AH1-272 Phase I Study Report

v1.00 released 2025-10-29 20:54

Argenta - Twin Branch 345 kV

123.9 MW Capacity / 185.0 MW Energy

Introduction

This Phase I System Impact Study Report (PH1) has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, sections 307 and 308 for New Service Requests (projects) in Transition Cycle 2. The Project Developer/Eligible Customer (developer) is Bankson Solar Project, LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is American Electric Power.

Preface

The Phase I System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle executive summary format and (ii) an individual project-level basis. The Phase I System Impact Study Results (for both the executive summary and individual reports) will be publicly available on PJM’s website. Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.3, PJM takes the following actions during the Phase I System Impact Study:
  1. PJM studies each New Service Request on a summer peak, winter peak and light load RTEP base case study. The case year is dependent on the new services cycle under study. PJM will identify the base case year to be used in the study of a specific cycle on its website.
  2. PJM will only perform load flow analysis during the Phase I System Impact Study.
  3. In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with Affected System impacts and provides each Affected System Operator with a list of New Service Request in the Cycle with potential impacts to their respective system.
  4. PJM will create both the short circuit and stability base cases to be used in the Phase II System Impact Study.
  5. The Phase I System Impact Study results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.
The Transmission Owner takes the following actions during the Phase I System Impact Study:
  1. Identify required Interconnection Facilities to accommodate the New Service Request.
  2. Identify required Network Upgrades to mitigate system violations from the Phase I System Impact Study.
  3. Provide planning-level preliminary estimates of Interconnection Facilities and Network Upgrades including scope, cost and elapsed time to complete the work.

Decision Point I Requirements

At the close of Phase I System Impact Study, PJM will initiate Decision Point I (DP1). During DP1, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.A.1. Additional information on these elements is available in PJM Manual 14H sections 4.4, 6, and 7.

Allowable project modifications at Decision Point I are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

General

The Project Developer has proposed a Solar generating facility located in the American Electric Power zone — Van Buren County, Michigan. The installed facilities will have a total capability of 185.0 MW with 123.9 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AH1-272
Project Name:
Argenta - Twin Branch 345 kV
Project Developer Name:
Bankson Solar Project, LLC
State:
Michigan
County:
Van Buren
Transmission Owner:
American Electric Power
MFO:
185.0
MWE:
185.0
MWC:
123.9
Fuel Type:
Solar
Basecase Study Year:
2028

Physical Interconnection Facility Study

Physical Interconnection Facilities Study is not performed as part of the Phase I System Impact Study. Physical Interconnection Facilities Study will commence in the Phase II System Impact Study.

Point of Interconnection

AH1-272 will interconnect on the American Electric Power transmission system by tapping the Argenta (MISO) - Twin Branch 345 kV line.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In the Phase I SIS, the costs shown are subject to change as a result of a facility study performed by the TO during the Phase II or Phase III System Impact Study.

Based on the Phase I SIS results, the AH1-272 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit are also shown below.

Cost Summary
DescriptionCost Allocated to AH1-272Cost Subject to Readiness*
Transmission Owner Interconnection Facilities (TOIF)$0$0
Other Scope$0$0
Option To Build Oversight$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$31,073,000$31,073,000
Network Upgrades$0$0
System Reliability Network Upgrades
Steady State Thermal & Voltage (SP & LL)$11,224$11,224
Transient Stability$0$0
Short Circuit$0$0
Transmission Owner Analysis
SubRegional$0$0
Distribution$0$0
Affected System Reinforcements
AFS - PJM Violatons$0$0
AFS - Non-PJM Violations$0$0
Total$31,084,224$31,084,224

* Contributes to calculation for Readiness Deposit #2 (RD2). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim deliverability study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 309 (Decision Point I) A.1.a.i and PJM Manual 14H, section 6.2, Readiness Deposit #2 (RD2) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point I (DP1), the Project Developer or Eligible Customer is required to submit Readiness Deposit #2, which is calculated as 10% of cost allocation for required Phase I Network Upgrades minus Readiness Deposit #1.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Readiness Deposit #2 Due for Project AH1-272

Readiness Deposit #2 has been calculated for the project based on the Phase I System Impact Study results and is shown in the table below. This Readiness Deposit #2 must be provided at Decision Point I through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit
Project ID10% of cost allocation for Phase I Network UpgradesReadiness Deposit #1 Received (RD1)Readiness Deposit #2 (RD2) for AH1-272 Project due at DP1
ABA - B
AH1-272$3,108,422$740,000$2,368,422

Note: Failure to provide an acceptable form of Readiness Deposit #2 by the end of Decision Point I will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Stand-Alone Network Upgrades
RTEP IDDescriptionTotal Cost ($USD)Allocated Cost ($USD)
(Pending)AEP will construct a new ring bus station, initially populated with 3 breakers$31,073,000 $31,073,000

Based on the scope of work for the Interconnection Facilities, it is expected to take a range of 30 to 36 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

The schedule for any required Network Impact Reinforcements will be more clearly identified in the Phase II and Phase III System Impact Studies.

Remote end work required on a Facility owned by a non-PJM Transmission Owner:

 

Please note that your project interconnects directly to an AEP (PJM Transmission Owner) facility which shares a tie line with METC (non-PJM Transmission Owner).  The Transmission Owner Scope of Work above outlines the interconnection facilities required on the AEP facilities.  Your project will also require upgrades at the remote end METC facility.  It is your responsibility to engage with METC regarding the upgrade work required to accommodate this interconnection.

Transmission Owner Analysis

No Transmission Owner impacts identified.

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. AEP interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Meteorological Data Reporting Requirement
The solar generation facility shall provide the Transmission Provider with site-specific meteorological data including:
  • Temperature (degrees Fahrenheit)
  • Atmospheric Pressure (hectopascals)
  • Irradiance
  • Forced outage data
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AH1-272 was evaluated as a 185.0 MW (123.9 MW Capacity) injection in the AEP area.

