AH1-239 Phase I Study Report

v1.00 released 2025-10-29 22:10

Upchurch - Zula 69 kV

48.0 MW Capacity / 80.0 MW Energy

Introduction

This Phase I System Impact Study Report (PH1) has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, sections 307 and 308 for New Service Requests (projects) in Transition Cycle 2. The Project Developer/Eligible Customer (developer) is Clinton Solar, LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is East Kentucky Power Cooperative, Inc..

Preface

The Phase I System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle executive summary format and (ii) an individual project-level basis. The Phase I System Impact Study Results (for both the executive summary and individual reports) will be publicly available on PJM’s website. Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.3, PJM takes the following actions during the Phase I System Impact Study:
  1. PJM studies each New Service Request on a summer peak, winter peak and light load RTEP base case study. The case year is dependent on the new services cycle under study. PJM will identify the base case year to be used in the study of a specific cycle on its website.
  2. PJM will only perform load flow analysis during the Phase I System Impact Study.
  3. In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with Affected System impacts and provides each Affected System Operator with a list of New Service Request in the Cycle with potential impacts to their respective system.
  4. PJM will create both the short circuit and stability base cases to be used in the Phase II System Impact Study.
  5. The Phase I System Impact Study results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.
The Transmission Owner takes the following actions during the Phase I System Impact Study:
  1. Identify required Interconnection Facilities to accommodate the New Service Request.
  2. Identify required Network Upgrades to mitigate system violations from the Phase I System Impact Study.
  3. Provide planning-level preliminary estimates of Interconnection Facilities and Network Upgrades including scope, cost and elapsed time to complete the work.

Decision Point I Requirements

At the close of Phase I System Impact Study, PJM will initiate Decision Point I (DP1). During DP1, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.A.1. Additional information on these elements is available in PJM Manual 14H sections 4.4, 6, and 7.

Allowable project modifications at Decision Point I are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

General

The Project Developer has proposed a Solar generating facility located in the East Kentucky Power Cooperative, Inc. zone — Boone County, Kentucky. The installed facilities will have a total capability of 80.0 MW with 48.0 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AH1-239
Project Name:
Upchurch - Zula 69 kV
Project Developer Name:
Clinton Solar, LLC
State:
Kentucky
County:
Boone
Transmission Owner:
East Kentucky Power Cooperative, Inc.
MFO:
80.0
MWE:
80.0
MWC:
48.0
Fuel Type:
Solar
Basecase Study Year:
2028

Physical Interconnection Facility Study

Physical Interconnection Facilities Study is not performed as part of the Phase I System Impact Study. Physical Interconnection Facilities Study will commence in the Phase II System Impact Study.

Point of Interconnection

AH1-239 will interconnect on the East Kentucky Power Cooperative, Inc. transmission system tapping the Upchurch - Zula 69 kV line .

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In the Phase I SIS, the costs shown are subject to change as a result of a facility study performed by the TO during the Phase II or Phase III System Impact Study.

Based on the Phase I SIS results, the AH1-239 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit are also shown below.

Cost Summary
DescriptionCost Allocated to AH1-239Cost Subject to Readiness*
Transmission Owner Interconnection Facilities (TOIF)$755,000$0
Other Scope$0$0
Option To Build Oversight$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$7,405,000$7,405,000
Network Upgrades$5,880,000$5,880,000
System Reliability Network Upgrades
Steady State Thermal & Voltage (SP & LL)$16,837,554$16,837,554
Transient Stability$0$0
Short Circuit$0$0
Transmission Owner Analysis
SubRegional$0$0
Distribution$0$0
Affected System Reinforcements
AFS - PJM Violatons$179,430$0
AFS - Non-PJM Violations$0$0
Total$31,056,984$30,122,554

* Contributes to calculation for Readiness Deposit #2 (RD2). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim deliverability study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 309 (Decision Point I) A.1.a.i and PJM Manual 14H, section 6.2, Readiness Deposit #2 (RD2) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point I (DP1), the Project Developer or Eligible Customer is required to submit Readiness Deposit #2, which is calculated as 10% of cost allocation for required Phase I Network Upgrades minus Readiness Deposit #1.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Readiness Deposit #2 Due for Project AH1-239

Readiness Deposit #2 has been calculated for the project based on the Phase I System Impact Study results and is shown in the table below. This Readiness Deposit #2 must be provided at Decision Point I through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit
Project ID10% of cost allocation for Phase I Network UpgradesReadiness Deposit #1 Received (RD1)Readiness Deposit #2 (RD2) for AH1-239 Project due at DP1
ABA - B
AH1-239$3,012,255$320,000$2,692,255

Note: Failure to provide an acceptable form of Readiness Deposit #2 by the end of Decision Point I will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Transmission Owner Interconnection Facilities
RTEP IDDescriptionTotal Cost ($USD)Allocated Cost ($USD)
(Pending)One (1) 69 kV generator lead line to include, but not limited to, installation of one 69 kV breaker, a 69 kV line monopole dead-end structure and foundation, a 3-pole disconnect switch mounted to the monopole, line conductor from the dead-end structure to the bus position in the switchyard, two (2) 48-strand fiber optic cables, and 69 kV metering equipment.$755,000 $755,000
Stand-Alone Network Upgrades
RTEP IDDescriptionTotal Cost ($USD)Allocated Cost ($USD)
(Pending)Clinton County 69 Switching Station: Construct a new 69 kV switching station along the Upchurch-Zula Junction 69 kV line.$7,405,000 $7,405,000
Network Upgrades
RTEP IDDescriptionTotal Cost ($USD)Allocated Cost ($USD)
(Pending)Revise relay settings/relays at the existing Wayne County substation.$65,000 $65,000
(Pending)Revise relay settings/relays at the existing Summer Shade substation.$65,000 $65,000
(Pending)Install new overhead optical ground wire (OPGW) on the existing Clinton County-Zula Junction-Wayne County 69 kV line sections (5.9 miles).$760,000 $760,000
(Pending)Loop the existing Upchurch-Zula Junction 69 kV line into the new Clinton County interconnection switching station.$580,000 $580,000
(Pending)Install new overhead optical ground wire (OPGW) on the existing Summer Shade-Snow and Albany-Clinton County 69 kV line sections (34.25 miles).$4,410,000 $4,410,000

Based on the scope of work for the Interconnection Facilities, it is expected to take a range of 19 to 31 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

The schedule for any required Network Impact Reinforcements will be more clearly identified in the Phase II and Phase III System Impact Studies.

Transmission Owner Analysis

No Transmission Owner impacts identified.

 

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. EKPC interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Meteorological Data Reporting Requirement
The solar generation facility shall provide the Transmission Provider with site-specific meteorological data including:
  • Temperature (degrees Fahrenheit)
  • Atmospheric Pressure (hectopascals)
  • Irradiance
  • Forced outage data
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AH1-239 was evaluated as a 80.0 MW (48.0 MW Capacity) injection in the EKPC area.

AH1-239 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 80.0 MW (80.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AEP
05CLOV17_XFL-05CLOVRD 345.0 kV Ckt 17 line
AEP_P4_#7421_05CLOVRD 765_BB2_SRT-A
BreakerAC107.8 %2320.0B2500.924.84
GD2AEP
05CLOV17_XFL-05CLOVRD 345.0 kV Ckt 17 line
AEP_P1-3_#7421_05CLOVRD 765_14_SRT-A
SingleAC106.66 %2320.0B2474.483.38
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AP_P1-3_MP-765-501T_SRT-A
SingleAC121.06 %3393.4B4107.975.93
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AP_P2-3_MP-500-020_SRT-SL
BreakerAC117.02 %3610.0B4224.558.54
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AP_P2-3_MP-500-021_SRT-SL
BreakerAC116.77 %3610.0B4215.438.51
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AEP_P4_#37_05MOUNTN 765_B1_SRT-A
BreakerAC116.68 %3610.0B4211.988.5
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AEP_P4_#2942_05KAMMER 765_PP_SRT-A
BreakerAC116.36 %3610.0B4200.438.5
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P1-2_#17217_SRT-A
SingleAC115.67 %5523.0B6388.327.49
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P4_#7445_05MARYSV 765_B_SRT-A
BreakerAC113.05 %5523.0B6243.539.11
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Base Case
SingleAC108.86 %4558.0A4961.856.0
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A
BreakerAC108.47 %5523.0B5991.0210.5
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P2-2_#7222_05MALIS 765_1_SRT-A
BusAC107.09 %5523.0B5914.329.45
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P1-2_#7422_16_SRT-A
SingleAC106.56 %5523.0B5885.347.33
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P7-1_#10944___SRT-A
TowerAC106.16 %5523.0B5863.479.47
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P7-1_#10856___SRT-A
TowerAC102.19 %5523.0B5644.149.57
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P1-2_#309_15_SRT-A
SingleAC141.78 %1540.0B2183.342.5
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P1-2_#709_546_SRT-A
SingleAC141.21 %1540.0B2174.622.63
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P2-2_#6763_05BIERSR 345_2_SRT-A
BusAC135.59 %1540.0B2088.163.72
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
34569 34598 34524_SRT-A
TowerAC132.73 %1540.0B2044.013.69
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
34524 34598_SRT-A
TowerAC132.58 %1540.0B2041.733.69
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
Base Case
SingleAC131.72 %1189.0A1566.092.45
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P2-2_#308_05CULLOD 765_1_SRT-A
BusAC129.85 %1540.0B1999.633.78
IPDEKPC
2ALBANY-2SNOW T 69.0 kV Ckt 1 line
EKPC_P1-2_AG1-471 TP-AH1-239 TP-69_SRT-A
SingleAC111.19 %54.0B60.0580.0
IPDEKPC
2ALBANY-2SNOW T 69.0 kV Ckt 1 line
EKPC_P1-2_AG1-471 TP-2ZULA J NO-69_SRT-A
SingleAC111.19 %54.0B60.0580.0
GD2EKPC
2ALBANY-2SNOW T 69.0 kV Ckt 1 line
EKPC_P1-2_AG1-471 TP-2ZULA J NO-69_SRT-A
SingleAC109.69 %54.0B59.2348.0
GD2EKPC
2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC195.67 %63.0B123.275.35
GD2EKPC
2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC188.87 %63.0B118.994.89
GD2EKPC
2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC188.85 %63.0B118.984.89
GD2EKPC
2COOPER DIST-2COOPER 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC195.49 %63.0B123.165.35
GD2EKPC
2COOPER DIST-2COOPER 69.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC188.68 %63.0B118.874.89
GD2EKPC
2COOPER DIST-2COOPER 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC188.66 %63.0B118.864.89
GD2EKPC
2COOPER-2SOMERSET 69.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
TowerAC217.32 %76.0B165.163.98
GD2EKPC
2COOPER-2SOMERSET 69.0 kV Ckt 2 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
TowerAC217.32 %76.0B165.163.98
GD2EKPC
2DENNY-2BRONSTON T 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC287.7 %46.0B132.345.35
GD2EKPC
2DENNY-2BRONSTON T 69.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC277.52 %46.0B127.664.89
GD2EKPC
2DENNY-2BRONSTON T 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC277.5 %46.0B127.654.89
GD2EKPC
2PATTON RD J-2FOX HOLLOW 69.0 kV Ckt 1 line
EKPC_P4-2_SSHAD S11-1004_SRT-A
BreakerAC105.62 %98.0B103.519.24
GD2EKPC
2PATTON RD J-2FOX HOLLOW 69.0 kV Ckt 1 line
EKPC_P2-3_SSHAD S11-1039_SRT-A
BreakerAC105.62 %98.0B103.519.24
GD2EKPC
2PATTON RD J-2FOX HOLLOW 69.0 kV Ckt 1 line
EKPC_P2-2_SUMMSHADE 161 #2_SRT-A
BusAC105.59 %98.0B103.489.24
GD2EKPC
2PATTON RD J-2FOX HOLLOW 69.0 kV Ckt 1 line
EKPC_P2-3_SSHAD S11-1044_SRT-A
BreakerAC104.71 %98.0B102.619.08
GD2EKPC
2PATTON RD J-2FOX HOLLOW 69.0 kV Ckt 1 line
EKPC_P4-5_SSHAD S11-1004_SRT-A
BreakerAC104.69 %98.0B102.69.08
GD2EKPC/LGEE
2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
TowerAC362.3 %105.0B380.429.42
GD2EKPC/LGEE
2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line
EKPC_P2-2_ELIHU-COOP 161_SRT-A
BusAC273.46 %105.0B287.137.73
GD2EKPC/LGEE
2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
TowerAC273.14 %105.0B286.87.73
GD2EKPC/LGEE
2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line
EKPC_P1-2_COOP-ELIHU161_SRT-A
SingleAC250.96 %105.0B263.55.39
GD2EKPC/LGEE
2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC136.6 %105.0B143.437.61
GD2EKPC/LGEE
2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC136.57 %105.0B143.47.61
GD2EKPC/LGEE
2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC113.62 %105.0B119.36.66
GD2EKPC
2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
TowerAC319.42 %115.0B367.348.21
GD2EKPC
2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line
EKPC_P2-2_ELIHU-COOP 161_SRT-A
BusAC233.63 %115.0B268.676.53
GD2EKPC
2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
TowerAC233.32 %115.0B268.326.53
GD2EKPC
2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line
EKPC_P1-2_COOP-ELIHU161_SRT-A
SingleAC217.54 %115.0B250.174.56
GD2EKPC
2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC119.59 %115.0B137.536.41
GD2EKPC
2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC119.55 %115.0B137.496.41
GD2EKPC
2SUMM SHADE-2EDM-JBGAL J 69.0 kV Ckt 1 line
EKPC_P2-3_SSHAD S11-1014_SRT-A
BreakerAC108.34 %46.0B49.842.54
GD2EKPC
2SUMM SHADE-2EDM-JBGAL J 69.0 kV Ckt 1 line
EKPC_P2-3_SSHAD S11-1004_SRT-A-1
BreakerAC105.05 %46.0B48.322.36
GD2EKPC
2SUMM SHADE-2EDM-JBGAL J 69.0 kV Ckt 1 line
EKPC_P4-5_SSHAD S11-1004_SRT-A
BreakerAC101.24 %46.0B46.573.72
IPDEKPC
2UPCHURCH T-2ALBANY 69.0 kV Ckt 1 line
EKPC_P1-2_AG1-471 TP-AH1-239 TP-69_SRT-A
SingleAC138.84 %54.0B74.9880.0
IPDEKPC
2UPCHURCH T-2ALBANY 69.0 kV Ckt 1 line
EKPC_P1-2_AG1-471 TP-2ZULA J NO-69_SRT-A
SingleAC138.84 %54.0B74.9880.0
GD2EKPC
2UPCHURCH T-2ALBANY 69.0 kV Ckt 1 line
EKPC_P1-2_AG1-471 TP-2ZULA J NO-69_SRT-A
SingleAC135.33 %54.0B73.0848.0
GD2EKPC
2ZULA J NO-2WAYNE CO 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC135.11 %63.0B85.1252.75
GD2EKPC
2ZULA J NO-2WAYNE CO 69.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC135.11 %63.0B85.1252.75
GD2EKPC
2ZULA J NO-2WAYNE CO 69.0 kV Ckt 1 line
EKPC_P2-3_MAR W38-1014_SRT-A
BreakerAC134.08 %63.0B84.4752.85
GD2EKPC
2ZULA J NO-2WAYNE CO 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC134.07 %63.0B84.4752.69
GD2EKPC
2ZULA J NO-2WAYNE CO 69.0 kV Ckt 1 line
EKPC_P4-2_TAYLOR W45-1014_SRT-A
BreakerAC133.36 %63.0B84.0152.88
GD2EKPC
2ZULA J NO-2WAYNE CO 69.0 kV Ckt 1 line
EKPC_P4-2_MAR W38-1004_SRT-A
BreakerAC133.36 %63.0B84.0152.88
GD2EKPC
2ZULA J NO-2WAYNE CO 69.0 kV Ckt 1 line
EKPC_P2-2_GREEN CO 161_SRT-A
BusAC132.81 %63.0B83.6752.87
GD2EKPC
2ZULA J NO-2WAYNE CO 69.0 kV Ckt 1 line
EKPC_P2-2_CASEY CO 161_SRT-A
BusAC132.58 %63.0B83.5352.81
GD2EKPC
2ZULA J NO-2WAYNE CO 69.0 kV Ckt 1 line
EKPC_P2-2_MARION CO 161_SRT-A
BusAC132.49 %63.0B83.4752.86
GD2EKPC
2ZULA J NO-2WAYNE CO 69.0 kV Ckt 1 line
EKPC_P2-2_MCCR-WINFD161_SRT-A
BusAC132.37 %63.0B83.3952.69
GD2EKPC
2ZULA J NO-2WAYNE CO 69.0 kV Ckt 1 line
EKPC_P7-1_BULL 161 DBL_SRT-A
TowerAC131.97 %63.0B83.1452.89
GD2EKPC
2ZULA J NO-2WAYNE CO 69.0 kV Ckt 1 line
EKPC_P7-1_SSHAD 161 DBL_SRT-A
TowerAC131.82 %63.0B83.0552.89
IPDEKPC
2ZULA J NO-2WAYNE CO 69.0 kV Ckt 1 line
EKPC_P1-2_AH1-239 TP-2UPCHURCH T-69_SRT-A
SingleAC130.76 %63.0B82.3880.0
GD2EKPC
2ZULA J NO-2WAYNE CO 69.0 kV Ckt 1 line
EKPC_P1-2_AH1-239 TP-2UPCHURCH T-69_SRT-A
SingleAC127.38 %63.0B80.2548.0
GD2EKPC/LGEE
4MARION CO-4LEBANON 138.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
TowerAC120.11 %220.0B264.255.85
GD2EKPC/LGEE
4MARION CO-4LEBANON 138.0 kV Ckt 1 line
EKPC_P2-2_ELIHU-COOP 161_SRT-A
BusAC100.58 %220.0B221.275.08
GD2EKPC/LGEE
4MARION CO-4LEBANON 138.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
TowerAC100.49 %220.0B221.085.08
GD2EKPC
5COOPER1-5PULASK CO J 161.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
TowerAC116.86 %298.0B348.265.76
GD2EKPC
5COOPER2-5COOPER1 161.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
TowerAC173.45 %501.0B869.015.58
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P7-1_LAURL 161 DBL_SRT-A
TowerAC270.52 %277.0B749.3413.2
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P2-2_LAUR-LAURD161_SRT-A
BusAC270.47 %277.0B749.2113.24
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P4-5_LAURL S50-1024_SRT-A
BreakerAC270.46 %277.0B749.1813.2
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P2-3_LAURL S50-1024_SRT-A
BreakerAC270.45 %277.0B749.1513.2
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P2-2_LAUREL CO 161_SRT-A
BusAC270.38 %277.0B748.9513.22
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P1-2_LAUR-L DAM161_SRT-A
SingleAC257.87 %277.0B714.319.24
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Base Case
SingleAC257.03 %219.0A562.897.87
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P1-2_COOP 161 TIE_SRT-A
SingleAC254.86 %277.0B705.974.0
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 1_SRT-A
TowerAC224.64 %277.0B622.247.69
GD2EKPC
5LAUREL CO-5PITTSBURG 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC174.31 %200.0B348.624.13
GD2EKPC
5LAUREL CO-5PITTSBURG 161.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC173.74 %200.0B347.484.11
GD2EKPC
5LAUREL CO-5PITTSBURG 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC173.72 %200.0B347.444.11
GD2EKPC
5LAUREL CO-5PITTSBURG 161.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
TowerAC102.02 %200.0B204.053.86
GD2EKPC
5LAUREL CO-5PITTSBURG 161.0 kV Ckt 1 line
EKPC_P2-2_ELIHU-COOP 161_SRT-A
BusAC101.66 %200.0B203.323.86
GD2EKPC
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC301.06 %200.0B602.126.02
GD2EKPC
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC300.14 %200.0B600.275.99
GD2EKPC
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC300.12 %200.0B600.245.99
GD2EKPC
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
TowerAC178.78 %200.0B357.555.56
GD2EKPC
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
EKPC_P2-2_ELIHU-COOP 161_SRT-A
BusAC178.17 %200.0B356.335.56
GD2EKPC
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
EKPC_P1-2_COOP-ELIHU161_SRT-A
SingleAC173.81 %200.0B347.623.88
GD2EKPC
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
EXT_B-345-100_SRT-S
SingleAC144.72 %200.0B289.443.5
GD2EKPC
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
EKPC_P2-2_PULASKI 161_SRT-A
BusAC131.09 %200.0B262.193.47
GD2EKPC
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
EKPC_P2-2_LIB JCT 161_SRT-A
BusAC129.44 %200.0B258.873.45
GD2EKPC
5LIBERTY J-5CASEY CO 161.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
TowerAC101.66 %182.0B185.033.55
GD2EKPC
5MARION CO-4MARION CO 161.0/138.0 kV Ckt 1 transformer
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
TowerAC119.88 %220.0B263.745.85
GD2EKPC
5MARION CO-4MARION CO 161.0/138.0 kV Ckt 1 transformer
EKPC_P2-2_ELIHU-COOP 161_SRT-A
BusAC100.55 %220.0B221.225.08
GD2EKPC
5MARION CO-4MARION CO 161.0/138.0 kV Ckt 1 transformer
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
TowerAC100.47 %220.0B221.025.08
GD2EKPC
5PULASK CO J-5LIBERTY J 161.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
TowerAC100.77 %256.0B257.974.38
GD2DAY/EKPC
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
DEOK_P4_1445_ZIMMER_SRT-A
BreakerAC118.71 %1532.0B1818.597.09
GD2DAY/EKPC
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
DEOK_P4_1449_ZIMMER_SRT-A
BreakerAC118.58 %1532.0B1816.677.08
GD2DAY/EKPC
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
34569 34598 34524_SRT-A
TowerAC117.61 %1532.0B1801.716.38
GD2DAY/EKPC
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
DEOK_P4_1373_PORTUNION_SRT-A
BreakerAC116.62 %1532.0B1786.66.42
GD2DAY/EKPC
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
DEOK_P4_1493_RED BANK_SRT-A
BreakerAC115.28 %1532.0B1766.126.3
GD2DAY/EKPC
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
DEOK_P4_1487_RED BANK_SRT-A
BreakerAC115.23 %1532.0B1765.386.3
GD2DAY/EKPC
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
DEOK_P_CIRCUIT1883&4545REDBANKSILGRVZIMMER_SRT-A
TowerAC115.19 %1532.0B1764.776.3
GD2DAY/EKPC
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
DEOK_P2.2_SILVER GROVE 345 BUS_SRT-A
BusAC115.16 %1532.0B1764.326.3
GD2DAY/EKPC
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
Base Case
SingleAC114.67 %1240.0A1421.954.25
GD2DAY/EKPC
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
EKPC_P2-2_MELD-SPUR 345_SRT-A
BusAC114.33 %1532.0B1751.587.11
GD2DAY/EKPC
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
DEOK_P1_ZIMMER-MELDAHL 34576_SRT-A
SingleAC105.32 %1532.0B1613.524.94
GD2DAY/EKPC
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
DEOK_P1_RED BANK-SILVER GROVE-ZIMMER 4545_SRT-A
SingleAC103.95 %1532.0B1592.574.4
GD2EKPC
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC157.65 %54.0B85.1352.75
GD2EKPC
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC157.65 %54.0B85.1352.75
GD2EKPC
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
EKPC_P2-3_MAR W38-1014_SRT-A
BreakerAC156.44 %54.0B84.4852.85
GD2EKPC
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC156.42 %54.0B84.4752.69
GD2EKPC
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
EKPC_P4-2_MAR W38-1004_SRT-A
BreakerAC155.6 %54.0B84.0252.88
GD2EKPC
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
EKPC_P4-2_TAYLOR W45-1014_SRT-A
BreakerAC155.6 %54.0B84.0252.88
GD2EKPC
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
EKPC_P2-2_GREEN CO 161_SRT-A
BusAC154.94 %54.0B83.6752.87
GD2EKPC
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
EKPC_P2-2_CASEY CO 161_SRT-A
BusAC154.68 %54.0B83.5352.81
GD2EKPC
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
EKPC_P2-2_MARION CO 161_SRT-A
BusAC154.57 %54.0B83.4752.86
GD2EKPC
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
EKPC_P2-2_MCCR-WINFD161_SRT-A
BusAC154.44 %54.0B83.452.69
GD2EKPC
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
EKPC_P7-1_BULL 161 DBL_SRT-A
TowerAC153.98 %54.0B83.1552.89
GD2EKPC
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
EKPC_P7-1_SSHAD 161 DBL_SRT-A
TowerAC153.79 %54.0B83.0552.89
IPDEKPC
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
EKPC_P1-2_AH1-239 TP-2UPCHURCH T-69_SRT-A
SingleAC152.57 %54.0B82.3980.0
GD2EKPC
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
EKPC_P1-2_AH1-239 TP-2UPCHURCH T-69_SRT-A
SingleAC148.65 %54.0B80.2748.0
GD2EKPC
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
Base Case
SingleAC108.81 %49.0A53.3236.86
GD2EKPC
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
EKPC_P1-2_MCCR-WAYNE161_SRT-A
SingleAC105.03 %54.0B56.7227.69
GD2EKPC
AH1-034 TP-2PATTON RD J 69.0 kV Ckt 1 line
EKPC_P2-3_SSHAD S11-1039_SRT-A
BreakerAC117.38 %63.0B73.955.13
GD2EKPC
AH1-034 TP-2PATTON RD J 69.0 kV Ckt 1 line
EKPC_P4-2_SSHAD S11-1004_SRT-A
BreakerAC117.37 %63.0B73.945.13
GD2EKPC
AH1-034 TP-2PATTON RD J 69.0 kV Ckt 1 line
EKPC_P2-2_SUMMSHADE 161 #2_SRT-A
BusAC117.33 %63.0B73.925.13
GD2EKPC
AH1-034 TP-2PATTON RD J 69.0 kV Ckt 1 line
EKPC_P4-5_SSHAD S11-1004_SRT-A
BreakerAC116.99 %63.0B73.75.04
GD2EKPC
AH1-034 TP-2PATTON RD J 69.0 kV Ckt 1 line
EKPC_P2-3_SSHAD S11-1044_SRT-A
BreakerAC116.97 %63.0B73.695.04
GD2EKPC
AH1-034 TP-2PATTON RD J 69.0 kV Ckt 1 line
EKPC_P2-2_SUMMSHADE 161 #1_SRT-A
BusAC109.71 %63.0B69.125.26
IPDEKPC
AH1-239 TP-2UPCHURCH T 69.0 kV Ckt 1 line
EKPC_P1-2_AG1-471 TP-2ZULA J NO-69_SRT-A
SingleAC150.75 %54.0B81.4180.0
IPDEKPC
AH1-239 TP-2UPCHURCH T 69.0 kV Ckt 1 line
EKPC_P1-2_AG1-471 TP-AH1-239 TP-69_SRT-A
SingleAC150.75 %54.0B81.4180.0
GD2EKPC
AH1-239 TP-2UPCHURCH T 69.0 kV Ckt 1 line
EKPC_P1-2_AG1-471 TP-2ZULA J NO-69_SRT-A
SingleAC148.61 %54.0B80.2548.0
GD2EKPC
AH1-239 TP-2UPCHURCH T 69.0 kV Ckt 1 line
EKPC_P2-2_TVA WAYNE 161_SRT-A
BusAC100.2 %54.0B54.1129.13
IPDEKPC
AH1-239 TP-AG1-471 TP 69.0 kV Ckt 1 line
EKPC_P1-2_AH1-239 TP-2UPCHURCH T-69_SRT-A
SingleAC152.64 %54.0B82.4380.0
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
EKPC_P1-2_COOP-DEN161_SRT-A-1
SingleAC188.87 %298.0B562.832.73
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
EKPC_P2-2_LAUR-LAURD161_SRT-A
BusAC136.17 %298.0B405.793.67
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
EKPC_P2-3_LAURL S50-1014_SRT-A
BreakerAC136.16 %298.0B405.773.67
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
EKPC_P2-2_LAUREL CO 161_SRT-A
BusAC136.16 %298.0B405.773.67
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
EKPC_P4-5_LAURL S50-1014_SRT-A
BreakerAC136.16 %298.0B405.763.67
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
EKPC_P7-1_LAURL 161 DBL_SRT-A
TowerAC136.1 %298.0B405.573.67
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
EKPC_P1-2_LAUR-L DAM161_SRT-A
SingleAC135.52 %298.0B403.842.56
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
EKPC_P1-2_COOP-LAUREL161_SRT-A-1
SingleAC267.78 %210.0B562.332.73
GD2EKPC
AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC175.99 %298.0B524.466.05
GD2EKPC
AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC175.54 %298.0B523.16.01
GD2EKPC
AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC175.53 %298.0B523.076.01

Details for 05CLOV17_XFL-05CLOVRD 345.0 kV Ckt 17 line l/o AEP_P4_#7421_05CLOVRD 765_BB2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05CLOV17_XFL-05CLOVRD 345.0 kV Ckt 17 line
Contingency Name:
AEP_P4_#7421_05CLOVRD 765_BB2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.8 %
Rating:2320.0 MVA
Rating Type:B
MVA to Mitigate:2500.92
MW Contribution:4.84
Bus #Bus NameTypeMW Contribution
970563AG2-360 GEN
50/50
26.913
943031AE2-326 GEN
Solar/Wind Harmer
3.913
962751AG1-124 GEN
Solar/Wind Harmer
9.063
960911AF2-382 GEN
Solar/Wind Harmer
5.848
971461AH1-227 GEN
Solar/Wind Harmer
3.853
972103AH1-617 GEN
Solar/Wind Harmer
13.923
270053AF1-130 C
Solar/Wind Harmer
2.393
972273AH1-721 GEN
Adder
50.38
970273AG2-179 GEN
Solar/Wind Harmer
2.326
339250AF1-203 GEN
Solar/Wind Harmer
0.353
971155AH1-034 GEN
Solar/Wind Harmer
5.827
962251AG1-071 GEN
Solar/Wind Harmer
3.186
24686205CER G4
Adder
4.732
24686405CER G5
Adder
4.713
960741AF2-365 GEN
Solar/Wind Harmer
2.839
966571AG1-526 GEN
Solar/Wind Harmer
12.469
970093AG2-073 GEN
Solar/Wind Harmer
5.535
270030AE2-140 GEN
Solar/Wind Harmer
10.994
3429391JKCT 9G
Adder
4.484
972167AH1-666 GEN
Solar/Wind Harmer
3.962
958171AF2-111 GEN
Solar/Wind Harmer
12.227
970243AG2-164 GEN
Solar/Wind Harmer
12.56
970519AG2-331 GEN
Solar/Wind Harmer
8.438
970699AG2-449 GEN
Solar/Wind Harmer
5.582
942481AE2-261 GEN
Solar/Wind Harmer
14.457
276621W2-048 GEN
Solar/Wind Harmer
2.989
276838X2-022 GEN2
Solar/Wind Harmer
0.111
970193AG2-126 GEN
Solar/Wind Harmer
7.161
276668AB2-070 GEN1
Solar/Wind Harmer
1.072
276686W4-005 GEN3
Solar/Wind Harmer
1.442
971993AH1-541 GEN
Solar/Wind Harmer
4.403
965931AG1-462 GEN
Solar/Wind Harmer
12.103
25196008MFTGT1
Adder
0.634
24728705AND G3
Adder
3.77
24728505AND G1
Adder
1.803
274853TWINGROVE;U1
Solar/Wind Harmer
3.387
965091AG1-374 GEN
Solar/Wind Harmer
14.098
959611AF2-252 GEN
Solar/Wind Harmer
1.093
274878BISHOP HL;2U
Solar/Wind Harmer
1.583
276157O29GEN1
Solar/Wind Harmer
1.787
942111AE2-223 GEN
Solar/Wind Harmer
3.834
274858EASY ROAD;U2
Solar/Wind Harmer
2.241
270214AC2-123 GEN
Solar/Wind Harmer
2.486
971277AH1-098 GEN
Solar/Wind Harmer
3.314
24728205BUCHG1
Adder
3.631
971225AH1-072 GEN
Solar/Wind Harmer
1.502
971227AH1-073 GEN
Solar/Wind Harmer
1.502
944971AF1-162 GEN
Solar/Wind Harmer
4.505
24723005RIVRG1
Adder
11.619
24723105RIVRG2
Adder
11.619
966021AG1-471 GEN
Solar/Wind Harmer
3.284
971485AH1-239 GEN
Solar/Wind Harmer
4.843
339231AF1-038_GEN
Solar/Wind Harmer
1.082
339255AE2-071 GEN
Solar/Wind Harmer
0.618
964781AG1-341 GEN
Solar/Wind Harmer
6.173
339236AF1-050_GEN
Solar/Wind Harmer
1.045
971081AG2-670 GEN
Solar/Wind Harmer
4.298
24685805CER G1
Adder
4.726
24685905CER G2
Adder
4.726
970653AG2-424 GEN
Solar/Wind Harmer
2.668
970653AG2-424 GEN
Solar/Wind Harmer
0.965
960161AF2-307 GEN
Solar/Wind Harmer
3.502
942891AE2-308 GEN
Solar/Wind Harmer
5.447
964571AG1-320 GEN
Solar/Wind Harmer
4.432
971125AH1-004 GEN
Solar/Wind Harmer
2.1
970107AG2-081 GEN
Solar/Wind Harmer
1.575
972043AH1-570 GEN
Solar/Wind Harmer
1.293
972045AH1-571 GEN
Solar/Wind Harmer
1.035
339221AD2-048_GEN
Solar/Wind Harmer
0.789
970235AG2-159 GEN
Solar/Wind Harmer
2.014
970235AG2-159 GEN
Solar/Wind Harmer
1.23
270444AC2-157 GEN1
Solar/Wind Harmer
2.736
970239AG2-162 GEN
Solar/Wind Harmer
5.35
276916AD2-100_GEN
Solar/Wind Harmer
10.174
276911AD2-131_GEN
Solar/Wind Harmer
2.056
957381AF2-032 GEN
Solar/Wind Harmer
0.202
276763AC1-053 GEN1
Solar/Wind Harmer
1.888
276764AC1-053 GEN2
Solar/Wind Harmer
1.888
945391AF1-204 GEN
Solar/Wind Harmer
6.653
270186AC1-089 GEN
Solar/Wind Harmer
2.887
960611AF2-352 GEN
Solar/Wind Harmer
1.093
276782AC1-033 GEN
Solar/Wind Harmer
1.871
276741O09 GEN1
Solar/Wind Harmer
1.678
276708O09 GEN2
Solar/Wind Harmer
1.678
972267AH1-718 GEN
Adder
1.953
274851PROVIDENC;RU
Solar/Wind Harmer
1.333
274849CRESCENT ;1U
Solar/Wind Harmer
0.866
276645AC1-214 GEN1
Solar/Wind Harmer
0.627
276646AC1-214 GEN2
Solar/Wind Harmer
0.627
276603SUBLETTE C
Solar/Wind Harmer
0.491
274764LEE CO EC;5U
Adder
4.36
274765LEE CO EC;6U
Adder
4.36
274762LEE CO EC;3U
Adder
4.35
274763LEE CO EC;4U
Adder
4.309
970241AG2-163 GEN
Solar/Wind Harmer
11.684
938861AE1-114 GEN
Solar/Wind Harmer
3.828
274856ECOGROVE ;U1
Solar/Wind Harmer
1.572
276611AD2-172 GEN
Solar/Wind Harmer
1.193
25194408D.CRK1
Adder
3.478
25194508D.CRK3
Adder
0.65
274683WAUKEGAN ;8U
Adder
9.693
274683WAUKEGAN ;8U
Adder
8.17
274696ROCKY RD ;4P
Adder
5.238
274695ROCKY RD ;2P
Adder
5.117
274693ROCKY RD ;1P
Adder
5.067
274697ROCKY RD ;3P
Adder
1.39
24728805RICHG1
Adder
1.728
24728905RICHG2
Adder
1.728
3132123MT JACKSON
Solar/Wind Helper
0.746
315821AE2-092 GEN
Solar/Wind Helper
1.824
966001AG1-469 GEN
Solar/Wind Helper
0.172
315651AD1-115 GEN
Solar/Wind Helper
0.441
3146776BUCKING
Solar/Wind Helper
0.504
3146776BUCKING
Solar/Wind Helper
0.041
966871AG1-558 GEN
Solar/Wind Helper
0.167
316468AD1-105 GEN
Solar/Wind Helper
0.61
316447AC1-158 HLD
Solar/Wind Helper
1.451
316075AC2-137 C
Solar/Wind Helper
0.179
3143526WINTERP
Solar/Wind Helper
0.609
3142946ENON
Solar/Wind Helper
0.011
316077AC2-138 C
Solar/Wind Helper
0.106
316487AF1-042 GEN
Solar/Wind Helper
0.113
24735205WLF2G2
Adder
4.909
24728305BUCHG2
Adder
3.631
971687AH1-348 GEN
Solar/Wind Harmer
0.747
971403AH1-188 GEN
Solar/Wind Harmer
9.188
971315AH1-136 GEN
Solar/Wind Harmer
1.275
24723205RIVRG3
Adder
11.619
970273AG2-179 GEN
Solar/Wind Harmer
1.456
270336AE1-100 GEN
Solar/Wind Harmer
1.013
962241AG1-070 GEN
Solar/Wind Harmer
2.607
964901AG1-354 GEN
Solar/Wind Harmer
8.682
339241AF1-083 GEN
Solar/Wind Harmer
0.951
24686105CER G3
Adder
4.757
24686505CER G6
Adder
4.751
971821AH1-427 GEN
Solar/Wind Harmer
5.664
3429241JKCT 3G
Adder
6.434
971565AH1-281 GEN
Solar/Wind Harmer
1.077
3429421JKCT 10G
Adder
4.484
958131AF2-107 GEN
Solar/Wind Harmer
2.669
943111AE2-339 GEN
Solar/Wind Harmer
0.467
943811AF1-049 GEN
Solar/Wind Harmer
1.99
339216AC1-074 GEN
Solar/Wind Harmer
0.86
970091AG2-072 GEN
Adder
38.082
945681AF1-233 GEN
Solar/Wind Harmer
9.348
270445AC2-157 GEN2
Solar/Wind Harmer
2.736
970333AG2-219 GEN
Solar/Wind Harmer
15.351
965911AG1-460 GEN
Solar/Wind Harmer
0.675
276615X2-022 GEN
Solar/Wind Harmer
0.939
963831AG1-236 GEN
Solar/Wind Harmer
4.696
274880W4-005 GEN4
Solar/Wind Harmer
1.442
972175AH1-670 GEN
Solar/Wind Harmer
6.469
25196008MFTGT1
Adder
0.655
24728605AND G2
Adder
1.803
274854TWINGROVE;U2
Solar/Wind Harmer
3.316
274877BISHOP HL;1U
Solar/Wind Harmer
1.583
276158O29GEN2
Solar/Wind Harmer
2.349
25196808ZIMRHP
Adder
35.531
276726Z2-087_GEN
Solar/Wind Harmer
3.699
939741AE1-205 GEN
Solar/Wind Harmer
9.353
274857EASY ROAD;U1
Solar/Wind Harmer
2.241
274761LEE CO EC;2U
Adder
4.35
274766LEE CO EC;7U
Adder
4.299
963741AG1-226 GEN
Solar/Wind Harmer
21.031
24721705FLATG2
Adder
9.459
971475AH1-234 GEN
Solar/Wind Harmer
10.445
972235AH1-702 GEN1
Adder
1.172
274822ROCKFORD ;11
Adder
9.123
25194608D.CRK4
Adder
0.756
274828WAUKEGAN ;BP
Adder
5.081
274682WAUKEGAN ;7U
Adder
8.262
274745AC1-111 GEN9
Adder
2.558
315616AA1-038_C
Solar/Wind Helper
1.807
3148013FISHERV
Solar/Wind Helper
0.286
316499AE2-029_GEN
Solar/Wind Helper
0.937
3132273ORANGE
Solar/Wind Helper
0.03
3147666LOUISA
Solar/Wind Helper
0.335
237061AD1-155 GEN
Solar/Wind Helper
0.025
316170AC1-121 GEN2
Solar/Wind Helper
0.204
316313AB2-026
Solar/Wind Helper
0.2
316258AE1-075 C
Solar/Wind Helper
0.18
316405AF2-144 C
Solar/Wind Helper
0.15
3146776BUCKING
Solar/Wind Helper
0.045
966881AG1-559 GEN
Solar/Wind Helper
0.168
316473AC1-191 GEN
Solar/Wind Helper
0.759
23583801GRNGAP
Solar/Wind Helper
2.125
238147AE2-230_GEN1
Solar/Wind Helper
0.213
238149AF1-291A_GEN
Solar/Wind Helper
0.061
316095T157 G97
Solar/Wind Helper
0.556
316044AC1-158 PL1
Solar/Wind Helper
0.659
316450AC1-158 RIC
Solar/Wind Helper
0.176
3141906WESTMOR
Solar/Wind Helper
0.046
3142946ENON
Solar/Wind Helper
0.038
3141196NOKESVL
Solar/Wind Helper
0.452
316404AE1-155 C
Solar/Wind Helper
0.945
316484AD2-074 GEN
Solar/Wind Helper
0.215
970819AG2-516 GEN
Solar/Wind Harmer
0.945
24735105WLF2G1
Adder
4.909
24734705WLF1G3
Adder
4.898
24734805WLF1G4
Adder
4.898
24734905WLF1G5
Adder
4.898
966391AG1-508 GEN
Solar/Wind Harmer
2.785
971981AH1-535 GEN
Solar/Wind Harmer
7.897
971313AH1-133 GEN
Solar/Wind Harmer
7.717
970281AG2-184 GEN
Solar/Wind Harmer
14.619
972143AH1-644 GEN
Solar/Wind Harmer
6.961
962211AG1-066 GEN
Solar/Wind Harmer
1.642
270399AC1-101 GEN
Solar/Wind Harmer
2.775
270400AC1-102 GEN
Solar/Wind Harmer
2.775
957241AF2-018 GEN
Solar/Wind Harmer
2.86
965401AG1-405 GEN
Solar/Wind Harmer
3.385
965411AG1-406 GEN
Solar/Wind Harmer
1.519
972203AH1-686 GEN
Adder
1.34
339211AE2-254 GEN
Solar/Wind Harmer
0.854
970455AG2-298 GEN
Solar/Wind Harmer
3.268
3429211JKCT 2G
Adder
6.351
339243AC2-075 GEN1
Solar/Wind Harmer
0.233
972163AH1-664 GEN
Solar/Wind Harmer
4.977
972165AH1-665 GEN
Solar/Wind Harmer
3.982
944221AF1-090 GEN
Solar/Wind Harmer
5.331
276849AB2-070 GEN2
Solar/Wind Harmer
1.072
276848AB2-070 GEN3
Solar/Wind Harmer
1.072
276785W4-005 GEN1
Solar/Wind Harmer
1.442
276174W4-005 GEN2
Solar/Wind Harmer
1.442
946321AF1-296 GEN
Solar/Wind Harmer
4.942
25196108MFTGT2
Adder
0.722
25196108MFTGT2
Adder
0.67
274848CAMPGROVE;RU
Solar/Wind Harmer
3.031
961011AF2-392 GEN
Solar/Wind Harmer
5.096
957751AF2-069 GEN
Solar/Wind Harmer
0.215
276655WTG1_EQ
Solar/Wind Harmer
4.083
276656WTG2_EQ
Solar/Wind Harmer
0.541
959341AF2-225 GEN
Solar/Wind Harmer
7.015
941731AE2-173 GEN
Solar/Wind Harmer
2.719
971681AH1-341 GEN
Solar/Wind Harmer
7.003
270367AC2-061_GEN
Solar/Wind Harmer
1.482
276612AE2-035 GEN
Solar/Wind Harmer
1.193
274823ROCKFORD ;21
Adder
9.057
25196408WSDLE3
Adder
4.052
25196308WSDLE2
Adder
4.017
25196208WSDLE1
Adder
4.006
25196708WSDLE6
Adder
3.996
25196508WSDLE4
Adder
3.896
274746AC1-111 G10
Adder
2.558
274744AC1-111 GEN8
Adder
2.558
274731ELWOOD EC;2P
Adder
7.487
274733ELWOOD EC;3P
Adder
7.487
274735ELWOOD EC;4P
Adder
2.023
3148463FAIRFLD
Solar/Wind Helper
0.398
3148133STUARTS
Solar/Wind Helper
0.172
3148013FISHERV
Solar/Wind Helper
0.165
3138266HYDRAULIC
Solar/Wind Helper
0.011
3138266HYDRAULIC
Solar/Wind Helper
0.007
316164AC1-076 GEN
Solar/Wind Helper
0.618
23546401DTGZ2-030
Solar/Wind Helper
0.04
238152AF2-075_GEN
Solar/Wind Helper
0.304
316312AB1-027
Solar/Wind Helper
0.233
316233AE1-074 FULL
Solar/Wind Helper
0.179
3141426STAFORD
Solar/Wind Helper
0.025
316223AC1-118
Solar/Wind Helper
0.173
3141813NORNECK
Solar/Wind Helper
0.113
3143873LANEXA
Solar/Wind Helper
0.067
316059AD1-063 C
Solar/Wind Helper
0.112
274760LEE CO EC;1U
Adder
4.35
274767LEE CO EC;8U
Adder
4.299
24721905FLATG4
Adder
9.459
972236AH1-702 GEN2
Adder
1.02
25194608D.CRK4
Adder
0.756
274682WAUKEGAN ;7U
Adder
8.262
25196608WSDLE5
Adder
3.936
274729ELWOOD EC;1P
Adder
7.487
3147983MERCK5
Solar/Wind Helper
0.107
316192AB2-158 GEN
Solar/Wind Helper
0.985
3147666LOUISA
Solar/Wind Helper
0.583
958121AF2-106 GEN
Solar/Wind Helper
1.048
316336AC2-165 C
Solar/Wind Helper
0.729
316254AC1-120 GEN1
Solar/Wind Helper
0.611
316322AB2-045
Solar/Wind Helper
0.14
3146776BUCKING
Solar/Wind Helper
0.05
238148AE2-230_GEN2
Solar/Wind Helper
0.214
316006AB2-029 C
Solar/Wind Helper
0.058
3142416OLDCHRC
Solar/Wind Helper
0.318
3142416OLDCHRC
Solar/Wind Helper
0.122
316097T157 G90
Solar/Wind Helper
0.556
316045AC1-158 PL2
Solar/Wind Helper
2.111
3143526WINTERP
Solar/Wind Helper
0.609
3143226MDLTHAN
Solar/Wind Helper
0.117
3142543TWELFTH
Solar/Wind Helper
0.011
316337AD2-073 GEN
Solar/Wind Helper
0.172
964211AG1-282 GEN
Solar/Wind Helper
0.152
3141726DUNNSVL
Solar/Wind Helper
0.452
3142433PROV 92
Solar/Wind Helper
0.448
3141766HARMONY
Solar/Wind Helper
0.022
944201AF1-088_MTX
Adder
56.965
957141AF2-008_MTX
Adder
28.482
CPLELTFEXP_CPLE->PJM
CLTF
3.112
CBM West 2LTFEXP_CBM-W2->PJM
CBM
73.214
LAGNLTFEXP_LAGN->PJM
CLTF
11.707
CBM South 2LTFEXP_CBM-S2->PJM
CBM
15.107
TVALTFEXP_TVA->PJM
CLTF
6.219
NYPJM->LTFIMP_NY
CLTF
1.478
LGEELTFEXP_LGEE->PJM
CLTF
3.565
WECLTFEXP_WEC->PJM
CLTF
1.782
AG2-052LTFEXP_AG2-052->PJM
LTF
0.105
AH1-155LTFEXP_AH1-155->PJM
LTF
0.158
CBM West 1LTFEXP_CBM-W1->PJM
CBM
64.396
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.657
MECLTFEXP_MEC->PJM
CLTF
8.32
SIGELTFEXP_SIGE->PJM
CLTF
0.271

Details for 05CLOV17_XFL-05CLOVRD 345.0 kV Ckt 17 line l/o AEP_P1-3_#7421_05CLOVRD 765_14_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05CLOV17_XFL-05CLOVRD 345.0 kV Ckt 17 line
Contingency Name:
AEP_P1-3_#7421_05CLOVRD 765_14_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.66 %
Rating:2320.0 MVA
Rating Type:B
MVA to Mitigate:2474.48
MW Contribution:3.38
Bus #Bus NameTypeMW Contribution
970563AG2-360 GEN
50/50
26.913
24689505VACITY
50/50
3.172
943031AE2-326 GEN
Solar/Wind Harmer
3.913
962751AG1-124 GEN
Solar/Wind Harmer
6.207
960911AF2-382 GEN
Solar/Wind Harmer
4.08
971461AH1-227 GEN
Solar/Wind Harmer
2.688
972103AH1-617 GEN
Solar/Wind Harmer
9.714
270053AF1-130 C
Solar/Wind Harmer
1.017
972273AH1-721 GEN
Adder
50.38
970273AG2-179 GEN
Solar/Wind Harmer
2.497
339250AF1-203 GEN
Solar/Wind Harmer
0.001
971155AH1-034 GEN
Solar/Wind Harmer
4.743
962251AG1-071 GEN
Solar/Wind Harmer
2.526
24686205CER G4
Adder
4.732
24686405CER G5
Adder
4.713
960741AF2-365 GEN
Solar/Wind Harmer
1.981
966571AG1-526 GEN
Solar/Wind Harmer
8.7
970093AG2-073 GEN
Solar/Wind Harmer
3.862
270030AE2-140 GEN
Solar/Wind Harmer
7.67
3429391JKCT 9G
Adder
4.484
972167AH1-666 GEN
Solar/Wind Harmer
2.764
958171AF2-111 GEN
Solar/Wind Harmer
8.53
970243AG2-164 GEN
Solar/Wind Harmer
1.988
970519AG2-331 GEN
Solar/Wind Harmer
8.834
970699AG2-449 GEN
Solar/Wind Harmer
0.849
942481AE2-261 GEN
Solar/Wind Harmer
10.086
276621W2-048 GEN
Solar/Wind Harmer
0.169
276838X2-022 GEN2
Solar/Wind Harmer
0.188
970193AG2-126 GEN
Solar/Wind Harmer
4.996
276668AB2-070 GEN1
Solar/Wind Harmer
0.121
276686W4-005 GEN3
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
1.536
965931AG1-462 GEN
Solar/Wind Harmer
8.444
25196008MFTGT1
Adder
0.634
24728705AND G3
Adder
3.77
24728505AND G1
Adder
1.803
274853TWINGROVE;U1
Solar/Wind Harmer
0.001
965091AG1-374 GEN
Solar/Wind Harmer
9.836
959611AF2-252 GEN
Solar/Wind Harmer
1.093
274878BISHOP HL;2U
Solar/Wind Harmer
0.11
276157O29GEN1
Solar/Wind Harmer
0.529
942111AE2-223 GEN
Solar/Wind Harmer
1.06
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
4.35
274767LEE CO EC;8U
Adder
4.299
24721905FLATG4
Adder
9.459
972236AH1-702 GEN2
Adder
1.02
970571AG2-364 GEN
Solar/Wind Harmer
6.485
959091AF2-200 GEN
Solar/Wind Harmer
6.478
274855GSG-6 ;RU
Solar/Wind Harmer
0.119
274850MENDOTA H;RU
Solar/Wind Harmer
0.038
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.058
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.345
276889AE2-281 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0.118
270356AE2-297 GEN
Solar/Wind Harmer
0.004
276805AD2-038 GEN
Solar/Wind Harmer
0.001
252510AF1-249 C
Solar/Wind Harmer
0.025
25194608D.CRK4
Adder
0.756
274682WAUKEGAN ;7U
Adder
8.262
25196608WSDLE5
Adder
3.936
276694AA1-018 GEN2
Solar/Wind Harmer
0
943121AE2-341 GEN
Solar/Wind Harmer
5.354
943591AF1-030 GEN
Solar/Wind Harmer
3.56
24755605MDL-5G
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.188
276893AG1-478 C
Solar/Wind Harmer
0.126
274729ELWOOD EC;1P
Adder
7.487
276897AD1-100 C
Solar/Wind Harmer
0.004
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
10.359
276806AD2-047 C O1
Solar/Wind Harmer
1.793
970941AG2-585 GEN
Solar/Wind Harmer
3.954
253316AC1-085 GEN3
Solar/Wind Harmer
0.002
253433AC1-085 GEN1
Solar/Wind Harmer
0.001
946181AF1-283 GEN
Solar/Wind Harmer
4.111
270222AC2-111 GEN
Solar/Wind Harmer
1.601
270437AC2-090 C
Solar/Wind Harmer
0.001
247642Z2-115 C
Solar/Wind Harmer
0.001
970289AG2-191 GEN
Solar/Wind Harmer
0.347
970291AG2-192 GEN
Solar/Wind Harmer
0.315
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
958821AF2-173 GEN
Solar/Wind Harmer
4.392
270004AE1-209 GEN
Solar/Wind Harmer
0.68
964401AG1-302 GEN
Solar/Wind Harmer
0
946031AF1-268 GEN
Solar/Wind Harmer
2.971
270535AF1-215 GEN1
Solar/Wind Harmer
0.004
253406AD2-031_GEN
Solar/Wind Harmer
0.232
971191AH1-055 GEN
Solar/Wind Harmer
7.979
3147983MERCK5
Solar/Wind Helper
0.107
316192AB2-158 GEN
Solar/Wind Helper
0.985
3147666LOUISA
Solar/Wind Helper
0.583
958121AF2-106 GEN
Solar/Wind Helper
1.048
316336AC2-165 C
Solar/Wind Helper
0.729
316254AC1-120 GEN1
Solar/Wind Helper
0.611
316322AB2-045
Solar/Wind Helper
0.14
3146776BUCKING
Solar/Wind Helper
0.05
238148AE2-230_GEN2
Solar/Wind Helper
0.214
316006AB2-029 C
Solar/Wind Helper
0.058
3142416OLDCHRC
Solar/Wind Helper
0.318
3142416OLDCHRC
Solar/Wind Helper
0.122
316097T157 G90
Solar/Wind Helper
0.556
316045AC1-158 PL2
Solar/Wind Helper
2.111
3143526WINTERP
Solar/Wind Helper
0.609
3143226MDLTHAN
Solar/Wind Helper
0.117
3142543TWELFTH
Solar/Wind Helper
0.011
316337AD2-073 GEN
Solar/Wind Helper
0.172
964211AG1-282 GEN
Solar/Wind Helper
0.152
3141726DUNNSVL
Solar/Wind Helper
0.452
3142433PROV 92
Solar/Wind Helper
0.448
3141766HARMONY
Solar/Wind Helper
0.022
24735205WLF2G2
50/50
5.209
24728305BUCHG2
Adder
3.631
971687AH1-348 GEN
Solar/Wind Harmer
0.521
971403AH1-188 GEN
Solar/Wind Harmer
6.41
971315AH1-136 GEN
Solar/Wind Harmer
0.889
24723205RIVRG3
Adder
11.619
970273AG2-179 GEN
Solar/Wind Harmer
1.456
270336AE1-100 GEN
Solar/Wind Harmer
0.002
962241AG1-070 GEN
Solar/Wind Harmer
2.203
964901AG1-354 GEN
Solar/Wind Harmer
6.057
24686105CER G3
Adder
4.757
24686505CER G6
Adder
4.751
971821AH1-427 GEN
Solar/Wind Harmer
3.952
3429241JKCT 3G
Adder
6.434
971565AH1-281 GEN
Solar/Wind Harmer
0.752
3429421JKCT 10G
Adder
4.484
958131AF2-107 GEN
Solar/Wind Harmer
2.005
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
339216AC1-074 GEN
Solar/Wind Harmer
0.098
970091AG2-072 GEN
Adder
38.082
945681AF1-233 GEN
Solar/Wind Harmer
6.522
270445AC2-157 GEN2
Solar/Wind Harmer
0.002
970333AG2-219 GEN
Solar/Wind Harmer
2.429
965911AG1-460 GEN
Solar/Wind Harmer
0.675
276615X2-022 GEN
Solar/Wind Harmer
0.035
963831AG1-236 GEN
Solar/Wind Harmer
1.299
24735105WLF2G1
50/50
5.209
24734705WLF1G3
50/50
5.198
24734805WLF1G4
50/50
5.198
24734905WLF1G5
50/50
5.198
966391AG1-508 GEN
Solar/Wind Harmer
0.87
971981AH1-535 GEN
Solar/Wind Harmer
3.673
971313AH1-133 GEN
Solar/Wind Harmer
5.384
970281AG2-184 GEN
Solar/Wind Harmer
10.199
972143AH1-644 GEN
Solar/Wind Harmer
5.262
270399AC1-101 GEN
Solar/Wind Harmer
1.445
270400AC1-102 GEN
Solar/Wind Harmer
1.445
971277AH1-098 GEN
Solar/Wind Harmer
2.312
24728205BUCHG1
Adder
3.631
971225AH1-072 GEN
Solar/Wind Harmer
1.048
971227AH1-073 GEN
Solar/Wind Harmer
1.048
944971AF1-162 GEN
Solar/Wind Harmer
4.505
24723005RIVRG1
Adder
11.619
24723105RIVRG2
Adder
11.619
966021AG1-471 GEN
Solar/Wind Harmer
2.291
971485AH1-239 GEN
Solar/Wind Harmer
3.379
339255AE2-071 GEN
Solar/Wind Harmer
-0.067
964781AG1-341 GEN
Solar/Wind Harmer
4.307
971081AG2-670 GEN
Solar/Wind Harmer
2.998
24685805CER G1
Adder
4.726
24685905CER G2
Adder
4.726
970653AG2-424 GEN
Solar/Wind Harmer
1.862
970653AG2-424 GEN
Solar/Wind Harmer
0.965
960161AF2-307 GEN
Solar/Wind Harmer
2.512
942891AE2-308 GEN
Solar/Wind Harmer
3.8
964571AG1-320 GEN
Solar/Wind Harmer
3.444
971125AH1-004 GEN
Solar/Wind Harmer
1.465
970107AG2-081 GEN
Solar/Wind Harmer
1.099
972043AH1-570 GEN
Solar/Wind Harmer
0.938
972045AH1-571 GEN
Solar/Wind Harmer
0.752
339221AD2-048_GEN
Solar/Wind Harmer
0.002
970235AG2-159 GEN
Solar/Wind Harmer
2.143
970235AG2-159 GEN
Solar/Wind Harmer
1.23
270444AC2-157 GEN1
Solar/Wind Harmer
0.002
971587AH1-292 GEN
Solar/Wind Harmer
2.506
970239AG2-162 GEN
Solar/Wind Harmer
0.849
276916AD2-100_GEN
Solar/Wind Harmer
7.098
276911AD2-131_GEN
Solar/Wind Harmer
0.468
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
945391AF1-204 GEN
Solar/Wind Harmer
3.539
270186AC1-089 GEN
Solar/Wind Harmer
0.002
960611AF2-352 GEN
Solar/Wind Harmer
1.093
276782AC1-033 GEN
Solar/Wind Harmer
0
276741O09 GEN1
Solar/Wind Harmer
0.117
276708O09 GEN2
Solar/Wind Harmer
0.117
972267AH1-718 GEN
Adder
1.953
274851PROVIDENC;RU
Solar/Wind Harmer
0
274849CRESCENT ;1U
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.128
276646AC1-214 GEN2
Solar/Wind Harmer
0.128
276603SUBLETTE C
Solar/Wind Harmer
0
274764LEE CO EC;5U
Adder
4.36
274765LEE CO EC;6U
Adder
4.36
274762LEE CO EC;3U
Adder
4.35
274763LEE CO EC;4U
Adder
4.309
970241AG2-163 GEN
Solar/Wind Harmer
1.902
938861AE1-114 GEN
Solar/Wind Harmer
1.846
274856ECOGROVE ;U1
Solar/Wind Harmer
0.077
276611AD2-172 GEN
Solar/Wind Harmer
0.001
252509AD1-136 GEN
Solar/Wind Harmer
0.016
971341AH1-150 GEN
Solar/Wind Harmer
6.478
971343AH1-151 GEN
Solar/Wind Harmer
6.478
971333AH1-146 GEN
Solar/Wind Harmer
6.465
971335AH1-147 GEN
Solar/Wind Harmer
6.465
962581AG1-107 GEN
Solar/Wind Harmer
0.001
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
942991AE2-321 GEN
Solar/Wind Harmer
3.603
970921AG2-575 GEN
Solar/Wind Harmer
3.218
970921AG2-575 GEN
Solar/Wind Harmer
1.073
274879MINONK ;1U
Solar/Wind Harmer
0.136
966841AG1-555 GEN
Solar/Wind Harmer
0.364
962691AG1-118 GEN
Solar/Wind Harmer
9.647
958491AF2-143 GEN
Solar/Wind Harmer
4.817
252519AF1-045_GEN
Solar/Wind Harmer
2.794
252516AE2-318_GEN
Solar/Wind Harmer
2.478
25183208HLCRTG
Solar/Wind Harmer
0.005
25194408D.CRK1
Adder
3.478
25194508D.CRK3
Adder
0.65
274683WAUKEGAN ;8U
Adder
9.693
274683WAUKEGAN ;8U
Adder
8.17
274696ROCKY RD ;4P
Adder
5.238
274695ROCKY RD ;2P
Adder
5.117
274693ROCKY RD ;1P
Adder
5.067
274697ROCKY RD ;3P
Adder
1.39
971573AH1-285 GEN
Solar/Wind Harmer
0.596
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.433
958481AF2-142 GEN
Solar/Wind Harmer
4.797
24728805RICHG1
Adder
1.728
24728905RICHG2
Adder
1.728
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
274888KELLY CRK;1U
Solar/Wind Harmer
0.186
274887GEN-1.85
Solar/Wind Harmer
0.083
276843GEN-1.7
Solar/Wind Harmer
0.102
958011AF2-095 GEN
Solar/Wind Harmer
4.555
253317AC1-085 GEN4
Solar/Wind Harmer
0.002
24379505HDWTR1G C
Solar/Wind Harmer
0.001
270209AC1-174_GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
971613AH1-306 GEN
Solar/Wind Harmer
1.51
270383AD1-128 GEN
Solar/Wind Harmer
0.002
960441AF2-335 GEN
Solar/Wind Harmer
3.136
970825AG2-519 GEN
Solar/Wind Harmer
3.475
253394AE2-221_GEN
Solar/Wind Harmer
0.004
253398AE2-221_GEN2
Solar/Wind Harmer
0.004
270599AE1-208 GEN
Solar/Wind Harmer
2.851
270031AE2-169
Solar/Wind Harmer
1.71
3132123MT JACKSON
Solar/Wind Helper
0.746
315821AE2-092 GEN
Solar/Wind Helper
1.824
966001AG1-469 GEN
Solar/Wind Helper
0.172
315651AD1-115 GEN
Solar/Wind Helper
0.441
3146776BUCKING
Solar/Wind Helper
0.504
3146776BUCKING
Solar/Wind Helper
0.041
966871AG1-558 GEN
Solar/Wind Helper
0.167
316468AD1-105 GEN
Solar/Wind Helper
0.61
316447AC1-158 HLD
Solar/Wind Helper
1.451
316075AC2-137 C
Solar/Wind Helper
0.179
3143526WINTERP
Solar/Wind Helper
0.609
3142946ENON
Solar/Wind Helper
0.011
316077AC2-138 C
Solar/Wind Helper
0.106
316487AF1-042 GEN
Solar/Wind Helper
0.113
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
965401AG1-405 GEN
Solar/Wind Harmer
2.362
965411AG1-406 GEN
Solar/Wind Harmer
1.519
972203AH1-686 GEN
Adder
1.34
339211AE2-254 GEN
Solar/Wind Harmer
0.002
970455AG2-298 GEN
Solar/Wind Harmer
2.533
3429211JKCT 2G
Adder
6.351
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
972163AH1-664 GEN
Solar/Wind Harmer
3.866
972165AH1-665 GEN
Solar/Wind Harmer
3.096
944221AF1-090 GEN
Solar/Wind Harmer
1.996
276849AB2-070 GEN2
Solar/Wind Harmer
0.121
276848AB2-070 GEN3
Solar/Wind Harmer
0.121
276785W4-005 GEN1
Solar/Wind Harmer
0
276174W4-005 GEN2
Solar/Wind Harmer
0
946321AF1-296 GEN
Solar/Wind Harmer
1.851
25196108MFTGT2
Adder
0.722
25196108MFTGT2
Adder
0.67
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
961011AF2-392 GEN
Solar/Wind Harmer
1.918
957751AF2-069 GEN
Solar/Wind Harmer
0.108
276655WTG1_EQ
Solar/Wind Harmer
0.001
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.426
941731AE2-173 GEN
Solar/Wind Harmer
2.719
971681AH1-341 GEN
Solar/Wind Harmer
5.244
270367AC2-061_GEN
Solar/Wind Harmer
0.003
276612AE2-035 GEN
Solar/Wind Harmer
0.001
274823ROCKFORD ;21
Adder
9.057
926823AC1-168 GEN
Solar/Wind Harmer
0.551
963841AG1-237 GEN
Solar/Wind Harmer
1.404
971171AH1-044 GEN
Solar/Wind Harmer
6.478
970169AG2-114 GEN
Solar/Wind Harmer
3.233
971675AH1-338 GEN
Solar/Wind Harmer
1.26
971411AH1-196 GEN
Solar/Wind Harmer
4.847
971177AH1-047 GEN
Solar/Wind Harmer
1.99
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
276868AE1-113 GEN
Solar/Wind Harmer
0.646
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
24387005FR-3G C
Solar/Wind Harmer
0.001
276882AE2-255 GEN
Solar/Wind Harmer
0.376
252524AE2-267 GEN
Solar/Wind Harmer
0.001
25196408WSDLE3
Adder
4.052
25196308WSDLE2
Adder
4.017
25196208WSDLE1
Adder
4.006
25196708WSDLE6
Adder
3.996
25196508WSDLE4
Adder
3.896
274746AC1-111 G10
Adder
2.558
274744AC1-111 GEN8
Adder
2.558
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0
270181AB1-006 GEN2
Solar/Wind Harmer
0
970833AG2-524 GEN
Solar/Wind Harmer
3.501
970833AG2-524 GEN
Solar/Wind Harmer
2.334
274731ELWOOD EC;2P
Adder
7.487
274733ELWOOD EC;3P
Adder
6.938
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0
960591AF2-350 GEN
Solar/Wind Harmer
3.163
270240V3-007_GEN2
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
1.877
970289AG2-191 GEN
Solar/Wind Harmer
0.599
971985AH1-537 GEN
Solar/Wind Harmer
0.937
270594AE1-207 GEN
Solar/Wind Harmer
3.524
958391AF2-133 GEN
Solar/Wind Harmer
0
970115AG2-085 GEN
Solar/Wind Harmer
1.255
270536AF1-215 GEN2
Solar/Wind Harmer
0.004
971609AH1-304 GEN
Solar/Wind Harmer
0.508
971673AH1-337 GEN
Solar/Wind Harmer
2.018
3148463FAIRFLD
Solar/Wind Helper
0.398
3148133STUARTS
Solar/Wind Helper
0.172
3148013FISHERV
Solar/Wind Helper
0.165
3138266HYDRAULIC
Solar/Wind Helper
0.011
3138266HYDRAULIC
Solar/Wind Helper
0.007
316164AC1-076 GEN
Solar/Wind Helper
0.618
23546401DTGZ2-030
Solar/Wind Helper
0.04
238152AF2-075_GEN
Solar/Wind Helper
0.304
316312AB1-027
Solar/Wind Helper
0.233
316233AE1-074 FULL
Solar/Wind Helper
0.179
3141426STAFORD
Solar/Wind Helper
0.025
316223AC1-118
Solar/Wind Helper
0.173
3141813NORNECK
Solar/Wind Helper
0.113
3143873LANEXA
Solar/Wind Helper
0.067
316059AD1-063 C
Solar/Wind Helper
0.112
971029AG2-637 GEN
Solar/Wind Harmer
4.547
274880W4-005 GEN4
Solar/Wind Harmer
0
972175AH1-670 GEN
Solar/Wind Harmer
2.731
25196008MFTGT1
Adder
0.655
24728605AND G2
Adder
1.803
274854TWINGROVE;U2
Solar/Wind Harmer
0.001
274877BISHOP HL;1U
Solar/Wind Harmer
0.11
276158O29GEN2
Solar/Wind Harmer
0
25196808ZIMRHP
Adder
35.531
276726Z2-087_GEN
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
4.568
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
4.35
274766LEE CO EC;7U
Adder
4.299
963741AG1-226 GEN
Solar/Wind Harmer
7.717
24721705FLATG2
Adder
9.459
971475AH1-234 GEN
Solar/Wind Harmer
1.579
970819AG2-516 GEN
Solar/Wind Harmer
3.899
972235AH1-702 GEN1
Adder
1.172
274822ROCKFORD ;11
Adder
9.123
970569AG2-363 GEN
Solar/Wind Harmer
9.728
252507AC2-088 GEN
Solar/Wind Harmer
0.147
957471AF2-041 GEN
Solar/Wind Harmer
9.717
959081AF2-199 GEN
Solar/Wind Harmer
3.239
971067AG2-660 GEN
Solar/Wind Harmer
1.08
276861AD2-134 GEN
Solar/Wind Harmer
0.058
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
274872LEEDK;1U
Solar/Wind Harmer
0.002
971997AH1-543 GEN
Solar/Wind Harmer
1.69
962781AG1-127 GEN
Solar/Wind Harmer
3.063
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.001
276901AD2-066 C O1
Solar/Wind Harmer
0.003
970773AG2-487 GEN
Solar/Wind Harmer
0.568
25194608D.CRK4
Adder
0.756
274828WAUKEGAN ;BP
Adder
5.081
274682WAUKEGAN ;7U
Adder
8.262
939401AE1-172 GEN
Solar/Wind Harmer
2.398
276691AA1-018 GEN1
Solar/Wind Harmer
0.387
274745AC1-111 GEN9
Adder
2.558
24791305MDL-5G
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
3.539
276776AD2-060 GEN
Solar/Wind Harmer
0.33
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
3.162
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
2.313
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
3.94
970291AG2-192 GEN
Solar/Wind Harmer
0.41
276164X3-005 C
Solar/Wind Harmer
0
270032AE2-172
Solar/Wind Harmer
2.098
270005AE1-210 C O1
Solar/Wind Harmer
0.68
965031AG1-367 GEN
Solar/Wind Harmer
3.137
970825AG2-519 GEN
Solar/Wind Harmer
1.113
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.07
958381AF2-132 GEN
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0.002
315616AA1-038_C
Solar/Wind Helper
1.807
3148013FISHERV
Solar/Wind Helper
0.286
316499AE2-029_GEN
Solar/Wind Helper
0.937
3132273ORANGE
Solar/Wind Helper
0.03
3147666LOUISA
Solar/Wind Helper
0.335
237061AD1-155 GEN
Solar/Wind Helper
0.025
316170AC1-121 GEN2
Solar/Wind Helper
0.204
316313AB2-026
Solar/Wind Helper
0.2
316258AE1-075 C
Solar/Wind Helper
0.18
316405AF2-144 C
Solar/Wind Helper
0.15
3146776BUCKING
Solar/Wind Helper
0.045
966881AG1-559 GEN
Solar/Wind Helper
0.168
316473AC1-191 GEN
Solar/Wind Helper
0.759
23583801GRNGAP
Solar/Wind Helper
2.125
238147AE2-230_GEN1
Solar/Wind Helper
0.213
238149AF1-291A_GEN
Solar/Wind Helper
0.061
316095T157 G97
Solar/Wind Helper
0.556
316044AC1-158 PL1
Solar/Wind Helper
0.659
316450AC1-158 RIC
Solar/Wind Helper
0.176
3141906WESTMOR
Solar/Wind Helper
0.046
3142946ENON
Solar/Wind Helper
0.038
3141196NOKESVL
Solar/Wind Helper
0.452
316404AE1-155 C
Solar/Wind Helper
0.945
316484AD2-074 GEN
Solar/Wind Helper
0.215
944201AF1-088_MTX
Adder
56.965
957141AF2-008_MTX
Adder
28.482
CPLELTFEXP_CPLE->PJM
CLTF
3.112
CBM West 2LTFEXP_CBM-W2->PJM
CBM
73.214
LAGNLTFEXP_LAGN->PJM
CLTF
11.707
CBM South 2LTFEXP_CBM-S2->PJM
CBM
15.107
TVALTFEXP_TVA->PJM
CLTF
6.219
NYPJM->LTFIMP_NY
CLTF
1.478
LGEELTFEXP_LGEE->PJM
CLTF
3.565
WECLTFEXP_WEC->PJM
CLTF
1.782
AG2-052LTFEXP_AG2-052->PJM
LTF
0.105
AH1-155LTFEXP_AH1-155->PJM
LTF
0.158
CBM West 1LTFEXP_CBM-W1->PJM
CBM
64.396
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.657
MECLTFEXP_MEC->PJM
CLTF
8.32
SIGELTFEXP_SIGE->PJM
CLTF
0.271

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AP_P1-3_MP-765-501T_SRT-A


Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-501T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:121.06 %
Rating:3393.4 MVA
Rating Type:B
MVA to Mitigate:4107.97
MW Contribution:5.93
Bus #Bus NameTypeMW Contribution
24290605CLAY-1
50/50
0.255
24290605CLAY-1
50/50
0.255
24290705CLAY-2
50/50
0.255
24290705CLAY-2
50/50
0.255
24684405SMG2
50/50
2.224
24684505SMG3
50/50
1.376
24684305SMG1
50/50
0.806
270583AD2-179 GEN
Solar/Wind Harmer
14.457
971277AH1-098 GEN
Solar/Wind Harmer
5.177
316217AC1-145 GEN
Solar/Wind Harmer
0.003
316197AC1-042 GEN
Solar/Wind Harmer
0.002
942671AE2-283 GEN
Solar/Wind Harmer
5.796
24728205BUCHG1
Adder
6.75
270013AE1-250 PV
Solar/Wind Harmer
0.006
971225AH1-072 GEN
Solar/Wind Harmer
1.905
971227AH1-073 GEN
Solar/Wind Harmer
1.905
944971AF1-162 GEN
Solar/Wind Harmer
9.068
24723005RIVRG1
Adder
22.954
24723105RIVRG2
Adder
22.954
24685805CER G1
Adder
9.822
24685905CER G2
Adder
9.822
942751AE2-291 GEN
Solar/Wind Harmer
7.887
966021AG1-471 GEN
Solar/Wind Harmer
4.013
971485AH1-239 GEN
Solar/Wind Harmer
5.928
960161AF2-307 GEN
Solar/Wind Harmer
4.775
339255AE2-071 GEN
Solar/Wind Harmer
-0.119
964781AG1-341 GEN
Solar/Wind Harmer
7.653
971081AG2-670 GEN
Solar/Wind Harmer
5.396
942891AE2-308 GEN
Solar/Wind Harmer
7.099
970653AG2-424 GEN
Solar/Wind Harmer
3.405
970653AG2-424 GEN
Solar/Wind Harmer
1.764
964571AG1-320 GEN
Solar/Wind Harmer
6.361
971125AH1-004 GEN
Solar/Wind Harmer
2.777
970107AG2-081 GEN
Solar/Wind Harmer
2.083
972043AH1-570 GEN
Solar/Wind Harmer
1.796
972045AH1-571 GEN
Solar/Wind Harmer
1.439
339221AD2-048_GEN
Solar/Wind Harmer
0.004
970235AG2-159 GEN
Solar/Wind Harmer
4.126
970235AG2-159 GEN
Solar/Wind Harmer
2.367
270186AC1-089 GEN
Solar/Wind Harmer
0.004
970239AG2-162 GEN
Solar/Wind Harmer
1.663
962581AG1-107 GEN
Solar/Wind Harmer
0.001
270444AC2-157 GEN1
Solar/Wind Harmer
0.003
971587AH1-292 GEN
Solar/Wind Harmer
4.8
252509AD1-136 GEN
Solar/Wind Harmer
0.033
25183208HLCRTG
Solar/Wind Harmer
0.01
252519AF1-045_GEN
Solar/Wind Harmer
5.589
252516AE2-318_GEN
Solar/Wind Harmer
4.958
25194408D.CRK1
Adder
6.938
25194508D.CRK3
Adder
1.297
971073AG2-665 GEN
Solar/Wind Harmer
5.761
945391AF1-204 GEN
Solar/Wind Harmer
6.765
276916AD2-100_GEN
Solar/Wind Harmer
13.364
276911AD2-131_GEN
Solar/Wind Harmer
0.88
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
970241AG2-163 GEN
Solar/Wind Harmer
3.651
24728805RICHG1
Adder
3.384
24728905RICHG2
Adder
3.384
253394AE2-221_GEN
Solar/Wind Harmer
0.008
253398AE2-221_GEN2
Solar/Wind Harmer
0.008
960251AF2-316 GEN
Solar/Wind Harmer
8.583
960201AF2-311 GEN
Solar/Wind Harmer
5.708
970823AG2-518 GEN
50/50
8.384
247619Y1-049
50/50
0.913
24684705SMG5
50/50
0.856
970481AG2-311 GEN
50/50
11.937
24728405LEESVG
50/50
0.295
24416005BYLLESBY
50/50
0.031
3151561HALLBR1
50/50
0.57
970563AG2-360 GEN
50/50
45.829
962751AG1-124 GEN
Solar/Wind Harmer
12.893
958121AF2-106 GEN
Solar/Wind Harmer
0.001
270173AC1-122 GEN
Solar/Wind Harmer
0.677
971331AH1-145 GEN
Solar/Wind Harmer
18.361
943031AE2-326 GEN
Solar/Wind Harmer
6.784
3147312GRETNA
Solar/Wind Harmer
0.186
3146802CHATHAM
Solar/Wind Harmer
0.175
941801AE2-185 GEN
Solar/Wind Harmer
7.452
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
3147123OTTER R
Solar/Wind Harmer
0.13
270346AE1-212 GEN
Solar/Wind Harmer
9.542
270030AE2-140 GEN
Solar/Wind Harmer
21.578
960911AF2-382 GEN
Solar/Wind Harmer
7.638
270016AE1-250 BESS
Solar/Wind Harmer
0.006
970913AG2-568 GEN
Solar/Wind Harmer
7.677
971461AH1-227 GEN
Solar/Wind Harmer
4.886
970223AG2-152 GEN
Solar/Wind Harmer
12.358
270053AF1-130 C
Solar/Wind Harmer
2.047
972103AH1-617 GEN
Solar/Wind Harmer
18.024
24686205CER G4
Adder
9.835
24686405CER G5
Adder
9.796
972273AH1-721 GEN
Adder
89.316
24721905FLATG4
Adder
21.686
970273AG2-179 GEN
Solar/Wind Harmer
4.425
339250AF1-203 GEN
Solar/Wind Harmer
0.001
971155AH1-034 GEN
Solar/Wind Harmer
8.427
962251AG1-071 GEN
Solar/Wind Harmer
4.496
966571AG1-526 GEN
Solar/Wind Harmer
15.967
970093AG2-073 GEN
Solar/Wind Harmer
7.166
960741AF2-365 GEN
Solar/Wind Harmer
3.563
3429391JKCT 9G
Adder
8.402
971191AH1-055 GEN
Solar/Wind Harmer
18.055
972167AH1-666 GEN
Solar/Wind Harmer
5.419
958171AF2-111 GEN
Solar/Wind Harmer
16.681
970243AG2-164 GEN
Solar/Wind Harmer
3.891
970519AG2-331 GEN
Solar/Wind Harmer
17.292
970699AG2-449 GEN
Solar/Wind Harmer
1.663
25196008MFTGT1
Adder
1.252
252510AF1-249 C
Solar/Wind Harmer
0.05
25194608D.CRK4
Adder
1.508
25196608WSDLE5
Adder
7.849
970193AG2-126 GEN
Solar/Wind Harmer
9.55
942481AE2-261 GEN
Solar/Wind Harmer
18.997
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
8.231
24728705AND G3
Adder
7.277
24728505AND G1
Adder
3.48
276621W2-048 GEN
Solar/Wind Harmer
0.318
276838X2-022 GEN2
Solar/Wind Harmer
0.355
276686W4-005 GEN3
Solar/Wind Harmer
0.001
276668AB2-070 GEN1
Solar/Wind Harmer
0.229
971993AH1-541 GEN
Solar/Wind Harmer
2.905
270356AE2-297 GEN
Solar/Wind Harmer
0.008
253406AD2-031_GEN
Solar/Wind Harmer
0.467
270222AC2-111 GEN
Solar/Wind Harmer
3.158
965931AG1-462 GEN
Solar/Wind Harmer
15.879
270291AC1-194 GEN
Solar/Wind Harmer
4.924
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
965091AG1-374 GEN
Solar/Wind Harmer
18.654
959611AF2-252 GEN
Solar/Wind Harmer
2.073
942111AE2-223 GEN
Solar/Wind Harmer
2.013
274878BISHOP HL;2U
Solar/Wind Harmer
0.208
276157O29GEN1
Solar/Wind Harmer
0.999
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
8.222
274767LEE CO EC;8U
Adder
8.125
270437AC2-090 C
Solar/Wind Harmer
0.003
970571AG2-364 GEN
Solar/Wind Harmer
12.296
253415AE1-040 GEN
Solar/Wind Harmer
0.002
972236AH1-702 GEN2
Adder
1.93
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.144
959091AF2-200 GEN
Solar/Wind Harmer
12.273
960611AF2-352 GEN
Solar/Wind Harmer
2.073
966841AG1-555 GEN
Solar/Wind Harmer
0.701
276782AC1-033 GEN
Solar/Wind Harmer
0.001
276741O09 GEN1
Solar/Wind Harmer
0.22
276708O09 GEN2
Solar/Wind Harmer
0.22
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.243
276646AC1-214 GEN2
Solar/Wind Harmer
0.243
972267AH1-718 GEN
Adder
3.688
276603SUBLETTE C
Solar/Wind Harmer
0
274764LEE CO EC;5U
Adder
8.241
274765LEE CO EC;6U
Adder
8.241
274762LEE CO EC;3U
Adder
8.222
274763LEE CO EC;4U
Adder
8.144
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
938861AE1-114 GEN
Solar/Wind Harmer
3.491
274856ECOGROVE ;U1
Solar/Wind Harmer
0.145
276611AD2-172 GEN
Solar/Wind Harmer
0.002
270383AD1-128 GEN
Solar/Wind Harmer
0.004
971341AH1-150 GEN
Solar/Wind Harmer
12.273
971343AH1-151 GEN
Solar/Wind Harmer
12.273
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
971333AH1-146 GEN
Solar/Wind Harmer
12.256
971335AH1-147 GEN
Solar/Wind Harmer
12.256
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
942991AE2-321 GEN
Solar/Wind Harmer
6.834
971613AH1-306 GEN
Solar/Wind Harmer
2.937
274879MINONK ;1U
Solar/Wind Harmer
0.258
970921AG2-575 GEN
Solar/Wind Harmer
6.111
970921AG2-575 GEN
Solar/Wind Harmer
2.037
962691AG1-118 GEN
Solar/Wind Harmer
18.322
958491AF2-143 GEN
Solar/Wind Harmer
9.158
960441AF2-335 GEN
Solar/Wind Harmer
6.106
970825AG2-519 GEN
Solar/Wind Harmer
6.767
274683WAUKEGAN ;8U
Adder
18.419
274683WAUKEGAN ;8U
Adder
15.526
274696ROCKY RD ;4P
Adder
9.957
274695ROCKY RD ;2P
Adder
9.727
274693ROCKY RD ;1P
Adder
9.632
274697ROCKY RD ;3P
Adder
2.642
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.824
958481AF2-142 GEN
Solar/Wind Harmer
9.131
971573AH1-285 GEN
Solar/Wind Harmer
1.134
3132123MT JACKSON
Solar/Wind Helper
1.389
315821AE2-092 GEN
Solar/Wind Helper
3.216
966001AG1-469 GEN
Solar/Wind Helper
0.32
315651AD1-115 GEN
Solar/Wind Helper
0.837
966871AG1-558 GEN
Solar/Wind Helper
0.306
316447AC1-158 HLD
Solar/Wind Helper
2.766
316468AD1-105 GEN
Solar/Wind Helper
1.124
971543AH1-269 GEN
50/50
12.247
966391AG1-508 GEN
Solar/Wind Harmer
1.993
270069AE2-166 C O1
Solar/Wind Harmer
0.008
971313AH1-133 GEN
Solar/Wind Harmer
10.952
24734705WLF1G3
Adder
8.194
24734805WLF1G4
Adder
8.194
24734905WLF1G5
Adder
8.194
270132AB1-180 C
Adder
0.169
24735105WLF2G1
Adder
8.023
270399AC1-101 GEN
Solar/Wind Harmer
2.892
270400AC1-102 GEN
Solar/Wind Harmer
2.892
941621AE2-160 GEN
Adder
4.285
957241AF2-018 GEN
Solar/Wind Harmer
-0.002
970281AG2-184 GEN
Solar/Wind Harmer
18.925
972143AH1-644 GEN
Solar/Wind Harmer
9.763
971981AH1-535 GEN
Solar/Wind Harmer
5.843
971061AG2-657 GEN
Solar/Wind Harmer
5.368
24477305BRIDGE
Adder
0.419
972203AH1-686 GEN
Adder
2.704
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
965401AG1-405 GEN
Solar/Wind Harmer
4.227
965411AG1-406 GEN
Solar/Wind Harmer
2.719
339211AE2-254 GEN
Solar/Wind Harmer
0.003
3429211JKCT 2G
Adder
11.873
970455AG2-298 GEN
Solar/Wind Harmer
4.677
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
972163AH1-664 GEN
Solar/Wind Harmer
7.568
972165AH1-665 GEN
Solar/Wind Harmer
6.061
971985AH1-537 GEN
Solar/Wind Harmer
2.011
270367AC2-061_GEN
Solar/Wind Harmer
0.005
316123AC1-075 GEN
Solar/Wind Harmer
0.168
970165AG2-112 GEN
Solar/Wind Harmer
0.998
970163AG2-111 GEN
Solar/Wind Harmer
0.952
25196108MFTGT2
Adder
1.425
25196108MFTGT2
Adder
1.324
970879AG2-548 GEN
Solar/Wind Harmer
5.761
944221AF1-090 GEN
Solar/Wind Harmer
3.754
252524AE2-267 GEN
Solar/Wind Harmer
0.002
25196408WSDLE3
Adder
8.08
25196308WSDLE2
Adder
8.01
25196208WSDLE1
Adder
7.99
25196708WSDLE6
Adder
7.97
25196508WSDLE4
Adder
7.769
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.229
276848AB2-070 GEN3
Solar/Wind Harmer
0.228
963841AG1-237 GEN
Solar/Wind Harmer
2.698
946321AF1-296 GEN
Solar/Wind Harmer
3.483
270340AC2-060 GEN
Solar/Wind Harmer
0.007
276655WTG1_EQ
Solar/Wind Harmer
0.002
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
6.505
941731AE2-173 GEN
Solar/Wind Harmer
5.162
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
957751AF2-069 GEN
Solar/Wind Harmer
0.204
961011AF2-392 GEN
Solar/Wind Harmer
3.623
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
270240V3-007_GEN2
Solar/Wind Harmer
0.002
971681AH1-341 GEN
Solar/Wind Harmer
9.917
276612AE2-035 GEN
Solar/Wind Harmer
0.002
926823AC1-168 GEN
Solar/Wind Harmer
1.045
970169AG2-114 GEN
Solar/Wind Harmer
6.149
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
970479AG2-310 GEN
50/50
20.255
270205AE1-176
50/50
0.006
24288905REUSENS
50/50
0.057
24684605SMG4
50/50
2.239
966251AG1-494 GEN
50/50
4.388
24728405LEESVG
50/50
0.297
24415905BUCK
50/50
0.034
971367AH1-164 GEN
Solar/Wind Harmer
4.886
971329AH1-144 GEN
Solar/Wind Harmer
11.568
3147312GRETNA
Solar/Wind Harmer
0.047
941821AE2-187 GEN
Solar/Wind Harmer
7.452
270197AD1-017 GEN1
Solar/Wind Harmer
1.429
270336AE1-100 GEN
Solar/Wind Harmer
0.006
943811AF1-049 GEN
Solar/Wind Harmer
-0.002
24728305BUCHG2
Adder
6.75
270018AE2-047 C O1
Solar/Wind Harmer
0.004
958131AF2-107 GEN
Solar/Wind Harmer
5.339
24735205WLF2G2
Adder
8.023
971687AH1-348 GEN
Solar/Wind Harmer
0.948
971403AH1-188 GEN
Solar/Wind Harmer
13.153
24723205RIVRG3
Adder
22.954
971315AH1-136 GEN
Solar/Wind Harmer
1.695
24686105CER G3
Adder
9.887
24686505CER G6
Adder
9.874
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
24721705FLATG2
Adder
21.686
970947AG2-589 GEN
Solar/Wind Harmer
0.249
970273AG2-179 GEN
Solar/Wind Harmer
2.581
971821AH1-427 GEN
Solar/Wind Harmer
7.218
964901AG1-354 GEN
Solar/Wind Harmer
10.814
962241AG1-070 GEN
Solar/Wind Harmer
3.92
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
3429241JKCT 3G
Adder
12.029
3429421JKCT 10G
Adder
8.402
971565AH1-281 GEN
Solar/Wind Harmer
1.396
339216AC1-074 GEN
Solar/Wind Harmer
0.187
945681AF1-233 GEN
Solar/Wind Harmer
12.782
927014AC1-188 GEN
Solar/Wind Harmer
0.004
970091AG2-072 GEN
Adder
74.012
970333AG2-219 GEN
Solar/Wind Harmer
4.755
270445AC2-157 GEN2
Solar/Wind Harmer
0.003
25196808ZIMRHP
Adder
70.616
252507AC2-088 GEN
Solar/Wind Harmer
0.295
25196008MFTGT1
Adder
1.293
25194608D.CRK4
Adder
1.508
965911AG1-460 GEN
Solar/Wind Harmer
1.271
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.331
24728605AND G2
Adder
3.48
276615X2-022 GEN
Solar/Wind Harmer
0.066
963831AG1-236 GEN
Solar/Wind Harmer
2.455
274880W4-005 GEN4
Solar/Wind Harmer
0.001
970773AG2-487 GEN
Solar/Wind Harmer
1.107
963741AG1-226 GEN
Solar/Wind Harmer
14.811
972175AH1-670 GEN
Solar/Wind Harmer
5.171
274854TWINGROVE;U2
Solar/Wind Harmer
0.003
276726Z2-087_GEN
Solar/Wind Harmer
0.002
939741AE1-205 GEN
Solar/Wind Harmer
8.673
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.002
274877BISHOP HL;1U
Solar/Wind Harmer
0.208
276158O29GEN2
Solar/Wind Harmer
0.001
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
8.222
274766LEE CO EC;7U
Adder
8.125
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.519
276903AD2-071 C
Solar/Wind Harmer
6.874
971475AH1-234 GEN
Solar/Wind Harmer
2.986
970819AG2-516 GEN
Solar/Wind Harmer
7.379
970569AG2-363 GEN
Solar/Wind Harmer
18.444
972235AH1-702 GEN1
Adder
2.22
24791305MDL-5G
Solar/Wind Harmer
0.001
274822ROCKFORD ;11
Adder
17.275
957471AF2-041 GEN
Solar/Wind Harmer
18.409
959081AF2-199 GEN
Solar/Wind Harmer
6.136
971067AG2-660 GEN
Solar/Wind Harmer
2.045
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
276861AD2-134 GEN
Solar/Wind Harmer
0.11
970291AG2-192 GEN
Solar/Wind Harmer
0.796
971997AH1-543 GEN
Solar/Wind Harmer
3.211
270032AE2-172
Solar/Wind Harmer
4.079
270263AC1-001 GEN
Solar/Wind Harmer
0.614
274872LEEDK;1U
Solar/Wind Harmer
0.004
270005AE1-210 C O1
Solar/Wind Harmer
1.324
965031AG1-367 GEN
Solar/Wind Harmer
6.111
962781AG1-127 GEN
Solar/Wind Harmer
5.815
276901AD2-066 C O1
Solar/Wind Harmer
0.006
939401AE1-172 GEN
Solar/Wind Harmer
4.568
970825AG2-519 GEN
Solar/Wind Harmer
2.167
274828WAUKEGAN ;BP
Adder
9.655
274682WAUKEGAN ;7U
Adder
15.703
276691AA1-018 GEN1
Solar/Wind Harmer
0.737
274745AC1-111 GEN9
Adder
4.87
315616AA1-038_C
Solar/Wind Helper
3.293
3148013FISHERV
Solar/Wind Helper
0.523
316499AE2-029_GEN
Solar/Wind Helper
1.725
3132273ORANGE
Solar/Wind Helper
0.056
3147666LOUISA
Solar/Wind Helper
0.625
237061AD1-155 GEN
Solar/Wind Helper
0.05
316170AC1-121 GEN2
Solar/Wind Helper
0.386
23583801GRNGAP
Solar/Wind Helper
4.287
316095T157 G97
Solar/Wind Helper
1.125
238147AE2-230_GEN1
Solar/Wind Helper
0.421
238149AF1-291A_GEN
Solar/Wind Helper
0.12
316313AB2-026
Solar/Wind Helper
0.354
316258AE1-075 C
Solar/Wind Helper
0.319
316405AF2-144 C
Solar/Wind Helper
0.265
966881AG1-559 GEN
Solar/Wind Helper
0.313
316473AC1-191 GEN
Solar/Wind Helper
1.387
316044AC1-158 PL1
Solar/Wind Helper
1.257
316450AC1-158 RIC
Solar/Wind Helper
0.335
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274823ROCKFORD ;21
Adder
17.15
971171AH1-044 GEN
Solar/Wind Harmer
12.273
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
971675AH1-338 GEN
Solar/Wind Harmer
2.39
971411AH1-196 GEN
Solar/Wind Harmer
9.19
970289AG2-191 GEN
Solar/Wind Harmer
1.163
971177AH1-047 GEN
Solar/Wind Harmer
3.774
270594AE1-207 GEN
Solar/Wind Harmer
6.853
276868AE1-113 GEN
Solar/Wind Harmer
1.227
276882AE2-255 GEN
Solar/Wind Harmer
0.715
970115AG2-085 GEN
Solar/Wind Harmer
2.442
971673AH1-337 GEN
Solar/Wind Harmer
3.956
274746AC1-111 G10
Adder
4.87
274744AC1-111 GEN8
Adder
4.87
25306009OHH W.
Adder
2.505
3148463FAIRFLD
Solar/Wind Helper
0.726
3148133STUARTS
Solar/Wind Helper
0.313
3148013FISHERV
Solar/Wind Helper
0.3
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
23546401DTGZ2-030
Solar/Wind Helper
0.078
316164AC1-076 GEN
Solar/Wind Helper
1.172
238152AF2-075_GEN
Solar/Wind Helper
0.602
971029AG2-637 GEN
Solar/Wind Harmer
2.803
276889AE2-281 GEN
Solar/Wind Harmer
0.001
274855GSG-6 ;RU
Solar/Wind Harmer
0.225
274850MENDOTA H;RU
Solar/Wind Harmer
0.072
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.11
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.654
247642Z2-115 C
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
0.673
970291AG2-192 GEN
Solar/Wind Harmer
0.612
274872LEEDK;1U
Solar/Wind Harmer
0.224
958821AF2-173 GEN
Solar/Wind Harmer
8.556
270004AE1-209 GEN
Solar/Wind Harmer
1.324
276805AD2-038 GEN
Solar/Wind Harmer
0.002
274682WAUKEGAN ;7U
Adder
15.703
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
946031AF1-268 GEN
Solar/Wind Harmer
5.79
943121AE2-341 GEN
Solar/Wind Harmer
10.192
943591AF1-030 GEN
Solar/Wind Harmer
6.778
274729ELWOOD EC;1P
Adder
13.481
3147983MERCK5
Solar/Wind Helper
0.198
316192AB2-158 GEN
Solar/Wind Helper
1.838
3147666LOUISA
Solar/Wind Helper
1.088
316254AC1-120 GEN1
Solar/Wind Helper
1.159
316097T157 G90
Solar/Wind Helper
1.125
238148AE2-230_GEN2
Solar/Wind Helper
0.423
316336AC2-165 C
Solar/Wind Helper
1.285
316006AB2-029 C
Solar/Wind Helper
0.112
316045AC1-158 PL2
Solar/Wind Helper
4.023
944201AF1-088_MTX
Adder
109.09
957141AF2-008_MTX
Adder
54.545
CPLELTFEXP_CPLE->PJM
CLTF
6.226
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.111
LAGNLTFEXP_LAGN->PJM
CLTF
20.28
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.555
TVALTFEXP_TVA->PJM
CLTF
10.606
NYPJM->LTFIMP_NY
CLTF
3.248
LGEELTFEXP_LGEE->PJM
CLTF
6.763
WECLTFEXP_WEC->PJM
CLTF
3.371
AG2-052LTFEXP_AG2-052->PJM
LTF
0.202
AH1-155LTFEXP_AH1-155->PJM
LTF
0.303
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.415
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.315
MECLTFEXP_MEC->PJM
CLTF
15.415
SIGELTFEXP_SIGE->PJM
CLTF
0.508

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-020_SRT-SL


Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-020_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.02 %
Rating:3610.0 MVA
Rating Type:B
MVA to Mitigate:4224.55
MW Contribution:8.54
Bus #Bus NameTypeMW Contribution
970823AG2-518 GEN
50/50
8.396
247619Y1-049
50/50
0.915
24684705SMG5
50/50
0.857
970481AG2-311 GEN
50/50
11.948
24728405LEESVG
50/50
0.296
24416005BYLLESBY
50/50
0.031
3151561HALLBR1
50/50
0.57
970563AG2-360 GEN
50/50
45.959
962751AG1-124 GEN
Solar/Wind Harmer
18.84
958121AF2-106 GEN
Solar/Wind Harmer
9.423
270173AC1-122 GEN
Solar/Wind Harmer
3.281
971331AH1-145 GEN
Solar/Wind Harmer
18.398
943031AE2-326 GEN
Solar/Wind Harmer
6.798
3147312GRETNA
Solar/Wind Harmer
-0.021
3146802CHATHAM
Solar/Wind Harmer
-0.02
941801AE2-185 GEN
Solar/Wind Harmer
9.82
270574AD1-017 GEN2
Solar/Wind Harmer
8.482
3147123OTTER R
Solar/Wind Harmer
-0.014
270346AE1-212 GEN
Solar/Wind Harmer
13.986
270030AE2-140 GEN
Solar/Wind Harmer
30.98
960911AF2-382 GEN
Solar/Wind Harmer
10.985
270016AE1-250 BESS
Solar/Wind Harmer
3.259
970913AG2-568 GEN
Solar/Wind Harmer
11.054
971461AH1-227 GEN
Solar/Wind Harmer
7.029
970223AG2-152 GEN
Solar/Wind Harmer
17.643
270053AF1-130 C
Solar/Wind Harmer
4.837
972103AH1-617 GEN
Solar/Wind Harmer
25.94
24686205CER G4
Adder
9.888
24686405CER G5
Adder
9.849
972273AH1-721 GEN
Adder
89.748
24721905FLATG4
Adder
21.813
970273AG2-179 GEN
Solar/Wind Harmer
4.143
339250AF1-203 GEN
Solar/Wind Harmer
0.631
971155AH1-034 GEN
Solar/Wind Harmer
10.404
966571AG1-526 GEN
Solar/Wind Harmer
23.009
962251AG1-071 GEN
Solar/Wind Harmer
5.699
970093AG2-073 GEN
Solar/Wind Harmer
10.328
960741AF2-365 GEN
Solar/Wind Harmer
5.133
971191AH1-055 GEN
Solar/Wind Harmer
22.339
3429391JKCT 9G
Adder
8.45
972167AH1-666 GEN
Solar/Wind Harmer
7.817
957541AF2-048 GEN
Solar/Wind Harmer
1.539
958171AF2-111 GEN
Solar/Wind Harmer
24.064
970243AG2-164 GEN
Solar/Wind Harmer
24.738
970519AG2-331 GEN
Solar/Wind Harmer
16.62
970699AG2-449 GEN
Solar/Wind Harmer
10.995
25196008MFTGT1
Adder
1.261
252510AF1-249 C
Solar/Wind Harmer
0.387
25194608D.CRK4
Adder
1.519
25196608WSDLE5
Adder
7.903
970193AG2-126 GEN
Solar/Wind Harmer
13.773
942481AE2-261 GEN
Solar/Wind Harmer
27.393
253316AC1-085 GEN3
Solar/Wind Harmer
7.655
253433AC1-085 GEN1
Solar/Wind Harmer
4.859
946181AF1-283 GEN
Solar/Wind Harmer
11.881
24728705AND G3
Adder
7.324
24728505AND G1
Adder
3.502
276621W2-048 GEN
Solar/Wind Harmer
5.679
276838X2-022 GEN2
Solar/Wind Harmer
0.212
276686W4-005 GEN3
Solar/Wind Harmer
2.743
276668AB2-070 GEN1
Solar/Wind Harmer
2.04
971993AH1-541 GEN
Solar/Wind Harmer
8.379
253406AD2-031_GEN
Solar/Wind Harmer
1.157
270356AE2-297 GEN
Solar/Wind Harmer
4.125
274760LEE CO EC;1U
Adder
8.273
274767LEE CO EC;8U
Adder
8.175
972236AH1-702 GEN2
Adder
1.942
274682WAUKEGAN ;7U
Adder
15.803
253370AE2-315 SEC1
Adder
1.753
253371AE2-315 SEC2
Adder
1.658
274729ELWOOD EC;1P
Adder
1.688
3147983MERCK5
Solar/Wind Helper
0.199
316192AB2-158 GEN
Solar/Wind Helper
1.845
3147666LOUISA
Solar/Wind Helper
1.091
316254AC1-120 GEN1
Solar/Wind Helper
1.164
316097T157 G90
Solar/Wind Helper
1.133
238148AE2-230_GEN2
Solar/Wind Helper
0.425
316336AC2-165 C
Solar/Wind Helper
1.289
316006AB2-029 C
Solar/Wind Helper
0.113
316045AC1-158 PL2
Solar/Wind Helper
4.042
3142416OLDCHRC
Solar/Wind Helper
0.58
3142416OLDCHRC
Solar/Wind Helper
0.222
970479AG2-310 GEN
50/50
20.278
270205AE1-176
50/50
0.006
24288905REUSENS
50/50
0.057
24684605SMG4
50/50
2.241
966251AG1-494 GEN
50/50
4.391
24728405LEESVG
50/50
0.297
24415905BUCK
50/50
0.034
971367AH1-164 GEN
Solar/Wind Harmer
7.012
971329AH1-144 GEN
Solar/Wind Harmer
23.734
3147312GRETNA
Solar/Wind Harmer
-0.005
941821AE2-187 GEN
Solar/Wind Harmer
9.82
270197AD1-017 GEN1
Solar/Wind Harmer
2.549
270336AE1-100 GEN
Solar/Wind Harmer
2.762
943811AF1-049 GEN
Solar/Wind Harmer
5.705
24728305BUCHG2
Adder
6.772
270018AE2-047 C O1
Solar/Wind Harmer
1.828
958131AF2-107 GEN
Solar/Wind Harmer
7.112
24735205WLF2G2
Adder
8.049
971687AH1-348 GEN
Solar/Wind Harmer
1.364
971403AH1-188 GEN
Solar/Wind Harmer
18.932
24723205RIVRG3
Adder
23.068
971315AH1-136 GEN
Solar/Wind Harmer
2.441
24686105CER G3
Adder
9.94
24686505CER G6
Adder
9.927
270331AC1-082 GEN3
Solar/Wind Harmer
0.49
970947AG2-589 GEN
Solar/Wind Harmer
2.153
24721705FLATG2
Adder
21.813
970273AG2-179 GEN
Solar/Wind Harmer
2.594
971821AH1-427 GEN
Solar/Wind Harmer
10.401
964901AG1-354 GEN
Solar/Wind Harmer
15.577
960001AF2-291 GEN
Solar/Wind Harmer
3.136
339241AF1-083 GEN
Solar/Wind Harmer
1.723
962241AG1-070 GEN
Solar/Wind Harmer
4.662
3429241JKCT 3G
Adder
12.097
3429421JKCT 10G
Adder
8.45
971565AH1-281 GEN
Solar/Wind Harmer
2.012
943111AE2-339 GEN
Solar/Wind Harmer
0.888
339216AC1-074 GEN
Solar/Wind Harmer
1.659
945681AF1-233 GEN
Solar/Wind Harmer
18.436
927014AC1-188 GEN
Solar/Wind Harmer
1.543
970091AG2-072 GEN
Adder
74.457
970333AG2-219 GEN
Solar/Wind Harmer
30.235
270445AC2-157 GEN2
Solar/Wind Harmer
5.271
25196808ZIMRHP
Adder
71.09
252507AC2-088 GEN
Solar/Wind Harmer
1.681
25196008MFTGT1
Adder
1.302
25194608D.CRK4
Adder
1.519
965911AG1-460 GEN
Solar/Wind Harmer
1.278
253432AC1-085 GEN2
Solar/Wind Harmer
0.245
946171AF1-282 GEN
Solar/Wind Harmer
9.139
24728605AND G2
Adder
3.502
276615X2-022 GEN
Solar/Wind Harmer
1.783
963831AG1-236 GEN
Solar/Wind Harmer
8.931
274880W4-005 GEN4
Solar/Wind Harmer
2.743
963741AG1-226 GEN
Solar/Wind Harmer
40.621
274761LEE CO EC;2U
Adder
8.273
274766LEE CO EC;7U
Adder
8.175
972235AH1-702 GEN1
Adder
2.234
274822ROCKFORD ;11
Adder
17.383
274828WAUKEGAN ;BP
Adder
9.716
274682WAUKEGAN ;7U
Adder
15.803
274745AC1-111 GEN9
Adder
4.901
253370AE2-315 SEC1
Adder
1.753
253371AE2-315 SEC2
Adder
1.658
315616AA1-038_C
Solar/Wind Helper
3.295
3148013FISHERV
Solar/Wind Helper
0.523
316499AE2-029_GEN
Solar/Wind Helper
1.727
3132273ORANGE
Solar/Wind Helper
0.056
3147666LOUISA
Solar/Wind Helper
0.628
237061AD1-155 GEN
Solar/Wind Helper
0.05
316170AC1-121 GEN2
Solar/Wind Helper
0.388
23583801GRNGAP
Solar/Wind Helper
4.315
316095T157 G97
Solar/Wind Helper
1.133
238147AE2-230_GEN1
Solar/Wind Helper
0.423
238149AF1-291A_GEN
Solar/Wind Helper
0.121
966881AG1-559 GEN
Solar/Wind Helper
0.314
316313AB2-026
Solar/Wind Helper
0.355
316258AE1-075 C
Solar/Wind Helper
0.319
316405AF2-144 C
Solar/Wind Helper
0.266
316044AC1-158 PL1
Solar/Wind Helper
1.263
316450AC1-158 RIC
Solar/Wind Helper
0.337
316473AC1-191 GEN
Solar/Wind Helper
1.391
972175AH1-670 GEN
Solar/Wind Harmer
4.749
24290605CLAY-1
50/50
0.256
24290605CLAY-1
50/50
0.256
24290705CLAY-2
50/50
0.256
24290705CLAY-2
50/50
0.256
24684405SMG2
50/50
2.226
24684505SMG3
50/50
1.377
24684305SMG1
50/50
0.807
270583AD2-179 GEN
Solar/Wind Harmer
20.758
270214AC2-123 GEN
Solar/Wind Harmer
4.319
971277AH1-098 GEN
Solar/Wind Harmer
7.435
316217AC1-145 GEN
Solar/Wind Harmer
4.25
316197AC1-042 GEN
Solar/Wind Harmer
3.222
942671AE2-283 GEN
Solar/Wind Harmer
8.674
24728205BUCHG1
Adder
6.772
270013AE1-250 PV
Solar/Wind Harmer
3.259
971225AH1-072 GEN
Solar/Wind Harmer
2.74
971227AH1-073 GEN
Solar/Wind Harmer
2.74
944971AF1-162 GEN
Solar/Wind Harmer
9.108
24723005RIVRG1
Adder
23.068
24723105RIVRG2
Adder
23.068
24685805CER G1
Adder
9.875
24685905CER G2
Adder
9.875
942751AE2-291 GEN
Solar/Wind Harmer
10.391
966021AG1-471 GEN
Solar/Wind Harmer
5.779
971485AH1-239 GEN
Solar/Wind Harmer
8.537
339231AF1-038_GEN
Solar/Wind Harmer
1.927
960161AF2-307 GEN
Solar/Wind Harmer
6.695
339255AE2-071 GEN
Solar/Wind Harmer
1.104
964781AG1-341 GEN
Solar/Wind Harmer
11.023
339236AF1-050_GEN
Solar/Wind Harmer
1.882
971081AG2-670 GEN
Solar/Wind Harmer
7.773
942891AE2-308 GEN
Solar/Wind Harmer
10.233
970653AG2-424 GEN
Solar/Wind Harmer
4.906
970653AG2-424 GEN
Solar/Wind Harmer
1.774
964571AG1-320 GEN
Solar/Wind Harmer
8.231
971125AH1-004 GEN
Solar/Wind Harmer
4.003
970107AG2-081 GEN
Solar/Wind Harmer
3.003
972043AH1-570 GEN
Solar/Wind Harmer
2.49
972045AH1-571 GEN
Solar/Wind Harmer
1.992
339221AD2-048_GEN
Solar/Wind Harmer
1.523
970235AG2-159 GEN
Solar/Wind Harmer
3.901
970235AG2-159 GEN
Solar/Wind Harmer
2.382
270186AC1-089 GEN
Solar/Wind Harmer
5.863
970239AG2-162 GEN
Solar/Wind Harmer
10.536
962581AG1-107 GEN
Solar/Wind Harmer
4.763
961491AF2-440 GEN
Solar/Wind Harmer
1.98
270444AC2-157 GEN1
Solar/Wind Harmer
5.271
252509AD1-136 GEN
Solar/Wind Harmer
0.24
25183208HLCRTG
Solar/Wind Harmer
5.62
252519AF1-045_GEN
Solar/Wind Harmer
5.628
252516AE2-318_GEN
Solar/Wind Harmer
4.293
970879AG2-548 GEN
Solar/Wind Harmer
5.702
971073AG2-665 GEN
Solar/Wind Harmer
5.702
971073AG2-665 GEN
Solar/Wind Harmer
3.978
25194408D.CRK1
Adder
6.985
25194508D.CRK3
Adder
1.306
945391AF1-204 GEN
Solar/Wind Harmer
12.796
276916AD2-100_GEN
Solar/Wind Harmer
19.269
276911AD2-131_GEN
Solar/Wind Harmer
3.894
957381AF2-032 GEN
Solar/Wind Harmer
0.383
253317AC1-085 GEN4
Solar/Wind Harmer
7.655
276763AC1-053 GEN1
Solar/Wind Harmer
3.59
276764AC1-053 GEN2
Solar/Wind Harmer
3.59
970241AG2-163 GEN
Solar/Wind Harmer
22.567
24728805RICHG1
Adder
3.406
24728905RICHG2
Adder
3.406
972267AH1-718 GEN
Adder
3.711
274764LEE CO EC;5U
Adder
8.292
274765LEE CO EC;6U
Adder
8.292
274762LEE CO EC;3U
Adder
8.273
274763LEE CO EC;4U
Adder
8.195
274683WAUKEGAN ;8U
Adder
18.536
274683WAUKEGAN ;8U
Adder
15.625
274696ROCKY RD ;4P
Adder
10.02
274695ROCKY RD ;2P
Adder
9.789
274693ROCKY RD ;1P
Adder
9.693
274697ROCKY RD ;3P
Adder
2.659
253370AE2-315 SEC1
Adder
1.753
3132123MT JACKSON
Solar/Wind Helper
1.392
315821AE2-092 GEN
Solar/Wind Helper
3.222
966001AG1-469 GEN
Solar/Wind Helper
0.321
315651AD1-115 GEN
Solar/Wind Helper
0.841
316447AC1-158 HLD
Solar/Wind Helper
2.779
966871AG1-558 GEN
Solar/Wind Helper
0.307
316468AD1-105 GEN
Solar/Wind Helper
1.129
971543AH1-269 GEN
50/50
12.267
966391AG1-508 GEN
Solar/Wind Harmer
6.388
270069AE2-166 C O1
Solar/Wind Harmer
4.514
971313AH1-133 GEN
Solar/Wind Harmer
15.745
24734705WLF1G3
Adder
8.22
24734805WLF1G4
Adder
8.22
24734905WLF1G5
Adder
8.22
270132AB1-180 C
Adder
0.169
24735105WLF2G1
Adder
8.049
270399AC1-101 GEN
Solar/Wind Harmer
5.58
270400AC1-102 GEN
Solar/Wind Harmer
5.58
941621AE2-160 GEN
Adder
4.308
957241AF2-018 GEN
Solar/Wind Harmer
5.782
970281AG2-184 GEN
Solar/Wind Harmer
27.237
972143AH1-644 GEN
Solar/Wind Harmer
12.97
971981AH1-535 GEN
Solar/Wind Harmer
12.604
962211AG1-066 GEN
Solar/Wind Harmer
3.014
971061AG2-657 GEN
Solar/Wind Harmer
11.059
24477305BRIDGE
Adder
0.422
972203AH1-686 GEN
Adder
2.718
270330AC1-082 GEN2
Solar/Wind Harmer
0.83
270329AC1-082 GEN1
Solar/Wind Harmer
0.489
965401AG1-405 GEN
Solar/Wind Harmer
6.089
965411AG1-406 GEN
Solar/Wind Harmer
2.733
339211AE2-254 GEN
Solar/Wind Harmer
1.572
3429211JKCT 2G
Adder
11.941
970455AG2-298 GEN
Solar/Wind Harmer
6.067
339243AC2-075 GEN1
Solar/Wind Harmer
0.449
972163AH1-664 GEN
Solar/Wind Harmer
9.805
972165AH1-665 GEN
Solar/Wind Harmer
7.844
971985AH1-537 GEN
Solar/Wind Harmer
17.415
270367AC2-061_GEN
Solar/Wind Harmer
3.029
316123AC1-075 GEN
Solar/Wind Harmer
1.494
970165AG2-112 GEN
Solar/Wind Harmer
1.315
970163AG2-111 GEN
Solar/Wind Harmer
1.255
25196108MFTGT2
Adder
1.435
25196108MFTGT2
Adder
1.332
970879AG2-548 GEN
Solar/Wind Harmer
3.978
944221AF1-090 GEN
Solar/Wind Harmer
10.083
252524AE2-267 GEN
Solar/Wind Harmer
1.454
25196408WSDLE3
Adder
8.135
25196308WSDLE2
Adder
8.064
25196208WSDLE1
Adder
8.044
25196708WSDLE6
Adder
8.024
25196508WSDLE4
Adder
7.822
276785W4-005 GEN1
Solar/Wind Harmer
2.743
276174W4-005 GEN2
Solar/Wind Harmer
2.743
276849AB2-070 GEN2
Solar/Wind Harmer
2.04
276848AB2-070 GEN3
Solar/Wind Harmer
2.04
274823ROCKFORD ;21
Adder
17.257
274746AC1-111 G10
Adder
4.901
274744AC1-111 GEN8
Adder
4.901
25306009OHH W.
Adder
2.523
253372AE2-315 SEC3
Adder
1.658
253372AE2-315 SEC3
Adder
1.658
3148463FAIRFLD
Solar/Wind Helper
0.727
3148133STUARTS
Solar/Wind Helper
0.314
3148013FISHERV
Solar/Wind Helper
0.301
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
23546401DTGZ2-030
Solar/Wind Helper
0.079
316164AC1-076 GEN
Solar/Wind Helper
1.177
238152AF2-075_GEN
Solar/Wind Helper
0.605
316312AB1-027
Solar/Wind Helper
0.425
3141426STAFORD
Solar/Wind Helper
0.049
944201AF1-088_MTX
Adder
109.749
957141AF2-008_MTX
Adder
54.874
CPLELTFEXP_CPLE->PJM
CLTF
6.237
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.77
LAGNLTFEXP_LAGN->PJM
CLTF
20.369
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.617
TVALTFEXP_TVA->PJM
CLTF
10.651
NYPJM->LTFIMP_NY
CLTF
3.272
LGEELTFEXP_LGEE->PJM
CLTF
6.802
WECLTFEXP_WEC->PJM
CLTF
3.393
AG2-052LTFEXP_AG2-052->PJM
LTF
0.203
AH1-155LTFEXP_AH1-155->PJM
LTF
0.304
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.199
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.491
MECLTFEXP_MEC->PJM
CLTF
15.504
SIGELTFEXP_SIGE->PJM
CLTF
0.511

