AH1-086 Phase I Study Report

v1.00 released 2025-10-29 20:12

Morrisville 230kV

90.0 MW Capacity / 90.0 MW Energy

Introduction

This Phase I System Impact Study Report (PH1) has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, sections 307 and 308 for New Service Requests (projects) in Transition Cycle 2. The Project Developer/Eligible Customer (developer) is Summersweet Energy Center, LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is Virginia Electric and Power Company (d/b/a Dominion Energy Virginia).

Preface

The Phase I System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle executive summary format and (ii) an individual project-level basis. The Phase I System Impact Study Results (for both the executive summary and individual reports) will be publicly available on PJM’s website. Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.3, PJM takes the following actions during the Phase I System Impact Study:
  1. PJM studies each New Service Request on a summer peak, winter peak and light load RTEP base case study. The case year is dependent on the new services cycle under study. PJM will identify the base case year to be used in the study of a specific cycle on its website.
  2. PJM will only perform load flow analysis during the Phase I System Impact Study.
  3. In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with Affected System impacts and provides each Affected System Operator with a list of New Service Request in the Cycle with potential impacts to their respective system.
  4. PJM will create both the short circuit and stability base cases to be used in the Phase II System Impact Study.
  5. The Phase I System Impact Study results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.
The Transmission Owner takes the following actions during the Phase I System Impact Study:
  1. Identify required Interconnection Facilities to accommodate the New Service Request.
  2. Identify required Network Upgrades to mitigate system violations from the Phase I System Impact Study.
  3. Provide planning-level preliminary estimates of Interconnection Facilities and Network Upgrades including scope, cost and elapsed time to complete the work.

Decision Point I Requirements

At the close of Phase I System Impact Study, PJM will initiate Decision Point I (DP1). During DP1, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.A.1. Additional information on these elements is available in PJM Manual 14H sections 4.4, 6, and 7.

Allowable project modifications at Decision Point I are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

General

The Project Developer has proposed a Storage facility located in the Virginia Electric and Power Company (d/b/a Dominion Energy Virginia) zone — Fauquier County, Virginia. The installed facilities will have a total capability of 90.0 MW with 90.0 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AH1-086
Project Name:
Morrisville 230kV
Project Developer Name:
Summersweet Energy Center, LLC
State:
Virginia
County:
Fauquier
Transmission Owner:
Virginia Electric and Power Company (d/b/a Dominion Energy Virginia)
MFO:
90.0
MWE:
90.0
MWC:
90.0
Battery Storage Specification:
360.0 MWh, 4.0-hr class
Grid Charging:
Yes
Fuel Type:
Storage
Basecase Study Year:
2028

Physical Interconnection Facility Study

Physical Interconnection Facilities Study is not performed as part of the Phase I System Impact Study. Physical Interconnection Facilities Study will commence in the Phase II System Impact Study.

Point of Interconnection

AH1-086 will interconnect on the Virginia Electric and Power Company (d/b/a Dominion Energy Virginia) transmission system at Morrisville 230 kV.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In the Phase I SIS, the costs shown are subject to change as a result of a facility study performed by the TO during the Phase II or Phase III System Impact Study.

Based on the Phase I SIS results, the AH1-086 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit are also shown below.

Cost Summary
DescriptionCost Allocated to AH1-086Cost Subject to Readiness*
Transmission Owner Interconnection Facilities (TOIF)$875,000$0
Other Scope$0$0
Option To Build Oversight$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$0$0
Network Upgrades$1,375,000$1,375,000
System Reliability Network Upgrades
Steady State Thermal & Voltage (SP & LL)$0$0
Transient Stability$0$0
Short Circuit$0$0
Transmission Owner Analysis
SubRegional$0$0
Distribution$0$0
Affected System Reinforcements
AFS - PJM Violatons$0$0
AFS - Non-PJM Violations$0$0
Total$2,250,000$1,375,000

* Contributes to calculation for Readiness Deposit #2 (RD2). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim deliverability study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 309 (Decision Point I) A.1.a.i and PJM Manual 14H, section 6.2, Readiness Deposit #2 (RD2) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point I (DP1), the Project Developer or Eligible Customer is required to submit Readiness Deposit #2, which is calculated as 10% of cost allocation for required Phase I Network Upgrades minus Readiness Deposit #1.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Readiness Deposit #2 Due for Project AH1-086

Readiness Deposit #2 has been calculated for the project based on the Phase I System Impact Study results and is shown in the table below. This Readiness Deposit #2 must be provided at Decision Point I through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit
Project ID10% of cost allocation for Phase I Network UpgradesReadiness Deposit #1 Received (RD1)Readiness Deposit #2 (RD2) for AH1-086 Project due at DP1
ABA - B
AH1-086$137,500$360,000$0

Note: Failure to provide an acceptable form of Readiness Deposit #2 by the end of Decision Point I will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Transmission Owner Interconnection Facilities
RTEP IDDescriptionTotal Cost ($USD)Allocated Cost ($USD)
(Pending)Install the Point of Change in Ownership (PCO) disconnect switch, the overhead line conductor from the PCO to the bus position that serves as the Point of Interconnection (POI), as well as any metering and associated protection equipment.$3,500,000 $875,000 (See Note 1)
Network Upgrades
RTEP IDDescriptionTotal Cost ($USD)Allocated Cost ($USD)
(Pending)Add one (1) new 230 kV breaker to the existing Morrisville 230 kV Substation. This station will serve as the interconnection location for AH1-086, AH1-087, AH1-088, and AH1-089, where the projects will be sharing interconnection facilities. Additional substation modification/expansion cost may be required after detailed design.$5,500,000 $1,375,000 (See Note 1)

Based on the scope of work for the Interconnection Facilities, it is expected to take a range of 46 to 50 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

The schedule for any required Network Impact Reinforcements will be more clearly identified in the Phase II and Phase III System Impact Studies.

Note 1: A Common Use Upgrade is a Network Upgrade that is needed for the interconnection of Generating Facilities or Merchant Transmission Facilities of more than one Project Developer or Eligible Customer and which is the shared responsibility of each Project Developer or Eligible Customer. If multiple Project Developers request to connect to the same interconnection substation, the Transmission Owner will determine the cost to accommodate all the requests at the substation. The cost for the interconnection will be allocated in proportion to the number of required terminations into the substation.

Transmission Owner Analysis

PJM performed a power flow analysis of the transmission system using a 2028 load flow model and the results were verified by Dominion.

 

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. Dominion interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AH1-086 was evaluated as a 90.0 MW (90.0 MW Capacity) injection in the Dominion area.

AH1-086 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 90.0 MW (90.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2DVP
6GI1MRUN-6REMNGCT 230.0 kV Ckt 1 line
DVP_P1-2: LN 2077_SRT-A
SingleAC135.43 %571.52B773.9915.68
GD2DVP
6GI1MRUN-6REMNGCT 230.0 kV Ckt 1 line
DVP_P4-2: 2077T2086_SRT-A
BreakerAC111.53 %699.0C779.615.68
GD2DVP
6GI1MRUN-6REMNGCT 230.0 kV Ckt 1 line
DVP_P4-2: 207762_SRT-S
BreakerAC111.5 %699.0C779.3815.68
GD2DVP
8BRAMBLETON-AH1-727 TP 500.0 kV Ckt 1 line
DVP_P1-2: LN 9344_SRT-A
SingleAC106.63 %3256.16B3472.0724.44

Details for 6GI1MRUN-6REMNGCT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2077_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6GI1MRUN-6REMNGCT 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2077_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:135.43 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:773.99
MW Contribution:15.68
Bus #Bus NameTypeMW Contribution
3150281M RUN A
50/50
37.335
3150291M RUN B
50/50
37.035
3150301M RUN C
50/50
37.312
3151721LOISA A
50/50
4.7
3151731LOISA B
50/50
4.724
3151741LOISA C
50/50
0.258
3151751LOISA D
50/50
4.724
3151761LOISA E
50/50
9.632
3151771S ANNAG1
50/50
0.235
3151781S ANNAS1
50/50
0.121
3151791S ANNAG2
50/50
0.235
3151801S ANNAS2
50/50
0.121
3147346CASHSCORNER
Solar/Wind Harmer
0.153
3141196NOKESVL
Solar/Wind Helper
0.588
315651AD1-115 GEN
Solar/Wind Helper
0.462
315683AE1-153 C
Solar/Wind Harmer
10.714
316006AB2-029 C
Solar/Wind Helper
0.166
971253AH1-086 GEN
50/50
15.683
971255AH1-087 GEN
50/50
3.485
971257AH1-088 GEN
50/50
3.485
971259AH1-089 GEN
50/50
3.485
966001AG1-469 GEN
Solar/Wind Harmer
0.034
972183AH1-676 GEN
50/50
78.905
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.286
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.491
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.415
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.934
NYPJM->LTFIMP_NY
CLTF
0.331
LGEELTFEXP_LGEE->PJM
CLTF
0.183
WECLTFEXP_WEC->PJM
CLTF
0.093
CPLELTFEXP_CPLE->PJM
CLTF
0.82
TVALTFEXP_TVA->PJM
CLTF
0.401
MECLTFEXP_MEC->PJM
CLTF
0.46
LAGNLTFEXP_LAGN->PJM
CLTF
0.789
SIGELTFEXP_SIGE->PJM
CLTF
0.014

Details for 6GI1MRUN-6REMNGCT 230.0 kV Ckt 1 line l/o DVP_P4-2: 2077T2086_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6GI1MRUN-6REMNGCT 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 2077T2086_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.53 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:779.6
MW Contribution:15.68
Bus #Bus NameTypeMW Contribution
3150281M RUN A
50/50
37.335
3150291M RUN B
50/50
37.035
3150301M RUN C
50/50
37.312
3151721LOISA A
Adder
4.429
3151731LOISA B
Adder
4.452
3151751LOISA D
Adder
4.452
3151761LOISA E
Adder
9.077
3147346CASHSCORNER
Solar/Wind Harmer
0.115
3141196NOKESVL
Solar/Wind Helper
0.588
315651AD1-115 GEN
Solar/Wind Helper
0.462
315683AE1-153 C
Solar/Wind Harmer
14.106
316006AB2-029 C
Solar/Wind Helper
0.166
971253AH1-086 GEN
50/50
15.683
971255AH1-087 GEN
50/50
3.485
971257AH1-088 GEN
50/50
3.485
971259AH1-089 GEN
50/50
3.485
966001AG1-469 GEN
Solar/Wind Harmer
0.124
972183AH1-676 GEN
Adder
74.36
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.286
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.491
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.415
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.934
NYPJM->LTFIMP_NY
CLTF
0.331
LGEELTFEXP_LGEE->PJM
CLTF
0.183
WECLTFEXP_WEC->PJM
CLTF
0.093
CPLELTFEXP_CPLE->PJM
CLTF
0.82
TVALTFEXP_TVA->PJM
CLTF
0.401
MECLTFEXP_MEC->PJM
CLTF
0.46
LAGNLTFEXP_LAGN->PJM
CLTF
0.789
SIGELTFEXP_SIGE->PJM
CLTF
0.014