AH1-272 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 185.0 MW (185.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P1-2_MP-500-007A_SRT-A
SingleAC130.62 %3729.0B4870.9814.87
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P1-2_MP-500-008A_SRT-SL
SingleAC124.1 %3729.0B4627.614.34
GD2ATSI
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line
ATSI_P2-3_TE-345-008B_SRT-SL
BreakerAC168.3 %1683.0B2832.5214.99
GD2ATSI
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line
ATSI_P2-3_TE-345-013_SRT-SL
BreakerAC146.58 %1683.0B2466.9915.4
GD2ATSI
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line
ATSI_P2-3_TE-345-014_SRT-A
BreakerAC146.58 %1683.0B2466.9715.4
GD2ATSI
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line
ATSI_P2-3_TE-345-009_SRT-A
BreakerAC146.4 %1683.0B2463.9915.38
GD2ATSI
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line
ATSI_P1-2_TE-345-602_SRT-A
SingleAC142.52 %1683.0B2398.5911.98
GD2ATSI
02BEAVER-02CARLIL 345.0 kV Ckt 1 line
ATSI_P7-1_OEC-345-002_SRT-A
TowerAC109.31 %1745.0B1907.4511.15
GD2ATSI
02BEAVER-02LAKEAVE 345.0 kV Ckt 1 line
ATSI_P2-3_OEC-345-901_SRT-SL
BreakerAC113.76 %1720.0B1956.710.15
GD2ATSI
02BEAVER-02LAKEAVE 345.0 kV Ckt 1 line
ATSI_P2-3_OEC-345-007A_SRT-SL
BreakerAC104.78 %1878.0B1967.8210.19
GD2ATSI
02BEAVER-02LAKEAVE 345.0 kV Ckt 1 line
ATSI_P2-3_OEC-345-031_SRT-A
BreakerAC100.84 %1878.0B1893.7210.06
GD2ATSI
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line
ATSI_P2-3_OEC-345-002_SRT-A
BreakerAC174.17 %1878.0B3270.9314.21
GD2ATSI
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line
ATSI_P2-3_OEC-345-003_SRT-SL
BreakerAC104.76 %1878.0B1967.4810.2
GD2ATSI
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line
ATSI_P2-3_OEC-345-028_SRT-A
BreakerAC101.37 %1878.0B1903.6510.11
GD2ATSI
02DAV-BE-02HAYES 345.0 kV Ckt 1 line
ATSI_P2-3_OEC-345-005_SRT-A
BreakerAC149.08 %1892.0B2820.5913.41
GD2ATSI
02DAV-BE-02HAYES 345.0 kV Ckt 1 line
ATSI_P2-3_OEC-345-006_SRT-SL
BreakerAC146.41 %1892.0B2770.1213.49
GD2ATSI
02DAV-BE-02HAYES 345.0 kV Ckt 1 line
ATSI_P2-3_TE-345-010A_SRT-SL
BreakerAC144.5 %1892.0B2733.8813.49
GD2ATSI
02DAV-BE-02HAYES 345.0 kV Ckt 1 line
ATSI_P1-2_OEC-345-825_SRT-A
SingleAC136.86 %1892.0B2589.3110.49
GD2ATSI
02DAV-BE-02HAYES 345.0 kV Ckt 1 line
ATSI_P1-2_OEC-345-824_SRT-A
SingleAC136.39 %1892.0B2580.5810.51
GD2ATSI
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line
ATSI_P2-3_OEC-345-1152-F1_SRT-A
BreakerAC155.03 %1646.0B2551.8413.0
GD2ATSI
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line
ATSI_P2-3_OEC-345-1152-12_SRT-A
BreakerAC155.03 %1646.0B2551.8413.0
GD2ATSI
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line
ATSI_P2-3_TE-345-010B1_SRT-SL
BreakerAC153.46 %1646.0B2525.9412.86
GD2ATSI
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line
ATSI_P2-3_TE-345-010B2_SRT-SL
BreakerAC153.46 %1646.0B2525.9412.86
GD2ATSI
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line
ATSI_P2-3_OEC-345-1152-3_SRT-A
BreakerAC151.55 %1646.0B2494.5712.83
GD2ATSI
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line
ATSI_P1-2_OEC-345-810_SRT-A
SingleAC136.64 %1646.0B2249.0110.01
GD2ATSI
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line
ATSI_P1-2_OEC-345-809_SRT-A
SingleAC128.94 %1646.0B2122.349.84
GD2ATSI
02HAYES-02BEAVER 345.0 kV Ckt 1 line
ATSI_P2-3_OEC-345-005_SRT-A
BreakerAC146.75 %1878.0B2755.8913.43
GD2ATSI
02HAYES-02BEAVER 345.0 kV Ckt 1 line
ATSI_P2-3_OEC-345-006_SRT-SL
BreakerAC144.08 %1878.0B2705.7413.58
GD2ATSI
02HAYES-02BEAVER 345.0 kV Ckt 1 line
ATSI_P2-3_TE-345-010A_SRT-SL
BreakerAC142.21 %1878.0B2670.7613.52
GD2ATSI
02HAYES-02BEAVER 345.0 kV Ckt 1 line
ATSI_P1-2_OEC-345-825_SRT-A
SingleAC136.05 %1878.0B2554.9510.52
GD2ATSI
02HAYES-02BEAVER 345.0 kV Ckt 1 line
ATSI_P1-2_OEC-345-824_SRT-A
SingleAC135.68 %1878.0B2548.0910.53
GD2AEP/ATSI
02LALLENDORF-05FOSTOR 345.0 kV Ckt 1 line
ATSI_P7-1_TE-345-021_SRT-A-1
TowerAC124.85 %1409.0B1759.159.68
GD2ATSI
02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line
ATSI_P2-3_TE-345-007_SRT-SL
BreakerAC137.87 %1878.0B2589.1914.84
GD2ATSI
02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line
ATSI_P2-3_TE-345-004_SRT-A
BreakerAC118.2 %1878.0B2219.815.24
GD2ATSI
02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line
ATSI_P2-3_TE-345-005_SRT-SL
BreakerAC118.2 %1878.0B2219.7315.24
GD2ATSI
02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line
ATSI_P2-3_TE-345-006_SRT-SL
BreakerAC118.2 %1878.0B2219.7315.24
GD2ATSI
02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line
ATSI_P1-2_TE-345-601_SRT-A
SingleAC113.99 %1878.0B2140.7311.87
GD2ATSI
02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line
ATSI_P7-1_TE-345-021_SRT-A-1
TowerAC109.02 %1878.0B2047.4313.11
GD2AEP
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC121.78 %1737.0B2115.310.1
GD2AEP
05BOKESCRK-05MARYSV 345.0 kV Ckt 1 line
AEP_P4_#7445_05MARYSV 765_B_SRT-A
BreakerAC117.99 %1302.0B1536.238.28
GD2AEP
05BOKESCRK-05MARYSV 345.0 kV Ckt 1 line
AEP_P4_#7441_05SORENS 765_J1_SRT-A
BreakerAC110.86 %1302.0B1443.458.65
GD2AEP
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line
AEP_P1-2_#709_546_SRT-A
SingleAC107.02 %5001.0B5352.1419.84
GD2AEP
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line
Base Case
SingleAC100.56 %4558.0A4583.4717.65
GD2AEP
05FLTLCK-05GAVIN_RF 765.0 kV Ckt 1 line
AEP_P4_#8075_05MARYSV 765_A2_SRT-A
BreakerAC103.34 %4349.0B4494.0823.44
GD2AEP
05GUNN RD SW-05BOKESCRK 345.0 kV Ckt 1 line
AEP_P4_#7445_05MARYSV 765_B_SRT-A
BreakerAC101.83 %1301.0B1324.818.46
GD2AEP
05HANGRCK_RJ-05HANG R 765.0 kV Ckt Z1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC106.88 %4571.0B4885.6617.28
GD2AEP
05HYATT-05VASSEL 345.0 kV Ckt 1 line
AEP_P4_#9728_05MALIS 138_L1_SRT-A
BreakerAC124.65 %1409.0B1756.356.33
GD2AEP
05HYATT-05VASSEL 345.0 kV Ckt 1 line
AEP_P4_#9730_05MALIS 138_P1_SRT-A
BreakerAC124.16 %1409.0B1749.366.32
GD2AEP
05HYATT-05VASSEL 345.0 kV Ckt 1 line
AEP_P4_#9729_05MALIS 138_M1_SRT-A
BreakerAC124.05 %1409.0B1747.916.31
GD2AEP
05HYATT-05VASSEL 345.0 kV Ckt 1 line
AEP_P2-2_#7222_05MALIS 765_1_SRT-A
BusAC112.44 %1409.0B1584.276.29
GD2AEP
05HYATT-05VASSEL 345.0 kV Ckt 1 line
AEP_P4_#7222_05MALIS 765_D_SRT-A
BreakerAC112.42 %1409.0B1584.056.29
GD2AEP
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer
AEP_P1-2_#709_546_SRT-A
SingleAC118.09 %3039.0B3588.6710.16
GD2AEP/OVEC
05JEFRSO-06CLIFTY 345.0 kV Ckt 1 line
AEP_P1-2_#709_546_SRT-A
SingleAC127.46 %2826.0B3601.9210.16
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P1-2_MP-500-007A_SRT-A
SingleAC131.92 %3792.0B5002.2814.87
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P1-2_MP-500-008A_SRT-SL
SingleAC125.38 %3792.0B4754.3314.34
GD2AEP
05MADDOX-05E LIMA 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC120.12 %2246.0B2697.989.68
GD2AEP
05MALIS-05VASSEL 765.0 kV Ckt 1 line
AP_P1-3_MP-765-501T_SRT-A
SingleAC130.8 %4142.0B5417.8616.34
GD2AEP
05MALIS-05VASSEL 765.0 kV Ckt 1 line
AEP_P4_#706_05GAVIN 765_C1_SRT-A
BreakerAC116.53 %4142.0B4826.4824.6
GD2AEP
05MALIS-05VASSEL 765.0 kV Ckt 1 line
AEP_P1-2_#706_SRT-A
SingleAC114.0 %4142.0B4722.0619.16
GD2AEP
05MALIS-05VASSEL 765.0 kV Ckt 1 line
ATSI_P7-1_TE-345-027A_SRT-A
TowerAC107.84 %4142.0B4466.8919.68
GD2AEP
05MALIS-05VASSEL 765.0 kV Ckt 1 line
ATSI_P7-1_TE-345-030_SRT-A
TowerAC107.63 %4142.0B4457.919.63
GD2AEP
05MALIS-05VASSEL 765.0 kV Ckt 1 line
Base Case
SingleAC100.2 %4142.0A4150.4414.03
GD2AEP
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
AP_P1-3_MP-765-501T_SRT-A
SingleAC130.64 %4571.0B5971.4316.35
GD2AEP
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
AEP_P1-2_#706_SRT-A
SingleAC116.18 %4571.0B5310.7719.68
GD2AEP
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Base Case
SingleAC114.73 %4047.0A4643.0214.03
GD2AEP
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
ATSI_P7-1_TE-345-027A_SRT-A
TowerAC109.99 %4571.0B5027.5115.97
GD2AEP
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
ATSI_P7-1_TE-345-030_SRT-A
TowerAC109.75 %4571.0B5016.8415.91
GD2AEP
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
AP_P1-3_MP-765-501T_SRT-A
SingleAC130.66 %4571.0B5972.5416.35
GD2AEP
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
AEP_P1-2_#706_SRT-A
SingleAC116.43 %4571.0B5322.0119.68
GD2AEP
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Base Case
SingleAC114.86 %4047.0A4648.2514.03
GD2AEP
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
ATSI_P7-1_TE-345-027A_SRT-A
TowerAC110.09 %4571.0B5032.3215.97
GD2AEP
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
ATSI_P7-1_TE-345-030_SRT-A
TowerAC109.86 %4571.0B5021.7215.91
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P1-2_#709_546_SRT-A
SingleAC145.65 %4142.0B6032.9326.67
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P4_#2995_05E LIMA 345_M_SRT-A
BreakerAC145.3 %4142.0B6018.3632.93
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P7-1_#11010___SRT-A
TowerAC141.23 %4142.0B5849.9332.98
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P1-2_#6463_16757_SRT-A
SingleAC140.14 %4142.0B5804.6625.63
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P7-1_#17567_SRT-SL
TowerAC140.03 %4142.0B5799.932.89
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P2-2_#16655_05GUNN RD SW 345_2_SRT-A
BusAC135.98 %4142.0B5632.1931.81
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P2-2_#16654_05GUNN RD SW 345_1_SRT-A
BusAC135.75 %4142.0B5622.5731.83
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Base Case
SingleAC130.5 %4047.0A5281.1923.96
GD2AEP
05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC132.35 %1868.0B2472.279.79
GD2AEP
05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer
AEP_P4_#7443_05DUMONT 765_A_SRT-A
BreakerAC116.16 %3097.0B3597.5521.94
GD2AEP
05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer
AEP_P4_#7442_05SORENS 765_K2_SRT-A
BreakerAC116.09 %3097.0B3595.3121.78
GD2AEP
05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer
AEP_P4_#7444_05DUMONT 765_A2_SRT-A
BreakerAC115.9 %3097.0B3589.5621.97
GD2AEP
05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer
AEP_P1-2_#7442_200545_SRT-A
SingleAC111.07 %3097.0B3439.7416.96
GD2AEP
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line
AEP_P1-2_#709_546_SRT-A
SingleAC109.05 %5523.0B6022.7726.67
GD2AEP
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line
AEP_P4_#2995_05E LIMA 345_M_SRT-A
BreakerAC108.54 %5523.0B5994.8832.93
GD2AEP
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line
AEP_P7-1_#11010___SRT-A
TowerAC105.44 %5523.0B5823.6832.98
GD2AEP
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line
AEP_P1-2_#6463_16757_SRT-A
SingleAC104.68 %5523.0B5781.325.63
GD2AEP
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line
AEP_P7-1_#17567_SRT-SL
TowerAC104.6 %5523.0B5777.1832.89
GD2AEP
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line
AEP_P2-2_#16655_05GUNN RD SW 345_2_SRT-A
BusAC101.5 %5523.0B5605.7931.81
GD2AEP
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line
AEP_P2-2_#16654_05GUNN RD SW 345_1_SRT-A
BusAC101.3 %5523.0B5594.7831.83
GD2AEP
05TWIN B-05MERIDN 345.0 kV Ckt 1 line
AEP_P4_#7442_05SORENS 765_K2_SRT-A
BreakerAC105.25 %897.0B944.1211.69
GD2ATSI/METC
18MOROCCO-02ALLEN 345.0 kV Ckt 1 line
ATSI_P2-3_TE-345-034T_SRT-A
BreakerAC108.58 %1793.0B1946.8120.2
GD2ATSI/METC
18MOROCCO-02ALLEN 345.0 kV Ckt 1 line
ATSI_P2-3_TE-345-033T_SRT-A
BreakerAC108.35 %1793.0B1942.6520.17
GD2ATSI/ITCT
19MON12-02LALLENDORF 345.0 kV Ckt 1 line
ATSI_P2-3_TE-345-023T_SRT-SL
BreakerAC117.29 %1660.0B1946.9420.75
GD2ATSI/ITCT
19MON12-02LALLENDORF 345.0 kV Ckt 1 line
ATSI_P2-3_TE-345-022T_SRT-A
BreakerAC117.16 %1660.0B1944.8520.75
GD2ATSI
AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line
ATSI_P2-3_OEC-345-009_SRT-SL
BreakerAC165.39 %1499.0B2479.1512.69
GD2ATSI
AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line
ATSI_P2-3_OEC-345-1152-12_SRT-A
BreakerAC145.45 %1798.0B2615.2612.97
GD2ATSI
AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line
ATSI_P2-3_OEC-345-1152-F1_SRT-A
BreakerAC145.45 %1798.0B2615.2612.97
GD2ATSI
AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line
ATSI_P2-3_OEC-345-1152-3_SRT-A
BreakerAC142.16 %1798.0B2556.0112.79
GD2ATSI
AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line
ATSI_P2-3_TE-345-010B1_SRT-SL
BreakerAC141.11 %1798.0B2537.1812.82
GD2ATSI
AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line
ATSI_P1-2_OEC-345-810_SRT-A
SingleAC123.08 %1798.0B2212.919.98
GD2ATSI
AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line
ATSI_P1-2_OEC-345-809_SRT-A
SingleAC117.76 %1798.0B2117.369.82
GD2AEP
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC138.82 %1868.0B2593.189.79
GD2AEP
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
AEP_P7-1_#11087___SRT-A-1
TowerAC101.08 %1868.0B1888.248.63
GD2AEP/ATSI
AG2-148 TP-02GALION 345.0 kV Ckt 1 line
ATSI_P7-1_TE-345-027A_SRT-A
TowerAC106.19 %1308.0B1388.999.06
GD2AEP/ATSI
AG2-148 TP-02GALION 345.0 kV Ckt 1 line
ATSI_P7-1_TE-345-030_SRT-A
TowerAC105.3 %1308.0B1377.338.87
GD2ATSI
AH1-690 TP-02BAY SH 345.0 kV Ckt 2 line
ATSI_P1-2_TE-345-606_SRT-A-1
SingleAC102.39 %1774.0B1816.367.71
GD2ATSI
AH1-690 TP-02BAY SH 345.0 kV Ckt 2 line
ATSI_P2-3_TE-345-002_SRT-SL
BreakerAC101.27 %1720.0B1741.779.87

