AH1-188 Phase I Study Report

v1.00 released 2025-10-29 21:25

Pigeon Creek 138 kV

84.0 MW Capacity / 140.0 MW Energy

Introduction

This Phase I System Impact Study Report (PH1) has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, sections 307 and 308 for New Service Requests (projects) in Transition Cycle 2. The Project Developer/Eligible Customer (developer) is Twisted Gun Solar, LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is American Electric Power.

Preface

The Phase I System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle executive summary format and (ii) an individual project-level basis. The Phase I System Impact Study Results (for both the executive summary and individual reports) will be publicly available on PJM’s website. Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.3, PJM takes the following actions during the Phase I System Impact Study:
  1. PJM studies each New Service Request on a summer peak, winter peak and light load RTEP base case study. The case year is dependent on the new services cycle under study. PJM will identify the base case year to be used in the study of a specific cycle on its website.
  2. PJM will only perform load flow analysis during the Phase I System Impact Study.
  3. In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with Affected System impacts and provides each Affected System Operator with a list of New Service Request in the Cycle with potential impacts to their respective system.
  4. PJM will create both the short circuit and stability base cases to be used in the Phase II System Impact Study.
  5. The Phase I System Impact Study results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.
The Transmission Owner takes the following actions during the Phase I System Impact Study:
  1. Identify required Interconnection Facilities to accommodate the New Service Request.
  2. Identify required Network Upgrades to mitigate system violations from the Phase I System Impact Study.
  3. Provide planning-level preliminary estimates of Interconnection Facilities and Network Upgrades including scope, cost and elapsed time to complete the work.

Decision Point I Requirements

At the close of Phase I System Impact Study, PJM will initiate Decision Point I (DP1). During DP1, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.A.1. Additional information on these elements is available in PJM Manual 14H sections 4.4, 6, and 7.

Allowable project modifications at Decision Point I are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

General

The Project Developer has proposed a Solar generating facility located in the American Electric Power zone — Mingo County, West Virginia. The installed facilities will have a total capability of 140.0 MW with 84.0 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AH1-188
Project Name:
Pigeon Creek 138 kV
Project Developer Name:
Twisted Gun Solar, LLC
State:
West Virginia
County:
Mingo
Transmission Owner:
American Electric Power
MFO:
140.0
MWE:
140.0
MWC:
84.0
Fuel Type:
Solar
Basecase Study Year:
2028

Physical Interconnection Facility Study

Physical Interconnection Facilities Study is not performed as part of the Phase I System Impact Study. Physical Interconnection Facilities Study will commence in the Phase II System Impact Study.

Point of Interconnection

AH1-188 will interconnect on the American Electric Power transmission system at the Pigeon Creek 138 kV substation.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In the Phase I SIS, the costs shown are subject to change as a result of a facility study performed by the TO during the Phase II or Phase III System Impact Study.

Based on the Phase I SIS results, the AH1-188 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit are also shown below.

Cost Summary
DescriptionCost Allocated to AH1-188Cost Subject to Readiness*
Transmission Owner Interconnection Facilities (TOIF)$0$0
Other Scope$0$0
Option To Build Oversight$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$69,534,792$69,534,792
Network Upgrades$0$0
System Reliability Network Upgrades
Steady State Thermal & Voltage (SP & LL)$0$0
Transient Stability$0$0
Short Circuit$0$0
Transmission Owner Analysis
SubRegional$0$0
Distribution$62,066$0
Affected System Reinforcements
AFS - PJM Violatons$0$0
AFS - Non-PJM Violations$0$0
Total$69,596,858$69,534,792

* Contributes to calculation for Readiness Deposit #2 (RD2). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim deliverability study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 309 (Decision Point I) A.1.a.i and PJM Manual 14H, section 6.2, Readiness Deposit #2 (RD2) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point I (DP1), the Project Developer or Eligible Customer is required to submit Readiness Deposit #2, which is calculated as 10% of cost allocation for required Phase I Network Upgrades minus Readiness Deposit #1.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Readiness Deposit #2 Due for Project AH1-188

Readiness Deposit #2 has been calculated for the project based on the Phase I System Impact Study results and is shown in the table below. This Readiness Deposit #2 must be provided at Decision Point I through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit
Project ID10% of cost allocation for Phase I Network UpgradesReadiness Deposit #1 Received (RD1)Readiness Deposit #2 (RD2) for AH1-188 Project due at DP1
ABA - B
AH1-188$6,953,479$560,000$6,393,479

Note: Failure to provide an acceptable form of Readiness Deposit #2 by the end of Decision Point I will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Stand-Alone Network Upgrades
RTEP IDDescriptionTotal Cost ($USD)Allocated Cost ($USD)
(Pending)AEP will construct a new ring bus station, initially populated with 4 breakers.$69,534,792 $69,534,792

Based on the scope of work for the Interconnection Facilities, it is expected to take a range of 24 to 30 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

The schedule for any required Network Impact Reinforcements will be more clearly identified in the Phase II and Phase III System Impact Studies.

Transmission Owner Analysis

Transmission Owner Identified Network Impacts

The Transmission Owner identified network impacts to Distribution facilities as follows:

Transmission Owner Identified Network Impacts to Distribution Facilities
Overloaded ElementContingencyRating [MVA]Final Cycle Loading %Contribution [MW]
244480 05CHAUNCEY 46.0 - 244511 05RICH CRK 46.0 CKT 1 AEP_P4_#14137_05LOGAN1 138_F_SRT-A
CONTINGENCY 'AEP_P4_#14137_05LOGAN1 138_F_SRT-A'  

  OPEN BRANCH FROM BUS 242704 TO BUS 242705 CKT Z1                 / 242704 05LOGAN1 138 242705 05LOGAN2 138 Z1

  OPEN BRANCH FROM BUS 242704 TO BUS 242726 CKT 1                  / 242704 05LOGAN1 138 242726 05MUDFRK 138 1

  OPEN BRANCH FROM BUS 242704 TO BUS 290392 CKT 1                  / 242704 05LOGAN1 138 290392 05ARGYLE 138 1

  OPEN BRANCH FROM BUS 242704 TO BUS 290391 CKT 1                  / 242704 05LOGAN1 138 290391 05TIN BRANCH 138 1

  OPEN BRANCH FROM BUS 242705 TO BUS 242809 CKT 1                  / 242705 05LOGAN2 138 242809 05SPRIG1 138 1

  OPEN BRANCH FROM BUS 242705 TO BUS 242735 CKT 1                  / 242705 05LOGAN2 138 242735 05NPOINT 138 1

  OPEN BRANCH FROM BUS 242705 TO BUS 247634 CKT 1                  / 242705 05LOGAN2 138 247634 05LYBURN SS 138 1

  REMOVE LOAD D4 FROM BUS 242704                                   / 242704 05LOGAN1 138 D4

  REMOVE SWSHUNT FROM BUS 242704                                   / 242704 05LOGAN1 138

  REMOVE SWSHUNT FROM BUS 242705                                   / 242705 05LOGAN2 138

END
29.0115.52 %13.04
244511 05RICH CRK 46.0 - 244498 05HUFFCRK 46.0 CKT 1 AEP_P4_#14137_05LOGAN1 138_F_SRT-A
CONTINGENCY 'AEP_P4_#14137_05LOGAN1 138_F_SRT-A'  

  OPEN BRANCH FROM BUS 242704 TO BUS 242705 CKT Z1                 / 242704 05LOGAN1 138 242705 05LOGAN2 138 Z1

  OPEN BRANCH FROM BUS 242704 TO BUS 242726 CKT 1                  / 242704 05LOGAN1 138 242726 05MUDFRK 138 1

  OPEN BRANCH FROM BUS 242704 TO BUS 290392 CKT 1                  / 242704 05LOGAN1 138 290392 05ARGYLE 138 1

  OPEN BRANCH FROM BUS 242704 TO BUS 290391 CKT 1                  / 242704 05LOGAN1 138 290391 05TIN BRANCH 138 1

  OPEN BRANCH FROM BUS 242705 TO BUS 242809 CKT 1                  / 242705 05LOGAN2 138 242809 05SPRIG1 138 1

  OPEN BRANCH FROM BUS 242705 TO BUS 242735 CKT 1                  / 242705 05LOGAN2 138 242735 05NPOINT 138 1

  OPEN BRANCH FROM BUS 242705 TO BUS 247634 CKT 1                  / 242705 05LOGAN2 138 247634 05LYBURN SS 138 1

  REMOVE LOAD D4 FROM BUS 242704                                   / 242704 05LOGAN1 138 D4

  REMOVE SWSHUNT FROM BUS 242704                                   / 242704 05LOGAN1 138

  REMOVE SWSHUNT FROM BUS 242705                                   / 242705 05LOGAN2 138

END
29.0114.72 %13.04
244558 05SPRIGG 46.0 - 244550 05GRAPEVIN 46.0 CKT 1 AEP_P4_#14137_05LOGAN1 138_F_SRT-A
CONTINGENCY 'AEP_P4_#14137_05LOGAN1 138_F_SRT-A'  

  OPEN BRANCH FROM BUS 242704 TO BUS 242705 CKT Z1                 / 242704 05LOGAN1 138 242705 05LOGAN2 138 Z1

  OPEN BRANCH FROM BUS 242704 TO BUS 242726 CKT 1                  / 242704 05LOGAN1 138 242726 05MUDFRK 138 1

  OPEN BRANCH FROM BUS 242704 TO BUS 290392 CKT 1                  / 242704 05LOGAN1 138 290392 05ARGYLE 138 1

  OPEN BRANCH FROM BUS 242704 TO BUS 290391 CKT 1                  / 242704 05LOGAN1 138 290391 05TIN BRANCH 138 1

  OPEN BRANCH FROM BUS 242705 TO BUS 242809 CKT 1                  / 242705 05LOGAN2 138 242809 05SPRIG1 138 1

  OPEN BRANCH FROM BUS 242705 TO BUS 242735 CKT 1                  / 242705 05LOGAN2 138 242735 05NPOINT 138 1

  OPEN BRANCH FROM BUS 242705 TO BUS 247634 CKT 1                  / 242705 05LOGAN2 138 247634 05LYBURN SS 138 1

  REMOVE LOAD D4 FROM BUS 242704                                   / 242704 05LOGAN1 138 D4

  REMOVE SWSHUNT FROM BUS 242704                                   / 242704 05LOGAN1 138

  REMOVE SWSHUNT FROM BUS 242705                                   / 242705 05LOGAN2 138

END
18.0118.77 %4.8
244558 05SPRIGG 46.0 - 244550 05GRAPEVIN 46.0 CKT 1 AEP_P7-1_#10809___SRT-A
CONTINGENCY 'AEP_P7-1_#10809___SRT-A'  

  OPEN BRANCH FROM BUS 242705 TO BUS 242809 CKT 1                  / 242705 05LOGAN2 138 242809 05SPRIG1 138 1

  OPEN BRANCH FROM BUS 290391 TO BUS 290518 CKT 1                  / 290391 05TIN BRANCH 138 290518 05HOLDEN 138 1

  OPEN BRANCH FROM BUS 242761 TO BUS 290518 CKT 1                  / 242761 05RAGLDZ 138 290518 05HOLDEN 138 1

END
18.0111.71 %5.48

There were no network impacts to Sub-Regional facilities identified by the Transmission Owner.

Transmission Owner Identified System Reinforcements
AH1-188 Transmission Owner Identified System Reinforcements Cost Breakdown:
TORTEP ID / TO IDCategoryTitleMW ImpactPercent AllocationAllocated Cost ($USD)
AEP(Pending) / TC2-AEP-185DistributionChauncey - Rich Creek: Sag study ~3.5 miles of 46kV line13.0 MW62.1%$24,826
AEP(Pending) / TC1-AEP-186DistributionRich Creek - Huff Creek: Sag study ~5.25 miles of 46kV line13.0 MW62.1%$37,239
Grand Total:$62,065

System Reinforcement
TO
AEP
RTEP ID / TO ID
(Pending) / TC2-AEP-185
Category
Distribution
Title
Chauncey - Rich Creek: Sag study ~3.5 miles of 46kV line
Description
Chauncey - Rich Creek: Sag study ~3.5 miles of 46kV line
Total Cost
$40,000
Contributor
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-1843.3 MW15.6%$6,245
AH1-18813.0 MW62.1%$24,826
AH1-6173.1 MW14.9%$5,959
AH1-6441.6 MW7.4%$2,970

System Reinforcement
TO
AEP
RTEP ID / TO ID
(Pending) / TC1-AEP-186
Category
Distribution
Title
Rich Creek - Huff Creek: Sag study ~5.25 miles of 46kV line
Description
Rich Creek - Huff Creek: Sag study ~5.25 miles of 46kV line
Total Cost
$60,000
Contributor
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-1843.3 MW15.6%$9,367
AH1-18813.0 MW62.1%$37,239
AH1-6173.1 MW14.9%$8,939
AH1-6441.6 MW7.4%$4,455

System Reinforcement: s3147.30
TO
AEP
RTEP ID / TO ID
s3147.30
Category
Distribution
Title
Grapevine Station - Removal of the Distribution station and equipment.
Description
Grapevine Station - Removal of the Distribution station and equipment.
Total Cost
$0
Contingent

Note: Although Queue Project AH1-188 may not have cost responsibility for this upgrade, Queue Project AH1-188 may need this upgrade in-service to be deliverable to the PJM system. If Queue Project AH1-188 comes into service prior to completion of the upgrade, Queue Project AH1-188 will need an interim study.

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. AEP interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Meteorological Data Reporting Requirement
The solar generation facility shall provide the Transmission Provider with site-specific meteorological data including:
  • Temperature (degrees Fahrenheit)
  • Atmospheric Pressure (hectopascals)
  • Irradiance
  • Forced outage data
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AH1-188 was evaluated as a 140.0 MW (84.0 MW Capacity) injection in the AEP area.

AH1-188 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 140.0 MW (140.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AEP
05CLOV17_XFL-05CLOVRD 345.0 kV Ckt 17 line
AEP_P4_#7421_05CLOVRD 765_BB2_SRT-A
BreakerAC107.8 %2320.0B2500.929.19
GD2AEP
05CLOV17_XFL-05CLOVRD 345.0 kV Ckt 17 line
AEP_P1-3_#7421_05CLOVRD 765_14_SRT-A
SingleAC106.66 %2320.0B2474.486.41
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AP_P1-3_MP-765-501T_SRT-A
SingleAC121.06 %3393.4B4107.9713.15
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AP_P2-3_MP-500-020_SRT-SL
BreakerAC117.02 %3610.0B4224.5518.93
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AP_P2-3_MP-500-021_SRT-SL
BreakerAC116.77 %3610.0B4215.4318.88
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AEP_P4_#37_05MOUNTN 765_B1_SRT-A
BreakerAC116.68 %3610.0B4211.9818.85
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AEP_P4_#2942_05KAMMER 765_PP_SRT-A
BreakerAC116.36 %3610.0B4200.4318.86
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P4_#8075_05MARYSV 765_A2_SRT-A
BreakerAC118.92 %5523.0B6567.8223.76
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P4_#8980_05KAMMER 765_QQ2_SRT-A
BreakerAC116.66 %5523.0B6443.1124.06
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P1-2_#17217_SRT-A
SingleAC115.67 %5523.0B6388.3216.79
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P4_#7445_05MARYSV 765_B_SRT-A
BreakerAC113.05 %5523.0B6243.5325.36
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P4_#17219_05GUERNSEY 765_A_SRT-A
BreakerAC112.12 %5523.0B6192.1724.25
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Base Case
SingleAC108.86 %4558.0A4961.8515.3
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A
BreakerAC108.47 %5523.0B5991.0226.09
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P2-2_#7222_05MALIS 765_1_SRT-A
BusAC107.09 %5523.0B5914.3223.03
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P1-2_#7422_16_SRT-A
SingleAC106.56 %5523.0B5885.3418.2
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P7-1_#10944___SRT-A
TowerAC106.16 %5523.0B5863.4724.8
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P7-1_#10856___SRT-A
TowerAC102.19 %5523.0B5644.1424.98
GD2DVP
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line
DVP_P7-1: LN 2168-555_SRT-A
TowerAC105.49 %3940.0C4156.412.19
GD2DVP
8VALLEY SC-8VALLEY 500.0 kV Ckt 1 line
DVP_P7-1: LN 2168-555_SRT-A
TowerAC105.23 %3940.0C4145.8812.19

Details for 05CLOV17_XFL-05CLOVRD 345.0 kV Ckt 17 line l/o AEP_P4_#7421_05CLOVRD 765_BB2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05CLOV17_XFL-05CLOVRD 345.0 kV Ckt 17 line
Contingency Name:
AEP_P4_#7421_05CLOVRD 765_BB2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.8 %
Rating:2320.0 MVA
Rating Type:B
MVA to Mitigate:2500.92
MW Contribution:9.19
Bus #Bus NameTypeMW Contribution
943031AE2-326 GEN
Solar/Wind Harmer
3.913
960911AF2-382 GEN
Solar/Wind Harmer
5.848
972103AH1-617 GEN
Solar/Wind Harmer
13.923
971155AH1-034 GEN
Solar/Wind Harmer
5.827
960741AF2-365 GEN
Solar/Wind Harmer
2.839
270030AE2-140 GEN
Solar/Wind Harmer
10.994
276668AB2-070 GEN1
Solar/Wind Harmer
1.072
24728505AND G1
Adder
1.803
274767LEE CO EC;8U
Adder
4.299
24721905FLATG4
Adder
9.459
25194608D.CRK4
Adder
0.756
274682WAUKEGAN ;7U
Adder
8.262
316192AB2-158 GEN
Solar/Wind Helper
0.985
316336AC2-165 C
Solar/Wind Helper
0.729
3142416OLDCHRC
Solar/Wind Helper
0.318
3142416OLDCHRC
Solar/Wind Helper
0.122
316097T157 G90
Solar/Wind Helper
0.556
3142433PROV 92
Solar/Wind Helper
0.448
971461AH1-227 GEN
Solar/Wind Harmer
3.853
24686205CER G4
Adder
4.732
3429391JKCT 9G
Adder
4.484
958171AF2-111 GEN
Solar/Wind Harmer
12.227
970519AG2-331 GEN
Solar/Wind Harmer
8.438
970699AG2-449 GEN
Solar/Wind Harmer
5.582
970193AG2-126 GEN
Solar/Wind Harmer
7.161
24728705AND G3
Adder
3.77
274853TWINGROVE;U1
Solar/Wind Harmer
3.387
959611AF2-252 GEN
Solar/Wind Harmer
1.093
25196608WSDLE5
Adder
3.936
3147666LOUISA
Solar/Wind Helper
0.583
958121AF2-106 GEN
Solar/Wind Helper
1.048
970281AG2-184 GEN
Solar/Wind Harmer
14.619
962211AG1-066 GEN
Solar/Wind Harmer
1.642
972203AH1-686 GEN
Adder
1.34
276849AB2-070 GEN2
Solar/Wind Harmer
1.072
276848AB2-070 GEN3
Solar/Wind Harmer
1.072
276785W4-005 GEN1
Solar/Wind Harmer
1.442
274848CAMPGROVE;RU
Solar/Wind Harmer
3.031
961011AF2-392 GEN
Solar/Wind Harmer
5.096
959341AF2-225 GEN
Solar/Wind Harmer
7.015
274744AC1-111 GEN8
Adder
2.558
274735ELWOOD EC;4P
Adder
2.023
3148463FAIRFLD
Solar/Wind Helper
0.398
24735205WLF2G2
Adder
4.909
24723205RIVRG3
Adder
11.619
270336AE1-100 GEN
Solar/Wind Harmer
1.013
964901AG1-354 GEN
Solar/Wind Harmer
8.682
339241AF1-083 GEN
Solar/Wind Harmer
0.951
24686105CER G3
Adder
4.757
971821AH1-427 GEN
Solar/Wind Harmer
5.664
943111AE2-339 GEN
Solar/Wind Harmer
0.467
943811AF1-049 GEN
Solar/Wind Harmer
1.99
945681AF1-233 GEN
Solar/Wind Harmer
9.348
270445AC2-157 GEN2
Solar/Wind Harmer
2.736
24728605AND G2
Adder
1.803
274877BISHOP HL;1U
Solar/Wind Harmer
1.583
24721705FLATG2
Adder
9.459
25194608D.CRK4
Adder
0.756
274828WAUKEGAN ;BP
Adder
5.081
274682WAUKEGAN ;7U
Adder
8.262
274745AC1-111 GEN9
Adder
2.558
316499AE2-029_GEN
Solar/Wind Helper
0.937
966881AG1-559 GEN
Solar/Wind Helper
0.168
316473AC1-191 GEN
Solar/Wind Helper
0.759
316095T157 G97
Solar/Wind Helper
0.556
3142946ENON
Solar/Wind Helper
0.038
270214AC2-123 GEN
Solar/Wind Harmer
2.486
971225AH1-072 GEN
Solar/Wind Harmer
1.502
971227AH1-073 GEN
Solar/Wind Harmer
1.502
24723005RIVRG1
Adder
11.619
24723105RIVRG2
Adder
11.619
24685805CER G1
Adder
4.726
24685905CER G2
Adder
4.726
971125AH1-004 GEN
Solar/Wind Harmer
2.1
270444AC2-157 GEN1
Solar/Wind Harmer
2.736
276916AD2-100_GEN
Solar/Wind Harmer
10.174
957381AF2-032 GEN
Solar/Wind Harmer
0.202
276763AC1-053 GEN1
Solar/Wind Harmer
1.888
276764AC1-053 GEN2
Solar/Wind Harmer
1.888
276741O09 GEN1
Solar/Wind Harmer
1.678
274849CRESCENT ;1U
Solar/Wind Harmer
0.866
315651AD1-115 GEN
Solar/Wind Helper
0.441
316447AC1-158 HLD
Solar/Wind Helper
1.451
3142946ENON
Solar/Wind Helper
0.011
316487AF1-042 GEN
Solar/Wind Helper
0.113
339236AF1-050_GEN
Solar/Wind Harmer
1.045
960161AF2-307 GEN
Solar/Wind Harmer
3.502
970107AG2-081 GEN
Solar/Wind Harmer
1.575
970235AG2-159 GEN
Solar/Wind Harmer
2.014
970235AG2-159 GEN
Solar/Wind Harmer
1.23
970239AG2-162 GEN
Solar/Wind Harmer
5.35
270186AC1-089 GEN
Solar/Wind Harmer
2.887
276645AC1-214 GEN1
Solar/Wind Harmer
0.627
276603SUBLETTE C
Solar/Wind Harmer
0.491
274762LEE CO EC;3U
Adder
4.35
970241AG2-163 GEN
Solar/Wind Harmer
11.684
938861AE1-114 GEN
Solar/Wind Harmer
3.828
274856ECOGROVE ;U1
Solar/Wind Harmer
1.572
276611AD2-172 GEN
Solar/Wind Harmer
1.193
274696ROCKY RD ;4P
Adder
5.238
971485AH1-239 GEN
Solar/Wind Harmer
4.843
964781AG1-341 GEN
Solar/Wind Harmer
6.173
971081AG2-670 GEN
Solar/Wind Harmer
4.298
942891AE2-308 GEN
Solar/Wind Harmer
5.447
972043AH1-570 GEN
Solar/Wind Harmer
1.293
945391AF1-204 GEN
Solar/Wind Harmer
6.653
960611AF2-352 GEN
Solar/Wind Harmer
1.093
276782AC1-033 GEN
Solar/Wind Harmer
1.871
276708O09 GEN2
Solar/Wind Harmer
1.678
972267AH1-718 GEN
Adder
1.953
274764LEE CO EC;5U
Adder
4.36
25194408D.CRK1
Adder
3.478
274683WAUKEGAN ;8U
Adder
9.693
274683WAUKEGAN ;8U
Adder
8.17
274693ROCKY RD ;1P
Adder
5.067
24728905RICHG2
Adder
1.728
3132123MT JACKSON
Solar/Wind Helper
0.746
966001AG1-469 GEN
Solar/Wind Helper
0.172
24735105WLF2G1
Adder
4.909
24734805WLF1G4
Adder
4.898
270400AC1-102 GEN
Solar/Wind Harmer
2.775
957241AF2-018 GEN
Solar/Wind Harmer
2.86
970455AG2-298 GEN
Solar/Wind Harmer
3.268
3429211JKCT 2G
Adder
6.351
339243AC2-075 GEN1
Solar/Wind Harmer
0.233
972163AH1-664 GEN
Solar/Wind Harmer
4.977
944221AF1-090 GEN
Solar/Wind Harmer
5.331
276655WTG1_EQ
Solar/Wind Harmer
4.083
25196508WSDLE4
Adder
3.896
274746AC1-111 G10
Adder
2.558
274731ELWOOD EC;2P
Adder
7.487
274733ELWOOD EC;3P
Adder
7.487
316164AC1-076 GEN
Solar/Wind Helper
0.618
23546401DTGZ2-030
Solar/Wind Helper
0.04
238152AF2-075_GEN
Solar/Wind Helper
0.304
316233AE1-074 FULL
Solar/Wind Helper
0.179
316223AC1-118
Solar/Wind Helper
0.173
3141813NORNECK
Solar/Wind Helper
0.113
971403AH1-188 GEN
Solar/Wind Harmer
9.188
970273AG2-179 GEN
Solar/Wind Harmer
1.456
971565AH1-281 GEN
Solar/Wind Harmer
1.077
3429421JKCT 10G
Adder
4.484
958131AF2-107 GEN
Solar/Wind Harmer
2.669
970091AG2-072 GEN
Adder
38.082
274854TWINGROVE;U2
Solar/Wind Harmer
3.316
276726Z2-087_GEN
Solar/Wind Harmer
3.699
963741AG1-226 GEN
Solar/Wind Harmer
21.031
971475AH1-234 GEN
Solar/Wind Harmer
10.445
24734705WLF1G3
Adder
4.898
24734905WLF1G5
Adder
4.898
966391AG1-508 GEN
Solar/Wind Harmer
2.785
971981AH1-535 GEN
Solar/Wind Harmer
7.897
972143AH1-644 GEN
Solar/Wind Harmer
6.961
270399AC1-101 GEN
Solar/Wind Harmer
2.775
965401AG1-405 GEN
Solar/Wind Harmer
3.385
339211AE2-254 GEN
Solar/Wind Harmer
0.854
972165AH1-665 GEN
Solar/Wind Harmer
3.982
946321AF1-296 GEN
Solar/Wind Harmer
4.942
276656WTG2_EQ
Solar/Wind Harmer
0.541
941731AE2-173 GEN
Solar/Wind Harmer
2.719
274823ROCKFORD ;21
Adder
9.057
3148013FISHERV
Solar/Wind Helper
0.165
3143873LANEXA
Solar/Wind Helper
0.067
24728305BUCHG2
Adder
3.631
962241AG1-070 GEN
Solar/Wind Harmer
2.607
24686505CER G6
Adder
4.751
3429241JKCT 3G
Adder
6.434
339216AC1-074 GEN
Solar/Wind Harmer
0.86
965911AG1-460 GEN
Solar/Wind Harmer
0.675
276615X2-022 GEN
Solar/Wind Harmer
0.939
963831AG1-236 GEN
Solar/Wind Harmer
4.696
274857EASY ROAD;U1
Solar/Wind Harmer
2.241
274822ROCKFORD ;11
Adder
9.123
3132273ORANGE
Solar/Wind Helper
0.03
316170AC1-121 GEN2
Solar/Wind Helper
0.204
316313AB2-026
Solar/Wind Helper
0.2
3146776BUCKING
Solar/Wind Helper
0.045
316484AD2-074 GEN
Solar/Wind Helper
0.215
970819AG2-516 GEN
Solar/Wind Harmer
0.945
971277AH1-098 GEN
Solar/Wind Harmer
3.314
24728205BUCHG1
Adder
3.631
944971AF1-162 GEN
Solar/Wind Harmer
4.505
966021AG1-471 GEN
Solar/Wind Harmer
3.284
339231AF1-038_GEN
Solar/Wind Harmer
1.082
339255AE2-071 GEN
Solar/Wind Harmer
0.618
970653AG2-424 GEN
Solar/Wind Harmer
2.668
970653AG2-424 GEN
Solar/Wind Harmer
0.965
964571AG1-320 GEN
Solar/Wind Harmer
4.432
972045AH1-571 GEN
Solar/Wind Harmer
1.035
339221AD2-048_GEN
Solar/Wind Harmer
0.789
274766LEE CO EC;7U
Adder
4.299
972235AH1-702 GEN1
Adder
1.172
315616AA1-038_C
Solar/Wind Helper
1.807
3148013FISHERV
Solar/Wind Helper
0.286
3147666LOUISA
Solar/Wind Helper
0.335
316405AF2-144 C
Solar/Wind Helper
0.15
238147AE2-230_GEN1
Solar/Wind Helper
0.213
316044AC1-158 PL1
Solar/Wind Helper
0.659
316450AC1-158 RIC
Solar/Wind Helper
0.176
3141906WESTMOR
Solar/Wind Helper
0.046
316404AE1-155 C
Solar/Wind Helper
0.945
276911AD2-131_GEN
Solar/Wind Harmer
2.056
274851PROVIDENC;RU
Solar/Wind Harmer
1.333
276646AC1-214 GEN2
Solar/Wind Harmer
0.627
274765LEE CO EC;6U
Adder
4.36
274763LEE CO EC;4U
Adder
4.309
25194508D.CRK3
Adder
0.65
274695ROCKY RD ;2P
Adder
5.117
24728805RICHG1
Adder
1.728
3146776BUCKING
Solar/Wind Helper
0.504
3146776BUCKING
Solar/Wind Helper
0.041
966871AG1-558 GEN
Solar/Wind Helper
0.167
274697ROCKY RD ;3P
Adder
1.39
315821AE2-092 GEN
Solar/Wind Helper
1.824
316468AD1-105 GEN
Solar/Wind Helper
0.61
316075AC2-137 C
Solar/Wind Helper
0.179
3143526WINTERP
Solar/Wind Helper
0.609
316077AC2-138 C
Solar/Wind Helper
0.106
971687AH1-348 GEN
Solar/Wind Harmer
0.747
971315AH1-136 GEN
Solar/Wind Harmer
1.275
970333AG2-219 GEN
Solar/Wind Harmer
15.351
274880W4-005 GEN4
Solar/Wind Harmer
1.442
972175AH1-670 GEN
Solar/Wind Harmer
6.469
25196008MFTGT1
Adder
0.655
276158O29GEN2
Solar/Wind Harmer
2.349
25196808ZIMRHP
Adder
35.531
939741AE1-205 GEN
Solar/Wind Harmer
9.353
274761LEE CO EC;2U
Adder
4.35
237061AD1-155 GEN
Solar/Wind Helper
0.025
316258AE1-075 C
Solar/Wind Helper
0.18
23583801GRNGAP
Solar/Wind Helper
2.125
238149AF1-291A_GEN
Solar/Wind Helper
0.061
3141196NOKESVL
Solar/Wind Helper
0.452
270053AF1-130 C
Solar/Wind Harmer
2.393
970273AG2-179 GEN
Solar/Wind Harmer
2.326
339250AF1-203 GEN
Solar/Wind Harmer
0.353
962251AG1-071 GEN
Solar/Wind Harmer
3.186
24686405CER G5
Adder
4.713
276686W4-005 GEN3
Solar/Wind Harmer
1.442
965931AG1-462 GEN
Solar/Wind Harmer
12.103
965091AG1-374 GEN
Solar/Wind Harmer
14.098
274878BISHOP HL;2U
Solar/Wind Harmer
1.583
274760LEE CO EC;1U
Adder
4.35
972236AH1-702 GEN2
Adder
1.02
3146776BUCKING
Solar/Wind Helper
0.05
238148AE2-230_GEN2
Solar/Wind Helper
0.214
316006AB2-029 C
Solar/Wind Helper
0.058
316045AC1-158 PL2
Solar/Wind Helper
2.111
316337AD2-073 GEN
Solar/Wind Helper
0.172
3141726DUNNSVL
Solar/Wind Helper
0.452
971313AH1-133 GEN
Solar/Wind Harmer
7.717
965411AG1-406 GEN
Solar/Wind Harmer
1.519
276174W4-005 GEN2
Solar/Wind Harmer
1.442
25196108MFTGT2
Adder
0.722
25196108MFTGT2
Adder
0.67
957751AF2-069 GEN
Solar/Wind Harmer
0.215
971681AH1-341 GEN
Solar/Wind Harmer
7.003
270367AC2-061_GEN
Solar/Wind Harmer
1.482
276612AE2-035 GEN
Solar/Wind Harmer
1.193
25196408WSDLE3
Adder
4.052
25196308WSDLE2
Adder
4.017
25196208WSDLE1
Adder
4.006
25196708WSDLE6
Adder
3.996
3148133STUARTS
Solar/Wind Helper
0.172
316312AB1-027
Solar/Wind Helper
0.233
3141426STAFORD
Solar/Wind Helper
0.025
316254AC1-120 GEN1
Solar/Wind Helper
0.611
3143226MDLTHAN
Solar/Wind Helper
0.117
3142543TWELFTH
Solar/Wind Helper
0.011
970563AG2-360 GEN
50/50
26.913
962751AG1-124 GEN
Solar/Wind Harmer
9.063
972273AH1-721 GEN
Adder
50.38
966571AG1-526 GEN
Solar/Wind Harmer
12.469
970093AG2-073 GEN
Solar/Wind Harmer
5.535
972167AH1-666 GEN
Solar/Wind Harmer
3.962
970243AG2-164 GEN
Solar/Wind Harmer
12.56
942481AE2-261 GEN
Solar/Wind Harmer
14.457
276621W2-048 GEN
Solar/Wind Harmer
2.989
276838X2-022 GEN2
Solar/Wind Harmer
0.111
971993AH1-541 GEN
Solar/Wind Harmer
4.403
25196008MFTGT1
Adder
0.634
276157O29GEN1
Solar/Wind Harmer
1.787
942111AE2-223 GEN
Solar/Wind Harmer
3.834
274858EASY ROAD;U2
Solar/Wind Harmer
2.241
274729ELWOOD EC;1P
Adder
7.487
3147983MERCK5
Solar/Wind Helper
0.107
316322AB2-045
Solar/Wind Helper
0.14
3143526WINTERP
Solar/Wind Helper
0.609
964211AG1-282 GEN
Solar/Wind Helper
0.152
3138266HYDRAULIC
Solar/Wind Helper
0.011
3138266HYDRAULIC
Solar/Wind Helper
0.007
316059AD1-063 C
Solar/Wind Helper
0.112
3141766HARMONY
Solar/Wind Helper
0.022
957141AF2-008_MTX
Adder
28.482
944201AF1-088_MTX
Adder
56.965
CBM West 1LTFEXP_CBM-W1->PJM
CBM
64.396
NYPJM->LTFIMP_NY
CLTF
1.478
TVALTFEXP_TVA->PJM
CLTF
6.219
AG2-052LTFEXP_AG2-052->PJM
LTF
0.105
CBM West 2LTFEXP_CBM-W2->PJM
CBM
73.214
LGEELTFEXP_LGEE->PJM
CLTF
3.565
MECLTFEXP_MEC->PJM
CLTF
8.32
AH1-155LTFEXP_AH1-155->PJM
LTF
0.158
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.657
WECLTFEXP_WEC->PJM
CLTF
1.782
LAGNLTFEXP_LAGN->PJM
CLTF
11.707
CBM South 2LTFEXP_CBM-S2->PJM
CBM
15.107
CPLELTFEXP_CPLE->PJM
CLTF
3.112
SIGELTFEXP_SIGE->PJM
CLTF
0.271

Details for 05CLOV17_XFL-05CLOVRD 345.0 kV Ckt 17 line l/o AEP_P1-3_#7421_05CLOVRD 765_14_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05CLOV17_XFL-05CLOVRD 345.0 kV Ckt 17 line
Contingency Name:
AEP_P1-3_#7421_05CLOVRD 765_14_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.66 %
Rating:2320.0 MVA
Rating Type:B
MVA to Mitigate:2474.48
MW Contribution:6.41
Bus #Bus NameTypeMW Contribution
971687AH1-348 GEN
Solar/Wind Harmer
0.521
971315AH1-136 GEN
Solar/Wind Harmer
0.889
970333AG2-219 GEN
Solar/Wind Harmer
2.429
274880W4-005 GEN4
Solar/Wind Harmer
0
972175AH1-670 GEN
Solar/Wind Harmer
2.731
971277AH1-098 GEN
Solar/Wind Harmer
2.312
24728205BUCHG1
Adder
3.631
944971AF1-162 GEN
Solar/Wind Harmer
4.505
966021AG1-471 GEN
Solar/Wind Harmer
2.291
339255AE2-071 GEN
Solar/Wind Harmer
-0.067
970653AG2-424 GEN
Solar/Wind Harmer
1.862
970653AG2-424 GEN
Solar/Wind Harmer
0.965
964571AG1-320 GEN
Solar/Wind Harmer
3.444
972045AH1-571 GEN
Solar/Wind Harmer
0.752
339221AD2-048_GEN
Solar/Wind Harmer
0.002
276911AD2-131_GEN
Solar/Wind Harmer
0.468
274851PROVIDENC;RU
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
0.128
274765LEE CO EC;6U
Adder
4.36
24735205WLF2G2
50/50
5.209
24723205RIVRG3
Adder
11.619
270336AE1-100 GEN
Solar/Wind Harmer
0.002
964901AG1-354 GEN
Solar/Wind Harmer
6.057
24686105CER G3
Adder
4.757
971821AH1-427 GEN
Solar/Wind Harmer
3.952
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
945681AF1-233 GEN
Solar/Wind Harmer
6.522
270445AC2-157 GEN2
Solar/Wind Harmer
0.002
24728605AND G2
Adder
1.803
274877BISHOP HL;1U
Solar/Wind Harmer
0.11
24721705FLATG2
Adder
9.459
957471AF2-041 GEN
Solar/Wind Harmer
9.717
24734705WLF1G3
50/50
5.198
24734905WLF1G5
50/50
5.198
966391AG1-508 GEN
Solar/Wind Harmer
0.87
971981AH1-535 GEN
Solar/Wind Harmer
3.673
972143AH1-644 GEN
Solar/Wind Harmer
5.262
270399AC1-101 GEN
Solar/Wind Harmer
1.445
965401AG1-405 GEN
Solar/Wind Harmer
2.362
339211AE2-254 GEN
Solar/Wind Harmer
0.002
972165AH1-665 GEN
Solar/Wind Harmer
3.096
25196008MFTGT1
Adder
0.655
276158O29GEN2
Solar/Wind Harmer
0
25196808ZIMRHP
Adder
35.531
939741AE1-205 GEN
Solar/Wind Harmer
4.568
274761LEE CO EC;2U
Adder
4.35
970569AG2-363 GEN
Solar/Wind Harmer
9.728
276861AD2-134 GEN
Solar/Wind Harmer
0.058
971997AH1-543 GEN
Solar/Wind Harmer
1.69
24387305FR-4G C
Solar/Wind Harmer
0.001
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
3.94
270032AE2-172
Solar/Wind Harmer
2.098
270005AE1-210 C O1
Solar/Wind Harmer
0.68
970825AG2-519 GEN
Solar/Wind Harmer
1.113
964861AG1-349 GEN
Solar/Wind Harmer
0
237061AD1-155 GEN
Solar/Wind Helper
0.025
316258AE1-075 C
Solar/Wind Helper
0.18
23583801GRNGAP
Solar/Wind Helper
2.125
238149AF1-291A_GEN
Solar/Wind Helper
0.061
3141196NOKESVL
Solar/Wind Helper
0.452
946321AF1-296 GEN
Solar/Wind Harmer
1.851
276656WTG2_EQ
Solar/Wind Harmer
0
941731AE2-173 GEN
Solar/Wind Harmer
2.719
274823ROCKFORD ;21
Adder
9.057
971171AH1-044 GEN
Solar/Wind Harmer
6.478
971675AH1-338 GEN
Solar/Wind Harmer
1.26
971411AH1-196 GEN
Solar/Wind Harmer
4.847
276868AE1-113 GEN
Solar/Wind Harmer
0.646
24386405FR-21G C
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
970833AG2-524 GEN
Solar/Wind Harmer
3.501
970833AG2-524 GEN
Solar/Wind Harmer
2.334
24725505WLD G2 C
Solar/Wind Harmer
0.001
960591AF2-350 GEN
Solar/Wind Harmer
3.163
971611AH1-305 GEN
Solar/Wind Harmer
1.877
971985AH1-537 GEN
Solar/Wind Harmer
0.937
3148013FISHERV
Solar/Wind Helper
0.165
3143873LANEXA
Solar/Wind Helper
0.067
971029AG2-637 GEN
Solar/Wind Harmer
4.547
971461AH1-227 GEN
Solar/Wind Harmer
2.688
24686205CER G4
Adder
4.732
3429391JKCT 9G
Adder
4.484
958171AF2-111 GEN
Solar/Wind Harmer
8.53
970519AG2-331 GEN
Solar/Wind Harmer
8.834
970699AG2-449 GEN
Solar/Wind Harmer
0.849
970193AG2-126 GEN
Solar/Wind Harmer
4.996
24728705AND G3
Adder
3.77
274853TWINGROVE;U1
Solar/Wind Harmer
0.001
959611AF2-252 GEN
Solar/Wind Harmer
1.093
274855GSG-6 ;RU
Solar/Wind Harmer
0.119
25196608WSDLE5
Adder
3.936
276694AA1-018 GEN2
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.188
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
10.359
270437AC2-090 C
Solar/Wind Harmer
0.001
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
958821AF2-173 GEN
Solar/Wind Harmer
4.392
253406AD2-031_GEN
Solar/Wind Harmer
0.232
3147666LOUISA
Solar/Wind Helper
0.583
958121AF2-106 GEN
Solar/Wind Helper
1.048
316254AC1-120 GEN1
Solar/Wind Helper
0.611
3143226MDLTHAN
Solar/Wind Helper
0.117
3142543TWELFTH
Solar/Wind Helper
0.011
24735105WLF2G1
50/50
5.209
24734805WLF1G4
50/50
5.198
270400AC1-102 GEN
Solar/Wind Harmer
1.445
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
970455AG2-298 GEN
Solar/Wind Harmer
2.533
3429211JKCT 2G
Adder
6.351
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
972163AH1-664 GEN
Solar/Wind Harmer
3.866
944221AF1-090 GEN
Solar/Wind Harmer
1.996
276655WTG1_EQ
Solar/Wind Harmer
0.001
926823AC1-168 GEN
Solar/Wind Harmer
0.551
963841AG1-237 GEN
Solar/Wind Harmer
1.404
24386205FR-12G C
Solar/Wind Harmer
0.001
276882AE2-255 GEN
Solar/Wind Harmer
0.376
25196508WSDLE4
Adder
3.896
274746AC1-111 G10
Adder
2.558
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24697905MDL-4G C
Solar/Wind Harmer
0
274731ELWOOD EC;2P
Adder
7.487
274733ELWOOD EC;3P
Adder
6.938
971485AH1-239 GEN
Solar/Wind Harmer
3.379
964781AG1-341 GEN
Solar/Wind Harmer
4.307
971081AG2-670 GEN
Solar/Wind Harmer
2.998
942891AE2-308 GEN
Solar/Wind Harmer
3.8
972043AH1-570 GEN
Solar/Wind Harmer
0.938
945391AF1-204 GEN
Solar/Wind Harmer
3.539
960611AF2-352 GEN
Solar/Wind Harmer
1.093
276782AC1-033 GEN
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.117
972267AH1-718 GEN
Adder
1.953
274764LEE CO EC;5U
Adder
4.36
971335AH1-147 GEN
Solar/Wind Harmer
6.465
970921AG2-575 GEN
Solar/Wind Harmer
3.218
970921AG2-575 GEN
Solar/Wind Harmer
1.073
274879MINONK ;1U
Solar/Wind Harmer
0.136
966841AG1-555 GEN
Solar/Wind Harmer
0.364
25194408D.CRK1
Adder
3.478
274683WAUKEGAN ;8U
Adder
9.693
274683WAUKEGAN ;8U
Adder
8.17
274693ROCKY RD ;1P
Adder
5.067
274862TOP CROP ;2U
Solar/Wind Harmer
0.433
958481AF2-142 GEN
Solar/Wind Harmer
4.797
24728905RICHG2
Adder
1.728
274887GEN-1.85
Solar/Wind Harmer
0.083
926881AC1-175 GEN
Solar/Wind Harmer
0
270599AE1-208 GEN
Solar/Wind Harmer
2.851
3132123MT JACKSON
Solar/Wind Helper
0.746
966001AG1-469 GEN
Solar/Wind Helper
0.172
971403AH1-188 GEN
Solar/Wind Harmer
6.41
970273AG2-179 GEN
Solar/Wind Harmer
1.456
971565AH1-281 GEN
Solar/Wind Harmer
0.752
3429421JKCT 10G
Adder
4.484
958131AF2-107 GEN
Solar/Wind Harmer
2.005
970091AG2-072 GEN
Adder
38.082
274854TWINGROVE;U2
Solar/Wind Harmer
0.001
276726Z2-087_GEN
Solar/Wind Harmer
0.001
963741AG1-226 GEN
Solar/Wind Harmer
7.717
971475AH1-234 GEN
Solar/Wind Harmer
1.579
970819AG2-516 GEN
Solar/Wind Harmer
3.899
274822ROCKFORD ;11
Adder
9.123
959081AF2-199 GEN
Solar/Wind Harmer
3.239
971067AG2-660 GEN
Solar/Wind Harmer
1.08
274872LEEDK;1U
Solar/Wind Harmer
0.002
970773AG2-487 GEN
Solar/Wind Harmer
0.568
276691AA1-018 GEN1
Solar/Wind Harmer
0.387
24791305MDL-5G
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.07
3132273ORANGE
Solar/Wind Helper
0.03
316170AC1-121 GEN2
Solar/Wind Helper
0.204
316313AB2-026
Solar/Wind Helper
0.2
3146776BUCKING
Solar/Wind Helper
0.045
316484AD2-074 GEN
Solar/Wind Helper
0.215
274763LEE CO EC;4U
Adder
4.309
252509AD1-136 GEN
Solar/Wind Harmer
0.016
971333AH1-146 GEN
Solar/Wind Harmer
6.465
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
942991AE2-321 GEN
Solar/Wind Harmer
3.603
958491AF2-143 GEN
Solar/Wind Harmer
4.817
25183208HLCRTG
Solar/Wind Harmer
0.005
25194508D.CRK3
Adder
0.65
274695ROCKY RD ;2P
Adder
5.117
971573AH1-285 GEN
Solar/Wind Harmer
0.596
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
24728805RICHG1
Adder
1.728
945421AF1-207 GEN
Solar/Wind Harmer
0
276843GEN-1.7
Solar/Wind Harmer
0.102
958011AF2-095 GEN
Solar/Wind Harmer
4.555
24379505HDWTR1G C
Solar/Wind Harmer
0.001
270383AD1-128 GEN
Solar/Wind Harmer
0.002
960441AF2-335 GEN
Solar/Wind Harmer
3.136
270031AE2-169
Solar/Wind Harmer
1.71
3146776BUCKING
Solar/Wind Helper
0.504
3146776BUCKING
Solar/Wind Helper
0.041
966871AG1-558 GEN
Solar/Wind Helper
0.167
24699105WLD G1 C
Solar/Wind Harmer
0
970115AG2-085 GEN
Solar/Wind Harmer
1.255
971609AH1-304 GEN
Solar/Wind Harmer
0.508
316164AC1-076 GEN
Solar/Wind Helper
0.618
23546401DTGZ2-030
Solar/Wind Helper
0.04
238152AF2-075_GEN
Solar/Wind Helper
0.304
316233AE1-074 FULL
Solar/Wind Helper
0.179
316223AC1-118
Solar/Wind Helper
0.173
3141813NORNECK
Solar/Wind Helper
0.113
943031AE2-326 GEN
Solar/Wind Harmer
3.913
960911AF2-382 GEN
Solar/Wind Harmer
4.08
972103AH1-617 GEN
Solar/Wind Harmer
9.714
971155AH1-034 GEN
Solar/Wind Harmer
4.743
960741AF2-365 GEN
Solar/Wind Harmer
1.981
270030AE2-140 GEN
Solar/Wind Harmer
7.67
276668AB2-070 GEN1
Solar/Wind Harmer
0.121
24728505AND G1
Adder
1.803
274767LEE CO EC;8U
Adder
4.299
24721905FLATG4
Adder
9.459
959091AF2-200 GEN
Solar/Wind Harmer
6.478
25194608D.CRK4
Adder
0.756
274682WAUKEGAN ;7U
Adder
8.262
943121AE2-341 GEN
Solar/Wind Harmer
5.354
943591AF1-030 GEN
Solar/Wind Harmer
3.56
24755605MDL-5G
Solar/Wind Harmer
0
276806AD2-047 C O1
Solar/Wind Harmer
1.793
253316AC1-085 GEN3
Solar/Wind Harmer
0.002
253433AC1-085 GEN1
Solar/Wind Harmer
0.001
946181AF1-283 GEN
Solar/Wind Harmer
4.111
247642Z2-115 C
Solar/Wind Harmer
0.001
970289AG2-191 GEN
Solar/Wind Harmer
0.347
970291AG2-192 GEN
Solar/Wind Harmer
0.315
946031AF1-268 GEN
Solar/Wind Harmer
2.971
270535AF1-215 GEN1
Solar/Wind Harmer
0.004
316192AB2-158 GEN
Solar/Wind Helper
0.985
316336AC2-165 C
Solar/Wind Helper
0.729
3142416OLDCHRC
Solar/Wind Helper
0.318
3142416OLDCHRC
Solar/Wind Helper
0.122
316097T157 G90
Solar/Wind Helper
0.556
3142433PROV 92
Solar/Wind Helper
0.448
971225AH1-072 GEN
Solar/Wind Harmer
1.048
971227AH1-073 GEN
Solar/Wind Harmer
1.048
24723005RIVRG1
Adder
11.619
24723105RIVRG2
Adder
11.619
24685805CER G1
Adder
4.726
24685905CER G2
Adder
4.726
971125AH1-004 GEN
Solar/Wind Harmer
1.465
270444AC2-157 GEN1
Solar/Wind Harmer
0.002
971587AH1-292 GEN
Solar/Wind Harmer
2.506
276916AD2-100_GEN
Solar/Wind Harmer
7.098
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
276741O09 GEN1
Solar/Wind Harmer
0.117
274849CRESCENT ;1U
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
6.478
971343AH1-151 GEN
Solar/Wind Harmer
6.478
252519AF1-045_GEN
Solar/Wind Harmer
2.794
252516AE2-318_GEN
Solar/Wind Harmer
2.478
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
253317AC1-085 GEN4
Solar/Wind Harmer
0.002
971613AH1-306 GEN
Solar/Wind Harmer
1.51
315651AD1-115 GEN
Solar/Wind Helper
0.441
316447AC1-158 HLD
Solar/Wind Helper
1.451
3142946ENON
Solar/Wind Helper
0.011
316487AF1-042 GEN
Solar/Wind Helper
0.113
276901AD2-066 C O1
Solar/Wind Harmer
0.003
25194608D.CRK4
Adder
0.756
274828WAUKEGAN ;BP
Adder
5.081
274682WAUKEGAN ;7U
Adder
8.262
274745AC1-111 GEN9
Adder
2.558
274871GR RIDGE ;2U
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
0.33
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
3.162
970613AG2-401 GEN
Solar/Wind Harmer
2.313
970291AG2-192 GEN
Solar/Wind Harmer
0.41
276164X3-005 C
Solar/Wind Harmer
0
965031AG1-367 GEN
Solar/Wind Harmer
3.137
270055AF2-134 C O1
Solar/Wind Harmer
0.002
316499AE2-029_GEN
Solar/Wind Helper
0.937
966881AG1-559 GEN
Solar/Wind Helper
0.168
316473AC1-191 GEN
Solar/Wind Helper
0.759
316095T157 G97
Solar/Wind Helper
0.556
3142946ENON
Solar/Wind Helper
0.038
970281AG2-184 GEN
Solar/Wind Harmer
10.199
972203AH1-686 GEN
Adder
1.34
276849AB2-070 GEN2
Solar/Wind Harmer
0.121
276848AB2-070 GEN3
Solar/Wind Harmer
0.121
276785W4-005 GEN1
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
961011AF2-392 GEN
Solar/Wind Harmer
1.918
959341AF2-225 GEN
Solar/Wind Harmer
3.426
970169AG2-114 GEN
Solar/Wind Harmer
3.233
252524AE2-267 GEN
Solar/Wind Harmer
0.001
274744AC1-111 GEN8
Adder
2.558
970289AG2-191 GEN
Solar/Wind Harmer
0.599
958391AF2-133 GEN
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0.004
3148463FAIRFLD
Solar/Wind Helper
0.398
3138266HYDRAULIC
Solar/Wind Helper
0.011
3138266HYDRAULIC
Solar/Wind Helper
0.007
316059AD1-063 C
Solar/Wind Helper
0.112
970563AG2-360 GEN
50/50
26.913
24689505VACITY
50/50
3.172
962751AG1-124 GEN
Solar/Wind Harmer
6.207
972273AH1-721 GEN
Adder
50.38
966571AG1-526 GEN
Solar/Wind Harmer
8.7
970093AG2-073 GEN
Solar/Wind Harmer
3.862
972167AH1-666 GEN
Solar/Wind Harmer
2.764
970243AG2-164 GEN
Solar/Wind Harmer
1.988
942481AE2-261 GEN
Solar/Wind Harmer
10.086
276621W2-048 GEN
Solar/Wind Harmer
0.169
276838X2-022 GEN2
Solar/Wind Harmer
0.188
971993AH1-541 GEN
Solar/Wind Harmer
1.536
25196008MFTGT1
Adder
0.634
276157O29GEN1
Solar/Wind Harmer
0.529
942111AE2-223 GEN
Solar/Wind Harmer
1.06
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
970571AG2-364 GEN
Solar/Wind Harmer
6.485
274850MENDOTA H;RU
Solar/Wind Harmer
0.038
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.058
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.345
276889AE2-281 GEN
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0.001
252510AF1-249 C
Solar/Wind Harmer
0.025
276893AG1-478 C
Solar/Wind Harmer
0.126
274729ELWOOD EC;1P
Adder
7.487
276897AD1-100 C
Solar/Wind Harmer
0.004
970941AG2-585 GEN
Solar/Wind Harmer
3.954
971191AH1-055 GEN
Solar/Wind Harmer
7.979
3147983MERCK5
Solar/Wind Helper
0.107
316322AB2-045
Solar/Wind Helper
0.14
3143526WINTERP
Solar/Wind Helper
0.609
964211AG1-282 GEN
Solar/Wind Helper
0.152
960161AF2-307 GEN
Solar/Wind Harmer
2.512
970107AG2-081 GEN
Solar/Wind Harmer
1.099
970235AG2-159 GEN
Solar/Wind Harmer
2.143
970235AG2-159 GEN
Solar/Wind Harmer
1.23
970239AG2-162 GEN
Solar/Wind Harmer
0.849
270186AC1-089 GEN
Solar/Wind Harmer
0.002
276645AC1-214 GEN1
Solar/Wind Harmer
0.128
276603SUBLETTE C
Solar/Wind Harmer
0
274762LEE CO EC;3U
Adder
4.35
970241AG2-163 GEN
Solar/Wind Harmer
1.902
938861AE1-114 GEN
Solar/Wind Harmer
1.846
274856ECOGROVE ;U1
Solar/Wind Harmer
0.077
276611AD2-172 GEN
Solar/Wind Harmer
0.001
962581AG1-107 GEN
Solar/Wind Harmer
0.001
962691AG1-118 GEN
Solar/Wind Harmer
9.647
274696ROCKY RD ;4P
Adder
5.238
274697ROCKY RD ;3P
Adder
1.39
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
274888KELLY CRK;1U
Solar/Wind Harmer
0.186
270209AC1-174_GEN
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
3.475
253394AE2-221_GEN
Solar/Wind Harmer
0.004
253398AE2-221_GEN2
Solar/Wind Harmer
0.004
315821AE2-092 GEN
Solar/Wind Helper
1.824
316468AD1-105 GEN
Solar/Wind Helper
0.61
316075AC2-137 C
Solar/Wind Helper
0.179
3143526WINTERP
Solar/Wind Helper
0.609
316077AC2-138 C
Solar/Wind Helper
0.106
270053AF1-130 C
Solar/Wind Harmer
1.017
24728305BUCHG2
Adder
3.631
962241AG1-070 GEN
Solar/Wind Harmer
2.203
24686505CER G6
Adder
4.751
3429241JKCT 3G
Adder
6.434
339216AC1-074 GEN
Solar/Wind Harmer
0.098
965911AG1-460 GEN
Solar/Wind Harmer
0.675
276615X2-022 GEN
Solar/Wind Harmer
0.035
963831AG1-236 GEN
Solar/Wind Harmer
1.299
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274766LEE CO EC;7U
Adder
4.299
972235AH1-702 GEN1
Adder
1.172
252507AC2-088 GEN
Solar/Wind Harmer
0.147
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
962781AG1-127 GEN
Solar/Wind Harmer
3.063
24385905FR-11G C
Solar/Wind Harmer
0.001
939401AE1-172 GEN
Solar/Wind Harmer
2.398
276903AD2-071 C
Solar/Wind Harmer
3.539
958381AF2-132 GEN
Solar/Wind Harmer
0
315616AA1-038_C
Solar/Wind Helper
1.807
3148013FISHERV
Solar/Wind Helper
0.286
3147666LOUISA
Solar/Wind Helper
0.335
316405AF2-144 C
Solar/Wind Helper
0.15
238147AE2-230_GEN1
Solar/Wind Helper
0.213
316044AC1-158 PL1
Solar/Wind Helper
0.659
316450AC1-158 RIC
Solar/Wind Helper
0.176
3141906WESTMOR
Solar/Wind Helper
0.046
316404AE1-155 C
Solar/Wind Helper
0.945
3141766HARMONY
Solar/Wind Helper
0.022
971313AH1-133 GEN
Solar/Wind Harmer
5.384
965411AG1-406 GEN
Solar/Wind Harmer
1.519
276174W4-005 GEN2
Solar/Wind Harmer
0
25196108MFTGT2
Adder
0.722
25196108MFTGT2
Adder
0.67
957751AF2-069 GEN
Solar/Wind Harmer
0.108
971681AH1-341 GEN
Solar/Wind Harmer
5.244
270367AC2-061_GEN
Solar/Wind Harmer
0.003
276612AE2-035 GEN
Solar/Wind Harmer
0.001
971177AH1-047 GEN
Solar/Wind Harmer
1.99
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0
24387005FR-3G C
Solar/Wind Harmer
0.001
25196408WSDLE3
Adder
4.052
25196308WSDLE2
Adder
4.017
25196208WSDLE1
Adder
4.006
25196708WSDLE6
Adder
3.996
24691005MDL-2G C
Solar/Wind Harmer
0.001
270240V3-007_GEN2
Solar/Wind Harmer
0.001
270594AE1-207 GEN
Solar/Wind Harmer
3.524
971673AH1-337 GEN
Solar/Wind Harmer
2.018
3148133STUARTS
Solar/Wind Helper
0.172
316312AB1-027
Solar/Wind Helper
0.233
3141426STAFORD
Solar/Wind Helper
0.025
970273AG2-179 GEN
Solar/Wind Harmer
2.497
339250AF1-203 GEN
Solar/Wind Harmer
0.001
962251AG1-071 GEN
Solar/Wind Harmer
2.526
24686405CER G5
Adder
4.713
276686W4-005 GEN3
Solar/Wind Harmer
0
965931AG1-462 GEN
Solar/Wind Harmer
8.444
965091AG1-374 GEN
Solar/Wind Harmer
9.836
274878BISHOP HL;2U
Solar/Wind Harmer
0.11
274760LEE CO EC;1U
Adder
4.35
972236AH1-702 GEN2
Adder
1.02
274872LEEDK;1U
Solar/Wind Harmer
0.118
270356AE2-297 GEN
Solar/Wind Harmer
0.004
270222AC2-111 GEN
Solar/Wind Harmer
1.601
270004AE1-209 GEN
Solar/Wind Harmer
0.68
964401AG1-302 GEN
Solar/Wind Harmer
0
3146776BUCKING
Solar/Wind Helper
0.05
238148AE2-230_GEN2
Solar/Wind Helper
0.214
316006AB2-029 C
Solar/Wind Helper
0.058
316045AC1-158 PL2
Solar/Wind Helper
2.111
316337AD2-073 GEN
Solar/Wind Helper
0.172
3141726DUNNSVL
Solar/Wind Helper
0.452
957141AF2-008_MTX
Adder
28.482
944201AF1-088_MTX
Adder
56.965
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.657
WECLTFEXP_WEC->PJM
CLTF
1.782
LAGNLTFEXP_LAGN->PJM
CLTF
11.707
CBM South 2LTFEXP_CBM-S2->PJM
CBM
15.107
CPLELTFEXP_CPLE->PJM
CLTF
3.112
SIGELTFEXP_SIGE->PJM
CLTF
0.271
CBM West 1LTFEXP_CBM-W1->PJM
CBM
64.396
NYPJM->LTFIMP_NY
CLTF
1.478
TVALTFEXP_TVA->PJM
CLTF
6.219
AG2-052LTFEXP_AG2-052->PJM
LTF
0.105
CBM West 2LTFEXP_CBM-W2->PJM
CBM
73.214
LGEELTFEXP_LGEE->PJM
CLTF
3.565
MECLTFEXP_MEC->PJM
CLTF
8.32
AH1-155LTFEXP_AH1-155->PJM
LTF
0.158