Details for 6GI1MRUN-6REMNGCT 230.0 kV Ckt 1 line l/o DVP_P4-2: 207762_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6GI1MRUN-6REMNGCT 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 207762_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.5 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:779.38
MW Contribution:15.68
Bus #Bus NameTypeMW Contribution
3150281M RUN A
50/50
37.335
3150291M RUN B
50/50
37.035
3150301M RUN C
50/50
37.312
3151721LOISA A
Adder
4.429
3151731LOISA B
Adder
4.452
3151751LOISA D
Adder
4.452
3151761LOISA E
Adder
9.077
3147346CASHSCORNER
Solar/Wind Harmer
0.115
3141196NOKESVL
Solar/Wind Helper
0.588
315651AD1-115 GEN
Solar/Wind Helper
0.462
315683AE1-153 C
Solar/Wind Harmer
14.106
316006AB2-029 C
Solar/Wind Helper
0.166
971253AH1-086 GEN
50/50
15.683
971255AH1-087 GEN
50/50
3.485
971257AH1-088 GEN
50/50
3.485
971259AH1-089 GEN
50/50
3.485
966001AG1-469 GEN
Solar/Wind Harmer
0.124
972183AH1-676 GEN
Adder
74.36
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.286
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.491
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.415
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.934
NYPJM->LTFIMP_NY
CLTF
0.331
LGEELTFEXP_LGEE->PJM
CLTF
0.183
WECLTFEXP_WEC->PJM
CLTF
0.093
CPLELTFEXP_CPLE->PJM
CLTF
0.82
TVALTFEXP_TVA->PJM
CLTF
0.401
MECLTFEXP_MEC->PJM
CLTF
0.46
LAGNLTFEXP_LAGN->PJM
CLTF
0.789
SIGELTFEXP_SIGE->PJM
CLTF
0.014

