.797
274770LINCOLN ;1U
Adder
8.676
274771LINCOLN ;2U
Adder
8.676
966841AG1-555 GEN
Solar/Wind Harmer
0.81
274808UNIV PK N;4U
Adder
5.117
274803UNIV PARK;6U
Adder
5.97
274888KELLY CRK;1U
Solar/Wind Harmer
0.419
274887GEN-1.85
Solar/Wind Harmer
0.188
276843GEN-1.7
Solar/Wind Harmer
0.231
958011AF2-095 GEN
Solar/Wind Harmer
10.284
972259AH1-714 GEN
Adder
19.507
274674JOLIET 9 ;6U
Adder
15.704
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
970241AG2-163 GEN
Solar/Wind Harmer
4.144
958481AF2-142 GEN
Solar/Wind Harmer
10.621
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.958
971573AH1-285 GEN
Solar/Wind Harmer
1.319
274696ROCKY RD ;4P
Adder
11.537
274695ROCKY RD ;2P
Adder
11.271
274693ROCKY RD ;1P
Adder
11.16
274697ROCKY RD ;3P
Adder
3.062
958491AF2-143 GEN
Solar/Wind Harmer
10.588
274879MINONK ;1U
Solar/Wind Harmer
0.297
23585401KL_K28_T16
Solar/Wind Helper
1.482
238120AE2-309 GEN
Solar/Wind Helper
0.525
238175AF1-290_GEN
Solar/Wind Helper
0.153
238169AE2-226 GEN1
Solar/Wind Helper
0.701
238170AE2-226 GEN2
Solar/Wind Helper
0.701
235020AA1-095 C
Solar/Wind Helper
0.053
23777901MDS_W4-102
Solar/Wind Helper
0.177
237002AB1-128_GEN
Solar/Wind Helper
0.443
237034AC2-136 C
Solar/Wind Helper
0.227
235063AE1-101 C2
Solar/Wind Helper
1.659
237001AB1-127_GEN
Solar/Wind Helper
0.442
23777801MSM_W1-116
Solar/Wind Helper
0.114
237025AB1-124 C
Solar/Wind Helper
0.164
237006AB1-125 GEN
Solar/Wind Helper
0.123
226929AD2-058 GEN
Solar/Wind Helper
0.099
205916AD1-020 GEN
Solar/Wind Helper
1.713
20390526W1-045 C
Solar/Wind Helper
0.35
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
233987AB2-037 GEN
Solar/Wind Helper
2.342
233933AB2-153 GEN
Solar/Wind Helper
0.232
233944AB2-135 GEN
Solar/Wind Helper
0.588
232424Y1-079 C
Solar/Wind Helper
0.116
234036AF2-325 C
Solar/Wind Helper
0.042
233946AB2-136 GEN
Solar/Wind Helper
0.568
233901CHERRYDALE C
Solar/Wind Helper
0.232
232408W1-005 C
Solar/Wind Helper
0.507
232410W1-006 C
Solar/Wind Helper
0.507
233939AC1-091 C
Solar/Wind Helper
0.35
233970AC1-092 C
Solar/Wind Helper
0.35
315651AD1-115 GEN
Solar/Wind Helper
0.785
316447AC1-158 HLD
Solar/Wind Helper
2.845
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.04
219921AF1-264
Solar/Wind Helper
0.051
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.082
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.19
20716928W4-060COL
Solar/Wind Helper
0.051
218440SUMMTASSOC C
Solar/Wind Helper
0.016
20673828FLE_V3-070
Solar/Wind Helper
0.09
207442AE1-156 GEN
Solar/Wind Helper
0.326
20676128MHD_W3-029
Solar/Wind Helper
0.096
20671828STAW2-080
Solar/Wind Helper
0.027
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
207471AF2-354 C
Solar/Wind Helper
0.168
20674928WA_W3-044
Solar/Wind Helper
0.098
20676228FRD_X1-012
Solar/Wind Helper
0.092
964851AG1-348 GEN
Solar/Wind Helper
0.081
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.074
211065PSPA IPP
Solar/Wind Helper
0.151
211065PSPA IPP
Solar/Wind Helper
0.151
270166AC1-044 GEN3
50/50
7.059
23559101PLEAS2
50/50
6.1
962761AG1-125 GEN
Solar/Wind Harmer
34.524
970149AG2-104 GEN
Solar/Wind Harmer
37.287
970155AG2-107 GEN
Solar/Wind Harmer
22.046
270349AD2-093_GEN
Solar/Wind Harmer
0.006
24721705FLATG2
Adder
23.918
270159DARBY CT4
Adder
10.243
970593AG2-378 GEN
Solar/Wind Harmer
1.812
270223U2-072_GEN1
Solar/Wind Harmer
0.001
253343AC1-166 GEN
Solar/Wind Harmer
0.003
253325AC1-069 GEN
Solar/Wind Harmer
0.012
270462AD2-086
Solar/Wind Harmer
0.017
971995AH1-542 GEN
Solar/Wind Harmer
2.906
270263AC1-001 GEN
Solar/Wind Harmer
0.786
270510AE1-227 GEN1
Solar/Wind Harmer
1.963
25326309TAIT D
Adder
1.196
241813AF1-122_GEN
Solar/Wind Harmer
3.405
960071AF2-298 GEN
Solar/Wind Harmer
3.786
253370AE2-315 SEC1
Adder
2.182
253371AE2-315 SEC2
Adder
2.063
927014AC1-188 GEN
Solar/Wind Harmer
0.005
246936BC-WTG1
Solar/Wind Harmer
0.305
270489AE1-102 GEN1
Solar/Wind Harmer
0.979
965421AG1-410 GEN
Solar/Wind Harmer
22.57
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.499
247521TR3_G114
Solar/Wind Harmer
0.273
270246TR4_N_V150
Solar/Wind Harmer
0.048
965011AG1-365 GEN
Solar/Wind Harmer
7.488
24695305TIMB G C
Solar/Wind Harmer
0.002
965651AG1-433 GEN
Solar/Wind Harmer
2.174
958861AF2-177 GEN
Solar/Wind Harmer
3.207
247536S-71 GEN
Solar/Wind Harmer
0.297
25194608D.CRK4
Adder
1.74
945371AF1-202 GEN
Solar/Wind Harmer
0.001
252507AC2-088 GEN
Solar/Wind Harmer
0.335
270063AE2-323 C
Solar/Wind Harmer
0.006
970245AG2-165 GEN
Solar/Wind Harmer
3.191
970947AG2-589 GEN
Solar/Wind Harmer
0.245
270005AE1-210 C O1
Solar/Wind Harmer
1.59
965031AG1-367 GEN
Solar/Wind Harmer
7.338
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.378
970825AG2-519 GEN
Solar/Wind Harmer
2.603
25196808ZIMRHP
Adder
79.729
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
944231AF1-091 GEN
Solar/Wind Harmer
1.953
24639705ELKHART HY
Adder
0.161
270032AE2-172
Solar/Wind Harmer
4.877
970291AG2-192 GEN
Solar/Wind Harmer
0.95
945111AF1-176 GEN
Solar/Wind Harmer
13.03
270505AE1-170 C O1
Solar/Wind Harmer
7.665
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.805
276903AD2-071 C
Solar/Wind Harmer
8.137
25196008MFTGT1
Adder
1.45
247522W1-056 GEN
Solar/Wind Harmer
0.001
970773AG2-487 GEN
Solar/Wind Harmer
1.284
970373AG2-245 GEN
Solar/Wind Harmer
15.247
270055AF2-134 C O1
Solar/Wind Harmer
0.006
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.41
970515AG2-329 GEN
Solar/Wind Harmer
18.805
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
9.032
24791305MDL-5G
Solar/Wind Harmer
0.001
970333AG2-219 GEN
Solar/Wind Harmer
5.139
274751CRETE EC ;1U
Adder
8.477
274754CRETE EC ;4U
Adder
8.477
274773LINCOLN ;4U
Adder
8.676
274774LINCOLN ;5U
Adder
8.676
274723RIVER EC ;12
Adder
18.418
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
5.139
24728605AND G2
Adder
3.927
276776AD2-060 GEN
Solar/Wind Harmer
0.746
945681AF1-233 GEN
Solar/Wind Harmer
13.461
274801UNIV PARK;4U
Adder
5.966
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
31.303
274732ELWOOD EC;7P
Adder
16.768
274674JOLIET 9 ;6U
Adder
15.704
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
963741AG1-226 GEN
Solar/Wind Harmer
16.815
274745AC1-111 GEN9
Adder
5.679
939401AE1-172 GEN
Solar/Wind Harmer
5.301
276691AA1-018 GEN1
Solar/Wind Harmer
0.858
970091AG2-072 GEN
Adder
77.629
276901AD2-066 C O1
Solar/Wind Harmer
0.007
316095T157 G97
Solar/Wind Helper
1.504
23583801GRNGAP
Solar/Wind Helper
5.601
238185AF2-356 C
Solar/Wind Helper
2.646
238108AE1-109 GEN1
Solar/Wind Helper
0.114
235054AD2-180 GEN
Solar/Wind Helper
2.03
235531U2-073 GEN
Solar/Wind Helper
3.282
238117U2-030
Solar/Wind Helper
0.341
238147AE2-230_GEN1
Solar/Wind Helper
0.495
238149AF1-291A_GEN
Solar/Wind Helper
0.141
23751201ROTHROCK
Solar/Wind Helper
0.824
237061AD1-155 GEN
Solar/Wind Helper
0.053
23562501BACKB
Solar/Wind Helper
1.007
238221AF1-254 C O1
Solar/Wind Helper
0.274
235067AD1-061 GEN
Solar/Wind Helper
0.496
23751101LEADS_P59
Solar/Wind Helper
1.404
237030AB1-096 C
Solar/Wind Helper
0.071
3141196NOKESVL
Solar/Wind Helper
1.032
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.346
223402AF1-300 C
Solar/Wind Helper
0.367
205917AD1-020 ES
Solar/Wind Helper
0.368
233918AB1-142 GEN
Solar/Wind Helper
0.502
233982AB2-133 GEN
Solar/Wind Helper
0.358
233994AC2-023 GEN
Solar/Wind Helper
0.961
233996TM1833_GEN
Solar/Wind Helper
0.261
233997TMININ_4.2
Solar/Wind Helper
0.261
232406W1-004 FULL
Solar/Wind Helper
0.507
233940AF2-379 C
Solar/Wind Helper
0.062
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.232
233971AC1-093 C
Solar/Wind Helper
0.357
316044AC1-158 PL1
Solar/Wind Helper
1.293
316450AC1-158 RIC
Solar/Wind Helper
0.345
230430AE1-229_GEN
Solar/Wind Helper
3.372
230415AB2-049 C
Solar/Wind Helper
0.03
228729W2-030 C
Solar/Wind Helper
0.11
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.15
219291REEVESSOUT C
Solar/Wind Helper
0.011
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
219348LDSOLAR C
Solar/Wind Helper
0.114
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.063
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.353
219276PARKLANDSO C
Solar/Wind Helper
0.089
20714528FRN_Y2-051
Solar/Wind Helper
0.057
20720528MAN_W1-024
Solar/Wind Helper
0.028
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.027
219908AB1-139 C
Solar/Wind Helper
0.074
219249CENTRALDIV C
Solar/Wind Helper
0.01
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.089
971997AH1-543 GEN
Solar/Wind Harmer
2.724
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.29
219620RIDERU C
Solar/Wind Helper
0.001
316164AC1-076 GEN
Solar/Wind Helper
1.096
20675528CPH_W2-050
Solar/Wind Helper
0.087
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
218524CNTRALGAS1 C
Solar/Wind Helper
0.16
966261AG1-495 GEN
Solar/Wind Helper
0.081
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20675928HOL_W4-097
Solar/Wind Helper
0.05
207484AF2-139 C O1
Solar/Wind Helper
0.084
20674828DL_W4-046
Solar/Wind Helper
0.008
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.136
20675128HRM_W1-127
Solar/Wind Helper
0.029
209116AE2-175 GEN
Solar/Wind Helper
1.778
972038AH1-567 GEN2
Adder
0.373
972228AH1-698 GEN2
Adder
3.79
276897AD1-100 C
Solar/Wind Harmer
0.009
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
970707AG2-453 GEN
Solar/Wind Harmer
23.303
274676JOLIET 29;8U
Adder
30.185
276893AG1-478 C
Solar/Wind Harmer
0.282
274729ELWOOD EC;1P
Adder
16.768
274730ELWOOD EC;6P
Adder
16.768
274734ELWOOD EC;8P
Adder
16.768
274736ELWOOD EC;9P
Adder
16.768
943121AE2-341 GEN
Solar/Wind Harmer
11.888
943591AF1-030 GEN
Solar/Wind Harmer
7.906
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
270541AE2-072 C
Solar/Wind Harmer
0.009
274682WAUKEGAN ;7U
Adder
9.728
276805AD2-038 GEN
Solar/Wind Harmer
0.002
964991AG1-363 GEN
Solar/Wind Helper
5.136
316097T157 G90
Solar/Wind Helper
1.504
23750701CROSSCHOOL
Solar/Wind Helper
1.502
238118U2-030_1
Solar/Wind Helper
0.341
238127S14_GEN_2
Solar/Wind Helper
0.827
238148AE2-230_GEN2
Solar/Wind Helper
0.497
237080AD1-060 GEN
Solar/Wind Helper
0.342
237038AE2-054 C
Solar/Wind Helper
0.272
235062AE1-101 C1
Solar/Wind Helper
1.659
23779801AA1-109
Solar/Wind Helper
0.193
237048AF1-022 C
Solar/Wind Helper
0.177
223401AF1-299 GEN
Solar/Wind Helper
0.367
316006AB2-029 C
Solar/Wind Helper
0.117
966131AG1-482 GEN
Solar/Wind Helper
0.137
233930AB2-032 GEN
Solar/Wind Helper
0.381
233915AB1-141 GEN
Solar/Wind Helper
0.502
232422X3-066 FULL
Solar/Wind Helper
0.114
232428Y3-058 C
Solar/Wind Helper
0.338
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
233998TM1NIN_3.36
Solar/Wind Helper
0.261
232404W1-003 C
Solar/Wind Helper
0.507
232434Z2-077 GEN
Solar/Wind Helper
0.127
233954AC2-188 GEN
Solar/Wind Helper
0.232
233950AC2-186 GEN
Solar/Wind Helper
0.116
233972AC1-094 C
Solar/Wind Helper
0.302
316045AC1-158 PL2
Solar/Wind Helper
4.138
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.23
228728W1-130C
Solar/Wind Helper
0.054
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219904AC1-010 C
Solar/Wind Helper
0.06
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.131
20720728JCB_W1-129
Solar/Wind Helper
0.057
316254AC1-120 GEN1
Solar/Wind Helper
1.059
207445AB1-138_GEN
Solar/Wind Helper
0.104
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.13
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.31
20715228NPK_W1-113
Solar/Wind Helper
0.078
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.495
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
207437AD2-070 GEN
Solar/Wind Helper
0.138
207518AF1-320_GEN
Solar/Wind Helper
1.571
20671928W4-073
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.029
LAGNLTFEXP_LAGN->PJM
CLTF
14.837
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.802
TVALTFEXP_TVA->PJM
CLTF
7.293
CPLELTFEXP_CPLE->PJM
CLTF
0.624
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.816
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.078
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.1
MECLTFEXP_MEC->PJM
CLTF
15.901
SIGELTFEXP_SIGE->PJM
CLTF
0.505
NYPJM->LTFIMP_NY
CLTF
4.797
LGEELTFEXP_LGEE->PJM
CLTF
6.749
WECLTFEXP_WEC->PJM
CLTF
3.825
AG2-052LTFEXP_AG2-052->PJM
LTF
0.24
AH1-155LTFEXP_AH1-155->PJM
LTF
0.359

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-012_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-012_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:130.23 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4856.26
MW Contribution:0.91
Bus #Bus NameTypeMW Contribution
270166AC1-044 GEN3
50/50
7.033
23559101PLEAS2
50/50
5.443
270122AB2-093 CT
50/50
4.116
962761AG1-125 GEN
Solar/Wind Harmer
40.965
970149AG2-104 GEN
Solar/Wind Harmer
50.592
970155AG2-107 GEN
Solar/Wind Harmer
17.863
270349AD2-093_GEN
Solar/Wind Harmer
4.529
270223U2-072_GEN1
Solar/Wind Harmer
2.339
270578AF1-285 GEN2
Solar/Wind Harmer
1.43
270391AF1-285 GEN3
Solar/Wind Harmer
1.43
270159DARBY CT4
Adder
10.388
971995AH1-542 GEN
Solar/Wind Harmer
12.974
970593AG2-378 GEN
Solar/Wind Harmer
2.345
270462AD2-086
Solar/Wind Harmer
8.157
270510AE1-227 GEN1
Solar/Wind Harmer
2.893
24721705FLATG2
Adder
23.506
253343AC1-166 GEN
Solar/Wind Harmer
1.256
253325AC1-069 GEN
Solar/Wind Harmer
1.211
241813AF1-122_GEN
Solar/Wind Harmer
7.346
270263AC1-001 GEN
Solar/Wind Harmer
1.187
241847AF2-150_GEN
Solar/Wind Harmer
4.622
246936BC-WTG1
Solar/Wind Harmer
4.343
270489AE1-102 GEN1
Solar/Wind Harmer
1.443
965421AG1-410 GEN
Solar/Wind Harmer
33.256
970515AG2-329 GEN
Solar/Wind Harmer
16.033
25326309TAIT D
Adder
1.21
960071AF2-298 GEN
Solar/Wind Harmer
5.501
253370AE2-315 SEC1
Adder
2.206
253371AE2-315 SEC2
Adder
2.086
247521TR3_G114
Solar/Wind Harmer
3.699
270246TR4_N_V150
Solar/Wind Harmer
0.936
247522W1-056 GEN
Solar/Wind Harmer
2.477
24318805MLG1
50/50
10.022
23559001PLEAS1
50/50
5.443
270051AF1-062 GEN
50/50
11.999
970153AG2-106 GEN
Solar/Wind Harmer
17.863
961921AG1-034 GEN
Solar/Wind Harmer
15.919
241955AC1-078 GEN
Solar/Wind Harmer
8.948
241974AD2-163_GEN2
Solar/Wind Harmer
2.37
942051AE2-217 GEN
Solar/Wind Harmer
21.374
942871AE2-306 GEN
Solar/Wind Harmer
1.073
270391AF1-285 GEN3
Solar/Wind Harmer
0.55
960801AF2-371 GEN
Solar/Wind Harmer
2.991
964871AG1-351 GEN
Solar/Wind Harmer
2.065
970605AG2-385 GEN
Solar/Wind Harmer
6.332
270485AE1-090_GEN
Solar/Wind Harmer
0.709
270512AE1-227 GEN2
Solar/Wind Harmer
2.455
24721905FLATG4
Adder
23.506
253338AC1-165 GEN
Solar/Wind Harmer
1.256
253333AC1-068 GEN
Solar/Wind Harmer
1.211
970065AG2-057 GEN
Solar/Wind Harmer
1.148
270273AD2-016 GEN
Solar/Wind Harmer
3.061
972173AH1-669 GEN
Solar/Wind Harmer
5.721
270377AD1-106 GEN
Solar/Wind Harmer
6.988
270588AE1-091_GEN
Solar/Wind Harmer
12.311
270291AC1-194 GEN
Solar/Wind Harmer
11.854
253415AE1-040 GEN
Solar/Wind Harmer
1.258
961961AG1-039 GEN
Solar/Wind Harmer
3.188
270491AE1-102 GEN2
Solar/Wind Harmer
1.443
970217AG2-149 GEN
Solar/Wind Harmer
35.355
958091AF2-103 GEN
Solar/Wind Harmer
0.178
253303V4-073 C
Solar/Wind Harmer
0.128
253370AE2-315 SEC1
Adder
2.206
253371AE2-315 SEC2
Adder
2.086
270119AB2-067 GEN1
50/50
7.033
270120AB2-067 GEN2
50/50
7.033
24318905MLG2
50/50
7.475
270471AD2-092_GEN
Solar/Wind Harmer
4.529
946101AF1-275 GEN
Solar/Wind Harmer
1.842
938701AE1-092 GEN
Solar/Wind Harmer
24.483
270224U2-072_GEN2
Solar/Wind Harmer
2.339
270227U2-072_GEN3
Solar/Wind Harmer
2.339
270228U2-072_GEN4
Solar/Wind Harmer
2.339
270231U2-072_GEN5
Solar/Wind Harmer
2.339
942861AE2-305 GEN
Solar/Wind Harmer
9.223
964601AG1-323 GEN
Solar/Wind Harmer
3.753
964601AG1-323 GEN
Solar/Wind Harmer
1.746
972269AH1-719 GEN
Adder
2.7
970077AG2-063 GEN
Solar/Wind Harmer
6.332
972159AH1-661 GEN
Adder
1.166
270518AE2-148 GEN
Solar/Wind Harmer
14.068
971199AH1-059 GEN
Solar/Wind Harmer
4.644
241960AC2-195 GEN
Solar/Wind Harmer
3.219
971201AH1-060 GEN
Solar/Wind Harmer
2.296
253378AE2-206_GEN
Solar/Wind Harmer
4.086
276820AF1-078_GEN
Solar/Wind Harmer
1.815
971231AH1-075 GEN
Solar/Wind Harmer
0.905
25326509SID D
Adder
1.48
25326109MON D
Adder
1.461
246938BC-WTG3
Solar/Wind Harmer
4.418
246937BC-WTG2
Solar/Wind Harmer
4.343
970879AG2-548 GEN
Solar/Wind Harmer
6.827
971073AG2-665 GEN
Solar/Wind Harmer
6.827
971073AG2-665 GEN
Solar/Wind Harmer
4.763
25322209TAIT E
Adder
10.77
25322209TAIT E
Adder
10.528
270007AE1-245 C
Solar/Wind Harmer
6.539
942801AE2-298 GEN
Solar/Wind Harmer
1.667
253370AE2-315 SEC1
Adder
2.206
970611AG2-400 GEN
Solar/Wind Harmer
10.972
253394AE2-221_GEN
Solar/Wind Harmer
4.954
253398AE2-221_GEN2
Solar/Wind Harmer
4.954
253317AC1-085 GEN4
Solar/Wind Harmer
9.07
971677AH1-339 GEN
Solar/Wind Harmer
8.643
942221AE2-234 GEN
Solar/Wind Harmer
0.79
944541AF1-119 GEN
Solar/Wind Harmer
4.511
960971AF2-388 GEN
Solar/Wind Harmer
11.771
247621Y3-024
Adder
0.259
270201AC2-176 GEN
Solar/Wind Harmer
5.522
970883AG2-550 GEN
Solar/Wind Harmer
10.73
970885AG2-551 GEN
Solar/Wind Harmer
2.495
247620Y3-023
Adder
0.494
964611AG1-324 GEN
Solar/Wind Harmer
1.264
964611AG1-324 GEN
Solar/Wind Harmer
0.561
25194408D.CRK1
Adder
8.061
25194508D.CRK3
Adder
1.507
24728805RICHG1
Adder
4.003
24728905RICHG2
Adder
4.003
970935AG2-582 GEN
Adder
239.406
274770LINCOLN ;1U
Adder
8.792
274771LINCOLN ;2U
Adder
8.792
274808UNIV PK N;4U
Adder
5.188
274803UNIV PARK;6U
Adder
6.05
972259AH1-714 GEN
Adder
19.76
238175AF1-290_GEN
Solar/Wind Helper
0.168
238169AE2-226 GEN1
Solar/Wind Helper
0.772
238170AE2-226 GEN2
Solar/Wind Helper
0.772
238120AE2-309 GEN
Solar/Wind Helper
0.552
23585401KL_K28_T16
Solar/Wind Helper
1.529
235020AA1-095 C
Solar/Wind Helper
0.057
23777901MDS_W4-102
Solar/Wind Helper
0.191
237034AC2-136 C
Solar/Wind Helper
0.244
237002AB1-128_GEN
Solar/Wind Helper
0.475
235063AE1-101 C2
Solar/Wind Helper
1.776
237001AB1-127_GEN
Solar/Wind Helper
0.473
23777801MSM_W1-116
Solar/Wind Helper
0.122
237025AB1-124 C
Solar/Wind Helper
0.175
237006AB1-125 GEN
Solar/Wind Helper
0.131
226929AD2-058 GEN
Solar/Wind Helper
0.108
315651AD1-115 GEN
Solar/Wind Helper
0.876
316447AC1-158 HLD
Solar/Wind Helper
3.175
205916AD1-020 GEN
Solar/Wind Helper
1.761
20390526W1-045 C
Solar/Wind Helper
0.36
208835TUHI V3-051
Solar/Wind Helper
0.025
972239AH1-704 GEN
50/50
3.102
962771AG1-126 GEN
Solar/Wind Harmer
40.965
270459AD2-067 GEN
Solar/Wind Harmer
10.453
961821AG1-024 GEN
Solar/Wind Harmer
10.613
270054AF2-122 C O1
Solar/Wind Harmer
4.071
270284AF1-227 GEN1
Solar/Wind Harmer
6.912
270286AF1-227 GEN2
Solar/Wind Harmer
2.557
270287AF1-227 GEN3
Solar/Wind Harmer
2.557
270520AE2-214 GEN
Solar/Wind Harmer
7.382
253383AE2-342_GEN
Solar/Wind Harmer
1.062
241973AD2-163_GEN1
Solar/Wind Harmer
2.37
940611AE2-048 GEN
Solar/Wind Harmer
26.074
941391AE2-136 GEN
Solar/Wind Harmer
13.511
270578AF1-285 GEN2
Solar/Wind Harmer
0.55
943861AF1-054 GEN
Solar/Wind Harmer
4.552
943851AF1-053 GEN
Solar/Wind Harmer
2.2
945631AF1-228 GEN
Solar/Wind Harmer
5.537
270156DARBY CT1
Adder
10.556
270157DARBY CT2
Adder
10.53
270158DARBY CT3
Adder
10.362
270302AB2-170 GEN
Solar/Wind Harmer
9.805
270317AD1-130_GEN
Solar/Wind Harmer
3.759
970689AG2-444 GEN
Solar/Wind Harmer
19.055
270432AC2-029 GEN
Solar/Wind Harmer
8.138
958581AF2-149 GEN
Solar/Wind Harmer
4.968
970179AG2-119 GEN
Solar/Wind Harmer
9.26
270269AC2-059
Solar/Wind Harmer
10.704
241972AD1-140 GEN
Solar/Wind Harmer
5.084
971567AH1-282 GEN
Solar/Wind Harmer
16.984
966831AG1-554 GEN
Solar/Wind Harmer
1.34
971989AH1-539 GEN
Solar/Wind Harmer
14.49
270340AC2-060 GEN
Solar/Wind Harmer
3.371
957201AF2-014 GEN
Solar/Wind Harmer
5.033
270435AC2-044 GEN
Solar/Wind Harmer
2.219
970879AG2-548 GEN
Solar/Wind Harmer
4.763
247607V1-011 GEN
Solar/Wind Harmer
4.359
253372AE2-315 SEC3
Adder
2.086
253372AE2-315 SEC3
Adder
2.086
965051AG1-369 GEN
Solar/Wind Harmer
5.494
25306009OHH W.
Adder
3.166
270297AD1-101 GEN
Solar/Wind Harmer
3.056
965041AG1-368 GEN
Solar/Wind Harmer
10.974
253349AC2-067 GEN
Solar/Wind Harmer
5.466
253400AC2-068 GEN
Solar/Wind Harmer
2.198
963791AG1-232 GEN
Solar/Wind Harmer
14.679
270071AF1-092 GEN
Solar/Wind Harmer
16.242
24729505KEY G4
Adder
7.02
945641AF1-229 GEN
Solar/Wind Harmer
3.923
270024AE2-089 GEN
Solar/Wind Harmer
5.065
958711AF2-162 GEN
Solar/Wind Harmer
1.089
965101AG1-375 GEN
Solar/Wind Harmer
10.752
961761AG1-017 GEN
Solar/Wind Harmer
0.46
270543AE2-219 C
Solar/Wind Harmer
5.494
971029AG2-637 GEN
Solar/Wind Harmer
16.089
971673AH1-337 GEN
Solar/Wind Harmer
4.934
25196408WSDLE3
Adder
9.412
25196308WSDLE2
Adder
9.33
25196208WSDLE1
Adder
9.306
25196708WSDLE6
Adder
9.283
25196508WSDLE4
Adder
9.049
25196108MFTGT2
Adder
1.608
25196108MFTGT2
Adder
1.494
274775LINCOLN ;6U
Adder
8.792
274776LINCOLN ;7U
Adder
8.792
274777LINCOLN ;8U
Adder
8.792
274814UNIV PK N;0U
Adder
5.256
274807UNIV PK N;3U
Adder
5.245
274805UNIV PK N;1U
Adder
5.222
274811UNIV PK N;7U
Adder
5.21
972037AH1-567 GEN1
Adder
0.19
274827FISK ;RP
Adder
8.047
972227AH1-698 GEN1
Adder
2.704
274687WILL CNTY;4U
Adder
28.893
274687WILL CNTY;4U
Adder
28.893
274675JOLIET 29;7U
Adder
31.706
274675JOLIET 29;7U
Adder
30.574
274731ELWOOD EC;2P
Adder
16.983
274733ELWOOD EC;3P
Adder
16.983
274735ELWOOD EC;4P
Adder
16.983
274728ELWOOD EC;5P
Adder
16.983
238109AE1-109 GEN2
Solar/Wind Helper
0.121
238110AE1-109 GEN3
Solar/Wind Helper
0.121
238152AF2-075_GEN
Solar/Wind Helper
0.789
23546401DTGZ2-030
Solar/Wind Helper
0.099
238126S14_GEN_1
Solar/Wind Helper
0.867
238208AF1-136 C
Solar/Wind Helper
0.236
237085AD2-009_GEN
Solar/Wind Helper
1.767
3138216PACIFIC
Solar/Wind Helper
0.049
316411AF1-147_GEN1
Solar/Wind Helper
0.978
316415AF1-147_GEN2
Solar/Wind Helper
0.978
3141426STAFORD
Solar/Wind Helper
0.058
316164AC1-076 GEN
Solar/Wind Helper
1.225
23750501ELLIOTTS
Solar/Wind Helper
0.629
959381AF2-229 GEN
Solar/Wind Helper
0.367
960921AF2-383 GEN
Solar/Wind Helper
0.185
205943AE1-185 GEN
Solar/Wind Helper
0.518
205932AD2-116_GEN
Solar/Wind Helper
0.518
205956AE1-196_GEN
Solar/Wind Helper
0.518
233935AB2-179 C
Solar/Wind Helper
1.29
232436AB1-176 C
Solar/Wind Helper
0.045
233923SMA
Solar/Wind Helper
0.974
233990AG1-397 GEN
Solar/Wind Helper
0.031
232432Z2-076 GEN
Solar/Wind Helper
0.068
234033AF1-007_GEN
Solar/Wind Helper
7.137
964001AG1-254 GEN
Solar/Wind Helper
0.966
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.116
24695305TIMB G C
Solar/Wind Harmer
6.051
965011AG1-365 GEN
Solar/Wind Harmer
10.972
927014AC1-188 GEN
Solar/Wind Harmer
1.729
944231AF1-091 GEN
Solar/Wind Harmer
4.078
253432AC1-085 GEN2
Solar/Wind Harmer
0.29
946171AF1-282 GEN
Solar/Wind Harmer
10.828
270063AE2-323 C
Solar/Wind Harmer
2.376
965651AG1-433 GEN
Solar/Wind Harmer
5.885
958861AF2-177 GEN
Solar/Wind Harmer
11.752
247536S-71 GEN
Solar/Wind Harmer
4.346
960001AF2-291 GEN
Solar/Wind Harmer
3.244
945371AF1-202 GEN
Solar/Wind Harmer
7.479
24639705ELKHART HY
Adder
0.164
25194608D.CRK4
Adder
1.752
25196808ZIMRHP
Adder
80.188
23906502RICHG2&3
Adder
1.272
972301AH1-735 GEN
Adder
6.357
23906402RICHG1
Adder
1.271
25196008MFTGT1
Adder
1.459
274751CRETE EC ;1U
Adder
8.598
274754CRETE EC ;4U
Adder
8.598
274723RIVER EC ;12
Adder
18.677
274773LINCOLN ;4U
Adder
8.792
274774LINCOLN ;5U
Adder
8.792
274812UNIV PK N;8U
Adder
5.21
23920202STRYCT
Adder
1.444
274801UNIV PARK;4U
Adder
6.045
274676JOLIET 29;8U
Adder
31.706
274732ELWOOD EC;7P
Adder
2.004
23583801GRNGAP
Solar/Wind Helper
6.365
316095T157 G97
Solar/Wind Helper
1.705
238108AE1-109 GEN1
Solar/Wind Helper
0.121
238185AF2-356 C
Solar/Wind Helper
2.767
238147AE2-230_GEN1
Solar/Wind Helper
0.552
238149AF1-291A_GEN
Solar/Wind Helper
0.158
237061AD1-155 GEN
Solar/Wind Helper
0.06
235054AD2-180 GEN
Solar/Wind Helper
2.111
235531U2-073 GEN
Solar/Wind Helper
3.439
238117U2-030
Solar/Wind Helper
0.356
238221AF1-254 C O1
Solar/Wind Helper
0.295
235067AD1-061 GEN
Solar/Wind Helper
0.532
3141196NOKESVL
Solar/Wind Helper
1.141
23751201ROTHROCK
Solar/Wind Helper
0.819
237030AB1-096 C
Solar/Wind Helper
0.075
23562501BACKB
Solar/Wind Helper
0.997
226910AB2-157 C
Solar/Wind Helper
0.015
227287AC2-120 GEN
Solar/Wind Helper
0.375
223402AF1-300 C
Solar/Wind Helper
0.387
316044AC1-158 PL1
Solar/Wind Helper
1.443
316450AC1-158 RIC
Solar/Wind Helper
0.385
316170AC1-121 GEN2
Solar/Wind Helper
0.395
23751101LEADS_P59
Solar/Wind Helper
1.316
205917AD1-020 ES
Solar/Wind Helper
0.379
3132273ORANGE
Solar/Wind Helper
0.049
233918AB1-142 GEN
Solar/Wind Helper
0.511
233982AB2-133 GEN
Solar/Wind Helper
0.364
233994AC2-023 GEN
Solar/Wind Helper
0.977
233996TM1833_GEN
Solar/Wind Helper
0.266
233997TMININ_4.2
Solar/Wind Helper
0.266
232406W1-004 FULL
Solar/Wind Helper
0.516
3147666LOUISA
Solar/Wind Helper
0.551
233940AF2-379 C
Solar/Wind Helper
0.063
234015AF2-250 C
Solar/Wind Helper
0.039
233952AC2-187 GEN
Solar/Wind Helper
0.236
233971AC1-093 C
Solar/Wind Helper
0.363
230430AE1-229_GEN
Solar/Wind Helper
3.409
230415AB2-049 C
Solar/Wind Helper
0.031
228729W2-030 C
Solar/Wind Helper
0.112
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.151
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
219348LDSOLAR C
Solar/Wind Helper
0.115
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.064
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.057
219276PARKLANDSO C
Solar/Wind Helper
0.09
20714528FRN_Y2-051
Solar/Wind Helper
0.057
20720528MAN_W1-024
Solar/Wind Helper
0.028
966881AG1-559 GEN
Solar/Wind Helper
0.312
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.027
219249CENTRALDIV C
Solar/Wind Helper
0.01
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.089
270191TR4_S_V150
Solar/Wind Harmer
3.3
270247TR4_N_V136
Solar/Wind Harmer
0.936
959331AF2-224 GEN
Solar/Wind Harmer
10.972
965021AG1-366 GEN
Solar/Wind Harmer
2.552
270258AD1-119 GEN
Solar/Wind Harmer
3.051
253406AD2-031_GEN
Solar/Wind Harmer
1.398
270044AE2-322 C
Solar/Wind Harmer
1.435
270404AC1-167 GEN
Solar/Wind Harmer
1.194
957541AF2-048 GEN
Solar/Wind Harmer
1.725
270043AE2-236 GEN
Solar/Wind Harmer
5.98
944531AF1-118 GEN
Solar/Wind Harmer
37.943
253316AC1-085 GEN3
Solar/Wind Harmer
9.07
253433AC1-085 GEN1
Solar/Wind Harmer
5.758
946181AF1-283 GEN
Solar/Wind Harmer
14.077
970031AG2-029 GEN
Solar/Wind Harmer
32.394
971617AH1-308 GEN
Solar/Wind Harmer
6.274
270541AE2-072 C
Solar/Wind Harmer
4.881
971191AH1-055 GEN
Solar/Wind Harmer
23.635
962031AG1-047 GEN
Solar/Wind Harmer
3.246
957741AF2-068 GEN
Solar/Wind Harmer
16.111
25196608WSDLE5
Adder
9.143
24642205MAYFLWER
Adder
0.678
25194608D.CRK4
Adder
1.752
247604X1-042
Adder
0.444
23906502RICHG2&3
Adder
1.272
25196008MFTGT1
Adder
1.413
274752CRETE EC ;2U
Adder
8.598
274753CRETE EC ;3U
Adder
8.598
274724RIVER EC ;11
Adder
18.459
274772LINCOLN ;3U
Adder
8.792
274802UNIV PARK;5U
Adder
6.05
274826FISK ;BP
Adder
11.355
274800UNIV PARK;3U
Adder
6.045
972038AH1-567 GEN2
Adder
0.378
972228AH1-698 GEN2
Adder
3.84
274676JOLIET 29;8U
Adder
30.573
274729ELWOOD EC;1P
Adder
16.983
274730ELWOOD EC;6P
Adder
16.983
964991AG1-363 GEN
Solar/Wind Helper
5.557
316097T157 G90
Solar/Wind Helper
1.705
23750701CROSSCHOOL
Solar/Wind Helper
1.586
238148AE2-230_GEN2
Solar/Wind Helper
0.555
238127S14_GEN_2
Solar/Wind Helper
0.867
238118U2-030_1
Solar/Wind Helper
0.356
237080AD1-060 GEN
Solar/Wind Helper
0.367
237038AE2-054 C
Solar/Wind Helper
0.292
235062AE1-101 C1
Solar/Wind Helper
1.776
23779801AA1-109
Solar/Wind Helper
0.207
316006AB2-029 C
Solar/Wind Helper
0.13
223401AF1-299 GEN
Solar/Wind Helper
0.387
316045AC1-158 PL2
Solar/Wind Helper
4.618
316254AC1-120 GEN1
Solar/Wind Helper
1.184
237048AF1-022 C
Solar/Wind Helper
0.173
966131AG1-482 GEN
Solar/Wind Helper
0.079
233930AB2-032 GEN
Solar/Wind Helper
0.387
233915AB1-141 GEN
Solar/Wind Helper
0.511
232422X3-066 FULL
Solar/Wind Helper
0.116
233964AF2-378 GEN
Solar/Wind Helper
0.042
232426Y1-080 FULL
Solar/Wind Helper
0.039
233998TM1NIN_3.36
Solar/Wind Helper
0.266
232404W1-003 C
Solar/Wind Helper
0.516
232428Y3-058 C
Solar/Wind Helper
0.344
3147666LOUISA
Solar/Wind Helper
0.958
232434Z2-077 GEN
Solar/Wind Helper
0.129
233954AC2-188 GEN
Solar/Wind Helper
0.236
233950AC2-186 GEN
Solar/Wind Helper
0.118
233972AC1-094 C
Solar/Wind Helper
0.307
316192AB2-158 GEN
Solar/Wind Helper
1.608
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.232
228728W1-130C
Solar/Wind Helper
0.054
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219904AC1-010 C
Solar/Wind Helper
0.061
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.132
20720728JCB_W1-129
Solar/Wind Helper
0.057
207445AB1-138_GEN
Solar/Wind Helper
0.105
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20715228NPK_W1-113
Solar/Wind Helper
0.078
207454AA2-184 E
Solar/Wind Helper
0.311
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.497
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
207437AD2-070 GEN
Solar/Wind Helper
0.137
207518AF1-320_GEN
Solar/Wind Helper
1.568
20671928W4-073
Solar/Wind Helper
0.089
20675828AU_W4-064
Solar/Wind Helper
0.029
208835TUHI V3-051
Solar/Wind Helper
0.025
3132123MT JACKSON
Solar/Wind Helper
0.764
233987AB2-037 GEN
Solar/Wind Helper
2.381
233933AB2-153 GEN
Solar/Wind Helper
0.236
232424Y1-079 C
Solar/Wind Helper
0.118
233944AB2-135 GEN
Solar/Wind Helper
0.598
233946AB2-136 GEN
Solar/Wind Helper
0.577
234036AF2-325 C
Solar/Wind Helper
0.043
233901CHERRYDALE C
Solar/Wind Helper
0.236
232408W1-005 C
Solar/Wind Helper
0.516
232410W1-006 C
Solar/Wind Helper
0.516
233939AC1-091 C
Solar/Wind Helper
0.356
233970AC1-092 C
Solar/Wind Helper
0.356
966001AG1-469 GEN
Solar/Wind Helper
0.255
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.041
219921AF1-264
Solar/Wind Helper
0.052
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.083
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.19
20716928W4-060COL
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.016
20673828FLE_V3-070
Solar/Wind Helper
0.091
207442AE1-156 GEN
Solar/Wind Helper
0.326
20676128MHD_W3-029
Solar/Wind Helper
0.096
20671828STAW2-080
Solar/Wind Helper
0.027
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
207471AF2-354 C
Solar/Wind Helper
0.168
20674928WA_W3-044
Solar/Wind Helper
0.098
20676228FRD_X1-012
Solar/Wind Helper
0.091
964851AG1-348 GEN
Solar/Wind Helper
0.081
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.044
211065PSPA IPP
Solar/Wind Helper
0.15
211065PSPA IPP
Solar/Wind Helper
0.15
203975AE1-071-GEN
Solar/Wind Helper
2.53
219272CLEANLIGHT C
Solar/Wind Helper
0.026
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.081
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.292
219620RIDERU C
Solar/Wind Helper
0.001
20675528CPH_W2-050
Solar/Wind Helper
0.087
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
218524CNTRALGAS1 C
Solar/Wind Helper
0.161
966261AG1-495 GEN
Solar/Wind Helper
0.081
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20675928HOL_W4-097
Solar/Wind Helper
0.05
20674828DL_W4-046
Solar/Wind Helper
0.008
207484AF2-139 C O1
Solar/Wind Helper
0.084
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.136
20675128HRM_W1-127
Solar/Wind Helper
0.029
209116AE2-175 GEN
Solar/Wind Helper
1.768
945581AF1-223 GEN
Solar/Wind Harmer
0.763
LAGNLTFEXP_LAGN->PJM
CLTF
14.521
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.32
TVALTFEXP_TVA->PJM
CLTF
7.111
CBM West 2LTFEXP_CBM-W2->PJM
CBM
111.893
CBM West 1LTFEXP_CBM-W1->PJM
CBM
146.579
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.544
MECLTFEXP_MEC->PJM
CLTF
15.979
SIGELTFEXP_SIGE->PJM
CLTF
0.506
NYPJM->LTFIMP_NY
CLTF
4.554
LGEELTFEXP_LGEE->PJM
CLTF
6.753
WECLTFEXP_WEC->PJM
CLTF
3.866
AG2-052LTFEXP_AG2-052->PJM
LTF
0.243
AH1-155LTFEXP_AH1-155->PJM
LTF
0.364

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-008A_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-008A_SRT-SL
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:124.1 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4627.6
MW Contribution:0.83
Bus #Bus NameTypeMW Contribution
270166AC1-044 GEN3
50/50
6.869
23559101PLEAS2
50/50
5.385
270122AB2-093 CT
50/50
3.689
962761AG1-125 GEN
Solar/Wind Harmer
33.269
970149AG2-104 GEN
Solar/Wind Harmer
35.932
970155AG2-107 GEN
Solar/Wind Harmer
21.245
270349AD2-093_GEN
Solar/Wind Harmer
0.006
24721705FLATG2
Adder
22.865
270159DARBY CT4
Adder
9.89
970593AG2-378 GEN
Solar/Wind Harmer
1.75
270223U2-072_GEN1
Solar/Wind Harmer
0.001
253343AC1-166 GEN
Solar/Wind Harmer
0.003
253325AC1-069 GEN
Solar/Wind Harmer
0.012
270462AD2-086
Solar/Wind Harmer
0.016
971995AH1-542 GEN
Solar/Wind Harmer
2.81
270263AC1-001 GEN
Solar/Wind Harmer
0.758
270510AE1-227 GEN1
Solar/Wind Harmer
1.904
241813AF1-122_GEN
Solar/Wind Harmer
3.294
25326309TAIT D
Adder
1.153
960071AF2-298 GEN
Solar/Wind Harmer
3.651
253370AE2-315 SEC1
Adder
2.103
253371AE2-315 SEC2
Adder
1.989
927014AC1-188 GEN
Solar/Wind Harmer
0.004
246936BC-WTG1
Solar/Wind Harmer
0.295
270119AB2-067 GEN1
50/50
6.869
270120AB2-067 GEN2
50/50
6.869
24318905MLG2
50/50
6.89
270471AD2-092_GEN
Solar/Wind Harmer
0.006
942861AE2-305 GEN
Solar/Wind Harmer
6.118
970077AG2-063 GEN
Solar/Wind Harmer
4.471
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
938701AE1-092 GEN
Solar/Wind Harmer
12.484
971655AH1-328 GEN
Solar/Wind Harmer
2.758
964601AG1-323 GEN
Solar/Wind Harmer
3.106
964601AG1-323 GEN
Solar/Wind Harmer
2.071
270518AE2-148 GEN
Solar/Wind Harmer
0.667
972269AH1-719 GEN
Adder
2.501
972159AH1-661 GEN
Adder
1.082
253378AE2-206_GEN
Solar/Wind Harmer
0.004
276820AF1-078_GEN
Solar/Wind Harmer
0.002
970329AG2-216 GEN
Solar/Wind Harmer
3.237
971199AH1-059 GEN
Solar/Wind Harmer
2.99
241960AC2-195 GEN
Solar/Wind Harmer
0.006
970935AG2-582 GEN
Adder
242.403
25326509SID D
Adder
1.4
971073AG2-665 GEN
Solar/Wind Harmer
6.645
25326109MON D
Adder
1.391
971201AH1-060 GEN
Solar/Wind Harmer
1.471
25322209TAIT E
Adder
10.262
25322209TAIT E
Adder
10.031
24318805MLG1
50/50
9.842
23559001PLEAS1
50/50
5.385
270051AF1-062 GEN
50/50
11.434
970153AG2-106 GEN
Solar/Wind Harmer
21.245
961921AG1-034 GEN
Solar/Wind Harmer
7.364
241955AC1-078 GEN
Solar/Wind Harmer
0.007
241974AD2-163_GEN2
Solar/Wind Harmer
0.006
942051AE2-217 GEN
Solar/Wind Harmer
14.169
24721905FLATG4
Adder
22.865
970605AG2-385 GEN
Solar/Wind Harmer
4.731
270391AF1-285 GEN3
Solar/Wind Harmer
0.518
253338AC1-165 GEN
Solar/Wind Harmer
0.003
253333AC1-068 GEN
Solar/Wind Harmer
0.012
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270273AD2-016 GEN
Solar/Wind Harmer
0.792
972173AH1-669 GEN
Solar/Wind Harmer
3.811
270512AE1-227 GEN2
Solar/Wind Harmer
1.904
270291AC1-194 GEN
Solar/Wind Harmer
5.884
253415AE1-040 GEN
Solar/Wind Harmer
0.003
970065AG2-057 GEN
Solar/Wind Harmer
0.735
253370AE2-315 SEC1
Adder
2.103
253371AE2-315 SEC2
Adder
1.989
970191AG2-125 GEN
Solar/Wind Harmer
1.876
253406AD2-031_GEN
Solar/Wind Harmer
0.543
270491AE1-102 GEN2
Solar/Wind Harmer
0.945
270377AD1-106 GEN
Solar/Wind Harmer
2.761
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.047
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
9.394
959331AF2-224 GEN
Solar/Wind Harmer
5.057
965021AG1-366 GEN
Solar/Wind Harmer
2.408
270588AE1-091_GEN
Solar/Wind Harmer
5.649
972239AH1-704 GEN
50/50
2.78
962771AG1-126 GEN
Solar/Wind Harmer
33.269
270459AD2-067 GEN
Solar/Wind Harmer
0
270054AF2-122 C O1
Solar/Wind Harmer
0.007
961821AG1-024 GEN
Solar/Wind Harmer
4.91
270520AE2-214 GEN
Solar/Wind Harmer
0.013
270284AF1-227 GEN1
Solar/Wind Harmer
0.01
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
253383AE2-342_GEN
Solar/Wind Harmer
0.003
241973AD2-163_GEN1
Solar/Wind Harmer
0.006
945631AF1-228 GEN
Solar/Wind Harmer
0
943861AF1-054 GEN
Solar/Wind Harmer
3.02
943851AF1-053 GEN
Solar/Wind Harmer
2.092
270156DARBY CT1
Adder
10.05
270157DARBY CT2
Adder
10.026
270158DARBY CT3
Adder
9.866
270578AF1-285 GEN2
Solar/Wind Harmer
0.518
970689AG2-444 GEN
Solar/Wind Harmer
15.861
270432AC2-029 GEN
Solar/Wind Harmer
3.428
940611AE2-048 GEN
Solar/Wind Harmer
18.967
941391AE2-136 GEN
Solar/Wind Harmer
10.684
270302AB2-170 GEN
Solar/Wind Harmer
0.005
270317AD1-130_GEN
Solar/Wind Harmer
0.011
971653AH1-327 GEN
Solar/Wind Harmer
1.08
270269AC2-059
Solar/Wind Harmer
0.004
241972AD1-140 GEN
Solar/Wind Harmer
0.824
970179AG2-119 GEN
Solar/Wind Harmer
6.658
270340AC2-060 GEN
Solar/Wind Harmer
0.009
970879AG2-548 GEN
Solar/Wind Harmer
6.645
253372AE2-315 SEC3
Adder
1.989
253372AE2-315 SEC3
Adder
1.989
25306009OHH W.
Adder
3.018
253349AC2-067 GEN
Solar/Wind Harmer
2.296
253400AC2-068 GEN
Solar/Wind Harmer
0.923
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
0.92
965051AG1-369 GEN
Solar/Wind Harmer
3.609
971567AH1-282 GEN
Solar/Wind Harmer
10.843
247607V1-011 GEN
Solar/Wind Harmer
0.001
965041AG1-368 GEN
Solar/Wind Harmer
7.21
971989AH1-539 GEN
Solar/Wind Harmer
3.109
963791AG1-232 GEN
Solar/Wind Harmer
9.689
24729505KEY G4
Adder
6.671
270071AF1-092 GEN
Solar/Wind Harmer
13.737
270024AE2-089 GEN
Solar/Wind Harmer
0.008
971985AH1-537 GEN
Solar/Wind Harmer
2.123
965101AG1-375 GEN
Solar/Wind Harmer
7.135
270297AD1-101 GEN
Solar/Wind Harmer
0.002
270367AC2-061_GEN
Solar/Wind Harmer
0.006
971673AH1-337 GEN
Solar/Wind Harmer
4.631
971029AG2-637 GEN
Solar/Wind Harmer
10.686
270543AE2-219 C
Solar/Wind Harmer
0.004
252524AE2-267 GEN
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
9.002
25196308WSDLE2
Adder
8.924
25196208WSDLE1
Adder
8.902
25196708WSDLE6
Adder
8.879
25196508WSDLE4
Adder
8.656
945581AF1-223 GEN
Solar/Wind Harmer
0.001
971347AH1-153 GEN
Solar/Wind Harmer
10.632
971609AH1-304 GEN
Solar/Wind Harmer
1.157
270240V3-007_GEN2
Solar/Wind Harmer
0.002
970115AG2-085 GEN
Solar/Wind Harmer
2.826
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
270594AE1-207 GEN
Solar/Wind Harmer
7.898
971771AH1-392 GEN
Solar/Wind Harmer
7.046
970289AG2-191 GEN
Solar/Wind Harmer
1.339
971619AH1-309 GEN
Solar/Wind Harmer
3.169
971769AH1-391 GEN
Solar/Wind Harmer
7.844
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
25196108MFTGT2
Adder
1.54
25196108MFTGT2
Adder
1.43
270536AF1-215 GEN2
Solar/Wind Harmer
0.009
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
4.146
971549AH1-272 GEN
Solar/Wind Harmer
14.344
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
8.364
274776LINCOLN ;7U
Adder
8.364
274777LINCOLN ;8U
Adder
8.364
274814UNIV PK N;0U
Adder
4.998
274807UNIV PK N;3U
Adder
4.987
274805UNIV PK N;1U
Adder
4.965
274811UNIV PK N;7U
Adder
4.954
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
972037AH1-567 GEN1
Adder
0.181
960591AF2-350 GEN
Solar/Wind Harmer
6.884
274827FISK ;RP
Adder
7.655
972227AH1-698 GEN1
Adder
2.573
963841AG1-237 GEN
Solar/Wind Harmer
2.978
274687WILL CNTY;4U
Adder
27.495
274687WILL CNTY;4U
Adder
27.495
274675JOLIET 29;7U
Adder
30.175
274675JOLIET 29;7U
Adder
29.097
972163AH1-664 GEN
Solar/Wind Harmer
7.639
972165AH1-665 GEN
Solar/Wind Harmer
6.118
274731ELWOOD EC;2P
Adder
16.163
274733ELWOOD EC;3P
Adder
16.163
274735ELWOOD EC;4P
Adder
16.163
274728ELWOOD EC;5P
Adder
16.163
970833AG2-524 GEN
Solar/Wind Harmer
7.542
970833AG2-524 GEN
Solar/Wind Harmer
5.028
945641AF1-229 GEN
Solar/Wind Harmer
0.001
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
276868AE1-113 GEN
Solar/Wind Harmer
1.363
276882AE2-255 GEN
Solar/Wind Harmer
0.794
238109AE1-109 GEN2
Solar/Wind Helper
0.106
238110AE1-109 GEN3
Solar/Wind Helper
0.106
238152AF2-075_GEN
Solar/Wind Helper
0.683
23546401DTGZ2-030
Solar/Wind Helper
0.086
238208AF1-136 C
Solar/Wind Helper
0.211
238126S14_GEN_1
Solar/Wind Helper
0.766
237085AD2-009_GEN
Solar/Wind Helper
1.588
3138216PACIFIC
Solar/Wind Helper
0.043
316411AF1-147_GEN1
Solar/Wind Helper
0.86
316415AF1-147_GEN2
Solar/Wind Helper
0.86
959381AF2-229 GEN
Solar/Wind Helper
0.345
23750501ELLIOTTS
Solar/Wind Helper
0.571
3141426STAFORD
Solar/Wind Helper
0.051
960921AF2-383 GEN
Solar/Wind Helper
0.352
205943AE1-185 GEN
Solar/Wind Helper
0.492
205956AE1-196_GEN
Solar/Wind Helper
0.492
205932AD2-116_GEN
Solar/Wind Helper
0.492
233935AB2-179 C
Solar/Wind Helper
1.227
232436AB1-176 C
Solar/Wind Helper
0.043
233923SMA
Solar/Wind Helper
0.927
233990AG1-397 GEN
Solar/Wind Helper
0.261
234033AF1-007_GEN
Solar/Wind Helper
6.787
232432Z2-076 GEN
Solar/Wind Helper
0.065
964001AG1-254 GEN
Solar/Wind Helper
0.924
228754AB1-001 C
Solar/Wind Helper
0.025
227927V4-067C
Solar/Wind Helper
0.01
219914AD2-027 C
Solar/Wind Helper
0.111
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.038
219607WPEMNERT C
Solar/Wind Helper
0.077
214067T20SOLAR
Solar/Wind Helper
0.011
203975AE1-071-GEN
Solar/Wind Helper
2.41
20715728PEM_W1-119
Solar/Wind Helper
0.093
20715828PEM_W1-120
Solar/Wind Helper
0.093
207459AE1-142 C O1
Solar/Wind Helper
0.28
316164AC1-076 GEN
Solar/Wind Helper
1.062
219620RIDERU C
Solar/Wind Helper
0.001
253370AE2-315 SEC1
Adder
2.103
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
246938BC-WTG3
Solar/Wind Harmer
0.263
246937BC-WTG2
Solar/Wind Harmer
0.295
971231AH1-075 GEN
Solar/Wind Harmer
0.833
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
970611AG2-400 GEN
Solar/Wind Harmer
7.225
970627AG2-408 GEN
Solar/Wind Harmer
2.167
270007AE1-245 C
Solar/Wind Harmer
0.002
970623AG2-406 GEN
Solar/Wind Harmer
1.309
962581AG1-107 GEN
Solar/Wind Harmer
0.001
25183208HLCRTG
Solar/Wind Harmer
0.011
944541AF1-119 GEN
Solar/Wind Harmer
0.479
960971AF2-388 GEN
Solar/Wind Harmer
4.192
942221AE2-234 GEN
Solar/Wind Harmer
0.036
252519AF1-045_GEN
Solar/Wind Harmer
6.204
252516AE2-318_GEN
Solar/Wind Harmer
5.503
970621AG2-405 GEN
Solar/Wind Harmer
1.305
247621Y3-024
Adder
0.246
970883AG2-550 GEN
Solar/Wind Harmer
7.123
970885AG2-551 GEN
Solar/Wind Harmer
2.374
270201AC2-176 GEN
Solar/Wind Harmer
0.001
25194408D.CRK1
Adder
7.711
25194508D.CRK3
Adder
1.442
964611AG1-324 GEN
Solar/Wind Harmer
0.534
252509AD1-136 GEN
Solar/Wind Harmer
0.036
970321AG2-212 GEN
Solar/Wind Harmer
3.076
270599AE1-208 GEN
Solar/Wind Harmer
6.495
270031AE2-169
Solar/Wind Harmer
3.897
270383AD1-128 GEN
Solar/Wind Harmer
0.004
270186AC1-089 GEN
Solar/Wind Harmer
0.004
247620Y3-023
Adder
0.466
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
970825AG2-519 GEN
Solar/Wind Harmer
7.834
960441AF2-335 GEN
Solar/Wind Harmer
7.065
270216AD2-079_GEN
Solar/Wind Harmer
0.001
971613AH1-306 GEN
Solar/Wind Harmer
3.385
24728805RICHG1
Adder
3.82
24728905RICHG2
Adder
3.82
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
14.072
961051AF2-396 GEN
Solar/Wind Harmer
9.381
270526AF1-158 GEN
Solar/Wind Harmer
0.009
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
8.77
965791AG1-447 GEN
Solar/Wind Harmer
6.431
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
970239AG2-162 GEN
Solar/Wind Harmer
1.73
274770LINCOLN ;1U
Adder
8.364
274771LINCOLN ;2U
Adder
8.364
274808UNIV PK N;4U
Adder
4.933
966841AG1-555 GEN
Solar/Wind Harmer
0.781
274803UNIV PARK;6U
Adder
5.755
274888KELLY CRK;1U
Solar/Wind Harmer
0.404
274887GEN-1.85
Solar/Wind Harmer
0.181
276843GEN-1.7
Solar/Wind Harmer
0.223
958011AF2-095 GEN
Solar/Wind Harmer
9.913
972259AH1-714 GEN
Adder
18.805
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
970241AG2-163 GEN
Solar/Wind Harmer
3.993
958481AF2-142 GEN
Solar/Wind Harmer
10.238
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.923
971573AH1-285 GEN
Solar/Wind Harmer
1.271
971677AH1-339 GEN
Solar/Wind Harmer
0.768
958491AF2-143 GEN
Solar/Wind Harmer
10.205
274879MINONK ;1U
Solar/Wind Harmer
0.287
238175AF1-290_GEN
Solar/Wind Helper
0.148
238169AE2-226 GEN1
Solar/Wind Helper
0.677
238170AE2-226 GEN2
Solar/Wind Helper
0.677
238120AE2-309 GEN
Solar/Wind Helper
0.487
235020AA1-095 C
Solar/Wind Helper
0.051
23777901MDS_W4-102
Solar/Wind Helper
0.171
23585401KL_K28_T16
Solar/Wind Helper
1.328
237034AC2-136 C
Solar/Wind Helper
0.219
237002AB1-128_GEN
Solar/Wind Helper
0.427
235063AE1-101 C2
Solar/Wind Helper
1.6
237001AB1-127_GEN
Solar/Wind Helper
0.426
23777801MSM_W1-116
Solar/Wind Helper
0.11
237025AB1-124 C
Solar/Wind Helper
0.159
237006AB1-125 GEN
Solar/Wind Helper
0.119
226929AD2-058 GEN
Solar/Wind Helper
0.096
205916AD1-020 GEN
Solar/Wind Helper
1.656
20390526W1-045 C
Solar/Wind Helper
0.338
208835TUHI V3-051
Solar/Wind Helper
0.023
208835TUHI V3-051
Solar/Wind Helper
0.023
233987AB2-037 GEN
Solar/Wind Helper
2.264
233933AB2-153 GEN
Solar/Wind Helper
0.225
232424Y1-079 C
Solar/Wind Helper
0.112
233944AB2-135 GEN
Solar/Wind Helper
0.569
233946AB2-136 GEN
Solar/Wind Helper
0.549
234036AF2-325 C
Solar/Wind Helper
0.041
233901CHERRYDALE C
Solar/Wind Helper
0.225
232408W1-005 C
Solar/Wind Helper
0.49
232410W1-006 C
Solar/Wind Helper
0.49
233939AC1-091 C
Solar/Wind Helper
0.338
233970AC1-092 C
Solar/Wind Helper
0.338
315651AD1-115 GEN
Solar/Wind Helper
0.76
316447AC1-158 HLD
Solar/Wind Helper
2.756
230433AD2-135 GEN
Solar/Wind Helper
0.016
230407AD2-065 C
Solar/Wind Helper
0.039
219921AF1-264
Solar/Wind Helper
0.049
219615MILLCREEK C
Solar/Wind Helper
0.026
963401AG1-189 GEN
Solar/Wind Helper
0.054
963391AG1-188 GEN
Solar/Wind Helper
0.079
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.183
270489AE1-102 GEN1
Solar/Wind Harmer
0.945
965421AG1-410 GEN
Solar/Wind Harmer
21.788
247521TR3_G114
Solar/Wind Harmer
0.263
270246TR4_N_V150
Solar/Wind Harmer
0.047
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.226
965011AG1-365 GEN
Solar/Wind Harmer
7.225
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
24695305TIMB G C
Solar/Wind Harmer
0.002
965651AG1-433 GEN
Solar/Wind Harmer
2.096
958861AF2-177 GEN
Solar/Wind Harmer
3.092
247536S-71 GEN
Solar/Wind Harmer
0.287
945371AF1-202 GEN
Solar/Wind Harmer
0.001
25194608D.CRK4
Adder
1.676
270063AE2-323 C
Solar/Wind Harmer
0.006
252507AC2-088 GEN
Solar/Wind Harmer
0.323
970245AG2-165 GEN
Solar/Wind Harmer
3.076
944231AF1-091 GEN
Solar/Wind Harmer
1.885
270005AE1-210 C O1
Solar/Wind Harmer
1.532
965031AG1-367 GEN
Solar/Wind Harmer
7.073
970947AG2-589 GEN
Solar/Wind Harmer
0.236
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.183
970825AG2-519 GEN
Solar/Wind Harmer
2.509
24639705ELKHART HY
Adder
0.155
25196808ZIMRHP
Adder
76.799
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
270032AE2-172
Solar/Wind Harmer
4.701
970291AG2-192 GEN
Solar/Wind Harmer
0.916
945111AF1-176 GEN
Solar/Wind Harmer
12.568
270505AE1-170 C O1
Solar/Wind Harmer
7.393
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.67
247522W1-056 GEN
Solar/Wind Harmer
0.001
276903AD2-071 C
Solar/Wind Harmer
7.842
25196008MFTGT1
Adder
1.397
970773AG2-487 GEN
Solar/Wind Harmer
1.237
970373AG2-245 GEN
Solar/Wind Harmer
14.699
970515AG2-329 GEN
Solar/Wind Harmer
18.197
270055AF2-134 C O1
Solar/Wind Harmer
0.005
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.071
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.706
24791305MDL-5G
Solar/Wind Harmer
0.001
970333AG2-219 GEN
Solar/Wind Harmer
4.947
274751CRETE EC ;1U
Adder
8.172
274754CRETE EC ;4U
Adder
8.172
274773LINCOLN ;4U
Adder
8.364
274774LINCOLN ;5U
Adder
8.364
274723RIVER EC ;12
Adder
17.756
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.954
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
276776AD2-060 GEN
Solar/Wind Harmer
0.719
24728605AND G2
Adder
3.784
274801UNIV PARK;4U
Adder
5.751
941551AE2-152 GEN
Solar/Wind Harmer
0.001
945681AF1-233 GEN
Solar/Wind Harmer
12.962
274676JOLIET 29;8U
Adder
30.175
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
963741AG1-226 GEN
Solar/Wind Harmer
16.202
939401AE1-172 GEN
Solar/Wind Harmer
5.109
276691AA1-018 GEN1
Solar/Wind Harmer
0.827
276901AD2-066 C O1
Solar/Wind Harmer
0.007
316095T157 G97
Solar/Wind Helper
1.455
23583801GRNGAP
Solar/Wind Helper
5.418
238108AE1-109 GEN1
Solar/Wind Helper
0.106
238185AF2-356 C
Solar/Wind Helper
2.425
238147AE2-230_GEN1
Solar/Wind Helper
0.478
238149AF1-291A_GEN
Solar/Wind Helper
0.137
235531U2-073 GEN
Solar/Wind Helper
3.034
235054AD2-180 GEN
Solar/Wind Helper
1.839
237061AD1-155 GEN
Solar/Wind Helper
0.051
238117U2-030
Solar/Wind Helper
0.314
238221AF1-254 C O1
Solar/Wind Helper
0.265
235067AD1-061 GEN
Solar/Wind Helper
0.478
237030AB1-096 C
Solar/Wind Helper
0.068
3141196NOKESVL
Solar/Wind Helper
0.999
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.335
223402AF1-300 C
Solar/Wind Helper
0.355
23751201ROTHROCK
Solar/Wind Helper
0.694
23562501BACKB
Solar/Wind Helper
0.842
205917AD1-020 ES
Solar/Wind Helper
0.356
233982AB2-133 GEN
Solar/Wind Helper
0.346
233918AB1-142 GEN
Solar/Wind Helper
0.486
233994AC2-023 GEN
Solar/Wind Helper
0.929
233996TM1833_GEN
Solar/Wind Helper
0.253
233997TMININ_4.2
Solar/Wind Helper
0.253
232406W1-004 FULL
Solar/Wind Helper
0.49
233940AF2-379 C
Solar/Wind Helper
0.06
234015AF2-250 C
Solar/Wind Helper
0.037
233952AC2-187 GEN
Solar/Wind Helper
0.225
233971AC1-093 C
Solar/Wind Helper
0.346
316044AC1-158 PL1
Solar/Wind Helper
1.252
316450AC1-158 RIC
Solar/Wind Helper
0.334
230430AE1-229_GEN
Solar/Wind Helper
3.26
230415AB2-049 C
Solar/Wind Helper
0.029
228729W2-030 C
Solar/Wind Helper
0.107
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.053
971191AH1-055 GEN
Solar/Wind Harmer
18.515
944531AF1-118 GEN
Solar/Wind Harmer
32.203
270043AE2-236 GEN
Solar/Wind Harmer
4.607
270258AD1-119 GEN
Solar/Wind Harmer
0.002
971617AH1-308 GEN
Solar/Wind Harmer
5.953
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
10.684
270404AC1-167 GEN
Solar/Wind Harmer
0.003
25196608WSDLE5
Adder
8.745
252510AF1-249 C
Solar/Wind Harmer
0.055
970031AG2-029 GEN
Solar/Wind Harmer
4.625
25194608D.CRK4
Adder
1.676
270222AC2-111 GEN
Solar/Wind Harmer
3.603
970513AG2-328 GEN
Solar/Wind Harmer
3.076
970517AG2-330 GEN
Solar/Wind Harmer
18.457
970349AG2-230 GEN
Solar/Wind Harmer
10.632
946031AF1-268 GEN
Solar/Wind Harmer
6.74
958821AF2-173 GEN
Solar/Wind Harmer
9.902
270004AE1-209 GEN
Solar/Wind Harmer
1.532
270437AC2-090 C
Solar/Wind Harmer
0.003
247643Z2-116 C
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.775
970291AG2-192 GEN
Solar/Wind Harmer
0.705
945111AF1-176 GEN
Solar/Wind Harmer
5.709
247642Z2-115 C
Solar/Wind Harmer
0.003
24642205MAYFLWER
Adder
0.641
24441205WTRV SLR C
Solar/Wind Harmer
0
25196008MFTGT1
Adder
1.353
270356AE2-297 GEN
Solar/Wind Harmer
0.009
970217AG2-149 GEN
Solar/Wind Harmer
6.066
247604X1-042
Adder
0.418
270535AF1-215 GEN1
Solar/Wind Harmer
0.009
964401AG1-302 GEN
Solar/Wind Harmer
0.001
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.935
970243AG2-164 GEN
Solar/Wind Harmer
4.047
970519AG2-331 GEN
Solar/Wind Harmer
17.988
970699AG2-449 GEN
Solar/Wind Harmer
1.73
274752CRETE EC ;2U
Adder
8.172
274753CRETE EC ;3U
Adder
8.172
274772LINCOLN ;3U
Adder
8.364
274724RIVER EC ;11
Adder
17.549
958171AF2-111 GEN
Solar/Wind Harmer
17.278
274802UNIV PARK;5U
Adder
5.755
276806AD2-047 C O1
Solar/Wind Harmer
3.901
970941AG2-585 GEN
Solar/Wind Harmer
8.605
274826FISK ;BP
Adder
10.802
24728705AND G3
Adder
7.914
24728505AND G1
Adder
3.784
274800UNIV PARK;3U
Adder
5.751
972038AH1-567 GEN2
Adder
0.36
972228AH1-698 GEN2
Adder
3.654
972167AH1-666 GEN
Solar/Wind Harmer
5.505
276897AD1-100 C
Solar/Wind Harmer
0.009
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
22.464
274676JOLIET 29;8U
Adder
29.097
274729ELWOOD EC;1P
Adder
16.163
274730ELWOOD EC;6P
Adder
13.491
276893AG1-478 C
Solar/Wind Harmer
0.272
270541AE2-072 C
Solar/Wind Harmer
0.009
943121AE2-341 GEN
Solar/Wind Harmer
11.459
943591AF1-030 GEN
Solar/Wind Harmer
7.62
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
276805AD2-038 GEN
Solar/Wind Harmer
0.002
964991AG1-363 GEN
Solar/Wind Helper
4.969
316097T157 G90
Solar/Wind Helper
1.455
23750701CROSSCHOOL
Solar/Wind Helper
1.397
238148AE2-230_GEN2
Solar/Wind Helper
0.48
238127S14_GEN_2
Solar/Wind Helper
0.766
238118U2-030_1
Solar/Wind Helper
0.314
237080AD1-060 GEN
Solar/Wind Helper
0.33
237038AE2-054 C
Solar/Wind Helper
0.262
235062AE1-101 C1
Solar/Wind Helper
1.6
23779801AA1-109
Solar/Wind Helper
0.187
223401AF1-299 GEN
Solar/Wind Helper
0.355
316006AB2-029 C
Solar/Wind Helper
0.113
966131AG1-482 GEN
Solar/Wind Helper
0.132
237048AF1-022 C
Solar/Wind Helper
0.159
233930AB2-032 GEN
Solar/Wind Helper
0.368
233915AB1-141 GEN
Solar/Wind Helper
0.486
232422X3-066 FULL
Solar/Wind Helper
0.11
232426Y1-080 FULL
Solar/Wind Helper
0.038
233964AF2-378 GEN
Solar/Wind Helper
0.04
233998TM1NIN_3.36
Solar/Wind Helper
0.253
232404W1-003 C
Solar/Wind Helper
0.49
232428Y3-058 C
Solar/Wind Helper
0.327
232434Z2-077 GEN
Solar/Wind Helper
0.123
233954AC2-188 GEN
Solar/Wind Helper
0.225
233950AC2-186 GEN
Solar/Wind Helper
0.112
233972AC1-094 C
Solar/Wind Helper
0.292
316045AC1-158 PL2
Solar/Wind Helper
4.009
230511AF1-262
Solar/Wind Helper
0.014
230434AG1-499 GEN
Solar/Wind Helper
0.222
228728W1-130C
Solar/Wind Helper
0.052
219258KINSLEYDEP C
Solar/Wind Helper
0.074
219904AC1-010 C
Solar/Wind Helper
0.058
218660EHAMPSOLAR C
Solar/Wind Helper
0.032
219907AC1-030 C
Solar/Wind Helper
0.033
219686LUMSOLAR_N C
Solar/Wind Helper
0.038
219304NAMERICA C
Solar/Wind Helper
0.127
316254AC1-120 GEN1
Solar/Wind Helper
1.026
20720728JCB_W1-129
Solar/Wind Helper
0.055
207445AB1-138_GEN
Solar/Wind Helper
0.101
963711AG1-223 GEN
Solar/Wind Helper
0.062
20714828MDF_W3-079
Solar/Wind Helper
0.126
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.299
20715228NPK_W1-113
Solar/Wind Helper
0.075
219912AD2-042 GEN
Solar/Wind Helper
0.145
219291REEVESSOUT C
Solar/Wind Helper
0.011
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.111
316170AC1-121 GEN2
Solar/Wind Helper
0.342
959561AF2-247 GEN
Solar/Wind Helper
0.02
20720828JCB_W4-025
Solar/Wind Helper
0.061
20716028EGP_W2-019
Solar/Wind Helper
0.018
20715028HAN_X4-015
Solar/Wind Helper
0.055
219276PARKLANDSO C
Solar/Wind Helper
0.086
20714528FRN_Y2-051
Solar/Wind Helper
0.055
20720528MAN_W1-024
Solar/Wind Helper
0.027
971997AH1-543 GEN
Solar/Wind Harmer
1.86
LAGNLTFEXP_LAGN->PJM
CLTF
14.268
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.432
TVALTFEXP_TVA->PJM
CLTF
7.011
CPLELTFEXP_CPLE->PJM
CLTF
0.567
CBM West 2LTFEXP_CBM-W2->PJM
CBM
108.576
CBM West 1LTFEXP_CBM-W1->PJM
CBM
137.982
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.984
MECLTFEXP_MEC->PJM
CLTF
15.319
SIGELTFEXP_SIGE->PJM
CLTF
0.486
NYPJM->LTFIMP_NY
CLTF
4.628
LGEELTFEXP_LGEE->PJM
CLTF
6.497
WECLTFEXP_WEC->PJM
CLTF
3.686
AG2-052LTFEXP_AG2-052->PJM
LTF
0.231
AH1-155LTFEXP_AH1-155->PJM
LTF
0.346

Details for 02BAY SH-02DAV-BE 345.0 kV Ckt 1 line l/o ATSI_P1-2_TE-345-602_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_TE-345-602_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:142.52 %
Rating:1683.0 MVA
Rating Type:B
MVA to Mitigate:2398.59
MW Contribution:0.38
Bus #Bus NameTypeMW Contribution
24190002OREGON_ST1
50/50
5.55
24189802OREGON_CT1
50/50
4.21
23888802TROY G4
50/50
1.526
241996AE2-282_GEN
Solar/Wind Harmer
0.006
971677AH1-339 GEN
Solar/Wind Harmer
0.659
970621AG2-405 GEN
Solar/Wind Harmer
0.944
970623AG2-406 GEN
Solar/Wind Harmer
0.885
961051AF2-396 GEN
Solar/Wind Harmer
9.384
961051AF2-396 GEN
Solar/Wind Harmer
6.256
246938BC-WTG3
Solar/Wind Harmer
0.168
246937BC-WTG2
Solar/Wind Harmer
0.188
957891AF2-083 GEN
Solar/Wind Harmer
0.001
270007AE1-245 C
Solar/Wind Harmer
0.001
247620Y3-023
Adder
0.296
270216AD2-079_GEN
Solar/Wind Harmer
0.001
270526AF1-158 GEN
Solar/Wind Harmer
0.005
24441505OLIV SLR
Solar/Wind Harmer
0
970611AG2-400 GEN
Solar/Wind Harmer
4.252
970627AG2-408 GEN
Solar/Wind Harmer
1.276
965681AG1-436 GEN
Solar/Wind Harmer
5.151
965791AG1-447 GEN
Solar/Wind Harmer
3.778
270224U2-072_GEN2
Solar/Wind Harmer
0
270227U2-072_GEN3
Solar/Wind Harmer
0
270228U2-072_GEN4
Solar/Wind Harmer
0
270231U2-072_GEN5
Solar/Wind Harmer
0
274808UNIV PK N;4U
Adder
2.71
274803UNIV PARK;6U
Adder
3.135
274888KELLY CRK;1U
Solar/Wind Harmer
0.219
274887GEN-1.85
Solar/Wind Harmer
0.098
276843GEN-1.7
Solar/Wind Harmer
0.121
958011AF2-095 GEN
Solar/Wind Harmer
5.377
274770LINCOLN ;1U
Adder
4.515
274771LINCOLN ;2U
Adder
4.515
972259AH1-714 GEN
Adder
10.138
274674JOLIET 9 ;6U
Adder
8.161
970321AG2-212 GEN
Solar/Wind Harmer
1.596
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
958481AF2-142 GEN
Solar/Wind Harmer
5.485
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.495
942221AE2-234 GEN
Solar/Wind Harmer
0.018
971573AH1-285 GEN
Solar/Wind Harmer
0.679
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
274696ROCKY RD ;4P
Adder
5.936
274695ROCKY RD ;2P
Adder
5.799
274693ROCKY RD ;1P
Adder
5.742
274697ROCKY RD ;3P
Adder
1.575
274683WAUKEGAN ;8U
Adder
10.969
274683WAUKEGAN ;8U
Adder
9.246
958491AF2-143 GEN
Solar/Wind Harmer
5.438
962691AG1-118 GEN
Solar/Wind Harmer
10.84
274879MINONK ;1U
Solar/Wind Harmer
0.152
970921AG2-575 GEN
Solar/Wind Harmer
3.608
970921AG2-575 GEN
Solar/Wind Harmer
1.203
942991AE2-321 GEN
Solar/Wind Harmer
4.013
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
971333AH1-146 GEN
Solar/Wind Harmer
7.161
971335AH1-147 GEN
Solar/Wind Harmer
7.161
971341AH1-150 GEN
Solar/Wind Harmer
7.133
971343AH1-151 GEN
Solar/Wind Harmer
7.133
274856ECOGROVE ;U1
Solar/Wind Harmer
0.084
276611AD2-172 GEN
Solar/Wind Harmer
0.001
938861AE1-114 GEN
Solar/Wind Harmer
1.999
274764LEE CO EC;5U
Adder
4.704
274765LEE CO EC;6U
Adder
4.704
274762LEE CO EC;3U
Adder
4.693
274763LEE CO EC;4U
Adder
4.649
276603SUBLETTE C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.397
274851PROVIDENC;RU
Solar/Wind Harmer
0
274849CRESCENT ;1U
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.137
276646AC1-214 GEN2
Solar/Wind Harmer
0.137
276741O09 GEN1
Solar/Wind Harmer
0.124
276708O09 GEN2
Solar/Wind Harmer
0.124
276782AC1-033 GEN
Solar/Wind Harmer
0.001
944541AF1-119 GEN
Solar/Wind Harmer
0.231
960971AF2-388 GEN
Solar/Wind Harmer
2.024
960611AF2-352 GEN
Solar/Wind Harmer
1.144
970241AG2-163 GEN
Solar/Wind Harmer
1.972
270201AC2-176 GEN
Solar/Wind Harmer
0.001
270599AE1-208 GEN
Solar/Wind Harmer
3.085
270031AE2-169
Solar/Wind Harmer
1.851
964611AG1-324 GEN
Solar/Wind Harmer
0.251
971613AH1-306 GEN
Solar/Wind Harmer
1.593
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
971231AH1-075 GEN
Solar/Wind Harmer
0.377
960441AF2-335 GEN
Solar/Wind Harmer
3.255
970825AG2-519 GEN
Solar/Wind Harmer
3.6
203947AF1-006 C
Solar/Wind Helper
0.391
203980AG1-197 GEN
Solar/Wind Helper
0.255
203979AG1-198 GEN
Solar/Wind Helper
0.198
241801AE1-079 GEN
Solar/Wind Helper
0.134
241967AE2-285_GEN
Solar/Wind Helper
0.345
241985AE1-237 GEN
Solar/Wind Helper
0.134
962101AG1-054 GEN
Solar/Wind Helper
0.332
946381AF1-302 GEN
Solar/Wind Helper
0.105
238217AF1-153 C O1
Solar/Wind Helper
0.111
24189902OREGON_CT2
50/50
4.125
23856402BAYSG1
50/50
1.577
23888702TROY G3
50/50
1.526
972253AH1-711 GEN
50/50
46.611
23920202STRYCT
50/50
1.928
241808AF1-120 C
Solar/Wind Harmer
0.003
241858AF1-205_GEN
Solar/Wind Harmer
3.78
241840AF1-064_GEN
Solar/Wind Harmer
0.004
972301AH1-735 GEN
Adder
6.727
23906402RICHG1
Adder
1.345
23906502RICHG2&3
Adder
1.343
270361_3
Solar/Wind Harmer
4.521
960841AF2-375 GEN
Solar/Wind Harmer
-0.002
970515AG2-329 GEN
Solar/Wind Harmer
14.08
944231AF1-091 GEN
Solar/Wind Harmer
1.351
247522W1-056 GEN
Solar/Wind Harmer
0.001
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.47
246936BC-WTG1
Solar/Wind Harmer
0.188
270489AE1-102 GEN1
Solar/Wind Harmer
0.603
945111AF1-176 GEN
Solar/Wind Harmer
8.251
270505AE1-170 C O1
Solar/Wind Harmer
4.856
965421AG1-410 GEN
Solar/Wind Harmer
13.81
24639705ELKHART HY
Adder
0.098
24695305TIMB G C
Solar/Wind Harmer
0.001
270063AE2-323 C
Solar/Wind Harmer
0.004
247521TR3_G114
Solar/Wind Harmer
0.158
270246TR4_N_V150
Solar/Wind Harmer
0.028
965011AG1-365 GEN
Solar/Wind Harmer
4.252
270462AD2-086
Solar/Wind Harmer
0.009
970373AG2-245 GEN
Solar/Wind Harmer
8.33
270055AF2-134 C O1
Solar/Wind Harmer
0.003
270223U2-072_GEN1
Solar/Wind Harmer
0
274751CRETE EC ;1U
Adder
4.532
274754CRETE EC ;4U
Adder
4.532
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
4.962
274723RIVER EC ;12
Adder
9.782
274812UNIV PK N;8U
Adder
2.722
276164X3-005 C
Solar/Wind Harmer
0
274801UNIV PARK;4U
Adder
3.125
276776AD2-060 GEN
Solar/Wind Harmer
0.39
274773LINCOLN ;4U
Adder
4.515
274774LINCOLN ;5U
Adder
4.515
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
4.664
274676JOLIET 29;8U
Adder
16.292
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
8.714
274674JOLIET 9 ;6U
Adder
8.161
970245AG2-165 GEN
Solar/Wind Harmer
1.596
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
2.931
276691AA1-018 GEN1
Solar/Wind Harmer
0.443
274682WAUKEGAN ;7U
Adder
9.363
274828WAUKEGAN ;BP
Adder
5.75
276901AD2-066 C O1
Solar/Wind Harmer
0.004
939401AE1-172 GEN
Solar/Wind Harmer
2.703
962781AG1-127 GEN
Solar/Wind Harmer
3.433
274872LEEDK;1U
Solar/Wind Harmer
0.002
24791305MDL-5G
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
1.887
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
276861AD2-134 GEN
Solar/Wind Harmer
0.064
957471AF2-041 GEN
Solar/Wind Harmer
10.7
959081AF2-199 GEN
Solar/Wind Harmer
3.567
971067AG2-660 GEN
Solar/Wind Harmer
1.189
274822ROCKFORD ;11
Adder
10.013
972235AH1-702 GEN1
Adder
1.284
970569AG2-363 GEN
Solar/Wind Harmer
10.66
970819AG2-516 GEN
Solar/Wind Harmer
4.256
971475AH1-234 GEN
Solar/Wind Harmer
1.718
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
4.693
274766LEE CO EC;7U
Adder
4.638
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.001
276158O29GEN2
Solar/Wind Harmer
0
274877BISHOP HL;1U
Solar/Wind Harmer
0.117
276726Z2-087_GEN
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
4.858
965651AG1-433 GEN
Solar/Wind Harmer
1.012
274854TWINGROVE;U2
Solar/Wind Harmer
0.001
958861AF2-177 GEN
Solar/Wind Harmer
1.482
963741AG1-226 GEN
Solar/Wind Harmer
7.999
972175AH1-670 GEN
Solar/Wind Harmer
2.788
945371AF1-202 GEN
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.435
274880W4-005 GEN4
Solar/Wind Harmer
0
270032AE2-172
Solar/Wind Harmer
2.212
963831AG1-236 GEN
Solar/Wind Harmer
1.29
247536S-71 GEN
Solar/Wind Harmer
0.132
276615X2-022 GEN
Solar/Wind Harmer
0.034
276903AD2-071 C
Solar/Wind Harmer
3.649
970825AG2-519 GEN
Solar/Wind Harmer
1.153
270005AE1-210 C O1
Solar/Wind Harmer
0.7
241885AC2-103 GEN1
Solar/Wind Helper
6.849
241807AE2-176_GEN
Solar/Wind Helper
1.64
961971AG1-040 GEN
Solar/Wind Helper
0.342
203835AF1-098 GEN
Solar/Wind Helper
1.348
203860AG1-193 C
Solar/Wind Helper
0.152
241966AE1-183 GEN
Solar/Wind Helper
0.132
254303AC2-168 GEN
Solar/Wind Helper
0.077
965031AG1-367 GEN
Solar/Wind Harmer
0.798
23929302BS-PKR
50/50
2.775
241832AE2-181_GEN
Solar/Wind Harmer
0.004
958321AF2-126 GEN
Solar/Wind Harmer
1.136
23906502RICHG2&3
Adder
1.343
270541AE2-072 C
Solar/Wind Harmer
0.008
270575GUS2 35KV
Solar/Wind Harmer
4.521
970217AG2-149 GEN
Solar/Wind Harmer
4.693
247604X1-042
Adder
0.303
270404AC1-167 GEN
Solar/Wind Harmer
0.002
24441205WTRV SLR C
Solar/Wind Harmer
0
270258AD1-119 GEN
Solar/Wind Harmer
0.001
270491AE1-102 GEN2
Solar/Wind Harmer
0.603
945111AF1-176 GEN
Solar/Wind Harmer
3.748
270588AE1-091_GEN
Solar/Wind Harmer
3.595
24642205MAYFLWER
Adder
0.41
247643Z2-116 C
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
2.866
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.028
959331AF2-224 GEN
Solar/Wind Harmer
2.976
965021AG1-366 GEN
Solar/Wind Harmer
1.417
270485AE1-090_GEN
Solar/Wind Harmer
0.001
970349AG2-230 GEN
Solar/Wind Harmer
6.147
270043AE2-236 GEN
Solar/Wind Harmer
2.609
270535AF1-215 GEN1
Solar/Wind Harmer
0.005
270391AF1-285 GEN3
Solar/Wind Harmer
0.256
274752CRETE EC ;2U
Adder
4.532
274753CRETE EC ;3U
Adder
4.532
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274724RIVER EC ;11
Adder
9.666
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
274802UNIV PARK;5U
Adder
3.135
274826FISK ;BP
Adder
5.877
274800UNIV PARK;3U
Adder
3.125
972038AH1-567 GEN2
Adder
0.196
276806AD2-047 C O1
Solar/Wind Harmer
2.116
970941AG2-585 GEN
Solar/Wind Harmer
4.668
274772LINCOLN ;3U
Adder
4.515
972228AH1-698 GEN2
Adder
1.977
274676JOLIET 29;8U
Adder
15.71
276897AD1-100 C
Solar/Wind Harmer
0.005
939351AE1-166 GEN
Solar/Wind Harmer
0
276893AG1-478 C
Solar/Wind Harmer
0.147
274730ELWOOD EC;6P
Adder
8.714
274734ELWOOD EC;8P
Adder
8.714
274736ELWOOD EC;9P
Adder
8.714
274729ELWOOD EC;1P
Adder
8.713
970707AG2-453 GEN
Solar/Wind Harmer
12.079
970513AG2-328 GEN
Solar/Wind Harmer
1.596
970517AG2-330 GEN
Solar/Wind Harmer
9.577
943121AE2-341 GEN
Solar/Wind Harmer
6.132
943591AF1-030 GEN
Solar/Wind Harmer
4.078
276694AA1-018 GEN2
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
9.363
276805AD2-038 GEN
Solar/Wind Harmer
0.001
274872LEEDK;1U
Solar/Wind Harmer
0.132
24755605MDL-5G
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.599
971617AH1-308 GEN
Solar/Wind Harmer
2.996
276889AE2-281 GEN
Solar/Wind Harmer
0
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.382
274855GSG-6 ;RU
Solar/Wind Harmer
0.131
274850MENDOTA H;RU
Solar/Wind Harmer
0.042
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.064
944531AF1-118 GEN
Solar/Wind Harmer
16.023
959091AF2-200 GEN
Solar/Wind Harmer
7.133
972236AH1-702 GEN2
Adder
1.116
970571AG2-364 GEN
Solar/Wind Harmer
7.107
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
4.693
274767LEE CO EC;8U
Adder
1.086
276157O29GEN1
Solar/Wind Harmer
0.565
274878BISHOP HL;2U
Solar/Wind Harmer
0.117
942111AE2-223 GEN
Solar/Wind Harmer
1.128
274853TWINGROVE;U1
Solar/Wind Harmer
0.001
965091AG1-374 GEN
Solar/Wind Harmer
10.299
959611AF2-252 GEN
Solar/Wind Harmer
1.144
965931AG1-462 GEN
Solar/Wind Harmer
8.719
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
5.066
247642Z2-115 C
Solar/Wind Harmer
0.001
970289AG2-191 GEN
Solar/Wind Harmer
0.368
970291AG2-192 GEN
Solar/Wind Harmer
0.334
276686W4-005 GEN3
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.121
971993AH1-541 GEN
Solar/Wind Harmer
1.533
270377AD1-106 GEN
Solar/Wind Harmer
1.25
276621W2-048 GEN
Solar/Wind Harmer
0.166
276838X2-022 GEN2
Solar/Wind Harmer
0.185
946031AF1-268 GEN
Solar/Wind Harmer
3.103
958821AF2-173 GEN
Solar/Wind Harmer
4.521
270004AE1-209 GEN
Solar/Wind Harmer
0.7
962511AG1-100 GEN
Solar/Wind Helper
0.35
203830AF1-094 GEN
Solar/Wind Helper
0.331
959441AF2-235 GEN
Solar/Wind Helper
0.15
254305AE2-115 C
Solar/Wind Helper
0.114
20334926Z1-069 C
Solar/Wind Helper
0.646
972211AH1-690 GEN
50/50
445.374
23888502TROY G1
50/50
1.526
23888602TROY G2
50/50
1.526
970817AG2-515 GEN
Solar/Wind Harmer
9.949
945411AF1-206 GEN
Solar/Wind Harmer
-0.001
945641AF1-229 GEN
Solar/Wind Harmer
0.001
270499AE1-146 GEN
Solar/Wind Harmer
0.029
971549AH1-272 GEN
Solar/Wind Harmer
11.98
270297AD1-101 GEN
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.588
971619AH1-309 GEN
Solar/Wind Harmer
2.081
247607V1-011 GEN
Solar/Wind Harmer
0.001
971771AH1-392 GEN
Solar/Wind Harmer
4.385
965041AG1-368 GEN
Solar/Wind Harmer
4.372
965051AG1-369 GEN
Solar/Wind Harmer
2.168
971989AH1-539 GEN
Solar/Wind Harmer
1.862
971769AH1-391 GEN
Solar/Wind Harmer
4.78
270302AB2-170 GEN
Solar/Wind Harmer
0.003
270317AD1-130_GEN
Solar/Wind Harmer
0.006
971653AH1-327 GEN
Solar/Wind Harmer
0.58
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971347AH1-153 GEN
Solar/Wind Harmer
6.147
963791AG1-232 GEN
Solar/Wind Harmer
5.327
971567AH1-282 GEN
Solar/Wind Harmer
5.89
270536AF1-215 GEN2
Solar/Wind Harmer
0.005
270578AF1-285 GEN2
Solar/Wind Harmer
0.256
274814UNIV PK N;0U
Adder
2.746
274807UNIV PK N;3U
Adder
2.74
274805UNIV PK N;1U
Adder
2.728
274811UNIV PK N;7U
Adder
2.722
270071AF1-092 GEN
Solar/Wind Harmer
7.267
958391AF2-133 GEN
Solar/Wind Harmer
0.001
972037AH1-567 GEN1
Adder
0.098
274827FISK ;RP
Adder
4.165
960591AF2-350 GEN
Solar/Wind Harmer
3.734
274775LINCOLN ;6U
Adder
4.515
274776LINCOLN ;7U
Adder
4.515
274777LINCOLN ;8U
Adder
4.515
971611AH1-305 GEN
Solar/Wind Harmer
2.222
972227AH1-698 GEN1
Adder
1.392
274687WILL CNTY;4U
Adder
14.867
274687WILL CNTY;4U
Adder
14.867
274675JOLIET 29;7U
Adder
16.292
274675JOLIET 29;7U
Adder
15.71
274728ELWOOD EC;5P
Adder
8.714
274731ELWOOD EC;2P
Adder
8.713
274733ELWOOD EC;3P
Adder
8.713
274735ELWOOD EC;4P
Adder
8.713
970833AG2-524 GEN
Solar/Wind Harmer
4.049
970833AG2-524 GEN
Solar/Wind Harmer
2.699
274746AC1-111 G10
Adder
2.931
274744AC1-111 GEN8
Adder
2.931
276868AE1-113 GEN
Solar/Wind Harmer
0.724
276882AE2-255 GEN
Solar/Wind Harmer
0.422
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0.004
971177AH1-047 GEN
Solar/Wind Harmer
2.216
971411AH1-196 GEN
Solar/Wind Harmer
5.375
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
1.396
971171AH1-044 GEN
Solar/Wind Harmer
7.133
274823ROCKFORD ;21
Adder
9.941
926823AC1-168 GEN
Solar/Wind Harmer
0.603
970169AG2-114 GEN
Solar/Wind Harmer
3.546
276612AE2-035 GEN
Solar/Wind Harmer
0.001
24729505KEY G4
Adder
3.294
971681AH1-341 GEN
Solar/Wind Harmer
5.682
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
24387005FR-3G C
Solar/Wind Harmer
0.001
961011AF2-392 GEN
Solar/Wind Harmer
2.056
957751AF2-069 GEN
Solar/Wind Harmer
0.115
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
276655WTG1_EQ
Solar/Wind Harmer
0.001
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.644
941731AE2-173 GEN
Solar/Wind Harmer
2.892
963841AG1-237 GEN
Solar/Wind Harmer
1.492
946321AF1-296 GEN
Solar/Wind Harmer
1.922
965101AG1-375 GEN
Solar/Wind Harmer
3.421
971609AH1-304 GEN
Solar/Wind Harmer
0.55
945581AF1-223 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.635
276785W4-005 GEN1
Solar/Wind Harmer
0
276174W4-005 GEN2
Solar/Wind Harmer
0
276849AB2-070 GEN2
Solar/Wind Harmer
0.121
276848AB2-070 GEN3
Solar/Wind Harmer
0.12
270594AE1-207 GEN
Solar/Wind Harmer
3.716
970115AG2-085 GEN
Solar/Wind Harmer
1.302
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0
241886AC2-103 GEN2
Solar/Wind Helper
6.849
241982AE2-343 S C
Solar/Wind Helper
0.12
254304AE2-114 C
Solar/Wind Helper
0.114
203846AF2-130 C
Solar/Wind Helper
0.251
241997AF1-093 GEN
Solar/Wind Helper
0.132
203804AE2-113_GEN
Solar/Wind Helper
0.869
991182J1586 G
External Queue
28.11846351623535
990527J1329
External Queue
2.0234405994415283
990142J1224
External Queue
14.791350364685059
991177J1571 G
External Queue
15.792752265930176
LAGNLTFEXP_LAGN->PJM
CLTF
6.061
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.4
TVALTFEXP_TVA->PJM
CLTF
2.775
CPLELTFEXP_CPLE->PJM
CLTF
0.731
CBM West 2LTFEXP_CBM-W2->PJM
CBM
47.539
CBM West 1LTFEXP_CBM-W1->PJM
CBM
112.86
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.907
MECLTFEXP_MEC->PJM
CLTF
7.633
SIGELTFEXP_SIGE->PJM
CLTF
0.2
NYPJM->LTFIMP_NY
CLTF
1.965
LGEELTFEXP_LGEE->PJM
CLTF
2.4
WECLTFEXP_WEC->PJM
CLTF
1.946
AG2-052LTFEXP_AG2-052->PJM
LTF
0.125
AH1-155LTFEXP_AH1-155->PJM
LTF
0.187