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AP_P1-3_MP-765-501T_SRT-A


Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-501T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:121.06 %
Rating:3393.4 MVA
Rating Type:B
MVA to Mitigate:4107.97
MW Contribution:13.15
Bus #Bus NameTypeMW Contribution
24290705CLAY-2
50/50
0.255
24290705CLAY-2
50/50
0.255
24684505SMG3
50/50
1.376
971277AH1-098 GEN
Solar/Wind Harmer
5.177
24728205BUCHG1
Adder
6.75
944971AF1-162 GEN
Solar/Wind Harmer
9.068
942751AE2-291 GEN
Solar/Wind Harmer
7.887
966021AG1-471 GEN
Solar/Wind Harmer
4.013
339255AE2-071 GEN
Solar/Wind Harmer
-0.119
970653AG2-424 GEN
Solar/Wind Harmer
3.405
970653AG2-424 GEN
Solar/Wind Harmer
1.764
964571AG1-320 GEN
Solar/Wind Harmer
6.361
972045AH1-571 GEN
Solar/Wind Harmer
1.439
339221AD2-048_GEN
Solar/Wind Harmer
0.004
252509AD1-136 GEN
Solar/Wind Harmer
0.033
25183208HLCRTG
Solar/Wind Harmer
0.01
25194508D.CRK3
Adder
1.297
971073AG2-665 GEN
Solar/Wind Harmer
5.761
276911AD2-131_GEN
Solar/Wind Harmer
0.88
24728805RICHG1
Adder
3.384
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
276646AC1-214 GEN2
Solar/Wind Harmer
0.243
274765LEE CO EC;6U
Adder
8.241
274763LEE CO EC;4U
Adder
8.144
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270383AD1-128 GEN
Solar/Wind Harmer
0.004
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
971333AH1-146 GEN
Solar/Wind Harmer
12.256
945421AF1-207 GEN
Solar/Wind Harmer
0.001
942991AE2-321 GEN
Solar/Wind Harmer
6.834
958491AF2-143 GEN
Solar/Wind Harmer
9.158
960441AF2-335 GEN
Solar/Wind Harmer
6.106
274695ROCKY RD ;2P
Adder
9.727
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
971573AH1-285 GEN
Solar/Wind Harmer
1.134
966871AG1-558 GEN
Solar/Wind Helper
0.306
970479AG2-310 GEN
50/50
20.255
270205AE1-176
50/50
0.006
966251AG1-494 GEN
50/50
4.388
24728405LEESVG
50/50
0.297
971367AH1-164 GEN
Solar/Wind Harmer
4.886
941821AE2-187 GEN
Solar/Wind Harmer
7.452
270197AD1-017 GEN1
Solar/Wind Harmer
1.429
270336AE1-100 GEN
Solar/Wind Harmer
0.006
943811AF1-049 GEN
Solar/Wind Harmer
-0.002
24735205WLF2G2
Adder
8.023
24723205RIVRG3
Adder
22.954
24686105CER G3
Adder
9.887
24721705FLATG2
Adder
21.686
970947AG2-589 GEN
Solar/Wind Harmer
0.249
971821AH1-427 GEN
Solar/Wind Harmer
7.218
964901AG1-354 GEN
Solar/Wind Harmer
10.814
945681AF1-233 GEN
Solar/Wind Harmer
12.782
270445AC2-157 GEN2
Solar/Wind Harmer
0.003
25194608D.CRK4
Adder
1.508
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.331
24728605AND G2
Adder
3.48
274877BISHOP HL;1U
Solar/Wind Harmer
0.208
970613AG2-401 GEN
Solar/Wind Harmer
4.519
957471AF2-041 GEN
Solar/Wind Harmer
18.409
970291AG2-192 GEN
Solar/Wind Harmer
0.796
965031AG1-367 GEN
Solar/Wind Harmer
6.111
276901AD2-066 C O1
Solar/Wind Harmer
0.006
274828WAUKEGAN ;BP
Adder
9.655
274682WAUKEGAN ;7U
Adder
15.703
274745AC1-111 GEN9
Adder
4.87
316499AE2-029_GEN
Solar/Wind Helper
1.725
316095T157 G97
Solar/Wind Helper
1.125
966881AG1-559 GEN
Solar/Wind Helper
0.313
316473AC1-191 GEN
Solar/Wind Helper
1.387
3147312GRETNA
Solar/Wind Harmer
0.047
971687AH1-348 GEN
Solar/Wind Harmer
0.948
971315AH1-136 GEN
Solar/Wind Harmer
1.695
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
970333AG2-219 GEN
Solar/Wind Harmer
4.755
25196808ZIMRHP
Adder
70.616
25196008MFTGT1
Adder
1.293
274880W4-005 GEN4
Solar/Wind Harmer
0.001
972175AH1-670 GEN
Solar/Wind Harmer
5.171
939741AE1-205 GEN
Solar/Wind Harmer
8.673
24387305FR-4G C
Solar/Wind Harmer
0.002
276158O29GEN2
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
8.222
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970569AG2-363 GEN
Solar/Wind Harmer
18.444
276861AD2-134 GEN
Solar/Wind Harmer
0.11
971997AH1-543 GEN
Solar/Wind Harmer
3.211
270032AE2-172
Solar/Wind Harmer
4.079
270005AE1-210 C O1
Solar/Wind Harmer
1.324
970825AG2-519 GEN
Solar/Wind Harmer
2.167
237061AD1-155 GEN
Solar/Wind Helper
0.05
23583801GRNGAP
Solar/Wind Helper
4.287
238149AF1-291A_GEN
Solar/Wind Helper
0.12
316258AE1-075 C
Solar/Wind Helper
0.319
24734805WLF1G4
Adder
8.194
24735105WLF2G1
Adder
8.023
270400AC1-102 GEN
Solar/Wind Harmer
2.892
941621AE2-160 GEN
Adder
4.285
957241AF2-018 GEN
Solar/Wind Harmer
-0.002
24477305BRIDGE
Adder
0.419
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
3429211JKCT 2G
Adder
11.873
970455AG2-298 GEN
Solar/Wind Harmer
4.677
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
972163AH1-664 GEN
Solar/Wind Harmer
7.568
944221AF1-090 GEN
Solar/Wind Harmer
3.754
25196508WSDLE4
Adder
7.769
963841AG1-237 GEN
Solar/Wind Harmer
2.698
270340AC2-060 GEN
Solar/Wind Harmer
0.007
276655WTG1_EQ
Solar/Wind Harmer
0.002
24386205FR-12G C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
926823AC1-168 GEN
Solar/Wind Harmer
1.045
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24697905MDL-4G C
Solar/Wind Harmer
0.001
276882AE2-255 GEN
Solar/Wind Harmer
0.715
970115AG2-085 GEN
Solar/Wind Harmer
2.442
274746AC1-111 G10
Adder
4.87
23546401DTGZ2-030
Solar/Wind Helper
0.078
316164AC1-076 GEN
Solar/Wind Helper
1.172
238152AF2-075_GEN
Solar/Wind Helper
0.602
970481AG2-311 GEN
50/50
11.937
24728405LEESVG
50/50
0.295
943031AE2-326 GEN
Solar/Wind Harmer
6.784
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
3147123OTTER R
Solar/Wind Harmer
0.13
270030AE2-140 GEN
Solar/Wind Harmer
21.578
960911AF2-382 GEN
Solar/Wind Harmer
7.638
972103AH1-617 GEN
Solar/Wind Harmer
18.024
24721905FLATG4
Adder
21.686
971155AH1-034 GEN
Solar/Wind Harmer
8.427
960741AF2-365 GEN
Solar/Wind Harmer
3.563
25194608D.CRK4
Adder
1.508
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
8.231
24728505AND G1
Adder
3.48
276668AB2-070 GEN1
Solar/Wind Harmer
0.229
274767LEE CO EC;8U
Adder
8.125
24755605MDL-5G
Solar/Wind Harmer
0.001
959091AF2-200 GEN
Solar/Wind Harmer
12.273
247642Z2-115 C
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
0.673
970291AG2-192 GEN
Solar/Wind Harmer
0.612
274682WAUKEGAN ;7U
Adder
15.703
946031AF1-268 GEN
Solar/Wind Harmer
5.79
943121AE2-341 GEN
Solar/Wind Harmer
10.192
943591AF1-030 GEN
Solar/Wind Harmer
6.778
316192AB2-158 GEN
Solar/Wind Helper
1.838
316097T157 G90
Solar/Wind Helper
1.125
316336AC2-165 C
Solar/Wind Helper
1.285
966391AG1-508 GEN
Solar/Wind Harmer
1.993
270069AE2-166 C O1
Solar/Wind Harmer
0.008
24734705WLF1G3
Adder
8.194
24734905WLF1G5
Adder
8.194
270399AC1-101 GEN
Solar/Wind Harmer
2.892
972143AH1-644 GEN
Solar/Wind Harmer
9.763
971981AH1-535 GEN
Solar/Wind Harmer
5.843
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
965401AG1-405 GEN
Solar/Wind Harmer
4.227
339211AE2-254 GEN
Solar/Wind Harmer
0.003
972165AH1-665 GEN
Solar/Wind Harmer
6.061
971985AH1-537 GEN
Solar/Wind Harmer
2.011
946321AF1-296 GEN
Solar/Wind Harmer
3.483
276656WTG2_EQ
Solar/Wind Harmer
0
941731AE2-173 GEN
Solar/Wind Harmer
5.162
24386405FR-21G C
Solar/Wind Harmer
0.001
24725505WLD G2 C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274823ROCKFORD ;21
Adder
17.15
971171AH1-044 GEN
Solar/Wind Harmer
12.273
971675AH1-338 GEN
Solar/Wind Harmer
2.39
971411AH1-196 GEN
Solar/Wind Harmer
9.19
276868AE1-113 GEN
Solar/Wind Harmer
1.227
3148013FISHERV
Solar/Wind Helper
0.3
971029AG2-637 GEN
Solar/Wind Harmer
2.803
970563AG2-360 GEN
50/50
45.829
962751AG1-124 GEN
Solar/Wind Harmer
12.893
3147312GRETNA
Solar/Wind Harmer
0.186
3146802CHATHAM
Solar/Wind Harmer
0.175
270016AE1-250 BESS
Solar/Wind Harmer
0.006
972273AH1-721 GEN
Adder
89.316
966571AG1-526 GEN
Solar/Wind Harmer
15.967
970093AG2-073 GEN
Solar/Wind Harmer
7.166
971191AH1-055 GEN
Solar/Wind Harmer
18.055
972167AH1-666 GEN
Solar/Wind Harmer
5.419
970243AG2-164 GEN
Solar/Wind Harmer
3.891
25196008MFTGT1
Adder
1.252
252510AF1-249 C
Solar/Wind Harmer
0.05
942481AE2-261 GEN
Solar/Wind Harmer
18.997
276621W2-048 GEN
Solar/Wind Harmer
0.318
276838X2-022 GEN2
Solar/Wind Harmer
0.355
971993AH1-541 GEN
Solar/Wind Harmer
2.905
942111AE2-223 GEN
Solar/Wind Harmer
2.013
276157O29GEN1
Solar/Wind Harmer
0.999
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
970571AG2-364 GEN
Solar/Wind Harmer
12.296
276889AE2-281 GEN
Solar/Wind Harmer
0.001
274850MENDOTA H;RU
Solar/Wind Harmer
0.072
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.11
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.654
276805AD2-038 GEN
Solar/Wind Harmer
0.002
274729ELWOOD EC;1P
Adder
13.481
3147983MERCK5
Solar/Wind Helper
0.198
970823AG2-518 GEN
50/50
8.384
247619Y1-049
50/50
0.913
24416005BYLLESBY
50/50
0.031
958121AF2-106 GEN
Solar/Wind Harmer
0.001
971331AH1-145 GEN
Solar/Wind Harmer
18.361
270346AE1-212 GEN
Solar/Wind Harmer
9.542
971461AH1-227 GEN
Solar/Wind Harmer
4.886
970223AG2-152 GEN
Solar/Wind Harmer
12.358
24686205CER G4
Adder
9.835
3429391JKCT 9G
Adder
8.402
958171AF2-111 GEN
Solar/Wind Harmer
16.681
970519AG2-331 GEN
Solar/Wind Harmer
17.292
970699AG2-449 GEN
Solar/Wind Harmer
1.663
25196608WSDLE5
Adder
7.849
970193AG2-126 GEN
Solar/Wind Harmer
9.55
24728705AND G3
Adder
7.277
253406AD2-031_GEN
Solar/Wind Harmer
0.467
270291AC1-194 GEN
Solar/Wind Harmer
4.924
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
959611AF2-252 GEN
Solar/Wind Harmer
2.073
270437AC2-090 C
Solar/Wind Harmer
0.003
253415AE1-040 GEN
Solar/Wind Harmer
0.002
970781AG2-491 GEN
Solar/Wind Harmer
6.144
274855GSG-6 ;RU
Solar/Wind Harmer
0.225
958821AF2-173 GEN
Solar/Wind Harmer
8.556
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
3147666LOUISA
Solar/Wind Helper
1.088
316254AC1-120 GEN1
Solar/Wind Helper
1.159
24290605CLAY-1
50/50
0.255
24290605CLAY-1
50/50
0.255
24684405SMG2
50/50
2.224
316217AC1-145 GEN
Solar/Wind Harmer
0.003
316197AC1-042 GEN
Solar/Wind Harmer
0.002
942671AE2-283 GEN
Solar/Wind Harmer
5.796
971485AH1-239 GEN
Solar/Wind Harmer
5.928
964781AG1-341 GEN
Solar/Wind Harmer
7.653
971081AG2-670 GEN
Solar/Wind Harmer
5.396
942891AE2-308 GEN
Solar/Wind Harmer
7.099
972043AH1-570 GEN
Solar/Wind Harmer
1.796
25194408D.CRK1
Adder
6.938
945391AF1-204 GEN
Solar/Wind Harmer
6.765
24728905RICHG2
Adder
3.384
960251AF2-316 GEN
Solar/Wind Harmer
8.583
960611AF2-352 GEN
Solar/Wind Harmer
2.073
966841AG1-555 GEN
Solar/Wind Harmer
0.701
276782AC1-033 GEN
Solar/Wind Harmer
0.001
276708O09 GEN2
Solar/Wind Harmer
0.22
972267AH1-718 GEN
Adder
3.688
274764LEE CO EC;5U
Adder
8.241
926881AC1-175 GEN
Solar/Wind Harmer
0
971335AH1-147 GEN
Solar/Wind Harmer
12.256
274879MINONK ;1U
Solar/Wind Harmer
0.258
970921AG2-575 GEN
Solar/Wind Harmer
6.111
970921AG2-575 GEN
Solar/Wind Harmer
2.037
274683WAUKEGAN ;8U
Adder
18.419
274683WAUKEGAN ;8U
Adder
15.526
274693ROCKY RD ;1P
Adder
9.632
274862TOP CROP ;2U
Solar/Wind Harmer
0.824
958481AF2-142 GEN
Solar/Wind Harmer
9.131
3132123MT JACKSON
Solar/Wind Helper
1.389
966001AG1-469 GEN
Solar/Wind Helper
0.32
24415905BUCK
50/50
0.034
971329AH1-144 GEN
Solar/Wind Harmer
11.568
958131AF2-107 GEN
Solar/Wind Harmer
5.339
971403AH1-188 GEN
Solar/Wind Harmer
13.153
970273AG2-179 GEN
Solar/Wind Harmer
2.581
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
3429421JKCT 10G
Adder
8.402
971565AH1-281 GEN
Solar/Wind Harmer
1.396
927014AC1-188 GEN
Solar/Wind Harmer
0.004
970091AG2-072 GEN
Adder
74.012
970773AG2-487 GEN
Solar/Wind Harmer
1.107
963741AG1-226 GEN
Solar/Wind Harmer
14.811
274854TWINGROVE;U2
Solar/Wind Harmer
0.003
276726Z2-087_GEN
Solar/Wind Harmer
0.002
971475AH1-234 GEN
Solar/Wind Harmer
2.986
970819AG2-516 GEN
Solar/Wind Harmer
7.379
24791305MDL-5G
Solar/Wind Harmer
0.001
274822ROCKFORD ;11
Adder
17.275
959081AF2-199 GEN
Solar/Wind Harmer
6.136
971067AG2-660 GEN
Solar/Wind Harmer
2.045
270263AC1-001 GEN
Solar/Wind Harmer
0.614
274872LEEDK;1U
Solar/Wind Harmer
0.004
276691AA1-018 GEN1
Solar/Wind Harmer
0.737
3132273ORANGE
Solar/Wind Helper
0.056
316170AC1-121 GEN2
Solar/Wind Helper
0.386
316313AB2-026
Solar/Wind Helper
0.354
24288905REUSENS
50/50
0.057
24684605SMG4
50/50
2.239
24728305BUCHG2
Adder
6.75
270018AE2-047 C O1
Solar/Wind Harmer
0.004
24686505CER G6
Adder
9.874
962241AG1-070 GEN
Solar/Wind Harmer
3.92
3429241JKCT 3G
Adder
12.029
339216AC1-074 GEN
Solar/Wind Harmer
0.187
252507AC2-088 GEN
Solar/Wind Harmer
0.295
965911AG1-460 GEN
Solar/Wind Harmer
1.271
276615X2-022 GEN
Solar/Wind Harmer
0.066
963831AG1-236 GEN
Solar/Wind Harmer
2.455
24385905FR-11G C
Solar/Wind Harmer
0.001
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274766LEE CO EC;7U
Adder
8.125
276903AD2-071 C
Solar/Wind Harmer
6.874
972235AH1-702 GEN1
Adder
2.22
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
962781AG1-127 GEN
Solar/Wind Harmer
5.815
939401AE1-172 GEN
Solar/Wind Harmer
4.568
315616AA1-038_C
Solar/Wind Helper
3.293
3148013FISHERV
Solar/Wind Helper
0.523
3147666LOUISA
Solar/Wind Helper
0.625
238147AE2-230_GEN1
Solar/Wind Helper
0.421
316405AF2-144 C
Solar/Wind Helper
0.265
316044AC1-158 PL1
Solar/Wind Helper
1.257
316450AC1-158 RIC
Solar/Wind Helper
0.335
270583AD2-179 GEN
Solar/Wind Harmer
14.457
971225AH1-072 GEN
Solar/Wind Harmer
1.905
971227AH1-073 GEN
Solar/Wind Harmer
1.905
24723005RIVRG1
Adder
22.954
24723105RIVRG2
Adder
22.954
24685805CER G1
Adder
9.822
24685905CER G2
Adder
9.822
971125AH1-004 GEN
Solar/Wind Harmer
2.777
270444AC2-157 GEN1
Solar/Wind Harmer
0.003
971587AH1-292 GEN
Solar/Wind Harmer
4.8
252519AF1-045_GEN
Solar/Wind Harmer
5.589
252516AE2-318_GEN
Solar/Wind Harmer
4.958
276916AD2-100_GEN
Solar/Wind Harmer
13.364
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
276741O09 GEN1
Solar/Wind Harmer
0.22
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
971341AH1-150 GEN
Solar/Wind Harmer
12.273
971343AH1-151 GEN
Solar/Wind Harmer
12.273
971613AH1-306 GEN
Solar/Wind Harmer
2.937
315651AD1-115 GEN
Solar/Wind Helper
0.837
316447AC1-158 HLD
Solar/Wind Helper
2.766
970281AG2-184 GEN
Solar/Wind Harmer
18.925
972203AH1-686 GEN
Adder
2.704
970165AG2-112 GEN
Solar/Wind Harmer
0.998
970163AG2-111 GEN
Solar/Wind Harmer
0.952
252524AE2-267 GEN
Solar/Wind Harmer
0.002
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.229
276848AB2-070 GEN3
Solar/Wind Harmer
0.228
959341AF2-225 GEN
Solar/Wind Harmer
6.505
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
961011AF2-392 GEN
Solar/Wind Harmer
3.623
970169AG2-114 GEN
Solar/Wind Harmer
6.149
970289AG2-191 GEN
Solar/Wind Harmer
1.163
274744AC1-111 GEN8
Adder
4.87
25306009OHH W.
Adder
2.505
3148463FAIRFLD
Solar/Wind Helper
0.726
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
24684305SMG1
50/50
0.806
270013AE1-250 PV
Solar/Wind Harmer
0.006
960161AF2-307 GEN
Solar/Wind Harmer
4.775
970107AG2-081 GEN
Solar/Wind Harmer
2.083
970235AG2-159 GEN
Solar/Wind Harmer
4.126
970235AG2-159 GEN
Solar/Wind Harmer
2.367
270186AC1-089 GEN
Solar/Wind Harmer
0.004
970239AG2-162 GEN
Solar/Wind Harmer
1.663
962581AG1-107 GEN
Solar/Wind Harmer
0.001
970241AG2-163 GEN
Solar/Wind Harmer
3.651
253394AE2-221_GEN
Solar/Wind Harmer
0.008
253398AE2-221_GEN2
Solar/Wind Harmer
0.008
960201AF2-311 GEN
Solar/Wind Harmer
5.708
276645AC1-214 GEN1
Solar/Wind Harmer
0.243
276603SUBLETTE C
Solar/Wind Harmer
0
274762LEE CO EC;3U
Adder
8.222
270209AC1-174_GEN
Solar/Wind Harmer
0
938861AE1-114 GEN
Solar/Wind Harmer
3.491
274856ECOGROVE ;U1
Solar/Wind Harmer
0.145
276611AD2-172 GEN
Solar/Wind Harmer
0.002
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
962691AG1-118 GEN
Solar/Wind Harmer
18.322
970825AG2-519 GEN
Solar/Wind Harmer
6.767
274696ROCKY RD ;4P
Adder
9.957
274697ROCKY RD ;3P
Adder
2.642
315821AE2-092 GEN
Solar/Wind Helper
3.216
316468AD1-105 GEN
Solar/Wind Helper
1.124
971543AH1-269 GEN
50/50
12.247
971313AH1-133 GEN
Solar/Wind Harmer
10.952
270132AB1-180 C
Adder
0.169
971061AG2-657 GEN
Solar/Wind Harmer
5.368
965411AG1-406 GEN
Solar/Wind Harmer
2.719
270367AC2-061_GEN
Solar/Wind Harmer
0.005
316123AC1-075 GEN
Solar/Wind Harmer
0.168
25196108MFTGT2
Adder
1.425
25196108MFTGT2
Adder
1.324
970879AG2-548 GEN
Solar/Wind Harmer
5.761
25196408WSDLE3
Adder
8.08
25196308WSDLE2
Adder
8.01
25196208WSDLE1
Adder
7.99
25196708WSDLE6
Adder
7.97
276174W4-005 GEN2
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
957751AF2-069 GEN
Solar/Wind Harmer
0.204
270240V3-007_GEN2
Solar/Wind Harmer
0.002
971681AH1-341 GEN
Solar/Wind Harmer
9.917
276612AE2-035 GEN
Solar/Wind Harmer
0.002
24691005MDL-2G C
Solar/Wind Harmer
0.001
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
971177AH1-047 GEN
Solar/Wind Harmer
3.774
270594AE1-207 GEN
Solar/Wind Harmer
6.853
971673AH1-337 GEN
Solar/Wind Harmer
3.956
3148133STUARTS
Solar/Wind Helper
0.313
24684705SMG5
50/50
0.856
3151561HALLBR1
50/50
0.57
270173AC1-122 GEN
Solar/Wind Harmer
0.677
941801AE2-185 GEN
Solar/Wind Harmer
7.452
970913AG2-568 GEN
Solar/Wind Harmer
7.677
270053AF1-130 C
Solar/Wind Harmer
2.047
24686405CER G5
Adder
9.796
970273AG2-179 GEN
Solar/Wind Harmer
4.425
339250AF1-203 GEN
Solar/Wind Harmer
0.001
962251AG1-071 GEN
Solar/Wind Harmer
4.496
276686W4-005 GEN3
Solar/Wind Harmer
0.001
270356AE2-297 GEN
Solar/Wind Harmer
0.008
270222AC2-111 GEN
Solar/Wind Harmer
3.158
965931AG1-462 GEN
Solar/Wind Harmer
15.879
965091AG1-374 GEN
Solar/Wind Harmer
18.654
274878BISHOP HL;2U
Solar/Wind Harmer
0.208
274760LEE CO EC;1U
Adder
8.222
972236AH1-702 GEN2
Adder
1.93
274872LEEDK;1U
Solar/Wind Harmer
0.224
270004AE1-209 GEN
Solar/Wind Harmer
1.324
238148AE2-230_GEN2
Solar/Wind Helper
0.423
316006AB2-029 C
Solar/Wind Helper
0.112
316045AC1-158 PL2
Solar/Wind Helper
4.023
957141AF2-008_MTX
Adder
54.545
944201AF1-088_MTX
Adder
109.09
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.415
NYPJM->LTFIMP_NY
CLTF
3.248
TVALTFEXP_TVA->PJM
CLTF
10.606
AG2-052LTFEXP_AG2-052->PJM
LTF
0.202
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.111
LGEELTFEXP_LGEE->PJM
CLTF
6.763
MECLTFEXP_MEC->PJM
CLTF
15.415
AH1-155LTFEXP_AH1-155->PJM
LTF
0.303
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.315
WECLTFEXP_WEC->PJM
CLTF
3.371
LAGNLTFEXP_LAGN->PJM
CLTF
20.28
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.555
CPLELTFEXP_CPLE->PJM
CLTF
6.226
SIGELTFEXP_SIGE->PJM
CLTF
0.508

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-020_SRT-SL


Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-020_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.02 %
Rating:3610.0 MVA
Rating Type:B
MVA to Mitigate:4224.55
MW Contribution:18.93
Bus #Bus NameTypeMW Contribution
24290705CLAY-2
50/50
0.256
24290705CLAY-2
50/50
0.256
24684505SMG3
50/50
1.377
971277AH1-098 GEN
Solar/Wind Harmer
7.435
24728205BUCHG1
Adder
6.772
944971AF1-162 GEN
Solar/Wind Harmer
9.108
942751AE2-291 GEN
Solar/Wind Harmer
10.391
966021AG1-471 GEN
Solar/Wind Harmer
5.779
339231AF1-038_GEN
Solar/Wind Harmer
1.927
339255AE2-071 GEN
Solar/Wind Harmer
1.104
970653AG2-424 GEN
Solar/Wind Harmer
4.906
970653AG2-424 GEN
Solar/Wind Harmer
1.774
964571AG1-320 GEN
Solar/Wind Harmer
8.231
972045AH1-571 GEN
Solar/Wind Harmer
1.992
339221AD2-048_GEN
Solar/Wind Harmer
1.523
252509AD1-136 GEN
Solar/Wind Harmer
0.24
25183208HLCRTG
Solar/Wind Harmer
5.62
971073AG2-665 GEN
Solar/Wind Harmer
5.702
971073AG2-665 GEN
Solar/Wind Harmer
3.978
25194508D.CRK3
Adder
1.306
276911AD2-131_GEN
Solar/Wind Harmer
3.894
24728805RICHG1
Adder
3.406
274765LEE CO EC;6U
Adder
8.292
274763LEE CO EC;4U
Adder
8.195
274695ROCKY RD ;2P
Adder
9.789
966871AG1-558 GEN
Solar/Wind Helper
0.307
24734805WLF1G4
Adder
8.22
24735105WLF2G1
Adder
8.049
270400AC1-102 GEN
Solar/Wind Harmer
5.58
941621AE2-160 GEN
Adder
4.308
957241AF2-018 GEN
Solar/Wind Harmer
5.782
24477305BRIDGE
Adder
0.422
270329AC1-082 GEN1
Solar/Wind Harmer
0.489
3429211JKCT 2G
Adder
11.941
970455AG2-298 GEN
Solar/Wind Harmer
6.067
339243AC2-075 GEN1
Solar/Wind Harmer
0.449
972163AH1-664 GEN
Solar/Wind Harmer
9.805
944221AF1-090 GEN
Solar/Wind Harmer
10.083
25196508WSDLE4
Adder
7.822
274746AC1-111 G10
Adder
4.901
23546401DTGZ2-030
Solar/Wind Helper
0.079
316164AC1-076 GEN
Solar/Wind Helper
1.177
238152AF2-075_GEN
Solar/Wind Helper
0.605
970479AG2-310 GEN
50/50
20.278
270205AE1-176
50/50
0.006
966251AG1-494 GEN
50/50
4.391
24728405LEESVG
50/50
0.297
971367AH1-164 GEN
Solar/Wind Harmer
7.012
941821AE2-187 GEN
Solar/Wind Harmer
9.82
270197AD1-017 GEN1
Solar/Wind Harmer
2.549
270336AE1-100 GEN
Solar/Wind Harmer
2.762
943811AF1-049 GEN
Solar/Wind Harmer
5.705
24735205WLF2G2
Adder
8.049
24723205RIVRG3
Adder
23.068
24686105CER G3
Adder
9.94
970947AG2-589 GEN
Solar/Wind Harmer
2.153
24721705FLATG2
Adder
21.813
971821AH1-427 GEN
Solar/Wind Harmer
10.401
964901AG1-354 GEN
Solar/Wind Harmer
15.577
339241AF1-083 GEN
Solar/Wind Harmer
1.723
943111AE2-339 GEN
Solar/Wind Harmer
0.888
945681AF1-233 GEN
Solar/Wind Harmer
18.436
270445AC2-157 GEN2
Solar/Wind Harmer
5.271
25194608D.CRK4
Adder
1.519
253432AC1-085 GEN2
Solar/Wind Harmer
0.245
946171AF1-282 GEN
Solar/Wind Harmer
9.139
24728605AND G2
Adder
3.502
274828WAUKEGAN ;BP
Adder
9.716
274682WAUKEGAN ;7U
Adder
15.803
274745AC1-111 GEN9
Adder
4.901
253370AE2-315 SEC1
Adder
1.753
253371AE2-315 SEC2
Adder
1.658
316499AE2-029_GEN
Solar/Wind Helper
1.727
316095T157 G97
Solar/Wind Helper
1.133
966881AG1-559 GEN
Solar/Wind Helper
0.314
316473AC1-191 GEN
Solar/Wind Helper
1.391
970823AG2-518 GEN
50/50
8.396
247619Y1-049
50/50
0.915
24416005BYLLESBY
50/50
0.031
958121AF2-106 GEN
Solar/Wind Harmer
9.423
971331AH1-145 GEN
Solar/Wind Harmer
18.398
270346AE1-212 GEN
Solar/Wind Harmer
13.986
971461AH1-227 GEN
Solar/Wind Harmer
7.029
970223AG2-152 GEN
Solar/Wind Harmer
17.643
24686205CER G4
Adder
9.888
3429391JKCT 9G
Adder
8.45
957541AF2-048 GEN
Solar/Wind Harmer
1.539
958171AF2-111 GEN
Solar/Wind Harmer
24.064
970519AG2-331 GEN
Solar/Wind Harmer
16.62
970699AG2-449 GEN
Solar/Wind Harmer
10.995
25196608WSDLE5
Adder
7.903
970193AG2-126 GEN
Solar/Wind Harmer
13.773
24728705AND G3
Adder
7.324
253406AD2-031_GEN
Solar/Wind Harmer
1.157
3147666LOUISA
Solar/Wind Helper
1.091
316254AC1-120 GEN1
Solar/Wind Helper
1.164
970281AG2-184 GEN
Solar/Wind Harmer
27.237
962211AG1-066 GEN
Solar/Wind Harmer
3.014
972203AH1-686 GEN
Adder
2.718
970165AG2-112 GEN
Solar/Wind Harmer
1.315
970163AG2-111 GEN
Solar/Wind Harmer
1.255
252524AE2-267 GEN
Solar/Wind Harmer
1.454
276785W4-005 GEN1
Solar/Wind Harmer
2.743
276849AB2-070 GEN2
Solar/Wind Harmer
2.04
970481AG2-311 GEN
50/50
11.948
24728405LEESVG
50/50
0.296
943031AE2-326 GEN
Solar/Wind Harmer
6.798
270574AD1-017 GEN2
Solar/Wind Harmer
8.482
3147123OTTER R
Solar/Wind Harmer
-0.014
270030AE2-140 GEN
Solar/Wind Harmer
30.98
960911AF2-382 GEN
Solar/Wind Harmer
10.985
972103AH1-617 GEN
Solar/Wind Harmer
25.94
24721905FLATG4
Adder
21.813
971155AH1-034 GEN
Solar/Wind Harmer
10.404
960741AF2-365 GEN
Solar/Wind Harmer
5.133
25194608D.CRK4
Adder
1.519
253316AC1-085 GEN3
Solar/Wind Harmer
7.655
253433AC1-085 GEN1
Solar/Wind Harmer
4.859
946181AF1-283 GEN
Solar/Wind Harmer
11.881
24728505AND G1
Adder
3.502
276668AB2-070 GEN1
Solar/Wind Harmer
2.04
274767LEE CO EC;8U
Adder
8.175
274682WAUKEGAN ;7U
Adder
15.803
253370AE2-315 SEC1
Adder
1.753
253371AE2-315 SEC2
Adder
1.658
316192AB2-158 GEN
Solar/Wind Helper
1.845
316097T157 G90
Solar/Wind Helper
1.133
316336AC2-165 C
Solar/Wind Helper
1.289
3142416OLDCHRC
Solar/Wind Helper
0.58
3142416OLDCHRC
Solar/Wind Helper
0.222
24290605CLAY-1
50/50
0.256
24290605CLAY-1
50/50
0.256
24684405SMG2
50/50
2.226
316217AC1-145 GEN
Solar/Wind Harmer
4.25
316197AC1-042 GEN
Solar/Wind Harmer
3.222
942671AE2-283 GEN
Solar/Wind Harmer
8.674
971485AH1-239 GEN
Solar/Wind Harmer
8.537
964781AG1-341 GEN
Solar/Wind Harmer
11.023
971081AG2-670 GEN
Solar/Wind Harmer
7.773
942891AE2-308 GEN
Solar/Wind Harmer
10.233
972043AH1-570 GEN
Solar/Wind Harmer
2.49
25194408D.CRK1
Adder
6.985
945391AF1-204 GEN
Solar/Wind Harmer
12.796
24728905RICHG2
Adder
3.406
972267AH1-718 GEN
Adder
3.711
274764LEE CO EC;5U
Adder
8.292
274683WAUKEGAN ;8U
Adder
18.536
274683WAUKEGAN ;8U
Adder
15.625
274693ROCKY RD ;1P
Adder
9.693
3132123MT JACKSON
Solar/Wind Helper
1.392
966001AG1-469 GEN
Solar/Wind Helper
0.321
270583AD2-179 GEN
Solar/Wind Harmer
20.758
270214AC2-123 GEN
Solar/Wind Harmer
4.319
971225AH1-072 GEN
Solar/Wind Harmer
2.74
971227AH1-073 GEN
Solar/Wind Harmer
2.74
24723005RIVRG1
Adder
23.068
24723105RIVRG2
Adder
23.068
24685805CER G1
Adder
9.875
24685905CER G2
Adder
9.875
971125AH1-004 GEN
Solar/Wind Harmer
4.003
270444AC2-157 GEN1
Solar/Wind Harmer
5.271
252519AF1-045_GEN
Solar/Wind Harmer
5.628
252516AE2-318_GEN
Solar/Wind Harmer
4.293
276916AD2-100_GEN
Solar/Wind Harmer
19.269
957381AF2-032 GEN
Solar/Wind Harmer
0.383
253317AC1-085 GEN4
Solar/Wind Harmer
7.655
276763AC1-053 GEN1
Solar/Wind Harmer
3.59
276764AC1-053 GEN2
Solar/Wind Harmer
3.59
253370AE2-315 SEC1
Adder
1.753
315651AD1-115 GEN
Solar/Wind Helper
0.841
316447AC1-158 HLD
Solar/Wind Helper
2.779
24684305SMG1
50/50
0.807
270013AE1-250 PV
Solar/Wind Harmer
3.259
960161AF2-307 GEN
Solar/Wind Harmer
6.695
339236AF1-050_GEN
Solar/Wind Harmer
1.882
970107AG2-081 GEN
Solar/Wind Harmer
3.003
970235AG2-159 GEN
Solar/Wind Harmer
3.901
970235AG2-159 GEN
Solar/Wind Harmer
2.382
270186AC1-089 GEN
Solar/Wind Harmer
5.863
970239AG2-162 GEN
Solar/Wind Harmer
10.536
962581AG1-107 GEN
Solar/Wind Harmer
4.763
961491AF2-440 GEN
Solar/Wind Harmer
1.98
970879AG2-548 GEN
Solar/Wind Harmer
5.702
970241AG2-163 GEN
Solar/Wind Harmer
22.567
274762LEE CO EC;3U
Adder
8.273
274696ROCKY RD ;4P
Adder
10.02
274697ROCKY RD ;3P
Adder
2.659
315821AE2-092 GEN
Solar/Wind Helper
3.222
316468AD1-105 GEN
Solar/Wind Helper
1.129
3147312GRETNA
Solar/Wind Harmer
-0.005
971687AH1-348 GEN
Solar/Wind Harmer
1.364
971315AH1-136 GEN
Solar/Wind Harmer
2.441
270331AC1-082 GEN3
Solar/Wind Harmer
0.49
970333AG2-219 GEN
Solar/Wind Harmer
30.235
25196808ZIMRHP
Adder
71.09
25196008MFTGT1
Adder
1.302
274880W4-005 GEN4
Solar/Wind Harmer
2.743
274761LEE CO EC;2U
Adder
8.273
237061AD1-155 GEN
Solar/Wind Helper
0.05
23583801GRNGAP
Solar/Wind Helper
4.315
238149AF1-291A_GEN
Solar/Wind Helper
0.121
316258AE1-075 C
Solar/Wind Helper
0.319
972175AH1-670 GEN
Solar/Wind Harmer
4.749
24415905BUCK
50/50
0.034
971329AH1-144 GEN
Solar/Wind Harmer
23.734
958131AF2-107 GEN
Solar/Wind Harmer
7.112
971403AH1-188 GEN
Solar/Wind Harmer
18.932
970273AG2-179 GEN
Solar/Wind Harmer
2.594
960001AF2-291 GEN
Solar/Wind Harmer
3.136
3429421JKCT 10G
Adder
8.45
971565AH1-281 GEN
Solar/Wind Harmer
2.012
927014AC1-188 GEN
Solar/Wind Harmer
1.543
970091AG2-072 GEN
Adder
74.457
963741AG1-226 GEN
Solar/Wind Harmer
40.621
274822ROCKFORD ;11
Adder
17.383
3132273ORANGE
Solar/Wind Helper
0.056
316170AC1-121 GEN2
Solar/Wind Helper
0.388
316313AB2-026
Solar/Wind Helper
0.355
970563AG2-360 GEN
50/50
45.959
962751AG1-124 GEN
Solar/Wind Harmer
18.84
3147312GRETNA
Solar/Wind Harmer
-0.021
3146802CHATHAM
Solar/Wind Harmer
-0.02
270016AE1-250 BESS
Solar/Wind Harmer
3.259
972273AH1-721 GEN
Adder
89.748
966571AG1-526 GEN
Solar/Wind Harmer
23.009
970093AG2-073 GEN
Solar/Wind Harmer
10.328
971191AH1-055 GEN
Solar/Wind Harmer
22.339
972167AH1-666 GEN
Solar/Wind Harmer
7.817
970243AG2-164 GEN
Solar/Wind Harmer
24.738
25196008MFTGT1
Adder
1.261
252510AF1-249 C
Solar/Wind Harmer
0.387
942481AE2-261 GEN
Solar/Wind Harmer
27.393
276621W2-048 GEN
Solar/Wind Harmer
5.679
24288905REUSENS
50/50
0.057
24684605SMG4
50/50
2.241
24728305BUCHG2
Adder
6.772
270018AE2-047 C O1
Solar/Wind Harmer
1.828
24686505CER G6
Adder
9.927
962241AG1-070 GEN
Solar/Wind Harmer
4.662
3429241JKCT 3G
Adder
12.097
339216AC1-074 GEN
Solar/Wind Harmer
1.659
252507AC2-088 GEN
Solar/Wind Harmer
1.681
965911AG1-460 GEN
Solar/Wind Harmer
1.278
276615X2-022 GEN
Solar/Wind Harmer
1.783
963831AG1-236 GEN
Solar/Wind Harmer
8.931
274766LEE CO EC;7U
Adder
8.175
972235AH1-702 GEN1
Adder
2.234
315616AA1-038_C
Solar/Wind Helper
3.295
3148013FISHERV
Solar/Wind Helper
0.523
3147666LOUISA
Solar/Wind Helper
0.628
238147AE2-230_GEN1
Solar/Wind Helper
0.423
316405AF2-144 C
Solar/Wind Helper
0.266
316044AC1-158 PL1
Solar/Wind Helper
1.263
316450AC1-158 RIC
Solar/Wind Helper
0.337
276838X2-022 GEN2
Solar/Wind Harmer
0.212
971993AH1-541 GEN
Solar/Wind Harmer
8.379
274729ELWOOD EC;1P
Adder
1.688
3147983MERCK5
Solar/Wind Helper
0.199
971543AH1-269 GEN
50/50
12.267
971313AH1-133 GEN
Solar/Wind Harmer
15.745
270132AB1-180 C
Adder
0.169
971061AG2-657 GEN
Solar/Wind Harmer
11.059
965411AG1-406 GEN
Solar/Wind Harmer
2.733
270367AC2-061_GEN
Solar/Wind Harmer
3.029
316123AC1-075 GEN
Solar/Wind Harmer
1.494
25196108MFTGT2
Adder
1.435
25196108MFTGT2
Adder
1.332
970879AG2-548 GEN
Solar/Wind Harmer
3.978
25196408WSDLE3
Adder
8.135
25196308WSDLE2
Adder
8.064
25196208WSDLE1
Adder
8.044
25196708WSDLE6
Adder
8.024
276174W4-005 GEN2
Solar/Wind Harmer
2.743
3148133STUARTS
Solar/Wind Helper
0.314
24684705SMG5
50/50
0.857
3151561HALLBR1
50/50
0.57
270173AC1-122 GEN
Solar/Wind Harmer
3.281
941801AE2-185 GEN
Solar/Wind Harmer
9.82
970913AG2-568 GEN
Solar/Wind Harmer
11.054
270053AF1-130 C
Solar/Wind Harmer
4.837
24686405CER G5
Adder
9.849
970273AG2-179 GEN
Solar/Wind Harmer
4.143
339250AF1-203 GEN
Solar/Wind Harmer
0.631
962251AG1-071 GEN
Solar/Wind Harmer
5.699
276686W4-005 GEN3
Solar/Wind Harmer
2.743
270356AE2-297 GEN
Solar/Wind Harmer
4.125
274760LEE CO EC;1U
Adder
8.273
972236AH1-702 GEN2
Adder
1.942
238148AE2-230_GEN2
Solar/Wind Helper
0.425
316006AB2-029 C
Solar/Wind Helper
0.113
316045AC1-158 PL2
Solar/Wind Helper
4.042
966391AG1-508 GEN
Solar/Wind Harmer
6.388
270069AE2-166 C O1
Solar/Wind Harmer
4.514
24734705WLF1G3
Adder
8.22
24734905WLF1G5
Adder
8.22
270399AC1-101 GEN
Solar/Wind Harmer
5.58
972143AH1-644 GEN
Solar/Wind Harmer
12.97
971981AH1-535 GEN
Solar/Wind Harmer
12.604
270330AC1-082 GEN2
Solar/Wind Harmer
0.83
965401AG1-405 GEN
Solar/Wind Harmer
6.089
339211AE2-254 GEN
Solar/Wind Harmer
1.572
972165AH1-665 GEN
Solar/Wind Harmer
7.844
971985AH1-537 GEN
Solar/Wind Harmer
17.415
274823ROCKFORD ;21
Adder
17.257
3148013FISHERV
Solar/Wind Helper
0.301
276848AB2-070 GEN3
Solar/Wind Harmer
2.04
274744AC1-111 GEN8
Adder
4.901
25306009OHH W.
Adder
2.523
253372AE2-315 SEC3
Adder
1.658
253372AE2-315 SEC3
Adder
1.658
3148463FAIRFLD
Solar/Wind Helper
0.727
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
316312AB1-027
Solar/Wind Helper
0.425
3141426STAFORD
Solar/Wind Helper
0.049
957141AF2-008_MTX
Adder
54.874
944201AF1-088_MTX
Adder
109.749
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.199
NYPJM->LTFIMP_NY
CLTF
3.272
TVALTFEXP_TVA->PJM
CLTF
10.651
AG2-052LTFEXP_AG2-052->PJM
LTF
0.203
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.77
LGEELTFEXP_LGEE->PJM
CLTF
6.802
MECLTFEXP_MEC->PJM
CLTF
15.504
AH1-155LTFEXP_AH1-155->PJM
LTF
0.304
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.491
WECLTFEXP_WEC->PJM
CLTF
3.393
LAGNLTFEXP_LAGN->PJM
CLTF
20.369
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.617
CPLELTFEXP_CPLE->PJM
CLTF
6.237
SIGELTFEXP_SIGE->PJM
CLTF
0.511

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-021_SRT-SL


Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-021_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.77 %
Rating:3610.0 MVA
Rating Type:B
MVA to Mitigate:4215.43
MW Contribution:18.88
Bus #Bus NameTypeMW Contribution
24290705CLAY-2
50/50
0.255
24290705CLAY-2
50/50
0.255
24684505SMG3
50/50
1.376
971277AH1-098 GEN
Solar/Wind Harmer
7.425
24728205BUCHG1
Adder
6.757
944971AF1-162 GEN
Solar/Wind Harmer
9.08
942751AE2-291 GEN
Solar/Wind Harmer
10.387
966021AG1-471 GEN
Solar/Wind Harmer
5.761
339231AF1-038_GEN
Solar/Wind Harmer
1.921
339255AE2-071 GEN
Solar/Wind Harmer
1.1
970653AG2-424 GEN
Solar/Wind Harmer
4.888
970653AG2-424 GEN
Solar/Wind Harmer
1.767
964571AG1-320 GEN
Solar/Wind Harmer
8.199
972045AH1-571 GEN
Solar/Wind Harmer
1.983
339221AD2-048_GEN
Solar/Wind Harmer
1.517
252509AD1-136 GEN
Solar/Wind Harmer
0.239
25183208HLCRTG
Solar/Wind Harmer
5.594
971073AG2-665 GEN
Solar/Wind Harmer
5.67
971073AG2-665 GEN
Solar/Wind Harmer
3.956
25194508D.CRK3
Adder
1.3
276911AD2-131_GEN
Solar/Wind Harmer
3.878
24728805RICHG1
Adder
3.391
274765LEE CO EC;6U
Adder
8.257
274763LEE CO EC;4U
Adder
8.16
274695ROCKY RD ;2P
Adder
9.746
966871AG1-558 GEN
Solar/Wind Helper
0.306
24734805WLF1G4
Adder
8.202
24735105WLF2G1
Adder
8.031
270400AC1-102 GEN
Solar/Wind Harmer
5.563
941621AE2-160 GEN
Adder
4.292
957241AF2-018 GEN
Solar/Wind Harmer
5.764
24477305BRIDGE
Adder
0.42
270329AC1-082 GEN1
Solar/Wind Harmer
0.486
3429211JKCT 2G
Adder
11.894
970455AG2-298 GEN
Solar/Wind Harmer
6.044
339243AC2-075 GEN1
Solar/Wind Harmer
0.447
972163AH1-664 GEN
Solar/Wind Harmer
9.762
944221AF1-090 GEN
Solar/Wind Harmer
10.042
25196508WSDLE4
Adder
7.785
274746AC1-111 G10
Adder
4.879
23546401DTGZ2-030
Solar/Wind Helper
0.079
316164AC1-076 GEN
Solar/Wind Helper
1.173
238152AF2-075_GEN
Solar/Wind Helper
0.603
970479AG2-310 GEN
50/50
20.262
270205AE1-176
50/50
0.006
966251AG1-494 GEN
50/50
4.389
24728405LEESVG
50/50
0.297
971367AH1-164 GEN
Solar/Wind Harmer
7.006
941821AE2-187 GEN
Solar/Wind Harmer
9.814
270197AD1-017 GEN1
Solar/Wind Harmer
2.547
270336AE1-100 GEN
Solar/Wind Harmer
2.759
943811AF1-049 GEN
Solar/Wind Harmer
5.698
24735205WLF2G2
Adder
8.031
24723205RIVRG3
Adder
22.989
24686105CER G3
Adder
9.903
24721705FLATG2
Adder
21.725
970947AG2-589 GEN
Solar/Wind Harmer
2.143
971821AH1-427 GEN
Solar/Wind Harmer
10.363
964901AG1-354 GEN
Solar/Wind Harmer
15.523
339241AF1-083 GEN
Solar/Wind Harmer
1.717
943111AE2-339 GEN
Solar/Wind Harmer
0.884
945681AF1-233 GEN
Solar/Wind Harmer
18.356
270445AC2-157 GEN2
Solar/Wind Harmer
5.249
25194608D.CRK4
Adder
1.511
253432AC1-085 GEN2
Solar/Wind Harmer
0.243
946171AF1-282 GEN
Solar/Wind Harmer
9.095
24728605AND G2
Adder
3.486
274828WAUKEGAN ;BP
Adder
9.674
274682WAUKEGAN ;7U
Adder
15.734
274745AC1-111 GEN9
Adder
4.879
253370AE2-315 SEC1
Adder
1.744
253371AE2-315 SEC2
Adder
1.649
316499AE2-029_GEN
Solar/Wind Helper
1.725
970823AG2-518 GEN
50/50
8.387
247619Y1-049
50/50
0.914
24416005BYLLESBY
50/50
0.031
958121AF2-106 GEN
Solar/Wind Harmer
9.412
971331AH1-145 GEN
Solar/Wind Harmer
18.373
270346AE1-212 GEN
Solar/Wind Harmer
13.951
971461AH1-227 GEN
Solar/Wind Harmer
7.011
970223AG2-152 GEN
Solar/Wind Harmer
17.629
24686205CER G4
Adder
9.851
3429391JKCT 9G
Adder
8.417
957541AF2-048 GEN
Solar/Wind Harmer
1.531
958171AF2-111 GEN
Solar/Wind Harmer
23.957
970519AG2-331 GEN
Solar/Wind Harmer
16.549
970699AG2-449 GEN
Solar/Wind Harmer
10.948
25196608WSDLE5
Adder
7.866
970193AG2-126 GEN
Solar/Wind Harmer
13.715
24728705AND G3
Adder
7.292
253406AD2-031_GEN
Solar/Wind Harmer
1.151
3147666LOUISA
Solar/Wind Helper
1.089
316254AC1-120 GEN1
Solar/Wind Helper
1.161
970481AG2-311 GEN
50/50
11.94
24728405LEESVG
50/50
0.296
943031AE2-326 GEN
Solar/Wind Harmer
6.789
270574AD1-017 GEN2
Solar/Wind Harmer
8.476
3147123OTTER R
Solar/Wind Harmer
-0.014
24290605CLAY-1
50/50
0.255
24290605CLAY-1
50/50
0.255
24684405SMG2
50/50
2.225
316217AC1-145 GEN
Solar/Wind Harmer
4.248
316197AC1-042 GEN
Solar/Wind Harmer
3.22
942671AE2-283 GEN
Solar/Wind Harmer
8.669
971485AH1-239 GEN
Solar/Wind Harmer
8.509
964781AG1-341 GEN
Solar/Wind Harmer
10.986
971081AG2-670 GEN
Solar/Wind Harmer
7.746
942891AE2-308 GEN
Solar/Wind Harmer
10.193
972043AH1-570 GEN
Solar/Wind Harmer
2.479
25194408D.CRK1
Adder
6.953
945391AF1-204 GEN
Solar/Wind Harmer
12.742
24728905RICHG2
Adder
3.391
972267AH1-718 GEN
Adder
3.695
274764LEE CO EC;5U
Adder
8.257
274683WAUKEGAN ;8U
Adder
18.455
274683WAUKEGAN ;8U
Adder
15.556
274693ROCKY RD ;1P
Adder
9.65
3132123MT JACKSON
Solar/Wind Helper
1.39
966001AG1-469 GEN
Solar/Wind Helper
0.32
270030AE2-140 GEN
Solar/Wind Harmer
30.945
960911AF2-382 GEN
Solar/Wind Harmer
10.959
972103AH1-617 GEN
Solar/Wind Harmer
25.867
24721905FLATG4
Adder
21.725
971155AH1-034 GEN
Solar/Wind Harmer
10.369
960741AF2-365 GEN
Solar/Wind Harmer
5.115
25194608D.CRK4
Adder
1.511
253316AC1-085 GEN3
Solar/Wind Harmer
7.618
253433AC1-085 GEN1
Solar/Wind Harmer
4.836
946181AF1-283 GEN
Solar/Wind Harmer
11.823
24728505AND G1
Adder
3.486
276668AB2-070 GEN1
Solar/Wind Harmer
2.031
274767LEE CO EC;8U
Adder
8.14
274682WAUKEGAN ;7U
Adder
15.734
253370AE2-315 SEC1
Adder
1.744
253371AE2-315 SEC2
Adder
1.649
316192AB2-158 GEN
Solar/Wind Helper
1.84
316097T157 G90
Solar/Wind Helper
1.128
316336AC2-165 C
Solar/Wind Helper
1.286
270583AD2-179 GEN
Solar/Wind Harmer
20.732
270214AC2-123 GEN
Solar/Wind Harmer
4.313
971225AH1-072 GEN
Solar/Wind Harmer
2.733
971227AH1-073 GEN
Solar/Wind Harmer
2.733
24723005RIVRG1
Adder
22.989
24723105RIVRG2
Adder
22.989
24685805CER G1
Adder
9.838
24685905CER G2
Adder
9.838
971125AH1-004 GEN
Solar/Wind Harmer
3.987
270444AC2-157 GEN1
Solar/Wind Harmer
5.249
252519AF1-045_GEN
Solar/Wind Harmer
5.601
252516AE2-318_GEN
Solar/Wind Harmer
4.272
276916AD2-100_GEN
Solar/Wind Harmer
19.19
957381AF2-032 GEN
Solar/Wind Harmer
0.382
253317AC1-085 GEN4
Solar/Wind Harmer
7.618
276763AC1-053 GEN1
Solar/Wind Harmer
3.575
276764AC1-053 GEN2
Solar/Wind Harmer
3.575
253370AE2-315 SEC1
Adder
1.744
315651AD1-115 GEN
Solar/Wind Helper
0.839
316447AC1-158 HLD
Solar/Wind Helper
2.77
316095T157 G97
Solar/Wind Helper
1.128
966881AG1-559 GEN
Solar/Wind Helper
0.314
316473AC1-191 GEN
Solar/Wind Helper
1.388
24684305SMG1
50/50
0.806
270013AE1-250 PV
Solar/Wind Harmer
3.257
960161AF2-307 GEN
Solar/Wind Harmer
6.669
339236AF1-050_GEN
Solar/Wind Harmer
1.875
970107AG2-081 GEN
Solar/Wind Harmer
2.99
970235AG2-159 GEN
Solar/Wind Harmer
3.885
970235AG2-159 GEN
Solar/Wind Harmer
2.372
270186AC1-089 GEN
Solar/Wind Harmer
5.836
970239AG2-162 GEN
Solar/Wind Harmer
10.492
962581AG1-107 GEN
Solar/Wind Harmer
4.741
961491AF2-440 GEN
Solar/Wind Harmer
1.97
970879AG2-548 GEN
Solar/Wind Harmer
5.67
970241AG2-163 GEN
Solar/Wind Harmer
22.469
274762LEE CO EC;3U
Adder
8.237
274696ROCKY RD ;4P
Adder
9.976
274697ROCKY RD ;3P
Adder
2.648
315821AE2-092 GEN
Solar/Wind Helper
3.218
316468AD1-105 GEN
Solar/Wind Helper
1.126
3147312GRETNA
Solar/Wind Harmer
-0.005
971687AH1-348 GEN
Solar/Wind Harmer
1.36
971315AH1-136 GEN
Solar/Wind Harmer
2.433
270331AC1-082 GEN3
Solar/Wind Harmer
0.488
970333AG2-219 GEN
Solar/Wind Harmer
30.107
25196808ZIMRHP
Adder
70.761
25196008MFTGT1
Adder
1.296
274880W4-005 GEN4
Solar/Wind Harmer
2.731
274761LEE CO EC;2U
Adder
8.237
237061AD1-155 GEN
Solar/Wind Helper
0.05
23583801GRNGAP
Solar/Wind Helper
4.296
238149AF1-291A_GEN
Solar/Wind Helper
0.12
316258AE1-075 C
Solar/Wind Helper
0.319
972175AH1-670 GEN
Solar/Wind Harmer
4.729
24415905BUCK
50/50
0.034
971329AH1-144 GEN
Solar/Wind Harmer
23.701
958131AF2-107 GEN
Solar/Wind Harmer
7.109
971403AH1-188 GEN
Solar/Wind Harmer
18.877
970273AG2-179 GEN
Solar/Wind Harmer
2.585
960001AF2-291 GEN
Solar/Wind Harmer
3.12
3429421JKCT 10G
Adder
8.417
971565AH1-281 GEN
Solar/Wind Harmer
2.004
927014AC1-188 GEN
Solar/Wind Harmer
1.535
970091AG2-072 GEN
Adder
74.149
963741AG1-226 GEN
Solar/Wind Harmer
40.444
24288905REUSENS
50/50
0.057
24684605SMG4
50/50
2.239
24728305BUCHG2
Adder
6.757
270018AE2-047 C O1
Solar/Wind Harmer
1.826
24686505CER G6
Adder
9.89
962241AG1-070 GEN
Solar/Wind Harmer
4.647
3429241JKCT 3G
Adder
12.05
339216AC1-074 GEN
Solar/Wind Harmer
1.652
252507AC2-088 GEN
Solar/Wind Harmer
1.673
965911AG1-460 GEN
Solar/Wind Harmer
1.273
276615X2-022 GEN
Solar/Wind Harmer
1.776
963831AG1-236 GEN
Solar/Wind Harmer
8.893
274766LEE CO EC;7U
Adder
8.14
972235AH1-702 GEN1
Adder
2.224
315616AA1-038_C
Solar/Wind Helper
3.294
3148013FISHERV
Solar/Wind Helper
0.523
3147666LOUISA
Solar/Wind Helper
0.626
238147AE2-230_GEN1
Solar/Wind Helper
0.422
316405AF2-144 C
Solar/Wind Helper
0.266
316044AC1-158 PL1
Solar/Wind Helper
1.259
316450AC1-158 RIC
Solar/Wind Helper
0.336
274822ROCKFORD ;11
Adder
17.308
3132273ORANGE
Solar/Wind Helper
0.056
316170AC1-121 GEN2
Solar/Wind Helper
0.387
316313AB2-026
Solar/Wind Helper
0.354
970563AG2-360 GEN
50/50
45.869
962751AG1-124 GEN
Solar/Wind Harmer
18.829
3147312GRETNA
Solar/Wind Harmer
-0.021
3146802CHATHAM
Solar/Wind Harmer
-0.02
270016AE1-250 BESS
Solar/Wind Harmer
3.257
972273AH1-721 GEN
Adder
89.448
966571AG1-526 GEN
Solar/Wind Harmer
22.923
970093AG2-073 GEN
Solar/Wind Harmer
10.289
971191AH1-055 GEN
Solar/Wind Harmer
22.23
972167AH1-666 GEN
Solar/Wind Harmer
7.783
970243AG2-164 GEN
Solar/Wind Harmer
24.633
25196008MFTGT1
Adder
1.255
252510AF1-249 C
Solar/Wind Harmer
0.385
942481AE2-261 GEN
Solar/Wind Harmer
27.279
276621W2-048 GEN
Solar/Wind Harmer
5.656
276838X2-022 GEN2
Solar/Wind Harmer
0.211
971993AH1-541 GEN
Solar/Wind Harmer
8.344
274729ELWOOD EC;1P
Adder
1.681
3147983MERCK5
Solar/Wind Helper
0.198
24684705SMG5
50/50
0.857
3151561HALLBR1
50/50
0.57
270173AC1-122 GEN
Solar/Wind Harmer
3.279
941801AE2-185 GEN
Solar/Wind Harmer
9.814
970913AG2-568 GEN
Solar/Wind Harmer
11.019
270053AF1-130 C
Solar/Wind Harmer
4.822
24686405CER G5
Adder
9.812
970273AG2-179 GEN
Solar/Wind Harmer
4.129
339250AF1-203 GEN
Solar/Wind Harmer
0.629
962251AG1-071 GEN
Solar/Wind Harmer
5.679
276686W4-005 GEN3
Solar/Wind Harmer
2.731
270356AE2-297 GEN
Solar/Wind Harmer
4.106
274760LEE CO EC;1U
Adder
8.237
972236AH1-702 GEN2
Adder
1.934
238148AE2-230_GEN2
Solar/Wind Helper
0.424
316006AB2-029 C
Solar/Wind Helper
0.113
316045AC1-158 PL2
Solar/Wind Helper
4.029
966391AG1-508 GEN
Solar/Wind Harmer
6.379
270069AE2-166 C O1
Solar/Wind Harmer
4.509
24734705WLF1G3
Adder
8.202
24734905WLF1G5
Adder
8.202
270399AC1-101 GEN
Solar/Wind Harmer
5.563
972143AH1-644 GEN
Solar/Wind Harmer
12.933
971981AH1-535 GEN
Solar/Wind Harmer
12.575
270330AC1-082 GEN2
Solar/Wind Harmer
0.826
965401AG1-405 GEN
Solar/Wind Harmer
6.068
339211AE2-254 GEN
Solar/Wind Harmer
1.566
972165AH1-665 GEN
Solar/Wind Harmer
7.81
971985AH1-537 GEN
Solar/Wind Harmer
17.332
274823ROCKFORD ;21
Adder
17.182
3148013FISHERV
Solar/Wind Helper
0.3
970281AG2-184 GEN
Solar/Wind Harmer
27.16
962211AG1-066 GEN
Solar/Wind Harmer
3.005
972203AH1-686 GEN
Adder
2.709
970165AG2-112 GEN
Solar/Wind Harmer
1.315
970163AG2-111 GEN
Solar/Wind Harmer
1.254
252524AE2-267 GEN
Solar/Wind Harmer
1.447
276849AB2-070 GEN2
Solar/Wind Harmer
2.031
276848AB2-070 GEN3
Solar/Wind Harmer
2.031
276785W4-005 GEN1
Solar/Wind Harmer
2.731
274744AC1-111 GEN8
Adder
4.879
25306009OHH W.
Adder
2.51
253372AE2-315 SEC3
Adder
1.649
253372AE2-315 SEC3
Adder
1.649
3148463FAIRFLD
Solar/Wind Helper
0.726
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
971543AH1-269 GEN
50/50
12.253
971313AH1-133 GEN
Solar/Wind Harmer
15.712
270132AB1-180 C
Adder
0.169
971061AG2-657 GEN
Solar/Wind Harmer
11.012
965411AG1-406 GEN
Solar/Wind Harmer
2.724
270367AC2-061_GEN
Solar/Wind Harmer
3.015
316123AC1-075 GEN
Solar/Wind Harmer
1.493
25196108MFTGT2
Adder
1.428
25196108MFTGT2
Adder
1.326
970879AG2-548 GEN
Solar/Wind Harmer
3.956
25196408WSDLE3
Adder
8.097
25196308WSDLE2
Adder
8.027
25196208WSDLE1
Adder
8.006
25196708WSDLE6
Adder
7.986
276174W4-005 GEN2
Solar/Wind Harmer
2.731
3148133STUARTS
Solar/Wind Helper
0.314
957141AF2-008_MTX
Adder
54.646
944201AF1-088_MTX
Adder
109.291
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.369
WECLTFEXP_WEC->PJM
CLTF
3.378
LAGNLTFEXP_LAGN->PJM
CLTF
20.308
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.574
CPLELTFEXP_CPLE->PJM
CLTF
6.229
SIGELTFEXP_SIGE->PJM
CLTF
0.509
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.655
NYPJM->LTFIMP_NY
CLTF
3.255
TVALTFEXP_TVA->PJM
CLTF
10.62
AG2-052LTFEXP_AG2-052->PJM
LTF
0.202
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.312
LGEELTFEXP_LGEE->PJM
CLTF
6.775
MECLTFEXP_MEC->PJM
CLTF
15.442
AH1-155LTFEXP_AH1-155->PJM
LTF
0.303