Details for 8BRAMBLETON-AH1-727 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 9344_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
8BRAMBLETON-AH1-727 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 9344_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.63 %
Rating:3256.16 MVA
Rating Type:B
MVA to Mitigate:3472.07
MW Contribution:24.44
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
Adder
0.459
3144293JTRSVLE
Adder
0.545
3144293JTRSVLE
Adder
0.545
3144293JTRSVLE
Adder
0.545
3147043LAWRENC
Solar/Wind Harmer
0.105
3147043LAWRENC
Adder
1.589
3147133PAMPLIN
Solar/Wind Harmer
0.539
3147133PAMPLIN
Solar/Wind Harmer
0.137
3147133PAMPLIN
Solar/Wind Harmer
0.172
20390526W1-045 C
Solar/Wind Helper
0.368
20671828STAW2-080
Solar/Wind Helper
0.027
20671928W4-073
Solar/Wind Helper
0.09
20673628F1S_V4-069
Solar/Wind Helper
0.03
20673728F2S_V4-070
Solar/Wind Helper
0.03
20673828FLE_V3-070
Solar/Wind Helper
0.092
20674128FR_U2-059
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.023
20674628WNG_W3-110
Solar/Wind Helper
0.09
20674828DL_W4-046
Solar/Wind Helper
0.008
20674928WA_W3-044
Solar/Wind Helper
0.099
20675128HRM_W1-127
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20675528CPH_W2-050
Solar/Wind Helper
0.088
20675728RH_W2-091
Solar/Wind Helper
0.137
20675828AU_W4-064
Solar/Wind Helper
0.03
20675928HOL_W4-097
Solar/Wind Helper
0.05
20676128MHD_W3-029
Solar/Wind Helper
0.097
20676228FRD_X1-012
Solar/Wind Helper
0.092
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20676428JCR_X2-075
Solar/Wind Helper
0.068
20676728BRNX1-095
Solar/Wind Helper
0.03
20714528FRN_Y2-051
Solar/Wind Helper
0.058
20714828MDF_W3-079
Solar/Wind Helper
0.132
20714928UPF_X1-085
Solar/Wind Helper
0.005
20715028HAN_X4-015
Solar/Wind Helper
0.058
20715228NPK_W1-113
Solar/Wind Helper
0.079
20715728PEM_W1-119
Solar/Wind Helper
0.097
20715828PEM_W1-120
Solar/Wind Helper
0.097
20716028EGP_W2-019
Solar/Wind Helper
0.019
20716928W4-060COL
Solar/Wind Helper
0.052
20720528MAN_W1-024
Solar/Wind Helper
0.029
20720628TIN_W1-124
Solar/Wind Helper
0.192
20720728JCB_W1-129
Solar/Wind Helper
0.058
20720828JCB_W4-025
Solar/Wind Helper
0.064
207408W3-077 C
Solar/Wind Helper
0.084
207439AE1-081 C O1
Solar/Wind Helper
0.019
214067T20SOLAR
Solar/Wind Helper
0.011
217206BARNGR HS C
Solar/Wind Helper
0.006
217208PARK ELE C
Solar/Wind Helper
0.004
217209CENTRL HS C
Solar/Wind Helper
0.008
217211CAMDEN ST C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
232404W1-003 C
Solar/Wind Helper
0.523
232408W1-005 C
Solar/Wind Helper
0.523
232410W1-006 C
Solar/Wind Helper
0.523
232426Y1-080 FULL
Solar/Wind Helper
0.04
232428Y3-058 C
Solar/Wind Helper
0.348
23777801MSM_W1-116
Solar/Wind Helper
0.131
23777901MDS_W4-102
Solar/Wind Helper
0.197
3137176SLIGO L2192
Solar/Wind Harmer
0.792
3140676OCCOQUN
Adder
0.566
3141316ARNOLDS
Adder
0.53
3141346CRANES
Adder
0.266
3141426STAFORD
Solar/Wind Harmer
0.05
3141843SHACKLE
Adder
1.073
3141843SHACKLE
Adder
1.073
3141906WESTMOR
Solar/Wind Harmer
0.086
3142296MT RD221
Adder
0.683
3142366NRTHEST
Adder
0.693
3142416OLDCHRC
Solar/Wind Harmer
0.554
3142416OLDCHRC
Solar/Wind Harmer
2.065
3142416OLDCHRC
Solar/Wind Harmer
0.212
3142433PROV 92
Solar/Wind Harmer
0.84
3142433PROV 92
Adder
0.408
3142433PROV 92
Adder
0.408
3142433PROV 92
Adder
0.408
3142433PROV 92
Adder
0.408
3142433PROV 92
Adder
0.408
3142433PROV 92
Adder
0.408
3142956BIRDNECK
Solar/Wind Harmer
0
3143096IRON208
Adder
0.866
3143096IRON208
Adder
0.883
3143096IRON208
Adder
0.883
3143316POE
Solar/Wind Harmer
0.803
3143336POWHATN
Solar/Wind Harmer
3.511
3143336POWHATN
Solar/Wind Harmer
2.984
3144216WINCHST
Adder
0.774
3144356SAPONY
Solar/Wind Harmer
1.625
3145506HICKORY
Solar/Wind Harmer
0.8
3145506HICKORY
Solar/Wind Harmer
0.48
3145506HICKORY
Solar/Wind Harmer
0.12
3146386ELIZ CT
Solar/Wind Harmer
0.197
3146396TANGLEW
Solar/Wind Harmer
0.542
3146776BUCKING
Solar/Wind Harmer
0.699
3146776BUCKING
Solar/Wind Harmer
0.057
3146776BUCKING
Solar/Wind Harmer
0.063
3146776BUCKING
Solar/Wind Harmer
0.07
3150071POSSM 5
Adder
101.873
3150151POSSMC1
Adder
2.229
3150151POSSMC1
Adder
2.229
3150151POSSMC1
Adder
2.229
3150181POSSMC2
Adder
2.229
3150181POSSMC2
Adder
2.229
3150181POSSMC2
Adder
2.248
3150211REMNGT1
Adder
37.902
3150221REMNGT2
50/50
40.487
3150231REMNGT3
50/50
43.711
3150241REMNGT4
50/50
40.756
3150281M RUN A
50/50
43.576
3150291M RUN B
50/50
43.226
3150301M RUN C
50/50
43.549
3150331BIRCHWDA
Adder
38.122
3150341NORNECKC1
Adder
2.213
3150341NORNECKC1
Adder
2.231
3150351NORNECKC2
Adder
2.16
3150351NORNECKC2
Adder
2.124
3150391LDYSMT3
Adder
31.782
3150401LDYSMT4
Adder
31.841
3150411LDYSMT5
Adder
31.941
3150671DARBY 1
Adder
15.189
3150681DARBY 2
Adder
15.207
3150691DARBY 3
Adder
15.26
3150701DARBY 4
Adder
15.225
3150921YORKTN3
Adder
5.164
217081WEATEXAS C
Solar/Wind Helper
0.013
217169METRODIV C
Solar/Wind Helper
0.004
217201HACKENSOLA C
Solar/Wind Helper
0.003
217202FBANKSOLAR C
Solar/Wind Helper
0.003
218428ETC SOLAR C
Solar/Wind Helper
0.005
218438BLK ROCK C
Solar/Wind Helper
0.028
218440SUMMTASSOC C
Solar/Wind Helper
0.017
218660EHAMPSOLAR C
Solar/Wind Helper
0.034
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219249CENTRALDIV C
Solar/Wind Helper
0.01
219272CLEANLIGHT C
Solar/Wind Helper
0.026
219276PARKLANDSO C
Solar/Wind Helper
0.091
219291REEVESSOUT C
Solar/Wind Helper
0.012
219348LDSOLAR C
Solar/Wind Helper
0.117
219607WPEMNERT C
Solar/Wind Helper
0.082
219612MATRIX C
Solar/Wind Helper
0.024
219615MILLCREEK C
Solar/Wind Helper
0.027
219620RIDERU C
Solar/Wind Helper
0.001
219766PARADISE C
Solar/Wind Helper
0.056
227927V4-067C
Solar/Wind Helper
0.01
235020AA1-095 C
Solar/Wind Helper
0.059
3150981CHESPKA
Adder
2.51
3150991CHESPKB
Adder
2.056
3150991CHESPKB
Adder
2.106
3151081ELIZAR1
Adder
18.434
3151091ELIZAR2
Adder
18.114
3151101ELIZAR3
Adder
18.67
3151171GRAVELC
Adder
2.168
3151171GRAVELC
Adder
2.85
3151191GRAVEL3
Adder
14.643
3151201GRAVEL4
Adder
14.831
3151211GRAVEL5
Adder
14.643
3151221GRAVEL6
Adder
14.814
3151721LOISA A
Adder
15.238
3151731LOISA B
Adder
15.317
3151751LOISA D
Adder
15.317
3151761LOISA E
Adder
31.228
3151861LOWMORA
Adder
1.283
3151861LOWMORA
Adder
1.233
3151881LOWMORC
Adder
1.253
3151881LOWMORC
Adder
1.273
3152601GOSPORTA
Adder
2.005
3152611GOSPORTB
Adder
2.56
3152621GOSPORTC
Adder
2.173
316075AC2-137 C
Solar/Wind Harmer
0.058
316077AC2-138 C
Solar/Wind Harmer
0.001
228728W1-130C
Solar/Wind Helper
0.055
228729W2-030 C
Solar/Wind Helper
0.113
3138133OCRAN
Solar/Wind Harmer
0.063
3138133OCRAN
Solar/Wind Harmer
0.126
3138283WHITEMARSH
Solar/Wind Harmer
0.048
3141766HARMONY
Solar/Wind Harmer
2.802
3141766HARMONY
Solar/Wind Harmer
0.042
3141783LANCAST
Solar/Wind Harmer
0.126
3141783LANCAST
Solar/Wind Harmer
0.084
3141813NORNECK
Solar/Wind Harmer
0.213
3141913WHIT STONE
Solar/Wind Harmer
0.21
3143226MDLTHAN
Solar/Wind Harmer
0.212
3143873LANEXA
Solar/Wind Harmer
0.126
3145273HOLLAND
Solar/Wind Harmer
0.145
3146376EDENTON
Solar/Wind Harmer
0.19
3146376EDENTON
Solar/Wind Harmer
0.847
3146376EDENTON
Solar/Wind Harmer
0.847
3146456SLIGO L269
Solar/Wind Harmer
3.521
3146456SLIGO L269
Solar/Wind Harmer
0.199
3146456SLIGO L269
Solar/Wind Harmer
0.199
3146486SUNBURY
Solar/Wind Harmer
0.197
3146486SUNBURY
Solar/Wind Harmer
0.197
3146516WINFALL
Solar/Wind Harmer
0.195
3146516WINFALL
Solar/Wind Harmer
0.195
3146516WINFALL
Solar/Wind Harmer
0.632
3146516WINFALL
Solar/Wind Harmer
0.195
3146516WINFALL
Solar/Wind Harmer
0.195
3146516WINFALL
Solar/Wind Harmer
0.195
3146626S HERTFORD
Solar/Wind Harmer
0.194
3146626S HERTFORD
Solar/Wind Harmer
