AH1-164 Phase I Study Report

v1.00 released 2025-10-29 20:44

Oak Level - Tank Hill 138 kV

21.0 MW Capacity / 35.0 MW Energy

Introduction

This Phase I System Impact Study Report (PH1) has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, sections 307 and 308 for New Service Requests (projects) in Transition Cycle 2. The Project Developer/Eligible Customer (developer) is Robin Ridge Solar, LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is American Electric Power.

Preface

The Phase I System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle executive summary format and (ii) an individual project-level basis. The Phase I System Impact Study Results (for both the executive summary and individual reports) will be publicly available on PJM’s website. Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.3, PJM takes the following actions during the Phase I System Impact Study:
  1. PJM studies each New Service Request on a summer peak, winter peak and light load RTEP base case study. The case year is dependent on the new services cycle under study. PJM will identify the base case year to be used in the study of a specific cycle on its website.
  2. PJM will only perform load flow analysis during the Phase I System Impact Study.
  3. In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with Affected System impacts and provides each Affected System Operator with a list of New Service Request in the Cycle with potential impacts to their respective system.
  4. PJM will create both the short circuit and stability base cases to be used in the Phase II System Impact Study.
  5. The Phase I System Impact Study results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.
The Transmission Owner takes the following actions during the Phase I System Impact Study:
  1. Identify required Interconnection Facilities to accommodate the New Service Request.
  2. Identify required Network Upgrades to mitigate system violations from the Phase I System Impact Study.
  3. Provide planning-level preliminary estimates of Interconnection Facilities and Network Upgrades including scope, cost and elapsed time to complete the work.

Decision Point I Requirements

At the close of Phase I System Impact Study, PJM will initiate Decision Point I (DP1). During DP1, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.A.1. Additional information on these elements is available in PJM Manual 14H sections 4.4, 6, and 7.

Allowable project modifications at Decision Point I are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

General

The Project Developer has proposed a Solar generating facility located in the American Electric Power zone — Franklin County, Virginia. The installed facilities will have a total capability of 35.0 MW with 21.0 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AH1-164
Project Name:
Oak Level - Tank Hill 138 kV
Project Developer Name:
Robin Ridge Solar, LLC
State:
Virginia
County:
Franklin
Transmission Owner:
American Electric Power
MFO:
35.0
MWE:
35.0
MWC:
21.0
Fuel Type:
Solar
Basecase Study Year:
2028

Physical Interconnection Facility Study

Physical Interconnection Facilities Study is not performed as part of the Phase I System Impact Study. Physical Interconnection Facilities Study will commence in the Phase II System Impact Study.

Point of Interconnection

AH1-164 will interconnect on the American Electric Power  transmission system by tapping the Oak Level - Tank Hill 138 kV line.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In the Phase I SIS, the costs shown are subject to change as a result of a facility study performed by the TO during the Phase II or Phase III System Impact Study.

Based on the Phase I SIS results, the AH1-164 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit are also shown below.

Cost Summary
DescriptionCost Allocated to AH1-164Cost Subject to Readiness*
Transmission Owner Interconnection Facilities (TOIF)$0$0
Other Scope$0$0
Option To Build Oversight$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$18,056,079$18,056,079
Network Upgrades$0$0
System Reliability Network Upgrades
Steady State Thermal & Voltage (SP & LL)$0$0
Transient Stability$0$0
Short Circuit$0$0
Transmission Owner Analysis
SubRegional$0$0
Distribution$0$0
Affected System Reinforcements
AFS - PJM Violatons$0$0
AFS - Non-PJM Violations$0$0
Total$18,056,079$18,056,079

* Contributes to calculation for Readiness Deposit #2 (RD2). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim deliverability study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 309 (Decision Point I) A.1.a.i and PJM Manual 14H, section 6.2, Readiness Deposit #2 (RD2) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point I (DP1), the Project Developer or Eligible Customer is required to submit Readiness Deposit #2, which is calculated as 10% of cost allocation for required Phase I Network Upgrades minus Readiness Deposit #1.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Readiness Deposit #2 Due for Project AH1-164

Readiness Deposit #2 has been calculated for the project based on the Phase I System Impact Study results and is shown in the table below. This Readiness Deposit #2 must be provided at Decision Point I through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit
Project ID10% of cost allocation for Phase I Network UpgradesReadiness Deposit #1 Received (RD1)Readiness Deposit #2 (RD2) for AH1-164 Project due at DP1
ABA - B
AH1-164$1,805,608$140,000$1,665,608

Note: Failure to provide an acceptable form of Readiness Deposit #2 by the end of Decision Point I will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Stand-Alone Network Upgrades
RTEP IDDescriptionTotal Cost ($USD)Allocated Cost ($USD)
(Pending)AEP will construct a new breaker and a half station, initially populated with 3 breakers and operated as a ring bus as well as the associated facilities required to support the interconnection.$18,056,079 $18,056,079

Based on the scope of work for the Interconnection Facilities, it is expected to take a range of 24 to 30 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

The schedule for any required Network Impact Reinforcements will be more clearly identified in the Phase II and Phase III System Impact Studies.

Transmission Owner Analysis

No Transmission Owner impacts identified.

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. AEP interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Meteorological Data Reporting Requirement
The solar generation facility shall provide the Transmission Provider with site-specific meteorological data including:
  • Temperature (degrees Fahrenheit)
  • Atmospheric Pressure (hectopascals)
  • Irradiance
  • Forced outage data
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AH1-164 was evaluated as a 35.0 MW (21.0 MW Capacity) injection in the AEP area.

AH1-164 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 35.0 MW (35.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AP_P1-3_MP-765-501T_SRT-A
SingleAC121.06 %3393.4B4107.974.89
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AP_P2-3_MP-500-020_SRT-SL
BreakerAC117.02 %3610.0B4224.557.01
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AP_P2-3_MP-500-021_SRT-SL
BreakerAC116.77 %3610.0B4215.437.01
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AEP_P4_#37_05MOUNTN 765_B1_SRT-A
BreakerAC116.68 %3610.0B4211.987.0
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AEP_P4_#2942_05KAMMER 765_PP_SRT-A
BreakerAC116.36 %3610.0B4200.437.0
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P4_#7445_05MARYSV 765_B_SRT-A
BreakerAC113.05 %5523.0B6243.533.99
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Base Case
SingleAC108.86 %4558.0A4961.852.34
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A
BreakerAC108.47 %5523.0B5991.025.07
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P1-2_#7422_16_SRT-A
SingleAC106.56 %5523.0B5885.343.54
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P7-1_#10944___SRT-A
TowerAC106.16 %5523.0B5863.473.82
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P7-1_#10856___SRT-A
TowerAC102.19 %5523.0B5644.143.87
GD2DVP
6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line
DVP_P4-2: 509T570_SRT-A
BreakerAC114.83 %997.0C1144.91.91
GD2DVP
6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line
DVP_P1-2: LN 570_SRT-A-3
SingleAC108.64 %814.98B885.411.35
GD2DVP
6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line
DVP_P1-2: LN 570_SRT-A-2
SingleAC106.47 %814.98B867.671.35
GD2DVP
6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line
DVP_P4-2: 57062_SRT-S
BreakerAC100.2 %997.0C998.971.94
GD2CPLE/DVP
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P1-2: LN 570_SRT-A-3
SingleAC182.88 %508.54B930.031.21
GD2CPLE/DVP
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P1-2: LN 570_SRT-A-2
SingleAC178.67 %508.54B908.591.21
GD2DVP
6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line
DVP_P4-2: 509T570_SRT-A
BreakerAC109.79 %997.0C1094.571.92
GD2DVP
6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line
DVP_P1-2: LN 570_SRT-A-3
SingleAC103.53 %814.98B843.751.36
GD2DVP
6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line
DVP_P1-2: LN 570_SRT-A-2
SingleAC101.35 %814.98B825.971.36
GD2DVP
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line
DVP_P1-2: LN 555_SRT-A
SingleAC112.33 %3220.44B3617.393.33
GD2DVP
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line
DVP_P7-1: LN 2168-555_SRT-A
TowerAC105.49 %3940.0C4156.45.35
GD2DVP
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-S
SingleAC173.01 %4070.2B7041.782.4
GD2DVP
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S
SingleAC153.9 %4070.2B6264.02.1
GD2DVP
8VALLEY SC-8VALLEY 500.0 kV Ckt 1 line
DVP_P1-2: LN 555_SRT-A
SingleAC112.01 %3220.44B3607.133.33
GD2DVP
8VALLEY SC-8VALLEY 500.0 kV Ckt 1 line
DVP_P7-1: LN 2168-555_SRT-A
TowerAC105.23 %3940.0C4145.885.35

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AP_P1-3_MP-765-501T_SRT-A


Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-501T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:121.06 %
Rating:3393.4 MVA
Rating Type:B
MVA to Mitigate:4107.97
MW Contribution:4.89
Bus #Bus NameTypeMW Contribution
970479AG2-310 GEN
50/50
20.255
270205AE1-176
50/50
0.006
966251AG1-494 GEN
50/50
4.388
24728405LEESVG
50/50
0.297
971367AH1-164 GEN
Solar/Wind Harmer
4.886
941821AE2-187 GEN
Solar/Wind Harmer
7.452
270197AD1-017 GEN1
Solar/Wind Harmer
1.429
270336AE1-100 GEN
Solar/Wind Harmer
0.006
943811AF1-049 GEN
Solar/Wind Harmer
-0.002
24735205WLF2G2
Adder
8.023
24723205RIVRG3
Adder
22.954
24686105CER G3
Adder
9.887
24721705FLATG2
Adder
21.686
970947AG2-589 GEN
Solar/Wind Harmer
0.249
971821AH1-427 GEN
Solar/Wind Harmer
7.218
964901AG1-354 GEN
Solar/Wind Harmer
10.814
945681AF1-233 GEN
Solar/Wind Harmer
12.782
270445AC2-157 GEN2
Solar/Wind Harmer
0.003
25194608D.CRK4
Adder
1.508
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.331
24728605AND G2
Adder
3.48
274877BISHOP HL;1U
Solar/Wind Harmer
0.208
970613AG2-401 GEN
Solar/Wind Harmer
4.519
957471AF2-041 GEN
Solar/Wind Harmer
18.409
970291AG2-192 GEN
Solar/Wind Harmer
0.796
965031AG1-367 GEN
Solar/Wind Harmer
6.111
276901AD2-066 C O1
Solar/Wind Harmer
0.006
274828WAUKEGAN ;BP
Adder
9.655
274682WAUKEGAN ;7U
Adder
15.703
274745AC1-111 GEN9
Adder
4.87
316499AE2-029_GEN
Solar/Wind Helper
1.725
316095T157 G97
Solar/Wind Helper
1.125
966881AG1-559 GEN
Solar/Wind Helper
0.313
316473AC1-191 GEN
Solar/Wind Helper
1.387
970481AG2-311 GEN
50/50
11.937
24728405LEESVG
50/50
0.295
943031AE2-326 GEN
Solar/Wind Harmer
6.784
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
3147123OTTER R
Solar/Wind Harmer
0.13
270030AE2-140 GEN
Solar/Wind Harmer
21.578
960911AF2-382 GEN
Solar/Wind Harmer
7.638
972103AH1-617 GEN
Solar/Wind Harmer
18.024
24721905FLATG4
Adder
21.686
971155AH1-034 GEN
Solar/Wind Harmer
8.427
960741AF2-365 GEN
Solar/Wind Harmer
3.563
25194608D.CRK4
Adder
1.508
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
8.231
24728505AND G1
Adder
3.48
276668AB2-070 GEN1
Solar/Wind Harmer
0.229
274767LEE CO EC;8U
Adder
8.125
24755605MDL-5G
Solar/Wind Harmer
0.001
959091AF2-200 GEN
Solar/Wind Harmer
12.273
247642Z2-115 C
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
0.673
970291AG2-192 GEN
Solar/Wind Harmer
0.612
274682WAUKEGAN ;7U
Adder
15.703
946031AF1-268 GEN
Solar/Wind Harmer
5.79
943121AE2-341 GEN
Solar/Wind Harmer
10.192
943591AF1-030 GEN
Solar/Wind Harmer
6.778
316192AB2-158 GEN
Solar/Wind Helper
1.838
316097T157 G90
Solar/Wind Helper
1.125
316336AC2-165 C
Solar/Wind Helper
1.285
24684705SMG5
50/50
0.856
3151561HALLBR1
50/50
0.57
270173AC1-122 GEN
Solar/Wind Harmer
0.677
941801AE2-185 GEN
Solar/Wind Harmer
7.452
970913AG2-568 GEN
Solar/Wind Harmer
7.677
270053AF1-130 C
Solar/Wind Harmer
2.047
24686405CER G5
Adder
9.796
970273AG2-179 GEN
Solar/Wind Harmer
4.425
339250AF1-203 GEN
Solar/Wind Harmer
0.001
962251AG1-071 GEN
Solar/Wind Harmer
4.496
276686W4-005 GEN3
Solar/Wind Harmer
0.001
270356AE2-297 GEN
Solar/Wind Harmer
0.008
270222AC2-111 GEN
Solar/Wind Harmer
3.158
24734805WLF1G4
Adder
8.194
24735105WLF2G1
Adder
8.023
270400AC1-102 GEN
Solar/Wind Harmer
2.892
941621AE2-160 GEN
Adder
4.285
957241AF2-018 GEN
Solar/Wind Harmer
-0.002
24477305BRIDGE
Adder
0.419
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
3429211JKCT 2G
Adder
11.873
970455AG2-298 GEN
Solar/Wind Harmer
4.677
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
972163AH1-664 GEN
Solar/Wind Harmer
7.568
944221AF1-090 GEN
Solar/Wind Harmer
3.754
25196508WSDLE4
Adder
7.769
963841AG1-237 GEN
Solar/Wind Harmer
2.698
270340AC2-060 GEN
Solar/Wind Harmer
0.007
276655WTG1_EQ
Solar/Wind Harmer
0.002
24386205FR-12G C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
926823AC1-168 GEN
Solar/Wind Harmer
1.045
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24697905MDL-4G C
Solar/Wind Harmer
0.001
276882AE2-255 GEN
Solar/Wind Harmer
0.715
970115AG2-085 GEN
Solar/Wind Harmer
2.442
274746AC1-111 G10
Adder
4.87
23546401DTGZ2-030
Solar/Wind Helper
0.078
316164AC1-076 GEN
Solar/Wind Helper
1.172
238152AF2-075_GEN
Solar/Wind Helper
0.602
970823AG2-518 GEN
50/50
8.384
247619Y1-049
50/50
0.913
24416005BYLLESBY
50/50
0.031
958121AF2-106 GEN
Solar/Wind Harmer
0.001
971331AH1-145 GEN
Solar/Wind Harmer
18.361
270346AE1-212 GEN
Solar/Wind Harmer
9.542
971461AH1-227 GEN
Solar/Wind Harmer
4.886
970223AG2-152 GEN
Solar/Wind Harmer
12.358
24686205CER G4
Adder
9.835
3429391JKCT 9G
Adder
8.402
958171AF2-111 GEN
Solar/Wind Harmer
16.681
970519AG2-331 GEN
Solar/Wind Harmer
17.292
970699AG2-449 GEN
Solar/Wind Harmer
1.663
25196608WSDLE5
Adder
7.849
970193AG2-126 GEN
Solar/Wind Harmer
9.55
24728705AND G3
Adder
7.277
253406AD2-031_GEN
Solar/Wind Harmer
0.467
270291AC1-194 GEN
Solar/Wind Harmer
4.924
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
959611AF2-252 GEN
Solar/Wind Harmer
2.073
270437AC2-090 C
Solar/Wind Harmer
0.003
253415AE1-040 GEN
Solar/Wind Harmer
0.002
970781AG2-491 GEN
Solar/Wind Harmer
6.144
274855GSG-6 ;RU
Solar/Wind Harmer
0.225
958821AF2-173 GEN
Solar/Wind Harmer
8.556
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
3147666LOUISA
Solar/Wind Helper
1.088
316254AC1-120 GEN1
Solar/Wind Helper
1.159
966391AG1-508 GEN
Solar/Wind Harmer
1.993
270069AE2-166 C O1
Solar/Wind Harmer
0.008
24734705WLF1G3
Adder
8.194
24734905WLF1G5
Adder
8.194
270399AC1-101 GEN
Solar/Wind Harmer
2.892
972143AH1-644 GEN
Solar/Wind Harmer
9.763
971981AH1-535 GEN
Solar/Wind Harmer
5.843
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
965401AG1-405 GEN
Solar/Wind Harmer
4.227
339211AE2-254 GEN
Solar/Wind Harmer
0.003
972165AH1-665 GEN
Solar/Wind Harmer
6.061
971985AH1-537 GEN
Solar/Wind Harmer
2.011
946321AF1-296 GEN
Solar/Wind Harmer
3.483
276656WTG2_EQ
Solar/Wind Harmer
0
941731AE2-173 GEN
Solar/Wind Harmer
5.162
24386405FR-21G C
Solar/Wind Harmer
0.001
24725505WLD G2 C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274823ROCKFORD ;21
Adder
17.15
971171AH1-044 GEN
Solar/Wind Harmer
12.273
971675AH1-338 GEN
Solar/Wind Harmer
2.39
971411AH1-196 GEN
Solar/Wind Harmer
9.19
276868AE1-113 GEN
Solar/Wind Harmer
1.227
3148013FISHERV
Solar/Wind Helper
0.3
971029AG2-637 GEN
Solar/Wind Harmer
2.803
24290605CLAY-1
50/50
0.255
24290605CLAY-1
50/50
0.255
24684405SMG2
50/50
2.224
316217AC1-145 GEN
Solar/Wind Harmer
0.003
316197AC1-042 GEN
Solar/Wind Harmer
0.002
942671AE2-283 GEN
Solar/Wind Harmer
5.796
971485AH1-239 GEN
Solar/Wind Harmer
5.928
964781AG1-341 GEN
Solar/Wind Harmer
7.653
971081AG2-670 GEN
Solar/Wind Harmer
5.396
942891AE2-308 GEN
Solar/Wind Harmer
7.099
972043AH1-570 GEN
Solar/Wind Harmer
1.796
25194408D.CRK1
Adder
6.938
945391AF1-204 GEN
Solar/Wind Harmer
6.765
24728905RICHG2
Adder
3.384
960251AF2-316 GEN
Solar/Wind Harmer
8.583
960611AF2-352 GEN
Solar/Wind Harmer
2.073
966841AG1-555 GEN
Solar/Wind Harmer
0.701
276782AC1-033 GEN
Solar/Wind Harmer
0.001
276708O09 GEN2
Solar/Wind Harmer
0.22
972267AH1-718 GEN
Adder
3.688
274764LEE CO EC;5U
Adder
8.241
926881AC1-175 GEN
Solar/Wind Harmer
0
971335AH1-147 GEN
Solar/Wind Harmer
12.256
274879MINONK ;1U
Solar/Wind Harmer
0.258
970921AG2-575 GEN
Solar/Wind Harmer
6.111
970921AG2-575 GEN
Solar/Wind Harmer
2.037
274683WAUKEGAN ;8U
Adder
18.419
274683WAUKEGAN ;8U
Adder
15.526
274693ROCKY RD ;1P
Adder
9.632
274862TOP CROP ;2U
Solar/Wind Harmer
0.824
958481AF2-142 GEN
Solar/Wind Harmer
9.131
3132123MT JACKSON
Solar/Wind Helper
1.389
966001AG1-469 GEN
Solar/Wind Helper
0.32
24290705CLAY-2
50/50
0.255
24290705CLAY-2
50/50
0.255
24684505SMG3
50/50
1.376
971277AH1-098 GEN
Solar/Wind Harmer
5.177
24728205BUCHG1
Adder
6.75
944971AF1-162 GEN
Solar/Wind Harmer
9.068
942751AE2-291 GEN
Solar/Wind Harmer
7.887
966021AG1-471 GEN
Solar/Wind Harmer
4.013
339255AE2-071 GEN
Solar/Wind Harmer
-0.119
970653AG2-424 GEN
Solar/Wind Harmer
3.405
970653AG2-424 GEN
Solar/Wind Harmer
1.764
964571AG1-320 GEN
Solar/Wind Harmer
6.361
972045AH1-571 GEN
Solar/Wind Harmer
1.439
339221AD2-048_GEN
Solar/Wind Harmer
0.004
252509AD1-136 GEN
Solar/Wind Harmer
0.033
25183208HLCRTG
Solar/Wind Harmer
0.01
25194508D.CRK3
Adder
1.297
971073AG2-665 GEN
Solar/Wind Harmer
5.761
276911AD2-131_GEN
Solar/Wind Harmer
0.88
24728805RICHG1
Adder
3.384
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
276646AC1-214 GEN2
Solar/Wind Harmer
0.243
274765LEE CO EC;6U
Adder
8.241
274763LEE CO EC;4U
Adder
8.144
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270383AD1-128 GEN
Solar/Wind Harmer
0.004
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
971333AH1-146 GEN
Solar/Wind Harmer
12.256
945421AF1-207 GEN
Solar/Wind Harmer
0.001
942991AE2-321 GEN
Solar/Wind Harmer
6.834
958491AF2-143 GEN
Solar/Wind Harmer
9.158
960441AF2-335 GEN
Solar/Wind Harmer
6.106
274695ROCKY RD ;2P
Adder
9.727
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
971573AH1-285 GEN
Solar/Wind Harmer
1.134
966871AG1-558 GEN
Solar/Wind Helper
0.306
3147312GRETNA
Solar/Wind Harmer
0.047
971687AH1-348 GEN
Solar/Wind Harmer
0.948
971315AH1-136 GEN
Solar/Wind Harmer
1.695
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
970333AG2-219 GEN
Solar/Wind Harmer
4.755
25196808ZIMRHP
Adder
70.616
25196008MFTGT1
Adder
1.293
274880W4-005 GEN4
Solar/Wind Harmer
0.001
972175AH1-670 GEN
Solar/Wind Harmer
5.171
939741AE1-205 GEN
Solar/Wind Harmer
8.673
24387305FR-4G C
Solar/Wind Harmer
0.002
276158O29GEN2
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
8.222
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970569AG2-363 GEN
Solar/Wind Harmer
18.444
276861AD2-134 GEN
Solar/Wind Harmer
0.11
971997AH1-543 GEN
Solar/Wind Harmer
3.211
270032AE2-172
Solar/Wind Harmer
4.079
270005AE1-210 C O1
Solar/Wind Harmer
1.324
970825AG2-519 GEN
Solar/Wind Harmer
2.167
237061AD1-155 GEN
Solar/Wind Helper
0.05
23583801GRNGAP
Solar/Wind Helper
4.287
970563AG2-360 GEN
50/50
45.829
962751AG1-124 GEN
Solar/Wind Harmer
12.893
3147312GRETNA
Solar/Wind Harmer
0.186
3146802CHATHAM
Solar/Wind Harmer
0.175
270016AE1-250 BESS
Solar/Wind Harmer
0.006
972273AH1-721 GEN
Adder
89.316
966571AG1-526 GEN
Solar/Wind Harmer
15.967
970093AG2-073 GEN
Solar/Wind Harmer
7.166
971191AH1-055 GEN
Solar/Wind Harmer
18.055
972167AH1-666 GEN
Solar/Wind Harmer
5.419
970243AG2-164 GEN
Solar/Wind Harmer
3.891
25196008MFTGT1
Adder
1.252
252510AF1-249 C
Solar/Wind Harmer
0.05
942481AE2-261 GEN
Solar/Wind Harmer
18.997
276621W2-048 GEN
Solar/Wind Harmer
0.318
276838X2-022 GEN2
Solar/Wind Harmer
0.355
971993AH1-541 GEN
Solar/Wind Harmer
2.905
942111AE2-223 GEN
Solar/Wind Harmer
2.013
276157O29GEN1
Solar/Wind Harmer
0.999
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
970571AG2-364 GEN
Solar/Wind Harmer
12.296
276889AE2-281 GEN
Solar/Wind Harmer
0.001
274850MENDOTA H;RU
Solar/Wind Harmer
0.072
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.11
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.654
276805AD2-038 GEN
Solar/Wind Harmer
0.002
274729ELWOOD EC;1P
Adder
13.481
3147983MERCK5
Solar/Wind Helper
0.198
24415905BUCK
50/50
0.034
971329AH1-144 GEN
Solar/Wind Harmer
11.568
958131AF2-107 GEN
Solar/Wind Harmer
5.339
971403AH1-188 GEN
Solar/Wind Harmer
13.153
970273AG2-179 GEN
Solar/Wind Harmer
2.581
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
3429421JKCT 10G
Adder
8.402
971565AH1-281 GEN
Solar/Wind Harmer
1.396
927014AC1-188 GEN
Solar/Wind Harmer
0.004
970091AG2-072 GEN
Adder
74.012
970773AG2-487 GEN
Solar/Wind Harmer
1.107
963741AG1-226 GEN
Solar/Wind Harmer
14.811
274854TWINGROVE;U2
Solar/Wind Harmer
0.003
276726Z2-087_GEN
Solar/Wind Harmer
0.002
971475AH1-234 GEN
Solar/Wind Harmer
2.986
970819AG2-516 GEN
Solar/Wind Harmer
7.379
24791305MDL-5G
Solar/Wind Harmer
0.001
274822ROCKFORD ;11
Adder
17.275
959081AF2-199 GEN
Solar/Wind Harmer
6.136
971067AG2-660 GEN
Solar/Wind Harmer
2.045
270263AC1-001 GEN
Solar/Wind Harmer
0.614
274872LEEDK;1U
Solar/Wind Harmer
0.004
276691AA1-018 GEN1
Solar/Wind Harmer
0.737
3132273ORANGE
Solar/Wind Helper
0.056
316170AC1-121 GEN2
Solar/Wind Helper
0.386
316313AB2-026
Solar/Wind Helper
0.354
24288905REUSENS
50/50
0.057
24684605SMG4
50/50
2.239
24728305BUCHG2
Adder
6.75
270018AE2-047 C O1
Solar/Wind Harmer
0.004
24686505CER G6
Adder
9.874
962241AG1-070 GEN
Solar/Wind Harmer
3.92
3429241JKCT 3G
Adder
12.029
339216AC1-074 GEN
Solar/Wind Harmer
0.187
252507AC2-088 GEN
Solar/Wind Harmer
0.295
965911AG1-460 GEN
Solar/Wind Harmer
1.271
276615X2-022 GEN
Solar/Wind Harmer
0.066
963831AG1-236 GEN
Solar/Wind Harmer
2.455
24385905FR-11G C
Solar/Wind Harmer
0.001
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274766LEE CO EC;7U
Adder
8.125
276903AD2-071 C
Solar/Wind Harmer
6.874
972235AH1-702 GEN1
Adder
2.22
238149AF1-291A_GEN
Solar/Wind Helper
0.12
316258AE1-075 C
Solar/Wind Helper
0.319
965931AG1-462 GEN
Solar/Wind Harmer
15.879
965091AG1-374 GEN
Solar/Wind Harmer
18.654
274878BISHOP HL;2U
Solar/Wind Harmer
0.208
274760LEE CO EC;1U
Adder
8.222
972236AH1-702 GEN2
Adder
1.93
274872LEEDK;1U
Solar/Wind Harmer
0.224
270004AE1-209 GEN
Solar/Wind Harmer
1.324
238148AE2-230_GEN2
Solar/Wind Helper
0.423
316006AB2-029 C
Solar/Wind Helper
0.112
316045AC1-158 PL2
Solar/Wind Helper
4.023
970281AG2-184 GEN
Solar/Wind Harmer
18.925
972203AH1-686 GEN
Adder
2.704
970165AG2-112 GEN
Solar/Wind Harmer
0.998
970163AG2-111 GEN
Solar/Wind Harmer
0.952
252524AE2-267 GEN
Solar/Wind Harmer
0.002
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.229
276848AB2-070 GEN3
Solar/Wind Harmer
0.228
959341AF2-225 GEN
Solar/Wind Harmer
6.505
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
961011AF2-392 GEN
Solar/Wind Harmer
3.623
970169AG2-114 GEN
Solar/Wind Harmer
6.149
970289AG2-191 GEN
Solar/Wind Harmer
1.163
274744AC1-111 GEN8
Adder
4.87
25306009OHH W.
Adder
2.505
3148463FAIRFLD
Solar/Wind Helper
0.726
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
962781AG1-127 GEN
Solar/Wind Harmer
5.815
939401AE1-172 GEN
Solar/Wind Harmer
4.568
315616AA1-038_C
Solar/Wind Helper
3.293
3148013FISHERV
Solar/Wind Helper
0.523
3147666LOUISA
Solar/Wind Helper
0.625
238147AE2-230_GEN1
Solar/Wind Helper
0.421
316405AF2-144 C
Solar/Wind Helper
0.265
316044AC1-158 PL1
Solar/Wind Helper
1.257
316450AC1-158 RIC
Solar/Wind Helper
0.335
270583AD2-179 GEN
Solar/Wind Harmer
14.457
971225AH1-072 GEN
Solar/Wind Harmer
1.905
971227AH1-073 GEN
Solar/Wind Harmer
1.905
24723005RIVRG1
Adder
22.954
24723105RIVRG2
Adder
22.954
24685805CER G1
Adder
9.822
24685905CER G2
Adder
9.822
971125AH1-004 GEN
Solar/Wind Harmer
2.777
270444AC2-157 GEN1
Solar/Wind Harmer
0.003
971587AH1-292 GEN
Solar/Wind Harmer
4.8
252519AF1-045_GEN
Solar/Wind Harmer
5.589
252516AE2-318_GEN
Solar/Wind Harmer
4.958
276916AD2-100_GEN
Solar/Wind Harmer
13.364
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
276741O09 GEN1
Solar/Wind Harmer
0.22
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
971341AH1-150 GEN
Solar/Wind Harmer
12.273
971343AH1-151 GEN
Solar/Wind Harmer
12.273
971613AH1-306 GEN
Solar/Wind Harmer
2.937
315651AD1-115 GEN
Solar/Wind Helper
0.837
316447AC1-158 HLD
Solar/Wind Helper
2.766
971543AH1-269 GEN
50/50
12.247
971313AH1-133 GEN
Solar/Wind Harmer
10.952
270132AB1-180 C
Adder
0.169
971061AG2-657 GEN
Solar/Wind Harmer
5.368
965411AG1-406 GEN
Solar/Wind Harmer
2.719
270367AC2-061_GEN
Solar/Wind Harmer
0.005
316123AC1-075 GEN
Solar/Wind Harmer
0.168
25196108MFTGT2
Adder
1.425
25196108MFTGT2
Adder
1.324
970879AG2-548 GEN
Solar/Wind Harmer
5.761
25196408WSDLE3
Adder
8.08
25196308WSDLE2
Adder
8.01
25196208WSDLE1
Adder
7.99
25196708WSDLE6
Adder
7.97
276174W4-005 GEN2
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
957751AF2-069 GEN
Solar/Wind Harmer
0.204
270240V3-007_GEN2
Solar/Wind Harmer
0.002
971681AH1-341 GEN
Solar/Wind Harmer
9.917
276612AE2-035 GEN
Solar/Wind Harmer
0.002
24691005MDL-2G C
Solar/Wind Harmer
0.001
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
971177AH1-047 GEN
Solar/Wind Harmer
3.774
270594AE1-207 GEN
Solar/Wind Harmer
6.853
971673AH1-337 GEN
Solar/Wind Harmer
3.956
3148133STUARTS
Solar/Wind Helper
0.313
24684305SMG1
50/50
0.806
270013AE1-250 PV
Solar/Wind Harmer
0.006
960161AF2-307 GEN
Solar/Wind Harmer
4.775
970107AG2-081 GEN
Solar/Wind Harmer
2.083
970235AG2-159 GEN
Solar/Wind Harmer
4.126
970235AG2-159 GEN
Solar/Wind Harmer
2.367
270186AC1-089 GEN
Solar/Wind Harmer
0.004
970239AG2-162 GEN
Solar/Wind Harmer
1.663
962581AG1-107 GEN
Solar/Wind Harmer
0.001
970241AG2-163 GEN
Solar/Wind Harmer
3.651
253394AE2-221_GEN
Solar/Wind Harmer
0.008
253398AE2-221_GEN2
Solar/Wind Harmer
0.008
960201AF2-311 GEN
Solar/Wind Harmer
5.708
276645AC1-214 GEN1
Solar/Wind Harmer
0.243
276603SUBLETTE C
Solar/Wind Harmer
0
274762LEE CO EC;3U
Adder
8.222
270209AC1-174_GEN
Solar/Wind Harmer
0
938861AE1-114 GEN
Solar/Wind Harmer
3.491
274856ECOGROVE ;U1
Solar/Wind Harmer
0.145
276611AD2-172 GEN
Solar/Wind Harmer
0.002
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
962691AG1-118 GEN
Solar/Wind Harmer
18.322
970825AG2-519 GEN
Solar/Wind Harmer
6.767
274696ROCKY RD ;4P
Adder
9.957
274697ROCKY RD ;3P
Adder
2.642
315821AE2-092 GEN
Solar/Wind Helper
3.216
316468AD1-105 GEN
Solar/Wind Helper
1.124
944201AF1-088_MTX
Adder
109.09
957141AF2-008_MTX
Adder
54.545
NYPJM->LTFIMP_NY
CLTF
3.248
LGEELTFEXP_LGEE->PJM
CLTF
6.763
WECLTFEXP_WEC->PJM
CLTF
3.371
AG2-052LTFEXP_AG2-052->PJM
LTF
0.202
AH1-155LTFEXP_AH1-155->PJM
LTF
0.303
LAGNLTFEXP_LAGN->PJM
CLTF
20.28
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.555
TVALTFEXP_TVA->PJM
CLTF
10.606
CPLELTFEXP_CPLE->PJM
CLTF
6.226
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.111
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.415
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.315
MECLTFEXP_MEC->PJM
CLTF
15.415
SIGELTFEXP_SIGE->PJM
CLTF
0.508

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-020_SRT-SL


Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-020_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.02 %
Rating:3610.0 MVA
Rating Type:B
MVA to Mitigate:4224.55
MW Contribution:7.01
Bus #Bus NameTypeMW Contribution
970479AG2-310 GEN
50/50
20.278
270205AE1-176
50/50
0.006
966251AG1-494 GEN
50/50
4.391
24728405LEESVG
50/50
0.297
971367AH1-164 GEN
Solar/Wind Harmer
7.012
941821AE2-187 GEN
Solar/Wind Harmer
9.82
270197AD1-017 GEN1
Solar/Wind Harmer
2.549
970481AG2-311 GEN
50/50
11.948
24728405LEESVG
50/50
0.296
943031AE2-326 GEN
Solar/Wind Harmer
6.798
270574AD1-017 GEN2
Solar/Wind Harmer
8.482
3147123OTTER R
Solar/Wind Harmer
-0.014
270030AE2-140 GEN
Solar/Wind Harmer
30.98
960911AF2-382 GEN
Solar/Wind Harmer
10.985
972103AH1-617 GEN
Solar/Wind Harmer
25.94
24721905FLATG4
Adder
21.813
971155AH1-034 GEN
Solar/Wind Harmer
10.404
960741AF2-365 GEN
Solar/Wind Harmer
5.133
25194608D.CRK4
Adder
1.519
253316AC1-085 GEN3
Solar/Wind Harmer
7.655
253433AC1-085 GEN1
Solar/Wind Harmer
4.859
946181AF1-283 GEN
Solar/Wind Harmer
11.881
24728505AND G1
Adder
3.502
276668AB2-070 GEN1
Solar/Wind Harmer
2.04
274767LEE CO EC;8U
Adder
8.175
274682WAUKEGAN ;7U
Adder
15.803
253370AE2-315 SEC1
Adder
1.753
253371AE2-315 SEC2
Adder
1.658
316192AB2-158 GEN
Solar/Wind Helper
1.845
316097T157 G90
Solar/Wind Helper
1.133
316336AC2-165 C
Solar/Wind Helper
1.289
3142416OLDCHRC
Solar/Wind Helper
0.58
3142416OLDCHRC
Solar/Wind Helper
0.222
970281AG2-184 GEN
Solar/Wind Harmer
27.237
962211AG1-066 GEN
Solar/Wind Harmer
3.014
972203AH1-686 GEN
Adder
2.718
970165AG2-112 GEN
Solar/Wind Harmer
1.315
970163AG2-111 GEN
Solar/Wind Harmer
1.255
252524AE2-267 GEN
Solar/Wind Harmer
1.454
276785W4-005 GEN1
Solar/Wind Harmer
2.743
276849AB2-070 GEN2
Solar/Wind Harmer
2.04
276848AB2-070 GEN3
Solar/Wind Harmer
2.04
274744AC1-111 GEN8
Adder
4.901
25306009OHH W.
Adder
2.523
253372AE2-315 SEC3
Adder
1.658
253372AE2-315 SEC3
Adder
1.658
970823AG2-518 GEN
50/50
8.396
247619Y1-049
50/50
0.915
24416005BYLLESBY
50/50
0.031
958121AF2-106 GEN
Solar/Wind Harmer
9.423
971331AH1-145 GEN
Solar/Wind Harmer
18.398
270346AE1-212 GEN
Solar/Wind Harmer
13.986
971461AH1-227 GEN
Solar/Wind Harmer
7.029
970223AG2-152 GEN
Solar/Wind Harmer
17.643
24686205CER G4
Adder
9.888
3429391JKCT 9G
Adder
8.45
957541AF2-048 GEN
Solar/Wind Harmer
1.539
958171AF2-111 GEN
Solar/Wind Harmer
24.064
970519AG2-331 GEN
Solar/Wind Harmer
16.62
970699AG2-449 GEN
Solar/Wind Harmer
10.995
25196608WSDLE5
Adder
7.903
970193AG2-126 GEN
Solar/Wind Harmer
13.773
24728705AND G3
Adder
7.324
253406AD2-031_GEN
Solar/Wind Harmer
1.157
3147666LOUISA
Solar/Wind Helper
1.091
316254AC1-120 GEN1
Solar/Wind Helper
1.164
3148463FAIRFLD
Solar/Wind Helper
0.727
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
3147312GRETNA
Solar/Wind Harmer
-0.005
971687AH1-348 GEN
Solar/Wind Harmer
1.364
971315AH1-136 GEN
Solar/Wind Harmer
2.441
270331AC1-082 GEN3
Solar/Wind Harmer
0.49
970333AG2-219 GEN
Solar/Wind Harmer
30.235
25196808ZIMRHP
Adder
71.09
25196008MFTGT1
Adder
1.302
274880W4-005 GEN4
Solar/Wind Harmer
2.743
274761LEE CO EC;2U
Adder
8.273
237061AD1-155 GEN
Solar/Wind Helper
0.05
23583801GRNGAP
Solar/Wind Helper
4.315
238149AF1-291A_GEN
Solar/Wind Helper
0.121
316258AE1-075 C
Solar/Wind Helper
0.319
972175AH1-670 GEN
Solar/Wind Harmer
4.749
971543AH1-269 GEN
50/50
12.267
971313AH1-133 GEN
Solar/Wind Harmer
15.745
270132AB1-180 C
Adder
0.169
971061AG2-657 GEN
Solar/Wind Harmer
11.059
965411AG1-406 GEN
Solar/Wind Harmer
2.733
270367AC2-061_GEN
Solar/Wind Harmer
3.029
316123AC1-075 GEN
Solar/Wind Harmer
1.494
25196108MFTGT2
Adder
1.435
25196108MFTGT2
Adder
1.332
970879AG2-548 GEN
Solar/Wind Harmer
3.978
25196408WSDLE3
Adder
8.135
25196308WSDLE2
Adder
8.064
25196208WSDLE1
Adder
8.044
25196708WSDLE6
Adder
8.024
276174W4-005 GEN2
Solar/Wind Harmer
2.743
3148133STUARTS
Solar/Wind Helper
0.314
316312AB1-027
Solar/Wind Helper
0.425
3141426STAFORD
Solar/Wind Helper
0.049
24684705SMG5
50/50
0.857
3151561HALLBR1
50/50
0.57
270173AC1-122 GEN
Solar/Wind Harmer
3.281
941801AE2-185 GEN
Solar/Wind Harmer
9.82
970913AG2-568 GEN
Solar/Wind Harmer
11.054
270053AF1-130 C
Solar/Wind Harmer
4.837
24686405CER G5
Adder
9.849
970273AG2-179 GEN
Solar/Wind Harmer
4.143
339250AF1-203 GEN
Solar/Wind Harmer
0.631
962251AG1-071 GEN
Solar/Wind Harmer
5.699
276686W4-005 GEN3
Solar/Wind Harmer
2.743
270356AE2-297 GEN
Solar/Wind Harmer
4.125
274760LEE CO EC;1U
Adder
8.273
972236AH1-702 GEN2
Adder
1.942
238148AE2-230_GEN2
Solar/Wind Helper
0.425
316006AB2-029 C
Solar/Wind Helper
0.113
316045AC1-158 PL2
Solar/Wind Helper
4.042
24290705CLAY-2
50/50
0.256
24290705CLAY-2
50/50
0.256
24684505SMG3
50/50
1.377
971277AH1-098 GEN
Solar/Wind Harmer
7.435
24728205BUCHG1
Adder
6.772
944971AF1-162 GEN
Solar/Wind Harmer
9.108
942751AE2-291 GEN
Solar/Wind Harmer
10.391
966021AG1-471 GEN
Solar/Wind Harmer
5.779
339231AF1-038_GEN
Solar/Wind Harmer
1.927
339255AE2-071 GEN
Solar/Wind Harmer
1.104
970653AG2-424 GEN
Solar/Wind Harmer
4.906
970653AG2-424 GEN
Solar/Wind Harmer
1.774
964571AG1-320 GEN
Solar/Wind Harmer
8.231
972045AH1-571 GEN
Solar/Wind Harmer
1.992
339221AD2-048_GEN
Solar/Wind Harmer
1.523
252509AD1-136 GEN
Solar/Wind Harmer
0.24
25183208HLCRTG
Solar/Wind Harmer
5.62
971073AG2-665 GEN
Solar/Wind Harmer
5.702
971073AG2-665 GEN
Solar/Wind Harmer
3.978
25194508D.CRK3
Adder
1.306
276911AD2-131_GEN
Solar/Wind Harmer
3.894
24728805RICHG1
Adder
3.406
274765LEE CO EC;6U
Adder
8.292
274763LEE CO EC;4U
Adder
8.195
274695ROCKY RD ;2P
Adder
9.789
966871AG1-558 GEN
Solar/Wind Helper
0.307
270583AD2-179 GEN
Solar/Wind Harmer
20.758
270214AC2-123 GEN
Solar/Wind Harmer
4.319
971225AH1-072 GEN
Solar/Wind Harmer
2.74
971227AH1-073 GEN
Solar/Wind Harmer
2.74
270336AE1-100 GEN
Solar/Wind Harmer
2.762
943811AF1-049 GEN
Solar/Wind Harmer
5.705
24735205WLF2G2
Adder
8.049
24723205RIVRG3
Adder
23.068
24686105CER G3
Adder
9.94
970947AG2-589 GEN
Solar/Wind Harmer
2.153
24721705FLATG2
Adder
21.813
971821AH1-427 GEN
Solar/Wind Harmer
10.401
964901AG1-354 GEN
Solar/Wind Harmer
15.577
339241AF1-083 GEN
Solar/Wind Harmer
1.723
943111AE2-339 GEN
Solar/Wind Harmer
0.888
945681AF1-233 GEN
Solar/Wind Harmer
18.436
270445AC2-157 GEN2
Solar/Wind Harmer
5.271
25194608D.CRK4
Adder
1.519
253432AC1-085 GEN2
Solar/Wind Harmer
0.245
946171AF1-282 GEN
Solar/Wind Harmer
9.139
24728605AND G2
Adder
3.502
274828WAUKEGAN ;BP
Adder
9.716
274682WAUKEGAN ;7U
Adder
15.803
274745AC1-111 GEN9
Adder
4.901
253370AE2-315 SEC1
Adder
1.753
253371AE2-315 SEC2
Adder
1.658
316499AE2-029_GEN
Solar/Wind Helper
1.727
316095T157 G97
Solar/Wind Helper
1.133
966881AG1-559 GEN
Solar/Wind Helper
0.314
316473AC1-191 GEN
Solar/Wind Helper
1.391
24290605CLAY-1
50/50
0.256
24290605CLAY-1
50/50
0.256
24684405SMG2
50/50
2.226
316217AC1-145 GEN
Solar/Wind Harmer
4.25
316197AC1-042 GEN
Solar/Wind Harmer
3.222
942671AE2-283 GEN
Solar/Wind Harmer
8.674
971485AH1-239 GEN
Solar/Wind Harmer
8.537
964781AG1-341 GEN
Solar/Wind Harmer
11.023
971081AG2-670 GEN
Solar/Wind Harmer
7.773
942891AE2-308 GEN
Solar/Wind Harmer
10.233
972043AH1-570 GEN
Solar/Wind Harmer
2.49
25194408D.CRK1
Adder
6.985
945391AF1-204 GEN
Solar/Wind Harmer
12.796
24728905RICHG2
Adder
3.406
972267AH1-718 GEN
Adder
3.711
274764LEE CO EC;5U
Adder
8.292
274683WAUKEGAN ;8U
Adder
18.536
274683WAUKEGAN ;8U
Adder
15.625
274693ROCKY RD ;1P
Adder
9.693
3132123MT JACKSON
Solar/Wind Helper
1.392
966001AG1-469 GEN
Solar/Wind Helper
0.321
24415905BUCK
50/50
0.034
971329AH1-144 GEN
Solar/Wind Harmer
23.734
958131AF2-107 GEN
Solar/Wind Harmer
7.112
971403AH1-188 GEN
Solar/Wind Harmer
18.932
970273AG2-179 GEN
Solar/Wind Harmer
2.594
960001AF2-291 GEN
Solar/Wind Harmer
3.136
3429421JKCT 10G
Adder
8.45
971565AH1-281 GEN
Solar/Wind Harmer
2.012
927014AC1-188 GEN
Solar/Wind Harmer
1.543
970091AG2-072 GEN
Adder
74.457
963741AG1-226 GEN
Solar/Wind Harmer
40.621
274822ROCKFORD ;11
Adder
17.383
3132273ORANGE
Solar/Wind Helper
0.056
316170AC1-121 GEN2
Solar/Wind Helper
0.388
316313AB2-026
Solar/Wind Helper
0.355
966391AG1-508 GEN
Solar/Wind Harmer
6.388
270069AE2-166 C O1
Solar/Wind Harmer
4.514
24734705WLF1G3
Adder
8.22
24734905WLF1G5
Adder
8.22
270399AC1-101 GEN
Solar/Wind Harmer
5.58
972143AH1-644 GEN
Solar/Wind Harmer
12.97
971981AH1-535 GEN
Solar/Wind Harmer
12.604
270330AC1-082 GEN2
Solar/Wind Harmer
0.83
965401AG1-405 GEN
Solar/Wind Harmer
6.089
339211AE2-254 GEN
Solar/Wind Harmer
1.572
972165AH1-665 GEN
Solar/Wind Harmer
7.844
971985AH1-537 GEN
Solar/Wind Harmer
17.415
274823ROCKFORD ;21
Adder
17.257
3148013FISHERV
Solar/Wind Helper
0.301
24734805WLF1G4
Adder
8.22
24735105WLF2G1
Adder
8.049
270400AC1-102 GEN
Solar/Wind Harmer
5.58
941621AE2-160 GEN
Adder
4.308
957241AF2-018 GEN
Solar/Wind Harmer
5.782
24477305BRIDGE
Adder
0.422
270329AC1-082 GEN1
Solar/Wind Harmer
0.489
3429211JKCT 2G
Adder
11.941
970455AG2-298 GEN
Solar/Wind Harmer
6.067
339243AC2-075 GEN1
Solar/Wind Harmer
0.449
972163AH1-664 GEN
Solar/Wind Harmer
9.805
944221AF1-090 GEN
Solar/Wind Harmer
10.083
25196508WSDLE4
Adder
7.822
274746AC1-111 G10
Adder
4.901
23546401DTGZ2-030
Solar/Wind Helper
0.079
316164AC1-076 GEN
Solar/Wind Helper
1.177
238152AF2-075_GEN
Solar/Wind Helper
0.605
24288905REUSENS
50/50
0.057
24684605SMG4
50/50
2.241
24728305BUCHG2
Adder
6.772
270018AE2-047 C O1
Solar/Wind Harmer
1.828
24686505CER G6
Adder
9.927
962241AG1-070 GEN
Solar/Wind Harmer
4.662
3429241JKCT 3G
Adder
12.097
339216AC1-074 GEN
Solar/Wind Harmer
1.659
252507AC2-088 GEN
Solar/Wind Harmer
1.681
965911AG1-460 GEN
Solar/Wind Harmer
1.278
276615X2-022 GEN
Solar/Wind Harmer
1.783
963831AG1-236 GEN
Solar/Wind Harmer
8.931
274766LEE CO EC;7U
Adder
8.175
972235AH1-702 GEN1
Adder
2.234
315616AA1-038_C
Solar/Wind Helper
3.295
3148013FISHERV
Solar/Wind Helper
0.523
3147666LOUISA
Solar/Wind Helper
0.628
238147AE2-230_GEN1
Solar/Wind Helper
0.423
316405AF2-144 C
Solar/Wind Helper
0.266
316044AC1-158 PL1
Solar/Wind Helper
1.263
316450AC1-158 RIC
Solar/Wind Helper
0.337
24723005RIVRG1
Adder
23.068
24723105RIVRG2
Adder
23.068
24685805CER G1
Adder
9.875
24685905CER G2
Adder
9.875
971125AH1-004 GEN
Solar/Wind Harmer
4.003
270444AC2-157 GEN1
Solar/Wind Harmer
5.271
252519AF1-045_GEN
Solar/Wind Harmer
5.628
252516AE2-318_GEN
Solar/Wind Harmer
4.293
276916AD2-100_GEN
Solar/Wind Harmer
19.269
957381AF2-032 GEN
Solar/Wind Harmer
0.383
253317AC1-085 GEN4
Solar/Wind Harmer
7.655
276763AC1-053 GEN1
Solar/Wind Harmer
3.59
276764AC1-053 GEN2
Solar/Wind Harmer
3.59
253370AE2-315 SEC1
Adder
1.753
315651AD1-115 GEN
Solar/Wind Helper
0.841
316447AC1-158 HLD
Solar/Wind Helper
2.779
24684305SMG1
50/50
0.807
270013AE1-250 PV
Solar/Wind Harmer
3.259
960161AF2-307 GEN
Solar/Wind Harmer
6.695
339236AF1-050_GEN
Solar/Wind Harmer
1.882
970107AG2-081 GEN
Solar/Wind Harmer
3.003
970235AG2-159 GEN
Solar/Wind Harmer
3.901
970235AG2-159 GEN
Solar/Wind Harmer
2.382
270186AC1-089 GEN
Solar/Wind Harmer
5.863
970239AG2-162 GEN
Solar/Wind Harmer
10.536
962581AG1-107 GEN
Solar/Wind Harmer
4.763
961491AF2-440 GEN
Solar/Wind Harmer
1.98
970879AG2-548 GEN
Solar/Wind Harmer
5.702
970241AG2-163 GEN
Solar/Wind Harmer
22.567
274762LEE CO EC;3U
Adder
8.273
274696ROCKY RD ;4P
Adder
10.02
274697ROCKY RD ;3P
Adder
2.659
315821AE2-092 GEN
Solar/Wind Helper
3.222
316468AD1-105 GEN
Solar/Wind Helper
1.129
970563AG2-360 GEN
50/50
45.959
962751AG1-124 GEN
Solar/Wind Harmer
18.84
3147312GRETNA
Solar/Wind Harmer
-0.021
3146802CHATHAM
Solar/Wind Harmer
-0.02
270016AE1-250 BESS
Solar/Wind Harmer
3.259
972273AH1-721 GEN
Adder
89.748
966571AG1-526 GEN
Solar/Wind Harmer
23.009
970093AG2-073 GEN
Solar/Wind Harmer
10.328
971191AH1-055 GEN
Solar/Wind Harmer
22.339
972167AH1-666 GEN
Solar/Wind Harmer
7.817
970243AG2-164 GEN
Solar/Wind Harmer
24.738
25196008MFTGT1
Adder
1.261
252510AF1-249 C
Solar/Wind Harmer
0.387
942481AE2-261 GEN
Solar/Wind Harmer
27.393
276621W2-048 GEN
Solar/Wind Harmer
5.679
276838X2-022 GEN2
Solar/Wind Harmer
0.212
971993AH1-541 GEN
Solar/Wind Harmer
8.379
274729ELWOOD EC;1P
Adder
1.688
3147983MERCK5
Solar/Wind Helper
0.199
944201AF1-088_MTX
Adder
109.749
957141AF2-008_MTX
Adder
54.874
NYPJM->LTFIMP_NY
CLTF
3.272
LGEELTFEXP_LGEE->PJM
CLTF
6.802
WECLTFEXP_WEC->PJM
CLTF
3.393
AG2-052LTFEXP_AG2-052->PJM
LTF
0.203
AH1-155LTFEXP_AH1-155->PJM
LTF
0.304
LAGNLTFEXP_LAGN->PJM
CLTF
20.369
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.617
TVALTFEXP_TVA->PJM
CLTF
10.651
CPLELTFEXP_CPLE->PJM
CLTF
6.237
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.77
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.199
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.491
MECLTFEXP_MEC->PJM
CLTF
15.504
SIGELTFEXP_SIGE->PJM
CLTF
0.511

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-021_SRT-SL


Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-021_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.77 %
Rating:3610.0 MVA
Rating Type:B
MVA to Mitigate:4215.43
MW Contribution:7.01
Bus #Bus NameTypeMW Contribution
970481AG2-311 GEN
50/50
11.94
24728405LEESVG
50/50
0.296
943031AE2-326 GEN
Solar/Wind Harmer
6.789
270574AD1-017 GEN2
Solar/Wind Harmer
8.476
3147123OTTER R
Solar/Wind Harmer
-0.014
270030AE2-140 GEN
Solar/Wind Harmer
30.945
960911AF2-382 GEN
Solar/Wind Harmer
10.959
972103AH1-617 GEN
Solar/Wind Harmer
25.867
24721905FLATG4
Adder
21.725
971155AH1-034 GEN
Solar/Wind Harmer
10.369
960741AF2-365 GEN
Solar/Wind Harmer
5.115
25194608D.CRK4
Adder
1.511
253316AC1-085 GEN3
Solar/Wind Harmer
7.618
253433AC1-085 GEN1
Solar/Wind Harmer
4.836
946181AF1-283 GEN
Solar/Wind Harmer
11.823
24728505AND G1
Adder
3.486
970823AG2-518 GEN
50/50
8.387
247619Y1-049
50/50
0.914
24416005BYLLESBY
50/50
0.031
958121AF2-106 GEN
Solar/Wind Harmer
9.412
971331AH1-145 GEN
Solar/Wind Harmer
18.373
270346AE1-212 GEN
Solar/Wind Harmer
13.951
971461AH1-227 GEN
Solar/Wind Harmer
7.011
970223AG2-152 GEN
Solar/Wind Harmer
17.629
24686205CER G4
Adder
9.851
3429391JKCT 9G
Adder
8.417
957541AF2-048 GEN
Solar/Wind Harmer
1.531
958171AF2-111 GEN
Solar/Wind Harmer
23.957
970519AG2-331 GEN
Solar/Wind Harmer
16.549
970699AG2-449 GEN
Solar/Wind Harmer
10.948
25196608WSDLE5
Adder
7.866
970193AG2-126 GEN
Solar/Wind Harmer
13.715
24728705AND G3
Adder
7.292
253406AD2-031_GEN
Solar/Wind Harmer
1.151
3147666LOUISA
Solar/Wind Helper
1.089
316254AC1-120 GEN1
Solar/Wind Helper
1.161
970281AG2-184 GEN
Solar/Wind Harmer
27.16
962211AG1-066 GEN
Solar/Wind Harmer
3.005
972203AH1-686 GEN
Adder
2.709
970165AG2-112 GEN
Solar/Wind Harmer
1.315
970163AG2-111 GEN
Solar/Wind Harmer
1.254
252524AE2-267 GEN
Solar/Wind Harmer
1.447
276849AB2-070 GEN2
Solar/Wind Harmer
2.031
276848AB2-070 GEN3
Solar/Wind Harmer
2.031
276785W4-005 GEN1
Solar/Wind Harmer
2.731
274744AC1-111 GEN8
Adder
4.879
25306009OHH W.
Adder
2.51
253372AE2-315 SEC3
Adder
1.649
3147312GRETNA
Solar/Wind Harmer
-0.005
971687AH1-348 GEN
Solar/Wind Harmer
1.36
971315AH1-136 GEN
Solar/Wind Harmer
2.433
270331AC1-082 GEN3
Solar/Wind Harmer
0.488
970333AG2-219 GEN
Solar/Wind Harmer
30.107
25196808ZIMRHP
Adder
70.761
25196008MFTGT1
Adder
1.296
274880W4-005 GEN4
Solar/Wind Harmer
2.731
274761LEE CO EC;2U
Adder
8.237
237061AD1-155 GEN
Solar/Wind Helper
0.05
23583801GRNGAP
Solar/Wind Helper
4.296
238149AF1-291A_GEN
Solar/Wind Helper
0.12
316258AE1-075 C
Solar/Wind Helper
0.319
972175AH1-670 GEN
Solar/Wind Harmer
4.729
24684705SMG5
50/50
0.857
3151561HALLBR1
50/50
0.57
270173AC1-122 GEN
Solar/Wind Harmer
3.279
941801AE2-185 GEN
Solar/Wind Harmer
9.814
970913AG2-568 GEN
Solar/Wind Harmer
11.019
270053AF1-130 C
Solar/Wind Harmer
4.822
24686405CER G5
Adder
9.812
970273AG2-179 GEN
Solar/Wind Harmer
4.129
339250AF1-203 GEN
Solar/Wind Harmer
0.629
962251AG1-071 GEN
Solar/Wind Harmer
5.679
276686W4-005 GEN3
Solar/Wind Harmer
2.731
270356AE2-297 GEN
Solar/Wind Harmer
4.106
274760LEE CO EC;1U
Adder
8.237
972236AH1-702 GEN2
Adder
1.934
238148AE2-230_GEN2
Solar/Wind Helper
0.424
24290705CLAY-2
50/50
0.255
24290705CLAY-2
50/50
0.255
24684505SMG3
50/50
1.376
971277AH1-098 GEN
Solar/Wind Harmer
7.425
24728205BUCHG1
Adder
6.757
944971AF1-162 GEN
Solar/Wind Harmer
9.08
942751AE2-291 GEN
Solar/Wind Harmer
10.387
966021AG1-471 GEN
Solar/Wind Harmer
5.761
339231AF1-038_GEN
Solar/Wind Harmer
1.921
339255AE2-071 GEN
Solar/Wind Harmer
1.1
970653AG2-424 GEN
Solar/Wind Harmer
4.888
970653AG2-424 GEN
Solar/Wind Harmer
1.767
964571AG1-320 GEN
Solar/Wind Harmer
8.199
972045AH1-571 GEN
Solar/Wind Harmer
1.983
339221AD2-048_GEN
Solar/Wind Harmer
1.517
252509AD1-136 GEN
Solar/Wind Harmer
0.239
25183208HLCRTG
Solar/Wind Harmer
5.594
971073AG2-665 GEN
Solar/Wind Harmer
5.67
971073AG2-665 GEN
Solar/Wind Harmer
3.956
25194508D.CRK3
Adder
1.3
276911AD2-131_GEN
Solar/Wind Harmer
3.878
24728805RICHG1
Adder
3.391
274765LEE CO EC;6U
Adder
8.257
274763LEE CO EC;4U
Adder
8.16
274695ROCKY RD ;2P
Adder
9.746
966871AG1-558 GEN
Solar/Wind Helper
0.306
970479AG2-310 GEN
50/50
20.262
270205AE1-176
50/50
0.006
966251AG1-494 GEN
50/50
4.389
24728405LEESVG
50/50
0.297
971367AH1-164 GEN
Solar/Wind Harmer
7.006
941821AE2-187 GEN
Solar/Wind Harmer
9.814
270197AD1-017 GEN1
Solar/Wind Harmer
2.547
270336AE1-100 GEN
Solar/Wind Harmer
2.759
943811AF1-049 GEN
Solar/Wind Harmer
5.698
24735205WLF2G2
Adder
8.031
24723205RIVRG3
Adder
22.989
24686105CER G3
Adder
9.903
24721705FLATG2
Adder
21.725
970947AG2-589 GEN
Solar/Wind Harmer
2.143
971821AH1-427 GEN
Solar/Wind Harmer
10.363
964901AG1-354 GEN
Solar/Wind Harmer
15.523
339241AF1-083 GEN
Solar/Wind Harmer
1.717
943111AE2-339 GEN
Solar/Wind Harmer
0.884
945681AF1-233 GEN
Solar/Wind Harmer
18.356
270445AC2-157 GEN2
Solar/Wind Harmer
5.249
25194608D.CRK4
Adder
1.511
253432AC1-085 GEN2
Solar/Wind Harmer
0.243
946171AF1-282 GEN
Solar/Wind Harmer
9.095
24728605AND G2
Adder
3.486
274828WAUKEGAN ;BP
Adder
9.674
274682WAUKEGAN ;7U
Adder
15.734
274745AC1-111 GEN9
Adder
4.879
253370AE2-315 SEC1
Adder
1.744
253371AE2-315 SEC2
Adder
1.649
316499AE2-029_GEN
Solar/Wind Helper
1.725
316095T157 G97
Solar/Wind Helper
1.128
966881AG1-559 GEN
Solar/Wind Helper
0.314
316473AC1-191 GEN
Solar/Wind Helper
1.388
24290605CLAY-1
50/50
0.255
24290605CLAY-1
50/50
0.255
24684405SMG2
50/50
2.225
316217AC1-145 GEN
Solar/Wind Harmer
4.248
316197AC1-042 GEN
Solar/Wind Harmer
3.22
942671AE2-283 GEN
Solar/Wind Harmer
8.669
971485AH1-239 GEN
Solar/Wind Harmer
8.509
964781AG1-341 GEN
Solar/Wind Harmer
10.986
971081AG2-670 GEN
Solar/Wind Harmer
7.746
942891AE2-308 GEN
Solar/Wind Harmer
10.193
972043AH1-570 GEN
Solar/Wind Harmer
2.479
25194408D.CRK1
Adder
6.953
945391AF1-204 GEN
Solar/Wind Harmer
12.742
24728905RICHG2
Adder
3.391
972267AH1-718 GEN
Adder
3.695
274764LEE CO EC;5U
Adder
8.257
274683WAUKEGAN ;8U
Adder
18.455
274683WAUKEGAN ;8U
Adder
15.556
274693ROCKY RD ;1P
Adder
9.65
3132123MT JACKSON
Solar/Wind Helper
1.39
966001AG1-469 GEN
Solar/Wind Helper
0.32
24415905BUCK
50/50
0.034
971329AH1-144 GEN
Solar/Wind Harmer
23.701
958131AF2-107 GEN
Solar/Wind Harmer
7.109
971403AH1-188 GEN
Solar/Wind Harmer
18.877
970273AG2-179 GEN
Solar/Wind Harmer
2.585
960001AF2-291 GEN
Solar/Wind Harmer
3.12
3429421JKCT 10G
Adder
8.417
971565AH1-281 GEN
Solar/Wind Harmer
2.004
927014AC1-188 GEN
Solar/Wind Harmer
1.535
970091AG2-072 GEN
Adder
74.149
963741AG1-226 GEN
Solar/Wind Harmer
40.444
274822ROCKFORD ;11
Adder
17.308
3132273ORANGE
Solar/Wind Helper
0.056
316170AC1-121 GEN2
Solar/Wind Helper
0.387
316313AB2-026
Solar/Wind Helper
0.354
253372AE2-315 SEC3
Adder
1.649
3148463FAIRFLD
Solar/Wind Helper
0.726
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
966391AG1-508 GEN
Solar/Wind Harmer
6.379
270069AE2-166 C O1
Solar/Wind Harmer
4.509
24734705WLF1G3
Adder
8.202
24734905WLF1G5
Adder
8.202
270399AC1-101 GEN
Solar/Wind Harmer
5.563
972143AH1-644 GEN
Solar/Wind Harmer
12.933
971981AH1-535 GEN
Solar/Wind Harmer
12.575
270330AC1-082 GEN2
Solar/Wind Harmer
0.826
965401AG1-405 GEN
Solar/Wind Harmer
6.068
24734805WLF1G4
Adder
8.202
24735105WLF2G1
Adder
8.031
270400AC1-102 GEN
Solar/Wind Harmer
5.563
941621AE2-160 GEN
Adder
4.292
957241AF2-018 GEN
Solar/Wind Harmer
5.764
24477305BRIDGE
Adder
0.42
270329AC1-082 GEN1
Solar/Wind Harmer
0.486
3429211JKCT 2G
Adder
11.894
970455AG2-298 GEN
Solar/Wind Harmer
6.044
339243AC2-075 GEN1
Solar/Wind Harmer
0.447
972163AH1-664 GEN
Solar/Wind Harmer
9.762
944221AF1-090 GEN
Solar/Wind Harmer
10.042
25196508WSDLE4
Adder
7.785
274746AC1-111 G10
Adder
4.879
23546401DTGZ2-030
Solar/Wind Helper
0.079
316164AC1-076 GEN
Solar/Wind Helper
1.173
238152AF2-075_GEN
Solar/Wind Helper
0.603
339211AE2-254 GEN
Solar/Wind Harmer
1.566
972165AH1-665 GEN
Solar/Wind Harmer
7.81
971985AH1-537 GEN
Solar/Wind Harmer
17.332
274823ROCKFORD ;21
Adder
17.182
3148013FISHERV
Solar/Wind Helper
0.3
24288905REUSENS
50/50
0.057
24684605SMG4
50/50
2.239
24728305BUCHG2
Adder
6.757
270018AE2-047 C O1
Solar/Wind Harmer
1.826
24686505CER G6
Adder
9.89
962241AG1-070 GEN
Solar/Wind Harmer
4.647
3429241JKCT 3G
Adder
12.05
339216AC1-074 GEN
Solar/Wind Harmer
1.652
252507AC2-088 GEN
Solar/Wind Harmer
1.673
965911AG1-460 GEN
Solar/Wind Harmer
1.273
276615X2-022 GEN
Solar/Wind Harmer
1.776
963831AG1-236 GEN
Solar/Wind Harmer
8.893
274766LEE CO EC;7U
Adder
8.14
972235AH1-702 GEN1
Adder
2.224
315616AA1-038_C
Solar/Wind Helper
3.294
3148013FISHERV
Solar/Wind Helper
0.523
3147666LOUISA
Solar/Wind Helper
0.626
238147AE2-230_GEN1
Solar/Wind Helper
0.422
316405AF2-144 C
Solar/Wind Helper
0.266
316044AC1-158 PL1
Solar/Wind Helper
1.259
316450AC1-158 RIC
Solar/Wind Helper
0.336
270583AD2-179 GEN
Solar/Wind Harmer
20.732
270214AC2-123 GEN
Solar/Wind Harmer
4.313
971225AH1-072 GEN
Solar/Wind Harmer
2.733
971227AH1-073 GEN
Solar/Wind Harmer
2.733
24723005RIVRG1
Adder
22.989
24723105RIVRG2
Adder
22.989
24685805CER G1
Adder
9.838
24685905CER G2
Adder
9.838
971125AH1-004 GEN
Solar/Wind Harmer
3.987
270444AC2-157 GEN1
Solar/Wind Harmer
5.249
252519AF1-045_GEN
Solar/Wind Harmer
5.601
252516AE2-318_GEN
Solar/Wind Harmer
4.272
276916AD2-100_GEN
Solar/Wind Harmer
19.19
957381AF2-032 GEN
Solar/Wind Harmer
0.382
253317AC1-085 GEN4
Solar/Wind Harmer
7.618
276763AC1-053 GEN1
Solar/Wind Harmer
3.575
276764AC1-053 GEN2
Solar/Wind Harmer
3.575
253370AE2-315 SEC1
Adder
1.744
315651AD1-115 GEN
Solar/Wind Helper
0.839
316447AC1-158 HLD
Solar/Wind Helper
2.77
971543AH1-269 GEN
50/50
12.253
971313AH1-133 GEN
Solar/Wind Harmer
15.712
270132AB1-180 C
Adder
0.169
971061AG2-657 GEN
Solar/Wind Harmer
11.012
965411AG1-406 GEN
Solar/Wind Harmer
2.724
270367AC2-061_GEN
Solar/Wind Harmer
3.015
316123AC1-075 GEN
Solar/Wind Harmer
1.493
25196108MFTGT2
Adder
1.428
25196108MFTGT2
Adder
1.326
970879AG2-548 GEN
Solar/Wind Harmer
3.956
25196408WSDLE3
Adder
8.097
25196308WSDLE2
Adder
8.027
25196208WSDLE1
Adder
8.006
25196708WSDLE6
Adder
7.986
276174W4-005 GEN2
Solar/Wind Harmer
2.731
3148133STUARTS
Solar/Wind Helper
0.314
24684305SMG1
50/50
0.806
270013AE1-250 PV
Solar/Wind Harmer
3.257
960161AF2-307 GEN
Solar/Wind Harmer
6.669
339236AF1-050_GEN
Solar/Wind Harmer
1.875
970107AG2-081 GEN
Solar/Wind Harmer
2.99
970235AG2-159 GEN
Solar/Wind Harmer
3.885
970235AG2-159 GEN
Solar/Wind Harmer
2.372
270186AC1-089 GEN
Solar/Wind Harmer
5.836
970239AG2-162 GEN
Solar/Wind Harmer
10.492
962581AG1-107 GEN
Solar/Wind Harmer
4.741
961491AF2-440 GEN
Solar/Wind Harmer
1.97
970879AG2-548 GEN
Solar/Wind Harmer
5.67
970241AG2-163 GEN
Solar/Wind Harmer
22.469
274762LEE CO EC;3U
Adder
8.237
274696ROCKY RD ;4P
Adder
9.976
274697ROCKY RD ;3P
Adder
2.648
315821AE2-092 GEN
Solar/Wind Helper
3.218
316468AD1-105 GEN
Solar/Wind Helper
1.126
276668AB2-070 GEN1
Solar/Wind Harmer
2.031
274767LEE CO EC;8U
Adder
8.14
274682WAUKEGAN ;7U
Adder
15.734
253370AE2-315 SEC1
Adder
1.744
253371AE2-315 SEC2
Adder
1.649
316192AB2-158 GEN
Solar/Wind Helper
1.84
316097T157 G90
Solar/Wind Helper
1.128
316336AC2-165 C
Solar/Wind Helper
1.286
970563AG2-360 GEN
50/50
45.869
962751AG1-124 GEN
Solar/Wind Harmer
18.829
3147312GRETNA
Solar/Wind Harmer
-0.021
3146802CHATHAM
Solar/Wind Harmer
-0.02
270016AE1-250 BESS
Solar/Wind Harmer
3.257
972273AH1-721 GEN
Adder
89.448
966571AG1-526 GEN
Solar/Wind Harmer
22.923
970093AG2-073 GEN
Solar/Wind Harmer
10.289
971191AH1-055 GEN
Solar/Wind Harmer
22.23
972167AH1-666 GEN
Solar/Wind Harmer
7.783
970243AG2-164 GEN
Solar/Wind Harmer
24.633
25196008MFTGT1
Adder
1.255
252510AF1-249 C
Solar/Wind Harmer
0.385
942481AE2-261 GEN
Solar/Wind Harmer
27.279
276621W2-048 GEN
Solar/Wind Harmer
5.656
276838X2-022 GEN2
Solar/Wind Harmer
0.211
971993AH1-541 GEN
Solar/Wind Harmer
8.344
274729ELWOOD EC;1P
Adder
1.681
3147983MERCK5
Solar/Wind Helper
0.198
316006AB2-029 C
Solar/Wind Helper
0.113
316045AC1-158 PL2
Solar/Wind Helper
4.029
944201AF1-088_MTX
Adder
109.291
957141AF2-008_MTX
Adder
54.646
NYPJM->LTFIMP_NY
CLTF
3.255
LGEELTFEXP_LGEE->PJM
CLTF
6.775
WECLTFEXP_WEC->PJM
CLTF
3.378
AG2-052LTFEXP_AG2-052->PJM
LTF
0.202
AH1-155LTFEXP_AH1-155->PJM
LTF
0.303
LAGNLTFEXP_LAGN->PJM
CLTF
20.308
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.574
TVALTFEXP_TVA->PJM
CLTF
10.62
CPLELTFEXP_CPLE->PJM
CLTF
6.229
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.312
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.655
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.369
MECLTFEXP_MEC->PJM
CLTF
15.442
SIGELTFEXP_SIGE->PJM
CLTF
0.509