Details for 02BEAVER-02CARLIL 345.0 kV Ckt 1 line l/o ATSI_P7-1_OEC-345-002_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02BEAVER-02CARLIL 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P7-1_OEC-345-002_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:109.31 %
Rating:1745.0 MVA
Rating Type:B
MVA to Mitigate:1907.45
MW Contribution:0.4
Bus #Bus NameTypeMW Contribution
23917402WLORG-5
50/50
1.527
23917102WLORG-2
50/50
1.505
966321AG1-501 GEN
50/50
1.834
957111AF2-005 GEN
50/50
1.467
24189902OREGON_CT2
50/50
2.208
23856402BAYSG1
50/50
1.196
241885AC2-103 GEN1
Solar/Wind Harmer
14.419
241807AE2-176_GEN
Solar/Wind Harmer
6.057
972253AH1-711 GEN
Adder
43.699
241858AF1-205_GEN
Solar/Wind Harmer
4.928
241808AF1-120 C
Solar/Wind Harmer
1.077
23920202STRYCT
Adder
1.608
241840AF1-064_GEN
Solar/Wind Harmer
1.274
972301AH1-735 GEN
Adder
5.944
23906402RICHG1
Adder
1.189
23906502RICHG2&3
Adder
1.187
23867002DVBSG1
50/50
10.407
972211AH1-690 GEN
50/50
238.133
241886AC2-103 GEN2
Solar/Wind Harmer
14.419
24191202EL_AA1-006
Adder
0.297
970817AG2-515 GEN
Solar/Wind Harmer
13.044
945411AF1-206 GEN
Solar/Wind Harmer
7.213
270499AE1-146 GEN
Solar/Wind Harmer
2.343
945641AF1-229 GEN
Solar/Wind Harmer
3.229
970159AG2-109 GEN
Solar/Wind Harmer
3.418
270297AD1-101 GEN
Solar/Wind Harmer
1.75
971549AH1-272 GEN
Solar/Wind Harmer
11.155
966831AG1-554 GEN
Solar/Wind Harmer
0.704
971989AH1-539 GEN
Solar/Wind Harmer
7.613
971567AH1-282 GEN
Solar/Wind Harmer
8.024
247607V1-011 GEN
Solar/Wind Harmer
2.098
957201AF2-014 GEN
Solar/Wind Harmer
2.368
270435AC2-044 GEN
Solar/Wind Harmer
1.044
944161AF1-084 GEN
Solar/Wind Harmer
1.106
965041AG1-368 GEN
Solar/Wind Harmer
4.881
965051AG1-369 GEN
Solar/Wind Harmer
2.43
270302AB2-170 GEN
Solar/Wind Harmer
3.966
270317AD1-130_GEN
Solar/Wind Harmer
1.52
971219AH1-069 GEN
Solar/Wind Harmer
0.796
971771AH1-392 GEN
Solar/Wind Harmer
4.129
971769AH1-391 GEN
Solar/Wind Harmer
4.471
270578AF1-285 GEN2
Solar/Wind Harmer
0.204
970179AG2-119 GEN
Solar/Wind Harmer
3.495
963791AG1-232 GEN
Solar/Wind Harmer
5.807
960681AF2-359 GEN
Solar/Wind Harmer
1.625
241982AE2-343 S C
Solar/Wind Helper
0.109
254304AE2-114 C
Solar/Wind Helper
0.104
241997AF1-093 GEN
Solar/Wind Helper
0.121
270361_3
Solar/Wind Harmer
8.521
960841AF2-375 GEN
Solar/Wind Harmer
3.749
270428AC2-015 C
Solar/Wind Harmer
4.415
247522W1-056 GEN
Solar/Wind Harmer
1.589
970515AG2-329 GEN
Solar/Wind Harmer
10.227
970905AG2-564 GEN
Solar/Wind Harmer
3.497
944231AF1-091 GEN
Solar/Wind Harmer
2.19
241847AF2-150_GEN
Solar/Wind Harmer
2.294
246936BC-WTG1
Solar/Wind Harmer
2.043
270489AE1-102 GEN1
Solar/Wind Harmer
0.679
965421AG1-410 GEN
Solar/Wind Harmer
15.499
24695305TIMB G C
Solar/Wind Harmer
2.781
270449AD2-020 GEN
Solar/Wind Harmer
1.385
943021AE2-325 GEN
Solar/Wind Harmer
1.799
247521TR3_G114
Solar/Wind Harmer
1.636
270246TR4_N_V150
Solar/Wind Harmer
0.414
945111AF1-176 GEN
Solar/Wind Harmer
8.634
270505AE1-170 C O1
Solar/Wind Harmer
7.249
270462AD2-086
Solar/Wind Harmer
3.299
24639705ELKHART HY
Adder
0.072
270063AE2-323 C
Solar/Wind Harmer
1.038
971221AH1-070 GEN
Solar/Wind Harmer
0.796
965011AG1-365 GEN
Solar/Wind Harmer
4.645
241813AF1-122_GEN
Solar/Wind Harmer
2.935
270223U2-072_GEN1
Solar/Wind Harmer
0.868
270578AF1-285 GEN2
Solar/Wind Harmer
0.531
270391AF1-285 GEN3
Solar/Wind Harmer
0.531
961971AG1-040 GEN
Solar/Wind Helper
0.251
203835AF1-098 GEN
Solar/Wind Helper
0.992
241966AE1-183 GEN
Solar/Wind Helper
0.121
203860AG1-193 C
Solar/Wind Helper
0.116
254303AC2-168 GEN
Solar/Wind Helper
0.071
957071AF2-004 GEN
50/50
12.095
23917502WLORG-6
50/50
0.764
23857102WLORG-A
50/50
9.096
23929302BS-PKR
50/50
2.106
241832AE2-181_GEN
Solar/Wind Harmer
1.75
958321AF2-126 GEN
Solar/Wind Harmer
1.366
23906502RICHG2&3
Adder
1.187
270575GUS2 35KV
Solar/Wind Harmer
10.039
270541AE2-072 C
Solar/Wind Harmer
3.99
970217AG2-149 GEN
Solar/Wind Harmer
22.552
270588AE1-091_GEN
Solar/Wind Harmer
6.591
270044AE2-322 C
Solar/Wind Harmer
0.769
270404AC1-167 GEN
Solar/Wind Harmer
0.641
270258AD1-119 GEN
Solar/Wind Harmer
1.565
961961AG1-039 GEN
Solar/Wind Harmer
1.583
958091AF2-103 GEN
Solar/Wind Harmer
0.086
247604X1-042
Adder
0.22
270491AE1-102 GEN2
Solar/Wind Harmer
0.679
24441205WTRV SLR C
Solar/Wind Harmer
0.07
270377AD1-106 GEN
Solar/Wind Harmer
3.082
270191TR4_S_V150
Solar/Wind Harmer
1.46
270247TR4_N_V136
Solar/Wind Harmer
0.414
945111AF1-176 GEN
Solar/Wind Harmer
2.737
270485AE1-090_GEN
Solar/Wind Harmer
0.287
24642205MAYFLWER
Adder
0.299
970031AG2-029 GEN
Solar/Wind Harmer
14.083
247643Z2-116 C
Solar/Wind Harmer
0.032
959331AF2-224 GEN
Solar/Wind Harmer
4.645
965021AG1-366 GEN
Solar/Wind Harmer
1.08
970065AG2-057 GEN
Solar/Wind Harmer
0.459
942871AE2-306 GEN
Solar/Wind Harmer
0.398
270391AF1-285 GEN3
Solar/Wind Harmer
0.204
270043AE2-236 GEN
Solar/Wind Harmer
2.394
962511AG1-100 GEN
Solar/Wind Helper
0.255
203830AF1-094 GEN
Solar/Wind Helper
0.245
254305AE2-115 C
Solar/Wind Helper
0.104
959441AF2-235 GEN
Solar/Wind Helper
0.115
23917202WLORG-3
50/50
1.553
23917302WLORG-4
50/50
1.519
966311AG1-500 GEN
50/50
141.29
23857202WLORG-B
50/50
9.372
24190002OREGON_ST1
50/50
2.971
24189802OREGON_CT1
50/50
2.254
241996AE2-282_GEN
Solar/Wind Harmer
1.931
971677AH1-339 GEN
Solar/Wind Harmer
6.773
270007AE1-245 C
Solar/Wind Harmer
3.147
942801AE2-298 GEN
Solar/Wind Harmer
0.797
246938BC-WTG3
Solar/Wind Harmer
2.078
246937BC-WTG2
Solar/Wind Harmer
2.043
971231AH1-075 GEN
Solar/Wind Harmer
0.399
961051AF2-396 GEN
Solar/Wind Harmer
7.783
961051AF2-396 GEN
Solar/Wind Harmer
3.62
960981AF2-389 GEN
Solar/Wind Harmer
0.728
957891AF2-083 GEN
Solar/Wind Harmer
1.625
247620Y3-023
Adder
0.218
270216AD2-079_GEN
Solar/Wind Harmer
0.283
970611AG2-400 GEN
Solar/Wind Harmer
4.645
971201AH1-060 GEN
Solar/Wind Harmer
0.917
270526AF1-158 GEN
Solar/Wind Harmer
2.042
24441505OLIV SLR
Solar/Wind Harmer
0.06
270224U2-072_GEN2
Solar/Wind Harmer
0.868
270227U2-072_GEN3
Solar/Wind Harmer
0.868
270228U2-072_GEN4
Solar/Wind Harmer
0.868
270231U2-072_GEN5
Solar/Wind Harmer
0.868
241960AC2-195 GEN
Solar/Wind Harmer
1.215
965681AG1-436 GEN
Solar/Wind Harmer
5.376
965791AG1-447 GEN
Solar/Wind Harmer
2.75
203947AF1-006 C
Solar/Wind Helper
0.283
241967AE2-285_GEN
Solar/Wind Helper
0.314
241801AE1-079 GEN
Solar/Wind Helper
0.122
203980AG1-197 GEN
Solar/Wind Helper
0.188
241985AE1-237 GEN
Solar/Wind Helper
0.122
203979AG1-198 GEN
Solar/Wind Helper
0.147
962101AG1-054 GEN
Solar/Wind Helper
0.304
990527J1329
External Queue
1.536989450454712
990142J1224
External Queue
11.235392570495605
991177J1571 G
External Queue
13.065269470214844
LAGNLTFEXP_LAGN->PJM
CLTF
4.111
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.536
TVALTFEXP_TVA->PJM
CLTF
1.857
CPLELTFEXP_CPLE->PJM
CLTF
0.14
CBM West 2LTFEXP_CBM-W2->PJM
CBM
33.236
CBM West 1LTFEXP_CBM-W1->PJM
CBM
79.335
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.4
MECLTFEXP_MEC->PJM
CLTF
5.472
SIGELTFEXP_SIGE->PJM
CLTF
0.142
NYPJM->LTFIMP_NY
CLTF
1.797
LGEELTFEXP_LGEE->PJM
CLTF
1.709
WECLTFEXP_WEC->PJM
CLTF
1.408
AG2-052LTFEXP_AG2-052->PJM
LTF
0.091
AH1-155LTFEXP_AH1-155->PJM
LTF
0.136

Details for 02BEAVER-02LAKEAVE 345.0 kV Ckt 1 line l/o ATSI_P2-3_OEC-345-901_SRT-SL


Base Case Flowgate

Area:ATSI
Facility Description:
02BEAVER-02LAKEAVE 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_OEC-345-901_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.76 %
Rating:1720.0 MVA
Rating Type:B
MVA to Mitigate:1956.7
MW Contribution:0.36
Bus #Bus NameTypeMW Contribution
23917202WLORG-3
50/50
1.38
23917302WLORG-4
50/50
1.349
966311AG1-500 GEN
50/50
125.486
24190002OREGON_ST1
50/50
2.61
24189802OREGON_CT1
50/50
1.98
241996AE2-282_GEN
Solar/Wind Harmer
1.697
23857202WLORG-B
Adder
4.429
971677AH1-339 GEN
Solar/Wind Harmer
5.947
270007AE1-245 C
Solar/Wind Harmer
2.879
942801AE2-298 GEN
Solar/Wind Harmer
0.729
246938BC-WTG3
Solar/Wind Harmer
1.905
246937BC-WTG2
Solar/Wind Harmer
1.873
961051AF2-396 GEN
Solar/Wind Harmer
7.181
961051AF2-396 GEN
Solar/Wind Harmer
3.34
971231AH1-075 GEN
Solar/Wind Harmer
0.362
960981AF2-389 GEN
Solar/Wind Harmer
0.673
957891AF2-083 GEN
Solar/Wind Harmer
1.501
247620Y3-023
Adder
0.202
270216AD2-079_GEN
Solar/Wind Harmer
0.262
970611AG2-400 GEN
Solar/Wind Harmer
4.301
203947AF1-006 C
Solar/Wind Helper
0.458
203980AG1-197 GEN
Solar/Wind Helper
0.296
203979AG1-198 GEN
Solar/Wind Helper
0.229
241967AE2-285_GEN
Solar/Wind Helper
0.308
241801AE1-079 GEN
Solar/Wind Helper
0.12
241985AE1-237 GEN
Solar/Wind Helper
0.119
946381AF1-302 GEN
Solar/Wind Helper
0.11
238217AF1-153 C O1
Solar/Wind Helper
0.118
962101AG1-054 GEN
Solar/Wind Helper
0.295
23867002DVBSG1
50/50
9.149
972211AH1-690 GEN
50/50
209.151
241886AC2-103 GEN2
Solar/Wind Harmer
12.757
970817AG2-515 GEN
Solar/Wind Harmer
11.458
24191202EL_AA1-006
Adder
0.247
945411AF1-206 GEN
Solar/Wind Harmer
6.338
270499AE1-146 GEN
Solar/Wind Harmer
2.056
945641AF1-229 GEN
Solar/Wind Harmer
2.848
970159AG2-109 GEN
Solar/Wind Harmer
2.554
270297AD1-101 GEN
Solar/Wind Harmer
1.58
971549AH1-272 GEN
Solar/Wind Harmer
10.147
966831AG1-554 GEN
Solar/Wind Harmer
0.634
971989AH1-539 GEN
Solar/Wind Harmer
6.852
247607V1-011 GEN
Solar/Wind Harmer
1.919
971567AH1-282 GEN
Solar/Wind Harmer
7.189
957201AF2-014 GEN
Solar/Wind Harmer
2.171
270435AC2-044 GEN
Solar/Wind Harmer
0.957
944161AF1-084 GEN
Solar/Wind Harmer
1.019
965041AG1-368 GEN
Solar/Wind Harmer
4.498
965051AG1-369 GEN
Solar/Wind Harmer
2.239
270302AB2-170 GEN
Solar/Wind Harmer
3.666
270317AD1-130_GEN
Solar/Wind Harmer
1.405
203846AF2-130 C
Solar/Wind Helper
0.272
203804AE2-113_GEN
Solar/Wind Helper
0.933
241982AE2-343 S C
Solar/Wind Helper
0.107
254304AE2-114 C
Solar/Wind Helper
0.102
241997AF1-093 GEN
Solar/Wind Helper
0.118
23917402WLORG-5
50/50
1.356
23917102WLORG-2
50/50
1.337
24189902OREGON_CT2
50/50
1.94
23856402BAYSG1
50/50
1.043
241885AC2-103 GEN1
Solar/Wind Harmer
12.757
241807AE2-176_GEN
Solar/Wind Harmer
5.062
972253AH1-711 GEN
Adder
38.383
241858AF1-205_GEN
Solar/Wind Harmer
4.326
241808AF1-120 C
Solar/Wind Harmer
0.946
23920202STRYCT
Adder
1.415
241840AF1-064_GEN
Solar/Wind Harmer
1.119
972301AH1-735 GEN
Adder
5.258
23906402RICHG1
Adder
1.052
23906502RICHG2&3
Adder
1.05
270361_3
Solar/Wind Harmer
7.454
960841AF2-375 GEN
Solar/Wind Harmer
3.283
966321AG1-501 GEN
Adder
0.867
957111AF2-005 GEN
Adder
0.693
270428AC2-015 C
Solar/Wind Harmer
3.75
247522W1-056 GEN
Solar/Wind Harmer
1.41
970515AG2-329 GEN
Solar/Wind Harmer
9.037
970905AG2-564 GEN
Solar/Wind Harmer
2.954
944231AF1-091 GEN
Solar/Wind Harmer
1.993
241847AF2-150_GEN
Solar/Wind Harmer
1.989
246936BC-WTG1
Solar/Wind Harmer
1.873
270489AE1-102 GEN1
Solar/Wind Harmer
0.622
965421AG1-410 GEN
Solar/Wind Harmer
14.219
24695305TIMB G C
Solar/Wind Harmer
2.555
270449AD2-020 GEN
Solar/Wind Harmer
1.277
943021AE2-325 GEN
Solar/Wind Harmer
1.659
247521TR3_G114
Solar/Wind Harmer
1.508
270246TR4_N_V150
Solar/Wind Harmer
0.381
945111AF1-176 GEN
Solar/Wind Harmer
7.974
270505AE1-170 C O1
Solar/Wind Harmer
6.696
270462AD2-086
Solar/Wind Harmer
3.05
24639705ELKHART HY
Adder
0.067
270063AE2-323 C
Solar/Wind Harmer
0.96
965011AG1-365 GEN
Solar/Wind Harmer
4.301
961971AG1-040 GEN
Solar/Wind Helper
0.397
203835AF1-098 GEN
Solar/Wind Helper
1.566
203860AG1-193 C
Solar/Wind Helper
0.172
241966AE1-183 GEN
Solar/Wind Helper
0.118
203954AE2-126 C
Solar/Wind Helper
0.23
254303AC2-168 GEN
Solar/Wind Helper
0.068
957071AF2-004 GEN
50/50
10.742
23929302BS-PKR
50/50
1.836
241832AE2-181_GEN
Solar/Wind Harmer
1.539
958321AF2-126 GEN
Solar/Wind Harmer
1.2
23906502RICHG2&3
Adder
1.05
270575GUS2 35KV
Solar/Wind Harmer
8.781
23857102WLORG-A
Adder
4.299
270541AE2-072 C
Solar/Wind Harmer
3.537
970217AG2-149 GEN
Solar/Wind Harmer
19.929
270588AE1-091_GEN
Solar/Wind Harmer
5.941
270044AE2-322 C
Solar/Wind Harmer
0.699
270404AC1-167 GEN
Solar/Wind Harmer
0.582
270258AD1-119 GEN
Solar/Wind Harmer
1.426
958091AF2-103 GEN
Solar/Wind Harmer
0.078
247604X1-042
Adder
0.202
961961AG1-039 GEN
Solar/Wind Harmer
1.372
270491AE1-102 GEN2
Solar/Wind Harmer
0.622
24441205WTRV SLR C
Solar/Wind Harmer
0.064
270377AD1-106 GEN
Solar/Wind Harmer
2.793
270191TR4_S_V150
Solar/Wind Harmer
1.345
270247TR4_N_V136
Solar/Wind Harmer
0.381
945111AF1-176 GEN
Solar/Wind Harmer
2.527
270485AE1-090_GEN
Solar/Wind Harmer
0.265
24642205MAYFLWER
Adder
0.277
970031AG2-029 GEN
Solar/Wind Harmer
13.034
247643Z2-116 C
Solar/Wind Harmer
0.03
959331AF2-224 GEN
Solar/Wind Harmer
4.301
965021AG1-366 GEN
Solar/Wind Harmer
1
962511AG1-100 GEN
Solar/Wind Helper
0.409
203830AF1-094 GEN
Solar/Wind Helper
0.382
959441AF2-235 GEN
Solar/Wind Helper
0.168
20334926Z1-069 C
Solar/Wind Helper
0.688
254305AE2-115 C
Solar/Wind Helper
0.102
990527J1329
External Queue
1.3126888275146484
990142J1224
External Queue
9.595755577087402
991177J1571 G
External Queue
11.149422645568848
LAGNLTFEXP_LAGN->PJM
CLTF
4.111
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.004
TVALTFEXP_TVA->PJM
CLTF
1.884
CPLELTFEXP_CPLE->PJM
CLTF
0.338
CBM West 2LTFEXP_CBM-W2->PJM
CBM
32.563
CBM West 1LTFEXP_CBM-W1->PJM
CBM
72.576
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.464
MECLTFEXP_MEC->PJM
CLTF
5.219
SIGELTFEXP_SIGE->PJM
CLTF
0.139
NYPJM->LTFIMP_NY
CLTF
1.974
LGEELTFEXP_LGEE->PJM
CLTF
1.688
WECLTFEXP_WEC->PJM
CLTF
1.329
AG2-052LTFEXP_AG2-052->PJM
LTF
0.085
AH1-155LTFEXP_AH1-155->PJM
LTF
0.128

Details for 02BEAVER-02LAKEAVE 345.0 kV Ckt 1 line l/o ATSI_P2-3_OEC-345-007A_SRT-SL


Base Case Flowgate

Area:ATSI
Facility Description:
02BEAVER-02LAKEAVE 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_OEC-345-007A_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.78 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:1967.82
MW Contribution:0.35
Bus #Bus NameTypeMW Contribution
23867002DVBSG1
50/50
9.378
972211AH1-690 GEN
50/50
212.091
241886AC2-103 GEN2
Solar/Wind Harmer
13.312
970817AG2-515 GEN
Solar/Wind Harmer
11.575
945411AF1-206 GEN
Solar/Wind Harmer
6.379
24191202EL_AA1-006
Adder
0.223
270499AE1-146 GEN
Solar/Wind Harmer
2.029
945641AF1-229 GEN
Solar/Wind Harmer
2.819
270297AD1-101 GEN
Solar/Wind Harmer
1.573
971549AH1-272 GEN
Solar/Wind Harmer
10.193
966831AG1-554 GEN
Solar/Wind Harmer
0.62
971989AH1-539 GEN
Solar/Wind Harmer
6.706
247607V1-011 GEN
Solar/Wind Harmer
1.912
957201AF2-014 GEN
Solar/Wind Harmer
2.164
270435AC2-044 GEN
Solar/Wind Harmer
0.954
944161AF1-084 GEN
Solar/Wind Harmer
1.021
971567AH1-282 GEN
Solar/Wind Harmer
6.891
970159AG2-109 GEN
Solar/Wind Harmer
1.835
965041AG1-368 GEN
Solar/Wind Harmer
4.486
965051AG1-369 GEN
Solar/Wind Harmer
2.232
270302AB2-170 GEN
Solar/Wind Harmer
3.641
270317AD1-130_GEN
Solar/Wind Harmer
1.396
203846AF2-130 C
Solar/Wind Helper
0.27
203804AE2-113_GEN
Solar/Wind Helper
0.928
241982AE2-343 S C
Solar/Wind Helper
0.106
254304AE2-114 C
Solar/Wind Helper
0.101
241997AF1-093 GEN
Solar/Wind Helper
0.117
957071AF2-004 GEN
50/50
11.332
23929302BS-PKR
Adder
1.735
241832AE2-181_GEN
Solar/Wind Harmer
1.549
958321AF2-126 GEN
Solar/Wind Harmer
1.204
23906502RICHG2&3
Adder
1.054
270575GUS2 35KV
Solar/Wind Harmer
8.659
270541AE2-072 C
Solar/Wind Harmer
3.532
970217AG2-149 GEN
Solar/Wind Harmer
19.363
270588AE1-091_GEN
Solar/Wind Harmer
5.847
270044AE2-322 C
Solar/Wind Harmer
0.698
270404AC1-167 GEN
Solar/Wind Harmer
0.581
270258AD1-119 GEN
Solar/Wind Harmer
1.423
247604X1-042
Adder
0.202
958091AF2-103 GEN
Solar/Wind Harmer
0.078
270491AE1-102 GEN2
Solar/Wind Harmer
0.62
24441205WTRV SLR C
Solar/Wind Harmer
0.064
945111AF1-176 GEN
Solar/Wind Harmer
2.531
270191TR4_S_V150
Solar/Wind Harmer
1.341
270247TR4_N_V136
Solar/Wind Harmer
0.38
961961AG1-039 GEN
Solar/Wind Harmer
1.258
24642205MAYFLWER
Adder
0.277
270377AD1-106 GEN
Solar/Wind Harmer
2.69
270485AE1-090_GEN
Solar/Wind Harmer
0.263
970031AG2-029 GEN
Solar/Wind Harmer
13.034
247643Z2-116 C
Solar/Wind Harmer
0.03
962511AG1-100 GEN
Solar/Wind Helper
0.406
203830AF1-094 GEN
Solar/Wind Helper
0.379
959441AF2-235 GEN
Solar/Wind Helper
0.167
20334926Z1-069 C
Solar/Wind Helper
0.684
254305AE2-115 C
Solar/Wind Helper
0.101
23917202WLORG-3
50/50
1.455
23917302WLORG-4
50/50
1.423
966311AG1-500 GEN
50/50
132.376
24190002OREGON_ST1
50/50
2.646
24189802OREGON_CT1
50/50
2.007
241996AE2-282_GEN
Solar/Wind Harmer
1.708
971677AH1-339 GEN
Solar/Wind Harmer
5.827
270007AE1-245 C
Solar/Wind Harmer
2.868
942801AE2-298 GEN
Solar/Wind Harmer
0.727
246938BC-WTG3
Solar/Wind Harmer
1.899
246937BC-WTG2
Solar/Wind Harmer
1.867
961051AF2-396 GEN
Solar/Wind Harmer
7.193
961051AF2-396 GEN
Solar/Wind Harmer
3.346
960981AF2-389 GEN
Solar/Wind Harmer
0.674
957891AF2-083 GEN
Solar/Wind Harmer
1.504
247620Y3-023
Adder
0.202
971231AH1-075 GEN
Solar/Wind Harmer
0.349
270216AD2-079_GEN
Solar/Wind Harmer
0.262
203947AF1-006 C
Solar/Wind Helper
0.455
203980AG1-197 GEN
Solar/Wind Helper
0.294
203979AG1-198 GEN
Solar/Wind Helper
0.227
241801AE1-079 GEN
Solar/Wind Helper
0.119
241967AE2-285_GEN
Solar/Wind Helper
0.305
241985AE1-237 GEN
Solar/Wind Helper
0.118
946381AF1-302 GEN
Solar/Wind Helper
0.109
238217AF1-153 C O1
Solar/Wind Helper
0.117
962101AG1-054 GEN
Solar/Wind Helper
0.293
23917402WLORG-5
50/50
1.431
23917102WLORG-2
50/50
1.41
24189902OREGON_CT2
50/50
1.967
241885AC2-103 GEN1
Solar/Wind Harmer
13.312
241807AE2-176_GEN
Solar/Wind Harmer
4.79
972253AH1-711 GEN
Adder
38.846
241858AF1-205_GEN
Solar/Wind Harmer
4.354
241808AF1-120 C
Solar/Wind Harmer
0.952
23920202STRYCT
Adder
1.423
241840AF1-064_GEN
Solar/Wind Harmer
1.123
972301AH1-735 GEN
Adder
5.278
23906402RICHG1
Adder
1.056
23906502RICHG2&3
Adder
1.054
270361_3
Solar/Wind Harmer
7.35
960841AF2-375 GEN
Solar/Wind Harmer
3.239
270428AC2-015 C
Solar/Wind Harmer
3.47
247522W1-056 GEN
Solar/Wind Harmer
1.38
970515AG2-329 GEN
Solar/Wind Harmer
8.781
970905AG2-564 GEN
Solar/Wind Harmer
2.663
944231AF1-091 GEN
Solar/Wind Harmer
1.994
246936BC-WTG1
Solar/Wind Harmer
1.867
270489AE1-102 GEN1
Solar/Wind Harmer
0.62
965421AG1-410 GEN
Solar/Wind Harmer
14.177
24695305TIMB G C
Solar/Wind Harmer
2.547
270449AD2-020 GEN
Solar/Wind Harmer
1.279
943021AE2-325 GEN
Solar/Wind Harmer
1.662
945111AF1-176 GEN
Solar/Wind Harmer
7.986
247521TR3_G114
Solar/Wind Harmer
1.503
270246TR4_N_V150
Solar/Wind Harmer
0.38
270505AE1-170 C O1
Solar/Wind Harmer
6.706
241847AF2-150_GEN
Solar/Wind Harmer
1.823
24639705ELKHART HY
Adder
0.067
270063AE2-323 C
Solar/Wind Harmer
0.96
270462AD2-086
Solar/Wind Harmer
3.029
961971AG1-040 GEN
Solar/Wind Helper
0.395
203835AF1-098 GEN
Solar/Wind Helper
1.556
203860AG1-193 C
Solar/Wind Helper
0.17
241966AE1-183 GEN
Solar/Wind Helper
0.117
203954AE2-126 C
Solar/Wind Helper
0.228
254303AC2-168 GEN
Solar/Wind Helper
0.067
990527J1329
External Queue
1.333598017692566
990142J1224
External Queue
9.748601913452148
991177J1571 G
External Queue
11.313738822937012
LAGNLTFEXP_LAGN->PJM
CLTF
4.085
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.967
TVALTFEXP_TVA->PJM
CLTF
1.87
CPLELTFEXP_CPLE->PJM
CLTF
0.326
CBM West 2LTFEXP_CBM-W2->PJM
CBM
32.394
CBM West 1LTFEXP_CBM-W1->PJM
CBM
72.887
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.407
MECLTFEXP_MEC->PJM
CLTF
5.205
SIGELTFEXP_SIGE->PJM
CLTF
0.138
NYPJM->LTFIMP_NY
CLTF
1.964
LGEELTFEXP_LGEE->PJM
CLTF
1.675
WECLTFEXP_WEC->PJM
CLTF
1.327
AG2-052LTFEXP_AG2-052->PJM
LTF
0.085
AH1-155LTFEXP_AH1-155->PJM
LTF
0.128

Details for 02BEAVER-02LAKEAVE 345.0 kV Ckt 1 line l/o ATSI_P2-3_OEC-345-031_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02BEAVER-02LAKEAVE 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_OEC-345-031_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.84 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:1893.72
MW Contribution:0.36
Bus #Bus NameTypeMW Contribution
23917402WLORG-5
50/50
1.318
23917102WLORG-2
50/50
1.299
24189902OREGON_CT2
50/50
1.916
23856402BAYSG1
50/50
1.035
241885AC2-103 GEN1
Solar/Wind Harmer
12.452
241807AE2-176_GEN
Solar/Wind Harmer
5.144
972253AH1-711 GEN
Adder
37.939
241858AF1-205_GEN
Solar/Wind Harmer
4.286
241808AF1-120 C
Solar/Wind Harmer
0.937
23920202STRYCT
Adder
1.402
241840AF1-064_GEN
Solar/Wind Harmer
1.11
966321AG1-501 GEN
Adder
1.036
957111AF2-005 GEN
Adder
0.829
972301AH1-735 GEN
Adder
5.214
23906402RICHG1
Adder
1.043
23906502RICHG2&3
Adder
1.042
270361_3
Solar/Wind Harmer
7.442
960841AF2-375 GEN
Solar/Wind Harmer
3.277
270428AC2-015 C
Solar/Wind Harmer
3.83
247522W1-056 GEN
Solar/Wind Harmer
1.411
970515AG2-329 GEN
Solar/Wind Harmer
9.065
970905AG2-564 GEN
Solar/Wind Harmer
3.041
944231AF1-091 GEN
Solar/Wind Harmer
1.98
241847AF2-150_GEN
Solar/Wind Harmer
2.034
246936BC-WTG1
Solar/Wind Harmer
1.863
270489AE1-102 GEN1
Solar/Wind Harmer
0.619
965421AG1-410 GEN
Solar/Wind Harmer
14.14
24695305TIMB G C
Solar/Wind Harmer
2.541
270449AD2-020 GEN
Solar/Wind Harmer
1.268
943021AE2-325 GEN
Solar/Wind Harmer
1.647
247521TR3_G114
Solar/Wind Harmer
1.5
270246TR4_N_V150
Solar/Wind Harmer
0.379
945111AF1-176 GEN
Solar/Wind Harmer
7.917
270505AE1-170 C O1
Solar/Wind Harmer
6.647
270462AD2-086
Solar/Wind Harmer
3.037
24639705ELKHART HY
Adder
0.066
270063AE2-323 C
Solar/Wind Harmer
0.954
961971AG1-040 GEN
Solar/Wind Helper
0.397
203835AF1-098 GEN
Solar/Wind Helper
1.564
203860AG1-193 C
Solar/Wind Helper
0.171
241966AE1-183 GEN
Solar/Wind Helper
0.118
203954AE2-126 C
Solar/Wind Helper
0.229
254303AC2-168 GEN
Solar/Wind Helper
0.068
957071AF2-004 GEN
50/50
10.437
23929302BS-PKR
50/50
1.821
241832AE2-181_GEN
Solar/Wind Harmer
1.524
958321AF2-126 GEN
Solar/Wind Harmer
1.19
23857102WLORG-A
Adder
5.14
23906502RICHG2&3
Adder
1.042
270575GUS2 35KV
Solar/Wind Harmer
8.767
270541AE2-072 C
Solar/Wind Harmer
3.515
970217AG2-149 GEN
Solar/Wind Harmer
19.989
270588AE1-091_GEN
Solar/Wind Harmer
5.936
270044AE2-322 C
Solar/Wind Harmer
0.695
270404AC1-167 GEN
Solar/Wind Harmer
0.579
270258AD1-119 GEN
Solar/Wind Harmer
1.418
961961AG1-039 GEN
Solar/Wind Harmer
1.403
958091AF2-103 GEN
Solar/Wind Harmer
0.078
247604X1-042
Adder
0.2
270491AE1-102 GEN2
Solar/Wind Harmer
0.619
24441205WTRV SLR C
Solar/Wind Harmer
0.064
270377AD1-106 GEN
Solar/Wind Harmer
2.813
270191TR4_S_V150
Solar/Wind Harmer
1.338
270247TR4_N_V136
Solar/Wind Harmer
0.379
945111AF1-176 GEN
Solar/Wind Harmer
2.509
270485AE1-090_GEN
Solar/Wind Harmer
0.264
24642205MAYFLWER
Adder
0.275
970031AG2-029 GEN
Solar/Wind Harmer
12.948
962511AG1-100 GEN
Solar/Wind Helper
0.408
203830AF1-094 GEN
Solar/Wind Helper
0.381
959441AF2-235 GEN
Solar/Wind Helper
0.168
20334926Z1-069 C
Solar/Wind Helper
0.686
254305AE2-115 C
Solar/Wind Helper
0.102
23867002DVBSG1
50/50
8.998
972211AH1-690 GEN
50/50
206.563
24191202EL_AA1-006
50/50
0.275
241886AC2-103 GEN2
Solar/Wind Harmer
12.452
970817AG2-515 GEN
Solar/Wind Harmer
11.334
945411AF1-206 GEN
Solar/Wind Harmer
6.279
270499AE1-146 GEN
Solar/Wind Harmer
2.052
945641AF1-229 GEN
Solar/Wind Harmer
2.838
970159AG2-109 GEN
Solar/Wind Harmer
2.868
270297AD1-101 GEN
Solar/Wind Harmer
1.572
971549AH1-272 GEN
Solar/Wind Harmer
10.061
966831AG1-554 GEN
Solar/Wind Harmer
0.634
971989AH1-539 GEN
Solar/Wind Harmer
6.861
971567AH1-282 GEN
Solar/Wind Harmer
7.246
247607V1-011 GEN
Solar/Wind Harmer
1.909
957201AF2-014 GEN
Solar/Wind Harmer
2.159
270435AC2-044 GEN
Solar/Wind Harmer
0.952
944161AF1-084 GEN
Solar/Wind Harmer
1.011
965041AG1-368 GEN
Solar/Wind Harmer
4.473
23917202WLORG-3
50/50
1.34
23917302WLORG-4
50/50
1.311
966311AG1-500 GEN
50/50
121.92
24190002OREGON_ST1
50/50
2.577
24189802OREGON_CT1
50/50
1.955
241996AE2-282_GEN
Solar/Wind Harmer
1.681
23857202WLORG-B
Adder
5.296
971677AH1-339 GEN
Solar/Wind Harmer
5.951
270007AE1-245 C
Solar/Wind Harmer
2.864
942801AE2-298 GEN
Solar/Wind Harmer
0.726
246938BC-WTG3
Solar/Wind Harmer
1.895
246937BC-WTG2
Solar/Wind Harmer
1.863
971231AH1-075 GEN
Solar/Wind Harmer
0.364
961051AF2-396 GEN
Solar/Wind Harmer
7.128
961051AF2-396 GEN
Solar/Wind Harmer
3.316
960981AF2-389 GEN
Solar/Wind Harmer
0.668
957891AF2-083 GEN
Solar/Wind Harmer
1.491
247620Y3-023
Adder
0.2
203947AF1-006 C
Solar/Wind Helper
0.458
203980AG1-197 GEN
Solar/Wind Helper
0.295
203979AG1-198 GEN
Solar/Wind Helper
0.229
241801AE1-079 GEN
Solar/Wind Helper
0.119
241967AE2-285_GEN
Solar/Wind Helper
0.307
241985AE1-237 GEN
Solar/Wind Helper
0.119
946381AF1-302 GEN
Solar/Wind Helper
0.11
238217AF1-153 C O1
Solar/Wind Helper
0.117
962101AG1-054 GEN
Solar/Wind Helper
0.294
965051AG1-369 GEN
Solar/Wind Harmer
2.227
270302AB2-170 GEN
Solar/Wind Harmer
3.651
270317AD1-130_GEN
Solar/Wind Harmer
1.4
203846AF2-130 C
Solar/Wind Helper
0.271
203804AE2-113_GEN
Solar/Wind Helper
0.931
241982AE2-343 S C
Solar/Wind Helper
0.107
254304AE2-114 C
Solar/Wind Helper
0.102
241997AF1-093 GEN
Solar/Wind Helper
0.118
990527J1329
External Queue
1.2952468395233154
990142J1224
External Queue
9.468253135681152
991177J1571 G
External Queue
11.006390571594238
LAGNLTFEXP_LAGN->PJM
CLTF
4.096
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.011
TVALTFEXP_TVA->PJM
CLTF
1.879
CPLELTFEXP_CPLE->PJM
CLTF
0.342
CBM West 2LTFEXP_CBM-W2->PJM
CBM
32.428
CBM West 1LTFEXP_CBM-W1->PJM
CBM
71.973
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.443
MECLTFEXP_MEC->PJM
CLTF
5.19
SIGELTFEXP_SIGE->PJM
CLTF
0.138
NYPJM->LTFIMP_NY
CLTF
1.967
LGEELTFEXP_LGEE->PJM
CLTF
1.683
WECLTFEXP_WEC->PJM
CLTF
1.321
AG2-052LTFEXP_AG2-052->PJM
LTF
0.085
AH1-155LTFEXP_AH1-155->PJM
LTF
0.127

Details for 02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line l/o ATSI_P2-3_OEC-345-002_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line
Contingency Name:
ATSI_P2-3_OEC-345-002_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:174.17 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:3270.93
MW Contribution:0.51
Bus #Bus NameTypeMW Contribution
23917402WLORG-5
50/50
1.92
23917102WLORG-2
50/50
1.892
24189902OREGON_CT2
50/50
2.76
23856402BAYSG1
50/50
1.489
241885AC2-103 GEN1
Solar/Wind Harmer
18.089
241807AE2-176_GEN
Solar/Wind Harmer
7.368
972253AH1-711 GEN
Adder
54.605
241858AF1-205_GEN
Solar/Wind Harmer
6.156
966321AG1-501 GEN
Adder
1.655
957111AF2-005 GEN
Adder
1.324
241808AF1-120 C
Solar/Wind Harmer
1.346
23920202STRYCT
Adder
2.011
241840AF1-064_GEN
Solar/Wind Harmer
1.592
972301AH1-735 GEN
Adder
7.456
23906402RICHG1
Adder
1.491
23906502RICHG2&3
Adder
1.489
270361_3
Solar/Wind Harmer
10.624
960841AF2-375 GEN
Solar/Wind Harmer
4.677
270428AC2-015 C
Solar/Wind Harmer
5.418
247522W1-056 GEN
Solar/Wind Harmer
1.996
970515AG2-329 GEN
Solar/Wind Harmer
12.822
970905AG2-564 GEN
Solar/Wind Harmer
4.278
944231AF1-091 GEN
Solar/Wind Harmer
2.791
241847AF2-150_GEN
Solar/Wind Harmer
2.847
246936BC-WTG1
Solar/Wind Harmer
2.614
270489AE1-102 GEN1
Solar/Wind Harmer
0.868
965421AG1-410 GEN
Solar/Wind Harmer
19.836
24695305TIMB G C
Solar/Wind Harmer
3.562
270449AD2-020 GEN
Solar/Wind Harmer
1.777
943021AE2-325 GEN
Solar/Wind Harmer
2.309
247521TR3_G114
Solar/Wind Harmer
2.099
270246TR4_N_V150
Solar/Wind Harmer
0.531
945111AF1-176 GEN
Solar/Wind Harmer
11.092
270505AE1-170 C O1
Solar/Wind Harmer
9.313
270462AD2-086
Solar/Wind Harmer
4.24
23917202WLORG-3
50/50
1.953
23917302WLORG-4
50/50
1.91
966311AG1-500 GEN
50/50
177.624
24190002OREGON_ST1
50/50
3.713
24189802OREGON_CT1
50/50
2.816
23857202WLORG-B
Adder
8.455
241996AE2-282_GEN
Solar/Wind Harmer
2.414
971677AH1-339 GEN
Solar/Wind Harmer
8.462
270007AE1-245 C
Solar/Wind Harmer
4.022
942801AE2-298 GEN
Solar/Wind Harmer
1.019
246938BC-WTG3
Solar/Wind Harmer
2.659
246937BC-WTG2
Solar/Wind Harmer
2.614
971231AH1-075 GEN
Solar/Wind Harmer
0.508
961051AF2-396 GEN
Solar/Wind Harmer
9.992
961051AF2-396 GEN
Solar/Wind Harmer
4.648
960981AF2-389 GEN
Solar/Wind Harmer
0.936
957891AF2-083 GEN
Solar/Wind Harmer
2.088
247620Y3-023
Adder
0.281
270216AD2-079_GEN
Solar/Wind Harmer
0.363
970611AG2-400 GEN
Solar/Wind Harmer
5.975
270526AF1-158 GEN
Solar/Wind Harmer
2.631
24441505OLIV SLR
Solar/Wind Harmer
0.077
971201AH1-060 GEN
Solar/Wind Harmer
1.151
270224U2-072_GEN2
Solar/Wind Harmer
1.12
270227U2-072_GEN3
Solar/Wind Harmer
1.12
270228U2-072_GEN4
Solar/Wind Harmer
1.12
270231U2-072_GEN5
Solar/Wind Harmer
1.12
965681AG1-436 GEN
Solar/Wind Harmer
6.942
965791AG1-447 GEN
Solar/Wind Harmer
3.552
241960AC2-195 GEN
Solar/Wind Harmer
1.533
274808UNIV PK N;4U
Adder
2.553
942221AE2-234 GEN
Solar/Wind Harmer
0.373
274803UNIV PARK;6U
Adder
2.953
274888KELLY CRK;1U
Solar/Wind Harmer
2.977
274887GEN-1.85
Solar/Wind Harmer
2.688
276843GEN-1.7
Solar/Wind Harmer
0.289
958011AF2-095 GEN
Solar/Wind Harmer
7.261
274770LINCOLN ;1U
Adder
3.125
274771LINCOLN ;2U
Adder
3.125
972259AH1-714 GEN
Adder
9.55
274674JOLIET 9 ;6U
Adder
7.687
970321AG2-212 GEN
Solar/Wind Harmer
8.906
274696ROCKY RD ;4P
Adder
5.589
274695ROCKY RD ;2P
Adder
5.46
274693ROCKY RD ;1P
Adder
5.407
274697ROCKY RD ;3P
Adder
1.483
274683WAUKEGAN ;8U
Adder
10.328
274683WAUKEGAN ;8U
Adder
8.706
25326509SID D
Adder
0.633
274764LEE CO EC;5U
Adder
4.426
274765LEE CO EC;6U
Adder
4.426
203947AF1-006 C
Solar/Wind Helper
0.516
203980AG1-197 GEN
Solar/Wind Helper
0.336
957071AF2-004 GEN
50/50
15.205
23929302BS-PKR
50/50
2.62
23857102WLORG-A
Adder
8.207
241832AE2-181_GEN
Solar/Wind Harmer
2.188
958321AF2-126 GEN
Solar/Wind Harmer
1.707
23906502RICHG2&3
Adder
1.489
270575GUS2 35KV
Solar/Wind Harmer
12.516
270541AE2-072 C
Solar/Wind Harmer
5.011
970217AG2-149 GEN
Solar/Wind Harmer
28.273
270588AE1-091_GEN
Solar/Wind Harmer
8.353
270044AE2-322 C
Solar/Wind Harmer
0.979
270404AC1-167 GEN
Solar/Wind Harmer
0.816
270258AD1-119 GEN
Solar/Wind Harmer
1.996
961961AG1-039 GEN
Solar/Wind Harmer
1.964
958091AF2-103 GEN
Solar/Wind Harmer
0.109
247604X1-042
Adder
0.282
270491AE1-102 GEN2
Solar/Wind Harmer
0.868
24441205WTRV SLR C
Solar/Wind Harmer
0.089
270377AD1-106 GEN
Solar/Wind Harmer
3.918
270191TR4_S_V150
Solar/Wind Harmer
1.873
270247TR4_N_V136
Solar/Wind Harmer
0.531
945111AF1-176 GEN
Solar/Wind Harmer
3.515
270485AE1-090_GEN
Solar/Wind Harmer
0.369
24642205MAYFLWER
Adder
0.384
970031AG2-029 GEN
Solar/Wind Harmer
18.113
247643Z2-116 C
Solar/Wind Harmer
0.042
959331AF2-224 GEN
Solar/Wind Harmer
5.975
965021AG1-366 GEN
Solar/Wind Harmer
1.39
970065AG2-057 GEN
Solar/Wind Harmer
0.575
942871AE2-306 GEN
Solar/Wind Harmer
0.514
270391AF1-285 GEN3
Solar/Wind Harmer
0.264
270043AE2-236 GEN
Solar/Wind Harmer
3.089
970349AG2-230 GEN
Solar/Wind Harmer
8.3
270535AF1-215 GEN1
Solar/Wind Harmer
2.387
972231SS25-0005
Solar/Wind Harmer
4.917
972181SS23-001
Solar/Wind Harmer
3.073
274752CRETE EC ;2U
Adder
2.532
274753CRETE EC ;3U
Adder
2.532
964401AG1-302 GEN
Solar/Wind Harmer
4.687
274724RIVER EC ;11
Adder
9.105
959141AF2-205 GEN
Solar/Wind Harmer
3.076
274802UNIV PARK;5U
Adder
2.953
274826FISK ;BP
Adder
5.536
274800UNIV PARK;3U
Adder
2.944
972038AH1-567 GEN2
Adder
0.184
276772AC2-154 GEN
Solar/Wind Harmer
1.406
276806AD2-047 C O1
Solar/Wind Harmer
5.394
970941AG2-585 GEN
Solar/Wind Harmer
6.303
274772LINCOLN ;3U
Adder
3.125
971617AH1-308 GEN
Solar/Wind Harmer
2.93
972228AH1-698 GEN2
Adder
1.862
274676JOLIET 29;8U
Adder
14.797
23867002DVBSG1
50/50
13.011
972211AH1-690 GEN
50/50
297.552
241886AC2-103 GEN2
Solar/Wind Harmer
18.089
24191202EL_AA1-006
Adder
0.36
970817AG2-515 GEN
Solar/Wind Harmer
16.3
945411AF1-206 GEN
Solar/Wind Harmer
9.015
270499AE1-146 GEN
Solar/Wind Harmer
2.926
945641AF1-229 GEN
Solar/Wind Harmer
4.044
970159AG2-109 GEN
Solar/Wind Harmer
3.924
270297AD1-101 GEN
Solar/Wind Harmer
2.22
971549AH1-272 GEN
Solar/Wind Harmer
14.209
966831AG1-554 GEN
Solar/Wind Harmer
0.892
971989AH1-539 GEN
Solar/Wind Harmer
9.641
247607V1-011 GEN
Solar/Wind Harmer
2.681
971567AH1-282 GEN
Solar/Wind Harmer
10.136
957201AF2-014 GEN
Solar/Wind Harmer
3.029
270435AC2-044 GEN
Solar/Wind Harmer
1.336
944161AF1-084 GEN
Solar/Wind Harmer
1.419
965041AG1-368 GEN
Solar/Wind Harmer
6.263
965051AG1-369 GEN
Solar/Wind Harmer
3.117
270302AB2-170 GEN
Solar/Wind Harmer
5.097
270317AD1-130_GEN
Solar/Wind Harmer
1.954
971771AH1-392 GEN
Solar/Wind Harmer
5.317
971769AH1-391 GEN
Solar/Wind Harmer
5.763
270578AF1-285 GEN2
Solar/Wind Harmer
0.264
960681AF2-359 GEN
Solar/Wind Harmer
2.098
963791AG1-232 GEN
Solar/Wind Harmer
7.497
971347AH1-153 GEN
Solar/Wind Harmer
8.3
970179AG2-119 GEN
Solar/Wind Harmer
4.411
971219AH1-069 GEN
Solar/Wind Harmer
0.907
270536AF1-215 GEN2
Solar/Wind Harmer
2.387
270071AF1-092 GEN
Solar/Wind Harmer
7.858
958391AF2-133 GEN
Solar/Wind Harmer
4.646
274814UNIV PK N;0U
Adder
2.586
274807UNIV PK N;3U
Adder
2.581
274805UNIV PK N;1U
Adder
2.569
274811UNIV PK N;7U
Adder
2.564
972037AH1-567 GEN1
Adder
0.093
274827FISK ;RP
Adder
3.924
960591AF2-350 GEN
Solar/Wind Harmer
5.042
274775LINCOLN ;6U
Adder
3.125
274776LINCOLN ;7U
Adder
3.125
274777LINCOLN ;8U
Adder
3.125
270024AE2-089 GEN
Solar/Wind Harmer
2.366
972227AH1-698 GEN1
Adder
1.311
274687WILL CNTY;4U
Adder
14.004
274687WILL CNTY;4U
Adder
14.004
274675JOLIET 29;7U
Adder
15.345
274675JOLIET 29;7U
Adder
14.797
274731ELWOOD EC;2P
Adder
8.208
274733ELWOOD EC;3P
Adder
8.208
274735ELWOOD EC;4P
Adder
8.208
274728ELWOOD EC;5P
Adder
8.208
274746AC1-111 G10
Adder
2.761
274744AC1-111 GEN8
Adder
2.761
24729505KEY G4
Adder
3.179
274823ROCKFORD ;21
Adder
9.356
203846AF2-130 C
Solar/Wind Helper
0.325
241982AE2-343 S C
Solar/Wind Helper
0.145
254304AE2-114 C
Solar/Wind Helper
0.138
241997AF1-093 GEN
Solar/Wind Helper
0.16
203804AE2-113_GEN
Solar/Wind Helper
1.128
203855AF2-088 C
Solar/Wind Helper
0.087
20090526Q36
Solar/Wind Helper
0.548
203993AD2-133_GEN1
Solar/Wind Helper
0.548
20091526CHSTN_FL
Solar/Wind Helper
0.29
20092526R32
Solar/Wind Helper
0.563
203961AE2-224 GEN
Solar/Wind Helper
1.164
941231AE2-117 GEN
Solar/Wind Helper
0.227
970833AG2-524 GEN
Solar/Wind Harmer
1.943
970833AG2-524 GEN
Solar/Wind Harmer
0.904
24639705ELKHART HY
Adder
0.093
270063AE2-323 C
Solar/Wind Harmer
1.334
965011AG1-365 GEN
Solar/Wind Harmer
5.975
241813AF1-122_GEN
Solar/Wind Harmer
3.682
270223U2-072_GEN1
Solar/Wind Harmer
1.12
270578AF1-285 GEN2
Solar/Wind Harmer
0.685
270391AF1-285 GEN3
Solar/Wind Harmer
0.685
970373AG2-245 GEN
Solar/Wind Harmer
11.24
971221AH1-070 GEN
Solar/Wind Harmer
0.907
270055AF2-134 C O1
Solar/Wind Harmer
1.591
274751CRETE EC ;1U
Adder
2.532
274754CRETE EC ;4U
Adder
2.532
958381AF2-132 GEN
Solar/Wind Harmer
4.687
964861AG1-349 GEN
Solar/Wind Harmer
4.054
971917AH1-482 GEN
Solar/Wind Harmer
4.678
274723RIVER EC ;12
Adder
9.215
274812UNIV PK N;8U
Adder
2.564
276164X3-005 C
Solar/Wind Harmer
0.358
274801UNIV PARK;4U
Adder
2.944
940581AE2-045 GEN
Solar/Wind Harmer
5.147
971605AH1-302 GEN
Solar/Wind Harmer
4.401
276776AD2-060 GEN
Solar/Wind Harmer
0.213
972207SS24-0001
Solar/Wind Harmer
11.112
274773LINCOLN ;4U
Adder
3.125
274774LINCOLN ;5U
Adder
3.125
274676JOLIET 29;8U
Adder
15.345
941551AE2-152 GEN
Solar/Wind Harmer
2.266
274732ELWOOD EC;7P
Adder
8.208
274674JOLIET 9 ;6U
Adder
7.687
970245AG2-165 GEN
Solar/Wind Harmer
8.906
274745AC1-111 GEN9
Adder
2.761
274682WAUKEGAN ;7U
Adder
8.816
274828WAUKEGAN ;BP
Adder
5.414
274822ROCKFORD ;11
Adder
9.424
972235AH1-702 GEN1
Adder
1.208
274761LEE CO EC;2U
Adder
2.885
961971AG1-040 GEN
Solar/Wind Helper
0.451
203835AF1-098 GEN
Solar/Wind Helper
1.778
203860AG1-193 C
Solar/Wind Helper
0.199
241966AE1-183 GEN
Solar/Wind Helper
0.16
254303AC2-168 GEN
Solar/Wind Helper
0.093
203954AE2-126 C
Solar/Wind Helper
0.282
959471AF2-238 GEN
Solar/Wind Helper
0.26
238206AE2-263_GEN
Solar/Wind Helper
0.502
20094526CT_V3-030
Solar/Wind Helper
0.243
20088826HIGHLAND
Solar/Wind Helper
0.435
964201AG1-281 GEN
Solar/Wind Helper
0.234
964391AG1-301 GEN
Solar/Wind Helper
0.226
203979AG1-198 GEN
Solar/Wind Helper
0.261
241967AE2-285_GEN
Solar/Wind Helper
0.417
241801AE1-079 GEN
Solar/Wind Helper
0.162
241985AE1-237 GEN
Solar/Wind Helper
0.162
962101AG1-054 GEN
Solar/Wind Helper
0.402
946381AF1-302 GEN
Solar/Wind Helper
0.136
238217AF1-153 C O1
Solar/Wind Helper
0.144
20398826ARMNA MT
Solar/Wind Helper
0.849
203853AF1-134 C O1
Solar/Wind Helper
0.264
203952AE2-129 C
Solar/Wind Helper
0.257
203946AE2-131 C
Solar/Wind Helper
0.258
946071AF1-272 GEN
Solar/Wind Helper
1.356
203940AF1-140 C
Solar/Wind Helper
0.192
20084626FORWARD
Solar/Wind Helper
0.17
20088626ARWF_N39
Solar/Wind Helper
0.584
20303426NA_O38_P22
Solar/Wind Helper
0.479
20088926STNY CRK
Solar/Wind Helper
0.38
20083426SW_E13_K22
Solar/Wind Helper
0.025
276897AD1-100 C
Solar/Wind Harmer
14.503
939351AE1-166 GEN
Solar/Wind Harmer
2.963
276893AG1-478 C
Solar/Wind Harmer
0.209
970707AG2-453 GEN
Solar/Wind Harmer
13.981
274729ELWOOD EC;1P
Adder
8.208
274730ELWOOD EC;6P
Adder
8.208
274734ELWOOD EC;8P
Adder
8.208
274736ELWOOD EC;9P
Adder
8.208
970513AG2-328 GEN
Solar/Wind Harmer
8.906
970517AG2-330 GEN
Solar/Wind Harmer
8.078
274682WAUKEGAN ;7U
Adder
8.816
972236AH1-702 GEN2
Adder
1.051
274760LEE CO EC;1U
Adder
4.416
962511AG1-100 GEN
Solar/Wind Helper
0.462
203830AF1-094 GEN
Solar/Wind Helper
0.435
959441AF2-235 GEN
Solar/Wind Helper
0.196
254305AE2-115 C
Solar/Wind Helper
0.138
20334926Z1-069 C
Solar/Wind Helper
0.837
203854AF2-039 C
Solar/Wind Helper
0.18
203818AF1-086 GEN
Solar/Wind Helper
0.912
238202AE2-262_GEN
Solar/Wind Helper
0.528
941421AE2-139 GEN
Solar/Wind Helper
1.203
235058AG1-386 C
Solar/Wind Helper
0.205
200917MEHOOPANY_G
Solar/Wind Helper
1.091
991182J1586 G
External Queue
25.886547088623047
990527J1329
External Queue
1.891624927520752
990142J1224
External Queue
13.827776908874512
991177J1571 G
External Queue
16.072763442993164
LAGNLTFEXP_LAGN->PJM
CLTF
5.524
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.427
TVALTFEXP_TVA->PJM
CLTF
2.517
CPLELTFEXP_CPLE->PJM
CLTF
0.342
CBM West 2LTFEXP_CBM-W2->PJM
CBM
44.143
CBM West 1LTFEXP_CBM-W1->PJM
CBM
101.376
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.995
MECLTFEXP_MEC->PJM
CLTF
7.157
SIGELTFEXP_SIGE->PJM
CLTF
0.189
NYPJM->LTFIMP_NY
CLTF
2.552
LGEELTFEXP_LGEE->PJM
CLTF
2.281
WECLTFEXP_WEC->PJM
CLTF
1.831
AG2-052LTFEXP_AG2-052->PJM
LTF
0.118
AH1-155LTFEXP_AH1-155->PJM
LTF
0.177

Details for 02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line l/o ATSI_P2-3_OEC-345-003_SRT-SL


Base Case Flowgate

Area:ATSI
Facility Description:
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line
Contingency Name:
ATSI_P2-3_OEC-345-003_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.76 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:1967.48
MW Contribution:0.36
Bus #Bus NameTypeMW Contribution
23867002DVBSG1
50/50
9.2
972211AH1-690 GEN
50/50
210.311
241886AC2-103 GEN2
Solar/Wind Harmer
12.828
970817AG2-515 GEN
Solar/Wind Harmer
11.522
24191202EL_AA1-006
Adder
0.249
945411AF1-206 GEN
Solar/Wind Harmer
6.374
270499AE1-146 GEN
Solar/Wind Harmer
2.067
945641AF1-229 GEN
Solar/Wind Harmer
2.863
970159AG2-109 GEN
Solar/Wind Harmer
2.569
270297AD1-101 GEN
Solar/Wind Harmer
1.589
971549AH1-272 GEN
Solar/Wind Harmer
10.203
966831AG1-554 GEN
Solar/Wind Harmer
0.637
971989AH1-539 GEN
Solar/Wind Harmer
6.89
247607V1-011 GEN
Solar/Wind Harmer
1.93
971567AH1-282 GEN
Solar/Wind Harmer
7.229
957201AF2-014 GEN
Solar/Wind Harmer
2.183
270435AC2-044 GEN
Solar/Wind Harmer
0.963
944161AF1-084 GEN
Solar/Wind Harmer
1.025
965041AG1-368 GEN
Solar/Wind Harmer
4.523
965051AG1-369 GEN
Solar/Wind Harmer
2.252
270302AB2-170 GEN
Solar/Wind Harmer
3.686
270317AD1-130_GEN
Solar/Wind Harmer
1.413
203846AF2-130 C
Solar/Wind Helper
0.273
203804AE2-113_GEN
Solar/Wind Helper
0.939
241982AE2-343 S C
Solar/Wind Helper
0.108
957071AF2-004 GEN
50/50
10.802
23929302BS-PKR
50/50
1.846
241832AE2-181_GEN
Solar/Wind Harmer
1.547
958321AF2-126 GEN
Solar/Wind Harmer
1.207
23906502RICHG2&3
Adder
1.056
270575GUS2 35KV
Solar/Wind Harmer
8.83
23857102WLORG-A
Adder
4.322
270541AE2-072 C
Solar/Wind Harmer
3.557
970217AG2-149 GEN
Solar/Wind Harmer
20.039
270588AE1-091_GEN
Solar/Wind Harmer
5.974
270044AE2-322 C
Solar/Wind Harmer
0.703
270404AC1-167 GEN
Solar/Wind Harmer
0.585
270258AD1-119 GEN
Solar/Wind Harmer
1.434
958091AF2-103 GEN
Solar/Wind Harmer
0.079
247604X1-042
Adder
0.203
961961AG1-039 GEN
Solar/Wind Harmer
1.38
270491AE1-102 GEN2
Solar/Wind Harmer
0.626
24441205WTRV SLR C
Solar/Wind Harmer
0.064
270377AD1-106 GEN
Solar/Wind Harmer
2.809
270191TR4_S_V150
Solar/Wind Harmer
1.353
270247TR4_N_V136
Solar/Wind Harmer
0.384
945111AF1-176 GEN
Solar/Wind Harmer
2.541
270485AE1-090_GEN
Solar/Wind Harmer
0.267
24642205MAYFLWER
Adder
0.278
970031AG2-029 GEN
Solar/Wind Harmer
13.106
247643Z2-116 C
Solar/Wind Harmer
0.03
959331AF2-224 GEN
Solar/Wind Harmer
4.324
965021AG1-366 GEN
Solar/Wind Harmer
1.006
962511AG1-100 GEN
Solar/Wind Helper
0.411
203830AF1-094 GEN
Solar/Wind Helper
0.384
959441AF2-235 GEN
Solar/Wind Helper
0.169
20334926Z1-069 C
Solar/Wind Helper
0.692
254305AE2-115 C
Solar/Wind Helper
0.103
23917202WLORG-3
50/50
1.387
23917302WLORG-4
50/50
1.357
966311AG1-500 GEN
50/50
126.182
24190002OREGON_ST1
50/50
2.624
24189802OREGON_CT1
50/50
1.991
241996AE2-282_GEN
Solar/Wind Harmer
1.706
23857202WLORG-B
Adder
4.453
971677AH1-339 GEN
Solar/Wind Harmer
5.98
270007AE1-245 C
Solar/Wind Harmer
2.895
942801AE2-298 GEN
Solar/Wind Harmer
0.734
246938BC-WTG3
Solar/Wind Harmer
1.916
246937BC-WTG2
Solar/Wind Harmer
1.883
961051AF2-396 GEN
Solar/Wind Harmer
7.22
961051AF2-396 GEN
Solar/Wind Harmer
3.358
971231AH1-075 GEN
Solar/Wind Harmer
0.364
960981AF2-389 GEN
Solar/Wind Harmer
0.677
957891AF2-083 GEN
Solar/Wind Harmer
1.51
247620Y3-023
Adder
0.203
270216AD2-079_GEN
Solar/Wind Harmer
0.263
970611AG2-400 GEN
Solar/Wind Harmer
4.324
203947AF1-006 C
Solar/Wind Helper
0.461
203980AG1-197 GEN
Solar/Wind Helper
0.297
203979AG1-198 GEN
Solar/Wind Helper
0.23
241967AE2-285_GEN
Solar/Wind Helper
0.309
241801AE1-079 GEN
Solar/Wind Helper
0.12
241985AE1-237 GEN
Solar/Wind Helper
0.12
946381AF1-302 GEN
Solar/Wind Helper
0.111
238217AF1-153 C O1
Solar/Wind Helper
0.118
962101AG1-054 GEN
Solar/Wind Helper
0.297
23917402WLORG-5
50/50
1.364
23917102WLORG-2
50/50
1.344
24189902OREGON_CT2
50/50
1.95
23856402BAYSG1
50/50
1.049
241885AC2-103 GEN1
Solar/Wind Harmer
12.828
241807AE2-176_GEN
Solar/Wind Harmer
5.09
972253AH1-711 GEN
Adder
38.596
241858AF1-205_GEN
Solar/Wind Harmer
4.35
241808AF1-120 C
Solar/Wind Harmer
0.951
23920202STRYCT
Adder
1.423
241840AF1-064_GEN
Solar/Wind Harmer
1.126
972301AH1-735 GEN
Adder
5.287
23906402RICHG1
Adder
1.057
23906502RICHG2&3
Adder
1.056
270361_3
Solar/Wind Harmer
7.495
960841AF2-375 GEN
Solar/Wind Harmer
3.301
966321AG1-501 GEN
Adder
0.871
957111AF2-005 GEN
Adder
0.697
270428AC2-015 C
Solar/Wind Harmer
3.771
247522W1-056 GEN
Solar/Wind Harmer
1.418
970515AG2-329 GEN
Solar/Wind Harmer
9.087
970905AG2-564 GEN
Solar/Wind Harmer
2.97
944231AF1-091 GEN
Solar/Wind Harmer
2.004
241847AF2-150_GEN
Solar/Wind Harmer
2
246936BC-WTG1
Solar/Wind Harmer
1.883
270489AE1-102 GEN1
Solar/Wind Harmer
0.626
965421AG1-410 GEN
Solar/Wind Harmer
14.298
24695305TIMB G C
Solar/Wind Harmer
2.569
270449AD2-020 GEN
Solar/Wind Harmer
1.284
943021AE2-325 GEN
Solar/Wind Harmer
1.668
247521TR3_G114
Solar/Wind Harmer
1.516
270246TR4_N_V150
Solar/Wind Harmer
0.384
945111AF1-176 GEN
Solar/Wind Harmer
8.018
270505AE1-170 C O1
Solar/Wind Harmer
6.733
270462AD2-086
Solar/Wind Harmer
3.066
24639705ELKHART HY
Adder
0.067
270063AE2-323 C
Solar/Wind Harmer
0.965
965011AG1-365 GEN
Solar/Wind Harmer
4.324
961971AG1-040 GEN
Solar/Wind Helper
0.4
203835AF1-098 GEN
Solar/Wind Helper
1.575
203860AG1-193 C
Solar/Wind Helper
0.173
241966AE1-183 GEN
Solar/Wind Helper
0.119
203954AE2-126 C
Solar/Wind Helper
0.231
254303AC2-168 GEN
Solar/Wind Helper
0.068
254304AE2-114 C
Solar/Wind Helper
0.103
241997AF1-093 GEN
Solar/Wind Helper
0.119
990527J1329
External Queue
1.3199658393859863
990142J1224
External Queue
9.648950576782227
991177J1571 G
External Queue
11.211230278015137
LAGNLTFEXP_LAGN->PJM
CLTF
4.134
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.016
TVALTFEXP_TVA->PJM
CLTF
1.895
CPLELTFEXP_CPLE->PJM
CLTF
0.34
CBM West 2LTFEXP_CBM-W2->PJM
CBM
32.744
CBM West 1LTFEXP_CBM-W1->PJM
CBM
72.978
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.506
MECLTFEXP_MEC->PJM
CLTF
5.248
SIGELTFEXP_SIGE->PJM
CLTF
0.14
NYPJM->LTFIMP_NY
CLTF
1.985
LGEELTFEXP_LGEE->PJM
CLTF
1.697
WECLTFEXP_WEC->PJM
CLTF
1.336
AG2-052LTFEXP_AG2-052->PJM
LTF
0.086
AH1-155LTFEXP_AH1-155->PJM
LTF
0.129

Details for 02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line l/o ATSI_P2-3_OEC-345-028_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line
Contingency Name:
ATSI_P2-3_OEC-345-028_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.37 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:1903.65
MW Contribution:0.37
Bus #Bus NameTypeMW Contribution
23917402WLORG-5
50/50
1.325
23917102WLORG-2
50/50
1.305
24189902OREGON_CT2
50/50
1.926
23856402BAYSG1
50/50
1.04
241885AC2-103 GEN1
Solar/Wind Harmer
12.516
241807AE2-176_GEN
Solar/Wind Harmer
5.17
972253AH1-711 GEN
Adder
38.133
241858AF1-205_GEN
Solar/Wind Harmer
4.307
241808AF1-120 C
Solar/Wind Harmer
0.942
23920202STRYCT
Adder
1.409
241840AF1-064_GEN
Solar/Wind Harmer
1.116
966321AG1-501 GEN
Adder
1.042
957111AF2-005 GEN
Adder
0.833
972301AH1-735 GEN
Adder
5.24
23906402RICHG1
Adder
1.048
23906502RICHG2&3
Adder
1.047
270361_3
Solar/Wind Harmer
7.48
960841AF2-375 GEN
Solar/Wind Harmer
3.294
270428AC2-015 C
Solar/Wind Harmer
3.85
247522W1-056 GEN
Solar/Wind Harmer
1.419
970515AG2-329 GEN
Solar/Wind Harmer
9.111
970905AG2-564 GEN
Solar/Wind Harmer
3.056
944231AF1-091 GEN
Solar/Wind Harmer
1.99
241847AF2-150_GEN
Solar/Wind Harmer
2.044
246936BC-WTG1
Solar/Wind Harmer
1.872
270489AE1-102 GEN1
Solar/Wind Harmer
0.622
965421AG1-410 GEN
Solar/Wind Harmer
14.212
24695305TIMB G C
Solar/Wind Harmer
2.554
270449AD2-020 GEN
Solar/Wind Harmer
1.274
943021AE2-325 GEN
Solar/Wind Harmer
1.655
247521TR3_G114
Solar/Wind Harmer
1.507
270246TR4_N_V150
Solar/Wind Harmer
0.381
945111AF1-176 GEN
Solar/Wind Harmer
7.958
270505AE1-170 C O1
Solar/Wind Harmer
6.681
270462AD2-086
Solar/Wind Harmer
3.053
24639705ELKHART HY
Adder
0.067
270063AE2-323 C
Solar/Wind Harmer
0.958
961971AG1-040 GEN
Solar/Wind Helper
0.399
203835AF1-098 GEN
Solar/Wind Helper
1.572
203860AG1-193 C
Solar/Wind Helper
0.172
241966AE1-183 GEN
Solar/Wind Helper
0.118
203954AE2-126 C
Solar/Wind Helper
0.231
254303AC2-168 GEN
Solar/Wind Helper
0.068
957071AF2-004 GEN
50/50
10.49
23929302BS-PKR
50/50
1.83
241832AE2-181_GEN
Solar/Wind Harmer
1.532
958321AF2-126 GEN
Solar/Wind Harmer
1.196
23857102WLORG-A
Adder
5.166
23906502RICHG2&3
Adder
1.047
270575GUS2 35KV
Solar/Wind Harmer
8.812
270541AE2-072 C
Solar/Wind Harmer
3.533
970217AG2-149 GEN
Solar/Wind Harmer
20.092
270588AE1-091_GEN
Solar/Wind Harmer
5.966
270044AE2-322 C
Solar/Wind Harmer
0.698
270404AC1-167 GEN
Solar/Wind Harmer
0.582
270258AD1-119 GEN
Solar/Wind Harmer
1.425
961961AG1-039 GEN
Solar/Wind Harmer
1.41
958091AF2-103 GEN
Solar/Wind Harmer
0.078
247604X1-042
Adder
0.201
270491AE1-102 GEN2
Solar/Wind Harmer
0.622
24441205WTRV SLR C
Solar/Wind Harmer
0.064
270377AD1-106 GEN
Solar/Wind Harmer
2.828
270191TR4_S_V150
Solar/Wind Harmer
1.345
270247TR4_N_V136
Solar/Wind Harmer
0.381
945111AF1-176 GEN
Solar/Wind Harmer
2.522
270485AE1-090_GEN
Solar/Wind Harmer
0.265
24642205MAYFLWER
Adder
0.276
970031AG2-029 GEN
Solar/Wind Harmer
13.014
247643Z2-116 C
Solar/Wind Harmer
0.03
962511AG1-100 GEN
Solar/Wind Helper
0.41
203830AF1-094 GEN
Solar/Wind Helper
0.383
959441AF2-235 GEN
Solar/Wind Helper
0.169
20334926Z1-069 C
Solar/Wind Helper
0.69
254305AE2-115 C
Solar/Wind Helper
0.102
23867002DVBSG1
50/50
9.044
972211AH1-690 GEN
50/50
207.621
24191202EL_AA1-006
50/50
0.277
241886AC2-103 GEN2
Solar/Wind Harmer
12.516
970817AG2-515 GEN
Solar/Wind Harmer
11.392
945411AF1-206 GEN
Solar/Wind Harmer
6.311
270499AE1-146 GEN
Solar/Wind Harmer
2.062
945641AF1-229 GEN
Solar/Wind Harmer
2.852
970159AG2-109 GEN
Solar/Wind Harmer
2.883
270297AD1-101 GEN
Solar/Wind Harmer
1.58
971549AH1-272 GEN
Solar/Wind Harmer
10.113
966831AG1-554 GEN
Solar/Wind Harmer
0.638
971989AH1-539 GEN
Solar/Wind Harmer
6.896
971567AH1-282 GEN
Solar/Wind Harmer
7.283
247607V1-011 GEN
Solar/Wind Harmer
1.919
957201AF2-014 GEN
Solar/Wind Harmer
2.17
270435AC2-044 GEN
Solar/Wind Harmer
0.957
944161AF1-084 GEN
Solar/Wind Harmer
1.017
965041AG1-368 GEN
Solar/Wind Harmer
4.496
965051AG1-369 GEN
Solar/Wind Harmer
2.238
270302AB2-170 GEN
Solar/Wind Harmer
3.67
270317AD1-130_GEN
Solar/Wind Harmer
1.407
203846AF2-130 C
Solar/Wind Helper
0.273
203804AE2-113_GEN
Solar/Wind Helper
0.936
241982AE2-343 S C
Solar/Wind Helper
0.107
254304AE2-114 C
Solar/Wind Helper
0.102
241997AF1-093 GEN
Solar/Wind Helper
0.118
23917202WLORG-3
50/50
1.347
23917302WLORG-4
50/50
1.318
966311AG1-500 GEN
50/50
122.544
24190002OREGON_ST1
50/50
2.591
24189802OREGON_CT1
50/50
1.965
241996AE2-282_GEN
Solar/Wind Harmer
1.69
23857202WLORG-B
Adder
5.323
971677AH1-339 GEN
Solar/Wind Harmer
5.982
270007AE1-245 C
Solar/Wind Harmer
2.879
942801AE2-298 GEN
Solar/Wind Harmer
0.729
246938BC-WTG3
Solar/Wind Harmer
1.904
246937BC-WTG2
Solar/Wind Harmer
1.872
971231AH1-075 GEN
Solar/Wind Harmer
0.366
961051AF2-396 GEN
Solar/Wind Harmer
7.165
961051AF2-396 GEN
Solar/Wind Harmer
3.333
960981AF2-389 GEN
Solar/Wind Harmer
0.672
957891AF2-083 GEN
Solar/Wind Harmer
1.498
247620Y3-023
Adder
0.202
270216AD2-079_GEN
Solar/Wind Harmer
0.261
203947AF1-006 C
Solar/Wind Helper
0.46
203980AG1-197 GEN
Solar/Wind Helper
0.297
203979AG1-198 GEN
Solar/Wind Helper
0.23
241967AE2-285_GEN
Solar/Wind Helper
0.308
241801AE1-079 GEN
Solar/Wind Helper
0.12
241985AE1-237 GEN
Solar/Wind Helper
0.12
946381AF1-302 GEN
Solar/Wind Helper
0.11
238217AF1-153 C O1
Solar/Wind Helper
0.118
962101AG1-054 GEN
Solar/Wind Helper
0.296
990527J1329
External Queue
1.3018794059753418
990142J1224
External Queue
9.516737937927246
991177J1571 G
External Queue
11.062751770019531
LAGNLTFEXP_LAGN->PJM
CLTF
4.117
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.021
TVALTFEXP_TVA->PJM
CLTF
1.889
CPLELTFEXP_CPLE->PJM
CLTF
0.344
CBM West 2LTFEXP_CBM-W2->PJM
CBM
32.594
CBM West 1LTFEXP_CBM-W1->PJM
CBM
72.342
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.481
MECLTFEXP_MEC->PJM
CLTF
5.217
SIGELTFEXP_SIGE->PJM
CLTF
0.139
NYPJM->LTFIMP_NY
CLTF
1.977
LGEELTFEXP_LGEE->PJM
CLTF
1.691
WECLTFEXP_WEC->PJM
CLTF
1.328
AG2-052LTFEXP_AG2-052->PJM
LTF
0.085
AH1-155LTFEXP_AH1-155->PJM
LTF
0.128

Details for 02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line l/o ATSI_P2-3_OEC-345-1152-3_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_OEC-345-1152-3_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:151.55 %
Rating:1646.0 MVA
Rating Type:B
MVA to Mitigate:2494.57
MW Contribution:0.37
Bus #Bus NameTypeMW Contribution
24190002OREGON_ST1
50/50
3.497
24189802OREGON_CT1
50/50
2.653
23888802TROY G4
50/50
1.766
241996AE2-282_GEN
Solar/Wind Harmer
2.162
971677AH1-339 GEN
Solar/Wind Harmer
6.682
270007AE1-245 C
Solar/Wind Harmer
3.485
942801AE2-298 GEN
Solar/Wind Harmer
0.882
246938BC-WTG3
Solar/Wind Harmer
2.318
246937BC-WTG2
Solar/Wind Harmer
2.279
961051AF2-396 GEN
Solar/Wind Harmer
8.926
961051AF2-396 GEN
Solar/Wind Harmer
4.152
960981AF2-389 GEN
Solar/Wind Harmer
0.835
957891AF2-083 GEN
Solar/Wind Harmer
1.863
247620Y3-023
Adder
0.25
270216AD2-079_GEN
Solar/Wind Harmer
0.324
970611AG2-400 GEN
Solar/Wind Harmer
5.243
270526AF1-158 GEN
Solar/Wind Harmer
2.341
24441505OLIV SLR
Solar/Wind Harmer
0.069
965681AG1-436 GEN
Solar/Wind Harmer
6.166
965791AG1-447 GEN
Solar/Wind Harmer
3.155
270224U2-072_GEN2
Solar/Wind Harmer
0.958
270227U2-072_GEN3
Solar/Wind Harmer
0.958
270228U2-072_GEN4
Solar/Wind Harmer
0.958
270231U2-072_GEN5
Solar/Wind Harmer
0.958
971231AH1-075 GEN
Solar/Wind Harmer
0.374
274808UNIV PK N;4U
Adder
2.26
274803UNIV PARK;6U
Adder
2.613
274888KELLY CRK;1U
Solar/Wind Harmer
2.634
274887GEN-1.85
Solar/Wind Harmer
2.378
276843GEN-1.7
Solar/Wind Harmer
0.256
958011AF2-095 GEN
Solar/Wind Harmer
6.424
274770LINCOLN ;1U
Adder
2.764
274771LINCOLN ;2U
Adder
2.764
942221AE2-234 GEN
Solar/Wind Harmer
0.326
972259AH1-714 GEN
Adder
8.447
274674JOLIET 9 ;6U
Adder
6.799
970321AG2-212 GEN
Solar/Wind Harmer
7.863
274847GR RIDGE ;BU
Solar/Wind Harmer
2.221
274696ROCKY RD ;4P
Adder
4.941
274695ROCKY RD ;2P
Adder
4.827
274693ROCKY RD ;1P
Adder
4.78
274697ROCKY RD ;3P
Adder
1.311
274683WAUKEGAN ;8U
Adder
9.13
274683WAUKEGAN ;8U
Adder
7.697
203947AF1-006 C
Solar/Wind Helper
0.378
203980AG1-197 GEN
Solar/Wind Helper
0.247
203979AG1-198 GEN
Solar/Wind Helper
0.193
241967AE2-285_GEN
Solar/Wind Helper
0.336
241801AE1-079 GEN
Solar/Wind Helper
0.131
241985AE1-237 GEN
Solar/Wind Helper
0.13
962101AG1-054 GEN
Solar/Wind Helper
0.324
946381AF1-302 GEN
Solar/Wind Helper
0.104
238217AF1-153 C O1
Solar/Wind Helper
0.11
23929302BS-PKR
50/50
2.267
241832AE2-181_GEN
Solar/Wind Harmer
1.96
958321AF2-126 GEN
Solar/Wind Harmer
1.494
23906502RICHG2&3
Adder
1.32
270575GUS2 35KV
Solar/Wind Harmer
10.036
270541AE2-072 C
Solar/Wind Harmer
4.33
970217AG2-149 GEN
Solar/Wind Harmer
22.419
270044AE2-322 C
Solar/Wind Harmer
0.854
270404AC1-167 GEN
Solar/Wind Harmer
0.711
270258AD1-119 GEN
Solar/Wind Harmer
1.74
270588AE1-091_GEN
Solar/Wind Harmer
6.813
247604X1-042
Adder
0.253
24441205WTRV SLR C
Solar/Wind Harmer
0.08
958091AF2-103 GEN
Solar/Wind Harmer
0.095
270491AE1-102 GEN2
Solar/Wind Harmer
0.757
945111AF1-176 GEN
Solar/Wind Harmer
3.137
270191TR4_S_V150
Solar/Wind Harmer
1.632
270247TR4_N_V136
Solar/Wind Harmer
0.463
24642205MAYFLWER
Adder
0.343
970031AG2-029 GEN
Solar/Wind Harmer
16.05
247643Z2-116 C
Solar/Wind Harmer
0.037
959331AF2-224 GEN
Solar/Wind Harmer
5.243
965021AG1-366 GEN
Solar/Wind Harmer
1.219
270485AE1-090_GEN
Solar/Wind Harmer
0.316
270043AE2-236 GEN
Solar/Wind Harmer
2.723
970349AG2-230 GEN
Solar/Wind Harmer
7.365
942871AE2-306 GEN
Solar/Wind Harmer
0.439
270391AF1-285 GEN3
Solar/Wind Harmer
0.225
270377AD1-106 GEN
Solar/Wind Harmer
2.883
270535AF1-215 GEN1
Solar/Wind Harmer
2.114
972231SS25-0005
Solar/Wind Harmer
4.354
972181SS23-001
Solar/Wind Harmer
2.721
274752CRETE EC ;2U
Adder
2.243
274753CRETE EC ;3U
Adder
2.243
964401AG1-302 GEN
Solar/Wind Harmer
4.148
274724RIVER EC ;11
Adder
8.061
959141AF2-205 GEN
Solar/Wind Harmer
2.72
274802UNIV PARK;5U
Adder
2.613
274826FISK ;BP
Adder
4.899
274800UNIV PARK;3U
Adder
2.605
972038AH1-567 GEN2
Adder
0.163
276772AC2-154 GEN
Solar/Wind Harmer
1.244
276806AD2-047 C O1
Solar/Wind Harmer
4.772
970941AG2-585 GEN
Solar/Wind Harmer
5.576
274772LINCOLN ;3U
Adder
2.764
972228AH1-698 GEN2
Adder
1.647
274676JOLIET 29;8U
Adder
13.089
276897AD1-100 C
Solar/Wind Harmer
12.825
939351AE1-166 GEN
Solar/Wind Harmer
2.621
276893AG1-478 C
Solar/Wind Harmer
0.185
274729ELWOOD EC;1P
Adder
7.259
274730ELWOOD EC;6P
Adder
7.259
274734ELWOOD EC;8P
Adder
7.259
274736ELWOOD EC;9P
Adder
7.259
970707AG2-453 GEN
Solar/Wind Harmer
12.364
970513AG2-328 GEN
Solar/Wind Harmer
7.863
970517AG2-330 GEN
Solar/Wind Harmer
7.132
971617AH1-308 GEN
Solar/Wind Harmer
2.555
943121AE2-341 GEN
Solar/Wind Harmer
6.548
943591AF1-030 GEN
Solar/Wind Harmer
4.365
274682WAUKEGAN ;7U
Adder
7.794
962511AG1-100 GEN
Solar/Wind Helper
0.339
203830AF1-094 GEN
Solar/Wind Helper
0.321
959441AF2-235 GEN
Solar/Wind Helper
0.146
254305AE2-115 C
Solar/Wind Helper
0.111
20334926Z1-069 C
Solar/Wind Helper
0.639
276694AA1-018 GEN2
Solar/Wind Harmer
0.632
24189902OREGON_CT2
50/50
2.599
23888702TROY G3
50/50
1.766
972253AH1-711 GEN
50/50
53.942
23856402BAYSG1
50/50
1.288
23920202STRYCT
50/50
1.908
241858AF1-205_GEN
Solar/Wind Harmer
5.509
241808AF1-120 C
Solar/Wind Harmer
1.205
241840AF1-064_GEN
Solar/Wind Harmer
1.394
972301AH1-735 GEN
Adder
6.613
23906402RICHG1
Adder
1.323
23906502RICHG2&3
Adder
1.32
270361_3
Solar/Wind Harmer
8.519
960841AF2-375 GEN
Solar/Wind Harmer
3.762
241807AE2-176_GEN
Solar/Wind Harmer
2.793
247522W1-056 GEN
Solar/Wind Harmer
1.578
970515AG2-329 GEN
Solar/Wind Harmer
10.167
944231AF1-091 GEN
Solar/Wind Harmer
2.462
246936BC-WTG1
Solar/Wind Harmer
2.279
270489AE1-102 GEN1
Solar/Wind Harmer
0.757
965421AG1-410 GEN
Solar/Wind Harmer
17.306
270449AD2-020 GEN
Solar/Wind Harmer
1.589
943021AE2-325 GEN
Solar/Wind Harmer
2.064
270428AC2-015 C
Solar/Wind Harmer
3.1
24695305TIMB G C
Solar/Wind Harmer
3.1
945111AF1-176 GEN
Solar/Wind Harmer
9.898
270505AE1-170 C O1
Solar/Wind Harmer
8.313
247521TR3_G114
Solar/Wind Harmer
1.829
270246TR4_N_V150
Solar/Wind Harmer
0.463
24639705ELKHART HY
Adder
0.083
270063AE2-323 C
Solar/Wind Harmer
1.182
965011AG1-365 GEN
Solar/Wind Harmer
5.243
270462AD2-086
Solar/Wind Harmer
3.638
270223U2-072_GEN1
Solar/Wind Harmer
0.958
270578AF1-285 GEN2
Solar/Wind Harmer
0.586
270391AF1-285 GEN3
Solar/Wind Harmer
0.586
970373AG2-245 GEN
Solar/Wind Harmer
9.966
270055AF2-134 C O1
Solar/Wind Harmer
1.409
274751CRETE EC ;1U
Adder
2.243
274754CRETE EC ;4U
Adder
2.243
958381AF2-132 GEN
Solar/Wind Harmer
4.148
964861AG1-349 GEN
Solar/Wind Harmer
3.588
971917AH1-482 GEN
Solar/Wind Harmer
4.14
274723RIVER EC ;12
Adder
8.158
274812UNIV PK N;8U
Adder
2.27
276164X3-005 C
Solar/Wind Harmer
0.317
274801UNIV PARK;4U
Adder
2.605
940581AE2-045 GEN
Solar/Wind Harmer
4.55
276776AD2-060 GEN
Solar/Wind Harmer
0.189
971605AH1-302 GEN
Solar/Wind Harmer
3.891
972207SS24-0001
Solar/Wind Harmer
9.829
274773LINCOLN ;4U
Adder
2.764
274774LINCOLN ;5U
Adder
2.764
274676JOLIET 29;8U
Adder
13.573
941551AE2-152 GEN
Solar/Wind Harmer
2.004
274732ELWOOD EC;7P
Adder
7.259
274674JOLIET 9 ;6U
Adder
6.799
970245AG2-165 GEN
Solar/Wind Harmer
7.863
274871GR RIDGE ;2U
Solar/Wind Harmer
3.377
970905AG2-564 GEN
Solar/Wind Harmer
2.194
274745AC1-111 GEN9
Adder
2.441
274682WAUKEGAN ;7U
Adder
7.794
274828WAUKEGAN ;BP
Adder
4.786
241885AC2-103 GEN1
Solar/Wind Helper
9.447
961971AG1-040 GEN
Solar/Wind Helper
0.332
203835AF1-098 GEN
Solar/Wind Helper
1.307
203860AG1-193 C
Solar/Wind Helper
0.148
241966AE1-183 GEN
Solar/Wind Helper
0.129
254303AC2-168 GEN
Solar/Wind Helper
0.075
276691AA1-018 GEN1
Solar/Wind Harmer
0.047
23867002DVBSG1
50/50
13.074
972211AH1-690 GEN
50/50
280.319
23888502TROY G1
50/50
1.766
23888602TROY G2
50/50
1.766
970817AG2-515 GEN
Solar/Wind Harmer
14.976
945411AF1-206 GEN
Solar/Wind Harmer
8.075
945641AF1-229 GEN
Solar/Wind Harmer
3.442
270499AE1-146 GEN
Solar/Wind Harmer
2.365
971549AH1-272 GEN
Solar/Wind Harmer
12.831
270297AD1-101 GEN
Solar/Wind Harmer
1.906
966831AG1-554 GEN
Solar/Wind Harmer
0.708
971989AH1-539 GEN
Solar/Wind Harmer
7.656
247607V1-011 GEN
Solar/Wind Harmer
2.323
957201AF2-014 GEN
Solar/Wind Harmer
2.642
270435AC2-044 GEN
Solar/Wind Harmer
1.165
944161AF1-084 GEN
Solar/Wind Harmer
1.269
965041AG1-368 GEN
Solar/Wind Harmer
5.468
965051AG1-369 GEN
Solar/Wind Harmer
2.716
971771AH1-392 GEN
Solar/Wind Harmer
4.733
270302AB2-170 GEN
Solar/Wind Harmer
4.373
270317AD1-130_GEN
Solar/Wind Harmer
1.676
971769AH1-391 GEN
Solar/Wind Harmer
5.127
971567AH1-282 GEN
Solar/Wind Harmer
7.606
960681AF2-359 GEN
Solar/Wind Harmer
1.863
971347AH1-153 GEN
Solar/Wind Harmer
7.365
963791AG1-232 GEN
Solar/Wind Harmer
6.558
270578AF1-285 GEN2
Solar/Wind Harmer
0.225
270536AF1-215 GEN2
Solar/Wind Harmer
2.114
270071AF1-092 GEN
Solar/Wind Harmer
6.904
958391AF2-133 GEN
Solar/Wind Harmer
4.11
274814UNIV PK N;0U
Adder
2.289
274807UNIV PK N;3U
Adder
2.285
274805UNIV PK N;1U
Adder
2.275
274811UNIV PK N;7U
Adder
2.27
972037AH1-567 GEN1
Adder
0.082
274827FISK ;RP
Adder
3.472
960591AF2-350 GEN
Solar/Wind Harmer
4.461
274775LINCOLN ;6U
Adder
2.764
274776LINCOLN ;7U
Adder
2.764
274777LINCOLN ;8U
Adder
2.764
972227AH1-698 GEN1
Adder
1.16
274687WILL CNTY;4U
Adder
12.387
274687WILL CNTY;4U
Adder
12.387
274675JOLIET 29;7U
Adder
13.573
274675JOLIET 29;7U
Adder
13.089
274731ELWOOD EC;2P
Adder
7.259
274733ELWOOD EC;3P
Adder
7.259
274735ELWOOD EC;4P
Adder
7.259
274728ELWOOD EC;5P
Adder
7.259
270024AE2-089 GEN
Solar/Wind Harmer
2.063
970833AG2-524 GEN
Solar/Wind Harmer
3.836
970833AG2-524 GEN
Solar/Wind Harmer
1.784
274746AC1-111 G10
Adder
2.441
274744AC1-111 GEN8
Adder
2.441
241886AC2-103 GEN2
Solar/Wind Helper
9.447
241982AE2-343 S C
Solar/Wind Helper
0.117
254304AE2-114 C
Solar/Wind Helper
0.111
203846AF2-130 C
Solar/Wind Helper
0.246
241997AF1-093 GEN
Solar/Wind Helper
0.129
203804AE2-113_GEN
Solar/Wind Helper
0.858
991182J1586 G
External Queue
24.279396057128906
990527J1329
External Queue
1.7751743793487549
990142J1224
External Queue
12.976524353027344
991177J1571 G
External Queue
14.956707954406738
LAGNLTFEXP_LAGN->PJM
CLTF
4.838
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.167
TVALTFEXP_TVA->PJM
CLTF
2.196
CPLELTFEXP_CPLE->PJM
CLTF
0.331
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.653
CBM West 1LTFEXP_CBM-W1->PJM
CBM
91.607
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.701
MECLTFEXP_MEC->PJM
CLTF
6.308
SIGELTFEXP_SIGE->PJM
CLTF
0.164
NYPJM->LTFIMP_NY
CLTF
2
LGEELTFEXP_LGEE->PJM
CLTF
1.969
WECLTFEXP_WEC->PJM
CLTF
1.618
AG2-052LTFEXP_AG2-052->PJM
LTF
0.104
AH1-155LTFEXP_AH1-155->PJM
LTF
0.156