0.194
3146626S HERTFORD
Solar/Wind Harmer
0.194
3146843MT LREL
Solar/Wind Harmer
0.159
3146843MT LREL
Solar/Wind Harmer
0.159
3146926FARMVIL
Solar/Wind Harmer
0.105
3146926FARMVIL
Solar/Wind Harmer
0.105
3147346CASHSCORNER
Solar/Wind Harmer
0.532
3147666LOUISA
Solar/Wind Harmer
0.979
3147666LOUISA
Solar/Wind Harmer
0.563
3147983MERCK5
Solar/Wind Harmer
0.05
232406W1-004 FULL
Solar/Wind Helper
0.523
232436AB1-176 C
Solar/Wind Helper
0.046
3141726DUNNSVL
Solar/Wind Harmer
0.851
3145663CRESWEL
Solar/Wind Harmer
0.523
316034AC1-036 C
Solar/Wind Harmer
0.012
316036AC1-147 C
Solar/Wind Harmer
0.037
316059AD1-063 C
Solar/Wind Harmer
0.001
316159AE1-175 C
Solar/Wind Harmer
0.179
316240AF1-291 C
Solar/Wind Harmer
0.002
316246AF1-032 C
Solar/Wind Harmer
0.09
316248AF1-058 C
Solar/Wind Harmer
0.001
316258AE1-075 C
Solar/Wind Harmer
0.149
316305AF2-043 C
Solar/Wind Harmer
0.002
316314AB2-024 C
Solar/Wind Harmer
0.001
316315AB2-025 C
Solar/Wind Harmer
0.157
316316AC1-027 C
Solar/Wind Harmer
0.193
316317KELFORD C
Solar/Wind Harmer
0.017
316336AC2-165 C
Solar/Wind Harmer
0.008
316382AG1-145 C
Solar/Wind Harmer
0.002
316405AF2-144 C
Solar/Wind Harmer
0.001
230415AB2-049 C
Solar/Wind Helper
0.031
20742028HF_AC1-207
Solar/Wind Helper
0.143
207454AA2-184 E
Solar/Wind Helper
0.315
207459AE1-142 C O1
Solar/Wind Helper
0.295
207471AF2-354 C
Solar/Wind Helper
0.169
232424Y1-079 C
Solar/Wind Helper
0.12
3150371LDYSMT1
Adder
30.767
3150381LDYSMT2
Adder
30.569
218524CNTRALGAS1 C
Solar/Wind Helper
0.162
218526CNTRALGAS2 C
Solar/Wind Helper
0.163
233901CHERRYDALE C
Solar/Wind Helper
0.239
233939AC1-091 C
Solar/Wind Helper
0.361
233940AF2-379 C
Solar/Wind Helper
0.064
233970AC1-092 C
Solar/Wind Helper
0.361
233971AC1-093 C
Solar/Wind Helper
0.369
233972AC1-094 C
Solar/Wind Helper
0.312
219907AC1-030 C
Solar/Wind Helper
0.035
219914AD2-027 C
Solar/Wind Helper
0.117
237025AB1-124 C
Solar/Wind Helper
0.187
237030AB1-096 C
Solar/Wind Helper
0.08
237034AC2-136 C
Solar/Wind Helper
0.259
237038AE2-054 C
Solar/Wind Helper
0.293
3130156CHOWAN
Solar/Wind Harmer
0.19
3130156CHOWAN
Solar/Wind Harmer
0.19
3130156CHOWAN
Solar/Wind Harmer
0.19
3145336SMITFLD
Solar/Wind Harmer
0.811
3145336SMITFLD
Solar/Wind Harmer
0.081
3148133STUARTS
Solar/Wind Harmer
0.083
3141196NOKESVL
Solar/Wind Harmer
1.195
3147243WELCO
Solar/Wind Harmer
0.096
3141873WAN 176
Solar/Wind Harmer
3.731
3141873WAN 176
Solar/Wind Harmer
0.042
3143526WINTERP
Solar/Wind Harmer
1.104
3143526WINTERP
Solar/Wind Harmer
1.104
316404AE1-155 C
Solar/Wind Harmer
0.048
316017AA1-139 ULT1
Solar/Wind Harmer
0.111
316018AA1-139 ULT2
Solar/Wind Harmer
0.005
316181AB2-040 GEN
Solar/Wind Harmer
0.257
316033AB2-134 GEN
Solar/Wind Harmer
0.012
228754AB1-001 C
Solar/Wind Helper
0.027
316388AE2-253 GEN
Solar/Wind Harmer
0.625
235062AE1-101 C1
Solar/Wind Helper
1.773
205956AE1-196_GEN
Solar/Wind Helper
0.502
217204WCALDSOLAR C
Solar/Wind Helper
0.003
3148013FISHERV
Solar/Wind Harmer
0.079
3148013FISHERV
Solar/Wind Harmer
0.138
3145176PASQUOTANK
Solar/Wind Harmer
0.122
3132123MT JACKSON
Solar/Wind Harmer
0.381
3132273ORANGE
Solar/Wind Harmer
0.051
3142543TWELFTH
Solar/Wind Harmer
0.02
3144303KENBRDG
Solar/Wind Harmer
0.135
3147173SINAI
Solar/Wind Harmer
0.154
3148463FAIRFLD
Solar/Wind Harmer
0.12
237080AD1-060 GEN
Solar/Wind Helper
0.373
235067AD1-061 GEN
Solar/Wind Helper
0.532
237001AB1-127_GEN
Solar/Wind Helper
0.481
237002AB1-128_GEN
Solar/Wind Helper
0.48
238221AF1-254 C O1
Solar/Wind Helper
0.304
238208AF1-136 C
Solar/Wind Helper
0.215
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
235063AE1-101 C2
Solar/Wind Helper
1.773
237085AD2-009_GEN
Solar/Wind Helper
1.73
316494AC1-189 GEN
Solar/Wind Harmer
0.556
315616AA1-038_C
Solar/Wind Harmer
0.001
316420AA1-050 GEN
Solar/Wind Harmer
0.005
316005AA1-067
Solar/Wind Harmer
0.179
233944AB2-135 GEN
Solar/Wind Helper
0.605
233946AB2-136 GEN
Solar/Wind Helper
0.585
316426AA2-053 GEN
Solar/Wind Harmer
0.594
316190AA2-174 GEN
Solar/Wind Harmer
0
316327AA2-057 GEN
Solar/Wind Harmer
0.25
3156081AA2-088 GEN
Solar/Wind Harmer
0.004
233994AC2-023 GEN
Solar/Wind Helper
0.99
234033AF1-007_GEN
Solar/Wind Helper
7.236
315614AA2-178 GEN
Solar/Wind Harmer
1.07
315816AE2-034 GEN
Solar/Wind Harmer
0.803
316312AB1-027
Solar/Wind Harmer
0.381
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316049AB1-081 GEN
Solar/Wind Harmer
0.917
316011AB1-132 GEN
Solar/Wind Harmer
3.202
316369SG1_INVT
Solar/Wind Harmer
0.008
315651AD1-115 GEN
Solar/Wind Harmer
0.009
316023GEN1_S
Solar/Wind Harmer
0.409
316365GEN2_N
Solar/Wind Harmer
0.409
237061AD1-155 GEN
Solar/Wind Harmer
0.003
237006AB1-125 GEN
Solar/Wind Helper
0.14
23779801AA1-109
Solar/Wind Helper
0.222
315705AF1-075 GEN
Solar/Wind Harmer
4.991
316463AE2-346 GEN
Solar/Wind Harmer
0.154
315839AE2-212 C
Solar/Wind Harmer
0.002
233982AB2-133 GEN
Solar/Wind Helper
0.368
233915AB1-141 GEN
Solar/Wind Helper
0.516
233918AB1-142 GEN
Solar/Wind Helper
0.516
315835AF2-110_GEN
Solar/Wind Harmer
1.359
315821AE2-092 GEN
Solar/Wind Harmer
0.01
315814AE2-033 C
Solar/Wind Harmer
15.327
315671AE2-027_GEN
Solar/Wind Harmer
13.209
233930AB2-032 GEN
Solar/Wind Helper
0.391
233987AB2-037 GEN
Solar/Wind Helper
2.414
315662AE1-191 GEN
Solar/Wind Harmer
0.007
315666AE1-190 GEN
Solar/Wind Harmer
0.002
315673AE1-157 GEN
Solar/Wind Harmer
16.074
315813AE1-149 C
Solar/Wind Harmer
10.825
315683AE1-153 C
Solar/Wind Harmer
20.71
315742AE1-103 GEN
Solar/Wind Harmer
0.002
319010AE1-072 C
Solar/Wind Harmer
1.001
315657AE1-056 GEN
Solar/Wind Harmer
5.923
316065AD1-022 GEN
Solar/Wind Harmer
8.417
315697AD1-025 GEN
Solar/Wind Harmer
0.231
316185AD1-033 GEN
Solar/Wind Harmer
0.006
233933AB2-153 GEN
Solar/Wind Helper
0.239
315773AC2-141 GEN
Solar/Wind Harmer
7.404
316280AD1-041 GEN
Solar/Wind Harmer
0.004
233935AB2-179 C
Solar/Wind Helper
1.3
316003AC1-222 GEN
Solar/Wind Harmer
0.004
315722AD1-056 GEN
Solar/Wind Harmer
1.053
315724AD1-057 GEN
Solar/Wind Harmer
0.624
315732AD1-074 GEN1
Solar/Wind Harmer
1.056
315733AD1-074 GEN2
Solar/Wind Harmer
1.056
315735AD1-075 GEN1
Solar/Wind Harmer
0.529
315737AD1-076 GEN
Solar/Wind Harmer
2.365
316473AC1-191 GEN
Solar/Wind Harmer
0.726
316478AD1-087 GEN
Solar/Wind Harmer
0.607
316486AD2-202 GEN
Solar/Wind Harmer
0.178
316447AC1-158 HLD
Solar/Wind Harmer
3.008
316044AC1-158 PL1
Solar/Wind Harmer
1.369
316045AC1-158 PL2
Solar/Wind Harmer
4.376
316450AC1-158 RIC
Solar/Wind Harmer
0.365
315693AD1-088 GEN
Solar/Wind Harmer
8.533
316468AD1-105 GEN
Solar/Wind Harmer
-0.071
316072AD1-144
Solar/Wind Harmer
0.072
315778AD1-151 GEN
Solar/Wind Harmer
16.459
315687AD1-152 GEN
Solar/Wind Harmer
0.005
316156AD2-030 GEN
Solar/Wind Harmer
0.155
315785AD2-033 C
Solar/Wind Harmer
1.375
316337AD2-073 GEN
Solar/Wind Harmer
0.187
234015AF2-250 C
Solar/Wind Helper
0.039
234036AF2-325 C
Solar/Wind Helper
0.043
233990AG1-397 GEN
Solar/Wind Helper
0.278
207528AF2-192 GEN
Solar/Wind Helper
0.077
207484AF2-139 C O1
Solar/Wind Helper
0.084
207510AF2-138 C
Solar/Wind Helper
0.081
207518AF1-320_GEN
Solar/Wind Helper
1.579
207442AE1-156 GEN
Solar/Wind Helper
0.329
207437AD2-070 GEN
Solar/Wind Helper
0.138
313526AB2-022
Solar/Wind Harmer
0.107
316313AB2-026
Solar/Wind Harmer
0.124
207445AB1-138_GEN
Solar/Wind Helper
0.106
209116AE2-175 GEN
Solar/Wind Helper
1.78
3145513AHOSKIE
Solar/Wind Harmer
0.179
3145513AHOSKIE
Solar/Wind Harmer
0.376
233923SMA
Solar/Wind Helper
0.988
230433AD2-135 GEN
Solar/Wind Helper
0.017
230430AE1-229_GEN
Solar/Wind Helper
3.449
219680HOPEWELLV C1
Solar/Wind Helper
0.003
219686LUMSOLAR_N C
Solar/Wind Helper
0.041
219688LUMSOLAR_S C