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-021_SRT-SL


Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-021_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.77 %
Rating:3610.0 MVA
Rating Type:B
MVA to Mitigate:4215.43
MW Contribution:8.51
Bus #Bus NameTypeMW Contribution
970823AG2-518 GEN
50/50
8.387
247619Y1-049
50/50
0.914
24684705SMG5
50/50
0.857
970481AG2-311 GEN
50/50
11.94
24728405LEESVG
50/50
0.296
24416005BYLLESBY
50/50
0.031
3151561HALLBR1
50/50
0.57
970563AG2-360 GEN
50/50
45.869
962751AG1-124 GEN
Solar/Wind Harmer
18.829
958121AF2-106 GEN
Solar/Wind Harmer
9.412
270173AC1-122 GEN
Solar/Wind Harmer
3.279
971331AH1-145 GEN
Solar/Wind Harmer
18.373
943031AE2-326 GEN
Solar/Wind Harmer
6.789
3147312GRETNA
Solar/Wind Harmer
-0.021
3146802CHATHAM
Solar/Wind Harmer
-0.02
941801AE2-185 GEN
Solar/Wind Harmer
9.814
270574AD1-017 GEN2
Solar/Wind Harmer
8.476
3147123OTTER R
Solar/Wind Harmer
-0.014
270346AE1-212 GEN
Solar/Wind Harmer
13.951
270030AE2-140 GEN
Solar/Wind Harmer
30.945
960911AF2-382 GEN
Solar/Wind Harmer
10.959
270016AE1-250 BESS
Solar/Wind Harmer
3.257
970913AG2-568 GEN
Solar/Wind Harmer
11.019
971461AH1-227 GEN
Solar/Wind Harmer
7.011
970223AG2-152 GEN
Solar/Wind Harmer
17.629
270053AF1-130 C
Solar/Wind Harmer
4.822
972103AH1-617 GEN
Solar/Wind Harmer
25.867
24686205CER G4
Adder
9.851
24686405CER G5
Adder
9.812
972273AH1-721 GEN
Adder
89.448
24721905FLATG4
Adder
21.725
970273AG2-179 GEN
Solar/Wind Harmer
4.129
339250AF1-203 GEN
Solar/Wind Harmer
0.629
971155AH1-034 GEN
Solar/Wind Harmer
10.369
966571AG1-526 GEN
Solar/Wind Harmer
22.923
962251AG1-071 GEN
Solar/Wind Harmer
5.679
970093AG2-073 GEN
Solar/Wind Harmer
10.289
960741AF2-365 GEN
Solar/Wind Harmer
5.115
3429391JKCT 9G
Adder
8.417
971191AH1-055 GEN
Solar/Wind Harmer
22.23
972167AH1-666 GEN
Solar/Wind Harmer
7.783
957541AF2-048 GEN
Solar/Wind Harmer
1.531
958171AF2-111 GEN
Solar/Wind Harmer
23.957
970243AG2-164 GEN
Solar/Wind Harmer
24.633
970519AG2-331 GEN
Solar/Wind Harmer
16.549
970699AG2-449 GEN
Solar/Wind Harmer
10.948
25196008MFTGT1
Adder
1.255
252510AF1-249 C
Solar/Wind Harmer
0.385
25194608D.CRK4
Adder
1.511
25196608WSDLE5
Adder
7.866
970193AG2-126 GEN
Solar/Wind Harmer
13.715
942481AE2-261 GEN
Solar/Wind Harmer
27.279
253316AC1-085 GEN3
Solar/Wind Harmer
7.618
253433AC1-085 GEN1
Solar/Wind Harmer
4.836
946181AF1-283 GEN
Solar/Wind Harmer
11.823
24728705AND G3
Adder
7.292
24728505AND G1
Adder
3.486
276621W2-048 GEN
Solar/Wind Harmer
5.656
276838X2-022 GEN2
Solar/Wind Harmer
0.211
276668AB2-070 GEN1
Solar/Wind Harmer
2.031
276686W4-005 GEN3
Solar/Wind Harmer
2.731
971993AH1-541 GEN
Solar/Wind Harmer
8.344
270356AE2-297 GEN
Solar/Wind Harmer
4.106
253406AD2-031_GEN
Solar/Wind Harmer
1.151
274760LEE CO EC;1U
Adder
8.237
274767LEE CO EC;8U
Adder
8.14
972236AH1-702 GEN2
Adder
1.934
274682WAUKEGAN ;7U
Adder
15.734
253370AE2-315 SEC1
Adder
1.744
253371AE2-315 SEC2
Adder
1.649
274729ELWOOD EC;1P
Adder
1.681
3147983MERCK5
Solar/Wind Helper
0.198
316192AB2-158 GEN
Solar/Wind Helper
1.84
3147666LOUISA
Solar/Wind Helper
1.089
316254AC1-120 GEN1
Solar/Wind Helper
1.161
316097T157 G90
Solar/Wind Helper
1.128
238148AE2-230_GEN2
Solar/Wind Helper
0.424
316336AC2-165 C
Solar/Wind Helper
1.286
316006AB2-029 C
Solar/Wind Helper
0.113
316045AC1-158 PL2
Solar/Wind Helper
4.029
24290605CLAY-1
50/50
0.255
24290605CLAY-1
50/50
0.255
24290705CLAY-2
50/50
0.255
24290705CLAY-2
50/50
0.255
24684405SMG2
50/50
2.225
24684505SMG3
50/50
1.376
24684305SMG1
50/50
0.806
270583AD2-179 GEN
Solar/Wind Harmer
20.732
270214AC2-123 GEN
Solar/Wind Harmer
4.313
971277AH1-098 GEN
Solar/Wind Harmer
7.425
316217AC1-145 GEN
Solar/Wind Harmer
4.248
316197AC1-042 GEN
Solar/Wind Harmer
3.22
942671AE2-283 GEN
Solar/Wind Harmer
8.669
24728205BUCHG1
Adder
6.757
270013AE1-250 PV
Solar/Wind Harmer
3.257
971225AH1-072 GEN
Solar/Wind Harmer
2.733
971227AH1-073 GEN
Solar/Wind Harmer
2.733
944971AF1-162 GEN
Solar/Wind Harmer
9.08
24723005RIVRG1
Adder
22.989
24723105RIVRG2
Adder
22.989
24685805CER G1
Adder
9.838
24685905CER G2
Adder
9.838
942751AE2-291 GEN
Solar/Wind Harmer
10.387
966021AG1-471 GEN
Solar/Wind Harmer
5.761
971485AH1-239 GEN
Solar/Wind Harmer
8.509
339231AF1-038_GEN
Solar/Wind Harmer
1.921
960161AF2-307 GEN
Solar/Wind Harmer
6.669
339255AE2-071 GEN
Solar/Wind Harmer
1.1
964781AG1-341 GEN
Solar/Wind Harmer
10.986
339236AF1-050_GEN
Solar/Wind Harmer
1.875
971081AG2-670 GEN
Solar/Wind Harmer
7.746
942891AE2-308 GEN
Solar/Wind Harmer
10.193
970653AG2-424 GEN
Solar/Wind Harmer
4.888
970653AG2-424 GEN
Solar/Wind Harmer
1.767
964571AG1-320 GEN
Solar/Wind Harmer
8.199
971125AH1-004 GEN
Solar/Wind Harmer
3.987
970107AG2-081 GEN
Solar/Wind Harmer
2.99
972043AH1-570 GEN
Solar/Wind Harmer
2.479
972045AH1-571 GEN
Solar/Wind Harmer
1.983
339221AD2-048_GEN
Solar/Wind Harmer
1.517
970235AG2-159 GEN
Solar/Wind Harmer
3.885
970235AG2-159 GEN
Solar/Wind Harmer
2.372
270186AC1-089 GEN
Solar/Wind Harmer
5.836
970239AG2-162 GEN
Solar/Wind Harmer
10.492
962581AG1-107 GEN
Solar/Wind Harmer
4.741
961491AF2-440 GEN
Solar/Wind Harmer
1.97
270444AC2-157 GEN1
Solar/Wind Harmer
5.249
252509AD1-136 GEN
Solar/Wind Harmer
0.239
25183208HLCRTG
Solar/Wind Harmer
5.594
252519AF1-045_GEN
Solar/Wind Harmer
5.601
252516AE2-318_GEN
Solar/Wind Harmer
4.272
970879AG2-548 GEN
Solar/Wind Harmer
5.67
971073AG2-665 GEN
Solar/Wind Harmer
5.67
971073AG2-665 GEN
Solar/Wind Harmer
3.956
971543AH1-269 GEN
50/50
12.253
966391AG1-508 GEN
Solar/Wind Harmer
6.379
270069AE2-166 C O1
Solar/Wind Harmer
4.509
971313AH1-133 GEN
Solar/Wind Harmer
15.712
24734705WLF1G3
Adder
8.202
24734805WLF1G4
Adder
8.202
24734905WLF1G5
Adder
8.202
270132AB1-180 C
Adder
0.169
25194408D.CRK1
Adder
6.953
25194508D.CRK3
Adder
1.3
945391AF1-204 GEN
Solar/Wind Harmer
12.742
276916AD2-100_GEN
Solar/Wind Harmer
19.19
276911AD2-131_GEN
Solar/Wind Harmer
3.878
957381AF2-032 GEN
Solar/Wind Harmer
0.382
253317AC1-085 GEN4
Solar/Wind Harmer
7.618
276763AC1-053 GEN1
Solar/Wind Harmer
3.575
276764AC1-053 GEN2
Solar/Wind Harmer
3.575
970241AG2-163 GEN
Solar/Wind Harmer
22.469
24728805RICHG1
Adder
3.391
24728905RICHG2
Adder
3.391
972267AH1-718 GEN
Adder
3.695
274764LEE CO EC;5U
Adder
8.257
274765LEE CO EC;6U
Adder
8.257
274762LEE CO EC;3U
Adder
8.237
274763LEE CO EC;4U
Adder
8.16
274683WAUKEGAN ;8U
Adder
18.455
274683WAUKEGAN ;8U
Adder
15.556
274696ROCKY RD ;4P
Adder
9.976
274695ROCKY RD ;2P
Adder
9.746
274693ROCKY RD ;1P
Adder
9.65
274697ROCKY RD ;3P
Adder
2.648
253370AE2-315 SEC1
Adder
1.744
3132123MT JACKSON
Solar/Wind Helper
1.39
315821AE2-092 GEN
Solar/Wind Helper
3.218
966001AG1-469 GEN
Solar/Wind Helper
0.32
315651AD1-115 GEN
Solar/Wind Helper
0.839
966871AG1-558 GEN
Solar/Wind Helper
0.306
316447AC1-158 HLD
Solar/Wind Helper
2.77
316468AD1-105 GEN
Solar/Wind Helper
1.126
24735105WLF2G1
Adder
8.031
270399AC1-101 GEN
Solar/Wind Harmer
5.563
270400AC1-102 GEN
Solar/Wind Harmer
5.563
941621AE2-160 GEN
Adder
4.292
957241AF2-018 GEN
Solar/Wind Harmer
5.764
970281AG2-184 GEN
Solar/Wind Harmer
27.16
972143AH1-644 GEN
Solar/Wind Harmer
12.933
971981AH1-535 GEN
Solar/Wind Harmer
12.575
962211AG1-066 GEN
Solar/Wind Harmer
3.005
971061AG2-657 GEN
Solar/Wind Harmer
11.012
24477305BRIDGE
Adder
0.42
972203AH1-686 GEN
Adder
2.709
270330AC1-082 GEN2
Solar/Wind Harmer
0.826
270329AC1-082 GEN1
Solar/Wind Harmer
0.486
965401AG1-405 GEN
Solar/Wind Harmer
6.068
965411AG1-406 GEN
Solar/Wind Harmer
2.724
339211AE2-254 GEN
Solar/Wind Harmer
1.566
3429211JKCT 2G
Adder
11.894
970455AG2-298 GEN
Solar/Wind Harmer
6.044
339243AC2-075 GEN1
Solar/Wind Harmer
0.447
972163AH1-664 GEN
Solar/Wind Harmer
9.762
972165AH1-665 GEN
Solar/Wind Harmer
7.81
971985AH1-537 GEN
Solar/Wind Harmer
17.332
270367AC2-061_GEN
Solar/Wind Harmer
3.015
316123AC1-075 GEN
Solar/Wind Harmer
1.493
970165AG2-112 GEN
Solar/Wind Harmer
1.315
970163AG2-111 GEN
Solar/Wind Harmer
1.254
25196108MFTGT2
Adder
1.428
25196108MFTGT2
Adder
1.326
970879AG2-548 GEN
Solar/Wind Harmer
3.956
944221AF1-090 GEN
Solar/Wind Harmer
10.042
252524AE2-267 GEN
Solar/Wind Harmer
1.447
25196408WSDLE3
Adder
8.097
25196308WSDLE2
Adder
8.027
25196208WSDLE1
Adder
8.006
25196708WSDLE6
Adder
7.986
25196508WSDLE4
Adder
7.785
276849AB2-070 GEN2
Solar/Wind Harmer
2.031
276848AB2-070 GEN3
Solar/Wind Harmer
2.031
276785W4-005 GEN1
Solar/Wind Harmer
2.731
276174W4-005 GEN2
Solar/Wind Harmer
2.731
274823ROCKFORD ;21
Adder
17.182
274746AC1-111 G10
Adder
4.879
274744AC1-111 GEN8
Adder
4.879
25306009OHH W.
Adder
2.51
253372AE2-315 SEC3
Adder
1.649
253372AE2-315 SEC3
Adder
1.649
3148463FAIRFLD
Solar/Wind Helper
0.726
3148133STUARTS
Solar/Wind Helper
0.314
3148013FISHERV
Solar/Wind Helper
0.3
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
23546401DTGZ2-030
Solar/Wind Helper
0.079
316164AC1-076 GEN
Solar/Wind Helper
1.173
238152AF2-075_GEN
Solar/Wind Helper
0.603
970479AG2-310 GEN
50/50
20.262
270205AE1-176
50/50
0.006
24288905REUSENS
50/50
0.057
24684605SMG4
50/50
2.239
966251AG1-494 GEN
50/50
4.389
24728405LEESVG
50/50
0.297
24415905BUCK
50/50
0.034
971367AH1-164 GEN
Solar/Wind Harmer
7.006
971329AH1-144 GEN
Solar/Wind Harmer
23.701
3147312GRETNA
Solar/Wind Harmer
-0.005
941821AE2-187 GEN
Solar/Wind Harmer
9.814
270197AD1-017 GEN1
Solar/Wind Harmer
2.547
270336AE1-100 GEN
Solar/Wind Harmer
2.759
943811AF1-049 GEN
Solar/Wind Harmer
5.698
24728305BUCHG2
Adder
6.757
270018AE2-047 C O1
Solar/Wind Harmer
1.826
958131AF2-107 GEN
Solar/Wind Harmer
7.109
24735205WLF2G2
Adder
8.031
971687AH1-348 GEN
Solar/Wind Harmer
1.36
971403AH1-188 GEN
Solar/Wind Harmer
18.877
24723205RIVRG3
Adder
22.989
971315AH1-136 GEN
Solar/Wind Harmer
2.433
24686105CER G3
Adder
9.903
24686505CER G6
Adder
9.89
270331AC1-082 GEN3
Solar/Wind Harmer
0.488
24721705FLATG2
Adder
21.725
970947AG2-589 GEN
Solar/Wind Harmer
2.143
970273AG2-179 GEN
Solar/Wind Harmer
2.585
971821AH1-427 GEN
Solar/Wind Harmer
10.363
964901AG1-354 GEN
Solar/Wind Harmer
15.523
339241AF1-083 GEN
Solar/Wind Harmer
1.717
962241AG1-070 GEN
Solar/Wind Harmer
4.647
960001AF2-291 GEN
Solar/Wind Harmer
3.12
3429241JKCT 3G
Adder
12.05
3429421JKCT 10G
Adder
8.417
971565AH1-281 GEN
Solar/Wind Harmer
2.004
943111AE2-339 GEN
Solar/Wind Harmer
0.884
339216AC1-074 GEN
Solar/Wind Harmer
1.652
945681AF1-233 GEN
Solar/Wind Harmer
18.356
927014AC1-188 GEN
Solar/Wind Harmer
1.535
970091AG2-072 GEN
Adder
74.149
970333AG2-219 GEN
Solar/Wind Harmer
30.107
270445AC2-157 GEN2
Solar/Wind Harmer
5.249
25196808ZIMRHP
Adder
70.761
252507AC2-088 GEN
Solar/Wind Harmer
1.673
25196008MFTGT1
Adder
1.296
25194608D.CRK4
Adder
1.511
965911AG1-460 GEN
Solar/Wind Harmer
1.273
253432AC1-085 GEN2
Solar/Wind Harmer
0.243
946171AF1-282 GEN
Solar/Wind Harmer
9.095
24728605AND G2
Adder
3.486
276615X2-022 GEN
Solar/Wind Harmer
1.776
963831AG1-236 GEN
Solar/Wind Harmer
8.893
274880W4-005 GEN4
Solar/Wind Harmer
2.731
963741AG1-226 GEN
Solar/Wind Harmer
40.444
274761LEE CO EC;2U
Adder
8.237
274766LEE CO EC;7U
Adder
8.14
972235AH1-702 GEN1
Adder
2.224
274822ROCKFORD ;11
Adder
17.308
274828WAUKEGAN ;BP
Adder
9.674
274682WAUKEGAN ;7U
Adder
15.734
274745AC1-111 GEN9
Adder
4.879
253370AE2-315 SEC1
Adder
1.744
253371AE2-315 SEC2
Adder
1.649
315616AA1-038_C
Solar/Wind Helper
3.294
3148013FISHERV
Solar/Wind Helper
0.523
316499AE2-029_GEN
Solar/Wind Helper
1.725
3132273ORANGE
Solar/Wind Helper
0.056
3147666LOUISA
Solar/Wind Helper
0.626
237061AD1-155 GEN
Solar/Wind Helper
0.05
316170AC1-121 GEN2
Solar/Wind Helper
0.387
23583801GRNGAP
Solar/Wind Helper
4.296
316095T157 G97
Solar/Wind Helper
1.128
238147AE2-230_GEN1
Solar/Wind Helper
0.422
238149AF1-291A_GEN
Solar/Wind Helper
0.12
966881AG1-559 GEN
Solar/Wind Helper
0.314
316313AB2-026
Solar/Wind Helper
0.354
316258AE1-075 C
Solar/Wind Helper
0.319
316405AF2-144 C
Solar/Wind Helper
0.266
316473AC1-191 GEN
Solar/Wind Helper
1.388
316044AC1-158 PL1
Solar/Wind Helper
1.259
316450AC1-158 RIC
Solar/Wind Helper
0.336
972175AH1-670 GEN
Solar/Wind Harmer
4.729
944201AF1-088_MTX
Adder
109.291
957141AF2-008_MTX
Adder
54.646
CPLELTFEXP_CPLE->PJM
CLTF
6.229
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.312
LAGNLTFEXP_LAGN->PJM
CLTF
20.308
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.574
TVALTFEXP_TVA->PJM
CLTF
10.62
NYPJM->LTFIMP_NY
CLTF
3.255
LGEELTFEXP_LGEE->PJM
CLTF
6.775
WECLTFEXP_WEC->PJM
CLTF
3.378
AG2-052LTFEXP_AG2-052->PJM
LTF
0.202
AH1-155LTFEXP_AH1-155->PJM
LTF
0.303
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.655
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.369
MECLTFEXP_MEC->PJM
CLTF
15.442
SIGELTFEXP_SIGE->PJM
CLTF
0.509

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AEP_P4_#37_05MOUNTN 765_B1_SRT-A


Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#37_05MOUNTN 765_B1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.68 %
Rating:3610.0 MVA
Rating Type:B
MVA to Mitigate:4211.98
MW Contribution:8.5
Bus #Bus NameTypeMW Contribution
970823AG2-518 GEN
50/50
8.384
247619Y1-049
50/50
0.913
24684705SMG5
50/50
0.856
970481AG2-311 GEN
50/50
11.937
24728405LEESVG
50/50
0.295
24416005BYLLESBY
50/50
0.031
3151561HALLBR1
50/50
0.57
970563AG2-360 GEN
50/50
45.829
962751AG1-124 GEN
Solar/Wind Harmer
18.825
958121AF2-106 GEN
Solar/Wind Harmer
9.407
270173AC1-122 GEN
Solar/Wind Harmer
3.278
971331AH1-145 GEN
Solar/Wind Harmer
18.361
943031AE2-326 GEN
Solar/Wind Harmer
6.784
3147312GRETNA
Solar/Wind Harmer
-0.021
3146802CHATHAM
Solar/Wind Harmer
-0.02
941801AE2-185 GEN
Solar/Wind Harmer
9.812
270574AD1-017 GEN2
Solar/Wind Harmer
8.473
3147123OTTER R
Solar/Wind Harmer
-0.014
270346AE1-212 GEN
Solar/Wind Harmer
13.936
270030AE2-140 GEN
Solar/Wind Harmer
30.929
960911AF2-382 GEN
Solar/Wind Harmer
10.948
270016AE1-250 BESS
Solar/Wind Harmer
3.256
970913AG2-568 GEN
Solar/Wind Harmer
11.004
971461AH1-227 GEN
Solar/Wind Harmer
7.003
970223AG2-152 GEN
Solar/Wind Harmer
17.623
270053AF1-130 C
Solar/Wind Harmer
4.815
972103AH1-617 GEN
Solar/Wind Harmer
25.835
24686205CER G4
Adder
9.835
24686405CER G5
Adder
9.796
972273AH1-721 GEN
Adder
89.316
24721905FLATG4
Adder
21.686
970273AG2-179 GEN
Solar/Wind Harmer
4.123
339250AF1-203 GEN
Solar/Wind Harmer
0.628
971155AH1-034 GEN
Solar/Wind Harmer
10.354
962251AG1-071 GEN
Solar/Wind Harmer
5.671
966571AG1-526 GEN
Solar/Wind Harmer
22.886
970093AG2-073 GEN
Solar/Wind Harmer
10.271
960741AF2-365 GEN
Solar/Wind Harmer
5.107
3429391JKCT 9G
Adder
8.402
971191AH1-055 GEN
Solar/Wind Harmer
22.182
972167AH1-666 GEN
Solar/Wind Harmer
7.768
957541AF2-048 GEN
Solar/Wind Harmer
1.528
958171AF2-111 GEN
Solar/Wind Harmer
23.91
970243AG2-164 GEN
Solar/Wind Harmer
24.587
970519AG2-331 GEN
Solar/Wind Harmer
16.518
970699AG2-449 GEN
Solar/Wind Harmer
10.927
25196008MFTGT1
Adder
1.252
252510AF1-249 C
Solar/Wind Harmer
0.384
25194608D.CRK4
Adder
1.508
25196608WSDLE5
Adder
7.849
970193AG2-126 GEN
Solar/Wind Harmer
13.689
942481AE2-261 GEN
Solar/Wind Harmer
27.229
253316AC1-085 GEN3
Solar/Wind Harmer
7.601
253433AC1-085 GEN1
Solar/Wind Harmer
4.825
946181AF1-283 GEN
Solar/Wind Harmer
11.797
24728705AND G3
Adder
7.277
24728505AND G1
Adder
3.48
276621W2-048 GEN
Solar/Wind Harmer
5.645
276838X2-022 GEN2
Solar/Wind Harmer
0.211
276686W4-005 GEN3
Solar/Wind Harmer
2.726
276668AB2-070 GEN1
Solar/Wind Harmer
2.027
971993AH1-541 GEN
Solar/Wind Harmer
8.328
270356AE2-297 GEN
Solar/Wind Harmer
4.098
253406AD2-031_GEN
Solar/Wind Harmer
1.149
274760LEE CO EC;1U
Adder
8.222
274767LEE CO EC;8U
Adder
8.125
972236AH1-702 GEN2
Adder
1.93
274682WAUKEGAN ;7U
Adder
15.703
274729ELWOOD EC;1P
Adder
13.481
3147983MERCK5
Solar/Wind Helper
0.198
316192AB2-158 GEN
Solar/Wind Helper
1.838
3147666LOUISA
Solar/Wind Helper
1.088
316254AC1-120 GEN1
Solar/Wind Helper
1.159
316097T157 G90
Solar/Wind Helper
1.125
238148AE2-230_GEN2
Solar/Wind Helper
0.423
316336AC2-165 C
Solar/Wind Helper
1.285
316006AB2-029 C
Solar/Wind Helper
0.112
316045AC1-158 PL2
Solar/Wind Helper
4.023
971543AH1-269 GEN
50/50
12.247
966391AG1-508 GEN
Solar/Wind Harmer
6.374
270069AE2-166 C O1
Solar/Wind Harmer
4.507
971313AH1-133 GEN
Solar/Wind Harmer
15.698
24734705WLF1G3
Adder
8.194
24734805WLF1G4
Adder
8.194
24734905WLF1G5
Adder
8.194
270132AB1-180 C
Adder
0.169
24735105WLF2G1
Adder
8.023
270399AC1-101 GEN
Solar/Wind Harmer
5.556
270400AC1-102 GEN
Solar/Wind Harmer
5.556
941621AE2-160 GEN
Adder
4.285
957241AF2-018 GEN
Solar/Wind Harmer
5.757
970281AG2-184 GEN
Solar/Wind Harmer
27.126
972143AH1-644 GEN
Solar/Wind Harmer
12.917
971981AH1-535 GEN
Solar/Wind Harmer
12.563
962211AG1-066 GEN
Solar/Wind Harmer
3.001
971061AG2-657 GEN
Solar/Wind Harmer
10.991
24477305BRIDGE
Adder
0.419
972203AH1-686 GEN
Adder
2.704
270330AC1-082 GEN2
Solar/Wind Harmer
0.824
270329AC1-082 GEN1
Solar/Wind Harmer
0.485
965401AG1-405 GEN
Solar/Wind Harmer
6.059
965411AG1-406 GEN
Solar/Wind Harmer
2.719
339211AE2-254 GEN
Solar/Wind Harmer
1.563
3429211JKCT 2G
Adder
11.873
970455AG2-298 GEN
Solar/Wind Harmer
6.034
339243AC2-075 GEN1
Solar/Wind Harmer
0.446
972163AH1-664 GEN
Solar/Wind Harmer
9.743
972165AH1-665 GEN
Solar/Wind Harmer
7.794
971985AH1-537 GEN
Solar/Wind Harmer
17.295
270367AC2-061_GEN
Solar/Wind Harmer
3.009
316123AC1-075 GEN
Solar/Wind Harmer
1.493
970165AG2-112 GEN
Solar/Wind Harmer
1.315
24290605CLAY-1
50/50
0.255
24290605CLAY-1
50/50
0.255
24290705CLAY-2
50/50
0.255
24290705CLAY-2
50/50
0.255
24684405SMG2
50/50
2.224
24684505SMG3
50/50
1.376
24684305SMG1
50/50
0.806
270583AD2-179 GEN
Solar/Wind Harmer
20.721
270214AC2-123 GEN
Solar/Wind Harmer
4.311
971277AH1-098 GEN
Solar/Wind Harmer
7.42
316217AC1-145 GEN
Solar/Wind Harmer
4.247
316197AC1-042 GEN
Solar/Wind Harmer
3.219
942671AE2-283 GEN
Solar/Wind Harmer
8.667
24728205BUCHG1
Adder
6.75
270013AE1-250 PV
Solar/Wind Harmer
3.256
971225AH1-072 GEN
Solar/Wind Harmer
2.73
971227AH1-073 GEN
Solar/Wind Harmer
2.73
944971AF1-162 GEN
Solar/Wind Harmer
9.068
24723005RIVRG1
Adder
22.954
24723105RIVRG2
Adder
22.954
24685805CER G1
Adder
9.822
24685905CER G2
Adder
9.822
942751AE2-291 GEN
Solar/Wind Harmer
10.385
966021AG1-471 GEN
Solar/Wind Harmer
5.753
971485AH1-239 GEN
Solar/Wind Harmer
8.497
339231AF1-038_GEN
Solar/Wind Harmer
1.918
960161AF2-307 GEN
Solar/Wind Harmer
6.658
339255AE2-071 GEN
Solar/Wind Harmer
1.099
964781AG1-341 GEN
Solar/Wind Harmer
10.97
339236AF1-050_GEN
Solar/Wind Harmer
1.872
971081AG2-670 GEN
Solar/Wind Harmer
7.734
942891AE2-308 GEN
Solar/Wind Harmer
10.176
970653AG2-424 GEN
Solar/Wind Harmer
4.88
970653AG2-424 GEN
Solar/Wind Harmer
1.764
964571AG1-320 GEN
Solar/Wind Harmer
8.186
971125AH1-004 GEN
Solar/Wind Harmer
3.98
970107AG2-081 GEN
Solar/Wind Harmer
2.985
972043AH1-570 GEN
Solar/Wind Harmer
2.475
972045AH1-571 GEN
Solar/Wind Harmer
1.98
339221AD2-048_GEN
Solar/Wind Harmer
1.514
970235AG2-159 GEN
Solar/Wind Harmer
3.878
970235AG2-159 GEN
Solar/Wind Harmer
2.367
270186AC1-089 GEN
Solar/Wind Harmer
5.824
970239AG2-162 GEN
Solar/Wind Harmer
10.472
962581AG1-107 GEN
Solar/Wind Harmer
4.731
961491AF2-440 GEN
Solar/Wind Harmer
1.966
270444AC2-157 GEN1
Solar/Wind Harmer
5.239
252509AD1-136 GEN
Solar/Wind Harmer
0.238
25183208HLCRTG
Solar/Wind Harmer
5.582
252519AF1-045_GEN
Solar/Wind Harmer
5.589
252516AE2-318_GEN
Solar/Wind Harmer
4.263
25194408D.CRK1
Adder
6.938
25194508D.CRK3
Adder
1.297
970879AG2-548 GEN
Solar/Wind Harmer
5.656
971073AG2-665 GEN
Solar/Wind Harmer
5.656
971073AG2-665 GEN
Solar/Wind Harmer
3.946
945391AF1-204 GEN
Solar/Wind Harmer
12.718
276916AD2-100_GEN
Solar/Wind Harmer
19.154
276911AD2-131_GEN
Solar/Wind Harmer
3.871
957381AF2-032 GEN
Solar/Wind Harmer
0.381
253317AC1-085 GEN4
Solar/Wind Harmer
7.601
276763AC1-053 GEN1
Solar/Wind Harmer
3.568
276764AC1-053 GEN2
Solar/Wind Harmer
3.568
970241AG2-163 GEN
Solar/Wind Harmer
22.426
24728805RICHG1
Adder
3.384
24728905RICHG2
Adder
3.384
972267AH1-718 GEN
Adder
3.688
274764LEE CO EC;5U
Adder
8.241
274765LEE CO EC;6U
Adder
8.241
274762LEE CO EC;3U
Adder
8.222
274763LEE CO EC;4U
Adder
8.144
274683WAUKEGAN ;8U
Adder
18.419
274683WAUKEGAN ;8U
Adder
15.526
274696ROCKY RD ;4P
Adder
9.957
274695ROCKY RD ;2P
Adder
9.727
274693ROCKY RD ;1P
Adder
9.632
274697ROCKY RD ;3P
Adder
2.642
3132123MT JACKSON
Solar/Wind Helper
1.389
315821AE2-092 GEN
Solar/Wind Helper
3.216
966001AG1-469 GEN
Solar/Wind Helper
0.32
315651AD1-115 GEN
Solar/Wind Helper
0.837
966871AG1-558 GEN
Solar/Wind Helper
0.306
316447AC1-158 HLD
Solar/Wind Helper
2.766
316468AD1-105 GEN
Solar/Wind Helper
1.124
970479AG2-310 GEN
50/50
20.255
270205AE1-176
50/50
0.006
24288905REUSENS
50/50
0.057
24684605SMG4
50/50
2.239
966251AG1-494 GEN
50/50
4.388
24728405LEESVG
50/50
0.297
24415905BUCK
50/50
0.034
971367AH1-164 GEN
Solar/Wind Harmer
7.003
971329AH1-144 GEN
Solar/Wind Harmer
23.686
3147312GRETNA
Solar/Wind Harmer
-0.005
941821AE2-187 GEN
Solar/Wind Harmer
9.812
270197AD1-017 GEN1
Solar/Wind Harmer
2.546
270336AE1-100 GEN
Solar/Wind Harmer
2.757
943811AF1-049 GEN
Solar/Wind Harmer
5.695
24728305BUCHG2
Adder
6.75
270018AE2-047 C O1
Solar/Wind Harmer
1.826
958131AF2-107 GEN
Solar/Wind Harmer
7.108
24735205WLF2G2
Adder
8.023
971687AH1-348 GEN
Solar/Wind Harmer
1.359
971403AH1-188 GEN
Solar/Wind Harmer
18.852
24723205RIVRG3
Adder
22.954
971315AH1-136 GEN
Solar/Wind Harmer
2.43
24686105CER G3
Adder
9.887
24686505CER G6
Adder
9.874
270331AC1-082 GEN3
Solar/Wind Harmer
0.487
24721705FLATG2
Adder
21.686
970947AG2-589 GEN
Solar/Wind Harmer
2.139
970273AG2-179 GEN
Solar/Wind Harmer
2.581
971821AH1-427 GEN
Solar/Wind Harmer
10.346
964901AG1-354 GEN
Solar/Wind Harmer
15.5
339241AF1-083 GEN
Solar/Wind Harmer
1.715
962241AG1-070 GEN
Solar/Wind Harmer
4.64
960001AF2-291 GEN
Solar/Wind Harmer
3.113
3429241JKCT 3G
Adder
12.029
3429421JKCT 10G
Adder
8.402
971565AH1-281 GEN
Solar/Wind Harmer
2.001
943111AE2-339 GEN
Solar/Wind Harmer
0.883
339216AC1-074 GEN
Solar/Wind Harmer
1.649
945681AF1-233 GEN
Solar/Wind Harmer
18.32
927014AC1-188 GEN
Solar/Wind Harmer
1.532
970091AG2-072 GEN
Adder
74.012
970333AG2-219 GEN
Solar/Wind Harmer
30.05
270445AC2-157 GEN2
Solar/Wind Harmer
5.239
25196808ZIMRHP
Adder
70.616
252507AC2-088 GEN
Solar/Wind Harmer
1.669
25196008MFTGT1
Adder
1.293
25194608D.CRK4
Adder
1.508
965911AG1-460 GEN
Solar/Wind Harmer
1.271
253432AC1-085 GEN2
Solar/Wind Harmer
0.243
946171AF1-282 GEN
Solar/Wind Harmer
9.075
24728605AND G2
Adder
3.48
276615X2-022 GEN
Solar/Wind Harmer
1.772
963831AG1-236 GEN
Solar/Wind Harmer
8.877
274880W4-005 GEN4
Solar/Wind Harmer
2.726
963741AG1-226 GEN
Solar/Wind Harmer
40.366
274761LEE CO EC;2U
Adder
8.222
274766LEE CO EC;7U
Adder
8.125
972235AH1-702 GEN1
Adder
2.22
274822ROCKFORD ;11
Adder
17.275
274828WAUKEGAN ;BP
Adder
9.655
274682WAUKEGAN ;7U
Adder
15.703
274745AC1-111 GEN9
Adder
4.87
315616AA1-038_C
Solar/Wind Helper
3.293
3148013FISHERV
Solar/Wind Helper
0.523
316499AE2-029_GEN
Solar/Wind Helper
1.725
3132273ORANGE
Solar/Wind Helper
0.056
3147666LOUISA
Solar/Wind Helper
0.625
237061AD1-155 GEN
Solar/Wind Helper
0.05
316170AC1-121 GEN2
Solar/Wind Helper
0.386
23583801GRNGAP
Solar/Wind Helper
4.287
316095T157 G97
Solar/Wind Helper
1.125
238147AE2-230_GEN1
Solar/Wind Helper
0.421
238149AF1-291A_GEN
Solar/Wind Helper
0.12
316313AB2-026
Solar/Wind Helper
0.354
316258AE1-075 C
Solar/Wind Helper
0.319
316405AF2-144 C
Solar/Wind Helper
0.265
966881AG1-559 GEN
Solar/Wind Helper
0.313
316473AC1-191 GEN
Solar/Wind Helper
1.387
316044AC1-158 PL1
Solar/Wind Helper
1.257
316450AC1-158 RIC
Solar/Wind Helper
0.335
972175AH1-670 GEN
Solar/Wind Harmer
4.72
970163AG2-111 GEN
Solar/Wind Harmer
1.254
25196108MFTGT2
Adder
1.425
25196108MFTGT2
Adder
1.324
970879AG2-548 GEN
Solar/Wind Harmer
3.946
944221AF1-090 GEN
Solar/Wind Harmer
10.024
252524AE2-267 GEN
Solar/Wind Harmer
1.444
25196408WSDLE3
Adder
8.08
25196308WSDLE2
Adder
8.01
25196208WSDLE1
Adder
7.99
25196708WSDLE6
Adder
7.97
25196508WSDLE4
Adder
7.769
276785W4-005 GEN1
Solar/Wind Harmer
2.726
276174W4-005 GEN2
Solar/Wind Harmer
2.726
276849AB2-070 GEN2
Solar/Wind Harmer
2.027
276848AB2-070 GEN3
Solar/Wind Harmer
2.027
274823ROCKFORD ;21
Adder
17.15
274746AC1-111 G10
Adder
4.87
274744AC1-111 GEN8
Adder
4.87
25306009OHH W.
Adder
2.505
3148463FAIRFLD
Solar/Wind Helper
0.726
3148133STUARTS
Solar/Wind Helper
0.313
3148013FISHERV
Solar/Wind Helper
0.3
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
23546401DTGZ2-030
Solar/Wind Helper
0.078
316164AC1-076 GEN
Solar/Wind Helper
1.172
238152AF2-075_GEN
Solar/Wind Helper
0.602
944201AF1-088_MTX
Adder
109.09
957141AF2-008_MTX
Adder
54.545
CPLELTFEXP_CPLE->PJM
CLTF
6.226
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.111
LAGNLTFEXP_LAGN->PJM
CLTF
20.28
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.555
TVALTFEXP_TVA->PJM
CLTF
10.606
NYPJM->LTFIMP_NY
CLTF
3.248
LGEELTFEXP_LGEE->PJM
CLTF
6.763
WECLTFEXP_WEC->PJM
CLTF
3.371
AG2-052LTFEXP_AG2-052->PJM
LTF
0.202
AH1-155LTFEXP_AH1-155->PJM
LTF
0.303
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.415
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.315
MECLTFEXP_MEC->PJM
CLTF
15.415
SIGELTFEXP_SIGE->PJM
CLTF
0.508

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AEP_P4_#2942_05KAMMER 765_PP_SRT-A


Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2942_05KAMMER 765_PP_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.36 %
Rating:3610.0 MVA
Rating Type:B
MVA to Mitigate:4200.43
MW Contribution:8.5
Bus #Bus NameTypeMW Contribution
970479AG2-310 GEN
50/50
20.26
270205AE1-176
50/50
0.006
24288905REUSENS
50/50
0.057
24684605SMG4
50/50
2.239
966251AG1-494 GEN
50/50
4.39
24728405LEESVG
50/50
0.297
24415905BUCK
50/50
0.034
971367AH1-164 GEN
Solar/Wind Harmer
7.005
971329AH1-144 GEN
Solar/Wind Harmer
23.694
3147312GRETNA
Solar/Wind Harmer
-0.005
941821AE2-187 GEN
Solar/Wind Harmer
9.815
270197AD1-017 GEN1
Solar/Wind Harmer
2.547
270336AE1-100 GEN
Solar/Wind Harmer
2.758
943811AF1-049 GEN
Solar/Wind Harmer
5.698
24728305BUCHG2
Adder
6.753
270018AE2-047 C O1
Solar/Wind Harmer
1.826
958131AF2-107 GEN
Solar/Wind Harmer
7.111
24735205WLF2G2
Adder
8.027
971687AH1-348 GEN
Solar/Wind Harmer
1.359
971403AH1-188 GEN
Solar/Wind Harmer
18.861
24723205RIVRG3
Adder
22.966
971315AH1-136 GEN
Solar/Wind Harmer
2.431
24686105CER G3
Adder
9.893
24686505CER G6
Adder
9.88
270331AC1-082 GEN3
Solar/Wind Harmer
0.487
24721705FLATG2
Adder
21.699
970947AG2-589 GEN
Solar/Wind Harmer
2.14
970273AG2-179 GEN
Solar/Wind Harmer
2.583
971821AH1-427 GEN
Solar/Wind Harmer
10.353
964901AG1-354 GEN
Solar/Wind Harmer
15.509
339241AF1-083 GEN
Solar/Wind Harmer
1.716
962241AG1-070 GEN
Solar/Wind Harmer
4.643
960001AF2-291 GEN
Solar/Wind Harmer
3.115
3429241JKCT 3G
Adder
12.037
3429421JKCT 10G
Adder
8.407
971565AH1-281 GEN
Solar/Wind Harmer
2.002
943111AE2-339 GEN
Solar/Wind Harmer
0.883
339216AC1-074 GEN
Solar/Wind Harmer
1.65
945681AF1-233 GEN
Solar/Wind Harmer
18.332
927014AC1-188 GEN
Solar/Wind Harmer
1.533
970091AG2-072 GEN
Adder
74.061
970333AG2-219 GEN
Solar/Wind Harmer
30.071
270445AC2-157 GEN2
Solar/Wind Harmer
5.243
25196808ZIMRHP
Adder
70.665
252507AC2-088 GEN
Solar/Wind Harmer
1.671
25196008MFTGT1
Adder
1.294
25194608D.CRK4
Adder
1.509
965911AG1-460 GEN
Solar/Wind Harmer
1.272
253432AC1-085 GEN2
Solar/Wind Harmer
0.243
946171AF1-282 GEN
Solar/Wind Harmer
9.081
24728605AND G2
Adder
3.482
971543AH1-269 GEN
50/50
12.251
966391AG1-508 GEN
Solar/Wind Harmer
6.377
270069AE2-166 C O1
Solar/Wind Harmer
4.508
971313AH1-133 GEN
Solar/Wind Harmer
15.705
24734705WLF1G3
Adder
8.198
24734805WLF1G4
Adder
8.198
24734905WLF1G5
Adder
8.198
270132AB1-180 C
Adder
0.169
24735105WLF2G1
Adder
8.027
270399AC1-101 GEN
Solar/Wind Harmer
5.558
270400AC1-102 GEN
Solar/Wind Harmer
5.558
941621AE2-160 GEN
Adder
4.287
957241AF2-018 GEN
Solar/Wind Harmer
5.759
970281AG2-184 GEN
Solar/Wind Harmer
27.14
972143AH1-644 GEN
Solar/Wind Harmer
12.924
971981AH1-535 GEN
Solar/Wind Harmer
12.569
962211AG1-066 GEN
Solar/Wind Harmer
3.003
971061AG2-657 GEN
Solar/Wind Harmer
10.996
24477305BRIDGE
Adder
0.419
972203AH1-686 GEN
Adder
2.706
270330AC1-082 GEN2
Solar/Wind Harmer
0.824
270329AC1-082 GEN1
Solar/Wind Harmer
0.486
965401AG1-405 GEN
Solar/Wind Harmer
6.063
965411AG1-406 GEN
Solar/Wind Harmer
2.721
339211AE2-254 GEN
Solar/Wind Harmer
1.564
3429211JKCT 2G
Adder
11.881
970455AG2-298 GEN
Solar/Wind Harmer
6.038
339243AC2-075 GEN1
Solar/Wind Harmer
0.447
972163AH1-664 GEN
Solar/Wind Harmer
9.749
972165AH1-665 GEN
Solar/Wind Harmer
7.8
971985AH1-537 GEN
Solar/Wind Harmer
17.306
270367AC2-061_GEN
Solar/Wind Harmer
3.011
316123AC1-075 GEN
Solar/Wind Harmer
1.494
970165AG2-112 GEN
Solar/Wind Harmer
1.315
970163AG2-111 GEN
Solar/Wind Harmer
1.255
25196108MFTGT2
Adder
1.426
25196108MFTGT2
Adder
1.325
970879AG2-548 GEN
Solar/Wind Harmer
3.949
944221AF1-090 GEN
Solar/Wind Harmer
10.031
24290605CLAY-1
50/50
0.255
24290605CLAY-1
50/50
0.255
24290705CLAY-2
50/50
0.255
24290705CLAY-2
50/50
0.255
24684405SMG2
50/50
2.225
24684505SMG3
50/50
1.376
24684305SMG1
50/50
0.806
270583AD2-179 GEN
Solar/Wind Harmer
20.728
270214AC2-123 GEN
Solar/Wind Harmer
4.312
971277AH1-098 GEN
Solar/Wind Harmer
7.423
316217AC1-145 GEN
Solar/Wind Harmer
4.248
316197AC1-042 GEN
Solar/Wind Harmer
3.22
942671AE2-283 GEN
Solar/Wind Harmer
8.67
24728205BUCHG1
Adder
6.753
270013AE1-250 PV
Solar/Wind Harmer
3.257
971225AH1-072 GEN
Solar/Wind Harmer
2.732
971227AH1-073 GEN
Solar/Wind Harmer
2.732
944971AF1-162 GEN
Solar/Wind Harmer
9.072
24723005RIVRG1
Adder
22.966
24723105RIVRG2
Adder
22.966
24685805CER G1
Adder
9.828
24685905CER G2
Adder
9.828
942751AE2-291 GEN
Solar/Wind Harmer
10.391
966021AG1-471 GEN
Solar/Wind Harmer
5.756
971485AH1-239 GEN
Solar/Wind Harmer
8.502
339231AF1-038_GEN
Solar/Wind Harmer
1.919
960161AF2-307 GEN
Solar/Wind Harmer
6.662
339255AE2-071 GEN
Solar/Wind Harmer
1.099
964781AG1-341 GEN
Solar/Wind Harmer
10.976
339236AF1-050_GEN
Solar/Wind Harmer
1.873
971081AG2-670 GEN
Solar/Wind Harmer
7.739
942891AE2-308 GEN
Solar/Wind Harmer
10.182
970653AG2-424 GEN
Solar/Wind Harmer
4.883
970653AG2-424 GEN
Solar/Wind Harmer
1.765
964571AG1-320 GEN
Solar/Wind Harmer
8.191
971125AH1-004 GEN
Solar/Wind Harmer
3.983
970107AG2-081 GEN
Solar/Wind Harmer
2.987
972043AH1-570 GEN
Solar/Wind Harmer
2.476
972045AH1-571 GEN
Solar/Wind Harmer
1.981
339221AD2-048_GEN
Solar/Wind Harmer
1.515
970235AG2-159 GEN
Solar/Wind Harmer
3.88
970235AG2-159 GEN
Solar/Wind Harmer
2.369
270186AC1-089 GEN
Solar/Wind Harmer
5.828
970239AG2-162 GEN
Solar/Wind Harmer
10.479
962581AG1-107 GEN
Solar/Wind Harmer
4.734
961491AF2-440 GEN
Solar/Wind Harmer
1.967
270444AC2-157 GEN1
Solar/Wind Harmer
5.243
252509AD1-136 GEN
Solar/Wind Harmer
0.239
25183208HLCRTG
Solar/Wind Harmer
5.586
252519AF1-045_GEN
Solar/Wind Harmer
5.593
252516AE2-318_GEN
Solar/Wind Harmer
4.266
25194408D.CRK1
Adder
6.943
25194508D.CRK3
Adder
1.298
970879AG2-548 GEN
Solar/Wind Harmer
5.66
971073AG2-665 GEN
Solar/Wind Harmer
5.66
971073AG2-665 GEN
Solar/Wind Harmer
3.949
945391AF1-204 GEN
Solar/Wind Harmer
12.727
276916AD2-100_GEN
Solar/Wind Harmer
19.168
276911AD2-131_GEN
Solar/Wind Harmer
3.874
957381AF2-032 GEN
Solar/Wind Harmer
0.381
253317AC1-085 GEN4
Solar/Wind Harmer
7.607
276763AC1-053 GEN1
Solar/Wind Harmer
3.571
276764AC1-053 GEN2
Solar/Wind Harmer
3.571
970241AG2-163 GEN
Solar/Wind Harmer
22.442
24728805RICHG1
Adder
3.386
24728905RICHG2
Adder
3.386
972267AH1-718 GEN
Adder
3.691
274764LEE CO EC;5U
Adder
8.247
274765LEE CO EC;6U
Adder
8.247
274762LEE CO EC;3U
Adder
8.227
274763LEE CO EC;4U
Adder
8.15
274683WAUKEGAN ;8U
Adder
18.432
274683WAUKEGAN ;8U
Adder
15.538
274696ROCKY RD ;4P
Adder
9.964
274695ROCKY RD ;2P
Adder
9.734
274693ROCKY RD ;1P
Adder
9.639
274697ROCKY RD ;3P
Adder
2.644
3132123MT JACKSON
Solar/Wind Helper
1.388
315821AE2-092 GEN
Solar/Wind Helper
3.215
966001AG1-469 GEN
Solar/Wind Helper
0.32
315651AD1-115 GEN
Solar/Wind Helper
0.837
970823AG2-518 GEN
50/50
8.386
247619Y1-049
50/50
0.913
24684705SMG5
50/50
0.857
970481AG2-311 GEN
50/50
11.941
24728405LEESVG
50/50
0.296
24416005BYLLESBY
50/50
0.031
3151561HALLBR1
50/50
0.57
970563AG2-360 GEN
50/50
45.847
962751AG1-124 GEN
Solar/Wind Harmer
18.831
958121AF2-106 GEN
Solar/Wind Harmer
9.409
270173AC1-122 GEN
Solar/Wind Harmer
3.279
971331AH1-145 GEN
Solar/Wind Harmer
18.367
943031AE2-326 GEN
Solar/Wind Harmer
6.787
3147312GRETNA
Solar/Wind Harmer
-0.021
3146802CHATHAM
Solar/Wind Harmer
-0.02
941801AE2-185 GEN
Solar/Wind Harmer
9.815
270574AD1-017 GEN2
Solar/Wind Harmer
8.476
3147123OTTER R
Solar/Wind Harmer
-0.014
270346AE1-212 GEN
Solar/Wind Harmer
13.941
270030AE2-140 GEN
Solar/Wind Harmer
30.942
960911AF2-382 GEN
Solar/Wind Harmer
10.952
270016AE1-250 BESS
Solar/Wind Harmer
3.257
970913AG2-568 GEN
Solar/Wind Harmer
11.009
971461AH1-227 GEN
Solar/Wind Harmer
7.007
970223AG2-152 GEN
Solar/Wind Harmer
17.631
270053AF1-130 C
Solar/Wind Harmer
4.818
972103AH1-617 GEN
Solar/Wind Harmer
25.847
24686205CER G4
Adder
9.841
24686405CER G5
Adder
9.802
972273AH1-721 GEN
Adder
89.369
24721905FLATG4
Adder
21.699
970273AG2-179 GEN
Solar/Wind Harmer
4.125
339250AF1-203 GEN
Solar/Wind Harmer
0.628
971155AH1-034 GEN
Solar/Wind Harmer
10.36
962251AG1-071 GEN
Solar/Wind Harmer
5.674
966571AG1-526 GEN
Solar/Wind Harmer
22.9
970093AG2-073 GEN
Solar/Wind Harmer
10.278
960741AF2-365 GEN
Solar/Wind Harmer
5.111
3429391JKCT 9G
Adder
8.407
971191AH1-055 GEN
Solar/Wind Harmer
22.196
972167AH1-666 GEN
Solar/Wind Harmer
7.773
957541AF2-048 GEN
Solar/Wind Harmer
1.529
958171AF2-111 GEN
Solar/Wind Harmer
23.926
970243AG2-164 GEN
Solar/Wind Harmer
24.603
970519AG2-331 GEN
Solar/Wind Harmer
16.529
970699AG2-449 GEN
Solar/Wind Harmer
10.935
25196008MFTGT1
Adder
1.253
252524AE2-267 GEN
Solar/Wind Harmer
1.445
25196408WSDLE3
Adder
8.086
25196308WSDLE2
Adder
8.015
25196208WSDLE1
Adder
7.995
25196708WSDLE6
Adder
7.975
25196508WSDLE4
Adder
7.774
276849AB2-070 GEN2
Solar/Wind Harmer
2.029
276848AB2-070 GEN3
Solar/Wind Harmer
2.029
276785W4-005 GEN1
Solar/Wind Harmer
2.728
276174W4-005 GEN2
Solar/Wind Harmer
2.728
274823ROCKFORD ;21
Adder
17.162
274746AC1-111 G10
Adder
4.873
274744AC1-111 GEN8
Adder
4.873
25306009OHH W.
Adder
2.506
3148463FAIRFLD
Solar/Wind Helper
0.726
3148133STUARTS
Solar/Wind Helper
0.313
3148013FISHERV
Solar/Wind Helper
0.3
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
23546401DTGZ2-030
Solar/Wind Helper
0.078
316164AC1-076 GEN
Solar/Wind Helper
1.171
238152AF2-075_GEN
Solar/Wind Helper
0.601
966871AG1-558 GEN
Solar/Wind Helper
0.306
316447AC1-158 HLD
Solar/Wind Helper
2.764
316468AD1-105 GEN
Solar/Wind Helper
1.124
276615X2-022 GEN
Solar/Wind Harmer
1.774
963831AG1-236 GEN
Solar/Wind Harmer
8.883
274880W4-005 GEN4
Solar/Wind Harmer
2.728
963741AG1-226 GEN
Solar/Wind Harmer
40.395
274761LEE CO EC;2U
Adder
8.227
274766LEE CO EC;7U
Adder
8.131
972235AH1-702 GEN1
Adder
2.221
274822ROCKFORD ;11
Adder
17.288
274828WAUKEGAN ;BP
Adder
9.662
274682WAUKEGAN ;7U
Adder
15.715
274745AC1-111 GEN9
Adder
4.873
315616AA1-038_C
Solar/Wind Helper
3.292
3148013FISHERV
Solar/Wind Helper
0.522
316499AE2-029_GEN
Solar/Wind Helper
1.724
3132273ORANGE
Solar/Wind Helper
0.056
3147666LOUISA
Solar/Wind Helper
0.625
237061AD1-155 GEN
Solar/Wind Helper
0.05
316170AC1-121 GEN2
Solar/Wind Helper
0.386
23583801GRNGAP
Solar/Wind Helper
4.284
316095T157 G97
Solar/Wind Helper
1.124
238147AE2-230_GEN1
Solar/Wind Helper
0.421
238149AF1-291A_GEN
Solar/Wind Helper
0.12
316313AB2-026
Solar/Wind Helper
0.354
316258AE1-075 C
Solar/Wind Helper
0.318
316405AF2-144 C
Solar/Wind Helper
0.265
966881AG1-559 GEN
Solar/Wind Helper
0.313
316473AC1-191 GEN
Solar/Wind Helper
1.386
316044AC1-158 PL1
Solar/Wind Helper
1.256
316450AC1-158 RIC
Solar/Wind Helper
0.335
972175AH1-670 GEN
Solar/Wind Harmer
4.723
252510AF1-249 C
Solar/Wind Harmer
0.385
25194608D.CRK4
Adder
1.509
25196608WSDLE5
Adder
7.855
970193AG2-126 GEN
Solar/Wind Harmer
13.698
942481AE2-261 GEN
Solar/Wind Harmer
27.248
253316AC1-085 GEN3
Solar/Wind Harmer
7.607
253433AC1-085 GEN1
Solar/Wind Harmer
4.829
946181AF1-283 GEN
Solar/Wind Harmer
11.806
24728705AND G3
Adder
7.283
24728505AND G1
Adder
3.482
276621W2-048 GEN
Solar/Wind Harmer
5.649
276838X2-022 GEN2
Solar/Wind Harmer
0.211
276668AB2-070 GEN1
Solar/Wind Harmer
2.029
276686W4-005 GEN3
Solar/Wind Harmer
2.728
971993AH1-541 GEN
Solar/Wind Harmer
8.334
270356AE2-297 GEN
Solar/Wind Harmer
4.101
253406AD2-031_GEN
Solar/Wind Harmer
1.149
274760LEE CO EC;1U
Adder
8.227
274767LEE CO EC;8U
Adder
8.131
972236AH1-702 GEN2
Adder
1.932
274682WAUKEGAN ;7U
Adder
15.715
274729ELWOOD EC;1P
Adder
13.491
3147983MERCK5
Solar/Wind Helper
0.198
316192AB2-158 GEN
Solar/Wind Helper
1.837
3147666LOUISA
Solar/Wind Helper
1.087
316254AC1-120 GEN1
Solar/Wind Helper
1.158
316097T157 G90
Solar/Wind Helper
1.124
238148AE2-230_GEN2
Solar/Wind Helper
0.423
316336AC2-165 C
Solar/Wind Helper
1.284
316006AB2-029 C
Solar/Wind Helper
0.112
316045AC1-158 PL2
Solar/Wind Helper
4.02
944201AF1-088_MTX
Adder
109.164
957141AF2-008_MTX
Adder
54.582
CPLELTFEXP_CPLE->PJM
CLTF
6.233
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.197
LAGNLTFEXP_LAGN->PJM
CLTF
20.293
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.574
TVALTFEXP_TVA->PJM
CLTF
10.613
NYPJM->LTFIMP_NY
CLTF
3.243
LGEELTFEXP_LGEE->PJM
CLTF
6.767
WECLTFEXP_WEC->PJM
CLTF
3.374
AG2-052LTFEXP_AG2-052->PJM
LTF
0.202
AH1-155LTFEXP_AH1-155->PJM
LTF
0.303
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.508
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.339
MECLTFEXP_MEC->PJM
CLTF
15.425
SIGELTFEXP_SIGE->PJM
CLTF
0.508

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P1-2_#17217_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#17217_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:115.67 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6388.32
MW Contribution:7.49
Bus #Bus NameTypeMW Contribution
243186AF1-051 GEN
50/50
12.478
24723005RIVRG1
Adder
36.021
24723105RIVRG2
Adder
36.021
24685805CER G1
Adder
15.526
24685905CER G2
Adder
15.526
944971AF1-162 GEN
Solar/Wind Harmer
12.174
971225AH1-072 GEN
Solar/Wind Harmer
2.13
971227AH1-073 GEN
Solar/Wind Harmer
2.13
24728205BUCHG1
Adder
6.831
970239AG2-162 GEN
Solar/Wind Harmer
2.59
270186AC1-089 GEN
Solar/Wind Harmer
0.006
962581AG1-107 GEN
Solar/Wind Harmer
0.002
960161AF2-307 GEN
Solar/Wind Harmer
6.771
971073AG2-665 GEN
Solar/Wind Harmer
9.191
252509AD1-136 GEN
Solar/Wind Harmer
0.051
339221AD2-048_GEN
Solar/Wind Harmer
0.006
972043AH1-570 GEN
Solar/Wind Harmer
2.614
972045AH1-571 GEN
Solar/Wind Harmer
2.094
25183208HLCRTG
Solar/Wind Harmer
0.016
252519AF1-045_GEN
Solar/Wind Harmer
8.714
252516AE2-318_GEN
Solar/Wind Harmer
7.729
970235AG2-159 GEN
Solar/Wind Harmer
6.108
970235AG2-159 GEN
Solar/Wind Harmer
3.504
971125AH1-004 GEN
Solar/Wind Harmer
3.992
970107AG2-081 GEN
Solar/Wind Harmer
2.994
25194408D.CRK1
Adder
10.799
25194508D.CRK3
Adder
2.019
942891AE2-308 GEN
Solar/Wind Harmer
9.954
253317AC1-085 GEN4
Solar/Wind Harmer
0.006
270444AC2-157 GEN1
Solar/Wind Harmer
0.004
971587AH1-292 GEN
Solar/Wind Harmer
7.197
253394AE2-221_GEN
Solar/Wind Harmer
0.012
253398AE2-221_GEN2
Solar/Wind Harmer
0.012
964571AG1-320 GEN
Solar/Wind Harmer
8.854
970653AG2-424 GEN
Solar/Wind Harmer
4.654
970653AG2-424 GEN
Solar/Wind Harmer
2.412
24728805RICHG1
Adder
5.204
24728905RICHG2
Adder
5.204
971081AG2-670 GEN
Solar/Wind Harmer
7.154
945391AF1-204 GEN
Solar/Wind Harmer
10.131
24379505HDWTR1G C
Solar/Wind Harmer
0.003
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
253370AE2-315 SEC1
Adder
2.733
270383AD1-128 GEN
Solar/Wind Harmer
0.006
970241AG2-163 GEN
Solar/Wind Harmer
5.517
971613AH1-306 GEN
Solar/Wind Harmer
4.531
25322209TAIT E
Adder
13.187
25322209TAIT E
Adder
12.891
970825AG2-519 GEN
Solar/Wind Harmer
10.439
960441AF2-335 GEN
Solar/Wind Harmer
9.416
966841AG1-555 GEN
Solar/Wind Harmer
1.065
339255AE2-071 GEN
Solar/Wind Harmer
-0.154
970321AG2-212 GEN
Solar/Wind Harmer
4.056
971485AH1-239 GEN
Solar/Wind Harmer
7.489
964781AG1-341 GEN
Solar/Wind Harmer
9.922
966021AG1-471 GEN
Solar/Wind Harmer
5.054
25326109MON D
Adder
1.763
970883AG2-550 GEN
Solar/Wind Harmer
9.347
970885AG2-551 GEN
Solar/Wind Harmer
3.116
945421AF1-207 GEN
Solar/Wind Harmer
0.001
24289405MTG1
50/50
11.351
24318705GVG2
50/50
11.615
24722005FLATG5
50/50
2.756
24721905FLATG4
50/50
50.519
24686205CER G4
Adder
15.547
24686405CER G5
Adder
15.485
270053AF1-130 C
Solar/Wind Harmer
2.748
970153AG2-106 GEN
Solar/Wind Harmer
29.498
971191AH1-055 GEN
Solar/Wind Harmer
30.005
970913AG2-568 GEN
Solar/Wind Harmer
8.769
972103AH1-617 GEN
Solar/Wind Harmer
21.835
960911AF2-382 GEN
Solar/Wind Harmer
8.035
971461AH1-227 GEN
Solar/Wind Harmer
5.464
970243AG2-164 GEN
Solar/Wind Harmer
6.06
970519AG2-331 GEN
Solar/Wind Harmer
26.931
970699AG2-449 GEN
Solar/Wind Harmer
2.59
972167AH1-666 GEN
Solar/Wind Harmer
8.145
958171AF2-111 GEN
Solar/Wind Harmer
25.128
252510AF1-249 C
Solar/Wind Harmer
0.077
25196008MFTGT1
Adder
1.926
25194608D.CRK4
Adder
2.348
25196608WSDLE5
Adder
12.22
3429391JKCT 9G
Adder
11.865
970093AG2-073 GEN
Solar/Wind Harmer
9.929
253316AC1-085 GEN3
Solar/Wind Harmer
0.006
253433AC1-085 GEN1
Solar/Wind Harmer
0.005
946181AF1-283 GEN
Solar/Wind Harmer
12.875
253406AD2-031_GEN
Solar/Wind Harmer
0.735
966571AG1-526 GEN
Solar/Wind Harmer
21.864
270291AC1-194 GEN
Solar/Wind Harmer
7.771
253415AE1-040 GEN
Solar/Wind Harmer
0.004
972173AH1-669 GEN
Solar/Wind Harmer
4.843
270222AC2-111 GEN
Solar/Wind Harmer
4.893
972273AH1-721 GEN
Adder
114.731
270273AD2-016 GEN
Solar/Wind Harmer
0.998
270356AE2-297 GEN
Solar/Wind Harmer
0.013
24728705AND G3
Adder
11.022
24728505AND G1
Adder
5.27
970193AG2-126 GEN
Solar/Wind Harmer
14.303
270437AC2-090 C
Solar/Wind Harmer
0.004
253370AE2-315 SEC1
Adder
2.733
253371AE2-315 SEC2
Adder
2.585
270346AE1-212 GEN
Solar/Wind Harmer
8.4
970273AG2-179 GEN
Solar/Wind Harmer
5.694
960741AF2-365 GEN
Solar/Wind Harmer
4.731
970191AG2-125 GEN
Solar/Wind Harmer
2.433
247642Z2-115 C
Solar/Wind Harmer
0.004
970289AG2-191 GEN
Solar/Wind Harmer
1.039
970291AG2-192 GEN
Solar/Wind Harmer
0.944
958821AF2-173 GEN
Solar/Wind Harmer
13.219
270004AE1-209 GEN
Solar/Wind Harmer
2.046
946031AF1-268 GEN
Solar/Wind Harmer
8.936
339250AF1-203 GEN
Solar/Wind Harmer
0.001
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
9.369
971155AH1-034 GEN
Solar/Wind Harmer
10.922
970513AG2-328 GEN
Solar/Wind Harmer
4.056
970517AG2-330 GEN
Solar/Wind Harmer
24.338
962251AG1-071 GEN
Solar/Wind Harmer
5.847
942481AE2-261 GEN
Solar/Wind Harmer
27.825
276621W2-048 GEN
Solar/Wind Harmer
0.469
276838X2-022 GEN2
Solar/Wind Harmer
0.523
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
4.291
276668AB2-070 GEN1
Solar/Wind Harmer
0.339
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
943031AE2-326 GEN
Solar/Wind Harmer
4.828
274853TWINGROVE;U1
Solar/Wind Harmer
0.004
965091AG1-374 GEN
Solar/Wind Harmer
27.736
959611AF2-252 GEN
Solar/Wind Harmer
3.082
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
13.864
942111AE2-223 GEN
Solar/Wind Harmer
3.001
964401AG1-302 GEN
Solar/Wind Harmer
0.001
944531AF1-118 GEN
Solar/Wind Harmer
41.286
270535AF1-215 GEN1
Solar/Wind Harmer
0.011
274878BISHOP HL;2U
Solar/Wind Harmer
0.308
253338AC1-165 GEN
Solar/Wind Harmer
0.004
253333AC1-068 GEN
Solar/Wind Harmer
0.014
970571AG2-364 GEN
Solar/Wind Harmer
18.307
276889AE2-281 GEN
Solar/Wind Harmer
0.001
276897AD1-100 C
Solar/Wind Harmer
0.012
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
274772LINCOLN ;3U
Adder
11.055
276805AD2-038 GEN
Solar/Wind Harmer
0.003
276157O29GEN1
Solar/Wind Harmer
1.478
970707AG2-453 GEN
Solar/Wind Harmer
29.848
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
943121AE2-341 GEN
Solar/Wind Harmer
15.314
943591AF1-030 GEN
Solar/Wind Harmer
10.184
274855GSG-6 ;RU
Solar/Wind Harmer
0.335
274850MENDOTA H;RU
Solar/Wind Harmer
0.108
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.164
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
0.974
274760LEE CO EC;1U
Adder
12.175
274767LEE CO EC;8U
Adder
12.032
24289405MTG1
50/50
11.351
243186AF1-051 GEN
50/50
12.478
24318705GVG2
50/50
11.615
24721805FLATG3
50/50
2.756
24721705FLATG2
50/50
50.519
24723205RIVRG3
Adder
36.021
24686105CER G3
Adder
15.629
24721605FLATG1
50/50
2.756
972203AH1-686 GEN
Adder
4.425
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
957241AF2-018 GEN
Solar/Wind Harmer
-0.002
270399AC1-101 GEN
Solar/Wind Harmer
3.805
270400AC1-102 GEN
Solar/Wind Harmer
3.805
962771AG1-126 GEN
Solar/Wind Harmer
46.194
24477305BRIDGE
Adder
0.588
970281AG2-184 GEN
Solar/Wind Harmer
22.926
972143AH1-644 GEN
Solar/Wind Harmer
11.827
971985AH1-537 GEN
Solar/Wind Harmer
3.245
941621AE2-160 GEN
Adder
5.057
971313AH1-133 GEN
Solar/Wind Harmer
10.378
270367AC2-061_GEN
Solar/Wind Harmer
0.008
970879AG2-548 GEN
Solar/Wind Harmer
9.191
972163AH1-664 GEN
Solar/Wind Harmer
11.344
972165AH1-665 GEN
Solar/Wind Harmer
9.085
339243AC2-075 GEN1
Solar/Wind Harmer
0.002
25196108MFTGT2
Adder
2.193
25196108MFTGT2
Adder
2.036
3429211JKCT 2G
Adder
16.676
252524AE2-267 GEN
Solar/Wind Harmer
0.004
25196408WSDLE3
Adder
12.579
25196308WSDLE2
Adder
12.47
25196208WSDLE1
Adder
12.439
25196708WSDLE6
Adder
12.407
25196508WSDLE4
Adder
12.095
24734705WLF1G3
Adder
8.198
24734805WLF1G4
Adder
8.198
24734905WLF1G5
Adder
8.198
270340AC2-060 GEN
Solar/Wind Harmer
0.011
270132AB1-180 C
Adder
0.17
339211AE2-254 GEN
Solar/Wind Harmer
0.004
24735105WLF2G1
Adder
8.08
970455AG2-298 GEN
Solar/Wind Harmer
6.495
965401AG1-405 GEN
Solar/Wind Harmer
5.522
965411AG1-406 GEN
Solar/Wind Harmer
3.552
270269AC2-059
Solar/Wind Harmer
0.006
971061AG2-657 GEN
Solar/Wind Harmer
6.031
270240V3-007_GEN2
Solar/Wind Harmer
0.003
253372AE2-315 SEC3
Adder
2.585
253372AE2-315 SEC3
Adder
2.585
25306009OHH W.
Adder
3.927
24725505WLD G2 C
Solar/Wind Harmer
0.002
24699105WLD G1 C
Solar/Wind Harmer
0.001
253349AC2-067 GEN
Solar/Wind Harmer
2.978
253400AC2-068 GEN
Solar/Wind Harmer
1.198
970289AG2-191 GEN
Solar/Wind Harmer
1.794
270594AE1-207 GEN
Solar/Wind Harmer
10.572
963841AG1-237 GEN
Solar/Wind Harmer
4.089
970115AG2-085 GEN
Solar/Wind Harmer
3.766
971673AH1-337 GEN
Solar/Wind Harmer
6.118
24386205FR-12G C
Solar/Wind Harmer
0.002
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.002
971029AG2-637 GEN
Solar/Wind Harmer
14.095
24690905MDL-1G C
Solar/Wind Harmer
0.003
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0.001
270543AE2-219 C
Solar/Wind Harmer
0.006
971609AH1-304 GEN
Solar/Wind Harmer
1.526
270432AC2-029 GEN
Solar/Wind Harmer
4.141
944221AF1-090 GEN
Solar/Wind Harmer
5.475
965101AG1-375 GEN
Solar/Wind Harmer
9.315
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.339
276848AB2-070 GEN3
Solar/Wind Harmer
0.337
971611AH1-305 GEN
Solar/Wind Harmer
5.525
958391AF2-133 GEN
Solar/Wind Harmer
0.001
276655WTG1_EQ
Solar/Wind Harmer
0.004
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
9.696
24729505KEY G4
Adder
8.586
941731AE2-173 GEN
Solar/Wind Harmer
7.695
966391AG1-508 GEN
Solar/Wind Harmer
1.427
970169AG2-114 GEN
Solar/Wind Harmer
9.2
274863CRW1-WTG
Solar/Wind Harmer
0.003
274864CRW2-WTG
Solar/Wind Harmer
0.003
241972AD1-140 GEN
Solar/Wind Harmer
1.003
274848CAMPGROVE;RU
Solar/Wind Harmer
0.002
957751AF2-069 GEN
Solar/Wind Harmer
0.302
270536AF1-215 GEN2
Solar/Wind Harmer
0.011
926823AC1-168 GEN
Solar/Wind Harmer
1.557
276868AE1-113 GEN
Solar/Wind Harmer
1.835
276882AE2-255 GEN
Solar/Wind Harmer
1.069
274775LINCOLN ;6U
Adder
11.055
274776LINCOLN ;7U
Adder
11.055
274777LINCOLN ;8U
Adder
11.055
970833AG2-524 GEN
Solar/Wind Harmer
10.052
970833AG2-524 GEN
Solar/Wind Harmer
6.701
274746AC1-111 G10
Adder
7.316
274729ELWOOD EC;1P
Adder
21.509
237048AF1-022 C
Solar/Wind Helper
0.228
237043AE2-125 C
Solar/Wind Helper
0.207
235058AG1-386 C
Solar/Wind Helper
0.514
964991AG1-363 GEN
Solar/Wind Helper
4.415
23750701CROSSCHOOL
Solar/Wind Helper
1.427
238118U2-030_1
Solar/Wind Helper
0.343
202652Y1-033 WT C
Solar/Wind Helper
0.655
20089126CSLMN_L13
Solar/Wind Helper
0.683
20089026BF_G21_K23
Solar/Wind Helper
0.541
238127S14_GEN_2
Solar/Wind Helper
0.81
254305AE2-115 C
Solar/Wind Helper
0.239
203818AF1-086 GEN
Solar/Wind Helper
1.887
203854AF2-039 C
Solar/Wind Helper
0.354
20334926Z1-069 C
Solar/Wind Helper
1.49
238202AE2-262_GEN
Solar/Wind Helper
1.063
941421AE2-139 GEN
Solar/Wind Helper
2.573
959441AF2-235 GEN
Solar/Wind Helper
0.255
200917MEHOOPANY_G
Solar/Wind Helper
2.428
209071AE2-133 GEN
Solar/Wind Helper
0.09
946731AF1-337 GEN
Solar/Wind Helper
0.5
212507AE2-042_GEN
Solar/Wind Helper
1.772
961341AF2-425 GEN
Solar/Wind Helper
0.499
212266LOR1
Solar/Wind Helper
0.054
961301AF2-421 GEN
Solar/Wind Helper
0.496
963151AG1-164 GEN
Solar/Wind Helper
0.496
316097T157 G90
Solar/Wind Helper
1.154
203830AF1-094 GEN
Solar/Wind Helper
0.495
20671928W4-073
Solar/Wind Helper
0.098
207518AF1-320_GEN
Solar/Wind Helper
1.718
207437AD2-070 GEN
Solar/Wind Helper
0.15
20675828AU_W4-064
Solar/Wind Helper
0.032
207439AE1-081 C O1
Solar/Wind Helper
0.02
20674328GAR_V4-001
Solar/Wind Helper
0.024
217208PARK ELE C
Solar/Wind Helper
0.005
217209CENTRL HS C
Solar/Wind Helper
0.009
20676428JCR_X2-075
Solar/Wind Helper
0.073
207528AF2-192 GEN
Solar/Wind Helper
0.082
20673628F1S_V4-069
Solar/Wind Helper
0.032
20675428EAM_W2-061
Solar/Wind Helper
0.017
962511AG1-100 GEN
Solar/Wind Helper
0.488
217213AMBOY SO C
Solar/Wind Helper
0.031
218428ETC SOLAR C
Solar/Wind Helper
0.005
205941AD2-115 GEN
Solar/Wind Helper
0.531
24686505CER G6
Adder
15.608
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
970947AG2-589 GEN
Solar/Wind Harmer
0.412
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
971403AH1-188 GEN
Solar/Wind Harmer
16.785
962761AG1-125 GEN
Solar/Wind Harmer
46.194
970149AG2-104 GEN
Solar/Wind Harmer
49.891
970155AG2-107 GEN
Solar/Wind Harmer
29.498
971315AH1-136 GEN
Solar/Wind Harmer
2.232
927014AC1-188 GEN
Solar/Wind Harmer
0.007
971687AH1-348 GEN
Solar/Wind Harmer
1.067
24728305BUCHG2
Adder
6.831
970333AG2-219 GEN
Solar/Wind Harmer
7.406
970091AG2-072 GEN
Adder
113.581
945681AF1-233 GEN
Solar/Wind Harmer
19.197
252507AC2-088 GEN
Solar/Wind Harmer
0.46
25196808ZIMRHP
Adder
109.116
339216AC1-074 GEN
Solar/Wind Harmer
0.274
25196008MFTGT1
Adder
1.989
25194608D.CRK4
Adder
2.348
3429241JKCT 3G
Adder
16.894
3429421JKCT 10G
Adder
11.865
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
9.904
270263AC1-001 GEN
Solar/Wind Harmer
0.987
270445AC2-157 GEN2
Solar/Wind Harmer
0.004
971565AH1-281 GEN
Solar/Wind Harmer
1.958
971821AH1-427 GEN
Solar/Wind Harmer
9.786
24735205WLF2G2
Adder
8.08
970773AG2-487 GEN
Solar/Wind Harmer
1.7
24728605AND G2
Adder
5.27
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0.001
970613AG2-401 GEN
Solar/Wind Harmer
6.984
253370AE2-315 SEC1
Adder
2.733
253371AE2-315 SEC2
Adder
2.585
970273AG2-179 GEN
Solar/Wind Harmer
3.322
276903AD2-071 C
Solar/Wind Harmer
10.574
963741AG1-226 GEN
Solar/Wind Harmer
22.385
970291AG2-192 GEN
Solar/Wind Harmer
1.228
270005AE1-210 C O1
Solar/Wind Harmer
2.046
965031AG1-367 GEN
Solar/Wind Harmer
9.442
270032AE2-172
Solar/Wind Harmer
6.293
25326309TAIT D
Adder
1.481
964901AG1-354 GEN
Solar/Wind Harmer
14.138
960071AF2-298 GEN
Solar/Wind Harmer
4.694
970825AG2-519 GEN
Solar/Wind Harmer
3.343
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.004
24791305MDL-5G
Solar/Wind Harmer
0.001
970245AG2-165 GEN
Solar/Wind Harmer
4.056
962241AG1-070 GEN
Solar/Wind Harmer
5.098
945371AF1-202 GEN
Solar/Wind Harmer
0.001
958861AF2-177 GEN
Solar/Wind Harmer
4.037
965911AG1-460 GEN
Solar/Wind Harmer
1.861
247536S-71 GEN
Solar/Wind Harmer
0.374
965651AG1-433 GEN
Solar/Wind Harmer
2.727
276615X2-022 GEN
Solar/Wind Harmer
0.098
963831AG1-236 GEN
Solar/Wind Harmer
3.623
274880W4-005 GEN4
Solar/Wind Harmer
0.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
11.601
972175AH1-670 GEN
Solar/Wind Harmer
7.662
274854TWINGROVE;U2
Solar/Wind Harmer
0.004
276726Z2-087_GEN
Solar/Wind Harmer
0.003
939741AE1-205 GEN
Solar/Wind Harmer
12.928
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
11.983
958381AF2-132 GEN
Solar/Wind Harmer
0.001
939401AE1-172 GEN
Solar/Wind Harmer
6.864
270055AF2-134 C O1
Solar/Wind Harmer
0.007
274877BISHOP HL;1U
Solar/Wind Harmer
0.308
253343AC1-166 GEN
Solar/Wind Harmer
0.004
253325AC1-069 GEN
Solar/Wind Harmer
0.014
970569AG2-363 GEN
Solar/Wind Harmer
27.46
971997AH1-543 GEN
Solar/Wind Harmer
4.802
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
276901AD2-066 C O1
Solar/Wind Harmer
0.009
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274773LINCOLN ;4U
Adder
11.055
274774LINCOLN ;5U
Adder
11.055
276158O29GEN2
Solar/Wind Harmer
0.001
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
276691AA1-018 GEN1
Solar/Wind Harmer
1.106
274745AC1-111 GEN9
Adder
7.316
276861AD2-134 GEN
Solar/Wind Harmer
0.164
274872LEEDK;1U
Solar/Wind Harmer
0.006
274761LEE CO EC;2U
Adder
12.175
274766LEE CO EC;7U
Adder
12.032
237046AF1-021 C
Solar/Wind Helper
0.577
238185AF2-356 C
Solar/Wind Helper
2.612
23751201ROTHROCK
Solar/Wind Helper
0.878
235054AD2-180 GEN
Solar/Wind Helper
2.032
23562501BACKB
Solar/Wind Helper
1.07
238117U2-030
Solar/Wind Helper
0.343
235531U2-073 GEN
Solar/Wind Helper
3.23
20089226LOOKOUT
Solar/Wind Helper
0.665
254303AC2-168 GEN
Solar/Wind Helper
0.173
241966AE1-183 GEN
Solar/Wind Helper
0.28
23751101LEADS_P59
Solar/Wind Helper
1.483
20088826HIGHLAND
Solar/Wind Helper
1.011
20094526CT_V3-030
Solar/Wind Helper
0.53
964201AG1-281 GEN
Solar/Wind Helper
0.544
238108AE1-109 GEN1
Solar/Wind Helper
0.102
964391AG1-301 GEN
Solar/Wind Helper
0.529
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
270599AE1-208 GEN
Solar/Wind Harmer
8.564
270031AE2-169
Solar/Wind Harmer
5.138
276916AD2-100_GEN
Solar/Wind Harmer
19.555
276911AD2-131_GEN
Solar/Wind Harmer
1.288
944541AF1-119 GEN
Solar/Wind Harmer
0.623
960971AF2-388 GEN
Solar/Wind Harmer
5.453
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
0.696
247621Y3-024
Adder
0.32
960611AF2-352 GEN
Solar/Wind Harmer
3.082
270201AC2-176 GEN
Solar/Wind Harmer
0.002
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.36
276646AC1-214 GEN2
Solar/Wind Harmer
0.36
276782AC1-033 GEN
Solar/Wind Harmer
0.001
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
274879MINONK ;1U
Solar/Wind Harmer
0.386
274770LINCOLN ;1U
Adder
11.055
274771LINCOLN ;2U
Adder
11.055
276741O09 GEN1
Solar/Wind Harmer
0.325
276708O09 GEN2
Solar/Wind Harmer
0.325
958491AF2-143 GEN
Solar/Wind Harmer
13.709
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
1.236
972259AH1-714 GEN
Adder
24.976
958481AF2-142 GEN
Solar/Wind Harmer
13.701
971573AH1-285 GEN
Solar/Wind Harmer
1.702
276603SUBLETTE C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
5.45
274696ROCKY RD ;4P
Adder
14.914
274695ROCKY RD ;2P
Adder
14.57
274693ROCKY RD ;1P
Adder
14.427
274764LEE CO EC;5U
Adder
12.204
274765LEE CO EC;6U
Adder
12.204
274762LEE CO EC;3U
Adder
12.175
274763LEE CO EC;4U
Adder
12.06
274697ROCKY RD ;3P
Adder
3.958
23652301WDPWR_K20
Solar/Wind Helper
0.168
23585401KL_K28_T16
Solar/Wind Helper
1.53
203955AF1-039 C O1
Solar/Wind Helper
0.432
944781AF1-143 GEN
Solar/Wind Helper
2.836
238120AE2-309 GEN
Solar/Wind Helper
0.507
962101AG1-054 GEN
Solar/Wind Helper
0.715
20083426SW_E13_K22
Solar/Wind Helper
0.064
241985AE1-237 GEN
Solar/Wind Helper
0.271
241967AE2-285_GEN
Solar/Wind Helper
0.696
241801AE1-079 GEN
Solar/Wind Helper
0.271
20088926STNY CRK
Solar/Wind Helper
0.928
946071AF1-272 GEN
Solar/Wind Helper
3.051
20084626FORWARD
Solar/Wind Helper
0.402
203940AF1-140 C
Solar/Wind Helper
0.446
20088626ARWF_N39
Solar/Wind Helper
1.362
20303426NA_O38_P22
Solar/Wind Helper
1.117
203853AF1-134 C O1
Solar/Wind Helper
0.534
946381AF1-302 GEN
Solar/Wind Helper
0.246
203952AE2-129 C
Solar/Wind Helper
0.529
203946AE2-131 C
Solar/Wind Helper
0.53
238217AF1-153 C O1
Solar/Wind Helper
0.262
20398826ARMNA MT
Solar/Wind Helper
1.656
209137AF2-361 C
Solar/Wind Helper
1.531
946751AF1-339 GEN
Solar/Wind Helper
0.5
209054AE2-059 GEN
Solar/Wind Helper
0.09
961431AF2-434 GEN
Solar/Wind Helper
0.499
208972BECR K09
Solar/Wind Helper
0.372
209029WAYMART-WD
Solar/Wind Helper
0.937
203979AG1-198 GEN
Solar/Wind Helper
0.297
211065PSPA IPP
Solar/Wind Helper
0.168
211065PSPA IPP
Solar/Wind Helper
0.168
203980AG1-197 GEN
Solar/Wind Helper
0.369
966111AG1-480 GEN
Solar/Wind Helper
0.082
20674128FR_U2-059
Solar/Wind Helper
0.004
964851AG1-348 GEN
Solar/Wind Helper
0.088
207471AF2-354 C
Solar/Wind Helper
0.184
20674928WA_W3-044
Solar/Wind Helper
0.107
20676228FRD_X1-012
Solar/Wind Helper
0.1
217204WCALDSOLAR C
Solar/Wind Helper
0.003
20742028HF_AC1-207
Solar/Wind Helper
0.15
20715228NPK_W1-113
Solar/Wind Helper
0.083
207454AA2-184 E
Solar/Wind Helper
0.331
219680HOPEWELLV C1
Solar/Wind Helper
0.003
963711AG1-223 GEN
Solar/Wind Helper
0.068
20714828MDF_W3-079
Solar/Wind Helper
0.139
207445AB1-138_GEN
Solar/Wind Helper
0.111
20720728JCB_W1-129
Solar/Wind Helper
0.061
219304NAMERICA C
Solar/Wind Helper
0.139
219686LUMSOLAR_N C
Solar/Wind Helper
0.042
219907AC1-030 C
Solar/Wind Helper
0.036
218660EHAMPSOLAR C
Solar/Wind Helper
0.035
219904AC1-010 C
Solar/Wind Helper
0.064
219258KINSLEYDEP C
Solar/Wind Helper
0.081
228728W1-130C
Solar/Wind Helper
0.057
230434AG1-499 GEN
Solar/Wind Helper
0.241
230511AF1-262
Solar/Wind Helper
0.015
233972AC1-094 C
Solar/Wind Helper
0.312
233998TM1NIN_3.36
Solar/Wind Helper
0.27
233954AC2-188 GEN
Solar/Wind Helper
0.24
232404W1-003 C
Solar/Wind Helper
0.523
233950AC2-186 GEN
Solar/Wind Helper
0.12
232428Y3-058 C
Solar/Wind Helper
0.349
232434Z2-077 GEN
Solar/Wind Helper
0.131
232426Y1-080 FULL
Solar/Wind Helper
0.04
233964AF2-378 GEN
Solar/Wind Helper
0.043
232422X3-066 FULL
Solar/Wind Helper
0.118
233930AB2-032 GEN
Solar/Wind Helper
0.392
233915AB1-141 GEN
Solar/Wind Helper
0.518
966131AG1-482 GEN
Solar/Wind Helper
0.139
235062AE1-101 C1
Solar/Wind Helper
1.463
237038AE2-054 C
Solar/Wind Helper
0.238
237080AD1-060 GEN
Solar/Wind Helper
0.296
23779801AA1-109
Solar/Wind Helper
0.168
223401AF1-299 GEN
Solar/Wind Helper
0.338
959091AF2-200 GEN
Solar/Wind Harmer
3.998
203954AE2-126 C
Solar/Wind Helper
0.522
238206AE2-263_GEN
Solar/Wind Helper
1.011
959471AF2-238 GEN
Solar/Wind Helper
0.517
203860AG1-193 C
Solar/Wind Helper
0.254
209067AE2-060 GEN
Solar/Wind Helper
0.091
946691AF1-333 GEN
Solar/Wind Helper
0.5
946741AF1-338 GEN
Solar/Wind Helper
0.5
961421AF2-433 GEN
Solar/Wind Helper
0.499
957921AF2-086 GEN
Solar/Wind Helper
0.493
961331AF2-424 GEN
Solar/Wind Helper
0.499
209027LOR2_Q27
Solar/Wind Helper
1.165
963071AG1-156 GEN
Solar/Wind Helper
1.625
963161AG1-165 GEN
Solar/Wind Helper
0.496
316095T157 G97
Solar/Wind Helper
1.154
23583801GRNGAP
Solar/Wind Helper
4.282
961971AG1-040 GEN
Solar/Wind Helper
0.492
203835AF1-098 GEN
Solar/Wind Helper
1.958
20674628WNG_W3-110
Solar/Wind Helper
0.097
207510AF2-138 C
Solar/Wind Helper
0.088
20676728BRNX1-095
Solar/Wind Helper
0.032
217169METRODIV C
Solar/Wind Helper
0.004
217211CAMDEN ST C
Solar/Wind Helper
0.005
20673728F2S_V4-070
Solar/Wind Helper
0.032
219249CENTRALDIV C
Solar/Wind Helper
0.011
219908AB1-139 C
Solar/Wind Helper
0.079
219919AE1-041 FULL
Solar/Wind Helper
0.004
218438BLK ROCK C
Solar/Wind Helper
0.029
274744AC1-111 GEN8
Adder
7.316
961011AF2-392 GEN
Solar/Wind Harmer
5.358
971675AH1-338 GEN
Solar/Wind Harmer
3.562
274731ELWOOD EC;2P
Adder
21.509
274733ELWOOD EC;3P
Adder
13.442
23750501ELLIOTTS
Solar/Wind Helper
0.788
238126S14_GEN_1
Solar/Wind Helper
0.81
254304AE2-114 C
Solar/Wind Helper
0.239
241997AF1-093 GEN
Solar/Wind Helper
0.28
241982AE2-343 S C
Solar/Wind Helper
0.243
20092526R32
Solar/Wind Helper
1.311
203961AE2-224 GEN
Solar/Wind Helper
2.707
20091526CHSTN_FL
Solar/Wind Helper
0.654
238109AE1-109 GEN2
Solar/Wind Helper
0.102
238110AE1-109 GEN3
Solar/Wind Helper
0.102
20090526Q36
Solar/Wind Helper
1.167
203993AD2-133_GEN1
Solar/Wind Helper
1.167
941231AE2-117 GEN
Solar/Wind Helper
0.53
203846AF2-130 C
Solar/Wind Helper
0.497
203855AF2-088 C
Solar/Wind Helper
0.17
203804AE2-113_GEN
Solar/Wind Helper
1.924
959431AF2-234 GEN
Solar/Wind Helper
1
964051AG1-259 GEN
Solar/Wind Helper
0.075
964061AG1-260 GEN
Solar/Wind Helper
0.075
959421AF2-233 GEN
Solar/Wind Helper
0.5
961261AF2-417 GEN
Solar/Wind Helper
0.495
209116AE2-175 GEN
Solar/Wind Helper
1.966
20675128HRM_W1-127
Solar/Wind Helper
0.032
207408W3-077 C
Solar/Wind Helper
0.092
20675728RH_W2-091
Solar/Wind Helper
0.149
207484AF2-139 C O1
Solar/Wind Helper
0.092
203975AE1-071-GEN
Solar/Wind Helper
2.674
20674828DL_W4-046
Solar/Wind Helper
0.008
20675928HOL_W4-097
Solar/Wind Helper
0.055
20676328BVR_Y1-020
Solar/Wind Helper
0.029
238208AF1-136 C
Solar/Wind Helper
0.192
207530AG1-191 GEN
Solar/Wind Helper
0.072
966261AG1-495 GEN
Solar/Wind Helper
0.088
218524CNTRALGAS1 C
Solar/Wind Helper
0.173
20675528CPH_W2-050
Solar/Wind Helper
0.093
218526CNTRALGAS2 C
Solar/Wind Helper
0.173
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217081WEATEXAS C
Solar/Wind Helper
0.014
20671828STAW2-080
Solar/Wind Helper
0.029
207442AE1-156 GEN
Solar/Wind Helper
0.351
20676128MHD_W3-029
Solar/Wind Helper
0.103
20673828FLE_V3-070
Solar/Wind Helper
0.097
218440SUMMTASSOC C
Solar/Wind Helper
0.018
20716928W4-060COL
Solar/Wind Helper
0.055
20720628TIN_W1-124
Solar/Wind Helper
0.203
963391AG1-188 GEN
Solar/Wind Helper
0.088
20714928UPF_X1-085
Solar/Wind Helper
0.005
963401AG1-189 GEN
Solar/Wind Helper
0.06
20390526W1-045 C
Solar/Wind Helper
0.357
219615MILLCREEK C
Solar/Wind Helper
0.028
219921AF1-264
Solar/Wind Helper
0.054
203947AF1-006 C
Solar/Wind Helper
0.527
230407AD2-065 C
Solar/Wind Helper
0.042
230433AD2-135 GEN
Solar/Wind Helper
0.018
233939AC1-091 C
Solar/Wind Helper
0.361
233970AC1-092 C
Solar/Wind Helper
0.361
233901CHERRYDALE C
Solar/Wind Helper
0.24
232408W1-005 C
Solar/Wind Helper
0.523
232410W1-006 C
Solar/Wind Helper
0.523
233946AB2-136 GEN
Solar/Wind Helper
0.586
234036AF2-325 C
Solar/Wind Helper
0.043
233987AB2-037 GEN
Solar/Wind Helper
2.415
233944AB2-135 GEN
Solar/Wind Helper
0.607
232424Y1-079 C
Solar/Wind Helper
0.12
233933AB2-153 GEN
Solar/Wind Helper
0.24
235063AE1-101 C2
Solar/Wind Helper
1.463
205916AD1-020 GEN
Solar/Wind Helper
1.711
237002AB1-128_GEN
Solar/Wind Helper
0.388
237001AB1-127_GEN
Solar/Wind Helper
0.388
235020AA1-095 C
Solar/Wind Helper
0.045
23777901MDS_W4-102
Solar/Wind Helper
0.15
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
237034AC2-136 C
Solar/Wind Helper
0.194
238175AF1-290_GEN
Solar/Wind Helper
0.123
237025AB1-124 C
Solar/Wind Helper
0.145
237006AB1-125 GEN
Solar/Wind Helper
0.109
23777801MSM_W1-116
Solar/Wind Helper
0.1
238169AE2-226 GEN1
Solar/Wind Helper
0.555
238170AE2-226 GEN2
Solar/Wind Helper
0.555
971341AH1-150 GEN
Solar/Wind Harmer
3.998
971343AH1-151 GEN
Solar/Wind Harmer
3.998
219612MATRIX C
Solar/Wind Helper
0.025
20720528MAN_W1-024
Solar/Wind Helper
0.03
20714528FRN_Y2-051
Solar/Wind Helper
0.061
219276PARKLANDSO C
Solar/Wind Helper
0.095
20720828JCB_W4-025
Solar/Wind Helper
0.067
20715028HAN_X4-015
Solar/Wind Helper
0.061
20716028EGP_W2-019
Solar/Wind Helper
0.02
959561AF2-247 GEN
Solar/Wind Helper
0.022
219348LDSOLAR C
Solar/Wind Helper
0.121
219906AC1-017 C
Solar/Wind Helper
0.044
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219291REEVESSOUT C
Solar/Wind Helper
0.012
219912AD2-042 GEN
Solar/Wind Helper
0.158
219766PARADISE C
Solar/Wind Helper
0.057
219623KINSLEYBEA C
Solar/Wind Helper
0.002
228729W2-030 C
Solar/Wind Helper
0.116
230415AB2-049 C
Solar/Wind Helper
0.032
230430AE1-229_GEN
Solar/Wind Helper
3.539
233971AC1-093 C
Solar/Wind Helper
0.369
233996TM1833_GEN
Solar/Wind Helper
0.27
233997TMININ_4.2
Solar/Wind Helper
0.27
233952AC2-187 GEN
Solar/Wind Helper
0.24
232406W1-004 FULL
Solar/Wind Helper
0.523
233940AF2-379 C
Solar/Wind Helper
0.064
234015AF2-250 C
Solar/Wind Helper
0.039
233994AC2-023 GEN
Solar/Wind Helper
0.992
233982AB2-133 GEN
Solar/Wind Helper
0.369
233918AB1-142 GEN
Solar/Wind Helper
0.518
235067AD1-061 GEN
Solar/Wind Helper
0.433
205917AD1-020 ES
Solar/Wind Helper
0.368
238221AF1-254 C O1
Solar/Wind Helper
0.236
237030AB1-096 C
Solar/Wind Helper
0.063
223402AF1-300 C
Solar/Wind Helper
0.338
957471AF2-041 GEN
Solar/Wind Harmer
5.997
959081AF2-199 GEN
Solar/Wind Harmer
1.999
971067AG2-660 GEN
Solar/Wind Harmer
0.666
219620RIDERU C
Solar/Wind Helper
0.001
207459AE1-142 C O1
Solar/Wind Helper
0.309
20715728PEM_W1-119
Solar/Wind Helper
0.102
20715828PEM_W1-120
Solar/Wind Helper
0.102
214067T20SOLAR
Solar/Wind Helper
0.012
959381AF2-229 GEN
Solar/Wind Helper
0.364
219607WPEMNERT C
Solar/Wind Helper
0.085
219688LUMSOLAR_S C
Solar/Wind Helper
0.042
219272CLEANLIGHT C
Solar/Wind Helper
0.027
219914AD2-027 C
Solar/Wind Helper
0.121
227927V4-067C
Solar/Wind Helper
0.011
228754AB1-001 C
Solar/Wind Helper
0.027
964001AG1-254 GEN
Solar/Wind Helper
1.003
234033AF1-007_GEN
Solar/Wind Helper
7.245
233923SMA
Solar/Wind Helper
0.989
233990AG1-397 GEN
Solar/Wind Helper
0.279
232432Z2-076 GEN
Solar/Wind Helper
0.069
237085AD2-009_GEN
Solar/Wind Helper
1.449
205932AD2-116_GEN
Solar/Wind Helper
0.523
205956AE1-196_GEN
Solar/Wind Helper
0.523
205943AE1-185 GEN
Solar/Wind Helper
0.523
232436AB1-176 C
Solar/Wind Helper
0.046
233935AB2-179 C
Solar/Wind Helper
1.307
960921AF2-383 GEN
Solar/Wind Helper
0.373
971171AH1-044 GEN
Solar/Wind Harmer
3.998
944201AF1-088_MTX
Adder
163.563
957141AF2-008_MTX
Adder
81.782
CPLELTFEXP_CPLE->PJM
CLTF
6.557
CBM West 2LTFEXP_CBM-W2->PJM
CBM
173.156
LAGNLTFEXP_LAGN->PJM
CLTF
24.864
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.24
TVALTFEXP_TVA->PJM
CLTF
12.63
NYPJM->LTFIMP_NY
CLTF
6.276
LGEELTFEXP_LGEE->PJM
CLTF
9.844
WECLTFEXP_WEC->PJM
CLTF
5.002
AG2-052LTFEXP_AG2-052->PJM
LTF
0.306
AH1-155LTFEXP_AH1-155->PJM
LTF
0.459
CBM West 1LTFEXP_CBM-W1->PJM
CBM
170.264
CBM South 1LTFEXP_CBM-S1->PJM
CBM
48.581
MECLTFEXP_MEC->PJM
CLTF
21.939
SIGELTFEXP_SIGE->PJM
CLTF
0.729

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7445_05MARYSV 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.05 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6243.53
MW Contribution:9.11
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
3.32
962771AG1-126 GEN
Solar/Wind Harmer
91.898
972203AH1-686 GEN
Adder
4.552
24477305BRIDGE
Adder
0.636
957241AF2-018 GEN
Solar/Wind Harmer
8.055
270399AC1-101 GEN
Solar/Wind Harmer
7.605
270400AC1-102 GEN
Solar/Wind Harmer
7.605
270330AC1-082 GEN2
Solar/Wind Harmer
1.366
270329AC1-082 GEN1
Solar/Wind Harmer
0.805
941621AE2-160 GEN
Adder
5.471
971313AH1-133 GEN
Solar/Wind Harmer
15.802
970281AG2-184 GEN
Solar/Wind Harmer
32.56
972143AH1-644 GEN
Solar/Wind Harmer
15.505
270132AB1-180 C
Adder
0.187
971061AG2-657 GEN
Solar/Wind Harmer
13.568
24734705WLF1G3
Adder
8.349
24734805WLF1G4
Adder
8.349
24734905WLF1G5
Adder
8.349
962211AG1-066 GEN
Solar/Wind Harmer
3.499
966391AG1-508 GEN
Solar/Wind Harmer
4.988
24735105WLF2G1
Adder
8.16
971985AH1-537 GEN
Solar/Wind Harmer
23.222
971981AH1-535 GEN
Solar/Wind Harmer
12.796
270069AE2-166 C O1
Solar/Wind Harmer
3.217
965401AG1-405 GEN
Solar/Wind Harmer
6.573
965411AG1-406 GEN
Solar/Wind Harmer
2.95
339211AE2-254 GEN
Solar/Wind Harmer
1.711
970879AG2-548 GEN
Solar/Wind Harmer
4.825
3429211JKCT 2G
Adder
13.038
970455AG2-298 GEN
Solar/Wind Harmer
6.646
972163AH1-664 GEN
Solar/Wind Harmer
10.872
972165AH1-665 GEN
Solar/Wind Harmer
8.697
270367AC2-061_GEN
Solar/Wind Harmer
3.448
339243AC2-075 GEN1
Solar/Wind Harmer
0.493
25196108MFTGT2
Adder
1.552
25196108MFTGT2
Adder
1.441
944221AF1-090 GEN
Solar/Wind Harmer
10.676
252524AE2-267 GEN
Solar/Wind Harmer
1.53
25196408WSDLE3
Adder
8.556
25196308WSDLE2
Adder
8.482
25196208WSDLE1
Adder
8.46
25196708WSDLE6
Adder
8.439
25196508WSDLE4
Adder
8.227
963841AG1-237 GEN
Solar/Wind Harmer
10.394
274823ROCKFORD ;21
Adder
17.536
274746AC1-111 G10
Adder
4.954
274744AC1-111 GEN8
Adder
4.954
274731ELWOOD EC;2P
Adder
14.499
274733ELWOOD EC;3P
Adder
10.298
23750501ELLIOTTS
Solar/Wind Helper
0.613
254304AE2-114 C
Solar/Wind Helper
0.199
241997AF1-093 GEN
Solar/Wind Helper
0.233
241982AE2-343 S C
Solar/Wind Helper
0.203
243186AF1-051 GEN
50/50
14.281
24723005RIVRG1
Adder
37.861
24723105RIVRG2
Adder
37.861
24685805CER G1
Adder
16.07
24685905CER G2
Adder
16.07
944971AF1-162 GEN
Solar/Wind Harmer
12.689
24728205BUCHG1
Adder
7.204
971225AH1-072 GEN
Solar/Wind Harmer
3.087
971227AH1-073 GEN
Solar/Wind Harmer
3.087
270214AC2-123 GEN
Solar/Wind Harmer
3.357
971277AH1-098 GEN
Solar/Wind Harmer
5.729
270583AD2-179 GEN
Solar/Wind Harmer
13.373
960161AF2-307 GEN
Solar/Wind Harmer
7.621
970239AG2-162 GEN
Solar/Wind Harmer
12.849
966021AG1-471 GEN
Solar/Wind Harmer
6.166
339231AF1-038_GEN
Solar/Wind Harmer
2.069
971485AH1-239 GEN
Solar/Wind Harmer
9.113
970879AG2-548 GEN
Solar/Wind Harmer
6.915
971073AG2-665 GEN
Solar/Wind Harmer
6.915
971073AG2-665 GEN
Solar/Wind Harmer
4.825
942891AE2-308 GEN
Solar/Wind Harmer
11.21
971081AG2-670 GEN
Solar/Wind Harmer
8.401
339236AF1-050_GEN
Solar/Wind Harmer
2.029
339255AE2-071 GEN
Solar/Wind Harmer
1.185
964781AG1-341 GEN
Solar/Wind Harmer
11.836
970653AG2-424 GEN
Solar/Wind Harmer
5.35
970653AG2-424 GEN
Solar/Wind Harmer
1.934
964571AG1-320 GEN
Solar/Wind Harmer
9.018
972043AH1-570 GEN
Solar/Wind Harmer
2.743
972045AH1-571 GEN
Solar/Wind Harmer
2.195
971125AH1-004 GEN
Solar/Wind Harmer
4.377
970107AG2-081 GEN
Solar/Wind Harmer
3.283
270186AC1-089 GEN
Solar/Wind Harmer
6.681
339221AD2-048_GEN
Solar/Wind Harmer
1.68
970235AG2-159 GEN
Solar/Wind Harmer
4.336
970235AG2-159 GEN
Solar/Wind Harmer
2.647
270444AC2-157 GEN1
Solar/Wind Harmer
5.954
962581AG1-107 GEN
Solar/Wind Harmer
5.324
961491AF2-440 GEN
Solar/Wind Harmer
2.213
252509AD1-136 GEN
Solar/Wind Harmer
0.262
945391AF1-204 GEN
Solar/Wind Harmer
13.769
252519AF1-045_GEN
Solar/Wind Harmer
5.968
252516AE2-318_GEN
Solar/Wind Harmer
4.552
25183208HLCRTG
Solar/Wind Harmer
5.931
25194408D.CRK1
Adder
7.379
25194508D.CRK3
Adder
1.38
276916AD2-100_GEN
Solar/Wind Harmer
20.308
276911AD2-131_GEN
Solar/Wind Harmer
4.104
957381AF2-032 GEN
Solar/Wind Harmer
0.403
970241AG2-163 GEN
Solar/Wind Harmer
23.985
276763AC1-053 GEN1
Solar/Wind Harmer
3.755
276764AC1-053 GEN2
Solar/Wind Harmer
3.755
24728805RICHG1
Adder
3.448
24728905RICHG2
Adder
3.448
972267AH1-718 GEN
Adder
3.785
274764LEE CO EC;5U
Adder
8.446
274765LEE CO EC;6U
Adder
8.446
274762LEE CO EC;3U
Adder
8.426
274763LEE CO EC;4U
Adder
8.346
274683WAUKEGAN ;8U
Adder
18.761
274683WAUKEGAN ;8U
Adder
15.814
274696ROCKY RD ;4P
Adder
10.143
274695ROCKY RD ;2P
Adder
9.908
274693ROCKY RD ;1P
Adder
9.811
274697ROCKY RD ;3P
Adder
2.692
23652301WDPWR_K20
Solar/Wind Helper
0.133
962101AG1-054 GEN
Solar/Wind Helper
0.594
241967AE2-285_GEN
Solar/Wind Helper
0.583
241801AE1-079 GEN
Solar/Wind Helper
0.227
241985AE1-237 GEN
Solar/Wind Helper
0.227
23585401KL_K28_T16
Solar/Wind Helper
1.167
203955AF1-039 C O1
Solar/Wind Helper
0.335
944781AF1-143 GEN
Solar/Wind Helper
2.213
24289405MTG1
50/50
12.693
24721805FLATG3
50/50
3.32
24721705FLATG2
50/50
60.871
243186AF1-051 GEN
50/50
14.281
24318705GVG2
50/50
13.293
962761AG1-125 GEN
Solar/Wind Harmer
91.898
970149AG2-104 GEN
Solar/Wind Harmer
113.494
970155AG2-107 GEN
Solar/Wind Harmer
40.072
24723205RIVRG3
Adder
37.861
24686105CER G3
Adder
16.176
24686505CER G6
Adder
16.155
971403AH1-188 GEN
Solar/Wind Harmer
25.361
270331AC1-082 GEN3
Solar/Wind Harmer
0.807
970947AG2-589 GEN
Solar/Wind Harmer
3.533
960001AF2-291 GEN
Solar/Wind Harmer
5.186
24728305BUCHG2
Adder
7.204
971687AH1-348 GEN
Solar/Wind Harmer
1.543
971315AH1-136 GEN
Solar/Wind Harmer
3.067
24735205WLF2G2
Adder
8.16
971329AH1-144 GEN
Solar/Wind Harmer
16.634
927014AC1-188 GEN
Solar/Wind Harmer
2.118
270336AE1-100 GEN
Solar/Wind Harmer
2.043
970091AG2-072 GEN
Adder
90.557
970333AG2-219 GEN
Solar/Wind Harmer
36.87
971367AH1-164 GEN
Solar/Wind Harmer
3.994
970273AG2-179 GEN
Solar/Wind Harmer
2.784
971821AH1-427 GEN
Solar/Wind Harmer
11.315
943811AF1-049 GEN
Solar/Wind Harmer
4.273
339241AF1-083 GEN
Solar/Wind Harmer
1.864
964901AG1-354 GEN
Solar/Wind Harmer
16.766
3429241JKCT 3G
Adder
13.209
962241AG1-070 GEN
Solar/Wind Harmer
5.006
971565AH1-281 GEN
Solar/Wind Harmer
2.213
3429421JKCT 10G
Adder
9.194
943111AE2-339 GEN
Solar/Wind Harmer
0.969
339216AC1-074 GEN
Solar/Wind Harmer
1.819
945681AF1-233 GEN
Solar/Wind Harmer
20.401
270445AC2-157 GEN2
Solar/Wind Harmer
5.954
270018AE2-047 C O1
Solar/Wind Harmer
1.277
252507AC2-088 GEN
Solar/Wind Harmer
1.836
25196008MFTGT1
Adder
1.408
25196808ZIMRHP
Adder
76.262
25194608D.CRK4
Adder
1.604
965911AG1-460 GEN
Solar/Wind Harmer
1.345
24728605AND G2
Adder
3.69
963741AG1-226 GEN
Solar/Wind Harmer
43.173
276615X2-022 GEN
Solar/Wind Harmer
1.868
274761LEE CO EC;2U
Adder
8.426
274766LEE CO EC;7U
Adder
8.327
972235AH1-702 GEN1
Adder
2.27
274822ROCKFORD ;11
Adder
17.664
274828WAUKEGAN ;BP
Adder
9.834
274682WAUKEGAN ;7U
Adder
15.992
274745AC1-111 GEN9
Adder
4.954
237046AF1-021 C
Solar/Wind Helper
0.454
254303AC2-168 GEN
Solar/Wind Helper
0.144
241966AE1-183 GEN
Solar/Wind Helper
0.233
238185AF2-356 C
Solar/Wind Helper
1.986
23751201ROTHROCK
Solar/Wind Helper
0.666
235054AD2-180 GEN
Solar/Wind Helper
1.542
23562501BACKB
Solar/Wind Helper
0.81
20089226LOOKOUT
Solar/Wind Helper
0.519
963831AG1-236 GEN
Solar/Wind Harmer
2.691
24289405MTG1
50/50
12.693
24722005FLATG5
50/50
3.32
24721905FLATG4
50/50
60.871
24318705GVG2
50/50
13.293
970153AG2-106 GEN
Solar/Wind Harmer
40.072
24686205CER G4
Adder
16.091
24686405CER G5
Adder
16.028
270053AF1-130 C
Solar/Wind Harmer
6.738
970913AG2-568 GEN
Solar/Wind Harmer
13.608
960911AF2-382 GEN
Solar/Wind Harmer
12.052
972103AH1-617 GEN
Solar/Wind Harmer
31.009
971461AH1-227 GEN
Solar/Wind Harmer
7.917
971191AH1-055 GEN
Solar/Wind Harmer
33.8
270346AE1-212 GEN
Solar/Wind Harmer
13.484
943031AE2-326 GEN
Solar/Wind Harmer
5.284
971331AH1-145 GEN
Solar/Wind Harmer
12.895
247619Y1-049
Adder
0.586
958121AF2-106 GEN
Solar/Wind Harmer
6.061
957541AF2-048 GEN
Solar/Wind Harmer
2.113
970243AG2-164 GEN
Solar/Wind Harmer
30.166
970519AG2-331 GEN
Solar/Wind Harmer
20.267
970699AG2-449 GEN
Solar/Wind Harmer
13.407
972273AH1-721 GEN
Adder
96.475
270030AE2-140 GEN
Solar/Wind Harmer
23.108
970273AG2-179 GEN
Solar/Wind Harmer
4.447
970093AG2-073 GEN
Solar/Wind Harmer
11.307
966571AG1-526 GEN
Solar/Wind Harmer
25.008
339250AF1-203 GEN
Solar/Wind Harmer
0.677
971155AH1-034 GEN
Solar/Wind Harmer
11.167
962251AG1-071 GEN
Solar/Wind Harmer
6.119
960741AF2-365 GEN
Solar/Wind Harmer
5.543
3429391JKCT 9G
Adder
9.194
972167AH1-666 GEN
Solar/Wind Harmer
8.642
958171AF2-111 GEN
Solar/Wind Harmer
25.894
270291AC1-194 GEN
Solar/Wind Harmer
10.843
25196008MFTGT1
Adder
1.363
970193AG2-126 GEN
Solar/Wind Harmer
14.82
252510AF1-249 C
Solar/Wind Harmer
0.411
270173AC1-122 GEN
Solar/Wind Harmer
1.562
25194608D.CRK4
Adder
1.604
25196608WSDLE5
Adder
8.312
942481AE2-261 GEN
Solar/Wind Harmer
28.829
24728705AND G3
Adder
7.718
24728505AND G1
Adder
3.69
962751AG1-124 GEN
Solar/Wind Harmer
8.642
276621W2-048 GEN
Solar/Wind Harmer
5.949
276838X2-022 GEN2
Solar/Wind Harmer
0.222
274760LEE CO EC;1U
Adder
8.426
274767LEE CO EC;8U
Adder
8.327
972236AH1-702 GEN2
Adder
1.974
274682WAUKEGAN ;7U
Adder
15.992
274729ELWOOD EC;1P
Adder
14.499
237048AF1-022 C
Solar/Wind Helper
0.178
235058AG1-386 C
Solar/Wind Helper
0.421
237043AE2-125 C
Solar/Wind Helper
0.164
254305AE2-115 C
Solar/Wind Helper
0.199
202652Y1-033 WT C
Solar/Wind Helper
0.509
23750701CROSSCHOOL
Solar/Wind Helper
1.078
20089126CSLMN_L13
Solar/Wind Helper
0.533
20089026BF_G21_K23
Solar/Wind Helper
0.422
964991AG1-363 GEN
Solar/Wind Helper
3.317
944201AF1-088_MTX
Adder
123.966
957141AF2-008_MTX
Adder
61.983
CPLELTFEXP_CPLE->PJM
CLTF
7.658
CBM West 2LTFEXP_CBM-W2->PJM
CBM
139.058
LAGNLTFEXP_LAGN->PJM
CLTF
21.271
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.975
TVALTFEXP_TVA->PJM
CLTF
11.116
NYPJM->LTFIMP_NY
CLTF
4.768
LGEELTFEXP_LGEE->PJM
CLTF
7.621
WECLTFEXP_WEC->PJM
CLTF
3.448
AG2-052LTFEXP_AG2-052->PJM
LTF
0.206
AH1-155LTFEXP_AH1-155->PJM
LTF
0.308
CBM West 1LTFEXP_CBM-W1->PJM
CBM
111.704
CBM South 1LTFEXP_CBM-S1->PJM
CBM
41.73
MECLTFEXP_MEC->PJM
CLTF
16.018
SIGELTFEXP_SIGE->PJM
CLTF
0.557

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.86 %
Rating:4558.0 MVA
Rating Type:A
MVA to Mitigate:4961.85
MW Contribution:6.0
Bus #Bus NameTypeMW Contribution
243186AF1-051 GEN
50/50
11.679
24723005RIVRG1
Adder
32.794
24723105RIVRG2
Adder
32.794
24685805CER G1
Adder
14.046
24685905CER G2
Adder
14.046
944971AF1-162 GEN
Solar/Wind Harmer
11.031
24728205BUCHG1
Adder
6.221
971225AH1-072 GEN
Solar/Wind Harmer
1.893
971227AH1-073 GEN
Solar/Wind Harmer
1.893
971277AH1-098 GEN
Solar/Wind Harmer
3.403
960161AF2-307 GEN
Solar/Wind Harmer
5.337
971073AG2-665 GEN
Solar/Wind Harmer
7.21
270583AD2-179 GEN
Solar/Wind Harmer
7.911
270186AC1-089 GEN
Solar/Wind Harmer
0.005
970239AG2-162 GEN
Solar/Wind Harmer
1.961
962581AG1-107 GEN
Solar/Wind Harmer
0.002
942891AE2-308 GEN
Solar/Wind Harmer
7.714
972043AH1-570 GEN
Solar/Wind Harmer
1.999
972045AH1-571 GEN
Solar/Wind Harmer
1.602
339221AD2-048_GEN
Solar/Wind Harmer
0.005
971125AH1-004 GEN
Solar/Wind Harmer
3.056
970107AG2-081 GEN
Solar/Wind Harmer
2.292
970235AG2-159 GEN
Solar/Wind Harmer
4.628
970235AG2-159 GEN
Solar/Wind Harmer
2.656
966021AG1-471 GEN
Solar/Wind Harmer
4.054
252509AD1-136 GEN
Solar/Wind Harmer
0.038
971485AH1-239 GEN
Solar/Wind Harmer
5.998
971081AG2-670 GEN
Solar/Wind Harmer
5.621
970653AG2-424 GEN
Solar/Wind Harmer
3.613
970653AG2-424 GEN
Solar/Wind Harmer
1.872
964571AG1-320 GEN
Solar/Wind Harmer
6.819
339255AE2-071 GEN
Solar/Wind Harmer
-0.122
964781AG1-341 GEN
Solar/Wind Harmer
7.848
25183208HLCRTG
Solar/Wind Harmer
0.011
252519AF1-045_GEN
Solar/Wind Harmer
6.373
252516AE2-318_GEN
Solar/Wind Harmer
5.653
270444AC2-157 GEN1
Solar/Wind Harmer
0.003
971587AH1-292 GEN
Solar/Wind Harmer
5.336
25194408D.CRK1
Adder
7.868
25194508D.CRK3
Adder
1.471
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
945391AF1-204 GEN
Solar/Wind Harmer
7.288
24728805RICHG1
Adder
3.669
24728905RICHG2
Adder
3.669
970241AG2-163 GEN
Solar/Wind Harmer
3.905
276916AD2-100_GEN
Solar/Wind Harmer
14.016
276911AD2-131_GEN
Solar/Wind Harmer
0.923
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
966841AG1-555 GEN
Solar/Wind Harmer
0.746
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
270383AD1-128 GEN
Solar/Wind Harmer
0.004
971613AH1-306 GEN
Solar/Wind Harmer
3.122
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
970825AG2-519 GEN
Solar/Wind Harmer
7.169
960441AF2-335 GEN
Solar/Wind Harmer
6.468
960611AF2-352 GEN
Solar/Wind Harmer
2.156
253370AE2-315 SEC1
Adder
1.856
970883AG2-550 GEN
Solar/Wind Harmer
6.374
970885AG2-551 GEN
Solar/Wind Harmer
2.125
276782AC1-033 GEN
Solar/Wind Harmer
0.001
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.25
276646AC1-214 GEN2
Solar/Wind Harmer
0.25
270599AE1-208 GEN
Solar/Wind Harmer
5.819
270031AE2-169
Solar/Wind Harmer
3.492
276741O09 GEN1
Solar/Wind Harmer
0.226
276708O09 GEN2
Solar/Wind Harmer
0.226
972267AH1-718 GEN
Adder
3.783
25322209TAIT E
Adder
8.86
25322209TAIT E
Adder
8.661
276603SUBLETTE C
Solar/Wind Harmer
0
274764LEE CO EC;5U
Adder
8.452
274765LEE CO EC;6U
Adder
8.452
274762LEE CO EC;3U
Adder
8.432
274763LEE CO EC;4U
Adder
8.352
938861AE1-114 GEN
Solar/Wind Harmer
3.58
274856ECOGROVE ;U1
Solar/Wind Harmer
0.149
276611AD2-172 GEN
Solar/Wind Harmer
0.002
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
971341AH1-150 GEN
Solar/Wind Harmer
12.585
971343AH1-151 GEN
Solar/Wind Harmer
12.585
247621Y3-024
Adder
0.216
274683WAUKEGAN ;8U
Adder
18.876
274683WAUKEGAN ;8U
Adder
15.912
274696ROCKY RD ;4P
Adder
10.207
274695ROCKY RD ;2P
Adder
9.971
274693ROCKY RD ;1P
Adder
9.873
274697ROCKY RD ;3P
Adder
2.709
23652301WDPWR_K20
Solar/Wind Helper
0.126
23585401KL_K28_T16
Solar/Wind Helper
1.149
970321AG2-212 GEN
Solar/Wind Harmer
1.358
24289405MTG1
50/50
10.907
243186AF1-051 GEN
50/50
11.679
24318705GVG2
50/50
10.872
24721805FLATG3
50/50
2.473
24721705FLATG2
50/50
45.331
24723205RIVRG3
Adder
32.794
24686105CER G3
Adder
14.139
24686505CER G6
Adder
14.12
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
970947AG2-589 GEN
Solar/Wind Harmer
0.368
971403AH1-188 GEN
Solar/Wind Harmer
15.305
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
24728305BUCHG2
Adder
6.221
971315AH1-136 GEN
Solar/Wind Harmer
1.928
971687AH1-348 GEN
Solar/Wind Harmer
0.947
927014AC1-188 GEN
Solar/Wind Harmer
0.005
24735205WLF2G2
Adder
7.162
971329AH1-144 GEN
Solar/Wind Harmer
6.901
970091AG2-072 GEN
Adder
86.947
970333AG2-219 GEN
Solar/Wind Harmer
5.608
945681AF1-233 GEN
Solar/Wind Harmer
14.563
3429241JKCT 3G
Adder
13.068
971821AH1-427 GEN
Solar/Wind Harmer
7.658
3429421JKCT 10G
Adder
9.139
339216AC1-074 GEN
Solar/Wind Harmer
0.209
970273AG2-179 GEN
Solar/Wind Harmer
2.644
971565AH1-281 GEN
Solar/Wind Harmer
1.508
252507AC2-088 GEN
Solar/Wind Harmer
0.341
964901AG1-354 GEN
Solar/Wind Harmer
11.154
25196808ZIMRHP
Adder
80.408
962241AG1-070 GEN
Solar/Wind Harmer
4.025
25196008MFTGT1
Adder
1.465
270445AC2-157 GEN2
Solar/Wind Harmer
0.003
25194608D.CRK4
Adder
1.71
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.086
962761AG1-125 GEN
Solar/Wind Harmer
27.465
970149AG2-104 GEN
Solar/Wind Harmer
29.663
970155AG2-107 GEN
Solar/Wind Harmer
17.538
270336AE1-100 GEN
Solar/Wind Harmer
0.004
270263AC1-001 GEN
Solar/Wind Harmer
0.699
24728605AND G2
Adder
3.761
970773AG2-487 GEN
Solar/Wind Harmer
1.204
971367AH1-164 GEN
Solar/Wind Harmer
2.344
963741AG1-226 GEN
Solar/Wind Harmer
15.844
965911AG1-460 GEN
Solar/Wind Harmer
1.332
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.849
276615X2-022 GEN
Solar/Wind Harmer
0.069
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.002
963831AG1-236 GEN
Solar/Wind Harmer
2.568
274880W4-005 GEN4
Solar/Wind Harmer
0.001
276903AD2-071 C
Solar/Wind Harmer
7.334
972175AH1-670 GEN
Solar/Wind Harmer
5.394
24791305MDL-5G
Solar/Wind Harmer
0.001
970291AG2-192 GEN
Solar/Wind Harmer
0.846
270032AE2-172
Solar/Wind Harmer
4.336
270005AE1-210 C O1
Solar/Wind Harmer
1.405
965031AG1-367 GEN
Solar/Wind Harmer
6.485
970825AG2-519 GEN
Solar/Wind Harmer
2.296
274854TWINGROVE;U2
Solar/Wind Harmer
0.003
253370AE2-315 SEC1
Adder
1.856
253371AE2-315 SEC2
Adder
1.755
276726Z2-087_GEN
Solar/Wind Harmer
0.002
939741AE1-205 GEN
Solar/Wind Harmer
9.009
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
7.976
274877BISHOP HL;1U
Solar/Wind Harmer
0.214
276158O29GEN2
Solar/Wind Harmer
0.001
960071AF2-298 GEN
Solar/Wind Harmer
3.157
25326309TAIT D
Adder
0.995
970569AG2-363 GEN
Solar/Wind Harmer
18.972
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
8.432
274766LEE CO EC;7U
Adder
8.332
945371AF1-202 GEN
Solar/Wind Harmer
0.001
247536S-71 GEN
Solar/Wind Harmer
0.254
971475AH1-234 GEN
Solar/Wind Harmer
3.061
970819AG2-516 GEN
Solar/Wind Harmer
7.565
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
972235AH1-702 GEN1
Adder
2.276
939401AE1-172 GEN
Solar/Wind Harmer
4.71
274822ROCKFORD ;11
Adder
17.71
957471AF2-041 GEN
Solar/Wind Harmer
18.878
959081AF2-199 GEN
Solar/Wind Harmer
6.293
971067AG2-660 GEN
Solar/Wind Harmer
2.098
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.18
971997AH1-543 GEN
Solar/Wind Harmer
3.301
274828WAUKEGAN ;BP
Adder
9.895
274682WAUKEGAN ;7U
Adder
16.093
274745AC1-111 GEN9
Adder
4.992
237046AF1-021 C
Solar/Wind Helper
0.433
238185AF2-356 C
Solar/Wind Helper
1.954
23751201ROTHROCK
Solar/Wind Helper
0.662
235054AD2-180 GEN
Solar/Wind Helper
1.52
23562501BACKB
Solar/Wind Helper
0.806
970245AG2-165 GEN
Solar/Wind Harmer
1.358
24721605FLATG1
50/50
2.473
972203AH1-686 GEN
Adder
3.978
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
957241AF2-018 GEN
Solar/Wind Harmer
-0.002
24477305BRIDGE
Adder
0.546
270399AC1-101 GEN
Solar/Wind Harmer
3.444
270400AC1-102 GEN
Solar/Wind Harmer
3.444
941621AE2-160 GEN
Adder
4.703
970281AG2-184 GEN
Solar/Wind Harmer
20.149
972143AH1-644 GEN
Solar/Wind Harmer
10.394
971313AH1-133 GEN
Solar/Wind Harmer
9.492
270132AB1-180 C
Adder
0.159
971061AG2-657 GEN
Solar/Wind Harmer
5.654
24734705WLF1G3
Adder
7.306
24734805WLF1G4
Adder
7.306
24734905WLF1G5
Adder
7.306
971985AH1-537 GEN
Solar/Wind Harmer
2.617
24735105WLF2G1
Adder
7.162
966391AG1-508 GEN
Solar/Wind Harmer
1.328
970879AG2-548 GEN
Solar/Wind Harmer
7.21
971981AH1-535 GEN
Solar/Wind Harmer
5.272
270367AC2-061_GEN
Solar/Wind Harmer
0.006
972163AH1-664 GEN
Solar/Wind Harmer
8.62
972165AH1-665 GEN
Solar/Wind Harmer
6.904
3429211JKCT 2G
Adder
12.898
965401AG1-405 GEN
Solar/Wind Harmer
4.386
965411AG1-406 GEN
Solar/Wind Harmer
2.821
339211AE2-254 GEN
Solar/Wind Harmer
0.003
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
970455AG2-298 GEN
Solar/Wind Harmer
5.018
25196108MFTGT2
Adder
1.614
25196108MFTGT2
Adder
1.499
252524AE2-267 GEN
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
9.147
25196308WSDLE2
Adder
9.067
25196208WSDLE1
Adder
9.045
25196708WSDLE6
Adder
9.022
25196508WSDLE4
Adder
8.795
962771AG1-126 GEN
Solar/Wind Harmer
27.465
270340AC2-060 GEN
Solar/Wind Harmer
0.008
270069AE2-166 C O1
Solar/Wind Harmer
0.005
944221AF1-090 GEN
Solar/Wind Harmer
3.946
963841AG1-237 GEN
Solar/Wind Harmer
2.88
270240V3-007_GEN2
Solar/Wind Harmer
0.002
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.24
276848AB2-070 GEN3
Solar/Wind Harmer
0.239
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
270269AC2-059
Solar/Wind Harmer
0.004
970289AG2-191 GEN
Solar/Wind Harmer
1.237
270594AE1-207 GEN
Solar/Wind Harmer
7.284
25306009OHH W.
Adder
2.673
970115AG2-085 GEN
Solar/Wind Harmer
2.587
253372AE2-315 SEC3
Adder
1.755
253372AE2-315 SEC3
Adder
1.755
971673AH1-337 GEN
Solar/Wind Harmer
4.2
971029AG2-637 GEN
Solar/Wind Harmer
9.661
276655WTG1_EQ
Solar/Wind Harmer
0.003
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
6.757
941731AE2-173 GEN
Solar/Wind Harmer
5.363
253349AC2-067 GEN
Solar/Wind Harmer
2.02
253400AC2-068 GEN
Solar/Wind Harmer
0.812
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
946321AF1-296 GEN
Solar/Wind Harmer
3.573
971611AH1-305 GEN
Solar/Wind Harmer
3.799
270543AE2-219 C
Solar/Wind Harmer
0.004
957751AF2-069 GEN
Solar/Wind Harmer
0.21
970169AG2-114 GEN
Solar/Wind Harmer
6.359
971609AH1-304 GEN
Solar/Wind Harmer
1.037
961011AF2-392 GEN
Solar/Wind Harmer
3.717
926823AC1-168 GEN
Solar/Wind Harmer
1.076
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971681AH1-341 GEN
Solar/Wind Harmer
10.171
945581AF1-223 GEN
Solar/Wind Harmer
0
276612AE2-035 GEN
Solar/Wind Harmer
0.002
274823ROCKFORD ;21
Adder
17.581
971171AH1-044 GEN
Solar/Wind Harmer
12.585
274746AC1-111 G10
Adder
4.992
274744AC1-111 GEN8
Adder
4.992
23750501ELLIOTTS
Solar/Wind Helper
0.594
24289405MTG1
50/50
10.907
24318705GVG2
50/50
10.872
24722005FLATG5
50/50
2.473
24721905FLATG4
50/50
45.331
24686205CER G4
Adder
14.065
24686405CER G5
Adder
14.009
270053AF1-130 C
Solar/Wind Harmer
2.49
970913AG2-568 GEN
Solar/Wind Harmer
8.136
971191AH1-055 GEN
Solar/Wind Harmer
25.624
960911AF2-382 GEN
Solar/Wind Harmer
7.284
972103AH1-617 GEN
Solar/Wind Harmer
19.189
971461AH1-227 GEN
Solar/Wind Harmer
4.855
270346AE1-212 GEN
Solar/Wind Harmer
7.86
943031AE2-326 GEN
Solar/Wind Harmer
4.498
971331AH1-145 GEN
Solar/Wind Harmer
10.953
247619Y1-049
Adder
0.497
958121AF2-106 GEN
Solar/Wind Harmer
0.001
970243AG2-164 GEN
Solar/Wind Harmer
4.588
970519AG2-331 GEN
Solar/Wind Harmer
20.392
970699AG2-449 GEN
Solar/Wind Harmer
1.961
970093AG2-073 GEN
Solar/Wind Harmer
7.734
972167AH1-666 GEN
Solar/Wind Harmer
6.174
972273AH1-721 GEN
Adder
91.659
966571AG1-526 GEN
Solar/Wind Harmer
17.032
3429391JKCT 9G
Adder
9.139
970273AG2-179 GEN
Solar/Wind Harmer
4.533
270291AC1-194 GEN
Solar/Wind Harmer
5.957
958171AF2-111 GEN
Solar/Wind Harmer
18.792
339250AF1-203 GEN
Solar/Wind Harmer
0.001
960741AF2-365 GEN
Solar/Wind Harmer
3.705
971155AH1-034 GEN
Solar/Wind Harmer
8.639
962251AG1-071 GEN
Solar/Wind Harmer
4.615
25196008MFTGT1
Adder
1.418
252510AF1-249 C
Solar/Wind Harmer
0.056
25194608D.CRK4
Adder
1.71
25196608WSDLE5
Adder
8.886
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
9.211
970153AG2-106 GEN
Solar/Wind Harmer
17.538
253406AD2-031_GEN
Solar/Wind Harmer
0.522
970193AG2-126 GEN
Solar/Wind Harmer
10.289
24728705AND G3
Adder
7.865
24728505AND G1
Adder
3.761
270356AE2-297 GEN
Solar/Wind Harmer
0.009
270222AC2-111 GEN
Solar/Wind Harmer
3.451
253415AE1-040 GEN
Solar/Wind Harmer
0.003
270030AE2-140 GEN
Solar/Wind Harmer
13.595
942481AE2-261 GEN
Solar/Wind Harmer
19.91
972173AH1-669 GEN
Solar/Wind Harmer
3.31
270437AC2-090 C
Solar/Wind Harmer
0.003
276621W2-048 GEN
Solar/Wind Harmer
0.333
276838X2-022 GEN2
Solar/Wind Harmer
0.372
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
3.038
276668AB2-070 GEN1
Solar/Wind Harmer
0.24
247642Z2-115 C
Solar/Wind Harmer
0.003
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.514
270273AD2-016 GEN
Solar/Wind Harmer
0.675
970289AG2-191 GEN
Solar/Wind Harmer
0.716
970291AG2-192 GEN
Solar/Wind Harmer
0.651
958821AF2-173 GEN
Solar/Wind Harmer
9.079
270004AE1-209 GEN
Solar/Wind Harmer
1.405
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
965091AG1-374 GEN
Solar/Wind Harmer
19.404
959611AF2-252 GEN
Solar/Wind Harmer
2.156
253370AE2-315 SEC1
Adder
1.856
253371AE2-315 SEC2
Adder
1.755
942111AE2-223 GEN
Solar/Wind Harmer
2.091
946031AF1-268 GEN
Solar/Wind Harmer
6.117
970191AG2-125 GEN
Solar/Wind Harmer
1.65
965931AG1-462 GEN
Solar/Wind Harmer
16.291
274878BISHOP HL;2U
Solar/Wind Harmer
0.214
276157O29GEN1
Solar/Wind Harmer
1.026
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
970571AG2-364 GEN
Solar/Wind Harmer
12.648
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
8.432
274767LEE CO EC;8U
Adder
8.332
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
1.979
959091AF2-200 GEN
Solar/Wind Harmer
12.585
274682WAUKEGAN ;7U
Adder
16.093
274729ELWOOD EC;1P
Adder
6.64
237048AF1-022 C
Solar/Wind Helper
0.172
237043AE2-125 C
Solar/Wind Helper
0.155
235058AG1-386 C
Solar/Wind Helper
0.383
970513AG2-328 GEN
Solar/Wind Harmer
1.358
970517AG2-330 GEN
Solar/Wind Harmer
8.151
944201AF1-088_MTX
Adder
121.273
957141AF2-008_MTX
Adder
60.637
CPLELTFEXP_CPLE->PJM
CLTF
6.38
CBM West 2LTFEXP_CBM-W2->PJM
CBM
132.776
LAGNLTFEXP_LAGN->PJM
CLTF
19.803
CBM South 2LTFEXP_CBM-S2->PJM
CBM
23.164
TVALTFEXP_TVA->PJM
CLTF
10.26
NYPJM->LTFIMP_NY
CLTF
4.59
LGEELTFEXP_LGEE->PJM
CLTF
7.503
WECLTFEXP_WEC->PJM
CLTF
3.454
AG2-052LTFEXP_AG2-052->PJM
LTF
0.209
AH1-155LTFEXP_AH1-155->PJM
LTF
0.313
CBM West 1LTFEXP_CBM-W1->PJM
CBM
116.498
CBM South 1LTFEXP_CBM-S1->PJM
CBM
38.98
MECLTFEXP_MEC->PJM
CLTF
15.75
SIGELTFEXP_SIGE->PJM
CLTF
0.547