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AEP_P4_#37_05MOUNTN 765_B1_SRT-A


Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#37_05MOUNTN 765_B1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.68 %
Rating:3610.0 MVA
Rating Type:B
MVA to Mitigate:4211.98
MW Contribution:7.0
Bus #Bus NameTypeMW Contribution
970823AG2-518 GEN
50/50
8.384
247619Y1-049
50/50
0.913
24416005BYLLESBY
50/50
0.031
958121AF2-106 GEN
Solar/Wind Harmer
9.407
971331AH1-145 GEN
Solar/Wind Harmer
18.361
270346AE1-212 GEN
Solar/Wind Harmer
13.936
971461AH1-227 GEN
Solar/Wind Harmer
7.003
3147312GRETNA
Solar/Wind Harmer
-0.005
971687AH1-348 GEN
Solar/Wind Harmer
1.359
971315AH1-136 GEN
Solar/Wind Harmer
2.43
270331AC1-082 GEN3
Solar/Wind Harmer
0.487
970333AG2-219 GEN
Solar/Wind Harmer
30.05
25196808ZIMRHP
Adder
70.616
25196008MFTGT1
Adder
1.293
274880W4-005 GEN4
Solar/Wind Harmer
2.726
274761LEE CO EC;2U
Adder
8.222
237061AD1-155 GEN
Solar/Wind Helper
0.05
23583801GRNGAP
Solar/Wind Helper
4.287
24290705CLAY-2
50/50
0.255
24290705CLAY-2
50/50
0.255
24684505SMG3
50/50
1.376
971277AH1-098 GEN
Solar/Wind Harmer
7.42
24728205BUCHG1
Adder
6.75
944971AF1-162 GEN
Solar/Wind Harmer
9.068
942751AE2-291 GEN
Solar/Wind Harmer
10.385
966021AG1-471 GEN
Solar/Wind Harmer
5.753
339231AF1-038_GEN
Solar/Wind Harmer
1.918
339255AE2-071 GEN
Solar/Wind Harmer
1.099
970653AG2-424 GEN
Solar/Wind Harmer
4.88
970653AG2-424 GEN
Solar/Wind Harmer
1.764
964571AG1-320 GEN
Solar/Wind Harmer
8.186
972045AH1-571 GEN
Solar/Wind Harmer
1.98
339221AD2-048_GEN
Solar/Wind Harmer
1.514
252509AD1-136 GEN
Solar/Wind Harmer
0.238
25183208HLCRTG
Solar/Wind Harmer
5.582
25194508D.CRK3
Adder
1.297
971073AG2-665 GEN
Solar/Wind Harmer
5.656
971073AG2-665 GEN
Solar/Wind Harmer
3.946
276911AD2-131_GEN
Solar/Wind Harmer
3.871
24728805RICHG1
Adder
3.384
274765LEE CO EC;6U
Adder
8.241
274763LEE CO EC;4U
Adder
8.144
274695ROCKY RD ;2P
Adder
9.727
966871AG1-558 GEN
Solar/Wind Helper
0.306
970479AG2-310 GEN
50/50
20.255
270205AE1-176
50/50
0.006
966251AG1-494 GEN
50/50
4.388
24728405LEESVG
50/50
0.297
971367AH1-164 GEN
Solar/Wind Harmer
7.003
941821AE2-187 GEN
Solar/Wind Harmer
9.812
270197AD1-017 GEN1
Solar/Wind Harmer
2.546
270336AE1-100 GEN
Solar/Wind Harmer
2.757
943811AF1-049 GEN
Solar/Wind Harmer
5.695
970223AG2-152 GEN
Solar/Wind Harmer
17.623
24686205CER G4
Adder
9.835
3429391JKCT 9G
Adder
8.402
957541AF2-048 GEN
Solar/Wind Harmer
1.528
958171AF2-111 GEN
Solar/Wind Harmer
23.91
970519AG2-331 GEN
Solar/Wind Harmer
16.518
970699AG2-449 GEN
Solar/Wind Harmer
10.927
25196608WSDLE5
Adder
7.849
970193AG2-126 GEN
Solar/Wind Harmer
13.689
24728705AND G3
Adder
7.277
253406AD2-031_GEN
Solar/Wind Harmer
1.149
3147666LOUISA
Solar/Wind Helper
1.088
316254AC1-120 GEN1
Solar/Wind Helper
1.159
24290605CLAY-1
50/50
0.255
24290605CLAY-1
50/50
0.255
24684405SMG2
50/50
2.224
316217AC1-145 GEN
Solar/Wind Harmer
4.247
316197AC1-042 GEN
Solar/Wind Harmer
3.219
942671AE2-283 GEN
Solar/Wind Harmer
8.667
971485AH1-239 GEN
Solar/Wind Harmer
8.497
964781AG1-341 GEN
Solar/Wind Harmer
10.97
971081AG2-670 GEN
Solar/Wind Harmer
7.734
942891AE2-308 GEN
Solar/Wind Harmer
10.176
972043AH1-570 GEN
Solar/Wind Harmer
2.475
24415905BUCK
50/50
0.034
971329AH1-144 GEN
Solar/Wind Harmer
23.686
958131AF2-107 GEN
Solar/Wind Harmer
7.108
971403AH1-188 GEN
Solar/Wind Harmer
18.852
970273AG2-179 GEN
Solar/Wind Harmer
2.581
960001AF2-291 GEN
Solar/Wind Harmer
3.113
3429421JKCT 10G
Adder
8.402
971565AH1-281 GEN
Solar/Wind Harmer
2.001
927014AC1-188 GEN
Solar/Wind Harmer
1.532
970091AG2-072 GEN
Adder
74.012
963741AG1-226 GEN
Solar/Wind Harmer
40.366
274822ROCKFORD ;11
Adder
17.275
3132273ORANGE
Solar/Wind Helper
0.056
316170AC1-121 GEN2
Solar/Wind Helper
0.386
316313AB2-026
Solar/Wind Helper
0.354
24735205WLF2G2
Adder
8.023
24723205RIVRG3
Adder
22.954
24686105CER G3
Adder
9.887
24721705FLATG2
Adder
21.686
970947AG2-589 GEN
Solar/Wind Harmer
2.139
971821AH1-427 GEN
Solar/Wind Harmer
10.346
964901AG1-354 GEN
Solar/Wind Harmer
15.5
339241AF1-083 GEN
Solar/Wind Harmer
1.715
943111AE2-339 GEN
Solar/Wind Harmer
0.883
945681AF1-233 GEN
Solar/Wind Harmer
18.32
270445AC2-157 GEN2
Solar/Wind Harmer
5.239
25194608D.CRK4
Adder
1.508
253432AC1-085 GEN2
Solar/Wind Harmer
0.243
946171AF1-282 GEN
Solar/Wind Harmer
9.075
24728605AND G2
Adder
3.48
274828WAUKEGAN ;BP
Adder
9.655
274682WAUKEGAN ;7U
Adder
15.703
274745AC1-111 GEN9
Adder
4.87
316499AE2-029_GEN
Solar/Wind Helper
1.725
316095T157 G97
Solar/Wind Helper
1.125
966881AG1-559 GEN
Solar/Wind Helper
0.313
316473AC1-191 GEN
Solar/Wind Helper
1.387
970281AG2-184 GEN
Solar/Wind Harmer
27.126
962211AG1-066 GEN
Solar/Wind Harmer
3.001
972203AH1-686 GEN
Adder
2.704
970165AG2-112 GEN
Solar/Wind Harmer
1.315
970163AG2-111 GEN
Solar/Wind Harmer
1.254
252524AE2-267 GEN
Solar/Wind Harmer
1.444
276785W4-005 GEN1
Solar/Wind Harmer
2.726
276849AB2-070 GEN2
Solar/Wind Harmer
2.027
276848AB2-070 GEN3
Solar/Wind Harmer
2.027
274744AC1-111 GEN8
Adder
4.87
25306009OHH W.
Adder
2.505
3148463FAIRFLD
Solar/Wind Helper
0.726
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
25194408D.CRK1
Adder
6.938
945391AF1-204 GEN
Solar/Wind Harmer
12.718
24728905RICHG2
Adder
3.384
972267AH1-718 GEN
Adder
3.688
274764LEE CO EC;5U
Adder
8.241
274683WAUKEGAN ;8U
Adder
18.419
274683WAUKEGAN ;8U
Adder
15.526
274693ROCKY RD ;1P
Adder
9.632
3132123MT JACKSON
Solar/Wind Helper
1.389
966001AG1-469 GEN
Solar/Wind Helper
0.32
966391AG1-508 GEN
Solar/Wind Harmer
6.374
270069AE2-166 C O1
Solar/Wind Harmer
4.507
24734705WLF1G3
Adder
8.194
24734905WLF1G5
Adder
8.194
270399AC1-101 GEN
Solar/Wind Harmer
5.556
972143AH1-644 GEN
Solar/Wind Harmer
12.917
971981AH1-535 GEN
Solar/Wind Harmer
12.563
270330AC1-082 GEN2
Solar/Wind Harmer
0.824
965401AG1-405 GEN
Solar/Wind Harmer
6.059
339211AE2-254 GEN
Solar/Wind Harmer
1.563
972165AH1-665 GEN
Solar/Wind Harmer
7.794
971985AH1-537 GEN
Solar/Wind Harmer
17.295
274823ROCKFORD ;21
Adder
17.15
3148013FISHERV
Solar/Wind Helper
0.3
24288905REUSENS
50/50
0.057
24684605SMG4
50/50
2.239
24728305BUCHG2
Adder
6.75
270018AE2-047 C O1
Solar/Wind Harmer
1.826
24686505CER G6
Adder
9.874
962241AG1-070 GEN
Solar/Wind Harmer
4.64
3429241JKCT 3G
Adder
12.029
339216AC1-074 GEN
Solar/Wind Harmer
1.649
252507AC2-088 GEN
Solar/Wind Harmer
1.669
965911AG1-460 GEN
Solar/Wind Harmer
1.271
276615X2-022 GEN
Solar/Wind Harmer
1.772
963831AG1-236 GEN
Solar/Wind Harmer
8.877
274766LEE CO EC;7U
Adder
8.125
972235AH1-702 GEN1
Adder
2.22
315616AA1-038_C
Solar/Wind Helper
3.293
3148013FISHERV
Solar/Wind Helper
0.523
3147666LOUISA
Solar/Wind Helper
0.625
238147AE2-230_GEN1
Solar/Wind Helper
0.421
316405AF2-144 C
Solar/Wind Helper
0.265
316044AC1-158 PL1
Solar/Wind Helper
1.257
316450AC1-158 RIC
Solar/Wind Helper
0.335
270583AD2-179 GEN
Solar/Wind Harmer
20.721
270214AC2-123 GEN
Solar/Wind Harmer
4.311
971225AH1-072 GEN
Solar/Wind Harmer
2.73
971227AH1-073 GEN
Solar/Wind Harmer
2.73
24723005RIVRG1
Adder
22.954
24723105RIVRG2
Adder
22.954
24685805CER G1
Adder
9.822
24685905CER G2
Adder
9.822
971125AH1-004 GEN
Solar/Wind Harmer
3.98
270444AC2-157 GEN1
Solar/Wind Harmer
5.239
252519AF1-045_GEN
Solar/Wind Harmer
5.589
252516AE2-318_GEN
Solar/Wind Harmer
4.263
276916AD2-100_GEN
Solar/Wind Harmer
19.154
957381AF2-032 GEN
Solar/Wind Harmer
0.381
253317AC1-085 GEN4
Solar/Wind Harmer
7.601
276763AC1-053 GEN1
Solar/Wind Harmer
3.568
276764AC1-053 GEN2
Solar/Wind Harmer
3.568
315651AD1-115 GEN
Solar/Wind Helper
0.837
316447AC1-158 HLD
Solar/Wind Helper
2.766
971543AH1-269 GEN
50/50
12.247
971313AH1-133 GEN
Solar/Wind Harmer
15.698
270132AB1-180 C
Adder
0.169
971061AG2-657 GEN
Solar/Wind Harmer
10.991
965411AG1-406 GEN
Solar/Wind Harmer
2.719
270367AC2-061_GEN
Solar/Wind Harmer
3.009
316123AC1-075 GEN
Solar/Wind Harmer
1.493
25196108MFTGT2
Adder
1.425
25196108MFTGT2
Adder
1.324
970879AG2-548 GEN
Solar/Wind Harmer
3.946
25196408WSDLE3
Adder
8.08
25196308WSDLE2
Adder
8.01
25196208WSDLE1
Adder
7.99
25196708WSDLE6
Adder
7.97
276174W4-005 GEN2
Solar/Wind Harmer
2.726
3148133STUARTS
Solar/Wind Helper
0.313
24684305SMG1
50/50
0.806
270013AE1-250 PV
Solar/Wind Harmer
3.256
960161AF2-307 GEN
Solar/Wind Harmer
6.658
339236AF1-050_GEN
Solar/Wind Harmer
1.872
970107AG2-081 GEN
Solar/Wind Harmer
2.985
970235AG2-159 GEN
Solar/Wind Harmer
3.878
970235AG2-159 GEN
Solar/Wind Harmer
2.367
270186AC1-089 GEN
Solar/Wind Harmer
5.824
970239AG2-162 GEN
Solar/Wind Harmer
10.472
962581AG1-107 GEN
Solar/Wind Harmer
4.731
961491AF2-440 GEN
Solar/Wind Harmer
1.966
970879AG2-548 GEN
Solar/Wind Harmer
5.656
970241AG2-163 GEN
Solar/Wind Harmer
22.426
274762LEE CO EC;3U
Adder
8.222
274696ROCKY RD ;4P
Adder
9.957
274697ROCKY RD ;3P
Adder
2.642
315821AE2-092 GEN
Solar/Wind Helper
3.216
316468AD1-105 GEN
Solar/Wind Helper
1.124
238149AF1-291A_GEN
Solar/Wind Helper
0.12
316258AE1-075 C
Solar/Wind Helper
0.319
972175AH1-670 GEN
Solar/Wind Harmer
4.72
970481AG2-311 GEN
50/50
11.937
24728405LEESVG
50/50
0.295
943031AE2-326 GEN
Solar/Wind Harmer
6.784
270574AD1-017 GEN2
Solar/Wind Harmer
8.473
3147123OTTER R
Solar/Wind Harmer
-0.014
270030AE2-140 GEN
Solar/Wind Harmer
30.929
960911AF2-382 GEN
Solar/Wind Harmer
10.948
972103AH1-617 GEN
Solar/Wind Harmer
25.835
24721905FLATG4
Adder
21.686
971155AH1-034 GEN
Solar/Wind Harmer
10.354
960741AF2-365 GEN
Solar/Wind Harmer
5.107
25194608D.CRK4
Adder
1.508
253316AC1-085 GEN3
Solar/Wind Harmer
7.601
253433AC1-085 GEN1
Solar/Wind Harmer
4.825
946181AF1-283 GEN
Solar/Wind Harmer
11.797
24728505AND G1
Adder
3.48
276668AB2-070 GEN1
Solar/Wind Harmer
2.027
274767LEE CO EC;8U
Adder
8.125
274682WAUKEGAN ;7U
Adder
15.703
316192AB2-158 GEN
Solar/Wind Helper
1.838
316097T157 G90
Solar/Wind Helper
1.125
316336AC2-165 C
Solar/Wind Helper
1.285
970563AG2-360 GEN
50/50
45.829
962751AG1-124 GEN
Solar/Wind Harmer
18.825
3147312GRETNA
Solar/Wind Harmer
-0.021
3146802CHATHAM
Solar/Wind Harmer
-0.02
270016AE1-250 BESS
Solar/Wind Harmer
3.256
972273AH1-721 GEN
Adder
89.316
966571AG1-526 GEN
Solar/Wind Harmer
22.886
970093AG2-073 GEN
Solar/Wind Harmer
10.271
971191AH1-055 GEN
Solar/Wind Harmer
22.182
972167AH1-666 GEN
Solar/Wind Harmer
7.768
970243AG2-164 GEN
Solar/Wind Harmer
24.587
25196008MFTGT1
Adder
1.252
252510AF1-249 C
Solar/Wind Harmer
0.384
942481AE2-261 GEN
Solar/Wind Harmer
27.229
276621W2-048 GEN
Solar/Wind Harmer
5.645
276838X2-022 GEN2
Solar/Wind Harmer
0.211
971993AH1-541 GEN
Solar/Wind Harmer
8.328
274729ELWOOD EC;1P
Adder
13.481
3147983MERCK5
Solar/Wind Helper
0.198
24734805WLF1G4
Adder
8.194
24735105WLF2G1
Adder
8.023
270400AC1-102 GEN
Solar/Wind Harmer
5.556
941621AE2-160 GEN
Adder
4.285
957241AF2-018 GEN
Solar/Wind Harmer
5.757
24477305BRIDGE
Adder
0.419
270329AC1-082 GEN1
Solar/Wind Harmer
0.485
3429211JKCT 2G
Adder
11.873
970455AG2-298 GEN
Solar/Wind Harmer
6.034
339243AC2-075 GEN1
Solar/Wind Harmer
0.446
972163AH1-664 GEN
Solar/Wind Harmer
9.743
944221AF1-090 GEN
Solar/Wind Harmer
10.024
25196508WSDLE4
Adder
7.769
274746AC1-111 G10
Adder
4.87
23546401DTGZ2-030
Solar/Wind Helper
0.078
316164AC1-076 GEN
Solar/Wind Helper
1.172
238152AF2-075_GEN
Solar/Wind Helper
0.602
24684705SMG5
50/50
0.856
3151561HALLBR1
50/50
0.57
270173AC1-122 GEN
Solar/Wind Harmer
3.278
941801AE2-185 GEN
Solar/Wind Harmer
9.812
970913AG2-568 GEN
Solar/Wind Harmer
11.004
270053AF1-130 C
Solar/Wind Harmer
4.815
24686405CER G5
Adder
9.796
970273AG2-179 GEN
Solar/Wind Harmer
4.123
339250AF1-203 GEN
Solar/Wind Harmer
0.628
962251AG1-071 GEN
Solar/Wind Harmer
5.671
276686W4-005 GEN3
Solar/Wind Harmer
2.726
270356AE2-297 GEN
Solar/Wind Harmer
4.098
274760LEE CO EC;1U
Adder
8.222
972236AH1-702 GEN2
Adder
1.93
238148AE2-230_GEN2
Solar/Wind Helper
0.423
316006AB2-029 C
Solar/Wind Helper
0.112
316045AC1-158 PL2
Solar/Wind Helper
4.023
944201AF1-088_MTX
Adder
109.09
957141AF2-008_MTX
Adder
54.545
NYPJM->LTFIMP_NY
CLTF
3.248
LGEELTFEXP_LGEE->PJM
CLTF
6.763
WECLTFEXP_WEC->PJM
CLTF
3.371
AG2-052LTFEXP_AG2-052->PJM
LTF
0.202
AH1-155LTFEXP_AH1-155->PJM
LTF
0.303
LAGNLTFEXP_LAGN->PJM
CLTF
20.28
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.555
TVALTFEXP_TVA->PJM
CLTF
10.606
CPLELTFEXP_CPLE->PJM
CLTF
6.226
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.111
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.415
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.315
MECLTFEXP_MEC->PJM
CLTF
15.415
SIGELTFEXP_SIGE->PJM
CLTF
0.508

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AEP_P4_#2942_05KAMMER 765_PP_SRT-A


Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2942_05KAMMER 765_PP_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.36 %
Rating:3610.0 MVA
Rating Type:B
MVA to Mitigate:4200.43
MW Contribution:7.0
Bus #Bus NameTypeMW Contribution
24290705CLAY-2
50/50
0.255
24290705CLAY-2
50/50
0.255
24684505SMG3
50/50
1.376
971277AH1-098 GEN
Solar/Wind Harmer
7.423
24728205BUCHG1
Adder
6.753
944971AF1-162 GEN
Solar/Wind Harmer
9.072
942751AE2-291 GEN
Solar/Wind Harmer
10.391
966021AG1-471 GEN
Solar/Wind Harmer
5.756
339231AF1-038_GEN
Solar/Wind Harmer
1.919
339255AE2-071 GEN
Solar/Wind Harmer
1.099
970653AG2-424 GEN
Solar/Wind Harmer
4.883
970653AG2-424 GEN
Solar/Wind Harmer
1.765
964571AG1-320 GEN
Solar/Wind Harmer
8.191
972045AH1-571 GEN
Solar/Wind Harmer
1.981
339221AD2-048_GEN
Solar/Wind Harmer
1.515
252509AD1-136 GEN
Solar/Wind Harmer
0.239
24415905BUCK
50/50
0.034
971329AH1-144 GEN
Solar/Wind Harmer
23.694
958131AF2-107 GEN
Solar/Wind Harmer
7.111
971403AH1-188 GEN
Solar/Wind Harmer
18.861
970273AG2-179 GEN
Solar/Wind Harmer
2.583
960001AF2-291 GEN
Solar/Wind Harmer
3.115
3429421JKCT 10G
Adder
8.407
971565AH1-281 GEN
Solar/Wind Harmer
2.002
927014AC1-188 GEN
Solar/Wind Harmer
1.533
970091AG2-072 GEN
Adder
74.061
963741AG1-226 GEN
Solar/Wind Harmer
40.395
274822ROCKFORD ;11
Adder
17.288
3132273ORANGE
Solar/Wind Helper
0.056
316170AC1-121 GEN2
Solar/Wind Helper
0.386
316313AB2-026
Solar/Wind Helper
0.354
970479AG2-310 GEN
50/50
20.26
270205AE1-176
50/50
0.006
966251AG1-494 GEN
50/50
4.39
24728405LEESVG
50/50
0.297
971367AH1-164 GEN
Solar/Wind Harmer
7.005
941821AE2-187 GEN
Solar/Wind Harmer
9.815
270197AD1-017 GEN1
Solar/Wind Harmer
2.547
270336AE1-100 GEN
Solar/Wind Harmer
2.758
943811AF1-049 GEN
Solar/Wind Harmer
5.698
24735205WLF2G2
Adder
8.027
24723205RIVRG3
Adder
22.966
24686105CER G3
Adder
9.893
24721705FLATG2
Adder
21.699
970947AG2-589 GEN
Solar/Wind Harmer
2.14
971821AH1-427 GEN
Solar/Wind Harmer
10.353
964901AG1-354 GEN
Solar/Wind Harmer
15.509
339241AF1-083 GEN
Solar/Wind Harmer
1.716
943111AE2-339 GEN
Solar/Wind Harmer
0.883
945681AF1-233 GEN
Solar/Wind Harmer
18.332
270445AC2-157 GEN2
Solar/Wind Harmer
5.243
25194608D.CRK4
Adder
1.509
253432AC1-085 GEN2
Solar/Wind Harmer
0.243
946171AF1-282 GEN
Solar/Wind Harmer
9.081
24728605AND G2
Adder
3.482
274828WAUKEGAN ;BP
Adder
9.662
274682WAUKEGAN ;7U
Adder
15.715
274745AC1-111 GEN9
Adder
4.873
316499AE2-029_GEN
Solar/Wind Helper
1.724
316095T157 G97
Solar/Wind Helper
1.124
966881AG1-559 GEN
Solar/Wind Helper
0.313
316473AC1-191 GEN
Solar/Wind Helper
1.386
970281AG2-184 GEN
Solar/Wind Harmer
27.14
962211AG1-066 GEN
Solar/Wind Harmer
3.003
972203AH1-686 GEN
Adder
2.706
970165AG2-112 GEN
Solar/Wind Harmer
1.315
970163AG2-111 GEN
Solar/Wind Harmer
1.255
252524AE2-267 GEN
Solar/Wind Harmer
1.445
276849AB2-070 GEN2
Solar/Wind Harmer
2.029
276848AB2-070 GEN3
Solar/Wind Harmer
2.029
276785W4-005 GEN1
Solar/Wind Harmer
2.728
274744AC1-111 GEN8
Adder
4.873
25306009OHH W.
Adder
2.506
3148463FAIRFLD
Solar/Wind Helper
0.726
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
24290605CLAY-1
50/50
0.255
24290605CLAY-1
50/50
0.255
24684405SMG2
50/50
2.225
316217AC1-145 GEN
Solar/Wind Harmer
4.248
316197AC1-042 GEN
Solar/Wind Harmer
3.22
942671AE2-283 GEN
Solar/Wind Harmer
8.67
971485AH1-239 GEN
Solar/Wind Harmer
8.502
964781AG1-341 GEN
Solar/Wind Harmer
10.976
971081AG2-670 GEN
Solar/Wind Harmer
7.739
942891AE2-308 GEN
Solar/Wind Harmer
10.182
972043AH1-570 GEN
Solar/Wind Harmer
2.476
25194408D.CRK1
Adder
6.943
945391AF1-204 GEN
Solar/Wind Harmer
12.727
24728905RICHG2
Adder
3.386
972267AH1-718 GEN
Adder
3.691
274764LEE CO EC;5U
Adder
8.247
274683WAUKEGAN ;8U
Adder
18.432
274683WAUKEGAN ;8U
Adder
15.538
274693ROCKY RD ;1P
Adder
9.639
3132123MT JACKSON
Solar/Wind Helper
1.388
966001AG1-469 GEN
Solar/Wind Helper
0.32
966391AG1-508 GEN
Solar/Wind Harmer
6.377
270069AE2-166 C O1
Solar/Wind Harmer
4.508
24734705WLF1G3
Adder
8.198
24734905WLF1G5
Adder
8.198
270399AC1-101 GEN
Solar/Wind Harmer
5.558
972143AH1-644 GEN
Solar/Wind Harmer
12.924
971981AH1-535 GEN
Solar/Wind Harmer
12.569
270330AC1-082 GEN2
Solar/Wind Harmer
0.824
965401AG1-405 GEN
Solar/Wind Harmer
6.063
339211AE2-254 GEN
Solar/Wind Harmer
1.564
972165AH1-665 GEN
Solar/Wind Harmer
7.8
971985AH1-537 GEN
Solar/Wind Harmer
17.306
274823ROCKFORD ;21
Adder
17.162
3148013FISHERV
Solar/Wind Helper
0.3
24288905REUSENS
50/50
0.057
24684605SMG4
50/50
2.239
24728305BUCHG2
Adder
6.753
270018AE2-047 C O1
Solar/Wind Harmer
1.826
24686505CER G6
Adder
9.88
962241AG1-070 GEN
Solar/Wind Harmer
4.643
3429241JKCT 3G
Adder
12.037
339216AC1-074 GEN
Solar/Wind Harmer
1.65
252507AC2-088 GEN
Solar/Wind Harmer
1.671
965911AG1-460 GEN
Solar/Wind Harmer
1.272
276615X2-022 GEN
Solar/Wind Harmer
1.774
963831AG1-236 GEN
Solar/Wind Harmer
8.883
274766LEE CO EC;7U
Adder
8.131
972235AH1-702 GEN1
Adder
2.221
315616AA1-038_C
Solar/Wind Helper
3.292
3148013FISHERV
Solar/Wind Helper
0.522
3147666LOUISA
Solar/Wind Helper
0.625
238147AE2-230_GEN1
Solar/Wind Helper
0.421
316405AF2-144 C
Solar/Wind Helper
0.265
316044AC1-158 PL1
Solar/Wind Helper
1.256
316450AC1-158 RIC
Solar/Wind Helper
0.335
270583AD2-179 GEN
Solar/Wind Harmer
20.728
270214AC2-123 GEN
Solar/Wind Harmer
4.312
971225AH1-072 GEN
Solar/Wind Harmer
2.732
971227AH1-073 GEN
Solar/Wind Harmer
2.732
24723005RIVRG1
Adder
22.966
24723105RIVRG2
Adder
22.966
24685805CER G1
Adder
9.828
24685905CER G2
Adder
9.828
971125AH1-004 GEN
Solar/Wind Harmer
3.983
270444AC2-157 GEN1
Solar/Wind Harmer
5.243
252519AF1-045_GEN
Solar/Wind Harmer
5.593
252516AE2-318_GEN
Solar/Wind Harmer
4.266
276916AD2-100_GEN
Solar/Wind Harmer
19.168
957381AF2-032 GEN
Solar/Wind Harmer
0.381
253317AC1-085 GEN4
Solar/Wind Harmer
7.607
276763AC1-053 GEN1
Solar/Wind Harmer
3.571
276764AC1-053 GEN2
Solar/Wind Harmer
3.571
315651AD1-115 GEN
Solar/Wind Helper
0.837
316447AC1-158 HLD
Solar/Wind Helper
2.764
971543AH1-269 GEN
50/50
12.251
971313AH1-133 GEN
Solar/Wind Harmer
15.705
270132AB1-180 C
Adder
0.169
971061AG2-657 GEN
Solar/Wind Harmer
10.996
965411AG1-406 GEN
Solar/Wind Harmer
2.721
270367AC2-061_GEN
Solar/Wind Harmer
3.011
316123AC1-075 GEN
Solar/Wind Harmer
1.494
25196108MFTGT2
Adder
1.426
25196108MFTGT2
Adder
1.325
970879AG2-548 GEN
Solar/Wind Harmer
3.949
25196408WSDLE3
Adder
8.086
25196308WSDLE2
Adder
8.015
25196208WSDLE1
Adder
7.995
25196708WSDLE6
Adder
7.975
276174W4-005 GEN2
Solar/Wind Harmer
2.728
3148133STUARTS
Solar/Wind Helper
0.313
24684305SMG1
50/50
0.806
270013AE1-250 PV
Solar/Wind Harmer
3.257
960161AF2-307 GEN
Solar/Wind Harmer
6.662
339236AF1-050_GEN
Solar/Wind Harmer
1.873
970107AG2-081 GEN
Solar/Wind Harmer
2.987
970235AG2-159 GEN
Solar/Wind Harmer
3.88
970235AG2-159 GEN
Solar/Wind Harmer
2.369
270186AC1-089 GEN
Solar/Wind Harmer
5.828
970239AG2-162 GEN
Solar/Wind Harmer
10.479
962581AG1-107 GEN
Solar/Wind Harmer
4.734
961491AF2-440 GEN
Solar/Wind Harmer
1.967
970879AG2-548 GEN
Solar/Wind Harmer
5.66
970241AG2-163 GEN
Solar/Wind Harmer
22.442
274762LEE CO EC;3U
Adder
8.227
274696ROCKY RD ;4P
Adder
9.964
274697ROCKY RD ;3P
Adder
2.644
315821AE2-092 GEN
Solar/Wind Helper
3.215
316468AD1-105 GEN
Solar/Wind Helper
1.124
3147312GRETNA
Solar/Wind Harmer
-0.005
971687AH1-348 GEN
Solar/Wind Harmer
1.359
971315AH1-136 GEN
Solar/Wind Harmer
2.431
270331AC1-082 GEN3
Solar/Wind Harmer
0.487
970333AG2-219 GEN
Solar/Wind Harmer
30.071
25196808ZIMRHP
Adder
70.665
25196008MFTGT1
Adder
1.294
274880W4-005 GEN4
Solar/Wind Harmer
2.728
274761LEE CO EC;2U
Adder
8.227
970481AG2-311 GEN
50/50
11.941
24728405LEESVG
50/50
0.296
943031AE2-326 GEN
Solar/Wind Harmer
6.787
270574AD1-017 GEN2
Solar/Wind Harmer
8.476
3147123OTTER R
Solar/Wind Harmer
-0.014
270030AE2-140 GEN
Solar/Wind Harmer
30.942
960911AF2-382 GEN
Solar/Wind Harmer
10.952
972103AH1-617 GEN
Solar/Wind Harmer
25.847
24721905FLATG4
Adder
21.699
971155AH1-034 GEN
Solar/Wind Harmer
10.36
960741AF2-365 GEN
Solar/Wind Harmer
5.111
25194608D.CRK4
Adder
1.509
253316AC1-085 GEN3
Solar/Wind Harmer
7.607
253433AC1-085 GEN1
Solar/Wind Harmer
4.829
946181AF1-283 GEN
Solar/Wind Harmer
11.806
24728505AND G1
Adder
3.482
276668AB2-070 GEN1
Solar/Wind Harmer
2.029
274767LEE CO EC;8U
Adder
8.131
274682WAUKEGAN ;7U
Adder
15.715
316192AB2-158 GEN
Solar/Wind Helper
1.837
316097T157 G90
Solar/Wind Helper
1.124
316336AC2-165 C
Solar/Wind Helper
1.284
237061AD1-155 GEN
Solar/Wind Helper
0.05
23583801GRNGAP
Solar/Wind Helper
4.284
238149AF1-291A_GEN
Solar/Wind Helper
0.12
316258AE1-075 C
Solar/Wind Helper
0.318
972175AH1-670 GEN
Solar/Wind Harmer
4.723
970563AG2-360 GEN
50/50
45.847
962751AG1-124 GEN
Solar/Wind Harmer
18.831
3147312GRETNA
Solar/Wind Harmer
-0.021
3146802CHATHAM
Solar/Wind Harmer
-0.02
270016AE1-250 BESS
Solar/Wind Harmer
3.257
972273AH1-721 GEN
Adder
89.369
966571AG1-526 GEN
Solar/Wind Harmer
22.9
970093AG2-073 GEN
Solar/Wind Harmer
10.278
971191AH1-055 GEN
Solar/Wind Harmer
22.196
972167AH1-666 GEN
Solar/Wind Harmer
7.773
970243AG2-164 GEN
Solar/Wind Harmer
24.603
25196008MFTGT1
Adder
1.253
252510AF1-249 C
Solar/Wind Harmer
0.385
942481AE2-261 GEN
Solar/Wind Harmer
27.248
276621W2-048 GEN
Solar/Wind Harmer
5.649
276838X2-022 GEN2
Solar/Wind Harmer
0.211
971993AH1-541 GEN
Solar/Wind Harmer
8.334
274729ELWOOD EC;1P
Adder
13.491
3147983MERCK5
Solar/Wind Helper
0.198
24734805WLF1G4
Adder
8.198
24735105WLF2G1
Adder
8.027
270400AC1-102 GEN
Solar/Wind Harmer
5.558
941621AE2-160 GEN
Adder
4.287
957241AF2-018 GEN
Solar/Wind Harmer
5.759
24477305BRIDGE
Adder
0.419
270329AC1-082 GEN1
Solar/Wind Harmer
0.486
3429211JKCT 2G
Adder
11.881
970455AG2-298 GEN
Solar/Wind Harmer
6.038
339243AC2-075 GEN1
Solar/Wind Harmer
0.447
972163AH1-664 GEN
Solar/Wind Harmer
9.749
944221AF1-090 GEN
Solar/Wind Harmer
10.031
25196508WSDLE4
Adder
7.774
274746AC1-111 G10
Adder
4.873
23546401DTGZ2-030
Solar/Wind Helper
0.078
316164AC1-076 GEN
Solar/Wind Helper
1.171
238152AF2-075_GEN
Solar/Wind Helper
0.601
25183208HLCRTG
Solar/Wind Harmer
5.586
25194508D.CRK3
Adder
1.298
971073AG2-665 GEN
Solar/Wind Harmer
5.66
971073AG2-665 GEN
Solar/Wind Harmer
3.949
276911AD2-131_GEN
Solar/Wind Harmer
3.874
24728805RICHG1
Adder
3.386
274765LEE CO EC;6U
Adder
8.247
274763LEE CO EC;4U
Adder
8.15
274695ROCKY RD ;2P
Adder
9.734
966871AG1-558 GEN
Solar/Wind Helper
0.306
24684705SMG5
50/50
0.857
3151561HALLBR1
50/50
0.57
270173AC1-122 GEN
Solar/Wind Harmer
3.279
941801AE2-185 GEN
Solar/Wind Harmer
9.815
970913AG2-568 GEN
Solar/Wind Harmer
11.009
270053AF1-130 C
Solar/Wind Harmer
4.818
24686405CER G5
Adder
9.802
970273AG2-179 GEN
Solar/Wind Harmer
4.125
339250AF1-203 GEN
Solar/Wind Harmer
0.628
962251AG1-071 GEN
Solar/Wind Harmer
5.674
276686W4-005 GEN3
Solar/Wind Harmer
2.728
270356AE2-297 GEN
Solar/Wind Harmer
4.101
970823AG2-518 GEN
50/50
8.386
247619Y1-049
50/50
0.913
24416005BYLLESBY
50/50
0.031
958121AF2-106 GEN
Solar/Wind Harmer
9.409
971331AH1-145 GEN
Solar/Wind Harmer
18.367
270346AE1-212 GEN
Solar/Wind Harmer
13.941
971461AH1-227 GEN
Solar/Wind Harmer
7.007
970223AG2-152 GEN
Solar/Wind Harmer
17.631
24686205CER G4
Adder
9.841
3429391JKCT 9G
Adder
8.407
957541AF2-048 GEN
Solar/Wind Harmer
1.529
958171AF2-111 GEN
Solar/Wind Harmer
23.926
970519AG2-331 GEN
Solar/Wind Harmer
16.529
970699AG2-449 GEN
Solar/Wind Harmer
10.935
25196608WSDLE5
Adder
7.855
970193AG2-126 GEN
Solar/Wind Harmer
13.698
24728705AND G3
Adder
7.283
253406AD2-031_GEN
Solar/Wind Harmer
1.149
3147666LOUISA
Solar/Wind Helper
1.087
316254AC1-120 GEN1
Solar/Wind Helper
1.158
274760LEE CO EC;1U
Adder
8.227
972236AH1-702 GEN2
Adder
1.932
238148AE2-230_GEN2
Solar/Wind Helper
0.423
316006AB2-029 C
Solar/Wind Helper
0.112
316045AC1-158 PL2
Solar/Wind Helper
4.02
944201AF1-088_MTX
Adder
109.164
957141AF2-008_MTX
Adder
54.582
NYPJM->LTFIMP_NY
CLTF
3.243
LGEELTFEXP_LGEE->PJM
CLTF
6.767
WECLTFEXP_WEC->PJM
CLTF
3.374
AG2-052LTFEXP_AG2-052->PJM
LTF
0.202
AH1-155LTFEXP_AH1-155->PJM
LTF
0.303
LAGNLTFEXP_LAGN->PJM
CLTF
20.293
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.574
TVALTFEXP_TVA->PJM
CLTF
10.613
CPLELTFEXP_CPLE->PJM
CLTF
6.233
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.197
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.508
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.339
MECLTFEXP_MEC->PJM
CLTF
15.425
SIGELTFEXP_SIGE->PJM
CLTF
0.508

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7445_05MARYSV 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.05 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6243.53
MW Contribution:3.99
Bus #Bus NameTypeMW Contribution
24721805FLATG3
50/50
3.32
24721705FLATG2
50/50
60.871
243186AF1-051 GEN
50/50
14.281
24289405MTG1
50/50
12.693
970149AG2-104 GEN
Solar/Wind Harmer
113.494
971403AH1-188 GEN
Solar/Wind Harmer
25.361
960001AF2-291 GEN
Solar/Wind Harmer
5.186
971329AH1-144 GEN
Solar/Wind Harmer
16.634
927014AC1-188 GEN
Solar/Wind Harmer
2.118
970091AG2-072 GEN
Adder
90.557
970273AG2-179 GEN
Solar/Wind Harmer
2.784
971565AH1-281 GEN
Solar/Wind Harmer
2.213
3429421JKCT 10G
Adder
9.194
963741AG1-226 GEN
Solar/Wind Harmer
43.173
274822ROCKFORD ;11
Adder
17.664
235054AD2-180 GEN
Solar/Wind Helper
1.542
23562501BACKB
Solar/Wind Helper
0.81
270399AC1-101 GEN
Solar/Wind Harmer
7.605
270330AC1-082 GEN2
Solar/Wind Harmer
1.366
972143AH1-644 GEN
Solar/Wind Harmer
15.505
24734705WLF1G3
Adder
8.349
24734905WLF1G5
Adder
8.349
966391AG1-508 GEN
Solar/Wind Harmer
4.988
971985AH1-537 GEN
Solar/Wind Harmer
23.222
971981AH1-535 GEN
Solar/Wind Harmer
12.796
270069AE2-166 C O1
Solar/Wind Harmer
3.217
965401AG1-405 GEN
Solar/Wind Harmer
6.573
339211AE2-254 GEN
Solar/Wind Harmer
1.711
972165AH1-665 GEN
Solar/Wind Harmer
8.697
274823ROCKFORD ;21
Adder
17.536
962761AG1-125 GEN
Solar/Wind Harmer
91.898
24686505CER G6
Adder
16.155
24728305BUCHG2
Adder
7.204
3429241JKCT 3G
Adder
13.209
962241AG1-070 GEN
Solar/Wind Harmer
5.006
339216AC1-074 GEN
Solar/Wind Harmer
1.819
270018AE2-047 C O1
Solar/Wind Harmer
1.277
252507AC2-088 GEN
Solar/Wind Harmer
1.836
965911AG1-460 GEN
Solar/Wind Harmer
1.345
276615X2-022 GEN
Solar/Wind Harmer
1.868
274766LEE CO EC;7U
Adder
8.327
972235AH1-702 GEN1
Adder
2.27
963831AG1-236 GEN
Solar/Wind Harmer
2.691
962771AG1-126 GEN
Solar/Wind Harmer
91.898
972203AH1-686 GEN
Adder
4.552
970281AG2-184 GEN
Solar/Wind Harmer
32.56
962211AG1-066 GEN
Solar/Wind Harmer
3.499
252524AE2-267 GEN
Solar/Wind Harmer
1.53
274744AC1-111 GEN8
Adder
4.954
241997AF1-093 GEN
Solar/Wind Helper
0.233
243186AF1-051 GEN
50/50
14.281
24723005RIVRG1
Adder
37.861
24723105RIVRG2
Adder
37.861
24685805CER G1
Adder
16.07
24685905CER G2
Adder
16.07
971225AH1-072 GEN
Solar/Wind Harmer
3.087
971227AH1-073 GEN
Solar/Wind Harmer
3.087
270214AC2-123 GEN
Solar/Wind Harmer
3.357
270583AD2-179 GEN
Solar/Wind Harmer
13.373
971125AH1-004 GEN
Solar/Wind Harmer
4.377
270444AC2-157 GEN1
Solar/Wind Harmer
5.954
252519AF1-045_GEN
Solar/Wind Harmer
5.968
252516AE2-318_GEN
Solar/Wind Harmer
4.552
276916AD2-100_GEN
Solar/Wind Harmer
20.308
957381AF2-032 GEN
Solar/Wind Harmer
0.403
276763AC1-053 GEN1
Solar/Wind Harmer
3.755
276764AC1-053 GEN2
Solar/Wind Harmer
3.755
241801AE1-079 GEN
Solar/Wind Helper
0.227
970155AG2-107 GEN
Solar/Wind Harmer
40.072
24723205RIVRG3
Adder
37.861
24686105CER G3
Adder
16.176
970947AG2-589 GEN
Solar/Wind Harmer
3.533
24735205WLF2G2
Adder
8.16
270336AE1-100 GEN
Solar/Wind Harmer
2.043
971367AH1-164 GEN
Solar/Wind Harmer
3.994
971821AH1-427 GEN
Solar/Wind Harmer
11.315
943811AF1-049 GEN
Solar/Wind Harmer
4.273
339241AF1-083 GEN
Solar/Wind Harmer
1.864
964901AG1-354 GEN
Solar/Wind Harmer
16.766
943111AE2-339 GEN
Solar/Wind Harmer
0.969
945681AF1-233 GEN
Solar/Wind Harmer
20.401
270445AC2-157 GEN2
Solar/Wind Harmer
5.954
25194608D.CRK4
Adder
1.604
24728605AND G2
Adder
3.69
274828WAUKEGAN ;BP
Adder
9.834
274682WAUKEGAN ;7U
Adder
15.992
274745AC1-111 GEN9
Adder
4.954
241966AE1-183 GEN
Solar/Wind Helper
0.233
238185AF2-356 C
Solar/Wind Helper
1.986
971313AH1-133 GEN
Solar/Wind Harmer
15.802
270132AB1-180 C
Adder
0.187
971061AG2-657 GEN
Solar/Wind Harmer
13.568
965411AG1-406 GEN
Solar/Wind Harmer
2.95
970879AG2-548 GEN
Solar/Wind Harmer
4.825
270367AC2-061_GEN
Solar/Wind Harmer
3.448
25196108MFTGT2
Adder
1.552
25196108MFTGT2
Adder
1.441
25196408WSDLE3
Adder
8.556
25196308WSDLE2
Adder
8.482
25196208WSDLE1
Adder
8.46
25196708WSDLE6
Adder
8.439
960161AF2-307 GEN
Solar/Wind Harmer
7.621
970239AG2-162 GEN
Solar/Wind Harmer
12.849
970879AG2-548 GEN
Solar/Wind Harmer
6.915
339236AF1-050_GEN
Solar/Wind Harmer
2.029
970107AG2-081 GEN
Solar/Wind Harmer
3.283
270186AC1-089 GEN
Solar/Wind Harmer
6.681
970235AG2-159 GEN
Solar/Wind Harmer
4.336
970235AG2-159 GEN
Solar/Wind Harmer
2.647
962581AG1-107 GEN
Solar/Wind Harmer
5.324
961491AF2-440 GEN
Solar/Wind Harmer
2.213
970241AG2-163 GEN
Solar/Wind Harmer
23.985
274762LEE CO EC;3U
Adder
8.426
274696ROCKY RD ;4P
Adder
10.143
274697ROCKY RD ;3P
Adder
2.692
962101AG1-054 GEN
Solar/Wind Helper
0.594
241985AE1-237 GEN
Solar/Wind Helper
0.227
944781AF1-143 GEN
Solar/Wind Helper
2.213
24722005FLATG5
50/50
3.32
24721905FLATG4
50/50
60.871
970153AG2-106 GEN
Solar/Wind Harmer
40.072
960911AF2-382 GEN
Solar/Wind Harmer
12.052
972103AH1-617 GEN
Solar/Wind Harmer
31.009
943031AE2-326 GEN
Solar/Wind Harmer
5.284
270030AE2-140 GEN
Solar/Wind Harmer
23.108
971155AH1-034 GEN
Solar/Wind Harmer
11.167
960741AF2-365 GEN
Solar/Wind Harmer
5.543
25194608D.CRK4
Adder
1.604
24728505AND G1
Adder
3.69
274767LEE CO EC;8U
Adder
8.327
274682WAUKEGAN ;7U
Adder
15.992
235058AG1-386 C
Solar/Wind Helper
0.421
964991AG1-363 GEN
Solar/Wind Helper
3.317
24318705GVG2
50/50
13.293
270331AC1-082 GEN3
Solar/Wind Harmer
0.807
971687AH1-348 GEN
Solar/Wind Harmer
1.543
971315AH1-136 GEN
Solar/Wind Harmer
3.067
970333AG2-219 GEN
Solar/Wind Harmer
36.87
25196008MFTGT1
Adder
1.408
25196808ZIMRHP
Adder
76.262
274761LEE CO EC;2U
Adder
8.426
237046AF1-021 C
Solar/Wind Helper
0.454
254303AC2-168 GEN
Solar/Wind Helper
0.144
23751201ROTHROCK
Solar/Wind Helper
0.666
20089226LOOKOUT
Solar/Wind Helper
0.519
24318705GVG2
50/50
13.293
971191AH1-055 GEN
Solar/Wind Harmer
33.8
970243AG2-164 GEN
Solar/Wind Harmer
30.166
972273AH1-721 GEN
Adder
96.475
970093AG2-073 GEN
Solar/Wind Harmer
11.307
966571AG1-526 GEN
Solar/Wind Harmer
25.008
972167AH1-666 GEN
Solar/Wind Harmer
8.642
25196008MFTGT1
Adder
1.363
252510AF1-249 C
Solar/Wind Harmer
0.411
942481AE2-261 GEN
Solar/Wind Harmer
28.829
962751AG1-124 GEN
Solar/Wind Harmer
8.642
276621W2-048 GEN
Solar/Wind Harmer
5.949
276838X2-022 GEN2
Solar/Wind Harmer
0.222
274729ELWOOD EC;1P
Adder
14.499
237048AF1-022 C
Solar/Wind Helper
0.178
237043AE2-125 C
Solar/Wind Helper
0.164
24721605FLATG1
50/50
3.32
24477305BRIDGE
Adder
0.636
957241AF2-018 GEN
Solar/Wind Harmer
8.055
270400AC1-102 GEN
Solar/Wind Harmer
7.605
270329AC1-082 GEN1
Solar/Wind Harmer
0.805
941621AE2-160 GEN
Adder
5.471
24734805WLF1G4
Adder
8.349
24735105WLF2G1
Adder
8.16
3429211JKCT 2G
Adder
13.038
970455AG2-298 GEN
Solar/Wind Harmer
6.646
972163AH1-664 GEN
Solar/Wind Harmer
10.872
339243AC2-075 GEN1
Solar/Wind Harmer
0.493
944221AF1-090 GEN
Solar/Wind Harmer
10.676
25196508WSDLE4
Adder
8.227
963841AG1-237 GEN
Solar/Wind Harmer
10.394
274746AC1-111 G10
Adder
4.954
274731ELWOOD EC;2P
Adder
14.499
274733ELWOOD EC;3P
Adder
10.298
23750501ELLIOTTS
Solar/Wind Helper
0.613
254304AE2-114 C
Solar/Wind Helper
0.199
241982AE2-343 S C
Solar/Wind Helper
0.203
944971AF1-162 GEN
Solar/Wind Harmer
12.689
24728205BUCHG1
Adder
7.204
971277AH1-098 GEN
Solar/Wind Harmer
5.729
966021AG1-471 GEN
Solar/Wind Harmer
6.166
339231AF1-038_GEN
Solar/Wind Harmer
2.069
971073AG2-665 GEN
Solar/Wind Harmer
6.915
971073AG2-665 GEN
Solar/Wind Harmer
4.825
339255AE2-071 GEN
Solar/Wind Harmer
1.185
970653AG2-424 GEN
Solar/Wind Harmer
5.35
970653AG2-424 GEN
Solar/Wind Harmer
1.934
964571AG1-320 GEN
Solar/Wind Harmer
9.018
972045AH1-571 GEN
Solar/Wind Harmer
2.195
339221AD2-048_GEN
Solar/Wind Harmer
1.68
252509AD1-136 GEN
Solar/Wind Harmer
0.262
25183208HLCRTG
Solar/Wind Harmer
5.931
25194508D.CRK3
Adder
1.38
276911AD2-131_GEN
Solar/Wind Harmer
4.104
24728805RICHG1
Adder
3.448
274765LEE CO EC;6U
Adder
8.446
274763LEE CO EC;4U
Adder
8.346
274695ROCKY RD ;2P
Adder
9.908
971485AH1-239 GEN
Solar/Wind Harmer
9.113
942891AE2-308 GEN
Solar/Wind Harmer
11.21
971081AG2-670 GEN
Solar/Wind Harmer
8.401
964781AG1-341 GEN
Solar/Wind Harmer
11.836
972043AH1-570 GEN
Solar/Wind Harmer
2.743
945391AF1-204 GEN
Solar/Wind Harmer
13.769
25194408D.CRK1
Adder
7.379
24728905RICHG2
Adder
3.448
972267AH1-718 GEN
Adder
3.785
274764LEE CO EC;5U
Adder
8.446
274683WAUKEGAN ;8U
Adder
18.761
274683WAUKEGAN ;8U
Adder
15.814
274693ROCKY RD ;1P
Adder
9.811
23652301WDPWR_K20
Solar/Wind Helper
0.133
241967AE2-285_GEN
Solar/Wind Helper
0.583
23585401KL_K28_T16
Solar/Wind Helper
1.167
203955AF1-039 C O1
Solar/Wind Helper
0.335
24686205CER G4
Adder
16.091
971461AH1-227 GEN
Solar/Wind Harmer
7.917
270346AE1-212 GEN
Solar/Wind Harmer
13.484
971331AH1-145 GEN
Solar/Wind Harmer
12.895
247619Y1-049
Adder
0.586
958121AF2-106 GEN
Solar/Wind Harmer
6.061
957541AF2-048 GEN
Solar/Wind Harmer
2.113
970519AG2-331 GEN
Solar/Wind Harmer
20.267
970699AG2-449 GEN
Solar/Wind Harmer
13.407
3429391JKCT 9G
Adder
9.194
958171AF2-111 GEN
Solar/Wind Harmer
25.894
270291AC1-194 GEN
Solar/Wind Harmer
10.843
24289405MTG1
50/50
12.693
24686405CER G5
Adder
16.028
270053AF1-130 C
Solar/Wind Harmer
6.738
970913AG2-568 GEN
Solar/Wind Harmer
13.608
970273AG2-179 GEN
Solar/Wind Harmer
4.447
339250AF1-203 GEN
Solar/Wind Harmer
0.677
962251AG1-071 GEN
Solar/Wind Harmer
6.119
270173AC1-122 GEN
Solar/Wind Harmer
1.562
274760LEE CO EC;1U
Adder
8.426
972236AH1-702 GEN2
Adder
1.974
20089126CSLMN_L13
Solar/Wind Helper
0.533
970193AG2-126 GEN
Solar/Wind Harmer
14.82
25196608WSDLE5
Adder
8.312
24728705AND G3
Adder
7.718
254305AE2-115 C
Solar/Wind Helper
0.199
202652Y1-033 WT C
Solar/Wind Helper
0.509
23750701CROSSCHOOL
Solar/Wind Helper
1.078
20089026BF_G21_K23
Solar/Wind Helper
0.422
944201AF1-088_MTX
Adder
123.966
957141AF2-008_MTX
Adder
61.983
NYPJM->LTFIMP_NY
CLTF
4.768
LGEELTFEXP_LGEE->PJM
CLTF
7.621
WECLTFEXP_WEC->PJM
CLTF
3.448
AG2-052LTFEXP_AG2-052->PJM
LTF
0.206
AH1-155LTFEXP_AH1-155->PJM
LTF
0.308
LAGNLTFEXP_LAGN->PJM
CLTF
21.271
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.975
TVALTFEXP_TVA->PJM
CLTF
11.116
CPLELTFEXP_CPLE->PJM
CLTF
7.658
CBM West 2LTFEXP_CBM-W2->PJM
CBM
139.058
CBM West 1LTFEXP_CBM-W1->PJM
CBM
111.704
CBM South 1LTFEXP_CBM-S1->PJM
CBM
41.73
MECLTFEXP_MEC->PJM
CLTF
16.018
SIGELTFEXP_SIGE->PJM
CLTF
0.557