Details for 02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line l/o ATSI_P1-2_OEC-345-809_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_OEC-345-809_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:128.94 %
Rating:1646.0 MVA
Rating Type:B
MVA to Mitigate:2122.34
MW Contribution:0.37
Bus #Bus NameTypeMW Contribution
24190002OREGON_ST1
50/50
3.432
24189802OREGON_CT1
50/50
2.603
23888802TROY G4
50/50
1.736
241996AE2-282_GEN
Solar/Wind Harmer
0.005
971677AH1-339 GEN
Solar/Wind Harmer
0.655
970621AG2-405 GEN
Solar/Wind Harmer
0.866
970623AG2-406 GEN
Solar/Wind Harmer
0.788
270007AE1-245 C
Solar/Wind Harmer
0.001
24189902OREGON_CT2
50/50
2.551
23888702TROY G3
50/50
1.736
972253AH1-711 GEN
50/50
53.019
23856402BAYSG1
50/50
1.281
23920202STRYCT
50/50
1.886
241858AF1-205_GEN
Solar/Wind Harmer
3.799
241808AF1-120 C
Solar/Wind Harmer
0.003
241840AF1-064_GEN
Solar/Wind Harmer
0.004
972301AH1-735 GEN
Adder
6.539
23906402RICHG1
Adder
1.308
23906502RICHG2&3
Adder
1.306
270361_3
Solar/Wind Harmer
4.656
960841AF2-375 GEN
Solar/Wind Harmer
-0.002
241807AE2-176_GEN
Solar/Wind Harmer
0.004
247522W1-056 GEN
Solar/Wind Harmer
0.001
970515AG2-329 GEN
Solar/Wind Harmer
12.569
944231AF1-091 GEN
Solar/Wind Harmer
1.201
270428AC2-015 C
Solar/Wind Harmer
0.002
246936BC-WTG1
Solar/Wind Harmer
0.163
270489AE1-102 GEN1
Solar/Wind Harmer
0.522
965421AG1-410 GEN
Solar/Wind Harmer
11.925
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.035
24695305TIMB G C
Solar/Wind Harmer
0.001
945111AF1-176 GEN
Solar/Wind Harmer
6.808
270505AE1-170 C O1
Solar/Wind Harmer
4.002
247521TR3_G114
Solar/Wind Harmer
0.137
270246TR4_N_V150
Solar/Wind Harmer
0.024
24639705ELKHART HY
Adder
0.082
270063AE2-323 C
Solar/Wind Harmer
0.003
965011AG1-365 GEN
Solar/Wind Harmer
3.611
270462AD2-086
Solar/Wind Harmer
0.008
270223U2-072_GEN1
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
6.857
270055AF2-134 C O1
Solar/Wind Harmer
0.002
970905AG2-564 GEN
Solar/Wind Harmer
1.733
274751CRETE EC ;1U
Adder
3.728
274754CRETE EC ;4U
Adder
3.728
958381AF2-132 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.083
274723RIVER EC ;12
Adder
8.046
274812UNIV PK N;8U
Adder
2.238
276164X3-005 C
Solar/Wind Harmer
0
274801UNIV PARK;4U
Adder
2.569
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
3.837
276776AD2-060 GEN
Solar/Wind Harmer
0.32
274773LINCOLN ;4U
Adder
3.711
274774LINCOLN ;5U
Adder
3.711
274676JOLIET 29;8U
Adder
13.387
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
7.16
274674JOLIET 9 ;6U
Adder
6.706
970245AG2-165 GEN
Solar/Wind Harmer
1.313
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
2.408
276691AA1-018 GEN1
Solar/Wind Harmer
0.364
241885AC2-103 GEN1
Solar/Wind Helper
9.503
961971AG1-040 GEN
Solar/Wind Helper
0.328
203835AF1-098 GEN
Solar/Wind Helper
1.293
203860AG1-193 C
Solar/Wind Helper
0.146
241966AE1-183 GEN
Solar/Wind Helper
0.128
254303AC2-168 GEN
Solar/Wind Helper
0.074
23867002DVBSG1
50/50
12.729
972211AH1-690 GEN
50/50
275.118
23888502TROY G1
50/50
1.736
23888602TROY G2
50/50
1.736
970817AG2-515 GEN
Solar/Wind Harmer
10.289
945411AF1-206 GEN
Solar/Wind Harmer
-0.001
270499AE1-146 GEN
Solar/Wind Harmer
0.029
945641AF1-229 GEN
Solar/Wind Harmer
0.001
971549AH1-272 GEN
Solar/Wind Harmer
9.844
270297AD1-101 GEN
Solar/Wind Harmer
0.001
971989AH1-539 GEN
Solar/Wind Harmer
1.772
247607V1-011 GEN
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.508
971619AH1-309 GEN
Solar/Wind Harmer
1.715
965041AG1-368 GEN
Solar/Wind Harmer
3.769
965051AG1-369 GEN
Solar/Wind Harmer
1.872
971771AH1-392 GEN
Solar/Wind Harmer
3.617
270302AB2-170 GEN
Solar/Wind Harmer
0.002
270317AD1-130_GEN
Solar/Wind Harmer
0.005
971653AH1-327 GEN
Solar/Wind Harmer
0.506
24191202EL_AA1-006
Adder
0.112
971769AH1-391 GEN
Solar/Wind Harmer
3.938
971567AH1-282 GEN
Solar/Wind Harmer
5.256
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971347AH1-153 GEN
Solar/Wind Harmer
5.067
963791AG1-232 GEN
Solar/Wind Harmer
4.517
270578AF1-285 GEN2
Solar/Wind Harmer
0.223
270536AF1-215 GEN2
Solar/Wind Harmer
0.004
270071AF1-092 GEN
Solar/Wind Harmer
6.074
274814UNIV PK N;0U
Adder
2.258
274807UNIV PK N;3U
Adder
2.253
274805UNIV PK N;1U
Adder
2.243
274811UNIV PK N;7U
Adder
2.238
958391AF2-133 GEN
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.081
274827FISK ;RP
Adder
3.424
971611AH1-305 GEN
Solar/Wind Harmer
1.828
960591AF2-350 GEN
Solar/Wind Harmer
3.069
274775LINCOLN ;6U
Adder
3.711
274776LINCOLN ;7U
Adder
3.711
274777LINCOLN ;8U
Adder
3.711
972227AH1-698 GEN1
Adder
1.144
274687WILL CNTY;4U
Adder
12.217
274687WILL CNTY;4U
Adder
12.217
274675JOLIET 29;7U
Adder
13.387
274675JOLIET 29;7U
Adder
12.909
274731ELWOOD EC;2P
Adder
7.16
274733ELWOOD EC;3P
Adder
7.16
274735ELWOOD EC;4P
Adder
7.16
274728ELWOOD EC;5P
Adder
7.16
270024AE2-089 GEN
Solar/Wind Harmer
0.003
970833AG2-524 GEN
Solar/Wind Harmer
3.326
970833AG2-524 GEN
Solar/Wind Harmer
2.217
274746AC1-111 G10
Adder
2.408
274744AC1-111 GEN8
Adder
2.408
241886AC2-103 GEN2
Solar/Wind Helper
9.503
241982AE2-343 S C
Solar/Wind Helper
0.116
254304AE2-114 C
Solar/Wind Helper
0.11
203846AF2-130 C
Solar/Wind Helper
0.243
241997AF1-093 GEN
Solar/Wind Helper
0.128
203804AE2-113_GEN
Solar/Wind Helper
0.848
246938BC-WTG3
Solar/Wind Harmer
0.145
246937BC-WTG2
Solar/Wind Harmer
0.163
961051AF2-396 GEN
Solar/Wind Harmer
7.735
961051AF2-396 GEN
Solar/Wind Harmer
5.157
957891AF2-083 GEN
Solar/Wind Harmer
0.001
247620Y3-023
Adder
0.246
270216AD2-079_GEN
Solar/Wind Harmer
0.001
970611AG2-400 GEN
Solar/Wind Harmer
3.611
970627AG2-408 GEN
Solar/Wind Harmer
1.083
270526AF1-158 GEN
Solar/Wind Harmer
0.004
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
4.242
965791AG1-447 GEN
Solar/Wind Harmer
3.111
270224U2-072_GEN2
Solar/Wind Harmer
0
270227U2-072_GEN3
Solar/Wind Harmer
0
270228U2-072_GEN4
Solar/Wind Harmer
0
270231U2-072_GEN5
Solar/Wind Harmer
0
971231AH1-075 GEN
Solar/Wind Harmer
0.374
274808UNIV PK N;4U
Adder
2.229
274803UNIV PARK;6U
Adder
2.577
274888KELLY CRK;1U
Solar/Wind Harmer
0.18
274887GEN-1.85
Solar/Wind Harmer
0.081
276843GEN-1.7
Solar/Wind Harmer
0.099
958011AF2-095 GEN
Solar/Wind Harmer
4.42
274770LINCOLN ;1U
Adder
3.711
274771LINCOLN ;2U
Adder
3.711
942221AE2-234 GEN
Solar/Wind Harmer
0.015
972259AH1-714 GEN
Adder
8.331
274674JOLIET 9 ;6U
Adder
6.706
970321AG2-212 GEN
Solar/Wind Harmer
1.313
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
958481AF2-142 GEN
Solar/Wind Harmer
4.505
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.406
203947AF1-006 C
Solar/Wind Helper
0.374
203980AG1-197 GEN
Solar/Wind Helper
0.244
203979AG1-198 GEN
Solar/Wind Helper
0.19
241967AE2-285_GEN
Solar/Wind Helper
0.332
241801AE1-079 GEN
Solar/Wind Helper
0.129
241985AE1-237 GEN
Solar/Wind Helper
0.129
962101AG1-054 GEN
Solar/Wind Helper
0.321
946381AF1-302 GEN
Solar/Wind Helper
0.103
23929302BS-PKR
50/50
2.254
241832AE2-181_GEN
Solar/Wind Harmer
0.003
958321AF2-126 GEN
Solar/Wind Harmer
1.148
23906502RICHG2&3
Adder
1.306
270575GUS2 35KV
Solar/Wind Harmer
4.656
270541AE2-072 C
Solar/Wind Harmer
0.008
970217AG2-149 GEN
Solar/Wind Harmer
4.19
270404AC1-167 GEN
Solar/Wind Harmer
0.002
270258AD1-119 GEN
Solar/Wind Harmer
0.001
270588AE1-091_GEN
Solar/Wind Harmer
3.358
247604X1-042
Adder
0.249
24441205WTRV SLR C
Solar/Wind Harmer
0
270491AE1-102 GEN2
Solar/Wind Harmer
0.522
945111AF1-176 GEN
Solar/Wind Harmer
3.093
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.024
24642205MAYFLWER
Adder
0.338
970031AG2-029 GEN
Solar/Wind Harmer
2.393
247643Z2-116 C
Solar/Wind Harmer
0
959331AF2-224 GEN
Solar/Wind Harmer
2.528
965021AG1-366 GEN
Solar/Wind Harmer
1.204
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270043AE2-236 GEN
Solar/Wind Harmer
2.187
970349AG2-230 GEN
Solar/Wind Harmer
5.067
270391AF1-285 GEN3
Solar/Wind Harmer
0.223
270377AD1-106 GEN
Solar/Wind Harmer
1.238
270535AF1-215 GEN1
Solar/Wind Harmer
0.004
274752CRETE EC ;2U
Adder
3.728
274753CRETE EC ;3U
Adder
3.728
964401AG1-302 GEN
Solar/Wind Harmer
0
274724RIVER EC ;11
Adder
7.95
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
274802UNIV PARK;5U
Adder
2.577
274826FISK ;BP
Adder
4.831
274800UNIV PARK;3U
Adder
2.569
972038AH1-567 GEN2
Adder
0.161
276806AD2-047 C O1
Solar/Wind Harmer
1.739
970941AG2-585 GEN
Solar/Wind Harmer
3.837
274772LINCOLN ;3U
Adder
3.711
972228AH1-698 GEN2
Adder
1.625
274676JOLIET 29;8U
Adder
12.909
276897AD1-100 C
Solar/Wind Harmer
0.004
939351AE1-166 GEN
Solar/Wind Harmer
0
276893AG1-478 C
Solar/Wind Harmer
0.12
970707AG2-453 GEN
Solar/Wind Harmer
9.926
274729ELWOOD EC;1P
Adder
7.16
274730ELWOOD EC;6P
Adder
7.16
274734ELWOOD EC;8P
Adder
7.16
274736ELWOOD EC;9P
Adder
7.16
970513AG2-328 GEN
Solar/Wind Harmer
1.313
970517AG2-330 GEN
Solar/Wind Harmer
7.878
971617AH1-308 GEN
Solar/Wind Harmer
2.523
943121AE2-341 GEN
Solar/Wind Harmer
5.036
943591AF1-030 GEN
Solar/Wind Harmer
3.349
276694AA1-018 GEN2
Solar/Wind Harmer
0
962511AG1-100 GEN
Solar/Wind Helper
0.335
203830AF1-094 GEN
Solar/Wind Helper
0.317
959441AF2-235 GEN
Solar/Wind Helper
0.144
254305AE2-115 C
Solar/Wind Helper
0.11
20334926Z1-069 C
Solar/Wind Helper
0.632
991182J1586 G
External Queue
23.868927001953125
990527J1329
External Queue
1.745489239692688
990142J1224
External Queue
12.759525299072266
991177J1571 G
External Queue
14.724894523620605
LAGNLTFEXP_LAGN->PJM
CLTF
4.775
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.139
TVALTFEXP_TVA->PJM
CLTF
2.168
CPLELTFEXP_CPLE->PJM
CLTF
0.326
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.144
CBM West 1LTFEXP_CBM-W1->PJM
CBM
90.231
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.589
MECLTFEXP_MEC->PJM
CLTF
6.223
SIGELTFEXP_SIGE->PJM
CLTF
0.162
NYPJM->LTFIMP_NY
CLTF
1.977
LGEELTFEXP_LGEE->PJM
CLTF
1.944
WECLTFEXP_WEC->PJM
CLTF
1.596
AG2-052LTFEXP_AG2-052->PJM
LTF
0.103
AH1-155LTFEXP_AH1-155->PJM
LTF
0.154

Details for 02HAYES-02BEAVER 345.0 kV Ckt 1 line l/o ATSI_P2-3_OEC-345-005_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02HAYES-02BEAVER 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_OEC-345-005_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:146.75 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:2755.89
MW Contribution:0.42
Bus #Bus NameTypeMW Contribution
24190002OREGON_ST1
50/50
3.596
24189802OREGON_CT1
50/50
2.727
23888802TROY G4
50/50
1.831
241996AE2-282_GEN
Solar/Wind Harmer
2.316
971677AH1-339 GEN
Solar/Wind Harmer
7.553
270007AE1-245 C
Solar/Wind Harmer
3.723
942801AE2-298 GEN
Solar/Wind Harmer
0.943
246938BC-WTG3
Solar/Wind Harmer
2.462
246937BC-WTG2
Solar/Wind Harmer
2.42
961051AF2-396 GEN
Solar/Wind Harmer
9.365
961051AF2-396 GEN
Solar/Wind Harmer
4.356
960981AF2-389 GEN
Solar/Wind Harmer
0.877
957891AF2-083 GEN
Solar/Wind Harmer
1.955
247620Y3-023
Adder
0.262
270216AD2-079_GEN
Solar/Wind Harmer
0.34
970611AG2-400 GEN
Solar/Wind Harmer
5.544
270526AF1-158 GEN
Solar/Wind Harmer
2.458
24441505OLIV SLR
Solar/Wind Harmer
0.072
971231AH1-075 GEN
Solar/Wind Harmer
0.425
965681AG1-436 GEN
Solar/Wind Harmer
6.472
965791AG1-447 GEN
Solar/Wind Harmer
3.311
270224U2-072_GEN2
Solar/Wind Harmer
1.021
270227U2-072_GEN3
Solar/Wind Harmer
1.021
270228U2-072_GEN4
Solar/Wind Harmer
1.021
270231U2-072_GEN5
Solar/Wind Harmer
1.021
274808UNIV PK N;4U
Adder
2.372
274803UNIV PARK;6U
Adder
2.744
942221AE2-234 GEN
Solar/Wind Harmer
0.344
274888KELLY CRK;1U
Solar/Wind Harmer
2.765
274887GEN-1.85
Solar/Wind Harmer
2.496
276843GEN-1.7
Solar/Wind Harmer
0.269
958011AF2-095 GEN
Solar/Wind Harmer
6.744
274770LINCOLN ;1U
Adder
2.903
274771LINCOLN ;2U
Adder
2.903
972259AH1-714 GEN
Adder
8.868
274674JOLIET 9 ;6U
Adder
7.138
970321AG2-212 GEN
Solar/Wind Harmer
8.259
274847GR RIDGE ;BU
Solar/Wind Harmer
2.332
274696ROCKY RD ;4P
Adder
5.187
274695ROCKY RD ;2P
Adder
5.068
274693ROCKY RD ;1P
Adder
5.018
274697ROCKY RD ;3P
Adder
1.377
274683WAUKEGAN ;8U
Adder
9.585
274683WAUKEGAN ;8U
Adder
8.08
274764LEE CO EC;5U
Adder
4.104
274765LEE CO EC;6U
Adder
4.104
274762LEE CO EC;3U
Adder
4.095
274763LEE CO EC;4U
Adder
4.056
972267AH1-718 GEN
Adder
1.82
25326509SID D
Adder
0.57
203947AF1-006 C
Solar/Wind Helper
0.411
203980AG1-197 GEN
Solar/Wind Helper
0.269
203979AG1-198 GEN
Solar/Wind Helper
0.209
241967AE2-285_GEN
Solar/Wind Helper
0.365
241801AE1-079 GEN
Solar/Wind Helper
0.142
241985AE1-237 GEN
Solar/Wind Helper
0.142
962101AG1-054 GEN
Solar/Wind Helper
0.353
946381AF1-302 GEN
Solar/Wind Helper
0.113
238217AF1-153 C O1
Solar/Wind Helper
0.12
20398826ARMNA MT
Solar/Wind Helper
0.712
203853AF1-134 C O1
Solar/Wind Helper
0.222
23929302BS-PKR
50/50
2.517
241832AE2-181_GEN
Solar/Wind Harmer
2.098
958321AF2-126 GEN
Solar/Wind Harmer
1.63
23906502RICHG2&3
Adder
1.417
270575GUS2 35KV
Solar/Wind Harmer
11.477
270541AE2-072 C
Solar/Wind Harmer
4.706
970217AG2-149 GEN
Solar/Wind Harmer
24.027
270044AE2-322 C
Solar/Wind Harmer
0.913
270404AC1-167 GEN
Solar/Wind Harmer
0.76
270588AE1-091_GEN
Solar/Wind Harmer
7.489
270258AD1-119 GEN
Solar/Wind Harmer
1.858
247604X1-042
Adder
0.265
958091AF2-103 GEN
Solar/Wind Harmer
0.101
24441205WTRV SLR C
Solar/Wind Harmer
0.084
270491AE1-102 GEN2
Solar/Wind Harmer
0.804
945111AF1-176 GEN
Solar/Wind Harmer
3.292
270191TR4_S_V150
Solar/Wind Harmer
1.734
270247TR4_N_V136
Solar/Wind Harmer
0.492
24642205MAYFLWER
Adder
0.36
970031AG2-029 GEN
Solar/Wind Harmer
16.895
247643Z2-116 C
Solar/Wind Harmer
0.039
270485AE1-090_GEN
Solar/Wind Harmer
0.337
959331AF2-224 GEN
Solar/Wind Harmer
5.544
965021AG1-366 GEN
Solar/Wind Harmer
1.289
270377AD1-106 GEN
Solar/Wind Harmer
3.284
270043AE2-236 GEN
Solar/Wind Harmer
2.87
942871AE2-306 GEN
Solar/Wind Harmer
0.468
270391AF1-285 GEN3
Solar/Wind Harmer
0.24
970349AG2-230 GEN
Solar/Wind Harmer
7.734
270535AF1-215 GEN1
Solar/Wind Harmer
2.22
972231SS25-0005
Solar/Wind Harmer
4.572
972181SS23-001
Solar/Wind Harmer
2.857
274752CRETE EC ;2U
Adder
2.355
274753CRETE EC ;3U
Adder
2.355
964401AG1-302 GEN
Solar/Wind Harmer
4.356
274724RIVER EC ;11
Adder
8.463
959141AF2-205 GEN
Solar/Wind Harmer
2.857
274802UNIV PARK;5U
Adder
2.744
961961AG1-039 GEN
Solar/Wind Harmer
1.348
274826FISK ;BP
Adder
5.143
274800UNIV PARK;3U
Adder
2.735
972038AH1-567 GEN2
Adder
0.171
276772AC2-154 GEN
Solar/Wind Harmer
1.306
276806AD2-047 C O1
Solar/Wind Harmer
5.01
970941AG2-585 GEN
Solar/Wind Harmer
5.854
274772LINCOLN ;3U
Adder
2.903
972228AH1-698 GEN2
Adder
1.73
274676JOLIET 29;8U
Adder
13.741
971617AH1-308 GEN
Solar/Wind Harmer
2.7
276897AD1-100 C
Solar/Wind Harmer
13.466
939351AE1-166 GEN
Solar/Wind Harmer
2.751
276893AG1-478 C
Solar/Wind Harmer
0.194
274729ELWOOD EC;1P
Adder
7.621
274730ELWOOD EC;6P
Adder
7.621
274734ELWOOD EC;8P
Adder
7.621
274736ELWOOD EC;9P
Adder
7.621
970707AG2-453 GEN
Solar/Wind Harmer
12.981
24189902OREGON_CT2
50/50
2.672
23856402BAYSG1
50/50
1.43
23888702TROY G3
50/50
1.831
972253AH1-711 GEN
50/50
55.942
23860302FRMENG 3
50/50
3.53
23920202STRYCT
50/50
2.045
241885AC2-103 GEN1
Solar/Wind Harmer
12.859
241807AE2-176_GEN
Solar/Wind Harmer
7.277
241858AF1-205_GEN
Solar/Wind Harmer
5.91
241808AF1-120 C
Solar/Wind Harmer
1.291
241840AF1-064_GEN
Solar/Wind Harmer
1.52
972301AH1-735 GEN
Adder
7.097
23906402RICHG1
Adder
1.419
23906502RICHG2&3
Adder
1.417
270361_3
Solar/Wind Harmer
9.742
960841AF2-375 GEN
Solar/Wind Harmer
4.291
247522W1-056 GEN
Solar/Wind Harmer
1.77
270428AC2-015 C
Solar/Wind Harmer
4.143
970515AG2-329 GEN
Solar/Wind Harmer
10.896
944231AF1-091 GEN
Solar/Wind Harmer
2.617
246936BC-WTG1
Solar/Wind Harmer
2.42
270489AE1-102 GEN1
Solar/Wind Harmer
0.804
965421AG1-410 GEN
Solar/Wind Harmer
18.372
24695305TIMB G C
Solar/Wind Harmer
3.301
270449AD2-020 GEN
Solar/Wind Harmer
1.666
943021AE2-325 GEN
Solar/Wind Harmer
2.165
970905AG2-564 GEN
Solar/Wind Harmer
2.943
945111AF1-176 GEN
Solar/Wind Harmer
10.388
270505AE1-170 C O1
Solar/Wind Harmer
8.723
247521TR3_G114
Solar/Wind Harmer
1.944
270246TR4_N_V150
Solar/Wind Harmer
0.492
24639705ELKHART HY
Adder
0.087
270063AE2-323 C
Solar/Wind Harmer
1.245
270462AD2-086
Solar/Wind Harmer
3.878
965011AG1-365 GEN
Solar/Wind Harmer
5.544
270223U2-072_GEN1
Solar/Wind Harmer
1.021
270578AF1-285 GEN2
Solar/Wind Harmer
0.624
270391AF1-285 GEN3
Solar/Wind Harmer
0.624
970373AG2-245 GEN
Solar/Wind Harmer
10.463
270055AF2-134 C O1
Solar/Wind Harmer
1.48
274751CRETE EC ;1U
Adder
2.355
274754CRETE EC ;4U
Adder
2.355
958381AF2-132 GEN
Solar/Wind Harmer
4.356
964861AG1-349 GEN
Solar/Wind Harmer
3.767
971917AH1-482 GEN
Solar/Wind Harmer
4.347
274723RIVER EC ;12
Adder
8.566
274812UNIV PK N;8U
Adder
2.383
276164X3-005 C
Solar/Wind Harmer
0.333
241847AF2-150_GEN
Solar/Wind Harmer
1.954
274801UNIV PARK;4U
Adder
2.735
940581AE2-045 GEN
Solar/Wind Harmer
4.778
971605AH1-302 GEN
Solar/Wind Harmer
4.086
276776AD2-060 GEN
Solar/Wind Harmer
0.198
972207SS24-0001
Solar/Wind Harmer
10.32
274773LINCOLN ;4U
Adder
2.903
274774LINCOLN ;5U
Adder
2.903
274676JOLIET 29;8U
Adder
14.25
941551AE2-152 GEN
Solar/Wind Harmer
2.104
274732ELWOOD EC;7P
Adder
7.621
274674JOLIET 9 ;6U
Adder
7.138
970245AG2-165 GEN
Solar/Wind Harmer
8.259
274871GR RIDGE ;2U
Solar/Wind Harmer
3.545
274745AC1-111 GEN9
Adder
2.563
274682WAUKEGAN ;7U
Adder
8.182
274828WAUKEGAN ;BP
Adder
5.024
274822ROCKFORD ;11
Adder
8.741
972235AH1-702 GEN1
Adder
1.121
274761LEE CO EC;2U
Adder
4.095
274766LEE CO EC;7U
Adder
4.047
961971AG1-040 GEN
Solar/Wind Helper
0.361
203835AF1-098 GEN
Solar/Wind Helper
1.422
203860AG1-193 C
Solar/Wind Helper
0.161
241966AE1-183 GEN
Solar/Wind Helper
0.14
254303AC2-168 GEN
Solar/Wind Helper
0.082
203954AE2-126 C
Solar/Wind Helper
0.235
23867002DVBSG1
50/50
12.801
972211AH1-690 GEN
50/50
288.187
23888502TROY G1
50/50
1.831
23888602TROY G2
50/50
1.831
23860102FRMENG 1
50/50
1.729
23860202FRMENG 2
50/50
1.729
24191202EL_AA1-006
50/50
0.333
241886AC2-103 GEN2
Solar/Wind Harmer
12.859
970817AG2-515 GEN
Solar/Wind Harmer
15.71
945411AF1-206 GEN
Solar/Wind Harmer
8.65
270499AE1-146 GEN
Solar/Wind Harmer
2.686
945641AF1-229 GEN
Solar/Wind Harmer
3.662
270297AD1-101 GEN
Solar/Wind Harmer
2.06
971549AH1-272 GEN
Solar/Wind Harmer
13.433
966831AG1-554 GEN
Solar/Wind Harmer
0.787
971989AH1-539 GEN
Solar/Wind Harmer
8.505
247607V1-011 GEN
Solar/Wind Harmer
2.482
957201AF2-014 GEN
Solar/Wind Harmer
2.805
270435AC2-044 GEN
Solar/Wind Harmer
1.237
944161AF1-084 GEN
Solar/Wind Harmer
1.331
965041AG1-368 GEN
Solar/Wind Harmer
5.807
965051AG1-369 GEN
Solar/Wind Harmer
2.887
270302AB2-170 GEN
Solar/Wind Harmer
4.661
270317AD1-130_GEN
Solar/Wind Harmer
1.787
971771AH1-392 GEN
Solar/Wind Harmer
4.969
971567AH1-282 GEN
Solar/Wind Harmer
8.2
971769AH1-391 GEN
Solar/Wind Harmer
5.381
960681AF2-359 GEN
Solar/Wind Harmer
1.956
270578AF1-285 GEN2
Solar/Wind Harmer
0.24
971347AH1-153 GEN
Solar/Wind Harmer
7.734
963791AG1-232 GEN
Solar/Wind Harmer
6.936
270536AF1-215 GEN2
Solar/Wind Harmer
2.22
270071AF1-092 GEN
Solar/Wind Harmer
7.277
958391AF2-133 GEN
Solar/Wind Harmer
4.316
274814UNIV PK N;0U
Adder
2.404
274807UNIV PK N;3U
Adder
2.399
274805UNIV PK N;1U
Adder
2.388
274811UNIV PK N;7U
Adder
2.383
972037AH1-567 GEN1
Adder
0.086
274827FISK ;RP
Adder
3.645
960591AF2-350 GEN
Solar/Wind Harmer
4.683
274775LINCOLN ;6U
Adder
2.903
274776LINCOLN ;7U
Adder
2.903
274777LINCOLN ;8U
Adder
2.903
972227AH1-698 GEN1
Adder
1.218
274687WILL CNTY;4U
Adder
13.005
274687WILL CNTY;4U
Adder
13.005
270024AE2-089 GEN
Solar/Wind Harmer
2.18
274675JOLIET 29;7U
Adder
14.25
274675JOLIET 29;7U
Adder
13.741
274731ELWOOD EC;2P
Adder
7.621
274733ELWOOD EC;3P
Adder
7.621
274735ELWOOD EC;4P
Adder
7.621
274728ELWOOD EC;5P
Adder
7.621
970833AG2-524 GEN
Solar/Wind Harmer
4.028
970833AG2-524 GEN
Solar/Wind Harmer
1.873
274746AC1-111 G10
Adder
2.563
274744AC1-111 GEN8
Adder
2.563
24729505KEY G4
Adder
2.933
274823ROCKFORD ;21
Adder
8.678
241982AE2-343 S C
Solar/Wind Helper
0.127
254304AE2-114 C
Solar/Wind Helper
0.121
203846AF2-130 C
Solar/Wind Helper
0.267
241997AF1-093 GEN
Solar/Wind Helper
0.14
203804AE2-113_GEN
Solar/Wind Helper
0.935
203855AF2-088 C
Solar/Wind Helper
0.073
970513AG2-328 GEN
Solar/Wind Harmer
8.259
970517AG2-330 GEN
Solar/Wind Harmer
7.49
274682WAUKEGAN ;7U
Adder
8.182
972236AH1-702 GEN2
Adder
0.975
274760LEE CO EC;1U
Adder
4.095
274767LEE CO EC;8U
Adder
4.047
962511AG1-100 GEN
Solar/Wind Helper
0.369
203830AF1-094 GEN
Solar/Wind Helper
0.349
959441AF2-235 GEN
Solar/Wind Helper
0.159
254305AE2-115 C
Solar/Wind Helper
0.121
20334926Z1-069 C
Solar/Wind Helper
0.696
203854AF2-039 C
Solar/Wind Helper
0.151
203818AF1-086 GEN
Solar/Wind Helper
0.772
943121AE2-341 GEN
Solar/Wind Harmer
2.136
943591AF1-030 GEN
Solar/Wind Harmer
1.424
991182J1586 G
External Queue
25.292837142944336
990527J1329
External Queue
1.8513455390930176
990142J1224
External Queue
13.53333568572998
991177J1571 G
External Queue
15.714932441711426
LAGNLTFEXP_LAGN->PJM
CLTF
5.047
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.15
TVALTFEXP_TVA->PJM
CLTF
2.288
CPLELTFEXP_CPLE->PJM
CLTF
0.293
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.459
CBM West 1LTFEXP_CBM-W1->PJM
CBM
95.745
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.083
MECLTFEXP_MEC->PJM
CLTF
6.617
SIGELTFEXP_SIGE->PJM
CLTF
0.172
NYPJM->LTFIMP_NY
CLTF
2.188
LGEELTFEXP_LGEE->PJM
CLTF
2.068
WECLTFEXP_WEC->PJM
CLTF
1.698
AG2-052LTFEXP_AG2-052->PJM
LTF
0.109
AH1-155LTFEXP_AH1-155->PJM
LTF
0.164

Details for 02HAYES-02BEAVER 345.0 kV Ckt 1 line l/o ATSI_P2-3_OEC-345-006_SRT-SL


Base Case Flowgate

Area:ATSI
Facility Description:
02HAYES-02BEAVER 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_OEC-345-006_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:144.08 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:2705.74
MW Contribution:0.44
Bus #Bus NameTypeMW Contribution
24190002OREGON_ST1
50/50
3.613
24189802OREGON_CT1
50/50
2.741
23888802TROY G4
50/50
1.842
241996AE2-282_GEN
Solar/Wind Harmer
2.333
971677AH1-339 GEN
Solar/Wind Harmer
7.68
270007AE1-245 C
Solar/Wind Harmer
3.775
942801AE2-298 GEN
Solar/Wind Harmer
0.956
246938BC-WTG3
Solar/Wind Harmer
2.496
246937BC-WTG2
Solar/Wind Harmer
2.454
961051AF2-396 GEN
Solar/Wind Harmer
9.484
961051AF2-396 GEN
Solar/Wind Harmer
4.411
960981AF2-389 GEN
Solar/Wind Harmer
0.888
957891AF2-083 GEN
Solar/Wind Harmer
1.981
247620Y3-023
Adder
0.266
270216AD2-079_GEN
Solar/Wind Harmer
0.344
970611AG2-400 GEN
Solar/Wind Harmer
5.623
270526AF1-158 GEN
Solar/Wind Harmer
2.491
971231AH1-075 GEN
Solar/Wind Harmer
0.437
24441505OLIV SLR
Solar/Wind Harmer
0.073
965681AG1-436 GEN
Solar/Wind Harmer
6.563
965791AG1-447 GEN
Solar/Wind Harmer
3.358
270224U2-072_GEN2
Solar/Wind Harmer
1.038
270227U2-072_GEN3
Solar/Wind Harmer
1.038
270228U2-072_GEN4
Solar/Wind Harmer
1.038
270231U2-072_GEN5
Solar/Wind Harmer
1.038
274808UNIV PK N;4U
Adder
2.408
274803UNIV PARK;6U
Adder
2.785
942221AE2-234 GEN
Solar/Wind Harmer
0.349
274888KELLY CRK;1U
Solar/Wind Harmer
2.807
274887GEN-1.85
Solar/Wind Harmer
2.534
276843GEN-1.7
Solar/Wind Harmer
0.273
958011AF2-095 GEN
Solar/Wind Harmer
6.846
274770LINCOLN ;1U
Adder
2.947
274771LINCOLN ;2U
Adder
2.947
24189902OREGON_CT2
50/50
2.686
23856402BAYSG1
50/50
1.441
23888702TROY G3
50/50
1.842
972253AH1-711 GEN
50/50
56.254
23860302FRMENG 3
50/50
3.59
23920202STRYCT
50/50
2.06
241885AC2-103 GEN1
Solar/Wind Harmer
12.88
241807AE2-176_GEN
Solar/Wind Harmer
7.419
241858AF1-205_GEN
Solar/Wind Harmer
5.953
241808AF1-120 C
Solar/Wind Harmer
1.301
241840AF1-064_GEN
Solar/Wind Harmer
1.533
972301AH1-735 GEN
Adder
7.158
23906402RICHG1
Adder
1.432
23906502RICHG2&3
Adder
1.43
270361_3
Solar/Wind Harmer
9.878
960841AF2-375 GEN
Solar/Wind Harmer
4.35
247522W1-056 GEN
Solar/Wind Harmer
1.802
270428AC2-015 C
Solar/Wind Harmer
4.301
970515AG2-329 GEN
Solar/Wind Harmer
11.13
944231AF1-091 GEN
Solar/Wind Harmer
2.648
246936BC-WTG1
Solar/Wind Harmer
2.454
270489AE1-102 GEN1
Solar/Wind Harmer
0.815
965421AG1-410 GEN
Solar/Wind Harmer
18.626
970905AG2-564 GEN
Solar/Wind Harmer
3.098
24695305TIMB G C
Solar/Wind Harmer
3.347
270449AD2-020 GEN
Solar/Wind Harmer
1.687
943021AE2-325 GEN
Solar/Wind Harmer
2.193
945111AF1-176 GEN
Solar/Wind Harmer
10.521
270505AE1-170 C O1
Solar/Wind Harmer
8.835
247521TR3_G114
Solar/Wind Harmer
1.972
270246TR4_N_V150
Solar/Wind Harmer
0.499
24639705ELKHART HY
Adder
0.088
270063AE2-323 C
Solar/Wind Harmer
1.262
270462AD2-086
Solar/Wind Harmer
3.938
965011AG1-365 GEN
Solar/Wind Harmer
5.623
270223U2-072_GEN1
Solar/Wind Harmer
1.038
270578AF1-285 GEN2
Solar/Wind Harmer
0.635
270391AF1-285 GEN3
Solar/Wind Harmer
0.635
970373AG2-245 GEN
Solar/Wind Harmer
10.614
270055AF2-134 C O1
Solar/Wind Harmer
1.502
241847AF2-150_GEN
Solar/Wind Harmer
2.052
274751CRETE EC ;1U
Adder
2.389
274754CRETE EC ;4U
Adder
2.389
958381AF2-132 GEN
Solar/Wind Harmer
4.421
964861AG1-349 GEN
Solar/Wind Harmer
3.823
971917AH1-482 GEN
Solar/Wind Harmer
4.412
274723RIVER EC ;12
Adder
8.693
274812UNIV PK N;8U
Adder
2.419
276164X3-005 C
Solar/Wind Harmer
0.338
274801UNIV PARK;4U
Adder
2.776
940581AE2-045 GEN
Solar/Wind Harmer
4.851
971605AH1-302 GEN
Solar/Wind Harmer
4.148
276776AD2-060 GEN
Solar/Wind Harmer
0.201
972207SS24-0001
Solar/Wind Harmer
10.477
274773LINCOLN ;4U
Adder
2.947
274774LINCOLN ;5U
Adder
2.947
274676JOLIET 29;8U
Adder
14.467
941551AE2-152 GEN
Solar/Wind Harmer
2.137
274732ELWOOD EC;7P
Adder
7.738
274674JOLIET 9 ;6U
Adder
7.247
970245AG2-165 GEN
Solar/Wind Harmer
8.386
274871GR RIDGE ;2U
Solar/Wind Harmer
3.6
274745AC1-111 GEN9
Adder
2.602
274682WAUKEGAN ;7U
Adder
8.309
274828WAUKEGAN ;BP
Adder
5.102
274822ROCKFORD ;11
Adder
8.879
972235AH1-702 GEN1
Adder
1.138
274761LEE CO EC;2U
Adder
4.16
274766LEE CO EC;7U
Adder
4.111
961971AG1-040 GEN
Solar/Wind Helper
0.363
203835AF1-098 GEN
Solar/Wind Helper
1.429
203860AG1-193 C
Solar/Wind Helper
0.162
241966AE1-183 GEN
Solar/Wind Helper
0.141
254303AC2-168 GEN
Solar/Wind Helper
0.082
203954AE2-126 C
Solar/Wind Helper
0.236
23867002DVBSG1
50/50
12.822
972211AH1-690 GEN
50/50
289.616
23888502TROY G1
50/50
1.842
23888602TROY G2
50/50
1.842
23860102FRMENG 1
50/50
1.758
23860202FRMENG 2
50/50
1.758
24191202EL_AA1-006
50/50
0.345
241886AC2-103 GEN2
Solar/Wind Harmer
12.88
970817AG2-515 GEN
Solar/Wind Harmer
15.806
945411AF1-206 GEN
Solar/Wind Harmer
8.713
270499AE1-146 GEN
Solar/Wind Harmer
2.723
945641AF1-229 GEN
Solar/Wind Harmer
3.712
270297AD1-101 GEN
Solar/Wind Harmer
2.086
971549AH1-272 GEN
Solar/Wind Harmer
13.576
966831AG1-554 GEN
Solar/Wind Harmer
0.802
971989AH1-539 GEN
Solar/Wind Harmer
8.669
247607V1-011 GEN
Solar/Wind Harmer
2.516
957201AF2-014 GEN
Solar/Wind Harmer
2.844
270435AC2-044 GEN
Solar/Wind Harmer
1.254
944161AF1-084 GEN
Solar/Wind Harmer
1.348
965041AG1-368 GEN
Solar/Wind Harmer
5.889
965051AG1-369 GEN
Solar/Wind Harmer
2.928
270302AB2-170 GEN
Solar/Wind Harmer
4.734
270317AD1-130_GEN
Solar/Wind Harmer
1.815
971567AH1-282 GEN
Solar/Wind Harmer
8.435
971771AH1-392 GEN
Solar/Wind Harmer
5.035
971769AH1-391 GEN
Solar/Wind Harmer
5.455
960681AF2-359 GEN
Solar/Wind Harmer
1.984
270578AF1-285 GEN2
Solar/Wind Harmer
0.244
971347AH1-153 GEN
Solar/Wind Harmer
7.843
963791AG1-232 GEN
Solar/Wind Harmer
7.04
270536AF1-215 GEN2
Solar/Wind Harmer
2.253
270071AF1-092 GEN
Solar/Wind Harmer
7.388
958391AF2-133 GEN
Solar/Wind Harmer
4.381
274814UNIV PK N;0U
Adder
2.44
274807UNIV PK N;3U
Adder
2.434
274805UNIV PK N;1U
Adder
2.424
274811UNIV PK N;7U
Adder
2.419
972037AH1-567 GEN1
Adder
0.087
274827FISK ;RP
Adder
3.7
960591AF2-350 GEN
Solar/Wind Harmer
4.754
274775LINCOLN ;6U
Adder
2.947
274776LINCOLN ;7U
Adder
2.947
274777LINCOLN ;8U
Adder
2.947
972227AH1-698 GEN1
Adder
1.236
274687WILL CNTY;4U
Adder
13.203
274687WILL CNTY;4U
Adder
13.203
270024AE2-089 GEN
Solar/Wind Harmer
2.215
274675JOLIET 29;7U
Adder
14.468
274675JOLIET 29;7U
Adder
13.951
274731ELWOOD EC;2P
Adder
7.738
274733ELWOOD EC;3P
Adder
7.738
274735ELWOOD EC;4P
Adder
7.738
274728ELWOOD EC;5P
Adder
7.738
970833AG2-524 GEN
Solar/Wind Harmer
4.089
970833AG2-524 GEN
Solar/Wind Harmer
1.902
274746AC1-111 G10
Adder
2.602
274744AC1-111 GEN8
Adder
2.602
24729505KEY G4
Adder
2.98
274823ROCKFORD ;21
Adder
8.814
241982AE2-343 S C
Solar/Wind Helper
0.127
254304AE2-114 C
Solar/Wind Helper
0.121
203846AF2-130 C
Solar/Wind Helper
0.268
241997AF1-093 GEN
Solar/Wind Helper
0.141
203804AE2-113_GEN
Solar/Wind Helper
0.937
203855AF2-088 C
Solar/Wind Helper
0.073
23929302BS-PKR
50/50
2.537
241832AE2-181_GEN
Solar/Wind Harmer
2.114
958321AF2-126 GEN
Solar/Wind Harmer
1.643
23906502RICHG2&3
Adder
1.43
270575GUS2 35KV
Solar/Wind Harmer
11.637
270541AE2-072 C
Solar/Wind Harmer
4.757
970217AG2-149 GEN
Solar/Wind Harmer
24.543
270044AE2-322 C
Solar/Wind Harmer
0.925
270404AC1-167 GEN
Solar/Wind Harmer
0.77
270588AE1-091_GEN
Solar/Wind Harmer
7.618
270258AD1-119 GEN
Solar/Wind Harmer
1.882
247604X1-042
Adder
0.268
958091AF2-103 GEN
Solar/Wind Harmer
0.103
24441205WTRV SLR C
Solar/Wind Harmer
0.085
270491AE1-102 GEN2
Solar/Wind Harmer
0.815
945111AF1-176 GEN
Solar/Wind Harmer
3.334
270191TR4_S_V150
Solar/Wind Harmer
1.759
270247TR4_N_V136
Solar/Wind Harmer
0.499
24642205MAYFLWER
Adder
0.364
970031AG2-029 GEN
Solar/Wind Harmer
17.123
247643Z2-116 C
Solar/Wind Harmer
0.04
270485AE1-090_GEN
Solar/Wind Harmer
0.342
959331AF2-224 GEN
Solar/Wind Harmer
5.623
965021AG1-366 GEN
Solar/Wind Harmer
1.308
270377AD1-106 GEN
Solar/Wind Harmer
3.371
270043AE2-236 GEN
Solar/Wind Harmer
2.911
942871AE2-306 GEN
Solar/Wind Harmer
0.476
270391AF1-285 GEN3
Solar/Wind Harmer
0.244
970349AG2-230 GEN
Solar/Wind Harmer
7.843
270535AF1-215 GEN1
Solar/Wind Harmer
2.253
961961AG1-039 GEN
Solar/Wind Harmer
1.415
972231SS25-0005
Solar/Wind Harmer
4.639
972181SS23-001
Solar/Wind Harmer
2.9
274752CRETE EC ;2U
Adder
2.389
274753CRETE EC ;3U
Adder
2.389
964401AG1-302 GEN
Solar/Wind Harmer
4.421
274724RIVER EC ;11
Adder
8.59
959141AF2-205 GEN
Solar/Wind Harmer
2.9
274802UNIV PARK;5U
Adder
2.785
274826FISK ;BP
Adder
5.221
274800UNIV PARK;3U
Adder
2.776
972038AH1-567 GEN2
Adder
0.174
276772AC2-154 GEN
Solar/Wind Harmer
1.326
276806AD2-047 C O1
Solar/Wind Harmer
5.086
970941AG2-585 GEN
Solar/Wind Harmer
5.943
274772LINCOLN ;3U
Adder
2.947
972228AH1-698 GEN2
Adder
1.756
971617AH1-308 GEN
Solar/Wind Harmer
2.744
274676JOLIET 29;8U
Adder
13.951
276897AD1-100 C
Solar/Wind Harmer
13.671
939351AE1-166 GEN
Solar/Wind Harmer
2.793
276893AG1-478 C
Solar/Wind Harmer
0.197
970707AG2-453 GEN
Solar/Wind Harmer
13.179
274729ELWOOD EC;1P
Adder
7.738
274730ELWOOD EC;6P
Adder
7.738
274734ELWOOD EC;8P
Adder
7.738
274736ELWOOD EC;9P
Adder
7.738
970513AG2-328 GEN
Solar/Wind Harmer
8.386
970517AG2-330 GEN
Solar/Wind Harmer
7.606
274682WAUKEGAN ;7U
Adder
8.309
972236AH1-702 GEN2
Adder
0.99
274760LEE CO EC;1U
Adder
4.16
274767LEE CO EC;8U
Adder
4.111
962511AG1-100 GEN
Solar/Wind Helper
0.371
203830AF1-094 GEN
Solar/Wind Helper
0.351
959441AF2-235 GEN
Solar/Wind Helper
0.159
254305AE2-115 C
Solar/Wind Helper
0.121
20334926Z1-069 C
Solar/Wind Helper
0.698
203854AF2-039 C
Solar/Wind Helper
0.151
203818AF1-086 GEN
Solar/Wind Helper
0.773
943121AE2-341 GEN
Solar/Wind Harmer
2.169
943591AF1-030 GEN
Solar/Wind Harmer
1.446
972259AH1-714 GEN
Adder
9.004
274674JOLIET 9 ;6U
Adder
7.247
970321AG2-212 GEN
Solar/Wind Harmer
8.386
274847GR RIDGE ;BU
Solar/Wind Harmer
2.368
274696ROCKY RD ;4P
Adder
5.267
274695ROCKY RD ;2P
Adder
5.146
274693ROCKY RD ;1P
Adder
5.095
274697ROCKY RD ;3P
Adder
1.398
274683WAUKEGAN ;8U
Adder
9.733
274683WAUKEGAN ;8U
Adder
8.205
274764LEE CO EC;5U
Adder
4.169
274765LEE CO EC;6U
Adder
4.169
274762LEE CO EC;3U
Adder
4.16
274763LEE CO EC;4U
Adder
4.12
972267AH1-718 GEN
Adder
1.849
25326509SID D
Adder
0.581
247621Y3-024
Adder
0.105
203947AF1-006 C
Solar/Wind Helper
0.413
203980AG1-197 GEN
Solar/Wind Helper
0.27
203979AG1-198 GEN
Solar/Wind Helper
0.21
241967AE2-285_GEN
Solar/Wind Helper
0.366
241801AE1-079 GEN
Solar/Wind Helper
0.143
241985AE1-237 GEN
Solar/Wind Helper
0.142
962101AG1-054 GEN
Solar/Wind Helper
0.354
946381AF1-302 GEN
Solar/Wind Helper
0.114
238217AF1-153 C O1
Solar/Wind Helper
0.12
20398826ARMNA MT
Solar/Wind Helper
0.713
203853AF1-134 C O1
Solar/Wind Helper
0.223
991182J1586 G
External Queue
25.351587295532227
990527J1329
External Queue
1.8554641008377075
990142J1224
External Queue
13.56344223022461
991177J1571 G
External Queue
15.754436492919922
LAGNLTFEXP_LAGN->PJM
CLTF
5.168
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.294
TVALTFEXP_TVA->PJM
CLTF
2.348
CPLELTFEXP_CPLE->PJM
CLTF
0.34
CBM West 2LTFEXP_CBM-W2->PJM
CBM
41.311
CBM West 1LTFEXP_CBM-W1->PJM
CBM
96.822
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.312
MECLTFEXP_MEC->PJM
CLTF
6.73
SIGELTFEXP_SIGE->PJM
CLTF
0.176
NYPJM->LTFIMP_NY
CLTF
2.183
LGEELTFEXP_LGEE->PJM
CLTF
2.114
WECLTFEXP_WEC->PJM
CLTF
1.725
AG2-052LTFEXP_AG2-052->PJM
LTF
0.111
AH1-155LTFEXP_AH1-155->PJM
LTF
0.167

Details for 02HAYES-02BEAVER 345.0 kV Ckt 1 line l/o ATSI_P2-3_TE-345-010A_SRT-SL


Base Case Flowgate

Area:ATSI
Facility Description:
02HAYES-02BEAVER 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_TE-345-010A_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:142.21 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:2670.76
MW Contribution:0.43
Bus #Bus NameTypeMW Contribution
24189902OREGON_CT2
50/50
2.68
23856402BAYSG1
50/50
1.434
23888702TROY G3
50/50
1.837
972253AH1-711 GEN
50/50
56.101
23860302FRMENG 3
50/50
3.54
23920202STRYCT
50/50
2.052
241807AE2-176_GEN
Solar/Wind Harmer
7.294
241858AF1-205_GEN
Solar/Wind Harmer
5.929
241808AF1-120 C
Solar/Wind Harmer
1.295
241840AF1-064_GEN
Solar/Wind Harmer
1.525
972301AH1-735 GEN
Adder
7.125
23906402RICHG1
Adder
1.425
23906502RICHG2&3
Adder
1.423
270361_3
Solar/Wind Harmer
9.783
960841AF2-375 GEN
Solar/Wind Harmer
4.309
247522W1-056 GEN
Solar/Wind Harmer
1.78
270428AC2-015 C
Solar/Wind Harmer
4.168
970515AG2-329 GEN
Solar/Wind Harmer
10.964
944231AF1-091 GEN
Solar/Wind Harmer
2.634
246936BC-WTG1
Solar/Wind Harmer
2.439
270489AE1-102 GEN1
Solar/Wind Harmer
0.81
965421AG1-410 GEN
Solar/Wind Harmer
18.512
24695305TIMB G C
Solar/Wind Harmer
3.326
270449AD2-020 GEN
Solar/Wind Harmer
1.68
943021AE2-325 GEN
Solar/Wind Harmer
2.182
970905AG2-564 GEN
Solar/Wind Harmer
2.966
945111AF1-176 GEN
Solar/Wind Harmer
10.472
270505AE1-170 C O1
Solar/Wind Harmer
8.793
247521TR3_G114
Solar/Wind Harmer
1.96
270246TR4_N_V150
Solar/Wind Harmer
0.496
24639705ELKHART HY
Adder
0.088
270063AE2-323 C
Solar/Wind Harmer
1.255
270462AD2-086
Solar/Wind Harmer
3.91
965011AG1-365 GEN
Solar/Wind Harmer
5.591
270223U2-072_GEN1
Solar/Wind Harmer
1.03
270578AF1-285 GEN2
Solar/Wind Harmer
0.63
270391AF1-285 GEN3
Solar/Wind Harmer
0.63
970373AG2-245 GEN
Solar/Wind Harmer
10.561
270055AF2-134 C O1
Solar/Wind Harmer
1.494
274751CRETE EC ;1U
Adder
2.377
274754CRETE EC ;4U
Adder
2.377
958381AF2-132 GEN
Solar/Wind Harmer
4.398
964861AG1-349 GEN
Solar/Wind Harmer
3.804
971917AH1-482 GEN
Solar/Wind Harmer
4.39
274723RIVER EC ;12
Adder
8.649
274812UNIV PK N;8U
Adder
2.406
276164X3-005 C
Solar/Wind Harmer
0.336
241847AF2-150_GEN
Solar/Wind Harmer
1.974
274801UNIV PARK;4U
Adder
2.762
940581AE2-045 GEN
Solar/Wind Harmer
4.826
971605AH1-302 GEN
Solar/Wind Harmer
4.126
276776AD2-060 GEN
Solar/Wind Harmer
0.2
972207SS24-0001
Solar/Wind Harmer
10.423
274773LINCOLN ;4U
Adder
2.932
274774LINCOLN ;5U
Adder
2.932
274676JOLIET 29;8U
Adder
14.394
941551AE2-152 GEN
Solar/Wind Harmer
2.126
274732ELWOOD EC;7P
Adder
7.698
274674JOLIET 9 ;6U
Adder
7.21
970245AG2-165 GEN
Solar/Wind Harmer
8.342
274871GR RIDGE ;2U
Solar/Wind Harmer
3.581
274745AC1-111 GEN9
Adder
2.589
274682WAUKEGAN ;7U
Adder
8.266
274828WAUKEGAN ;BP
Adder
5.076
274822ROCKFORD ;11
Adder
8.833
972235AH1-702 GEN1
Adder
1.133
274761LEE CO EC;2U
Adder
4.138
274766LEE CO EC;7U
Adder
4.089
241885AC2-103 GEN1
Solar/Wind Helper
4.614
961971AG1-040 GEN
Solar/Wind Helper
0.358
203835AF1-098 GEN
Solar/Wind Helper
1.412
203860AG1-193 C
Solar/Wind Helper
0.16
241966AE1-183 GEN
Solar/Wind Helper
0.139
254303AC2-168 GEN
Solar/Wind Helper
0.081
203954AE2-126 C
Solar/Wind Helper
0.233
23867002DVBSG1
50/50
12.828
972211AH1-690 GEN
50/50
288.97
23888502TROY G1
50/50
1.837
23888602TROY G2
50/50
1.837
23860102FRMENG 1
50/50
1.734
23860202FRMENG 2
50/50
1.734
24191202EL_AA1-006
50/50
0.334
970817AG2-515 GEN
Solar/Wind Harmer
15.756
945411AF1-206 GEN
Solar/Wind Harmer
8.678
270499AE1-146 GEN
Solar/Wind Harmer
2.698
945641AF1-229 GEN
Solar/Wind Harmer
3.679
270297AD1-101 GEN
Solar/Wind Harmer
2.073
971549AH1-272 GEN
Solar/Wind Harmer
13.52
966831AG1-554 GEN
Solar/Wind Harmer
0.792
971989AH1-539 GEN
Solar/Wind Harmer
8.566
247607V1-011 GEN
Solar/Wind Harmer
2.5
957201AF2-014 GEN
Solar/Wind Harmer
2.826
270435AC2-044 GEN
Solar/Wind Harmer
1.246
944161AF1-084 GEN
Solar/Wind Harmer
1.342
965041AG1-368 GEN
Solar/Wind Harmer
5.854
965051AG1-369 GEN
Solar/Wind Harmer
2.91
270302AB2-170 GEN
Solar/Wind Harmer
4.7
270317AD1-130_GEN
Solar/Wind Harmer
1.802
971771AH1-392 GEN
Solar/Wind Harmer
5.011
971567AH1-282 GEN
Solar/Wind Harmer
8.27
971769AH1-391 GEN
Solar/Wind Harmer
5.428
960681AF2-359 GEN
Solar/Wind Harmer
1.974
270578AF1-285 GEN2
Solar/Wind Harmer
0.242
971347AH1-153 GEN
Solar/Wind Harmer
7.804
963791AG1-232 GEN
Solar/Wind Harmer
7
270536AF1-215 GEN2
Solar/Wind Harmer
2.241
270071AF1-092 GEN
Solar/Wind Harmer
7.347
958391AF2-133 GEN
Solar/Wind Harmer
4.359
274814UNIV PK N;0U
Adder
2.427
274807UNIV PK N;3U
Adder
2.422
274805UNIV PK N;1U
Adder
2.412
274811UNIV PK N;7U
Adder
2.406
972037AH1-567 GEN1
Adder
0.087
274827FISK ;RP
Adder
3.681
960591AF2-350 GEN
Solar/Wind Harmer
4.73
274775LINCOLN ;6U
Adder
2.932
274776LINCOLN ;7U
Adder
2.932
274777LINCOLN ;8U
Adder
2.932
972227AH1-698 GEN1
Adder
1.23
274687WILL CNTY;4U
Adder
13.136
274687WILL CNTY;4U
Adder
13.136
270024AE2-089 GEN
Solar/Wind Harmer
2.202
274675JOLIET 29;7U
Adder
14.394
274675JOLIET 29;7U
Adder
13.88
274731ELWOOD EC;2P
Adder
7.698
274733ELWOOD EC;3P
Adder
7.698
274735ELWOOD EC;4P
Adder
7.698
274728ELWOOD EC;5P
Adder
7.698
970833AG2-524 GEN
Solar/Wind Harmer
4.069
970833AG2-524 GEN
Solar/Wind Harmer
1.892
274746AC1-111 G10
Adder
2.589
274744AC1-111 GEN8
Adder
2.589
24729505KEY G4
Adder
2.963
274823ROCKFORD ;21
Adder
8.769
241886AC2-103 GEN2
Solar/Wind Helper
4.614
241982AE2-343 S C
Solar/Wind Helper
0.126
254304AE2-114 C
Solar/Wind Helper
0.12
203846AF2-130 C
Solar/Wind Helper
0.265
241997AF1-093 GEN
Solar/Wind Helper
0.139
203804AE2-113_GEN
Solar/Wind Helper
0.926
203855AF2-088 C
Solar/Wind Helper
0.072
23929302BS-PKR
50/50
2.524
241832AE2-181_GEN
Solar/Wind Harmer
2.105
958321AF2-126 GEN
Solar/Wind Harmer
1.635
23906502RICHG2&3
Adder
1.423
270575GUS2 35KV
Solar/Wind Harmer
11.525
270541AE2-072 C
Solar/Wind Harmer
4.728
970217AG2-149 GEN
Solar/Wind Harmer
24.176
270044AE2-322 C
Solar/Wind Harmer
0.919
270404AC1-167 GEN
Solar/Wind Harmer
0.766
270588AE1-091_GEN
Solar/Wind Harmer
7.54
270258AD1-119 GEN
Solar/Wind Harmer
1.871
247604X1-042
Adder
0.267
958091AF2-103 GEN
Solar/Wind Harmer
0.102
24441205WTRV SLR C
Solar/Wind Harmer
0.084
270491AE1-102 GEN2
Solar/Wind Harmer
0.81
945111AF1-176 GEN
Solar/Wind Harmer
3.319
270191TR4_S_V150
Solar/Wind Harmer
1.748
270247TR4_N_V136
Solar/Wind Harmer
0.496
24642205MAYFLWER
Adder
0.363
970031AG2-029 GEN
Solar/Wind Harmer
17.036
247643Z2-116 C
Solar/Wind Harmer
0.039
270485AE1-090_GEN
Solar/Wind Harmer
0.34
959331AF2-224 GEN
Solar/Wind Harmer
5.591
965021AG1-366 GEN
Solar/Wind Harmer
1.3
270377AD1-106 GEN
Solar/Wind Harmer
3.313
270043AE2-236 GEN
Solar/Wind Harmer
2.896
942871AE2-306 GEN
Solar/Wind Harmer
0.472
270391AF1-285 GEN3
Solar/Wind Harmer
0.242
970349AG2-230 GEN
Solar/Wind Harmer
7.804
270535AF1-215 GEN1
Solar/Wind Harmer
2.241
972231SS25-0005
Solar/Wind Harmer
4.616
972181SS23-001
Solar/Wind Harmer
2.885
274752CRETE EC ;2U
Adder
2.377
274753CRETE EC ;3U
Adder
2.377
964401AG1-302 GEN
Solar/Wind Harmer
4.398
274724RIVER EC ;11
Adder
8.546
959141AF2-205 GEN
Solar/Wind Harmer
2.885
274802UNIV PARK;5U
Adder
2.771
961961AG1-039 GEN
Solar/Wind Harmer
1.361
274826FISK ;BP
Adder
5.194
274800UNIV PARK;3U
Adder
2.762
972038AH1-567 GEN2
Adder
0.173
276772AC2-154 GEN
Solar/Wind Harmer
1.319
276806AD2-047 C O1
Solar/Wind Harmer
5.06
970941AG2-585 GEN
Solar/Wind Harmer
5.913
274772LINCOLN ;3U
Adder
2.932
972228AH1-698 GEN2
Adder
1.747
274676JOLIET 29;8U
Adder
13.879
971617AH1-308 GEN
Solar/Wind Harmer
2.727
276897AD1-100 C
Solar/Wind Harmer
13.601
939351AE1-166 GEN
Solar/Wind Harmer
2.779
276893AG1-478 C
Solar/Wind Harmer
0.196
970707AG2-453 GEN
Solar/Wind Harmer
13.112
274729ELWOOD EC;1P
Adder
7.698
274730ELWOOD EC;6P
Adder
7.698
274734ELWOOD EC;8P
Adder
7.698
274736ELWOOD EC;9P
Adder
7.698
970513AG2-328 GEN
Solar/Wind Harmer
8.342
970517AG2-330 GEN
Solar/Wind Harmer
7.566
274682WAUKEGAN ;7U
Adder
8.266
972236AH1-702 GEN2
Adder
0.985
274760LEE CO EC;1U
Adder
4.138
274767LEE CO EC;8U
Adder
4.089
962511AG1-100 GEN
Solar/Wind Helper
0.366
203830AF1-094 GEN
Solar/Wind Helper
0.347
959441AF2-235 GEN
Solar/Wind Helper
0.157
254305AE2-115 C
Solar/Wind Helper
0.12
20334926Z1-069 C
Solar/Wind Helper
0.689
203854AF2-039 C
Solar/Wind Helper
0.149
943121AE2-341 GEN
Solar/Wind Harmer
5.427
943591AF1-030 GEN
Solar/Wind Harmer
3.618
24190002OREGON_ST1
50/50
3.605
24189802OREGON_CT1
50/50
2.735
23888802TROY G4
50/50
1.837
241996AE2-282_GEN
Solar/Wind Harmer
2.323
971677AH1-339 GEN
Solar/Wind Harmer
7.59
270007AE1-245 C
Solar/Wind Harmer
3.751
942801AE2-298 GEN
Solar/Wind Harmer
0.95
246938BC-WTG3
Solar/Wind Harmer
2.481
246937BC-WTG2
Solar/Wind Harmer
2.439
961051AF2-396 GEN
Solar/Wind Harmer
9.439
961051AF2-396 GEN
Solar/Wind Harmer
4.39
960981AF2-389 GEN
Solar/Wind Harmer
0.884
957891AF2-083 GEN
Solar/Wind Harmer
1.971
247620Y3-023
Adder
0.264
270216AD2-079_GEN
Solar/Wind Harmer
0.343
970611AG2-400 GEN
Solar/Wind Harmer
5.591
270526AF1-158 GEN
Solar/Wind Harmer
2.479
24441505OLIV SLR
Solar/Wind Harmer
0.073
971231AH1-075 GEN
Solar/Wind Harmer
0.429
965681AG1-436 GEN
Solar/Wind Harmer
6.531
965791AG1-447 GEN
Solar/Wind Harmer
3.341
270224U2-072_GEN2
Solar/Wind Harmer
1.03
270227U2-072_GEN3
Solar/Wind Harmer
1.03
270228U2-072_GEN4
Solar/Wind Harmer
1.03
270231U2-072_GEN5
Solar/Wind Harmer
1.03
274808UNIV PK N;4U
Adder
2.396
274803UNIV PARK;6U
Adder
2.771
942221AE2-234 GEN
Solar/Wind Harmer
0.347
274888KELLY CRK;1U
Solar/Wind Harmer
2.793
274887GEN-1.85
Solar/Wind Harmer
2.521
276843GEN-1.7
Solar/Wind Harmer
0.271
958011AF2-095 GEN
Solar/Wind Harmer
6.812
274770LINCOLN ;1U
Adder
2.932
274771LINCOLN ;2U
Adder
2.932
972259AH1-714 GEN
Adder
8.958
274674JOLIET 9 ;6U
Adder
7.21
970321AG2-212 GEN
Solar/Wind Harmer
8.342
274847GR RIDGE ;BU
Solar/Wind Harmer
2.356
274696ROCKY RD ;4P
Adder
5.24
274695ROCKY RD ;2P
Adder
5.12
274693ROCKY RD ;1P
Adder
5.069
274697ROCKY RD ;3P
Adder
1.391
274683WAUKEGAN ;8U
Adder
9.683
274683WAUKEGAN ;8U
Adder
8.163
274764LEE CO EC;5U
Adder
4.148
274765LEE CO EC;6U
Adder
4.148
274762LEE CO EC;3U
Adder
4.138
274763LEE CO EC;4U
Adder
4.099
972267AH1-718 GEN
Adder
1.84
25326509SID D
Adder
0.576
247621Y3-024
Adder
0.105
203947AF1-006 C
Solar/Wind Helper
0.408
203980AG1-197 GEN
Solar/Wind Helper
0.267
203979AG1-198 GEN
Solar/Wind Helper
0.208
241967AE2-285_GEN
Solar/Wind Helper
0.362
241801AE1-079 GEN
Solar/Wind Helper
0.141
241985AE1-237 GEN
Solar/Wind Helper
0.14
962101AG1-054 GEN
Solar/Wind Helper
0.35
946381AF1-302 GEN
Solar/Wind Helper
0.112
238217AF1-153 C O1
Solar/Wind Helper
0.119
20398826ARMNA MT
Solar/Wind Helper
0.704
991182J1586 G
External Queue
25.292837142944336
990527J1329
External Queue
1.8513455390930176
990142J1224
External Queue
13.53333568572998
991177J1571 G
External Queue
15.714932441711426
LAGNLTFEXP_LAGN->PJM
CLTF
5.142
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.292
TVALTFEXP_TVA->PJM
CLTF
2.336
CPLELTFEXP_CPLE->PJM
CLTF
0.344
CBM West 2LTFEXP_CBM-W2->PJM
CBM
41.091
CBM West 1LTFEXP_CBM-W1->PJM
CBM
96.429
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.261
MECLTFEXP_MEC->PJM
CLTF
6.695
SIGELTFEXP_SIGE->PJM
CLTF
0.175
NYPJM->LTFIMP_NY
CLTF
2.158
LGEELTFEXP_LGEE->PJM
CLTF
2.101
WECLTFEXP_WEC->PJM
CLTF
1.716
AG2-052LTFEXP_AG2-052->PJM
LTF
0.11
AH1-155LTFEXP_AH1-155->PJM
LTF
0.166

Details for 02HAYES-02BEAVER 345.0 kV Ckt 1 line l/o ATSI_P1-2_OEC-345-825_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02HAYES-02BEAVER 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_OEC-345-825_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:136.05 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:2554.95
MW Contribution:0.43
Bus #Bus NameTypeMW Contribution
24190002OREGON_ST1
50/50
3.603
24189802OREGON_CT1
50/50
2.733
23888802TROY G4
50/50
1.836
241996AE2-282_GEN
Solar/Wind Harmer
0.006
971677AH1-339 GEN
Solar/Wind Harmer
0.745
970621AG2-405 GEN
Solar/Wind Harmer
0.95
970623AG2-406 GEN
Solar/Wind Harmer
0.856
270007AE1-245 C
Solar/Wind Harmer
0.001
246938BC-WTG3
Solar/Wind Harmer
0.157
246937BC-WTG2
Solar/Wind Harmer
0.176
961051AF2-396 GEN
Solar/Wind Harmer
8.284
961051AF2-396 GEN
Solar/Wind Harmer
5.523
957891AF2-083 GEN
Solar/Wind Harmer
0.001
247620Y3-023
Adder
0.264
270216AD2-079_GEN
Solar/Wind Harmer
0.001
970611AG2-400 GEN
Solar/Wind Harmer
3.894
970627AG2-408 GEN
Solar/Wind Harmer
1.168
270526AF1-158 GEN
Solar/Wind Harmer
0.005
24441505OLIV SLR
Solar/Wind Harmer
0
971231AH1-075 GEN
Solar/Wind Harmer
0.428
965681AG1-436 GEN
Solar/Wind Harmer
4.548
965791AG1-447 GEN
Solar/Wind Harmer
3.335
270224U2-072_GEN2
Solar/Wind Harmer
0
270227U2-072_GEN3
Solar/Wind Harmer
0
270228U2-072_GEN4
Solar/Wind Harmer
0
270231U2-072_GEN5
Solar/Wind Harmer
0
274808UNIV PK N;4U
Adder
2.391
274803UNIV PARK;6U
Adder
2.765
942221AE2-234 GEN
Solar/Wind Harmer
0.017
274888KELLY CRK;1U
Solar/Wind Harmer
0.193
274887GEN-1.85
Solar/Wind Harmer
0.087
276843GEN-1.7
Solar/Wind Harmer
0.107
958011AF2-095 GEN
Solar/Wind Harmer
4.742
274770LINCOLN ;1U
Adder
3.982
274771LINCOLN ;2U
Adder
3.982
972259AH1-714 GEN
Adder
8.939
274674JOLIET 9 ;6U
Adder
7.195
970321AG2-212 GEN
Solar/Wind Harmer
1.409
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
958481AF2-142 GEN
Solar/Wind Harmer
4.833
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.436
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
971573AH1-285 GEN
Solar/Wind Harmer
0.598
274696ROCKY RD ;4P
Adder
5.229
274695ROCKY RD ;2P
Adder
5.109
274693ROCKY RD ;1P
Adder
5.059
274697ROCKY RD ;3P
Adder
1.388
274683WAUKEGAN ;8U
Adder
9.663
274683WAUKEGAN ;8U
Adder
8.145
958491AF2-143 GEN
Solar/Wind Harmer
4.791
962691AG1-118 GEN
Solar/Wind Harmer
9.548
274879MINONK ;1U
Solar/Wind Harmer
0.134
970921AG2-575 GEN
Solar/Wind Harmer
3.177
970921AG2-575 GEN
Solar/Wind Harmer
1.059
942991AE2-321 GEN
Solar/Wind Harmer
3.534
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
971333AH1-146 GEN
Solar/Wind Harmer
6.305
971335AH1-147 GEN
Solar/Wind Harmer
6.305
971341AH1-150 GEN
Solar/Wind Harmer
6.279
971343AH1-151 GEN
Solar/Wind Harmer
6.279
274856ECOGROVE ;U1
Solar/Wind Harmer
0.074
276611AD2-172 GEN
Solar/Wind Harmer
0.001
938861AE1-114 GEN
Solar/Wind Harmer
1.759
274764LEE CO EC;5U
Adder
4.139
274765LEE CO EC;6U
Adder
4.139
274762LEE CO EC;3U
Adder
4.129
274763LEE CO EC;4U
Adder
4.09
966841AG1-555 GEN
Solar/Wind Harmer
0.35
944541AF1-119 GEN
Solar/Wind Harmer
0.207
276603SUBLETTE C
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
1.815
274851PROVIDENC;RU
Solar/Wind Harmer
0
274849CRESCENT ;1U
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.121
276646AC1-214 GEN2
Solar/Wind Harmer
0.121
276741O09 GEN1
Solar/Wind Harmer
0.109
276708O09 GEN2
Solar/Wind Harmer
0.109
276782AC1-033 GEN
Solar/Wind Harmer
0
270201AC2-176 GEN
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
0.227
253378AE2-206_GEN
Solar/Wind Harmer
0.002
276820AF1-078_GEN
Solar/Wind Harmer
0.001
970329AG2-216 GEN
Solar/Wind Harmer
1.305
960611AF2-352 GEN
Solar/Wind Harmer
1.007
270599AE1-208 GEN
Solar/Wind Harmer
2.766
270031AE2-169
Solar/Wind Harmer
1.66
203947AF1-006 C
Solar/Wind Helper
0.409
203980AG1-197 GEN
Solar/Wind Helper
0.267
203979AG1-198 GEN
Solar/Wind Helper
0.208
241967AE2-285_GEN
Solar/Wind Helper
0.363
241801AE1-079 GEN
Solar/Wind Helper
0.141
241985AE1-237 GEN
Solar/Wind Helper
0.141
962101AG1-054 GEN
Solar/Wind Helper
0.35
946381AF1-302 GEN
Solar/Wind Helper
0.113
238217AF1-153 C O1
Solar/Wind Helper
0.119
20398826ARMNA MT
Solar/Wind Helper
0.706
203853AF1-134 C O1
Solar/Wind Helper
0.221
24189902OREGON_CT2
50/50
2.678
23856402BAYSG1
50/50
1.433
23888702TROY G3
50/50
1.836
972253AH1-711 GEN
50/50
56.068
23860302FRMENG 3
50/50
3.538
23920202STRYCT
50/50
2.05
241885AC2-103 GEN1
Solar/Wind Harmer
-0.001
241807AE2-176_GEN
Solar/Wind Harmer
0.009
241858AF1-205_GEN
Solar/Wind Harmer
4.134
241808AF1-120 C
Solar/Wind Harmer
0.003
241840AF1-064_GEN
Solar/Wind Harmer
0.004
972301AH1-735 GEN
Adder
7.119
23906402RICHG1
Adder
1.424
23906502RICHG2&3
Adder
1.422
270361_3
Solar/Wind Harmer
5.343
960841AF2-375 GEN
Solar/Wind Harmer
-0.002
247522W1-056 GEN
Solar/Wind Harmer
0.001
270428AC2-015 C
Solar/Wind Harmer
0.003
970515AG2-329 GEN
Solar/Wind Harmer
13.687
944231AF1-091 GEN
Solar/Wind Harmer
1.299
246936BC-WTG1
Solar/Wind Harmer
0.176
270489AE1-102 GEN1
Solar/Wind Harmer
0.564
965421AG1-410 GEN
Solar/Wind Harmer
12.895
24695305TIMB G C
Solar/Wind Harmer
0.001
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.179
970905AG2-564 GEN
Solar/Wind Harmer
2.266
945111AF1-176 GEN
Solar/Wind Harmer
7.294
270505AE1-170 C O1
Solar/Wind Harmer
4.287
247521TR3_G114
Solar/Wind Harmer
0.148
270246TR4_N_V150
Solar/Wind Harmer
0.026
24639705ELKHART HY
Adder
0.087
270063AE2-323 C
Solar/Wind Harmer
0.003
270462AD2-086
Solar/Wind Harmer
0.008
965011AG1-365 GEN
Solar/Wind Harmer
3.894
270223U2-072_GEN1
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
7.354
270055AF2-134 C O1
Solar/Wind Harmer
0.003
274751CRETE EC ;1U
Adder
4
274754CRETE EC ;4U
Adder
4
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.381
274723RIVER EC ;12
Adder
8.632
274812UNIV PK N;8U
Adder
2.401
276164X3-005 C
Solar/Wind Harmer
0
274801UNIV PARK;4U
Adder
2.756
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
4.118
276776AD2-060 GEN
Solar/Wind Harmer
0.344
274773LINCOLN ;4U
Adder
3.982
274774LINCOLN ;5U
Adder
3.982
274676JOLIET 29;8U
Adder
14.364
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
7.682
274674JOLIET 9 ;6U
Adder
7.195
970245AG2-165 GEN
Solar/Wind Harmer
1.409
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
2.583
276691AA1-018 GEN1
Solar/Wind Harmer
0.39
274682WAUKEGAN ;7U
Adder
8.249
274828WAUKEGAN ;BP
Adder
5.065
276901AD2-066 C O1
Solar/Wind Harmer
0.003
939401AE1-172 GEN
Solar/Wind Harmer
2.382
962781AG1-127 GEN
Solar/Wind Harmer
3.024
24791305MDL-5G
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0.002
971997AH1-543 GEN
Solar/Wind Harmer
1.662
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
276861AD2-134 GEN
Solar/Wind Harmer
0.057
957471AF2-041 GEN
Solar/Wind Harmer
9.419
959081AF2-199 GEN
Solar/Wind Harmer
3.14
971067AG2-660 GEN
Solar/Wind Harmer
1.047
274822ROCKFORD ;11
Adder
8.814
970569AG2-363 GEN
Solar/Wind Harmer
9.385
972235AH1-702 GEN1
Adder
1.13
970819AG2-516 GEN
Solar/Wind Harmer
3.745
971475AH1-234 GEN
Solar/Wind Harmer
1.512
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
4.129
274766LEE CO EC;7U
Adder
0.439
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.001
965651AG1-433 GEN
Solar/Wind Harmer
0.908
276158O29GEN2
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
1.328
274877BISHOP HL;1U
Solar/Wind Harmer
0.103
276726Z2-087_GEN
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
4.276
274854TWINGROVE;U2
Solar/Wind Harmer
0.001
945371AF1-202 GEN
Solar/Wind Harmer
0
961971AG1-040 GEN
Solar/Wind Helper
0.359
203835AF1-098 GEN
Solar/Wind Helper
1.414
203860AG1-193 C
Solar/Wind Helper
0.16
241966AE1-183 GEN
Solar/Wind Helper
0.139
254303AC2-168 GEN
Solar/Wind Helper
0.081
203954AE2-126 C
Solar/Wind Helper
0.234
23929302BS-PKR
50/50
2.523
241832AE2-181_GEN
Solar/Wind Harmer
0.004
958321AF2-126 GEN
Solar/Wind Harmer
1.267
23906502RICHG2&3
Adder
1.422
270575GUS2 35KV
Solar/Wind Harmer
5.343
270541AE2-072 C
Solar/Wind Harmer
0.009
970217AG2-149 GEN
Solar/Wind Harmer
4.562
270404AC1-167 GEN
Solar/Wind Harmer
0.002
270588AE1-091_GEN
Solar/Wind Harmer
3.735
270258AD1-119 GEN
Solar/Wind Harmer
0.001
247604X1-042
Adder
0.266
24441205WTRV SLR C
Solar/Wind Harmer
0
270491AE1-102 GEN2
Solar/Wind Harmer
0.564
945111AF1-176 GEN
Solar/Wind Harmer
3.313
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.026
24642205MAYFLWER
Adder
0.362
970031AG2-029 GEN
Solar/Wind Harmer
2.571
247643Z2-116 C
Solar/Wind Harmer
0
270485AE1-090_GEN
Solar/Wind Harmer
0.001
959331AF2-224 GEN
Solar/Wind Harmer
2.726
965021AG1-366 GEN
Solar/Wind Harmer
1.298
270377AD1-106 GEN
Solar/Wind Harmer
1.42
270043AE2-236 GEN
Solar/Wind Harmer
2.353
270391AF1-285 GEN3
Solar/Wind Harmer
0.242
970349AG2-230 GEN
Solar/Wind Harmer
5.434
270535AF1-215 GEN1
Solar/Wind Harmer
0.004
274752CRETE EC ;2U
Adder
4
274753CRETE EC ;3U
Adder
4
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274724RIVER EC ;11
Adder
8.529
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
274802UNIV PARK;5U
Adder
2.765
274826FISK ;BP
Adder
5.184
274800UNIV PARK;3U
Adder
2.756
972038AH1-567 GEN2
Adder
0.173
276806AD2-047 C O1
Solar/Wind Harmer
1.866
970941AG2-585 GEN
Solar/Wind Harmer
4.117
274772LINCOLN ;3U
Adder
3.982
972228AH1-698 GEN2
Adder
1.743
274676JOLIET 29;8U
Adder
13.851
971617AH1-308 GEN
Solar/Wind Harmer
2.722
276897AD1-100 C
Solar/Wind Harmer
0.004
939351AE1-166 GEN
Solar/Wind Harmer
0
276893AG1-478 C
Solar/Wind Harmer
0.129
274729ELWOOD EC;1P
Adder
7.682
274730ELWOOD EC;6P
Adder
7.682
274734ELWOOD EC;8P
Adder
7.682
274736ELWOOD EC;9P
Adder
7.682
970707AG2-453 GEN
Solar/Wind Harmer
10.65
970513AG2-328 GEN
Solar/Wind Harmer
1.409
970517AG2-330 GEN
Solar/Wind Harmer
8.456
943121AE2-341 GEN
Solar/Wind Harmer
5.404
943591AF1-030 GEN
Solar/Wind Harmer
3.594
276694AA1-018 GEN2
Solar/Wind Harmer
0
944531AF1-118 GEN
Solar/Wind Harmer
14.389
274682WAUKEGAN ;7U
Adder
8.249
276805AD2-038 GEN
Solar/Wind Harmer
0.001
24755605MDL-5G
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.176
274872LEEDK;1U
Solar/Wind Harmer
0.116
276889AE2-281 GEN
Solar/Wind Harmer
0
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.336
274855GSG-6 ;RU
Solar/Wind Harmer
0.116
274850MENDOTA H;RU
Solar/Wind Harmer
0.037
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.057
959091AF2-200 GEN
Solar/Wind Harmer
6.279
970571AG2-364 GEN
Solar/Wind Harmer
6.257
972236AH1-702 GEN2
Adder
0.983
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
4.129
276157O29GEN1
Solar/Wind Harmer
0.497
274878BISHOP HL;2U
Solar/Wind Harmer
0.103
942111AE2-223 GEN
Solar/Wind Harmer
0.993
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
4.58
274853TWINGROVE;U1
Solar/Wind Harmer
0.001
965091AG1-374 GEN
Solar/Wind Harmer
9.061
959611AF2-252 GEN
Solar/Wind Harmer
1.007
965931AG1-462 GEN
Solar/Wind Harmer
7.661
247642Z2-115 C
Solar/Wind Harmer
0.001
962511AG1-100 GEN
Solar/Wind Helper
0.367
203830AF1-094 GEN
Solar/Wind Helper
0.347
959441AF2-235 GEN
Solar/Wind Helper
0.158
254305AE2-115 C
Solar/Wind Helper
0.12
20334926Z1-069 C
Solar/Wind Helper
0.691
203854AF2-039 C
Solar/Wind Helper
0.15
23867002DVBSG1
50/50
12.822
972211AH1-690 GEN
50/50
288.807
23888502TROY G1
50/50
1.836
23888602TROY G2
50/50
1.836
23860102FRMENG 1
50/50
1.733
23860202FRMENG 2
50/50
1.733
24191202EL_AA1-006
50/50
0.334
241886AC2-103 GEN2
Solar/Wind Harmer
-0.001
970817AG2-515 GEN
Solar/Wind Harmer
10.986
945411AF1-206 GEN
Solar/Wind Harmer
-0.001
270499AE1-146 GEN
Solar/Wind Harmer
0.033
945641AF1-229 GEN
Solar/Wind Harmer
0.001
270297AD1-101 GEN
Solar/Wind Harmer
0.001
971549AH1-272 GEN
Solar/Wind Harmer
10.515
971989AH1-539 GEN
Solar/Wind Harmer
1.989
247607V1-011 GEN
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.55
971619AH1-309 GEN
Solar/Wind Harmer
1.837
965041AG1-368 GEN
Solar/Wind Harmer
4.077
965051AG1-369 GEN
Solar/Wind Harmer
2.027
270302AB2-170 GEN
Solar/Wind Harmer
0.002
270317AD1-130_GEN
Solar/Wind Harmer
0.006
971653AH1-327 GEN
Solar/Wind Harmer
0.55
971771AH1-392 GEN
Solar/Wind Harmer
3.877
971567AH1-282 GEN
Solar/Wind Harmer
5.76
971769AH1-391 GEN
Solar/Wind Harmer
4.221
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
270578AF1-285 GEN2
Solar/Wind Harmer
0.242
971347AH1-153 GEN
Solar/Wind Harmer
5.434
963791AG1-232 GEN
Solar/Wind Harmer
4.874
270536AF1-215 GEN2
Solar/Wind Harmer
0.004
270071AF1-092 GEN
Solar/Wind Harmer
6.537
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274814UNIV PK N;0U
Adder
2.422
274807UNIV PK N;3U
Adder
2.417
274805UNIV PK N;1U
Adder
2.407
274811UNIV PK N;7U
Adder
2.401
972037AH1-567 GEN1
Adder
0.087
274827FISK ;RP
Adder
3.674
971611AH1-305 GEN
Solar/Wind Harmer
1.961
960591AF2-350 GEN
Solar/Wind Harmer
3.293
274775LINCOLN ;6U
Adder
3.982
274776LINCOLN ;7U
Adder
3.982
274777LINCOLN ;8U
Adder
3.982
972227AH1-698 GEN1
Adder
1.228
274687WILL CNTY;4U
Adder
13.109
274687WILL CNTY;4U
Adder
13.109
270024AE2-089 GEN
Solar/Wind Harmer
0.004
274675JOLIET 29;7U
Adder
14.364
274675JOLIET 29;7U
Adder
13.851
274731ELWOOD EC;2P
Adder
7.682
274733ELWOOD EC;3P
Adder
7.682
274735ELWOOD EC;4P
Adder
7.682
274728ELWOOD EC;5P
Adder
7.682
970833AG2-524 GEN
Solar/Wind Harmer
3.569
970833AG2-524 GEN
Solar/Wind Harmer
2.379
274746AC1-111 G10
Adder
2.583
274744AC1-111 GEN8
Adder
2.583
24729505KEY G4
Adder
2.957
276868AE1-113 GEN
Solar/Wind Harmer
0.638
276882AE2-255 GEN
Solar/Wind Harmer
0.372
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0
270181AB1-006 GEN2
Solar/Wind Harmer
0
971177AH1-047 GEN
Solar/Wind Harmer
1.951
971411AH1-196 GEN
Solar/Wind Harmer
4.733
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
1.229
971171AH1-044 GEN
Solar/Wind Harmer
6.279
274823ROCKFORD ;21
Adder
8.75
970169AG2-114 GEN
Solar/Wind Harmer
3.123
926823AC1-168 GEN
Solar/Wind Harmer
0.531
276612AE2-035 GEN
Solar/Wind Harmer
0.001
971681AH1-341 GEN
Solar/Wind Harmer
5
24386205FR-12G C
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
24387005FR-3G C
Solar/Wind Harmer
0.001
961011AF2-392 GEN
Solar/Wind Harmer
1.808
957751AF2-069 GEN
Solar/Wind Harmer
0.102
965101AG1-375 GEN
Solar/Wind Harmer
3.066
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
276655WTG1_EQ
Solar/Wind Harmer
0.001
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.207
941731AE2-173 GEN
Solar/Wind Harmer
2.545
963841AG1-237 GEN
Solar/Wind Harmer
1.315
971609AH1-304 GEN
Solar/Wind Harmer
0.493
946321AF1-296 GEN
Solar/Wind Harmer
1.689
945581AF1-223 GEN
Solar/Wind Harmer
0
241982AE2-343 S C
Solar/Wind Helper
0.126
254304AE2-114 C
Solar/Wind Helper
0.12
203846AF2-130 C
Solar/Wind Helper
0.266
241997AF1-093 GEN
Solar/Wind Helper
0.139
203804AE2-113_GEN
Solar/Wind Helper
0.928
203855AF2-088 C
Solar/Wind Helper
0.072
991182J1586 G
External Queue
25.292837142944336
990527J1329
External Queue
1.8513455390930176
990142J1224
External Queue
13.53333568572998
991177J1571 G
External Queue
15.714932441711426
LAGNLTFEXP_LAGN->PJM
CLTF
5.122
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.262
TVALTFEXP_TVA->PJM
CLTF
2.326
CPLELTFEXP_CPLE->PJM
CLTF
0.333
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.959
CBM West 1LTFEXP_CBM-W1->PJM
CBM
96.287
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.224
MECLTFEXP_MEC->PJM
CLTF
6.679
SIGELTFEXP_SIGE->PJM
CLTF
0.174
NYPJM->LTFIMP_NY
CLTF
2.164
LGEELTFEXP_LGEE->PJM
CLTF
2.094
WECLTFEXP_WEC->PJM
CLTF
1.712
AG2-052LTFEXP_AG2-052->PJM
LTF
0.11
AH1-155LTFEXP_AH1-155->PJM
LTF
0.165