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-007A_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-007A_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:130.62 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4870.98
MW Contribution:14.87
Bus #Bus NameTypeMW Contribution
270166AC1-044 GEN3
50/50
7.059
23559101PLEAS2
50/50
6.1
962761AG1-125 GEN
Solar/Wind Harmer
34.524
970149AG2-104 GEN
Solar/Wind Harmer
37.287
970155AG2-107 GEN
Solar/Wind Harmer
22.046
270349AD2-093_GEN
Solar/Wind Harmer
0.006
24721705FLATG2
Adder
23.918
270159DARBY CT4
Adder
10.243
970593AG2-378 GEN
Solar/Wind Harmer
1.812
270223U2-072_GEN1
Solar/Wind Harmer
0.001
253343AC1-166 GEN
Solar/Wind Harmer
0.003
253325AC1-069 GEN
Solar/Wind Harmer
0.012
270462AD2-086
Solar/Wind Harmer
0.017
971995AH1-542 GEN
Solar/Wind Harmer
2.906
270263AC1-001 GEN
Solar/Wind Harmer
0.786
270510AE1-227 GEN1
Solar/Wind Harmer
1.963
25326309TAIT D
Adder
1.196
241813AF1-122_GEN
Solar/Wind Harmer
3.405
960071AF2-298 GEN
Solar/Wind Harmer
3.786
253370AE2-315 SEC1
Adder
2.182
253371AE2-315 SEC2
Adder
2.063
927014AC1-188 GEN
Solar/Wind Harmer
0.005
246936BC-WTG1
Solar/Wind Harmer
0.305
270489AE1-102 GEN1
Solar/Wind Harmer
0.979
965421AG1-410 GEN
Solar/Wind Harmer
22.57
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.499
247521TR3_G114
Solar/Wind Harmer
0.273
270246TR4_N_V150
Solar/Wind Harmer
0.048
965011AG1-365 GEN
Solar/Wind Harmer
7.488
24695305TIMB G C
Solar/Wind Harmer
0.002
965651AG1-433 GEN
Solar/Wind Harmer
2.174
958861AF2-177 GEN
Solar/Wind Harmer
3.207
247536S-71 GEN
Solar/Wind Harmer
0.297
25194608D.CRK4
Adder
1.74
945371AF1-202 GEN
Solar/Wind Harmer
0.001
252507AC2-088 GEN
Solar/Wind Harmer
0.335
270063AE2-323 C
Solar/Wind Harmer
0.006
970245AG2-165 GEN
Solar/Wind Harmer
3.191
970947AG2-589 GEN
Solar/Wind Harmer
0.245
270005AE1-210 C O1
Solar/Wind Harmer
1.59
965031AG1-367 GEN
Solar/Wind Harmer
7.338
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.378
970825AG2-519 GEN
Solar/Wind Harmer
2.603
25196808ZIMRHP
Adder
79.729
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
944231AF1-091 GEN
Solar/Wind Harmer
1.953
24639705ELKHART HY
Adder
0.161
270032AE2-172
Solar/Wind Harmer
4.877
970291AG2-192 GEN
Solar/Wind Harmer
0.95
945111AF1-176 GEN
Solar/Wind Harmer
13.03
270505AE1-170 C O1
Solar/Wind Harmer
7.665
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.805
276903AD2-071 C
Solar/Wind Harmer
8.137
25196008MFTGT1
Adder
1.45
247522W1-056 GEN
Solar/Wind Harmer
0.001
970773AG2-487 GEN
Solar/Wind Harmer
1.284
970373AG2-245 GEN
Solar/Wind Harmer
15.247
270055AF2-134 C O1
Solar/Wind Harmer
0.006
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.41
970515AG2-329 GEN
Solar/Wind Harmer
18.805
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
9.032
24791305MDL-5G
Solar/Wind Harmer
0.001
970333AG2-219 GEN
Solar/Wind Harmer
5.139
274751CRETE EC ;1U
Adder
8.477
274754CRETE EC ;4U
Adder
8.477
274773LINCOLN ;4U
Adder
8.676
274774LINCOLN ;5U
Adder
8.676
274723RIVER EC ;12
Adder
18.418
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
5.139
24728605AND G2
Adder
3.927
276776AD2-060 GEN
Solar/Wind Harmer
0.746
945681AF1-233 GEN
Solar/Wind Harmer
13.461
274801UNIV PARK;4U
Adder
5.966
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
31.303
274732ELWOOD EC;7P
Adder
16.768
274674JOLIET 9 ;6U
Adder
15.704
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
963741AG1-226 GEN
Solar/Wind Harmer
16.815
274745AC1-111 GEN9
Adder
5.679
939401AE1-172 GEN
Solar/Wind Harmer
5.301
276691AA1-018 GEN1
Solar/Wind Harmer
0.858
970091AG2-072 GEN
Adder
77.629
276901AD2-066 C O1
Solar/Wind Harmer
0.007
316095T157 G97
Solar/Wind Helper
1.504
23583801GRNGAP
Solar/Wind Helper
5.601
238185AF2-356 C
Solar/Wind Helper
2.646
238108AE1-109 GEN1
Solar/Wind Helper
0.114
235054AD2-180 GEN
Solar/Wind Helper
2.03
235531U2-073 GEN
Solar/Wind Helper
3.282
238117U2-030
Solar/Wind Helper
0.341
238147AE2-230_GEN1
Solar/Wind Helper
0.495
238149AF1-291A_GEN
Solar/Wind Helper
0.141
962771AG1-126 GEN
Solar/Wind Harmer
34.524
972239AH1-704 GEN
Adder
2.689
270054AF2-122 C O1
Solar/Wind Harmer
0.007
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
5.077
270520AE2-214 GEN
Solar/Wind Harmer
0.013
270284AF1-227 GEN1
Solar/Wind Harmer
0.011
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
253383AE2-342_GEN
Solar/Wind Harmer
0.003
241973AD2-163_GEN1
Solar/Wind Harmer
0.006
945631AF1-228 GEN
Solar/Wind Harmer
0
943861AF1-054 GEN
Solar/Wind Harmer
3.127
943851AF1-053 GEN
Solar/Wind Harmer
2.166
270156DARBY CT1
Adder
10.409
270157DARBY CT2
Adder
10.383
270158DARBY CT3
Adder
10.218
970689AG2-444 GEN
Solar/Wind Harmer
16.436
270578AF1-285 GEN2
Solar/Wind Harmer
0.536
270432AC2-029 GEN
Solar/Wind Harmer
3.553
940611AE2-048 GEN
Solar/Wind Harmer
19.602
941391AE2-136 GEN
Solar/Wind Harmer
11.042
270302AB2-170 GEN
Solar/Wind Harmer
0.005
270317AD1-130_GEN
Solar/Wind Harmer
0.011
971653AH1-327 GEN
Solar/Wind Harmer
1.117
270269AC2-059
Solar/Wind Harmer
0.005
241972AD1-140 GEN
Solar/Wind Harmer
0.854
970179AG2-119 GEN
Solar/Wind Harmer
6.883
270340AC2-060 GEN
Solar/Wind Harmer
0.009
970879AG2-548 GEN
Solar/Wind Harmer
6.898
253372AE2-315 SEC3
Adder
2.063
253372AE2-315 SEC3
Adder
2.063
25306009OHH W.
Adder
3.13
253349AC2-067 GEN
Solar/Wind Harmer
2.381
253400AC2-068 GEN
Solar/Wind Harmer
0.958
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
0.953
965051AG1-369 GEN
Solar/Wind Harmer
3.739
965041AG1-368 GEN
Solar/Wind Harmer
7.471
247607V1-011 GEN
Solar/Wind Harmer
0.001
971567AH1-282 GEN
Solar/Wind Harmer
11.206
971989AH1-539 GEN
Solar/Wind Harmer
3.215
963791AG1-232 GEN
Solar/Wind Harmer
10.044
24729505KEY G4
Adder
6.919
270071AF1-092 GEN
Solar/Wind Harmer
14.245
971985AH1-537 GEN
Solar/Wind Harmer
2.206
270024AE2-089 GEN
Solar/Wind Harmer
0.008
270367AC2-061_GEN
Solar/Wind Harmer
0.006
965101AG1-375 GEN
Solar/Wind Harmer
7.401
971673AH1-337 GEN
Solar/Wind Harmer
4.804
252524AE2-267 GEN
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
9.344
25196308WSDLE2
Adder
9.263
25196208WSDLE1
Adder
9.24
25196708WSDLE6
Adder
9.217
25196508WSDLE4
Adder
8.984
971029AG2-637 GEN
Solar/Wind Harmer
11.085
270543AE2-219 C
Solar/Wind Harmer
0.004
945581AF1-223 GEN
Solar/Wind Harmer
0.001
270297AD1-101 GEN
Solar/Wind Harmer
0.002
971347AH1-153 GEN
Solar/Wind Harmer
11.025
971609AH1-304 GEN
Solar/Wind Harmer
1.2
270240V3-007_GEN2
Solar/Wind Harmer
0.002
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
970115AG2-085 GEN
Solar/Wind Harmer
2.932
270594AE1-207 GEN
Solar/Wind Harmer
8.194
970289AG2-191 GEN
Solar/Wind Harmer
1.389
971771AH1-392 GEN
Solar/Wind Harmer
7.306
971619AH1-309 GEN
Solar/Wind Harmer
3.285
971769AH1-391 GEN
Solar/Wind Harmer
8.134
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
25196108MFTGT2
Adder
1.599
25196108MFTGT2
Adder
1.484
270536AF1-215 GEN2
Solar/Wind Harmer
0.009
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
4.302
971549AH1-272 GEN
Solar/Wind Harmer
14.865
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
8.676
274776LINCOLN ;7U
Adder
8.676
274777LINCOLN ;8U
Adder
8.676
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
274814UNIV PK N;0U
Adder
5.184
274807UNIV PK N;3U
Adder
5.173
274805UNIV PK N;1U
Adder
5.15
274811UNIV PK N;7U
Adder
5.139
972037AH1-567 GEN1
Adder
0.187
960591AF2-350 GEN
Solar/Wind Harmer
7.141
274827FISK ;RP
Adder
7.941
972227AH1-698 GEN1
Adder
2.669
963841AG1-237 GEN
Solar/Wind Harmer
3.09
972163AH1-664 GEN
Solar/Wind Harmer
7.933
972165AH1-665 GEN
Solar/Wind Harmer
6.354
274687WILL CNTY;4U
Adder
28.523
274687WILL CNTY;4U
Adder
28.523
274675JOLIET 29;7U
Adder
31.303
274675JOLIET 29;7U
Adder
30.185
274731ELWOOD EC;2P
Adder
16.768
274733ELWOOD EC;3P
Adder
16.768
274735ELWOOD EC;4P
Adder
16.768
274728ELWOOD EC;5P
Adder
16.768
970833AG2-524 GEN
Solar/Wind Harmer
7.824
970833AG2-524 GEN
Solar/Wind Harmer
5.216
274746AC1-111 G10
Adder
5.679
274744AC1-111 GEN8
Adder
5.679
972203AH1-686 GEN
Adder
2.338
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
276868AE1-113 GEN
Solar/Wind Harmer
1.414
276882AE2-255 GEN
Solar/Wind Harmer
0.824
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238126S14_GEN_1
Solar/Wind Helper
0.827
238152AF2-075_GEN
Solar/Wind Helper
0.707
238208AF1-136 C
Solar/Wind Helper
0.22
23546401DTGZ2-030
Solar/Wind Helper
0.089
237085AD2-009_GEN
Solar/Wind Helper
1.649
3138216PACIFIC
Solar/Wind Helper
0.044
316411AF1-147_GEN1
Solar/Wind Helper
0.888
316415AF1-147_GEN2
Solar/Wind Helper
0.888
23750501ELLIOTTS
Solar/Wind Helper
0.638
959381AF2-229 GEN
Solar/Wind Helper
0.357
3141426STAFORD
Solar/Wind Helper
0.052
960921AF2-383 GEN
Solar/Wind Helper
0.364
205943AE1-185 GEN
Solar/Wind Helper
0.509
205932AD2-116_GEN
Solar/Wind Helper
0.509
205956AE1-196_GEN
Solar/Wind Helper
0.509
233935AB2-179 C
Solar/Wind Helper
1.269
232436AB1-176 C
Solar/Wind Helper
0.044
233923SMA
Solar/Wind Helper
0.958
233990AG1-397 GEN
Solar/Wind Helper
0.27
232432Z2-076 GEN
Solar/Wind Helper
0.067
234033AF1-007_GEN
Solar/Wind Helper
7.02
964001AG1-254 GEN
Solar/Wind Helper
0.955
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.115
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.08
203975AE1-071-GEN
Solar/Wind Helper
2.498
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.29
219620RIDERU C
Solar/Wind Helper
0.001
316164AC1-076 GEN
Solar/Wind Helper
1.096
20675528CPH_W2-050
Solar/Wind Helper
0.087
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
218524CNTRALGAS1 C
Solar/Wind Helper
0.16
966261AG1-495 GEN
Solar/Wind Helper
0.081
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20675928HOL_W4-097
Solar/Wind Helper
0.05
207484AF2-139 C O1
Solar/Wind Helper
0.084
20674828DL_W4-046
Solar/Wind Helper
0.008
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.136
20675128HRM_W1-127
Solar/Wind Helper
0.029
209116AE2-175 GEN
Solar/Wind Helper
1.778
24318805MLG1
50/50
10.095
23559001PLEAS1
50/50
6.1
270051AF1-062 GEN
50/50
11.821
270475AD2-096_GEN
50/50
7.141
970153AG2-106 GEN
Solar/Wind Harmer
22.046
961921AG1-034 GEN
Solar/Wind Harmer
7.615
241955AC1-078 GEN
Solar/Wind Harmer
0.007
24721905FLATG4
Adder
23.918
241974AD2-163_GEN2
Solar/Wind Harmer
0.006
942051AE2-217 GEN
Solar/Wind Harmer
14.671
970605AG2-385 GEN
Solar/Wind Harmer
4.899
270391AF1-285 GEN3
Solar/Wind Harmer
0.536
253338AC1-165 GEN
Solar/Wind Harmer
0.003
253333AC1-068 GEN
Solar/Wind Harmer
0.012
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270273AD2-016 GEN
Solar/Wind Harmer
0.821
972173AH1-669 GEN
Solar/Wind Harmer
3.952
270291AC1-194 GEN
Solar/Wind Harmer
6.106
253415AE1-040 GEN
Solar/Wind Harmer
0.003
270512AE1-227 GEN2
Solar/Wind Harmer
1.963
970065AG2-057 GEN
Solar/Wind Harmer
0.76
253370AE2-315 SEC1
Adder
2.182
253371AE2-315 SEC2
Adder
2.063
253406AD2-031_GEN
Solar/Wind Harmer
0.563
970191AG2-125 GEN
Solar/Wind Harmer
1.945
270491AE1-102 GEN2
Solar/Wind Harmer
0.979
270377AD1-106 GEN
Solar/Wind Harmer
2.855
971191AH1-055 GEN
Solar/Wind Harmer
19.26
253316AC1-085 GEN3
Solar/Wind Harmer
0.005
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
9.749
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.048
959331AF2-224 GEN
Solar/Wind Harmer
5.242
965021AG1-366 GEN
Solar/Wind Harmer
2.496
270588AE1-091_GEN
Solar/Wind Harmer
5.845
944531AF1-118 GEN
Solar/Wind Harmer
33.395
270043AE2-236 GEN
Solar/Wind Harmer
4.777
270258AD1-119 GEN
Solar/Wind Harmer
0.002
971617AH1-308 GEN
Solar/Wind Harmer
6.173
25196608WSDLE5
Adder
9.077
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
252510AF1-249 C
Solar/Wind Harmer
0.057
957741AF2-068 GEN
Solar/Wind Harmer
11.081
25194608D.CRK4
Adder
1.74
270222AC2-111 GEN
Solar/Wind Harmer
3.739
970031AG2-029 GEN
Solar/Wind Harmer
4.795
270404AC1-167 GEN
Solar/Wind Harmer
0.003
970513AG2-328 GEN
Solar/Wind Harmer
3.191
970517AG2-330 GEN
Solar/Wind Harmer
19.146
970349AG2-230 GEN
Solar/Wind Harmer
11.025
946031AF1-268 GEN