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AEP_P4_#37_05MOUNTN 765_B1_SRT-A


Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#37_05MOUNTN 765_B1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.68 %
Rating:3610.0 MVA
Rating Type:B
MVA to Mitigate:4211.98
MW Contribution:18.85
Bus #Bus NameTypeMW Contribution
24290705CLAY-2
50/50
0.255
24290705CLAY-2
50/50
0.255
24684505SMG3
50/50
1.376
971277AH1-098 GEN
Solar/Wind Harmer
7.42
24728205BUCHG1
Adder
6.75
944971AF1-162 GEN
Solar/Wind Harmer
9.068
942751AE2-291 GEN
Solar/Wind Harmer
10.385
966021AG1-471 GEN
Solar/Wind Harmer
5.753
339231AF1-038_GEN
Solar/Wind Harmer
1.918
339255AE2-071 GEN
Solar/Wind Harmer
1.099
970653AG2-424 GEN
Solar/Wind Harmer
4.88
970653AG2-424 GEN
Solar/Wind Harmer
1.764
964571AG1-320 GEN
Solar/Wind Harmer
8.186
972045AH1-571 GEN
Solar/Wind Harmer
1.98
339221AD2-048_GEN
Solar/Wind Harmer
1.514
252509AD1-136 GEN
Solar/Wind Harmer
0.238
25183208HLCRTG
Solar/Wind Harmer
5.582
25194508D.CRK3
Adder
1.297
971073AG2-665 GEN
Solar/Wind Harmer
5.656
971073AG2-665 GEN
Solar/Wind Harmer
3.946
24734805WLF1G4
Adder
8.194
24735105WLF2G1
Adder
8.023
270400AC1-102 GEN
Solar/Wind Harmer
5.556
941621AE2-160 GEN
Adder
4.285
957241AF2-018 GEN
Solar/Wind Harmer
5.757
24477305BRIDGE
Adder
0.419
270329AC1-082 GEN1
Solar/Wind Harmer
0.485
3429211JKCT 2G
Adder
11.873
970455AG2-298 GEN
Solar/Wind Harmer
6.034
339243AC2-075 GEN1
Solar/Wind Harmer
0.446
972163AH1-664 GEN
Solar/Wind Harmer
9.743
944221AF1-090 GEN
Solar/Wind Harmer
10.024
25196508WSDLE4
Adder
7.769
274746AC1-111 G10
Adder
4.87
23546401DTGZ2-030
Solar/Wind Helper
0.078
316164AC1-076 GEN
Solar/Wind Helper
1.172
238152AF2-075_GEN
Solar/Wind Helper
0.602
970823AG2-518 GEN
50/50
8.384
247619Y1-049
50/50
0.913
24416005BYLLESBY
50/50
0.031
958121AF2-106 GEN
Solar/Wind Harmer
9.407
971331AH1-145 GEN
Solar/Wind Harmer
18.361
270346AE1-212 GEN
Solar/Wind Harmer
13.936
971461AH1-227 GEN
Solar/Wind Harmer
7.003
970223AG2-152 GEN
Solar/Wind Harmer
17.623
24686205CER G4
Adder
9.835
3429391JKCT 9G
Adder
8.402
957541AF2-048 GEN
Solar/Wind Harmer
1.528
958171AF2-111 GEN
Solar/Wind Harmer
23.91
970519AG2-331 GEN
Solar/Wind Harmer
16.518
970699AG2-449 GEN
Solar/Wind Harmer
10.927
25196608WSDLE5
Adder
7.849
970193AG2-126 GEN
Solar/Wind Harmer
13.689
24728705AND G3
Adder
7.277
253406AD2-031_GEN
Solar/Wind Harmer
1.149
3147666LOUISA
Solar/Wind Helper
1.088
316254AC1-120 GEN1
Solar/Wind Helper
1.159
24290605CLAY-1
50/50
0.255
24290605CLAY-1
50/50
0.255
970481AG2-311 GEN
50/50
11.937
24728405LEESVG
50/50
0.295
943031AE2-326 GEN
Solar/Wind Harmer
6.784
270574AD1-017 GEN2
Solar/Wind Harmer
8.473
3147123OTTER R
Solar/Wind Harmer
-0.014
270030AE2-140 GEN
Solar/Wind Harmer
30.929
960911AF2-382 GEN
Solar/Wind Harmer
10.948
972103AH1-617 GEN
Solar/Wind Harmer
25.835
24721905FLATG4
Adder
21.686
971155AH1-034 GEN
Solar/Wind Harmer
10.354
960741AF2-365 GEN
Solar/Wind Harmer
5.107
25194608D.CRK4
Adder
1.508
253316AC1-085 GEN3
Solar/Wind Harmer
7.601
253433AC1-085 GEN1
Solar/Wind Harmer
4.825
946181AF1-283 GEN
Solar/Wind Harmer
11.797
24728505AND G1
Adder
3.48
276668AB2-070 GEN1
Solar/Wind Harmer
2.027
274767LEE CO EC;8U
Adder
8.125
274682WAUKEGAN ;7U
Adder
15.703
316192AB2-158 GEN
Solar/Wind Helper
1.838
316097T157 G90
Solar/Wind Helper
1.125
316336AC2-165 C
Solar/Wind Helper
1.285
270583AD2-179 GEN
Solar/Wind Harmer
20.721
270214AC2-123 GEN
Solar/Wind Harmer
4.311
971225AH1-072 GEN
Solar/Wind Harmer
2.73
971227AH1-073 GEN
Solar/Wind Harmer
2.73
24723005RIVRG1
Adder
22.954
24723105RIVRG2
Adder
22.954
24685805CER G1
Adder
9.822
24685905CER G2
Adder
9.822
971125AH1-004 GEN
Solar/Wind Harmer
3.98
270444AC2-157 GEN1
Solar/Wind Harmer
5.239
252519AF1-045_GEN
Solar/Wind Harmer
5.589
252516AE2-318_GEN
Solar/Wind Harmer
4.263
276916AD2-100_GEN
Solar/Wind Harmer
19.154
957381AF2-032 GEN
Solar/Wind Harmer
0.381
253317AC1-085 GEN4
Solar/Wind Harmer
7.601
276763AC1-053 GEN1
Solar/Wind Harmer
3.568
276764AC1-053 GEN2
Solar/Wind Harmer
3.568
315651AD1-115 GEN
Solar/Wind Helper
0.837
316447AC1-158 HLD
Solar/Wind Helper
2.766
970479AG2-310 GEN
50/50
20.255
270205AE1-176
50/50
0.006
966251AG1-494 GEN
50/50
4.388
24728405LEESVG
50/50
0.297
971367AH1-164 GEN
Solar/Wind Harmer
7.003
941821AE2-187 GEN
Solar/Wind Harmer
9.812
270197AD1-017 GEN1
Solar/Wind Harmer
2.546
270336AE1-100 GEN
Solar/Wind Harmer
2.757
943811AF1-049 GEN
Solar/Wind Harmer
5.695
24735205WLF2G2
Adder
8.023
24723205RIVRG3
Adder
22.954
24686105CER G3
Adder
9.887
24721705FLATG2
Adder
21.686
970947AG2-589 GEN
Solar/Wind Harmer
2.139
971821AH1-427 GEN
Solar/Wind Harmer
10.346
964901AG1-354 GEN
Solar/Wind Harmer
15.5
339241AF1-083 GEN
Solar/Wind Harmer
1.715
943111AE2-339 GEN
Solar/Wind Harmer
0.883
945681AF1-233 GEN
Solar/Wind Harmer
18.32
270445AC2-157 GEN2
Solar/Wind Harmer
5.239
25194608D.CRK4
Adder
1.508
253432AC1-085 GEN2
Solar/Wind Harmer
0.243
946171AF1-282 GEN
Solar/Wind Harmer
9.075
24728605AND G2
Adder
3.48
274828WAUKEGAN ;BP
Adder
9.655
274682WAUKEGAN ;7U
Adder
15.703
274745AC1-111 GEN9
Adder
4.87
316499AE2-029_GEN
Solar/Wind Helper
1.725
316095T157 G97
Solar/Wind Helper
1.125
966881AG1-559 GEN
Solar/Wind Helper
0.313
316473AC1-191 GEN
Solar/Wind Helper
1.387
24684305SMG1
50/50
0.806
270013AE1-250 PV
Solar/Wind Harmer
3.256
960161AF2-307 GEN
Solar/Wind Harmer
6.658
339236AF1-050_GEN
Solar/Wind Harmer
1.872
970107AG2-081 GEN
Solar/Wind Harmer
2.985
970235AG2-159 GEN
Solar/Wind Harmer
3.878
970235AG2-159 GEN
Solar/Wind Harmer
2.367
270186AC1-089 GEN
Solar/Wind Harmer
5.824
970239AG2-162 GEN
Solar/Wind Harmer
10.472
962581AG1-107 GEN
Solar/Wind Harmer
4.731
961491AF2-440 GEN
Solar/Wind Harmer
1.966
970879AG2-548 GEN
Solar/Wind Harmer
5.656
970241AG2-163 GEN
Solar/Wind Harmer
22.426
274762LEE CO EC;3U
Adder
8.222
274696ROCKY RD ;4P
Adder
9.957
274697ROCKY RD ;3P
Adder
2.642
315821AE2-092 GEN
Solar/Wind Helper
3.216
316468AD1-105 GEN
Solar/Wind Helper
1.124
3147312GRETNA
Solar/Wind Harmer
-0.005
971687AH1-348 GEN
Solar/Wind Harmer
1.359
971315AH1-136 GEN
Solar/Wind Harmer
2.43
270331AC1-082 GEN3
Solar/Wind Harmer
0.487
970333AG2-219 GEN
Solar/Wind Harmer
30.05
25196808ZIMRHP
Adder
70.616
25196008MFTGT1
Adder
1.293
274880W4-005 GEN4
Solar/Wind Harmer
2.726
274761LEE CO EC;2U
Adder
8.222
237061AD1-155 GEN
Solar/Wind Helper
0.05
23583801GRNGAP
Solar/Wind Helper
4.287
238149AF1-291A_GEN
Solar/Wind Helper
0.12
316258AE1-075 C
Solar/Wind Helper
0.319
972175AH1-670 GEN
Solar/Wind Harmer
4.72
24684405SMG2
50/50
2.224
316217AC1-145 GEN
Solar/Wind Harmer
4.247
316197AC1-042 GEN
Solar/Wind Harmer
3.219
942671AE2-283 GEN
Solar/Wind Harmer
8.667
971485AH1-239 GEN
Solar/Wind Harmer
8.497
964781AG1-341 GEN
Solar/Wind Harmer
10.97
971081AG2-670 GEN
Solar/Wind Harmer
7.734
942891AE2-308 GEN
Solar/Wind Harmer
10.176
972043AH1-570 GEN
Solar/Wind Harmer
2.475
25194408D.CRK1
Adder
6.938
945391AF1-204 GEN
Solar/Wind Harmer
12.718
24728905RICHG2
Adder
3.384
972267AH1-718 GEN
Adder
3.688
274764LEE CO EC;5U
Adder
8.241
274683WAUKEGAN ;8U
Adder
18.419
274683WAUKEGAN ;8U
Adder
15.526
274693ROCKY RD ;1P
Adder
9.632
3132123MT JACKSON
Solar/Wind Helper
1.389
966001AG1-469 GEN
Solar/Wind Helper
0.32
24288905REUSENS
50/50
0.057
24684605SMG4
50/50
2.239
24728305BUCHG2
Adder
6.75
270018AE2-047 C O1
Solar/Wind Harmer
1.826
24686505CER G6
Adder
9.874
962241AG1-070 GEN
Solar/Wind Harmer
4.64
3429241JKCT 3G
Adder
12.029
339216AC1-074 GEN
Solar/Wind Harmer
1.649
252507AC2-088 GEN
Solar/Wind Harmer
1.669
24415905BUCK
50/50
0.034
971329AH1-144 GEN
Solar/Wind Harmer
23.686
958131AF2-107 GEN
Solar/Wind Harmer
7.108
971403AH1-188 GEN
Solar/Wind Harmer
18.852
970273AG2-179 GEN
Solar/Wind Harmer
2.581
960001AF2-291 GEN
Solar/Wind Harmer
3.113
3429421JKCT 10G
Adder
8.402
971565AH1-281 GEN
Solar/Wind Harmer
2.001
927014AC1-188 GEN
Solar/Wind Harmer
1.532
970091AG2-072 GEN
Adder
74.012
963741AG1-226 GEN
Solar/Wind Harmer
40.366
274822ROCKFORD ;11
Adder
17.275
3132273ORANGE
Solar/Wind Helper
0.056
316170AC1-121 GEN2
Solar/Wind Helper
0.386
316313AB2-026
Solar/Wind Helper
0.354
276911AD2-131_GEN
Solar/Wind Harmer
3.871
24728805RICHG1
Adder
3.384
274765LEE CO EC;6U
Adder
8.241
274763LEE CO EC;4U
Adder
8.144
274695ROCKY RD ;2P
Adder
9.727
966871AG1-558 GEN
Solar/Wind Helper
0.306
965911AG1-460 GEN
Solar/Wind Harmer
1.271
276615X2-022 GEN
Solar/Wind Harmer
1.772
963831AG1-236 GEN
Solar/Wind Harmer
8.877
274766LEE CO EC;7U
Adder
8.125
972235AH1-702 GEN1
Adder
2.22
315616AA1-038_C
Solar/Wind Helper
3.293
3148013FISHERV
Solar/Wind Helper
0.523
3147666LOUISA
Solar/Wind Helper
0.625
238147AE2-230_GEN1
Solar/Wind Helper
0.421
316405AF2-144 C
Solar/Wind Helper
0.265
316044AC1-158 PL1
Solar/Wind Helper
1.257
316450AC1-158 RIC
Solar/Wind Helper
0.335
970563AG2-360 GEN
50/50
45.829
962751AG1-124 GEN
Solar/Wind Harmer
18.825
3147312GRETNA
Solar/Wind Harmer
-0.021
3146802CHATHAM
Solar/Wind Harmer
-0.02
270016AE1-250 BESS
Solar/Wind Harmer
3.256
972273AH1-721 GEN
Adder
89.316
966571AG1-526 GEN
Solar/Wind Harmer
22.886
970093AG2-073 GEN
Solar/Wind Harmer
10.271
971191AH1-055 GEN
Solar/Wind Harmer
22.182
972167AH1-666 GEN
Solar/Wind Harmer
7.768
970243AG2-164 GEN
Solar/Wind Harmer
24.587
25196008MFTGT1
Adder
1.252
252510AF1-249 C
Solar/Wind Harmer
0.384
942481AE2-261 GEN
Solar/Wind Harmer
27.229
276621W2-048 GEN
Solar/Wind Harmer
5.645
276838X2-022 GEN2
Solar/Wind Harmer
0.211
971993AH1-541 GEN
Solar/Wind Harmer
8.328
274729ELWOOD EC;1P
Adder
13.481
3147983MERCK5
Solar/Wind Helper
0.198
24684705SMG5
50/50
0.856
3151561HALLBR1
50/50
0.57
270173AC1-122 GEN
Solar/Wind Harmer
3.278
941801AE2-185 GEN
Solar/Wind Harmer
9.812
970913AG2-568 GEN
Solar/Wind Harmer
11.004
270053AF1-130 C
Solar/Wind Harmer
4.815
24686405CER G5
Adder
9.796
970273AG2-179 GEN
Solar/Wind Harmer
4.123
339250AF1-203 GEN
Solar/Wind Harmer
0.628
962251AG1-071 GEN
Solar/Wind Harmer
5.671
276686W4-005 GEN3
Solar/Wind Harmer
2.726
270356AE2-297 GEN
Solar/Wind Harmer
4.098
274760LEE CO EC;1U
Adder
8.222
972236AH1-702 GEN2
Adder
1.93
238148AE2-230_GEN2
Solar/Wind Helper
0.423
316006AB2-029 C
Solar/Wind Helper
0.112
316045AC1-158 PL2
Solar/Wind Helper
4.023
966391AG1-508 GEN
Solar/Wind Harmer
6.374
270069AE2-166 C O1
Solar/Wind Harmer
4.507
24734705WLF1G3
Adder
8.194
24734905WLF1G5
Adder
8.194
270399AC1-101 GEN
Solar/Wind Harmer
5.556
972143AH1-644 GEN
Solar/Wind Harmer
12.917
971981AH1-535 GEN
Solar/Wind Harmer
12.563
270330AC1-082 GEN2
Solar/Wind Harmer
0.824
965401AG1-405 GEN
Solar/Wind Harmer
6.059
339211AE2-254 GEN
Solar/Wind Harmer
1.563
972165AH1-665 GEN
Solar/Wind Harmer
7.794
971985AH1-537 GEN
Solar/Wind Harmer
17.295
274823ROCKFORD ;21
Adder
17.15
3148013FISHERV
Solar/Wind Helper
0.3
970281AG2-184 GEN
Solar/Wind Harmer
27.126
962211AG1-066 GEN
Solar/Wind Harmer
3.001
972203AH1-686 GEN
Adder
2.704
970165AG2-112 GEN
Solar/Wind Harmer
1.315
970163AG2-111 GEN
Solar/Wind Harmer
1.254
252524AE2-267 GEN
Solar/Wind Harmer
1.444
276785W4-005 GEN1
Solar/Wind Harmer
2.726
276849AB2-070 GEN2
Solar/Wind Harmer
2.027
276848AB2-070 GEN3
Solar/Wind Harmer
2.027
274744AC1-111 GEN8
Adder
4.87
25306009OHH W.
Adder
2.505
3148463FAIRFLD
Solar/Wind Helper
0.726
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
971543AH1-269 GEN
50/50
12.247
971313AH1-133 GEN
Solar/Wind Harmer
15.698
270132AB1-180 C
Adder
0.169
971061AG2-657 GEN
Solar/Wind Harmer
10.991
965411AG1-406 GEN
Solar/Wind Harmer
2.719
270367AC2-061_GEN
Solar/Wind Harmer
3.009
316123AC1-075 GEN
Solar/Wind Harmer
1.493
25196108MFTGT2
Adder
1.425
25196108MFTGT2
Adder
1.324
970879AG2-548 GEN
Solar/Wind Harmer
3.946
25196408WSDLE3
Adder
8.08
25196308WSDLE2
Adder
8.01
25196208WSDLE1
Adder
7.99
25196708WSDLE6
Adder
7.97
276174W4-005 GEN2
Solar/Wind Harmer
2.726
3148133STUARTS
Solar/Wind Helper
0.313
957141AF2-008_MTX
Adder
54.545
944201AF1-088_MTX
Adder
109.09
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.415
NYPJM->LTFIMP_NY
CLTF
3.248
TVALTFEXP_TVA->PJM
CLTF
10.606
AG2-052LTFEXP_AG2-052->PJM
LTF
0.202
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.111
LGEELTFEXP_LGEE->PJM
CLTF
6.763
MECLTFEXP_MEC->PJM
CLTF
15.415
AH1-155LTFEXP_AH1-155->PJM
LTF
0.303
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.315
WECLTFEXP_WEC->PJM
CLTF
3.371
LAGNLTFEXP_LAGN->PJM
CLTF
20.28
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.555
CPLELTFEXP_CPLE->PJM
CLTF
6.226
SIGELTFEXP_SIGE->PJM
CLTF
0.508

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AEP_P4_#2942_05KAMMER 765_PP_SRT-A


Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2942_05KAMMER 765_PP_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.36 %
Rating:3610.0 MVA
Rating Type:B
MVA to Mitigate:4200.43
MW Contribution:18.86
Bus #Bus NameTypeMW Contribution
270583AD2-179 GEN
Solar/Wind Harmer
20.728
270214AC2-123 GEN
Solar/Wind Harmer
4.312
971225AH1-072 GEN
Solar/Wind Harmer
2.732
970479AG2-310 GEN
50/50
20.26
270205AE1-176
50/50
0.006
966251AG1-494 GEN
50/50
4.39
24728405LEESVG
50/50
0.297
971367AH1-164 GEN
Solar/Wind Harmer
7.005
941821AE2-187 GEN
Solar/Wind Harmer
9.815
270197AD1-017 GEN1
Solar/Wind Harmer
2.547
270336AE1-100 GEN
Solar/Wind Harmer
2.758
943811AF1-049 GEN
Solar/Wind Harmer
5.698
24735205WLF2G2
Adder
8.027
24723205RIVRG3
Adder
22.966
24686105CER G3
Adder
9.893
24721705FLATG2
Adder
21.699
970947AG2-589 GEN
Solar/Wind Harmer
2.14
971821AH1-427 GEN
Solar/Wind Harmer
10.353
964901AG1-354 GEN
Solar/Wind Harmer
15.509
339241AF1-083 GEN
Solar/Wind Harmer
1.716
943111AE2-339 GEN
Solar/Wind Harmer
0.883
945681AF1-233 GEN
Solar/Wind Harmer
18.332
270445AC2-157 GEN2
Solar/Wind Harmer
5.243
25194608D.CRK4
Adder
1.509
253432AC1-085 GEN2
Solar/Wind Harmer
0.243
946171AF1-282 GEN
Solar/Wind Harmer
9.081
24728605AND G2
Adder
3.482
274828WAUKEGAN ;BP
Adder
9.662
274682WAUKEGAN ;7U
Adder
15.715
274745AC1-111 GEN9
Adder
4.873
316499AE2-029_GEN
Solar/Wind Helper
1.724
316095T157 G97
Solar/Wind Helper
1.124
966881AG1-559 GEN
Solar/Wind Helper
0.313
316473AC1-191 GEN
Solar/Wind Helper
1.386
24684305SMG1
50/50
0.806
270013AE1-250 PV
Solar/Wind Harmer
3.257
960161AF2-307 GEN
Solar/Wind Harmer
6.662
339236AF1-050_GEN
Solar/Wind Harmer
1.873
3147312GRETNA
Solar/Wind Harmer
-0.005
971687AH1-348 GEN
Solar/Wind Harmer
1.359
971315AH1-136 GEN
Solar/Wind Harmer
2.431
270331AC1-082 GEN3
Solar/Wind Harmer
0.487
970333AG2-219 GEN
Solar/Wind Harmer
30.071
25196808ZIMRHP
Adder
70.665
25196008MFTGT1
Adder
1.294
274880W4-005 GEN4
Solar/Wind Harmer
2.728
274761LEE CO EC;2U
Adder
8.227
24415905BUCK
50/50
0.034
971329AH1-144 GEN
Solar/Wind Harmer
23.694
958131AF2-107 GEN
Solar/Wind Harmer
7.111
971403AH1-188 GEN
Solar/Wind Harmer
18.861
970273AG2-179 GEN
Solar/Wind Harmer
2.583
960001AF2-291 GEN
Solar/Wind Harmer
3.115
3429421JKCT 10G
Adder
8.407
971565AH1-281 GEN
Solar/Wind Harmer
2.002
927014AC1-188 GEN
Solar/Wind Harmer
1.533
970091AG2-072 GEN
Adder
74.061
963741AG1-226 GEN
Solar/Wind Harmer
40.395
274822ROCKFORD ;11
Adder
17.288
3132273ORANGE
Solar/Wind Helper
0.056
316170AC1-121 GEN2
Solar/Wind Helper
0.386
316313AB2-026
Solar/Wind Helper
0.354
24288905REUSENS
50/50
0.057
24684605SMG4
50/50
2.239
24728305BUCHG2
Adder
6.753
270018AE2-047 C O1
Solar/Wind Harmer
1.826
24686505CER G6
Adder
9.88
962241AG1-070 GEN
Solar/Wind Harmer
4.643
3429241JKCT 3G
Adder
12.037
339216AC1-074 GEN
Solar/Wind Harmer
1.65
252507AC2-088 GEN
Solar/Wind Harmer
1.671
965911AG1-460 GEN
Solar/Wind Harmer
1.272
276615X2-022 GEN
Solar/Wind Harmer
1.774
963831AG1-236 GEN
Solar/Wind Harmer
8.883
274766LEE CO EC;7U
Adder
8.131
972235AH1-702 GEN1
Adder
2.221
315616AA1-038_C
Solar/Wind Helper
3.292
3148013FISHERV
Solar/Wind Helper
0.522
3147666LOUISA
Solar/Wind Helper
0.625
238147AE2-230_GEN1
Solar/Wind Helper
0.421
316405AF2-144 C
Solar/Wind Helper
0.265
316044AC1-158 PL1
Solar/Wind Helper
1.256
316450AC1-158 RIC
Solar/Wind Helper
0.335
970563AG2-360 GEN
50/50
45.847
962751AG1-124 GEN
Solar/Wind Harmer
18.831
3147312GRETNA
Solar/Wind Harmer
-0.021
3146802CHATHAM
Solar/Wind Harmer
-0.02
270016AE1-250 BESS
Solar/Wind Harmer
3.257
972273AH1-721 GEN
Adder
89.369
966571AG1-526 GEN
Solar/Wind Harmer
22.9
24290705CLAY-2
50/50
0.255
24290705CLAY-2
50/50
0.255
24684505SMG3
50/50
1.376
971277AH1-098 GEN
Solar/Wind Harmer
7.423
24728205BUCHG1
Adder
6.753
944971AF1-162 GEN
Solar/Wind Harmer
9.072
942751AE2-291 GEN
Solar/Wind Harmer
10.391
966021AG1-471 GEN
Solar/Wind Harmer
5.756
339231AF1-038_GEN
Solar/Wind Harmer
1.919
339255AE2-071 GEN
Solar/Wind Harmer
1.099
970653AG2-424 GEN
Solar/Wind Harmer
4.883
970653AG2-424 GEN
Solar/Wind Harmer
1.765
964571AG1-320 GEN
Solar/Wind Harmer
8.191
972045AH1-571 GEN
Solar/Wind Harmer
1.981
339221AD2-048_GEN
Solar/Wind Harmer
1.515
252509AD1-136 GEN
Solar/Wind Harmer
0.239
25183208HLCRTG
Solar/Wind Harmer
5.586
25194508D.CRK3
Adder
1.298
971073AG2-665 GEN
Solar/Wind Harmer
5.66
971073AG2-665 GEN
Solar/Wind Harmer
3.949
276911AD2-131_GEN
Solar/Wind Harmer
3.874
24728805RICHG1
Adder
3.386
274765LEE CO EC;6U
Adder
8.247
274763LEE CO EC;4U
Adder
8.15
274695ROCKY RD ;2P
Adder
9.734
966871AG1-558 GEN
Solar/Wind Helper
0.306
24684705SMG5
50/50
0.857
3151561HALLBR1
50/50
0.57
270173AC1-122 GEN
Solar/Wind Harmer
3.279
941801AE2-185 GEN
Solar/Wind Harmer
9.815
970913AG2-568 GEN
Solar/Wind Harmer
11.009
270053AF1-130 C
Solar/Wind Harmer
4.818
24686405CER G5
Adder
9.802
970273AG2-179 GEN
Solar/Wind Harmer
4.125
339250AF1-203 GEN
Solar/Wind Harmer
0.628
962251AG1-071 GEN
Solar/Wind Harmer
5.674
276686W4-005 GEN3
Solar/Wind Harmer
2.728
270356AE2-297 GEN
Solar/Wind Harmer
4.101
274760LEE CO EC;1U
Adder
8.227
972236AH1-702 GEN2
Adder
1.932
238148AE2-230_GEN2
Solar/Wind Helper
0.423
316006AB2-029 C
Solar/Wind Helper
0.112
316045AC1-158 PL2
Solar/Wind Helper
4.02
966391AG1-508 GEN
Solar/Wind Harmer
6.377
270069AE2-166 C O1
Solar/Wind Harmer
4.508
24734705WLF1G3
Adder
8.198
24734905WLF1G5
Adder
8.198
270399AC1-101 GEN
Solar/Wind Harmer
5.558
972143AH1-644 GEN
Solar/Wind Harmer
12.924
971981AH1-535 GEN
Solar/Wind Harmer
12.569
270330AC1-082 GEN2
Solar/Wind Harmer
0.824
965401AG1-405 GEN
Solar/Wind Harmer
6.063
339211AE2-254 GEN
Solar/Wind Harmer
1.564
972165AH1-665 GEN
Solar/Wind Harmer
7.8
971985AH1-537 GEN
Solar/Wind Harmer
17.306
274823ROCKFORD ;21
Adder
17.162
3148013FISHERV
Solar/Wind Helper
0.3
970823AG2-518 GEN
50/50
8.386
247619Y1-049
50/50
0.913
24416005BYLLESBY
50/50
0.031
958121AF2-106 GEN
Solar/Wind Harmer
9.409
971331AH1-145 GEN
Solar/Wind Harmer
18.367
270346AE1-212 GEN
Solar/Wind Harmer
13.941
971461AH1-227 GEN
Solar/Wind Harmer
7.007
970223AG2-152 GEN
Solar/Wind Harmer
17.631
24686205CER G4
Adder
9.841
3429391JKCT 9G
Adder
8.407
957541AF2-048 GEN
Solar/Wind Harmer
1.529
958171AF2-111 GEN
Solar/Wind Harmer
23.926
970519AG2-331 GEN
Solar/Wind Harmer
16.529
970699AG2-449 GEN
Solar/Wind Harmer
10.935
25196608WSDLE5
Adder
7.855
970193AG2-126 GEN
Solar/Wind Harmer
13.698
24728705AND G3
Adder
7.283
253406AD2-031_GEN
Solar/Wind Harmer
1.149
3147666LOUISA
Solar/Wind Helper
1.087
316254AC1-120 GEN1
Solar/Wind Helper
1.158
970481AG2-311 GEN
50/50
11.941
24728405LEESVG
50/50
0.296
943031AE2-326 GEN
Solar/Wind Harmer
6.787
270574AD1-017 GEN2
Solar/Wind Harmer
8.476
3147123OTTER R
Solar/Wind Harmer
-0.014
270030AE2-140 GEN
Solar/Wind Harmer
30.942
960911AF2-382 GEN
Solar/Wind Harmer
10.952
972103AH1-617 GEN
Solar/Wind Harmer
25.847
24721905FLATG4
Adder
21.699
971155AH1-034 GEN
Solar/Wind Harmer
10.36
960741AF2-365 GEN
Solar/Wind Harmer
5.111
25194608D.CRK4
Adder
1.509
253316AC1-085 GEN3
Solar/Wind Harmer
7.607
253433AC1-085 GEN1
Solar/Wind Harmer
4.829
946181AF1-283 GEN
Solar/Wind Harmer
11.806
24728505AND G1
Adder
3.482
276668AB2-070 GEN1
Solar/Wind Harmer
2.029
274767LEE CO EC;8U
Adder
8.131
274682WAUKEGAN ;7U
Adder
15.715
316192AB2-158 GEN
Solar/Wind Helper
1.837
316097T157 G90
Solar/Wind Helper
1.124
316336AC2-165 C
Solar/Wind Helper
1.284
970281AG2-184 GEN
Solar/Wind Harmer
27.14
962211AG1-066 GEN
Solar/Wind Harmer
3.003
972203AH1-686 GEN
Adder
2.706
970165AG2-112 GEN
Solar/Wind Harmer
1.315
970163AG2-111 GEN
Solar/Wind Harmer
1.255
252524AE2-267 GEN
Solar/Wind Harmer
1.445
276849AB2-070 GEN2
Solar/Wind Harmer
2.029
276848AB2-070 GEN3
Solar/Wind Harmer
2.029
276785W4-005 GEN1
Solar/Wind Harmer
2.728
274744AC1-111 GEN8
Adder
4.873
25306009OHH W.
Adder
2.506
3148463FAIRFLD
Solar/Wind Helper
0.726
24734805WLF1G4
Adder
8.198
24735105WLF2G1
Adder
8.027
270400AC1-102 GEN
Solar/Wind Harmer
5.558
941621AE2-160 GEN
Adder
4.287
957241AF2-018 GEN
Solar/Wind Harmer
5.759
24477305BRIDGE
Adder
0.419
270329AC1-082 GEN1
Solar/Wind Harmer
0.486
3429211JKCT 2G
Adder
11.881
970455AG2-298 GEN
Solar/Wind Harmer
6.038
339243AC2-075 GEN1
Solar/Wind Harmer
0.447
972163AH1-664 GEN
Solar/Wind Harmer
9.749
944221AF1-090 GEN
Solar/Wind Harmer
10.031
25196508WSDLE4
Adder
7.774
274746AC1-111 G10
Adder
4.873
23546401DTGZ2-030
Solar/Wind Helper
0.078
316164AC1-076 GEN
Solar/Wind Helper
1.171
238152AF2-075_GEN
Solar/Wind Helper
0.601
24290605CLAY-1
50/50
0.255
24290605CLAY-1
50/50
0.255
24684405SMG2
50/50
2.225
316217AC1-145 GEN
Solar/Wind Harmer
4.248
316197AC1-042 GEN
Solar/Wind Harmer
3.22
942671AE2-283 GEN
Solar/Wind Harmer
8.67
971485AH1-239 GEN
Solar/Wind Harmer
8.502
964781AG1-341 GEN
Solar/Wind Harmer
10.976
971081AG2-670 GEN
Solar/Wind Harmer
7.739
942891AE2-308 GEN
Solar/Wind Harmer
10.182
972043AH1-570 GEN
Solar/Wind Harmer
2.476
25194408D.CRK1
Adder
6.943
945391AF1-204 GEN
Solar/Wind Harmer
12.727
24728905RICHG2
Adder
3.386
972267AH1-718 GEN
Adder
3.691
274764LEE CO EC;5U
Adder
8.247
274683WAUKEGAN ;8U
Adder
18.432
274683WAUKEGAN ;8U
Adder
15.538
274693ROCKY RD ;1P
Adder
9.639
3132123MT JACKSON
Solar/Wind Helper
1.388
966001AG1-469 GEN
Solar/Wind Helper
0.32
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
971227AH1-073 GEN
Solar/Wind Harmer
2.732
24723005RIVRG1
Adder
22.966
24723105RIVRG2
Adder
22.966
24685805CER G1
Adder
9.828
24685905CER G2
Adder
9.828
971125AH1-004 GEN
Solar/Wind Harmer
3.983
270444AC2-157 GEN1
Solar/Wind Harmer
5.243
252519AF1-045_GEN
Solar/Wind Harmer
5.593
252516AE2-318_GEN
Solar/Wind Harmer
4.266
276916AD2-100_GEN
Solar/Wind Harmer
19.168
957381AF2-032 GEN
Solar/Wind Harmer
0.381
253317AC1-085 GEN4
Solar/Wind Harmer
7.607
276763AC1-053 GEN1
Solar/Wind Harmer
3.571
276764AC1-053 GEN2
Solar/Wind Harmer
3.571
315651AD1-115 GEN
Solar/Wind Helper
0.837
316447AC1-158 HLD
Solar/Wind Helper
2.764
971543AH1-269 GEN
50/50
12.251
971313AH1-133 GEN
Solar/Wind Harmer
15.705
270132AB1-180 C
Adder
0.169
971061AG2-657 GEN
Solar/Wind Harmer
10.996
965411AG1-406 GEN
Solar/Wind Harmer
2.721
270367AC2-061_GEN
Solar/Wind Harmer
3.011
316123AC1-075 GEN
Solar/Wind Harmer
1.494
25196108MFTGT2
Adder
1.426
25196108MFTGT2
Adder
1.325
970879AG2-548 GEN
Solar/Wind Harmer
3.949
25196408WSDLE3
Adder
8.086
25196308WSDLE2
Adder
8.015
25196208WSDLE1
Adder
7.995
25196708WSDLE6
Adder
7.975
276174W4-005 GEN2
Solar/Wind Harmer
2.728
3148133STUARTS
Solar/Wind Helper
0.313
970107AG2-081 GEN
Solar/Wind Harmer
2.987
970235AG2-159 GEN
Solar/Wind Harmer
3.88
970235AG2-159 GEN
Solar/Wind Harmer
2.369
270186AC1-089 GEN
Solar/Wind Harmer
5.828
970239AG2-162 GEN
Solar/Wind Harmer
10.479
962581AG1-107 GEN
Solar/Wind Harmer
4.734
961491AF2-440 GEN
Solar/Wind Harmer
1.967
970879AG2-548 GEN
Solar/Wind Harmer
5.66
970241AG2-163 GEN
Solar/Wind Harmer
22.442
274762LEE CO EC;3U
Adder
8.227
274696ROCKY RD ;4P
Adder
9.964
274697ROCKY RD ;3P
Adder
2.644
315821AE2-092 GEN
Solar/Wind Helper
3.215
316468AD1-105 GEN
Solar/Wind Helper
1.124
237061AD1-155 GEN
Solar/Wind Helper
0.05
23583801GRNGAP
Solar/Wind Helper
4.284
238149AF1-291A_GEN
Solar/Wind Helper
0.12
316258AE1-075 C
Solar/Wind Helper
0.318
972175AH1-670 GEN
Solar/Wind Harmer
4.723
970093AG2-073 GEN
Solar/Wind Harmer
10.278
971191AH1-055 GEN
Solar/Wind Harmer
22.196
972167AH1-666 GEN
Solar/Wind Harmer
7.773
970243AG2-164 GEN
Solar/Wind Harmer
24.603
25196008MFTGT1
Adder
1.253
252510AF1-249 C
Solar/Wind Harmer
0.385
942481AE2-261 GEN
Solar/Wind Harmer
27.248
276621W2-048 GEN
Solar/Wind Harmer
5.649
276838X2-022 GEN2
Solar/Wind Harmer
0.211
971993AH1-541 GEN
Solar/Wind Harmer
8.334
274729ELWOOD EC;1P
Adder
13.491
3147983MERCK5
Solar/Wind Helper
0.198
957141AF2-008_MTX
Adder
54.582
944201AF1-088_MTX
Adder
109.164
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.508
NYPJM->LTFIMP_NY
CLTF
3.243
TVALTFEXP_TVA->PJM
CLTF
10.613
AG2-052LTFEXP_AG2-052->PJM
LTF
0.202
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.197
LGEELTFEXP_LGEE->PJM
CLTF
6.767
MECLTFEXP_MEC->PJM
CLTF
15.425
AH1-155LTFEXP_AH1-155->PJM
LTF
0.303
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.339
WECLTFEXP_WEC->PJM
CLTF
3.374
LAGNLTFEXP_LAGN->PJM
CLTF
20.293
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.574
CPLELTFEXP_CPLE->PJM
CLTF
6.233
SIGELTFEXP_SIGE->PJM
CLTF
0.508

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P4_#8075_05MARYSV 765_A2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#8075_05MARYSV 765_A2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:118.92 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6567.82
MW Contribution:23.76
Bus #Bus NameTypeMW Contribution
944971AF1-162 GEN
Solar/Wind Harmer
11.935
24728205BUCHG1
Adder
6.779
971277AH1-098 GEN
Solar/Wind Harmer
5.306
945421AF1-207 GEN
Solar/Wind Harmer
17.235
276911AD2-131_GEN
Solar/Wind Harmer
5.181
274695ROCKY RD ;2P
Adder
13.539
20088926STNY CRK
Solar/Wind Helper
0.8
20088626ARWF_N39
Solar/Wind Helper
1.174
946381AF1-302 GEN
Solar/Wind Helper
0.215
203946AE2-131 C
Solar/Wind Helper
0.459
238217AF1-153 C O1
Solar/Wind Helper
0.229
24721605FLATG1
50/50
2.932
957241AF2-018 GEN
Solar/Wind Harmer
7.577
270400AC1-102 GEN
Solar/Wind Harmer
7.162
24477305BRIDGE
Adder
0.586
270329AC1-082 GEN1
Solar/Wind Harmer
0.751
941621AE2-160 GEN
Adder
5.032
24734805WLF1G4
Adder
8.014
24735105WLF2G1
Adder
7.873
24386205FR-12G C
Solar/Wind Harmer
5.273
963841AG1-237 GEN
Solar/Wind Harmer
13.441
24690905MDL-1G C
Solar/Wind Harmer
9.861
270180AB1-006 GEN1
Solar/Wind Harmer
8.834
946581AF1-322 GEN
Solar/Wind Harmer
12.566
24697905MDL-4G C
Solar/Wind Harmer
2.819
274776LINCOLN ;7U
Adder
7.573
944221AF1-090 GEN
Solar/Wind Harmer
13.349
276655WTG1_EQ
Solar/Wind Harmer
10.651
274746AC1-111 G10
Adder
6.801
274731ELWOOD EC;2P
Adder
19.981
274733ELWOOD EC;3P
Adder
19.981
274687WILL CNTY;4U
Adder
2.145
23750501ELLIOTTS
Solar/Wind Helper
0.675
254304AE2-114 C
Solar/Wind Helper
0.214
241982AE2-343 S C
Solar/Wind Helper
0.219
203961AE2-224 GEN
Solar/Wind Helper
2.335
243186AF1-051 GEN
50/50
13.011
24721805FLATG3
50/50
2.932
24721705FLATG2
50/50
53.759
970155AG2-107 GEN
Solar/Wind Harmer
29.42
24723205RIVRG3
Adder
35.494
24686105CER G3
Adder
15.183
970947AG2-589 GEN
Solar/Wind Harmer
3.299
24735205WLF2G2
Adder
7.873
270445AC2-157 GEN2
Solar/Wind Harmer
7.082
972207SS24-0001
Solar/Wind Harmer
26.925
274745AC1-111 GEN9
Adder
6.801
274682WAUKEGAN ;7U
Adder
21.842
274676JOLIET 29;8U
Adder
37.288
274828WAUKEGAN ;BP
Adder
13.424
238185AF2-356 C
Solar/Wind Helper
2.208
241966AE1-183 GEN
Solar/Wind Helper
0.251
964201AG1-281 GEN
Solar/Wind Helper
0.47
23751101LEADS_P59
Solar/Wind Helper
1.247
203860AG1-193 C
Solar/Wind Helper
0.227
238206AE2-263_GEN
Solar/Wind Helper
0.874
959471AF2-238 GEN
Solar/Wind Helper
0.447
203835AF1-098 GEN
Solar/Wind Helper
1.765
962761AG1-125 GEN
Solar/Wind Harmer
67.471
24686505CER G6
Adder
15.163
24728305BUCHG2
Adder
6.779
970245AG2-165 GEN
Solar/Wind Harmer
22.591
24385905FR-11G C
Solar/Wind Harmer
10.226
963831AG1-236 GEN
Solar/Wind Harmer
12.008
276615X2-022 GEN
Solar/Wind Harmer
2.392
965911AG1-460 GEN
Solar/Wind Harmer
1.703
24686205CER G4
Adder
15.103
971461AH1-227 GEN
Solar/Wind Harmer
7.579
270346AE1-212 GEN
Solar/Wind Harmer
12.382
970519AG2-331 GEN
Solar/Wind Harmer
23.555
970699AG2-449 GEN
Solar/Wind Harmer
15.583
971331AH1-145 GEN
Solar/Wind Harmer
11.867
957541AF2-048 GEN
Solar/Wind Harmer
2.003
970513AG2-328 GEN
Solar/Wind Harmer
22.591
970517AG2-330 GEN
Solar/Wind Harmer
20.49
247619Y1-049
Adder
0.54
970193AG2-126 GEN
Solar/Wind Harmer
18.442
970781AG2-491 GEN
Solar/Wind Harmer
12.28
958121AF2-106 GEN
Solar/Wind Harmer
5.567
274853TWINGROVE;U1
Solar/Wind Harmer
8.794
959611AF2-252 GEN
Solar/Wind Harmer
2.837
972228AH1-698 GEN2
Adder
4.504
274730ELWOOD EC;6P
Adder
19.981
254305AE2-115 C
Solar/Wind Helper
0.214
23750701CROSSCHOOL
Solar/Wind Helper
1.202
202652Y1-033 WT C
Solar/Wind Helper
0.561
20089026BF_G21_K23
Solar/Wind Helper
0.465
238127S14_GEN_2
Solar/Wind Helper
0.681
238202AE2-262_GEN
Solar/Wind Helper
0.919
962771AG1-126 GEN
Solar/Wind Harmer
67.471
972203AH1-686 GEN
Adder
4.314
970281AG2-184 GEN
Solar/Wind Harmer
31.364
962211AG1-066 GEN
Solar/Wind Harmer
3.426
276785W4-005 GEN1
Solar/Wind Harmer
3.693
276849AB2-070 GEN2
Solar/Wind Harmer
2.746
276848AB2-070 GEN3
Solar/Wind Harmer
2.746
959341AF2-225 GEN
Solar/Wind Harmer
18.299
274744AC1-111 GEN8
Adder
6.801
972227AH1-698 GEN1
Adder
3.171
274735ELWOOD EC;4P
Adder
19.981
241997AF1-093 GEN
Solar/Wind Helper
0.251
20091526CHSTN_FL
Solar/Wind Helper
0.565
20090526Q36
Solar/Wind Helper
1.009
203993AD2-133_GEN1
Solar/Wind Helper
1.009
203804AE2-113_GEN
Solar/Wind Helper
1.683
238109AE1-109 GEN2
Solar/Wind Helper
0.085
238110AE1-109 GEN3
Solar/Wind Helper
0.085
24722005FLATG5
50/50
2.932
24721905FLATG4
50/50
53.759
970153AG2-106 GEN
Solar/Wind Harmer
29.42
960911AF2-382 GEN
Solar/Wind Harmer
11.374
972103AH1-617 GEN
Solar/Wind Harmer
29.871
943031AE2-326 GEN
Solar/Wind Harmer
4.895
24755605MDL-5G
Solar/Wind Harmer
2.962
276668AB2-070 GEN1
Solar/Wind Harmer
2.746
274734ELWOOD EC;8P
Adder
19.981
274736ELWOOD EC;9P
Adder
19.981
274682WAUKEGAN ;7U
Adder
21.842
274676JOLIET 29;8U
Adder
35.957
235058AG1-386 C
Solar/Wind Helper
0.457
964991AG1-363 GEN
Solar/Wind Helper
3.697
203818AF1-086 GEN
Solar/Wind Helper
1.639
203830AF1-094 GEN
Solar/Wind Helper
0.445
966841AG1-555 GEN
Solar/Wind Harmer
3.087
945391AF1-204 GEN
Solar/Wind Harmer
17.134
960611AF2-352 GEN
Solar/Wind Harmer
2.837
274693ROCKY RD ;1P
Adder
13.406
274674JOLIET 9 ;6U
Adder
18.717
274683WAUKEGAN ;8U
Adder
25.61
274683WAUKEGAN ;8U
Adder
21.588
23652301WDPWR_K20
Solar/Wind Helper
0.145
23585401KL_K28_T16
Solar/Wind Helper
1.297
241967AE2-285_GEN
Solar/Wind Helper
0.626
203955AF1-039 C O1
Solar/Wind Helper
0.37
20083426SW_E13_K22
Solar/Wind Helper
0.055
946071AF1-272 GEN
Solar/Wind Helper
2.647
20084626FORWARD
Solar/Wind Helper
0.347
20398826ARMNA MT
Solar/Wind Helper
1.433
243186AF1-051 GEN
50/50
13.011
24723005RIVRG1
Adder
35.494
24723105RIVRG2
Adder
35.494
24685805CER G1
Adder
15.083
24685905CER G2
Adder
15.083
971225AH1-072 GEN
Solar/Wind Harmer
2.955
971227AH1-073 GEN
Solar/Wind Harmer
2.955
270214AC2-123 GEN
Solar/Wind Harmer
3.11
270444AC2-157 GEN1
Solar/Wind Harmer
7.082
270583AD2-179 GEN
Solar/Wind Harmer
12.284
276763AC1-053 GEN1
Solar/Wind Harmer
4.827
276764AC1-053 GEN2
Solar/Wind Harmer
4.827
276916AD2-100_GEN
Solar/Wind Harmer
25.634
957381AF2-032 GEN
Solar/Wind Harmer
0.511
241801AE1-079 GEN
Solar/Wind Helper
0.243
238120AE2-309 GEN
Solar/Wind Helper
0.426
20303426NA_O38_P22
Solar/Wind Helper
0.963
203853AF1-134 C O1
Solar/Wind Helper
0.463
203952AE2-129 C
Solar/Wind Helper
0.458
203979AG1-198 GEN
Solar/Wind Helper
0.267
203980AG1-197 GEN
Solar/Wind Helper
0.333
970239AG2-162 GEN
Solar/Wind Harmer
14.933
970321AG2-212 GEN
Solar/Wind Harmer
22.591
970241AG2-163 GEN
Solar/Wind Harmer
30.74
957841AF2-078 GEN
Solar/Wind Harmer
7.417
960161AF2-307 GEN
Solar/Wind Harmer
7.874
274770LINCOLN ;1U
Adder
7.573
274771LINCOLN ;2U
Adder
7.573
972259AH1-714 GEN
Adder
23.231
274696ROCKY RD ;4P
Adder
13.859
274697ROCKY RD ;3P
Adder
3.678
962101AG1-054 GEN
Solar/Wind Helper
0.64
241985AE1-237 GEN
Solar/Wind Helper
0.244
944781AF1-143 GEN
Solar/Wind Helper
2.439
203940AF1-140 C
Solar/Wind Helper
0.385
24318705GVG2
50/50
12.111
270331AC1-082 GEN3
Solar/Wind Harmer
0.753
971315AH1-136 GEN
Solar/Wind Harmer
2.975
971687AH1-348 GEN
Solar/Wind Harmer
1.478
970333AG2-219 GEN
Solar/Wind Harmer
42.852
24387305FR-4G C
Solar/Wind Harmer
6.252
274773LINCOLN ;4U
Adder
7.573
274774LINCOLN ;5U
Adder
7.573
274880W4-005 GEN4
Solar/Wind Harmer
3.693
972175AH1-670 GEN
Solar/Wind Harmer
16.675
940581AE2-045 GEN
Solar/Wind Harmer
12.446
971605AH1-302 GEN
Solar/Wind Harmer
10.643
237046AF1-021 C
Solar/Wind Helper
0.497
254303AC2-168 GEN
Solar/Wind Helper
0.155
23751201ROTHROCK
Solar/Wind Helper
0.744
20089226LOOKOUT
Solar/Wind Helper
0.572
961971AG1-040 GEN
Solar/Wind Helper
0.444
939741AE1-205 GEN
Solar/Wind Harmer
20.221
24289405MTG1
50/50
11.755
24686405CER G5
Adder
15.043
270053AF1-130 C
Solar/Wind Harmer
6.338
970913AG2-568 GEN
Solar/Wind Harmer
12.572
276686W4-005 GEN3
Solar/Wind Harmer
3.693
965091AG1-374 GEN
Solar/Wind Harmer
36.602
238118U2-030_1
Solar/Wind Helper
0.289
20089126CSLMN_L13
Solar/Wind Helper
0.588
959441AF2-235 GEN
Solar/Wind Helper
0.228
24289405MTG1
50/50
11.755
970149AG2-104 GEN
Solar/Wind Harmer
83.326
971403AH1-188 GEN
Solar/Wind Harmer
23.764
960001AF2-291 GEN
Solar/Wind Harmer
4.831
970091AG2-072 GEN
Adder
103.022
971329AH1-144 GEN
Solar/Wind Harmer
15.308
927014AC1-188 GEN
Solar/Wind Harmer
2.008
963741AG1-226 GEN
Solar/Wind Harmer
55.333
24791305MDL-5G
Solar/Wind Harmer
2.962
274854TWINGROVE;U2
Solar/Wind Harmer
8.609
276726Z2-087_GEN
Solar/Wind Harmer
9.649
235054AD2-180 GEN
Solar/Wind Helper
1.717
23562501BACKB
Solar/Wind Helper
0.906
235531U2-073 GEN
Solar/Wind Helper
2.719
20094526CT_V3-030
Solar/Wind Helper
0.459
203954AE2-126 C
Solar/Wind Helper
0.454
238108AE1-109 GEN1
Solar/Wind Helper
0.085
24318705GVG2
50/50
12.111
971191AH1-055 GEN
Solar/Wind Harmer
32.25
970243AG2-164 GEN
Solar/Wind Harmer
35.061
274772LINCOLN ;3U
Adder
7.573
971993AH1-541 GEN
Solar/Wind Harmer
11.28
276621W2-048 GEN
Solar/Wind Harmer
7.618
276838X2-022 GEN2
Solar/Wind Harmer
0.284
942481AE2-261 GEN
Solar/Wind Harmer
36.492
942111AE2-223 GEN
Solar/Wind Harmer
10.001
972273AH1-721 GEN
Adder
101.345
274729ELWOOD EC;1P
Adder
19.981
237048AF1-022 C
Solar/Wind Helper
0.196
237043AE2-125 C
Solar/Wind Helper
0.18
274674JOLIET 9 ;6U
Adder
18.717
274732ELWOOD EC;7P
Adder
19.981
238117U2-030
Solar/Wind Helper
0.289
20088826HIGHLAND
Solar/Wind Helper
0.874
964391AG1-301 GEN
Solar/Wind Helper
0.454
270399AC1-101 GEN
Solar/Wind Harmer
7.162
270330AC1-082 GEN2
Solar/Wind Harmer
1.275
972143AH1-644 GEN
Solar/Wind Harmer
14.935
24734705WLF1G3
Adder
8.014
24734905WLF1G5
Adder
8.014
966391AG1-508 GEN
Solar/Wind Harmer
4.623
971985AH1-537 GEN
Solar/Wind Harmer
23.443
971313AH1-133 GEN
Solar/Wind Harmer
14.825
270132AB1-180 C
Adder
0.172
971061AG2-657 GEN
Solar/Wind Harmer
12.379
24386605FR-22G C
Solar/Wind Harmer
5.292
24387005FR-3G C
Solar/Wind Harmer
4.867
24691005MDL-2G C
Solar/Wind Harmer
4.542
276174W4-005 GEN2
Solar/Wind Harmer
3.693
274728ELWOOD EC;5P
Adder
19.981
238126S14_GEN_1
Solar/Wind Helper
0.681
941231AE2-117 GEN
Solar/Wind Helper
0.455
203854AF2-039 C
Solar/Wind Helper
0.307
20334926Z1-069 C
Solar/Wind Helper
1.299
962511AG1-100 GEN
Solar/Wind Helper
0.442
971981AH1-535 GEN
Solar/Wind Harmer
12.541
24386405FR-21G C
Solar/Wind Harmer
5.292
24697605MDL-3G C
Solar/Wind Harmer
4.528
270181AB1-006 GEN2
Solar/Wind Harmer
0.878
274775LINCOLN ;6U
Adder
7.573
274777LINCOLN ;8U
Adder
7.573
276656WTG2_EQ
Solar/Wind Harmer
1.41
274675JOLIET 29;7U
Adder
37.288
274675JOLIET 29;7U
Adder
35.957
20092526R32
Solar/Wind Helper
1.133
203846AF2-130 C
Solar/Wind Helper
0.44
203855AF2-088 C
Solar/Wind Helper
0.148
941731AE2-173 GEN
Solar/Wind Harmer
5.878
957141AF2-008_MTX
Adder
73.729
944201AF1-088_MTX
Adder
147.459
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.72
WECLTFEXP_WEC->PJM
CLTF
4.643
LAGNLTFEXP_LAGN->PJM
CLTF
23.289
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.656
CPLELTFEXP_CPLE->PJM
CLTF
6.999
SIGELTFEXP_SIGE->PJM
CLTF
0.642
CBM West 1LTFEXP_CBM-W1->PJM
CBM
150.395
NYPJM->LTFIMP_NY
CLTF
5.324
TVALTFEXP_TVA->PJM
CLTF
11.825
AG2-052LTFEXP_AG2-052->PJM
LTF
0.281
CBM West 2LTFEXP_CBM-W2->PJM
CBM
159.017
LGEELTFEXP_LGEE->PJM
CLTF
8.439
MECLTFEXP_MEC->PJM
CLTF
20.29
AH1-155LTFEXP_AH1-155->PJM
LTF
0.422