Details for 02HAYES-02BEAVER 345.0 kV Ckt 1 line l/o ATSI_P1-2_OEC-345-824_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02HAYES-02BEAVER 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_OEC-345-824_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:135.68 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:2548.09
MW Contribution:0.43
Bus #Bus NameTypeMW Contribution
24190002OREGON_ST1
50/50
3.605
24189802OREGON_CT1
50/50
2.735
23888802TROY G4
50/50
1.837
241996AE2-282_GEN
Solar/Wind Harmer
0.006
971677AH1-339 GEN
Solar/Wind Harmer
0.746
970621AG2-405 GEN
Solar/Wind Harmer
0.951
970623AG2-406 GEN
Solar/Wind Harmer
0.857
270007AE1-245 C
Solar/Wind Harmer
0.001
246938BC-WTG3
Solar/Wind Harmer
0.158
246937BC-WTG2
Solar/Wind Harmer
0.176
961051AF2-396 GEN
Solar/Wind Harmer
8.298
24189902OREGON_CT2
50/50
2.68
23856402BAYSG1
50/50
1.434
23888702TROY G3
50/50
1.837
972253AH1-711 GEN
50/50
56.101
23860302FRMENG 3
50/50
3.54
23920202STRYCT
50/50
2.052
241807AE2-176_GEN
Solar/Wind Harmer
0.009
241858AF1-205_GEN
Solar/Wind Harmer
4.136
241808AF1-120 C
Solar/Wind Harmer
0.003
241840AF1-064_GEN
Solar/Wind Harmer
0.004
972301AH1-735 GEN
Adder
7.125
23906402RICHG1
Adder
1.425
23929302BS-PKR
50/50
2.524
241832AE2-181_GEN
Solar/Wind Harmer
0.004
958321AF2-126 GEN
Solar/Wind Harmer
1.268
23906502RICHG2&3
Adder
1.423
270575GUS2 35KV
Solar/Wind Harmer
5.347
270541AE2-072 C
Solar/Wind Harmer
0.009
970217AG2-149 GEN
Solar/Wind Harmer
4.568
270404AC1-167 GEN
Solar/Wind Harmer
0.002
270588AE1-091_GEN
Solar/Wind Harmer
3.741
270258AD1-119 GEN
Solar/Wind Harmer
0.001
247604X1-042
Adder
0.267
24441205WTRV SLR C
Solar/Wind Harmer
0
270491AE1-102 GEN2
Solar/Wind Harmer
0.565
945111AF1-176 GEN
Solar/Wind Harmer
3.319
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.026
24642205MAYFLWER
Adder
0.363
970031AG2-029 GEN
Solar/Wind Harmer
2.575
247643Z2-116 C
Solar/Wind Harmer
0
270485AE1-090_GEN
Solar/Wind Harmer
0.001
959331AF2-224 GEN
Solar/Wind Harmer
2.73
965021AG1-366 GEN
Solar/Wind Harmer
1.3
270377AD1-106 GEN
Solar/Wind Harmer
1.422
270043AE2-236 GEN
Solar/Wind Harmer
2.357
23867002DVBSG1
50/50
12.828
972211AH1-690 GEN
50/50
288.97
23888502TROY G1
50/50
1.837
23888602TROY G2
50/50
1.837
23860102FRMENG 1
50/50
1.734
23860202FRMENG 2
50/50
1.734
24191202EL_AA1-006
50/50
0.334
970817AG2-515 GEN
Solar/Wind Harmer
10.993
945411AF1-206 GEN
Solar/Wind Harmer
-0.001
270499AE1-146 GEN
Solar/Wind Harmer
0.033
945641AF1-229 GEN
Solar/Wind Harmer
0.001
270297AD1-101 GEN
Solar/Wind Harmer
0.001
971549AH1-272 GEN
Solar/Wind Harmer
10.529
971989AH1-539 GEN
Solar/Wind Harmer
1.992
247607V1-011 GEN
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.551
971619AH1-309 GEN
Solar/Wind Harmer
1.84
965041AG1-368 GEN
Solar/Wind Harmer
4.084
965051AG1-369 GEN
Solar/Wind Harmer
2.03
270302AB2-170 GEN
Solar/Wind Harmer
0.002
270317AD1-130_GEN
Solar/Wind Harmer
0.006
971653AH1-327 GEN
Solar/Wind Harmer
0.551
971771AH1-392 GEN
Solar/Wind Harmer
3.884
971567AH1-282 GEN
Solar/Wind Harmer
5.77
971769AH1-391 GEN
Solar/Wind Harmer
4.229
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
270578AF1-285 GEN2
Solar/Wind Harmer
0.242
971347AH1-153 GEN
Solar/Wind Harmer
5.444
963791AG1-232 GEN
Solar/Wind Harmer
4.883
270536AF1-215 GEN2
Solar/Wind Harmer
0.004
270071AF1-092 GEN
Solar/Wind Harmer
6.55
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274814UNIV PK N;0U
Adder
2.427
274807UNIV PK N;3U
Adder
2.422
274805UNIV PK N;1U
Adder
2.412
274811UNIV PK N;7U
Adder
2.406
972037AH1-567 GEN1
Adder
0.087
274827FISK ;RP
Adder
3.681
971611AH1-305 GEN
Solar/Wind Harmer
1.965
960591AF2-350 GEN
Solar/Wind Harmer
3.3
274775LINCOLN ;6U
Adder
3.991
274776LINCOLN ;7U
Adder
3.991
274777LINCOLN ;8U
Adder
3.991
972227AH1-698 GEN1
Adder
1.23
274687WILL CNTY;4U
Adder
13.136
274687WILL CNTY;4U
Adder
13.136
270024AE2-089 GEN
Solar/Wind Harmer
0.004
274675JOLIET 29;7U
Adder
14.394
274675JOLIET 29;7U
Adder
13.88
274731ELWOOD EC;2P
Adder
7.698
274733ELWOOD EC;3P
Adder
7.698
274735ELWOOD EC;4P
Adder
7.698
274728ELWOOD EC;5P
Adder
7.698
970833AG2-524 GEN
Solar/Wind Harmer
3.577
970833AG2-524 GEN
Solar/Wind Harmer
2.384
274746AC1-111 G10
Adder
2.589
274744AC1-111 GEN8
Adder
2.589
24729505KEY G4
Adder
2.963
276868AE1-113 GEN
Solar/Wind Harmer
0.639
276882AE2-255 GEN
Solar/Wind Harmer
0.372
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0
270181AB1-006 GEN2
Solar/Wind Harmer
0
971177AH1-047 GEN
Solar/Wind Harmer
1.955
971411AH1-196 GEN
Solar/Wind Harmer
4.743
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
1.232
971171AH1-044 GEN
Solar/Wind Harmer
6.293
274823ROCKFORD ;21
Adder
8.769
970169AG2-114 GEN
Solar/Wind Harmer
3.129
926823AC1-168 GEN
Solar/Wind Harmer
0.532
276612AE2-035 GEN
Solar/Wind Harmer
0.001
971681AH1-341 GEN
Solar/Wind Harmer
5.011
24386205FR-12G C
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
24387005FR-3G C
Solar/Wind Harmer
0.001
961011AF2-392 GEN
Solar/Wind Harmer
1.812
957751AF2-069 GEN
Solar/Wind Harmer
0.102
965101AG1-375 GEN
Solar/Wind Harmer
3.072
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
276655WTG1_EQ
Solar/Wind Harmer
0.001
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.214
941731AE2-173 GEN
Solar/Wind Harmer
2.551
963841AG1-237 GEN
Solar/Wind Harmer
1.318
971609AH1-304 GEN
Solar/Wind Harmer
0.494
946321AF1-296 GEN
Solar/Wind Harmer
1.693
945581AF1-223 GEN
Solar/Wind Harmer
0
241886AC2-103 GEN2
Solar/Wind Helper
4.614
241982AE2-343 S C
Solar/Wind Helper
0.126
254304AE2-114 C
Solar/Wind Helper
0.12
203846AF2-130 C
Solar/Wind Helper
0.265
241997AF1-093 GEN
Solar/Wind Helper
0.139
203804AE2-113_GEN
Solar/Wind Helper
0.926
203855AF2-088 C
Solar/Wind Helper
0.072
961051AF2-396 GEN
Solar/Wind Harmer
5.532
957891AF2-083 GEN
Solar/Wind Harmer
0.001
247620Y3-023
Adder
0.264
270216AD2-079_GEN
Solar/Wind Harmer
0.001
970611AG2-400 GEN
Solar/Wind Harmer
3.901
970627AG2-408 GEN
Solar/Wind Harmer
1.17
270526AF1-158 GEN
Solar/Wind Harmer
0.005
24441505OLIV SLR
Solar/Wind Harmer
0
971231AH1-075 GEN
Solar/Wind Harmer
0.429
965681AG1-436 GEN
Solar/Wind Harmer
4.556
965791AG1-447 GEN
Solar/Wind Harmer
3.341
270224U2-072_GEN2
Solar/Wind Harmer
0
270227U2-072_GEN3
Solar/Wind Harmer
0
270228U2-072_GEN4
Solar/Wind Harmer
0
270231U2-072_GEN5
Solar/Wind Harmer
0
274808UNIV PK N;4U
Adder
2.396
274803UNIV PARK;6U
Adder
2.771
942221AE2-234 GEN
Solar/Wind Harmer
0.017
274888KELLY CRK;1U
Solar/Wind Harmer
0.194
274887GEN-1.85
Solar/Wind Harmer
0.087
276843GEN-1.7
Solar/Wind Harmer
0.107
958011AF2-095 GEN
Solar/Wind Harmer
4.752
274770LINCOLN ;1U
Adder
3.991
274771LINCOLN ;2U
Adder
3.991
972259AH1-714 GEN
Adder
8.958
274674JOLIET 9 ;6U
Adder
7.21
970321AG2-212 GEN
Solar/Wind Harmer
1.412
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
958481AF2-142 GEN
Solar/Wind Harmer
4.844
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.437
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
971573AH1-285 GEN
Solar/Wind Harmer
0.6
274696ROCKY RD ;4P
Adder
5.24
274695ROCKY RD ;2P
Adder
5.12
274693ROCKY RD ;1P
Adder
5.069
274697ROCKY RD ;3P
Adder
1.391
274683WAUKEGAN ;8U
Adder
9.683
274683WAUKEGAN ;8U
Adder
8.163
958491AF2-143 GEN
Solar/Wind Harmer
4.801
962691AG1-118 GEN
Solar/Wind Harmer
9.569
274879MINONK ;1U
Solar/Wind Harmer
0.134
970921AG2-575 GEN
Solar/Wind Harmer
3.184
970921AG2-575 GEN
Solar/Wind Harmer
1.061
942991AE2-321 GEN
Solar/Wind Harmer
3.541
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
971333AH1-146 GEN
Solar/Wind Harmer
6.319
971335AH1-147 GEN
Solar/Wind Harmer
6.319
971341AH1-150 GEN
Solar/Wind Harmer
6.293
971343AH1-151 GEN
Solar/Wind Harmer
6.293
274856ECOGROVE ;U1
Solar/Wind Harmer
0.074
276611AD2-172 GEN
Solar/Wind Harmer
0.001
938861AE1-114 GEN
Solar/Wind Harmer
1.763
274764LEE CO EC;5U
Adder
4.148
274765LEE CO EC;6U
Adder
4.148
274762LEE CO EC;3U
Adder
4.138
274763LEE CO EC;4U
Adder
4.099
966841AG1-555 GEN
Solar/Wind Harmer
0.351
944541AF1-119 GEN
Solar/Wind Harmer
0.208
276603SUBLETTE C
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
1.819
274851PROVIDENC;RU
Solar/Wind Harmer
0
274849CRESCENT ;1U
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.121
276646AC1-214 GEN2
Solar/Wind Harmer
0.121
276741O09 GEN1
Solar/Wind Harmer
0.11
276708O09 GEN2
Solar/Wind Harmer
0.11
276782AC1-033 GEN
Solar/Wind Harmer
0
270201AC2-176 GEN
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
0.227
253378AE2-206_GEN
Solar/Wind Harmer
0.002
276820AF1-078_GEN
Solar/Wind Harmer
0.001
970329AG2-216 GEN
Solar/Wind Harmer
1.308
960611AF2-352 GEN
Solar/Wind Harmer
1.009
270599AE1-208 GEN
Solar/Wind Harmer
2.772
270031AE2-169
Solar/Wind Harmer
1.663
203947AF1-006 C
Solar/Wind Helper
0.408
203980AG1-197 GEN
Solar/Wind Helper
0.267
203979AG1-198 GEN
Solar/Wind Helper
0.208
241967AE2-285_GEN
Solar/Wind Helper
0.362
241801AE1-079 GEN
Solar/Wind Helper
0.141
241985AE1-237 GEN
Solar/Wind Helper
0.14
962101AG1-054 GEN
Solar/Wind Helper
0.35
946381AF1-302 GEN
Solar/Wind Helper
0.112
238217AF1-153 C O1
Solar/Wind Helper
0.119
20398826ARMNA MT
Solar/Wind Helper
0.704
270391AF1-285 GEN3
Solar/Wind Harmer
0.242
970349AG2-230 GEN
Solar/Wind Harmer
5.444
270535AF1-215 GEN1
Solar/Wind Harmer
0.004
274752CRETE EC ;2U
Adder
4.008
274753CRETE EC ;3U
Adder
4.008
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274724RIVER EC ;11
Adder
8.546
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
274802UNIV PARK;5U
Adder
2.771
274826FISK ;BP
Adder
5.194
274800UNIV PARK;3U
Adder
2.762
972038AH1-567 GEN2
Adder
0.173
276806AD2-047 C O1
Solar/Wind Harmer
1.87
970941AG2-585 GEN
Solar/Wind Harmer
4.125
274772LINCOLN ;3U
Adder
3.991
972228AH1-698 GEN2
Adder
1.747
274676JOLIET 29;8U
Adder
13.879
971617AH1-308 GEN
Solar/Wind Harmer
2.727
276897AD1-100 C
Solar/Wind Harmer
0.004
939351AE1-166 GEN
Solar/Wind Harmer
0
276893AG1-478 C
Solar/Wind Harmer
0.13
970707AG2-453 GEN
Solar/Wind Harmer
10.672
274729ELWOOD EC;1P
Adder
7.698
274730ELWOOD EC;6P
Adder
7.698
274734ELWOOD EC;8P
Adder
7.698
274736ELWOOD EC;9P
Adder
7.698
970513AG2-328 GEN
Solar/Wind Harmer
1.412
970517AG2-330 GEN
Solar/Wind Harmer
8.474
943121AE2-341 GEN
Solar/Wind Harmer
5.415
943591AF1-030 GEN
Solar/Wind Harmer
3.601
276694AA1-018 GEN2
Solar/Wind Harmer
0
944531AF1-118 GEN
Solar/Wind Harmer
14.419
274682WAUKEGAN ;7U
Adder
8.266
276805AD2-038 GEN
Solar/Wind Harmer
0.001
24755605MDL-5G
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.183
274872LEEDK;1U
Solar/Wind Harmer
0.117
276889AE2-281 GEN
Solar/Wind Harmer
0
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.337
274855GSG-6 ;RU
Solar/Wind Harmer
0.116
274850MENDOTA H;RU
Solar/Wind Harmer
0.037
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.057
959091AF2-200 GEN
Solar/Wind Harmer
6.293
970571AG2-364 GEN
Solar/Wind Harmer
6.27
972236AH1-702 GEN2
Adder
0.985
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
4.138
276157O29GEN1
Solar/Wind Harmer
0.498
274878BISHOP HL;2U
Solar/Wind Harmer
0.103
942111AE2-223 GEN
Solar/Wind Harmer
0.995
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
4.59
274853TWINGROVE;U1
Solar/Wind Harmer
0.001
965091AG1-374 GEN
Solar/Wind Harmer
9.081
959611AF2-252 GEN
Solar/Wind Harmer
1.009
965931AG1-462 GEN
Solar/Wind Harmer
7.678
247642Z2-115 C
Solar/Wind Harmer
0.001
962511AG1-100 GEN
Solar/Wind Helper
0.366
203830AF1-094 GEN
Solar/Wind Helper
0.347
959441AF2-235 GEN
Solar/Wind Helper
0.157
254305AE2-115 C
Solar/Wind Helper
0.12
20334926Z1-069 C
Solar/Wind Helper
0.689
203854AF2-039 C
Solar/Wind Helper
0.149
23906502RICHG2&3
Adder
1.423
270361_3
Solar/Wind Harmer
5.347
960841AF2-375 GEN
Solar/Wind Harmer
-0.002
247522W1-056 GEN
Solar/Wind Harmer
0.001
270428AC2-015 C
Solar/Wind Harmer
0.003
970515AG2-329 GEN
Solar/Wind Harmer
13.704
944231AF1-091 GEN
Solar/Wind Harmer
1.301
246936BC-WTG1
Solar/Wind Harmer
0.176
270489AE1-102 GEN1
Solar/Wind Harmer
0.565
965421AG1-410 GEN
Solar/Wind Harmer
12.915
24695305TIMB G C
Solar/Wind Harmer
0.001
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.182
970905AG2-564 GEN
Solar/Wind Harmer
2.27
945111AF1-176 GEN
Solar/Wind Harmer
7.306
270505AE1-170 C O1
Solar/Wind Harmer
4.294
247521TR3_G114
Solar/Wind Harmer
0.148
270246TR4_N_V150
Solar/Wind Harmer
0.026
24639705ELKHART HY
Adder
0.088
270063AE2-323 C
Solar/Wind Harmer
0.003
270462AD2-086
Solar/Wind Harmer
0.008
965011AG1-365 GEN
Solar/Wind Harmer
3.901
270223U2-072_GEN1
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
7.368
270055AF2-134 C O1
Solar/Wind Harmer
0.003
274751CRETE EC ;1U
Adder
4.008
274754CRETE EC ;4U
Adder
4.008
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.39
274723RIVER EC ;12
Adder
8.649
274812UNIV PK N;8U
Adder
2.406
276164X3-005 C
Solar/Wind Harmer
0
274801UNIV PARK;4U
Adder
2.762
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
4.126
276776AD2-060 GEN
Solar/Wind Harmer
0.345
274773LINCOLN ;4U
Adder
3.991
274774LINCOLN ;5U
Adder
3.991
274676JOLIET 29;8U
Adder
14.394
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
7.698
274674JOLIET 9 ;6U
Adder
7.21
970245AG2-165 GEN
Solar/Wind Harmer
1.412
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
2.589
276691AA1-018 GEN1
Solar/Wind Harmer
0.391
274682WAUKEGAN ;7U
Adder
8.266
274828WAUKEGAN ;BP
Adder
5.076
276901AD2-066 C O1
Solar/Wind Harmer
0.003
939401AE1-172 GEN
Solar/Wind Harmer
2.387
962781AG1-127 GEN
Solar/Wind Harmer
3.03
24791305MDL-5G
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0.002
971997AH1-543 GEN
Solar/Wind Harmer
1.665
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
276861AD2-134 GEN
Solar/Wind Harmer
0.057
957471AF2-041 GEN
Solar/Wind Harmer
9.44
959081AF2-199 GEN
Solar/Wind Harmer
3.147
971067AG2-660 GEN
Solar/Wind Harmer
1.049
274822ROCKFORD ;11
Adder
8.833
970569AG2-363 GEN
Solar/Wind Harmer
9.405
972235AH1-702 GEN1
Adder
1.133
970819AG2-516 GEN
Solar/Wind Harmer
3.753
971475AH1-234 GEN
Solar/Wind Harmer
1.515
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
4.138
274766LEE CO EC;7U
Adder
0.44
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.001
965651AG1-433 GEN
Solar/Wind Harmer
0.909
276158O29GEN2
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
1.331
274877BISHOP HL;1U
Solar/Wind Harmer
0.103
276726Z2-087_GEN
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
4.286
274854TWINGROVE;U2
Solar/Wind Harmer
0.001
945371AF1-202 GEN
Solar/Wind Harmer
0
241885AC2-103 GEN1
Solar/Wind Helper
4.614
961971AG1-040 GEN
Solar/Wind Helper
0.358
203835AF1-098 GEN
Solar/Wind Helper
1.412
203860AG1-193 C
Solar/Wind Helper
0.16
241966AE1-183 GEN
Solar/Wind Helper
0.139
254303AC2-168 GEN
Solar/Wind Helper
0.081
203954AE2-126 C
Solar/Wind Helper
0.233
991182J1586 G
External Queue
25.292837142944336
990527J1329
External Queue
1.8513455390930176
990142J1224
External Queue
13.53333568572998
991177J1571 G
External Queue
15.714932441711426
LAGNLTFEXP_LAGN->PJM
CLTF
5.142
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.292
TVALTFEXP_TVA->PJM
CLTF
2.336
CPLELTFEXP_CPLE->PJM
CLTF
0.344
CBM West 2LTFEXP_CBM-W2->PJM
CBM
41.091
CBM West 1LTFEXP_CBM-W1->PJM
CBM
96.429
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.261
MECLTFEXP_MEC->PJM
CLTF
6.695
SIGELTFEXP_SIGE->PJM
CLTF
0.175
NYPJM->LTFIMP_NY
CLTF
2.158
LGEELTFEXP_LGEE->PJM
CLTF
2.101
WECLTFEXP_WEC->PJM
CLTF
1.716
AG2-052LTFEXP_AG2-052->PJM
LTF
0.11
AH1-155LTFEXP_AH1-155->PJM
LTF
0.166

Details for 02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line l/o ATSI_P1-2_TE-345-601_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_TE-345-601_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.99 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:2140.73
MW Contribution:0.41
Bus #Bus NameTypeMW Contribution
23888802TROY G4
50/50
2.643
24190002OREGON_ST1
50/50
2.928
24189802OREGON_CT1
50/50
2.221
241996AE2-282_GEN
Solar/Wind Harmer
0.007
971677AH1-339 GEN
Solar/Wind Harmer
0.714
970621AG2-405 GEN
Solar/Wind Harmer
1.043
970623AG2-406 GEN
Solar/Wind Harmer
0.966
270007AE1-245 C
Solar/Wind Harmer
0.001
246938BC-WTG3
Solar/Wind Harmer
0.178
246937BC-WTG2
Solar/Wind Harmer
0.199
961051AF2-396 GEN
Solar/Wind Harmer
9.419
961051AF2-396 GEN
Solar/Wind Harmer
6.28
957891AF2-083 GEN
Solar/Wind Harmer
0.001
247620Y3-023
Adder
0.301
270216AD2-079_GEN
Solar/Wind Harmer
0.001
970611AG2-400 GEN
Solar/Wind Harmer
4.433
970627AG2-408 GEN
Solar/Wind Harmer
1.33
270526AF1-158 GEN
Solar/Wind Harmer
0.005
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
5.205
965791AG1-447 GEN
Solar/Wind Harmer
3.817
270224U2-072_GEN2
Solar/Wind Harmer
0
270227U2-072_GEN3
Solar/Wind Harmer
0
270228U2-072_GEN4
Solar/Wind Harmer
0
270231U2-072_GEN5
Solar/Wind Harmer
0
274808UNIV PK N;4U
Adder
2.75
274803UNIV PARK;6U
Adder
3.182
942221AE2-234 GEN
Solar/Wind Harmer
0.019
274888KELLY CRK;1U
Solar/Wind Harmer
0.223
274887GEN-1.85
Solar/Wind Harmer
0.1
276843GEN-1.7
Solar/Wind Harmer
0.123
958011AF2-095 GEN
Solar/Wind Harmer
5.459
274770LINCOLN ;1U
Adder
4.584
274771LINCOLN ;2U
Adder
4.584
972259AH1-714 GEN
Adder
10.294
274674JOLIET 9 ;6U
Adder
8.288
970321AG2-212 GEN
Solar/Wind Harmer
1.623
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
958481AF2-142 GEN
Solar/Wind Harmer
5.572
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.503
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
971573AH1-285 GEN
Solar/Wind Harmer
0.69
274695ROCKY RD ;2P
Adder
5.891
274693ROCKY RD ;1P
Adder
5.833
274697ROCKY RD ;3P
Adder
1.6
274696ROCKY RD ;4P
Adder
6.03
274683WAUKEGAN ;8U
Adder
11.144
274683WAUKEGAN ;8U
Adder
9.394
958491AF2-143 GEN
Solar/Wind Harmer
5.526
962691AG1-118 GEN
Solar/Wind Harmer
11.015
23888502TROY G1
50/50
2.643
23888602TROY G2
50/50
2.643
972211AH1-690 GEN
50/50
234.282
23906902RICHG6
50/50
1.04
23906702RICHG4
50/50
1.037
23906802RICHG5
50/50
0.758
970817AG2-515 GEN
Solar/Wind Harmer
14.376
945411AF1-206 GEN
Solar/Wind Harmer
-0.001
945641AF1-229 GEN
Solar/Wind Harmer
0.001
270499AE1-146 GEN
Solar/Wind Harmer
0.032
971549AH1-272 GEN
Solar/Wind Harmer
11.871
270297AD1-101 GEN
Solar/Wind Harmer
0.001
247607V1-011 GEN
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.621
971989AH1-539 GEN
Solar/Wind Harmer
2.024
971619AH1-309 GEN
Solar/Wind Harmer
2.091
965041AG1-368 GEN
Solar/Wind Harmer
4.612
965051AG1-369 GEN
Solar/Wind Harmer
2.289
971771AH1-392 GEN
Solar/Wind Harmer
4.424
270302AB2-170 GEN
Solar/Wind Harmer
0.003
270317AD1-130_GEN
Solar/Wind Harmer
0.006
971653AH1-327 GEN
Solar/Wind Harmer
0.621
971769AH1-391 GEN
Solar/Wind Harmer
4.822
971567AH1-282 GEN
Solar/Wind Harmer
6.357
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971347AH1-153 GEN
Solar/Wind Harmer
6.22
963791AG1-232 GEN
Solar/Wind Harmer
5.569
270578AF1-285 GEN2
Solar/Wind Harmer
0.274
270536AF1-215 GEN2
Solar/Wind Harmer
0.005
270071AF1-092 GEN
Solar/Wind Harmer
7.505
274814UNIV PK N;0U
Adder
2.786
274807UNIV PK N;3U
Adder
2.78
274805UNIV PK N;1U
Adder
2.768
274811UNIV PK N;7U
Adder
2.762
958391AF2-133 GEN
Solar/Wind Harmer
0.001
972037AH1-567 GEN1
Adder
0.1
274827FISK ;RP
Adder
4.228
971611AH1-305 GEN
Solar/Wind Harmer
2.257
960591AF2-350 GEN
Solar/Wind Harmer
3.791
274775LINCOLN ;6U
Adder
4.584
274776LINCOLN ;7U
Adder
4.584
274777LINCOLN ;8U
Adder
4.584
972227AH1-698 GEN1
Adder
1.413
274687WILL CNTY;4U
Adder
15.095
274687WILL CNTY;4U
Adder
15.095
274675JOLIET 29;7U
Adder
16.543
274675JOLIET 29;7U
Adder
15.952
274731ELWOOD EC;2P
Adder
8.848
274733ELWOOD EC;3P
Adder
8.848
274735ELWOOD EC;4P
Adder
8.848
274728ELWOOD EC;5P
Adder
8.849
270024AE2-089 GEN
Solar/Wind Harmer
0.004
970833AG2-524 GEN
Solar/Wind Harmer
4.112
970833AG2-524 GEN
Solar/Wind Harmer
2.741
274746AC1-111 G10
Adder
2.978
274744AC1-111 GEN8
Adder
2.978
276868AE1-113 GEN
Solar/Wind Harmer
0.736
276882AE2-255 GEN
Solar/Wind Harmer
0.429
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
24729505KEY G4
Adder
3.405
971177AH1-047 GEN
Solar/Wind Harmer
2.252
971411AH1-196 GEN
Solar/Wind Harmer
5.463
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
1.419
971171AH1-044 GEN
Solar/Wind Harmer
7.251
274823ROCKFORD ;21
Adder
10.105
926823AC1-168 GEN
Solar/Wind Harmer
0.613
970169AG2-114 GEN
Solar/Wind Harmer
3.606
276612AE2-035 GEN
Solar/Wind Harmer
0.001
971681AH1-341 GEN
Solar/Wind Harmer
5.777
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0
23906502RICHG2&3
50/50
1.747
241832AE2-181_GEN
Solar/Wind Harmer
0.004
958321AF2-126 GEN
Solar/Wind Harmer
1.413
23929302BS-PKR
Adder
1.959
270541AE2-072 C
Solar/Wind Harmer
0.01
270575GUS2 35KV
Solar/Wind Harmer
4.971
970217AG2-149 GEN
Solar/Wind Harmer
5.053
270404AC1-167 GEN
Solar/Wind Harmer
0.002
270258AD1-119 GEN
Solar/Wind Harmer
0.001
247604X1-042
Adder
0.302
270588AE1-091_GEN
Solar/Wind Harmer
3.901
24441205WTRV SLR C
Solar/Wind Harmer
0
270491AE1-102 GEN2
Solar/Wind Harmer
0.637
945111AF1-176 GEN
Solar/Wind Harmer
3.77
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.03
24642205MAYFLWER
Adder
0.413
970031AG2-029 GEN
Solar/Wind Harmer
2.93
247643Z2-116 C
Solar/Wind Harmer
0
959331AF2-224 GEN
Solar/Wind Harmer
3.103
965021AG1-366 GEN
Solar/Wind Harmer
1.478
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270043AE2-236 GEN
Solar/Wind Harmer
2.692
970349AG2-230 GEN
Solar/Wind Harmer
6.22
270391AF1-285 GEN3
Solar/Wind Harmer
0.274
270535AF1-215 GEN1
Solar/Wind Harmer
0.005
274752CRETE EC ;2U
Adder
4.596
274753CRETE EC ;3U
Adder
4.596
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274724RIVER EC ;11
Adder
9.806
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
274802UNIV PARK;5U
Adder
3.182
274826FISK ;BP
Adder
5.966
274800UNIV PARK;3U
Adder
3.173
972038AH1-567 GEN2
Adder
0.199
276806AD2-047 C O1
Solar/Wind Harmer
2.148
970941AG2-585 GEN
Solar/Wind Harmer
4.739
274772LINCOLN ;3U
Adder
4.584
972228AH1-698 GEN2
Adder
2.007
274676JOLIET 29;8U
Adder
15.952
276897AD1-100 C
Solar/Wind Harmer
0.005
939351AE1-166 GEN
Solar/Wind Harmer
0
276893AG1-478 C
Solar/Wind Harmer
0.149
274729ELWOOD EC;1P
Adder
8.848
274730ELWOOD EC;6P
Adder
8.849
23888702TROY G3
50/50
2.643
972253AH1-711 GEN
50/50
80.741
23920202STRYCT
50/50
2.39
24189902OREGON_CT2
50/50
2.176
972301AH1-735 GEN
50/50
8.755
23906402RICHG1
50/50
1.751
23906502RICHG2&3
50/50
1.747
241858AF1-205_GEN
Solar/Wind Harmer
4.885
241808AF1-120 C
Solar/Wind Harmer
0.004
241840AF1-064_GEN
Solar/Wind Harmer
0.005
270361_3
Solar/Wind Harmer
4.971
960841AF2-375 GEN
Solar/Wind Harmer
-0.002
970515AG2-329 GEN
Solar/Wind Harmer
15.158
944231AF1-091 GEN
Solar/Wind Harmer
1.488
247522W1-056 GEN
Solar/Wind Harmer
0.001
246936BC-WTG1
Solar/Wind Harmer
0.199
270489AE1-102 GEN1
Solar/Wind Harmer
0.637
965421AG1-410 GEN
Solar/Wind Harmer
14.575
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.476
24695305TIMB G C
Solar/Wind Harmer
0.001
945111AF1-176 GEN
Solar/Wind Harmer
8.299
270505AE1-170 C O1
Solar/Wind Harmer
4.878
247521TR3_G114
Solar/Wind Harmer
0.167
270246TR4_N_V150
Solar/Wind Harmer
0.03
24639705ELKHART HY
Adder
0.1
270063AE2-323 C
Solar/Wind Harmer
0.004
965011AG1-365 GEN
Solar/Wind Harmer
4.433
270462AD2-086
Solar/Wind Harmer
0.009
270223U2-072_GEN1
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
8.434
270055AF2-134 C O1
Solar/Wind Harmer
0.003
274751CRETE EC ;1U
Adder
4.596
274754CRETE EC ;4U
Adder
4.596
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
5.035
274723RIVER EC ;12
Adder
9.924
274812UNIV PK N;8U
Adder
2.762
276164X3-005 C
Solar/Wind Harmer
0
274801UNIV PARK;4U
Adder
3.173
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
4.739
276776AD2-060 GEN
Solar/Wind Harmer
0.396
274773LINCOLN ;4U
Adder
4.584
274774LINCOLN ;5U
Adder
4.584
274676JOLIET 29;8U
Adder
16.543
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
8.849
274674JOLIET 9 ;6U
Adder
8.288
970245AG2-165 GEN
Solar/Wind Harmer
1.623
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
2.978
276691AA1-018 GEN1
Solar/Wind Harmer
0.45
274682WAUKEGAN ;7U
Adder
9.512
274828WAUKEGAN ;BP
Adder
5.841
276901AD2-066 C O1
Solar/Wind Harmer
0.004
939401AE1-172 GEN
Solar/Wind Harmer
2.747
962781AG1-127 GEN
Solar/Wind Harmer
3.489
24791305MDL-5G
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0.002
971997AH1-543 GEN
Solar/Wind Harmer
1.918
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
276861AD2-134 GEN
Solar/Wind Harmer
0.065
957471AF2-041 GEN
Solar/Wind Harmer
10.876
959081AF2-199 GEN
Solar/Wind Harmer
3.625
971067AG2-660 GEN
Solar/Wind Harmer
1.208
274822ROCKFORD ;11
Adder
10.179
970569AG2-363 GEN
Solar/Wind Harmer
10.839
972235AH1-702 GEN1
Adder
1.305
970819AG2-516 GEN
Solar/Wind Harmer
4.326
971475AH1-234 GEN
Solar/Wind Harmer
1.747
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
4.772
274766LEE CO EC;7U
Adder
4.716
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.001
965651AG1-433 GEN
Solar/Wind Harmer
1.047
276158O29GEN2
Solar/Wind Harmer
0
274877BISHOP HL;1U
Solar/Wind Harmer
0.119
958861AF2-177 GEN
Solar/Wind Harmer
1.533
276726Z2-087_GEN
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
4.946
274854TWINGROVE;U2
Solar/Wind Harmer
0.001
945371AF1-202 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
8.165
970291AG2-192 GEN
Solar/Wind Harmer
0.448
972175AH1-670 GEN
Solar/Wind Harmer
2.841
247536S-71 GEN
Solar/Wind Harmer
0.138
270032AE2-172
Solar/Wind Harmer
2.283
274880W4-005 GEN4
Solar/Wind Harmer
0
963831AG1-236 GEN
Solar/Wind Harmer
1.315
276903AD2-071 C
Solar/Wind Harmer
3.766
970825AG2-519 GEN
Solar/Wind Harmer
1.195
276615X2-022 GEN
Solar/Wind Harmer
0.035
241885AC2-103 GEN1
Solar/Wind Helper
7.083
241807AE2-176_GEN
Solar/Wind Helper
1.701
961971AG1-040 GEN
Solar/Wind Helper
0.352
203835AF1-098 GEN
Solar/Wind Helper
1.388
203860AG1-193 C
Solar/Wind Helper
0.156
241966AE1-183 GEN
Solar/Wind Helper
0.136
254303AC2-168 GEN
Solar/Wind Helper
0.079
203954AE2-126 C
Solar/Wind Helper
0.223
274879MINONK ;1U
Solar/Wind Harmer
0.155
970921AG2-575 GEN
Solar/Wind Harmer
3.666
970921AG2-575 GEN
Solar/Wind Harmer
1.222
942991AE2-321 GEN
Solar/Wind Harmer
4.078
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
971333AH1-146 GEN
Solar/Wind Harmer
7.279
971335AH1-147 GEN
Solar/Wind Harmer
7.279
971341AH1-150 GEN
Solar/Wind Harmer
7.251
971343AH1-151 GEN
Solar/Wind Harmer
7.251
274856ECOGROVE ;U1
Solar/Wind Harmer
0.085
276611AD2-172 GEN
Solar/Wind Harmer
0.001
971231AH1-075 GEN
Solar/Wind Harmer
0.412
938861AE1-114 GEN
Solar/Wind Harmer
2.033
274764LEE CO EC;5U
Adder
4.784
274765LEE CO EC;6U
Adder
4.784
274762LEE CO EC;3U
Adder
4.772
274763LEE CO EC;4U
Adder
4.727
966841AG1-555 GEN
Solar/Wind Harmer
0.405
276603SUBLETTE C
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.239
960971AF2-388 GEN
Solar/Wind Harmer
2.094
274851PROVIDENC;RU
Solar/Wind Harmer
0
274849CRESCENT ;1U
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.14
276646AC1-214 GEN2
Solar/Wind Harmer
0.14
276741O09 GEN1
Solar/Wind Harmer
0.127
276708O09 GEN2
Solar/Wind Harmer
0.127
276782AC1-033 GEN
Solar/Wind Harmer
0.001
270201AC2-176 GEN
Solar/Wind Harmer
0.001
960611AF2-352 GEN
Solar/Wind Harmer
1.165
964611AG1-324 GEN
Solar/Wind Harmer
0.262
270599AE1-208 GEN
Solar/Wind Harmer
3.195
270031AE2-169
Solar/Wind Harmer
1.917
970241AG2-163 GEN
Solar/Wind Harmer
2.013
253378AE2-206_GEN
Solar/Wind Harmer
0.002
276820AF1-078_GEN
Solar/Wind Harmer
0.001
970329AG2-216 GEN
Solar/Wind Harmer
1.487
971613AH1-306 GEN
Solar/Wind Harmer
1.644
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
960441AF2-335 GEN
Solar/Wind Harmer
3.372
970825AG2-519 GEN
Solar/Wind Harmer
3.73
970883AG2-550 GEN
Solar/Wind Harmer
3.346
970885AG2-551 GEN
Solar/Wind Harmer
1.115
203947AF1-006 C
Solar/Wind Helper
0.402
203980AG1-197 GEN
Solar/Wind Helper
0.262
203979AG1-198 GEN
Solar/Wind Helper
0.204
241967AE2-285_GEN
Solar/Wind Helper
0.354
241801AE1-079 GEN
Solar/Wind Helper
0.138
241985AE1-237 GEN
Solar/Wind Helper
0.137
962101AG1-054 GEN
Solar/Wind Helper
0.34
946381AF1-302 GEN
Solar/Wind Helper
0.108
238217AF1-153 C O1
Solar/Wind Helper
0.114
274734ELWOOD EC;8P
Adder
8.849
274736ELWOOD EC;9P
Adder
8.849
970707AG2-453 GEN
Solar/Wind Harmer
12.267
971617AH1-308 GEN
Solar/Wind Harmer
3.125
970513AG2-328 GEN
Solar/Wind Harmer
1.623
970517AG2-330 GEN
Solar/Wind Harmer
9.737
943121AE2-341 GEN
Solar/Wind Harmer
6.229
943591AF1-030 GEN
Solar/Wind Harmer
4.142
276694AA1-018 GEN2
Solar/Wind Harmer
0
944531AF1-118 GEN
Solar/Wind Harmer
16.565
274682WAUKEGAN ;7U
Adder
9.512
276805AD2-038 GEN
Solar/Wind Harmer
0.001
24755605MDL-5G
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.663
274872LEEDK;1U
Solar/Wind Harmer
0.134
276889AE2-281 GEN
Solar/Wind Harmer
0
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.388
274855GSG-6 ;RU
Solar/Wind Harmer
0.133
274850MENDOTA H;RU
Solar/Wind Harmer
0.043
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.065
959091AF2-200 GEN
Solar/Wind Harmer
7.251
970571AG2-364 GEN
Solar/Wind Harmer
7.226
972236AH1-702 GEN2
Adder
1.135
270377AD1-106 GEN
Solar/Wind Harmer
1.364
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
4.772
274767LEE CO EC;8U
Adder
0.229
276157O29GEN1
Solar/Wind Harmer
0.575
274878BISHOP HL;2U
Solar/Wind Harmer
0.119
942111AE2-223 GEN
Solar/Wind Harmer
1.148
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
5.278
274853TWINGROVE;U1
Solar/Wind Harmer
0.001
965091AG1-374 GEN
Solar/Wind Harmer
10.488
959611AF2-252 GEN
Solar/Wind Harmer
1.165
965931AG1-462 GEN
Solar/Wind Harmer
8.873
247642Z2-115 C
Solar/Wind Harmer
0.002
970289AG2-191 GEN
Solar/Wind Harmer
0.379
970291AG2-192 GEN
Solar/Wind Harmer
0.345
276686W4-005 GEN3
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
1.563
276668AB2-070 GEN1
Solar/Wind Harmer
0.123
946031AF1-268 GEN
Solar/Wind Harmer
3.219
276621W2-048 GEN
Solar/Wind Harmer
0.169
276838X2-022 GEN2
Solar/Wind Harmer
0.189
962511AG1-100 GEN
Solar/Wind Helper
0.361
203830AF1-094 GEN
Solar/Wind Helper
0.34
959441AF2-235 GEN
Solar/Wind Helper
0.154
254305AE2-115 C
Solar/Wind Helper
0.117
20334926Z1-069 C
Solar/Wind Helper
0.662
958821AF2-173 GEN
Solar/Wind Harmer
1.049
24386605FR-22G C
Solar/Wind Harmer
0
24387005FR-3G C
Solar/Wind Harmer
0.001
961011AF2-392 GEN
Solar/Wind Harmer
2.09
957751AF2-069 GEN
Solar/Wind Harmer
0.117
965101AG1-375 GEN
Solar/Wind Harmer
3.538
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
276655WTG1_EQ
Solar/Wind Harmer
0.001
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.709
941731AE2-173 GEN
Solar/Wind Harmer
2.944
963841AG1-237 GEN
Solar/Wind Harmer
1.521
946321AF1-296 GEN
Solar/Wind Harmer
1.955
971609AH1-304 GEN
Solar/Wind Harmer
0.569
945581AF1-223 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.655
270594AE1-207 GEN
Solar/Wind Harmer
3.835
276785W4-005 GEN1
Solar/Wind Harmer
0
276174W4-005 GEN2
Solar/Wind Harmer
0
276849AB2-070 GEN2
Solar/Wind Harmer
0.123
276848AB2-070 GEN3
Solar/Wind Harmer
0.123
970115AG2-085 GEN
Solar/Wind Harmer
1.349
270543AE2-219 C
Solar/Wind Harmer
0.002
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0
241886AC2-103 GEN2
Solar/Wind Helper
7.083
241982AE2-343 S C
Solar/Wind Helper
0.123
254304AE2-114 C
Solar/Wind Helper
0.117
203846AF2-130 C
Solar/Wind Helper
0.257
241997AF1-093 GEN
Solar/Wind Helper
0.136
203804AE2-113_GEN
Solar/Wind Helper
0.892
991182J1586 G
External Queue
28.404245376586914
990527J1329
External Queue
2.100800037384033
990142J1224
External Queue
15.35684871673584
991177J1571 G
External Queue
18.513126373291016
LAGNLTFEXP_LAGN->PJM
CLTF
6.243
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.59
TVALTFEXP_TVA->PJM
CLTF
2.868
CPLELTFEXP_CPLE->PJM
CLTF
0.787
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.86
CBM West 1LTFEXP_CBM-W1->PJM
CBM
107.191
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.28
MECLTFEXP_MEC->PJM
CLTF
7.783
SIGELTFEXP_SIGE->PJM
CLTF
0.206
NYPJM->LTFIMP_NY
CLTF
2.006
LGEELTFEXP_LGEE->PJM
CLTF
2.487
WECLTFEXP_WEC->PJM
CLTF
1.978
AG2-052LTFEXP_AG2-052->PJM
LTF
0.127
AH1-155LTFEXP_AH1-155->PJM
LTF
0.19

Details for 05BOKESCRK-05MARYSV 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05BOKESCRK-05MARYSV 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7445_05MARYSV 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.99 %
Rating:1302.0 MVA
Rating Type:B
MVA to Mitigate:1536.23
MW Contribution:0.35
Bus #Bus NameTypeMW Contribution
24727005RPMNG1
50/50
0.947
270223U2-072_GEN1
Solar/Wind Harmer
8.675
270578AF1-285 GEN2
Solar/Wind Harmer
5.305
270391AF1-285 GEN3
Solar/Wind Harmer
5.305
270462AD2-086
Solar/Wind Harmer
26.506
246936BC-WTG1
Solar/Wind Harmer
4.395
270489AE1-102 GEN1
Solar/Wind Harmer
1.46
965421AG1-410 GEN
Solar/Wind Harmer
32.457
247522W1-056 GEN
Solar/Wind Harmer
1.843
960841AF2-375 GEN
Solar/Wind Harmer
3.015
24695305TIMB G C
Solar/Wind Harmer
4.219
270361_3
Solar/Wind Harmer
6.463
965431AG1-411 GEN
50/50
12.58
24727105RPMNG2
50/50
0.95
942871AE2-306 GEN
Solar/Wind Harmer
3.979
270391AF1-285 GEN3
Solar/Wind Harmer
2.041
270485AE1-090_GEN
Solar/Wind Harmer
2.304
270491AE1-102 GEN2
Solar/Wind Harmer
1.46
270466AD2-091
50/50
22.116
270224U2-072_GEN2
Solar/Wind Harmer
8.675
270227U2-072_GEN3
Solar/Wind Harmer
8.675
270228U2-072_GEN4
Solar/Wind Harmer
8.675
270231U2-072_GEN5
Solar/Wind Harmer
8.675
246938BC-WTG3
Solar/Wind Harmer
4.471
246937BC-WTG2
Solar/Wind Harmer
4.395
270007AE1-245 C
Solar/Wind Harmer
4.993
942801AE2-298 GEN
Solar/Wind Harmer
1.179
970611AG2-400 GEN
Solar/Wind Harmer
6.922
971677AH1-339 GEN
Solar/Wind Harmer
5.222
241996AE2-282_GEN
Solar/Wind Harmer
0.963
247620Y3-023
Adder
0.211
971231AH1-075 GEN
Solar/Wind Harmer
0.352
942221AE2-234 GEN
Solar/Wind Harmer
0.32
270216AD2-079_GEN
Solar/Wind Harmer
0.262
270471AD2-092_GEN
Solar/Wind Helper
1.798
946101AF1-275 GEN
Solar/Wind Helper
0.318
270036AE2-216 BAT
50/50
24.327
24727205RPMNG3
50/50
0.942
270284AF1-227 GEN1
Solar/Wind Harmer
35.4
270286AF1-227 GEN2
Solar/Wind Harmer
13.096
270287AF1-227 GEN3
Solar/Wind Harmer
13.096
270578AF1-285 GEN2
Solar/Wind Harmer
2.041
270302AB2-170 GEN
Solar/Wind Harmer
31.863
270317AD1-130_GEN
Solar/Wind Harmer
12.215
957201AF2-014 GEN
Solar/Wind Harmer
5.094
270435AC2-044 GEN
Solar/Wind Harmer
2.246
270297AD1-101 GEN
Solar/Wind Harmer
2.352
247607V1-011 GEN
Solar/Wind Harmer
3.327
966831AG1-554 GEN
Solar/Wind Harmer
0.997
971989AH1-539 GEN
Solar/Wind Harmer
10.779
270499AE1-146 GEN
Solar/Wind Harmer
2.04
965051AG1-369 GEN
Solar/Wind Harmer
3.576
965041AG1-368 GEN
Solar/Wind Harmer
7.155
945411AF1-206 GEN
Solar/Wind Harmer
3.599
970817AG2-515 GEN
Solar/Wind Harmer
5.709
972211AH1-690 GEN
Adder
87.557
963791AG1-232 GEN
Solar/Wind Harmer
7.374
945641AF1-229 GEN
Solar/Wind Harmer
1.909
270071AF1-092 GEN
Solar/Wind Harmer
6.82
971549AH1-272 GEN
Solar/Wind Harmer
8.28
270024AE2-089 GEN
Solar/Wind Harmer
2.024
270520AE2-214 GEN
Solar/Wind Helper
2.538
270054AF2-122 C O1
Solar/Wind Helper
0.659
247521TR3_G114
Solar/Wind Harmer
2.408
270246TR4_N_V150
Solar/Wind Harmer
0.609
965011AG1-365 GEN
Solar/Wind Harmer
6.922
23906502RICHG2&3
Adder
0.822
972301AH1-735 GEN
Adder
4.089
23906402RICHG1
Adder
0.818
241840AF1-064_GEN
Solar/Wind Harmer
0.752
23920202STRYCT
Adder
0.86
944231AF1-091 GEN
Solar/Wind Harmer
2.303
241808AF1-120 C
Solar/Wind Harmer
0.537
241858AF1-205_GEN
Solar/Wind Harmer
2.383
972253AH1-711 GEN
Adder
18.549
270063AE2-323 C
Solar/Wind Harmer
1.091
24639705ELKHART HY
Adder
0.068
945111AF1-176 GEN
Solar/Wind Harmer
7.706
270349AD2-093_GEN
Solar/Wind Helper
1.798
270588AE1-091_GEN
Solar/Wind Harmer
10.946
270541AE2-072 C
Solar/Wind Harmer
3.904
958091AF2-103 GEN
Solar/Wind Harmer
0.136
270575GUS2 35KV
Solar/Wind Harmer
7.614
270258AD1-119 GEN
Solar/Wind Harmer
2.055
270044AE2-322 C
Solar/Wind Harmer
0.958
270404AC1-167 GEN
Solar/Wind Harmer
0.797
270191TR4_S_V150
Solar/Wind Harmer
2.148
270247TR4_N_V136
Solar/Wind Harmer
0.609
959331AF2-224 GEN
Solar/Wind Harmer
6.922
965021AG1-366 GEN
Solar/Wind Harmer
1.61
23906502RICHG2&3
Adder
0.822
958321AF2-126 GEN
Solar/Wind Harmer
0.806
241832AE2-181_GEN
Solar/Wind Harmer
0.902
23929302BS-PKR
Adder
0.782
970031AG2-029 GEN
Solar/Wind Harmer
15.427
270043AE2-236 GEN
Solar/Wind Harmer
2.738
270377AD1-106 GEN
Solar/Wind Harmer
2.718
945111AF1-176 GEN
Solar/Wind Harmer
2.442
247643Z2-116 C
Solar/Wind Harmer
0.03
971617AH1-308 GEN
Solar/Wind Harmer
2.507
LAGNLTFEXP_LAGN->PJM
CLTF
2.114
TVALTFEXP_TVA->PJM
CLTF
0.753
CBM West 2LTFEXP_CBM-W2->PJM
CBM
20.723
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.177
CBM West 1LTFEXP_CBM-W1->PJM
CBM
51.204
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.052
MECLTFEXP_MEC->PJM
CLTF
4.384
SIGELTFEXP_SIGE->PJM
CLTF
0.085
NYPJM->LTFIMP_NY
CLTF
0.798
LGEELTFEXP_LGEE->PJM
CLTF
0.744
WECLTFEXP_WEC->PJM
CLTF
1.222
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.369
AG2-052LTFEXP_AG2-052->PJM
LTF
0.08
AH1-155LTFEXP_AH1-155->PJM
LTF
0.12

Details for 05BOKESCRK-05MARYSV 345.0 kV Ckt 1 line l/o AEP_P4_#7441_05SORENS 765_J1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05BOKESCRK-05MARYSV 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7441_05SORENS 765_J1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.86 %
Rating:1302.0 MVA
Rating Type:B
MVA to Mitigate:1443.45
MW Contribution:0.4
Bus #Bus NameTypeMW Contribution
270036AE2-216 BAT
50/50
24.946
24727205RPMNG3
50/50
0.982
270284AF1-227 GEN1
Solar/Wind Harmer
36.123
270286AF1-227 GEN2
Solar/Wind Harmer
13.364
270287AF1-227 GEN3
Solar/Wind Harmer
13.364
270578AF1-285 GEN2
Solar/Wind Harmer
2.089
270302AB2-170 GEN
Solar/Wind Harmer
32.674
270317AD1-130_GEN
Solar/Wind Harmer
12.526
957201AF2-014 GEN
Solar/Wind Harmer
5.307
270435AC2-044 GEN
Solar/Wind Harmer
2.34
966831AG1-554 GEN
Solar/Wind Harmer
1.072
971989AH1-539 GEN
Solar/Wind Harmer
11.594
270297AD1-101 GEN
Solar/Wind Harmer
2.489
247607V1-011 GEN
Solar/Wind Harmer
3.496
270499AE1-146 GEN
Solar/Wind Harmer
2.176
965051AG1-369 GEN
Solar/Wind Harmer
3.76
965041AG1-368 GEN
Solar/Wind Harmer
7.49
945411AF1-206 GEN
Solar/Wind Harmer
3.846
970817AG2-515 GEN
Solar/Wind Harmer
6.123
972211AH1-690 GEN
Adder
94.166
945641AF1-229 GEN
Solar/Wind Harmer
2.109
963791AG1-232 GEN
Solar/Wind Harmer
7.721
270071AF1-092 GEN
Solar/Wind Harmer
7.086
971549AH1-272 GEN
Solar/Wind Harmer
8.654
270024AE2-089 GEN
Solar/Wind Harmer
2.13
944161AF1-084 GEN
Solar/Wind Harmer
0.983
971771AH1-392 GEN
Solar/Wind Harmer
3.88
24727005RPMNG1
50/50
0.986
270223U2-072_GEN1
Solar/Wind Harmer
8.881
270578AF1-285 GEN2
Solar/Wind Harmer
5.431
270391AF1-285 GEN3
Solar/Wind Harmer
5.431
270462AD2-086
Solar/Wind Harmer
27.18
246936BC-WTG1
Solar/Wind Harmer
4.579
270489AE1-102 GEN1
Solar/Wind Harmer
1.521
965421AG1-410 GEN
Solar/Wind Harmer
33.814
247522W1-056 GEN
Solar/Wind Harmer
1.977
960841AF2-375 GEN
Solar/Wind Harmer
3.224
24695305TIMB G C
Solar/Wind Harmer
4.424
270361_3
Solar/Wind Harmer
6.922
247521TR3_G114
Solar/Wind Harmer
2.532
270246TR4_N_V150
Solar/Wind Harmer
0.641
23906502RICHG2&3
Adder
0.873
965011AG1-365 GEN
Solar/Wind Harmer
7.215
965431AG1-411 GEN
50/50
13.106
24727105RPMNG2
50/50
0.99
942871AE2-306 GEN
Solar/Wind Harmer
4.074
270391AF1-285 GEN3
Solar/Wind Harmer
2.089
270485AE1-090_GEN
Solar/Wind Harmer
2.363
270491AE1-102 GEN2
Solar/Wind Harmer
1.521
270588AE1-091_GEN
Solar/Wind Harmer
11.649
270541AE2-072 C
Solar/Wind Harmer
4.133
958091AF2-103 GEN
Solar/Wind Harmer
0.143
270575GUS2 35KV
Solar/Wind Harmer
8.155
270258AD1-119 GEN
Solar/Wind Harmer
2.165
270044AE2-322 C
Solar/Wind Harmer
1.008
270404AC1-167 GEN
Solar/Wind Harmer
0.84
270191TR4_S_V150
Solar/Wind Harmer
2.259
270247TR4_N_V136
Solar/Wind Harmer
0.641
23906502RICHG2&3
Adder
0.873
959331AF2-224 GEN
Solar/Wind Harmer
7.215
965021AG1-366 GEN
Solar/Wind Harmer
1.678
958321AF2-126 GEN
Solar/Wind Harmer
0.86
241832AE2-181_GEN
Solar/Wind Harmer
0.964
23929302BS-PKR
Adder
0.842
970031AG2-029 GEN
Solar/Wind Harmer
16.057
270043AE2-236 GEN
Solar/Wind Harmer
2.85
270377AD1-106 GEN
Solar/Wind Harmer
3.103
971617AH1-308 GEN
Solar/Wind Harmer
2.638
945111AF1-176 GEN
Solar/Wind Harmer
2.538
247643Z2-116 C
Solar/Wind Harmer
0.031
247604X1-042
Adder
0.185
24441205WTRV SLR C
Solar/Wind Harmer
0.06
944531AF1-118 GEN
Solar/Wind Harmer
15.258
24642205MAYFLWER
Adder
0.276
270466AD2-091
50/50
22.679
270224U2-072_GEN2
Solar/Wind Harmer
8.881
270227U2-072_GEN3
Solar/Wind Harmer
8.881
270228U2-072_GEN4
Solar/Wind Harmer
8.881
270231U2-072_GEN5
Solar/Wind Harmer
8.881
246938BC-WTG3
Solar/Wind Harmer
4.658
246937BC-WTG2
Solar/Wind Harmer
4.579
270007AE1-245 C
Solar/Wind Harmer
5.246
942801AE2-298 GEN
Solar/Wind Harmer
1.244
970611AG2-400 GEN
Solar/Wind Harmer
7.215
971677AH1-339 GEN
Solar/Wind Harmer
5.666
241996AE2-282_GEN
Solar/Wind Harmer
1.03
971231AH1-075 GEN
Solar/Wind Harmer
0.402
247620Y3-023
Adder
0.219
942221AE2-234 GEN
Solar/Wind Harmer
0.335
270216AD2-079_GEN
Solar/Wind Harmer
0.272
961051AF2-396 GEN
Solar/Wind Harmer
7.083
961051AF2-396 GEN
Solar/Wind Harmer
3.295
960981AF2-389 GEN
Solar/Wind Harmer
0.67
957891AF2-083 GEN
Solar/Wind Harmer
1.495
270471AD2-092_GEN
Solar/Wind Helper
1.579
972301AH1-735 GEN
Adder
4.34
23906402RICHG1
Adder
0.868
241840AF1-064_GEN
Solar/Wind Harmer
0.802
23920202STRYCT
Adder
0.918
944231AF1-091 GEN
Solar/Wind Harmer
2.414
241808AF1-120 C
Solar/Wind Harmer
0.574
241858AF1-205_GEN
Solar/Wind Harmer
2.55
972253AH1-711 GEN
Adder
19.928
270063AE2-323 C
Solar/Wind Harmer
1.135
24639705ELKHART HY
Adder
0.071
945111AF1-176 GEN
Solar/Wind Harmer
8.008
270449AD2-020 GEN
Solar/Wind Harmer
1.247
943021AE2-325 GEN
Solar/Wind Harmer
1.62
270505AE1-170 C O1
Solar/Wind Harmer
6.636
270428AC2-015 C
Solar/Wind Harmer
2.363
270349AD2-093_GEN
Solar/Wind Helper
1.579
LAGNLTFEXP_LAGN->PJM
CLTF
1.858
TVALTFEXP_TVA->PJM
CLTF
0.593
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CBM West 2LTFEXP_CBM-W2->PJM
CBM
19.885
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.293
CBM West 1LTFEXP_CBM-W1->PJM
CBM
53.067
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.552
MECLTFEXP_MEC->PJM
CLTF
4.428
SIGELTFEXP_SIGE->PJM
CLTF
0.085
NYPJM->LTFIMP_NY
CLTF
0.774
LGEELTFEXP_LGEE->PJM
CLTF
0.737
WECLTFEXP_WEC->PJM
CLTF
1.252
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.545
AG2-052LTFEXP_AG2-052->PJM
LTF
0.082
AH1-155LTFEXP_AH1-155->PJM
LTF
0.124

Details for 05E LIMA-05SW LIM 345.0 kV Ckt 1 line l/o AEP_P4_#6497_05MARYSV 345_J2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05E LIMA-05SW LIM 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#6497_05MARYSV 345_J2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.9 %
Rating:971.0 MVA
Rating Type:B
MVA to Mitigate:1096.25
MW Contribution:0.41
Bus #Bus NameTypeMW Contribution
270466AD2-091
50/50
14.101
270224U2-072_GEN2
Solar/Wind Harmer
4.793
270227U2-072_GEN3
Solar/Wind Harmer
4.793
270228U2-072_GEN4
Solar/Wind Harmer
4.793
270231U2-072_GEN5
Solar/Wind Harmer
4.793
246938BC-WTG3
Solar/Wind Harmer
5.566
246937BC-WTG2
Solar/Wind Harmer
5.471
971677AH1-339 GEN
Solar/Wind Harmer
6.461
270036AE2-216 BAT
50/50
15.511
24727205RPMNG3
50/50
1.104
270302AB2-170 GEN
Solar/Wind Harmer
20.316
270317AD1-130_GEN
Solar/Wind Harmer
7.788
270578AF1-285 GEN2
Solar/Wind Harmer
1.128
270284AF1-227 GEN1
Solar/Wind Harmer
13.691
270286AF1-227 GEN2
Solar/Wind Harmer
5.065
270287AF1-227 GEN3
Solar/Wind Harmer
5.065
957201AF2-014 GEN
Solar/Wind Harmer
6.341
270435AC2-044 GEN
Solar/Wind Harmer
2.796
270499AE1-146 GEN
Solar/Wind Harmer
2.321
966831AG1-554 GEN
Solar/Wind Harmer
0.972
971989AH1-539 GEN
Solar/Wind Harmer
10.515
945641AF1-229 GEN
Solar/Wind Harmer
2.888
972211AH1-690 GEN
Adder
115.56
970817AG2-515 GEN
Solar/Wind Harmer
7.248
945411AF1-206 GEN
Solar/Wind Harmer
4.225
247607V1-011 GEN
Solar/Wind Harmer
2.22
965041AG1-368 GEN
Solar/Wind Harmer
5.14
241886AC2-103 GEN2
Solar/Wind Harmer
3.01
24191202EL_AA1-006
Adder
0.108
253383AE2-342_GEN
Solar/Wind Helper
0.488
241972AD1-140 GEN
Solar/Wind Helper
2.205
24727005RPMNG1
50/50
1.109
270462AD2-086
Solar/Wind Harmer
16.9
270223U2-072_GEN1
Solar/Wind Harmer
4.793
270578AF1-285 GEN2
Solar/Wind Harmer
2.932
270391AF1-285 GEN3
Solar/Wind Harmer
2.932
246936BC-WTG1
Solar/Wind Harmer
5.471
270489AE1-102 GEN1
Solar/Wind Harmer
1.818
965421AG1-410 GEN
Solar/Wind Harmer
39.687
960841AF2-375 GEN
Solar/Wind Harmer
3.561
270361_3
Solar/Wind Harmer
7.855
247522W1-056 GEN
Solar/Wind Harmer
1.881
972253AH1-711 GEN
Adder
24.425
241840AF1-064_GEN
Solar/Wind Harmer
0.826
241858AF1-205_GEN
Solar/Wind Harmer
2.862
23920202STRYCT
Adder
0.981
241808AF1-120 C
Solar/Wind Harmer
0.631
23906502RICHG2&3
Adder
0.842
972301AH1-735 GEN
Adder
4.188
23906402RICHG1
Adder
0.838
965011AG1-365 GEN
Solar/Wind Harmer
6.123
270428AC2-015 C
Solar/Wind Harmer
3.044
241807AE2-176_GEN
Solar/Wind Harmer
2.084
970515AG2-329 GEN
Solar/Wind Harmer
7.906
24695305TIMB G C
Solar/Wind Harmer
2.935
241885AC2-103 GEN1
Solar/Wind Harmer
3.01
970905AG2-564 GEN
Solar/Wind Harmer
2.385
944231AF1-091 GEN
Solar/Wind Harmer
1.77
270349AD2-093_GEN
Solar/Wind Helper
0.767
965431AG1-411 GEN
50/50
15.383
24727105RPMNG2
50/50
1.113
270485AE1-090_GEN
Solar/Wind Harmer
1.469
942871AE2-306 GEN
Solar/Wind Harmer
2.199
270391AF1-285 GEN3
Solar/Wind Harmer
1.128
270491AE1-102 GEN2
Solar/Wind Harmer
1.818
270588AE1-091_GEN
Solar/Wind Harmer
10.17
270575GUS2 35KV
Solar/Wind Harmer
9.254
270541AE2-072 C
Solar/Wind Harmer
3.796
958321AF2-126 GEN
Solar/Wind Harmer
0.886
23929302BS-PKR
Adder
1.019
241832AE2-181_GEN
Solar/Wind Harmer
1.046
23906502RICHG2&3
Adder
0.842
959331AF2-224 GEN
Solar/Wind Harmer
6.123
965021AG1-366 GEN
Solar/Wind Harmer
1.424
958091AF2-103 GEN
Solar/Wind Harmer
0.091
970217AG2-149 GEN
Solar/Wind Harmer
17.433
270377AD1-106 GEN
Solar/Wind Harmer
3.205
270044AE2-322 C
Solar/Wind Harmer
0.58
270404AC1-167 GEN
Solar/Wind Harmer
0.483
241996AE2-282_GEN
Solar/Wind Harmer
1.131
970611AG2-400 GEN
Solar/Wind Harmer
6.123
270007AE1-245 C
Solar/Wind Harmer
3.331
971231AH1-075 GEN
Solar/Wind Harmer
0.415
253378AE2-206_GEN
Solar/Wind Helper
1.724
276820AF1-078_GEN
Solar/Wind Helper
0.805
270471AD2-092_GEN
Solar/Wind Helper
0.767
990527J1329
External Queue
1.068130612373352
990142J1224
External Queue
7.808034420013428
991177J1571 G
External Queue
9.20388412475586
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.855
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.588
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.355
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.026
CBM West 1LTFEXP_CBM-W1->PJM
CBM
31.659
MECLTFEXP_MEC->PJM
CLTF
1.044
NYPJM->LTFIMP_NY
CLTF
0.093
WECLTFEXP_WEC->PJM
CLTF
0.42
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.562

Details for 05E LIMA-05SW LIM 345.0 kV Ckt 1 line l/o AEP_P4_#17564_05BOKESCRK 345_CB2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05E LIMA-05SW LIM 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#17564_05BOKESCRK 345_CB2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.18 %
Rating:971.0 MVA
Rating Type:B
MVA to Mitigate:1021.28
MW Contribution:0.42
Bus #Bus NameTypeMW Contribution
270036AE2-216 BAT
50/50
15.529
24727205RPMNG3
50/50
1.106
270302AB2-170 GEN
Solar/Wind Harmer
20.339
270317AD1-130_GEN
Solar/Wind Harmer
7.797
270578AF1-285 GEN2
Solar/Wind Harmer
1.129
957201AF2-014 GEN
Solar/Wind Harmer
6.354
270435AC2-044 GEN
Solar/Wind Harmer
2.802
270499AE1-146 GEN
Solar/Wind Harmer
2.328
966831AG1-554 GEN
Solar/Wind Harmer
0.976
971989AH1-539 GEN
Solar/Wind Harmer
10.55
945641AF1-229 GEN
Solar/Wind Harmer
2.898
972211AH1-690 GEN
Adder
115.994
970817AG2-515 GEN
Solar/Wind Harmer
7.276
945411AF1-206 GEN
Solar/Wind Harmer
4.242
247607V1-011 GEN
Solar/Wind Harmer
2.231
965041AG1-368 GEN
Solar/Wind Harmer
5.168
241886AC2-103 GEN2
Solar/Wind Harmer
3.026
24191202EL_AA1-006
Adder
0.109
253383AE2-342_GEN
Solar/Wind Helper
0.486
241972AD1-140 GEN
Solar/Wind Helper
2.193
965431AG1-411 GEN
50/50
15.415
24727105RPMNG2
50/50
1.116
270485AE1-090_GEN
Solar/Wind Harmer
1.471
942871AE2-306 GEN
Solar/Wind Harmer
2.201
270391AF1-285 GEN3
Solar/Wind Harmer
1.129
270491AE1-102 GEN2
Solar/Wind Harmer
1.821
270588AE1-091_GEN
Solar/Wind Harmer
10.201
270575GUS2 35KV
Solar/Wind Harmer
9.282
270541AE2-072 C
Solar/Wind Harmer
3.809
958321AF2-126 GEN
Solar/Wind Harmer
0.889
23929302BS-PKR
Adder
1.023
241832AE2-181_GEN
Solar/Wind Harmer
1.05
23906502RICHG2&3
Adder
0.845
959331AF2-224 GEN
Solar/Wind Harmer
6.15
965021AG1-366 GEN
Solar/Wind Harmer
1.43
958091AF2-103 GEN
Solar/Wind Harmer
0.091
970217AG2-149 GEN
Solar/Wind Harmer
17.522
270377AD1-106 GEN
Solar/Wind Harmer
3.222
270044AE2-322 C
Solar/Wind Harmer
0.583
270404AC1-167 GEN
Solar/Wind Harmer
0.486
270466AD2-091
50/50
14.117
270224U2-072_GEN2
Solar/Wind Harmer
4.799
270227U2-072_GEN3
Solar/Wind Harmer
4.799
270228U2-072_GEN4
Solar/Wind Harmer
4.799
270231U2-072_GEN5
Solar/Wind Harmer
4.799
246938BC-WTG3
Solar/Wind Harmer
5.577
246937BC-WTG2
Solar/Wind Harmer
5.482
971677AH1-339 GEN
Solar/Wind Harmer
6.484
241996AE2-282_GEN
Solar/Wind Harmer
1.136
970611AG2-400 GEN
Solar/Wind Harmer
6.15
270007AE1-245 C
Solar/Wind Harmer
3.347
971231AH1-075 GEN
Solar/Wind Harmer
0.417
253378AE2-206_GEN
Solar/Wind Helper
1.721
276820AF1-078_GEN
Solar/Wind Helper
0.804
270471AD2-092_GEN
Solar/Wind Helper
0.763
24727005RPMNG1
50/50
1.112
270462AD2-086
Solar/Wind Harmer
16.919
270223U2-072_GEN1
Solar/Wind Harmer
4.799
270578AF1-285 GEN2
Solar/Wind Harmer
2.935
270391AF1-285 GEN3
Solar/Wind Harmer
2.935
246936BC-WTG1
Solar/Wind Harmer
5.482
270489AE1-102 GEN1
Solar/Wind Harmer
1.821
965421AG1-410 GEN
Solar/Wind Harmer
39.77
960841AF2-375 GEN
Solar/Wind Harmer
3.572
270361_3
Solar/Wind Harmer
7.879
247522W1-056 GEN
Solar/Wind Harmer
1.887
972253AH1-711 GEN
Adder
24.514
241840AF1-064_GEN
Solar/Wind Harmer
0.829
241858AF1-205_GEN
Solar/Wind Harmer
2.873
23920202STRYCT
Adder
0.985
241808AF1-120 C
Solar/Wind Harmer
0.633
23906502RICHG2&3
Adder
0.845
972301AH1-735 GEN
Adder
4.205
23906402RICHG1
Adder
0.841
965011AG1-365 GEN
Solar/Wind Harmer
6.15
270428AC2-015 C
Solar/Wind Harmer
3.059
241807AE2-176_GEN
Solar/Wind Harmer
2.095
970515AG2-329 GEN
Solar/Wind Harmer
7.946
24695305TIMB G C
Solar/Wind Harmer
2.95
241885AC2-103 GEN1
Solar/Wind Harmer
3.026
970905AG2-564 GEN
Solar/Wind Harmer
2.399
944231AF1-091 GEN
Solar/Wind Harmer
1.78
270349AD2-093_GEN
Solar/Wind Helper
0.763
990527J1329
External Queue
1.068130612373352
990142J1224
External Queue
7.808034420013428
991177J1571 G
External Queue
9.20388412475586
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.837
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.533
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.344
CBM West 1LTFEXP_CBM-W1->PJM
CBM
32.062
MECLTFEXP_MEC->PJM
CLTF
1.09
NYPJM->LTFIMP_NY
CLTF
0.075
WECLTFEXP_WEC->PJM
CLTF
0.43
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.544

Details for 05E LIMA-05SW LIM 345.0 kV Ckt 1 line l/o AEP_P4_#16659_05GUNN RD SW 345_M2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05E LIMA-05SW LIM 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#16659_05GUNN RD SW 345_M2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.18 %
Rating:971.0 MVA
Rating Type:B
MVA to Mitigate:1011.61
MW Contribution:0.42
Bus #Bus NameTypeMW Contribution
965431AG1-411 GEN
50/50
15.422
24727105RPMNG2
50/50
1.116
270485AE1-090_GEN
Solar/Wind Harmer
1.471
942871AE2-306 GEN
Solar/Wind Harmer
2.202
270391AF1-285 GEN3
Solar/Wind Harmer
1.129
270491AE1-102 GEN2
Solar/Wind Harmer
1.822
270588AE1-091_GEN
Solar/Wind Harmer
10.207
270575GUS2 35KV
Solar/Wind Harmer
9.288
270541AE2-072 C
Solar/Wind Harmer
3.811
958321AF2-126 GEN
Solar/Wind Harmer
0.89
23929302BS-PKR
Adder
1.023
241832AE2-181_GEN
Solar/Wind Harmer
1.051
23906502RICHG2&3
Adder
0.846
959331AF2-224 GEN
Solar/Wind Harmer
6.157
965021AG1-366 GEN
Solar/Wind Harmer
1.432
270466AD2-091
50/50
14.121
270224U2-072_GEN2
Solar/Wind Harmer
4.8
270227U2-072_GEN3
Solar/Wind Harmer
4.8
270228U2-072_GEN4
Solar/Wind Harmer
4.8
270231U2-072_GEN5
Solar/Wind Harmer
4.8
246938BC-WTG3
Solar/Wind Harmer
5.579
24727005RPMNG1
50/50
1.112
270462AD2-086
Solar/Wind Harmer
16.924
270223U2-072_GEN1
Solar/Wind Harmer
4.8
270578AF1-285 GEN2
Solar/Wind Harmer
2.936
270391AF1-285 GEN3
Solar/Wind Harmer
2.936
246936BC-WTG1
Solar/Wind Harmer
5.484
270489AE1-102 GEN1
Solar/Wind Harmer
1.822
965421AG1-410 GEN
Solar/Wind Harmer
39.788
960841AF2-375 GEN
Solar/Wind Harmer
3.575
270361_3
Solar/Wind Harmer
7.884
247522W1-056 GEN
Solar/Wind Harmer
1.889
972253AH1-711 GEN
Adder
24.533
241840AF1-064_GEN
Solar/Wind Harmer
0.83
241858AF1-205_GEN
Solar/Wind Harmer
2.875
23920202STRYCT
Adder
0.986
241808AF1-120 C
Solar/Wind Harmer
0.634
23906502RICHG2&3
Adder
0.846
972301AH1-735 GEN
Adder
4.209
23906402RICHG1
Adder
0.842
965011AG1-365 GEN
Solar/Wind Harmer
6.157
270428AC2-015 C
Solar/Wind Harmer
3.063
241807AE2-176_GEN
Solar/Wind Harmer
2.097
970515AG2-329 GEN
Solar/Wind Harmer
7.955
24695305TIMB G C
Solar/Wind Harmer
2.953
241885AC2-103 GEN1
Solar/Wind Harmer
3.03
970905AG2-564 GEN
Solar/Wind Harmer
2.402
944231AF1-091 GEN
Solar/Wind Harmer
1.782
270349AD2-093_GEN
Solar/Wind Helper
0.762
958091AF2-103 GEN
Solar/Wind Harmer
0.091
970217AG2-149 GEN
Solar/Wind Harmer
17.541
270377AD1-106 GEN
Solar/Wind Harmer
3.226
270044AE2-322 C
Solar/Wind Harmer
0.584
270404AC1-167 GEN
Solar/Wind Harmer
0.486
270036AE2-216 BAT
50/50
15.533
24727205RPMNG3
50/50
1.107
270302AB2-170 GEN
Solar/Wind Harmer
20.344
270317AD1-130_GEN
Solar/Wind Harmer
7.799
270578AF1-285 GEN2
Solar/Wind Harmer
1.129
957201AF2-014 GEN
Solar/Wind Harmer
6.357
270435AC2-044 GEN
Solar/Wind Harmer
2.803
270499AE1-146 GEN
Solar/Wind Harmer
2.33
966831AG1-554 GEN
Solar/Wind Harmer
0.976
971989AH1-539 GEN
Solar/Wind Harmer
10.558
945641AF1-229 GEN
Solar/Wind Harmer
2.9
972211AH1-690 GEN
Adder
116.091
970817AG2-515 GEN
Solar/Wind Harmer
7.282
945411AF1-206 GEN
Solar/Wind Harmer
4.246
247607V1-011 GEN
Solar/Wind Harmer
2.233
965041AG1-368 GEN
Solar/Wind Harmer
5.174
241886AC2-103 GEN2
Solar/Wind Harmer
3.03
24191202EL_AA1-006
Adder
0.109
253383AE2-342_GEN
Solar/Wind Helper
0.485
241972AD1-140 GEN
Solar/Wind Helper
2.191
270284AF1-227 GEN1
Solar/Wind Helper
1.184
270286AF1-227 GEN2
Solar/Wind Helper
0.434
270287AF1-227 GEN3
Solar/Wind Helper
0.434
246937BC-WTG2
Solar/Wind Harmer
5.484
971677AH1-339 GEN
Solar/Wind Harmer
6.488
241996AE2-282_GEN
Solar/Wind Harmer
1.137
970611AG2-400 GEN
Solar/Wind Harmer
6.157
270007AE1-245 C
Solar/Wind Harmer
3.351
971231AH1-075 GEN
Solar/Wind Harmer
0.418
253378AE2-206_GEN
Solar/Wind Helper
1.72
276820AF1-078_GEN
Solar/Wind Helper
0.803
270471AD2-092_GEN
Solar/Wind Helper
0.762
990527J1329
External Queue
1.068130612373352
990142J1224
External Queue
7.808034420013428
991177J1571 G
External Queue
9.20388412475586
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.833
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.521
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.341
CBM West 1LTFEXP_CBM-W1->PJM
CBM
32.151
MECLTFEXP_MEC->PJM
CLTF
1.1
NYPJM->LTFIMP_NY
CLTF
0.071
WECLTFEXP_WEC->PJM
CLTF
0.433
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.54

Details for 05E LIMA-05SW LIM 345.0 kV Ckt 1 line l/o AEP_P2-2_#16655_05GUNN RD SW 345_2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05E LIMA-05SW LIM 345.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#16655_05GUNN RD SW 345_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:104.17 %
Rating:971.0 MVA
Rating Type:B
MVA to Mitigate:1011.54
MW Contribution:0.42
Bus #Bus NameTypeMW Contribution
24727005RPMNG1
50/50
1.112
270462AD2-086
Solar/Wind Harmer
16.924
270223U2-072_GEN1
Solar/Wind Harmer
4.8
270578AF1-285 GEN2
Solar/Wind Harmer
2.936
270391AF1-285 GEN3
Solar/Wind Harmer
2.936
246936BC-WTG1
Solar/Wind Harmer
5.484
270489AE1-102 GEN1
Solar/Wind Harmer
1.822
965421AG1-410 GEN
Solar/Wind Harmer
39.788
960841AF2-375 GEN
Solar/Wind Harmer
3.575
270361_3
Solar/Wind Harmer
7.884
247522W1-056 GEN
Solar/Wind Harmer
1.889
972253AH1-711 GEN
Adder
24.533
241840AF1-064_GEN
Solar/Wind Harmer
0.83
241858AF1-205_GEN
Solar/Wind Harmer
2.875
23920202STRYCT
Adder
0.986
241808AF1-120 C
Solar/Wind Harmer
0.634
23906502RICHG2&3
Adder
0.846
972301AH1-735 GEN
Adder
4.209
23906402RICHG1
Adder
0.842
965011AG1-365 GEN
Solar/Wind Harmer
6.157
270428AC2-015 C
Solar/Wind Harmer
3.063
241807AE2-176_GEN
Solar/Wind Harmer
2.097
970515AG2-329 GEN
Solar/Wind Harmer
7.955
24695305TIMB G C
Solar/Wind Harmer
2.953
241885AC2-103 GEN1
Solar/Wind Harmer
3.03
970905AG2-564 GEN
Solar/Wind Harmer
2.402
944231AF1-091 GEN
Solar/Wind Harmer
1.782
270349AD2-093_GEN
Solar/Wind Helper
0.762
965431AG1-411 GEN
50/50
15.422
24727105RPMNG2
50/50
1.116
270485AE1-090_GEN
Solar/Wind Harmer
1.471
270466AD2-091
50/50
14.121
270224U2-072_GEN2
Solar/Wind Harmer
4.8
270227U2-072_GEN3
Solar/Wind Harmer
4.8
270228U2-072_GEN4
Solar/Wind Harmer
4.8
270231U2-072_GEN5
Solar/Wind Harmer
4.8
246938BC-WTG3
Solar/Wind Harmer
5.579
246937BC-WTG2
Solar/Wind Harmer
5.484
971677AH1-339 GEN
Solar/Wind Harmer
6.488
241996AE2-282_GEN
Solar/Wind Harmer
1.137
970611AG2-400 GEN
Solar/Wind Harmer
6.157
270007AE1-245 C
Solar/Wind Harmer
3.351
270036AE2-216 BAT
50/50
15.533
24727205RPMNG3
50/50
1.107
270302AB2-170 GEN
Solar/Wind Harmer
20.344
270317AD1-130_GEN
Solar/Wind Harmer
7.799
270578AF1-285 GEN2
Solar/Wind Harmer
1.129
957201AF2-014 GEN
Solar/Wind Harmer
6.357
270435AC2-044 GEN
Solar/Wind Harmer
2.803
270499AE1-146 GEN
Solar/Wind Harmer
2.33
966831AG1-554 GEN
Solar/Wind Harmer
0.976
971989AH1-539 GEN
Solar/Wind Harmer
10.558
945641AF1-229 GEN
Solar/Wind Harmer
2.9
972211AH1-690 GEN
Adder
116.091
970817AG2-515 GEN
Solar/Wind Harmer
7.282
945411AF1-206 GEN
Solar/Wind Harmer
4.246
247607V1-011 GEN
Solar/Wind Harmer
2.233
965041AG1-368 GEN
Solar/Wind Harmer
5.174
241886AC2-103 GEN2
Solar/Wind Harmer
3.03
24191202EL_AA1-006
Adder
0.109
253383AE2-342_GEN
Solar/Wind Helper
0.485
241972AD1-140 GEN
Solar/Wind Helper
2.191
270284AF1-227 GEN1
Solar/Wind Helper
1.184
270286AF1-227 GEN2
Solar/Wind Helper
0.434
270287AF1-227 GEN3
Solar/Wind Helper
0.434
942871AE2-306 GEN
Solar/Wind Harmer
2.202
270391AF1-285 GEN3
Solar/Wind Harmer
1.129
270491AE1-102 GEN2
Solar/Wind Harmer
1.822
270588AE1-091_GEN
Solar/Wind Harmer
10.207
270575GUS2 35KV
Solar/Wind Harmer
9.288
270541AE2-072 C
Solar/Wind Harmer
3.811
958321AF2-126 GEN
Solar/Wind Harmer
0.89
23929302BS-PKR
Adder
1.023
241832AE2-181_GEN
Solar/Wind Harmer
1.051
23906502RICHG2&3
Adder
0.846
959331AF2-224 GEN
Solar/Wind Harmer
6.157
965021AG1-366 GEN
Solar/Wind Harmer
1.432
958091AF2-103 GEN
Solar/Wind Harmer
0.091
970217AG2-149 GEN
Solar/Wind Harmer
17.541
270377AD1-106 GEN
Solar/Wind Harmer
3.226
270044AE2-322 C
Solar/Wind Harmer
0.584
270404AC1-167 GEN
Solar/Wind Harmer
0.486
971231AH1-075 GEN
Solar/Wind Harmer
0.418
253378AE2-206_GEN
Solar/Wind Helper
1.72
276820AF1-078_GEN
Solar/Wind Helper
0.803
270471AD2-092_GEN
Solar/Wind Helper
0.762
990527J1329
External Queue
1.068130612373352
990142J1224
External Queue
7.808034420013428
991177J1571 G
External Queue
9.20388412475586
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.833
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.521
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.341
CBM West 1LTFEXP_CBM-W1->PJM
CBM
32.151
MECLTFEXP_MEC->PJM
CLTF
1.1
NYPJM->LTFIMP_NY
CLTF
0.071
WECLTFEXP_WEC->PJM
CLTF
0.433
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.54

Details for 05GUNN RD SW-05BOKESCRK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05GUNN RD SW-05BOKESCRK 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7445_05MARYSV 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.83 %
Rating:1301.0 MVA
Rating Type:B
MVA to Mitigate:1324.81
MW Contribution:0.36
Bus #Bus NameTypeMW Contribution
24727005RPMNG1
50/50
0.956
270223U2-072_GEN1
Solar/Wind Harmer
8.695
270578AF1-285 GEN2
Solar/Wind Harmer
5.317
270391AF1-285 GEN3
Solar/Wind Harmer
5.317
270462AD2-086
Solar/Wind Harmer
26.575
246936BC-WTG1
Solar/Wind Harmer
4.434
270489AE1-102 GEN1
Solar/Wind Harmer
1.473
965421AG1-410 GEN
Solar/Wind Harmer
32.755
247522W1-056 GEN
Solar/Wind Harmer
1.866
960841AF2-375 GEN
Solar/Wind Harmer
3.054
24695305TIMB G C
Solar/Wind Harmer
4.274
270361_3
Solar/Wind Harmer
6.549
247521TR3_G114
Solar/Wind Harmer
2.441
270246TR4_N_V150
Solar/Wind Harmer
0.618
965011AG1-365 GEN
Solar/Wind Harmer
7.021
23906502RICHG2&3
Adder
0.834
972301AH1-735 GEN
Adder
4.148
23906402RICHG1
Adder
0.83
241840AF1-064_GEN
Solar/Wind Harmer
0.763
23920202STRYCT
Adder
0.874
944231AF1-091 GEN
Solar/Wind Harmer
2.34
241808AF1-120 C
Solar/Wind Harmer
0.546
241858AF1-205_GEN
Solar/Wind Harmer
2.423
972253AH1-711 GEN
Adder
18.867
270063AE2-323 C
Solar/Wind Harmer
1.113
24639705ELKHART HY
Adder
0.07
945111AF1-176 GEN
Solar/Wind Harmer
7.883
270449AD2-020 GEN
Solar/Wind Harmer
1.227
943021AE2-325 GEN
Solar/Wind Harmer
1.594
270505AE1-170 C O1
Solar/Wind Harmer
6.536
270349AD2-093_GEN
Solar/Wind Helper
1.782
965431AG1-411 GEN
50/50
12.696
24727105RPMNG2
50/50
0.96
942871AE2-306 GEN
Solar/Wind Harmer
3.988
270391AF1-285 GEN3
Solar/Wind Harmer
2.045
270485AE1-090_GEN
Solar/Wind Harmer
2.31
270491AE1-102 GEN2
Solar/Wind Harmer
1.473
270588AE1-091_GEN
Solar/Wind Harmer
11.055
270541AE2-072 C
Solar/Wind Harmer
3.949
958091AF2-103 GEN
Solar/Wind Harmer
0.137
270575GUS2 35KV
Solar/Wind Harmer
7.716
270258AD1-119 GEN
Solar/Wind Harmer
2.083
270044AE2-322 C
Solar/Wind Harmer
0.971
270404AC1-167 GEN
Solar/Wind Harmer
0.808
270191TR4_S_V150
Solar/Wind Harmer
2.178
270247TR4_N_V136
Solar/Wind Harmer
0.618
959331AF2-224 GEN
Solar/Wind Harmer
7.021
965021AG1-366 GEN
Solar/Wind Harmer
1.633
23906502RICHG2&3
Adder
0.834
958321AF2-126 GEN
Solar/Wind Harmer
0.818
241832AE2-181_GEN
Solar/Wind Harmer
0.917
23929302BS-PKR
Adder
0.797
970031AG2-029 GEN
Solar/Wind Harmer
15.724
270043AE2-236 GEN
Solar/Wind Harmer
2.792
270377AD1-106 GEN
Solar/Wind Harmer
2.779
945111AF1-176 GEN
Solar/Wind Harmer
2.498
247643Z2-116 C
Solar/Wind Harmer
0.031
971617AH1-308 GEN
Solar/Wind Harmer
2.565
247604X1-042
Adder
0.182
24441205WTRV SLR C
Solar/Wind Harmer
0.059
270036AE2-216 BAT
50/50
24.391
24727205RPMNG3
50/50
0.952
270578AF1-285 GEN2
Solar/Wind Harmer
2.045
270302AB2-170 GEN
Solar/Wind Harmer
31.946
270317AD1-130_GEN
Solar/Wind Harmer
12.246
957201AF2-014 GEN
Solar/Wind Harmer
5.139
270435AC2-044 GEN
Solar/Wind Harmer
2.266
270297AD1-101 GEN
Solar/Wind Harmer
2.38
247607V1-011 GEN
Solar/Wind Harmer
3.367
966831AG1-554 GEN
Solar/Wind Harmer
1.009
971989AH1-539 GEN
Solar/Wind Harmer
10.907
270499AE1-146 GEN
Solar/Wind Harmer
2.064
965051AG1-369 GEN
Solar/Wind Harmer
3.625
965041AG1-368 GEN
Solar/Wind Harmer
7.254
945411AF1-206 GEN
Solar/Wind Harmer
3.658
970817AG2-515 GEN
Solar/Wind Harmer
5.808
972211AH1-690 GEN
Adder
89.121
963791AG1-232 GEN
Solar/Wind Harmer
7.507
945641AF1-229 GEN
Solar/Wind Harmer
1.945
270071AF1-092 GEN
Solar/Wind Harmer
6.969
971549AH1-272 GEN
Solar/Wind Harmer
8.464
270024AE2-089 GEN
Solar/Wind Harmer
2.07
944161AF1-084 GEN
Solar/Wind Harmer
0.967
270284AF1-227 GEN1
Solar/Wind Helper
5.57
270286AF1-227 GEN2
Solar/Wind Helper
2.043
270287AF1-227 GEN3
Solar/Wind Helper
2.043
270520AE2-214 GEN
Solar/Wind Helper
2.488
270054AF2-122 C O1
Solar/Wind Helper
0.645
270466AD2-091
50/50
22.173
270224U2-072_GEN2
Solar/Wind Harmer
8.695
270227U2-072_GEN3
Solar/Wind Harmer
8.695
270228U2-072_GEN4
Solar/Wind Harmer
8.695
270231U2-072_GEN5
Solar/Wind Harmer
8.695
246938BC-WTG3
Solar/Wind Harmer
4.511
246937BC-WTG2
Solar/Wind Harmer
4.434
270007AE1-245 C
Solar/Wind Harmer
5.052
942801AE2-298 GEN
Solar/Wind Harmer
1.194
970611AG2-400 GEN
Solar/Wind Harmer
7.021
971677AH1-339 GEN
Solar/Wind Harmer
5.301
241996AE2-282_GEN
Solar/Wind Harmer
0.979
247620Y3-023
Adder
0.215
971231AH1-075 GEN
Solar/Wind Harmer
0.36
942221AE2-234 GEN
Solar/Wind Harmer
0.327
270216AD2-079_GEN
Solar/Wind Harmer
0.268
961051AF2-396 GEN
Solar/Wind Harmer
6.972
961051AF2-396 GEN
Solar/Wind Harmer
3.243
960981AF2-389 GEN
Solar/Wind Harmer
0.66
957891AF2-083 GEN
Solar/Wind Harmer
1.473
270471AD2-092_GEN
Solar/Wind Helper
1.782
946101AF1-275 GEN
Solar/Wind Helper
0.312
LAGNLTFEXP_LAGN->PJM
CLTF
2.316
TVALTFEXP_TVA->PJM
CLTF
0.854
CBM West 2LTFEXP_CBM-W2->PJM
CBM
22.063
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.137
CBM West 1LTFEXP_CBM-W1->PJM
CBM
52.655
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.43
MECLTFEXP_MEC->PJM
CLTF
4.551
SIGELTFEXP_SIGE->PJM
CLTF
0.09
NYPJM->LTFIMP_NY
CLTF
0.734
LGEELTFEXP_LGEE->PJM
CLTF
0.812
WECLTFEXP_WEC->PJM
CLTF
1.26
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.302
AG2-052LTFEXP_AG2-052->PJM
LTF
0.082
AH1-155LTFEXP_AH1-155->PJM
LTF
0.124