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.47 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5991.02
MW Contribution:10.5
Bus #Bus NameTypeMW Contribution
243186AF1-051 GEN
50/50
12.748
24723005RIVRG1
Adder
37.637
24723105RIVRG2
Adder
37.637
24685805CER G1
Adder
16.117
24685905CER G2
Adder
16.117
944971AF1-162 GEN
Solar/Wind Harmer
13.01
24728205BUCHG1
Adder
7.763
270214AC2-123 GEN
Solar/Wind Harmer
3.882
971225AH1-072 GEN
Solar/Wind Harmer
3.33
971227AH1-073 GEN
Solar/Wind Harmer
3.33
971277AH1-098 GEN
Solar/Wind Harmer
6.642
270583AD2-179 GEN
Solar/Wind Harmer
16.345
960161AF2-307 GEN
Solar/Wind Harmer
8.906
970879AG2-548 GEN
Solar/Wind Harmer
8.293
971073AG2-665 GEN
Solar/Wind Harmer
8.293
971073AG2-665 GEN
Solar/Wind Harmer
5.786
270186AC1-089 GEN
Solar/Wind Harmer
8.143
970239AG2-162 GEN
Solar/Wind Harmer
14.622
942891AE2-308 GEN
Solar/Wind Harmer
13.304
339231AF1-038_GEN
Solar/Wind Harmer
2.394
972043AH1-570 GEN
Solar/Wind Harmer
3.299
972045AH1-571 GEN
Solar/Wind Harmer
2.639
339221AD2-048_GEN
Solar/Wind Harmer
2.024
966021AG1-471 GEN
Solar/Wind Harmer
7.099
971125AH1-004 GEN
Solar/Wind Harmer
5.257
970107AG2-081 GEN
Solar/Wind Harmer
3.942
971485AH1-239 GEN
Solar/Wind Harmer
10.499
962581AG1-107 GEN
Solar/Wind Harmer
6.599
961491AF2-440 GEN
Solar/Wind Harmer
2.742
971081AG2-670 GEN
Solar/Wind Harmer
9.778
970235AG2-159 GEN
Solar/Wind Harmer
5.2
970235AG2-159 GEN
Solar/Wind Harmer
3.174
339236AF1-050_GEN
Solar/Wind Harmer
2.357
970653AG2-424 GEN
Solar/Wind Harmer
6.261
970653AG2-424 GEN
Solar/Wind Harmer
2.263
339255AE2-071 GEN
Solar/Wind Harmer
1.372
964781AG1-341 GEN
Solar/Wind Harmer
13.698
964571AG1-320 GEN
Solar/Wind Harmer
10.586
252509AD1-136 GEN
Solar/Wind Harmer
0.327
25183208HLCRTG
Solar/Wind Harmer
7.582
252519AF1-045_GEN
Solar/Wind Harmer
7.591
252516AE2-318_GEN
Solar/Wind Harmer
5.79
270444AC2-157 GEN1
Solar/Wind Harmer
6.973
25194408D.CRK1
Adder
9.381
25194508D.CRK3
Adder
1.754
253317AC1-085 GEN4
Solar/Wind Harmer
10.168
945391AF1-204 GEN
Solar/Wind Harmer
16.499
253394AE2-221_GEN
Solar/Wind Harmer
5.367
253398AE2-221_GEN2
Solar/Wind Harmer
5.367
316217AC1-145 GEN
Solar/Wind Harmer
2.806
316197AC1-042 GEN
Solar/Wind Harmer
2.127
942671AE2-283 GEN
Solar/Wind Harmer
5.728
24728805RICHG1
Adder
4.412
24728905RICHG2
Adder
4.412
276916AD2-100_GEN
Solar/Wind Harmer
24.323
276911AD2-131_GEN
Solar/Wind Harmer
4.916
253370AE2-315 SEC1
Adder
2.238
972267AH1-718 GEN
Adder
4.6
274764LEE CO EC;5U
Adder
10.276
274765LEE CO EC;6U
Adder
10.276
274762LEE CO EC;3U
Adder
10.252
274763LEE CO EC;4U
Adder
10.155
25322209TAIT E
Adder
10.707
25322209TAIT E
Adder
10.466
274683WAUKEGAN ;8U
Adder
22.951
274683WAUKEGAN ;8U
Adder
19.347
274696ROCKY RD ;4P
Adder
12.409
274695ROCKY RD ;2P
Adder
12.123
274693ROCKY RD ;1P
Adder
12.003
274697ROCKY RD ;3P
Adder
3.293
247621Y3-024
Adder
0.262
23585401KL_K28_T16
Solar/Wind Helper
1.267
23652301WDPWR_K20
Solar/Wind Helper
0.133
238120AE2-309 GEN
Solar/Wind Helper
0.43
203955AF1-039 C O1
Solar/Wind Helper
0.352
944781AF1-143 GEN
Solar/Wind Helper
2.298
20083426SW_E13_K22
Solar/Wind Helper
0.051
20088926STNY CRK
Solar/Wind Helper
0.747
20084626FORWARD
Solar/Wind Helper
0.323
946071AF1-272 GEN
Solar/Wind Helper
2.428
203940AF1-140 C
Solar/Wind Helper
0.359
970241AG2-163 GEN
Solar/Wind Harmer
12.594
24289405MTG1
50/50
11.79
243186AF1-051 GEN
50/50
12.748
24318705GVG2
50/50
11.866
24721805FLATG3
50/50
2.714
24721705FLATG2
50/50
49.755
24723205RIVRG3
Adder
37.637
24686105CER G3
Adder
16.224
24686505CER G6
Adder
16.203
971403AH1-188 GEN
Solar/Wind Harmer
26.09
270331AC1-082 GEN3
Solar/Wind Harmer
0.823
970947AG2-589 GEN
Solar/Wind Harmer
3.612
960001AF2-291 GEN
Solar/Wind Harmer
5.329
24728305BUCHG2
Adder
7.763
971687AH1-348 GEN
Solar/Wind Harmer
1.664
971329AH1-144 GEN
Solar/Wind Harmer
19.813
971315AH1-136 GEN
Solar/Wind Harmer
3.299
24735205WLF2G2
Adder
9.002
927014AC1-188 GEN
Solar/Wind Harmer
2.379
971367AH1-164 GEN
Solar/Wind Harmer
5.069
270336AE1-100 GEN
Solar/Wind Harmer
2.384
970091AG2-072 GEN
Adder
103.033
970333AG2-219 GEN
Solar/Wind Harmer
41.959
3429241JKCT 3G
Adder
15.723
971821AH1-427 GEN
Solar/Wind Harmer
13.272
3429421JKCT 10G
Adder
10.993
945681AF1-233 GEN
Solar/Wind Harmer
24.878
970273AG2-179 GEN
Solar/Wind Harmer
3.221
943111AE2-339 GEN
Solar/Wind Harmer
1.163
943811AF1-049 GEN
Solar/Wind Harmer
4.961
339216AC1-074 GEN
Solar/Wind Harmer
2.198
339241AF1-083 GEN
Solar/Wind Harmer
2.171
971565AH1-281 GEN
Solar/Wind Harmer
2.604
964901AG1-354 GEN
Solar/Wind Harmer
19.445
962241AG1-070 GEN
Solar/Wind Harmer
5.799
252507AC2-088 GEN
Solar/Wind Harmer
2.292
25196808ZIMRHP
Adder
95.812
25196008MFTGT1
Adder
1.747
270445AC2-157 GEN2
Solar/Wind Harmer
6.973
25194608D.CRK4
Adder
2.039
270018AE2-047 C O1
Solar/Wind Harmer
1.511
253432AC1-085 GEN2
Solar/Wind Harmer
0.325
946171AF1-282 GEN
Solar/Wind Harmer
12.138
270263AC1-001 GEN
Solar/Wind Harmer
1.245
24728605AND G2
Adder
4.525
962761AG1-125 GEN
Solar/Wind Harmer
38.198
970149AG2-104 GEN
Solar/Wind Harmer
47.174
970155AG2-107 GEN
Solar/Wind Harmer
16.656
270197AD1-017 GEN1
Solar/Wind Harmer
1.81
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
6.484
253370AE2-315 SEC1
Adder
2.238
253371AE2-315 SEC2
Adder
2.117
274761LEE CO EC;2U
Adder
10.252
274766LEE CO EC;7U
Adder
10.131
972235AH1-702 GEN1
Adder
2.767
25326309TAIT D
Adder
1.202
274822ROCKFORD ;11
Adder
21.533
274828WAUKEGAN ;BP
Adder
12.03
274682WAUKEGAN ;7U
Adder
19.567
274745AC1-111 GEN9
Adder
6.069
238185AF2-356 C
Solar/Wind Helper
2.176
237046AF1-021 C
Solar/Wind Helper
0.457
235054AD2-180 GEN
Solar/Wind Helper
1.695
238117U2-030
Solar/Wind Helper
0.288
235531U2-073 GEN
Solar/Wind Helper
2.733
23751201ROTHROCK
Solar/Wind Helper
0.71
23562501BACKB
Solar/Wind Helper
0.864
23583801GRNGAP
Solar/Wind Helper
4.088
316095T157 G97
Solar/Wind Helper
1.094
238108AE1-109 GEN1
Solar/Wind Helper
0.088
20089226LOOKOUT
Solar/Wind Helper
0.539
20088826HIGHLAND
Solar/Wind Helper
0.812
963741AG1-226 GEN
Solar/Wind Harmer
22.669
24721605FLATG1
50/50
2.714
972203AH1-686 GEN
Adder
4.544
957241AF2-018 GEN
Solar/Wind Harmer
8.259
270399AC1-101 GEN
Solar/Wind Harmer
7.833
270400AC1-102 GEN
Solar/Wind Harmer
7.833
24477305BRIDGE
Adder
0.637
270330AC1-082 GEN2
Solar/Wind Harmer
1.393
270329AC1-082 GEN1
Solar/Wind Harmer
0.821
971313AH1-133 GEN
Solar/Wind Harmer
17.224
941621AE2-160 GEN
Adder
5.66
966391AG1-508 GEN
Solar/Wind Harmer
5.763
970281AG2-184 GEN
Solar/Wind Harmer
34.934
972143AH1-644 GEN
Solar/Wind Harmer
16.635
270132AB1-180 C
Adder
0.198
24734705WLF1G3
Adder
9.185
24734805WLF1G4
Adder
9.185
24734905WLF1G5
Adder
9.185
962211AG1-066 GEN
Solar/Wind Harmer
3.823
24735105WLF2G1
Adder
9.002
971061AG2-657 GEN
Solar/Wind Harmer
14.056
971985AH1-537 GEN
Solar/Wind Harmer
26.201
971981AH1-535 GEN
Solar/Wind Harmer
14.209
270069AE2-166 C O1
Solar/Wind Harmer
3.796
970879AG2-548 GEN
Solar/Wind Harmer
5.786
965401AG1-405 GEN
Solar/Wind Harmer
7.637
965411AG1-406 GEN
Solar/Wind Harmer
3.428
270367AC2-061_GEN
Solar/Wind Harmer
4.222
3429211JKCT 2G
Adder
15.52
339211AE2-254 GEN
Solar/Wind Harmer
2.01
972163AH1-664 GEN
Solar/Wind Harmer
13.228
972165AH1-665 GEN
Solar/Wind Harmer
10.582
339243AC2-075 GEN1
Solar/Wind Harmer
0.595
970455AG2-298 GEN
Solar/Wind Harmer
7.809
25196108MFTGT2
Adder
1.926
25196108MFTGT2
Adder
1.788
24289405MTG1
50/50
11.79
24318705GVG2
50/50
11.866
24722005FLATG5
50/50
2.714
24721905FLATG4
50/50
49.755
24686205CER G4
Adder
16.139
24686405CER G5
Adder
16.075
270053AF1-130 C
Solar/Wind Harmer
6.909
970913AG2-568 GEN
Solar/Wind Harmer
14.13
960911AF2-382 GEN
Solar/Wind Harmer
12.931
943031AE2-326 GEN
Solar/Wind Harmer
6.109
971461AH1-227 GEN
Solar/Wind Harmer
8.54
972103AH1-617 GEN
Solar/Wind Harmer
33.271
971331AH1-145 GEN
Solar/Wind Harmer
15.359
247619Y1-049
Adder
0.704
971191AH1-055 GEN
Solar/Wind Harmer
36.143
270346AE1-212 GEN
Solar/Wind Harmer
14.72
958121AF2-106 GEN
Solar/Wind Harmer
7.412
957541AF2-048 GEN
Solar/Wind Harmer
2.373
972273AH1-721 GEN
Adder
111.61
270030AE2-140 GEN
Solar/Wind Harmer
26.875
970093AG2-073 GEN
Solar/Wind Harmer
13.356
970243AG2-164 GEN
Solar/Wind Harmer
34.33
970519AG2-331 GEN
Solar/Wind Harmer
23.064
970699AG2-449 GEN
Solar/Wind Harmer
15.258
966571AG1-526 GEN
Solar/Wind Harmer
29.484
270173AC1-122 GEN
Solar/Wind Harmer
2.108
3429391JKCT 9G
Adder
10.993
970273AG2-179 GEN
Solar/Wind Harmer
5.144
972167AH1-666 GEN
Solar/Wind Harmer
10.547
962751AG1-124 GEN
Solar/Wind Harmer
11.816
339250AF1-203 GEN
Solar/Wind Harmer
0.784
971155AH1-034 GEN
Solar/Wind Harmer
12.926
960741AF2-365 GEN
Solar/Wind Harmer
6.448
962251AG1-071 GEN
Solar/Wind Harmer
7.087
958171AF2-111 GEN
Solar/Wind Harmer
32.167
270291AC1-194 GEN
Solar/Wind Harmer
13.485
25196008MFTGT1
Adder
1.692
252510AF1-249 C
Solar/Wind Harmer
0.521
25194608D.CRK4
Adder
2.039
25196608WSDLE5
Adder
10.598
253316AC1-085 GEN3
Solar/Wind Harmer
10.168
253433AC1-085 GEN1
Solar/Wind Harmer
6.454
946181AF1-283 GEN
Solar/Wind Harmer
15.78
253406AD2-031_GEN
Solar/Wind Harmer
1.534
970193AG2-126 GEN
Solar/Wind Harmer
17.759
24728705AND G3
Adder
9.464
24728505AND G1
Adder
4.525
970153AG2-106 GEN
Solar/Wind Harmer
16.656
270574AD1-017 GEN2
Solar/Wind Harmer
6.023
3147312GRETNA
Solar/Wind Harmer
-0.014
3146802CHATHAM
Solar/Wind Harmer
-0.013
941801AE2-185 GEN
Solar/Wind Harmer
6.484
270356AE2-297 GEN
Solar/Wind Harmer
5.354
270222AC2-111 GEN
Solar/Wind Harmer
9.554
253415AE1-040 GEN
Solar/Wind Harmer
1.318
253370AE2-315 SEC1
Adder
2.238
253371AE2-315 SEC2
Adder
2.117
274760LEE CO EC;1U
Adder
10.252
274767LEE CO EC;8U
Adder
10.131
972236AH1-702 GEN2
Adder
2.406
274682WAUKEGAN ;7U
Adder
19.567
274729ELWOOD EC;1P
Adder
8.072
237048AF1-022 C
Solar/Wind Helper
0.182
964991AG1-363 GEN
Solar/Wind Helper
3.709
23750701CROSSCHOOL
Solar/Wind Helper
1.197
238118U2-030_1
Solar/Wind Helper
0.288
238127S14_GEN_2
Solar/Wind Helper
0.687
237043AE2-125 C
Solar/Wind Helper
0.163
202652Y1-033 WT C
Solar/Wind Helper
0.534
316097T157 G90
Solar/Wind Helper
1.094
20089126CSLMN_L13
Solar/Wind Helper
0.554
20089026BF_G21_K23
Solar/Wind Helper
0.438
252524AE2-267 GEN
Solar/Wind Harmer
1.95
25196408WSDLE3
Adder
10.91
25196308WSDLE2
Adder
10.815
25196208WSDLE1
Adder
10.788
25196708WSDLE6
Adder
10.761
25196508WSDLE4
Adder
10.49
270340AC2-060 GEN
Solar/Wind Harmer
3.615
962771AG1-126 GEN
Solar/Wind Harmer
38.198
944031AF1-071 GEN
Solar/Wind Harmer
1.178
944221AF1-090 GEN
Solar/Wind Harmer
12.754
25306009OHH W.
Adder
3.223
253372AE2-315 SEC3
Adder
2.117
253372AE2-315 SEC3
Adder
2.117
274823ROCKFORD ;21
Adder
21.377
274746AC1-111 G10
Adder
6.069
274744AC1-111 GEN8
Adder
6.069
23750501ELLIOTTS
Solar/Wind Helper
0.635
238126S14_GEN_1
Solar/Wind Helper
0.687
238109AE1-109 GEN2
Solar/Wind Helper
0.088
238110AE1-109 GEN3
Solar/Wind Helper
0.088
20092526R32
Solar/Wind Helper
1.053
944201AF1-088_MTX
Adder
145.184
957141AF2-008_MTX
Adder
72.592
CPLELTFEXP_CPLE->PJM
CLTF
7.791
CBM West 2LTFEXP_CBM-W2->PJM
CBM
162.06
LAGNLTFEXP_LAGN->PJM
CLTF
24.37
CBM South 2LTFEXP_CBM-S2->PJM
CBM
29.03
TVALTFEXP_TVA->PJM
CLTF
12.655
NYPJM->LTFIMP_NY
CLTF
5.271
LGEELTFEXP_LGEE->PJM
CLTF
8.989
WECLTFEXP_WEC->PJM
CLTF
4.2
AG2-052LTFEXP_AG2-052->PJM
LTF
0.253
AH1-155LTFEXP_AH1-155->PJM
LTF
0.38
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.592
CBM South 1LTFEXP_CBM-S1->PJM
CBM
47.815
MECLTFEXP_MEC->PJM
CLTF
19.173
SIGELTFEXP_SIGE->PJM
CLTF
0.659

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P2-2_#7222_05MALIS 765_1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#7222_05MALIS 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:107.09 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5914.32
MW Contribution:9.45
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
2.714
972203AH1-686 GEN
Adder
4.188
957241AF2-018 GEN
Solar/Wind Harmer
7.355
270330AC1-082 GEN2
Solar/Wind Harmer
1.259
270329AC1-082 GEN1
Solar/Wind Harmer
0.741
270399AC1-101 GEN
Solar/Wind Harmer
6.952
270400AC1-102 GEN
Solar/Wind Harmer
6.952
24477305BRIDGE
Adder
0.568
962771AG1-126 GEN
Solar/Wind Harmer
51.279
941621AE2-160 GEN
Adder
4.884
970281AG2-184 GEN
Solar/Wind Harmer
30.593
972143AH1-644 GEN
Solar/Wind Harmer
14.568
971313AH1-133 GEN
Solar/Wind Harmer
14.325
962211AG1-066 GEN
Solar/Wind Harmer
3.356
270132AB1-180 C
Adder
0.166
24734705WLF1G3
Adder
7.759
24734805WLF1G4
Adder
7.759
24734905WLF1G5
Adder
7.759
971061AG2-657 GEN
Solar/Wind Harmer
12.002
971985AH1-537 GEN
Solar/Wind Harmer
23.775
24735105WLF2G1
Adder
7.624
966391AG1-508 GEN
Solar/Wind Harmer
4.457
971981AH1-535 GEN
Solar/Wind Harmer
12.146
965401AG1-405 GEN
Solar/Wind Harmer
6.855
965411AG1-406 GEN
Solar/Wind Harmer
3.076
339211AE2-254 GEN
Solar/Wind Harmer
1.816
970455AG2-298 GEN
Solar/Wind Harmer
7.163
3429211JKCT 2G
Adder
13.952
270367AC2-061_GEN
Solar/Wind Harmer
3.766
972163AH1-664 GEN
Solar/Wind Harmer
11.816
972165AH1-665 GEN
Solar/Wind Harmer
9.453
339243AC2-075 GEN1
Solar/Wind Harmer
0.537
963841AG1-237 GEN
Solar/Wind Harmer
12.629
25196108MFTGT2
Adder
1.772
25196108MFTGT2
Adder
1.645
24386205FR-12G C
Solar/Wind Harmer
4.941
24386405FR-21G C
Solar/Wind Harmer
4.958
24386605FR-22G C
Solar/Wind Harmer
4.958
24387005FR-3G C
Solar/Wind Harmer
4.561
944221AF1-090 GEN
Solar/Wind Harmer
12.589
24690905MDL-1G C
Solar/Wind Harmer
9.207
270180AB1-006 GEN1
Solar/Wind Harmer
8.248
946581AF1-322 GEN
Solar/Wind Harmer
11.733
24691005MDL-2G C
Solar/Wind Harmer
4.241
24697605MDL-3G C
Solar/Wind Harmer
4.228
25196408WSDLE3
Adder
9.904
25196308WSDLE2
Adder
9.818
25196208WSDLE1
Adder
9.794
25196708WSDLE6
Adder
9.769
25196508WSDLE4
Adder
9.523
274823ROCKFORD ;21
Adder
21.86
274746AC1-111 G10
Adder
6.26
274744AC1-111 GEN8
Adder
6.26
274775LINCOLN ;6U
Adder
9.447
274776LINCOLN ;7U
Adder
1.661
23750501ELLIOTTS
Solar/Wind Helper
0.66
254304AE2-114 C
Solar/Wind Helper
0.203
241997AF1-093 GEN
Solar/Wind Helper
0.238
241982AE2-343 S C
Solar/Wind Helper
0.207
238126S14_GEN_1
Solar/Wind Helper
0.669
20092526R32
Solar/Wind Helper
1.095
203961AE2-224 GEN
Solar/Wind Helper
2.258
20091526CHSTN_FL
Solar/Wind Helper
0.546
20090526Q36
Solar/Wind Helper
0.975
203993AD2-133_GEN1
Solar/Wind Helper
0.975
203846AF2-130 C
Solar/Wind Helper
0.42
238109AE1-109 GEN2
Solar/Wind Helper
0.084
238110AE1-109 GEN3
Solar/Wind Helper
0.084
941231AE2-117 GEN
Solar/Wind Helper
0.441
24697905MDL-4G C
Solar/Wind Harmer
1.02
243186AF1-051 GEN
50/50
12.367
24723005RIVRG1
Adder
34.405
24723105RIVRG2
Adder
34.405
24685805CER G1
Adder
14.69
24685905CER G2
Adder
14.69
944971AF1-162 GEN
Solar/Wind Harmer
11.585
24728205BUCHG1
Adder
6.555
971225AH1-072 GEN
Solar/Wind Harmer
2.872
971227AH1-073 GEN
Solar/Wind Harmer
2.872
970239AG2-162 GEN
Solar/Wind Harmer
14.243
270214AC2-123 GEN
Solar/Wind Harmer
2.998
971277AH1-098 GEN
Solar/Wind Harmer
5.115
960161AF2-307 GEN
Solar/Wind Harmer
7.971
270444AC2-157 GEN1
Solar/Wind Harmer
6.775
942891AE2-308 GEN
Solar/Wind Harmer
11.976
970235AG2-159 GEN
Solar/Wind Harmer
4.77
970235AG2-159 GEN
Solar/Wind Harmer
2.912
964571AG1-320 GEN
Solar/Wind Harmer
9.767
970653AG2-424 GEN
Solar/Wind Harmer
5.74
970653AG2-424 GEN
Solar/Wind Harmer
2.075
339231AF1-038_GEN
Solar/Wind Harmer
2.157
270186AC1-089 GEN
Solar/Wind Harmer
7.264
972043AH1-570 GEN
Solar/Wind Harmer
2.97
972045AH1-571 GEN
Solar/Wind Harmer
2.376
339221AD2-048_GEN
Solar/Wind Harmer
1.825
971081AG2-670 GEN
Solar/Wind Harmer
8.888
270583AD2-179 GEN
Solar/Wind Harmer
11.844
971125AH1-004 GEN
Solar/Wind Harmer
4.737
970107AG2-081 GEN
Solar/Wind Harmer
3.553
966021AG1-471 GEN
Solar/Wind Harmer
6.38
339236AF1-050_GEN
Solar/Wind Harmer
2.142
971485AH1-239 GEN
Solar/Wind Harmer
9.446
339255AE2-071 GEN
Solar/Wind Harmer
1.246
964781AG1-341 GEN
Solar/Wind Harmer
12.447
945391AF1-204 GEN
Solar/Wind Harmer
16.279
962581AG1-107 GEN
Solar/Wind Harmer
5.875
961491AF2-440 GEN
Solar/Wind Harmer
2.442
970241AG2-163 GEN
Solar/Wind Harmer
28.958
966841AG1-555 GEN
Solar/Wind Harmer
2.893
252509AD1-136 GEN
Solar/Wind Harmer
0.295
970321AG2-212 GEN
Solar/Wind Harmer
20.527
276916AD2-100_GEN
Solar/Wind Harmer
24.115
276911AD2-131_GEN
Solar/Wind Harmer
4.874
957381AF2-032 GEN
Solar/Wind Harmer
0.48
25194408D.CRK1
Adder
8.517
25194508D.CRK3
Adder
1.592
972267AH1-718 GEN
Adder
4.679
274764LEE CO EC;5U
Adder
10.473
274765LEE CO EC;6U
Adder
10.473
274762LEE CO EC;3U
Adder
10.448
274763LEE CO EC;4U
Adder
10.35
274696ROCKY RD ;4P
Adder
12.769
274695ROCKY RD ;2P
Adder
12.475
274693ROCKY RD ;1P
Adder
12.352
274697ROCKY RD ;3P
Adder
3.389
274683WAUKEGAN ;8U
Adder
23.604
274683WAUKEGAN ;8U
Adder
19.897
274770LINCOLN ;1U
Adder
9.447
274771LINCOLN ;2U
Adder
9.447
23652301WDPWR_K20
Solar/Wind Helper
0.141
23585401KL_K28_T16
Solar/Wind Helper
1.274
203955AF1-039 C O1
Solar/Wind Helper
0.36
962101AG1-054 GEN
Solar/Wind Helper
0.609
241985AE1-237 GEN
Solar/Wind Helper
0.231
241967AE2-285_GEN
Solar/Wind Helper
0.593
241801AE1-079 GEN
Solar/Wind Helper
0.231
944781AF1-143 GEN
Solar/Wind Helper
2.369
238120AE2-309 GEN
Solar/Wind Helper
0.419
20083426SW_E13_K22
Solar/Wind Helper
0.053
946071AF1-272 GEN
Solar/Wind Helper
2.555
20088926STNY CRK
Solar/Wind Helper
0.775
20084626FORWARD
Solar/Wind Helper
0.336
203940AF1-140 C
Solar/Wind Helper
0.373
20088626ARWF_N39
Solar/Wind Helper
1.136
20303426NA_O38_P22
Solar/Wind Helper
0.931
203853AF1-134 C O1
Solar/Wind Helper
0.446
946381AF1-302 GEN
Solar/Wind Helper
0.207
203952AE2-129 C
Solar/Wind Helper
0.442
203946AE2-131 C
Solar/Wind Helper
0.442
24289405MTG1
50/50
11.329
243186AF1-051 GEN
50/50
12.367
24318705GVG2
50/50
11.512
24721805FLATG3
50/50
2.714
24721705FLATG2
50/50
49.756
24723205RIVRG3
Adder
34.405
24686105CER G3
Adder
14.787
24686505CER G6
Adder
14.768
971403AH1-188 GEN
Solar/Wind Harmer
23.029
270331AC1-082 GEN3
Solar/Wind Harmer
0.743
970947AG2-589 GEN
Solar/Wind Harmer
3.261
960001AF2-291 GEN
Solar/Wind Harmer
4.797
962761AG1-125 GEN
Solar/Wind Harmer
51.279
970149AG2-104 GEN
Solar/Wind Harmer
63.33
970155AG2-107 GEN
Solar/Wind Harmer
22.36
971315AH1-136 GEN
Solar/Wind Harmer
2.924
24728305BUCHG2
Adder
6.555
971687AH1-348 GEN
Solar/Wind Harmer
1.437
24735205WLF2G2
Adder
7.624
927014AC1-188 GEN
Solar/Wind Harmer
2.074
970333AG2-219 GEN
Solar/Wind Harmer
40.872
970091AG2-072 GEN
Adder
99.087
971329AH1-144 GEN
Solar/Wind Harmer
14.766
270445AC2-157 GEN2
Solar/Wind Harmer
6.775
971821AH1-427 GEN
Solar/Wind Harmer
11.992
971565AH1-281 GEN
Solar/Wind Harmer
2.394
3429241JKCT 3G
Adder
14.135
970273AG2-179 GEN
Solar/Wind Harmer
2.902
339241AF1-083 GEN
Solar/Wind Harmer
1.973
3429421JKCT 10G
Adder
9.882
943111AE2-339 GEN
Solar/Wind Harmer
1.047
339216AC1-074 GEN
Solar/Wind Harmer
1.982
945681AF1-233 GEN
Solar/Wind Harmer
22.212
964901AG1-354 GEN
Solar/Wind Harmer
17.673
962241AG1-070 GEN
Solar/Wind Harmer
5.277
963741AG1-226 GEN
Solar/Wind Harmer
52.124
25196008MFTGT1
Adder
1.607
24385905FR-11G C
Solar/Wind Harmer
9.582
24387305FR-4G C
Solar/Wind Harmer
5.858
252507AC2-088 GEN
Solar/Wind Harmer
2.064
24728605AND G2
Adder
4.411
970245AG2-165 GEN
Solar/Wind Harmer
20.527
965911AG1-460 GEN
Solar/Wind Harmer
1.601
25196808ZIMRHP
Adder
86.412
25194608D.CRK4
Adder
1.851
274761LEE CO EC;2U
Adder
10.448
274766LEE CO EC;7U
Adder
10.325
972235AH1-702 GEN1
Adder
2.828
274822ROCKFORD ;11
Adder
22.02
274745AC1-111 GEN9
Adder
6.26
274682WAUKEGAN ;7U
Adder
20.129
274828WAUKEGAN ;BP
Adder
12.373
274773LINCOLN ;4U
Adder
9.447
274774LINCOLN ;5U
Adder
9.447
237046AF1-021 C
Solar/Wind Helper
0.484
238185AF2-356 C
Solar/Wind Helper
2.169
23751201ROTHROCK
Solar/Wind Helper
0.732
235054AD2-180 GEN
Solar/Wind Helper
1.687
23562501BACKB
Solar/Wind Helper
0.892
254303AC2-168 GEN
Solar/Wind Helper
0.147
238117U2-030
Solar/Wind Helper
0.284
241966AE1-183 GEN
Solar/Wind Helper
0.238
20089226LOOKOUT
Solar/Wind Helper
0.556
235531U2-073 GEN
Solar/Wind Helper
2.67
23751101LEADS_P59
Solar/Wind Helper
1.234
20088826HIGHLAND
Solar/Wind Helper
0.845
20094526CT_V3-030
Solar/Wind Helper
0.443
964201AG1-281 GEN
Solar/Wind Helper
0.454
238108AE1-109 GEN1
Solar/Wind Helper
0.084
24791305MDL-5G
Solar/Wind Harmer
1.072
24289405MTG1
50/50
11.329
24318705GVG2
50/50
11.512
24722005FLATG5
50/50
2.714
24721905FLATG4
50/50
49.756
24686205CER G4
Adder
14.71
24686405CER G5
Adder
14.651
270053AF1-130 C
Solar/Wind Harmer
6.152
970153AG2-106 GEN
Solar/Wind Harmer
22.36
970913AG2-568 GEN
Solar/Wind Harmer
12.168
971191AH1-055 GEN
Solar/Wind Harmer
32.44
960911AF2-382 GEN
Solar/Wind Harmer
11.01
972103AH1-617 GEN
Solar/Wind Harmer
29.136
971461AH1-227 GEN
Solar/Wind Harmer
7.367
270346AE1-212 GEN
Solar/Wind Harmer
11.966
957541AF2-048 GEN
Solar/Wind Harmer
2.069
970243AG2-164 GEN
Solar/Wind Harmer
33.441
970519AG2-331 GEN
Solar/Wind Harmer
22.466
970699AG2-449 GEN
Solar/Wind Harmer
14.862
943031AE2-326 GEN
Solar/Wind Harmer
4.718
971331AH1-145 GEN
Solar/Wind Harmer
11.446
247619Y1-049
Adder
0.52
972273AH1-721 GEN
Adder
100.06
970093AG2-073 GEN
Solar/Wind Harmer
12.017
966571AG1-526 GEN
Solar/Wind Harmer
26.615
970273AG2-179 GEN
Solar/Wind Harmer
4.636
3429391JKCT 9G
Adder
9.882
958121AF2-106 GEN
Solar/Wind Harmer
5.368
960741AF2-365 GEN
Solar/Wind Harmer
5.892
972167AH1-666 GEN
Solar/Wind Harmer
9.416
339250AF1-203 GEN
Solar/Wind Harmer
0.712
971155AH1-034 GEN
Solar/Wind Harmer
11.743
962251AG1-071 GEN
Solar/Wind Harmer
6.45
970193AG2-126 GEN
Solar/Wind Harmer
17.522
25196008MFTGT1
Adder
1.556
24728705AND G3
Adder
9.226
24728505AND G1
Adder
4.411
970513AG2-328 GEN
Solar/Wind Harmer
20.527
970517AG2-330 GEN
Solar/Wind Harmer
18.618
942481AE2-261 GEN
Solar/Wind Harmer
34.305
25194608D.CRK4
Adder
1.851
274760LEE CO EC;1U
Adder
10.448
274767LEE CO EC;8U
Adder
10.325
25196608WSDLE5
Adder
9.621
972236AH1-702 GEN2
Adder
2.459
274682WAUKEGAN ;7U
Adder
20.129
274772LINCOLN ;3U
Adder
9.447
237048AF1-022 C
Solar/Wind Helper
0.191
237043AE2-125 C
Solar/Wind Helper
0.174
235058AG1-386 C
Solar/Wind Helper
0.436
23750701CROSSCHOOL
Solar/Wind Helper
1.181
964991AG1-363 GEN
Solar/Wind Helper
3.632
202652Y1-033 WT C
Solar/Wind Helper
0.547
238118U2-030_1
Solar/Wind Helper
0.284
254305AE2-115 C
Solar/Wind Helper
0.203
20089126CSLMN_L13
Solar/Wind Helper
0.571
20089026BF_G21_K23
Solar/Wind Helper
0.452
238127S14_GEN_2
Solar/Wind Helper
0.669
203818AF1-086 GEN
Solar/Wind Helper
1.58
24755605MDL-5G
Solar/Wind Harmer
1.072
944201AF1-088_MTX
Adder
141.066
957141AF2-008_MTX
Adder
70.533
CPLELTFEXP_CPLE->PJM
CLTF
6.692
CBM West 2LTFEXP_CBM-W2->PJM
CBM
152.177
LAGNLTFEXP_LAGN->PJM
CLTF
22.306
CBM South 2LTFEXP_CBM-S2->PJM
CBM
24.638
TVALTFEXP_TVA->PJM
CLTF
11.394
NYPJM->LTFIMP_NY
CLTF
5.171
LGEELTFEXP_LGEE->PJM
CLTF
8.351
WECLTFEXP_WEC->PJM
CLTF
4.291
AG2-052LTFEXP_AG2-052->PJM
LTF
0.261
AH1-155LTFEXP_AH1-155->PJM
LTF
0.391
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.051
CBM South 1LTFEXP_CBM-S1->PJM
CBM
43.304
MECLTFEXP_MEC->PJM
CLTF
18.986
SIGELTFEXP_SIGE->PJM
CLTF
0.624

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P1-2_#7422_16_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7422_16_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.56 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5885.34
MW Contribution:7.33
Bus #Bus NameTypeMW Contribution
24289405MTG1
50/50
11.79
24318705GVG2
50/50
11.866
24722005FLATG5
50/50
2.714
24721905FLATG4
50/50
49.755
24686205CER G4
Adder
16.139
24686405CER G5
Adder
16.075
270053AF1-130 C
Solar/Wind Harmer
2.937
970913AG2-568 GEN
Solar/Wind Harmer
9.858
960911AF2-382 GEN
Solar/Wind Harmer
9.021
943031AE2-326 GEN
Solar/Wind Harmer
6.109
971461AH1-227 GEN
Solar/Wind Harmer
5.958
972103AH1-617 GEN
Solar/Wind Harmer
23.212
971331AH1-145 GEN
Solar/Wind Harmer
15.359
247619Y1-049
Adder
0.704
971191AH1-055 GEN
Solar/Wind Harmer
29.418
270346AE1-212 GEN
Solar/Wind Harmer
10.08
958121AF2-106 GEN
Solar/Wind Harmer
0.001
972273AH1-721 GEN
Adder
111.61
270030AE2-140 GEN
Solar/Wind Harmer
18.75
970093AG2-073 GEN
Solar/Wind Harmer
9.318
970243AG2-164 GEN
Solar/Wind Harmer
5.432
970519AG2-331 GEN
Solar/Wind Harmer
24.144
970699AG2-449 GEN
Solar/Wind Harmer
2.322
966571AG1-526 GEN
Solar/Wind Harmer
20.57
270173AC1-122 GEN
Solar/Wind Harmer
0.435
3429391JKCT 9G
Adder
10.993
970273AG2-179 GEN
Solar/Wind Harmer
5.522
972167AH1-666 GEN
Solar/Wind Harmer
7.359
962751AG1-124 GEN
Solar/Wind Harmer
8.092
339250AF1-203 GEN
Solar/Wind Harmer
0.001
971155AH1-034 GEN
Solar/Wind Harmer
10.521
960741AF2-365 GEN
Solar/Wind Harmer
4.499
962251AG1-071 GEN
Solar/Wind Harmer
5.619
958171AF2-111 GEN
Solar/Wind Harmer
22.442
270291AC1-194 GEN
Solar/Wind Harmer
7.02
25196008MFTGT1
Adder
1.692
252510AF1-249 C
Solar/Wind Harmer
0.067
25194608D.CRK4
Adder
2.039
25196608WSDLE5
Adder
10.598
253316AC1-085 GEN3
Solar/Wind Harmer
0.005
253433AC1-085 GEN1
Solar/Wind Harmer
0.004
946181AF1-283 GEN
Solar/Wind Harmer
11.009
253406AD2-031_GEN
Solar/Wind Harmer
0.624
970193AG2-126 GEN
Solar/Wind Harmer
12.39
24728705AND G3
Adder
9.464
24728505AND G1
Adder
4.525
970153AG2-106 GEN
Solar/Wind Harmer
20.57
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
3147312GRETNA
Solar/Wind Harmer
0.123
3146802CHATHAM
Solar/Wind Harmer
0.115
941801AE2-185 GEN
Solar/Wind Harmer
4.925
270356AE2-297 GEN
Solar/Wind Harmer
0.011
270222AC2-111 GEN
Solar/Wind Harmer
4.144
253415AE1-040 GEN
Solar/Wind Harmer
0.003
942481AE2-261 GEN
Solar/Wind Harmer
24.109
276621W2-048 GEN
Solar/Wind Harmer
0.403
276838X2-022 GEN2
Solar/Wind Harmer
0.45
270437AC2-090 C
Solar/Wind Harmer
0.004
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
3.68
276668AB2-070 GEN1
Solar/Wind Harmer
0.29
972173AH1-669 GEN
Solar/Wind Harmer
3.965
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
7.866
247642Z2-115 C
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
0.864
970291AG2-192 GEN
Solar/Wind Harmer
0.786
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
965091AG1-374 GEN
Solar/Wind Harmer
23.525
959611AF2-252 GEN
Solar/Wind Harmer
2.614
958821AF2-173 GEN
Solar/Wind Harmer
10.961
270004AE1-209 GEN
Solar/Wind Harmer
1.696
270273AD2-016 GEN
Solar/Wind Harmer
0.81
942111AE2-223 GEN
Solar/Wind Harmer
2.536
253370AE2-315 SEC1
Adder
2.238
253371AE2-315 SEC2
Adder
2.117
965931AG1-462 GEN
Solar/Wind Harmer
19.808
946031AF1-268 GEN
Solar/Wind Harmer
7.391
3147123OTTER R
Solar/Wind Harmer
0.087
274878BISHOP HL;2U
Solar/Wind Harmer
0.26
970191AG2-125 GEN
Solar/Wind Harmer
1.992
276157O29GEN1
Solar/Wind Harmer
1.248
274858EASY ROAD;U2
Solar/Wind Harmer
0.002
274760LEE CO EC;1U
Adder
10.252
274767LEE CO EC;8U
Adder
10.131
970571AG2-364 GEN
Solar/Wind Harmer
15.368
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
972236AH1-702 GEN2
Adder
2.406
276889AE2-281 GEN
Solar/Wind Harmer
0.001
270016AE1-250 BESS
Solar/Wind Harmer
0.004
959091AF2-200 GEN
Solar/Wind Harmer
15.301
274855GSG-6 ;RU
Solar/Wind Harmer
0.28
274850MENDOTA H;RU
Solar/Wind Harmer
0.09
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.137
274682WAUKEGAN ;7U
Adder
19.567
274729ELWOOD EC;1P
Adder
8.072
237048AF1-022 C
Solar/Wind Helper
0.182
964991AG1-363 GEN
Solar/Wind Helper
3.709
23750701CROSSCHOOL
Solar/Wind Helper
1.197
238118U2-030_1
Solar/Wind Helper
0.288
238127S14_GEN_2
Solar/Wind Helper
0.687
237043AE2-125 C
Solar/Wind Helper
0.163
202652Y1-033 WT C
Solar/Wind Helper
0.534
316097T157 G90
Solar/Wind Helper
1.094
20089126CSLMN_L13
Solar/Wind Helper
0.554
20089026BF_G21_K23
Solar/Wind Helper
0.438
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
0.329
243186AF1-051 GEN
50/50
12.748
24723005RIVRG1
Adder
37.637
24723105RIVRG2
Adder
37.637
24685805CER G1
Adder
16.117
24685905CER G2
Adder
16.117
944971AF1-162 GEN
Solar/Wind Harmer
13.01
24728205BUCHG1
Adder
7.763
971225AH1-072 GEN
Solar/Wind Harmer
2.323
971227AH1-073 GEN
Solar/Wind Harmer
2.323
971277AH1-098 GEN
Solar/Wind Harmer
4.634
270583AD2-179 GEN
Solar/Wind Harmer
11.403
960161AF2-307 GEN
Solar/Wind Harmer
6.387
971073AG2-665 GEN
Solar/Wind Harmer
8.448
270186AC1-089 GEN
Solar/Wind Harmer
0.006
970239AG2-162 GEN
Solar/Wind Harmer
2.322
942891AE2-308 GEN
Solar/Wind Harmer
9.282
972043AH1-570 GEN
Solar/Wind Harmer
2.394
972045AH1-571 GEN
Solar/Wind Harmer
1.918
339221AD2-048_GEN
Solar/Wind Harmer
0.006
966021AG1-471 GEN
Solar/Wind Harmer
4.953
971125AH1-004 GEN
Solar/Wind Harmer
3.667
970107AG2-081 GEN
Solar/Wind Harmer
2.751
971485AH1-239 GEN
Solar/Wind Harmer
7.325
962581AG1-107 GEN
Solar/Wind Harmer
0.002
971081AG2-670 GEN
Solar/Wind Harmer
6.822
970235AG2-159 GEN
Solar/Wind Harmer
5.533
970235AG2-159 GEN
Solar/Wind Harmer
3.174
970653AG2-424 GEN
Solar/Wind Harmer
4.368
970653AG2-424 GEN
Solar/Wind Harmer
2.263
339255AE2-071 GEN
Solar/Wind Harmer
-0.148
964781AG1-341 GEN
Solar/Wind Harmer
9.557
964571AG1-320 GEN
Solar/Wind Harmer
8.226
252509AD1-136 GEN
Solar/Wind Harmer
0.045
25183208HLCRTG
Solar/Wind Harmer
0.014
252519AF1-045_GEN
Solar/Wind Harmer
7.591
252516AE2-318_GEN
Solar/Wind Harmer
6.733
270444AC2-157 GEN1
Solar/Wind Harmer
0.004
971587AH1-292 GEN
Solar/Wind Harmer
6.388
25194408D.CRK1
Adder
9.381
25194508D.CRK3
Adder
1.754
253317AC1-085 GEN4
Solar/Wind Harmer
0.005
945391AF1-204 GEN
Solar/Wind Harmer
8.776
253394AE2-221_GEN
Solar/Wind Harmer
0.01
253398AE2-221_GEN2
Solar/Wind Harmer
0.01
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.002
942671AE2-283 GEN
Solar/Wind Harmer
3.83
24728805RICHG1
Adder
4.412
24728905RICHG2
Adder
4.412
276916AD2-100_GEN
Solar/Wind Harmer
16.969
24721605FLATG1
50/50
2.714
972203AH1-686 GEN
Adder
4.544
957241AF2-018 GEN
Solar/Wind Harmer
-0.002
270399AC1-101 GEN
Solar/Wind Harmer
4.077
270400AC1-102 GEN
Solar/Wind Harmer
4.077
24477305BRIDGE
Adder
0.637
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
971313AH1-133 GEN
Solar/Wind Harmer
12.016
941621AE2-160 GEN
Adder
5.66
966391AG1-508 GEN
Solar/Wind Harmer
1.802
970281AG2-184 GEN
Solar/Wind Harmer
24.373
972143AH1-644 GEN
Solar/Wind Harmer
12.573
276911AD2-131_GEN
Solar/Wind Harmer
1.118
970241AG2-163 GEN
Solar/Wind Harmer
4.709
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
24379505HDWTR1G C
Solar/Wind Harmer
0.003
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
966841AG1-555 GEN
Solar/Wind Harmer
0.9
270383AD1-128 GEN
Solar/Wind Harmer
0.005
971613AH1-306 GEN
Solar/Wind Harmer
3.767
960611AF2-352 GEN
Solar/Wind Harmer
2.614
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
970825AG2-519 GEN
Solar/Wind Harmer
8.658
960441AF2-335 GEN
Solar/Wind Harmer
7.811
253370AE2-315 SEC1
Adder
2.238
276782AC1-033 GEN
Solar/Wind Harmer
0.001
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.304
276646AC1-214 GEN2
Solar/Wind Harmer
0.304
276741O09 GEN1
Solar/Wind Harmer
0.275
276708O09 GEN2
Solar/Wind Harmer
0.275
972267AH1-718 GEN
Adder
4.6
970883AG2-550 GEN
Solar/Wind Harmer
7.705
970885AG2-551 GEN
Solar/Wind Harmer
2.568
276603SUBLETTE C
Solar/Wind Harmer
0
274764LEE CO EC;5U
Adder
10.276
274765LEE CO EC;6U
Adder
10.276
274762LEE CO EC;3U
Adder
10.252
274763LEE CO EC;4U
Adder
10.155
938861AE1-114 GEN
Solar/Wind Harmer
4.353
270599AE1-208 GEN
Solar/Wind Harmer
7.04
270031AE2-169
Solar/Wind Harmer
4.224
274856ECOGROVE ;U1
Solar/Wind Harmer
0.181
276611AD2-172 GEN
Solar/Wind Harmer
0.002
25322209TAIT E
Adder
10.707
25322209TAIT E
Adder
10.466
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
270013AE1-250 PV
Solar/Wind Harmer
0.004
971341AH1-150 GEN
Solar/Wind Harmer
15.301
971343AH1-151 GEN
Solar/Wind Harmer
15.301
274683WAUKEGAN ;8U
Adder
22.951
274683WAUKEGAN ;8U
Adder
19.347
274696ROCKY RD ;4P
Adder
12.409
274695ROCKY RD ;2P
Adder
12.123
274693ROCKY RD ;1P
Adder
12.003
274697ROCKY RD ;3P
Adder
3.293
247621Y3-024
Adder
0.262
23585401KL_K28_T16
Solar/Wind Helper
1.267
23652301WDPWR_K20
Solar/Wind Helper
0.133
238120AE2-309 GEN
Solar/Wind Helper
0.43
203955AF1-039 C O1
Solar/Wind Helper
0.352
944781AF1-143 GEN
Solar/Wind Helper
2.298
20083426SW_E13_K22
Solar/Wind Helper
0.051
20088926STNY CRK
Solar/Wind Helper
0.747
20084626FORWARD
Solar/Wind Helper
0.323
946071AF1-272 GEN
Solar/Wind Helper
2.428
203940AF1-140 C
Solar/Wind Helper
0.359
270132AB1-180 C
Adder
0.198
24734705WLF1G3
Adder
9.185
24734805WLF1G4
Adder
9.185
24734905WLF1G5
Adder
9.185
24735105WLF2G1
Adder
9.002
971061AG2-657 GEN
Solar/Wind Harmer
6.864
971985AH1-537 GEN
Solar/Wind Harmer
3.047
971981AH1-535 GEN
Solar/Wind Harmer
6.609
270069AE2-166 C O1
Solar/Wind Harmer
0.007
970879AG2-548 GEN
Solar/Wind Harmer
8.448
965401AG1-405 GEN
Solar/Wind Harmer
5.328
965411AG1-406 GEN
Solar/Wind Harmer
3.428
270367AC2-061_GEN
Solar/Wind Harmer
0.007
3429211JKCT 2G
Adder
15.52
339211AE2-254 GEN
Solar/Wind Harmer
0.004
972163AH1-664 GEN
Solar/Wind Harmer
10.275
972165AH1-665 GEN
Solar/Wind Harmer
8.229
339243AC2-075 GEN1
Solar/Wind Harmer
0.002
970455AG2-298 GEN
Solar/Wind Harmer
6.053
25196108MFTGT2
Adder
1.926
25196108MFTGT2
Adder
1.788
252524AE2-267 GEN
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
10.91
25196308WSDLE2
Adder
10.815
25196208WSDLE1
Adder
10.788
25196708WSDLE6
Adder
10.761
25196508WSDLE4
Adder
10.49
270340AC2-060 GEN
Solar/Wind Harmer
0.01
24289405MTG1
50/50
11.79
243186AF1-051 GEN
50/50
12.748
24318705GVG2
50/50
11.866
24721805FLATG3
50/50
2.714
24721705FLATG2
50/50
49.755
24723205RIVRG3
Adder
37.637
24686105CER G3
Adder
16.224
24686505CER G6
Adder
16.203
971403AH1-188 GEN
Solar/Wind Harmer
18.202
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
970947AG2-589 GEN
Solar/Wind Harmer
0.42
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
24728305BUCHG2
Adder
7.763
971687AH1-348 GEN
Solar/Wind Harmer
1.161
971329AH1-144 GEN
Solar/Wind Harmer
9.676
971315AH1-136 GEN
Solar/Wind Harmer
2.301
24735205WLF2G2
Adder
9.002
927014AC1-188 GEN
Solar/Wind Harmer
0.006
971367AH1-164 GEN
Solar/Wind Harmer
3.536
270336AE1-100 GEN
Solar/Wind Harmer
0.005
970091AG2-072 GEN
Adder
103.033
962771AG1-126 GEN
Solar/Wind Harmer
32.213
944221AF1-090 GEN
Solar/Wind Harmer
4.776
963841AG1-237 GEN
Solar/Wind Harmer
3.474
270240V3-007_GEN2
Solar/Wind Harmer
0.002
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.29
276848AB2-070 GEN3
Solar/Wind Harmer
0.289
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
1.493
270594AE1-207 GEN
Solar/Wind Harmer
8.791
270269AC2-059
Solar/Wind Harmer
0.004
970115AG2-085 GEN
Solar/Wind Harmer
3.124
276655WTG1_EQ
Solar/Wind Harmer
0.003
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
8.194
941731AE2-173 GEN
Solar/Wind Harmer
6.503
25306009OHH W.
Adder
3.223
971673AH1-337 GEN
Solar/Wind Harmer
5.07
253372AE2-315 SEC3
Adder
2.117
253372AE2-315 SEC3
Adder
2.117
971029AG2-637 GEN
Solar/Wind Harmer
11.666
946321AF1-296 GEN
Solar/Wind Harmer
4.345
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
253349AC2-067 GEN
Solar/Wind Harmer
2.438
253400AC2-068 GEN
Solar/Wind Harmer
0.981
957751AF2-069 GEN
Solar/Wind Harmer
0.255
971611AH1-305 GEN
Solar/Wind Harmer
4.596
970169AG2-114 GEN
Solar/Wind Harmer
7.718
270543AE2-219 C
Solar/Wind Harmer
0.005
961011AF2-392 GEN
Solar/Wind Harmer
4.519
926823AC1-168 GEN
Solar/Wind Harmer
1.307
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
971681AH1-341 GEN
Solar/Wind Harmer
12.366
971609AH1-304 GEN
Solar/Wind Harmer
1.254
276612AE2-035 GEN
Solar/Wind Harmer
0.002
274823ROCKFORD ;21
Adder
21.377
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971171AH1-044 GEN
Solar/Wind Harmer
15.301
970333AG2-219 GEN
Solar/Wind Harmer
6.64
3429241JKCT 3G
Adder
15.723
971821AH1-427 GEN
Solar/Wind Harmer
9.259
3429421JKCT 10G
Adder
10.993
945681AF1-233 GEN
Solar/Wind Harmer
17.357
970273AG2-179 GEN
Solar/Wind Harmer
3.221
943811AF1-049 GEN
Solar/Wind Harmer
-0.002
339216AC1-074 GEN
Solar/Wind Harmer
0.25
971565AH1-281 GEN
Solar/Wind Harmer
1.817
964901AG1-354 GEN
Solar/Wind Harmer
13.566
962241AG1-070 GEN
Solar/Wind Harmer
4.9
252507AC2-088 GEN
Solar/Wind Harmer
0.405
25196808ZIMRHP
Adder
95.812
25196008MFTGT1
Adder
1.747
270445AC2-157 GEN2
Solar/Wind Harmer
0.004
25194608D.CRK4
Adder
2.039
270018AE2-047 C O1
Solar/Wind Harmer
0.004
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
8.469
270263AC1-001 GEN
Solar/Wind Harmer
0.833
24728605AND G2
Adder
4.525
962761AG1-125 GEN
Solar/Wind Harmer
32.213
970149AG2-104 GEN
Solar/Wind Harmer
34.791
970155AG2-107 GEN
Solar/Wind Harmer
20.57
270197AD1-017 GEN1
Solar/Wind Harmer
1.016
3147312GRETNA
Solar/Wind Harmer
0.031
941821AE2-187 GEN
Solar/Wind Harmer
4.925
970773AG2-487 GEN
Solar/Wind Harmer
1.447
963741AG1-226 GEN
Solar/Wind Harmer
19.103
965911AG1-460 GEN
Solar/Wind Harmer
1.613
276615X2-022 GEN
Solar/Wind Harmer
0.084
963831AG1-236 GEN
Solar/Wind Harmer
3.11
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0.001
970613AG2-401 GEN
Solar/Wind Harmer
5.842
274880W4-005 GEN4
Solar/Wind Harmer
0.001
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
276903AD2-071 C
Solar/Wind Harmer
8.845
972175AH1-670 GEN
Solar/Wind Harmer
6.537
24791305MDL-5G
Solar/Wind Harmer
0.001
970291AG2-192 GEN
Solar/Wind Harmer
1.021
270032AE2-172
Solar/Wind Harmer
5.233
274854TWINGROVE;U2
Solar/Wind Harmer
0.003
270005AE1-210 C O1
Solar/Wind Harmer
1.696
965031AG1-367 GEN
Solar/Wind Harmer
7.829
970825AG2-519 GEN
Solar/Wind Harmer
2.773
276726Z2-087_GEN
Solar/Wind Harmer
0.003
939741AE1-205 GEN
Solar/Wind Harmer
10.926
253370AE2-315 SEC1
Adder
2.238
253371AE2-315 SEC2
Adder
2.117
274877BISHOP HL;1U
Solar/Wind Harmer
0.26
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
9.649
276158O29GEN2
Solar/Wind Harmer
0.001
274857EASY ROAD;U1
Solar/Wind Harmer
0.002
274761LEE CO EC;2U
Adder
10.252
274766LEE CO EC;7U
Adder
10.131
970569AG2-363 GEN
Solar/Wind Harmer
23.052
971475AH1-234 GEN
Solar/Wind Harmer
3.722
970819AG2-516 GEN
Solar/Wind Harmer
9.198
972235AH1-702 GEN1
Adder
2.767
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
960071AF2-298 GEN
Solar/Wind Harmer
3.815
25326309TAIT D
Adder
1.202
274822ROCKFORD ;11
Adder
21.533
957471AF2-041 GEN
Solar/Wind Harmer
22.952
959081AF2-199 GEN
Solar/Wind Harmer
7.651
971067AG2-660 GEN
Solar/Wind Harmer
2.55
939401AE1-172 GEN
Solar/Wind Harmer
5.72
971997AH1-543 GEN
Solar/Wind Harmer
4.011
276861AD2-134 GEN
Solar/Wind Harmer
0.137
945371AF1-202 GEN
Solar/Wind Harmer
0.001
274828WAUKEGAN ;BP
Adder
12.03
274682WAUKEGAN ;7U
Adder
19.567
274745AC1-111 GEN9
Adder
6.069
238185AF2-356 C
Solar/Wind Helper
2.176
237046AF1-021 C
Solar/Wind Helper
0.457
235054AD2-180 GEN
Solar/Wind Helper
1.695
238117U2-030
Solar/Wind Helper
0.288
235531U2-073 GEN
Solar/Wind Helper
2.733
23751201ROTHROCK
Solar/Wind Helper
0.71
23562501BACKB
Solar/Wind Helper
0.864
23583801GRNGAP
Solar/Wind Helper
4.088
316095T157 G97
Solar/Wind Helper
1.094
238108AE1-109 GEN1
Solar/Wind Helper
0.088
20089226LOOKOUT
Solar/Wind Helper
0.539
20088826HIGHLAND
Solar/Wind Helper
0.812
971675AH1-338 GEN
Solar/Wind Harmer
2.979
945581AF1-223 GEN
Solar/Wind Harmer
0.001
274746AC1-111 G10
Adder
6.069
274744AC1-111 GEN8
Adder
6.069
23750501ELLIOTTS
Solar/Wind Helper
0.635
238126S14_GEN_1
Solar/Wind Helper
0.687
238109AE1-109 GEN2
Solar/Wind Helper
0.088
238110AE1-109 GEN3
Solar/Wind Helper
0.088
20092526R32
Solar/Wind Helper
1.053
944201AF1-088_MTX
Adder
145.184
957141AF2-008_MTX
Adder
72.592
CPLELTFEXP_CPLE->PJM
CLTF
7.791
CBM West 2LTFEXP_CBM-W2->PJM
CBM
162.06
LAGNLTFEXP_LAGN->PJM
CLTF
24.37
CBM South 2LTFEXP_CBM-S2->PJM
CBM
29.03
TVALTFEXP_TVA->PJM
CLTF
12.655
NYPJM->LTFIMP_NY
CLTF
5.271
LGEELTFEXP_LGEE->PJM
CLTF
8.989
WECLTFEXP_WEC->PJM
CLTF
4.2
AG2-052LTFEXP_AG2-052->PJM
LTF
0.253
AH1-155LTFEXP_AH1-155->PJM
LTF
0.38
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.592
CBM South 1LTFEXP_CBM-S1->PJM
CBM
47.815
MECLTFEXP_MEC->PJM
CLTF
19.173
SIGELTFEXP_SIGE->PJM
CLTF
0.659

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P7-1_#10944___SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10944___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:106.16 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5863.47
MW Contribution:9.47
Bus #Bus NameTypeMW Contribution
24289405MTG1
50/50
11.76
243186AF1-051 GEN
50/50
12.611
24318705GVG2
50/50
11.739
24721805FLATG3
50/50
2.658
24721705FLATG2
50/50
48.723
960001AF2-291 GEN
Solar/Wind Harmer
6.065
24723205RIVRG3
Adder
37.09
270331AC1-082 GEN3
Solar/Wind Harmer
0.892
970947AG2-589 GEN
Solar/Wind Harmer
3.922
24686105CER G3
Adder
16.263
24686505CER G6
Adder
16.242
971403AH1-188 GEN
Solar/Wind Harmer
24.803
24728305BUCHG2
Adder
6.985
971315AH1-136 GEN
Solar/Wind Harmer
3.105
927014AC1-188 GEN
Solar/Wind Harmer
2.455
971687AH1-348 GEN
Solar/Wind Harmer
1.523
24735205WLF2G2
Adder
7.999
971329AH1-144 GEN
Solar/Wind Harmer
16.096
970091AG2-072 GEN
Adder
94.679
970333AG2-219 GEN
Solar/Wind Harmer
38.461
945681AF1-233 GEN
Solar/Wind Harmer
22.966
3429241JKCT 3G
Adder
14.375
971821AH1-427 GEN
Solar/Wind Harmer
12.078
3429421JKCT 10G
Adder
10.046
943111AE2-339 GEN
Solar/Wind Harmer
1.064
339216AC1-074 GEN
Solar/Wind Harmer
2.018
970273AG2-179 GEN
Solar/Wind Harmer
2.912
971565AH1-281 GEN
Solar/Wind Harmer
2.371
339241AF1-083 GEN
Solar/Wind Harmer
1.967
252507AC2-088 GEN
Solar/Wind Harmer
2.122
964901AG1-354 GEN
Solar/Wind Harmer
17.575
962241AG1-070 GEN
Solar/Wind Harmer
5.234
25196808ZIMRHP
Adder
88.001
25196008MFTGT1
Adder
1.601
25194608D.CRK4
Adder
1.865
270336AE1-100 GEN
Solar/Wind Harmer
1.949
270445AC2-157 GEN2
Solar/Wind Harmer
6.293
253432AC1-085 GEN2
Solar/Wind Harmer
0.293
946171AF1-282 GEN
Solar/Wind Harmer
10.953
971367AH1-164 GEN
Solar/Wind Harmer
3.823
943811AF1-049 GEN
Solar/Wind Harmer
4.073
270263AC1-001 GEN
Solar/Wind Harmer
1.114
24728605AND G2
Adder
4.036
963741AG1-226 GEN
Solar/Wind Harmer
46.021
965911AG1-460 GEN
Solar/Wind Harmer
1.423
962761AG1-125 GEN
Solar/Wind Harmer
40.758
253370AE2-315 SEC1
Adder
1.951
253371AE2-315 SEC2
Adder
1.845
274761LEE CO EC;2U
Adder
8.918
274766LEE CO EC;7U
Adder
8.813
972235AH1-702 GEN1
Adder
2.404
274822ROCKFORD ;11
Adder
18.707
25326309TAIT D
Adder
1.04
274828WAUKEGAN ;BP
Adder
10.429
274682WAUKEGAN ;7U
Adder
16.961
274745AC1-111 GEN9
Adder
5.257
237046AF1-021 C
Solar/Wind Helper
0.476
254303AC2-168 GEN
Solar/Wind Helper
0.153
241966AE1-183 GEN
Solar/Wind Helper
0.245
238185AF2-356 C
Solar/Wind Helper
2.079
23751201ROTHROCK
Solar/Wind Helper
0.699
24721605FLATG1
50/50
2.658
270330AC1-082 GEN2
Solar/Wind Harmer
1.51
270329AC1-082 GEN1
Solar/Wind Harmer
0.889
972203AH1-686 GEN
Adder
4.44
24477305BRIDGE
Adder
0.635
957241AF2-018 GEN
Solar/Wind Harmer
7.929
270399AC1-101 GEN
Solar/Wind Harmer
7.483
270400AC1-102 GEN
Solar/Wind Harmer
7.483
941621AE2-160 GEN
Adder
5.566
970281AG2-184 GEN
Solar/Wind Harmer
32.43
972143AH1-644 GEN
Solar/Wind Harmer
15.443
270132AB1-180 C
Adder
0.184
971313AH1-133 GEN
Solar/Wind Harmer
15.282
971061AG2-657 GEN
Solar/Wind Harmer
13.752
971985AH1-537 GEN
Solar/Wind Harmer
26.909
962211AG1-066 GEN
Solar/Wind Harmer
3.527
24734705WLF1G3
Adder
8.169
24734805WLF1G4
Adder
8.169
24734905WLF1G5
Adder
8.169
24735105WLF2G1
Adder
7.999
966391AG1-508 GEN
Solar/Wind Harmer
4.787
970879AG2-548 GEN
Solar/Wind Harmer
5.647
971981AH1-535 GEN
Solar/Wind Harmer
12.632
270367AC2-061_GEN
Solar/Wind Harmer
3.956
972163AH1-664 GEN
Solar/Wind Harmer
12.214
972165AH1-665 GEN
Solar/Wind Harmer
9.771
965401AG1-405 GEN
Solar/Wind Harmer
6.93
965411AG1-406 GEN
Solar/Wind Harmer
3.11
3429211JKCT 2G
Adder
14.189
339211AE2-254 GEN
Solar/Wind Harmer
1.83
339243AC2-075 GEN1
Solar/Wind Harmer
0.546
970455AG2-298 GEN
Solar/Wind Harmer
7.102
25196108MFTGT2
Adder
1.765
25196108MFTGT2
Adder
1.639
252524AE2-267 GEN
Solar/Wind Harmer
1.782
25196408WSDLE3
Adder
9.966
25196308WSDLE2
Adder
9.88
25196208WSDLE1
Adder
9.855
25196708WSDLE6
Adder
9.83
25196508WSDLE4
Adder
9.582
270069AE2-166 C O1
Solar/Wind Harmer
3.07
270340AC2-060 GEN
Solar/Wind Harmer
3.233
944031AF1-071 GEN
Solar/Wind Harmer
1.053
944221AF1-090 GEN
Solar/Wind Harmer
11.289
962771AG1-126 GEN
Solar/Wind Harmer
40.758
25306009OHH W.
Adder
2.813
253372AE2-315 SEC3
Adder
1.845
253372AE2-315 SEC3
Adder
1.845
274823ROCKFORD ;21
Adder
18.572
274746AC1-111 G10
Adder
5.257
274744AC1-111 GEN8
Adder
5.257
23750501ELLIOTTS
Solar/Wind Helper
0.642
254304AE2-114 C
Solar/Wind Helper
0.211
241997AF1-093 GEN
Solar/Wind Helper
0.245
241982AE2-343 S C
Solar/Wind Helper
0.214
20092526R32
Solar/Wind Helper
1.083
203846AF2-130 C
Solar/Wind Helper
0.425
238126S14_GEN_1
Solar/Wind Helper
0.64
203961AE2-224 GEN
Solar/Wind Helper
2.23
20091526CHSTN_FL
Solar/Wind Helper
0.54
20090526Q36
Solar/Wind Helper
0.964
203993AD2-133_GEN1
Solar/Wind Helper
0.964
235054AD2-180 GEN
Solar/Wind Helper
1.616
243186AF1-051 GEN
50/50
12.611
24723005RIVRG1
Adder
37.09
24723105RIVRG2
Adder
37.09
24685805CER G1
Adder
16.156
24685905CER G2
Adder
16.156
944971AF1-162 GEN
Solar/Wind Harmer
12.489
24728205BUCHG1
Adder
6.985
971225AH1-072 GEN
Solar/Wind Harmer
3.044
971227AH1-073 GEN
Solar/Wind Harmer
3.044
270214AC2-123 GEN
Solar/Wind Harmer
3.214
971277AH1-098 GEN
Solar/Wind Harmer
5.494
970879AG2-548 GEN
Solar/Wind Harmer
8.094
971073AG2-665 GEN
Solar/Wind Harmer
8.094
971073AG2-665 GEN
Solar/Wind Harmer
5.647
270583AD2-179 GEN
Solar/Wind Harmer
12.914
960161AF2-307 GEN
Solar/Wind Harmer
8.235
270186AC1-089 GEN
Solar/Wind Harmer
7.622
962581AG1-107 GEN
Solar/Wind Harmer
6.151
961491AF2-440 GEN
Solar/Wind Harmer
2.556
970239AG2-162 GEN
Solar/Wind Harmer
13.403
942891AE2-308 GEN
Solar/Wind Harmer
12.168
972043AH1-570 GEN
Solar/Wind Harmer
3.032
972045AH1-571 GEN
Solar/Wind Harmer
2.426
339221AD2-048_GEN
Solar/Wind Harmer
1.861
971125AH1-004 GEN
Solar/Wind Harmer
4.815
970107AG2-081 GEN
Solar/Wind Harmer
3.611
970235AG2-159 GEN
Solar/Wind Harmer
4.78
970235AG2-159 GEN
Solar/Wind Harmer
2.918
339231AF1-038_GEN
Solar/Wind Harmer
2.165
966021AG1-471 GEN
Solar/Wind Harmer
6.404
971485AH1-239 GEN
Solar/Wind Harmer
9.472
252509AD1-136 GEN
Solar/Wind Harmer
0.303
971081AG2-670 GEN
Solar/Wind Harmer
8.855
970653AG2-424 GEN
Solar/Wind Harmer
5.682
970653AG2-424 GEN
Solar/Wind Harmer
2.054
339236AF1-050_GEN
Solar/Wind Harmer
2.132
964571AG1-320 GEN
Solar/Wind Harmer
9.614
339255AE2-071 GEN
Solar/Wind Harmer
1.239
964781AG1-341 GEN
Solar/Wind Harmer
12.366
25183208HLCRTG
Solar/Wind Harmer
6.95
252519AF1-045_GEN
Solar/Wind Harmer
6.963
252516AE2-318_GEN
Solar/Wind Harmer
5.311
25194408D.CRK1
Adder
8.581
25194508D.CRK3
Adder
1.604
270444AC2-157 GEN1
Solar/Wind Harmer
6.293
253317AC1-085 GEN4
Solar/Wind Harmer
9.175
945391AF1-204 GEN
Solar/Wind Harmer
14.686
253394AE2-221_GEN
Solar/Wind Harmer
4.786
253398AE2-221_GEN2
Solar/Wind Harmer
4.786
24728805RICHG1
Adder
3.931
24728905RICHG2
Adder
3.931
276916AD2-100_GEN
Solar/Wind Harmer
21.483
276911AD2-131_GEN
Solar/Wind Harmer
4.342
970241AG2-163 GEN
Solar/Wind Harmer
25.567
957381AF2-032 GEN
Solar/Wind Harmer
0.427
253370AE2-315 SEC1
Adder
1.951
972267AH1-718 GEN
Adder
4.004
274764LEE CO EC;5U
Adder
8.939
274765LEE CO EC;6U
Adder
8.939
274762LEE CO EC;3U
Adder
8.918
274763LEE CO EC;4U
Adder
8.834
25322209TAIT E
Adder
9.264
25322209TAIT E
Adder
9.056
247621Y3-024
Adder
0.228
274683WAUKEGAN ;8U
Adder
19.896
274683WAUKEGAN ;8U
Adder
16.771
274696ROCKY RD ;4P
Adder
10.757
274695ROCKY RD ;2P
Adder
10.508
274693ROCKY RD ;1P
Adder
10.405
274697ROCKY RD ;3P
Adder
2.855
23652301WDPWR_K20
Solar/Wind Helper
0.139
962101AG1-054 GEN
Solar/Wind Helper
0.626
241967AE2-285_GEN
Solar/Wind Helper
0.613
241801AE1-079 GEN
Solar/Wind Helper
0.238
241985AE1-237 GEN
Solar/Wind Helper
0.238
23585401KL_K28_T16
Solar/Wind Helper
1.223
203955AF1-039 C O1
Solar/Wind Helper
0.352
944781AF1-143 GEN
Solar/Wind Helper
2.323
946071AF1-272 GEN
Solar/Wind Helper
2.537
20083426SW_E13_K22
Solar/Wind Helper
0.052
20088926STNY CRK
Solar/Wind Helper
0.764
20084626FORWARD
Solar/Wind Helper
0.332
203940AF1-140 C
Solar/Wind Helper
0.368
238120AE2-309 GEN
Solar/Wind Helper
0.4
946381AF1-302 GEN
Solar/Wind Helper
0.207
20088626ARWF_N39
Solar/Wind Helper
1.121
20303426NA_O38_P22
Solar/Wind Helper
0.919
203853AF1-134 C O1
Solar/Wind Helper
0.443
24289405MTG1
50/50
11.76
24318705GVG2
50/50
11.739
24722005FLATG5
50/50
2.658
24721905FLATG4
50/50
48.723
24686205CER G4
Adder
16.177
24686405CER G5
Adder
16.113
270053AF1-130 C
Solar/Wind Harmer
6.632
971191AH1-055 GEN
Solar/Wind Harmer
39.064
970913AG2-568 GEN
Solar/Wind Harmer
13.469
960911AF2-382 GEN
Solar/Wind Harmer
11.728
957541AF2-048 GEN
Solar/Wind Harmer
2.449
972103AH1-617 GEN
Solar/Wind Harmer
30.886
971461AH1-227 GEN
Solar/Wind Harmer
7.809
270346AE1-212 GEN
Solar/Wind Harmer
13.257
943031AE2-326 GEN
Solar/Wind Harmer
5.058
971331AH1-145 GEN
Solar/Wind Harmer
12.477
247619Y1-049
Adder
0.564
958121AF2-106 GEN
Solar/Wind Harmer
5.853
970093AG2-073 GEN
Solar/Wind Harmer
12.205
970243AG2-164 GEN
Solar/Wind Harmer
31.468
970519AG2-331 GEN
Solar/Wind Harmer
21.141
970699AG2-449 GEN
Solar/Wind Harmer
13.986
972167AH1-666 GEN
Solar/Wind Harmer
9.735
972273AH1-721 GEN
Adder
101.075
966571AG1-526 GEN
Solar/Wind Harmer
26.852
270291AC1-194 GEN
Solar/Wind Harmer
12.828
3429391JKCT 9G
Adder
10.046
970273AG2-179 GEN
Solar/Wind Harmer
4.651
958171AF2-111 GEN
Solar/Wind Harmer
29.515
339250AF1-203 GEN
Solar/Wind Harmer
0.708
971155AH1-034 GEN
Solar/Wind Harmer
11.668
960741AF2-365 GEN
Solar/Wind Harmer
5.83
962251AG1-071 GEN
Solar/Wind Harmer
6.397
25196008MFTGT1
Adder
1.55
252510AF1-249 C
Solar/Wind Harmer
0.477
25194608D.CRK4
Adder
1.865
25196608WSDLE5
Adder
9.681
270030AE2-140 GEN
Solar/Wind Harmer
22.032
253316AC1-085 GEN3
Solar/Wind Harmer
9.175
253433AC1-085 GEN1
Solar/Wind Harmer
5.824
23562501BACKB
Solar/Wind Helper
0.85
20089226LOOKOUT
Solar/Wind Helper
0.545
238117U2-030
Solar/Wind Helper
0.272
20088826HIGHLAND
Solar/Wind Helper
0.835
235531U2-073 GEN
Solar/Wind Helper
2.555
20094526CT_V3-030
Solar/Wind Helper
0.44
964201AG1-281 GEN
Solar/Wind Helper
0.449
970149AG2-104 GEN
Solar/Wind Harmer
20.717
946181AF1-283 GEN
Solar/Wind Harmer
14.239
253406AD2-031_GEN
Solar/Wind Harmer
1.378
970193AG2-126 GEN
Solar/Wind Harmer
15.807
24728705AND G3
Adder
8.441
24728505AND G1
Adder
4.036
270356AE2-297 GEN
Solar/Wind Harmer
4.782
270222AC2-111 GEN
Solar/Wind Harmer
8.539
253415AE1-040 GEN
Solar/Wind Harmer
1.167
942481AE2-261 GEN
Solar/Wind Harmer
30.502
253370AE2-315 SEC1
Adder
1.951
253371AE2-315 SEC2
Adder
1.845
274760LEE CO EC;1U
Adder
8.918
274767LEE CO EC;8U
Adder
8.813
972236AH1-702 GEN2
Adder
2.091
274682WAUKEGAN ;7U
Adder
16.961
274729ELWOOD EC;1P
Adder
6.986
237048AF1-022 C
Solar/Wind Helper
0.187
235058AG1-386 C
Solar/Wind Helper
0.451
237043AE2-125 C
Solar/Wind Helper
0.173
254305AE2-115 C
Solar/Wind Helper
0.211
202652Y1-033 WT C
Solar/Wind Helper
0.534
23750701CROSSCHOOL
Solar/Wind Helper
1.129
20089126CSLMN_L13
Solar/Wind Helper
0.56
20089026BF_G21_K23
Solar/Wind Helper
0.443
964991AG1-363 GEN
Solar/Wind Helper
3.463
238118U2-030_1
Solar/Wind Helper
0.272
203818AF1-086 GEN
Solar/Wind Helper
1.57
238127S14_GEN_2
Solar/Wind Helper
0.64
959441AF2-235 GEN
Solar/Wind Helper
0.22
944201AF1-088_MTX
Adder
131.041
957141AF2-008_MTX
Adder
65.52
CPLELTFEXP_CPLE->PJM
CLTF
7.285
CBM West 2LTFEXP_CBM-W2->PJM
CBM
144.471
LAGNLTFEXP_LAGN->PJM
CLTF
21.71
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.108
TVALTFEXP_TVA->PJM
CLTF
11.299
NYPJM->LTFIMP_NY
CLTF
5.029
LGEELTFEXP_LGEE->PJM
CLTF
8.22
WECLTFEXP_WEC->PJM
CLTF
3.65
AG2-052LTFEXP_AG2-052->PJM
LTF
0.22
AH1-155LTFEXP_AH1-155->PJM
LTF
0.329
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.529
CBM South 1LTFEXP_CBM-S1->PJM
CBM
42.883
MECLTFEXP_MEC->PJM
CLTF
16.832
SIGELTFEXP_SIGE->PJM
CLTF
0.595

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P7-1_#10856___SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10856___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:102.19 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5644.14
MW Contribution:9.57
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
2.672
270330AC1-082 GEN2
Solar/Wind Harmer
1.52
270329AC1-082 GEN1
Solar/Wind Harmer
0.895
972203AH1-686 GEN
Adder
4.469
24477305BRIDGE
Adder
0.639
957241AF2-018 GEN
Solar/Wind Harmer
7.983
270399AC1-101 GEN
Solar/Wind Harmer
7.536
270400AC1-102 GEN
Solar/Wind Harmer
7.536
941621AE2-160 GEN
Adder
5.607
970281AG2-184 GEN
Solar/Wind Harmer
32.691
972143AH1-644 GEN
Solar/Wind Harmer
15.567
270132AB1-180 C
Adder
0.186
971313AH1-133 GEN
Solar/Wind Harmer
15.406
971061AG2-657 GEN
Solar/Wind Harmer
13.864
971985AH1-537 GEN
Solar/Wind Harmer
27.131
962211AG1-066 GEN
Solar/Wind Harmer
3.557
24734705WLF1G3
Adder
8.24
24734805WLF1G4
Adder
8.24
24734905WLF1G5
Adder
8.24
24735105WLF2G1
Adder
8.071
966391AG1-508 GEN
Solar/Wind Harmer
4.83
970879AG2-548 GEN
Solar/Wind Harmer
5.701
971981AH1-535 GEN
Solar/Wind Harmer
12.756
270367AC2-061_GEN
Solar/Wind Harmer
3.995
972163AH1-664 GEN
Solar/Wind Harmer
12.338
972165AH1-665 GEN
Solar/Wind Harmer
9.871
243186AF1-051 GEN
50/50
12.674
24723005RIVRG1
Adder
37.324
24723105RIVRG2
Adder
37.324
24685805CER G1
Adder
16.259
24685905CER G2
Adder
16.259
944971AF1-162 GEN
Solar/Wind Harmer
12.576
24728205BUCHG1
Adder
7.041
971225AH1-072 GEN
Solar/Wind Harmer
3.069
971227AH1-073 GEN
Solar/Wind Harmer
3.069
270214AC2-123 GEN
Solar/Wind Harmer
3.243
971277AH1-098 GEN
Solar/Wind Harmer
5.544
970879AG2-548 GEN
Solar/Wind Harmer
8.171
971073AG2-665 GEN
Solar/Wind Harmer
8.171
971073AG2-665 GEN
Solar/Wind Harmer
5.701
270583AD2-179 GEN
Solar/Wind Harmer
13.038
960161AF2-307 GEN
Solar/Wind Harmer
8.314
270186AC1-089 GEN
Solar/Wind Harmer
7.697
962581AG1-107 GEN
Solar/Wind Harmer
6.214
961491AF2-440 GEN
Solar/Wind Harmer
2.582
970239AG2-162 GEN
Solar/Wind Harmer
13.539
965401AG1-405 GEN
Solar/Wind Harmer
7.001
965411AG1-406 GEN
Solar/Wind Harmer
3.142
3429211JKCT 2G
Adder
14.334
339211AE2-254 GEN
Solar/Wind Harmer
1.849
339243AC2-075 GEN1
Solar/Wind Harmer
0.552
970455AG2-298 GEN
Solar/Wind Harmer
7.176
25196108MFTGT2
Adder
1.784
25196108MFTGT2
Adder
1.656
252524AE2-267 GEN
Solar/Wind Harmer
1.801
25196408WSDLE3
Adder
10.076
25196308WSDLE2
Adder
9.988
25196208WSDLE1
Adder
9.963
25196708WSDLE6
Adder
9.938
25196508WSDLE4
Adder
9.688
270069AE2-166 C O1
Solar/Wind Harmer
3.104
270340AC2-060 GEN
Solar/Wind Harmer
3.271
944031AF1-071 GEN
Solar/Wind Harmer
1.065
944221AF1-090 GEN
Solar/Wind Harmer
11.424
962771AG1-126 GEN
Solar/Wind Harmer
41.255
25306009OHH W.
Adder
2.849
253372AE2-315 SEC3
Adder
1.869
253372AE2-315 SEC3
Adder
1.869
274823ROCKFORD ;21
Adder
18.813
274746AC1-111 G10
Adder
5.326
274744AC1-111 GEN8
Adder
5.326
23750501ELLIOTTS
Solar/Wind Helper
0.635
254304AE2-114 C
Solar/Wind Helper
0.208
241997AF1-093 GEN
Solar/Wind Helper
0.242
241982AE2-343 S C
Solar/Wind Helper
0.211
20092526R32
Solar/Wind Helper
1.068
203846AF2-130 C
Solar/Wind Helper
0.419
238126S14_GEN_1
Solar/Wind Helper
0.631
203961AE2-224 GEN
Solar/Wind Helper
2.198
20091526CHSTN_FL
Solar/Wind Helper
0.532
24289405MTG1
50/50
11.814
243186AF1-051 GEN
50/50
12.674
24318705GVG2
50/50
11.798
24721805FLATG3
50/50
2.672
24721705FLATG2
50/50
48.99
960001AF2-291 GEN
Solar/Wind Harmer
6.103
24723205RIVRG3
Adder
37.324
270331AC1-082 GEN3
Solar/Wind Harmer
0.897
970947AG2-589 GEN
Solar/Wind Harmer
3.947
24686105CER G3
Adder
16.366
24686505CER G6
Adder
16.345
971403AH1-188 GEN
Solar/Wind Harmer
24.977
24728305BUCHG2
Adder
7.041
971315AH1-136 GEN
Solar/Wind Harmer
3.129
927014AC1-188 GEN
Solar/Wind Harmer
2.475
971687AH1-348 GEN
Solar/Wind Harmer
1.535
24735205WLF2G2
Adder
8.071
971329AH1-144 GEN
Solar/Wind Harmer
16.245
970091AG2-072 GEN
Adder
95.631
970333AG2-219 GEN
Solar/Wind Harmer
38.852
945681AF1-233 GEN
Solar/Wind Harmer
23.2
3429241JKCT 3G
Adder
14.522
971821AH1-427 GEN
Solar/Wind Harmer
12.202
3429421JKCT 10G
Adder
10.15
943111AE2-339 GEN
Solar/Wind Harmer
1.075
339216AC1-074 GEN
Solar/Wind Harmer
2.039
970273AG2-179 GEN
Solar/Wind Harmer
2.943
971565AH1-281 GEN
Solar/Wind Harmer
2.396
339241AF1-083 GEN
Solar/Wind Harmer
1.988
252507AC2-088 GEN
Solar/Wind Harmer
2.144
964901AG1-354 GEN
Solar/Wind Harmer
17.761
962241AG1-070 GEN
Solar/Wind Harmer
5.29
25196808ZIMRHP
Adder
88.943
25196008MFTGT1
Adder
1.618
25194608D.CRK4
Adder
1.886
270336AE1-100 GEN
Solar/Wind Harmer
1.97
270445AC2-157 GEN2
Solar/Wind Harmer
6.363
253432AC1-085 GEN2
Solar/Wind Harmer
0.297
946171AF1-282 GEN
Solar/Wind Harmer
11.077
971367AH1-164 GEN
Solar/Wind Harmer
3.867
943811AF1-049 GEN
Solar/Wind Harmer
4.12
270263AC1-001 GEN
Solar/Wind Harmer
1.127
24728605AND G2
Adder
4.084
963741AG1-226 GEN
Solar/Wind Harmer
46.579
965911AG1-460 GEN
Solar/Wind Harmer
1.441
962761AG1-125 GEN
Solar/Wind Harmer
41.255
253370AE2-315 SEC1
Adder
1.976
253371AE2-315 SEC2
Adder
1.869
274761LEE CO EC;2U
Adder
9.033
274766LEE CO EC;7U
Adder
8.927
972235AH1-702 GEN1
Adder
2.436
274822ROCKFORD ;11
Adder
18.951
25326309TAIT D
Adder
1.054
274828WAUKEGAN ;BP
Adder
10.566
274682WAUKEGAN ;7U
Adder
17.184
274745AC1-111 GEN9
Adder
5.326
237046AF1-021 C
Solar/Wind Helper
0.471
254303AC2-168 GEN
Solar/Wind Helper
0.151
241966AE1-183 GEN
Solar/Wind Helper
0.242
238185AF2-356 C
Solar/Wind Helper
2.051
23751201ROTHROCK
Solar/Wind Helper
0.69
235054AD2-180 GEN
Solar/Wind Helper
1.594
23562501BACKB
Solar/Wind Helper
0.838
20089226LOOKOUT
Solar/Wind Helper
0.537
238117U2-030
Solar/Wind Helper
0.268
20088826HIGHLAND
Solar/Wind Helper
0.824
235531U2-073 GEN
Solar/Wind Helper
2.519
20094526CT_V3-030
Solar/Wind Helper
0.433
964201AG1-281 GEN
Solar/Wind Helper
0.442
970149AG2-104 GEN
Solar/Wind Harmer
20.97
942891AE2-308 GEN
Solar/Wind Harmer
12.292
972043AH1-570 GEN
Solar/Wind Harmer
3.063
972045AH1-571 GEN
Solar/Wind Harmer
2.45
339221AD2-048_GEN
Solar/Wind Harmer
1.88
971125AH1-004 GEN
Solar/Wind Harmer
4.864
970107AG2-081 GEN
Solar/Wind Harmer
3.648
970235AG2-159 GEN
Solar/Wind Harmer
4.83
970235AG2-159 GEN
Solar/Wind Harmer
2.948
339231AF1-038_GEN
Solar/Wind Harmer
2.187
966021AG1-471 GEN
Solar/Wind Harmer
6.471
971485AH1-239 GEN
Solar/Wind Harmer
9.571
252509AD1-136 GEN
Solar/Wind Harmer
0.306
971081AG2-670 GEN
Solar/Wind Harmer
8.948
970653AG2-424 GEN
Solar/Wind Harmer
5.742
970653AG2-424 GEN
Solar/Wind Harmer
2.076
339236AF1-050_GEN
Solar/Wind Harmer
2.155
964571AG1-320 GEN
Solar/Wind Harmer
9.715
339255AE2-071 GEN
Solar/Wind Harmer
1.252
964781AG1-341 GEN
Solar/Wind Harmer
12.498
25183208HLCRTG
Solar/Wind Harmer
7.025
252519AF1-045_GEN
Solar/Wind Harmer
7.038
252516AE2-318_GEN
Solar/Wind Harmer
5.369
25194408D.CRK1
Adder
8.675
25194508D.CRK3
Adder
1.622
270444AC2-157 GEN1
Solar/Wind Harmer
6.363
253317AC1-085 GEN4
Solar/Wind Harmer
9.279
945391AF1-204 GEN
Solar/Wind Harmer
14.859
253394AE2-221_GEN
Solar/Wind Harmer
4.843
253398AE2-221_GEN2
Solar/Wind Harmer
4.843
24728805RICHG1
Adder
3.978
24728905RICHG2
Adder
3.978
276916AD2-100_GEN
Solar/Wind Harmer
21.743
276911AD2-131_GEN
Solar/Wind Harmer
4.394
970241AG2-163 GEN
Solar/Wind Harmer
25.877
957381AF2-032 GEN
Solar/Wind Harmer
0.432
253370AE2-315 SEC1
Adder
1.976
972267AH1-718 GEN
Adder
4.056
274764LEE CO EC;5U
Adder
9.055
274765LEE CO EC;6U
Adder
9.055
274762LEE CO EC;3U
Adder
9.033
274763LEE CO EC;4U
Adder
8.948
25322209TAIT E
Adder
9.385
25322209TAIT E
Adder
9.175
247621Y3-024
Adder
0.231
274683WAUKEGAN ;8U
Adder
20.157
274683WAUKEGAN ;8U
Adder
16.992
274696ROCKY RD ;4P
Adder
10.898
274695ROCKY RD ;2P
Adder
10.646
274693ROCKY RD ;1P
Adder
10.542
274697ROCKY RD ;3P
Adder
2.892
23652301WDPWR_K20
Solar/Wind Helper
0.138
962101AG1-054 GEN
Solar/Wind Helper
0.618
241985AE1-237 GEN
Solar/Wind Helper
0.235
241967AE2-285_GEN
Solar/Wind Helper
0.605
241801AE1-079 GEN
Solar/Wind Helper
0.235
23585401KL_K28_T16
Solar/Wind Helper
1.207
203955AF1-039 C O1
Solar/Wind Helper
0.347
944781AF1-143 GEN
Solar/Wind Helper
2.291
946071AF1-272 GEN
Solar/Wind Helper
2.502
20083426SW_E13_K22
Solar/Wind Helper
0.052
20088926STNY CRK
Solar/Wind Helper
0.754
20084626FORWARD
Solar/Wind Helper
0.327
203940AF1-140 C
Solar/Wind Helper
0.363
238120AE2-309 GEN
Solar/Wind Helper
0.394
24289405MTG1
50/50
11.814
24318705GVG2
50/50
11.798
24722005FLATG5
50/50
2.672
24721905FLATG4
50/50
48.99
24686205CER G4
Adder
16.28
24686405CER G5
Adder
16.216
270053AF1-130 C
Solar/Wind Harmer
6.678
971191AH1-055 GEN
Solar/Wind Harmer
39.337
970913AG2-568 GEN
Solar/Wind Harmer
13.568
960911AF2-382 GEN
Solar/Wind Harmer
11.821
957541AF2-048 GEN
Solar/Wind Harmer
2.468
972103AH1-617 GEN
Solar/Wind Harmer
31.134
971461AH1-227 GEN
Solar/Wind Harmer
7.872
270346AE1-212 GEN
Solar/Wind Harmer
13.369
943031AE2-326 GEN
Solar/Wind Harmer
5.103
971331AH1-145 GEN
Solar/Wind Harmer
12.593
247619Y1-049
Adder
0.569
958121AF2-106 GEN
Solar/Wind Harmer
5.909
970093AG2-073 GEN
Solar/Wind Harmer
12.329
970243AG2-164 GEN
Solar/Wind Harmer
31.788
970519AG2-331 GEN
Solar/Wind Harmer
21.356
970699AG2-449 GEN
Solar/Wind Harmer
14.128
972167AH1-666 GEN
Solar/Wind Harmer
9.834
972273AH1-721 GEN
Adder
102.108
966571AG1-526 GEN
Solar/Wind Harmer
27.128
270291AC1-194 GEN
Solar/Wind Harmer
12.959
3429391JKCT 9G
Adder
10.15
970273AG2-179 GEN
Solar/Wind Harmer
4.7
958171AF2-111 GEN
Solar/Wind Harmer
29.825
339250AF1-203 GEN
Solar/Wind Harmer
0.715
971155AH1-034 GEN
Solar/Wind Harmer
11.792
960741AF2-365 GEN
Solar/Wind Harmer
5.892
962251AG1-071 GEN
Solar/Wind Harmer
6.465
25196008MFTGT1
Adder
1.567
252510AF1-249 C
Solar/Wind Harmer
0.482
25194608D.CRK4
Adder
1.886
25196608WSDLE5
Adder
9.788
270030AE2-140 GEN
Solar/Wind Harmer
22.282
253316AC1-085 GEN3
Solar/Wind Harmer
9.279
253433AC1-085 GEN1
Solar/Wind Harmer
5.89
946181AF1-283 GEN
Solar/Wind Harmer
14.4
253406AD2-031_GEN
Solar/Wind Harmer
1.394
970193AG2-126 GEN
Solar/Wind Harmer
15.993
24728705AND G3
Adder
8.541
24728505AND G1
Adder
4.084
270356AE2-297 GEN
Solar/Wind Harmer
4.839
270222AC2-111 GEN
Solar/Wind Harmer
8.641
253415AE1-040 GEN
Solar/Wind Harmer
1.181
942481AE2-261 GEN
Solar/Wind Harmer
30.873
253370AE2-315 SEC1
Adder
1.976
253371AE2-315 SEC2
Adder
1.869
274760LEE CO EC;1U
Adder
9.033
274767LEE CO EC;8U
Adder
8.927
972236AH1-702 GEN2
Adder
2.118
274682WAUKEGAN ;7U
Adder
17.184
274729ELWOOD EC;1P
Adder
7.078
237048AF1-022 C
Solar/Wind Helper
0.185
235058AG1-386 C
Solar/Wind Helper
0.446
237043AE2-125 C
Solar/Wind Helper
0.171
254305AE2-115 C
Solar/Wind Helper
0.208
202652Y1-033 WT C
Solar/Wind Helper
0.526
23750701CROSSCHOOL
Solar/Wind Helper
1.114
20089126CSLMN_L13
Solar/Wind Helper
0.552
20089026BF_G21_K23
Solar/Wind Helper
0.437
964991AG1-363 GEN
Solar/Wind Helper
3.415
238118U2-030_1
Solar/Wind Helper
0.268
203818AF1-086 GEN
Solar/Wind Helper
1.548
238127S14_GEN_2
Solar/Wind Helper
0.631
944201AF1-088_MTX
Adder
132.484
957141AF2-008_MTX
Adder
66.242
CPLELTFEXP_CPLE->PJM
CLTF
7.421
CBM West 2LTFEXP_CBM-W2->PJM
CBM
146.148
LAGNLTFEXP_LAGN->PJM
CLTF
21.962
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.485
TVALTFEXP_TVA->PJM
CLTF
11.425
NYPJM->LTFIMP_NY
CLTF
4.949
LGEELTFEXP_LGEE->PJM
CLTF
8.306
WECLTFEXP_WEC->PJM
CLTF
3.698
AG2-052LTFEXP_AG2-052->PJM
LTF
0.222
AH1-155LTFEXP_AH1-155->PJM
LTF
0.334
CBM West 1LTFEXP_CBM-W1->PJM
CBM
123.346
CBM South 1LTFEXP_CBM-S1->PJM
CBM
43.356
MECLTFEXP_MEC->PJM
CLTF
17.041
SIGELTFEXP_SIGE->PJM
CLTF
0.602

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P1-2_#309_15_SRT-A


Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#309_15_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:141.78 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:2183.34
MW Contribution:2.5
Bus #Bus NameTypeMW Contribution
24803006KYGER 3HP
50/50
4.181
24802806KYGER 2HP
50/50
4.156
24802906KYGER 2LP
50/50
2.443
252509AD1-136 GEN
Solar/Wind Harmer
0.042
25183208HLCRTG
Solar/Wind Harmer
0.012
252519AF1-045_GEN
Solar/Wind Harmer
6.799
252516AE2-318_GEN
Solar/Wind Harmer
6.03
25194408D.CRK1
Adder
8.173
25194508D.CRK3
Adder
1.528
253317AC1-085 GEN4
Solar/Wind Harmer
0.005
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
270186AC1-089 GEN
Solar/Wind Harmer
0.004
962581AG1-107 GEN
Solar/Wind Harmer
0.001
970235AG2-159 GEN
Solar/Wind Harmer
3.893
970235AG2-159 GEN
Solar/Wind Harmer
2.234
339221AD2-048_GEN
Solar/Wind Harmer
0.004
972043AH1-570 GEN
Solar/Wind Harmer
1.576
972045AH1-571 GEN
Solar/Wind Harmer
1.263
253370AE2-315 SEC1
Adder
1.718
971125AH1-004 GEN
Solar/Wind Harmer
2.354
970107AG2-081 GEN
Solar/Wind Harmer
1.765
25322209TAIT E
Adder
8.088
25322209TAIT E
Adder
7.906
25326109MON D
Adder
1.064
24728805RICHG1
Adder
2.986
24728905RICHG2
Adder
2.986
942891AE2-308 GEN
Solar/Wind Harmer
5.244
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0.003
960161AF2-307 GEN
Solar/Wind Harmer
3.231
970883AG2-550 GEN
Solar/Wind Harmer
4.773
970885AG2-551 GEN
Solar/Wind Harmer
1.591
970825AG2-519 GEN
Solar/Wind Harmer
5.021
964571AG1-320 GEN
Solar/Wind Harmer
4.118
960441AF2-335 GEN
Solar/Wind Harmer
4.504
247621Y3-024
Adder
0.155
964611AG1-324 GEN
Solar/Wind Harmer
0.33
970239AG2-162 GEN
Solar/Wind Harmer
1.093
270201AC2-176 GEN
Solar/Wind Harmer
0.001
970653AG2-424 GEN
Solar/Wind Harmer
2.075
970653AG2-424 GEN
Solar/Wind Harmer
1.075
971613AH1-306 GEN
Solar/Wind Harmer
2.042
270518AE2-148 GEN
Solar/Wind Harmer
0.367
270599AE1-208 GEN
Solar/Wind Harmer
3.89
270031AE2-169
Solar/Wind Harmer
2.334
270444AC2-157 GEN1
Solar/Wind Harmer
0.002
971587AH1-292 GEN
Solar/Wind Harmer
3.032
25326509SID D
Adder
0.76
944541AF1-119 GEN
Solar/Wind Harmer
0.266
960971AF2-388 GEN
Solar/Wind Harmer
2.332
945391AF1-204 GEN
Solar/Wind Harmer
4.178
971081AG2-670 GEN
Solar/Wind Harmer
2.902
942221AE2-234 GEN
Solar/Wind Harmer
0.019
253378AE2-206_GEN
Solar/Wind Harmer
0.002
276820AF1-078_GEN
Solar/Wind Harmer
0.001
970329AG2-216 GEN
Solar/Wind Harmer
1.613
970241AG2-163 GEN
Solar/Wind Harmer
2.169
970077AG2-063 GEN
Solar/Wind Harmer
2.064
966841AG1-555 GEN
Solar/Wind Harmer
0.406
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
276916AD2-100_GEN
Solar/Wind Harmer
7.156
276911AD2-131_GEN
Solar/Wind Harmer
0.471
24803106KYGER 3LP
50/50
2.461
24803306KYGER 4LP
50/50
2.41
971191AH1-055 GEN
Solar/Wind Harmer
70.447
25194608D.CRK4
Adder
1.777
25196608WSDLE5
Adder
9.26
252510AF1-249 C
Solar/Wind Harmer
0.058
253316AC1-085 GEN3
Solar/Wind Harmer
0.005
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
9.726
958171AF2-111 GEN
Solar/Wind Harmer
17.961
25196008MFTGT1
Adder
1.385
972173AH1-669 GEN
Solar/Wind Harmer
3.407
972167AH1-666 GEN
Solar/Wind Harmer
5.387
253406AD2-031_GEN
Solar/Wind Harmer
0.496
270273AD2-016 GEN
Solar/Wind Harmer
0.676
253415AE1-040 GEN
Solar/Wind Harmer
0.003
270222AC2-111 GEN
Solar/Wind Harmer
3.033
253370AE2-315 SEC1
Adder
1.718
253371AE2-315 SEC2
Adder
1.625
970191AG2-125 GEN
Solar/Wind Harmer
1.473
3429391JKCT 9G
Adder
6.595
270356AE2-297 GEN
Solar/Wind Harmer
0.007
270437AC2-090 C
Solar/Wind Harmer
0.002
970093AG2-073 GEN
Solar/Wind Harmer
4.986
966571AG1-526 GEN
Solar/Wind Harmer
10.654
24728705AND G3
Adder
5.404
24728505AND G1
Adder
2.584
253338AC1-165 GEN
Solar/Wind Harmer
0.002
253333AC1-068 GEN
Solar/Wind Harmer
0.007
958821AF2-173 GEN
Solar/Wind Harmer
6.409
270004AE1-209 GEN
Solar/Wind Harmer
0.992
946031AF1-268 GEN
Solar/Wind Harmer
4.321
970243AG2-164 GEN
Solar/Wind Harmer
2.557
970519AG2-331 GEN
Solar/Wind Harmer
11.364
970699AG2-449 GEN
Solar/Wind Harmer
1.093
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
6.542
970289AG2-191 GEN
Solar/Wind Harmer
0.457
970291AG2-192 GEN
Solar/Wind Harmer
0.416
247642Z2-115 C
Solar/Wind Harmer
0.002
971617AH1-308 GEN
Solar/Wind Harmer
3.313
970193AG2-126 GEN
Solar/Wind Harmer
5.898
960741AF2-365 GEN
Solar/Wind Harmer
1.874
944531AF1-118 GEN
Solar/Wind Harmer
16.287
970605AG2-385 GEN
Solar/Wind Harmer
2.184
972273AH1-721 GEN
Adder
42.389
24755605MDL-5G
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.498
970273AG2-179 GEN
Solar/Wind Harmer
2.077
962251AG1-071 GEN
Solar/Wind Harmer
2.135
339250AF1-203 GEN
Solar/Wind Harmer
0.001
942481AE2-261 GEN
Solar/Wind Harmer
10.156
971155AH1-034 GEN
Solar/Wind Harmer
3.958
276621W2-048 GEN
Solar/Wind Harmer
0.17
276838X2-022 GEN2
Solar/Wind Harmer
0.19
276686W4-005 GEN3
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
1.555
276668AB2-070 GEN1
Solar/Wind Harmer
0.123
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
964401AG1-302 GEN
Solar/Wind Harmer
0
274853TWINGROVE;U1
Solar/Wind Harmer
0.001
965091AG1-374 GEN
Solar/Wind Harmer
9.838
959611AF2-252 GEN
Solar/Wind Harmer
1.093
942111AE2-223 GEN
Solar/Wind Harmer
1.059
270535AF1-215 GEN1
Solar/Wind Harmer
0.004
970513AG2-328 GEN
Solar/Wind Harmer
1.366
970517AG2-330 GEN
Solar/Wind Harmer
8.195
274878BISHOP HL;2U
Solar/Wind Harmer
0.105
970571AG2-364 GEN
Solar/Wind Harmer
6.209
942051AE2-217 GEN
Solar/Wind Harmer
5.584
276889AE2-281 GEN
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0.001
276897AD1-100 C
Solar/Wind Harmer
0.004
939351AE1-166 GEN
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.496
276893AG1-478 C
Solar/Wind Harmer
0.121
274729ELWOOD EC;1P
Adder
7.212
274730ELWOOD EC;6P
Adder
7.212
274734ELWOOD EC;8P
Adder
7.212
274736ELWOOD EC;9P
Adder
7.212
972228AH1-698 GEN2
Adder
1.624
276806AD2-047 C O1
Solar/Wind Harmer
1.732
970941AG2-585 GEN
Solar/Wind Harmer
3.821
274676JOLIET 29;8U
Adder
12.942
274800UNIV PARK;3U
Adder
2.55
972038AH1-567 GEN2
Adder
0.16
274855GSG-6 ;RU
Solar/Wind Harmer
0.112
274850MENDOTA H;RU
Solar/Wind Harmer
0.036
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.055
276799AD1-013 GEN
Solar/Wind Harmer
0.001
339255AE2-071 GEN
Solar/Wind Harmer
-0.056
964781AG1-341 GEN
Solar/Wind Harmer
3.601
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
942861AE2-305 GEN
Solar/Wind Harmer
2.586
960611AF2-352 GEN
Solar/Wind Harmer
1.093
970321AG2-212 GEN
Solar/Wind Harmer
1.366
274851PROVIDENC;RU
Solar/Wind Harmer
0
274849CRESCENT ;1U
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.123
276646AC1-214 GEN2
Solar/Wind Harmer
0.123
971485AH1-239 GEN
Solar/Wind Harmer
2.495
276782AC1-033 GEN
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
274879MINONK ;1U
Solar/Wind Harmer
0.13
958491AF2-143 GEN
Solar/Wind Harmer
4.624
966021AG1-471 GEN
Solar/Wind Harmer
1.664
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.416
958481AF2-142 GEN
Solar/Wind Harmer
4.61
276741O09 GEN1
Solar/Wind Harmer
0.109
276708O09 GEN2
Solar/Wind Harmer
0.109
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
274888KELLY CRK;1U
Solar/Wind Harmer
0.18
274887GEN-1.85
Solar/Wind Harmer
0.08
276843GEN-1.7
Solar/Wind Harmer
0.099
958011AF2-095 GEN
Solar/Wind Harmer
4.402
274674JOLIET 9 ;6U
Adder
6.747
972259AH1-714 GEN
Adder
8.351
276603SUBLETTE C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
1.821
971341AH1-150 GEN
Solar/Wind Harmer
6.1
971343AH1-151 GEN
Solar/Wind Harmer
6.1
274803UNIV PARK;6U
Adder
2.549
938861AE1-114 GEN
Solar/Wind Harmer
1.728
962691AG1-118 GEN
Solar/Wind Harmer
9.146
274764LEE CO EC;5U
Adder
4.075
274765LEE CO EC;6U
Adder
2.574
970921AG2-575 GEN
Solar/Wind Harmer
3.048
970921AG2-575 GEN
Solar/Wind Harmer
1.016
971573AH1-285 GEN
Solar/Wind Harmer
0.568
237033AB1-150 GEN
Solar/Wind Helper
0.403
971333AH1-146 GEN
Solar/Wind Harmer
3.002
971335AH1-147 GEN
Solar/Wind Harmer
3.002
946671AF1-331 GEN
Solar/Wind Harmer
0.325
959091AF2-200 GEN
Solar/Wind Harmer
6.1
274802UNIV PARK;5U
Adder
2.549
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
965931AG1-462 GEN
Solar/Wind Harmer
7.774
274872LEEDK;1U
Solar/Wind Harmer
0.112
235780M24_1
Solar/Wind Helper
0.999
24803406KYGER 5HP
50/50
4.134
24803206KYGER 4HP
50/50
4.13
252507AC2-088 GEN
Solar/Wind Harmer
0.38
25196808ZIMRHP
Adder
83.68
25194608D.CRK4
Adder
1.777
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.481
25196008MFTGT1
Adder
1.431
945681AF1-233 GEN
Solar/Wind Harmer
12.638
270263AC1-001 GEN
Solar/Wind Harmer
0.653
339216AC1-074 GEN
Solar/Wind Harmer
0.174
253370AE2-315 SEC1
Adder
1.718
253371AE2-315 SEC2
Adder
1.625
25326309TAIT D
Adder
0.908
960071AF2-298 GEN
Solar/Wind Harmer
2.849
3429421JKCT 10G
Adder
6.595
3429241JKCT 3G
Adder
9.082
970773AG2-487 GEN
Solar/Wind Harmer
0.935
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
3.657
971565AH1-281 GEN
Solar/Wind Harmer
0.959
24728605AND G2
Adder
2.584
253343AC1-166 GEN
Solar/Wind Harmer
0.002
253325AC1-069 GEN
Solar/Wind Harmer
0.007
247536S-71 GEN
Solar/Wind Harmer
0.185
270005AE1-210 C O1
Solar/Wind Harmer
0.992
965031AG1-367 GEN
Solar/Wind Harmer
4.578
970825AG2-519 GEN
Solar/Wind Harmer
1.608
971821AH1-427 GEN
Solar/Wind Harmer
4.505
970091AG2-072 GEN
Adder
49.379
970333AG2-219 GEN
Solar/Wind Harmer
3.125
276903AD2-071 C
Solar/Wind Harmer
4.849
270032AE2-172
Solar/Wind Harmer
2.837
945371AF1-202 GEN
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.54
270445AC2-157 GEN2
Solar/Wind Harmer
0.002
958861AF2-177 GEN
Solar/Wind Harmer
1.758
965651AG1-433 GEN
Solar/Wind Harmer
1.166
270159DARBY CT4
Adder
4.759
963741AG1-226 GEN
Solar/Wind Harmer
8.802
970593AG2-378 GEN
Solar/Wind Harmer
0.808
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.001
964901AG1-354 GEN
Solar/Wind Harmer
5.358
24791305MDL-5G
Solar/Wind Harmer
0
970273AG2-179 GEN
Solar/Wind Harmer
1.212
962241AG1-070 GEN
Solar/Wind Harmer
1.862
965911AG1-460 GEN
Solar/Wind Harmer
0.679
276615X2-022 GEN
Solar/Wind Harmer
0.035
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
4.214
963831AG1-236 GEN
Solar/Wind Harmer
1.313
274880W4-005 GEN4
Solar/Wind Harmer
0
972175AH1-670 GEN
Solar/Wind Harmer
2.749
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.279
958381AF2-132 GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0.001
276726Z2-087_GEN
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
4.562
270055AF2-134 C O1
Solar/Wind Harmer
0.002
970373AG2-245 GEN
Solar/Wind Harmer
6.619
970245AG2-165 GEN
Solar/Wind Harmer
1.366
939401AE1-172 GEN
Solar/Wind Harmer
2.35
274877BISHOP HL;1U
Solar/Wind Harmer
0.105
970569AG2-363 GEN
Solar/Wind Harmer
9.313
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
971997AH1-543 GEN
Solar/Wind Harmer
1.624
276901AD2-066 C O1
Solar/Wind Harmer
0.003
941551AE2-152 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.372
276158O29GEN2
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
7.212
276776AD2-060 GEN
Solar/Wind Harmer
0.319
274674JOLIET 9 ;6U
Adder
6.747
274676JOLIET 29;8U
Adder
13.422
274801UNIV PARK;4U
Adder
2.55
274745AC1-111 GEN9
Adder
2.444
276861AD2-134 GEN
Solar/Wind Harmer
0.055
957471AF2-041 GEN
Solar/Wind Harmer
9.15
959081AF2-199 GEN
Solar/Wind Harmer
3.05
971067AG2-660 GEN
Solar/Wind Harmer
1.017
274872LEEDK;1U
Solar/Wind Harmer
0.002
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
962781AG1-127 GEN
Solar/Wind Harmer
2.901
960001AF2-291 GEN
Solar/Wind Helper
1.676
270331AC1-082 GEN3
Solar/Wind Helper
0.198
24802606KYGER 1HP
50/50
4.205
24802706KYGER 1LP
50/50
2.468
24803506KYGER 5LP
50/50
2.41
25016408BKJDB1
50/50
0.29
25183008BIOENL
50/50
0.032
971985AH1-537 GEN
Solar/Wind Harmer
5.902
252524AE2-267 GEN
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
9.532
25196308WSDLE2
Adder
9.449
25196208WSDLE1
Adder
9.426
25196708WSDLE6
Adder
9.402
25196508WSDLE4
Adder
9.165
25196108MFTGT2
Adder
1.577
25196108MFTGT2
Adder
1.464
972163AH1-664 GEN
Solar/Wind Harmer
7.374
972165AH1-665 GEN
Solar/Wind Harmer
5.906
270367AC2-061_GEN
Solar/Wind Harmer
0.005
270269AC2-059
Solar/Wind Harmer
0.004
270340AC2-060 GEN
Solar/Wind Harmer
0.007
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
253372AE2-315 SEC3
Adder
1.625
253372AE2-315 SEC3
Adder
1.625
25306009OHH W.
Adder
2.427
970689AG2-444 GEN
Solar/Wind Harmer
11.775
253349AC2-067 GEN
Solar/Wind Harmer
1.803
253400AC2-068 GEN
Solar/Wind Harmer
0.725
3429211JKCT 2G
Adder
8.965
270432AC2-029 GEN
Solar/Wind Harmer
2.302
971673AH1-337 GEN
Solar/Wind Harmer
3.274
270240V3-007_GEN2
Solar/Wind Harmer
0.001
971029AG2-637 GEN
Solar/Wind Harmer
7.455
241972AD1-140 GEN
Solar/Wind Harmer
0.537
270543AE2-219 C
Solar/Wind Harmer
0.003
970455AG2-298 GEN
Solar/Wind Harmer
3.084
339211AE2-254 GEN
Solar/Wind Harmer
0.002
970115AG2-085 GEN
Solar/Wind Harmer
1.802
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
270594AE1-207 GEN
Solar/Wind Harmer
4.766
971609AH1-304 GEN
Solar/Wind Harmer
0.693
945581AF1-223 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.789
965101AG1-375 GEN
Solar/Wind Harmer
4.056
270024AE2-089 GEN
Solar/Wind Harmer
0.004
965401AG1-405 GEN
Solar/Wind Harmer
2.199
965411AG1-406 GEN
Solar/Wind Harmer
1.415
270156DARBY CT1
Adder
4.836
270157DARBY CT2
Adder
4.825
270158DARBY CT3
Adder
4.747
24729505KEY G4
Adder
3.463
972203AH1-686 GEN
Adder
1.225
963841AG1-237 GEN
Solar/Wind Harmer
1.584
945631AF1-228 GEN
Solar/Wind Harmer
0
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
24387005FR-3G C
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
944221AF1-090 GEN
Solar/Wind Harmer
2.022
971611AH1-305 GEN
Solar/Wind Harmer
2.007
276785W4-005 GEN1
Solar/Wind Harmer
0
276174W4-005 GEN2
Solar/Wind Harmer
0
276849AB2-070 GEN2
Solar/Wind Harmer
0.123
276848AB2-070 GEN3
Solar/Wind Harmer
0.122
963791AG1-232 GEN
Solar/Wind Harmer
4.535
958391AF2-133 GEN
Solar/Wind Harmer
0
943861AF1-054 GEN
Solar/Wind Harmer
1.276
943851AF1-053 GEN
Solar/Wind Harmer
0.884
276655WTG1_EQ
Solar/Wind Harmer
0.001
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.422
941731AE2-173 GEN
Solar/Wind Harmer
2.716
270536AF1-215 GEN2
Solar/Wind Harmer
0.004
270071AF1-092 GEN
Solar/Wind Harmer
6.133
970169AG2-114 GEN
Solar/Wind Harmer
3.189
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
957751AF2-069 GEN
Solar/Wind Harmer
0.103
926823AC1-168 GEN
Solar/Wind Harmer
0.529
276868AE1-113 GEN
Solar/Wind Harmer
0.619
276882AE2-255 GEN
Solar/Wind Harmer
0.361
970833AG2-524 GEN
Solar/Wind Harmer
3.372
970833AG2-524 GEN
Solar/Wind Harmer
2.248
274731ELWOOD EC;2P
Adder
7.212
274733ELWOOD EC;3P
Adder
7.212
274735ELWOOD EC;4P
Adder
7.212
274728ELWOOD EC;5P
Adder
7.212
972227AH1-698 GEN1
Adder
1.144
960591AF2-350 GEN
Solar/Wind Harmer
3.057
961011AF2-392 GEN
Solar/Wind Harmer
1.791
274675JOLIET 29;7U
Adder
13.422
274675JOLIET 29;7U
Adder
12.942
274687WILL CNTY;4U
Adder
12.222
274687WILL CNTY;4U
Adder
12.222
971681AH1-341 GEN
Solar/Wind Harmer
4.912
274746AC1-111 G10
Adder
2.444
274744AC1-111 GEN8
Adder
2.444
971171AH1-044 GEN
Solar/Wind Harmer
6.1
971675AH1-338 GEN
Solar/Wind Harmer
1.189
972037AH1-567 GEN1
Adder
0.08
946321AF1-296 GEN
Solar/Wind Harmer
1.708
270330AC1-082 GEN2
Solar/Wind Helper
0.041
270329AC1-082 GEN1
Solar/Wind Helper
0.199
944201AF1-088_MTX
Adder
68.911
957141AF2-008_MTX
Adder
34.455
CBM West 2LTFEXP_CBM-W2->PJM
CBM
53.937
LAGNLTFEXP_LAGN->PJM
CLTF
5.672
TVALTFEXP_TVA->PJM
CLTF
2.671
NYPJM->LTFIMP_NY
CLTF
1.591
LGEELTFEXP_LGEE->PJM
CLTF
5.309
WECLTFEXP_WEC->PJM
CLTF
1.664
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.623
AG2-052LTFEXP_AG2-052->PJM
LTF
0.109
AH1-155LTFEXP_AH1-155->PJM
LTF
0.163
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.271
CBM West 1LTFEXP_CBM-W1->PJM
CBM
65.759
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.454
MECLTFEXP_MEC->PJM
CLTF
7.145
SIGELTFEXP_SIGE->PJM
CLTF
0.331