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P4_#8980_05KAMMER 765_QQ2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#8980_05KAMMER 765_QQ2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.66 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6443.11
MW Contribution:24.06
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
2.756
270329AC1-082 GEN1
Solar/Wind Harmer
0.802
957241AF2-018 GEN
Solar/Wind Harmer
7.728
270400AC1-102 GEN
Solar/Wind Harmer
7.31
24477305BRIDGE
Adder
0.588
941621AE2-160 GEN
Adder
5.057
972163AH1-664 GEN
Solar/Wind Harmer
14.604
339243AC2-075 GEN1
Solar/Wind Harmer
0.653
3429211JKCT 2G
Adder
16.676
25196508WSDLE4
Adder
12.095
24734805WLF1G4
Adder
8.198
270340AC2-060 GEN
Solar/Wind Harmer
4.288
24735105WLF2G1
Adder
8.08
970455AG2-298 GEN
Solar/Wind Harmer
8.379
270269AC2-059
Solar/Wind Harmer
12.868
24699105WLD G1 C
Solar/Wind Harmer
5.339
253400AC2-068 GEN
Solar/Wind Harmer
2.717
963841AG1-237 GEN
Solar/Wind Harmer
14.783
274776LINCOLN ;7U
Adder
11.055
274746AC1-111 G10
Adder
7.316
274731ELWOOD EC;2P
Adder
21.509
24686205CER G4
Adder
15.547
957541AF2-048 GEN
Solar/Wind Harmer
2.488
971461AH1-227 GEN
Solar/Wind Harmer
7.832
970519AG2-331 GEN
Solar/Wind Harmer
25.727
970699AG2-449 GEN
Solar/Wind Harmer
17.019
958171AF2-111 GEN
Solar/Wind Harmer
36.017
25196608WSDLE5
Adder
12.22
3429391JKCT 9G
Adder
11.865
253406AD2-031_GEN
Solar/Wind Harmer
1.808
270291AC1-194 GEN
Solar/Wind Harmer
14.929
253415AE1-040 GEN
Solar/Wind Harmer
1.582
270273AD2-016 GEN
Solar/Wind Harmer
3.68
24728705AND G3
Adder
11.022
970193AG2-126 GEN
Solar/Wind Harmer
20.501
270437AC2-090 C
Solar/Wind Harmer
7.623
270346AE1-212 GEN
Solar/Wind Harmer
12.267
958821AF2-173 GEN
Solar/Wind Harmer
18.947
23750701CROSSCHOOL
Solar/Wind Helper
1.427
202652Y1-033 WT C
Solar/Wind Helper
0.655
20089026BF_G21_K23
Solar/Wind Helper
0.541
238127S14_GEN_2
Solar/Wind Helper
0.81
254305AE2-115 C
Solar/Wind Helper
0.239
238202AE2-262_GEN
Solar/Wind Helper
1.063
24722005FLATG5
50/50
2.756
24721905FLATG4
50/50
50.519
970153AG2-106 GEN
Solar/Wind Harmer
23.885
972103AH1-617 GEN
Solar/Wind Harmer
31.296
960911AF2-382 GEN
Solar/Wind Harmer
11.517
25194608D.CRK4
Adder
2.348
253316AC1-085 GEN3
Solar/Wind Harmer
11.89
253433AC1-085 GEN1
Solar/Wind Harmer
7.548
946181AF1-283 GEN
Solar/Wind Harmer
18.454
24728505AND G1
Adder
5.27
253303V4-073 C
Solar/Wind Harmer
0.158
253370AE2-315 SEC1
Adder
2.733
253371AE2-315 SEC2
Adder
2.585
960741AF2-365 GEN
Solar/Wind Harmer
6.78
247642Z2-115 C
Solar/Wind Harmer
0.087
970289AG2-191 GEN
Solar/Wind Harmer
1.039
970291AG2-192 GEN
Solar/Wind Harmer
0.944
243186AF1-051 GEN
50/50
12.478
24723005RIVRG1
Adder
36.021
24723105RIVRG2
Adder
36.021
24685805CER G1
Adder
15.526
24685905CER G2
Adder
15.526
971225AH1-072 GEN
Solar/Wind Harmer
3.053
971227AH1-073 GEN
Solar/Wind Harmer
3.053
252519AF1-045_GEN
Solar/Wind Harmer
8.714
252516AE2-318_GEN
Solar/Wind Harmer
6.647
971125AH1-004 GEN
Solar/Wind Harmer
5.722
253317AC1-085 GEN4
Solar/Wind Harmer
11.89
270444AC2-157 GEN1
Solar/Wind Harmer
7.855
253370AE2-315 SEC1
Adder
2.733
25322209TAIT E
Adder
13.187
25322209TAIT E
Adder
12.891
247621Y3-024
Adder
0.32
238120AE2-309 GEN
Solar/Wind Helper
0.507
241801AE1-079 GEN
Solar/Wind Helper
0.271
20303426NA_O38_P22
Solar/Wind Helper
1.117
203853AF1-134 C O1
Solar/Wind Helper
0.534
203952AE2-129 C
Solar/Wind Helper
0.529
209054AE2-059 GEN
Solar/Wind Helper
0.09
203979AG1-198 GEN
Solar/Wind Helper
0.297
203980AG1-197 GEN
Solar/Wind Helper
0.369
964851AG1-348 GEN
Solar/Wind Helper
0.088
217204WCALDSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.003
218440SUMMTASSOC C
Solar/Wind Helper
0.018
20714928UPF_X1-085
Solar/Wind Helper
0.005
230407AD2-065 C
Solar/Wind Helper
0.042
237025AB1-124 C
Solar/Wind Helper
0.145
23777801MSM_W1-116
Solar/Wind Helper
0.1
238169AE2-226 GEN1
Solar/Wind Helper
0.555
238170AE2-226 GEN2
Solar/Wind Helper
0.555
243186AF1-051 GEN
50/50
12.478
24721805FLATG3
50/50
2.756
24721705FLATG2
50/50
50.519
24723205RIVRG3
Adder
36.021
24686105CER G3
Adder
15.629
970947AG2-589 GEN
Solar/Wind Harmer
3.539
970155AG2-107 GEN
Solar/Wind Harmer
23.885
945681AF1-233 GEN
Solar/Wind Harmer
27.516
943111AE2-339 GEN
Solar/Wind Harmer
1.263
25194608D.CRK4
Adder
2.348
253432AC1-085 GEN2
Solar/Wind Harmer
0.38
946171AF1-282 GEN
Solar/Wind Harmer
14.195
270445AC2-157 GEN2
Solar/Wind Harmer
7.855
971821AH1-427 GEN
Solar/Wind Harmer
14.027
24735205WLF2G2
Adder
8.08
24728605AND G2
Adder
5.27
339241AF1-083 GEN
Solar/Wind Harmer
2.279
253370AE2-315 SEC1
Adder
2.733
253371AE2-315 SEC2
Adder
2.585
970291AG2-192 GEN
Solar/Wind Harmer
1.76
965031AG1-367 GEN
Solar/Wind Harmer
13.534
964901AG1-354 GEN
Solar/Wind Harmer
20.265
960071AF2-298 GEN
Solar/Wind Harmer
6.737
274745AC1-111 GEN9
Adder
7.316
238185AF2-356 C
Solar/Wind Helper
2.612
241966AE1-183 GEN
Solar/Wind Helper
0.28
23751101LEADS_P59
Solar/Wind Helper
1.483
964201AG1-281 GEN
Solar/Wind Helper
0.544
238206AE2-263_GEN
Solar/Wind Helper
1.011
959471AF2-238 GEN
Solar/Wind Helper
0.517
203860AG1-193 C
Solar/Wind Helper
0.254
209067AE2-060 GEN
Solar/Wind Helper
0.091
963071AG1-156 GEN
Solar/Wind Helper
1.625
316095T157 G97
Solar/Wind Helper
1.154
203835AF1-098 GEN
Solar/Wind Helper
1.958
20674628WNG_W3-110
Solar/Wind Helper
0.097
219919AE1-041 FULL
Solar/Wind Helper
0.004
218438BLK ROCK C
Solar/Wind Helper
0.029
20714528FRN_Y2-051
Solar/Wind Helper
0.061
20720828JCB_W4-025
Solar/Wind Helper
0.067
219906AC1-017 C
Solar/Wind Helper
0.044
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219291REEVESSOUT C
Solar/Wind Helper
0.012
219912AD2-042 GEN
Solar/Wind Helper
0.158
219766PARADISE C
Solar/Wind Helper
0.057
230415AB2-049 C
Solar/Wind Helper
0.032
230430AE1-229_GEN
Solar/Wind Helper
3.539
233996TM1833_GEN
Solar/Wind Helper
0.27
232406W1-004 FULL
Solar/Wind Helper
0.523
237030AB1-096 C
Solar/Wind Helper
0.063
970239AG2-162 GEN
Solar/Wind Harmer
16.31
270186AC1-089 GEN
Solar/Wind Harmer
9.06
962581AG1-107 GEN
Solar/Wind Harmer
7.424
961491AF2-440 GEN
Solar/Wind Harmer
3.085
960161AF2-307 GEN
Solar/Wind Harmer
9.441
970879AG2-548 GEN
Solar/Wind Harmer
9.023
970235AG2-159 GEN
Solar/Wind Harmer
5.741
970235AG2-159 GEN
Solar/Wind Harmer
3.504
970107AG2-081 GEN
Solar/Wind Harmer
4.291
253394AE2-221_GEN
Solar/Wind Harmer
6.369
253398AE2-221_GEN2
Solar/Wind Harmer
6.369
270209AC1-174_GEN
Solar/Wind Harmer
7.62
339236AF1-050_GEN
Solar/Wind Harmer
2.463
970241AG2-163 GEN
Solar/Wind Harmer
33.893
274770LINCOLN ;1U
Adder
11.055
274771LINCOLN ;2U
Adder
11.055
972259AH1-714 GEN
Adder
24.976
274696ROCKY RD ;4P
Adder
14.914
274762LEE CO EC;3U
Adder
12.175
274697ROCKY RD ;3P
Adder
3.958
944781AF1-143 GEN
Solar/Wind Helper
2.836
962101AG1-054 GEN
Solar/Wind Helper
0.715
241985AE1-237 GEN
Solar/Wind Helper
0.271
203940AF1-140 C
Solar/Wind Helper
0.446
961431AF2-434 GEN
Solar/Wind Helper
0.499
207471AF2-354 C
Solar/Wind Helper
0.184
20676228FRD_X1-012
Solar/Wind Helper
0.1
217081WEATEXAS C
Solar/Wind Helper
0.014
20676128MHD_W3-029
Solar/Wind Helper
0.103
20673828FLE_V3-070
Solar/Wind Helper
0.097
20716928W4-060COL
Solar/Wind Helper
0.055
963391AG1-188 GEN
Solar/Wind Helper
0.088
963401AG1-189 GEN
Solar/Wind Helper
0.06
20390526W1-045 C
Solar/Wind Helper
0.357
233939AC1-091 C
Solar/Wind Helper
0.361
232408W1-005 C
Solar/Wind Helper
0.523
232410W1-006 C
Solar/Wind Helper
0.523
233946AB2-136 GEN
Solar/Wind Helper
0.586
233944AB2-135 GEN
Solar/Wind Helper
0.607
233933AB2-153 GEN
Solar/Wind Helper
0.24
205916AD1-020 GEN
Solar/Wind Helper
1.711
235020AA1-095 C
Solar/Wind Helper
0.045
238175AF1-290_GEN
Solar/Wind Helper
0.123
970825AG2-519 GEN
Solar/Wind Harmer
8.467
24318705GVG2
50/50
11.615
270331AC1-082 GEN3
Solar/Wind Harmer
0.804
971315AH1-136 GEN
Solar/Wind Harmer
3.199
971687AH1-348 GEN
Solar/Wind Harmer
1.529
970333AG2-219 GEN
Solar/Wind Harmer
46.803
25196808ZIMRHP
Adder
109.116
25196008MFTGT1
Adder
1.989
942081AE2-220 GEN
Solar/Wind Harmer
8.729
270239V3-007_GEN1
Solar/Wind Harmer
2.35
270005AE1-210 C O1
Solar/Wind Harmer
7.396
270032AE2-172
Solar/Wind Harmer
6.293
274773LINCOLN ;4U
Adder
11.055
274774LINCOLN ;5U
Adder
11.055
274761LEE CO EC;2U
Adder
12.175
237046AF1-021 C
Solar/Wind Helper
0.577
23751201ROTHROCK
Solar/Wind Helper
0.878
20089226LOOKOUT
Solar/Wind Helper
0.665
254303AC2-168 GEN
Solar/Wind Helper
0.173
946691AF1-333 GEN
Solar/Wind Helper
0.5
946741AF1-338 GEN
Solar/Wind Helper
0.5
961421AF2-433 GEN
Solar/Wind Helper
0.499
209027LOR2_Q27
Solar/Wind Helper
1.165
23583801GRNGAP
Solar/Wind Helper
4.282
961971AG1-040 GEN
Solar/Wind Helper
0.492
207510AF2-138 C
Solar/Wind Helper
0.088
20673728F2S_V4-070
Solar/Wind Helper
0.032
219908AB1-139 C
Solar/Wind Helper
0.079
219612MATRIX C
Solar/Wind Helper
0.025
20716028EGP_W2-019
Solar/Wind Helper
0.02
219623KINSLEYBEA C
Solar/Wind Helper
0.002
233952AC2-187 GEN
Solar/Wind Helper
0.24
233940AF2-379 C
Solar/Wind Helper
0.064
233982AB2-133 GEN
Solar/Wind Helper
0.369
238221AF1-254 C O1
Solar/Wind Helper
0.236
223402AF1-300 C
Solar/Wind Helper
0.338
970825AG2-519 GEN
Solar/Wind Harmer
1.889
972043AH1-570 GEN
Solar/Wind Harmer
3.602
25194408D.CRK1
Adder
10.799
942891AE2-308 GEN
Solar/Wind Harmer
14.268
24728905RICHG2
Adder
5.204
971081AG2-670 GEN
Solar/Wind Harmer
10.253
945391AF1-204 GEN
Solar/Wind Harmer
19.047
926881AC1-175 GEN
Solar/Wind Harmer
7.62
972267AH1-718 GEN
Adder
5.45
274693ROCKY RD ;1P
Adder
14.427
274764LEE CO EC;5U
Adder
12.204
23652301WDPWR_K20
Solar/Wind Helper
0.168
23585401KL_K28_T16
Solar/Wind Helper
1.53
203955AF1-039 C O1
Solar/Wind Helper
0.432
20083426SW_E13_K22
Solar/Wind Helper
0.064
241967AE2-285_GEN
Solar/Wind Helper
0.696
946071AF1-272 GEN
Solar/Wind Helper
3.051
20084626FORWARD
Solar/Wind Helper
0.402
20398826ARMNA MT
Solar/Wind Helper
1.656
209137AF2-361 C
Solar/Wind Helper
1.531
208972BECR K09
Solar/Wind Helper
0.372
966111AG1-480 GEN
Solar/Wind Helper
0.049
20674928WA_W3-044
Solar/Wind Helper
0.107
219615MILLCREEK C
Solar/Wind Helper
0.028
219921AF1-264
Solar/Wind Helper
0.054
203947AF1-006 C
Solar/Wind Helper
0.527
230433AD2-135 GEN
Solar/Wind Helper
0.018
233970AC1-092 C
Solar/Wind Helper
0.361
232424Y1-079 C
Solar/Wind Helper
0.12
237002AB1-128_GEN
Solar/Wind Helper
0.388
23777901MDS_W4-102
Solar/Wind Helper
0.15
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
237006AB1-125 GEN
Solar/Wind Helper
0.109
24289405MTG1
50/50
11.351
960001AF2-291 GEN
Solar/Wind Harmer
5.242
971403AH1-188 GEN
Solar/Wind Harmer
24.059
970149AG2-104 GEN
Solar/Wind Harmer
67.649
927014AC1-188 GEN
Solar/Wind Harmer
2.494
970091AG2-072 GEN
Adder
113.581
3429421JKCT 10G
Adder
11.865
270263AC1-001 GEN
Solar/Wind Harmer
1.475
971565AH1-281 GEN
Solar/Wind Harmer
2.807
970273AG2-179 GEN
Solar/Wind Harmer
3.322
963741AG1-226 GEN
Solar/Wind Harmer
61.007
235054AD2-180 GEN
Solar/Wind Helper
2.032
23562501BACKB
Solar/Wind Helper
1.07
235531U2-073 GEN
Solar/Wind Helper
3.23
20094526CT_V3-030
Solar/Wind Helper
0.53
238108AE1-109 GEN1
Solar/Wind Helper
0.102
203954AE2-126 C
Solar/Wind Helper
0.522
957921AF2-086 GEN
Solar/Wind Helper
0.493
217211CAMDEN ST C
Solar/Wind Helper
0.005
219249CENTRALDIV C
Solar/Wind Helper
0.011
20715028HAN_X4-015
Solar/Wind Helper
0.061
959561AF2-247 GEN
Solar/Wind Helper
0.022
219348LDSOLAR C
Solar/Wind Helper
0.121
228729W2-030 C
Solar/Wind Helper
0.116
233971AC1-093 C
Solar/Wind Helper
0.369
233997TMININ_4.2
Solar/Wind Helper
0.27
233994AC2-023 GEN
Solar/Wind Helper
0.992
233918AB1-142 GEN
Solar/Wind Helper
0.518
205917AD1-020 ES
Solar/Wind Helper
0.368
944971AF1-162 GEN
Solar/Wind Harmer
12.174
24728205BUCHG1
Adder
6.831
971073AG2-665 GEN
Solar/Wind Harmer
9.023
971073AG2-665 GEN
Solar/Wind Harmer
6.295
252509AD1-136 GEN
Solar/Wind Harmer
0.372
339221AD2-048_GEN
Solar/Wind Harmer
2.218
972045AH1-571 GEN
Solar/Wind Harmer
2.882
25183208HLCRTG
Solar/Wind Harmer
8.709
25194508D.CRK3
Adder
2.019
964571AG1-320 GEN
Solar/Wind Harmer
11.394
970653AG2-424 GEN
Solar/Wind Harmer
6.671
970653AG2-424 GEN
Solar/Wind Harmer
2.412
24728805RICHG1
Adder
5.204
24379505HDWTR1G C
Solar/Wind Harmer
10.797
339231AF1-038_GEN
Solar/Wind Harmer
2.469
270383AD1-128 GEN
Solar/Wind Harmer
8.302
25326109MON D
Adder
1.763
274695ROCKY RD ;2P
Adder
14.57
274765LEE CO EC;6U
Adder
12.204
274763LEE CO EC;4U
Adder
12.06
20088926STNY CRK
Solar/Wind Helper
0.928
20088626ARWF_N39
Solar/Wind Helper
1.362
24686505CER G6
Adder
15.608
962761AG1-125 GEN
Solar/Wind Harmer
54.777
24728305BUCHG2
Adder
6.831
252507AC2-088 GEN
Solar/Wind Harmer
2.603
339216AC1-074 GEN
Solar/Wind Harmer
2.413
3429241JKCT 3G
Adder
16.894
276903AD2-071 C
Solar/Wind Harmer
13.573
25326309TAIT D
Adder
1.481
274766LEE CO EC;7U
Adder
12.032
238117U2-030
Solar/Wind Helper
0.343
20088826HIGHLAND
Solar/Wind Helper
1.011
964391AG1-301 GEN
Solar/Wind Helper
0.529
961331AF2-424 GEN
Solar/Wind Helper
0.499
963161AG1-165 GEN
Solar/Wind Helper
0.496
20676728BRNX1-095
Solar/Wind Helper
0.032
217169METRODIV C
Solar/Wind Helper
0.004
20720528MAN_W1-024
Solar/Wind Helper
0.03
219276PARKLANDSO C
Solar/Wind Helper
0.095
234015AF2-250 C
Solar/Wind Helper
0.039
235067AD1-061 GEN
Solar/Wind Helper
0.433
24318705GVG2
50/50
11.615
971191AH1-055 GEN
Solar/Wind Harmer
36.863
970243AG2-164 GEN
Solar/Wind Harmer
38.293
972167AH1-666 GEN
Solar/Wind Harmer
11.674
252510AF1-249 C
Solar/Wind Harmer
0.598
25196008MFTGT1
Adder
1.926
970093AG2-073 GEN
Solar/Wind Harmer
14.232
966571AG1-526 GEN
Solar/Wind Harmer
31.338
972273AH1-721 GEN
Adder
114.731
274772LINCOLN ;3U
Adder
11.055
274729ELWOOD EC;1P
Adder
21.509
237048AF1-022 C
Solar/Wind Helper
0.228
237043AE2-125 C
Solar/Wind Helper
0.207
946731AF1-337 GEN
Solar/Wind Helper
0.5
20671928W4-073
Solar/Wind Helper
0.098
207437AD2-070 GEN
Solar/Wind Helper
0.15
20675828AU_W4-064
Solar/Wind Helper
0.032
207528AF2-192 GEN
Solar/Wind Helper
0.082
20673628F1S_V4-069
Solar/Wind Helper
0.032
217213AMBOY SO C
Solar/Wind Helper
0.031
218428ETC SOLAR C
Solar/Wind Helper
0.005
219907AC1-030 C
Solar/Wind Helper
0.036
219258KINSLEYDEP C
Solar/Wind Helper
0.081
230434AG1-499 GEN
Solar/Wind Helper
0.241
230511AF1-262
Solar/Wind Helper
0.015
233954AC2-188 GEN
Solar/Wind Helper
0.24
233930AB2-032 GEN
Solar/Wind Helper
0.392
946381AF1-302 GEN
Solar/Wind Helper
0.246
203946AE2-131 C
Solar/Wind Helper
0.53
238217AF1-153 C O1
Solar/Wind Helper
0.262
946751AF1-339 GEN
Solar/Wind Helper
0.5
209029WAYMART-WD
Solar/Wind Helper
0.937
211065PSPA IPP
Solar/Wind Helper
0.168
211065PSPA IPP
Solar/Wind Helper
0.168
20674128FR_U2-059
Solar/Wind Helper
0.004
20671828STAW2-080
Solar/Wind Helper
0.029
207442AE1-156 GEN
Solar/Wind Helper
0.351
20720628TIN_W1-124
Solar/Wind Helper
0.203
233901CHERRYDALE C
Solar/Wind Helper
0.24
234036AF2-325 C
Solar/Wind Helper
0.043
233987AB2-037 GEN
Solar/Wind Helper
2.415
235063AE1-101 C2
Solar/Wind Helper
1.463
237001AB1-127_GEN
Solar/Wind Helper
0.388
237034AC2-136 C
Solar/Wind Helper
0.194
24289405MTG1
50/50
11.351
24686405CER G5
Adder
15.485
270053AF1-130 C
Solar/Wind Harmer
6.465
970913AG2-568 GEN
Solar/Wind Harmer
12.569
972173AH1-669 GEN
Solar/Wind Harmer
6.941
270222AC2-111 GEN
Solar/Wind Harmer
11.283
270356AE2-297 GEN
Solar/Wind Harmer
6.29
970273AG2-179 GEN
Solar/Wind Harmer
5.305
270004AE1-209 GEN
Solar/Wind Harmer
7.396
274760LEE CO EC;1U
Adder
12.175
238118U2-030_1
Solar/Wind Helper
0.343
20089126CSLMN_L13
Solar/Wind Helper
0.683
203854AF2-039 C
Solar/Wind Helper
0.354
20334926Z1-069 C
Solar/Wind Helper
1.49
959441AF2-235 GEN
Solar/Wind Helper
0.255
212507AE2-042_GEN
Solar/Wind Helper
1.772
961341AF2-425 GEN
Solar/Wind Helper
0.499
961301AF2-421 GEN
Solar/Wind Helper
0.496
963151AG1-164 GEN
Solar/Wind Helper
0.496
207439AE1-081 C O1
Solar/Wind Helper
0.02
20674328GAR_V4-001
Solar/Wind Helper
0.024
217209CENTRL HS C
Solar/Wind Helper
0.009
20676428JCR_X2-075
Solar/Wind Helper
0.073
962511AG1-100 GEN
Solar/Wind Helper
0.488
207445AB1-138_GEN
Solar/Wind Helper
0.111
219304NAMERICA C
Solar/Wind Helper
0.139
219686LUMSOLAR_N C
Solar/Wind Helper
0.042
237038AE2-054 C
Solar/Wind Helper
0.238
23779801AA1-109
Solar/Wind Helper
0.168
270330AC1-082 GEN2
Solar/Wind Harmer
1.362
270399AC1-101 GEN
Solar/Wind Harmer
7.31
972143AH1-644 GEN
Solar/Wind Harmer
15.648
971985AH1-537 GEN
Solar/Wind Harmer
27.909
972165AH1-665 GEN
Solar/Wind Harmer
11.684
24734705WLF1G3
Adder
8.198
24734905WLF1G5
Adder
8.198
339211AE2-254 GEN
Solar/Wind Harmer
2.129
965401AG1-405 GEN
Solar/Wind Harmer
7.914
944031AF1-071 GEN
Solar/Wind Harmer
1.391
24725505WLD G2 C
Solar/Wind Harmer
5.403
253349AC2-067 GEN
Solar/Wind Harmer
6.756
274775LINCOLN ;6U
Adder
11.055
274777LINCOLN ;8U
Adder
11.055
20092526R32
Solar/Wind Helper
1.311
203846AF2-130 C
Solar/Wind Helper
0.497
203855AF2-088 C
Solar/Wind Helper
0.17
959431AF2-234 GEN
Solar/Wind Helper
1
961261AF2-417 GEN
Solar/Wind Helper
0.495
20676328BVR_Y1-020
Solar/Wind Helper
0.029
238208AF1-136 C
Solar/Wind Helper
0.192
218526CNTRALGAS2 C
Solar/Wind Helper
0.173
219620RIDERU C
Solar/Wind Helper
0.001
207459AE1-142 C O1
Solar/Wind Helper
0.309
20715828PEM_W1-120
Solar/Wind Helper
0.102
214067T20SOLAR
Solar/Wind Helper
0.012
219688LUMSOLAR_S C
Solar/Wind Helper
0.042
227927V4-067C
Solar/Wind Helper
0.011
964001AG1-254 GEN
Solar/Wind Helper
1.003
233990AG1-397 GEN
Solar/Wind Helper
0.031
205943AE1-185 GEN
Solar/Wind Helper
0.523
941421AE2-139 GEN
Solar/Wind Helper
2.573
209071AE2-133 GEN
Solar/Wind Helper
0.09
212266LOR1
Solar/Wind Helper
0.054
207518AF1-320_GEN
Solar/Wind Helper
1.718
20675428EAM_W2-061
Solar/Wind Helper
0.017
20715228NPK_W1-113
Solar/Wind Helper
0.083
207454AA2-184 E
Solar/Wind Helper
0.331
963711AG1-223 GEN
Solar/Wind Helper
0.068
218660EHAMPSOLAR C
Solar/Wind Helper
0.035
228728W1-130C
Solar/Wind Helper
0.057
233972AC1-094 C
Solar/Wind Helper
0.312
233998TM1NIN_3.36
Solar/Wind Helper
0.27
232404W1-003 C
Solar/Wind Helper
0.523
233950AC2-186 GEN
Solar/Wind Helper
0.12
232428Y3-058 C
Solar/Wind Helper
0.349
233915AB1-141 GEN
Solar/Wind Helper
0.518
235062AE1-101 C1
Solar/Wind Helper
1.463
223401AF1-299 GEN
Solar/Wind Helper
0.338
274767LEE CO EC;8U
Adder
12.032
235058AG1-386 C
Solar/Wind Helper
0.514
964991AG1-363 GEN
Solar/Wind Helper
4.415
203818AF1-086 GEN
Solar/Wind Helper
1.887
200917MEHOOPANY_G
Solar/Wind Helper
2.428
316097T157 G90
Solar/Wind Helper
1.154
203830AF1-094 GEN
Solar/Wind Helper
0.495
217208PARK ELE C
Solar/Wind Helper
0.005
205941AD2-115 GEN
Solar/Wind Helper
0.531
20742028HF_AC1-207
Solar/Wind Helper
0.15
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20714828MDF_W3-079
Solar/Wind Helper
0.139
20720728JCB_W1-129
Solar/Wind Helper
0.061
219904AC1-010 C
Solar/Wind Helper
0.064
232434Z2-077 GEN
Solar/Wind Helper
0.131
232426Y1-080 FULL
Solar/Wind Helper
0.04
233964AF2-378 GEN
Solar/Wind Helper
0.043
232422X3-066 FULL
Solar/Wind Helper
0.118
966131AG1-482 GEN
Solar/Wind Helper
0.078
237080AD1-060 GEN
Solar/Wind Helper
0.296
972203AH1-686 GEN
Adder
4.425
962771AG1-126 GEN
Solar/Wind Harmer
54.777
970281AG2-184 GEN
Solar/Wind Harmer
32.861
962211AG1-066 GEN
Solar/Wind Harmer
3.665
252524AE2-267 GEN
Solar/Wind Harmer
2.249
253372AE2-315 SEC3
Adder
2.585
253372AE2-315 SEC3
Adder
2.585
25306009OHH W.
Adder
3.927
970289AG2-191 GEN
Solar/Wind Harmer
2.572
274744AC1-111 GEN8
Adder
7.316
241997AF1-093 GEN
Solar/Wind Helper
0.28
20091526CHSTN_FL
Solar/Wind Helper
0.654
238109AE1-109 GEN2
Solar/Wind Helper
0.102
238110AE1-109 GEN3
Solar/Wind Helper
0.102
20090526Q36
Solar/Wind Helper
1.167
203993AD2-133_GEN1
Solar/Wind Helper
1.167
203804AE2-113_GEN
Solar/Wind Helper
1.924
207408W3-077 C
Solar/Wind Helper
0.092
203975AE1-071-GEN
Solar/Wind Helper
2.674
20674828DL_W4-046
Solar/Wind Helper
0.008
966261AG1-495 GEN
Solar/Wind Helper
0.088
959381AF2-229 GEN
Solar/Wind Helper
0.364
234033AF1-007_GEN
Solar/Wind Helper
7.245
232432Z2-076 GEN
Solar/Wind Helper
0.069
205932AD2-116_GEN
Solar/Wind Helper
0.523
960921AF2-383 GEN
Solar/Wind Helper
0.186
274733ELWOOD EC;3P
Adder
13.442
23750501ELLIOTTS
Solar/Wind Helper
0.788
254304AE2-114 C
Solar/Wind Helper
0.239
241982AE2-343 S C
Solar/Wind Helper
0.243
203961AE2-224 GEN
Solar/Wind Helper
2.707
959421AF2-233 GEN
Solar/Wind Helper
0.5
20675128HRM_W1-127
Solar/Wind Helper
0.032
207530AG1-191 GEN
Solar/Wind Helper
0.072
218524CNTRALGAS1 C
Solar/Wind Helper
0.173
20675528CPH_W2-050
Solar/Wind Helper
0.093
20715728PEM_W1-119
Solar/Wind Helper
0.102
219607WPEMNERT C
Solar/Wind Helper
0.085
219914AD2-027 C
Solar/Wind Helper
0.121
233923SMA
Solar/Wind Helper
0.989
205956AE1-196_GEN
Solar/Wind Helper
0.523
232436AB1-176 C
Solar/Wind Helper
0.046
233935AB2-179 C
Solar/Wind Helper
1.307
971313AH1-133 GEN
Solar/Wind Harmer
14.875
270367AC2-061_GEN
Solar/Wind Harmer
4.719
970879AG2-548 GEN
Solar/Wind Harmer
6.295
25196108MFTGT2
Adder
2.193
25196108MFTGT2
Adder
2.036
25196408WSDLE3
Adder
12.579
25196308WSDLE2
Adder
12.47
25196208WSDLE1
Adder
12.439
25196708WSDLE6
Adder
12.407
270132AB1-180 C
Adder
0.17
965411AG1-406 GEN
Solar/Wind Harmer
3.552
971061AG2-657 GEN
Solar/Wind Harmer
12.35
270240V3-007_GEN2
Solar/Wind Harmer
8.448
965461AG1-414 GEN
Solar/Wind Harmer
3.069
270594AE1-207 GEN
Solar/Wind Harmer
19.886
24729505KEY G4
Adder
8.586
238126S14_GEN_1
Solar/Wind Helper
0.81
941231AE2-117 GEN
Solar/Wind Helper
0.53
964051AG1-259 GEN
Solar/Wind Helper
0.075
964061AG1-260 GEN
Solar/Wind Helper
0.075
209116AE2-175 GEN
Solar/Wind Helper
1.966
20675728RH_W2-091
Solar/Wind Helper
0.149
207484AF2-139 C O1
Solar/Wind Helper
0.092
20675928HOL_W4-097
Solar/Wind Helper
0.055
219272CLEANLIGHT C
Solar/Wind Helper
0.027
228754AB1-001 C
Solar/Wind Helper
0.027
237085AD2-009_GEN
Solar/Wind Helper
1.449
957141AF2-008_MTX
Adder
81.782
944201AF1-088_MTX
Adder
163.563
CBM South 1LTFEXP_CBM-S1->PJM
CBM
48.581
WECLTFEXP_WEC->PJM
CLTF
5.002
LAGNLTFEXP_LAGN->PJM
CLTF
24.864
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.24
CPLELTFEXP_CPLE->PJM
CLTF
6.557
SIGELTFEXP_SIGE->PJM
CLTF
0.729
CBM West 1LTFEXP_CBM-W1->PJM
CBM
170.264
NYPJM->LTFIMP_NY
CLTF
6.276
TVALTFEXP_TVA->PJM
CLTF
12.63
AG2-052LTFEXP_AG2-052->PJM
LTF
0.306
CBM West 2LTFEXP_CBM-W2->PJM
CBM
173.156
LGEELTFEXP_LGEE->PJM
CLTF
9.844
MECLTFEXP_MEC->PJM
CLTF
21.939
AH1-155LTFEXP_AH1-155->PJM
LTF
0.459

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P1-2_#17217_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#17217_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:115.67 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6388.32
MW Contribution:16.79
Bus #Bus NameTypeMW Contribution
944971AF1-162 GEN
Solar/Wind Harmer
12.174
24728205BUCHG1
Adder
6.831
971073AG2-665 GEN
Solar/Wind Harmer
9.191
252509AD1-136 GEN
Solar/Wind Harmer
0.051
339221AD2-048_GEN
Solar/Wind Harmer
0.006
972045AH1-571 GEN
Solar/Wind Harmer
2.094
25183208HLCRTG
Solar/Wind Harmer
0.016
25194508D.CRK3
Adder
2.019
964571AG1-320 GEN
Solar/Wind Harmer
8.854
970653AG2-424 GEN
Solar/Wind Harmer
4.654
970653AG2-424 GEN
Solar/Wind Harmer
2.412
24728805RICHG1
Adder
5.204
24379505HDWTR1G C
Solar/Wind Harmer
0.003
270383AD1-128 GEN
Solar/Wind Harmer
0.006
960441AF2-335 GEN
Solar/Wind Harmer
9.416
339255AE2-071 GEN
Solar/Wind Harmer
-0.154
966021AG1-471 GEN
Solar/Wind Harmer
5.054
25326109MON D
Adder
1.763
970885AG2-551 GEN
Solar/Wind Harmer
3.116
945421AF1-207 GEN
Solar/Wind Harmer
0.001
270031AE2-169
Solar/Wind Harmer
5.138
276911AD2-131_GEN
Solar/Wind Harmer
1.288
944541AF1-119 GEN
Solar/Wind Harmer
0.623
964611AG1-324 GEN
Solar/Wind Harmer
0.696
270201AC2-176 GEN
Solar/Wind Harmer
0.002
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
276646AC1-214 GEN2
Solar/Wind Harmer
0.36
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
958491AF2-143 GEN
Solar/Wind Harmer
13.709
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
971573AH1-285 GEN
Solar/Wind Harmer
1.702
274695ROCKY RD ;2P
Adder
14.57
274765LEE CO EC;6U
Adder
12.204
274763LEE CO EC;4U
Adder
12.06
20088926STNY CRK
Solar/Wind Helper
0.928
20088626ARWF_N39
Solar/Wind Helper
1.362
946381AF1-302 GEN
Solar/Wind Helper
0.246
203946AE2-131 C
Solar/Wind Helper
0.53
238217AF1-153 C O1
Solar/Wind Helper
0.262
946751AF1-339 GEN
Solar/Wind Helper
0.5
209029WAYMART-WD
Solar/Wind Helper
0.937
211065PSPA IPP
Solar/Wind Helper
0.168
211065PSPA IPP
Solar/Wind Helper
0.168
20674128FR_U2-059
Solar/Wind Helper
0.004
20671828STAW2-080
Solar/Wind Helper
0.029
207442AE1-156 GEN
Solar/Wind Helper
0.351
20720628TIN_W1-124
Solar/Wind Helper
0.203
233901CHERRYDALE C
Solar/Wind Helper
0.24
234036AF2-325 C
Solar/Wind Helper
0.043
233987AB2-037 GEN
Solar/Wind Helper
2.415
235063AE1-101 C2
Solar/Wind Helper
1.463
237001AB1-127_GEN
Solar/Wind Helper
0.388
237034AC2-136 C
Solar/Wind Helper
0.194
243186AF1-051 GEN
50/50
12.478
24721805FLATG3
50/50
2.756
24721705FLATG2
50/50
50.519
24723205RIVRG3
Adder
36.021
24686105CER G3
Adder
15.629
970947AG2-589 GEN
Solar/Wind Harmer
0.412
970155AG2-107 GEN
Solar/Wind Harmer
29.498
945681AF1-233 GEN
Solar/Wind Harmer
19.197
25194608D.CRK4
Adder
2.348
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
9.904
270445AC2-157 GEN2
Solar/Wind Harmer
0.004
971821AH1-427 GEN
Solar/Wind Harmer
9.786
24735205WLF2G2
Adder
8.08
24728605AND G2
Adder
5.27
970613AG2-401 GEN
Solar/Wind Harmer
6.984
253370AE2-315 SEC1
Adder
2.733
253371AE2-315 SEC2
Adder
2.585
970291AG2-192 GEN
Solar/Wind Harmer
1.228
965031AG1-367 GEN
Solar/Wind Harmer
9.442
964901AG1-354 GEN
Solar/Wind Harmer
14.138
960071AF2-298 GEN
Solar/Wind Harmer
4.694
965651AG1-433 GEN
Solar/Wind Harmer
2.727
270055AF2-134 C O1
Solar/Wind Harmer
0.007
274877BISHOP HL;1U
Solar/Wind Harmer
0.308
253343AC1-166 GEN
Solar/Wind Harmer
0.004
276901AD2-066 C O1
Solar/Wind Harmer
0.009
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
274745AC1-111 GEN9
Adder
7.316
238185AF2-356 C
Solar/Wind Helper
2.612
241966AE1-183 GEN
Solar/Wind Helper
0.28
23751101LEADS_P59
Solar/Wind Helper
1.483
964201AG1-281 GEN
Solar/Wind Helper
0.544
238206AE2-263_GEN
Solar/Wind Helper
1.011
959471AF2-238 GEN
Solar/Wind Helper
0.517
203860AG1-193 C
Solar/Wind Helper
0.254
209067AE2-060 GEN
Solar/Wind Helper
0.091
963071AG1-156 GEN
Solar/Wind Helper
1.625
316095T157 G97
Solar/Wind Helper
1.154
203835AF1-098 GEN
Solar/Wind Helper
1.958
20674628WNG_W3-110
Solar/Wind Helper
0.097
219919AE1-041 FULL
Solar/Wind Helper
0.004
218438BLK ROCK C
Solar/Wind Helper
0.029
20714528FRN_Y2-051
Solar/Wind Helper
0.061
20720828JCB_W4-025
Solar/Wind Helper
0.067
219906AC1-017 C
Solar/Wind Helper
0.044
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219291REEVESSOUT C
Solar/Wind Helper
0.012
219912AD2-042 GEN
Solar/Wind Helper
0.158
219766PARADISE C
Solar/Wind Helper
0.057
230415AB2-049 C
Solar/Wind Helper
0.032
230430AE1-229_GEN
Solar/Wind Helper
3.539
233996TM1833_GEN
Solar/Wind Helper
0.27
232406W1-004 FULL
Solar/Wind Helper
0.523
237030AB1-096 C
Solar/Wind Helper
0.063
957471AF2-041 GEN
Solar/Wind Harmer
5.997
24318705GVG2
50/50
11.615
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
971315AH1-136 GEN
Solar/Wind Harmer
2.232
971687AH1-348 GEN
Solar/Wind Harmer
1.067
970333AG2-219 GEN
Solar/Wind Harmer
7.406
25196808ZIMRHP
Adder
109.116
25196008MFTGT1
Adder
1.989
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0.001
270005AE1-210 C O1
Solar/Wind Harmer
2.046
270032AE2-172
Solar/Wind Harmer
6.293
970825AG2-519 GEN
Solar/Wind Harmer
3.343
24387305FR-4G C
Solar/Wind Harmer
0.004
945371AF1-202 GEN
Solar/Wind Harmer
0.001
958861AF2-177 GEN
Solar/Wind Harmer
4.037
274880W4-005 GEN4
Solar/Wind Harmer
0.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
11.601
972175AH1-670 GEN
Solar/Wind Harmer
7.662
939741AE1-205 GEN
Solar/Wind Harmer
12.928
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
970569AG2-363 GEN
Solar/Wind Harmer
27.46
971997AH1-543 GEN
Solar/Wind Harmer
4.802
274773LINCOLN ;4U
Adder
11.055
274774LINCOLN ;5U
Adder
11.055
276158O29GEN2
Solar/Wind Harmer
0.001
276861AD2-134 GEN
Solar/Wind Harmer
0.164
274761LEE CO EC;2U
Adder
12.175
237046AF1-021 C
Solar/Wind Helper
0.577
23751201ROTHROCK
Solar/Wind Helper
0.878
20089226LOOKOUT
Solar/Wind Helper
0.665
254303AC2-168 GEN
Solar/Wind Helper
0.173
946691AF1-333 GEN
Solar/Wind Helper
0.5
946741AF1-338 GEN
Solar/Wind Helper
0.5
961421AF2-433 GEN
Solar/Wind Helper
0.499
209027LOR2_Q27
Solar/Wind Helper
1.165
23583801GRNGAP
Solar/Wind Helper
4.282
961971AG1-040 GEN
Solar/Wind Helper
0.492
207510AF2-138 C
Solar/Wind Helper
0.088
20673728F2S_V4-070
Solar/Wind Helper
0.032
219908AB1-139 C
Solar/Wind Helper
0.079
219612MATRIX C
Solar/Wind Helper
0.025
20716028EGP_W2-019
Solar/Wind Helper
0.02
219623KINSLEYBEA C
Solar/Wind Helper
0.002
233952AC2-187 GEN
Solar/Wind Helper
0.24
233940AF2-379 C
Solar/Wind Helper
0.064
233982AB2-133 GEN
Solar/Wind Helper
0.369
238221AF1-254 C O1
Solar/Wind Helper
0.236
223402AF1-300 C
Solar/Wind Helper
0.338
24721605FLATG1
50/50
2.756
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
957241AF2-018 GEN
Solar/Wind Harmer
-0.002
270400AC1-102 GEN
Solar/Wind Harmer
3.805
24477305BRIDGE
Adder
0.588
941621AE2-160 GEN
Adder
5.057
972163AH1-664 GEN
Solar/Wind Harmer
11.344
339243AC2-075 GEN1
Solar/Wind Harmer
0.002
3429211JKCT 2G
Adder
16.676
25196508WSDLE4
Adder
12.095
24734805WLF1G4
Adder
8.198
270340AC2-060 GEN
Solar/Wind Harmer
0.011
24735105WLF2G1
Adder
8.08
970455AG2-298 GEN
Solar/Wind Harmer
6.495
270269AC2-059
Solar/Wind Harmer
0.006
24699105WLD G1 C
Solar/Wind Harmer
0.001
253400AC2-068 GEN
Solar/Wind Harmer
1.198
963841AG1-237 GEN
Solar/Wind Harmer
4.089
970115AG2-085 GEN
Solar/Wind Harmer
3.766
24386205FR-12G C
Solar/Wind Harmer
0.002
24690905MDL-1G C
Solar/Wind Harmer
0.003
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
971609AH1-304 GEN
Solar/Wind Harmer
1.526
270432AC2-029 GEN
Solar/Wind Harmer
4.141
944221AF1-090 GEN
Solar/Wind Harmer
5.475
965101AG1-375 GEN
Solar/Wind Harmer
9.315
276655WTG1_EQ
Solar/Wind Harmer
0.004
241972AD1-140 GEN
Solar/Wind Harmer
1.003
926823AC1-168 GEN
Solar/Wind Harmer
1.557
276882AE2-255 GEN
Solar/Wind Harmer
1.069
274776LINCOLN ;7U
Adder
11.055
274746AC1-111 G10
Adder
7.316
274731ELWOOD EC;2P
Adder
21.509
274733ELWOOD EC;3P
Adder
13.442
23750501ELLIOTTS
Solar/Wind Helper
0.788
254304AE2-114 C
Solar/Wind Helper
0.239
241982AE2-343 S C
Solar/Wind Helper
0.243
203961AE2-224 GEN
Solar/Wind Helper
2.707
959421AF2-233 GEN
Solar/Wind Helper
0.5
20675128HRM_W1-127
Solar/Wind Helper
0.032
207530AG1-191 GEN
Solar/Wind Helper
0.072
218524CNTRALGAS1 C
Solar/Wind Helper
0.173
20675528CPH_W2-050
Solar/Wind Helper
0.093
20715728PEM_W1-119
Solar/Wind Helper
0.102
219607WPEMNERT C
Solar/Wind Helper
0.085
219914AD2-027 C
Solar/Wind Helper
0.121
233923SMA
Solar/Wind Helper
0.989
205956AE1-196_GEN
Solar/Wind Helper
0.523
232436AB1-176 C
Solar/Wind Helper
0.046
24722005FLATG5
50/50
2.756
24721905FLATG4
50/50
50.519
970153AG2-106 GEN
Solar/Wind Harmer
29.498
972103AH1-617 GEN
Solar/Wind Harmer
21.835
960911AF2-382 GEN
Solar/Wind Harmer
8.035
25194608D.CRK4
Adder
2.348
253316AC1-085 GEN3
Solar/Wind Harmer
0.006
253433AC1-085 GEN1
Solar/Wind Harmer
0.005
946181AF1-283 GEN
Solar/Wind Harmer
12.875
24728505AND G1
Adder
5.27
253370AE2-315 SEC1
Adder
2.733
253371AE2-315 SEC2
Adder
2.585
960741AF2-365 GEN
Solar/Wind Harmer
4.731
247642Z2-115 C
Solar/Wind Harmer
0.004
970289AG2-191 GEN
Solar/Wind Harmer
1.039
970291AG2-192 GEN
Solar/Wind Harmer
0.944
946031AF1-268 GEN
Solar/Wind Harmer
8.936
24755605MDL-5G
Solar/Wind Harmer
0.001
971155AH1-034 GEN
Solar/Wind Harmer
10.922
276668AB2-070 GEN1
Solar/Wind Harmer
0.339
943031AE2-326 GEN
Solar/Wind Harmer
4.828
270535AF1-215 GEN1
Solar/Wind Harmer
0.011
943121AE2-341 GEN
Solar/Wind Harmer
15.314
943591AF1-030 GEN
Solar/Wind Harmer
10.184
274767LEE CO EC;8U
Adder
12.032
235058AG1-386 C
Solar/Wind Helper
0.514
964991AG1-363 GEN
Solar/Wind Helper
4.415
203818AF1-086 GEN
Solar/Wind Helper
1.887
200917MEHOOPANY_G
Solar/Wind Helper
2.428
316097T157 G90
Solar/Wind Helper
1.154
203830AF1-094 GEN
Solar/Wind Helper
0.495
217208PARK ELE C
Solar/Wind Helper
0.005
205941AD2-115 GEN
Solar/Wind Helper
0.531
20742028HF_AC1-207
Solar/Wind Helper
0.15
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20714828MDF_W3-079
Solar/Wind Helper
0.139
20720728JCB_W1-129
Solar/Wind Helper
0.061
219904AC1-010 C
Solar/Wind Helper
0.064
232434Z2-077 GEN
Solar/Wind Helper
0.131
232426Y1-080 FULL
Solar/Wind Helper
0.04
233964AF2-378 GEN
Solar/Wind Helper
0.043
232422X3-066 FULL
Solar/Wind Helper
0.118
966131AG1-482 GEN
Solar/Wind Helper
0.139
237080AD1-060 GEN
Solar/Wind Helper
0.296
959091AF2-200 GEN
Solar/Wind Harmer
3.998
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270399AC1-101 GEN
Solar/Wind Harmer
3.805
972143AH1-644 GEN
Solar/Wind Harmer
11.827
971985AH1-537 GEN
Solar/Wind Harmer
3.245
972165AH1-665 GEN
Solar/Wind Harmer
9.085
24734705WLF1G3
Adder
8.198
24734905WLF1G5
Adder
8.198
339211AE2-254 GEN
Solar/Wind Harmer
0.004
965401AG1-405 GEN
Solar/Wind Harmer
5.522
24725505WLD G2 C
Solar/Wind Harmer
0.002
253349AC2-067 GEN
Solar/Wind Harmer
2.978
24386405FR-21G C
Solar/Wind Harmer
0.001
971029AG2-637 GEN
Solar/Wind Harmer
14.095
24697605MDL-3G C
Solar/Wind Harmer
0.002
270181AB1-006 GEN2
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
5.525
276656WTG2_EQ
Solar/Wind Harmer
0
941731AE2-173 GEN
Solar/Wind Harmer
7.695
966391AG1-508 GEN
Solar/Wind Harmer
1.427
276868AE1-113 GEN
Solar/Wind Harmer
1.835
274775LINCOLN ;6U
Adder
11.055
274777LINCOLN ;8U
Adder
11.055
970833AG2-524 GEN
Solar/Wind Harmer
10.052
970833AG2-524 GEN
Solar/Wind Harmer
6.701
971675AH1-338 GEN
Solar/Wind Harmer
3.562
20092526R32
Solar/Wind Helper
1.311
203846AF2-130 C
Solar/Wind Helper
0.497
203855AF2-088 C
Solar/Wind Helper
0.17
959431AF2-234 GEN
Solar/Wind Helper
1
961261AF2-417 GEN
Solar/Wind Helper
0.495
20676328BVR_Y1-020
Solar/Wind Helper
0.029
238208AF1-136 C
Solar/Wind Helper
0.192
218526CNTRALGAS2 C
Solar/Wind Helper
0.173
219620RIDERU C
Solar/Wind Helper
0.001
207459AE1-142 C O1
Solar/Wind Helper
0.309
20715828PEM_W1-120
Solar/Wind Helper
0.102
214067T20SOLAR
Solar/Wind Helper
0.012
219688LUMSOLAR_S C
Solar/Wind Helper
0.042
227927V4-067C
Solar/Wind Helper
0.011
964001AG1-254 GEN
Solar/Wind Helper
1.003
233990AG1-397 GEN
Solar/Wind Helper
0.279
205943AE1-185 GEN
Solar/Wind Helper
0.523
971171AH1-044 GEN
Solar/Wind Harmer
3.998
24318705GVG2
50/50
11.615
971191AH1-055 GEN
Solar/Wind Harmer
30.005
970243AG2-164 GEN
Solar/Wind Harmer
6.06
972167AH1-666 GEN
Solar/Wind Harmer
8.145
252510AF1-249 C
Solar/Wind Harmer
0.077
25196008MFTGT1
Adder
1.926
970093AG2-073 GEN
Solar/Wind Harmer
9.929
966571AG1-526 GEN
Solar/Wind Harmer
21.864
972273AH1-721 GEN
Adder
114.731
942481AE2-261 GEN
Solar/Wind Harmer
27.825
276621W2-048 GEN
Solar/Wind Harmer
0.469
276838X2-022 GEN2
Solar/Wind Harmer
0.523
971993AH1-541 GEN
Solar/Wind Harmer
4.291
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
13.864
942111AE2-223 GEN
Solar/Wind Harmer
3.001
970571AG2-364 GEN
Solar/Wind Harmer
18.307
276889AE2-281 GEN
Solar/Wind Harmer
0.001
276897AD1-100 C
Solar/Wind Harmer
0.012
274772LINCOLN ;3U
Adder
11.055
276805AD2-038 GEN
Solar/Wind Harmer
0.003
276157O29GEN1
Solar/Wind Harmer
1.478
274850MENDOTA H;RU
Solar/Wind Harmer
0.108
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.164
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
0.974
274729ELWOOD EC;1P
Adder
21.509
237048AF1-022 C
Solar/Wind Helper
0.228
237043AE2-125 C
Solar/Wind Helper
0.207
946731AF1-337 GEN
Solar/Wind Helper
0.5
20671928W4-073
Solar/Wind Helper
0.098
207437AD2-070 GEN
Solar/Wind Helper
0.15
20675828AU_W4-064
Solar/Wind Helper
0.032
207528AF2-192 GEN
Solar/Wind Helper
0.082
20673628F1S_V4-069
Solar/Wind Helper
0.032
217213AMBOY SO C
Solar/Wind Helper
0.031
218428ETC SOLAR C
Solar/Wind Helper
0.005
219907AC1-030 C
Solar/Wind Helper
0.036
219258KINSLEYDEP C
Solar/Wind Helper
0.081
230434AG1-499 GEN
Solar/Wind Helper
0.241
230511AF1-262
Solar/Wind Helper
0.015
233954AC2-188 GEN
Solar/Wind Helper
0.24
233930AB2-032 GEN
Solar/Wind Helper
0.392
24686205CER G4
Adder
15.547
971461AH1-227 GEN
Solar/Wind Harmer
5.464
970519AG2-331 GEN
Solar/Wind Harmer
26.931
970699AG2-449 GEN
Solar/Wind Harmer
2.59
958171AF2-111 GEN
Solar/Wind Harmer
25.128
25196608WSDLE5
Adder
12.22
3429391JKCT 9G
Adder
11.865
253406AD2-031_GEN
Solar/Wind Harmer
0.735
270291AC1-194 GEN
Solar/Wind Harmer
7.771
253415AE1-040 GEN
Solar/Wind Harmer
0.004
270273AD2-016 GEN
Solar/Wind Harmer
0.998
24728705AND G3
Adder
11.022
970193AG2-126 GEN
Solar/Wind Harmer
14.303
270437AC2-090 C
Solar/Wind Harmer
0.004
270346AE1-212 GEN
Solar/Wind Harmer
8.4
958821AF2-173 GEN
Solar/Wind Harmer
13.219
970781AG2-491 GEN
Solar/Wind Harmer
9.369
970513AG2-328 GEN
Solar/Wind Harmer
4.056
970517AG2-330 GEN
Solar/Wind Harmer
24.338
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
274853TWINGROVE;U1
Solar/Wind Harmer
0.004
959611AF2-252 GEN
Solar/Wind Harmer
3.082
944531AF1-118 GEN
Solar/Wind Harmer
41.286
253333AC1-068 GEN
Solar/Wind Harmer
0.014
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
970707AG2-453 GEN
Solar/Wind Harmer
29.848
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274855GSG-6 ;RU
Solar/Wind Harmer
0.335
23750701CROSSCHOOL
Solar/Wind Helper
1.427
202652Y1-033 WT C
Solar/Wind Helper
0.655
20089026BF_G21_K23
Solar/Wind Helper
0.541
238127S14_GEN_2
Solar/Wind Helper
0.81
254305AE2-115 C
Solar/Wind Helper
0.239
238202AE2-262_GEN
Solar/Wind Helper
1.063
941421AE2-139 GEN
Solar/Wind Helper
2.573
209071AE2-133 GEN
Solar/Wind Helper
0.09
212266LOR1
Solar/Wind Helper
0.054
207518AF1-320_GEN
Solar/Wind Helper
1.718
20675428EAM_W2-061
Solar/Wind Helper
0.017
20715228NPK_W1-113
Solar/Wind Helper
0.083
207454AA2-184 E
Solar/Wind Helper
0.331
963711AG1-223 GEN
Solar/Wind Helper
0.068
218660EHAMPSOLAR C
Solar/Wind Helper
0.035
228728W1-130C
Solar/Wind Helper
0.057
233972AC1-094 C
Solar/Wind Helper
0.312
233998TM1NIN_3.36
Solar/Wind Helper
0.27
232404W1-003 C
Solar/Wind Helper
0.523
233950AC2-186 GEN
Solar/Wind Helper
0.12
232428Y3-058 C
Solar/Wind Helper
0.349
233915AB1-141 GEN
Solar/Wind Helper
0.518
235062AE1-101 C1
Solar/Wind Helper
1.463
223401AF1-299 GEN
Solar/Wind Helper
0.338
972043AH1-570 GEN
Solar/Wind Harmer
2.614
25194408D.CRK1
Adder
10.799
942891AE2-308 GEN
Solar/Wind Harmer
9.954
24728905RICHG2
Adder
5.204
971081AG2-670 GEN
Solar/Wind Harmer
7.154
945391AF1-204 GEN
Solar/Wind Harmer
10.131
926881AC1-175 GEN
Solar/Wind Harmer
0.001
966841AG1-555 GEN
Solar/Wind Harmer
1.065
971485AH1-239 GEN
Solar/Wind Harmer
7.489
964781AG1-341 GEN
Solar/Wind Harmer
9.922
970883AG2-550 GEN
Solar/Wind Harmer
9.347
270599AE1-208 GEN
Solar/Wind Harmer
8.564
960971AF2-388 GEN
Solar/Wind Harmer
5.453
960611AF2-352 GEN
Solar/Wind Harmer
3.082
276782AC1-033 GEN
Solar/Wind Harmer
0.001
274879MINONK ;1U
Solar/Wind Harmer
0.386
276708O09 GEN2
Solar/Wind Harmer
0.325
274862TOP CROP ;2U
Solar/Wind Harmer
1.236
958481AF2-142 GEN
Solar/Wind Harmer
13.701
972267AH1-718 GEN
Adder
5.45
274693ROCKY RD ;1P
Adder
14.427
233935AB2-179 C
Solar/Wind Helper
1.307
24289405MTG1
50/50
11.351
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
971403AH1-188 GEN
Solar/Wind Harmer
16.785
970149AG2-104 GEN
Solar/Wind Harmer
49.891
927014AC1-188 GEN
Solar/Wind Harmer
0.007
970091AG2-072 GEN
Adder
113.581
3429421JKCT 10G
Adder
11.865
270263AC1-001 GEN
Solar/Wind Harmer
0.987
971565AH1-281 GEN
Solar/Wind Harmer
1.958
970773AG2-487 GEN
Solar/Wind Harmer
1.7
970273AG2-179 GEN
Solar/Wind Harmer
3.322
963741AG1-226 GEN
Solar/Wind Harmer
22.385
24791305MDL-5G
Solar/Wind Harmer
0.001
274854TWINGROVE;U2
Solar/Wind Harmer
0.004
276726Z2-087_GEN
Solar/Wind Harmer
0.003
971917AH1-482 GEN
Solar/Wind Harmer
11.983
253325AC1-069 GEN
Solar/Wind Harmer
0.014
941551AE2-152 GEN
Solar/Wind Harmer
0.001
276691AA1-018 GEN1
Solar/Wind Harmer
1.106
274872LEEDK;1U
Solar/Wind Harmer
0.006
235054AD2-180 GEN
Solar/Wind Helper
2.032
23562501BACKB
Solar/Wind Helper
1.07
235531U2-073 GEN
Solar/Wind Helper
3.23
20094526CT_V3-030
Solar/Wind Helper
0.53
238108AE1-109 GEN1
Solar/Wind Helper
0.102
203954AE2-126 C
Solar/Wind Helper
0.522
957921AF2-086 GEN
Solar/Wind Helper
0.493
274764LEE CO EC;5U
Adder
12.204
23652301WDPWR_K20
Solar/Wind Helper
0.168
23585401KL_K28_T16
Solar/Wind Helper
1.53
203955AF1-039 C O1
Solar/Wind Helper
0.432
20083426SW_E13_K22
Solar/Wind Helper
0.064
241967AE2-285_GEN
Solar/Wind Helper
0.696
946071AF1-272 GEN
Solar/Wind Helper
3.051
20084626FORWARD
Solar/Wind Helper
0.402
20398826ARMNA MT
Solar/Wind Helper
1.656
209137AF2-361 C
Solar/Wind Helper
1.531
208972BECR K09
Solar/Wind Helper
0.372
966111AG1-480 GEN
Solar/Wind Helper
0.082
20674928WA_W3-044
Solar/Wind Helper
0.107
219615MILLCREEK C
Solar/Wind Helper
0.028
219921AF1-264
Solar/Wind Helper
0.054
203947AF1-006 C
Solar/Wind Helper
0.527
230433AD2-135 GEN
Solar/Wind Helper
0.018
233970AC1-092 C
Solar/Wind Helper
0.361
232424Y1-079 C
Solar/Wind Helper
0.12
237002AB1-128_GEN
Solar/Wind Helper
0.388
23777901MDS_W4-102
Solar/Wind Helper
0.15
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
237006AB1-125 GEN
Solar/Wind Helper
0.109
24686505CER G6
Adder
15.608
217211CAMDEN ST C
Solar/Wind Helper
0.005
219249CENTRALDIV C
Solar/Wind Helper
0.011
20715028HAN_X4-015
Solar/Wind Helper
0.061
959561AF2-247 GEN
Solar/Wind Helper
0.022
219348LDSOLAR C
Solar/Wind Helper
0.121
228729W2-030 C
Solar/Wind Helper
0.116
233971AC1-093 C
Solar/Wind Helper
0.369
233997TMININ_4.2
Solar/Wind Helper
0.27
233994AC2-023 GEN
Solar/Wind Helper
0.992
233918AB1-142 GEN
Solar/Wind Helper
0.518
205917AD1-020 ES
Solar/Wind Helper
0.368
959081AF2-199 GEN
Solar/Wind Harmer
1.999
971067AG2-660 GEN
Solar/Wind Harmer
0.666
243186AF1-051 GEN
50/50
12.478
24723005RIVRG1
Adder
36.021
24723105RIVRG2
Adder
36.021
24685805CER G1
Adder
15.526
24685905CER G2
Adder
15.526
971225AH1-072 GEN
Solar/Wind Harmer
2.13
971227AH1-073 GEN
Solar/Wind Harmer
2.13
252519AF1-045_GEN
Solar/Wind Harmer
8.714
252516AE2-318_GEN
Solar/Wind Harmer
7.729
971125AH1-004 GEN
Solar/Wind Harmer
3.992
253317AC1-085 GEN4
Solar/Wind Harmer
0.006
270444AC2-157 GEN1
Solar/Wind Harmer
0.004
971587AH1-292 GEN
Solar/Wind Harmer
7.197
253370AE2-315 SEC1
Adder
2.733
971613AH1-306 GEN
Solar/Wind Harmer
4.531
25322209TAIT E
Adder
13.187
25322209TAIT E
Adder
12.891
276916AD2-100_GEN
Solar/Wind Harmer
19.555
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
247621Y3-024
Adder
0.32
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276741O09 GEN1
Solar/Wind Harmer
0.325
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
238120AE2-309 GEN
Solar/Wind Helper
0.507
241801AE1-079 GEN
Solar/Wind Helper
0.271
20303426NA_O38_P22
Solar/Wind Helper
1.117
203853AF1-134 C O1
Solar/Wind Helper
0.534
203952AE2-129 C
Solar/Wind Helper
0.529
209054AE2-059 GEN
Solar/Wind Helper
0.09
203979AG1-198 GEN
Solar/Wind Helper
0.297
203980AG1-197 GEN
Solar/Wind Helper
0.369
964851AG1-348 GEN
Solar/Wind Helper
0.088
217204WCALDSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.003
218440SUMMTASSOC C
Solar/Wind Helper
0.018
20714928UPF_X1-085
Solar/Wind Helper
0.005
230407AD2-065 C
Solar/Wind Helper
0.042
237025AB1-124 C
Solar/Wind Helper
0.145
23777801MSM_W1-116
Solar/Wind Helper
0.1
238169AE2-226 GEN1
Solar/Wind Helper
0.555
238170AE2-226 GEN2
Solar/Wind Helper
0.555
971341AH1-150 GEN
Solar/Wind Harmer
3.998
971343AH1-151 GEN
Solar/Wind Harmer
3.998
972203AH1-686 GEN
Adder
4.425
962771AG1-126 GEN
Solar/Wind Harmer
46.194
970281AG2-184 GEN
Solar/Wind Harmer
22.926
252524AE2-267 GEN
Solar/Wind Harmer
0.004
253372AE2-315 SEC3
Adder
2.585
253372AE2-315 SEC3
Adder
2.585
25306009OHH W.
Adder
3.927
970289AG2-191 GEN
Solar/Wind Harmer
1.794
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.339
276848AB2-070 GEN3
Solar/Wind Harmer
0.337
958391AF2-133 GEN
Solar/Wind Harmer
0.001
959341AF2-225 GEN
Solar/Wind Harmer
9.696
970169AG2-114 GEN
Solar/Wind Harmer
9.2
274848CAMPGROVE;RU
Solar/Wind Harmer
0.002
270536AF1-215 GEN2
Solar/Wind Harmer
0.011
274744AC1-111 GEN8
Adder
7.316
961011AF2-392 GEN
Solar/Wind Harmer
5.358
241997AF1-093 GEN
Solar/Wind Helper
0.28
20091526CHSTN_FL
Solar/Wind Helper
0.654
238109AE1-109 GEN2
Solar/Wind Helper
0.102
238110AE1-109 GEN3
Solar/Wind Helper
0.102
20090526Q36
Solar/Wind Helper
1.167
203993AD2-133_GEN1
Solar/Wind Helper
1.167
203804AE2-113_GEN
Solar/Wind Helper
1.924
207408W3-077 C
Solar/Wind Helper
0.092
203975AE1-071-GEN
Solar/Wind Helper
2.674
20674828DL_W4-046
Solar/Wind Helper
0.008
966261AG1-495 GEN
Solar/Wind Helper
0.088
959381AF2-229 GEN
Solar/Wind Helper
0.364
234033AF1-007_GEN
Solar/Wind Helper
7.245
232432Z2-076 GEN
Solar/Wind Helper
0.069
205932AD2-116_GEN
Solar/Wind Helper
0.523
960921AF2-383 GEN
Solar/Wind Helper
0.373
970239AG2-162 GEN
Solar/Wind Harmer
2.59
270186AC1-089 GEN
Solar/Wind Harmer
0.006
962581AG1-107 GEN
Solar/Wind Harmer
0.002
960161AF2-307 GEN
Solar/Wind Harmer
6.771
970235AG2-159 GEN
Solar/Wind Harmer
6.108
970235AG2-159 GEN
Solar/Wind Harmer
3.504
970107AG2-081 GEN
Solar/Wind Harmer
2.994
253394AE2-221_GEN
Solar/Wind Harmer
0.012
253398AE2-221_GEN2
Solar/Wind Harmer
0.012
270209AC1-174_GEN
Solar/Wind Harmer
0.001
970241AG2-163 GEN
Solar/Wind Harmer
5.517
970825AG2-519 GEN
Solar/Wind Harmer
10.439
970321AG2-212 GEN
Solar/Wind Harmer
4.056
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
276645AC1-214 GEN1
Solar/Wind Harmer
0.36
274770LINCOLN ;1U
Adder
11.055
274771LINCOLN ;2U
Adder
11.055
972259AH1-714 GEN
Adder
24.976
276603SUBLETTE C
Solar/Wind Harmer
0
274696ROCKY RD ;4P
Adder
14.914
274762LEE CO EC;3U
Adder
12.175
274697ROCKY RD ;3P
Adder
3.958
944781AF1-143 GEN
Solar/Wind Helper
2.836
962101AG1-054 GEN
Solar/Wind Helper
0.715
241985AE1-237 GEN
Solar/Wind Helper
0.271
203940AF1-140 C
Solar/Wind Helper
0.446
961431AF2-434 GEN
Solar/Wind Helper
0.499
207471AF2-354 C
Solar/Wind Helper
0.184
20676228FRD_X1-012
Solar/Wind Helper
0.1
217081WEATEXAS C
Solar/Wind Helper
0.014
20676128MHD_W3-029
Solar/Wind Helper
0.103
20673828FLE_V3-070
Solar/Wind Helper
0.097
20716928W4-060COL
Solar/Wind Helper
0.055
963391AG1-188 GEN
Solar/Wind Helper
0.088
963401AG1-189 GEN
Solar/Wind Helper
0.06
20390526W1-045 C
Solar/Wind Helper
0.357
233939AC1-091 C
Solar/Wind Helper
0.361
232408W1-005 C
Solar/Wind Helper
0.523
232410W1-006 C
Solar/Wind Helper
0.523
233946AB2-136 GEN
Solar/Wind Helper
0.586
233944AB2-135 GEN
Solar/Wind Helper
0.607
233933AB2-153 GEN
Solar/Wind Helper
0.24
205916AD1-020 GEN
Solar/Wind Helper
1.711
235020AA1-095 C
Solar/Wind Helper
0.045
238175AF1-290_GEN
Solar/Wind Helper
0.123
24289405MTG1
50/50
11.351
24686405CER G5
Adder
15.485
270053AF1-130 C
Solar/Wind Harmer
2.748
970913AG2-568 GEN
Solar/Wind Harmer
8.769
972173AH1-669 GEN
Solar/Wind Harmer
4.843
270222AC2-111 GEN
Solar/Wind Harmer
4.893
270356AE2-297 GEN
Solar/Wind Harmer
0.013
970273AG2-179 GEN
Solar/Wind Harmer
5.694
970191AG2-125 GEN
Solar/Wind Harmer
2.433
270004AE1-209 GEN
Solar/Wind Harmer
2.046
339250AF1-203 GEN
Solar/Wind Harmer
0.001
962251AG1-071 GEN
Solar/Wind Harmer
5.847
276686W4-005 GEN3
Solar/Wind Harmer
0.001
965091AG1-374 GEN
Solar/Wind Harmer
27.736
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274878BISHOP HL;2U
Solar/Wind Harmer
0.308
253338AC1-165 GEN
Solar/Wind Harmer
0.004
274760LEE CO EC;1U
Adder
12.175
238118U2-030_1
Solar/Wind Helper
0.343
20089126CSLMN_L13
Solar/Wind Helper
0.683
203854AF2-039 C
Solar/Wind Helper
0.354
20334926Z1-069 C
Solar/Wind Helper
1.49
959441AF2-235 GEN
Solar/Wind Helper
0.255
212507AE2-042_GEN
Solar/Wind Helper
1.772
961341AF2-425 GEN
Solar/Wind Helper
0.499
961301AF2-421 GEN
Solar/Wind Helper
0.496
963151AG1-164 GEN
Solar/Wind Helper
0.496
207439AE1-081 C O1
Solar/Wind Helper
0.02
20674328GAR_V4-001
Solar/Wind Helper
0.024
217209CENTRL HS C
Solar/Wind Helper
0.009
20676428JCR_X2-075
Solar/Wind Helper
0.073
962511AG1-100 GEN
Solar/Wind Helper
0.488
207445AB1-138_GEN
Solar/Wind Helper
0.111
219304NAMERICA C
Solar/Wind Helper
0.139
219686LUMSOLAR_N C
Solar/Wind Helper
0.042
237038AE2-054 C
Solar/Wind Helper
0.238
23779801AA1-109
Solar/Wind Helper
0.168
962761AG1-125 GEN
Solar/Wind Harmer
46.194
24728305BUCHG2
Adder
6.831
252507AC2-088 GEN
Solar/Wind Harmer
0.46
339216AC1-074 GEN
Solar/Wind Harmer
0.274
3429241JKCT 3G
Adder
16.894
276903AD2-071 C
Solar/Wind Harmer
10.574
25326309TAIT D
Adder
1.481
24385905FR-11G C
Solar/Wind Harmer
0.002
970245AG2-165 GEN
Solar/Wind Harmer
4.056
962241AG1-070 GEN
Solar/Wind Harmer
5.098
965911AG1-460 GEN
Solar/Wind Harmer
1.861
247536S-71 GEN
Solar/Wind Harmer
0.374
276615X2-022 GEN
Solar/Wind Harmer
0.098
963831AG1-236 GEN
Solar/Wind Harmer
3.623
958381AF2-132 GEN
Solar/Wind Harmer
0.001
939401AE1-172 GEN
Solar/Wind Harmer
6.864
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
274766LEE CO EC;7U
Adder
12.032
238117U2-030
Solar/Wind Helper
0.343
20088826HIGHLAND
Solar/Wind Helper
1.011
964391AG1-301 GEN
Solar/Wind Helper
0.529
961331AF2-424 GEN
Solar/Wind Helper
0.499
963161AG1-165 GEN
Solar/Wind Helper
0.496
20676728BRNX1-095
Solar/Wind Helper
0.032
217169METRODIV C
Solar/Wind Helper
0.004
20720528MAN_W1-024
Solar/Wind Helper
0.03
219276PARKLANDSO C
Solar/Wind Helper
0.095
234015AF2-250 C
Solar/Wind Helper
0.039
235067AD1-061 GEN
Solar/Wind Helper
0.433
971313AH1-133 GEN
Solar/Wind Harmer
10.378
270367AC2-061_GEN
Solar/Wind Harmer
0.008
970879AG2-548 GEN
Solar/Wind Harmer
9.191
25196108MFTGT2
Adder
2.193
25196108MFTGT2
Adder
2.036
25196408WSDLE3
Adder
12.579
25196308WSDLE2
Adder
12.47
25196208WSDLE1
Adder
12.439
25196708WSDLE6
Adder
12.407
270132AB1-180 C
Adder
0.17
965411AG1-406 GEN
Solar/Wind Harmer
3.552
971061AG2-657 GEN
Solar/Wind Harmer
6.031
270240V3-007_GEN2
Solar/Wind Harmer
0.003
270594AE1-207 GEN
Solar/Wind Harmer
10.572
971673AH1-337 GEN
Solar/Wind Harmer
6.118
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.002
24691005MDL-2G C
Solar/Wind Harmer
0.002
270543AE2-219 C
Solar/Wind Harmer
0.006
276174W4-005 GEN2
Solar/Wind Harmer
0.001
24729505KEY G4
Adder
8.586
274863CRW1-WTG
Solar/Wind Harmer
0.003
274864CRW2-WTG
Solar/Wind Harmer
0.003
957751AF2-069 GEN
Solar/Wind Harmer
0.302
238126S14_GEN_1
Solar/Wind Helper
0.81
941231AE2-117 GEN
Solar/Wind Helper
0.53
964051AG1-259 GEN
Solar/Wind Helper
0.075
964061AG1-260 GEN
Solar/Wind Helper
0.075
209116AE2-175 GEN
Solar/Wind Helper
1.966
20675728RH_W2-091
Solar/Wind Helper
0.149
207484AF2-139 C O1
Solar/Wind Helper
0.092
20675928HOL_W4-097
Solar/Wind Helper
0.055
219272CLEANLIGHT C
Solar/Wind Helper
0.027
228754AB1-001 C
Solar/Wind Helper
0.027
237085AD2-009_GEN
Solar/Wind Helper
1.449
957141AF2-008_MTX
Adder
81.782
944201AF1-088_MTX
Adder
163.563
CBM South 1LTFEXP_CBM-S1->PJM
CBM
48.581
WECLTFEXP_WEC->PJM
CLTF
5.002
LAGNLTFEXP_LAGN->PJM
CLTF
24.864
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.24
CPLELTFEXP_CPLE->PJM
CLTF
6.557
SIGELTFEXP_SIGE->PJM
CLTF
0.729
CBM West 1LTFEXP_CBM-W1->PJM
CBM
170.264
NYPJM->LTFIMP_NY
CLTF
6.276
TVALTFEXP_TVA->PJM
CLTF
12.63
AG2-052LTFEXP_AG2-052->PJM
LTF
0.306
CBM West 2LTFEXP_CBM-W2->PJM
CBM
173.156
LGEELTFEXP_LGEE->PJM
CLTF
9.844
MECLTFEXP_MEC->PJM
CLTF
21.939
AH1-155LTFEXP_AH1-155->PJM
LTF
0.459