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.86 %
Rating:4558.0 MVA
Rating Type:A
MVA to Mitigate:4961.85
MW Contribution:2.34
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
2.473
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
957241AF2-018 GEN
Solar/Wind Harmer
-0.002
24477305BRIDGE
Adder
0.546
270400AC1-102 GEN
Solar/Wind Harmer
3.444
941621AE2-160 GEN
Adder
4.703
24734805WLF1G4
Adder
7.306
24735105WLF2G1
Adder
7.162
972163AH1-664 GEN
Solar/Wind Harmer
8.62
3429211JKCT 2G
Adder
12.898
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
970455AG2-298 GEN
Solar/Wind Harmer
5.018
25196508WSDLE4
Adder
8.795
270340AC2-060 GEN
Solar/Wind Harmer
0.008
944221AF1-090 GEN
Solar/Wind Harmer
3.946
963841AG1-237 GEN
Solar/Wind Harmer
2.88
24386205FR-12G C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270269AC2-059
Solar/Wind Harmer
0.004
970115AG2-085 GEN
Solar/Wind Harmer
2.587
276655WTG1_EQ
Solar/Wind Harmer
0.003
253400AC2-068 GEN
Solar/Wind Harmer
0.812
971609AH1-304 GEN
Solar/Wind Harmer
1.037
926823AC1-168 GEN
Solar/Wind Harmer
1.076
274746AC1-111 G10
Adder
4.992
23750501ELLIOTTS
Solar/Wind Helper
0.594
24686205CER G4
Adder
14.065
971461AH1-227 GEN
Solar/Wind Harmer
4.855
270346AE1-212 GEN
Solar/Wind Harmer
7.86
971331AH1-145 GEN
Solar/Wind Harmer
10.953
247619Y1-049
Adder
0.497
958121AF2-106 GEN
Solar/Wind Harmer
0.001
970519AG2-331 GEN
Solar/Wind Harmer
20.392
970699AG2-449 GEN
Solar/Wind Harmer
1.961
3429391JKCT 9G
Adder
9.139
270291AC1-194 GEN
Solar/Wind Harmer
5.957
958171AF2-111 GEN
Solar/Wind Harmer
18.792
25196608WSDLE5
Adder
8.886
253406AD2-031_GEN
Solar/Wind Harmer
0.522
970193AG2-126 GEN
Solar/Wind Harmer
10.289
24728705AND G3
Adder
7.865
253415AE1-040 GEN
Solar/Wind Harmer
0.003
270437AC2-090 C
Solar/Wind Harmer
0.003
970781AG2-491 GEN
Solar/Wind Harmer
6.514
270273AD2-016 GEN
Solar/Wind Harmer
0.675
958821AF2-173 GEN
Solar/Wind Harmer
9.079
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
959611AF2-252 GEN
Solar/Wind Harmer
2.156
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
970513AG2-328 GEN
Solar/Wind Harmer
1.358
970517AG2-330 GEN
Solar/Wind Harmer
8.151
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270399AC1-101 GEN
Solar/Wind Harmer
3.444
972143AH1-644 GEN
Solar/Wind Harmer
10.394
24734705WLF1G3
Adder
7.306
24734905WLF1G5
Adder
7.306
971985AH1-537 GEN
Solar/Wind Harmer
2.617
966391AG1-508 GEN
Solar/Wind Harmer
1.328
971981AH1-535 GEN
Solar/Wind Harmer
5.272
972165AH1-665 GEN
Solar/Wind Harmer
6.904
965401AG1-405 GEN
Solar/Wind Harmer
4.386
339211AE2-254 GEN
Solar/Wind Harmer
0.003
270069AE2-166 C O1
Solar/Wind Harmer
0.005
24386405FR-21G C
Solar/Wind Harmer
0.001
24725505WLD G2 C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
9.661
276656WTG2_EQ
Solar/Wind Harmer
0
941731AE2-173 GEN
Solar/Wind Harmer
5.363
253349AC2-067 GEN
Solar/Wind Harmer
2.02
946321AF1-296 GEN
Solar/Wind Harmer
3.573
971611AH1-305 GEN
Solar/Wind Harmer
3.799
945581AF1-223 GEN
Solar/Wind Harmer
0
274823ROCKFORD ;21
Adder
17.581
971171AH1-044 GEN
Solar/Wind Harmer
12.585
944971AF1-162 GEN
Solar/Wind Harmer
11.031
24728205BUCHG1
Adder
6.221
971277AH1-098 GEN
Solar/Wind Harmer
3.403
971073AG2-665 GEN
Solar/Wind Harmer
7.21
972045AH1-571 GEN
Solar/Wind Harmer
1.602
339221AD2-048_GEN
Solar/Wind Harmer
0.005
966021AG1-471 GEN
Solar/Wind Harmer
4.054
252509AD1-136 GEN
Solar/Wind Harmer
0.038
970653AG2-424 GEN
Solar/Wind Harmer
3.613
970653AG2-424 GEN
Solar/Wind Harmer
1.872
964571AG1-320 GEN
Solar/Wind Harmer
6.819
339255AE2-071 GEN
Solar/Wind Harmer
-0.122
25183208HLCRTG
Solar/Wind Harmer
0.011
25194508D.CRK3
Adder
1.471
24728805RICHG1
Adder
3.669
276911AD2-131_GEN
Solar/Wind Harmer
0.923
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270383AD1-128 GEN
Solar/Wind Harmer
0.004
945421AF1-207 GEN
Solar/Wind Harmer
0.001
960441AF2-335 GEN
Solar/Wind Harmer
6.468
970885AG2-551 GEN
Solar/Wind Harmer
2.125
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
276646AC1-214 GEN2
Solar/Wind Harmer
0.25
270031AE2-169
Solar/Wind Harmer
3.492
274765LEE CO EC;6U
Adder
8.452
274763LEE CO EC;4U
Adder
8.352
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
274695ROCKY RD ;2P
Adder
9.971
24318705GVG2
50/50
10.872
971191AH1-055 GEN
Solar/Wind Harmer
25.624
970243AG2-164 GEN
Solar/Wind Harmer
4.588
970093AG2-073 GEN
Solar/Wind Harmer
7.734
972167AH1-666 GEN
Solar/Wind Harmer
6.174
972273AH1-721 GEN
Adder
91.659
966571AG1-526 GEN
Solar/Wind Harmer
17.032
25196008MFTGT1
Adder
1.418
252510AF1-249 C
Solar/Wind Harmer
0.056
942481AE2-261 GEN
Solar/Wind Harmer
19.91
276621W2-048 GEN
Solar/Wind Harmer
0.333
276838X2-022 GEN2
Solar/Wind Harmer
0.372
971993AH1-541 GEN
Solar/Wind Harmer
3.038
942111AE2-223 GEN
Solar/Wind Harmer
2.091
276157O29GEN1
Solar/Wind Harmer
1.026
970571AG2-364 GEN
Solar/Wind Harmer
12.648
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
276889AE2-281 GEN
Solar/Wind Harmer
0.001
274729ELWOOD EC;1P
Adder
6.64
237048AF1-022 C
Solar/Wind Helper
0.172
237043AE2-125 C
Solar/Wind Helper
0.155
942891AE2-308 GEN
Solar/Wind Harmer
7.714
972043AH1-570 GEN
Solar/Wind Harmer
1.999
971485AH1-239 GEN
Solar/Wind Harmer
5.998
971081AG2-670 GEN
Solar/Wind Harmer
5.621
964781AG1-341 GEN
Solar/Wind Harmer
7.848
25194408D.CRK1
Adder
7.868
945391AF1-204 GEN
Solar/Wind Harmer
7.288
24728905RICHG2
Adder
3.669
926881AC1-175 GEN
Solar/Wind Harmer
0.001
966841AG1-555 GEN
Solar/Wind Harmer
0.746
960611AF2-352 GEN
Solar/Wind Harmer
2.156
970883AG2-550 GEN
Solar/Wind Harmer
6.374
276782AC1-033 GEN
Solar/Wind Harmer
0.001
270599AE1-208 GEN
Solar/Wind Harmer
5.819
276708O09 GEN2
Solar/Wind Harmer
0.226
972267AH1-718 GEN
Adder
3.783
274764LEE CO EC;5U
Adder
8.452
274683WAUKEGAN ;8U
Adder
18.876
274683WAUKEGAN ;8U
Adder
15.912
274693ROCKY RD ;1P
Adder
9.873
23652301WDPWR_K20
Solar/Wind Helper
0.126
23585401KL_K28_T16
Solar/Wind Helper
1.149
24722005FLATG5
50/50
2.473
24721905FLATG4
50/50
45.331
960911AF2-382 GEN
Solar/Wind Harmer
7.284
972103AH1-617 GEN
Solar/Wind Harmer
19.189
943031AE2-326 GEN
Solar/Wind Harmer
4.498
960741AF2-365 GEN
Solar/Wind Harmer
3.705
971155AH1-034 GEN
Solar/Wind Harmer
8.639
25194608D.CRK4
Adder
1.71
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
9.211
970153AG2-106 GEN
Solar/Wind Harmer
17.538
24728505AND G1
Adder
3.761
270030AE2-140 GEN
Solar/Wind Harmer
13.595
276668AB2-070 GEN1
Solar/Wind Harmer
0.24
247642Z2-115 C
Solar/Wind Harmer
0.003
24755605MDL-5G
Solar/Wind Harmer
0.001
970289AG2-191 GEN
Solar/Wind Harmer
0.716
970291AG2-192 GEN
Solar/Wind Harmer
0.651
253370AE2-315 SEC1
Adder
1.856
253371AE2-315 SEC2
Adder
1.755
946031AF1-268 GEN
Solar/Wind Harmer
6.117
274767LEE CO EC;8U
Adder
8.332
959091AF2-200 GEN
Solar/Wind Harmer
12.585
274682WAUKEGAN ;7U
Adder
16.093
235058AG1-386 C
Solar/Wind Helper
0.383
243186AF1-051 GEN
50/50
11.679
24721805FLATG3
50/50
2.473
24721705FLATG2
50/50
45.331
24723205RIVRG3
Adder
32.794
24686105CER G3
Adder
14.139
970947AG2-589 GEN
Solar/Wind Harmer
0.368
24735205WLF2G2
Adder
7.162
945681AF1-233 GEN
Solar/Wind Harmer
14.563
971821AH1-427 GEN
Solar/Wind Harmer
7.658
964901AG1-354 GEN
Solar/Wind Harmer
11.154
270445AC2-157 GEN2
Solar/Wind Harmer
0.003
25194608D.CRK4
Adder
1.71
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.086
970155AG2-107 GEN
Solar/Wind Harmer
17.538
270336AE1-100 GEN
Solar/Wind Harmer
0.004
24728605AND G2
Adder
3.761
971367AH1-164 GEN
Solar/Wind Harmer
2.344
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
970613AG2-401 GEN
Solar/Wind Harmer
4.849
970291AG2-192 GEN
Solar/Wind Harmer
0.846
965031AG1-367 GEN
Solar/Wind Harmer
6.485
253370AE2-315 SEC1
Adder
1.856
253371AE2-315 SEC2
Adder
1.755
274877BISHOP HL;1U
Solar/Wind Harmer
0.214
960071AF2-298 GEN
Solar/Wind Harmer
3.157
957471AF2-041 GEN
Solar/Wind Harmer
18.878
274828WAUKEGAN ;BP
Adder
9.895
274682WAUKEGAN ;7U
Adder
16.093
274745AC1-111 GEN9
Adder
4.992
238185AF2-356 C
Solar/Wind Helper
1.954
24318705GVG2
50/50
10.872
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
971315AH1-136 GEN
Solar/Wind Harmer
1.928
971687AH1-348 GEN
Solar/Wind Harmer
0.947
970333AG2-219 GEN
Solar/Wind Harmer
5.608
25196808ZIMRHP
Adder
80.408
25196008MFTGT1
Adder
1.465
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0.002
274880W4-005 GEN4
Solar/Wind Harmer
0.001
972175AH1-670 GEN
Solar/Wind Harmer
5.394
270032AE2-172
Solar/Wind Harmer
4.336
270005AE1-210 C O1
Solar/Wind Harmer
1.405
970825AG2-519 GEN
Solar/Wind Harmer
2.296
939741AE1-205 GEN
Solar/Wind Harmer
9.009
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
7.976
276158O29GEN2
Solar/Wind Harmer
0.001
970569AG2-363 GEN
Solar/Wind Harmer
18.972
274761LEE CO EC;2U
Adder
8.432
945371AF1-202 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971997AH1-543 GEN
Solar/Wind Harmer
3.301
237046AF1-021 C
Solar/Wind Helper
0.433
23751201ROTHROCK
Solar/Wind Helper
0.662
24289405MTG1
50/50
10.907
971403AH1-188 GEN
Solar/Wind Harmer
15.305
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
927014AC1-188 GEN
Solar/Wind Harmer
0.005
971329AH1-144 GEN
Solar/Wind Harmer
6.901
970091AG2-072 GEN
Adder
86.947
3429421JKCT 10G
Adder
9.139
970273AG2-179 GEN
Solar/Wind Harmer
2.644
971565AH1-281 GEN
Solar/Wind Harmer
1.508
970149AG2-104 GEN
Solar/Wind Harmer
29.663
270263AC1-001 GEN
Solar/Wind Harmer
0.699
970773AG2-487 GEN
Solar/Wind Harmer
1.204
963741AG1-226 GEN
Solar/Wind Harmer
15.844
24791305MDL-5G
Solar/Wind Harmer
0.001
274854TWINGROVE;U2
Solar/Wind Harmer
0.003
276726Z2-087_GEN
Solar/Wind Harmer
0.002
971475AH1-234 GEN
Solar/Wind Harmer
3.061
970819AG2-516 GEN
Solar/Wind Harmer
7.565
274822ROCKFORD ;11
Adder
17.71
959081AF2-199 GEN
Solar/Wind Harmer
6.293
971067AG2-660 GEN
Solar/Wind Harmer
2.098
971917AH1-482 GEN
Solar/Wind Harmer
8.18
235054AD2-180 GEN
Solar/Wind Helper
1.52
23562501BACKB
Solar/Wind Helper
0.806
24289405MTG1
50/50
10.907
24686405CER G5
Adder
14.009
270053AF1-130 C
Solar/Wind Harmer
2.49
970913AG2-568 GEN
Solar/Wind Harmer
8.136
970273AG2-179 GEN
Solar/Wind Harmer
4.533
339250AF1-203 GEN
Solar/Wind Harmer
0.001
962251AG1-071 GEN
Solar/Wind Harmer
4.615
270356AE2-297 GEN
Solar/Wind Harmer
0.009
270222AC2-111 GEN
Solar/Wind Harmer
3.451
972173AH1-669 GEN
Solar/Wind Harmer
3.31
276686W4-005 GEN3
Solar/Wind Harmer
0.001
270004AE1-209 GEN
Solar/Wind Harmer
1.405
965091AG1-374 GEN
Solar/Wind Harmer
19.404
970191AG2-125 GEN
Solar/Wind Harmer
1.65
965931AG1-462 GEN
Solar/Wind Harmer
16.291
274878BISHOP HL;2U
Solar/Wind Harmer
0.214
274760LEE CO EC;1U
Adder
8.432
972236AH1-702 GEN2
Adder
1.979
972203AH1-686 GEN
Adder
3.978
970281AG2-184 GEN
Solar/Wind Harmer
20.149
252524AE2-267 GEN
Solar/Wind Harmer
0.003
962771AG1-126 GEN
Solar/Wind Harmer
27.465
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.24
276848AB2-070 GEN3
Solar/Wind Harmer
0.239
970289AG2-191 GEN
Solar/Wind Harmer
1.237
25306009OHH W.
Adder
2.673
253372AE2-315 SEC3
Adder
1.755
253372AE2-315 SEC3
Adder
1.755
959341AF2-225 GEN
Solar/Wind Harmer
6.757
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
970169AG2-114 GEN
Solar/Wind Harmer
6.359
961011AF2-392 GEN
Solar/Wind Harmer
3.717
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274744AC1-111 GEN8
Adder
4.992
24686505CER G6
Adder
14.12
24728305BUCHG2
Adder
6.221
3429241JKCT 3G
Adder
13.068
339216AC1-074 GEN
Solar/Wind Harmer
0.209
252507AC2-088 GEN
Solar/Wind Harmer
0.341
962241AG1-070 GEN
Solar/Wind Harmer
4.025
962761AG1-125 GEN
Solar/Wind Harmer
27.465
965911AG1-460 GEN
Solar/Wind Harmer
1.332
276615X2-022 GEN
Solar/Wind Harmer
0.069
24385905FR-11G C
Solar/Wind Harmer
0.002
963831AG1-236 GEN
Solar/Wind Harmer
2.568
276903AD2-071 C
Solar/Wind Harmer
7.334
25326309TAIT D
Adder
0.995
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274766LEE CO EC;7U
Adder
8.332
247536S-71 GEN
Solar/Wind Harmer
0.254
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
972235AH1-702 GEN1
Adder
2.276
939401AE1-172 GEN
Solar/Wind Harmer
4.71
970245AG2-165 GEN
Solar/Wind Harmer
1.358
243186AF1-051 GEN
50/50
11.679
24723005RIVRG1
Adder
32.794
24723105RIVRG2
Adder
32.794
24685805CER G1
Adder
14.046
24685905CER G2
Adder
14.046
971225AH1-072 GEN
Solar/Wind Harmer
1.893
971227AH1-073 GEN
Solar/Wind Harmer
1.893
270583AD2-179 GEN
Solar/Wind Harmer
7.911
971125AH1-004 GEN
Solar/Wind Harmer
3.056
252519AF1-045_GEN
Solar/Wind Harmer
6.373
252516AE2-318_GEN
Solar/Wind Harmer
5.653
270444AC2-157 GEN1
Solar/Wind Harmer
0.003
971587AH1-292 GEN
Solar/Wind Harmer
5.336
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
276916AD2-100_GEN
Solar/Wind Harmer
14.016
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
971613AH1-306 GEN
Solar/Wind Harmer
3.122
253370AE2-315 SEC1
Adder
1.856
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276741O09 GEN1
Solar/Wind Harmer
0.226
25322209TAIT E
Adder
8.86
25322209TAIT E
Adder
8.661
971341AH1-150 GEN
Solar/Wind Harmer
12.585
971343AH1-151 GEN
Solar/Wind Harmer
12.585
247621Y3-024
Adder
0.216
971313AH1-133 GEN
Solar/Wind Harmer
9.492
270132AB1-180 C
Adder
0.159
971061AG2-657 GEN
Solar/Wind Harmer
5.654
970879AG2-548 GEN
Solar/Wind Harmer
7.21
270367AC2-061_GEN
Solar/Wind Harmer
0.006
965411AG1-406 GEN
Solar/Wind Harmer
2.821
25196108MFTGT2
Adder
1.614
25196108MFTGT2
Adder
1.499
25196408WSDLE3
Adder
9.147
25196308WSDLE2
Adder
9.067
25196208WSDLE1
Adder
9.045
25196708WSDLE6
Adder
9.022
270240V3-007_GEN2
Solar/Wind Harmer
0.002
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
270594AE1-207 GEN
Solar/Wind Harmer
7.284
971673AH1-337 GEN
Solar/Wind Harmer
4.2
270543AE2-219 C
Solar/Wind Harmer
0.004
957751AF2-069 GEN
Solar/Wind Harmer
0.21
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
971681AH1-341 GEN
Solar/Wind Harmer
10.171
276612AE2-035 GEN
Solar/Wind Harmer
0.002
960161AF2-307 GEN
Solar/Wind Harmer
5.337
270186AC1-089 GEN
Solar/Wind Harmer
0.005
970239AG2-162 GEN
Solar/Wind Harmer
1.961
962581AG1-107 GEN
Solar/Wind Harmer
0.002
970107AG2-081 GEN
Solar/Wind Harmer
2.292
970235AG2-159 GEN
Solar/Wind Harmer
4.628
970235AG2-159 GEN
Solar/Wind Harmer
2.656
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
970241AG2-163 GEN
Solar/Wind Harmer
3.905
270209AC1-174_GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
970825AG2-519 GEN
Solar/Wind Harmer
7.169
276645AC1-214 GEN1
Solar/Wind Harmer
0.25
276603SUBLETTE C
Solar/Wind Harmer
0
274762LEE CO EC;3U
Adder
8.432
938861AE1-114 GEN
Solar/Wind Harmer
3.58
274856ECOGROVE ;U1
Solar/Wind Harmer
0.149
276611AD2-172 GEN
Solar/Wind Harmer
0.002
274696ROCKY RD ;4P
Adder
10.207
274697ROCKY RD ;3P
Adder
2.709
970321AG2-212 GEN
Solar/Wind Harmer
1.358
944201AF1-088_MTX
Adder
121.273
957141AF2-008_MTX
Adder
60.637
NYPJM->LTFIMP_NY
CLTF
4.59
LGEELTFEXP_LGEE->PJM
CLTF
7.503
WECLTFEXP_WEC->PJM
CLTF
3.454
AG2-052LTFEXP_AG2-052->PJM
LTF
0.209
AH1-155LTFEXP_AH1-155->PJM
LTF
0.313
LAGNLTFEXP_LAGN->PJM
CLTF
19.803
CBM South 2LTFEXP_CBM-S2->PJM
CBM
23.164
TVALTFEXP_TVA->PJM
CLTF
10.26
CPLELTFEXP_CPLE->PJM
CLTF
6.38
CBM West 2LTFEXP_CBM-W2->PJM
CBM
132.776
CBM West 1LTFEXP_CBM-W1->PJM
CBM
116.498
CBM South 1LTFEXP_CBM-S1->PJM
CBM
38.98
MECLTFEXP_MEC->PJM
CLTF
15.75
SIGELTFEXP_SIGE->PJM
CLTF
0.547

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.47 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5991.02
MW Contribution:5.07
Bus #Bus NameTypeMW Contribution
24289405MTG1
50/50
11.79
971403AH1-188 GEN
Solar/Wind Harmer
26.09
960001AF2-291 GEN
Solar/Wind Harmer
5.329
971329AH1-144 GEN
Solar/Wind Harmer
19.813
927014AC1-188 GEN
Solar/Wind Harmer
2.379
270399AC1-101 GEN
Solar/Wind Harmer
7.833
270330AC1-082 GEN2
Solar/Wind Harmer
1.393
966391AG1-508 GEN
Solar/Wind Harmer
5.763
972143AH1-644 GEN
Solar/Wind Harmer
16.635
24734705WLF1G3
Adder
9.185
24734905WLF1G5
Adder
9.185
971985AH1-537 GEN
Solar/Wind Harmer
26.201
971981AH1-535 GEN
Solar/Wind Harmer
14.209
270069AE2-166 C O1
Solar/Wind Harmer
3.796
965401AG1-405 GEN
Solar/Wind Harmer
7.637
339211AE2-254 GEN
Solar/Wind Harmer
2.01
972165AH1-665 GEN
Solar/Wind Harmer
10.582
944031AF1-071 GEN
Solar/Wind Harmer
1.178
274823ROCKFORD ;21
Adder
21.377
20092526R32
Solar/Wind Helper
1.053
24686505CER G6
Adder
16.203
24728305BUCHG2
Adder
7.763
3429241JKCT 3G
Adder
15.723
972203AH1-686 GEN
Adder
4.544
970281AG2-184 GEN
Solar/Wind Harmer
34.934
962211AG1-066 GEN
Solar/Wind Harmer
3.823
252524AE2-267 GEN
Solar/Wind Harmer
1.95
962771AG1-126 GEN
Solar/Wind Harmer
38.198
25306009OHH W.
Adder
3.223
253372AE2-315 SEC3
Adder
2.117
253372AE2-315 SEC3
Adder
2.117
274744AC1-111 GEN8
Adder
6.069
238109AE1-109 GEN2
Solar/Wind Helper
0.088
238110AE1-109 GEN3
Solar/Wind Helper
0.088
243186AF1-051 GEN
50/50
12.748
24723005RIVRG1
Adder
37.637
24723105RIVRG2
Adder
37.637
24685805CER G1
Adder
16.117
24685905CER G2
Adder
16.117
270214AC2-123 GEN
Solar/Wind Harmer
3.882
971225AH1-072 GEN
Solar/Wind Harmer
3.33
971227AH1-073 GEN
Solar/Wind Harmer
3.33
270583AD2-179 GEN
Solar/Wind Harmer
16.345
971125AH1-004 GEN
Solar/Wind Harmer
5.257
252519AF1-045_GEN
Solar/Wind Harmer
7.591
252516AE2-318_GEN
Solar/Wind Harmer
5.79
270444AC2-157 GEN1
Solar/Wind Harmer
6.973
253317AC1-085 GEN4
Solar/Wind Harmer
10.168
276916AD2-100_GEN
Solar/Wind Harmer
24.323
253370AE2-315 SEC1
Adder
2.238
25322209TAIT E
Adder
10.707
25322209TAIT E
Adder
10.466
247621Y3-024
Adder
0.262
238120AE2-309 GEN
Solar/Wind Helper
0.43
243186AF1-051 GEN
50/50
12.748
24721805FLATG3
50/50
2.714
24721705FLATG2
50/50
49.755
24723205RIVRG3
Adder
37.637
24686105CER G3
Adder
16.224
970947AG2-589 GEN
Solar/Wind Harmer
3.612
24735205WLF2G2
Adder
9.002
971367AH1-164 GEN
Solar/Wind Harmer
5.069
270336AE1-100 GEN
Solar/Wind Harmer
2.384
971821AH1-427 GEN
Solar/Wind Harmer
13.272
945681AF1-233 GEN
Solar/Wind Harmer
24.878
943111AE2-339 GEN
Solar/Wind Harmer
1.163
943811AF1-049 GEN
Solar/Wind Harmer
4.961
339241AF1-083 GEN
Solar/Wind Harmer
2.171
964901AG1-354 GEN
Solar/Wind Harmer
19.445
270445AC2-157 GEN2
Solar/Wind Harmer
6.973
25194608D.CRK4
Adder
2.039
253432AC1-085 GEN2
Solar/Wind Harmer
0.325
946171AF1-282 GEN
Solar/Wind Harmer
12.138
971313AH1-133 GEN
Solar/Wind Harmer
17.224
270132AB1-180 C
Adder
0.198
971061AG2-657 GEN
Solar/Wind Harmer
14.056
970879AG2-548 GEN
Solar/Wind Harmer
5.786
965411AG1-406 GEN
Solar/Wind Harmer
3.428
270367AC2-061_GEN
Solar/Wind Harmer
4.222
25196108MFTGT2
Adder
1.926
25196108MFTGT2
Adder
1.788
25196408WSDLE3
Adder
10.91
25196308WSDLE2
Adder
10.815
25196208WSDLE1
Adder
10.788
25196708WSDLE6
Adder
10.761
238126S14_GEN_1
Solar/Wind Helper
0.687
960161AF2-307 GEN
Solar/Wind Harmer
8.906
970879AG2-548 GEN
Solar/Wind Harmer
8.293
270186AC1-089 GEN
Solar/Wind Harmer
8.143
970239AG2-162 GEN
Solar/Wind Harmer
14.622
970107AG2-081 GEN
Solar/Wind Harmer
3.942
962581AG1-107 GEN
Solar/Wind Harmer
6.599
961491AF2-440 GEN
Solar/Wind Harmer
2.742
970235AG2-159 GEN
Solar/Wind Harmer
5.2
970235AG2-159 GEN
Solar/Wind Harmer
3.174
339236AF1-050_GEN
Solar/Wind Harmer
2.357
253394AE2-221_GEN
Solar/Wind Harmer
5.367
253398AE2-221_GEN2
Solar/Wind Harmer
5.367
274762LEE CO EC;3U
Adder
10.252
274696ROCKY RD ;4P
Adder
12.409
274697ROCKY RD ;3P
Adder
3.293
944781AF1-143 GEN
Solar/Wind Helper
2.298
203940AF1-140 C
Solar/Wind Helper
0.359
970241AG2-163 GEN
Solar/Wind Harmer
12.594
24728605AND G2
Adder
4.525
970155AG2-107 GEN
Solar/Wind Harmer
16.656
270197AD1-017 GEN1
Solar/Wind Harmer
1.81
941821AE2-187 GEN
Solar/Wind Harmer
6.484
253370AE2-315 SEC1
Adder
2.238
253371AE2-315 SEC2
Adder
2.117
274828WAUKEGAN ;BP
Adder
12.03
274682WAUKEGAN ;7U
Adder
19.567
274745AC1-111 GEN9
Adder
6.069
238185AF2-356 C
Solar/Wind Helper
2.176
316095T157 G97
Solar/Wind Helper
1.094
24318705GVG2
50/50
11.866
270331AC1-082 GEN3
Solar/Wind Harmer
0.823
971687AH1-348 GEN
Solar/Wind Harmer
1.664
971315AH1-136 GEN
Solar/Wind Harmer
3.299
970333AG2-219 GEN
Solar/Wind Harmer
41.959
25196808ZIMRHP
Adder
95.812
25196008MFTGT1
Adder
1.747
3147312GRETNA
Solar/Wind Harmer
-0.003
274761LEE CO EC;2U
Adder
10.252
237046AF1-021 C
Solar/Wind Helper
0.457
23751201ROTHROCK
Solar/Wind Helper
0.71
23583801GRNGAP
Solar/Wind Helper
4.088
20089226LOOKOUT
Solar/Wind Helper
0.539
24722005FLATG5
50/50
2.714
24721905FLATG4
50/50
49.755
960911AF2-382 GEN
Solar/Wind Harmer
12.931
943031AE2-326 GEN
Solar/Wind Harmer
6.109
972103AH1-617 GEN
Solar/Wind Harmer
33.271
270030AE2-140 GEN
Solar/Wind Harmer
26.875
971155AH1-034 GEN
Solar/Wind Harmer
12.926
960741AF2-365 GEN
Solar/Wind Harmer
6.448
25194608D.CRK4
Adder
2.039
253316AC1-085 GEN3
Solar/Wind Harmer
10.168
253433AC1-085 GEN1
Solar/Wind Harmer
6.454
946181AF1-283 GEN
Solar/Wind Harmer
15.78
24728505AND G1
Adder
4.525
970153AG2-106 GEN
Solar/Wind Harmer
16.656
270574AD1-017 GEN2
Solar/Wind Harmer
6.023
253370AE2-315 SEC1
Adder
2.238
253371AE2-315 SEC2
Adder
2.117
274767LEE CO EC;8U
Adder
10.131
274682WAUKEGAN ;7U
Adder
19.567
964991AG1-363 GEN
Solar/Wind Helper
3.709
316097T157 G90
Solar/Wind Helper
1.094
24318705GVG2
50/50
11.866
971191AH1-055 GEN
Solar/Wind Harmer
36.143
972273AH1-721 GEN
Adder
111.61
970093AG2-073 GEN
Solar/Wind Harmer
13.356
970243AG2-164 GEN
Solar/Wind Harmer
34.33
966571AG1-526 GEN
Solar/Wind Harmer
29.484
972167AH1-666 GEN
Solar/Wind Harmer
10.547
962751AG1-124 GEN
Solar/Wind Harmer
11.816
25196008MFTGT1
Adder
1.692
252510AF1-249 C
Solar/Wind Harmer
0.521
3147312GRETNA
Solar/Wind Harmer
-0.014
3146802CHATHAM
Solar/Wind Harmer
-0.013
274729ELWOOD EC;1P
Adder
8.072
237048AF1-022 C
Solar/Wind Helper
0.182
237043AE2-125 C
Solar/Wind Helper
0.163
24721605FLATG1
50/50
2.714
957241AF2-018 GEN
Solar/Wind Harmer
8.259
270400AC1-102 GEN
Solar/Wind Harmer
7.833
24477305BRIDGE
Adder
0.637
270329AC1-082 GEN1
Solar/Wind Harmer
0.821
941621AE2-160 GEN
Adder
5.66
24734805WLF1G4
Adder
9.185
24735105WLF2G1
Adder
9.002
3429211JKCT 2G
Adder
15.52
972163AH1-664 GEN
Solar/Wind Harmer
13.228
339243AC2-075 GEN1
Solar/Wind Harmer
0.595
970455AG2-298 GEN
Solar/Wind Harmer
7.809
25196508WSDLE4
Adder
10.49
270340AC2-060 GEN
Solar/Wind Harmer
3.615
944221AF1-090 GEN
Solar/Wind Harmer
12.754
274746AC1-111 G10
Adder
6.069
23750501ELLIOTTS
Solar/Wind Helper
0.635
944971AF1-162 GEN
Solar/Wind Harmer
13.01
24728205BUCHG1
Adder
7.763
971277AH1-098 GEN
Solar/Wind Harmer
6.642
971073AG2-665 GEN
Solar/Wind Harmer
8.293
971073AG2-665 GEN
Solar/Wind Harmer
5.786
339231AF1-038_GEN
Solar/Wind Harmer
2.394
972045AH1-571 GEN
Solar/Wind Harmer
2.639
339221AD2-048_GEN
Solar/Wind Harmer
2.024
966021AG1-471 GEN
Solar/Wind Harmer
7.099
970653AG2-424 GEN
Solar/Wind Harmer
6.261
970653AG2-424 GEN
Solar/Wind Harmer
2.263
339255AE2-071 GEN
Solar/Wind Harmer
1.372
964571AG1-320 GEN
Solar/Wind Harmer
10.586
252509AD1-136 GEN
Solar/Wind Harmer
0.327
25183208HLCRTG
Solar/Wind Harmer
7.582
25194508D.CRK3
Adder
1.754
24728805RICHG1
Adder
4.412
276911AD2-131_GEN
Solar/Wind Harmer
4.916
274765LEE CO EC;6U
Adder
10.276
274763LEE CO EC;4U
Adder
10.155
274695ROCKY RD ;2P
Adder
12.123
20088926STNY CRK
Solar/Wind Helper
0.747
970091AG2-072 GEN
Adder
103.033
3429421JKCT 10G
Adder
10.993
970273AG2-179 GEN
Solar/Wind Harmer
3.221
971565AH1-281 GEN
Solar/Wind Harmer
2.604
270263AC1-001 GEN
Solar/Wind Harmer
1.245
970149AG2-104 GEN
Solar/Wind Harmer
47.174
274822ROCKFORD ;11
Adder
21.533
235054AD2-180 GEN
Solar/Wind Helper
1.695
235531U2-073 GEN
Solar/Wind Helper
2.733
23562501BACKB
Solar/Wind Helper
0.864
238108AE1-109 GEN1
Solar/Wind Helper
0.088
963741AG1-226 GEN
Solar/Wind Harmer
22.669
339216AC1-074 GEN
Solar/Wind Harmer
2.198
962241AG1-070 GEN
Solar/Wind Harmer
5.799
252507AC2-088 GEN
Solar/Wind Harmer
2.292
270018AE2-047 C O1
Solar/Wind Harmer
1.511
962761AG1-125 GEN
Solar/Wind Harmer
38.198
274766LEE CO EC;7U
Adder
10.131
972235AH1-702 GEN1
Adder
2.767
25326309TAIT D
Adder
1.202
238117U2-030
Solar/Wind Helper
0.288
942891AE2-308 GEN
Solar/Wind Harmer
13.304
972043AH1-570 GEN
Solar/Wind Harmer
3.299
971485AH1-239 GEN
Solar/Wind Harmer
10.499
971081AG2-670 GEN
Solar/Wind Harmer
9.778
964781AG1-341 GEN
Solar/Wind Harmer
13.698
25194408D.CRK1
Adder
9.381
945391AF1-204 GEN
Solar/Wind Harmer
16.499
316217AC1-145 GEN
Solar/Wind Harmer
2.806
316197AC1-042 GEN
Solar/Wind Harmer
2.127
942671AE2-283 GEN
Solar/Wind Harmer
5.728
24728905RICHG2
Adder
4.412
972267AH1-718 GEN
Adder
4.6
274764LEE CO EC;5U
Adder
10.276
274683WAUKEGAN ;8U
Adder
22.951
274683WAUKEGAN ;8U
Adder
19.347
274693ROCKY RD ;1P
Adder
12.003
23585401KL_K28_T16
Solar/Wind Helper
1.267
23652301WDPWR_K20
Solar/Wind Helper
0.133
203955AF1-039 C O1
Solar/Wind Helper
0.352
20083426SW_E13_K22
Solar/Wind Helper
0.051
20084626FORWARD
Solar/Wind Helper
0.323
946071AF1-272 GEN
Solar/Wind Helper
2.428
20088826HIGHLAND
Solar/Wind Helper
0.812
24289405MTG1
50/50
11.79
24686405CER G5
Adder
16.075
270053AF1-130 C
Solar/Wind Harmer
6.909
970913AG2-568 GEN
Solar/Wind Harmer
14.13
270173AC1-122 GEN
Solar/Wind Harmer
2.108
970273AG2-179 GEN
Solar/Wind Harmer
5.144
339250AF1-203 GEN
Solar/Wind Harmer
0.784
962251AG1-071 GEN
Solar/Wind Harmer
7.087
941801AE2-185 GEN
Solar/Wind Harmer
6.484
270356AE2-297 GEN
Solar/Wind Harmer
5.354
270222AC2-111 GEN
Solar/Wind Harmer
9.554
274760LEE CO EC;1U
Adder
10.252
972236AH1-702 GEN2
Adder
2.406
238118U2-030_1
Solar/Wind Helper
0.288
20089126CSLMN_L13
Solar/Wind Helper
0.554
24686205CER G4
Adder
16.139
971461AH1-227 GEN
Solar/Wind Harmer
8.54
971331AH1-145 GEN
Solar/Wind Harmer
15.359
247619Y1-049
Adder
0.704
270346AE1-212 GEN
Solar/Wind Harmer
14.72
958121AF2-106 GEN
Solar/Wind Harmer
7.412
957541AF2-048 GEN
Solar/Wind Harmer
2.373
970519AG2-331 GEN
Solar/Wind Harmer
23.064
970699AG2-449 GEN
Solar/Wind Harmer
15.258
3429391JKCT 9G
Adder
10.993
958171AF2-111 GEN
Solar/Wind Harmer
32.167
270291AC1-194 GEN
Solar/Wind Harmer
13.485
25196608WSDLE5
Adder
10.598
253406AD2-031_GEN
Solar/Wind Harmer
1.534
970193AG2-126 GEN
Solar/Wind Harmer
17.759
24728705AND G3
Adder
9.464
253415AE1-040 GEN
Solar/Wind Harmer
1.318
23750701CROSSCHOOL
Solar/Wind Helper
1.197
238127S14_GEN_2
Solar/Wind Helper
0.687
202652Y1-033 WT C
Solar/Wind Helper
0.534
20089026BF_G21_K23
Solar/Wind Helper
0.438
944201AF1-088_MTX
Adder
145.184
957141AF2-008_MTX
Adder
72.592
NYPJM->LTFIMP_NY
CLTF
5.271
LGEELTFEXP_LGEE->PJM
CLTF
8.989
WECLTFEXP_WEC->PJM
CLTF
4.2
AG2-052LTFEXP_AG2-052->PJM
LTF
0.253
AH1-155LTFEXP_AH1-155->PJM
LTF
0.38
LAGNLTFEXP_LAGN->PJM
CLTF
24.37
CBM South 2LTFEXP_CBM-S2->PJM
CBM
29.03
TVALTFEXP_TVA->PJM
CLTF
12.655
CPLELTFEXP_CPLE->PJM
CLTF
7.791
CBM West 2LTFEXP_CBM-W2->PJM
CBM
162.06
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.592
CBM South 1LTFEXP_CBM-S1->PJM
CBM
47.815
MECLTFEXP_MEC->PJM
CLTF
19.173
SIGELTFEXP_SIGE->PJM
CLTF
0.659

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P1-2_#7422_16_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7422_16_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.56 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5885.34
MW Contribution:3.54
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
2.714
957241AF2-018 GEN
Solar/Wind Harmer
-0.002
270400AC1-102 GEN
Solar/Wind Harmer
4.077
24477305BRIDGE
Adder
0.637
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
941621AE2-160 GEN
Adder
5.66
24734805WLF1G4
Adder
9.185
270399AC1-101 GEN
Solar/Wind Harmer
4.077
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
966391AG1-508 GEN
Solar/Wind Harmer
1.802
972143AH1-644 GEN
Solar/Wind Harmer
12.573
24734705WLF1G3
Adder
9.185
24734905WLF1G5
Adder
9.185
971985AH1-537 GEN
Solar/Wind Harmer
3.047
971981AH1-535 GEN
Solar/Wind Harmer
6.609
270069AE2-166 C O1
Solar/Wind Harmer
0.007
965401AG1-405 GEN
Solar/Wind Harmer
5.328
339211AE2-254 GEN
Solar/Wind Harmer
0.004
972165AH1-665 GEN
Solar/Wind Harmer
8.229
24386405FR-21G C
Solar/Wind Harmer
0.001
24725505WLD G2 C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.002
270181AB1-006 GEN2
Solar/Wind Harmer
0
276656WTG2_EQ
Solar/Wind Harmer
0
941731AE2-173 GEN
Solar/Wind Harmer
6.503
971029AG2-637 GEN
Solar/Wind Harmer
11.666
946321AF1-296 GEN
Solar/Wind Harmer
4.345
253349AC2-067 GEN
Solar/Wind Harmer
2.438
971611AH1-305 GEN
Solar/Wind Harmer
4.596
274823ROCKFORD ;21
Adder
21.377
971171AH1-044 GEN
Solar/Wind Harmer
15.301
971675AH1-338 GEN
Solar/Wind Harmer
2.979
945581AF1-223 GEN
Solar/Wind Harmer
0.001
24735105WLF2G1
Adder
9.002
3429211JKCT 2G
Adder
15.52
972163AH1-664 GEN
Solar/Wind Harmer
10.275
339243AC2-075 GEN1
Solar/Wind Harmer
0.002
970455AG2-298 GEN
Solar/Wind Harmer
6.053
25196508WSDLE4
Adder
10.49
270340AC2-060 GEN
Solar/Wind Harmer
0.01
944221AF1-090 GEN
Solar/Wind Harmer
4.776
963841AG1-237 GEN
Solar/Wind Harmer
3.474
24386205FR-12G C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270269AC2-059
Solar/Wind Harmer
0.004
970115AG2-085 GEN
Solar/Wind Harmer
3.124
276655WTG1_EQ
Solar/Wind Harmer
0.003
253400AC2-068 GEN
Solar/Wind Harmer
0.981
24318705GVG2
50/50
11.866
971191AH1-055 GEN
Solar/Wind Harmer
29.418
972273AH1-721 GEN
Adder
111.61
970093AG2-073 GEN
Solar/Wind Harmer
9.318
970243AG2-164 GEN
Solar/Wind Harmer
5.432
966571AG1-526 GEN
Solar/Wind Harmer
20.57
972167AH1-666 GEN
Solar/Wind Harmer
7.359
962751AG1-124 GEN
Solar/Wind Harmer
8.092
25196008MFTGT1
Adder
1.692
252510AF1-249 C
Solar/Wind Harmer
0.067
3147312GRETNA
Solar/Wind Harmer
0.123
3146802CHATHAM
Solar/Wind Harmer
0.115
942481AE2-261 GEN
Solar/Wind Harmer
24.109
276621W2-048 GEN
Solar/Wind Harmer
0.403
276838X2-022 GEN2
Solar/Wind Harmer
0.45
971993AH1-541 GEN
Solar/Wind Harmer
3.68
942111AE2-223 GEN
Solar/Wind Harmer
2.536
276157O29GEN1
Solar/Wind Harmer
1.248
274858EASY ROAD;U2
Solar/Wind Harmer
0.002
970571AG2-364 GEN
Solar/Wind Harmer
15.368
276889AE2-281 GEN
Solar/Wind Harmer
0.001
270016AE1-250 BESS
Solar/Wind Harmer
0.004
274850MENDOTA H;RU
Solar/Wind Harmer
0.09
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.137
274729ELWOOD EC;1P
Adder
8.072
237048AF1-022 C
Solar/Wind Helper
0.182
237043AE2-125 C
Solar/Wind Helper
0.163
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
0.329
944971AF1-162 GEN
Solar/Wind Harmer
13.01
24728205BUCHG1
Adder
7.763
971277AH1-098 GEN
Solar/Wind Harmer
4.634
971073AG2-665 GEN
Solar/Wind Harmer
8.448
972045AH1-571 GEN
Solar/Wind Harmer
1.918
339221AD2-048_GEN
Solar/Wind Harmer
0.006
966021AG1-471 GEN
Solar/Wind Harmer
4.953
970653AG2-424 GEN
Solar/Wind Harmer
4.368
970653AG2-424 GEN
Solar/Wind Harmer
2.263
339255AE2-071 GEN
Solar/Wind Harmer
-0.148
964571AG1-320 GEN
Solar/Wind Harmer
8.226
252509AD1-136 GEN
Solar/Wind Harmer
0.045
25183208HLCRTG
Solar/Wind Harmer
0.014
25194508D.CRK3
Adder
1.754
24728805RICHG1
Adder
4.412
276911AD2-131_GEN
Solar/Wind Harmer
1.118
24379505HDWTR1G C
Solar/Wind Harmer
0.003
270383AD1-128 GEN
Solar/Wind Harmer
0.005
945421AF1-207 GEN
Solar/Wind Harmer
0.001
960441AF2-335 GEN
Solar/Wind Harmer
7.811
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
276646AC1-214 GEN2
Solar/Wind Harmer
0.304
970885AG2-551 GEN
Solar/Wind Harmer
2.568
274765LEE CO EC;6U
Adder
10.276
274763LEE CO EC;4U
Adder
10.155
270031AE2-169
Solar/Wind Harmer
4.224
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
274695ROCKY RD ;2P
Adder
12.123
20088926STNY CRK
Solar/Wind Helper
0.747
942891AE2-308 GEN
Solar/Wind Harmer
9.282
972043AH1-570 GEN
Solar/Wind Harmer
2.394
971485AH1-239 GEN
Solar/Wind Harmer
7.325
971081AG2-670 GEN
Solar/Wind Harmer
6.822
964781AG1-341 GEN
Solar/Wind Harmer
9.557
25194408D.CRK1
Adder
9.381
945391AF1-204 GEN
Solar/Wind Harmer
8.776
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.002
942671AE2-283 GEN
Solar/Wind Harmer
3.83
24728905RICHG2
Adder
4.412
926881AC1-175 GEN
Solar/Wind Harmer
0.001
966841AG1-555 GEN
Solar/Wind Harmer
0.9
960611AF2-352 GEN
Solar/Wind Harmer
2.614
276782AC1-033 GEN
Solar/Wind Harmer
0.001
276708O09 GEN2
Solar/Wind Harmer
0.275
972267AH1-718 GEN
Adder
4.6
970883AG2-550 GEN
Solar/Wind Harmer
7.705
274764LEE CO EC;5U
Adder
10.276
270599AE1-208 GEN
Solar/Wind Harmer
7.04
274683WAUKEGAN ;8U
Adder
22.951
274683WAUKEGAN ;8U
Adder
19.347
274693ROCKY RD ;1P
Adder
12.003
23585401KL_K28_T16
Solar/Wind Helper
1.267
23652301WDPWR_K20
Solar/Wind Helper
0.133
203955AF1-039 C O1
Solar/Wind Helper
0.352
243186AF1-051 GEN
50/50
12.748
24721805FLATG3
50/50
2.714
24721705FLATG2
50/50
49.755
24723205RIVRG3
Adder
37.637
24686105CER G3
Adder
16.224
970947AG2-589 GEN
Solar/Wind Harmer
0.42
24735205WLF2G2
Adder
9.002
971367AH1-164 GEN
Solar/Wind Harmer
3.536
270336AE1-100 GEN
Solar/Wind Harmer
0.005
971821AH1-427 GEN
Solar/Wind Harmer
9.259
945681AF1-233 GEN
Solar/Wind Harmer
17.357
943811AF1-049 GEN
Solar/Wind Harmer
-0.002
964901AG1-354 GEN
Solar/Wind Harmer
13.566
24318705GVG2
50/50
11.866
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
971687AH1-348 GEN
Solar/Wind Harmer
1.161
971315AH1-136 GEN
Solar/Wind Harmer
2.301
970333AG2-219 GEN
Solar/Wind Harmer
6.64
25196808ZIMRHP
Adder
95.812
25196008MFTGT1
Adder
1.747
3147312GRETNA
Solar/Wind Harmer
0.031
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0.001
274880W4-005 GEN4
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.003
972175AH1-670 GEN
Solar/Wind Harmer
6.537
270032AE2-172
Solar/Wind Harmer
5.233
270005AE1-210 C O1
Solar/Wind Harmer
1.696
970825AG2-519 GEN
Solar/Wind Harmer
2.773
939741AE1-205 GEN
Solar/Wind Harmer
10.926
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
9.649
276158O29GEN2
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
10.252
970569AG2-363 GEN
Solar/Wind Harmer
23.052
971997AH1-543 GEN
Solar/Wind Harmer
4.011
276861AD2-134 GEN
Solar/Wind Harmer
0.137
945371AF1-202 GEN
Solar/Wind Harmer
0.001
237046AF1-021 C
Solar/Wind Helper
0.457
23751201ROTHROCK
Solar/Wind Helper
0.71
23583801GRNGAP
Solar/Wind Helper
4.088
20089226LOOKOUT
Solar/Wind Helper
0.539
270445AC2-157 GEN2
Solar/Wind Harmer
0.004
25194608D.CRK4
Adder
2.039
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
8.469
24728605AND G2
Adder
4.525
970155AG2-107 GEN
Solar/Wind Harmer
20.57
270197AD1-017 GEN1
Solar/Wind Harmer
1.016
941821AE2-187 GEN
Solar/Wind Harmer
4.925
970613AG2-401 GEN
Solar/Wind Harmer
5.842
970291AG2-192 GEN
Solar/Wind Harmer
1.021
965031AG1-367 GEN
Solar/Wind Harmer
7.829
253370AE2-315 SEC1
Adder
2.238
253371AE2-315 SEC2
Adder
2.117
274877BISHOP HL;1U
Solar/Wind Harmer
0.26
960071AF2-298 GEN
Solar/Wind Harmer
3.815
957471AF2-041 GEN
Solar/Wind Harmer
22.952
274828WAUKEGAN ;BP
Adder
12.03
274682WAUKEGAN ;7U
Adder
19.567
274745AC1-111 GEN9
Adder
6.069
238185AF2-356 C
Solar/Wind Helper
2.176
316095T157 G97
Solar/Wind Helper
1.094
24722005FLATG5
50/50
2.714
24721905FLATG4
50/50
49.755
960911AF2-382 GEN
Solar/Wind Harmer
9.021
943031AE2-326 GEN
Solar/Wind Harmer
6.109
972103AH1-617 GEN
Solar/Wind Harmer
23.212
270030AE2-140 GEN
Solar/Wind Harmer
18.75
971155AH1-034 GEN
Solar/Wind Harmer
10.521
960741AF2-365 GEN
Solar/Wind Harmer
4.499
25194608D.CRK4
Adder
2.039
253316AC1-085 GEN3
Solar/Wind Harmer
0.005
253433AC1-085 GEN1
Solar/Wind Harmer
0.004
946181AF1-283 GEN
Solar/Wind Harmer
11.009
24728505AND G1
Adder
4.525
970153AG2-106 GEN
Solar/Wind Harmer
20.57
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
276668AB2-070 GEN1
Solar/Wind Harmer
0.29
24755605MDL-5G
Solar/Wind Harmer
0.001
247642Z2-115 C
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
0.864
970291AG2-192 GEN
Solar/Wind Harmer
0.786
253370AE2-315 SEC1
Adder
2.238
253371AE2-315 SEC2
Adder
2.117
946031AF1-268 GEN
Solar/Wind Harmer
7.391
3147123OTTER R
Solar/Wind Harmer
0.087
274767LEE CO EC;8U
Adder
10.131
959091AF2-200 GEN
Solar/Wind Harmer
15.301
274682WAUKEGAN ;7U
Adder
19.567
964991AG1-363 GEN
Solar/Wind Helper
3.709
24289405MTG1
50/50
11.79
971403AH1-188 GEN
Solar/Wind Harmer
18.202
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
971329AH1-144 GEN
Solar/Wind Harmer
9.676
927014AC1-188 GEN
Solar/Wind Harmer
0.006
970091AG2-072 GEN
Adder
103.033
3429421JKCT 10G
Adder
10.993
970273AG2-179 GEN
Solar/Wind Harmer
3.221
971565AH1-281 GEN
Solar/Wind Harmer
1.817
270263AC1-001 GEN
Solar/Wind Harmer
0.833
970149AG2-104 GEN
Solar/Wind Harmer
34.791
970773AG2-487 GEN
Solar/Wind Harmer
1.447
963741AG1-226 GEN
Solar/Wind Harmer
19.103
24791305MDL-5G
Solar/Wind Harmer
0.001
274854TWINGROVE;U2
Solar/Wind Harmer
0.003
276726Z2-087_GEN
Solar/Wind Harmer
0.003
971475AH1-234 GEN
Solar/Wind Harmer
3.722
970819AG2-516 GEN
Solar/Wind Harmer
9.198
274822ROCKFORD ;11
Adder
21.533
959081AF2-199 GEN
Solar/Wind Harmer
7.651
971067AG2-660 GEN
Solar/Wind Harmer
2.55
235054AD2-180 GEN
Solar/Wind Helper
1.695
235531U2-073 GEN
Solar/Wind Helper
2.733
23562501BACKB
Solar/Wind Helper
0.864
238108AE1-109 GEN1
Solar/Wind Helper
0.088
316097T157 G90
Solar/Wind Helper
1.094
972203AH1-686 GEN
Adder
4.544
970281AG2-184 GEN
Solar/Wind Harmer
24.373
252524AE2-267 GEN
Solar/Wind Harmer
0.003
962771AG1-126 GEN
Solar/Wind Harmer
32.213
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.29
276848AB2-070 GEN3
Solar/Wind Harmer
0.289
970289AG2-191 GEN
Solar/Wind Harmer
1.493
959341AF2-225 GEN
Solar/Wind Harmer
8.194
25306009OHH W.
Adder
3.223
253372AE2-315 SEC3
Adder
2.117
253372AE2-315 SEC3
Adder
2.117
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
970169AG2-114 GEN
Solar/Wind Harmer
7.718
961011AF2-392 GEN
Solar/Wind Harmer
4.519
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274744AC1-111 GEN8
Adder
6.069
238109AE1-109 GEN2
Solar/Wind Helper
0.088
238110AE1-109 GEN3
Solar/Wind Helper
0.088
24686505CER G6
Adder
16.203
24728305BUCHG2
Adder
7.763
3429241JKCT 3G
Adder
15.723
339216AC1-074 GEN
Solar/Wind Harmer
0.25
962241AG1-070 GEN
Solar/Wind Harmer
4.9
252507AC2-088 GEN
Solar/Wind Harmer
0.405
270018AE2-047 C O1
Solar/Wind Harmer
0.004
962761AG1-125 GEN
Solar/Wind Harmer
32.213
965911AG1-460 GEN
Solar/Wind Harmer
1.613
276615X2-022 GEN
Solar/Wind Harmer
0.084
963831AG1-236 GEN
Solar/Wind Harmer
3.11
24385905FR-11G C
Solar/Wind Harmer
0.002
276903AD2-071 C
Solar/Wind Harmer
8.845
274857EASY ROAD;U1
Solar/Wind Harmer
0.002
274766LEE CO EC;7U
Adder
10.131
972235AH1-702 GEN1
Adder
2.767
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
25326309TAIT D
Adder
1.202
939401AE1-172 GEN
Solar/Wind Harmer
5.72
238117U2-030
Solar/Wind Helper
0.288
20088826HIGHLAND
Solar/Wind Helper
0.812
24686205CER G4
Adder
16.139
971461AH1-227 GEN
Solar/Wind Harmer
5.958
971331AH1-145 GEN
Solar/Wind Harmer
15.359
247619Y1-049
Adder
0.704
270346AE1-212 GEN
Solar/Wind Harmer
10.08
958121AF2-106 GEN
Solar/Wind Harmer
0.001
970519AG2-331 GEN
Solar/Wind Harmer
24.144
970699AG2-449 GEN
Solar/Wind Harmer
2.322
3429391JKCT 9G
Adder
10.993
958171AF2-111 GEN
Solar/Wind Harmer
22.442
270291AC1-194 GEN
Solar/Wind Harmer
7.02
25196608WSDLE5
Adder
10.598
253406AD2-031_GEN
Solar/Wind Harmer
0.624
970193AG2-126 GEN
Solar/Wind Harmer
12.39
24728705AND G3
Adder
9.464
253415AE1-040 GEN
Solar/Wind Harmer
0.003
270437AC2-090 C
Solar/Wind Harmer
0.004
970781AG2-491 GEN
Solar/Wind Harmer
7.866
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
959611AF2-252 GEN
Solar/Wind Harmer
2.614
958821AF2-173 GEN
Solar/Wind Harmer
10.961
270273AD2-016 GEN
Solar/Wind Harmer
0.81
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
274855GSG-6 ;RU
Solar/Wind Harmer
0.28
23750701CROSSCHOOL
Solar/Wind Helper
1.197
238127S14_GEN_2
Solar/Wind Helper
0.687
202652Y1-033 WT C
Solar/Wind Helper
0.534
20089026BF_G21_K23
Solar/Wind Helper
0.438
243186AF1-051 GEN
50/50
12.748
24723005RIVRG1
Adder
37.637
24723105RIVRG2
Adder
37.637
24685805CER G1
Adder
16.117
24685905CER G2
Adder
16.117
971225AH1-072 GEN
Solar/Wind Harmer
2.323
971227AH1-073 GEN
Solar/Wind Harmer
2.323
270583AD2-179 GEN
Solar/Wind Harmer
11.403
971125AH1-004 GEN
Solar/Wind Harmer
3.667
252519AF1-045_GEN
Solar/Wind Harmer
7.591
252516AE2-318_GEN
Solar/Wind Harmer
6.733
270444AC2-157 GEN1
Solar/Wind Harmer
0.004
971587AH1-292 GEN
Solar/Wind Harmer
6.388
253317AC1-085 GEN4
Solar/Wind Harmer
0.005
276916AD2-100_GEN
Solar/Wind Harmer
16.969
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
971613AH1-306 GEN
Solar/Wind Harmer
3.767
971313AH1-133 GEN
Solar/Wind Harmer
12.016
270132AB1-180 C
Adder
0.198
971061AG2-657 GEN
Solar/Wind Harmer
6.864
970879AG2-548 GEN
Solar/Wind Harmer
8.448
965411AG1-406 GEN
Solar/Wind Harmer
3.428
270367AC2-061_GEN
Solar/Wind Harmer
0.007
25196108MFTGT2
Adder
1.926
25196108MFTGT2
Adder
1.788
25196408WSDLE3
Adder
10.91
25196308WSDLE2
Adder
10.815
25196208WSDLE1
Adder
10.788
25196708WSDLE6
Adder
10.761
270240V3-007_GEN2
Solar/Wind Harmer
0.002
276174W4-005 GEN2
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
270594AE1-207 GEN
Solar/Wind Harmer
8.791
971673AH1-337 GEN
Solar/Wind Harmer
5.07
957751AF2-069 GEN
Solar/Wind Harmer
0.255
270543AE2-219 C
Solar/Wind Harmer
0.005
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
971681AH1-341 GEN
Solar/Wind Harmer
12.366
276612AE2-035 GEN
Solar/Wind Harmer
0.002
238126S14_GEN_1
Solar/Wind Helper
0.687
24289405MTG1
50/50
11.79
24686405CER G5
Adder
16.075
270053AF1-130 C
Solar/Wind Harmer
2.937
970913AG2-568 GEN
Solar/Wind Harmer
9.858
270173AC1-122 GEN
Solar/Wind Harmer
0.435
970273AG2-179 GEN
Solar/Wind Harmer
5.522
339250AF1-203 GEN
Solar/Wind Harmer
0.001
962251AG1-071 GEN
Solar/Wind Harmer
5.619
941801AE2-185 GEN
Solar/Wind Harmer
4.925
270356AE2-297 GEN
Solar/Wind Harmer
0.011
270222AC2-111 GEN
Solar/Wind Harmer
4.144
276686W4-005 GEN3
Solar/Wind Harmer
0.001
972173AH1-669 GEN
Solar/Wind Harmer
3.965
965091AG1-374 GEN
Solar/Wind Harmer
23.525
270004AE1-209 GEN
Solar/Wind Harmer
1.696
965931AG1-462 GEN
Solar/Wind Harmer
19.808
274878BISHOP HL;2U
Solar/Wind Harmer
0.26
970191AG2-125 GEN
Solar/Wind Harmer
1.992
274760LEE CO EC;1U
Adder
10.252
972236AH1-702 GEN2
Adder
2.406
238118U2-030_1
Solar/Wind Helper
0.288
20089126CSLMN_L13
Solar/Wind Helper
0.554
253370AE2-315 SEC1
Adder
2.238
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276741O09 GEN1
Solar/Wind Harmer
0.275
25322209TAIT E
Adder
10.707
25322209TAIT E
Adder
10.466
971341AH1-150 GEN
Solar/Wind Harmer
15.301
971343AH1-151 GEN
Solar/Wind Harmer
15.301
247621Y3-024
Adder
0.262
238120AE2-309 GEN
Solar/Wind Helper
0.43
20083426SW_E13_K22
Solar/Wind Helper
0.051
20084626FORWARD
Solar/Wind Helper
0.323
946071AF1-272 GEN
Solar/Wind Helper
2.428
20092526R32
Solar/Wind Helper
1.053
926823AC1-168 GEN
Solar/Wind Harmer
1.307
971609AH1-304 GEN
Solar/Wind Harmer
1.254
274746AC1-111 G10
Adder
6.069
23750501ELLIOTTS
Solar/Wind Helper
0.635
960161AF2-307 GEN
Solar/Wind Harmer
6.387
270186AC1-089 GEN
Solar/Wind Harmer
0.006
970239AG2-162 GEN
Solar/Wind Harmer
2.322
970107AG2-081 GEN
Solar/Wind Harmer
2.751
962581AG1-107 GEN
Solar/Wind Harmer
0.002
970235AG2-159 GEN
Solar/Wind Harmer
5.533
970235AG2-159 GEN
Solar/Wind Harmer
3.174
253394AE2-221_GEN
Solar/Wind Harmer
0.01
253398AE2-221_GEN2
Solar/Wind Harmer
0.01
970241AG2-163 GEN
Solar/Wind Harmer
4.709
270209AC1-174_GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
970825AG2-519 GEN
Solar/Wind Harmer
8.658
276645AC1-214 GEN1
Solar/Wind Harmer
0.304
276603SUBLETTE C
Solar/Wind Harmer
0
274762LEE CO EC;3U
Adder
10.252
938861AE1-114 GEN
Solar/Wind Harmer
4.353
274856ECOGROVE ;U1
Solar/Wind Harmer
0.181
276611AD2-172 GEN
Solar/Wind Harmer
0.002
270013AE1-250 PV
Solar/Wind Harmer
0.004
274696ROCKY RD ;4P
Adder
12.409
274697ROCKY RD ;3P
Adder
3.293
944781AF1-143 GEN
Solar/Wind Helper
2.298
203940AF1-140 C
Solar/Wind Helper
0.359
944201AF1-088_MTX
Adder
145.184
957141AF2-008_MTX
Adder
72.592
NYPJM->LTFIMP_NY
CLTF
5.271
LGEELTFEXP_LGEE->PJM
CLTF
8.989
WECLTFEXP_WEC->PJM
CLTF
4.2
AG2-052LTFEXP_AG2-052->PJM
LTF
0.253
AH1-155LTFEXP_AH1-155->PJM
LTF
0.38
LAGNLTFEXP_LAGN->PJM
CLTF
24.37
CBM South 2LTFEXP_CBM-S2->PJM
CBM
29.03
TVALTFEXP_TVA->PJM
CLTF
12.655
CPLELTFEXP_CPLE->PJM
CLTF
7.791
CBM West 2LTFEXP_CBM-W2->PJM
CBM
162.06
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.592
CBM South 1LTFEXP_CBM-S1->PJM
CBM
47.815
MECLTFEXP_MEC->PJM
CLTF
19.173
SIGELTFEXP_SIGE->PJM
CLTF
0.659