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P1-2_#709_546_SRT-A


Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#709_546_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:141.21 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:2174.62
MW Contribution:2.63
Bus #Bus NameTypeMW Contribution
24803106KYGER 3LP
50/50
2.428
24803306KYGER 4LP
50/50
2.378
971191AH1-055 GEN
Solar/Wind Harmer
68.522
25196608WSDLE5
Adder
8.99
25194608D.CRK4
Adder
1.724
252510AF1-249 C
Solar/Wind Harmer
0.056
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
9.265
25196008MFTGT1
Adder
1.357
958171AF2-111 GEN
Solar/Wind Harmer
17.326
972167AH1-666 GEN
Solar/Wind Harmer
5.211
253406AD2-031_GEN
Solar/Wind Harmer
0.471
972173AH1-669 GEN
Solar/Wind Harmer
3.114
270273AD2-016 GEN
Solar/Wind Harmer
0.618
253415AE1-040 GEN
Solar/Wind Harmer
0.002
270222AC2-111 GEN
Solar/Wind Harmer
2.968
253370AE2-315 SEC1
Adder
1.649
253371AE2-315 SEC2
Adder
1.56
970191AG2-125 GEN
Solar/Wind Harmer
1.42
3429391JKCT 9G
Adder
6.526
270356AE2-297 GEN
Solar/Wind Harmer
0.007
970093AG2-073 GEN
Solar/Wind Harmer
4.983
270437AC2-090 C
Solar/Wind Harmer
0.002
966571AG1-526 GEN
Solar/Wind Harmer
10.726
24728705AND G3
Adder
5.44
24728505AND G1
Adder
2.601
970243AG2-164 GEN
Solar/Wind Harmer
2.75
970519AG2-331 GEN
Solar/Wind Harmer
12.22
970699AG2-449 GEN
Solar/Wind Harmer
1.175
958821AF2-173 GEN
Solar/Wind Harmer
6.381
270004AE1-209 GEN
Solar/Wind Harmer
0.988
946031AF1-268 GEN
Solar/Wind Harmer
4.297
253338AC1-165 GEN
Solar/Wind Harmer
0.002
253333AC1-068 GEN
Solar/Wind Harmer
0.007
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
6.485
970289AG2-191 GEN
Solar/Wind Harmer
0.462
970291AG2-192 GEN
Solar/Wind Harmer
0.42
247642Z2-115 C
Solar/Wind Harmer
0.002
970193AG2-126 GEN
Solar/Wind Harmer
6.094
971617AH1-308 GEN
Solar/Wind Harmer
3.288
960741AF2-365 GEN
Solar/Wind Harmer
1.942
972273AH1-721 GEN
Adder
44.027
944531AF1-118 GEN
Solar/Wind Harmer
16.271
24755605MDL-5G
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.627
970273AG2-179 GEN
Solar/Wind Harmer
2.166
962251AG1-071 GEN
Solar/Wind Harmer
2.234
339250AF1-203 GEN
Solar/Wind Harmer
0.001
971155AH1-034 GEN
Solar/Wind Harmer
4.144
942481AE2-261 GEN
Solar/Wind Harmer
10.562
276621W2-048 GEN
Solar/Wind Harmer
0.177
276838X2-022 GEN2
Solar/Wind Harmer
0.197
276686W4-005 GEN3
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
1.614
276668AB2-070 GEN1
Solar/Wind Harmer
0.127
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
274853TWINGROVE;U1
Solar/Wind Harmer
0.001
965091AG1-374 GEN
Solar/Wind Harmer
10.197
959611AF2-252 GEN
Solar/Wind Harmer
1.133
964401AG1-302 GEN
Solar/Wind Harmer
0.001
942111AE2-223 GEN
Solar/Wind Harmer
1.097
970605AG2-385 GEN
Solar/Wind Harmer
2.043
270535AF1-215 GEN1
Solar/Wind Harmer
0.004
970513AG2-328 GEN
Solar/Wind Harmer
1.415
970517AG2-330 GEN
Solar/Wind Harmer
8.489
274878BISHOP HL;2U
Solar/Wind Harmer
0.108
970571AG2-364 GEN
Solar/Wind Harmer
6.432
276889AE2-281 GEN
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0.001
24803006KYGER 3HP
50/50
4.124
24802806KYGER 2HP
50/50
4.1
24802906KYGER 2LP
50/50
2.411
252509AD1-136 GEN
Solar/Wind Harmer
0.041
25183208HLCRTG
Solar/Wind Harmer
0.012
252519AF1-045_GEN
Solar/Wind Harmer
6.564
252516AE2-318_GEN
Solar/Wind Harmer
5.822
25194408D.CRK1
Adder
7.931
25194508D.CRK3
Adder
1.483
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
253394AE2-221_GEN
Solar/Wind Harmer
0.008
253398AE2-221_GEN2
Solar/Wind Harmer
0.008
970235AG2-159 GEN
Solar/Wind Harmer
3.857
970235AG2-159 GEN
Solar/Wind Harmer
2.213
276157O29GEN1
Solar/Wind Harmer
0.515
276694AA1-018 GEN2
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
0.004
939351AE1-166 GEN
Solar/Wind Harmer
0
965931AG1-462 GEN
Solar/Wind Harmer
8.083
276893AG1-478 C
Solar/Wind Harmer
0.125
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274729ELWOOD EC;1P
Adder
7.45
274730ELWOOD EC;6P
Adder
7.45
274734ELWOOD EC;8P
Adder
7.45
274736ELWOOD EC;9P
Adder
7.45
274760LEE CO EC;1U
Adder
4.217
274767LEE CO EC;8U
Adder
4.167
959091AF2-200 GEN
Solar/Wind Harmer
6.32
274855GSG-6 ;RU
Solar/Wind Harmer
0.116
24803406KYGER 5HP
50/50
4.078
24803206KYGER 4HP
50/50
4.075
252507AC2-088 GEN
Solar/Wind Harmer
0.367
25196808ZIMRHP
Adder
80.97
25194608D.CRK4
Adder
1.724
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.127
25196008MFTGT1
Adder
1.401
945681AF1-233 GEN
Solar/Wind Harmer
12.229
339216AC1-074 GEN
Solar/Wind Harmer
0.17
270263AC1-001 GEN
Solar/Wind Harmer
0.594
253370AE2-315 SEC1
Adder
1.649
253371AE2-315 SEC2
Adder
1.56
25326309TAIT D
Adder
0.872
960071AF2-298 GEN
Solar/Wind Harmer
2.739
3429421JKCT 10G
Adder
6.526
3429241JKCT 3G
Adder
9.013
970773AG2-487 GEN
Solar/Wind Harmer
0.928
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
3.628
971565AH1-281 GEN
Solar/Wind Harmer
0.973
970091AG2-072 GEN
Adder
52.877
24728605AND G2
Adder
2.601
970333AG2-219 GEN
Solar/Wind Harmer
3.361
971821AH1-427 GEN
Solar/Wind Harmer
4.564
270005AE1-210 C O1
Solar/Wind Harmer
0.988
965031AG1-367 GEN
Solar/Wind Harmer
4.558
247536S-71 GEN
Solar/Wind Harmer
0.183
970825AG2-519 GEN
Solar/Wind Harmer
1.602
276903AD2-071 C
Solar/Wind Harmer
4.881
253343AC1-166 GEN
Solar/Wind Harmer
0.002
253325AC1-069 GEN
Solar/Wind Harmer
0.007
270445AC2-157 GEN2
Solar/Wind Harmer
0.002
270032AE2-172
Solar/Wind Harmer
2.855
945371AF1-202 GEN
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.546
958861AF2-177 GEN
Solar/Wind Harmer
1.753
965651AG1-433 GEN
Solar/Wind Harmer
1.163
963741AG1-226 GEN
Solar/Wind Harmer
9.112
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.001
964901AG1-354 GEN
Solar/Wind Harmer
5.578
24791305MDL-5G
Solar/Wind Harmer
0
970273AG2-179 GEN
Solar/Wind Harmer
1.264
962241AG1-070 GEN
Solar/Wind Harmer
1.948
965911AG1-460 GEN
Solar/Wind Harmer
0.707
276615X2-022 GEN
Solar/Wind Harmer
0.037
963831AG1-236 GEN
Solar/Wind Harmer
1.363
274880W4-005 GEN4
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
4.362
270159DARBY CT4
Adder
4.382
972175AH1-670 GEN
Solar/Wind Harmer
2.852
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.423
274854TWINGROVE;U2
Solar/Wind Harmer
0.001
958381AF2-132 GEN
Solar/Wind Harmer
0.001
276726Z2-087_GEN
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
4.726
970593AG2-378 GEN
Solar/Wind Harmer
0.756
270055AF2-134 C O1
Solar/Wind Harmer
0.003
970245AG2-165 GEN
Solar/Wind Harmer
1.415
970373AG2-245 GEN
Solar/Wind Harmer
6.824
939401AE1-172 GEN
Solar/Wind Harmer
2.429
274877BISHOP HL;1U
Solar/Wind Harmer
0.108
970569AG2-363 GEN
Solar/Wind Harmer
9.647
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
971997AH1-543 GEN
Solar/Wind Harmer
1.681
276901AD2-066 C O1
Solar/Wind Harmer
0.003
24802606KYGER 1HP
50/50
4.148
24802706KYGER 1LP
50/50
2.435
24803506KYGER 5LP
50/50
2.378
25016408BKJDB1
50/50
0.282
25183008BIOENL
50/50
0.031
971985AH1-537 GEN
Solar/Wind Harmer
5.794
252524AE2-267 GEN
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
9.254
25196308WSDLE2
Adder
9.174
25196208WSDLE1
Adder
9.151
25196708WSDLE6
Adder
9.128
25196508WSDLE4
Adder
8.898
25196108MFTGT2
Adder
1.544
25196108MFTGT2
Adder
1.434
972163AH1-664 GEN
Solar/Wind Harmer
7.142
972165AH1-665 GEN
Solar/Wind Harmer
5.72
270367AC2-061_GEN
Solar/Wind Harmer
0.005
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
270340AC2-060 GEN
Solar/Wind Harmer
0.007
270269AC2-059
Solar/Wind Harmer
0.003
253372AE2-315 SEC3
Adder
1.56
253372AE2-315 SEC3
Adder
1.56
25306009OHH W.
Adder
2.334
253349AC2-067 GEN
Solar/Wind Harmer
1.738
253400AC2-068 GEN
Solar/Wind Harmer
0.699
3429211JKCT 2G
Adder
8.896
970689AG2-444 GEN
Solar/Wind Harmer
10.729
971673AH1-337 GEN
Solar/Wind Harmer
3.222
270240V3-007_GEN2
Solar/Wind Harmer
0.001
971029AG2-637 GEN
Solar/Wind Harmer
7.342
270543AE2-219 C
Solar/Wind Harmer
0.003
270432AC2-029 GEN
Solar/Wind Harmer
2.087
970455AG2-298 GEN
Solar/Wind Harmer
3.135
241972AD1-140 GEN
Solar/Wind Harmer
0.511
339211AE2-254 GEN
Solar/Wind Harmer
0.002
970115AG2-085 GEN
Solar/Wind Harmer
1.796
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
270594AE1-207 GEN
Solar/Wind Harmer
4.796
971609AH1-304 GEN
Solar/Wind Harmer
0.692
945581AF1-223 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.797
965101AG1-375 GEN
Solar/Wind Harmer
4.045
965401AG1-405 GEN
Solar/Wind Harmer
2.261
965411AG1-406 GEN
Solar/Wind Harmer
1.454
270024AE2-089 GEN
Solar/Wind Harmer
0.004
963841AG1-237 GEN
Solar/Wind Harmer
1.641
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
270186AC1-089 GEN
Solar/Wind Harmer
0.004
962581AG1-107 GEN
Solar/Wind Harmer
0.001
339221AD2-048_GEN
Solar/Wind Harmer
0.004
972043AH1-570 GEN
Solar/Wind Harmer
1.547
972045AH1-571 GEN
Solar/Wind Harmer
1.239
971125AH1-004 GEN
Solar/Wind Harmer
2.32
970107AG2-081 GEN
Solar/Wind Harmer
1.74
253370AE2-315 SEC1
Adder
1.649
25322209TAIT E
Adder
7.765
25322209TAIT E
Adder
7.591
24728805RICHG1
Adder
2.942
24728905RICHG2
Adder
2.942
25326109MON D
Adder
1.02
942891AE2-308 GEN
Solar/Wind Harmer
5.216
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0.003
960161AF2-307 GEN
Solar/Wind Harmer
3.205
970883AG2-550 GEN
Solar/Wind Harmer
4.71
970885AG2-551 GEN
Solar/Wind Harmer
1.57
970239AG2-162 GEN
Solar/Wind Harmer
1.175
964571AG1-320 GEN
Solar/Wind Harmer
4.203
970825AG2-519 GEN
Solar/Wind Harmer
5.003
960441AF2-335 GEN
Solar/Wind Harmer
4.491
247621Y3-024
Adder
0.153
970653AG2-424 GEN
Solar/Wind Harmer
2.124
970653AG2-424 GEN
Solar/Wind Harmer
1.101
964611AG1-324 GEN
Solar/Wind Harmer
0.327
270444AC2-157 GEN1
Solar/Wind Harmer
0.002
971587AH1-292 GEN
Solar/Wind Harmer
3.178
270201AC2-176 GEN
Solar/Wind Harmer
0.001
971613AH1-306 GEN
Solar/Wind Harmer
2.055
270599AE1-208 GEN
Solar/Wind Harmer
3.884
270031AE2-169
Solar/Wind Harmer
2.33
945391AF1-204 GEN
Solar/Wind Harmer
4.317
971081AG2-670 GEN
Solar/Wind Harmer
2.994
270518AE2-148 GEN
Solar/Wind Harmer
0.344
944541AF1-119 GEN
Solar/Wind Harmer
0.266
960971AF2-388 GEN
Solar/Wind Harmer
2.326
25326509SID D
Adder
0.727
970241AG2-163 GEN
Solar/Wind Harmer
2.246
942221AE2-234 GEN
Solar/Wind Harmer
0.019
966841AG1-555 GEN
Solar/Wind Harmer
0.421
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
339255AE2-071 GEN
Solar/Wind Harmer
-0.058
253378AE2-206_GEN
Solar/Wind Harmer
0.002
276820AF1-078_GEN
Solar/Wind Harmer
0.001
970329AG2-216 GEN
Solar/Wind Harmer
1.538
964781AG1-341 GEN
Solar/Wind Harmer
3.771
276916AD2-100_GEN
Solar/Wind Harmer
7.444
276911AD2-131_GEN
Solar/Wind Harmer
0.49
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
960611AF2-352 GEN
Solar/Wind Harmer
1.133
970077AG2-063 GEN
Solar/Wind Harmer
1.932
971485AH1-239 GEN
Solar/Wind Harmer
2.635
970321AG2-212 GEN
Solar/Wind Harmer
1.415
966021AG1-471 GEN
Solar/Wind Harmer
1.759
274851PROVIDENC;RU
Solar/Wind Harmer
0
274849CRESCENT ;1U
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.127
276646AC1-214 GEN2
Solar/Wind Harmer
0.127
276782AC1-033 GEN
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
274879MINONK ;1U
Solar/Wind Harmer
0.135
24387005FR-3G C
Solar/Wind Harmer
0.001
24729505KEY G4
Adder
3.458
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
944221AF1-090 GEN
Solar/Wind Harmer
2.105
276785W4-005 GEN1
Solar/Wind Harmer
0
276174W4-005 GEN2
Solar/Wind Harmer
0
276849AB2-070 GEN2
Solar/Wind Harmer
0.127
276848AB2-070 GEN3
Solar/Wind Harmer
0.127
971611AH1-305 GEN
Solar/Wind Harmer
2.078
270156DARBY CT1
Adder
4.453
270157DARBY CT2
Adder
4.442
270158DARBY CT3
Adder
4.371
958391AF2-133 GEN
Solar/Wind Harmer
0.001
276655WTG1_EQ
Solar/Wind Harmer
0.001
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.544
941731AE2-173 GEN
Solar/Wind Harmer
2.813
963791AG1-232 GEN
Solar/Wind Harmer
4.514
945631AF1-228 GEN
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0.004
970169AG2-114 GEN
Solar/Wind Harmer
3.3
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
270071AF1-092 GEN
Solar/Wind Harmer
6.21
957751AF2-069 GEN
Solar/Wind Harmer
0.107
926823AC1-168 GEN
Solar/Wind Harmer
0.548
276868AE1-113 GEN
Solar/Wind Harmer
0.641
276882AE2-255 GEN
Solar/Wind Harmer
0.373
958491AF2-143 GEN
Solar/Wind Harmer
4.784
276741O09 GEN1
Solar/Wind Harmer
0.113
276708O09 GEN2
Solar/Wind Harmer
0.113
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.43
958481AF2-142 GEN
Solar/Wind Harmer
4.767
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
276603SUBLETTE C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
1.89
938861AE1-114 GEN
Solar/Wind Harmer
1.792
274764LEE CO EC;5U
Adder
4.227
274765LEE CO EC;6U
Adder
4.227
274762LEE CO EC;3U
Adder
4.217
274763LEE CO EC;4U
Adder
4.177
971341AH1-150 GEN
Solar/Wind Harmer
6.32
971343AH1-151 GEN
Solar/Wind Harmer
6.32
274856ECOGROVE ;U1
Solar/Wind Harmer
0.075
276611AD2-172 GEN
Solar/Wind Harmer
0.001
274674JOLIET 9 ;6U
Adder
6.97
971333AH1-146 GEN
Solar/Wind Harmer
6.312
971335AH1-147 GEN
Solar/Wind Harmer
6.312
274888KELLY CRK;1U
Solar/Wind Harmer
0.185
274887GEN-1.85
Solar/Wind Harmer
0.083
276843GEN-1.7
Solar/Wind Harmer
0.102
958011AF2-095 GEN
Solar/Wind Harmer
4.544
970921AG2-575 GEN
Solar/Wind Harmer
3.156
970921AG2-575 GEN
Solar/Wind Harmer
1.052
962691AG1-118 GEN
Solar/Wind Harmer
9.466
972259AH1-714 GEN
Adder
8.624
274696ROCKY RD ;4P
Adder
5.152
274695ROCKY RD ;2P
Adder
5.033
274693ROCKY RD ;1P
Adder
4.983
274697ROCKY RD ;3P
Adder
1.367
237033AB1-150 GEN
Solar/Wind Helper
0.407
276158O29GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.385
941551AE2-152 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274732ELWOOD EC;7P
Adder
7.45
274761LEE CO EC;2U
Adder
4.217
274766LEE CO EC;7U
Adder
4.167
957471AF2-041 GEN
Solar/Wind Harmer
9.481
959081AF2-199 GEN
Solar/Wind Harmer
3.16
971067AG2-660 GEN
Solar/Wind Harmer
1.053
276861AD2-134 GEN
Solar/Wind Harmer
0.057
274674JOLIET 9 ;6U
Adder
6.97
972235AH1-702 GEN1
Adder
1.141
274872LEEDK;1U
Solar/Wind Harmer
0.002
970819AG2-516 GEN
Solar/Wind Harmer
3.788
276776AD2-060 GEN
Solar/Wind Harmer
0.329
274822ROCKFORD ;11
Adder
8.878
962781AG1-127 GEN
Solar/Wind Harmer
3.003
274745AC1-111 GEN9
Adder
2.527
274676JOLIET 29;8U
Adder
13.865
274850MENDOTA H;RU
Solar/Wind Harmer
0.037
960001AF2-291 GEN
Solar/Wind Helper
1.732
270331AC1-082 GEN3
Solar/Wind Helper
0.208
946321AF1-296 GEN
Solar/Wind Harmer
1.775
961011AF2-392 GEN
Solar/Wind Harmer
1.859
970833AG2-524 GEN
Solar/Wind Harmer
3.484
970833AG2-524 GEN
Solar/Wind Harmer
2.323
971681AH1-341 GEN
Solar/Wind Harmer
5.094
274731ELWOOD EC;2P
Adder
7.45
274733ELWOOD EC;3P
Adder
7.45
274735ELWOOD EC;4P
Adder
7.45
274728ELWOOD EC;5P
Adder
7.45
971171AH1-044 GEN
Solar/Wind Harmer
6.32
971675AH1-338 GEN
Solar/Wind Harmer
1.232
972227AH1-698 GEN1
Adder
1.181
276612AE2-035 GEN
Solar/Wind Harmer
0.001
274823ROCKFORD ;21
Adder
8.814
960591AF2-350 GEN
Solar/Wind Harmer
3.156
274746AC1-111 G10
Adder
2.527
274744AC1-111 GEN8
Adder
2.527
274675JOLIET 29;7U
Adder
13.865
274675JOLIET 29;7U
Adder
0.85
270330AC1-082 GEN2
Solar/Wind Helper
0.043
270329AC1-082 GEN1
Solar/Wind Helper
0.209
971411AH1-196 GEN
Solar/Wind Harmer
0.519
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.057
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.337
972228AH1-698 GEN2
Adder
1.677
972236AH1-702 GEN2
Adder
0.992
274872LEEDK;1U
Solar/Wind Harmer
0.116
276806AD2-047 C O1
Solar/Wind Harmer
1.788
970941AG2-585 GEN
Solar/Wind Harmer
3.945
235780M24_1
Solar/Wind Helper
1.009
944201AF1-088_MTX
Adder
72.238
957141AF2-008_MTX
Adder
36.119
CBM West 2LTFEXP_CBM-W2->PJM
CBM
57.499
LAGNLTFEXP_LAGN->PJM
CLTF
6.342
TVALTFEXP_TVA->PJM
CLTF
3.038
NYPJM->LTFIMP_NY
CLTF
1.588
LGEELTFEXP_LGEE->PJM
CLTF
5.37
WECLTFEXP_WEC->PJM
CLTF
1.725
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.352
AG2-052LTFEXP_AG2-052->PJM
LTF
0.112
AH1-155LTFEXP_AH1-155->PJM
LTF
0.168
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.09
CBM West 1LTFEXP_CBM-W1->PJM
CBM
67.313
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.642
MECLTFEXP_MEC->PJM
CLTF
7.485
SIGELTFEXP_SIGE->PJM
CLTF
0.339

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P2-2_#6763_05BIERSR 345_2_SRT-A


Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#6763_05BIERSR 345_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:135.59 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:2088.16
MW Contribution:3.72
Bus #Bus NameTypeMW Contribution
24803406KYGER 5HP
50/50
4.162
24803206KYGER 4HP
50/50
4.159
270263AC1-001 GEN
Solar/Wind Harmer
1.225
252507AC2-088 GEN
Solar/Wind Harmer
2.082
25196808ZIMRHP
Adder
80.646
25194608D.CRK4
Adder
1.702
253432AC1-085 GEN2
Solar/Wind Harmer
0.275
946171AF1-282 GEN
Solar/Wind Harmer
10.256
25196008MFTGT1
Adder
1.367
945681AF1-233 GEN
Solar/Wind Harmer
17.786
339216AC1-074 GEN
Solar/Wind Harmer
1.493
943111AE2-339 GEN
Solar/Wind Harmer
0.717
253370AE2-315 SEC1
Adder
1.591
253371AE2-315 SEC2
Adder
1.505
3429421JKCT 10G
Adder
6.507
25326309TAIT D
Adder
0.835
3429241JKCT 3G
Adder
8.993
960071AF2-298 GEN
Solar/Wind Harmer
3.766
971565AH1-281 GEN
Solar/Wind Harmer
1.333
942081AE2-220 GEN
Solar/Wind Harmer
4.218
270239V3-007_GEN1
Solar/Wind Harmer
1.135
971821AH1-427 GEN
Solar/Wind Harmer
6.444
24728605AND G2
Adder
2.377
270005AE1-210 C O1
Solar/Wind Harmer
3.277
965031AG1-367 GEN
Solar/Wind Harmer
5.997
247536S-71 GEN
Solar/Wind Harmer
2.426
970825AG2-519 GEN
Solar/Wind Harmer
1.394
339241AF1-083 GEN
Solar/Wind Harmer
0.937
276903AD2-071 C
Solar/Wind Harmer
5.625
253343AC1-166 GEN
Solar/Wind Harmer
0.608
253325AC1-069 GEN
Solar/Wind Harmer
0.586
970091AG2-072 GEN
Adder
42.53
270032AE2-172
Solar/Wind Harmer
2.553
945371AF1-202 GEN
Solar/Wind Harmer
3.81
970291AG2-192 GEN
Solar/Wind Harmer
0.693
970333AG2-219 GEN
Solar/Wind Harmer
16.705
270445AC2-157 GEN2
Solar/Wind Harmer
2.94
958861AF2-177 GEN
Solar/Wind Harmer
5.717
964901AG1-354 GEN
Solar/Wind Harmer
7.741
965651AG1-433 GEN
Solar/Wind Harmer
2.793
970273AG2-179 GEN
Solar/Wind Harmer
1.244
962241AG1-070 GEN
Solar/Wind Harmer
2.225
963741AG1-226 GEN
Solar/Wind Harmer
21.164
24385905FR-11G C
Solar/Wind Harmer
3.734
24803006KYGER 3HP
50/50
4.209
24802606KYGER 1HP
50/50
4.234
24802706KYGER 1LP
50/50
2.485
24803506KYGER 5LP
50/50
2.427
25016408BKJDB1
50/50
0.281
25183008BIOENL
50/50
0.031
971985AH1-537 GEN
Solar/Wind Harmer
50.621
270269AC2-059
Solar/Wind Harmer
11.349
252524AE2-267 GEN
Solar/Wind Harmer
1.629
25196408WSDLE3
Adder
9.115
25196308WSDLE2
Adder
9.036
25196208WSDLE1
Adder
9.013
25196708WSDLE6
Adder
8.99
25196508WSDLE4
Adder
8.764
270340AC2-060 GEN
Solar/Wind Harmer
3.131
25196108MFTGT2
Adder
1.507
25196108MFTGT2
Adder
1.4
270367AC2-061_GEN
Solar/Wind Harmer
3.017
972163AH1-664 GEN
Solar/Wind Harmer
9.331
972165AH1-665 GEN
Solar/Wind Harmer
7.465
339243AC2-075 GEN1
Solar/Wind Harmer
0.404
270432AC2-029 GEN
Solar/Wind Harmer
6.133
944031AF1-071 GEN
Solar/Wind Harmer
0.808
253372AE2-315 SEC3
Adder
1.505
253372AE2-315 SEC3
Adder
1.505
25306009OHH W.
Adder
2.25
3429211JKCT 2G
Adder
8.876
253349AC2-067 GEN
Solar/Wind Harmer
3.779
253400AC2-068 GEN
Solar/Wind Harmer
1.52
971673AH1-337 GEN
Solar/Wind Harmer
3.058
270240V3-007_GEN2
Solar/Wind Harmer
4.082
339211AE2-254 GEN
Solar/Wind Harmer
0.993
971029AG2-637 GEN
Solar/Wind Harmer
9.823
970455AG2-298 GEN
Solar/Wind Harmer
3.88
270543AE2-219 C
Solar/Wind Harmer
3.206
241972AD1-140 GEN
Solar/Wind Harmer
2.785
970115AG2-085 GEN
Solar/Wind Harmer
2.353
24725505WLD G2 C
Solar/Wind Harmer
2.288
24699105WLD G1 C
Solar/Wind Harmer
2.261
961761AG1-017 GEN
Solar/Wind Harmer
0.242
965401AG1-405 GEN
Solar/Wind Harmer
3.224
965411AG1-406 GEN
Solar/Wind Harmer
1.447
270594AE1-207 GEN
Solar/Wind Harmer
8.066
945581AF1-223 GEN
Solar/Wind Harmer
2.476
965461AG1-414 GEN
Solar/Wind Harmer
1.209
970289AG2-191 GEN
Solar/Wind Harmer
1.013
965101AG1-375 GEN
Solar/Wind Harmer
5.23
958711AF2-162 GEN
Solar/Wind Harmer
0.517
270024AE2-089 GEN
Solar/Wind Harmer
2.39
24729505KEY G4
Adder
3.077
963841AG1-237 GEN
Solar/Wind Harmer
5.029
24386205FR-12G C
Solar/Wind Harmer
1.926
24386405FR-21G C
Solar/Wind Harmer
1.932
24386605FR-22G C
Solar/Wind Harmer
1.932
24387005FR-3G C
Solar/Wind Harmer
1.777
270330AC1-082 GEN2
Solar/Wind Helper
0.039
270329AC1-082 GEN1
Solar/Wind Helper
0.188
24802806KYGER 2HP
50/50
4.185
24802906KYGER 2LP
50/50
2.46
252509AD1-136 GEN
Solar/Wind Harmer
0.297
25183208HLCRTG
Solar/Wind Harmer
6.65
252519AF1-045_GEN
Solar/Wind Harmer
6.541
252516AE2-318_GEN
Solar/Wind Harmer
4.99
25194408D.CRK1
Adder
7.828
25194508D.CRK3
Adder
1.464
253317AC1-085 GEN4
Solar/Wind Harmer
8.59
253394AE2-221_GEN
Solar/Wind Harmer
4.35
253398AE2-221_GEN2
Solar/Wind Harmer
4.35
270186AC1-089 GEN
Solar/Wind Harmer
5.71
962581AG1-107 GEN
Solar/Wind Harmer
4.635
961491AF2-440 GEN
Solar/Wind Harmer
1.926
970235AG2-159 GEN
Solar/Wind Harmer
3.527
970235AG2-159 GEN
Solar/Wind Harmer
2.153
339221AD2-048_GEN
Solar/Wind Harmer
1.344
972043AH1-570 GEN
Solar/Wind Harmer
2.133
972045AH1-571 GEN
Solar/Wind Harmer
1.707
971125AH1-004 GEN
Solar/Wind Harmer
3.309
970107AG2-081 GEN
Solar/Wind Harmer
2.482
253370AE2-315 SEC1
Adder
1.591
25322209TAIT E
Adder
7.443
25322209TAIT E
Adder
7.276
942891AE2-308 GEN
Solar/Wind Harmer
7.449
25326109MON D
Adder
0.971
24728805RICHG1
Adder
2.784
24728905RICHG2
Adder
2.784
960161AF2-307 GEN
Solar/Wind Harmer
4.571
24379505HDWTR1G C
Solar/Wind Harmer
5.217
270209AC1-174_GEN
Solar/Wind Harmer
3.682
926881AC1-175 GEN
Solar/Wind Harmer
3.682
270383AD1-128 GEN
Solar/Wind Harmer
3.962
964571AG1-320 GEN
Solar/Wind Harmer
5.136
970883AG2-550 GEN
Solar/Wind Harmer
6.261
970885AG2-551 GEN
Solar/Wind Harmer
1.456
970653AG2-424 GEN
Solar/Wind Harmer
2.916
970653AG2-424 GEN
Solar/Wind Harmer
1.054
970825AG2-519 GEN
Solar/Wind Harmer
6.248
960441AF2-335 GEN
Solar/Wind Harmer
5.883
247621Y3-024
Adder
0.14
964611AG1-324 GEN
Solar/Wind Harmer
0.674
964611AG1-324 GEN
Solar/Wind Harmer
0.299
270201AC2-176 GEN
Solar/Wind Harmer
2.909
971081AG2-670 GEN
Solar/Wind Harmer
4.164
270599AE1-208 GEN
Solar/Wind Harmer
4.481
270031AE2-169
Solar/Wind Harmer
4.481
339236AF1-050_GEN
Solar/Wind Harmer
0.967
970239AG2-162 GEN
Solar/Wind Harmer
5.822
270444AC2-157 GEN1
Solar/Wind Harmer
2.94
339231AF1-038_GEN
Solar/Wind Harmer
0.928
944541AF1-119 GEN
Solar/Wind Harmer
2.14
960971AF2-388 GEN
Solar/Wind Harmer
5.586
25326509SID D
Adder
0.665
945391AF1-204 GEN
Solar/Wind Harmer
7.039
339255AE2-071 GEN
Solar/Wind Harmer
0.525
964781AG1-341 GEN
Solar/Wind Harmer
5.228
270518AE2-148 GEN
Solar/Wind Harmer
5.786
942221AE2-234 GEN
Solar/Wind Harmer
0.35
970241AG2-163 GEN
Solar/Wind Harmer
11.758
971485AH1-239 GEN
Solar/Wind Harmer
3.722
966021AG1-471 GEN
Solar/Wind Harmer
2.491
253378AE2-206_GEN
Solar/Wind Harmer
1.656
276820AF1-078_GEN
Solar/Wind Harmer
0.736
966841AG1-555 GEN
Solar/Wind Harmer
0.721
24387305FR-4G C
Solar/Wind Harmer
2.283
960001AF2-291 GEN
Solar/Wind Helper
1.622
270331AC1-082 GEN3
Solar/Wind Helper
0.187
24803106KYGER 3LP
50/50
2.478
24803306KYGER 4LP
50/50
2.427
971191AH1-055 GEN
Solar/Wind Harmer
87.457
972173AH1-669 GEN
Solar/Wind Harmer
6.452
270273AD2-016 GEN
Solar/Wind Harmer
3.245
252510AF1-249 C
Solar/Wind Harmer
0.433
25194608D.CRK4
Adder
1.702
25196608WSDLE5
Adder
8.854
253316AC1-085 GEN3
Solar/Wind Harmer
8.59
253433AC1-085 GEN1
Solar/Wind Harmer
5.453
946181AF1-283 GEN
Solar/Wind Harmer
13.332
958171AF2-111 GEN
Solar/Wind Harmer
25.055
25196008MFTGT1
Adder
1.324
253415AE1-040 GEN
Solar/Wind Harmer
1.099
972167AH1-666 GEN
Solar/Wind Harmer
7.578
253406AD2-031_GEN
Solar/Wind Harmer
1.187
270222AC2-111 GEN
Solar/Wind Harmer
6.559
253303V4-073 C
Solar/Wind Harmer
0.092
253370AE2-315 SEC1
Adder
1.591
253371AE2-315 SEC2
Adder
1.505
3429391JKCT 9G
Adder
6.507
970093AG2-073 GEN
Solar/Wind Harmer
7.118
270356AE2-297 GEN
Solar/Wind Harmer
3.213
966571AG1-526 GEN
Solar/Wind Harmer
15.167
270437AC2-090 C
Solar/Wind Harmer
3.683
24728705AND G3
Adder
4.972
24728505AND G1
Adder
2.377
958821AF2-173 GEN
Solar/Wind Harmer
8.396
270004AE1-209 GEN
Solar/Wind Harmer
3.277
946031AF1-268 GEN
Solar/Wind Harmer
4.924
962031AG1-047 GEN
Solar/Wind Harmer
1.711
957741AF2-068 GEN
Solar/Wind Harmer
8.489
253338AC1-165 GEN
Solar/Wind Harmer
0.608
253333AC1-068 GEN
Solar/Wind Harmer
0.586
960741AF2-365 GEN
Solar/Wind Harmer
2.673
970289AG2-191 GEN
Solar/Wind Harmer
0.409
970291AG2-192 GEN
Solar/Wind Harmer
0.372
970243AG2-164 GEN
Solar/Wind Harmer
13.668
970519AG2-331 GEN
Solar/Wind Harmer
9.183
970699AG2-449 GEN
Solar/Wind Harmer
6.075
972273AH1-721 GEN
Adder
43.806
247642Z2-115 C
Solar/Wind Harmer
0.033
970273AG2-179 GEN
Solar/Wind Harmer
1.986
971617AH1-308 GEN
Solar/Wind Harmer
2.961
970193AG2-126 GEN
Solar/Wind Harmer
7.576
339250AF1-203 GEN
Solar/Wind Harmer
0.3
962251AG1-071 GEN
Solar/Wind Harmer
2.72
971155AH1-034 GEN
Solar/Wind Harmer
4.929
944531AF1-118 GEN
Solar/Wind Harmer
16.137
944201AF1-088_MTX
Adder
61.225
957141AF2-008_MTX
Adder
30.613
CBM West 2LTFEXP_CBM-W2->PJM
CBM
52.847
LAGNLTFEXP_LAGN->PJM
CLTF
6.069
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.548
TVALTFEXP_TVA->PJM
CLTF
2.997
NYPJM->LTFIMP_NY
CLTF
1.498
LGEELTFEXP_LGEE->PJM
CLTF
5.05
WECLTFEXP_WEC->PJM
CLTF
1.467
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.1
AG2-052LTFEXP_AG2-052->PJM
LTF
0.095
AH1-155LTFEXP_AH1-155->PJM
LTF
0.142
CBM West 1LTFEXP_CBM-W1->PJM
CBM
58.569
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.203
MECLTFEXP_MEC->PJM
CLTF
6.527
SIGELTFEXP_SIGE->PJM
CLTF
0.311

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o 34569 34598 34524_SRT-A


Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
34569 34598 34524_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:132.73 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:2044.01
MW Contribution:3.69
Bus #Bus NameTypeMW Contribution
24802606KYGER 1HP
50/50
4.181
24802706KYGER 1LP
50/50
2.454
24803506KYGER 5LP
50/50
2.396
25016408BKJDB1
50/50
0.293
25250008NTE_CT
50/50
1.921
25250108NTE_ST
50/50
1.463
971985AH1-537 GEN
Solar/Wind Harmer
50.537
252524AE2-267 GEN
Solar/Wind Harmer
1.791
25196408WSDLE3
Adder
10.017
25196308WSDLE2
Adder
9.93
25196208WSDLE1
Adder
9.905
25196708WSDLE6
Adder
9.88
25196508WSDLE4
Adder
9.631
25196108MFTGT2
Adder
1.576
25196108MFTGT2
Adder
1.463
972163AH1-664 GEN
Solar/Wind Harmer
9.197
972165AH1-665 GEN
Solar/Wind Harmer
7.358
270367AC2-061_GEN
Solar/Wind Harmer
2.867
339243AC2-075 GEN1
Solar/Wind Harmer
0.403
270269AC2-059
Solar/Wind Harmer
7.919
270340AC2-060 GEN
Solar/Wind Harmer
2.488
944031AF1-071 GEN
Solar/Wind Harmer
0.811
3429211JKCT 2G
Adder
8.808
970689AG2-444 GEN
Solar/Wind Harmer
12.105
270240V3-007_GEN2
Solar/Wind Harmer
4.203
270432AC2-029 GEN
Solar/Wind Harmer
4.625
971673AH1-337 GEN
Solar/Wind Harmer
3.039
339211AE2-254 GEN
Solar/Wind Harmer
0.989
971029AG2-637 GEN
Solar/Wind Harmer
9.777
970455AG2-298 GEN
Solar/Wind Harmer
3.893
253349AC2-067 GEN
Solar/Wind Harmer
3.188
253400AC2-068 GEN
Solar/Wind Harmer
1.282
25306009OHH W.
Adder
1.837
253372AE2-315 SEC3
Adder
1.189
253372AE2-315 SEC3
Adder
1.189
270543AE2-219 C
Solar/Wind Harmer
3.202
970115AG2-085 GEN
Solar/Wind Harmer
2.405
24725505WLD G2 C
Solar/Wind Harmer
2.339
24699105WLD G1 C
Solar/Wind Harmer
2.311
961761AG1-017 GEN
Solar/Wind Harmer
0.244
945581AF1-223 GEN
Solar/Wind Harmer
2.545
965401AG1-405 GEN
Solar/Wind Harmer
3.196
965411AG1-406 GEN
Solar/Wind Harmer
1.435
270594AE1-207 GEN
Solar/Wind Harmer
8.234
965461AG1-414 GEN
Solar/Wind Harmer
1.234
970289AG2-191 GEN
Solar/Wind Harmer
1.034
965101AG1-375 GEN
Solar/Wind Harmer
5.378
958711AF2-162 GEN
Solar/Wind Harmer
0.532
270024AE2-089 GEN
Solar/Wind Harmer
2.414
241972AD1-140 GEN
Solar/Wind Harmer
2.212
24729505KEY G4
Adder
3.167
963841AG1-237 GEN
Solar/Wind Harmer
5.111
24386205FR-12G C
Solar/Wind Harmer
1.958
24386405FR-21G C
Solar/Wind Harmer
1.964
24386605FR-22G C
Solar/Wind Harmer
1.964
24387005FR-3G C
Solar/Wind Harmer
1.807
270156DARBY CT1
Adder
3.979
270157DARBY CT2
Adder
3.97
270158DARBY CT3
Adder
3.906
270330AC1-082 GEN2
Solar/Wind Helper
0.041
270329AC1-082 GEN1
Solar/Wind Helper
0.199
944221AF1-090 GEN
Solar/Wind Harmer
0.044
24803006KYGER 3HP
50/50
4.157
24802806KYGER 2HP
50/50
4.133
24802906KYGER 2LP
50/50
2.43
252509AD1-136 GEN
Solar/Wind Harmer
0.304
252519AF1-045_GEN
Solar/Wind Harmer
6.939
252516AE2-318_GEN
Solar/Wind Harmer
5.293
25194408D.CRK1
Adder
8.527
25194508D.CRK3
Adder
1.594
25183208HLCRTG
Solar/Wind Harmer
6.758
253317AC1-085 GEN4
Solar/Wind Harmer
7.888
970235AG2-159 GEN
Solar/Wind Harmer
3.588
970235AG2-159 GEN
Solar/Wind Harmer
2.19
270186AC1-089 GEN
Solar/Wind Harmer
5.394
339221AD2-048_GEN
Solar/Wind Harmer
1.338
962581AG1-107 GEN
Solar/Wind Harmer
4.27
961491AF2-440 GEN
Solar/Wind Harmer
1.775
972043AH1-570 GEN
Solar/Wind Harmer
2.119
972045AH1-571 GEN
Solar/Wind Harmer
1.695
253394AE2-221_GEN
Solar/Wind Harmer
3.836
253398AE2-221_GEN2
Solar/Wind Harmer
3.836
971125AH1-004 GEN
Solar/Wind Harmer
3.294
970107AG2-081 GEN
Solar/Wind Harmer
2.471
24728805RICHG1
Adder
2.798
24728905RICHG2
Adder
2.798
942891AE2-308 GEN
Solar/Wind Harmer
7.396
960161AF2-307 GEN
Solar/Wind Harmer
4.489
24379505HDWTR1G C
Solar/Wind Harmer
5.372
270209AC1-174_GEN
Solar/Wind Harmer
3.791
926881AC1-175 GEN
Solar/Wind Harmer
3.791
270383AD1-128 GEN
Solar/Wind Harmer
4.025
964571AG1-320 GEN
Solar/Wind Harmer
5.163
253370AE2-315 SEC1
Adder
1.257
970883AG2-550 GEN
Solar/Wind Harmer
6.253
970885AG2-551 GEN
Solar/Wind Harmer
1.454
25322209TAIT E
Adder
5.931
25322209TAIT E
Adder
5.798
970653AG2-424 GEN
Solar/Wind Harmer
2.924
970653AG2-424 GEN
Solar/Wind Harmer
1.057
970825AG2-519 GEN
Solar/Wind Harmer
6.385
24803406KYGER 5HP
50/50
4.111
24803206KYGER 4HP
50/50
4.107
252507AC2-088 GEN
Solar/Wind Harmer
2.131
25194608D.CRK4
Adder
1.854
25196808ZIMRHP
Adder
83.848
25196008MFTGT1
Adder
1.43
253432AC1-085 GEN2
Solar/Wind Harmer
0.252
946171AF1-282 GEN
Solar/Wind Harmer
9.417
945681AF1-233 GEN
Solar/Wind Harmer
17.533
339216AC1-074 GEN
Solar/Wind Harmer
1.49
270263AC1-001 GEN
Solar/Wind Harmer
0.891
943111AE2-339 GEN
Solar/Wind Harmer
0.713
3429421JKCT 10G
Adder
6.458
3429241JKCT 3G
Adder
8.923
942081AE2-220 GEN
Solar/Wind Harmer
4.343
270239V3-007_GEN1
Solar/Wind Harmer
1.169
971565AH1-281 GEN
Solar/Wind Harmer
1.339
971821AH1-427 GEN
Solar/Wind Harmer
6.42
24728605AND G2
Adder
2.429
253370AE2-315 SEC1
Adder
1.257
253371AE2-315 SEC2
Adder
1.189
270005AE1-210 C O1
Solar/Wind Harmer
3.366
965031AG1-367 GEN
Solar/Wind Harmer
6.159
960071AF2-298 GEN
Solar/Wind Harmer
3.07
25326309TAIT D
Adder
0.666
970825AG2-519 GEN
Solar/Wind Harmer
1.425
247536S-71 GEN
Solar/Wind Harmer
2.43
276903AD2-071 C
Solar/Wind Harmer
5.746
253343AC1-166 GEN
Solar/Wind Harmer
0.615
253325AC1-069 GEN
Solar/Wind Harmer
0.593
339241AF1-083 GEN
Solar/Wind Harmer
0.936
945371AF1-202 GEN
Solar/Wind Harmer
3.916
270032AE2-172
Solar/Wind Harmer
2.606
970091AG2-072 GEN
Adder
42.548
970291AG2-192 GEN
Solar/Wind Harmer
0.707
958861AF2-177 GEN
Solar/Wind Harmer
5.878
270445AC2-157 GEN2
Solar/Wind Harmer
2.967
970333AG2-219 GEN
Solar/Wind Harmer
16.702
965651AG1-433 GEN
Solar/Wind Harmer
2.872
964901AG1-354 GEN
Solar/Wind Harmer
7.722
970273AG2-179 GEN
Solar/Wind Harmer
1.235
962241AG1-070 GEN
Solar/Wind Harmer
2.22
963741AG1-226 GEN
Solar/Wind Harmer
21.505
24385905FR-11G C
Solar/Wind Harmer
3.796
24387305FR-4G C
Solar/Wind Harmer
2.321
270159DARBY CT4
Adder
3.916
960001AF2-291 GEN
Solar/Wind Helper
1.678
270331AC1-082 GEN3
Solar/Wind Helper
0.198
960441AF2-335 GEN
Solar/Wind Harmer
6.012
247621Y3-024
Adder
0.141
25326109MON D
Adder
0.761
964611AG1-324 GEN
Solar/Wind Harmer
0.68
964611AG1-324 GEN
Solar/Wind Harmer
0.302
270201AC2-176 GEN
Solar/Wind Harmer
2.928
270599AE1-208 GEN
Solar/Wind Harmer
4.584
270031AE2-169
Solar/Wind Harmer
4.584
971081AG2-670 GEN
Solar/Wind Harmer
4.157
339236AF1-050_GEN
Solar/Wind Harmer
0.965
270444AC2-157 GEN1
Solar/Wind Harmer
2.967
970239AG2-162 GEN
Solar/Wind Harmer
5.82
944541AF1-119 GEN
Solar/Wind Harmer
2.201
960971AF2-388 GEN
Solar/Wind Harmer
5.745
945391AF1-204 GEN
Solar/Wind Harmer
7.147
339231AF1-038_GEN
Solar/Wind Harmer
0.921
339255AE2-071 GEN
Solar/Wind Harmer
0.523
964781AG1-341 GEN
Solar/Wind Harmer
5.213
942221AE2-234 GEN
Solar/Wind Harmer
0.356
970241AG2-163 GEN
Solar/Wind Harmer
11.947
971485AH1-239 GEN
Solar/Wind Harmer
3.69
966021AG1-471 GEN
Solar/Wind Harmer
2.468
966841AG1-555 GEN
Solar/Wind Harmer
1.146
25326509SID D
Adder
0.572
237033AB1-150 GEN
Solar/Wind Helper
0.372
24803106KYGER 3LP
50/50
2.447
24803306KYGER 4LP
50/50
2.396
971191AH1-055 GEN
Solar/Wind Harmer
85.12
25196608WSDLE5
Adder
9.731
25194608D.CRK4
Adder
1.854
252510AF1-249 C
Solar/Wind Harmer
0.469
25196008MFTGT1
Adder
1.385
958171AF2-111 GEN
Solar/Wind Harmer
24.753
253316AC1-085 GEN3
Solar/Wind Harmer
7.888
253433AC1-085 GEN1
Solar/Wind Harmer
5.007
946181AF1-283 GEN
Solar/Wind Harmer
12.242
972167AH1-666 GEN
Solar/Wind Harmer
7.471
972173AH1-669 GEN
Solar/Wind Harmer
4.449
270273AD2-016 GEN
Solar/Wind Harmer
2.265
270222AC2-111 GEN
Solar/Wind Harmer
6.583
253406AD2-031_GEN
Solar/Wind Harmer
1.022
253415AE1-040 GEN
Solar/Wind Harmer
0.887
3429391JKCT 9G
Adder
6.458
270356AE2-297 GEN
Solar/Wind Harmer
3.298
970093AG2-073 GEN
Solar/Wind Harmer
7.066
966571AG1-526 GEN
Solar/Wind Harmer
15.11
270437AC2-090 C
Solar/Wind Harmer
3.793
24728705AND G3
Adder
5.08
24728505AND G1
Adder
2.429
253303V4-073 C
Solar/Wind Harmer
0.073
253370AE2-315 SEC1
Adder
1.257
253371AE2-315 SEC2
Adder
1.189
958821AF2-173 GEN
Solar/Wind Harmer
8.623
270004AE1-209 GEN
Solar/Wind Harmer
3.366
946031AF1-268 GEN
Solar/Wind Harmer
5.017
962031AG1-047 GEN
Solar/Wind Harmer
1.721
957741AF2-068 GEN
Solar/Wind Harmer
8.543
253338AC1-165 GEN
Solar/Wind Harmer
0.615
253333AC1-068 GEN
Solar/Wind Harmer
0.593
970289AG2-191 GEN
Solar/Wind Harmer
0.418
970291AG2-192 GEN
Solar/Wind Harmer
0.38
960741AF2-365 GEN
Solar/Wind Harmer
2.673
970243AG2-164 GEN
Solar/Wind Harmer
13.665
970519AG2-331 GEN
Solar/Wind Harmer
9.181
970699AG2-449 GEN
Solar/Wind Harmer
6.073
247642Z2-115 C
Solar/Wind Harmer
0.034
972273AH1-721 GEN
Adder
43.41
971617AH1-308 GEN
Solar/Wind Harmer
2.99
970193AG2-126 GEN
Solar/Wind Harmer
7.693
970273AG2-179 GEN
Solar/Wind Harmer
1.973
339250AF1-203 GEN
Solar/Wind Harmer
0.299
962251AG1-071 GEN
Solar/Wind Harmer
2.713
971155AH1-034 GEN
Solar/Wind Harmer
4.913
944531AF1-118 GEN
Solar/Wind Harmer
16.613
235780M24_1
Solar/Wind Helper
0.923
944201AF1-088_MTX
Adder
61.779
957141AF2-008_MTX
Adder
30.89
CBM West 2LTFEXP_CBM-W2->PJM
CBM
52.963
LAGNLTFEXP_LAGN->PJM
CLTF
5.99
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.148
TVALTFEXP_TVA->PJM
CLTF
2.938
NYPJM->LTFIMP_NY
CLTF
1.486
LGEELTFEXP_LGEE->PJM
CLTF
5.109
WECLTFEXP_WEC->PJM
CLTF
1.495
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.187
AG2-052LTFEXP_AG2-052->PJM
LTF
0.096
AH1-155LTFEXP_AH1-155->PJM
LTF
0.145
CBM West 1LTFEXP_CBM-W1->PJM
CBM
59.602
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.08
MECLTFEXP_MEC->PJM
CLTF
6.608
SIGELTFEXP_SIGE->PJM
CLTF
0.315

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o 34524 34598_SRT-A


Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
34524 34598_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:132.58 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:2041.73
MW Contribution:3.69
Bus #Bus NameTypeMW Contribution
24803406KYGER 5HP
50/50
4.111
24803206KYGER 4HP
50/50
4.107
252507AC2-088 GEN
Solar/Wind Harmer
2.144
25194608D.CRK4
Adder
1.836
25196808ZIMRHP
Adder
83.684
25196008MFTGT1
Adder
1.421
253432AC1-085 GEN2
Solar/Wind Harmer
0.255
946171AF1-282 GEN
Solar/Wind Harmer
9.53
945681AF1-233 GEN
Solar/Wind Harmer
17.654
339216AC1-074 GEN
Solar/Wind Harmer
1.495
270263AC1-001 GEN
Solar/Wind Harmer
0.893
943111AE2-339 GEN
Solar/Wind Harmer
0.716
3429421JKCT 10G
Adder
6.486
3429241JKCT 3G
Adder
8.959
942081AE2-220 GEN
Solar/Wind Harmer
4.322
270239V3-007_GEN1
Solar/Wind Harmer
1.163
971565AH1-281 GEN
Solar/Wind Harmer
1.338
971821AH1-427 GEN
Solar/Wind Harmer
6.429
24728605AND G2
Adder
2.419
253370AE2-315 SEC1
Adder
1.261
253371AE2-315 SEC2
Adder
1.193
960071AF2-298 GEN
Solar/Wind Harmer
3.077
270005AE1-210 C O1
Solar/Wind Harmer
3.35
965031AG1-367 GEN
Solar/Wind Harmer
6.131
25326309TAIT D
Adder
0.668
970825AG2-519 GEN
Solar/Wind Harmer
1.418
247536S-71 GEN
Solar/Wind Harmer
2.42
276903AD2-071 C
Solar/Wind Harmer
5.722
253343AC1-166 GEN
Solar/Wind Harmer
0.621
253325AC1-069 GEN
Solar/Wind Harmer
0.599
339241AF1-083 GEN
Solar/Wind Harmer
0.936
945371AF1-202 GEN
Solar/Wind Harmer
3.898
270032AE2-172
Solar/Wind Harmer
2.595
970091AG2-072 GEN
Adder
42.403
970291AG2-192 GEN
Solar/Wind Harmer
0.704
958861AF2-177 GEN
Solar/Wind Harmer
5.853
270445AC2-157 GEN2
Solar/Wind Harmer
2.957
970333AG2-219 GEN
Solar/Wind Harmer
16.645
965651AG1-433 GEN
Solar/Wind Harmer
2.86
964901AG1-354 GEN
Solar/Wind Harmer
7.717
970273AG2-179 GEN
Solar/Wind Harmer
1.236
962241AG1-070 GEN
Solar/Wind Harmer
2.218
963741AG1-226 GEN
Solar/Wind Harmer
21.432
24385905FR-11G C
Solar/Wind Harmer
3.783
24387305FR-4G C
Solar/Wind Harmer
2.313
270159DARBY CT4
Adder
3.955
960001AF2-291 GEN
Solar/Wind Helper
1.678
24802606KYGER 1HP
50/50
4.181
24802706KYGER 1LP
50/50
2.454
24803506KYGER 5LP
50/50
2.396
25016408BKJDB1
50/50
0.291
25183008BIOENL
50/50
0.032
25250008NTE_CT
50/50
1.9
25250108NTE_ST
50/50
1.447
971985AH1-537 GEN
Solar/Wind Harmer
50.462
252524AE2-267 GEN
Solar/Wind Harmer
1.772
25196408WSDLE3
Adder
9.913
25196308WSDLE2
Adder
9.827
25196208WSDLE1
Adder
9.802
25196708WSDLE6
Adder
9.777
25196508WSDLE4
Adder
9.531
25196108MFTGT2
Adder
1.567
25196108MFTGT2
Adder
1.455
972163AH1-664 GEN
Solar/Wind Harmer
9.259
972165AH1-665 GEN
Solar/Wind Harmer
7.407
270367AC2-061_GEN
Solar/Wind Harmer
2.864
339243AC2-075 GEN1
Solar/Wind Harmer
0.405
270269AC2-059
Solar/Wind Harmer
7.935
270340AC2-060 GEN
Solar/Wind Harmer
2.497
944031AF1-071 GEN
Solar/Wind Harmer
0.807
3429211JKCT 2G
Adder
8.843
970689AG2-444 GEN
Solar/Wind Harmer
12.133
270240V3-007_GEN2
Solar/Wind Harmer
4.182
270432AC2-029 GEN
Solar/Wind Harmer
4.637
971673AH1-337 GEN
Solar/Wind Harmer
3.026
339211AE2-254 GEN
Solar/Wind Harmer
0.991
971029AG2-637 GEN
Solar/Wind Harmer
9.737
970455AG2-298 GEN
Solar/Wind Harmer
3.891
253349AC2-067 GEN
Solar/Wind Harmer
3.191
253400AC2-068 GEN
Solar/Wind Harmer
1.283
25306009OHH W.
Adder
1.841
253372AE2-315 SEC3
Adder
1.193
253372AE2-315 SEC3
Adder
1.193
270543AE2-219 C
Solar/Wind Harmer
3.189
970115AG2-085 GEN
Solar/Wind Harmer
2.394
24725505WLD G2 C
Solar/Wind Harmer
2.329
24699105WLD G1 C
Solar/Wind Harmer
2.301
961761AG1-017 GEN
Solar/Wind Harmer
0.243
965401AG1-405 GEN
Solar/Wind Harmer
3.201
965411AG1-406 GEN
Solar/Wind Harmer
1.437
945581AF1-223 GEN
Solar/Wind Harmer
2.534
270594AE1-207 GEN
Solar/Wind Harmer
8.199
965461AG1-414 GEN
Solar/Wind Harmer
1.229
970289AG2-191 GEN
Solar/Wind Harmer
1.03
965101AG1-375 GEN
Solar/Wind Harmer
5.355
958711AF2-162 GEN
Solar/Wind Harmer
0.529
270024AE2-089 GEN
Solar/Wind Harmer
2.404
241972AD1-140 GEN
Solar/Wind Harmer
2.223
24729505KEY G4
Adder
3.154
963841AG1-237 GEN
Solar/Wind Harmer
5.094
24386205FR-12G C
Solar/Wind Harmer
1.951
24386405FR-21G C
Solar/Wind Harmer
1.958
24386605FR-22G C
Solar/Wind Harmer
1.958
24387005FR-3G C
Solar/Wind Harmer
1.801
270156DARBY CT1
Adder
4.019
270157DARBY CT2
Adder
4.009
270158DARBY CT3
Adder
3.945
270330AC1-082 GEN2
Solar/Wind Helper
0.041
270329AC1-082 GEN1
Solar/Wind Helper
0.199
944221AF1-090 GEN
Solar/Wind Harmer
0.044
24803006KYGER 3HP
50/50
4.157
24802806KYGER 2HP
50/50
4.133
24802906KYGER 2LP
50/50
2.43
252509AD1-136 GEN
Solar/Wind Harmer
0.306
25183208HLCRTG
Solar/Wind Harmer
6.991
252519AF1-045_GEN
Solar/Wind Harmer
6.973
252516AE2-318_GEN
Solar/Wind Harmer
5.319
25194408D.CRK1
Adder
8.448
25194508D.CRK3
Adder
1.579
253317AC1-085 GEN4
Solar/Wind Harmer
7.982
970235AG2-159 GEN
Solar/Wind Harmer
3.58
970235AG2-159 GEN
Solar/Wind Harmer
2.186
270186AC1-089 GEN
Solar/Wind Harmer
5.399
339221AD2-048_GEN
Solar/Wind Harmer
1.342
253394AE2-221_GEN
Solar/Wind Harmer
3.877
253398AE2-221_GEN2
Solar/Wind Harmer
3.877
972043AH1-570 GEN
Solar/Wind Harmer
2.126
972045AH1-571 GEN
Solar/Wind Harmer
1.701
962581AG1-107 GEN
Solar/Wind Harmer
4.271
961491AF2-440 GEN
Solar/Wind Harmer
1.775
971125AH1-004 GEN
Solar/Wind Harmer
3.306
970107AG2-081 GEN
Solar/Wind Harmer
2.48
942891AE2-308 GEN
Solar/Wind Harmer
7.422
24728805RICHG1
Adder
2.785
24728905RICHG2
Adder
2.785
960161AF2-307 GEN
Solar/Wind Harmer
4.511
24379505HDWTR1G C
Solar/Wind Harmer
5.345
270209AC1-174_GEN
Solar/Wind Harmer
3.772
926881AC1-175 GEN
Solar/Wind Harmer
3.772
270383AD1-128 GEN
Solar/Wind Harmer
4.006
253370AE2-315 SEC1
Adder
1.261
964571AG1-320 GEN
Solar/Wind Harmer
5.157
970883AG2-550 GEN
Solar/Wind Harmer
6.228
970885AG2-551 GEN
Solar/Wind Harmer
1.448
25322209TAIT E
Adder
5.949
25322209TAIT E
Adder
5.815
970653AG2-424 GEN
Solar/Wind Harmer
2.922
970653AG2-424 GEN
Solar/Wind Harmer
1.056
970825AG2-519 GEN
Solar/Wind Harmer
6.356
960441AF2-335 GEN
Solar/Wind Harmer
5.986
247621Y3-024
Adder
0.14
25326109MON D
Adder
0.764
964611AG1-324 GEN
Solar/Wind Harmer
0.677
964611AG1-324 GEN
Solar/Wind Harmer
0.301
270201AC2-176 GEN
Solar/Wind Harmer
2.916
270599AE1-208 GEN
Solar/Wind Harmer
4.564
270031AE2-169
Solar/Wind Harmer
4.564
971081AG2-670 GEN
Solar/Wind Harmer
4.155
339236AF1-050_GEN
Solar/Wind Harmer
0.964
270444AC2-157 GEN1
Solar/Wind Harmer
2.957
970239AG2-162 GEN
Solar/Wind Harmer
5.801
944541AF1-119 GEN
Solar/Wind Harmer
2.192
960971AF2-388 GEN
Solar/Wind Harmer
5.72
945391AF1-204 GEN
Solar/Wind Harmer
7.122
339231AF1-038_GEN
Solar/Wind Harmer
0.921
339255AE2-071 GEN
Solar/Wind Harmer
0.523
964781AG1-341 GEN
Solar/Wind Harmer
5.208
942221AE2-234 GEN
Solar/Wind Harmer
0.355
970241AG2-163 GEN
Solar/Wind Harmer
11.906
971485AH1-239 GEN
Solar/Wind Harmer
3.69
966021AG1-471 GEN
Solar/Wind Harmer
2.468
966841AG1-555 GEN
Solar/Wind Harmer
1.142
25326509SID D
Adder
0.573
24803106KYGER 3LP
50/50
2.447
24803306KYGER 4LP
50/50
2.396
971191AH1-055 GEN
Solar/Wind Harmer
85.136
25196608WSDLE5
Adder
9.63
25194608D.CRK4
Adder
1.836
252510AF1-249 C
Solar/Wind Harmer
0.465
25196008MFTGT1
Adder
1.376
958171AF2-111 GEN
Solar/Wind Harmer
24.947
253316AC1-085 GEN3
Solar/Wind Harmer
7.982
253433AC1-085 GEN1
Solar/Wind Harmer
5.067
946181AF1-283 GEN
Solar/Wind Harmer
12.388
972167AH1-666 GEN
Solar/Wind Harmer
7.523
972173AH1-669 GEN
Solar/Wind Harmer
4.457
270273AD2-016 GEN
Solar/Wind Harmer
2.269
253406AD2-031_GEN
Solar/Wind Harmer
1.029
270222AC2-111 GEN
Solar/Wind Harmer
6.549
237033AB1-150 GEN
Solar/Wind Helper
0.372
270331AC1-082 GEN3
Solar/Wind Helper
0.198
253415AE1-040 GEN
Solar/Wind Harmer
0.891
3429391JKCT 9G
Adder
6.486
270356AE2-297 GEN
Solar/Wind Harmer
3.281
970093AG2-073 GEN
Solar/Wind Harmer
7.088
966571AG1-526 GEN
Solar/Wind Harmer
15.14
270437AC2-090 C
Solar/Wind Harmer
3.774
24728705AND G3
Adder
5.059
24728505AND G1
Adder
2.419
253303V4-073 C
Solar/Wind Harmer
0.073
253370AE2-315 SEC1
Adder
1.261
253371AE2-315 SEC2
Adder
1.193
958821AF2-173 GEN
Solar/Wind Harmer
8.583
270004AE1-209 GEN
Solar/Wind Harmer
3.35
946031AF1-268 GEN
Solar/Wind Harmer
4.995
253338AC1-165 GEN
Solar/Wind Harmer
0.621
253333AC1-068 GEN
Solar/Wind Harmer
0.599
962031AG1-047 GEN
Solar/Wind Harmer
1.715
957741AF2-068 GEN
Solar/Wind Harmer
8.509
970289AG2-191 GEN
Solar/Wind Harmer
0.416
970291AG2-192 GEN
Solar/Wind Harmer
0.378
960741AF2-365 GEN
Solar/Wind Harmer
2.671
970243AG2-164 GEN
Solar/Wind Harmer
13.619
970519AG2-331 GEN
Solar/Wind Harmer
9.15
970699AG2-449 GEN
Solar/Wind Harmer
6.053
247642Z2-115 C
Solar/Wind Harmer
0.034
972273AH1-721 GEN
Adder
43.453
971617AH1-308 GEN
Solar/Wind Harmer
2.978
970193AG2-126 GEN
Solar/Wind Harmer
7.666
970273AG2-179 GEN
Solar/Wind Harmer
1.973
339250AF1-203 GEN
Solar/Wind Harmer
0.299
962251AG1-071 GEN
Solar/Wind Harmer
2.711
971155AH1-034 GEN
Solar/Wind Harmer
4.909
944531AF1-118 GEN
Solar/Wind Harmer
16.546
235780M24_1
Solar/Wind Helper
0.922
944201AF1-088_MTX
Adder
61.569
957141AF2-008_MTX
Adder
30.784
CBM West 2LTFEXP_CBM-W2->PJM
CBM
52.814
LAGNLTFEXP_LAGN->PJM
CLTF
5.976
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.15
TVALTFEXP_TVA->PJM
CLTF
2.933
NYPJM->LTFIMP_NY
CLTF
1.483
LGEELTFEXP_LGEE->PJM
CLTF
5.097
WECLTFEXP_WEC->PJM
CLTF
1.49
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.186
AG2-052LTFEXP_AG2-052->PJM
LTF
0.096
AH1-155LTFEXP_AH1-155->PJM
LTF
0.144
CBM West 1LTFEXP_CBM-W1->PJM
CBM
59.458
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.052
MECLTFEXP_MEC->PJM
CLTF
6.588
SIGELTFEXP_SIGE->PJM
CLTF
0.314

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:131.72 %
Rating:1189.0 MVA
Rating Type:A
MVA to Mitigate:1566.09
MW Contribution:2.45
Bus #Bus NameTypeMW Contribution
24803006KYGER 3HP
50/50
4.149
24802806KYGER 2HP
50/50
4.125
24802906KYGER 2LP
50/50
2.425
252509AD1-136 GEN
Solar/Wind Harmer
0.04
25183208HLCRTG
Solar/Wind Harmer
0.012
252519AF1-045_GEN
Solar/Wind Harmer
6.35
252516AE2-318_GEN
Solar/Wind Harmer
5.632
25194408D.CRK1
Adder
7.616
25194508D.CRK3
Adder
1.424
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
253394AE2-221_GEN
Solar/Wind Harmer
0.008
253398AE2-221_GEN2
Solar/Wind Harmer
0.008
270186AC1-089 GEN
Solar/Wind Harmer
0.004
962581AG1-107 GEN
Solar/Wind Harmer
0.001
970235AG2-159 GEN
Solar/Wind Harmer
3.613
970235AG2-159 GEN
Solar/Wind Harmer
2.073
339221AD2-048_GEN
Solar/Wind Harmer
0.004
972043AH1-570 GEN
Solar/Wind Harmer
1.484
972045AH1-571 GEN
Solar/Wind Harmer
1.189
253370AE2-315 SEC1
Adder
1.592
971125AH1-004 GEN
Solar/Wind Harmer
2.215
970107AG2-081 GEN
Solar/Wind Harmer
1.662
25322209TAIT E
Adder
7.486
25322209TAIT E
Adder
7.317
25326109MON D
Adder
0.984
24728805RICHG1
Adder
2.73
24728905RICHG2
Adder
2.73
942891AE2-308 GEN
Solar/Wind Harmer
4.97
960161AF2-307 GEN
Solar/Wind Harmer
3.112
24379505HDWTR1G C
Solar/Wind Harmer
0.001
270209AC1-174_GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0.003
970883AG2-550 GEN
Solar/Wind Harmer
4.325
970885AG2-551 GEN
Solar/Wind Harmer
1.442
964571AG1-320 GEN
Solar/Wind Harmer
3.821
970825AG2-519 GEN
Solar/Wind Harmer
4.514
960441AF2-335 GEN
Solar/Wind Harmer
4.047
247621Y3-024
Adder
0.139
970653AG2-424 GEN
Solar/Wind Harmer
1.943
970653AG2-424 GEN
Solar/Wind Harmer
1.007
964611AG1-324 GEN
Solar/Wind Harmer
0.297
270201AC2-176 GEN
Solar/Wind Harmer
0.001
270518AE2-148 GEN
Solar/Wind Harmer
0.337
270599AE1-208 GEN
Solar/Wind Harmer
3.479
270031AE2-169
Solar/Wind Harmer
2.087
971613AH1-306 GEN
Solar/Wind Harmer
1.811
971081AG2-670 GEN
Solar/Wind Harmer
2.763
25326509SID D
Adder
0.693
270444AC2-157 GEN1
Solar/Wind Harmer
0.002
971587AH1-292 GEN
Solar/Wind Harmer
2.6
944541AF1-119 GEN
Solar/Wind Harmer
0.237
960971AF2-388 GEN
Solar/Wind Harmer
2.079
970239AG2-162 GEN
Solar/Wind Harmer
0.884
945391AF1-204 GEN
Solar/Wind Harmer
3.646
253378AE2-206_GEN
Solar/Wind Harmer
0.002
276820AF1-078_GEN
Solar/Wind Harmer
0.001
970329AG2-216 GEN
Solar/Wind Harmer
1.467
942221AE2-234 GEN
Solar/Wind Harmer
0.017
339255AE2-071 GEN
Solar/Wind Harmer
-0.054
970077AG2-063 GEN
Solar/Wind Harmer
1.879
964781AG1-341 GEN
Solar/Wind Harmer
3.457
970241AG2-163 GEN
Solar/Wind Harmer
1.873
966841AG1-555 GEN
Solar/Wind Harmer
0.348
971485AH1-239 GEN
Solar/Wind Harmer
2.448
966021AG1-471 GEN
Solar/Wind Harmer
1.637
942861AE2-305 GEN
Solar/Wind Harmer
2.346
237033AB1-150 GEN
Solar/Wind Helper
0.372
24803106KYGER 3LP
50/50
2.442
24803306KYGER 4LP
50/50
2.392
971191AH1-055 GEN
Solar/Wind Harmer
69.07
25194608D.CRK4
Adder
1.656
25196608WSDLE5
Adder
8.625
252510AF1-249 C
Solar/Wind Harmer
0.054
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
9.086
958171AF2-111 GEN
Solar/Wind Harmer
16.854
25196008MFTGT1
Adder
1.285
972167AH1-666 GEN
Solar/Wind Harmer
5.077
972173AH1-669 GEN
Solar/Wind Harmer
3.165
253406AD2-031_GEN
Solar/Wind Harmer
0.462
270273AD2-016 GEN
Solar/Wind Harmer
0.628
253415AE1-040 GEN
Solar/Wind Harmer
0.002
253370AE2-315 SEC1
Adder
1.592
253371AE2-315 SEC2
Adder
1.506
270222AC2-111 GEN
Solar/Wind Harmer
2.79
970191AG2-125 GEN
Solar/Wind Harmer
1.36
3429391JKCT 9G
Adder
6.235
270356AE2-297 GEN
Solar/Wind Harmer
0.006
970093AG2-073 GEN
Solar/Wind Harmer
4.742
966571AG1-526 GEN
Solar/Wind Harmer
10.106
270437AC2-090 C
Solar/Wind Harmer
0.002
253338AC1-165 GEN
Solar/Wind Harmer
0.002
253333AC1-068 GEN
Solar/Wind Harmer
0.007
24728705AND G3
Adder
4.853
24728505AND G1
Adder
2.32
958821AF2-173 GEN
Solar/Wind Harmer
5.771
270004AE1-209 GEN
Solar/Wind Harmer
0.893
946031AF1-268 GEN
Solar/Wind Harmer
3.889
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
5.885
970289AG2-191 GEN
Solar/Wind Harmer
0.403
970291AG2-192 GEN
Solar/Wind Harmer
0.367
247642Z2-115 C
Solar/Wind Harmer
0.002
971617AH1-308 GEN
Solar/Wind Harmer
2.961
960741AF2-365 GEN
Solar/Wind Harmer
1.775
970243AG2-164 GEN
Solar/Wind Harmer
2.07
970519AG2-331 GEN
Solar/Wind Harmer
9.199
970699AG2-449 GEN
Solar/Wind Harmer
0.884
972273AH1-721 GEN
Adder
41.409
970193AG2-126 GEN
Solar/Wind Harmer
5.147
970273AG2-179 GEN
Solar/Wind Harmer
2.017
339250AF1-203 GEN
Solar/Wind Harmer
0
962251AG1-071 GEN
Solar/Wind Harmer
2.045
970605AG2-385 GEN
Solar/Wind Harmer
1.988
971155AH1-034 GEN
Solar/Wind Harmer
3.802
944531AF1-118 GEN
Solar/Wind Harmer
14.426
235780M24_1
Solar/Wind Helper
0.923
24802606KYGER 1HP
50/50
4.173
24802706KYGER 1LP
50/50
2.449
24803506KYGER 5LP
50/50
2.392
25016408BKJDB1
50/50
0.272
25183008BIOENL
50/50
0.03
971985AH1-537 GEN
Solar/Wind Harmer
5.759
252524AE2-267 GEN
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
8.879
25196308WSDLE2
Adder
8.801
25196208WSDLE1
Adder
8.779
25196708WSDLE6
Adder
8.757
25196508WSDLE4
Adder
8.537
25196108MFTGT2
Adder
1.463
25196108MFTGT2
Adder
1.358
972163AH1-664 GEN
Solar/Wind Harmer
6.955
972165AH1-665 GEN
Solar/Wind Harmer
5.57
270367AC2-061_GEN
Solar/Wind Harmer
0.005
270269AC2-059
Solar/Wind Harmer
0.003
270340AC2-060 GEN
Solar/Wind Harmer
0.007
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
253372AE2-315 SEC3
Adder
1.506
253372AE2-315 SEC3
Adder
1.506
25306009OHH W.
Adder
2.247
970689AG2-444 GEN
Solar/Wind Harmer
10.893
253349AC2-067 GEN
Solar/Wind Harmer
1.665
253400AC2-068 GEN
Solar/Wind Harmer
0.67
3429211JKCT 2G
Adder
8.494
270432AC2-029 GEN
Solar/Wind Harmer
2.121
971673AH1-337 GEN
Solar/Wind Harmer
2.979
241972AD1-140 GEN
Solar/Wind Harmer
0.495
270240V3-007_GEN2
Solar/Wind Harmer
0.001
971029AG2-637 GEN
Solar/Wind Harmer
6.776
339211AE2-254 GEN
Solar/Wind Harmer
0.002
270543AE2-219 C
Solar/Wind Harmer
0.003
970455AG2-298 GEN
Solar/Wind Harmer
2.878
970115AG2-085 GEN
Solar/Wind Harmer
1.619
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
971609AH1-304 GEN
Solar/Wind Harmer
0.62
270594AE1-207 GEN
Solar/Wind Harmer
4.227
945581AF1-223 GEN
Solar/Wind Harmer
0
965401AG1-405 GEN
Solar/Wind Harmer
2.132
965411AG1-406 GEN
Solar/Wind Harmer
1.371
970289AG2-191 GEN
Solar/Wind Harmer
0.697
965101AG1-375 GEN
Solar/Wind Harmer
3.623
270024AE2-089 GEN
Solar/Wind Harmer
0.004
270156DARBY CT1
Adder
4.415
270157DARBY CT2
Adder
4.404
270158DARBY CT3
Adder
4.334
24729505KEY G4
Adder
3.073
945631AF1-228 GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
1.363
24386205FR-12G C
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
24387005FR-3G C
Solar/Wind Harmer
0.001
944221AF1-090 GEN
Solar/Wind Harmer
1.779
943861AF1-054 GEN
Solar/Wind Harmer
1.158
943851AF1-053 GEN
Solar/Wind Harmer
0.802
270330AC1-082 GEN2
Solar/Wind Helper
0.041
270329AC1-082 GEN1
Solar/Wind Helper
0.199
24803406KYGER 5HP
50/50
4.102
24803206KYGER 4HP
50/50
4.099
252507AC2-088 GEN
Solar/Wind Harmer
0.356
25196808ZIMRHP
Adder
78.156
25194608D.CRK4
Adder
1.656
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.99
25196008MFTGT1
Adder
1.327
945681AF1-233 GEN
Solar/Wind Harmer
11.914
270263AC1-001 GEN
Solar/Wind Harmer
0.606
339216AC1-074 GEN
Solar/Wind Harmer
0.163
253370AE2-315 SEC1
Adder
1.592
253371AE2-315 SEC2
Adder
1.506
25326309TAIT D
Adder
0.84
960071AF2-298 GEN
Solar/Wind Harmer
2.635
3429421JKCT 10G
Adder
6.235
3429241JKCT 3G
Adder
8.606
970773AG2-487 GEN
Solar/Wind Harmer
0.849
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
3.314
971565AH1-281 GEN
Solar/Wind Harmer
0.891
253343AC1-166 GEN
Solar/Wind Harmer
0.002
253325AC1-069 GEN
Solar/Wind Harmer
0.007
971821AH1-427 GEN
Solar/Wind Harmer
4.286
24728605AND G2
Adder
2.32
247536S-71 GEN
Solar/Wind Harmer
0.167
270005AE1-210 C O1
Solar/Wind Harmer
0.893
965031AG1-367 GEN
Solar/Wind Harmer
4.122
970825AG2-519 GEN
Solar/Wind Harmer
1.446
276903AD2-071 C
Solar/Wind Harmer
4.31
270032AE2-172
Solar/Wind Harmer
2.516
945371AF1-202 GEN
Solar/Wind Harmer
0
970091AG2-072 GEN
Adder
40.612
970291AG2-192 GEN
Solar/Wind Harmer
0.477
958861AF2-177 GEN
Solar/Wind Harmer
1.57
270445AC2-157 GEN2
Solar/Wind Harmer
0.002
965651AG1-433 GEN
Solar/Wind Harmer
1.04
970333AG2-219 GEN
Solar/Wind Harmer
2.53
270159DARBY CT4
Adder
4.344
964901AG1-354 GEN
Solar/Wind Harmer
5.126
970273AG2-179 GEN
Solar/Wind Harmer
1.177
962241AG1-070 GEN
Solar/Wind Harmer
1.783
970593AG2-378 GEN
Solar/Wind Harmer
0.735
963741AG1-226 GEN
Solar/Wind Harmer
7.599
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.001
960001AF2-291 GEN
Solar/Wind Helper
1.682
270331AC1-082 GEN3
Solar/Wind Helper
0.198
944201AF1-088_MTX
Adder
59.081
957141AF2-008_MTX
Adder
29.541
CBM West 2LTFEXP_CBM-W2->PJM
CBM
50.459
LAGNLTFEXP_LAGN->PJM
CLTF
5.678
TVALTFEXP_TVA->PJM
CLTF
2.775
NYPJM->LTFIMP_NY
CLTF
1.447
LGEELTFEXP_LGEE->PJM
CLTF
4.851
WECLTFEXP_WEC->PJM
CLTF
1.45
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.226
AG2-052LTFEXP_AG2-052->PJM
LTF
0.094
AH1-155LTFEXP_AH1-155->PJM
LTF
0.141
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.02
CBM West 1LTFEXP_CBM-W1->PJM
CBM
58.512
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.324
MECLTFEXP_MEC->PJM
CLTF
6.369
SIGELTFEXP_SIGE->PJM
CLTF
0.3

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P2-2_#308_05CULLOD 765_1_SRT-A


Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#308_05CULLOD 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:129.85 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:1999.63
MW Contribution:3.78
Bus #Bus NameTypeMW Contribution
24803406KYGER 5HP
50/50
4.109
24803206KYGER 4HP
50/50
4.106
252507AC2-088 GEN
Solar/Wind Harmer
2.063
25196808ZIMRHP
Adder
80.243
25194608D.CRK4
Adder
1.699
253432AC1-085 GEN2
Solar/Wind Harmer
0.275
946171AF1-282 GEN
Solar/Wind Harmer
10.264
25196008MFTGT1
Adder
1.365
945681AF1-233 GEN
Solar/Wind Harmer
17.684
339216AC1-074 GEN
Solar/Wind Harmer
1.487
270263AC1-001 GEN
Solar/Wind Harmer
0.926
253370AE2-315 SEC1
Adder
1.632
253371AE2-315 SEC2
Adder
1.544
943111AE2-339 GEN
Solar/Wind Harmer
0.717
25326309TAIT D
Adder
0.861
3429421JKCT 10G
Adder
6.507
960071AF2-298 GEN
Solar/Wind Harmer
3.876
3429241JKCT 3G
Adder
9
971565AH1-281 GEN
Solar/Wind Harmer
1.343
942081AE2-220 GEN
Solar/Wind Harmer
4.283
270239V3-007_GEN1
Solar/Wind Harmer
1.153
971821AH1-427 GEN
Solar/Wind Harmer
6.483
253343AC1-166 GEN
Solar/Wind Harmer
0.685
253325AC1-069 GEN
Solar/Wind Harmer
0.661
24728605AND G2
Adder
2.418
247536S-71 GEN
Solar/Wind Harmer
2.485
270005AE1-210 C O1
Solar/Wind Harmer
3.344
965031AG1-367 GEN
Solar/Wind Harmer
6.119
970825AG2-519 GEN
Solar/Wind Harmer
1.424
276903AD2-071 C
Solar/Wind Harmer
5.761
970091AG2-072 GEN
Adder
43.741
339241AF1-083 GEN
Solar/Wind Harmer
0.947
270032AE2-172
Solar/Wind Harmer
2.619
945371AF1-202 GEN
Solar/Wind Harmer
3.908
970291AG2-192 GEN
Solar/Wind Harmer
0.712
970333AG2-219 GEN
Solar/Wind Harmer
17.254
270445AC2-157 GEN2
Solar/Wind Harmer
3.02
958861AF2-177 GEN
Solar/Wind Harmer
5.879
965651AG1-433 GEN
Solar/Wind Harmer
2.876
964901AG1-354 GEN
Solar/Wind Harmer
7.844
970273AG2-179 GEN
Solar/Wind Harmer
1.26
270159DARBY CT4
Adder
4.417
962241AG1-070 GEN
Solar/Wind Harmer
2.258
963741AG1-226 GEN
Solar/Wind Harmer
21.878
970593AG2-378 GEN
Solar/Wind Harmer
0.952
960001AF2-291 GEN
Solar/Wind Helper
1.685
270331AC1-082 GEN3
Solar/Wind Helper
0.198
24802606KYGER 1HP
50/50
4.179
24802706KYGER 1LP
50/50
2.453
24803506KYGER 5LP
50/50
2.395
25016408BKJDB1
50/50
0.278
25183008BIOENL
50/50
0.031
971985AH1-537 GEN
Solar/Wind Harmer
49.916
252524AE2-267 GEN
Solar/Wind Harmer
1.628
25196408WSDLE3
Adder
9.108
25196308WSDLE2
Adder
9.029
25196208WSDLE1
Adder
9.006
25196708WSDLE6
Adder
8.984
25196508WSDLE4
Adder
8.757
25196108MFTGT2
Adder
1.505
25196108MFTGT2
Adder
1.398
972163AH1-664 GEN
Solar/Wind Harmer
9.279
972165AH1-665 GEN
Solar/Wind Harmer
7.423
270367AC2-061_GEN
Solar/Wind Harmer
2.923
270340AC2-060 GEN
Solar/Wind Harmer
2.694
339243AC2-075 GEN1
Solar/Wind Harmer
0.403
270269AC2-059
Solar/Wind Harmer
8.257
253372AE2-315 SEC3
Adder
1.544
253372AE2-315 SEC3
Adder
1.544
944031AF1-071 GEN
Solar/Wind Harmer
0.817
25306009OHH W.
Adder
2.305
970689AG2-444 GEN
Solar/Wind Harmer
12.68
253349AC2-067 GEN
Solar/Wind Harmer
3.875
253400AC2-068 GEN
Solar/Wind Harmer
1.558
3429211JKCT 2G
Adder
8.883
270432AC2-029 GEN
Solar/Wind Harmer
4.894
971673AH1-337 GEN
Solar/Wind Harmer
3.118
270240V3-007_GEN2
Solar/Wind Harmer
4.145
971029AG2-637 GEN
Solar/Wind Harmer
10.023
241972AD1-140 GEN
Solar/Wind Harmer
2.969
339211AE2-254 GEN
Solar/Wind Harmer
0.998
970455AG2-298 GEN
Solar/Wind Harmer
3.91
270543AE2-219 C
Solar/Wind Harmer
3.278
970115AG2-085 GEN
Solar/Wind Harmer
2.405
24725505WLD G2 C
Solar/Wind Harmer
2.341
24699105WLD G1 C
Solar/Wind Harmer
2.313
961761AG1-017 GEN
Solar/Wind Harmer
0.249
965401AG1-405 GEN
Solar/Wind Harmer
3.255
965411AG1-406 GEN
Solar/Wind Harmer
1.461
270594AE1-207 GEN
Solar/Wind Harmer
8.276
945581AF1-223 GEN
Solar/Wind Harmer
2.54
965461AG1-414 GEN
Solar/Wind Harmer
1.243
970289AG2-191 GEN
Solar/Wind Harmer
1.041
965101AG1-375 GEN
Solar/Wind Harmer
5.378
270024AE2-089 GEN
Solar/Wind Harmer
2.472
958711AF2-162 GEN
Solar/Wind Harmer
0.532
270156DARBY CT1
Adder
4.488
270157DARBY CT2
Adder
4.477
270158DARBY CT3
Adder
4.406
24729505KEY G4
Adder
3.183
945631AF1-228 GEN
Solar/Wind Harmer
2.242
963841AG1-237 GEN
Solar/Wind Harmer
5.208
270330AC1-082 GEN2
Solar/Wind Helper
0.041
270329AC1-082 GEN1
Solar/Wind Helper
0.199
24803006KYGER 3HP
50/50
4.155
24802806KYGER 2HP
50/50
4.131
24802906KYGER 2LP
50/50
2.429
252509AD1-136 GEN
Solar/Wind Harmer
0.295
25183208HLCRTG
Solar/Wind Harmer
6.613
252519AF1-045_GEN
Solar/Wind Harmer
6.511
252516AE2-318_GEN
Solar/Wind Harmer
4.966
25194408D.CRK1
Adder
7.814
25194508D.CRK3
Adder
1.461
253317AC1-085 GEN4
Solar/Wind Harmer
8.597
253394AE2-221_GEN
Solar/Wind Harmer
4.388
253398AE2-221_GEN2
Solar/Wind Harmer
4.388
270186AC1-089 GEN
Solar/Wind Harmer
5.544
962581AG1-107 GEN
Solar/Wind Harmer
4.504
961491AF2-440 GEN
Solar/Wind Harmer
1.872
970235AG2-159 GEN
Solar/Wind Harmer
3.522
970235AG2-159 GEN
Solar/Wind Harmer
2.15
339221AD2-048_GEN
Solar/Wind Harmer
1.339
972043AH1-570 GEN
Solar/Wind Harmer
2.126
972045AH1-571 GEN
Solar/Wind Harmer
1.701
971125AH1-004 GEN
Solar/Wind Harmer
3.304
970107AG2-081 GEN
Solar/Wind Harmer
2.478
253370AE2-315 SEC1
Adder
1.632
25322209TAIT E
Adder
7.67
25322209TAIT E
Adder
7.497
25326109MON D
Adder
1.008
942891AE2-308 GEN
Solar/Wind Harmer
7.459
24728805RICHG1
Adder
2.819
24728905RICHG2
Adder
2.819
960161AF2-307 GEN
Solar/Wind Harmer
4.583
24379505HDWTR1G C
Solar/Wind Harmer
5.297
270209AC1-174_GEN
Solar/Wind Harmer
3.738
926881AC1-175 GEN
Solar/Wind Harmer
3.738
270383AD1-128 GEN
Solar/Wind Harmer
4.033
970883AG2-550 GEN
Solar/Wind Harmer
6.402
970885AG2-551 GEN
Solar/Wind Harmer
1.489
964571AG1-320 GEN
Solar/Wind Harmer
5.185
970653AG2-424 GEN
Solar/Wind Harmer
2.945
970653AG2-424 GEN
Solar/Wind Harmer
1.064
970825AG2-519 GEN
Solar/Wind Harmer
6.384
960441AF2-335 GEN
Solar/Wind Harmer
6.013
247621Y3-024
Adder
0.144
964611AG1-324 GEN
Solar/Wind Harmer
0.692
964611AG1-324 GEN
Solar/Wind Harmer
0.307
270201AC2-176 GEN
Solar/Wind Harmer
2.99
270518AE2-148 GEN
Solar/Wind Harmer
6.89
270599AE1-208 GEN
Solar/Wind Harmer
4.598
270031AE2-169
Solar/Wind Harmer
4.598
971081AG2-670 GEN
Solar/Wind Harmer
4.21
970239AG2-162 GEN
Solar/Wind Harmer
6.013
270444AC2-157 GEN1
Solar/Wind Harmer
3.02
339236AF1-050_GEN
Solar/Wind Harmer
0.979
25326509SID D
Adder
0.708
944541AF1-119 GEN
Solar/Wind Harmer
2.204
960971AF2-388 GEN
Solar/Wind Harmer
5.752
945391AF1-204 GEN
Solar/Wind Harmer
7.237
339231AF1-038_GEN
Solar/Wind Harmer
0.94
339255AE2-071 GEN
Solar/Wind Harmer
0.533
964781AG1-341 GEN
Solar/Wind Harmer
5.305
253378AE2-206_GEN
Solar/Wind Harmer
1.785
276820AF1-078_GEN
Solar/Wind Harmer
0.793
942221AE2-234 GEN
Solar/Wind Harmer
0.363
970241AG2-163 GEN
Solar/Wind Harmer
12.155
970077AG2-063 GEN
Solar/Wind Harmer
2.572
971485AH1-239 GEN
Solar/Wind Harmer
3.781
237033AB1-150 GEN
Solar/Wind Helper
0.388
966021AG1-471 GEN
Solar/Wind Harmer
1.628
24803106KYGER 3LP
50/50
2.446
24803306KYGER 4LP
50/50
2.395
971191AH1-055 GEN
Solar/Wind Harmer
85.348
25194608D.CRK4
Adder
1.699
252510AF1-249 C
Solar/Wind Harmer
0.432
25196608WSDLE5
Adder
8.848
253316AC1-085 GEN3
Solar/Wind Harmer
8.597
253433AC1-085 GEN1
Solar/Wind Harmer
5.457
946181AF1-283 GEN
Solar/Wind Harmer
13.343
958171AF2-111 GEN
Solar/Wind Harmer
24.891
25196008MFTGT1
Adder
1.322
972167AH1-666 GEN
Solar/Wind Harmer
7.534
972173AH1-669 GEN
Solar/Wind Harmer
4.627
253406AD2-031_GEN
Solar/Wind Harmer
1.167
270273AD2-016 GEN
Solar/Wind Harmer
2.361
253415AE1-040 GEN
Solar/Wind Harmer
0.974
253303V4-073 C
Solar/Wind Harmer
0.094
253370AE2-315 SEC1
Adder
1.632
253371AE2-315 SEC2
Adder
1.544
270222AC2-111 GEN
Solar/Wind Harmer
6.625
3429391JKCT 9G
Adder
6.507
970093AG2-073 GEN
Solar/Wind Harmer
7.137
270356AE2-297 GEN
Solar/Wind Harmer
3.253
966571AG1-526 GEN
Solar/Wind Harmer
15.237
270437AC2-090 C
Solar/Wind Harmer
3.74
253338AC1-165 GEN
Solar/Wind Harmer
0.685
253333AC1-068 GEN
Solar/Wind Harmer
0.661
24728705AND G3
Adder
5.058
24728505AND G1
Adder
2.418
958821AF2-173 GEN
Solar/Wind Harmer
8.567
270004AE1-209 GEN
Solar/Wind Harmer
3.344
946031AF1-268 GEN
Solar/Wind Harmer
5.034
962031AG1-047 GEN
Solar/Wind Harmer
1.758
957741AF2-068 GEN
Solar/Wind Harmer
8.723
970289AG2-191 GEN
Solar/Wind Harmer
0.421
970291AG2-192 GEN
Solar/Wind Harmer
0.382
970243AG2-164 GEN
Solar/Wind Harmer
14.117
970519AG2-331 GEN
Solar/Wind Harmer
9.484
970699AG2-449 GEN
Solar/Wind Harmer
6.274
960741AF2-365 GEN
Solar/Wind Harmer
2.708
247642Z2-115 C
Solar/Wind Harmer
0.034
972273AH1-721 GEN
Adder
44.331
971617AH1-308 GEN
Solar/Wind Harmer
3.063
970193AG2-126 GEN
Solar/Wind Harmer
7.79
970273AG2-179 GEN
Solar/Wind Harmer
2.013
339250AF1-203 GEN
Solar/Wind Harmer
0.304
962251AG1-071 GEN
Solar/Wind Harmer
2.76
971155AH1-034 GEN
Solar/Wind Harmer
5.002
944531AF1-118 GEN
Solar/Wind Harmer
16.727
970605AG2-385 GEN
Solar/Wind Harmer
2.572
235780M24_1
Solar/Wind Helper
0.963
944201AF1-088_MTX
Adder
62.879
957141AF2-008_MTX
Adder
31.44
CBM West 2LTFEXP_CBM-W2->PJM
CBM
54.292
LAGNLTFEXP_LAGN->PJM
CLTF
6.26
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.502
TVALTFEXP_TVA->PJM
CLTF
3.092
NYPJM->LTFIMP_NY
CLTF
1.51
LGEELTFEXP_LGEE->PJM
CLTF
5.08
WECLTFEXP_WEC->PJM
CLTF
1.532
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.12
AG2-052LTFEXP_AG2-052->PJM
LTF
0.099
AH1-155LTFEXP_AH1-155->PJM
LTF
0.148
CBM West 1LTFEXP_CBM-W1->PJM
CBM
61.189
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.524
MECLTFEXP_MEC->PJM
CLTF
6.778
SIGELTFEXP_SIGE->PJM
CLTF
0.316

Details for [AH1-239] 2ALBANY-2SNOW T 69.0 kV Ckt 1 line l/o EKPC_P1-2_AG1-471 TP-AH1-239 TP-69_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
2ALBANY-2SNOW T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_AG1-471 TP-AH1-239 TP-69_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.19 %
Rating:54.0 MVA
Rating Type:B
MVA to Mitigate:60.05
MW Contribution:80.0
IPD Plant:AH1-239
Bus #Bus NameTypeMW Contribution
971485AH1-239 GEN
PJM_IPD
80

Details for [AH1-239] 2ALBANY-2SNOW T 69.0 kV Ckt 1 line l/o EKPC_P1-2_AG1-471 TP-2ZULA J NO-69_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
2ALBANY-2SNOW T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_AG1-471 TP-2ZULA J NO-69_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.19 %
Rating:54.0 MVA
Rating Type:B
MVA to Mitigate:60.05
MW Contribution:80.0
IPD Plant:AH1-239
Bus #Bus NameTypeMW Contribution
971485AH1-239 GEN
PJM_IPD
80

Details for 2ALBANY-2SNOW T 69.0 kV Ckt 1 line l/o EKPC_P1-2_AG1-471 TP-2ZULA J NO-69_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
2ALBANY-2SNOW T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_AG1-471 TP-2ZULA J NO-69_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:109.69 %
Rating:54.0 MVA
Rating Type:B
MVA to Mitigate:59.23
MW Contribution:48.0
Bus #Bus NameTypeMW Contribution
971485AH1-239 GEN
Solar/Wind Harmer
48
966021AG1-471 GEN
Solar/Wind Harmer
32.4

Details for 2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:195.67 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:123.27
MW Contribution:5.35
Bus #Bus NameTypeMW Contribution
966021AG1-471 GEN
Solar/Wind Harmer
4.016
971485AH1-239 GEN
Solar/Wind Harmer
5.346
972273AH1-721 GEN
50/50
108.319
G-007ALTFEXP_G-007A->PJM
CMTX
0.017
CPLELTFEXP_CPLE->PJM
CLTF
0.08
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.021
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.134
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.066
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.203
LAGNLTFEXP_LAGN->PJM
CLTF
0.305
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.294
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.215
WECLTFEXP_WEC->PJM
CLTF
0.002
VTFLTFEXP_VFT->PJM
CMTX
0.045
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.072
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.565
MECLTFEXP_MEC->PJM
CLTF
0.06

Details for 2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:188.87 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:118.99
MW Contribution:4.89
Bus #Bus NameTypeMW Contribution
966021AG1-471 GEN
Solar/Wind Harmer
3.717
971485AH1-239 GEN
Solar/Wind Harmer
4.892
3429451LAUREL 1G
50/50
0.391
972273AH1-721 GEN
50/50
115.385
G-007ALTFEXP_G-007A->PJM
CMTX
0.022
CPLELTFEXP_CPLE->PJM
CLTF
0.061
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.034
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.374
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.073
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.235
LAGNLTFEXP_LAGN->PJM
CLTF
0.157
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.217
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.108
VTFLTFEXP_VFT->PJM
CMTX
0.06
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.236
MECLTFEXP_MEC->PJM
CLTF
0

Details for 2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:188.85 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:118.98
MW Contribution:4.89
Bus #Bus NameTypeMW Contribution
966021AG1-471 GEN
Solar/Wind Harmer
3.717
971485AH1-239 GEN
Solar/Wind Harmer
4.892
3429451LAUREL 1G
50/50
0.391
972273AH1-721 GEN
50/50
115.385
G-007ALTFEXP_G-007A->PJM
CMTX
0.022
CPLELTFEXP_CPLE->PJM
CLTF
0.061
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.034
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.374
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.073
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.235
LAGNLTFEXP_LAGN->PJM
CLTF
0.157
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.217
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.108
VTFLTFEXP_VFT->PJM
CMTX
0.06
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.236
MECLTFEXP_MEC->PJM
CLTF
0

Details for 2COOPER DIST-2COOPER 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER DIST-2COOPER 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:195.49 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:123.16
MW Contribution:5.35
Bus #Bus NameTypeMW Contribution
966021AG1-471 GEN
Solar/Wind Harmer
4.016
971485AH1-239 GEN
Solar/Wind Harmer
5.346
972273AH1-721 GEN
50/50
108.319
G-007ALTFEXP_G-007A->PJM
CMTX
0.017
CPLELTFEXP_CPLE->PJM
CLTF
0.08
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.021
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.134
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.066
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.203
LAGNLTFEXP_LAGN->PJM
CLTF
0.305
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.294
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.215
WECLTFEXP_WEC->PJM
CLTF
0.002
VTFLTFEXP_VFT->PJM
CMTX
0.045
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.072
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.565
MECLTFEXP_MEC->PJM
CLTF
0.06

Details for 2COOPER DIST-2COOPER 69.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER DIST-2COOPER 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:188.68 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:118.87
MW Contribution:4.89
Bus #Bus NameTypeMW Contribution
966021AG1-471 GEN
Solar/Wind Harmer
3.717
971485AH1-239 GEN
Solar/Wind Harmer
4.892
3429451LAUREL 1G
50/50
0.391
972273AH1-721 GEN
50/50
115.385
G-007ALTFEXP_G-007A->PJM
CMTX
0.022
CPLELTFEXP_CPLE->PJM
CLTF
0.061
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.034
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.374
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.073
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.235
LAGNLTFEXP_LAGN->PJM
CLTF
0.157
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.217
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.108
VTFLTFEXP_VFT->PJM
CMTX
0.06
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.236
MECLTFEXP_MEC->PJM
CLTF
0

Details for 2COOPER DIST-2COOPER 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER DIST-2COOPER 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:188.66 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:118.86
MW Contribution:4.89
Bus #Bus NameTypeMW Contribution
966021AG1-471 GEN
Solar/Wind Harmer
3.717
971485AH1-239 GEN
Solar/Wind Harmer
4.892
3429451LAUREL 1G
50/50
0.391
972273AH1-721 GEN
50/50
115.385
G-007ALTFEXP_G-007A->PJM
CMTX
0.022
CPLELTFEXP_CPLE->PJM
CLTF
0.061
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.034
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.374
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.073
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.235
LAGNLTFEXP_LAGN->PJM
CLTF
0.157
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.217
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.108
VTFLTFEXP_VFT->PJM
CMTX
0.06
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.236
MECLTFEXP_MEC->PJM
CLTF
0

Details for 2COOPER-2SOMERSET 69.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-2


Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER-2SOMERSET 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:217.32 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:165.16
MW Contribution:3.98
Bus #Bus NameTypeMW Contribution
966021AG1-471 GEN
Solar/Wind Harmer
2.892
971485AH1-239 GEN
Solar/Wind Harmer
3.98
972273AH1-721 GEN
50/50
101.944
3429031COOPER2 G
50/50
1.651
CPLELTFEXP_CPLE->PJM
CLTF
0.053
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.167
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.002
LAGNLTFEXP_LAGN->PJM
CLTF
0.444
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.227
TVALTFEXP_TVA->PJM
CLTF
0.317
NYPJM->LTFIMP_NY
CLTF
0.014
WECLTFEXP_WEC->PJM
CLTF
0.018
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.59
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.951
MECLTFEXP_MEC->PJM
CLTF
0.156
SIGELTFEXP_SIGE->PJM
CLTF
0.005

Details for 2COOPER-2SOMERSET 69.0 kV Ckt 2 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-2


Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER-2SOMERSET 69.0 kV Ckt 2 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:217.32 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:165.16
MW Contribution:3.98
Bus #Bus NameTypeMW Contribution
966021AG1-471 GEN
Solar/Wind Harmer
2.892
971485AH1-239 GEN
Solar/Wind Harmer
3.98
972273AH1-721 GEN
50/50
101.944
3429031COOPER2 G
50/50
1.651
CPLELTFEXP_CPLE->PJM
CLTF
0.053
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.167
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.002
LAGNLTFEXP_LAGN->PJM
CLTF
0.444
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.227
TVALTFEXP_TVA->PJM
CLTF
0.317
NYPJM->LTFIMP_NY
CLTF
0.014
WECLTFEXP_WEC->PJM
CLTF
0.018
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.59
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.951
MECLTFEXP_MEC->PJM
CLTF
0.156
SIGELTFEXP_SIGE->PJM
CLTF
0.005

Details for 2DENNY-2BRONSTON T 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
2DENNY-2BRONSTON T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:287.7 %
Rating:46.0 MVA
Rating Type:B
MVA to Mitigate:132.34
MW Contribution:5.35
Bus #Bus NameTypeMW Contribution
966021AG1-471 GEN
Solar/Wind Harmer
4.016
971485AH1-239 GEN
Solar/Wind Harmer
5.346
972273AH1-721 GEN
50/50
108.319
G-007ALTFEXP_G-007A->PJM
CMTX
0.017
CPLELTFEXP_CPLE->PJM
CLTF
0.08
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.021
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.134
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.066
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.203
LAGNLTFEXP_LAGN->PJM
CLTF
0.305
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.294
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.215
WECLTFEXP_WEC->PJM
CLTF
0.002
VTFLTFEXP_VFT->PJM
CMTX
0.045
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.072
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.565
MECLTFEXP_MEC->PJM
CLTF
0.06

Details for 2DENNY-2BRONSTON T 69.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
2DENNY-2BRONSTON T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:277.52 %
Rating:46.0 MVA
Rating Type:B
MVA to Mitigate:127.66
MW Contribution:4.89
Bus #Bus NameTypeMW Contribution
966021AG1-471 GEN
Solar/Wind Harmer
3.717
971485AH1-239 GEN
Solar/Wind Harmer
4.892
3429451LAUREL 1G
50/50
0.391
972273AH1-721 GEN
50/50
115.385
G-007ALTFEXP_G-007A->PJM
CMTX
0.022
CPLELTFEXP_CPLE->PJM
CLTF
0.061
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.034
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.374
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.073
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.235
LAGNLTFEXP_LAGN->PJM
CLTF
0.157
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.217
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.108
VTFLTFEXP_VFT->PJM
CMTX
0.06
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.236
MECLTFEXP_MEC->PJM
CLTF
0

Details for 2DENNY-2BRONSTON T 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
2DENNY-2BRONSTON T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:277.5 %
Rating:46.0 MVA
Rating Type:B
MVA to Mitigate:127.65
MW Contribution:4.89
Bus #Bus NameTypeMW Contribution
966021AG1-471 GEN
Solar/Wind Harmer
3.717
971485AH1-239 GEN
Solar/Wind Harmer
4.892
3429451LAUREL 1G
50/50
0.391
972273AH1-721 GEN
50/50
115.385
G-007ALTFEXP_G-007A->PJM
CMTX
0.022
CPLELTFEXP_CPLE->PJM
CLTF
0.061
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.034
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.374
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.073
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.235
LAGNLTFEXP_LAGN->PJM
CLTF
0.157
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.217
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.108
VTFLTFEXP_VFT->PJM
CMTX
0.06
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.236
MECLTFEXP_MEC->PJM
CLTF
0

Details for 2PATTON RD J-2FOX HOLLOW 69.0 kV Ckt 1 line l/o EKPC_P4-2_SSHAD S11-1004_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
2PATTON RD J-2FOX HOLLOW 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P4-2_SSHAD S11-1004_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.62 %
Rating:98.0 MVA
Rating Type:B
MVA to Mitigate:103.51
MW Contribution:9.24
Bus #Bus NameTypeMW Contribution
339255AE2-071 GEN
Solar/Wind Harmer
5.093
971485AH1-239 GEN
Solar/Wind Harmer
9.237
339231AF1-038_GEN
Solar/Wind Harmer
1.78
966021AG1-471 GEN
Solar/Wind Harmer
3.869
339236AF1-050_GEN
Solar/Wind Harmer
1.245
971081AG2-670 GEN
Solar/Wind Harmer
4.72
970653AG2-424 GEN
Solar/Wind Harmer
2.425
970653AG2-424 GEN
Solar/Wind Harmer
0.877
970273AG2-179 GEN
Solar/Wind Harmer
2.49
964901AG1-354 GEN
Solar/Wind Harmer
10.292
339241AF1-083 GEN
Solar/Wind Harmer
0.943
971155AH1-034 GEN
Solar/Wind Harmer
54.765
339250AF1-203 GEN
Solar/Wind Harmer
2.91
970273AG2-179 GEN
Solar/Wind Harmer
3.976
972273AH1-721 GEN
Adder
13.481
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.017
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.007
LGEELTFEXP_LGEE->PJM
CLTF
0.05
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.059
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.039
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.684

Details for 2PATTON RD J-2FOX HOLLOW 69.0 kV Ckt 1 line l/o EKPC_P2-3_SSHAD S11-1039_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
2PATTON RD J-2FOX HOLLOW 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_SSHAD S11-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.62 %
Rating:98.0 MVA
Rating Type:B
MVA to Mitigate:103.51
MW Contribution:9.24
Bus #Bus NameTypeMW Contribution
339255AE2-071 GEN
Solar/Wind Harmer
5.093
971485AH1-239 GEN
Solar/Wind Harmer
9.237
339231AF1-038_GEN
Solar/Wind Harmer
1.78
966021AG1-471 GEN
Solar/Wind Harmer
3.869
339236AF1-050_GEN
Solar/Wind Harmer
1.245
971081AG2-670 GEN
Solar/Wind Harmer
4.72
970653AG2-424 GEN
Solar/Wind Harmer
2.425
970653AG2-424 GEN
Solar/Wind Harmer
0.877
970273AG2-179 GEN
Solar/Wind Harmer
2.49
964901AG1-354 GEN
Solar/Wind Harmer
10.292
339241AF1-083 GEN
Solar/Wind Harmer
0.943
971155AH1-034 GEN
Solar/Wind Harmer
54.765
339250AF1-203 GEN
Solar/Wind Harmer
2.91
970273AG2-179 GEN
Solar/Wind Harmer
3.976
972273AH1-721 GEN
Adder
13.481
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.017
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.007
LGEELTFEXP_LGEE->PJM
CLTF
0.05
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.059
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.039
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.684

Details for 2PATTON RD J-2FOX HOLLOW 69.0 kV Ckt 1 line l/o EKPC_P2-2_SUMMSHADE 161 #2_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
2PATTON RD J-2FOX HOLLOW 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_SUMMSHADE 161 #2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:105.59 %
Rating:98.0 MVA
Rating Type:B
MVA to Mitigate:103.48
MW Contribution:9.24
Bus #Bus NameTypeMW Contribution
339255AE2-071 GEN
Solar/Wind Harmer
5.093
971485AH1-239 GEN
Solar/Wind Harmer
9.237
339231AF1-038_GEN
Solar/Wind Harmer
1.78
966021AG1-471 GEN
Solar/Wind Harmer
3.869
339236AF1-050_GEN
Solar/Wind Harmer
1.245
971081AG2-670 GEN
Solar/Wind Harmer
4.72
970653AG2-424 GEN
Solar/Wind Harmer
2.425
970653AG2-424 GEN
Solar/Wind Harmer
0.877
970273AG2-179 GEN
Solar/Wind Harmer
2.49
964901AG1-354 GEN
Solar/Wind Harmer
10.292
339241AF1-083 GEN
Solar/Wind Harmer
0.943
971155AH1-034 GEN
Solar/Wind Harmer
54.765
339250AF1-203 GEN
Solar/Wind Harmer
2.91
970273AG2-179 GEN
Solar/Wind Harmer
3.976
972273AH1-721 GEN
Adder
13.481
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.017
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.007
LGEELTFEXP_LGEE->PJM
CLTF
0.05
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.059
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.039
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.684

Details for 2PATTON RD J-2FOX HOLLOW 69.0 kV Ckt 1 line l/o EKPC_P2-3_SSHAD S11-1044_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
2PATTON RD J-2FOX HOLLOW 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_SSHAD S11-1044_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.71 %
Rating:98.0 MVA
Rating Type:B
MVA to Mitigate:102.61
MW Contribution:9.08
Bus #Bus NameTypeMW Contribution
970273AG2-179 GEN
Solar/Wind Harmer
2.45
964901AG1-354 GEN
Solar/Wind Harmer
10.233
339241AF1-083 GEN
Solar/Wind Harmer
0.937
339255AE2-071 GEN
Solar/Wind Harmer
5.07
971485AH1-239 GEN
Solar/Wind Harmer
9.08
339231AF1-038_GEN
Solar/Wind Harmer
1.752
966021AG1-471 GEN
Solar/Wind Harmer
3.764
339236AF1-050_GEN
Solar/Wind Harmer
1.238
971081AG2-670 GEN
Solar/Wind Harmer
4.692
970653AG2-424 GEN
Solar/Wind Harmer
2.427
970653AG2-424 GEN
Solar/Wind Harmer
0.877
971155AH1-034 GEN
Solar/Wind Harmer
54.528
339250AF1-203 GEN
Solar/Wind Harmer
2.897
970273AG2-179 GEN
Solar/Wind Harmer
3.913
972273AH1-721 GEN
Adder
12.813
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.008
LGEELTFEXP_LGEE->PJM
CLTF
0.083
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.072
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.048
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.719

Details for 2PATTON RD J-2FOX HOLLOW 69.0 kV Ckt 1 line l/o EKPC_P4-5_SSHAD S11-1004_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
2PATTON RD J-2FOX HOLLOW 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P4-5_SSHAD S11-1004_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.69 %
Rating:98.0 MVA
Rating Type:B
MVA to Mitigate:102.6
MW Contribution:9.08
Bus #Bus NameTypeMW Contribution
970273AG2-179 GEN
Solar/Wind Harmer
2.45
964901AG1-354 GEN
Solar/Wind Harmer
10.233
339241AF1-083 GEN
Solar/Wind Harmer
0.937
339255AE2-071 GEN
Solar/Wind Harmer
5.07
971485AH1-239 GEN
Solar/Wind Harmer
9.08
339231AF1-038_GEN
Solar/Wind Harmer
1.752
966021AG1-471 GEN
Solar/Wind Harmer
3.764
339236AF1-050_GEN
Solar/Wind Harmer
1.238
971081AG2-670 GEN
Solar/Wind Harmer
4.692
970653AG2-424 GEN
Solar/Wind Harmer
2.427
970653AG2-424 GEN
Solar/Wind Harmer
0.877
971155AH1-034 GEN
Solar/Wind Harmer
54.528
339250AF1-203 GEN
Solar/Wind Harmer
2.897
970273AG2-179 GEN
Solar/Wind Harmer
3.913
972273AH1-721 GEN
Adder
12.813
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.008
LGEELTFEXP_LGEE->PJM
CLTF
0.083
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.072
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.048
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.719

Details for 2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-2


Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:362.3 %
Rating:105.0 MVA
Rating Type:B
MVA to Mitigate:380.42
MW Contribution:9.42
Bus #Bus NameTypeMW Contribution
965401AG1-405 GEN
Solar/Wind Harmer
15.906
965411AG1-406 GEN
Solar/Wind Harmer
7.138
339231AF1-038_GEN
Solar/Wind Harmer
3.633
966021AG1-471 GEN
Solar/Wind Harmer
6.628
971485AH1-239 GEN
Solar/Wind Harmer
9.419
339255AE2-071 GEN
Solar/Wind Harmer
0.817
971081AG2-670 GEN
Solar/Wind Harmer
5.523
339236AF1-050_GEN
Solar/Wind Harmer
1.284
964781AG1-341 GEN
Solar/Wind Harmer
7.2
970273AG2-179 GEN
Solar/Wind Harmer
4.779
339241AF1-083 GEN
Solar/Wind Harmer
1.258
964901AG1-354 GEN
Solar/Wind Harmer
10.435
962241AG1-070 GEN
Solar/Wind Harmer
2.752
971821AH1-427 GEN
Solar/Wind Harmer
5.135
3429031COOPER2 G
50/50
3.298
972273AH1-721 GEN
50/50
203.518
970273AG2-179 GEN
Solar/Wind Harmer
7.633
339250AF1-203 GEN
Solar/Wind Harmer
0.467
971155AH1-034 GEN
Solar/Wind Harmer
7.301
962251AG1-071 GEN
Solar/Wind Harmer
3.364
960741AF2-365 GEN
Solar/Wind Harmer
2.51
950011AG9-010
External Queue
7.339287757873535
CPLELTFEXP_CPLE->PJM
CLTF
0.083
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.307
LAGNLTFEXP_LAGN->PJM
CLTF
1.212
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.419
TVALTFEXP_TVA->PJM
CLTF
0.87
NYPJM->LTFIMP_NY
CLTF
0.043
WECLTFEXP_WEC->PJM
CLTF
0.064
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.151
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.674
MECLTFEXP_MEC->PJM
CLTF
0.492
SIGELTFEXP_SIGE->PJM
CLTF
0.018

Details for 2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line l/o EKPC_P2-2_ELIHU-COOP 161_SRT-A


Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_ELIHU-COOP 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:273.46 %
Rating:105.0 MVA
Rating Type:B
MVA to Mitigate:287.13
MW Contribution:7.73
Bus #Bus NameTypeMW Contribution
339231AF1-038_GEN
Solar/Wind Harmer
3.215
3429451LAUREL 1G
50/50
0.481
970273AG2-179 GEN
Solar/Wind Harmer
4.217
339241AF1-083 GEN
Solar/Wind Harmer
1.018
964901AG1-354 GEN
Solar/Wind Harmer
8.475
962241AG1-070 GEN
Solar/Wind Harmer
2.246
971821AH1-427 GEN
Solar/Wind Harmer
4.861
3429031COOPER2 G
50/50
2.491
972273AH1-721 GEN
50/50
153.02
970273AG2-179 GEN
Solar/Wind Harmer
6.736
339250AF1-203 GEN
Solar/Wind Harmer
0.386
971155AH1-034 GEN
Solar/Wind Harmer
6.018
962251AG1-071 GEN
Solar/Wind Harmer
2.745
965401AG1-405 GEN
Solar/Wind Harmer
14.697
965411AG1-406 GEN
Solar/Wind Harmer
6.596
966021AG1-471 GEN
Solar/Wind Harmer
5.438
971485AH1-239 GEN
Solar/Wind Harmer
7.732
339255AE2-071 GEN
Solar/Wind Harmer
0.675
971081AG2-670 GEN
Solar/Wind Harmer
4.473
339236AF1-050_GEN
Solar/Wind Harmer
1.042
964781AG1-341 GEN
Solar/Wind Harmer
5.857
950011AG9-010
External Queue
5.9790544509887695
CPLELTFEXP_CPLE->PJM
CLTF
0.047
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.735
LAGNLTFEXP_LAGN->PJM
CLTF
0.92
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.27
TVALTFEXP_TVA->PJM
CLTF
0.669
NYPJM->LTFIMP_NY
CLTF
0.038
WECLTFEXP_WEC->PJM
CLTF
0.046
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.548
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.026
MECLTFEXP_MEC->PJM
CLTF
0.366
SIGELTFEXP_SIGE->PJM
CLTF
0.013