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7445_05MARYSV 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.05 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6243.53
MW Contribution:25.36
Bus #Bus NameTypeMW Contribution
24721805FLATG3
50/50
3.32
24721705FLATG2
50/50
60.871
243186AF1-051 GEN
50/50
14.281
970155AG2-107 GEN
Solar/Wind Harmer
40.072
24723205RIVRG3
Adder
37.861
24686105CER G3
Adder
16.176
970947AG2-589 GEN
Solar/Wind Harmer
3.533
24735205WLF2G2
Adder
8.16
270336AE1-100 GEN
Solar/Wind Harmer
2.043
971367AH1-164 GEN
Solar/Wind Harmer
3.994
971821AH1-427 GEN
Solar/Wind Harmer
11.315
943811AF1-049 GEN
Solar/Wind Harmer
4.273
339241AF1-083 GEN
Solar/Wind Harmer
1.864
964901AG1-354 GEN
Solar/Wind Harmer
16.766
943111AE2-339 GEN
Solar/Wind Harmer
0.969
945681AF1-233 GEN
Solar/Wind Harmer
20.401
24289405MTG1
50/50
12.693
970149AG2-104 GEN
Solar/Wind Harmer
113.494
971403AH1-188 GEN
Solar/Wind Harmer
25.361
960001AF2-291 GEN
Solar/Wind Harmer
5.186
971329AH1-144 GEN
Solar/Wind Harmer
16.634
927014AC1-188 GEN
Solar/Wind Harmer
2.118
970091AG2-072 GEN
Adder
90.557
970273AG2-179 GEN
Solar/Wind Harmer
2.784
971565AH1-281 GEN
Solar/Wind Harmer
2.213
3429421JKCT 10G
Adder
9.194
963741AG1-226 GEN
Solar/Wind Harmer
43.173
274822ROCKFORD ;11
Adder
17.664
235054AD2-180 GEN
Solar/Wind Helper
1.542
23562501BACKB
Solar/Wind Helper
0.81
962761AG1-125 GEN
Solar/Wind Harmer
91.898
24686505CER G6
Adder
16.155
24728305BUCHG2
Adder
7.204
3429241JKCT 3G
Adder
13.209
962241AG1-070 GEN
Solar/Wind Harmer
5.006
339216AC1-074 GEN
Solar/Wind Harmer
1.819
270018AE2-047 C O1
Solar/Wind Harmer
1.277
252507AC2-088 GEN
Solar/Wind Harmer
1.836
965911AG1-460 GEN
Solar/Wind Harmer
1.345
276615X2-022 GEN
Solar/Wind Harmer
1.868
274766LEE CO EC;7U
Adder
8.327
972235AH1-702 GEN1
Adder
2.27
963831AG1-236 GEN
Solar/Wind Harmer
2.691
944971AF1-162 GEN
Solar/Wind Harmer
12.689
24728205BUCHG1
Adder
7.204
971277AH1-098 GEN
Solar/Wind Harmer
5.729
966021AG1-471 GEN
Solar/Wind Harmer
6.166
339231AF1-038_GEN
Solar/Wind Harmer
2.069
971073AG2-665 GEN
Solar/Wind Harmer
6.915
971073AG2-665 GEN
Solar/Wind Harmer
4.825
339255AE2-071 GEN
Solar/Wind Harmer
1.185
970653AG2-424 GEN
Solar/Wind Harmer
5.35
970653AG2-424 GEN
Solar/Wind Harmer
1.934
964571AG1-320 GEN
Solar/Wind Harmer
9.018
972045AH1-571 GEN
Solar/Wind Harmer
2.195
339221AD2-048_GEN
Solar/Wind Harmer
1.68
252509AD1-136 GEN
Solar/Wind Harmer
0.262
25183208HLCRTG
Solar/Wind Harmer
5.931
25194508D.CRK3
Adder
1.38
276911AD2-131_GEN
Solar/Wind Harmer
4.104
24728805RICHG1
Adder
3.448
274765LEE CO EC;6U
Adder
8.446
274763LEE CO EC;4U
Adder
8.346
274695ROCKY RD ;2P
Adder
9.908
24289405MTG1
50/50
12.693
24686405CER G5
Adder
16.028
270053AF1-130 C
Solar/Wind Harmer
6.738
970913AG2-568 GEN
Solar/Wind Harmer
13.608
970273AG2-179 GEN
Solar/Wind Harmer
4.447
339250AF1-203 GEN
Solar/Wind Harmer
0.677
962251AG1-071 GEN
Solar/Wind Harmer
6.119
270173AC1-122 GEN
Solar/Wind Harmer
1.562
270399AC1-101 GEN
Solar/Wind Harmer
7.605
270330AC1-082 GEN2
Solar/Wind Harmer
1.366
972143AH1-644 GEN
Solar/Wind Harmer
15.505
24686205CER G4
Adder
16.091
971461AH1-227 GEN
Solar/Wind Harmer
7.917
270346AE1-212 GEN
Solar/Wind Harmer
13.484
971331AH1-145 GEN
Solar/Wind Harmer
12.895
247619Y1-049
Adder
0.586
958121AF2-106 GEN
Solar/Wind Harmer
6.061
957541AF2-048 GEN
Solar/Wind Harmer
2.113
970519AG2-331 GEN
Solar/Wind Harmer
20.267
970699AG2-449 GEN
Solar/Wind Harmer
13.407
3429391JKCT 9G
Adder
9.194
958171AF2-111 GEN
Solar/Wind Harmer
25.894
270291AC1-194 GEN
Solar/Wind Harmer
10.843
970193AG2-126 GEN
Solar/Wind Harmer
14.82
25196608WSDLE5
Adder
8.312
24728705AND G3
Adder
7.718
254305AE2-115 C
Solar/Wind Helper
0.199
202652Y1-033 WT C
Solar/Wind Helper
0.509
23750701CROSSCHOOL
Solar/Wind Helper
1.078
20089026BF_G21_K23
Solar/Wind Helper
0.422
270445AC2-157 GEN2
Solar/Wind Harmer
5.954
25194608D.CRK4
Adder
1.604
24728605AND G2
Adder
3.69
274828WAUKEGAN ;BP
Adder
9.834
274682WAUKEGAN ;7U
Adder
15.992
24722005FLATG5
50/50
3.32
24721905FLATG4
50/50
60.871
970153AG2-106 GEN
Solar/Wind Harmer
40.072
960911AF2-382 GEN
Solar/Wind Harmer
12.052
972103AH1-617 GEN
Solar/Wind Harmer
31.009
943031AE2-326 GEN
Solar/Wind Harmer
5.284
270030AE2-140 GEN
Solar/Wind Harmer
23.108
971155AH1-034 GEN
Solar/Wind Harmer
11.167
960741AF2-365 GEN
Solar/Wind Harmer
5.543
25194608D.CRK4
Adder
1.604
24728505AND G1
Adder
3.69
274767LEE CO EC;8U
Adder
8.327
274682WAUKEGAN ;7U
Adder
15.992
235058AG1-386 C
Solar/Wind Helper
0.421
964991AG1-363 GEN
Solar/Wind Helper
3.317
274760LEE CO EC;1U
Adder
8.426
972236AH1-702 GEN2
Adder
1.974
20089126CSLMN_L13
Solar/Wind Helper
0.533
24721605FLATG1
50/50
3.32
24477305BRIDGE
Adder
0.636
957241AF2-018 GEN
Solar/Wind Harmer
8.055
270400AC1-102 GEN
Solar/Wind Harmer
7.605
270329AC1-082 GEN1
Solar/Wind Harmer
0.805
941621AE2-160 GEN
Adder
5.471
24734805WLF1G4
Adder
8.349
24735105WLF2G1
Adder
8.16
3429211JKCT 2G
Adder
13.038
970455AG2-298 GEN
Solar/Wind Harmer
6.646
972163AH1-664 GEN
Solar/Wind Harmer
10.872
339243AC2-075 GEN1
Solar/Wind Harmer
0.493
944221AF1-090 GEN
Solar/Wind Harmer
10.676
25196508WSDLE4
Adder
8.227
963841AG1-237 GEN
Solar/Wind Harmer
10.394
274746AC1-111 G10
Adder
4.954
274731ELWOOD EC;2P
Adder
14.499
274733ELWOOD EC;3P
Adder
10.298
23750501ELLIOTTS
Solar/Wind Helper
0.613
254304AE2-114 C
Solar/Wind Helper
0.199
241982AE2-343 S C
Solar/Wind Helper
0.203
971485AH1-239 GEN
Solar/Wind Harmer
9.113
942891AE2-308 GEN
Solar/Wind Harmer
11.21
971081AG2-670 GEN
Solar/Wind Harmer
8.401
964781AG1-341 GEN
Solar/Wind Harmer
11.836
972043AH1-570 GEN
Solar/Wind Harmer
2.743
945391AF1-204 GEN
Solar/Wind Harmer
13.769
25194408D.CRK1
Adder
7.379
24728905RICHG2
Adder
3.448
972267AH1-718 GEN
Adder
3.785
274764LEE CO EC;5U
Adder
8.446
274683WAUKEGAN ;8U
Adder
18.761
274683WAUKEGAN ;8U
Adder
15.814
274693ROCKY RD ;1P
Adder
9.811
23652301WDPWR_K20
Solar/Wind Helper
0.133
241967AE2-285_GEN
Solar/Wind Helper
0.583
23585401KL_K28_T16
Solar/Wind Helper
1.167
203955AF1-039 C O1
Solar/Wind Helper
0.335
962771AG1-126 GEN
Solar/Wind Harmer
91.898
972203AH1-686 GEN
Adder
4.552
970281AG2-184 GEN
Solar/Wind Harmer
32.56
962211AG1-066 GEN
Solar/Wind Harmer
3.499
252524AE2-267 GEN
Solar/Wind Harmer
1.53
274744AC1-111 GEN8
Adder
4.954
241997AF1-093 GEN
Solar/Wind Helper
0.233
274745AC1-111 GEN9
Adder
4.954
241966AE1-183 GEN
Solar/Wind Helper
0.233
238185AF2-356 C
Solar/Wind Helper
1.986
243186AF1-051 GEN
50/50
14.281
24723005RIVRG1
Adder
37.861
24723105RIVRG2
Adder
37.861
24685805CER G1
Adder
16.07
24685905CER G2
Adder
16.07
971225AH1-072 GEN
Solar/Wind Harmer
3.087
971227AH1-073 GEN
Solar/Wind Harmer
3.087
270214AC2-123 GEN
Solar/Wind Harmer
3.357
270583AD2-179 GEN
Solar/Wind Harmer
13.373
971125AH1-004 GEN
Solar/Wind Harmer
4.377
270444AC2-157 GEN1
Solar/Wind Harmer
5.954
252519AF1-045_GEN
Solar/Wind Harmer
5.968
252516AE2-318_GEN
Solar/Wind Harmer
4.552
276916AD2-100_GEN
Solar/Wind Harmer
20.308
957381AF2-032 GEN
Solar/Wind Harmer
0.403
276763AC1-053 GEN1
Solar/Wind Harmer
3.755
276764AC1-053 GEN2
Solar/Wind Harmer
3.755
241801AE1-079 GEN
Solar/Wind Helper
0.227
971313AH1-133 GEN
Solar/Wind Harmer
15.802
270132AB1-180 C
Adder
0.187
971061AG2-657 GEN
Solar/Wind Harmer
13.568
965411AG1-406 GEN
Solar/Wind Harmer
2.95
970879AG2-548 GEN
Solar/Wind Harmer
4.825
270367AC2-061_GEN
Solar/Wind Harmer
3.448
25196108MFTGT2
Adder
1.552
25196108MFTGT2
Adder
1.441
25196408WSDLE3
Adder
8.556
25196308WSDLE2
Adder
8.482
25196208WSDLE1
Adder
8.46
25196708WSDLE6
Adder
8.439
960161AF2-307 GEN
Solar/Wind Harmer
7.621
970239AG2-162 GEN
Solar/Wind Harmer
12.849
970879AG2-548 GEN
Solar/Wind Harmer
6.915
339236AF1-050_GEN
Solar/Wind Harmer
2.029
970107AG2-081 GEN
Solar/Wind Harmer
3.283
270186AC1-089 GEN
Solar/Wind Harmer
6.681
970235AG2-159 GEN
Solar/Wind Harmer
4.336
970235AG2-159 GEN
Solar/Wind Harmer
2.647
962581AG1-107 GEN
Solar/Wind Harmer
5.324
961491AF2-440 GEN
Solar/Wind Harmer
2.213
970241AG2-163 GEN
Solar/Wind Harmer
23.985
274762LEE CO EC;3U
Adder
8.426
274696ROCKY RD ;4P
Adder
10.143
274697ROCKY RD ;3P
Adder
2.692
962101AG1-054 GEN
Solar/Wind Helper
0.594
241985AE1-237 GEN
Solar/Wind Helper
0.227
944781AF1-143 GEN
Solar/Wind Helper
2.213
24734705WLF1G3
Adder
8.349
24734905WLF1G5
Adder
8.349
966391AG1-508 GEN
Solar/Wind Harmer
4.988
971985AH1-537 GEN
Solar/Wind Harmer
23.222
971981AH1-535 GEN
Solar/Wind Harmer
12.796
270069AE2-166 C O1
Solar/Wind Harmer
3.217
965401AG1-405 GEN
Solar/Wind Harmer
6.573
339211AE2-254 GEN
Solar/Wind Harmer
1.711
972165AH1-665 GEN
Solar/Wind Harmer
8.697
274823ROCKFORD ;21
Adder
17.536
24318705GVG2
50/50
13.293
270331AC1-082 GEN3
Solar/Wind Harmer
0.807
971687AH1-348 GEN
Solar/Wind Harmer
1.543
971315AH1-136 GEN
Solar/Wind Harmer
3.067
970333AG2-219 GEN
Solar/Wind Harmer
36.87
25196008MFTGT1
Adder
1.408
25196808ZIMRHP
Adder
76.262
274761LEE CO EC;2U
Adder
8.426
237046AF1-021 C
Solar/Wind Helper
0.454
254303AC2-168 GEN
Solar/Wind Helper
0.144
23751201ROTHROCK
Solar/Wind Helper
0.666
20089226LOOKOUT
Solar/Wind Helper
0.519
24318705GVG2
50/50
13.293
971191AH1-055 GEN
Solar/Wind Harmer
33.8
970243AG2-164 GEN
Solar/Wind Harmer
30.166
972273AH1-721 GEN
Adder
96.475
970093AG2-073 GEN
Solar/Wind Harmer
11.307
966571AG1-526 GEN
Solar/Wind Harmer
25.008
972167AH1-666 GEN
Solar/Wind Harmer
8.642
25196008MFTGT1
Adder
1.363
252510AF1-249 C
Solar/Wind Harmer
0.411
942481AE2-261 GEN
Solar/Wind Harmer
28.829
962751AG1-124 GEN
Solar/Wind Harmer
8.642
276621W2-048 GEN
Solar/Wind Harmer
5.949
276838X2-022 GEN2
Solar/Wind Harmer
0.222
274729ELWOOD EC;1P
Adder
14.499
237048AF1-022 C
Solar/Wind Helper
0.178
237043AE2-125 C
Solar/Wind Helper
0.164
957141AF2-008_MTX
Adder
61.983
944201AF1-088_MTX
Adder
123.966
CBM South 1LTFEXP_CBM-S1->PJM
CBM
41.73
WECLTFEXP_WEC->PJM
CLTF
3.448
LAGNLTFEXP_LAGN->PJM
CLTF
21.271
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.975
CPLELTFEXP_CPLE->PJM
CLTF
7.658
SIGELTFEXP_SIGE->PJM
CLTF
0.557
CBM West 1LTFEXP_CBM-W1->PJM
CBM
111.704
NYPJM->LTFIMP_NY
CLTF
4.768
TVALTFEXP_TVA->PJM
CLTF
11.116
AG2-052LTFEXP_AG2-052->PJM
LTF
0.206
CBM West 2LTFEXP_CBM-W2->PJM
CBM
139.058
LGEELTFEXP_LGEE->PJM
CLTF
7.621
MECLTFEXP_MEC->PJM
CLTF
16.018
AH1-155LTFEXP_AH1-155->PJM
LTF
0.308

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P4_#17219_05GUERNSEY 765_A_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#17219_05GUERNSEY 765_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.12 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6192.17
MW Contribution:24.25
Bus #Bus NameTypeMW Contribution
24289405MTG1
50/50
11.412
960001AF2-291 GEN
Solar/Wind Harmer
5.284
24686505CER G6
Adder
15.725
962761AG1-125 GEN
Solar/Wind Harmer
55.23
24728305BUCHG2
Adder
6.894
252507AC2-088 GEN
Solar/Wind Harmer
2.628
339216AC1-074 GEN
Solar/Wind Harmer
2.436
3429241JKCT 3G
Adder
17.06
276903AD2-071 C
Solar/Wind Harmer
13.713
25326309TAIT D
Adder
1.497
274766LEE CO EC;7U
Adder
12.16
238117U2-030
Solar/Wind Helper
0.339
20088826HIGHLAND
Solar/Wind Helper
0.998
964391AG1-301 GEN
Solar/Wind Helper
0.522
961331AF2-424 GEN
Solar/Wind Helper
0.491
944971AF1-162 GEN
Solar/Wind Harmer
12.272
24728205BUCHG1
Adder
6.894
971073AG2-665 GEN
Solar/Wind Harmer
9.109
971073AG2-665 GEN
Solar/Wind Harmer
6.355
252509AD1-136 GEN
Solar/Wind Harmer
0.375
339221AD2-048_GEN
Solar/Wind Harmer
2.24
972045AH1-571 GEN
Solar/Wind Harmer
2.91
25183208HLCRTG
Solar/Wind Harmer
8.794
25194508D.CRK3
Adder
2.039
964571AG1-320 GEN
Solar/Wind Harmer
11.509
970653AG2-424 GEN
Solar/Wind Harmer
6.739
970653AG2-424 GEN
Solar/Wind Harmer
2.436
24728805RICHG1
Adder
5.257
24379505HDWTR1G C
Solar/Wind Harmer
10.908
339231AF1-038_GEN
Solar/Wind Harmer
2.495
270383AD1-128 GEN
Solar/Wind Harmer
8.387
25326109MON D
Adder
1.782
274695ROCKY RD ;2P
Adder
14.726
274765LEE CO EC;6U
Adder
12.334
274763LEE CO EC;4U
Adder
12.189
20088926STNY CRK
Solar/Wind Helper
0.916
20088626ARWF_N39
Solar/Wind Helper
1.344
946381AF1-302 GEN
Solar/Wind Helper
0.243
203946AE2-131 C
Solar/Wind Helper
0.522
238217AF1-153 C O1
Solar/Wind Helper
0.259
946751AF1-339 GEN
Solar/Wind Helper
0.493
209029WAYMART-WD
Solar/Wind Helper
0.923
211065PSPA IPP
Solar/Wind Helper
0.165
211065PSPA IPP
Solar/Wind Helper
0.165
20674128FR_U2-059
Solar/Wind Helper
0.004
20671828STAW2-080
Solar/Wind Helper
0.028
207442AE1-156 GEN
Solar/Wind Helper
0.346
20720628TIN_W1-124
Solar/Wind Helper
0.2
233901CHERRYDALE C
Solar/Wind Helper
0.236
234036AF2-325 C
Solar/Wind Helper
0.043
233987AB2-037 GEN
Solar/Wind Helper
2.379
235063AE1-101 C2
Solar/Wind Helper
1.441
237001AB1-127_GEN
Solar/Wind Helper
0.382
237034AC2-136 C
Solar/Wind Helper
0.191
24686205CER G4
Adder
15.663
957541AF2-048 GEN
Solar/Wind Harmer
2.51
971461AH1-227 GEN
Solar/Wind Harmer
7.904
970519AG2-331 GEN
Solar/Wind Harmer
25.969
970699AG2-449 GEN
Solar/Wind Harmer
17.18
958171AF2-111 GEN
Solar/Wind Harmer
36.367
25196608WSDLE5
Adder
12.34
3429391JKCT 9G
Adder
11.981
253406AD2-031_GEN
Solar/Wind Harmer
1.826
270291AC1-194 GEN
Solar/Wind Harmer
15.077
253415AE1-040 GEN
Solar/Wind Harmer
1.598
270273AD2-016 GEN
Solar/Wind Harmer
3.717
24728705AND G3
Adder
11.134
970193AG2-126 GEN
Solar/Wind Harmer
20.711
270437AC2-090 C
Solar/Wind Harmer
7.702
270346AE1-212 GEN
Solar/Wind Harmer
12.393
958821AF2-173 GEN
Solar/Wind Harmer
19.143
23750701CROSSCHOOL
Solar/Wind Helper
1.41
202652Y1-033 WT C
Solar/Wind Helper
0.647
20089026BF_G21_K23
Solar/Wind Helper
0.534
238127S14_GEN_2
Solar/Wind Helper
0.8
254305AE2-115 C
Solar/Wind Helper
0.235
238202AE2-262_GEN
Solar/Wind Helper
1.048
941421AE2-139 GEN
Solar/Wind Helper
2.537
209071AE2-133 GEN
Solar/Wind Helper
0.089
212266LOR1
Solar/Wind Helper
0.053
207518AF1-320_GEN
Solar/Wind Helper
1.692
20675428EAM_W2-061
Solar/Wind Helper
0.017
20715228NPK_W1-113
Solar/Wind Helper
0.082
207454AA2-184 E
Solar/Wind Helper
0.327
963711AG1-223 GEN
Solar/Wind Helper
0.067
218660EHAMPSOLAR C
Solar/Wind Helper
0.034
228728W1-130C
Solar/Wind Helper
0.056
233972AC1-094 C
Solar/Wind Helper
0.308
233950AC2-186 GEN
Solar/Wind Helper
0.118
233998TM1NIN_3.36
Solar/Wind Helper
0.266
232404W1-003 C
Solar/Wind Helper
0.516
232428Y3-058 C
Solar/Wind Helper
0.344
233915AB1-141 GEN
Solar/Wind Helper
0.51
235062AE1-101 C1
Solar/Wind Helper
1.441
223401AF1-299 GEN
Solar/Wind Helper
0.332
24722005FLATG5
50/50
2.772
24721905FLATG4
50/50
50.82
970153AG2-106 GEN
Solar/Wind Harmer
24.083
972103AH1-617 GEN
Solar/Wind Harmer
31.576
960911AF2-382 GEN
Solar/Wind Harmer
11.622
25194608D.CRK4
Adder
2.371
253316AC1-085 GEN3
Solar/Wind Harmer
12.008
253433AC1-085 GEN1
Solar/Wind Harmer
7.622
946181AF1-283 GEN
Solar/Wind Harmer
18.636
24728505AND G1
Adder
5.324
253303V4-073 C
Solar/Wind Harmer
0.16
253370AE2-315 SEC1
Adder
2.761
253371AE2-315 SEC2
Adder
2.611
960741AF2-365 GEN
Solar/Wind Harmer
6.85
247642Z2-115 C
Solar/Wind Harmer
0.088
970289AG2-191 GEN
Solar/Wind Harmer
1.05
970291AG2-192 GEN
Solar/Wind Harmer
0.954
274767LEE CO EC;8U
Adder
12.16
235058AG1-386 C
Solar/Wind Helper
0.508
964991AG1-363 GEN
Solar/Wind Helper
4.361
203818AF1-086 GEN
Solar/Wind Helper
1.862
200917MEHOOPANY_G
Solar/Wind Helper
2.394
316097T157 G90
Solar/Wind Helper
1.137
203830AF1-094 GEN
Solar/Wind Helper
0.488
217208PARK ELE C
Solar/Wind Helper
0.005
205941AD2-115 GEN
Solar/Wind Helper
0.524
20742028HF_AC1-207
Solar/Wind Helper
0.148
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20714828MDF_W3-079
Solar/Wind Helper
0.137
20720728JCB_W1-129
Solar/Wind Helper
0.06
219904AC1-010 C
Solar/Wind Helper
0.063
232434Z2-077 GEN
Solar/Wind Helper
0.129
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
232422X3-066 FULL
Solar/Wind Helper
0.116
966131AG1-482 GEN
Solar/Wind Helper
0.077
237080AD1-060 GEN
Solar/Wind Helper
0.292
24289405MTG1
50/50
11.412
24686405CER G5
Adder
15.601
270053AF1-130 C
Solar/Wind Harmer
6.517
970913AG2-568 GEN
Solar/Wind Harmer
12.681
972173AH1-669 GEN
Solar/Wind Harmer
7.011
270222AC2-111 GEN
Solar/Wind Harmer
11.397
270356AE2-297 GEN
Solar/Wind Harmer
6.354
970273AG2-179 GEN
Solar/Wind Harmer
5.36
270004AE1-209 GEN
Solar/Wind Harmer
7.473
274760LEE CO EC;1U
Adder
12.305
238118U2-030_1
Solar/Wind Helper
0.339
20089126CSLMN_L13
Solar/Wind Helper
0.675
203854AF2-039 C
Solar/Wind Helper
0.349
20334926Z1-069 C
Solar/Wind Helper
1.47
959441AF2-235 GEN
Solar/Wind Helper
0.252
212507AE2-042_GEN
Solar/Wind Helper
1.746
961341AF2-425 GEN
Solar/Wind Helper
0.491
961301AF2-421 GEN
Solar/Wind Helper
0.489
963151AG1-164 GEN
Solar/Wind Helper
0.489
207439AE1-081 C O1
Solar/Wind Helper
0.02
20674328GAR_V4-001
Solar/Wind Helper
0.024
217209CENTRL HS C
Solar/Wind Helper
0.009
24721605FLATG1
50/50
2.772
270329AC1-082 GEN1
Solar/Wind Harmer
0.808
957241AF2-018 GEN
Solar/Wind Harmer
7.79
270400AC1-102 GEN
Solar/Wind Harmer
7.37
24477305BRIDGE
Adder
0.593
941621AE2-160 GEN
Adder
5.103
972163AH1-664 GEN
Solar/Wind Harmer
14.744
339243AC2-075 GEN1
Solar/Wind Harmer
0.66
3429211JKCT 2G
Adder
16.839
25196508WSDLE4
Adder
12.214
24734805WLF1G4
Adder
8.278
270340AC2-060 GEN
Solar/Wind Harmer
4.33
24735105WLF2G1
Adder
8.161
970455AG2-298 GEN
Solar/Wind Harmer
8.463
270269AC2-059
Solar/Wind Harmer
12.998
24699105WLD G1 C
Solar/Wind Harmer
5.394
253400AC2-068 GEN
Solar/Wind Harmer
2.745
963841AG1-237 GEN
Solar/Wind Harmer
14.936
274776LINCOLN ;7U
Adder
11.173
274746AC1-111 G10
Adder
7.394
274731ELWOOD EC;2P
Adder
21.74
274733ELWOOD EC;3P
Adder
13.586
23750501ELLIOTTS
Solar/Wind Helper
0.779
254304AE2-114 C
Solar/Wind Helper
0.235
241982AE2-343 S C
Solar/Wind Helper
0.24
203961AE2-224 GEN
Solar/Wind Helper
2.672
959421AF2-233 GEN
Solar/Wind Helper
0.493
20675128HRM_W1-127
Solar/Wind Helper
0.032
972043AH1-570 GEN
Solar/Wind Harmer
3.637
25194408D.CRK1
Adder
10.905
942891AE2-308 GEN
Solar/Wind Harmer
14.408
24728905RICHG2
Adder
5.257
971081AG2-670 GEN
Solar/Wind Harmer
10.358
945391AF1-204 GEN
Solar/Wind Harmer
19.242
926881AC1-175 GEN
Solar/Wind Harmer
7.698
972267AH1-718 GEN
Adder
5.508
274693ROCKY RD ;1P
Adder
14.581
274764LEE CO EC;5U
Adder
12.334
23652301WDPWR_K20
Solar/Wind Helper
0.166
23585401KL_K28_T16
Solar/Wind Helper
1.512
203955AF1-039 C O1
Solar/Wind Helper
0.427
20083426SW_E13_K22
Solar/Wind Helper
0.063
241967AE2-285_GEN
Solar/Wind Helper
0.687
946071AF1-272 GEN
Solar/Wind Helper
3.012
20084626FORWARD
Solar/Wind Helper
0.397
20398826ARMNA MT
Solar/Wind Helper
1.633
209137AF2-361 C
Solar/Wind Helper
1.509
208972BECR K09
Solar/Wind Helper
0.367
966111AG1-480 GEN
Solar/Wind Helper
0.048
20674928WA_W3-044
Solar/Wind Helper
0.106
219615MILLCREEK C
Solar/Wind Helper
0.028
219921AF1-264
Solar/Wind Helper
0.053
203947AF1-006 C
Solar/Wind Helper
0.519
230433AD2-135 GEN
Solar/Wind Helper
0.018
233970AC1-092 C
Solar/Wind Helper
0.356
232424Y1-079 C
Solar/Wind Helper
0.118
237002AB1-128_GEN
Solar/Wind Helper
0.382
23777901MDS_W4-102
Solar/Wind Helper
0.148
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
237006AB1-125 GEN
Solar/Wind Helper
0.107
972203AH1-686 GEN
Adder
4.457
962771AG1-126 GEN
Solar/Wind Harmer
55.23
970281AG2-184 GEN
Solar/Wind Harmer
33.155
962211AG1-066 GEN
Solar/Wind Harmer
3.699
252524AE2-267 GEN
Solar/Wind Harmer
2.271
253372AE2-315 SEC3
Adder
2.611
253372AE2-315 SEC3
Adder
2.611
25306009OHH W.
Adder
3.967
970289AG2-191 GEN
Solar/Wind Harmer
2.598
274744AC1-111 GEN8
Adder
7.394
241997AF1-093 GEN
Solar/Wind Helper
0.277
20091526CHSTN_FL
Solar/Wind Helper
0.646
238109AE1-109 GEN2
Solar/Wind Helper
0.101
238110AE1-109 GEN3
Solar/Wind Helper
0.101
20090526Q36
Solar/Wind Helper
1.152
203993AD2-133_GEN1
Solar/Wind Helper
1.152
203804AE2-113_GEN
Solar/Wind Helper
1.898
207408W3-077 C
Solar/Wind Helper
0.09
203975AE1-071-GEN
Solar/Wind Helper
2.635
20674828DL_W4-046
Solar/Wind Helper
0.008
966261AG1-495 GEN
Solar/Wind Helper
0.087
959381AF2-229 GEN
Solar/Wind Helper
0.359
234033AF1-007_GEN
Solar/Wind Helper
7.137
232432Z2-076 GEN
Solar/Wind Helper
0.068
205932AD2-116_GEN
Solar/Wind Helper
0.516
960921AF2-383 GEN
Solar/Wind Helper
0.183
243186AF1-051 GEN
50/50
12.549
24721805FLATG3
50/50
2.772
24721705FLATG2
50/50
50.82
24723205RIVRG3
Adder
36.284
24686105CER G3
Adder
15.746
970947AG2-589 GEN
Solar/Wind Harmer
3.567
970155AG2-107 GEN
Solar/Wind Harmer
24.083
945681AF1-233 GEN
Solar/Wind Harmer
27.78
943111AE2-339 GEN
Solar/Wind Harmer
1.275
25194608D.CRK4
Adder
2.371
253432AC1-085 GEN2
Solar/Wind Harmer
0.384
946171AF1-282 GEN
Solar/Wind Harmer
14.335
270445AC2-157 GEN2
Solar/Wind Harmer
7.934
971821AH1-427 GEN
Solar/Wind Harmer
14.167
24735205WLF2G2
Adder
8.161
24728605AND G2
Adder
5.324
339241AF1-083 GEN
Solar/Wind Harmer
2.303
253370AE2-315 SEC1
Adder
2.761
253371AE2-315 SEC2
Adder
2.611
970291AG2-192 GEN
Solar/Wind Harmer
1.778
965031AG1-367 GEN
Solar/Wind Harmer
13.674
964901AG1-354 GEN
Solar/Wind Harmer
20.475
960071AF2-298 GEN
Solar/Wind Harmer
6.807
274745AC1-111 GEN9
Adder
7.394
238185AF2-356 C
Solar/Wind Helper
2.581
241966AE1-183 GEN
Solar/Wind Helper
0.277
23751101LEADS_P59
Solar/Wind Helper
1.464
964201AG1-281 GEN
Solar/Wind Helper
0.537
238206AE2-263_GEN
Solar/Wind Helper
0.997
959471AF2-238 GEN
Solar/Wind Helper
0.51
203860AG1-193 C
Solar/Wind Helper
0.25
209067AE2-060 GEN
Solar/Wind Helper
0.09
963071AG1-156 GEN
Solar/Wind Helper
1.601
316095T157 G97
Solar/Wind Helper
1.137
203835AF1-098 GEN
Solar/Wind Helper
1.929
20674628WNG_W3-110
Solar/Wind Helper
0.096
219919AE1-041 FULL
Solar/Wind Helper
0.004
218438BLK ROCK C
Solar/Wind Helper
0.029
20714528FRN_Y2-051
Solar/Wind Helper
0.06
20720828JCB_W4-025
Solar/Wind Helper
0.066
219906AC1-017 C
Solar/Wind Helper
0.043
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219291REEVESSOUT C
Solar/Wind Helper
0.012
219912AD2-042 GEN
Solar/Wind Helper
0.155
219766PARADISE C
Solar/Wind Helper
0.057
230415AB2-049 C
Solar/Wind Helper
0.031
230430AE1-229_GEN
Solar/Wind Helper
3.487
233996TM1833_GEN
Solar/Wind Helper
0.266
232406W1-004 FULL
Solar/Wind Helper
0.516
237030AB1-096 C
Solar/Wind Helper
0.062
243186AF1-051 GEN
50/50
12.549
24723005RIVRG1
Adder
36.284
24723105RIVRG2
Adder
36.284
24685805CER G1
Adder
15.642
24685905CER G2
Adder
15.642
971225AH1-072 GEN
Solar/Wind Harmer
3.081
971227AH1-073 GEN
Solar/Wind Harmer
3.081
252519AF1-045_GEN
Solar/Wind Harmer
8.799
252516AE2-318_GEN
Solar/Wind Harmer
6.712
971125AH1-004 GEN
Solar/Wind Harmer
5.778
253317AC1-085 GEN4
Solar/Wind Harmer
12.008
270444AC2-157 GEN1
Solar/Wind Harmer
7.934
253370AE2-315 SEC1
Adder
2.761
25322209TAIT E
Adder
13.324
25322209TAIT E
Adder
13.025
247621Y3-024
Adder
0.324
238120AE2-309 GEN
Solar/Wind Helper
0.501
241801AE1-079 GEN
Solar/Wind Helper
0.267
20303426NA_O38_P22
Solar/Wind Helper
1.102
203853AF1-134 C O1
Solar/Wind Helper
0.526
203952AE2-129 C
Solar/Wind Helper
0.521
209054AE2-059 GEN
Solar/Wind Helper
0.089
203979AG1-198 GEN
Solar/Wind Helper
0.292
203980AG1-197 GEN
Solar/Wind Helper
0.363
964851AG1-348 GEN
Solar/Wind Helper
0.087
217204WCALDSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.003
218440SUMMTASSOC C
Solar/Wind Helper
0.017
20714928UPF_X1-085
Solar/Wind Helper
0.005
230407AD2-065 C
Solar/Wind Helper
0.042
237025AB1-124 C
Solar/Wind Helper
0.143
23777801MSM_W1-116
Solar/Wind Helper
0.098
238169AE2-226 GEN1
Solar/Wind Helper
0.546
238170AE2-226 GEN2
Solar/Wind Helper
0.546
971313AH1-133 GEN
Solar/Wind Harmer
15.015
270367AC2-061_GEN
Solar/Wind Harmer
4.764
970879AG2-548 GEN
Solar/Wind Harmer
6.355
25196108MFTGT2
Adder
2.214
25196108MFTGT2
Adder
2.056
25196408WSDLE3
Adder
12.703
25196308WSDLE2
Adder
12.592
25196208WSDLE1
Adder
12.561
25196708WSDLE6
Adder
12.529
270132AB1-180 C
Adder
0.172
965411AG1-406 GEN
Solar/Wind Harmer
3.588
971061AG2-657 GEN
Solar/Wind Harmer
12.476
270240V3-007_GEN2
Solar/Wind Harmer
8.534
965461AG1-414 GEN
Solar/Wind Harmer
3.101
270594AE1-207 GEN
Solar/Wind Harmer
20.092
24729505KEY G4
Adder
8.677
238126S14_GEN_1
Solar/Wind Helper
0.8
941231AE2-117 GEN
Solar/Wind Helper
0.523
970239AG2-162 GEN
Solar/Wind Harmer
16.464
270186AC1-089 GEN
Solar/Wind Harmer
9.145
962581AG1-107 GEN
Solar/Wind Harmer
7.495
961491AF2-440 GEN
Solar/Wind Harmer
3.115
960161AF2-307 GEN
Solar/Wind Harmer
9.531
970879AG2-548 GEN
Solar/Wind Harmer
9.109
970235AG2-159 GEN
Solar/Wind Harmer
5.797
970235AG2-159 GEN
Solar/Wind Harmer
3.539
970107AG2-081 GEN
Solar/Wind Harmer
4.333
253394AE2-221_GEN
Solar/Wind Harmer
6.433
253398AE2-221_GEN2
Solar/Wind Harmer
6.433
270209AC1-174_GEN
Solar/Wind Harmer
7.698
339236AF1-050_GEN
Solar/Wind Harmer
2.488
970241AG2-163 GEN
Solar/Wind Harmer
34.243
274770LINCOLN ;1U
Adder
11.173
274771LINCOLN ;2U
Adder
11.173
972259AH1-714 GEN
Adder
25.243
274696ROCKY RD ;4P
Adder
15.074
274697ROCKY RD ;3P
Adder
4
274762LEE CO EC;3U
Adder
12.305
944781AF1-143 GEN
Solar/Wind Helper
2.801
962101AG1-054 GEN
Solar/Wind Helper
0.706
241985AE1-237 GEN
Solar/Wind Helper
0.267
203940AF1-140 C
Solar/Wind Helper
0.44
961431AF2-434 GEN
Solar/Wind Helper
0.491
20676228FRD_X1-012
Solar/Wind Helper
0.099
207471AF2-354 C
Solar/Wind Helper
0.181
217081WEATEXAS C
Solar/Wind Helper
0.013
20676128MHD_W3-029
Solar/Wind Helper
0.102
20673828FLE_V3-070
Solar/Wind Helper
0.096
20716928W4-060COL
Solar/Wind Helper
0.054
963391AG1-188 GEN
Solar/Wind Helper
0.086
963401AG1-189 GEN
Solar/Wind Helper
0.059
20390526W1-045 C
Solar/Wind Helper
0.351
233939AC1-091 C
Solar/Wind Helper
0.356
232408W1-005 C
Solar/Wind Helper
0.516
232410W1-006 C
Solar/Wind Helper
0.516
233946AB2-136 GEN
Solar/Wind Helper
0.577
233944AB2-135 GEN
Solar/Wind Helper
0.598
233933AB2-153 GEN
Solar/Wind Helper
0.236
205916AD1-020 GEN
Solar/Wind Helper
1.685
235020AA1-095 C
Solar/Wind Helper
0.044
238175AF1-290_GEN
Solar/Wind Helper
0.121
970825AG2-519 GEN
Solar/Wind Harmer
8.555
270330AC1-082 GEN2
Solar/Wind Harmer
1.373
270399AC1-101 GEN
Solar/Wind Harmer
7.37
972143AH1-644 GEN
Solar/Wind Harmer
15.788
971985AH1-537 GEN
Solar/Wind Harmer
28.159
972165AH1-665 GEN
Solar/Wind Harmer
11.796
24734705WLF1G3
Adder
8.278
24734905WLF1G5
Adder
8.278
339211AE2-254 GEN
Solar/Wind Harmer
2.15
965401AG1-405 GEN
Solar/Wind Harmer
7.994
944031AF1-071 GEN
Solar/Wind Harmer
1.405
24725505WLD G2 C
Solar/Wind Harmer
5.459
253349AC2-067 GEN
Solar/Wind Harmer
6.826
274775LINCOLN ;6U
Adder
11.173
274777LINCOLN ;8U
Adder
11.173
20092526R32
Solar/Wind Helper
1.294
203846AF2-130 C
Solar/Wind Helper
0.491
203855AF2-088 C
Solar/Wind Helper
0.168
959431AF2-234 GEN
Solar/Wind Helper
0.986
961261AF2-417 GEN
Solar/Wind Helper
0.488
238208AF1-136 C
Solar/Wind Helper
0.189
20676328BVR_Y1-020
Solar/Wind Helper
0.029
218526CNTRALGAS2 C
Solar/Wind Helper
0.17
219620RIDERU C
Solar/Wind Helper
0.001
207459AE1-142 C O1
Solar/Wind Helper
0.304
20715828PEM_W1-120
Solar/Wind Helper
0.1
214067T20SOLAR
Solar/Wind Helper
0.012
219688LUMSOLAR_S C
Solar/Wind Helper
0.041
227927V4-067C
Solar/Wind Helper
0.011
964001AG1-254 GEN
Solar/Wind Helper
0.988
233990AG1-397 GEN
Solar/Wind Helper
0.031
205943AE1-185 GEN
Solar/Wind Helper
0.515
207530AG1-191 GEN
Solar/Wind Helper
0.071
218524CNTRALGAS1 C
Solar/Wind Helper
0.17
20675528CPH_W2-050
Solar/Wind Helper
0.092
20715728PEM_W1-119
Solar/Wind Helper
0.1
219607WPEMNERT C
Solar/Wind Helper
0.083
219914AD2-027 C
Solar/Wind Helper
0.119
233923SMA
Solar/Wind Helper
0.974
205956AE1-196_GEN
Solar/Wind Helper
0.516
232436AB1-176 C
Solar/Wind Helper
0.045
233935AB2-179 C
Solar/Wind Helper
1.288
971403AH1-188 GEN
Solar/Wind Harmer
24.255
970149AG2-104 GEN
Solar/Wind Harmer
68.21
927014AC1-188 GEN
Solar/Wind Harmer
2.517
970091AG2-072 GEN
Adder
114.655
3429421JKCT 10G
Adder
11.981
270263AC1-001 GEN
Solar/Wind Harmer
1.49
971565AH1-281 GEN
Solar/Wind Harmer
2.835
970273AG2-179 GEN
Solar/Wind Harmer
3.356
963741AG1-226 GEN
Solar/Wind Harmer
61.637
235054AD2-180 GEN
Solar/Wind Helper
2.007
23562501BACKB
Solar/Wind Helper
1.057
235531U2-073 GEN
Solar/Wind Helper
3.19
20094526CT_V3-030
Solar/Wind Helper
0.523
238108AE1-109 GEN1
Solar/Wind Helper
0.101
203954AE2-126 C
Solar/Wind Helper
0.514
957921AF2-086 GEN
Solar/Wind Helper
0.486
217211CAMDEN ST C
Solar/Wind Helper
0.005
219249CENTRALDIV C
Solar/Wind Helper
0.011
20715028HAN_X4-015
Solar/Wind Helper
0.06
959561AF2-247 GEN
Solar/Wind Helper
0.022
219348LDSOLAR C
Solar/Wind Helper
0.119
228729W2-030 C
Solar/Wind Helper
0.114
233971AC1-093 C
Solar/Wind Helper
0.364
233994AC2-023 GEN
Solar/Wind Helper
0.977
233997TMININ_4.2
Solar/Wind Helper
0.266
233918AB1-142 GEN
Solar/Wind Helper
0.51
205917AD1-020 ES
Solar/Wind Helper
0.362
963161AG1-165 GEN
Solar/Wind Helper
0.489
20676728BRNX1-095
Solar/Wind Helper
0.032
217169METRODIV C
Solar/Wind Helper
0.004
20720528MAN_W1-024
Solar/Wind Helper
0.03
219276PARKLANDSO C
Solar/Wind Helper
0.094
234015AF2-250 C
Solar/Wind Helper
0.039
235067AD1-061 GEN
Solar/Wind Helper
0.427
24318705GVG2
50/50
11.681
270331AC1-082 GEN3
Solar/Wind Harmer
0.811
971315AH1-136 GEN
Solar/Wind Harmer
3.227
971687AH1-348 GEN
Solar/Wind Harmer
1.543
970333AG2-219 GEN
Solar/Wind Harmer
47.244
25196808ZIMRHP
Adder
110.178
25196008MFTGT1
Adder
2.009
942081AE2-220 GEN
Solar/Wind Harmer
8.819
270239V3-007_GEN1
Solar/Wind Harmer
2.374
270005AE1-210 C O1
Solar/Wind Harmer
7.473
270032AE2-172
Solar/Wind Harmer
6.358
274773LINCOLN ;4U
Adder
11.173
274774LINCOLN ;5U
Adder
11.173
274761LEE CO EC;2U
Adder
12.305
237046AF1-021 C
Solar/Wind Helper
0.57
23751201ROTHROCK
Solar/Wind Helper
0.868
20089226LOOKOUT
Solar/Wind Helper
0.657
254303AC2-168 GEN
Solar/Wind Helper
0.171
946691AF1-333 GEN
Solar/Wind Helper
0.493
946741AF1-338 GEN
Solar/Wind Helper
0.493
961421AF2-433 GEN
Solar/Wind Helper
0.491
209027LOR2_Q27
Solar/Wind Helper
1.148
23583801GRNGAP
Solar/Wind Helper
4.22
961971AG1-040 GEN
Solar/Wind Helper
0.485
207510AF2-138 C
Solar/Wind Helper
0.087
20673728F2S_V4-070
Solar/Wind Helper
0.032
219908AB1-139 C
Solar/Wind Helper
0.078
219612MATRIX C
Solar/Wind Helper
0.025
20716028EGP_W2-019
Solar/Wind Helper
0.019
219623KINSLEYBEA C
Solar/Wind Helper
0.002
233952AC2-187 GEN
Solar/Wind Helper
0.236
233940AF2-379 C
Solar/Wind Helper
0.063
233982AB2-133 GEN
Solar/Wind Helper
0.363
238221AF1-254 C O1
Solar/Wind Helper
0.232
223402AF1-300 C
Solar/Wind Helper
0.332
970825AG2-519 GEN
Solar/Wind Harmer
1.909
964051AG1-259 GEN
Solar/Wind Helper
0.074
964061AG1-260 GEN
Solar/Wind Helper
0.074
209116AE2-175 GEN
Solar/Wind Helper
1.938
20675728RH_W2-091
Solar/Wind Helper
0.147
207484AF2-139 C O1
Solar/Wind Helper
0.09
20675928HOL_W4-097
Solar/Wind Helper
0.054
219272CLEANLIGHT C
Solar/Wind Helper
0.026
228754AB1-001 C
Solar/Wind Helper
0.027
237085AD2-009_GEN
Solar/Wind Helper
1.427
20676428JCR_X2-075
Solar/Wind Helper
0.072
962511AG1-100 GEN
Solar/Wind Helper
0.481
207445AB1-138_GEN
Solar/Wind Helper
0.109
219304NAMERICA C
Solar/Wind Helper
0.137
219686LUMSOLAR_N C
Solar/Wind Helper
0.041
237038AE2-054 C
Solar/Wind Helper
0.234
23779801AA1-109
Solar/Wind Helper
0.165
24318705GVG2
50/50
11.681
971191AH1-055 GEN
Solar/Wind Harmer
37.171
970243AG2-164 GEN
Solar/Wind Harmer
38.654
972167AH1-666 GEN
Solar/Wind Harmer
11.786
252510AF1-249 C
Solar/Wind Harmer
0.604
25196008MFTGT1
Adder
1.945
970093AG2-073 GEN
Solar/Wind Harmer
14.372
966571AG1-526 GEN
Solar/Wind Harmer
31.649
972273AH1-721 GEN
Adder
115.895
274772LINCOLN ;3U
Adder
11.173
274729ELWOOD EC;1P
Adder
21.74
237048AF1-022 C
Solar/Wind Helper
0.225
237043AE2-125 C
Solar/Wind Helper
0.205
946731AF1-337 GEN
Solar/Wind Helper
0.493
20671928W4-073
Solar/Wind Helper
0.097
207437AD2-070 GEN
Solar/Wind Helper
0.148
20675828AU_W4-064
Solar/Wind Helper
0.032
207528AF2-192 GEN
Solar/Wind Helper
0.081
20673628F1S_V4-069
Solar/Wind Helper
0.032
217213AMBOY SO C
Solar/Wind Helper
0.03
218428ETC SOLAR C
Solar/Wind Helper
0.005
219907AC1-030 C
Solar/Wind Helper
0.035
219258KINSLEYDEP C
Solar/Wind Helper
0.079
230434AG1-499 GEN
Solar/Wind Helper
0.238
230511AF1-262
Solar/Wind Helper
0.015
233954AC2-188 GEN
Solar/Wind Helper
0.236
233930AB2-032 GEN
Solar/Wind Helper
0.387
957141AF2-008_MTX
Adder
82.596
944201AF1-088_MTX
Adder
165.192
CBM West 1LTFEXP_CBM-W1->PJM
CBM
172.314
NYPJM->LTFIMP_NY
CLTF
6.186
TVALTFEXP_TVA->PJM
CLTF
12.772
AG2-052LTFEXP_AG2-052->PJM
LTF
0.309
CBM West 2LTFEXP_CBM-W2->PJM
CBM
175.047
LGEELTFEXP_LGEE->PJM
CLTF
9.94
MECLTFEXP_MEC->PJM
CLTF
22.175
AH1-155LTFEXP_AH1-155->PJM
LTF
0.464
CBM South 1LTFEXP_CBM-S1->PJM
CBM
49.115
WECLTFEXP_WEC->PJM
CLTF
5.055
LAGNLTFEXP_LAGN->PJM
CLTF
25.149
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.665
CPLELTFEXP_CPLE->PJM
CLTF
6.71
SIGELTFEXP_SIGE->PJM
CLTF
0.736