Solar/Wind Harmer
6.992
958821AF2-173 GEN
Solar/Wind Harmer
10.273
270004AE1-209 GEN
Solar/Wind Harmer
1.59
270437AC2-090 C
Solar/Wind Harmer
0.003
247643Z2-116 C
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.804
970291AG2-192 GEN
Solar/Wind Harmer
0.731
247642Z2-115 C
Solar/Wind Harmer
0.003
945111AF1-176 GEN
Solar/Wind Harmer
5.919
24642205MAYFLWER
Adder
0.665
25196008MFTGT1
Adder
1.405
270356AE2-297 GEN
Solar/Wind Harmer
0.01
24441205WTRV SLR C
Solar/Wind Harmer
0
247604X1-042
Adder
0.433
270535AF1-215 GEN1
Solar/Wind Harmer
0.009
964401AG1-302 GEN
Solar/Wind Harmer
0.001
970217AG2-149 GEN
Solar/Wind Harmer
6.268
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
7.196
970243AG2-164 GEN
Solar/Wind Harmer
4.205
970519AG2-331 GEN
Solar/Wind Harmer
18.687
970699AG2-449 GEN
Solar/Wind Harmer
1.797
274752CRETE EC ;2U
Adder
8.477
274753CRETE EC ;3U
Adder
8.477
958171AF2-111 GEN
Solar/Wind Harmer
17.94
274772LINCOLN ;3U
Adder
8.676
274724RIVER EC ;11
Adder
18.203
972167AH1-666 GEN
Solar/Wind Harmer
5.717
24728705AND G3
Adder
8.214
274802UNIV PARK;5U
Adder
5.97
24728505AND G1
Adder
3.927
276806AD2-047 C O1
Solar/Wind Harmer
4.047
970941AG2-585 GEN
Solar/Wind Harmer
8.927
274826FISK ;BP
Adder
11.205
274800UNIV PARK;3U
Adder
5.966
972038AH1-567 GEN2
Adder
0.373
972228AH1-698 GEN2
Adder
3.79
276897AD1-100 C
Solar/Wind Harmer
0.009
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
970707AG2-453 GEN
Solar/Wind Harmer
23.303
274676JOLIET 29;8U
Adder
30.185
276893AG1-478 C
Solar/Wind Harmer
0.282
274729ELWOOD EC;1P
Adder
16.768
274730ELWOOD EC;6P
Adder
16.768
274734ELWOOD EC;8P
Adder
16.768
274736ELWOOD EC;9P
Adder
16.768
943121AE2-341 GEN
Solar/Wind Harmer
11.888
943591AF1-030 GEN
Solar/Wind Harmer
7.906
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
270541AE2-072 C
Solar/Wind Harmer
0.009
274682WAUKEGAN ;7U
Adder
9.728
276805AD2-038 GEN
Solar/Wind Harmer
0.002
964991AG1-363 GEN
Solar/Wind Helper
5.136
316097T157 G90
Solar/Wind Helper
1.504
23750701CROSSCHOOL
Solar/Wind Helper
1.502
238118U2-030_1
Solar/Wind Helper
0.341
238127S14_GEN_2
Solar/Wind Helper
0.827
238148AE2-230_GEN2
Solar/Wind Helper
0.497
237080AD1-060 GEN
Solar/Wind Helper
0.342
237038AE2-054 C
Solar/Wind Helper
0.272
235062AE1-101 C1
Solar/Wind Helper
1.659
23779801AA1-109
Solar/Wind Helper
0.193
237048AF1-022 C
Solar/Wind Helper
0.177
223401AF1-299 GEN
Solar/Wind Helper
0.367
316006AB2-029 C
Solar/Wind Helper
0.117
966131AG1-482 GEN
Solar/Wind Helper
0.137
233930AB2-032 GEN
Solar/Wind Helper
0.381
233915AB1-141 GEN
Solar/Wind Helper
0.502
232422X3-066 FULL
Solar/Wind Helper
0.114
232428Y3-058 C
Solar/Wind Helper
0.338
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
23751201ROTHROCK
Solar/Wind Helper
0.824
237061AD1-155 GEN
Solar/Wind Helper
0.053
23562501BACKB
Solar/Wind Helper
1.007
238221AF1-254 C O1
Solar/Wind Helper
0.274
235067AD1-061 GEN
Solar/Wind Helper
0.496
270119AB2-067 GEN1
50/50
7.059
270120AB2-067 GEN2
50/50
7.059
24318905MLG2
50/50
7.071
270471AD2-092_GEN
Solar/Wind Harmer
0.006
942861AE2-305 GEN
Solar/Wind Harmer
6.335
970077AG2-063 GEN
Solar/Wind Harmer
4.631
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
938701AE1-092 GEN
Solar/Wind Harmer
12.917
971655AH1-328 GEN
Solar/Wind Harmer
2.854
964601AG1-323 GEN
Solar/Wind Harmer
3.215
964601AG1-323 GEN
Solar/Wind Harmer
2.143
270518AE2-148 GEN
Solar/Wind Harmer
0.691
972269AH1-719 GEN
Adder
2.584
972159AH1-661 GEN
Adder
1.118
253378AE2-206_GEN
Solar/Wind Harmer
0.004
276820AF1-078_GEN
Solar/Wind Harmer
0.002
970329AG2-216 GEN
Solar/Wind Harmer
3.354
971199AH1-059 GEN
Solar/Wind Harmer
3.09
241960AC2-195 GEN
Solar/Wind Harmer
0.006
25326509SID D
Adder
1.451
971073AG2-665 GEN
Solar/Wind Harmer
6.898
25326109MON D
Adder
1.443
25322209TAIT E
Adder
10.642
25322209TAIT E
Adder
10.403
971201AH1-060 GEN
Solar/Wind Harmer
1.52
253370AE2-315 SEC1
Adder
2.182
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
246938BC-WTG3
Solar/Wind Harmer
0.273
246937BC-WTG2
Solar/Wind Harmer
0.305
971231AH1-075 GEN
Solar/Wind Harmer
0.861
253317AC1-085 GEN4
Solar/Wind Harmer
0.005
970611AG2-400 GEN
Solar/Wind Harmer
7.488
970627AG2-408 GEN
Solar/Wind Harmer
2.246
270007AE1-245 C
Solar/Wind Harmer
0.002
962581AG1-107 GEN
Solar/Wind Harmer
0.002
25183208HLCRTG
Solar/Wind Harmer
0.012
944541AF1-119 GEN
Solar/Wind Harmer
0.497
960971AF2-388 GEN
Solar/Wind Harmer
4.347
970623AG2-406 GEN
Solar/Wind Harmer
1.356
942221AE2-234 GEN
Solar/Wind Harmer
0.037
252519AF1-045_GEN
Solar/Wind Harmer
6.44
252516AE2-318_GEN
Solar/Wind Harmer
5.712
247621Y3-024
Adder
0.255
970883AG2-550 GEN
Solar/Wind Harmer
7.389
970885AG2-551 GEN
Solar/Wind Harmer
2.463
270201AC2-176 GEN
Solar/Wind Harmer
0.001
25194408D.CRK1
Adder
8.004
25194508D.CRK3
Adder
1.496
970621AG2-405 GEN
Solar/Wind Harmer
1.351
964611AG1-324 GEN
Solar/Wind Harmer
0.553
252509AD1-136 GEN
Solar/Wind Harmer
0.037
970321AG2-212 GEN
Solar/Wind Harmer
3.191
270599AE1-208 GEN
Solar/Wind Harmer
6.737
270031AE2-169
Solar/Wind Harmer
4.042
270186AC1-089 GEN
Solar/Wind Harmer
0.004
270383AD1-128 GEN
Solar/Wind Harmer
0.004
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
970825AG2-519 GEN
Solar/Wind Harmer
8.127
247620Y3-023
Adder
0.484
960441AF2-335 GEN
Solar/Wind Harmer
7.33
270216AD2-079_GEN
Solar/Wind Harmer
0.001
971613AH1-306 GEN
Solar/Wind Harmer
3.512
24728805RICHG1
Adder
3.964
24728905RICHG2
Adder
3.964
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
14.589
961051AF2-396 GEN
Solar/Wind Harmer
9.726
270526AF1-158 GEN
Solar/Wind Harmer
0.009
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
9.095
965791AG1-447 GEN
Solar/Wind Harmer
6.67
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
970239AG2-162 GEN
Solar/Wind Harmer
1.797
274770LINCOLN ;1U
Adder
8.676
274771LINCOLN ;2U
Adder
8.676
966841AG1-555 GEN
Solar/Wind Harmer
0.81
274808UNIV PK N;4U
Adder
5.117
274803UNIV PARK;6U
Adder
5.97
274888KELLY CRK;1U
Solar/Wind Harmer
0.419
274887GEN-1.85
Solar/Wind Harmer
0.188
276843GEN-1.7
Solar/Wind Harmer
0.231
958011AF2-095 GEN
Solar/Wind Harmer
10.284
972259AH1-714 GEN
Adder
19.507
274674JOLIET 9 ;6U
Adder
15.704
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
970241AG2-163 GEN
Solar/Wind Harmer
4.144
958481AF2-142 GEN
Solar/Wind Harmer
10.621
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.958
971573AH1-285 GEN
Solar/Wind Harmer
1.319
274696ROCKY RD ;4P
Adder
11.537
274695ROCKY RD ;2P
Adder
11.271
274693ROCKY RD ;1P
Adder
11.16
274697ROCKY RD ;3P
Adder
3.062
958491AF2-143 GEN
Solar/Wind Harmer
10.588
274879MINONK ;1U
Solar/Wind Harmer
0.297
23585401KL_K28_T16
Solar/Wind Helper
1.482
238120AE2-309 GEN
Solar/Wind Helper
0.525
238175AF1-290_GEN
Solar/Wind Helper
0.153
238169AE2-226 GEN1
Solar/Wind Helper
0.701
238170AE2-226 GEN2
Solar/Wind Helper
0.701
235020AA1-095 C
Solar/Wind Helper
0.053
23777901MDS_W4-102
Solar/Wind Helper
0.177
237002AB1-128_GEN
Solar/Wind Helper
0.443
237034AC2-136 C
Solar/Wind Helper
0.227
235063AE1-101 C2
Solar/Wind Helper
1.659
237001AB1-127_GEN
Solar/Wind Helper
0.442
23777801MSM_W1-116
Solar/Wind Helper
0.114
237025AB1-124 C
Solar/Wind Helper
0.164
237006AB1-125 GEN
Solar/Wind Helper
0.123
226929AD2-058 GEN
Solar/Wind Helper
0.099
205916AD1-020 GEN
Solar/Wind Helper
1.713
20390526W1-045 C
Solar/Wind Helper
0.35
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
233987AB2-037 GEN
Solar/Wind Helper
2.342
233933AB2-153 GEN
Solar/Wind Helper
0.232
233944AB2-135 GEN
Solar/Wind Helper
0.588
232424Y1-079 C
Solar/Wind Helper
0.116
234036AF2-325 C
Solar/Wind Helper
0.042
233946AB2-136 GEN
Solar/Wind Helper
0.568
233901CHERRYDALE C
Solar/Wind Helper
0.232
232408W1-005 C
Solar/Wind Helper
0.507
232410W1-006 C
Solar/Wind Helper
0.507
233939AC1-091 C
Solar/Wind Helper
0.35
233970AC1-092 C
Solar/Wind Helper
0.35
315651AD1-115 GEN
Solar/Wind Helper
0.785
316447AC1-158 HLD
Solar/Wind Helper
2.845
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.04
219921AF1-264
Solar/Wind Helper
0.051
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.082
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.19
20716928W4-060COL
Solar/Wind Helper
0.051
218440SUMMTASSOC C
Solar/Wind Helper
0.016
20673828FLE_V3-070
Solar/Wind Helper
0.09
207442AE1-156 GEN
Solar/Wind Helper
0.326
20676128MHD_W3-029
Solar/Wind Helper
0.096
20671828STAW2-080
Solar/Wind Helper
0.027
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
207471AF2-354 C
Solar/Wind Helper
0.168
20674928WA_W3-044
Solar/Wind Helper
0.098
20676228FRD_X1-012
Solar/Wind Helper
0.092
964851AG1-348 GEN
Solar/Wind Helper
0.081
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.074
211065PSPA IPP
Solar/Wind Helper
0.151
211065PSPA IPP
Solar/Wind Helper
0.151
23751101LEADS_P59
Solar/Wind Helper
1.404
237030AB1-096 C
Solar/Wind Helper
0.071
3141196NOKESVL
Solar/Wind Helper
1.032
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.346
223402AF1-300 C
Solar/Wind Helper
0.367
205917AD1-020 ES
Solar/Wind Helper
0.368
233918AB1-142 GEN
Solar/Wind Helper
0.502
233982AB2-133 GEN
Solar/Wind Helper
0.358
233994AC2-023 GEN
Solar/Wind Helper
0.961
233996TM1833_GEN
Solar/Wind Helper
0.261
233997TMININ_4.2
Solar/Wind Helper
0.261
232406W1-004 FULL
Solar/Wind Helper
0.507
233940AF2-379 C
Solar/Wind Helper
0.062
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.232
233971AC1-093 C
Solar/Wind Helper
0.357
316044AC1-158 PL1
Solar/Wind Helper
1.293
316450AC1-158 RIC
Solar/Wind Helper
0.345
230430AE1-229_GEN
Solar/Wind Helper
3.372
230415AB2-049 C
Solar/Wind Helper
0.03
228729W2-030 C
Solar/Wind Helper
0.11
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.15
219291REEVESSOUT C
Solar/Wind Helper
0.011
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
219348LDSOLAR C
Solar/Wind Helper
0.114
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.063
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.353
219276PARKLANDSO C
Solar/Wind Helper
0.089
20714528FRN_Y2-051
Solar/Wind Helper
0.057
20720528MAN_W1-024
Solar/Wind Helper
0.028
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.027
219908AB1-139 C
Solar/Wind Helper
0.074
219249CENTRALDIV C
Solar/Wind Helper
0.01
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.089
971997AH1-543 GEN
Solar/Wind Harmer
2.724
233998TM1NIN_3.36
Solar/Wind Helper
0.261
232404W1-003 C
Solar/Wind Helper
0.507
232434Z2-077 GEN
Solar/Wind Helper
0.127
233954AC2-188 GEN
Solar/Wind Helper
0.232
233950AC2-186 GEN
Solar/Wind Helper
0.116
233972AC1-094 C
Solar/Wind Helper
0.302
316045AC1-158 PL2
Solar/Wind Helper
4.138
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.23
228728W1-130C
Solar/Wind Helper
0.054
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219904AC1-010 C
Solar/Wind Helper
0.06
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.131
20720728JCB_W1-129
Solar/Wind Helper
0.057
316254AC1-120 GEN1
Solar/Wind Helper
1.059
207445AB1-138_GEN
Solar/Wind Helper
0.104
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.13
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.31
20715228NPK_W1-113
Solar/Wind Helper
0.078
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.495
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
207437AD2-070 GEN
Solar/Wind Helper
0.138
207518AF1-320_GEN
Solar/Wind Helper
1.571
20671928W4-073
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.029
LAGNLTFEXP_LAGN->PJM
CLTF
14.837
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.802
TVALTFEXP_TVA->PJM
CLTF
7.293
CPLELTFEXP_CPLE->PJM
CLTF
0.624
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.816
NYPJM->LTFIMP_NY
CLTF
4.797
LGEELTFEXP_LGEE->PJM
CLTF
6.749
WECLTFEXP_WEC->PJM
CLTF
3.825
AG2-052LTFEXP_AG2-052->PJM
LTF
0.24
AH1-155LTFEXP_AH1-155->PJM
LTF
0.359
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.078
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.1
MECLTFEXP_MEC->PJM
CLTF
15.901
SIGELTFEXP_SIGE->PJM
CLTF
0.505