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P2-3_MP-500-024_SRT-A


Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-024_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:134.01 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5081.52
MW Contribution:0.86
Bus #Bus NameTypeMW Contribution
270119AB2-067 GEN1
50/50
7.1
270120AB2-067 GEN2
50/50
7.1
24318905MLG2
50/50
7.059
270471AD2-092_GEN
Solar/Wind Harmer
4.477
946101AF1-275 GEN
Solar/Wind Harmer
1.818
942861AE2-305 GEN
Solar/Wind Harmer
9.105
970077AG2-063 GEN
Solar/Wind Harmer
6.25
270224U2-072_GEN2
Solar/Wind Harmer
2.287
270227U2-072_GEN3
Solar/Wind Harmer
2.287
270228U2-072_GEN4
Solar/Wind Harmer
2.287
270231U2-072_GEN5
Solar/Wind Harmer
2.287
938701AE1-092 GEN
Solar/Wind Harmer
23.86
964601AG1-323 GEN
Solar/Wind Harmer
3.665
964601AG1-323 GEN
Solar/Wind Harmer
1.705
270518AE2-148 GEN
Solar/Wind Harmer
13.911
253378AE2-206_GEN
Solar/Wind Harmer
4.016
276820AF1-078_GEN
Solar/Wind Harmer
1.784
972159AH1-661 GEN
Adder
1.111
972269AH1-719 GEN
Adder
2.557
25326509SID D
Adder
1.455
971199AH1-059 GEN
Solar/Wind Harmer
4.424
241960AC2-195 GEN
Solar/Wind Harmer
3.074
970879AG2-548 GEN
Solar/Wind Harmer
6.788
971073AG2-665 GEN
Solar/Wind Harmer
6.788
971073AG2-665 GEN
Solar/Wind Harmer
4.736
25326109MON D
Adder
1.447
25322209TAIT E
Adder
10.679
25322209TAIT E
Adder
10.439
253370AE2-315 SEC1
Adder
2.189
971201AH1-060 GEN
Solar/Wind Harmer
2.181
253394AE2-221_GEN
Solar/Wind Harmer
4.93
253398AE2-221_GEN2
Solar/Wind Harmer
4.93
246938BC-WTG3
Solar/Wind Harmer
4.31
246937BC-WTG2
Solar/Wind Harmer
4.237
253317AC1-085 GEN4
Solar/Wind Harmer
9.037
970611AG2-400 GEN
Solar/Wind Harmer
10.775
971231AH1-075 GEN
Solar/Wind Harmer
0.862
270007AE1-245 C
Solar/Wind Harmer
6.374
942801AE2-298 GEN
Solar/Wind Harmer
1.626
962581AG1-107 GEN
Solar/Wind Harmer
5.38
961491AF2-440 GEN
Solar/Wind Harmer
2.236
25183208HLCRTG
Solar/Wind Harmer
6.467
944541AF1-119 GEN
Solar/Wind Harmer
4.468
960971AF2-388 GEN
Solar/Wind Harmer
11.659
942221AE2-234 GEN
Solar/Wind Harmer
0.781
252519AF1-045_GEN
Solar/Wind Harmer
6.466
252516AE2-318_GEN
Solar/Wind Harmer
4.932
247621Y3-024
Adder
0.256
970883AG2-550 GEN
Solar/Wind Harmer
10.634
970885AG2-551 GEN
Solar/Wind Harmer
2.473
270201AC2-176 GEN
Solar/Wind Harmer
5.466
25194408D.CRK1
Adder
8.037
25194508D.CRK3
Adder
1.502
964611AG1-324 GEN
Solar/Wind Harmer
1.252
964611AG1-324 GEN
Solar/Wind Harmer
0.556
252509AD1-136 GEN
Solar/Wind Harmer
0.272
247620Y3-023
Adder
0.486
24728805RICHG1
Adder
3.981
24728905RICHG2
Adder
3.981
274770LINCOLN ;1U
Adder
8.715
274771LINCOLN ;2U
Adder
8.715
274808UNIV PK N;4U
Adder
5.14
274803UNIV PARK;6U
Adder
5.997
972259AH1-714 GEN
Adder
19.596
274674JOLIET 9 ;6U
Adder
15.776
274696ROCKY RD ;4P
Adder
11.59
274695ROCKY RD ;2P
Adder
11.323
274693ROCKY RD ;1P
Adder
11.211
274697ROCKY RD ;3P
Adder
3.076
23585401KL_K28_T16
Solar/Wind Helper
1.493
238120AE2-309 GEN
Solar/Wind Helper
0.528
238175AF1-290_GEN
Solar/Wind Helper
0.153
238169AE2-226 GEN1
Solar/Wind Helper
0.703
238170AE2-226 GEN2
Solar/Wind Helper
0.703
235020AA1-095 C
Solar/Wind Helper
0.053
23777901MDS_W4-102
Solar/Wind Helper
0.177
237002AB1-128_GEN
Solar/Wind Helper
0.445
237034AC2-136 C
Solar/Wind Helper
0.228
235063AE1-101 C2
Solar/Wind Helper
1.665
237001AB1-127_GEN
Solar/Wind Helper
0.443
23777801MSM_W1-116
Solar/Wind Helper
0.115
237025AB1-124 C
Solar/Wind Helper
0.165
237006AB1-125 GEN
Solar/Wind Helper
0.123
226929AD2-058 GEN
Solar/Wind Helper
0.099
205916AD1-020 GEN
Solar/Wind Helper
1.72
20390526W1-045 C
Solar/Wind Helper
0.351
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
233987AB2-037 GEN
Solar/Wind Helper
2.35
233933AB2-153 GEN
Solar/Wind Helper
0.233
232424Y1-079 C
Solar/Wind Helper
0.117
233944AB2-135 GEN
Solar/Wind Helper
0.591
233946AB2-136 GEN
Solar/Wind Helper
0.57
234036AF2-325 C
Solar/Wind Helper
0.042
233901CHERRYDALE C
Solar/Wind Helper
0.233
232408W1-005 C
Solar/Wind Helper
0.509
232410W1-006 C
Solar/Wind Helper
0.509
233939AC1-091 C
Solar/Wind Helper
0.351
233970AC1-092 C
Solar/Wind Helper
0.351
315651AD1-115 GEN
Solar/Wind Helper
0.787
316447AC1-158 HLD
Solar/Wind Helper
2.853
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.04
219921AF1-264
Solar/Wind Helper
0.051
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.083
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.19
20716928W4-060COL
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.016
20673828FLE_V3-070
Solar/Wind Helper
0.091
207442AE1-156 GEN
Solar/Wind Helper
0.327
20676128MHD_W3-029
Solar/Wind Helper
0.096
20671828STAW2-080
Solar/Wind Helper
0.027
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
207471AF2-354 C
Solar/Wind Helper
0.169
20674928WA_W3-044
Solar/Wind Helper
0.099
964851AG1-348 GEN
Solar/Wind Helper
0.081
20676228FRD_X1-012
Solar/Wind Helper
0.092
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.045
211065PSPA IPP
Solar/Wind Helper
0.152
211065PSPA IPP
Solar/Wind Helper
0.152
203955AF1-039 C O1
Solar/Wind Helper
0.33
970321AG2-212 GEN
Solar/Wind Harmer
4.981
962771AG1-126 GEN
Solar/Wind Harmer
41.173
270459AD2-067 GEN
Solar/Wind Harmer
10.252
961821AG1-024 GEN
Solar/Wind Harmer
10.408
270054AF2-122 C O1
Solar/Wind Harmer
3.995
972239AH1-704 GEN
Adder
2.671
270284AF1-227 GEN1
Solar/Wind Harmer
6.806
270286AF1-227 GEN2
Solar/Wind Harmer
2.518
270287AF1-227 GEN3
Solar/Wind Harmer
2.518
270520AE2-214 GEN
Solar/Wind Harmer
7.284
253383AE2-342_GEN
Solar/Wind Harmer
1.047
241973AD2-163_GEN1
Solar/Wind Harmer
2.334
943861AF1-054 GEN
Solar/Wind Harmer
4.494
943851AF1-053 GEN
Solar/Wind Harmer
2.172
945631AF1-228 GEN
Solar/Wind Harmer
5.47
270156DARBY CT1
Adder
10.432
270157DARBY CT2
Adder
10.407
270158DARBY CT3
Adder
10.24
270578AF1-285 GEN2
Solar/Wind Harmer
0.538
970689AG2-444 GEN
Solar/Wind Harmer
18.845
270432AC2-029 GEN
Solar/Wind Harmer
8.059
270302AB2-170 GEN
Solar/Wind Harmer
9.566
270317AD1-130_GEN
Solar/Wind Harmer
3.667
270269AC2-059
Solar/Wind Harmer
10.62
940611AE2-048 GEN
Solar/Wind Harmer
24.866
941391AE2-136 GEN
Solar/Wind Harmer
12.885
241972AD1-140 GEN
Solar/Wind Harmer
5.031
270340AC2-060 GEN
Solar/Wind Harmer
3.353
958581AF2-149 GEN
Solar/Wind Harmer
4.732
970179AG2-119 GEN
Solar/Wind Harmer
8.844
970879AG2-548 GEN
Solar/Wind Harmer
4.736
253372AE2-315 SEC3
Adder
2.071
253372AE2-315 SEC3
Adder
2.071
25306009OHH W.
Adder
3.141
253349AC2-067 GEN
Solar/Wind Harmer
5.421
253400AC2-068 GEN
Solar/Wind Harmer
2.18
957201AF2-014 GEN
Solar/Wind Harmer
4.91
270435AC2-044 GEN
Solar/Wind Harmer
2.165
965051AG1-369 GEN
Solar/Wind Harmer
5.38
965041AG1-368 GEN
Solar/Wind Harmer
10.749
247607V1-011 GEN
Solar/Wind Harmer
4.249
24729505KEY G4
Adder
6.948
963791AG1-232 GEN
Solar/Wind Harmer
14.455
971567AH1-282 GEN
Solar/Wind Harmer
16.053
966831AG1-554 GEN
Solar/Wind Harmer
1.28
971989AH1-539 GEN
Solar/Wind Harmer
13.846
270071AF1-092 GEN
Solar/Wind Harmer
16.048
971985AH1-537 GEN
Solar/Wind Harmer
19.051
958711AF2-162 GEN
Solar/Wind Harmer
1.079
270024AE2-089 GEN
Solar/Wind Harmer
5.004
965101AG1-375 GEN
Solar/Wind Harmer
10.653
270367AC2-061_GEN
Solar/Wind Harmer
3.388
971673AH1-337 GEN
Solar/Wind Harmer
4.893
971029AG2-637 GEN
Solar/Wind Harmer
15.954
252524AE2-267 GEN
Solar/Wind Harmer
1.677
25196408WSDLE3
Adder
9.382
25196308WSDLE2
Adder
9.3
25196208WSDLE1
Adder
9.277
25196708WSDLE6
Adder
9.254
25196508WSDLE4
Adder
9.021
270543AE2-219 C
Solar/Wind Harmer
5.445
961761AG1-017 GEN
Solar/Wind Harmer
0.455
945581AF1-223 GEN
Solar/Wind Harmer
4.819
944031AF1-071 GEN
Solar/Wind Harmer
1.067
270297AD1-101 GEN
Solar/Wind Harmer
2.953
25196108MFTGT2
Adder
1.605
25196108MFTGT2
Adder
1.491
274775LINCOLN ;6U
Adder
8.715
274776LINCOLN ;7U
Adder
8.715
274777LINCOLN ;8U
Adder
8.715
274814UNIV PK N;0U
Adder
5.208
274807UNIV PK N;3U
Adder
5.196
274805UNIV PK N;1U
Adder
5.174
274811UNIV PK N;7U
Adder
5.162
972037AH1-567 GEN1
Adder
0.188
274827FISK ;RP
Adder
7.977
972227AH1-698 GEN1
Adder
2.681
274687WILL CNTY;4U
Adder
28.653
274687WILL CNTY;4U
Adder
28.653
274675JOLIET 29;7U
Adder
31.445
274675JOLIET 29;7U
Adder
30.322
274731ELWOOD EC;2P
Adder
16.844
274733ELWOOD EC;3P
Adder
16.844
274735ELWOOD EC;4P
Adder
16.844
274728ELWOOD EC;5P
Adder
16.844
972203AH1-686 GEN
Adder
2.356
274746AC1-111 G10
Adder
5.705
274744AC1-111 GEN8
Adder
5.705
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238126S14_GEN_1
Solar/Wind Helper
0.832
238152AF2-075_GEN
Solar/Wind Helper
0.709
238208AF1-136 C
Solar/Wind Helper
0.221
23546401DTGZ2-030
Solar/Wind Helper
0.089
237085AD2-009_GEN
Solar/Wind Helper
1.655
3138216PACIFIC
Solar/Wind Helper
0.044
316411AF1-147_GEN1
Solar/Wind Helper
0.891
316415AF1-147_GEN2
Solar/Wind Helper
0.891
23750501ELLIOTTS
Solar/Wind Helper
0.644
959381AF2-229 GEN
Solar/Wind Helper
0.359
3141426STAFORD
Solar/Wind Helper
0.052
960921AF2-383 GEN
Solar/Wind Helper
0.182
205943AE1-185 GEN
Solar/Wind Helper
0.511
205932AD2-116_GEN
Solar/Wind Helper
0.511
205956AE1-196_GEN
Solar/Wind Helper
0.511
233935AB2-179 C
Solar/Wind Helper
1.273
232436AB1-176 C
Solar/Wind Helper
0.045
233923SMA
Solar/Wind Helper
0.962
233990AG1-397 GEN
Solar/Wind Helper
0.031
232432Z2-076 GEN
Solar/Wind Helper
0.067
234033AF1-007_GEN
Solar/Wind Helper
7.046
964001AG1-254 GEN
Solar/Wind Helper
0.959
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.115
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.08
203975AE1-071-GEN
Solar/Wind Helper
2.508
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.291
219620RIDERU C
Solar/Wind Helper
0.001
316164AC1-076 GEN
Solar/Wind Helper
1.099
20675528CPH_W2-050
Solar/Wind Helper
0.087
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
218524CNTRALGAS1 C
Solar/Wind Helper
0.161
966261AG1-495 GEN
Solar/Wind Helper
0.082
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20675928HOL_W4-097
Solar/Wind Helper
0.05
207484AF2-139 C O1
Solar/Wind Helper
0.084
20674828DL_W4-046
Solar/Wind Helper
0.008
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.137
20675128HRM_W1-127
Solar/Wind Helper
0.03
209116AE2-175 GEN
Solar/Wind Helper
1.786
270166AC1-044 GEN3
50/50
7.1
23559101PLEAS2
50/50
6.365
962761AG1-125 GEN
Solar/Wind Harmer
41.173
970149AG2-104 GEN
Solar/Wind Harmer
50.849
970155AG2-107 GEN
Solar/Wind Harmer
17.953
270349AD2-093_GEN
Solar/Wind Harmer
4.477
24721705FLATG2
Adder
24.144
270159DARBY CT4
Adder
10.266
970593AG2-378 GEN
Solar/Wind Harmer
2.315
270223U2-072_GEN1
Solar/Wind Harmer
2.287
270578AF1-285 GEN2
Solar/Wind Harmer
1.399
270391AF1-285 GEN3
Solar/Wind Harmer
1.399
253343AC1-166 GEN
Solar/Wind Harmer
1.243
253325AC1-069 GEN
Solar/Wind Harmer
1.199
270462AD2-086
Solar/Wind Harmer
7.958
971995AH1-542 GEN
Solar/Wind Harmer
12.515
270263AC1-001 GEN
Solar/Wind Harmer
1.179
25326309TAIT D
Adder
1.2
960071AF2-298 GEN
Solar/Wind Harmer
5.454
253370AE2-315 SEC1
Adder
2.189
253371AE2-315 SEC2
Adder
2.071
927014AC1-188 GEN
Solar/Wind Harmer
1.729
241813AF1-122_GEN
Solar/Wind Harmer
6.978
246936BC-WTG1
Solar/Wind Harmer
4.237
270489AE1-102 GEN1
Solar/Wind Harmer
1.407
965421AG1-410 GEN
Solar/Wind Harmer
32.464
960001AF2-291 GEN
Solar/Wind Harmer
3.264
253432AC1-085 GEN2
Solar/Wind Harmer
0.289
946171AF1-282 GEN
Solar/Wind Harmer
10.789
247521TR3_G114
Solar/Wind Harmer
3.623
270246TR4_N_V150
Solar/Wind Harmer
0.916
965011AG1-365 GEN
Solar/Wind Harmer
10.775
24695305TIMB G C
Solar/Wind Harmer
5.916
965651AG1-433 GEN
Solar/Wind Harmer
5.83
958861AF2-177 GEN
Solar/Wind Harmer
11.644
247536S-71 GEN
Solar/Wind Harmer
4.305
25194608D.CRK4
Adder
1.747
945371AF1-202 GEN
Solar/Wind Harmer
7.414
252507AC2-088 GEN
Solar/Wind Harmer
1.904
270063AE2-323 C
Solar/Wind Harmer
2.336
25196808ZIMRHP
Adder
80.055
24639705ELKHART HY
Adder
0.162
25196008MFTGT1
Adder
1.456
274751CRETE EC ;1U
Adder
8.515
274754CRETE EC ;4U
Adder
8.515
274773LINCOLN ;4U
Adder
8.715
274774LINCOLN ;5U
Adder
8.715
274723RIVER EC ;12
Adder
18.501
274812UNIV PK N;8U
Adder
5.162
24728605AND G2
Adder
3.945
274801UNIV PARK;4U
Adder
5.993
274676JOLIET 29;8U
Adder
31.445
274732ELWOOD EC;7P
Adder
16.844
274674JOLIET 9 ;6U
Adder
15.776
274745AC1-111 GEN9
Adder
5.705
970091AG2-072 GEN
Adder
78.03
316095T157 G97
Solar/Wind Helper
1.508
23583801GRNGAP
Solar/Wind Helper
5.618
238185AF2-356 C
Solar/Wind Helper
2.662
238108AE1-109 GEN1
Solar/Wind Helper
0.114
235054AD2-180 GEN
Solar/Wind Helper
2.043
235531U2-073 GEN
Solar/Wind Helper
3.301
238117U2-030
Solar/Wind Helper
0.344
238147AE2-230_GEN1
Solar/Wind Helper
0.496
238149AF1-291A_GEN
Solar/Wind Helper
0.142
23751201ROTHROCK
Solar/Wind Helper
0.832
23562501BACKB
Solar/Wind Helper
1.017
237061AD1-155 GEN
Solar/Wind Helper
0.053
238221AF1-254 C O1
Solar/Wind Helper
0.275
235067AD1-061 GEN
Solar/Wind Helper
0.498
23751101LEADS_P59
Solar/Wind Helper
1.424
237030AB1-096 C
Solar/Wind Helper
0.071
3141196NOKESVL
Solar/Wind Helper
1.034
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.347
223402AF1-300 C
Solar/Wind Helper
0.369
205917AD1-020 ES
Solar/Wind Helper
0.37
233918AB1-142 GEN
Solar/Wind Helper
0.504
233982AB2-133 GEN
Solar/Wind Helper
0.359
233994AC2-023 GEN
Solar/Wind Helper
0.965
233996TM1833_GEN
Solar/Wind Helper
0.262
233997TMININ_4.2
Solar/Wind Helper
0.262
232406W1-004 FULL
Solar/Wind Helper
0.509
233940AF2-379 C
Solar/Wind Helper
0.062
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.233
233971AC1-093 C
Solar/Wind Helper
0.359
230430AE1-229_GEN
Solar/Wind Helper
3.385
316044AC1-158 PL1
Solar/Wind Helper
1.296
316450AC1-158 RIC
Solar/Wind Helper
0.346
230415AB2-049 C
Solar/Wind Helper
0.03
228729W2-030 C
Solar/Wind Helper
0.111
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.15
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
219348LDSOLAR C
Solar/Wind Helper
0.115
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.063
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.354
219276PARKLANDSO C
Solar/Wind Helper
0.09
20714528FRN_Y2-051
Solar/Wind Helper
0.057
20720528MAN_W1-024
Solar/Wind Helper
0.028
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.027
219249CENTRALDIV C
Solar/Wind Helper
0.01
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.089
963161AG1-165 GEN
Solar/Wind Helper
0.441
970245AG2-165 GEN
Solar/Wind Harmer
4.981
24318805MLG1
50/50
10.158
23559001PLEAS1
50/50
6.365
270051AF1-062 GEN
50/50
11.843
270475AD2-096_GEN
50/50
7.165
970153AG2-106 GEN
Solar/Wind Harmer
17.953
961921AG1-034 GEN
Solar/Wind Harmer
15.612
24721905FLATG4
Adder
24.144
241955AC1-078 GEN
Solar/Wind Harmer
8.824
241974AD2-163_GEN2
Solar/Wind Harmer
2.334
942051AE2-217 GEN
Solar/Wind Harmer
21.08
960801AF2-371 GEN
Solar/Wind Harmer
2.95
964871AG1-351 GEN
Solar/Wind Harmer
2.037
970605AG2-385 GEN
Solar/Wind Harmer
6.25
942871AE2-306 GEN
Solar/Wind Harmer
1.049
270391AF1-285 GEN3
Solar/Wind Harmer
0.538
253338AC1-165 GEN
Solar/Wind Harmer
1.243
253333AC1-068 GEN
Solar/Wind Harmer
1.199
270485AE1-090_GEN
Solar/Wind Harmer
0.692
270273AD2-016 GEN
Solar/Wind Harmer
3.037
972173AH1-669 GEN
Solar/Wind Harmer
5.679
253415AE1-040 GEN
Solar/Wind Harmer
1.251
270291AC1-194 GEN
Solar/Wind Harmer
11.751
253303V4-073 C
Solar/Wind Harmer
0.127
253370AE2-315 SEC1
Adder
2.189
253371AE2-315 SEC2
Adder
2.071
957541AF2-048 GEN
Solar/Wind Harmer
1.724
970065AG2-057 GEN
Solar/Wind Harmer
1.09
253406AD2-031_GEN
Solar/Wind Harmer
1.391
270491AE1-102 GEN2
Solar/Wind Harmer
1.407
971191AH1-055 GEN
Solar/Wind Harmer
23.759
253316AC1-085 GEN3
Solar/Wind Harmer
9.037
253433AC1-085 GEN1
Solar/Wind Harmer
5.737
946181AF1-283 GEN
Solar/Wind Harmer
14.025
270191TR4_S_V150
Solar/Wind Harmer
3.232
270247TR4_N_V136
Solar/Wind Harmer
0.916
959331AF2-224 GEN
Solar/Wind Harmer
10.775
965021AG1-366 GEN
Solar/Wind Harmer
2.506
270377AD1-106 GEN
Solar/Wind Harmer
6.65
958091AF2-103 GEN
Solar/Wind Harmer
0.174
270588AE1-091_GEN
Solar/Wind Harmer
11.804
944531AF1-118 GEN
Solar/Wind Harmer
37.541
270043AE2-236 GEN
Solar/Wind Harmer
5.893
971617AH1-308 GEN
Solar/Wind Harmer
6.198
270258AD1-119 GEN
Solar/Wind Harmer
2.97
25196608WSDLE5
Adder
9.114
962031AG1-047 GEN
Solar/Wind Harmer
3.214
957741AF2-068 GEN
Solar/Wind Harmer
15.949
252510AF1-249 C
Solar/Wind Harmer
0.444
25194608D.CRK4
Adder
1.747
270222AC2-111 GEN
Solar/Wind Harmer
8.657
970031AG2-029 GEN
Solar/Wind Harmer
31.849
270044AE2-322 C
Solar/Wind Harmer
1.394
270404AC1-167 GEN
Solar/Wind Harmer
1.161
24642205MAYFLWER
Adder
0.667
25196008MFTGT1
Adder
1.411
247604X1-042
Adder
0.435
274752CRETE EC ;2U
Adder
8.515
274753CRETE EC ;3U
Adder
8.515
274772LINCOLN ;3U
Adder
8.715
274724RIVER EC ;11
Adder
18.285
274802UNIV PARK;5U
Adder
5.997
24728705AND G3
Adder
8.251
24728505AND G1
Adder
3.945
274826FISK ;BP
Adder
11.256
274800UNIV PARK;3U
Adder
5.993
972038AH1-567 GEN2
Adder
0.375
972228AH1-698 GEN2
Adder
3.807
274676JOLIET 29;8U
Adder
30.322
274729ELWOOD EC;1P
Adder
16.844
274730ELWOOD EC;6P
Adder
16.844
274734ELWOOD EC;8P
Adder
16.844
274736ELWOOD EC;9P
Adder
16.844
274682WAUKEGAN ;7U
Adder
9.773
964991AG1-363 GEN
Solar/Wind Helper
5.152
316097T157 G90
Solar/Wind Helper
1.508
23750701CROSSCHOOL
Solar/Wind Helper
1.51
238118U2-030_1
Solar/Wind Helper
0.344
238127S14_GEN_2
Solar/Wind Helper
0.832
238148AE2-230_GEN2
Solar/Wind Helper
0.498
237080AD1-060 GEN
Solar/Wind Helper
0.343
237038AE2-054 C
Solar/Wind Helper
0.273
235062AE1-101 C1
Solar/Wind Helper
1.665
23779801AA1-109
Solar/Wind Helper
0.194
237048AF1-022 C
Solar/Wind Helper
0.179
223401AF1-299 GEN
Solar/Wind Helper
0.369
316006AB2-029 C
Solar/Wind Helper
0.117
966131AG1-482 GEN
Solar/Wind Helper
0.078
233930AB2-032 GEN
Solar/Wind Helper
0.382
233915AB1-141 GEN
Solar/Wind Helper
0.504
232422X3-066 FULL
Solar/Wind Helper
0.115
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
233998TM1NIN_3.36
Solar/Wind Helper
0.262
232404W1-003 C
Solar/Wind Helper
0.509
232428Y3-058 C
Solar/Wind Helper
0.339
232434Z2-077 GEN
Solar/Wind Helper
0.127
233954AC2-188 GEN
Solar/Wind Helper
0.233
233950AC2-186 GEN
Solar/Wind Helper
0.117
233972AC1-094 C
Solar/Wind Helper
0.303
230511AF1-262
Solar/Wind Helper
0.015
316045AC1-158 PL2
Solar/Wind Helper
4.149
230434AG1-499 GEN
Solar/Wind Helper
0.231
228728W1-130C
Solar/Wind Helper
0.054
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219904AC1-010 C
Solar/Wind Helper
0.061
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.132
20720728JCB_W1-129
Solar/Wind Helper
0.057
207445AB1-138_GEN
Solar/Wind Helper
0.105
316254AC1-120 GEN1
Solar/Wind Helper
1.062
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.311
20715228NPK_W1-113
Solar/Wind Helper
0.078
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.497
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.023
207439AE1-081 C O1
Solar/Wind Helper
0.019
207437AD2-070 GEN
Solar/Wind Helper
0.138
207518AF1-320_GEN
Solar/Wind Helper
1.577
20671928W4-073
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.03
202652Y1-033 WT C
Solar/Wind Helper
0.5
961301AF2-421 GEN
Solar/Wind Helper
0.441
963151AG1-164 GEN
Solar/Wind Helper
0.441
970513AG2-328 GEN
Solar/Wind Harmer
4.981
970517AG2-330 GEN
Solar/Wind Harmer
4.518
LAGNLTFEXP_LAGN->PJM
CLTF
14.924
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.891
TVALTFEXP_TVA->PJM
CLTF
7.337
CPLELTFEXP_CPLE->PJM
CLTF
0.647
CBM West 2LTFEXP_CBM-W2->PJM
CBM
113.418
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.671
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.268
MECLTFEXP_MEC->PJM
CLTF
15.978
SIGELTFEXP_SIGE->PJM
CLTF
0.507
NYPJM->LTFIMP_NY
CLTF
4.819
LGEELTFEXP_LGEE->PJM
CLTF
6.781
WECLTFEXP_WEC->PJM
CLTF
3.842
AG2-052LTFEXP_AG2-052->PJM
LTF
0.241
AH1-155LTFEXP_AH1-155->PJM
LTF
0.361

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P2-3_MP-500-025_SRT-A


Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-025_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:133.21 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5051.2
MW Contribution:0.86
Bus #Bus NameTypeMW Contribution
270119AB2-067 GEN1
50/50
7.072
270120AB2-067 GEN2
50/50
7.072
24318905MLG2
50/50
7.067
270471AD2-092_GEN
Solar/Wind Harmer
4.467
946101AF1-275 GEN
Solar/Wind Harmer
1.815
942861AE2-305 GEN
Solar/Wind Harmer
9.088
970077AG2-063 GEN
Solar/Wind Harmer
6.239
270224U2-072_GEN2
Solar/Wind Harmer
2.282
270227U2-072_GEN3
Solar/Wind Harmer
2.282
270228U2-072_GEN4
Solar/Wind Harmer
2.282
270231U2-072_GEN5
Solar/Wind Harmer
2.282
938701AE1-092 GEN
Solar/Wind Harmer
23.824
964601AG1-323 GEN
Solar/Wind Harmer
3.66
964601AG1-323 GEN
Solar/Wind Harmer
1.702
270518AE2-148 GEN
Solar/Wind Harmer
13.886
972269AH1-719 GEN
Adder
2.575
972159AH1-661 GEN
Adder
1.116
253378AE2-206_GEN
Solar/Wind Harmer
4.007
276820AF1-078_GEN
Solar/Wind Harmer
1.78
971199AH1-059 GEN
Solar/Wind Harmer
4.428
241960AC2-195 GEN
Solar/Wind Harmer
3.072
25326509SID D
Adder
1.452
970879AG2-548 GEN
Solar/Wind Harmer
6.777
971073AG2-665 GEN
Solar/Wind Harmer
6.777
971073AG2-665 GEN
Solar/Wind Harmer
4.728
25326109MON D
Adder
1.444
25322209TAIT E
Adder
10.654
25322209TAIT E
Adder
10.414
253370AE2-315 SEC1
Adder
2.184
971201AH1-060 GEN
Solar/Wind Harmer
2.179
253394AE2-221_GEN
Solar/Wind Harmer
4.918
253398AE2-221_GEN2
Solar/Wind Harmer
4.918
246938BC-WTG3
Solar/Wind Harmer
4.299
246937BC-WTG2
Solar/Wind Harmer
4.226
971231AH1-075 GEN
Solar/Wind Harmer
0.861
253317AC1-085 GEN4
Solar/Wind Harmer
9.014
970611AG2-400 GEN
Solar/Wind Harmer
10.746
270007AE1-245 C
Solar/Wind Harmer
6.359
942801AE2-298 GEN
Solar/Wind Harmer
1.622
962581AG1-107 GEN
Solar/Wind Harmer
5.366
961491AF2-440 GEN
Solar/Wind Harmer
2.23
25183208HLCRTG
Solar/Wind Harmer
6.45
944541AF1-119 GEN
Solar/Wind Harmer
4.455
960971AF2-388 GEN
Solar/Wind Harmer
11.625
942221AE2-234 GEN
Solar/Wind Harmer
0.779
252519AF1-045_GEN
Solar/Wind Harmer
6.448
252516AE2-318_GEN
Solar/Wind Harmer
4.919
247621Y3-024
Adder
0.256
970883AG2-550 GEN
Solar/Wind Harmer
10.605
962771AG1-126 GEN
Solar/Wind Harmer
41.012
972239AH1-704 GEN
Adder
2.683
270459AD2-067 GEN
Solar/Wind Harmer
10.243
961821AG1-024 GEN
Solar/Wind Harmer
10.399
270054AF2-122 C O1
Solar/Wind Harmer
3.993
270520AE2-214 GEN
Solar/Wind Harmer
7.274
270284AF1-227 GEN1
Solar/Wind Harmer
6.791
270286AF1-227 GEN2
Solar/Wind Harmer
2.512
270287AF1-227 GEN3
Solar/Wind Harmer
2.512
253383AE2-342_GEN
Solar/Wind Harmer
1.045
241973AD2-163_GEN1
Solar/Wind Harmer
2.33
945631AF1-228 GEN
Solar/Wind Harmer
5.461
943861AF1-054 GEN
Solar/Wind Harmer
4.486
943851AF1-053 GEN
Solar/Wind Harmer
2.168
270156DARBY CT1
Adder
10.416
270157DARBY CT2
Adder
10.391
270158DARBY CT3
Adder
10.225
970689AG2-444 GEN
Solar/Wind Harmer
18.82
270578AF1-285 GEN2
Solar/Wind Harmer
0.537
270432AC2-029 GEN
Solar/Wind Harmer
8.046
270302AB2-170 GEN
Solar/Wind Harmer
9.546
270317AD1-130_GEN
Solar/Wind Harmer
3.66
940611AE2-048 GEN
Solar/Wind Harmer
25.033
941391AE2-136 GEN
Solar/Wind Harmer
12.972
270269AC2-059
Solar/Wind Harmer
10.602
241972AD1-140 GEN
Solar/Wind Harmer
5.021
958581AF2-149 GEN
Solar/Wind Harmer
4.736
970179AG2-119 GEN
Solar/Wind Harmer
8.837
270340AC2-060 GEN
Solar/Wind Harmer
3.346
970879AG2-548 GEN
Solar/Wind Harmer
4.728
253372AE2-315 SEC3
Adder
2.066
253372AE2-315 SEC3
Adder
2.066
25306009OHH W.
Adder
3.134
253349AC2-067 GEN
Solar/Wind Harmer
5.408
253400AC2-068 GEN
Solar/Wind Harmer
2.175
957201AF2-014 GEN
Solar/Wind Harmer
4.898
270435AC2-044 GEN
Solar/Wind Harmer
2.16
965051AG1-369 GEN
Solar/Wind Harmer
5.366
965041AG1-368 GEN
Solar/Wind Harmer
10.722
247607V1-011 GEN
Solar/Wind Harmer
4.239
971567AH1-282 GEN
Solar/Wind Harmer
16.059
966831AG1-554 GEN
Solar/Wind Harmer
1.279
971989AH1-539 GEN
Solar/Wind Harmer
13.833
24729505KEY G4
Adder
6.928
963791AG1-232 GEN
Solar/Wind Harmer
14.415
270071AF1-092 GEN
Solar/Wind Harmer
16.001
971985AH1-537 GEN
Solar/Wind Harmer
18.998
958711AF2-162 GEN
Solar/Wind Harmer
1.076
270024AE2-089 GEN
Solar/Wind Harmer
4.99
270367AC2-061_GEN
Solar/Wind Harmer
3.379
965101AG1-375 GEN
Solar/Wind Harmer
10.622
971673AH1-337 GEN
Solar/Wind Harmer
4.88
252524AE2-267 GEN
Solar/Wind Harmer
1.673
971029AG2-637 GEN
Solar/Wind Harmer
15.909
25196408WSDLE3
Adder
9.356
25196308WSDLE2
Adder
9.275
25196208WSDLE1
Adder
9.252
25196708WSDLE6
Adder
9.228
25196508WSDLE4
Adder
8.996
270543AE2-219 C
Solar/Wind Harmer
5.43
961761AG1-017 GEN
Solar/Wind Harmer
0.454
945581AF1-223 GEN
Solar/Wind Harmer
4.805
270297AD1-101 GEN
Solar/Wind Harmer
2.947
944031AF1-071 GEN
Solar/Wind Harmer
1.064
25196108MFTGT2
Adder
1.601
25196108MFTGT2
Adder
1.486
274775LINCOLN ;6U
Adder
8.688
274776LINCOLN ;7U
Adder
8.688
274777LINCOLN ;8U
Adder
8.688
274814UNIV PK N;0U
Adder
5.192
274807UNIV PK N;3U
Adder
5.18
274805UNIV PK N;1U
Adder
5.158
274811UNIV PK N;7U
Adder
5.147
972037AH1-567 GEN1
Adder
0.188
274827FISK ;RP
Adder
7.953
972227AH1-698 GEN1
Adder
2.673
274687WILL CNTY;4U
Adder
28.564
274687WILL CNTY;4U
Adder
28.564
274675JOLIET 29;7U
Adder
31.348
274675JOLIET 29;7U
Adder
30.228
274731ELWOOD EC;2P
Adder
16.792
274733ELWOOD EC;3P
Adder
16.792
274735ELWOOD EC;4P
Adder
16.792
274728ELWOOD EC;5P
Adder
16.792
972203AH1-686 GEN
Adder
2.344
274746AC1-111 G10
Adder
5.687
274744AC1-111 GEN8
Adder
5.687
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238126S14_GEN_1
Solar/Wind Helper
0.829
238152AF2-075_GEN
Solar/Wind Helper
0.708
238208AF1-136 C
Solar/Wind Helper
0.22
23546401DTGZ2-030
Solar/Wind Helper
0.089
237085AD2-009_GEN
Solar/Wind Helper
1.651
3138216PACIFIC
Solar/Wind Helper
0.044
316411AF1-147_GEN1
Solar/Wind Helper
0.889
316415AF1-147_GEN2
Solar/Wind Helper
0.889
23750501ELLIOTTS
Solar/Wind Helper
0.64
959381AF2-229 GEN
Solar/Wind Helper
0.358
3141426STAFORD
Solar/Wind Helper
0.052
960921AF2-383 GEN
Solar/Wind Helper
0.182
205943AE1-185 GEN
Solar/Wind Helper
0.51
205932AD2-116_GEN
Solar/Wind Helper
0.509
205956AE1-196_GEN
Solar/Wind Helper
0.509
233935AB2-179 C
Solar/Wind Helper
1.27
232436AB1-176 C
Solar/Wind Helper
0.044
233923SMA
Solar/Wind Helper
0.959
233990AG1-397 GEN
Solar/Wind Helper
0.03
234033AF1-007_GEN
Solar/Wind Helper
7.028
232432Z2-076 GEN
Solar/Wind Helper
0.067
964001AG1-254 GEN
Solar/Wind Helper
0.957
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.115
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.08
203975AE1-071-GEN
Solar/Wind Helper
2.501
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.29
219620RIDERU C
Solar/Wind Helper
0.001
316164AC1-076 GEN
Solar/Wind Helper
1.097
20675528CPH_W2-050
Solar/Wind Helper
0.087
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
218524CNTRALGAS1 C
Solar/Wind Helper
0.161
966261AG1-495 GEN
Solar/Wind Helper
0.081
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20675928HOL_W4-097
Solar/Wind Helper
0.05
207484AF2-139 C O1
Solar/Wind Helper
0.084
20674828DL_W4-046
Solar/Wind Helper
0.008
207408W3-077 C
Solar/Wind Helper
0.084
970885AG2-551 GEN
Solar/Wind Harmer
2.466
270201AC2-176 GEN
Solar/Wind Harmer
5.45
25194408D.CRK1
Adder
8.014
25194508D.CRK3
Adder
1.498
964611AG1-324 GEN
Solar/Wind Harmer
1.249
964611AG1-324 GEN
Solar/Wind Harmer
0.554
252509AD1-136 GEN
Solar/Wind Harmer
0.271
247620Y3-023
Adder
0.484
24728805RICHG1
Adder
3.969
24728905RICHG2
Adder
3.969
274770LINCOLN ;1U
Adder
8.688
274771LINCOLN ;2U
Adder
8.688
274808UNIV PK N;4U
Adder
5.124
274803UNIV PARK;6U
Adder
5.978
972259AH1-714 GEN
Adder
19.535
274674JOLIET 9 ;6U
Adder
15.727
274696ROCKY RD ;4P
Adder
11.554
274695ROCKY RD ;2P
Adder
11.287
274693ROCKY RD ;1P
Adder
11.176
274697ROCKY RD ;3P
Adder
3.066
23585401KL_K28_T16
Solar/Wind Helper
1.485
238120AE2-309 GEN
Solar/Wind Helper
0.526
238175AF1-290_GEN
Solar/Wind Helper
0.153
238169AE2-226 GEN1
Solar/Wind Helper
0.702
238170AE2-226 GEN2
Solar/Wind Helper
0.702
235020AA1-095 C
Solar/Wind Helper
0.053
23777901MDS_W4-102
Solar/Wind Helper
0.177
237002AB1-128_GEN
Solar/Wind Helper
0.444
237034AC2-136 C
Solar/Wind Helper
0.227
235063AE1-101 C2
Solar/Wind Helper
1.661
237001AB1-127_GEN
Solar/Wind Helper
0.442
23777801MSM_W1-116
Solar/Wind Helper
0.114
237025AB1-124 C
Solar/Wind Helper
0.164
237006AB1-125 GEN
Solar/Wind Helper
0.123
226929AD2-058 GEN
Solar/Wind Helper
0.099
205916AD1-020 GEN
Solar/Wind Helper
1.715
20390526W1-045 C
Solar/Wind Helper
0.35
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
233987AB2-037 GEN
Solar/Wind Helper
2.344
233933AB2-153 GEN
Solar/Wind Helper
0.233
232424Y1-079 C
Solar/Wind Helper
0.116
233944AB2-135 GEN
Solar/Wind Helper
0.589
233946AB2-136 GEN
Solar/Wind Helper
0.569
234036AF2-325 C
Solar/Wind Helper
0.042
233901CHERRYDALE C
Solar/Wind Helper
0.233
232408W1-005 C
Solar/Wind Helper
0.508
232410W1-006 C
Solar/Wind Helper
0.508
233939AC1-091 C
Solar/Wind Helper
0.35
233970AC1-092 C
Solar/Wind Helper
0.35
315651AD1-115 GEN
Solar/Wind Helper
0.785
316447AC1-158 HLD
Solar/Wind Helper
2.848
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.04
219921AF1-264
Solar/Wind Helper
0.051
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.082
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.19
20716928W4-060COL
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.016
20673828FLE_V3-070
Solar/Wind Helper
0.091
207442AE1-156 GEN
Solar/Wind Helper
0.326
20676128MHD_W3-029
Solar/Wind Helper
0.096
20671828STAW2-080
Solar/Wind Helper
0.027
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
207471AF2-354 C
Solar/Wind Helper
0.169
20674928WA_W3-044
Solar/Wind Helper
0.098
20676228FRD_X1-012
Solar/Wind Helper
0.092
964851AG1-348 GEN
Solar/Wind Helper
0.081
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.045
211065PSPA IPP
Solar/Wind Helper
0.152
211065PSPA IPP
Solar/Wind Helper
0.152
970321AG2-212 GEN
Solar/Wind Harmer
3.728
270166AC1-044 GEN3
50/50
7.072
23559101PLEAS2
50/50
6.183
962761AG1-125 GEN
Solar/Wind Harmer
41.012
970149AG2-104 GEN
Solar/Wind Harmer
50.65
970155AG2-107 GEN
Solar/Wind Harmer
17.883
270349AD2-093_GEN
Solar/Wind Harmer
4.467
24721705FLATG2
Adder
23.989
270159DARBY CT4
Adder
10.25
970593AG2-378 GEN
Solar/Wind Harmer
2.311
270223U2-072_GEN1
Solar/Wind Harmer
2.282
270578AF1-285 GEN2
Solar/Wind Harmer
1.396
270391AF1-285 GEN3
Solar/Wind Harmer
1.396
253343AC1-166 GEN
Solar/Wind Harmer
1.241
253325AC1-069 GEN
Solar/Wind Harmer
1.197
270462AD2-086
Solar/Wind Harmer
7.941
971995AH1-542 GEN
Solar/Wind Harmer
12.502
270263AC1-001 GEN
Solar/Wind Harmer
1.177
25326309TAIT D
Adder
1.197
960071AF2-298 GEN
Solar/Wind Harmer
5.441
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.066
241813AF1-122_GEN
Solar/Wind Harmer
6.974
927014AC1-188 GEN
Solar/Wind Harmer
1.725
270510AE1-227 GEN1
Solar/Wind Harmer
2.689
246936BC-WTG1
Solar/Wind Harmer
4.226
270489AE1-102 GEN1
Solar/Wind Harmer
1.404
965421AG1-410 GEN
Solar/Wind Harmer
32.386
960001AF2-291 GEN
Solar/Wind Harmer
3.255
253432AC1-085 GEN2
Solar/Wind Harmer
0.288
946171AF1-282 GEN
Solar/Wind Harmer
10.761
247521TR3_G114
Solar/Wind Harmer
3.613
270246TR4_N_V150
Solar/Wind Harmer
0.914
965011AG1-365 GEN
Solar/Wind Harmer
10.746
24695305TIMB G C
Solar/Wind Harmer
5.901
965651AG1-433 GEN
Solar/Wind Harmer
5.813
958861AF2-177 GEN
Solar/Wind Harmer
11.61
247536S-71 GEN
Solar/Wind Harmer
4.293
25194608D.CRK4
Adder
1.742
945371AF1-202 GEN
Solar/Wind Harmer
7.392
252507AC2-088 GEN
Solar/Wind Harmer
1.899
270063AE2-323 C
Solar/Wind Harmer
2.33
25196808ZIMRHP
Adder
79.831
24639705ELKHART HY
Adder
0.161
25196008MFTGT1
Adder
1.452
274751CRETE EC ;1U
Adder
8.489
274754CRETE EC ;4U
Adder
8.489
274773LINCOLN ;4U
Adder
8.688
274774LINCOLN ;5U
Adder
8.688
274723RIVER EC ;12
Adder
18.445
274812UNIV PK N;8U
Adder
5.147
24728605AND G2
Adder
3.933
274801UNIV PARK;4U
Adder
5.975
274676JOLIET 29;8U
Adder
31.348
274732ELWOOD EC;7P
Adder
16.792
274674JOLIET 9 ;6U
Adder
15.727
274745AC1-111 GEN9
Adder
5.687
970091AG2-072 GEN
Adder
77.755
316095T157 G97
Solar/Wind Helper
1.505
23583801GRNGAP
Solar/Wind Helper
5.606
238185AF2-356 C
Solar/Wind Helper
2.651
238108AE1-109 GEN1
Solar/Wind Helper
0.114
235054AD2-180 GEN
Solar/Wind Helper
2.034
235531U2-073 GEN
Solar/Wind Helper
3.288
238117U2-030
Solar/Wind Helper
0.342
238147AE2-230_GEN1
Solar/Wind Helper
0.495
238149AF1-291A_GEN
Solar/Wind Helper
0.141
23751201ROTHROCK
Solar/Wind Helper
0.826
23562501BACKB
Solar/Wind Helper
1.01
237061AD1-155 GEN
Solar/Wind Helper
0.053
238221AF1-254 C O1
Solar/Wind Helper
0.275
235067AD1-061 GEN
Solar/Wind Helper
0.496
23751101LEADS_P59
Solar/Wind Helper
1.41
237030AB1-096 C
Solar/Wind Helper
0.071
3141196NOKESVL
Solar/Wind Helper
1.032
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.346
223402AF1-300 C
Solar/Wind Helper
0.368
205917AD1-020 ES
Solar/Wind Helper
0.369
233982AB2-133 GEN
Solar/Wind Helper
0.358
233918AB1-142 GEN
Solar/Wind Helper
0.503
233994AC2-023 GEN
Solar/Wind Helper
0.962
233996TM1833_GEN
Solar/Wind Helper
0.262
233997TMININ_4.2
Solar/Wind Helper
0.262
232406W1-004 FULL
Solar/Wind Helper
0.508
233940AF2-379 C
Solar/Wind Helper
0.062
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.233
233971AC1-093 C
Solar/Wind Helper
0.358
316044AC1-158 PL1
Solar/Wind Helper
1.294
316450AC1-158 RIC
Solar/Wind Helper
0.345
230430AE1-229_GEN
Solar/Wind Helper
3.376
230415AB2-049 C
Solar/Wind Helper
0.03
228729W2-030 C
Solar/Wind Helper
0.111
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.15
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
219348LDSOLAR C
Solar/Wind Helper
0.115
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.063
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.353
219276PARKLANDSO C
Solar/Wind Helper
0.089
20714528FRN_Y2-051
Solar/Wind Helper
0.057
20720528MAN_W1-024
Solar/Wind Helper
0.028
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.027
219249CENTRALDIV C
Solar/Wind Helper
0.01
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.089
970245AG2-165 GEN
Solar/Wind Harmer
3.728
20675728RH_W2-091
Solar/Wind Helper
0.137
20675128HRM_W1-127
Solar/Wind Helper
0.03
209116AE2-175 GEN
Solar/Wind Helper
1.781
24318805MLG1
50/50
10.115
23559001PLEAS1
50/50
6.183
270051AF1-062 GEN
50/50
11.828
270475AD2-096_GEN
50/50
7.148
970153AG2-106 GEN
Solar/Wind Harmer
17.883
961921AG1-034 GEN
Solar/Wind Harmer
15.599
24721905FLATG4
Adder
23.989
241955AC1-078 GEN
Solar/Wind Harmer
8.811
241974AD2-163_GEN2
Solar/Wind Harmer
2.33
942051AE2-217 GEN
Solar/Wind Harmer
21.044
960801AF2-371 GEN
Solar/Wind Harmer
2.947
964871AG1-351 GEN
Solar/Wind Harmer
2.035
970605AG2-385 GEN
Solar/Wind Harmer
6.239
942871AE2-306 GEN
Solar/Wind Harmer
1.047
270391AF1-285 GEN3
Solar/Wind Harmer
0.537
253338AC1-165 GEN
Solar/Wind Harmer
1.241
253333AC1-068 GEN
Solar/Wind Harmer
1.197
270485AE1-090_GEN
Solar/Wind Harmer
0.69
270273AD2-016 GEN
Solar/Wind Harmer
3.032
972173AH1-669 GEN
Solar/Wind Harmer
5.669
253415AE1-040 GEN
Solar/Wind Harmer
1.248
270291AC1-194 GEN
Solar/Wind Harmer
11.736
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.066
970065AG2-057 GEN
Solar/Wind Harmer
1.09
957541AF2-048 GEN
Solar/Wind Harmer
1.72
270512AE1-227 GEN2
Solar/Wind Harmer
2.283
253406AD2-031_GEN
Solar/Wind Harmer
1.388
270491AE1-102 GEN2
Solar/Wind Harmer
1.404
971191AH1-055 GEN
Solar/Wind Harmer
23.693
270377AD1-106 GEN
Solar/Wind Harmer
6.649
253316AC1-085 GEN3
Solar/Wind Harmer
9.014
253433AC1-085 GEN1
Solar/Wind Harmer
5.722
946181AF1-283 GEN
Solar/Wind Harmer
13.99
270191TR4_S_V150
Solar/Wind Harmer
3.224
270247TR4_N_V136
Solar/Wind Harmer
0.914
959331AF2-224 GEN
Solar/Wind Harmer
10.746
965021AG1-366 GEN
Solar/Wind Harmer
2.499
958091AF2-103 GEN
Solar/Wind Harmer
0.173
270588AE1-091_GEN
Solar/Wind Harmer
11.789
944531AF1-118 GEN
Solar/Wind Harmer
37.432
270043AE2-236 GEN
Solar/Wind Harmer
5.876
270258AD1-119 GEN
Solar/Wind Harmer
2.963
971617AH1-308 GEN
Solar/Wind Harmer
6.181
25196608WSDLE5
Adder
9.089
962031AG1-047 GEN
Solar/Wind Harmer
3.205
252510AF1-249 C
Solar/Wind Harmer
0.443
957741AF2-068 GEN
Solar/Wind Harmer
15.904
25194608D.CRK4
Adder
1.742
270222AC2-111 GEN
Solar/Wind Harmer
8.632
970031AG2-029 GEN
Solar/Wind Harmer
31.759
270044AE2-322 C
Solar/Wind Harmer
1.391
270404AC1-167 GEN
Solar/Wind Harmer
1.158
24642205MAYFLWER
Adder
0.665
25196008MFTGT1
Adder
1.406
247604X1-042
Adder
0.434
274752CRETE EC ;2U
Adder
8.489
274753CRETE EC ;3U
Adder
8.489
274772LINCOLN ;3U
Adder
8.688
274724RIVER EC ;11
Adder
18.229
24728705AND G3
Adder
8.226
274802UNIV PARK;5U
Adder
5.978
24728505AND G1
Adder
3.933
274826FISK ;BP
Adder
11.221
274800UNIV PARK;3U
Adder
5.975
972038AH1-567 GEN2
Adder
0.374
972228AH1-698 GEN2
Adder
3.796
274676JOLIET 29;8U
Adder
30.228
274729ELWOOD EC;1P
Adder
16.792
274730ELWOOD EC;6P
Adder
16.792
274734ELWOOD EC;8P
Adder
16.792
274736ELWOOD EC;9P
Adder
16.792
274682WAUKEGAN ;7U
Adder
9.742
964991AG1-363 GEN
Solar/Wind Helper
5.141
316097T157 G90
Solar/Wind Helper
1.505
23750701CROSSCHOOL
Solar/Wind Helper
1.505
238118U2-030_1
Solar/Wind Helper
0.342
238127S14_GEN_2
Solar/Wind Helper
0.829
238148AE2-230_GEN2
Solar/Wind Helper
0.497
237080AD1-060 GEN
Solar/Wind Helper
0.342
237038AE2-054 C
Solar/Wind Helper
0.272
235062AE1-101 C1
Solar/Wind Helper
1.661
23779801AA1-109
Solar/Wind Helper
0.193
237048AF1-022 C
Solar/Wind Helper
0.178
223401AF1-299 GEN
Solar/Wind Helper
0.368
316006AB2-029 C
Solar/Wind Helper
0.117
966131AG1-482 GEN
Solar/Wind Helper
0.077
233930AB2-032 GEN
Solar/Wind Helper
0.381
233915AB1-141 GEN
Solar/Wind Helper
0.503
232422X3-066 FULL
Solar/Wind Helper
0.114
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
233998TM1NIN_3.36
Solar/Wind Helper
0.262
232404W1-003 C
Solar/Wind Helper
0.508
232428Y3-058 C
Solar/Wind Helper
0.338
233954AC2-188 GEN
Solar/Wind Helper
0.233
233950AC2-186 GEN
Solar/Wind Helper
0.116
232434Z2-077 GEN
Solar/Wind Helper
0.127
233972AC1-094 C
Solar/Wind Helper
0.303
316045AC1-158 PL2
Solar/Wind Helper
4.142
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.23
228728W1-130C
Solar/Wind Helper
0.054
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219904AC1-010 C
Solar/Wind Helper
0.061
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.131
20720728JCB_W1-129
Solar/Wind Helper
0.057
316254AC1-120 GEN1
Solar/Wind Helper
1.06
207445AB1-138_GEN
Solar/Wind Helper
0.104
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.31
20715228NPK_W1-113
Solar/Wind Helper
0.078
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.496
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
207437AD2-070 GEN
Solar/Wind Helper
0.138
207518AF1-320_GEN
Solar/Wind Helper
1.573
20671928W4-073
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.03
970513AG2-328 GEN
Solar/Wind Harmer
3.728
970517AG2-330 GEN
Solar/Wind Harmer
3.381
LAGNLTFEXP_LAGN->PJM
CLTF
14.864
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.83
TVALTFEXP_TVA->PJM
CLTF
7.306
CPLELTFEXP_CPLE->PJM
CLTF
0.632
CBM West 2LTFEXP_CBM-W2->PJM
CBM
113.005
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.265
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.153
MECLTFEXP_MEC->PJM
CLTF
15.925
SIGELTFEXP_SIGE->PJM
CLTF
0.506
NYPJM->LTFIMP_NY
CLTF
4.803
LGEELTFEXP_LGEE->PJM
CLTF
6.759
WECLTFEXP_WEC->PJM
CLTF
3.83
AG2-052LTFEXP_AG2-052->PJM
LTF
0.24
AH1-155LTFEXP_AH1-155->PJM
LTF
0.36

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P2-3_MP-500-015_SRT-A


Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-015_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:132.9 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5039.69
MW Contribution:0.86
Bus #Bus NameTypeMW Contribution
270119AB2-067 GEN1
50/50
7.063
270120AB2-067 GEN2
50/50
7.063
24318905MLG2
50/50
7.074
270471AD2-092_GEN
Solar/Wind Harmer
4.466
946101AF1-275 GEN
Solar/Wind Harmer
1.816
942861AE2-305 GEN
Solar/Wind Harmer
9.089
970077AG2-063 GEN
Solar/Wind Harmer
6.24
270224U2-072_GEN2
Solar/Wind Harmer
2.282
270227U2-072_GEN3
Solar/Wind Harmer
2.282
270228U2-072_GEN4
Solar/Wind Harmer
2.282
270231U2-072_GEN5
Solar/Wind Harmer
2.282
938701AE1-092 GEN
Solar/Wind Harmer
23.829
964601AG1-323 GEN
Solar/Wind Harmer
3.66
964601AG1-323 GEN
Solar/Wind Harmer
1.702
270518AE2-148 GEN
Solar/Wind Harmer
13.889
972269AH1-719 GEN
Adder
2.587
972159AH1-661 GEN
Adder
1.119
253378AE2-206_GEN
Solar/Wind Harmer
4.007
276820AF1-078_GEN
Solar/Wind Harmer
1.78
971199AH1-059 GEN
Solar/Wind Harmer
4.433
241960AC2-195 GEN
Solar/Wind Harmer
3.073
25326509SID D
Adder
1.452
970879AG2-548 GEN
Solar/Wind Harmer
6.78
971073AG2-665 GEN
Solar/Wind Harmer
6.78
971073AG2-665 GEN
Solar/Wind Harmer
4.73
25326109MON D
Adder
1.444
25322209TAIT E
Adder
10.653
25322209TAIT E
Adder
10.414
971201AH1-060 GEN
Solar/Wind Harmer
2.181
253370AE2-315 SEC1
Adder
2.184
253394AE2-221_GEN
Solar/Wind Harmer
4.918
253398AE2-221_GEN2
Solar/Wind Harmer
4.918
246938BC-WTG3
Solar/Wind Harmer
4.299
246937BC-WTG2
Solar/Wind Harmer
4.226
971231AH1-075 GEN
Solar/Wind Harmer
0.862
253317AC1-085 GEN4
Solar/Wind Harmer
9.013
970611AG2-400 GEN
Solar/Wind Harmer
10.743
270007AE1-245 C
Solar/Wind Harmer
6.358
942801AE2-298 GEN
Solar/Wind Harmer
1.622
962581AG1-107 GEN
Solar/Wind Harmer
5.365
961491AF2-440 GEN
Solar/Wind Harmer
2.229
25183208HLCRTG
Solar/Wind Harmer
6.449
944541AF1-119 GEN
Solar/Wind Harmer
4.453
960971AF2-388 GEN
Solar/Wind Harmer
11.621
942221AE2-234 GEN
Solar/Wind Harmer
0.778
252519AF1-045_GEN
Solar/Wind Harmer
6.447
252516AE2-318_GEN
Solar/Wind Harmer
4.918
247621Y3-024
Adder
0.256
970883AG2-550 GEN
Solar/Wind Harmer
10.602
970885AG2-551 GEN
Solar/Wind Harmer
2.465
270201AC2-176 GEN
Solar/Wind Harmer
5.449
25194408D.CRK1
Adder
8.013
25194508D.CRK3
Adder
1.498
964611AG1-324 GEN
Solar/Wind Harmer
1.248
964611AG1-324 GEN
Solar/Wind Harmer
0.554
252509AD1-136 GEN
Solar/Wind Harmer
0.271
247620Y3-023
Adder
0.484
24728805RICHG1
Adder
3.968
24728905RICHG2
Adder
3.968
274770LINCOLN ;1U
Adder
8.684
274771LINCOLN ;2U
Adder
8.684
274808UNIV PK N;4U
Adder
5.122
274803UNIV PARK;6U
Adder
5.976
972259AH1-714 GEN
Adder
19.527
274674JOLIET 9 ;6U
Adder
15.72
274696ROCKY RD ;4P
Adder
11.549
274695ROCKY RD ;2P
Adder
11.282
274693ROCKY RD ;1P
Adder
11.171
274697ROCKY RD ;3P
Adder
3.065
23585401KL_K28_T16
Solar/Wind Helper
1.478
238120AE2-309 GEN
Solar/Wind Helper
0.524
238175AF1-290_GEN
Solar/Wind Helper
0.153
238169AE2-226 GEN1
Solar/Wind Helper
0.702
238170AE2-226 GEN2
Solar/Wind Helper
0.702
235020AA1-095 C
Solar/Wind Helper
0.053
23777901MDS_W4-102
Solar/Wind Helper
0.177
237034AC2-136 C
Solar/Wind Helper
0.227
237002AB1-128_GEN
Solar/Wind Helper
0.443
235063AE1-101 C2
Solar/Wind Helper
1.661
237001AB1-127_GEN
Solar/Wind Helper
0.442
23777801MSM_W1-116
Solar/Wind Helper
0.114
237025AB1-124 C
Solar/Wind Helper
0.164
237006AB1-125 GEN
Solar/Wind Helper
0.123
226929AD2-058 GEN
Solar/Wind Helper
0.099
205916AD1-020 GEN
Solar/Wind Helper
1.715
20390526W1-045 C
Solar/Wind Helper
0.35
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
233987AB2-037 GEN
Solar/Wind Helper
2.344
233933AB2-153 GEN
Solar/Wind Helper
0.233
232424Y1-079 C
Solar/Wind Helper
0.116
233944AB2-135 GEN
Solar/Wind Helper
0.589
233946AB2-136 GEN
Solar/Wind Helper
0.569
234036AF2-325 C
Solar/Wind Helper
0.042
233901CHERRYDALE C
Solar/Wind Helper
0.233
232408W1-005 C
Solar/Wind Helper
0.508
232410W1-006 C
Solar/Wind Helper
0.508
233939AC1-091 C
Solar/Wind Helper
0.35
233970AC1-092 C
Solar/Wind Helper
0.35
315651AD1-115 GEN
Solar/Wind Helper
0.785
316447AC1-158 HLD
Solar/Wind Helper
2.848
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.04
219921AF1-264
Solar/Wind Helper
0.051
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.082
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.19
20716928W4-060COL
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.016
20673828FLE_V3-070
Solar/Wind Helper
0.091
207442AE1-156 GEN
Solar/Wind Helper
0.326
20676128MHD_W3-029
Solar/Wind Helper
0.096
20671828STAW2-080
Solar/Wind Helper
0.027
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
207471AF2-354 C
Solar/Wind Helper
0.169
20674928WA_W3-044
Solar/Wind Helper
0.098
964851AG1-348 GEN
Solar/Wind Helper
0.081
20676228FRD_X1-012
Solar/Wind Helper
0.092
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.045
211065PSPA IPP
Solar/Wind Helper
0.152
211065PSPA IPP
Solar/Wind Helper
0.152
970321AG2-212 GEN
Solar/Wind Harmer
3.726
270166AC1-044 GEN3
50/50
7.063
23559101PLEAS2
50/50
6.112
23684101S70BUS1
50/50
0.168
962761AG1-125 GEN
Solar/Wind Harmer
40.976
970149AG2-104 GEN
Solar/Wind Harmer
50.605
970155AG2-107 GEN
Solar/Wind Harmer
17.867
270349AD2-093_GEN
Solar/Wind Harmer
4.466
24721705FLATG2
Adder
23.946
270159DARBY CT4
Adder
10.253
970593AG2-378 GEN
Solar/Wind Harmer
2.311
270223U2-072_GEN1
Solar/Wind Harmer
2.282
270578AF1-285 GEN2
Solar/Wind Harmer
1.396
270391AF1-285 GEN3
Solar/Wind Harmer
1.396
253343AC1-166 GEN
Solar/Wind Harmer
1.242
253325AC1-069 GEN
Solar/Wind Harmer
1.197
270462AD2-086
Solar/Wind Harmer
7.941
971995AH1-542 GEN
Solar/Wind Harmer
12.507
270263AC1-001 GEN
Solar/Wind Harmer
1.177
270510AE1-227 GEN1
Solar/Wind Harmer
2.727
25326309TAIT D
Adder
1.197
241813AF1-122_GEN
Solar/Wind Harmer
6.978
960071AF2-298 GEN
Solar/Wind Harmer
5.44
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.065
927014AC1-188 GEN
Solar/Wind Harmer
1.725
246936BC-WTG1
Solar/Wind Harmer
4.226
270489AE1-102 GEN1
Solar/Wind Harmer
1.404
965421AG1-410 GEN
Solar/Wind Harmer
32.379
960001AF2-291 GEN
Solar/Wind Harmer
3.256
253432AC1-085 GEN2
Solar/Wind Harmer
0.288
946171AF1-282 GEN
Solar/Wind Harmer
10.76
247521TR3_G114
Solar/Wind Harmer
3.612
270246TR4_N_V150
Solar/Wind Harmer
0.914
962771AG1-126 GEN
Solar/Wind Harmer
40.976
972239AH1-704 GEN
Adder
2.69
270054AF2-122 C O1
Solar/Wind Harmer
3.996
270459AD2-067 GEN
Solar/Wind Harmer
10.248
961821AG1-024 GEN
Solar/Wind Harmer
10.404
270520AE2-214 GEN
Solar/Wind Harmer
7.276
270284AF1-227 GEN1
Solar/Wind Harmer
6.79
270286AF1-227 GEN2
Solar/Wind Harmer
2.512
270287AF1-227 GEN3
Solar/Wind Harmer
2.512
253383AE2-342_GEN
Solar/Wind Harmer
1.045
241973AD2-163_GEN1
Solar/Wind Harmer
2.331
945631AF1-228 GEN
Solar/Wind Harmer
5.463
943861AF1-054 GEN
Solar/Wind Harmer
4.486
943851AF1-053 GEN
Solar/Wind Harmer
2.168
270156DARBY CT1
Adder
10.419
270157DARBY CT2
Adder
10.393
270158DARBY CT3
Adder
10.228
970689AG2-444 GEN
Solar/Wind Harmer
18.827
270578AF1-285 GEN2
Solar/Wind Harmer
0.537
270432AC2-029 GEN
Solar/Wind Harmer
8.049
940611AE2-048 GEN
Solar/Wind Harmer
25.14
941391AE2-136 GEN
Solar/Wind Harmer
13.027
270302AB2-170 GEN
Solar/Wind Harmer
9.546
270317AD1-130_GEN
Solar/Wind Harmer
3.659
270269AC2-059
Solar/Wind Harmer
10.605
241972AD1-140 GEN
Solar/Wind Harmer
5.021
958581AF2-149 GEN
Solar/Wind Harmer
4.743
970179AG2-119 GEN
Solar/Wind Harmer
8.842
270340AC2-060 GEN
Solar/Wind Harmer
3.346
970879AG2-548 GEN
Solar/Wind Harmer
4.73
253372AE2-315 SEC3
Adder
2.065
253372AE2-315 SEC3
Adder
2.065
25306009OHH W.
Adder
3.133
253349AC2-067 GEN
Solar/Wind Harmer
5.407
253400AC2-068 GEN
Solar/Wind Harmer
2.174
957201AF2-014 GEN
Solar/Wind Harmer
4.898
270435AC2-044 GEN
Solar/Wind Harmer
2.16
965051AG1-369 GEN
Solar/Wind Harmer
5.365
965041AG1-368 GEN
Solar/Wind Harmer
10.719
247607V1-011 GEN
Solar/Wind Harmer
4.239
971567AH1-282 GEN
Solar/Wind Harmer
16.075
966831AG1-554 GEN
Solar/Wind Harmer
1.28
971989AH1-539 GEN
Solar/Wind Harmer
13.838
24729505KEY G4
Adder
6.925
963791AG1-232 GEN
Solar/Wind Harmer
14.411
270071AF1-092 GEN
Solar/Wind Harmer
15.995
971985AH1-537 GEN
Solar/Wind Harmer
18.996
958711AF2-162 GEN
Solar/Wind Harmer
1.076
270024AE2-089 GEN
Solar/Wind Harmer
4.988
270367AC2-061_GEN
Solar/Wind Harmer
3.378
965101AG1-375 GEN
Solar/Wind Harmer
10.618
971673AH1-337 GEN
Solar/Wind Harmer
4.878
252524AE2-267 GEN
Solar/Wind Harmer
1.672
25196408WSDLE3
Adder
9.354
25196308WSDLE2
Adder
9.273
25196208WSDLE1
Adder
9.25
25196708WSDLE6
Adder
9.227
25196508WSDLE4
Adder
8.994
971029AG2-637 GEN
Solar/Wind Harmer
15.905
270543AE2-219 C
Solar/Wind Harmer
5.429
961761AG1-017 GEN
Solar/Wind Harmer
0.454
945581AF1-223 GEN
Solar/Wind Harmer
4.803
270297AD1-101 GEN
Solar/Wind Harmer
2.947
944031AF1-071 GEN
Solar/Wind Harmer
1.064
25196108MFTGT2
Adder
1.6
25196108MFTGT2
Adder
1.486
274775LINCOLN ;6U
Adder
8.684
274776LINCOLN ;7U
Adder
8.684
274777LINCOLN ;8U
Adder
8.684
274814UNIV PK N;0U
Adder
5.189
274807UNIV PK N;3U
Adder
5.178
274805UNIV PK N;1U
Adder
5.156
274811UNIV PK N;7U
Adder
5.144
972037AH1-567 GEN1
Adder
0.188
274827FISK ;RP
Adder
7.949
972227AH1-698 GEN1
Adder
2.671
274687WILL CNTY;4U
Adder
28.551
274687WILL CNTY;4U
Adder
28.551
274675JOLIET 29;7U
Adder
31.334
274675JOLIET 29;7U
Adder
30.215
274731ELWOOD EC;2P
Adder
16.784
274733ELWOOD EC;3P
Adder
16.784
274735ELWOOD EC;4P
Adder
16.784
274728ELWOOD EC;5P
Adder
16.784
972203AH1-686 GEN
Adder
2.341
274746AC1-111 G10
Adder
5.685
274744AC1-111 GEN8
Adder
5.685
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238126S14_GEN_1
Solar/Wind Helper
0.826
238152AF2-075_GEN
Solar/Wind Helper
0.708
238208AF1-136 C
Solar/Wind Helper
0.22
23546401DTGZ2-030
Solar/Wind Helper
0.089
237085AD2-009_GEN
Solar/Wind Helper
1.65
3138216PACIFIC
Solar/Wind Helper
0.044
316411AF1-147_GEN1
Solar/Wind Helper
0.889
316415AF1-147_GEN2
Solar/Wind Helper
0.889
23750501ELLIOTTS
Solar/Wind Helper
0.637
959381AF2-229 GEN
Solar/Wind Helper
0.358
3141426STAFORD
Solar/Wind Helper
0.052
960921AF2-383 GEN
Solar/Wind Helper
0.182
205943AE1-185 GEN
Solar/Wind Helper
0.51
205932AD2-116_GEN
Solar/Wind Helper
0.509
205956AE1-196_GEN
Solar/Wind Helper
0.509
233935AB2-179 C
Solar/Wind Helper
1.27
232436AB1-176 C
Solar/Wind Helper
0.044
233923SMA
Solar/Wind Helper
0.959
234033AF1-007_GEN
Solar/Wind Helper
7.028
233990AG1-397 GEN
Solar/Wind Helper
0.03
232432Z2-076 GEN
Solar/Wind Helper
0.067
964001AG1-254 GEN
Solar/Wind Helper
0.956
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.115
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.08
203975AE1-071-GEN
Solar/Wind Helper
2.5
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.29
219620RIDERU C
Solar/Wind Helper
0.001
316164AC1-076 GEN
Solar/Wind Helper
1.097
20675528CPH_W2-050
Solar/Wind Helper
0.087
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
218524CNTRALGAS1 C
Solar/Wind Helper
0.161
966261AG1-495 GEN
Solar/Wind Helper
0.081
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20675928HOL_W4-097
Solar/Wind Helper
0.05
20674828DL_W4-046
Solar/Wind Helper
0.008
207484AF2-139 C O1
Solar/Wind Helper
0.084
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.137
20675128HRM_W1-127
Solar/Wind Helper
0.03
209116AE2-175 GEN
Solar/Wind Helper
1.781
24318805MLG1
50/50
10.098
23559001PLEAS1
50/50
6.112
270051AF1-062 GEN
50/50
11.831
23684201S70BUS2
50/50
0.171
270475AD2-096_GEN
50/50
7.147
970153AG2-106 GEN
Solar/Wind Harmer
17.867
961921AG1-034 GEN
Solar/Wind Harmer
15.607
241955AC1-078 GEN
Solar/Wind Harmer
8.813
24721905FLATG4
Adder
23.946
241974AD2-163_GEN2
Solar/Wind Harmer
2.331
942051AE2-217 GEN
Solar/Wind Harmer
21.048
960801AF2-371 GEN
Solar/Wind Harmer
2.948
964871AG1-351 GEN
Solar/Wind Harmer
2.036
970605AG2-385 GEN
Solar/Wind Harmer
6.24
942871AE2-306 GEN
Solar/Wind Harmer
1.047
270391AF1-285 GEN3
Solar/Wind Harmer
0.537
253338AC1-165 GEN
Solar/Wind Harmer
1.242
253333AC1-068 GEN
Solar/Wind Harmer
1.197
270485AE1-090_GEN
Solar/Wind Harmer
0.69
270273AD2-016 GEN
Solar/Wind Harmer
3.033
972173AH1-669 GEN
Solar/Wind Harmer
5.671
270291AC1-194 GEN
Solar/Wind Harmer
11.744
253415AE1-040 GEN
Solar/Wind Harmer
1.248
270512AE1-227 GEN2
Solar/Wind Harmer
2.315
970065AG2-057 GEN
Solar/Wind Harmer
1.09
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.065
957541AF2-048 GEN
Solar/Wind Harmer
1.721
253406AD2-031_GEN
Solar/Wind Harmer
1.388
270491AE1-102 GEN2
Solar/Wind Harmer
1.404
270377AD1-106 GEN
Solar/Wind Harmer
6.655
971191AH1-055 GEN
Solar/Wind Harmer
23.692
253316AC1-085 GEN3
Solar/Wind Harmer
9.013
253433AC1-085 GEN1
Solar/Wind Harmer
5.721
946181AF1-283 GEN
Solar/Wind Harmer
13.988
270191TR4_S_V150
Solar/Wind Harmer
3.223
270247TR4_N_V136
Solar/Wind Harmer
0.914
959331AF2-224 GEN
Solar/Wind Harmer
10.743
965021AG1-366 GEN
Solar/Wind Harmer
2.498
270588AE1-091_GEN
Solar/Wind Harmer
11.792
958091AF2-103 GEN
Solar/Wind Harmer
0.173
944531AF1-118 GEN
Solar/Wind Harmer
37.418
270043AE2-236 GEN
Solar/Wind Harmer
5.874
270258AD1-119 GEN
Solar/Wind Harmer
2.962
971617AH1-308 GEN
Solar/Wind Harmer
6.179
25196608WSDLE5
Adder
9.087
252510AF1-249 C
Solar/Wind Harmer
0.443
962031AG1-047 GEN
Solar/Wind Harmer
3.204
957741AF2-068 GEN
Solar/Wind Harmer
15.899
25194608D.CRK4
Adder
1.742
270222AC2-111 GEN
Solar/Wind Harmer
8.63
970031AG2-029 GEN
Solar/Wind Harmer
31.748
270044AE2-322 C
Solar/Wind Harmer
1.39
270404AC1-167 GEN
Solar/Wind Harmer
1.158
24642205MAYFLWER
Adder
0.665
25196008MFTGT1
Adder
1.406
247604X1-042
Adder
0.433
274752CRETE EC ;2U
Adder
8.485
274753CRETE EC ;3U
Adder
8.485
274772LINCOLN ;3U
Adder
8.684
274724RIVER EC ;11
Adder
18.221
24728705AND G3
Adder
8.223
274802UNIV PARK;5U
Adder
5.976
24728505AND G1
Adder
3.932
274826FISK ;BP
Adder
11.216
274800UNIV PARK;3U
Adder
5.972
972038AH1-567 GEN2
Adder
0.374
972228AH1-698 GEN2
Adder
3.794
274676JOLIET 29;8U
Adder
30.215
274729ELWOOD EC;1P
Adder
16.784
274730ELWOOD EC;6P
Adder
16.784
274734ELWOOD EC;8P
Adder
16.784
274736ELWOOD EC;9P
Adder
16.784
274682WAUKEGAN ;7U
Adder
9.459
964991AG1-363 GEN
Solar/Wind Helper
5.14
316097T157 G90
Solar/Wind Helper
1.505
23750701CROSSCHOOL
Solar/Wind Helper
1.501
238118U2-030_1
Solar/Wind Helper
0.341
238127S14_GEN_2
Solar/Wind Helper
0.826
238148AE2-230_GEN2
Solar/Wind Helper
0.497
237080AD1-060 GEN
Solar/Wind Helper
0.342
237038AE2-054 C
Solar/Wind Helper
0.272
235062AE1-101 C1
Solar/Wind Helper
1.661
23779801AA1-109
Solar/Wind Helper
0.193
237048AF1-022 C
Solar/Wind Helper
0.177
223401AF1-299 GEN
Solar/Wind Helper
0.368
316006AB2-029 C
Solar/Wind Helper
0.117
966131AG1-482 GEN
Solar/Wind Helper
0.077
233930AB2-032 GEN
Solar/Wind Helper
0.381
233915AB1-141 GEN
Solar/Wind Helper
0.503
232422X3-066 FULL
Solar/Wind Helper
0.114
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
233998TM1NIN_3.36
Solar/Wind Helper
0.262
232404W1-003 C
Solar/Wind Helper
0.508
232428Y3-058 C
Solar/Wind Helper
0.338
232434Z2-077 GEN
Solar/Wind Helper
0.127
233954AC2-188 GEN
Solar/Wind Helper
0.233
233950AC2-186 GEN
Solar/Wind Helper
0.116
233972AC1-094 C
Solar/Wind Helper
0.303
316045AC1-158 PL2
Solar/Wind Helper
4.142
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.23
228728W1-130C
Solar/Wind Helper
0.054
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219904AC1-010 C
Solar/Wind Helper
0.06
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.131
20720728JCB_W1-129
Solar/Wind Helper
0.057
316254AC1-120 GEN1
Solar/Wind Helper
1.061
207445AB1-138_GEN
Solar/Wind Helper
0.104
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.31
20715228NPK_W1-113
Solar/Wind Helper
0.078
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.496
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
207437AD2-070 GEN
Solar/Wind Helper
0.138
207518AF1-320_GEN
Solar/Wind Helper
1.573
20671928W4-073
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.03
970513AG2-328 GEN
Solar/Wind Harmer
3.726
970517AG2-330 GEN
Solar/Wind Harmer
3.379
965011AG1-365 GEN
Solar/Wind Harmer
10.743
24695305TIMB G C
Solar/Wind Harmer
5.899
965651AG1-433 GEN
Solar/Wind Harmer
5.811
958861AF2-177 GEN
Solar/Wind Harmer
11.606
247536S-71 GEN
Solar/Wind Harmer
4.292
25194608D.CRK4
Adder
1.742
945371AF1-202 GEN
Solar/Wind Harmer
7.39
252507AC2-088 GEN
Solar/Wind Harmer
1.898
270063AE2-323 C
Solar/Wind Harmer
2.329
25196808ZIMRHP
Adder
79.816
24639705ELKHART HY
Adder
0.161
25196008MFTGT1
Adder
1.452
274751CRETE EC ;1U
Adder
8.485
274754CRETE EC ;4U
Adder
8.485
274773LINCOLN ;4U
Adder
8.684
274774LINCOLN ;5U
Adder
8.684
274723RIVER EC ;12
Adder
18.437
274812UNIV PK N;8U
Adder
5.144
24728605AND G2
Adder
3.932
274801UNIV PARK;4U
Adder
5.972
274676JOLIET 29;8U
Adder
31.334
274732ELWOOD EC;7P
Adder
16.784
274674JOLIET 9 ;6U
Adder
15.72
274745AC1-111 GEN9
Adder
5.685
970091AG2-072 GEN
Adder
77.715
316095T157 G97
Solar/Wind Helper
1.505
23583801GRNGAP
Solar/Wind Helper
5.607
238185AF2-356 C
Solar/Wind Helper
2.642
238108AE1-109 GEN1
Solar/Wind Helper
0.114
235054AD2-180 GEN
Solar/Wind Helper
2.025
235531U2-073 GEN
Solar/Wind Helper
3.278
238117U2-030
Solar/Wind Helper
0.341
238147AE2-230_GEN1
Solar/Wind Helper
0.495
238149AF1-291A_GEN
Solar/Wind Helper
0.141
237061AD1-155 GEN
Solar/Wind Helper
0.053
23751201ROTHROCK
Solar/Wind Helper
0.819
238221AF1-254 C O1
Solar/Wind Helper
0.275
23562501BACKB
Solar/Wind Helper
1.001
235067AD1-061 GEN
Solar/Wind Helper
0.496
23751101LEADS_P59
Solar/Wind Helper
1.388
237030AB1-096 C
Solar/Wind Helper
0.071
3141196NOKESVL
Solar/Wind Helper
1.033
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.346
223402AF1-300 C
Solar/Wind Helper
0.368
205917AD1-020 ES
Solar/Wind Helper
0.369
233982AB2-133 GEN
Solar/Wind Helper
0.358
233918AB1-142 GEN
Solar/Wind Helper
0.503
233994AC2-023 GEN
Solar/Wind Helper
0.962
233996TM1833_GEN
Solar/Wind Helper
0.262
233997TMININ_4.2
Solar/Wind Helper
0.262
232406W1-004 FULL
Solar/Wind Helper
0.508
233940AF2-379 C
Solar/Wind Helper
0.062
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.233
233971AC1-093 C
Solar/Wind Helper
0.358
316044AC1-158 PL1
Solar/Wind Helper
1.294
316450AC1-158 RIC
Solar/Wind Helper
0.345
230430AE1-229_GEN
Solar/Wind Helper
3.376
230415AB2-049 C
Solar/Wind Helper
0.03
228729W2-030 C
Solar/Wind Helper
0.111
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.15
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
219348LDSOLAR C
Solar/Wind Helper
0.115
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.063
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.354
219276PARKLANDSO C
Solar/Wind Helper
0.089
20714528FRN_Y2-051
Solar/Wind Helper
0.057
20720528MAN_W1-024
Solar/Wind Helper
0.028
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.027
219249CENTRALDIV C
Solar/Wind Helper
0.01
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.089
970245AG2-165 GEN
Solar/Wind Harmer
3.726
LAGNLTFEXP_LAGN->PJM
CLTF
14.855
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.816
TVALTFEXP_TVA->PJM
CLTF
7.302
CPLELTFEXP_CPLE->PJM
CLTF
0.627
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.944
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.216
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.135
MECLTFEXP_MEC->PJM
CLTF
15.918
SIGELTFEXP_SIGE->PJM
CLTF
0.506
NYPJM->LTFIMP_NY
CLTF
4.803
LGEELTFEXP_LGEE->PJM
CLTF
6.756
WECLTFEXP_WEC->PJM
CLTF
3.828
AG2-052LTFEXP_AG2-052->PJM
LTF
0.24
AH1-155LTFEXP_AH1-155->PJM
LTF
0.36

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P2-3_MP-500-014_SRT-A


Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:132.9 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5039.69
MW Contribution:0.86
Bus #Bus NameTypeMW Contribution
270119AB2-067 GEN1
50/50
7.063
270120AB2-067 GEN2
50/50
7.063
24318905MLG2
50/50
7.074
270471AD2-092_GEN
Solar/Wind Harmer
4.466
946101AF1-275 GEN
Solar/Wind Harmer
1.816
942861AE2-305 GEN
Solar/Wind Harmer
9.089
970077AG2-063 GEN
Solar/Wind Harmer
6.24
270224U2-072_GEN2
Solar/Wind Harmer
2.282
270227U2-072_GEN3
Solar/Wind Harmer
2.282
270228U2-072_GEN4
Solar/Wind Harmer
2.282
270231U2-072_GEN5
Solar/Wind Harmer
2.282
938701AE1-092 GEN
Solar/Wind Harmer
23.829
964601AG1-323 GEN
Solar/Wind Harmer
3.66
964601AG1-323 GEN
Solar/Wind Harmer
1.702
270518AE2-148 GEN
Solar/Wind Harmer
13.889
972269AH1-719 GEN
Adder
2.587
972159AH1-661 GEN
Adder
1.119
253378AE2-206_GEN
Solar/Wind Harmer
4.007
276820AF1-078_GEN
Solar/Wind Harmer
1.78
971199AH1-059 GEN
Solar/Wind Harmer
4.433
241960AC2-195 GEN
Solar/Wind Harmer
3.073
25326509SID D
Adder
1.452
970879AG2-548 GEN
Solar/Wind Harmer
6.78
971073AG2-665 GEN
Solar/Wind Harmer
6.78
971073AG2-665 GEN
Solar/Wind Harmer
4.73
25326109MON D
Adder
1.444
25322209TAIT E
Adder
10.653
25322209TAIT E
Adder
10.414
971201AH1-060 GEN
Solar/Wind Harmer
2.181
253370AE2-315 SEC1
Adder
2.184
253394AE2-221_GEN
Solar/Wind Harmer
4.918
253398AE2-221_GEN2
Solar/Wind Harmer
4.918
246938BC-WTG3
Solar/Wind Harmer
4.299
246937BC-WTG2
Solar/Wind Harmer
4.226
971231AH1-075 GEN
Solar/Wind Harmer
0.862
253317AC1-085 GEN4
Solar/Wind Harmer
9.013
970611AG2-400 GEN
Solar/Wind Harmer
10.743
270007AE1-245 C
Solar/Wind Harmer
6.358
942801AE2-298 GEN
Solar/Wind Harmer
1.622
962581AG1-107 GEN
Solar/Wind Harmer
5.365
961491AF2-440 GEN
Solar/Wind Harmer
2.229
25183208HLCRTG
Solar/Wind Harmer
6.449
944541AF1-119 GEN
Solar/Wind Harmer
4.453
960971AF2-388 GEN
Solar/Wind Harmer
11.621
942221AE2-234 GEN
Solar/Wind Harmer
0.778
252519AF1-045_GEN
Solar/Wind Harmer
6.447
252516AE2-318_GEN
Solar/Wind Harmer
4.918
247621Y3-024
Adder
0.256
970883AG2-550 GEN
Solar/Wind Harmer
10.602
970885AG2-551 GEN
Solar/Wind Harmer
2.465
270201AC2-176 GEN
Solar/Wind Harmer
5.449
25194408D.CRK1
Adder
8.013
25194508D.CRK3
Adder
1.498
964611AG1-324 GEN
Solar/Wind Harmer
1.248
964611AG1-324 GEN
Solar/Wind Harmer
0.554
252509AD1-136 GEN
Solar/Wind Harmer
0.271
247620Y3-023
Adder
0.484
24728805RICHG1
Adder
3.968
24728905RICHG2
Adder
3.968
274770LINCOLN ;1U
Adder
8.684
274771LINCOLN ;2U
Adder
8.684
274808UNIV PK N;4U
Adder
5.122
274803UNIV PARK;6U
Adder
5.976
972259AH1-714 GEN
Adder
19.527
274674JOLIET 9 ;6U
Adder
15.72
274696ROCKY RD ;4P
Adder
11.549
274695ROCKY RD ;2P
Adder
11.282
274693ROCKY RD ;1P
Adder
11.171
274697ROCKY RD ;3P
Adder
3.065
23585401KL_K28_T16
Solar/Wind Helper
1.478
238120AE2-309 GEN
Solar/Wind Helper
0.524
238175AF1-290_GEN
Solar/Wind Helper
0.153
238169AE2-226 GEN1
Solar/Wind Helper
0.702
238170AE2-226 GEN2
Solar/Wind Helper
0.702
235020AA1-095 C
Solar/Wind Helper
0.053
23777901MDS_W4-102
Solar/Wind Helper
0.177
237034AC2-136 C
Solar/Wind Helper
0.227
237002AB1-128_GEN
Solar/Wind Helper
0.443
235063AE1-101 C2
Solar/Wind Helper
1.661
237001AB1-127_GEN
Solar/Wind Helper
0.442
23777801MSM_W1-116
Solar/Wind Helper
0.114
237025AB1-124 C
Solar/Wind Helper
0.164
237006AB1-125 GEN
Solar/Wind Helper
0.123
226929AD2-058 GEN
Solar/Wind Helper
0.099
205916AD1-020 GEN
Solar/Wind Helper
1.715
20390526W1-045 C
Solar/Wind Helper
0.35
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
233987AB2-037 GEN
Solar/Wind Helper
2.344
233933AB2-153 GEN
Solar/Wind Helper
0.233
232424Y1-079 C
Solar/Wind Helper
0.116
233944AB2-135 GEN
Solar/Wind Helper
0.589
233946AB2-136 GEN
Solar/Wind Helper
0.569
234036AF2-325 C
Solar/Wind Helper
0.042
233901CHERRYDALE C
Solar/Wind Helper
0.233
232408W1-005 C
Solar/Wind Helper
0.508
232410W1-006 C
Solar/Wind Helper
0.508
233939AC1-091 C
Solar/Wind Helper
0.35
233970AC1-092 C
Solar/Wind Helper
0.35
315651AD1-115 GEN
Solar/Wind Helper
0.785
316447AC1-158 HLD
Solar/Wind Helper
2.848
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.04
219921AF1-264
Solar/Wind Helper
0.051
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.082
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.19
20716928W4-060COL
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.016
20673828FLE_V3-070
Solar/Wind Helper
0.091
207442AE1-156 GEN
Solar/Wind Helper
0.326
20676128MHD_W3-029
Solar/Wind Helper
0.096
20671828STAW2-080
Solar/Wind Helper
0.027
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
207471AF2-354 C
Solar/Wind Helper
0.169
20674928WA_W3-044
Solar/Wind Helper
0.098
964851AG1-348 GEN
Solar/Wind Helper
0.081
20676228FRD_X1-012
Solar/Wind Helper
0.092
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.045
211065PSPA IPP
Solar/Wind Helper
0.152
211065PSPA IPP
Solar/Wind Helper
0.152
970321AG2-212 GEN
Solar/Wind Harmer
3.726
962771AG1-126 GEN
Solar/Wind Harmer
40.976
972239AH1-704 GEN
Adder
2.69
270054AF2-122 C O1
Solar/Wind Harmer
3.996
270459AD2-067 GEN
Solar/Wind Harmer
10.248
961821AG1-024 GEN
Solar/Wind Harmer
10.404
270520AE2-214 GEN
Solar/Wind Harmer
7.276
270284AF1-227 GEN1
Solar/Wind Harmer
6.79
270286AF1-227 GEN2
Solar/Wind Harmer
2.512
270287AF1-227 GEN3
Solar/Wind Harmer
2.512
253383AE2-342_GEN
Solar/Wind Harmer
1.045
241973AD2-163_GEN1
Solar/Wind Harmer
2.331
945631AF1-228 GEN
Solar/Wind Harmer
5.463
943861AF1-054 GEN
Solar/Wind Harmer
4.486
943851AF1-053 GEN
Solar/Wind Harmer
2.168
270156DARBY CT1
Adder
10.419
270157DARBY CT2
Adder
10.393
270158DARBY CT3
Adder
10.228
970689AG2-444 GEN
Solar/Wind Harmer
18.827
270578AF1-285 GEN2
Solar/Wind Harmer
0.537
270432AC2-029 GEN
Solar/Wind Harmer
8.049
940611AE2-048 GEN
Solar/Wind Harmer
25.14
941391AE2-136 GEN
Solar/Wind Harmer
13.027
270302AB2-170 GEN
Solar/Wind Harmer
9.546
270317AD1-130_GEN
Solar/Wind Harmer
3.659
270269AC2-059
Solar/Wind Harmer
10.605
241972AD1-140 GEN
Solar/Wind Harmer
5.021
958581AF2-149 GEN
Solar/Wind Harmer
4.743
970179AG2-119 GEN
Solar/Wind Harmer
8.842
270340AC2-060 GEN
Solar/Wind Harmer
3.346
970879AG2-548 GEN
Solar/Wind Harmer
4.73
253372AE2-315 SEC3
Adder
2.065
253372AE2-315 SEC3
Adder
2.065
25306009OHH W.
Adder
3.133
253349AC2-067 GEN
Solar/Wind Harmer
5.407
253400AC2-068 GEN
Solar/Wind Harmer
2.174
957201AF2-014 GEN
Solar/Wind Harmer
4.898
270435AC2-044 GEN
Solar/Wind Harmer
2.16
965051AG1-369 GEN
Solar/Wind Harmer
5.365
965041AG1-368 GEN
Solar/Wind Harmer
10.719
247607V1-011 GEN
Solar/Wind Harmer
4.239
971567AH1-282 GEN
Solar/Wind Harmer
16.075
966831AG1-554 GEN
Solar/Wind Harmer
1.28
971989AH1-539 GEN
Solar/Wind Harmer
13.838
24729505KEY G4
Adder
6.925
963791AG1-232 GEN
Solar/Wind Harmer
14.411
270071AF1-092 GEN
Solar/Wind Harmer
15.995
971985AH1-537 GEN
Solar/Wind Harmer
18.996
958711AF2-162 GEN
Solar/Wind Harmer
1.076
270024AE2-089 GEN
Solar/Wind Harmer
4.988
270367AC2-061_GEN
Solar/Wind Harmer
3.378
965101AG1-375 GEN
Solar/Wind Harmer
10.618
971673AH1-337 GEN
Solar/Wind Harmer
4.878
252524AE2-267 GEN
Solar/Wind Harmer
1.672
25196408WSDLE3
Adder
9.354
25196308WSDLE2
Adder
9.273
25196208WSDLE1
Adder
9.25
25196708WSDLE6
Adder
9.227
25196508WSDLE4
Adder
8.994
971029AG2-637 GEN
Solar/Wind Harmer
15.905
270543AE2-219 C
Solar/Wind Harmer
5.429
961761AG1-017 GEN
Solar/Wind Harmer
0.454
945581AF1-223 GEN
Solar/Wind Harmer
4.803
270297AD1-101 GEN
Solar/Wind Harmer
2.947
944031AF1-071 GEN
Solar/Wind Harmer
1.064
25196108MFTGT2
Adder
1.6
25196108MFTGT2
Adder
1.486
274775LINCOLN ;6U
Adder
8.684
274776LINCOLN ;7U
Adder
8.684
274777LINCOLN ;8U
Adder
8.684
274814UNIV PK N;0U
Adder
5.189
274807UNIV PK N;3U
Adder
5.178
274805UNIV PK N;1U
Adder
5.156
274811UNIV PK N;7U
Adder
5.144
972037AH1-567 GEN1
Adder
0.188
274827FISK ;RP
Adder
7.949
972227AH1-698 GEN1
Adder
2.671
274687WILL CNTY;4U
Adder
28.551
274687WILL CNTY;4U
Adder
28.551
274675JOLIET 29;7U
Adder
31.334
274675JOLIET 29;7U
Adder
30.215
274731ELWOOD EC;2P
Adder
16.784
274733ELWOOD EC;3P
Adder
16.784
274735ELWOOD EC;4P
Adder
16.784
274728ELWOOD EC;5P
Adder
16.784
972203AH1-686 GEN
Adder
2.341
274746AC1-111 G10
Adder
5.685
274744AC1-111 GEN8
Adder
5.685
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238126S14_GEN_1
Solar/Wind Helper
0.826
238152AF2-075_GEN
Solar/Wind Helper
0.708
238208AF1-136 C
Solar/Wind Helper
0.22
23546401DTGZ2-030
Solar/Wind Helper
0.089
237085AD2-009_GEN
Solar/Wind Helper
1.65
3138216PACIFIC
Solar/Wind Helper
0.044
316411AF1-147_GEN1
Solar/Wind Helper
0.889
316415AF1-147_GEN2
Solar/Wind Helper
0.889
23750501ELLIOTTS
Solar/Wind Helper
0.637
959381AF2-229 GEN
Solar/Wind Helper
0.358
3141426STAFORD
Solar/Wind Helper
0.052
960921AF2-383 GEN
Solar/Wind Helper
0.182
205943AE1-185 GEN
Solar/Wind Helper
0.51
205932AD2-116_GEN
Solar/Wind Helper
0.509
205956AE1-196_GEN
Solar/Wind Helper
0.509
233935AB2-179 C
Solar/Wind Helper
1.27
232436AB1-176 C
Solar/Wind Helper
0.044
233923SMA
Solar/Wind Helper
0.959
234033AF1-007_GEN
Solar/Wind Helper
7.028
233990AG1-397 GEN
Solar/Wind Helper
0.03
232432Z2-076 GEN
Solar/Wind Helper
0.067
964001AG1-254 GEN
Solar/Wind Helper
0.956
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.115
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.08
203975AE1-071-GEN
Solar/Wind Helper
2.5
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.29
219620RIDERU C
Solar/Wind Helper
0.001
316164AC1-076 GEN
Solar/Wind Helper
1.097
20675528CPH_W2-050
Solar/Wind Helper
0.087
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
218524CNTRALGAS1 C
Solar/Wind Helper
0.161
966261AG1-495 GEN
Solar/Wind Helper
0.081
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20675928HOL_W4-097
Solar/Wind Helper
0.05
20674828DL_W4-046
Solar/Wind Helper
0.008
207484AF2-139 C O1
Solar/Wind Helper
0.084
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.137
20675128HRM_W1-127
Solar/Wind Helper
0.03
209116AE2-175 GEN
Solar/Wind Helper
1.781
24318805MLG1
50/50
10.098
23559001PLEAS1
50/50
6.112
270051AF1-062 GEN
50/50
11.831
23684201S70BUS2
50/50
0.171
270475AD2-096_GEN
50/50
7.147
970153AG2-106 GEN
Solar/Wind Harmer
17.867
961921AG1-034 GEN
Solar/Wind Harmer
15.607
241955AC1-078 GEN
Solar/Wind Harmer
8.813
24721905FLATG4
Adder
23.946
241974AD2-163_GEN2
Solar/Wind Harmer
2.331
942051AE2-217 GEN
Solar/Wind Harmer
21.048
960801AF2-371 GEN
Solar/Wind Harmer
2.948
964871AG1-351 GEN
Solar/Wind Harmer
2.036
970605AG2-385 GEN
Solar/Wind Harmer
6.24
942871AE2-306 GEN
Solar/Wind Harmer
1.047
270391AF1-285 GEN3
Solar/Wind Harmer
0.537
253338AC1-165 GEN
Solar/Wind Harmer
1.242
253333AC1-068 GEN
Solar/Wind Harmer
1.197
270485AE1-090_GEN
Solar/Wind Harmer
0.69
270273AD2-016 GEN
Solar/Wind Harmer
3.033
972173AH1-669 GEN
Solar/Wind Harmer
5.671
270291AC1-194 GEN
Solar/Wind Harmer
11.744
253415AE1-040 GEN
Solar/Wind Harmer
1.248
270512AE1-227 GEN2
Solar/Wind Harmer
2.315
970065AG2-057 GEN
Solar/Wind Harmer
1.09
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.065
957541AF2-048 GEN
Solar/Wind Harmer
1.721
253406AD2-031_GEN
Solar/Wind Harmer
1.388
270491AE1-102 GEN2
Solar/Wind Harmer
1.404
270377AD1-106 GEN
Solar/Wind Harmer
6.655
971191AH1-055 GEN
Solar/Wind Harmer
23.692
253316AC1-085 GEN3
Solar/Wind Harmer
9.013
253433AC1-085 GEN1
Solar/Wind Harmer
5.721
946181AF1-283 GEN
Solar/Wind Harmer
13.988
270191TR4_S_V150
Solar/Wind Harmer
3.223
270247TR4_N_V136
Solar/Wind Harmer
0.914
959331AF2-224 GEN
Solar/Wind Harmer
10.743
965021AG1-366 GEN
Solar/Wind Harmer
2.498
270588AE1-091_GEN
Solar/Wind Harmer
11.792
958091AF2-103 GEN
Solar/Wind Harmer
0.173
944531AF1-118 GEN
Solar/Wind Harmer
37.418
270043AE2-236 GEN
Solar/Wind Harmer
5.874
270258AD1-119 GEN
Solar/Wind Harmer
2.962
971617AH1-308 GEN
Solar/Wind Harmer
6.179
25196608WSDLE5
Adder
9.087
252510AF1-249 C
Solar/Wind Harmer
0.443
962031AG1-047 GEN
Solar/Wind Harmer
3.204
957741AF2-068 GEN
Solar/Wind Harmer
15.899
25194608D.CRK4
Adder
1.742
270222AC2-111 GEN
Solar/Wind Harmer
8.63
970031AG2-029 GEN
Solar/Wind Harmer
31.748
270044AE2-322 C
Solar/Wind Harmer
1.39
270404AC1-167 GEN
Solar/Wind Harmer
1.158
24642205MAYFLWER
Adder
0.665
25196008MFTGT1
Adder
1.406
247604X1-042
Adder
0.433
274752CRETE EC ;2U
Adder
8.485
274753CRETE EC ;3U
Adder
8.485
274772LINCOLN ;3U
Adder
8.684
274724RIVER EC ;11
Adder
18.221
24728705AND G3
Adder
8.223
274802UNIV PARK;5U
Adder
5.976
24728505AND G1
Adder
3.932
274826FISK ;BP
Adder
11.216
274800UNIV PARK;3U
Adder
5.972
972038AH1-567 GEN2
Adder
0.374
972228AH1-698 GEN2
Adder
3.794
274676JOLIET 29;8U
Adder
30.215
274729ELWOOD EC;1P
Adder
16.784
274730ELWOOD EC;6P
Adder
16.784
274734ELWOOD EC;8P
Adder
16.784
274736ELWOOD EC;9P
Adder
16.784
274682WAUKEGAN ;7U
Adder
9.459
964991AG1-363 GEN
Solar/Wind Helper
5.14
316097T157 G90
Solar/Wind Helper
1.505
23750701CROSSCHOOL
Solar/Wind Helper
1.501
238118U2-030_1
Solar/Wind Helper
0.341
238127S14_GEN_2
Solar/Wind Helper
0.826
238148AE2-230_GEN2
Solar/Wind Helper
0.497
237080AD1-060 GEN
Solar/Wind Helper
0.342
237038AE2-054 C
Solar/Wind Helper
0.272
235062AE1-101 C1
Solar/Wind Helper
1.661
23779801AA1-109
Solar/Wind Helper
0.193
237048AF1-022 C
Solar/Wind Helper
0.177
223401AF1-299 GEN
Solar/Wind Helper
0.368
316006AB2-029 C
Solar/Wind Helper
0.117
966131AG1-482 GEN
Solar/Wind Helper
0.077
233930AB2-032 GEN
Solar/Wind Helper
0.381
233915AB1-141 GEN
Solar/Wind Helper
0.503
232422X3-066 FULL
Solar/Wind Helper
0.114
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
233998TM1NIN_3.36
Solar/Wind Helper
0.262
232404W1-003 C
Solar/Wind Helper
0.508
232428Y3-058 C
Solar/Wind Helper
0.338
232434Z2-077 GEN
Solar/Wind Helper
0.127
233954AC2-188 GEN
Solar/Wind Helper
0.233
233950AC2-186 GEN
Solar/Wind Helper
0.116
233972AC1-094 C
Solar/Wind Helper
0.303
316045AC1-158 PL2
Solar/Wind Helper
4.142
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.23
228728W1-130C
Solar/Wind Helper
0.054
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219904AC1-010 C
Solar/Wind Helper
0.06
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.131
20720728JCB_W1-129
Solar/Wind Helper
0.057
316254AC1-120 GEN1
Solar/Wind Helper
1.061
207445AB1-138_GEN
Solar/Wind Helper
0.104
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.31
20715228NPK_W1-113
Solar/Wind Helper
0.078
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.496
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
207437AD2-070 GEN
Solar/Wind Helper
0.138
207518AF1-320_GEN
Solar/Wind Helper
1.573
20671928W4-073
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.03
970513AG2-328 GEN
Solar/Wind Harmer
3.726
970517AG2-330 GEN
Solar/Wind Harmer
3.379
270166AC1-044 GEN3
50/50
7.063
23559101PLEAS2
50/50
6.112
23684101S70BUS1
50/50
0.168
962761AG1-125 GEN
Solar/Wind Harmer
40.976
970149AG2-104 GEN
Solar/Wind Harmer
50.605
970155AG2-107 GEN
Solar/Wind Harmer
17.867
270349AD2-093_GEN
Solar/Wind Harmer
4.466
24721705FLATG2
Adder
23.946
270159DARBY CT4
Adder
10.253
970593AG2-378 GEN
Solar/Wind Harmer
2.311
270223U2-072_GEN1
Solar/Wind Harmer
2.282
270578AF1-285 GEN2
Solar/Wind Harmer
1.396
270391AF1-285 GEN3
Solar/Wind Harmer
1.396
253343AC1-166 GEN
Solar/Wind Harmer
1.242
253325AC1-069 GEN
Solar/Wind Harmer
1.197
270462AD2-086
Solar/Wind Harmer
7.941
971995AH1-542 GEN
Solar/Wind Harmer
12.507
270263AC1-001 GEN
Solar/Wind Harmer
1.177
270510AE1-227 GEN1
Solar/Wind Harmer
2.727
25326309TAIT D
Adder
1.197
241813AF1-122_GEN
Solar/Wind Harmer
6.978
960071AF2-298 GEN
Solar/Wind Harmer
5.44
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.065
927014AC1-188 GEN
Solar/Wind Harmer
1.725
246936BC-WTG1
Solar/Wind Harmer
4.226
270489AE1-102 GEN1
Solar/Wind Harmer
1.404
965421AG1-410 GEN
Solar/Wind Harmer
32.379
960001AF2-291 GEN
Solar/Wind Harmer
3.256
253432AC1-085 GEN2
Solar/Wind Harmer
0.288
946171AF1-282 GEN
Solar/Wind Harmer
10.76
247521TR3_G114
Solar/Wind Harmer
3.612
270246TR4_N_V150
Solar/Wind Harmer
0.914
965011AG1-365 GEN
Solar/Wind Harmer
10.743
24695305TIMB G C
Solar/Wind Harmer
5.899
965651AG1-433 GEN
Solar/Wind Harmer
5.811
958861AF2-177 GEN
Solar/Wind Harmer
11.606
247536S-71 GEN
Solar/Wind Harmer
4.292
25194608D.CRK4
Adder
1.742
945371AF1-202 GEN
Solar/Wind Harmer
7.39
252507AC2-088 GEN
Solar/Wind Harmer
1.898
270063AE2-323 C
Solar/Wind Harmer
2.329
25196808ZIMRHP
Adder
79.816
24639705ELKHART HY
Adder
0.161
25196008MFTGT1
Adder
1.452
274751CRETE EC ;1U
Adder
8.485
274754CRETE EC ;4U
Adder
8.485
274773LINCOLN ;4U
Adder
8.684
274774LINCOLN ;5U
Adder
8.684
274723RIVER EC ;12
Adder
18.437
274812UNIV PK N;8U
Adder
5.144
24728605AND G2
Adder
3.932
274801UNIV PARK;4U
Adder
5.972
274676JOLIET 29;8U
Adder
31.334
274732ELWOOD EC;7P
Adder
16.784
274674JOLIET 9 ;6U
Adder
15.72
274745AC1-111 GEN9
Adder
5.685
970091AG2-072 GEN
Adder
77.715
316095T157 G97
Solar/Wind Helper
1.505
23583801GRNGAP
Solar/Wind Helper
5.607
238185AF2-356 C
Solar/Wind Helper
2.642
238108AE1-109 GEN1
Solar/Wind Helper
0.114
235054AD2-180 GEN
Solar/Wind Helper
2.025
235531U2-073 GEN
Solar/Wind Helper
3.278
238117U2-030
Solar/Wind Helper
0.341
238147AE2-230_GEN1
Solar/Wind Helper
0.495
238149AF1-291A_GEN
Solar/Wind Helper
0.141
237061AD1-155 GEN
Solar/Wind Helper
0.053
23751201ROTHROCK
Solar/Wind Helper
0.819
238221AF1-254 C O1
Solar/Wind Helper
0.275
23562501BACKB
Solar/Wind Helper
1.001
235067AD1-061 GEN
Solar/Wind Helper
0.496
23751101LEADS_P59
Solar/Wind Helper
1.388
237030AB1-096 C
Solar/Wind Helper
0.071
3141196NOKESVL
Solar/Wind Helper
1.033
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.346
223402AF1-300 C
Solar/Wind Helper
0.368
205917AD1-020 ES
Solar/Wind Helper
0.369
233982AB2-133 GEN
Solar/Wind Helper
0.358
233918AB1-142 GEN
Solar/Wind Helper
0.503
233994AC2-023 GEN
Solar/Wind Helper
0.962
233996TM1833_GEN
Solar/Wind Helper
0.262
233997TMININ_4.2
Solar/Wind Helper
0.262
232406W1-004 FULL
Solar/Wind Helper
0.508
233940AF2-379 C
Solar/Wind Helper
0.062
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.233
233971AC1-093 C
Solar/Wind Helper
0.358
316044AC1-158 PL1
Solar/Wind Helper
1.294
316450AC1-158 RIC
Solar/Wind Helper
0.345
230430AE1-229_GEN
Solar/Wind Helper
3.376
230415AB2-049 C
Solar/Wind Helper
0.03
228729W2-030 C
Solar/Wind Helper
0.111
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.15
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
219348LDSOLAR C
Solar/Wind Helper
0.115
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.063
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.354
219276PARKLANDSO C
Solar/Wind Helper
0.089
20714528FRN_Y2-051
Solar/Wind Helper
0.057
20720528MAN_W1-024
Solar/Wind Helper
0.028
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.027
219249CENTRALDIV C
Solar/Wind Helper
0.01
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.089
970245AG2-165 GEN
Solar/Wind Harmer
3.726
LAGNLTFEXP_LAGN->PJM
CLTF
14.855
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.816
TVALTFEXP_TVA->PJM
CLTF
7.302
CPLELTFEXP_CPLE->PJM
CLTF
0.627
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.944
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.216
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.135
MECLTFEXP_MEC->PJM
CLTF
15.918
SIGELTFEXP_SIGE->PJM
CLTF
0.506
NYPJM->LTFIMP_NY
CLTF
4.803
LGEELTFEXP_LGEE->PJM
CLTF
6.756
WECLTFEXP_WEC->PJM
CLTF
3.828
AG2-052LTFEXP_AG2-052->PJM
LTF
0.24
AH1-155LTFEXP_AH1-155->PJM
LTF
0.36