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.86 %
Rating:4558.0 MVA
Rating Type:A
MVA to Mitigate:4961.85
MW Contribution:15.3
Bus #Bus NameTypeMW Contribution
944971AF1-162 GEN
Solar/Wind Harmer
11.031
24728205BUCHG1
Adder
6.221
971277AH1-098 GEN
Solar/Wind Harmer
3.403
971073AG2-665 GEN
Solar/Wind Harmer
7.21
972045AH1-571 GEN
Solar/Wind Harmer
1.602
339221AD2-048_GEN
Solar/Wind Harmer
0.005
966021AG1-471 GEN
Solar/Wind Harmer
4.054
252509AD1-136 GEN
Solar/Wind Harmer
0.038
970653AG2-424 GEN
Solar/Wind Harmer
3.613
970653AG2-424 GEN
Solar/Wind Harmer
1.872
964571AG1-320 GEN
Solar/Wind Harmer
6.819
339255AE2-071 GEN
Solar/Wind Harmer
-0.122
25183208HLCRTG
Solar/Wind Harmer
0.011
25194508D.CRK3
Adder
1.471
24728805RICHG1
Adder
3.669
276911AD2-131_GEN
Solar/Wind Harmer
0.923
243186AF1-051 GEN
50/50
11.679
24721805FLATG3
50/50
2.473
24721705FLATG2
50/50
45.331
24723205RIVRG3
Adder
32.794
24686105CER G3
Adder
14.139
970947AG2-589 GEN
Solar/Wind Harmer
0.368
24735205WLF2G2
Adder
7.162
945681AF1-233 GEN
Solar/Wind Harmer
14.563
971821AH1-427 GEN
Solar/Wind Harmer
7.658
964901AG1-354 GEN
Solar/Wind Harmer
11.154
270445AC2-157 GEN2
Solar/Wind Harmer
0.003
25194608D.CRK4
Adder
1.71
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.086
970155AG2-107 GEN
Solar/Wind Harmer
17.538
270336AE1-100 GEN
Solar/Wind Harmer
0.004
24318705GVG2
50/50
10.872
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
971315AH1-136 GEN
Solar/Wind Harmer
1.928
971687AH1-348 GEN
Solar/Wind Harmer
0.947
970333AG2-219 GEN
Solar/Wind Harmer
5.608
25196808ZIMRHP
Adder
80.408
25196008MFTGT1
Adder
1.465
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0.002
274880W4-005 GEN4
Solar/Wind Harmer
0.001
972175AH1-670 GEN
Solar/Wind Harmer
5.394
270032AE2-172
Solar/Wind Harmer
4.336
270005AE1-210 C O1
Solar/Wind Harmer
1.405
970825AG2-519 GEN
Solar/Wind Harmer
2.296
939741AE1-205 GEN
Solar/Wind Harmer
9.009
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
7.976
276158O29GEN2
Solar/Wind Harmer
0.001
970569AG2-363 GEN
Solar/Wind Harmer
18.972
274761LEE CO EC;2U
Adder
8.432
945371AF1-202 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971997AH1-543 GEN
Solar/Wind Harmer
3.301
237046AF1-021 C
Solar/Wind Helper
0.433
23751201ROTHROCK
Solar/Wind Helper
0.662
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270383AD1-128 GEN
Solar/Wind Harmer
0.004
945421AF1-207 GEN
Solar/Wind Harmer
0.001
960441AF2-335 GEN
Solar/Wind Harmer
6.468
970885AG2-551 GEN
Solar/Wind Harmer
2.125
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
276646AC1-214 GEN2
Solar/Wind Harmer
0.25
270031AE2-169
Solar/Wind Harmer
3.492
274765LEE CO EC;6U
Adder
8.452
274763LEE CO EC;4U
Adder
8.352
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
274695ROCKY RD ;2P
Adder
9.971
24728605AND G2
Adder
3.761
971367AH1-164 GEN
Solar/Wind Harmer
2.344
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
970613AG2-401 GEN
Solar/Wind Harmer
4.849
970291AG2-192 GEN
Solar/Wind Harmer
0.846
965031AG1-367 GEN
Solar/Wind Harmer
6.485
253370AE2-315 SEC1
Adder
1.856
253371AE2-315 SEC2
Adder
1.755
274877BISHOP HL;1U
Solar/Wind Harmer
0.214
960071AF2-298 GEN
Solar/Wind Harmer
3.157
957471AF2-041 GEN
Solar/Wind Harmer
18.878
274828WAUKEGAN ;BP
Adder
9.895
274682WAUKEGAN ;7U
Adder
16.093
274745AC1-111 GEN9
Adder
4.992
238185AF2-356 C
Solar/Wind Helper
1.954
24722005FLATG5
50/50
2.473
24721905FLATG4
50/50
45.331
960911AF2-382 GEN
Solar/Wind Harmer
7.284
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270399AC1-101 GEN
Solar/Wind Harmer
3.444
972143AH1-644 GEN
Solar/Wind Harmer
10.394
24734705WLF1G3
Adder
7.306
24734905WLF1G5
Adder
7.306
971985AH1-537 GEN
Solar/Wind Harmer
2.617
966391AG1-508 GEN
Solar/Wind Harmer
1.328
971981AH1-535 GEN
Solar/Wind Harmer
5.272
972165AH1-665 GEN
Solar/Wind Harmer
6.904
965401AG1-405 GEN
Solar/Wind Harmer
4.386
339211AE2-254 GEN
Solar/Wind Harmer
0.003
270069AE2-166 C O1
Solar/Wind Harmer
0.005
24386405FR-21G C
Solar/Wind Harmer
0.001
24725505WLD G2 C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
9.661
276656WTG2_EQ
Solar/Wind Harmer
0
941731AE2-173 GEN
Solar/Wind Harmer
5.363
253349AC2-067 GEN
Solar/Wind Harmer
2.02
946321AF1-296 GEN
Solar/Wind Harmer
3.573
971611AH1-305 GEN
Solar/Wind Harmer
3.799
945581AF1-223 GEN
Solar/Wind Harmer
0
274823ROCKFORD ;21
Adder
17.581
971171AH1-044 GEN
Solar/Wind Harmer
12.585
24318705GVG2
50/50
10.872
971191AH1-055 GEN
Solar/Wind Harmer
25.624
970243AG2-164 GEN
Solar/Wind Harmer
4.588
970093AG2-073 GEN
Solar/Wind Harmer
7.734
972167AH1-666 GEN
Solar/Wind Harmer
6.174
972273AH1-721 GEN
Adder
91.659
24686205CER G4
Adder
14.065
971461AH1-227 GEN
Solar/Wind Harmer
4.855
270346AE1-212 GEN
Solar/Wind Harmer
7.86
971331AH1-145 GEN
Solar/Wind Harmer
10.953
247619Y1-049
Adder
0.497
958121AF2-106 GEN
Solar/Wind Harmer
0.001
970519AG2-331 GEN
Solar/Wind Harmer
20.392
970699AG2-449 GEN
Solar/Wind Harmer
1.961
3429391JKCT 9G
Adder
9.139
270291AC1-194 GEN
Solar/Wind Harmer
5.957
958171AF2-111 GEN
Solar/Wind Harmer
18.792
25196608WSDLE5
Adder
8.886
253406AD2-031_GEN
Solar/Wind Harmer
0.522
970193AG2-126 GEN
Solar/Wind Harmer
10.289
24728705AND G3
Adder
7.865
253415AE1-040 GEN
Solar/Wind Harmer
0.003
270437AC2-090 C
Solar/Wind Harmer
0.003
970781AG2-491 GEN
Solar/Wind Harmer
6.514
270273AD2-016 GEN
Solar/Wind Harmer
0.675
958821AF2-173 GEN
Solar/Wind Harmer
9.079
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
959611AF2-252 GEN
Solar/Wind Harmer
2.156
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
970513AG2-328 GEN
Solar/Wind Harmer
1.358
970517AG2-330 GEN
Solar/Wind Harmer
8.151
24721605FLATG1
50/50
2.473
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
957241AF2-018 GEN
Solar/Wind Harmer
-0.002
24477305BRIDGE
Adder
0.546
270400AC1-102 GEN
Solar/Wind Harmer
3.444
941621AE2-160 GEN
Adder
4.703
24734805WLF1G4
Adder
7.306
24735105WLF2G1
Adder
7.162
972163AH1-664 GEN
Solar/Wind Harmer
8.62
3429211JKCT 2G
Adder
12.898
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
970455AG2-298 GEN
Solar/Wind Harmer
5.018
25196508WSDLE4
Adder
8.795
270340AC2-060 GEN
Solar/Wind Harmer
0.008
944221AF1-090 GEN
Solar/Wind Harmer
3.946
963841AG1-237 GEN
Solar/Wind Harmer
2.88
24386205FR-12G C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270269AC2-059
Solar/Wind Harmer
0.004
970115AG2-085 GEN
Solar/Wind Harmer
2.587
276655WTG1_EQ
Solar/Wind Harmer
0.003
253400AC2-068 GEN
Solar/Wind Harmer
0.812
971609AH1-304 GEN
Solar/Wind Harmer
1.037
926823AC1-168 GEN
Solar/Wind Harmer
1.076
274746AC1-111 G10
Adder
4.992
23750501ELLIOTTS
Solar/Wind Helper
0.594
942891AE2-308 GEN
Solar/Wind Harmer
7.714
972043AH1-570 GEN
Solar/Wind Harmer
1.999
971485AH1-239 GEN
Solar/Wind Harmer
5.998
971081AG2-670 GEN
Solar/Wind Harmer
5.621
964781AG1-341 GEN
Solar/Wind Harmer
7.848
25194408D.CRK1
Adder
7.868
945391AF1-204 GEN
Solar/Wind Harmer
7.288
24728905RICHG2
Adder
3.669
926881AC1-175 GEN
Solar/Wind Harmer
0.001
966841AG1-555 GEN
Solar/Wind Harmer
0.746
960611AF2-352 GEN
Solar/Wind Harmer
2.156
970883AG2-550 GEN
Solar/Wind Harmer
6.374
276782AC1-033 GEN
Solar/Wind Harmer
0.001
270599AE1-208 GEN
Solar/Wind Harmer
5.819
276708O09 GEN2
Solar/Wind Harmer
0.226
972267AH1-718 GEN
Adder
3.783
274764LEE CO EC;5U
Adder
8.452
274683WAUKEGAN ;8U
Adder
18.876
274683WAUKEGAN ;8U
Adder
15.912
274693ROCKY RD ;1P
Adder
9.873
23652301WDPWR_K20
Solar/Wind Helper
0.126
23585401KL_K28_T16
Solar/Wind Helper
1.149
24289405MTG1
50/50
10.907
971403AH1-188 GEN
Solar/Wind Harmer
15.305
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
927014AC1-188 GEN
Solar/Wind Harmer
0.005
971329AH1-144 GEN
Solar/Wind Harmer
6.901
970091AG2-072 GEN
Adder
86.947
3429421JKCT 10G
Adder
9.139
970273AG2-179 GEN
Solar/Wind Harmer
2.644
971565AH1-281 GEN
Solar/Wind Harmer
1.508
970149AG2-104 GEN
Solar/Wind Harmer
29.663
270263AC1-001 GEN
Solar/Wind Harmer
0.699
970773AG2-487 GEN
Solar/Wind Harmer
1.204
963741AG1-226 GEN
Solar/Wind Harmer
15.844
24791305MDL-5G
Solar/Wind Harmer
0.001
274854TWINGROVE;U2
Solar/Wind Harmer
0.003
276726Z2-087_GEN
Solar/Wind Harmer
0.002
971475AH1-234 GEN
Solar/Wind Harmer
3.061
970819AG2-516 GEN
Solar/Wind Harmer
7.565
274822ROCKFORD ;11
Adder
17.71
959081AF2-199 GEN
Solar/Wind Harmer
6.293
971067AG2-660 GEN
Solar/Wind Harmer
2.098
971917AH1-482 GEN
Solar/Wind Harmer
8.18
235054AD2-180 GEN
Solar/Wind Helper
1.52
23562501BACKB
Solar/Wind Helper
0.806
972103AH1-617 GEN
Solar/Wind Harmer
19.189
943031AE2-326 GEN
Solar/Wind Harmer
4.498
960741AF2-365 GEN
Solar/Wind Harmer
3.705
971155AH1-034 GEN
Solar/Wind Harmer
8.639
25194608D.CRK4
Adder
1.71
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
9.211
970153AG2-106 GEN
Solar/Wind Harmer
17.538
24728505AND G1
Adder
3.761
270030AE2-140 GEN
Solar/Wind Harmer
13.595
276668AB2-070 GEN1
Solar/Wind Harmer
0.24
247642Z2-115 C
Solar/Wind Harmer
0.003
24755605MDL-5G
Solar/Wind Harmer
0.001
970289AG2-191 GEN
Solar/Wind Harmer
0.716
970291AG2-192 GEN
Solar/Wind Harmer
0.651
253370AE2-315 SEC1
Adder
1.856
253371AE2-315 SEC2
Adder
1.755
946031AF1-268 GEN
Solar/Wind Harmer
6.117
274767LEE CO EC;8U
Adder
8.332
959091AF2-200 GEN
Solar/Wind Harmer
12.585
274682WAUKEGAN ;7U
Adder
16.093
235058AG1-386 C
Solar/Wind Helper
0.383
243186AF1-051 GEN
50/50
11.679
24723005RIVRG1
Adder
32.794
24723105RIVRG2
Adder
32.794
24685805CER G1
Adder
14.046
24685905CER G2
Adder
14.046
971225AH1-072 GEN
Solar/Wind Harmer
1.893
971227AH1-073 GEN
Solar/Wind Harmer
1.893
270583AD2-179 GEN
Solar/Wind Harmer
7.911
971125AH1-004 GEN
Solar/Wind Harmer
3.056
252519AF1-045_GEN
Solar/Wind Harmer
6.373
252516AE2-318_GEN
Solar/Wind Harmer
5.653
270444AC2-157 GEN1
Solar/Wind Harmer
0.003
971587AH1-292 GEN
Solar/Wind Harmer
5.336
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
276916AD2-100_GEN
Solar/Wind Harmer
14.016
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
971613AH1-306 GEN
Solar/Wind Harmer
3.122
253370AE2-315 SEC1
Adder
1.856
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276741O09 GEN1
Solar/Wind Harmer
0.226
25322209TAIT E
Adder
8.86
25322209TAIT E
Adder
8.661
971341AH1-150 GEN
Solar/Wind Harmer
12.585
971343AH1-151 GEN
Solar/Wind Harmer
12.585
247621Y3-024
Adder
0.216
972203AH1-686 GEN
Adder
3.978
970281AG2-184 GEN
Solar/Wind Harmer
20.149
252524AE2-267 GEN
Solar/Wind Harmer
0.003
962771AG1-126 GEN
Solar/Wind Harmer
27.465
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.24
276848AB2-070 GEN3
Solar/Wind Harmer
0.239
970289AG2-191 GEN
Solar/Wind Harmer
1.237
25306009OHH W.
Adder
2.673
253372AE2-315 SEC3
Adder
1.755
253372AE2-315 SEC3
Adder
1.755
959341AF2-225 GEN
Solar/Wind Harmer
6.757
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
970169AG2-114 GEN
Solar/Wind Harmer
6.359
961011AF2-392 GEN
Solar/Wind Harmer
3.717
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274744AC1-111 GEN8
Adder
4.992
966571AG1-526 GEN
Solar/Wind Harmer
17.032
25196008MFTGT1
Adder
1.418
252510AF1-249 C
Solar/Wind Harmer
0.056
942481AE2-261 GEN
Solar/Wind Harmer
19.91
276621W2-048 GEN
Solar/Wind Harmer
0.333
276838X2-022 GEN2
Solar/Wind Harmer
0.372
971993AH1-541 GEN
Solar/Wind Harmer
3.038
942111AE2-223 GEN
Solar/Wind Harmer
2.091
276157O29GEN1
Solar/Wind Harmer
1.026
970571AG2-364 GEN
Solar/Wind Harmer
12.648
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
276889AE2-281 GEN
Solar/Wind Harmer
0.001
274729ELWOOD EC;1P
Adder
6.64
237048AF1-022 C
Solar/Wind Helper
0.172
237043AE2-125 C
Solar/Wind Helper
0.155
960161AF2-307 GEN
Solar/Wind Harmer
5.337
270186AC1-089 GEN
Solar/Wind Harmer
0.005
970239AG2-162 GEN
Solar/Wind Harmer
1.961
962581AG1-107 GEN
Solar/Wind Harmer
0.002
970107AG2-081 GEN
Solar/Wind Harmer
2.292
970235AG2-159 GEN
Solar/Wind Harmer
4.628
970235AG2-159 GEN
Solar/Wind Harmer
2.656
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
970241AG2-163 GEN
Solar/Wind Harmer
3.905
270209AC1-174_GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
970825AG2-519 GEN
Solar/Wind Harmer
7.169
276645AC1-214 GEN1
Solar/Wind Harmer
0.25
276603SUBLETTE C
Solar/Wind Harmer
0
274762LEE CO EC;3U
Adder
8.432
938861AE1-114 GEN
Solar/Wind Harmer
3.58
274856ECOGROVE ;U1
Solar/Wind Harmer
0.149
276611AD2-172 GEN
Solar/Wind Harmer
0.002
274696ROCKY RD ;4P
Adder
10.207
274697ROCKY RD ;3P
Adder
2.709
970321AG2-212 GEN
Solar/Wind Harmer
1.358
24289405MTG1
50/50
10.907
24686405CER G5
Adder
14.009
270053AF1-130 C
Solar/Wind Harmer
2.49
970913AG2-568 GEN
Solar/Wind Harmer
8.136
970273AG2-179 GEN
Solar/Wind Harmer
4.533
339250AF1-203 GEN
Solar/Wind Harmer
0.001
962251AG1-071 GEN
Solar/Wind Harmer
4.615
270356AE2-297 GEN
Solar/Wind Harmer
0.009
270222AC2-111 GEN
Solar/Wind Harmer
3.451
972173AH1-669 GEN
Solar/Wind Harmer
3.31
276686W4-005 GEN3
Solar/Wind Harmer
0.001
270004AE1-209 GEN
Solar/Wind Harmer
1.405
965091AG1-374 GEN
Solar/Wind Harmer
19.404
970191AG2-125 GEN
Solar/Wind Harmer
1.65
965931AG1-462 GEN
Solar/Wind Harmer
16.291
274878BISHOP HL;2U
Solar/Wind Harmer
0.214
274760LEE CO EC;1U
Adder
8.432
972236AH1-702 GEN2
Adder
1.979
24686505CER G6
Adder
14.12
24728305BUCHG2
Adder
6.221
3429241JKCT 3G
Adder
13.068
339216AC1-074 GEN
Solar/Wind Harmer
0.209
252507AC2-088 GEN
Solar/Wind Harmer
0.341
962241AG1-070 GEN
Solar/Wind Harmer
4.025
962761AG1-125 GEN
Solar/Wind Harmer
27.465
965911AG1-460 GEN
Solar/Wind Harmer
1.332
276615X2-022 GEN
Solar/Wind Harmer
0.069
24385905FR-11G C
Solar/Wind Harmer
0.002
963831AG1-236 GEN
Solar/Wind Harmer
2.568
276903AD2-071 C
Solar/Wind Harmer
7.334
25326309TAIT D
Adder
0.995
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274766LEE CO EC;7U
Adder
8.332
247536S-71 GEN
Solar/Wind Harmer
0.254
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
972235AH1-702 GEN1
Adder
2.276
939401AE1-172 GEN
Solar/Wind Harmer
4.71
970245AG2-165 GEN
Solar/Wind Harmer
1.358
971313AH1-133 GEN
Solar/Wind Harmer
9.492
270132AB1-180 C
Adder
0.159
971061AG2-657 GEN
Solar/Wind Harmer
5.654
970879AG2-548 GEN
Solar/Wind Harmer
7.21
270367AC2-061_GEN
Solar/Wind Harmer
0.006
965411AG1-406 GEN
Solar/Wind Harmer
2.821
25196108MFTGT2
Adder
1.614
25196108MFTGT2
Adder
1.499
25196408WSDLE3
Adder
9.147
25196308WSDLE2
Adder
9.067
25196208WSDLE1
Adder
9.045
25196708WSDLE6
Adder
9.022
270240V3-007_GEN2
Solar/Wind Harmer
0.002
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
270594AE1-207 GEN
Solar/Wind Harmer
7.284
971673AH1-337 GEN
Solar/Wind Harmer
4.2
270543AE2-219 C
Solar/Wind Harmer
0.004
957751AF2-069 GEN
Solar/Wind Harmer
0.21
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
971681AH1-341 GEN
Solar/Wind Harmer
10.171
276612AE2-035 GEN
Solar/Wind Harmer
0.002
957141AF2-008_MTX
Adder
60.637
944201AF1-088_MTX
Adder
121.273
CBM West 1LTFEXP_CBM-W1->PJM
CBM
116.498
NYPJM->LTFIMP_NY
CLTF
4.59
TVALTFEXP_TVA->PJM
CLTF
10.26
AG2-052LTFEXP_AG2-052->PJM
LTF
0.209
CBM West 2LTFEXP_CBM-W2->PJM
CBM
132.776
LGEELTFEXP_LGEE->PJM
CLTF
7.503
MECLTFEXP_MEC->PJM
CLTF
15.75
AH1-155LTFEXP_AH1-155->PJM
LTF
0.313
CBM South 1LTFEXP_CBM-S1->PJM
CBM
38.98
WECLTFEXP_WEC->PJM
CLTF
3.454
LAGNLTFEXP_LAGN->PJM
CLTF
19.803
CBM South 2LTFEXP_CBM-S2->PJM
CBM
23.164
CPLELTFEXP_CPLE->PJM
CLTF
6.38
SIGELTFEXP_SIGE->PJM
CLTF
0.547

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.47 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5991.02
MW Contribution:26.09
Bus #Bus NameTypeMW Contribution
944971AF1-162 GEN
Solar/Wind Harmer
13.01
24728205BUCHG1
Adder
7.763
24686205CER G4
Adder
16.139
971461AH1-227 GEN
Solar/Wind Harmer
8.54
971331AH1-145 GEN
Solar/Wind Harmer
15.359
247619Y1-049
Adder
0.704
270346AE1-212 GEN
Solar/Wind Harmer
14.72
958121AF2-106 GEN
Solar/Wind Harmer
7.412
957541AF2-048 GEN
Solar/Wind Harmer
2.373
970519AG2-331 GEN
Solar/Wind Harmer
23.064
970699AG2-449 GEN
Solar/Wind Harmer
15.258
3429391JKCT 9G
Adder
10.993
24722005FLATG5
50/50
2.714
24721905FLATG4
50/50
49.755
960911AF2-382 GEN
Solar/Wind Harmer
12.931
943031AE2-326 GEN
Solar/Wind Harmer
6.109
972103AH1-617 GEN
Solar/Wind Harmer
33.271
270030AE2-140 GEN
Solar/Wind Harmer
26.875
971155AH1-034 GEN
Solar/Wind Harmer
12.926
960741AF2-365 GEN
Solar/Wind Harmer
6.448
25194608D.CRK4
Adder
2.039
253316AC1-085 GEN3
Solar/Wind Harmer
10.168
253433AC1-085 GEN1
Solar/Wind Harmer
6.454
946181AF1-283 GEN
Solar/Wind Harmer
15.78
24728505AND G1
Adder
4.525
970153AG2-106 GEN
Solar/Wind Harmer
16.656
270574AD1-017 GEN2
Solar/Wind Harmer
6.023
253370AE2-315 SEC1
Adder
2.238
253371AE2-315 SEC2
Adder
2.117
274767LEE CO EC;8U
Adder
10.131
274682WAUKEGAN ;7U
Adder
19.567
964991AG1-363 GEN
Solar/Wind Helper
3.709
316097T157 G90
Solar/Wind Helper
1.094
958171AF2-111 GEN
Solar/Wind Harmer
32.167
270291AC1-194 GEN
Solar/Wind Harmer
13.485
25196608WSDLE5
Adder
10.598
253406AD2-031_GEN
Solar/Wind Harmer
1.534
970193AG2-126 GEN
Solar/Wind Harmer
17.759
24728705AND G3
Adder
9.464
253415AE1-040 GEN
Solar/Wind Harmer
1.318
23750701CROSSCHOOL
Solar/Wind Helper
1.197
238127S14_GEN_2
Solar/Wind Helper
0.687
202652Y1-033 WT C
Solar/Wind Helper
0.534
20089026BF_G21_K23
Solar/Wind Helper
0.438
942891AE2-308 GEN
Solar/Wind Harmer
13.304
972043AH1-570 GEN
Solar/Wind Harmer
3.299
971485AH1-239 GEN
Solar/Wind Harmer
10.499
971081AG2-670 GEN
Solar/Wind Harmer
9.778
964781AG1-341 GEN
Solar/Wind Harmer
13.698
25194408D.CRK1
Adder
9.381
945391AF1-204 GEN
Solar/Wind Harmer
16.499
316217AC1-145 GEN
Solar/Wind Harmer
2.806
316197AC1-042 GEN
Solar/Wind Harmer
2.127
942671AE2-283 GEN
Solar/Wind Harmer
5.728
24728905RICHG2
Adder
4.412
972267AH1-718 GEN
Adder
4.6
972203AH1-686 GEN
Adder
4.544
970281AG2-184 GEN
Solar/Wind Harmer
34.934
962211AG1-066 GEN
Solar/Wind Harmer
3.823
252524AE2-267 GEN
Solar/Wind Harmer
1.95
962771AG1-126 GEN
Solar/Wind Harmer
38.198
25306009OHH W.
Adder
3.223
253372AE2-315 SEC3
Adder
2.117
253372AE2-315 SEC3
Adder
2.117
274744AC1-111 GEN8
Adder
6.069
238109AE1-109 GEN2
Solar/Wind Helper
0.088
238110AE1-109 GEN3
Solar/Wind Helper
0.088
243186AF1-051 GEN
50/50
12.748
24721805FLATG3
50/50
2.714
24721705FLATG2
50/50
49.755
24723205RIVRG3
Adder
37.637
24686105CER G3
Adder
16.224
970947AG2-589 GEN
Solar/Wind Harmer
3.612
24735205WLF2G2
Adder
9.002
971367AH1-164 GEN
Solar/Wind Harmer
5.069
270336AE1-100 GEN
Solar/Wind Harmer
2.384
971821AH1-427 GEN
Solar/Wind Harmer
13.272
945681AF1-233 GEN
Solar/Wind Harmer
24.878
943111AE2-339 GEN
Solar/Wind Harmer
1.163
943811AF1-049 GEN
Solar/Wind Harmer
4.961
339241AF1-083 GEN
Solar/Wind Harmer
2.171
964901AG1-354 GEN
Solar/Wind Harmer
19.445
270445AC2-157 GEN2
Solar/Wind Harmer
6.973
25194608D.CRK4
Adder
2.039
253432AC1-085 GEN2
Solar/Wind Harmer
0.325
946171AF1-282 GEN
Solar/Wind Harmer
12.138
24728605AND G2
Adder
4.525
970155AG2-107 GEN
Solar/Wind Harmer
16.656
270197AD1-017 GEN1
Solar/Wind Harmer
1.81
941821AE2-187 GEN
Solar/Wind Harmer
6.484
253370AE2-315 SEC1
Adder
2.238
253371AE2-315 SEC2
Adder
2.117
274828WAUKEGAN ;BP
Adder
12.03
274682WAUKEGAN ;7U
Adder
19.567
274745AC1-111 GEN9
Adder
6.069
238185AF2-356 C
Solar/Wind Helper
2.176
316095T157 G97
Solar/Wind Helper
1.094
243186AF1-051 GEN
50/50
12.748
24723005RIVRG1
Adder
37.637
24723105RIVRG2
Adder
37.637
24685805CER G1
Adder
16.117
24685905CER G2
Adder
16.117
270214AC2-123 GEN
Solar/Wind Harmer
3.882
971225AH1-072 GEN
Solar/Wind Harmer
3.33
971227AH1-073 GEN
Solar/Wind Harmer
3.33
270583AD2-179 GEN
Solar/Wind Harmer
16.345
971125AH1-004 GEN
Solar/Wind Harmer
5.257
252519AF1-045_GEN
Solar/Wind Harmer
7.591
252516AE2-318_GEN
Solar/Wind Harmer
5.79
270444AC2-157 GEN1
Solar/Wind Harmer
6.973
253317AC1-085 GEN4
Solar/Wind Harmer
10.168
276916AD2-100_GEN
Solar/Wind Harmer
24.323
253370AE2-315 SEC1
Adder
2.238
25322209TAIT E
Adder
10.707
25322209TAIT E
Adder
10.466
247621Y3-024
Adder
0.262
238120AE2-309 GEN
Solar/Wind Helper
0.43
960161AF2-307 GEN
Solar/Wind Harmer
8.906
970879AG2-548 GEN
Solar/Wind Harmer
8.293
270186AC1-089 GEN
Solar/Wind Harmer
8.143
970239AG2-162 GEN
Solar/Wind Harmer
14.622
970107AG2-081 GEN
Solar/Wind Harmer
3.942
962581AG1-107 GEN
Solar/Wind Harmer
6.599
961491AF2-440 GEN
Solar/Wind Harmer
2.742
970235AG2-159 GEN
Solar/Wind Harmer
5.2
970235AG2-159 GEN
Solar/Wind Harmer
3.174
339236AF1-050_GEN
Solar/Wind Harmer
2.357
253394AE2-221_GEN
Solar/Wind Harmer
5.367
253398AE2-221_GEN2
Solar/Wind Harmer
5.367
274762LEE CO EC;3U
Adder
10.252
274696ROCKY RD ;4P
Adder
12.409
274697ROCKY RD ;3P
Adder
3.293
944781AF1-143 GEN
Solar/Wind Helper
2.298
203940AF1-140 C
Solar/Wind Helper
0.359
970241AG2-163 GEN
Solar/Wind Harmer
12.594
274764LEE CO EC;5U
Adder
10.276
274683WAUKEGAN ;8U
Adder
22.951
274683WAUKEGAN ;8U
Adder
19.347
274693ROCKY RD ;1P
Adder
12.003
23585401KL_K28_T16
Solar/Wind Helper
1.267
23652301WDPWR_K20
Solar/Wind Helper
0.133
203955AF1-039 C O1
Solar/Wind Helper
0.352
20083426SW_E13_K22
Solar/Wind Helper
0.051
20084626FORWARD
Solar/Wind Helper
0.323
946071AF1-272 GEN
Solar/Wind Helper
2.428
270399AC1-101 GEN
Solar/Wind Harmer
7.833
270330AC1-082 GEN2
Solar/Wind Harmer
1.393
966391AG1-508 GEN
Solar/Wind Harmer
5.763
972143AH1-644 GEN
Solar/Wind Harmer
16.635
24734705WLF1G3
Adder
9.185
24734905WLF1G5
Adder
9.185
971985AH1-537 GEN
Solar/Wind Harmer
26.201
971981AH1-535 GEN
Solar/Wind Harmer
14.209
270069AE2-166 C O1
Solar/Wind Harmer
3.796
965401AG1-405 GEN
Solar/Wind Harmer
7.637
339211AE2-254 GEN
Solar/Wind Harmer
2.01
972165AH1-665 GEN
Solar/Wind Harmer
10.582
944031AF1-071 GEN
Solar/Wind Harmer
1.178
24721605FLATG1
50/50
2.714
957241AF2-018 GEN
Solar/Wind Harmer
8.259
270400AC1-102 GEN
Solar/Wind Harmer
7.833
24477305BRIDGE
Adder
0.637
270329AC1-082 GEN1
Solar/Wind Harmer
0.821
941621AE2-160 GEN
Adder
5.66
24734805WLF1G4
Adder
9.185
24735105WLF2G1
Adder
9.002
3429211JKCT 2G
Adder
15.52
972163AH1-664 GEN
Solar/Wind Harmer
13.228
339243AC2-075 GEN1
Solar/Wind Harmer
0.595
970455AG2-298 GEN
Solar/Wind Harmer
7.809
25196508WSDLE4
Adder
10.49
270340AC2-060 GEN
Solar/Wind Harmer
3.615
944221AF1-090 GEN
Solar/Wind Harmer
12.754
274746AC1-111 G10
Adder
6.069
23750501ELLIOTTS
Solar/Wind Helper
0.635
24289405MTG1
50/50
11.79
971403AH1-188 GEN
Solar/Wind Harmer
26.09
960001AF2-291 GEN
Solar/Wind Harmer
5.329
971329AH1-144 GEN
Solar/Wind Harmer
19.813
927014AC1-188 GEN
Solar/Wind Harmer
2.379
970091AG2-072 GEN
Adder
103.033
3429421JKCT 10G
Adder
10.993
970273AG2-179 GEN
Solar/Wind Harmer
3.221
971565AH1-281 GEN
Solar/Wind Harmer
2.604
270263AC1-001 GEN
Solar/Wind Harmer
1.245
970149AG2-104 GEN
Solar/Wind Harmer
47.174
274822ROCKFORD ;11
Adder
21.533
235054AD2-180 GEN
Solar/Wind Helper
1.695
235531U2-073 GEN
Solar/Wind Helper
2.733
23562501BACKB
Solar/Wind Helper
0.864
238108AE1-109 GEN1
Solar/Wind Helper
0.088
963741AG1-226 GEN
Solar/Wind Harmer
22.669
274823ROCKFORD ;21
Adder
21.377
20092526R32
Solar/Wind Helper
1.053
24686505CER G6
Adder
16.203
24728305BUCHG2
Adder
7.763
3429241JKCT 3G
Adder
15.723
339216AC1-074 GEN
Solar/Wind Harmer
2.198
962241AG1-070 GEN
Solar/Wind Harmer
5.799
252507AC2-088 GEN
Solar/Wind Harmer
2.292
270018AE2-047 C O1
Solar/Wind Harmer
1.511
962761AG1-125 GEN
Solar/Wind Harmer
38.198
274766LEE CO EC;7U
Adder
10.131
972235AH1-702 GEN1
Adder
2.767
25326309TAIT D
Adder
1.202
238117U2-030
Solar/Wind Helper
0.288
20088826HIGHLAND
Solar/Wind Helper
0.812
971277AH1-098 GEN
Solar/Wind Harmer
6.642
971073AG2-665 GEN
Solar/Wind Harmer
8.293
971073AG2-665 GEN
Solar/Wind Harmer
5.786
339231AF1-038_GEN
Solar/Wind Harmer
2.394
972045AH1-571 GEN
Solar/Wind Harmer
2.639
339221AD2-048_GEN
Solar/Wind Harmer
2.024
966021AG1-471 GEN
Solar/Wind Harmer
7.099
970653AG2-424 GEN
Solar/Wind Harmer
6.261
970653AG2-424 GEN
Solar/Wind Harmer
2.263
339255AE2-071 GEN
Solar/Wind Harmer
1.372
964571AG1-320 GEN
Solar/Wind Harmer
10.586
252509AD1-136 GEN
Solar/Wind Harmer
0.327
25183208HLCRTG
Solar/Wind Harmer
7.582
25194508D.CRK3
Adder
1.754
24728805RICHG1
Adder
4.412
276911AD2-131_GEN
Solar/Wind Harmer
4.916
274765LEE CO EC;6U
Adder
10.276
274763LEE CO EC;4U
Adder
10.155
274695ROCKY RD ;2P
Adder
12.123
20088926STNY CRK
Solar/Wind Helper
0.747
24318705GVG2
50/50
11.866
270331AC1-082 GEN3
Solar/Wind Harmer
0.823
971687AH1-348 GEN
Solar/Wind Harmer
1.664
971315AH1-136 GEN
Solar/Wind Harmer
3.299
970333AG2-219 GEN
Solar/Wind Harmer
41.959
25196808ZIMRHP
Adder
95.812
25196008MFTGT1
Adder
1.747
3147312GRETNA
Solar/Wind Harmer
-0.003
274761LEE CO EC;2U
Adder
10.252
237046AF1-021 C
Solar/Wind Helper
0.457
23751201ROTHROCK
Solar/Wind Helper
0.71
23583801GRNGAP
Solar/Wind Helper
4.088
20089226LOOKOUT
Solar/Wind Helper
0.539
971313AH1-133 GEN
Solar/Wind Harmer
17.224
270132AB1-180 C
Adder
0.198
971061AG2-657 GEN
Solar/Wind Harmer
14.056
970879AG2-548 GEN
Solar/Wind Harmer
5.786
24289405MTG1
50/50
11.79
24686405CER G5
Adder
16.075
270053AF1-130 C
Solar/Wind Harmer
6.909
970913AG2-568 GEN
Solar/Wind Harmer
14.13
270173AC1-122 GEN
Solar/Wind Harmer
2.108
970273AG2-179 GEN
Solar/Wind Harmer
5.144
339250AF1-203 GEN
Solar/Wind Harmer
0.784
962251AG1-071 GEN
Solar/Wind Harmer
7.087
941801AE2-185 GEN
Solar/Wind Harmer
6.484
270356AE2-297 GEN
Solar/Wind Harmer
5.354
270222AC2-111 GEN
Solar/Wind Harmer
9.554
274760LEE CO EC;1U
Adder
10.252
972236AH1-702 GEN2
Adder
2.406
238118U2-030_1
Solar/Wind Helper
0.288
20089126CSLMN_L13
Solar/Wind Helper
0.554
965411AG1-406 GEN
Solar/Wind Harmer
3.428
270367AC2-061_GEN
Solar/Wind Harmer
4.222
25196108MFTGT2
Adder
1.926
25196108MFTGT2
Adder
1.788
25196408WSDLE3
Adder
10.91
25196308WSDLE2
Adder
10.815
25196208WSDLE1
Adder
10.788
25196708WSDLE6
Adder
10.761
238126S14_GEN_1
Solar/Wind Helper
0.687
24318705GVG2
50/50
11.866
971191AH1-055 GEN
Solar/Wind Harmer
36.143
972273AH1-721 GEN
Adder
111.61
970093AG2-073 GEN
Solar/Wind Harmer
13.356
970243AG2-164 GEN
Solar/Wind Harmer
34.33
966571AG1-526 GEN
Solar/Wind Harmer
29.484
972167AH1-666 GEN
Solar/Wind Harmer
10.547
962751AG1-124 GEN
Solar/Wind Harmer
11.816
25196008MFTGT1
Adder
1.692
252510AF1-249 C
Solar/Wind Harmer
0.521
3147312GRETNA
Solar/Wind Harmer
-0.014
3146802CHATHAM
Solar/Wind Harmer
-0.013
274729ELWOOD EC;1P
Adder
8.072
237048AF1-022 C
Solar/Wind Helper
0.182
237043AE2-125 C
Solar/Wind Helper
0.163
957141AF2-008_MTX
Adder
72.592
944201AF1-088_MTX
Adder
145.184
CBM South 1LTFEXP_CBM-S1->PJM
CBM
47.815
WECLTFEXP_WEC->PJM
CLTF
4.2
LAGNLTFEXP_LAGN->PJM
CLTF
24.37
CBM South 2LTFEXP_CBM-S2->PJM
CBM
29.03
CPLELTFEXP_CPLE->PJM
CLTF
7.791
SIGELTFEXP_SIGE->PJM
CLTF
0.659
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.592
NYPJM->LTFIMP_NY
CLTF
5.271
TVALTFEXP_TVA->PJM
CLTF
12.655
AG2-052LTFEXP_AG2-052->PJM
LTF
0.253
CBM West 2LTFEXP_CBM-W2->PJM
CBM
162.06
LGEELTFEXP_LGEE->PJM
CLTF
8.989
MECLTFEXP_MEC->PJM
CLTF
19.173
AH1-155LTFEXP_AH1-155->PJM
LTF
0.38

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P2-2_#7222_05MALIS 765_1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#7222_05MALIS 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:107.09 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5914.32
MW Contribution:23.03
Bus #Bus NameTypeMW Contribution
243186AF1-051 GEN
50/50
12.367
24721805FLATG3
50/50
2.714
24721705FLATG2
50/50
49.756
24723205RIVRG3
Adder
34.405
24686105CER G3
Adder
14.787
970947AG2-589 GEN
Solar/Wind Harmer
3.261
970155AG2-107 GEN
Solar/Wind Harmer
22.36
24735205WLF2G2
Adder
7.624
270445AC2-157 GEN2
Solar/Wind Harmer
6.775
971821AH1-427 GEN
Solar/Wind Harmer
11.992
339241AF1-083 GEN
Solar/Wind Harmer
1.973
943111AE2-339 GEN
Solar/Wind Harmer
1.047
945681AF1-233 GEN
Solar/Wind Harmer
22.212
964901AG1-354 GEN
Solar/Wind Harmer
17.673
24728605AND G2
Adder
4.411
25194608D.CRK4
Adder
1.851
274745AC1-111 GEN9
Adder
6.26
274682WAUKEGAN ;7U
Adder
20.129
274828WAUKEGAN ;BP
Adder
12.373
238185AF2-356 C
Solar/Wind Helper
2.169
241966AE1-183 GEN
Solar/Wind Helper
0.238
23751101LEADS_P59
Solar/Wind Helper
1.234
964201AG1-281 GEN
Solar/Wind Helper
0.454
243186AF1-051 GEN
50/50
12.367
24723005RIVRG1
Adder
34.405
24723105RIVRG2
Adder
34.405
24685805CER G1
Adder
14.69
24685905CER G2
Adder
14.69
971225AH1-072 GEN
Solar/Wind Harmer
2.872
971227AH1-073 GEN
Solar/Wind Harmer
2.872
270214AC2-123 GEN
Solar/Wind Harmer
2.998
270444AC2-157 GEN1
Solar/Wind Harmer
6.775
270583AD2-179 GEN
Solar/Wind Harmer
11.844
971125AH1-004 GEN
Solar/Wind Harmer
4.737
276916AD2-100_GEN
Solar/Wind Harmer
24.115
957381AF2-032 GEN
Solar/Wind Harmer
0.48
241801AE1-079 GEN
Solar/Wind Helper
0.231
238120AE2-309 GEN
Solar/Wind Helper
0.419
20303426NA_O38_P22
Solar/Wind Helper
0.931
203853AF1-134 C O1
Solar/Wind Helper
0.446
203952AE2-129 C
Solar/Wind Helper
0.442
942891AE2-308 GEN
Solar/Wind Harmer
11.976
972043AH1-570 GEN
Solar/Wind Harmer
2.97
971081AG2-670 GEN
Solar/Wind Harmer
8.888
971485AH1-239 GEN
Solar/Wind Harmer
9.446
964781AG1-341 GEN
Solar/Wind Harmer
12.447
945391AF1-204 GEN
Solar/Wind Harmer
16.279
966841AG1-555 GEN
Solar/Wind Harmer
2.893
25194408D.CRK1
Adder
8.517
972267AH1-718 GEN
Adder
4.679
274764LEE CO EC;5U
Adder
10.473
274693ROCKY RD ;1P
Adder
12.352
274683WAUKEGAN ;8U
Adder
23.604
274683WAUKEGAN ;8U
Adder
19.897
23652301WDPWR_K20
Solar/Wind Helper
0.141
23585401KL_K28_T16
Solar/Wind Helper
1.274
203955AF1-039 C O1
Solar/Wind Helper
0.36
241967AE2-285_GEN
Solar/Wind Helper
0.593
20083426SW_E13_K22
Solar/Wind Helper
0.053
946071AF1-272 GEN
Solar/Wind Helper
2.555
20084626FORWARD
Solar/Wind Helper
0.336
24721605FLATG1
50/50
2.714
957241AF2-018 GEN
Solar/Wind Harmer
7.355
270329AC1-082 GEN1
Solar/Wind Harmer
0.741
270400AC1-102 GEN
Solar/Wind Harmer
6.952
24477305BRIDGE
Adder
0.568
941621AE2-160 GEN
Adder
4.884
270330AC1-082 GEN2
Solar/Wind Harmer
1.259
270399AC1-101 GEN
Solar/Wind Harmer
6.952
972143AH1-644 GEN
Solar/Wind Harmer
14.568
24734705WLF1G3
Adder
7.759
24734905WLF1G5
Adder
7.759
971985AH1-537 GEN
Solar/Wind Harmer
23.775
966391AG1-508 GEN
Solar/Wind Harmer
4.457
971981AH1-535 GEN
Solar/Wind Harmer
12.146
965401AG1-405 GEN
Solar/Wind Harmer
6.855
339211AE2-254 GEN
Solar/Wind Harmer
1.816
972165AH1-665 GEN
Solar/Wind Harmer
9.453
24386405FR-21G C
Solar/Wind Harmer
4.958
24697605MDL-3G C
Solar/Wind Harmer
4.228
274823ROCKFORD ;21
Adder
21.86
274775LINCOLN ;6U
Adder
9.447
20092526R32
Solar/Wind Helper
1.095
203846AF2-130 C
Solar/Wind Helper
0.42
24289405MTG1
50/50
11.329
971403AH1-188 GEN
Solar/Wind Harmer
23.029
960001AF2-291 GEN
Solar/Wind Harmer
4.797
970149AG2-104 GEN
Solar/Wind Harmer
63.33
927014AC1-188 GEN
Solar/Wind Harmer
2.074
970091AG2-072 GEN
Adder
99.087
971329AH1-144 GEN
Solar/Wind Harmer
14.766
971565AH1-281 GEN
Solar/Wind Harmer
2.394
970273AG2-179 GEN
Solar/Wind Harmer
2.902
3429421JKCT 10G
Adder
9.882
963741AG1-226 GEN
Solar/Wind Harmer
52.124
274822ROCKFORD ;11
Adder
22.02
235054AD2-180 GEN
Solar/Wind Helper
1.687
23562501BACKB
Solar/Wind Helper
0.892
235531U2-073 GEN
Solar/Wind Helper
2.67
20094526CT_V3-030
Solar/Wind Helper
0.443
238108AE1-109 GEN1
Solar/Wind Helper
0.084
24791305MDL-5G
Solar/Wind Harmer
1.072
24686505CER G6
Adder
14.768
962761AG1-125 GEN
Solar/Wind Harmer
51.279
24728305BUCHG2
Adder
6.555
3429241JKCT 3G
Adder
14.135
339216AC1-074 GEN
Solar/Wind Harmer
1.982
962241AG1-070 GEN
Solar/Wind Harmer
5.277
24385905FR-11G C
Solar/Wind Harmer
9.582
252507AC2-088 GEN
Solar/Wind Harmer
2.064
970245AG2-165 GEN
Solar/Wind Harmer
20.527
965911AG1-460 GEN
Solar/Wind Harmer
1.601
274766LEE CO EC;7U
Adder
10.325
972235AH1-702 GEN1
Adder
2.828
238117U2-030
Solar/Wind Helper
0.284
20088826HIGHLAND
Solar/Wind Helper
0.845
944971AF1-162 GEN
Solar/Wind Harmer
11.585
24728205BUCHG1
Adder
6.555
971277AH1-098 GEN
Solar/Wind Harmer
5.115
964571AG1-320 GEN
Solar/Wind Harmer
9.767
970653AG2-424 GEN
Solar/Wind Harmer
5.74
970653AG2-424 GEN
Solar/Wind Harmer
2.075
339231AF1-038_GEN
Solar/Wind Harmer
2.157
972045AH1-571 GEN
Solar/Wind Harmer
2.376
339221AD2-048_GEN
Solar/Wind Harmer
1.825
966021AG1-471 GEN
Solar/Wind Harmer
6.38
339255AE2-071 GEN
Solar/Wind Harmer
1.246
252509AD1-136 GEN
Solar/Wind Harmer
0.295
276911AD2-131_GEN
Solar/Wind Harmer
4.874
25194508D.CRK3
Adder
1.592
274765LEE CO EC;6U
Adder
10.473
274763LEE CO EC;4U
Adder
10.35
274695ROCKY RD ;2P
Adder
12.475
20088926STNY CRK
Solar/Wind Helper
0.775
20088626ARWF_N39
Solar/Wind Helper
1.136
946381AF1-302 GEN
Solar/Wind Helper
0.207
203946AE2-131 C
Solar/Wind Helper
0.442
24734805WLF1G4
Adder
7.759
24735105WLF2G1
Adder
7.624
970455AG2-298 GEN
Solar/Wind Harmer
7.163
3429211JKCT 2G
Adder
13.952
972163AH1-664 GEN
Solar/Wind Harmer
11.816
339243AC2-075 GEN1
Solar/Wind Harmer
0.537
963841AG1-237 GEN
Solar/Wind Harmer
12.629
24386205FR-12G C
Solar/Wind Harmer
4.941
944221AF1-090 GEN
Solar/Wind Harmer
12.589
24690905MDL-1G C
Solar/Wind Harmer
9.207
270180AB1-006 GEN1
Solar/Wind Harmer
8.248
946581AF1-322 GEN
Solar/Wind Harmer
11.733
25196508WSDLE4
Adder
9.523
274746AC1-111 G10
Adder
6.26
274776LINCOLN ;7U
Adder
1.661
23750501ELLIOTTS
Solar/Wind Helper
0.66
254304AE2-114 C
Solar/Wind Helper
0.203
241982AE2-343 S C
Solar/Wind Helper
0.207
203961AE2-224 GEN
Solar/Wind Helper
2.258
24697905MDL-4G C
Solar/Wind Harmer
1.02
970239AG2-162 GEN
Solar/Wind Harmer
14.243
960161AF2-307 GEN
Solar/Wind Harmer
7.971
970235AG2-159 GEN
Solar/Wind Harmer
4.77
970235AG2-159 GEN
Solar/Wind Harmer
2.912
270186AC1-089 GEN
Solar/Wind Harmer
7.264
970107AG2-081 GEN
Solar/Wind Harmer
3.553
339236AF1-050_GEN
Solar/Wind Harmer
2.142
962581AG1-107 GEN
Solar/Wind Harmer
5.875
961491AF2-440 GEN
Solar/Wind Harmer
2.442
970241AG2-163 GEN
Solar/Wind Harmer
28.958
970321AG2-212 GEN
Solar/Wind Harmer
20.527
274762LEE CO EC;3U
Adder
10.448
274696ROCKY RD ;4P
Adder
12.769
274697ROCKY RD ;3P
Adder
3.389
274770LINCOLN ;1U
Adder
9.447
274771LINCOLN ;2U
Adder
9.447
962101AG1-054 GEN
Solar/Wind Helper
0.609
24318705GVG2
50/50
11.512
270331AC1-082 GEN3
Solar/Wind Harmer
0.743
971315AH1-136 GEN
Solar/Wind Harmer
2.924
971687AH1-348 GEN
Solar/Wind Harmer
1.437
970333AG2-219 GEN
Solar/Wind Harmer
40.872
25196008MFTGT1
Adder
1.607
24387305FR-4G C
Solar/Wind Harmer
5.858
25196808ZIMRHP
Adder
86.412
274761LEE CO EC;2U
Adder
10.448
274773LINCOLN ;4U
Adder
9.447
274774LINCOLN ;5U
Adder
9.447
237046AF1-021 C
Solar/Wind Helper
0.484
23751201ROTHROCK
Solar/Wind Helper
0.732
254303AC2-168 GEN
Solar/Wind Helper
0.147
20089226LOOKOUT
Solar/Wind Helper
0.556
241985AE1-237 GEN
Solar/Wind Helper
0.231
944781AF1-143 GEN
Solar/Wind Helper
2.369
203940AF1-140 C
Solar/Wind Helper
0.373
24289405MTG1
50/50
11.329
24686405CER G5
Adder
14.651
270053AF1-130 C
Solar/Wind Harmer
6.152
970913AG2-568 GEN
Solar/Wind Harmer
12.168
970273AG2-179 GEN
Solar/Wind Harmer
4.636
339250AF1-203 GEN
Solar/Wind Harmer
0.712
962251AG1-071 GEN
Solar/Wind Harmer
6.45
274760LEE CO EC;1U
Adder
10.448
972236AH1-702 GEN2
Adder
2.459
238118U2-030_1
Solar/Wind Helper
0.284
20089126CSLMN_L13
Solar/Wind Helper
0.571
971313AH1-133 GEN
Solar/Wind Harmer
14.325
270132AB1-180 C
Adder
0.166
971061AG2-657 GEN
Solar/Wind Harmer
12.002
965411AG1-406 GEN
Solar/Wind Harmer
3.076
270367AC2-061_GEN
Solar/Wind Harmer
3.766
25196108MFTGT2
Adder
1.772
25196108MFTGT2
Adder
1.645
24386605FR-22G C
Solar/Wind Harmer
4.958
24387005FR-3G C
Solar/Wind Harmer
4.561
24691005MDL-2G C
Solar/Wind Harmer
4.241
25196408WSDLE3
Adder
9.904
25196308WSDLE2
Adder
9.818
25196208WSDLE1
Adder
9.794
25196708WSDLE6
Adder
9.769
238126S14_GEN_1
Solar/Wind Helper
0.669
941231AE2-117 GEN
Solar/Wind Helper
0.441
24686205CER G4
Adder
14.71
971461AH1-227 GEN
Solar/Wind Harmer
7.367
270346AE1-212 GEN
Solar/Wind Harmer
11.966
957541AF2-048 GEN
Solar/Wind Harmer
2.069
970519AG2-331 GEN
Solar/Wind Harmer
22.466
970699AG2-449 GEN
Solar/Wind Harmer
14.862
971331AH1-145 GEN
Solar/Wind Harmer
11.446
247619Y1-049
Adder
0.52
3429391JKCT 9G
Adder
9.882
958121AF2-106 GEN
Solar/Wind Harmer
5.368
970193AG2-126 GEN
Solar/Wind Harmer
17.522
24728705AND G3
Adder
9.226
970513AG2-328 GEN
Solar/Wind Harmer
20.527
970517AG2-330 GEN
Solar/Wind Harmer
18.618
25196608WSDLE5
Adder
9.621
23750701CROSSCHOOL
Solar/Wind Helper
1.181
202652Y1-033 WT C
Solar/Wind Helper
0.547
254305AE2-115 C
Solar/Wind Helper
0.203
20089026BF_G21_K23
Solar/Wind Helper
0.452
238127S14_GEN_2
Solar/Wind Helper
0.669
24318705GVG2
50/50
11.512
971191AH1-055 GEN
Solar/Wind Harmer
32.44
970243AG2-164 GEN
Solar/Wind Harmer
33.441
972273AH1-721 GEN
Adder
100.06
970093AG2-073 GEN
Solar/Wind Harmer
12.017
966571AG1-526 GEN
Solar/Wind Harmer
26.615
972167AH1-666 GEN
Solar/Wind Harmer
9.416
25196008MFTGT1
Adder
1.556
942481AE2-261 GEN
Solar/Wind Harmer
34.305
274772LINCOLN ;3U
Adder
9.447
237048AF1-022 C
Solar/Wind Helper
0.191
237043AE2-125 C
Solar/Wind Helper
0.174
972203AH1-686 GEN
Adder
4.188
962771AG1-126 GEN
Solar/Wind Harmer
51.279
970281AG2-184 GEN
Solar/Wind Harmer
30.593
962211AG1-066 GEN
Solar/Wind Harmer
3.356
274744AC1-111 GEN8
Adder
6.26
241997AF1-093 GEN
Solar/Wind Helper
0.238
20091526CHSTN_FL
Solar/Wind Helper
0.546
20090526Q36
Solar/Wind Helper
0.975
203993AD2-133_GEN1
Solar/Wind Helper
0.975
238109AE1-109 GEN2
Solar/Wind Helper
0.084
238110AE1-109 GEN3
Solar/Wind Helper
0.084
24722005FLATG5
50/50
2.714
24721905FLATG4
50/50
49.756
970153AG2-106 GEN
Solar/Wind Harmer
22.36
960911AF2-382 GEN
Solar/Wind Harmer
11.01
972103AH1-617 GEN
Solar/Wind Harmer
29.136
943031AE2-326 GEN
Solar/Wind Harmer
4.718
960741AF2-365 GEN
Solar/Wind Harmer
5.892
971155AH1-034 GEN
Solar/Wind Harmer
11.743
24728505AND G1
Adder
4.411
25194608D.CRK4
Adder
1.851
274767LEE CO EC;8U
Adder
10.325
274682WAUKEGAN ;7U
Adder
20.129
235058AG1-386 C
Solar/Wind Helper
0.436
964991AG1-363 GEN
Solar/Wind Helper
3.632
203818AF1-086 GEN
Solar/Wind Helper
1.58
24755605MDL-5G
Solar/Wind Harmer
1.072
957141AF2-008_MTX
Adder
70.533
944201AF1-088_MTX
Adder
141.066
CBM South 1LTFEXP_CBM-S1->PJM
CBM
43.304
WECLTFEXP_WEC->PJM
CLTF
4.291
LAGNLTFEXP_LAGN->PJM
CLTF
22.306
CBM South 2LTFEXP_CBM-S2->PJM
CBM
24.638
CPLELTFEXP_CPLE->PJM
CLTF
6.692
SIGELTFEXP_SIGE->PJM
CLTF
0.624
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.051
NYPJM->LTFIMP_NY
CLTF
5.171
TVALTFEXP_TVA->PJM
CLTF
11.394
AG2-052LTFEXP_AG2-052->PJM
LTF
0.261
CBM West 2LTFEXP_CBM-W2->PJM
CBM
152.177
LGEELTFEXP_LGEE->PJM
CLTF
8.351
MECLTFEXP_MEC->PJM
CLTF
18.986
AH1-155LTFEXP_AH1-155->PJM
LTF
0.391