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P7-1_#10944___SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10944___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:106.16 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5863.47
MW Contribution:3.82
Bus #Bus NameTypeMW Contribution
243186AF1-051 GEN
50/50
12.611
24721805FLATG3
50/50
2.658
24721705FLATG2
50/50
48.723
24723205RIVRG3
Adder
37.09
970947AG2-589 GEN
Solar/Wind Harmer
3.922
24686105CER G3
Adder
16.263
24735205WLF2G2
Adder
7.999
945681AF1-233 GEN
Solar/Wind Harmer
22.966
971821AH1-427 GEN
Solar/Wind Harmer
12.078
943111AE2-339 GEN
Solar/Wind Harmer
1.064
339241AF1-083 GEN
Solar/Wind Harmer
1.967
964901AG1-354 GEN
Solar/Wind Harmer
17.575
25194608D.CRK4
Adder
1.865
270336AE1-100 GEN
Solar/Wind Harmer
1.949
270445AC2-157 GEN2
Solar/Wind Harmer
6.293
253432AC1-085 GEN2
Solar/Wind Harmer
0.293
946171AF1-282 GEN
Solar/Wind Harmer
10.953
971367AH1-164 GEN
Solar/Wind Harmer
3.823
943811AF1-049 GEN
Solar/Wind Harmer
4.073
24728605AND G2
Adder
4.036
253370AE2-315 SEC1
Adder
1.951
253371AE2-315 SEC2
Adder
1.845
274828WAUKEGAN ;BP
Adder
10.429
274682WAUKEGAN ;7U
Adder
16.961
274745AC1-111 GEN9
Adder
5.257
241966AE1-183 GEN
Solar/Wind Helper
0.245
238185AF2-356 C
Solar/Wind Helper
2.079
964201AG1-281 GEN
Solar/Wind Helper
0.449
24289405MTG1
50/50
11.76
960001AF2-291 GEN
Solar/Wind Harmer
6.065
971403AH1-188 GEN
Solar/Wind Harmer
24.803
927014AC1-188 GEN
Solar/Wind Harmer
2.455
971329AH1-144 GEN
Solar/Wind Harmer
16.096
970091AG2-072 GEN
Adder
94.679
3429421JKCT 10G
Adder
10.046
970273AG2-179 GEN
Solar/Wind Harmer
2.912
971565AH1-281 GEN
Solar/Wind Harmer
2.371
270263AC1-001 GEN
Solar/Wind Harmer
1.114
963741AG1-226 GEN
Solar/Wind Harmer
46.021
274822ROCKFORD ;11
Adder
18.707
235054AD2-180 GEN
Solar/Wind Helper
1.616
23562501BACKB
Solar/Wind Helper
0.85
235531U2-073 GEN
Solar/Wind Helper
2.555
20094526CT_V3-030
Solar/Wind Helper
0.44
970149AG2-104 GEN
Solar/Wind Harmer
20.717
24686505CER G6
Adder
16.242
24728305BUCHG2
Adder
6.985
3429241JKCT 3G
Adder
14.375
339216AC1-074 GEN
Solar/Wind Harmer
2.018
252507AC2-088 GEN
Solar/Wind Harmer
2.122
962241AG1-070 GEN
Solar/Wind Harmer
5.234
965911AG1-460 GEN
Solar/Wind Harmer
1.423
962761AG1-125 GEN
Solar/Wind Harmer
40.758
274766LEE CO EC;7U
Adder
8.813
972235AH1-702 GEN1
Adder
2.404
25326309TAIT D
Adder
1.04
238117U2-030
Solar/Wind Helper
0.272
20088826HIGHLAND
Solar/Wind Helper
0.835
24722005FLATG5
50/50
2.658
24721905FLATG4
50/50
48.723
960911AF2-382 GEN
Solar/Wind Harmer
11.728
972103AH1-617 GEN
Solar/Wind Harmer
30.886
943031AE2-326 GEN
Solar/Wind Harmer
5.058
971155AH1-034 GEN
Solar/Wind Harmer
11.668
960741AF2-365 GEN
Solar/Wind Harmer
5.83
25194608D.CRK4
Adder
1.865
270030AE2-140 GEN
Solar/Wind Harmer
22.032
253316AC1-085 GEN3
Solar/Wind Harmer
9.175
253433AC1-085 GEN1
Solar/Wind Harmer
5.824
946181AF1-283 GEN
Solar/Wind Harmer
14.239
24728505AND G1
Adder
4.036
253370AE2-315 SEC1
Adder
1.951
253371AE2-315 SEC2
Adder
1.845
274767LEE CO EC;8U
Adder
8.813
274682WAUKEGAN ;7U
Adder
16.961
235058AG1-386 C
Solar/Wind Helper
0.451
964991AG1-363 GEN
Solar/Wind Helper
3.463
203818AF1-086 GEN
Solar/Wind Helper
1.57
24686205CER G4
Adder
16.177
957541AF2-048 GEN
Solar/Wind Harmer
2.449
971461AH1-227 GEN
Solar/Wind Harmer
7.809
270346AE1-212 GEN
Solar/Wind Harmer
13.257
971331AH1-145 GEN
Solar/Wind Harmer
12.477
247619Y1-049
Adder
0.564
958121AF2-106 GEN
Solar/Wind Harmer
5.853
970519AG2-331 GEN
Solar/Wind Harmer
21.141
970699AG2-449 GEN
Solar/Wind Harmer
13.986
270291AC1-194 GEN
Solar/Wind Harmer
12.828
3429391JKCT 9G
Adder
10.046
958171AF2-111 GEN
Solar/Wind Harmer
29.515
25196608WSDLE5
Adder
9.681
253406AD2-031_GEN
Solar/Wind Harmer
1.378
970193AG2-126 GEN
Solar/Wind Harmer
15.807
24728705AND G3
Adder
8.441
253415AE1-040 GEN
Solar/Wind Harmer
1.167
254305AE2-115 C
Solar/Wind Helper
0.211
202652Y1-033 WT C
Solar/Wind Helper
0.534
23750701CROSSCHOOL
Solar/Wind Helper
1.129
20089026BF_G21_K23
Solar/Wind Helper
0.443
238127S14_GEN_2
Solar/Wind Helper
0.64
942891AE2-308 GEN
Solar/Wind Harmer
12.168
972043AH1-570 GEN
Solar/Wind Harmer
3.032
971485AH1-239 GEN
Solar/Wind Harmer
9.472
971081AG2-670 GEN
Solar/Wind Harmer
8.855
964781AG1-341 GEN
Solar/Wind Harmer
12.366
25194408D.CRK1
Adder
8.581
945391AF1-204 GEN
Solar/Wind Harmer
14.686
24728905RICHG2
Adder
3.931
972267AH1-718 GEN
Adder
4.004
274764LEE CO EC;5U
Adder
8.939
274683WAUKEGAN ;8U
Adder
19.896
274683WAUKEGAN ;8U
Adder
16.771
274693ROCKY RD ;1P
Adder
10.405
23652301WDPWR_K20
Solar/Wind Helper
0.139
241967AE2-285_GEN
Solar/Wind Helper
0.613
23585401KL_K28_T16
Solar/Wind Helper
1.223
203955AF1-039 C O1
Solar/Wind Helper
0.352
946071AF1-272 GEN
Solar/Wind Helper
2.537
20083426SW_E13_K22
Solar/Wind Helper
0.052
20084626FORWARD
Solar/Wind Helper
0.332
24318705GVG2
50/50
11.739
971191AH1-055 GEN
Solar/Wind Harmer
39.064
970093AG2-073 GEN
Solar/Wind Harmer
12.205
970243AG2-164 GEN
Solar/Wind Harmer
31.468
972167AH1-666 GEN
Solar/Wind Harmer
9.735
972273AH1-721 GEN
Adder
101.075
966571AG1-526 GEN
Solar/Wind Harmer
26.852
25196008MFTGT1
Adder
1.55
252510AF1-249 C
Solar/Wind Harmer
0.477
942481AE2-261 GEN
Solar/Wind Harmer
30.502
274729ELWOOD EC;1P
Adder
6.986
237048AF1-022 C
Solar/Wind Helper
0.187
237043AE2-125 C
Solar/Wind Helper
0.173
972203AH1-686 GEN
Adder
4.44
970281AG2-184 GEN
Solar/Wind Harmer
32.43
962211AG1-066 GEN
Solar/Wind Harmer
3.527
252524AE2-267 GEN
Solar/Wind Harmer
1.782
962771AG1-126 GEN
Solar/Wind Harmer
40.758
25306009OHH W.
Adder
2.813
253372AE2-315 SEC3
Adder
1.845
253372AE2-315 SEC3
Adder
1.845
274744AC1-111 GEN8
Adder
5.257
241997AF1-093 GEN
Solar/Wind Helper
0.245
20091526CHSTN_FL
Solar/Wind Helper
0.54
20090526Q36
Solar/Wind Helper
0.964
203993AD2-133_GEN1
Solar/Wind Helper
0.964
24721605FLATG1
50/50
2.658
270329AC1-082 GEN1
Solar/Wind Harmer
0.889
24477305BRIDGE
Adder
0.635
957241AF2-018 GEN
Solar/Wind Harmer
7.929
270400AC1-102 GEN
Solar/Wind Harmer
7.483
941621AE2-160 GEN
Adder
5.566
24734805WLF1G4
Adder
8.169
24735105WLF2G1
Adder
7.999
972163AH1-664 GEN
Solar/Wind Harmer
12.214
3429211JKCT 2G
Adder
14.189
339243AC2-075 GEN1
Solar/Wind Harmer
0.546
970455AG2-298 GEN
Solar/Wind Harmer
7.102
25196508WSDLE4
Adder
9.582
270340AC2-060 GEN
Solar/Wind Harmer
3.233
944221AF1-090 GEN
Solar/Wind Harmer
11.289
274746AC1-111 G10
Adder
5.257
23750501ELLIOTTS
Solar/Wind Helper
0.642
254304AE2-114 C
Solar/Wind Helper
0.211
241982AE2-343 S C
Solar/Wind Helper
0.214
203961AE2-224 GEN
Solar/Wind Helper
2.23
270132AB1-180 C
Adder
0.184
971313AH1-133 GEN
Solar/Wind Harmer
15.282
971061AG2-657 GEN
Solar/Wind Harmer
13.752
970879AG2-548 GEN
Solar/Wind Harmer
5.647
270367AC2-061_GEN
Solar/Wind Harmer
3.956
965411AG1-406 GEN
Solar/Wind Harmer
3.11
25196108MFTGT2
Adder
1.765
25196108MFTGT2
Adder
1.639
25196408WSDLE3
Adder
9.966
25196308WSDLE2
Adder
9.88
25196208WSDLE1
Adder
9.855
25196708WSDLE6
Adder
9.83
238126S14_GEN_1
Solar/Wind Helper
0.64
270330AC1-082 GEN2
Solar/Wind Harmer
1.51
270399AC1-101 GEN
Solar/Wind Harmer
7.483
972143AH1-644 GEN
Solar/Wind Harmer
15.443
971985AH1-537 GEN
Solar/Wind Harmer
26.909
24734705WLF1G3
Adder
8.169
24734905WLF1G5
Adder
8.169
966391AG1-508 GEN
Solar/Wind Harmer
4.787
971981AH1-535 GEN
Solar/Wind Harmer
12.632
972165AH1-665 GEN
Solar/Wind Harmer
9.771
965401AG1-405 GEN
Solar/Wind Harmer
6.93
339211AE2-254 GEN
Solar/Wind Harmer
1.83
270069AE2-166 C O1
Solar/Wind Harmer
3.07
944031AF1-071 GEN
Solar/Wind Harmer
1.053
274823ROCKFORD ;21
Adder
18.572
20092526R32
Solar/Wind Helper
1.083
203846AF2-130 C
Solar/Wind Helper
0.425
243186AF1-051 GEN
50/50
12.611
24723005RIVRG1
Adder
37.09
24723105RIVRG2
Adder
37.09
24685805CER G1
Adder
16.156
24685905CER G2
Adder
16.156
971225AH1-072 GEN
Solar/Wind Harmer
3.044
971227AH1-073 GEN
Solar/Wind Harmer
3.044
270214AC2-123 GEN
Solar/Wind Harmer
3.214
270583AD2-179 GEN
Solar/Wind Harmer
12.914
971125AH1-004 GEN
Solar/Wind Harmer
4.815
252519AF1-045_GEN
Solar/Wind Harmer
6.963
252516AE2-318_GEN
Solar/Wind Harmer
5.311
270444AC2-157 GEN1
Solar/Wind Harmer
6.293
253317AC1-085 GEN4
Solar/Wind Harmer
9.175
276916AD2-100_GEN
Solar/Wind Harmer
21.483
957381AF2-032 GEN
Solar/Wind Harmer
0.427
253370AE2-315 SEC1
Adder
1.951
25322209TAIT E
Adder
9.264
25322209TAIT E
Adder
9.056
247621Y3-024
Adder
0.228
241801AE1-079 GEN
Solar/Wind Helper
0.238
238120AE2-309 GEN
Solar/Wind Helper
0.4
20303426NA_O38_P22
Solar/Wind Helper
0.919
944971AF1-162 GEN
Solar/Wind Harmer
12.489
24728205BUCHG1
Adder
6.985
971277AH1-098 GEN
Solar/Wind Harmer
5.494
971073AG2-665 GEN
Solar/Wind Harmer
8.094
971073AG2-665 GEN
Solar/Wind Harmer
5.647
972045AH1-571 GEN
Solar/Wind Harmer
2.426
339221AD2-048_GEN
Solar/Wind Harmer
1.861
339231AF1-038_GEN
Solar/Wind Harmer
2.165
966021AG1-471 GEN
Solar/Wind Harmer
6.404
252509AD1-136 GEN
Solar/Wind Harmer
0.303
970653AG2-424 GEN
Solar/Wind Harmer
5.682
970653AG2-424 GEN
Solar/Wind Harmer
2.054
964571AG1-320 GEN
Solar/Wind Harmer
9.614
339255AE2-071 GEN
Solar/Wind Harmer
1.239
25183208HLCRTG
Solar/Wind Harmer
6.95
25194508D.CRK3
Adder
1.604
24728805RICHG1
Adder
3.931
276911AD2-131_GEN
Solar/Wind Harmer
4.342
274765LEE CO EC;6U
Adder
8.939
274763LEE CO EC;4U
Adder
8.834
274695ROCKY RD ;2P
Adder
10.508
20088926STNY CRK
Solar/Wind Helper
0.764
946381AF1-302 GEN
Solar/Wind Helper
0.207
20088626ARWF_N39
Solar/Wind Helper
1.121
970879AG2-548 GEN
Solar/Wind Harmer
8.094
960161AF2-307 GEN
Solar/Wind Harmer
8.235
270186AC1-089 GEN
Solar/Wind Harmer
7.622
962581AG1-107 GEN
Solar/Wind Harmer
6.151
961491AF2-440 GEN
Solar/Wind Harmer
2.556
970239AG2-162 GEN
Solar/Wind Harmer
13.403
970107AG2-081 GEN
Solar/Wind Harmer
3.611
970235AG2-159 GEN
Solar/Wind Harmer
4.78
970235AG2-159 GEN
Solar/Wind Harmer
2.918
339236AF1-050_GEN
Solar/Wind Harmer
2.132
253394AE2-221_GEN
Solar/Wind Harmer
4.786
253398AE2-221_GEN2
Solar/Wind Harmer
4.786
970241AG2-163 GEN
Solar/Wind Harmer
25.567
274762LEE CO EC;3U
Adder
8.918
274696ROCKY RD ;4P
Adder
10.757
274697ROCKY RD ;3P
Adder
2.855
962101AG1-054 GEN
Solar/Wind Helper
0.626
241985AE1-237 GEN
Solar/Wind Helper
0.238
944781AF1-143 GEN
Solar/Wind Helper
2.323
203940AF1-140 C
Solar/Wind Helper
0.368
24318705GVG2
50/50
11.739
270331AC1-082 GEN3
Solar/Wind Harmer
0.892
971315AH1-136 GEN
Solar/Wind Harmer
3.105
971687AH1-348 GEN
Solar/Wind Harmer
1.523
970333AG2-219 GEN
Solar/Wind Harmer
38.461
25196808ZIMRHP
Adder
88.001
25196008MFTGT1
Adder
1.601
274761LEE CO EC;2U
Adder
8.918
237046AF1-021 C
Solar/Wind Helper
0.476
254303AC2-168 GEN
Solar/Wind Helper
0.153
23751201ROTHROCK
Solar/Wind Helper
0.699
20089226LOOKOUT
Solar/Wind Helper
0.545
203853AF1-134 C O1
Solar/Wind Helper
0.443
24289405MTG1
50/50
11.76
24686405CER G5
Adder
16.113
270053AF1-130 C
Solar/Wind Harmer
6.632
970913AG2-568 GEN
Solar/Wind Harmer
13.469
970273AG2-179 GEN
Solar/Wind Harmer
4.651
339250AF1-203 GEN
Solar/Wind Harmer
0.708
962251AG1-071 GEN
Solar/Wind Harmer
6.397
270356AE2-297 GEN
Solar/Wind Harmer
4.782
270222AC2-111 GEN
Solar/Wind Harmer
8.539
274760LEE CO EC;1U
Adder
8.918
972236AH1-702 GEN2
Adder
2.091
20089126CSLMN_L13
Solar/Wind Helper
0.56
238118U2-030_1
Solar/Wind Helper
0.272
959441AF2-235 GEN
Solar/Wind Helper
0.22
944201AF1-088_MTX
Adder
131.041
957141AF2-008_MTX
Adder
65.52
NYPJM->LTFIMP_NY
CLTF
5.029
LGEELTFEXP_LGEE->PJM
CLTF
8.22
WECLTFEXP_WEC->PJM
CLTF
3.65
AG2-052LTFEXP_AG2-052->PJM
LTF
0.22
AH1-155LTFEXP_AH1-155->PJM
LTF
0.329
LAGNLTFEXP_LAGN->PJM
CLTF
21.71
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.108
TVALTFEXP_TVA->PJM
CLTF
11.299
CPLELTFEXP_CPLE->PJM
CLTF
7.285
CBM West 2LTFEXP_CBM-W2->PJM
CBM
144.471
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.529
CBM South 1LTFEXP_CBM-S1->PJM
CBM
42.883
MECLTFEXP_MEC->PJM
CLTF
16.832
SIGELTFEXP_SIGE->PJM
CLTF
0.595

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P7-1_#10856___SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10856___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:102.19 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5644.14
MW Contribution:3.87
Bus #Bus NameTypeMW Contribution
243186AF1-051 GEN
50/50
12.674
24721805FLATG3
50/50
2.672
24721705FLATG2
50/50
48.99
24723205RIVRG3
Adder
37.324
970947AG2-589 GEN
Solar/Wind Harmer
3.947
24686105CER G3
Adder
16.366
24735205WLF2G2
Adder
8.071
945681AF1-233 GEN
Solar/Wind Harmer
23.2
971821AH1-427 GEN
Solar/Wind Harmer
12.202
943111AE2-339 GEN
Solar/Wind Harmer
1.075
339241AF1-083 GEN
Solar/Wind Harmer
1.988
964901AG1-354 GEN
Solar/Wind Harmer
17.761
25194608D.CRK4
Adder
1.886
270336AE1-100 GEN
Solar/Wind Harmer
1.97
270445AC2-157 GEN2
Solar/Wind Harmer
6.363
253432AC1-085 GEN2
Solar/Wind Harmer
0.297
946171AF1-282 GEN
Solar/Wind Harmer
11.077
971367AH1-164 GEN
Solar/Wind Harmer
3.867
943811AF1-049 GEN
Solar/Wind Harmer
4.12
24728605AND G2
Adder
4.084
253370AE2-315 SEC1
Adder
1.976
253371AE2-315 SEC2
Adder
1.869
274828WAUKEGAN ;BP
Adder
10.566
274682WAUKEGAN ;7U
Adder
17.184
274745AC1-111 GEN9
Adder
5.326
241966AE1-183 GEN
Solar/Wind Helper
0.242
238185AF2-356 C
Solar/Wind Helper
2.051
964201AG1-281 GEN
Solar/Wind Helper
0.442
24289405MTG1
50/50
11.814
960001AF2-291 GEN
Solar/Wind Harmer
6.103
971403AH1-188 GEN
Solar/Wind Harmer
24.977
927014AC1-188 GEN
Solar/Wind Harmer
2.475
971329AH1-144 GEN
Solar/Wind Harmer
16.245
970091AG2-072 GEN
Adder
95.631
3429421JKCT 10G
Adder
10.15
970273AG2-179 GEN
Solar/Wind Harmer
2.943
971565AH1-281 GEN
Solar/Wind Harmer
2.396
270263AC1-001 GEN
Solar/Wind Harmer
1.127
963741AG1-226 GEN
Solar/Wind Harmer
46.579
274822ROCKFORD ;11
Adder
18.951
235054AD2-180 GEN
Solar/Wind Helper
1.594
23562501BACKB
Solar/Wind Helper
0.838
235531U2-073 GEN
Solar/Wind Helper
2.519
20094526CT_V3-030
Solar/Wind Helper
0.433
970149AG2-104 GEN
Solar/Wind Harmer
20.97
24686505CER G6
Adder
16.345
24728305BUCHG2
Adder
7.041
3429241JKCT 3G
Adder
14.522
339216AC1-074 GEN
Solar/Wind Harmer
2.039
252507AC2-088 GEN
Solar/Wind Harmer
2.144
962241AG1-070 GEN
Solar/Wind Harmer
5.29
965911AG1-460 GEN
Solar/Wind Harmer
1.441
962761AG1-125 GEN
Solar/Wind Harmer
41.255
274766LEE CO EC;7U
Adder
8.927
972235AH1-702 GEN1
Adder
2.436
25326309TAIT D
Adder
1.054
238117U2-030
Solar/Wind Helper
0.268
20088826HIGHLAND
Solar/Wind Helper
0.824
24722005FLATG5
50/50
2.672
24721905FLATG4
50/50
48.99
960911AF2-382 GEN
Solar/Wind Harmer
11.821
972103AH1-617 GEN
Solar/Wind Harmer
31.134
943031AE2-326 GEN
Solar/Wind Harmer
5.103
971155AH1-034 GEN
Solar/Wind Harmer
11.792
960741AF2-365 GEN
Solar/Wind Harmer
5.892
25194608D.CRK4
Adder
1.886
270030AE2-140 GEN
Solar/Wind Harmer
22.282
253316AC1-085 GEN3
Solar/Wind Harmer
9.279
253433AC1-085 GEN1
Solar/Wind Harmer
5.89
946181AF1-283 GEN
Solar/Wind Harmer
14.4
24728505AND G1
Adder
4.084
253370AE2-315 SEC1
Adder
1.976
253371AE2-315 SEC2
Adder
1.869
274767LEE CO EC;8U
Adder
8.927
274682WAUKEGAN ;7U
Adder
17.184
235058AG1-386 C
Solar/Wind Helper
0.446
964991AG1-363 GEN
Solar/Wind Helper
3.415
203818AF1-086 GEN
Solar/Wind Helper
1.548
24686205CER G4
Adder
16.28
957541AF2-048 GEN
Solar/Wind Harmer
2.468
971461AH1-227 GEN
Solar/Wind Harmer
7.872
270346AE1-212 GEN
Solar/Wind Harmer
13.369
971331AH1-145 GEN
Solar/Wind Harmer
12.593
247619Y1-049
Adder
0.569
958121AF2-106 GEN
Solar/Wind Harmer
5.909
970519AG2-331 GEN
Solar/Wind Harmer
21.356
970699AG2-449 GEN
Solar/Wind Harmer
14.128
270291AC1-194 GEN
Solar/Wind Harmer
12.959
3429391JKCT 9G
Adder
10.15
958171AF2-111 GEN
Solar/Wind Harmer
29.825
25196608WSDLE5
Adder
9.788
253406AD2-031_GEN
Solar/Wind Harmer
1.394
970193AG2-126 GEN
Solar/Wind Harmer
15.993
24728705AND G3
Adder
8.541
253415AE1-040 GEN
Solar/Wind Harmer
1.181
254305AE2-115 C
Solar/Wind Helper
0.208
202652Y1-033 WT C
Solar/Wind Helper
0.526
23750701CROSSCHOOL
Solar/Wind Helper
1.114
20089026BF_G21_K23
Solar/Wind Helper
0.437
238127S14_GEN_2
Solar/Wind Helper
0.631
942891AE2-308 GEN
Solar/Wind Harmer
12.292
972043AH1-570 GEN
Solar/Wind Harmer
3.063
971485AH1-239 GEN
Solar/Wind Harmer
9.571
971081AG2-670 GEN
Solar/Wind Harmer
8.948
964781AG1-341 GEN
Solar/Wind Harmer
12.498
25194408D.CRK1
Adder
8.675
945391AF1-204 GEN
Solar/Wind Harmer
14.859
24728905RICHG2
Adder
3.978
972267AH1-718 GEN
Adder
4.056
274764LEE CO EC;5U
Adder
9.055
274683WAUKEGAN ;8U
Adder
20.157
274683WAUKEGAN ;8U
Adder
16.992
24318705GVG2
50/50
11.798
971191AH1-055 GEN
Solar/Wind Harmer
39.337
970093AG2-073 GEN
Solar/Wind Harmer
12.329
970243AG2-164 GEN
Solar/Wind Harmer
31.788
972167AH1-666 GEN
Solar/Wind Harmer
9.834
972273AH1-721 GEN
Adder
102.108
966571AG1-526 GEN
Solar/Wind Harmer
27.128
25196008MFTGT1
Adder
1.567
252510AF1-249 C
Solar/Wind Harmer
0.482
942481AE2-261 GEN
Solar/Wind Harmer
30.873
274729ELWOOD EC;1P
Adder
7.078
237048AF1-022 C
Solar/Wind Helper
0.185
237043AE2-125 C
Solar/Wind Helper
0.171
972203AH1-686 GEN
Adder
4.469
970281AG2-184 GEN
Solar/Wind Harmer
32.691
962211AG1-066 GEN
Solar/Wind Harmer
3.557
252524AE2-267 GEN
Solar/Wind Harmer
1.801
962771AG1-126 GEN
Solar/Wind Harmer
41.255
25306009OHH W.
Adder
2.849
253372AE2-315 SEC3
Adder
1.869
253372AE2-315 SEC3
Adder
1.869
274744AC1-111 GEN8
Adder
5.326
241997AF1-093 GEN
Solar/Wind Helper
0.242
20091526CHSTN_FL
Solar/Wind Helper
0.532
24721605FLATG1
50/50
2.672
270329AC1-082 GEN1
Solar/Wind Harmer
0.895
24477305BRIDGE
Adder
0.639
957241AF2-018 GEN
Solar/Wind Harmer
7.983
270400AC1-102 GEN
Solar/Wind Harmer
7.536
941621AE2-160 GEN
Adder
5.607
24734805WLF1G4
Adder
8.24
24735105WLF2G1
Adder
8.071
972163AH1-664 GEN
Solar/Wind Harmer
12.338
3429211JKCT 2G
Adder
14.334
339243AC2-075 GEN1
Solar/Wind Harmer
0.552
970455AG2-298 GEN
Solar/Wind Harmer
7.176
25196508WSDLE4
Adder
9.688
270340AC2-060 GEN
Solar/Wind Harmer
3.271
944221AF1-090 GEN
Solar/Wind Harmer
11.424
274746AC1-111 G10
Adder
5.326
23750501ELLIOTTS
Solar/Wind Helper
0.635
254304AE2-114 C
Solar/Wind Helper
0.208
241982AE2-343 S C
Solar/Wind Helper
0.211
203961AE2-224 GEN
Solar/Wind Helper
2.198
270132AB1-180 C
Adder
0.186
971313AH1-133 GEN
Solar/Wind Harmer
15.406
971061AG2-657 GEN
Solar/Wind Harmer
13.864
970879AG2-548 GEN
Solar/Wind Harmer
5.701
270367AC2-061_GEN
Solar/Wind Harmer
3.995
965411AG1-406 GEN
Solar/Wind Harmer
3.142
25196108MFTGT2
Adder
1.784
25196108MFTGT2
Adder
1.656
25196408WSDLE3
Adder
10.076
25196308WSDLE2
Adder
9.988
25196208WSDLE1
Adder
9.963
25196708WSDLE6
Adder
9.938
238126S14_GEN_1
Solar/Wind Helper
0.631
274693ROCKY RD ;1P
Adder
10.542
23652301WDPWR_K20
Solar/Wind Helper
0.138
241967AE2-285_GEN
Solar/Wind Helper
0.605
23585401KL_K28_T16
Solar/Wind Helper
1.207
203955AF1-039 C O1
Solar/Wind Helper
0.347
946071AF1-272 GEN
Solar/Wind Helper
2.502
20083426SW_E13_K22
Solar/Wind Helper
0.052
20084626FORWARD
Solar/Wind Helper
0.327
944971AF1-162 GEN
Solar/Wind Harmer
12.576
24728205BUCHG1
Adder
7.041
971277AH1-098 GEN
Solar/Wind Harmer
5.544
971073AG2-665 GEN
Solar/Wind Harmer
8.171
971073AG2-665 GEN
Solar/Wind Harmer
5.701
972045AH1-571 GEN
Solar/Wind Harmer
2.45
339221AD2-048_GEN
Solar/Wind Harmer
1.88
339231AF1-038_GEN
Solar/Wind Harmer
2.187
966021AG1-471 GEN
Solar/Wind Harmer
6.471
252509AD1-136 GEN
Solar/Wind Harmer
0.306
970653AG2-424 GEN
Solar/Wind Harmer
5.742
970879AG2-548 GEN
Solar/Wind Harmer
8.171
960161AF2-307 GEN
Solar/Wind Harmer
8.314
270186AC1-089 GEN
Solar/Wind Harmer
7.697
962581AG1-107 GEN
Solar/Wind Harmer
6.214
961491AF2-440 GEN
Solar/Wind Harmer
2.582
970239AG2-162 GEN
Solar/Wind Harmer
13.539
970107AG2-081 GEN
Solar/Wind Harmer
3.648
970235AG2-159 GEN
Solar/Wind Harmer
4.83
970235AG2-159 GEN
Solar/Wind Harmer
2.948
339236AF1-050_GEN
Solar/Wind Harmer
2.155
253394AE2-221_GEN
Solar/Wind Harmer
4.843
253398AE2-221_GEN2
Solar/Wind Harmer
4.843
970241AG2-163 GEN
Solar/Wind Harmer
25.877
274762LEE CO EC;3U
Adder
9.033
274696ROCKY RD ;4P
Adder
10.898
274697ROCKY RD ;3P
Adder
2.892
962101AG1-054 GEN
Solar/Wind Helper
0.618
241985AE1-237 GEN
Solar/Wind Helper
0.235
944781AF1-143 GEN
Solar/Wind Helper
2.291
203940AF1-140 C
Solar/Wind Helper
0.363
24318705GVG2
50/50
11.798
270331AC1-082 GEN3
Solar/Wind Harmer
0.897
243186AF1-051 GEN
50/50
12.674
24723005RIVRG1
Adder
37.324
24723105RIVRG2
Adder
37.324
24685805CER G1
Adder
16.259
24685905CER G2
Adder
16.259
971225AH1-072 GEN
Solar/Wind Harmer
3.069
971227AH1-073 GEN
Solar/Wind Harmer
3.069
270214AC2-123 GEN
Solar/Wind Harmer
3.243
270583AD2-179 GEN
Solar/Wind Harmer
13.038
971125AH1-004 GEN
Solar/Wind Harmer
4.864
252519AF1-045_GEN
Solar/Wind Harmer
7.038
252516AE2-318_GEN
Solar/Wind Harmer
5.369
270444AC2-157 GEN1
Solar/Wind Harmer
6.363
253317AC1-085 GEN4
Solar/Wind Harmer
9.279
276916AD2-100_GEN
Solar/Wind Harmer
21.743
957381AF2-032 GEN
Solar/Wind Harmer
0.432
253370AE2-315 SEC1
Adder
1.976
25322209TAIT E
Adder
9.385
25322209TAIT E
Adder
9.175
247621Y3-024
Adder
0.231
241801AE1-079 GEN
Solar/Wind Helper
0.235
238120AE2-309 GEN
Solar/Wind Helper
0.394
970653AG2-424 GEN
Solar/Wind Harmer
2.076
964571AG1-320 GEN
Solar/Wind Harmer
9.715
339255AE2-071 GEN
Solar/Wind Harmer
1.252
25183208HLCRTG
Solar/Wind Harmer
7.025
25194508D.CRK3
Adder
1.622
24728805RICHG1
Adder
3.978
276911AD2-131_GEN
Solar/Wind Harmer
4.394
274765LEE CO EC;6U
Adder
9.055
274763LEE CO EC;4U
Adder
8.948
274695ROCKY RD ;2P
Adder
10.646
20088926STNY CRK
Solar/Wind Helper
0.754
24289405MTG1
50/50
11.814
24686405CER G5
Adder
16.216
270053AF1-130 C
Solar/Wind Harmer
6.678
970913AG2-568 GEN
Solar/Wind Harmer
13.568
970273AG2-179 GEN
Solar/Wind Harmer
4.7
339250AF1-203 GEN
Solar/Wind Harmer
0.715
962251AG1-071 GEN
Solar/Wind Harmer
6.465
270356AE2-297 GEN
Solar/Wind Harmer
4.839
270222AC2-111 GEN
Solar/Wind Harmer
8.641
274760LEE CO EC;1U
Adder
9.033
972236AH1-702 GEN2
Adder
2.118
20089126CSLMN_L13
Solar/Wind Helper
0.552
238118U2-030_1
Solar/Wind Helper
0.268
270330AC1-082 GEN2
Solar/Wind Harmer
1.52
270399AC1-101 GEN
Solar/Wind Harmer
7.536
972143AH1-644 GEN
Solar/Wind Harmer
15.567
971985AH1-537 GEN
Solar/Wind Harmer
27.131
24734705WLF1G3
Adder
8.24
24734905WLF1G5
Adder
8.24
966391AG1-508 GEN
Solar/Wind Harmer
4.83
971981AH1-535 GEN
Solar/Wind Harmer
12.756
972165AH1-665 GEN
Solar/Wind Harmer
9.871
965401AG1-405 GEN
Solar/Wind Harmer
7.001
339211AE2-254 GEN
Solar/Wind Harmer
1.849
270069AE2-166 C O1
Solar/Wind Harmer
3.104
944031AF1-071 GEN
Solar/Wind Harmer
1.065
274823ROCKFORD ;21
Adder
18.813
20092526R32
Solar/Wind Helper
1.068
203846AF2-130 C
Solar/Wind Helper
0.419
971315AH1-136 GEN
Solar/Wind Harmer
3.129
971687AH1-348 GEN
Solar/Wind Harmer
1.535
970333AG2-219 GEN
Solar/Wind Harmer
38.852
25196808ZIMRHP
Adder
88.943
25196008MFTGT1
Adder
1.618
274761LEE CO EC;2U
Adder
9.033
237046AF1-021 C
Solar/Wind Helper
0.471
254303AC2-168 GEN
Solar/Wind Helper
0.151
23751201ROTHROCK
Solar/Wind Helper
0.69
20089226LOOKOUT
Solar/Wind Helper
0.537
944201AF1-088_MTX
Adder
132.484
957141AF2-008_MTX
Adder
66.242
NYPJM->LTFIMP_NY
CLTF
4.949
LGEELTFEXP_LGEE->PJM
CLTF
8.306
WECLTFEXP_WEC->PJM
CLTF
3.698
AG2-052LTFEXP_AG2-052->PJM
LTF
0.222
AH1-155LTFEXP_AH1-155->PJM
LTF
0.334
LAGNLTFEXP_LAGN->PJM
CLTF
21.962
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.485
TVALTFEXP_TVA->PJM
CLTF
11.425
CPLELTFEXP_CPLE->PJM
CLTF
7.421
CBM West 2LTFEXP_CBM-W2->PJM
CBM
146.148
CBM West 1LTFEXP_CBM-W1->PJM
CBM
123.346
CBM South 1LTFEXP_CBM-S1->PJM
CBM
43.356
MECLTFEXP_MEC->PJM
CLTF
17.041
SIGELTFEXP_SIGE->PJM
CLTF
0.602

Details for 6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line l/o DVP_P4-2: 509T570_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 509T570_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.83 %
Rating:997.0 MVA
Rating Type:C
MVA to Mitigate:1144.9
MW Contribution:1.91
Bus #Bus NameTypeMW Contribution
961601AG1-000A GEN
Solar/Wind Harmer
2.784
3145543BTLEBRO
Solar/Wind Harmer
-0.007
24728405LEESVG
50/50
0.137
316283AC2-100 C
Solar/Wind Harmer
2.82
941821AE2-187 GEN
Solar/Wind Harmer
5.461
270197AD1-017 GEN1
Solar/Wind Harmer
1.353
943811AF1-049 GEN
Solar/Wind Harmer
2.868
270336AE1-100 GEN
Solar/Wind Harmer
1.167
971367AH1-164 GEN
Solar/Wind Harmer
1.912
316478AD1-087 GEN
Solar/Wind Helper
3.08
316486AD2-202 GEN
Solar/Wind Helper
0.902
3145336SMITFLD
Solar/Wind Helper
0.06
3146456SLIGO L269
Solar/Wind Helper
0.143
3142946ENON
Solar/Wind Helper
0.045
316473AC1-191 GEN
Solar/Wind Helper
0.746
3147173SINAI
Solar/Wind Harmer
-0.042
3147243WELCO
Solar/Wind Harmer
-0.026
970165AG2-112 GEN
Solar/Wind Harmer
2.848
970163AG2-111 GEN
Solar/Wind Harmer
2.717
270455AD2-022 GEN
Solar/Wind Harmer
3.531
316349AD2-085 GEN
Solar/Wind Helper
0.637
316059AD1-063 C
Solar/Wind Helper
0.137
3152661PLYWOOD A
50/50
0.685
316217AC1-145 GEN
Solar/Wind Harmer
2.364
316197AC1-042 GEN
Solar/Wind Harmer
1.792
942671AE2-283 GEN
Solar/Wind Harmer
4.824
316236AE1-162_GEN
Solar/Wind Helper
0.202
3145506HICKORY
Solar/Wind Helper
0.599
3145506HICKORY
Solar/Wind Helper
0.359
3145506HICKORY
Solar/Wind Helper
0.09
316339AD2-160 GEN
Solar/Wind Helper
0.555
316033AB2-134 GEN
Solar/Wind Helper
0.501
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146776BUCKING
Solar/Wind Helper
0.07
315773AC2-141 GEN
Solar/Wind Helper
3.622
3144536CHRHLND
Solar/Wind Helper
0.023
316313AB2-026
Solar/Wind Helper
0.213
316156AD2-030 GEN
Solar/Wind Helper
0.206
316484AD2-074 GEN
Solar/Wind Helper
0.254
316320Y1-086
Solar/Wind Helper
0.059
316435W1029_GEN3
Solar/Wind Helper
0.485
3146516WINFALL
Solar/Wind Helper
0.117
970581AG2-369 GEN
Solar/Wind Harmer
8.549
270069AE2-166 C O1
Solar/Wind Harmer
1.803
971981AH1-535 GEN
Solar/Wind Harmer
4.605
3143316POE
Solar/Wind Helper
0.634
316369SG1_INVT
Solar/Wind Helper
0.701
319010AE1-072 C
Solar/Wind Helper
1.62
3141873WAN 176
Solar/Wind Helper
0.027
315662AE1-191 GEN
Solar/Wind Helper
0.732
3143873LANEXA
Solar/Wind Helper
0.081
3138133OCRAN
Solar/Wind Helper
0.04
3146486SUNBURY
Solar/Wind Helper
0.128
3146486SUNBURY
Solar/Wind Helper
0.128
316321Z2-027
Solar/Wind Helper
0.193
3145176PASQUOTANK
Solar/Wind Helper
0.078
970917AG2-570 GEN
Solar/Wind Harmer
39.759
270018AE2-047 C O1
Solar/Wind Harmer
1.019
3146926FARMVIL
Solar/Wind Helper
0.145
3144873MCLAUGH
Solar/Wind Helper
0.004
316382AG1-145 C
Solar/Wind Helper
0.193
316405AF2-144 C
Solar/Wind Helper
0.16
316280AD1-041 GEN
Solar/Wind Helper
0.457
316404AE1-155 C
Solar/Wind Helper
1.1
3141906WESTMOR
Solar/Wind Helper
0.048
3141783LANCAST
Solar/Wind Helper
0.08
3141783LANCAST
Solar/Wind Helper
0.054
313526AB2-022
Solar/Wind Helper
0.2
316222AC1-221 GEN
Solar/Wind Harmer
3.1
3146843MT LREL
Solar/Wind Harmer
-0.026
3146843MT LREL
Solar/Wind Harmer
-0.026
316017AA1-139 ULT1
Solar/Wind Helper
0.661
3142946ENON
Solar/Wind Helper
0.014
316487AF1-042 GEN
Solar/Wind Helper
0.133
3146386ELIZ CT
Solar/Wind Helper
0.131
316431W1029_GEN1
Solar/Wind Helper
0.485
316433W1029_GEN2
Solar/Wind Helper
0.485
970865AG2-541 GEN
Solar/Wind Harmer
14.146
316123AC1-075 GEN
Solar/Wind Harmer
3.235
957831AF2-077 GEN
Solar/Wind Helper
0.192
3141913WHIT STONE
Solar/Wind Helper
0.135
316315AB2-025 C
Solar/Wind Helper
0.199
316312AB1-027
Solar/Wind Helper
0.241
962561AG1-105 GEN
Solar/Wind Harmer
12.783
270013AE1-250 PV
Solar/Wind Harmer
2.226
316263AC1-034 GEN
Solar/Wind Harmer
3.259
316316AC1-027 C
Solar/Wind Helper
0.241
316185AD1-033 GEN
Solar/Wind Helper
0.715
315697AD1-025 GEN
Solar/Wind Helper
1.666
3143526WINTERP
Solar/Wind Helper
0.718
316075AC2-137 C
Solar/Wind Helper
0.201
3144356SAPONY
Solar/Wind Helper
0.234
316077AC2-138 C
Solar/Wind Helper
0.12
316468AD1-105 GEN
Solar/Wind Helper
0.568
971629AH1-314 GEN
50/50
13.489
24728405LEESVG
50/50
0.136
316003AC1-222 GEN
Solar/Wind Harmer
3.856
3147123OTTER R
Solar/Wind Harmer
-0.01
270574AD1-017 GEN2
Solar/Wind Harmer
4.502
270030AE2-140 GEN
Solar/Wind Harmer
14.747
316359AB2-059 GEN
Solar/Wind Harmer
0.937
3142053HEARTS
Solar/Wind Harmer
0.082
316294AC1-161 GEN
Solar/Wind Helper
3.077
316375AC2-012 GEN
Solar/Wind Helper
0.404
3145336SMITFLD
Solar/Wind Helper
0.602
3146456SLIGO L269
Solar/Wind Helper
0.143
316336AC2-165 C
Solar/Wind Helper
0.752
3142433PROV 92
Solar/Wind Helper
0.545
3141766HARMONY
Solar/Wind Helper
0.027
3142416OLDCHRC
Solar/Wind Helper
0.33
3142416OLDCHRC
Solar/Wind Helper
0.126
316248AF1-058 C
Solar/Wind Harmer
1.27
960061AF2-297 GEN
Solar/Wind Harmer
21.067
971683AH1-343 GEN
Solar/Wind Harmer
16.042
3147312GRETNA
Solar/Wind Harmer
-0.003
942461AE2-259 GEN
Solar/Wind Helper
1.133
315839AE2-212 C
Solar/Wind Helper
0.205
316258AE1-075 C
Solar/Wind Helper
0.192
315687AD1-152 GEN
Solar/Wind Harmer
8.943
970401AG2-262 GEN
Solar/Wind Harmer
1.705
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
270016AE1-250 BESS
Solar/Wind Harmer
2.226
316322AB2-045
Solar/Wind Helper
0.217
316072AD1-144
Solar/Wind Helper
0.163
3143526WINTERP
Solar/Wind Helper
0.718
964211AG1-282 GEN
Solar/Wind Helper
0.173
316118AC1-105 GEN
Solar/Wind Harmer
2.355
270457AD2-023 GEN
Solar/Wind Harmer
1.791
970085AG2-068 GEN
Solar/Wind Harmer
9.94
316132AB2-190 GEN1
Solar/Wind Helper
0.826
316305AF2-043 C
Solar/Wind Helper
0.189
316233AE1-074 FULL
Solar/Wind Helper
0.211
957601AF2-054 GEN
Solar/Wind Helper
0.183
315666AE1-190 GEN
Solar/Wind Helper
0.183
3141813NORNECK
Solar/Wind Helper
0.128
316223AC1-118
Solar/Wind Helper
0.184
942751AE2-291 GEN
Solar/Wind Harmer
17.158
964791AG1-342 GEN
Solar/Wind Harmer
5.579
961601AG1-000A GEN
Solar/Wind Harmer
2.749
3146776BUCKING
Solar/Wind Helper
0.779
3146776BUCKING
Solar/Wind Helper
0.063
316036AC1-147 C
Solar/Wind Helper
0.235
3142956BIRDNECK
Solar/Wind Helper
0.103
316240AF1-291 C
Solar/Wind Helper
0.198
316018AA1-139 ULT2
Solar/Wind Helper
0.622
966871AG1-558 GEN
Solar/Wind Helper
0.165
3146516WINFALL
Solar/Wind Helper
0.117
3146516WINFALL
Solar/Wind Helper
0.117
3146516WINFALL
Solar/Wind Helper
0.117
3137176SLIGO L2192
Solar/Wind Helper
0.569
3130086AYDLETT
Solar/Wind Helper
0.564
970087AG2-069 GEN
Solar/Wind Harmer
14.91
970223AG2-152 GEN
Solar/Wind Harmer
13.358
316049AB1-081 GEN
Solar/Wind Harmer
0.75
3146926FARMVIL
Solar/Wind Helper
0.145
316381AD1-082 GEN
Solar/Wind Helper
0.757
316388AE2-253 GEN
Solar/Wind Helper
0.555
316458AB2-190 GEN2
Solar/Wind Helper
0.826
316159AE1-175 C
Solar/Wind Helper
0.218
3143226MDLTHAN
Solar/Wind Helper
0.141
316246AF1-032 C
Solar/Wind Helper
0.161
3142543TWELFTH
Solar/Wind Helper
0.013
3138133OCRAN
Solar/Wind Helper
0.081
3151561HALLBR1
50/50
0.374
970919AG2-571 GEN
Solar/Wind Harmer
5.033
941801AE2-185 GEN
Solar/Wind Harmer
5.461
270173AC1-122 GEN
Solar/Wind Harmer
1.038
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.078
3141726DUNNSVL
Solar/Wind Helper
0.513
316337AD2-073 GEN
Solar/Wind Helper
0.188
3146516WINFALL
Solar/Wind Helper
0.38
3146516WINFALL
Solar/Wind Helper
0.117
NYPJM->LTFIMP_NY
CLTF
0.755
LGEELTFEXP_LGEE->PJM
CLTF
1.98
WECLTFEXP_WEC->PJM
CLTF
1.048
LAGNLTFEXP_LAGN->PJM
CLTF
9.202
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.294
TVALTFEXP_TVA->PJM
CLTF
4.607
CPLELTFEXP_CPLE->PJM
CLTF
11.151
CBM West 2LTFEXP_CBM-W2->PJM
CBM
51.541
CBM West 1LTFEXP_CBM-W1->PJM
CBM
38.067
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.134
MECLTFEXP_MEC->PJM
CLTF
5.224
SIGELTFEXP_SIGE->PJM
CLTF
0.159

Details for 6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 570_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.64 %
Rating:814.98 MVA
Rating Type:B
MVA to Mitigate:885.41
MW Contribution:1.35
Bus #Bus NameTypeMW Contribution
316118AC1-105 GEN
Solar/Wind Harmer
0.789
970085AG2-068 GEN
Solar/Wind Harmer
7.603
316132AB2-190 GEN1
Solar/Wind Helper
0.815
316305AF2-043 C
Solar/Wind Helper
0.186
316233AE1-074 FULL
Solar/Wind Helper
0.208
957601AF2-054 GEN
Solar/Wind Helper
0.18
315666AE1-190 GEN
Solar/Wind Helper
0.18
3141813NORNECK
Solar/Wind Helper
0.126
316223AC1-118
Solar/Wind Helper
0.181
970417AG2-272 GEN
50/50
1.899
970087AG2-069 GEN
Solar/Wind Harmer
11.404
970223AG2-152 GEN
Solar/Wind Harmer
9.437
316049AB1-081 GEN
Solar/Wind Harmer
0.36
3146926FARMVIL
Solar/Wind Helper
0.144
316381AD1-082 GEN
Solar/Wind Helper
0.747
316388AE2-253 GEN
Solar/Wind Helper
0.548
316458AB2-190 GEN2
Solar/Wind Helper
0.815
970581AG2-369 GEN
Solar/Wind Harmer
6.538
270069AE2-166 C O1
Solar/Wind Harmer
0.003
971981AH1-535 GEN
Solar/Wind Harmer
2.177
3143316POE
Solar/Wind Helper
0.626
316369SG1_INVT
Solar/Wind Helper
0.691
319010AE1-072 C
Solar/Wind Helper
1.597
3141873WAN 176
Solar/Wind Helper
0.027
315662AE1-191 GEN
Solar/Wind Helper
0.721
3143873LANEXA
Solar/Wind Helper
0.08
3138133OCRAN
Solar/Wind Helper
0.04
3146486SUNBURY
Solar/Wind Helper
0.126
3146486SUNBURY
Solar/Wind Helper
0.126
316321Z2-027
Solar/Wind Helper
0.19
3145176PASQUOTANK
Solar/Wind Helper
0.077
315687AD1-152 GEN
Solar/Wind Harmer
0.022
970401AG2-262 GEN
Solar/Wind Harmer
1.37
3147312GRETNA
Solar/Wind Harmer
0.104
3146802CHATHAM
Solar/Wind Harmer
0.098
270016AE1-250 BESS
Solar/Wind Harmer
0.004
316322AB2-045
Solar/Wind Helper
0.215
316072AD1-144
Solar/Wind Helper
0.16
3143526WINTERP
Solar/Wind Helper
0.708
964211AG1-282 GEN
Solar/Wind Helper
0.17
24684505SMG3
50/50
0.529
942751AE2-291 GEN
Solar/Wind Harmer
13.086
964791AG1-342 GEN
Solar/Wind Harmer
4.482
961601AG1-000A GEN
Solar/Wind Harmer
1.124
3146776BUCKING
Solar/Wind Helper
0.771
3146776BUCKING
Solar/Wind Helper
0.062
316036AC1-147 C
Solar/Wind Helper
0.232
3142956BIRDNECK
Solar/Wind Helper
0.102
316240AF1-291 C
Solar/Wind Helper
0.195
316018AA1-139 ULT2
Solar/Wind Helper
0.614
966871AG1-558 GEN
Solar/Wind Helper
0.162
3146516WINFALL
Solar/Wind Helper
0.115
3146516WINFALL
Solar/Wind Helper
0.115
3146516WINFALL
Solar/Wind Helper
0.115
3152661PLYWOOD A
50/50
0.687
24684405SMG2
50/50
0.856
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
3.251
316236AE1-162_GEN
Solar/Wind Helper
0.2
3145506HICKORY
Solar/Wind Helper
0.591
3145506HICKORY
Solar/Wind Helper
0.355
3145506HICKORY
Solar/Wind Helper
0.089
316339AD2-160 GEN
Solar/Wind Helper
0.548
316033AB2-134 GEN
Solar/Wind Helper
0.494
3137176SLIGO L2192
Solar/Wind Helper
0.561
3130086AYDLETT
Solar/Wind Helper
0.556
971629AH1-314 GEN
50/50
13.578
24728405LEESVG
50/50
0.138
970481AG2-311 GEN
50/50
4.594
316003AC1-222 GEN
Solar/Wind Harmer
0.009
3147123OTTER R
Solar/Wind Harmer
0.091
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
270030AE2-140 GEN
Solar/Wind Harmer
10.396
316359AB2-059 GEN
Solar/Wind Harmer
0.226
3142053HEARTS
Solar/Wind Harmer
0.111
316294AC1-161 GEN
Solar/Wind Helper
3.041
24728405LEESVG
50/50
0.138
316283AC2-100 C
Solar/Wind Harmer
0.523
941821AE2-187 GEN
Solar/Wind Harmer
4.18
270197AD1-017 GEN1
Solar/Wind Harmer
0.766
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
270336AE1-100 GEN
Solar/Wind Harmer
0.003
971367AH1-164 GEN
Solar/Wind Harmer
1.353
971623AH1-311 GEN
Solar/Wind Harmer
0.126
316478AD1-087 GEN
Solar/Wind Helper
3.07
316486AD2-202 GEN
Solar/Wind Helper
0.899
3145336SMITFLD
Solar/Wind Helper
0.059
3146456SLIGO L269
Solar/Wind Helper
0.141
3142946ENON
Solar/Wind Helper
0.045
316473AC1-191 GEN
Solar/Wind Helper
0.734
316248AF1-058 C
Solar/Wind Harmer
0.003
960061AF2-297 GEN
Solar/Wind Harmer
16.042
971683AH1-343 GEN
Solar/Wind Harmer
12.22
3147312GRETNA
Solar/Wind Harmer
0.026
942461AE2-259 GEN
Solar/Wind Helper
1.12
315839AE2-212 C
Solar/Wind Helper
0.202
316258AE1-075 C
Solar/Wind Helper
0.189
316375AC2-012 GEN
Solar/Wind Helper
0.399
3145336SMITFLD
Solar/Wind Helper
0.594
3146456SLIGO L269
Solar/Wind Helper
0.141
316336AC2-165 C
Solar/Wind Helper
0.741
3142433PROV 92
Solar/Wind Helper
0.538
3141766HARMONY
Solar/Wind Helper
0.027
3142416OLDCHRC
Solar/Wind Helper
0.325
3142416OLDCHRC
Solar/Wind Helper
0.124
961601AG1-000A GEN
Solar/Wind Harmer
4.498
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
3146776BUCKING
Solar/Wind Helper
0.069
315773AC2-141 GEN
Solar/Wind Helper
3.58
3144536CHRHLND
Solar/Wind Helper
0.023
316313AB2-026
Solar/Wind Helper
0.21
316156AD2-030 GEN
Solar/Wind Helper
0.203
316484AD2-074 GEN
Solar/Wind Helper
0.25
316320Y1-086
Solar/Wind Helper
0.058
316435W1029_GEN3
Solar/Wind Helper
0.477
3146516WINFALL
Solar/Wind Helper
0.115
3151561HALLBR1
50/50
0.376
24684705SMG5
50/50
0.33
3147173SINAI
Solar/Wind Harmer
0.376
3147243WELCO
Solar/Wind Harmer
0.235
970165AG2-112 GEN
Solar/Wind Harmer
2.171
970163AG2-111 GEN
Solar/Wind Harmer
2.071
316349AD2-085 GEN
Solar/Wind Helper
0.628
316059AD1-063 C
Solar/Wind Helper
0.135
3141783LANCAST
Solar/Wind Helper
0.079
3141783LANCAST
Solar/Wind Helper
0.053
313526AB2-022
Solar/Wind Helper
0.197
24684605SMG4
50/50
0.862
24288905REUSENS
50/50
0.013
970917AG2-570 GEN
Solar/Wind Harmer
12.67
270018AE2-047 C O1
Solar/Wind Harmer
0.002
3146926FARMVIL
Solar/Wind Helper
0.144
3144873MCLAUGH
Solar/Wind Helper
0.004
316382AG1-145 C
Solar/Wind Helper
0.191
316405AF2-144 C
Solar/Wind Helper
0.157
316280AD1-041 GEN
Solar/Wind Helper
0.451
316404AE1-155 C
Solar/Wind Helper
1.083
3141906WESTMOR
Solar/Wind Helper
0.047
316159AE1-175 C
Solar/Wind Helper
0.215
3143226MDLTHAN
Solar/Wind Helper
0.139
316246AF1-032 C
Solar/Wind Helper
0.159
3142543TWELFTH
Solar/Wind Helper
0.013
3138133OCRAN
Solar/Wind Helper
0.08
316222AC1-221 GEN
Solar/Wind Harmer
1.136
3146843MT LREL
Solar/Wind Harmer
0.235
3146843MT LREL
Solar/Wind Harmer
0.235
316017AA1-139 ULT1
Solar/Wind Helper
0.652
3142946ENON
Solar/Wind Helper
0.013
316487AF1-042 GEN
Solar/Wind Helper
0.131
3146386ELIZ CT
Solar/Wind Helper
0.129
316431W1029_GEN1
Solar/Wind Helper
0.477
316433W1029_GEN2
Solar/Wind Helper
0.477
970865AG2-541 GEN
Solar/Wind Harmer
10.778
316123AC1-075 GEN
Solar/Wind Harmer
0.366
957831AF2-077 GEN
Solar/Wind Helper
0.189
3141913WHIT STONE
Solar/Wind Helper
0.133
316315AB2-025 C
Solar/Wind Helper
0.196
316312AB1-027
Solar/Wind Helper
0.238
970919AG2-571 GEN
Solar/Wind Harmer
5.068
941801AE2-185 GEN
Solar/Wind Harmer
4.18
270173AC1-122 GEN
Solar/Wind Harmer
0.217
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.05
3146776BUCKING
Solar/Wind Helper
0.077
3141726DUNNSVL
Solar/Wind Helper
0.505
316337AD2-073 GEN
Solar/Wind Helper
0.185
3146516WINFALL
Solar/Wind Helper
0.373
3146516WINFALL
Solar/Wind Helper
0.115
24684305SMG1
50/50
0.31
962561AG1-105 GEN
Solar/Wind Harmer
9.757
270013AE1-250 PV
Solar/Wind Harmer
0.004
316263AC1-034 GEN
Solar/Wind Harmer
2.389
316316AC1-027 C
Solar/Wind Helper
0.238
316185AD1-033 GEN
Solar/Wind Helper
0.706
315697AD1-025 GEN
Solar/Wind Helper
1.643
3143526WINTERP
Solar/Wind Helper
0.708
316075AC2-137 C
Solar/Wind Helper
0.198
3144356SAPONY
Solar/Wind Helper
0.23
316077AC2-138 C
Solar/Wind Helper
0.118
316468AD1-105 GEN
Solar/Wind Helper
0.559
NYPJM->LTFIMP_NY
CLTF
0.706
LGEELTFEXP_LGEE->PJM
CLTF
2.033
WECLTFEXP_WEC->PJM
CLTF
1.077
AG2-052LTFEXP_AG2-052->PJM
LTF
0.061
AH1-155LTFEXP_AH1-155->PJM
LTF
0.091
LAGNLTFEXP_LAGN->PJM
CLTF
9.357
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.525
TVALTFEXP_TVA->PJM
CLTF
4.684
CPLELTFEXP_CPLE->PJM
CLTF
11.235
CBM West 2LTFEXP_CBM-W2->PJM
CBM
52.568
CBM West 1LTFEXP_CBM-W1->PJM
CBM
39.18
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.424
MECLTFEXP_MEC->PJM
CLTF
5.352
SIGELTFEXP_SIGE->PJM
CLTF
0.163

Details for 6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 570_SRT-A-2


Base Case Flowgate

Area:DVP
Facility Description:
6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.47 %
Rating:814.98 MVA
Rating Type:B
MVA to Mitigate:867.67
MW Contribution:1.35
Bus #Bus NameTypeMW Contribution
315687AD1-152 GEN
Solar/Wind Harmer
0.022
970401AG2-262 GEN
Solar/Wind Harmer
1.37
3147312GRETNA
Solar/Wind Harmer
0.104
24684505SMG3
50/50
0.529
942751AE2-291 GEN
Solar/Wind Harmer
13.086
964791AG1-342 GEN
Solar/Wind Harmer
4.482
3146802CHATHAM
Solar/Wind Harmer
0.098
270016AE1-250 BESS
Solar/Wind Harmer
0.004
316322AB2-045
Solar/Wind Helper
0.215
316072AD1-144
Solar/Wind Helper
0.16
3143526WINTERP
Solar/Wind Helper
0.708
964211AG1-282 GEN
Solar/Wind Helper
0.17
316248AF1-058 C
Solar/Wind Harmer
0.003
960061AF2-297 GEN
Solar/Wind Harmer
16.042
971683AH1-343 GEN
Solar/Wind Harmer
12.22
3147312GRETNA
Solar/Wind Harmer
0.026
942461AE2-259 GEN
Solar/Wind Helper
1.12
315839AE2-212 C
Solar/Wind Helper
0.202
316258AE1-075 C
Solar/Wind Helper
0.189
24728405LEESVG
50/50
0.138
316283AC2-100 C
Solar/Wind Harmer
0.523
941821AE2-187 GEN
Solar/Wind Harmer
4.18
270197AD1-017 GEN1
Solar/Wind Harmer
0.766
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
270336AE1-100 GEN
Solar/Wind Harmer
0.003
971367AH1-164 GEN
Solar/Wind Harmer
1.353
971623AH1-311 GEN
Solar/Wind Harmer
0.126
316478AD1-087 GEN
Solar/Wind Helper
3.07
316486AD2-202 GEN
Solar/Wind Helper
0.899
3145336SMITFLD
Solar/Wind Helper
0.059
3146456SLIGO L269
Solar/Wind Helper
0.141
3142946ENON
Solar/Wind Helper
0.045
316473AC1-191 GEN
Solar/Wind Helper
0.734
961601AG1-000A GEN
Solar/Wind Harmer
4.498
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
3146776BUCKING
Solar/Wind Helper
0.069
315773AC2-141 GEN
Solar/Wind Helper
3.58
3144536CHRHLND
Solar/Wind Helper
0.023
316313AB2-026
Solar/Wind Helper
0.21
316156AD2-030 GEN
Solar/Wind Helper
0.203
971629AH1-314 GEN
50/50
13.578
24728405LEESVG
50/50
0.138
970481AG2-311 GEN
50/50
4.594
316003AC1-222 GEN
Solar/Wind Harmer
0.009
3147123OTTER R
Solar/Wind Harmer
0.091
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
270030AE2-140 GEN
Solar/Wind Harmer
10.396
316359AB2-059 GEN
Solar/Wind Harmer
0.226
3142053HEARTS
Solar/Wind Harmer
0.111
316294AC1-161 GEN
Solar/Wind Helper
3.041
316375AC2-012 GEN
Solar/Wind Helper
0.399
3145336SMITFLD
Solar/Wind Helper
0.594
3146456SLIGO L269
Solar/Wind Helper
0.141
316336AC2-165 C
Solar/Wind Helper
0.741
3142433PROV 92
Solar/Wind Helper
0.538
3141766HARMONY
Solar/Wind Helper
0.027
3142416OLDCHRC
Solar/Wind Helper
0.325
3142416OLDCHRC
Solar/Wind Helper
0.124
3147173SINAI
Solar/Wind Harmer
0.376
3147243WELCO
Solar/Wind Harmer
0.235
970165AG2-112 GEN
Solar/Wind Harmer
2.171
970163AG2-111 GEN
Solar/Wind Harmer
2.071
316349AD2-085 GEN
Solar/Wind Helper
0.628
316059AD1-063 C
Solar/Wind Helper
0.135
3141783LANCAST
Solar/Wind Helper
0.079
3141783LANCAST
Solar/Wind Helper
0.053
313526AB2-022
Solar/Wind Helper
0.197
24684605SMG4
50/50
0.862
24288905REUSENS
50/50
0.013
270018AE2-047 C O1
Solar/Wind Harmer
0.002
3146926FARMVIL
Solar/Wind Helper
0.144
3144873MCLAUGH
Solar/Wind Helper
0.004
316382AG1-145 C
Solar/Wind Helper
0.191
316405AF2-144 C
Solar/Wind Helper
0.157
316280AD1-041 GEN
Solar/Wind Helper
0.451
316404AE1-155 C
Solar/Wind Helper
1.083
3141906WESTMOR
Solar/Wind Helper
0.047
970417AG2-272 GEN
50/50
1.899
970087AG2-069 GEN
Solar/Wind Harmer
11.404
970223AG2-152 GEN
Solar/Wind Harmer
9.437
316049AB1-081 GEN
Solar/Wind Harmer
0.36
3146926FARMVIL
Solar/Wind Helper
0.144
316381AD1-082 GEN
Solar/Wind Helper
0.747
316388AE2-253 GEN
Solar/Wind Helper
0.548
316458AB2-190 GEN2
Solar/Wind Helper
0.815
316159AE1-175 C
Solar/Wind Helper
0.215
3143226MDLTHAN
Solar/Wind Helper
0.139
316246AF1-032 C
Solar/Wind Helper
0.159
3142543TWELFTH
Solar/Wind Helper
0.013
3138133OCRAN
Solar/Wind Helper
0.08
970865AG2-541 GEN
Solar/Wind Harmer
10.778
316123AC1-075 GEN
Solar/Wind Harmer
0.366
957831AF2-077 GEN
Solar/Wind Helper
0.189
3141913WHIT STONE
Solar/Wind Helper
0.133
316315AB2-025 C
Solar/Wind Helper
0.196
316312AB1-027
Solar/Wind Helper
0.238
3151561HALLBR1
50/50
0.376
24684705SMG5
50/50
0.33
941801AE2-185 GEN
Solar/Wind Harmer
4.18
270173AC1-122 GEN
Solar/Wind Harmer
0.217
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.05
3146776BUCKING
Solar/Wind Helper
0.077
3141726DUNNSVL
Solar/Wind Helper
0.505
316337AD2-073 GEN
Solar/Wind Helper
0.185
3146516WINFALL
Solar/Wind Helper
0.373
3146516WINFALL
Solar/Wind Helper
0.115
961601AG1-000A GEN
Solar/Wind Harmer
1.124
3146776BUCKING
Solar/Wind Helper
0.771
3146776BUCKING
Solar/Wind Helper
0.062
316036AC1-147 C
Solar/Wind Helper
0.232
3142956BIRDNECK
Solar/Wind Helper
0.102
316240AF1-291 C
Solar/Wind Helper
0.195
316018AA1-139 ULT2
Solar/Wind Helper
0.614
966871AG1-558 GEN
Solar/Wind Helper
0.162
3146516WINFALL
Solar/Wind Helper
0.115
3146516WINFALL
Solar/Wind Helper
0.115
3146516WINFALL
Solar/Wind Helper
0.115
316222AC1-221 GEN
Solar/Wind Harmer
1.136
3146843MT LREL
Solar/Wind Harmer
0.235
3146843MT LREL
Solar/Wind Harmer
0.235
316017AA1-139 ULT1
Solar/Wind Helper
0.652
3142946ENON
Solar/Wind Helper
0.013
316487AF1-042 GEN
Solar/Wind Helper
0.131
3146386ELIZ CT
Solar/Wind Helper
0.129
316431W1029_GEN1
Solar/Wind Helper
0.477
316433W1029_GEN2
Solar/Wind Helper
0.477
3152661PLYWOOD A
50/50
0.687
24684405SMG2
50/50
0.856
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
3.251
316236AE1-162_GEN
Solar/Wind Helper
0.2
3145506HICKORY
Solar/Wind Helper
0.591
3145506HICKORY
Solar/Wind Helper
0.355
3145506HICKORY
Solar/Wind Helper
0.089
316339AD2-160 GEN
Solar/Wind Helper
0.548
316033AB2-134 GEN
Solar/Wind Helper
0.494
3137176SLIGO L2192
Solar/Wind Helper
0.561
3130086AYDLETT
Solar/Wind Helper
0.556
316484AD2-074 GEN
Solar/Wind Helper
0.25
316320Y1-086
Solar/Wind Helper
0.058
316435W1029_GEN3
Solar/Wind Helper
0.477
3146516WINFALL
Solar/Wind Helper
0.115
970581AG2-369 GEN
Solar/Wind Harmer
6.538
270069AE2-166 C O1
Solar/Wind Harmer
0.003
971981AH1-535 GEN
Solar/Wind Harmer
2.177
3143316POE
Solar/Wind Helper
0.626
316369SG1_INVT
Solar/Wind Helper
0.691
319010AE1-072 C
Solar/Wind Helper
1.597
3141873WAN 176
Solar/Wind Helper
0.027
315662AE1-191 GEN
Solar/Wind Helper
0.721
3143873LANEXA
Solar/Wind Helper
0.08
3138133OCRAN
Solar/Wind Helper
0.04
3146486SUNBURY
Solar/Wind Helper
0.126
3146486SUNBURY
Solar/Wind Helper
0.126
316321Z2-027
Solar/Wind Helper
0.19
3145176PASQUOTANK
Solar/Wind Helper
0.077
316118AC1-105 GEN
Solar/Wind Harmer
0.789
970085AG2-068 GEN
Solar/Wind Harmer
7.603
316132AB2-190 GEN1
Solar/Wind Helper
0.815
316305AF2-043 C
Solar/Wind Helper
0.186
316233AE1-074 FULL
Solar/Wind Helper
0.208
957601AF2-054 GEN
Solar/Wind Helper
0.18
315666AE1-190 GEN
Solar/Wind Helper
0.18
3141813NORNECK
Solar/Wind Helper
0.126
316223AC1-118
Solar/Wind Helper
0.181
24684305SMG1
50/50
0.31
962561AG1-105 GEN
Solar/Wind Harmer
9.757
270013AE1-250 PV
Solar/Wind Harmer
0.004
316263AC1-034 GEN
Solar/Wind Harmer
2.389
316316AC1-027 C
Solar/Wind Helper
0.238
316185AD1-033 GEN
Solar/Wind Helper
0.706
315697AD1-025 GEN
Solar/Wind Helper
1.643
3143526WINTERP
Solar/Wind Helper
0.708
316075AC2-137 C
Solar/Wind Helper
0.198
3144356SAPONY
Solar/Wind Helper
0.23
316077AC2-138 C
Solar/Wind Helper
0.118
316468AD1-105 GEN
Solar/Wind Helper
0.559
NYPJM->LTFIMP_NY
CLTF
0.706
LGEELTFEXP_LGEE->PJM
CLTF
2.033
WECLTFEXP_WEC->PJM
CLTF
1.077
AG2-052LTFEXP_AG2-052->PJM
LTF
0.061
AH1-155LTFEXP_AH1-155->PJM
LTF
0.091
LAGNLTFEXP_LAGN->PJM
CLTF
9.357
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.525
TVALTFEXP_TVA->PJM
CLTF
4.684
CPLELTFEXP_CPLE->PJM
CLTF
11.235
CBM West 2LTFEXP_CBM-W2->PJM
CBM
52.568
CBM West 1LTFEXP_CBM-W1->PJM
CBM
39.18
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.424
MECLTFEXP_MEC->PJM
CLTF
5.352
SIGELTFEXP_SIGE->PJM
CLTF
0.163