Details for 2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-1


Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:273.14 %
Rating:105.0 MVA
Rating Type:B
MVA to Mitigate:286.8
MW Contribution:7.73
Bus #Bus NameTypeMW Contribution
339231AF1-038_GEN
Solar/Wind Harmer
3.216
966021AG1-471 GEN
Solar/Wind Harmer
5.437
971485AH1-239 GEN
Solar/Wind Harmer
7.731
339255AE2-071 GEN
Solar/Wind Harmer
0.676
971081AG2-670 GEN
Solar/Wind Harmer
4.477
339236AF1-050_GEN
Solar/Wind Harmer
1.042
964781AG1-341 GEN
Solar/Wind Harmer
5.862
965401AG1-405 GEN
Solar/Wind Harmer
14.702
965411AG1-406 GEN
Solar/Wind Harmer
6.598
3429451LAUREL 1G
50/50
0.48
970273AG2-179 GEN
Solar/Wind Harmer
4.22
339241AF1-083 GEN
Solar/Wind Harmer
1.019
964901AG1-354 GEN
Solar/Wind Harmer
8.482
962241AG1-070 GEN
Solar/Wind Harmer
2.248
971821AH1-427 GEN
Solar/Wind Harmer
4.863
3429031COOPER2 G
50/50
2.494
972273AH1-721 GEN
50/50
152.479
970273AG2-179 GEN
Solar/Wind Harmer
6.739
339250AF1-203 GEN
Solar/Wind Harmer
0.386
971155AH1-034 GEN
Solar/Wind Harmer
6.022
962251AG1-071 GEN
Solar/Wind Harmer
2.747
950011AG9-010
External Queue
5.984987735748291
CPLELTFEXP_CPLE->PJM
CLTF
0.047
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.739
LAGNLTFEXP_LAGN->PJM
CLTF
0.921
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.27
TVALTFEXP_TVA->PJM
CLTF
0.67
NYPJM->LTFIMP_NY
CLTF
0.038
WECLTFEXP_WEC->PJM
CLTF
0.047
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.55
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.028
MECLTFEXP_MEC->PJM
CLTF
0.366
SIGELTFEXP_SIGE->PJM
CLTF
0.013

Details for 2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line l/o EKPC_P1-2_COOP-ELIHU161_SRT-A


Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_COOP-ELIHU161_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:250.96 %
Rating:105.0 MVA
Rating Type:B
MVA to Mitigate:263.5
MW Contribution:5.39
Bus #Bus NameTypeMW Contribution
966021AG1-471 GEN
Solar/Wind Harmer
3.794
971485AH1-239 GEN
Solar/Wind Harmer
5.394
339255AE2-071 GEN
Solar/Wind Harmer
-0.073
971081AG2-670 GEN
Solar/Wind Harmer
3.12
964781AG1-341 GEN
Solar/Wind Harmer
4.086
3429031COOPER2 G
50/50
2.491
972273AH1-721 GEN
50/50
153.02
970273AG2-179 GEN
Solar/Wind Harmer
7.23
339250AF1-203 GEN
Solar/Wind Harmer
0.001
971155AH1-034 GEN
Solar/Wind Harmer
4.898
962251AG1-071 GEN
Solar/Wind Harmer
2.177
3429451LAUREL 1G
50/50
0.481
970273AG2-179 GEN
Solar/Wind Harmer
4.217
964901AG1-354 GEN
Solar/Wind Harmer
5.913
962241AG1-070 GEN
Solar/Wind Harmer
1.898
971821AH1-427 GEN
Solar/Wind Harmer
3.391
965401AG1-405 GEN
Solar/Wind Harmer
10.254
965411AG1-406 GEN
Solar/Wind Harmer
6.596
950011AG9-010
External Queue
5.9790544509887695
CPLELTFEXP_CPLE->PJM
CLTF
0.047
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.735
LAGNLTFEXP_LAGN->PJM
CLTF
0.92
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.27
TVALTFEXP_TVA->PJM
CLTF
0.669
NYPJM->LTFIMP_NY
CLTF
0.038
WECLTFEXP_WEC->PJM
CLTF
0.046
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.548
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.026
MECLTFEXP_MEC->PJM
CLTF
0.366
SIGELTFEXP_SIGE->PJM
CLTF
0.013

Details for 2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:136.6 %
Rating:105.0 MVA
Rating Type:B
MVA to Mitigate:143.43
MW Contribution:7.61
Bus #Bus NameTypeMW Contribution
339231AF1-038_GEN
Solar/Wind Harmer
3.521
966021AG1-471 GEN
Solar/Wind Harmer
5.289
970273AG2-179 GEN
Solar/Wind Harmer
4.626
339241AF1-083 GEN
Solar/Wind Harmer
1.216
964901AG1-354 GEN
Solar/Wind Harmer
9.862
962241AG1-070 GEN
Solar/Wind Harmer
2.574
971821AH1-427 GEN
Solar/Wind Harmer
5.331
971485AH1-239 GEN
Solar/Wind Harmer
7.609
339255AE2-071 GEN
Solar/Wind Harmer
0.76
971081AG2-670 GEN
Solar/Wind Harmer
5.313
339236AF1-050_GEN
Solar/Wind Harmer
1.222
964781AG1-341 GEN
Solar/Wind Harmer
6.732
965401AG1-405 GEN
Solar/Wind Harmer
15.687
965411AG1-406 GEN
Solar/Wind Harmer
7.04
970273AG2-179 GEN
Solar/Wind Harmer
7.388
339250AF1-203 GEN
Solar/Wind Harmer
0.434
971155AH1-034 GEN
Solar/Wind Harmer
6.798
962251AG1-071 GEN
Solar/Wind Harmer
3.146
972273AH1-721 GEN
Adder
44.758
960741AF2-365 GEN
Solar/Wind Harmer
2.369
950011AG9-010
External Queue
7.141107559204102
CPLELTFEXP_CPLE->PJM
CLTF
0.081
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.908
LAGNLTFEXP_LAGN->PJM
CLTF
1.107
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.381
TVALTFEXP_TVA->PJM
CLTF
0.789
NYPJM->LTFIMP_NY
CLTF
0.026
LGEELTFEXP_LGEE->PJM
CLTF
0.02
WECLTFEXP_WEC->PJM
CLTF
0.068
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.315
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.448
MECLTFEXP_MEC->PJM
CLTF
0.482
SIGELTFEXP_SIGE->PJM
CLTF
0.018

Details for 2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:136.57 %
Rating:105.0 MVA
Rating Type:B
MVA to Mitigate:143.4
MW Contribution:7.61
Bus #Bus NameTypeMW Contribution
965401AG1-405 GEN
Solar/Wind Harmer
15.687
965411AG1-406 GEN
Solar/Wind Harmer
7.04
970273AG2-179 GEN
Solar/Wind Harmer
4.626
339241AF1-083 GEN
Solar/Wind Harmer
1.216
964901AG1-354 GEN
Solar/Wind Harmer
9.862
962241AG1-070 GEN
Solar/Wind Harmer
2.574
971821AH1-427 GEN
Solar/Wind Harmer
5.331
339231AF1-038_GEN
Solar/Wind Harmer
3.521
966021AG1-471 GEN
Solar/Wind Harmer
5.289
971485AH1-239 GEN
Solar/Wind Harmer
7.609
339255AE2-071 GEN
Solar/Wind Harmer
0.76
971081AG2-670 GEN
Solar/Wind Harmer
5.313
339236AF1-050_GEN
Solar/Wind Harmer
1.222
964781AG1-341 GEN
Solar/Wind Harmer
6.732
970273AG2-179 GEN
Solar/Wind Harmer
7.388
339250AF1-203 GEN
Solar/Wind Harmer
0.434
971155AH1-034 GEN
Solar/Wind Harmer
6.798
962251AG1-071 GEN
Solar/Wind Harmer
3.146
972273AH1-721 GEN
Adder
44.758
960741AF2-365 GEN
Solar/Wind Harmer
2.369
950011AG9-010
External Queue
7.141107559204102
CPLELTFEXP_CPLE->PJM
CLTF
0.081
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.908
LAGNLTFEXP_LAGN->PJM
CLTF
1.107
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.381
TVALTFEXP_TVA->PJM
CLTF
0.789
NYPJM->LTFIMP_NY
CLTF
0.026
LGEELTFEXP_LGEE->PJM
CLTF
0.02
WECLTFEXP_WEC->PJM
CLTF
0.068
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.315
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.448
MECLTFEXP_MEC->PJM
CLTF
0.482
SIGELTFEXP_SIGE->PJM
CLTF
0.018

Details for 2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.62 %
Rating:105.0 MVA
Rating Type:B
MVA to Mitigate:119.3
MW Contribution:6.66
Bus #Bus NameTypeMW Contribution
965401AG1-405 GEN
Solar/Wind Harmer
17.192
965411AG1-406 GEN
Solar/Wind Harmer
7.716
339231AF1-038_GEN
Solar/Wind Harmer
3.409
966021AG1-471 GEN
Solar/Wind Harmer
4.67
971485AH1-239 GEN
Solar/Wind Harmer
6.662
339255AE2-071 GEN
Solar/Wind Harmer
0.603
971081AG2-670 GEN
Solar/Wind Harmer
4.234
339236AF1-050_GEN
Solar/Wind Harmer
0.947
964781AG1-341 GEN
Solar/Wind Harmer
4.94
970273AG2-179 GEN
Solar/Wind Harmer
4.437
339241AF1-083 GEN
Solar/Wind Harmer
0.979
971821AH1-427 GEN
Solar/Wind Harmer
5.035
964901AG1-354 GEN
Solar/Wind Harmer
7.476
962241AG1-070 GEN
Solar/Wind Harmer
1.944
970273AG2-179 GEN
Solar/Wind Harmer
7.087
972273AH1-721 GEN
Adder
60.03
339250AF1-203 GEN
Solar/Wind Harmer
0.345
971155AH1-034 GEN
Solar/Wind Harmer
5.337
962251AG1-071 GEN
Solar/Wind Harmer
2.376
950011AG9-010
External Queue
5.8951191902160645
CPLELTFEXP_CPLE->PJM
CLTF
0.042
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.247
LAGNLTFEXP_LAGN->PJM
CLTF
0.786
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.224
TVALTFEXP_TVA->PJM
CLTF
0.558
NYPJM->LTFIMP_NY
CLTF
0.022
LGEELTFEXP_LGEE->PJM
CLTF
0.018
WECLTFEXP_WEC->PJM
CLTF
0.05
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.696
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.735
MECLTFEXP_MEC->PJM
CLTF
0.35
SIGELTFEXP_SIGE->PJM
CLTF
0.013

Details for 2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-2


Base Case Flowgate

Area:EKPC
Facility Description:
2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:319.42 %
Rating:115.0 MVA
Rating Type:B
MVA to Mitigate:367.34
MW Contribution:8.21
Bus #Bus NameTypeMW Contribution
965401AG1-405 GEN
Solar/Wind Harmer
17.565
965411AG1-406 GEN
Solar/Wind Harmer
7.883
339231AF1-038_GEN
Solar/Wind Harmer
2.641
966021AG1-471 GEN
Solar/Wind Harmer
5.826
971485AH1-239 GEN
Solar/Wind Harmer
8.214
971081AG2-670 GEN
Solar/Wind Harmer
5.013
339236AF1-050_GEN
Solar/Wind Harmer
1.109
339255AE2-071 GEN
Solar/Wind Harmer
0.643
964781AG1-341 GEN
Solar/Wind Harmer
5.665
970273AG2-179 GEN
Solar/Wind Harmer
3.341
339241AF1-083 GEN
Solar/Wind Harmer
1.165
964901AG1-354 GEN
Solar/Wind Harmer
8.68
971821AH1-427 GEN
Solar/Wind Harmer
5.249
962241AG1-070 GEN
Solar/Wind Harmer
2.185
3429031COOPER2 G
50/50
3.373
972273AH1-721 GEN
50/50
208.134
970273AG2-179 GEN
Solar/Wind Harmer
5.336
339250AF1-203 GEN
Solar/Wind Harmer
0.368
971155AH1-034 GEN
Solar/Wind Harmer
5.752
962251AG1-071 GEN
Solar/Wind Harmer
2.671
950011AG9-010
External Queue
7.104497909545898
CPLELTFEXP_CPLE->PJM
CLTF
0.039
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.874
LAGNLTFEXP_LAGN->PJM
CLTF
0.919
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.247
TVALTFEXP_TVA->PJM
CLTF
0.659
NYPJM->LTFIMP_NY
CLTF
0.041
LGEELTFEXP_LGEE->PJM
CLTF
0.014
WECLTFEXP_WEC->PJM
CLTF
0.051
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.682
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.042
MECLTFEXP_MEC->PJM
CLTF
0.383
SIGELTFEXP_SIGE->PJM
CLTF
0.015

Details for 2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line l/o EKPC_P2-2_ELIHU-COOP 161_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_ELIHU-COOP 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:233.63 %
Rating:115.0 MVA
Rating Type:B
MVA to Mitigate:268.67
MW Contribution:6.53
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
0.507
970273AG2-179 GEN
Solar/Wind Harmer
2.781
339241AF1-083 GEN
Solar/Wind Harmer
0.926
971821AH1-427 GEN
Solar/Wind Harmer
4.976
964901AG1-354 GEN
Solar/Wind Harmer
6.726
3429031COOPER2 G
50/50
2.568
972273AH1-721 GEN
50/50
157.798
970273AG2-179 GEN
Solar/Wind Harmer
4.442
339250AF1-203 GEN
Solar/Wind Harmer
0.287
971155AH1-034 GEN
Solar/Wind Harmer
4.473
965401AG1-405 GEN
Solar/Wind Harmer
16.361
965411AG1-406 GEN
Solar/Wind Harmer
7.343
339231AF1-038_GEN
Solar/Wind Harmer
2.224
966021AG1-471 GEN
Solar/Wind Harmer
4.64
971485AH1-239 GEN
Solar/Wind Harmer
6.532
971081AG2-670 GEN
Solar/Wind Harmer
3.966
339236AF1-050_GEN
Solar/Wind Harmer
0.867
339255AE2-071 GEN
Solar/Wind Harmer
0.502
950011AG9-010
External Queue
5.748639106750488
CPLELTFEXP_CPLE->PJM
CLTF
0.003
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.307
LAGNLTFEXP_LAGN->PJM
CLTF
0.628
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.099
TVALTFEXP_TVA->PJM
CLTF
0.459
NYPJM->LTFIMP_NY
CLTF
0.036
WECLTFEXP_WEC->PJM
CLTF
0.033
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.081
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.396
MECLTFEXP_MEC->PJM
CLTF
0.258
SIGELTFEXP_SIGE->PJM
CLTF
0.01

Details for 2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-1


Base Case Flowgate

Area:EKPC
Facility Description:
2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:233.32 %
Rating:115.0 MVA
Rating Type:B
MVA to Mitigate:268.32
MW Contribution:6.53
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
0.505
970273AG2-179 GEN
Solar/Wind Harmer
2.783
339241AF1-083 GEN
Solar/Wind Harmer
0.927
971821AH1-427 GEN
Solar/Wind Harmer
4.978
964901AG1-354 GEN
Solar/Wind Harmer
6.733
965401AG1-405 GEN
Solar/Wind Harmer
16.366
965411AG1-406 GEN
Solar/Wind Harmer
7.345
339231AF1-038_GEN
Solar/Wind Harmer
2.226
966021AG1-471 GEN
Solar/Wind Harmer
4.639
971485AH1-239 GEN
Solar/Wind Harmer
6.532
971081AG2-670 GEN
Solar/Wind Harmer
3.97
339236AF1-050_GEN
Solar/Wind Harmer
0.868
339255AE2-071 GEN
Solar/Wind Harmer
0.502
3429031COOPER2 G
50/50
2.572
972273AH1-721 GEN
50/50
157.265
970273AG2-179 GEN
Solar/Wind Harmer
4.446
339250AF1-203 GEN
Solar/Wind Harmer
0.287
971155AH1-034 GEN
Solar/Wind Harmer
4.477
950011AG9-010
External Queue
5.754502296447754
CPLELTFEXP_CPLE->PJM
CLTF
0.003
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.311
LAGNLTFEXP_LAGN->PJM
CLTF
0.629
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.099
TVALTFEXP_TVA->PJM
CLTF
0.459
NYPJM->LTFIMP_NY
CLTF
0.036
WECLTFEXP_WEC->PJM
CLTF
0.033
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.083
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.397
MECLTFEXP_MEC->PJM
CLTF
0.258
SIGELTFEXP_SIGE->PJM
CLTF
0.01

Details for 2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line l/o EKPC_P1-2_COOP-ELIHU161_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_COOP-ELIHU161_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:217.54 %
Rating:115.0 MVA
Rating Type:B
MVA to Mitigate:250.17
MW Contribution:4.56
Bus #Bus NameTypeMW Contribution
3429031COOPER2 G
50/50
2.568
972273AH1-721 GEN
50/50
157.798
970273AG2-179 GEN
Solar/Wind Harmer
4.768
339250AF1-203 GEN
Solar/Wind Harmer
0
971155AH1-034 GEN
Solar/Wind Harmer
3.641
966021AG1-471 GEN
Solar/Wind Harmer
3.237
971485AH1-239 GEN
Solar/Wind Harmer
4.558
971081AG2-670 GEN
Solar/Wind Harmer
2.767
339255AE2-071 GEN
Solar/Wind Harmer
-0.054
3429451LAUREL 1G
50/50
0.507
970273AG2-179 GEN
Solar/Wind Harmer
2.781
971821AH1-427 GEN
Solar/Wind Harmer
3.472
964901AG1-354 GEN
Solar/Wind Harmer
4.693
965401AG1-405 GEN
Solar/Wind Harmer
11.415
965411AG1-406 GEN
Solar/Wind Harmer
7.343
950011AG9-010
External Queue
5.748639106750488
CPLELTFEXP_CPLE->PJM
CLTF
0.003
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.307
LAGNLTFEXP_LAGN->PJM
CLTF
0.628
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.099
TVALTFEXP_TVA->PJM
CLTF
0.459
NYPJM->LTFIMP_NY
CLTF
0.036
WECLTFEXP_WEC->PJM
CLTF
0.033
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.081
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.396
MECLTFEXP_MEC->PJM
CLTF
0.258
SIGELTFEXP_SIGE->PJM
CLTF
0.01

Details for 2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:119.59 %
Rating:115.0 MVA
Rating Type:B
MVA to Mitigate:137.53
MW Contribution:6.41
Bus #Bus NameTypeMW Contribution
339231AF1-038_GEN
Solar/Wind Harmer
2.527
966021AG1-471 GEN
Solar/Wind Harmer
4.494
971485AH1-239 GEN
Solar/Wind Harmer
6.412
971081AG2-670 GEN
Solar/Wind Harmer
4.797
339236AF1-050_GEN
Solar/Wind Harmer
1.046
339255AE2-071 GEN
Solar/Wind Harmer
0.586
964781AG1-341 GEN
Solar/Wind Harmer
5.192
965401AG1-405 GEN
Solar/Wind Harmer
17.34
965411AG1-406 GEN
Solar/Wind Harmer
7.782
970273AG2-179 GEN
Solar/Wind Harmer
3.185
339241AF1-083 GEN
Solar/Wind Harmer
1.121
971821AH1-427 GEN
Solar/Wind Harmer
5.441
964901AG1-354 GEN
Solar/Wind Harmer
8.098
962241AG1-070 GEN
Solar/Wind Harmer
2.005
970273AG2-179 GEN
Solar/Wind Harmer
5.087
972273AH1-721 GEN
Adder
50.456
339250AF1-203 GEN
Solar/Wind Harmer
0.335
971155AH1-034 GEN
Solar/Wind Harmer
5.244
962251AG1-071 GEN
Solar/Wind Harmer
2.45
950011AG9-010
External Queue
6.89682674407959
CPLELTFEXP_CPLE->PJM
CLTF
0.037
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.479
LAGNLTFEXP_LAGN->PJM
CLTF
0.814
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.211
TVALTFEXP_TVA->PJM
CLTF
0.578
NYPJM->LTFIMP_NY
CLTF
0.023
LGEELTFEXP_LGEE->PJM
CLTF
0.038
WECLTFEXP_WEC->PJM
CLTF
0.054
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.852
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.816
MECLTFEXP_MEC->PJM
CLTF
0.374
SIGELTFEXP_SIGE->PJM
CLTF
0.015

Details for 2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:119.55 %
Rating:115.0 MVA
Rating Type:B
MVA to Mitigate:137.49
MW Contribution:6.41
Bus #Bus NameTypeMW Contribution
970273AG2-179 GEN
Solar/Wind Harmer
5.087
339231AF1-038_GEN
Solar/Wind Harmer
2.527
966021AG1-471 GEN
Solar/Wind Harmer
4.494
971485AH1-239 GEN
Solar/Wind Harmer
6.412
971081AG2-670 GEN
Solar/Wind Harmer
4.797
339236AF1-050_GEN
Solar/Wind Harmer
1.046
339255AE2-071 GEN
Solar/Wind Harmer
0.586
964781AG1-341 GEN
Solar/Wind Harmer
5.192
970273AG2-179 GEN
Solar/Wind Harmer
3.185
339241AF1-083 GEN
Solar/Wind Harmer
1.121
971821AH1-427 GEN
Solar/Wind Harmer
5.441
964901AG1-354 GEN
Solar/Wind Harmer
8.098
962241AG1-070 GEN
Solar/Wind Harmer
2.005
965401AG1-405 GEN
Solar/Wind Harmer
17.34
965411AG1-406 GEN
Solar/Wind Harmer
7.782
972273AH1-721 GEN
Adder
50.456
339250AF1-203 GEN
Solar/Wind Harmer
0.335
971155AH1-034 GEN
Solar/Wind Harmer
5.244
962251AG1-071 GEN
Solar/Wind Harmer
2.45
950011AG9-010
External Queue
6.89682674407959
CPLELTFEXP_CPLE->PJM
CLTF
0.037
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.479
LAGNLTFEXP_LAGN->PJM
CLTF
0.814
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.211
TVALTFEXP_TVA->PJM
CLTF
0.578
NYPJM->LTFIMP_NY
CLTF
0.023
LGEELTFEXP_LGEE->PJM
CLTF
0.038
WECLTFEXP_WEC->PJM
CLTF
0.054
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.852
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.816
MECLTFEXP_MEC->PJM
CLTF
0.374
SIGELTFEXP_SIGE->PJM
CLTF
0.015

Details for 2SUMM SHADE-2EDM-JBGAL J 69.0 kV Ckt 1 line l/o EKPC_P2-3_SSHAD S11-1014_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
2SUMM SHADE-2EDM-JBGAL J 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_SSHAD S11-1014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.34 %
Rating:46.0 MVA
Rating Type:B
MVA to Mitigate:49.84
MW Contribution:2.54
Bus #Bus NameTypeMW Contribution
339255AE2-071 GEN
Solar/Wind Harmer
0.899
964781AG1-341 GEN
Solar/Wind Harmer
3.718
971485AH1-239 GEN
Solar/Wind Harmer
2.541
339236AF1-050_GEN
Solar/Wind Helper
0.831
962241AG1-070 GEN
Solar/Wind Harmer
1.751
339241AF1-083 GEN
Solar/Wind Helper
0.616
339250AF1-203 GEN
Solar/Wind Harmer
0.514
971155AH1-034 GEN
Solar/Wind Harmer
7.34
962251AG1-071 GEN
Solar/Wind Harmer
2.14
G-007ALTFEXP_G-007A->PJM
CMTX
0.044
CPLELTFEXP_CPLE->PJM
CLTF
0.132
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.068
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.354
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.112
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.365
LAGNLTFEXP_LAGN->PJM
CLTF
0.587
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.471
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.407
WECLTFEXP_WEC->PJM
CLTF
0.012
VTFLTFEXP_VFT->PJM
CMTX
0.116
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.44
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.095
MECLTFEXP_MEC->PJM
CLTF
0.153

Details for 2SUMM SHADE-2EDM-JBGAL J 69.0 kV Ckt 1 line l/o EKPC_P2-3_SSHAD S11-1004_SRT-A-1


Base Case Flowgate

Area:EKPC
Facility Description:
2SUMM SHADE-2EDM-JBGAL J 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_SSHAD S11-1004_SRT-A-1
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.05 %
Rating:46.0 MVA
Rating Type:B
MVA to Mitigate:48.32
MW Contribution:2.36
Bus #Bus NameTypeMW Contribution
339255AE2-071 GEN
Solar/Wind Harmer
0.862
964781AG1-341 GEN
Solar/Wind Harmer
3.281
971485AH1-239 GEN
Solar/Wind Harmer
2.357
339236AF1-050_GEN
Solar/Wind Helper
0.836
962241AG1-070 GEN
Solar/Wind Harmer
1.57
339241AF1-083 GEN
Solar/Wind Helper
0.62
339250AF1-203 GEN
Solar/Wind Harmer
0.493
971155AH1-034 GEN
Solar/Wind Harmer
6.984
962251AG1-071 GEN
Solar/Wind Harmer
1.919
G-007ALTFEXP_G-007A->PJM
CMTX
0.038
CPLELTFEXP_CPLE->PJM
CLTF
0.113
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.06
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.103
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.075
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.23
LAGNLTFEXP_LAGN->PJM
CLTF
0.516
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.407
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.357
WECLTFEXP_WEC->PJM
CLTF
0.012
VTFLTFEXP_VFT->PJM
CMTX
0.101
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.444
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.973
MECLTFEXP_MEC->PJM
CLTF
0.141

Details for 2SUMM SHADE-2EDM-JBGAL J 69.0 kV Ckt 1 line l/o EKPC_P4-5_SSHAD S11-1004_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
2SUMM SHADE-2EDM-JBGAL J 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P4-5_SSHAD S11-1004_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.24 %
Rating:46.0 MVA
Rating Type:B
MVA to Mitigate:46.57
MW Contribution:3.72
Bus #Bus NameTypeMW Contribution
962241AG1-070 GEN
Solar/Wind Harmer
2.334
339241AF1-083 GEN
Solar/Wind Helper
0.552
339255AE2-071 GEN
Solar/Wind Harmer
1.573
971485AH1-239 GEN
Solar/Wind Harmer
3.718
339236AF1-050_GEN
Solar/Wind Helper
0.748
339250AF1-203 GEN
Solar/Wind Harmer
0.899
971155AH1-034 GEN
Solar/Wind Harmer
12.333
962251AG1-071 GEN
Solar/Wind Harmer
2.853
G-007ALTFEXP_G-007A->PJM
CMTX
0.034
CPLELTFEXP_CPLE->PJM
CLTF
0.111
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.051
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.934
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.103
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.338
LAGNLTFEXP_LAGN->PJM
CLTF
0.489
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.4
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.34
WECLTFEXP_WEC->PJM
CLTF
0.009
VTFLTFEXP_VFT->PJM
CMTX
0.09
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.316
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.904
MECLTFEXP_MEC->PJM
CLTF
0.122

Details for [AH1-239] 2UPCHURCH T-2ALBANY 69.0 kV Ckt 1 line l/o EKPC_P1-2_AG1-471 TP-AH1-239 TP-69_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
2UPCHURCH T-2ALBANY 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_AG1-471 TP-AH1-239 TP-69_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:138.84 %
Rating:54.0 MVA
Rating Type:B
MVA to Mitigate:74.98
MW Contribution:80.0
IPD Plant:AH1-239
Bus #Bus NameTypeMW Contribution
971485AH1-239 GEN
PJM_IPD
80

Details for [AH1-239] 2UPCHURCH T-2ALBANY 69.0 kV Ckt 1 line l/o EKPC_P1-2_AG1-471 TP-2ZULA J NO-69_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
2UPCHURCH T-2ALBANY 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_AG1-471 TP-2ZULA J NO-69_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:138.84 %
Rating:54.0 MVA
Rating Type:B
MVA to Mitigate:74.98
MW Contribution:80.0
IPD Plant:AH1-239
Bus #Bus NameTypeMW Contribution
971485AH1-239 GEN
PJM_IPD
80

Details for 2UPCHURCH T-2ALBANY 69.0 kV Ckt 1 line l/o EKPC_P1-2_AG1-471 TP-2ZULA J NO-69_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
2UPCHURCH T-2ALBANY 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_AG1-471 TP-2ZULA J NO-69_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:135.33 %
Rating:54.0 MVA
Rating Type:B
MVA to Mitigate:73.08
MW Contribution:48.0
Bus #Bus NameTypeMW Contribution
971485AH1-239 GEN
Solar/Wind Harmer
48
966021AG1-471 GEN
Solar/Wind Harmer
32.4

Details for 2ZULA J NO-2WAYNE CO 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
2ZULA J NO-2WAYNE CO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:135.11 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:85.12
MW Contribution:52.75
Bus #Bus NameTypeMW Contribution
966021AG1-471 GEN
Solar/Wind Harmer
39.753
971485AH1-239 GEN
Solar/Wind Harmer
52.747
339255AE2-071 GEN
Solar/Wind Harmer
0.562
339250AF1-203 GEN
Solar/Wind Harmer
0.321
971155AH1-034 GEN
Solar/Wind Harmer
4.448
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.495
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
0.041
TVALTFEXP_TVA->PJM
CLTF
0.014
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.006
LGEELTFEXP_LGEE->PJM
CLTF
0.046
WECLTFEXP_WEC->PJM
CLTF
0.011
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.019
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.013
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.384
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.088
MECLTFEXP_MEC->PJM
CLTF
0.058
SIGELTFEXP_SIGE->PJM
CLTF
0.005

Details for 2ZULA J NO-2WAYNE CO 69.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
2ZULA J NO-2WAYNE CO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:135.11 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:85.12
MW Contribution:52.75
Bus #Bus NameTypeMW Contribution
339250AF1-203 GEN
Solar/Wind Harmer
0.321
971155AH1-034 GEN
Solar/Wind Harmer
4.448
966021AG1-471 GEN
Solar/Wind Harmer
39.753
971485AH1-239 GEN
Solar/Wind Harmer
52.747
339255AE2-071 GEN
Solar/Wind Harmer
0.562
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.495
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
0.041
TVALTFEXP_TVA->PJM
CLTF
0.014
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.006
LGEELTFEXP_LGEE->PJM
CLTF
0.046
WECLTFEXP_WEC->PJM
CLTF
0.011
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.019
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.013
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.384
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.088
MECLTFEXP_MEC->PJM
CLTF
0.058
SIGELTFEXP_SIGE->PJM
CLTF
0.005

Details for 2ZULA J NO-2WAYNE CO 69.0 kV Ckt 1 line l/o EKPC_P2-3_MAR W38-1014_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
2ZULA J NO-2WAYNE CO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_MAR W38-1014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:134.08 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:84.47
MW Contribution:52.85
Bus #Bus NameTypeMW Contribution
966021AG1-471 GEN
Solar/Wind Harmer
39.827
971485AH1-239 GEN
Solar/Wind Harmer
52.855
339255AE2-071 GEN
Solar/Wind Harmer
0.576
339250AF1-203 GEN
Solar/Wind Harmer
0.329
971155AH1-034 GEN
Solar/Wind Harmer
4.574
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.588
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
0.059
TVALTFEXP_TVA->PJM
CLTF
0.026
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.006
LGEELTFEXP_LGEE->PJM
CLTF
0.044
WECLTFEXP_WEC->PJM
CLTF
0.012
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.017
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.012
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.419
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.122
MECLTFEXP_MEC->PJM
CLTF
0.066
SIGELTFEXP_SIGE->PJM
CLTF
0.005

Details for 2ZULA J NO-2WAYNE CO 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
2ZULA J NO-2WAYNE CO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:134.07 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:84.47
MW Contribution:52.69
Bus #Bus NameTypeMW Contribution
966021AG1-471 GEN
Solar/Wind Harmer
39.712
971485AH1-239 GEN
Solar/Wind Harmer
52.69
339255AE2-071 GEN
Solar/Wind Harmer
0.559
339250AF1-203 GEN
Solar/Wind Harmer
0.32
971155AH1-034 GEN
Solar/Wind Harmer
4.425
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.459
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
0.031
TVALTFEXP_TVA->PJM
CLTF
0.006
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.006
LGEELTFEXP_LGEE->PJM
CLTF
0.05
WECLTFEXP_WEC->PJM
CLTF
0.011
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.021
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.015
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.382
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.067
MECLTFEXP_MEC->PJM
CLTF
0.056
SIGELTFEXP_SIGE->PJM
CLTF
0.005

Details for 2ZULA J NO-2WAYNE CO 69.0 kV Ckt 1 line l/o EKPC_P4-2_TAYLOR W45-1014_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
2ZULA J NO-2WAYNE CO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P4-2_TAYLOR W45-1014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:133.36 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:84.01
MW Contribution:52.88
Bus #Bus NameTypeMW Contribution
966021AG1-471 GEN
Solar/Wind Harmer
39.846
971485AH1-239 GEN
Solar/Wind Harmer
52.881
339255AE2-071 GEN
Solar/Wind Harmer
0.577
339250AF1-203 GEN
Solar/Wind Harmer
0.329
971155AH1-034 GEN
Solar/Wind Harmer
4.58
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.589
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
0.063
TVALTFEXP_TVA->PJM
CLTF
0.028
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.005
LGEELTFEXP_LGEE->PJM
CLTF
0.041
WECLTFEXP_WEC->PJM
CLTF
0.012
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.016
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.011
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.41
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.127
MECLTFEXP_MEC->PJM
CLTF
0.065
SIGELTFEXP_SIGE->PJM
CLTF
0.005

Details for 2ZULA J NO-2WAYNE CO 69.0 kV Ckt 1 line l/o EKPC_P4-2_MAR W38-1004_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
2ZULA J NO-2WAYNE CO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P4-2_MAR W38-1004_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:133.36 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:84.01
MW Contribution:52.88
Bus #Bus NameTypeMW Contribution
966021AG1-471 GEN
Solar/Wind Harmer
39.846
971485AH1-239 GEN
Solar/Wind Harmer
52.881
339255AE2-071 GEN
Solar/Wind Harmer
0.577
339250AF1-203 GEN
Solar/Wind Harmer
0.329
971155AH1-034 GEN
Solar/Wind Harmer
4.58
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.589
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
0.063
TVALTFEXP_TVA->PJM
CLTF
0.028
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.005
LGEELTFEXP_LGEE->PJM
CLTF
0.041
WECLTFEXP_WEC->PJM
CLTF
0.012
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.016
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.011
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.41
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.127
MECLTFEXP_MEC->PJM
CLTF
0.065
SIGELTFEXP_SIGE->PJM
CLTF
0.005

Details for 2ZULA J NO-2WAYNE CO 69.0 kV Ckt 1 line l/o EKPC_P2-2_GREEN CO 161_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
2ZULA J NO-2WAYNE CO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_GREEN CO 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:132.81 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:83.67
MW Contribution:52.87
Bus #Bus NameTypeMW Contribution
339250AF1-203 GEN
Solar/Wind Harmer
0.328
966021AG1-471 GEN
Solar/Wind Harmer
39.839
971485AH1-239 GEN
Solar/Wind Harmer
52.869
339255AE2-071 GEN
Solar/Wind Harmer
0.573
971155AH1-034 GEN
Solar/Wind Harmer
4.548
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.564
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
0.057
TVALTFEXP_TVA->PJM
CLTF
0.025
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.005
LGEELTFEXP_LGEE->PJM
CLTF
0.042
WECLTFEXP_WEC->PJM
CLTF
0.012
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.016
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.011
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.404
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.117
MECLTFEXP_MEC->PJM
CLTF
0.063
SIGELTFEXP_SIGE->PJM
CLTF
0.005

Details for 2ZULA J NO-2WAYNE CO 69.0 kV Ckt 1 line l/o EKPC_P2-2_CASEY CO 161_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
2ZULA J NO-2WAYNE CO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_CASEY CO 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:132.58 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:83.53
MW Contribution:52.81
Bus #Bus NameTypeMW Contribution
966021AG1-471 GEN
Solar/Wind Harmer
39.801
971485AH1-239 GEN
Solar/Wind Harmer
52.813
339255AE2-071 GEN
Solar/Wind Harmer
0.566
339250AF1-203 GEN
Solar/Wind Harmer
0.323
971155AH1-034 GEN
Solar/Wind Harmer
4.487
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.535
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
0.046
TVALTFEXP_TVA->PJM
CLTF
0.016
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.005
LGEELTFEXP_LGEE->PJM
CLTF
0.049
WECLTFEXP_WEC->PJM
CLTF
0.012
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.019
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.013
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.414
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.097
MECLTFEXP_MEC->PJM
CLTF
0.063
SIGELTFEXP_SIGE->PJM
CLTF
0.005

Details for 2ZULA J NO-2WAYNE CO 69.0 kV Ckt 1 line l/o EKPC_P2-2_MARION CO 161_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
2ZULA J NO-2WAYNE CO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_MARION CO 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:132.49 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:83.47
MW Contribution:52.86
Bus #Bus NameTypeMW Contribution
966021AG1-471 GEN
Solar/Wind Harmer
39.827
971485AH1-239 GEN
Solar/Wind Harmer
52.856
339255AE2-071 GEN
Solar/Wind Harmer
0.576
339250AF1-203 GEN
Solar/Wind Harmer
0.329
971155AH1-034 GEN
Solar/Wind Harmer
4.575
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.596
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
0.06
TVALTFEXP_TVA->PJM
CLTF
0.026
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.005
LGEELTFEXP_LGEE->PJM
CLTF
0.045
WECLTFEXP_WEC->PJM
CLTF
0.013
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.017
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.012
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.427
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.125
MECLTFEXP_MEC->PJM
CLTF
0.067
SIGELTFEXP_SIGE->PJM
CLTF
0.005

Details for 2ZULA J NO-2WAYNE CO 69.0 kV Ckt 1 line l/o EKPC_P2-2_MCCR-WINFD161_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
2ZULA J NO-2WAYNE CO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_MCCR-WINFD161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:132.37 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:83.39
MW Contribution:52.69
Bus #Bus NameTypeMW Contribution
966021AG1-471 GEN
Solar/Wind Harmer
39.712
971485AH1-239 GEN
Solar/Wind Harmer
52.689
339255AE2-071 GEN
Solar/Wind Harmer
0.558
339250AF1-203 GEN
Solar/Wind Harmer
0.319
971155AH1-034 GEN
Solar/Wind Harmer
4.418
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.6
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
0.069
TVALTFEXP_TVA->PJM
CLTF
0.031
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.005
LGEELTFEXP_LGEE->PJM
CLTF
0.038
WECLTFEXP_WEC->PJM
CLTF
0.012
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.014
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.01
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.402
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.134
MECLTFEXP_MEC->PJM
CLTF
0.065
SIGELTFEXP_SIGE->PJM
CLTF
0.004

Details for 2ZULA J NO-2WAYNE CO 69.0 kV Ckt 1 line l/o EKPC_P7-1_BULL 161 DBL_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
2ZULA J NO-2WAYNE CO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_BULL 161 DBL_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:131.97 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:83.14
MW Contribution:52.89
Bus #Bus NameTypeMW Contribution
966021AG1-471 GEN
Solar/Wind Harmer
39.856
971485AH1-239 GEN
Solar/Wind Harmer
52.892
339255AE2-071 GEN
Solar/Wind Harmer
0.574
339250AF1-203 GEN
Solar/Wind Harmer
0.328
971155AH1-034 GEN
Solar/Wind Harmer
4.56
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.57
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
0.064
TVALTFEXP_TVA->PJM
CLTF
0.03
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.005
LGEELTFEXP_LGEE->PJM
CLTF
0.033
WECLTFEXP_WEC->PJM
CLTF
0.011
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.014
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.01
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.379
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.125
MECLTFEXP_MEC->PJM
CLTF
0.062
SIGELTFEXP_SIGE->PJM
CLTF
0.004

Details for 2ZULA J NO-2WAYNE CO 69.0 kV Ckt 1 line l/o EKPC_P7-1_SSHAD 161 DBL_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
2ZULA J NO-2WAYNE CO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_SSHAD 161 DBL_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:131.82 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:83.05
MW Contribution:52.89
Bus #Bus NameTypeMW Contribution
966021AG1-471 GEN
Solar/Wind Harmer
39.853
971485AH1-239 GEN
Solar/Wind Harmer
52.888
339255AE2-071 GEN
Solar/Wind Harmer
0.573
339250AF1-203 GEN
Solar/Wind Harmer
0.327
971155AH1-034 GEN
Solar/Wind Harmer
4.549
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.56
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
0.063
TVALTFEXP_TVA->PJM
CLTF
0.029
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.005
LGEELTFEXP_LGEE->PJM
CLTF
0.033
WECLTFEXP_WEC->PJM
CLTF
0.011
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.015
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.01
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.375
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.123
MECLTFEXP_MEC->PJM
CLTF
0.061
SIGELTFEXP_SIGE->PJM
CLTF
0.004

Details for [AH1-239] 2ZULA J NO-2WAYNE CO 69.0 kV Ckt 1 line l/o EKPC_P1-2_AH1-239 TP-2UPCHURCH T-69_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
2ZULA J NO-2WAYNE CO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_AH1-239 TP-2UPCHURCH T-69_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:130.76 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:82.38
MW Contribution:80.0
IPD Plant:AH1-239
Bus #Bus NameTypeMW Contribution
971485AH1-239 GEN
PJM_IPD
80

Details for 2ZULA J NO-2WAYNE CO 69.0 kV Ckt 1 line l/o EKPC_P1-2_AH1-239 TP-2UPCHURCH T-69_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
2ZULA J NO-2WAYNE CO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_AH1-239 TP-2UPCHURCH T-69_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:127.38 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:80.25
MW Contribution:48.0
Bus #Bus NameTypeMW Contribution
971485AH1-239 GEN
Solar/Wind Harmer
48
966021AG1-471 GEN
Solar/Wind Harmer
32.4

Details for 4MARION CO-4LEBANON 138.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-2


Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
4MARION CO-4LEBANON 138.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:120.11 %
Rating:220.0 MVA
Rating Type:B
MVA to Mitigate:264.25
MW Contribution:5.85
Bus #Bus NameTypeMW Contribution
965401AG1-405 GEN
Solar/Wind Harmer
4.452
965411AG1-406 GEN
Solar/Wind Harmer
1.998
971081AG2-670 GEN
Solar/Wind Harmer
16.943
339236AF1-050_GEN
Solar/Wind Harmer
2.932
339231AF1-038_GEN
Solar/Wind Harmer
1.786
971485AH1-239 GEN
Solar/Wind Harmer
5.85
966021AG1-471 GEN
Solar/Wind Harmer
3.94
339255AE2-071 GEN
Solar/Wind Harmer
0.772
964781AG1-341 GEN
Solar/Wind Harmer
7.499
970653AG2-424 GEN
Solar/Wind Harmer
2.693
970653AG2-424 GEN
Solar/Wind Harmer
0.973
339241AF1-083 GEN
Solar/Wind Harmer
4.334
964901AG1-354 GEN
Solar/Wind Harmer
18.467
970273AG2-179 GEN
Solar/Wind Harmer
2.363
962241AG1-070 GEN
Solar/Wind Harmer
2.149
3429031COOPER2 G
50/50
1.767
972273AH1-721 GEN
50/50
108.963
970273AG2-179 GEN
Solar/Wind Harmer
3.775
339250AF1-203 GEN
Solar/Wind Harmer
0.441
971155AH1-034 GEN
Solar/Wind Harmer
6.798
962251AG1-071 GEN
Solar/Wind Harmer
2.626
CPLELTFEXP_CPLE->PJM
CLTF
0.304
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.985
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.292
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.887
LAGNLTFEXP_LAGN->PJM
CLTF
1.207
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.12
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.892
NYPJM->LTFIMP_NY
CLTF
0.008
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.25
MECLTFEXP_MEC->PJM
CLTF
0.173

Details for 4MARION CO-4LEBANON 138.0 kV Ckt 1 line l/o EKPC_P2-2_ELIHU-COOP 161_SRT-A


Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
4MARION CO-4LEBANON 138.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_ELIHU-COOP 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:100.58 %
Rating:220.0 MVA
Rating Type:B
MVA to Mitigate:221.27
MW Contribution:5.08
Bus #Bus NameTypeMW Contribution
965401AG1-405 GEN
Solar/Wind Harmer
3.902
965411AG1-406 GEN
Solar/Wind Harmer
1.751
971081AG2-670 GEN
Solar/Wind Harmer
16.464
339236AF1-050_GEN
Solar/Wind Harmer
2.822
339231AF1-038_GEN
Solar/Wind Harmer
1.595
339255AE2-071 GEN
Solar/Wind Harmer
0.708
964781AG1-341 GEN
Solar/Wind Harmer
6.887
971485AH1-239 GEN
Solar/Wind Harmer
5.081
966021AG1-471 GEN
Solar/Wind Harmer
3.398
970653AG2-424 GEN
Solar/Wind Harmer
2.53
970653AG2-424 GEN
Solar/Wind Harmer
0.915
339241AF1-083 GEN
Solar/Wind Harmer
4.225
964901AG1-354 GEN
Solar/Wind Harmer
17.574
970273AG2-179 GEN
Solar/Wind Harmer
2.108
3429031COOPER2 G
50/50
1.399
972273AH1-721 GEN
50/50
85.966
970273AG2-179 GEN
Solar/Wind Harmer
3.366
339250AF1-203 GEN
Solar/Wind Harmer
0.404
971155AH1-034 GEN
Solar/Wind Harmer
6.214
G-007ALTFEXP_G-007A->PJM
CMTX
0.006
CPLELTFEXP_CPLE->PJM
CLTF
0.288
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.269
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.308
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.948
LAGNLTFEXP_LAGN->PJM
CLTF
1.074
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.052
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.801
NYPJM->LTFIMP_NY
CLTF
0.005
VTFLTFEXP_VFT->PJM
CMTX
0.012
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.954
MECLTFEXP_MEC->PJM
CLTF
0.115

Details for 4MARION CO-4LEBANON 138.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-1


Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
4MARION CO-4LEBANON 138.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:100.49 %
Rating:220.0 MVA
Rating Type:B
MVA to Mitigate:221.08
MW Contribution:5.08
Bus #Bus NameTypeMW Contribution
965401AG1-405 GEN
Solar/Wind Harmer
3.905
965411AG1-406 GEN
Solar/Wind Harmer
1.752
971081AG2-670 GEN
Solar/Wind Harmer
16.467
339236AF1-050_GEN
Solar/Wind Harmer
2.822
339231AF1-038_GEN
Solar/Wind Harmer
1.596
339255AE2-071 GEN
Solar/Wind Harmer
0.708
964781AG1-341 GEN
Solar/Wind Harmer
6.89
971485AH1-239 GEN
Solar/Wind Harmer
5.081
966021AG1-471 GEN
Solar/Wind Harmer
3.397
970653AG2-424 GEN
Solar/Wind Harmer
2.531
970653AG2-424 GEN
Solar/Wind Harmer
0.915
339241AF1-083 GEN
Solar/Wind Harmer
4.226
964901AG1-354 GEN
Solar/Wind Harmer
17.578
970273AG2-179 GEN
Solar/Wind Harmer
2.109
3429031COOPER2 G
50/50
1.402
972273AH1-721 GEN
50/50
85.656
970273AG2-179 GEN
Solar/Wind Harmer
3.368
339250AF1-203 GEN
Solar/Wind Harmer
0.404
971155AH1-034 GEN
Solar/Wind Harmer
6.216
G-007ALTFEXP_G-007A->PJM
CMTX
0.005
CPLELTFEXP_CPLE->PJM
CLTF
0.288
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.272
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.308
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.948
LAGNLTFEXP_LAGN->PJM
CLTF
1.075
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.052
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.801
NYPJM->LTFIMP_NY
CLTF
0.005
VTFLTFEXP_VFT->PJM
CMTX
0.012
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.955
MECLTFEXP_MEC->PJM
CLTF
0.116

Details for 5COOPER1-5PULASK CO J 161.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-2


Base Case Flowgate

Area:EKPC
Facility Description:
5COOPER1-5PULASK CO J 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:116.86 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:348.26
MW Contribution:5.76
Bus #Bus NameTypeMW Contribution
339211AE2-254 GEN
Solar/Wind Helper
0.368
966021AG1-471 GEN
Solar/Wind Harmer
4.284
971485AH1-239 GEN
Solar/Wind Harmer
5.759
339241AF1-083 GEN
Solar/Wind Helper
0.54
3429031COOPER2 G
50/50
3.813
972273AH1-721 GEN
50/50
234.927
G-007ALTFEXP_G-007A->PJM
CMTX
0.016
CPLELTFEXP_CPLE->PJM
CLTF
0.21
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.065
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.203
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.641
LAGNLTFEXP_LAGN->PJM
CLTF
0.678
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.765
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.525
NYPJM->LTFIMP_NY
CLTF
0.001
VTFLTFEXP_VFT->PJM
CMTX
0.041
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.319
MECLTFEXP_MEC->PJM
CLTF
0.062

Details for 5COOPER2-5COOPER1 161.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-2


Base Case Flowgate

Area:EKPC
Facility Description:
5COOPER2-5COOPER1 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:173.45 %
Rating:501.0 MVA
Rating Type:B
MVA to Mitigate:869.01
MW Contribution:5.58
Bus #Bus NameTypeMW Contribution
966021AG1-471 GEN
Solar/Wind Harmer
4.247
971485AH1-239 GEN
Solar/Wind Harmer
5.582
3429031COOPER2 G
50/50
10.927
972273AH1-721 GEN
50/50
672.839
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.13
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.415
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.029
NYPJM->LTFIMP_NY
CLTF
0.055
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.011
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.002
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.257

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P7-1_LAURL 161 DBL_SRT-A


Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_LAURL 161 DBL_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:270.52 %
Rating:277.0 MVA
Rating Type:B
MVA to Mitigate:749.34
MW Contribution:13.2
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
2.141
970273AG2-179 GEN
Solar/Wind Harmer
3.839
339241AF1-083 GEN
Solar/Wind Harmer
1.907
964901AG1-354 GEN
Solar/Wind Harmer
15.318
962241AG1-070 GEN
Solar/Wind Harmer
3.892
971821AH1-427 GEN
Solar/Wind Harmer
6.111
965401AG1-405 GEN
Solar/Wind Harmer
7.672
965411AG1-406 GEN
Solar/Wind Harmer
3.443
966021AG1-471 GEN
Solar/Wind Harmer
9.329
971485AH1-239 GEN
Solar/Wind Harmer
13.196
339231AF1-038_GEN
Solar/Wind Harmer
2.843
971081AG2-670 GEN
Solar/Wind Harmer
8.31
339236AF1-050_GEN
Solar/Wind Harmer
1.903
339255AE2-071 GEN
Solar/Wind Harmer
1.084
964781AG1-341 GEN
Solar/Wind Harmer
10.424
970653AG2-424 GEN
Solar/Wind Harmer
2.677
970653AG2-424 GEN
Solar/Wind Harmer
0.968
3429031COOPER2 G
50/50
6.797
972273AH1-721 GEN
50/50
418.861
970273AG2-179 GEN
Solar/Wind Harmer
6.132
339250AF1-203 GEN
Solar/Wind Harmer
0.62
971155AH1-034 GEN
Solar/Wind Harmer
9.825
962251AG1-071 GEN
Solar/Wind Harmer
4.757
960741AF2-365 GEN
Solar/Wind Harmer
3.616
950011AG9-010
External Queue
11.361790657043457
CPLELTFEXP_CPLE->PJM
CLTF
0.123
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.004
LAGNLTFEXP_LAGN->PJM
CLTF
1.783
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.644
TVALTFEXP_TVA->PJM
CLTF
1.294
NYPJM->LTFIMP_NY
CLTF
0.082
WECLTFEXP_WEC->PJM
CLTF
0.079
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.553
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.921
MECLTFEXP_MEC->PJM
CLTF
0.665
SIGELTFEXP_SIGE->PJM
CLTF
0.024

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P2-2_LAUR-LAURD161_SRT-A


Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_LAUR-LAURD161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:270.47 %
Rating:277.0 MVA
Rating Type:B
MVA to Mitigate:749.21
MW Contribution:13.24
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
2.145
970273AG2-179 GEN
Solar/Wind Harmer
3.854
339241AF1-083 GEN
Solar/Wind Harmer
1.912
964901AG1-354 GEN
Solar/Wind Harmer
15.364
962241AG1-070 GEN
Solar/Wind Harmer
3.905
971821AH1-427 GEN
Solar/Wind Harmer
6.197
965401AG1-405 GEN
Solar/Wind Harmer
7.69
965411AG1-406 GEN
Solar/Wind Harmer
3.451
966021AG1-471 GEN
Solar/Wind Harmer
9.361
971485AH1-239 GEN
Solar/Wind Harmer
13.241
339231AF1-038_GEN
Solar/Wind Harmer
2.854
971081AG2-670 GEN
Solar/Wind Harmer
8.332
339236AF1-050_GEN
Solar/Wind Harmer
1.908
339255AE2-071 GEN
Solar/Wind Harmer
1.088
964781AG1-341 GEN
Solar/Wind Harmer
10.457
970653AG2-424 GEN
Solar/Wind Harmer
2.685
970653AG2-424 GEN
Solar/Wind Harmer
0.971
3429031COOPER2 G
50/50
6.809
972273AH1-721 GEN
50/50
419.594
970273AG2-179 GEN
Solar/Wind Harmer
6.155
339250AF1-203 GEN
Solar/Wind Harmer
0.622
971155AH1-034 GEN
Solar/Wind Harmer
9.857
962251AG1-071 GEN
Solar/Wind Harmer
4.772
960741AF2-365 GEN
Solar/Wind Harmer
3.628
950011AG9-010
External Queue
11.390689849853516
CPLELTFEXP_CPLE->PJM
CLTF
0.13
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.101
LAGNLTFEXP_LAGN->PJM
CLTF
1.805
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.667
TVALTFEXP_TVA->PJM
CLTF
1.308
NYPJM->LTFIMP_NY
CLTF
0.082
WECLTFEXP_WEC->PJM
CLTF
0.079
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.573
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.964
MECLTFEXP_MEC->PJM
CLTF
0.671
SIGELTFEXP_SIGE->PJM
CLTF
0.024

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P4-5_LAURL S50-1024_SRT-A


Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P4-5_LAURL S50-1024_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:270.46 %
Rating:277.0 MVA
Rating Type:B
MVA to Mitigate:749.18
MW Contribution:13.2
Bus #Bus NameTypeMW Contribution
965401AG1-405 GEN
Solar/Wind Harmer
7.672
965411AG1-406 GEN
Solar/Wind Harmer
3.443
966021AG1-471 GEN
Solar/Wind Harmer
9.329
971485AH1-239 GEN
Solar/Wind Harmer
13.196
339231AF1-038_GEN
Solar/Wind Harmer
2.843
971081AG2-670 GEN
Solar/Wind Harmer
8.31
339236AF1-050_GEN
Solar/Wind Harmer
1.903
339255AE2-071 GEN
Solar/Wind Harmer
1.084
964781AG1-341 GEN
Solar/Wind Harmer
10.424
970653AG2-424 GEN
Solar/Wind Harmer
2.677
970653AG2-424 GEN
Solar/Wind Harmer
0.968
3429451LAUREL 1G
50/50
2.141
970273AG2-179 GEN
Solar/Wind Harmer
3.839
339241AF1-083 GEN
Solar/Wind Harmer
1.907
964901AG1-354 GEN
Solar/Wind Harmer
15.318
962241AG1-070 GEN
Solar/Wind Harmer
3.892
971821AH1-427 GEN
Solar/Wind Harmer
6.111
3429031COOPER2 G
50/50
6.797
972273AH1-721 GEN
50/50
418.861
970273AG2-179 GEN
Solar/Wind Harmer
6.132
339250AF1-203 GEN
Solar/Wind Harmer
0.62
971155AH1-034 GEN
Solar/Wind Harmer
9.825
962251AG1-071 GEN
Solar/Wind Harmer
4.757
960741AF2-365 GEN
Solar/Wind Harmer
3.616
950011AG9-010
External Queue
11.361790657043457
CPLELTFEXP_CPLE->PJM
CLTF
0.123
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.004
LAGNLTFEXP_LAGN->PJM
CLTF
1.783
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.644
TVALTFEXP_TVA->PJM
CLTF
1.294
NYPJM->LTFIMP_NY
CLTF
0.082
WECLTFEXP_WEC->PJM
CLTF
0.079
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.553
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.921
MECLTFEXP_MEC->PJM
CLTF
0.665
SIGELTFEXP_SIGE->PJM
CLTF
0.024

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P2-3_LAURL S50-1024_SRT-A


Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_LAURL S50-1024_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:270.45 %
Rating:277.0 MVA
Rating Type:B
MVA to Mitigate:749.15
MW Contribution:13.2
Bus #Bus NameTypeMW Contribution
965401AG1-405 GEN
Solar/Wind Harmer
7.672
965411AG1-406 GEN
Solar/Wind Harmer
3.443
966021AG1-471 GEN
Solar/Wind Harmer
9.329
971485AH1-239 GEN
Solar/Wind Harmer
13.196
339231AF1-038_GEN
Solar/Wind Harmer
2.843
971081AG2-670 GEN
Solar/Wind Harmer
8.31
339236AF1-050_GEN
Solar/Wind Harmer
1.903
339255AE2-071 GEN
Solar/Wind Harmer
1.084
964781AG1-341 GEN
Solar/Wind Harmer
10.424
970653AG2-424 GEN
Solar/Wind Harmer
2.677
970653AG2-424 GEN
Solar/Wind Harmer
0.968
3429451LAUREL 1G
50/50
2.141
970273AG2-179 GEN
Solar/Wind Harmer
3.839
339241AF1-083 GEN
Solar/Wind Harmer
1.907
964901AG1-354 GEN
Solar/Wind Harmer
15.318
962241AG1-070 GEN
Solar/Wind Harmer
3.892
971821AH1-427 GEN
Solar/Wind Harmer
6.111
3429031COOPER2 G
50/50
6.797
972273AH1-721 GEN
50/50
418.861
970273AG2-179 GEN
Solar/Wind Harmer
6.132
339250AF1-203 GEN
Solar/Wind Harmer
0.62
971155AH1-034 GEN
Solar/Wind Harmer
9.825
962251AG1-071 GEN
Solar/Wind Harmer
4.757
960741AF2-365 GEN
Solar/Wind Harmer
3.616
950011AG9-010
External Queue
11.361790657043457
CPLELTFEXP_CPLE->PJM
CLTF
0.123
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.004
LAGNLTFEXP_LAGN->PJM
CLTF
1.783
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.644
TVALTFEXP_TVA->PJM
CLTF
1.294
NYPJM->LTFIMP_NY
CLTF
0.082
WECLTFEXP_WEC->PJM
CLTF
0.079
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.553
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.921
MECLTFEXP_MEC->PJM
CLTF
0.665
SIGELTFEXP_SIGE->PJM
CLTF
0.024

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P2-2_LAUREL CO 161_SRT-A


Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_LAUREL CO 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:270.38 %
Rating:277.0 MVA
Rating Type:B
MVA to Mitigate:748.95
MW Contribution:13.22
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
2.143
970273AG2-179 GEN
Solar/Wind Harmer
3.847
339241AF1-083 GEN
Solar/Wind Harmer
1.91
964901AG1-354 GEN
Solar/Wind Harmer
15.342
962241AG1-070 GEN
Solar/Wind Harmer
3.898
971821AH1-427 GEN
Solar/Wind Harmer
6.192
965401AG1-405 GEN
Solar/Wind Harmer
7.682
965411AG1-406 GEN
Solar/Wind Harmer
3.448
966021AG1-471 GEN
Solar/Wind Harmer
9.345
971485AH1-239 GEN
Solar/Wind Harmer
13.218
339231AF1-038_GEN
Solar/Wind Harmer
2.849
971081AG2-670 GEN
Solar/Wind Harmer
8.322
339236AF1-050_GEN
Solar/Wind Harmer
1.906
339255AE2-071 GEN
Solar/Wind Harmer
1.086
964781AG1-341 GEN
Solar/Wind Harmer
10.441
970653AG2-424 GEN
Solar/Wind Harmer
2.682
970653AG2-424 GEN
Solar/Wind Harmer
0.969
3429031COOPER2 G
50/50
6.803
972273AH1-721 GEN
50/50
419.22
970273AG2-179 GEN
Solar/Wind Harmer
6.144
339250AF1-203 GEN
Solar/Wind Harmer
0.621
971155AH1-034 GEN
Solar/Wind Harmer
9.841
962251AG1-071 GEN
Solar/Wind Harmer
4.765
960741AF2-365 GEN
Solar/Wind Harmer
3.623
950011AG9-010
External Queue
11.378859519958496
CPLELTFEXP_CPLE->PJM
CLTF
0.126
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.056
LAGNLTFEXP_LAGN->PJM
CLTF
1.795
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.656
TVALTFEXP_TVA->PJM
CLTF
1.301
NYPJM->LTFIMP_NY
CLTF
0.082
WECLTFEXP_WEC->PJM
CLTF
0.079
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.564
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.944
MECLTFEXP_MEC->PJM
CLTF
0.668
SIGELTFEXP_SIGE->PJM
CLTF
0.024

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P1-2_LAUR-L DAM161_SRT-A


Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_LAUR-L DAM161_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:257.87 %
Rating:277.0 MVA
Rating Type:B
MVA to Mitigate:714.31
MW Contribution:9.24
Bus #Bus NameTypeMW Contribution
966021AG1-471 GEN
Solar/Wind Harmer
6.531
971485AH1-239 GEN
Solar/Wind Harmer
9.238
971081AG2-670 GEN
Solar/Wind Harmer
5.813
339255AE2-071 GEN
Solar/Wind Harmer
-0.117
964781AG1-341 GEN
Solar/Wind Harmer
7.296
970653AG2-424 GEN
Solar/Wind Harmer
1.873
970653AG2-424 GEN
Solar/Wind Harmer
0.971
965401AG1-405 GEN
Solar/Wind Harmer
5.365
965411AG1-406 GEN
Solar/Wind Harmer
3.451
3429451LAUREL 1G
50/50
2.145
970273AG2-179 GEN
Solar/Wind Harmer
3.854
964901AG1-354 GEN
Solar/Wind Harmer
10.719
962241AG1-070 GEN
Solar/Wind Harmer
3.299
971821AH1-427 GEN
Solar/Wind Harmer
4.324
3429031COOPER2 G
50/50
6.809
972273AH1-721 GEN
50/50
419.594
970273AG2-179 GEN
Solar/Wind Harmer
6.607
339250AF1-203 GEN
Solar/Wind Harmer
0.001
971155AH1-034 GEN
Solar/Wind Harmer
8.023
962251AG1-071 GEN
Solar/Wind Harmer
3.784
960741AF2-365 GEN
Solar/Wind Harmer
2.531
950011AG9-010
External Queue
11.390689849853516
CPLELTFEXP_CPLE->PJM
CLTF
0.13
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.101
LAGNLTFEXP_LAGN->PJM
CLTF
1.805
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.667
TVALTFEXP_TVA->PJM
CLTF
1.308
NYPJM->LTFIMP_NY
CLTF
0.082
WECLTFEXP_WEC->PJM
CLTF
0.079
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.573
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.964
MECLTFEXP_MEC->PJM
CLTF
0.671
SIGELTFEXP_SIGE->PJM
CLTF
0.024

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:257.03 %
Rating:219.0 MVA
Rating Type:A
MVA to Mitigate:562.89
MW Contribution:7.87
Bus #Bus NameTypeMW Contribution
966021AG1-471 GEN
Solar/Wind Harmer
5.566
971485AH1-239 GEN
Solar/Wind Harmer
7.869
971081AG2-670 GEN
Solar/Wind Harmer
4.974
339255AE2-071 GEN
Solar/Wind Harmer
-0.099
964781AG1-341 GEN
Solar/Wind Harmer
6.206
970653AG2-424 GEN
Solar/Wind Harmer
1.578
970653AG2-424 GEN
Solar/Wind Harmer
0.818
3429031COOPER2 G
50/50
5.929
972273AH1-721 GEN
50/50
363.688
970273AG2-179 GEN
Solar/Wind Harmer
5.359
339250AF1-203 GEN
Solar/Wind Harmer
0.001
971155AH1-034 GEN
Solar/Wind Harmer
6.793
962251AG1-071 GEN
Solar/Wind Harmer
3.209
960741AF2-365 GEN
Solar/Wind Harmer
2.143
3429451LAUREL 1G
50/50
1.187
970273AG2-179 GEN
Solar/Wind Harmer
3.126
964901AG1-354 GEN
Solar/Wind Harmer
9.137
962241AG1-070 GEN
Solar/Wind Harmer
2.798
971821AH1-427 GEN
Solar/Wind Harmer
4.497
965401AG1-405 GEN
Solar/Wind Harmer
4.216
965411AG1-406 GEN
Solar/Wind Harmer
2.712
339211AE2-254 GEN
Solar/Wind Harmer
0.001
950011AG9-010
External Queue
9.891345024108887
CPLELTFEXP_CPLE->PJM
CLTF
0.092
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.126
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.03
LAGNLTFEXP_LAGN->PJM
CLTF
1.442
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.493
TVALTFEXP_TVA->PJM
CLTF
1.06
NYPJM->LTFIMP_NY
CLTF
0.066
WECLTFEXP_WEC->PJM
CLTF
0.058
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.906
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.139
MECLTFEXP_MEC->PJM
CLTF
0.519
SIGELTFEXP_SIGE->PJM
CLTF
0.016

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P1-2_COOP 161 TIE_SRT-A


Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_COOP 161 TIE_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:254.86 %
Rating:277.0 MVA
Rating Type:B
MVA to Mitigate:705.97
MW Contribution:4.0
Bus #Bus NameTypeMW Contribution
966021AG1-471 GEN
Solar/Wind Harmer
2.99
971485AH1-239 GEN
Solar/Wind Harmer
4.002
3429451LAUREL 1G
50/50
1.896
3429031COOPER2 G
50/50
9.148
972273AH1-721 GEN
50/50
560.965
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.187
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.586
LAGNLTFEXP_LAGN->PJM
CLTF
0.032
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.078
NYPJM->LTFIMP_NY
CLTF
0.06
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.029
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.015
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.23

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 1_SRT-A


Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 1_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:224.64 %
Rating:277.0 MVA
Rating Type:B
MVA to Mitigate:622.24
MW Contribution:7.69
Bus #Bus NameTypeMW Contribution
966021AG1-471 GEN
Solar/Wind Harmer
5.649
971485AH1-239 GEN
Solar/Wind Harmer
7.693
339231AF1-038_GEN
Solar/Wind Harmer
1.23
965401AG1-405 GEN
Solar/Wind Harmer
5.14
965411AG1-406 GEN
Solar/Wind Harmer
2.307
3429451LAUREL 1G
50/50
1.68
970273AG2-179 GEN
Solar/Wind Harmer
1.653
3429031COOPER2 G
50/50
8.114
972273AH1-721 GEN
50/50
497.807
970273AG2-179 GEN
Solar/Wind Harmer
2.64
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.895
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.167
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.5
LAGNLTFEXP_LAGN->PJM
CLTF
0.331
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.05
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.283
NYPJM->LTFIMP_NY
CLTF
0.058
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.001
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.638

Details for 5LAUREL CO-5PITTSBURG 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL CO-5PITTSBURG 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:174.31 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:348.62
MW Contribution:4.13
Bus #Bus NameTypeMW Contribution
966021AG1-471 GEN
Solar/Wind Harmer
3.031
971485AH1-239 GEN
Solar/Wind Harmer
4.13
3429451LAUREL 1G
50/50
1.753
972273AH1-721 GEN
50/50
289.389
CPLELTFEXP_CPLE->PJM
CLTF
0.149
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.797
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.01
LAGNLTFEXP_LAGN->PJM
CLTF
0.621
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.561
TVALTFEXP_TVA->PJM
CLTF
0.418
NYPJM->LTFIMP_NY
CLTF
0.006
WECLTFEXP_WEC->PJM
CLTF
0.017
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.533
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.26
MECLTFEXP_MEC->PJM
CLTF
0.179
SIGELTFEXP_SIGE->PJM
CLTF
0.004

Details for 5LAUREL CO-5PITTSBURG 161.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL CO-5PITTSBURG 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:173.74 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:347.48
MW Contribution:4.11
Bus #Bus NameTypeMW Contribution
966021AG1-471 GEN
Solar/Wind Harmer
3.013
971485AH1-239 GEN
Solar/Wind Harmer
4.113
3429451LAUREL 1G
50/50
1.747
972273AH1-721 GEN
50/50
287.816
CPLELTFEXP_CPLE->PJM
CLTF
0.147
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.863
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.005
LAGNLTFEXP_LAGN->PJM
CLTF
0.629
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.555
TVALTFEXP_TVA->PJM
CLTF
0.423
NYPJM->LTFIMP_NY
CLTF
0.006
WECLTFEXP_WEC->PJM
CLTF
0.018
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.576
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.282
MECLTFEXP_MEC->PJM
CLTF
0.185
SIGELTFEXP_SIGE->PJM
CLTF
0.005

Details for 5LAUREL CO-5PITTSBURG 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL CO-5PITTSBURG 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:173.72 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:347.44
MW Contribution:4.11
Bus #Bus NameTypeMW Contribution
966021AG1-471 GEN
Solar/Wind Harmer
3.013
971485AH1-239 GEN
Solar/Wind Harmer
4.113
3429451LAUREL 1G
50/50
1.747
972273AH1-721 GEN
50/50
287.816
CPLELTFEXP_CPLE->PJM
CLTF
0.147
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.863
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.005
LAGNLTFEXP_LAGN->PJM
CLTF
0.629
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.555
TVALTFEXP_TVA->PJM
CLTF
0.423
NYPJM->LTFIMP_NY
CLTF
0.006
WECLTFEXP_WEC->PJM
CLTF
0.018
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.576
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.282
MECLTFEXP_MEC->PJM
CLTF
0.185
SIGELTFEXP_SIGE->PJM
CLTF
0.005

Details for 5LAUREL CO-5PITTSBURG 161.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-1


Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL CO-5PITTSBURG 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:102.02 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:204.05
MW Contribution:3.86
Bus #Bus NameTypeMW Contribution
965401AG1-405 GEN
Solar/Wind Harmer
2.513
965411AG1-406 GEN
Solar/Wind Harmer
1.128
3429451LAUREL 1G
50/50
1.124
970273AG2-179 GEN
Solar/Wind Harmer
1.266
339231AF1-038_GEN
Solar/Wind Harmer
0.946
966021AG1-471 GEN
Solar/Wind Harmer
2.731
971485AH1-239 GEN
Solar/Wind Harmer
3.861
972273AH1-721 GEN
50/50
106.424
3429031COOPER2 G
50/50
1.682
970273AG2-179 GEN
Solar/Wind Harmer
2.022
CPLELTFEXP_CPLE->PJM
CLTF
0.147
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.165
LAGNLTFEXP_LAGN->PJM
CLTF
0.842
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.587
TVALTFEXP_TVA->PJM
CLTF
0.574
NYPJM->LTFIMP_NY
CLTF
0.019
LGEELTFEXP_LGEE->PJM
CLTF
0.037
WECLTFEXP_WEC->PJM
CLTF
0.035
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.123
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.805
MECLTFEXP_MEC->PJM
CLTF
0.296
SIGELTFEXP_SIGE->PJM
CLTF
0.011

Details for 5LAUREL CO-5PITTSBURG 161.0 kV Ckt 1 line l/o EKPC_P2-2_ELIHU-COOP 161_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL CO-5PITTSBURG 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_ELIHU-COOP 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:101.66 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:203.32
MW Contribution:3.86
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
1.121
970273AG2-179 GEN
Solar/Wind Harmer
1.27
965401AG1-405 GEN
Solar/Wind Harmer
2.522
965411AG1-406 GEN
Solar/Wind Harmer
1.132
339231AF1-038_GEN
Solar/Wind Harmer
0.948
966021AG1-471 GEN
Solar/Wind Harmer
2.729
971485AH1-239 GEN
Solar/Wind Harmer
3.86
972273AH1-721 GEN
50/50
105.494
3429031COOPER2 G
50/50
1.689
970273AG2-179 GEN
Solar/Wind Harmer
2.028
CPLELTFEXP_CPLE->PJM
CLTF
0.147
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.172
LAGNLTFEXP_LAGN->PJM
CLTF
0.843
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.587
TVALTFEXP_TVA->PJM
CLTF
0.575
NYPJM->LTFIMP_NY
CLTF
0.019
LGEELTFEXP_LGEE->PJM
CLTF
0.037
WECLTFEXP_WEC->PJM
CLTF
0.035
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.126
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.807
MECLTFEXP_MEC->PJM
CLTF
0.296
SIGELTFEXP_SIGE->PJM
CLTF
0.012

Details for 5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:301.06 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:602.12
MW Contribution:6.02
Bus #Bus NameTypeMW Contribution
966021AG1-471 GEN
Solar/Wind Harmer
4.438
971485AH1-239 GEN
Solar/Wind Harmer
6.024
3429451LAUREL 1G
50/50
2.917
972273AH1-721 GEN
50/50
477.648
CPLELTFEXP_CPLE->PJM
CLTF
0.082
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.449
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.004
LAGNLTFEXP_LAGN->PJM
CLTF
0.527
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.342
TVALTFEXP_TVA->PJM
CLTF
0.367
NYPJM->LTFIMP_NY
CLTF
0.018
WECLTFEXP_WEC->PJM
CLTF
0.016
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.502
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.104
MECLTFEXP_MEC->PJM
CLTF
0.163
SIGELTFEXP_SIGE->PJM
CLTF
0.004

Details for 5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:300.14 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:600.27
MW Contribution:5.99
Bus #Bus NameTypeMW Contribution
966021AG1-471 GEN
Solar/Wind Harmer
4.405
971485AH1-239 GEN
Solar/Wind Harmer
5.987
3429451LAUREL 1G
50/50
2.91
972273AH1-721 GEN
50/50
475.838
CPLELTFEXP_CPLE->PJM
CLTF
0.079
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.51
LAGNLTFEXP_LAGN->PJM
CLTF
0.532
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.333
TVALTFEXP_TVA->PJM
CLTF
0.37
NYPJM->LTFIMP_NY
CLTF
0.019
WECLTFEXP_WEC->PJM
CLTF
0.017
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.547
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.121
MECLTFEXP_MEC->PJM
CLTF
0.169
SIGELTFEXP_SIGE->PJM
CLTF
0.005

Details for 5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:300.12 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:600.24
MW Contribution:5.99
Bus #Bus NameTypeMW Contribution
966021AG1-471 GEN
Solar/Wind Harmer
4.405
971485AH1-239 GEN
Solar/Wind Harmer
5.987
3429451LAUREL 1G
50/50
2.91
972273AH1-721 GEN
50/50
475.838
CPLELTFEXP_CPLE->PJM
CLTF
0.079
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.51
LAGNLTFEXP_LAGN->PJM
CLTF
0.532
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.333
TVALTFEXP_TVA->PJM
CLTF
0.37
NYPJM->LTFIMP_NY
CLTF
0.019
WECLTFEXP_WEC->PJM
CLTF
0.017
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.547
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.121
MECLTFEXP_MEC->PJM
CLTF
0.169
SIGELTFEXP_SIGE->PJM
CLTF
0.005

Details for 5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-1


Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:178.78 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:357.55
MW Contribution:5.56
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
1.854
970273AG2-179 GEN
Solar/Wind Harmer
1.845
339241AF1-083 GEN
Solar/Wind Harmer
0.787
965401AG1-405 GEN
Solar/Wind Harmer
3.968
965411AG1-406 GEN
Solar/Wind Harmer
1.781
339231AF1-038_GEN
Solar/Wind Harmer
1.376
966021AG1-471 GEN
Solar/Wind Harmer
3.927
971485AH1-239 GEN
Solar/Wind Harmer
5.562
971081AG2-670 GEN
Solar/Wind Harmer
3.441
339255AE2-071 GEN
Solar/Wind Harmer
0.465
339236AF1-050_GEN
Solar/Wind Harmer
0.794
972273AH1-721 GEN
50/50
168.515
3429031COOPER2 G
50/50
2.659
970273AG2-179 GEN
Solar/Wind Harmer
2.947
339250AF1-203 GEN
Solar/Wind Harmer
0.266
CPLELTFEXP_CPLE->PJM
CLTF
0.081
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.739
LAGNLTFEXP_LAGN->PJM
CLTF
0.897
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.392
TVALTFEXP_TVA->PJM
CLTF
0.628
NYPJM->LTFIMP_NY
CLTF
0.04
LGEELTFEXP_LGEE->PJM
CLTF
0.082
WECLTFEXP_WEC->PJM
CLTF
0.046
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.499
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.014
MECLTFEXP_MEC->PJM
CLTF
0.359
SIGELTFEXP_SIGE->PJM
CLTF
0.016

Details for 5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line l/o EKPC_P2-2_ELIHU-COOP 161_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_ELIHU-COOP 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:178.17 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:356.33
MW Contribution:5.56
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
1.849
970273AG2-179 GEN
Solar/Wind Harmer
1.851
339241AF1-083 GEN
Solar/Wind Harmer
0.79
965401AG1-405 GEN
Solar/Wind Harmer
3.983
965411AG1-406 GEN
Solar/Wind Harmer
1.787
339231AF1-038_GEN
Solar/Wind Harmer
1.381
966021AG1-471 GEN
Solar/Wind Harmer
3.925
971485AH1-239 GEN
Solar/Wind Harmer
5.56
971081AG2-670 GEN
Solar/Wind Harmer
3.453
339255AE2-071 GEN
Solar/Wind Harmer
0.466
339236AF1-050_GEN
Solar/Wind Harmer
0.796
972273AH1-721 GEN
50/50
166.938
3429031COOPER2 G
50/50
2.67
970273AG2-179 GEN
Solar/Wind Harmer
2.956
339250AF1-203 GEN
Solar/Wind Harmer
0.266
CPLELTFEXP_CPLE->PJM
CLTF
0.081
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.751
LAGNLTFEXP_LAGN->PJM
CLTF
0.899
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.392
TVALTFEXP_TVA->PJM
CLTF
0.629
NYPJM->LTFIMP_NY
CLTF
0.04
LGEELTFEXP_LGEE->PJM
CLTF
0.083
WECLTFEXP_WEC->PJM
CLTF
0.047
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.504
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.018
MECLTFEXP_MEC->PJM
CLTF
0.36
SIGELTFEXP_SIGE->PJM
CLTF
0.016

Details for 5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line l/o EKPC_P1-2_COOP-ELIHU161_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_COOP-ELIHU161_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:173.81 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:347.62
MW Contribution:3.88
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
166.938
3429031COOPER2 G
50/50
2.67
970273AG2-179 GEN
Solar/Wind Harmer
3.173
339250AF1-203 GEN
Solar/Wind Harmer
0
966021AG1-471 GEN
Solar/Wind Harmer
2.738
971485AH1-239 GEN
Solar/Wind Harmer
3.879
971081AG2-670 GEN
Solar/Wind Harmer
2.409
339255AE2-071 GEN
Solar/Wind Harmer
-0.05
3429451LAUREL 1G
50/50
1.849
970273AG2-179 GEN
Solar/Wind Harmer
1.851
965401AG1-405 GEN
Solar/Wind Harmer
2.779
965411AG1-406 GEN
Solar/Wind Harmer
1.787
CPLELTFEXP_CPLE->PJM
CLTF
0.081
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.751
LAGNLTFEXP_LAGN->PJM
CLTF
0.899
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.392
TVALTFEXP_TVA->PJM
CLTF
0.629
NYPJM->LTFIMP_NY
CLTF
0.04
LGEELTFEXP_LGEE->PJM
CLTF
0.083
WECLTFEXP_WEC->PJM
CLTF
0.047
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.504
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.018
MECLTFEXP_MEC->PJM
CLTF
0.36
SIGELTFEXP_SIGE->PJM
CLTF
0.016

Details for 5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line l/o EXT_B-345-100_SRT-S


Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EXT_B-345-100_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:144.72 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:289.44
MW Contribution:3.5
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
1.77
970273AG2-179 GEN
Solar/Wind Harmer
1.902
965401AG1-405 GEN
Solar/Wind Harmer
3.339
965411AG1-406 GEN
Solar/Wind Harmer
2.148
966021AG1-471 GEN
Solar/Wind Harmer
2.471
971485AH1-239 GEN
Solar/Wind Harmer
3.501
972273AH1-721 GEN
50/50
136.002
3429031COOPER2 G
50/50
2.164
970273AG2-179 GEN
Solar/Wind Harmer
3.261
CPLELTFEXP_CPLE->PJM
CLTF
0.107
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.408
LAGNLTFEXP_LAGN->PJM
CLTF
0.867
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.465
TVALTFEXP_TVA->PJM
CLTF
0.605
NYPJM->LTFIMP_NY
CLTF
0.032
LGEELTFEXP_LGEE->PJM
CLTF
0.038
WECLTFEXP_WEC->PJM
CLTF
0.039
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.255
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.899
MECLTFEXP_MEC->PJM
CLTF
0.322
SIGELTFEXP_SIGE->PJM
CLTF
0.013

Details for 5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line l/o EKPC_P2-2_PULASKI 161_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_PULASKI 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:131.09 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:262.19
MW Contribution:3.47
Bus #Bus NameTypeMW Contribution
965401AG1-405 GEN
Solar/Wind Harmer
2.467
965411AG1-406 GEN
Solar/Wind Harmer
1.107
966021AG1-471 GEN
Solar/Wind Harmer
2.475
339231AF1-038_GEN
Solar/Wind Harmer
0.827
971485AH1-239 GEN
Solar/Wind Harmer
3.473
3429451LAUREL 1G
50/50
1.653
970273AG2-179 GEN
Solar/Wind Harmer
1.115
972273AH1-721 GEN
50/50
105.722
3429031COOPER2 G
50/50
1.672
970273AG2-179 GEN
Solar/Wind Harmer
1.781
CPLELTFEXP_CPLE->PJM
CLTF
0.081
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.158
LAGNLTFEXP_LAGN->PJM
CLTF
0.611
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.351
TVALTFEXP_TVA->PJM
CLTF
0.423
NYPJM->LTFIMP_NY
CLTF
0.024
LGEELTFEXP_LGEE->PJM
CLTF
0.07
WECLTFEXP_WEC->PJM
CLTF
0.029
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.927
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.373
MECLTFEXP_MEC->PJM
CLTF
0.232
SIGELTFEXP_SIGE->PJM
CLTF
0.01

Details for 5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line l/o EKPC_P2-2_LIB JCT 161_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_LIB JCT 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:129.44 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:258.87
MW Contribution:3.45
Bus #Bus NameTypeMW Contribution
965401AG1-405 GEN
Solar/Wind Harmer
3.383
965411AG1-406 GEN
Solar/Wind Harmer
1.518
339231AF1-038_GEN
Solar/Wind Harmer
0.853
966021AG1-471 GEN
Solar/Wind Harmer
2.461
971485AH1-239 GEN
Solar/Wind Harmer
3.454
3429451LAUREL 1G
50/50
1.648
970273AG2-179 GEN
Solar/Wind Harmer
1.147
972273AH1-721 GEN
50/50
104.097
3429031COOPER2 G
50/50
1.645
970273AG2-179 GEN
Solar/Wind Harmer
1.832
CPLELTFEXP_CPLE->PJM
CLTF
0.079
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.122
LAGNLTFEXP_LAGN->PJM
CLTF
0.603
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.343
TVALTFEXP_TVA->PJM
CLTF
0.418
NYPJM->LTFIMP_NY
CLTF
0.024
LGEELTFEXP_LGEE->PJM
CLTF
0.071
WECLTFEXP_WEC->PJM
CLTF
0.029
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.922
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.357
MECLTFEXP_MEC->PJM
CLTF
0.23
SIGELTFEXP_SIGE->PJM
CLTF
0.01

Details for 5LIBERTY J-5CASEY CO 161.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-2


Base Case Flowgate

Area:EKPC
Facility Description:
5LIBERTY J-5CASEY CO 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:101.66 %
Rating:182.0 MVA
Rating Type:B
MVA to Mitigate:185.03
MW Contribution:3.55
Bus #Bus NameTypeMW Contribution
339231AF1-038_GEN
Solar/Wind Harmer
1.313
966021AG1-471 GEN
Solar/Wind Harmer
2.708
971485AH1-239 GEN
Solar/Wind Harmer
3.551
339236AF1-050_GEN
Solar/Wind Helper
0.503
965401AG1-405 GEN
Solar/Wind Harmer
6.116
965411AG1-406 GEN
Solar/Wind Harmer
2.745
970273AG2-179 GEN
Solar/Wind Harmer
1.711
339241AF1-083 GEN
Solar/Wind Helper
0.88
3429031COOPER2 G
50/50
2.319
972273AH1-721 GEN
50/50
142.913
970273AG2-179 GEN
Solar/Wind Harmer
2.732
G-007ALTFEXP_G-007A->PJM
CMTX
0.06
CPLELTFEXP_CPLE->PJM
CLTF
0.148
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.092
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.223
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.752
LAGNLTFEXP_LAGN->PJM
CLTF
0.224
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.511
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.214
VTFLTFEXP_VFT->PJM
CMTX
0.161
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.258
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.372

Details for 5MARION CO-4MARION CO 161.0/138.0 kV Ckt 1 transformer l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-2


Base Case Flowgate

Area:EKPC
Facility Description:
5MARION CO-4MARION CO 161.0/138.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:119.88 %
Rating:220.0 MVA
Rating Type:B
MVA to Mitigate:263.74
MW Contribution:5.85
Bus #Bus NameTypeMW Contribution
965401AG1-405 GEN
Solar/Wind Harmer
4.452
965411AG1-406 GEN
Solar/Wind Harmer
1.998
971081AG2-670 GEN
Solar/Wind Harmer
16.943
339236AF1-050_GEN
Solar/Wind Harmer
2.932
339231AF1-038_GEN
Solar/Wind Harmer
1.786
971485AH1-239 GEN
Solar/Wind Harmer
5.85
966021AG1-471 GEN
Solar/Wind Harmer
3.94
339255AE2-071 GEN
Solar/Wind Harmer
0.772
964781AG1-341 GEN
Solar/Wind Harmer
7.499
970653AG2-424 GEN
Solar/Wind Harmer
2.693
970653AG2-424 GEN
Solar/Wind Harmer
0.973
339241AF1-083 GEN
Solar/Wind Harmer
4.334
964901AG1-354 GEN
Solar/Wind Harmer
18.467
970273AG2-179 GEN
Solar/Wind Harmer
2.363
962241AG1-070 GEN
Solar/Wind Harmer
2.149
3429031COOPER2 G
50/50
1.767
972273AH1-721 GEN
50/50
108.963
970273AG2-179 GEN
Solar/Wind Harmer
3.775
339250AF1-203 GEN
Solar/Wind Harmer
0.441
971155AH1-034 GEN
Solar/Wind Harmer
6.798
962251AG1-071 GEN
Solar/Wind Harmer
2.626
CPLELTFEXP_CPLE->PJM
CLTF
0.304
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.985
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.292
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.887
LAGNLTFEXP_LAGN->PJM
CLTF
1.207
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.12
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.892
NYPJM->LTFIMP_NY
CLTF
0.008
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.25
MECLTFEXP_MEC->PJM
CLTF
0.173

Details for 5MARION CO-4MARION CO 161.0/138.0 kV Ckt 1 transformer l/o EKPC_P2-2_ELIHU-COOP 161_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
5MARION CO-4MARION CO 161.0/138.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P2-2_ELIHU-COOP 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:100.55 %
Rating:220.0 MVA
Rating Type:B
MVA to Mitigate:221.22
MW Contribution:5.08
Bus #Bus NameTypeMW Contribution
965401AG1-405 GEN
Solar/Wind Harmer
3.902
965411AG1-406 GEN
Solar/Wind Harmer
1.751
971081AG2-670 GEN
Solar/Wind Harmer
16.464
339236AF1-050_GEN
Solar/Wind Harmer
2.822
339231AF1-038_GEN
Solar/Wind Harmer
1.595
339255AE2-071 GEN
Solar/Wind Harmer
0.708
964781AG1-341 GEN
Solar/Wind Harmer
6.887
971485AH1-239 GEN
Solar/Wind Harmer
5.081
966021AG1-471 GEN
Solar/Wind Harmer
3.398
970653AG2-424 GEN
Solar/Wind Harmer
2.53
970653AG2-424 GEN
Solar/Wind Harmer
0.915
339241AF1-083 GEN
Solar/Wind Harmer
4.225
964901AG1-354 GEN
Solar/Wind Harmer
17.574
970273AG2-179 GEN
Solar/Wind Harmer
2.108
3429031COOPER2 G
50/50
1.399
972273AH1-721 GEN
50/50
85.966
970273AG2-179 GEN
Solar/Wind Harmer
3.366
339250AF1-203 GEN
Solar/Wind Harmer
0.404
971155AH1-034 GEN
Solar/Wind Harmer
6.214
G-007ALTFEXP_G-007A->PJM
CMTX
0.006
CPLELTFEXP_CPLE->PJM
CLTF
0.288
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.269
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.308
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.948
LAGNLTFEXP_LAGN->PJM
CLTF
1.074
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.052
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.801
NYPJM->LTFIMP_NY
CLTF
0.005
VTFLTFEXP_VFT->PJM
CMTX
0.012
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.954
MECLTFEXP_MEC->PJM
CLTF
0.115

Details for 5MARION CO-4MARION CO 161.0/138.0 kV Ckt 1 transformer l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-1


Base Case Flowgate

Area:EKPC
Facility Description:
5MARION CO-4MARION CO 161.0/138.0 kV Ckt 1 transformer
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:100.47 %
Rating:220.0 MVA
Rating Type:B
MVA to Mitigate:221.02
MW Contribution:5.08
Bus #Bus NameTypeMW Contribution
965401AG1-405 GEN
Solar/Wind Harmer
3.905
965411AG1-406 GEN
Solar/Wind Harmer
1.752
971081AG2-670 GEN
Solar/Wind Harmer
16.467
339236AF1-050_GEN
Solar/Wind Harmer
2.822
339231AF1-038_GEN
Solar/Wind Harmer
1.596
339255AE2-071 GEN
Solar/Wind Harmer
0.708
964781AG1-341 GEN
Solar/Wind Harmer
6.89
971485AH1-239 GEN
Solar/Wind Harmer
5.081
966021AG1-471 GEN
Solar/Wind Harmer
3.397
970653AG2-424 GEN
Solar/Wind Harmer
2.531
970653AG2-424 GEN
Solar/Wind Harmer
0.915
339241AF1-083 GEN
Solar/Wind Harmer
4.226
964901AG1-354 GEN
Solar/Wind Harmer
17.578
970273AG2-179 GEN
Solar/Wind Harmer
2.109
3429031COOPER2 G
50/50
1.402
972273AH1-721 GEN
50/50
85.656
970273AG2-179 GEN
Solar/Wind Harmer
3.368
339250AF1-203 GEN
Solar/Wind Harmer
0.404
971155AH1-034 GEN
Solar/Wind Harmer
6.216
G-007ALTFEXP_G-007A->PJM
CMTX
0.005
CPLELTFEXP_CPLE->PJM
CLTF
0.288
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.272
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.308
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.948
LAGNLTFEXP_LAGN->PJM
CLTF
1.075
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.052
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.801
NYPJM->LTFIMP_NY
CLTF
0.005
VTFLTFEXP_VFT->PJM
CMTX
0.012
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.955
MECLTFEXP_MEC->PJM
CLTF
0.116

Details for 5PULASK CO J-5LIBERTY J 161.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-2


Base Case Flowgate

Area:EKPC
Facility Description:
5PULASK CO J-5LIBERTY J 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:100.77 %
Rating:256.0 MVA
Rating Type:B
MVA to Mitigate:257.97
MW Contribution:4.38
Bus #Bus NameTypeMW Contribution
965401AG1-405 GEN
Solar/Wind Harmer
7.258
965411AG1-406 GEN
Solar/Wind Harmer
3.257
339211AE2-254 GEN
Solar/Wind Helper
0.43
339241AF1-083 GEN
Solar/Wind Helper
0.721
966021AG1-471 GEN
Solar/Wind Harmer
3.329
971485AH1-239 GEN
Solar/Wind Harmer
4.382
339236AF1-050_GEN
Solar/Wind Helper
0.391
3429031COOPER2 G
50/50
2.985
972273AH1-721 GEN
50/50
183.956
G-007ALTFEXP_G-007A->PJM
CMTX
0.052
CPLELTFEXP_CPLE->PJM
CLTF
0.179
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.069
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.566
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.229
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.752
LAGNLTFEXP_LAGN->PJM
CLTF
0.398
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.633
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.332
VTFLTFEXP_VFT->PJM
CMTX
0.138
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.101
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.706

Details for 7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P4_1445_ZIMMER_SRT-A


Base Case Flowgate

Area:DAY/EKPC
Facility Description:
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
Contingency Name:
DEOK_P4_1445_ZIMMER_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:118.71 %
Rating:1532.0 MVA
Rating Type:B
MVA to Mitigate:1818.59
MW Contribution:7.09
Bus #Bus NameTypeMW Contribution
3429601SPURLK2G
50/50
18.627
972043AH1-570 GEN
Solar/Wind Harmer
7.195
972045AH1-571 GEN
Solar/Wind Harmer
5.756
971125AH1-004 GEN
Solar/Wind Harmer
11.442
970107AG2-081 GEN
Solar/Wind Harmer
8.582
960161AF2-307 GEN
Solar/Wind Harmer
17.966
339221AD2-048_GEN
Solar/Wind Harmer
4.296
942891AE2-308 GEN
Solar/Wind Harmer
25.136
339231AF1-038_GEN
Solar/Wind Harmer
1.926
970235AG2-159 GEN
Solar/Wind Harmer
4.243
970235AG2-159 GEN
Solar/Wind Harmer
2.59
971081AG2-670 GEN
Solar/Wind Harmer
7.638
970653AG2-424 GEN
Solar/Wind Harmer
4.629
970653AG2-424 GEN
Solar/Wind Harmer
1.673
339236AF1-050_GEN
Solar/Wind Harmer
1.673
966021AG1-471 GEN
Solar/Wind Harmer
4.84
270186AC1-089 GEN
Solar/Wind Harmer
5.47
971485AH1-239 GEN
Solar/Wind Harmer
7.086
964571AG1-320 GEN
Solar/Wind Harmer
7.225
339255AE2-071 GEN
Solar/Wind Harmer
0.846
964781AG1-341 GEN
Solar/Wind Harmer
8.106
971225AH1-072 GEN
Solar/Wind Harmer
0.881
971227AH1-073 GEN
Solar/Wind Harmer
0.881
253394AE2-221_GEN
Solar/Wind Helper
2.188
253398AE2-221_GEN2
Solar/Wind Helper
2.188
25183208HLCRTG
Solar/Wind Helper
2.422
252509AD1-136 GEN
Solar/Wind Helper
0.142
270518AE2-148 GEN
Solar/Wind Helper
6.114
3429661SPURLK4G
50/50
9.769
25197208MELDL3
50/50
1.274
3429571SPURLK1G
50/50
9.785
945681AF1-233 GEN
Solar/Wind Harmer
83.563
339216AC1-074 GEN
Solar/Wind Harmer
4.868
943111AE2-339 GEN
Solar/Wind Harmer
2.558
3429421JKCT 10G
Adder
24.075
3429241JKCT 3G
Adder
32.162
971821AH1-427 GEN
Solar/Wind Harmer
16.414
971565AH1-281 GEN
Solar/Wind Harmer
2.168
339241AF1-083 GEN
Solar/Wind Harmer
1.765
971315AH1-136 GEN
Solar/Wind Harmer
2.121
970273AG2-179 GEN
Solar/Wind Harmer
2.564
964901AG1-354 GEN
Solar/Wind Harmer
12.831
962241AG1-070 GEN
Solar/Wind Harmer
3.397
971687AH1-348 GEN
Solar/Wind Harmer
0.457
253343AC1-166 GEN
Solar/Wind Helper
0.796
253325AC1-069 GEN
Solar/Wind Helper
0.825
252507AC2-088 GEN
Solar/Wind Helper
0.993
25197008MELDL1
50/50
1.267
972163AH1-664 GEN
Solar/Wind Harmer
43.014
972165AH1-665 GEN
Solar/Wind Harmer
34.411
339243AC2-075 GEN1
Solar/Wind Harmer
1.318
3429211JKCT 2G
Adder
31.746
339211AE2-254 GEN
Solar/Wind Harmer
2.561
965401AG1-405 GEN
Solar/Wind Harmer
8.383
965411AG1-406 GEN
Solar/Wind Harmer
3.762
970455AG2-298 GEN
Solar/Wind Harmer
6.675
962211AG1-066 GEN
Solar/Wind Harmer
2.191
970281AG2-184 GEN
Solar/Wind Harmer
13.013
972143AH1-644 GEN
Solar/Wind Harmer
6.197
945631AF1-228 GEN
Solar/Wind Helper
0.922
241972AD1-140 GEN
Solar/Wind Helper
1.753
3429631SPURLK3G
50/50
9.769
25197108MELDL2
50/50
1.285
958171AF2-111 GEN
Solar/Wind Harmer
128.708
972167AH1-666 GEN
Solar/Wind Harmer
35.712
3429391JKCT 9G
Adder
24.075
970093AG2-073 GEN
Solar/Wind Harmer
23.159
966571AG1-526 GEN
Solar/Wind Harmer
42.232
972273AH1-721 GEN
Adder
104.488
970273AG2-179 GEN
Solar/Wind Harmer
4.096
960741AF2-365 GEN
Solar/Wind Harmer
4.057
339250AF1-203 GEN
Solar/Wind Harmer
0.484
971155AH1-034 GEN
Solar/Wind Harmer
7.829
962251AG1-071 GEN
Solar/Wind Harmer
4.152
972103AH1-617 GEN
Solar/Wind Harmer
12.393
971461AH1-227 GEN
Solar/Wind Harmer
2.259
253338AC1-165 GEN
Solar/Wind Helper
0.796
253333AC1-068 GEN
Solar/Wind Helper
0.825
253406AD2-031_GEN
Solar/Wind Helper
0.684
253415AE1-040 GEN
Solar/Wind Helper
0.407
950041AG9-017
External Queue
23.325098037719727
950011AG9-010
External Queue
6.110060214996338
950051AG9-018
External Queue
23.242685317993164
CPLELTFEXP_CPLE->PJM
CLTF
1.17
CBM West 2LTFEXP_CBM-W2->PJM
CBM
36.494
LAGNLTFEXP_LAGN->PJM
CLTF
6.065
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.858
TVALTFEXP_TVA->PJM
CLTF
3.721
NYPJM->LTFIMP_NY
CLTF
0.561
LGEELTFEXP_LGEE->PJM
CLTF
4.925
WECLTFEXP_WEC->PJM
CLTF
0.319
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.62
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.309
MECLTFEXP_MEC->PJM
CLTF
2.533
SIGELTFEXP_SIGE->PJM
CLTF
0.218

Details for 7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P4_1449_ZIMMER_SRT-A


Base Case Flowgate

Area:DAY/EKPC
Facility Description:
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
Contingency Name:
DEOK_P4_1449_ZIMMER_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:118.58 %
Rating:1532.0 MVA
Rating Type:B
MVA to Mitigate:1816.67
MW Contribution:7.08
Bus #Bus NameTypeMW Contribution
3429601SPURLK2G
50/50
18.629
972043AH1-570 GEN
Solar/Wind Harmer
7.195
972045AH1-571 GEN
Solar/Wind Harmer
5.756
971125AH1-004 GEN
Solar/Wind Harmer
11.441
970107AG2-081 GEN
Solar/Wind Harmer
8.581
960161AF2-307 GEN
Solar/Wind Harmer
17.966
339221AD2-048_GEN
Solar/Wind Harmer
4.295
942891AE2-308 GEN
Solar/Wind Harmer
25.135
339231AF1-038_GEN
Solar/Wind Harmer
1.926
970235AG2-159 GEN
Solar/Wind Harmer
4.237
970235AG2-159 GEN
Solar/Wind Harmer
2.587
971081AG2-670 GEN
Solar/Wind Harmer
7.636
970653AG2-424 GEN
Solar/Wind Harmer
4.628
970653AG2-424 GEN
Solar/Wind Harmer
1.673
339236AF1-050_GEN
Solar/Wind Harmer
1.672
270186AC1-089 GEN
Solar/Wind Harmer
5.474
966021AG1-471 GEN
Solar/Wind Harmer
4.838
971485AH1-239 GEN
Solar/Wind Harmer
7.084
964571AG1-320 GEN
Solar/Wind Harmer
7.222
339255AE2-071 GEN
Solar/Wind Harmer
0.846
964781AG1-341 GEN
Solar/Wind Harmer
8.103
971225AH1-072 GEN
Solar/Wind Harmer
0.881
971227AH1-073 GEN
Solar/Wind Harmer
0.881
3429661SPURLK4G
50/50
9.77
25197208MELDL3
50/50
1.274
3429571SPURLK1G
50/50
9.786
945681AF1-233 GEN
Solar/Wind Harmer
83.568
339216AC1-074 GEN
Solar/Wind Harmer
4.867
943111AE2-339 GEN
Solar/Wind Harmer
2.558
3429421JKCT 10G
Adder
24.075
3429241JKCT 3G
Adder
32.161
971821AH1-427 GEN
Solar/Wind Harmer
16.411
971565AH1-281 GEN
Solar/Wind Harmer
2.167
339241AF1-083 GEN
Solar/Wind Harmer
1.764
971315AH1-136 GEN
Solar/Wind Harmer
2.12
970273AG2-179 GEN
Solar/Wind Harmer
2.564
964901AG1-354 GEN
Solar/Wind Harmer
12.826
962241AG1-070 GEN
Solar/Wind Harmer
3.396
971687AH1-348 GEN
Solar/Wind Harmer
0.457
253343AC1-166 GEN
Solar/Wind Helper
0.796
253325AC1-069 GEN
Solar/Wind Helper
0.825
252507AC2-088 GEN
Solar/Wind Helper
0.996
25197008MELDL1
50/50
1.267
972163AH1-664 GEN
Solar/Wind Harmer
43.016
972165AH1-665 GEN
Solar/Wind Harmer
34.413
339243AC2-075 GEN1
Solar/Wind Harmer
1.318
3429211JKCT 2G
Adder
31.745
339211AE2-254 GEN
Solar/Wind Harmer
2.561
965401AG1-405 GEN
Solar/Wind Harmer
8.381
965411AG1-406 GEN
Solar/Wind Harmer
3.762
970455AG2-298 GEN
Solar/Wind Harmer
6.673
962211AG1-066 GEN
Solar/Wind Harmer
2.191
970281AG2-184 GEN
Solar/Wind Harmer
13.012
972143AH1-644 GEN
Solar/Wind Harmer
6.196
945631AF1-228 GEN
Solar/Wind Helper
0.92
253394AE2-221_GEN
Solar/Wind Helper
2.185
253398AE2-221_GEN2
Solar/Wind Helper
2.185
25183208HLCRTG
Solar/Wind Helper
2.418
252509AD1-136 GEN
Solar/Wind Helper
0.142
270518AE2-148 GEN
Solar/Wind Helper
6.102
3429631SPURLK3G
50/50
9.77
25197108MELDL2
50/50
1.285
958171AF2-111 GEN
Solar/Wind Harmer
128.718
972167AH1-666 GEN
Solar/Wind Harmer
35.714
3429391JKCT 9G
Adder
24.075
970093AG2-073 GEN
Solar/Wind Harmer
23.157
966571AG1-526 GEN
Solar/Wind Harmer
42.226
972273AH1-721 GEN
Adder
104.468
970273AG2-179 GEN
Solar/Wind Harmer
4.095
960741AF2-365 GEN
Solar/Wind Harmer
4.056
339250AF1-203 GEN
Solar/Wind Harmer
0.483
971155AH1-034 GEN
Solar/Wind Harmer
7.826
962251AG1-071 GEN
Solar/Wind Harmer
4.151
972103AH1-617 GEN
Solar/Wind Harmer
12.392
971461AH1-227 GEN
Solar/Wind Harmer
2.259
253338AC1-165 GEN
Solar/Wind Helper
0.796
253333AC1-068 GEN
Solar/Wind Helper
0.825
253406AD2-031_GEN
Solar/Wind Helper
0.683
253415AE1-040 GEN
Solar/Wind Helper
0.407
950041AG9-017
External Queue
23.331375122070312
950011AG9-010
External Queue
6.113064289093018
950051AG9-018
External Queue
23.248964309692383
CPLELTFEXP_CPLE->PJM
CLTF
1.169
CBM West 2LTFEXP_CBM-W2->PJM
CBM
36.457
LAGNLTFEXP_LAGN->PJM
CLTF
6.06
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.856
TVALTFEXP_TVA->PJM
CLTF
3.719
NYPJM->LTFIMP_NY
CLTF
0.561
LGEELTFEXP_LGEE->PJM
CLTF
4.921
WECLTFEXP_WEC->PJM
CLTF
0.318
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.596
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.299
MECLTFEXP_MEC->PJM
CLTF
2.529
SIGELTFEXP_SIGE->PJM
CLTF
0.218

Details for 7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o 34569 34598 34524_SRT-A


Base Case Flowgate

Area:DAY/EKPC
Facility Description:
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
Contingency Name:
34569 34598 34524_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:117.61 %
Rating:1532.0 MVA
Rating Type:B
MVA to Mitigate:1801.71
MW Contribution:6.38
Bus #Bus NameTypeMW Contribution
25197008MELDL1
50/50
0.565
972163AH1-664 GEN
Solar/Wind Harmer
31.627
972165AH1-665 GEN
Solar/Wind Harmer
25.302
339243AC2-075 GEN1
Solar/Wind Harmer
1.04
3429211JKCT 2G
Adder
24.5
339211AE2-254 GEN
Solar/Wind Harmer
2.124
965401AG1-405 GEN
Solar/Wind Harmer
6.938
965411AG1-406 GEN
Solar/Wind Harmer
3.114
970455AG2-298 GEN
Solar/Wind Harmer
6.185
25196108MFTGT2
Adder
1.16
25196108MFTGT2
Adder
1.077
962211AG1-066 GEN
Solar/Wind Harmer
1.705
252524AE2-267 GEN
Solar/Wind Harmer
1.086
25196408WSDLE3
Adder
6.077
25196308WSDLE2
Adder
6.024
25196208WSDLE1
Adder
6.009
25196708WSDLE6
Adder
5.994
25196508WSDLE4
Adder
5.843
970281AG2-184 GEN
Solar/Wind Harmer
9.902
972143AH1-644 GEN
Solar/Wind Harmer
4.715
945631AF1-228 GEN
Solar/Wind Helper
1.431
241972AD1-140 GEN
Solar/Wind Helper
2.723
270340AC2-060 GEN
Solar/Wind Helper
1.337
270520AE2-214 GEN
Solar/Wind Helper
2.981
241973AD2-163_GEN1
Solar/Wind Helper
0.936
253383AE2-342_GEN
Solar/Wind Helper
0.365
3429661SPURLK4G
50/50
7.046
3429571SPURLK1G
50/50
7.13
25197208MELDL3
50/50
0.569
945681AF1-233 GEN
Solar/Wind Harmer
61.301
339216AC1-074 GEN
Solar/Wind Harmer
3.841
943111AE2-339 GEN
Solar/Wind Harmer
1.977
3429421JKCT 10G
Adder
18.466
25196808ZIMRHP
Adder
160.301
3429241JKCT 3G
Adder
24.821
971821AH1-427 GEN
Solar/Wind Harmer
13.653
971565AH1-281 GEN
Solar/Wind Harmer
2.045
339241AF1-083 GEN
Solar/Wind Harmer
1.592
970273AG2-179 GEN
Solar/Wind Harmer
2.255
964901AG1-354 GEN
Solar/Wind Harmer
12.036
971315AH1-136 GEN
Solar/Wind Harmer
1.582
25196008MFTGT1
Adder
1.052
962241AG1-070 GEN
Solar/Wind Harmer
3.274
25194608D.CRK4
Adder
1.11
253343AC1-166 GEN
Solar/Wind Helper
1.288
3429601SPURLK2G
50/50
13.435
972043AH1-570 GEN
Solar/Wind Harmer
5.591
972045AH1-571 GEN
Solar/Wind Harmer
4.473
971125AH1-004 GEN
Solar/Wind Harmer
8.9
970107AG2-081 GEN
Solar/Wind Harmer
6.675
339221AD2-048_GEN
Solar/Wind Harmer
3.382
960161AF2-307 GEN
Solar/Wind Harmer
13.557
942891AE2-308 GEN
Solar/Wind Harmer
19.615
970235AG2-159 GEN
Solar/Wind Harmer
4.694
970235AG2-159 GEN
Solar/Wind Harmer
2.866
339231AF1-038_GEN
Solar/Wind Harmer
1.69
971081AG2-670 GEN
Solar/Wind Harmer
6.943
970653AG2-424 GEN
Solar/Wind Harmer
4.401
970653AG2-424 GEN
Solar/Wind Harmer
1.591
964571AG1-320 GEN
Solar/Wind Harmer
7.156
339236AF1-050_GEN
Solar/Wind Harmer
1.548
966021AG1-471 GEN
Solar/Wind Harmer
4.332
971485AH1-239 GEN
Solar/Wind Harmer
6.379
339255AE2-071 GEN
Solar/Wind Harmer
0.801
964781AG1-341 GEN
Solar/Wind Harmer
7.773
270186AC1-089 GEN
Solar/Wind Harmer
4.24
25194408D.CRK1
Adder
5.107
25194508D.CRK3
Adder
0.955
25183208HLCRTG
Solar/Wind Helper
5.68
253394AE2-221_GEN
Solar/Wind Helper
3.647
253398AE2-221_GEN2
Solar/Wind Helper
3.647
270518AE2-148 GEN
Solar/Wind Helper
9.647
252509AD1-136 GEN
Solar/Wind Helper
0.14
946101AF1-275 GEN
Solar/Wind Helper
0.373
253325AC1-069 GEN
Solar/Wind Helper
1.335
252507AC2-088 GEN
Solar/Wind Helper
0.98
270263AC1-001 GEN
Solar/Wind Helper
0.509
3429631SPURLK3G
50/50
7.046
25197108MELDL2
50/50
0.574
958171AF2-111 GEN
Solar/Wind Harmer
93.548
972167AH1-666 GEN
Solar/Wind Harmer
26.189
3429391JKCT 9G
Adder
18.466
970093AG2-073 GEN
Solar/Wind Harmer
18.208
966571AG1-526 GEN
Solar/Wind Harmer
34.399
972273AH1-721 GEN
Adder
88.436
970273AG2-179 GEN
Solar/Wind Harmer
3.601
960741AF2-365 GEN
Solar/Wind Harmer
3.916
25196008MFTGT1
Adder
1.019
339250AF1-203 GEN
Solar/Wind Harmer
0.458
971155AH1-034 GEN
Solar/Wind Harmer
7.447
962251AG1-071 GEN
Solar/Wind Harmer
4.002
25196608WSDLE5
Adder
5.903
25194608D.CRK4
Adder
1.11
252510AF1-249 C
Solar/Wind Harmer
0.263
972103AH1-617 GEN
Solar/Wind Harmer
9.431
253338AC1-165 GEN
Solar/Wind Helper
1.288
253333AC1-068 GEN
Solar/Wind Helper
1.335
253406AD2-031_GEN
Solar/Wind Helper
1.189
253415AE1-040 GEN
Solar/Wind Helper
0.677
241955AC1-078 GEN
Solar/Wind Helper
1.207
241974AD2-163_GEN2
Solar/Wind Helper
0.936
270273AD2-016 GEN
Solar/Wind Helper
1.38
960801AF2-371 GEN
Solar/Wind Helper
0.521
964871AG1-351 GEN
Solar/Wind Helper
0.36
950041AG9-017
External Queue
14.816180229187012
950051AG9-018
External Queue
14.528197288513184
CPLELTFEXP_CPLE->PJM
CLTF
0.878
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.602
LAGNLTFEXP_LAGN->PJM
CLTF
6.832
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.13
TVALTFEXP_TVA->PJM
CLTF
3.879
NYPJM->LTFIMP_NY
CLTF
0.784
LGEELTFEXP_LGEE->PJM
CLTF
5.678
WECLTFEXP_WEC->PJM
CLTF
0.782
CBM West 1LTFEXP_CBM-W1->PJM
CBM
22.26
CBM South 1LTFEXP_CBM-S1->PJM
CBM
17.536
MECLTFEXP_MEC->PJM
CLTF
4.374
SIGELTFEXP_SIGE->PJM
CLTF
0.293

Details for 7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P4_1373_PORTUNION_SRT-A


Base Case Flowgate

Area:DAY/EKPC
Facility Description:
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
Contingency Name:
DEOK_P4_1373_PORTUNION_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.62 %
Rating:1532.0 MVA
Rating Type:B
MVA to Mitigate:1786.6
MW Contribution:6.42
Bus #Bus NameTypeMW Contribution
3429631SPURLK3G
50/50
7.884
25197108MELDL2
50/50
0.698
958171AF2-111 GEN
Solar/Wind Harmer
104.27
972167AH1-666 GEN
Solar/Wind Harmer
29.055
3429391JKCT 9G
Adder
20.047
970093AG2-073 GEN
Solar/Wind Harmer
19.531
966571AG1-526 GEN
Solar/Wind Harmer
36.287
972273AH1-721 GEN
Adder
91.547
970273AG2-179 GEN
Solar/Wind Harmer
3.663
960741AF2-365 GEN
Solar/Wind Harmer
3.824
339250AF1-203 GEN
Solar/Wind Harmer
0.45
971155AH1-034 GEN
Solar/Wind Harmer
7.314
962251AG1-071 GEN
Solar/Wind Harmer
3.909
972103AH1-617 GEN
Solar/Wind Harmer
10.145
25196008MFTGT1
Adder
0.637
253338AC1-165 GEN
Solar/Wind Helper
1.021
253333AC1-068 GEN
Solar/Wind Helper
1.058
253406AD2-031_GEN
Solar/Wind Helper
0.902
253415AE1-040 GEN
Solar/Wind Helper
0.53
241955AC1-078 GEN
Solar/Wind Helper
0.928
25197008MELDL1
50/50
0.688
972163AH1-664 GEN
Solar/Wind Harmer
35.04
972165AH1-665 GEN
Solar/Wind Harmer
28.032
339243AC2-075 GEN1
Solar/Wind Harmer
1.117
3429211JKCT 2G
Adder
26.517
339211AE2-254 GEN
Solar/Wind Harmer
2.222
965401AG1-405 GEN
Solar/Wind Harmer
7.259
965411AG1-406 GEN
Solar/Wind Harmer
3.258
970455AG2-298 GEN
Solar/Wind Harmer
6.151
962211AG1-066 GEN
Solar/Wind Harmer
1.825
970281AG2-184 GEN
Solar/Wind Harmer
10.652
972143AH1-644 GEN
Solar/Wind Harmer
5.072
25196108MFTGT2
Adder
0.725
25196108MFTGT2
Adder
0.673
945631AF1-228 GEN
Solar/Wind Helper
1.079
270340AC2-060 GEN
Solar/Wind Helper
1.058
270520AE2-214 GEN
Solar/Wind Helper
2.349
241972AD1-140 GEN
Solar/Wind Helper
1.835
3429601SPURLK2G
50/50
15.032
972043AH1-570 GEN
Solar/Wind Harmer
6.036
972045AH1-571 GEN
Solar/Wind Harmer
4.829
971125AH1-004 GEN
Solar/Wind Harmer
9.607
970107AG2-081 GEN
Solar/Wind Harmer
7.205
339221AD2-048_GEN
Solar/Wind Harmer
3.631
960161AF2-307 GEN
Solar/Wind Harmer
14.82
942891AE2-308 GEN
Solar/Wind Harmer
21.118
970235AG2-159 GEN
Solar/Wind Harmer
4.418
970235AG2-159 GEN
Solar/Wind Harmer
2.697
339231AF1-038_GEN
Solar/Wind Harmer
1.721
971081AG2-670 GEN
Solar/Wind Harmer
6.96
970653AG2-424 GEN
Solar/Wind Harmer
4.326
970653AG2-424 GEN
Solar/Wind Harmer
1.564
339236AF1-050_GEN
Solar/Wind Harmer
1.539
964571AG1-320 GEN
Solar/Wind Harmer
6.913
966021AG1-471 GEN
Solar/Wind Harmer
4.369
971485AH1-239 GEN
Solar/Wind Harmer
6.417
339255AE2-071 GEN
Solar/Wind Harmer
0.788
964781AG1-341 GEN
Solar/Wind Harmer
7.607
270186AC1-089 GEN
Solar/Wind Harmer
4.26
253394AE2-221_GEN
Solar/Wind Helper
2.834
253398AE2-221_GEN2
Solar/Wind Helper
2.834
25183208HLCRTG
Solar/Wind Helper
2.94
270518AE2-148 GEN
Solar/Wind Helper
6.991
946101AF1-275 GEN
Solar/Wind Helper
0.294
252509AD1-136 GEN
Solar/Wind Helper
0.105
3429661SPURLK4G
50/50
7.884
3429571SPURLK1G
50/50
7.938
25197208MELDL3
50/50
0.692
25196808ZIMRHP
50/50
216.474
945681AF1-233 GEN
Solar/Wind Harmer
67.998
339216AC1-074 GEN
Solar/Wind Harmer
4.124
943111AE2-339 GEN
Solar/Wind Harmer
2.139
3429421JKCT 10G
Adder
20.047
3429241JKCT 3G
Adder
26.865
971821AH1-427 GEN
Solar/Wind Harmer
14.261
971565AH1-281 GEN
Solar/Wind Harmer
2.017
339241AF1-083 GEN
Solar/Wind Harmer
1.601
970273AG2-179 GEN
Solar/Wind Harmer
2.293
971315AH1-136 GEN
Solar/Wind Harmer
1.727
964901AG1-354 GEN
Solar/Wind Harmer
11.895
962241AG1-070 GEN
Solar/Wind Harmer
3.198
25196008MFTGT1
Adder
0.658
253343AC1-166 GEN
Solar/Wind Helper
1.021
253325AC1-069 GEN
Solar/Wind Helper
1.058
252507AC2-088 GEN
Solar/Wind Helper
0.737
950041AG9-017
External Queue
17.643001556396484
950051AG9-018
External Queue
17.501935958862305
CPLELTFEXP_CPLE->PJM
CLTF
0.924
CBM West 2LTFEXP_CBM-W2->PJM
CBM
42.2
LAGNLTFEXP_LAGN->PJM
CLTF
6.269
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.16
TVALTFEXP_TVA->PJM
CLTF
3.662
NYPJM->LTFIMP_NY
CLTF
0.663
LGEELTFEXP_LGEE->PJM
CLTF
5.148
WECLTFEXP_WEC->PJM
CLTF
0.587
CBM West 1LTFEXP_CBM-W1->PJM
CBM
16.428
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.346
MECLTFEXP_MEC->PJM
CLTF
3.54
SIGELTFEXP_SIGE->PJM
CLTF
0.254

Details for 7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P4_1493_RED BANK_SRT-A


Base Case Flowgate

Area:DAY/EKPC
Facility Description:
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
Contingency Name:
DEOK_P4_1493_RED BANK_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.28 %
Rating:1532.0 MVA
Rating Type:B
MVA to Mitigate:1766.12
MW Contribution:6.3
Bus #Bus NameTypeMW Contribution
3429661SPURLK4G
50/50
8.094
3429571SPURLK1G
50/50
8.131
25197208MELDL3
50/50
0.74
25196808ZIMRHP
50/50
235.684
945681AF1-233 GEN
Solar/Wind Harmer
69.569
339216AC1-074 GEN
Solar/Wind Harmer
4.143
943111AE2-339 GEN
Solar/Wind Harmer
2.164
3429421JKCT 10G
Adder
20.324
3429241JKCT 3G
Adder
27.202
971821AH1-427 GEN
Solar/Wind Harmer
14.224
971565AH1-281 GEN
Solar/Wind Harmer
1.965
339241AF1-083 GEN
Solar/Wind Harmer
1.573
970273AG2-179 GEN
Solar/Wind Harmer
2.263
971315AH1-136 GEN
Solar/Wind Harmer
1.759
25197008MELDL1
50/50
0.735
972163AH1-664 GEN
Solar/Wind Harmer
35.835
972165AH1-665 GEN
Solar/Wind Harmer
28.668
339243AC2-075 GEN1
Solar/Wind Harmer
1.122
3429211JKCT 2G
Adder
26.85
339211AE2-254 GEN
Solar/Wind Harmer
2.217
965401AG1-405 GEN
Solar/Wind Harmer
7.248
965411AG1-406 GEN
Solar/Wind Harmer
3.253
970455AG2-298 GEN
Solar/Wind Harmer
6.011
962211AG1-066 GEN
Solar/Wind Harmer
1.843
970281AG2-184 GEN
Solar/Wind Harmer
10.786
972143AH1-644 GEN
Solar/Wind Harmer
5.136
945631AF1-228 GEN
Solar/Wind Helper
0.946
964901AG1-354 GEN
Solar/Wind Harmer
11.595
962241AG1-070 GEN
Solar/Wind Harmer
3.101
253343AC1-166 GEN
Solar/Wind Helper
0.943
253325AC1-069 GEN
Solar/Wind Helper
0.977
252507AC2-088 GEN
Solar/Wind Helper
0.88
3429601SPURLK2G
50/50
15.432
972043AH1-570 GEN
Solar/Wind Harmer
6.098
972045AH1-571 GEN
Solar/Wind Harmer
4.878
971125AH1-004 GEN
Solar/Wind Harmer
9.7
970107AG2-081 GEN
Solar/Wind Harmer
7.275
339221AD2-048_GEN
Solar/Wind Harmer
3.655
960161AF2-307 GEN
Solar/Wind Harmer
15.078
942891AE2-308 GEN
Solar/Wind Harmer
21.334
970235AG2-159 GEN
Solar/Wind Harmer
4.075
970235AG2-159 GEN
Solar/Wind Harmer
2.488
339231AF1-038_GEN
Solar/Wind Harmer
1.699
971081AG2-670 GEN
Solar/Wind Harmer
6.826
970653AG2-424 GEN
Solar/Wind Harmer
4.208
970653AG2-424 GEN
Solar/Wind Harmer
1.521
339236AF1-050_GEN
Solar/Wind Harmer
1.504
964571AG1-320 GEN
Solar/Wind Harmer
6.672
966021AG1-471 GEN
Solar/Wind Harmer
4.296
971485AH1-239 GEN
Solar/Wind Harmer
6.303
270186AC1-089 GEN
Solar/Wind Harmer
4.702
339255AE2-071 GEN
Solar/Wind Harmer
0.767
964781AG1-341 GEN
Solar/Wind Harmer
7.383
253394AE2-221_GEN
Solar/Wind Helper
2.6
253398AE2-221_GEN2
Solar/Wind Helper
2.6
25183208HLCRTG
Solar/Wind Helper
2.511
252509AD1-136 GEN
Solar/Wind Helper
0.126
270518AE2-148 GEN
Solar/Wind Helper
5.923
3429631SPURLK3G
50/50
8.094
25197108MELDL2
50/50
0.746
958171AF2-111 GEN
Solar/Wind Harmer
106.877
972167AH1-666 GEN
Solar/Wind Harmer
29.728
3429391JKCT 9G
Adder
20.324
970093AG2-073 GEN
Solar/Wind Harmer
19.701
966571AG1-526 GEN
Solar/Wind Harmer
36.35
972273AH1-721 GEN
Adder
91.003
970273AG2-179 GEN
Solar/Wind Harmer
3.615
960741AF2-365 GEN
Solar/Wind Harmer
3.707
339250AF1-203 GEN
Solar/Wind Harmer
0.438
971155AH1-034 GEN
Solar/Wind Harmer
7.11
962251AG1-071 GEN
Solar/Wind Harmer
3.79
972103AH1-617 GEN
Solar/Wind Harmer
10.272
253338AC1-165 GEN
Solar/Wind Helper
0.943
253333AC1-068 GEN
Solar/Wind Helper
0.977
253406AD2-031_GEN
Solar/Wind Helper
0.781
253415AE1-040 GEN
Solar/Wind Helper
0.462
950041AG9-017
External Queue
18.620590209960938
950051AG9-018
External Queue
18.44816780090332
CPLELTFEXP_CPLE->PJM
CLTF
0.92
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.381
LAGNLTFEXP_LAGN->PJM
CLTF
5.883
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.08
TVALTFEXP_TVA->PJM
CLTF
3.489
NYPJM->LTFIMP_NY
CLTF
0.611
LGEELTFEXP_LGEE->PJM
CLTF
4.827
WECLTFEXP_WEC->PJM
CLTF
0.485
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.31
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.496
MECLTFEXP_MEC->PJM
CLTF
3.082
SIGELTFEXP_SIGE->PJM
CLTF
0.231