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P1-2_MP-500-007A_SRT-A


Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P1-2_MP-500-007A_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:131.92 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5002.28
MW Contribution:0.86
Bus #Bus NameTypeMW Contribution
962771AG1-126 GEN
Solar/Wind Harmer
34.524
972239AH1-704 GEN
Adder
2.689
270054AF2-122 C O1
Solar/Wind Harmer
0.007
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
5.077
270520AE2-214 GEN
Solar/Wind Harmer
0.013
270284AF1-227 GEN1
Solar/Wind Harmer
0.011
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
270119AB2-067 GEN1
50/50
7.059
270120AB2-067 GEN2
50/50
7.059
24318905MLG2
50/50
7.071
270471AD2-092_GEN
Solar/Wind Harmer
0.006
942861AE2-305 GEN
Solar/Wind Harmer
6.335
970077AG2-063 GEN
Solar/Wind Harmer
4.631
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
938701AE1-092 GEN
Solar/Wind Harmer
12.917
971655AH1-328 GEN
Solar/Wind Harmer
2.854
964601AG1-323 GEN
Solar/Wind Harmer
3.215
964601AG1-323 GEN
Solar/Wind Harmer
2.143
270518AE2-148 GEN
Solar/Wind Harmer
0.691
972269AH1-719 GEN
Adder
2.584
972159AH1-661 GEN
Adder
1.118
253378AE2-206_GEN
Solar/Wind Harmer
0.004
276820AF1-078_GEN
Solar/Wind Harmer
0.002
970329AG2-216 GEN
Solar/Wind Harmer
3.354
971199AH1-059 GEN
Solar/Wind Harmer
3.09
241960AC2-195 GEN
Solar/Wind Harmer
0.006
25326509SID D
Adder
1.451
971073AG2-665 GEN
Solar/Wind Harmer
6.898
25326109MON D
Adder
1.443
25322209TAIT E
Adder
10.642
25322209TAIT E
Adder
10.403
971201AH1-060 GEN
Solar/Wind Harmer
1.52
253370AE2-315 SEC1
Adder
2.182
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
246938BC-WTG3
Solar/Wind Harmer
0.273
246937BC-WTG2
Solar/Wind Harmer
0.305
971231AH1-075 GEN
Solar/Wind Harmer
0.861
253317AC1-085 GEN4
Solar/Wind Harmer
0.005
970611AG2-400 GEN
Solar/Wind Harmer
7.488
970627AG2-408 GEN
Solar/Wind Harmer
2.246
270007AE1-245 C
Solar/Wind Harmer
0.002
962581AG1-107 GEN
Solar/Wind Harmer
0.002
25183208HLCRTG
Solar/Wind Harmer
0.012
944541AF1-119 GEN
Solar/Wind Harmer
0.497
960971AF2-388 GEN
Solar/Wind Harmer
4.347
970623AG2-406 GEN
Solar/Wind Harmer
1.356
942221AE2-234 GEN
Solar/Wind Harmer
0.037
252519AF1-045_GEN
Solar/Wind Harmer
6.44
252516AE2-318_GEN
Solar/Wind Harmer
5.712
247621Y3-024
Adder
0.255
970883AG2-550 GEN
Solar/Wind Harmer
7.389
970885AG2-551 GEN
Solar/Wind Harmer
2.463
270201AC2-176 GEN
Solar/Wind Harmer
0.001
25194408D.CRK1
Adder
8.004
25194508D.CRK3
Adder
1.496
970621AG2-405 GEN
Solar/Wind Harmer
1.351
964611AG1-324 GEN
Solar/Wind Harmer
0.553
252509AD1-136 GEN
Solar/Wind Harmer
0.037
970321AG2-212 GEN
Solar/Wind Harmer
3.191
270599AE1-208 GEN
Solar/Wind Harmer
6.737
270031AE2-169
Solar/Wind Harmer
4.042
270186AC1-089 GEN
Solar/Wind Harmer
0.004
270383AD1-128 GEN
Solar/Wind Harmer
0.004
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
970825AG2-519 GEN
Solar/Wind Harmer
8.127
247620Y3-023
Adder
0.484
960441AF2-335 GEN
Solar/Wind Harmer
7.33
270216AD2-079_GEN
Solar/Wind Harmer
0.001
971613AH1-306 GEN
Solar/Wind Harmer
3.512
24728805RICHG1
Adder
3.964
24728905RICHG2
Adder
3.964
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
14.589
961051AF2-396 GEN
Solar/Wind Harmer
9.726
270526AF1-158 GEN
Solar/Wind Harmer
0.009
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
9.095
965791AG1-447 GEN
Solar/Wind Harmer
6.67
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
970239AG2-162 GEN
Solar/Wind Harmer
1.797
274770LINCOLN ;1U
Adder
8.676
274771LINCOLN ;2U
Adder
8.676
966841AG1-555 GEN
Solar/Wind Harmer
0.81
274808UNIV PK N;4U
Adder
5.117
274803UNIV PARK;6U
Adder
5.97
274888KELLY CRK;1U
Solar/Wind Harmer
0.419
274887GEN-1.85
Solar/Wind Harmer
0.188
276843GEN-1.7
Solar/Wind Harmer
0.231
958011AF2-095 GEN
Solar/Wind Harmer
10.284
972259AH1-714 GEN
Adder
19.507
274674JOLIET 9 ;6U
Adder
15.704
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
970241AG2-163 GEN
Solar/Wind Harmer
4.144
958481AF2-142 GEN
Solar/Wind Harmer
10.621
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.958
971573AH1-285 GEN
Solar/Wind Harmer
1.319
274696ROCKY RD ;4P
Adder
11.537
274695ROCKY RD ;2P
Adder
11.271
274693ROCKY RD ;1P
Adder
11.16
274697ROCKY RD ;3P
Adder
3.062
958491AF2-143 GEN
Solar/Wind Harmer
10.588
274879MINONK ;1U
Solar/Wind Harmer
0.297
23585401KL_K28_T16
Solar/Wind Helper
1.482
238120AE2-309 GEN
Solar/Wind Helper
0.525
238175AF1-290_GEN
Solar/Wind Helper
0.153
238169AE2-226 GEN1
Solar/Wind Helper
0.701
238170AE2-226 GEN2
Solar/Wind Helper
0.701
235020AA1-095 C
Solar/Wind Helper
0.053
23777901MDS_W4-102
Solar/Wind Helper
0.177
237002AB1-128_GEN
Solar/Wind Helper
0.443
237034AC2-136 C
Solar/Wind Helper
0.227
235063AE1-101 C2
Solar/Wind Helper
1.659
237001AB1-127_GEN
Solar/Wind Helper
0.442
23777801MSM_W1-116
Solar/Wind Helper
0.114
237025AB1-124 C
Solar/Wind Helper
0.164
237006AB1-125 GEN
Solar/Wind Helper
0.123
226929AD2-058 GEN
Solar/Wind Helper
0.099
205916AD1-020 GEN
Solar/Wind Helper
1.713
20390526W1-045 C
Solar/Wind Helper
0.35
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
233987AB2-037 GEN
Solar/Wind Helper
2.342
233933AB2-153 GEN
Solar/Wind Helper
0.232
233944AB2-135 GEN
Solar/Wind Helper
0.588
232424Y1-079 C
Solar/Wind Helper
0.116
234036AF2-325 C
Solar/Wind Helper
0.042
233946AB2-136 GEN
Solar/Wind Helper
0.568
233901CHERRYDALE C
Solar/Wind Helper
0.232
232408W1-005 C
Solar/Wind Helper
0.507
232410W1-006 C
Solar/Wind Helper
0.507
233939AC1-091 C
Solar/Wind Helper
0.35
233970AC1-092 C
Solar/Wind Helper
0.35
315651AD1-115 GEN
Solar/Wind Helper
0.785
316447AC1-158 HLD
Solar/Wind Helper
2.845
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.04
219921AF1-264
Solar/Wind Helper
0.051
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.082
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.19
20716928W4-060COL
Solar/Wind Helper
0.051
218440SUMMTASSOC C
Solar/Wind Helper
0.016
20673828FLE_V3-070
Solar/Wind Helper
0.09
207442AE1-156 GEN
Solar/Wind Helper
0.326
20676128MHD_W3-029
Solar/Wind Helper
0.096
20671828STAW2-080
Solar/Wind Helper
0.027
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
207471AF2-354 C
Solar/Wind Helper
0.168
20674928WA_W3-044
Solar/Wind Helper
0.098
20676228FRD_X1-012
Solar/Wind Helper
0.092
964851AG1-348 GEN
Solar/Wind Helper
0.081
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.074
211065PSPA IPP
Solar/Wind Helper
0.151
211065PSPA IPP
Solar/Wind Helper
0.151
24318805MLG1
50/50
10.095
23559001PLEAS1
50/50
6.1
270051AF1-062 GEN
50/50
11.821
270475AD2-096_GEN
50/50
7.141
970153AG2-106 GEN
Solar/Wind Harmer
22.046
961921AG1-034 GEN
Solar/Wind Harmer
7.615
241955AC1-078 GEN
Solar/Wind Harmer
0.007
24721905FLATG4
Adder
23.918
241974AD2-163_GEN2
Solar/Wind Harmer
0.006
942051AE2-217 GEN
Solar/Wind Harmer
14.671
970605AG2-385 GEN
Solar/Wind Harmer
4.899
270391AF1-285 GEN3
Solar/Wind Harmer
0.536
253338AC1-165 GEN
Solar/Wind Harmer
0.003
253333AC1-068 GEN
Solar/Wind Harmer
0.012
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270273AD2-016 GEN
Solar/Wind Harmer
0.821
972173AH1-669 GEN
Solar/Wind Harmer
3.952
270291AC1-194 GEN
Solar/Wind Harmer
6.106
253415AE1-040 GEN
Solar/Wind Harmer
0.003
270512AE1-227 GEN2
Solar/Wind Harmer
1.963
970065AG2-057 GEN
Solar/Wind Harmer
0.76
253370AE2-315 SEC1
Adder
2.182
253371AE2-315 SEC2
Adder
2.063
253406AD2-031_GEN
Solar/Wind Harmer
0.563
970191AG2-125 GEN
Solar/Wind Harmer
1.945
270491AE1-102 GEN2
Solar/Wind Harmer
0.979
270377AD1-106 GEN
Solar/Wind Harmer
2.855
971191AH1-055 GEN
Solar/Wind Harmer
19.26
253316AC1-085 GEN3
Solar/Wind Harmer
0.005
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
9.749
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.048
959331AF2-224 GEN
Solar/Wind Harmer
5.242
965021AG1-366 GEN
Solar/Wind Harmer
2.496
270588AE1-091_GEN
Solar/Wind Harmer
5.845
944531AF1-118 GEN
Solar/Wind Harmer
33.395
270043AE2-236 GEN
Solar/Wind Harmer
4.777
270258AD1-119 GEN
Solar/Wind Harmer
0.002
971617AH1-308 GEN
Solar/Wind Harmer
6.173
25196608WSDLE5
Adder
9.077
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
252510AF1-249 C
Solar/Wind Harmer
0.057
957741AF2-068 GEN
Solar/Wind Harmer
11.081
25194608D.CRK4
Adder
1.74
270222AC2-111 GEN
Solar/Wind Harmer
3.739
970031AG2-029 GEN
Solar/Wind Harmer
4.795
270404AC1-167 GEN
Solar/Wind Harmer
0.003
970513AG2-328 GEN
Solar/Wind Harmer
3.191
970517AG2-330 GEN
Solar/Wind Harmer
19.146
970349AG2-230 GEN
Solar/Wind Harmer
11.025
946031AF1-268 GEN
Solar/Wind Harmer
6.992
958821AF2-173 GEN
Solar/Wind Harmer
10.273
270004AE1-209 GEN
Solar/Wind Harmer
1.59
270437AC2-090 C
Solar/Wind Harmer
0.003
247643Z2-116 C
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.804
970291AG2-192 GEN
Solar/Wind Harmer
0.731
247642Z2-115 C
Solar/Wind Harmer
0.003
945111AF1-176 GEN
Solar/Wind Harmer
5.919
24642205MAYFLWER
Adder
0.665
25196008MFTGT1
Adder
1.405
270356AE2-297 GEN
Solar/Wind Harmer
0.01
24441205WTRV SLR C
Solar/Wind Harmer
0
247604X1-042
Adder
0.433
270535AF1-215 GEN1
Solar/Wind Harmer
0.009
964401AG1-302 GEN
Solar/Wind Harmer
0.001
970217AG2-149 GEN
Solar/Wind Harmer
6.268
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
7.196
970243AG2-164 GEN
Solar/Wind Harmer
4.205
970519AG2-331 GEN
Solar/Wind Harmer
18.687
970699AG2-449 GEN
Solar/Wind Harmer
1.797
274752CRETE EC ;2U
Adder
8.477
274753CRETE EC ;3U
Adder
8.477
958171AF2-111 GEN
Solar/Wind Harmer
17.94
274772LINCOLN ;3U
Adder
8.676
274724RIVER EC ;11
Adder
18.203
972167AH1-666 GEN
Solar/Wind Harmer
5.717
24728705AND G3
Adder
8.214
274802UNIV PARK;5U
Adder
5.97
24728505AND G1
Adder
3.927
276806AD2-047 C O1
Solar/Wind Harmer
4.047
970941AG2-585 GEN
Solar/Wind Harmer
8.927
274826FISK ;BP
Adder
11.205
274800UNIV PARK;3U
Adder
5.966
972038AH1-567 GEN2
Adder
0.373
972228AH1-698 GEN2
Adder
3.79
276897AD1-100 C
Solar/Wind Harmer
0.009
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
970707AG2-453 GEN
Solar/Wind Harmer
23.303
274676JOLIET 29;8U
Adder
30.185
276893AG1-478 C
Solar/Wind Harmer
0.282
274729ELWOOD EC;1P
Adder
16.768
274730ELWOOD EC;6P
Adder
16.768
274734ELWOOD EC;8P
Adder
16.768
274736ELWOOD EC;9P
Adder
16.768
943121AE2-341 GEN
Solar/Wind Harmer
11.888
943591AF1-030 GEN
Solar/Wind Harmer
7.906
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
270541AE2-072 C
Solar/Wind Harmer
0.009
274682WAUKEGAN ;7U
Adder
9.728
276805AD2-038 GEN
Solar/Wind Harmer
0.002
964991AG1-363 GEN
Solar/Wind Helper
5.136
316097T157 G90
Solar/Wind Helper
1.504
23750701CROSSCHOOL
Solar/Wind Helper
1.502
238118U2-030_1
Solar/Wind Helper
0.341
238127S14_GEN_2
Solar/Wind Helper
0.827
238148AE2-230_GEN2
Solar/Wind Helper
0.497
237080AD1-060 GEN
Solar/Wind Helper
0.342
237038AE2-054 C
Solar/Wind Helper
0.272
235062AE1-101 C1
Solar/Wind Helper
1.659
23779801AA1-109
Solar/Wind Helper
0.193
237048AF1-022 C
Solar/Wind Helper
0.177
223401AF1-299 GEN
Solar/Wind Helper
0.367
316006AB2-029 C
Solar/Wind Helper
0.117
966131AG1-482 GEN
Solar/Wind Helper
0.137
233930AB2-032 GEN
Solar/Wind Helper
0.381
233915AB1-141 GEN
Solar/Wind Helper
0.502
232422X3-066 FULL
Solar/Wind Helper
0.114
232428Y3-058 C
Solar/Wind Helper
0.338
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
233998TM1NIN_3.36
Solar/Wind Helper
0.261
232404W1-003 C
Solar/Wind Helper
0.507
232434Z2-077 GEN
Solar/Wind Helper
0.127
233954AC2-188 GEN
Solar/Wind Helper
0.232
233950AC2-186 GEN
Solar/Wind Helper
0.116
233972AC1-094 C
Solar/Wind Helper
0.302
316045AC1-158 PL2
Solar/Wind Helper
4.138
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.23
228728W1-130C
Solar/Wind Helper
0.054
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219904AC1-010 C
Solar/Wind Helper
0.06
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.131
20720728JCB_W1-129
Solar/Wind Helper
0.057
316254AC1-120 GEN1
Solar/Wind Helper
1.059
207445AB1-138_GEN
Solar/Wind Helper
0.104
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.13
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.31
20715228NPK_W1-113
Solar/Wind Helper
0.078
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.495
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
207437AD2-070 GEN
Solar/Wind Helper
0.138
207518AF1-320_GEN
Solar/Wind Helper
1.571
20671928W4-073
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.029
253383AE2-342_GEN
Solar/Wind Harmer
0.003
241973AD2-163_GEN1
Solar/Wind Harmer
0.006
945631AF1-228 GEN
Solar/Wind Harmer
0
943861AF1-054 GEN
Solar/Wind Harmer
3.127
943851AF1-053 GEN
Solar/Wind Harmer
2.166
270156DARBY CT1
Adder
10.409
270157DARBY CT2
Adder
10.383
270158DARBY CT3
Adder
10.218
970689AG2-444 GEN
Solar/Wind Harmer
16.436
270578AF1-285 GEN2
Solar/Wind Harmer
0.536
270432AC2-029 GEN
Solar/Wind Harmer
3.553
940611AE2-048 GEN
Solar/Wind Harmer
19.602
941391AE2-136 GEN
Solar/Wind Harmer
11.042
270302AB2-170 GEN
Solar/Wind Harmer
0.005
270317AD1-130_GEN
Solar/Wind Harmer
0.011
971653AH1-327 GEN
Solar/Wind Harmer
1.117
270269AC2-059
Solar/Wind Harmer
0.005
241972AD1-140 GEN
Solar/Wind Harmer
0.854
970179AG2-119 GEN
Solar/Wind Harmer
6.883
270340AC2-060 GEN
Solar/Wind Harmer
0.009
970879AG2-548 GEN
Solar/Wind Harmer
6.898
253372AE2-315 SEC3
Adder
2.063
253372AE2-315 SEC3
Adder
2.063
25306009OHH W.
Adder
3.13
253349AC2-067 GEN
Solar/Wind Harmer
2.381
253400AC2-068 GEN
Solar/Wind Harmer
0.958
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
0.953
965051AG1-369 GEN
Solar/Wind Harmer
3.739
965041AG1-368 GEN
Solar/Wind Harmer
7.471
247607V1-011 GEN
Solar/Wind Harmer
0.001
971567AH1-282 GEN
Solar/Wind Harmer
11.206
971989AH1-539 GEN
Solar/Wind Harmer
3.215
963791AG1-232 GEN
Solar/Wind Harmer
10.044
24729505KEY G4
Adder
6.919
270071AF1-092 GEN
Solar/Wind Harmer
14.245
971985AH1-537 GEN
Solar/Wind Harmer
2.206
270024AE2-089 GEN
Solar/Wind Harmer
0.008
270367AC2-061_GEN
Solar/Wind Harmer
0.006
965101AG1-375 GEN
Solar/Wind Harmer
7.401
971673AH1-337 GEN
Solar/Wind Harmer
4.804
252524AE2-267 GEN
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
9.344
25196308WSDLE2
Adder
9.263
25196208WSDLE1
Adder
9.24
25196708WSDLE6
Adder
9.217
25196508WSDLE4
Adder
8.984
971029AG2-637 GEN
Solar/Wind Harmer
11.085
270543AE2-219 C
Solar/Wind Harmer
0.004
945581AF1-223 GEN
Solar/Wind Harmer
0.001
270297AD1-101 GEN
Solar/Wind Harmer
0.002
971347AH1-153 GEN
Solar/Wind Harmer
11.025
971609AH1-304 GEN
Solar/Wind Harmer
1.2
270240V3-007_GEN2
Solar/Wind Harmer
0.002
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
970115AG2-085 GEN
Solar/Wind Harmer
2.932
270594AE1-207 GEN
Solar/Wind Harmer
8.194
970289AG2-191 GEN
Solar/Wind Harmer
1.389
971771AH1-392 GEN
Solar/Wind Harmer
7.306
971619AH1-309 GEN
Solar/Wind Harmer
3.285
971769AH1-391 GEN
Solar/Wind Harmer
8.134
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
25196108MFTGT2
Adder
1.599
25196108MFTGT2
Adder
1.484
270536AF1-215 GEN2
Solar/Wind Harmer
0.009
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
4.302
971549AH1-272 GEN
Solar/Wind Harmer
14.865
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
8.676
274776LINCOLN ;7U
Adder
8.676
274777LINCOLN ;8U
Adder
8.676
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
274814UNIV PK N;0U
Adder
5.184
274807UNIV PK N;3U
Adder
5.173
274805UNIV PK N;1U
Adder
5.15
274811UNIV PK N;7U
Adder
5.139
972037AH1-567 GEN1
Adder
0.187
960591AF2-350 GEN
Solar/Wind Harmer
7.141
274827FISK ;RP
Adder
7.941
972227AH1-698 GEN1
Adder
2.669
963841AG1-237 GEN
Solar/Wind Harmer
3.09
972163AH1-664 GEN
Solar/Wind Harmer
7.933
972165AH1-665 GEN
Solar/Wind Harmer
6.354
274687WILL CNTY;4U
Adder
28.523
274687WILL CNTY;4U
Adder
28.523
274675JOLIET 29;7U
Adder
31.303
274675JOLIET 29;7U
Adder
30.185
274731ELWOOD EC;2P
Adder
16.768
274733ELWOOD EC;3P
Adder
16.768
274735ELWOOD EC;4P
Adder
16.768
274728ELWOOD EC;5P
Adder
16.768
970833AG2-524 GEN
Solar/Wind Harmer
7.824
970833AG2-524 GEN
Solar/Wind Harmer
5.216
274746AC1-111 G10
Adder
5.679
274744AC1-111 GEN8
Adder
5.679
972203AH1-686 GEN
Adder
2.338
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
276868AE1-113 GEN
Solar/Wind Harmer
1.414
276882AE2-255 GEN
Solar/Wind Harmer
0.824
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238126S14_GEN_1
Solar/Wind Helper
0.827
238152AF2-075_GEN
Solar/Wind Helper
0.707
238208AF1-136 C
Solar/Wind Helper
0.22
23546401DTGZ2-030
Solar/Wind Helper
0.089
237085AD2-009_GEN
Solar/Wind Helper
1.649
3138216PACIFIC
Solar/Wind Helper
0.044
316411AF1-147_GEN1
Solar/Wind Helper
0.888
316415AF1-147_GEN2
Solar/Wind Helper
0.888
23750501ELLIOTTS
Solar/Wind Helper
0.638
959381AF2-229 GEN
Solar/Wind Helper
0.357
3141426STAFORD
Solar/Wind Helper
0.052
960921AF2-383 GEN
Solar/Wind Helper
0.364
205943AE1-185 GEN
Solar/Wind Helper
0.509
205932AD2-116_GEN
Solar/Wind Helper
0.509
205956AE1-196_GEN
Solar/Wind Helper
0.509
233935AB2-179 C
Solar/Wind Helper
1.269
232436AB1-176 C
Solar/Wind Helper
0.044
233923SMA
Solar/Wind Helper
0.958
233990AG1-397 GEN
Solar/Wind Helper
0.27
232432Z2-076 GEN
Solar/Wind Helper
0.067
234033AF1-007_GEN
Solar/Wind Helper
7.02
964001AG1-254 GEN
Solar/Wind Helper
0.955
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.115
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.08
203975AE1-071-GEN
Solar/Wind Helper
2.498
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.29
219620RIDERU C
Solar/Wind Helper
0.001
316164AC1-076 GEN
Solar/Wind Helper
1.096
20675528CPH_W2-050
Solar/Wind Helper
0.087
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
218524CNTRALGAS1 C
Solar/Wind Helper
0.16
966261AG1-495 GEN
Solar/Wind Helper
0.081
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20675928HOL_W4-097
Solar/Wind Helper
0.05
207484AF2-139 C O1
Solar/Wind Helper
0.084
20674828DL_W4-046
Solar/Wind Helper
0.008
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.136
20675128HRM_W1-127
Solar/Wind Helper
0.029
209116AE2-175 GEN
Solar/Wind Helper
1.778
270166AC1-044 GEN3
50/50
7.059
23559101PLEAS2
50/50
6.1
962761AG1-125 GEN
Solar/Wind Harmer
34.524
970149AG2-104 GEN
Solar/Wind Harmer
37.287
970155AG2-107 GEN
Solar/Wind Harmer
22.046
270349AD2-093_GEN
Solar/Wind Harmer
0.006
24721705FLATG2
Adder
23.918
270159DARBY CT4
Adder
10.243
970593AG2-378 GEN
Solar/Wind Harmer
1.812
270223U2-072_GEN1
Solar/Wind Harmer
0.001
253343AC1-166 GEN
Solar/Wind Harmer
0.003
253325AC1-069 GEN
Solar/Wind Harmer
0.012
270462AD2-086
Solar/Wind Harmer
0.017
971995AH1-542 GEN
Solar/Wind Harmer
2.906
270263AC1-001 GEN
Solar/Wind Harmer
0.786
270510AE1-227 GEN1
Solar/Wind Harmer
1.963
25326309TAIT D
Adder
1.196
241813AF1-122_GEN
Solar/Wind Harmer
3.405
960071AF2-298 GEN
Solar/Wind Harmer
3.786
253370AE2-315 SEC1
Adder
2.182
253371AE2-315 SEC2
Adder
2.063
927014AC1-188 GEN
Solar/Wind Harmer
0.005
246936BC-WTG1
Solar/Wind Harmer
0.305
270489AE1-102 GEN1
Solar/Wind Harmer
0.979
965421AG1-410 GEN
Solar/Wind Harmer
22.57
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.499
247521TR3_G114
Solar/Wind Harmer
0.273
270246TR4_N_V150
Solar/Wind Harmer
0.048
965011AG1-365 GEN
Solar/Wind Harmer
7.488
24695305TIMB G C
Solar/Wind Harmer
0.002
965651AG1-433 GEN
Solar/Wind Harmer
2.174
958861AF2-177 GEN
Solar/Wind Harmer
3.207
247536S-71 GEN
Solar/Wind Harmer
0.297
25194608D.CRK4
Adder
1.74
945371AF1-202 GEN
Solar/Wind Harmer
0.001
252507AC2-088 GEN
Solar/Wind Harmer
0.335
270063AE2-323 C
Solar/Wind Harmer
0.006
970245AG2-165 GEN
Solar/Wind Harmer
3.191
970947AG2-589 GEN
Solar/Wind Harmer
0.245
270005AE1-210 C O1
Solar/Wind Harmer
1.59
965031AG1-367 GEN
Solar/Wind Harmer
7.338
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.378
970825AG2-519 GEN
Solar/Wind Harmer
2.603
25196808ZIMRHP
Adder
79.729
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
944231AF1-091 GEN
Solar/Wind Harmer
1.953
24639705ELKHART HY
Adder
0.161
270032AE2-172
Solar/Wind Harmer
4.877
970291AG2-192 GEN
Solar/Wind Harmer
0.95
945111AF1-176 GEN
Solar/Wind Harmer
13.03
270505AE1-170 C O1
Solar/Wind Harmer
7.665
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.805
276903AD2-071 C
Solar/Wind Harmer
8.137
25196008MFTGT1
Adder
1.45
247522W1-056 GEN
Solar/Wind Harmer
0.001
970773AG2-487 GEN
Solar/Wind Harmer
1.284
970373AG2-245 GEN
Solar/Wind Harmer
15.247
270055AF2-134 C O1
Solar/Wind Harmer
0.006
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.41
970515AG2-329 GEN
Solar/Wind Harmer
18.805
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
9.032
24791305MDL-5G
Solar/Wind Harmer
0.001
970333AG2-219 GEN
Solar/Wind Harmer
5.139
274751CRETE EC ;1U
Adder
8.477
274754CRETE EC ;4U
Adder
8.477
274773LINCOLN ;4U
Adder
8.676
274774LINCOLN ;5U
Adder
8.676
274723RIVER EC ;12
Adder
18.418
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
5.139
24728605AND G2
Adder
3.927
276776AD2-060 GEN
Solar/Wind Harmer
0.746
945681AF1-233 GEN
Solar/Wind Harmer
13.461
274801UNIV PARK;4U
Adder
5.966
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
31.303
274732ELWOOD EC;7P
Adder
16.768
274674JOLIET 9 ;6U
Adder
15.704
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
963741AG1-226 GEN
Solar/Wind Harmer
16.815
274745AC1-111 GEN9
Adder
5.679
939401AE1-172 GEN
Solar/Wind Harmer
5.301
276691AA1-018 GEN1
Solar/Wind Harmer
0.858
970091AG2-072 GEN
Adder
77.629
276901AD2-066 C O1
Solar/Wind Harmer
0.007
316095T157 G97
Solar/Wind Helper
1.504
23583801GRNGAP
Solar/Wind Helper
5.601
238185AF2-356 C
Solar/Wind Helper
2.646
238108AE1-109 GEN1
Solar/Wind Helper
0.114
235054AD2-180 GEN
Solar/Wind Helper
2.03
235531U2-073 GEN
Solar/Wind Helper
3.282
238117U2-030
Solar/Wind Helper
0.341
238147AE2-230_GEN1
Solar/Wind Helper
0.495
238149AF1-291A_GEN
Solar/Wind Helper
0.141
23751201ROTHROCK
Solar/Wind Helper
0.824
237061AD1-155 GEN
Solar/Wind Helper
0.053
23562501BACKB
Solar/Wind Helper
1.007
238221AF1-254 C O1
Solar/Wind Helper
0.274
235067AD1-061 GEN
Solar/Wind Helper
0.496
23751101LEADS_P59
Solar/Wind Helper
1.404
237030AB1-096 C
Solar/Wind Helper
0.071
3141196NOKESVL
Solar/Wind Helper
1.032
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.346
223402AF1-300 C
Solar/Wind Helper
0.367
205917AD1-020 ES
Solar/Wind Helper
0.368
233918AB1-142 GEN
Solar/Wind Helper
0.502
233982AB2-133 GEN
Solar/Wind Helper
0.358
233994AC2-023 GEN
Solar/Wind Helper
0.961
233996TM1833_GEN
Solar/Wind Helper
0.261
233997TMININ_4.2
Solar/Wind Helper
0.261
232406W1-004 FULL
Solar/Wind Helper
0.507
233940AF2-379 C
Solar/Wind Helper
0.062
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.232
233971AC1-093 C
Solar/Wind Helper
0.357
316044AC1-158 PL1
Solar/Wind Helper
1.293
316450AC1-158 RIC
Solar/Wind Helper
0.345
230430AE1-229_GEN
Solar/Wind Helper
3.372
230415AB2-049 C
Solar/Wind Helper
0.03
228729W2-030 C
Solar/Wind Helper
0.11
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.15
219291REEVESSOUT C
Solar/Wind Helper
0.011
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
219348LDSOLAR C
Solar/Wind Helper
0.114
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.063
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.353
219276PARKLANDSO C
Solar/Wind Helper
0.089
20714528FRN_Y2-051
Solar/Wind Helper
0.057
20720528MAN_W1-024
Solar/Wind Helper
0.028
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.027
219908AB1-139 C
Solar/Wind Helper
0.074
219249CENTRALDIV C
Solar/Wind Helper
0.01
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.089
971997AH1-543 GEN
Solar/Wind Harmer
2.724
LAGNLTFEXP_LAGN->PJM
CLTF
14.837
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.802
TVALTFEXP_TVA->PJM
CLTF
7.293
CPLELTFEXP_CPLE->PJM
CLTF
0.624
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.816
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.078
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.1
MECLTFEXP_MEC->PJM
CLTF
15.901
SIGELTFEXP_SIGE->PJM
CLTF
0.505
NYPJM->LTFIMP_NY
CLTF
4.797
LGEELTFEXP_LGEE->PJM
CLTF
6.749
WECLTFEXP_WEC->PJM
CLTF
3.825
AG2-052LTFEXP_AG2-052->PJM
LTF
0.24
AH1-155LTFEXP_AH1-155->PJM
LTF
0.359

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P2-3_MP-500-012_SRT-A


Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-012_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:131.49 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4985.98
MW Contribution:0.91
Bus #Bus NameTypeMW Contribution
270166AC1-044 GEN3
50/50
7.033
23559101PLEAS2
50/50
5.443
270122AB2-093 CT
50/50
4.116
962761AG1-125 GEN
Solar/Wind Harmer
40.965
970149AG2-104 GEN
Solar/Wind Harmer
50.592
970155AG2-107 GEN
Solar/Wind Harmer
17.863
270349AD2-093_GEN
Solar/Wind Harmer
4.529
270223U2-072_GEN1
Solar/Wind Harmer
2.339
270578AF1-285 GEN2
Solar/Wind Harmer
1.43
270391AF1-285 GEN3
Solar/Wind Harmer
1.43
270159DARBY CT4
Adder
10.388
971995AH1-542 GEN
Solar/Wind Harmer
12.974
970593AG2-378 GEN
Solar/Wind Harmer
2.345
270462AD2-086
Solar/Wind Harmer
8.157
270510AE1-227 GEN1
Solar/Wind Harmer
2.893
24721705FLATG2
Adder
23.506
253343AC1-166 GEN
Solar/Wind Harmer
1.256
253325AC1-069 GEN
Solar/Wind Harmer
1.211
241813AF1-122_GEN
Solar/Wind Harmer
7.346
270263AC1-001 GEN
Solar/Wind Harmer
1.187
241847AF2-150_GEN
Solar/Wind Harmer
4.622
246936BC-WTG1
Solar/Wind Harmer
4.343
270489AE1-102 GEN1
Solar/Wind Harmer
1.443
965421AG1-410 GEN
Solar/Wind Harmer
33.256
970515AG2-329 GEN
Solar/Wind Harmer
16.033
25326309TAIT D
Adder
1.21
960071AF2-298 GEN
Solar/Wind Harmer
5.501
253370AE2-315 SEC1
Adder
2.206
253371AE2-315 SEC2
Adder
2.086
247521TR3_G114
Solar/Wind Harmer
3.699
270246TR4_N_V150
Solar/Wind Harmer
0.936
247522W1-056 GEN
Solar/Wind Harmer
2.477
24695305TIMB G C
Solar/Wind Harmer
6.051
965011AG1-365 GEN
Solar/Wind Harmer
10.972
927014AC1-188 GEN
Solar/Wind Harmer
1.729
944231AF1-091 GEN
Solar/Wind Harmer
4.078
253432AC1-085 GEN2
Solar/Wind Harmer
0.29
946171AF1-282 GEN
Solar/Wind Harmer
10.828
270063AE2-323 C
Solar/Wind Harmer
2.376
965651AG1-433 GEN
Solar/Wind Harmer
5.885
958861AF2-177 GEN
Solar/Wind Harmer
11.752
247536S-71 GEN
Solar/Wind Harmer
4.346
960001AF2-291 GEN
Solar/Wind Harmer
3.244
945371AF1-202 GEN
Solar/Wind Harmer
7.479
24639705ELKHART HY
Adder
0.164
25194608D.CRK4
Adder
1.752
25196808ZIMRHP
Adder
80.188
23906502RICHG2&3
Adder
1.272
972301AH1-735 GEN
Adder
6.357
23906402RICHG1
Adder
1.271
25196008MFTGT1
Adder
1.459
274751CRETE EC ;1U
Adder
8.598
274754CRETE EC ;4U
Adder
8.598
274723RIVER EC ;12
Adder
18.677
274773LINCOLN ;4U
Adder
8.792
274774LINCOLN ;5U
Adder
8.792
274812UNIV PK N;8U
Adder
5.21
23920202STRYCT
Adder
1.444
274801UNIV PARK;4U
Adder
6.045
274676JOLIET 29;8U
Adder
31.706
274732ELWOOD EC;7P
Adder
2.004
23583801GRNGAP
Solar/Wind Helper
6.365
316095T157 G97
Solar/Wind Helper
1.705
238108AE1-109 GEN1
Solar/Wind Helper
0.121
238185AF2-356 C
Solar/Wind Helper
2.767
238147AE2-230_GEN1
Solar/Wind Helper
0.552
238149AF1-291A_GEN
Solar/Wind Helper
0.158
237061AD1-155 GEN
Solar/Wind Helper
0.06
235054AD2-180 GEN
Solar/Wind Helper
2.111
235531U2-073 GEN
Solar/Wind Helper
3.439
238117U2-030
Solar/Wind Helper
0.356
238221AF1-254 C O1
Solar/Wind Helper
0.295
235067AD1-061 GEN
Solar/Wind Helper
0.532
3141196NOKESVL
Solar/Wind Helper
1.141
23751201ROTHROCK
Solar/Wind Helper
0.819
237030AB1-096 C
Solar/Wind Helper
0.075
23562501BACKB
Solar/Wind Helper
0.997
226910AB2-157 C
Solar/Wind Helper
0.015
227287AC2-120 GEN
Solar/Wind Helper
0.375
223402AF1-300 C
Solar/Wind Helper
0.387
316044AC1-158 PL1
Solar/Wind Helper
1.443
316450AC1-158 RIC
Solar/Wind Helper
0.385
316170AC1-121 GEN2
Solar/Wind Helper
0.395
23751101LEADS_P59
Solar/Wind Helper
1.316
205917AD1-020 ES
Solar/Wind Helper
0.379
3132273ORANGE
Solar/Wind Helper
0.049
233918AB1-142 GEN
Solar/Wind Helper
0.511
233982AB2-133 GEN
Solar/Wind Helper
0.364
233994AC2-023 GEN
Solar/Wind Helper
0.977
233996TM1833_GEN
Solar/Wind Helper
0.266
233997TMININ_4.2
Solar/Wind Helper
0.266
232406W1-004 FULL
Solar/Wind Helper
0.516
3147666LOUISA
Solar/Wind Helper
0.551
233940AF2-379 C
Solar/Wind Helper
0.063
234015AF2-250 C
Solar/Wind Helper
0.039
233952AC2-187 GEN
Solar/Wind Helper
0.236
233971AC1-093 C
Solar/Wind Helper
0.363
230430AE1-229_GEN
Solar/Wind Helper
3.409
230415AB2-049 C
Solar/Wind Helper
0.031
228729W2-030 C
Solar/Wind Helper
0.112
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.151
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
219348LDSOLAR C
Solar/Wind Helper
0.115
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.064
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.057
219276PARKLANDSO C
Solar/Wind Helper
0.09
20714528FRN_Y2-051
Solar/Wind Helper
0.057
20720528MAN_W1-024
Solar/Wind Helper
0.028
966881AG1-559 GEN
Solar/Wind Helper
0.312
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.027
219249CENTRALDIV C
Solar/Wind Helper
0.01
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.089
24318805MLG1
50/50
10.022
23559001PLEAS1
50/50
5.443
270051AF1-062 GEN
50/50
11.999
970153AG2-106 GEN
Solar/Wind Harmer
17.863
961921AG1-034 GEN
Solar/Wind Harmer
15.919
241955AC1-078 GEN
Solar/Wind Harmer
8.948
241974AD2-163_GEN2
Solar/Wind Harmer
2.37
942051AE2-217 GEN
Solar/Wind Harmer
21.374
942871AE2-306 GEN
Solar/Wind Harmer
1.073
270391AF1-285 GEN3
Solar/Wind Harmer
0.55
960801AF2-371 GEN
Solar/Wind Harmer
2.991
964871AG1-351 GEN
Solar/Wind Harmer
2.065
970605AG2-385 GEN
Solar/Wind Harmer
6.332
270485AE1-090_GEN
Solar/Wind Harmer
0.709
270512AE1-227 GEN2
Solar/Wind Harmer
2.455
24721905FLATG4
Adder
23.506
253338AC1-165 GEN
Solar/Wind Harmer
1.256
253333AC1-068 GEN
Solar/Wind Harmer
1.211
970065AG2-057 GEN
Solar/Wind Harmer
1.148
270273AD2-016 GEN
Solar/Wind Harmer
3.061
972173AH1-669 GEN
Solar/Wind Harmer
5.721
270377AD1-106 GEN
Solar/Wind Harmer
6.988
270588AE1-091_GEN
Solar/Wind Harmer
12.311
270291AC1-194 GEN
Solar/Wind Harmer
11.854
253415AE1-040 GEN
Solar/Wind Harmer
1.258
961961AG1-039 GEN
Solar/Wind Harmer
3.188
270491AE1-102 GEN2
Solar/Wind Harmer
1.443
970217AG2-149 GEN
Solar/Wind Harmer
35.355
958091AF2-103 GEN
Solar/Wind Harmer
0.178
253303V4-073 C
Solar/Wind Harmer
0.128
253370AE2-315 SEC1
Adder
2.206
253371AE2-315 SEC2
Adder
2.086
270191TR4_S_V150
Solar/Wind Harmer
3.3
270247TR4_N_V136
Solar/Wind Harmer
0.936
959331AF2-224 GEN
Solar/Wind Harmer
10.972
965021AG1-366 GEN
Solar/Wind Harmer
2.552
270258AD1-119 GEN
Solar/Wind Harmer
3.051
253406AD2-031_GEN
Solar/Wind Harmer
1.398
270044AE2-322 C
Solar/Wind Harmer
1.435
270404AC1-167 GEN
Solar/Wind Harmer
1.194
957541AF2-048 GEN
Solar/Wind Harmer
1.725
270043AE2-236 GEN
Solar/Wind Harmer
5.98
944531AF1-118 GEN
Solar/Wind Harmer
37.943
253316AC1-085 GEN3
Solar/Wind Harmer
9.07
253433AC1-085 GEN1
Solar/Wind Harmer
5.758
946181AF1-283 GEN
Solar/Wind Harmer
14.077
970031AG2-029 GEN
Solar/Wind Harmer
32.394
971617AH1-308 GEN
Solar/Wind Harmer
6.274
270541AE2-072 C
Solar/Wind Harmer
4.881
971191AH1-055 GEN
Solar/Wind Harmer
23.635
962031AG1-047 GEN
Solar/Wind Harmer
3.246
957741AF2-068 GEN
Solar/Wind Harmer
16.111
25196608WSDLE5
Adder
9.143
24642205MAYFLWER
Adder
0.678
25194608D.CRK4
Adder
1.752
247604X1-042
Adder
0.444
23906502RICHG2&3
Adder
1.272
25196008MFTGT1
Adder
1.413
274752CRETE EC ;2U
Adder
8.598
274753CRETE EC ;3U
Adder
8.598
274724RIVER EC ;11
Adder
18.459
274772LINCOLN ;3U
Adder
8.792
274802UNIV PARK;5U
Adder
6.05
274826FISK ;BP
Adder
11.355
274800UNIV PARK;3U
Adder
6.045
972038AH1-567 GEN2
Adder
0.378
972228AH1-698 GEN2
Adder
3.84
274676JOLIET 29;8U
Adder
30.573
274729ELWOOD EC;1P
Adder
16.983
274730ELWOOD EC;6P
Adder
16.983
964991AG1-363 GEN
Solar/Wind Helper
5.557
316097T157 G90
Solar/Wind Helper
1.705
23750701CROSSCHOOL
Solar/Wind Helper
1.586
238148AE2-230_GEN2
Solar/Wind Helper
0.555
238127S14_GEN_2
Solar/Wind Helper
0.867
238118U2-030_1
Solar/Wind Helper
0.356
237080AD1-060 GEN
Solar/Wind Helper
0.367
237038AE2-054 C
Solar/Wind Helper
0.292
235062AE1-101 C1
Solar/Wind Helper
1.776
23779801AA1-109
Solar/Wind Helper
0.207
316006AB2-029 C
Solar/Wind Helper
0.13
223401AF1-299 GEN
Solar/Wind Helper
0.387
316045AC1-158 PL2
Solar/Wind Helper
4.618
316254AC1-120 GEN1
Solar/Wind Helper
1.184
237048AF1-022 C
Solar/Wind Helper
0.173
966131AG1-482 GEN
Solar/Wind Helper
0.079
233930AB2-032 GEN
Solar/Wind Helper
0.387
233915AB1-141 GEN
Solar/Wind Helper
0.511
232422X3-066 FULL
Solar/Wind Helper
0.116
233964AF2-378 GEN
Solar/Wind Helper
0.042
232426Y1-080 FULL
Solar/Wind Helper
0.039
233998TM1NIN_3.36
Solar/Wind Helper
0.266
232404W1-003 C
Solar/Wind Helper
0.516
232428Y3-058 C
Solar/Wind Helper
0.344
3147666LOUISA
Solar/Wind Helper
0.958
232434Z2-077 GEN
Solar/Wind Helper
0.129
233954AC2-188 GEN
Solar/Wind Helper
0.236
233950AC2-186 GEN
Solar/Wind Helper
0.118
233972AC1-094 C
Solar/Wind Helper
0.307
316192AB2-158 GEN
Solar/Wind Helper
1.608
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.232
228728W1-130C
Solar/Wind Helper
0.054
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219904AC1-010 C
Solar/Wind Helper
0.061
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.132
20720728JCB_W1-129
Solar/Wind Helper
0.057
207445AB1-138_GEN
Solar/Wind Helper
0.105
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20715228NPK_W1-113
Solar/Wind Helper
0.078
207454AA2-184 E
Solar/Wind Helper
0.311
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.497
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
207437AD2-070 GEN
Solar/Wind Helper
0.137
207518AF1-320_GEN
Solar/Wind Helper
1.568
20671928W4-073
Solar/Wind Helper
0.089
20675828AU_W4-064
Solar/Wind Helper
0.029
270119AB2-067 GEN1
50/50
7.033
270120AB2-067 GEN2
50/50
7.033
24318905MLG2
50/50
7.475
270471AD2-092_GEN
Solar/Wind Harmer
4.529
946101AF1-275 GEN
Solar/Wind Harmer
1.842
938701AE1-092 GEN
Solar/Wind Harmer
24.483
270224U2-072_GEN2
Solar/Wind Harmer
2.339
270227U2-072_GEN3
Solar/Wind Harmer
2.339
270228U2-072_GEN4
Solar/Wind Harmer
2.339
270231U2-072_GEN5
Solar/Wind Harmer
2.339
942861AE2-305 GEN
Solar/Wind Harmer
9.223
964601AG1-323 GEN
Solar/Wind Harmer
3.753
964601AG1-323 GEN
Solar/Wind Harmer
1.746
972269AH1-719 GEN
Adder
2.7
970077AG2-063 GEN
Solar/Wind Harmer
6.332
972159AH1-661 GEN
Adder
1.166
270518AE2-148 GEN
Solar/Wind Harmer
14.068
971199AH1-059 GEN
Solar/Wind Harmer
4.644
241960AC2-195 GEN
Solar/Wind Harmer
3.219
971201AH1-060 GEN
Solar/Wind Harmer
2.296
253378AE2-206_GEN
Solar/Wind Harmer
4.086
276820AF1-078_GEN
Solar/Wind Harmer
1.815
971231AH1-075 GEN
Solar/Wind Harmer
0.905
25326509SID D
Adder
1.48
25326109MON D
Adder
1.461
246938BC-WTG3
Solar/Wind Harmer
4.418
246937BC-WTG2
Solar/Wind Harmer
4.343
970879AG2-548 GEN
Solar/Wind Harmer
6.827
971073AG2-665 GEN
Solar/Wind Harmer
6.827
971073AG2-665 GEN
Solar/Wind Harmer
4.763
25322209TAIT E
Adder
10.77
25322209TAIT E
Adder
10.528
270007AE1-245 C
Solar/Wind Harmer
6.539
942801AE2-298 GEN
Solar/Wind Harmer
1.667
253370AE2-315 SEC1
Adder
2.206
970611AG2-400 GEN
Solar/Wind Harmer
10.972
253394AE2-221_GEN
Solar/Wind Harmer
4.954
253398AE2-221_GEN2
Solar/Wind Harmer
4.954
253317AC1-085 GEN4
Solar/Wind Harmer
9.07
971677AH1-339 GEN
Solar/Wind Harmer
8.643
942221AE2-234 GEN
Solar/Wind Harmer
0.79
944541AF1-119 GEN
Solar/Wind Harmer
4.511
960971AF2-388 GEN
Solar/Wind Harmer
11.771
247621Y3-024
Adder
0.259
270201AC2-176 GEN
Solar/Wind Harmer
5.522
970883AG2-550 GEN
Solar/Wind Harmer
10.73
970885AG2-551 GEN
Solar/Wind Harmer
2.495
247620Y3-023
Adder
0.494
964611AG1-324 GEN
Solar/Wind Harmer
1.264
964611AG1-324 GEN
Solar/Wind Harmer
0.561
25194408D.CRK1
Adder
8.061
25194508D.CRK3
Adder
1.507
24728805RICHG1
Adder
4.003
24728905RICHG2
Adder
4.003
970935AG2-582 GEN
Adder
239.406
274770LINCOLN ;1U
Adder
8.792
274771LINCOLN ;2U
Adder
8.792
274808UNIV PK N;4U
Adder
5.188
274803UNIV PARK;6U
Adder
6.05
972259AH1-714 GEN
Adder
19.76
238175AF1-290_GEN
Solar/Wind Helper
0.168
238169AE2-226 GEN1
Solar/Wind Helper
0.772
238170AE2-226 GEN2
Solar/Wind Helper
0.772
238120AE2-309 GEN
Solar/Wind Helper
0.552
23585401KL_K28_T16
Solar/Wind Helper
1.529
235020AA1-095 C
Solar/Wind Helper
0.057
23777901MDS_W4-102
Solar/Wind Helper
0.191
237034AC2-136 C
Solar/Wind Helper
0.244
237002AB1-128_GEN
Solar/Wind Helper
0.475
235063AE1-101 C2
Solar/Wind Helper
1.776
237001AB1-127_GEN
Solar/Wind Helper
0.473
23777801MSM_W1-116
Solar/Wind Helper
0.122
237025AB1-124 C
Solar/Wind Helper
0.175
237006AB1-125 GEN
Solar/Wind Helper
0.131
226929AD2-058 GEN
Solar/Wind Helper
0.108
315651AD1-115 GEN
Solar/Wind Helper
0.876
316447AC1-158 HLD
Solar/Wind Helper
3.175
205916AD1-020 GEN
Solar/Wind Helper
1.761
20390526W1-045 C
Solar/Wind Helper
0.36
208835TUHI V3-051
Solar/Wind Helper
0.025
208835TUHI V3-051
Solar/Wind Helper
0.025
3132123MT JACKSON
Solar/Wind Helper
0.764
233987AB2-037 GEN
Solar/Wind Helper
2.381
233933AB2-153 GEN
Solar/Wind Helper
0.236
232424Y1-079 C
Solar/Wind Helper
0.118
233944AB2-135 GEN
Solar/Wind Helper
0.598
233946AB2-136 GEN
Solar/Wind Helper
0.577
234036AF2-325 C
Solar/Wind Helper
0.043
233901CHERRYDALE C
Solar/Wind Helper
0.236
232408W1-005 C
Solar/Wind Helper
0.516
232410W1-006 C
Solar/Wind Helper
0.516
233939AC1-091 C
Solar/Wind Helper
0.356
233970AC1-092 C
Solar/Wind Helper
0.356
966001AG1-469 GEN
Solar/Wind Helper
0.255
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.041
219921AF1-264
Solar/Wind Helper
0.052
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.083
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.19
20716928W4-060COL
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.016
20673828FLE_V3-070
Solar/Wind Helper
0.091
207442AE1-156 GEN
Solar/Wind Helper
0.326
20676128MHD_W3-029
Solar/Wind Helper
0.096
20671828STAW2-080
Solar/Wind Helper
0.027
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
207471AF2-354 C
Solar/Wind Helper
0.168
20674928WA_W3-044
Solar/Wind Helper
0.098
20676228FRD_X1-012
Solar/Wind Helper
0.091
964851AG1-348 GEN
Solar/Wind Helper
0.081
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.044
211065PSPA IPP
Solar/Wind Helper
0.15
211065PSPA IPP
Solar/Wind Helper
0.15
972239AH1-704 GEN
50/50
3.102
962771AG1-126 GEN
Solar/Wind Harmer
40.965
270459AD2-067 GEN
Solar/Wind Harmer
10.453
961821AG1-024 GEN
Solar/Wind Harmer
10.613
270054AF2-122 C O1
Solar/Wind Harmer
4.071
270284AF1-227 GEN1
Solar/Wind Harmer
6.912
270286AF1-227 GEN2
Solar/Wind Harmer
2.557
270287AF1-227 GEN3
Solar/Wind Harmer
2.557
270520AE2-214 GEN
Solar/Wind Harmer
7.382
253383AE2-342_GEN
Solar/Wind Harmer
1.062
241973AD2-163_GEN1
Solar/Wind Harmer
2.37
940611AE2-048 GEN
Solar/Wind Harmer
26.074
941391AE2-136 GEN
Solar/Wind Harmer
13.511
270578AF1-285 GEN2
Solar/Wind Harmer
0.55
943861AF1-054 GEN
Solar/Wind Harmer
4.552
943851AF1-053 GEN
Solar/Wind Harmer
2.2
945631AF1-228 GEN
Solar/Wind Harmer
5.537
270156DARBY CT1
Adder
10.556
270157DARBY CT2
Adder
10.53
270158DARBY CT3
Adder
10.362
270302AB2-170 GEN
Solar/Wind Harmer
9.805
270317AD1-130_GEN
Solar/Wind Harmer
3.759
970689AG2-444 GEN
Solar/Wind Harmer
19.055
270432AC2-029 GEN
Solar/Wind Harmer
8.138
958581AF2-149 GEN
Solar/Wind Harmer
4.968
970179AG2-119 GEN
Solar/Wind Harmer
9.26
270269AC2-059
Solar/Wind Harmer
10.704
241972AD1-140 GEN
Solar/Wind Harmer
5.084
971567AH1-282 GEN
Solar/Wind Harmer
16.984
966831AG1-554 GEN
Solar/Wind Harmer
1.34
971989AH1-539 GEN
Solar/Wind Harmer
14.49
270340AC2-060 GEN
Solar/Wind Harmer
3.371
957201AF2-014 GEN
Solar/Wind Harmer
5.033
270435AC2-044 GEN
Solar/Wind Harmer
2.219
970879AG2-548 GEN
Solar/Wind Harmer
4.763
247607V1-011 GEN
Solar/Wind Harmer
4.359
253372AE2-315 SEC3
Adder
2.086
253372AE2-315 SEC3
Adder
2.086
965051AG1-369 GEN
Solar/Wind Harmer
5.494
25306009OHH W.
Adder
3.166
270297AD1-101 GEN
Solar/Wind Harmer
3.056
965041AG1-368 GEN
Solar/Wind Harmer
10.974
253349AC2-067 GEN
Solar/Wind Harmer
5.466
253400AC2-068 GEN
Solar/Wind Harmer
2.198
963791AG1-232 GEN
Solar/Wind Harmer
14.679
270071AF1-092 GEN
Solar/Wind Harmer
16.242
24729505KEY G4
Adder
7.02
945641AF1-229 GEN
Solar/Wind Harmer
3.923
270024AE2-089 GEN
Solar/Wind Harmer
5.065
958711AF2-162 GEN
Solar/Wind Harmer
1.089
965101AG1-375 GEN
Solar/Wind Harmer
10.752
961761AG1-017 GEN
Solar/Wind Harmer
0.46
270543AE2-219 C
Solar/Wind Harmer
5.494
971029AG2-637 GEN
Solar/Wind Harmer
16.089
971673AH1-337 GEN
Solar/Wind Harmer
4.934
25196408WSDLE3
Adder
9.412
25196308WSDLE2
Adder
9.33
25196208WSDLE1
Adder
9.306
25196708WSDLE6
Adder
9.283
25196508WSDLE4
Adder
9.049
25196108MFTGT2
Adder
1.608
25196108MFTGT2
Adder
1.494
274775LINCOLN ;6U
Adder
8.792
274776LINCOLN ;7U
Adder
8.792
274777LINCOLN ;8U
Adder
8.792
274814UNIV PK N;0U
Adder
5.256
274807UNIV PK N;3U
Adder
5.245
274805UNIV PK N;1U
Adder
5.222
274811UNIV PK N;7U
Adder
5.21
972037AH1-567 GEN1
Adder
0.19
274827FISK ;RP
Adder
8.047
972227AH1-698 GEN1
Adder
2.704
274687WILL CNTY;4U
Adder
28.893
274687WILL CNTY;4U
Adder
28.893
274675JOLIET 29;7U
Adder
31.706
274675JOLIET 29;7U
Adder
30.574
274731ELWOOD EC;2P
Adder
16.983
274733ELWOOD EC;3P
Adder
16.983
274735ELWOOD EC;4P
Adder
16.983
274728ELWOOD EC;5P
Adder
16.983
238109AE1-109 GEN2
Solar/Wind Helper
0.121
238110AE1-109 GEN3
Solar/Wind Helper
0.121
238152AF2-075_GEN
Solar/Wind Helper
0.789
23546401DTGZ2-030
Solar/Wind Helper
0.099
238126S14_GEN_1
Solar/Wind Helper
0.867
238208AF1-136 C
Solar/Wind Helper
0.236
237085AD2-009_GEN
Solar/Wind Helper
1.767
3138216PACIFIC
Solar/Wind Helper
0.049
316411AF1-147_GEN1
Solar/Wind Helper
0.978
316415AF1-147_GEN2
Solar/Wind Helper
0.978
3141426STAFORD
Solar/Wind Helper
0.058
316164AC1-076 GEN
Solar/Wind Helper
1.225
23750501ELLIOTTS
Solar/Wind Helper
0.629
959381AF2-229 GEN
Solar/Wind Helper
0.367
960921AF2-383 GEN
Solar/Wind Helper
0.185
205943AE1-185 GEN
Solar/Wind Helper
0.518
205932AD2-116_GEN
Solar/Wind Helper
0.518
205956AE1-196_GEN
Solar/Wind Helper
0.518
233935AB2-179 C
Solar/Wind Helper
1.29
232436AB1-176 C
Solar/Wind Helper
0.045
233923SMA
Solar/Wind Helper
0.974
233990AG1-397 GEN
Solar/Wind Helper
0.031
232432Z2-076 GEN
Solar/Wind Helper
0.068
234033AF1-007_GEN
Solar/Wind Helper
7.137
964001AG1-254 GEN
Solar/Wind Helper
0.966
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.116
203975AE1-071-GEN
Solar/Wind Helper
2.53
219272CLEANLIGHT C
Solar/Wind Helper
0.026
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.081
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.292
219620RIDERU C
Solar/Wind Helper
0.001
20675528CPH_W2-050
Solar/Wind Helper
0.087
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
218524CNTRALGAS1 C
Solar/Wind Helper
0.161
966261AG1-495 GEN
Solar/Wind Helper
0.081
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20675928HOL_W4-097
Solar/Wind Helper
0.05
20674828DL_W4-046
Solar/Wind Helper
0.008
207484AF2-139 C O1
Solar/Wind Helper
0.084
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.136
20675128HRM_W1-127
Solar/Wind Helper
0.029
209116AE2-175 GEN
Solar/Wind Helper
1.768
945581AF1-223 GEN
Solar/Wind Harmer
0.763
LAGNLTFEXP_LAGN->PJM
CLTF
14.521
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.32
TVALTFEXP_TVA->PJM
CLTF
7.111
CBM West 2LTFEXP_CBM-W2->PJM
CBM
111.893
CBM West 1LTFEXP_CBM-W1->PJM
CBM
146.579
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.544
MECLTFEXP_MEC->PJM
CLTF
15.979
SIGELTFEXP_SIGE->PJM
CLTF
0.506
NYPJM->LTFIMP_NY
CLTF
4.554
LGEELTFEXP_LGEE->PJM
CLTF
6.753
WECLTFEXP_WEC->PJM
CLTF
3.866
AG2-052LTFEXP_AG2-052->PJM
LTF
0.243
AH1-155LTFEXP_AH1-155->PJM
LTF
0.364

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P1-2_MP-500-008A_SRT-SL


Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P1-2_MP-500-008A_SRT-SL
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:125.38 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4754.33
MW Contribution:0.83
Bus #Bus NameTypeMW Contribution
270166AC1-044 GEN3
50/50
6.869
23559101PLEAS2
50/50
5.385
270122AB2-093 CT
50/50
3.689
962761AG1-125 GEN
Solar/Wind Harmer
33.269
970149AG2-104 GEN
Solar/Wind Harmer
35.932
970155AG2-107 GEN
Solar/Wind Harmer
21.245
270349AD2-093_GEN
Solar/Wind Harmer
0.006
24721705FLATG2
Adder
22.865
270159DARBY CT4
Adder
9.89
970593AG2-378 GEN
Solar/Wind Harmer
1.75
270223U2-072_GEN1
Solar/Wind Harmer
0.001
253343AC1-166 GEN
Solar/Wind Harmer
0.003
253325AC1-069 GEN
Solar/Wind Harmer
0.012
270462AD2-086
Solar/Wind Harmer
0.016
971995AH1-542 GEN
Solar/Wind Harmer
2.81
270263AC1-001 GEN
Solar/Wind Harmer
0.758
270510AE1-227 GEN1
Solar/Wind Harmer
1.904
241813AF1-122_GEN
Solar/Wind Harmer
3.294
25326309TAIT D
Adder
1.153
960071AF2-298 GEN
Solar/Wind Harmer
3.651
253370AE2-315 SEC1
Adder
2.103
253371AE2-315 SEC2
Adder
1.989
927014AC1-188 GEN
Solar/Wind Harmer
0.004
246936BC-WTG1
Solar/Wind Harmer
0.295
270489AE1-102 GEN1
Solar/Wind Harmer
0.945
965421AG1-410 GEN
Solar/Wind Harmer
21.788
247521TR3_G114
Solar/Wind Harmer
0.263
270246TR4_N_V150
Solar/Wind Harmer
0.047
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.226
965011AG1-365 GEN
Solar/Wind Harmer
7.225
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
24695305TIMB G C
Solar/Wind Harmer
0.002
965651AG1-433 GEN
Solar/Wind Harmer
2.096
958861AF2-177 GEN
Solar/Wind Harmer
3.092
247536S-71 GEN
Solar/Wind Harmer
0.287
945371AF1-202 GEN
Solar/Wind Harmer
0.001
25194608D.CRK4
Adder
1.676
270063AE2-323 C
Solar/Wind Harmer
0.006
252507AC2-088 GEN
Solar/Wind Harmer
0.323
970245AG2-165 GEN
Solar/Wind Harmer
3.076
944231AF1-091 GEN
Solar/Wind Harmer
1.885
270005AE1-210 C O1
Solar/Wind Harmer
1.532
965031AG1-367 GEN
Solar/Wind Harmer
7.073
970947AG2-589 GEN
Solar/Wind Harmer
0.236
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.183
970825AG2-519 GEN
Solar/Wind Harmer
2.509
24639705ELKHART HY
Adder
0.155
25196808ZIMRHP
Adder
76.799
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
270032AE2-172
Solar/Wind Harmer
4.701
970291AG2-192 GEN
Solar/Wind Harmer
0.916
945111AF1-176 GEN
Solar/Wind Harmer
12.568
270505AE1-170 C O1
Solar/Wind Harmer
7.393
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.67
247522W1-056 GEN
Solar/Wind Harmer
0.001
276903AD2-071 C
Solar/Wind Harmer
7.842
25196008MFTGT1
Adder
1.397
970773AG2-487 GEN
Solar/Wind Harmer
1.237
972239AH1-704 GEN
50/50
2.78
962771AG1-126 GEN
Solar/Wind Harmer
33.269
270459AD2-067 GEN
Solar/Wind Harmer
0
270054AF2-122 C O1
Solar/Wind Harmer
0.007
961821AG1-024 GEN
Solar/Wind Harmer
4.91
270520AE2-214 GEN
Solar/Wind Harmer
0.013
270284AF1-227 GEN1
Solar/Wind Harmer
0.01
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
253383AE2-342_GEN
Solar/Wind Harmer
0.003
241973AD2-163_GEN1
Solar/Wind Harmer
0.006
945631AF1-228 GEN
Solar/Wind Harmer
0
943861AF1-054 GEN
Solar/Wind Harmer
3.02
943851AF1-053 GEN
Solar/Wind Harmer
2.092
270156DARBY CT1
Adder
10.05
270157DARBY CT2
Adder
10.026
270158DARBY CT3
Adder
9.866
270578AF1-285 GEN2
Solar/Wind Harmer
0.518
970689AG2-444 GEN
Solar/Wind Harmer
15.861
270432AC2-029 GEN
Solar/Wind Harmer
3.428
940611AE2-048 GEN
Solar/Wind Harmer
18.967
941391AE2-136 GEN
Solar/Wind Harmer
10.684
270302AB2-170 GEN
Solar/Wind Harmer
0.005
270317AD1-130_GEN
Solar/Wind Harmer
0.011
971653AH1-327 GEN
Solar/Wind Harmer
1.08
270269AC2-059
Solar/Wind Harmer
0.004
241972AD1-140 GEN
Solar/Wind Harmer
0.824
270119AB2-067 GEN1
50/50
6.869
270120AB2-067 GEN2
50/50
6.869
24318905MLG2
50/50
6.89
270471AD2-092_GEN
Solar/Wind Harmer
0.006
942861AE2-305 GEN
Solar/Wind Harmer
6.118
970077AG2-063 GEN
Solar/Wind Harmer
4.471
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
938701AE1-092 GEN
Solar/Wind Harmer
12.484
971655AH1-328 GEN
Solar/Wind Harmer
2.758
964601AG1-323 GEN
Solar/Wind Harmer
3.106
964601AG1-323 GEN
Solar/Wind Harmer
2.071
270518AE2-148 GEN
Solar/Wind Harmer
0.667
972269AH1-719 GEN
Adder
2.501
972159AH1-661 GEN
Adder
1.082
253378AE2-206_GEN
Solar/Wind Harmer
0.004
276820AF1-078_GEN
Solar/Wind Harmer
0.002
970329AG2-216 GEN
Solar/Wind Harmer
3.237
971199AH1-059 GEN
Solar/Wind Harmer
2.99
241960AC2-195 GEN
Solar/Wind Harmer
0.006
970935AG2-582 GEN
Adder
242.403
25326509SID D
Adder
1.4
971073AG2-665 GEN
Solar/Wind Harmer
6.645
25326109MON D
Adder
1.391
971201AH1-060 GEN
Solar/Wind Harmer
1.471
25322209TAIT E
Adder
10.262
25322209TAIT E
Adder
10.031
253370AE2-315 SEC1
Adder
2.103
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
246938BC-WTG3
Solar/Wind Harmer
0.263
246937BC-WTG2
Solar/Wind Harmer
0.295
971231AH1-075 GEN
Solar/Wind Harmer
0.833
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
970611AG2-400 GEN
Solar/Wind Harmer
7.225
970627AG2-408 GEN
Solar/Wind Harmer
2.167
270007AE1-245 C
Solar/Wind Harmer
0.002
970623AG2-406 GEN
Solar/Wind Harmer
1.309
962581AG1-107 GEN
Solar/Wind Harmer
0.001
25183208HLCRTG
Solar/Wind Harmer
0.011
944541AF1-119 GEN
Solar/Wind Harmer
0.479
960971AF2-388 GEN
Solar/Wind Harmer
4.192
942221AE2-234 GEN
Solar/Wind Harmer
0.036
252519AF1-045_GEN
Solar/Wind Harmer
6.204
252516AE2-318_GEN
Solar/Wind Harmer
5.503
970621AG2-405 GEN
Solar/Wind Harmer
1.305
247621Y3-024
Adder
0.246
970883AG2-550 GEN
Solar/Wind Harmer
7.123
970885AG2-551 GEN
Solar/Wind Harmer
2.374
270201AC2-176 GEN
Solar/Wind Harmer
0.001
25194408D.CRK1
Adder
7.711
25194508D.CRK3
Adder
1.442
964611AG1-324 GEN
Solar/Wind Harmer
0.534
252509AD1-136 GEN
Solar/Wind Harmer
0.036
970321AG2-212 GEN
Solar/Wind Harmer
3.076
270599AE1-208 GEN
Solar/Wind Harmer
6.495
270031AE2-169
Solar/Wind Harmer
3.897
270383AD1-128 GEN
Solar/Wind Harmer
0.004
270186AC1-089 GEN
Solar/Wind Harmer
0.004
247620Y3-023
Adder
0.466
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0.001
24318805MLG1
50/50
9.842
23559001PLEAS1
50/50
5.385
270051AF1-062 GEN
50/50
11.434
970153AG2-106 GEN
Solar/Wind Harmer
21.245
961921AG1-034 GEN
Solar/Wind Harmer
7.364
241955AC1-078 GEN
Solar/Wind Harmer
0.007
241974AD2-163_GEN2
Solar/Wind Harmer
0.006
942051AE2-217 GEN
Solar/Wind Harmer
14.169
24721905FLATG4
Adder
22.865
970605AG2-385 GEN
Solar/Wind Harmer
4.731
270391AF1-285 GEN3
Solar/Wind Harmer
0.518
253338AC1-165 GEN
Solar/Wind Harmer
0.003
253333AC1-068 GEN
Solar/Wind Harmer
0.012
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270273AD2-016 GEN
Solar/Wind Harmer
0.792
972173AH1-669 GEN
Solar/Wind Harmer
3.811
270512AE1-227 GEN2
Solar/Wind Harmer
1.904
270291AC1-194 GEN
Solar/Wind Harmer
5.884
253415AE1-040 GEN
Solar/Wind Harmer
0.003
970065AG2-057 GEN
Solar/Wind Harmer
0.735
253370AE2-315 SEC1
Adder
2.103
253371AE2-315 SEC2
Adder
1.989
970191AG2-125 GEN
Solar/Wind Harmer
1.876
253406AD2-031_GEN
Solar/Wind Harmer
0.543
270491AE1-102 GEN2
Solar/Wind Harmer
0.945
270377AD1-106 GEN
Solar/Wind Harmer
2.761
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.047
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
9.394
959331AF2-224 GEN
Solar/Wind Harmer
5.057
965021AG1-366 GEN
Solar/Wind Harmer
2.408
270588AE1-091_GEN
Solar/Wind Harmer
5.649
971191AH1-055 GEN
Solar/Wind Harmer
18.515
944531AF1-118 GEN
Solar/Wind Harmer
32.203
270043AE2-236 GEN
Solar/Wind Harmer
4.607
270258AD1-119 GEN
Solar/Wind Harmer
0.002
971617AH1-308 GEN
Solar/Wind Harmer
5.953
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
10.684
270404AC1-167 GEN
Solar/Wind Harmer
0.003
25196608WSDLE5
Adder
8.745
252510AF1-249 C
Solar/Wind Harmer
0.055
970031AG2-029 GEN
Solar/Wind Harmer
4.625
25194608D.CRK4
Adder
1.676
270222AC2-111 GEN
Solar/Wind Harmer
3.603
970513AG2-328 GEN
Solar/Wind Harmer
3.076
970517AG2-330 GEN
Solar/Wind Harmer
18.457
970349AG2-230 GEN
Solar/Wind Harmer
10.632
946031AF1-268 GEN
Solar/Wind Harmer
6.74
958821AF2-173 GEN
Solar/Wind Harmer
9.902
270004AE1-209 GEN
Solar/Wind Harmer
1.532
270437AC2-090 C
Solar/Wind Harmer
0.003
247643Z2-116 C
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.775
970291AG2-192 GEN
Solar/Wind Harmer
0.705
945111AF1-176 GEN
Solar/Wind Harmer
5.709
247642Z2-115 C
Solar/Wind Harmer
0.003
24642205MAYFLWER
Adder
0.641
24441205WTRV SLR C
Solar/Wind Harmer
0
25196008MFTGT1
Adder
1.353
270356AE2-297 GEN
Solar/Wind Harmer
0.009
970217AG2-149 GEN
Solar/Wind Harmer
6.066
247604X1-042
Adder
0.418
270535AF1-215 GEN1
Solar/Wind Harmer
0.009
964401AG1-302 GEN
Solar/Wind Harmer
0.001
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.935
970243AG2-164 GEN
Solar/Wind Harmer
4.047
970519AG2-331 GEN
Solar/Wind Harmer
17.988
970699AG2-449 GEN
Solar/Wind Harmer
1.73
970373AG2-245 GEN
Solar/Wind Harmer
14.699
970515AG2-329 GEN
Solar/Wind Harmer
18.197
270055AF2-134 C O1
Solar/Wind Harmer
0.005
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.071
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.706
24791305MDL-5G
Solar/Wind Harmer
0.001
970333AG2-219 GEN
Solar/Wind Harmer
4.947
274751CRETE EC ;1U
Adder
8.172
274754CRETE EC ;4U
Adder
8.172
274773LINCOLN ;4U
Adder
8.364
274774LINCOLN ;5U
Adder
8.364
274723RIVER EC ;12
Adder
17.756
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.954
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
276776AD2-060 GEN
Solar/Wind Harmer
0.719
24728605AND G2
Adder
3.784
274801UNIV PARK;4U
Adder
5.751
941551AE2-152 GEN
Solar/Wind Harmer
0.001
945681AF1-233 GEN
Solar/Wind Harmer
12.962
274676JOLIET 29;8U
Adder
30.175
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
963741AG1-226 GEN
Solar/Wind Harmer
16.202
939401AE1-172 GEN
Solar/Wind Harmer
5.109
276691AA1-018 GEN1
Solar/Wind Harmer
0.827
276901AD2-066 C O1
Solar/Wind Harmer
0.007
316095T157 G97
Solar/Wind Helper
1.455
23583801GRNGAP
Solar/Wind Helper
5.418
238108AE1-109 GEN1
Solar/Wind Helper
0.106
238185AF2-356 C
Solar/Wind Helper
2.425
238147AE2-230_GEN1
Solar/Wind Helper
0.478
238149AF1-291A_GEN
Solar/Wind Helper
0.137
235531U2-073 GEN
Solar/Wind Helper
3.034
235054AD2-180 GEN
Solar/Wind Helper
1.839
237061AD1-155 GEN
Solar/Wind Helper
0.051
238117U2-030
Solar/Wind Helper
0.314
238221AF1-254 C O1
Solar/Wind Helper
0.265
235067AD1-061 GEN
Solar/Wind Helper
0.478
237030AB1-096 C
Solar/Wind Helper
0.068
3141196NOKESVL
Solar/Wind Helper
0.999
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.335
223402AF1-300 C
Solar/Wind Helper
0.355
23751201ROTHROCK
Solar/Wind Helper
0.694
23562501BACKB
Solar/Wind Helper
0.842
205917AD1-020 ES
Solar/Wind Helper
0.356
233982AB2-133 GEN
Solar/Wind Helper
0.346
233918AB1-142 GEN
Solar/Wind Helper
0.486
233994AC2-023 GEN
Solar/Wind Helper
0.929
233996TM1833_GEN
Solar/Wind Helper
0.253
233997TMININ_4.2
Solar/Wind Helper
0.253
232406W1-004 FULL
Solar/Wind Helper
0.49
233940AF2-379 C
Solar/Wind Helper
0.06
234015AF2-250 C
Solar/Wind Helper
0.037
233952AC2-187 GEN
Solar/Wind Helper
0.225
233971AC1-093 C
Solar/Wind Helper
0.346
316044AC1-158 PL1
Solar/Wind Helper
1.252
316450AC1-158 RIC
Solar/Wind Helper
0.334
230430AE1-229_GEN
Solar/Wind Helper
3.26
230415AB2-049 C
Solar/Wind Helper
0.029
228729W2-030 C
Solar/Wind Helper
0.107
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.053
219912AD2-042 GEN
Solar/Wind Helper
0.145
219291REEVESSOUT C
Solar/Wind Helper
0.011
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.111
316170AC1-121 GEN2
Solar/Wind Helper
0.342
959561AF2-247 GEN
Solar/Wind Helper
0.02
20720828JCB_W4-025
Solar/Wind Helper
0.061
20716028EGP_W2-019
Solar/Wind Helper
0.018
20715028HAN_X4-015
Solar/Wind Helper
0.055
219276PARKLANDSO C
Solar/Wind Helper
0.086
20714528FRN_Y2-051
Solar/Wind Helper
0.055
20720528MAN_W1-024
Solar/Wind Helper
0.027
971997AH1-543 GEN
Solar/Wind Harmer
1.86
970179AG2-119 GEN
Solar/Wind Harmer
6.658
270340AC2-060 GEN
Solar/Wind Harmer
0.009
970879AG2-548 GEN
Solar/Wind Harmer
6.645
253372AE2-315 SEC3
Adder
1.989
253372AE2-315 SEC3
Adder
1.989
25306009OHH W.
Adder
3.018
253349AC2-067 GEN
Solar/Wind Harmer
2.296
253400AC2-068 GEN
Solar/Wind Harmer
0.923
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
0.92
965051AG1-369 GEN
Solar/Wind Harmer
3.609
971567AH1-282 GEN
Solar/Wind Harmer
10.843
247607V1-011 GEN
Solar/Wind Harmer
0.001
965041AG1-368 GEN
Solar/Wind Harmer
7.21
971989AH1-539 GEN
Solar/Wind Harmer
3.109
963791AG1-232 GEN
Solar/Wind Harmer
9.689
24729505KEY G4
Adder
6.671
270071AF1-092 GEN
Solar/Wind Harmer
13.737
270024AE2-089 GEN
Solar/Wind Harmer
0.008
971985AH1-537 GEN
Solar/Wind Harmer
2.123
965101AG1-375 GEN
Solar/Wind Harmer
7.135
270297AD1-101 GEN
Solar/Wind Harmer
0.002
270367AC2-061_GEN
Solar/Wind Harmer
0.006
971673AH1-337 GEN
Solar/Wind Harmer
4.631
971029AG2-637 GEN
Solar/Wind Harmer
10.686
270543AE2-219 C
Solar/Wind Harmer
0.004
252524AE2-267 GEN
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
9.002
25196308WSDLE2
Adder
8.924
25196208WSDLE1
Adder
8.902
25196708WSDLE6
Adder
8.879
25196508WSDLE4
Adder
8.656
945581AF1-223 GEN
Solar/Wind Harmer
0.001
971347AH1-153 GEN
Solar/Wind Harmer
10.632
971609AH1-304 GEN
Solar/Wind Harmer
1.157
270240V3-007_GEN2
Solar/Wind Harmer
0.002
970115AG2-085 GEN
Solar/Wind Harmer
2.826
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
270594AE1-207 GEN
Solar/Wind Harmer
7.898
971771AH1-392 GEN
Solar/Wind Harmer
7.046
970289AG2-191 GEN
Solar/Wind Harmer
1.339
971619AH1-309 GEN
Solar/Wind Harmer
3.169
971769AH1-391 GEN
Solar/Wind Harmer
7.844
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
25196108MFTGT2
Adder
1.54
25196108MFTGT2
Adder
1.43
270536AF1-215 GEN2
Solar/Wind Harmer
0.009
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
4.146
971549AH1-272 GEN
Solar/Wind Harmer
14.344
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
8.364
274776LINCOLN ;7U
Adder
8.364
274777LINCOLN ;8U
Adder
8.364
274814UNIV PK N;0U
Adder
4.998
274807UNIV PK N;3U
Adder
4.987
274805UNIV PK N;1U
Adder
4.965
274811UNIV PK N;7U
Adder
4.954
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
972037AH1-567 GEN1
Adder
0.181
960591AF2-350 GEN
Solar/Wind Harmer
6.884
274827FISK ;RP
Adder
7.655
972227AH1-698 GEN1
Adder
2.573
963841AG1-237 GEN
Solar/Wind Harmer
2.978
274687WILL CNTY;4U
Adder
27.495
274687WILL CNTY;4U
Adder
27.495
274675JOLIET 29;7U
Adder
30.175
274675JOLIET 29;7U
Adder
29.097
972163AH1-664 GEN
Solar/Wind Harmer
7.639
972165AH1-665 GEN
Solar/Wind Harmer
6.118
274731ELWOOD EC;2P
Adder
16.163
274733ELWOOD EC;3P
Adder
16.163
274735ELWOOD EC;4P
Adder
16.163
274728ELWOOD EC;5P
Adder
16.163
970833AG2-524 GEN
Solar/Wind Harmer
7.542
970833AG2-524 GEN
Solar/Wind Harmer
5.028
945641AF1-229 GEN
Solar/Wind Harmer
0.001
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
276868AE1-113 GEN
Solar/Wind Harmer
1.363
276882AE2-255 GEN
Solar/Wind Harmer
0.794
238109AE1-109 GEN2
Solar/Wind Helper
0.106
238110AE1-109 GEN3
Solar/Wind Helper
0.106
238152AF2-075_GEN
Solar/Wind Helper
0.683
23546401DTGZ2-030
Solar/Wind Helper
0.086
238208AF1-136 C
Solar/Wind Helper
0.211
238126S14_GEN_1
Solar/Wind Helper
0.766
237085AD2-009_GEN
Solar/Wind Helper
1.588
3138216PACIFIC
Solar/Wind Helper
0.043
316411AF1-147_GEN1
Solar/Wind Helper
0.86
316415AF1-147_GEN2
Solar/Wind Helper
0.86
959381AF2-229 GEN
Solar/Wind Helper
0.345
23750501ELLIOTTS
Solar/Wind Helper
0.571
3141426STAFORD
Solar/Wind Helper
0.051
960921AF2-383 GEN
Solar/Wind Helper
0.352
926881AC1-175 GEN
Solar/Wind Harmer
0.001
970825AG2-519 GEN
Solar/Wind Harmer
7.834
960441AF2-335 GEN
Solar/Wind Harmer
7.065
270216AD2-079_GEN
Solar/Wind Harmer
0.001
971613AH1-306 GEN
Solar/Wind Harmer
3.385
24728805RICHG1
Adder
3.82
24728905RICHG2
Adder
3.82
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
14.072
961051AF2-396 GEN
Solar/Wind Harmer
9.381
270526AF1-158 GEN
Solar/Wind Harmer
0.009
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
8.77
965791AG1-447 GEN
Solar/Wind Harmer
6.431
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
970239AG2-162 GEN
Solar/Wind Harmer
1.73
274770LINCOLN ;1U
Adder
8.364
274771LINCOLN ;2U
Adder
8.364
274808UNIV PK N;4U
Adder
4.933
966841AG1-555 GEN
Solar/Wind Harmer
0.781
274803UNIV PARK;6U
Adder
5.755
274888KELLY CRK;1U
Solar/Wind Harmer
0.404
274887GEN-1.85
Solar/Wind Harmer
0.181
276843GEN-1.7
Solar/Wind Harmer
0.223
958011AF2-095 GEN
Solar/Wind Harmer
9.913
972259AH1-714 GEN
Adder
18.805
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
970241AG2-163 GEN
Solar/Wind Harmer
3.993
958481AF2-142 GEN
Solar/Wind Harmer
10.238
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.923
971573AH1-285 GEN
Solar/Wind Harmer
1.271
971677AH1-339 GEN
Solar/Wind Harmer
0.768
958491AF2-143 GEN
Solar/Wind Harmer
10.205
274879MINONK ;1U
Solar/Wind Harmer
0.287
238175AF1-290_GEN
Solar/Wind Helper
0.148
238169AE2-226 GEN1
Solar/Wind Helper
0.677
238170AE2-226 GEN2
Solar/Wind Helper
0.677
238120AE2-309 GEN
Solar/Wind Helper
0.487
235020AA1-095 C
Solar/Wind Helper
0.051
23777901MDS_W4-102
Solar/Wind Helper
0.171
23585401KL_K28_T16
Solar/Wind Helper
1.328
237034AC2-136 C
Solar/Wind Helper
0.219
237002AB1-128_GEN
Solar/Wind Helper
0.427
235063AE1-101 C2
Solar/Wind Helper
1.6
237001AB1-127_GEN
Solar/Wind Helper
0.426
23777801MSM_W1-116
Solar/Wind Helper
0.11
237025AB1-124 C
Solar/Wind Helper
0.159
237006AB1-125 GEN
Solar/Wind Helper
0.119
226929AD2-058 GEN
Solar/Wind Helper
0.096
205916AD1-020 GEN
Solar/Wind Helper
1.656
20390526W1-045 C
Solar/Wind Helper
0.338
208835TUHI V3-051
Solar/Wind Helper
0.023
208835TUHI V3-051
Solar/Wind Helper
0.023
233987AB2-037 GEN
Solar/Wind Helper
2.264
233933AB2-153 GEN
Solar/Wind Helper
0.225
232424Y1-079 C
Solar/Wind Helper
0.112
233944AB2-135 GEN
Solar/Wind Helper
0.569
233946AB2-136 GEN
Solar/Wind Helper
0.549
234036AF2-325 C
Solar/Wind Helper
0.041
233901CHERRYDALE C
Solar/Wind Helper
0.225
232408W1-005 C
Solar/Wind Helper
0.49
232410W1-006 C
Solar/Wind Helper
0.49
233939AC1-091 C
Solar/Wind Helper
0.338
233970AC1-092 C
Solar/Wind Helper
0.338
315651AD1-115 GEN
Solar/Wind Helper
0.76
316447AC1-158 HLD
Solar/Wind Helper
2.756
230433AD2-135 GEN
Solar/Wind Helper
0.016
230407AD2-065 C
Solar/Wind Helper
0.039
219921AF1-264
Solar/Wind Helper
0.049
219615MILLCREEK C
Solar/Wind Helper
0.026
963401AG1-189 GEN
Solar/Wind Helper
0.054
963391AG1-188 GEN
Solar/Wind Helper
0.079
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.183
274752CRETE EC ;2U
Adder
8.172
274753CRETE EC ;3U
Adder
8.172
274772LINCOLN ;3U
Adder
8.364
274724RIVER EC ;11
Adder
17.549
958171AF2-111 GEN
Solar/Wind Harmer
17.278
274802UNIV PARK;5U
Adder
5.755
276806AD2-047 C O1
Solar/Wind Harmer
3.901
970941AG2-585 GEN
Solar/Wind Harmer
8.605
274826FISK ;BP
Adder
10.802
24728705AND G3
Adder
7.914
24728505AND G1
Adder
3.784
274800UNIV PARK;3U
Adder
5.751
972038AH1-567 GEN2
Adder
0.36
972228AH1-698 GEN2
Adder
3.654
972167AH1-666 GEN
Solar/Wind Harmer
5.505
276897AD1-100 C
Solar/Wind Harmer
0.009
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
22.464
274676JOLIET 29;8U
Adder
29.097
274729ELWOOD EC;1P
Adder
16.163
274730ELWOOD EC;6P
Adder
13.491
276893AG1-478 C
Solar/Wind Harmer
0.272
270541AE2-072 C
Solar/Wind Harmer
0.009
943121AE2-341 GEN
Solar/Wind Harmer
11.459
943591AF1-030 GEN
Solar/Wind Harmer
7.62
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
276805AD2-038 GEN
Solar/Wind Harmer
0.002
964991AG1-363 GEN
Solar/Wind Helper
4.969
316097T157 G90
Solar/Wind Helper
1.455
23750701CROSSCHOOL
Solar/Wind Helper
1.397
238148AE2-230_GEN2
Solar/Wind Helper
0.48
238127S14_GEN_2
Solar/Wind Helper
0.766
238118U2-030_1
Solar/Wind Helper
0.314
237080AD1-060 GEN
Solar/Wind Helper
0.33
237038AE2-054 C
Solar/Wind Helper
0.262
235062AE1-101 C1
Solar/Wind Helper
1.6
23779801AA1-109
Solar/Wind Helper
0.187
223401AF1-299 GEN
Solar/Wind Helper
0.355
316006AB2-029 C
Solar/Wind Helper
0.113
966131AG1-482 GEN
Solar/Wind Helper
0.132
237048AF1-022 C
Solar/Wind Helper
0.159
233930AB2-032 GEN
Solar/Wind Helper
0.368
233915AB1-141 GEN
Solar/Wind Helper
0.486
232422X3-066 FULL
Solar/Wind Helper
0.11
232426Y1-080 FULL
Solar/Wind Helper
0.038
233964AF2-378 GEN
Solar/Wind Helper
0.04
233998TM1NIN_3.36
Solar/Wind Helper
0.253
232404W1-003 C
Solar/Wind Helper
0.49
232428Y3-058 C
Solar/Wind Helper
0.327
232434Z2-077 GEN
Solar/Wind Helper
0.123
233954AC2-188 GEN
Solar/Wind Helper
0.225
233950AC2-186 GEN
Solar/Wind Helper
0.112
233972AC1-094 C
Solar/Wind Helper
0.292
316045AC1-158 PL2
Solar/Wind Helper
4.009
230511AF1-262
Solar/Wind Helper
0.014
230434AG1-499 GEN
Solar/Wind Helper
0.222
228728W1-130C
Solar/Wind Helper
0.052
219258KINSLEYDEP C
Solar/Wind Helper
0.074
219904AC1-010 C
Solar/Wind Helper
0.058
218660EHAMPSOLAR C
Solar/Wind Helper
0.032
219907AC1-030 C
Solar/Wind Helper
0.033
219686LUMSOLAR_N C
Solar/Wind Helper
0.038
219304NAMERICA C
Solar/Wind Helper
0.127
316254AC1-120 GEN1
Solar/Wind Helper
1.026
20720728JCB_W1-129
Solar/Wind Helper
0.055
207445AB1-138_GEN
Solar/Wind Helper
0.101
963711AG1-223 GEN
Solar/Wind Helper
0.062
20714828MDF_W3-079
Solar/Wind Helper
0.126
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.299
20715228NPK_W1-113
Solar/Wind Helper
0.075
205943AE1-185 GEN
Solar/Wind Helper
0.492
205956AE1-196_GEN
Solar/Wind Helper
0.492
205932AD2-116_GEN
Solar/Wind Helper
0.492
233935AB2-179 C
Solar/Wind Helper
1.227
232436AB1-176 C
Solar/Wind Helper
0.043
233923SMA
Solar/Wind Helper
0.927
233990AG1-397 GEN
Solar/Wind Helper
0.261
234033AF1-007_GEN
Solar/Wind Helper
6.787
232432Z2-076 GEN
Solar/Wind Helper
0.065
964001AG1-254 GEN
Solar/Wind Helper
0.924
228754AB1-001 C
Solar/Wind Helper
0.025
227927V4-067C
Solar/Wind Helper
0.01
219914AD2-027 C
Solar/Wind Helper
0.111
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.038
219607WPEMNERT C
Solar/Wind Helper
0.077
214067T20SOLAR
Solar/Wind Helper
0.011
203975AE1-071-GEN
Solar/Wind Helper
2.41
20715728PEM_W1-119
Solar/Wind Helper
0.093
20715828PEM_W1-120
Solar/Wind Helper
0.093
207459AE1-142 C O1
Solar/Wind Helper
0.28
316164AC1-076 GEN
Solar/Wind Helper
1.062
219620RIDERU C
Solar/Wind Helper
0.001
LAGNLTFEXP_LAGN->PJM
CLTF
14.268
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.432
TVALTFEXP_TVA->PJM
CLTF
7.011
CPLELTFEXP_CPLE->PJM
CLTF
0.567
CBM West 2LTFEXP_CBM-W2->PJM
CBM
108.576
CBM West 1LTFEXP_CBM-W1->PJM
CBM
137.982
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.984
MECLTFEXP_MEC->PJM
CLTF
15.319
SIGELTFEXP_SIGE->PJM
CLTF
0.486
NYPJM->LTFIMP_NY
CLTF
4.628
LGEELTFEXP_LGEE->PJM
CLTF
6.497
WECLTFEXP_WEC->PJM
CLTF
3.686
AG2-052LTFEXP_AG2-052->PJM
LTF
0.231
AH1-155LTFEXP_AH1-155->PJM
LTF
0.346