Details for 6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line l/o DVP_P4-2: 57062_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 57062_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.2 %
Rating:997.0 MVA
Rating Type:C
MVA to Mitigate:998.97
MW Contribution:1.94
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.138
316283AC2-100 C
Solar/Wind Harmer
2.83
941821AE2-187 GEN
Solar/Wind Harmer
5.503
270197AD1-017 GEN1
Solar/Wind Harmer
1.364
943811AF1-049 GEN
Solar/Wind Harmer
2.896
270336AE1-100 GEN
Solar/Wind Harmer
1.18
971367AH1-164 GEN
Solar/Wind Harmer
1.939
316478AD1-087 GEN
Solar/Wind Helper
3.07
316486AD2-202 GEN
Solar/Wind Helper
0.899
3145336SMITFLD
Solar/Wind Helper
0.059
3146456SLIGO L269
Solar/Wind Helper
0.141
3142946ENON
Solar/Wind Helper
0.045
316473AC1-191 GEN
Solar/Wind Helper
0.734
961601AG1-000A GEN
Solar/Wind Harmer
2.829
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146776BUCKING
Solar/Wind Helper
0.069
315773AC2-141 GEN
Solar/Wind Helper
3.58
3144536CHRHLND
Solar/Wind Helper
0.023
316313AB2-026
Solar/Wind Helper
0.21
316156AD2-030 GEN
Solar/Wind Helper
0.203
316484AD2-074 GEN
Solar/Wind Helper
0.25
316320Y1-086
Solar/Wind Helper
0.058
316435W1029_GEN3
Solar/Wind Helper
0.477
3146516WINFALL
Solar/Wind Helper
0.115
970917AG2-570 GEN
Solar/Wind Harmer
40.038
270018AE2-047 C O1
Solar/Wind Harmer
1.028
3146926FARMVIL
Solar/Wind Helper
0.144
3144873MCLAUGH
Solar/Wind Helper
0.004
316382AG1-145 C
Solar/Wind Helper
0.191
316405AF2-144 C
Solar/Wind Helper
0.157
316280AD1-041 GEN
Solar/Wind Helper
0.451
316404AE1-155 C
Solar/Wind Helper
1.083
3141906WESTMOR
Solar/Wind Helper
0.047
971629AH1-314 GEN
50/50
13.578
24728405LEESVG
50/50
0.138
316003AC1-222 GEN
Solar/Wind Harmer
3.867
3147123OTTER R
Solar/Wind Harmer
-0.01
270574AD1-017 GEN2
Solar/Wind Harmer
4.541
270030AE2-140 GEN
Solar/Wind Harmer
14.9
316359AB2-059 GEN
Solar/Wind Harmer
0.952
3142053HEARTS
Solar/Wind Harmer
0.083
316294AC1-161 GEN
Solar/Wind Helper
3.041
316375AC2-012 GEN
Solar/Wind Helper
0.399
3145336SMITFLD
Solar/Wind Helper
0.594
3146456SLIGO L269
Solar/Wind Helper
0.141
316336AC2-165 C
Solar/Wind Helper
0.741
3142433PROV 92
Solar/Wind Helper
0.538
3141766HARMONY
Solar/Wind Helper
0.027
3142416OLDCHRC
Solar/Wind Helper
0.325
3142416OLDCHRC
Solar/Wind Helper
0.124
970087AG2-069 GEN
Solar/Wind Harmer
15.015
970223AG2-152 GEN
Solar/Wind Harmer
13.457
316049AB1-081 GEN
Solar/Wind Harmer
0.762
3146926FARMVIL
Solar/Wind Helper
0.144
316381AD1-082 GEN
Solar/Wind Helper
0.747
316388AE2-253 GEN
Solar/Wind Helper
0.548
316458AB2-190 GEN2
Solar/Wind Helper
0.815
316159AE1-175 C
Solar/Wind Helper
0.215
3143226MDLTHAN
Solar/Wind Helper
0.139
316246AF1-032 C
Solar/Wind Helper
0.159
3142543TWELFTH
Solar/Wind Helper
0.013
3138133OCRAN
Solar/Wind Helper
0.08
3152661PLYWOOD A
50/50
0.687
316217AC1-145 GEN
Solar/Wind Harmer
2.382
316197AC1-042 GEN
Solar/Wind Harmer
1.806
942671AE2-283 GEN
Solar/Wind Harmer
4.861
316236AE1-162_GEN
Solar/Wind Helper
0.2
3145506HICKORY
Solar/Wind Helper
0.591
3145506HICKORY
Solar/Wind Helper
0.355
3145506HICKORY
Solar/Wind Helper
0.089
316339AD2-160 GEN
Solar/Wind Helper
0.548
316033AB2-134 GEN
Solar/Wind Helper
0.494
3137176SLIGO L2192
Solar/Wind Helper
0.561
3130086AYDLETT
Solar/Wind Helper
0.556
315687AD1-152 GEN
Solar/Wind Harmer
8.957
970401AG2-262 GEN
Solar/Wind Harmer
1.712
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
270016AE1-250 BESS
Solar/Wind Harmer
2.243
316322AB2-045
Solar/Wind Helper
0.215
316072AD1-144
Solar/Wind Helper
0.16
3143526WINTERP
Solar/Wind Helper
0.708
964211AG1-282 GEN
Solar/Wind Helper
0.17
3147173SINAI
Solar/Wind Harmer
-0.042
3147243WELCO
Solar/Wind Harmer
-0.026
970165AG2-112 GEN
Solar/Wind Harmer
2.859
970163AG2-111 GEN
Solar/Wind Harmer
2.727
270455AD2-022 GEN
Solar/Wind Harmer
3.551
316349AD2-085 GEN
Solar/Wind Helper
0.628
316059AD1-063 C
Solar/Wind Helper
0.135
3141783LANCAST
Solar/Wind Helper
0.079
3141783LANCAST
Solar/Wind Helper
0.053
313526AB2-022
Solar/Wind Helper
0.197
316118AC1-105 GEN
Solar/Wind Harmer
2.363
270457AD2-023 GEN
Solar/Wind Harmer
1.801
970085AG2-068 GEN
Solar/Wind Harmer
10.01
316132AB2-190 GEN1
Solar/Wind Helper
0.815
316305AF2-043 C
Solar/Wind Helper
0.186
316233AE1-074 FULL
Solar/Wind Helper
0.208
957601AF2-054 GEN
Solar/Wind Helper
0.18
315666AE1-190 GEN
Solar/Wind Helper
0.18
3141813NORNECK
Solar/Wind Helper
0.126
316223AC1-118
Solar/Wind Helper
0.181
970865AG2-541 GEN
Solar/Wind Harmer
14.192
316123AC1-075 GEN
Solar/Wind Harmer
3.247
957831AF2-077 GEN
Solar/Wind Helper
0.189
3141913WHIT STONE
Solar/Wind Helper
0.133
316315AB2-025 C
Solar/Wind Helper
0.196
316312AB1-027
Solar/Wind Helper
0.238
970581AG2-369 GEN
Solar/Wind Harmer
8.609
270069AE2-166 C O1
Solar/Wind Harmer
1.824
971981AH1-535 GEN
Solar/Wind Harmer
4.681
3143316POE
Solar/Wind Helper
0.626
316369SG1_INVT
Solar/Wind Helper
0.691
319010AE1-072 C
Solar/Wind Helper
1.597
3141873WAN 176
Solar/Wind Helper
0.027
315662AE1-191 GEN
Solar/Wind Helper
0.721
3143873LANEXA
Solar/Wind Helper
0.08
3138133OCRAN
Solar/Wind Helper
0.04
3146486SUNBURY
Solar/Wind Helper
0.126
3146486SUNBURY
Solar/Wind Helper
0.126
316321Z2-027
Solar/Wind Helper
0.19
3145176PASQUOTANK
Solar/Wind Helper
0.077
316222AC1-221 GEN
Solar/Wind Harmer
3.111
3146843MT LREL
Solar/Wind Harmer
-0.026
3146843MT LREL
Solar/Wind Harmer
-0.026
316017AA1-139 ULT1
Solar/Wind Helper
0.652
3142946ENON
Solar/Wind Helper
0.013
316487AF1-042 GEN
Solar/Wind Helper
0.131
3146386ELIZ CT
Solar/Wind Helper
0.129
316431W1029_GEN1
Solar/Wind Helper
0.477
316433W1029_GEN2
Solar/Wind Helper
0.477
942751AE2-291 GEN
Solar/Wind Harmer
17.229
964791AG1-342 GEN
Solar/Wind Harmer
5.603
961601AG1-000A GEN
Solar/Wind Harmer
2.793
3146776BUCKING
Solar/Wind Helper
0.771
3146776BUCKING
Solar/Wind Helper
0.062
316036AC1-147 C
Solar/Wind Helper
0.232
3142956BIRDNECK
Solar/Wind Helper
0.102
316240AF1-291 C
Solar/Wind Helper
0.195
316018AA1-139 ULT2
Solar/Wind Helper
0.614
966871AG1-558 GEN
Solar/Wind Helper
0.162
3146516WINFALL
Solar/Wind Helper
0.115
3146516WINFALL
Solar/Wind Helper
0.115
3146516WINFALL
Solar/Wind Helper
0.115
962561AG1-105 GEN
Solar/Wind Harmer
12.846
270013AE1-250 PV
Solar/Wind Harmer
2.243
316263AC1-034 GEN
Solar/Wind Harmer
3.311
316316AC1-027 C
Solar/Wind Helper
0.238
316185AD1-033 GEN
Solar/Wind Helper
0.706
315697AD1-025 GEN
Solar/Wind Helper
1.643
3143526WINTERP
Solar/Wind Helper
0.708
316075AC2-137 C
Solar/Wind Helper
0.198
3144356SAPONY
Solar/Wind Helper
0.23
316077AC2-138 C
Solar/Wind Helper
0.118
316468AD1-105 GEN
Solar/Wind Helper
0.559
316248AF1-058 C
Solar/Wind Harmer
1.273
960061AF2-297 GEN
Solar/Wind Harmer
21.123
971683AH1-343 GEN
Solar/Wind Harmer
16.09
3147312GRETNA
Solar/Wind Harmer
-0.003
942461AE2-259 GEN
Solar/Wind Helper
1.12
315839AE2-212 C
Solar/Wind Helper
0.202
316258AE1-075 C
Solar/Wind Helper
0.189
3151561HALLBR1
50/50
0.376
970919AG2-571 GEN
Solar/Wind Harmer
5.068
941801AE2-185 GEN
Solar/Wind Harmer
5.503
270173AC1-122 GEN
Solar/Wind Harmer
1.05
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.077
3141726DUNNSVL
Solar/Wind Helper
0.505
316337AD2-073 GEN
Solar/Wind Helper
0.185
3146516WINFALL
Solar/Wind Helper
0.373
3146516WINFALL
Solar/Wind Helper
0.115
NYPJM->LTFIMP_NY
CLTF
0.706
LGEELTFEXP_LGEE->PJM
CLTF
2.033
WECLTFEXP_WEC->PJM
CLTF
1.077
AG2-052LTFEXP_AG2-052->PJM
LTF
0.061
AH1-155LTFEXP_AH1-155->PJM
LTF
0.091
LAGNLTFEXP_LAGN->PJM
CLTF
9.357
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.525
TVALTFEXP_TVA->PJM
CLTF
4.684
CPLELTFEXP_CPLE->PJM
CLTF
11.235
CBM West 2LTFEXP_CBM-W2->PJM
CBM
52.568
CBM West 1LTFEXP_CBM-W1->PJM
CBM
39.18
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.424
MECLTFEXP_MEC->PJM
CLTF
5.352
SIGELTFEXP_SIGE->PJM
CLTF
0.163

Details for 6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 570_SRT-A-3


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:182.88 %
Rating:508.54 MVA
Rating Type:B
MVA to Mitigate:930.03
MW Contribution:1.21
Bus #Bus NameTypeMW Contribution
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
270336AE1-100 GEN
Solar/Wind Harmer
0.003
270197AD1-017 GEN1
Solar/Wind Harmer
0.53
971623AH1-311 GEN
Solar/Wind Harmer
0.145
971367AH1-164 GEN
Solar/Wind Harmer
1.205
3146073TAR RVR
Solar/Wind Harmer
0.064
3146083TARBORO
Solar/Wind Harmer
0.064
3138543CONSLDL
Solar/Wind Harmer
0.039
957471AF2-041 GEN
Solar/Wind Harmer
6.215
274676JOLIET 29;8U
Adder
8.719
316283AC2-100 C
Solar/Wind Helper
8.307
316478AD1-087 GEN
Solar/Wind Helper
2.495
316486AD2-202 GEN
Solar/Wind Helper
0.731
316131AB2-060 GEN
Solar/Wind Helper
2.179
3147133PAMPLIN
Solar/Wind Helper
0.969
3147043LAWRENC
Solar/Wind Helper
0.109
3145336SMITFLD
Solar/Wind Helper
0.053
3146456SLIGO L269
Solar/Wind Helper
0.123
3142946ENON
Solar/Wind Helper
0.04
961601AG1-000A GEN
Solar/Wind Harmer
5.289
3145543BTLEBRO
Solar/Wind Harmer
0.072
3145543BTLEBRO
Solar/Wind Harmer
0.072
959081AF2-199 GEN
Solar/Wind Harmer
2.072
971067AG2-660 GEN
Solar/Wind Harmer
0.691
3146776BUCKING
Solar/Wind Helper
0.077
315773AC2-141 GEN
Solar/Wind Helper
3.147
316313AB2-026
Solar/Wind Helper
0.207
3144536CHRHLND
Solar/Wind Helper
0.02
316156AD2-030 GEN
Solar/Wind Helper
0.181
316484AD2-074 GEN
Solar/Wind Helper
0.224
316320Y1-086
Solar/Wind Helper
0.05
970917AG2-570 GEN
Solar/Wind Harmer
15.316
270018AE2-047 C O1
Solar/Wind Harmer
0.003
3146233WITAKRS
Solar/Wind Harmer
0.287
3146233WITAKRS
Solar/Wind Harmer
0.039
274732ELWOOD EC;7P
Adder
4.672
315785AD2-033 C
Solar/Wind Helper
3.963
3146926FARMVIL
Solar/Wind Helper
0.16
316405AF2-144 C
Solar/Wind Helper
0.155
3144873MCLAUGH
Solar/Wind Helper
0.003
316382AG1-145 C
Solar/Wind Helper
0.17
316280AD1-041 GEN
Solar/Wind Helper
0.403
316404AE1-155 C
Solar/Wind Helper
0.968
971629AH1-314 GEN
50/50
15.388
270030AE2-140 GEN
Solar/Wind Harmer
11.004
270574AD1-017 GEN2
Solar/Wind Harmer
0
316359AB2-059 GEN
Solar/Wind Harmer
0.261
3142053HEARTS
Solar/Wind Harmer
0.128
3146083TARBORO
Solar/Wind Harmer
0.064
959091AF2-200 GEN
Solar/Wind Harmer
4.143
274734ELWOOD EC;8P
Adder
4.672
970417AG2-272 GEN
50/50
2.023
970087AG2-069 GEN
Solar/Wind Harmer
13.785
970223AG2-152 GEN
Solar/Wind Harmer
8.891
316049AB1-081 GEN
Solar/Wind Harmer
0.416
3145493TOT1
Solar/Wind Harmer
0.283
3146233WITAKRS
Solar/Wind Harmer
0.227
274730ELWOOD EC;6P
Adder
4.672
3146926FARMVIL
Solar/Wind Helper
0.16
316381AD1-082 GEN
Solar/Wind Helper
0.67
3143226MDLTHAN
Solar/Wind Helper
0.128
316458AB2-190 GEN2
Solar/Wind Helper
0.728
316159AE1-175 C
Solar/Wind Helper
0.191
316388AE2-253 GEN
Solar/Wind Helper
0.48
3142543TWELFTH
Solar/Wind Helper
0.012
316246AF1-032 C
Solar/Wind Helper
0.14
3138133OCRAN
Solar/Wind Helper
0.071
270016AE1-250 BESS
Solar/Wind Harmer
0.003
972273AH1-721 GEN
Adder
31.464
274729ELWOOD EC;1P
Adder
4.672
315687AD1-152 GEN
Solar/Wind Helper
3.789
316237AB2-079_GEN
Solar/Wind Helper
0.489
316322AB2-045
Solar/Wind Helper
0.238
316129AC1-054 GEN
Solar/Wind Helper
0.854
3143526WINTERP
Solar/Wind Helper
0.647
316072AD1-144
Solar/Wind Helper
0.141
964211AG1-282 GEN
Solar/Wind Helper
0.152
274736ELWOOD EC;9P
Adder
4.672
274676JOLIET 29;8U
Adder
8.408
316003AC1-222 GEN
Solar/Wind Helper
2.887
316294AC1-161 GEN
Solar/Wind Helper
2.674
3147123OTTER R
Solar/Wind Helper
0.085
316336AC2-165 C
Solar/Wind Helper
0.744
316375AC2-012 GEN
Solar/Wind Helper
0.351
3145336SMITFLD
Solar/Wind Helper
0.525
3146456SLIGO L269
Solar/Wind Helper
0.123
3142433PROV 92
Solar/Wind Helper
0.482
3141766HARMONY
Solar/Wind Helper
0.024
3142416OLDCHRC
Solar/Wind Helper
0.293
3142416OLDCHRC
Solar/Wind Helper
0.112
316420AA1-050 GEN
Solar/Wind Harmer
0.002
316319Z2-044 C
Solar/Wind Harmer
0
274735ELWOOD EC;4P
Adder
4.672
3147173SINAI
Solar/Wind Helper
0.727
3147243WELCO
Solar/Wind Helper
0.454
316349AD2-085 GEN
Solar/Wind Helper
0.563
316059AD1-063 C
Solar/Wind Helper
0.12
3141783LANCAST
Solar/Wind Helper
0.071
3141783LANCAST
Solar/Wind Helper
0.047
313526AB2-022
Solar/Wind Helper
0.171
970085AG2-068 GEN
Solar/Wind Harmer
9.19
274731ELWOOD EC;2P
Adder
4.672
274733ELWOOD EC;3P
Adder
4.672
972211AH1-690 GEN
Adder
28.667
316118AC1-105 GEN
Solar/Wind Helper
2.53
3144303KENBRDG
Solar/Wind Helper
0.269
316132AB2-190 GEN1
Solar/Wind Helper
0.728
316233AE1-074 FULL
Solar/Wind Helper
0.19
316305AF2-043 C
Solar/Wind Helper
0.164
957601AF2-054 GEN
Solar/Wind Helper
0.161
315666AE1-190 GEN
Solar/Wind Helper
0.161
3141813NORNECK
Solar/Wind Helper
0.112
3145573BETHELC
Solar/Wind Harmer
0.064
3145573BETHELC
Solar/Wind Harmer
0.064
274728ELWOOD EC;5P
Adder
4.672
316123AC1-075 GEN
Solar/Wind Helper
2.71
316239AB2-077_GEN
Solar/Wind Helper
0.489
316238AB2-078_GEN
Solar/Wind Helper
0.489
957831AF2-077 GEN
Solar/Wind Helper
0.168
316315AB2-025 C
Solar/Wind Helper
0.187
3141913WHIT STONE
Solar/Wind Helper
0.119
316312AB1-027
Solar/Wind Helper
0.214
3145493TOT1
Solar/Wind Harmer
0.148
316236AE1-162_GEN
Solar/Wind Helper
0.176
3145506HICKORY
Solar/Wind Helper
0.519
3145506HICKORY
Solar/Wind Helper
0.311
3145506HICKORY
Solar/Wind Helper
0.078
316033AB2-134 GEN
Solar/Wind Helper
0.44
316339AD2-160 GEN
Solar/Wind Helper
0.48
3137176SLIGO L2192
Solar/Wind Helper
0.49
3130086AYDLETT
Solar/Wind Helper
0.486
270013AE1-250 PV
Solar/Wind Harmer
0.003
316263AC1-034 GEN
Solar/Wind Harmer
2.764
3145603CNETO
Solar/Wind Harmer
0.059
316034AC1-036 C
Solar/Wind Helper
0.351
316316AC1-027 C
Solar/Wind Helper
0.209
316185AD1-033 GEN
Solar/Wind Helper
0.62
315697AD1-025 GEN
Solar/Wind Helper
1.464
3143526WINTERP
Solar/Wind Helper
0.647
3144356SAPONY
Solar/Wind Helper
0.22
316075AC2-137 C
Solar/Wind Helper
0.178
316077AC2-138 C
Solar/Wind Helper
0.106
971341AH1-150 GEN
Solar/Wind Harmer
4.143
971343AH1-151 GEN
Solar/Wind Harmer
4.143
316222AC1-221 GEN
Solar/Wind Helper
8.797
3146843MT LREL
Solar/Wind Helper
0.574
3146843MT LREL
Solar/Wind Helper
0.574
3147133PAMPLIN
Solar/Wind Helper
0.308
3147133PAMPLIN
Solar/Wind Helper
0.247
316017AA1-139 ULT1
Solar/Wind Helper
0.571
3142946ENON
Solar/Wind Helper
0.012
316487AF1-042 GEN
Solar/Wind Helper
0.117
3146386ELIZ CT
Solar/Wind Helper
0.113
961601AG1-000A GEN
Solar/Wind Harmer
1.322
3145453TOT5
Solar/Wind Harmer
0.089
3146776BUCKING
Solar/Wind Helper
0.854
3146776BUCKING
Solar/Wind Helper
0.069
316036AC1-147 C
Solar/Wind Helper
0.204
3142956BIRDNECK
Solar/Wind Helper
0.089
316240AF1-291 C
Solar/Wind Helper
0.176
316018AA1-139 ULT2
Solar/Wind Helper
0.537
970919AG2-571 GEN
Solar/Wind Harmer
6.126
3145543BTLEBRO
Solar/Wind Harmer
0.072
3145543BTLEBRO
Solar/Wind Harmer
0.058
961671AG1-007 GEN
Solar/Wind Harmer
0.01
3146776BUCKING
Solar/Wind Helper
0.085
3141726DUNNSVL
Solar/Wind Helper
0.452
970581AG2-369 GEN
Solar/Wind Harmer
7.903
270069AE2-166 C O1
Solar/Wind Harmer
0.003
971981AH1-535 GEN
Solar/Wind Harmer
2.359
971171AH1-044 GEN
Solar/Wind Harmer
4.143
274675JOLIET 29;7U
Adder
8.719
274675JOLIET 29;7U
Adder
8.408
3143316POE
Solar/Wind Helper
0.561
316369SG1_INVT
Solar/Wind Helper
0.616
319010AE1-072 C
Solar/Wind Helper
1.397
3141873WAN 176
Solar/Wind Helper
0.024
315662AE1-191 GEN
Solar/Wind Helper
0.644
3143873LANEXA
Solar/Wind Helper
0.072
3138133OCRAN
Solar/Wind Helper
0.036
316248AF1-058 C
Solar/Wind Helper
0.977
942461AE2-259 GEN
Solar/Wind Helper
1.948
316258AE1-075 C
Solar/Wind Helper
0.186
315839AE2-212 C
Solar/Wind Helper
0.182
944201AF1-088_MTX
Adder
34.575
900033ID_568986
External Queue
3.919766426086426
NYPJM->LTFIMP_NY
CLTF
0.599
LGEELTFEXP_LGEE->PJM
CLTF
2.145
WECLTFEXP_WEC->PJM
CLTF
1.147
AG2-052LTFEXP_AG2-052->PJM
LTF
0.064
AH1-155LTFEXP_AH1-155->PJM
LTF
0.096
LAGNLTFEXP_LAGN->PJM
CLTF
10.425
CBM South 2LTFEXP_CBM-S2->PJM
CBM
30.051
TVALTFEXP_TVA->PJM
CLTF
5.193
CPLELTFEXP_CPLE->PJM
CLTF
13.504
CBM West 2LTFEXP_CBM-W2->PJM
CBM
57.694
CBM West 1LTFEXP_CBM-W1->PJM
CBM
41.755
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.101
MECLTFEXP_MEC->PJM
CLTF
5.768
SIGELTFEXP_SIGE->PJM
CLTF
0.174

Details for 6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 570_SRT-A-2


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:178.67 %
Rating:508.54 MVA
Rating Type:B
MVA to Mitigate:908.59
MW Contribution:1.21
Bus #Bus NameTypeMW Contribution
961601AG1-000A GEN
Solar/Wind Harmer
5.289
3145543BTLEBRO
Solar/Wind Harmer
0.072
3145543BTLEBRO
Solar/Wind Harmer
0.072
959081AF2-199 GEN
Solar/Wind Harmer
2.072
971067AG2-660 GEN
Solar/Wind Harmer
0.691
3146776BUCKING
Solar/Wind Helper
0.077
315773AC2-141 GEN
Solar/Wind Helper
3.147
316313AB2-026
Solar/Wind Helper
0.207
3144536CHRHLND
Solar/Wind Helper
0.02
316156AD2-030 GEN
Solar/Wind Helper
0.181
316484AD2-074 GEN
Solar/Wind Helper
0.224
316320Y1-086
Solar/Wind Helper
0.05
270018AE2-047 C O1
Solar/Wind Harmer
0.003
3146233WITAKRS
Solar/Wind Harmer
0.287
3146233WITAKRS
Solar/Wind Harmer
0.039
274732ELWOOD EC;7P
Adder
4.672
315785AD2-033 C
Solar/Wind Helper
3.963
3146926FARMVIL
Solar/Wind Helper
0.16
316405AF2-144 C
Solar/Wind Helper
0.155
3144873MCLAUGH
Solar/Wind Helper
0.003
316382AG1-145 C
Solar/Wind Helper
0.17
316280AD1-041 GEN
Solar/Wind Helper
0.403
316404AE1-155 C
Solar/Wind Helper
0.968
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
270336AE1-100 GEN
Solar/Wind Harmer
0.003
270197AD1-017 GEN1
Solar/Wind Harmer
0.53
971623AH1-311 GEN
Solar/Wind Harmer
0.145
971367AH1-164 GEN
Solar/Wind Harmer
1.205
3146073TAR RVR
Solar/Wind Harmer
0.064
3146083TARBORO
Solar/Wind Harmer
0.064
3138543CONSLDL
Solar/Wind Harmer
0.039
957471AF2-041 GEN
Solar/Wind Harmer
6.215
274676JOLIET 29;8U
Adder
8.719
316283AC2-100 C
Solar/Wind Helper
8.307
316478AD1-087 GEN
Solar/Wind Helper
2.495
316486AD2-202 GEN
Solar/Wind Helper
0.731
316131AB2-060 GEN
Solar/Wind Helper
2.179
3147133PAMPLIN
Solar/Wind Helper
0.969
3147043LAWRENC
Solar/Wind Helper
0.109
3145336SMITFLD
Solar/Wind Helper
0.053
3146456SLIGO L269
Solar/Wind Helper
0.123
3142946ENON
Solar/Wind Helper
0.04
970417AG2-272 GEN
50/50
2.023
970087AG2-069 GEN
Solar/Wind Harmer
13.785
970223AG2-152 GEN
Solar/Wind Harmer
8.891
316049AB1-081 GEN
Solar/Wind Harmer
0.416
3145493TOT1
Solar/Wind Harmer
0.283
3146233WITAKRS
Solar/Wind Harmer
0.227
274730ELWOOD EC;6P
Adder
4.672
3146926FARMVIL
Solar/Wind Helper
0.16
316381AD1-082 GEN
Solar/Wind Helper
0.67
3143226MDLTHAN
Solar/Wind Helper
0.128
316458AB2-190 GEN2
Solar/Wind Helper
0.728
316159AE1-175 C
Solar/Wind Helper
0.191
316388AE2-253 GEN
Solar/Wind Helper
0.48
3142543TWELFTH
Solar/Wind Helper
0.012
316246AF1-032 C
Solar/Wind Helper
0.14
3138133OCRAN
Solar/Wind Helper
0.071
270016AE1-250 BESS
Solar/Wind Harmer
0.003
972273AH1-721 GEN
Adder
31.464
274729ELWOOD EC;1P
Adder
4.672
315687AD1-152 GEN
Solar/Wind Helper
3.789
316237AB2-079_GEN
Solar/Wind Helper
0.489
316322AB2-045
Solar/Wind Helper
0.238
316129AC1-054 GEN
Solar/Wind Helper
0.854
3143526WINTERP
Solar/Wind Helper
0.647
316072AD1-144
Solar/Wind Helper
0.141
964211AG1-282 GEN
Solar/Wind Helper
0.152
971629AH1-314 GEN
50/50
15.388
270030AE2-140 GEN
Solar/Wind Harmer
11.004
270574AD1-017 GEN2
Solar/Wind Harmer
0
316359AB2-059 GEN
Solar/Wind Harmer
0.261
3142053HEARTS
Solar/Wind Harmer
0.128
3146083TARBORO
Solar/Wind Harmer
0.064
959091AF2-200 GEN
Solar/Wind Harmer
4.143
274734ELWOOD EC;8P
Adder
4.672
274736ELWOOD EC;9P
Adder
4.672
274676JOLIET 29;8U
Adder
8.408
316003AC1-222 GEN
Solar/Wind Helper
2.887
316294AC1-161 GEN
Solar/Wind Helper
2.674
3147123OTTER R
Solar/Wind Helper
0.085
316336AC2-165 C
Solar/Wind Helper
0.744
316375AC2-012 GEN
Solar/Wind Helper
0.351
3145336SMITFLD
Solar/Wind Helper
0.525
3146456SLIGO L269
Solar/Wind Helper
0.123
3142433PROV 92
Solar/Wind Helper
0.482
3141766HARMONY
Solar/Wind Helper
0.024
3142416OLDCHRC
Solar/Wind Helper
0.293
3142416OLDCHRC
Solar/Wind Helper
0.112
316420AA1-050 GEN
Solar/Wind Harmer
0.002
970085AG2-068 GEN
Solar/Wind Harmer
9.19
274731ELWOOD EC;2P
Adder
4.672
274733ELWOOD EC;3P
Adder
4.672
972211AH1-690 GEN
Adder
28.667
316118AC1-105 GEN
Solar/Wind Helper
2.53
3144303KENBRDG
Solar/Wind Helper
0.269
316132AB2-190 GEN1
Solar/Wind Helper
0.728
316233AE1-074 FULL
Solar/Wind Helper
0.19
316305AF2-043 C
Solar/Wind Helper
0.164
3145573BETHELC
Solar/Wind Harmer
0.064
3145573BETHELC
Solar/Wind Harmer
0.064
274728ELWOOD EC;5P
Adder
4.672
316123AC1-075 GEN
Solar/Wind Helper
2.71
316239AB2-077_GEN
Solar/Wind Helper
0.489
316238AB2-078_GEN
Solar/Wind Helper
0.489
957831AF2-077 GEN
Solar/Wind Helper
0.168
316315AB2-025 C
Solar/Wind Helper
0.187
3141913WHIT STONE
Solar/Wind Helper
0.119
316312AB1-027
Solar/Wind Helper
0.214
3145493TOT1
Solar/Wind Harmer
0.148
316236AE1-162_GEN
Solar/Wind Helper
0.176
3145506HICKORY
Solar/Wind Helper
0.519
3145506HICKORY
Solar/Wind Helper
0.311
3145506HICKORY
Solar/Wind Helper
0.078
316033AB2-134 GEN
Solar/Wind Helper
0.44
316339AD2-160 GEN
Solar/Wind Helper
0.48
3137176SLIGO L2192
Solar/Wind Helper
0.49
3130086AYDLETT
Solar/Wind Helper
0.486
316319Z2-044 C
Solar/Wind Harmer
0
274735ELWOOD EC;4P
Adder
4.672
3147173SINAI
Solar/Wind Helper
0.727
3147243WELCO
Solar/Wind Helper
0.454
316349AD2-085 GEN
Solar/Wind Helper
0.563
316059AD1-063 C
Solar/Wind Helper
0.12
3141783LANCAST
Solar/Wind Helper
0.071
3141783LANCAST
Solar/Wind Helper
0.047
313526AB2-022
Solar/Wind Helper
0.171
957601AF2-054 GEN
Solar/Wind Helper
0.161
315666AE1-190 GEN
Solar/Wind Helper
0.161
3141813NORNECK
Solar/Wind Helper
0.112
270013AE1-250 PV
Solar/Wind Harmer
0.003
316263AC1-034 GEN
Solar/Wind Harmer
2.764
3145603CNETO
Solar/Wind Harmer
0.059
316034AC1-036 C
Solar/Wind Helper
0.351
316316AC1-027 C
Solar/Wind Helper
0.209
316185AD1-033 GEN
Solar/Wind Helper
0.62
315697AD1-025 GEN
Solar/Wind Helper
1.464
3143526WINTERP
Solar/Wind Helper
0.647
3144356SAPONY
Solar/Wind Helper
0.22
316075AC2-137 C
Solar/Wind Helper
0.178
316077AC2-138 C
Solar/Wind Helper
0.106
971341AH1-150 GEN
Solar/Wind Harmer
4.143
971343AH1-151 GEN
Solar/Wind Harmer
4.143
316222AC1-221 GEN
Solar/Wind Helper
8.797
3146843MT LREL
Solar/Wind Helper
0.574
3146843MT LREL
Solar/Wind Helper
0.574
3147133PAMPLIN
Solar/Wind Helper
0.308
3147133PAMPLIN
Solar/Wind Helper
0.247
316017AA1-139 ULT1
Solar/Wind Helper
0.571
3142946ENON
Solar/Wind Helper
0.012
316487AF1-042 GEN
Solar/Wind Helper
0.117
3146386ELIZ CT
Solar/Wind Helper
0.113
961601AG1-000A GEN
Solar/Wind Harmer
1.322
3145453TOT5
Solar/Wind Harmer
0.089
3146776BUCKING
Solar/Wind Helper
0.854
3146776BUCKING
Solar/Wind Helper
0.069
316036AC1-147 C
Solar/Wind Helper
0.204
3142956BIRDNECK
Solar/Wind Helper
0.089
316240AF1-291 C
Solar/Wind Helper
0.176
316018AA1-139 ULT2
Solar/Wind Helper
0.537
3145543BTLEBRO
Solar/Wind Harmer
0.072
3145543BTLEBRO
Solar/Wind Harmer
0.058
961671AG1-007 GEN
Solar/Wind Harmer
0.01
3146776BUCKING
Solar/Wind Helper
0.085
3141726DUNNSVL
Solar/Wind Helper
0.452
970581AG2-369 GEN
Solar/Wind Harmer
7.903
270069AE2-166 C O1
Solar/Wind Harmer
0.003
971981AH1-535 GEN
Solar/Wind Harmer
2.359
971171AH1-044 GEN
Solar/Wind Harmer
4.143
274675JOLIET 29;7U
Adder
8.719
274675JOLIET 29;7U
Adder
8.408
3143316POE
Solar/Wind Helper
0.561
316369SG1_INVT
Solar/Wind Helper
0.616
319010AE1-072 C
Solar/Wind Helper
1.397
3141873WAN 176
Solar/Wind Helper
0.024
315662AE1-191 GEN
Solar/Wind Helper
0.644
3143873LANEXA
Solar/Wind Helper
0.072
3138133OCRAN
Solar/Wind Helper
0.036
316248AF1-058 C
Solar/Wind Helper
0.977
942461AE2-259 GEN
Solar/Wind Helper
1.948
316258AE1-075 C
Solar/Wind Helper
0.186
315839AE2-212 C
Solar/Wind Helper
0.182
944201AF1-088_MTX
Adder
34.575
900033ID_568986
External Queue
3.919766426086426
NYPJM->LTFIMP_NY
CLTF
0.599
LGEELTFEXP_LGEE->PJM
CLTF
2.145
WECLTFEXP_WEC->PJM
CLTF
1.147
AG2-052LTFEXP_AG2-052->PJM
LTF
0.064
AH1-155LTFEXP_AH1-155->PJM
LTF
0.096
LAGNLTFEXP_LAGN->PJM
CLTF
10.425
CBM South 2LTFEXP_CBM-S2->PJM
CBM
30.051
TVALTFEXP_TVA->PJM
CLTF
5.193
CPLELTFEXP_CPLE->PJM
CLTF
13.504
CBM West 2LTFEXP_CBM-W2->PJM
CBM
57.694
CBM West 1LTFEXP_CBM-W1->PJM
CBM
41.755
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.101
MECLTFEXP_MEC->PJM
CLTF
5.768
SIGELTFEXP_SIGE->PJM
CLTF
0.174

Details for 6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line l/o DVP_P4-2: 509T570_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 509T570_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.79 %
Rating:997.0 MVA
Rating Type:C
MVA to Mitigate:1094.57
MW Contribution:1.92
Bus #Bus NameTypeMW Contribution
961601AG1-000A GEN
Solar/Wind Harmer
2.799
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146776BUCKING
Solar/Wind Helper
0.07
315773AC2-141 GEN
Solar/Wind Helper
3.608
3144536CHRHLND
Solar/Wind Helper
0.023
316313AB2-026
Solar/Wind Helper
0.212
316156AD2-030 GEN
Solar/Wind Helper
0.205
316484AD2-074 GEN
Solar/Wind Helper
0.253
316320Y1-086
Solar/Wind Helper
0.058
316435W1029_GEN3
Solar/Wind Helper
0.482
3146516WINFALL
Solar/Wind Helper
0.117
970581AG2-369 GEN
Solar/Wind Harmer
8.568
270069AE2-166 C O1
Solar/Wind Harmer
1.81
971981AH1-535 GEN
Solar/Wind Harmer
4.63
3143316POE
Solar/Wind Helper
0.631
316369SG1_INVT
Solar/Wind Helper
0.698
319010AE1-072 C
Solar/Wind Helper
1.613
3141873WAN 176
Solar/Wind Helper
0.027
315662AE1-191 GEN
Solar/Wind Helper
0.728
3143873LANEXA
Solar/Wind Helper
0.081
3138133OCRAN
Solar/Wind Helper
0.04
3146486SUNBURY
Solar/Wind Helper
0.128
3146486SUNBURY
Solar/Wind Helper
0.128
316321Z2-027
Solar/Wind Helper
0.192
3145176PASQUOTANK
Solar/Wind Helper
0.078
970917AG2-570 GEN
Solar/Wind Harmer
39.848
270018AE2-047 C O1
Solar/Wind Harmer
1.022
3146926FARMVIL
Solar/Wind Helper
0.145
3144873MCLAUGH
Solar/Wind Helper
0.004
316382AG1-145 C
Solar/Wind Helper
0.193
316405AF2-144 C
Solar/Wind Helper
0.159
316280AD1-041 GEN
Solar/Wind Helper
0.455
316404AE1-155 C
Solar/Wind Helper
1.094
3141906WESTMOR
Solar/Wind Helper
0.048
3147173SINAI
Solar/Wind Harmer
-0.042
3147243WELCO
Solar/Wind Harmer
-0.026
970165AG2-112 GEN
Solar/Wind Harmer
2.852
970163AG2-111 GEN
Solar/Wind Harmer
2.72
270455AD2-022 GEN
Solar/Wind Harmer
3.538
316349AD2-085 GEN
Solar/Wind Helper
0.634
316059AD1-063 C
Solar/Wind Helper
0.136
3141783LANCAST
Solar/Wind Helper
0.08
3141783LANCAST
Solar/Wind Helper
0.053
313526AB2-022
Solar/Wind Helper
0.199
316222AC1-221 GEN
Solar/Wind Harmer
3.103
3146843MT LREL
Solar/Wind Harmer
-0.026
3146843MT LREL
Solar/Wind Harmer
-0.026
316017AA1-139 ULT1
Solar/Wind Helper
0.658
3142946ENON
Solar/Wind Helper
0.014
316487AF1-042 GEN
Solar/Wind Helper
0.132
3146386ELIZ CT
Solar/Wind Helper
0.131
316431W1029_GEN1
Solar/Wind Helper
0.482
316433W1029_GEN2
Solar/Wind Helper
0.482
24728405LEESVG
50/50
0.137
316283AC2-100 C
Solar/Wind Harmer
2.823
941821AE2-187 GEN
Solar/Wind Harmer
5.475
270197AD1-017 GEN1
Solar/Wind Harmer
1.356
943811AF1-049 GEN
Solar/Wind Harmer
2.877
270336AE1-100 GEN
Solar/Wind Harmer
1.171
971367AH1-164 GEN
Solar/Wind Harmer
1.921
316478AD1-087 GEN
Solar/Wind Helper
3.077
316486AD2-202 GEN
Solar/Wind Helper
0.901
3145336SMITFLD
Solar/Wind Helper
0.06
3146456SLIGO L269
Solar/Wind Helper
0.142
3142946ENON
Solar/Wind Helper
0.045
316473AC1-191 GEN
Solar/Wind Helper
0.742
970865AG2-541 GEN
Solar/Wind Harmer
14.161
316123AC1-075 GEN
Solar/Wind Harmer
3.239
957831AF2-077 GEN
Solar/Wind Helper
0.191
3141913WHIT STONE
Solar/Wind Helper
0.134
316315AB2-025 C
Solar/Wind Helper
0.198
316312AB1-027
Solar/Wind Helper
0.24
962561AG1-105 GEN
Solar/Wind Harmer
12.803
270013AE1-250 PV
Solar/Wind Harmer
2.232
316263AC1-034 GEN
Solar/Wind Harmer
3.276
316316AC1-027 C
Solar/Wind Helper
0.24
316185AD1-033 GEN
Solar/Wind Helper
0.713
315697AD1-025 GEN
Solar/Wind Helper
1.658
3143526WINTERP
Solar/Wind Helper
0.715
316075AC2-137 C
Solar/Wind Helper
0.2
3144356SAPONY
Solar/Wind Helper
0.233
316077AC2-138 C
Solar/Wind Helper
0.12
316468AD1-105 GEN
Solar/Wind Helper
0.565
971629AH1-314 GEN
50/50
13.518
24728405LEESVG
50/50
0.137
316003AC1-222 GEN
Solar/Wind Harmer
3.859
3147123OTTER R
Solar/Wind Harmer
-0.01
270574AD1-017 GEN2
Solar/Wind Harmer
4.514
270030AE2-140 GEN
Solar/Wind Harmer
14.796
316359AB2-059 GEN
Solar/Wind Harmer
0.942
3142053HEARTS
Solar/Wind Harmer
0.082
316294AC1-161 GEN
Solar/Wind Helper
3.066
316375AC2-012 GEN
Solar/Wind Helper
0.403
3145336SMITFLD
Solar/Wind Helper
0.6
3146456SLIGO L269
Solar/Wind Helper
0.142
316336AC2-165 C
Solar/Wind Helper
0.748
316248AF1-058 C
Solar/Wind Harmer
1.271
960061AF2-297 GEN
Solar/Wind Harmer
21.085
971683AH1-343 GEN
Solar/Wind Harmer
16.057
3147312GRETNA
Solar/Wind Harmer
-0.003
942461AE2-259 GEN
Solar/Wind Helper
1.129
315839AE2-212 C
Solar/Wind Helper
0.204
316258AE1-075 C
Solar/Wind Helper
0.191
3142433PROV 92
Solar/Wind Helper
0.543
3141766HARMONY
Solar/Wind Helper
0.027
3142416OLDCHRC
Solar/Wind Helper
0.328
3142416OLDCHRC
Solar/Wind Helper
0.126
970401AG2-262 GEN
Solar/Wind Harmer
1.707
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
270016AE1-250 BESS
Solar/Wind Harmer
2.232
315687AD1-152 GEN
Solar/Wind Helper
4.938
316322AB2-045
Solar/Wind Helper
0.216
316072AD1-144
Solar/Wind Helper
0.162
3143526WINTERP
Solar/Wind Helper
0.715
964211AG1-282 GEN
Solar/Wind Helper
0.172
316118AC1-105 GEN
Solar/Wind Harmer
2.358
270457AD2-023 GEN
Solar/Wind Harmer
1.794
970085AG2-068 GEN
Solar/Wind Harmer
9.963
316132AB2-190 GEN1
Solar/Wind Helper
0.823
316305AF2-043 C
Solar/Wind Helper
0.188
316233AE1-074 FULL
Solar/Wind Helper
0.21
957601AF2-054 GEN
Solar/Wind Helper
0.182
315666AE1-190 GEN
Solar/Wind Helper
0.182
3141813NORNECK
Solar/Wind Helper
0.127
316223AC1-118
Solar/Wind Helper
0.183
942751AE2-291 GEN
Solar/Wind Harmer
17.181
964791AG1-342 GEN
Solar/Wind Harmer
5.586
961601AG1-000A GEN
Solar/Wind Harmer
2.764
3146776BUCKING
Solar/Wind Helper
0.776
3146776BUCKING
Solar/Wind Helper
0.063
316036AC1-147 C
Solar/Wind Helper
0.234
3142956BIRDNECK
Solar/Wind Helper
0.103
316240AF1-291 C
Solar/Wind Helper
0.197
316018AA1-139 ULT2
Solar/Wind Helper
0.62
966871AG1-558 GEN
Solar/Wind Helper
0.164
3146516WINFALL
Solar/Wind Helper
0.117
3146516WINFALL
Solar/Wind Helper
0.117
3146516WINFALL
Solar/Wind Helper
0.117
3152661PLYWOOD A
50/50
0.686
316217AC1-145 GEN
Solar/Wind Harmer
2.369
316197AC1-042 GEN
Solar/Wind Harmer
1.796
942671AE2-283 GEN
Solar/Wind Harmer
4.836
316236AE1-162_GEN
Solar/Wind Helper
0.201
3145506HICKORY
Solar/Wind Helper
0.597
3145506HICKORY
Solar/Wind Helper
0.358
3145506HICKORY
Solar/Wind Helper
0.089
316339AD2-160 GEN
Solar/Wind Helper
0.553
316033AB2-134 GEN
Solar/Wind Helper
0.499
3137176SLIGO L2192
Solar/Wind Helper
0.566
3130086AYDLETT
Solar/Wind Helper
0.562
3151561HALLBR1
50/50
0.374
970919AG2-571 GEN
Solar/Wind Harmer
5.044
941801AE2-185 GEN
Solar/Wind Harmer
5.475
270173AC1-122 GEN
Solar/Wind Harmer
1.042
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.078
3141726DUNNSVL
Solar/Wind Helper
0.511
316337AD2-073 GEN
Solar/Wind Helper
0.187
3146516WINFALL
Solar/Wind Helper
0.378
3146516WINFALL
Solar/Wind Helper
0.117
970087AG2-069 GEN
Solar/Wind Harmer
14.944
970223AG2-152 GEN
Solar/Wind Harmer
13.39
316049AB1-081 GEN
Solar/Wind Harmer
0.754
3146926FARMVIL
Solar/Wind Helper
0.145
316381AD1-082 GEN
Solar/Wind Helper
0.754
316388AE2-253 GEN
Solar/Wind Helper
0.553
316458AB2-190 GEN2
Solar/Wind Helper
0.823
316159AE1-175 C
Solar/Wind Helper
0.217
3143226MDLTHAN
Solar/Wind Helper
0.14
316246AF1-032 C
Solar/Wind Helper
0.16
3142543TWELFTH
Solar/Wind Helper
0.013
3138133OCRAN
Solar/Wind Helper
0.08
NYPJM->LTFIMP_NY
CLTF
0.739
LGEELTFEXP_LGEE->PJM
CLTF
1.997
WECLTFEXP_WEC->PJM
CLTF
1.057
LAGNLTFEXP_LAGN->PJM
CLTF
9.252
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.368
TVALTFEXP_TVA->PJM
CLTF
4.632
CPLELTFEXP_CPLE->PJM
CLTF
11.178
CBM West 2LTFEXP_CBM-W2->PJM
CBM
51.871
CBM West 1LTFEXP_CBM-W1->PJM
CBM
38.424
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.227
MECLTFEXP_MEC->PJM
CLTF
5.265
SIGELTFEXP_SIGE->PJM
CLTF
0.161

Details for 6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 570_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.53 %
Rating:814.98 MVA
Rating Type:B
MVA to Mitigate:843.75
MW Contribution:1.36
Bus #Bus NameTypeMW Contribution
970401AG2-262 GEN
Solar/Wind Harmer
1.371
3147312GRETNA
Solar/Wind Harmer
0.105
3146802CHATHAM
Solar/Wind Harmer
0.098
270016AE1-250 BESS
Solar/Wind Harmer
0.004
315687AD1-152 GEN
Solar/Wind Helper
4.927
316322AB2-045
Solar/Wind Helper
0.214
316072AD1-144
Solar/Wind Helper
0.16
3143526WINTERP
Solar/Wind Helper
0.705
964211AG1-282 GEN
Solar/Wind Helper
0.169
316248AF1-058 C
Solar/Wind Harmer
0.003
960061AF2-297 GEN
Solar/Wind Harmer
16.056
971683AH1-343 GEN
Solar/Wind Harmer
12.232
3147312GRETNA
Solar/Wind Harmer
0.026
942461AE2-259 GEN
Solar/Wind Helper
1.116
315839AE2-212 C
Solar/Wind Helper
0.201
316258AE1-075 C
Solar/Wind Helper
0.188
24728405LEESVG
50/50
0.138
316283AC2-100 C
Solar/Wind Harmer
0.524
941821AE2-187 GEN
Solar/Wind Harmer
4.19
270197AD1-017 GEN1
Solar/Wind Harmer
0.768
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
270336AE1-100 GEN
Solar/Wind Harmer
0.003
971367AH1-164 GEN
Solar/Wind Harmer
1.359
971623AH1-311 GEN
Solar/Wind Harmer
0.126
316478AD1-087 GEN
Solar/Wind Helper
3.067
316486AD2-202 GEN
Solar/Wind Helper
0.898
3145336SMITFLD
Solar/Wind Helper
0.059
3146456SLIGO L269
Solar/Wind Helper
0.14
3142946ENON
Solar/Wind Helper
0.045
316473AC1-191 GEN
Solar/Wind Helper
0.73
971629AH1-314 GEN
50/50
13.606
24728405LEESVG
50/50
0.138
970481AG2-311 GEN
50/50
4.609
316003AC1-222 GEN
Solar/Wind Harmer
0.009
3147123OTTER R
Solar/Wind Harmer
0.091
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
270030AE2-140 GEN
Solar/Wind Harmer
10.43
316359AB2-059 GEN
Solar/Wind Harmer
0.227
3142053HEARTS
Solar/Wind Harmer
0.111
316294AC1-161 GEN
Solar/Wind Helper
3.03
316375AC2-012 GEN
Solar/Wind Helper
0.398
3145336SMITFLD
Solar/Wind Helper
0.592
3146456SLIGO L269
Solar/Wind Helper
0.14
316336AC2-165 C
Solar/Wind Helper
0.738
3142433PROV 92
Solar/Wind Helper
0.535
3141766HARMONY
Solar/Wind Helper
0.027
3142416OLDCHRC
Solar/Wind Helper
0.323
3142416OLDCHRC
Solar/Wind Helper
0.124
3147173SINAI
Solar/Wind Harmer
0.376
3147243WELCO
Solar/Wind Harmer
0.235
970165AG2-112 GEN
Solar/Wind Harmer
2.174
970163AG2-111 GEN
Solar/Wind Harmer
2.074
316349AD2-085 GEN
Solar/Wind Helper
0.625
316059AD1-063 C
Solar/Wind Helper
0.134
3141783LANCAST
Solar/Wind Helper
0.079
3141783LANCAST
Solar/Wind Helper
0.053
313526AB2-022
Solar/Wind Helper
0.196
24684605SMG4
50/50
0.864
24288905REUSENS
50/50
0.013
970917AG2-570 GEN
Solar/Wind Harmer
12.699
270018AE2-047 C O1
Solar/Wind Harmer
0.002
3146926FARMVIL
Solar/Wind Helper
0.143
3144873MCLAUGH
Solar/Wind Helper
0.004
316382AG1-145 C
Solar/Wind Helper
0.19
316405AF2-144 C
Solar/Wind Helper
0.157
316280AD1-041 GEN
Solar/Wind Helper
0.449
316404AE1-155 C
Solar/Wind Helper
1.078
3141906WESTMOR
Solar/Wind Helper
0.047
970417AG2-272 GEN
50/50
1.905
970087AG2-069 GEN
Solar/Wind Harmer
11.429
970223AG2-152 GEN
Solar/Wind Harmer
9.459
316049AB1-081 GEN
Solar/Wind Harmer
0.362
3146926FARMVIL
Solar/Wind Helper
0.143
316381AD1-082 GEN
Solar/Wind Helper
0.744
316388AE2-253 GEN
Solar/Wind Helper
0.545
316458AB2-190 GEN2
Solar/Wind Helper
0.811
316159AE1-175 C
Solar/Wind Helper
0.214
3143226MDLTHAN
Solar/Wind Helper
0.138
316246AF1-032 C
Solar/Wind Helper
0.158
3142543TWELFTH
Solar/Wind Helper
0.013
3138133OCRAN
Solar/Wind Helper
0.079
970865AG2-541 GEN
Solar/Wind Harmer
10.789
316123AC1-075 GEN
Solar/Wind Harmer
0.367
957831AF2-077 GEN
Solar/Wind Helper
0.188
3141913WHIT STONE
Solar/Wind Helper
0.132
316315AB2-025 C
Solar/Wind Helper
0.195
316312AB1-027
Solar/Wind Helper
0.236
3151561HALLBR1
50/50
0.377
24684705SMG5
50/50
0.331
970919AG2-571 GEN
Solar/Wind Harmer
5.079
941801AE2-185 GEN
Solar/Wind Harmer
4.19
270173AC1-122 GEN
Solar/Wind Harmer
0.218
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.05
3146776BUCKING
Solar/Wind Helper
0.077
3141726DUNNSVL
Solar/Wind Helper
0.503
316337AD2-073 GEN
Solar/Wind Helper
0.184
3146516WINFALL
Solar/Wind Helper
0.371
3146516WINFALL
Solar/Wind Helper
0.115
24684505SMG3
50/50
0.531
942751AE2-291 GEN
Solar/Wind Harmer
13.103
964791AG1-342 GEN
Solar/Wind Harmer
4.488
961601AG1-000A GEN
Solar/Wind Harmer
1.13
3146776BUCKING
Solar/Wind Helper
0.769
3146776BUCKING
Solar/Wind Helper
0.062
316036AC1-147 C
Solar/Wind Helper
0.231
3142956BIRDNECK
Solar/Wind Helper
0.101
316240AF1-291 C
Solar/Wind Helper
0.194
316018AA1-139 ULT2
Solar/Wind Helper
0.611
966871AG1-558 GEN
Solar/Wind Helper
0.161
3146516WINFALL
Solar/Wind Helper
0.115
3146516WINFALL
Solar/Wind Helper
0.115
3146516WINFALL
Solar/Wind Helper
0.115
316222AC1-221 GEN
Solar/Wind Harmer
1.137
3146843MT LREL
Solar/Wind Harmer
0.235
3146843MT LREL
Solar/Wind Harmer
0.235
316017AA1-139 ULT1
Solar/Wind Helper
0.649
3142946ENON
Solar/Wind Helper
0.013
316487AF1-042 GEN
Solar/Wind Helper
0.13
3146386ELIZ CT
Solar/Wind Helper
0.129
316431W1029_GEN1
Solar/Wind Helper
0.474
316433W1029_GEN2
Solar/Wind Helper
0.474
3152661PLYWOOD A
50/50
0.688
24684405SMG2
50/50
0.859
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
3.259
316236AE1-162_GEN
Solar/Wind Helper
0.199
3145506HICKORY
Solar/Wind Helper
0.589
3145506HICKORY
Solar/Wind Helper
0.353
3145506HICKORY
Solar/Wind Helper
0.088
316339AD2-160 GEN
Solar/Wind Helper
0.545
316033AB2-134 GEN
Solar/Wind Helper
0.492
3137176SLIGO L2192
Solar/Wind Helper
0.558
3130086AYDLETT
Solar/Wind Helper
0.554
961601AG1-000A GEN
Solar/Wind Harmer
4.52
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
3146776BUCKING
Solar/Wind Helper
0.069
315773AC2-141 GEN
Solar/Wind Helper
3.566
3144536CHRHLND
Solar/Wind Helper
0.023
316313AB2-026
Solar/Wind Helper
0.209
316156AD2-030 GEN
Solar/Wind Helper
0.202
316484AD2-074 GEN
Solar/Wind Helper
0.249
316320Y1-086
Solar/Wind Helper
0.057
316435W1029_GEN3
Solar/Wind Helper
0.474
3146516WINFALL
Solar/Wind Helper
0.115
970581AG2-369 GEN
Solar/Wind Harmer
6.553
270069AE2-166 C O1
Solar/Wind Harmer
0.003
971981AH1-535 GEN
Solar/Wind Harmer
2.189
3143316POE
Solar/Wind Helper
0.623
316369SG1_INVT
Solar/Wind Helper
0.688
319010AE1-072 C
Solar/Wind Helper
1.59
3141873WAN 176
Solar/Wind Helper
0.027
315662AE1-191 GEN
Solar/Wind Helper
0.718
3143873LANEXA
Solar/Wind Helper
0.08
3138133OCRAN
Solar/Wind Helper
0.04
3146486SUNBURY
Solar/Wind Helper
0.126
3146486SUNBURY
Solar/Wind Helper
0.126
316321Z2-027
Solar/Wind Helper
0.189
3145176PASQUOTANK
Solar/Wind Helper
0.077
316118AC1-105 GEN
Solar/Wind Harmer
0.79
970085AG2-068 GEN
Solar/Wind Harmer
7.62
316132AB2-190 GEN1
Solar/Wind Helper
0.811
316305AF2-043 C
Solar/Wind Helper
0.186
316233AE1-074 FULL
Solar/Wind Helper
0.207
957601AF2-054 GEN
Solar/Wind Helper
0.179
315666AE1-190 GEN
Solar/Wind Helper
0.179
3141813NORNECK
Solar/Wind Helper
0.125
316223AC1-118
Solar/Wind Helper
0.18
24684305SMG1
50/50
0.311
962561AG1-105 GEN
Solar/Wind Harmer
9.772
270013AE1-250 PV
Solar/Wind Harmer
0.004
316263AC1-034 GEN
Solar/Wind Harmer
2.401
316316AC1-027 C
Solar/Wind Helper
0.237
316185AD1-033 GEN
Solar/Wind Helper
0.703
315697AD1-025 GEN
Solar/Wind Helper
1.636
3143526WINTERP
Solar/Wind Helper
0.705
316075AC2-137 C
Solar/Wind Helper
0.197
3144356SAPONY
Solar/Wind Helper
0.229
316077AC2-138 C
Solar/Wind Helper
0.118
316468AD1-105 GEN
Solar/Wind Helper
0.556
NYPJM->LTFIMP_NY
CLTF
0.69
LGEELTFEXP_LGEE->PJM
CLTF
2.05
WECLTFEXP_WEC->PJM
CLTF
1.087
AG2-052LTFEXP_AG2-052->PJM
LTF
0.061
AH1-155LTFEXP_AH1-155->PJM
LTF
0.092
LAGNLTFEXP_LAGN->PJM
CLTF
9.406
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.599
TVALTFEXP_TVA->PJM
CLTF
4.709
CPLELTFEXP_CPLE->PJM
CLTF
11.262
CBM West 2LTFEXP_CBM-W2->PJM
CBM
52.898
CBM West 1LTFEXP_CBM-W1->PJM
CBM
39.537
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.517
MECLTFEXP_MEC->PJM
CLTF
5.393
SIGELTFEXP_SIGE->PJM
CLTF
0.165

Details for 6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 570_SRT-A-2


Base Case Flowgate

Area:DVP
Facility Description:
6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.35 %
Rating:814.98 MVA
Rating Type:B
MVA to Mitigate:825.97
MW Contribution:1.36
Bus #Bus NameTypeMW Contribution
970401AG2-262 GEN
Solar/Wind Harmer
1.371
3147312GRETNA
Solar/Wind Harmer
0.105
3146802CHATHAM
Solar/Wind Harmer
0.098
316248AF1-058 C
Solar/Wind Harmer
0.003
960061AF2-297 GEN
Solar/Wind Harmer
16.056
971683AH1-343 GEN
Solar/Wind Harmer
12.232
24728405LEESVG
50/50
0.138
316283AC2-100 C
Solar/Wind Harmer
0.524
941821AE2-187 GEN
Solar/Wind Harmer
4.19
270197AD1-017 GEN1
Solar/Wind Harmer
0.768
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
270336AE1-100 GEN
Solar/Wind Harmer
0.003
971367AH1-164 GEN
Solar/Wind Harmer
1.359
971623AH1-311 GEN
Solar/Wind Harmer
0.126
316478AD1-087 GEN
Solar/Wind Helper
3.067
316486AD2-202 GEN
Solar/Wind Helper
0.898
3145336SMITFLD
Solar/Wind Helper
0.059
3146456SLIGO L269
Solar/Wind Helper
0.14
3142946ENON
Solar/Wind Helper
0.045
316473AC1-191 GEN
Solar/Wind Helper
0.73
971629AH1-314 GEN
50/50
13.606
24728405LEESVG
50/50
0.138
970481AG2-311 GEN
50/50
4.609
316003AC1-222 GEN
Solar/Wind Harmer
0.009
3147123OTTER R
Solar/Wind Harmer
0.091
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
270030AE2-140 GEN
Solar/Wind Harmer
10.43
316359AB2-059 GEN
Solar/Wind Harmer
0.227
3142053HEARTS
Solar/Wind Harmer
0.111
316294AC1-161 GEN
Solar/Wind Helper
3.03
316375AC2-012 GEN
Solar/Wind Helper
0.398
3145336SMITFLD
Solar/Wind Helper
0.592
3146456SLIGO L269
Solar/Wind Helper
0.14
316336AC2-165 C
Solar/Wind Helper
0.738
3142433PROV 92
Solar/Wind Helper
0.535
3141766HARMONY
Solar/Wind Helper
0.027
3142416OLDCHRC
Solar/Wind Helper
0.323
3142416OLDCHRC
Solar/Wind Helper
0.124
3147173SINAI
Solar/Wind Harmer
0.376
3147243WELCO
Solar/Wind Harmer
0.235
970165AG2-112 GEN
Solar/Wind Harmer
2.174
970163AG2-111 GEN
Solar/Wind Harmer
2.074
316349AD2-085 GEN
Solar/Wind Helper
0.625
316059AD1-063 C
Solar/Wind Helper
0.134
3141783LANCAST
Solar/Wind Helper
0.079
3141783LANCAST
Solar/Wind Helper
0.053
313526AB2-022
Solar/Wind Helper
0.196
24684605SMG4
50/50
0.864
24288905REUSENS
50/50
0.013
270018AE2-047 C O1
Solar/Wind Harmer
0.002
970417AG2-272 GEN
50/50
1.905
970087AG2-069 GEN
Solar/Wind Harmer
11.429
970223AG2-152 GEN
Solar/Wind Harmer
9.459
316049AB1-081 GEN
Solar/Wind Harmer
0.362
3146926FARMVIL
Solar/Wind Helper
0.143
316381AD1-082 GEN
Solar/Wind Helper
0.744
316388AE2-253 GEN
Solar/Wind Helper
0.545
316458AB2-190 GEN2
Solar/Wind Helper
0.811
316159AE1-175 C
Solar/Wind Helper
0.214
3143226MDLTHAN
Solar/Wind Helper
0.138
316246AF1-032 C
Solar/Wind Helper
0.158
3142543TWELFTH
Solar/Wind Helper
0.013
3138133OCRAN
Solar/Wind Helper
0.079
3147312GRETNA
Solar/Wind Harmer
0.026
942461AE2-259 GEN
Solar/Wind Helper
1.116
315839AE2-212 C
Solar/Wind Helper
0.201
316258AE1-075 C
Solar/Wind Helper
0.188
970865AG2-541 GEN
Solar/Wind Harmer
10.789
316123AC1-075 GEN
Solar/Wind Harmer
0.367
957831AF2-077 GEN
Solar/Wind Helper
0.188
3141913WHIT STONE
Solar/Wind Helper
0.132
316315AB2-025 C
Solar/Wind Helper
0.195
316312AB1-027
Solar/Wind Helper
0.236
3151561HALLBR1
50/50
0.377
24684705SMG5
50/50
0.331
941801AE2-185 GEN
Solar/Wind Harmer
4.19
270173AC1-122 GEN
Solar/Wind Harmer
0.218
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.05
3146776BUCKING
Solar/Wind Helper
0.077
3141726DUNNSVL
Solar/Wind Helper
0.503
316337AD2-073 GEN
Solar/Wind Helper
0.184
3146516WINFALL
Solar/Wind Helper
0.371
3146516WINFALL
Solar/Wind Helper
0.115
24684505SMG3
50/50
0.531
942751AE2-291 GEN
Solar/Wind Harmer
13.103
964791AG1-342 GEN
Solar/Wind Harmer
4.488
961601AG1-000A GEN
Solar/Wind Harmer
1.13
3146776BUCKING
Solar/Wind Helper
0.769
3146776BUCKING
Solar/Wind Helper
0.062
316036AC1-147 C
Solar/Wind Helper
0.231
3142956BIRDNECK
Solar/Wind Helper
0.101
316240AF1-291 C
Solar/Wind Helper
0.194
316018AA1-139 ULT2
Solar/Wind Helper
0.611
966871AG1-558 GEN
Solar/Wind Helper
0.161
3146516WINFALL
Solar/Wind Helper
0.115
3146516WINFALL
Solar/Wind Helper
0.115
3146516WINFALL
Solar/Wind Helper
0.115
316222AC1-221 GEN
Solar/Wind Harmer
1.137
3146843MT LREL
Solar/Wind Harmer
0.235
3146843MT LREL
Solar/Wind Harmer
0.235
316017AA1-139 ULT1
Solar/Wind Helper
0.649
3142946ENON
Solar/Wind Helper
0.013
316487AF1-042 GEN
Solar/Wind Helper
0.13
3146386ELIZ CT
Solar/Wind Helper
0.129
316431W1029_GEN1
Solar/Wind Helper
0.474
316433W1029_GEN2
Solar/Wind Helper
0.474
3152661PLYWOOD A
50/50
0.688
24684405SMG2
50/50
0.859
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
3.259
316236AE1-162_GEN
Solar/Wind Helper
0.199
3145506HICKORY
Solar/Wind Helper
0.589
3145506HICKORY
Solar/Wind Helper
0.353
3145506HICKORY
Solar/Wind Helper
0.088
316339AD2-160 GEN
Solar/Wind Helper
0.545
316033AB2-134 GEN
Solar/Wind Helper
0.492
3137176SLIGO L2192
Solar/Wind Helper
0.558
3130086AYDLETT
Solar/Wind Helper
0.554
961601AG1-000A GEN
Solar/Wind Harmer
4.52
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
3146776BUCKING
Solar/Wind Helper
0.069
315773AC2-141 GEN
Solar/Wind Helper
3.566
3144536CHRHLND
Solar/Wind Helper
0.023
316313AB2-026
Solar/Wind Helper
0.209
316156AD2-030 GEN
Solar/Wind Helper
0.202
316484AD2-074 GEN
Solar/Wind Helper
0.249
316320Y1-086
Solar/Wind Helper
0.057
316435W1029_GEN3
Solar/Wind Helper
0.474
3146516WINFALL
Solar/Wind Helper
0.115
970581AG2-369 GEN
Solar/Wind Harmer
6.553
270069AE2-166 C O1
Solar/Wind Harmer
0.003
971981AH1-535 GEN
Solar/Wind Harmer
2.189
3143316POE
Solar/Wind Helper
0.623
316369SG1_INVT
Solar/Wind Helper
0.688
319010AE1-072 C
Solar/Wind Helper
1.59
3141873WAN 176
Solar/Wind Helper
0.027
315662AE1-191 GEN
Solar/Wind Helper
0.718
3143873LANEXA
Solar/Wind Helper
0.08
3138133OCRAN
Solar/Wind Helper
0.04
3146486SUNBURY
Solar/Wind Helper
0.126
3146486SUNBURY
Solar/Wind Helper
0.126
316321Z2-027
Solar/Wind Helper
0.189
3145176PASQUOTANK
Solar/Wind Helper
0.077
316118AC1-105 GEN
Solar/Wind Harmer
0.79
970085AG2-068 GEN
Solar/Wind Harmer
7.62
316132AB2-190 GEN1
Solar/Wind Helper
0.811
316305AF2-043 C
Solar/Wind Helper
0.186
316233AE1-074 FULL
Solar/Wind Helper
0.207
957601AF2-054 GEN
Solar/Wind Helper
0.179
315666AE1-190 GEN
Solar/Wind Helper
0.179
3141813NORNECK
Solar/Wind Helper
0.125
316223AC1-118
Solar/Wind Helper
0.18
3146926FARMVIL
Solar/Wind Helper
0.143
3144873MCLAUGH
Solar/Wind Helper
0.004
316382AG1-145 C
Solar/Wind Helper
0.19
316405AF2-144 C
Solar/Wind Helper
0.157
316280AD1-041 GEN
Solar/Wind Helper
0.449
316404AE1-155 C
Solar/Wind Helper
1.078
3141906WESTMOR
Solar/Wind Helper
0.047
24684305SMG1
50/50
0.311
962561AG1-105 GEN
Solar/Wind Harmer
9.772
270013AE1-250 PV
Solar/Wind Harmer
0.004
316263AC1-034 GEN
Solar/Wind Harmer
2.401
316316AC1-027 C
Solar/Wind Helper
0.237
316185AD1-033 GEN
Solar/Wind Helper
0.703
315697AD1-025 GEN
Solar/Wind Helper
1.636
3143526WINTERP
Solar/Wind Helper
0.705
316075AC2-137 C
Solar/Wind Helper
0.197
3144356SAPONY
Solar/Wind Helper
0.229
316077AC2-138 C
Solar/Wind Helper
0.118
316468AD1-105 GEN
Solar/Wind Helper
0.556
270016AE1-250 BESS
Solar/Wind Harmer
0.004
315687AD1-152 GEN
Solar/Wind Helper
4.927
316322AB2-045
Solar/Wind Helper
0.214
316072AD1-144
Solar/Wind Helper
0.16
3143526WINTERP
Solar/Wind Helper
0.705
964211AG1-282 GEN
Solar/Wind Helper
0.169
NYPJM->LTFIMP_NY
CLTF
0.69
LGEELTFEXP_LGEE->PJM
CLTF
2.05
WECLTFEXP_WEC->PJM
CLTF
1.087
AG2-052LTFEXP_AG2-052->PJM
LTF
0.061
AH1-155LTFEXP_AH1-155->PJM
LTF
0.092
LAGNLTFEXP_LAGN->PJM
CLTF
9.406
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.599
TVALTFEXP_TVA->PJM
CLTF
4.709
CPLELTFEXP_CPLE->PJM
CLTF
11.262
CBM West 2LTFEXP_CBM-W2->PJM
CBM
52.898
CBM West 1LTFEXP_CBM-W1->PJM
CBM
39.537
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.517
MECLTFEXP_MEC->PJM
CLTF
5.393
SIGELTFEXP_SIGE->PJM
CLTF
0.165