Details for 7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P4_1487_RED BANK_SRT-A


Base Case Flowgate

Area:DAY/EKPC
Facility Description:
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
Contingency Name:
DEOK_P4_1487_RED BANK_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.23 %
Rating:1532.0 MVA
Rating Type:B
MVA to Mitigate:1765.38
MW Contribution:6.3
Bus #Bus NameTypeMW Contribution
25197008MELDL1
50/50
0.735
972163AH1-664 GEN
Solar/Wind Harmer
35.835
972165AH1-665 GEN
Solar/Wind Harmer
28.668
339243AC2-075 GEN1
Solar/Wind Harmer
1.122
3429211JKCT 2G
Adder
26.85
339211AE2-254 GEN
Solar/Wind Harmer
2.217
965401AG1-405 GEN
Solar/Wind Harmer
7.248
965411AG1-406 GEN
Solar/Wind Harmer
3.253
970455AG2-298 GEN
Solar/Wind Harmer
6.011
962211AG1-066 GEN
Solar/Wind Harmer
1.843
970281AG2-184 GEN
Solar/Wind Harmer
10.786
972143AH1-644 GEN
Solar/Wind Harmer
5.136
945631AF1-228 GEN
Solar/Wind Helper
0.946
3429601SPURLK2G
50/50
15.432
972043AH1-570 GEN
Solar/Wind Harmer
6.098
972045AH1-571 GEN
Solar/Wind Harmer
4.878
971125AH1-004 GEN
Solar/Wind Harmer
9.7
970107AG2-081 GEN
Solar/Wind Harmer
7.275
339221AD2-048_GEN
Solar/Wind Harmer
3.655
960161AF2-307 GEN
Solar/Wind Harmer
15.078
942891AE2-308 GEN
Solar/Wind Harmer
21.334
970235AG2-159 GEN
Solar/Wind Harmer
4.075
970235AG2-159 GEN
Solar/Wind Harmer
2.488
339231AF1-038_GEN
Solar/Wind Harmer
1.699
971081AG2-670 GEN
Solar/Wind Harmer
6.826
970653AG2-424 GEN
Solar/Wind Harmer
4.208
970653AG2-424 GEN
Solar/Wind Harmer
1.521
339236AF1-050_GEN
Solar/Wind Harmer
1.504
964571AG1-320 GEN
Solar/Wind Harmer
6.672
966021AG1-471 GEN
Solar/Wind Harmer
4.296
971485AH1-239 GEN
Solar/Wind Harmer
6.303
270186AC1-089 GEN
Solar/Wind Harmer
4.703
339255AE2-071 GEN
Solar/Wind Harmer
0.767
964781AG1-341 GEN
Solar/Wind Harmer
7.383
253394AE2-221_GEN
Solar/Wind Helper
2.6
253398AE2-221_GEN2
Solar/Wind Helper
2.6
25183208HLCRTG
Solar/Wind Helper
2.511
252509AD1-136 GEN
Solar/Wind Helper
0.125
270518AE2-148 GEN
Solar/Wind Helper
5.924
3429661SPURLK4G
50/50
8.094
3429571SPURLK1G
50/50
8.131
25197208MELDL3
50/50
0.739
25196808ZIMRHP
50/50
235.666
945681AF1-233 GEN
Solar/Wind Harmer
69.568
339216AC1-074 GEN
Solar/Wind Harmer
4.143
943111AE2-339 GEN
Solar/Wind Harmer
2.164
3429421JKCT 10G
Adder
20.324
3429241JKCT 3G
Adder
27.202
971821AH1-427 GEN
Solar/Wind Harmer
14.224
971565AH1-281 GEN
Solar/Wind Harmer
1.965
339241AF1-083 GEN
Solar/Wind Harmer
1.573
970273AG2-179 GEN
Solar/Wind Harmer
2.263
971315AH1-136 GEN
Solar/Wind Harmer
1.759
964901AG1-354 GEN
Solar/Wind Harmer
11.595
962241AG1-070 GEN
Solar/Wind Harmer
3.101
253343AC1-166 GEN
Solar/Wind Helper
0.943
253325AC1-069 GEN
Solar/Wind Helper
0.977
252507AC2-088 GEN
Solar/Wind Helper
0.878
3429631SPURLK3G
50/50
8.094
25197108MELDL2
50/50
0.746
958171AF2-111 GEN
Solar/Wind Harmer
106.876
972167AH1-666 GEN
Solar/Wind Harmer
29.728
3429391JKCT 9G
Adder
20.324
970093AG2-073 GEN
Solar/Wind Harmer
19.701
966571AG1-526 GEN
Solar/Wind Harmer
36.35
972273AH1-721 GEN
Adder
91.003
970273AG2-179 GEN
Solar/Wind Harmer
3.615
960741AF2-365 GEN
Solar/Wind Harmer
3.707
339250AF1-203 GEN
Solar/Wind Harmer
0.438
971155AH1-034 GEN
Solar/Wind Harmer
7.11
962251AG1-071 GEN
Solar/Wind Harmer
3.79
972103AH1-617 GEN
Solar/Wind Harmer
10.273
253338AC1-165 GEN
Solar/Wind Helper
0.943
253333AC1-068 GEN
Solar/Wind Helper
0.977
253406AD2-031_GEN
Solar/Wind Helper
0.781
253415AE1-040 GEN
Solar/Wind Helper
0.462
950041AG9-017
External Queue
18.620628356933594
950051AG9-018
External Queue
18.448036193847656
CPLELTFEXP_CPLE->PJM
CLTF
0.92
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.378
LAGNLTFEXP_LAGN->PJM
CLTF
5.883
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.081
TVALTFEXP_TVA->PJM
CLTF
3.489
NYPJM->LTFIMP_NY
CLTF
0.611
LGEELTFEXP_LGEE->PJM
CLTF
4.827
WECLTFEXP_WEC->PJM
CLTF
0.485
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.306
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.496
MECLTFEXP_MEC->PJM
CLTF
3.081
SIGELTFEXP_SIGE->PJM
CLTF
0.231

Details for 7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P_CIRCUIT1883&4545REDBANKSILGRVZIMMER_SRT-A


Base Case Flowgate

Area:DAY/EKPC
Facility Description:
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
Contingency Name:
DEOK_P_CIRCUIT1883&4545REDBANKSILGRVZIMMER_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:115.19 %
Rating:1532.0 MVA
Rating Type:B
MVA to Mitigate:1764.77
MW Contribution:6.3
Bus #Bus NameTypeMW Contribution
25197008MELDL1
50/50
0.735
972163AH1-664 GEN
Solar/Wind Harmer
35.838
972165AH1-665 GEN
Solar/Wind Harmer
28.67
339243AC2-075 GEN1
Solar/Wind Harmer
1.122
3429211JKCT 2G
Adder
26.853
339211AE2-254 GEN
Solar/Wind Harmer
2.218
965401AG1-405 GEN
Solar/Wind Harmer
7.249
965411AG1-406 GEN
Solar/Wind Harmer
3.254
970455AG2-298 GEN
Solar/Wind Harmer
6.013
962211AG1-066 GEN
Solar/Wind Harmer
1.843
3429661SPURLK4G
50/50
8.094
3429571SPURLK1G
50/50
8.131
25197208MELDL3
50/50
0.74
25196808ZIMRHP
50/50
235.719
945681AF1-233 GEN
Solar/Wind Harmer
69.574
339216AC1-074 GEN
Solar/Wind Harmer
4.144
943111AE2-339 GEN
Solar/Wind Harmer
2.165
3429421JKCT 10G
Adder
20.327
3429241JKCT 3G
Adder
27.206
971821AH1-427 GEN
Solar/Wind Harmer
14.227
971565AH1-281 GEN
Solar/Wind Harmer
1.966
339241AF1-083 GEN
Solar/Wind Harmer
1.573
970273AG2-179 GEN
Solar/Wind Harmer
2.264
971315AH1-136 GEN
Solar/Wind Harmer
1.759
964901AG1-354 GEN
Solar/Wind Harmer
11.598
962241AG1-070 GEN
Solar/Wind Harmer
3.102
253343AC1-166 GEN
Solar/Wind Helper
0.943
253325AC1-069 GEN
Solar/Wind Helper
0.977
252507AC2-088 GEN
Solar/Wind Helper
0.886
970281AG2-184 GEN
Solar/Wind Harmer
10.786
972143AH1-644 GEN
Solar/Wind Harmer
5.136
945631AF1-228 GEN
Solar/Wind Helper
0.946
3429601SPURLK2G
50/50
15.433
972043AH1-570 GEN
Solar/Wind Harmer
6.099
972045AH1-571 GEN
Solar/Wind Harmer
4.879
971125AH1-004 GEN
Solar/Wind Harmer
9.702
970107AG2-081 GEN
Solar/Wind Harmer
7.276
339221AD2-048_GEN
Solar/Wind Harmer
3.656
960161AF2-307 GEN
Solar/Wind Harmer
15.079
942891AE2-308 GEN
Solar/Wind Harmer
21.337
970235AG2-159 GEN
Solar/Wind Harmer
4.079
970235AG2-159 GEN
Solar/Wind Harmer
2.49
339231AF1-038_GEN
Solar/Wind Harmer
1.699
971081AG2-670 GEN
Solar/Wind Harmer
6.828
970653AG2-424 GEN
Solar/Wind Harmer
4.209
970653AG2-424 GEN
Solar/Wind Harmer
1.521
339236AF1-050_GEN
Solar/Wind Harmer
1.505
964571AG1-320 GEN
Solar/Wind Harmer
6.674
966021AG1-471 GEN
Solar/Wind Harmer
4.297
971485AH1-239 GEN
Solar/Wind Harmer
6.305
270186AC1-089 GEN
Solar/Wind Harmer
4.704
339255AE2-071 GEN
Solar/Wind Harmer
0.767
964781AG1-341 GEN
Solar/Wind Harmer
7.385
253394AE2-221_GEN
Solar/Wind Helper
2.6
253398AE2-221_GEN2
Solar/Wind Helper
2.6
25183208HLCRTG
Solar/Wind Helper
2.512
252509AD1-136 GEN
Solar/Wind Helper
0.127
270518AE2-148 GEN
Solar/Wind Helper
5.922
3429631SPURLK3G
50/50
8.094
25197108MELDL2
50/50
0.746
958171AF2-111 GEN
Solar/Wind Harmer
106.883
972167AH1-666 GEN
Solar/Wind Harmer
29.73
3429391JKCT 9G
Adder
20.327
970093AG2-073 GEN
Solar/Wind Harmer
19.704
966571AG1-526 GEN
Solar/Wind Harmer
36.357
972273AH1-721 GEN
Adder
91.022
970273AG2-179 GEN
Solar/Wind Harmer
3.616
960741AF2-365 GEN
Solar/Wind Harmer
3.709
339250AF1-203 GEN
Solar/Wind Harmer
0.438
971155AH1-034 GEN
Solar/Wind Harmer
7.112
962251AG1-071 GEN
Solar/Wind Harmer
3.791
972103AH1-617 GEN
Solar/Wind Harmer
10.273
253338AC1-165 GEN
Solar/Wind Helper
0.943
253333AC1-068 GEN
Solar/Wind Helper
0.977
253406AD2-031_GEN
Solar/Wind Helper
0.781
253415AE1-040 GEN
Solar/Wind Helper
0.462
950041AG9-017
External Queue
18.62034034729004
950051AG9-018
External Queue
18.447389602661133
CPLELTFEXP_CPLE->PJM
CLTF
0.92
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.402
LAGNLTFEXP_LAGN->PJM
CLTF
5.885
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.08
TVALTFEXP_TVA->PJM
CLTF
3.49
NYPJM->LTFIMP_NY
CLTF
0.611
LGEELTFEXP_LGEE->PJM
CLTF
4.829
WECLTFEXP_WEC->PJM
CLTF
0.485
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.324
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.502
MECLTFEXP_MEC->PJM
CLTF
3.084
SIGELTFEXP_SIGE->PJM
CLTF
0.231

Details for 7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2.2_SILVER GROVE 345 BUS_SRT-A


Base Case Flowgate

Area:DAY/EKPC
Facility Description:
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
Contingency Name:
DEOK_P2.2_SILVER GROVE 345 BUS_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:115.16 %
Rating:1532.0 MVA
Rating Type:B
MVA to Mitigate:1764.32
MW Contribution:6.3
Bus #Bus NameTypeMW Contribution
25197008MELDL1
50/50
0.735
972163AH1-664 GEN
Solar/Wind Harmer
35.834
972165AH1-665 GEN
Solar/Wind Harmer
28.668
339243AC2-075 GEN1
Solar/Wind Harmer
1.122
3429211JKCT 2G
Adder
26.85
339211AE2-254 GEN
Solar/Wind Harmer
2.217
965401AG1-405 GEN
Solar/Wind Harmer
7.249
965411AG1-406 GEN
Solar/Wind Harmer
3.253
970455AG2-298 GEN
Solar/Wind Harmer
6.012
962211AG1-066 GEN
Solar/Wind Harmer
1.843
970281AG2-184 GEN
Solar/Wind Harmer
10.787
972143AH1-644 GEN
Solar/Wind Harmer
5.137
945631AF1-228 GEN
Solar/Wind Helper
0.946
3429601SPURLK2G
50/50
15.432
972043AH1-570 GEN
Solar/Wind Harmer
6.098
972045AH1-571 GEN
Solar/Wind Harmer
4.878
971125AH1-004 GEN
Solar/Wind Harmer
9.701
970107AG2-081 GEN
Solar/Wind Harmer
7.275
339221AD2-048_GEN
Solar/Wind Harmer
3.655
960161AF2-307 GEN
Solar/Wind Harmer
15.078
942891AE2-308 GEN
Solar/Wind Harmer
21.334
970235AG2-159 GEN
Solar/Wind Harmer
4.078
970235AG2-159 GEN
Solar/Wind Harmer
2.489
339231AF1-038_GEN
Solar/Wind Harmer
1.699
971081AG2-670 GEN
Solar/Wind Harmer
6.827
970653AG2-424 GEN
Solar/Wind Harmer
4.208
970653AG2-424 GEN
Solar/Wind Harmer
1.521
339236AF1-050_GEN
Solar/Wind Harmer
1.504
964571AG1-320 GEN
Solar/Wind Harmer
6.673
966021AG1-471 GEN
Solar/Wind Harmer
4.296
971485AH1-239 GEN
Solar/Wind Harmer
6.304
270186AC1-089 GEN
Solar/Wind Harmer
4.703
339255AE2-071 GEN
Solar/Wind Harmer
0.767
964781AG1-341 GEN
Solar/Wind Harmer
7.384
253394AE2-221_GEN
Solar/Wind Helper
2.601
253398AE2-221_GEN2
Solar/Wind Helper
2.601
25183208HLCRTG
Solar/Wind Helper
2.511
252509AD1-136 GEN
Solar/Wind Helper
0.125
270518AE2-148 GEN
Solar/Wind Helper
5.925
3429661SPURLK4G
50/50
8.093
3429571SPURLK1G
50/50
8.131
25197208MELDL3
50/50
0.739
25196808ZIMRHP
50/50
235.624
945681AF1-233 GEN
Solar/Wind Harmer
69.568
339216AC1-074 GEN
Solar/Wind Harmer
4.144
943111AE2-339 GEN
Solar/Wind Harmer
2.164
3429421JKCT 10G
Adder
20.324
3429241JKCT 3G
Adder
27.203
971821AH1-427 GEN
Solar/Wind Harmer
14.225
971565AH1-281 GEN
Solar/Wind Harmer
1.965
339241AF1-083 GEN
Solar/Wind Harmer
1.573
970273AG2-179 GEN
Solar/Wind Harmer
2.263
971315AH1-136 GEN
Solar/Wind Harmer
1.759
964901AG1-354 GEN
Solar/Wind Harmer
11.596
962241AG1-070 GEN
Solar/Wind Harmer
3.101
253343AC1-166 GEN
Solar/Wind Helper
0.943
253325AC1-069 GEN
Solar/Wind Helper
0.977
252507AC2-088 GEN
Solar/Wind Helper
0.876
3429631SPURLK3G
50/50
8.093
25197108MELDL2
50/50
0.746
958171AF2-111 GEN
Solar/Wind Harmer
106.873
972167AH1-666 GEN
Solar/Wind Harmer
29.728
3429391JKCT 9G
Adder
20.324
970093AG2-073 GEN
Solar/Wind Harmer
19.702
966571AG1-526 GEN
Solar/Wind Harmer
36.352
972273AH1-721 GEN
Adder
91.009
970273AG2-179 GEN
Solar/Wind Harmer
3.615
960741AF2-365 GEN
Solar/Wind Harmer
3.708
339250AF1-203 GEN
Solar/Wind Harmer
0.438
971155AH1-034 GEN
Solar/Wind Harmer
7.111
962251AG1-071 GEN
Solar/Wind Harmer
3.791
972103AH1-617 GEN
Solar/Wind Harmer
10.274
253338AC1-165 GEN
Solar/Wind Helper
0.943
253333AC1-068 GEN
Solar/Wind Helper
0.977
253406AD2-031_GEN
Solar/Wind Helper
0.781
253415AE1-040 GEN
Solar/Wind Helper
0.462
950041AG9-017
External Queue
18.61962890625
950051AG9-018
External Queue
18.446699142456055
CPLELTFEXP_CPLE->PJM
CLTF
0.921
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.382
LAGNLTFEXP_LAGN->PJM
CLTF
5.884
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.082
TVALTFEXP_TVA->PJM
CLTF
3.489
NYPJM->LTFIMP_NY
CLTF
0.611
LGEELTFEXP_LGEE->PJM
CLTF
4.828
WECLTFEXP_WEC->PJM
CLTF
0.485
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.306
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.499
MECLTFEXP_MEC->PJM
CLTF
3.081
SIGELTFEXP_SIGE->PJM
CLTF
0.231

Details for 7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DAY/EKPC
Facility Description:
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.67 %
Rating:1240.0 MVA
Rating Type:A
MVA to Mitigate:1421.95
MW Contribution:4.25
Bus #Bus NameTypeMW Contribution
3429631SPURLK3G
50/50
7.485
25197108MELDL2
50/50
0.555
958171AF2-111 GEN
Solar/Wind Harmer
69.07
972167AH1-666 GEN
Solar/Wind Harmer
19.252
3429391JKCT 9G
Adder
19.034
970093AG2-073 GEN
Solar/Wind Harmer
12.938
966571AG1-526 GEN
Solar/Wind Harmer
24.04
972273AH1-721 GEN
Adder
86.897
3429601SPURLK2G
50/50
14.272
972043AH1-570 GEN
Solar/Wind Harmer
4.16
972045AH1-571 GEN
Solar/Wind Harmer
3.333
971125AH1-004 GEN
Solar/Wind Harmer
6.363
970107AG2-081 GEN
Solar/Wind Harmer
4.772
339221AD2-048_GEN
Solar/Wind Harmer
0.009
960161AF2-307 GEN
Solar/Wind Harmer
10.094
942891AE2-308 GEN
Solar/Wind Harmer
13.99
970235AG2-159 GEN
Solar/Wind Harmer
4.442
970235AG2-159 GEN
Solar/Wind Harmer
2.549
3429661SPURLK4G
50/50
7.485
3429571SPURLK1G
50/50
7.538
25197208MELDL3
50/50
0.55
945681AF1-233 GEN
Solar/Wind Harmer
45.056
339216AC1-074 GEN
Solar/Wind Harmer
0.445
3429421JKCT 10G
Adder
19.034
3429241JKCT 3G
Adder
25.509
25196808ZIMRHP
Adder
146.521
971821AH1-427 GEN
Solar/Wind Harmer
9.447
971565AH1-281 GEN
Solar/Wind Harmer
1.338
970273AG2-179 GEN
Solar/Wind Harmer
2.177
971315AH1-136 GEN
Solar/Wind Harmer
1.141
964901AG1-354 GEN
Solar/Wind Harmer
7.882
962241AG1-070 GEN
Solar/Wind Harmer
2.566
25196008MFTGT1
Adder
0.622
253343AC1-166 GEN
Solar/Wind Helper
1.014
253325AC1-069 GEN
Solar/Wind Helper
1.051
25197008MELDL1
50/50
0.547
972163AH1-664 GEN
Solar/Wind Harmer
25.851
972165AH1-665 GEN
Solar/Wind Harmer
20.704
339243AC2-075 GEN1
Solar/Wind Harmer
0.003
3429211JKCT 2G
Adder
25.178
339211AE2-254 GEN
Solar/Wind Harmer
0.004
965401AG1-405 GEN
Solar/Wind Harmer
4.808
965411AG1-406 GEN
Solar/Wind Harmer
3.093
970455AG2-298 GEN
Solar/Wind Harmer
4.531
970281AG2-184 GEN
Solar/Wind Harmer
7.014
972143AH1-644 GEN
Solar/Wind Harmer
3.618
25196108MFTGT2
Adder
0.686
25196108MFTGT2
Adder
0.637
945631AF1-228 GEN
Solar/Wind Helper
0.994
270340AC2-060 GEN
Solar/Wind Helper
0.992
270520AE2-214 GEN
Solar/Wind Helper
2.234
971081AG2-670 GEN
Solar/Wind Harmer
4.612
970653AG2-424 GEN
Solar/Wind Harmer
2.868
970653AG2-424 GEN
Solar/Wind Harmer
1.486
964571AG1-320 GEN
Solar/Wind Harmer
5.107
966021AG1-471 GEN
Solar/Wind Harmer
2.893
971485AH1-239 GEN
Solar/Wind Harmer
4.249
270186AC1-089 GEN
Solar/Wind Harmer
0.003
339255AE2-071 GEN
Solar/Wind Harmer
-0.081
964781AG1-341 GEN
Solar/Wind Harmer
5.04
253394AE2-221_GEN
Solar/Wind Helper
2.805
253398AE2-221_GEN2
Solar/Wind Helper
2.805
25183208HLCRTG
Solar/Wind Helper
2.661
270518AE2-148 GEN
Solar/Wind Helper
6.187
252509AD1-136 GEN
Solar/Wind Helper
0.107
946101AF1-275 GEN
Solar/Wind Helper
0.28
252507AC2-088 GEN
Solar/Wind Helper
0.746
970273AG2-179 GEN
Solar/Wind Harmer
3.732
960741AF2-365 GEN
Solar/Wind Harmer
2.535
339250AF1-203 GEN
Solar/Wind Harmer
0.001
971155AH1-034 GEN
Solar/Wind Harmer
5.654
962251AG1-071 GEN
Solar/Wind Harmer
2.943
972103AH1-617 GEN
Solar/Wind Harmer
6.68
25196008MFTGT1
Adder
0.603
253338AC1-165 GEN
Solar/Wind Helper
1.014
253333AC1-068 GEN
Solar/Wind Helper
1.051
253406AD2-031_GEN
Solar/Wind Helper
0.849
253415AE1-040 GEN
Solar/Wind Helper
0.499
950041AG9-017
External Queue
16.814743041992188
950051AG9-018
External Queue
16.609764099121094
CPLELTFEXP_CPLE->PJM
CLTF
0.85
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.046
LAGNLTFEXP_LAGN->PJM
CLTF
5.94
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.879
TVALTFEXP_TVA->PJM
CLTF
3.468
NYPJM->LTFIMP_NY
CLTF
0.637
LGEELTFEXP_LGEE->PJM
CLTF
4.904
WECLTFEXP_WEC->PJM
CLTF
0.565
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.941
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.508
MECLTFEXP_MEC->PJM
CLTF
3.38
SIGELTFEXP_SIGE->PJM
CLTF
0.241

Details for 7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o EKPC_P2-2_MELD-SPUR 345_SRT-A


Base Case Flowgate

Area:DAY/EKPC
Facility Description:
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_MELD-SPUR 345_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:114.33 %
Rating:1532.0 MVA
Rating Type:B
MVA to Mitigate:1751.58
MW Contribution:7.11
Bus #Bus NameTypeMW Contribution
3429601SPURLK2G
50/50
18.64
972043AH1-570 GEN
Solar/Wind Harmer
7.203
972045AH1-571 GEN
Solar/Wind Harmer
5.763
971125AH1-004 GEN
Solar/Wind Harmer
11.455
970107AG2-081 GEN
Solar/Wind Harmer
8.591
960161AF2-307 GEN
Solar/Wind Harmer
17.988
339221AD2-048_GEN
Solar/Wind Harmer
4.301
942891AE2-308 GEN
Solar/Wind Harmer
25.169
339231AF1-038_GEN
Solar/Wind Harmer
1.932
970235AG2-159 GEN
Solar/Wind Harmer
4.251
970235AG2-159 GEN
Solar/Wind Harmer
2.595
971081AG2-670 GEN
Solar/Wind Harmer
7.662
970653AG2-424 GEN
Solar/Wind Harmer
4.644
970653AG2-424 GEN
Solar/Wind Harmer
1.679
339236AF1-050_GEN
Solar/Wind Harmer
1.678
270186AC1-089 GEN
Solar/Wind Harmer
5.494
966021AG1-471 GEN
Solar/Wind Harmer
4.857
971485AH1-239 GEN
Solar/Wind Harmer
7.111
964571AG1-320 GEN
Solar/Wind Harmer
7.25
339255AE2-071 GEN
Solar/Wind Harmer
0.849
964781AG1-341 GEN
Solar/Wind Harmer
8.139
3429661SPURLK4G
50/50
9.776
3429571SPURLK1G
50/50
9.792
945681AF1-233 GEN
Solar/Wind Harmer
83.633
339216AC1-074 GEN
Solar/Wind Harmer
4.873
943111AE2-339 GEN
Solar/Wind Harmer
2.561
3429421JKCT 10G
Adder
24.103
3429241JKCT 3G
Adder
32.202
971821AH1-427 GEN
Solar/Wind Harmer
16.445
971565AH1-281 GEN
Solar/Wind Harmer
2.174
339241AF1-083 GEN
Solar/Wind Harmer
1.77
971315AH1-136 GEN
Solar/Wind Harmer
2.127
970273AG2-179 GEN
Solar/Wind Harmer
2.572
964901AG1-354 GEN
Solar/Wind Harmer
12.878
962241AG1-070 GEN
Solar/Wind Harmer
3.411
971687AH1-348 GEN
Solar/Wind Harmer
0.46
972163AH1-664 GEN
Solar/Wind Harmer
43.05
972165AH1-665 GEN
Solar/Wind Harmer
34.44
339243AC2-075 GEN1
Solar/Wind Harmer
1.319
3429211JKCT 2G
Adder
31.785
339211AE2-254 GEN
Solar/Wind Harmer
2.566
965401AG1-405 GEN
Solar/Wind Harmer
8.401
965411AG1-406 GEN
Solar/Wind Harmer
3.77
970455AG2-298 GEN
Solar/Wind Harmer
6.693
962211AG1-066 GEN
Solar/Wind Harmer
2.199
970281AG2-184 GEN
Solar/Wind Harmer
13.084
972143AH1-644 GEN
Solar/Wind Harmer
6.23
945631AF1-228 GEN
Solar/Wind Helper
0.914
253343AC1-166 GEN
Solar/Wind Helper
0.792
253325AC1-069 GEN
Solar/Wind Helper
0.821
252507AC2-088 GEN
Solar/Wind Helper
0.99
3429631SPURLK3G
50/50
9.776
958171AF2-111 GEN
Solar/Wind Harmer
128.804
972167AH1-666 GEN
Solar/Wind Harmer
35.741
3429391JKCT 9G
Adder
24.103
970093AG2-073 GEN
Solar/Wind Harmer
23.192
966571AG1-526 GEN
Solar/Wind Harmer
42.302
972273AH1-721 GEN
Adder
104.752
970273AG2-179 GEN
Solar/Wind Harmer
4.108
960741AF2-365 GEN
Solar/Wind Harmer
4.073
339250AF1-203 GEN
Solar/Wind Harmer
0.485
971155AH1-034 GEN
Solar/Wind Harmer
7.86
962251AG1-071 GEN
Solar/Wind Harmer
4.17
972103AH1-617 GEN
Solar/Wind Harmer
12.461
971461AH1-227 GEN
Solar/Wind Harmer
2.276
971225AH1-072 GEN
Solar/Wind Harmer
0.888
971227AH1-073 GEN
Solar/Wind Harmer
0.888
253394AE2-221_GEN
Solar/Wind Helper
2.179
253398AE2-221_GEN2
Solar/Wind Helper
2.179
25183208HLCRTG
Solar/Wind Helper
2.409
252509AD1-136 GEN
Solar/Wind Helper
0.141
270518AE2-148 GEN
Solar/Wind Helper
6.059
253338AC1-165 GEN
Solar/Wind Helper
0.792
253333AC1-068 GEN
Solar/Wind Helper
0.821
253406AD2-031_GEN
Solar/Wind Helper
0.679
253415AE1-040 GEN
Solar/Wind Helper
0.403
950041AG9-017
External Queue
23.331375122070312
950011AG9-010
External Queue
6.113064289093018
950051AG9-018
External Queue
23.248964309692383
CPLELTFEXP_CPLE->PJM
CLTF
1.207
CBM West 2LTFEXP_CBM-W2->PJM
CBM
36.92
LAGNLTFEXP_LAGN->PJM
CLTF
6.13
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.96
TVALTFEXP_TVA->PJM
CLTF
3.754
NYPJM->LTFIMP_NY
CLTF
0.539
LGEELTFEXP_LGEE->PJM
CLTF
4.945
WECLTFEXP_WEC->PJM
CLTF
0.331
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.097
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.429
MECLTFEXP_MEC->PJM
CLTF
2.587
SIGELTFEXP_SIGE->PJM
CLTF
0.22

Details for 7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P1_ZIMMER-MELDAHL 34576_SRT-A


Base Case Flowgate

Area:DAY/EKPC
Facility Description:
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
Contingency Name:
DEOK_P1_ZIMMER-MELDAHL 34576_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.32 %
Rating:1532.0 MVA
Rating Type:B
MVA to Mitigate:1613.52
MW Contribution:4.94
Bus #Bus NameTypeMW Contribution
3429601SPURLK2G
50/50
18.629
972043AH1-570 GEN
Solar/Wind Harmer
5.22
972045AH1-571 GEN
Solar/Wind Harmer
4.183
971125AH1-004 GEN
Solar/Wind Harmer
7.982
970107AG2-081 GEN
Solar/Wind Harmer
5.987
960161AF2-307 GEN
Solar/Wind Harmer
12.886
339221AD2-048_GEN
Solar/Wind Harmer
0.012
942891AE2-308 GEN
Solar/Wind Harmer
17.536
970235AG2-159 GEN
Solar/Wind Harmer
4.508
970235AG2-159 GEN
Solar/Wind Harmer
2.587
971081AG2-670 GEN
Solar/Wind Harmer
5.327
970653AG2-424 GEN
Solar/Wind Harmer
3.229
970653AG2-424 GEN
Solar/Wind Harmer
1.673
270186AC1-089 GEN
Solar/Wind Harmer
0.004
966021AG1-471 GEN
Solar/Wind Harmer
3.376
971485AH1-239 GEN
Solar/Wind Harmer
4.942
964571AG1-320 GEN
Solar/Wind Harmer
5.612
339255AE2-071 GEN
Solar/Wind Harmer
-0.091
964781AG1-341 GEN
Solar/Wind Harmer
5.653
971225AH1-072 GEN
Solar/Wind Harmer
0.614
971227AH1-073 GEN
Solar/Wind Harmer
0.614
253394AE2-221_GEN
Solar/Wind Helper
2.185
253398AE2-221_GEN2
Solar/Wind Helper
2.185
25183208HLCRTG
Solar/Wind Helper
2.418
252509AD1-136 GEN
Solar/Wind Helper
0.142
270518AE2-148 GEN
Solar/Wind Helper
6.102
3429661SPURLK4G
50/50
9.77
25197208MELDL3
50/50
1.274
3429571SPURLK1G
50/50
9.786
945681AF1-233 GEN
Solar/Wind Harmer
58.303
339216AC1-074 GEN
Solar/Wind Harmer
0.553
3429421JKCT 10G
Adder
24.075
3429241JKCT 3G
Adder
32.161
971821AH1-427 GEN
Solar/Wind Harmer
11.449
971565AH1-281 GEN
Solar/Wind Harmer
1.512
971315AH1-136 GEN
Solar/Wind Harmer
1.479
970273AG2-179 GEN
Solar/Wind Harmer
2.564
964901AG1-354 GEN
Solar/Wind Harmer
8.949
962241AG1-070 GEN
Solar/Wind Harmer
2.87
971687AH1-348 GEN
Solar/Wind Harmer
0.319
253343AC1-166 GEN
Solar/Wind Helper
0.796
253325AC1-069 GEN
Solar/Wind Helper
0.825
252507AC2-088 GEN
Solar/Wind Helper
0.996
25197008MELDL1
50/50
1.267
972163AH1-664 GEN
Solar/Wind Harmer
33.413
972165AH1-665 GEN
Solar/Wind Harmer
26.76
339243AC2-075 GEN1
Solar/Wind Harmer
0.003
3429211JKCT 2G
Adder
31.745
339211AE2-254 GEN
Solar/Wind Harmer
0.005
965401AG1-405 GEN
Solar/Wind Harmer
5.847
965411AG1-406 GEN
Solar/Wind Harmer
3.762
970455AG2-298 GEN
Solar/Wind Harmer
5.173
970281AG2-184 GEN
Solar/Wind Harmer
9.078
972143AH1-644 GEN
Solar/Wind Harmer
4.683
945631AF1-228 GEN
Solar/Wind Helper
0.92
3429631SPURLK3G
50/50
9.77
25197108MELDL2
50/50
1.285
958171AF2-111 GEN
Solar/Wind Harmer
89.804
972167AH1-666 GEN
Solar/Wind Harmer
24.916
3429391JKCT 9G
Adder
24.075
970093AG2-073 GEN
Solar/Wind Harmer
16.156
966571AG1-526 GEN
Solar/Wind Harmer
29.46
972273AH1-721 GEN
Adder
104.468
970273AG2-179 GEN
Solar/Wind Harmer
4.395
960741AF2-365 GEN
Solar/Wind Harmer
2.829
339250AF1-203 GEN
Solar/Wind Harmer
0.001
971155AH1-034 GEN
Solar/Wind Harmer
6.37
962251AG1-071 GEN
Solar/Wind Harmer
3.291
972103AH1-617 GEN
Solar/Wind Harmer
8.646
971461AH1-227 GEN
Solar/Wind Harmer
1.576
253338AC1-165 GEN
Solar/Wind Helper
0.796
253333AC1-068 GEN
Solar/Wind Helper
0.825
253406AD2-031_GEN
Solar/Wind Helper
0.683
253415AE1-040 GEN
Solar/Wind Helper
0.407
950041AG9-017
External Queue
23.331375122070312
950011AG9-010
External Queue
6.113064289093018
950051AG9-018
External Queue
23.248964309692383
CPLELTFEXP_CPLE->PJM
CLTF
1.169
CBM West 2LTFEXP_CBM-W2->PJM
CBM
36.457
LAGNLTFEXP_LAGN->PJM
CLTF
6.06
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.856
TVALTFEXP_TVA->PJM
CLTF
3.719
NYPJM->LTFIMP_NY
CLTF
0.561
LGEELTFEXP_LGEE->PJM
CLTF
4.921
WECLTFEXP_WEC->PJM
CLTF
0.318
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.596
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.299
MECLTFEXP_MEC->PJM
CLTF
2.529
SIGELTFEXP_SIGE->PJM
CLTF
0.218

Details for 7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P1_RED BANK-SILVER GROVE-ZIMMER 4545_SRT-A


Base Case Flowgate

Area:DAY/EKPC
Facility Description:
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
Contingency Name:
DEOK_P1_RED BANK-SILVER GROVE-ZIMMER 4545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.95 %
Rating:1532.0 MVA
Rating Type:B
MVA to Mitigate:1592.57
MW Contribution:4.4
Bus #Bus NameTypeMW Contribution
3429601SPURLK2G
50/50
15.432
972043AH1-570 GEN
Solar/Wind Harmer
4.425
972045AH1-571 GEN
Solar/Wind Harmer
3.545
971125AH1-004 GEN
Solar/Wind Harmer
6.768
970107AG2-081 GEN
Solar/Wind Harmer
5.076
339221AD2-048_GEN
Solar/Wind Harmer
0.01
960161AF2-307 GEN
Solar/Wind Harmer
10.815
942891AE2-308 GEN
Solar/Wind Harmer
14.884
970235AG2-159 GEN
Solar/Wind Harmer
4.339
970235AG2-159 GEN
Solar/Wind Harmer
2.489
971081AG2-670 GEN
Solar/Wind Harmer
4.763
970653AG2-424 GEN
Solar/Wind Harmer
2.936
970653AG2-424 GEN
Solar/Wind Harmer
1.521
964571AG1-320 GEN
Solar/Wind Harmer
5.185
966021AG1-471 GEN
Solar/Wind Harmer
2.997
971485AH1-239 GEN
Solar/Wind Harmer
4.398
270186AC1-089 GEN
Solar/Wind Harmer
0.003
339255AE2-071 GEN
Solar/Wind Harmer
-0.083
964781AG1-341 GEN
Solar/Wind Harmer
5.152
253394AE2-221_GEN
Solar/Wind Helper
2.601
253398AE2-221_GEN2
Solar/Wind Helper
2.601
25183208HLCRTG
Solar/Wind Helper
2.511
252509AD1-136 GEN
Solar/Wind Helper
0.125
270518AE2-148 GEN
Solar/Wind Helper
5.925
3429661SPURLK4G
50/50
8.093
3429571SPURLK1G
50/50
8.131
25197208MELDL3
50/50
0.739
25196808ZIMRHP
50/50
235.624
945681AF1-233 GEN
Solar/Wind Harmer
48.536
339216AC1-074 GEN
Solar/Wind Harmer
0.471
3429421JKCT 10G
Adder
20.324
3429241JKCT 3G
Adder
27.203
971821AH1-427 GEN
Solar/Wind Harmer
9.925
971565AH1-281 GEN
Solar/Wind Harmer
1.371
970273AG2-179 GEN
Solar/Wind Harmer
2.263
971315AH1-136 GEN
Solar/Wind Harmer
1.227
964901AG1-354 GEN
Solar/Wind Harmer
8.09
962241AG1-070 GEN
Solar/Wind Harmer
2.621
253343AC1-166 GEN
Solar/Wind Helper
0.943
253325AC1-069 GEN
Solar/Wind Helper
0.977
252507AC2-088 GEN
Solar/Wind Helper
0.876
25197008MELDL1
50/50
0.735
972163AH1-664 GEN
Solar/Wind Harmer
27.834
972165AH1-665 GEN
Solar/Wind Harmer
22.292
339243AC2-075 GEN1
Solar/Wind Harmer
0.003
3429211JKCT 2G
Adder
26.85
339211AE2-254 GEN
Solar/Wind Harmer
0.004
965401AG1-405 GEN
Solar/Wind Harmer
5.057
965411AG1-406 GEN
Solar/Wind Harmer
3.253
970455AG2-298 GEN
Solar/Wind Harmer
4.66
970281AG2-184 GEN
Solar/Wind Harmer
7.526
972143AH1-644 GEN
Solar/Wind Harmer
3.883
945631AF1-228 GEN
Solar/Wind Helper
0.946
3429631SPURLK3G
50/50
8.093
25197108MELDL2
50/50
0.746
958171AF2-111 GEN
Solar/Wind Harmer
74.563
972167AH1-666 GEN
Solar/Wind Harmer
20.74
3429391JKCT 9G
Adder
20.324
970093AG2-073 GEN
Solar/Wind Harmer
13.746
966571AG1-526 GEN
Solar/Wind Harmer
25.362
972273AH1-721 GEN
Adder
91.009
970273AG2-179 GEN
Solar/Wind Harmer
3.88
960741AF2-365 GEN
Solar/Wind Harmer
2.587
339250AF1-203 GEN
Solar/Wind Harmer
0.001
971155AH1-034 GEN
Solar/Wind Harmer
5.788
962251AG1-071 GEN
Solar/Wind Harmer
3.005
972103AH1-617 GEN
Solar/Wind Harmer
7.168
253338AC1-165 GEN
Solar/Wind Helper
0.943
253333AC1-068 GEN
Solar/Wind Helper
0.977
253406AD2-031_GEN
Solar/Wind Helper
0.781
253415AE1-040 GEN
Solar/Wind Helper
0.462
950041AG9-017
External Queue
18.61962890625
950051AG9-018
External Queue
18.446699142456055
CPLELTFEXP_CPLE->PJM
CLTF
0.921
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.382
LAGNLTFEXP_LAGN->PJM
CLTF
5.884
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.082
TVALTFEXP_TVA->PJM
CLTF
3.489
NYPJM->LTFIMP_NY
CLTF
0.611
LGEELTFEXP_LGEE->PJM
CLTF
4.828
WECLTFEXP_WEC->PJM
CLTF
0.485
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.306
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.499
MECLTFEXP_MEC->PJM
CLTF
3.081
SIGELTFEXP_SIGE->PJM
CLTF
0.231

Details for AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:157.65 %
Rating:54.0 MVA
Rating Type:B
MVA to Mitigate:85.13
MW Contribution:52.75
Bus #Bus NameTypeMW Contribution
966021AG1-471 GEN
Solar/Wind Harmer
39.753
971485AH1-239 GEN
Solar/Wind Harmer
52.747
339255AE2-071 GEN
Solar/Wind Harmer
0.562
339250AF1-203 GEN
Solar/Wind Harmer
0.321
971155AH1-034 GEN
Solar/Wind Harmer
4.448
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.495
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
0.041
TVALTFEXP_TVA->PJM
CLTF
0.014
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.006
LGEELTFEXP_LGEE->PJM
CLTF
0.046
WECLTFEXP_WEC->PJM
CLTF
0.011
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.019
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.013
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.384
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.088
MECLTFEXP_MEC->PJM
CLTF
0.058
SIGELTFEXP_SIGE->PJM
CLTF
0.005

Details for AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:157.65 %
Rating:54.0 MVA
Rating Type:B
MVA to Mitigate:85.13
MW Contribution:52.75
Bus #Bus NameTypeMW Contribution
966021AG1-471 GEN
Solar/Wind Harmer
39.753
971485AH1-239 GEN
Solar/Wind Harmer
52.747
339255AE2-071 GEN
Solar/Wind Harmer
0.562
339250AF1-203 GEN
Solar/Wind Harmer
0.321
971155AH1-034 GEN
Solar/Wind Harmer
4.448
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.495
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
0.041
TVALTFEXP_TVA->PJM
CLTF
0.014
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.006
LGEELTFEXP_LGEE->PJM
CLTF
0.046
WECLTFEXP_WEC->PJM
CLTF
0.011
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.019
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.013
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.384
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.088
MECLTFEXP_MEC->PJM
CLTF
0.058
SIGELTFEXP_SIGE->PJM
CLTF
0.005

Details for AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line l/o EKPC_P2-3_MAR W38-1014_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_MAR W38-1014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:156.44 %
Rating:54.0 MVA
Rating Type:B
MVA to Mitigate:84.48
MW Contribution:52.85
Bus #Bus NameTypeMW Contribution
966021AG1-471 GEN
Solar/Wind Harmer
39.827
971485AH1-239 GEN
Solar/Wind Harmer
52.855
339255AE2-071 GEN
Solar/Wind Harmer
0.576
339250AF1-203 GEN
Solar/Wind Harmer
0.329
971155AH1-034 GEN
Solar/Wind Harmer
4.574
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.588
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
0.059
TVALTFEXP_TVA->PJM
CLTF
0.026
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.006
LGEELTFEXP_LGEE->PJM
CLTF
0.044
WECLTFEXP_WEC->PJM
CLTF
0.012
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.017
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.012
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.419
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.122
MECLTFEXP_MEC->PJM
CLTF
0.066
SIGELTFEXP_SIGE->PJM
CLTF
0.005

Details for AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:156.42 %
Rating:54.0 MVA
Rating Type:B
MVA to Mitigate:84.47
MW Contribution:52.69
Bus #Bus NameTypeMW Contribution
966021AG1-471 GEN
Solar/Wind Harmer
39.712
971485AH1-239 GEN
Solar/Wind Harmer
52.69
339255AE2-071 GEN
Solar/Wind Harmer
0.559
339250AF1-203 GEN
Solar/Wind Harmer
0.32
971155AH1-034 GEN
Solar/Wind Harmer
4.425
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.459
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
0.031
TVALTFEXP_TVA->PJM
CLTF
0.006
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.006
LGEELTFEXP_LGEE->PJM
CLTF
0.05
WECLTFEXP_WEC->PJM
CLTF
0.011
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.021
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.015
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.382
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.067
MECLTFEXP_MEC->PJM
CLTF
0.056
SIGELTFEXP_SIGE->PJM
CLTF
0.005

Details for AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line l/o EKPC_P4-2_MAR W38-1004_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P4-2_MAR W38-1004_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:155.6 %
Rating:54.0 MVA
Rating Type:B
MVA to Mitigate:84.02
MW Contribution:52.88
Bus #Bus NameTypeMW Contribution
966021AG1-471 GEN
Solar/Wind Harmer
39.846
971485AH1-239 GEN
Solar/Wind Harmer
52.881
339255AE2-071 GEN
Solar/Wind Harmer
0.577
339250AF1-203 GEN
Solar/Wind Harmer
0.329
971155AH1-034 GEN
Solar/Wind Harmer
4.58
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.589
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
0.063
TVALTFEXP_TVA->PJM
CLTF
0.028
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.005
LGEELTFEXP_LGEE->PJM
CLTF
0.041
WECLTFEXP_WEC->PJM
CLTF
0.012
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.016
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.011
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.41
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.127
MECLTFEXP_MEC->PJM
CLTF
0.065
SIGELTFEXP_SIGE->PJM
CLTF
0.005

Details for AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line l/o EKPC_P4-2_TAYLOR W45-1014_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P4-2_TAYLOR W45-1014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:155.6 %
Rating:54.0 MVA
Rating Type:B
MVA to Mitigate:84.02
MW Contribution:52.88
Bus #Bus NameTypeMW Contribution
966021AG1-471 GEN
Solar/Wind Harmer
39.846
971485AH1-239 GEN
Solar/Wind Harmer
52.881
339255AE2-071 GEN
Solar/Wind Harmer
0.577
339250AF1-203 GEN
Solar/Wind Harmer
0.329
971155AH1-034 GEN
Solar/Wind Harmer
4.58
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.589
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
0.063
TVALTFEXP_TVA->PJM
CLTF
0.028
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.005
LGEELTFEXP_LGEE->PJM
CLTF
0.041
WECLTFEXP_WEC->PJM
CLTF
0.012
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.016
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.011
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.41
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.127
MECLTFEXP_MEC->PJM
CLTF
0.065
SIGELTFEXP_SIGE->PJM
CLTF
0.005

Details for AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line l/o EKPC_P2-2_GREEN CO 161_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_GREEN CO 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:154.94 %
Rating:54.0 MVA
Rating Type:B
MVA to Mitigate:83.67
MW Contribution:52.87
Bus #Bus NameTypeMW Contribution
339250AF1-203 GEN
Solar/Wind Harmer
0.328
971155AH1-034 GEN
Solar/Wind Harmer
4.548
966021AG1-471 GEN
Solar/Wind Harmer
39.839
971485AH1-239 GEN
Solar/Wind Harmer
52.869
339255AE2-071 GEN
Solar/Wind Harmer
0.573
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.564
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
0.057
TVALTFEXP_TVA->PJM
CLTF
0.025
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.005
LGEELTFEXP_LGEE->PJM
CLTF
0.042
WECLTFEXP_WEC->PJM
CLTF
0.012
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.016
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.011
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.404
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.117
MECLTFEXP_MEC->PJM
CLTF
0.063
SIGELTFEXP_SIGE->PJM
CLTF
0.005

Details for AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line l/o EKPC_P2-2_CASEY CO 161_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_CASEY CO 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:154.68 %
Rating:54.0 MVA
Rating Type:B
MVA to Mitigate:83.53
MW Contribution:52.81
Bus #Bus NameTypeMW Contribution
966021AG1-471 GEN
Solar/Wind Harmer
39.801
971485AH1-239 GEN
Solar/Wind Harmer
52.813
339255AE2-071 GEN
Solar/Wind Harmer
0.566
339250AF1-203 GEN
Solar/Wind Harmer
0.323
971155AH1-034 GEN
Solar/Wind Harmer
4.487
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.535
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
0.046
TVALTFEXP_TVA->PJM
CLTF
0.016
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.005
LGEELTFEXP_LGEE->PJM
CLTF
0.049
WECLTFEXP_WEC->PJM
CLTF
0.012
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.019
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.013
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.414
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.097
MECLTFEXP_MEC->PJM
CLTF
0.063
SIGELTFEXP_SIGE->PJM
CLTF
0.005

Details for AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line l/o EKPC_P2-2_MARION CO 161_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_MARION CO 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:154.57 %
Rating:54.0 MVA
Rating Type:B
MVA to Mitigate:83.47
MW Contribution:52.86
Bus #Bus NameTypeMW Contribution
966021AG1-471 GEN
Solar/Wind Harmer
39.827
971485AH1-239 GEN
Solar/Wind Harmer
52.856
339255AE2-071 GEN
Solar/Wind Harmer
0.576
339250AF1-203 GEN
Solar/Wind Harmer
0.329
971155AH1-034 GEN
Solar/Wind Harmer
4.575
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.596
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
0.06
TVALTFEXP_TVA->PJM
CLTF
0.026
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.005
LGEELTFEXP_LGEE->PJM
CLTF
0.045
WECLTFEXP_WEC->PJM
CLTF
0.013
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.017
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.012
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.427
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.125
MECLTFEXP_MEC->PJM
CLTF
0.067
SIGELTFEXP_SIGE->PJM
CLTF
0.005

Details for AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line l/o EKPC_P2-2_MCCR-WINFD161_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_MCCR-WINFD161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:154.44 %
Rating:54.0 MVA
Rating Type:B
MVA to Mitigate:83.4
MW Contribution:52.69
Bus #Bus NameTypeMW Contribution
966021AG1-471 GEN
Solar/Wind Harmer
39.712
971485AH1-239 GEN
Solar/Wind Harmer
52.689
339255AE2-071 GEN
Solar/Wind Harmer
0.558
339250AF1-203 GEN
Solar/Wind Harmer
0.319
971155AH1-034 GEN
Solar/Wind Harmer
4.418
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.6
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
0.069
TVALTFEXP_TVA->PJM
CLTF
0.031
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.005
LGEELTFEXP_LGEE->PJM
CLTF
0.038
WECLTFEXP_WEC->PJM
CLTF
0.012
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.014
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.01
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.402
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.134
MECLTFEXP_MEC->PJM
CLTF
0.065
SIGELTFEXP_SIGE->PJM
CLTF
0.004

Details for AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line l/o EKPC_P7-1_BULL 161 DBL_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_BULL 161 DBL_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:153.98 %
Rating:54.0 MVA
Rating Type:B
MVA to Mitigate:83.15
MW Contribution:52.89
Bus #Bus NameTypeMW Contribution
966021AG1-471 GEN
Solar/Wind Harmer
39.856
971485AH1-239 GEN
Solar/Wind Harmer
52.892
339255AE2-071 GEN
Solar/Wind Harmer
0.574
339250AF1-203 GEN
Solar/Wind Harmer
0.328
971155AH1-034 GEN
Solar/Wind Harmer
4.56
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.57
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
0.064
TVALTFEXP_TVA->PJM
CLTF
0.03
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.005
LGEELTFEXP_LGEE->PJM
CLTF
0.033
WECLTFEXP_WEC->PJM
CLTF
0.011
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.014
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.01
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.379
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.125
MECLTFEXP_MEC->PJM
CLTF
0.062
SIGELTFEXP_SIGE->PJM
CLTF
0.004

Details for AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line l/o EKPC_P7-1_SSHAD 161 DBL_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_SSHAD 161 DBL_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:153.79 %
Rating:54.0 MVA
Rating Type:B
MVA to Mitigate:83.05
MW Contribution:52.89
Bus #Bus NameTypeMW Contribution
966021AG1-471 GEN
Solar/Wind Harmer
39.853
971485AH1-239 GEN
Solar/Wind Harmer
52.888
339255AE2-071 GEN
Solar/Wind Harmer
0.573
339250AF1-203 GEN
Solar/Wind Harmer
0.327
971155AH1-034 GEN
Solar/Wind Harmer
4.549
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.56
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
0.063
TVALTFEXP_TVA->PJM
CLTF
0.029
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.005
LGEELTFEXP_LGEE->PJM
CLTF
0.033
WECLTFEXP_WEC->PJM
CLTF
0.011
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.015
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.01
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.375
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.123
MECLTFEXP_MEC->PJM
CLTF
0.061
SIGELTFEXP_SIGE->PJM
CLTF
0.004

Details for [AH1-239] AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line l/o EKPC_P1-2_AH1-239 TP-2UPCHURCH T-69_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_AH1-239 TP-2UPCHURCH T-69_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:152.57 %
Rating:54.0 MVA
Rating Type:B
MVA to Mitigate:82.39
MW Contribution:80.0
IPD Plant:AH1-239
Bus #Bus NameTypeMW Contribution
971485AH1-239 GEN
PJM_IPD
80

Details for AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line l/o EKPC_P1-2_AH1-239 TP-2UPCHURCH T-69_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_AH1-239 TP-2UPCHURCH T-69_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:148.65 %
Rating:54.0 MVA
Rating Type:B
MVA to Mitigate:80.27
MW Contribution:48.0
Bus #Bus NameTypeMW Contribution
971485AH1-239 GEN
Solar/Wind Harmer
48
966021AG1-471 GEN
Solar/Wind Harmer
32.4

Details for AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:EKPC
Facility Description:
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.81 %
Rating:49.0 MVA
Rating Type:A
MVA to Mitigate:53.32
MW Contribution:36.86
Bus #Bus NameTypeMW Contribution
339250AF1-203 GEN
Solar/Wind Harmer
0.001
971155AH1-034 GEN
Solar/Wind Harmer
3.626
966021AG1-471 GEN
Solar/Wind Harmer
27.782
971485AH1-239 GEN
Solar/Wind Harmer
36.862
339255AE2-071 GEN
Solar/Wind Harmer
-0.061
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.5
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
0.044
TVALTFEXP_TVA->PJM
CLTF
0.015
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.005
LGEELTFEXP_LGEE->PJM
CLTF
0.043
WECLTFEXP_WEC->PJM
CLTF
0.011
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.018
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.013
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.384
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.091
MECLTFEXP_MEC->PJM
CLTF
0.058
SIGELTFEXP_SIGE->PJM
CLTF
0.004

Details for AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line l/o EKPC_P1-2_MCCR-WAYNE161_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_MCCR-WAYNE161_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.03 %
Rating:54.0 MVA
Rating Type:B
MVA to Mitigate:56.72
MW Contribution:27.69
Bus #Bus NameTypeMW Contribution
339250AF1-203 GEN
Solar/Wind Harmer
0
971155AH1-034 GEN
Solar/Wind Harmer
3.072
966021AG1-471 GEN
Solar/Wind Harmer
20.847
971485AH1-239 GEN
Solar/Wind Harmer
27.688
339255AE2-071 GEN
Solar/Wind Harmer
-0.05
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.935
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
0.148
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.006
TVALTFEXP_TVA->PJM
CLTF
0.096
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.004
LGEELTFEXP_LGEE->PJM
CLTF
0.025
WECLTFEXP_WEC->PJM
CLTF
0.014
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.478
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.32
MECLTFEXP_MEC->PJM
CLTF
0.087
SIGELTFEXP_SIGE->PJM
CLTF
0.004

Details for AH1-034 TP-2PATTON RD J 69.0 kV Ckt 1 line l/o EKPC_P2-3_SSHAD S11-1039_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
AH1-034 TP-2PATTON RD J 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_SSHAD S11-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.38 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:73.95
MW Contribution:5.13
Bus #Bus NameTypeMW Contribution
339255AE2-071 GEN
Solar/Wind Harmer
3.235
971485AH1-239 GEN
Solar/Wind Harmer
5.131
339231AF1-038_GEN
Solar/Wind Harmer
0.989
970273AG2-179 GEN
Solar/Wind Harmer
1.383
964901AG1-354 GEN
Solar/Wind Harmer
5.717
971155AH1-034 GEN
Solar/Wind Harmer
49.502
339250AF1-203 GEN
Solar/Wind Harmer
1.849
970273AG2-179 GEN
Solar/Wind Harmer
2.209
972273AH1-721 GEN
Adder
7.484
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.011
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.005
LGEELTFEXP_LGEE->PJM
CLTF
0.027
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.034
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.022
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.382

Details for AH1-034 TP-2PATTON RD J 69.0 kV Ckt 1 line l/o EKPC_P4-2_SSHAD S11-1004_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
AH1-034 TP-2PATTON RD J 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P4-2_SSHAD S11-1004_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.37 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:73.94
MW Contribution:5.13
Bus #Bus NameTypeMW Contribution
339255AE2-071 GEN
Solar/Wind Harmer
3.235
971485AH1-239 GEN
Solar/Wind Harmer
5.131
339231AF1-038_GEN
Solar/Wind Harmer
0.989
970273AG2-179 GEN
Solar/Wind Harmer
1.383
964901AG1-354 GEN
Solar/Wind Harmer
5.717
971155AH1-034 GEN
Solar/Wind Harmer
49.502
339250AF1-203 GEN
Solar/Wind Harmer
1.849
970273AG2-179 GEN
Solar/Wind Harmer
2.209
972273AH1-721 GEN
Adder
7.484
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.011
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.005
LGEELTFEXP_LGEE->PJM
CLTF
0.027
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.034
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.022
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.382

Details for AH1-034 TP-2PATTON RD J 69.0 kV Ckt 1 line l/o EKPC_P2-2_SUMMSHADE 161 #2_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
AH1-034 TP-2PATTON RD J 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_SUMMSHADE 161 #2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:117.33 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:73.92
MW Contribution:5.13
Bus #Bus NameTypeMW Contribution
339255AE2-071 GEN
Solar/Wind Harmer
3.235
971485AH1-239 GEN
Solar/Wind Harmer
5.131
339231AF1-038_GEN
Solar/Wind Harmer
0.989
970273AG2-179 GEN
Solar/Wind Harmer
1.383
964901AG1-354 GEN
Solar/Wind Harmer
5.717
971155AH1-034 GEN
Solar/Wind Harmer
49.502
339250AF1-203 GEN
Solar/Wind Harmer
1.849
970273AG2-179 GEN
Solar/Wind Harmer
2.209
972273AH1-721 GEN
Adder
7.484
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.011
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.005
LGEELTFEXP_LGEE->PJM
CLTF
0.027
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.034
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.022
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.382

Details for AH1-034 TP-2PATTON RD J 69.0 kV Ckt 1 line l/o EKPC_P4-5_SSHAD S11-1004_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
AH1-034 TP-2PATTON RD J 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P4-5_SSHAD S11-1004_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.99 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:73.7
MW Contribution:5.04
Bus #Bus NameTypeMW Contribution
339255AE2-071 GEN
Solar/Wind Harmer
3.222
971485AH1-239 GEN
Solar/Wind Harmer
5.044
339231AF1-038_GEN
Solar/Wind Harmer
0.973
970273AG2-179 GEN
Solar/Wind Harmer
1.361
964901AG1-354 GEN
Solar/Wind Harmer
5.684
971155AH1-034 GEN
Solar/Wind Harmer
49.37
339250AF1-203 GEN
Solar/Wind Harmer
1.841
970273AG2-179 GEN
Solar/Wind Harmer
2.174
972273AH1-721 GEN
Adder
7.113
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.005
LGEELTFEXP_LGEE->PJM
CLTF
0.046
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.04
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.027
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.402

Details for AH1-034 TP-2PATTON RD J 69.0 kV Ckt 1 line l/o EKPC_P2-3_SSHAD S11-1044_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
AH1-034 TP-2PATTON RD J 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_SSHAD S11-1044_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.97 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:73.69
MW Contribution:5.04
Bus #Bus NameTypeMW Contribution
970273AG2-179 GEN
Solar/Wind Harmer
1.361
964901AG1-354 GEN
Solar/Wind Harmer
5.684
339255AE2-071 GEN
Solar/Wind Harmer
3.222
971485AH1-239 GEN
Solar/Wind Harmer
5.044
339231AF1-038_GEN
Solar/Wind Harmer
0.973
971155AH1-034 GEN
Solar/Wind Harmer
49.37
339250AF1-203 GEN
Solar/Wind Harmer
1.841
970273AG2-179 GEN
Solar/Wind Harmer
2.174
972273AH1-721 GEN
Adder
7.113
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.005
LGEELTFEXP_LGEE->PJM
CLTF
0.046
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.04
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.027
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.402

Details for AH1-034 TP-2PATTON RD J 69.0 kV Ckt 1 line l/o EKPC_P2-2_SUMMSHADE 161 #1_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
AH1-034 TP-2PATTON RD J 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_SUMMSHADE 161 #1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:109.71 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:69.12
MW Contribution:5.26
Bus #Bus NameTypeMW Contribution
339255AE2-071 GEN
Solar/Wind Harmer
3.263
971485AH1-239 GEN
Solar/Wind Harmer
5.262
339231AF1-038_GEN
Solar/Wind Harmer
0.989
970273AG2-179 GEN
Solar/Wind Harmer
1.387
971155AH1-034 GEN
Solar/Wind Harmer
49.919
339250AF1-203 GEN
Solar/Wind Harmer
1.864
970273AG2-179 GEN
Solar/Wind Harmer
2.215
972273AH1-721 GEN
Adder
6.632
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.006
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.032
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.003
LGEELTFEXP_LGEE->PJM
CLTF
0.01
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.021
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.014
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.304

Details for [AH1-239] AH1-239 TP-2UPCHURCH T 69.0 kV Ckt 1 line l/o EKPC_P1-2_AG1-471 TP-2ZULA J NO-69_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
AH1-239 TP-2UPCHURCH T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_AG1-471 TP-2ZULA J NO-69_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:150.75 %
Rating:54.0 MVA
Rating Type:B
MVA to Mitigate:81.41
MW Contribution:80.0
IPD Plant:AH1-239
Bus #Bus NameTypeMW Contribution
971485AH1-239 GEN
PJM_IPD
80

Details for [AH1-239] AH1-239 TP-2UPCHURCH T 69.0 kV Ckt 1 line l/o EKPC_P1-2_AG1-471 TP-AH1-239 TP-69_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
AH1-239 TP-2UPCHURCH T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_AG1-471 TP-AH1-239 TP-69_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:150.75 %
Rating:54.0 MVA
Rating Type:B
MVA to Mitigate:81.41
MW Contribution:80.0
IPD Plant:AH1-239
Bus #Bus NameTypeMW Contribution
971485AH1-239 GEN
PJM_IPD
80

Details for AH1-239 TP-2UPCHURCH T 69.0 kV Ckt 1 line l/o EKPC_P1-2_AG1-471 TP-2ZULA J NO-69_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
AH1-239 TP-2UPCHURCH T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_AG1-471 TP-2ZULA J NO-69_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:148.61 %
Rating:54.0 MVA
Rating Type:B
MVA to Mitigate:80.25
MW Contribution:48.0
Bus #Bus NameTypeMW Contribution
971485AH1-239 GEN
Solar/Wind Harmer
48
966021AG1-471 GEN
Solar/Wind Harmer
32.4

Details for AH1-239 TP-2UPCHURCH T 69.0 kV Ckt 1 line l/o EKPC_P2-2_TVA WAYNE 161_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
AH1-239 TP-2UPCHURCH T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_TVA WAYNE 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:100.2 %
Rating:54.0 MVA
Rating Type:B
MVA to Mitigate:54.11
MW Contribution:29.13
Bus #Bus NameTypeMW Contribution
971485AH1-239 GEN
Solar/Wind Harmer
29.128
966021AG1-471 GEN
Solar/Wind Harmer
16.565
339255AE2-071 GEN
Solar/Wind Helper
0.193
972273AH1-721 GEN
Adder
10.298
339250AF1-203 GEN
Solar/Wind Helper
0.11
G-007ALTFEXP_G-007A->PJM
CMTX
0.014
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.027
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.028
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.108
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.004
VTFLTFEXP_VFT->PJM
CMTX
0.036
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.003
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.216

Details for [AH1-239] AH1-239 TP-AG1-471 TP 69.0 kV Ckt 1 line l/o EKPC_P1-2_AH1-239 TP-2UPCHURCH T-69_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
AH1-239 TP-AG1-471 TP 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_AH1-239 TP-2UPCHURCH T-69_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:152.64 %
Rating:54.0 MVA
Rating Type:B
MVA to Mitigate:82.43
MW Contribution:80.0
IPD Plant:AH1-239
Bus #Bus NameTypeMW Contribution
971485AH1-239 GEN
PJM_IPD
80

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line l/o EKPC_P1-2_COOP-DEN161_SRT-A-1


Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_COOP-DEN161_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:188.87 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:562.83
MW Contribution:2.73
Bus #Bus NameTypeMW Contribution
966021AG1-471 GEN
Solar/Wind Harmer
2.141
971485AH1-239 GEN
Solar/Wind Harmer
2.729
339231AF1-038_GEN
Solar/Wind Helper
0.353
3429451LAUREL 1G
50/50
2.132
972273AH1-721 GEN
50/50
625.962
G-007ALTFEXP_G-007A->PJM
CMTX
0.054
CPLELTFEXP_CPLE->PJM
CLTF
0.014
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.104
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.17
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.578
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.018
GibsonPJM->LTFIMP_GIBSON
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
0.146
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.458

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line l/o EKPC_P2-2_LAUR-LAURD161_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_LAUR-LAURD161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:136.17 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:405.79
MW Contribution:3.67
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
1.907
966021AG1-471 GEN
Solar/Wind Harmer
2.749
971485AH1-239 GEN
Solar/Wind Harmer
3.669
972273AH1-721 GEN
50/50
373.146
CPLELTFEXP_CPLE->PJM
CLTF
0.038
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.66
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.039
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.119
LAGNLTFEXP_LAGN->PJM
CLTF
0.182
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.154
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.129
NYPJM->LTFIMP_NY
CLTF
0.007
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.342
MECLTFEXP_MEC->PJM
CLTF
0.028

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line l/o EKPC_P2-3_LAURL S50-1014_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_LAURL S50-1014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:136.16 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:405.77
MW Contribution:3.67
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
1.907
966021AG1-471 GEN
Solar/Wind Harmer
2.749
971485AH1-239 GEN
Solar/Wind Harmer
3.669
972273AH1-721 GEN
50/50
373.157
CPLELTFEXP_CPLE->PJM
CLTF
0.038
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.661
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.039
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.119
LAGNLTFEXP_LAGN->PJM
CLTF
0.182
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.154
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.129
NYPJM->LTFIMP_NY
CLTF
0.007
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.342
MECLTFEXP_MEC->PJM
CLTF
0.028

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line l/o EKPC_P2-2_LAUREL CO 161_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_LAUREL CO 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:136.16 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:405.77
MW Contribution:3.67
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
1.907
972273AH1-721 GEN
50/50
373.157
966021AG1-471 GEN
Solar/Wind Harmer
2.749
971485AH1-239 GEN
Solar/Wind Harmer
3.669
CPLELTFEXP_CPLE->PJM
CLTF
0.038
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.661
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.039
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.119
LAGNLTFEXP_LAGN->PJM
CLTF
0.182
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.154
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.129
NYPJM->LTFIMP_NY
CLTF
0.007
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.342
MECLTFEXP_MEC->PJM
CLTF
0.028

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line l/o EKPC_P4-5_LAURL S50-1014_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P4-5_LAURL S50-1014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:136.16 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:405.76
MW Contribution:3.67
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
1.907
966021AG1-471 GEN
Solar/Wind Harmer
2.749
971485AH1-239 GEN
Solar/Wind Harmer
3.669
972273AH1-721 GEN
50/50
373.157
CPLELTFEXP_CPLE->PJM
CLTF
0.038
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.661
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.039
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.119
LAGNLTFEXP_LAGN->PJM
CLTF
0.182
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.154
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.129
NYPJM->LTFIMP_NY
CLTF
0.007
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.342
MECLTFEXP_MEC->PJM
CLTF
0.028

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line l/o EKPC_P7-1_LAURL 161 DBL_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_LAURL 161 DBL_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:136.1 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:405.57
MW Contribution:3.67
Bus #Bus NameTypeMW Contribution
966021AG1-471 GEN
Solar/Wind Harmer
2.75
971485AH1-239 GEN
Solar/Wind Harmer
3.67
3429451LAUREL 1G
50/50
1.907
972273AH1-721 GEN
50/50
373.165
CPLELTFEXP_CPLE->PJM
CLTF
0.039
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.663
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.039
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.119
LAGNLTFEXP_LAGN->PJM
CLTF
0.183
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.155
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.13
NYPJM->LTFIMP_NY
CLTF
0.007
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.343
MECLTFEXP_MEC->PJM
CLTF
0.028

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line l/o EKPC_P1-2_LAUR-L DAM161_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_LAUR-L DAM161_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:135.52 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:403.84
MW Contribution:2.56
Bus #Bus NameTypeMW Contribution
966021AG1-471 GEN
Solar/Wind Harmer
1.918
971485AH1-239 GEN
Solar/Wind Harmer
2.56
3429451LAUREL 1G
50/50
1.907
972273AH1-721 GEN
50/50
373.146
CPLELTFEXP_CPLE->PJM
CLTF
0.038
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.66
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.039
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.119
LAGNLTFEXP_LAGN->PJM
CLTF
0.182
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.154
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.129
NYPJM->LTFIMP_NY
CLTF
0.007
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.342
MECLTFEXP_MEC->PJM
CLTF
0.028

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line l/o EKPC_P1-2_COOP-LAUREL161_SRT-A-1


Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
Contingency Name:
EKPC_P1-2_COOP-LAUREL161_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:267.78 %
Rating:210.0 MVA
Rating Type:B
MVA to Mitigate:562.33
MW Contribution:2.73
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
625.421
966021AG1-471 GEN
Solar/Wind Harmer
2.139
971485AH1-239 GEN
Solar/Wind Harmer
2.726
339231AF1-038_GEN
Solar/Wind Helper
0.352
3429451LAUREL 1G
50/50
2.13
G-007ALTFEXP_G-007A->PJM
CMTX
0.054
CPLELTFEXP_CPLE->PJM
CLTF
0.014
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.104
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.17
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.578
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.018
GibsonPJM->LTFIMP_GIBSON
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
0.145
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.458

Details for AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:175.99 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:524.46
MW Contribution:6.05
Bus #Bus NameTypeMW Contribution
966021AG1-471 GEN
Solar/Wind Harmer
4.456
971485AH1-239 GEN
Solar/Wind Harmer
6.051
972273AH1-721 GEN
50/50
477.945
G-007ALTFEXP_G-007A->PJM
CMTX
0.023
CPLELTFEXP_CPLE->PJM
CLTF
0.119
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.031
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.903
LAGNLTFEXP_LAGN->PJM
CLTF
0.595
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.444
TVALTFEXP_TVA->PJM
CLTF
0.401
WECLTFEXP_WEC->PJM
CLTF
0.029
VTFLTFEXP_VFT->PJM
CMTX
0.06
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.994
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.233
MECLTFEXP_MEC->PJM
CLTF
0.219
SIGELTFEXP_SIGE->PJM
CLTF
0.006

Details for AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:175.54 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:523.1
MW Contribution:6.01
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
476.135
966021AG1-471 GEN
Solar/Wind Harmer
4.424
971485AH1-239 GEN
Solar/Wind Harmer
6.014
G-007ALTFEXP_G-007A->PJM
CMTX
0.019
CPLELTFEXP_CPLE->PJM
CLTF
0.116
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.025
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.964
LAGNLTFEXP_LAGN->PJM
CLTF
0.6
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.435
TVALTFEXP_TVA->PJM
CLTF
0.404
LGEELTFEXP_LGEE->PJM
CLTF
0.005
WECLTFEXP_WEC->PJM
CLTF
0.03
VTFLTFEXP_VFT->PJM
CMTX
0.05
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.04
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.249
MECLTFEXP_MEC->PJM
CLTF
0.226
SIGELTFEXP_SIGE->PJM
CLTF
0.007

Details for AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:175.53 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:523.07
MW Contribution:6.01
Bus #Bus NameTypeMW Contribution
966021AG1-471 GEN
Solar/Wind Harmer
4.424
971485AH1-239 GEN
Solar/Wind Harmer
6.014
972273AH1-721 GEN
50/50
476.135
G-007ALTFEXP_G-007A->PJM
CMTX
0.019
CPLELTFEXP_CPLE->PJM
CLTF
0.116
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.025
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.964
LAGNLTFEXP_LAGN->PJM
CLTF
0.6
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.435
TVALTFEXP_TVA->PJM
CLTF
0.404
LGEELTFEXP_LGEE->PJM
CLTF
0.005
WECLTFEXP_WEC->PJM
CLTF
0.03
VTFLTFEXP_VFT->PJM
CMTX
0.05
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.04
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.249
MECLTFEXP_MEC->PJM
CLTF
0.226
SIGELTFEXP_SIGE->PJM
CLTF
0.007
CONTINGENCY 'AEP_P4_#7421_05CLOVRD 765_BB2_SRT-A'
 OPEN BRANCH FROM BUS 242512 TO BUS 242519 CKT 14   /*05CLOVRD     765.0 - 05CLOVRD     500.0
END
CONTINGENCY 'AEP_P1-3_#7421_05CLOVRD 765_14_SRT-A'
 OPEN BRANCH FROM BUS 242512 TO BUS 242519 CKT 14   /*05CLOVRD     765.0 - 05CLOVRD     500.0
END
CONTINGENCY 'AP_P1-3_MP-765-501T_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1   /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                   /*05BELMON     765.0
END
CONTINGENCY 'AP_P2-3_MP-500-020_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 1          /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 2          /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5          /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1          /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1          /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                          /*05BELMON     765.0
 SET POSTCONTRATING 2492 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
 SET PRECONTRATING 1986 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
END
CONTINGENCY 'AP_P2-3_MP-500-021_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 3          /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5          /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1          /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1          /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                          /*05BELMON     765.0
 SET POSTCONTRATING 2492 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
 SET PRECONTRATING 1986 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
END
CONTINGENCY 'AEP_P4_#37_05MOUNTN 765_B1_SRT-A'
 OPEN BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242516 TO BUS 242920 CKT 1   /*05MOUNTN     765.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
END
CONTINGENCY 'AEP_P4_#2942_05KAMMER 765_PP_SRT-A'
 OPEN BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242516 TO BUS 242920 CKT 1   /*05MOUNTN     765.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
 OPEN BRANCH FROM BUS 242925 TO BUS 243188 CKT 1   /*05KAMMER     765.0 - 05MLG1        26.0
 REMOVE UNIT 1 FROM BUS 243188                     /*05MLG1        26.0
END
CONTINGENCY 'AEP_P1-2_#17217_SRT-A'
 OPEN BRANCH FROM BUS 242925 TO BUS 290623 CKT Z1   /*05KAMMER     765.0 - 05KAMMER_RG  765.0
 OPEN BRANCH FROM BUS 246526 TO BUS 290623 CKT 1    /*05GUERNSEY   765.0 - 05KAMMER_RG  765.0
END
CONTINGENCY 'AEP_P4_#7445_05MARYSV 765_B_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290621 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RF 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 962760 TO BUS 290621 CKT 1    /*AG1-125 TP   765.0 - 05MARYSVL_RF 765.0
END
CONTINGENCY 'AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1   /*05CLOVRD     500.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'AEP_P2-2_#7222_05MALIS 765_1_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1    /*05MALIS      765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290237 CKT 1    /*05MALIS      765.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT SR   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT ZB   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243538 TO BUS 290237 CKT 1    /*05MALISX     138.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 290237 TO BUS 290238 CKT 1    /*05MALIS 1EQ    1.0 - 05MALIS T1    13.8
END
CONTINGENCY 'AEP_P1-2_#7422_16_SRT-A'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1   /*05CLOVRD     500.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'AEP_P7-1_#10944___SRT-A'
 OPEN BRANCH FROM BUS 242528 TO BUS 242940 CKT 1   /*05SPORN      345.0 - 05MUSKNG     345.0
 OPEN BRANCH FROM BUS 242940 TO BUS 242947 CKT 1   /*05MUSKNG     345.0 - 05WATERFORD  345.0
END
CONTINGENCY 'AEP_P7-1_#10856___SRT-A'
 OPEN BRANCH FROM BUS 242528 TO BUS 242940 CKT 1   /*05SPORN      345.0 - 05MUSKNG     345.0
 OPEN BRANCH FROM BUS 242528 TO BUS 242947 CKT 1   /*05SPORN      345.0 - 05WATERFORD  345.0
END
CONTINGENCY 'AEP_P1-2_#309_15_SRT-A'
 OPEN BRANCH FROM BUS 242510 TO BUS 242924 CKT 1   /*05BAKER      765.0 - 05HANG R     765.0
END
CONTINGENCY 'AEP_P1-2_#709_546_SRT-A'
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
END
CONTINGENCY 'AEP_P2-2_#6763_05BIERSR 345_2_SRT-A'
 OPEN BRANCH FROM BUS 970688 TO BUS 246888 CKT 1   /*AG2-444 TP   345.0 - 05BIERSR     345.0
END
CONTINGENCY '34569 34598 34524_SRT-A'
 OPEN BRANCH FROM BUS 249566 TO BUS 249578 CKT 1   /*08FOSTER     345.0 - 08HILCRT     345.0
 OPEN BRANCH FROM BUS 249566 TO BUS 253006 CKT 1   /*08FOSTER     345.0 - 09BATH       345.0
 OPEN BRANCH FROM BUS 249566 TO BUS 253079 CKT 1   /*08FOSTER     345.0 - 09SUGRCK     345.0
END
CONTINGENCY '34524 34598_SRT-A'
 OPEN BRANCH FROM BUS 249566 TO BUS 253006 CKT 1   /*08FOSTER     345.0 - 09BATH       345.0
 OPEN BRANCH FROM BUS 249566 TO BUS 253079 CKT 1   /*08FOSTER     345.0 - 09SUGRCK     345.0
END
CONTINGENCY 'AEP_P2-2_#308_05CULLOD 765_1_SRT-A'
 OPEN BRANCH FROM BUS 242510 TO BUS 242513 CKT 1   /*05BAKER      765.0 - 05CULLOD     765.0
END
CONTINGENCY 'EKPC_P1-2_AG1-471 TP-AH1-239 TP-69_SRT-A'
 DISCONNECT BRANCH FROM BUS 966020 TO BUS 971484 CKT 1   /*AG1-471 TP    69.0 - AH1-239 TP    69.0
END
CONTINGENCY 'EKPC_P1-2_AG1-471 TP-2ZULA J NO-69_SRT-A'
 DISCONNECT BRANCH FROM BUS 966020 TO BUS 342532 CKT 1   /*AG1-471 TP    69.0 - 2ZULA J NO    69.0
END
CONTINGENCY 'EKPC_P2-3_COOP S42-1039_SRT-A'
 OPEN BUS 342715   /*5COOPER1     161.0
 OPEN BUS 342718   /*5COOPER2     161.0
 OPEN BUS 342900   /*1COOPER1 G    13.8
 OPEN BUS 342903   /*1COOPER2 G    20.0
END
CONTINGENCY 'EKPC_P2-2_COOPER 2 161_SRT-A'
 OPEN BUS 342718   /*5COOPER2     161.0
END
CONTINGENCY 'EKPC_P2-3_COOP S42-210G_SRT-A'
 OPEN BUS 342718   /*5COOPER2     161.0
 OPEN BUS 342903   /*1COOPER2 G    20.0
END
CONTINGENCY 'EKPC_P7-1_COOP 161 DBL 2_SRT-A-2'
 OPEN BRANCH FROM BUS 324141 TO BUS 342718 CKT 1   /*5ELIHU       161.0 - 5COOPER2     161.0
 OPEN BRANCH FROM BUS 972272 TO BUS 342757 CKT 1   /*AH1-721 TP   161.0 - 5LAUREL DAM  161.0
END
CONTINGENCY 'EKPC_P4-2_SSHAD S11-1004_SRT-A'
 OPEN BUS 342814   /*5SUMM SHADE  161.0
END
CONTINGENCY 'EKPC_P2-3_SSHAD S11-1039_SRT-A'
 OPEN BRANCH FROM BUS 341059 TO BUS 342694 CKT 1   /*2BARREN CO    69.0 - 5BARREN CO   161.0
 OPEN BUS 342814                                   /*5SUMM SHADE  161.0
END
CONTINGENCY 'EKPC_P2-2_SUMMSHADE 161 #2_SRT-A'
 OPEN BUS 342814   /*5SUMM SHADE  161.0
END
CONTINGENCY 'EKPC_P2-3_SSHAD S11-1044_SRT-A'
 OPEN BRANCH FROM BUS 964900 TO BUS 342814 CKT 1   /*AG1-354 TP   161.0 - 5SUMM SHADE  161.0
 OPEN BUS 342814                                   /*5SUMM SHADE  161.0
 OPEN BUS 361788                                   /*5SUM SHAD TP 161.0
END
CONTINGENCY 'EKPC_P4-5_SSHAD S11-1004_SRT-A'
 OPEN BRANCH FROM BUS 341059 TO BUS 342694 CKT 1   /*2BARREN CO    69.0 - 5BARREN CO   161.0
 OPEN BRANCH FROM BUS 342694 TO BUS 342814 CKT 1   /*5BARREN CO   161.0 - 5SUMM SHADE  161.0
 OPEN BUS 342814                                   /*5SUMM SHADE  161.0
 OPEN BUS 361788                                   /*5SUM SHAD TP 161.0
END
CONTINGENCY 'EKPC_P2-2_ELIHU-COOP 161_SRT-A'
 OPEN BRANCH FROM BUS 324141 TO BUS 342718 CKT 1   /*5ELIHU       161.0 - 5COOPER2     161.0
END
CONTINGENCY 'EKPC_P7-1_COOP 161 DBL 2_SRT-A-1'
 OPEN BRANCH FROM BUS 324141 TO BUS 342718 CKT 1   /*5ELIHU       161.0 - 5COOPER2     161.0
 OPEN BRANCH FROM BUS 342718 TO BUS 972272 CKT 1   /*5COOPER2     161.0 - AH1-721 TP   161.0
END
CONTINGENCY 'EKPC_P1-2_COOP-ELIHU161_SRT-A'
 OPEN BRANCH FROM BUS 324141 TO BUS 342718 CKT 1   /*5ELIHU       161.0 - 5COOPER2     161.0
END
CONTINGENCY 'EKPC_P2-3_SSHAD S11-1014_SRT-A'
 OPEN BRANCH FROM BUS 964900 TO BUS 342814 CKT 1   /*AG1-354 TP   161.0 - 5SUMM SHADE  161.0
 OPEN BUS 361788                                   /*5SUM SHAD TP 161.0
END
CONTINGENCY 'EKPC_P2-3_SSHAD S11-1004_SRT-A-1'
 OPEN BRANCH FROM BUS 341059 TO BUS 342694 CKT 1   /*2BARREN CO    69.0 - 5BARREN CO   161.0
 OPEN BRANCH FROM BUS 342694 TO BUS 342814 CKT 1   /*5BARREN CO   161.0 - 5SUMM SHADE  161.0
 OPEN BRANCH FROM BUS 361788 TO BUS 342814 CKT 1   /*5SUM SHAD TP 161.0 - 5SUMM SHADE  161.0
 OPEN BRANCH FROM BUS 964900 TO BUS 342814 CKT 1   /*AG1-354 TP   161.0 - 5SUMM SHADE  161.0
END
CONTINGENCY 'EKPC_P2-3_MAR W38-1014_SRT-A'
 OPEN BRANCH FROM BUS 341269 TO BUS 342703 CKT 1   /*2CASEY CO     69.0 - 5CASEY CO    161.0
 OPEN BRANCH FROM BUS 342703 TO BUS 342760 CKT 1   /*5CASEY CO    161.0 - 5LIBERTY J   161.0
 OPEN BRANCH FROM BUS 342703 TO BUS 342769 CKT 1   /*5CASEY CO    161.0 - 5MARION CO   161.0
 OPEN BRANCH FROM BUS 342770 TO BUS 342769 CKT 1   /*4MARION CO   138.0 - 5MARION CO   161.0
END
CONTINGENCY 'EKPC_P4-2_TAYLOR W45-1014_SRT-A'
 OPEN BRANCH FROM BUS 342769 TO BUS 342775 CKT 1   /*5MARION CO   161.0 - 5MARION IP T 161.0
 OPEN BRANCH FROM BUS 342772 TO BUS 342797 CKT 1   /*5MARION IP   161.0 - 5S MARION IT 161.0
 OPEN BRANCH FROM BUS 342775 TO BUS 342805 CKT 1   /*5MARION IP T 161.0 - 5SALOMA  T   161.0
 OPEN BRANCH FROM BUS 342802 TO BUS 342805 CKT 1   /*5SALOMA      161.0 - 5SALOMA  T   161.0
END
CONTINGENCY 'EKPC_P4-2_MAR W38-1004_SRT-A'
 OPEN BRANCH FROM BUS 342769 TO BUS 342775 CKT 1   /*5MARION CO   161.0 - 5MARION IP T 161.0
 OPEN BRANCH FROM BUS 342772 TO BUS 342797 CKT 1   /*5MARION IP   161.0 - 5S MARION IT 161.0
 OPEN BRANCH FROM BUS 342775 TO BUS 342797 CKT 1   /*5MARION IP T 161.0 - 5S MARION IT 161.0
 OPEN BRANCH FROM BUS 342775 TO BUS 342805 CKT 1   /*5MARION IP T 161.0 - 5SALOMA  T   161.0
 OPEN BRANCH FROM BUS 342797 TO BUS 342798 CKT 1   /*5S MARION IT 161.0 - 5S MARION IP 161.0
 OPEN BRANCH FROM BUS 342802 TO BUS 342805 CKT 1   /*5SALOMA      161.0 - 5SALOMA  T   161.0
 OPEN BRANCH FROM BUS 342805 TO BUS 339237 CKT 1   /*5SALOMA  T   161.0 - AF1-083 TAP  161.0
END
CONTINGENCY 'EKPC_P2-2_GREEN CO 161_SRT-A'
 OPEN BUS 342733   /*5GREEN CO    161.0
END
CONTINGENCY 'EKPC_P2-2_CASEY CO 161_SRT-A'
 OPEN BUS 342703   /*5CASEY CO    161.0
END
CONTINGENCY 'EKPC_P2-2_MARION CO 161_SRT-A'
 OPEN BUS 342769   /*5MARION CO   161.0
END
CONTINGENCY 'EKPC_P2-2_MCCR-WINFD161_SRT-A'
 OPEN BRANCH FROM BUS 342778 TO BUS 361579 CKT 1   /*5MCCREARY CO 161.0 - 5WINFIELD TN 161.0
END
CONTINGENCY 'EKPC_P7-1_BULL 161 DBL_SRT-A'
 OPEN BUS 326975   /*5CEDAR GRV   161.0
 OPEN BUS 361788   /*5SUM SHAD TP 161.0
END
CONTINGENCY 'EKPC_P7-1_SSHAD 161 DBL_SRT-A'
 OPEN BRANCH FROM BUS 324150 TO BUS 324154 CKT 1   /*5LEBANON JCT 161.0 - 5PADDYS RUN  161.0
 OPEN BRANCH FROM BUS 324150 TO BUS 360334 CKT 1   /*5LEBANON JCT 161.0 - 5SUMMER SHAD 161.0
END
CONTINGENCY 'EKPC_P1-2_AH1-239 TP-2UPCHURCH T-69_SRT-A'
 DISCONNECT BRANCH FROM BUS 971484 TO BUS 342397 CKT 1   /*AH1-239 TP    69.0 - 2UPCHURCH T   69.0
END
CONTINGENCY 'EKPC_P7-1_LAURL 161 DBL_SRT-A'
 OPEN BRANCH FROM BUS 342754 TO BUS 342757 CKT 1   /*5LAUREL CO   161.0 - 5LAUREL DAM  161.0
 OPEN BRANCH FROM BUS 342754 TO BUS 342781 CKT 1   /*5LAUREL CO   161.0 - 5PITTSBURG   161.0
 OPEN BRANCH FROM BUS 342781 TO BUS 342820 CKT 1   /*5PITTSBURG   161.0 - 5TYNER       161.0
END
CONTINGENCY 'EKPC_P2-2_LAUR-LAURD161_SRT-A'
 OPEN BRANCH FROM BUS 342754 TO BUS 342757 CKT 1   /*5LAUREL CO   161.0 - 5LAUREL DAM  161.0
END
CONTINGENCY 'EKPC_P4-5_LAURL S50-1024_SRT-A'
 OPEN BRANCH FROM BUS 324688 TO BUS 342781 CKT 1   /*2PITTSBRG KU  69.0 - 5PITTSBURG   161.0
 OPEN BRANCH FROM BUS 342781 TO BUS 342820 CKT 1   /*5PITTSBURG   161.0 - 5TYNER       161.0
 OPEN BUS 342754                                   /*5LAUREL CO   161.0
END
CONTINGENCY 'EKPC_P2-3_LAURL S50-1024_SRT-A'
 OPEN BRANCH FROM BUS 324688 TO BUS 342781 CKT 1   /*2PITTSBRG KU  69.0 - 5PITTSBURG   161.0
 OPEN BRANCH FROM BUS 341740 TO BUS 342754 CKT 1   /*2LAUREL CO    69.0 - 5LAUREL CO   161.0
 OPEN BRANCH FROM BUS 342754 TO BUS 342781 CKT 1   /*5LAUREL CO   161.0 - 5PITTSBURG   161.0
 OPEN BRANCH FROM BUS 342781 TO BUS 342820 CKT 1   /*5PITTSBURG   161.0 - 5TYNER       161.0
END
CONTINGENCY 'EKPC_P2-2_LAUREL CO 161_SRT-A'
 OPEN BUS 342754   /*5LAUREL CO   161.0
END
CONTINGENCY 'EKPC_P1-2_LAUR-L DAM161_SRT-A'
 OPEN BRANCH FROM BUS 342754 TO BUS 342757 CKT 1   /*5LAUREL CO   161.0 - 5LAUREL DAM  161.0
END
CONTINGENCY 'EKPC_P1-2_COOP 161 TIE_SRT-A'
 OPEN BRANCH FROM BUS 342715 TO BUS 342718 CKT 1   /*5COOPER1     161.0 - 5COOPER2     161.0
END
CONTINGENCY 'EKPC_P7-1_COOP 161 DBL 1_SRT-A'
 OPEN BRANCH FROM BUS 342115 TO BUS 342787 CKT 1   /*2PULASK CO    69.0 - 5PULASK CO   161.0
 OPEN BRANCH FROM BUS 342715 TO BUS 342790 CKT 1   /*5COOPER1     161.0 - 5PULASK CO J 161.0
 OPEN BRANCH FROM BUS 342715 TO BUS 342799 CKT 1   /*5COOPER1     161.0 - 5S OAKHILL   161.0
 OPEN BRANCH FROM BUS 342742 TO BUS 342745 CKT 1   /*5JABEZ       161.0 - 5JABEZ T     161.0
 OPEN BRANCH FROM BUS 342745 TO BUS 342751 CKT 1   /*5JABEZ T     161.0 - 5JAMESTOWN T 161.0
 OPEN BRANCH FROM BUS 342745 TO BUS 342799 CKT 1   /*5JABEZ T     161.0 - 5S OAKHILL   161.0
 OPEN BRANCH FROM BUS 342748 TO BUS 342751 CKT 1   /*5JAMESTOWN   161.0 - 5JAMESTOWN T 161.0
 OPEN BRANCH FROM BUS 342751 TO BUS 342796 CKT 1   /*5JAMESTOWN T 161.0 - 5RUSSEL CO J 161.0
 OPEN BRANCH FROM BUS 342760 TO BUS 342790 CKT 1   /*5LIBERTY J   161.0 - 5PULASK CO J 161.0
 OPEN BRANCH FROM BUS 342787 TO BUS 342790 CKT 1   /*5PULASK CO   161.0 - 5PULASK CO J 161.0
 OPEN BRANCH FROM BUS 342793 TO BUS 342796 CKT 1   /*5RUSSEL CO   161.0 - 5RUSSEL CO J 161.0
 OPEN BRANCH FROM BUS 342796 TO BUS 360448 CKT 1   /*5RUSSEL CO J 161.0 - 5WOLF CRK HP 161.0
END
CONTINGENCY 'EXT_B-345-100_SRT-S'
 OPEN BRANCH FROM BUS 324100 TO BUS 324102 CKT 1   /*7ALCALDE     345.0 - 7BROWN NORTH 345.0
 OPEN BRANCH FROM BUS 324100 TO BUS 324112 CKT 1   /*7ALCALDE     345.0 - 7PINEVILLE   345.0
 OPEN BRANCH FROM BUS 324100 TO BUS 324130 CKT 1   /*7ALCALDE     345.0 - 5ALCALDE     161.0
END
CONTINGENCY 'EKPC_P2-2_PULASKI 161_SRT-A'
 OPEN BUS 342787   /*5PULASK CO   161.0
 OPEN BUS 342790   /*5PULASK CO J 161.0
END
CONTINGENCY 'EKPC_P2-2_LIB JCT 161_SRT-A'
 OPEN BUS 342760   /*5LIBERTY J   161.0
END
CONTINGENCY 'DEOK_P4_1445_ZIMMER_SRT-A'
 OPEN BRANCH FROM BUS 249570 TO BUS 249577 CKT 1   /*08P.UNON     345.0 - 08ZIMER      345.0
 OPEN BRANCH FROM BUS 249581 TO BUS 249577 CKT 1   /*08MELDAL     345.0 - 08ZIMER      345.0
END
CONTINGENCY 'DEOK_P4_1449_ZIMMER_SRT-A'
 OPEN BRANCH FROM BUS 249581 TO BUS 249577 CKT 1   /*08MELDAL     345.0 - 08ZIMER      345.0
END
CONTINGENCY 'DEOK_P4_1373_PORTUNION_SRT-A'
 OPEN BRANCH FROM BUS 249570 TO BUS 249575 CKT 1   /*08P.UNON     345.0 - 08TERMNL     345.0
 OPEN BRANCH FROM BUS 249570 TO BUS 249577 CKT 1   /*08P.UNON     345.0 - 08ZIMER      345.0
END
CONTINGENCY 'DEOK_P4_1493_RED BANK_SRT-A'
 OPEN BRANCH FROM BUS 249571 TO BUS 250092 CKT 1   /*08REDBK1     345.0 - 08REDBK1     138.0
 OPEN BUS 249573                                   /*08SGROVE     345.0
END
CONTINGENCY 'DEOK_P4_1487_RED BANK_SRT-A'
 OPEN BRANCH FROM BUS 249571 TO BUS 250093 CKT 1   /*08REDBK1     345.0 - 08REDBK2     138.0
 OPEN BUS 249573                                   /*08SGROVE     345.0
END
CONTINGENCY 'DEOK_P_CIRCUIT1883&4545REDBANKSILGRVZIMMER_SRT-A'
 OPEN BUS 249573   /*08SGROVE     345.0
 OPEN BUS 250079   /*08NWTWN1     138.0
END
CONTINGENCY 'DEOK_P2.2_SILVER GROVE 345 BUS_SRT-A'
 OPEN BUS 249573   /*08SGROVE     345.0
END
CONTINGENCY 'EKPC_P2-2_MELD-SPUR 345_SRT-A'
 OPEN BRANCH FROM BUS 249581 TO BUS 342838 CKT 1   /*08MELDAL     345.0 - 7SPURLOCK    345.0
END
CONTINGENCY 'DEOK_P1_ZIMMER-MELDAHL 34576_SRT-A'
 OPEN BRANCH FROM BUS 249577 TO BUS 249581 CKT 1   /*08ZIMER      345.0 - 08MELDAL     345.0
END
CONTINGENCY 'DEOK_P1_RED BANK-SILVER GROVE-ZIMMER 4545_SRT-A'
 OPEN BUS 249573   /*08SGROVE     345.0
END
CONTINGENCY 'EKPC_P1-2_MCCR-WAYNE161_SRT-A'
 OPEN BRANCH FROM BUS 342478 TO BUS 342823 CKT 1   /*2WAYNE CO     69.0 - 5WAYNE CO    161.0
 OPEN BRANCH FROM BUS 342778 TO BUS 360486 CKT 1   /*5MCCREARY CO 161.0 - 5WAYNE CO KY 161.0
 OPEN BRANCH FROM BUS 342823 TO BUS 360486 CKT 1   /*5WAYNE CO    161.0 - 5WAYNE CO KY 161.0
 OPEN BRANCH FROM BUS 360448 TO BUS 360486 CKT 1   /*5WOLF CRK HP 161.0 - 5WAYNE CO KY 161.0
END
CONTINGENCY 'EKPC_P2-2_SUMMSHADE 161 #1_SRT-A'
 OPEN BRANCH FROM BUS 342322 TO BUS 342814 CKT 1   /*2SUMM SHADE   69.0 - 5SUMM SHADE  161.0
 OPEN BRANCH FROM BUS 342814 TO BUS 360334 CKT 1   /*5SUMM SHADE  161.0 - 5SUMMER SHAD 161.0
END
CONTINGENCY 'EKPC_P2-2_TVA WAYNE 161_SRT-A'
 OPEN BRANCH FROM BUS 342823 TO BUS 360486 CKT 1   /*5WAYNE CO    161.0 - 5WAYNE CO KY 161.0
END
CONTINGENCY 'EKPC_P1-2_COOP-DEN161_SRT-A-1'
 OPEN BRANCH FROM BUS 342718 TO BUS 972272 CKT 2   /*5COOPER2     161.0 - AH1-721 TP   161.0
END
CONTINGENCY 'EKPC_P2-3_LAURL S50-1014_SRT-A'
 OPEN BRANCH FROM BUS 341740 TO BUS 342754 CKT 1   /*2LAUREL CO    69.0 - 5LAUREL CO   161.0
 OPEN BRANCH FROM BUS 342754 TO BUS 342757 CKT 1   /*5LAUREL CO   161.0 - 5LAUREL DAM  161.0
END
CONTINGENCY 'EKPC_P4-5_LAURL S50-1014_SRT-A'
 OPEN BUS 342754   /*5LAUREL CO   161.0
END
CONTINGENCY 'EKPC_P1-2_COOP-LAUREL161_SRT-A-1'
 OPEN BRANCH FROM BUS 342718 TO BUS 972272 CKT 1   /*5COOPER2     161.0 - AH1-721 TP   161.0
END
247977 to 242524 ckt 17
242519 to 314912 ckt 1
242516 to 242920 ckt 1
248005 to 242528 ckt 1
341005 to 342283 ckt 1
341206 to 341347 ckt 1
341347 to 341344 ckt 1
341344 to 342286 ckt 1
341344 to 342286 ckt 2
341392 to 341206 ckt 1
342049 to 341491 ckt 1
342287 to 324531 ckt 1
342286 to 342287 ckt 1
342322 to 341431 ckt 1
342397 to 341005 ckt 1
342532 to 342478 ckt 1
342770 to 324271 ckt 1
342715 to 342790 ckt 1
342718 to 342715 ckt 1
342718 to 324141 ckt 1
342754 to 342781 ckt 1
342757 to 342754 ckt 1
342760 to 342703 ckt 1
342769 to 342770 ckt 1
342790 to 342760 ckt 1
342838 to 253077 ckt 1
966020 to 342532 ckt 1
971154 to 342049 ckt 1
971484 to 342397 ckt 1
971484 to 966020 ckt 1
972272 to 342718 ckt 1
972272 to 342718 ckt 2
972272 to 342757 ckt 1

Winter Peak Analysis

The New Service Request AH1-239 was evaluated as a 80.0 MW (48.0 MW Capacity) injection in the EKPC area.

AH1-239 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 80.0 MW (80.0 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2EKPC
2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC131.03 %86.0B112.690.31
GD2EKPC
2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC127.8 %86.0B109.910.28
GD2EKPC
2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC127.8 %86.0B109.910.28
GD2EKPC
2COOPER DIST-2COOPER 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC130.78 %86.0B112.470.31
GD2EKPC
2COOPER DIST-2COOPER 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC127.54 %86.0B109.690.28
GD2EKPC
2COOPER DIST-2COOPER 69.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC127.54 %86.0B109.690.28
GD2EKPC
2COOPER-2SOMERSET 69.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
TowerAC174.76 %89.0B155.530.23
GD2EKPC
2COOPER-2SOMERSET 69.0 kV Ckt 2 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
TowerAC174.76 %89.0B155.530.23
GD2EKPC
2DENNY-2BRONSTON T 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC168.51 %76.0B128.070.31
GD2EKPC
2DENNY-2BRONSTON T 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC163.97 %76.0B124.620.28
GD2EKPC
2DENNY-2BRONSTON T 69.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC163.97 %76.0B124.620.28
GD2EKPC/LGEE
2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
TowerAC157.64 %141.0B222.270.55
GD2EKPC/LGEE
2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line
EKPC_P1-2_COOP-ELIHU161_SRT-A
SingleAC102.43 %141.0B144.430.45
GD2EKPC/LGEE
2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line
EKPC_P2-2_ELIHU-COOP 161_SRT-A
BusAC102.42 %141.0B144.420.45
GD2EKPC/LGEE
2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
TowerAC102.11 %141.0B143.980.45
GD2EKPC
2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
TowerAC146.43 %156.0B228.420.48
IPDEKPC
2UPCHURCH T-2ALBANY 69.0 kV Ckt 1 line
EKPC_P1-2_AG1-471 TP-2ZULA J NO-69_SRT-A
SingleAC101.89 %73.0B74.3880.0
IPDEKPC
2UPCHURCH T-2ALBANY 69.0 kV Ckt 1 line
EKPC_P1-2_AG1-471 TP-AH1-239 TP-69_SRT-A
SingleAC101.89 %73.0B74.3880.0
GD2EKPC
5COOPER2-5COOPER1 161.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
TowerAC177.05 %501.0B887.010.33
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1014_SRT-A
BreakerAC227.22 %305.0B693.030.36
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1024_SRT-A
BreakerAC224.87 %305.0B685.840.35
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1008_SRT-A
BreakerAC224.7 %305.0B685.340.35
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P2-2_COOPER 1 161_SRT-A
BusAC224.7 %305.0B685.330.35
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P1-2_COOP 161 TIE_SRT-A
SingleAC224.26 %305.0B684.00.34
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P4-5_LAURL S50-1024_SRT-A
BreakerAC187.62 %305.0B572.240.77
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P2-3_LAURL S50-1024_SRT-A
BreakerAC187.61 %305.0B572.220.77
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P7-1_LAURL 161 DBL_SRT-A
TowerAC187.61 %305.0B572.220.77
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P1-2_LAUR-L DAM161_SRT-A
SingleAC187.19 %305.0B570.920.77
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P2-2_LAUR-LAURD161_SRT-A
BusAC187.19 %305.0B570.920.77
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P2-2_LAUREL CO 161_SRT-A
BusAC187.16 %305.0B570.830.77
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 1_SRT-A
TowerAC185.15 %305.0B564.710.45
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P2-2_COOP-LAURD 161_SRT-A
BusAC174.3 %305.0B531.610.77
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P2-2_PULASKI 161_SRT-A
BusAC168.53 %305.0B514.030.7
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Base Case
SingleAC152.65 %279.0A425.90.66
GD2EKPC
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC181.03 %334.0B604.630.35
GD2EKPC
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC179.96 %334.0B601.060.35
GD2EKPC
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC179.95 %334.0B601.050.35
IPDEKPC
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
EKPC_P1-2_AH1-239 TP-2UPCHURCH T-69_SRT-A
SingleAC112.0 %73.0B81.7680.0
IPDEKPC
AH1-239 TP-2UPCHURCH T 69.0 kV Ckt 1 line
EKPC_P1-2_AG1-471 TP-2ZULA J NO-69_SRT-A
SingleAC113.09 %73.0B82.5680.0
IPDEKPC
AH1-239 TP-2UPCHURCH T 69.0 kV Ckt 1 line
EKPC_P1-2_AG1-471 TP-AH1-239 TP-69_SRT-A
SingleAC113.08 %73.0B82.5580.0
IPDEKPC
AH1-239 TP-AG1-471 TP 69.0 kV Ckt 1 line
EKPC_P1-2_AH1-239 TP-2UPCHURCH T-69_SRT-A
SingleAC112.04 %73.0B81.7980.0
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
EKPC_P1-2_COOP-DEN161_SRT-A-1
SingleAC178.28 %334.0B595.450.23
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
EKPC_P1-2_LAUR-L DAM161_SRT-A
SingleAC123.67 %334.0B413.070.21
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
EKPC_P2-2_LAUR-LAURD161_SRT-A
BusAC123.67 %334.0B413.070.21
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
EKPC_P2-3_LAURL S50-1014_SRT-A
BreakerAC123.67 %334.0B413.070.21
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
EKPC_P4-5_LAURL S50-1014_SRT-A
BreakerAC123.67 %334.0B413.050.21
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
EKPC_P2-2_LAUREL CO 161_SRT-A
BusAC123.67 %334.0B413.050.21
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
EKPC_P7-1_LAURL 161 DBL_SRT-A
TowerAC123.59 %334.0B412.790.21
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
EKPC_P1-2_COOP-LAUREL161_SRT-A-1
SingleAC230.58 %258.0B594.910.23
GD2EKPC
AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC157.76 %334.0B526.90.35
GD2EKPC
AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC156.84 %334.0B523.850.35
GD2EKPC
AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC156.84 %334.0B523.850.35

Details for 2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:131.03 %
Rating:86.0 MVA
Rating Type:B
MVA to Mitigate:112.69
MW Contribution:0.31
Bus #Bus NameTypeMW Contribution
971485AH1-239 GEN
Solar/Wind Harmer
0.311
966021AG1-471 GEN
Solar/Wind Harmer
0.233
972273AH1-721 GEN
50/50
112.161
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.068
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.207
LAGNLTFEXP_LAGN->PJM
CLTF
0.303
G-007ALTFEXP_G-007A->PJM
CMTX
0.011
CPLELTFEXP_CPLE->PJM
CLTF
0.078
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.01
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.098
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.547
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.286
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.208
WECLTFEXP_WEC->PJM
CLTF
0.001
VFTLTFEXP_VFT->PJM
CMTX
0.029
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.086
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.542
MECLTFEXP_MEC->PJM
CLTF
0.058

Details for 2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:127.8 %
Rating:86.0 MVA
Rating Type:B
MVA to Mitigate:109.91
MW Contribution:0.28
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
0.386
971485AH1-239 GEN
Solar/Wind Harmer
0.284
966021AG1-471 GEN
Solar/Wind Harmer
0.216
972273AH1-721 GEN
50/50
119.476
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.074
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.24
LAGNLTFEXP_LAGN->PJM
CLTF
0.154
G-007ALTFEXP_G-007A->PJM
CMTX
0.016
CPLELTFEXP_CPLE->PJM
CLTF
0.059
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.021
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.343
MDUPJM->LTFIMP_MDU
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.455
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.209
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.108
VFTLTFEXP_VFT->PJM
CMTX
0.042
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.234

Details for 2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:127.8 %
Rating:86.0 MVA
Rating Type:B
MVA to Mitigate:109.91
MW Contribution:0.28
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
0.386
971485AH1-239 GEN
Solar/Wind Harmer
0.284
966021AG1-471 GEN
Solar/Wind Harmer
0.216
972273AH1-721 GEN
50/50
119.476
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.074
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.24
LAGNLTFEXP_LAGN->PJM
CLTF
0.154
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.209
G-007ALTFEXP_G-007A->PJM
CMTX
0.016
CPLELTFEXP_CPLE->PJM
CLTF
0.059
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.021
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.343
MDUPJM->LTFIMP_MDU
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.455
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.108
VFTLTFEXP_VFT->PJM
CMTX
0.042
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.234

Details for 2COOPER DIST-2COOPER 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER DIST-2COOPER 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:130.78 %
Rating:86.0 MVA
Rating Type:B
MVA to Mitigate:112.47
MW Contribution:0.31
Bus #Bus NameTypeMW Contribution
971485AH1-239 GEN
Solar/Wind Harmer
0.311
966021AG1-471 GEN
Solar/Wind Harmer
0.233
972273AH1-721 GEN
50/50
112.161
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.068
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.207
LAGNLTFEXP_LAGN->PJM
CLTF
0.303
G-007ALTFEXP_G-007A->PJM
CMTX
0.011
CPLELTFEXP_CPLE->PJM
CLTF
0.078
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.01
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.098
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.547
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.286
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.208
WECLTFEXP_WEC->PJM
CLTF
0.001
VFTLTFEXP_VFT->PJM
CMTX
0.029
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.086
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.542
MECLTFEXP_MEC->PJM
CLTF
0.058

Details for 2COOPER DIST-2COOPER 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER DIST-2COOPER 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:127.54 %
Rating:86.0 MVA
Rating Type:B
MVA to Mitigate:109.69
MW Contribution:0.28
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
0.386
971485AH1-239 GEN
Solar/Wind Harmer
0.284
966021AG1-471 GEN
Solar/Wind Harmer
0.216
972273AH1-721 GEN
50/50
119.476
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.074
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.24
LAGNLTFEXP_LAGN->PJM
CLTF
0.154
G-007ALTFEXP_G-007A->PJM
CMTX
0.016
CPLELTFEXP_CPLE->PJM
CLTF
0.059
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.021
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.343
MDUPJM->LTFIMP_MDU
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.455
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.209
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.108
VFTLTFEXP_VFT->PJM
CMTX
0.042
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.234

Details for 2COOPER DIST-2COOPER 69.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER DIST-2COOPER 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:127.54 %
Rating:86.0 MVA
Rating Type:B
MVA to Mitigate:109.69
MW Contribution:0.28
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
0.386
971485AH1-239 GEN
Solar/Wind Harmer
0.284
966021AG1-471 GEN
Solar/Wind Harmer
0.216
972273AH1-721 GEN
50/50
119.476
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.074
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.24
LAGNLTFEXP_LAGN->PJM
CLTF
0.154
G-007ALTFEXP_G-007A->PJM
CMTX
0.016
CPLELTFEXP_CPLE->PJM
CLTF
0.059
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.021
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.343
MDUPJM->LTFIMP_MDU
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.455
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.209
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.108
VFTLTFEXP_VFT->PJM
CMTX
0.042
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.234

Details for 2COOPER-2SOMERSET 69.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-2


Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER-2SOMERSET 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:174.76 %
Rating:89.0 MVA
Rating Type:B
MVA to Mitigate:155.53
MW Contribution:0.23
Bus #Bus NameTypeMW Contribution
971485AH1-239 GEN
Solar/Wind Harmer
0.232
966021AG1-471 GEN
Solar/Wind Harmer
0.169
3429031COOPER2 G
50/50
30.256
972273AH1-721 GEN
50/50
105.719
LAGNLTFEXP_LAGN->PJM
CLTF
0.476
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.272
CPLELTFEXP_CPLE->PJM
CLTF
0.069
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.351
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.331
TVALTFEXP_TVA->PJM
CLTF
0.316
NYPJM->LTFIMP_NY
CLTF
0.004
WECLTFEXP_WEC->PJM
CLTF
0.024
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.901
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.959
MECLTFEXP_MEC->PJM
CLTF
0.185
SIGELTFEXP_SIGE->PJM
CLTF
0.006

Details for 2COOPER-2SOMERSET 69.0 kV Ckt 2 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-2


Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER-2SOMERSET 69.0 kV Ckt 2 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:174.76 %
Rating:89.0 MVA
Rating Type:B
MVA to Mitigate:155.53
MW Contribution:0.23
Bus #Bus NameTypeMW Contribution
971485AH1-239 GEN
Solar/Wind Harmer
0.232
966021AG1-471 GEN
Solar/Wind Harmer
0.169
3429031COOPER2 G
50/50
30.256
972273AH1-721 GEN
50/50
105.719
LAGNLTFEXP_LAGN->PJM
CLTF
0.476
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.272
CPLELTFEXP_CPLE->PJM
CLTF
0.069
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.351
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.331
TVALTFEXP_TVA->PJM
CLTF
0.316
NYPJM->LTFIMP_NY
CLTF
0.004
WECLTFEXP_WEC->PJM
CLTF
0.024
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.901
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.959
MECLTFEXP_MEC->PJM
CLTF
0.185
SIGELTFEXP_SIGE->PJM
CLTF
0.006

Details for 2DENNY-2BRONSTON T 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
2DENNY-2BRONSTON T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:168.51 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:128.07
MW Contribution:0.31
Bus #Bus NameTypeMW Contribution
971485AH1-239 GEN
Solar/Wind Harmer
0.311
966021AG1-471 GEN
Solar/Wind Harmer
0.233
972273AH1-721 GEN
50/50
112.161
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.068
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.207
LAGNLTFEXP_LAGN->PJM
CLTF
0.303
G-007ALTFEXP_G-007A->PJM
CMTX
0.011
CPLELTFEXP_CPLE->PJM
CLTF
0.078
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.01
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.098
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.547
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.286
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.208
WECLTFEXP_WEC->PJM
CLTF
0.001
VFTLTFEXP_VFT->PJM
CMTX
0.029
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.086
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.542
MECLTFEXP_MEC->PJM
CLTF
0.058

Details for 2DENNY-2BRONSTON T 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
2DENNY-2BRONSTON T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:163.97 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:124.62
MW Contribution:0.28
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
0.386
971485AH1-239 GEN
Solar/Wind Harmer
0.284
966021AG1-471 GEN
Solar/Wind Harmer
0.216
972273AH1-721 GEN
50/50
119.476
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.074
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.24
LAGNLTFEXP_LAGN->PJM
CLTF
0.154
G-007ALTFEXP_G-007A->PJM
CMTX
0.016
CPLELTFEXP_CPLE->PJM
CLTF
0.059
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.021
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.343
MDUPJM->LTFIMP_MDU
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.455
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.209
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.108
VFTLTFEXP_VFT->PJM
CMTX
0.042
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.234

Details for 2DENNY-2BRONSTON T 69.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
2DENNY-2BRONSTON T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:163.97 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:124.62
MW Contribution:0.28
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
0.386
971485AH1-239 GEN
Solar/Wind Harmer
0.284
966021AG1-471 GEN
Solar/Wind Harmer
0.216
972273AH1-721 GEN
50/50
119.476
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.074
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.24
LAGNLTFEXP_LAGN->PJM
CLTF
0.154
G-007ALTFEXP_G-007A->PJM
CMTX
0.016
CPLELTFEXP_CPLE->PJM
CLTF
0.059
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.021
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.343
MDUPJM->LTFIMP_MDU
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.455
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.209
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.108
VFTLTFEXP_VFT->PJM
CMTX
0.042
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.234

Details for 2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-2


Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:157.64 %
Rating:141.0 MVA
Rating Type:B
MVA to Mitigate:222.27
MW Contribution:0.55
Bus #Bus NameTypeMW Contribution
965401AG1-405 GEN
Solar/Wind Harmer
0.926
971485AH1-239 GEN
Solar/Wind Harmer
0.549
964781AG1-341 GEN
Solar/Wind Harmer
0.421
966021AG1-471 GEN
Solar/Wind Harmer
0.387
3429031COOPER2 G
50/50
60.462
970273AG2-179 GEN
Solar/Wind Harmer
4.788
971081AG2-670 GEN
Solar/Wind Harmer
0.323
962241AG1-070 GEN
Solar/Wind Harmer
0.161
970273AG2-179 GEN
Solar/Wind Harmer
0.445
962251AG1-071 GEN
Solar/Wind Harmer
0.197
964901AG1-354 GEN
Solar/Wind Harmer
0.61
971821AH1-427 GEN
Solar/Wind Harmer
0.301
960741AF2-365 GEN
Solar/Wind Harmer
0.147
971155AH1-034 GEN
Solar/Wind Harmer
0.427
972273AH1-721 GEN
50/50
211.125
965411AG1-406 GEN
Solar/Wind Harmer
7.148
950011AG9-010
External Queue
0.42752912640571594
LAGNLTFEXP_LAGN->PJM
CLTF
1.29
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.532
CPLELTFEXP_CPLE->PJM
CLTF
0.124
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.75
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.643
TVALTFEXP_TVA->PJM
CLTF
0.855
NYPJM->LTFIMP_NY
CLTF
0.018
LGEELTFEXP_LGEE->PJM
CLTF
0.015
WECLTFEXP_WEC->PJM
CLTF
0.079
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.952
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.653
MECLTFEXP_MEC->PJM
CLTF
0.563
SIGELTFEXP_SIGE->PJM
CLTF
0.02

Details for 2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line l/o EKPC_P1-2_COOP-ELIHU161_SRT-A


Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_COOP-ELIHU161_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.43 %
Rating:141.0 MVA
Rating Type:B
MVA to Mitigate:144.43
MW Contribution:0.45
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
0.477
965401AG1-405 GEN
Solar/Wind Harmer
0.855
971485AH1-239 GEN
Solar/Wind Harmer
0.451
964781AG1-341 GEN
Solar/Wind Harmer
0.342
966021AG1-471 GEN
Solar/Wind Harmer
0.317
3429031COOPER2 G
50/50
45.658
970273AG2-179 GEN
Solar/Wind Harmer
4.225
970273AG2-179 GEN
Solar/Wind Harmer
0.392
962251AG1-071 GEN
Solar/Wind Harmer
0.161
971081AG2-670 GEN
Solar/Wind Harmer
0.261
962241AG1-070 GEN
Solar/Wind Harmer
0.131
964901AG1-354 GEN
Solar/Wind Harmer
0.495
971821AH1-427 GEN
Solar/Wind Harmer
0.284
971155AH1-034 GEN
Solar/Wind Harmer
0.352
972273AH1-721 GEN
50/50
158.747
965411AG1-406 GEN
Solar/Wind Harmer
6.604
950011AG9-010
External Queue
0.3483022153377533
LAGNLTFEXP_LAGN->PJM
CLTF
0.98
CPLELTFEXP_CPLE->PJM
CLTF
0.079
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.079
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.556
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.358
TVALTFEXP_TVA->PJM
CLTF
0.656
NYPJM->LTFIMP_NY
CLTF
0.019
WECLTFEXP_WEC->PJM
CLTF
0.058
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.167
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.003
MECLTFEXP_MEC->PJM
CLTF
0.421
SIGELTFEXP_SIGE->PJM
CLTF
0.014

Details for 2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line l/o EKPC_P2-2_ELIHU-COOP 161_SRT-A


Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_ELIHU-COOP 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:102.42 %
Rating:141.0 MVA
Rating Type:B
MVA to Mitigate:144.42
MW Contribution:0.45
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
0.477
965401AG1-405 GEN
Solar/Wind Harmer
0.855
971485AH1-239 GEN
Solar/Wind Harmer
0.451
964781AG1-341 GEN
Solar/Wind Harmer
0.342
966021AG1-471 GEN
Solar/Wind Harmer
0.317
3429031COOPER2 G
50/50
45.658
970273AG2-179 GEN
Solar/Wind Harmer
4.225
971081AG2-670 GEN
Solar/Wind Harmer
0.261
962241AG1-070 GEN
Solar/Wind Harmer
0.131
970273AG2-179 GEN
Solar/Wind Harmer
0.392
962251AG1-071 GEN
Solar/Wind Harmer
0.161
964901AG1-354 GEN
Solar/Wind Harmer
0.495
971821AH1-427 GEN
Solar/Wind Harmer
0.284
971155AH1-034 GEN
Solar/Wind Harmer
0.352
972273AH1-721 GEN
50/50
158.747
965411AG1-406 GEN
Solar/Wind Harmer
6.604
950011AG9-010
External Queue
0.3483022153377533
LAGNLTFEXP_LAGN->PJM
CLTF
0.98
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.358
CPLELTFEXP_CPLE->PJM
CLTF
0.079
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.079
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.556
TVALTFEXP_TVA->PJM
CLTF
0.656
NYPJM->LTFIMP_NY
CLTF
0.019
WECLTFEXP_WEC->PJM
CLTF
0.058
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.167
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.003
MECLTFEXP_MEC->PJM
CLTF
0.421
SIGELTFEXP_SIGE->PJM
CLTF
0.014