Solar/Wind Helper
0.041
219908AB1-139 C
Solar/Wind Helper
0.075
219904AC1-010 C
Solar/Wind Helper
0.062
219906AC1-017 C
Solar/Wind Helper
0.043
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219258KINSLEYDEP C
Solar/Wind Helper
0.078
219304NAMERICA C
Solar/Wind Helper
0.134
219921AF1-264
Solar/Wind Helper
0.052
203975AE1-071-GEN
Solar/Wind Helper
2.597
211065PSPA IPP
Solar/Wind Helper
0.151
211065PSPA IPP
Solar/Wind Helper
0.151
207530AG1-191 GEN
Solar/Wind Helper
0.066
230511AF1-262
Solar/Wind Helper
0.015
205932AD2-116_GEN
Solar/Wind Helper
0.502
205941AD2-115 GEN
Solar/Wind Helper
0.494
205943AE1-185 GEN
Solar/Wind Helper
0.503
205917AD1-020 ES
Solar/Wind Helper
0.38
205916AD1-020 GEN
Solar/Wind Helper
1.767
270494AE1-108_GEN
Solar/Wind Harmer
1.806
3145746EVERETS
Solar/Wind Harmer
0.167
3145746EVERETS
Solar/Wind Harmer
0.167
3145746EVERETS
Solar/Wind Harmer
0.167
3145746EVERETS
Solar/Wind Harmer
0.167
3145746EVERETS
Solar/Wind Harmer
0.664
3145746EVERETS
Solar/Wind Harmer
0.167
3145746EVERETS
Solar/Wind Harmer
0.167
3145746EVERETS
Solar/Wind Harmer
0.167
3147623JAMES R
Solar/Wind Harmer
0.389
3146206CASHIE
Solar/Wind Harmer
0.182
3146206CASHIE
Solar/Wind Harmer
0.182
3146206CASHIE
Solar/Wind Harmer
0.182
3142666NORTHAMPTON
Solar/Wind Harmer
0.176
3142666NORTHAMPTON
Solar/Wind Harmer
0.176
3142666NORTHAMPTON
Solar/Wind Harmer
0.176
3142666NORTHAMPTON
Solar/Wind Harmer
0.106
3142666NORTHAMPTON
Solar/Wind Harmer
0.176
316274AC1-208 GEN
Solar/Wind Harmer
0.88
316349AD2-085 GEN
Solar/Wind Harmer
0.137
3156021HOLLOMANSOL
Solar/Wind Harmer
0.817
315652AC1-086 GEN
Solar/Wind Harmer
19.374
313506AB2-031 GEN
Solar/Wind Harmer
0.548
316006AB2-029 C
Solar/Wind Harmer
0.002
313527AB2-043 GEN
Solar/Wind Harmer
0.002
316322AB2-045
Solar/Wind Harmer
0.001
316359AB2-059 GEN
Solar/Wind Harmer
0.576
316131AB2-060 GEN
Solar/Wind Harmer
0.527
316192AB2-158 GEN
Solar/Wind Harmer
1.381
316083AB2-161 GEN
Solar/Wind Harmer
0.003
316174AB2-169 GEN
Solar/Wind Harmer
0.005
316087AB2-174 GEN
Solar/Wind Harmer
0.005
316132AB2-190 GEN1
Solar/Wind Harmer
1.107
316458AB2-190 GEN2
Solar/Wind Harmer
1.107
316263AC1-034 GEN
Solar/Wind Harmer
6.088
316129AC1-054 GEN
Solar/Wind Harmer
0.638
316123AC1-075 GEN
Solar/Wind Harmer
0.181
316210AC1-098 GEN
Solar/Wind Harmer
1.582
316212AC1-099_GEN
Solar/Wind Harmer
0.882
316118AC1-105 GEN
Solar/Wind Harmer
0.404
316254AC1-120 GEN1
Solar/Wind Harmer
0.583
316170AC1-121 GEN2
Solar/Wind Harmer
0.291
316222AC1-221 GEN
Solar/Wind Harmer
0.583
316375AC2-012 GEN
Solar/Wind Harmer
0.005
316311AC2-079 GEN
Solar/Wind Harmer
5.725
316283AC2-100 C
Solar/Wind Harmer
0.274
316339AD2-160 GEN
Solar/Wind Harmer
0.323
316164AC1-076 GEN
Solar/Wind Harmer
0.382
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316237AB2-079_GEN
Solar/Wind Harmer
0.001
316140AB2-099
Solar/Wind Harmer
0.064
316223AC1-118
Solar/Wind Harmer
0.155
316294AC1-161 GEN
Solar/Wind Harmer
3.512
315975AC1-164 GENB
Solar/Wind Harmer
0.646
315976AC1-164 GENA
Solar/Wind Harmer
21.836
316169AC1-164_GENC
Solar/Wind Harmer
18.864
316381AD1-082 GEN
Solar/Wind Harmer
0.21
316233AE1-074 FULL
Solar/Wind Harmer
0.17
316236AE1-162_GEN
Solar/Wind Harmer
0.002
316093AE2-104_GEN
Solar/Wind Harmer
3.331
315607AA1-063A GEN
Solar/Wind Harmer
0.365
3150851SPRUNCC
Adder
0.972
3150861SPRUNCD
Adder
0.972
230434AG1-499 GEN
Solar/Wind Helper
0.235
233964AF2-378 GEN
Solar/Wind Helper
0.043
3130546PLYMOUTH
Solar/Wind Harmer
0.184
3145543BTLEBRO
Solar/Wind Harmer
0.128
3145543BTLEBRO
Solar/Wind Harmer
0.16
3145543BTLEBRO
Solar/Wind Harmer
0.16
3145543BTLEBRO
Solar/Wind Harmer
0.16
3145593CAROLNA
Solar/Wind Harmer
0.218
3145593CAROLNA
Solar/Wind Harmer
0.175
3145593CAROLNA
Solar/Wind Harmer
0.175
3145683EARLEYS
Solar/Wind Harmer
0.179
3145683EARLEYS
Solar/Wind Harmer
0.179
3145683EARLEYS
Solar/Wind Harmer
0.179
3145683EARLEYS
Solar/Wind Harmer
0.358
230407AD2-065 C
Solar/Wind Helper
0.041
232422X3-066 FULL
Solar/Wind Helper
0.117
232432Z2-076 GEN
Solar/Wind Helper
0.069
232434Z2-077 GEN
Solar/Wind Helper
0.131
233996TM1833_GEN
Solar/Wind Helper
0.269
233997TMININ_4.2
Solar/Wind Helper
0.269
233998TM1NIN_3.36
Solar/Wind Helper
0.269
3130086AYDLETT
Solar/Wind Harmer
0.795
3137643SOCKMAN
Solar/Wind Harmer
0.704
3138126ROCKLANDING
Solar/Wind Harmer
0.094
3138266HYDRAULIC
Solar/Wind Harmer
0.004
3138266HYDRAULIC
Solar/Wind Harmer
0.007
3138543CONSLDL
Solar/Wind Harmer
0.107
3142053HEARTS
Solar/Wind Harmer
0.282
3142946ENON
Solar/Wind Harmer
0.021
3142946ENON
Solar/Wind Harmer
0.07
3144536CHRHLND
Solar/Wind Harmer
0.03
3144873MCLAUGH
Solar/Wind Harmer
0.005
3145453TOT5
Solar/Wind Harmer
0.226
3145493TOT1
Solar/Wind Harmer
0.723
3145493TOT1
Solar/Wind Harmer
0.377
3145573BETHELC
Solar/Wind Harmer
0.163
3145573BETHELC
Solar/Wind Harmer
0.163
3145603CNETO
Solar/Wind Harmer
0.151
3145783HORNRTN
Solar/Wind Harmer
0.174
3145783HORNRTN
Solar/Wind Harmer
3.102
3145783HORNRTN
Solar/Wind Harmer
2.482
3145783HORNRTN
Solar/Wind Harmer
0.776
3145783HORNRTN
Solar/Wind Harmer
0.31
3145796HORNRTN
Solar/Wind Harmer
0.521
3145796HORNRTN
Solar/Wind Harmer
0.573
3145796HORNRTN
Solar/Wind Harmer
0.174
3145796HORNRTN
Solar/Wind Harmer
0.174
3145796HORNRTN
Solar/Wind Harmer
0.695
3145796HORNRTN
Solar/Wind Harmer
0.556
3145796HORNRTN
Solar/Wind Harmer
0.07
3145823KELFORD
Solar/Wind Harmer
0.176
3145823KELFORD
Solar/Wind Harmer
0.176
3145893MURPHYS
Solar/Wind Harmer
1.217
3145893MURPHYS
Solar/Wind Harmer
0.327
3145893MURPHYS
Solar/Wind Harmer
0.304
3145893MURPHYS
Solar/Wind Harmer
0.809
3145893MURPHYS
Solar/Wind Harmer
0.182
3145893MURPHYS
Solar/Wind Harmer
0.727
3145893MURPHYS
Solar/Wind Harmer
0.182
3145893MURPHYS
Solar/Wind Harmer
0.491
3145933PARMELE
Solar/Wind Harmer
0.34
3145933PARMELE
Solar/Wind Harmer
0.17
3145933PARMELE
Solar/Wind Harmer
0.17
3145963POPLR C
Solar/Wind Harmer
0.176
3145963POPLR C
Solar/Wind Harmer
0.176
3146033SCOT NK
Solar/Wind Harmer
0.691
3146043SEABORD
Solar/Wind Harmer
0.179
3146073TAR RVR
Solar/Wind Harmer
0.163
3146083TARBORO
Solar/Wind Harmer
0.163
3146083TARBORO
Solar/Wind Harmer
0.163
3146173TUNIS
Solar/Wind Harmer
0.18
3146173TUNIS
Solar/Wind Harmer
0.18
3146173TUNIS
Solar/Wind Harmer
0.18
3146173TUNIS
Solar/Wind Harmer
0.18
3146233WITAKRS
Solar/Wind Harmer
0.817
3146233WITAKRS
Solar/Wind Harmer
0.648
3146233WITAKRS
Solar/Wind Harmer
0.111
3146263WOODLND
Solar/Wind Harmer
0.178
3146263WOODLND
Solar/Wind Harmer
0.178
3146293MARTNCO
Solar/Wind Harmer
0.158
3146406KITTY HAWK
Solar/Wind Harmer
0.025
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
316319Z2-044 C
Solar/Wind Harmer
0
316320Y1-086
Solar/Wind Harmer
0.001
316321Z2-027
Solar/Wind Harmer
0.037
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
942751AE2-291 GEN
Solar/Wind Harmer
6.934
944011AF1-069 GEN
Solar/Wind Harmer
11.68
944491AF1-114 GEN
Solar/Wind Harmer
0.001
944581AF1-123 GEN
Solar/Wind Harmer
45.254
944591AF1-124 GEN
Solar/Wind Harmer
45.415
944601AF1-125 GEN
Solar/Wind Harmer
44.557
944631AF1-128 GEN
Adder
99.968
944641AF1-129 GEN
Adder
98.867
946301AF1-294 GEN
Solar/Wind Harmer
3.377
959311AF2-222 GEN
Solar/Wind Harmer
15.084
959381AF2-229 GEN
Solar/Wind Helper
0.375
959561AF2-247 GEN
Solar/Wind Helper
0.021
960061AF2-297 GEN
Solar/Wind Harmer
6.556
960081AF2-299 GEN
Solar/Wind Harmer
1.72
960921AF2-383 GEN
Solar/Wind Helper
0.358
961601AG1-000A GEN
Solar/Wind Harmer
2.849
961601AG1-000A GEN
Solar/Wind Harmer
11.396
961611AG1-000B GEN
Solar/Wind Harmer
10.718
961611AG1-000B GEN
Solar/Wind Harmer
5.45
961671AG1-007 GEN
Solar/Wind Harmer
0.025
961681AG1-008 GEN
Solar/Wind Harmer
13.506