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-008A_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-008A_SRT-SL
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:124.1 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4627.6
MW Contribution:14.34
Bus #Bus NameTypeMW Contribution
24318805MLG1
50/50
9.842
23559001PLEAS1
50/50
5.385
270051AF1-062 GEN
50/50
11.434
970153AG2-106 GEN
Solar/Wind Harmer
21.245
972239AH1-704 GEN
50/50
2.78
962771AG1-126 GEN
Solar/Wind Harmer
33.269
270459AD2-067 GEN
Solar/Wind Harmer
0
270054AF2-122 C O1
Solar/Wind Harmer
0.007
961821AG1-024 GEN
Solar/Wind Harmer
4.91
270520AE2-214 GEN
Solar/Wind Harmer
0.013
270284AF1-227 GEN1
Solar/Wind Harmer
0.01
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
253383AE2-342_GEN
Solar/Wind Harmer
0.003
241973AD2-163_GEN1
Solar/Wind Harmer
0.006
945631AF1-228 GEN
Solar/Wind Harmer
0
943861AF1-054 GEN
Solar/Wind Harmer
3.02
943851AF1-053 GEN
Solar/Wind Harmer
2.092
270156DARBY CT1
Adder
10.05
270157DARBY CT2
Adder
10.026
270158DARBY CT3
Adder
9.866
270578AF1-285 GEN2
Solar/Wind Harmer
0.518
970689AG2-444 GEN
Solar/Wind Harmer
15.861
270432AC2-029 GEN
Solar/Wind Harmer
3.428
940611AE2-048 GEN
Solar/Wind Harmer
18.967
941391AE2-136 GEN
Solar/Wind Harmer
10.684
270302AB2-170 GEN
Solar/Wind Harmer
0.005
270317AD1-130_GEN
Solar/Wind Harmer
0.011
971653AH1-327 GEN
Solar/Wind Harmer
1.08
270269AC2-059
Solar/Wind Harmer
0.004
241972AD1-140 GEN
Solar/Wind Harmer
0.824
970179AG2-119 GEN
Solar/Wind Harmer
6.658
270340AC2-060 GEN
Solar/Wind Harmer
0.009
970879AG2-548 GEN
Solar/Wind Harmer
6.645
253372AE2-315 SEC3
Adder
1.989
253372AE2-315 SEC3
Adder
1.989
25306009OHH W.
Adder
3.018
253349AC2-067 GEN
Solar/Wind Harmer
2.296
253400AC2-068 GEN
Solar/Wind Harmer
0.923
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
0.92
965051AG1-369 GEN
Solar/Wind Harmer
3.609
971567AH1-282 GEN
Solar/Wind Harmer
10.843
247607V1-011 GEN
Solar/Wind Harmer
0.001
965041AG1-368 GEN
Solar/Wind Harmer
7.21
971989AH1-539 GEN
Solar/Wind Harmer
3.109
963791AG1-232 GEN
Solar/Wind Harmer
9.689
24729505KEY G4
Adder
6.671
270071AF1-092 GEN
Solar/Wind Harmer
13.737
270024AE2-089 GEN
Solar/Wind Harmer
0.008
971985AH1-537 GEN
Solar/Wind Harmer
2.123
270119AB2-067 GEN1
50/50
6.869
270120AB2-067 GEN2
50/50
6.869
24318905MLG2
50/50
6.89
270471AD2-092_GEN
Solar/Wind Harmer
0.006
942861AE2-305 GEN
Solar/Wind Harmer
6.118
970077AG2-063 GEN
Solar/Wind Harmer
4.471
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
938701AE1-092 GEN
Solar/Wind Harmer
12.484
971655AH1-328 GEN
Solar/Wind Harmer
2.758
964601AG1-323 GEN
Solar/Wind Harmer
3.106
964601AG1-323 GEN
Solar/Wind Harmer
2.071
270518AE2-148 GEN
Solar/Wind Harmer
0.667
972269AH1-719 GEN
Adder
2.501
972159AH1-661 GEN
Adder
1.082
253378AE2-206_GEN
Solar/Wind Harmer
0.004
276820AF1-078_GEN
Solar/Wind Harmer
0.002
970329AG2-216 GEN
Solar/Wind Harmer
3.237
971199AH1-059 GEN
Solar/Wind Harmer
2.99
241960AC2-195 GEN
Solar/Wind Harmer
0.006
970935AG2-582 GEN
Adder
242.403
25326509SID D
Adder
1.4
971073AG2-665 GEN
Solar/Wind Harmer
6.645
25326109MON D
Adder
1.391
971201AH1-060 GEN
Solar/Wind Harmer
1.471
25322209TAIT E
Adder
10.262
25322209TAIT E
Adder
10.031
253370AE2-315 SEC1
Adder
2.103
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
246938BC-WTG3
Solar/Wind Harmer
0.263
246937BC-WTG2
Solar/Wind Harmer
0.295
971231AH1-075 GEN
Solar/Wind Harmer
0.833
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
970611AG2-400 GEN
Solar/Wind Harmer
7.225
970627AG2-408 GEN
Solar/Wind Harmer
2.167
270007AE1-245 C
Solar/Wind Harmer
0.002
970623AG2-406 GEN
Solar/Wind Harmer
1.309
962581AG1-107 GEN
Solar/Wind Harmer
0.001
25183208HLCRTG
Solar/Wind Harmer
0.011
944541AF1-119 GEN
Solar/Wind Harmer
0.479
960971AF2-388 GEN
Solar/Wind Harmer
4.192
942221AE2-234 GEN
Solar/Wind Harmer
0.036
252519AF1-045_GEN
Solar/Wind Harmer
6.204
252516AE2-318_GEN
Solar/Wind Harmer
5.503
970621AG2-405 GEN
Solar/Wind Harmer
1.305
247621Y3-024
Adder
0.246
970883AG2-550 GEN
Solar/Wind Harmer
7.123
970885AG2-551 GEN
Solar/Wind Harmer
2.374
270201AC2-176 GEN
Solar/Wind Harmer
0.001
25194408D.CRK1
Adder
7.711
25194508D.CRK3
Adder
1.442
964611AG1-324 GEN
Solar/Wind Harmer
0.534
252509AD1-136 GEN
Solar/Wind Harmer
0.036
970321AG2-212 GEN
Solar/Wind Harmer
3.076
270599AE1-208 GEN
Solar/Wind Harmer
6.495
270031AE2-169
Solar/Wind Harmer
3.897
270383AD1-128 GEN
Solar/Wind Harmer
0.004
270186AC1-089 GEN
Solar/Wind Harmer
0.004
247620Y3-023
Adder
0.466
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
970825AG2-519 GEN
Solar/Wind Harmer
7.834
960441AF2-335 GEN
Solar/Wind Harmer
7.065
270216AD2-079_GEN
Solar/Wind Harmer
0.001
971613AH1-306 GEN
Solar/Wind Harmer
3.385
24728805RICHG1
Adder
3.82
24728905RICHG2
Adder
3.82
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
14.072
961051AF2-396 GEN
Solar/Wind Harmer
9.381
270526AF1-158 GEN
Solar/Wind Harmer
0.009
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
8.77
965791AG1-447 GEN
Solar/Wind Harmer
6.431
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
970239AG2-162 GEN
Solar/Wind Harmer
1.73
274770LINCOLN ;1U
Adder
8.364
274771LINCOLN ;2U
Adder
8.364
274808UNIV PK N;4U
Adder
4.933
966841AG1-555 GEN
Solar/Wind Harmer
0.781
274803UNIV PARK;6U
Adder
5.755
274888KELLY CRK;1U
Solar/Wind Harmer
0.404
274887GEN-1.85
Solar/Wind Harmer
0.181
276843GEN-1.7
Solar/Wind Harmer
0.223
958011AF2-095 GEN
Solar/Wind Harmer
9.913
972259AH1-714 GEN
Adder
18.805
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
970241AG2-163 GEN
Solar/Wind Harmer
3.993
958481AF2-142 GEN
Solar/Wind Harmer
10.238
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.923
971573AH1-285 GEN
Solar/Wind Harmer
1.271
971677AH1-339 GEN
Solar/Wind Harmer
0.768
958491AF2-143 GEN
Solar/Wind Harmer
10.205
274879MINONK ;1U
Solar/Wind Harmer
0.287
238175AF1-290_GEN
Solar/Wind Helper
0.148
238169AE2-226 GEN1
Solar/Wind Helper
0.677
238170AE2-226 GEN2
Solar/Wind Helper
0.677
238120AE2-309 GEN
Solar/Wind Helper
0.487
235020AA1-095 C
Solar/Wind Helper
0.051
23777901MDS_W4-102
Solar/Wind Helper
0.171
23585401KL_K28_T16
Solar/Wind Helper
1.328
237034AC2-136 C
Solar/Wind Helper
0.219
237002AB1-128_GEN
Solar/Wind Helper
0.427
235063AE1-101 C2
Solar/Wind Helper
1.6
237001AB1-127_GEN
Solar/Wind Helper
0.426
23777801MSM_W1-116
Solar/Wind Helper
0.11
237025AB1-124 C
Solar/Wind Helper
0.159
237006AB1-125 GEN
Solar/Wind Helper
0.119
226929AD2-058 GEN
Solar/Wind Helper
0.096
205916AD1-020 GEN
Solar/Wind Helper
1.656
20390526W1-045 C
Solar/Wind Helper
0.338
208835TUHI V3-051
Solar/Wind Helper
0.023
208835TUHI V3-051
Solar/Wind Helper
0.023
233987AB2-037 GEN
Solar/Wind Helper
2.264
233933AB2-153 GEN
Solar/Wind Helper
0.225
232424Y1-079 C
Solar/Wind Helper
0.112
233944AB2-135 GEN
Solar/Wind Helper
0.569
233946AB2-136 GEN
Solar/Wind Helper
0.549
234036AF2-325 C
Solar/Wind Helper
0.041
233901CHERRYDALE C
Solar/Wind Helper
0.225
270166AC1-044 GEN3
50/50
6.869
23559101PLEAS2
50/50
5.385
270122AB2-093 CT
50/50
3.689
962761AG1-125 GEN
Solar/Wind Harmer
33.269
970149AG2-104 GEN
Solar/Wind Harmer
35.932
970155AG2-107 GEN
Solar/Wind Harmer
21.245
270349AD2-093_GEN
Solar/Wind Harmer
0.006
24721705FLATG2
Adder
22.865
270159DARBY CT4
Adder
9.89
970593AG2-378 GEN
Solar/Wind Harmer
1.75
270223U2-072_GEN1
Solar/Wind Harmer
0.001
253343AC1-166 GEN
Solar/Wind Harmer
0.003
253325AC1-069 GEN
Solar/Wind Harmer
0.012
270462AD2-086
Solar/Wind Harmer
0.016
971995AH1-542 GEN
Solar/Wind Harmer
2.81
270263AC1-001 GEN
Solar/Wind Harmer
0.758
270510AE1-227 GEN1
Solar/Wind Harmer
1.904
241813AF1-122_GEN
Solar/Wind Harmer
3.294
25326309TAIT D
Adder
1.153
960071AF2-298 GEN
Solar/Wind Harmer
3.651
253370AE2-315 SEC1
Adder
2.103
253371AE2-315 SEC2
Adder
1.989
927014AC1-188 GEN
Solar/Wind Harmer
0.004
246936BC-WTG1
Solar/Wind Harmer
0.295
270489AE1-102 GEN1
Solar/Wind Harmer
0.945
965421AG1-410 GEN
Solar/Wind Harmer
21.788
247521TR3_G114
Solar/Wind Harmer
0.263
270246TR4_N_V150
Solar/Wind Harmer
0.047
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.226
965011AG1-365 GEN
Solar/Wind Harmer
7.225
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
24695305TIMB G C
Solar/Wind Harmer
0.002
965651AG1-433 GEN
Solar/Wind Harmer
2.096
958861AF2-177 GEN
Solar/Wind Harmer
3.092
247536S-71 GEN
Solar/Wind Harmer
0.287
945371AF1-202 GEN
Solar/Wind Harmer
0.001
25194608D.CRK4
Adder
1.676
270063AE2-323 C
Solar/Wind Harmer
0.006
252507AC2-088 GEN
Solar/Wind Harmer
0.323
970245AG2-165 GEN
Solar/Wind Harmer
3.076
944231AF1-091 GEN
Solar/Wind Harmer
1.885
270005AE1-210 C O1
Solar/Wind Harmer
1.532
965031AG1-367 GEN
Solar/Wind Harmer
7.073
970947AG2-589 GEN
Solar/Wind Harmer
0.236
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.183
970825AG2-519 GEN
Solar/Wind Harmer
2.509
24639705ELKHART HY
Adder
0.155
25196808ZIMRHP
Adder
76.799
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
270032AE2-172
Solar/Wind Harmer
4.701
970291AG2-192 GEN
Solar/Wind Harmer
0.916
945111AF1-176 GEN
Solar/Wind Harmer
12.568
270505AE1-170 C O1
Solar/Wind Harmer
7.393
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.67
247522W1-056 GEN
Solar/Wind Harmer
0.001
276903AD2-071 C
Solar/Wind Harmer
7.842
25196008MFTGT1
Adder
1.397
970773AG2-487 GEN
Solar/Wind Harmer
1.237
970373AG2-245 GEN
Solar/Wind Harmer
14.699
970515AG2-329 GEN
Solar/Wind Harmer
18.197
270055AF2-134 C O1
Solar/Wind Harmer
0.005
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.071
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.706
24791305MDL-5G
Solar/Wind Harmer
0.001
970333AG2-219 GEN
Solar/Wind Harmer
4.947
274751CRETE EC ;1U
Adder
8.172
274754CRETE EC ;4U
Adder
8.172
274773LINCOLN ;4U
Adder
8.364
274774LINCOLN ;5U
Adder
8.364
274723RIVER EC ;12
Adder
17.756
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.954
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
276776AD2-060 GEN
Solar/Wind Harmer
0.719
24728605AND G2
Adder
3.784
274801UNIV PARK;4U
Adder
5.751
941551AE2-152 GEN
Solar/Wind Harmer
0.001
945681AF1-233 GEN
Solar/Wind Harmer
12.962
274676JOLIET 29;8U
Adder
30.175
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
963741AG1-226 GEN
Solar/Wind Harmer
16.202
939401AE1-172 GEN
Solar/Wind Harmer
5.109
276691AA1-018 GEN1
Solar/Wind Harmer
0.827
276901AD2-066 C O1
Solar/Wind Harmer
0.007
316095T157 G97
Solar/Wind Helper
1.455
23583801GRNGAP
Solar/Wind Helper
5.418
238108AE1-109 GEN1
Solar/Wind Helper
0.106
238185AF2-356 C
Solar/Wind Helper
2.425
238147AE2-230_GEN1
Solar/Wind Helper
0.478
238149AF1-291A_GEN
Solar/Wind Helper
0.137
235531U2-073 GEN
Solar/Wind Helper
3.034
235054AD2-180 GEN
Solar/Wind Helper
1.839
237061AD1-155 GEN
Solar/Wind Helper
0.051
238117U2-030
Solar/Wind Helper
0.314
238221AF1-254 C O1
Solar/Wind Helper
0.265
235067AD1-061 GEN
Solar/Wind Helper
0.478
237030AB1-096 C
Solar/Wind Helper
0.068
3141196NOKESVL
Solar/Wind Helper
0.999
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.335
223402AF1-300 C
Solar/Wind Helper
0.355
23751201ROTHROCK
Solar/Wind Helper
0.694
23562501BACKB
Solar/Wind Helper
0.842
205917AD1-020 ES
Solar/Wind Helper
0.356
233982AB2-133 GEN
Solar/Wind Helper
0.346
233918AB1-142 GEN
Solar/Wind Helper
0.486
233994AC2-023 GEN
Solar/Wind Helper
0.929
233996TM1833_GEN