Details for 05W.NEWTONSS-05E LIMA 138.0 kV Ckt 1 line l/o AEP_P4_#13372_05N WALDO 69.0_A_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05W.NEWTONSS-05E LIMA 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#13372_05N WALDO 69.0_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.71 %
Rating:183.0 MVA
Rating Type:B
MVA to Mitigate:209.92
MW Contribution:5.09
Bus #Bus NameTypeMW Contribution
971231AH1-075 GEN
Solar/Wind Harmer
5.086
971677AH1-339 GEN
Solar/Wind Harmer
9.591
966831AG1-554 GEN
Solar/Wind Harmer
7.723
971989AH1-539 GEN
Solar/Wind Harmer
83.507
247522W1-056 GEN
Solar/Wind Harmer
5.342
270588AE1-091_GEN
Solar/Wind Harmer
79.007
270377AD1-106 GEN
Solar/Wind Harmer
39.257
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.063
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.196
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
0.051
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.159
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
0.14
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.018
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.266
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.026

Details for 05W.NEWTONSS-05E LIMA 138.0 kV Ckt 1 line l/o AEP_P2-2_#14773_05N WALDO 69.0_1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05W.NEWTONSS-05E LIMA 138.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#14773_05N WALDO 69.0_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:114.01 %
Rating:183.0 MVA
Rating Type:B
MVA to Mitigate:208.64
MW Contribution:5.09
Bus #Bus NameTypeMW Contribution
247522W1-056 GEN
Solar/Wind Harmer
5.342
270588AE1-091_GEN
Solar/Wind Harmer
79.007
270377AD1-106 GEN
Solar/Wind Harmer
39.257
971231AH1-075 GEN
Solar/Wind Harmer
5.086
971677AH1-339 GEN
Solar/Wind Harmer
9.591
966831AG1-554 GEN
Solar/Wind Harmer
7.723
971989AH1-539 GEN
Solar/Wind Harmer
83.507
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.063
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.196
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
0.051
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.159
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
0.14
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.018
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.266
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.026

Details for 05W.NEWTONSS-05E LIMA 138.0 kV Ckt 1 line l/o AEP_P4_#10732_05WMTVER 138_A_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05W.NEWTONSS-05E LIMA 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10732_05WMTVER 138_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.59 %
Rating:183.0 MVA
Rating Type:B
MVA to Mitigate:207.88
MW Contribution:5.09
Bus #Bus NameTypeMW Contribution
971231AH1-075 GEN
Solar/Wind Harmer
5.086
971677AH1-339 GEN
Solar/Wind Harmer
9.598
966831AG1-554 GEN
Solar/Wind Harmer
7.723
971989AH1-539 GEN
Solar/Wind Harmer
83.512
247522W1-056 GEN
Solar/Wind Harmer
5.343
270588AE1-091_GEN
Solar/Wind Harmer
79.011
270377AD1-106 GEN
Solar/Wind Harmer
39.26
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.063
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.197
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
0.052
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.16
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
0.141
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.018
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.267
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.026

Details for 05W.NEWTONSS-05E LIMA 138.0 kV Ckt 1 line l/o AEP_P4_#5710_05WMTVER 138_B_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05W.NEWTONSS-05E LIMA 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#5710_05WMTVER 138_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.86 %
Rating:183.0 MVA
Rating Type:B
MVA to Mitigate:184.57
MW Contribution:4.39
Bus #Bus NameTypeMW Contribution
247522W1-056 GEN
Solar/Wind Harmer
5.404
270588AE1-091_GEN
Solar/Wind Harmer
76.492
270377AD1-106 GEN
Solar/Wind Harmer
33.915
966831AG1-554 GEN
Solar/Wind Harmer
7.312
971989AH1-539 GEN
Solar/Wind Harmer
79.066
971231AH1-075 GEN
Solar/Wind Harmer
4.394
971677AH1-339 GEN
Solar/Wind Harmer
10.153
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.075
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.233
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
0.075
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.22
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
0.204
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.02
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.317
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.029

Details for 05W.NEWTONSS-05E LIMA 138.0 kV Ckt 1 line l/o AEP_P2-2_#5710_05WMTVER 138_1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05W.NEWTONSS-05E LIMA 138.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#5710_05WMTVER 138_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:100.85 %
Rating:183.0 MVA
Rating Type:B
MVA to Mitigate:184.56
MW Contribution:4.39
Bus #Bus NameTypeMW Contribution
247522W1-056 GEN
Solar/Wind Harmer
5.404
966831AG1-554 GEN
Solar/Wind Harmer
7.312
971989AH1-539 GEN
Solar/Wind Harmer
79.066
270588AE1-091_GEN
Solar/Wind Harmer
76.492
270377AD1-106 GEN
Solar/Wind Harmer
33.915
971231AH1-075 GEN
Solar/Wind Harmer
4.394
971677AH1-339 GEN
Solar/Wind Harmer
10.153
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.075
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.233
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
0.075
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.22
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
0.204
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.02
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.317
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.029

Details for AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line l/o ATSI_P2-3_OEC-345-009_SRT-SL


Base Case Flowgate

Area:ATSI
Facility Description:
AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_OEC-345-009_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:165.39 %
Rating:1499.0 MVA
Rating Type:B
MVA to Mitigate:2479.15
MW Contribution:0.38
Bus #Bus NameTypeMW Contribution
23867002DVBSG1
50/50
12.736
972211AH1-690 GEN
50/50
275.935
23888502TROY G1
50/50
1.742
23888602TROY G2
50/50
1.742
23860102FRMENG 1
50/50
1.188
23860202FRMENG 2
50/50
1.188
24189902OREGON_CT2
50/50
2.559
23888702TROY G3
50/50
1.742
972253AH1-711 GEN
50/50
53.201
23856402BAYSG1
50/50
1.289
23920202STRYCT
50/50
1.895
23860302FRMENG 3
50/50
2.426
241885AC2-103 GEN1
Solar/Wind Harmer
25.595
241858AF1-205_GEN
Solar/Wind Harmer
5.472
241808AF1-120 C
Solar/Wind Harmer
1.197
241840AF1-064_GEN
Solar/Wind Harmer
1.39
972301AH1-735 GEN
Adder
6.573
23906402RICHG1
Adder
1.315
23906502RICHG2&3
Adder
1.312
270361_3
Solar/Wind Harmer
8.607
960841AF2-375 GEN
Solar/Wind Harmer
3.799
241807AE2-176_GEN
Solar/Wind Harmer
3.58
247522W1-056 GEN
Solar/Wind Harmer
1.591
970515AG2-329 GEN
Solar/Wind Harmer
10.186
944231AF1-091 GEN
Solar/Wind Harmer
2.443
270428AC2-015 C
Solar/Wind Harmer
3.305
246936BC-WTG1
Solar/Wind Harmer
2.263
270489AE1-102 GEN1
Solar/Wind Harmer
0.752
965421AG1-410 GEN
Solar/Wind Harmer
17.181
270449AD2-020 GEN
Solar/Wind Harmer
1.572
943021AE2-325 GEN
Solar/Wind Harmer
2.042
24695305TIMB G C
Solar/Wind Harmer
3.08
945111AF1-176 GEN
Solar/Wind Harmer
9.795
270505AE1-170 C O1
Solar/Wind Harmer
8.226
247521TR3_G114
Solar/Wind Harmer
1.816
270246TR4_N_V150
Solar/Wind Harmer
0.459
24639705ELKHART HY
Adder
0.082
270063AE2-323 C
Solar/Wind Harmer
1.171
965011AG1-365 GEN
Solar/Wind Harmer
5.199
270462AD2-086
Solar/Wind Harmer
3.617
270223U2-072_GEN1
Solar/Wind Harmer
0.952
270578AF1-285 GEN2
Solar/Wind Harmer
0.582
270391AF1-285 GEN3
Solar/Wind Harmer
0.582
970905AG2-564 GEN
Solar/Wind Harmer
2.368
970373AG2-245 GEN
Solar/Wind Harmer
9.864
270055AF2-134 C O1
Solar/Wind Harmer
1.395
274751CRETE EC ;1U
Adder
2.22
274754CRETE EC ;4U
Adder
2.22
958381AF2-132 GEN
Solar/Wind Harmer
4.106
964861AG1-349 GEN
Solar/Wind Harmer
3.551
971917AH1-482 GEN
Solar/Wind Harmer
4.098
274723RIVER EC ;12
Adder
8.075
274812UNIV PK N;8U
Adder
2.246
276164X3-005 C
Solar/Wind Harmer
0.314
274801UNIV PARK;4U
Adder
2.578
940581AE2-045 GEN
Solar/Wind Harmer
4.504
276776AD2-060 GEN
Solar/Wind Harmer
0.187
971605AH1-302 GEN
Solar/Wind Harmer
3.851
972207SS24-0001
Solar/Wind Harmer
9.729
274773LINCOLN ;4U
Adder
2.736
274774LINCOLN ;5U
Adder
2.736
241847AF2-150_GEN
Solar/Wind Harmer
1.821
274676JOLIET 29;8U
Adder
13.435
941551AE2-152 GEN
Solar/Wind Harmer
1.984
274732ELWOOD EC;7P
Adder
7.185
274674JOLIET 9 ;6U
Adder
6.73
24190002OREGON_ST1
50/50
3.442
24189802OREGON_CT1
50/50
2.611
23888802TROY G4
50/50
1.742
241996AE2-282_GEN
Solar/Wind Harmer
2.147
971677AH1-339 GEN
Solar/Wind Harmer
6.747
270007AE1-245 C
Solar/Wind Harmer
3.464
942801AE2-298 GEN
Solar/Wind Harmer
0.877
246938BC-WTG3
Solar/Wind Harmer
2.302
246937BC-WTG2
Solar/Wind Harmer
2.263
961051AF2-396 GEN
Solar/Wind Harmer
8.832
961051AF2-396 GEN
Solar/Wind Harmer
4.108
960981AF2-389 GEN
Solar/Wind Harmer
0.827
957891AF2-083 GEN
Solar/Wind Harmer
1.844
247620Y3-023
Adder
0.247
270216AD2-079_GEN
Solar/Wind Harmer
0.32
970611AG2-400 GEN
Solar/Wind Harmer
5.199
270526AF1-158 GEN
Solar/Wind Harmer
2.317
24441505OLIV SLR
Solar/Wind Harmer
0.068
965681AG1-436 GEN
Solar/Wind Harmer
6.102
965791AG1-447 GEN
Solar/Wind Harmer
3.122
270224U2-072_GEN2
Solar/Wind Harmer
0.952
270227U2-072_GEN3
Solar/Wind Harmer
0.952
270228U2-072_GEN4
Solar/Wind Harmer
0.952
270231U2-072_GEN5
Solar/Wind Harmer
0.952
971231AH1-075 GEN
Solar/Wind Harmer
0.379
274808UNIV PK N;4U
Adder
2.237
274803UNIV PARK;6U
Adder
2.587
274888KELLY CRK;1U
Solar/Wind Harmer
2.607
274887GEN-1.85
Solar/Wind Harmer
2.354
276843GEN-1.7
Solar/Wind Harmer
0.253
958011AF2-095 GEN
Solar/Wind Harmer
6.358
274770LINCOLN ;1U
Adder
2.736
274771LINCOLN ;2U
Adder
2.736
942221AE2-234 GEN
Solar/Wind Harmer
0.323
972259AH1-714 GEN
Adder
8.361
274674JOLIET 9 ;6U
Adder
6.73
970321AG2-212 GEN
Solar/Wind Harmer
7.784
274847GR RIDGE ;BU
Solar/Wind Harmer
2.199
203947AF1-006 C
Solar/Wind Helper
0.379
203980AG1-197 GEN
Solar/Wind Helper
0.248
203979AG1-198 GEN
Solar/Wind Helper
0.193
241967AE2-285_GEN
Solar/Wind Helper
0.337
241801AE1-079 GEN
Solar/Wind Helper
0.131
241985AE1-237 GEN
Solar/Wind Helper
0.131
962101AG1-054 GEN
Solar/Wind Helper
0.325
946381AF1-302 GEN
Solar/Wind Helper
0.105
238217AF1-153 C O1
Solar/Wind Helper
0.111
23929302BS-PKR
50/50
2.268
241832AE2-181_GEN
Solar/Wind Harmer
1.946
958321AF2-126 GEN
Solar/Wind Harmer
1.49
23906502RICHG2&3
Adder
1.312
270575GUS2 35KV
Solar/Wind Harmer
10.14
270541AE2-072 C
Solar/Wind Harmer
4.319
970217AG2-149 GEN
Solar/Wind Harmer
22.462
270044AE2-322 C
Solar/Wind Harmer
0.849
270404AC1-167 GEN
Solar/Wind Harmer
0.707
270588AE1-091_GEN
Solar/Wind Harmer
6.832
270258AD1-119 GEN
Solar/Wind Harmer
1.729
247604X1-042
Adder
0.25
24441205WTRV SLR C
Solar/Wind Harmer
0.079
958091AF2-103 GEN
Solar/Wind Harmer
0.094
270491AE1-102 GEN2
Solar/Wind Harmer
0.752
945111AF1-176 GEN
Solar/Wind Harmer
3.104
270191TR4_S_V150
Solar/Wind Harmer
1.62
270247TR4_N_V136
Solar/Wind Harmer
0.459
24642205MAYFLWER
Adder
0.339
970031AG2-029 GEN
Solar/Wind Harmer
15.896
247643Z2-116 C
Solar/Wind Harmer
0.037
959331AF2-224 GEN
Solar/Wind Harmer
5.199
965021AG1-366 GEN
Solar/Wind Harmer
1.209
270485AE1-090_GEN
Solar/Wind Harmer
0.314
270043AE2-236 GEN
Solar/Wind Harmer
2.698
970349AG2-230 GEN
Solar/Wind Harmer
7.29
942871AE2-306 GEN
Solar/Wind Harmer
0.437
270391AF1-285 GEN3
Solar/Wind Harmer
0.224
270377AD1-106 GEN
Solar/Wind Harmer
2.928
270535AF1-215 GEN1
Solar/Wind Harmer
2.093
972231SS25-0005
Solar/Wind Harmer
4.31
972181SS23-001
Solar/Wind Harmer
2.694
274752CRETE EC ;2U
Adder
2.22
274753CRETE EC ;3U
Adder
2.22
964401AG1-302 GEN
Solar/Wind Harmer
4.106
274724RIVER EC ;11
Adder
7.979
959141AF2-205 GEN
Solar/Wind Harmer
2.693
274802UNIV PARK;5U
Adder
2.587
274826FISK ;BP
Adder
4.849
274800UNIV PARK;3U
Adder
2.578
972038AH1-567 GEN2
Adder
0.161
276772AC2-154 GEN
Solar/Wind Harmer
1.231
276806AD2-047 C O1
Solar/Wind Harmer
4.723
970941AG2-585 GEN
Solar/Wind Harmer
5.519
274772LINCOLN ;3U
Adder
2.736
972228AH1-698 GEN2
Adder
1.631
961961AG1-039 GEN
Solar/Wind Harmer
1.256
274676JOLIET 29;8U
Adder
12.955
276897AD1-100 C
Solar/Wind Harmer
12.695
939351AE1-166 GEN
Solar/Wind Harmer
2.594
276893AG1-478 C
Solar/Wind Harmer
0.183
274730ELWOOD EC;6P
Adder
7.185
274734ELWOOD EC;8P
Adder
7.185
274736ELWOOD EC;9P
Adder
7.185
970707AG2-453 GEN
Solar/Wind Harmer
12.238
274729ELWOOD EC;1P
Adder
7.185
970513AG2-328 GEN
Solar/Wind Harmer
7.784
970517AG2-330 GEN
Solar/Wind Harmer
7.06
971617AH1-308 GEN
Solar/Wind Harmer
2.534
962511AG1-100 GEN
Solar/Wind Helper
0.34
203830AF1-094 GEN
Solar/Wind Helper
0.322
959441AF2-235 GEN
Solar/Wind Helper
0.146
254305AE2-115 C
Solar/Wind Helper
0.112
20334926Z1-069 C
Solar/Wind Helper
0.641
943121AE2-341 GEN
Solar/Wind Harmer
2.014
943591AF1-030 GEN
Solar/Wind Harmer
1.343
970245AG2-165 GEN
Solar/Wind Harmer
7.784
274871GR RIDGE ;2U
Solar/Wind Harmer
3.343
274745AC1-111 GEN9
Adder
2.416
961971AG1-040 GEN
Solar/Wind Helper
0.333
203835AF1-098 GEN
Solar/Wind Helper
1.311
203860AG1-193 C
Solar/Wind Helper
0.149
241966AE1-183 GEN
Solar/Wind Helper
0.129
254303AC2-168 GEN
Solar/Wind Helper
0.075
241886AC2-103 GEN2
Solar/Wind Harmer
25.595
970817AG2-515 GEN
Solar/Wind Harmer
14.806
945411AF1-206 GEN
Solar/Wind Harmer
8.02
270499AE1-146 GEN
Solar/Wind Harmer
2.385
945641AF1-229 GEN
Solar/Wind Harmer
3.427
971549AH1-272 GEN
Solar/Wind Harmer
12.688
270297AD1-101 GEN
Solar/Wind Harmer
1.9
966831AG1-554 GEN
Solar/Wind Harmer
0.712
971989AH1-539 GEN
Solar/Wind Harmer
7.704
247607V1-011 GEN
Solar/Wind Harmer
2.309
957201AF2-014 GEN
Solar/Wind Harmer
2.623
270435AC2-044 GEN
Solar/Wind Harmer
1.157
944161AF1-084 GEN
Solar/Wind Harmer
1.256
24191202EL_AA1-006
Adder
0.123
965041AG1-368 GEN
Solar/Wind Harmer
5.428
965051AG1-369 GEN
Solar/Wind Harmer
2.697
971771AH1-392 GEN
Solar/Wind Harmer
4.684
270302AB2-170 GEN
Solar/Wind Harmer
4.348
270317AD1-130_GEN
Solar/Wind Harmer
1.667
971567AH1-282 GEN
Solar/Wind Harmer
7.657
971769AH1-391 GEN
Solar/Wind Harmer
5.074
960681AF2-359 GEN
Solar/Wind Harmer
1.844
971347AH1-153 GEN
Solar/Wind Harmer
7.29
963791AG1-232 GEN
Solar/Wind Harmer
6.504
270578AF1-285 GEN2
Solar/Wind Harmer
0.224
270536AF1-215 GEN2
Solar/Wind Harmer
2.093
270071AF1-092 GEN
Solar/Wind Harmer
6.841
274814UNIV PK N;0U
Adder
2.266
274807UNIV PK N;3U
Adder
2.261
274805UNIV PK N;1U
Adder
2.251
274811UNIV PK N;7U
Adder
2.246
958391AF2-133 GEN
Solar/Wind Harmer
4.069
972037AH1-567 GEN1
Adder
0.081
274827FISK ;RP
Adder
3.436
960591AF2-350 GEN
Solar/Wind Harmer
4.415
274775LINCOLN ;6U
Adder
2.736
274776LINCOLN ;7U
Adder
2.736
274777LINCOLN ;8U
Adder
2.736
972227AH1-698 GEN1
Adder
1.148
274687WILL CNTY;4U
Adder
12.261
274687WILL CNTY;4U
Adder
12.261
274675JOLIET 29;7U
Adder
13.435
274675JOLIET 29;7U
Adder
12.955
274728ELWOOD EC;5P
Adder
7.185
274731ELWOOD EC;2P
Adder
7.185
274733ELWOOD EC;3P
Adder
7.185
274735ELWOOD EC;4P
Adder
7.185
270024AE2-089 GEN
Solar/Wind Harmer
2.045
970833AG2-524 GEN
Solar/Wind Harmer
3.797
970833AG2-524 GEN
Solar/Wind Harmer
1.766
274746AC1-111 G10
Adder
2.416
274744AC1-111 GEN8
Adder
2.416
241982AE2-343 S C
Solar/Wind Helper
0.117
254304AE2-114 C
Solar/Wind Helper
0.112
203846AF2-130 C
Solar/Wind Helper
0.246
241997AF1-093 GEN
Solar/Wind Helper
0.129
203804AE2-113_GEN
Solar/Wind Helper
0.861
991182J1586 G
External Queue
23.962841033935547
990527J1329
External Queue
1.7522491216659546
990142J1224
External Queue
12.808939933776855
991177J1571 G
External Queue
14.786787033081055
LAGNLTFEXP_LAGN->PJM
CLTF
4.78
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.107
TVALTFEXP_TVA->PJM
CLTF
2.169
CPLELTFEXP_CPLE->PJM
CLTF
0.311
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.23
CBM West 1LTFEXP_CBM-W1->PJM
CBM
90.542
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.6
MECLTFEXP_MEC->PJM
CLTF
6.243
SIGELTFEXP_SIGE->PJM
CLTF
0.163
NYPJM->LTFIMP_NY
CLTF
2.01
LGEELTFEXP_LGEE->PJM
CLTF
1.95
WECLTFEXP_WEC->PJM
CLTF
1.601
AG2-052LTFEXP_AG2-052->PJM
LTF
0.103
AH1-155LTFEXP_AH1-155->PJM
LTF
0.155

Details for AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line l/o ATSI_P2-3_OEC-345-1152-3_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_OEC-345-1152-3_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:142.16 %
Rating:1798.0 MVA
Rating Type:B
MVA to Mitigate:2556.01
MW Contribution:0.37
Bus #Bus NameTypeMW Contribution
24189902OREGON_CT2
50/50
2.596
23888702TROY G3
50/50
1.764
972253AH1-711 GEN
50/50
53.875
23856402BAYSG1
50/50
1.286
23920202STRYCT
50/50
1.905
241885AC2-103 GEN1
Solar/Wind Harmer
25.888
241858AF1-205_GEN
Solar/Wind Harmer
5.501
241808AF1-120 C
Solar/Wind Harmer
1.204
241840AF1-064_GEN
Solar/Wind Harmer
1.392
972301AH1-735 GEN
Adder
6.601
23906402RICHG1
Adder
1.32
23906502RICHG2&3
Adder
1.318
270361_3
Solar/Wind Harmer
8.502
960841AF2-375 GEN
Solar/Wind Harmer
3.755
241807AE2-176_GEN
Solar/Wind Harmer
2.785
247522W1-056 GEN
Solar/Wind Harmer
1.573
970515AG2-329 GEN
Solar/Wind Harmer
10.138
944231AF1-091 GEN
Solar/Wind Harmer
2.455
246936BC-WTG1
Solar/Wind Harmer
2.271
270489AE1-102 GEN1
Solar/Wind Harmer
0.755
965421AG1-410 GEN
Solar/Wind Harmer
17.247
270449AD2-020 GEN
Solar/Wind Harmer
1.583
943021AE2-325 GEN
Solar/Wind Harmer
2.057
23867002DVBSG1
50/50
13.062
972211AH1-690 GEN
50/50
279.989
23888502TROY G1
50/50
1.764
23888602TROY G2
50/50
1.764
241886AC2-103 GEN2
Solar/Wind Harmer
25.888
970817AG2-515 GEN
Solar/Wind Harmer
14.956
945411AF1-206 GEN
Solar/Wind Harmer
8.063
945641AF1-229 GEN
Solar/Wind Harmer
3.434
270499AE1-146 GEN
Solar/Wind Harmer
2.36
971549AH1-272 GEN
Solar/Wind Harmer
12.795
270297AD1-101 GEN
Solar/Wind Harmer
1.901
23929302BS-PKR
50/50
2.264
241832AE2-181_GEN
Solar/Wind Harmer
1.957
958321AF2-126 GEN
Solar/Wind Harmer
1.492
23906502RICHG2&3
Adder
1.318
270575GUS2 35KV
Solar/Wind Harmer
10.016
270541AE2-072 C
Solar/Wind Harmer
4.321
970217AG2-149 GEN
Solar/Wind Harmer
22.356
270044AE2-322 C
Solar/Wind Harmer
0.852
270404AC1-167 GEN
Solar/Wind Harmer
0.709
270258AD1-119 GEN
Solar/Wind Harmer
1.735
270588AE1-091_GEN
Solar/Wind Harmer
6.791
247604X1-042
Adder
0.252
24441205WTRV SLR C
Solar/Wind Harmer
0.08
958091AF2-103 GEN
Solar/Wind Harmer
0.095
270491AE1-102 GEN2
Solar/Wind Harmer
0.755
945111AF1-176 GEN
Solar/Wind Harmer
3.126
270191TR4_S_V150
Solar/Wind Harmer
1.626
270247TR4_N_V136
Solar/Wind Harmer
0.461
24642205MAYFLWER
Adder
0.342
970031AG2-029 GEN
Solar/Wind Harmer
15.991
247643Z2-116 C
Solar/Wind Harmer
0.037
959331AF2-224 GEN
Solar/Wind Harmer
5.223
965021AG1-366 GEN
Solar/Wind Harmer
1.215
270485AE1-090_GEN
Solar/Wind Harmer
0.315
270043AE2-236 GEN
Solar/Wind Harmer
2.712
970349AG2-230 GEN
Solar/Wind Harmer
7.336
942871AE2-306 GEN
Solar/Wind Harmer
0.438
270391AF1-285 GEN3
Solar/Wind Harmer
0.224
270377AD1-106 GEN
Solar/Wind Harmer
2.871
270535AF1-215 GEN1
Solar/Wind Harmer
2.105
972231SS25-0005
Solar/Wind Harmer
4.336
972181SS23-001
Solar/Wind Harmer
2.71
274752CRETE EC ;2U
Adder
2.233
274753CRETE EC ;3U
Adder
2.233
964401AG1-302 GEN
Solar/Wind Harmer
4.13
274724RIVER EC ;11
Adder
8.026
959141AF2-205 GEN
Solar/Wind Harmer
2.708
274802UNIV PARK;5U
Adder
2.602
274826FISK ;BP
Adder
4.877
274800UNIV PARK;3U
Adder
2.593
972038AH1-567 GEN2
Adder
0.162
276772AC2-154 GEN
Solar/Wind Harmer
1.239
276806AD2-047 C O1
Solar/Wind Harmer
4.751
970941AG2-585 GEN
Solar/Wind Harmer
5.551
274772LINCOLN ;3U
Adder
2.752
972228AH1-698 GEN2
Adder
1.64
274676JOLIET 29;8U
Adder
13.03
276897AD1-100 C
Solar/Wind Harmer
12.768
939351AE1-166 GEN
Solar/Wind Harmer
2.609
276893AG1-478 C
Solar/Wind Harmer
0.184
274729ELWOOD EC;1P
Adder
7.227
274730ELWOOD EC;6P
Adder
7.227
274734ELWOOD EC;8P
Adder
7.227
274736ELWOOD EC;9P
Adder
7.227
970707AG2-453 GEN
Solar/Wind Harmer
12.309
970513AG2-328 GEN
Solar/Wind Harmer
7.828
970517AG2-330 GEN
Solar/Wind Harmer
7.1
24190002OREGON_ST1
50/50
3.493
24189802OREGON_CT1
50/50
2.65
23888802TROY G4
50/50
1.764
241996AE2-282_GEN
Solar/Wind Harmer
2.159
971677AH1-339 GEN
Solar/Wind Harmer
6.666
270007AE1-245 C
Solar/Wind Harmer
3.473
942801AE2-298 GEN
Solar/Wind Harmer
0.88
246938BC-WTG3
Solar/Wind Harmer
2.311
246937BC-WTG2
Solar/Wind Harmer
2.271
961051AF2-396 GEN
Solar/Wind Harmer
8.895
961051AF2-396 GEN
Solar/Wind Harmer
4.137
960981AF2-389 GEN
Solar/Wind Harmer
0.832
957891AF2-083 GEN
Solar/Wind Harmer
1.857
247620Y3-023
Adder
0.249
270216AD2-079_GEN
Solar/Wind Harmer
0.322
970611AG2-400 GEN
Solar/Wind Harmer
5.223
270526AF1-158 GEN
Solar/Wind Harmer
2.332
24441505OLIV SLR
Solar/Wind Harmer
0.068
965681AG1-436 GEN
Solar/Wind Harmer
6.141
965791AG1-447 GEN
Solar/Wind Harmer
3.142
270224U2-072_GEN2
Solar/Wind Harmer
0.954
270227U2-072_GEN3
Solar/Wind Harmer
0.954
270228U2-072_GEN4
Solar/Wind Harmer
0.954
270231U2-072_GEN5
Solar/Wind Harmer
0.954
971231AH1-075 GEN
Solar/Wind Harmer
0.372
274808UNIV PK N;4U
Adder
2.25
274803UNIV PARK;6U
Adder
2.602
274888KELLY CRK;1U
Solar/Wind Harmer
2.622
274887GEN-1.85
Solar/Wind Harmer
2.367
276843GEN-1.7
Solar/Wind Harmer
0.255
958011AF2-095 GEN
Solar/Wind Harmer
6.395
274770LINCOLN ;1U
Adder
2.752
274771LINCOLN ;2U
Adder
2.752
942221AE2-234 GEN
Solar/Wind Harmer
0.324
972259AH1-714 GEN
Adder
8.409
274674JOLIET 9 ;6U
Adder
6.769
970321AG2-212 GEN
Solar/Wind Harmer
7.828
274847GR RIDGE ;BU
Solar/Wind Harmer
2.211
274696ROCKY RD ;4P
Adder
4.919
274695ROCKY RD ;2P
Adder
4.805
274693ROCKY RD ;1P
Adder
4.758
274697ROCKY RD ;3P
Adder
1.305
274683WAUKEGAN ;8U
Adder
9.089
274683WAUKEGAN ;8U
Adder
7.662
203947AF1-006 C
Solar/Wind Helper
0.379
203980AG1-197 GEN
Solar/Wind Helper
0.248
203979AG1-198 GEN
Solar/Wind Helper
0.193
241967AE2-285_GEN
Solar/Wind Helper
0.337
241801AE1-079 GEN
Solar/Wind Helper
0.131
241985AE1-237 GEN
Solar/Wind Helper
0.131
962101AG1-054 GEN
Solar/Wind Helper
0.326
946381AF1-302 GEN
Solar/Wind Helper
0.105
238217AF1-153 C O1
Solar/Wind Helper
0.111
966831AG1-554 GEN
Solar/Wind Harmer
0.706
971989AH1-539 GEN
Solar/Wind Harmer
7.631
247607V1-011 GEN
Solar/Wind Harmer
2.315
957201AF2-014 GEN
Solar/Wind Harmer
2.633
270435AC2-044 GEN
Solar/Wind Harmer
1.161
944161AF1-084 GEN
Solar/Wind Harmer
1.265
965041AG1-368 GEN
Solar/Wind Harmer
5.449
965051AG1-369 GEN
Solar/Wind Harmer
2.706
971771AH1-392 GEN
Solar/Wind Harmer
4.715
270302AB2-170 GEN
Solar/Wind Harmer
4.356
270317AD1-130_GEN
Solar/Wind Harmer
1.67
971769AH1-391 GEN
Solar/Wind Harmer
5.107
971567AH1-282 GEN
Solar/Wind Harmer
7.577
960681AF2-359 GEN
Solar/Wind Harmer
1.856
971347AH1-153 GEN
Solar/Wind Harmer
7.336
963791AG1-232 GEN
Solar/Wind Harmer
6.532
270578AF1-285 GEN2
Solar/Wind Harmer
0.224
270536AF1-215 GEN2
Solar/Wind Harmer
2.105
270071AF1-092 GEN
Solar/Wind Harmer
6.875
274814UNIV PK N;0U
Adder
2.28
274807UNIV PK N;3U
Adder
2.275
274805UNIV PK N;1U
Adder
2.265
274811UNIV PK N;7U
Adder
2.26
958391AF2-133 GEN
Solar/Wind Harmer
4.092
972037AH1-567 GEN1
Adder
0.082
274827FISK ;RP
Adder
3.457
960591AF2-350 GEN
Solar/Wind Harmer
4.441
274775LINCOLN ;6U
Adder
2.752
274776LINCOLN ;7U
Adder
2.752
274777LINCOLN ;8U
Adder
2.752
972227AH1-698 GEN1
Adder
1.155
274687WILL CNTY;4U
Adder
12.332
274687WILL CNTY;4U
Adder
12.332
274675JOLIET 29;7U
Adder
13.513
274675JOLIET 29;7U
Adder
13.03
274731ELWOOD EC;2P
Adder
7.227
274733ELWOOD EC;3P
Adder
7.227
274735ELWOOD EC;4P
Adder
7.227
274728ELWOOD EC;5P
Adder
7.227
270024AE2-089 GEN
Solar/Wind Harmer
2.053
970833AG2-524 GEN
Solar/Wind Harmer
3.819
970833AG2-524 GEN
Solar/Wind Harmer
1.776
274746AC1-111 G10
Adder
2.43
274744AC1-111 GEN8
Adder
2.43
241982AE2-343 S C
Solar/Wind Helper
0.117
254304AE2-114 C
Solar/Wind Helper
0.112
203846AF2-130 C
Solar/Wind Helper
0.247
241997AF1-093 GEN
Solar/Wind Helper
0.13
203804AE2-113_GEN
Solar/Wind Helper
0.862
270428AC2-015 C
Solar/Wind Harmer
3.089
24695305TIMB G C
Solar/Wind Harmer
3.089
945111AF1-176 GEN
Solar/Wind Harmer
9.863
270505AE1-170 C O1
Solar/Wind Harmer
8.284
247521TR3_G114
Solar/Wind Harmer
1.822
270246TR4_N_V150
Solar/Wind Harmer
0.461
24639705ELKHART HY
Adder
0.082
270063AE2-323 C
Solar/Wind Harmer
1.178
965011AG1-365 GEN
Solar/Wind Harmer
5.223
270462AD2-086
Solar/Wind Harmer
3.624
270223U2-072_GEN1
Solar/Wind Harmer
0.954
270578AF1-285 GEN2
Solar/Wind Harmer
0.583
270391AF1-285 GEN3
Solar/Wind Harmer
0.583
970373AG2-245 GEN
Solar/Wind Harmer
9.924
270055AF2-134 C O1
Solar/Wind Harmer
1.403
274751CRETE EC ;1U
Adder
2.233
274754CRETE EC ;4U
Adder
2.233
958381AF2-132 GEN
Solar/Wind Harmer
4.13
964861AG1-349 GEN
Solar/Wind Harmer
3.572
971917AH1-482 GEN
Solar/Wind Harmer
4.122
274723RIVER EC ;12
Adder
8.123
274812UNIV PK N;8U
Adder
2.26
276164X3-005 C
Solar/Wind Harmer
0.316
274801UNIV PARK;4U
Adder
2.593
940581AE2-045 GEN
Solar/Wind Harmer
4.53
276776AD2-060 GEN
Solar/Wind Harmer
0.188
971605AH1-302 GEN
Solar/Wind Harmer
3.873
972207SS24-0001
Solar/Wind Harmer
9.786
274773LINCOLN ;4U
Adder
2.752
274774LINCOLN ;5U
Adder
2.752
274676JOLIET 29;8U
Adder
13.513
941551AE2-152 GEN
Solar/Wind Harmer
1.995
274732ELWOOD EC;7P
Adder
7.227
274674JOLIET 9 ;6U
Adder
6.769
970245AG2-165 GEN
Solar/Wind Harmer
7.828
274871GR RIDGE ;2U
Solar/Wind Harmer
3.362
970905AG2-564 GEN
Solar/Wind Harmer
2.184
274745AC1-111 GEN9
Adder
2.43
274682WAUKEGAN ;7U
Adder
7.759
274828WAUKEGAN ;BP
Adder
4.764
961971AG1-040 GEN
Solar/Wind Helper
0.333
203835AF1-098 GEN
Solar/Wind Helper
1.311
203860AG1-193 C
Solar/Wind Helper
0.149
241966AE1-183 GEN
Solar/Wind Helper
0.13
254303AC2-168 GEN
Solar/Wind Helper
0.075
971617AH1-308 GEN
Solar/Wind Harmer
2.543
274682WAUKEGAN ;7U
Adder
7.759
962511AG1-100 GEN
Solar/Wind Helper
0.34
203830AF1-094 GEN
Solar/Wind Helper
0.322
959441AF2-235 GEN
Solar/Wind Helper
0.146
254305AE2-115 C
Solar/Wind Helper
0.112
20334926Z1-069 C
Solar/Wind Helper
0.642
943121AE2-341 GEN
Solar/Wind Harmer
3.856
943591AF1-030 GEN
Solar/Wind Harmer
2.571
991182J1586 G
External Queue
24.279396057128906
990527J1329
External Queue
1.7751743793487549
990142J1224
External Queue
12.976524353027344
991177J1571 G
External Queue
14.956707954406738
LAGNLTFEXP_LAGN->PJM
CLTF
4.798
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.107
TVALTFEXP_TVA->PJM
CLTF
2.176
CPLELTFEXP_CPLE->PJM
CLTF
0.309
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.387
CBM West 1LTFEXP_CBM-W1->PJM
CBM
91.319
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.626
MECLTFEXP_MEC->PJM
CLTF
6.275
SIGELTFEXP_SIGE->PJM
CLTF
0.163
NYPJM->LTFIMP_NY
CLTF
2.013
LGEELTFEXP_LGEE->PJM
CLTF
1.955
WECLTFEXP_WEC->PJM
CLTF
1.61
AG2-052LTFEXP_AG2-052->PJM
LTF
0.104
AH1-155LTFEXP_AH1-155->PJM
LTF
0.156

Details for AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line l/o ATSI_P1-2_OEC-345-809_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_OEC-345-809_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:117.76 %
Rating:1798.0 MVA
Rating Type:B
MVA to Mitigate:2117.36
MW Contribution:0.37
Bus #Bus NameTypeMW Contribution
23867002DVBSG1
50/50
12.718
972211AH1-690 GEN
50/50
274.788
23888502TROY G1
50/50
1.734
23888602TROY G2
50/50
1.734
241886AC2-103 GEN2
Solar/Wind Harmer
-0.001
970817AG2-515 GEN
Solar/Wind Harmer
10.276
945411AF1-206 GEN
Solar/Wind Harmer
-0.001
270499AE1-146 GEN
Solar/Wind Harmer
0.029
945641AF1-229 GEN
Solar/Wind Harmer
0.001
971549AH1-272 GEN
Solar/Wind Harmer
9.816
270297AD1-101 GEN
Solar/Wind Harmer
0.001
971989AH1-539 GEN
Solar/Wind Harmer
1.766
247607V1-011 GEN
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.507
971619AH1-309 GEN
Solar/Wind Harmer
1.709
965041AG1-368 GEN
Solar/Wind Harmer
3.755
965051AG1-369 GEN
Solar/Wind Harmer
1.865
971771AH1-392 GEN
Solar/Wind Harmer
3.604
270302AB2-170 GEN
Solar/Wind Harmer
0.002
270317AD1-130_GEN
Solar/Wind Harmer
0.005
971653AH1-327 GEN
Solar/Wind Harmer
0.505
24191202EL_AA1-006
Adder
0.112
971769AH1-391 GEN
Solar/Wind Harmer
3.923
971567AH1-282 GEN
Solar/Wind Harmer
5.235
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971347AH1-153 GEN
Solar/Wind Harmer
5.047
963791AG1-232 GEN
Solar/Wind Harmer
4.499
270578AF1-285 GEN2
Solar/Wind Harmer
0.222
270536AF1-215 GEN2
Solar/Wind Harmer
0.004
270071AF1-092 GEN
Solar/Wind Harmer
6.048
24190002OREGON_ST1
50/50
3.428
24189802OREGON_CT1
50/50
2.6
23888802TROY G4
50/50
1.734
241996AE2-282_GEN
Solar/Wind Harmer
0.005
971677AH1-339 GEN
Solar/Wind Harmer
0.654
970621AG2-405 GEN
Solar/Wind Harmer
0.864
970623AG2-406 GEN
Solar/Wind Harmer
0.785
270007AE1-245 C
Solar/Wind Harmer
0.001
246938BC-WTG3
Solar/Wind Harmer
0.145
246937BC-WTG2
Solar/Wind Harmer
0.162
961051AF2-396 GEN
Solar/Wind Harmer
7.707
961051AF2-396 GEN
Solar/Wind Harmer
5.138
957891AF2-083 GEN
Solar/Wind Harmer
0.001
247620Y3-023
Adder
0.245
270216AD2-079_GEN
Solar/Wind Harmer
0.001
970611AG2-400 GEN
Solar/Wind Harmer
3.597
970627AG2-408 GEN
Solar/Wind Harmer
1.079
270526AF1-158 GEN
Solar/Wind Harmer
0.004
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
4.224
965791AG1-447 GEN
Solar/Wind Harmer
3.098
270224U2-072_GEN2
Solar/Wind Harmer
0
270227U2-072_GEN3
Solar/Wind Harmer
0
270228U2-072_GEN4
Solar/Wind Harmer
0
270231U2-072_GEN5
Solar/Wind Harmer
0
971231AH1-075 GEN
Solar/Wind Harmer
0.372
274808UNIV PK N;4U
Adder
2.219
274803UNIV PARK;6U
Adder
2.566
274888KELLY CRK;1U
Solar/Wind Harmer
0.179
274887GEN-1.85
Solar/Wind Harmer
0.08
276843GEN-1.7
Solar/Wind Harmer
0.099
958011AF2-095 GEN
Solar/Wind Harmer
4.4
274770LINCOLN ;1U
Adder
3.695
274771LINCOLN ;2U
Adder
3.695
942221AE2-234 GEN
Solar/Wind Harmer
0.015
972259AH1-714 GEN
Adder
8.293
274674JOLIET 9 ;6U
Adder
6.676
970321AG2-212 GEN
Solar/Wind Harmer
1.307
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
203947AF1-006 C
Solar/Wind Helper
0.375
203980AG1-197 GEN
Solar/Wind Helper
0.245
203979AG1-198 GEN
Solar/Wind Helper
0.191
241967AE2-285_GEN
Solar/Wind Helper
0.334
241801AE1-079 GEN
Solar/Wind Helper
0.13
241985AE1-237 GEN
Solar/Wind Helper
0.129
962101AG1-054 GEN
Solar/Wind Helper
0.322
946381AF1-302 GEN
Solar/Wind Helper
0.103
274814UNIV PK N;0U
Adder
2.248
274807UNIV PK N;3U
Adder
2.243
274805UNIV PK N;1U
Adder
2.233
274811UNIV PK N;7U
Adder
2.229
958391AF2-133 GEN
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.081
274827FISK ;RP
Adder
3.409
971611AH1-305 GEN
Solar/Wind Harmer
1.819
960591AF2-350 GEN
Solar/Wind Harmer
3.056
274775LINCOLN ;6U
Adder
3.695
274776LINCOLN ;7U
Adder
3.695
274777LINCOLN ;8U
Adder
3.695
972227AH1-698 GEN1
Adder
1.139
274687WILL CNTY;4U
Adder
12.162
274687WILL CNTY;4U
Adder
12.162
274675JOLIET 29;7U
Adder
13.327
274675JOLIET 29;7U
Adder
12.851
274728ELWOOD EC;5P
Adder
7.127
274731ELWOOD EC;2P
Adder
7.127
274733ELWOOD EC;3P
Adder
7.127
274735ELWOOD EC;4P
Adder
7.127
270024AE2-089 GEN
Solar/Wind Harmer
0.003
970833AG2-524 GEN
Solar/Wind Harmer
3.311
970833AG2-524 GEN
Solar/Wind Harmer
2.207
241982AE2-343 S C
Solar/Wind Helper
0.116
254304AE2-114 C
Solar/Wind Helper
0.111
203846AF2-130 C
Solar/Wind Helper
0.244
241997AF1-093 GEN
Solar/Wind Helper
0.128
203804AE2-113_GEN
Solar/Wind Helper
0.852
23929302BS-PKR
50/50
2.251
241832AE2-181_GEN
Solar/Wind Harmer
0.003
958321AF2-126 GEN
Solar/Wind Harmer
1.147
23906502RICHG2&3
Adder
1.303
270575GUS2 35KV
Solar/Wind Harmer
4.647
270541AE2-072 C
Solar/Wind Harmer
0.008
970217AG2-149 GEN
Solar/Wind Harmer
4.178
270404AC1-167 GEN
Solar/Wind Harmer
0.002
270258AD1-119 GEN
Solar/Wind Harmer
0.001
270588AE1-091_GEN
Solar/Wind Harmer
3.347
247604X1-042
Adder
0.248
24441205WTRV SLR C
Solar/Wind Harmer
0
270491AE1-102 GEN2
Solar/Wind Harmer
0.52
945111AF1-176 GEN
Solar/Wind Harmer
3.081
270191TR4_S_V150
Solar/Wind Harmer
0
270247TR4_N_V136
Solar/Wind Harmer
0.024
24642205MAYFLWER
Adder
0.337
970031AG2-029 GEN
Solar/Wind Harmer
2.384
247643Z2-116 C
Solar/Wind Harmer
0
959331AF2-224 GEN
Solar/Wind Harmer
2.518
965021AG1-366 GEN
Solar/Wind Harmer
1.199
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270043AE2-236 GEN
Solar/Wind Harmer
2.178
970349AG2-230 GEN
Solar/Wind Harmer
5.047
270391AF1-285 GEN3
Solar/Wind Harmer
0.222
270377AD1-106 GEN
Solar/Wind Harmer
1.233
270535AF1-215 GEN1
Solar/Wind Harmer
0.004
274752CRETE EC ;2U
Adder
3.712
274753CRETE EC ;3U
Adder
3.712
964401AG1-302 GEN
Solar/Wind Harmer
0
274724RIVER EC ;11
Adder
7.915
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
274802UNIV PARK;5U
Adder
2.566
274826FISK ;BP
Adder
4.81
274800UNIV PARK;3U
Adder
2.557
972038AH1-567 GEN2
Adder
0.16
276806AD2-047 C O1
Solar/Wind Harmer
1.732
970941AG2-585 GEN
Solar/Wind Harmer
3.82
274772LINCOLN ;3U
Adder
3.695
972228AH1-698 GEN2
Adder
1.618
274676JOLIET 29;8U
Adder
12.851
276897AD1-100 C
Solar/Wind Harmer
0.004
939351AE1-166 GEN
Solar/Wind Harmer
0
276893AG1-478 C
Solar/Wind Harmer
0.12
274730ELWOOD EC;6P
Adder
7.127
274734ELWOOD EC;8P
Adder
7.127
274736ELWOOD EC;9P
Adder
7.127
970707AG2-453 GEN
Solar/Wind Harmer
9.881
274729ELWOOD EC;1P
Adder
7.127
970513AG2-328 GEN
Solar/Wind Harmer
1.307
970517AG2-330 GEN
Solar/Wind Harmer
7.843
971617AH1-308 GEN
Solar/Wind Harmer
2.511
962511AG1-100 GEN
Solar/Wind Helper
0.336
203830AF1-094 GEN
Solar/Wind Helper
0.318
959441AF2-235 GEN
Solar/Wind Helper
0.145
254305AE2-115 C
Solar/Wind Helper
0.111
20334926Z1-069 C
Solar/Wind Helper
0.635
24189902OREGON_CT2
50/50
2.548
23888702TROY G3
50/50
1.734
972253AH1-711 GEN
50/50
52.952
23856402BAYSG1
50/50
1.279
23920202STRYCT
50/50
1.883
241885AC2-103 GEN1
Solar/Wind Harmer
-0.001
241858AF1-205_GEN
Solar/Wind Harmer
3.794
241808AF1-120 C
Solar/Wind Harmer
0.003
241840AF1-064_GEN
Solar/Wind Harmer
0.004
972301AH1-735 GEN
Adder
6.527
23906402RICHG1
Adder
1.305
23906502RICHG2&3
Adder
1.303
270361_3
Solar/Wind Harmer
4.647
960841AF2-375 GEN
Solar/Wind Harmer
-0.002
241807AE2-176_GEN
Solar/Wind Harmer
0.004
247522W1-056 GEN
Solar/Wind Harmer
0.001
970515AG2-329 GEN
Solar/Wind Harmer
12.533
944231AF1-091 GEN
Solar/Wind Harmer
1.197
270428AC2-015 C
Solar/Wind Harmer
0.002
246936BC-WTG1
Solar/Wind Harmer
0.162
270489AE1-102 GEN1
Solar/Wind Harmer
0.52
965421AG1-410 GEN
Solar/Wind Harmer
11.884
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.028
24695305TIMB G C
Solar/Wind Harmer
0.001
945111AF1-176 GEN
Solar/Wind Harmer
6.783
270505AE1-170 C O1
Solar/Wind Harmer
3.988
247521TR3_G114
Solar/Wind Harmer
0.136
270246TR4_N_V150
Solar/Wind Harmer
0.024
24639705ELKHART HY
Adder
0.081
270063AE2-323 C
Solar/Wind Harmer
0.003
965011AG1-365 GEN
Solar/Wind Harmer
3.597
270462AD2-086
Solar/Wind Harmer
0.008
270223U2-072_GEN1
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
6.828
270055AF2-134 C O1
Solar/Wind Harmer
0.002
970905AG2-564 GEN
Solar/Wind Harmer
1.725
274751CRETE EC ;1U
Adder
3.712
274754CRETE EC ;4U
Adder
3.712
958381AF2-132 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.065
274723RIVER EC ;12
Adder
8.011
274812UNIV PK N;8U
Adder
2.229
276164X3-005 C
Solar/Wind Harmer
0
274801UNIV PARK;4U
Adder
2.557
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
3.82
276776AD2-060 GEN
Solar/Wind Harmer
0.319
274773LINCOLN ;4U
Adder
3.695
274774LINCOLN ;5U
Adder
3.695
274676JOLIET 29;8U
Adder
13.326
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
7.127
274674JOLIET 9 ;6U
Adder
6.676
970245AG2-165 GEN
Solar/Wind Harmer
1.307
274871GR RIDGE ;2U
Solar/Wind Harmer
0
961971AG1-040 GEN
Solar/Wind Helper
0.329
203835AF1-098 GEN
Solar/Wind Helper
1.297
203860AG1-193 C
Solar/Wind Helper
0.147
241966AE1-183 GEN
Solar/Wind Helper
0.128
254303AC2-168 GEN
Solar/Wind Helper
0.075
991182J1586 G
External Queue
23.868927001953125
990527J1329
External Queue
1.745489239692688
990142J1224
External Queue
12.759525299072266
991177J1571 G
External Queue
14.724894523620605
LAGNLTFEXP_LAGN->PJM
CLTF
4.735
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.079
TVALTFEXP_TVA->PJM
CLTF
2.148
CPLELTFEXP_CPLE->PJM
CLTF
0.305
CBM West 2LTFEXP_CBM-W2->PJM
CBM
37.878
CBM West 1LTFEXP_CBM-W1->PJM
CBM
89.942
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.514
MECLTFEXP_MEC->PJM
CLTF
6.19
SIGELTFEXP_SIGE->PJM
CLTF
0.161
NYPJM->LTFIMP_NY
CLTF
1.99
LGEELTFEXP_LGEE->PJM
CLTF
1.931
WECLTFEXP_WEC->PJM
CLTF
1.588
AG2-052LTFEXP_AG2-052->PJM
LTF
0.102
AH1-155LTFEXP_AH1-155->PJM
LTF
0.153

Details for AE1-091_POI-05W.NEWTONSS 138.0 kV Ckt 1 line l/o AEP_P4_#13372_05N WALDO 69.0_A_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AE1-091_POI-05W.NEWTONSS 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#13372_05N WALDO 69.0_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.39 %
Rating:183.0 MVA
Rating Type:B
MVA to Mitigate:213.0
MW Contribution:5.09
Bus #Bus NameTypeMW Contribution
971231AH1-075 GEN
Solar/Wind Harmer
5.086
971677AH1-339 GEN
Solar/Wind Harmer
9.591
966831AG1-554 GEN
Solar/Wind Harmer
7.723
971989AH1-539 GEN
Solar/Wind Harmer
83.507
247522W1-056 GEN
Solar/Wind Harmer
5.342
270588AE1-091_GEN
Solar/Wind Harmer
79.007
270377AD1-106 GEN
Solar/Wind Harmer
39.257
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.063
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.196
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
0.051
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.159
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
0.14
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.018
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.266
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.026

Details for AE1-091_POI-05W.NEWTONSS 138.0 kV Ckt 1 line l/o AEP_P2-2_#14773_05N WALDO 69.0_1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AE1-091_POI-05W.NEWTONSS 138.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#14773_05N WALDO 69.0_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:115.71 %
Rating:183.0 MVA
Rating Type:B
MVA to Mitigate:211.75
MW Contribution:5.09
Bus #Bus NameTypeMW Contribution
247522W1-056 GEN
Solar/Wind Harmer
5.342
270588AE1-091_GEN
Solar/Wind Harmer
79.007
270377AD1-106 GEN
Solar/Wind Harmer
39.257
971231AH1-075 GEN
Solar/Wind Harmer
5.086
971677AH1-339 GEN
Solar/Wind Harmer
9.591
966831AG1-554 GEN
Solar/Wind Harmer
7.723
971989AH1-539 GEN
Solar/Wind Harmer
83.507
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.063
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.196
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
0.051
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.159
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
0.14
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.018
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.266
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.026

Details for AE1-091_POI-05W.NEWTONSS 138.0 kV Ckt 1 line l/o AEP_P4_#10732_05WMTVER 138_A_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AE1-091_POI-05W.NEWTONSS 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10732_05WMTVER 138_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.3 %
Rating:183.0 MVA
Rating Type:B
MVA to Mitigate:211.01
MW Contribution:5.09
Bus #Bus NameTypeMW Contribution
971231AH1-075 GEN
Solar/Wind Harmer
5.086
971677AH1-339 GEN
Solar/Wind Harmer
9.598
966831AG1-554 GEN
Solar/Wind Harmer
7.723
971989AH1-539 GEN
Solar/Wind Harmer
83.512
247522W1-056 GEN
Solar/Wind Harmer
5.343
270588AE1-091_GEN
Solar/Wind Harmer
79.011
270377AD1-106 GEN
Solar/Wind Harmer
39.26
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.063
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.197
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
0.052
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.16
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
0.141
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.018
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.267
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.026

Details for AE1-091_POI-05W.NEWTONSS 138.0 kV Ckt 1 line l/o AEP_P4_#5710_05WMTVER 138_B_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AE1-091_POI-05W.NEWTONSS 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#5710_05WMTVER 138_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.61 %
Rating:183.0 MVA
Rating Type:B
MVA to Mitigate:187.78
MW Contribution:4.39
Bus #Bus NameTypeMW Contribution
247522W1-056 GEN
Solar/Wind Harmer
5.404
270588AE1-091_GEN
Solar/Wind Harmer
76.492
270377AD1-106 GEN
Solar/Wind Harmer
33.915
966831AG1-554 GEN
Solar/Wind Harmer
7.312
971989AH1-539 GEN
Solar/Wind Harmer
79.066
971231AH1-075 GEN
Solar/Wind Harmer
4.394
971677AH1-339 GEN
Solar/Wind Harmer
10.153
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.075
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.233
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
0.075
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.22
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
0.204
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.02
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.317
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.029

Details for AE1-091_POI-05W.NEWTONSS 138.0 kV Ckt 1 line l/o AEP_P2-2_#5710_05WMTVER 138_1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AE1-091_POI-05W.NEWTONSS 138.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#5710_05WMTVER 138_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:102.61 %
Rating:183.0 MVA
Rating Type:B
MVA to Mitigate:187.77
MW Contribution:4.39
Bus #Bus NameTypeMW Contribution
247522W1-056 GEN
Solar/Wind Harmer
5.404
966831AG1-554 GEN
Solar/Wind Harmer
7.312
971989AH1-539 GEN
Solar/Wind Harmer
79.066
270588AE1-091_GEN
Solar/Wind Harmer
76.492
270377AD1-106 GEN
Solar/Wind Harmer
33.915
971231AH1-075 GEN
Solar/Wind Harmer
4.394
971677AH1-339 GEN
Solar/Wind Harmer
10.153
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.075
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.233
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
0.075
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.22
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
0.204
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.02
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.317
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.029
CONTINGENCY 'AP_P2-3_MP-500-024_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235235 CKT 1   /*01BELMNT     500.0 - 01FLINTRUN   500.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 1   /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 2   /*01BELMNT     500.0 - 01BELMNT     138.0
END
CONTINGENCY 'AP_P2-3_MP-500-025_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235235 CKT 1   /*01BELMNT     500.0 - 01FLINTRUN   500.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 3   /*01BELMNT     500.0 - 01BELMNT     138.0
END
CONTINGENCY 'AP_P2-3_MP-500-015_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235235 CKT 1   /*01BELMNT     500.0 - 01FLINTRUN   500.0
 DISCONNECT BRANCH FROM BUS 235235 TO BUS 235100 CKT 2   /*01FLINTRUN   500.0 - 01FLINTRN    138.0
END
CONTINGENCY 'AP_P2-3_MP-500-014_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235235 CKT 1   /*01BELMNT     500.0 - 01FLINTRUN   500.0
 DISCONNECT BRANCH FROM BUS 235235 TO BUS 235100 CKT 1   /*01FLINTRUN   500.0 - 01FLINTRN    138.0
END
CONTINGENCY 'AP_P1-2_MP-500-007A_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235235 CKT 1   /*01BELMNT     500.0 - 01FLINTRUN   500.0
END
CONTINGENCY 'AP_P2-3_MP-500-012_SRT-A'
 DISCONNECT BRANCH FROM BUS 235107 TO BUS 235235 CKT 1   /*01HARRSN     500.0 - 01FLINTRUN   500.0
 DISCONNECT BRANCH FROM BUS 235107 TO BUS 235703 CKT 1   /*01HARRSN     500.0 - 01WYLIE R    500.0
END
CONTINGENCY 'AP_P1-2_MP-500-008A_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235235 TO BUS 235107 CKT 1          /*01FLINTRUN   500.0 - 01HARRSN     500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235107 TO BUS 235703 CKT 1 /*01HARRSN     500.0 - 01WYLIE R    500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235107 TO BUS 235703 CKT 1 /*01HARRSN     500.0 - 01WYLIE R    500.0
END
CONTINGENCY 'ATSI_P1-2_TE-345-602_SRT-A'
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 238889 CKT 1   /*02DAV-BE     345.0 - 02LEMOYN     345.0
END
CONTINGENCY 'ATSI_P7-1_OEC-345-002_SRT-A'
 DISCONNECT BRANCH FROM BUS 238569 TO BUS 239725 CKT 1   /*02BEAVER     345.0 - 02LAKEAVE    345.0
 DISCONNECT BRANCH FROM BUS 238569 TO BUS 239725 CKT 2   /*02BEAVER     345.0 - 02LAKEAVE    345.0
END
CONTINGENCY 'ATSI_P2-3_OEC-345-901_SRT-SL'
 DISCONNECT BRANCH FROM BUS 238569 TO BUS 239725 CKT 2          /*02BEAVER     345.0 - 02LAKEAVE    345.0
 SET POSTCONTRATING 1499 BRANCH FROM BUS 241877 TO BUS 238569 CKT 1 /*AC2-103 TAP  345.0 - 02BEAVER     345.0
 SET POSTCONTRATING 1720 BRANCH FROM BUS 239725 TO BUS 238569 CKT 1 /*02LAKEAVE    345.0 - 02BEAVER     345.0
 SET PRECONTRATING 1245 BRANCH FROM BUS 241877 TO BUS 238569 CKT 1 /*AC2-103 TAP  345.0 - 02BEAVER     345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 239725 TO BUS 238569 CKT 1 /*02LAKEAVE    345.0 - 02BEAVER     345.0
END
CONTINGENCY 'ATSI_P2-3_OEC-345-007A_SRT-SL'
 DISCONNECT BRANCH FROM BUS 238569 TO BUS 238570 CKT 2          /*02BEAVER     345.0 - 02BEAVER     138.0
 DISCONNECT BRANCH FROM BUS 238569 TO BUS 239725 CKT 2          /*02BEAVER     345.0 - 02LAKEAVE    345.0
 SET POSTCONTRATING 1499 BRANCH FROM BUS 241877 TO BUS 238569 CKT 1 /*AC2-103 TAP  345.0 - 02BEAVER     345.0
 SET PRECONTRATING 1245 BRANCH FROM BUS 241877 TO BUS 238569 CKT 1 /*AC2-103 TAP  345.0 - 02BEAVER     345.0
END
CONTINGENCY 'ATSI_P2-3_OEC-345-031_SRT-A'
 DISCONNECT BRANCH FROM BUS 239725 TO BUS 238569 CKT 2   /*02LAKEAVE    345.0 - 02BEAVER     345.0
 DISCONNECT BRANCH FROM BUS 239725 TO BUS 239726 CKT 1   /*02LAKEAVE    345.0 - 02LAKEAVE    138.0
END
CONTINGENCY 'ATSI_P2-3_OEC-345-002_SRT-A'
 DISCONNECT BRANCH FROM BUS 238569 TO BUS 238607 CKT 1   /*02BEAVER     345.0 - 02CARLIL     345.0
 DISCONNECT BRANCH FROM BUS 238569 TO BUS 239725 CKT 1   /*02BEAVER     345.0 - 02LAKEAVE    345.0
END
CONTINGENCY 'ATSI_P2-3_OEC-345-003_SRT-SL'
 DISCONNECT BRANCH FROM BUS 238569 TO BUS 239725 CKT 1          /*02BEAVER     345.0 - 02LAKEAVE    345.0
 SET POSTCONTRATING 1394 BRANCH FROM BUS 238607 TO BUS 238569 CKT 1 /*02CARLIL     345.0 - 02BEAVER     345.0
 SET POSTCONTRATING 1499 BRANCH FROM BUS 238566 TO BUS 238569 CKT 1 /*02WLORAIN    345.0 - 02BEAVER     345.0
 SET PRECONTRATING 1245 BRANCH FROM BUS 238566 TO BUS 238569 CKT 1 /*02WLORAIN    345.0 - 02BEAVER     345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 238607 TO BUS 238569 CKT 1 /*02CARLIL     345.0 - 02BEAVER     345.0
END
CONTINGENCY 'ATSI_P2-3_OEC-345-028_SRT-A'
 DISCONNECT BRANCH FROM BUS 239725 TO BUS 238569 CKT 1   /*02LAKEAVE    345.0 - 02BEAVER     345.0
 DISCONNECT BRANCH FROM BUS 239725 TO BUS 239726 CKT 1   /*02LAKEAVE    345.0 - 02LAKEAVE    138.0
END
CONTINGENCY 'ATSI_P2-3_OEC-345-1152-3_SRT-A'
 DISCONNECT BRANCH FROM BUS 239289 TO BUS 238569 CKT 1   /*02HAYES      345.0 - 02BEAVER     345.0
 DISCONNECT BRANCH FROM BUS 239289 TO BUS 239290 CKT 1   /*02HAYES      345.0 - 02HAYES      138.0
END
CONTINGENCY 'ATSI_P1-2_OEC-345-809_SRT-A'
 DISCONNECT BRANCH FROM BUS 239289 TO BUS 238569 CKT 1   /*02HAYES      345.0 - 02BEAVER     345.0
END
CONTINGENCY 'ATSI_P2-3_OEC-345-005_SRT-A'
 DISCONNECT BRANCH FROM BUS 238566 TO BUS 239171 CKT 2   /*02WLORAIN    345.0 - 02WLORG-2     13.8
 DISCONNECT BRANCH FROM BUS 238566 TO BUS 239172 CKT 3   /*02WLORAIN    345.0 - 02WLORG-3     13.8
 DISCONNECT BRANCH FROM BUS 238566 TO BUS 239173 CKT 4   /*02WLORAIN    345.0 - 02WLORG-4     13.8
 DISCONNECT BRANCH FROM BUS 238566 TO BUS 239174 CKT 5   /*02WLORAIN    345.0 - 02WLORG-5     13.8
 DISCONNECT BRANCH FROM BUS 238569 TO BUS 238566 CKT 1   /*02BEAVER     345.0 - 02WLORAIN    345.0
 DISCONNECT BRANCH FROM BUS 238569 TO BUS 241877 CKT 1   /*02BEAVER     345.0 - AC2-103 TAP  345.0
 DISCONNECT BUS 239171                                   /*02WLORG-2     13.8
 DISCONNECT BUS 239172                                   /*02WLORG-3     13.8
 DISCONNECT BUS 239173                                   /*02WLORG-4     13.8
 DISCONNECT BUS 239174                                   /*02WLORG-5     13.8
 REMOVE MACHINE 2 FROM BUS 239171                        /*02WLORG-2     13.8
 REMOVE MACHINE 3 FROM BUS 239172                        /*02WLORG-3     13.8
 REMOVE MACHINE 4 FROM BUS 239173                        /*02WLORG-4     13.8
 REMOVE MACHINE 5 FROM BUS 239174                        /*02WLORG-5     13.8
END
CONTINGENCY 'ATSI_P2-3_OEC-345-006_SRT-SL'
 DISCONNECT BRANCH FROM BUS 238569 TO BUS 238570 CKT 2          /*02BEAVER     345.0 - 02BEAVER     138.0
 DISCONNECT BRANCH FROM BUS 238569 TO BUS 241877 CKT 1          /*02BEAVER     345.0 - AC2-103 TAP  345.0
 SET POSTCONTRATING 1646 BRANCH FROM BUS 239725 TO BUS 238569 CKT 2 /*02LAKEAVE    345.0 - 02BEAVER     345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 239725 TO BUS 238569 CKT 2 /*02LAKEAVE    345.0 - 02BEAVER     345.0
END
CONTINGENCY 'ATSI_P2-3_TE-345-010A_SRT-SL'
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 241877 CKT 1          /*02DAV-BE     345.0 - AC2-103 TAP  345.0
 SET POSTCONTRATING 1683 BRANCH FROM BUS 238654 TO BUS 238563 CKT 1 /*02DAV-BE     345.0 - 02BAY SH     345.0
 SET POSTCONTRATING 1878 BRANCH FROM BUS 238654 TO BUS 238889 CKT 1 /*02DAV-BE     345.0 - 02LEMOYN     345.0
 SET POSTCONTRATING 1892 BRANCH FROM BUS 238654 TO BUS 239289 CKT 1 /*02DAV-BE     345.0 - 02HAYES      345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 238654 TO BUS 238563 CKT 1 /*02DAV-BE     345.0 - 02BAY SH     345.0
 SET PRECONTRATING 1542 BRANCH FROM BUS 238654 TO BUS 238889 CKT 1 /*02DAV-BE     345.0 - 02LEMOYN     345.0
 SET PRECONTRATING 1555 BRANCH FROM BUS 238654 TO BUS 239289 CKT 1 /*02DAV-BE     345.0 - 02HAYES      345.0
END
CONTINGENCY 'ATSI_P1-2_OEC-345-825_SRT-A'
 DISCONNECT BRANCH FROM BUS 241877 TO BUS 238569 CKT 1   /*AC2-103 TAP  345.0 - 02BEAVER     345.0
END
CONTINGENCY 'ATSI_P1-2_OEC-345-824_SRT-A'
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 241877 CKT 1   /*02DAV-BE     345.0 - AC2-103 TAP  345.0
END
CONTINGENCY 'ATSI_P1-2_TE-345-601_SRT-A'
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 238563 CKT 1   /*02DAV-BE     345.0 - 02BAY SH     345.0
END
CONTINGENCY 'AEP_P4_#7445_05MARYSV 765_B_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290621 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RF 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 962760 TO BUS 290621 CKT 1    /*AG1-125 TP   765.0 - 05MARYSVL_RF 765.0
END
CONTINGENCY 'AEP_P4_#7441_05SORENS 765_J1_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
END
CONTINGENCY 'AEP_P4_#6497_05MARYSV 345_J2_SRT-A'
 OPEN BRANCH FROM BUS 242939 TO BUS 290984 CKT 1   /*05MARYSV     345.0 - 05BOKESCRK   345.0
END
CONTINGENCY 'AEP_P4_#17564_05BOKESCRK 345_CB2_SRT-A'
 OPEN BRANCH FROM BUS 242939 TO BUS 290984 CKT 1   /*05MARYSV     345.0 - 05BOKESCRK   345.0
 OPEN BRANCH FROM BUS 243903 TO BUS 290984 CKT 1   /*05GUNN RD SW 345.0 - 05BOKESCRK   345.0
END
CONTINGENCY 'AEP_P4_#16659_05GUNN RD SW 345_M2_SRT-A'
 OPEN BRANCH FROM BUS 243903 TO BUS 290984 CKT 1   /*05GUNN RD SW 345.0 - 05BOKESCRK   345.0
END
CONTINGENCY 'AEP_P2-2_#16655_05GUNN RD SW 345_2_SRT-A'
 OPEN BRANCH FROM BUS 243903 TO BUS 290984 CKT 1   /*05GUNN RD SW 345.0 - 05BOKESCRK   345.0
END
CONTINGENCY 'AEP_P4_#13372_05N WALDO 69.0_A_SRT-A'
 OPEN BRANCH FROM BUS 242963 TO BUS 243011 CKT 1    /*05HEDDSS     138.0 - 05FULTON     138.0
 OPEN BRANCH FROM BUS 242963 TO BUS 243153 CKT 1    /*05HEDDSS     138.0 - 05WMTVER     138.0
 OPEN BRANCH FROM BUS 242963 TO BUS 245540 CKT 1    /*05HEDDSS     138.0 - 05BLOOMFLD8  138.0
 OPEN BRANCH FROM BUS 243011 TO BUS 243148 CKT 1    /*05FULTON     138.0 - 05WINDFL     138.0
 OPEN BRANCH FROM BUS 243048 TO BUS 243148 CKT 1    /*05N WALD     138.0 - 05WINDFL     138.0
 OPEN BRANCH FROM BUS 243048 TO BUS 245708 CKT 1    /*05N WALD     138.0 - 05N WALDO     69.0
 OPEN BRANCH FROM BUS 243048 TO BUS 270372 CKT 1    /*05N WALD     138.0 - AD1-106 TAP  138.0
 OPEN BRANCH FROM BUS 245391 TO BUS 245710 CKT 1    /*05RIDGEDALE8  69.0 - 05RIDGEDALEZ  69.0
 OPEN BRANCH FROM BUS 245699 TO BUS 245701 CKT 1    /*05HARPSTER P  69.0 - 05HARPSTER    69.0
 OPEN BRANCH FROM BUS 245699 TO BUS 290079 CKT 1    /*05HARPSTER P  69.0 - 05GOODNOW SS  69.0
 OPEN BRANCH FROM BUS 245708 TO BUS 245716 CKT 1    /*05N WALDO     69.0 - 05WALDO       69.0
 OPEN BRANCH FROM BUS 245710 TO BUS 245711 CKT 1    /*05RIDGEDALEZ  69.0 - 05S MORRAL    69.0
 OPEN BRANCH FROM BUS 245710 TO BUS 290079 CKT Z1   /*05RIDGEDALEZ  69.0 - 05GOODNOW SS  69.0
 OPEN BRANCH FROM BUS 245711 TO BUS 247032 CKT 1    /*05S MORRAL    69.0 - 05UNCAPHSS    69.0
 OPEN BRANCH FROM BUS 245716 TO BUS 247032 CKT 1    /*05WALDO       69.0 - 05UNCAPHSS    69.0
 REMOVE LOAD C1 FROM BUS 245699                     /*05HARPSTER P  69.0
 REMOVE LOAD D1 FROM BUS 243011                     /*05FULTON     138.0
 REMOVE LOAD D1 FROM BUS 245711                     /*05S MORRAL    69.0
 REMOVE LOAD D1 FROM BUS 245716                     /*05WALDO       69.0
 REMOVE LOAD D1 FROM BUS 247032                     /*05UNCAPHSS    69.0
 REMOVE LOAD T1 FROM BUS 243148                     /*05WINDFL     138.0
 REMOVE LOAD T1 FROM BUS 245391                     /*05RIDGEDALE8  69.0
 REMOVE LOAD T1 FROM BUS 245540                     /*05BLOOMFLD8  138.0
 REMOVE SWSHUNT FROM BUS 245716                     /*05WALDO       69.0
END
CONTINGENCY 'AEP_P2-2_#14773_05N WALDO 69.0_1_SRT-A'
 OPEN BRANCH FROM BUS 242963 TO BUS 243011 CKT 1   /*05HEDDSS     138.0 - 05FULTON     138.0
 OPEN BRANCH FROM BUS 242963 TO BUS 243153 CKT 1   /*05HEDDSS     138.0 - 05WMTVER     138.0
 OPEN BRANCH FROM BUS 242963 TO BUS 245540 CKT 1   /*05HEDDSS     138.0 - 05BLOOMFLD8  138.0
 OPEN BRANCH FROM BUS 243011 TO BUS 243148 CKT 1   /*05FULTON     138.0 - 05WINDFL     138.0
 OPEN BRANCH FROM BUS 243048 TO BUS 243148 CKT 1   /*05N WALD     138.0 - 05WINDFL     138.0
 OPEN BRANCH FROM BUS 243048 TO BUS 245708 CKT 1   /*05N WALD     138.0 - 05N WALDO     69.0
 OPEN BRANCH FROM BUS 243048 TO BUS 270372 CKT 1   /*05N WALD     138.0 - AD1-106 TAP  138.0
 OPEN BRANCH FROM BUS 245708 TO BUS 245716 CKT 1   /*05N WALDO     69.0 - 05WALDO       69.0
 REMOVE LOAD D2 FROM BUS 245708                    /*05N WALDO     69.0
END
CONTINGENCY 'AEP_P4_#10732_05WMTVER 138_A_SRT-A'
 OPEN BRANCH FROM BUS 242950 TO BUS 243153 CKT 1   /*05ACADEM     138.0 - 05WMTVER     138.0
 OPEN BRANCH FROM BUS 242963 TO BUS 243011 CKT 1   /*05HEDDSS     138.0 - 05FULTON     138.0
 OPEN BRANCH FROM BUS 242963 TO BUS 243153 CKT 1   /*05HEDDSS     138.0 - 05WMTVER     138.0
 OPEN BRANCH FROM BUS 242963 TO BUS 245540 CKT 1   /*05HEDDSS     138.0 - 05BLOOMFLD8  138.0
 OPEN BRANCH FROM BUS 243011 TO BUS 243148 CKT 1   /*05FULTON     138.0 - 05WINDFL     138.0
 OPEN BRANCH FROM BUS 243048 TO BUS 243148 CKT 1   /*05N WALD     138.0 - 05WINDFL     138.0
 OPEN BRANCH FROM BUS 243048 TO BUS 245708 CKT 1   /*05N WALD     138.0 - 05N WALDO     69.0
 OPEN BRANCH FROM BUS 243048 TO BUS 270372 CKT 1   /*05N WALD     138.0 - AD1-106 TAP  138.0
 OPEN BRANCH FROM BUS 243098 TO BUS 243153 CKT 1   /*05SHARPR     138.0 - 05WMTVER     138.0
 OPEN BRANCH FROM BUS 243153 TO BUS 245562 CKT 1   /*05WMTVER     138.0 - 05W MT VER    69.0
 REMOVE SWSHUNT FROM BUS 243153                    /*05WMTVER     138.0
END
CONTINGENCY 'AEP_P4_#5710_05WMTVER 138_B_SRT-A'
 OPEN BRANCH FROM BUS 242950 TO BUS 243153 CKT 1   /*05ACADEM     138.0 - 05WMTVER     138.0
 OPEN BRANCH FROM BUS 242963 TO BUS 243153 CKT 1   /*05HEDDSS     138.0 - 05WMTVER     138.0
 OPEN BRANCH FROM BUS 243098 TO BUS 243153 CKT 1   /*05SHARPR     138.0 - 05WMTVER     138.0
 OPEN BRANCH FROM BUS 243153 TO BUS 245562 CKT 1   /*05WMTVER     138.0 - 05W MT VER    69.0
 REMOVE SWSHUNT FROM BUS 243153                    /*05WMTVER     138.0
END
CONTINGENCY 'AEP_P2-2_#5710_05WMTVER 138_1_SRT-A'
 OPEN BRANCH FROM BUS 242950 TO BUS 243153 CKT 1   /*05ACADEM     138.0 - 05WMTVER     138.0
 OPEN BRANCH FROM BUS 242963 TO BUS 243153 CKT 1   /*05HEDDSS     138.0 - 05WMTVER     138.0
 OPEN BRANCH FROM BUS 243098 TO BUS 243153 CKT 1   /*05SHARPR     138.0 - 05WMTVER     138.0
 OPEN BRANCH FROM BUS 243153 TO BUS 245562 CKT 1   /*05WMTVER     138.0 - 05W MT VER    69.0
 REMOVE SWSHUNT FROM BUS 243153                    /*05WMTVER     138.0
END
CONTINGENCY 'ATSI_P2-3_OEC-345-009_SRT-SL'
 DISCONNECT BRANCH FROM BUS 238569 TO BUS 238570 CKT 2          /*02BEAVER     345.0 - 02BEAVER     138.0
 DISCONNECT BRANCH FROM BUS 238569 TO BUS 239289 CKT 1          /*02BEAVER     345.0 - 02HAYES      345.0
 SET POSTCONTRATING 1499 BRANCH FROM BUS 241877 TO BUS 238569 CKT 1 /*AC2-103 TAP  345.0 - 02BEAVER     345.0
 SET POSTCONTRATING 1720 BRANCH FROM BUS 238607 TO BUS 238569 CKT 1 /*02CARLIL     345.0 - 02BEAVER     345.0
 SET POSTCONTRATING 1720 BRANCH FROM BUS 239725 TO BUS 238569 CKT 2 /*02LAKEAVE    345.0 - 02BEAVER     345.0
 SET PRECONTRATING 1245 BRANCH FROM BUS 241877 TO BUS 238569 CKT 1 /*AC2-103 TAP  345.0 - 02BEAVER     345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 238607 TO BUS 238569 CKT 1 /*02CARLIL     345.0 - 02BEAVER     345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 239725 TO BUS 238569 CKT 2 /*02LAKEAVE    345.0 - 02BEAVER     345.0
END
235117 to 235111 ckt 1
238563 to 238654 ckt 1
238569 to 238607 ckt 1
238569 to 239725 ckt 1
238569 to 239725 ckt 2
238654 to 241877 ckt 1
239289 to 238569 ckt 1
238889 to 238654 ckt 1
290984 to 242939 ckt 1
242935 to 242945 ckt 1
243903 to 290984 ckt 1
242925 to 235117 ckt 1
243155 to 242989 ckt 1
241877 to 238569 ckt 1
270584 to 243155 ckt 1

Winter Peak Analysis

The New Service Request AH1-075 was evaluated as a 8.0 MW (24.7 MW Capacity) injection in the AEP area.