Details for 8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 555_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 555_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:112.33 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3617.39
MW Contribution:3.33
Bus #Bus NameTypeMW Contribution
270205AE1-176
50/50
0.004
970479AG2-310 GEN
50/50
14.12
971367AH1-164 GEN
Solar/Wind Harmer
3.331
941821AE2-187 GEN
Solar/Wind Harmer
5.17
270197AD1-017 GEN1
Solar/Wind Harmer
0.974
270336AE1-100 GEN
Solar/Wind Harmer
0.004
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
316499AE2-029_GEN
Solar/Wind Helper
1.225
943031AE2-326 GEN
Solar/Wind Harmer
4.43
3147123OTTER R
Solar/Wind Harmer
0.09
3151861LOWMORA
50/50
3.918
24734805WLF1G4
Adder
4.975
3152061BATH 6F
50/50
16.44
970823AG2-518 GEN
50/50
5.734
958121AF2-106 GEN
Solar/Wind Harmer
0.001
247619Y1-049
Adder
0.574
971331AH1-145 GEN
Solar/Wind Harmer
12.171
270346AE1-212 GEN
Solar/Wind Harmer
5.915
970223AG2-152 GEN
Solar/Wind Harmer
8.195
3152041BATH 4D
50/50
16.352
3151881LOWMORC
50/50
4.046
3151881LOWMORC
50/50
3.982
966391AG1-508 GEN
Solar/Wind Harmer
1.299
270069AE2-166 C O1
Solar/Wind Harmer
0.005
24734705WLF1G3
Adder
4.975
24734905WLF1G5
Adder
4.975
3148013FISHERV
Solar/Wind Helper
0.175
24290605CLAY-1
50/50
0.172
24290605CLAY-1
50/50
0.172
316217AC1-145 GEN
Solar/Wind Harmer
0.002
24290705CLAY-2
50/50
0.172
24290705CLAY-2
50/50
0.172
971277AH1-098 GEN
Solar/Wind Harmer
3.383
24728205BUCHG1
Adder
4.101
962751AG1-124 GEN
Solar/Wind Harmer
9.115
3147312GRETNA
Solar/Wind Harmer
0.129
3146802CHATHAM
Solar/Wind Harmer
0.121
270016AE1-250 BESS
Solar/Wind Harmer
0.004
3147983MERCK5
Solar/Wind Helper
0.146
3152051BATH 5E
50/50
16.369
3151861LOWMORA
50/50
4.078
3137383CUSHAW
50/50
0.078
971329AH1-144 GEN
Solar/Wind Harmer
7.668
958131AF2-107 GEN
Solar/Wind Harmer
3.843
316197AC1-042 GEN
Solar/Wind Harmer
0.002
942671AE2-283 GEN
Solar/Wind Harmer
4.021
3132123MT JACKSON
Solar/Wind Helper
1.116
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
270030AE2-140 GEN
Solar/Wind Harmer
14.108
960911AF2-382 GEN
Solar/Wind Harmer
4.593
3147312GRETNA
Solar/Wind Harmer
0.032
23583801GRNGAP
Solar/Wind Helper
3.885
237061AD1-155 GEN
Solar/Wind Helper
0.042
270173AC1-122 GEN
Solar/Wind Harmer
0.472
941801AE2-185 GEN
Solar/Wind Harmer
5.17
3152011BATH 1A
50/50
16.383
3152021BATH 2B
50/50
16.383
3152031BATH 3C
50/50
16.378
3148463FAIRFLD
Solar/Wind Harmer
0.358
3138266HYDRAULIC
Solar/Wind Helper
0.012
3138266HYDRAULIC
Solar/Wind Helper
0.007
24288905REUSENS
50/50
0.04
315616AA1-038_C
Solar/Wind Harmer
0.003
270018AE2-047 C O1
Solar/Wind Harmer
0.003
24728305BUCHG2
Adder
4.101
3148013FISHERV
Solar/Wind Helper
0.304
270583AD2-179 GEN
Solar/Wind Harmer
9.708
971543AH1-269 GEN
50/50
8.257
971313AH1-133 GEN
Solar/Wind Harmer
6.761
3148133STUARTS
Solar/Wind Helper
0.182
270013AE1-250 PV
Solar/Wind Harmer
0.004
NYPJM->LTFIMP_NY
CLTF
2.909
LGEELTFEXP_LGEE->PJM
CLTF
3.588
WECLTFEXP_WEC->PJM
CLTF
1.753
AG2-052LTFEXP_AG2-052->PJM
LTF
0.104
AH1-155LTFEXP_AH1-155->PJM
LTF
0.155
LAGNLTFEXP_LAGN->PJM
CLTF
11.387
CBM South 2LTFEXP_CBM-S2->PJM
CBM
14.911
TVALTFEXP_TVA->PJM
CLTF
6.03
CPLELTFEXP_CPLE->PJM
CLTF
3.393
CBM West 2LTFEXP_CBM-W2->PJM
CBM
71.784
CBM West 1LTFEXP_CBM-W1->PJM
CBM
62.503
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.099
MECLTFEXP_MEC->PJM
CLTF
8.174
SIGELTFEXP_SIGE->PJM
CLTF
0.27

Details for 8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2168-555_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2168-555_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:105.49 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4156.4
MW Contribution:5.35
Bus #Bus NameTypeMW Contribution
270205AE1-176
50/50
0.005
970479AG2-310 GEN
50/50
15.892
971367AH1-164 GEN
Solar/Wind Harmer
5.352
941821AE2-187 GEN
Solar/Wind Harmer
7.544
270197AD1-017 GEN1
Solar/Wind Harmer
1.927
270336AE1-100 GEN
Solar/Wind Harmer
2.02
943811AF1-049 GEN
Solar/Wind Harmer
4.147
24735205WLF2G2
Adder
5.48
316499AE2-029_GEN
Solar/Wind Helper
1.577
316095T157 G97
Solar/Wind Helper
1.082
3152051BATH 5E
50/50
17.355
3137383CUSHAW
50/50
0.134
3151861LOWMORA
50/50
7.039
971329AH1-144 GEN
Solar/Wind Harmer
17.696
958131AF2-107 GEN
Solar/Wind Harmer
5.403
971403AH1-188 GEN
Solar/Wind Harmer
12.187
3132273ORANGE
Solar/Wind Helper
0.051
316170AC1-121 GEN2
Solar/Wind Helper
0.36
24288905REUSENS
50/50
0.045
315616AA1-038_C
Solar/Wind Harmer
14.233
270018AE2-047 C O1
Solar/Wind Harmer
1.338
24728305BUCHG2
Adder
4.634
3148013FISHERV
Solar/Wind Helper
0.457
3147666LOUISA
Solar/Wind Helper
0.577
238147AE2-230_GEN1
Solar/Wind Helper
0.401
943031AE2-326 GEN
Solar/Wind Harmer
4.99
3147123OTTER R
Solar/Wind Harmer
-0.011
270574AD1-017 GEN2
Solar/Wind Harmer
6.414
270030AE2-140 GEN
Solar/Wind Harmer
22.569
960911AF2-382 GEN
Solar/Wind Harmer
7.443
316192AB2-158 GEN
Solar/Wind Helper
1.696
316097T157 G90
Solar/Wind Helper
1.082
316336AC2-165 C
Solar/Wind Helper
1.208
3152061BATH 6F
50/50
17.43
970823AG2-518 GEN
50/50
6.455
958121AF2-106 GEN
Solar/Wind Harmer
7.115
247619Y1-049
Adder
0.646
971331AH1-145 GEN
Solar/Wind Harmer
13.718
270346AE1-212 GEN
Solar/Wind Harmer
9.778
970223AG2-152 GEN
Solar/Wind Harmer
12.909
971461AH1-227 GEN
Solar/Wind Harmer
4.678
3147666LOUISA
Solar/Wind Helper
1.004
316254AC1-120 GEN1
Solar/Wind Helper
1.079
24290605CLAY-1
50/50
0.194
24290605CLAY-1
50/50
0.194
316217AC1-145 GEN
Solar/Wind Harmer
3.265
316197AC1-042 GEN
Solar/Wind Harmer
2.475
942671AE2-283 GEN
Solar/Wind Harmer
6.664
3132123MT JACKSON
Solar/Wind Helper
1.31
966001AG1-469 GEN
Solar/Wind Helper
0.292
962751AG1-124 GEN
Solar/Wind Harmer
14.726
3147312GRETNA
Solar/Wind Harmer
-0.016
3146802CHATHAM
Solar/Wind Harmer
-0.015
270016AE1-250 BESS
Solar/Wind Harmer
2.411
3147983MERCK5
Solar/Wind Helper
0.183
3152011BATH 1A
50/50
17.37
3152021BATH 2B
50/50
17.37
3152031BATH 3C
50/50
17.364
3148463FAIRFLD
Solar/Wind Harmer
-0.069
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.011
3151861LOWMORA
50/50
6.765
24734805WLF1G4
Adder
5.613
24735105WLF2G1
Adder
5.48
23546401DTGZ2-030
Solar/Wind Helper
0.075
238152AF2-075_GEN
Solar/Wind Helper
0.572
316164AC1-076 GEN
Solar/Wind Helper
1.095
971543AH1-269 GEN
50/50
9.298
971313AH1-133 GEN
Solar/Wind Harmer
10.943
270132AB1-180 C
Adder
0.114
3148133STUARTS
Solar/Wind Helper
0.274
3152041BATH 4D
50/50
17.337
3151881LOWMORC
50/50
6.984
24290705CLAY-2
50/50
0.194
24290705CLAY-2
50/50
0.194
971277AH1-098 GEN
Solar/Wind Harmer
5.461
24728205BUCHG1
Adder
4.634
270013AE1-250 PV
Solar/Wind Harmer
2.411
315821AE2-092 GEN
Solar/Wind Helper
2.895
3147312GRETNA
Solar/Wind Harmer
-0.004
971687AH1-348 GEN
Solar/Wind Harmer
0.906
237061AD1-155 GEN
Solar/Wind Helper
0.047
23583801GRNGAP
Solar/Wind Helper
4.125
238149AF1-291A_GEN
Solar/Wind Helper
0.114
270583AD2-179 GEN
Solar/Wind Harmer
15.671
270214AC2-123 GEN
Solar/Wind Harmer
3.17
971225AH1-072 GEN
Solar/Wind Harmer
1.824
971227AH1-073 GEN
Solar/Wind Harmer
1.824
315651AD1-115 GEN
Solar/Wind Helper
0.781
270173AC1-122 GEN
Solar/Wind Harmer
2.55
941801AE2-185 GEN
Solar/Wind Harmer
7.544
970913AG2-568 GEN
Solar/Wind Harmer
7.285
238148AE2-230_GEN2
Solar/Wind Helper
0.402
3151881LOWMORC
50/50
6.875
966391AG1-508 GEN
Solar/Wind Harmer
4.68
270069AE2-166 C O1
Solar/Wind Harmer
3.325
24734705WLF1G3
Adder
5.613
24734905WLF1G5
Adder
5.613
3148013FISHERV
Solar/Wind Helper
0.263
NYPJM->LTFIMP_NY
CLTF
3.2
LGEELTFEXP_LGEE->PJM
CLTF
4.095
WECLTFEXP_WEC->PJM
CLTF
2.007
AG2-052LTFEXP_AG2-052->PJM
LTF
0.119
AH1-155LTFEXP_AH1-155->PJM
LTF
0.178
LAGNLTFEXP_LAGN->PJM
CLTF
12.827
CBM South 2LTFEXP_CBM-S2->PJM
CBM
16.289
TVALTFEXP_TVA->PJM
CLTF
6.791
CPLELTFEXP_CPLE->PJM
CLTF
3.547
CBM West 2LTFEXP_CBM-W2->PJM
CBM
81.312
CBM West 1LTFEXP_CBM-W1->PJM
CBM
71.759
CBM South 1LTFEXP_CBM-S1->PJM
CBM
24.94
MECLTFEXP_MEC->PJM
CLTF
9.322
SIGELTFEXP_SIGE->PJM
CLTF
0.308

Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:173.01 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:7041.78
MW Contribution:2.4
Bus #Bus NameTypeMW Contribution
3151161SURRY 1
50/50
14.066
970293AG2-193 GEN
Solar/Wind Harmer
4.092
3150921YORKTN3
Adder
9.356
315773AC2-141 GEN
Solar/Wind Harmer
13.538
3144536CHRHLND
Solar/Wind Harmer
0.054
944581AF1-123 GEN
Solar/Wind Harmer
81.792
970659AG2-427 GEN
Solar/Wind Harmer
3.767
316320Y1-086
Solar/Wind Harmer
0.002
316435W1029_GEN3
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.349
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316156AD2-030 GEN
Solar/Wind Harmer
0.254
315614AA2-178 GEN
Solar/Wind Harmer
1.889
971157AH1-035 GEN
Solar/Wind Harmer
3.886
3145893MURPHYS
Solar/Wind Harmer
0.528
3145893MURPHYS
Solar/Wind Harmer
0.316
957521AF2-046 GEN
Solar/Wind Harmer
23.434
316463AE2-346 GEN
Solar/Wind Harmer
0.267
316140AB2-099
Solar/Wind Harmer
0.111
3146263WOODLND
Solar/Wind Harmer
0.306
316382AG1-145 C
Solar/Wind Harmer
0.003
3143096IRON208
Adder
1.57
3143096IRON208
Adder
1.539
970129AG2-093 GEN
Solar/Wind Harmer
22.266
961611AG1-000B GEN
Solar/Wind Harmer
9.778
3151171GRAVELC
Adder
5.122
3150861SPRUNCD
Adder
1.682
3144873MCLAUGH
Solar/Wind Harmer
0.009
965281AG1-393 GEN
Solar/Wind Harmer
3.845
970661AG2-428 GEN
Solar/Wind Harmer
7.524
3141843SHACKLE
Adder
1.778
3146626S HERTFORD
Solar/Wind Harmer
0.346
316280AD1-041 GEN
Solar/Wind Harmer
0.007
3141873WAN 176
Solar/Wind Harmer
6.098
315737AD1-076 GEN
Solar/Wind Harmer
4.152
3156081AA2-088 GEN
Solar/Wind Harmer
0.008
961681AG1-008 GEN
Solar/Wind Harmer
23.434
962971AG1-146 GEN
Solar/Wind Harmer
5.016
962331AG1-082 GEN
Solar/Wind Harmer
3.322
970917AG2-570 GEN
Solar/Wind Harmer
27.198
3142666NORTHAMPTON
Solar/Wind Harmer
0.302
313506AB2-031 GEN
Solar/Wind Harmer
0.929
316404AE1-155 C
Solar/Wind Harmer
0.067
3145933PARMELE
Solar/Wind Harmer
0.292
966801AG1-551 GEN
Solar/Wind Harmer
3.408
316405AF2-144 C
Solar/Wind Harmer
0.002
3146233WITAKRS
Solar/Wind Harmer
1.382
3146233WITAKRS
Solar/Wind Harmer
0.187
315785AD2-033 C
Solar/Wind Harmer
2.125
970257AG2-171 GEN
Solar/Wind Harmer
8.336
963181AG1-167 GEN
Solar/Wind Harmer
1.024
3146926FARMVIL
Solar/Wind Harmer
0.147
3141906WESTMOR
Solar/Wind Harmer
0.083
270018AE2-047 C O1
Solar/Wind Harmer
0.003
3148013FISHERV
Solar/Wind Harmer
0.154
315616AA1-038_C
Solar/Wind Harmer
0.001
971645AH1-323 GEN
50/50
34.852
3142416OLDCHRC
Solar/Wind Harmer
3.771
3142946ENON
Solar/Wind Harmer
0.127
970133AG2-095 GEN
Solar/Wind Harmer
3.544
3151221GRAVEL6
Adder
26.624
3145336SMITFLD
Solar/Wind Harmer
0.146
3142433PROV 92
Adder
0.696
316044AC1-158 PL1
Solar/Wind Helper
2.503
316450AC1-158 RIC
Solar/Wind Helper
0.667
3147666LOUISA
Solar/Wind Helper
0.737
235067AD1-061 GEN
Solar/Wind Helper
0.424
234015AF2-250 C
Solar/Wind Helper
0.037
316159AE1-175 C
Solar/Wind Harmer
0.327
3143096IRON208
Adder
1.57
3138126ROCKLANDING
Solar/Wind Harmer
0.171
3142543TWELFTH
Solar/Wind Harmer
0.035
970129AG2-093 GEN
Solar/Wind Harmer
10.478
316458AB2-190 GEN2
Solar/Wind Harmer
1.976
971069AG2-661 GEN
Solar/Wind Harmer
6.539
971647AH1-324 GEN
Solar/Wind Harmer
15.662
961611AG1-000B GEN
Solar/Wind Harmer
19.23
3151171GRAVELC
Adder
3.895
3150981CHESPKA
Adder
4.531
316388AE2-253 GEN
Solar/Wind Harmer
1.126
316246AF1-032 C
Solar/Wind Harmer
0.161
316381AD1-082 GEN
Solar/Wind Harmer
0.371
970661AG2-428 GEN
Solar/Wind Harmer
35.374
3141843SHACKLE
Adder
1.778
3143226MDLTHAN
Solar/Wind Harmer
0.343
3130156CHOWAN
Solar/Wind Harmer
0.338
3138133OCRAN
Solar/Wind Harmer
0.198
971163AH1-040 GEN
Solar/Wind Harmer
26.412
970087AG2-069 GEN
Solar/Wind Harmer
24.391
316190AA2-174 GEN
Solar/Wind Harmer
0.001
3146293MARTNCO
Solar/Wind Harmer
0.271
944631AF1-128 GEN
Adder
179.515
971317AH1-138 GEN
Solar/Wind Harmer
2.773
944591AF1-124 GEN
Solar/Wind Harmer
82.083
315671AE2-027_GEN
Solar/Wind Harmer
23.135
316072AD1-144
Solar/Wind Harmer
0.13
3143526WINTERP
Solar/Wind Harmer
1.841
939411AE1-173 GEN
Solar/Wind Harmer
148.397
940641AE2-051 GEN
Solar/Wind Harmer
27.456
972277AH1-723 GEN
Adder
191.941
971547AH1-271 GEN
Solar/Wind Harmer
6.801
3145823KELFORD
Solar/Wind Harmer
0.303
960081AF2-299 GEN
Solar/Wind Harmer
2.907
962571AG1-106 GEN
Solar/Wind Harmer
4.28
3145796HORNRTN
Solar/Wind Harmer
0.978
3145796HORNRTN
Solar/Wind Harmer
0.296
3145783HORNRTN
Solar/Wind Harmer
0.296
316212AC1-099_GEN
Solar/Wind Harmer
1.505
3143336POWHATN
Solar/Wind Harmer
5.15
3145746EVERETS
Solar/Wind Harmer
0.286
3145746EVERETS
Solar/Wind Harmer
0.286
316129AC1-054 GEN
Solar/Wind Harmer
1.053
971065AG2-659 GEN
Solar/Wind Harmer
11.883
3150351NORNECKC2
Adder
2.758
315687AD1-152 GEN
Solar/Wind Harmer
0.009
316237AB2-079_GEN
Solar/Wind Harmer
0.002
3144293JTRSVLE
Adder
0.815
970401AG2-262 GEN
Solar/Wind Harmer
1.493
316322AB2-045
Solar/Wind Harmer
0.002
972003AH1-546 GEN
Solar/Wind Harmer
9.023
3147623JAMES R
Solar/Wind Harmer
0.462
270016AE1-250 BESS
Solar/Wind Harmer
0.005
3147312GRETNA
Solar/Wind Harmer
0.127
3146802CHATHAM
Solar/Wind Harmer
0.119
962751AG1-124 GEN
Solar/Wind Harmer
6.367
233930AB2-032 GEN
Solar/Wind Helper
0.368
233954AC2-188 GEN
Solar/Wind Helper
0.225
230511AF1-262
Solar/Wind Helper
0.014
230434AG1-499 GEN
Solar/Wind Helper
0.221
219258KINSLEYDEP C
Solar/Wind Helper
0.074
219907AC1-030 C
Solar/Wind Helper
0.032
3152331SURRY 2
50/50
15.859
3142416OLDCHRC
Solar/Wind Harmer
1.011
3142416OLDCHRC
Solar/Wind Harmer
0.387
316294AC1-161 GEN
Solar/Wind Harmer
6.422
3145336SMITFLD
Solar/Wind Harmer
1.459
316375AC2-012 GEN
Solar/Wind Harmer
0.009
3142433PROV 92
Solar/Wind Harmer
1.432
3142433PROV 92
Adder
0.696
3142433PROV 92
Adder
0.696
3146456SLIGO L269
Solar/Wind Harmer
0.358
3141766HARMONY
Solar/Wind Harmer
0.07
971777AH1-397 GEN
Solar/Wind Harmer
0.918
3145663CRESWEL
Solar/Wind Harmer
0.924
3146206CASHIE
Solar/Wind Harmer
0.318
3146173TUNIS
Solar/Wind Harmer
0.313
316023GEN1_S
Solar/Wind Harmer
0.699
3145683EARLEYS
Solar/Wind Harmer
0.31
3145963POPLR C
Solar/Wind Harmer
0.306
316313AB2-026
Solar/Wind Harmer
0.183
316327AA2-057 GEN
Solar/Wind Harmer
0.423
961601AG1-000A GEN
Solar/Wind Harmer
19.24
3145543BTLEBRO
Solar/Wind Harmer
0.27
3145543BTLEBRO
Solar/Wind Harmer
0.27
3146776BUCKING
Solar/Wind Harmer
0.082
970221AG2-151 GEN
Solar/Wind Harmer
10.629
970737AG2-469 GEN
Solar/Wind Harmer
7.511
3151861LOWMORA
Adder
1.607
958131AF2-107 GEN
Solar/Wind Harmer
4.297
316170AC1-121 GEN2
Solar/Wind Helper
0.521
3132273ORANGE
Solar/Wind Helper
0.053
205917AD1-020 ES
Solar/Wind Helper
0.354
233918AB1-142 GEN
Solar/Wind Helper
0.486
233994AC2-023 GEN
Solar/Wind Helper
0.929
233997TMININ_4.2
Solar/Wind Helper
0.253
233971AC1-093 C
Solar/Wind Helper
0.346
228729W2-030 C
Solar/Wind Helper
0.106
316312AB1-027
Solar/Wind Harmer
0.696
971445AH1-216 GEN
Solar/Wind Harmer
25.708
971285AH1-108 GEN
Adder
2.752
3151081ELIZAR1
Adder
33.28
3151091ELIZAR2
Adder
32.702
3152611GOSPORTB
Adder
4.621
3152621GOSPORTC
Adder
3.922
3152601GOSPORTA
Adder
3.618
957871AF2-081 GEN
Solar/Wind Harmer
17.869
315833AF1-017_GEN
Solar/Wind Harmer
0.002
316314AB2-024 C
Solar/Wind Harmer
0.001
3141913WHIT STONE
Solar/Wind Harmer
0.333
316315AB2-025 C
Solar/Wind Harmer
0.269
941031AE2-094 GEN
Solar/Wind Harmer
60.194
970673AG2-436 GEN
Solar/Wind Harmer
68.642
970673AG2-436 GEN
Solar/Wind Harmer
45.761
970327AG2-215 GEN
Solar/Wind Harmer
10.069
3145796HORNRTN
Solar/Wind Harmer
0.948
3145796HORNRTN
Solar/Wind Harmer
0.119
3145746EVERETS
Solar/Wind Harmer
1.138
3145746EVERETS
Solar/Wind Harmer
0.286
3145746EVERETS
Solar/Wind Harmer
0.286
3145746EVERETS
Solar/Wind Harmer
0.286
3150681DARBY 2
50/50
29.012
316033AB2-134 GEN
Solar/Wind Harmer
0.022
316236AE1-162_GEN
Solar/Wind Harmer
0.003
3145506HICKORY
Solar/Wind Harmer
1.442
3145506HICKORY
Solar/Wind Harmer
0.865
3145506HICKORY
Solar/Wind Harmer
0.217
316339AD2-160 GEN
Solar/Wind Harmer
0.583
3137176SLIGO L2192
Solar/Wind Harmer
1.425
3130086AYDLETT
Solar/Wind Harmer
1.43
970657AG2-426 GEN
Solar/Wind Harmer
12.462
970657AG2-426 GEN
Solar/Wind Harmer
2.613
3146626S HERTFORD
Solar/Wind Harmer
0.346
3146626S HERTFORD
Solar/Wind Harmer
0.346
3142666NORTHAMPTON
Solar/Wind Harmer
0.302
3142666NORTHAMPTON
Solar/Wind Harmer
0.302
3142666NORTHAMPTON
Solar/Wind Harmer
0.302
3142666NORTHAMPTON
Solar/Wind Harmer
0.181
3145593CAROLNA
Solar/Wind Harmer
0.298
3145593CAROLNA
Solar/Wind Harmer
0.298
3145593CAROLNA
Solar/Wind Harmer
0.371
3145933PARMELE
Solar/Wind Harmer
0.585
3145933PARMELE
Solar/Wind Harmer
0.292
3150341NORNECKC1
Adder
2.897
3150341NORNECKC1
Adder
2.874
3145493TOT1
Solar/Wind Harmer
0.64
313527AB2-043 GEN
Solar/Wind Harmer
0.003
970301AG2-198 GEN
Solar/Wind Harmer
11.171
970323AG2-213 GEN
Solar/Wind Harmer
11.115
971775AH1-396 GEN
Solar/Wind Harmer
0.417
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.002
942671AE2-283 GEN
Solar/Wind Harmer
3.945
237006AB1-125 GEN
Solar/Wind Helper
0.12
23777901MDS_W4-102
Solar/Wind Helper
0.152
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
237002AB1-128_GEN
Solar/Wind Helper
0.384
232424Y1-079 C
Solar/Wind Helper
0.112
233970AC1-092 C
Solar/Wind Helper
0.338
230433AD2-135 GEN
Solar/Wind Helper
0.016
219921AF1-264
Solar/Wind Helper
0.049
315976AC1-164 GENA
Solar/Wind Harmer
40.142
316169AC1-164_GENC
Solar/Wind Harmer
34.679
315975AC1-164 GENB
Solar/Wind Harmer
1.188
3151201GRAVEL4
Adder
26.654
3151211GRAVEL5
Adder
26.317
3142433PROV 92
Adder
0.696
3142433PROV 92
Adder
0.696
316349AD2-085 GEN
Solar/Wind Harmer
0.243
316311AC2-079 GEN
Solar/Wind Harmer
10.187
315835AF2-110_GEN
Solar/Wind Harmer
2.43
313526AB2-022
Solar/Wind Harmer
0.192
3146396TANGLEW
Solar/Wind Harmer
0.971
316059AD1-063 C
Solar/Wind Harmer
0.002
315814AE2-033 C
Solar/Wind Harmer
26.26
3141783LANCAST
Solar/Wind Harmer
0.195
3141783LANCAST
Solar/Wind Harmer
0.13
3146206CASHIE
Solar/Wind Harmer
0.318
3145683EARLEYS
Solar/Wind Harmer
0.62
3145683EARLEYS
Solar/Wind Harmer
0.31
3145683EARLEYS
Solar/Wind Harmer
0.31
3146043SEABORD
Solar/Wind Harmer
0.307
316420AA1-050 GEN
Solar/Wind Harmer
0.009
316319Z2-044 C
Solar/Wind Harmer
0
961791AG1-021 GEN
Solar/Wind Harmer
2.457
3147173SINAI
Solar/Wind Harmer
0.246
3147243WELCO
Solar/Wind Harmer
0.154
970285AG2-188 GEN
Solar/Wind Harmer
18.408
971845AH1-439 GEN
Solar/Wind Harmer
10.428
970165AG2-112 GEN
Solar/Wind Harmer
1.683
970163AG2-111 GEN
Solar/Wind Harmer
1.606
3148463FAIRFLD
Solar/Wind Harmer
0.15
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
960921AF2-383 GEN
Solar/Wind Helper
0.352
205932AD2-116_GEN
Solar/Wind Helper
0.491
232432Z2-076 GEN
Solar/Wind Helper
0.065
234033AF1-007_GEN
Solar/Wind Helper
6.788
316132AB2-190 GEN1
Solar/Wind Harmer
1.976
972265AH1-717 GEN
Adder
28.433
3151191GRAVEL3
Adder
26.317
971167AH1-042 GEN
Solar/Wind Harmer
31.907
3138283WHITEMARSH
Solar/Wind Harmer
0.083
3146406KITTY HAWK
Solar/Wind Harmer
0.045
316305AF2-043 C
Solar/Wind Harmer
0.003
316233AE1-074 FULL
Solar/Wind Harmer
0.283
971283AH1-107 GEN
Solar/Wind Harmer
4.913
970189AG2-124 GEN
Solar/Wind Harmer
10.307
315666AE1-190 GEN
Solar/Wind Harmer
0.003
944011AF1-069 GEN
Solar/Wind Harmer
19.668
315732AD1-074 GEN1
Solar/Wind Harmer
1.854
315735AD1-075 GEN1
Solar/Wind Harmer
0.928
972193AH1-681 GEN
Adder
7.36
965291AG1-394 GEN
Solar/Wind Harmer
1.416
971967AH1-528 GEN
Solar/Wind Harmer
50.838
3145893MURPHYS
Solar/Wind Harmer
0.852
3145893MURPHYS
Solar/Wind Harmer
0.316
962981AG1-147 GEN
Solar/Wind Harmer
11.703
3145513AHOSKIE
Solar/Wind Harmer
0.651
3145513AHOSKIE
Solar/Wind Harmer
0.311
315607AA1-063A GEN
Solar/Wind Harmer
0.625
970085AG2-068 GEN
Solar/Wind Harmer
16.26
315652AC1-086 GEN
Solar/Wind Harmer
33.087
3137643SOCKMAN
Solar/Wind Harmer
1.194
316005AA1-067
Solar/Wind Harmer
0.307
3141813NORNECK
Solar/Wind Harmer
0.276
971443AH1-215 GEN
Solar/Wind Harmer
4.38
3144303KENBRDG
Solar/Wind Harmer
0.208
946301AF1-294 GEN
Solar/Wind Harmer
5.05
315657AE1-056 GEN
Solar/Wind Harmer
8.773
316118AC1-105 GEN
Solar/Wind Harmer
0.646
316223AC1-118
Solar/Wind Harmer
0.15
270494AE1-108_GEN
Solar/Wind Harmer
2.206
3151861LOWMORA
Adder
1.545
316164AC1-076 GEN
Solar/Wind Helper
1.845
3138216PACIFIC
Solar/Wind Helper
0.053
233935AB2-179 C
Solar/Wind Helper
1.229
232436AB1-176 C
Solar/Wind Helper
0.043
205956AE1-196_GEN
Solar/Wind Helper
0.491
233923SMA
Solar/Wind Helper
0.927
219914AD2-027 C
Solar/Wind Helper
0.11
970831AG2-522 GEN
Solar/Wind Harmer
12.024
957861AF2-080 GEN
Solar/Wind Harmer
12.104
3145573BETHELC
Solar/Wind Harmer
0.276
3145573BETHELC
Solar/Wind Harmer
0.276
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
970683AG2-441 GEN
Solar/Wind Harmer
17.21
970681AG2-440 GEN
Solar/Wind Harmer
13.768
970865AG2-541 GEN
Solar/Wind Harmer
7.734
316123AC1-075 GEN
Solar/Wind Harmer
0.284
971447AH1-217 GEN
Solar/Wind Harmer
5.953
3148133STUARTS
Solar/Wind Harmer
0.092
316411AF1-147_GEN1
Solar/Wind Helper
1.079
316415AF1-147_GEN2
Solar/Wind Helper
1.079
3141426STAFORD
Solar/Wind Helper
0.061
237085AD2-009_GEN
Solar/Wind Helper
1.388
228754AB1-001 C
Solar/Wind Helper
0.025
219272CLEANLIGHT C
Solar/Wind Helper
0.024
316075AC2-137 C
Solar/Wind Harmer
0.106
315697AD1-025 GEN
Solar/Wind Harmer
0.413
944641AF1-129 GEN
Adder
174.18
316316AC1-027 C
Solar/Wind Harmer
0.347
316185AD1-033 GEN
Solar/Wind Harmer
0.01
3143526WINTERP
Solar/Wind Harmer
1.841
3144356SAPONY
Solar/Wind Harmer
2.786
972185AH1-677 GEN
Adder
17.914
3145796HORNRTN
Solar/Wind Harmer
0.889
3145783HORNRTN
Solar/Wind Harmer
5.27
3145783HORNRTN
Solar/Wind Harmer
4.216
3145783HORNRTN
Solar/Wind Harmer
1.317
3145783HORNRTN
Solar/Wind Harmer
0.527
970099AG2-077 GEN
Solar/Wind Harmer
31.087
316077AC2-138 C
Solar/Wind Harmer
0.001
3145603CNETO
Solar/Wind Harmer
0.256
316263AC1-034 GEN
Solar/Wind Harmer
10.275
316034AC1-036 C
Solar/Wind Harmer
0.019
962561AG1-105 GEN
Solar/Wind Harmer
12.3
963191AG1-168 GEN
Solar/Wind Harmer
1.024
3144293JTRSVLE
Adder
0.815
3144293JTRSVLE
Adder
0.686
316468AD1-105 GEN
Solar/Wind Harmer
-0.081
315821AE2-092 GEN
Solar/Wind Harmer
0.011
270013AE1-250 PV
Solar/Wind Harmer
0.005
235020AA1-095 C
Solar/Wind Helper
0.045
205916AD1-020 GEN
Solar/Wind Helper
1.645
233933AB2-153 GEN
Solar/Wind Helper
0.225
233944AB2-135 GEN
Solar/Wind Helper
0.569
233946AB2-136 GEN
Solar/Wind Helper
0.549
232408W1-005 C
Solar/Wind Helper
0.491
232410W1-006 C
Solar/Wind Helper
0.491
233939AC1-091 C
Solar/Wind Helper
0.338
238175AF1-290_GEN
Solar/Wind Helper
0.118
3150691DARBY 3
50/50
29.113
3150701DARBY 4
50/50
29.046
3142366NRTHEST
50/50
1.317
3142946ENON
Solar/Wind Harmer
0.038
316017AA1-139 ULT1
Solar/Wind Harmer
0.2
3146456SLIGO L269
Solar/Wind Harmer
6.337
3146386ELIZ CT
Solar/Wind Harmer
0.354
316431W1029_GEN1
Solar/Wind Harmer
0.002
316433W1029_GEN2
Solar/Wind Harmer
0.002
315742AE1-103 GEN
Solar/Wind Harmer
0.004
3146376EDENTON
Solar/Wind Harmer
1.504
3146376EDENTON
Solar/Wind Harmer
1.504
3146173TUNIS
Solar/Wind Harmer
0.313
3146173TUNIS
Solar/Wind Harmer
0.313
970933AG2-581 GEN
Solar/Wind Harmer
24.83
316181AB2-040 GEN
Solar/Wind Harmer
0.436
958261AF2-120 GEN
Solar/Wind Harmer
9.788
316274AC1-208 GEN
Solar/Wind Harmer
1.496
958211AF2-115 GEN
Solar/Wind Harmer
3.071
3146843MT LREL
Solar/Wind Harmer
0.254
3146843MT LREL
Solar/Wind Harmer
0.254
3147133PAMPLIN
Solar/Wind Harmer
0.254
3147133PAMPLIN
Solar/Wind Harmer
0.203
316222AC1-221 GEN
Solar/Wind Harmer
0.945
316447AC1-158 HLD
Solar/Wind Helper
5.508
315651AD1-115 GEN
Solar/Wind Helper
1.146
23777801MSM_W1-116
Solar/Wind Helper
0.11
237025AB1-124 C
Solar/Wind Helper
0.159
230407AD2-065 C
Solar/Wind Helper
0.039
3142433PROV 92
Adder
0.696
3146456SLIGO L269
Solar/Wind Harmer
0.358
971153AH1-033 GEN
Solar/Wind Harmer
4.14
316473AC1-191 GEN
Solar/Wind Harmer
1.209
315813AE1-149 C
Solar/Wind Harmer
19.023
316083AB2-161 GEN
Solar/Wind Harmer
0.005
3141766HARMONY
Solar/Wind Harmer
4.656
3145273HOLLAND
Solar/Wind Harmer
0.258
3146376EDENTON
Solar/Wind Harmer
0.338
972255AH1-712 GEN
Adder
164.714
3146206CASHIE
Solar/Wind Harmer
0.318
3156021HOLLOMANSOL
Solar/Wind Harmer
1.422
3146173TUNIS
Solar/Wind Harmer
0.313
316365GEN2_N
Solar/Wind Harmer
0.699
970009AG2-005 GEN
Solar/Wind Harmer
2.291
3147043LAWRENC
Solar/Wind Harmer
0.175
315724AD1-057 GEN
Solar/Wind Harmer
1.059
316478AD1-087 GEN
Solar/Wind Harmer
0.983
316486AD2-202 GEN
Solar/Wind Harmer
0.289
3146073TAR RVR
Solar/Wind Harmer
0.276
3146083TARBORO
Solar/Wind Harmer
0.276
3138543CONSLDL
Solar/Wind Harmer
0.181
971623AH1-311 GEN
Solar/Wind Harmer
0.541
316131AB2-060 GEN
Solar/Wind Harmer
0.835
959311AF2-222 GEN
Solar/Wind Harmer
23.097
3147133PAMPLIN
Solar/Wind Harmer
0.798
971781AH1-399 GEN
Solar/Wind Harmer
0.329
316283AC2-100 C
Solar/Wind Harmer
0.444
270197AD1-017 GEN1
Solar/Wind Harmer
1.056
941821AE2-187 GEN
Solar/Wind Harmer
5.072
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
270336AE1-100 GEN
Solar/Wind Harmer
0.004
971367AH1-164 GEN
Solar/Wind Harmer
2.405
227287AC2-120 GEN
Solar/Wind Helper
0.432
237030AB1-096 C
Solar/Wind Helper
0.069
233996TM1833_GEN
Solar/Wind Helper
0.253
232406W1-004 FULL
Solar/Wind Helper
0.491
230430AE1-229_GEN
Solar/Wind Helper
3.238
230415AB2-049 C
Solar/Wind Helper
0.029
219766PARADISE C
Solar/Wind Helper
0.052
219912AD2-042 GEN
Solar/Wind Helper
0.144
219291REEVESSOUT C
Solar/Wind Helper
0.011
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
3142296MT RD221
50/50
1.311
3150671DARBY 1
50/50
28.978
316240AF1-291 C
Solar/Wind Harmer
0.003
316036AC1-147 C
Solar/Wind Harmer
0.067
3150991CHESPKB
Adder
3.801
3150991CHESPKB
Adder
3.71
3142956BIRDNECK
Solar/Wind Harmer
0
316018AA1-139 ULT2
Solar/Wind Harmer
0.009
966871AG1-558 GEN
Solar/Wind Harmer
0.414
3146516WINFALL
Solar/Wind Harmer
0.349
3146516WINFALL
Solar/Wind Harmer
0.349
3146516WINFALL
Solar/Wind Harmer
0.349
971223AH1-071 GEN
Solar/Wind Harmer
3.664
316065AD1-022 GEN
Solar/Wind Harmer
14.743
3145893MURPHYS
Solar/Wind Harmer
2.113
3145893MURPHYS
Solar/Wind Harmer
0.568
972187AH1-678 GEN
Adder
8.995
316426AA2-053 GEN
Solar/Wind Harmer
1.013
966811AG1-552 GEN
Solar/Wind Harmer
3.231
3145453TOT5
Solar/Wind Harmer
0.384
961601AG1-000A GEN
Solar/Wind Harmer
4.81
939181AE1-148 GEN
Solar/Wind Harmer
12.944
971741AH1-377 GEN
Solar/Wind Harmer
26.49
964791AG1-342 GEN
Solar/Wind Harmer
4.887
3146776BUCKING
Solar/Wind Harmer
0.914
3146776BUCKING
Solar/Wind Harmer
0.074
971489AH1-241 GEN
Solar/Wind Harmer
10.629
942751AE2-291 GEN
Solar/Wind Harmer
10.765
226929AD2-058 GEN
Solar/Wind Helper
0.127
237034AC2-136 C
Solar/Wind Helper
0.207
237001AB1-127_GEN
Solar/Wind Helper
0.385
235063AE1-101 C2
Solar/Wind Helper
1.423
233987AB2-037 GEN
Solar/Wind Helper
2.265
234036AF2-325 C
Solar/Wind Helper
0.041
233901CHERRYDALE C
Solar/Wind Helper
0.225
971795AH1-408 GEN
Solar/Wind Harmer
19.673
3147043LAWRENC
Adder
2.638
315722AD1-056 GEN
Solar/Wind Harmer
1.786
3146083TARBORO
Solar/Wind Harmer
0.276
316336AC2-165 C
Solar/Wind Harmer
0.011
316359AB2-059 GEN
Solar/Wind Harmer
0.971
3142053HEARTS
Solar/Wind Harmer
0.476
970937AG2-583 GEN
Solar/Wind Harmer
14.682
316003AC1-222 GEN
Solar/Wind Harmer
0.006
3147123OTTER R
Solar/Wind Harmer
0.1
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
972135AH1-637 GEN
Solar/Wind Harmer
1.317
270030AE2-140 GEN
Solar/Wind Harmer
15.132
315705AF1-075 GEN
Solar/Wind Harmer
5.115
316192AB2-158 GEN
Solar/Wind Helper
2.104
237080AD1-060 GEN
Solar/Wind Helper
0.295
966131AG1-482 GEN
Solar/Wind Helper
0.131
232422X3-066 FULL
Solar/Wind Helper
0.11
233964AF2-378 GEN
Solar/Wind Helper
0.04
232426Y1-080 FULL
Solar/Wind Helper
0.038
232434Z2-077 GEN
Solar/Wind Helper
0.123
219904AC1-010 C
Solar/Wind Helper
0.058
3150851SPRUNCC
Adder
1.682
970659AG2-427 GEN
Solar/Wind Harmer
17.218
316093AE2-104_GEN
Solar/Wind Harmer
5.955
3146516WINFALL
Solar/Wind Harmer
1.13
3146516WINFALL
Solar/Wind Harmer
0.349
315800Z1-036_GEN1
Solar/Wind Harmer
0.003
3145893MURPHYS
Solar/Wind Harmer
1.262
3145893MURPHYS
Solar/Wind Harmer
1.404
3146263WOODLND
Solar/Wind Harmer
0.306
3145963POPLR C
Solar/Wind Harmer
0.306
970919AG2-571 GEN
Solar/Wind Harmer
10.879
316174AB2-169 GEN
Solar/Wind Harmer
0.008
316011AB1-132 GEN
Solar/Wind Harmer
5.469
962861AG1-135 GEN
Solar/Wind Harmer
9.564
3141726DUNNSVL
Solar/Wind Harmer
1.146
315693AD1-088 GEN
Solar/Wind Harmer
13.658
962491AG1-098 GEN
Solar/Wind Harmer
16.171
316494AC1-189 GEN
Solar/Wind Harmer
0.948
961671AG1-007 GEN
Solar/Wind Harmer
0.042
3145543BTLEBRO
Solar/Wind Harmer
0.27
3145543BTLEBRO
Solar/Wind Harmer
0.216
963171AG1-166 GEN
Solar/Wind Harmer
1.365
316337AD2-073 GEN
Solar/Wind Harmer
0.212
3146776BUCKING
Solar/Wind Harmer
0.091
941801AE2-185 GEN
Solar/Wind Harmer
5.072
270173AC1-122 GEN
Solar/Wind Harmer
0.358
316045AC1-158 PL2
Solar/Wind Helper
8.011
316006AB2-029 C
Solar/Wind Helper
0.164
23779801AA1-109
Solar/Wind Helper
0.185
237038AE2-054 C
Solar/Wind Helper
0.233
219686LUMSOLAR_N C
Solar/Wind Helper
0.038
972263AH1-716 GEN
50/50
220.54
316369SG1_INVT
Solar/Wind Harmer
0.014
319010AE1-072 C
Solar/Wind Harmer
1.802
3143873LANEXA
Solar/Wind Harmer
0.213
971281AH1-106 GEN
Solar/Wind Harmer
4.913
3146486SUNBURY
Solar/Wind Harmer
0.352
3146486SUNBURY
Solar/Wind Harmer
0.352
3143316POE
Solar/Wind Harmer
1.396
316321Z2-027
Solar/Wind Harmer
0.065
3145176PASQUOTANK
Solar/Wind Harmer
0.218
315662AE1-191 GEN
Solar/Wind Harmer
0.011
3141873WAN 176
Solar/Wind Harmer
0.069
315611Z1-036_GEN2
Solar/Wind Harmer
0.003
3130156CHOWAN
Solar/Wind Harmer
0.338
3130156CHOWAN
Solar/Wind Harmer
0.338
3138133OCRAN
Solar/Wind Harmer
0.099
315816AE2-034 GEN
Solar/Wind Harmer
1.417
3130546PLYMOUTH
Solar/Wind Harmer
0.324
315733AD1-074 GEN2
Solar/Wind Harmer
1.854
970601AG2-382 GEN
Solar/Wind Harmer
11.901
970581AG2-369 GEN
Solar/Wind Harmer
13.984
316087AB2-174 GEN
Solar/Wind Harmer
0.009
3146033SCOT NK
Solar/Wind Harmer
1.185
970181AG2-120 GEN
Solar/Wind Harmer
3.56
972189AH1-679 GEN
Adder
4.36
972205AH1-687 GEN
Adder
8.917
3148013FISHERV
Solar/Wind Harmer
0.088
3151881LOWMORC
Adder
1.595
3151881LOWMORC
Adder
1.57
270069AE2-166 C O1
Solar/Wind Harmer
0.005
944491AF1-114 GEN
Solar/Wind Harmer
0
205943AE1-185 GEN
Solar/Wind Helper
0.491
233990AG1-397 GEN
Solar/Wind Helper
0.261
238208AF1-136 C
Solar/Wind Helper
0.173
964001AG1-254 GEN
Solar/Wind Helper
0.917
227927V4-067C
Solar/Wind Helper
0.01
219688LUMSOLAR_S C
Solar/Wind Helper
0.038
957481AF2-042 GEN
Solar/Wind Harmer
77.718
3145493TOT1
Solar/Wind Harmer
1.227
3146233WITAKRS
Solar/Wind Harmer
1.096
316049AB1-081 GEN
Solar/Wind Harmer
1.547
970685AG2-442 GEN
Solar/Wind Harmer
19.275
971563AH1-280 GEN
Solar/Wind Harmer
2.73
3146926FARMVIL
Solar/Wind Harmer
0.147
971377AH1-170 GEN
Solar/Wind Harmer
2.126
970223AG2-152 GEN
Solar/Wind Harmer
12.134
316254AC1-120 GEN1
Solar/Wind Helper
1.563
3147666LOUISA
Solar/Wind Helper
1.282
223401AF1-299 GEN
Solar/Wind Helper
0.393
235062AE1-101 C1
Solar/Wind Helper
1.423
233915AB1-141 GEN
Solar/Wind Helper
0.486
232428Y3-058 C
Solar/Wind Helper
0.327
233998TM1NIN_3.36
Solar/Wind Helper
0.253
232404W1-003 C
Solar/Wind Helper
0.491
233950AC2-186 GEN
Solar/Wind Helper
0.112
233972AC1-094 C
Solar/Wind Helper
0.292
228728W1-130C
Solar/Wind Helper
0.052
218660EHAMPSOLAR C
Solar/Wind Helper
0.032
3144216WINCHST
Adder
1.402
315778AD1-151 GEN
Solar/Wind Harmer
29.426
944601AF1-125 GEN
Solar/Wind Harmer
80.532
3151101ELIZAR3
Adder
33.706
315839AE2-212 C
Solar/Wind Harmer
0.003
316317KELFORD C
Solar/Wind Harmer
0.029
3145823KELFORD
Solar/Wind Harmer
0.303
3145796HORNRTN
Solar/Wind Harmer
1.185
3145796HORNRTN
Solar/Wind Harmer
0.296
316210AC1-098 GEN
Solar/Wind Harmer
2.699
316258AE1-075 C
Solar/Wind Harmer
0.219
3143336POWHATN
Solar/Wind Harmer
4.377
3145746EVERETS
Solar/Wind Harmer
0.286
3145746EVERETS
Solar/Wind Harmer
0.286
3150351NORNECKC2
Adder
2.804
964241AG1-285 GEN
Solar/Wind Harmer
17.596
970909AG2-566 GEN
Solar/Wind Harmer
2.793
3144293JTRSVLE
Adder
0.815
971193AH1-056 GEN
Solar/Wind Harmer
15.489
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
10.514
971683AH1-343 GEN
Solar/Wind Harmer
8.489
3147312GRETNA
Solar/Wind Harmer
0.032
3141196NOKESVL
Solar/Wind Helper
1.389
226910AB2-157 C
Solar/Wind Helper
0.018
223402AF1-300 C
Solar/Wind Helper
0.393
238221AF1-254 C O1
Solar/Wind Helper
0.238
233982AB2-133 GEN
Solar/Wind Helper
0.346
233940AF2-379 C
Solar/Wind Helper
0.06
233952AC2-187 GEN
Solar/Wind Helper
0.225
219623KINSLEYBEA C
Solar/Wind Helper
0.002
NYPJM->LTFIMP_NY
CLTF
4.634
LGEELTFEXP_LGEE->PJM
CLTF
3.014
WECLTFEXP_WEC->PJM
CLTF
1.525
AG2-052LTFEXP_AG2-052->PJM
LTF
0.084
AH1-155LTFEXP_AH1-155->PJM
LTF
0.126
LAGNLTFEXP_LAGN->PJM
CLTF
14.625
CBM South 2LTFEXP_CBM-S2->PJM
CBM
39.998
TVALTFEXP_TVA->PJM
CLTF
7.404
CPLELTFEXP_CPLE->PJM
CLTF
17.713
CBM West 2LTFEXP_CBM-W2->PJM
CBM
80.377
CBM West 1LTFEXP_CBM-W1->PJM
CBM
53.563
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.762
MECLTFEXP_MEC->PJM
CLTF
7.835
SIGELTFEXP_SIGE->PJM
CLTF
0.242

Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:153.9 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:6264.0
MW Contribution:2.1
Bus #Bus NameTypeMW Contribution
316382AG1-145 C
Solar/Wind Harmer
0.003
3144873MCLAUGH
Solar/Wind Harmer
0.008
3151171GRAVELC
Adder
4.361
961611AG1-000B GEN
Solar/Wind Harmer
8.272
970129AG2-093 GEN
Solar/Wind Harmer
18.454
970661AG2-428 GEN
Solar/Wind Harmer
6.346
3146626S HERTFORD
Solar/Wind Harmer
0.299
3141843SHACKLE
Adder
1.519
316280AD1-041 GEN
Solar/Wind Harmer
0.006
3141873WAN 176
Solar/Wind Harmer
5.232
965281AG1-393 GEN
Solar/Wind Harmer
3.137
3143096IRON208
Adder
1.226
3143096IRON208
Adder
1.201
315737AD1-076 GEN
Solar/Wind Harmer
3.567
3156081AA2-088 GEN
Solar/Wind Harmer
0.006
961681AG1-008 GEN
Solar/Wind Harmer
20.016
962971AG1-146 GEN
Solar/Wind Harmer
4.293
962331AG1-082 GEN
Solar/Wind Harmer
2.839
970917AG2-570 GEN
Solar/Wind Harmer
23.14
971317AH1-138 GEN
Solar/Wind Harmer
2.41
3150921YORKTN3
50/50
8.624
3151161SURRY 1
50/50
11.975
315773AC2-141 GEN
Solar/Wind Harmer
11.84
970293AG2-193 GEN
Solar/Wind Harmer
3.398
944581AF1-123 GEN
Solar/Wind Harmer
71.01
3144536CHRHLND
Solar/Wind Harmer
0.047
944591AF1-124 GEN
Solar/Wind Harmer
71.262
316072AD1-144
Solar/Wind Harmer
0.112
944631AF1-128 GEN
Adder
146.833
972277AH1-723 GEN
Adder
183.583
939411AE1-173 GEN
Solar/Wind Harmer
127.601
315671AE2-027_GEN
Solar/Wind Harmer
18.84
940641AE2-051 GEN
Solar/Wind Harmer
23.538
971547AH1-271 GEN
Solar/Wind Harmer
5.835
3145823KELFORD
Solar/Wind Harmer
0.259
962571AG1-106 GEN
Solar/Wind Harmer
3.63
960081AF2-299 GEN
Solar/Wind Harmer
2.448
3145796HORNRTN
Solar/Wind Harmer
0.83
3145796HORNRTN
Solar/Wind Harmer
0.251
3145783HORNRTN
Solar/Wind Harmer
0.251
316212AC1-099_GEN
Solar/Wind Harmer
1.281
3145746EVERETS
Solar/Wind Harmer
0.244
3145746EVERETS
Solar/Wind Harmer
0.244
3150351NORNECKC2
Adder
2.352
316129AC1-054 GEN
Solar/Wind Harmer
0.885
971065AG2-659 GEN
Solar/Wind Harmer
9.97
315687AD1-152 GEN
Solar/Wind Harmer
0.007
316237AB2-079_GEN
Solar/Wind Harmer
0.002
970401AG2-262 GEN
Solar/Wind Harmer
1.243
3144293JTRSVLE
Adder
0.645
3143526WINTERP
Solar/Wind Harmer
0.968
316236AE1-162_GEN
Solar/Wind Harmer
0.003
3145506HICKORY
Solar/Wind Harmer
1.25
3145506HICKORY
Solar/Wind Harmer
0.75
3145506HICKORY
Solar/Wind Harmer
0.188
316339AD2-160 GEN
Solar/Wind Harmer
0.505
3150681DARBY 2
Adder
22.265
315976AC1-164 GENA
Solar/Wind Harmer
34.449
316169AC1-164_GENC
Solar/Wind Harmer
29.761
315975AC1-164 GENB
Solar/Wind Harmer
1.019
3151201GRAVEL4
Adder
22.69
3151211GRAVEL5
Adder
22.403
313526AB2-022
Solar/Wind Harmer
0.166
315835AF2-110_GEN
Solar/Wind Harmer
2.092
3146396TANGLEW
Solar/Wind Harmer
0.839
316311AC2-079 GEN
Solar/Wind Harmer
8.688
316349AD2-085 GEN
Solar/Wind Harmer
0.207
3142433PROV 92
Adder
0.583
3142433PROV 92
Adder
0.583
316059AD1-063 C
Solar/Wind Harmer
0.002
315814AE2-033 C
Solar/Wind Harmer
22.041
3141783LANCAST
Solar/Wind Harmer
0.167
3141783LANCAST
Solar/Wind Harmer
0.111
3146206CASHIE
Solar/Wind Harmer
0.273
3145683EARLEYS
Solar/Wind Harmer
0.53
3145683EARLEYS
Solar/Wind Harmer
0.265
3145683EARLEYS
Solar/Wind Harmer
0.265
3146043SEABORD
Solar/Wind Harmer
0.261
316420AA1-050 GEN
Solar/Wind Harmer
0.008
316319Z2-044 C
Solar/Wind Harmer
0
3147173SINAI
Solar/Wind Harmer
0.207
3147243WELCO
Solar/Wind Harmer
0.129
961791AG1-021 GEN
Solar/Wind Harmer
1.944
970165AG2-112 GEN
Solar/Wind Harmer
1.423
970163AG2-111 GEN
Solar/Wind Harmer
1.357
970285AG2-188 GEN
Solar/Wind Harmer
13.264
972265AH1-717 GEN
Adder
24.205
3151191GRAVEL3
Adder
22.403
3146406KITTY HAWK
Solar/Wind Harmer
0.039
3138283WHITEMARSH
Solar/Wind Harmer
0.072
3151081ELIZAR1
50/50
30.584
3151091ELIZAR2
50/50
30.053
3152611GOSPORTB
50/50
4.245
3152621GOSPORTC
50/50
3.603
3152601GOSPORTA
50/50
3.323
316312AB1-027
Solar/Wind Harmer
0.592
971445AH1-216 GEN
Solar/Wind Harmer
22.015
957871AF2-081 GEN
Solar/Wind Harmer
15.477
316314AB2-024 C
Solar/Wind Harmer
0.001
315833AF1-017_GEN
Solar/Wind Harmer
0.002
3141913WHIT STONE
Solar/Wind Harmer
0.285
316315AB2-025 C
Solar/Wind Harmer
0.226
941031AE2-094 GEN
Solar/Wind Harmer
51.279
970673AG2-436 GEN
Solar/Wind Harmer
58.436
970673AG2-436 GEN
Solar/Wind Harmer
38.957
970327AG2-215 GEN
Solar/Wind Harmer
8.614
971285AH1-108 GEN
Adder
1.899
3145796HORNRTN
Solar/Wind Harmer
0.805
3145796HORNRTN
Solar/Wind Harmer
0.101
3145746EVERETS
Solar/Wind Harmer
0.973
3145746EVERETS
Solar/Wind Harmer
0.244
3145746EVERETS
Solar/Wind Harmer
0.244
3145746EVERETS
Solar/Wind Harmer
0.244
957861AF2-080 GEN
Solar/Wind Harmer
10.333
970831AG2-522 GEN
Solar/Wind Harmer
10.106
3145573BETHELC
Solar/Wind Harmer
0.235
3145573BETHELC
Solar/Wind Harmer
0.235
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
970683AG2-441 GEN
Solar/Wind Harmer
13.748
970681AG2-440 GEN
Solar/Wind Harmer
10.999
970865AG2-541 GEN
Solar/Wind Harmer
6.515
316075AC2-137 C
Solar/Wind Harmer
0.09
316316AC1-027 C
Solar/Wind Harmer
0.301
316185AD1-033 GEN
Solar/Wind Harmer
0.009
315697AD1-025 GEN
Solar/Wind Harmer
0.346
944641AF1-129 GEN
Adder
140.632
3144356SAPONY
Solar/Wind Harmer
2.337
972185AH1-677 GEN
Adder
15.245
3145796HORNRTN
Solar/Wind Harmer
0.754
3145783HORNRTN
Solar/Wind Harmer
4.467
3145783HORNRTN
Solar/Wind Harmer
3.574
3145783HORNRTN
Solar/Wind Harmer
1.117
3145783HORNRTN
Solar/Wind Harmer
0.447
970099AG2-077 GEN
Solar/Wind Harmer
26.046
316077AC2-138 C
Solar/Wind Harmer
0.001
3145603CNETO
Solar/Wind Harmer
0.218
316263AC1-034 GEN
Solar/Wind Harmer
8.746
962561AG1-105 GEN
Solar/Wind Harmer
10.222
316034AC1-036 C
Solar/Wind Harmer
0.015
3142946ENON
Solar/Wind Harmer
0.031
316017AA1-139 ULT1
Solar/Wind Harmer
0.174
3150691DARBY 3
Adder
22.343
3150701DARBY 4
Adder
22.291
3146456SLIGO L269
Solar/Wind Harmer
5.488
3146386ELIZ CT
Solar/Wind Harmer
0.306
3142366NRTHEST
Adder
1
316431W1029_GEN1
Solar/Wind Harmer
0.002
316433W1029_GEN2
Solar/Wind Harmer
0.002
3146376EDENTON
Solar/Wind Harmer
1.297
3146376EDENTON
Solar/Wind Harmer
1.297
315742AE1-103 GEN
Solar/Wind Harmer
0.003
3146173TUNIS
Solar/Wind Harmer
0.267
3146173TUNIS
Solar/Wind Harmer
0.267
970933AG2-581 GEN
Solar/Wind Harmer
21
971645AH1-323 GEN
50/50
29.723
3142416OLDCHRC
Solar/Wind Harmer
3.208
3142946ENON
Solar/Wind Harmer
0.105
3145336SMITFLD
Solar/Wind Harmer
0.125
3151221GRAVEL6
Adder
22.664
3146456SLIGO L269
Solar/Wind Harmer
0.31
971153AH1-033 GEN
Solar/Wind Harmer
3.585
972255AH1-712 GEN
Adder
157.541
970133AG2-095 GEN
Solar/Wind Harmer
2.91
3142433PROV 92
Adder
0.583
3142433PROV 92
Adder
0.583
316473AC1-191 GEN
Solar/Wind Harmer
1.014
3141766HARMONY
Solar/Wind Harmer
3.995
316083AB2-161 GEN
Solar/Wind Harmer
0.004
315813AE1-149 C
Solar/Wind Harmer
15.819
3145273HOLLAND
Solar/Wind Harmer
0.221
3146376EDENTON
Solar/Wind Harmer
0.291
3146206CASHIE
Solar/Wind Harmer
0.273
3156021HOLLOMANSOL
Solar/Wind Harmer
1.218
3146173TUNIS
Solar/Wind Harmer
0.267
316365GEN2_N
Solar/Wind Harmer
0.59
970009AG2-005 GEN
Solar/Wind Harmer
1.96
3147043LAWRENC
Solar/Wind Harmer
0.146
315724AD1-057 GEN
Solar/Wind Harmer
0.9
316478AD1-087 GEN
Solar/Wind Harmer
0.823
316486AD2-202 GEN
Solar/Wind Harmer
0.242
3146073TAR RVR
Solar/Wind Harmer
0.235
3146083TARBORO
Solar/Wind Harmer
0.235
3138543CONSLDL
Solar/Wind Harmer
0.154
971623AH1-311 GEN
Solar/Wind Harmer
0.46
316131AB2-060 GEN
Solar/Wind Harmer
0.687
959311AF2-222 GEN
Solar/Wind Harmer
18.581
971781AH1-399 GEN
Solar/Wind Harmer
0.272
3147133PAMPLIN
Solar/Wind Harmer
0.627
316283AC2-100 C
Solar/Wind Harmer
0.376
270197AD1-017 GEN1
Solar/Wind Harmer
0.911
941821AE2-187 GEN
Solar/Wind Harmer
4.349
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
270336AE1-100 GEN
Solar/Wind Harmer
0.003
971367AH1-164 GEN
Solar/Wind Harmer
2.104
227287AC2-120 GEN
Solar/Wind Helper
0.383
237030AB1-096 C
Solar/Wind Helper
0.06
3142296MT RD221
50/50
1.096
3150991CHESPKB
50/50
3.492
3150991CHESPKB
50/50
3.408
316036AC1-147 C
Solar/Wind Harmer
0.058
3142956BIRDNECK
Solar/Wind Harmer
0
316018AA1-139 ULT2
Solar/Wind Harmer
0.008
3150671DARBY 1
Adder
22.239
3146516WINFALL
Solar/Wind Harmer
0.301
3146516WINFALL
Solar/Wind Harmer
0.301
3146516WINFALL
Solar/Wind Harmer
0.301
966871AG1-558 GEN
Solar/Wind Harmer
0.347
316240AF1-291 C
Solar/Wind Harmer
0.002
316065AD1-022 GEN
Solar/Wind Harmer
12.657
3145893MURPHYS
Solar/Wind Harmer
1.804
3152331SURRY 2
50/50
13.991
971353AH1-157 GEN
50/50
28.65
970017AG2-010 GEN
50/50
21.737
3142416OLDCHRC
Solar/Wind Harmer
0.86
3142416OLDCHRC
Solar/Wind Harmer
0.33
316294AC1-161 GEN
Solar/Wind Harmer
5.617
316375AC2-012 GEN
Solar/Wind Harmer
0.008
3145336SMITFLD
Solar/Wind Harmer
1.25
3146456SLIGO L269
Solar/Wind Harmer
0.31
3142433PROV 92
Solar/Wind Harmer
1.2
3142433PROV 92
Adder
0.583
3142433PROV 92
Adder
0.583
3141766HARMONY
Solar/Wind Harmer
0.06
971777AH1-397 GEN
Solar/Wind Harmer
0.785
3145663CRESWEL
Solar/Wind Harmer
0.795
3146206CASHIE
Solar/Wind Harmer
0.273
3146173TUNIS
Solar/Wind Harmer
0.267
3145683EARLEYS
Solar/Wind Harmer
0.265
316023GEN1_S
Solar/Wind Harmer
0.59
971795AH1-408 GEN
Solar/Wind Harmer
16.501
3147043LAWRENC
Adder
2.208
315722AD1-056 GEN
Solar/Wind Harmer
1.518
3146083TARBORO
Solar/Wind Harmer
0.235
316359AB2-059 GEN
Solar/Wind Harmer
0.827
3142053HEARTS
Solar/Wind Harmer
0.405
316003AC1-222 GEN
Solar/Wind Harmer
0.005
3147123OTTER R
Solar/Wind Harmer
0.085
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
970937AG2-583 GEN
Solar/Wind Harmer
8.286
316336AC2-165 C
Solar/Wind Harmer
0.005
972135AH1-637 GEN
Solar/Wind Harmer
1.098
270030AE2-140 GEN
Solar/Wind Harmer
13.116
315705AF1-075 GEN
Solar/Wind Harmer
4.718
316192AB2-158 GEN
Solar/Wind Helper
1.689
316093AE2-104_GEN
Solar/Wind Harmer
5.127
3146516WINFALL
Solar/Wind Harmer
0.976
3146516WINFALL
Solar/Wind Harmer
0.301
970659AG2-427 GEN
Solar/Wind Harmer
14.437
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
3145893MURPHYS
Solar/Wind Harmer
1.078
3145893MURPHYS
Solar/Wind Harmer
1.199
3145963POPLR C
Solar/Wind Harmer
0.263
3146263WOODLND
Solar/Wind Harmer
0.261
316174AB2-169 GEN
Solar/Wind Harmer
0.007
970919AG2-571 GEN
Solar/Wind Harmer
9.256
962861AG1-135 GEN
Solar/Wind Harmer
8.175
316011AB1-132 GEN
Solar/Wind Harmer
4.638
3150851SPRUNCC
Adder
1.161
3141726DUNNSVL
Solar/Wind Harmer
0.979
316494AC1-189 GEN
Solar/Wind Harmer
0.81
315693AD1-088 GEN
Solar/Wind Harmer
11.318
961671AG1-007 GEN
Solar/Wind Harmer
0.036
962491AG1-098 GEN
Solar/Wind Harmer
13.368
3145543BTLEBRO
Solar/Wind Harmer
0.23
3145543BTLEBRO
Solar/Wind Harmer
0.184
316337AD2-073 GEN
Solar/Wind Harmer
0.18
963171AG1-166 GEN
Solar/Wind Harmer
1.08
3146776BUCKING
Solar/Wind Harmer
0.065
941801AE2-185 GEN
Solar/Wind Harmer
4.349
270173AC1-122 GEN
Solar/Wind Harmer
0.31
316045AC1-158 PL2
Solar/Wind Helper
6.543
316006AB2-029 C
Solar/Wind Helper
0.142
23779801AA1-109
Solar/Wind Helper
0.161
316305AF2-043 C
Solar/Wind Harmer
0.002
972193AH1-681 GEN
Adder
7.039
316132AB2-190 GEN1
Solar/Wind Harmer
1.639
971167AH1-042 GEN
Solar/Wind Harmer
26.63
970189AG2-124 GEN
Solar/Wind Harmer
8.811
315666AE1-190 GEN
Solar/Wind Harmer
0.002
944011AF1-069 GEN
Solar/Wind Harmer
16.755
315732AD1-074 GEN1
Solar/Wind Harmer
1.593
315735AD1-075 GEN1
Solar/Wind Harmer
0.797
965291AG1-394 GEN
Solar/Wind Harmer
1.209
971967AH1-528 GEN
Solar/Wind Harmer
43.16
3145893MURPHYS
Solar/Wind Harmer
0.728
3145893MURPHYS
Solar/Wind Harmer
0.269
962981AG1-147 GEN
Solar/Wind Harmer
10.018
3145513AHOSKIE
Solar/Wind Harmer
0.556
3145513AHOSKIE
Solar/Wind Harmer
0.266
315607AA1-063A GEN
Solar/Wind Harmer
0.531
970085AG2-068 GEN
Solar/Wind Harmer
13.834
315652AC1-086 GEN
Solar/Wind Harmer
28.063
3137643SOCKMAN
Solar/Wind Harmer
1.011
316005AA1-067
Solar/Wind Harmer
0.262
3141813NORNECK
Solar/Wind Harmer
0.236
971443AH1-215 GEN
Solar/Wind Harmer
3.537
3144303KENBRDG
Solar/Wind Harmer
0.168
316118AC1-105 GEN
Solar/Wind Harmer
0.54
946301AF1-294 GEN
Solar/Wind Harmer
3.996
315657AE1-056 GEN
Solar/Wind Harmer
6.894
316233AE1-074 FULL
Solar/Wind Harmer
0.149
971283AH1-107 GEN
Solar/Wind Harmer
2.583
316223AC1-118
Solar/Wind Harmer
0.126
3151861LOWMORA
Adder
1.42
270494AE1-108_GEN
Solar/Wind Harmer
1.551
316164AC1-076 GEN
Solar/Wind Helper
1.573
3138216PACIFIC
Solar/Wind Helper
0.046
972263AH1-716 GEN
50/50
194.204
941591AE2-156 GEN
50/50
27.947
319010AE1-072 C
Solar/Wind Harmer
1.561
316369SG1_INVT
Solar/Wind Harmer
0.011
3146486SUNBURY
Solar/Wind Harmer
0.305
3146486SUNBURY
Solar/Wind Harmer
0.305
316321Z2-027
Solar/Wind Harmer
0.057
3150981CHESPKA
50/50
4.162
316159AE1-175 C
Solar/Wind Harmer
0.283
3138126ROCKLANDING
Solar/Wind Harmer
0.148
3151171GRAVELC
Adder
3.316
316388AE2-253 GEN
Solar/Wind Harmer
0.975
961611AG1-000B GEN
Solar/Wind Harmer
16.269
971647AH1-324 GEN
Solar/Wind Harmer
13.184
316246AF1-032 C
Solar/Wind Harmer
0.139
971069AG2-661 GEN
Solar/Wind Harmer
5.456
316458AB2-190 GEN2
Solar/Wind Harmer
1.639
970129AG2-093 GEN
Solar/Wind Harmer
8.684
970661AG2-428 GEN
Solar/Wind Harmer
29.836
316381AD1-082 GEN
Solar/Wind Harmer
0.311
3141843SHACKLE
Adder
1.519
3143096IRON208
Adder
1.226
3130156CHOWAN
Solar/Wind Harmer
0.292
971163AH1-040 GEN
Solar/Wind Harmer
22.732
3138133OCRAN
Solar/Wind Harmer
0.17
3142543TWELFTH
Solar/Wind Harmer
0.027
970087AG2-069 GEN
Solar/Wind Harmer
20.752
316190AA2-174 GEN
Solar/Wind Harmer
0
3146293MARTNCO
Solar/Wind Harmer
0.232
957481AF2-042 GEN
Solar/Wind Harmer
65.115
3145493TOT1
Solar/Wind Harmer
1.047
3146233WITAKRS
Solar/Wind Harmer
0.932
316049AB1-081 GEN
Solar/Wind Harmer
1.317
970685AG2-442 GEN
Solar/Wind Harmer
15.398
971563AH1-280 GEN
Solar/Wind Harmer
2.16
3146926FARMVIL
Solar/Wind Harmer
0.111
970223AG2-152 GEN
Solar/Wind Harmer
10.425
3143226MDLTHAN
Solar/Wind Harmer
0.134
971377AH1-170 GEN
Solar/Wind Harmer
1.425
316254AC1-120 GEN1
Solar/Wind Helper
1.333
3147666LOUISA
Solar/Wind Helper
1.029
223401AF1-299 GEN
Solar/Wind Helper
0.346
3145176PASQUOTANK
Solar/Wind Harmer
0.189
3143873LANEXA
Solar/Wind Harmer
0.181
315662AE1-191 GEN
Solar/Wind Harmer
0.01
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
3141873WAN 176
Solar/Wind Harmer
0.059
3130156CHOWAN
Solar/Wind Harmer
0.292
3130156CHOWAN
Solar/Wind Harmer
0.292
3143316POE
Solar/Wind Harmer
1.153
315816AE2-034 GEN
Solar/Wind Harmer
1.219
3138133OCRAN
Solar/Wind Harmer
0.085
3130546PLYMOUTH
Solar/Wind Harmer
0.278
315733AD1-074 GEN2
Solar/Wind Harmer
1.593
970601AG2-382 GEN
Solar/Wind Harmer
10.212
970581AG2-369 GEN
Solar/Wind Harmer
11.898
316087AB2-174 GEN
Solar/Wind Harmer
0.007
3146033SCOT NK
Solar/Wind Harmer
1.01
970181AG2-120 GEN
Solar/Wind Harmer
3.044
972189AH1-679 GEN
Adder
3.657
971281AH1-106 GEN
Solar/Wind Harmer
2.583
3151881LOWMORC
Adder
1.466
3151881LOWMORC
Adder
1.443
3148013FISHERV
Solar/Wind Harmer
0.078
972205AH1-687 GEN
Adder
5.785
270069AE2-166 C O1
Solar/Wind Harmer
0.004
3137176SLIGO L2192
Solar/Wind Harmer
1.234
3130086AYDLETT
Solar/Wind Harmer
1.238
316033AB2-134 GEN
Solar/Wind Harmer
0.018
970657AG2-426 GEN
Solar/Wind Harmer
10.482
970657AG2-426 GEN
Solar/Wind Harmer
2.198
3146626S HERTFORD
Solar/Wind Harmer
0.299
3146626S HERTFORD
Solar/Wind Harmer
0.299
3142666NORTHAMPTON
Solar/Wind Harmer
0.256
3142666NORTHAMPTON
Solar/Wind Harmer
0.256
3142666NORTHAMPTON
Solar/Wind Harmer
0.256
3142666NORTHAMPTON
Solar/Wind Harmer
0.154
3145593CAROLNA
Solar/Wind Harmer
0.252
3145593CAROLNA
Solar/Wind Harmer
0.252
3145593CAROLNA
Solar/Wind Harmer
0.314
3145933PARMELE
Solar/Wind Harmer
0.501
3145933PARMELE
Solar/Wind Harmer
0.25
3150341NORNECKC1
Adder
2.471
3150341NORNECKC1
Adder
2.451
3145493TOT1
Solar/Wind Harmer
0.546
313527AB2-043 GEN
Solar/Wind Harmer
0.003
970323AG2-213 GEN
Solar/Wind Harmer
8.967
971775AH1-396 GEN
Solar/Wind Harmer
0.336
970301AG2-198 GEN
Solar/Wind Harmer
8.797
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
3.383
237006AB1-125 GEN
Solar/Wind Helper
0.105
3145893MURPHYS
Solar/Wind Harmer
0.485
972187AH1-678 GEN
Adder
7.651
316426AA2-053 GEN
Solar/Wind Harmer
0.86
966811AG1-552 GEN
Solar/Wind Harmer
2.738
3145453TOT5
Solar/Wind Harmer
0.327
961601AG1-000A GEN
Solar/Wind Harmer
4.095
939181AE1-148 GEN
Solar/Wind Harmer
10.786
971741AH1-377 GEN
Solar/Wind Harmer
21.126
964791AG1-342 GEN
Solar/Wind Harmer
4.068
942751AE2-291 GEN
Solar/Wind Harmer
9.118
3146776BUCKING
Solar/Wind Harmer
0.649
3146776BUCKING
Solar/Wind Harmer
0.052
971223AH1-071 GEN
Solar/Wind Harmer
1.43
971489AH1-241 GEN
Solar/Wind Harmer
7.125
226929AD2-058 GEN
Solar/Wind Helper
0.113
3144216WINCHST
50/50
1.289
3151101ELIZAR3
50/50
30.975
944601AF1-125 GEN
Solar/Wind Harmer
69.916
315778AD1-151 GEN
Solar/Wind Harmer
24.551
315839AE2-212 C
Solar/Wind Harmer
0.002
316317KELFORD C
Solar/Wind Harmer
0.025
3145823KELFORD
Solar/Wind Harmer
0.259
3145796HORNRTN
Solar/Wind Harmer
1.006
3145796HORNRTN
Solar/Wind Harmer
0.251
316210AC1-098 GEN
Solar/Wind Harmer
2.297
3145746EVERETS
Solar/Wind Harmer
0.244
3145746EVERETS
Solar/Wind Harmer
0.244
3150351NORNECKC2
Adder
2.392
964241AG1-285 GEN
Solar/Wind Harmer
14.393
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
8.82
970909AG2-566 GEN
Solar/Wind Harmer
2.199
3144293JTRSVLE
Adder
0.645
971193AH1-056 GEN
Solar/Wind Harmer
12.172
971683AH1-343 GEN
Solar/Wind Harmer
7.141
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3147312GRETNA
Solar/Wind Harmer
0.027
316258AE1-075 C
Solar/Wind Harmer
0.102
3143336POWHATN
Solar/Wind Harmer
2.034
3141196NOKESVL
Solar/Wind Helper
1.216
226910AB2-157 C
Solar/Wind Helper
0.016
223402AF1-300 C
Solar/Wind Helper
0.346
316322AB2-045
Solar/Wind Harmer
0.001
270016AE1-250 BESS
Solar/Wind Harmer
0.004
972003AH1-546 GEN
Solar/Wind Harmer
5.963
3147312GRETNA
Solar/Wind Harmer
0.109
3146802CHATHAM
Solar/Wind Harmer
0.102
3143336POWHATN
Solar/Wind Harmer
2.393
3147623JAMES R
Solar/Wind Harmer
0.31
962751AG1-124 GEN
Solar/Wind Harmer
5.402
316320Y1-086
Solar/Wind Harmer
0.002
316435W1029_GEN3
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.301
970659AG2-427 GEN
Solar/Wind Harmer
3.158
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316156AD2-030 GEN
Solar/Wind Harmer
0.218
315614AA2-178 GEN
Solar/Wind Harmer
1.626
971157AH1-035 GEN
Solar/Wind Harmer
3.34
3145893MURPHYS
Solar/Wind Harmer
0.451
3145893MURPHYS
Solar/Wind Harmer
0.269
957521AF2-046 GEN
Solar/Wind Harmer
20.016
316463AE2-346 GEN
Solar/Wind Harmer
0.229
316140AB2-099
Solar/Wind Harmer
0.095
3145963POPLR C
Solar/Wind Harmer
0.263
3146263WOODLND
Solar/Wind Harmer
0.261
316327AA2-057 GEN
Solar/Wind Harmer
0.36
961601AG1-000A GEN
Solar/Wind Harmer
16.379
3145543BTLEBRO
Solar/Wind Harmer
0.23
3145543BTLEBRO
Solar/Wind Harmer
0.23
3146776BUCKING
Solar/Wind Harmer
0.058
970737AG2-469 GEN
Solar/Wind Harmer
6.299
3151861LOWMORA
Adder
1.478
316313AB2-026
Solar/Wind Harmer
0.085
970221AG2-151 GEN
Solar/Wind Harmer
7.125
958131AF2-107 GEN
Solar/Wind Harmer
3.424
316170AC1-121 GEN2
Solar/Wind Helper
0.444
3142666NORTHAMPTON
Solar/Wind Harmer
0.256
313506AB2-031 GEN
Solar/Wind Harmer
0.784
316404AE1-155 C
Solar/Wind Harmer
0.057
3150861SPRUNCD
Adder
1.161
3145933PARMELE
Solar/Wind Harmer
0.25
966801AG1-551 GEN
Solar/Wind Harmer
2.916
3146233WITAKRS
Solar/Wind Harmer
1.176
3146233WITAKRS
Solar/Wind Harmer
0.159
315785AD2-033 C
Solar/Wind Harmer
1.721
970257AG2-171 GEN
Solar/Wind Harmer
6.725
963181AG1-167 GEN
Solar/Wind Harmer
0.81
3146926FARMVIL
Solar/Wind Harmer
0.111
3141906WESTMOR
Solar/Wind Harmer
0.07
315616AA1-038_C
Solar/Wind Harmer
0.001
3148013FISHERV
Solar/Wind Harmer
0.135
316405AF2-144 C
Solar/Wind Harmer
0.001
270018AE2-047 C O1
Solar/Wind Harmer
0.003
316044AC1-158 PL1
Solar/Wind Helper
2.044
316450AC1-158 RIC
Solar/Wind Helper
0.545
3147666LOUISA
Solar/Wind Helper
0.591
971845AH1-439 GEN
Solar/Wind Harmer
7.44
3148463FAIRFLD
Solar/Wind Harmer
0.138
316181AB2-040 GEN
Solar/Wind Harmer
0.368
958261AF2-120 GEN
Solar/Wind Harmer
8.365
316274AC1-208 GEN
Solar/Wind Harmer
1.272
3146843MT LREL
Solar/Wind Harmer
0.212
3146843MT LREL
Solar/Wind Harmer
0.212
958211AF2-115 GEN
Solar/Wind Harmer
2.43
3147133PAMPLIN
Solar/Wind Harmer
0.2
3147133PAMPLIN
Solar/Wind Harmer
0.16
316222AC1-221 GEN
Solar/Wind Harmer
0.802
316447AC1-158 HLD
Solar/Wind Helper
4.499
315651AD1-115 GEN
Solar/Wind Helper
0.98
23777801MSM_W1-116
Solar/Wind Helper
0.096
237025AB1-124 C
Solar/Wind Helper
0.14
316123AC1-075 GEN
Solar/Wind Harmer
0.24
3148133STUARTS
Solar/Wind Harmer
0.081
971447AH1-217 GEN
Solar/Wind Harmer
4.064
316411AF1-147_GEN1
Solar/Wind Helper
0.945
316415AF1-147_GEN2
Solar/Wind Helper
0.945
3141426STAFORD
Solar/Wind Helper
0.055
316468AD1-105 GEN
Solar/Wind Harmer
-0.067
963191AG1-168 GEN
Solar/Wind Harmer
0.81
3144293JTRSVLE
Adder
0.645
3144293JTRSVLE
Adder
0.543
3143526WINTERP
Solar/Wind Harmer
0.968
270013AE1-250 PV
Solar/Wind Harmer
0.004
315821AE2-092 GEN
Solar/Wind Harmer
0.008
NYPJM->LTFIMP_NY
CLTF
4.044
LGEELTFEXP_LGEE->PJM
CLTF
2.658
WECLTFEXP_WEC->PJM
CLTF
1.346
AG2-052LTFEXP_AG2-052->PJM
LTF
0.074
AH1-155LTFEXP_AH1-155->PJM
LTF
0.112
LAGNLTFEXP_LAGN->PJM
CLTF
12.709
CBM South 2LTFEXP_CBM-S2->PJM
CBM
34.309
TVALTFEXP_TVA->PJM
CLTF
6.437
CPLELTFEXP_CPLE->PJM
CLTF
15.123
CBM West 2LTFEXP_CBM-W2->PJM
CBM
70.159
CBM West 1LTFEXP_CBM-W1->PJM
CBM
47.354
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.437
MECLTFEXP_MEC->PJM
CLTF
6.883
SIGELTFEXP_SIGE->PJM
CLTF
0.213

Details for 8VALLEY SC-8VALLEY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 555_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
8VALLEY SC-8VALLEY 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 555_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:112.01 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3607.13
MW Contribution:3.33
Bus #Bus NameTypeMW Contribution
270205AE1-176
50/50
0.004
970479AG2-310 GEN
50/50
14.12
971367AH1-164 GEN
Solar/Wind Harmer
3.331
3151861LOWMORA
50/50
3.918
24734805WLF1G4
Adder
4.975
3152061BATH 6F
50/50
16.44
970823AG2-518 GEN
50/50
5.734
958121AF2-106 GEN
Solar/Wind Harmer
0.001
247619Y1-049
Adder
0.574
971331AH1-145 GEN
Solar/Wind Harmer
12.171
270346AE1-212 GEN
Solar/Wind Harmer
5.915
970223AG2-152 GEN
Solar/Wind Harmer
8.195
3152041BATH 4D
50/50
16.352
3151881LOWMORC
50/50
4.046
3151881LOWMORC
50/50
3.982
966391AG1-508 GEN
Solar/Wind Harmer
1.299
270069AE2-166 C O1
Solar/Wind Harmer
0.005
24734705WLF1G3
Adder
4.975
24734905WLF1G5
Adder
4.975
3148013FISHERV
Solar/Wind Helper
0.175
24290705CLAY-2
50/50
0.172
24290705CLAY-2
50/50
0.172
971277AH1-098 GEN
Solar/Wind Harmer
3.383
24728205BUCHG1
Adder
4.101
962751AG1-124 GEN
Solar/Wind Harmer
9.115
3147312GRETNA
Solar/Wind Harmer
0.129
3146802CHATHAM
Solar/Wind Harmer
0.121
270016AE1-250 BESS
Solar/Wind Harmer
0.004
3147983MERCK5
Solar/Wind Helper
0.146
3152051BATH 5E
50/50
16.369
3151861LOWMORA
50/50
4.078
3137383CUSHAW
50/50
0.078
24290605CLAY-1
50/50
0.172
24290605CLAY-1
50/50
0.172
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.002
942671AE2-283 GEN
Solar/Wind Harmer
4.021
3132123MT JACKSON
Solar/Wind Helper
1.116
943031AE2-326 GEN
Solar/Wind Harmer
4.43
3147123OTTER R
Solar/Wind Harmer
0.09
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
270030AE2-140 GEN
Solar/Wind Harmer
14.108
960911AF2-382 GEN
Solar/Wind Harmer
4.593
941821AE2-187 GEN
Solar/Wind Harmer
5.17
270197AD1-017 GEN1
Solar/Wind Harmer
0.974
270336AE1-100 GEN
Solar/Wind Harmer
0.004
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
316499AE2-029_GEN
Solar/Wind Helper
1.225
3147312GRETNA
Solar/Wind Harmer
0.032
23583801GRNGAP
Solar/Wind Helper
3.885
237061AD1-155 GEN
Solar/Wind Helper
0.042
971329AH1-144 GEN
Solar/Wind Harmer
7.668
958131AF2-107 GEN
Solar/Wind Harmer
3.843
270173AC1-122 GEN
Solar/Wind Harmer
0.472
941801AE2-185 GEN
Solar/Wind Harmer
5.17
3152011BATH 1A
50/50
16.383
3152021BATH 2B
50/50
16.383
3152031BATH 3C
50/50
16.378
3148463FAIRFLD
Solar/Wind Harmer
0.358
3138266HYDRAULIC
Solar/Wind Helper
0.012
3138266HYDRAULIC
Solar/Wind Helper
0.007
24288905REUSENS
50/50
0.04
315616AA1-038_C
Solar/Wind Harmer
0.003
270018AE2-047 C O1
Solar/Wind Harmer
0.003
24728305BUCHG2
Adder
4.101
3148013FISHERV
Solar/Wind Helper
0.304
270583AD2-179 GEN
Solar/Wind Harmer
9.708
971543AH1-269 GEN
50/50
8.257
971313AH1-133 GEN
Solar/Wind Harmer
6.761
3148133STUARTS
Solar/Wind Helper
0.182
270013AE1-250 PV
Solar/Wind Harmer
0.004
NYPJM->LTFIMP_NY
CLTF
2.909
LGEELTFEXP_LGEE->PJM
CLTF
3.588
WECLTFEXP_WEC->PJM
CLTF
1.753
AG2-052LTFEXP_AG2-052->PJM
LTF
0.104
AH1-155LTFEXP_AH1-155->PJM
LTF
0.155
LAGNLTFEXP_LAGN->PJM
CLTF
11.387
CBM South 2LTFEXP_CBM-S2->PJM
CBM
14.911
TVALTFEXP_TVA->PJM
CLTF
6.03
CPLELTFEXP_CPLE->PJM
CLTF
3.393
CBM West 2LTFEXP_CBM-W2->PJM
CBM
71.784
CBM West 1LTFEXP_CBM-W1->PJM
CBM
62.503
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.099
MECLTFEXP_MEC->PJM
CLTF
8.174
SIGELTFEXP_SIGE->PJM
CLTF
0.27

Details for 8VALLEY SC-8VALLEY 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2168-555_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
8VALLEY SC-8VALLEY 500.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2168-555_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:105.23 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4145.88
MW Contribution:5.35
Bus #Bus NameTypeMW Contribution
270205AE1-176
50/50
0.005
970479AG2-310 GEN
50/50
15.892
971367AH1-164 GEN
Solar/Wind Harmer
5.352
941821AE2-187 GEN
Solar/Wind Harmer
7.544
270197AD1-017 GEN1
Solar/Wind Harmer
1.927
270336AE1-100 GEN
Solar/Wind Harmer
2.02
943811AF1-049 GEN
Solar/Wind Harmer
4.147
24735205WLF2G2
Adder
5.48
316499AE2-029_GEN
Solar/Wind Helper
1.577
316095T157 G97
Solar/Wind Helper
1.082
3152051BATH 5E
50/50
17.355
3137383CUSHAW
50/50
0.134
3151861LOWMORA
50/50
7.039
971329AH1-144 GEN
Solar/Wind Harmer
17.696
958131AF2-107 GEN
Solar/Wind Harmer
5.403
971403AH1-188 GEN
Solar/Wind Harmer
12.187
3132273ORANGE
Solar/Wind Helper
0.051
316170AC1-121 GEN2
Solar/Wind Helper
0.36
24288905REUSENS
50/50
0.045
315616AA1-038_C
Solar/Wind Harmer
14.233
270018AE2-047 C O1
Solar/Wind Harmer
1.338
24728305BUCHG2
Adder
4.634
3148013FISHERV
Solar/Wind Helper
0.457
3147666LOUISA
Solar/Wind Helper
0.577
238147AE2-230_GEN1
Solar/Wind Helper
0.401
943031AE2-326 GEN
Solar/Wind Harmer
4.99
3147123OTTER R
Solar/Wind Harmer
-0.011
270574AD1-017 GEN2
Solar/Wind Harmer
6.414
270030AE2-140 GEN
Solar/Wind Harmer
22.569
960911AF2-382 GEN
Solar/Wind Harmer
7.443
316192AB2-158 GEN
Solar/Wind Helper
1.696
316097T157 G90
Solar/Wind Helper
1.082
316336AC2-165 C
Solar/Wind Helper
1.208
3152061BATH 6F
50/50
17.43
970823AG2-518 GEN
50/50
6.455
958121AF2-106 GEN
Solar/Wind Harmer
7.115
247619Y1-049
Adder
0.646
971331AH1-145 GEN
Solar/Wind Harmer
13.718
270346AE1-212 GEN
Solar/Wind Harmer
9.778
970223AG2-152 GEN
Solar/Wind Harmer
12.909
971461AH1-227 GEN
Solar/Wind Harmer
4.678
3147666LOUISA
Solar/Wind Helper
1.004
316254AC1-120 GEN1
Solar/Wind Helper
1.079
24290605CLAY-1
50/50
0.194
24290605CLAY-1
50/50
0.194
316217AC1-145 GEN
Solar/Wind Harmer
3.265
316197AC1-042 GEN
Solar/Wind Harmer
2.475
942671AE2-283 GEN
Solar/Wind Harmer
6.664
3132123MT JACKSON
Solar/Wind Helper
1.31
966001AG1-469 GEN
Solar/Wind Helper
0.292
962751AG1-124 GEN
Solar/Wind Harmer
14.726
3147312GRETNA
Solar/Wind Harmer
-0.016
3146802CHATHAM
Solar/Wind Harmer
-0.015
270016AE1-250 BESS
Solar/Wind Harmer
2.411
3147983MERCK5
Solar/Wind Helper
0.183
3152011BATH 1A
50/50
17.37
3152021BATH 2B
50/50
17.37
3152031BATH 3C
50/50
17.364
3148463FAIRFLD
Solar/Wind Harmer
-0.069
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.011
3151861LOWMORA
50/50
6.765
24734805WLF1G4
Adder
5.613
24735105WLF2G1
Adder
5.48
23546401DTGZ2-030
Solar/Wind Helper
0.075
238152AF2-075_GEN
Solar/Wind Helper
0.572
316164AC1-076 GEN
Solar/Wind Helper
1.095
971543AH1-269 GEN
50/50
9.298
971313AH1-133 GEN
Solar/Wind Harmer
10.943
270132AB1-180 C
Adder
0.114
3148133STUARTS
Solar/Wind Helper
0.274
24290705CLAY-2
50/50
0.194
24290705CLAY-2
50/50
0.194
971277AH1-098 GEN
Solar/Wind Harmer
5.461
24728205BUCHG1
Adder
4.634
270013AE1-250 PV
Solar/Wind Harmer
2.411
315821AE2-092 GEN
Solar/Wind Helper
2.895
3147312GRETNA
Solar/Wind Harmer
-0.004
971687AH1-348 GEN
Solar/Wind Harmer
0.906
237061AD1-155 GEN
Solar/Wind Helper
0.047
23583801GRNGAP
Solar/Wind Helper
4.125
238149AF1-291A_GEN
Solar/Wind Helper
0.114
270583AD2-179 GEN
Solar/Wind Harmer
15.671
270214AC2-123 GEN
Solar/Wind Harmer
3.17
971225AH1-072 GEN
Solar/Wind Harmer
1.824
971227AH1-073 GEN
Solar/Wind Harmer
1.824
315651AD1-115 GEN
Solar/Wind Helper
0.781
270173AC1-122 GEN
Solar/Wind Harmer
2.55
941801AE2-185 GEN
Solar/Wind Harmer
7.544
970913AG2-568 GEN
Solar/Wind Harmer
7.285
238148AE2-230_GEN2
Solar/Wind Helper
0.402
3152041BATH 4D
50/50
17.337
3151881LOWMORC
50/50
6.984
3151881LOWMORC
50/50
6.875
966391AG1-508 GEN
Solar/Wind Harmer
4.68
270069AE2-166 C O1
Solar/Wind Harmer
3.325
24734705WLF1G3
Adder
5.613
24734905WLF1G5
Adder
5.613
3148013FISHERV
Solar/Wind Helper
0.263
NYPJM->LTFIMP_NY
CLTF
3.2
LGEELTFEXP_LGEE->PJM
CLTF
4.095
WECLTFEXP_WEC->PJM
CLTF
2.007
AG2-052LTFEXP_AG2-052->PJM
LTF
0.119
AH1-155LTFEXP_AH1-155->PJM
LTF
0.178
LAGNLTFEXP_LAGN->PJM
CLTF
12.827
CBM South 2LTFEXP_CBM-S2->PJM
CBM
16.289
TVALTFEXP_TVA->PJM
CLTF
6.791
CPLELTFEXP_CPLE->PJM
CLTF
3.547
CBM West 2LTFEXP_CBM-W2->PJM
CBM
81.312
CBM West 1LTFEXP_CBM-W1->PJM
CBM
71.759
CBM South 1LTFEXP_CBM-S1->PJM
CBM
24.94
MECLTFEXP_MEC->PJM
CLTF
9.322
SIGELTFEXP_SIGE->PJM
CLTF
0.308
CONTINGENCY 'AP_P1-3_MP-765-501T_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1   /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                   /*05BELMON     765.0
END
CONTINGENCY 'AP_P2-3_MP-500-020_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 1          /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 2          /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5          /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1          /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1          /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                          /*05BELMON     765.0
 SET POSTCONTRATING 2492 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
 SET PRECONTRATING 1986 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
END
CONTINGENCY 'AP_P2-3_MP-500-021_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 3          /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5          /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1          /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1          /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                          /*05BELMON     765.0
 SET POSTCONTRATING 2492 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
 SET PRECONTRATING 1986 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
END
CONTINGENCY 'AEP_P4_#37_05MOUNTN 765_B1_SRT-A'
 OPEN BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242516 TO BUS 242920 CKT 1   /*05MOUNTN     765.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
END
CONTINGENCY 'AEP_P4_#2942_05KAMMER 765_PP_SRT-A'
 OPEN BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242516 TO BUS 242920 CKT 1   /*05MOUNTN     765.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
 OPEN BRANCH FROM BUS 242925 TO BUS 243188 CKT 1   /*05KAMMER     765.0 - 05MLG1        26.0
 REMOVE UNIT 1 FROM BUS 243188                     /*05MLG1        26.0
END
CONTINGENCY 'AEP_P4_#7445_05MARYSV 765_B_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290621 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RF 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 962760 TO BUS 290621 CKT 1    /*AG1-125 TP   765.0 - 05MARYSVL_RF 765.0
END
CONTINGENCY 'AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1   /*05CLOVRD     500.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'AEP_P1-2_#7422_16_SRT-A'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1   /*05CLOVRD     500.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'AEP_P7-1_#10944___SRT-A'
 OPEN BRANCH FROM BUS 242528 TO BUS 242940 CKT 1   /*05SPORN      345.0 - 05MUSKNG     345.0
 OPEN BRANCH FROM BUS 242940 TO BUS 242947 CKT 1   /*05MUSKNG     345.0 - 05WATERFORD  345.0
END
CONTINGENCY 'AEP_P7-1_#10856___SRT-A'
 OPEN BRANCH FROM BUS 242528 TO BUS 242940 CKT 1   /*05SPORN      345.0 - 05MUSKNG     345.0
 OPEN BRANCH FROM BUS 242528 TO BUS 242947 CKT 1   /*05SPORN      345.0 - 05WATERFORD  345.0
END
CONTINGENCY 'DVP_P4-2: 509T570_SRT-A'
 OPEN BRANCH FROM BUS 314935 TO BUS 314945 CKT 1   /*8HERITAGE    500.0 - 8BRUNSWICK   500.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315102 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKG1  21.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315103 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKG2  21.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315104 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKG3  21.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315105 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKS1  19.0
 OPEN BRANCH FROM BUS 970916 TO BUS 314935 CKT 1   /*AG2-570 TP   500.0 - 8HERITAGE    500.0
 OPEN BUS 314945                                   /*8BRUNSWICK   500.0
 OPEN BUS 315102                                   /*1BRUNSWICKG1  21.0
 OPEN BUS 315103                                   /*1BRUNSWICKG2  21.0
 OPEN BUS 315104                                   /*1BRUNSWICKG3  21.0
 OPEN BUS 315105                                   /*1BRUNSWICKS1  19.0
END
CONTINGENCY 'DVP_P1-2: LN 570_SRT-A-3'
 OPEN BRANCH FROM BUS 970916 TO BUS 314935 CKT 1   /*AG2-570 TP   500.0 - 8HERITAGE    500.0
END
CONTINGENCY 'DVP_P1-2: LN 570_SRT-A-2'
 OPEN BRANCH FROM BUS 970916 TO BUS 970084 CKT 1   /*AG2-570 TP   500.0 - AG2-068 TP   500.0
END
CONTINGENCY 'DVP_P4-2: 57062_SRT-S'
 OPEN BRANCH FROM BUS 970916 TO BUS 314935 CKT 1                /*AG2-570 TP   500.0 - 8HERITAGE    500.0
 SET POSTCONTRATING 3464 BRANCH FROM BUS 314935 TO BUS 314940 CKT 1 /*8HERITAGE    500.0 - 8ROGERS RD   500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3464 BRANCH FROM BUS 314935 TO BUS 314940 CKT 1 /*8HERITAGE    500.0 - 8ROGERS RD   500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P1-2: LN 555_SRT-A'
 OPEN BRANCH FROM BUS 314907 TO BUS 314912 CKT 1   /*8DOOMS       500.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'DVP_P7-1: LN 2168-555_SRT-A'
 OPEN BRANCH FROM BUS 314794 TO BUS 314854 CKT 1   /*6DOOMS       230.0 - 6LEXNGT1     230.0
 OPEN BRANCH FROM BUS 314907 TO BUS 314912 CKT 1   /*8DOOMS       500.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'DVP_P1-2: LN 576_SRT-S'
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1   /*8MDLTHAN     500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P1-2: LN 563_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
242519 to 314912 ckt 1
242516 to 242920 ckt 1
315684 to 314690 ckt 1
304070 to 316281 ckt 1
314697 to 315684 ckt 1
314901 to 314991 ckt 1
314908 to 314911 ckt 1
314991 to 314926 ckt 1

Winter Peak Analysis

The New Service Request AH1-164 was evaluated as a 35.0 MW (21.0 MW Capacity) injection in the AEP area.

AH1-164 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 35.0 MW (35.0 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2CPLE/DVP
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P4-2: 509T570_SRT-A
BreakerAC143.28 %694.0B994.380.1
GD2CPLE/DVP
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P1-2: LN 570_SRT-A-3
SingleAC136.4 %652.36B889.840.1
GD2CPLE/DVP
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P1-2: LN 570_SRT-A-2
SingleAC134.99 %652.36B880.620.1
GD2CPLE/DVP
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P4-2: 57062_SRT-W
BreakerAC130.48 %694.0B905.50.1
IPDCPLE/DVP
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P4-2: 509T570_SRT-A
BreakerAC106.37 %694.0B738.182.0

Details for 6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 509T570_SRT-A


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 509T570_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:143.28 %
Rating:694.0 MVA
Rating Type:B
MVA to Mitigate:994.38
MW Contribution:0.1
Bus #Bus NameTypeMW Contribution
3147043LAWRENC
Solar/Wind Helper
0.153
3147133PAMPLIN
Solar/Wind Helper
1.357
3147133PAMPLIN
Solar/Wind Helper
0.346
3147133PAMPLIN
Solar/Wind Helper
0.432
3143316POE
Solar/Wind Helper
0.789
3145506HICKORY
Solar/Wind Helper
0.729
3145506HICKORY
Solar/Wind Helper
0.438
3145506HICKORY
Solar/Wind Helper
0.109
3146776BUCKING
Solar/Wind Helper
1.198
3146776BUCKING
Solar/Wind Helper
0.097
3146776BUCKING
Solar/Wind Helper
0.108
3146776BUCKING
Solar/Wind Helper
0.12
3143226MDLTHAN
Solar/Wind Helper
0.18
3146843MT LREL
Solar/Wind Helper
0.804
3146843MT LREL
Solar/Wind Helper
0.804
3146926FARMVIL
Solar/Wind Helper
0.225
3146926FARMVIL
Solar/Wind Helper
0.225
3147123OTTER R
Solar/Wind Helper
0.119
316034AC1-036 C
Solar/Wind Helper
0.104
316036AC1-147 C
Solar/Wind Helper
0.061
316159AE1-175 C
Solar/Wind Helper
0.057
316240AF1-291 C
Solar/Wind Helper
0.059
316248AF1-058 C
Solar/Wind Helper
0.327
316258AE1-075 C
Solar/Wind Helper
0.055
316316AC1-027 C
Solar/Wind Helper
0.053
316336AC2-165 C
Solar/Wind Helper
0.312
316382AG1-145 C
Solar/Wind Helper
0.057
316405AF2-144 C
Solar/Wind Helper
0.052
3145336SMITFLD
Solar/Wind Helper
0.738
3145336SMITFLD
Solar/Wind Helper
0.074
3147243WELCO
Solar/Wind Helper
0.636
316017AA1-139 ULT1
Solar/Wind Helper
0.169
316018AA1-139 ULT2
Solar/Wind Helper
0.016
316033AB2-134 GEN
Solar/Wind Helper
0.412
316388AE2-253 GEN
Solar/Wind Helper
0.142
3144303KENBRDG
Solar/Wind Helper
0.376
3147173SINAI
Solar/Wind Helper
1.018
316369SG1_INVT
Solar/Wind Helper
0.284
315839AE2-212 C
Solar/Wind Helper
0.061
315697AD1-025 GEN
Solar/Wind Helper
0.434
316185AD1-033 GEN
Solar/Wind Helper
0.208
316478AD1-087 GEN
Solar/Wind Helper
0.737
316486AD2-202 GEN
Solar/Wind Helper
0.216
315687AD1-152 GEN
Solar/Wind Helper
1.268
315785AD2-033 C
Solar/Wind Helper
0.995
316313AB2-026
Solar/Wind Helper
0.061
270030AE2-140 GEN
Solar/Wind Harmer
0.914
313527AB2-043 GEN
Solar/Wind Helper
0.404
316322AB2-045
Solar/Wind Helper
0.095
316359AB2-059 GEN
Solar/Wind Harmer
0
316131AB2-060 GEN
Solar/Wind Helper
0.644
316083AB2-161 GEN
Solar/Wind Helper
0.146
316132AB2-190 GEN1
Solar/Wind Helper
0.216
316458AB2-190 GEN2
Solar/Wind Helper
0.216
316123AC1-075 GEN
Solar/Wind Helper
0.801
316375AC2-012 GEN
Solar/Wind Helper
0.357
316339AD2-160 GEN
Solar/Wind Helper
0.142
316239AB2-077_GEN
Solar/Wind Helper
0.164
316238AB2-078_GEN
Solar/Wind Helper
0.164
316237AB2-079_GEN
Solar/Wind Helper
0.164
316381AD1-082 GEN
Solar/Wind Helper
0.199
316236AE1-162_GEN
Solar/Wind Helper
0.059
3145543BTLEBRO
Solar/Wind Harmer
-0.146
3145543BTLEBRO
Solar/Wind Harmer
-0.183
3145543BTLEBRO
Solar/Wind Harmer
-0.183
3145543BTLEBRO
Solar/Wind Harmer
-0.183
3138543CONSLDL
Solar/Wind Harmer
-0.098
3142053HEARTS
Solar/Wind Harmer
0.006
3144536CHRHLND
Solar/Wind Helper
0.028
3144873MCLAUGH
Solar/Wind Helper
0.005
3145453TOT5
Solar/Wind Harmer
0.004
3145493TOT1
Solar/Wind Harmer
0.014
3145493TOT1
Solar/Wind Harmer
0.007
3145573BETHELC
Solar/Wind Harmer
-0.161
3145573BETHELC
Solar/Wind Harmer
-0.161
3145603CNETO
Solar/Wind Harmer
0.003
3146073TAR RVR
Solar/Wind Harmer
-0.161
3146083TARBORO
Solar/Wind Harmer
-0.161
3146083TARBORO
Solar/Wind Harmer
-0.161
3146233WITAKRS
Solar/Wind Harmer
0.03
3146233WITAKRS
Solar/Wind Harmer
-0.575
3146233WITAKRS
Solar/Wind Harmer
-0.098
942461AE2-259 GEN
Solar/Wind Helper
0.651
943811AF1-049 GEN
Solar/Wind Harmer
0
961601AG1-000A GEN
Solar/Wind Harmer
0.329
961601AG1-000A GEN
Solar/Wind Harmer
5.263
961611AG1-000B GEN
Solar/Wind Helper
0.259
970085AG2-068 GEN
Solar/Wind Harmer
0.764
970087AG2-069 GEN
Solar/Wind Harmer
1.146
970223AG2-152 GEN
Solar/Wind Harmer
0.735
970581AG2-369 GEN
Solar/Wind Harmer
0.657
970917AG2-570 GEN
Solar/Wind Harmer
3.057
970919AG2-571 GEN
Solar/Wind Harmer
6.113
971367AH1-164 GEN
Solar/Wind Harmer
0.1
971629AH1-314 GEN
50/50
15.356
971981AH1-535 GEN
Solar/Wind Harmer
0.293
315773AC2-141 GEN
Solar/Wind Helper
0.792
316003AC1-222 GEN
Solar/Wind Helper
0.97
316118AC1-105 GEN
Solar/Wind Helper
0.747
316129AC1-054 GEN
Solar/Wind Helper
0.253
316222AC1-221 GEN
Solar/Wind Helper
2.596
316263AC1-034 GEN
Solar/Wind Harmer
0.241
316283AC2-100 C
Solar/Wind Helper
2.444
316294AC1-161 GEN
Solar/Wind Helper
0.792
900033ID_568986
External Queue
0.2332763522863388
CBM West 1LTFEXP_CBM-W1->PJM
CBM
42.454
CBM West 2LTFEXP_CBM-W2->PJM
CBM
57.31
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.037
CBM South 2LTFEXP_CBM-S2->PJM
CBM
30.468
NYPJM->LTFIMP_NY
CLTF
0.617
LGEELTFEXP_LGEE->PJM
CLTF
2.103
WECLTFEXP_WEC->PJM
CLTF
1.136
CPLELTFEXP_CPLE->PJM
CLTF
13.823
TVALTFEXP_TVA->PJM
CLTF
5.181
MECLTFEXP_MEC->PJM
CLTF
5.746
LAGNLTFEXP_LAGN->PJM
CLTF
10.439
SIGELTFEXP_SIGE->PJM
CLTF
0.173
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
4.495
AG2-052LTFEXP_AG2-052->PJM
LTF
0.064
AH1-155LTFEXP_AH1-155->PJM
LTF
0.095

Details for 6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 570_SRT-A-3


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:136.4 %
Rating:652.36 MVA
Rating Type:B
MVA to Mitigate:889.84
MW Contribution:0.1
Bus #Bus NameTypeMW Contribution
3147043LAWRENC
Solar/Wind Helper
0.151
3147133PAMPLIN
Solar/Wind Helper
1.348
3147133PAMPLIN
Solar/Wind Helper
0.343
3147133PAMPLIN
Solar/Wind Helper
0.429
3137176SLIGO L2192
Solar/Wind Helper
0.678
3142433PROV 92
Solar/Wind Helper
0.666
3143316POE
Solar/Wind Helper
0.777
3145506HICKORY
Solar/Wind Helper
0.717
3145506HICKORY
Solar/Wind Helper
0.43
3145506HICKORY
Solar/Wind Helper
0.108
3146776BUCKING
Solar/Wind Helper
1.185
3146776BUCKING
Solar/Wind Helper
0.096
3146776BUCKING
Solar/Wind Helper
0.107
3146776BUCKING
Solar/Wind Helper
0.119
316075AC2-137 C
Solar/Wind Helper
0.052
3138133OCRAN
Solar/Wind Helper
0.049
3138133OCRAN
Solar/Wind Helper
0.098
3141766HARMONY
Solar/Wind Helper
0.033
3141783LANCAST
Solar/Wind Helper
0.098
3141783LANCAST
Solar/Wind Helper
0.065
3141913WHIT STONE
Solar/Wind Helper
0.164
3143226MDLTHAN
Solar/Wind Helper
0.177
3143873LANEXA
Solar/Wind Helper
0.099
3146456SLIGO L269
Solar/Wind Helper
0.17
3146456SLIGO L269
Solar/Wind Helper
0.17
3146843MT LREL
Solar/Wind Helper
0.801
3146843MT LREL
Solar/Wind Helper
0.801
3146926FARMVIL
Solar/Wind Helper
0.223
3146926FARMVIL
Solar/Wind Helper
0.223
3147123OTTER R
Solar/Wind Helper
0.117
3141726DUNNSVL
Solar/Wind Helper
0.624
316034AC1-036 C
Solar/Wind Helper
0.104
316036AC1-147 C
Solar/Wind Helper
0.06
316059AD1-063 C
Solar/Wind Helper
0.04
316159AE1-175 C
Solar/Wind Helper
0.056
316240AF1-291 C
Solar/Wind Helper
0.058
316246AF1-032 C
Solar/Wind Helper
0.041
316248AF1-058 C
Solar/Wind Helper
0.326
316258AE1-075 C
Solar/Wind Helper
0.054
316305AF2-043 C
Solar/Wind Helper
0.054
316314AB2-024 C
Solar/Wind Helper
0.053
316315AB2-025 C
Solar/Wind Helper
0.055
316316AC1-027 C
Solar/Wind Helper
0.052
316336AC2-165 C
Solar/Wind Helper
0.307
316382AG1-145 C
Solar/Wind Helper
0.056
316405AF2-144 C
Solar/Wind Helper
0.051
3145336SMITFLD
Solar/Wind Helper
0.726
3145336SMITFLD
Solar/Wind Helper
0.073
3147243WELCO
Solar/Wind Helper
0.634
3141873WAN 176
Solar/Wind Helper
0.033
3143526WINTERP
Solar/Wind Helper
0.894
3143526WINTERP
Solar/Wind Helper
0.894
316404AE1-155 C
Solar/Wind Helper
0.323
316017AA1-139 ULT1
Solar/Wind Helper
0.166
316018AA1-139 ULT2
Solar/Wind Helper
0.166
316033AB2-134 GEN
Solar/Wind Helper
0.405
316388AE2-253 GEN
Solar/Wind Helper
0.14
3142543TWELFTH
Solar/Wind Helper
0.016
3144303KENBRDG
Solar/Wind Helper
0.374
3147173SINAI
Solar/Wind Helper
1.015
316203AE2-005 GEN
Solar/Wind Helper
0.345
316441AF1-014 GEN
Solar/Wind Helper
0.053
316484AD2-074 GEN
Solar/Wind Helper
0.221
315833AF1-017_GEN
Solar/Wind Helper
0.109
316369SG1_INVT
Solar/Wind Helper
0.279
316487AF1-042 GEN
Solar/Wind Helper
0.116
315839AE2-212 C
Solar/Wind Helper
0.06
315662AE1-191 GEN
Solar/Wind Helper
0.213
315666AE1-190 GEN
Solar/Wind Helper
0.053
319010AE1-072 C
Solar/Wind Helper
0.407
315697AD1-025 GEN
Solar/Wind Helper
0.427
316185AD1-033 GEN
Solar/Wind Helper
0.205
316280AD1-041 GEN
Solar/Wind Helper
0.133
316478AD1-087 GEN
Solar/Wind Helper
0.734
316486AD2-202 GEN
Solar/Wind Helper
0.215
316072AD1-144
Solar/Wind Helper
0.041
315687AD1-152 GEN
Solar/Wind Helper
1.264
316156AD2-030 GEN
Solar/Wind Helper
0.053
315785AD2-033 C
Solar/Wind Helper
0.988
316313AB2-026
Solar/Wind Helper
0.06
270030AE2-140 GEN
Solar/Wind Harmer
0.924
316349AD2-085 GEN
Solar/Wind Helper
0.139
313527AB2-043 GEN
Solar/Wind Helper
0.402
316322AB2-045
Solar/Wind Helper
0.094
316359AB2-059 GEN
Solar/Wind Harmer
0
316131AB2-060 GEN
Solar/Wind Helper
0.64
316083AB2-161 GEN
Solar/Wind Helper
0.144
316132AB2-190 GEN1
Solar/Wind Helper
0.212
316458AB2-190 GEN2
Solar/Wind Helper
0.212
316123AC1-075 GEN
Solar/Wind Helper
0.797
316375AC2-012 GEN
Solar/Wind Helper
0.351
316339AD2-160 GEN
Solar/Wind Helper
0.14
316239AB2-077_GEN
Solar/Wind Helper
0.163
316238AB2-078_GEN
Solar/Wind Helper
0.163
316237AB2-079_GEN
Solar/Wind Helper
0.163
316381AD1-082 GEN
Solar/Wind Helper
0.195
316233AE1-074 FULL
Solar/Wind Helper
0.055
316236AE1-162_GEN
Solar/Wind Helper
0.058
3145543BTLEBRO
Solar/Wind Harmer
-0.149
3145543BTLEBRO
Solar/Wind Harmer
-0.186
3145543BTLEBRO
Solar/Wind Harmer
-0.186
3145543BTLEBRO
Solar/Wind Harmer
-0.186
3130086AYDLETT
Solar/Wind Helper
0.672
3138543CONSLDL
Solar/Wind Harmer
-0.1
3142053HEARTS
Solar/Wind Harmer
0.006
3142946ENON
Solar/Wind Helper
0.017
3142946ENON
Solar/Wind Helper
0.056
3144536CHRHLND
Solar/Wind Helper
0.028
3144873MCLAUGH
Solar/Wind Helper
0.005
3145453TOT5
Solar/Wind Harmer
0.004
3145493TOT1
Solar/Wind Harmer
0.014
3145493TOT1
Solar/Wind Harmer
0.007
3145573BETHELC
Solar/Wind Harmer
-0.164
3145573BETHELC
Solar/Wind Harmer
-0.164
3145603CNETO
Solar/Wind Harmer
0.003
3146073TAR RVR
Solar/Wind Harmer
-0.164
3146083TARBORO
Solar/Wind Harmer
-0.164
3146083TARBORO
Solar/Wind Harmer
-0.164
3146233WITAKRS
Solar/Wind Harmer
0.031
3146233WITAKRS
Solar/Wind Harmer
-0.586
3146233WITAKRS
Solar/Wind Harmer
-0.1
942461AE2-259 GEN
Solar/Wind Helper
0.646
943811AF1-049 GEN
Solar/Wind Harmer
0
961601AG1-000A GEN
Solar/Wind Harmer
0.334
961601AG1-000A GEN
Solar/Wind Harmer
5.342
961611AG1-000B GEN
Solar/Wind Helper
0.254
961951AG1-038 GEN
Solar/Wind Helper
0.116
970085AG2-068 GEN
Solar/Wind Harmer
0.769
970087AG2-069 GEN
Solar/Wind Harmer
1.154
970223AG2-152 GEN
Solar/Wind Harmer
0.742
970417AG2-272 GEN
50/50
2.037
970581AG2-369 GEN
Solar/Wind Harmer
0.661
970917AG2-570 GEN
Solar/Wind Harmer
3.076
970919AG2-571 GEN
Solar/Wind Harmer
6.153
971367AH1-164 GEN
Solar/Wind Harmer
0.102
971629AH1-314 GEN
50/50
15.454
957601AF2-054 GEN
Solar/Wind Helper
0.053
957831AF2-077 GEN
Solar/Wind Helper
0.055
964211AG1-282 GEN
Solar/Wind Helper
0.05
971981AH1-535 GEN
Solar/Wind Harmer
0.298
315773AC2-141 GEN
Solar/Wind Helper
0.78
316003AC1-222 GEN
Solar/Wind Helper
0.967
316118AC1-105 GEN
Solar/Wind Helper
0.744
316129AC1-054 GEN
Solar/Wind Helper
0.25
316222AC1-221 GEN
Solar/Wind Helper
2.592
316263AC1-034 GEN
Solar/Wind Harmer
0.245
316283AC2-100 C
Solar/Wind Helper
2.441
316294AC1-161 GEN
Solar/Wind Helper
0.78
944201AF1-088_MTX
Adder
35.265
900033ID_568986
External Queue
0.2332763522863388
CBM West 1LTFEXP_CBM-W1->PJM
CBM
43.691
CBM West 2LTFEXP_CBM-W2->PJM
CBM
58.452
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.359
CBM South 2LTFEXP_CBM-S2->PJM
CBM
30.725
NYPJM->LTFIMP_NY
CLTF
0.562
LGEELTFEXP_LGEE->PJM
CLTF
2.162
WECLTFEXP_WEC->PJM
CLTF
1.169
CPLELTFEXP_CPLE->PJM
CLTF
13.916
TVALTFEXP_TVA->PJM
CLTF
5.267
MECLTFEXP_MEC->PJM
CLTF
5.888
LAGNLTFEXP_LAGN->PJM
CLTF
10.611
SIGELTFEXP_SIGE->PJM
CLTF
0.177
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
4.495
AG2-052LTFEXP_AG2-052->PJM
LTF
0.066
AH1-155LTFEXP_AH1-155->PJM
LTF
0.098

Details for 6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 570_SRT-A-2


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:134.99 %
Rating:652.36 MVA
Rating Type:B
MVA to Mitigate:880.62
MW Contribution:0.1
Bus #Bus NameTypeMW Contribution
3147043LAWRENC
Solar/Wind Helper
0.151
3147133PAMPLIN
Solar/Wind Helper
1.348
3147133PAMPLIN
Solar/Wind Helper
0.343
3147133PAMPLIN
Solar/Wind Helper
0.429
3137176SLIGO L2192
Solar/Wind Helper
0.678
3142433PROV 92
Solar/Wind Helper
0.666
3143316POE
Solar/Wind Helper
0.777
3145506HICKORY
Solar/Wind Helper
0.717
3145506HICKORY
Solar/Wind Helper
0.43
3145506HICKORY
Solar/Wind Helper
0.108
3146776BUCKING
Solar/Wind Helper
1.185
3146776BUCKING
Solar/Wind Helper
0.096
3146776BUCKING
Solar/Wind Helper
0.107
3146776BUCKING
Solar/Wind Helper
0.119
316075AC2-137 C
Solar/Wind Helper
0.052
3138133OCRAN
Solar/Wind Helper
0.049
3138133OCRAN
Solar/Wind Helper
0.098
3141766HARMONY
Solar/Wind Helper
0.033
3141783LANCAST
Solar/Wind Helper
0.098
3141783LANCAST
Solar/Wind Helper
0.065
3141913WHIT STONE
Solar/Wind Helper
0.164
3143226MDLTHAN
Solar/Wind Helper
0.177
3143873LANEXA
Solar/Wind Helper
0.099
3146456SLIGO L269
Solar/Wind Helper
0.17
3146456SLIGO L269
Solar/Wind Helper
0.17
3146843MT LREL
Solar/Wind Helper
0.801
3146843MT LREL
Solar/Wind Helper
0.801
3146926FARMVIL
Solar/Wind Helper
0.223
3146926FARMVIL
Solar/Wind Helper
0.223
3147123OTTER R
Solar/Wind Helper
0.117
3141726DUNNSVL
Solar/Wind Helper
0.624
316034AC1-036 C
Solar/Wind Helper
0.104
316036AC1-147 C
Solar/Wind Helper
0.06
316059AD1-063 C
Solar/Wind Helper
0.04
316159AE1-175 C
Solar/Wind Helper
0.056
316240AF1-291 C
Solar/Wind Helper
0.058
316246AF1-032 C
Solar/Wind Helper
0.041
316248AF1-058 C
Solar/Wind Helper
0.326
316258AE1-075 C
Solar/Wind Helper
0.054
316305AF2-043 C
Solar/Wind Helper
0.054
316314AB2-024 C
Solar/Wind Helper
0.053
316315AB2-025 C
Solar/Wind Helper
0.055
316316AC1-027 C
Solar/Wind Helper
0.052
316336AC2-165 C
Solar/Wind Helper
0.307
316382AG1-145 C
Solar/Wind Helper
0.056
316405AF2-144 C
Solar/Wind Helper
0.051
3145336SMITFLD
Solar/Wind Helper
0.726
3145336SMITFLD
Solar/Wind Helper
0.073
3147243WELCO
Solar/Wind Helper
0.634
3141873WAN 176
Solar/Wind Helper
0.033
3143526WINTERP
Solar/Wind Helper
0.894
3143526WINTERP
Solar/Wind Helper
0.894
316404AE1-155 C
Solar/Wind Helper
0.323
316017AA1-139 ULT1
Solar/Wind Helper
0.166
316018AA1-139 ULT2
Solar/Wind Helper
0.166
316033AB2-134 GEN
Solar/Wind Helper
0.405
316388AE2-253 GEN
Solar/Wind Helper
0.14
3142543TWELFTH
Solar/Wind Helper
0.016
3144303KENBRDG
Solar/Wind Helper
0.374
3147173SINAI
Solar/Wind Helper
1.015
316203AE2-005 GEN
Solar/Wind Helper
0.345
316441AF1-014 GEN
Solar/Wind Helper
0.053
316484AD2-074 GEN
Solar/Wind Helper
0.221
315833AF1-017_GEN
Solar/Wind Helper
0.109
316369SG1_INVT
Solar/Wind Helper
0.279
316487AF1-042 GEN
Solar/Wind Helper
0.116
315839AE2-212 C
Solar/Wind Helper
0.06
315662AE1-191 GEN
Solar/Wind Helper
0.213
315666AE1-190 GEN
Solar/Wind Helper
0.053
319010AE1-072 C
Solar/Wind Helper
0.407
315697AD1-025 GEN
Solar/Wind Helper
0.427
316185AD1-033 GEN
Solar/Wind Helper
0.205
316280AD1-041 GEN
Solar/Wind Helper
0.133
316478AD1-087 GEN
Solar/Wind Helper
0.734
316486AD2-202 GEN
Solar/Wind Helper
0.215
316072AD1-144
Solar/Wind Helper
0.041
315687AD1-152 GEN
Solar/Wind Helper
1.264
316156AD2-030 GEN
Solar/Wind Helper
0.053
315785AD2-033 C
Solar/Wind Helper
0.988
316313AB2-026
Solar/Wind Helper
0.06
270030AE2-140 GEN
Solar/Wind Harmer
0.924
316349AD2-085 GEN
Solar/Wind Helper
0.139
313527AB2-043 GEN
Solar/Wind Helper
0.402
316322AB2-045
Solar/Wind Helper
0.094
316359AB2-059 GEN
Solar/Wind Harmer
0
316131AB2-060 GEN
Solar/Wind Helper
0.64
316083AB2-161 GEN
Solar/Wind Helper
0.144
316132AB2-190 GEN1
Solar/Wind Helper
0.212
316458AB2-190 GEN2
Solar/Wind Helper
0.212
316123AC1-075 GEN
Solar/Wind Helper
0.797
316375AC2-012 GEN
Solar/Wind Helper
0.351
316339AD2-160 GEN
Solar/Wind Helper
0.14
316239AB2-077_GEN
Solar/Wind Helper
0.163
316238AB2-078_GEN
Solar/Wind Helper
0.163
316237AB2-079_GEN
Solar/Wind Helper
0.163
316381AD1-082 GEN
Solar/Wind Helper
0.195
316233AE1-074 FULL
Solar/Wind Helper
0.055
316236AE1-162_GEN
Solar/Wind Helper
0.058
3145543BTLEBRO
Solar/Wind Harmer
-0.149
3145543BTLEBRO
Solar/Wind Harmer
-0.186
3145543BTLEBRO
Solar/Wind Harmer
-0.186
3145543BTLEBRO
Solar/Wind Harmer
-0.186
3130086AYDLETT
Solar/Wind Helper
0.672
3138543CONSLDL
Solar/Wind Harmer
-0.1
3142053HEARTS
Solar/Wind Harmer
0.006
3142946ENON
Solar/Wind Helper
0.017
3142946ENON
Solar/Wind Helper
0.056
3144536CHRHLND
Solar/Wind Helper
0.028
3144873MCLAUGH
Solar/Wind Helper
0.005
3145453TOT5
Solar/Wind Harmer
0.004
3145493TOT1
Solar/Wind Harmer
0.014
3145493TOT1
Solar/Wind Harmer
0.007
3145573BETHELC
Solar/Wind Harmer
-0.164
3145573BETHELC
Solar/Wind Harmer
-0.164
3145603CNETO
Solar/Wind Harmer
0.003
3146073TAR RVR
Solar/Wind Harmer
-0.164
3146083TARBORO
Solar/Wind Harmer
-0.164
3146083TARBORO
Solar/Wind Harmer
-0.164
3146233WITAKRS
Solar/Wind Harmer
0.031
3146233WITAKRS
Solar/Wind Harmer
-0.586
3146233WITAKRS
Solar/Wind Harmer
-0.1
942461AE2-259 GEN
Solar/Wind Helper
0.646
943811AF1-049 GEN
Solar/Wind Harmer
0
961601AG1-000A GEN
Solar/Wind Harmer
0.334
961601AG1-000A GEN
Solar/Wind Harmer
5.342
961611AG1-000B GEN
Solar/Wind Helper
0.254
961951AG1-038 GEN
Solar/Wind Helper
0.116
970085AG2-068 GEN
Solar/Wind Harmer
0.769
970087AG2-069 GEN
Solar/Wind Harmer
1.154
970223AG2-152 GEN
Solar/Wind Harmer
0.742
970417AG2-272 GEN
50/50
2.037
970581AG2-369 GEN
Solar/Wind Harmer
0.661
971367AH1-164 GEN
Solar/Wind Harmer
0.102
971629AH1-314 GEN
50/50
15.454
957601AF2-054 GEN
Solar/Wind Helper
0.053
957831AF2-077 GEN
Solar/Wind Helper
0.055
964211AG1-282 GEN
Solar/Wind Helper
0.05
971981AH1-535 GEN
Solar/Wind Harmer
0.298
315773AC2-141 GEN
Solar/Wind Helper
0.78
316003AC1-222 GEN
Solar/Wind Helper
0.967
316118AC1-105 GEN
Solar/Wind Helper
0.744
316129AC1-054 GEN
Solar/Wind Helper
0.25
316222AC1-221 GEN
Solar/Wind Helper
2.592
316263AC1-034 GEN
Solar/Wind Harmer
0.245
316283AC2-100 C
Solar/Wind Helper
2.441
316294AC1-161 GEN
Solar/Wind Helper
0.78
944201AF1-088_MTX
Adder
35.265
900033ID_568986
External Queue
0.2332763522863388
CBM West 1LTFEXP_CBM-W1->PJM
CBM
43.691
CBM West 2LTFEXP_CBM-W2->PJM
CBM
58.452
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.359
CBM South 2LTFEXP_CBM-S2->PJM
CBM
30.725
NYPJM->LTFIMP_NY
CLTF
0.562
LGEELTFEXP_LGEE->PJM
CLTF
2.162
WECLTFEXP_WEC->PJM
CLTF
1.169
CPLELTFEXP_CPLE->PJM
CLTF
13.916
TVALTFEXP_TVA->PJM
CLTF
5.267
MECLTFEXP_MEC->PJM
CLTF
5.888
LAGNLTFEXP_LAGN->PJM
CLTF
10.611
SIGELTFEXP_SIGE->PJM
CLTF
0.177
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
4.495
AG2-052LTFEXP_AG2-052->PJM
LTF
0.066
AH1-155LTFEXP_AH1-155->PJM
LTF
0.098