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P1-2_#7422_16_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7422_16_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.56 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5885.34
MW Contribution:18.2
Bus #Bus NameTypeMW Contribution
24318705GVG2
50/50
11.866
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
971687AH1-348 GEN
Solar/Wind Harmer
1.161
270399AC1-101 GEN
Solar/Wind Harmer
4.077
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
966391AG1-508 GEN
Solar/Wind Harmer
1.802
972143AH1-644 GEN
Solar/Wind Harmer
12.573
24734705WLF1G3
Adder
9.185
24734905WLF1G5
Adder
9.185
24686205CER G4
Adder
16.139
942891AE2-308 GEN
Solar/Wind Harmer
9.282
972043AH1-570 GEN
Solar/Wind Harmer
2.394
971485AH1-239 GEN
Solar/Wind Harmer
7.325
971081AG2-670 GEN
Solar/Wind Harmer
6.822
24289405MTG1
50/50
11.79
971403AH1-188 GEN
Solar/Wind Harmer
18.202
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
971329AH1-144 GEN
Solar/Wind Harmer
9.676
927014AC1-188 GEN
Solar/Wind Harmer
0.006
970091AG2-072 GEN
Adder
103.033
3429421JKCT 10G
Adder
10.993
970273AG2-179 GEN
Solar/Wind Harmer
3.221
971565AH1-281 GEN
Solar/Wind Harmer
1.817
270263AC1-001 GEN
Solar/Wind Harmer
0.833
970149AG2-104 GEN
Solar/Wind Harmer
34.791
970773AG2-487 GEN
Solar/Wind Harmer
1.447
963741AG1-226 GEN
Solar/Wind Harmer
19.103
24791305MDL-5G
Solar/Wind Harmer
0.001
274854TWINGROVE;U2
Solar/Wind Harmer
0.003
944971AF1-162 GEN
Solar/Wind Harmer
13.01
24728205BUCHG1
Adder
7.763
971277AH1-098 GEN
Solar/Wind Harmer
4.634
971073AG2-665 GEN
Solar/Wind Harmer
8.448
972045AH1-571 GEN
Solar/Wind Harmer
1.918
339221AD2-048_GEN
Solar/Wind Harmer
0.006
966021AG1-471 GEN
Solar/Wind Harmer
4.953
970653AG2-424 GEN
Solar/Wind Harmer
4.368
970653AG2-424 GEN
Solar/Wind Harmer
2.263
339255AE2-071 GEN
Solar/Wind Harmer
-0.148
964571AG1-320 GEN
Solar/Wind Harmer
8.226
252509AD1-136 GEN
Solar/Wind Harmer
0.045
25183208HLCRTG
Solar/Wind Harmer
0.014
25194508D.CRK3
Adder
1.754
24728805RICHG1
Adder
4.412
276911AD2-131_GEN
Solar/Wind Harmer
1.118
24379505HDWTR1G C
Solar/Wind Harmer
0.003
270383AD1-128 GEN
Solar/Wind Harmer
0.005
945421AF1-207 GEN
Solar/Wind Harmer
0.001
960441AF2-335 GEN
Solar/Wind Harmer
7.811
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
276646AC1-214 GEN2
Solar/Wind Harmer
0.304
970885AG2-551 GEN
Solar/Wind Harmer
2.568
274765LEE CO EC;6U
Adder
10.276
274763LEE CO EC;4U
Adder
10.155
270031AE2-169
Solar/Wind Harmer
4.224
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
274695ROCKY RD ;2P
Adder
12.123
20088926STNY CRK
Solar/Wind Helper
0.747
24721605FLATG1
50/50
2.714
957241AF2-018 GEN
Solar/Wind Harmer
-0.002
270400AC1-102 GEN
Solar/Wind Harmer
4.077
24477305BRIDGE
Adder
0.637
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
941621AE2-160 GEN
Adder
5.66
24734805WLF1G4
Adder
9.185
24735105WLF2G1
Adder
9.002
3429211JKCT 2G
Adder
15.52
972163AH1-664 GEN
Solar/Wind Harmer
10.275
339243AC2-075 GEN1
Solar/Wind Harmer
0.002
970455AG2-298 GEN
Solar/Wind Harmer
6.053
25196508WSDLE4
Adder
10.49
270340AC2-060 GEN
Solar/Wind Harmer
0.01
944221AF1-090 GEN
Solar/Wind Harmer
4.776
963841AG1-237 GEN
Solar/Wind Harmer
3.474
24386205FR-12G C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270269AC2-059
Solar/Wind Harmer
0.004
970115AG2-085 GEN
Solar/Wind Harmer
3.124
276655WTG1_EQ
Solar/Wind Harmer
0.003
253400AC2-068 GEN
Solar/Wind Harmer
0.981
926823AC1-168 GEN
Solar/Wind Harmer
1.307
971609AH1-304 GEN
Solar/Wind Harmer
1.254
274746AC1-111 G10
Adder
6.069
23750501ELLIOTTS
Solar/Wind Helper
0.635
243186AF1-051 GEN
50/50
12.748
24723005RIVRG1
Adder
37.637
24723105RIVRG2
Adder
37.637
24685805CER G1
Adder
16.117
24685905CER G2
Adder
16.117
971225AH1-072 GEN
Solar/Wind Harmer
2.323
971227AH1-073 GEN
Solar/Wind Harmer
2.323
270583AD2-179 GEN
Solar/Wind Harmer
11.403
971125AH1-004 GEN
Solar/Wind Harmer
3.667
252519AF1-045_GEN
Solar/Wind Harmer
7.591
252516AE2-318_GEN
Solar/Wind Harmer
6.733
270444AC2-157 GEN1
Solar/Wind Harmer
0.004
971587AH1-292 GEN
Solar/Wind Harmer
6.388
243186AF1-051 GEN
50/50
12.748
24721805FLATG3
50/50
2.714
24721705FLATG2
50/50
49.755
24723205RIVRG3
Adder
37.637
24686105CER G3
Adder
16.224
970947AG2-589 GEN
Solar/Wind Harmer
0.42
24735205WLF2G2
Adder
9.002
971367AH1-164 GEN
Solar/Wind Harmer
3.536
270336AE1-100 GEN
Solar/Wind Harmer
0.005
971821AH1-427 GEN
Solar/Wind Harmer
9.259
945681AF1-233 GEN
Solar/Wind Harmer
17.357
943811AF1-049 GEN
Solar/Wind Harmer
-0.002
964901AG1-354 GEN
Solar/Wind Harmer
13.566
270445AC2-157 GEN2
Solar/Wind Harmer
0.004
25194608D.CRK4
Adder
2.039
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
8.469
24728605AND G2
Adder
4.525
970155AG2-107 GEN
Solar/Wind Harmer
20.57
270197AD1-017 GEN1
Solar/Wind Harmer
1.016
941821AE2-187 GEN
Solar/Wind Harmer
4.925
970613AG2-401 GEN
Solar/Wind Harmer
5.842
970291AG2-192 GEN
Solar/Wind Harmer
1.021
965031AG1-367 GEN
Solar/Wind Harmer
7.829
253370AE2-315 SEC1
Adder
2.238
253371AE2-315 SEC2
Adder
2.117
274877BISHOP HL;1U
Solar/Wind Harmer
0.26
960071AF2-298 GEN
Solar/Wind Harmer
3.815
957471AF2-041 GEN
Solar/Wind Harmer
22.952
274828WAUKEGAN ;BP
Adder
12.03
274682WAUKEGAN ;7U
Adder
19.567
274745AC1-111 GEN9
Adder
6.069
238185AF2-356 C
Solar/Wind Helper
2.176
316095T157 G97
Solar/Wind Helper
1.094
972203AH1-686 GEN
Adder
4.544
970281AG2-184 GEN
Solar/Wind Harmer
24.373
252524AE2-267 GEN
Solar/Wind Harmer
0.003
962771AG1-126 GEN
Solar/Wind Harmer
32.213
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.29
276848AB2-070 GEN3
Solar/Wind Harmer
0.289
970289AG2-191 GEN
Solar/Wind Harmer
1.493
959341AF2-225 GEN
Solar/Wind Harmer
8.194
25306009OHH W.
Adder
3.223
253372AE2-315 SEC3
Adder
2.117
253372AE2-315 SEC3
Adder
2.117
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
970169AG2-114 GEN
Solar/Wind Harmer
7.718
961011AF2-392 GEN
Solar/Wind Harmer
4.519
24318705GVG2
50/50
11.866
971191AH1-055 GEN
Solar/Wind Harmer
29.418
960161AF2-307 GEN
Solar/Wind Harmer
6.387
270186AC1-089 GEN
Solar/Wind Harmer
0.006
970239AG2-162 GEN
Solar/Wind Harmer
2.322
970107AG2-081 GEN
Solar/Wind Harmer
2.751
962581AG1-107 GEN
Solar/Wind Harmer
0.002
970235AG2-159 GEN
Solar/Wind Harmer
5.533
970235AG2-159 GEN
Solar/Wind Harmer
3.174
253394AE2-221_GEN
Solar/Wind Harmer
0.01
24686505CER G6
Adder
16.203
24728305BUCHG2
Adder
7.763
3429241JKCT 3G
Adder
15.723
339216AC1-074 GEN
Solar/Wind Harmer
0.25
962241AG1-070 GEN
Solar/Wind Harmer
4.9
252507AC2-088 GEN
Solar/Wind Harmer
0.405
270018AE2-047 C O1
Solar/Wind Harmer
0.004
962761AG1-125 GEN
Solar/Wind Harmer
32.213
965911AG1-460 GEN
Solar/Wind Harmer
1.613
276615X2-022 GEN
Solar/Wind Harmer
0.084
963831AG1-236 GEN
Solar/Wind Harmer
3.11
24385905FR-11G C
Solar/Wind Harmer
0.002
276903AD2-071 C
Solar/Wind Harmer
8.845
274857EASY ROAD;U1
Solar/Wind Harmer
0.002
274766LEE CO EC;7U
Adder
10.131
972235AH1-702 GEN1
Adder
2.767
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
25326309TAIT D
Adder
1.202
939401AE1-172 GEN
Solar/Wind Harmer
5.72
238117U2-030
Solar/Wind Helper
0.288
20088826HIGHLAND
Solar/Wind Helper
0.812
971461AH1-227 GEN
Solar/Wind Harmer
5.958
971331AH1-145 GEN
Solar/Wind Harmer
15.359
247619Y1-049
Adder
0.704
270346AE1-212 GEN
Solar/Wind Harmer
10.08
958121AF2-106 GEN
Solar/Wind Harmer
0.001
970519AG2-331 GEN
Solar/Wind Harmer
24.144
970699AG2-449 GEN
Solar/Wind Harmer
2.322
3429391JKCT 9G
Adder
10.993
958171AF2-111 GEN
Solar/Wind Harmer
22.442
270291AC1-194 GEN
Solar/Wind Harmer
7.02
25196608WSDLE5
Adder
10.598
253406AD2-031_GEN
Solar/Wind Harmer
0.624
970193AG2-126 GEN
Solar/Wind Harmer
12.39
24728705AND G3
Adder
9.464
253415AE1-040 GEN
Solar/Wind Harmer
0.003
270437AC2-090 C
Solar/Wind Harmer
0.004
970781AG2-491 GEN
Solar/Wind Harmer
7.866
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
959611AF2-252 GEN
Solar/Wind Harmer
2.614
958821AF2-173 GEN
Solar/Wind Harmer
10.961
270273AD2-016 GEN
Solar/Wind Harmer
0.81
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
274855GSG-6 ;RU
Solar/Wind Harmer
0.28
23750701CROSSCHOOL
Solar/Wind Helper
1.197
238127S14_GEN_2
Solar/Wind Helper
0.687
202652Y1-033 WT C
Solar/Wind Helper
0.534
20089026BF_G21_K23
Solar/Wind Helper
0.438
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274744AC1-111 GEN8
Adder
6.069
238109AE1-109 GEN2
Solar/Wind Helper
0.088
238110AE1-109 GEN3
Solar/Wind Helper
0.088
24722005FLATG5
50/50
2.714
24721905FLATG4
50/50
49.755
960911AF2-382 GEN
Solar/Wind Harmer
9.021
943031AE2-326 GEN
Solar/Wind Harmer
6.109
972103AH1-617 GEN
Solar/Wind Harmer
23.212
270030AE2-140 GEN
Solar/Wind Harmer
18.75
971155AH1-034 GEN
Solar/Wind Harmer
10.521
960741AF2-365 GEN
Solar/Wind Harmer
4.499
25194608D.CRK4
Adder
2.039
253316AC1-085 GEN3
Solar/Wind Harmer
0.005
253433AC1-085 GEN1
Solar/Wind Harmer
0.004
946181AF1-283 GEN
Solar/Wind Harmer
11.009
24728505AND G1
Adder
4.525
970153AG2-106 GEN
Solar/Wind Harmer
20.57
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
276668AB2-070 GEN1
Solar/Wind Harmer
0.29
24755605MDL-5G
Solar/Wind Harmer
0.001
247642Z2-115 C
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
0.864
970291AG2-192 GEN
Solar/Wind Harmer
0.786
253370AE2-315 SEC1
Adder
2.238
253371AE2-315 SEC2
Adder
2.117
946031AF1-268 GEN
Solar/Wind Harmer
7.391
3147123OTTER R
Solar/Wind Harmer
0.087
274767LEE CO EC;8U
Adder
10.131
959091AF2-200 GEN
Solar/Wind Harmer
15.301
274682WAUKEGAN ;7U
Adder
19.567
964991AG1-363 GEN
Solar/Wind Helper
3.709
316097T157 G90
Solar/Wind Helper
1.094
964781AG1-341 GEN
Solar/Wind Harmer
9.557
25194408D.CRK1
Adder
9.381
945391AF1-204 GEN
Solar/Wind Harmer
8.776
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.002
942671AE2-283 GEN
Solar/Wind Harmer
3.83
24728905RICHG2
Adder
4.412
926881AC1-175 GEN
Solar/Wind Harmer
0.001
966841AG1-555 GEN
Solar/Wind Harmer
0.9
960611AF2-352 GEN
Solar/Wind Harmer
2.614
276782AC1-033 GEN
Solar/Wind Harmer
0.001
276708O09 GEN2
Solar/Wind Harmer
0.275
972267AH1-718 GEN
Adder
4.6
970883AG2-550 GEN
Solar/Wind Harmer
7.705
274764LEE CO EC;5U
Adder
10.276
270599AE1-208 GEN
Solar/Wind Harmer
7.04
274683WAUKEGAN ;8U
Adder
22.951
274683WAUKEGAN ;8U
Adder
19.347
274693ROCKY RD ;1P
Adder
12.003
23585401KL_K28_T16
Solar/Wind Helper
1.267
23652301WDPWR_K20
Solar/Wind Helper
0.133
203955AF1-039 C O1
Solar/Wind Helper
0.352
20083426SW_E13_K22
Solar/Wind Helper
0.051
20084626FORWARD
Solar/Wind Helper
0.323
946071AF1-272 GEN
Solar/Wind Helper
2.428
253317AC1-085 GEN4
Solar/Wind Harmer
0.005
276916AD2-100_GEN
Solar/Wind Harmer
16.969
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
971613AH1-306 GEN
Solar/Wind Harmer
3.767
253370AE2-315 SEC1
Adder
2.238
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276741O09 GEN1
Solar/Wind Harmer
0.275
25322209TAIT E
Adder
10.707
25322209TAIT E
Adder
10.466
971341AH1-150 GEN
Solar/Wind Harmer
15.301
971343AH1-151 GEN
Solar/Wind Harmer
15.301
247621Y3-024
Adder
0.262
238120AE2-309 GEN
Solar/Wind Helper
0.43
971313AH1-133 GEN
Solar/Wind Harmer
12.016
270132AB1-180 C
Adder
0.198
971061AG2-657 GEN
Solar/Wind Harmer
6.864
970879AG2-548 GEN
Solar/Wind Harmer
8.448
965411AG1-406 GEN
Solar/Wind Harmer
3.428
270367AC2-061_GEN
Solar/Wind Harmer
0.007
25196108MFTGT2
Adder
1.926
25196108MFTGT2
Adder
1.788
25196408WSDLE3
Adder
10.91
25196308WSDLE2
Adder
10.815
25196208WSDLE1
Adder
10.788
25196708WSDLE6
Adder
10.761
270240V3-007_GEN2
Solar/Wind Harmer
0.002
276174W4-005 GEN2
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
270594AE1-207 GEN
Solar/Wind Harmer
8.791
971673AH1-337 GEN
Solar/Wind Harmer
5.07
957751AF2-069 GEN
Solar/Wind Harmer
0.255
270543AE2-219 C
Solar/Wind Harmer
0.005
253398AE2-221_GEN2
Solar/Wind Harmer
0.01
970241AG2-163 GEN
Solar/Wind Harmer
4.709
270209AC1-174_GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
970825AG2-519 GEN
Solar/Wind Harmer
8.658
276645AC1-214 GEN1
Solar/Wind Harmer
0.304
276603SUBLETTE C
Solar/Wind Harmer
0
274762LEE CO EC;3U
Adder
10.252
938861AE1-114 GEN
Solar/Wind Harmer
4.353
274856ECOGROVE ;U1
Solar/Wind Harmer
0.181
276611AD2-172 GEN
Solar/Wind Harmer
0.002
270013AE1-250 PV
Solar/Wind Harmer
0.004
274696ROCKY RD ;4P
Adder
12.409
274697ROCKY RD ;3P
Adder
3.293
944781AF1-143 GEN
Solar/Wind Helper
2.298
203940AF1-140 C
Solar/Wind Helper
0.359
971315AH1-136 GEN
Solar/Wind Harmer
2.301
970333AG2-219 GEN
Solar/Wind Harmer
6.64
25196808ZIMRHP
Adder
95.812
25196008MFTGT1
Adder
1.747
3147312GRETNA
Solar/Wind Harmer
0.031
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0.001
274880W4-005 GEN4
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.003
972175AH1-670 GEN
Solar/Wind Harmer
6.537
270032AE2-172
Solar/Wind Harmer
5.233
270005AE1-210 C O1
Solar/Wind Harmer
1.696
970825AG2-519 GEN
Solar/Wind Harmer
2.773
939741AE1-205 GEN
Solar/Wind Harmer
10.926
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
9.649
276158O29GEN2
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
10.252
970569AG2-363 GEN
Solar/Wind Harmer
23.052
971997AH1-543 GEN
Solar/Wind Harmer
4.011
276861AD2-134 GEN
Solar/Wind Harmer
0.137
945371AF1-202 GEN
Solar/Wind Harmer
0.001
237046AF1-021 C
Solar/Wind Helper
0.457
23751201ROTHROCK
Solar/Wind Helper
0.71
23583801GRNGAP
Solar/Wind Helper
4.088
20089226LOOKOUT
Solar/Wind Helper
0.539
24289405MTG1
50/50
11.79
24686405CER G5
Adder
16.075
270053AF1-130 C
Solar/Wind Harmer
2.937
970913AG2-568 GEN
Solar/Wind Harmer
9.858
270173AC1-122 GEN
Solar/Wind Harmer
0.435
970273AG2-179 GEN
Solar/Wind Harmer
5.522
339250AF1-203 GEN
Solar/Wind Harmer
0.001
962251AG1-071 GEN
Solar/Wind Harmer
5.619
941801AE2-185 GEN
Solar/Wind Harmer
4.925
270356AE2-297 GEN
Solar/Wind Harmer
0.011
270222AC2-111 GEN
Solar/Wind Harmer
4.144
276686W4-005 GEN3
Solar/Wind Harmer
0.001
972173AH1-669 GEN
Solar/Wind Harmer
3.965
965091AG1-374 GEN
Solar/Wind Harmer
23.525
270004AE1-209 GEN
Solar/Wind Harmer
1.696
965931AG1-462 GEN
Solar/Wind Harmer
19.808
274878BISHOP HL;2U
Solar/Wind Harmer
0.26
970191AG2-125 GEN
Solar/Wind Harmer
1.992
274760LEE CO EC;1U
Adder
10.252
972236AH1-702 GEN2
Adder
2.406
238118U2-030_1
Solar/Wind Helper
0.288
20089126CSLMN_L13
Solar/Wind Helper
0.554
276726Z2-087_GEN
Solar/Wind Harmer
0.003
971475AH1-234 GEN
Solar/Wind Harmer
3.722
970819AG2-516 GEN
Solar/Wind Harmer
9.198
274822ROCKFORD ;11
Adder
21.533
959081AF2-199 GEN
Solar/Wind Harmer
7.651
971067AG2-660 GEN
Solar/Wind Harmer
2.55
235054AD2-180 GEN
Solar/Wind Helper
1.695
235531U2-073 GEN
Solar/Wind Helper
2.733
23562501BACKB
Solar/Wind Helper
0.864
238108AE1-109 GEN1
Solar/Wind Helper
0.088
972273AH1-721 GEN
Adder
111.61
970093AG2-073 GEN
Solar/Wind Harmer
9.318
970243AG2-164 GEN
Solar/Wind Harmer
5.432
966571AG1-526 GEN
Solar/Wind Harmer
20.57
972167AH1-666 GEN
Solar/Wind Harmer
7.359
962751AG1-124 GEN
Solar/Wind Harmer
8.092
25196008MFTGT1
Adder
1.692
252510AF1-249 C
Solar/Wind Harmer
0.067
3147312GRETNA
Solar/Wind Harmer
0.123
3146802CHATHAM
Solar/Wind Harmer
0.115
942481AE2-261 GEN
Solar/Wind Harmer
24.109
276621W2-048 GEN
Solar/Wind Harmer
0.403
276838X2-022 GEN2
Solar/Wind Harmer
0.45
971993AH1-541 GEN
Solar/Wind Harmer
3.68
942111AE2-223 GEN
Solar/Wind Harmer
2.536
276157O29GEN1
Solar/Wind Harmer
1.248
274858EASY ROAD;U2
Solar/Wind Harmer
0.002
970571AG2-364 GEN
Solar/Wind Harmer
15.368
276889AE2-281 GEN
Solar/Wind Harmer
0.001
270016AE1-250 BESS
Solar/Wind Harmer
0.004
274850MENDOTA H;RU
Solar/Wind Harmer
0.09
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.137
274729ELWOOD EC;1P
Adder
8.072
237048AF1-022 C
Solar/Wind Helper
0.182
237043AE2-125 C
Solar/Wind Helper
0.163
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
0.329
971985AH1-537 GEN
Solar/Wind Harmer
3.047
971981AH1-535 GEN
Solar/Wind Harmer
6.609
270069AE2-166 C O1
Solar/Wind Harmer
0.007
965401AG1-405 GEN
Solar/Wind Harmer
5.328
339211AE2-254 GEN
Solar/Wind Harmer
0.004
972165AH1-665 GEN
Solar/Wind Harmer
8.229
24386405FR-21G C
Solar/Wind Harmer
0.001
24725505WLD G2 C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.002
270181AB1-006 GEN2
Solar/Wind Harmer
0
276656WTG2_EQ
Solar/Wind Harmer
0
941731AE2-173 GEN
Solar/Wind Harmer
6.503
971029AG2-637 GEN
Solar/Wind Harmer
11.666
946321AF1-296 GEN
Solar/Wind Harmer
4.345
253349AC2-067 GEN
Solar/Wind Harmer
2.438
971611AH1-305 GEN
Solar/Wind Harmer
4.596
274823ROCKFORD ;21
Adder
21.377
971171AH1-044 GEN
Solar/Wind Harmer
15.301
971675AH1-338 GEN
Solar/Wind Harmer
2.979
945581AF1-223 GEN
Solar/Wind Harmer
0.001
20092526R32
Solar/Wind Helper
1.053
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
971681AH1-341 GEN
Solar/Wind Harmer
12.366
276612AE2-035 GEN
Solar/Wind Harmer
0.002
238126S14_GEN_1
Solar/Wind Helper
0.687
957141AF2-008_MTX
Adder
72.592
944201AF1-088_MTX
Adder
145.184
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.592
NYPJM->LTFIMP_NY
CLTF
5.271
TVALTFEXP_TVA->PJM
CLTF
12.655
AG2-052LTFEXP_AG2-052->PJM
LTF
0.253
CBM West 2LTFEXP_CBM-W2->PJM
CBM
162.06
LGEELTFEXP_LGEE->PJM
CLTF
8.989
MECLTFEXP_MEC->PJM
CLTF
19.173
AH1-155LTFEXP_AH1-155->PJM
LTF
0.38
CBM South 1LTFEXP_CBM-S1->PJM
CBM
47.815
WECLTFEXP_WEC->PJM
CLTF
4.2
LAGNLTFEXP_LAGN->PJM
CLTF
24.37
CBM South 2LTFEXP_CBM-S2->PJM
CBM
29.03
CPLELTFEXP_CPLE->PJM
CLTF
7.791
SIGELTFEXP_SIGE->PJM
CLTF
0.659

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P7-1_#10944___SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10944___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:106.16 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5863.47
MW Contribution:24.8
Bus #Bus NameTypeMW Contribution
243186AF1-051 GEN
50/50
12.611
24721805FLATG3
50/50
2.658
24721705FLATG2
50/50
48.723
24723205RIVRG3
Adder
37.09
970947AG2-589 GEN
Solar/Wind Harmer
3.922
24686105CER G3
Adder
16.263
24735205WLF2G2
Adder
7.999
945681AF1-233 GEN
Solar/Wind Harmer
22.966
243186AF1-051 GEN
50/50
12.611
942891AE2-308 GEN
Solar/Wind Harmer
12.168
972043AH1-570 GEN
Solar/Wind Harmer
3.032
971485AH1-239 GEN
Solar/Wind Harmer
9.472
971081AG2-670 GEN
Solar/Wind Harmer
8.855
270330AC1-082 GEN2
Solar/Wind Harmer
1.51
270399AC1-101 GEN
Solar/Wind Harmer
7.483
972143AH1-644 GEN
Solar/Wind Harmer
15.443
971985AH1-537 GEN
Solar/Wind Harmer
26.909
24734705WLF1G3
Adder
8.169
24734905WLF1G5
Adder
8.169
966391AG1-508 GEN
Solar/Wind Harmer
4.787
971981AH1-535 GEN
Solar/Wind Harmer
12.632
972165AH1-665 GEN
Solar/Wind Harmer
9.771
965401AG1-405 GEN
Solar/Wind Harmer
6.93
339211AE2-254 GEN
Solar/Wind Harmer
1.83
270069AE2-166 C O1
Solar/Wind Harmer
3.07
944031AF1-071 GEN
Solar/Wind Harmer
1.053
274823ROCKFORD ;21
Adder
18.572
20092526R32
Solar/Wind Helper
1.083
203846AF2-130 C
Solar/Wind Helper
0.425
24289405MTG1
50/50
11.76
960001AF2-291 GEN
Solar/Wind Harmer
6.065
971403AH1-188 GEN
Solar/Wind Harmer
24.803
927014AC1-188 GEN
Solar/Wind Harmer
2.455
971329AH1-144 GEN
Solar/Wind Harmer
16.096
970091AG2-072 GEN
Adder
94.679
3429421JKCT 10G
Adder
10.046
970273AG2-179 GEN
Solar/Wind Harmer
2.912
971565AH1-281 GEN
Solar/Wind Harmer
2.371
270263AC1-001 GEN
Solar/Wind Harmer
1.114
963741AG1-226 GEN
Solar/Wind Harmer
46.021
274822ROCKFORD ;11
Adder
18.707
235054AD2-180 GEN
Solar/Wind Helper
1.616
23562501BACKB
Solar/Wind Helper
0.85
235531U2-073 GEN
Solar/Wind Helper
2.555
20094526CT_V3-030
Solar/Wind Helper
0.44
970149AG2-104 GEN
Solar/Wind Harmer
20.717
24686505CER G6
Adder
16.242
24728305BUCHG2
Adder
6.985
3429241JKCT 3G
Adder
14.375
339216AC1-074 GEN
Solar/Wind Harmer
2.018
252507AC2-088 GEN
Solar/Wind Harmer
2.122
962241AG1-070 GEN
Solar/Wind Harmer
5.234
965911AG1-460 GEN
Solar/Wind Harmer
1.423
962761AG1-125 GEN
Solar/Wind Harmer
40.758
274766LEE CO EC;7U
Adder
8.813
972235AH1-702 GEN1
Adder
2.404
25326309TAIT D
Adder
1.04
238117U2-030
Solar/Wind Helper
0.272
20088826HIGHLAND
Solar/Wind Helper
0.835
964781AG1-341 GEN
Solar/Wind Harmer
12.366
25194408D.CRK1
Adder
8.581
945391AF1-204 GEN
Solar/Wind Harmer
14.686
24728905RICHG2
Adder
3.931
972267AH1-718 GEN
Adder
4.004
274764LEE CO EC;5U
Adder
8.939
274683WAUKEGAN ;8U
Adder
19.896
274683WAUKEGAN ;8U
Adder
16.771
274693ROCKY RD ;1P
Adder
10.405
23652301WDPWR_K20
Solar/Wind Helper
0.139
241967AE2-285_GEN
Solar/Wind Helper
0.613
23585401KL_K28_T16
Solar/Wind Helper
1.223
203955AF1-039 C O1
Solar/Wind Helper
0.352
946071AF1-272 GEN
Solar/Wind Helper
2.537
20083426SW_E13_K22
Solar/Wind Helper
0.052
20084626FORWARD
Solar/Wind Helper
0.332
24723005RIVRG1
Adder
37.09
24723105RIVRG2
Adder
37.09
24685805CER G1
Adder
16.156
24685905CER G2
Adder
16.156
971225AH1-072 GEN
Solar/Wind Harmer
3.044
971227AH1-073 GEN
Solar/Wind Harmer
3.044
270214AC2-123 GEN
Solar/Wind Harmer
3.214
971821AH1-427 GEN
Solar/Wind Harmer
12.078
943111AE2-339 GEN
Solar/Wind Harmer
1.064
339241AF1-083 GEN
Solar/Wind Harmer
1.967
964901AG1-354 GEN
Solar/Wind Harmer
17.575
25194608D.CRK4
Adder
1.865
270336AE1-100 GEN
Solar/Wind Harmer
1.949
270445AC2-157 GEN2
Solar/Wind Harmer
6.293
253432AC1-085 GEN2
Solar/Wind Harmer
0.293
946171AF1-282 GEN
Solar/Wind Harmer
10.953
971367AH1-164 GEN
Solar/Wind Harmer
3.823
943811AF1-049 GEN
Solar/Wind Harmer
4.073
24728605AND G2
Adder
4.036
253370AE2-315 SEC1
Adder
1.951
253371AE2-315 SEC2
Adder
1.845
274828WAUKEGAN ;BP
Adder
10.429
274682WAUKEGAN ;7U
Adder
16.961
274745AC1-111 GEN9
Adder
5.257
241966AE1-183 GEN
Solar/Wind Helper
0.245
238185AF2-356 C
Solar/Wind Helper
2.079
964201AG1-281 GEN
Solar/Wind Helper
0.449
270583AD2-179 GEN
Solar/Wind Harmer
12.914
971125AH1-004 GEN
Solar/Wind Harmer
4.815
252519AF1-045_GEN
Solar/Wind Harmer
6.963
252516AE2-318_GEN
Solar/Wind Harmer
5.311
270444AC2-157 GEN1
Solar/Wind Harmer
6.293
253317AC1-085 GEN4
Solar/Wind Harmer
9.175
276916AD2-100_GEN
Solar/Wind Harmer
21.483
957381AF2-032 GEN
Solar/Wind Harmer
0.427
253370AE2-315 SEC1
Adder
1.951
25322209TAIT E
Adder
9.264
25322209TAIT E
Adder
9.056
247621Y3-024
Adder
0.228
241801AE1-079 GEN
Solar/Wind Helper
0.238
238120AE2-309 GEN
Solar/Wind Helper
0.4
20303426NA_O38_P22
Solar/Wind Helper
0.919
203853AF1-134 C O1
Solar/Wind Helper
0.443
944971AF1-162 GEN
Solar/Wind Harmer
12.489
24728205BUCHG1
Adder
6.985
971277AH1-098 GEN
Solar/Wind Harmer
5.494
971073AG2-665 GEN
Solar/Wind Harmer
8.094
971073AG2-665 GEN
Solar/Wind Harmer
5.647
972045AH1-571 GEN
Solar/Wind Harmer
2.426
339221AD2-048_GEN
Solar/Wind Harmer
1.861
339231AF1-038_GEN
Solar/Wind Harmer
2.165
966021AG1-471 GEN
Solar/Wind Harmer
6.404
252509AD1-136 GEN
Solar/Wind Harmer
0.303
970653AG2-424 GEN
Solar/Wind Harmer
5.682
970653AG2-424 GEN
Solar/Wind Harmer
2.054
964571AG1-320 GEN
Solar/Wind Harmer
9.614
339255AE2-071 GEN
Solar/Wind Harmer
1.239
25183208HLCRTG
Solar/Wind Harmer
6.95
25194508D.CRK3
Adder
1.604
24728805RICHG1
Adder
3.931
276911AD2-131_GEN
Solar/Wind Harmer
4.342
274765LEE CO EC;6U
Adder
8.939
274763LEE CO EC;4U
Adder
8.834
274695ROCKY RD ;2P
Adder
10.508
20088926STNY CRK
Solar/Wind Helper
0.764
946381AF1-302 GEN
Solar/Wind Helper
0.207
20088626ARWF_N39
Solar/Wind Helper
1.121
24721605FLATG1
50/50
2.658
270329AC1-082 GEN1
Solar/Wind Harmer
0.889
24318705GVG2
50/50
11.739
270331AC1-082 GEN3
Solar/Wind Harmer
0.892
971315AH1-136 GEN
Solar/Wind Harmer
3.105
971687AH1-348 GEN
Solar/Wind Harmer
1.523
970333AG2-219 GEN
Solar/Wind Harmer
38.461
25196808ZIMRHP
Adder
88.001
25196008MFTGT1
Adder
1.601
274761LEE CO EC;2U
Adder
8.918
237046AF1-021 C
Solar/Wind Helper
0.476
254303AC2-168 GEN
Solar/Wind Helper
0.153
23751201ROTHROCK
Solar/Wind Helper
0.699
20089226LOOKOUT
Solar/Wind Helper
0.545
970879AG2-548 GEN
Solar/Wind Harmer
8.094
960161AF2-307 GEN
Solar/Wind Harmer
8.235
270186AC1-089 GEN
Solar/Wind Harmer
7.622
962581AG1-107 GEN
Solar/Wind Harmer
6.151
961491AF2-440 GEN
Solar/Wind Harmer
2.556
970239AG2-162 GEN
Solar/Wind Harmer
13.403
970107AG2-081 GEN
Solar/Wind Harmer
3.611
970235AG2-159 GEN
Solar/Wind Harmer
4.78
970235AG2-159 GEN
Solar/Wind Harmer
2.918
339236AF1-050_GEN
Solar/Wind Harmer
2.132
253394AE2-221_GEN
Solar/Wind Harmer
4.786
253398AE2-221_GEN2
Solar/Wind Harmer
4.786
970241AG2-163 GEN
Solar/Wind Harmer
25.567
274762LEE CO EC;3U
Adder
8.918
274696ROCKY RD ;4P
Adder
10.757
274697ROCKY RD ;3P
Adder
2.855
962101AG1-054 GEN
Solar/Wind Helper
0.626
241985AE1-237 GEN
Solar/Wind Helper
0.238
944781AF1-143 GEN
Solar/Wind Helper
2.323
203940AF1-140 C
Solar/Wind Helper
0.368
24477305BRIDGE
Adder
0.635
957241AF2-018 GEN
Solar/Wind Harmer
7.929
270400AC1-102 GEN
Solar/Wind Harmer
7.483
941621AE2-160 GEN
Adder
5.566
24734805WLF1G4
Adder
8.169
24735105WLF2G1
Adder
7.999
972163AH1-664 GEN
Solar/Wind Harmer
12.214
3429211JKCT 2G
Adder
14.189
339243AC2-075 GEN1
Solar/Wind Harmer
0.546
970455AG2-298 GEN
Solar/Wind Harmer
7.102
25196508WSDLE4
Adder
9.582
270340AC2-060 GEN
Solar/Wind Harmer
3.233
944221AF1-090 GEN
Solar/Wind Harmer
11.289
274746AC1-111 G10
Adder
5.257
23750501ELLIOTTS
Solar/Wind Helper
0.642
254304AE2-114 C
Solar/Wind Helper
0.211
241982AE2-343 S C
Solar/Wind Helper
0.214
203961AE2-224 GEN
Solar/Wind Helper
2.23
24289405MTG1
50/50
11.76
24686405CER G5
Adder
16.113
270053AF1-130 C
Solar/Wind Harmer
6.632
970913AG2-568 GEN
Solar/Wind Harmer
13.469
970273AG2-179 GEN
Solar/Wind Harmer
4.651
339250AF1-203 GEN
Solar/Wind Harmer
0.708
962251AG1-071 GEN
Solar/Wind Harmer
6.397
270356AE2-297 GEN
Solar/Wind Harmer
4.782
270132AB1-180 C
Adder
0.184
971313AH1-133 GEN
Solar/Wind Harmer
15.282
971061AG2-657 GEN
Solar/Wind Harmer
13.752
970879AG2-548 GEN
Solar/Wind Harmer
5.647
270367AC2-061_GEN
Solar/Wind Harmer
3.956
965411AG1-406 GEN
Solar/Wind Harmer
3.11
25196108MFTGT2
Adder
1.765
25196108MFTGT2
Adder
1.639
25196408WSDLE3
Adder
9.966
25196308WSDLE2
Adder
9.88
25196208WSDLE1
Adder
9.855
25196708WSDLE6
Adder
9.83
238126S14_GEN_1
Solar/Wind Helper
0.64
24686205CER G4
Adder
16.177
957541AF2-048 GEN
Solar/Wind Harmer
2.449
971461AH1-227 GEN
Solar/Wind Harmer
7.809
270346AE1-212 GEN
Solar/Wind Harmer
13.257
971331AH1-145 GEN
Solar/Wind Harmer
12.477
247619Y1-049
Adder
0.564
958121AF2-106 GEN
Solar/Wind Harmer
5.853
970519AG2-331 GEN
Solar/Wind Harmer
21.141
970699AG2-449 GEN
Solar/Wind Harmer
13.986
270291AC1-194 GEN
Solar/Wind Harmer
12.828
3429391JKCT 9G
Adder
10.046
958171AF2-111 GEN
Solar/Wind Harmer
29.515
25196608WSDLE5
Adder
9.681
253406AD2-031_GEN
Solar/Wind Harmer
1.378
970193AG2-126 GEN
Solar/Wind Harmer
15.807
24728705AND G3
Adder
8.441
253415AE1-040 GEN
Solar/Wind Harmer
1.167
254305AE2-115 C
Solar/Wind Helper
0.211
202652Y1-033 WT C
Solar/Wind Helper
0.534
23750701CROSSCHOOL
Solar/Wind Helper
1.129
20089026BF_G21_K23
Solar/Wind Helper
0.443
238127S14_GEN_2
Solar/Wind Helper
0.64
270222AC2-111 GEN
Solar/Wind Harmer
8.539
274760LEE CO EC;1U
Adder
8.918
972236AH1-702 GEN2
Adder
2.091
20089126CSLMN_L13
Solar/Wind Helper
0.56
238118U2-030_1
Solar/Wind Helper
0.272
959441AF2-235 GEN
Solar/Wind Helper
0.22
24318705GVG2
50/50
11.739
971191AH1-055 GEN
Solar/Wind Harmer
39.064
970093AG2-073 GEN
Solar/Wind Harmer
12.205
970243AG2-164 GEN
Solar/Wind Harmer
31.468
972167AH1-666 GEN
Solar/Wind Harmer
9.735
972273AH1-721 GEN
Adder
101.075
966571AG1-526 GEN
Solar/Wind Harmer
26.852
25196008MFTGT1
Adder
1.55
252510AF1-249 C
Solar/Wind Harmer
0.477
942481AE2-261 GEN
Solar/Wind Harmer
30.502
274729ELWOOD EC;1P
Adder
6.986
237048AF1-022 C
Solar/Wind Helper
0.187
237043AE2-125 C
Solar/Wind Helper
0.173
972203AH1-686 GEN
Adder
4.44
970281AG2-184 GEN
Solar/Wind Harmer
32.43
962211AG1-066 GEN
Solar/Wind Harmer
3.527
252524AE2-267 GEN
Solar/Wind Harmer
1.782
962771AG1-126 GEN
Solar/Wind Harmer
40.758
25306009OHH W.
Adder
2.813
253372AE2-315 SEC3
Adder
1.845
253372AE2-315 SEC3
Adder
1.845
274744AC1-111 GEN8
Adder
5.257
241997AF1-093 GEN
Solar/Wind Helper
0.245
20091526CHSTN_FL
Solar/Wind Helper
0.54
20090526Q36
Solar/Wind Helper
0.964
203993AD2-133_GEN1
Solar/Wind Helper
0.964
24722005FLATG5
50/50
2.658
24721905FLATG4
50/50
48.723
960911AF2-382 GEN
Solar/Wind Harmer
11.728
972103AH1-617 GEN
Solar/Wind Harmer
30.886
943031AE2-326 GEN
Solar/Wind Harmer
5.058
971155AH1-034 GEN
Solar/Wind Harmer
11.668
960741AF2-365 GEN
Solar/Wind Harmer
5.83
25194608D.CRK4
Adder
1.865
270030AE2-140 GEN
Solar/Wind Harmer
22.032
253316AC1-085 GEN3
Solar/Wind Harmer
9.175
253433AC1-085 GEN1
Solar/Wind Harmer
5.824
946181AF1-283 GEN
Solar/Wind Harmer
14.239
24728505AND G1
Adder
4.036
253370AE2-315 SEC1
Adder
1.951
253371AE2-315 SEC2
Adder
1.845
274767LEE CO EC;8U
Adder
8.813
274682WAUKEGAN ;7U
Adder
16.961
235058AG1-386 C
Solar/Wind Helper
0.451
964991AG1-363 GEN
Solar/Wind Helper
3.463
203818AF1-086 GEN
Solar/Wind Helper
1.57
957141AF2-008_MTX
Adder
65.52
944201AF1-088_MTX
Adder
131.041
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.529
NYPJM->LTFIMP_NY
CLTF
5.029
TVALTFEXP_TVA->PJM
CLTF
11.299
AG2-052LTFEXP_AG2-052->PJM
LTF
0.22
CBM West 2LTFEXP_CBM-W2->PJM
CBM
144.471
LGEELTFEXP_LGEE->PJM
CLTF
8.22
MECLTFEXP_MEC->PJM
CLTF
16.832
AH1-155LTFEXP_AH1-155->PJM
LTF
0.329
CBM South 1LTFEXP_CBM-S1->PJM
CBM
42.883
WECLTFEXP_WEC->PJM
CLTF
3.65
LAGNLTFEXP_LAGN->PJM
CLTF
21.71
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.108
CPLELTFEXP_CPLE->PJM
CLTF
7.285
SIGELTFEXP_SIGE->PJM
CLTF
0.595

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P7-1_#10856___SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10856___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:102.19 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5644.14
MW Contribution:24.98
Bus #Bus NameTypeMW Contribution
270330AC1-082 GEN2
Solar/Wind Harmer
1.52
270399AC1-101 GEN
Solar/Wind Harmer
7.536
972143AH1-644 GEN
Solar/Wind Harmer
15.567
971985AH1-537 GEN
Solar/Wind Harmer
27.131
24734705WLF1G3
Adder
8.24
24734905WLF1G5
Adder
8.24
966391AG1-508 GEN
Solar/Wind Harmer
4.83
971981AH1-535 GEN
Solar/Wind Harmer
12.756
972165AH1-665 GEN
Solar/Wind Harmer
9.871
965401AG1-405 GEN
Solar/Wind Harmer
7.001
339211AE2-254 GEN
Solar/Wind Harmer
1.849
270069AE2-166 C O1
Solar/Wind Harmer
3.104
944031AF1-071 GEN
Solar/Wind Harmer
1.065
24289405MTG1
50/50
11.814
960001AF2-291 GEN
Solar/Wind Harmer
6.103
971403AH1-188 GEN
Solar/Wind Harmer
24.977
927014AC1-188 GEN
Solar/Wind Harmer
2.475
971329AH1-144 GEN
Solar/Wind Harmer
16.245
970091AG2-072 GEN
Adder
95.631
3429421JKCT 10G
Adder
10.15
970273AG2-179 GEN
Solar/Wind Harmer
2.943
971565AH1-281 GEN
Solar/Wind Harmer
2.396
270263AC1-001 GEN
Solar/Wind Harmer
1.127
963741AG1-226 GEN
Solar/Wind Harmer
46.579
274822ROCKFORD ;11
Adder
18.951
235054AD2-180 GEN
Solar/Wind Helper
1.594
23562501BACKB
Solar/Wind Helper
0.838
235531U2-073 GEN
Solar/Wind Helper
2.519
20094526CT_V3-030
Solar/Wind Helper
0.433
970149AG2-104 GEN
Solar/Wind Harmer
20.97
24686505CER G6
Adder
16.345
24728305BUCHG2
Adder
7.041
3429241JKCT 3G
Adder
14.522
339216AC1-074 GEN
Solar/Wind Harmer
2.039
252507AC2-088 GEN
Solar/Wind Harmer
2.144
962241AG1-070 GEN
Solar/Wind Harmer
5.29
965911AG1-460 GEN
Solar/Wind Harmer
1.441
962761AG1-125 GEN
Solar/Wind Harmer
41.255
274766LEE CO EC;7U
Adder
8.927
972235AH1-702 GEN1
Adder
2.436
25326309TAIT D
Adder
1.054
238117U2-030
Solar/Wind Helper
0.268
20088826HIGHLAND
Solar/Wind Helper
0.824
942891AE2-308 GEN
Solar/Wind Harmer
12.292
972043AH1-570 GEN
Solar/Wind Harmer
3.063
971485AH1-239 GEN
Solar/Wind Harmer
9.571
971081AG2-670 GEN
Solar/Wind Harmer
8.948
964781AG1-341 GEN
Solar/Wind Harmer
12.498
25194408D.CRK1
Adder
8.675
945391AF1-204 GEN
Solar/Wind Harmer
14.859
24728905RICHG2
Adder
3.978
972267AH1-718 GEN
Adder
4.056
274764LEE CO EC;5U
Adder
9.055
274683WAUKEGAN ;8U
Adder
20.157
274683WAUKEGAN ;8U
Adder
16.992
274693ROCKY RD ;1P
Adder
10.542
23652301WDPWR_K20
Solar/Wind Helper
0.138
243186AF1-051 GEN
50/50
12.674
24721805FLATG3
50/50
2.672
24721705FLATG2
50/50
48.99
24723205RIVRG3
Adder
37.324
970947AG2-589 GEN
Solar/Wind Harmer
3.947
24686105CER G3
Adder
16.366
24735205WLF2G2
Adder
8.071
945681AF1-233 GEN
Solar/Wind Harmer
23.2
971821AH1-427 GEN
Solar/Wind Harmer
12.202
943111AE2-339 GEN
Solar/Wind Harmer
1.075
339241AF1-083 GEN
Solar/Wind Harmer
1.988
964901AG1-354 GEN
Solar/Wind Harmer
17.761
25194608D.CRK4
Adder
1.886
270336AE1-100 GEN
Solar/Wind Harmer
1.97
270445AC2-157 GEN2
Solar/Wind Harmer
6.363
253432AC1-085 GEN2
Solar/Wind Harmer
0.297
946171AF1-282 GEN
Solar/Wind Harmer
11.077
971367AH1-164 GEN
Solar/Wind Harmer
3.867
943811AF1-049 GEN
Solar/Wind Harmer
4.12
24728605AND G2
Adder
4.084
253370AE2-315 SEC1
Adder
1.976
253371AE2-315 SEC2
Adder
1.869
274828WAUKEGAN ;BP
Adder
10.566
274682WAUKEGAN ;7U
Adder
17.184
274745AC1-111 GEN9
Adder
5.326
241966AE1-183 GEN
Solar/Wind Helper
0.242
238185AF2-356 C
Solar/Wind Helper
2.051
964201AG1-281 GEN
Solar/Wind Helper
0.442
243186AF1-051 GEN
50/50
12.674
24723005RIVRG1
Adder
37.324
24723105RIVRG2
Adder
37.324
24685805CER G1
Adder
16.259
24685905CER G2
Adder
16.259
971225AH1-072 GEN
Solar/Wind Harmer
3.069
971227AH1-073 GEN
Solar/Wind Harmer
3.069
944971AF1-162 GEN
Solar/Wind Harmer
12.576
24728205BUCHG1
Adder
7.041
971277AH1-098 GEN
Solar/Wind Harmer
5.544
971073AG2-665 GEN
Solar/Wind Harmer
8.171
971073AG2-665 GEN
Solar/Wind Harmer
5.701
972045AH1-571 GEN
Solar/Wind Harmer
2.45
339221AD2-048_GEN
Solar/Wind Harmer
1.88
339231AF1-038_GEN
Solar/Wind Harmer
2.187
966021AG1-471 GEN
Solar/Wind Harmer
6.471
252509AD1-136 GEN
Solar/Wind Harmer
0.306
970653AG2-424 GEN
Solar/Wind Harmer
5.742
970653AG2-424 GEN
Solar/Wind Harmer
2.076
964571AG1-320 GEN
Solar/Wind Harmer
9.715
339255AE2-071 GEN
Solar/Wind Harmer
1.252
25183208HLCRTG
Solar/Wind Harmer
7.025
25194508D.CRK3
Adder
1.622
24728805RICHG1
Adder
3.978
276911AD2-131_GEN
Solar/Wind Harmer
4.394
274765LEE CO EC;6U
Adder
9.055
274763LEE CO EC;4U
Adder
8.948
274695ROCKY RD ;2P
Adder
10.646
20088926STNY CRK
Solar/Wind Helper
0.754
24318705GVG2
50/50
11.798
270331AC1-082 GEN3
Solar/Wind Harmer
0.897
971315AH1-136 GEN
Solar/Wind Harmer
3.129
971687AH1-348 GEN
Solar/Wind Harmer
1.535
970333AG2-219 GEN
Solar/Wind Harmer
38.852
25196808ZIMRHP
Adder
88.943
25196008MFTGT1
Adder
1.618
274761LEE CO EC;2U
Adder
9.033
237046AF1-021 C
Solar/Wind Helper
0.471
254303AC2-168 GEN
Solar/Wind Helper
0.151
23751201ROTHROCK
Solar/Wind Helper
0.69
20089226LOOKOUT
Solar/Wind Helper
0.537
970879AG2-548 GEN
Solar/Wind Harmer
8.171
960161AF2-307 GEN
Solar/Wind Harmer
8.314
270186AC1-089 GEN
Solar/Wind Harmer
7.697
962581AG1-107 GEN
Solar/Wind Harmer
6.214
961491AF2-440 GEN
Solar/Wind Harmer
2.582
970239AG2-162 GEN
Solar/Wind Harmer
13.539
970107AG2-081 GEN
Solar/Wind Harmer
3.648
970235AG2-159 GEN
Solar/Wind Harmer
4.83
970235AG2-159 GEN
Solar/Wind Harmer
2.948
339236AF1-050_GEN
Solar/Wind Harmer
2.155
253394AE2-221_GEN
Solar/Wind Harmer
4.843
253398AE2-221_GEN2
Solar/Wind Harmer
4.843
970241AG2-163 GEN
Solar/Wind Harmer
25.877
274762LEE CO EC;3U
Adder
9.033
274696ROCKY RD ;4P
Adder
10.898
274697ROCKY RD ;3P
Adder
2.892
962101AG1-054 GEN
Solar/Wind Helper
0.618
241985AE1-237 GEN
Solar/Wind Helper
0.235
944781AF1-143 GEN
Solar/Wind Helper
2.291
203940AF1-140 C
Solar/Wind Helper
0.363
24721605FLATG1
50/50
2.672
270329AC1-082 GEN1
Solar/Wind Harmer
0.895
24477305BRIDGE
Adder
0.639
957241AF2-018 GEN
Solar/Wind Harmer
7.983
270400AC1-102 GEN
Solar/Wind Harmer
7.536
941621AE2-160 GEN
Adder
5.607
24734805WLF1G4
Adder
8.24
24735105WLF2G1
Adder
8.071
972163AH1-664 GEN
Solar/Wind Harmer
12.338
3429211JKCT 2G
Adder
14.334
339243AC2-075 GEN1
Solar/Wind Harmer
0.552
970455AG2-298 GEN
Solar/Wind Harmer
7.176
25196508WSDLE4
Adder
9.688
270340AC2-060 GEN
Solar/Wind Harmer
3.271
944221AF1-090 GEN
Solar/Wind Harmer
11.424
274746AC1-111 G10
Adder
5.326
23750501ELLIOTTS
Solar/Wind Helper
0.635
254304AE2-114 C
Solar/Wind Helper
0.208
241982AE2-343 S C
Solar/Wind Helper
0.211
203961AE2-224 GEN
Solar/Wind Helper
2.198
270132AB1-180 C
Adder
0.186
971313AH1-133 GEN
Solar/Wind Harmer
15.406
971061AG2-657 GEN
Solar/Wind Harmer
13.864
970879AG2-548 GEN
Solar/Wind Harmer
5.701
270367AC2-061_GEN
Solar/Wind Harmer
3.995
965411AG1-406 GEN
Solar/Wind Harmer
3.142
25196108MFTGT2
Adder
1.784
25196108MFTGT2
Adder
1.656
25196408WSDLE3
Adder
10.076
25196308WSDLE2
Adder
9.988
25196208WSDLE1
Adder
9.963
25196708WSDLE6
Adder
9.938
238126S14_GEN_1
Solar/Wind Helper
0.631
241967AE2-285_GEN
Solar/Wind Helper
0.605
23585401KL_K28_T16
Solar/Wind Helper
1.207
203955AF1-039 C O1
Solar/Wind Helper
0.347
946071AF1-272 GEN
Solar/Wind Helper
2.502
20083426SW_E13_K22
Solar/Wind Helper
0.052
20084626FORWARD
Solar/Wind Helper
0.327
274823ROCKFORD ;21
Adder
18.813
20092526R32
Solar/Wind Helper
1.068
203846AF2-130 C
Solar/Wind Helper
0.419
24686205CER G4
Adder
16.28
957541AF2-048 GEN
Solar/Wind Harmer
2.468
971461AH1-227 GEN
Solar/Wind Harmer
7.872
270346AE1-212 GEN
Solar/Wind Harmer
13.369
971331AH1-145 GEN
Solar/Wind Harmer
12.593
247619Y1-049
Adder
0.569
958121AF2-106 GEN
Solar/Wind Harmer
5.909
970519AG2-331 GEN
Solar/Wind Harmer
21.356
970699AG2-449 GEN
Solar/Wind Harmer
14.128
270291AC1-194 GEN
Solar/Wind Harmer
12.959
3429391JKCT 9G
Adder
10.15
958171AF2-111 GEN
Solar/Wind Harmer
29.825
25196608WSDLE5
Adder
9.788
253406AD2-031_GEN
Solar/Wind Harmer
1.394
970193AG2-126 GEN
Solar/Wind Harmer
15.993
24728705AND G3
Adder
8.541
253415AE1-040 GEN
Solar/Wind Harmer
1.181
254305AE2-115 C
Solar/Wind Helper
0.208
202652Y1-033 WT C
Solar/Wind Helper
0.526
23750701CROSSCHOOL
Solar/Wind Helper
1.114
20089026BF_G21_K23
Solar/Wind Helper
0.437
238127S14_GEN_2
Solar/Wind Helper
0.631
24289405MTG1
50/50
11.814
24686405CER G5
Adder
16.216
270053AF1-130 C
Solar/Wind Harmer
6.678
970913AG2-568 GEN
Solar/Wind Harmer
13.568
970273AG2-179 GEN
Solar/Wind Harmer
4.7
339250AF1-203 GEN
Solar/Wind Harmer
0.715
962251AG1-071 GEN
Solar/Wind Harmer
6.465
270356AE2-297 GEN
Solar/Wind Harmer
4.839
270222AC2-111 GEN
Solar/Wind Harmer
8.641
274760LEE CO EC;1U
Adder
9.033
972236AH1-702 GEN2
Adder
2.118
20089126CSLMN_L13
Solar/Wind Helper
0.552
238118U2-030_1
Solar/Wind Helper
0.268
24318705GVG2
50/50
11.798
971191AH1-055 GEN
Solar/Wind Harmer
39.337
970093AG2-073 GEN
Solar/Wind Harmer
12.329
970243AG2-164 GEN
Solar/Wind Harmer
31.788
972167AH1-666 GEN
Solar/Wind Harmer
9.834
972273AH1-721 GEN
Adder
102.108
966571AG1-526 GEN
Solar/Wind Harmer
27.128
25196008MFTGT1
Adder
1.567
252510AF1-249 C
Solar/Wind Harmer
0.482
942481AE2-261 GEN
Solar/Wind Harmer
30.873
274729ELWOOD EC;1P
Adder
7.078
237048AF1-022 C
Solar/Wind Helper
0.185
237043AE2-125 C
Solar/Wind Helper
0.171
270214AC2-123 GEN
Solar/Wind Harmer
3.243
270583AD2-179 GEN
Solar/Wind Harmer
13.038
971125AH1-004 GEN
Solar/Wind Harmer
4.864
252519AF1-045_GEN
Solar/Wind Harmer
7.038
252516AE2-318_GEN
Solar/Wind Harmer
5.369
270444AC2-157 GEN1
Solar/Wind Harmer
6.363
253317AC1-085 GEN4
Solar/Wind Harmer
9.279
276916AD2-100_GEN
Solar/Wind Harmer
21.743
957381AF2-032 GEN
Solar/Wind Harmer
0.432
253370AE2-315 SEC1
Adder
1.976
25322209TAIT E
Adder
9.385
25322209TAIT E
Adder
9.175
247621Y3-024
Adder
0.231
241801AE1-079 GEN
Solar/Wind Helper
0.235
238120AE2-309 GEN
Solar/Wind Helper
0.394
972203AH1-686 GEN
Adder
4.469
970281AG2-184 GEN
Solar/Wind Harmer
32.691
962211AG1-066 GEN
Solar/Wind Harmer
3.557
252524AE2-267 GEN
Solar/Wind Harmer
1.801
962771AG1-126 GEN
Solar/Wind Harmer
41.255
25306009OHH W.
Adder
2.849
253372AE2-315 SEC3
Adder
1.869
253372AE2-315 SEC3
Adder
1.869
274744AC1-111 GEN8
Adder
5.326
241997AF1-093 GEN
Solar/Wind Helper
0.242
20091526CHSTN_FL
Solar/Wind Helper
0.532
24722005FLATG5
50/50
2.672
24721905FLATG4
50/50
48.99
960911AF2-382 GEN
Solar/Wind Harmer
11.821
972103AH1-617 GEN
Solar/Wind Harmer
31.134
943031AE2-326 GEN
Solar/Wind Harmer
5.103
971155AH1-034 GEN
Solar/Wind Harmer
11.792
960741AF2-365 GEN
Solar/Wind Harmer
5.892
25194608D.CRK4
Adder
1.886
270030AE2-140 GEN
Solar/Wind Harmer
22.282
253316AC1-085 GEN3
Solar/Wind Harmer
9.279
253433AC1-085 GEN1
Solar/Wind Harmer
5.89
946181AF1-283 GEN
Solar/Wind Harmer
14.4
24728505AND G1
Adder
4.084
253370AE2-315 SEC1
Adder
1.976
253371AE2-315 SEC2
Adder
1.869
274767LEE CO EC;8U
Adder
8.927
274682WAUKEGAN ;7U
Adder
17.184
235058AG1-386 C
Solar/Wind Helper
0.446
964991AG1-363 GEN
Solar/Wind Helper
3.415
203818AF1-086 GEN
Solar/Wind Helper
1.548
957141AF2-008_MTX
Adder
66.242
944201AF1-088_MTX
Adder
132.484
CBM South 1LTFEXP_CBM-S1->PJM
CBM
43.356
WECLTFEXP_WEC->PJM
CLTF
3.698
LAGNLTFEXP_LAGN->PJM
CLTF
21.962
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.485
CPLELTFEXP_CPLE->PJM
CLTF
7.421
SIGELTFEXP_SIGE->PJM
CLTF
0.602
CBM West 1LTFEXP_CBM-W1->PJM
CBM
123.346
NYPJM->LTFIMP_NY
CLTF
4.949
TVALTFEXP_TVA->PJM
CLTF
11.425
AG2-052LTFEXP_AG2-052->PJM
LTF
0.222
CBM West 2LTFEXP_CBM-W2->PJM
CBM
146.148
LGEELTFEXP_LGEE->PJM
CLTF
8.306
MECLTFEXP_MEC->PJM
CLTF
17.041
AH1-155LTFEXP_AH1-155->PJM
LTF
0.334