Details for 2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-1


Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:102.11 %
Rating:141.0 MVA
Rating Type:B
MVA to Mitigate:143.98
MW Contribution:0.45
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
0.475
965401AG1-405 GEN
Solar/Wind Harmer
0.856
971485AH1-239 GEN
Solar/Wind Harmer
0.451
966021AG1-471 GEN
Solar/Wind Harmer
0.317
3429031COOPER2 G
50/50
45.728
970273AG2-179 GEN
Solar/Wind Harmer
4.227
964781AG1-341 GEN
Solar/Wind Harmer
0.343
971081AG2-670 GEN
Solar/Wind Harmer
0.262
962241AG1-070 GEN
Solar/Wind Harmer
0.131
970273AG2-179 GEN
Solar/Wind Harmer
0.392
962251AG1-071 GEN
Solar/Wind Harmer
0.161
964901AG1-354 GEN
Solar/Wind Harmer
0.496
971821AH1-427 GEN
Solar/Wind Harmer
0.284
971155AH1-034 GEN
Solar/Wind Harmer
0.352
972273AH1-721 GEN
50/50
158.188
965411AG1-406 GEN
Solar/Wind Harmer
6.606
950011AG9-010
External Queue
0.3486476242542267
LAGNLTFEXP_LAGN->PJM
CLTF
0.981
CPLELTFEXP_CPLE->PJM
CLTF
0.079
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.084
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.556
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.358
TVALTFEXP_TVA->PJM
CLTF
0.656
NYPJM->LTFIMP_NY
CLTF
0.019
WECLTFEXP_WEC->PJM
CLTF
0.058
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.17
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.004
MECLTFEXP_MEC->PJM
CLTF
0.421
SIGELTFEXP_SIGE->PJM
CLTF
0.014

Details for 2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-2


Base Case Flowgate

Area:EKPC
Facility Description:
2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:146.43 %
Rating:156.0 MVA
Rating Type:B
MVA to Mitigate:228.42
MW Contribution:0.48
Bus #Bus NameTypeMW Contribution
965401AG1-405 GEN
Solar/Wind Harmer
1.023
971485AH1-239 GEN
Solar/Wind Harmer
0.479
964781AG1-341 GEN
Solar/Wind Harmer
0.332
966021AG1-471 GEN
Solar/Wind Harmer
0.34
3429031COOPER2 G
50/50
61.828
970273AG2-179 GEN
Solar/Wind Harmer
3.35
971081AG2-670 GEN
Solar/Wind Harmer
0.293
962241AG1-070 GEN
Solar/Wind Harmer
0.128
970273AG2-179 GEN
Solar/Wind Harmer
0.311
962251AG1-071 GEN
Solar/Wind Harmer
0.156
964901AG1-354 GEN
Solar/Wind Harmer
0.508
971821AH1-427 GEN
Solar/Wind Harmer
0.307
971155AH1-034 GEN
Solar/Wind Harmer
0.337
972273AH1-721 GEN
50/50
215.903
965411AG1-406 GEN
Solar/Wind Harmer
7.893
950011AG9-010
External Queue
0.41379016637802124
LAGNLTFEXP_LAGN->PJM
CLTF
0.996
CPLELTFEXP_CPLE->PJM
CLTF
0.08
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.329
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.401
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.361
TVALTFEXP_TVA->PJM
CLTF
0.656
NYPJM->LTFIMP_NY
CLTF
0.017
LGEELTFEXP_LGEE->PJM
CLTF
0.034
WECLTFEXP_WEC->PJM
CLTF
0.065
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.427
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.057
MECLTFEXP_MEC->PJM
CLTF
0.452
SIGELTFEXP_SIGE->PJM
CLTF
0.017

Details for [AH1-239] 2UPCHURCH T-2ALBANY 69.0 kV Ckt 1 line l/o EKPC_P1-2_AG1-471 TP-2ZULA J NO-69_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
2UPCHURCH T-2ALBANY 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_AG1-471 TP-2ZULA J NO-69_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.89 %
Rating:73.0 MVA
Rating Type:B
MVA to Mitigate:74.38
MW Contribution:80.0
IPD Plant:AH1-239
Bus #Bus NameTypeMW Contribution
971485AH1-239 GEN
PJM_IPD
80

Details for [AH1-239] 2UPCHURCH T-2ALBANY 69.0 kV Ckt 1 line l/o EKPC_P1-2_AG1-471 TP-AH1-239 TP-69_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
2UPCHURCH T-2ALBANY 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_AG1-471 TP-AH1-239 TP-69_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.89 %
Rating:73.0 MVA
Rating Type:B
MVA to Mitigate:74.38
MW Contribution:80.0
IPD Plant:AH1-239
Bus #Bus NameTypeMW Contribution
971485AH1-239 GEN
PJM_IPD
80

Details for 5COOPER2-5COOPER1 161.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-2


Base Case Flowgate

Area:EKPC
Facility Description:
5COOPER2-5COOPER1 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:177.05 %
Rating:501.0 MVA
Rating Type:B
MVA to Mitigate:887.01
MW Contribution:0.33
Bus #Bus NameTypeMW Contribution
971485AH1-239 GEN
Solar/Wind Harmer
0.329
966021AG1-471 GEN
Solar/Wind Harmer
0.25
3429031COOPER2 G
50/50
200.23
972273AH1-721 GEN
50/50
697.677
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.069
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.226
LAGNLTFEXP_LAGN->PJM
CLTF
0.191
G-007ALTFEXP_G-007A->PJM
CMTX
0.031
CPLELTFEXP_CPLE->PJM
CLTF
0.077
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.05
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.506
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.488
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.271
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.128
VFTLTFEXP_VFT->PJM
CMTX
0.083
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.306
MECLTFEXP_MEC->PJM
CLTF
0.009

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1014_SRT-A


Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:227.22 %
Rating:305.0 MVA
Rating Type:B
MVA to Mitigate:693.03
MW Contribution:0.36
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
1.861
971485AH1-239 GEN
Solar/Wind Harmer
0.36
966021AG1-471 GEN
Solar/Wind Harmer
0.269
3429031COOPER2 G
50/50
166.522
972273AH1-721 GEN
50/50
577.836
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.142
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.438
LAGNLTFEXP_LAGN->PJM
CLTF
0.299
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.209
CPLELTFEXP_CPLE->PJM
CLTF
0.052
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.85
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.791
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.223
NYPJM->LTFIMP_NY
CLTF
0.009
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.486
MECLTFEXP_MEC->PJM
CLTF
0.023

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1024_SRT-A


Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1024_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:224.87 %
Rating:305.0 MVA
Rating Type:B
MVA to Mitigate:685.84
MW Contribution:0.35
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
1.865
971485AH1-239 GEN
Solar/Wind Harmer
0.348
966021AG1-471 GEN
Solar/Wind Harmer
0.259
3429031COOPER2 G
50/50
166.838
972273AH1-721 GEN
50/50
578.936
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.135
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.418
LAGNLTFEXP_LAGN->PJM
CLTF
0.251
CPLELTFEXP_CPLE->PJM
CLTF
0.041
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.659
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.714
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.166
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.189
NYPJM->LTFIMP_NY
CLTF
0.009
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.391
MECLTFEXP_MEC->PJM
CLTF
0.011

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1008_SRT-A


Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1008_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:224.7 %
Rating:305.0 MVA
Rating Type:B
MVA to Mitigate:685.34
MW Contribution:0.35
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
1.869
971485AH1-239 GEN
Solar/Wind Harmer
0.348
966021AG1-471 GEN
Solar/Wind Harmer
0.259
3429031COOPER2 G
50/50
167.08
972273AH1-721 GEN
50/50
579.779
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.138
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.43
LAGNLTFEXP_LAGN->PJM
CLTF
0.246
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.169
CPLELTFEXP_CPLE->PJM
CLTF
0.041
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.614
MDUPJM->LTFIMP_MDU
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.728
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.186
NYPJM->LTFIMP_NY
CLTF
0.009
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.379
MECLTFEXP_MEC->PJM
CLTF
0.007

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 1 161_SRT-A


Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 1 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:224.7 %
Rating:305.0 MVA
Rating Type:B
MVA to Mitigate:685.33
MW Contribution:0.35
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
1.869
971485AH1-239 GEN
Solar/Wind Harmer
0.348
966021AG1-471 GEN
Solar/Wind Harmer
0.259
3429031COOPER2 G
50/50
167.08
972273AH1-721 GEN
50/50
579.779
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.138
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.43
LAGNLTFEXP_LAGN->PJM
CLTF
0.246
CPLELTFEXP_CPLE->PJM
CLTF
0.041
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.614
MDUPJM->LTFIMP_MDU
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.728
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.169
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.186
NYPJM->LTFIMP_NY
CLTF
0.009
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.379
MECLTFEXP_MEC->PJM
CLTF
0.007

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P1-2_COOP 161 TIE_SRT-A


Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_COOP 161 TIE_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:224.26 %
Rating:305.0 MVA
Rating Type:B
MVA to Mitigate:684.0
MW Contribution:0.34
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
1.876
971485AH1-239 GEN
Solar/Wind Harmer
0.337
966021AG1-471 GEN
Solar/Wind Harmer
0.252
3429031COOPER2 G
50/50
167.627
972273AH1-721 GEN
50/50
581.685
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.136
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.426
LAGNLTFEXP_LAGN->PJM
CLTF
0.196
CPLELTFEXP_CPLE->PJM
CLTF
0.032
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.387
MDUPJM->LTFIMP_MDU
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.674
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.134
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.152
NYPJM->LTFIMP_NY
CLTF
0.009
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.278

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P4-5_LAURL S50-1024_SRT-A


Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P4-5_LAURL S50-1024_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:187.62 %
Rating:305.0 MVA
Rating Type:B
MVA to Mitigate:572.24
MW Contribution:0.77
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
2.117
965401AG1-405 GEN
Solar/Wind Harmer
0.448
971485AH1-239 GEN
Solar/Wind Harmer
0.77
964781AG1-341 GEN
Solar/Wind Harmer
0.61
966021AG1-471 GEN
Solar/Wind Harmer
0.545
3429031COOPER2 G
50/50
124.578
970273AG2-179 GEN
Solar/Wind Harmer
3.856
970653AG2-424 GEN
Solar/Wind Harmer
0.158
970653AG2-424 GEN
Solar/Wind Harmer
0.979
971081AG2-670 GEN
Solar/Wind Harmer
0.486
962241AG1-070 GEN
Solar/Wind Harmer
0.228
970273AG2-179 GEN
Solar/Wind Harmer
0.358
962251AG1-071 GEN
Solar/Wind Harmer
0.279
964901AG1-354 GEN
Solar/Wind Harmer
0.896
971821AH1-427 GEN
Solar/Wind Harmer
0.359
960741AF2-365 GEN
Solar/Wind Harmer
0.212
971155AH1-034 GEN
Solar/Wind Harmer
0.575
972273AH1-721 GEN
50/50
434.406
965411AG1-406 GEN
Solar/Wind Harmer
3.46
950011AG9-010
External Queue
0.661795973777771
LAGNLTFEXP_LAGN->PJM
CLTF
1.92
CPLELTFEXP_CPLE->PJM
CLTF
0.195
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.8
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.093
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.842
TVALTFEXP_TVA->PJM
CLTF
1.284
NYPJM->LTFIMP_NY
CLTF
0.039
WECLTFEXP_WEC->PJM
CLTF
0.104
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.897
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.932
MECLTFEXP_MEC->PJM
CLTF
0.788
SIGELTFEXP_SIGE->PJM
CLTF
0.027

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P2-3_LAURL S50-1024_SRT-A


Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_LAURL S50-1024_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:187.61 %
Rating:305.0 MVA
Rating Type:B
MVA to Mitigate:572.22
MW Contribution:0.77
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
2.117
965401AG1-405 GEN
Solar/Wind Harmer
0.448
971485AH1-239 GEN
Solar/Wind Harmer
0.77
964781AG1-341 GEN
Solar/Wind Harmer
0.61
966021AG1-471 GEN
Solar/Wind Harmer
0.545
3429031COOPER2 G
50/50
124.578
970273AG2-179 GEN
Solar/Wind Harmer
3.856
970653AG2-424 GEN
Solar/Wind Harmer
0.158
970653AG2-424 GEN
Solar/Wind Harmer
0.979
971081AG2-670 GEN
Solar/Wind Harmer
0.486
962241AG1-070 GEN
Solar/Wind Harmer
0.228
970273AG2-179 GEN
Solar/Wind Harmer
0.358
962251AG1-071 GEN
Solar/Wind Harmer
0.279
964901AG1-354 GEN
Solar/Wind Harmer
0.896
971821AH1-427 GEN
Solar/Wind Harmer
0.359
960741AF2-365 GEN
Solar/Wind Harmer
0.212
971155AH1-034 GEN
Solar/Wind Harmer
0.575
972273AH1-721 GEN
50/50
434.406
965411AG1-406 GEN
Solar/Wind Harmer
3.46
950011AG9-010
External Queue
0.661795973777771
LAGNLTFEXP_LAGN->PJM
CLTF
1.92
CPLELTFEXP_CPLE->PJM
CLTF
0.195
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.8
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.093
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.842
TVALTFEXP_TVA->PJM
CLTF
1.284
NYPJM->LTFIMP_NY
CLTF
0.039
WECLTFEXP_WEC->PJM
CLTF
0.104
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.897
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.932
MECLTFEXP_MEC->PJM
CLTF
0.788
SIGELTFEXP_SIGE->PJM
CLTF
0.027

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P7-1_LAURL 161 DBL_SRT-A


Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_LAURL 161 DBL_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:187.61 %
Rating:305.0 MVA
Rating Type:B
MVA to Mitigate:572.22
MW Contribution:0.77
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
2.117
965401AG1-405 GEN
Solar/Wind Harmer
0.448
971485AH1-239 GEN
Solar/Wind Harmer
0.77
964781AG1-341 GEN
Solar/Wind Harmer
0.61
966021AG1-471 GEN
Solar/Wind Harmer
0.545
3429031COOPER2 G
50/50
124.578
970273AG2-179 GEN
Solar/Wind Harmer
3.856
970653AG2-424 GEN
Solar/Wind Harmer
0.158
970653AG2-424 GEN
Solar/Wind Harmer
0.979
971081AG2-670 GEN
Solar/Wind Harmer
0.486
962241AG1-070 GEN
Solar/Wind Harmer
0.228
970273AG2-179 GEN
Solar/Wind Harmer
0.358
962251AG1-071 GEN
Solar/Wind Harmer
0.279
964901AG1-354 GEN
Solar/Wind Harmer
0.896
971821AH1-427 GEN
Solar/Wind Harmer
0.359
960741AF2-365 GEN
Solar/Wind Harmer
0.212
971155AH1-034 GEN
Solar/Wind Harmer
0.575
972273AH1-721 GEN
50/50
434.406
965411AG1-406 GEN
Solar/Wind Harmer
3.46
950011AG9-010
External Queue
0.661795973777771
LAGNLTFEXP_LAGN->PJM
CLTF
1.92
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.842
CPLELTFEXP_CPLE->PJM
CLTF
0.195
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.8
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.093
TVALTFEXP_TVA->PJM
CLTF
1.284
NYPJM->LTFIMP_NY
CLTF
0.039
WECLTFEXP_WEC->PJM
CLTF
0.104
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.897
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.932
MECLTFEXP_MEC->PJM
CLTF
0.788
SIGELTFEXP_SIGE->PJM
CLTF
0.027

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P1-2_LAUR-L DAM161_SRT-A


Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_LAUR-L DAM161_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:187.19 %
Rating:305.0 MVA
Rating Type:B
MVA to Mitigate:570.92
MW Contribution:0.77
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
2.12
965401AG1-405 GEN
Solar/Wind Harmer
0.449
971485AH1-239 GEN
Solar/Wind Harmer
0.773
964781AG1-341 GEN
Solar/Wind Harmer
0.612
966021AG1-471 GEN
Solar/Wind Harmer
0.546
3429031COOPER2 G
50/50
124.796
970273AG2-179 GEN
Solar/Wind Harmer
3.87
970653AG2-424 GEN
Solar/Wind Harmer
0.158
970653AG2-424 GEN
Solar/Wind Harmer
0.982
970273AG2-179 GEN
Solar/Wind Harmer
0.359
962251AG1-071 GEN
Solar/Wind Harmer
0.28
971081AG2-670 GEN
Solar/Wind Harmer
0.487
962241AG1-070 GEN
Solar/Wind Harmer
0.229
964901AG1-354 GEN
Solar/Wind Harmer
0.899
971821AH1-427 GEN
Solar/Wind Harmer
0.364
960741AF2-365 GEN
Solar/Wind Harmer
0.213
971155AH1-034 GEN
Solar/Wind Harmer
0.577
972273AH1-721 GEN
50/50
435.166
965411AG1-406 GEN
Solar/Wind Harmer
3.469
950011AG9-010
External Queue
0.6634885668754578
LAGNLTFEXP_LAGN->PJM
CLTF
1.942
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.865
CPLELTFEXP_CPLE->PJM
CLTF
0.201
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.896
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.112
TVALTFEXP_TVA->PJM
CLTF
1.298
NYPJM->LTFIMP_NY
CLTF
0.038
WECLTFEXP_WEC->PJM
CLTF
0.105
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.92
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.975
MECLTFEXP_MEC->PJM
CLTF
0.795
SIGELTFEXP_SIGE->PJM
CLTF
0.028

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P2-2_LAUR-LAURD161_SRT-A


Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_LAUR-LAURD161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:187.19 %
Rating:305.0 MVA
Rating Type:B
MVA to Mitigate:570.92
MW Contribution:0.77
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
2.12
965401AG1-405 GEN
Solar/Wind Harmer
0.449
971485AH1-239 GEN
Solar/Wind Harmer
0.773
964781AG1-341 GEN
Solar/Wind Harmer
0.612
966021AG1-471 GEN
Solar/Wind Harmer
0.546
3429031COOPER2 G
50/50
124.796
970273AG2-179 GEN
Solar/Wind Harmer
3.87
970653AG2-424 GEN
Solar/Wind Harmer
0.158
970653AG2-424 GEN
Solar/Wind Harmer
0.982
971081AG2-670 GEN
Solar/Wind Harmer
0.487
962241AG1-070 GEN
Solar/Wind Harmer
0.229
970273AG2-179 GEN
Solar/Wind Harmer
0.359
962251AG1-071 GEN
Solar/Wind Harmer
0.28
964901AG1-354 GEN
Solar/Wind Harmer
0.899
971821AH1-427 GEN
Solar/Wind Harmer
0.364
960741AF2-365 GEN
Solar/Wind Harmer
0.213
971155AH1-034 GEN
Solar/Wind Harmer
0.577
972273AH1-721 GEN
50/50
435.166
965411AG1-406 GEN
Solar/Wind Harmer
3.469
950011AG9-010
External Queue
0.6634885668754578
LAGNLTFEXP_LAGN->PJM
CLTF
1.942
CPLELTFEXP_CPLE->PJM
CLTF
0.201
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.896
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.112
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.865
TVALTFEXP_TVA->PJM
CLTF
1.298
NYPJM->LTFIMP_NY
CLTF
0.038
WECLTFEXP_WEC->PJM
CLTF
0.105
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.92
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.975
MECLTFEXP_MEC->PJM
CLTF
0.795
SIGELTFEXP_SIGE->PJM
CLTF
0.028

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P2-2_LAUREL CO 161_SRT-A


Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_LAUREL CO 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:187.16 %
Rating:305.0 MVA
Rating Type:B
MVA to Mitigate:570.83
MW Contribution:0.77
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
2.119
965401AG1-405 GEN
Solar/Wind Harmer
0.449
971485AH1-239 GEN
Solar/Wind Harmer
0.772
964781AG1-341 GEN
Solar/Wind Harmer
0.611
966021AG1-471 GEN
Solar/Wind Harmer
0.545
3429031COOPER2 G
50/50
124.685
970273AG2-179 GEN
Solar/Wind Harmer
3.864
970653AG2-424 GEN
Solar/Wind Harmer
0.158
970653AG2-424 GEN
Solar/Wind Harmer
0.981
971081AG2-670 GEN
Solar/Wind Harmer
0.487
962241AG1-070 GEN
Solar/Wind Harmer
0.228
970273AG2-179 GEN
Solar/Wind Harmer
0.359
962251AG1-071 GEN
Solar/Wind Harmer
0.279
964901AG1-354 GEN
Solar/Wind Harmer
0.898
971821AH1-427 GEN
Solar/Wind Harmer
0.364
960741AF2-365 GEN
Solar/Wind Harmer
0.213
971155AH1-034 GEN
Solar/Wind Harmer
0.576
972273AH1-721 GEN
50/50
434.778
965411AG1-406 GEN
Solar/Wind Harmer
3.465
950011AG9-010
External Queue
0.662796139717102
LAGNLTFEXP_LAGN->PJM
CLTF
1.931
CPLELTFEXP_CPLE->PJM
CLTF
0.198
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.851
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.102
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.854
TVALTFEXP_TVA->PJM
CLTF
1.291
NYPJM->LTFIMP_NY
CLTF
0.038
WECLTFEXP_WEC->PJM
CLTF
0.104
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.91
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.955
MECLTFEXP_MEC->PJM
CLTF
0.792
SIGELTFEXP_SIGE->PJM
CLTF
0.027

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 1_SRT-A


Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 1_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:185.15 %
Rating:305.0 MVA
Rating Type:B
MVA to Mitigate:564.71
MW Contribution:0.45
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
1.662
965401AG1-405 GEN
Solar/Wind Harmer
0.301
971485AH1-239 GEN
Solar/Wind Harmer
0.451
966021AG1-471 GEN
Solar/Wind Harmer
0.331
3429031COOPER2 G
50/50
148.683
970273AG2-179 GEN
Solar/Wind Harmer
1.671
970273AG2-179 GEN
Solar/Wind Harmer
0.155
972273AH1-721 GEN
50/50
516.216
965411AG1-406 GEN
Solar/Wind Harmer
2.325
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.12
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.354
LAGNLTFEXP_LAGN->PJM
CLTF
0.48
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.268
CPLELTFEXP_CPLE->PJM
CLTF
0.065
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.859
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.831
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.339
NYPJM->LTFIMP_NY
CLTF
0.011
WECLTFEXP_WEC->PJM
CLTF
0.005
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.248
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.86
MECLTFEXP_MEC->PJM
CLTF
0.112

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P2-2_COOP-LAURD 161_SRT-A


Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOP-LAURD 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:174.3 %
Rating:305.0 MVA
Rating Type:B
MVA to Mitigate:531.61
MW Contribution:0.77
Bus #Bus NameTypeMW Contribution
965401AG1-405 GEN
Solar/Wind Harmer
0.45
971485AH1-239 GEN
Solar/Wind Harmer
0.774
964781AG1-341 GEN
Solar/Wind Harmer
0.614
966021AG1-471 GEN
Solar/Wind Harmer
0.547
3429031COOPER2 G
50/50
124.856
970273AG2-179 GEN
Solar/Wind Harmer
3.876
970653AG2-424 GEN
Solar/Wind Harmer
0.159
970653AG2-424 GEN
Solar/Wind Harmer
0.986
971081AG2-670 GEN
Solar/Wind Harmer
0.488
962241AG1-070 GEN
Solar/Wind Harmer
0.229
970273AG2-179 GEN
Solar/Wind Harmer
0.36
962251AG1-071 GEN
Solar/Wind Harmer
0.28
964901AG1-354 GEN
Solar/Wind Harmer
0.901
971821AH1-427 GEN
Solar/Wind Harmer
0.366
960741AF2-365 GEN
Solar/Wind Harmer
0.214
971155AH1-034 GEN
Solar/Wind Harmer
0.578
972273AH1-721 GEN
50/50
435.377
965411AG1-406 GEN
Solar/Wind Harmer
3.475
950011AG9-010
External Queue
0.6634885668754578
LAGNLTFEXP_LAGN->PJM
CLTF
1.989
CPLELTFEXP_CPLE->PJM
CLTF
0.227
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.208
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.112
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.935
TVALTFEXP_TVA->PJM
CLTF
1.321
NYPJM->LTFIMP_NY
CLTF
0.024
WECLTFEXP_WEC->PJM
CLTF
0.113
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.258
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.063
MECLTFEXP_MEC->PJM
CLTF
0.833
SIGELTFEXP_SIGE->PJM
CLTF
0.029

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P2-2_PULASKI 161_SRT-A


Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_PULASKI 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:168.53 %
Rating:305.0 MVA
Rating Type:B
MVA to Mitigate:514.03
MW Contribution:0.7
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
1.354
965401AG1-405 GEN
Solar/Wind Harmer
0.152
971485AH1-239 GEN
Solar/Wind Harmer
0.702
964781AG1-341 GEN
Solar/Wind Harmer
0.475
966021AG1-471 GEN
Solar/Wind Harmer
0.503
3429031COOPER2 G
50/50
123.916
970273AG2-179 GEN
Solar/Wind Harmer
2.664
971081AG2-670 GEN
Solar/Wind Harmer
0.199
962241AG1-070 GEN
Solar/Wind Harmer
0.17
970273AG2-179 GEN
Solar/Wind Harmer
0.247
962251AG1-071 GEN
Solar/Wind Harmer
0.208
964901AG1-354 GEN
Solar/Wind Harmer
0.571
960741AF2-365 GEN
Solar/Wind Harmer
0.137
971155AH1-034 GEN
Solar/Wind Harmer
0.434
972273AH1-721 GEN
50/50
430.203
965411AG1-406 GEN
Solar/Wind Harmer
1.175
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.108
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.239
LAGNLTFEXP_LAGN->PJM
CLTF
1.596
CPLELTFEXP_CPLE->PJM
CLTF
0.235
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.283
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.718
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.927
TVALTFEXP_TVA->PJM
CLTF
1.095
NYPJM->LTFIMP_NY
CLTF
0.017
WECLTFEXP_WEC->PJM
CLTF
0.058
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.292
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.138
MECLTFEXP_MEC->PJM
CLTF
0.536
SIGELTFEXP_SIGE->PJM
CLTF
0.009

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:152.65 %
Rating:279.0 MVA
Rating Type:A
MVA to Mitigate:425.9
MW Contribution:0.66
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
1.175
965401AG1-405 GEN
Solar/Wind Harmer
0.353
971485AH1-239 GEN
Solar/Wind Harmer
0.659
964781AG1-341 GEN
Solar/Wind Harmer
0.521
966021AG1-471 GEN
Solar/Wind Harmer
0.466
3429031COOPER2 G
50/50
108.658
970273AG2-179 GEN
Solar/Wind Harmer
3.141
970653AG2-424 GEN
Solar/Wind Harmer
0.133
970653AG2-424 GEN
Solar/Wind Harmer
0.828
970273AG2-179 GEN
Solar/Wind Harmer
0.292
962251AG1-071 GEN
Solar/Wind Harmer
0.237
971081AG2-670 GEN
Solar/Wind Harmer
0.417
962241AG1-070 GEN
Solar/Wind Harmer
0.194
964901AG1-354 GEN
Solar/Wind Harmer
0.767
971821AH1-427 GEN
Solar/Wind Harmer
0.378
960741AF2-365 GEN
Solar/Wind Harmer
0.18
971155AH1-034 GEN
Solar/Wind Harmer
0.489
972273AH1-721 GEN
50/50
377.206
965411AG1-406 GEN
Solar/Wind Harmer
2.728
950011AG9-010
External Queue
0.5761643052101135
LAGNLTFEXP_LAGN->PJM
CLTF
1.566
CPLELTFEXP_CPLE->PJM
CLTF
0.157
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.854
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.069
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.672
TVALTFEXP_TVA->PJM
CLTF
1.054
NYPJM->LTFIMP_NY
CLTF
0.027
WECLTFEXP_WEC->PJM
CLTF
0.081
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.08
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.158
MECLTFEXP_MEC->PJM
CLTF
0.629
SIGELTFEXP_SIGE->PJM
CLTF
0.019

Details for 5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:181.03 %
Rating:334.0 MVA
Rating Type:B
MVA to Mitigate:604.63
MW Contribution:0.35
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
2.879
971485AH1-239 GEN
Solar/Wind Harmer
0.35
966021AG1-471 GEN
Solar/Wind Harmer
0.258
972273AH1-721 GEN
50/50
494.632
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.007
LAGNLTFEXP_LAGN->PJM
CLTF
0.519
CPLELTFEXP_CPLE->PJM
CLTF
0.077
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.363
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.45
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.327
TVALTFEXP_TVA->PJM
CLTF
0.35
NYPJM->LTFIMP_NY
CLTF
0.021
WECLTFEXP_WEC->PJM
CLTF
0.014
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.537
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.049
MECLTFEXP_MEC->PJM
CLTF
0.158
SIGELTFEXP_SIGE->PJM
CLTF
0.004

Details for 5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:179.96 %
Rating:334.0 MVA
Rating Type:B
MVA to Mitigate:601.06
MW Contribution:0.35
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
2.873
971485AH1-239 GEN
Solar/Wind Harmer
0.348
966021AG1-471 GEN
Solar/Wind Harmer
0.256
972273AH1-721 GEN
50/50
492.76
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.001
LAGNLTFEXP_LAGN->PJM
CLTF
0.525
CPLELTFEXP_CPLE->PJM
CLTF
0.074
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.427
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.424
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.318
TVALTFEXP_TVA->PJM
CLTF
0.353
NYPJM->LTFIMP_NY
CLTF
0.021
WECLTFEXP_WEC->PJM
CLTF
0.016
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.589
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.065
MECLTFEXP_MEC->PJM
CLTF
0.165
SIGELTFEXP_SIGE->PJM
CLTF
0.005

Details for 5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:179.95 %
Rating:334.0 MVA
Rating Type:B
MVA to Mitigate:601.05
MW Contribution:0.35
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
2.873
971485AH1-239 GEN
Solar/Wind Harmer
0.348
966021AG1-471 GEN
Solar/Wind Harmer
0.256
972273AH1-721 GEN
50/50
492.76
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.001
LAGNLTFEXP_LAGN->PJM
CLTF
0.525
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.318
CPLELTFEXP_CPLE->PJM
CLTF
0.074
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.427
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.424
TVALTFEXP_TVA->PJM
CLTF
0.353
NYPJM->LTFIMP_NY
CLTF
0.021
WECLTFEXP_WEC->PJM
CLTF
0.016
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.589
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.065
MECLTFEXP_MEC->PJM
CLTF
0.165
SIGELTFEXP_SIGE->PJM
CLTF
0.005

Details for [AH1-239] AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line l/o EKPC_P1-2_AH1-239 TP-2UPCHURCH T-69_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_AH1-239 TP-2UPCHURCH T-69_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:112.0 %
Rating:73.0 MVA
Rating Type:B
MVA to Mitigate:81.76
MW Contribution:80.0
IPD Plant:AH1-239
Bus #Bus NameTypeMW Contribution
971485AH1-239 GEN
PJM_IPD
80

Details for [AH1-239] AH1-239 TP-2UPCHURCH T 69.0 kV Ckt 1 line l/o EKPC_P1-2_AG1-471 TP-2ZULA J NO-69_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
AH1-239 TP-2UPCHURCH T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_AG1-471 TP-2ZULA J NO-69_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.09 %
Rating:73.0 MVA
Rating Type:B
MVA to Mitigate:82.56
MW Contribution:80.0
IPD Plant:AH1-239
Bus #Bus NameTypeMW Contribution
971485AH1-239 GEN
PJM_IPD
80

Details for [AH1-239] AH1-239 TP-2UPCHURCH T 69.0 kV Ckt 1 line l/o EKPC_P1-2_AG1-471 TP-AH1-239 TP-69_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
AH1-239 TP-2UPCHURCH T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_AG1-471 TP-AH1-239 TP-69_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.08 %
Rating:73.0 MVA
Rating Type:B
MVA to Mitigate:82.55
MW Contribution:80.0
IPD Plant:AH1-239
Bus #Bus NameTypeMW Contribution
971485AH1-239 GEN
PJM_IPD
80

Details for [AH1-239] AH1-239 TP-AG1-471 TP 69.0 kV Ckt 1 line l/o EKPC_P1-2_AH1-239 TP-2UPCHURCH T-69_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
AH1-239 TP-AG1-471 TP 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_AH1-239 TP-2UPCHURCH T-69_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:112.04 %
Rating:73.0 MVA
Rating Type:B
MVA to Mitigate:81.79
MW Contribution:80.0
IPD Plant:AH1-239
Bus #Bus NameTypeMW Contribution
971485AH1-239 GEN
PJM_IPD
80

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line l/o EKPC_P1-2_COOP-DEN161_SRT-A-1


Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_COOP-DEN161_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:178.28 %
Rating:334.0 MVA
Rating Type:B
MVA to Mitigate:595.45
MW Contribution:0.23
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
2.104
971485AH1-239 GEN
Solar/Wind Harmer
0.226
966021AG1-471 GEN
Solar/Wind Harmer
0.178
339231AF1-038_GEN
Solar/Wind Helper
0.161
972273AH1-721 GEN
50/50
648.068
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.185
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.623
MDUPJM->LTFIMP_MDU
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.536
GibsonPJM->LTFIMP_GIBSON
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.003
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.008
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.005
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.525

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line l/o EKPC_P1-2_LAUR-L DAM161_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_LAUR-L DAM161_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:123.67 %
Rating:334.0 MVA
Rating Type:B
MVA to Mitigate:413.07
MW Contribution:0.21
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
1.883
971485AH1-239 GEN
Solar/Wind Harmer
0.213
966021AG1-471 GEN
Solar/Wind Harmer
0.16
972273AH1-721 GEN
50/50
386.389
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.043
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.131
LAGNLTFEXP_LAGN->PJM
CLTF
0.171
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.134
CPLELTFEXP_CPLE->PJM
CLTF
0.031
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.572
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.315
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.121
NYPJM->LTFIMP_NY
CLTF
0.011
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.312
MECLTFEXP_MEC->PJM
CLTF
0.019

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line l/o EKPC_P2-2_LAUR-LAURD161_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_LAUR-LAURD161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:123.67 %
Rating:334.0 MVA
Rating Type:B
MVA to Mitigate:413.07
MW Contribution:0.21
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
1.883
971485AH1-239 GEN
Solar/Wind Harmer
0.213
966021AG1-471 GEN
Solar/Wind Harmer
0.16
972273AH1-721 GEN
50/50
386.389
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.043
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.131
LAGNLTFEXP_LAGN->PJM
CLTF
0.171
CPLELTFEXP_CPLE->PJM
CLTF
0.031
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.572
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.315
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.134
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.121
NYPJM->LTFIMP_NY
CLTF
0.011
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.312
MECLTFEXP_MEC->PJM
CLTF
0.019

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line l/o EKPC_P2-3_LAURL S50-1014_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_LAURL S50-1014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:123.67 %
Rating:334.0 MVA
Rating Type:B
MVA to Mitigate:413.07
MW Contribution:0.21
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
1.883
971485AH1-239 GEN
Solar/Wind Harmer
0.213
966021AG1-471 GEN
Solar/Wind Harmer
0.16
972273AH1-721 GEN
50/50
386.401
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.043
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.131
LAGNLTFEXP_LAGN->PJM
CLTF
0.171
CPLELTFEXP_CPLE->PJM
CLTF
0.032
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.573
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.316
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.135
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.121
NYPJM->LTFIMP_NY
CLTF
0.011
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.312
MECLTFEXP_MEC->PJM
CLTF
0.019

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line l/o EKPC_P4-5_LAURL S50-1014_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P4-5_LAURL S50-1014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:123.67 %
Rating:334.0 MVA
Rating Type:B
MVA to Mitigate:413.05
MW Contribution:0.21
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
1.883
971485AH1-239 GEN
Solar/Wind Harmer
0.213
966021AG1-471 GEN
Solar/Wind Harmer
0.16
972273AH1-721 GEN
50/50
386.401
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.043
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.131
LAGNLTFEXP_LAGN->PJM
CLTF
0.171
CPLELTFEXP_CPLE->PJM
CLTF
0.032
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.573
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.316
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.135
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.121
NYPJM->LTFIMP_NY
CLTF
0.011
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.312
MECLTFEXP_MEC->PJM
CLTF
0.019

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line l/o EKPC_P2-2_LAUREL CO 161_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_LAUREL CO 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:123.67 %
Rating:334.0 MVA
Rating Type:B
MVA to Mitigate:413.05
MW Contribution:0.21
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
1.883
971485AH1-239 GEN
Solar/Wind Harmer
0.213
966021AG1-471 GEN
Solar/Wind Harmer
0.16
972273AH1-721 GEN
50/50
386.401
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.043
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.131
LAGNLTFEXP_LAGN->PJM
CLTF
0.171
CPLELTFEXP_CPLE->PJM
CLTF
0.032
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.573
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.316
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.135
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.121
NYPJM->LTFIMP_NY
CLTF
0.011
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.312
MECLTFEXP_MEC->PJM
CLTF
0.019

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line l/o EKPC_P7-1_LAURL 161 DBL_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_LAURL 161 DBL_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:123.59 %
Rating:334.0 MVA
Rating Type:B
MVA to Mitigate:412.79
MW Contribution:0.21
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
1.883
971485AH1-239 GEN
Solar/Wind Harmer
0.213
966021AG1-471 GEN
Solar/Wind Harmer
0.16
972273AH1-721 GEN
50/50
386.409
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.043
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.131
LAGNLTFEXP_LAGN->PJM
CLTF
0.172
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.135
CPLELTFEXP_CPLE->PJM
CLTF
0.032
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.575
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.316
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.121
NYPJM->LTFIMP_NY
CLTF
0.011
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.313
MECLTFEXP_MEC->PJM
CLTF
0.019

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line l/o EKPC_P1-2_COOP-LAUREL161_SRT-A-1


Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
Contingency Name:
EKPC_P1-2_COOP-LAUREL161_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:230.58 %
Rating:258.0 MVA
Rating Type:B
MVA to Mitigate:594.91
MW Contribution:0.23
Bus #Bus NameTypeMW Contribution
3429451LAUREL 1G
50/50
2.102
971485AH1-239 GEN
Solar/Wind Harmer
0.226
966021AG1-471 GEN
Solar/Wind Harmer
0.178
339231AF1-038_GEN
Solar/Wind Helper
0.161
972273AH1-721 GEN
50/50
647.508
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.184
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.623
MDUPJM->LTFIMP_MDU
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.536
GibsonPJM->LTFIMP_GIBSON
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.003
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.008
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.005
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.524

Details for AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:157.76 %
Rating:334.0 MVA
Rating Type:B
MVA to Mitigate:526.9
MW Contribution:0.35
Bus #Bus NameTypeMW Contribution
971485AH1-239 GEN
Solar/Wind Harmer
0.352
966021AG1-471 GEN
Solar/Wind Harmer
0.259
972273AH1-721 GEN
50/50
494.987
LAGNLTFEXP_LAGN->PJM
CLTF
0.598
G-007ALTFEXP_G-007A->PJM
CMTX
0.025
CPLELTFEXP_CPLE->PJM
CLTF
0.119
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.037
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.888
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.45
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.445
TVALTFEXP_TVA->PJM
CLTF
0.389
WECLTFEXP_WEC->PJM
CLTF
0.029
VFTLTFEXP_VFT->PJM
CMTX
0.067
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.106
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.197
MECLTFEXP_MEC->PJM
CLTF
0.223
SIGELTFEXP_SIGE->PJM
CLTF
0.006

Details for AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:156.84 %
Rating:334.0 MVA
Rating Type:B
MVA to Mitigate:523.85
MW Contribution:0.35
Bus #Bus NameTypeMW Contribution
971485AH1-239 GEN
Solar/Wind Harmer
0.35
966021AG1-471 GEN
Solar/Wind Harmer
0.257
972273AH1-721 GEN
50/50
493.115
LAGNLTFEXP_LAGN->PJM
CLTF
0.604
G-007ALTFEXP_G-007A->PJM
CMTX
0.022
CPLELTFEXP_CPLE->PJM
CLTF
0.116
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.032
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.952
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.424
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.436
TVALTFEXP_TVA->PJM
CLTF
0.392
LGEELTFEXP_LGEE->PJM
CLTF
0.004
WECLTFEXP_WEC->PJM
CLTF
0.031
VFTLTFEXP_VFT->PJM
CMTX
0.06
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.158
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.213
MECLTFEXP_MEC->PJM
CLTF
0.231
SIGELTFEXP_SIGE->PJM
CLTF
0.007

Details for AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:156.84 %
Rating:334.0 MVA
Rating Type:B
MVA to Mitigate:523.85
MW Contribution:0.35
Bus #Bus NameTypeMW Contribution
971485AH1-239 GEN
Solar/Wind Harmer
0.35
966021AG1-471 GEN
Solar/Wind Harmer
0.257
972273AH1-721 GEN
50/50
493.115
LAGNLTFEXP_LAGN->PJM
CLTF
0.604
G-007ALTFEXP_G-007A->PJM
CMTX
0.022
CPLELTFEXP_CPLE->PJM
CLTF
0.116
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.032
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.952
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.424
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.436
TVALTFEXP_TVA->PJM
CLTF
0.392
LGEELTFEXP_LGEE->PJM
CLTF
0.004
WECLTFEXP_WEC->PJM
CLTF
0.031
VFTLTFEXP_VFT->PJM
CMTX
0.06
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.158
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.213
MECLTFEXP_MEC->PJM
CLTF
0.231
SIGELTFEXP_SIGE->PJM
CLTF
0.007
CONTINGENCY 'EKPC_P2-3_COOP S42-1039_SRT-A'
 OPEN BUS 342715   /*5COOPER1     161.0
 OPEN BUS 342718   /*5COOPER2     161.0
 OPEN BUS 342900   /*1COOPER1 G    13.8
 OPEN BUS 342903   /*1COOPER2 G    20.0
END
CONTINGENCY 'EKPC_P2-3_COOP S42-210G_SRT-A'
 OPEN BUS 342718   /*5COOPER2     161.0
 OPEN BUS 342903   /*1COOPER2 G    20.0
END
CONTINGENCY 'EKPC_P2-2_COOPER 2 161_SRT-A'
 OPEN BUS 342718   /*5COOPER2     161.0
END
CONTINGENCY 'EKPC_P7-1_COOP 161 DBL 2_SRT-A-2'
 OPEN BRANCH FROM BUS 324141 TO BUS 342718 CKT 1   /*5ELIHU       161.0 - 5COOPER2     161.0
 OPEN BRANCH FROM BUS 972272 TO BUS 342757 CKT 1   /*AH1-721 TP   161.0 - 5LAUREL DAM  161.0
END
CONTINGENCY 'EKPC_P1-2_COOP-ELIHU161_SRT-A'
 OPEN BRANCH FROM BUS 324141 TO BUS 342718 CKT 1   /*5ELIHU       161.0 - 5COOPER2     161.0
END
CONTINGENCY 'EKPC_P2-2_ELIHU-COOP 161_SRT-A'
 OPEN BRANCH FROM BUS 324141 TO BUS 342718 CKT 1   /*5ELIHU       161.0 - 5COOPER2     161.0
END
CONTINGENCY 'EKPC_P7-1_COOP 161 DBL 2_SRT-A-1'
 OPEN BRANCH FROM BUS 324141 TO BUS 342718 CKT 1   /*5ELIHU       161.0 - 5COOPER2     161.0
 OPEN BRANCH FROM BUS 342718 TO BUS 972272 CKT 1   /*5COOPER2     161.0 - AH1-721 TP   161.0
END
CONTINGENCY 'EKPC_P1-2_AG1-471 TP-2ZULA J NO-69_SRT-A'
 DISCONNECT BRANCH FROM BUS 966020 TO BUS 342532 CKT 1   /*AG1-471 TP    69.0 - 2ZULA J NO    69.0
END
CONTINGENCY 'EKPC_P1-2_AG1-471 TP-AH1-239 TP-69_SRT-A'
 DISCONNECT BRANCH FROM BUS 966020 TO BUS 971484 CKT 1   /*AG1-471 TP    69.0 - AH1-239 TP    69.0
END
CONTINGENCY 'EKPC_P2-3_COOP S42-1014_SRT-A'
 OPEN BRANCH FROM BUS 342742 TO BUS 342745 CKT 1   /*5JABEZ       161.0 - 5JABEZ T     161.0
 OPEN BRANCH FROM BUS 342745 TO BUS 342751 CKT 1   /*5JABEZ T     161.0 - 5JAMESTOWN T 161.0
 OPEN BRANCH FROM BUS 342745 TO BUS 342799 CKT 1   /*5JABEZ T     161.0 - 5S OAKHILL   161.0
 OPEN BRANCH FROM BUS 342748 TO BUS 342751 CKT 1   /*5JAMESTOWN   161.0 - 5JAMESTOWN T 161.0
 OPEN BRANCH FROM BUS 342751 TO BUS 342796 CKT 1   /*5JAMESTOWN T 161.0 - 5RUSSEL CO J 161.0
 OPEN BRANCH FROM BUS 342793 TO BUS 342796 CKT 1   /*5RUSSEL CO   161.0 - 5RUSSEL CO J 161.0
 OPEN BRANCH FROM BUS 342796 TO BUS 360448 CKT 1   /*5RUSSEL CO J 161.0 - 5WOLF CRK HP 161.0
 OPEN BUS 342715                                   /*5COOPER1     161.0
 OPEN BUS 342900                                   /*1COOPER1 G    13.8
END
CONTINGENCY 'EKPC_P2-3_COOP S42-1024_SRT-A'
 OPEN BRANCH FROM BUS 342115 TO BUS 342787 CKT 1   /*2PULASK CO    69.0 - 5PULASK CO   161.0
 OPEN BRANCH FROM BUS 342760 TO BUS 342790 CKT 1   /*5LIBERTY J   161.0 - 5PULASK CO J 161.0
 OPEN BRANCH FROM BUS 342787 TO BUS 342790 CKT 1   /*5PULASK CO   161.0 - 5PULASK CO J 161.0
 OPEN BUS 342715                                   /*5COOPER1     161.0
 OPEN BUS 342900                                   /*1COOPER1 G    13.8
END
CONTINGENCY 'EKPC_P2-3_COOP S42-1008_SRT-A'
 OPEN BUS 342715   /*5COOPER1     161.0
 OPEN BUS 342900   /*1COOPER1 G    13.8
END
CONTINGENCY 'EKPC_P2-2_COOPER 1 161_SRT-A'
 OPEN BUS 342715   /*5COOPER1     161.0
END
CONTINGENCY 'EKPC_P1-2_COOP 161 TIE_SRT-A'
 OPEN BRANCH FROM BUS 342715 TO BUS 342718 CKT 1   /*5COOPER1     161.0 - 5COOPER2     161.0
END
CONTINGENCY 'EKPC_P4-5_LAURL S50-1024_SRT-A'
 OPEN BRANCH FROM BUS 324688 TO BUS 342781 CKT 1   /*2PITTSBRG KU  69.0 - 5PITTSBURG   161.0
 OPEN BRANCH FROM BUS 342781 TO BUS 342820 CKT 1   /*5PITTSBURG   161.0 - 5TYNER       161.0
 OPEN BUS 342754                                   /*5LAUREL CO   161.0
END
CONTINGENCY 'EKPC_P2-3_LAURL S50-1024_SRT-A'
 OPEN BRANCH FROM BUS 324688 TO BUS 342781 CKT 1   /*2PITTSBRG KU  69.0 - 5PITTSBURG   161.0
 OPEN BRANCH FROM BUS 341740 TO BUS 342754 CKT 1   /*2LAUREL CO    69.0 - 5LAUREL CO   161.0
 OPEN BRANCH FROM BUS 342754 TO BUS 342781 CKT 1   /*5LAUREL CO   161.0 - 5PITTSBURG   161.0
 OPEN BRANCH FROM BUS 342781 TO BUS 342820 CKT 1   /*5PITTSBURG   161.0 - 5TYNER       161.0
END
CONTINGENCY 'EKPC_P7-1_LAURL 161 DBL_SRT-A'
 OPEN BRANCH FROM BUS 342754 TO BUS 342757 CKT 1   /*5LAUREL CO   161.0 - 5LAUREL DAM  161.0
 OPEN BRANCH FROM BUS 342754 TO BUS 342781 CKT 1   /*5LAUREL CO   161.0 - 5PITTSBURG   161.0
 OPEN BRANCH FROM BUS 342781 TO BUS 342820 CKT 1   /*5PITTSBURG   161.0 - 5TYNER       161.0
END
CONTINGENCY 'EKPC_P1-2_LAUR-L DAM161_SRT-A'
 OPEN BRANCH FROM BUS 342754 TO BUS 342757 CKT 1   /*5LAUREL CO   161.0 - 5LAUREL DAM  161.0
END
CONTINGENCY 'EKPC_P2-2_LAUR-LAURD161_SRT-A'
 OPEN BRANCH FROM BUS 342754 TO BUS 342757 CKT 1   /*5LAUREL CO   161.0 - 5LAUREL DAM  161.0
END
CONTINGENCY 'EKPC_P2-2_LAUREL CO 161_SRT-A'
 OPEN BUS 342754   /*5LAUREL CO   161.0
END
CONTINGENCY 'EKPC_P7-1_COOP 161 DBL 1_SRT-A'
 OPEN BRANCH FROM BUS 342115 TO BUS 342787 CKT 1   /*2PULASK CO    69.0 - 5PULASK CO   161.0
 OPEN BRANCH FROM BUS 342715 TO BUS 342790 CKT 1   /*5COOPER1     161.0 - 5PULASK CO J 161.0
 OPEN BRANCH FROM BUS 342715 TO BUS 342799 CKT 1   /*5COOPER1     161.0 - 5S OAKHILL   161.0
 OPEN BRANCH FROM BUS 342742 TO BUS 342745 CKT 1   /*5JABEZ       161.0 - 5JABEZ T     161.0
 OPEN BRANCH FROM BUS 342745 TO BUS 342751 CKT 1   /*5JABEZ T     161.0 - 5JAMESTOWN T 161.0
 OPEN BRANCH FROM BUS 342745 TO BUS 342799 CKT 1   /*5JABEZ T     161.0 - 5S OAKHILL   161.0
 OPEN BRANCH FROM BUS 342748 TO BUS 342751 CKT 1   /*5JAMESTOWN   161.0 - 5JAMESTOWN T 161.0
 OPEN BRANCH FROM BUS 342751 TO BUS 342796 CKT 1   /*5JAMESTOWN T 161.0 - 5RUSSEL CO J 161.0
 OPEN BRANCH FROM BUS 342760 TO BUS 342790 CKT 1   /*5LIBERTY J   161.0 - 5PULASK CO J 161.0
 OPEN BRANCH FROM BUS 342787 TO BUS 342790 CKT 1   /*5PULASK CO   161.0 - 5PULASK CO J 161.0
 OPEN BRANCH FROM BUS 342793 TO BUS 342796 CKT 1   /*5RUSSEL CO   161.0 - 5RUSSEL CO J 161.0
 OPEN BRANCH FROM BUS 342796 TO BUS 360448 CKT 1   /*5RUSSEL CO J 161.0 - 5WOLF CRK HP 161.0
END
CONTINGENCY 'EKPC_P2-2_COOP-LAURD 161_SRT-A'
 OPEN BRANCH FROM BUS 972272 TO BUS 342757 CKT 1   /*AH1-721 TP   161.0 - 5LAUREL DAM  161.0
END
CONTINGENCY 'EKPC_P2-2_PULASKI 161_SRT-A'
 OPEN BUS 342787   /*5PULASK CO   161.0
 OPEN BUS 342790   /*5PULASK CO J 161.0
END
CONTINGENCY 'EKPC_P1-2_AH1-239 TP-2UPCHURCH T-69_SRT-A'
 DISCONNECT BRANCH FROM BUS 971484 TO BUS 342397 CKT 1   /*AH1-239 TP    69.0 - 2UPCHURCH T   69.0
END
CONTINGENCY 'EKPC_P1-2_COOP-DEN161_SRT-A-1'
 OPEN BRANCH FROM BUS 342718 TO BUS 972272 CKT 2   /*5COOPER2     161.0 - AH1-721 TP   161.0
END
CONTINGENCY 'EKPC_P2-3_LAURL S50-1014_SRT-A'
 OPEN BRANCH FROM BUS 341740 TO BUS 342754 CKT 1   /*2LAUREL CO    69.0 - 5LAUREL CO   161.0
 OPEN BRANCH FROM BUS 342754 TO BUS 342757 CKT 1   /*5LAUREL CO   161.0 - 5LAUREL DAM  161.0
END
CONTINGENCY 'EKPC_P4-5_LAURL S50-1014_SRT-A'
 OPEN BUS 342754   /*5LAUREL CO   161.0
END
CONTINGENCY 'EKPC_P1-2_COOP-LAUREL161_SRT-A-1'
 OPEN BRANCH FROM BUS 342718 TO BUS 972272 CKT 1   /*5COOPER2     161.0 - AH1-721 TP   161.0
END
341206 to 341347 ckt 1
341347 to 341344 ckt 1
341344 to 342286 ckt 1
341344 to 342286 ckt 2
341392 to 341206 ckt 1
342287 to 324531 ckt 1
342286 to 342287 ckt 1
342397 to 341005 ckt 1
342718 to 342715 ckt 1
342718 to 324141 ckt 1
342757 to 342754 ckt 1
966020 to 342532 ckt 1
971484 to 342397 ckt 1
971484 to 966020 ckt 1
972272 to 342718 ckt 1
972272 to 342718 ckt 2
972272 to 342757 ckt 1

Light Load Analysis

The New Service Request AH1-239 was evaluated as a 80.0 MW injection

AH1-239 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 80.0 MW (80.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
IPDEKPC
2ALBANY-2SNOW T 69.0 kV Ckt 1 line
EKPC_P1-2_AG1-471 TP-AH1-239 TP-69_SRT-A
SingleAC128.13 %54.0B69.1980.0
IPDEKPC
2ALBANY-2SNOW T 69.0 kV Ckt 1 line
EKPC_P1-2_AG1-471 TP-2ZULA J NO-69_SRT-A
SingleAC128.13 %54.0B69.1980.0
GD2EKPC
2ALBANY-2SNOW T 69.0 kV Ckt 1 line
EKPC_P1-2_AG1-471 TP-2ZULA J NO-69_SRT-A
SingleAC116.56 %54.0B62.9444.0
GD2EKPC
2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC184.76 %63.0B116.43.13
GD2EKPC
2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC184.76 %63.0B116.43.13
GD2EKPC
2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC184.19 %63.0B116.043.42
GD2EKPC
2COOPER DIST-2COOPER 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC184.55 %63.0B116.273.13
GD2EKPC
2COOPER DIST-2COOPER 69.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC184.53 %63.0B116.263.13
GD2EKPC
2COOPER DIST-2COOPER 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC184.0 %63.0B115.923.42
GD2EKPC
2COOPER-2SOMERSET 69.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
TowerAC161.9 %76.0B123.042.55
GD2EKPC
2COOPER-2SOMERSET 69.0 kV Ckt 2 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
TowerAC161.9 %76.0B123.042.55
GD2EKPC
2DENNY-2BRONSTON T 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC262.88 %46.0B120.933.13
GD2EKPC
2DENNY-2BRONSTON T 69.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC262.88 %46.0B120.933.13
GD2EKPC
2DENNY-2BRONSTON T 69.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC262.26 %46.0B120.643.42
GD2EKPC/LGEE
2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
TowerAC394.44 %76.0B299.776.03
GD2EKPC/LGEE
2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line
EKPC_P2-2_ELIHU-COOP 161_SRT-A
BusAC308.58 %76.0B234.524.95
GD2EKPC/LGEE
2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
TowerAC307.86 %76.0B233.974.94
GD2EKPC/LGEE
2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line
EKPC_P1-2_COOP-ELIHU161_SRT-A
SingleAC299.62 %76.0B227.714.95
GD2EKPC
2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
TowerAC250.1 %115.0B287.625.26
GD2EKPC
2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line
EKPC_P1-2_COOP-ELIHU161_SRT-A
SingleAC188.4 %115.0B216.664.18
GD2EKPC
2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line
EKPC_P2-2_ELIHU-COOP 161_SRT-A
BusAC188.4 %115.0B216.664.18
GD2EKPC
2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
TowerAC187.91 %115.0B216.14.18
IPDEKPC
2UPCHURCH T-2ALBANY 69.0 kV Ckt 1 line
EKPC_P1-2_AG1-471 TP-AH1-239 TP-69_SRT-A
SingleAC144.65 %54.0B78.1180.0
IPDEKPC
2UPCHURCH T-2ALBANY 69.0 kV Ckt 1 line
EKPC_P1-2_AG1-471 TP-2ZULA J NO-69_SRT-A
SingleAC144.65 %54.0B78.1180.0
GD2EKPC
2UPCHURCH T-2ALBANY 69.0 kV Ckt 1 line
EKPC_P1-2_AG1-471 TP-2ZULA J NO-69_SRT-A
SingleAC129.8 %54.0B70.0944.0
IPDEKPC
2ZULA J NO-2WAYNE CO 69.0 kV Ckt 1 line
EKPC_P1-2_AH1-239 TP-2UPCHURCH T-69_SRT-A
SingleAC129.75 %63.0B81.7480.0
GD2EKPC
2ZULA J NO-2WAYNE CO 69.0 kV Ckt 1 line
EKPC_P1-2_AH1-239 TP-2UPCHURCH T-69_SRT-A
SingleAC116.73 %63.0B73.5444.0
IPDEKPC
2ZULA J NO-2WAYNE CO 69.0 kV Ckt 1 line
Base Case
SingleAC107.69 %57.0A61.3861.44
GD2EKPC
2ZULA J NO-2WAYNE CO 69.0 kV Ckt 1 line
Base Case
SingleAC102.29 %57.0A58.333.79
IPDEKPC
2ZULA J NO-2WAYNE CO 69.0 kV Ckt 1 line
EXT_324106 7HARDIN CO 345 325140 7GLENDALE S 345 1_SRT-L
SingleAC100.14 %63.0B63.0961.43
GD2EKPC
5COOPER2-5COOPER1 161.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
TowerAC135.41 %501.0B678.413.62
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P2-2_LAUR-LAURD161_SRT-A
BusAC199.49 %298.0B594.498.47
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P2-3_LAURL S50-1014_SRT-A
BreakerAC199.28 %298.0B593.848.46
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P4-5_LAURL S50-1014_SRT-A
BreakerAC199.25 %298.0B593.778.46
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P2-2_LAUREL CO 161_SRT-A
BusAC199.25 %298.0B593.758.46
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P4-5_LAURL S50-1024_SRT-A
BreakerAC199.06 %298.0B593.218.44
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P2-3_LAURL S50-1024_SRT-A
BreakerAC199.06 %298.0B593.198.44
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P7-1_LAURL 161 DBL_SRT-A
TowerAC199.05 %298.0B593.168.44
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P1-2_COOP 161 TIE_SRT-A
SingleAC195.41 %298.0B582.333.7
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P1-2_LAUR-L DAM161_SRT-A
SingleAC195.41 %298.0B582.338.47
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1014_SRT-A
BreakerAC195.32 %298.0B582.043.96
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P2-2_COOPER 1 161_SRT-A
BusAC195.21 %298.0B581.723.82
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Base Case
SingleAC191.57 %249.0A477.027.22
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P2-2_COOP-LAURD 161_SRT-A
BusAC187.53 %298.0B558.838.49
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 1_SRT-A
TowerAC176.12 %298.0B524.854.95
GD2EKPC/LGEE
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
EKPC_P2-2_PULASKI 161_SRT-A
BusAC171.77 %298.0B511.877.71
GD2EKPC
5LAUREL CO-5PITTSBURG 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC166.78 %200.0B333.562.63
GD2EKPC
5LAUREL CO-5PITTSBURG 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC166.77 %200.0B333.532.62
GD2EKPC
5LAUREL CO-5PITTSBURG 161.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC166.77 %200.0B333.532.62
GD2EKPC
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC279.15 %200.0B558.313.84
GD2EKPC
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC279.13 %200.0B558.263.81
GD2EKPC
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC279.13 %200.0B558.253.81
GD2EKPC
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
EXT_324130 5ALCALDE 161 324141 5ELIHU 161 1_SRT-L
SingleAC150.23 %200.0B300.464.47
GD2EKPC
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
TowerAC130.77 %200.0B261.533.55
GD2EKPC
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
EKPC_P1-2_COOP-ELIHU161_SRT-A
SingleAC130.05 %200.0B260.093.55
GD2EKPC
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
EKPC_P2-2_ELIHU-COOP 161_SRT-A
BusAC130.05 %200.0B260.093.55
IPDEKPC
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
EKPC_P1-2_AH1-239 TP-2UPCHURCH T-69_SRT-A
SingleAC151.39 %54.0B81.7580.0
GD2EKPC
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
EKPC_P1-2_AH1-239 TP-2UPCHURCH T-69_SRT-A
SingleAC136.22 %54.0B73.5644.0
IPDEKPC
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
Base Case
SingleAC125.28 %49.0A61.3961.44
GD2EKPC
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
Base Case
SingleAC118.97 %49.0A58.2933.79
IPDEKPC
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
EXT_324106 7HARDIN CO 345 325140 7GLENDALE S 345 1_SRT-L
SingleAC116.84 %54.0B63.0961.43
IPDEKPC
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
EKPC_P2-3_MAR W38-1014_SRT-A
BreakerAC116.02 %54.0B62.6561.46
IPDEKPC
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
EKPC_P2-2_SUMMSHADE 161 #1_SRT-A
BusAC115.71 %54.0B62.4962.65
IPDEKPC
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
EKPC_P2-3_CASEY S89-1008_SRT-A
BreakerAC114.83 %54.0B62.0161.41
IPDEKPC
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
EKPC_P2-2_CASEY CO 161_SRT-A
BusAC114.83 %54.0B62.0161.41
IPDEKPC
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
TowerAC113.47 %54.0B61.2861.34
IPDEKPC
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
TowerAC113.26 %54.0B61.1661.27
GD2EKPC
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
EKPC_P2-2_SUMMSHADE 161 #1_SRT-A
BusAC112.21 %54.0B60.5934.46
GD2EKPC
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
EKPC_P2-2_SUMMSHADE 161 #2_SRT-A
BusAC111.61 %54.0B60.2734.45
GD2EKPC
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
EKPC_P1-2_AH1-034 TP-2PATTON RD J-69_SRT-A
SingleAC109.81 %54.0B59.333.85
GD2EKPC
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
EKPC_P2-3_MAR W38-1014_SRT-A
BreakerAC108.84 %54.0B58.7733.8
GD2EKPC
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
EKPC_P4-2_MAR W38-1004_SRT-A
BreakerAC108.68 %54.0B58.6933.82
GD2EKPC
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
EKPC_P7-1_BULL 161 DBL_SRT-A
TowerAC108.13 %54.0B58.3933.83
GD2EKPC
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
EKPC_P7-1_SSHAD 161 DBL_SRT-A
TowerAC107.92 %54.0B58.2833.82
IPDEKPC
AH1-239 TP-2UPCHURCH T 69.0 kV Ckt 1 line
EKPC_P1-2_AG1-471 TP-AH1-239 TP-69_SRT-A
SingleAC151.02 %54.0B81.5580.0
IPDEKPC
AH1-239 TP-2UPCHURCH T 69.0 kV Ckt 1 line
EKPC_P1-2_AG1-471 TP-2ZULA J NO-69_SRT-A
SingleAC151.02 %54.0B81.5580.0
GD2EKPC
AH1-239 TP-2UPCHURCH T 69.0 kV Ckt 1 line
EKPC_P1-2_AG1-471 TP-2ZULA J NO-69_SRT-A
SingleAC136.2 %54.0B73.5544.0
IPDEKPC
AH1-239 TP-AG1-471 TP 69.0 kV Ckt 1 line
EKPC_P1-2_AH1-239 TP-2UPCHURCH T-69_SRT-A
SingleAC151.46 %54.0B81.7980.0
IPDEKPC
AH1-239 TP-AG1-471 TP 69.0 kV Ckt 1 line
Base Case
SingleAC125.38 %49.0A61.4461.44
IPDEKPC
AH1-239 TP-AG1-471 TP 69.0 kV Ckt 1 line
EXT_324106 7HARDIN CO 345 325140 7GLENDALE S 345 1_SRT-L
SingleAC116.93 %54.0B63.1461.43
IPDEKPC
AH1-239 TP-AG1-471 TP 69.0 kV Ckt 1 line
EKPC_P2-3_MAR W38-1014_SRT-A
BreakerAC116.11 %54.0B62.761.46
IPDEKPC
AH1-239 TP-AG1-471 TP 69.0 kV Ckt 1 line
EKPC_P2-2_SUMMSHADE 161 #1_SRT-A
BusAC115.8 %54.0B62.5362.65
IPDEKPC
AH1-239 TP-AG1-471 TP 69.0 kV Ckt 1 line
EKPC_P2-3_CASEY S89-1008_SRT-A
BreakerAC114.91 %54.0B62.0561.41
IPDEKPC
AH1-239 TP-AG1-471 TP 69.0 kV Ckt 1 line
EKPC_P2-2_CASEY CO 161_SRT-A
BusAC114.91 %54.0B62.0561.41
IPDEKPC
AH1-239 TP-AG1-471 TP 69.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
TowerAC113.56 %54.0B61.3261.34
IPDEKPC
AH1-239 TP-AG1-471 TP 69.0 kV Ckt 1 line
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
TowerAC113.35 %54.0B61.2161.27
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
EKPC_P1-2_COOP-DEN161_SRT-A-1
SingleAC217.77 %298.0B648.952.49
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
EKPC_P1-2_LAUR-L DAM161_SRT-A
SingleAC139.0 %298.0B414.212.34
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
EKPC_P2-2_LAUR-LAURD161_SRT-A
BusAC139.0 %298.0B414.212.34
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
EKPC_P2-3_LAURL S50-1014_SRT-A
BreakerAC138.99 %298.0B414.22.34
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
EKPC_P4-5_LAURL S50-1014_SRT-A
BreakerAC138.98 %298.0B414.162.34
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
EKPC_P2-2_LAUREL CO 161_SRT-A
BusAC138.98 %298.0B414.162.34
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
EKPC_P7-1_LAURL 161 DBL_SRT-A
TowerAC138.95 %298.0B414.062.34
GD2EKPC
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
EKPC_P1-2_COOP-LAUREL161_SRT-A-1
SingleAC308.72 %210.0B648.322.49
GD2EKPC
AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-1039_SRT-A
BreakerAC165.91 %298.0B494.413.87
GD2EKPC
AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line
EKPC_P2-3_COOP S42-210G_SRT-A
BreakerAC165.91 %298.0B494.413.85
GD2EKPC
AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line
EKPC_P2-2_COOPER 2 161_SRT-A
BusAC165.91 %298.0B494.43.85

Details for [AH1-239] 2ALBANY-2SNOW T 69.0 kV Ckt 1 line l/o EKPC_P1-2_AG1-471 TP-AH1-239 TP-69_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
2ALBANY-2SNOW T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_AG1-471 TP-AH1-239 TP-69_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:128.13 %
Rating:54.0 MVA
Rating Type:B
MVA to Mitigate:69.19
MW Contribution:80.0
IPD Plant:AH1-239
Bus #Bus NameTypeMW Contribution
971485AH1-239 GEN
PJM_IPD
80

Details for [AH1-239] 2ALBANY-2SNOW T 69.0 kV Ckt 1 line l/o EKPC_P1-2_AG1-471 TP-2ZULA J NO-69_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
2ALBANY-2SNOW T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_AG1-471 TP-2ZULA J NO-69_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:128.13 %
Rating:54.0 MVA
Rating Type:B
MVA to Mitigate:69.19
MW Contribution:80.0
IPD Plant:AH1-239
Bus #Bus NameTypeMW Contribution
971485AH1-239 GEN
PJM_IPD
80

Details for 2ALBANY-2SNOW T 69.0 kV Ckt 1 line l/o EKPC_P1-2_AG1-471 TP-2ZULA J NO-69_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
2ALBANY-2SNOW T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_AG1-471 TP-2ZULA J NO-69_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.56 %
Rating:54.0 MVA
Rating Type:B
MVA to Mitigate:62.94
MW Contribution:44.0
Bus #Bus NameTypeMW Contribution
971485AH1-239 GEN
Solar/Wind Harmer
44
966021AG1-471 GEN
Solar/Wind Harmer
29.7

Details for 2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:184.76 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:116.4
MW Contribution:3.13
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
115.381
966021AG1-471 GEN
Solar/Wind Harmer
2.376
971485AH1-239 GEN
Solar/Wind Harmer
3.128
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.256
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.074
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.24
LAGNLTFEXP_LAGN->PJM
CLTF
0.152
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.225
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.11
G-007ALTFEXP_G-007A->PJM
CMTX
0.015
CPLELTFEXP_CPLE->PJM
CLTF
0.063
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.02
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.322
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
0.041
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
2.315

Details for 2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:184.76 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:116.4
MW Contribution:3.13
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
115.381
966021AG1-471 GEN
Solar/Wind Harmer
2.376
971485AH1-239 GEN
Solar/Wind Harmer
3.128
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.256
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.074
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.24
LAGNLTFEXP_LAGN->PJM
CLTF
0.152
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.225
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.11
G-007ALTFEXP_G-007A->PJM
CMTX
0.015
CPLELTFEXP_CPLE->PJM
CLTF
0.063
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.02
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.322
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
0.041
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
2.315

Details for 2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
2BRONSTON T-2COOPER DIST 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:184.19 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:116.04
MW Contribution:3.42
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
108.296
966021AG1-471 GEN
Solar/Wind Harmer
2.567
971485AH1-239 GEN
Solar/Wind Harmer
3.417
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.048
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.539
MECLTFEXP_MEC->PJM
CLTF
0.055
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.069
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.213
LAGNLTFEXP_LAGN->PJM
CLTF
0.296
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.305
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.199
G-007ALTFEXP_G-007A->PJM
CMTX
0.004
CPLELTFEXP_CPLE->PJM
CLTF
0.083
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.064
NYPJM->LTFIMP_NY
CLTF
0.001
WECLTFEXP_WEC->PJM
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
0.01
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
2.811

Details for 2COOPER DIST-2COOPER 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER DIST-2COOPER 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:184.55 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:116.27
MW Contribution:3.13
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
115.381
966021AG1-471 GEN
Solar/Wind Harmer
2.376
971485AH1-239 GEN
Solar/Wind Harmer
3.128
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.256
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.074
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.24
LAGNLTFEXP_LAGN->PJM
CLTF
0.152
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.225
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.11
G-007ALTFEXP_G-007A->PJM
CMTX
0.015
CPLELTFEXP_CPLE->PJM
CLTF
0.063
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.02
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.322
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
0.041
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
2.315

Details for 2COOPER DIST-2COOPER 69.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER DIST-2COOPER 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:184.53 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:116.26
MW Contribution:3.13
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
115.381
966021AG1-471 GEN
Solar/Wind Harmer
2.376
971485AH1-239 GEN
Solar/Wind Harmer
3.128
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.256
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.074
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.24
LAGNLTFEXP_LAGN->PJM
CLTF
0.152
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.225
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.11
G-007ALTFEXP_G-007A->PJM
CMTX
0.015
CPLELTFEXP_CPLE->PJM
CLTF
0.063
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.02
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.322
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
0.041
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
2.315

Details for 2COOPER DIST-2COOPER 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER DIST-2COOPER 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:184.0 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:115.92
MW Contribution:3.42
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
108.296
966021AG1-471 GEN
Solar/Wind Harmer
2.567
971485AH1-239 GEN
Solar/Wind Harmer
3.417
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.048
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.539
MECLTFEXP_MEC->PJM
CLTF
0.055
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.069
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.213
LAGNLTFEXP_LAGN->PJM
CLTF
0.296
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.305
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.199
G-007ALTFEXP_G-007A->PJM
CMTX
0.004
CPLELTFEXP_CPLE->PJM
CLTF
0.083
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.064
NYPJM->LTFIMP_NY
CLTF
0.001
WECLTFEXP_WEC->PJM
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
0.01
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
2.811

Details for 2COOPER-2SOMERSET 69.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-2


Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER-2SOMERSET 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:161.9 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:123.04
MW Contribution:2.55
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
102.01
966021AG1-471 GEN
Solar/Wind Harmer
1.852
971485AH1-239 GEN
Solar/Wind Harmer
2.549
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.769
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.899
MECLTFEXP_MEC->PJM
CLTF
0.172
SIGELTFEXP_SIGE->PJM
CLTF
0.005
LAGNLTFEXP_LAGN->PJM
CLTF
0.46
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.284
TVALTFEXP_TVA->PJM
CLTF
0.287
CPLELTFEXP_CPLE->PJM
CLTF
0.071
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.303
NYPJM->LTFIMP_NY
CLTF
0.009
LGEELTFEXP_LGEE->PJM
CLTF
0.011
WECLTFEXP_WEC->PJM
CLTF
0.021
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.761

Details for 2COOPER-2SOMERSET 69.0 kV Ckt 2 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-2


Base Case Flowgate

Area:EKPC
Facility Description:
2COOPER-2SOMERSET 69.0 kV Ckt 2 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:161.9 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:123.04
MW Contribution:2.55
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
102.01
966021AG1-471 GEN
Solar/Wind Harmer
1.852
971485AH1-239 GEN
Solar/Wind Harmer
2.549
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.769
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.899
MECLTFEXP_MEC->PJM
CLTF
0.172
SIGELTFEXP_SIGE->PJM
CLTF
0.005
LAGNLTFEXP_LAGN->PJM
CLTF
0.46
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.284
TVALTFEXP_TVA->PJM
CLTF
0.287
CPLELTFEXP_CPLE->PJM
CLTF
0.071
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.303
NYPJM->LTFIMP_NY
CLTF
0.009
LGEELTFEXP_LGEE->PJM
CLTF
0.011
WECLTFEXP_WEC->PJM
CLTF
0.021
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.761

Details for 2DENNY-2BRONSTON T 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
2DENNY-2BRONSTON T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:262.88 %
Rating:46.0 MVA
Rating Type:B
MVA to Mitigate:120.93
MW Contribution:3.13
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
115.381
966021AG1-471 GEN
Solar/Wind Harmer
2.376
971485AH1-239 GEN
Solar/Wind Harmer
3.128
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.256
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.074
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.24
LAGNLTFEXP_LAGN->PJM
CLTF
0.152
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.225
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.11
G-007ALTFEXP_G-007A->PJM
CMTX
0.015
CPLELTFEXP_CPLE->PJM
CLTF
0.063
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.02
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.322
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
0.041
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
2.315

Details for 2DENNY-2BRONSTON T 69.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
2DENNY-2BRONSTON T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:262.88 %
Rating:46.0 MVA
Rating Type:B
MVA to Mitigate:120.93
MW Contribution:3.13
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
115.381
966021AG1-471 GEN
Solar/Wind Harmer
2.376
971485AH1-239 GEN
Solar/Wind Harmer
3.128
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.256
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.074
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.24
LAGNLTFEXP_LAGN->PJM
CLTF
0.152
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.225
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.11
G-007ALTFEXP_G-007A->PJM
CMTX
0.015
CPLELTFEXP_CPLE->PJM
CLTF
0.063
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.02
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.322
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
0.041
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
2.315

Details for 2DENNY-2BRONSTON T 69.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
2DENNY-2BRONSTON T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:262.26 %
Rating:46.0 MVA
Rating Type:B
MVA to Mitigate:120.64
MW Contribution:3.42
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
108.296
966021AG1-471 GEN
Solar/Wind Harmer
2.567
971485AH1-239 GEN
Solar/Wind Harmer
3.417
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.048
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.539
MECLTFEXP_MEC->PJM
CLTF
0.055
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.069
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.213
LAGNLTFEXP_LAGN->PJM
CLTF
0.296
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.305
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.199
G-007ALTFEXP_G-007A->PJM
CMTX
0.004
CPLELTFEXP_CPLE->PJM
CLTF
0.083
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.064
NYPJM->LTFIMP_NY
CLTF
0.001
WECLTFEXP_WEC->PJM
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
0.01
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
2.811

Details for 2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-2


Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:394.44 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:299.77
MW Contribution:6.03
Bus #Bus NameTypeMW Contribution
965401AG1-405 GEN
Solar/Wind Harmer
10.174
965411AG1-406 GEN
Solar/Wind Harmer
7.14
964781AG1-341 GEN
Solar/Wind Harmer
2.973
970273AG2-179 GEN
Solar/Wind Harmer
4.883
970273AG2-179 GEN
Solar/Wind Harmer
4.78
971081AG2-670 GEN
Solar/Wind Harmer
3.535
962251AG1-071 GEN
Solar/Wind Harmer
2.153
960741AF2-365 GEN
Solar/Wind Harmer
1.607
971155AH1-034 GEN
Solar/Wind Harmer
4.673
962241AG1-070 GEN
Solar/Wind Harmer
1.762
972273AH1-721 GEN
50/50
203.566
966021AG1-471 GEN
Solar/Wind Harmer
4.241
971485AH1-239 GEN
Solar/Wind Harmer
6.026
964901AG1-354 GEN
Solar/Wind Harmer
6.679
964781AG1-341 GEN
Solar/Wind Harmer
5.406
971821AH1-427 GEN
Solar/Wind Harmer
3.287
950011AG9-010
External Queue
4.594685077667236
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.418
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.414
MECLTFEXP_MEC->PJM
CLTF
0.509
SIGELTFEXP_SIGE->PJM
CLTF
0.019
LAGNLTFEXP_LAGN->PJM
CLTF
1.224
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.525
TVALTFEXP_TVA->PJM
CLTF
0.751
CPLELTFEXP_CPLE->PJM
CLTF
0.114
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.496
NYPJM->LTFIMP_NY
CLTF
0.04
LGEELTFEXP_LGEE->PJM
CLTF
0.09
WECLTFEXP_WEC->PJM
CLTF
0.068
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
3.513

Details for 2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line l/o EKPC_P2-2_ELIHU-COOP 161_SRT-A


Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_ELIHU-COOP 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:308.58 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:234.52
MW Contribution:4.95
Bus #Bus NameTypeMW Contribution
965401AG1-405 GEN
Solar/Wind Harmer
9.399
965411AG1-406 GEN
Solar/Wind Harmer
6.596
964781AG1-341 GEN
Solar/Wind Harmer
2.417
970273AG2-179 GEN
Solar/Wind Harmer
4.308
970273AG2-179 GEN
Solar/Wind Harmer
4.218
971081AG2-670 GEN
Solar/Wind Harmer
2.861
962251AG1-071 GEN
Solar/Wind Harmer
1.756
972273AH1-721 GEN
50/50
153.03
966021AG1-471 GEN
Solar/Wind Harmer
3.478
971485AH1-239 GEN
Solar/Wind Harmer
4.945
964901AG1-354 GEN
Solar/Wind Harmer
5.42
964781AG1-341 GEN
Solar/Wind Harmer
4.394
971821AH1-427 GEN
Solar/Wind Harmer
3.109
971155AH1-034 GEN
Solar/Wind Harmer
3.849
962241AG1-070 GEN
Solar/Wind Harmer
1.437
950011AG9-010
External Queue
3.74114727973938
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.687
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.797
MECLTFEXP_MEC->PJM
CLTF
0.371
SIGELTFEXP_SIGE->PJM
CLTF
0.013
LAGNLTFEXP_LAGN->PJM
CLTF
0.92
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.337
TVALTFEXP_TVA->PJM
CLTF
0.568
CPLELTFEXP_CPLE->PJM
CLTF
0.066
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.815
NYPJM->LTFIMP_NY
CLTF
0.038
LGEELTFEXP_LGEE->PJM
CLTF
0.039
WECLTFEXP_WEC->PJM
CLTF
0.047
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
2.995

Details for 2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-1


Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:307.86 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:233.97
MW Contribution:4.94
Bus #Bus NameTypeMW Contribution
965401AG1-405 GEN
Solar/Wind Harmer
9.403
965411AG1-406 GEN
Solar/Wind Harmer
6.598
964781AG1-341 GEN
Solar/Wind Harmer
2.419
970273AG2-179 GEN
Solar/Wind Harmer
4.31
970273AG2-179 GEN
Solar/Wind Harmer
4.22
971081AG2-670 GEN
Solar/Wind Harmer
2.863
962251AG1-071 GEN
Solar/Wind Harmer
1.757
971155AH1-034 GEN
Solar/Wind Harmer
3.851
962241AG1-070 GEN
Solar/Wind Harmer
1.438
972273AH1-721 GEN
50/50
152.49
966021AG1-471 GEN
Solar/Wind Harmer
3.477
971485AH1-239 GEN
Solar/Wind Harmer
4.944
964901AG1-354 GEN
Solar/Wind Harmer
5.425
964781AG1-341 GEN
Solar/Wind Harmer
4.397
971821AH1-427 GEN
Solar/Wind Harmer
3.11
950011AG9-010
External Queue
3.7449028491973877
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.69
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.798
MECLTFEXP_MEC->PJM
CLTF
0.372
SIGELTFEXP_SIGE->PJM
CLTF
0.013
LAGNLTFEXP_LAGN->PJM
CLTF
0.921
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.337
TVALTFEXP_TVA->PJM
CLTF
0.568
CPLELTFEXP_CPLE->PJM
CLTF
0.066
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.82
NYPJM->LTFIMP_NY
CLTF
0.038
LGEELTFEXP_LGEE->PJM
CLTF
0.04
WECLTFEXP_WEC->PJM
CLTF
0.047
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
2.994

Details for 2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line l/o EKPC_P1-2_COOP-ELIHU161_SRT-A


Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
2SOMERSET KU-2FERGUSON SO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_COOP-ELIHU161_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:299.62 %
Rating:76.0 MVA
Rating Type:B
MVA to Mitigate:227.71
MW Contribution:4.95
Bus #Bus NameTypeMW Contribution
965401AG1-405 GEN
Solar/Wind Harmer
9.399
965411AG1-406 GEN
Solar/Wind Harmer
6.596
970273AG2-179 GEN
Solar/Wind Harmer
4.308
970273AG2-179 GEN
Solar/Wind Harmer
4.218
971081AG2-670 GEN
Solar/Wind Harmer
2.861
962251AG1-071 GEN
Solar/Wind Harmer
1.756
972273AH1-721 GEN
50/50
153.03
966021AG1-471 GEN
Solar/Wind Harmer
3.478
971485AH1-239 GEN
Solar/Wind Harmer
4.945
964901AG1-354 GEN
Solar/Wind Harmer
5.42
971821AH1-427 GEN
Solar/Wind Harmer
3.109
971155AH1-034 GEN
Solar/Wind Harmer
3.849
962241AG1-070 GEN
Solar/Wind Harmer
1.437
950011AG9-010
External Queue
3.74114727973938
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.687
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.797
MECLTFEXP_MEC->PJM
CLTF
0.371
SIGELTFEXP_SIGE->PJM
CLTF
0.013
LAGNLTFEXP_LAGN->PJM
CLTF
0.92
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.337
TVALTFEXP_TVA->PJM
CLTF
0.568
CPLELTFEXP_CPLE->PJM
CLTF
0.066
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.815
NYPJM->LTFIMP_NY
CLTF
0.038
LGEELTFEXP_LGEE->PJM
CLTF
0.039
WECLTFEXP_WEC->PJM
CLTF
0.047
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
2.995

Details for 2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-2


Base Case Flowgate

Area:EKPC
Facility Description:
2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:250.1 %
Rating:115.0 MVA
Rating Type:B
MVA to Mitigate:287.62
MW Contribution:5.26
Bus #Bus NameTypeMW Contribution
965401AG1-405 GEN
Solar/Wind Harmer
11.238
965411AG1-406 GEN
Solar/Wind Harmer
7.886
964781AG1-341 GEN
Solar/Wind Harmer
2.342
970273AG2-179 GEN
Solar/Wind Harmer
3.415
970273AG2-179 GEN
Solar/Wind Harmer
3.344
971081AG2-670 GEN
Solar/Wind Harmer
3.211
962251AG1-071 GEN
Solar/Wind Harmer
1.712
971155AH1-034 GEN
Solar/Wind Harmer
3.685
962241AG1-070 GEN
Solar/Wind Harmer
1.401
972273AH1-721 GEN
50/50
208.23
966021AG1-471 GEN
Solar/Wind Harmer
3.73
971485AH1-239 GEN
Solar/Wind Harmer
5.259
964901AG1-354 GEN
Solar/Wind Harmer
5.561
964781AG1-341 GEN
Solar/Wind Harmer
4.259
971821AH1-427 GEN
Solar/Wind Harmer
3.364
950011AG9-010
External Queue
4.469371318817139
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.985
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.865
MECLTFEXP_MEC->PJM
CLTF
0.408
SIGELTFEXP_SIGE->PJM
CLTF
0.016
LAGNLTFEXP_LAGN->PJM
CLTF
0.942
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.349
TVALTFEXP_TVA->PJM
CLTF
0.574
CPLELTFEXP_CPLE->PJM
CLTF
0.07
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.119
NYPJM->LTFIMP_NY
CLTF
0.035
LGEELTFEXP_LGEE->PJM
CLTF
0.089
WECLTFEXP_WEC->PJM
CLTF
0.056
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
2.225

Details for 2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line l/o EKPC_P1-2_COOP-ELIHU161_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_COOP-ELIHU161_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:188.4 %
Rating:115.0 MVA
Rating Type:B
MVA to Mitigate:216.66
MW Contribution:4.18
Bus #Bus NameTypeMW Contribution
965401AG1-405 GEN
Solar/Wind Harmer
10.465
965411AG1-406 GEN
Solar/Wind Harmer
7.344
970273AG2-179 GEN
Solar/Wind Harmer
2.842
970273AG2-179 GEN
Solar/Wind Harmer
2.783
971081AG2-670 GEN
Solar/Wind Harmer
2.539
972273AH1-721 GEN
50/50
157.856
966021AG1-471 GEN
Solar/Wind Harmer
2.969
971485AH1-239 GEN
Solar/Wind Harmer
4.181
971821AH1-427 GEN
Solar/Wind Harmer
3.186
964901AG1-354 GEN
Solar/Wind Harmer
4.307
971155AH1-034 GEN
Solar/Wind Harmer
2.864
950011AG9-010
External Queue
3.6185758113861084
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.257
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.25
MECLTFEXP_MEC->PJM
CLTF
0.27
SIGELTFEXP_SIGE->PJM
CLTF
0.01
LAGNLTFEXP_LAGN->PJM
CLTF
0.639
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.162
TVALTFEXP_TVA->PJM
CLTF
0.391
CPLELTFEXP_CPLE->PJM
CLTF
0.022
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.443
NYPJM->LTFIMP_NY
CLTF
0.033
LGEELTFEXP_LGEE->PJM
CLTF
0.039
WECLTFEXP_WEC->PJM
CLTF
0.035
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.708

Details for 2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line l/o EKPC_P2-2_ELIHU-COOP 161_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_ELIHU-COOP 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:188.4 %
Rating:115.0 MVA
Rating Type:B
MVA to Mitigate:216.66
MW Contribution:4.18
Bus #Bus NameTypeMW Contribution
965401AG1-405 GEN
Solar/Wind Harmer
10.465
965411AG1-406 GEN
Solar/Wind Harmer
7.344
970273AG2-179 GEN
Solar/Wind Harmer
2.842
970273AG2-179 GEN
Solar/Wind Harmer
2.783
971081AG2-670 GEN
Solar/Wind Harmer
2.539
972273AH1-721 GEN
50/50
157.856
966021AG1-471 GEN
Solar/Wind Harmer
2.969
971485AH1-239 GEN
Solar/Wind Harmer
4.181
971821AH1-427 GEN
Solar/Wind Harmer
3.186
964901AG1-354 GEN
Solar/Wind Harmer
4.307
971155AH1-034 GEN
Solar/Wind Harmer
2.864
950011AG9-010
External Queue
3.6185758113861084
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.257
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.25
MECLTFEXP_MEC->PJM
CLTF
0.27
SIGELTFEXP_SIGE->PJM
CLTF
0.01
LAGNLTFEXP_LAGN->PJM
CLTF
0.639
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.162
TVALTFEXP_TVA->PJM
CLTF
0.391
CPLELTFEXP_CPLE->PJM
CLTF
0.022
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.443
NYPJM->LTFIMP_NY
CLTF
0.033
LGEELTFEXP_LGEE->PJM
CLTF
0.039
WECLTFEXP_WEC->PJM
CLTF
0.035
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.708

Details for 2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-1


Base Case Flowgate

Area:EKPC
Facility Description:
2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:187.91 %
Rating:115.0 MVA
Rating Type:B
MVA to Mitigate:216.1
MW Contribution:4.18
Bus #Bus NameTypeMW Contribution
965401AG1-405 GEN
Solar/Wind Harmer
10.469
965411AG1-406 GEN
Solar/Wind Harmer
7.346
970273AG2-179 GEN
Solar/Wind Harmer
2.844
970273AG2-179 GEN
Solar/Wind Harmer
2.785
971081AG2-670 GEN
Solar/Wind Harmer
2.542
972273AH1-721 GEN
50/50
157.323
966021AG1-471 GEN
Solar/Wind Harmer
2.969
971485AH1-239 GEN
Solar/Wind Harmer
4.18
971821AH1-427 GEN
Solar/Wind Harmer
3.187
964901AG1-354 GEN
Solar/Wind Harmer
4.311
971155AH1-034 GEN
Solar/Wind Harmer
2.866
950011AG9-010
External Queue
3.622286319732666
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.259
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.252
MECLTFEXP_MEC->PJM
CLTF
0.271
SIGELTFEXP_SIGE->PJM
CLTF
0.01
LAGNLTFEXP_LAGN->PJM
CLTF
0.64
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.162
TVALTFEXP_TVA->PJM
CLTF
0.392
CPLELTFEXP_CPLE->PJM
CLTF
0.022
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.447
NYPJM->LTFIMP_NY
CLTF
0.033
LGEELTFEXP_LGEE->PJM
CLTF
0.039
WECLTFEXP_WEC->PJM
CLTF
0.035
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.707

Details for [AH1-239] 2UPCHURCH T-2ALBANY 69.0 kV Ckt 1 line l/o EKPC_P1-2_AG1-471 TP-AH1-239 TP-69_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
2UPCHURCH T-2ALBANY 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_AG1-471 TP-AH1-239 TP-69_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:144.65 %
Rating:54.0 MVA
Rating Type:B
MVA to Mitigate:78.11
MW Contribution:80.0
IPD Plant:AH1-239
Bus #Bus NameTypeMW Contribution
971485AH1-239 GEN
PJM_IPD
80

Details for [AH1-239] 2UPCHURCH T-2ALBANY 69.0 kV Ckt 1 line l/o EKPC_P1-2_AG1-471 TP-2ZULA J NO-69_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
2UPCHURCH T-2ALBANY 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_AG1-471 TP-2ZULA J NO-69_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:144.65 %
Rating:54.0 MVA
Rating Type:B
MVA to Mitigate:78.11
MW Contribution:80.0
IPD Plant:AH1-239
Bus #Bus NameTypeMW Contribution
971485AH1-239 GEN
PJM_IPD
80

Details for 2UPCHURCH T-2ALBANY 69.0 kV Ckt 1 line l/o EKPC_P1-2_AG1-471 TP-2ZULA J NO-69_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
2UPCHURCH T-2ALBANY 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_AG1-471 TP-2ZULA J NO-69_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:129.8 %
Rating:54.0 MVA
Rating Type:B
MVA to Mitigate:70.09
MW Contribution:44.0
Bus #Bus NameTypeMW Contribution
971485AH1-239 GEN
Solar/Wind Harmer
44
966021AG1-471 GEN
Solar/Wind Harmer
29.7

Details for [AH1-239] 2ZULA J NO-2WAYNE CO 69.0 kV Ckt 1 line l/o EKPC_P1-2_AH1-239 TP-2UPCHURCH T-69_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
2ZULA J NO-2WAYNE CO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_AH1-239 TP-2UPCHURCH T-69_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:129.75 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:81.74
MW Contribution:80.0
IPD Plant:AH1-239
Bus #Bus NameTypeMW Contribution
971485AH1-239 GEN
PJM_IPD
80

Details for 2ZULA J NO-2WAYNE CO 69.0 kV Ckt 1 line l/o EKPC_P1-2_AH1-239 TP-2UPCHURCH T-69_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
2ZULA J NO-2WAYNE CO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_AH1-239 TP-2UPCHURCH T-69_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.73 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:73.54
MW Contribution:44.0
Bus #Bus NameTypeMW Contribution
971485AH1-239 GEN
Solar/Wind Harmer
44
966021AG1-471 GEN
Solar/Wind Harmer
29.7

Details for [AH1-239] 2ZULA J NO-2WAYNE CO 69.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:EKPC
Facility Description:
2ZULA J NO-2WAYNE CO 69.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:107.69 %
Rating:57.0 MVA
Rating Type:A
MVA to Mitigate:61.38
MW Contribution:61.44
IPD Plant:AH1-239
Bus #Bus NameTypeMW Contribution
971485AH1-239 GEN
PJM_IPD
61.435

Details for 2ZULA J NO-2WAYNE CO 69.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:EKPC
Facility Description:
2ZULA J NO-2WAYNE CO 69.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.29 %
Rating:57.0 MVA
Rating Type:A
MVA to Mitigate:58.3
MW Contribution:33.79
Bus #Bus NameTypeMW Contribution
966021AG1-471 GEN
Solar/Wind Harmer
25.466
971485AH1-239 GEN
Solar/Wind Harmer
33.789
971155AH1-034 GEN
Solar/Wind Harmer
2.847
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.014
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.349
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.094
MECLTFEXP_MEC->PJM
CLTF
0.054
SIGELTFEXP_SIGE->PJM
CLTF
0.004
LAGNLTFEXP_LAGN->PJM
CLTF
0.038
TVALTFEXP_TVA->PJM
CLTF
0.014
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.484
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.007
LGEELTFEXP_LGEE->PJM
CLTF
0.053
WECLTFEXP_WEC->PJM
CLTF
0.01
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.02

Details for [AH1-239] 2ZULA J NO-2WAYNE CO 69.0 kV Ckt 1 line l/o EXT_324106 7HARDIN CO 345 325140 7GLENDALE S 345 1_SRT-L


Base Case Flowgate

Area:EKPC
Facility Description:
2ZULA J NO-2WAYNE CO 69.0 kV Ckt 1 line
Contingency Name:
EXT_324106 7HARDIN CO 345 325140 7GLENDALE S 345 1_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.14 %
Rating:63.0 MVA
Rating Type:B
MVA to Mitigate:63.09
MW Contribution:61.43
IPD Plant:AH1-239
Bus #Bus NameTypeMW Contribution
971485AH1-239 GEN
PJM_IPD
61.429

Details for 5COOPER2-5COOPER1 161.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-2


Base Case Flowgate

Area:EKPC
Facility Description:
5COOPER2-5COOPER1 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:135.41 %
Rating:501.0 MVA
Rating Type:B
MVA to Mitigate:678.41
MW Contribution:3.62
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
673.687
966021AG1-471 GEN
Solar/Wind Harmer
2.75
971485AH1-239 GEN
Solar/Wind Harmer
3.619
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.342
MECLTFEXP_MEC->PJM
CLTF
0.013
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.068
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.221
LAGNLTFEXP_LAGN->PJM
CLTF
0.193
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.297
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.136
G-007ALTFEXP_G-007A->PJM
CMTX
0.037
CPLELTFEXP_CPLE->PJM
CLTF
0.085
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.062
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.515
VFTLTFEXP_VFT->PJM
CMTX
0.099
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
2.503

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P2-2_LAUR-LAURD161_SRT-A


Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_LAUR-LAURD161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:199.49 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:594.49
MW Contribution:8.47
Bus #Bus NameTypeMW Contribution
965401AG1-405 GEN
Solar/Wind Harmer
4.921
965411AG1-406 GEN
Solar/Wind Harmer
3.453
964781AG1-341 GEN
Solar/Wind Harmer
4.318
970653AG2-424 GEN
Solar/Wind Harmer
1.72
970653AG2-424 GEN
Solar/Wind Harmer
0.972
970273AG2-179 GEN
Solar/Wind Harmer
3.939
970273AG2-179 GEN
Solar/Wind Harmer
3.856
971081AG2-670 GEN
Solar/Wind Harmer
5.333
962251AG1-071 GEN
Solar/Wind Harmer
3.055
960741AF2-365 GEN
Solar/Wind Harmer
2.323
971155AH1-034 GEN
Solar/Wind Harmer
6.309
962241AG1-070 GEN
Solar/Wind Harmer
2.499
972273AH1-721 GEN
50/50
419.661
966021AG1-471 GEN
Solar/Wind Harmer
5.989
971485AH1-239 GEN
Solar/Wind Harmer
8.472
964901AG1-354 GEN
Solar/Wind Harmer
9.833
964781AG1-341 GEN
Solar/Wind Harmer
7.851
971821AH1-427 GEN
Solar/Wind Harmer
3.968
950011AG9-010
External Queue
7.131826877593994
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.975
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.587
MECLTFEXP_MEC->PJM
CLTF
0.697
SIGELTFEXP_SIGE->PJM
CLTF
0.025
LAGNLTFEXP_LAGN->PJM
CLTF
1.822
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.83
TVALTFEXP_TVA->PJM
CLTF
1.133
CPLELTFEXP_CPLE->PJM
CLTF
0.178
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.377
NYPJM->LTFIMP_NY
CLTF
0.077
LGEELTFEXP_LGEE->PJM
CLTF
0.08
WECLTFEXP_WEC->PJM
CLTF
0.084
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
5.985

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P2-3_LAURL S50-1014_SRT-A


Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_LAURL S50-1014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:199.28 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:593.84
MW Contribution:8.46
Bus #Bus NameTypeMW Contribution
965401AG1-405 GEN
Solar/Wind Harmer
4.916
965411AG1-406 GEN
Solar/Wind Harmer
3.45
964781AG1-341 GEN
Solar/Wind Harmer
4.312
970653AG2-424 GEN
Solar/Wind Harmer
1.717
970653AG2-424 GEN
Solar/Wind Harmer
0.971
970273AG2-179 GEN
Solar/Wind Harmer
3.931
970273AG2-179 GEN
Solar/Wind Harmer
3.849
971081AG2-670 GEN
Solar/Wind Harmer
5.326
962251AG1-071 GEN
Solar/Wind Harmer
3.05
960741AF2-365 GEN
Solar/Wind Harmer
2.319
972273AH1-721 GEN
50/50
419.289
966021AG1-471 GEN
Solar/Wind Harmer
5.979
971485AH1-239 GEN
Solar/Wind Harmer
8.457
964901AG1-354 GEN
Solar/Wind Harmer
9.819
964781AG1-341 GEN
Solar/Wind Harmer
7.839
971821AH1-427 GEN
Solar/Wind Harmer
3.965
971155AH1-034 GEN
Solar/Wind Harmer
6.299
962241AG1-070 GEN
Solar/Wind Harmer
2.496
950011AG9-010
External Queue
7.124643802642822
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.968
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.567
MECLTFEXP_MEC->PJM
CLTF
0.694
SIGELTFEXP_SIGE->PJM
CLTF
0.025
LAGNLTFEXP_LAGN->PJM
CLTF
1.812
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.818
TVALTFEXP_TVA->PJM
CLTF
1.126
CPLELTFEXP_CPLE->PJM
CLTF
0.175
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.333
NYPJM->LTFIMP_NY
CLTF
0.077
LGEELTFEXP_LGEE->PJM
CLTF
0.08
WECLTFEXP_WEC->PJM
CLTF
0.084
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
5.935

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P4-5_LAURL S50-1014_SRT-A


Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P4-5_LAURL S50-1014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:199.25 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:593.77
MW Contribution:8.46
Bus #Bus NameTypeMW Contribution
965401AG1-405 GEN
Solar/Wind Harmer
4.916
965411AG1-406 GEN
Solar/Wind Harmer
3.45
964781AG1-341 GEN
Solar/Wind Harmer
4.312
970653AG2-424 GEN
Solar/Wind Harmer
1.717
970653AG2-424 GEN
Solar/Wind Harmer
0.971
970273AG2-179 GEN
Solar/Wind Harmer
3.931
970273AG2-179 GEN
Solar/Wind Harmer
3.849
971081AG2-670 GEN
Solar/Wind Harmer
5.326
962251AG1-071 GEN
Solar/Wind Harmer
3.05
960741AF2-365 GEN
Solar/Wind Harmer
2.319
972273AH1-721 GEN
50/50
419.289
966021AG1-471 GEN
Solar/Wind Harmer
5.979
971485AH1-239 GEN
Solar/Wind Harmer
8.457
964901AG1-354 GEN
Solar/Wind Harmer
9.819
964781AG1-341 GEN
Solar/Wind Harmer
7.839
971821AH1-427 GEN
Solar/Wind Harmer
3.965
971155AH1-034 GEN
Solar/Wind Harmer
6.299
962241AG1-070 GEN
Solar/Wind Harmer
2.496
950011AG9-010
External Queue
7.124643802642822
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.968
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.567
MECLTFEXP_MEC->PJM
CLTF
0.694
SIGELTFEXP_SIGE->PJM
CLTF
0.025
LAGNLTFEXP_LAGN->PJM
CLTF
1.812
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.818
TVALTFEXP_TVA->PJM
CLTF
1.126
CPLELTFEXP_CPLE->PJM
CLTF
0.175
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.333
NYPJM->LTFIMP_NY
CLTF
0.077
LGEELTFEXP_LGEE->PJM
CLTF
0.08
WECLTFEXP_WEC->PJM
CLTF
0.084
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
5.935

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P2-2_LAUREL CO 161_SRT-A


Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_LAUREL CO 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:199.25 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:593.75
MW Contribution:8.46
Bus #Bus NameTypeMW Contribution
965401AG1-405 GEN
Solar/Wind Harmer
4.916
965411AG1-406 GEN
Solar/Wind Harmer
3.45
964781AG1-341 GEN
Solar/Wind Harmer
4.312
970653AG2-424 GEN
Solar/Wind Harmer
1.717
970653AG2-424 GEN
Solar/Wind Harmer
0.971
970273AG2-179 GEN
Solar/Wind Harmer
3.931
970273AG2-179 GEN
Solar/Wind Harmer
3.849
971081AG2-670 GEN
Solar/Wind Harmer
5.326
962251AG1-071 GEN
Solar/Wind Harmer
3.05
960741AF2-365 GEN
Solar/Wind Harmer
2.319
972273AH1-721 GEN
50/50
419.289
966021AG1-471 GEN
Solar/Wind Harmer
5.979
971485AH1-239 GEN
Solar/Wind Harmer
8.457
964901AG1-354 GEN
Solar/Wind Harmer
9.819
964781AG1-341 GEN
Solar/Wind Harmer
7.839
971821AH1-427 GEN
Solar/Wind Harmer
3.965
971155AH1-034 GEN
Solar/Wind Harmer
6.299
962241AG1-070 GEN
Solar/Wind Harmer
2.496
950011AG9-010
External Queue
7.124643802642822
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.968
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.567
MECLTFEXP_MEC->PJM
CLTF
0.694
SIGELTFEXP_SIGE->PJM
CLTF
0.025
LAGNLTFEXP_LAGN->PJM
CLTF
1.812
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.818
TVALTFEXP_TVA->PJM
CLTF
1.126
CPLELTFEXP_CPLE->PJM
CLTF
0.175
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.333
NYPJM->LTFIMP_NY
CLTF
0.077
LGEELTFEXP_LGEE->PJM
CLTF
0.08
WECLTFEXP_WEC->PJM
CLTF
0.084
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
5.935

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P4-5_LAURL S50-1024_SRT-A


Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P4-5_LAURL S50-1024_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:199.06 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:593.21
MW Contribution:8.44
Bus #Bus NameTypeMW Contribution
965401AG1-405 GEN
Solar/Wind Harmer
4.909
965411AG1-406 GEN
Solar/Wind Harmer
3.445
964781AG1-341 GEN
Solar/Wind Harmer
4.305
970653AG2-424 GEN
Solar/Wind Harmer
1.715
970653AG2-424 GEN
Solar/Wind Harmer
0.969
970273AG2-179 GEN
Solar/Wind Harmer
3.924
970273AG2-179 GEN
Solar/Wind Harmer
3.841
971081AG2-670 GEN
Solar/Wind Harmer
5.318
962251AG1-071 GEN
Solar/Wind Harmer
3.045
960741AF2-365 GEN
Solar/Wind Harmer
2.316
972273AH1-721 GEN
50/50
418.932
966021AG1-471 GEN
Solar/Wind Harmer
5.969
971485AH1-239 GEN
Solar/Wind Harmer
8.443
964901AG1-354 GEN
Solar/Wind Harmer
9.804
964781AG1-341 GEN
Solar/Wind Harmer
7.827
971821AH1-427 GEN
Solar/Wind Harmer
3.914
971155AH1-034 GEN
Solar/Wind Harmer
6.289
962241AG1-070 GEN
Solar/Wind Harmer
2.491
950011AG9-010
External Queue
7.1139235496521
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.958
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.545
MECLTFEXP_MEC->PJM
CLTF
0.691
SIGELTFEXP_SIGE->PJM
CLTF
0.025
LAGNLTFEXP_LAGN->PJM
CLTF
1.801
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.806
TVALTFEXP_TVA->PJM
CLTF
1.119
CPLELTFEXP_CPLE->PJM
CLTF
0.172
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.284
NYPJM->LTFIMP_NY
CLTF
0.077
LGEELTFEXP_LGEE->PJM
CLTF
0.079
WECLTFEXP_WEC->PJM
CLTF
0.083
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
5.888

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P2-3_LAURL S50-1024_SRT-A


Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_LAURL S50-1024_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:199.06 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:593.19
MW Contribution:8.44
Bus #Bus NameTypeMW Contribution
965401AG1-405 GEN
Solar/Wind Harmer
4.909
965411AG1-406 GEN
Solar/Wind Harmer
3.445
964781AG1-341 GEN
Solar/Wind Harmer
4.305
970653AG2-424 GEN
Solar/Wind Harmer
1.715
970653AG2-424 GEN
Solar/Wind Harmer
0.969
970273AG2-179 GEN
Solar/Wind Harmer
3.924
970273AG2-179 GEN
Solar/Wind Harmer
3.841
971081AG2-670 GEN
Solar/Wind Harmer
5.318
962251AG1-071 GEN
Solar/Wind Harmer
3.045
960741AF2-365 GEN
Solar/Wind Harmer
2.316
972273AH1-721 GEN
50/50
418.932
966021AG1-471 GEN
Solar/Wind Harmer
5.969
971485AH1-239 GEN
Solar/Wind Harmer
8.443
964901AG1-354 GEN
Solar/Wind Harmer
9.804
964781AG1-341 GEN
Solar/Wind Harmer
7.827
971821AH1-427 GEN
Solar/Wind Harmer
3.914
971155AH1-034 GEN
Solar/Wind Harmer
6.289
962241AG1-070 GEN
Solar/Wind Harmer
2.491
950011AG9-010
External Queue
7.1139235496521
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.958
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.545
MECLTFEXP_MEC->PJM
CLTF
0.691
SIGELTFEXP_SIGE->PJM
CLTF
0.025
LAGNLTFEXP_LAGN->PJM
CLTF
1.801
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.806
TVALTFEXP_TVA->PJM
CLTF
1.119
CPLELTFEXP_CPLE->PJM
CLTF
0.172
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.284
NYPJM->LTFIMP_NY
CLTF
0.077
LGEELTFEXP_LGEE->PJM
CLTF
0.079
WECLTFEXP_WEC->PJM
CLTF
0.083
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
5.888

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P7-1_LAURL 161 DBL_SRT-A


Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_LAURL 161 DBL_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:199.05 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:593.16
MW Contribution:8.44
Bus #Bus NameTypeMW Contribution
965401AG1-405 GEN
Solar/Wind Harmer
4.909
965411AG1-406 GEN
Solar/Wind Harmer
3.445
964781AG1-341 GEN
Solar/Wind Harmer
4.305
970653AG2-424 GEN
Solar/Wind Harmer
1.715
970653AG2-424 GEN
Solar/Wind Harmer
0.969
970273AG2-179 GEN
Solar/Wind Harmer
3.924
970273AG2-179 GEN
Solar/Wind Harmer
3.841
971081AG2-670 GEN
Solar/Wind Harmer
5.318
962251AG1-071 GEN
Solar/Wind Harmer
3.045
960741AF2-365 GEN
Solar/Wind Harmer
2.316
971155AH1-034 GEN
Solar/Wind Harmer
6.289
962241AG1-070 GEN
Solar/Wind Harmer
2.491
972273AH1-721 GEN
50/50
418.932
966021AG1-471 GEN
Solar/Wind Harmer
5.969
971485AH1-239 GEN
Solar/Wind Harmer
8.443
964901AG1-354 GEN
Solar/Wind Harmer
9.804
964781AG1-341 GEN
Solar/Wind Harmer
7.827
971821AH1-427 GEN
Solar/Wind Harmer
3.914
950011AG9-010
External Queue
7.1139235496521
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.958
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.545
MECLTFEXP_MEC->PJM
CLTF
0.691
SIGELTFEXP_SIGE->PJM
CLTF
0.025
LAGNLTFEXP_LAGN->PJM
CLTF
1.801
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.806
TVALTFEXP_TVA->PJM
CLTF
1.119
CPLELTFEXP_CPLE->PJM
CLTF
0.172
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.284
NYPJM->LTFIMP_NY
CLTF
0.077
LGEELTFEXP_LGEE->PJM
CLTF
0.079
WECLTFEXP_WEC->PJM
CLTF
0.083
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
5.888

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P1-2_COOP 161 TIE_SRT-A


Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_COOP 161 TIE_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:195.41 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:582.33
MW Contribution:3.7
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
561.572
966021AG1-471 GEN
Solar/Wind Harmer
2.764
971485AH1-239 GEN
Solar/Wind Harmer
3.703
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.03
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.239
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.144
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.452
LAGNLTFEXP_LAGN->PJM
CLTF
0.168
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.115
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.129
CPLELTFEXP_CPLE->PJM
CLTF
0.024
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.194
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.017
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
3.364

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P1-2_LAUR-L DAM161_SRT-A


Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_LAUR-L DAM161_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:195.41 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:582.33
MW Contribution:8.47
Bus #Bus NameTypeMW Contribution
965401AG1-405 GEN
Solar/Wind Harmer
4.921
965411AG1-406 GEN
Solar/Wind Harmer
3.453
970653AG2-424 GEN
Solar/Wind Harmer
1.72
970653AG2-424 GEN
Solar/Wind Harmer
0.972
970273AG2-179 GEN
Solar/Wind Harmer
3.939
970273AG2-179 GEN
Solar/Wind Harmer
3.856
971081AG2-670 GEN
Solar/Wind Harmer
5.333
962251AG1-071 GEN
Solar/Wind Harmer
3.055
960741AF2-365 GEN
Solar/Wind Harmer
2.323
972273AH1-721 GEN
50/50
419.661
966021AG1-471 GEN
Solar/Wind Harmer
5.989
971485AH1-239 GEN
Solar/Wind Harmer
8.472
964901AG1-354 GEN
Solar/Wind Harmer
9.833
971821AH1-427 GEN
Solar/Wind Harmer
3.968
971155AH1-034 GEN
Solar/Wind Harmer
6.309
962241AG1-070 GEN
Solar/Wind Harmer
2.499
950011AG9-010
External Queue
7.131826877593994
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.975
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.587
MECLTFEXP_MEC->PJM
CLTF
0.697
SIGELTFEXP_SIGE->PJM
CLTF
0.025
LAGNLTFEXP_LAGN->PJM
CLTF
1.822
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.83
TVALTFEXP_TVA->PJM
CLTF
1.133
CPLELTFEXP_CPLE->PJM
CLTF
0.178
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.377
NYPJM->LTFIMP_NY
CLTF
0.077
LGEELTFEXP_LGEE->PJM
CLTF
0.08
WECLTFEXP_WEC->PJM
CLTF
0.084
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
5.985

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1014_SRT-A


Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:195.32 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:582.04
MW Contribution:3.96
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
557.857
966021AG1-471 GEN
Solar/Wind Harmer
2.95
971485AH1-239 GEN
Solar/Wind Harmer
3.958
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.437
MECLTFEXP_MEC->PJM
CLTF
0.002
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.15
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.464
LAGNLTFEXP_LAGN->PJM
CLTF
0.271
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.198
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.194
CPLELTFEXP_CPLE->PJM
CLTF
0.046
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.665
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.017
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
3.98

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 1 161_SRT-A


Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 1 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:195.21 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:581.72
MW Contribution:3.82
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
559.729
966021AG1-471 GEN
Solar/Wind Harmer
2.848
971485AH1-239 GEN
Solar/Wind Harmer
3.823
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.333
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.147
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.457
LAGNLTFEXP_LAGN->PJM
CLTF
0.217
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.152
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.16
CPLELTFEXP_CPLE->PJM
CLTF
0.034
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.42
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.017
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
3.65

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:191.57 %
Rating:249.0 MVA
Rating Type:A
MVA to Mitigate:477.02
MW Contribution:7.22
Bus #Bus NameTypeMW Contribution
965401AG1-405 GEN
Solar/Wind Harmer
3.871
965411AG1-406 GEN
Solar/Wind Harmer
2.716
970653AG2-424 GEN
Solar/Wind Harmer
1.452
970653AG2-424 GEN
Solar/Wind Harmer
0.821
970273AG2-179 GEN
Solar/Wind Harmer
3.197
970273AG2-179 GEN
Solar/Wind Harmer
3.13
971081AG2-670 GEN
Solar/Wind Harmer
4.567
962251AG1-071 GEN
Solar/Wind Harmer
2.595
960741AF2-365 GEN
Solar/Wind Harmer
1.97
972273AH1-721 GEN
50/50
363.844
966021AG1-471 GEN
Solar/Wind Harmer
5.108
971485AH1-239 GEN
Solar/Wind Harmer
7.222
964901AG1-354 GEN
Solar/Wind Harmer
8.392
971821AH1-427 GEN
Solar/Wind Harmer
4.133
971155AH1-034 GEN
Solar/Wind Harmer
5.348
962241AG1-070 GEN
Solar/Wind Harmer
2.123
950011AG9-010
External Queue
6.188554286956787
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.379
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.858
MECLTFEXP_MEC->PJM
CLTF
0.557
SIGELTFEXP_SIGE->PJM
CLTF
0.018
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.019
LAGNLTFEXP_LAGN->PJM
CLTF
1.477
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.653
TVALTFEXP_TVA->PJM
CLTF
0.92
CPLELTFEXP_CPLE->PJM
CLTF
0.142
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.474
NYPJM->LTFIMP_NY
CLTF
0.056
LGEELTFEXP_LGEE->PJM
CLTF
0.008
WECLTFEXP_WEC->PJM
CLTF
0.066
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
5.637

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P2-2_COOP-LAURD 161_SRT-A


Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOP-LAURD 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:187.53 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:558.83
MW Contribution:8.49
Bus #Bus NameTypeMW Contribution
965401AG1-405 GEN
Solar/Wind Harmer
4.935
965411AG1-406 GEN
Solar/Wind Harmer
3.463
964781AG1-341 GEN
Solar/Wind Harmer
4.335
970653AG2-424 GEN
Solar/Wind Harmer
1.731
970653AG2-424 GEN
Solar/Wind Harmer
0.979
970273AG2-179 GEN
Solar/Wind Harmer
3.948
970273AG2-179 GEN
Solar/Wind Harmer
3.865
971081AG2-670 GEN
Solar/Wind Harmer
5.351
962251AG1-071 GEN
Solar/Wind Harmer
3.068
960741AF2-365 GEN
Solar/Wind Harmer
2.335
972273AH1-721 GEN
50/50
419.998
966021AG1-471 GEN
Solar/Wind Harmer
6.002
971485AH1-239 GEN
Solar/Wind Harmer
8.491
964901AG1-354 GEN
Solar/Wind Harmer
9.87
964781AG1-341 GEN
Solar/Wind Harmer
7.881
971821AH1-427 GEN
Solar/Wind Harmer
3.993
971155AH1-034 GEN
Solar/Wind Harmer
6.333
962241AG1-070 GEN
Solar/Wind Harmer
2.51
950011AG9-010
External Queue
7.131826877593994
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.535
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.733
MECLTFEXP_MEC->PJM
CLTF
0.761
SIGELTFEXP_SIGE->PJM
CLTF
0.027
LAGNLTFEXP_LAGN->PJM
CLTF
1.9
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.946
TVALTFEXP_TVA->PJM
CLTF
1.172
CPLELTFEXP_CPLE->PJM
CLTF
0.22
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.893
NYPJM->LTFIMP_NY
CLTF
0.053
LGEELTFEXP_LGEE->PJM
CLTF
0.106
WECLTFEXP_WEC->PJM
CLTF
0.098
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
5.985

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 1_SRT-A


Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 1_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:176.12 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:524.85
MW Contribution:4.95
Bus #Bus NameTypeMW Contribution
965401AG1-405 GEN
Solar/Wind Harmer
3.307
965411AG1-406 GEN
Solar/Wind Harmer
2.321
970273AG2-179 GEN
Solar/Wind Harmer
1.702
970273AG2-179 GEN
Solar/Wind Harmer
1.666
972273AH1-721 GEN
50/50
498.296
966021AG1-471 GEN
Solar/Wind Harmer
3.631
971485AH1-239 GEN
Solar/Wind Harmer
4.948
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.775
MECLTFEXP_MEC->PJM
CLTF
0.08
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.133
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.393
LAGNLTFEXP_LAGN->PJM
CLTF
0.439
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.251
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.296
CPLELTFEXP_CPLE->PJM
CLTF
0.056
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.618
NYPJM->LTFIMP_NY
CLTF
0.024
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
4.223

Details for 5COOPER2-5ELIHU 161.0 kV Ckt 1 line l/o EKPC_P2-2_PULASKI 161_SRT-A


Base Case Flowgate

Area:EKPC/LGEE
Facility Description:
5COOPER2-5ELIHU 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_PULASKI 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:171.77 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:511.87
MW Contribution:7.71
Bus #Bus NameTypeMW Contribution
964781AG1-341 GEN
Solar/Wind Harmer
3.354
965401AG1-405 GEN
Solar/Wind Harmer
1.662
965411AG1-406 GEN
Solar/Wind Harmer
1.166
970273AG2-179 GEN
Solar/Wind Harmer
2.713
970273AG2-179 GEN
Solar/Wind Harmer
2.656
962251AG1-071 GEN
Solar/Wind Harmer
2.277
960741AF2-365 GEN
Solar/Wind Harmer
1.5
971081AG2-670 GEN
Solar/Wind Harmer
2.169
972273AH1-721 GEN
50/50
415.113
966021AG1-471 GEN
Solar/Wind Harmer
5.521
971485AH1-239 GEN
Solar/Wind Harmer
7.708
964781AG1-341 GEN
Solar/Wind Harmer
6.099
964901AG1-354 GEN
Solar/Wind Harmer
6.249
971155AH1-034 GEN
Solar/Wind Harmer
4.756
962241AG1-070 GEN
Solar/Wind Harmer
1.863
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.762
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.888
MECLTFEXP_MEC->PJM
CLTF
0.482
SIGELTFEXP_SIGE->PJM
CLTF
0.007
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.13
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.307
LAGNLTFEXP_LAGN->PJM
CLTF
1.525
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.948
TVALTFEXP_TVA->PJM
CLTF
0.972
CPLELTFEXP_CPLE->PJM
CLTF
0.234
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.974
NYPJM->LTFIMP_NY
CLTF
0.039
WECLTFEXP_WEC->PJM
CLTF
0.047
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
8.963

Details for 5LAUREL CO-5PITTSBURG 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL CO-5PITTSBURG 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:166.78 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:333.56
MW Contribution:2.63
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
289.327
966021AG1-471 GEN
Solar/Wind Harmer
1.93
971485AH1-239 GEN
Solar/Wind Harmer
2.629
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.257
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.142
MECLTFEXP_MEC->PJM
CLTF
0.14
SIGELTFEXP_SIGE->PJM
CLTF
0.003
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.026
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.049
LAGNLTFEXP_LAGN->PJM
CLTF
0.569
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.534
TVALTFEXP_TVA->PJM
CLTF
0.374
CPLELTFEXP_CPLE->PJM
CLTF
0.136
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.49
NYPJM->LTFIMP_NY
CLTF
0.022
WECLTFEXP_WEC->PJM
CLTF
0.008
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
3.02

Details for 5LAUREL CO-5PITTSBURG 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL CO-5PITTSBURG 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:166.77 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:333.53
MW Contribution:2.62
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
287.75
966021AG1-471 GEN
Solar/Wind Harmer
1.919
971485AH1-239 GEN
Solar/Wind Harmer
2.618
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.297
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.158
MECLTFEXP_MEC->PJM
CLTF
0.147
SIGELTFEXP_SIGE->PJM
CLTF
0.004
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.022
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.033
LAGNLTFEXP_LAGN->PJM
CLTF
0.577
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.529
TVALTFEXP_TVA->PJM
CLTF
0.378
CPLELTFEXP_CPLE->PJM
CLTF
0.134
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.555
NYPJM->LTFIMP_NY
CLTF
0.023
WECLTFEXP_WEC->PJM
CLTF
0.009
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
2.928

Details for 5LAUREL CO-5PITTSBURG 161.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL CO-5PITTSBURG 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:166.77 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:333.53
MW Contribution:2.62
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
287.75
966021AG1-471 GEN
Solar/Wind Harmer
1.919
971485AH1-239 GEN
Solar/Wind Harmer
2.618
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.297
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.158
MECLTFEXP_MEC->PJM
CLTF
0.147
SIGELTFEXP_SIGE->PJM
CLTF
0.004
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.022
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.033
LAGNLTFEXP_LAGN->PJM
CLTF
0.577
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.529
TVALTFEXP_TVA->PJM
CLTF
0.378
CPLELTFEXP_CPLE->PJM
CLTF
0.134
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.555
NYPJM->LTFIMP_NY
CLTF
0.023
WECLTFEXP_WEC->PJM
CLTF
0.009
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
2.928