Solar/Wind Helper
0.253
233997TMININ_4.2
Solar/Wind Helper
0.253
232406W1-004 FULL
Solar/Wind Helper
0.49
233940AF2-379 C
Solar/Wind Helper
0.06
234015AF2-250 C
Solar/Wind Helper
0.037
233952AC2-187 GEN
Solar/Wind Helper
0.225
233971AC1-093 C
Solar/Wind Helper
0.346
316044AC1-158 PL1
Solar/Wind Helper
1.252
316450AC1-158 RIC
Solar/Wind Helper
0.334
230430AE1-229_GEN
Solar/Wind Helper
3.26
230415AB2-049 C
Solar/Wind Helper
0.029
228729W2-030 C
Solar/Wind Helper
0.107
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.053
219912AD2-042 GEN
Solar/Wind Helper
0.145
219291REEVESSOUT C
Solar/Wind Helper
0.011
961921AG1-034 GEN
Solar/Wind Harmer
7.364
241955AC1-078 GEN
Solar/Wind Harmer
0.007
241974AD2-163_GEN2
Solar/Wind Harmer
0.006
942051AE2-217 GEN
Solar/Wind Harmer
14.169
24721905FLATG4
Adder
22.865
970605AG2-385 GEN
Solar/Wind Harmer
4.731
965101AG1-375 GEN
Solar/Wind Harmer
7.135
270297AD1-101 GEN
Solar/Wind Harmer
0.002
270367AC2-061_GEN
Solar/Wind Harmer
0.006
971673AH1-337 GEN
Solar/Wind Harmer
4.631
971029AG2-637 GEN
Solar/Wind Harmer
10.686
270543AE2-219 C
Solar/Wind Harmer
0.004
252524AE2-267 GEN
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
9.002
25196308WSDLE2
Adder
8.924
25196208WSDLE1
Adder
8.902
25196708WSDLE6
Adder
8.879
25196508WSDLE4
Adder
8.656
945581AF1-223 GEN
Solar/Wind Harmer
0.001
971347AH1-153 GEN
Solar/Wind Harmer
10.632
971609AH1-304 GEN
Solar/Wind Harmer
1.157
270240V3-007_GEN2
Solar/Wind Harmer
0.002
970115AG2-085 GEN
Solar/Wind Harmer
2.826
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
270594AE1-207 GEN
Solar/Wind Harmer
7.898
971771AH1-392 GEN
Solar/Wind Harmer
7.046
970289AG2-191 GEN
Solar/Wind Harmer
1.339
971619AH1-309 GEN
Solar/Wind Harmer
3.169
971769AH1-391 GEN
Solar/Wind Harmer
7.844
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
25196108MFTGT2
Adder
1.54
25196108MFTGT2
Adder
1.43
270536AF1-215 GEN2
Solar/Wind Harmer
0.009
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
4.146
971549AH1-272 GEN
Solar/Wind Harmer
14.344
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
8.364
274776LINCOLN ;7U
Adder
8.364
274777LINCOLN ;8U
Adder
8.364
274814UNIV PK N;0U
Adder
4.998
274807UNIV PK N;3U
Adder
4.987
274805UNIV PK N;1U
Adder
4.965
274811UNIV PK N;7U
Adder
4.954
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
972037AH1-567 GEN1
Adder
0.181
960591AF2-350 GEN
Solar/Wind Harmer
6.884
274827FISK ;RP
Adder
7.655
972227AH1-698 GEN1
Adder
2.573
963841AG1-237 GEN
Solar/Wind Harmer
2.978
274687WILL CNTY;4U
Adder
27.495
274687WILL CNTY;4U
Adder
27.495
274675JOLIET 29;7U
Adder
30.175
274675JOLIET 29;7U
Adder
29.097
972163AH1-664 GEN
Solar/Wind Harmer
7.639
972165AH1-665 GEN
Solar/Wind Harmer
6.118
274731ELWOOD EC;2P
Adder
16.163
274733ELWOOD EC;3P
Adder
16.163
274735ELWOOD EC;4P
Adder
16.163
270391AF1-285 GEN3
Solar/Wind Harmer
0.518
253338AC1-165 GEN
Solar/Wind Harmer
0.003
253333AC1-068 GEN
Solar/Wind Harmer
0.012
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270273AD2-016 GEN
Solar/Wind Harmer
0.792
972173AH1-669 GEN
Solar/Wind Harmer
3.811
270512AE1-227 GEN2
Solar/Wind Harmer
1.904
270291AC1-194 GEN
Solar/Wind Harmer
5.884
253415AE1-040 GEN
Solar/Wind Harmer
0.003
970065AG2-057 GEN
Solar/Wind Harmer
0.735
253370AE2-315 SEC1
Adder
2.103
253371AE2-315 SEC2
Adder
1.989
970191AG2-125 GEN
Solar/Wind Harmer
1.876
253406AD2-031_GEN
Solar/Wind Harmer
0.543
274728ELWOOD EC;5P
Adder
16.163
970833AG2-524 GEN
Solar/Wind Harmer
7.542
970833AG2-524 GEN
Solar/Wind Harmer
5.028
945641AF1-229 GEN
Solar/Wind Harmer
0.001
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
276868AE1-113 GEN
Solar/Wind Harmer
1.363
276882AE2-255 GEN
Solar/Wind Harmer
0.794
238109AE1-109 GEN2
Solar/Wind Helper
0.106
238110AE1-109 GEN3
Solar/Wind Helper
0.106
238152AF2-075_GEN
Solar/Wind Helper
0.683
23546401DTGZ2-030
Solar/Wind Helper
0.086
238208AF1-136 C
Solar/Wind Helper
0.211
238126S14_GEN_1
Solar/Wind Helper
0.766
237085AD2-009_GEN
Solar/Wind Helper
1.588
3138216PACIFIC
Solar/Wind Helper
0.043
316411AF1-147_GEN1
Solar/Wind Helper
0.86
316415AF1-147_GEN2
Solar/Wind Helper
0.86
959381AF2-229 GEN
Solar/Wind Helper
0.345
23750501ELLIOTTS
Solar/Wind Helper
0.571
3141426STAFORD
Solar/Wind Helper
0.051
960921AF2-383 GEN
Solar/Wind Helper
0.352
205943AE1-185 GEN
Solar/Wind Helper
0.492
205956AE1-196_GEN
Solar/Wind Helper
0.492
205932AD2-116_GEN
Solar/Wind Helper
0.492
233935AB2-179 C
Solar/Wind Helper
1.227
232436AB1-176 C
Solar/Wind Helper
0.043
233923SMA
Solar/Wind Helper
0.927
233990AG1-397 GEN
Solar/Wind Helper
0.261
234033AF1-007_GEN
Solar/Wind Helper
6.787
232432Z2-076 GEN
Solar/Wind Helper
0.065
964001AG1-254 GEN
Solar/Wind Helper
0.924
228754AB1-001 C
Solar/Wind Helper
0.025
227927V4-067C
Solar/Wind Helper
0.01
219914AD2-027 C
Solar/Wind Helper
0.111
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.038
219607WPEMNERT C
Solar/Wind Helper
0.077
214067T20SOLAR
Solar/Wind Helper
0.011
203975AE1-071-GEN
Solar/Wind Helper
2.41
20715728PEM_W1-119
Solar/Wind Helper
0.093
20715828PEM_W1-120
Solar/Wind Helper
0.093
207459AE1-142 C O1
Solar/Wind Helper
0.28
316164AC1-076 GEN
Solar/Wind Helper
1.062
219620RIDERU C
Solar/Wind Helper
0.001
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.111
316170AC1-121 GEN2
Solar/Wind Helper
0.342
959561AF2-247 GEN
Solar/Wind Helper
0.02
20720828JCB_W4-025
Solar/Wind Helper
0.061
20716028EGP_W2-019
Solar/Wind Helper
0.018
20715028HAN_X4-015
Solar/Wind Helper
0.055
219276PARKLANDSO C
Solar/Wind Helper
0.086
20714528FRN_Y2-051
Solar/Wind Helper
0.055
20720528MAN_W1-024
Solar/Wind Helper
0.027
971997AH1-543 GEN
Solar/Wind Harmer
1.86
270491AE1-102 GEN2
Solar/Wind Harmer
0.945
270377AD1-106 GEN
Solar/Wind Harmer
2.761
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.047
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
9.394
959331AF2-224 GEN
Solar/Wind Harmer
5.057
965021AG1-366 GEN
Solar/Wind Harmer
2.408
270588AE1-091_GEN
Solar/Wind Harmer
5.649
971191AH1-055 GEN
Solar/Wind Harmer
18.515
944531AF1-118 GEN
Solar/Wind Harmer
32.203
270043AE2-236 GEN
Solar/Wind Harmer
4.607
270258AD1-119 GEN
Solar/Wind Harmer
0.002
971617AH1-308 GEN
Solar/Wind Harmer
5.953
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
10.684
270404AC1-167 GEN
Solar/Wind Harmer
0.003
25196608WSDLE5
Adder
8.745
252510AF1-249 C
Solar/Wind Harmer
0.055
970031AG2-029 GEN
Solar/Wind Harmer
4.625
25194608D.CRK4
Adder
1.676
270222AC2-111 GEN
Solar/Wind Harmer
3.603
970513AG2-328 GEN
Solar/Wind Harmer
3.076
970517AG2-330 GEN
Solar/Wind Harmer
18.457
970349AG2-230 GEN
Solar/Wind Harmer
10.632
946031AF1-268 GEN
Solar/Wind Harmer
6.74
958821AF2-173 GEN
Solar/Wind Harmer
9.902
270004AE1-209 GEN
Solar/Wind Harmer
1.532
270437AC2-090 C
Solar/Wind Harmer
0.003
247643Z2-116 C
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.775
970291AG2-192 GEN
Solar/Wind Harmer
0.705
945111AF1-176 GEN
Solar/Wind Harmer
5.709
247642Z2-115 C
Solar/Wind Harmer
0.003
24642205MAYFLWER
Adder
0.641
24441205WTRV SLR C
Solar/Wind Harmer
0
25196008MFTGT1
Adder
1.353
270356AE2-297 GEN
Solar/Wind Harmer
0.009
970217AG2-149 GEN
Solar/Wind Harmer
6.066
247604X1-042
Adder
0.418
270535AF1-215 GEN1
Solar/Wind Harmer
0.009
964401AG1-302 GEN
Solar/Wind Harmer
0.001
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.935
970243AG2-164 GEN
Solar/Wind Harmer
4.047
970519AG2-331 GEN
Solar/Wind Harmer
17.988
970699AG2-449 GEN
Solar/Wind Harmer
1.73
274752CRETE EC ;2U
Adder
8.172
274753CRETE EC ;3U
Adder
8.172
274772LINCOLN ;3U
Adder
8.364
274724RIVER EC ;11
Adder
17.549
958171AF2-111 GEN
Solar/Wind Harmer
17.278
274802UNIV PARK;5U
Adder
5.755
276806AD2-047 C O1
Solar/Wind Harmer
3.901
970941AG2-585 GEN
Solar/Wind Harmer
8.605
274826FISK ;BP
Adder
10.802
24728705AND G3
Adder
7.914
24728505AND G1
Adder
3.784
274800UNIV PARK;3U
Adder
5.751
972038AH1-567 GEN2
Adder
0.36
972228AH1-698 GEN2
Adder
3.654
972167AH1-666 GEN
Solar/Wind Harmer
5.505
276897AD1-100 C
Solar/Wind Harmer
0.009
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
22.464
274676JOLIET 29;8U
Adder
29.097
274729ELWOOD EC;1P
Adder
16.163
274730ELWOOD EC;6P
Adder
13.491
276893AG1-478 C
Solar/Wind Harmer
0.272
270541AE2-072 C
Solar/Wind Harmer
0.009
943121AE2-341 GEN
Solar/Wind Harmer
11.459
943591AF1-030 GEN
Solar/Wind Harmer
7.62
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
276805AD2-038 GEN
Solar/Wind Harmer
0.002
964991AG1-363 GEN
Solar/Wind Helper
4.969
316097T157 G90
Solar/Wind Helper
1.455
23750701CROSSCHOOL
Solar/Wind Helper
1.397
238148AE2-230_GEN2
Solar/Wind Helper
0.48
238127S14_GEN_2
Solar/Wind Helper
0.766
238118U2-030_1
Solar/Wind Helper
0.314
237080AD1-060 GEN
Solar/Wind Helper
0.33
237038AE2-054 C
Solar/Wind Helper
0.262
235062AE1-101 C1
Solar/Wind Helper
1.6
23779801AA1-109
Solar/Wind Helper
0.187
223401AF1-299 GEN
Solar/Wind Helper
0.355
316006AB2-029 C
Solar/Wind Helper
0.113
966131AG1-482 GEN
Solar/Wind Helper
0.132
237048AF1-022 C
Solar/Wind Helper
0.159
233930AB2-032 GEN
Solar/Wind Helper
0.368
233915AB1-141 GEN
Solar/Wind Helper
0.486
232422X3-066 FULL
Solar/Wind Helper
0.11
232426Y1-080 FULL
Solar/Wind Helper
0.038
233964AF2-378 GEN
Solar/Wind Helper
0.04
233998TM1NIN_3.36
Solar/Wind Helper
0.253
232404W1-003 C
Solar/Wind Helper
0.49
232428Y3-058 C
Solar/Wind Helper
0.327
232434Z2-077 GEN
Solar/Wind Helper
0.123
233954AC2-188 GEN
Solar/Wind Helper
0.225
233950AC2-186 GEN
Solar/Wind Helper
0.112
233972AC1-094 C
Solar/Wind Helper
0.292
316045AC1-158 PL2
Solar/Wind Helper
4.009
230511AF1-262
Solar/Wind Helper
0.014
230434AG1-499 GEN
Solar/Wind Helper
0.222
228728W1-130C
Solar/Wind Helper
0.052
219258KINSLEYDEP C
Solar/Wind Helper
0.074
219904AC1-010 C
Solar/Wind Helper
0.058
218660EHAMPSOLAR C
Solar/Wind Helper
0.032
219907AC1-030 C
Solar/Wind Helper
0.033
219686LUMSOLAR_N C
Solar/Wind Helper
0.038
219304NAMERICA C
Solar/Wind Helper
0.127
316254AC1-120 GEN1
Solar/Wind Helper
1.026
20720728JCB_W1-129
Solar/Wind Helper
0.055
207445AB1-138_GEN
Solar/Wind Helper
0.101
963711AG1-223 GEN
Solar/Wind Helper
0.062
20714828MDF_W3-079
Solar/Wind Helper
0.126
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.299
20715228NPK_W1-113
Solar/Wind Helper
0.075
232408W1-005 C
Solar/Wind Helper
0.49
232410W1-006 C
Solar/Wind Helper
0.49
233939AC1-091 C
Solar/Wind Helper
0.338
233970AC1-092 C
Solar/Wind Helper
0.338
315651AD1-115 GEN
Solar/Wind Helper
0.76
316447AC1-158 HLD
Solar/Wind Helper
2.756
230433AD2-135 GEN
Solar/Wind Helper
0.016
230407AD2-065 C
Solar/Wind Helper
0.039
219921AF1-264
Solar/Wind Helper
0.049
219615MILLCREEK C
Solar/Wind Helper
0.026
963401AG1-189 GEN
Solar/Wind Helper
0.054
963391AG1-188 GEN
Solar/Wind Helper
0.079
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.183
LAGNLTFEXP_LAGN->PJM
CLTF
14.268
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.432
TVALTFEXP_TVA->PJM
CLTF
7.011
CPLELTFEXP_CPLE->PJM
CLTF
0.567
CBM West 2LTFEXP_CBM-W2->PJM
CBM
108.576
NYPJM->LTFIMP_NY
CLTF
4.628
LGEELTFEXP_LGEE->PJM
CLTF
6.497
WECLTFEXP_WEC->PJM
CLTF
3.686
AG2-052LTFEXP_AG2-052->PJM
LTF
0.231
AH1-155LTFEXP_AH1-155->PJM
LTF
0.346
CBM West 1LTFEXP_CBM-W1->PJM
CBM
137.982
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.984
MECLTFEXP_MEC->PJM
CLTF
15.319
SIGELTFEXP_SIGE->PJM
CLTF
0.486