961791AG1-021 GEN
Solar/Wind Harmer
1.643
962331AG1-082 GEN
Solar/Wind Harmer
1.916
962491AG1-098 GEN
Solar/Wind Harmer
10.141
962561AG1-105 GEN
Solar/Wind Harmer
7.712
962571AG1-106 GEN
Solar/Wind Harmer
2.506
962861AG1-135 GEN
Solar/Wind Harmer
6.784
962971AG1-146 GEN
Solar/Wind Harmer
3.381
962981AG1-147 GEN
Solar/Wind Harmer
7.889
963171AG1-166 GEN
Solar/Wind Harmer
0.913
963181AG1-167 GEN
Solar/Wind Harmer
0.685
963191AG1-168 GEN
Solar/Wind Harmer
0.685
963391AG1-188 GEN
Solar/Wind Helper
0.084
963401AG1-189 GEN
Solar/Wind Helper
0.057
966801AG1-551 GEN
Solar/Wind Harmer
1.979
966811AG1-552 GEN
Solar/Wind Harmer
1.903
966871AG1-558 GEN
Solar/Wind Harmer
0.248
966881AG1-559 GEN
Solar/Wind Harmer
0.265
970009AG2-005 GEN
Solar/Wind Harmer
1.58
970053AG2-049 GEN
Adder
3.548
970085AG2-068 GEN
Solar/Wind Harmer
9.72
970087AG2-069 GEN
Solar/Wind Harmer
14.579
970099AG2-077 GEN
Solar/Wind Harmer
19.085
970117AG2-086 GEN
Solar/Wind Harmer
2.919
970117AG2-086 GEN
Solar/Wind Harmer
1.946
970129AG2-093 GEN
Solar/Wind Harmer
12.476
970129AG2-093 GEN
Solar/Wind Harmer
5.871
970133AG2-095 GEN
Solar/Wind Harmer
1.99
970163AG2-111 GEN
Solar/Wind Harmer
1.027
970165AG2-112 GEN
Solar/Wind Harmer
1.076
970181AG2-120 GEN
Solar/Wind Harmer
2.078
970189AG2-124 GEN
Solar/Wind Harmer
6.224
970221AG2-151 GEN
Solar/Wind Harmer
8.948
970257AG2-171 GEN
Solar/Wind Harmer
5.422
970285AG2-188 GEN
Solar/Wind Harmer
13.847
970293AG2-193 GEN
Solar/Wind Harmer
2.259
970301AG2-198 GEN
Solar/Wind Harmer
7.522
970317AG2-208 GEN
Solar/Wind Harmer
9.074
970323AG2-213 GEN
Solar/Wind Harmer
7.229
970327AG2-215 GEN
Solar/Wind Harmer
6.945
970401AG2-262 GEN
Solar/Wind Harmer
0.935
970581AG2-369 GEN
Solar/Wind Harmer
8.359
970601AG2-382 GEN
Solar/Wind Harmer
6.803
970657AG2-426 GEN
Solar/Wind Harmer
7.052
970657AG2-426 GEN
Solar/Wind Harmer
1.478
970659AG2-427 GEN
Solar/Wind Harmer
9.759
970659AG2-427 GEN
Solar/Wind Harmer
2.135
970661AG2-428 GEN
Solar/Wind Harmer
19.99
970661AG2-428 GEN
Solar/Wind Harmer
4.252
970673AG2-436 GEN
Solar/Wind Harmer
40.848
970673AG2-436 GEN
Solar/Wind Harmer
27.232
970681AG2-440 GEN
Solar/Wind Harmer
9.084
970683AG2-441 GEN
Solar/Wind Harmer
11.355
970685AG2-442 GEN
Solar/Wind Harmer
12.717
970737AG2-469 GEN
Solar/Wind Harmer
9.258
970831AG2-522 GEN
Solar/Wind Harmer
7.264
970865AG2-541 GEN
Solar/Wind Harmer
4.891
970909AG2-566 GEN
Solar/Wind Harmer
1.881
970917AG2-570 GEN
Solar/Wind Harmer
16.254
970919AG2-571 GEN
Solar/Wind Harmer
6.502
970933AG2-581 GEN
Solar/Wind Harmer
14.962
970937AG2-583 GEN
Solar/Wind Harmer
11.244
971065AG2-659 GEN
Solar/Wind Harmer
7.218
971069AG2-661 GEN
Solar/Wind Harmer
3.658
971153AH1-033 GEN
Solar/Wind Harmer
2.3
971157AH1-035 GEN
Solar/Wind Harmer
2.212
971163AH1-040 GEN
Solar/Wind Harmer
14.962
971167AH1-042 GEN
Solar/Wind Harmer
18.654
971193AH1-056 GEN
Solar/Wind Harmer
10.456
971223AH1-071 GEN
Solar/Wind Harmer
2.268
971253AH1-086 GEN
50/50
24.442
971255AH1-087 GEN
50/50
5.432
971257AH1-088 GEN
50/50
5.432
971259AH1-089 GEN
50/50
5.432
971281AH1-106 GEN
Solar/Wind Harmer
2.946
971283AH1-107 GEN
Solar/Wind Harmer
2.946
971285AH1-108 GEN
Adder
1.591
971317AH1-138 GEN
Solar/Wind Harmer
1.542
971377AH1-170 GEN
Solar/Wind Harmer
1.79
971443AH1-215 GEN
Solar/Wind Harmer
2.845
971445AH1-216 GEN
Solar/Wind Harmer
14.282
971447AH1-217 GEN
Solar/Wind Harmer
5.04
971489AH1-241 GEN
Solar/Wind Harmer
8.948
971547AH1-271 GEN
Solar/Wind Harmer
3.887
971563AH1-280 GEN
Solar/Wind Harmer
1.826
971623AH1-311 GEN
Solar/Wind Harmer
0.32
971647AH1-324 GEN
Solar/Wind Harmer
8.741
971683AH1-343 GEN
Solar/Wind Harmer
5.342
971685AH1-345 GEN
Solar/Wind Harmer
2.219
219912AD2-042 GEN
Solar/Wind Helper
0.153
219919AE1-041 FULL
Solar/Wind Helper
0.004
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
316435W1029_GEN3
Solar/Wind Harmer
0.001
939181AE1-148 GEN
Solar/Wind Harmer
8.005
939411AE1-173 GEN
Solar/Wind Harmer
85.364
940641AE2-051 GEN
Solar/Wind Harmer
15.997
941031AE2-094 GEN
Solar/Wind Harmer
35.747
957411AF2-035 GEN
Solar/Wind Harmer
9.794
957481AF2-042 GEN
Solar/Wind Harmer
47.712
957521AF2-046 GEN
Solar/Wind Harmer
13.506
957861AF2-080 GEN
Solar/Wind Harmer
7.098
957871AF2-081 GEN
Solar/Wind Harmer
9.922
958211AF2-115 GEN
Solar/Wind Harmer
2.054
958261AF2-120 GEN
Solar/Wind Harmer
7.015
963711AG1-223 GEN
Solar/Wind Helper
0.065
964001AG1-254 GEN
Solar/Wind Helper
0.977
964241AG1-285 GEN
Solar/Wind Harmer
11.211
964791AG1-342 GEN
Solar/Wind Harmer
3.061
964851AG1-348 GEN
Solar/Wind Helper
0.081
965281AG1-393 GEN
Solar/Wind Harmer
2.197
965291AG1-394 GEN
Solar/Wind Harmer
0.815
966001AG1-469 GEN
Solar/Wind Harmer
0.139
966111AG1-480 GEN
Solar/Wind Helper
0.074
966131AG1-482 GEN
Solar/Wind Helper
0.138
966261AG1-495 GEN
Solar/Wind Helper
0.082
971741AH1-377 GEN
Solar/Wind Harmer
17.523
971761AH1-387 GEN
Solar/Wind Harmer
2.843
971775AH1-396 GEN
Solar/Wind Harmer
0.271
971777AH1-397 GEN
Solar/Wind Harmer
0.554
971781AH1-399 GEN
Solar/Wind Harmer
0.287
971795AH1-408 GEN
Solar/Wind Harmer
11.784
971845AH1-439 GEN
Solar/Wind Harmer
7.933
971967AH1-528 GEN
Solar/Wind Harmer
30.407
972003AH1-546 GEN
Solar/Wind Harmer
7.424
972135AH1-637 GEN
Solar/Wind Harmer
1.858
972183AH1-676 GEN
Adder
251.695
972185AH1-677 GEN
Adder
10.672
972187AH1-678 GEN
Adder
5.366
972189AH1-679 GEN
Adder
3.695
972193AH1-681 GEN
Adder
3.732
972195AH1-682 GEN
Adder
4.177
972197AH1-683 GEN
Adder
4.972
972199AH1-684 GEN
Adder
5.823
972201AH1-685 GEN
50/50
6.985
972205AH1-687 GEN
Adder
7.463
972213AH1-691 GEN
Adder
5.171
972215AH1-692 GEN
Adder
5.171
972217AH1-693 GEN
50/50
5.373
972219AH1-694 GEN
Adder
3.58
972223AH1-696 GEN
Adder
17.606
972255AH1-712 GEN
Adder
83.534
972265AH1-717 GEN
Adder
15.821
972277AH1-723 GEN
Adder
97.342
233950AC2-186 GEN
Solar/Wind Helper
0.12
233952AC2-187 GEN
Solar/Wind Helper
0.239
233954AC2-188 GEN
Solar/Wind Helper
0.239
CBM West 1LTFEXP_CBM-W1->PJM
CBM
35.101
CBM West 2LTFEXP_CBM-W2->PJM
CBM
52.117
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.667
CBM South 2LTFEXP_CBM-S2->PJM
CBM
24.867
NYPJM->LTFIMP_NY
CLTF
4.891
LGEELTFEXP_LGEE->PJM
CLTF
2.004
WECLTFEXP_WEC->PJM
CLTF
1.006
CPLELTFEXP_CPLE->PJM
CLTF
10.838
TVALTFEXP_TVA->PJM
CLTF
4.772
MECLTFEXP_MEC->PJM
CLTF
5.134
LAGNLTFEXP_LAGN->PJM
CLTF
9.398
SIGELTFEXP_SIGE->PJM
CLTF
0.16
CONTINGENCY 'DVP_P1-2: LN 2077_SRT-A'
 OPEN BRANCH FROM BUS 314080 TO BUS 314085 CKT 1   /*6REMNGTN     230.0 - 6REMNGCT     230.0
END
CONTINGENCY 'DVP_P4-2: 2077T2086_SRT-A'
 OPEN BRANCH FROM BUS 314080 TO BUS 314085 CKT 1   /*6REMNGTN     230.0 - 6REMNGCT     230.0
 OPEN BRANCH FROM BUS 314085 TO BUS 314093 CKT 2   /*6REMNGCT     230.0 - 6WARRNTN     230.0
END
CONTINGENCY 'DVP_P4-2: 207762_SRT-S'
 OPEN BRANCH FROM BUS 314080 TO BUS 314085 CKT 1                /*6REMNGTN     230.0 - 6REMNGCT     230.0
 OPEN BRANCH FROM BUS 314085 TO BUS 315021 CKT 1                /*6REMNGCT     230.0 - 1REMNGT1      18.0
 OPEN BRANCH FROM BUS 314085 TO BUS 315022 CKT 1                /*6REMNGCT     230.0 - 1REMNGT2      18.0
 OPEN BUS 315021                                                /*1REMNGT1      18.0
 OPEN BUS 315022                                                /*1REMNGT2      18.0
 SET POSTCONTRATING 1302 BRANCH FROM BUS 314085 TO BUS 314110 CKT 1 /*6REMNGCT     230.0 - 6ELK RUN     230.0
 SET PRECONTRATING 1174 BRANCH FROM BUS 314085 TO BUS 314110 CKT 1 /*6REMNGCT     230.0 - 6ELK RUN     230.0
END
CONTINGENCY 'DVP_P1-2: LN 9344_SRT-A'
 OPEN BRANCH FROM BUS 313393 TO BUS 313905 CKT 1   /*8MARS        500.0 - 8WSHNGSTAR   500.0
END
314099 to 314085 ckt 1
314933 to 972284 ckt 1