Details for 6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57062_SRT-W


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 57062_SRT-W
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:130.48 %
Rating:694.0 MVA
Rating Type:B
MVA to Mitigate:905.5
MW Contribution:0.1
Bus #Bus NameTypeMW Contribution
3147043LAWRENC
Solar/Wind Helper
0.151
3147133PAMPLIN
Solar/Wind Helper
1.348
3147133PAMPLIN
Solar/Wind Helper
0.343
3147133PAMPLIN
Solar/Wind Helper
0.429
3137176SLIGO L2192
Solar/Wind Helper
0.678
3142433PROV 92
Solar/Wind Helper
0.666
3143316POE
Solar/Wind Helper
0.777
3145506HICKORY
Solar/Wind Helper
0.717
3145506HICKORY
Solar/Wind Helper
0.43
3145506HICKORY
Solar/Wind Helper
0.108
3146776BUCKING
Solar/Wind Helper
1.185
3146776BUCKING
Solar/Wind Helper
0.096
3146776BUCKING
Solar/Wind Helper
0.107
3146776BUCKING
Solar/Wind Helper
0.119
316075AC2-137 C
Solar/Wind Helper
0.052
3138133OCRAN
Solar/Wind Helper
0.049
3138133OCRAN
Solar/Wind Helper
0.098
3141766HARMONY
Solar/Wind Helper
0.033
3141783LANCAST
Solar/Wind Helper
0.098
3141783LANCAST
Solar/Wind Helper
0.065
3141913WHIT STONE
Solar/Wind Helper
0.164
3143226MDLTHAN
Solar/Wind Helper
0.177
3143873LANEXA
Solar/Wind Helper
0.099
3146456SLIGO L269
Solar/Wind Helper
0.17
3146456SLIGO L269
Solar/Wind Helper
0.17
3146843MT LREL
Solar/Wind Helper
0.801
3146843MT LREL
Solar/Wind Helper
0.801
3146926FARMVIL
Solar/Wind Helper
0.223
3146926FARMVIL
Solar/Wind Helper
0.223
3147123OTTER R
Solar/Wind Helper
0.117
3141726DUNNSVL
Solar/Wind Helper
0.624
316034AC1-036 C
Solar/Wind Helper
0.104
316036AC1-147 C
Solar/Wind Helper
0.06
316059AD1-063 C
Solar/Wind Helper
0.04
316159AE1-175 C
Solar/Wind Helper
0.056
316240AF1-291 C
Solar/Wind Helper
0.058
316246AF1-032 C
Solar/Wind Helper
0.041
316248AF1-058 C
Solar/Wind Helper
0.326
316258AE1-075 C
Solar/Wind Helper
0.054
316305AF2-043 C
Solar/Wind Helper
0.054
316314AB2-024 C
Solar/Wind Helper
0.053
316315AB2-025 C
Solar/Wind Helper
0.055
316316AC1-027 C
Solar/Wind Helper
0.052
316336AC2-165 C
Solar/Wind Helper
0.307
316382AG1-145 C
Solar/Wind Helper
0.056
316405AF2-144 C
Solar/Wind Helper
0.051
3145336SMITFLD
Solar/Wind Helper
0.726
3145336SMITFLD
Solar/Wind Helper
0.073
3147243WELCO
Solar/Wind Helper
0.634
3141873WAN 176
Solar/Wind Helper
0.033
3143526WINTERP
Solar/Wind Helper
0.894
3143526WINTERP
Solar/Wind Helper
0.894
316404AE1-155 C
Solar/Wind Helper
0.323
316017AA1-139 ULT1
Solar/Wind Helper
0.166
316018AA1-139 ULT2
Solar/Wind Helper
0.166
316033AB2-134 GEN
Solar/Wind Helper
0.405
316388AE2-253 GEN
Solar/Wind Helper
0.14
3142543TWELFTH
Solar/Wind Helper
0.016
3144303KENBRDG
Solar/Wind Helper
0.374
3147173SINAI
Solar/Wind Helper
1.015
316203AE2-005 GEN
Solar/Wind Helper
0.345
316441AF1-014 GEN
Solar/Wind Helper
0.053
316484AD2-074 GEN
Solar/Wind Helper
0.221
315833AF1-017_GEN
Solar/Wind Helper
0.109
316369SG1_INVT
Solar/Wind Helper
0.279
316487AF1-042 GEN
Solar/Wind Helper
0.116
315839AE2-212 C
Solar/Wind Helper
0.06
315662AE1-191 GEN
Solar/Wind Helper
0.213
315666AE1-190 GEN
Solar/Wind Helper
0.053
319010AE1-072 C
Solar/Wind Helper
0.407
315697AD1-025 GEN
Solar/Wind Helper
0.427
316185AD1-033 GEN
Solar/Wind Helper
0.205
316280AD1-041 GEN
Solar/Wind Helper
0.133
316478AD1-087 GEN
Solar/Wind Helper
0.734
316486AD2-202 GEN
Solar/Wind Helper
0.215
316072AD1-144
Solar/Wind Helper
0.041
315687AD1-152 GEN
Solar/Wind Helper
1.264
316156AD2-030 GEN
Solar/Wind Helper
0.053
315785AD2-033 C
Solar/Wind Helper
0.988
316313AB2-026
Solar/Wind Helper
0.06
270030AE2-140 GEN
Solar/Wind Harmer
0.924
316349AD2-085 GEN
Solar/Wind Helper
0.139
313527AB2-043 GEN
Solar/Wind Helper
0.402
316322AB2-045
Solar/Wind Helper
0.094
316359AB2-059 GEN
Solar/Wind Harmer
0
316131AB2-060 GEN
Solar/Wind Helper
0.64
316083AB2-161 GEN
Solar/Wind Helper
0.144
316132AB2-190 GEN1
Solar/Wind Helper
0.212
316458AB2-190 GEN2
Solar/Wind Helper
0.212
316123AC1-075 GEN
Solar/Wind Helper
0.797
316375AC2-012 GEN
Solar/Wind Helper
0.351
316339AD2-160 GEN
Solar/Wind Helper
0.14
316239AB2-077_GEN
Solar/Wind Helper
0.163
316238AB2-078_GEN
Solar/Wind Helper
0.163
316237AB2-079_GEN
Solar/Wind Helper
0.163
316381AD1-082 GEN
Solar/Wind Helper
0.195
316233AE1-074 FULL
Solar/Wind Helper
0.055
316236AE1-162_GEN
Solar/Wind Helper
0.058
3145543BTLEBRO
Solar/Wind Harmer
-0.149
3145543BTLEBRO
Solar/Wind Harmer
-0.186
3145543BTLEBRO
Solar/Wind Harmer
-0.186
3145543BTLEBRO
Solar/Wind Harmer
-0.186
3130086AYDLETT
Solar/Wind Helper
0.672
3138543CONSLDL
Solar/Wind Harmer
-0.1
3142053HEARTS
Solar/Wind Harmer
0.006
3142946ENON
Solar/Wind Helper
0.017
3142946ENON
Solar/Wind Helper
0.056
3144536CHRHLND
Solar/Wind Helper
0.028
3144873MCLAUGH
Solar/Wind Helper
0.005
3145453TOT5
Solar/Wind Harmer
0.004
3145493TOT1
Solar/Wind Harmer
0.014
3145493TOT1
Solar/Wind Harmer
0.007
3145573BETHELC
Solar/Wind Harmer
-0.164
3145573BETHELC
Solar/Wind Harmer
-0.164
3145603CNETO
Solar/Wind Harmer
0.003
3146073TAR RVR
Solar/Wind Harmer
-0.164
3146083TARBORO
Solar/Wind Harmer
-0.164
3146083TARBORO
Solar/Wind Harmer
-0.164
3146233WITAKRS
Solar/Wind Harmer
0.031
3146233WITAKRS
Solar/Wind Harmer
-0.586
3146233WITAKRS
Solar/Wind Harmer
-0.1
942461AE2-259 GEN
Solar/Wind Helper
0.646
943811AF1-049 GEN
Solar/Wind Harmer
0
961601AG1-000A GEN
Solar/Wind Harmer
0.334
961601AG1-000A GEN
Solar/Wind Harmer
5.342
961611AG1-000B GEN
Solar/Wind Helper
0.254
961951AG1-038 GEN
Solar/Wind Helper
0.116
970085AG2-068 GEN
Solar/Wind Harmer
0.769
970087AG2-069 GEN
Solar/Wind Harmer
1.154
970223AG2-152 GEN
Solar/Wind Harmer
0.742
970581AG2-369 GEN
Solar/Wind Harmer
0.661
970917AG2-570 GEN
Solar/Wind Harmer
3.076
970919AG2-571 GEN
Solar/Wind Harmer
6.153
971367AH1-164 GEN
Solar/Wind Harmer
0.102
971629AH1-314 GEN
50/50
15.454
957601AF2-054 GEN
Solar/Wind Helper
0.053
957831AF2-077 GEN
Solar/Wind Helper
0.055
964211AG1-282 GEN
Solar/Wind Helper
0.05
971981AH1-535 GEN
Solar/Wind Harmer
0.298
315773AC2-141 GEN
Solar/Wind Helper
0.78
316003AC1-222 GEN
Solar/Wind Helper
0.967
316118AC1-105 GEN
Solar/Wind Helper
0.744
316129AC1-054 GEN
Solar/Wind Helper
0.25
316222AC1-221 GEN
Solar/Wind Helper
2.592
316263AC1-034 GEN
Solar/Wind Harmer
0.245
316283AC2-100 C
Solar/Wind Helper
2.441
316294AC1-161 GEN
Solar/Wind Helper
0.78
944201AF1-088_MTX
Adder
35.265
957141AF2-008_MTX
Adder
17.632
900033ID_568986
External Queue
0.2332763522863388
CBM West 1LTFEXP_CBM-W1->PJM
CBM
43.691
CBM West 2LTFEXP_CBM-W2->PJM
CBM
58.452
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.359
CBM South 2LTFEXP_CBM-S2->PJM
CBM
30.725
NYPJM->LTFIMP_NY
CLTF
0.562
LGEELTFEXP_LGEE->PJM
CLTF
2.162
WECLTFEXP_WEC->PJM
CLTF
1.169
CPLELTFEXP_CPLE->PJM
CLTF
13.916
TVALTFEXP_TVA->PJM
CLTF
5.267
MECLTFEXP_MEC->PJM
CLTF
5.888
LAGNLTFEXP_LAGN->PJM
CLTF
10.611
SIGELTFEXP_SIGE->PJM
CLTF
0.177
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
4.495
AG2-052LTFEXP_AG2-052->PJM
LTF
0.066
AH1-155LTFEXP_AH1-155->PJM
LTF
0.098

Details for [AH1-164] 6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 509T570_SRT-A


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 509T570_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.37 %
Rating:694.0 MVA
Rating Type:B
MVA to Mitigate:738.18
MW Contribution:2.0
IPD Plant:AH1-164
Bus #Bus NameTypeMW Contribution
971367AH1-164 GEN
PJM_IPD
1.998
CONTINGENCY 'DVP_P4-2: 509T570_SRT-A'
 OPEN BRANCH FROM BUS 314935 TO BUS 314945 CKT 1   /*8HERITAGE    500.0 - 8BRUNSWICK   500.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315102 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKG1  21.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315103 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKG2  21.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315104 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKG3  21.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315105 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKS1  19.0
 OPEN BRANCH FROM BUS 970916 TO BUS 314935 CKT 1   /*AG2-570 TP   500.0 - 8HERITAGE    500.0
 OPEN BUS 314945                                   /*8BRUNSWICK   500.0
 OPEN BUS 315102                                   /*1BRUNSWICKG1  21.0
 OPEN BUS 315103                                   /*1BRUNSWICKG2  21.0
 OPEN BUS 315104                                   /*1BRUNSWICKG3  21.0
 OPEN BUS 315105                                   /*1BRUNSWICKS1  19.0
END
CONTINGENCY 'DVP_P1-2: LN 570_SRT-A-3'
 OPEN BRANCH FROM BUS 970916 TO BUS 314935 CKT 1   /*AG2-570 TP   500.0 - 8HERITAGE    500.0
END
CONTINGENCY 'DVP_P1-2: LN 570_SRT-A-2'
 OPEN BRANCH FROM BUS 970916 TO BUS 970084 CKT 1   /*AG2-570 TP   500.0 - AG2-068 TP   500.0
END
CONTINGENCY 'DVP_P4-2: 57062_SRT-W'
 OPEN BRANCH FROM BUS 970916 TO BUS 314935 CKT 1                /*AG2-570 TP   500.0 - 8HERITAGE    500.0
 SET POSTCONTRATING 4018 BRANCH FROM BUS 314935 TO BUS 314940 CKT 1 /*8HERITAGE    500.0 - 8ROGERS RD   500.0
 SET POSTCONTRATING 4538 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3984 BRANCH FROM BUS 314935 TO BUS 314940 CKT 1 /*8HERITAGE    500.0 - 8ROGERS RD   500.0
 SET PRECONTRATING 4261 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
304070 to 316281 ckt 1

Light Load Analysis

The New Service Request AH1-164 was evaluated as a 35.0 MW injection

AH1-164 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 35.0 MW (35.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2CPLE/DVP
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P4-2: 509T570_SRT-A
BreakerAC109.87 %541.0B594.421.12

Details for 6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 509T570_SRT-A


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 509T570_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.87 %
Rating:541.0 MVA
Rating Type:B
MVA to Mitigate:594.42
MW Contribution:1.12
Bus #Bus NameTypeMW Contribution
3142956BIRDNECK
Solar/Wind Helper
0.29
316075AC2-137 C
Solar/Wind Helper
0.279
316034AC1-036 C
Solar/Wind Helper
0.557
316036AC1-147 C
Solar/Wind Helper
0.321
316059AD1-063 C
Solar/Wind Helper
0.214
316159AE1-175 C
Solar/Wind Helper
0.301
316240AF1-291 C
Solar/Wind Helper
0.313
316246AF1-032 C
Solar/Wind Helper
0.219
316248AF1-058 C
Solar/Wind Helper
1.76
316258AE1-075 C
Solar/Wind Helper
0.293
316305AF2-043 C
Solar/Wind Helper
0.292
316314AB2-024 C
Solar/Wind Helper
0.285
316315AB2-025 C
Solar/Wind Helper
0.294
316316AC1-027 C
Solar/Wind Helper
0.259
316336AC2-165 C
Solar/Wind Helper
1.653
316382AG1-145 C
Solar/Wind Helper
0.302
316405AF2-144 C
Solar/Wind Helper
0.205
316404AE1-155 C
Solar/Wind Helper
1.741
316017AA1-139 ULT1
Solar/Wind Helper
0.898
316018AA1-139 ULT2
Solar/Wind Helper
0.898
316033AB2-134 GEN
Solar/Wind Helper
2.184
316388AE2-253 GEN
Solar/Wind Helper
0.754
316203AE2-005 GEN
Solar/Wind Helper
1.863
316441AF1-014 GEN
Solar/Wind Helper
0.285
316484AD2-074 GEN
Solar/Wind Helper
1.103
315833AF1-017_GEN
Solar/Wind Helper
0.589
316369SG1_INVT
Solar/Wind Helper
1.502
316487AF1-042 GEN
Solar/Wind Helper
0.577
315839AE2-212 C
Solar/Wind Helper
0.324
315662AE1-191 GEN
Solar/Wind Helper
1.147
315666AE1-190 GEN
Solar/Wind Helper
0.287
319010AE1-072 C
Solar/Wind Helper
2.194
315697AD1-025 GEN
Solar/Wind Helper
2.301
316185AD1-033 GEN
Solar/Wind Helper
1.106
315773AC2-141 GEN
Solar/Wind Helper
3.897
316280AD1-041 GEN
Solar/Wind Helper
0.717
316003AC1-222 GEN
Solar/Wind Helper
5.211
316478AD1-087 GEN
Solar/Wind Helper
3.961
316486AD2-202 GEN
Solar/Wind Helper
1.16
316072AD1-144
Solar/Wind Helper
0.222
315687AD1-152 GEN
Solar/Wind Helper
6.825
316156AD2-030 GEN
Solar/Wind Helper
0.284
315785AD2-033 C
Solar/Wind Helper
4.938
316313AB2-026
Solar/Wind Helper
0.326
270030AE2-140 GEN
Solar/Wind Harmer
10.168
316349AD2-085 GEN
Solar/Wind Helper
0.696
313527AB2-043 GEN
Solar/Wind Helper
2.164
316322AB2-045
Solar/Wind Helper
0.501
316359AB2-059 GEN
Solar/Wind Harmer
0
316131AB2-060 GEN
Solar/Wind Helper
3.454
316083AB2-161 GEN
Solar/Wind Helper
0.201
316132AB2-190 GEN1
Solar/Wind Helper
1.145
316458AB2-190 GEN2
Solar/Wind Helper
1.145
316263AC1-034 GEN
Solar/Wind Harmer
2.844
316129AC1-054 GEN
Solar/Wind Helper
1.347
316123AC1-075 GEN
Solar/Wind Helper
4.3
316118AC1-105 GEN
Solar/Wind Helper
4.018
316222AC1-221 GEN
Solar/Wind Helper
13.996
316375AC2-012 GEN
Solar/Wind Helper
1.755
316283AC2-100 C
Solar/Wind Helper
13.179
316339AD2-160 GEN
Solar/Wind Helper
0.754
316239AB2-077_GEN
Solar/Wind Helper
0.88
316238AB2-078_GEN
Solar/Wind Helper
0.88
316237AB2-079_GEN
Solar/Wind Helper
0.88
316294AC1-161 GEN
Solar/Wind Helper
4.209
316381AD1-082 GEN
Solar/Wind Helper
1.054
316233AE1-074 FULL
Solar/Wind Helper
0.298
316236AE1-162_GEN
Solar/Wind Helper
0.315
3145543BTLEBRO
Solar/Wind Harmer
0.188
3145543BTLEBRO
Solar/Wind Harmer
0.188
3145543BTLEBRO
Solar/Wind Harmer
0.188
3145543BTLEBRO
Solar/Wind Harmer
0.151
3138543CONSLDL
Solar/Wind Harmer
0.102
3142053HEARTS
Solar/Wind Harmer
0.075
3145453TOT5
Solar/Wind Harmer
0.052
3145493TOT1
Solar/Wind Harmer
0.166
3145493TOT1
Solar/Wind Harmer
0.087
3145573BETHELC
Solar/Wind Harmer
0.166
3145573BETHELC
Solar/Wind Harmer
0.166
3145603CNETO
Solar/Wind Harmer
0.035
3146073TAR RVR
Solar/Wind Harmer
0.166
3146083TARBORO
Solar/Wind Harmer
0.166
3146083TARBORO
Solar/Wind Harmer
0.166
3146233WITAKRS
Solar/Wind Harmer
0.595
3146233WITAKRS
Solar/Wind Harmer
0.359
3146233WITAKRS
Solar/Wind Harmer
0.102
942461AE2-259 GEN
Solar/Wind Helper
3.485
943811AF1-049 GEN
Solar/Wind Harmer
0
961601AG1-000A GEN
Solar/Wind Harmer
2.81
961601AG1-000A GEN
Solar/Wind Harmer
3.875
961671AG1-007 GEN
Solar/Wind Harmer
0.313
961951AG1-038 GEN
Solar/Wind Helper
0.624
970085AG2-068 GEN
Solar/Wind Harmer
8.927
970087AG2-069 GEN
Solar/Wind Harmer
13.39
970223AG2-152 GEN
Solar/Wind Harmer
8.162
970413AG2-270 GEN
50/50
Charging
34.023
970535AG2-341 GEN
50/50
Charging
6.525
970581AG2-369 GEN
Solar/Wind Harmer
7.677
970865AG2-541 GEN
50/50
Charging
16.223
970909AG2-566 GEN
50/50
Charging
4.285
970917AG2-570 GEN
Solar/Wind Harmer
35.706
970919AG2-571 GEN
Solar/Wind Harmer
15.391
971367AH1-164 GEN
Solar/Wind Harmer
1.119
971443AH1-215 GEN
50/50
Charging
2.844
971629AH1-314 GEN
50/50
15.462
957601AF2-054 GEN
Solar/Wind Helper
0.286
957831AF2-077 GEN
Solar/Wind Helper
0.299
964211AG1-282 GEN
Solar/Wind Helper
0.27
971981AH1-535 GEN
Solar/Wind Harmer
2.856
971981AH1-535 GEN
Solar/Wind Harmer
3.116
944201AF1-088_MTX
Adder
35.322
957141AF2-008_MTX
Adder
14.034
900033ID_568986
External Queue
3.5454747676849365
CBM West 1LTFEXP_CBM-W1->PJM
CBM
43.161
CBM West 2LTFEXP_CBM-W2->PJM
CBM
58.725
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.69
CBM South 2LTFEXP_CBM-S2->PJM
CBM
28.334
NYPJM->LTFIMP_NY
CLTF
0.559
LGEELTFEXP_LGEE->PJM
CLTF
2.162
WECLTFEXP_WEC->PJM
CLTF
1.175
CPLELTFEXP_CPLE->PJM
CLTF
12.214
TVALTFEXP_TVA->PJM
CLTF
5.364
MECLTFEXP_MEC->PJM
CLTF
5.904
LAGNLTFEXP_LAGN->PJM
CLTF
10.551
SIGELTFEXP_SIGE->PJM
CLTF
0.178
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
28.118
AG2-052LTFEXP_AG2-052->PJM
LTF
0.066
AH1-155LTFEXP_AH1-155->PJM
LTF
0.099
CONTINGENCY 'DVP_P4-2: 509T570_SRT-A'
 OPEN BRANCH FROM BUS 314935 TO BUS 314945 CKT 1   /*8HERITAGE    500.0 - 8BRUNSWICK   500.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315102 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKG1  21.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315103 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKG2  21.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315104 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKG3  21.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315105 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKS1  19.0
 OPEN BRANCH FROM BUS 970916 TO BUS 314935 CKT 1   /*AG2-570 TP   500.0 - 8HERITAGE    500.0
 OPEN BUS 314945                                   /*8BRUNSWICK   500.0
 OPEN BUS 315102                                   /*1BRUNSWICKG1  21.0
 OPEN BUS 315103                                   /*1BRUNSWICKG2  21.0
 OPEN BUS 315104                                   /*1BRUNSWICKG3  21.0
 OPEN BUS 315105                                   /*1BRUNSWICKS1  19.0
END
304070 to 316281 ckt 1

Short Circuit Analysis

Short Circuit analysis is not performed as part of the Phase I System Impact Study. Short Circuit analysis will commence in the Phase II System Impact Study.

Stability Analysis

Stability analysis is not performed as part of the Phase I System Impact Study. Stability analysis will commence in the Phase II System Impact Study.

Reactive Power Analysis

Reactive Power analysis is not performed as part of the Phase I System Impact Study. Reactive Power analysis will commence in the Phase II System Impact Study.

Steady-State Voltage Analysis

Steady State Voltage Analysis is Not Required.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-018Powerton-Goodings GroveIn Service
AA1-038Lexington-Low Moor 230kVUnder Construction
AA1-050Tarboro-Everetts 230kVIn Service
AA1-063ACarolina–Seaboard 115kVIn Service
AA1-067Everetts 34.5kVIn Service
AA1-095Halfway-Marlowe 34.5kVIn Service
AA1-139Hickory-Shawboro 230kVIn Service
AA2-053Carolina-Jackson 115kVIn Service
AA2-057Hornertown-Whitakers 115kVIn Service
AA2-174Carolina-Jackson 115kVIn Service
AA2-178Mackeys 230kVIn Service
AB1-001Absecon 12 kVIn Service
AB1-006Meadow Lake 345kVIn Service
AB1-027Old Church 34.5 KVIn Service
AB1-081Anaconda-Mayo Dunbar 115kVIn Service
AB1-096Carroll-Mt. Airy 34.5kVIn Service
AB1-124Carroll-Monocacy 34.5kVPartially in Service - Under Construction
AB1-125Carroll-Monocacy 34.5kVIn Service
AB1-127St. Thomas-Guilford 34.5kVIn Service
AB1-128St. Thomas-Mercersburg 34.5kVIn Service
AB1-132Thelma 230kVIn Service
AB1-141Church-Wye Mills 138 kV IIn Service
AB1-142Church-Wye Mills 138 kV IIIn Service
AB1-176Price 25kV IIEngineering & Procurement
AB1-180Pine View 12kVIn Service
AB2-022Elizabeth City 34.5kVIn Service
AB2-024Correctional 34.5kVIn Service
AB2-025Sapony 34.5kVIn Service
AB2-026Powhatan 34.5kVIn Service
AB2-029Remington 34.5kVIn Service
AB2-031Brink-Trego 115kVIn Service
AB2-032Church-Wye Mills 138 kVIn Service
AB2-037Keeney-Steele 230kVUnder Construction
AB2-040Brink 115kVIn Service
AB2-043Chase City 115kVIn Service
AB2-045Buckingham 34.5kVIn Service
AB2-049Gloucester Township 12kVIn Service
AB2-059Benson-Dunbar 115kVIn Service
AB2-060Chase City-Lunenburg 115kVIn Service
AB2-070Mt. Pulaski-BrokawIn Service
AB2-077Buggs Island-Chase City 115kVIn Service
AB2-078Buggs Island-Chase City 115kVIn Service
AB2-079Buggs Island-Chase City 115kVIn Service
AB2-099Ahoskie 34.5kVIn Service
AB2-133Chestertown 69kVUnder Construction
AB2-134Hopewell-Surry 230kVIn Service
AB2-135Church-Kent 69kVIn Service
AB2-136Cambridge-West Cambridge 69kVUnder Construction
AB2-153Church-Wye Mills 138 kVIn Service
AB2-157Prince George's County 12kVIn Service
AB2-158Louisa-South Anna 230kVIn Service
AB2-161Waverly #2 DP 115kVIn Service
AB2-169Pantago-Five Points 115kVIn Service
AB2-174Emporia-Trego 115kVIn Service
AB2-179Townsend 138kVIn Service
AB2-190Hopewell-Surry 230kVIn Service
AC1-001Delano 138kVIn Service
AC1-010Gloucester 26kVUnder Construction
AC1-027Pendleton 34.5kVIn Service
AC1-030Cinnaminson 13kVIn Service
AC1-033Kewanee 138 kVIn Service
AC1-034Heartsease DP - Mayo Dunbar 115kVSuspended
AC1-036Twittys Creek 34.5kVIn Service
AC1-042Altavista-Mt. Airy 69kVIn Service
AC1-053Lanesville-BrokawPartially in Service - Under Construction
AC1-054Kerr Dam–Eatons Ferry 115 kVIn Service
AC1-074Jacksonville-Renaker 138kV IIn Service
AC1-075Perth-Hickory Grove 115kVIn Service
AC1-076Locust Grove-Paytes 115kVIn Service
AC1-082Ravenswood-Hemlock 69kVUnder Construction
AC1-085Stuart-Clinton 345kVIn Service
AC1-086Thelma 230kVSuspended
AC1-089Hillsboro-Wildcat 138kVIn Service
AC1-091Cedar Creek 138kV IEngineering & Procurement
AC1-092Cedar Creek 138kV IIEngineering & Procurement
AC1-093Cedar Creek 138kV IIIEngineering & Procurement
AC1-094Cedar Creek 138kV IVEngineering & Procurement
AC1-098Dawson-South Justice 115kVPartially in Service - Under Construction
AC1-099Dawson-South Justice 115kVPartially in Service - Under Construction
AC1-101Johns Creek-Excel 138kV ISuspended
AC1-102Johns Creek-Excel 138kV IISuspended
AC1-105Halifax-Mt. Laurel 115kVIn Service
AC1-111Aurora 138kVIn Service
AC1-118Westmoreland 34.5kVIn Service
AC1-120Mitchell-Mountain Run 115kVEngineering & Procurement
AC1-121Mitchell-Mountain Run 115kVEngineering & Procurement
AC1-122Smith Mountain-Candler's Mountain 138kVIn Service
AC1-145Gretna DP 69 kVIn Service
AC1-147Grassfield 34.5kVIn Service
AC1-158Spotsylvania 500kVIn Service
AC1-161Septa 500kVIn Service
AC1-164Chickahominy 230kVPartially in Service - Under Construction
AC1-168Kewanee-StreatorSuspended
AC1-174Losantville 345kVIn Service
AC1-175Losantville 345kVIn Service
AC1-188Rio-Lick 138kVEngineering & Procurement
AC1-189Chinquapin-Everetts 230kVUnder Construction
AC1-191Elmont 115kVEngineering & Procurement
AC1-194Elk 138kVActive
AC1-208Cox-Whitakers 115kVUnder Construction
AC1-214Crescent RidgeIn Service
AC1-221Halifax-Person 230kVIn Service
AC1-222Crystal Hill-Halifax 115kVIn Service
AC2-012Grassfield-Great Bridge 115kVIn Service
AC2-023Hebron 69kVEngineering & Procurement
AC2-059Biers Run-Circleville 138kVIn Service
AC2-060Buckskin 69kVIn Service
AC2-061Hillsboro-Clinton 138kVIn Service
AC2-067Camden-Crystal I 69kVEngineering & Procurement
AC2-068Camden-Crystal II 69kVEngineering & Procurement
AC2-075Jacksonville-Renaker 138 kVIn Service
AC2-079Ivor-Oak Ridge 115kVSuspended
AC2-088S. Bethel-Brown 69kVIn Service
AC2-090Losantville 345kVIn Service
AC2-100Halifax-Person 230kVIn Service
AC2-111College Corner 138kVEngineering & Procurement
AC2-120Ripley 69kVIn Service
AC2-123Jacksons Ferry 138kVIn Service
AC2-136East Hagerstown 12kVUnder Construction
AC2-137Elko 34.5kVIn Service
AC2-138Northern Neck 34.5kVIn Service
AC2-141Septa 500kVEngineering & Procurement
AC2-157Sullivan 345 kVUnder Construction
AC2-165Bremo-Powhatan 230kVSuspended
AC2-168Clinton 23kVIn Service
AC2-186Harrington 25kVUnder Construction
AC2-187Harrington 69kVUnder Construction
AC2-188Harrington 69 kVUnder Construction
AD1-013Twombly Road 138kVEngineering & Procurement
AD1-017Smith Mountain-Bearskin 138 kVIn Service
AD1-020Hunterstown-Lincoln 115 kVIn Service
AD1-022Cashie-Trowbridge 230 kVEngineering & Procurement
AD1-025Hopewell-Surry 230 kVUnder Construction
AD1-033Fentress-Landstown 230 kVIn Service
AD1-041Harmony Village-Shackleford 115 kVIn Service
AD1-056Hornertown-Hathaway 230 kVSuspended
AD1-057Hornertown-Hathaway 230 kVSuspended
AD1-060Mercersburg-Milnor 34.5 kVIn Service
AD1-061McConnelsburg-Mercersburg 34 kVIn Service
AD1-063Harmony Village 34.5 kVIn Service
AD1-074Trowbridge 230 kVEngineering & Procurement
AD1-075Trowbridge 230 kVEngineering & Procurement
AD1-076Trowbridge 230 kVEngineering & Procurement
AD1-082Bakers Pond-Ivor 115kVIn Service
AD1-087Clover-Sedge Hill 230 kVIn Service
AD1-088Briery-Clover 230 kVSuspended
AD1-105Kings Dominion DP 115 kVUnder Construction
AD1-115Mountain Run-Mitchell 115 kVEngineering & Procurement
AD1-128Modoc-Delaware 138 kVPartially in Service - Under Construction
AD1-136South Bethel-Brown 69 kVIn Service
AD1-144Kings Fork 34.5 kVIn Service
AD1-151Hopewell-Surry 230 kVSuspended
AD1-152Clover-Sedge Hill 230 kVIn Service
AD1-155Meadow Brook-Strasburg 138 kVIn Service
AD2-009McConnellsburg 138 kVIn Service
AD2-016Biers Run-Circleville 138 kVIn Service
AD2-022East Danville - Roxborough 230 kVEngineering & Procurement
AD2-023East Danville - Roxborough 230 kVEngineering & Procurement
AD2-027Camden Switch 26 kVIn Service
AD2-030Wan 34.5 kVIn Service
AD2-031Martinsville-Wilmington 69 kVIn Service
AD2-033Chase City-Lunenburg 115 kVUnder Construction
AD2-038Powerton-Nevada 345 kVUnder Construction
AD2-042Camden Switch 26 kV IIIn Service
AD2-048Cynthia-Headquarters 69 kVUnder Construction
AD2-058St. Barnabas 13 kVIn Service
AD2-065Atco 12 kVIn Service
AD2-066Mazon-Crescent Ridge 138 kVEngineering & Procurement
AD2-071Strawton-Deer Creek 138 kVSuspended
AD2-073Sanders DP 230 kVIn Service
AD2-074Garner DP-Lancaster 115 kVEngineering & Procurement
AD2-085Myrtle-Windsor DP 115kVEngineering & Procurement
AD2-100Kincaid-Pana 345 kVSuspended
AD2-116Hokes-Grantley 69 kVIn Service
AD2-131Kincaid-Pana 345kVSuspended
AD2-133Eagle Valley 115kVIn Service
AD2-134Shady OaksPartially in Service - Under Construction
AD2-135Williamstown 12kVPartially in Service - Under Construction
AD2-160Hickory-Moyock 230kVIn Service
AD2-172Lena 138kVIn Service
AD2-179Morgans Cut-Glen Lyn 138kVSuspended
AD2-180Elk Garden-Parr Run 138kVIn Service
AD2-202Clover-Sedge Hill 230kVIn Service
AE1-040Greenfield 69 kVIn Service
AE1-056Red House-South Creek 115 kVWithdrawn
AE1-072Shawboro-Sligo 230 kVUnder Construction
AE1-074Winterpock 34.5 kVUnder Construction
AE1-075Powhatan 34.5 kVIn Service
AE1-079Maysville-Sharon 69 kVUnder Construction
AE1-100Axton 138 kVIn Service
AE1-101McConnellsburg-Texas Eastern 138 kVIn Service
AE1-103Holland-Union Camp 115 kVUnder Construction
AE1-108Bremo-Scottsville 138 kVEngineering & Procurement
AE1-109Frenchs Mill 34 kVIn Service
AE1-113Mole Creek 345 kVEngineering & Procurement
AE1-114Maryland-Lancaster 138 kVActive
AE1-148Kerr Dam-Ridge Rd 115 kVActive
AE1-149Disputanta-Poe 115 kVSuspended
AE1-155Garner-Northern Neck 115 kVIn Service
AE1-162Smithfield 34.5 kVIn Service
AE1-163Powerton-Nevada 345 kVEngineering & Procurement
AE1-172Loretto-Wilton CenterActive
AE1-173Carson-Suffolk 500 kVUnder Construction
AE1-175Light Foot 34.5 kVIn Service
AE1-176Roanoke-Vinton 12 kV (Niagara Hydro)In Service
AE1-183Maysville-McDowell 69 kVEngineering & Procurement
AE1-185Hokes-Jackson 69 kVIn Service
AE1-190Harmony Village-Shackleford 115 kVPartially in Service - Under Construction
AE1-191Harmony Village-Shackleford 115 kVPartially in Service - Under Construction
AE1-196Hokes-Jackson 69 kV IIIn Service
AE1-205McLean 345 kVEngineering & Procurement
AE1-207Mississinewa-Gaston 138 kVSuspended
AE1-208Delaware-Van Buren 138 kVSuspended
AE1-209Desoto 345 kVSuspended
AE1-210Desoto 345 kVSuspended
AE1-212Grandview-Clifftop 138 kVSuspended
AE1-229Deepwater-Upper Pittsgrove 138 kVSuspended
AE1-237Andover (Maysville) 69kV IUnder Construction
AE1-250Smith Mountain-E. Danville 138 kVEngineering & Procurement
AE2-005Harmony Village-Shackleford 115 kVUnder Construction
AE2-027Harrowgate-Locks 115kVUnder Construction
AE2-029Grottoes-Merck 115kVUnder Construction
AE2-033Clubhouse-Sapony 230 kVSuspended
AE2-034Mackeys 230 kVPartially in Service - Under Construction
AE2-035Lena 138 kVIn Service
AE2-045Olive-Reynolds 345 kVEngineering & Procurement
AE2-047Ridgeway-Solite 69 kVEngineering & Procurement
AE2-051Carson-Septa 500 kVEngineering & Procurement
AE2-054Warfordsburg 34 kVIn Service
AE2-071Patton Rd-Summer Shade 69 kVIn Service
AE2-092Kidds Store-Sherwood 115 kVEngineering & Procurement
AE2-094Carson-Rogers Road 500 kVEngineering & Procurement
AE2-104Suffolk 115 kVSuspended
AE2-114Midland 23 kV IIn Service
AE2-115Midland 23 kV IIIn Service
AE2-125Stahlstown-Ligonier 25 kVIn Service
AE2-140Axton-Danville 138 kVSuspended
AE2-156Yadkin 115 kVActive
AE2-160Kanawha River 138 kVEngineering & Procurement
AE2-166Stockton 138 kVSuspended
AE2-169Delaware-Van Buren 138 kVSuspended
AE2-172Mississinewa-Gaston 138 kVSuspended
AE2-173McLean 345 kVActive
AE2-185Gladys DP-Stonemill Switching Station 69 kVActive
AE2-187Shockoe DP-Chatham 69 kVActive
AE2-212Harrowgate 34 kVEngineering & Procurement
AE2-219Bluff Point-Randolph 138 kVSuspended
AE2-220Losantville 345 kVEngineering & Procurement
AE2-221Clinton-Stuart 345 kVUnder Construction
AE2-223McLean 345 kVActive
AE2-224Bear Rock-Johnstown 230 kVIn Service
AE2-230Bartonsville-Meadow Brook 138 kVIn Service
AE2-253Hickory-Moyock 230 kVIn Service
AE2-254Garrard County-Tommy-Gooch 69 kVIn Service
AE2-255Molecreek 345 kVEngineering & Procurement
AE2-259Curdsville-Willis Mtn 115 kVEngineering & Procurement
AE2-261Kincaid-Pana 345 kVActive
AE2-267Woodsdale 345 kVEngineering & Procurement
AE2-281Powerton-Nevada 345 kVEngineering & Procurement
AE2-283Gladys-Stone Mill 69 kVActive
AE2-285Maysville 69 kVEngineering & Procurement
AE2-291Grit DP-Perth 115 kVActive
AE2-297Madison-Tanners Creek 138 kVIn Service
AE2-308Three Forks-Dale 138 kVActive
AE2-309Carlos Junction-Lonaconing 34.5 kVIn Service
AE2-315Yankee Tap 69 kVIn Service
AE2-318Ford-Cedarville 138 kVSuspended
AE2-321Belvidere-Marengo 138 kVActive
AE2-326Jacksons Ferry 138 kVEngineering & Procurement
AE2-339Avon 138 kVEngineering & Procurement
AE2-341Sandwich-Plano 138 kVActive
AE2-343Andover (Maysville) 69 kV IIUnder Construction
AE2-346Ahoskie 34.5 kVIn Service
AF1-007Indian River 230 kV ISuspended
AF1-014Harmony Village-Shackleford 115 kVUnder Construction
AF1-017Myrtle-Windsor 115 kVEngineering & Procurement
AF1-021Bethelboro-Connellsville #1 25 kVIn Service
AF1-022Lake Lynn-Uniontown 25 kVIn Service
AF1-030Sandwich-Plano 138 kVActive
AF1-032Suffolk 34.5 kVIn Service
AF1-038Sewellton Jct-Webbs Crossroads 69 kVEngineering & Procurement
AF1-039Listonburg-Highpoint 24.9 kVIn Service
AF1-042Garner DP-Lancaster 115 kVEngineering & Procurement
AF1-045Cedarville-Ford 138 kVSuspended
AF1-049Berry Hill 138 kVUnder Construction
AF1-050Summer Shade - Green County 161 kVEngineering & Procurement
AF1-051Gavin 765 kVIn Service
AF1-058Welco 34.5 kVIn Service
AF1-069Carson-Rogers Rd 500 kVEngineering & Procurement
AF1-071College Corner 138 kVEngineering & Procurement
AF1-075Harrisburg-Endless Caverns 230 kVSuspended
AF1-083Green County-Saloma 161 kVEngineering & Procurement
AF1-086Madera-Westover South 115 kVUnder Construction
AF1-088Sullivan 345 kVActive
AF1-090Kincaid-PanaEngineering & Procurement
AF1-093Henderson-Stoneboro 69 kVEngineering & Procurement
AF1-114Oak Grove-Dahlgren 230 kVEngineering & Procurement
AF1-123Harper 230 kVActive
AF1-124Harper 230 kVActive
AF1-125Harper 230 kVActive
AF1-128Chesterfield 230 kVActive
AF1-129Chesterfield 230 kVEngineering & Procurement
AF1-130Inez 138 kVSuspended
AF1-134Philipsburg-Madera 34.5 kVEngineering & Procurement
AF1-136Warfordsburg-Purcell Junction 34.5 kVEngineering & Procurement
AF1-140Claysburg 23 kVEngineering & Procurement
AF1-143Lick Run 115 kVEngineering & Procurement
AF1-147Poland Rd-Runway DP 230kVUnder Construction
AF1-162Inez 138 kVEngineering & Procurement
AF1-202Keystone-Desoto 345 kVUnder Construction
AF1-203Patton Rd-Summer Shade 69 kVIn Service
AF1-204Eugene 345 kVActive
AF1-207Reynolds-Olive #1 345 kVEngineering & Procurement
AF1-223Keystone-Desoto 345 kVUnder Construction
AF1-233Flemingsburg – Spurlock 138kVActive
AF1-249Nickel 12.47 kVIn Service
AF1-254Milnor-Huyetts 34.5 kVUnder Construction
AF1-262Upper Pittsgrove 12 kVIn Service
AF1-264Runnemede 13 kVIn Service
AF1-268Desoto-Jay 138 kVEngineering & Procurement
AF1-272Lucerne 115 kVEngineering & Procurement
AF1-282Stuart-Clinton 345 kVEngineering & Procurement
AF1-283Stuart-Clinton 345 kVEngineering & Procurement
AF1-290Feagans Mill-Millville 138 kVIn Service
AF1-291Tyler 34.5 kVEngineering & Procurement
AF1-291ABartonsville-Meadow Brook 138 kVIn Service
AF1-294Jetersville-Ponton 115 kVActive
AF1-296Garden Plain 138 kVActive
AF1-299Otter Point 34.5 kV IIn Service
AF1-300Otter Point 34.5 kV IIIn Service
AF1-302Brookville-Squab Hollow 138 kVEngineering & Procurement
AF1-322Meadow Lake 345 kVEngineering & Procurement
AF1-331Twombley RoadEngineering & Procurement
AF2-008Sullivan 345 kVActive
AF2-018Inez 138 kVEngineering & Procurement
AF2-032Kincaid 345 kVEngineering & Procurement
AF2-041Nelson-Electric Junction 345 kVActive
AF2-042Clover-Rawlings 500 kVActive
AF2-043Suffolk 34.5 kVIn Service
AF2-046Tunis-Mapleton 115 kVActive
AF2-048Rio-Lick 138 kVEngineering & Procurement
AF2-054Wan 34.5 kVIn Service
AF2-069Crescent Ridge 138 kVActive
AF2-075Bartonsville-Meadow Brook 138 kV IIIIn Service
AF2-077White Marsh 34.5 kVIn Service
AF2-078Reynolds-Olive #1 345 kVEngineering & Procurement
AF2-080Chinquapin-Everetts 230 kVActive
AF2-081Moyock 230 kVActive
AF2-106Hazel Hollow-Glen Lyn #1 138 kVEngineering & Procurement
AF2-107Clifford 138 kVEngineering & Procurement
AF2-110Suffolk 115 kVSuspended
AF2-111North Clark-Spurlock 345 kVActive
AF2-115Jetersville-Ponton 115 kVActive
AF2-120Garner-Northern Neck 115 kVActive
AF2-130Cobalt Corners 34.5 kVIn Service
AF2-133Reynolds-Olive #2 345 kVUnder Construction
AF2-142Nevada 345 kVActive
AF2-143Powerton-Nevada 345 kVActive
AF2-144Powhatan 34.5 kVIn Service
AF2-173Desoto 345 kVActive
AF2-199Nelson-Electric Junction 345 kVActive
AF2-200Nelson-Electric Junction 345 kVActive
AF2-205Olive-Reynolds #2 345 kVEngineering & Procurement
AF2-222Madisonville DP-Twitty's Creek 115 kVActive
AF2-225McLean 345 kVActive
AF2-235Titusville-Oil Creek 34.5 kVWithdrawn
AF2-250Edgewood 12 kV IIIIn Service
AF2-252Blue Mound 345 kVEngineering & Procurement
AF2-291Sporn South-Leon 138 kVEngineering & Procurement
AF2-297Sedge Hill 115 kVActive
AF2-298Crown-New Lebanon 69 kVEngineering & Procurement
AF2-299Fields 34.5 kVActive
AF2-307Hope-Belvins Valley Tap 69 kVActive
AF2-311Gilboa-Jones Branch 138 kVEngineering & Procurement
AF2-316Gilboa-Jones Branch 138 kV IIEngineering & Procurement
AF2-325Jacktown 12 kVEngineering & Procurement
AF2-335Delaware-Royerton 138 kVActive
AF2-352Blue Mound 345 kVEngineering & Procurement
AF2-356Albright-Mt. Zion 138 kVUnder Construction
AF2-365Munfordville KU Tap-Horse Cave Jct. 69 kVActive
AF2-378Cambridge 12 kVEngineering & Procurement
AF2-379Princess Anne 25 kVUnder Construction
AF2-382Hurley 69 kVEngineering & Procurement
AF2-383Tolna 115 kVWithdrawn
AF2-392Nelson-Dixon 138 kVActive
AF2-440Hillsboro-Middleboro 138 kVEngineering & Procurement
AG1-007Tar River 12.5 kVEngineering & Procurement
AG1-008Tunis-Mapleton 115 kVActive
AG1-021Jetersville-Ponton 115 kVActive
AG1-038Garner DP-Lancaster 115 kVEngineering & Procurement
AG1-054Potter-Harlan 69 kVEngineering & Procurement
AG1-066Bonnyman 69 kVEngineering & Procurement
AG1-070Bon Ayr 69 kVActive
AG1-071Bon Ayr 69 kVActive
AG1-082Ahoskie 34.5 kVActive
AG1-098Briery-Clover 230 kVActive
AG1-105Mount Laurel-Barnes Junction 115 kVActive
AG1-106Thelma 230 kVActive
AG1-107Hillsboro-Middleboro 138 kVEngineering & Procurement
AG1-118Sugar Grove-Waterman 138kVActive
AG1-124Gladstone 138 kVActive
AG1-125Marysville-Flatlick 765 kVEngineering & Procurement
AG1-126Marysville-Flatlick 765 kVEngineering & Procurement
AG1-127Crego Rd 138 kVActive
AG1-135Garner-Lancaster 115 kVActive
AG1-145Lightfoot 34.5 kVIn Service
AG1-146Garner DP-Lancaster 115 kVActive
AG1-147Garner DP-Lancaster 115 kVActive
AG1-166Lone Pine 115 kVActive
AG1-167Lone Pine 115 kVActive
AG1-168Lone Pine 115 kVActive
AG1-226Dequine-Eugene 345 kVActive
AG1-236Lanesville-Brokaw 345 kVActive
AG1-237Dequine-Eugene 345 kVEngineering & Procurement
AG1-254Salem-Woodstown 69 kVEngineering & Procurement
AG1-281Claysburg-HCR Tap 46 kVEngineering & Procurement
AG1-282Dunnsville 34.5 kVEngineering & Procurement
AG1-285Chase City-Central 115 kVActive
AG1-320Glendale-Stephensburg 69 kVActive
AG1-341Summer Shade 161 kVActive
AG1-342Dryburg 115 kVActive
AG1-349Olive-Reynolds #2 345 kVEngineering & Procurement
AG1-354Summershade-Green County 161 kVActive
AG1-363Black Oak-Hatfield 500 kVEngineering & Procurement
AG1-367DeSoto 345 kVActive
AG1-374Blue Mound 345 kVActive
AG1-386Smith-Francis Junction 25 kVIn Service
AG1-393Sapony 34.5 kVActive
AG1-394Boykins 34.5 kVActive
AG1-397Walston 12 kVWithdrawn
AG1-405Walnut Grove-Asahi 69 kVActive
AG1-406Walnut Grove-Asahi 69 kVActive
AG1-460Kincaid-Pana 345 kVActive
AG1-462Cordova 345 kVActive
AG1-469Gordonsville 34.5 kVEngineering & Procurement
AG1-471Up Church-Wayne County 69 kVActive
AG1-482Hamilton 115 kVWithdrawn
AG1-494Boxwood-Riverville 138 kVActive
AG1-499Lambs 12.47 kVUnder Construction
AG1-508Point Lookout 69 kVEngineering & Procurement
AG1-526West Garrard 345 kVActive
AG1-551Parmele 34.5 kVActive
AG1-552Carolina 34.5 kVActive
AG1-555Dequine 345 kVEngineering & Procurement
AG1-558Buckner 34.5 kVEngineering & Procurement
AG1-559Caroline Pines 22 kVEngineering & Procurement
AG2-005Garner DP-Lancaster 115 kVActive
AG2-010Peninsula-Whealton 115 kVActive
AG2-068Heritage - Wake 500 kVActive
AG2-069Heritage - Wake 500 kVActive
AG2-072Rockport 765 kVActive
AG2-073Crooksville 69 kVActive
AG2-077Clover-Rawlings 500 kVActive
AG2-081Mt. Sterling-Fogg Pike 69 kVActive
AG2-085Delaware-Royerton 138 kVActive
AG2-093Colonial Trail-Hopewell 230 kVActive
AG2-095Hopewell 34.5 kV (Circuit 313)Active
AG2-104Marysville-Flatlick 765 kVActive
AG2-106Marysville-Flatlick 765 kVActive
AG2-107Marysville-Flatlick 765 kVActive
AG2-111Perth 34.5 kV Substation (Circuit 408)Active
AG2-112Perth 34.5 kV Substation (Circuit 404)Active
AG2-114Dresden-Pontiac Midpoint 345 kVActive
AG2-120Everetts 34.5 kVActive
AG2-124Shackleford-Harmony 115 kVActive
AG2-125Camden-Crystal 69 kVActive
AG2-126Eugene 345 kVActive
AG2-151Trices Lake - James River Tap 115 kVActive
AG2-152Banister-Bear Skin 138 kVActive
AG2-159Williamstown 69 kVActive
AG2-162Jefferson-Greentown 765 kVActive
AG2-163Dequine-Eugene 345 kVActive
AG2-164Jefferson-Greentown 765 kVActive
AG2-165Dumont-Greentown 765 kVActive
AG2-171Lunenburg-Nutbush 115 kVActive
AG2-179Sewellton Junction 69 kVActive
AG2-184Harbert Metering 138 kVActive
AG2-188Farmville - Buckingham 230 kVActive
AG2-191Mississinewa 138 kVActive
AG2-192Mississinewa 138 kVActive
AG2-193Turner 34.5 kVActive
AG2-198Briery - Finneywood 230 kVActive
AG2-212Dumont-Greentown 765 kVActive
AG2-213Gary D.P Tap - Gary D.P 115 kVActive
AG2-215Garner DP-Lancaster 115 kVActive
AG2-219Jefferson-Greentown 765 kVActive
AG2-262Dryburg 115 kVActive
AG2-270Clover 230 kVActive
AG2-272Berry Hill 138 kVActive
AG2-298Sulphur Creek-Loretto 69 kVActive
AG2-310Matt Funk 138 kVActive
AG2-311Smith Mountain 138 kVActive
AG2-328Dumont - Greentown 765 kVActive
AG2-330Dumont - Greentown 765 kVActive
AG2-331Jefferson-Greentown 765 kVActive
AG2-341Ridge Road 115 kVActive
AG2-360Broadford 138 kVActive
AG2-363Powerton 345 kVActive
AG2-364Powerton 345 kVActive
AG2-369Heritage - Wake 500 kVActive
AG2-382Cashie 230 kVActive
AG2-401Losantville 345 kVActive
AG2-424Magnolia - Summersville 69 kVActive
AG2-426Wakefield - Waverly 115 kVActive
AG2-427Waverly 115 kVActive
AG2-428Wakefield 115 kVActive
AG2-436Carson - Rogers Road 500 kVActive
AG2-440Twittys Creek - Madisonville 115 kVActive
AG2-441Twittys Creek - Madisonville 115 kVActive
AG2-442Twittys Creek - Madisonville 115 kVActive
AG2-449Jefferson-Greentown 765 kVActive
AG2-469Westmoreland – Oak Grove 230 kVActive
AG2-487Madison - Tanners Creek 138 kVActive
AG2-491Meadow Lake 345 kVActive
AG2-516Pecatonica 138kVActive
AG2-518Tech Drive 138 kVActive
AG2-519Royerton - Desoto 138 kVActive
AG2-522Five Forks DP 115 kVActive
AG2-541Perth - Crystal Hill 115 kVActive
AG2-548Corwin - Elk 138 kVActive
AG2-550Bluff Point - Randolph 138 kVActive
AG2-551Bluff Point - Randolph 138 kVActive
AG2-566Briery - Finneywood 230 kVActive
AG2-568Stink Run – Sundial 138 kVActive
AG2-570Heritage - Wake 500 kVActive
AG2-571Heritage - Wake 500 kVActive
AG2-575Crego Rd. 138 kVActive
AG2-581Rawlings-Clover 500 kVActive
AG2-583Bremo - Cartersville 230 kVActive
AG2-589Ravenswood - Hemlock 69 kVActive
AG2-637Randolph - Hodgin 138 kVActive
AG2-657Kanawha River - Carbondale 138 kVActive
AG2-659Kerr Dam – Hawtree 115 kVActive
AG2-660Nelson-Electric Junction 345 kVActive
AG2-661Hopewell - Colonial Trail 230 kVActive
AG2-665Corwin - Elk 138 kVActive
AG2-670Green County -Taylor County Junction 161 kVActive
AH1-004Avon - Renaker 138 kVActive
AH1-033Sligo 34.5 kVActive
AH1-034Patton Road Junction - Summer Shade 69 kVActive
AH1-035Plymouth 34.5 kVActive
AH1-040Mackeys - Creswell 115 kVActive
AH1-042Providence Forge-Turner 115kVActive
AH1-044Nelson - Electric Junction 345 kVActive
AH1-047Marengo - Belvidere 138 kVActive
AH1-055Kyger Creek - Don Marquis 345 kVActive
AH1-056Red House DP 115kVActive
AH1-071Midlothian 34.5 kVActive
AH1-072Red Onion - VC5 69 kVActive
AH1-073Red Onion - VC5 69 kVActive
AH1-098Wolf Glade-West Carroll 138 kVActive
AH1-106Winterpock 34.5kVActive
AH1-107Winterpock 34.5kVActive
AH1-108Spruance NUG 230 kVActive
AH1-133Saltville - Tazewell 138 kVActive
AH1-136Falcon - Middle Creek 46 kVActive
AH1-138Penniman 34.5 kVActive
AH1-144Peter's Mountain 138 kVActive
AH1-145Peter's Mountain 138 kVActive
AH1-146White Rock - Wayne 345 kVActive
AH1-147White Rock - Wayne 345 kVActive
AH1-150Nelson-Electric Junction 345 kVActive
AH1-151Nelson-Electric Junction 345 kVActive
AH1-157Penniman - Waller 230 kVActive
AH1-170Columbia DP 115kVActive
AH1-188Pigeon Creek 138 kVActive
AH1-196Prairie 345 kVActive
AH1-215Central VA-Twitty 115 kVActive
AH1-216Smithfield-Surry 230 kVActive
AH1-217Kidds Store - Fork Union 115 kV IIActive
AH1-227Flemming - Fremont 69 kVActive
AH1-234Wempletown - Paddock 345 kVActive
AH1-239Upchurch - Zula 69 kVActive
AH1-241Cobbs Creek - James River Industrial 115kVActive
AH1-269Claytor 138 kVActive
AH1-271Cashie 230 kVActive
AH1-280Jetersville-Ponton 115 kVActive
AH1-281Bluegrass Parkway Tap - Woodlawn 69 kVActive
AH1-285Sandwich 138 kVActive
AH1-292Sullivan 345 kVActive
AH1-302Olive - Reynolds 345 kVActive
AH1-304Delaware-Van Buren 138 kVActive
AH1-305Olive - Reynolds 345 kVActive
AH1-306Mississinewa-Gaston 138 kVActive
AH1-311Heartsease DP - Mayo Dunbar 115kVActive
AH1-314East Danville 138 kVActive
AH1-323Elmont 230 kVActive
AH1-324Colonial Trail – Surry 230 kVActive
AH1-337Randolph - Hodgin 138 kVActive
AH1-338McGirr Rd - Ritchie Road 138kVActive
AH1-341Stillman - Dixon 138KVActive
AH1-343Crystal Hill DP- Perth 115kVActive
AH1-348Pound 34.5 kVActive
AH1-377Clover- Farmville 230kVActive
AH1-396Gary 24.94 kVActive
AH1-397Shacklesford 34.5 kVActive
AH1-399North Doswell 12.5 kVActive
AH1-408Freeman DP – Lawrenceville 115 kVActive
AH1-427Tommy Gooch - Garrard County 69 kVActive
AH1-439Buckingham- Farmville 230kVActive
AH1-482Olive - Reynolds #2 345 kVActive
AH1-528Rawlings - Unity 500 kVActive
AH1-535Nagel - Cane River 230 kVActive
AH1-537Pierce - Kyger Creek 345 kVActive
AH1-541Chestnut 345 kVActive
AH1-543Mulberry – Tazewell 345 kVActive
AH1-546Bremo - Buckingham 230 kVActive
AH1-570Headquarters - Millersburg Junction 69 kVActive
AH1-571Headquarters - Millersburg Junction 69 kVActive
AH1-617Harbert Metering 138 kVActive
AH1-637Oak Grove 34.5 kVActive
AH1-644Spicewood Metering 138 kVActive
AH1-664Goddard-Plumville 138 kVActive
AH1-665Goddard-Plumsville 138 kV IIActive
AH1-666Flemingsburg - Spurlock 138 kVActive
AH1-669Circleville-Biers Run 138 kVActive
AH1-670Blue Mound-Chestnut 345 kVActive
AH1-677Rogers Road 500 kVActive
AH1-678Heritage 500 kVActive
AH1-679Four Rivers 230 kVActive
AH1-681Cunningham 500 kVActive
AH1-686Hanging Rock 765 kVActive
AH1-687Bear Garden 230kVActive
AH1-690Bay Shore - Lallendorf 345 kVActive
AH1-702Byron 345 kVActive
AH1-712Cunningham 500 kVActive
AH1-716Surry-Skiffes Creek 500kVActive
AH1-717Surry 230kVActive
AH1-718Nelson 345 kVActive
AH1-721Laurel-Cooper 161 kVActive
AH1-723Cunningham 500 kVActive
U2-030Four Mile Ridge Wind 138kVIn Service
U2-073Frostburg 138kV IIIn Service
V3-007Desoto-Tanners Creek #1 345kVIn Service
V4-067Cates Road Egg Harbor Township 12kVDeactivated
W1-003Oak HallIn Service
W1-004Oak HallIn Service
W1-005Oak HallIn Service
W1-006Oak HallIn Service
W1-130Vine Road 12kVIn Service
W2-030Egg Harbor TownshipIn Service
W2-048Brokaw-LanesvilleIn Service
W4-005Blue Mound-LathamIn Service
X2-022Brokaw-LanesvilleIn Service
X3-066Church Hill 69kVIn Service
Y1-033Penn Mar-Rock Wood 115kVIn Service
Y1-049Wurno 34.5kVIn Service
Y1-079Wye Mills 69kVIn Service
Y1-080Dorchester 12kVIn Service
Y1-086Morgans CornerIn Service
Y3-024Bluff Point 12kVIn Service
Y3-058Rockawalkin 69kVIn Service
Z1-036WinFall-Chowan 230kVIn Service
Z2-027Pasquotank 34.5kVIn Service
Z2-044Whitakers 34.5kVIn Service
Z2-076Worcester South 25kVIn Service
Z2-077Worcester North 25kVIn Service
Z2-087Pontiac MidPoint-Brokaw 345kVIn Service
Z2-115Deer Creek 12.47kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)Identified Impacts

No cost allocated AFS Tie Line reinforcements were identified for this project in the Phase I System Impact Study load flow analysis.


System Reinforcement
Type
Load Flow
TO
CPLE
RTEP ID / TO ID
(Pending) / TC2-CPLE-0001
Title
Person - VP Hendrick 230kV Line (Existing Line Uprate)
Description
Currently no costs since there is already a DEP project to reconductor to upgrade this line. This is the estimated ISD for the current project CPLE is developing. The Person - Hendrick 230 kV line will be reconductored with bundled 795 ACSS/TW and will have a rating 1195MVA.
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
0 to 48 Months

Info

Note: AH1-164 contributes to the loading of an overloaded tie line facility between PJM and an affected system entity, which was identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line and will be confirmed in subsequent study phases, along with cost allocation of such upgrade if applicable, in coordination with the affected system.

FacilityContingency
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line(Any)

Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with potential Affected System impacts. PJM initiates coordination with each Affected System Operator by providing a list of New Service Requests in the Cycle with potential impacts to their respective system. If the Affected System Operator indicates an Affected System Study is required, PJM will notify the Project Developer or Eligible Customer of the need for an Affected System Study. See below if any Affected System Operator requires a study for this project:

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

No cost allocated system reinforcements were identified for this project in the Phase I System Impact Study load flow analysis.

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement: b4000.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.1
Title
Add two 765 kV breakers at Amos Substation to expand the breaker and a half scheme to accommodate the new Amos-Welton Spring 765 kV line (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-164 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-164 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.2
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.2
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - AEP Section of the line is 30 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-164 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-164 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.3
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.3
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - APS/FE Section of the line is 145 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-164 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-164 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.4
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.4
Title
Construct a new 765 kV switchyard - Welton Spring (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-164 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-164 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.5
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.5
Title
Install four 250 MVAR shunt capacitors, and a +/-500 MVAR STATCOM at Welton Spring 765 kV substation
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-164 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-164 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.7
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.7
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line - in DVP local area/Millville to Lovettsville section, roughly 10.5 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-164 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-164 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.8
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.8
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (DVP local area to Rocky Point, roughly 4.8 miles)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-164 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-164 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.9
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.9
Title
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard (Projected ISD 6/1/2029)
Description
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard. Loop in the Doubs-Goose Creek 500 kV line, the Doubs-Aspen 500 kV line, and the Woodside-Goose Creek 500 kV line. Install two 765/500 kV transformer at Rocky Point substation. 765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-164 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-164 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.11
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.11
Title
Expand Black Oak Substation & Loop in the 502 Jct-Woodside 500 kV line (Projected ISD 6/1/2029)
Description
Expand Black Oak Substation to accommodate the connection of the 502 Jct-Woodside 500 kV line and loop the 502 Jct-Woodside 500 kV line into the Black Oak substation by constructing ~0.85 miles of new 500 kV line into and out of Black Oak 500 kV substation
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-164 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-164 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.10
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.10
Title
Install four 250 MVAR cap banks (two on 765 and two on 500 kV side) and a +/-500 MVAR STATCOM on the 765 kV Rocky Point yard
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-164 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-164 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.6
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.6
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (Welton Spring to DVP local area, roughly 21 miles) (VA Portion)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-164 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-164 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0044
Title
Wreck and rebuild 4.5 miles of 230 kV Line 2204 between Black Walnut and Edmonson with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Description
Wreck and rebuild 4.5 miles of 230 kV Line 2204 between Black Walnut and Edmonson with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Total Cost ($USD)
$17,100,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 42 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-164 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-164 could receive cost allocation. Although AH1-164 may not presently have cost responsibility for this upgrade, AH1-164 is a potential Aggregate Pool Contributor.

FacilityContingency
6BLACK WALNU-6EDMONSON 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2043
Title
Wreck and rebuild 0.93 miles of 230 kV Line 2241 between Hendrick and Persons with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C. Dominion portion of line only.
Description
Wreck and rebuild 0.93 miles of 230 kV Line 2241 between Hendrick and Persons with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C. Dominion portion of line only.
Total Cost ($USD)
$3,534,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 42 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-164 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-164 could receive cost allocation. Although AH1-164 may not presently have cost responsibility for this upgrade, AH1-164 is a potential Aggregate Pool Contributor.

FacilityContingency
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0045
Title
Wreck and rebuild 8.3 miles of 230 kV Line 2250 between Edmonson and Sedge Hill with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Description
Wreck and rebuild 8.3 miles of 230 kV Line 2250 between Edmonson and Sedge Hill with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Total Cost ($USD)
$31,540,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 42 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-164 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-164 could receive cost allocation. Although AH1-164 may not presently have cost responsibility for this upgrade, AH1-164 is a potential Aggregate Pool Contributor.

FacilityContingency
6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.357
Title
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Description
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-164 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-164 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.341
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.341
Title
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.
Description
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV substation and extend approximately 0.2 miles of conductor to fly-over the site.
Cost Information
Time Estimate
Jul 13 2029

Not Contingent

Note: AH1-164 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-164 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.342
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.342
Title
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Description
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Cost Information
Time Estimate
Jul 13 2029

Not Contingent

Note: AH1-164 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-164 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.355
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.355
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-164 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-164 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)

System Reinforcement: n9249.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9249.0 / TC1-PH2-DOM-043
Title
Construct new 37.26 mile line between Midlothian and Carson with (3) 1351.5 ACSR (45/7) "Dipper" at 110 degrees C. Station upgrades at Midlothian and Carson to accommodate new line.
Description
Construct new 37.26 mile line between Midlothian and Carson with (3) 1351.5 ACSR (45/7) "Dipper" at 110 degrees C. Station upgrades at Midlothian and Carson to accommodate new line. New Rating = 4356/4356/5009 MVA
Total Cost ($USD)
$231,012,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 60 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-164 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-164 could receive cost allocation. Although AH1-164 may not presently have cost responsibility for this upgrade, AH1-164 is a potential Aggregate Pool Contributor.

FacilityContingency
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-S

System Reinforcement: n9139.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9139.0 / TC1-PH1-DOM-073
Title
Wreck and rebuild 37.41 miles of 500kV line 563 between Midlothian and Carson with (3) 1351.5 ACSR (45/7) "Dipper" and associated substation work.
Description
Wreck and rebuild 37.41 miles of 500kV transmission line 563 between Midlothian and Carson with (3) 1351.5 ACSR (45/7) "Dipper" at 110 degrees C and associated substation work to achieve new rating of 4356/4356/5009 MVA. Remove wave traps.
Total Cost ($USD)
$245,455,768
Allocated Cost ($USD)
$0
Time Estimate
69 to 70 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-164 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-164 could receive cost allocation. Although AH1-164 may not presently have cost responsibility for this upgrade, AH1-164 is a potential Aggregate Pool Contributor.

FacilityContingency
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-S

System Reinforcement: b4000.325
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.325
Title
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Description
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Cost Information
Time Estimate
Feb 24 2029

Not Contingent

Note: AH1-164 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-164 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.326
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.326
Title
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Description
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Cost Information
Time Estimate
Feb 24 2029

Not Contingent

Note: AH1-164 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-164 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.327
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.327
Title
Upgrade/install equipment at Ladysmith Substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230 kV strings of breaker and a half scheme.
Description
Upgrade/install equipment at Ladysmith substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230kV strings of breaker and a half scheme.
Cost Information
Time Estimate
Feb 24 2029

Not Contingent

Note: AH1-164 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-164 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)

System Reinforcement: n9191.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9191.0 / TC1-PH1-DOM-090
Title
Rebuild 41.13 miles of line 576 between North Anna and Midlothian with triple bundled (3) 1351.5 ACSR (45/7) "Dipper" conductor and associated substation work.
Description
Rebuild 41.13 miles of line 576 between North Anna and Midlothian with triple bundled (3) 1351.5 ACSR (45/7) "Dipper" conductor at 110 degrees C and associated substation work to achieve new rating of 4356/4356/5009 MVA.
Total Cost ($USD)
$256,706,175
Allocated Cost ($USD)
$0
Time Estimate
74 to 75 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-164 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-164 could receive cost allocation. Although AH1-164 may not presently have cost responsibility for this upgrade, AH1-164 is a potential Aggregate Pool Contributor.

FacilityContingency
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 lineDVP_P1-2: LN 576_SRT-S
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 lineDVP_P4-2: WT576_SRT-S
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 lineDVP_P4-2: 57602_SRT-S

System Reinforcement: b4000.344
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.344
Title
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AH1-164 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-164 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.345
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.345
Title
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AH1-164 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-164 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.346
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.346
Title
Cut-in 500kV line from Kraken substation into Yeat substation
Description
Cut-in 500kV line from Kraken substation into Yeat substation
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-164 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-164 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.348
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.348
Title
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.
Description
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers. A new redundant breaker ring will be added at Kraken to accommodate the new 500kV line from North Anna to Kraken.
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-164 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-164 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.349
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.349
Title
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Description
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AH1-164 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-164 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.351
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.351
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AH1-164 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-164 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.352
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.352
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AH1-164 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-164 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)

System Reinforcement: n9248.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9248.0 / TC1-PH2-DOM-042
Title
Construct new 41.13 mile line between North Anna and Midlothian with (3) 1351.5 ACSS TW/HS285 (42/19) "MARTIN" at 145 degrees C. Station upgrades at North Anna and Midlothian to accommodate new line.
Description
Construct new 41.13 mile line between North Anna and Midlothian with (3) 1351.5 ACSS TW/HS285 (42/19) "MARTIN" at 145 degrees C. Station upgrades at North Anna and Midlothian to accommodate new line.
Total Cost ($USD)
$345,766,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 60 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-164 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-164 could receive cost allocation. Although AH1-164 may not presently have cost responsibility for this upgrade, AH1-164 is a potential Aggregate Pool Contributor.

FacilityContingency
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 lineDVP_P1-2: LN 576_SRT-S
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 lineDVP_P4-2: WT576_SRT-S
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 lineDVP_P4-2: 57602_SRT-S

System Reinforcement: b4000.350
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.350
Title
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Description
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AH1-164 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-164 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.356
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.356
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-164 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-164 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)

Attachments

AH1-164 One Line Diagram

AH1-164 One Line Diagram.jpg
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.