Details for 02BAY SH-02DAV-BE 345.0 kV Ckt 1 line l/o ATSI_P2-3_TE-345-008B_SRT-SL


Base Case Flowgate

Area:ATSI
Facility Description:
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_TE-345-008B_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:168.3 %
Rating:1683.0 MVA
Rating Type:B
MVA to Mitigate:2832.52
MW Contribution:14.99
Bus #Bus NameTypeMW Contribution
23929302BS-PKR
50/50
2.743
241832AE2-181_GEN
Solar/Wind Harmer
1.964
958321AF2-126 GEN
Solar/Wind Harmer
1.44
23906502RICHG2&3
Adder
1.317
270541AE2-072 C
Solar/Wind Harmer
4.336
270575GUS2 35KV
Solar/Wind Harmer
9.524
970217AG2-149 GEN
Solar/Wind Harmer
24.156
247604X1-042
Adder
0.294
270044AE2-322 C
Solar/Wind Harmer
0.914
270404AC1-167 GEN
Solar/Wind Harmer
0.761
24441205WTRV SLR C
Solar/Wind Harmer
0.093
270258AD1-119 GEN
Solar/Wind Harmer
1.873
270491AE1-102 GEN2
Solar/Wind Harmer
0.837
945111AF1-176 GEN
Solar/Wind Harmer
3.628
958091AF2-103 GEN
Solar/Wind Harmer
0.103
270588AE1-091_GEN
Solar/Wind Harmer
7.012
24642205MAYFLWER
Adder
0.396
247643Z2-116 C
Solar/Wind Harmer
0.043
970031AG2-029 GEN
Solar/Wind Harmer
18.318
270191TR4_S_V150
Solar/Wind Harmer
1.803
270247TR4_N_V136
Solar/Wind Harmer
0.511
959331AF2-224 GEN
Solar/Wind Harmer
5.881
965021AG1-366 GEN
Solar/Wind Harmer
1.368
270485AE1-090_GEN
Solar/Wind Harmer
0.345
970349AG2-230 GEN
Solar/Wind Harmer
8.492
270043AE2-236 GEN
Solar/Wind Harmer
3.088
270535AF1-215 GEN1
Solar/Wind Harmer
2.437
942871AE2-306 GEN
Solar/Wind Harmer
0.48
270391AF1-285 GEN3
Solar/Wind Harmer
0.246
972231SS25-0005
Solar/Wind Harmer
5.018
972181SS23-001
Solar/Wind Harmer
3.136
274752CRETE EC ;2U
Adder
2.584
274753CRETE EC ;3U
Adder
2.584
964401AG1-302 GEN
Solar/Wind Harmer
4.779
274724RIVER EC ;11
Adder
9.288
959141AF2-205 GEN
Solar/Wind Harmer
3.132
274802UNIV PARK;5U
Adder
3.011
274826FISK ;BP
Adder
5.644
274800UNIV PARK;3U
Adder
3.001
972038AH1-567 GEN2
Adder
0.188
276772AC2-154 GEN
Solar/Wind Harmer
1.433
276806AD2-047 C O1
Solar/Wind Harmer
5.498
970941AG2-585 GEN
Solar/Wind Harmer
6.424
274772LINCOLN ;3U
Adder
3.184
972228AH1-698 GEN2
Adder
1.898
24190002OREGON_ST1
50/50
5.505
24189802OREGON_CT1
50/50
4.176
23888802TROY G4
50/50
1.502
241996AE2-282_GEN
Solar/Wind Harmer
2.202
971677AH1-339 GEN
Solar/Wind Harmer
6.538
961051AF2-396 GEN
Solar/Wind Harmer
10.337
961051AF2-396 GEN
Solar/Wind Harmer
4.808
246938BC-WTG3
Solar/Wind Harmer
2.563
246937BC-WTG2
Solar/Wind Harmer
2.519
960981AF2-389 GEN
Solar/Wind Harmer
0.966
957891AF2-083 GEN
Solar/Wind Harmer
2.156
270007AE1-245 C
Solar/Wind Harmer
3.789
942801AE2-298 GEN
Solar/Wind Harmer
0.957
247620Y3-023
Adder
0.286
270216AD2-079_GEN
Solar/Wind Harmer
0.373
270526AF1-158 GEN
Solar/Wind Harmer
2.704
24441505OLIV SLR
Solar/Wind Harmer
0.079
970611AG2-400 GEN
Solar/Wind Harmer
5.881
965681AG1-436 GEN
Solar/Wind Harmer
7.117
965791AG1-447 GEN
Solar/Wind Harmer
3.641
270224U2-072_GEN2
Solar/Wind Harmer
1.047
270227U2-072_GEN3
Solar/Wind Harmer
1.047
270228U2-072_GEN4
Solar/Wind Harmer
1.047
270231U2-072_GEN5
Solar/Wind Harmer
1.047
274808UNIV PK N;4U
Adder
2.604
274803UNIV PARK;6U
Adder
3.011
274888KELLY CRK;1U
Solar/Wind Harmer
3.034
274887GEN-1.85
Solar/Wind Harmer
2.739
276843GEN-1.7
Solar/Wind Harmer
0.295
958011AF2-095 GEN
Solar/Wind Harmer
7.401
274770LINCOLN ;1U
Adder
3.184
274771LINCOLN ;2U
Adder
3.184
972259AH1-714 GEN
Adder
9.731
274674JOLIET 9 ;6U
Adder
7.833
24189902OREGON_CT2
50/50
4.092
23856402BAYSG1
50/50
1.558
23888702TROY G3
50/50
1.502
972253AH1-711 GEN
50/50
45.886
23920202STRYCT
50/50
1.896
241808AF1-120 C
Solar/Wind Harmer
1.228
241858AF1-205_GEN
Solar/Wind Harmer
5.333
241840AF1-064_GEN
Solar/Wind Harmer
1.343
972301AH1-735 GEN
Adder
6.599
23906402RICHG1
Adder
1.32
23906502RICHG2&3
Adder
1.317
270361_3
Solar/Wind Harmer
8.085
960841AF2-375 GEN
Solar/Wind Harmer
3.588
970515AG2-329 GEN
Solar/Wind Harmer
10.955
944231AF1-091 GEN
Solar/Wind Harmer
2.656
247522W1-056 GEN
Solar/Wind Harmer
1.562
270449AD2-020 GEN
Solar/Wind Harmer
1.841
943021AE2-325 GEN
Solar/Wind Harmer
2.392
246936BC-WTG1
Solar/Wind Harmer
2.519
270489AE1-102 GEN1
Solar/Wind Harmer
0.837
945111AF1-176 GEN
Solar/Wind Harmer
11.446
270505AE1-170 C O1
Solar/Wind Harmer
9.623
965421AG1-410 GEN
Solar/Wind Harmer
19.155
24639705ELKHART HY
Adder
0.095
24695305TIMB G C
Solar/Wind Harmer
3.406
270063AE2-323 C
Solar/Wind Harmer
1.345
247521TR3_G114
Solar/Wind Harmer
2.021
270246TR4_N_V150
Solar/Wind Harmer
0.511
965011AG1-365 GEN
Solar/Wind Harmer
5.881
270462AD2-086
Solar/Wind Harmer
3.972
970373AG2-245 GEN
Solar/Wind Harmer
11.492
270055AF2-134 C O1
Solar/Wind Harmer
1.624
270223U2-072_GEN1
Solar/Wind Harmer
1.047
972211AH1-690 GEN
50/50
441.807
23888502TROY G1
50/50
1.502
23888602TROY G2
50/50
1.502
970817AG2-515 GEN
Solar/Wind Harmer
14.047
945411AF1-206 GEN
Solar/Wind Harmer
8.225
945641AF1-229 GEN
Solar/Wind Harmer
3.751
270499AE1-146 GEN
Solar/Wind Harmer
2.271
971549AH1-272 GEN
Solar/Wind Harmer
14.989
270297AD1-101 GEN
Solar/Wind Harmer
1.998
944161AF1-084 GEN
Solar/Wind Harmer
1.473
957201AF2-014 GEN
Solar/Wind Harmer
2.92
270435AC2-044 GEN
Solar/Wind Harmer
1.288
247607V1-011 GEN
Solar/Wind Harmer
2.525
971771AH1-392 GEN
Solar/Wind Harmer
5.464
965041AG1-368 GEN
Solar/Wind Harmer
6.053
965051AG1-369 GEN
Solar/Wind Harmer
3.001
966831AG1-554 GEN
Solar/Wind Harmer
0.715
971989AH1-539 GEN
Solar/Wind Harmer
7.733
971769AH1-391 GEN
Solar/Wind Harmer
5.922
270302AB2-170 GEN
Solar/Wind Harmer
4.775
270317AD1-130_GEN
Solar/Wind Harmer
1.83
960681AF2-359 GEN
Solar/Wind Harmer
2.151
971347AH1-153 GEN
Solar/Wind Harmer
8.492
963791AG1-232 GEN
Solar/Wind Harmer
7.348
971567AH1-282 GEN
Solar/Wind Harmer
8.122
270536AF1-215 GEN2
Solar/Wind Harmer
2.437
270578AF1-285 GEN2
Solar/Wind Harmer
0.246
274814UNIV PK N;0U
Adder
2.638
274807UNIV PK N;3U
Adder
2.632
274805UNIV PK N;1U
Adder
2.621
274811UNIV PK N;7U
Adder
2.615
270071AF1-092 GEN
Solar/Wind Harmer
7.832
958391AF2-133 GEN
Solar/Wind Harmer
4.734
972037AH1-567 GEN1
Adder
0.095
274827FISK ;RP
Adder
4
960591AF2-350 GEN
Solar/Wind Harmer
5.139
274775LINCOLN ;6U
Adder
3.184
274776LINCOLN ;7U
Adder
3.184
274777LINCOLN ;8U
Adder
3.184
972227AH1-698 GEN1
Adder
1.336
274687WILL CNTY;4U
Adder
14.272
274687WILL CNTY;4U
Adder
14.272
274675JOLIET 29;7U
Adder
15.638
274675JOLIET 29;7U
Adder
15.08
274731ELWOOD EC;2P
Adder
8.363
274733ELWOOD EC;3P
Adder
8.363
274735ELWOOD EC;4P
Adder
8.363
274728ELWOOD EC;5P
Adder
8.363
970833AG2-524 GEN
Solar/Wind Harmer
4.42
970833AG2-524 GEN
Solar/Wind Harmer
2.056
274746AC1-111 G10
Adder
2.812
274744AC1-111 GEN8
Adder
2.812
274823ROCKFORD ;21
Adder
9.526
24729505KEY G4
Adder
3.155
241886AC2-103 GEN2
Solar/Wind Helper
6.897
241982AE2-343 S C
Solar/Wind Helper
0.125
254304AE2-114 C
Solar/Wind Helper
0.119
203846AF2-130 C
Solar/Wind Helper
0.261
241997AF1-093 GEN
Solar/Wind Helper
0.138
203804AE2-113_GEN
Solar/Wind Helper
0.91
970321AG2-212 GEN
Solar/Wind Harmer
9.047
274847GR RIDGE ;BU
Solar/Wind Harmer
2.559
958481AF2-142 GEN
Solar/Wind Harmer
7.542
274861TOP CROP ;1U
Solar/Wind Harmer
3.046
274862TOP CROP ;2U
Solar/Wind Harmer
2.544
942221AE2-234 GEN
Solar/Wind Harmer
0.367
274696ROCKY RD ;4P
Adder
5.693
274695ROCKY RD ;2P
Adder
5.562
274693ROCKY RD ;1P
Adder
5.507
274697ROCKY RD ;3P
Adder
1.511
274683WAUKEGAN ;8U
Adder
10.52
274683WAUKEGAN ;8U
Adder
8.868
274764LEE CO EC;5U
Adder
4.506
274765LEE CO EC;6U
Adder
4.506
274762LEE CO EC;3U
Adder
4.495
274763LEE CO EC;4U
Adder
4.453
972267AH1-718 GEN
Adder
1.998
247621Y3-024
Adder
0.11
25326509SID D
Adder
0.587
203947AF1-006 C
Solar/Wind Helper
0.402
203980AG1-197 GEN
Solar/Wind Helper
0.263
203979AG1-198 GEN
Solar/Wind Helper
0.205
241967AE2-285_GEN
Solar/Wind Helper
0.358
241801AE1-079 GEN
Solar/Wind Helper
0.139
241985AE1-237 GEN
Solar/Wind Helper
0.139
962101AG1-054 GEN
Solar/Wind Helper
0.345
946381AF1-302 GEN
Solar/Wind Helper
0.11
238217AF1-153 C O1
Solar/Wind Helper
0.117
971573AH1-285 GEN
Solar/Wind Harmer
0.202
274676JOLIET 29;8U
Adder
15.079
276897AD1-100 C
Solar/Wind Harmer
14.775
939351AE1-166 GEN
Solar/Wind Harmer
3.019
276893AG1-478 C
Solar/Wind Harmer
0.213
274729ELWOOD EC;1P
Adder
8.363
274730ELWOOD EC;6P
Adder
8.363
274734ELWOOD EC;8P
Adder
8.363
274736ELWOOD EC;9P
Adder
8.363
970707AG2-453 GEN
Solar/Wind Harmer
14.243
970513AG2-328 GEN
Solar/Wind Harmer
9.047
970517AG2-330 GEN
Solar/Wind Harmer
8.206
943121AE2-341 GEN
Solar/Wind Harmer
7.543
943591AF1-030 GEN
Solar/Wind Harmer
5.029
276694AA1-018 GEN2
Solar/Wind Harmer
3.173
274682WAUKEGAN ;7U
Adder
8.98
972236AH1-702 GEN2
Adder
1.07
274760LEE CO EC;1U
Adder
4.495
274767LEE CO EC;8U
Adder
4.442
962511AG1-100 GEN
Solar/Wind Helper
0.361
203830AF1-094 GEN
Solar/Wind Helper
0.342
959441AF2-235 GEN
Solar/Wind Helper
0.155
254305AE2-115 C
Solar/Wind Helper
0.119
20334926Z1-069 C
Solar/Wind Helper
0.677
270578AF1-285 GEN2
Solar/Wind Harmer
0.64
270391AF1-285 GEN3
Solar/Wind Harmer
0.64
274751CRETE EC ;1U
Adder
2.584
274754CRETE EC ;4U
Adder
2.584
958381AF2-132 GEN
Solar/Wind Harmer
4.779
964861AG1-349 GEN
Solar/Wind Harmer
4.133
971917AH1-482 GEN
Solar/Wind Harmer
4.769
274723RIVER EC ;12
Adder
9.4
274812UNIV PK N;8U
Adder
2.615
276164X3-005 C
Solar/Wind Harmer
0.365
274801UNIV PARK;4U
Adder
3.001
276776AD2-060 GEN
Solar/Wind Harmer
0.217
972207SS24-0001
Solar/Wind Harmer
11.322
274773LINCOLN ;4U
Adder
3.184
274774LINCOLN ;5U
Adder
3.184
940581AE2-045 GEN
Solar/Wind Harmer
5.238
971605AH1-302 GEN
Solar/Wind Harmer
4.479
274676JOLIET 29;8U
Adder
15.638
941551AE2-152 GEN
Solar/Wind Harmer
2.309
274732ELWOOD EC;7P
Adder
8.363
274674JOLIET 9 ;6U
Adder
7.833
970245AG2-165 GEN
Solar/Wind Harmer
9.047
274871GR RIDGE ;2U
Solar/Wind Harmer
3.89
274745AC1-111 GEN9
Adder
2.812
276691AA1-018 GEN1
Solar/Wind Harmer
0.234
274682WAUKEGAN ;7U
Adder
8.98
274828WAUKEGAN ;BP
Adder
5.514
274822ROCKFORD ;11
Adder
9.595
972235AH1-702 GEN1
Adder
1.23
274761LEE CO EC;2U
Adder
4.495
274766LEE CO EC;7U
Adder
4.442
241885AC2-103 GEN1
Solar/Wind Helper
6.897
241807AE2-176_GEN
Solar/Wind Helper
1.674
961971AG1-040 GEN
Solar/Wind Helper
0.353
203835AF1-098 GEN
Solar/Wind Helper
1.392
203860AG1-193 C
Solar/Wind Helper
0.157
241966AE1-183 GEN
Solar/Wind Helper
0.138
254303AC2-168 GEN
Solar/Wind Helper
0.08
203954AE2-126 C
Solar/Wind Helper
0.229
991177J1571 G
External Queue
15.792752265930176
990527J1329
External Queue
2.0234405994415283
990142J1224
External Queue
14.791350364685059
991182J1586 G
External Queue
28.11846351623535
LAGNLTFEXP_LAGN->PJM
CLTF
5.627
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.753
TVALTFEXP_TVA->PJM
CLTF
2.558
CPLELTFEXP_CPLE->PJM
CLTF
0.497
CBM West 2LTFEXP_CBM-W2->PJM
CBM
44.66
NYPJM->LTFIMP_NY
CLTF
2.102
LGEELTFEXP_LGEE->PJM
CLTF
2.253
WECLTFEXP_WEC->PJM
CLTF
1.864
AG2-052LTFEXP_AG2-052->PJM
LTF
0.12
AH1-155LTFEXP_AH1-155->PJM
LTF
0.18
CBM West 1LTFEXP_CBM-W1->PJM
CBM
109.741
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.094
MECLTFEXP_MEC->PJM
CLTF
7.274
SIGELTFEXP_SIGE->PJM
CLTF
0.188