Winter Peak Analysis

The New Service Request AH1-086 was evaluated as a 90.0 MW (90.0 MW Capacity) injection in the Dominion area.

AH1-086 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 90.0 MW (90.0 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

(No impacts were found for this analysis)

Light Load Analysis

The New Service Request AH1-086 was evaluated as a 90.0 MW injection and 90.0 MW withdrawal in the Dominion area.

AH1-086 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 90.0 MW (90.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

(No impacts were found for this analysis)

Short Circuit Analysis

Short Circuit analysis is not performed as part of the Phase I System Impact Study. Short Circuit analysis will commence in the Phase II System Impact Study.

Stability Analysis

Stability analysis is not performed as part of the Phase I System Impact Study. Stability analysis will commence in the Phase II System Impact Study.

Reactive Power Analysis

Reactive Power analysis is not performed as part of the Phase I System Impact Study. Reactive Power analysis will commence in the Phase II System Impact Study.

Steady-State Voltage Analysis

Steady State Voltage Analysis is Not Required.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-038Lexington-Low Moor 230kVUnder Construction
AA1-050Tarboro-Everetts 230kVIn Service
AA1-063ACarolina–Seaboard 115kVIn Service
AA1-067Everetts 34.5kVIn Service
AA1-095Halfway-Marlowe 34.5kVIn Service
AA1-139Hickory-Shawboro 230kVIn Service
AA2-053Carolina-Jackson 115kVIn Service
AA2-057Hornertown-Whitakers 115kVIn Service
AA2-174Carolina-Jackson 115kVIn Service
AA2-178Mackeys 230kVIn Service
AA2-184Atlantic-Red Bank 34kVIn Service
AB1-001Absecon 12 kVIn Service
AB1-027Old Church 34.5 KVIn Service
AB1-081Anaconda-Mayo Dunbar 115kVIn Service
AB1-096Carroll-Mt. Airy 34.5kVIn Service
AB1-124Carroll-Monocacy 34.5kVPartially in Service - Under Construction
AB1-125Carroll-Monocacy 34.5kVIn Service
AB1-127St. Thomas-Guilford 34.5kVIn Service
AB1-128St. Thomas-Mercersburg 34.5kVIn Service
AB1-132Thelma 230kVIn Service
AB1-138Navy 34.5kVIn Service
AB1-139Metuchen 26kVIn Service
AB1-141Church-Wye Mills 138 kV IIn Service
AB1-142Church-Wye Mills 138 kV IIIn Service
AB1-176Price 25kV IIEngineering & Procurement
AB2-022Elizabeth City 34.5kVIn Service
AB2-024Correctional 34.5kVIn Service
AB2-025Sapony 34.5kVIn Service
AB2-026Powhatan 34.5kVIn Service
AB2-029Remington 34.5kVIn Service
AB2-031Brink-Trego 115kVIn Service
AB2-032Church-Wye Mills 138 kVIn Service
AB2-037Keeney-Steele 230kVUnder Construction
AB2-040Brink 115kVIn Service
AB2-043Chase City 115kVIn Service
AB2-045Buckingham 34.5kVIn Service
AB2-049Gloucester Township 12kVIn Service
AB2-059Benson-Dunbar 115kVIn Service
AB2-060Chase City-Lunenburg 115kVIn Service
AB2-077Buggs Island-Chase City 115kVIn Service
AB2-078Buggs Island-Chase City 115kVIn Service
AB2-079Buggs Island-Chase City 115kVIn Service
AB2-099Ahoskie 34.5kVIn Service
AB2-133Chestertown 69kVUnder Construction
AB2-134Hopewell-Surry 230kVIn Service
AB2-135Church-Kent 69kVIn Service
AB2-136Cambridge-West Cambridge 69kVUnder Construction
AB2-153Church-Wye Mills 138 kVIn Service
AB2-158Louisa-South Anna 230kVIn Service
AB2-161Waverly #2 DP 115kVIn Service
AB2-169Pantago-Five Points 115kVIn Service
AB2-174Emporia-Trego 115kVIn Service
AB2-179Townsend 138kVIn Service
AB2-190Hopewell-Surry 230kVIn Service
AC1-010Gloucester 26kVUnder Construction
AC1-017Levittown 13 kVIn Service
AC1-027Pendleton 34.5kVIn Service
AC1-030Cinnaminson 13kVIn Service
AC1-034Heartsease DP - Mayo Dunbar 115kVSuspended
AC1-036Twittys Creek 34.5kVIn Service
AC1-054Kerr Dam–Eatons Ferry 115 kVIn Service
AC1-075Perth-Hickory Grove 115kVIn Service
AC1-076Locust Grove-Paytes 115kVIn Service
AC1-086Thelma 230kVSuspended
AC1-091Cedar Creek 138kV IEngineering & Procurement
AC1-092Cedar Creek 138kV IIEngineering & Procurement
AC1-093Cedar Creek 138kV IIIEngineering & Procurement
AC1-094Cedar Creek 138kV IVEngineering & Procurement
AC1-098Dawson-South Justice 115kVPartially in Service - Under Construction
AC1-099Dawson-South Justice 115kVPartially in Service - Under Construction
AC1-105Halifax-Mt. Laurel 115kVIn Service
AC1-118Westmoreland 34.5kVIn Service
AC1-120Mitchell-Mountain Run 115kVEngineering & Procurement
AC1-121Mitchell-Mountain Run 115kVEngineering & Procurement
AC1-147Grassfield 34.5kVIn Service
AC1-158Spotsylvania 500kVIn Service
AC1-161Septa 500kVIn Service
AC1-164Chickahominy 230kVPartially in Service - Under Construction
AC1-189Chinquapin-Everetts 230kVUnder Construction
AC1-191Elmont 115kVEngineering & Procurement
AC1-208Cox-Whitakers 115kVUnder Construction
AC1-221Halifax-Person 230kVIn Service
AC1-222Crystal Hill-Halifax 115kVIn Service
AC2-012Grassfield-Great Bridge 115kVIn Service
AC2-023Hebron 69kVEngineering & Procurement
AC2-079Ivor-Oak Ridge 115kVSuspended
AC2-100Halifax-Person 230kVIn Service
AC2-136East Hagerstown 12kVUnder Construction
AC2-137Elko 34.5kVIn Service
AC2-138Northern Neck 34.5kVIn Service
AC2-141Septa 500kVEngineering & Procurement
AC2-165Bremo-Powhatan 230kVSuspended
AC2-186Harrington 25kVUnder Construction
AC2-187Harrington 69kVUnder Construction
AC2-188Harrington 69 kVUnder Construction
AD1-020Hunterstown-Lincoln 115 kVIn Service
AD1-022Cashie-Trowbridge 230 kVEngineering & Procurement
AD1-025Hopewell-Surry 230 kVUnder Construction
AD1-033Fentress-Landstown 230 kVIn Service
AD1-041Harmony Village-Shackleford 115 kVIn Service
AD1-056Hornertown-Hathaway 230 kVSuspended
AD1-057Hornertown-Hathaway 230 kVSuspended
AD1-060Mercersburg-Milnor 34.5 kVIn Service
AD1-061McConnelsburg-Mercersburg 34 kVIn Service
AD1-063Harmony Village 34.5 kVIn Service
AD1-074Trowbridge 230 kVEngineering & Procurement
AD1-075Trowbridge 230 kVEngineering & Procurement
AD1-076Trowbridge 230 kVEngineering & Procurement
AD1-082Bakers Pond-Ivor 115kVIn Service
AD1-087Clover-Sedge Hill 230 kVIn Service
AD1-088Briery-Clover 230 kVSuspended
AD1-105Kings Dominion DP 115 kVUnder Construction
AD1-115Mountain Run-Mitchell 115 kVEngineering & Procurement
AD1-144Kings Fork 34.5 kVIn Service
AD1-151Hopewell-Surry 230 kVSuspended
AD1-152Clover-Sedge Hill 230 kVIn Service
AD1-155Meadow Brook-Strasburg 138 kVIn Service
AD2-009McConnellsburg 138 kVIn Service
AD2-027Camden Switch 26 kVIn Service
AD2-030Wan 34.5 kVIn Service
AD2-033Chase City-Lunenburg 115 kVUnder Construction
AD2-042Camden Switch 26 kV IIIn Service
AD2-065Atco 12 kVIn Service
AD2-070Gilbert-Morris Park 34.5kVIn Service
AD2-073Sanders DP 230 kVIn Service
AD2-085Myrtle-Windsor DP 115kVEngineering & Procurement
AD2-115Lyons-Moselem 69kVIn Service
AD2-116Hokes-Grantley 69 kVIn Service
AD2-135Williamstown 12kVPartially in Service - Under Construction
AD2-160Hickory-Moyock 230kVIn Service
AD2-202Clover-Sedge Hill 230kVIn Service
AE1-041Edison 4kVIn Service
AE1-056Red House-South Creek 115 kVWithdrawn
AE1-071Shade Gap-Roxbury 115 kVIn Service
AE1-072Shawboro-Sligo 230 kVUnder Construction
AE1-074Winterpock 34.5 kVUnder Construction
AE1-075Powhatan 34.5 kVIn Service
AE1-081Landing 12.47 kVIn Service
AE1-101McConnellsburg-Texas Eastern 138 kVIn Service
AE1-103Holland-Union Camp 115 kVUnder Construction
AE1-108Bremo-Scottsville 138 kVEngineering & Procurement
AE1-142Manitou-Pleasant Plains 34.5 kVIn Service
AE1-148Kerr Dam-Ridge Rd 115 kVActive
AE1-149Disputanta-Poe 115 kVSuspended
AE1-153Remington-Gordonsville 230 kVSuspended
AE1-155Garner-Northern Neck 115 kVIn Service
AE1-156Quakertown Solar II 34.5 kVPartially in Service - Under Construction
AE1-157Ladysmith CT-St. Johns 230 kVSuspended
AE1-162Smithfield 34.5 kVIn Service
AE1-173Carson-Suffolk 500 kVUnder Construction
AE1-175Light Foot 34.5 kVIn Service
AE1-185Hokes-Jackson 69 kVIn Service
AE1-190Harmony Village-Shackleford 115 kVPartially in Service - Under Construction
AE1-191Harmony Village-Shackleford 115 kVPartially in Service - Under Construction
AE1-196Hokes-Jackson 69 kV IIIn Service
AE1-229Deepwater-Upper Pittsgrove 138 kVSuspended
AE2-005Harmony Village-Shackleford 115 kVUnder Construction
AE2-027Harrowgate-Locks 115kVUnder Construction
AE2-033Clubhouse-Sapony 230 kVSuspended
AE2-034Mackeys 230 kVPartially in Service - Under Construction
AE2-051Carson-Septa 500 kVEngineering & Procurement
AE2-054Warfordsburg 34 kVIn Service
AE2-092Kidds Store-Sherwood 115 kVEngineering & Procurement
AE2-094Carson-Rogers Road 500 kVEngineering & Procurement
AE2-104Suffolk 115 kVSuspended
AE2-175Jackson-Long Pond 69 kVPartially in Service - Under Construction
AE2-212Harrowgate 34 kVEngineering & Procurement
AE2-253Hickory-Moyock 230 kVIn Service
AE2-259Curdsville-Willis Mtn 115 kVEngineering & Procurement
AE2-291Grit DP-Perth 115 kVActive
AE2-346Ahoskie 34.5 kVIn Service
AF1-007Indian River 230 kV ISuspended
AF1-017Myrtle-Windsor 115 kVEngineering & Procurement
AF1-032Suffolk 34.5 kVIn Service
AF1-058Welco 34.5 kVIn Service
AF1-069Carson-Rogers Rd 500 kVEngineering & Procurement
AF1-075Harrisburg-Endless Caverns 230 kVSuspended
AF1-114Oak Grove-Dahlgren 230 kVEngineering & Procurement
AF1-123Harper 230 kVActive
AF1-124Harper 230 kVActive
AF1-125Harper 230 kVActive
AF1-128Chesterfield 230 kVActive
AF1-129Chesterfield 230 kVEngineering & Procurement
AF1-136Warfordsburg-Purcell Junction 34.5 kVEngineering & Procurement
AF1-254Milnor-Huyetts 34.5 kVUnder Construction
AF1-262Upper Pittsgrove 12 kVIn Service
AF1-264Runnemede 13 kVIn Service
AF1-291Tyler 34.5 kVEngineering & Procurement
AF1-294Jetersville-Ponton 115 kVActive
AF1-320Merrill Creek 115 kVEngineering & Procurement
AF2-035St. Johns 115 kVActive
AF2-042Clover-Rawlings 500 kVActive
AF2-043Suffolk 34.5 kVIn Service
AF2-046Tunis-Mapleton 115 kVActive
AF2-080Chinquapin-Everetts 230 kVActive
AF2-081Moyock 230 kVActive
AF2-110Suffolk 115 kVSuspended
AF2-115Jetersville-Ponton 115 kVActive
AF2-120Garner-Northern Neck 115 kVActive
AF2-138Flanders-West Wharton 34.5 kVIn Service
AF2-139Gilbert-Warren Glen 34.5 kVIn Service
AF2-144Powhatan 34.5 kVIn Service
AF2-192Frenchtown Solar-West Flemington 34.5 kVSuspended
AF2-222Madisonville DP-Twitty's Creek 115 kVActive
AF2-229Roxbury 23 kVEngineering & Procurement
AF2-247Bustleton 13.2 kVIn Service
AF2-250Edgewood 12 kV IIIIn Service
AF2-297Sedge Hill 115 kVActive
AF2-299Fields 34.5 kVActive
AF2-325Jacktown 12 kVEngineering & Procurement
AF2-354Washington 34.5 kV IIEngineering & Procurement
AF2-378Cambridge 12 kVEngineering & Procurement
AF2-379Princess Anne 25 kVUnder Construction
AF2-383Tolna 115 kVWithdrawn
AG1-007Tar River 12.5 kVEngineering & Procurement
AG1-008Tunis-Mapleton 115 kVActive
AG1-021Jetersville-Ponton 115 kVActive
AG1-082Ahoskie 34.5 kVActive
AG1-098Briery-Clover 230 kVActive
AG1-105Mount Laurel-Barnes Junction 115 kVActive
AG1-106Thelma 230 kVActive
AG1-135Garner-Lancaster 115 kVActive
AG1-145Lightfoot 34.5 kVIn Service
AG1-146Garner DP-Lancaster 115 kVActive
AG1-147Garner DP-Lancaster 115 kVActive
AG1-166Lone Pine 115 kVActive
AG1-167Lone Pine 115 kVActive
AG1-168Lone Pine 115 kVActive
AG1-188Manitou-Oyster Creek 34.5 kVEngineering & Procurement
AG1-189Oyster Creek-Bamber Lake 34.5Engineering & Procurement
AG1-191Chester-Pohatcong Mountain 34.5 kVPartially in Service - Under Construction
AG1-223Larrabee-Allaire 34.5 kVUnder Construction
AG1-254Salem-Woodstown 69 kVEngineering & Procurement
AG1-285Chase City-Central 115 kVActive
AG1-342Dryburg 115 kVActive
AG1-348Pequest River-Washington 34.5 kVIn Service
AG1-393Sapony 34.5 kVActive
AG1-394Boykins 34.5 kVActive
AG1-397Walston 12 kVWithdrawn
AG1-469Gordonsville 34.5 kVEngineering & Procurement
AG1-480Shawnee 34.5 kVEngineering & Procurement
AG1-482Hamilton 115 kVWithdrawn
AG1-495Gilbert-Rocktown 34.5 kVEngineering & Procurement
AG1-499Lambs 12.47 kVUnder Construction
AG1-551Parmele 34.5 kVActive
AG1-552Carolina 34.5 kVActive
AG1-558Buckner 34.5 kVEngineering & Procurement
AG1-559Caroline Pines 22 kVEngineering & Procurement
AG2-005Garner DP-Lancaster 115 kVActive
AG2-049Van Dorn 34.5 kVActive
AG2-068Heritage - Wake 500 kVActive
AG2-069Heritage - Wake 500 kVActive
AG2-077Clover-Rawlings 500 kVActive
AG2-086Mt. Jackson DP-Mt. Jackson 115 kVActive
AG2-093Colonial Trail-Hopewell 230 kVActive
AG2-095Hopewell 34.5 kV (Circuit 313)Active
AG2-111Perth 34.5 kV Substation (Circuit 408)Active
AG2-112Perth 34.5 kV Substation (Circuit 404)Active
AG2-120Everetts 34.5 kVActive
AG2-124Shackleford-Harmony 115 kVActive
AG2-151Trices Lake - James River Tap 115 kVActive
AG2-171Lunenburg-Nutbush 115 kVActive
AG2-188Farmville - Buckingham 230 kVActive
AG2-193Turner 34.5 kVActive
AG2-198Briery - Finneywood 230 kVActive
AG2-208Greenwood DP - St. Johns DP 115 kVActive
AG2-213Gary D.P Tap - Gary D.P 115 kVActive
AG2-215Garner DP-Lancaster 115 kVActive
AG2-262Dryburg 115 kVActive
AG2-369Heritage - Wake 500 kVActive
AG2-382Cashie 230 kVActive
AG2-426Wakefield - Waverly 115 kVActive
AG2-427Waverly 115 kVActive
AG2-428Wakefield 115 kVActive
AG2-436Carson - Rogers Road 500 kVActive
AG2-440Twittys Creek - Madisonville 115 kVActive
AG2-441Twittys Creek - Madisonville 115 kVActive
AG2-442Twittys Creek - Madisonville 115 kVActive
AG2-469Westmoreland – Oak Grove 230 kVActive
AG2-522Five Forks DP 115 kVActive
AG2-541Perth - Crystal Hill 115 kVActive
AG2-566Briery - Finneywood 230 kVActive
AG2-570Heritage - Wake 500 kVActive
AG2-571Heritage - Wake 500 kVActive
AG2-581Rawlings-Clover 500 kVActive
AG2-583Bremo - Cartersville 230 kVActive
AG2-659Kerr Dam – Hawtree 115 kVActive
AG2-661Hopewell - Colonial Trail 230 kVActive
AH1-033Sligo 34.5 kVActive
AH1-035Plymouth 34.5 kVActive
AH1-040Mackeys - Creswell 115 kVActive
AH1-042Providence Forge-Turner 115kVActive
AH1-056Red House DP 115kVActive
AH1-071Midlothian 34.5 kVActive
AH1-087Morrisville 230kVActive
AH1-088Morrisville 230kVActive
AH1-089Morrisville 230kVActive
AH1-106Winterpock 34.5kVActive
AH1-107Winterpock 34.5kVActive
AH1-108Spruance NUG 230 kVActive
AH1-138Penniman 34.5 kVActive
AH1-170Columbia DP 115kVActive
AH1-215Central VA-Twitty 115 kVActive
AH1-216Smithfield-Surry 230 kVActive
AH1-217Kidds Store - Fork Union 115 kV IIActive
AH1-241Cobbs Creek - James River Industrial 115kVActive
AH1-271Cashie 230 kVActive
AH1-280Jetersville-Ponton 115 kVActive
AH1-311Heartsease DP - Mayo Dunbar 115kVActive
AH1-324Colonial Trail – Surry 230 kVActive
AH1-343Crystal Hill DP- Perth 115kVActive
AH1-345Remington 324 34.5 kVActive
AH1-377Clover- Farmville 230kVActive
AH1-387Meadowbrook-Greenland Gap 500kVActive
AH1-396Gary 24.94 kVActive
AH1-397Shacklesford 34.5 kVActive
AH1-399North Doswell 12.5 kVActive
AH1-408Freeman DP – Lawrenceville 115 kVActive
AH1-439Buckingham- Farmville 230kVActive
AH1-528Rawlings - Unity 500 kVActive
AH1-546Bremo - Buckingham 230 kVActive
AH1-637Oak Grove 34.5 kVActive
AH1-676Gordonsville 230 kVActive
AH1-677Rogers Road 500 kVActive
AH1-678Heritage 500 kVActive
AH1-679Four Rivers 230 kVActive
AH1-681Cunningham 500 kVActive
AH1-682Ladysmith CT 230 kVActive
AH1-683Ladysmith CT 230 kVActive
AH1-684Remington CT 230 kVActive
AH1-685Remington CT 230 kVActive
AH1-687Bear Garden 230kVActive
AH1-691Ladysmith CT 230 kVActive
AH1-692Ladysmith CT 230 kVActive
AH1-693Remington CT 230 kVActive
AH1-694Ladysmith CT 230 kVActive
AH1-696Possum Point 230kVActive
AH1-712Cunningham 500 kVActive
AH1-717Surry 230kVActive
AH1-723Cunningham 500 kVActive
V4-067Cates Road Egg Harbor Township 12kVDeactivated
W1-003Oak HallIn Service
W1-004Oak HallIn Service
W1-005Oak HallIn Service
W1-006Oak HallIn Service
W1-130Vine Road 12kVIn Service
W2-030Egg Harbor TownshipIn Service
W3-077Broadway-Stewartsville 34.5kVIn Service
X3-066Church Hill 69kVIn Service
Y1-079Wye Mills 69kVIn Service
Y1-080Dorchester 12kVIn Service
Y1-086Morgans CornerIn Service
Y3-058Rockawalkin 69kVIn Service
Z1-036WinFall-Chowan 230kVIn Service
Z2-027Pasquotank 34.5kVIn Service
Z2-044Whitakers 34.5kVIn Service
Z2-076Worcester South 25kVIn Service
Z2-077Worcester North 25kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with potential Affected System impacts. PJM initiates coordination with each Affected System Operator by providing a list of New Service Requests in the Cycle with potential impacts to their respective system. If the Affected System Operator indicates an Affected System Study is required, PJM will notify the Project Developer or Eligible Customer of the need for an Affected System Study. See below if any Affected System Operator requires a study for this project:

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

No cost allocated system reinforcements were identified for this project in the Phase I System Impact Study load flow analysis.

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement: b4000.300
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.300
Title
Rebuild approximately 1.71 miles of 230kV line 299 from the Marsh Run substation to the Remington CT substation. New conductor has a summer rating of 1573 MVA.
Description
Rebuild approximately 1.71 miles of 230kV line 299 from the Marsh Run substation to the Remington CT substation. New conductor has a summer rating of 1573 MVA.
Cost Information
Time Estimate
May 30 2029

Contingent

Note: Although AH1-086 may not presently have cost responsibility for this upgrade, AH1-086 may need this upgrade in-service to be deliverable to the PJM system. If AH1-086 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6REMNGCT-6GI1MRUN 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.303
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.303
Title
Uprate line #299 terminal equipment, line leads, and bus at Remington CT substation to be rated to 4000A.
Description
Uprate line #299 terminal equipment, line leads, and bus at Remington CT substation to be rated to 4000A.
Cost Information
Time Estimate
May 30 2029

Contingent

Note: Although AH1-086 may not presently have cost responsibility for this upgrade, AH1-086 may need this upgrade in-service to be deliverable to the PJM system. If AH1-086 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6REMNGCT-6GI1MRUN 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.343
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.343
Title
Uprate bus at Brambleton to support 500kV Line #558 (Aspen to Brambleton) uprate.
Description
Uprate bus at Brambleton to support 500kV Line #558 (Aspen to Brambleton) uprate.
Cost Information
Time Estimate
Nov 28 2025

Not Contingent

Note: AH1-086 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-086 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8BRAMBLETON-AH1-727 TP 500.0 kV Ckt 1 line(Any)

Attachments

AH1-086 One Line Diagram

AH1-086 One Line Diagram.pdf
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.