AH1-075 was evaluated as part of a plant. The plant consists of AH1-075. The total Energy output of the plant was evaluated at its maximum seasonal capability of 68.0 MW (8.0 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

(No impacts were found for this analysis)

Light Load Analysis

The New Service Request AH1-075 was evaluated as a 8.0 MW injection

AH1-075 was evaluated as part of a plant. The plant consists of AH1-075. The total Energy output of the plant was evaluated at its maximum seasonal capability of 68.0 MW (8.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AEP
05W.NEWTONSS-05E LIMA 138.0 kV Ckt 1 line
AEP_P4_#13372_05N WALDO 69.0_A_SRT-A
BreakerAC107.11 %183.0B196.013.25
GD2AEP
05W.NEWTONSS-05E LIMA 138.0 kV Ckt 1 line
AEP_P4_#10732_05WMTVER 138_A_SRT-A
BreakerAC106.98 %183.0B195.773.25
GD2AEP
05W.NEWTONSS-05E LIMA 138.0 kV Ckt 1 line
AEP_P2-2_#14773_05N WALDO 69.0_1_SRT-A
BusAC106.92 %183.0B195.673.25
GD2AEP
05W.NEWTONSS-05E LIMA 138.0 kV Ckt 1 line
AEP_P1-3_#14772_05N WALD 138_1_SRT-A-1
SingleAC106.92 %183.0B195.663.25
GD2AEP
05W.NEWTONSS-05E LIMA 138.0 kV Ckt 1 line
AEP_P1-2_#14768_SRT-A-1
SingleAC106.9 %183.0B195.623.25
GD2AEP
05W.NEWTONSS-05E LIMA 138.0 kV Ckt 1 line
AEP_P4_#5710_05WMTVER 138_B_SRT-A
BreakerAC100.39 %183.0B183.712.81
GD2AEP
05W.NEWTONSS-05E LIMA 138.0 kV Ckt 1 line
AEP_P2-2_#5710_05WMTVER 138_1_SRT-A
BusAC100.39 %183.0B183.712.81
GD2AEP
AE1-091_POI-05W.NEWTONSS 138.0 kV Ckt 1 line
AEP_P4_#13372_05N WALDO 69.0_A_SRT-A
BreakerAC107.03 %183.0B195.863.25
GD2AEP
AE1-091_POI-05W.NEWTONSS 138.0 kV Ckt 1 line
AEP_P4_#10732_05WMTVER 138_A_SRT-A
BreakerAC106.89 %183.0B195.613.25
GD2AEP
AE1-091_POI-05W.NEWTONSS 138.0 kV Ckt 1 line
AEP_P1-3_#14772_05N WALD 138_1_SRT-A-1
SingleAC106.83 %183.0B195.53.25
GD2AEP
AE1-091_POI-05W.NEWTONSS 138.0 kV Ckt 1 line
AEP_P2-2_#14773_05N WALDO 69.0_1_SRT-A
BusAC106.83 %183.0B195.53.25
GD2AEP
AE1-091_POI-05W.NEWTONSS 138.0 kV Ckt 1 line
AEP_P1-2_#14768_SRT-A-1
SingleAC106.8 %183.0B195.453.25
GD2AEP
AE1-091_POI-05W.NEWTONSS 138.0 kV Ckt 1 line
AEP_P4_#5710_05WMTVER 138_B_SRT-A
BreakerAC100.31 %183.0B183.572.81
GD2AEP
AE1-091_POI-05W.NEWTONSS 138.0 kV Ckt 1 line
AEP_P2-2_#5710_05WMTVER 138_1_SRT-A
BusAC100.31 %183.0B183.572.81

Details for 05W.NEWTONSS-05E LIMA 138.0 kV Ckt 1 line l/o AEP_P4_#13372_05N WALDO 69.0_A_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05W.NEWTONSS-05E LIMA 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#13372_05N WALDO 69.0_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.11 %
Rating:183.0 MVA
Rating Type:B
MVA to Mitigate:196.01
MW Contribution:3.25
Bus #Bus NameTypeMW Contribution
270377AD1-106 GEN
Solar/Wind Harmer
25.101
270588AE1-091_GEN
Solar/Wind Harmer
50.518
247522W1-056 GEN
Solar/Wind Harmer
7.91
966831AG1-554 GEN
Solar/Wind Harmer
0
971231AH1-075 GEN
Solar/Wind Harmer
3.252
971677AH1-339 GEN
Solar/Wind Harmer
6.127
971989AH1-539 GEN
Solar/Wind Harmer
53.394
971989AH1-539 GEN
Solar/Wind Harmer
26.183
G-007ALTFEXP_G-007A->PJM
CMTX
0.016
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.034
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.023
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.302
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.071
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.22
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.087
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
0.046

Details for 05W.NEWTONSS-05E LIMA 138.0 kV Ckt 1 line l/o AEP_P4_#10732_05WMTVER 138_A_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05W.NEWTONSS-05E LIMA 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10732_05WMTVER 138_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.98 %
Rating:183.0 MVA
Rating Type:B
MVA to Mitigate:195.77
MW Contribution:3.25
Bus #Bus NameTypeMW Contribution
270377AD1-106 GEN
Solar/Wind Harmer
25.102
270588AE1-091_GEN
Solar/Wind Harmer
50.52
247522W1-056 GEN
Solar/Wind Harmer
7.912
966831AG1-554 GEN
Solar/Wind Harmer
0
971231AH1-075 GEN
Solar/Wind Harmer
3.252
971677AH1-339 GEN
Solar/Wind Harmer
6.131
971989AH1-539 GEN
Solar/Wind Harmer
53.397
971989AH1-539 GEN
Solar/Wind Harmer
26.185
G-007ALTFEXP_G-007A->PJM
CMTX
0.016
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.034
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.023
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.303
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.071
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.221
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.088
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
0.045

Details for 05W.NEWTONSS-05E LIMA 138.0 kV Ckt 1 line l/o AEP_P2-2_#14773_05N WALDO 69.0_1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05W.NEWTONSS-05E LIMA 138.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#14773_05N WALDO 69.0_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:106.92 %
Rating:183.0 MVA
Rating Type:B
MVA to Mitigate:195.67
MW Contribution:3.25
Bus #Bus NameTypeMW Contribution
270377AD1-106 GEN
Solar/Wind Harmer
25.101
270588AE1-091_GEN
Solar/Wind Harmer
50.518
247522W1-056 GEN
Solar/Wind Harmer
7.91
966831AG1-554 GEN
Solar/Wind Harmer
0
971231AH1-075 GEN
Solar/Wind Harmer
3.252
971677AH1-339 GEN
Solar/Wind Harmer
6.127
971989AH1-539 GEN
Solar/Wind Harmer
53.394
971989AH1-539 GEN
Solar/Wind Harmer
26.183
G-007ALTFEXP_G-007A->PJM
CMTX
0.016
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.034
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.023
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.302
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.071
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.22
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.087
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
0.046

Details for 05W.NEWTONSS-05E LIMA 138.0 kV Ckt 1 line l/o AEP_P1-3_#14772_05N WALD 138_1_SRT-A-1


Base Case Flowgate

Area:AEP
Facility Description:
05W.NEWTONSS-05E LIMA 138.0 kV Ckt 1 line
Contingency Name:
AEP_P1-3_#14772_05N WALD 138_1_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.92 %
Rating:183.0 MVA
Rating Type:B
MVA to Mitigate:195.66
MW Contribution:3.25
Bus #Bus NameTypeMW Contribution
270377AD1-106 GEN
Solar/Wind Harmer
25.101
270588AE1-091_GEN
Solar/Wind Harmer
50.518
247522W1-056 GEN
Solar/Wind Harmer
7.91
966831AG1-554 GEN
Solar/Wind Harmer
0
971231AH1-075 GEN
Solar/Wind Harmer
3.252
971677AH1-339 GEN
Solar/Wind Harmer
6.127
971989AH1-539 GEN
Solar/Wind Harmer
53.394
971989AH1-539 GEN
Solar/Wind Harmer
26.183
G-007ALTFEXP_G-007A->PJM
CMTX
0.016
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.034
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.023
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.302
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.071
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.22
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.087
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
0.046

Details for 05W.NEWTONSS-05E LIMA 138.0 kV Ckt 1 line l/o AEP_P1-2_#14768_SRT-A-1


Base Case Flowgate

Area:AEP
Facility Description:
05W.NEWTONSS-05E LIMA 138.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#14768_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.9 %
Rating:183.0 MVA
Rating Type:B
MVA to Mitigate:195.62
MW Contribution:3.25
Bus #Bus NameTypeMW Contribution
270377AD1-106 GEN
Solar/Wind Harmer
25.101
270588AE1-091_GEN
Solar/Wind Harmer
50.518
247522W1-056 GEN
Solar/Wind Harmer
7.91
966831AG1-554 GEN
Solar/Wind Harmer
0
971231AH1-075 GEN
Solar/Wind Harmer
3.252
971677AH1-339 GEN
Solar/Wind Harmer
6.127
971989AH1-539 GEN
Solar/Wind Harmer
53.394
971989AH1-539 GEN
Solar/Wind Harmer
26.183
G-007ALTFEXP_G-007A->PJM
CMTX
0.016
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.034
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.023
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.302
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.071
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.22
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.087
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
0.046

Details for 05W.NEWTONSS-05E LIMA 138.0 kV Ckt 1 line l/o AEP_P4_#5710_05WMTVER 138_B_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05W.NEWTONSS-05E LIMA 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#5710_05WMTVER 138_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.39 %
Rating:183.0 MVA
Rating Type:B
MVA to Mitigate:183.71
MW Contribution:2.81
Bus #Bus NameTypeMW Contribution
270377AD1-106 GEN
Solar/Wind Harmer
21.684
270588AE1-091_GEN
Solar/Wind Harmer
48.909
247522W1-056 GEN
Solar/Wind Harmer
8.002
966831AG1-554 GEN
Solar/Wind Harmer
0
971231AH1-075 GEN
Solar/Wind Harmer
2.809
971677AH1-339 GEN
Solar/Wind Harmer
6.486
971989AH1-539 GEN
Solar/Wind Harmer
50.554
971989AH1-539 GEN
Solar/Wind Harmer
24.79
G-007ALTFEXP_G-007A->PJM
CMTX
0.04
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.037
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.025
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.351
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.083
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.257
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.149
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
0.11

Details for 05W.NEWTONSS-05E LIMA 138.0 kV Ckt 1 line l/o AEP_P2-2_#5710_05WMTVER 138_1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05W.NEWTONSS-05E LIMA 138.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#5710_05WMTVER 138_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:100.39 %
Rating:183.0 MVA
Rating Type:B
MVA to Mitigate:183.71
MW Contribution:2.81
Bus #Bus NameTypeMW Contribution
270377AD1-106 GEN
Solar/Wind Harmer
21.684
270588AE1-091_GEN
Solar/Wind Harmer
48.909
247522W1-056 GEN
Solar/Wind Harmer
8.002
966831AG1-554 GEN
Solar/Wind Harmer
0
971231AH1-075 GEN
Solar/Wind Harmer
2.809
971677AH1-339 GEN
Solar/Wind Harmer
6.486
971989AH1-539 GEN
Solar/Wind Harmer
50.554
971989AH1-539 GEN
Solar/Wind Harmer
24.79
G-007ALTFEXP_G-007A->PJM
CMTX
0.04
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.037
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.025
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.351
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.083
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.257
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.149
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
0.11

Details for AE1-091_POI-05W.NEWTONSS 138.0 kV Ckt 1 line l/o AEP_P4_#13372_05N WALDO 69.0_A_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AE1-091_POI-05W.NEWTONSS 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#13372_05N WALDO 69.0_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.03 %
Rating:183.0 MVA
Rating Type:B
MVA to Mitigate:195.86
MW Contribution:3.25
Bus #Bus NameTypeMW Contribution
270377AD1-106 GEN
Solar/Wind Harmer
25.101
270588AE1-091_GEN
Solar/Wind Harmer
50.518
247522W1-056 GEN
Solar/Wind Harmer
7.91
966831AG1-554 GEN
Solar/Wind Harmer
0
971231AH1-075 GEN
Solar/Wind Harmer
3.252
971677AH1-339 GEN
Solar/Wind Harmer
6.127
971989AH1-539 GEN
Solar/Wind Harmer
53.394
971989AH1-539 GEN
Solar/Wind Harmer
26.183
G-007ALTFEXP_G-007A->PJM
CMTX
0.016
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.034
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.023
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.302
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.071
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.22
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.087
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
0.046

Details for AE1-091_POI-05W.NEWTONSS 138.0 kV Ckt 1 line l/o AEP_P4_#10732_05WMTVER 138_A_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AE1-091_POI-05W.NEWTONSS 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10732_05WMTVER 138_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.89 %
Rating:183.0 MVA
Rating Type:B
MVA to Mitigate:195.61
MW Contribution:3.25
Bus #Bus NameTypeMW Contribution
270377AD1-106 GEN
Solar/Wind Harmer
25.102
270588AE1-091_GEN
Solar/Wind Harmer
50.52
247522W1-056 GEN
Solar/Wind Harmer
7.912
966831AG1-554 GEN
Solar/Wind Harmer
0
971231AH1-075 GEN
Solar/Wind Harmer
3.252
971677AH1-339 GEN
Solar/Wind Harmer
6.131
971989AH1-539 GEN
Solar/Wind Harmer
53.397
971989AH1-539 GEN
Solar/Wind Harmer
26.185
G-007ALTFEXP_G-007A->PJM
CMTX
0.016
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.034
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.023
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.303
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.071
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.221
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.088
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
0.045

Details for AE1-091_POI-05W.NEWTONSS 138.0 kV Ckt 1 line l/o AEP_P1-3_#14772_05N WALD 138_1_SRT-A-1


Base Case Flowgate

Area:AEP
Facility Description:
AE1-091_POI-05W.NEWTONSS 138.0 kV Ckt 1 line
Contingency Name:
AEP_P1-3_#14772_05N WALD 138_1_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.83 %
Rating:183.0 MVA
Rating Type:B
MVA to Mitigate:195.5
MW Contribution:3.25
Bus #Bus NameTypeMW Contribution
270377AD1-106 GEN
Solar/Wind Harmer
25.101
270588AE1-091_GEN
Solar/Wind Harmer
50.518
247522W1-056 GEN
Solar/Wind Harmer
7.91
966831AG1-554 GEN
Solar/Wind Harmer
0
971231AH1-075 GEN
Solar/Wind Harmer
3.252
971677AH1-339 GEN
Solar/Wind Harmer
6.127
971989AH1-539 GEN
Solar/Wind Harmer
53.394
971989AH1-539 GEN
Solar/Wind Harmer
26.183
G-007ALTFEXP_G-007A->PJM
CMTX
0.016
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.034
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.023
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.302
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.071
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.22
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.087
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
0.046

Details for AE1-091_POI-05W.NEWTONSS 138.0 kV Ckt 1 line l/o AEP_P2-2_#14773_05N WALDO 69.0_1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AE1-091_POI-05W.NEWTONSS 138.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#14773_05N WALDO 69.0_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:106.83 %
Rating:183.0 MVA
Rating Type:B
MVA to Mitigate:195.5
MW Contribution:3.25
Bus #Bus NameTypeMW Contribution
270377AD1-106 GEN
Solar/Wind Harmer
25.101
270588AE1-091_GEN
Solar/Wind Harmer
50.518
247522W1-056 GEN
Solar/Wind Harmer
7.91
966831AG1-554 GEN
Solar/Wind Harmer
0
971231AH1-075 GEN
Solar/Wind Harmer
3.252
971677AH1-339 GEN
Solar/Wind Harmer
6.127
971989AH1-539 GEN
Solar/Wind Harmer
53.394
971989AH1-539 GEN
Solar/Wind Harmer
26.183
G-007ALTFEXP_G-007A->PJM
CMTX
0.016
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.034
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.023
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.302
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.071
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.22
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.087
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
0.046

Details for AE1-091_POI-05W.NEWTONSS 138.0 kV Ckt 1 line l/o AEP_P1-2_#14768_SRT-A-1


Base Case Flowgate

Area:AEP
Facility Description:
AE1-091_POI-05W.NEWTONSS 138.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#14768_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.8 %
Rating:183.0 MVA
Rating Type:B
MVA to Mitigate:195.45
MW Contribution:3.25
Bus #Bus NameTypeMW Contribution
270377AD1-106 GEN
Solar/Wind Harmer
25.101
270588AE1-091_GEN
Solar/Wind Harmer
50.518
247522W1-056 GEN
Solar/Wind Harmer
7.91
966831AG1-554 GEN
Solar/Wind Harmer
0
971231AH1-075 GEN
Solar/Wind Harmer
3.252
971677AH1-339 GEN
Solar/Wind Harmer
6.127
971989AH1-539 GEN
Solar/Wind Harmer
53.394
971989AH1-539 GEN
Solar/Wind Harmer
26.183
G-007ALTFEXP_G-007A->PJM
CMTX
0.016
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.034
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.023
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.302
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.071
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.22
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.087
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
0.046

Details for AE1-091_POI-05W.NEWTONSS 138.0 kV Ckt 1 line l/o AEP_P4_#5710_05WMTVER 138_B_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AE1-091_POI-05W.NEWTONSS 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#5710_05WMTVER 138_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.31 %
Rating:183.0 MVA
Rating Type:B
MVA to Mitigate:183.57
MW Contribution:2.81
Bus #Bus NameTypeMW Contribution
270377AD1-106 GEN
Solar/Wind Harmer
21.684
270588AE1-091_GEN
Solar/Wind Harmer
48.909
247522W1-056 GEN
Solar/Wind Harmer
8.002
966831AG1-554 GEN
Solar/Wind Harmer
0
971231AH1-075 GEN
Solar/Wind Harmer
2.809
971677AH1-339 GEN
Solar/Wind Harmer
6.486
971989AH1-539 GEN
Solar/Wind Harmer
50.554
971989AH1-539 GEN
Solar/Wind Harmer
24.79
G-007ALTFEXP_G-007A->PJM
CMTX
0.04
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.037
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.025
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.351
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.083
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.257
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.149
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
0.11

Details for AE1-091_POI-05W.NEWTONSS 138.0 kV Ckt 1 line l/o AEP_P2-2_#5710_05WMTVER 138_1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AE1-091_POI-05W.NEWTONSS 138.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#5710_05WMTVER 138_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:100.31 %
Rating:183.0 MVA
Rating Type:B
MVA to Mitigate:183.57
MW Contribution:2.81
Bus #Bus NameTypeMW Contribution
270377AD1-106 GEN
Solar/Wind Harmer
21.684
270588AE1-091_GEN
Solar/Wind Harmer
48.909
247522W1-056 GEN
Solar/Wind Harmer
8.002
966831AG1-554 GEN
Solar/Wind Harmer
0
971231AH1-075 GEN
Solar/Wind Harmer
2.809
971677AH1-339 GEN
Solar/Wind Harmer
6.486
971989AH1-539 GEN
Solar/Wind Harmer
50.554
971989AH1-539 GEN
Solar/Wind Harmer
24.79
G-007ALTFEXP_G-007A->PJM
CMTX
0.04
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.037
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.025
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.351
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.083
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.257
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.149
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
0.11
CONTINGENCY 'AEP_P4_#13372_05N WALDO 69.0_A_SRT-A'
 OPEN BRANCH FROM BUS 242963 TO BUS 243011 CKT 1    /*05HEDDSS     138.0 - 05FULTON     138.0
 OPEN BRANCH FROM BUS 242963 TO BUS 243153 CKT 1    /*05HEDDSS     138.0 - 05WMTVER     138.0
 OPEN BRANCH FROM BUS 242963 TO BUS 245540 CKT 1    /*05HEDDSS     138.0 - 05BLOOMFLD8  138.0
 OPEN BRANCH FROM BUS 243011 TO BUS 243148 CKT 1    /*05FULTON     138.0 - 05WINDFL     138.0
 OPEN BRANCH FROM BUS 243048 TO BUS 243148 CKT 1    /*05N WALD     138.0 - 05WINDFL     138.0
 OPEN BRANCH FROM BUS 243048 TO BUS 245708 CKT 1    /*05N WALD     138.0 - 05N WALDO     69.0
 OPEN BRANCH FROM BUS 243048 TO BUS 270372 CKT 1    /*05N WALD     138.0 - AD1-106 TAP  138.0
 OPEN BRANCH FROM BUS 245391 TO BUS 245710 CKT 1    /*05RIDGEDALE8  69.0 - 05RIDGEDALEZ  69.0
 OPEN BRANCH FROM BUS 245699 TO BUS 245701 CKT 1    /*05HARPSTER P  69.0 - 05HARPSTER    69.0
 OPEN BRANCH FROM BUS 245699 TO BUS 290079 CKT 1    /*05HARPSTER P  69.0 - 05GOODNOW SS  69.0
 OPEN BRANCH FROM BUS 245708 TO BUS 245716 CKT 1    /*05N WALDO     69.0 - 05WALDO       69.0
 OPEN BRANCH FROM BUS 245710 TO BUS 245711 CKT 1    /*05RIDGEDALEZ  69.0 - 05S MORRAL    69.0
 OPEN BRANCH FROM BUS 245710 TO BUS 290079 CKT Z1   /*05RIDGEDALEZ  69.0 - 05GOODNOW SS  69.0
 OPEN BRANCH FROM BUS 245711 TO BUS 247032 CKT 1    /*05S MORRAL    69.0 - 05UNCAPHSS    69.0
 OPEN BRANCH FROM BUS 245716 TO BUS 247032 CKT 1    /*05WALDO       69.0 - 05UNCAPHSS    69.0
 REMOVE LOAD C1 FROM BUS 245699                     /*05HARPSTER P  69.0
 REMOVE LOAD D1 FROM BUS 243011                     /*05FULTON     138.0
 REMOVE LOAD D1 FROM BUS 245711                     /*05S MORRAL    69.0
 REMOVE LOAD D1 FROM BUS 245716                     /*05WALDO       69.0
 REMOVE LOAD D1 FROM BUS 247032                     /*05UNCAPHSS    69.0
 REMOVE LOAD T1 FROM BUS 243148                     /*05WINDFL     138.0
 REMOVE LOAD T1 FROM BUS 245391                     /*05RIDGEDALE8  69.0
 REMOVE LOAD T1 FROM BUS 245540                     /*05BLOOMFLD8  138.0
 REMOVE SWSHUNT FROM BUS 245716                     /*05WALDO       69.0
END
CONTINGENCY 'AEP_P4_#10732_05WMTVER 138_A_SRT-A'
 OPEN BRANCH FROM BUS 242950 TO BUS 243153 CKT 1   /*05ACADEM     138.0 - 05WMTVER     138.0
 OPEN BRANCH FROM BUS 242963 TO BUS 243011 CKT 1   /*05HEDDSS     138.0 - 05FULTON     138.0
 OPEN BRANCH FROM BUS 242963 TO BUS 243153 CKT 1   /*05HEDDSS     138.0 - 05WMTVER     138.0
 OPEN BRANCH FROM BUS 242963 TO BUS 245540 CKT 1   /*05HEDDSS     138.0 - 05BLOOMFLD8  138.0
 OPEN BRANCH FROM BUS 243011 TO BUS 243148 CKT 1   /*05FULTON     138.0 - 05WINDFL     138.0
 OPEN BRANCH FROM BUS 243048 TO BUS 243148 CKT 1   /*05N WALD     138.0 - 05WINDFL     138.0
 OPEN BRANCH FROM BUS 243048 TO BUS 245708 CKT 1   /*05N WALD     138.0 - 05N WALDO     69.0
 OPEN BRANCH FROM BUS 243048 TO BUS 270372 CKT 1   /*05N WALD     138.0 - AD1-106 TAP  138.0
 OPEN BRANCH FROM BUS 243098 TO BUS 243153 CKT 1   /*05SHARPR     138.0 - 05WMTVER     138.0
 OPEN BRANCH FROM BUS 243153 TO BUS 245562 CKT 1   /*05WMTVER     138.0 - 05W MT VER    69.0
 REMOVE SWSHUNT FROM BUS 243153                    /*05WMTVER     138.0
END
CONTINGENCY 'AEP_P2-2_#14773_05N WALDO 69.0_1_SRT-A'
 OPEN BRANCH FROM BUS 242963 TO BUS 243011 CKT 1   /*05HEDDSS     138.0 - 05FULTON     138.0
 OPEN BRANCH FROM BUS 242963 TO BUS 243153 CKT 1   /*05HEDDSS     138.0 - 05WMTVER     138.0
 OPEN BRANCH FROM BUS 242963 TO BUS 245540 CKT 1   /*05HEDDSS     138.0 - 05BLOOMFLD8  138.0
 OPEN BRANCH FROM BUS 243011 TO BUS 243148 CKT 1   /*05FULTON     138.0 - 05WINDFL     138.0
 OPEN BRANCH FROM BUS 243048 TO BUS 243148 CKT 1   /*05N WALD     138.0 - 05WINDFL     138.0
 OPEN BRANCH FROM BUS 243048 TO BUS 245708 CKT 1   /*05N WALD     138.0 - 05N WALDO     69.0
 OPEN BRANCH FROM BUS 243048 TO BUS 270372 CKT 1   /*05N WALD     138.0 - AD1-106 TAP  138.0
 OPEN BRANCH FROM BUS 245708 TO BUS 245716 CKT 1   /*05N WALDO     69.0 - 05WALDO       69.0
 REMOVE LOAD D2 FROM BUS 245708                    /*05N WALDO     69.0
END
CONTINGENCY 'AEP_P1-3_#14772_05N WALD 138_1_SRT-A-1'
 OPEN BRANCH FROM BUS 242963 TO BUS 243011 CKT 1   /*05HEDDSS     138.0 - 05FULTON     138.0
 OPEN BRANCH FROM BUS 242963 TO BUS 243153 CKT 1   /*05HEDDSS     138.0 - 05WMTVER     138.0
 OPEN BRANCH FROM BUS 242963 TO BUS 245540 CKT 1   /*05HEDDSS     138.0 - 05BLOOMFLD8  138.0
 OPEN BRANCH FROM BUS 243011 TO BUS 243148 CKT 1   /*05FULTON     138.0 - 05WINDFL     138.0
 OPEN BRANCH FROM BUS 243048 TO BUS 243148 CKT 1   /*05N WALD     138.0 - 05WINDFL     138.0
 OPEN BRANCH FROM BUS 243048 TO BUS 245708 CKT 1   /*05N WALD     138.0 - 05N WALDO     69.0
 OPEN BRANCH FROM BUS 243048 TO BUS 270372 CKT 1   /*05N WALD     138.0 - AD1-106 TAP  138.0
 OPEN BRANCH FROM BUS 245708 TO BUS 245716 CKT 1   /*05N WALDO     69.0 - 05WALDO       69.0
END
CONTINGENCY 'AEP_P1-2_#14768_SRT-A-1'
 OPEN BRANCH FROM BUS 242963 TO BUS 243011 CKT 1   /*05HEDDSS     138.0 - 05FULTON     138.0
 OPEN BRANCH FROM BUS 242963 TO BUS 243153 CKT 1   /*05HEDDSS     138.0 - 05WMTVER     138.0
 OPEN BRANCH FROM BUS 242963 TO BUS 245540 CKT 1   /*05HEDDSS     138.0 - 05BLOOMFLD8  138.0
 OPEN BRANCH FROM BUS 243011 TO BUS 243148 CKT 1   /*05FULTON     138.0 - 05WINDFL     138.0
 OPEN BRANCH FROM BUS 243048 TO BUS 243148 CKT 1   /*05N WALD     138.0 - 05WINDFL     138.0
 OPEN BRANCH FROM BUS 243048 TO BUS 245708 CKT 1   /*05N WALD     138.0 - 05N WALDO     69.0
 OPEN BRANCH FROM BUS 243048 TO BUS 270372 CKT 1   /*05N WALD     138.0 - AD1-106 TAP  138.0
END
CONTINGENCY 'AEP_P4_#5710_05WMTVER 138_B_SRT-A'
 OPEN BRANCH FROM BUS 242950 TO BUS 243153 CKT 1   /*05ACADEM     138.0 - 05WMTVER     138.0
 OPEN BRANCH FROM BUS 242963 TO BUS 243153 CKT 1   /*05HEDDSS     138.0 - 05WMTVER     138.0
 OPEN BRANCH FROM BUS 243098 TO BUS 243153 CKT 1   /*05SHARPR     138.0 - 05WMTVER     138.0
 OPEN BRANCH FROM BUS 243153 TO BUS 245562 CKT 1   /*05WMTVER     138.0 - 05W MT VER    69.0
 REMOVE SWSHUNT FROM BUS 243153                    /*05WMTVER     138.0
END
CONTINGENCY 'AEP_P2-2_#5710_05WMTVER 138_1_SRT-A'
 OPEN BRANCH FROM BUS 242950 TO BUS 243153 CKT 1   /*05ACADEM     138.0 - 05WMTVER     138.0
 OPEN BRANCH FROM BUS 242963 TO BUS 243153 CKT 1   /*05HEDDSS     138.0 - 05WMTVER     138.0
 OPEN BRANCH FROM BUS 243098 TO BUS 243153 CKT 1   /*05SHARPR     138.0 - 05WMTVER     138.0
 OPEN BRANCH FROM BUS 243153 TO BUS 245562 CKT 1   /*05WMTVER     138.0 - 05W MT VER    69.0
 REMOVE SWSHUNT FROM BUS 243153                    /*05WMTVER     138.0
END
243155 to 242989 ckt 1
270584 to 243155 ckt 1

Short Circuit Analysis

Short Circuit analysis is not performed as part of the Phase I System Impact Study. Short Circuit analysis will commence in the Phase II System Impact Study.

Stability Analysis

Stability analysis is not performed as part of the Phase I System Impact Study. Stability analysis will commence in the Phase II System Impact Study.

Reactive Power Analysis

Reactive Power analysis is not performed as part of the Phase I System Impact Study. Reactive Power analysis will commence in the Phase II System Impact Study.

Steady-State Voltage Analysis

Steady State Voltage Analysis is Not Required.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-018Powerton-Goodings GroveIn Service
AA1-095Halfway-Marlowe 34.5kVIn Service
AA2-184Atlantic-Red Bank 34kVIn Service
AB1-001Absecon 12 kVIn Service
AB1-006Meadow Lake 345kVIn Service
AB1-096Carroll-Mt. Airy 34.5kVIn Service
AB1-124Carroll-Monocacy 34.5kVPartially in Service - Under Construction
AB1-125Carroll-Monocacy 34.5kVIn Service
AB1-127St. Thomas-Guilford 34.5kVIn Service
AB1-128St. Thomas-Mercersburg 34.5kVIn Service
AB1-138Navy 34.5kVIn Service
AB1-139Metuchen 26kVIn Service
AB1-141Church-Wye Mills 138 kV IIn Service
AB1-142Church-Wye Mills 138 kV IIIn Service
AB1-176Price 25kV IIEngineering & Procurement
AB2-029Remington 34.5kVIn Service
AB2-032Church-Wye Mills 138 kVIn Service
AB2-037Keeney-Steele 230kVUnder Construction
AB2-049Gloucester Township 12kVIn Service
AB2-067Kammer-Vassell 765kVIn Service
AB2-070Mt. Pulaski-BrokawIn Service
AB2-093Ormet 138kVIn Service
AB2-133Chestertown 69kVUnder Construction
AB2-135Church-Kent 69kVIn Service
AB2-136Cambridge-West Cambridge 69kVUnder Construction
AB2-153Church-Wye Mills 138 kVIn Service
AB2-157Prince George's County 12kVIn Service
AB2-158Louisa-South Anna 230kVIn Service
AB2-170East Lima-Marysville 345kVIn Service
AB2-179Townsend 138kVIn Service
AC1-001Delano 138kVIn Service
AC1-010Gloucester 26kVUnder Construction
AC1-017Levittown 13 kVIn Service
AC1-030Cinnaminson 13kVIn Service
AC1-033Kewanee 138 kVIn Service
AC1-044Kammer-Vassell 765kVIn Service
AC1-053Lanesville-BrokawPartially in Service - Under Construction
AC1-068Atlanta 69kV IIn Service
AC1-069Atlanta 69kV IIIn Service
AC1-076Locust Grove-Paytes 115kVIn Service
AC1-078Beatty-London 138kVIn Service
AC1-082Ravenswood-Hemlock 69kVUnder Construction
AC1-085Stuart-Clinton 345kVIn Service
AC1-089Hillsboro-Wildcat 138kVIn Service
AC1-091Cedar Creek 138kV IEngineering & Procurement
AC1-092Cedar Creek 138kV IIEngineering & Procurement
AC1-093Cedar Creek 138kV IIIEngineering & Procurement
AC1-094Cedar Creek 138kV IVEngineering & Procurement
AC1-111Aurora 138kVIn Service
AC1-120Mitchell-Mountain Run 115kVEngineering & Procurement
AC1-121Mitchell-Mountain Run 115kVEngineering & Procurement
AC1-158Spotsylvania 500kVIn Service
AC1-165Atlanta 69kV IIIIn Service
AC1-166Atlanta 69kV IVIn Service
AC1-167Mark Center 69kVUnder Construction
AC1-168Kewanee-StreatorSuspended
AC1-174Losantville 345kVIn Service
AC1-175Losantville 345kVIn Service
AC1-188Rio-Lick 138kVEngineering & Procurement
AC1-194Elk 138kVActive
AC1-214Crescent RidgeIn Service
AC2-015Chatfield-Howard 138kVPartially in Service - Under Construction
AC2-023Hebron 69kVEngineering & Procurement
AC2-029Circleville 138kVSuspended
AC2-044Maddox Creek 345kVSuspended
AC2-059Biers Run-Circleville 138kVIn Service
AC2-060Buckskin 69kVIn Service
AC2-061Hillsboro-Clinton 138kVIn Service
AC2-067Camden-Crystal I 69kVEngineering & Procurement
AC2-068Camden-Crystal II 69kVEngineering & Procurement
AC2-088S. Bethel-Brown 69kVIn Service
AC2-090Losantville 345kVIn Service
AC2-103Beaver-Davis Besse 345 kV IEngineering & Procurement
AC2-111College Corner 138kVEngineering & Procurement
AC2-120Ripley 69kVIn Service
AC2-136East Hagerstown 12kVUnder Construction
AC2-154Davis Creek 138kVEngineering & Procurement
AC2-168Clinton 23kVIn Service
AC2-176Jay 138 kVIn Service
AC2-186Harrington 25kVUnder Construction
AC2-187Harrington 69kVUnder Construction
AC2-188Harrington 69 kVUnder Construction
AC2-195Galion-Roberts South 138 kVUnder Construction
AD1-013Twombly Road 138kVEngineering & Procurement
AD1-020Hunterstown-Lincoln 115 kVIn Service
AD1-060Mercersburg-Milnor 34.5 kVIn Service
AD1-061McConnelsburg-Mercersburg 34 kVIn Service
AD1-100Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVUnder Construction
AD1-101Continental 69 kVIn Service
AD1-106North Waldo-Wild Creek 138 kVSuspended
AD1-115Mountain Run-Mitchell 115 kVEngineering & Procurement
AD1-119Payne 69 kVIn Service
AD1-128Modoc-Delaware 138 kVPartially in Service - Under Construction
AD1-130Hardin Switch 345 kVIn Service
AD1-136South Bethel-Brown 69 kVIn Service
AD1-140Greene-Clark 138 kVEngineering & Procurement
AD1-155Meadow Brook-Strasburg 138 kVIn Service
AD2-009McConnellsburg 138 kVIn Service
AD2-016Biers Run-Circleville 138 kVIn Service
AD2-020Valley 138 kVEngineering & Procurement
AD2-027Camden Switch 26 kVIn Service
AD2-031Martinsville-Wilmington 69 kVIn Service
AD2-038Powerton-Nevada 345 kVUnder Construction
AD2-042Camden Switch 26 kV IIIn Service
AD2-047Davis Creek 138 kVSuspended
AD2-058St. Barnabas 13 kVIn Service
AD2-060Davis Creek 138kVEngineering & Procurement
AD2-065Atco 12 kVIn Service
AD2-066Mazon-Crescent Ridge 138 kVEngineering & Procurement
AD2-067Centerburg 138kVEngineering & Procurement
AD2-070Gilbert-Morris Park 34.5kVIn Service
AD2-071Strawton-Deer Creek 138 kVSuspended
AD2-079Capitol Ave 34.5kVIn Service
AD2-086Hardin Switch 345 kVIn Service
AD2-091Hardin Tap 345kVSuspended
AD2-092Marysville 345kVUnder Construction
AD2-093Marysville 345kVUnder Construction
AD2-096Marysville 345kVSuspended
AD2-115Lyons-Moselem 69kVIn Service
AD2-116Hokes-Grantley 69 kVIn Service
AD2-133Eagle Valley 115kVIn Service
AD2-134Shady OaksPartially in Service - Under Construction
AD2-135Williamstown 12kVPartially in Service - Under Construction
AD2-163Broadview-Tangy 138 kVIn Service
AD2-172Lena 138kVIn Service
AD2-180Elk Garden-Parr Run 138kVIn Service
AE1-040Greenfield 69 kVIn Service
AE1-041Edison 4kVIn Service
AE1-071Shade Gap-Roxbury 115 kVIn Service
AE1-079Maysville-Sharon 69 kVUnder Construction
AE1-081Landing 12.47 kVIn Service
AE1-090Hardin Switch 345 kVIn Service
AE1-091West Newton-Lynn 138 kVSuspended
AE1-092Blue Jacket-Kirby 138 kVActive
AE1-101McConnellsburg-Texas Eastern 138 kVIn Service
AE1-102Maddox Creek 345 kVSuspended
AE1-109Frenchs Mill 34 kVIn Service
AE1-113Mole Creek 345 kVEngineering & Procurement
AE1-114Maryland-Lancaster 138 kVActive
AE1-142Manitou-Pleasant Plains 34.5 kVIn Service
AE1-146Ebersole #2-Fostoria Central 138 kVUnder Construction
AE1-156Quakertown Solar II 34.5 kVPartially in Service - Under Construction
AE1-163Powerton-Nevada 345 kVEngineering & Procurement
AE1-166Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE1-170Kenzie Creek-Colby 138 kVSuspended
AE1-172Loretto-Wilton CenterActive
AE1-183Maysville-McDowell 69 kVEngineering & Procurement
AE1-185Hokes-Jackson 69 kVIn Service
AE1-196Hokes-Jackson 69 kV IIIn Service
AE1-205McLean 345 kVEngineering & Procurement
AE1-207Mississinewa-Gaston 138 kVSuspended
AE1-208Delaware-Van Buren 138 kVSuspended
AE1-209Desoto 345 kVSuspended
AE1-210Desoto 345 kVSuspended
AE1-227South Cumberland 69 kVSuspended
AE1-229Deepwater-Upper Pittsgrove 138 kVSuspended
AE1-237Andover (Maysville) 69kV IUnder Construction
AE1-245Haviland 138 kVUnder Construction
AE2-035Lena 138 kVIn Service
AE2-045Olive-Reynolds 345 kVEngineering & Procurement
AE2-048Muskingum-W. Millersport 345 kVEngineering & Procurement
AE2-054Warfordsburg 34 kVIn Service
AE2-072East Leipsic-Richland 138 kVIn Service
AE2-089Pennville-Adams 138 kVEngineering & Procurement
AE2-113Farmers Valley-Ridgeway 115 kVUnder Construction
AE2-114Midland 23 kV IIn Service
AE2-115Midland 23 kV IIIn Service
AE2-117ABW Tap-Alexandria 46 kVSuspended
AE2-126Dubois-Curwensville 34.5 kVIn Service
AE2-129Philipsburg-Clarence 34.5 kVIn Service
AE2-131Philipsburg-Karthaus 34.5Under Construction
AE2-136Muskingum River-W. Millersport 345 kVEngineering & Procurement
AE2-139East Towanda-Grover 230 kVEngineering & Procurement
AE2-148Beatty-Greene 345 kVIn Service
AE2-152Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE2-169Delaware-Van Buren 138 kVSuspended
AE2-172Mississinewa-Gaston 138 kVSuspended
AE2-173McLean 345 kVActive
AE2-175Jackson-Long Pond 69 kVPartially in Service - Under Construction
AE2-176Groton 138 kV SolarIn Service
AE2-181Snyder 69kVUnder Construction
AE2-206East Sidney-Quincy 138 kVIn Service
AE2-214Cole 345 kVEngineering & Procurement
AE2-216Hardin Switch 345 kVEngineering & Procurement
AE2-217East Springfield-London 138 kVEngineering & Procurement
AE2-219Bluff Point-Randolph 138 kVSuspended
AE2-220Losantville 345 kVEngineering & Procurement
AE2-221Clinton-Stuart 345 kVUnder Construction
AE2-223McLean 345 kVActive
AE2-224Bear Rock-Johnstown 230 kVIn Service
AE2-226Millville-Old Chapel 138 kVEngineering & Procurement
AE2-230Bartonsville-Meadow Brook 138 kVIn Service
AE2-234Liberty Center-Buckeye Tap 69 kVEngineering & Procurement
AE2-236Columbia-Northeast 138 kVSuspended
AE2-255Molecreek 345 kVEngineering & Procurement
AE2-262Moshannon-Milesburg 230 kVEngineering & Procurement
AE2-263Moshannon-Milesburg 230 kV IIEngineering & Procurement
AE2-267Woodsdale 345 kVEngineering & Procurement
AE2-281Powerton-Nevada 345 kVEngineering & Procurement
AE2-282East Fayette 138 kVIn Service
AE2-285Maysville 69 kVEngineering & Procurement
AE2-297Madison-Tanners Creek 138 kVIn Service
AE2-298Cavett Switch - West Van Wert 69 kVEngineering & Procurement
AE2-305Givens-Mechanicsburg 138 kVEngineering & Procurement
AE2-306Gunn Road 345 kVUnder Construction
AE2-309Carlos Junction-Lonaconing 34.5 kVIn Service
AE2-315Yankee Tap 69 kVIn Service
AE2-318Ford-Cedarville 138 kVSuspended
AE2-321Belvidere-Marengo 138 kVActive
AE2-322Mark Center 69 kVUnder Construction
AE2-323Twin Branch-Guardian 138 kVUnder Construction
AE2-325Valley 138 kVActive
AE2-341Sandwich-Plano 138 kVActive
AE2-342Woodstock 69 kVEngineering & Procurement
AE2-343Andover (Maysville) 69 kV IIUnder Construction
AF1-006Fairview East 34.5 kVIn Service
AF1-007Indian River 230 kV ISuspended
AF1-022Lake Lynn-Uniontown 25 kVIn Service
AF1-030Sandwich-Plano 138 kVActive
AF1-039Listonburg-Highpoint 24.9 kVIn Service
AF1-045Cedarville-Ford 138 kVSuspended
AF1-053Givens-Mechanicsburg 138 kVEngineering & Procurement
AF1-054Givens-Mechanicsburg 138 kVEngineering & Procurement
AF1-062Jug Street 138 kVEngineering & Procurement
AF1-064Weston 69 kVUnder Construction
AF1-071College Corner 138 kVEngineering & Procurement
AF1-078East Sidney-Quincy 138 kVIn Service
AF1-084Hartford-Almena 69 kVEngineering & Procurement
AF1-086Madera-Westover South 115 kVUnder Construction
AF1-091Varner - Sowers 138 kVEngineering & Procurement
AF1-092Huntington Jct. 138 kVSuspended
AF1-093Henderson-Stoneboro 69 kVEngineering & Procurement
AF1-094Union City-Cambridge Springs 34.5 kVEngineering & Procurement
AF1-098Four Mile Jct-Corry East 115 kVEngineering & Procurement
AF1-118Sorenson-Desoto 345 kVEngineering & Procurement
AF1-119Keystone-Desoto 345 kVEngineering & Procurement
AF1-120East Fayette 2 138 kVIn Service
AF1-122Cardington-Liberty 69 kVSuspended
AF1-134Philipsburg-Madera 34.5 kVEngineering & Procurement
AF1-136Warfordsburg-Purcell Junction 34.5 kVEngineering & Procurement
AF1-140Claysburg 23 kVEngineering & Procurement
AF1-147Poland Rd-Runway DP 230kVUnder Construction
AF1-153Motion-Ridgeway 46 kVSuspended
AF1-158Edison-Gravel Pit 138 kVIn Service
AF1-176Corey 138 kVActive
AF1-202Keystone-Desoto 345 kVUnder Construction
AF1-205Napoleon Muni 138 kVSuspended
AF1-206East Fayette 138 kVEngineering & Procurement
AF1-207Reynolds-Olive #1 345 kVEngineering & Procurement
AF1-215Olive-Reynolds 345 kVIn Service
AF1-223Keystone-Desoto 345 kVUnder Construction
AF1-227Marysville – Gunn Road 345 kVIn Service
AF1-228Beatty-Greene 345 kVEngineering & Procurement
AF1-229Galion-South Berwick 345 kVEngineering & Procurement
AF1-233Flemingsburg – Spurlock 138kVActive
AF1-249Nickel 12.47 kVIn Service
AF1-254Milnor-Huyetts 34.5 kVUnder Construction
AF1-262Upper Pittsgrove 12 kVIn Service
AF1-264Runnemede 13 kVIn Service
AF1-268Desoto-Jay 138 kVEngineering & Procurement
AF1-272Lucerne 115 kVEngineering & Procurement
AF1-275Cole 345 kVEngineering & Procurement
AF1-282Stuart-Clinton 345 kVEngineering & Procurement
AF1-283Stuart-Clinton 345 kVEngineering & Procurement
AF1-285Gunn Road 345 kVUnder Construction
AF1-290Feagans Mill-Millville 138 kVIn Service
AF1-291ABartonsville-Meadow Brook 138 kVIn Service
AF1-296Garden Plain 138 kVActive
AF1-299Otter Point 34.5 kV IIn Service
AF1-300Otter Point 34.5 kV IIIn Service
AF1-302Brookville-Squab Hollow 138 kVEngineering & Procurement
AF1-320Merrill Creek 115 kVEngineering & Procurement
AF1-322Meadow Lake 345 kVEngineering & Procurement
AF1-331Twombley RoadEngineering & Procurement
AF2-004Beaver 345 kVEngineering & Procurement
AF2-005Beaver 138 kVEngineering & Procurement
AF2-014Maddox Creek 345 kVEngineering & Procurement
AF2-039Shawville-Clearfield 34.5 kVEngineering & Procurement
AF2-041Nelson-Electric Junction 345 kVActive
AF2-048Rio-Lick 138 kVEngineering & Procurement
AF2-068Jay 138 kVActive
AF2-069Crescent Ridge 138 kVActive
AF2-075Bartonsville-Meadow Brook 138 kV IIIIn Service
AF2-078Reynolds-Olive #1 345 kVEngineering & Procurement
AF2-083Kenzie Creek-Stone Lake 69 kVUnder Construction
AF2-088Shawville-Clearfield 34.5 kV IIEngineering & Procurement
AF2-095Davis Creek 138 kVActive
AF2-103Haviland 138 kVIn Service
AF2-111North Clark-Spurlock 345 kVActive
AF2-122Kirk 138 kVUnder Construction
AF2-126Weston 69 kV IIActive
AF2-130Cobalt Corners 34.5 kVIn Service
AF2-132Reynolds-Olive #1 345 kVUnder Construction
AF2-133Reynolds-Olive #2 345 kVUnder Construction
AF2-134Olive-Reynolds #2 345 kVIn Service
AF2-138Flanders-West Wharton 34.5 kVIn Service
AF2-139Gilbert-Warren Glen 34.5 kVIn Service
AF2-142Nevada 345 kVActive
AF2-143Powerton-Nevada 345 kVActive
AF2-149Sharp Road 69 kVEngineering & Procurement
AF2-150Galion 138 kVUnder Construction
AF2-162Keystone-Desoto 345 kVEngineering & Procurement
AF2-173Desoto 345 kVActive
AF2-177Sorenson-DeSoto #2 345 kVActive
AF2-192Frenchtown Solar-West Flemington 34.5 kVSuspended
AF2-199Nelson-Electric Junction 345 kVActive
AF2-200Nelson-Electric Junction 345 kVActive
AF2-205Olive-Reynolds #2 345 kVEngineering & Procurement
AF2-224Allen 345 kVEngineering & Procurement
AF2-225McLean 345 kVActive
AF2-229Roxbury 23 kVEngineering & Procurement
AF2-235Titusville-Oil Creek 34.5 kVWithdrawn
AF2-238Mansfield-South Troy 34.5 kVEngineering & Procurement
AF2-247Bustleton 13.2 kVIn Service
AF2-250Edgewood 12 kV IIIIn Service
AF2-252Blue Mound 345 kVEngineering & Procurement
AF2-291Sporn South-Leon 138 kVEngineering & Procurement
AF2-298Crown-New Lebanon 69 kVEngineering & Procurement
AF2-325Jacktown 12 kVEngineering & Procurement
AF2-335Delaware-Royerton 138 kVActive
AF2-350Kensington 138 kVActive
AF2-352Blue Mound 345 kVEngineering & Procurement
AF2-354Washington 34.5 kV IIEngineering & Procurement
AF2-356Albright-Mt. Zion 138 kVUnder Construction
AF2-359Olive-University Park 345 kVEngineering & Procurement
AF2-371Harrison-Good Hope 138 kVEngineering & Procurement
AF2-375Ebersole-Fostoria 138 kVEngineering & Procurement
AF2-378Cambridge 12 kVEngineering & Procurement
AF2-379Princess Anne 25 kVUnder Construction
AF2-383Tolna 115 kVWithdrawn
AF2-388Keystone-Desoto 345 kVActive
AF2-389Kenzie Creek-Stone Lake 69 kVWithdrawn
AF2-392Nelson-Dixon 138 kVActive
AF2-396Stinger 138 kVActive
AF2-421East Hazelton-Weatherly Tap 69Engineering & Procurement
AF2-440Hillsboro-Middleboro 138 kVEngineering & Procurement
AG1-017Jay 138 kVUnder Construction
AG1-024Centerburg 138 kVEngineering & Procurement
AG1-034Centerburg 138 kVEngineering & Procurement
AG1-039Galion 138 kV IIUnder Construction
AG1-040Morgan Street-Mount Hope 34.5 kVEngineering & Procurement
AG1-047Jay 138 kVEngineering & Procurement
AG1-054Potter-Harlan 69 kVEngineering & Procurement
AG1-100Venango-Saegertown 34.5 kVEngineering & Procurement
AG1-107Hillsboro-Middleboro 138 kVEngineering & Procurement
AG1-118Sugar Grove-Waterman 138kVActive
AG1-125Marysville-Flatlick 765 kVEngineering & Procurement
AG1-126Marysville-Flatlick 765 kVEngineering & Procurement
AG1-127Crego Rd 138 kVActive
AG1-164East Hazelton-Weatherly Tap 69 kVEngineering & Procurement
AG1-165East Hazelton-Weatherly Tap 69 kVEngineering & Procurement
AG1-188Manitou-Oyster Creek 34.5 kVEngineering & Procurement
AG1-189Oyster Creek-Bamber Lake 34.5Engineering & Procurement
AG1-191Chester-Pohatcong Mountain 34.5 kVPartially in Service - Under Construction
AG1-193Utica Junction 34.5 kVSuspended
AG1-197Morgan Street-Cochranton 34.5 kVSuspended
AG1-198Union City 34.5 kVUnder Construction
AG1-223Larrabee-Allaire 34.5 kVUnder Construction
AG1-226Dequine-Eugene 345 kVActive
AG1-232Magley 138 kVEngineering & Procurement
AG1-236Lanesville-Brokaw 345 kVActive
AG1-237Dequine-Eugene 345 kVEngineering & Procurement
AG1-254Salem-Woodstown 69 kVEngineering & Procurement
AG1-281Claysburg-HCR Tap 46 kVEngineering & Procurement
AG1-301Miller REC-Warrior Ridge 46 kVEngineering & Procurement
AG1-302Olive-Reynolds #1 345 kVUnder Construction
AG1-323Blue Jacket 138 kVActive
AG1-324Jay-Desoto 138 kVEngineering & Procurement
AG1-348Pequest River-Washington 34.5 kVIn Service
AG1-349Olive-Reynolds #2 345 kVEngineering & Procurement
AG1-351Harrison-Good Hope 138 kVEngineering & Procurement
AG1-363Black Oak-Hatfield 500 kVEngineering & Procurement
AG1-365Allen 345 kVEngineering & Procurement
AG1-366Allen 345 kVEngineering & Procurement
AG1-367DeSoto 345 kVActive
AG1-368Tillman 138 kVEngineering & Procurement
AG1-369Logtown 138 kVEngineering & Procurement
AG1-374Blue Mound 345 kVActive
AG1-375Sorenson-Desoto 345 kVActive
AG1-386Smith-Francis Junction 25 kVIn Service
AG1-397Walston 12 kVWithdrawn
AG1-410Maddox Creek-RP Mone 345 kVActive
AG1-411Maddox Creek-RP Mone 345 kVActive
AG1-433Keystone-DeSoto 345 kVActive
AG1-436Olive-University Park 345 kVActive
AG1-447Olive-University Park 345 kVActive
AG1-462Cordova 345 kVActive
AG1-469Gordonsville 34.5 kVEngineering & Procurement
AG1-478Wilmington 34.5 kVEngineering & Procurement
AG1-480Shawnee 34.5 kVEngineering & Procurement
AG1-482Hamilton 115 kVWithdrawn
AG1-495Gilbert-Rocktown 34.5 kVEngineering & Procurement
AG1-499Lambs 12.47 kVUnder Construction
AG1-500Beaver 345 kVEngineering & Procurement
AG1-501Beaver 138 kVEngineering & Procurement
AG1-554South Kenton 138 kVEngineering & Procurement
AG1-555Dequine 345 kVEngineering & Procurement
AG1-559Caroline Pines 22 kVEngineering & Procurement
AG2-029Forest G. Hipple-Collingwood 345 kVActive
AG2-057Cardington-Liberty 69 kV IIActive
AG2-063North Hampton 69 kVActive
AG2-072Rockport 765 kVActive
AG2-085Delaware-Royerton 138 kVActive
AG2-104Marysville-Flatlick 765 kVActive
AG2-106Marysville-Flatlick 765 kVActive
AG2-107Marysville-Flatlick 765 kVActive
AG2-109Fitchville-New London 69 kVActive
AG2-114Dresden-Pontiac Midpoint 345 kVActive
AG2-119Galion-Roberts South 138 kV IIActive
AG2-125Camden-Crystal 69 kVActive
AG2-149Galion-South Berwick 345 kVActive
AG2-162Jefferson-Greentown 765 kVActive
AG2-163Dequine-Eugene 345 kVActive
AG2-164Jefferson-Greentown 765 kVActive
AG2-165Dumont-Greentown 765 kVActive
AG2-191Mississinewa 138 kVActive
AG2-192Mississinewa 138 kVActive
AG2-212Dumont-Greentown 765 kVActive
AG2-216East Sidney-Quincy 138 kVActive
AG2-219Jefferson-Greentown 765 kVActive
AG2-230Dumont 345 kVActive
AG2-245Olive - Reynolds #1 345 kVActive
AG2-328Dumont - Greentown 765 kVActive
AG2-329S Berwick - Galion 345 kVActive
AG2-330Dumont - Greentown 765 kVActive
AG2-331Jefferson-Greentown 765 kVActive
AG2-363Powerton 345 kVActive
AG2-364Powerton 345 kVActive
AG2-378North Hampton – Medway 69 kVActive
AG2-385North Hampton 69 kVActive
AG2-400Allen 345 kVActive
AG2-401Losantville 345 kVActive
AG2-405Continental 69 kVActive
AG2-406Payne 69 kVActive
AG2-408Allen 345 kVActive
AG2-444Bixby - Biers Run 345 kVActive
AG2-449Jefferson-Greentown 765 kVActive
AG2-453Lasalle - Plano 345 kVActive
AG2-487Madison - Tanners Creek 138 kVActive
AG2-491Meadow Lake 345 kVActive
AG2-515Midway 345 kV IIIActive
AG2-516Pecatonica 138kVActive
AG2-519Royerton - Desoto 138 kVActive
AG2-524LaSalle Station - Mazon 138 kVActive
AG2-548Corwin - Elk 138 kVActive
AG2-550Bluff Point - Randolph 138 kVActive
AG2-551Bluff Point - Randolph 138 kVActive
AG2-564Sulphur Springs 138 kVActive
AG2-575Crego Rd. 138 kVActive
AG2-582Flint Run 500 kVActive
AG2-585Kensington 138kVActive
AG2-589Ravenswood - Hemlock 69 kVActive
AG2-637Randolph - Hodgin 138 kVActive
AG2-660Nelson-Electric Junction 345 kVActive
AG2-665Corwin - Elk 138 kVActive
AH1-044Nelson - Electric Junction 345 kVActive
AH1-047Marengo - Belvidere 138 kVActive
AH1-055Kyger Creek - Don Marquis 345 kVActive
AH1-059Sharp Road 69 kVActive
AH1-060Cardington-Liberty 69 kV IIIActive
AH1-069Jerome – Mohicanville 69 kVActive
AH1-070Jerome – Mohicanville 69 kVActive
AH1-146White Rock - Wayne 345 kVActive
AH1-147White Rock - Wayne 345 kVActive
AH1-150Nelson-Electric Junction 345 kVActive
AH1-151Nelson-Electric Junction 345 kVActive
AH1-153Dumont 345 kVActive
AH1-196Prairie 345 kVActive
AH1-234Wempletown - Paddock 345 kVActive
AH1-272Argenta - Twin Branch 345 kVActive
AH1-282Galion - Ohio Central 345 kVActive
AH1-285Sandwich 138 kVActive
AH1-302Olive - Reynolds 345 kVActive
AH1-304Delaware-Van Buren 138 kVActive
AH1-305Olive - Reynolds 345 kVActive
AH1-306Mississinewa-Gaston 138 kVActive
AH1-308Pennville - Adams 138 kVActive
AH1-309Kenzie Creek-Colby 138 kVActive
AH1-327Hardin Switch 345 kVActive
AH1-328Blue Jacket - Kirby 138 kVActive
AH1-337Randolph - Hodgin 138 kVActive
AH1-338McGirr Rd - Ritchie Road 138kVActive
AH1-339West Crawford 69 kVActive
AH1-341Stillman - Dixon 138KVActive
AH1-391Olive 138 kVActive
AH1-392Gravel Pit-Kankakee 138 kVActive
AH1-482Olive - Reynolds #2 345 kVActive
AH1-537Pierce - Kyger Creek 345 kVActive
AH1-539South Kenton 138 kVActive
AH1-541Chestnut 345 kVActive
AH1-542Crissinger-Kirby 138kVActive
AH1-543Mulberry – Tazewell 345 kVActive
AH1-567University Park 138 kVActive
AH1-661Cannelville 12.47 kVActive
AH1-664Goddard-Plumville 138 kVActive
AH1-665Goddard-Plumsville 138 kV IIActive
AH1-666Flemingsburg - Spurlock 138 kVActive
AH1-669Circleville-Biers Run 138 kVActive
AH1-670Blue Mound-Chestnut 345 kVActive
AH1-686Hanging Rock 765 kVActive
AH1-690Bay Shore - Lallendorf 345 kVActive
AH1-698Braidwood 345 kVActive
AH1-702Byron 345 kVActive
AH1-704Hannibal 138 kVActive
AH1-711Lemoyne 345 kVActive
AH1-714Lasalle 345 kVActive
AH1-718Nelson 345 kVActive
AH1-719Beverly 345 kVActive
AH1-735Richland 138 kVActive
U2-030Four Mile Ridge Wind 138kVIn Service
U2-072East Lima-Marysville 345kVIn Service
U2-073Frostburg 138kV IIIn Service
V1-011Haviland 138kVIn Service
V3-007Desoto-Tanners Creek #1 345kVIn Service
V4-067Cates Road Egg Harbor Township 12kVDeactivated
V4-073Yankee 12.5kVIn Service
W1-003Oak HallIn Service
W1-004Oak HallIn Service
W1-005Oak HallIn Service
W1-006Oak HallIn Service
W1-056Ada-Dunkirk 69kVIn Service
W1-130Vine Road 12kVIn Service
W2-030Egg Harbor TownshipIn Service
W2-048Brokaw-LanesvilleIn Service
W3-077Broadway-Stewartsville 34.5kVIn Service
W4-005Blue Mound-LathamIn Service
X1-042WatervlietIn Service
X2-022Brokaw-LanesvilleIn Service
X3-005Wildwood 12kVIn Service
X3-066Church Hill 69kVIn Service
Y1-033Penn Mar-Rock Wood 115kVIn Service
Y1-079Wye Mills 69kVIn Service
Y1-080Dorchester 12kVIn Service
Y3-023Country Side 12kVIn Service
Y3-024Bluff Point 12kVIn Service
Y3-058Rockawalkin 69kVIn Service
Z2-076Worcester South 25kVIn Service
Z2-077Worcester North 25kVIn Service
Z2-087Pontiac MidPoint-Brokaw 345kVIn Service
Z2-115Deer Creek 12.47kVIn Service
Z2-116Twin Branch 12.47kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with potential Affected System impacts. PJM initiates coordination with each Affected System Operator by providing a list of New Service Requests in the Cycle with potential impacts to their respective system. If the Affected System Operator indicates an Affected System Study is required, PJM will notify the Project Developer or Eligible Customer of the need for an Affected System Study. See below if any Affected System Operator requires a study for this project:

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

Based on the Phase I analysis results, this project may have a cost responsibility for the following System Reinforcements:

AH1-075 System Reinforcements:
TORTEP IDTitleAllocated Cost ($USD)
AEP(Pending) / AEP-TC2-18621AE1-091_POI 138.0 kV to 05W.NEWTONSS 138.0 kV ckt 1 - Rebuild$1,878,293
AEP(Pending) / AEP-TC2-1873005W.NEWTONSS 138kV – 05E LIMA 138kV - Rebuild$1,010,114
Grand Total:$2,888,407

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18621
Title
AE1-091_POI 138.0 kV to 05W.NEWTONSS 138.0 kV ckt 1 - Rebuild
Description
Rebuild ~9.8 miles of 138kV single circuit. At West Newton Sw: replace sub conductor
Total Cost ($USD)
$36,260,000
Allocated Cost ($USD)
$1,878,293
Time Estimate
32 to 48 Months

Contributor

FacilityContingency
05W.NEWTONSS-AE1-091_POI 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AH1-075
5.1 MW5.2%$1,878,293
AH1-339
9.6 MW9.8%$3,542,020
AH1-539
83.5 MW85.1%$30,839,687

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18730
Title
05W.NEWTONSS 138kV – 05E LIMA 138kV - Rebuild
Description
~5.0 miles (total 13.38 miles) 138kV single circuit rebuild. At East Lima: replace sub conductor and wave traps / line relaying and relay trip limit. At West Newton Sw: replace sub conductor.
Total Cost ($USD)
$19,500,000
Allocated Cost ($USD)
$1,010,114
Time Estimate
36 to 48 Months

Contributor

FacilityContingency
05E LIMA-05W.NEWTONSS 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AH1-075
5.1 MW5.2%$1,010,114
AH1-339
9.6 MW9.8%$1,904,837
AH1-539
83.5 MW85.1%$16,585,049

System Reinforcement: b4000.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.1
Title
Add two 765 kV breakers at Amos Substation to expand the breaker and a half scheme to accommodate the new Amos-Welton Spring 765 kV line (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-075 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-075 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)

System Reinforcement: b4000.2
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.2
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - AEP Section of the line is 30 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-075 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-075 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)

System Reinforcement: b4000.3
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.3
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - APS/FE Section of the line is 145 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-075 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-075 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)

System Reinforcement: b4000.4
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.4
Title
Construct a new 765 kV switchyard - Welton Spring (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-075 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-075 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)

System Reinforcement: b4000.5
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.5
Title
Install four 250 MVAR shunt capacitors, and a +/-500 MVAR STATCOM at Welton Spring 765 kV substation
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-075 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-075 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)

System Reinforcement: b4000.7
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.7
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line - in DVP local area/Millville to Lovettsville section, roughly 10.5 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-075 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-075 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)

System Reinforcement: b4000.8
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.8
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (DVP local area to Rocky Point, roughly 4.8 miles)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-075 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-075 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)

System Reinforcement: b4000.9
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.9
Title
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard (Projected ISD 6/1/2029)
Description
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard. Loop in the Doubs-Goose Creek 500 kV line, the Doubs-Aspen 500 kV line, and the Woodside-Goose Creek 500 kV line. Install two 765/500 kV transformer at Rocky Point substation. 765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-075 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-075 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)

System Reinforcement: b4000.11
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.11
Title
Expand Black Oak Substation & Loop in the 502 Jct-Woodside 500 kV line (Projected ISD 6/1/2029)
Description
Expand Black Oak Substation to accommodate the connection of the 502 Jct-Woodside 500 kV line and loop the 502 Jct-Woodside 500 kV line into the Black Oak substation by constructing ~0.85 miles of new 500 kV line into and out of Black Oak 500 kV substation
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-075 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-075 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)

System Reinforcement: b4000.10
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.10
Title
Install four 250 MVAR cap banks (two on 765 and two on 500 kV side) and a +/-500 MVAR STATCOM on the 765 kV Rocky Point yard
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-075 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-075 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.a
Title
Upgrade (4) 1024.5 ACAR 24/13 sub conductors at Davis Besse
Description
Upgrade (4) 1024.5 ACAR 24/13 sub conductors at Davis Besse
Total Cost ($USD)
$1,099,401
Allocated Cost ($USD)
$0
Time Estimate
14 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-075 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-075 could receive cost allocation. Although AH1-075 may not presently have cost responsibility for this upgrade, AH1-075 is a potential Aggregate Pool Contributor.

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.b
Title
Upgrade (3) 345kV bus and line side disconnect switches at Davis Besse substation at Davis Besse
Description
Upgrade (3) 345kV bus and line side disconnect switches at Davis Besse substation at Davis Besse
Total Cost ($USD)
$1,324,127
Allocated Cost ($USD)
$0
Time Estimate
37 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-075 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-075 could receive cost allocation. Although AH1-075 may not presently have cost responsibility for this upgrade, AH1-075 is a potential Aggregate Pool Contributor.

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.c
Title
Upgrade 345kV 1033.5 AAC 61 sub conductors at Davis Besse substation at Davis Besse
Description
Upgrade 345kV 1033.5 AAC 61 sub conductors at Davis Besse substation at Davis Besse
Total Cost ($USD)
$257,762
Allocated Cost ($USD)
$0
Time Estimate
13 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-075 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-075 could receive cost allocation. Although AH1-075 may not presently have cost responsibility for this upgrade, AH1-075 is a potential Aggregate Pool Contributor.

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.d
Title
Reconductor (possible rebuild) 345kV 20.75 miles of transmission line and line drops at both remote ends
Description
Reconductor (possible rebuild) 345kV 20.75 miles of transmission line and line drops at both remote ends using dual (2) 1590 54/19 "Falcon" ACSS
Total Cost ($USD)
$121,594,776
Allocated Cost ($USD)
$0
Time Estimate
71 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-075 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-075 could receive cost allocation. Although AH1-075 may not presently have cost responsibility for this upgrade, AH1-075 is a potential Aggregate Pool Contributor.

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.e
Title
Upgrade 345kV 3500 SAC 127 sub conductor at Davis Besse
Description
Upgrade 345kV 3500 SAC 127 sub conductor at Davis Besse
Total Cost ($USD)
$257,762
Allocated Cost ($USD)
$0
Time Estimate
13 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-075 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-075 could receive cost allocation. Although AH1-075 may not presently have cost responsibility for this upgrade, AH1-075 is a potential Aggregate Pool Contributor.

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.f
Title
Upgrade (2) 345kV Wave Traps at Bayshore and (2) at Davis Besse
Description
Upgrade (2) 345kV Wave Traps at Bayshore and (2) at Davis Besse
Total Cost ($USD)
$1,215,694
Allocated Cost ($USD)
$0
Time Estimate
22 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-075 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-075 could receive cost allocation. Although AH1-075 may not presently have cost responsibility for this upgrade, AH1-075 is a potential Aggregate Pool Contributor.

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.g
Title
Upgrade (2) 345kV circuit breakers at Bayshore and (2) at Davis Besse
Description
Upgrade (2) 345kV circuit breakers at Bayshore and (2) at Davis Besse
Total Cost ($USD)
$7,786,806
Allocated Cost ($USD)
$0
Time Estimate
60 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-075 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-075 could receive cost allocation. Although AH1-075 may not presently have cost responsibility for this upgrade, AH1-075 is a potential Aggregate Pool Contributor.

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.h
Title
Upgrade (8) 1590 AAC 61 sub conductor at BAYSHORE
Description
Upgrade (8) 1590 AAC 61 sub conductor at BAYSHORE
Total Cost ($USD)
$211,119
Allocated Cost ($USD)
$0
Time Estimate
13 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-075 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-075 could receive cost allocation. Although AH1-075 may not presently have cost responsibility for this upgrade, AH1-075 is a potential Aggregate Pool Contributor.

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.i
Title
Upgrade B34544 CT at BAYSHORE
Description
Upgrade B34544 CT at BAYSHORE
Total Cost ($USD)
$712,356
Allocated Cost ($USD)
$0
Time Estimate
20 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-075 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-075 could receive cost allocation. Although AH1-075 may not presently have cost responsibility for this upgrade, AH1-075 is a potential Aggregate Pool Contributor.

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.j
Title
Upgrade (1) 1590 ACSR 45/7 sub conductor at Davis Besse
Description
Upgrade (1) 1590 ACSR 45/7 sub conductor at Davis Besse
Total Cost ($USD)
$393,871
Allocated Cost ($USD)
$0
Time Estimate
13 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-075 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-075 could receive cost allocation. Although AH1-075 may not presently have cost responsibility for this upgrade, AH1-075 is a potential Aggregate Pool Contributor.

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.k
Title
Upgrade the B34545 and 34562 (4) Meter and (2) Relay Thermals at Bayshore and Davis Besse
Description
Upgrade the B34545 and 34562 (4) Meter and (2) Relay Thermals at Bayshore and Davis Besse
Total Cost ($USD)
$998,835
Allocated Cost ($USD)
$0
Time Estimate
19 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-075 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-075 could receive cost allocation. Although AH1-075 may not presently have cost responsibility for this upgrade, AH1-075 is a potential Aggregate Pool Contributor.

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-004.a
Title
Upgrade D120 and D125 disconnect switches at Beaver substation
Description
Upgrade D120 and D125 disconnect switches at Beaver substation
Total Cost ($USD)
$929,516
Allocated Cost ($USD)
$0
Time Estimate
22 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-075 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-075 could receive cost allocation. Although AH1-075 may not presently have cost responsibility for this upgrade, AH1-075 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02CARLIL 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-004.b
Title
Upgrade (1) 3000 SAC 169 line drop at Beaver
Description
Upgrade (1) 3000 SAC 169 line drop at Beaver
Total Cost ($USD)
$263,169
Allocated Cost ($USD)
$0
Time Estimate
12 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-075 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-075 could receive cost allocation. Although AH1-075 may not presently have cost responsibility for this upgrade, AH1-075 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02CARLIL 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-004.c
Title
Reconductor (possible rebuild) 18.22 miles of 954 ACSR 48/7 transmission line and (3) line drops at Beaver on the Beaver - Carlisle Ckt 1 345 kV
Description
Reconductor (possible rebuild) 18.22 miles of 954 ACSR 48/7 transmission line and (3) line drops at Beaver on the Beaver - Carlisle Ckt 1 345 kV using dual (2) 795 26/7 "Drake ACSS
Total Cost ($USD)
$109,211,408
Allocated Cost ($USD)
$0
Time Estimate
63 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-075 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-075 could receive cost allocation. Although AH1-075 may not presently have cost responsibility for this upgrade, AH1-075 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02CARLIL 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-004.d
Title
Upgrade (1) 3500 SAC 127 D120-to-B121 breaker lead at Beaver
Description
Upgrade (1) 3500 SAC 127 D120-to-B121 breaker lead at Beaver
Total Cost ($USD)
$265,209
Allocated Cost ($USD)
$0
Time Estimate
12 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-075 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-075 could receive cost allocation. Although AH1-075 may not presently have cost responsibility for this upgrade, AH1-075 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02CARLIL 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-014.a
Title
Reconductor (possible rebuild) 29.61 miles of transmission line and line drops ( line drops at Hayes) on the Beaver - Hayes Ckt 1 345 kV line
Description
Reconductor (possible rebuild) 29.61 miles of transmission line and line drops ( line drops at Hayes) on the Beaver - Hayes Ckt 1 345 kV line using dual (2) 954 54/7 "Cardinal" ACSS
Total Cost ($USD)
$175,902,477
Allocated Cost ($USD)
$0
Time Estimate
90 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-075 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-075 could receive cost allocation. Although AH1-075 may not presently have cost responsibility for this upgrade, AH1-075 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-014.b
Title
Upgrade 3500 SAC (2) B3 and (2) B6 breaker leads at Hayes
Description
Upgrade 3500 SAC (2) B3 and (2) B6 breaker leads at Hayes
Total Cost ($USD)
$152,573
Allocated Cost ($USD)
$0
Time Estimate
18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-075 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-075 could receive cost allocation. Although AH1-075 may not presently have cost responsibility for this upgrade, AH1-075 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-014.c
Title
Upgrade (2) L3000 wavetraps at Beaver and Hayes
Description
Upgrade (2) L3000 wavetraps at Beaver and Hayes
Total Cost ($USD)
$729,124
Allocated Cost ($USD)
$0
Time Estimate
18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-075 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-075 could receive cost allocation. Although AH1-075 may not presently have cost responsibility for this upgrade, AH1-075 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-014.d
Title
Upgrade (4) circuit breakers at Beaver and Hayes (B88, B115, B3, B6)
Description
Upgrade (4) circuit breakers at Beaver and Hayes (B88, B115, B3, B6)
Total Cost ($USD)
$7,937,520
Allocated Cost ($USD)
$0
Time Estimate
60 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-075 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-075 could receive cost allocation. Although AH1-075 may not presently have cost responsibility for this upgrade, AH1-075 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-014.e
Title
Upgrade the 1590 AAC (2) B88 and (2) B15 breaker leads at Beaver
Description
Upgrade the 1590 AAC (2) B88 and (2) B15 breaker leads at Beaver
Total Cost ($USD)
$152,573
Allocated Cost ($USD)
$0
Time Estimate
18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-075 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-075 could receive cost allocation. Although AH1-075 may not presently have cost responsibility for this upgrade, AH1-075 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-014.f
Title
Upgrade the B6 CT at Hayes
Description
Upgrade the B6 CT at Hayes
Total Cost ($USD)
$727,300
Allocated Cost ($USD)
$0
Time Estimate
20 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-075 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-075 could receive cost allocation. Although AH1-075 may not presently have cost responsibility for this upgrade, AH1-075 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-014.g
Title
Upgrade (3) 1590 AAC line drops at Beaver (line drop to WT, Phase 1&3 "B-B", and SHARED NODE TO: WT, PH 2 / 5" AL, PH 1&3)
Description
Upgrade (3) 1590 AAC line drops at Beaver (line drop to WT, Phase 1&3 "B-B", and SHARED NODE TO: WT, PH 2 / 5" AL, PH 1&3) using dual (2) 954 54/7 "Cardinal" ACSS
Total Cost ($USD)
$591,863
Allocated Cost ($USD)
$0
Time Estimate
18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-075 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-075 could receive cost allocation. Although AH1-075 may not presently have cost responsibility for this upgrade, AH1-075 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-014.h
Title
Upgrade the B88 and B115 CTs at Beaver
Description
Upgrade the B88 and B115 CTs at Beaver
Total Cost ($USD)
$1,258,596
Allocated Cost ($USD)
$0
Time Estimate
21 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-075 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-075 could receive cost allocation. Although AH1-075 may not presently have cost responsibility for this upgrade, AH1-075 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-014.i
Title
Upgrade the 10A B115 relay and B88 meter thermal at Beaver
Description
Upgrade the 10A B115 relay and B88 meter thermal at Beaver
Total Cost ($USD)
$509,895
Allocated Cost ($USD)
$0
Time Estimate
18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-075 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-075 could receive cost allocation. Although AH1-075 may not presently have cost responsibility for this upgrade, AH1-075 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-014.j
Title
Upgrade the B88 and B3 impedance relays at Beaver and Hayes
Description
Upgrade the B88 and B3 impedance relays at Beaver and Hayes
Total Cost ($USD)
$1,019,790
Allocated Cost ($USD)
$0
Time Estimate
19 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-075 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-075 could receive cost allocation. Although AH1-075 may not presently have cost responsibility for this upgrade, AH1-075 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-014.k
Title
Upgrade (9) 3000A disconnect switches at Beaver and Hayes (D:74,92,93,116,4,5,7,8,11)
Description
Upgrade (9) 3000A disconnect switches at Beaver and Hayes (D:74,92,93,116,4,5,7,8,11)
Total Cost ($USD)
$3,774,791
Allocated Cost ($USD)
$0
Time Estimate
29 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-075 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-075 could receive cost allocation. Although AH1-075 may not presently have cost responsibility for this upgrade, AH1-075 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-005.a
Title
Upgrade (3) disconnect switches at Beaver (D:120,166,165)
Description
Upgrade (3) disconnect switches at Beaver (D:120,166,165)
Total Cost ($USD)
$1,350,788
Allocated Cost ($USD)
$0
Time Estimate
37 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-075 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-075 could receive cost allocation. Although AH1-075 may not presently have cost responsibility for this upgrade, AH1-075 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-005.b
Title
Upgrade (4) 954 ACSR 45/7 overhead line and line drops at Beaver Substation
Description
Upgrade (4) 954 ACSR 45/7 overhead line and line drops at Beaver Substation
Total Cost ($USD)
$809,465
Allocated Cost ($USD)
$0
Time Estimate
15 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-075 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-075 could receive cost allocation. Although AH1-075 may not presently have cost responsibility for this upgrade, AH1-075 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-005c
Title
Upgrade 3500 SAC 127 B161 (2) breaker leads and (1) B121-to-D120 breaker lead at Beaver
Description
Upgrade 3500 SAC 127 B161 (2) breaker leads and (1) B121-to-D120 breaker lead at Beaver
Total Cost ($USD)
$191,109
Allocated Cost ($USD)
$0
Time Estimate
11 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-075 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-075 could receive cost allocation. Although AH1-075 may not presently have cost responsibility for this upgrade, AH1-075 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-005.d
Title
Reconductor (possible rebuild) 8.37 miles of 954 ACSR 48/7 transmission line on the Beaver - Lake Avenue Ckt 1 345 kV
Description
Reconductor (possible rebuild) 8.37 miles of 954 ACSR 48/7 transmission line on the Beaver - Lake Avenue Ckt 1 345 kV using dual (2) 954 54/7 "Cardinal" ACSS
Total Cost ($USD)
$50,053,445
Allocated Cost ($USD)
$0
Time Estimate
38 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-075 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-075 could receive cost allocation. Although AH1-075 may not presently have cost responsibility for this upgrade, AH1-075 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 1 line(Any)

System Reinforcement: n9227.0
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
n9227.0 / TC1-ATSI-001.b
Title
Upgrade T-line drops, overhead substation conductor and TL reconductor
Description
Reconductor (possible rebuild) of 8.12 miles of dual transmission line and (2) single conductor line drops at Beaver on the Beaver-Lake Ave Ckt 2 345 kV line using triple (3) 1113 54/19 ""Finch"" ACSS"
Total Cost ($USD)
$48,873,856
Allocated Cost ($USD)
$0
Time Estimate
37 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-075 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-075 could receive cost allocation. Although AH1-075 may not presently have cost responsibility for this upgrade, AH1-075 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-021.a
Title
Upgrade (4) circuit breakers at Beaver and Lake Ave (B:3,4,216,219)
Description
Upgrade (4) circuit breakers at Beaver and Lake Ave (B:3,4,216,219)
Total Cost ($USD)
$7,786,809
Allocated Cost ($USD)
$0
Time Estimate
56 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-075 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-075 could receive cost allocation. Although AH1-075 may not presently have cost responsibility for this upgrade, AH1-075 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-021.b
Title
Upgrade 1590 AAC B3, B4, B216 and B219 breaker leads at Beaver and Lake Ave
Description
Upgrade 1590 AAC B3, B4, B216 and B219 breaker leads at Beaver and Lake Ave
Total Cost ($USD)
$305,540
Allocated Cost ($USD)
$0
Time Estimate
12 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-075 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-075 could receive cost allocation. Although AH1-075 may not presently have cost responsibility for this upgrade, AH1-075 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-021.c
Title
Upgrade the (3) B216, B219 and B4 1500 CTs
Description
Upgrade the (3) B216, B219 and B4 1500 CTs
Total Cost ($USD)
$853,850
Allocated Cost ($USD)
$0
Time Estimate
16 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-075 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-075 could receive cost allocation. Although AH1-075 may not presently have cost responsibility for this upgrade, AH1-075 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-021.d
Title
Upgrade (3) 1590 line drops at Beaver and Lake Ave
Description
Upgrade (3) 1590 line drops at Beaver and Lake Ave
Total Cost ($USD)
$690,685
Allocated Cost ($USD)
$0
Time Estimate
12 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-075 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-075 could receive cost allocation. Although AH1-075 may not presently have cost responsibility for this upgrade, AH1-075 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-021.e
Title
Upgrade the (1) B219 1200 CT to PVD at Beaver
Description
Upgrade the (1) B219 1200 CT to PVD at Beaver
Total Cost ($USD)
$349,952
Allocated Cost ($USD)
$0
Time Estimate
16 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-075 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-075 could receive cost allocation. Although AH1-075 may not presently have cost responsibility for this upgrade, AH1-075 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-021.f
Title
Upgrade the (1) B216 relay thermal at Beaver
Description
Upgrade the (1) B216 relay thermal at Beaver
Total Cost ($USD)
$509,895
Allocated Cost ($USD)
$0
Time Estimate
18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-075 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-075 could receive cost allocation. Although AH1-075 may not presently have cost responsibility for this upgrade, AH1-075 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-021.g
Title
Upgrade (1) 4.00 SPS.AL PIPE at Beaver
Description
Upgrade (1) 4.00 SPS.AL PIPE at Beaver
Total Cost ($USD)
$178,089
Allocated Cost ($USD)
$0
Time Estimate
12 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-075 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-075 could receive cost allocation. Although AH1-075 may not presently have cost responsibility for this upgrade, AH1-075 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-021.h
Title
Upgrade (9) disconnect switches at Beaver and Lake Ave (D: 19,20,21,22, 212,215,217,218,220)
Description
Upgrade (9) disconnect switches at Beaver and Lake Ave (D: 19,20,21,22, 212,215,217,218,220)
Total Cost ($USD)
$3,850,794
Allocated Cost ($USD)
$0
Time Estimate
39 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-075 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-075 could receive cost allocation. Although AH1-075 may not presently have cost responsibility for this upgrade, AH1-075 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-021.i
Title
Upgrade the (2) B3 SEL411L impedance relays at Lake Ave
Description
Upgrade the (2) B3 SEL411L impedance relays at Lake Ave
Total Cost ($USD)
$509,895
Allocated Cost ($USD)
$0
Time Estimate
18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-075 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-075 could receive cost allocation. Although AH1-075 may not presently have cost responsibility for this upgrade, AH1-075 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-021.j
Title
Upgrade (2) 2.50 SPS.AL PIPE SCCIR at Beaver
Description
Upgrade (2) 2.50 SPS.AL PIPE SCCIR at Beaver
Total Cost ($USD)
$173,391
Allocated Cost ($USD)
$0
Time Estimate
12 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-075 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-075 could receive cost allocation. Although AH1-075 may not presently have cost responsibility for this upgrade, AH1-075 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-021.k
Title
Upgrade the (15) B216, B219, B3 and B4 2000 CTs at Beaver and Lake Ave
Description
Upgrade the (15) B216, B219, B3 and B4 2000 CTs at Beaver and Lake Ave
Total Cost ($USD)
$2,701,212
Allocated Cost ($USD)
$0
Time Estimate
17 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-075 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-075 could receive cost allocation. Although AH1-075 may not presently have cost responsibility for this upgrade, AH1-075 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-021.l
Title
Upgrade the (2) B216 SEL411L impedance relays at Lake Ave
Description
Upgrade the (2) B216 SEL411L impedance relays at Lake Ave
Total Cost ($USD)
$509,895
Allocated Cost ($USD)
$0
Time Estimate
18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-075 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-075 could receive cost allocation. Although AH1-075 may not presently have cost responsibility for this upgrade, AH1-075 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-021.m
Title
Upgrade (8) 5.00 SPS.AL PIPE SCCIR at Beaver
Description
Upgrade (8) 5.00 SPS.AL PIPE SCCIR at Beaver
Total Cost ($USD)
$250,039
Allocated Cost ($USD)
$0
Time Estimate
12 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-075 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-075 could receive cost allocation. Although AH1-075 may not presently have cost responsibility for this upgrade, AH1-075 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-020.a
Title
Upgrade B185 and B182 circuit breakers at Beaver
Description
Upgrade B185 and B182 circuit breakers at Beaver
Total Cost ($USD)
$3,893,404
Allocated Cost ($USD)
$0
Time Estimate
56 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-075 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-075 could receive cost allocation. Although AH1-075 may not presently have cost responsibility for this upgrade, AH1-075 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-020.b
Title
Upgrade (4) disconnect switches at Beaver (D186,184,181,183)
Description
Upgrade (4) disconnect switches at Beaver (D186,184,181,183)
Total Cost ($USD)
$1,699,640
Allocated Cost ($USD)
$0
Time Estimate
25 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-075 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-075 could receive cost allocation. Although AH1-075 may not presently have cost responsibility for this upgrade, AH1-075 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-020.c
Title
Upgrade 3000 AAC B185 and B185 breaker leads at Beaver
Description
Upgrade 3000 AAC B185 and B185 breaker leads at Beaver
Total Cost ($USD)
$187,449
Allocated Cost ($USD)
$0
Time Estimate
13 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-075 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-075 could receive cost allocation. Although AH1-075 may not presently have cost responsibility for this upgrade, AH1-075 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-020.d
Title
Reconductor (possible rebuild) 29.61 miles of transmission line and (4) line drops beginning at Beaver towards Davis Besse on the Beaver - Davis Besse Ckt 1 345 kV line
Description
Reconductor (possible rebuild) 29.61 miles of transmission line and (4) line drops beginning at Beaver towards Davis Besse on the Beaver - Davis Besse Ckt 1 345 kV line using dual (2) 1590 54/19 "Falcon" ACSS
Total Cost ($USD)
$149,403,319
Allocated Cost ($USD)
$0
Time Estimate
82 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-075 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-075 could receive cost allocation. Although AH1-075 may not presently have cost responsibility for this upgrade, AH1-075 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-020.e
Title
Upgrade (2) L3000 wavetraps at Beaver
Description
Upgrade (2) L3000 wavetraps at Beaver
Total Cost ($USD)
$620,600
Allocated Cost ($USD)
$0
Time Estimate
18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-075 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-075 could receive cost allocation. Although AH1-075 may not presently have cost responsibility for this upgrade, AH1-075 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-020.f
Title
Upgrade (2) B182 impedance relays at Beaver (SEL-321: Z2-BU & Z2-PR)
Description
Upgrade (2) B182 impedance relays at Beaver (SEL-321: Z2-BU & Z2-PR)
Total Cost ($USD)
$509,895
Allocated Cost ($USD)
$0
Time Estimate
19 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-075 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-075 could receive cost allocation. Although AH1-075 may not presently have cost responsibility for this upgrade, AH1-075 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-020.g
Title
Upgrade (2) B185 and B182 revenue meter CTs at Beaver
Description
Upgrade (2) B185 and B182 revenue meter CTs at Beaver
Total Cost ($USD)
$1,258,596
Allocated Cost ($USD)
$0
Time Estimate
21 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-075 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-075 could receive cost allocation. Although AH1-075 may not presently have cost responsibility for this upgrade, AH1-075 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-020.h
Title
Upgrade the B185 CT to PVD at Beaver
Description
Upgrade the B185 CT to PVD at Beaver
Total Cost ($USD)
$349,952
Allocated Cost ($USD)
$0
Time Estimate
17 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-075 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-075 could receive cost allocation. Although AH1-075 may not presently have cost responsibility for this upgrade, AH1-075 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-020.i
Title
Upgrade B182 relay thermal at Beaver
Description
Upgrade B182 relay thermal at Beaver
Total Cost ($USD)
$509,895
Allocated Cost ($USD)
$0
Time Estimate
19 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-075 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-075 could receive cost allocation. Although AH1-075 may not presently have cost responsibility for this upgrade, AH1-075 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-015.a
Title
Reconductor (possible rebuild) 21.68 miles of transmission line and (1) line drop (line drop at Lemoyne) on the Davis Besse - Lemoyne 345 kV
Description
Reconductor (possible rebuild) 21.68 miles of transmission line and (1) line drop (line drop at Lemoyne) on the Davis Besse - Lemoyne 345 kV using dual (2) 1272 54/19 "Pheasant" ACSS
Total Cost ($USD)
$126,131,949
Allocated Cost ($USD)
$0
Time Estimate
73 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-075 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-075 could receive cost allocation. Although AH1-075 may not presently have cost responsibility for this upgrade, AH1-075 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-02LEMOYN 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-015.b
Title
Upgrade (4) L300 wavetraps at Davis Besse and Lemoyne
Description
Upgrade (4) L300 wavetraps at Davis Besse and Lemoyne
Total Cost ($USD)
$1,132,675
Allocated Cost ($USD)
$0
Time Estimate
22 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-075 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-075 could receive cost allocation. Although AH1-075 may not presently have cost responsibility for this upgrade, AH1-075 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-02LEMOYN 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-008.a
Title
Upgrade D41 and D42 disconnect switches at Davis Besse
Description
Upgrade D41 and D42 disconnect switches at Davis Besse
Total Cost ($USD)
$967,716
Allocated Cost ($USD)
$0
Time Estimate
36 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-075 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-075 could receive cost allocation. Although AH1-075 may not presently have cost responsibility for this upgrade, AH1-075 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-008.b
Title
Upgrade (1) 1024 ACAR 6E550-52-1 "A" line drop at Davis Besse
Description
Upgrade (1) 1024 ACAR 6E550-52-1 "A" line drop at Davis Besse
Total Cost ($USD)
$263,169
Allocated Cost ($USD)
$0
Time Estimate
12 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-075 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-075 could receive cost allocation. Although AH1-075 may not presently have cost responsibility for this upgrade, AH1-075 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-008.c
Title
Reconductor (possible rebuild) 15.6 miles of 954 ACSR 45/7 on the Davis Besse - AC2-103 Tap 345 kV line
Description
Reconductor (possible rebuild) 15.6 miles of 954 ACSR 45/7 on the Davis Besse - AC2-103 Tap 345 kV line using dual (2) 1272 54/19 "Pheasant" ACSS
Total Cost ($USD)
$91,775,258
Allocated Cost ($USD)
$0
Time Estimate
57 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-075 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-075 could receive cost allocation. Although AH1-075 may not presently have cost responsibility for this upgrade, AH1-075 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-008.d
Title
Upgrade (2) 3500 SAC 127 line drops at Davis Besse
Description
Upgrade (2) 3500 SAC 127 line drops at Davis Besse
Total Cost ($USD)
$263,169
Allocated Cost ($USD)
$0
Time Estimate
12 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-075 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-075 could receive cost allocation. Although AH1-075 may not presently have cost responsibility for this upgrade, AH1-075 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-008.e
Title
Upgrade 3500 SAC B65 breaker leads and subconductor (D42 to wave trap) at Davis Besse
Description
Upgrade 3500 SAC B65 breaker leads and subconductor (D42 to wave trap) at Davis Besse
Total Cost ($USD)
$197,592
Allocated Cost ($USD)
$0
Time Estimate
13 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-075 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-075 could receive cost allocation. Although AH1-075 may not presently have cost responsibility for this upgrade, AH1-075 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-008.f
Title
Reconductor (possible rebuild) 18.7 miles of 954 ACSR 48/7 on the Davis Besse - AC2-103 TAP 345kV
Description
Reconductor (possible rebuild) 18.7 miles of 954 ACSR 48/7 on the Davis Besse - AC2-103 TAP 345kV using dual (2) 1272 54/19 "Pheasant" ACSS
Total Cost ($USD)
$111,822,087
Allocated Cost ($USD)
$0
Time Estimate
64 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-075 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-075 could receive cost allocation. Although AH1-075 may not presently have cost responsibility for this upgrade, AH1-075 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-008.g
Title
Upgrade (2) Wave Traps at Davis Besse
Description
Upgrade (2) Wave Traps at Davis Besse
Total Cost ($USD)
$620,599
Allocated Cost ($USD)
$0
Time Estimate
20 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-075 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-075 could receive cost allocation. Although AH1-075 may not presently have cost responsibility for this upgrade, AH1-075 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-008.i
Title
Upgrade (4) 1590 ACSR 45/7 sub conductors at Davis Besse
Description
Upgrade (4) 1590 ACSR 45/7 sub conductors at Davis Besse
Total Cost ($USD)
$756,208
Allocated Cost ($USD)
$0
Time Estimate
13 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-075 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-075 could receive cost allocation. Although AH1-075 may not presently have cost responsibility for this upgrade, AH1-075 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-008.j
Title
Upgrade (2) 13.03 Ohm B65 Impedance Relays at Davis Besse
Description
Upgrade (2) 13.03 Ohm B65 Impedance Relays at Davis Besse
Total Cost ($USD)
$509,895
Allocated Cost ($USD)
$0
Time Estimate
18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-075 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-075 could receive cost allocation. Although AH1-075 may not presently have cost responsibility for this upgrade, AH1-075 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-008.k
Title
Upgrade (2) 6.65 Ohm B65 Impedance Relays at Davis Besse
Description
Upgrade (2) 6.65 Ohm B65 Impedance Relays at Davis Besse
Total Cost ($USD)
$509,895
Allocated Cost ($USD)
$0
Time Estimate
18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-075 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-075 could receive cost allocation. Although AH1-075 may not presently have cost responsibility for this upgrade, AH1-075 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-008.l
Title
Upgrade Circuit Breaker B65 at Davis Besse
Description
Upgrade Circuit Breaker B65 at Davis Besse
Total Cost ($USD)
$2,068,856
Allocated Cost ($USD)
$0
Time Estimate
54 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-075 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-075 could receive cost allocation. Although AH1-075 may not presently have cost responsibility for this upgrade, AH1-075 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-008.m
Title
Upgrade (2) B65 Meter Thermals at Davis Besse
Description
Upgrade (2) B65 Meter Thermals at Davis Besse
Total Cost ($USD)
$509,895
Allocated Cost ($USD)
$0
Time Estimate
18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-075 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-075 could receive cost allocation. Although AH1-075 may not presently have cost responsibility for this upgrade, AH1-075 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-008.h
Title
Upgrade Circuit Breaker 34564 at Davis Besse
Description
Upgrade Circuit Breaker 34564 at Davis Besse
Total Cost ($USD)
$2,068,856
Allocated Cost ($USD)
$0
Time Estimate
54 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-075 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-075 could receive cost allocation. Although AH1-075 may not presently have cost responsibility for this upgrade, AH1-075 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18681
Title
05E LIMA 345.0 kV to 05SW LIM 345.0 kV ckt 1 - Rebuild
Description
AEP owned line, ~14.66 miles (total 21.97 miles) of 345kV single circuit needs to be rebuilt. Existing conductor is 1-1414 ACSR/PE 62/19 & 1-1708.8 ACSR/AE 66/19
Total Cost ($USD)
$58,640,000
Allocated Cost ($USD)
$0
Time Estimate
24 to 36 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-075 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-075 could receive cost allocation. Although AH1-075 may not presently have cost responsibility for this upgrade, AH1-075 is a potential Aggregate Pool Contributor.

FacilityContingency
05E LIMA-05SW LIM 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18700
Title
05GUNN RD SW 345.0 kV to 05BOKESCRK 345.0 kV ckt 1- Rebuild
Description
AEP owned line, 16.54 miles of 345kV single circuit with PE conductor (1-1275 ACSR/PE 54/19) needs to be rebuilt
Total Cost ($USD)
$66,000,000
Allocated Cost ($USD)
$0
Time Estimate
24 to 36 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-075 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-075 could receive cost allocation. Although AH1-075 may not presently have cost responsibility for this upgrade, AH1-075 is a potential Aggregate Pool Contributor.

FacilityContingency
05GUNN RD SW-05BOKESCRK 345.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.6
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.6
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (Welton Spring to DVP local area, roughly 21 miles) (VA Portion)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-075 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-075 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18733
Title
05BOKESCRK 345kV to 05MARYSV 345kV ckt 1 - Reconductor
Description
Reconductor line between Marysville - Boke Creek 345 kV due to paper expanded line. New line will be 2-954 ACSR RAIL
Total Cost ($USD)
$6,810,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 52 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-075 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-075 could receive cost allocation. Although AH1-075 may not presently have cost responsibility for this upgrade, AH1-075 is a potential Aggregate Pool Contributor.

FacilityContingency
05MARYSV-05BOKESCRK 345.0 kV Ckt 1 line(Any)

Attachments

AH1-075 One Line Diagram

AH1-075 One Line Diagram.jpg
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.