Details for 5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:279.15 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:558.31
MW Contribution:3.84
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
477.315
966021AG1-471 GEN
Solar/Wind Harmer
2.827
971485AH1-239 GEN
Solar/Wind Harmer
3.836
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.109
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.924
MECLTFEXP_MEC->PJM
CLTF
0.112
SIGELTFEXP_SIGE->PJM
CLTF
0.003
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.025
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.046
LAGNLTFEXP_LAGN->PJM
CLTF
0.461
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.288
TVALTFEXP_TVA->PJM
CLTF
0.304
CPLELTFEXP_CPLE->PJM
CLTF
0.059
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.045
NYPJM->LTFIMP_NY
CLTF
0.039
WECLTFEXP_WEC->PJM
CLTF
0.004
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
2.428

Details for 5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:279.13 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:558.26
MW Contribution:3.81
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
475.503
966021AG1-471 GEN
Solar/Wind Harmer
2.806
971485AH1-239 GEN
Solar/Wind Harmer
3.812
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.151
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.937
MECLTFEXP_MEC->PJM
CLTF
0.118
SIGELTFEXP_SIGE->PJM
CLTF
0.003
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.02
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.027
LAGNLTFEXP_LAGN->PJM
CLTF
0.466
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.278
TVALTFEXP_TVA->PJM
CLTF
0.306
CPLELTFEXP_CPLE->PJM
CLTF
0.056
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.105
NYPJM->LTFIMP_NY
CLTF
0.04
WECLTFEXP_WEC->PJM
CLTF
0.005
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
2.293

Details for 5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:279.13 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:558.25
MW Contribution:3.81
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
475.503
966021AG1-471 GEN
Solar/Wind Harmer
2.806
971485AH1-239 GEN
Solar/Wind Harmer
3.812
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.151
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.937
MECLTFEXP_MEC->PJM
CLTF
0.118
SIGELTFEXP_SIGE->PJM
CLTF
0.003
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.02
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.027
LAGNLTFEXP_LAGN->PJM
CLTF
0.466
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.278
TVALTFEXP_TVA->PJM
CLTF
0.306
CPLELTFEXP_CPLE->PJM
CLTF
0.056
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.105
NYPJM->LTFIMP_NY
CLTF
0.04
WECLTFEXP_WEC->PJM
CLTF
0.005
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
2.293

Details for 5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line l/o EXT_324130 5ALCALDE 161 324141 5ELIHU 161 1_SRT-L


Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EXT_324130 5ALCALDE 161 324141 5ELIHU 161 1_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:150.23 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:300.46
MW Contribution:4.47
Bus #Bus NameTypeMW Contribution
965401AG1-405 GEN
Solar/Wind Harmer
4.597
965411AG1-406 GEN
Solar/Wind Harmer
3.226
970273AG2-179 GEN
Solar/Wind Harmer
2.773
970273AG2-179 GEN
Solar/Wind Harmer
2.715
971081AG2-670 GEN
Solar/Wind Harmer
2.681
962251AG1-071 GEN
Solar/Wind Harmer
1.605
972273AH1-721 GEN
50/50
186.846
966021AG1-471 GEN
Solar/Wind Harmer
3.154
971485AH1-239 GEN
Solar/Wind Harmer
4.469
964901AG1-354 GEN
Solar/Wind Harmer
5.043
971155AH1-034 GEN
Solar/Wind Harmer
3.386
962241AG1-070 GEN
Solar/Wind Harmer
1.313
950011AG9-010
External Queue
3.442777395248413
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.75
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.146
MECLTFEXP_MEC->PJM
CLTF
0.412
SIGELTFEXP_SIGE->PJM
CLTF
0.018
LAGNLTFEXP_LAGN->PJM
CLTF
1.057
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.518
TVALTFEXP_TVA->PJM
CLTF
0.656
CPLELTFEXP_CPLE->PJM
CLTF
0.11
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.587
NYPJM->LTFIMP_NY
CLTF
0.053
LGEELTFEXP_LGEE->PJM
CLTF
0.118
WECLTFEXP_WEC->PJM
CLTF
0.05
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
2.524

Details for 5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-1


Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:130.77 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:261.53
MW Contribution:3.55
Bus #Bus NameTypeMW Contribution
965401AG1-405 GEN
Solar/Wind Harmer
2.533
965411AG1-406 GEN
Solar/Wind Harmer
1.777
970273AG2-179 GEN
Solar/Wind Harmer
1.881
970273AG2-179 GEN
Solar/Wind Harmer
1.842
971081AG2-670 GEN
Solar/Wind Harmer
2.195
972273AH1-721 GEN
50/50
168.382
966021AG1-471 GEN
Solar/Wind Harmer
2.507
971485AH1-239 GEN
Solar/Wind Harmer
3.551
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.472
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.794
MECLTFEXP_MEC->PJM
CLTF
0.346
SIGELTFEXP_SIGE->PJM
CLTF
0.016
LAGNLTFEXP_LAGN->PJM
CLTF
0.874
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.427
TVALTFEXP_TVA->PJM
CLTF
0.541
CPLELTFEXP_CPLE->PJM
CLTF
0.089
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.686
NYPJM->LTFIMP_NY
CLTF
0.047
LGEELTFEXP_LGEE->PJM
CLTF
0.122
WECLTFEXP_WEC->PJM
CLTF
0.043
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.718

Details for 5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line l/o EKPC_P1-2_COOP-ELIHU161_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_COOP-ELIHU161_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:130.05 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:260.09
MW Contribution:3.55
Bus #Bus NameTypeMW Contribution
965401AG1-405 GEN
Solar/Wind Harmer
2.542
965411AG1-406 GEN
Solar/Wind Harmer
1.784
970273AG2-179 GEN
Solar/Wind Harmer
1.887
970273AG2-179 GEN
Solar/Wind Harmer
1.848
971081AG2-670 GEN
Solar/Wind Harmer
2.203
972273AH1-721 GEN
50/50
166.806
966021AG1-471 GEN
Solar/Wind Harmer
2.506
971485AH1-239 GEN
Solar/Wind Harmer
3.55
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.479
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.799
MECLTFEXP_MEC->PJM
CLTF
0.347
SIGELTFEXP_SIGE->PJM
CLTF
0.016
LAGNLTFEXP_LAGN->PJM
CLTF
0.876
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.428
TVALTFEXP_TVA->PJM
CLTF
0.543
CPLELTFEXP_CPLE->PJM
CLTF
0.089
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.699
NYPJM->LTFIMP_NY
CLTF
0.047
LGEELTFEXP_LGEE->PJM
CLTF
0.123
WECLTFEXP_WEC->PJM
CLTF
0.043
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.715

Details for 5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line l/o EKPC_P2-2_ELIHU-COOP 161_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
5LAUREL DAM-5LAUREL CO 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_ELIHU-COOP 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:130.05 %
Rating:200.0 MVA
Rating Type:B
MVA to Mitigate:260.09
MW Contribution:3.55
Bus #Bus NameTypeMW Contribution
965401AG1-405 GEN
Solar/Wind Harmer
2.542
965411AG1-406 GEN
Solar/Wind Harmer
1.784
970273AG2-179 GEN
Solar/Wind Harmer
1.887
970273AG2-179 GEN
Solar/Wind Harmer
1.848
971081AG2-670 GEN
Solar/Wind Harmer
2.203
972273AH1-721 GEN
50/50
166.806
966021AG1-471 GEN
Solar/Wind Harmer
2.506
971485AH1-239 GEN
Solar/Wind Harmer
3.55
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.479
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.799
MECLTFEXP_MEC->PJM
CLTF
0.347
SIGELTFEXP_SIGE->PJM
CLTF
0.016
LAGNLTFEXP_LAGN->PJM
CLTF
0.876
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.428
TVALTFEXP_TVA->PJM
CLTF
0.543
CPLELTFEXP_CPLE->PJM
CLTF
0.089
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.699
NYPJM->LTFIMP_NY
CLTF
0.047
LGEELTFEXP_LGEE->PJM
CLTF
0.123
WECLTFEXP_WEC->PJM
CLTF
0.043
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.715

Details for [AH1-239] AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line l/o EKPC_P1-2_AH1-239 TP-2UPCHURCH T-69_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_AH1-239 TP-2UPCHURCH T-69_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:151.39 %
Rating:54.0 MVA
Rating Type:B
MVA to Mitigate:81.75
MW Contribution:80.0
IPD Plant:AH1-239
Bus #Bus NameTypeMW Contribution
971485AH1-239 GEN
PJM_IPD
80

Details for AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line l/o EKPC_P1-2_AH1-239 TP-2UPCHURCH T-69_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_AH1-239 TP-2UPCHURCH T-69_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:136.22 %
Rating:54.0 MVA
Rating Type:B
MVA to Mitigate:73.56
MW Contribution:44.0
Bus #Bus NameTypeMW Contribution
971485AH1-239 GEN
Solar/Wind Harmer
44
966021AG1-471 GEN
Solar/Wind Harmer
29.7

Details for [AH1-239] AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:EKPC
Facility Description:
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:125.28 %
Rating:49.0 MVA
Rating Type:A
MVA to Mitigate:61.39
MW Contribution:61.44
IPD Plant:AH1-239
Bus #Bus NameTypeMW Contribution
971485AH1-239 GEN
PJM_IPD
61.435

Details for AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:EKPC
Facility Description:
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.97 %
Rating:49.0 MVA
Rating Type:A
MVA to Mitigate:58.29
MW Contribution:33.79
Bus #Bus NameTypeMW Contribution
966021AG1-471 GEN
Solar/Wind Harmer
25.466
971485AH1-239 GEN
Solar/Wind Harmer
33.789
971155AH1-034 GEN
Solar/Wind Harmer
2.847
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.014
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.349
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.094
MECLTFEXP_MEC->PJM
CLTF
0.054
SIGELTFEXP_SIGE->PJM
CLTF
0.004
LAGNLTFEXP_LAGN->PJM
CLTF
0.038
TVALTFEXP_TVA->PJM
CLTF
0.014
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.484
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.007
LGEELTFEXP_LGEE->PJM
CLTF
0.053
WECLTFEXP_WEC->PJM
CLTF
0.01
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.02

Details for [AH1-239] AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line l/o EXT_324106 7HARDIN CO 345 325140 7GLENDALE S 345 1_SRT-L


Base Case Flowgate

Area:EKPC
Facility Description:
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
Contingency Name:
EXT_324106 7HARDIN CO 345 325140 7GLENDALE S 345 1_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.84 %
Rating:54.0 MVA
Rating Type:B
MVA to Mitigate:63.09
MW Contribution:61.43
IPD Plant:AH1-239
Bus #Bus NameTypeMW Contribution
971485AH1-239 GEN
PJM_IPD
61.429

Details for [AH1-239] AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line l/o EKPC_P2-3_MAR W38-1014_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_MAR W38-1014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.02 %
Rating:54.0 MVA
Rating Type:B
MVA to Mitigate:62.65
MW Contribution:61.46
IPD Plant:AH1-239
Bus #Bus NameTypeMW Contribution
971485AH1-239 GEN
PJM_IPD
61.456

Details for [AH1-239] AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line l/o EKPC_P2-2_SUMMSHADE 161 #1_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_SUMMSHADE 161 #1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:115.71 %
Rating:54.0 MVA
Rating Type:B
MVA to Mitigate:62.49
MW Contribution:62.65
IPD Plant:AH1-239
Bus #Bus NameTypeMW Contribution
971485AH1-239 GEN
PJM_IPD
62.647

Details for [AH1-239] AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line l/o EKPC_P2-3_CASEY S89-1008_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_CASEY S89-1008_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.83 %
Rating:54.0 MVA
Rating Type:B
MVA to Mitigate:62.01
MW Contribution:61.41
IPD Plant:AH1-239
Bus #Bus NameTypeMW Contribution
971485AH1-239 GEN
PJM_IPD
61.407

Details for [AH1-239] AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line l/o EKPC_P2-2_CASEY CO 161_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_CASEY CO 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:114.83 %
Rating:54.0 MVA
Rating Type:B
MVA to Mitigate:62.01
MW Contribution:61.41
IPD Plant:AH1-239
Bus #Bus NameTypeMW Contribution
971485AH1-239 GEN
PJM_IPD
61.407

Details for [AH1-239] AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-1


Base Case Flowgate

Area:EKPC
Facility Description:
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:113.47 %
Rating:54.0 MVA
Rating Type:B
MVA to Mitigate:61.28
MW Contribution:61.34
IPD Plant:AH1-239
Bus #Bus NameTypeMW Contribution
971485AH1-239 GEN
PJM_IPD
61.343

Details for [AH1-239] AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-2


Base Case Flowgate

Area:EKPC
Facility Description:
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:113.26 %
Rating:54.0 MVA
Rating Type:B
MVA to Mitigate:61.16
MW Contribution:61.27
IPD Plant:AH1-239
Bus #Bus NameTypeMW Contribution
971485AH1-239 GEN
PJM_IPD
61.271

Details for AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line l/o EKPC_P2-2_SUMMSHADE 161 #1_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_SUMMSHADE 161 #1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:112.21 %
Rating:54.0 MVA
Rating Type:B
MVA to Mitigate:60.59
MW Contribution:34.46
Bus #Bus NameTypeMW Contribution
971155AH1-034 GEN
Solar/Wind Harmer
5.455
966021AG1-471 GEN
Solar/Wind Harmer
25.731
971485AH1-239 GEN
Solar/Wind Harmer
34.456
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.016
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.269
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.04
MECLTFEXP_MEC->PJM
CLTF
0.04
SIGELTFEXP_SIGE->PJM
CLTF
0.004
LAGNLTFEXP_LAGN->PJM
CLTF
0.01
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.34
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.008
LGEELTFEXP_LGEE->PJM
CLTF
0.044
WECLTFEXP_WEC->PJM
CLTF
0.008
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.023

Details for AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line l/o EKPC_P2-2_SUMMSHADE 161 #2_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_SUMMSHADE 161 #2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:111.61 %
Rating:54.0 MVA
Rating Type:B
MVA to Mitigate:60.27
MW Contribution:34.45
Bus #Bus NameTypeMW Contribution
971155AH1-034 GEN
Solar/Wind Harmer
5.579
966021AG1-471 GEN
Solar/Wind Harmer
25.715
971485AH1-239 GEN
Solar/Wind Harmer
34.446
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.019
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.244
MECLTFEXP_MEC->PJM
CLTF
0.033
SIGELTFEXP_SIGE->PJM
CLTF
0.004
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.239
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.009
LGEELTFEXP_LGEE->PJM
CLTF
0.047
WECLTFEXP_WEC->PJM
CLTF
0.008
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.028

Details for AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line l/o EKPC_P1-2_AH1-034 TP-2PATTON RD J-69_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_AH1-034 TP-2PATTON RD J-69_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:109.81 %
Rating:54.0 MVA
Rating Type:B
MVA to Mitigate:59.3
MW Contribution:33.85
Bus #Bus NameTypeMW Contribution
966021AG1-471 GEN
Solar/Wind Harmer
25.495
971485AH1-239 GEN
Solar/Wind Harmer
33.853
971155AH1-034 GEN
Solar/Wind Harmer
3.828
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.014
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.33
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.08
MECLTFEXP_MEC->PJM
CLTF
0.05
SIGELTFEXP_SIGE->PJM
CLTF
0.004
LAGNLTFEXP_LAGN->PJM
CLTF
0.03
TVALTFEXP_TVA->PJM
CLTF
0.009
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.441
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.007
LGEELTFEXP_LGEE->PJM
CLTF
0.053
WECLTFEXP_WEC->PJM
CLTF
0.01
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.021

Details for AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line l/o EKPC_P2-3_MAR W38-1014_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_MAR W38-1014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.84 %
Rating:54.0 MVA
Rating Type:B
MVA to Mitigate:58.77
MW Contribution:33.8
Bus #Bus NameTypeMW Contribution
966021AG1-471 GEN
Solar/Wind Harmer
25.469
971485AH1-239 GEN
Solar/Wind Harmer
33.801
971155AH1-034 GEN
Solar/Wind Harmer
2.923
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.014
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.376
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.123
MECLTFEXP_MEC->PJM
CLTF
0.06
SIGELTFEXP_SIGE->PJM
CLTF
0.005
LAGNLTFEXP_LAGN->PJM
CLTF
0.052
TVALTFEXP_TVA->PJM
CLTF
0.023
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.564
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.008
LGEELTFEXP_LGEE->PJM
CLTF
0.055
WECLTFEXP_WEC->PJM
CLTF
0.011
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.02

Details for AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line l/o EKPC_P4-2_MAR W38-1004_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P4-2_MAR W38-1004_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.68 %
Rating:54.0 MVA
Rating Type:B
MVA to Mitigate:58.69
MW Contribution:33.82
Bus #Bus NameTypeMW Contribution
966021AG1-471 GEN
Solar/Wind Harmer
25.481
971485AH1-239 GEN
Solar/Wind Harmer
33.817
971155AH1-034 GEN
Solar/Wind Harmer
2.927
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.012
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.374
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.13
MECLTFEXP_MEC->PJM
CLTF
0.06
SIGELTFEXP_SIGE->PJM
CLTF
0.004
LAGNLTFEXP_LAGN->PJM
CLTF
0.056
TVALTFEXP_TVA->PJM
CLTF
0.026
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.569
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.007
LGEELTFEXP_LGEE->PJM
CLTF
0.052
WECLTFEXP_WEC->PJM
CLTF
0.011
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.018

Details for AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line l/o EKPC_P7-1_BULL 161 DBL_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_BULL 161 DBL_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:108.13 %
Rating:54.0 MVA
Rating Type:B
MVA to Mitigate:58.39
MW Contribution:33.83
Bus #Bus NameTypeMW Contribution
966021AG1-471 GEN
Solar/Wind Harmer
25.488
971485AH1-239 GEN
Solar/Wind Harmer
33.825
971155AH1-034 GEN
Solar/Wind Harmer
2.915
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.011
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.347
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.124
MECLTFEXP_MEC->PJM
CLTF
0.057
SIGELTFEXP_SIGE->PJM
CLTF
0.004
LAGNLTFEXP_LAGN->PJM
CLTF
0.058
TVALTFEXP_TVA->PJM
CLTF
0.028
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.551
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.007
LGEELTFEXP_LGEE->PJM
CLTF
0.039
WECLTFEXP_WEC->PJM
CLTF
0.01
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.017

Details for AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line l/o EKPC_P7-1_SSHAD 161 DBL_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
AG1-471 TP-2ZULA J NO 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_SSHAD 161 DBL_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:107.92 %
Rating:54.0 MVA
Rating Type:B
MVA to Mitigate:58.28
MW Contribution:33.82
Bus #Bus NameTypeMW Contribution
966021AG1-471 GEN
Solar/Wind Harmer
25.487
971485AH1-239 GEN
Solar/Wind Harmer
33.822
971155AH1-034 GEN
Solar/Wind Harmer
2.907
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.011
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.342
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.12
MECLTFEXP_MEC->PJM
CLTF
0.056
SIGELTFEXP_SIGE->PJM
CLTF
0.004
LAGNLTFEXP_LAGN->PJM
CLTF
0.057
TVALTFEXP_TVA->PJM
CLTF
0.027
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.542
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.007
LGEELTFEXP_LGEE->PJM
CLTF
0.038
WECLTFEXP_WEC->PJM
CLTF
0.01
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.017

Details for [AH1-239] AH1-239 TP-2UPCHURCH T 69.0 kV Ckt 1 line l/o EKPC_P1-2_AG1-471 TP-AH1-239 TP-69_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
AH1-239 TP-2UPCHURCH T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_AG1-471 TP-AH1-239 TP-69_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:151.02 %
Rating:54.0 MVA
Rating Type:B
MVA to Mitigate:81.55
MW Contribution:80.0
IPD Plant:AH1-239
Bus #Bus NameTypeMW Contribution
971485AH1-239 GEN
PJM_IPD
80

Details for [AH1-239] AH1-239 TP-2UPCHURCH T 69.0 kV Ckt 1 line l/o EKPC_P1-2_AG1-471 TP-2ZULA J NO-69_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
AH1-239 TP-2UPCHURCH T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_AG1-471 TP-2ZULA J NO-69_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:151.02 %
Rating:54.0 MVA
Rating Type:B
MVA to Mitigate:81.55
MW Contribution:80.0
IPD Plant:AH1-239
Bus #Bus NameTypeMW Contribution
971485AH1-239 GEN
PJM_IPD
80

Details for AH1-239 TP-2UPCHURCH T 69.0 kV Ckt 1 line l/o EKPC_P1-2_AG1-471 TP-2ZULA J NO-69_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
AH1-239 TP-2UPCHURCH T 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_AG1-471 TP-2ZULA J NO-69_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:136.2 %
Rating:54.0 MVA
Rating Type:B
MVA to Mitigate:73.55
MW Contribution:44.0
Bus #Bus NameTypeMW Contribution
971485AH1-239 GEN
Solar/Wind Harmer
44
966021AG1-471 GEN
Solar/Wind Harmer
29.7

Details for [AH1-239] AH1-239 TP-AG1-471 TP 69.0 kV Ckt 1 line l/o EKPC_P1-2_AH1-239 TP-2UPCHURCH T-69_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
AH1-239 TP-AG1-471 TP 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_AH1-239 TP-2UPCHURCH T-69_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:151.46 %
Rating:54.0 MVA
Rating Type:B
MVA to Mitigate:81.79
MW Contribution:80.0
IPD Plant:AH1-239
Bus #Bus NameTypeMW Contribution
971485AH1-239 GEN
PJM_IPD
80

Details for [AH1-239] AH1-239 TP-AG1-471 TP 69.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:EKPC
Facility Description:
AH1-239 TP-AG1-471 TP 69.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:125.38 %
Rating:49.0 MVA
Rating Type:A
MVA to Mitigate:61.44
MW Contribution:61.44
IPD Plant:AH1-239
Bus #Bus NameTypeMW Contribution
971485AH1-239 GEN
PJM_IPD
61.435

Details for [AH1-239] AH1-239 TP-AG1-471 TP 69.0 kV Ckt 1 line l/o EXT_324106 7HARDIN CO 345 325140 7GLENDALE S 345 1_SRT-L


Base Case Flowgate

Area:EKPC
Facility Description:
AH1-239 TP-AG1-471 TP 69.0 kV Ckt 1 line
Contingency Name:
EXT_324106 7HARDIN CO 345 325140 7GLENDALE S 345 1_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.93 %
Rating:54.0 MVA
Rating Type:B
MVA to Mitigate:63.14
MW Contribution:61.43
IPD Plant:AH1-239
Bus #Bus NameTypeMW Contribution
971485AH1-239 GEN
PJM_IPD
61.429

Details for [AH1-239] AH1-239 TP-AG1-471 TP 69.0 kV Ckt 1 line l/o EKPC_P2-3_MAR W38-1014_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
AH1-239 TP-AG1-471 TP 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_MAR W38-1014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.11 %
Rating:54.0 MVA
Rating Type:B
MVA to Mitigate:62.7
MW Contribution:61.46
IPD Plant:AH1-239
Bus #Bus NameTypeMW Contribution
971485AH1-239 GEN
PJM_IPD
61.456

Details for [AH1-239] AH1-239 TP-AG1-471 TP 69.0 kV Ckt 1 line l/o EKPC_P2-2_SUMMSHADE 161 #1_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
AH1-239 TP-AG1-471 TP 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_SUMMSHADE 161 #1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:115.8 %
Rating:54.0 MVA
Rating Type:B
MVA to Mitigate:62.53
MW Contribution:62.65
IPD Plant:AH1-239
Bus #Bus NameTypeMW Contribution
971485AH1-239 GEN
PJM_IPD
62.647

Details for [AH1-239] AH1-239 TP-AG1-471 TP 69.0 kV Ckt 1 line l/o EKPC_P2-3_CASEY S89-1008_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
AH1-239 TP-AG1-471 TP 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_CASEY S89-1008_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.91 %
Rating:54.0 MVA
Rating Type:B
MVA to Mitigate:62.05
MW Contribution:61.41
IPD Plant:AH1-239
Bus #Bus NameTypeMW Contribution
971485AH1-239 GEN
PJM_IPD
61.407

Details for [AH1-239] AH1-239 TP-AG1-471 TP 69.0 kV Ckt 1 line l/o EKPC_P2-2_CASEY CO 161_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
AH1-239 TP-AG1-471 TP 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_CASEY CO 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:114.91 %
Rating:54.0 MVA
Rating Type:B
MVA to Mitigate:62.05
MW Contribution:61.41
IPD Plant:AH1-239
Bus #Bus NameTypeMW Contribution
971485AH1-239 GEN
PJM_IPD
61.407

Details for [AH1-239] AH1-239 TP-AG1-471 TP 69.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-1


Base Case Flowgate

Area:EKPC
Facility Description:
AH1-239 TP-AG1-471 TP 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:113.56 %
Rating:54.0 MVA
Rating Type:B
MVA to Mitigate:61.32
MW Contribution:61.34
IPD Plant:AH1-239
Bus #Bus NameTypeMW Contribution
971485AH1-239 GEN
PJM_IPD
61.343

Details for [AH1-239] AH1-239 TP-AG1-471 TP 69.0 kV Ckt 1 line l/o EKPC_P7-1_COOP 161 DBL 2_SRT-A-2


Base Case Flowgate

Area:EKPC
Facility Description:
AH1-239 TP-AG1-471 TP 69.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:113.35 %
Rating:54.0 MVA
Rating Type:B
MVA to Mitigate:61.21
MW Contribution:61.27
IPD Plant:AH1-239
Bus #Bus NameTypeMW Contribution
971485AH1-239 GEN
PJM_IPD
61.271

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line l/o EKPC_P1-2_COOP-DEN161_SRT-A-1


Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_COOP-DEN161_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:217.77 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:648.95
MW Contribution:2.49
Bus #Bus NameTypeMW Contribution
965411AG1-406 GEN
50/50
Charging
1.399
970273AG2-179 GEN
50/50
Charging
1.105
972273AH1-721 GEN
50/50
625.762
966021AG1-471 GEN
Solar/Wind Harmer
1.955
971485AH1-239 GEN
Solar/Wind Harmer
2.489
339231AF1-038_GEN
Solar/Wind Helper
0.87
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.006
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.532
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.186
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.627
GibsonPJM->LTFIMP_GIBSON
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.004
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.01
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
2.575

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line l/o EKPC_P1-2_LAUR-L DAM161_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P1-2_LAUR-L DAM161_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:139.0 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:414.21
MW Contribution:2.34
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
372.969
966021AG1-471 GEN
Solar/Wind Harmer
1.751
971485AH1-239 GEN
Solar/Wind Harmer
2.336
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.265
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.052
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.159
LAGNLTFEXP_LAGN->PJM
CLTF
0.141
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.111
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.103
CPLELTFEXP_CPLE->PJM
CLTF
0.022
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.39
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.02
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.633

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line l/o EKPC_P2-2_LAUR-LAURD161_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_LAUR-LAURD161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:139.0 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:414.21
MW Contribution:2.34
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
372.969
966021AG1-471 GEN
Solar/Wind Harmer
1.751
971485AH1-239 GEN
Solar/Wind Harmer
2.336
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.265
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.052
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.159
LAGNLTFEXP_LAGN->PJM
CLTF
0.141
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.111
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.103
CPLELTFEXP_CPLE->PJM
CLTF
0.022
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.39
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.02
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.633

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line l/o EKPC_P2-3_LAURL S50-1014_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_LAURL S50-1014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:138.99 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:414.2
MW Contribution:2.34
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
372.98
966021AG1-471 GEN
Solar/Wind Harmer
1.751
971485AH1-239 GEN
Solar/Wind Harmer
2.337
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.265
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.052
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.159
LAGNLTFEXP_LAGN->PJM
CLTF
0.142
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.111
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.104
CPLELTFEXP_CPLE->PJM
CLTF
0.022
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.391
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.02
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.635

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line l/o EKPC_P4-5_LAURL S50-1014_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P4-5_LAURL S50-1014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:138.98 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:414.16
MW Contribution:2.34
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
372.98
966021AG1-471 GEN
Solar/Wind Harmer
1.751
971485AH1-239 GEN
Solar/Wind Harmer
2.337
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.265
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.052
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.159
LAGNLTFEXP_LAGN->PJM
CLTF
0.142
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.111
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.104
CPLELTFEXP_CPLE->PJM
CLTF
0.022
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.391
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.02
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.635

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line l/o EKPC_P2-2_LAUREL CO 161_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_LAUREL CO 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:138.98 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:414.16
MW Contribution:2.34
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
372.98
966021AG1-471 GEN
Solar/Wind Harmer
1.751
971485AH1-239 GEN
Solar/Wind Harmer
2.337
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.265
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.052
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.159
LAGNLTFEXP_LAGN->PJM
CLTF
0.142
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.111
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.104
CPLELTFEXP_CPLE->PJM
CLTF
0.022
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.391
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.02
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.635

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line l/o EKPC_P7-1_LAURL 161 DBL_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P7-1_LAURL 161 DBL_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:138.95 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:414.06
MW Contribution:2.34
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
372.989
966021AG1-471 GEN
Solar/Wind Harmer
1.752
971485AH1-239 GEN
Solar/Wind Harmer
2.337
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.266
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.052
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.159
LAGNLTFEXP_LAGN->PJM
CLTF
0.142
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.111
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.104
CPLELTFEXP_CPLE->PJM
CLTF
0.022
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.392
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.02
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.636

Details for AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line l/o EKPC_P1-2_COOP-LAUREL161_SRT-A-1


Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5COOPER2 161.0 kV Ckt 2 line
Contingency Name:
EKPC_P1-2_COOP-LAUREL161_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:308.72 %
Rating:210.0 MVA
Rating Type:B
MVA to Mitigate:648.32
MW Contribution:2.49
Bus #Bus NameTypeMW Contribution
965411AG1-406 GEN
50/50
Charging
1.398
970273AG2-179 GEN
50/50
Charging
1.104
972273AH1-721 GEN
50/50
625.222
966021AG1-471 GEN
Solar/Wind Harmer
1.953
971485AH1-239 GEN
Solar/Wind Harmer
2.487
339231AF1-038_GEN
Solar/Wind Helper
0.87
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.006
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.531
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.186
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.627
GibsonPJM->LTFIMP_GIBSON
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.004
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.01
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
2.573

Details for AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-1039_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-1039_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:165.91 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:494.41
MW Contribution:3.87
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
477.882
966021AG1-471 GEN
Solar/Wind Harmer
2.849
971485AH1-239 GEN
Solar/Wind Harmer
3.868
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.05
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.169
MECLTFEXP_MEC->PJM
CLTF
0.22
SIGELTFEXP_SIGE->PJM
CLTF
0.006
LAGNLTFEXP_LAGN->PJM
CLTF
0.592
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.483
TVALTFEXP_TVA->PJM
CLTF
0.37
G-007ALTFEXP_G-007A->PJM
CMTX
0.018
CPLELTFEXP_CPLE->PJM
CLTF
0.13
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.021
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.914
LGEELTFEXP_LGEE->PJM
CLTF
0.025
WECLTFEXP_WEC->PJM
CLTF
0.029
VFTLTFEXP_VFT->PJM
CMTX
0.046
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
2.428

Details for AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line l/o EKPC_P2-3_COOP S42-210G_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-3_COOP S42-210G_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:165.91 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:494.41
MW Contribution:3.85
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
476.07
966021AG1-471 GEN
Solar/Wind Harmer
2.828
971485AH1-239 GEN
Solar/Wind Harmer
3.845
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.093
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.182
MECLTFEXP_MEC->PJM
CLTF
0.226
SIGELTFEXP_SIGE->PJM
CLTF
0.007
LAGNLTFEXP_LAGN->PJM
CLTF
0.596
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.473
TVALTFEXP_TVA->PJM
CLTF
0.371
G-007ALTFEXP_G-007A->PJM
CMTX
0.013
CPLELTFEXP_CPLE->PJM
CLTF
0.127
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.012
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.974
LGEELTFEXP_LGEE->PJM
CLTF
0.032
WECLTFEXP_WEC->PJM
CLTF
0.03
VFTLTFEXP_VFT->PJM
CMTX
0.034
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
2.293

Details for AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line l/o EKPC_P2-2_COOPER 2 161_SRT-A


Base Case Flowgate

Area:EKPC
Facility Description:
AH1-721 TP-5LAUREL DAM 161.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_COOPER 2 161_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:165.91 %
Rating:298.0 MVA
Rating Type:B
MVA to Mitigate:494.4
MW Contribution:3.85
Bus #Bus NameTypeMW Contribution
972273AH1-721 GEN
50/50
476.07
966021AG1-471 GEN
Solar/Wind Harmer
2.828
971485AH1-239 GEN
Solar/Wind Harmer
3.845
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.093
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.182
MECLTFEXP_MEC->PJM
CLTF
0.226
SIGELTFEXP_SIGE->PJM
CLTF
0.007
LAGNLTFEXP_LAGN->PJM
CLTF
0.596
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.473
TVALTFEXP_TVA->PJM
CLTF
0.371
G-007ALTFEXP_G-007A->PJM
CMTX
0.013
CPLELTFEXP_CPLE->PJM
CLTF
0.127
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.012
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.974
LGEELTFEXP_LGEE->PJM
CLTF
0.032
WECLTFEXP_WEC->PJM
CLTF
0.03
VFTLTFEXP_VFT->PJM
CMTX
0.034
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
2.293
CONTINGENCY 'EKPC_P1-2_AG1-471 TP-AH1-239 TP-69_SRT-A'
 DISCONNECT BRANCH FROM BUS 966020 TO BUS 971484 CKT 1   /*AG1-471 TP    69.0 - AH1-239 TP    69.0
END
CONTINGENCY 'EKPC_P1-2_AG1-471 TP-2ZULA J NO-69_SRT-A'
 DISCONNECT BRANCH FROM BUS 966020 TO BUS 342532 CKT 1   /*AG1-471 TP    69.0 - 2ZULA J NO    69.0
END
CONTINGENCY 'EKPC_P2-3_COOP S42-210G_SRT-A'
 OPEN BUS 342718   /*5COOPER2     161.0
 OPEN BUS 342903   /*1COOPER2 G    20.0
END
CONTINGENCY 'EKPC_P2-2_COOPER 2 161_SRT-A'
 OPEN BUS 342718   /*5COOPER2     161.0
END
CONTINGENCY 'EKPC_P2-3_COOP S42-1039_SRT-A'
 OPEN BUS 342715   /*5COOPER1     161.0
 OPEN BUS 342718   /*5COOPER2     161.0
 OPEN BUS 342900   /*1COOPER1 G    13.8
 OPEN BUS 342903   /*1COOPER2 G    20.0
END
CONTINGENCY 'EKPC_P7-1_COOP 161 DBL 2_SRT-A-2'
 OPEN BRANCH FROM BUS 324141 TO BUS 342718 CKT 1   /*5ELIHU       161.0 - 5COOPER2     161.0
 OPEN BRANCH FROM BUS 972272 TO BUS 342757 CKT 1   /*AH1-721 TP   161.0 - 5LAUREL DAM  161.0
END
CONTINGENCY 'EKPC_P2-2_ELIHU-COOP 161_SRT-A'
 OPEN BRANCH FROM BUS 324141 TO BUS 342718 CKT 1   /*5ELIHU       161.0 - 5COOPER2     161.0
END
CONTINGENCY 'EKPC_P7-1_COOP 161 DBL 2_SRT-A-1'
 OPEN BRANCH FROM BUS 324141 TO BUS 342718 CKT 1   /*5ELIHU       161.0 - 5COOPER2     161.0
 OPEN BRANCH FROM BUS 342718 TO BUS 972272 CKT 1   /*5COOPER2     161.0 - AH1-721 TP   161.0
END
CONTINGENCY 'EKPC_P1-2_COOP-ELIHU161_SRT-A'
 OPEN BRANCH FROM BUS 324141 TO BUS 342718 CKT 1   /*5ELIHU       161.0 - 5COOPER2     161.0
END
CONTINGENCY 'EKPC_P1-2_AH1-239 TP-2UPCHURCH T-69_SRT-A'
 DISCONNECT BRANCH FROM BUS 971484 TO BUS 342397 CKT 1   /*AH1-239 TP    69.0 - 2UPCHURCH T   69.0
END
CONTINGENCY 'EXT_324106 7HARDIN CO 345 325140 7GLENDALE S 345 1_SRT-L'
 OPEN BRANCH FROM BUS 324106 TO BUS 325140 CKT 1   /*7HARDIN CO   345.0 - 7GLENDALE S  345.0
END
CONTINGENCY 'EKPC_P2-2_LAUR-LAURD161_SRT-A'
 OPEN BRANCH FROM BUS 342754 TO BUS 342757 CKT 1   /*5LAUREL CO   161.0 - 5LAUREL DAM  161.0
END
CONTINGENCY 'EKPC_P2-3_LAURL S50-1014_SRT-A'
 OPEN BRANCH FROM BUS 341740 TO BUS 342754 CKT 1   /*2LAUREL CO    69.0 - 5LAUREL CO   161.0
 OPEN BRANCH FROM BUS 342754 TO BUS 342757 CKT 1   /*5LAUREL CO   161.0 - 5LAUREL DAM  161.0
END
CONTINGENCY 'EKPC_P4-5_LAURL S50-1014_SRT-A'
 OPEN BUS 342754   /*5LAUREL CO   161.0
END
CONTINGENCY 'EKPC_P2-2_LAUREL CO 161_SRT-A'
 OPEN BUS 342754   /*5LAUREL CO   161.0
END
CONTINGENCY 'EKPC_P4-5_LAURL S50-1024_SRT-A'
 OPEN BRANCH FROM BUS 324688 TO BUS 342781 CKT 1   /*2PITTSBRG KU  69.0 - 5PITTSBURG   161.0
 OPEN BRANCH FROM BUS 342781 TO BUS 342820 CKT 1   /*5PITTSBURG   161.0 - 5TYNER       161.0
 OPEN BUS 342754                                   /*5LAUREL CO   161.0
END
CONTINGENCY 'EKPC_P2-3_LAURL S50-1024_SRT-A'
 OPEN BRANCH FROM BUS 324688 TO BUS 342781 CKT 1   /*2PITTSBRG KU  69.0 - 5PITTSBURG   161.0
 OPEN BRANCH FROM BUS 341740 TO BUS 342754 CKT 1   /*2LAUREL CO    69.0 - 5LAUREL CO   161.0
 OPEN BRANCH FROM BUS 342754 TO BUS 342781 CKT 1   /*5LAUREL CO   161.0 - 5PITTSBURG   161.0
 OPEN BRANCH FROM BUS 342781 TO BUS 342820 CKT 1   /*5PITTSBURG   161.0 - 5TYNER       161.0
END
CONTINGENCY 'EKPC_P7-1_LAURL 161 DBL_SRT-A'
 OPEN BRANCH FROM BUS 342754 TO BUS 342757 CKT 1   /*5LAUREL CO   161.0 - 5LAUREL DAM  161.0
 OPEN BRANCH FROM BUS 342754 TO BUS 342781 CKT 1   /*5LAUREL CO   161.0 - 5PITTSBURG   161.0
 OPEN BRANCH FROM BUS 342781 TO BUS 342820 CKT 1   /*5PITTSBURG   161.0 - 5TYNER       161.0
END
CONTINGENCY 'EKPC_P1-2_COOP 161 TIE_SRT-A'
 OPEN BRANCH FROM BUS 342715 TO BUS 342718 CKT 1   /*5COOPER1     161.0 - 5COOPER2     161.0
END
CONTINGENCY 'EKPC_P1-2_LAUR-L DAM161_SRT-A'
 OPEN BRANCH FROM BUS 342754 TO BUS 342757 CKT 1   /*5LAUREL CO   161.0 - 5LAUREL DAM  161.0
END
CONTINGENCY 'EKPC_P2-3_COOP S42-1014_SRT-A'
 OPEN BRANCH FROM BUS 342742 TO BUS 342745 CKT 1   /*5JABEZ       161.0 - 5JABEZ T     161.0
 OPEN BRANCH FROM BUS 342745 TO BUS 342751 CKT 1   /*5JABEZ T     161.0 - 5JAMESTOWN T 161.0
 OPEN BRANCH FROM BUS 342745 TO BUS 342799 CKT 1   /*5JABEZ T     161.0 - 5S OAKHILL   161.0
 OPEN BRANCH FROM BUS 342748 TO BUS 342751 CKT 1   /*5JAMESTOWN   161.0 - 5JAMESTOWN T 161.0
 OPEN BRANCH FROM BUS 342751 TO BUS 342796 CKT 1   /*5JAMESTOWN T 161.0 - 5RUSSEL CO J 161.0
 OPEN BRANCH FROM BUS 342793 TO BUS 342796 CKT 1   /*5RUSSEL CO   161.0 - 5RUSSEL CO J 161.0
 OPEN BRANCH FROM BUS 342796 TO BUS 360448 CKT 1   /*5RUSSEL CO J 161.0 - 5WOLF CRK HP 161.0
 OPEN BUS 342715                                   /*5COOPER1     161.0
 OPEN BUS 342900                                   /*1COOPER1 G    13.8
END
CONTINGENCY 'EKPC_P2-2_COOPER 1 161_SRT-A'
 OPEN BUS 342715   /*5COOPER1     161.0
END
CONTINGENCY 'EKPC_P2-2_COOP-LAURD 161_SRT-A'
 OPEN BRANCH FROM BUS 972272 TO BUS 342757 CKT 1   /*AH1-721 TP   161.0 - 5LAUREL DAM  161.0
END
CONTINGENCY 'EKPC_P7-1_COOP 161 DBL 1_SRT-A'
 OPEN BRANCH FROM BUS 342115 TO BUS 342787 CKT 1   /*2PULASK CO    69.0 - 5PULASK CO   161.0
 OPEN BRANCH FROM BUS 342715 TO BUS 342790 CKT 1   /*5COOPER1     161.0 - 5PULASK CO J 161.0
 OPEN BRANCH FROM BUS 342715 TO BUS 342799 CKT 1   /*5COOPER1     161.0 - 5S OAKHILL   161.0
 OPEN BRANCH FROM BUS 342742 TO BUS 342745 CKT 1   /*5JABEZ       161.0 - 5JABEZ T     161.0
 OPEN BRANCH FROM BUS 342745 TO BUS 342751 CKT 1   /*5JABEZ T     161.0 - 5JAMESTOWN T 161.0
 OPEN BRANCH FROM BUS 342745 TO BUS 342799 CKT 1   /*5JABEZ T     161.0 - 5S OAKHILL   161.0
 OPEN BRANCH FROM BUS 342748 TO BUS 342751 CKT 1   /*5JAMESTOWN   161.0 - 5JAMESTOWN T 161.0
 OPEN BRANCH FROM BUS 342751 TO BUS 342796 CKT 1   /*5JAMESTOWN T 161.0 - 5RUSSEL CO J 161.0
 OPEN BRANCH FROM BUS 342760 TO BUS 342790 CKT 1   /*5LIBERTY J   161.0 - 5PULASK CO J 161.0
 OPEN BRANCH FROM BUS 342787 TO BUS 342790 CKT 1   /*5PULASK CO   161.0 - 5PULASK CO J 161.0
 OPEN BRANCH FROM BUS 342793 TO BUS 342796 CKT 1   /*5RUSSEL CO   161.0 - 5RUSSEL CO J 161.0
 OPEN BRANCH FROM BUS 342796 TO BUS 360448 CKT 1   /*5RUSSEL CO J 161.0 - 5WOLF CRK HP 161.0
END
CONTINGENCY 'EKPC_P2-2_PULASKI 161_SRT-A'
 OPEN BUS 342787   /*5PULASK CO   161.0
 OPEN BUS 342790   /*5PULASK CO J 161.0
END
CONTINGENCY 'EXT_324130 5ALCALDE 161 324141 5ELIHU 161 1_SRT-L'
 OPEN BRANCH FROM BUS 324130 TO BUS 324141 CKT 1   /*5ALCALDE     161.0 - 5ELIHU       161.0
END
CONTINGENCY 'EKPC_P2-3_MAR W38-1014_SRT-A'
 OPEN BRANCH FROM BUS 341269 TO BUS 342703 CKT 1   /*2CASEY CO     69.0 - 5CASEY CO    161.0
 OPEN BRANCH FROM BUS 342703 TO BUS 342760 CKT 1   /*5CASEY CO    161.0 - 5LIBERTY J   161.0
 OPEN BRANCH FROM BUS 342703 TO BUS 342769 CKT 1   /*5CASEY CO    161.0 - 5MARION CO   161.0
 OPEN BRANCH FROM BUS 342770 TO BUS 342769 CKT 1   /*4MARION CO   138.0 - 5MARION CO   161.0
END
CONTINGENCY 'EKPC_P2-2_SUMMSHADE 161 #1_SRT-A'
 OPEN BRANCH FROM BUS 342322 TO BUS 342814 CKT 1   /*2SUMM SHADE   69.0 - 5SUMM SHADE  161.0
 OPEN BRANCH FROM BUS 342814 TO BUS 360334 CKT 1   /*5SUMM SHADE  161.0 - 5SUMMER SHAD 161.0
END
CONTINGENCY 'EKPC_P2-3_CASEY S89-1008_SRT-A'
 OPEN BRANCH FROM BUS 341269 TO BUS 342703 CKT 1   /*2CASEY CO     69.0 - 5CASEY CO    161.0
 OPEN BRANCH FROM BUS 342703 TO BUS 342760 CKT 1   /*5CASEY CO    161.0 - 5LIBERTY J   161.0
 OPEN BRANCH FROM BUS 342703 TO BUS 342769 CKT 1   /*5CASEY CO    161.0 - 5MARION CO   161.0
END
CONTINGENCY 'EKPC_P2-2_CASEY CO 161_SRT-A'
 OPEN BUS 342703   /*5CASEY CO    161.0
END
CONTINGENCY 'EKPC_P2-2_SUMMSHADE 161 #2_SRT-A'
 OPEN BUS 342814   /*5SUMM SHADE  161.0
END
CONTINGENCY 'EKPC_P1-2_AH1-034 TP-2PATTON RD J-69_SRT-A'
 DISCONNECT BRANCH FROM BUS 971154 TO BUS 342049 CKT 1   /*AH1-034 TP    69.0 - 2PATTON RD J  69.0
END
CONTINGENCY 'EKPC_P4-2_MAR W38-1004_SRT-A'
 OPEN BRANCH FROM BUS 342769 TO BUS 342775 CKT 1   /*5MARION CO   161.0 - 5MARION IP T 161.0
 OPEN BRANCH FROM BUS 342772 TO BUS 342797 CKT 1   /*5MARION IP   161.0 - 5S MARION IT 161.0
 OPEN BRANCH FROM BUS 342775 TO BUS 342797 CKT 1   /*5MARION IP T 161.0 - 5S MARION IT 161.0
 OPEN BRANCH FROM BUS 342775 TO BUS 342805 CKT 1   /*5MARION IP T 161.0 - 5SALOMA  T   161.0
 OPEN BRANCH FROM BUS 342797 TO BUS 342798 CKT 1   /*5S MARION IT 161.0 - 5S MARION IP 161.0
 OPEN BRANCH FROM BUS 342802 TO BUS 342805 CKT 1   /*5SALOMA      161.0 - 5SALOMA  T   161.0
 OPEN BRANCH FROM BUS 342805 TO BUS 339237 CKT 1   /*5SALOMA  T   161.0 - AF1-083 TAP  161.0
END
CONTINGENCY 'EKPC_P7-1_BULL 161 DBL_SRT-A'
 OPEN BUS 326975   /*5CEDAR GRV   161.0
 OPEN BUS 361788   /*5SUM SHAD TP 161.0
END
CONTINGENCY 'EKPC_P7-1_SSHAD 161 DBL_SRT-A'
 OPEN BRANCH FROM BUS 324150 TO BUS 324154 CKT 1   /*5LEBANON JCT 161.0 - 5PADDYS RUN  161.0
 OPEN BRANCH FROM BUS 324150 TO BUS 360334 CKT 1   /*5LEBANON JCT 161.0 - 5SUMMER SHAD 161.0
END
CONTINGENCY 'EKPC_P1-2_COOP-DEN161_SRT-A-1'
 OPEN BRANCH FROM BUS 342718 TO BUS 972272 CKT 2   /*5COOPER2     161.0 - AH1-721 TP   161.0
END
CONTINGENCY 'EKPC_P1-2_COOP-LAUREL161_SRT-A-1'
 OPEN BRANCH FROM BUS 342718 TO BUS 972272 CKT 1   /*5COOPER2     161.0 - AH1-721 TP   161.0
END
341005 to 342283 ckt 1
341206 to 341347 ckt 1
341347 to 341344 ckt 1
341344 to 342286 ckt 1
341344 to 342286 ckt 2
341392 to 341206 ckt 1
342287 to 324531 ckt 1
342286 to 342287 ckt 1
342397 to 341005 ckt 1
342532 to 342478 ckt 1
342718 to 342715 ckt 1
342718 to 324141 ckt 1
342754 to 342781 ckt 1
342757 to 342754 ckt 1
966020 to 342532 ckt 1
971484 to 342397 ckt 1
971484 to 966020 ckt 1
972272 to 342718 ckt 1
972272 to 342718 ckt 2
972272 to 342757 ckt 1

Short Circuit Analysis

Short Circuit analysis is not performed as part of the Phase I System Impact Study. Short Circuit analysis will commence in the Phase II System Impact Study.

Stability Analysis

Stability analysis is not performed as part of the Phase I System Impact Study. Stability analysis will commence in the Phase II System Impact Study.

Reactive Power Analysis

Reactive Power analysis is not performed as part of the Phase I System Impact Study. Reactive Power analysis will commence in the Phase II System Impact Study.

Steady-State Voltage Analysis

Steady State Voltage Analysis is Not Required.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-018Powerton-Goodings GroveIn Service
AA1-038Lexington-Low Moor 230kVUnder Construction
AA1-095Halfway-Marlowe 34.5kVIn Service
AA2-184Atlantic-Red Bank 34kVIn Service
AB1-001Absecon 12 kVIn Service
AB1-006Meadow Lake 345kVIn Service
AB1-027Old Church 34.5 KVIn Service
AB1-096Carroll-Mt. Airy 34.5kVIn Service
AB1-124Carroll-Monocacy 34.5kVPartially in Service - Under Construction
AB1-125Carroll-Monocacy 34.5kVIn Service
AB1-127St. Thomas-Guilford 34.5kVIn Service
AB1-128St. Thomas-Mercersburg 34.5kVIn Service
AB1-138Navy 34.5kVIn Service
AB1-139Metuchen 26kVIn Service
AB1-141Church-Wye Mills 138 kV IIn Service
AB1-142Church-Wye Mills 138 kV IIIn Service
AB1-150Grassy Falls 138kVIn Service
AB1-176Price 25kV IIEngineering & Procurement
AB1-180Pine View 12kVIn Service
AB2-026Powhatan 34.5kVIn Service
AB2-029Remington 34.5kVIn Service
AB2-032Church-Wye Mills 138 kVIn Service
AB2-037Keeney-Steele 230kVUnder Construction
AB2-045Buckingham 34.5kVIn Service
AB2-049Gloucester Township 12kVIn Service
AB2-070Mt. Pulaski-BrokawIn Service
AB2-133Chestertown 69kVUnder Construction
AB2-135Church-Kent 69kVIn Service
AB2-136Cambridge-West Cambridge 69kVUnder Construction
AB2-153Church-Wye Mills 138 kVIn Service
AB2-158Louisa-South Anna 230kVIn Service
AB2-179Townsend 138kVIn Service
AC1-001Delano 138kVIn Service
AC1-010Gloucester 26kVUnder Construction
AC1-017Levittown 13 kVIn Service
AC1-030Cinnaminson 13kVIn Service
AC1-033Kewanee 138 kVIn Service
AC1-042Altavista-Mt. Airy 69kVIn Service
AC1-053Lanesville-BrokawPartially in Service - Under Construction
AC1-068Atlanta 69kV IIn Service
AC1-069Atlanta 69kV IIIn Service
AC1-074Jacksonville-Renaker 138kV IIn Service
AC1-075Perth-Hickory Grove 115kVIn Service
AC1-076Locust Grove-Paytes 115kVIn Service
AC1-078Beatty-London 138kVIn Service
AC1-082Ravenswood-Hemlock 69kVUnder Construction
AC1-085Stuart-Clinton 345kVIn Service
AC1-089Hillsboro-Wildcat 138kVIn Service
AC1-091Cedar Creek 138kV IEngineering & Procurement
AC1-092Cedar Creek 138kV IIEngineering & Procurement
AC1-093Cedar Creek 138kV IIIEngineering & Procurement
AC1-094Cedar Creek 138kV IVEngineering & Procurement
AC1-101Johns Creek-Excel 138kV ISuspended
AC1-102Johns Creek-Excel 138kV IISuspended
AC1-111Aurora 138kVIn Service
AC1-118Westmoreland 34.5kVIn Service
AC1-120Mitchell-Mountain Run 115kVEngineering & Procurement
AC1-121Mitchell-Mountain Run 115kVEngineering & Procurement
AC1-122Smith Mountain-Candler's Mountain 138kVIn Service
AC1-145Gretna DP 69 kVIn Service
AC1-158Spotsylvania 500kVIn Service
AC1-165Atlanta 69kV IIIIn Service
AC1-166Atlanta 69kV IVIn Service
AC1-168Kewanee-StreatorSuspended
AC1-174Losantville 345kVIn Service
AC1-175Losantville 345kVIn Service
AC1-188Rio-Lick 138kVEngineering & Procurement
AC1-191Elmont 115kVEngineering & Procurement
AC1-194Elk 138kVActive
AC1-214Crescent RidgeIn Service
AC2-023Hebron 69kVEngineering & Procurement
AC2-029Circleville 138kVSuspended
AC2-059Biers Run-Circleville 138kVIn Service
AC2-060Buckskin 69kVIn Service
AC2-061Hillsboro-Clinton 138kVIn Service
AC2-067Camden-Crystal I 69kVEngineering & Procurement
AC2-068Camden-Crystal II 69kVEngineering & Procurement
AC2-075Jacksonville-Renaker 138 kVIn Service
AC2-088S. Bethel-Brown 69kVIn Service
AC2-090Losantville 345kVIn Service
AC2-111College Corner 138kVEngineering & Procurement
AC2-123Jacksons Ferry 138kVIn Service
AC2-136East Hagerstown 12kVUnder Construction
AC2-137Elko 34.5kVIn Service
AC2-138Northern Neck 34.5kVIn Service
AC2-157Sullivan 345 kVUnder Construction
AC2-165Bremo-Powhatan 230kVSuspended
AC2-168Clinton 23kVIn Service
AC2-176Jay 138 kVIn Service
AC2-186Harrington 25kVUnder Construction
AC2-187Harrington 69kVUnder Construction
AC2-188Harrington 69 kVUnder Construction
AD1-013Twombly Road 138kVEngineering & Procurement
AD1-017Smith Mountain-Bearskin 138 kVIn Service
AD1-020Hunterstown-Lincoln 115 kVIn Service
AD1-060Mercersburg-Milnor 34.5 kVIn Service
AD1-061McConnelsburg-Mercersburg 34 kVIn Service
AD1-063Harmony Village 34.5 kVIn Service
AD1-100Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVUnder Construction
AD1-105Kings Dominion DP 115 kVUnder Construction
AD1-115Mountain Run-Mitchell 115 kVEngineering & Procurement
AD1-128Modoc-Delaware 138 kVPartially in Service - Under Construction
AD1-136South Bethel-Brown 69 kVIn Service
AD1-140Greene-Clark 138 kVEngineering & Procurement
AD1-155Meadow Brook-Strasburg 138 kVIn Service
AD2-009McConnellsburg 138 kVIn Service
AD2-016Biers Run-Circleville 138 kVIn Service
AD2-027Camden Switch 26 kVIn Service
AD2-031Martinsville-Wilmington 69 kVIn Service
AD2-038Powerton-Nevada 345 kVUnder Construction
AD2-042Camden Switch 26 kV IIIn Service
AD2-047Davis Creek 138 kVSuspended
AD2-048Cynthia-Headquarters 69 kVUnder Construction
AD2-060Davis Creek 138kVEngineering & Procurement
AD2-065Atco 12 kVIn Service
AD2-066Mazon-Crescent Ridge 138 kVEngineering & Procurement
AD2-070Gilbert-Morris Park 34.5kVIn Service
AD2-071Strawton-Deer Creek 138 kVSuspended
AD2-073Sanders DP 230 kVIn Service
AD2-074Garner DP-Lancaster 115 kVEngineering & Procurement
AD2-100Kincaid-Pana 345 kVSuspended
AD2-115Lyons-Moselem 69kVIn Service
AD2-116Hokes-Grantley 69 kVIn Service
AD2-131Kincaid-Pana 345kVSuspended
AD2-133Eagle Valley 115kVIn Service
AD2-134Shady OaksPartially in Service - Under Construction
AD2-135Williamstown 12kVPartially in Service - Under Construction
AD2-163Broadview-Tangy 138 kVIn Service
AD2-172Lena 138kVIn Service
AD2-179Morgans Cut-Glen Lyn 138kVSuspended
AD2-180Elk Garden-Parr Run 138kVIn Service
AE1-040Greenfield 69 kVIn Service
AE1-041Edison 4kVIn Service
AE1-071Shade Gap-Roxbury 115 kVIn Service
AE1-074Winterpock 34.5 kVUnder Construction
AE1-075Powhatan 34.5 kVIn Service
AE1-079Maysville-Sharon 69 kVUnder Construction
AE1-081Landing 12.47 kVIn Service
AE1-100Axton 138 kVIn Service
AE1-101McConnellsburg-Texas Eastern 138 kVIn Service
AE1-109Frenchs Mill 34 kVIn Service
AE1-113Mole Creek 345 kVEngineering & Procurement
AE1-114Maryland-Lancaster 138 kVActive
AE1-142Manitou-Pleasant Plains 34.5 kVIn Service
AE1-155Garner-Northern Neck 115 kVIn Service
AE1-156Quakertown Solar II 34.5 kVPartially in Service - Under Construction
AE1-163Powerton-Nevada 345 kVEngineering & Procurement
AE1-166Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE1-172Loretto-Wilton CenterActive
AE1-176Roanoke-Vinton 12 kV (Niagara Hydro)In Service
AE1-183Maysville-McDowell 69 kVEngineering & Procurement
AE1-185Hokes-Jackson 69 kVIn Service
AE1-196Hokes-Jackson 69 kV IIIn Service
AE1-205McLean 345 kVEngineering & Procurement
AE1-207Mississinewa-Gaston 138 kVSuspended
AE1-208Delaware-Van Buren 138 kVSuspended
AE1-209Desoto 345 kVSuspended
AE1-210Desoto 345 kVSuspended
AE1-212Grandview-Clifftop 138 kVSuspended
AE1-229Deepwater-Upper Pittsgrove 138 kVSuspended
AE1-237Andover (Maysville) 69kV IUnder Construction
AE1-250Smith Mountain-E. Danville 138 kVEngineering & Procurement
AE2-029Grottoes-Merck 115kVUnder Construction
AE2-035Lena 138 kVIn Service
AE2-042Milton 69 kVIn Service
AE2-045Olive-Reynolds 345 kVEngineering & Procurement
AE2-047Ridgeway-Solite 69 kVEngineering & Procurement
AE2-054Warfordsburg 34 kVIn Service
AE2-059Derry Tap-Derry Bus 69 kVIn Service
AE2-060Mifflintown Bus-Mifflintown Tap 69 kVIn Service
AE2-071Patton Rd-Summer Shade 69 kVIn Service
AE2-089Pennville-Adams 138 kVEngineering & Procurement
AE2-092Kidds Store-Sherwood 115 kVEngineering & Procurement
AE2-113Farmers Valley-Ridgeway 115 kVUnder Construction
AE2-114Midland 23 kV IIn Service
AE2-115Midland 23 kV IIIn Service
AE2-117ABW Tap-Alexandria 46 kVSuspended
AE2-125Stahlstown-Ligonier 25 kVIn Service
AE2-126Dubois-Curwensville 34.5 kVIn Service
AE2-129Philipsburg-Clarence 34.5 kVIn Service
AE2-131Philipsburg-Karthaus 34.5Under Construction
AE2-133Penns Tap-Richfield Tie 69 kVIn Service
AE2-139East Towanda-Grover 230 kVEngineering & Procurement
AE2-140Axton-Danville 138 kVSuspended
AE2-148Beatty-Greene 345 kVIn Service
AE2-152Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE2-160Kanawha River 138 kVEngineering & Procurement
AE2-166Stockton 138 kVSuspended
AE2-169Delaware-Van Buren 138 kVSuspended
AE2-172Mississinewa-Gaston 138 kVSuspended
AE2-173McLean 345 kVActive
AE2-175Jackson-Long Pond 69 kVPartially in Service - Under Construction
AE2-185Gladys DP-Stonemill Switching Station 69 kVActive
AE2-187Shockoe DP-Chatham 69 kVActive
AE2-206East Sidney-Quincy 138 kVIn Service
AE2-214Cole 345 kVEngineering & Procurement
AE2-217East Springfield-London 138 kVEngineering & Procurement
AE2-219Bluff Point-Randolph 138 kVSuspended
AE2-220Losantville 345 kVEngineering & Procurement
AE2-221Clinton-Stuart 345 kVUnder Construction
AE2-223McLean 345 kVActive
AE2-224Bear Rock-Johnstown 230 kVIn Service
AE2-226Millville-Old Chapel 138 kVEngineering & Procurement
AE2-230Bartonsville-Meadow Brook 138 kVIn Service
AE2-234Liberty Center-Buckeye Tap 69 kVEngineering & Procurement
AE2-254Garrard County-Tommy-Gooch 69 kVIn Service
AE2-255Molecreek 345 kVEngineering & Procurement
AE2-261Kincaid-Pana 345 kVActive
AE2-262Moshannon-Milesburg 230 kVEngineering & Procurement
AE2-263Moshannon-Milesburg 230 kV IIEngineering & Procurement
AE2-267Woodsdale 345 kVEngineering & Procurement
AE2-281Powerton-Nevada 345 kVEngineering & Procurement
AE2-283Gladys-Stone Mill 69 kVActive
AE2-285Maysville 69 kVEngineering & Procurement
AE2-291Grit DP-Perth 115 kVActive
AE2-297Madison-Tanners Creek 138 kVIn Service
AE2-305Givens-Mechanicsburg 138 kVEngineering & Procurement
AE2-308Three Forks-Dale 138 kVActive
AE2-309Carlos Junction-Lonaconing 34.5 kVIn Service
AE2-315Yankee Tap 69 kVIn Service
AE2-318Ford-Cedarville 138 kVSuspended
AE2-321Belvidere-Marengo 138 kVActive
AE2-326Jacksons Ferry 138 kVEngineering & Procurement
AE2-339Avon 138 kVEngineering & Procurement
AE2-341Sandwich-Plano 138 kVActive
AE2-342Woodstock 69 kVEngineering & Procurement
AE2-343Andover (Maysville) 69 kV IIUnder Construction
AF1-006Fairview East 34.5 kVIn Service
AF1-007Indian River 230 kV ISuspended
AF1-021Bethelboro-Connellsville #1 25 kVIn Service
AF1-022Lake Lynn-Uniontown 25 kVIn Service
AF1-030Sandwich-Plano 138 kVActive
AF1-038Sewellton Jct-Webbs Crossroads 69 kVEngineering & Procurement
AF1-039Listonburg-Highpoint 24.9 kVIn Service
AF1-042Garner DP-Lancaster 115 kVEngineering & Procurement
AF1-045Cedarville-Ford 138 kVSuspended
AF1-049Berry Hill 138 kVUnder Construction
AF1-050Summer Shade - Green County 161 kVEngineering & Procurement
AF1-051Gavin 765 kVIn Service
AF1-053Givens-Mechanicsburg 138 kVEngineering & Procurement
AF1-054Givens-Mechanicsburg 138 kVEngineering & Procurement
AF1-071College Corner 138 kVEngineering & Procurement
AF1-078East Sidney-Quincy 138 kVIn Service
AF1-083Green County-Saloma 161 kVEngineering & Procurement
AF1-086Madera-Westover South 115 kVUnder Construction
AF1-088Sullivan 345 kVActive
AF1-090Kincaid-PanaEngineering & Procurement
AF1-092Huntington Jct. 138 kVSuspended
AF1-093Henderson-Stoneboro 69 kVEngineering & Procurement
AF1-094Union City-Cambridge Springs 34.5 kVEngineering & Procurement
AF1-098Four Mile Jct-Corry East 115 kVEngineering & Procurement
AF1-118Sorenson-Desoto 345 kVEngineering & Procurement
AF1-119Keystone-Desoto 345 kVEngineering & Procurement
AF1-130Inez 138 kVSuspended
AF1-134Philipsburg-Madera 34.5 kVEngineering & Procurement
AF1-136Warfordsburg-Purcell Junction 34.5 kVEngineering & Procurement
AF1-140Claysburg 23 kVEngineering & Procurement
AF1-143Lick Run 115 kVEngineering & Procurement
AF1-153Motion-Ridgeway 46 kVSuspended
AF1-162Inez 138 kVEngineering & Procurement
AF1-202Keystone-Desoto 345 kVUnder Construction
AF1-203Patton Rd-Summer Shade 69 kVIn Service
AF1-204Eugene 345 kVActive
AF1-207Reynolds-Olive #1 345 kVEngineering & Procurement
AF1-215Olive-Reynolds 345 kVIn Service
AF1-223Keystone-Desoto 345 kVUnder Construction
AF1-228Beatty-Greene 345 kVEngineering & Procurement
AF1-233Flemingsburg – Spurlock 138kVActive
AF1-249Nickel 12.47 kVIn Service
AF1-254Milnor-Huyetts 34.5 kVUnder Construction
AF1-262Upper Pittsgrove 12 kVIn Service
AF1-264Runnemede 13 kVIn Service
AF1-268Desoto-Jay 138 kVEngineering & Procurement
AF1-272Lucerne 115 kVEngineering & Procurement
AF1-275Cole 345 kVEngineering & Procurement
AF1-282Stuart-Clinton 345 kVEngineering & Procurement
AF1-283Stuart-Clinton 345 kVEngineering & Procurement
AF1-290Feagans Mill-Millville 138 kVIn Service
AF1-291ABartonsville-Meadow Brook 138 kVIn Service
AF1-296Garden Plain 138 kVActive
AF1-299Otter Point 34.5 kV IIn Service
AF1-300Otter Point 34.5 kV IIIn Service
AF1-302Brookville-Squab Hollow 138 kVEngineering & Procurement
AF1-320Merrill Creek 115 kVEngineering & Procurement
AF1-322Meadow Lake 345 kVEngineering & Procurement
AF1-331Twombley RoadEngineering & Procurement
AF1-333Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF1-337Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF1-338Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF1-339Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF2-008Sullivan 345 kVActive
AF2-018Inez 138 kVEngineering & Procurement
AF2-032Kincaid 345 kVEngineering & Procurement
AF2-039Shawville-Clearfield 34.5 kVEngineering & Procurement
AF2-041Nelson-Electric Junction 345 kVActive
AF2-048Rio-Lick 138 kVEngineering & Procurement
AF2-068Jay 138 kVActive
AF2-069Crescent Ridge 138 kVActive
AF2-075Bartonsville-Meadow Brook 138 kV IIIIn Service
AF2-078Reynolds-Olive #1 345 kVEngineering & Procurement
AF2-086Scott Tap-Bowmans Mill Tap 69 kVEngineering & Procurement
AF2-088Shawville-Clearfield 34.5 kV IIEngineering & Procurement
AF2-095Davis Creek 138 kVActive
AF2-106Hazel Hollow-Glen Lyn #1 138 kVEngineering & Procurement
AF2-107Clifford 138 kVEngineering & Procurement
AF2-111North Clark-Spurlock 345 kVActive
AF2-130Cobalt Corners 34.5 kVIn Service
AF2-132Reynolds-Olive #1 345 kVUnder Construction
AF2-133Reynolds-Olive #2 345 kVUnder Construction
AF2-134Olive-Reynolds #2 345 kVIn Service
AF2-138Flanders-West Wharton 34.5 kVIn Service
AF2-139Gilbert-Warren Glen 34.5 kVIn Service
AF2-142Nevada 345 kVActive
AF2-143Powerton-Nevada 345 kVActive
AF2-144Powhatan 34.5 kVIn Service
AF2-162Keystone-Desoto 345 kVEngineering & Procurement
AF2-173Desoto 345 kVActive
AF2-177Sorenson-DeSoto #2 345 kVActive
AF2-192Frenchtown Solar-West Flemington 34.5 kVSuspended
AF2-199Nelson-Electric Junction 345 kVActive
AF2-200Nelson-Electric Junction 345 kVActive
AF2-205Olive-Reynolds #2 345 kVEngineering & Procurement
AF2-225McLean 345 kVActive
AF2-229Roxbury 23 kVEngineering & Procurement
AF2-233Penns-Richfield Tie #1 69 kVEngineering & Procurement
AF2-234Sunbury Yard #1-Richfield Tie #2 69 kVEngineering & Procurement
AF2-235Titusville-Oil Creek 34.5 kVWithdrawn
AF2-238Mansfield-South Troy 34.5 kVEngineering & Procurement
AF2-247Bustleton 13.2 kVIn Service
AF2-250Edgewood 12 kV IIIIn Service
AF2-252Blue Mound 345 kVEngineering & Procurement
AF2-291Sporn South-Leon 138 kVEngineering & Procurement
AF2-298Crown-New Lebanon 69 kVEngineering & Procurement
AF2-307Hope-Belvins Valley Tap 69 kVActive
AF2-311Gilboa-Jones Branch 138 kVEngineering & Procurement
AF2-316Gilboa-Jones Branch 138 kV IIEngineering & Procurement
AF2-325Jacktown 12 kVEngineering & Procurement
AF2-335Delaware-Royerton 138 kVActive
AF2-350Kensington 138 kVActive
AF2-352Blue Mound 345 kVEngineering & Procurement
AF2-354Washington 34.5 kV IIEngineering & Procurement
AF2-356Albright-Mt. Zion 138 kVUnder Construction
AF2-361Mifflintown Tap 69 kVEngineering & Procurement
AF2-365Munfordville KU Tap-Horse Cave Jct. 69 kVActive
AF2-371Harrison-Good Hope 138 kVEngineering & Procurement
AF2-378Cambridge 12 kVEngineering & Procurement
AF2-379Princess Anne 25 kVUnder Construction
AF2-382Hurley 69 kVEngineering & Procurement
AF2-383Tolna 115 kVWithdrawn
AF2-388Keystone-Desoto 345 kVActive
AF2-392Nelson-Dixon 138 kVActive
AF2-417West Damascus Tap-West Damascus 69 kVEngineering & Procurement
AF2-421East Hazelton-Weatherly Tap 69Engineering & Procurement
AF2-424Reed-Reed Tap #1 69 kVEngineering & Procurement
AF2-425Reed-Reed Tap#1 69 kVEngineering & Procurement
AF2-433Columbia-Geisinger Tap #1 69 kVEngineering & Procurement
AF2-434Columbia-Geisinger Tap #1 69 kVEngineering & Procurement
AF2-440Hillsboro-Middleboro 138 kVEngineering & Procurement
AG1-017Jay 138 kVUnder Construction
AG1-040Morgan Street-Mount Hope 34.5 kVEngineering & Procurement
AG1-047Jay 138 kVEngineering & Procurement
AG1-054Potter-Harlan 69 kVEngineering & Procurement
AG1-066Bonnyman 69 kVEngineering & Procurement
AG1-070Bon Ayr 69 kVActive
AG1-071Bon Ayr 69 kVActive
AG1-100Venango-Saegertown 34.5 kVEngineering & Procurement
AG1-107Hillsboro-Middleboro 138 kVEngineering & Procurement
AG1-118Sugar Grove-Waterman 138kVActive
AG1-124Gladstone 138 kVActive
AG1-125Marysville-Flatlick 765 kVEngineering & Procurement
AG1-126Marysville-Flatlick 765 kVEngineering & Procurement
AG1-127Crego Rd 138 kVActive
AG1-156Jack Frost-Lake Harmony 69 kVEngineering & Procurement
AG1-164East Hazelton-Weatherly Tap 69 kVEngineering & Procurement
AG1-165East Hazelton-Weatherly Tap 69 kVEngineering & Procurement
AG1-188Manitou-Oyster Creek 34.5 kVEngineering & Procurement
AG1-189Oyster Creek-Bamber Lake 34.5Engineering & Procurement
AG1-191Chester-Pohatcong Mountain 34.5 kVPartially in Service - Under Construction
AG1-193Utica Junction 34.5 kVSuspended
AG1-197Morgan Street-Cochranton 34.5 kVSuspended
AG1-198Union City 34.5 kVUnder Construction
AG1-223Larrabee-Allaire 34.5 kVUnder Construction
AG1-226Dequine-Eugene 345 kVActive
AG1-232Magley 138 kVEngineering & Procurement
AG1-236Lanesville-Brokaw 345 kVActive
AG1-237Dequine-Eugene 345 kVEngineering & Procurement
AG1-254Salem-Woodstown 69 kVEngineering & Procurement
AG1-259Sunbury-Dalmatia 69 kVEngineering & Procurement
AG1-260Sunbury-Dalmatia 69 kVEngineering & Procurement
AG1-281Claysburg-HCR Tap 46 kVEngineering & Procurement
AG1-282Dunnsville 34.5 kVEngineering & Procurement
AG1-301Miller REC-Warrior Ridge 46 kVEngineering & Procurement
AG1-302Olive-Reynolds #1 345 kVUnder Construction
AG1-320Glendale-Stephensburg 69 kVActive
AG1-324Jay-Desoto 138 kVEngineering & Procurement
AG1-341Summer Shade 161 kVActive
AG1-348Pequest River-Washington 34.5 kVIn Service
AG1-349Olive-Reynolds #2 345 kVEngineering & Procurement
AG1-351Harrison-Good Hope 138 kVEngineering & Procurement
AG1-354Summershade-Green County 161 kVActive
AG1-363Black Oak-Hatfield 500 kVEngineering & Procurement
AG1-367DeSoto 345 kVActive
AG1-374Blue Mound 345 kVActive
AG1-375Sorenson-Desoto 345 kVActive
AG1-386Smith-Francis Junction 25 kVIn Service
AG1-397Walston 12 kVWithdrawn
AG1-405Walnut Grove-Asahi 69 kVActive
AG1-406Walnut Grove-Asahi 69 kVActive
AG1-414Mississinewa 138 kVEngineering & Procurement
AG1-433Keystone-DeSoto 345 kVActive
AG1-460Kincaid-Pana 345 kVActive
AG1-462Cordova 345 kVActive
AG1-469Gordonsville 34.5 kVEngineering & Procurement
AG1-471Up Church-Wayne County 69 kVActive
AG1-478Wilmington 34.5 kVEngineering & Procurement
AG1-480Shawnee 34.5 kVEngineering & Procurement
AG1-482Hamilton 115 kVWithdrawn
AG1-494Boxwood-Riverville 138 kVActive
AG1-495Gilbert-Rocktown 34.5 kVEngineering & Procurement
AG1-499Lambs 12.47 kVUnder Construction
AG1-508Point Lookout 69 kVEngineering & Procurement
AG1-526West Garrard 345 kVActive
AG1-555Dequine 345 kVEngineering & Procurement
AG1-558Buckner 34.5 kVEngineering & Procurement
AG1-559Caroline Pines 22 kVEngineering & Procurement
AG2-063North Hampton 69 kVActive
AG2-072Rockport 765 kVActive
AG2-073Crooksville 69 kVActive
AG2-081Mt. Sterling-Fogg Pike 69 kVActive
AG2-085Delaware-Royerton 138 kVActive
AG2-104Marysville-Flatlick 765 kVActive
AG2-106Marysville-Flatlick 765 kVActive
AG2-107Marysville-Flatlick 765 kVActive
AG2-111Perth 34.5 kV Substation (Circuit 408)Active
AG2-112Perth 34.5 kV Substation (Circuit 404)Active
AG2-114Dresden-Pontiac Midpoint 345 kVActive
AG2-125Camden-Crystal 69 kVActive
AG2-126Eugene 345 kVActive
AG2-152Banister-Bear Skin 138 kVActive
AG2-159Williamstown 69 kVActive
AG2-162Jefferson-Greentown 765 kVActive
AG2-163Dequine-Eugene 345 kVActive
AG2-164Jefferson-Greentown 765 kVActive
AG2-165Dumont-Greentown 765 kVActive
AG2-179Sewellton Junction 69 kVActive
AG2-184Harbert Metering 138 kVActive
AG2-191Mississinewa 138 kVActive
AG2-192Mississinewa 138 kVActive
AG2-212Dumont-Greentown 765 kVActive
AG2-216East Sidney-Quincy 138 kVActive
AG2-219Jefferson-Greentown 765 kVActive
AG2-245Olive - Reynolds #1 345 kVActive
AG2-298Sulphur Creek-Loretto 69 kVActive
AG2-310Matt Funk 138 kVActive
AG2-311Smith Mountain 138 kVActive
AG2-328Dumont - Greentown 765 kVActive
AG2-330Dumont - Greentown 765 kVActive
AG2-331Jefferson-Greentown 765 kVActive
AG2-360Broadford 138 kVActive
AG2-363Powerton 345 kVActive
AG2-364Powerton 345 kVActive
AG2-378North Hampton – Medway 69 kVActive
AG2-385North Hampton 69 kVActive
AG2-401Losantville 345 kVActive
AG2-424Magnolia - Summersville 69 kVActive
AG2-444Bixby - Biers Run 345 kVActive
AG2-449Jefferson-Greentown 765 kVActive
AG2-453Lasalle - Plano 345 kVActive
AG2-487Madison - Tanners Creek 138 kVActive
AG2-491Meadow Lake 345 kVActive
AG2-516Pecatonica 138kVActive
AG2-518Tech Drive 138 kVActive
AG2-519Royerton - Desoto 138 kVActive
AG2-524LaSalle Station - Mazon 138 kVActive
AG2-548Corwin - Elk 138 kVActive
AG2-550Bluff Point - Randolph 138 kVActive
AG2-551Bluff Point - Randolph 138 kVActive
AG2-568Stink Run – Sundial 138 kVActive
AG2-575Crego Rd. 138 kVActive
AG2-585Kensington 138kVActive
AG2-589Ravenswood - Hemlock 69 kVActive
AG2-637Randolph - Hodgin 138 kVActive
AG2-657Kanawha River - Carbondale 138 kVActive
AG2-660Nelson-Electric Junction 345 kVActive
AG2-665Corwin - Elk 138 kVActive
AG2-670Green County -Taylor County Junction 161 kVActive
AH1-004Avon - Renaker 138 kVActive
AH1-034Patton Road Junction - Summer Shade 69 kVActive
AH1-044Nelson - Electric Junction 345 kVActive
AH1-047Marengo - Belvidere 138 kVActive
AH1-055Kyger Creek - Don Marquis 345 kVActive
AH1-072Red Onion - VC5 69 kVActive
AH1-073Red Onion - VC5 69 kVActive
AH1-098Wolf Glade-West Carroll 138 kVActive
AH1-133Saltville - Tazewell 138 kVActive
AH1-136Falcon - Middle Creek 46 kVActive
AH1-144Peter's Mountain 138 kVActive
AH1-145Peter's Mountain 138 kVActive
AH1-146White Rock - Wayne 345 kVActive
AH1-147White Rock - Wayne 345 kVActive
AH1-150Nelson-Electric Junction 345 kVActive
AH1-151Nelson-Electric Junction 345 kVActive
AH1-164Oak Level - Tank Hill 138 kVActive
AH1-188Pigeon Creek 138 kVActive
AH1-196Prairie 345 kVActive
AH1-227Flemming - Fremont 69 kVActive
AH1-234Wempletown - Paddock 345 kVActive
AH1-269Claytor 138 kVActive
AH1-281Bluegrass Parkway Tap - Woodlawn 69 kVActive
AH1-285Sandwich 138 kVActive
AH1-292Sullivan 345 kVActive
AH1-302Olive - Reynolds 345 kVActive
AH1-304Delaware-Van Buren 138 kVActive
AH1-305Olive - Reynolds 345 kVActive
AH1-306Mississinewa-Gaston 138 kVActive
AH1-308Pennville - Adams 138 kVActive
AH1-337Randolph - Hodgin 138 kVActive
AH1-338McGirr Rd - Ritchie Road 138kVActive
AH1-341Stillman - Dixon 138KVActive
AH1-348Pound 34.5 kVActive
AH1-427Tommy Gooch - Garrard County 69 kVActive
AH1-482Olive - Reynolds #2 345 kVActive
AH1-535Nagel - Cane River 230 kVActive
AH1-537Pierce - Kyger Creek 345 kVActive
AH1-541Chestnut 345 kVActive
AH1-543Mulberry – Tazewell 345 kVActive
AH1-567University Park 138 kVActive
AH1-570Headquarters - Millersburg Junction 69 kVActive
AH1-571Headquarters - Millersburg Junction 69 kVActive
AH1-617Harbert Metering 138 kVActive
AH1-644Spicewood Metering 138 kVActive
AH1-664Goddard-Plumville 138 kVActive
AH1-665Goddard-Plumsville 138 kV IIActive
AH1-666Flemingsburg - Spurlock 138 kVActive
AH1-669Circleville-Biers Run 138 kVActive
AH1-670Blue Mound-Chestnut 345 kVActive
AH1-686Hanging Rock 765 kVActive
AH1-698Braidwood 345 kVActive
AH1-702Byron 345 kVActive
AH1-714Lasalle 345 kVActive
AH1-718Nelson 345 kVActive
AH1-721Laurel-Cooper 161 kVActive
U2-030Four Mile Ridge Wind 138kVIn Service
U2-073Frostburg 138kV IIIn Service
V3-007Desoto-Tanners Creek #1 345kVIn Service
V4-067Cates Road Egg Harbor Township 12kVDeactivated
V4-073Yankee 12.5kVIn Service
W1-003Oak HallIn Service
W1-004Oak HallIn Service
W1-005Oak HallIn Service
W1-006Oak HallIn Service
W1-130Vine Road 12kVIn Service
W2-030Egg Harbor TownshipIn Service
W2-048Brokaw-LanesvilleIn Service
W3-077Broadway-Stewartsville 34.5kVIn Service
W4-005Blue Mound-LathamIn Service
X2-022Brokaw-LanesvilleIn Service
X3-005Wildwood 12kVIn Service
X3-066Church Hill 69kVIn Service
Y1-033Penn Mar-Rock Wood 115kVIn Service
Y1-049Wurno 34.5kVIn Service
Y1-079Wye Mills 69kVIn Service
Y1-080Dorchester 12kVIn Service
Y3-024Bluff Point 12kVIn Service
Y3-058Rockawalkin 69kVIn Service
Z2-076Worcester South 25kVIn Service
Z2-077Worcester North 25kVIn Service
Z2-087Pontiac MidPoint-Brokaw 345kVIn Service
Z2-115Deer Creek 12.47kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)Identified Impacts
AH1-239 System Reinforcements:
TOTrans Owner IDTitleAllocated Cost ($USD)
LGEETC2-LGEE-0002Line reconductor or parallel line$116,114
LGEETC2-LGEE-0003Replacing all terminal equipment at Elihu$63,316
LGEETC2-LGEE-0006Invalid - P2 contingency 69 kV not monitored$0
LGEELGEE_TC1_15527Load shedding of 10% PC load is allowed for P2 contingency$0
LGEELGEE_TC1_15521Load shedding of 10% PC load is allowed for P7 contingency$0
LGEETC2-LGEE-0013Invalid - common mode contingency over 69 kV addressed by load shedding or generation redispatch$0
LGEETC2-LGEE-0014Invalid - common mode contingency over 69 kV addressed by load shedding or generation redispatch$0
Grand Total:$179,430

System Reinforcement
Type
Load Flow
TO
LGEE
RTEP ID / TO ID
(Pending) / TC2-LGEE-0002
Title
Line reconductor or parallel line
Description
LG&E/KU has a project to reconductor this line scheduled for 11/2026 - New ratings would be 104/132 MVA SP and 161/178 MVA WP. Anything above these flows would require a new project to upgrade the line to larger conductor or build a parallel line. $3,000k
Total Cost ($USD)
$3,000,000
Allocated Cost ($USD)
$116,114
Time Estimate
0 to 36 Months

Contributor

FacilityContingency
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-179
12.4 MW5.1%$152,999
AG2-670
5.5 MW2.3%$68,086
AH1-034
7.3 MW3.0%$90,004
AH1-239
9.4 MW3.9%$116,114
AH1-427
5.1 MW2.1%$63,303
AH1-721
203.6 MW83.6%$2,509,494

System Reinforcement
Type
Load Flow
TO
LGEE
RTEP ID / TO ID
(Pending) / TC2-LGEE-0003
Title
Replacing all terminal equipment at Elihu
Description
Replacing all terminal equipment at Elihu LG&E/KU rating is 219/277 MVA SP & 335/368 MVA WP, flow would require replacement of all terminal equipment at Elihu. $3,000,000 36 months
Total Cost ($USD)
$3,000,000
Allocated Cost ($USD)
$63,316
Time Estimate
0 to 36 Months

Contributor

FacilityContingency
5ELIHU-5COOPER2 161.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-179
10.0 MW1.6%$47,842
AG2-670
8.3 MW1.3%$39,872
AH1-034
9.8 MW1.6%$47,141
AH1-239
13.2 MW2.1%$63,316
AH1-427
6.1 MW1.0%$29,321
AH1-721
577.8 MW92.4%$2,772,508

System Reinforcement
Type
Load Flow
TO
LGEE
RTEP ID / TO ID
(Pending)
Title
LGEE Summer 83/105 & winter 128/141
Description
LGEE Summer 83/105 & winter 128/141
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
LGEE
RTEP ID / TO ID
(Pending)
Title
LGEE Project scheduled for 11/30/2026 Summer 104/132 & winter 161/178
Description
LGEE Summer 104/132 & winter 161/178 Project scheduled for 11/30/2026
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
LGEE
RTEP ID / TO ID
(Pending) / TC2-LGEE-0006
Title
Invalid - P2 contingency 69 kV not monitored
Description
Per LG&E/KU: LG&E/KU does not monitor the 69kV for this NERC Cont Cat
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
LGEE
RTEP ID / TO ID
(Pending) / LGEE_TC1_15519
Title
Invalid - P7 contingency 69kV not monitored by LGEE
Description
Invalid - P7 contingency 69kV not monitored by LGEE EKPC emergency rating is 143 MVA on the Somerset KU - Ferguston 69kV line.
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
LGEE
RTEP ID / TO ID
(Pending) / LGEE_TC1_15527
Title
Load shedding of 10% PC load is allowed for P2 contingency
Description
Load shedding of 10% PC load is allowed for P2 contingency
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
4LEBANON-4MARION CO 138.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
LGEE
RTEP ID / TO ID
(Pending) / LGEE_TC1_15521
Title
Load shedding of 10% PC load is allowed for P7 contingency
Description
Load shedding of 10% PC load is allowed for P7 contingency
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
4LEBANON-4MARION CO 138.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
LGEE
RTEP ID / TO ID
(Pending) / TC2-LGEE-0013
Title
Invalid - common mode contingency over 69 kV addressed by load shedding or generation redispatch
Description
LG&E/KU planning guidelines permit redispatch of generation or 5% load shedding to resolve overload for the contingency category
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
4LEBANON-4MARION CO 138.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
LGEE
RTEP ID / TO ID
(Pending) / LGEE_TC1_15524
Title
Load shedding of 10% PC load is allowed for P7 contingency
Description
Load shedding of 10% PC load is allowed for P7 contingency
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
5ELIHU-5COOPER2 161.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
LGEE
RTEP ID / TO ID
(Pending) / TC2-LGEE-0014
Title
Invalid - common mode contingency over 69 kV addressed by load shedding or generation redispatch
Description
LG&E/KU planning guidelines permit redispatch of generation or 5% load shedding to resolve overload for the contingency category
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
5ELIHU-5COOPER2 161.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
LGEE
RTEP ID / TO ID
(Pending)
Title
Load shedding of 10% PC load is allowed for P2 contingency
Description
Load shedding of 10% PC load is allowed for P2 contingency
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
5ELIHU-5COOPER2 161.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
LGEE
RTEP ID / TO ID
(Pending) / LGEE_TC1_15525
Title
Load shedding of 10% PC load is allowed for P4 contingency
Description
Load shedding of 10% PC load is allowed for P4 contingency
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
5ELIHU-5COOPER2 161.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
LGEE
RTEP ID / TO ID
(Pending) / LGEE_TC1_15510
Title
Upgrade terminal equipment at Elihu 161kV associated with the Elihu-Cooper (EKPC) 161kV line to a minimum SE rating of 1200 amps.
Description
Upgrade terminal equipment at Elihu 161kV associated with the Elihu-Cooper (EKPC) 161kV line to a minimum SE rating of 1200 amps.
Total Cost ($USD)
$300,000
Allocated Cost ($USD)
$0
Time Estimate
TBD

Info

Note: AH1-239 contributes to the loading of an overloaded tie line facility between PJM and an affected system entity, which was identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line and will be confirmed in subsequent study phases, along with cost allocation of such upgrade if applicable, in coordination with the affected system.

FacilityContingency
5ELIHU-5COOPER2 161.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
LGEE
RTEP ID / TO ID
(Pending)
Title
LGEE Summer 219/277 MVA & winter 335/335 MVA Rate A/Rate B
Description
LGEE Summer 219/277 MVA & winter 335/335 MVA Rate A/Rate B
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
5ELIHU-5COOPER2 161.0 kV Ckt 1 line(Any)

Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with potential Affected System impacts. PJM initiates coordination with each Affected System Operator by providing a list of New Service Requests in the Cycle with potential impacts to their respective system. If the Affected System Operator indicates an Affected System Study is required, PJM will notify the Project Developer or Eligible Customer of the need for an Affected System Study. See below if any Affected System Operator requires a study for this project:

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Study Pending
Louisville Gas & Electric (LG&E)Study Pending
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

Based on the Phase I analysis results, this project may have a cost responsibility for the following System Reinforcements:

AH1-239 System Reinforcements:
TORTEP IDTitleAllocated Cost ($USD)
EKPC(Pending) / EKPC-tc2-nu001Albany-Upchurch Tap 69 kV Line Section Rebuild (3.79 miles)$6,035,000
EKPC(Pending) / EKPC-tc2-nu046Rebuild the AG1-471 Tap (Massingale Road)-AH1-239 Tap 69 kV line (Clinton County) (4.5 miles) using 556.5 MCM ACSR conductor.$4,215,000
EKPC(Pending) / EKPC-tc2-nu031Upchurch Tap-AH1-239 Tap (Clinton County) 69 kV Line Section Rebuild (1.5 miles)$2,117,433
EKPC(Pending) / EKPC-tc2-nu032Wayne County-Zula Junction N.O. 69 kV Line Section Rebuild (0.78 miles)$1,179,424
EKPC(Pending) / EKPC-tc2-nu034Zula Junction N.O.-AG1-471 (Massingale Road) 69 kV Line Section Rebuild (0.6 miles)$909,435
EKPC(Pending) / EKPC-tc2-nu011Fox Hollow-Patton Road Junction 69 kV Line Rebuild$582,014
EKPCn8369 / EKPC-tc1-r0015aReplace the existing Marion County 161/138 kV, 200 MVA transformer with a 300 MVA transformer.$403,283
EKPC(Pending) / EKPC-tc2-nu022Patton Road Junction-AH1-034 Tap (East Barren County) 69 kV Line Section Rebuild (4.7 miles)$395,847
EKPC(Pending) / EKPC-tc2-nu003Cooper CCGT-Alcalde 161 kV Double-Circuit Line Addition$388,355
EKPCn8368.2 / EKPC-tc1-r0012bRebuild the Cooper-Elihu 161 kV line section using 1272 MCM ACSS conductor (4.2 miles)$218,122
EKPCn9668.0 / r0004Increase the maximum operating temperature of the Summershade-Edm. JB Galloway Jct 69kV line section 266 MCM conductor to 212F (7.88 miles)$163,172
EKPC(Pending) / EKPC-tc2-nu002Albany-Upchurch Tap 69 kV Jumper Replacement$105,000
EKPC(Pending) / EKPC-tc2-nu033Wayne County-Zula Junction N.O. 69 kV Jumper Replacement$99,469
EKPCn6232.1 / EKPC-tc1-r0003bReplace the 1200A interconnection metering CTs with 1600A equipment.$11,752
EKPCn8364.1 / EKPC-tc1-r0009bReplace the 636 MCM ACSR conductor in the Marion County-KU Lebanon 138 kV line with 954 MCM ACSS conductor.$9,140
EKPCn7771.2 / EKPC-tc1-r0014aIncrease the maximum operating temperature of the Laurel County-Laurel Dam 161 kV line section 795 MCM conductor to 212 degrees F (~4.47 miles)$3,892
EKPCn8368.4 / EKPC-tc1-r0012dUpgrade the existing 795 MCM ACSR jumpers at the Cooper substation associated with the Cooper-Elihu 161 kV line using bundled 500 MCM CU or equivalent$739
EKPCn7771.1 / r0013Increase the maximum operating temperature of the Laurel County-Laurel Dam 161 kV line section 795 MCM conductor to 167 degrees F (~0.2 miles)$264
EKPCn8368.3 / EKPC-tc1-r0012cChange the Zone 3 relay setting at Elihu substation associated with the line protection to at least 383 MVA LTE rating.$211
Grand Total:$16,837,552

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement
Type
Load Flow
TO
EKPC
RTEP ID / TO ID
(Pending) / EKPC-tc2-nu001
Title
Albany-Upchurch Tap 69 kV Line Section Rebuild (3.79 miles)
Description
Rebuild the Albany-Upchurch Tap 69 kV line section (3.79 miles) using 556.5 ACSR conductor.
Total Cost ($USD)
$6,035,000
Allocated Cost ($USD)
$6,035,000
Time Estimate
12 to 20 Months

Contributor

FacilityContingency
2ALBANY-2UPCHURCH T 69.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AH1-239
80.0 MW100.0%$6,035,000

System Reinforcement
Type
Load Flow
TO
EKPC
RTEP ID / TO ID
(Pending) / EKPC-tc2-nu046
Title
Rebuild the AG1-471 Tap (Massingale Road)-AH1-239 Tap 69 kV line (Clinton County) (4.5 miles) using 556.5 MCM ACSR conductor.
Description
Rebuild the AG1-471 Tap (Massingale Road)-AH1-239 Tap 69 kV line (Clinton County) (4.5 miles) using 556.5 MCM ACSR conductor.
Total Cost ($USD)
$4,215,000
Allocated Cost ($USD)
$4,215,000
Time Estimate
20 to 25 Months

Contributor

FacilityContingency
AG1-471 TP-AH1-239 TP 69.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AH1-239
80.0 MW100.0%$4,215,000

System Reinforcement
Type
Load Flow
TO
EKPC
RTEP ID / TO ID
(Pending) / EKPC-tc2-nu031
Title
Upchurch Tap-AH1-239 Tap (Clinton County) 69 kV Line Section Rebuild (1.5 miles)
Description
Rebuild the Upchurch Tap-AH1-239 Tap (Clinton County) 69 kV line section (1.5 miles) using 556.5 ACSR conductor.
Total Cost ($USD)
$2,390,000
Allocated Cost ($USD)
$2,117,433
Time Estimate
12 to 18 Months

Contributor

FacilityContingency
2UPCHURCH T-AH1-239 TP 69.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AH1-239
80.0 MW88.6%$2,117,433
AH1-721
10.3 MW11.4%$272,567

System Reinforcement
Type
Load Flow
TO
EKPC
RTEP ID / TO ID
(Pending) / EKPC-tc2-nu032
Title
Wayne County-Zula Junction N.O. 69 kV Line Section Rebuild (0.78 miles)
Description
Rebuild the Wayne County-Zula Junction N.O. 69 kV line section (0.78 miles) using 556.5 ACSR conductor.
Total Cost ($USD)
$1,245,000
Allocated Cost ($USD)
$1,179,424
Time Estimate
12 to 18 Months

Contributor

FacilityContingency
2WAYNE CO-2ZULA J NO 69.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AH1-034
4.4 MW5.3%$65,576
AH1-239
80.0 MW94.7%$1,179,424

System Reinforcement
Type
Load Flow
TO
EKPC
RTEP ID / TO ID
(Pending) / EKPC-tc2-nu034
Title
Zula Junction N.O.-AG1-471 (Massingale Road) 69 kV Line Section Rebuild (0.6 miles)
Description
Rebuild the Zula Junction N.O.-AG1-471 (Massingale Road) 69 kV line section (0.6 miles) using 556.5 ACSR conductor.
Total Cost ($USD)
$960,000
Allocated Cost ($USD)
$909,435
Time Estimate
12 to 18 Months

Contributor

FacilityContingency
2ZULA J NO-AG1-471 TP 69.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AH1-034
4.4 MW5.3%$50,565
AH1-239
80.0 MW94.7%$909,435

System Reinforcement
Type
Load Flow
TO
EKPC
RTEP ID / TO ID
(Pending) / EKPC-tc2-nu011
Title
Fox Hollow-Patton Road Junction 69 kV Line Rebuild
Description
Rebuild the Fox Hollow-Patton Road Junction 69 kV line section (3.34 miles) using 795 MCM ACSR conductor.
Total Cost ($USD)
$5,795,000
Allocated Cost ($USD)
$582,014
Time Estimate
13 to 20 Months

Contributor

FacilityContingency
2FOX HOLLOW-2PATTON RD J 69.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-179
6.5 MW7.0%$407,416
AG2-424
3.3 MW3.6%$208,056
AG2-670
4.7 MW5.1%$297,402
AH1-034
54.8 MW59.5%$3,450,687
AH1-239
9.2 MW10.0%$582,014
AH1-721
13.5 MW14.7%$849,424

System Reinforcement: n8369
Type
Load Flow
TO
EKPC
RTEP ID / TO ID
n8369 / EKPC-tc1-r0015a
Title
Replace the existing Marion County 161/138 kV, 200 MVA transformer with a 300 MVA transformer.
Description
Replace the existing Marion County 161/69 kV, 200 MVA transformer with a 300 MVA transformer.
Total Cost ($USD)
$8,825,000
Allocated Cost ($USD)
$403,283
Time Estimate
36 to 42 Months

Contributor

FacilityContingency
5MARION CO-4MARION CO 161.0/138.0 kV Ckt 1 transformer(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-179
6.1 MW4.8%$423,137
AG2-670
16.9 MW13.2%$1,168,004
AH1-034
6.8 MW5.3%$468,635
AH1-239
5.8 MW4.6%$403,283
AH1-721
92.3 MW72.1%$6,361,942

System Reinforcement
Type
Load Flow
TO
EKPC
RTEP ID / TO ID
(Pending) / EKPC-tc2-nu022
Title
Patton Road Junction-AH1-034 Tap (East Barren County) 69 kV Line Section Rebuild (4.7 miles)
Description
Rebuild the Patton Road Junction-AH1-034 Tap (East Barren County) 69 kV line section (4.7 miles) using 954 MCM ACSR conductor.
Total Cost ($USD)
$8,965,000
Allocated Cost ($USD)
$395,847
Time Estimate
15 to 23 Months

Contributor

FacilityContingency
2PATTON RD J-AH1-034 TP 69.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-179
3.6 MW3.1%$277,116
AH1-034
100.0 MW86.1%$7,714,660
AH1-239
5.1 MW4.4%$395,847
AH1-721
7.5 MW6.4%$577,377

System Reinforcement
Type
Load Flow
TO
EKPC
RTEP ID / TO ID
(Pending) / EKPC-tc2-nu003
Title
Cooper CCGT-Alcalde 161 kV Double-Circuit Line Addition
Description
Construct a new double-circuit 161 kV line between EKPC's new Cooper CCGT substation and the LG&E/KU Alcalde substation (approximate length of 5 miles) using 1272 MCM ACSS conductor.
Total Cost ($USD)
$15,730,000
Allocated Cost ($USD)
$388,355
Time Estimate
22 to 36 Months

Contributor

FacilityContingency
(Any)EKPC_P2-2_ELIHU-COOP 161_SRT-A
(Any)EKPC_P7-1_COOP 161 DBL 2_SRT-A-1
(Any)EKPC_P2-2_COOPER 2 161_SRT-A
(Any)EKPC_P2-2_COOP-LAURD 161_SRT-A
(Any)EKPC_P2-2_COOPER 1 161_SRT-A
(Any)EKPC_P1-2_COOP-DEN161_SRT-A-1
(Any)EKPC_P2-3_COOP S42-1024_SRT-A
(Any)EKPC_P7-1_COOP 161 DBL 1_SRT-A
(Any)EKPC_P2-3_COOP S42-210G_SRT-A
(Any)EKPC_P1-2_COOP-LAUREL161_SRT-A-1
(Any)EKPC_P1-2_COOP-ELIHU161_SRT-A
(Any)EKPC_P7-1_COOP 161 DBL 2_SRT-A-2
(Any)EKPC_P2-3_COOP S42-1039_SRT-A
(Any)EKPC_P2-3_COOP S42-1008_SRT-A
(Any)EKPC_P1-2_COOP 161 TIE_SRT-A
(Any)EKPC_P2-3_COOP S42-1014_SRT-A
2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line(Any)
5LAUREL CO-5LAUREL DAM 161.0 kV Ckt 1 line(Any)
5ELIHU-5COOPER2 161.0 kV Ckt 1 line(Any)
5COOPER1-5COOPER2 161.0 kV Ckt 1 line(Any)
5COOPER2-AH1-721 TP 161.0 kV Ckt 1 line(Any)
5COOPER2-AH1-721 TP 161.0 kV Ckt 2 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-179
118.0 MW1.1%$172,619
AG2-298
53.4 MW0.5%$78,102
AG2-424
8.3 MW0.1%$12,126
AG2-670
61.6 MW0.6%$90,148
AH1-034
202.7 MW1.9%$296,637
AH1-239
265.4 MW2.5%$388,355
AH1-427
163.7 MW1.5%$239,579
AH1-721
9875.8 MW91.9%$14,452,434

System Reinforcement: n8368.2
Type
Load Flow
TO
EKPC
RTEP ID / TO ID
n8368.2 / EKPC-tc1-r0012b
Title
Rebuild the Cooper-Elihu 161 kV line section using 1272 MCM ACSS conductor (4.2 miles)
Description
Rebuild the Cooper-Elihu 161 kV line section using 1272 MCM ACSS conductor (4.2 miles).
Total Cost ($USD)
$10,335,000
Allocated Cost ($USD)
$218,122
Time Estimate
16 to 27 Months

Contributor

FacilityContingency
5ELIHU-5COOPER2 161.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-179
10.0 MW1.6%$164,815
AG2-670
8.3 MW1.3%$137,359
AH1-034
9.8 MW1.6%$162,401
AH1-239
13.2 MW2.1%$218,122
AH1-427
6.1 MW1.0%$101,011
AH1-721
577.8 MW92.4%$9,551,291

System Reinforcement: n9668.0
Type
Load Flow
TO
EKPC
RTEP ID / TO ID
n9668.0 / r0004
Title
Increase the maximum operating temperature of the Summershade-Edm. JB Galloway Jct 69kV line section 266 MCM conductor to 212F (7.88 miles)
Description
Increase the maximum operating temperature of the Summershade-Edm. JB Galloway Jct 69kV line section 266 MCM conductor to 212F (7.88 miles)
Total Cost ($USD)
$420,000
Allocated Cost ($USD)
$163,172
Time Estimate
12 to 15 Months

Contributor

FacilityContingency
2EDM-JBGAL J-2SUMM SHADE 69.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AH1-034
5.9 MW61.1%$256,828
AH1-239
3.7 MW38.9%$163,172

System Reinforcement
Type
Load Flow
TO
EKPC
RTEP ID / TO ID
(Pending) / EKPC-tc2-nu002
Title
Albany-Upchurch Tap 69 kV Jumper Replacement
Description
Replace the 4/0 ACSR jumpers at the Albany substation associated with the Albany-Upchurch Tap 69 kV line section using 556.5 ACSR or larger conductor.
Total Cost ($USD)
$105,000
Allocated Cost ($USD)
$105,000
Time Estimate
9 to 15 Months

Contributor

FacilityContingency
2ALBANY-2UPCHURCH T 69.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AH1-239
80.0 MW100.0%$105,000

System Reinforcement
Type
Load Flow
TO
EKPC
RTEP ID / TO ID
(Pending) / EKPC-tc2-nu033
Title
Wayne County-Zula Junction N.O. 69 kV Jumper Replacement
Description
Replace the 266.8 MCM ACSR jumpers at the Wayne County substation associated with the Wayne County-Zula Junction N.O. 69 kV line section using 556.5 MCM ACSR or larger conductor.
Total Cost ($USD)
$105,000
Allocated Cost ($USD)
$99,469
Time Estimate
9 to 15 Months

Contributor

FacilityContingency
2WAYNE CO-2ZULA J NO 69.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AH1-034
4.4 MW5.3%$5,531
AH1-239
80.0 MW94.7%$99,469

System Reinforcement: n6232.1
Type
Load Flow
TO
EKPC
RTEP ID / TO ID
n6232.1 / EKPC-tc1-r0003b
Title
Replace the 1200A interconnection metering CTs with 1600A equipment.
Description
Replace the 1200A interconnection metering CTs with 1600A equipment.
Total Cost ($USD)
$345,000
Allocated Cost ($USD)
$11,752
Time Estimate
12 to 15 Months

Contributor

FacilityContingency
2SOMERSET-2SOMERSET KU 69.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-179
8.7 MW3.6%$12,414
AG2-670
5.0 MW2.1%$7,172
AH1-034
5.8 MW2.4%$8,230
AH1-239
8.2 MW3.4%$11,752
AH1-427
5.2 MW2.2%$7,510
AH1-721
208.2 MW86.4%$297,922

System Reinforcement: n8364.1
Type
Load Flow
TO
EKPC
RTEP ID / TO ID
n8364.1 / EKPC-tc1-r0009b
Title
Replace the 636 MCM ACSR conductor in the Marion County-KU Lebanon 138 kV line with 954 MCM ACSS conductor.
Description
Replace the 636 MCM ACSR conductor in the Marion County-KU Lebanon 138 kV line with 954 MCM ACSS conductor.
Total Cost ($USD)
$200,000
Allocated Cost ($USD)
$9,140
Time Estimate
21 to 27 Months

Contributor

FacilityContingency
4LEBANON-4MARION CO 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-179
6.1 MW4.8%$9,590
AG2-670
16.9 MW13.2%$26,470
AH1-034
6.8 MW5.3%$10,621
AH1-239
5.8 MW4.6%$9,140
AH1-721
92.3 MW72.1%$144,180

System Reinforcement: n7771.2
Type
Load Flow
TO
EKPC
RTEP ID / TO ID
n7771.2 / EKPC-tc1-r0014a
Title
Increase the maximum operating temperature of the Laurel County-Laurel Dam 161 kV line section 795 MCM conductor to 212 degrees F (~4.47 miles)
Description
Increase the maximum operating temperature of the Laurel County-Laurel Dam 161 kV line section 795 MCM conductor to 212 degrees F (~4.47 miles)
Total Cost ($USD)
$515,000
Allocated Cost ($USD)
$3,892
Time Estimate
12 to 15 Months

Contributor

FacilityContingency
5LAUREL CO-5LAUREL DAM 161.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-179
5.5 MW0.7%$3,546
AH1-239
6.0 MW0.8%$3,892
AH1-721
785.6 MW98.6%$507,562

System Reinforcement: n8368.4
Type
Load Flow
TO
EKPC
RTEP ID / TO ID
n8368.4 / EKPC-tc1-r0012d
Title
Upgrade the existing 795 MCM ACSR jumpers at the Cooper substation associated with the Cooper-Elihu 161 kV line using bundled 500 MCM CU or equivalent
Description
Upgrade the existing 795 MCM ACSR jumpers at the Cooper substation associated with the Cooper-Elihu 161 kV line using bundled 500 MCM CU or equivalent
Total Cost ($USD)
$35,000
Allocated Cost ($USD)
$739
Time Estimate
9 to 12 Months

Contributor

FacilityContingency
5ELIHU-5COOPER2 161.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-179
10.0 MW1.6%$558
AG2-670
8.3 MW1.3%$465
AH1-034
9.8 MW1.6%$550
AH1-239
13.2 MW2.1%$739
AH1-427
6.1 MW1.0%$342
AH1-721
577.8 MW92.4%$32,346

System Reinforcement: n7771.1
Type
Load Flow
TO
EKPC
RTEP ID / TO ID
n7771.1 / r0013
Title
Increase the maximum operating temperature of the Laurel County-Laurel Dam 161 kV line section 795 MCM conductor to 167 degrees F (~0.2 miles)
Description
Total Cost ($USD)
$35,000
Allocated Cost ($USD)
$264
Time Estimate
6 Months

Contributor

FacilityContingency
5LAUREL CO-5LAUREL DAM 161.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-179
5.5 MW0.7%$241
AH1-239
6.0 MW0.8%$264
AH1-721
785.6 MW98.6%$34,495

System Reinforcement: n8368.3
Type
Load Flow
TO
EKPC
RTEP ID / TO ID
n8368.3 / EKPC-tc1-r0012c
Title
Change the Zone 3 relay setting at Elihu substation associated with the line protection to at least 383 MVA LTE rating.
Description
Change the Zone 3 relay setting at Elihu substation associated with the line protection to at least 383 MVA LTE rating.
Total Cost ($USD)
$10,000
Allocated Cost ($USD)
$211
Time Estimate
9 to 12 Months

Contributor

FacilityContingency
5ELIHU-5COOPER2 161.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-179
10.0 MW1.6%$159
AG2-670
8.3 MW1.3%$133
AH1-034
9.8 MW1.6%$157
AH1-239
13.2 MW2.1%$211
AH1-427
6.1 MW1.0%$98
AH1-721
577.8 MW92.4%$9,242

System Reinforcement: b4000.10
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.10
Title
Install four 250 MVAR cap banks (two on 765 and two on 500 kV side) and a +/-500 MVAR STATCOM on the 765 kV Rocky Point yard
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-239 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-239 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)

System Reinforcement: b4000.7
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.7
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line - in DVP local area/Millville to Lovettsville section, roughly 10.5 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-239 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-239 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)

System Reinforcement: b4000.11
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.11
Title
Expand Black Oak Substation & Loop in the 502 Jct-Woodside 500 kV line (Projected ISD 6/1/2029)
Description
Expand Black Oak Substation to accommodate the connection of the 502 Jct-Woodside 500 kV line and loop the 502 Jct-Woodside 500 kV line into the Black Oak substation by constructing ~0.85 miles of new 500 kV line into and out of Black Oak 500 kV substation
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-239 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-239 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.1
Title
Add two 765 kV breakers at Amos Substation to expand the breaker and a half scheme to accommodate the new Amos-Welton Spring 765 kV line (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-239 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-239 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)

System Reinforcement: b4000.2
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.2
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - AEP Section of the line is 30 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-239 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-239 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.6
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.6
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (Welton Spring to DVP local area, roughly 21 miles) (VA Portion)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-239 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-239 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.9
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.9
Title
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard (Projected ISD 6/1/2029)
Description
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard. Loop in the Doubs-Goose Creek 500 kV line, the Doubs-Aspen 500 kV line, and the Woodside-Goose Creek 500 kV line. Install two 765/500 kV transformer at Rocky Point substation. 765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-239 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-239 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.5
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.5
Title
Install four 250 MVAR shunt capacitors, and a +/-500 MVAR STATCOM at Welton Spring 765 kV substation
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-239 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-239 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.4
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.4
Title
Construct a new 765 kV switchyard - Welton Spring (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-239 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-239 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.8
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.8
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (DVP local area to Rocky Point, roughly 4.8 miles)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-239 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-239 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.3
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.3
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - APS/FE Section of the line is 145 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-239 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-239 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)

System Reinforcement: b3788.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b3788.1 / B3788.1
Title
Replace limiting station elements at Kyger Creek
Description
Upgrade existing 345 kV terminal equipment at Kyger Creek on the Kyger Creek-Sporn 345 kV line. Projected in-service date 6/1/2028 Replace AEP-owned station takeoff riser and breaker BB risers at OVEC-owned Kyger Creek station.
Cost Information
Time Estimate
Nov 18 2027

Not Contingent

Note: AH1-239 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-239 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05SPORN-06KYGER 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18751
Title
05KYGER 345kV to 05SPORN 345kV ckt 1 - Replace Equipment and Sag Study
Description
Sag study Sporn - Kyger Creek line and at Kyger Creek Replace the following equipment: 2156.0 KCM ACSR (84/19), 3000A Switch, CB-BB, 2870 MCM ACSR (Bus), GCB AA, Wave Trap, Line Relay/CT, Meters, Switch 104, and Switch 10
Total Cost ($USD)
$5,052,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 60 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-239 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-239 could receive cost allocation. Although AH1-239 may not presently have cost responsibility for this upgrade, AH1-239 is a potential Aggregate Pool Contributor.

FacilityContingency
05SPORN-06KYGER 345.0 kV Ckt 1 line(Any)

System Reinforcement: b3788.2
Type
Load Flow
TO
OVEC
RTEP ID / TO ID
b3788.2 / B3788.2
Title
Replace limiting station elements at Kyger Creek
Description
Upgrade existing 345 kV terminal equipment at Kyger Creek on the Kyger Creek-Sporn 345 kV line. Projected in-service date 6/1/2028 Replace OVEC-owned breaker AA risers, bus work, and breaker AA disconnect switches at OVEC-owned Kyger Creek station.
Cost Information
Time Estimate
Jun 01 2028

Not Contingent

Note: AH1-239 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-239 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05SPORN-06KYGER 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dayton
RTEP ID / TO ID
(Pending) / Dayton-TC2-18817
Title
Replace Stuart Switches to 4000 A
Description
Replace Stuart Switches to 4000 A
Total Cost ($USD)
$1,200,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 60 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-239 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-239 could receive cost allocation. Although AH1-239 may not presently have cost responsibility for this upgrade, AH1-239 is a potential Aggregate Pool Contributor.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dayton
RTEP ID / TO ID
(Pending) / Dayton-TC2-18818
Title
Replace Wavetrap to 4000 A
Description
Replace Wavetrap to 4000 A
Total Cost ($USD)
$100,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 60 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-239 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-239 could receive cost allocation. Although AH1-239 may not presently have cost responsibility for this upgrade, AH1-239 is a potential Aggregate Pool Contributor.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 line(Any)

System Reinforcement: n9670.0
Type
Load Flow
TO
Dayton
RTEP ID / TO ID
n9670.0 / DAYr190039
Title
Reconductor Stuart-Spurlock line with twin bundle 1033 Curlew ACCR conductor.
Description
Reconductor Stuart-Spurlock line with twin bundle 1033 Curlew ACCR conductor.
Total Cost ($USD)
$50,000,000
Allocated Cost ($USD)
$0
Time Estimate
60 to 72 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-239 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-239 could receive cost allocation. Although AH1-239 may not presently have cost responsibility for this upgrade, AH1-239 is a potential Aggregate Pool Contributor.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 line(Any)

System Reinforcement: n9671.0
Type
Load Flow
TO
Dayton
RTEP ID / TO ID
n9671.0 / DAYr190040
Title
Replace Stuart substation bus and conductor
Description
Replace Stuart substation bus and conductor
Total Cost ($USD)
$1,000,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 60 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-239 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-239 could receive cost allocation. Although AH1-239 may not presently have cost responsibility for this upgrade, AH1-239 is a potential Aggregate Pool Contributor.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 line(Any)

System Reinforcement: n9672.0
Type
Load Flow
TO
Dayton
RTEP ID / TO ID
n9672.0 / DAYr190041
Title
Replace Stuart substation breakers to 4000 A breakers
Description
Replace Stuart substation breakers to 4000 A breakers
Total Cost ($USD)
$2,000,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 60 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-239 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-239 could receive cost allocation. Although AH1-239 may not presently have cost responsibility for this upgrade, AH1-239 is a potential Aggregate Pool Contributor.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 line(Any)

System Reinforcement: n9673.0
Type
Load Flow
TO
EKPC
RTEP ID / TO ID
n9673.0 / EKPC-tc1-r0020b
Title
Replace the 1500A interconnection metering CTs at Spurlock Station with 2000A equipment.
Description
Replace the 1500A interconnection metering CTs at Spurlock Station with 2000A equipment.
Total Cost ($USD)
$1,295,000
Allocated Cost ($USD)
$0
Time Estimate
18 to 21 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-239 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-239 could receive cost allocation. Although AH1-239 may not presently have cost responsibility for this upgrade, AH1-239 is a potential Aggregate Pool Contributor.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
EKPC
RTEP ID / TO ID
(Pending) / EKPC-tc1-r0020a
Title
Dayton Power & Light addresses its limiting elements (EKPC limits are 1777/1792/1792 for Rate A/B/C).
Description
Dayton Power & Light addresses its limiting elements (EKPC limits are 1777/1792/1792 for Rate A/B/C).
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 line(Any)

System Reinforcement: s3170.0
Type
Load Flow
TO
EKPC
RTEP ID / TO ID
s3170.0 / s3170
Title
Rebuild the 4.4 mile, Snow Tap-North Albany 69 kV line using 556.5 conductor and steel pole construction.
Description
Rebuild the 4.4 mile, Snow Tap-North Albany 69 kV line using 556.5 conductor and steel pole construction.
Cost Information
Time Estimate
Jun 01 2026

Contingent

Note: Although AH1-239 may not presently have cost responsibility for this upgrade, AH1-239 may need this upgrade in-service to be deliverable to the PJM system. If AH1-239 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
2ALBANY-2SNOW T 69.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
EKPC
RTEP ID / TO ID
(Pending) / EKPC-tc1-r0004a
Title
EKPC emergency rating is 143 MVA.
Description
EKPC emergency rating is 143 MVA. LG&E: SE rating is 105 MVA.
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
2FERGUSON SO-2SOMERSET KU 69.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
EKPC
RTEP ID / TO ID
(Pending) / EKPC-tc1-r0009a
Title
LGE/KU to address limiting element.
Description
LGE/KU addresses limiting element on its side of the interconnection. Cost and scope to be determined by LGE/KU via Affected System study
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
4LEBANON-4MARION CO 138.0 kV Ckt 1 line(Any)

System Reinforcement: n6833.1
Type
Load Flow
TO
EKPC
RTEP ID / TO ID
n6833.1 / EKPC-tc1-r0011a
Title
Increase the maximum operating temperature of the 636 MCM ACSR conductor in the Casey County-Liberty Junction 161 kV line section to 176 degrees F.
Description
Increase the maximum operating temperature of the 636 MCM ACSR conductor in the Casey County-Liberty Junction 161 kV line section to 176 degrees F. (13.36 mile)
Total Cost ($USD)
$1,155,000
Allocated Cost ($USD)
$0
Time Estimate
12 to 18 Months

Contingent

Note: Based on PJM cost allocation criteria, AH1-239 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-239 could receive cost allocation. Although AH1-239 may not presently have cost responsibility for this upgrade, AH1-239 may need this upgrade in-service to be deliverable to the PJM system. If AH1-239 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
5CASEY CO-5LIBERTY J 161.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
EKPC
RTEP ID / TO ID
(Pending) / EKPC-tc1-r0012a
Title
LGE/KU is limiting this facility. EKPC emergency rating is 298 MVA.
Description
LGE/KU is limiting this facility (LGEE Summer 219/277 MVA & winter 335/335 MVA Rate A/Rate B). EKPC emergency rating is 298 MVA. LGEE AFS for TC1 has determined they will not require an reinforcement and thus EKPC existing 298 MVA Rate B is adequate as LGEE is the limiting element of the line.
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
5ELIHU-5COOPER2 161.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.350
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.350
Title
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Description
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AH1-239 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-239 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.355
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.355
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-239 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-239 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.342
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.342
Title
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Description
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Cost Information
Time Estimate
Jul 13 2029

Not Contingent

Note: AH1-239 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-239 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.326
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.326
Title
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Description
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Cost Information
Time Estimate
Feb 24 2029

Not Contingent

Note: AH1-239 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-239 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.351
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.351
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AH1-239 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-239 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.345
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.345
Title
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AH1-239 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-239 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.357
Title
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Description
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-239 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-239 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.327
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.327
Title
Upgrade/install equipment at Ladysmith Substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230 kV strings of breaker and a half scheme.
Description
Upgrade/install equipment at Ladysmith substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230kV strings of breaker and a half scheme.
Cost Information
Time Estimate
Feb 24 2029

Not Contingent

Note: AH1-239 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-239 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.348
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.348
Title
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.
Description
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers. A new redundant breaker ring will be added at Kraken to accommodate the new 500kV line from North Anna to Kraken.
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-239 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-239 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.341
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.341
Title
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.
Description
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV substation and extend approximately 0.2 miles of conductor to fly-over the site.
Cost Information
Time Estimate
Jul 13 2029

Not Contingent

Note: AH1-239 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-239 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.325
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.325
Title
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Description
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Cost Information
Time Estimate
Feb 24 2029

Not Contingent

Note: AH1-239 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-239 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.344
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.344
Title
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AH1-239 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-239 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.352
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.352
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AH1-239 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-239 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.349
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.349
Title
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Description
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AH1-239 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-239 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.346
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.346
Title
Cut-in 500kV line from Kraken substation into Yeat substation
Description
Cut-in 500kV line from Kraken substation into Yeat substation
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-239 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-239 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.356
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.356
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-239 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-239 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

Attachments

AH1-239 One Line Diagram

AH1-239 One Line Diagram.pdf
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.