Details for 8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2168-555_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2168-555_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:105.49 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4156.4
MW Contribution:12.19
Bus #Bus NameTypeMW Contribution
3152041BATH 4D
50/50
17.337
3151881LOWMORC
50/50
6.984
3151881LOWMORC
50/50
6.875
966391AG1-508 GEN
Solar/Wind Harmer
4.68
270069AE2-166 C O1
Solar/Wind Harmer
3.325
24734705WLF1G3
Adder
5.613
24734905WLF1G5
Adder
5.613
3148013FISHERV
Solar/Wind Helper
0.263
3152051BATH 5E
50/50
17.355
3137383CUSHAW
50/50
0.134
3151861LOWMORA
50/50
7.039
971329AH1-144 GEN
Solar/Wind Harmer
17.696
958131AF2-107 GEN
Solar/Wind Harmer
5.403
971403AH1-188 GEN
Solar/Wind Harmer
12.187
3132273ORANGE
Solar/Wind Helper
0.051
316170AC1-121 GEN2
Solar/Wind Helper
0.36
24288905REUSENS
50/50
0.045
315616AA1-038_C
Solar/Wind Harmer
14.233
270018AE2-047 C O1
Solar/Wind Harmer
1.338
24728305BUCHG2
Adder
4.634
3148013FISHERV
Solar/Wind Helper
0.457
3147666LOUISA
Solar/Wind Helper
0.577
238147AE2-230_GEN1
Solar/Wind Helper
0.401
24290605CLAY-1
50/50
0.194
24290605CLAY-1
50/50
0.194
316217AC1-145 GEN
Solar/Wind Harmer
3.265
316197AC1-042 GEN
Solar/Wind Harmer
2.475
942671AE2-283 GEN
Solar/Wind Harmer
6.664
3132123MT JACKSON
Solar/Wind Helper
1.31
966001AG1-469 GEN
Solar/Wind Helper
0.292
270205AE1-176
50/50
0.005
970479AG2-310 GEN
50/50
15.892
971367AH1-164 GEN
Solar/Wind Harmer
5.352
941821AE2-187 GEN
Solar/Wind Harmer
7.544
270197AD1-017 GEN1
Solar/Wind Harmer
1.927
270336AE1-100 GEN
Solar/Wind Harmer
2.02
943811AF1-049 GEN
Solar/Wind Harmer
4.147
24735205WLF2G2
Adder
5.48
316499AE2-029_GEN
Solar/Wind Helper
1.577
316095T157 G97
Solar/Wind Helper
1.082
270583AD2-179 GEN
Solar/Wind Harmer
15.671
270214AC2-123 GEN
Solar/Wind Harmer
3.17
971225AH1-072 GEN
Solar/Wind Harmer
1.824
971227AH1-073 GEN
Solar/Wind Harmer
1.824
315651AD1-115 GEN
Solar/Wind Helper
0.781
24290705CLAY-2
50/50
0.194
24290705CLAY-2
50/50
0.194
971277AH1-098 GEN
Solar/Wind Harmer
5.461
24728205BUCHG1
Adder
4.634
3147312GRETNA
Solar/Wind Harmer
-0.004
971687AH1-348 GEN
Solar/Wind Harmer
0.906
237061AD1-155 GEN
Solar/Wind Helper
0.047
23583801GRNGAP
Solar/Wind Helper
4.125
238149AF1-291A_GEN
Solar/Wind Helper
0.114
270013AE1-250 PV
Solar/Wind Harmer
2.411
315821AE2-092 GEN
Solar/Wind Helper
2.895
3151861LOWMORA
50/50
6.765
24734805WLF1G4
Adder
5.613
24735105WLF2G1
Adder
5.48
23546401DTGZ2-030
Solar/Wind Helper
0.075
238152AF2-075_GEN
Solar/Wind Helper
0.572
316164AC1-076 GEN
Solar/Wind Helper
1.095
971543AH1-269 GEN
50/50
9.298
971313AH1-133 GEN
Solar/Wind Harmer
10.943
270132AB1-180 C
Adder
0.114
3148133STUARTS
Solar/Wind Helper
0.274
3152061BATH 6F
50/50
17.43
970823AG2-518 GEN
50/50
6.455
958121AF2-106 GEN
Solar/Wind Harmer
7.115
247619Y1-049
Adder
0.646
971331AH1-145 GEN
Solar/Wind Harmer
13.718
270346AE1-212 GEN
Solar/Wind Harmer
9.778
970223AG2-152 GEN
Solar/Wind Harmer
12.909
971461AH1-227 GEN
Solar/Wind Harmer
4.678
3147666LOUISA
Solar/Wind Helper
1.004
316254AC1-120 GEN1
Solar/Wind Helper
1.079
270173AC1-122 GEN
Solar/Wind Harmer
2.55
941801AE2-185 GEN
Solar/Wind Harmer
7.544
970913AG2-568 GEN
Solar/Wind Harmer
7.285
238148AE2-230_GEN2
Solar/Wind Helper
0.402
962751AG1-124 GEN
Solar/Wind Harmer
14.726
3147312GRETNA
Solar/Wind Harmer
-0.016
3146802CHATHAM
Solar/Wind Harmer
-0.015
270016AE1-250 BESS
Solar/Wind Harmer
2.411
3147983MERCK5
Solar/Wind Helper
0.183
3152011BATH 1A
50/50
17.37
3152021BATH 2B
50/50
17.37
3152031BATH 3C
50/50
17.364
3148463FAIRFLD
Solar/Wind Harmer
-0.069
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.011
943031AE2-326 GEN
Solar/Wind Harmer
4.99
3147123OTTER R
Solar/Wind Harmer
-0.011
270574AD1-017 GEN2
Solar/Wind Harmer
6.414
270030AE2-140 GEN
Solar/Wind Harmer
22.569
960911AF2-382 GEN
Solar/Wind Harmer
7.443
316192AB2-158 GEN
Solar/Wind Helper
1.696
316097T157 G90
Solar/Wind Helper
1.082
316336AC2-165 C
Solar/Wind Helper
1.208
CBM South 1LTFEXP_CBM-S1->PJM
CBM
24.94
WECLTFEXP_WEC->PJM
CLTF
2.007
LAGNLTFEXP_LAGN->PJM
CLTF
12.827
CBM South 2LTFEXP_CBM-S2->PJM
CBM
16.289
CPLELTFEXP_CPLE->PJM
CLTF
3.547
SIGELTFEXP_SIGE->PJM
CLTF
0.308
CBM West 1LTFEXP_CBM-W1->PJM
CBM
71.759
NYPJM->LTFIMP_NY
CLTF
3.2
TVALTFEXP_TVA->PJM
CLTF
6.791
AG2-052LTFEXP_AG2-052->PJM
LTF
0.119
CBM West 2LTFEXP_CBM-W2->PJM
CBM
81.312
LGEELTFEXP_LGEE->PJM
CLTF
4.095
MECLTFEXP_MEC->PJM
CLTF
9.322
AH1-155LTFEXP_AH1-155->PJM
LTF
0.178

Details for 8VALLEY SC-8VALLEY 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2168-555_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
8VALLEY SC-8VALLEY 500.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2168-555_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:105.23 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4145.88
MW Contribution:12.19
Bus #Bus NameTypeMW Contribution
3152041BATH 4D
50/50
17.337
3151881LOWMORC
50/50
6.984
3151881LOWMORC
50/50
6.875
966391AG1-508 GEN
Solar/Wind Harmer
4.68
270069AE2-166 C O1
Solar/Wind Harmer
3.325
24734705WLF1G3
Adder
5.613
24734905WLF1G5
Adder
5.613
3148013FISHERV
Solar/Wind Helper
0.263
3152051BATH 5E
50/50
17.355
3137383CUSHAW
50/50
0.134
3151861LOWMORA
50/50
7.039
971329AH1-144 GEN
Solar/Wind Harmer
17.696
958131AF2-107 GEN
Solar/Wind Harmer
5.403
971403AH1-188 GEN
Solar/Wind Harmer
12.187
3132273ORANGE
Solar/Wind Helper
0.051
316170AC1-121 GEN2
Solar/Wind Helper
0.36
24288905REUSENS
50/50
0.045
315616AA1-038_C
Solar/Wind Harmer
14.233
270018AE2-047 C O1
Solar/Wind Harmer
1.338
24728305BUCHG2
Adder
4.634
3148013FISHERV
Solar/Wind Helper
0.457
3147666LOUISA
Solar/Wind Helper
0.577
238147AE2-230_GEN1
Solar/Wind Helper
0.401
24290605CLAY-1
50/50
0.194
24290605CLAY-1
50/50
0.194
316217AC1-145 GEN
Solar/Wind Harmer
3.265
316197AC1-042 GEN
Solar/Wind Harmer
2.475
942671AE2-283 GEN
Solar/Wind Harmer
6.664
3132123MT JACKSON
Solar/Wind Helper
1.31
966001AG1-469 GEN
Solar/Wind Helper
0.292
270205AE1-176
50/50
0.005
970479AG2-310 GEN
50/50
15.892
971367AH1-164 GEN
Solar/Wind Harmer
5.352
941821AE2-187 GEN
Solar/Wind Harmer
7.544
270197AD1-017 GEN1
Solar/Wind Harmer
1.927
270336AE1-100 GEN
Solar/Wind Harmer
2.02
943811AF1-049 GEN
Solar/Wind Harmer
4.147
24735205WLF2G2
Adder
5.48
316499AE2-029_GEN
Solar/Wind Helper
1.577
316095T157 G97
Solar/Wind Helper
1.082
270583AD2-179 GEN
Solar/Wind Harmer
15.671
270214AC2-123 GEN
Solar/Wind Harmer
3.17
971225AH1-072 GEN
Solar/Wind Harmer
1.824
971227AH1-073 GEN
Solar/Wind Harmer
1.824
315651AD1-115 GEN
Solar/Wind Helper
0.781
24290705CLAY-2
50/50
0.194
24290705CLAY-2
50/50
0.194
971277AH1-098 GEN
Solar/Wind Harmer
5.461
24728205BUCHG1
Adder
4.634
3147312GRETNA
Solar/Wind Harmer
-0.004
971687AH1-348 GEN
Solar/Wind Harmer
0.906
237061AD1-155 GEN
Solar/Wind Helper
0.047
23583801GRNGAP
Solar/Wind Helper
4.125
238149AF1-291A_GEN
Solar/Wind Helper
0.114
270013AE1-250 PV
Solar/Wind Harmer
2.411
315821AE2-092 GEN
Solar/Wind Helper
2.895
3151861LOWMORA
50/50
6.765
24734805WLF1G4
Adder
5.613
24735105WLF2G1
Adder
5.48
23546401DTGZ2-030
Solar/Wind Helper
0.075
238152AF2-075_GEN
Solar/Wind Helper
0.572
316164AC1-076 GEN
Solar/Wind Helper
1.095
971543AH1-269 GEN
50/50
9.298
971313AH1-133 GEN
Solar/Wind Harmer
10.943
270132AB1-180 C
Adder
0.114
3148133STUARTS
Solar/Wind Helper
0.274
3152061BATH 6F
50/50
17.43
970823AG2-518 GEN
50/50
6.455
958121AF2-106 GEN
Solar/Wind Harmer
7.115
247619Y1-049
Adder
0.646
971331AH1-145 GEN
Solar/Wind Harmer
13.718
270346AE1-212 GEN
Solar/Wind Harmer
9.778
970223AG2-152 GEN
Solar/Wind Harmer
12.909
971461AH1-227 GEN
Solar/Wind Harmer
4.678
3147666LOUISA
Solar/Wind Helper
1.004
316254AC1-120 GEN1
Solar/Wind Helper
1.079
270173AC1-122 GEN
Solar/Wind Harmer
2.55
941801AE2-185 GEN
Solar/Wind Harmer
7.544
970913AG2-568 GEN
Solar/Wind Harmer
7.285
238148AE2-230_GEN2
Solar/Wind Helper
0.402
962751AG1-124 GEN
Solar/Wind Harmer
14.726
3147312GRETNA
Solar/Wind Harmer
-0.016
3146802CHATHAM
Solar/Wind Harmer
-0.015
270016AE1-250 BESS
Solar/Wind Harmer
2.411
3147983MERCK5
Solar/Wind Helper
0.183
3152011BATH 1A
50/50
17.37
3152021BATH 2B
50/50
17.37
3152031BATH 3C
50/50
17.364
3148463FAIRFLD
Solar/Wind Harmer
-0.069
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.011
943031AE2-326 GEN
Solar/Wind Harmer
4.99
3147123OTTER R
Solar/Wind Harmer
-0.011
270574AD1-017 GEN2
Solar/Wind Harmer
6.414
270030AE2-140 GEN
Solar/Wind Harmer
22.569
960911AF2-382 GEN
Solar/Wind Harmer
7.443
316192AB2-158 GEN
Solar/Wind Helper
1.696
316097T157 G90
Solar/Wind Helper
1.082
316336AC2-165 C
Solar/Wind Helper
1.208
CBM West 1LTFEXP_CBM-W1->PJM
CBM
71.759
NYPJM->LTFIMP_NY
CLTF
3.2
TVALTFEXP_TVA->PJM
CLTF
6.791
AG2-052LTFEXP_AG2-052->PJM
LTF
0.119
CBM West 2LTFEXP_CBM-W2->PJM
CBM
81.312
LGEELTFEXP_LGEE->PJM
CLTF
4.095
MECLTFEXP_MEC->PJM
CLTF
9.322
AH1-155LTFEXP_AH1-155->PJM
LTF
0.178
CBM South 1LTFEXP_CBM-S1->PJM
CBM
24.94
WECLTFEXP_WEC->PJM
CLTF
2.007
LAGNLTFEXP_LAGN->PJM
CLTF
12.827
CBM South 2LTFEXP_CBM-S2->PJM
CBM
16.289
CPLELTFEXP_CPLE->PJM
CLTF
3.547
SIGELTFEXP_SIGE->PJM
CLTF
0.308
CONTINGENCY 'AEP_P4_#7421_05CLOVRD 765_BB2_SRT-A'
 OPEN BRANCH FROM BUS 242512 TO BUS 242519 CKT 14   /*05CLOVRD     765.0 - 05CLOVRD     500.0
END
CONTINGENCY 'AEP_P1-3_#7421_05CLOVRD 765_14_SRT-A'
 OPEN BRANCH FROM BUS 242512 TO BUS 242519 CKT 14   /*05CLOVRD     765.0 - 05CLOVRD     500.0
END
CONTINGENCY 'AP_P1-3_MP-765-501T_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1   /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                   /*05BELMON     765.0
END
CONTINGENCY 'AP_P2-3_MP-500-020_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 1          /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 2          /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5          /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1          /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1          /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                          /*05BELMON     765.0
 SET POSTCONTRATING 2492 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
 SET PRECONTRATING 1986 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
END
CONTINGENCY 'AP_P2-3_MP-500-021_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 3          /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5          /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1          /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1          /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                          /*05BELMON     765.0
 SET POSTCONTRATING 2492 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
 SET PRECONTRATING 1986 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
END
CONTINGENCY 'AEP_P4_#37_05MOUNTN 765_B1_SRT-A'
 OPEN BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242516 TO BUS 242920 CKT 1   /*05MOUNTN     765.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
END
CONTINGENCY 'AEP_P4_#2942_05KAMMER 765_PP_SRT-A'
 OPEN BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242516 TO BUS 242920 CKT 1   /*05MOUNTN     765.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
 OPEN BRANCH FROM BUS 242925 TO BUS 243188 CKT 1   /*05KAMMER     765.0 - 05MLG1        26.0
 REMOVE UNIT 1 FROM BUS 243188                     /*05MLG1        26.0
END
CONTINGENCY 'AEP_P4_#8075_05MARYSV 765_A2_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 242939 CKT 2    /*05MARYSV     765.0 - 05MARYSV     345.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
END
CONTINGENCY 'AEP_P4_#8980_05KAMMER 765_QQ2_SRT-A'
 OPEN BRANCH FROM BUS 242925 TO BUS 290623 CKT Z1   /*05KAMMER     765.0 - 05KAMMER_RG  765.0
 OPEN BRANCH FROM BUS 246526 TO BUS 290623 CKT 1    /*05GUERNSEY   765.0 - 05KAMMER_RG  765.0
END
CONTINGENCY 'AEP_P1-2_#17217_SRT-A'
 OPEN BRANCH FROM BUS 242925 TO BUS 290623 CKT Z1   /*05KAMMER     765.0 - 05KAMMER_RG  765.0
 OPEN BRANCH FROM BUS 246526 TO BUS 290623 CKT 1    /*05GUERNSEY   765.0 - 05KAMMER_RG  765.0
END
CONTINGENCY 'AEP_P4_#7445_05MARYSV 765_B_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290621 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RF 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 962760 TO BUS 290621 CKT 1    /*AG1-125 TP   765.0 - 05MARYSVL_RF 765.0
END
CONTINGENCY 'AEP_P4_#17219_05GUERNSEY 765_A_SRT-A'
 OPEN BRANCH FROM BUS 242925 TO BUS 290623 CKT Z1   /*05KAMMER     765.0 - 05KAMMER_RG  765.0
 OPEN BRANCH FROM BUS 246526 TO BUS 246751 CKT 1    /*05GUERNSEY   765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 246526 TO BUS 290623 CKT 1    /*05GUERNSEY   765.0 - 05KAMMER_RG  765.0
END
CONTINGENCY 'AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1   /*05CLOVRD     500.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'AEP_P2-2_#7222_05MALIS 765_1_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1    /*05MALIS      765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290237 CKT 1    /*05MALIS      765.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT SR   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT ZB   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243538 TO BUS 290237 CKT 1    /*05MALISX     138.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 290237 TO BUS 290238 CKT 1    /*05MALIS 1EQ    1.0 - 05MALIS T1    13.8
END
CONTINGENCY 'AEP_P1-2_#7422_16_SRT-A'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1   /*05CLOVRD     500.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'AEP_P7-1_#10944___SRT-A'
 OPEN BRANCH FROM BUS 242528 TO BUS 242940 CKT 1   /*05SPORN      345.0 - 05MUSKNG     345.0
 OPEN BRANCH FROM BUS 242940 TO BUS 242947 CKT 1   /*05MUSKNG     345.0 - 05WATERFORD  345.0
END
CONTINGENCY 'AEP_P7-1_#10856___SRT-A'
 OPEN BRANCH FROM BUS 242528 TO BUS 242940 CKT 1   /*05SPORN      345.0 - 05MUSKNG     345.0
 OPEN BRANCH FROM BUS 242528 TO BUS 242947 CKT 1   /*05SPORN      345.0 - 05WATERFORD  345.0
END
CONTINGENCY 'DVP_P7-1: LN 2168-555_SRT-A'
 OPEN BRANCH FROM BUS 314794 TO BUS 314854 CKT 1   /*6DOOMS       230.0 - 6LEXNGT1     230.0
 OPEN BRANCH FROM BUS 314907 TO BUS 314912 CKT 1   /*8DOOMS       500.0 - 8LEXNGTN     500.0
END
247977 to 242524 ckt 17
242519 to 314912 ckt 1
242516 to 242920 ckt 1
314901 to 314991 ckt 1
314991 to 314926 ckt 1

Winter Peak Analysis

The New Service Request AH1-188 was evaluated as a 140.0 MW (84.0 MW Capacity) injection in the AEP area.

AH1-188 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 140.0 MW (140.0 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

(No impacts were found for this analysis)

Light Load Analysis

The New Service Request AH1-188 was evaluated as a 140.0 MW injection

AH1-188 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 140.0 MW (140.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

(No impacts were found for this analysis)

Short Circuit Analysis

Short Circuit analysis is not performed as part of the Phase I System Impact Study. Short Circuit analysis will commence in the Phase II System Impact Study.

Stability Analysis

Stability analysis is not performed as part of the Phase I System Impact Study. Stability analysis will commence in the Phase II System Impact Study.

Reactive Power Analysis

Reactive Power analysis is not performed as part of the Phase I System Impact Study. Reactive Power analysis will commence in the Phase II System Impact Study.

Steady-State Voltage Analysis

Steady State Voltage Analysis is Not Required.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-018Powerton-Goodings GroveIn Service
AA1-038Lexington-Low Moor 230kVUnder Construction
AA1-095Halfway-Marlowe 34.5kVIn Service
AA2-184Atlantic-Red Bank 34kVIn Service
AB1-001Absecon 12 kVIn Service
AB1-006Meadow Lake 345kVIn Service
AB1-027Old Church 34.5 KVIn Service
AB1-096Carroll-Mt. Airy 34.5kVIn Service
AB1-124Carroll-Monocacy 34.5kVPartially in Service - Under Construction
AB1-125Carroll-Monocacy 34.5kVIn Service
AB1-127St. Thomas-Guilford 34.5kVIn Service
AB1-128St. Thomas-Mercersburg 34.5kVIn Service
AB1-138Navy 34.5kVIn Service
AB1-139Metuchen 26kVIn Service
AB1-141Church-Wye Mills 138 kV IIn Service
AB1-142Church-Wye Mills 138 kV IIIn Service
AB1-176Price 25kV IIEngineering & Procurement
AB1-180Pine View 12kVIn Service
AB2-026Powhatan 34.5kVIn Service
AB2-029Remington 34.5kVIn Service
AB2-032Church-Wye Mills 138 kVIn Service
AB2-037Keeney-Steele 230kVUnder Construction
AB2-045Buckingham 34.5kVIn Service
AB2-049Gloucester Township 12kVIn Service
AB2-070Mt. Pulaski-BrokawIn Service
AB2-133Chestertown 69kVUnder Construction
AB2-135Church-Kent 69kVIn Service
AB2-136Cambridge-West Cambridge 69kVUnder Construction
AB2-153Church-Wye Mills 138 kVIn Service
AB2-158Louisa-South Anna 230kVIn Service
AB2-179Townsend 138kVIn Service
AC1-001Delano 138kVIn Service
AC1-010Gloucester 26kVUnder Construction
AC1-017Levittown 13 kVIn Service
AC1-030Cinnaminson 13kVIn Service
AC1-033Kewanee 138 kVIn Service
AC1-042Altavista-Mt. Airy 69kVIn Service
AC1-053Lanesville-BrokawPartially in Service - Under Construction
AC1-068Atlanta 69kV IIn Service
AC1-069Atlanta 69kV IIIn Service
AC1-074Jacksonville-Renaker 138kV IIn Service
AC1-075Perth-Hickory Grove 115kVIn Service
AC1-076Locust Grove-Paytes 115kVIn Service
AC1-082Ravenswood-Hemlock 69kVUnder Construction
AC1-085Stuart-Clinton 345kVIn Service
AC1-089Hillsboro-Wildcat 138kVIn Service
AC1-091Cedar Creek 138kV IEngineering & Procurement
AC1-092Cedar Creek 138kV IIEngineering & Procurement
AC1-093Cedar Creek 138kV IIIEngineering & Procurement
AC1-094Cedar Creek 138kV IVEngineering & Procurement
AC1-101Johns Creek-Excel 138kV ISuspended
AC1-102Johns Creek-Excel 138kV IISuspended
AC1-111Aurora 138kVIn Service
AC1-118Westmoreland 34.5kVIn Service
AC1-120Mitchell-Mountain Run 115kVEngineering & Procurement
AC1-121Mitchell-Mountain Run 115kVEngineering & Procurement
AC1-122Smith Mountain-Candler's Mountain 138kVIn Service
AC1-145Gretna DP 69 kVIn Service
AC1-158Spotsylvania 500kVIn Service
AC1-165Atlanta 69kV IIIIn Service
AC1-166Atlanta 69kV IVIn Service
AC1-168Kewanee-StreatorSuspended
AC1-174Losantville 345kVIn Service
AC1-175Losantville 345kVIn Service
AC1-188Rio-Lick 138kVEngineering & Procurement
AC1-191Elmont 115kVEngineering & Procurement
AC1-194Elk 138kVActive
AC1-214Crescent RidgeIn Service
AC2-023Hebron 69kVEngineering & Procurement
AC2-029Circleville 138kVSuspended
AC2-059Biers Run-Circleville 138kVIn Service
AC2-060Buckskin 69kVIn Service
AC2-061Hillsboro-Clinton 138kVIn Service
AC2-067Camden-Crystal I 69kVEngineering & Procurement
AC2-068Camden-Crystal II 69kVEngineering & Procurement
AC2-075Jacksonville-Renaker 138 kVIn Service
AC2-088S. Bethel-Brown 69kVIn Service
AC2-090Losantville 345kVIn Service
AC2-111College Corner 138kVEngineering & Procurement
AC2-123Jacksons Ferry 138kVIn Service
AC2-136East Hagerstown 12kVUnder Construction
AC2-137Elko 34.5kVIn Service
AC2-138Northern Neck 34.5kVIn Service
AC2-157Sullivan 345 kVUnder Construction
AC2-165Bremo-Powhatan 230kVSuspended
AC2-168Clinton 23kVIn Service
AC2-176Jay 138 kVIn Service
AC2-186Harrington 25kVUnder Construction
AC2-187Harrington 69kVUnder Construction
AC2-188Harrington 69 kVUnder Construction
AD1-013Twombly Road 138kVEngineering & Procurement
AD1-017Smith Mountain-Bearskin 138 kVIn Service
AD1-020Hunterstown-Lincoln 115 kVIn Service
AD1-060Mercersburg-Milnor 34.5 kVIn Service
AD1-061McConnelsburg-Mercersburg 34 kVIn Service
AD1-063Harmony Village 34.5 kVIn Service
AD1-100Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVUnder Construction
AD1-105Kings Dominion DP 115 kVUnder Construction
AD1-115Mountain Run-Mitchell 115 kVEngineering & Procurement
AD1-128Modoc-Delaware 138 kVPartially in Service - Under Construction
AD1-136South Bethel-Brown 69 kVIn Service
AD1-140Greene-Clark 138 kVEngineering & Procurement
AD1-155Meadow Brook-Strasburg 138 kVIn Service
AD2-009McConnellsburg 138 kVIn Service
AD2-016Biers Run-Circleville 138 kVIn Service
AD2-027Camden Switch 26 kVIn Service
AD2-031Martinsville-Wilmington 69 kVIn Service
AD2-038Powerton-Nevada 345 kVUnder Construction
AD2-042Camden Switch 26 kV IIIn Service
AD2-047Davis Creek 138 kVSuspended
AD2-048Cynthia-Headquarters 69 kVUnder Construction
AD2-060Davis Creek 138kVEngineering & Procurement
AD2-065Atco 12 kVIn Service
AD2-066Mazon-Crescent Ridge 138 kVEngineering & Procurement
AD2-070Gilbert-Morris Park 34.5kVIn Service
AD2-071Strawton-Deer Creek 138 kVSuspended
AD2-073Sanders DP 230 kVIn Service
AD2-074Garner DP-Lancaster 115 kVEngineering & Procurement
AD2-100Kincaid-Pana 345 kVSuspended
AD2-115Lyons-Moselem 69kVIn Service
AD2-116Hokes-Grantley 69 kVIn Service
AD2-131Kincaid-Pana 345kVSuspended
AD2-133Eagle Valley 115kVIn Service
AD2-134Shady OaksPartially in Service - Under Construction
AD2-135Williamstown 12kVPartially in Service - Under Construction
AD2-172Lena 138kVIn Service
AD2-179Morgans Cut-Glen Lyn 138kVSuspended
AD2-180Elk Garden-Parr Run 138kVIn Service
AE1-040Greenfield 69 kVIn Service
AE1-041Edison 4kVIn Service
AE1-071Shade Gap-Roxbury 115 kVIn Service
AE1-074Winterpock 34.5 kVUnder Construction
AE1-075Powhatan 34.5 kVIn Service
AE1-079Maysville-Sharon 69 kVUnder Construction
AE1-081Landing 12.47 kVIn Service
AE1-100Axton 138 kVIn Service
AE1-101McConnellsburg-Texas Eastern 138 kVIn Service
AE1-109Frenchs Mill 34 kVIn Service
AE1-113Mole Creek 345 kVEngineering & Procurement
AE1-114Maryland-Lancaster 138 kVActive
AE1-142Manitou-Pleasant Plains 34.5 kVIn Service
AE1-155Garner-Northern Neck 115 kVIn Service
AE1-156Quakertown Solar II 34.5 kVPartially in Service - Under Construction
AE1-163Powerton-Nevada 345 kVEngineering & Procurement
AE1-166Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE1-172Loretto-Wilton CenterActive
AE1-176Roanoke-Vinton 12 kV (Niagara Hydro)In Service
AE1-183Maysville-McDowell 69 kVEngineering & Procurement
AE1-185Hokes-Jackson 69 kVIn Service
AE1-196Hokes-Jackson 69 kV IIIn Service
AE1-205McLean 345 kVEngineering & Procurement
AE1-207Mississinewa-Gaston 138 kVSuspended
AE1-208Delaware-Van Buren 138 kVSuspended
AE1-209Desoto 345 kVSuspended
AE1-210Desoto 345 kVSuspended
AE1-212Grandview-Clifftop 138 kVSuspended
AE1-229Deepwater-Upper Pittsgrove 138 kVSuspended
AE1-237Andover (Maysville) 69kV IUnder Construction
AE1-250Smith Mountain-E. Danville 138 kVEngineering & Procurement
AE2-029Grottoes-Merck 115kVUnder Construction
AE2-035Lena 138 kVIn Service
AE2-042Milton 69 kVIn Service
AE2-045Olive-Reynolds 345 kVEngineering & Procurement
AE2-047Ridgeway-Solite 69 kVEngineering & Procurement
AE2-054Warfordsburg 34 kVIn Service
AE2-059Derry Tap-Derry Bus 69 kVIn Service
AE2-060Mifflintown Bus-Mifflintown Tap 69 kVIn Service
AE2-071Patton Rd-Summer Shade 69 kVIn Service
AE2-092Kidds Store-Sherwood 115 kVEngineering & Procurement
AE2-113Farmers Valley-Ridgeway 115 kVUnder Construction
AE2-114Midland 23 kV IIn Service
AE2-115Midland 23 kV IIIn Service
AE2-117ABW Tap-Alexandria 46 kVSuspended
AE2-125Stahlstown-Ligonier 25 kVIn Service
AE2-126Dubois-Curwensville 34.5 kVIn Service
AE2-129Philipsburg-Clarence 34.5 kVIn Service
AE2-131Philipsburg-Karthaus 34.5Under Construction
AE2-133Penns Tap-Richfield Tie 69 kVIn Service
AE2-139East Towanda-Grover 230 kVEngineering & Procurement
AE2-140Axton-Danville 138 kVSuspended
AE2-152Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE2-160Kanawha River 138 kVEngineering & Procurement
AE2-166Stockton 138 kVSuspended
AE2-169Delaware-Van Buren 138 kVSuspended
AE2-172Mississinewa-Gaston 138 kVSuspended
AE2-173McLean 345 kVActive
AE2-175Jackson-Long Pond 69 kVPartially in Service - Under Construction
AE2-185Gladys DP-Stonemill Switching Station 69 kVActive
AE2-187Shockoe DP-Chatham 69 kVActive
AE2-219Bluff Point-Randolph 138 kVSuspended
AE2-220Losantville 345 kVEngineering & Procurement
AE2-221Clinton-Stuart 345 kVUnder Construction
AE2-223McLean 345 kVActive
AE2-224Bear Rock-Johnstown 230 kVIn Service
AE2-226Millville-Old Chapel 138 kVEngineering & Procurement
AE2-230Bartonsville-Meadow Brook 138 kVIn Service
AE2-254Garrard County-Tommy-Gooch 69 kVIn Service
AE2-255Molecreek 345 kVEngineering & Procurement
AE2-261Kincaid-Pana 345 kVActive
AE2-262Moshannon-Milesburg 230 kVEngineering & Procurement
AE2-263Moshannon-Milesburg 230 kV IIEngineering & Procurement
AE2-267Woodsdale 345 kVEngineering & Procurement
AE2-281Powerton-Nevada 345 kVEngineering & Procurement
AE2-283Gladys-Stone Mill 69 kVActive
AE2-285Maysville 69 kVEngineering & Procurement
AE2-291Grit DP-Perth 115 kVActive
AE2-297Madison-Tanners Creek 138 kVIn Service
AE2-308Three Forks-Dale 138 kVActive
AE2-309Carlos Junction-Lonaconing 34.5 kVIn Service
AE2-315Yankee Tap 69 kVIn Service
AE2-318Ford-Cedarville 138 kVSuspended
AE2-321Belvidere-Marengo 138 kVActive
AE2-326Jacksons Ferry 138 kVEngineering & Procurement
AE2-339Avon 138 kVEngineering & Procurement
AE2-341Sandwich-Plano 138 kVActive
AE2-343Andover (Maysville) 69 kV IIUnder Construction
AF1-006Fairview East 34.5 kVIn Service
AF1-007Indian River 230 kV ISuspended
AF1-021Bethelboro-Connellsville #1 25 kVIn Service
AF1-022Lake Lynn-Uniontown 25 kVIn Service
AF1-030Sandwich-Plano 138 kVActive
AF1-038Sewellton Jct-Webbs Crossroads 69 kVEngineering & Procurement
AF1-039Listonburg-Highpoint 24.9 kVIn Service
AF1-042Garner DP-Lancaster 115 kVEngineering & Procurement
AF1-045Cedarville-Ford 138 kVSuspended
AF1-049Berry Hill 138 kVUnder Construction
AF1-050Summer Shade - Green County 161 kVEngineering & Procurement
AF1-051Gavin 765 kVIn Service
AF1-071College Corner 138 kVEngineering & Procurement
AF1-083Green County-Saloma 161 kVEngineering & Procurement
AF1-086Madera-Westover South 115 kVUnder Construction
AF1-088Sullivan 345 kVActive
AF1-090Kincaid-PanaEngineering & Procurement
AF1-093Henderson-Stoneboro 69 kVEngineering & Procurement
AF1-094Union City-Cambridge Springs 34.5 kVEngineering & Procurement
AF1-098Four Mile Jct-Corry East 115 kVEngineering & Procurement
AF1-118Sorenson-Desoto 345 kVEngineering & Procurement
AF1-119Keystone-Desoto 345 kVEngineering & Procurement
AF1-130Inez 138 kVSuspended
AF1-134Philipsburg-Madera 34.5 kVEngineering & Procurement
AF1-136Warfordsburg-Purcell Junction 34.5 kVEngineering & Procurement
AF1-140Claysburg 23 kVEngineering & Procurement
AF1-143Lick Run 115 kVEngineering & Procurement
AF1-153Motion-Ridgeway 46 kVSuspended
AF1-162Inez 138 kVEngineering & Procurement
AF1-202Keystone-Desoto 345 kVUnder Construction
AF1-203Patton Rd-Summer Shade 69 kVIn Service
AF1-204Eugene 345 kVActive
AF1-207Reynolds-Olive #1 345 kVEngineering & Procurement
AF1-215Olive-Reynolds 345 kVIn Service
AF1-223Keystone-Desoto 345 kVUnder Construction
AF1-233Flemingsburg – Spurlock 138kVActive
AF1-249Nickel 12.47 kVIn Service
AF1-254Milnor-Huyetts 34.5 kVUnder Construction
AF1-262Upper Pittsgrove 12 kVIn Service
AF1-264Runnemede 13 kVIn Service
AF1-268Desoto-Jay 138 kVEngineering & Procurement
AF1-272Lucerne 115 kVEngineering & Procurement
AF1-282Stuart-Clinton 345 kVEngineering & Procurement
AF1-283Stuart-Clinton 345 kVEngineering & Procurement
AF1-290Feagans Mill-Millville 138 kVIn Service
AF1-291ABartonsville-Meadow Brook 138 kVIn Service
AF1-296Garden Plain 138 kVActive
AF1-299Otter Point 34.5 kV IIn Service
AF1-300Otter Point 34.5 kV IIIn Service
AF1-302Brookville-Squab Hollow 138 kVEngineering & Procurement
AF1-320Merrill Creek 115 kVEngineering & Procurement
AF1-322Meadow Lake 345 kVEngineering & Procurement
AF1-331Twombley RoadEngineering & Procurement
AF1-333Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF1-337Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF1-338Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF1-339Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF2-008Sullivan 345 kVActive
AF2-018Inez 138 kVEngineering & Procurement
AF2-032Kincaid 345 kVEngineering & Procurement
AF2-039Shawville-Clearfield 34.5 kVEngineering & Procurement
AF2-041Nelson-Electric Junction 345 kVActive
AF2-048Rio-Lick 138 kVEngineering & Procurement
AF2-068Jay 138 kVActive
AF2-069Crescent Ridge 138 kVActive
AF2-075Bartonsville-Meadow Brook 138 kV IIIIn Service
AF2-078Reynolds-Olive #1 345 kVEngineering & Procurement
AF2-086Scott Tap-Bowmans Mill Tap 69 kVEngineering & Procurement
AF2-088Shawville-Clearfield 34.5 kV IIEngineering & Procurement
AF2-095Davis Creek 138 kVActive
AF2-106Hazel Hollow-Glen Lyn #1 138 kVEngineering & Procurement
AF2-107Clifford 138 kVEngineering & Procurement
AF2-111North Clark-Spurlock 345 kVActive
AF2-130Cobalt Corners 34.5 kVIn Service
AF2-132Reynolds-Olive #1 345 kVUnder Construction
AF2-133Reynolds-Olive #2 345 kVUnder Construction
AF2-134Olive-Reynolds #2 345 kVIn Service
AF2-138Flanders-West Wharton 34.5 kVIn Service
AF2-139Gilbert-Warren Glen 34.5 kVIn Service
AF2-142Nevada 345 kVActive
AF2-143Powerton-Nevada 345 kVActive
AF2-144Powhatan 34.5 kVIn Service
AF2-173Desoto 345 kVActive
AF2-177Sorenson-DeSoto #2 345 kVActive
AF2-192Frenchtown Solar-West Flemington 34.5 kVSuspended
AF2-199Nelson-Electric Junction 345 kVActive
AF2-200Nelson-Electric Junction 345 kVActive
AF2-205Olive-Reynolds #2 345 kVEngineering & Procurement
AF2-225McLean 345 kVActive
AF2-229Roxbury 23 kVEngineering & Procurement
AF2-233Penns-Richfield Tie #1 69 kVEngineering & Procurement
AF2-234Sunbury Yard #1-Richfield Tie #2 69 kVEngineering & Procurement
AF2-235Titusville-Oil Creek 34.5 kVWithdrawn
AF2-238Mansfield-South Troy 34.5 kVEngineering & Procurement
AF2-247Bustleton 13.2 kVIn Service
AF2-250Edgewood 12 kV IIIIn Service
AF2-252Blue Mound 345 kVEngineering & Procurement
AF2-291Sporn South-Leon 138 kVEngineering & Procurement
AF2-298Crown-New Lebanon 69 kVEngineering & Procurement
AF2-307Hope-Belvins Valley Tap 69 kVActive
AF2-311Gilboa-Jones Branch 138 kVEngineering & Procurement
AF2-316Gilboa-Jones Branch 138 kV IIEngineering & Procurement
AF2-325Jacktown 12 kVEngineering & Procurement
AF2-335Delaware-Royerton 138 kVActive
AF2-350Kensington 138 kVActive
AF2-352Blue Mound 345 kVEngineering & Procurement
AF2-354Washington 34.5 kV IIEngineering & Procurement
AF2-356Albright-Mt. Zion 138 kVUnder Construction
AF2-361Mifflintown Tap 69 kVEngineering & Procurement
AF2-365Munfordville KU Tap-Horse Cave Jct. 69 kVActive
AF2-378Cambridge 12 kVEngineering & Procurement
AF2-379Princess Anne 25 kVUnder Construction
AF2-382Hurley 69 kVEngineering & Procurement
AF2-383Tolna 115 kVWithdrawn
AF2-388Keystone-Desoto 345 kVActive
AF2-392Nelson-Dixon 138 kVActive
AF2-417West Damascus Tap-West Damascus 69 kVEngineering & Procurement
AF2-421East Hazelton-Weatherly Tap 69Engineering & Procurement
AF2-424Reed-Reed Tap #1 69 kVEngineering & Procurement
AF2-425Reed-Reed Tap#1 69 kVEngineering & Procurement
AF2-433Columbia-Geisinger Tap #1 69 kVEngineering & Procurement
AF2-434Columbia-Geisinger Tap #1 69 kVEngineering & Procurement
AF2-440Hillsboro-Middleboro 138 kVEngineering & Procurement
AG1-040Morgan Street-Mount Hope 34.5 kVEngineering & Procurement
AG1-047Jay 138 kVEngineering & Procurement
AG1-054Potter-Harlan 69 kVEngineering & Procurement
AG1-066Bonnyman 69 kVEngineering & Procurement
AG1-070Bon Ayr 69 kVActive
AG1-071Bon Ayr 69 kVActive
AG1-100Venango-Saegertown 34.5 kVEngineering & Procurement
AG1-107Hillsboro-Middleboro 138 kVEngineering & Procurement
AG1-118Sugar Grove-Waterman 138kVActive
AG1-124Gladstone 138 kVActive
AG1-125Marysville-Flatlick 765 kVEngineering & Procurement
AG1-126Marysville-Flatlick 765 kVEngineering & Procurement
AG1-127Crego Rd 138 kVActive
AG1-156Jack Frost-Lake Harmony 69 kVEngineering & Procurement
AG1-164East Hazelton-Weatherly Tap 69 kVEngineering & Procurement
AG1-165East Hazelton-Weatherly Tap 69 kVEngineering & Procurement
AG1-188Manitou-Oyster Creek 34.5 kVEngineering & Procurement
AG1-189Oyster Creek-Bamber Lake 34.5Engineering & Procurement
AG1-191Chester-Pohatcong Mountain 34.5 kVPartially in Service - Under Construction
AG1-193Utica Junction 34.5 kVSuspended
AG1-197Morgan Street-Cochranton 34.5 kVSuspended
AG1-198Union City 34.5 kVUnder Construction
AG1-223Larrabee-Allaire 34.5 kVUnder Construction
AG1-226Dequine-Eugene 345 kVActive
AG1-236Lanesville-Brokaw 345 kVActive
AG1-237Dequine-Eugene 345 kVEngineering & Procurement
AG1-254Salem-Woodstown 69 kVEngineering & Procurement
AG1-259Sunbury-Dalmatia 69 kVEngineering & Procurement
AG1-260Sunbury-Dalmatia 69 kVEngineering & Procurement
AG1-281Claysburg-HCR Tap 46 kVEngineering & Procurement
AG1-282Dunnsville 34.5 kVEngineering & Procurement
AG1-301Miller REC-Warrior Ridge 46 kVEngineering & Procurement
AG1-302Olive-Reynolds #1 345 kVUnder Construction
AG1-320Glendale-Stephensburg 69 kVActive
AG1-324Jay-Desoto 138 kVEngineering & Procurement
AG1-341Summer Shade 161 kVActive
AG1-348Pequest River-Washington 34.5 kVIn Service
AG1-349Olive-Reynolds #2 345 kVEngineering & Procurement
AG1-354Summershade-Green County 161 kVActive
AG1-363Black Oak-Hatfield 500 kVEngineering & Procurement
AG1-367DeSoto 345 kVActive
AG1-374Blue Mound 345 kVActive
AG1-375Sorenson-Desoto 345 kVActive
AG1-386Smith-Francis Junction 25 kVIn Service
AG1-397Walston 12 kVWithdrawn
AG1-405Walnut Grove-Asahi 69 kVActive
AG1-406Walnut Grove-Asahi 69 kVActive
AG1-414Mississinewa 138 kVEngineering & Procurement
AG1-433Keystone-DeSoto 345 kVActive
AG1-460Kincaid-Pana 345 kVActive
AG1-462Cordova 345 kVActive
AG1-469Gordonsville 34.5 kVEngineering & Procurement
AG1-471Up Church-Wayne County 69 kVActive
AG1-478Wilmington 34.5 kVEngineering & Procurement
AG1-480Shawnee 34.5 kVEngineering & Procurement
AG1-482Hamilton 115 kVWithdrawn
AG1-494Boxwood-Riverville 138 kVActive
AG1-495Gilbert-Rocktown 34.5 kVEngineering & Procurement
AG1-499Lambs 12.47 kVUnder Construction
AG1-508Point Lookout 69 kVEngineering & Procurement
AG1-526West Garrard 345 kVActive
AG1-555Dequine 345 kVEngineering & Procurement
AG1-558Buckner 34.5 kVEngineering & Procurement
AG1-559Caroline Pines 22 kVEngineering & Procurement
AG2-072Rockport 765 kVActive
AG2-073Crooksville 69 kVActive
AG2-081Mt. Sterling-Fogg Pike 69 kVActive
AG2-085Delaware-Royerton 138 kVActive
AG2-104Marysville-Flatlick 765 kVActive
AG2-106Marysville-Flatlick 765 kVActive
AG2-107Marysville-Flatlick 765 kVActive
AG2-111Perth 34.5 kV Substation (Circuit 408)Active
AG2-112Perth 34.5 kV Substation (Circuit 404)Active
AG2-114Dresden-Pontiac Midpoint 345 kVActive
AG2-125Camden-Crystal 69 kVActive
AG2-126Eugene 345 kVActive
AG2-152Banister-Bear Skin 138 kVActive
AG2-159Williamstown 69 kVActive
AG2-162Jefferson-Greentown 765 kVActive
AG2-163Dequine-Eugene 345 kVActive
AG2-164Jefferson-Greentown 765 kVActive
AG2-165Dumont-Greentown 765 kVActive
AG2-179Sewellton Junction 69 kVActive
AG2-184Harbert Metering 138 kVActive
AG2-191Mississinewa 138 kVActive
AG2-192Mississinewa 138 kVActive
AG2-212Dumont-Greentown 765 kVActive
AG2-219Jefferson-Greentown 765 kVActive
AG2-298Sulphur Creek-Loretto 69 kVActive
AG2-310Matt Funk 138 kVActive
AG2-311Smith Mountain 138 kVActive
AG2-328Dumont - Greentown 765 kVActive
AG2-330Dumont - Greentown 765 kVActive
AG2-331Jefferson-Greentown 765 kVActive
AG2-360Broadford 138 kVActive
AG2-363Powerton 345 kVActive
AG2-364Powerton 345 kVActive
AG2-401Losantville 345 kVActive
AG2-424Magnolia - Summersville 69 kVActive
AG2-449Jefferson-Greentown 765 kVActive
AG2-453Lasalle - Plano 345 kVActive
AG2-487Madison - Tanners Creek 138 kVActive
AG2-491Meadow Lake 345 kVActive
AG2-516Pecatonica 138kVActive
AG2-518Tech Drive 138 kVActive
AG2-519Royerton - Desoto 138 kVActive
AG2-524LaSalle Station - Mazon 138 kVActive
AG2-548Corwin - Elk 138 kVActive
AG2-550Bluff Point - Randolph 138 kVActive
AG2-551Bluff Point - Randolph 138 kVActive
AG2-568Stink Run – Sundial 138 kVActive
AG2-575Crego Rd. 138 kVActive
AG2-585Kensington 138kVActive
AG2-589Ravenswood - Hemlock 69 kVActive
AG2-637Randolph - Hodgin 138 kVActive
AG2-657Kanawha River - Carbondale 138 kVActive
AG2-660Nelson-Electric Junction 345 kVActive
AG2-665Corwin - Elk 138 kVActive
AG2-670Green County -Taylor County Junction 161 kVActive
AH1-004Avon - Renaker 138 kVActive
AH1-034Patton Road Junction - Summer Shade 69 kVActive
AH1-044Nelson - Electric Junction 345 kVActive
AH1-047Marengo - Belvidere 138 kVActive
AH1-055Kyger Creek - Don Marquis 345 kVActive
AH1-072Red Onion - VC5 69 kVActive
AH1-073Red Onion - VC5 69 kVActive
AH1-098Wolf Glade-West Carroll 138 kVActive
AH1-133Saltville - Tazewell 138 kVActive
AH1-136Falcon - Middle Creek 46 kVActive
AH1-144Peter's Mountain 138 kVActive
AH1-145Peter's Mountain 138 kVActive
AH1-146White Rock - Wayne 345 kVActive
AH1-147White Rock - Wayne 345 kVActive
AH1-150Nelson-Electric Junction 345 kVActive
AH1-151Nelson-Electric Junction 345 kVActive
AH1-164Oak Level - Tank Hill 138 kVActive
AH1-196Prairie 345 kVActive
AH1-227Flemming - Fremont 69 kVActive
AH1-234Wempletown - Paddock 345 kVActive
AH1-239Upchurch - Zula 69 kVActive
AH1-269Claytor 138 kVActive
AH1-281Bluegrass Parkway Tap - Woodlawn 69 kVActive
AH1-285Sandwich 138 kVActive
AH1-292Sullivan 345 kVActive
AH1-302Olive - Reynolds 345 kVActive
AH1-304Delaware-Van Buren 138 kVActive
AH1-305Olive - Reynolds 345 kVActive
AH1-306Mississinewa-Gaston 138 kVActive
AH1-337Randolph - Hodgin 138 kVActive
AH1-338McGirr Rd - Ritchie Road 138kVActive
AH1-341Stillman - Dixon 138KVActive
AH1-348Pound 34.5 kVActive
AH1-427Tommy Gooch - Garrard County 69 kVActive
AH1-482Olive - Reynolds #2 345 kVActive
AH1-535Nagel - Cane River 230 kVActive
AH1-537Pierce - Kyger Creek 345 kVActive
AH1-541Chestnut 345 kVActive
AH1-543Mulberry – Tazewell 345 kVActive
AH1-570Headquarters - Millersburg Junction 69 kVActive
AH1-571Headquarters - Millersburg Junction 69 kVActive
AH1-617Harbert Metering 138 kVActive
AH1-644Spicewood Metering 138 kVActive
AH1-664Goddard-Plumville 138 kVActive
AH1-665Goddard-Plumsville 138 kV IIActive
AH1-666Flemingsburg - Spurlock 138 kVActive
AH1-669Circleville-Biers Run 138 kVActive
AH1-670Blue Mound-Chestnut 345 kVActive
AH1-686Hanging Rock 765 kVActive
AH1-698Braidwood 345 kVActive
AH1-702Byron 345 kVActive
AH1-714Lasalle 345 kVActive
AH1-718Nelson 345 kVActive
AH1-721Laurel-Cooper 161 kVActive
U2-030Four Mile Ridge Wind 138kVIn Service
U2-073Frostburg 138kV IIIn Service
V3-007Desoto-Tanners Creek #1 345kVIn Service
V4-067Cates Road Egg Harbor Township 12kVDeactivated
V4-073Yankee 12.5kVIn Service
W1-003Oak HallIn Service
W1-004Oak HallIn Service
W1-005Oak HallIn Service
W1-006Oak HallIn Service
W1-130Vine Road 12kVIn Service
W2-030Egg Harbor TownshipIn Service
W2-048Brokaw-LanesvilleIn Service
W3-077Broadway-Stewartsville 34.5kVIn Service
W4-005Blue Mound-LathamIn Service
X2-022Brokaw-LanesvilleIn Service
X3-005Wildwood 12kVIn Service
X3-066Church Hill 69kVIn Service
Y1-033Penn Mar-Rock Wood 115kVIn Service
Y1-049Wurno 34.5kVIn Service
Y1-079Wye Mills 69kVIn Service
Y1-080Dorchester 12kVIn Service
Y3-024Bluff Point 12kVIn Service
Y3-058Rockawalkin 69kVIn Service
Z2-076Worcester South 25kVIn Service
Z2-077Worcester North 25kVIn Service
Z2-087Pontiac MidPoint-Brokaw 345kVIn Service
Z2-115Deer Creek 12.47kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with potential Affected System impacts. PJM initiates coordination with each Affected System Operator by providing a list of New Service Requests in the Cycle with potential impacts to their respective system. If the Affected System Operator indicates an Affected System Study is required, PJM will notify the Project Developer or Eligible Customer of the need for an Affected System Study. See below if any Affected System Operator requires a study for this project:

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

No cost allocated system reinforcements were identified for this project in the Phase I System Impact Study load flow analysis.

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement: b4000.10
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.10
Title
Install four 250 MVAR cap banks (two on 765 and two on 500 kV side) and a +/-500 MVAR STATCOM on the 765 kV Rocky Point yard
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-188 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-188 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)

System Reinforcement: b4000.7
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.7
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line - in DVP local area/Millville to Lovettsville section, roughly 10.5 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-188 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-188 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)

System Reinforcement: b4000.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.1
Title
Add two 765 kV breakers at Amos Substation to expand the breaker and a half scheme to accommodate the new Amos-Welton Spring 765 kV line (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-188 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-188 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.3
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.3
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - APS/FE Section of the line is 145 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-188 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-188 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)

System Reinforcement: b4000.6
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.6
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (Welton Spring to DVP local area, roughly 21 miles) (VA Portion)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-188 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-188 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)

System Reinforcement: b4000.8
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.8
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (DVP local area to Rocky Point, roughly 4.8 miles)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-188 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-188 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)

System Reinforcement: b4000.11
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.11
Title
Expand Black Oak Substation & Loop in the 502 Jct-Woodside 500 kV line (Projected ISD 6/1/2029)
Description
Expand Black Oak Substation to accommodate the connection of the 502 Jct-Woodside 500 kV line and loop the 502 Jct-Woodside 500 kV line into the Black Oak substation by constructing ~0.85 miles of new 500 kV line into and out of Black Oak 500 kV substation
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-188 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-188 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)

System Reinforcement: b4000.2
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.2
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - AEP Section of the line is 30 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-188 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-188 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)

System Reinforcement: b4000.5
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.5
Title
Install four 250 MVAR shunt capacitors, and a +/-500 MVAR STATCOM at Welton Spring 765 kV substation
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-188 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-188 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)

System Reinforcement: b4000.9
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.9
Title
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard (Projected ISD 6/1/2029)
Description
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard. Loop in the Doubs-Goose Creek 500 kV line, the Doubs-Aspen 500 kV line, and the Woodside-Goose Creek 500 kV line. Install two 765/500 kV transformer at Rocky Point substation. 765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-188 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-188 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)

System Reinforcement: b4000.4
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.4
Title
Construct a new 765 kV switchyard - Welton Spring (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-188 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-188 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)

System Reinforcement: b4000.325
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.325
Title
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Description
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Cost Information
Time Estimate
Feb 24 2029

Not Contingent

Note: AH1-188 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-188 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.344
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.344
Title
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AH1-188 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-188 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.346
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.346
Title
Cut-in 500kV line from Kraken substation into Yeat substation
Description
Cut-in 500kV line from Kraken substation into Yeat substation
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-188 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-188 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.352
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.352
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AH1-188 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-188 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.356
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.356
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-188 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-188 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.345
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.345
Title
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AH1-188 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-188 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.327
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.327
Title
Upgrade/install equipment at Ladysmith Substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230 kV strings of breaker and a half scheme.
Description
Upgrade/install equipment at Ladysmith substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230kV strings of breaker and a half scheme.
Cost Information
Time Estimate
Feb 24 2029

Not Contingent

Note: AH1-188 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-188 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.348
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.348
Title
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.
Description
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers. A new redundant breaker ring will be added at Kraken to accommodate the new 500kV line from North Anna to Kraken.
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-188 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-188 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.341
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.341
Title
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.
Description
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV substation and extend approximately 0.2 miles of conductor to fly-over the site.
Cost Information
Time Estimate
Jul 13 2029

Not Contingent

Note: AH1-188 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-188 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.357
Title
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Description
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-188 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-188 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.349
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.349
Title
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Description
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AH1-188 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-188 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.351
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.351
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AH1-188 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-188 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.326
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.326
Title
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Description
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Cost Information
Time Estimate
Feb 24 2029

Not Contingent

Note: AH1-188 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-188 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.342
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.342
Title
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Description
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Cost Information
Time Estimate
Jul 13 2029

Not Contingent

Note: AH1-188 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-188 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.355
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.355
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-188 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-188 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.350
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.350
Title
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Description
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AH1-188 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-188 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

Attachments

AH1-188 One Line Diagram

AH1-188 One Line Diagram.jpg
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.