Details for 02BAY SH-02DAV-BE 345.0 kV Ckt 1 line l/o ATSI_P2-3_TE-345-013_SRT-SL


Base Case Flowgate

Area:ATSI
Facility Description:
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_TE-345-013_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:146.58 %
Rating:1683.0 MVA
Rating Type:B
MVA to Mitigate:2466.99
MW Contribution:15.4
Bus #Bus NameTypeMW Contribution
24189902OREGON_CT2
50/50
4.123
23856402BAYSG1
50/50
1.571
23888702TROY G3
50/50
1.536
972253AH1-711 GEN
50/50
46.925
23920202STRYCT
50/50
1.926
241808AF1-120 C
Solar/Wind Harmer
1.246
241858AF1-205_GEN
Solar/Wind Harmer
5.409
241840AF1-064_GEN
Solar/Wind Harmer
1.361
972301AH1-735 GEN
Adder
6.723
23906402RICHG1
Adder
1.345
23906502RICHG2&3
Adder
1.342
270361_3
Solar/Wind Harmer
8.261
960841AF2-375 GEN
Solar/Wind Harmer
3.668
970515AG2-329 GEN
Solar/Wind Harmer
11.285
944231AF1-091 GEN
Solar/Wind Harmer
2.737
247522W1-056 GEN
Solar/Wind Harmer
1.61
270449AD2-020 GEN
Solar/Wind Harmer
1.903
943021AE2-325 GEN
Solar/Wind Harmer
2.473
246936BC-WTG1
Solar/Wind Harmer
2.606
270489AE1-102 GEN1
Solar/Wind Harmer
0.866
945111AF1-176 GEN
Solar/Wind Harmer
11.84
270505AE1-170 C O1
Solar/Wind Harmer
9.954
965421AG1-410 GEN
Solar/Wind Harmer
19.819
24639705ELKHART HY
Adder
0.099
24695305TIMB G C
Solar/Wind Harmer
3.527
270063AE2-323 C
Solar/Wind Harmer
1.394
247521TR3_G114
Solar/Wind Harmer
2.094
270246TR4_N_V150
Solar/Wind Harmer
0.53
965011AG1-365 GEN
Solar/Wind Harmer
6.101
270462AD2-086
Solar/Wind Harmer
4.126
970373AG2-245 GEN
Solar/Wind Harmer
11.954
270055AF2-134 C O1
Solar/Wind Harmer
1.691
270223U2-072_GEN1
Solar/Wind Harmer
1.091
270578AF1-285 GEN2
Solar/Wind Harmer
0.667
270391AF1-285 GEN3
Solar/Wind Harmer
0.667
274751CRETE EC ;1U
Adder
2.692
274754CRETE EC ;4U
Adder
2.692
958381AF2-132 GEN
Solar/Wind Harmer
4.978
964861AG1-349 GEN
Solar/Wind Harmer
4.305
971917AH1-482 GEN
Solar/Wind Harmer
4.968
274723RIVER EC ;12
Adder
9.794
274812UNIV PK N;8U
Adder
2.725
276164X3-005 C
Solar/Wind Harmer
0.381
274801UNIV PARK;4U
Adder
3.129
276776AD2-060 GEN
Solar/Wind Harmer
0.227
972207SS24-0001
Solar/Wind Harmer
11.806
274773LINCOLN ;4U
Adder
3.32
274774LINCOLN ;5U
Adder
3.32
940581AE2-045 GEN
Solar/Wind Harmer
5.461
971605AH1-302 GEN
Solar/Wind Harmer
4.67
274676JOLIET 29;8U
Adder
16.311
941551AE2-152 GEN
Solar/Wind Harmer
2.408
274732ELWOOD EC;7P
Adder
8.724
274674JOLIET 9 ;6U
Adder
8.171
970245AG2-165 GEN
Solar/Wind Harmer
9.439
274871GR RIDGE ;2U
Solar/Wind Harmer
4.059
274745AC1-111 GEN9
Adder
2.935
276691AA1-018 GEN1
Solar/Wind Harmer
0.244
274682WAUKEGAN ;7U
Adder
9.374
274828WAUKEGAN ;BP
Adder
5.756
274822ROCKFORD ;11
Adder
10.025
972235AH1-702 GEN1
Adder
1.285
274761LEE CO EC;2U
Adder
4.699
274766LEE CO EC;7U
Adder
4.644
24728605AND G2
Adder
1.664
241885AC2-103 GEN1
Solar/Wind Helper
6.853
241807AE2-176_GEN
Solar/Wind Helper
1.649
961971AG1-040 GEN
Solar/Wind Helper
0.343
203835AF1-098 GEN
Solar/Wind Helper
1.35
203860AG1-193 C
Solar/Wind Helper
0.152
241966AE1-183 GEN
Solar/Wind Helper
0.132
254303AC2-168 GEN
Solar/Wind Helper
0.077
24190002OREGON_ST1
50/50
5.547
24189802OREGON_CT1
50/50
4.208
23888802TROY G4
50/50
1.536
241996AE2-282_GEN
Solar/Wind Harmer
2.235
971677AH1-339 GEN
Solar/Wind Harmer
6.71
961051AF2-396 GEN
Solar/Wind Harmer
10.688
961051AF2-396 GEN
Solar/Wind Harmer
4.971
246938BC-WTG3
Solar/Wind Harmer
2.651
246937BC-WTG2
Solar/Wind Harmer
2.606
960981AF2-389 GEN
Solar/Wind Harmer
1
957891AF2-083 GEN
Solar/Wind Harmer
2.231
270007AE1-245 C
Solar/Wind Harmer
3.918
942801AE2-298 GEN
Solar/Wind Harmer
0.99
247620Y3-023
Adder
0.296
270216AD2-079_GEN
Solar/Wind Harmer
0.386
270526AF1-158 GEN
Solar/Wind Harmer
2.804
24441505OLIV SLR
Solar/Wind Harmer
0.082
970611AG2-400 GEN
Solar/Wind Harmer
6.101
965681AG1-436 GEN
Solar/Wind Harmer
7.392
965791AG1-447 GEN
Solar/Wind Harmer
3.782
972211AH1-690 GEN
50/50
445.145
23888502TROY G1
50/50
1.536
23888602TROY G2
50/50
1.536
970817AG2-515 GEN
Solar/Wind Harmer
14.306
945411AF1-206 GEN
Solar/Wind Harmer
8.348
945641AF1-229 GEN
Solar/Wind Harmer
3.836
270499AE1-146 GEN
Solar/Wind Harmer
2.323
971549AH1-272 GEN
Solar/Wind Harmer
15.402
270297AD1-101 GEN
Solar/Wind Harmer
2.057
944161AF1-084 GEN
Solar/Wind Harmer
1.521
957201AF2-014 GEN
Solar/Wind Harmer
3.021
270435AC2-044 GEN
Solar/Wind Harmer
1.332
247607V1-011 GEN
Solar/Wind Harmer
2.612
971771AH1-392 GEN
Solar/Wind Harmer
5.663
965041AG1-368 GEN
Solar/Wind Harmer
6.272
965051AG1-369 GEN
Solar/Wind Harmer
3.11
966831AG1-554 GEN
Solar/Wind Harmer
0.741
971989AH1-539 GEN
Solar/Wind Harmer
8.012
971769AH1-391 GEN
Solar/Wind Harmer
6.143
270302AB2-170 GEN
Solar/Wind Harmer
4.96
270317AD1-130_GEN
Solar/Wind Harmer
1.901
960681AF2-359 GEN
Solar/Wind Harmer
2.234
971347AH1-153 GEN
Solar/Wind Harmer
8.822
963791AG1-232 GEN
Solar/Wind Harmer
7.644
971567AH1-282 GEN
Solar/Wind Harmer
8.457
270536AF1-215 GEN2
Solar/Wind Harmer
2.537
270578AF1-285 GEN2
Solar/Wind Harmer
0.257
274814UNIV PK N;0U
Adder
2.749
274807UNIV PK N;3U
Adder
2.743
274805UNIV PK N;1U
Adder
2.731
274811UNIV PK N;7U
Adder
2.725
270071AF1-092 GEN
Solar/Wind Harmer
8.161
958391AF2-133 GEN
Solar/Wind Harmer
4.933
972037AH1-567 GEN1
Adder
0.099
274827FISK ;RP
Adder
4.17
960591AF2-350 GEN
Solar/Wind Harmer
5.359
274775LINCOLN ;6U
Adder
3.32
274776LINCOLN ;7U
Adder
3.32
274777LINCOLN ;8U
Adder
3.32
972227AH1-698 GEN1
Adder
1.394
274687WILL CNTY;4U
Adder
14.885
274687WILL CNTY;4U
Adder
14.885
274675JOLIET 29;7U
Adder
16.311
274675JOLIET 29;7U
Adder
15.729
274731ELWOOD EC;2P
Adder
8.724
274733ELWOOD EC;3P
Adder
8.724
274735ELWOOD EC;4P
Adder
8.724
274728ELWOOD EC;5P
Adder
8.724
970833AG2-524 GEN
Solar/Wind Harmer
4.611
970833AG2-524 GEN
Solar/Wind Harmer
2.145
274746AC1-111 G10
Adder
2.935
274744AC1-111 GEN8
Adder
2.935
274823ROCKFORD ;21
Adder
9.953
24729505KEY G4
Adder
3.297
241886AC2-103 GEN2
Solar/Wind Helper
6.853
241982AE2-343 S C
Solar/Wind Helper
0.12
254304AE2-114 C
Solar/Wind Helper
0.114
203846AF2-130 C
Solar/Wind Helper
0.251
241997AF1-093 GEN
Solar/Wind Helper
0.132
203804AE2-113_GEN
Solar/Wind Helper
0.87
270224U2-072_GEN2
Solar/Wind Harmer
1.091
270227U2-072_GEN3
Solar/Wind Harmer
1.091
270228U2-072_GEN4
Solar/Wind Harmer
1.091
270231U2-072_GEN5
Solar/Wind Harmer
1.091
274808UNIV PK N;4U
Adder
2.713
274803UNIV PARK;6U
Adder
3.139
274888KELLY CRK;1U
Solar/Wind Harmer
3.164
274887GEN-1.85
Solar/Wind Harmer
2.856
276843GEN-1.7
Solar/Wind Harmer
0.307
958011AF2-095 GEN
Solar/Wind Harmer
7.717
274770LINCOLN ;1U
Adder
3.32
274771LINCOLN ;2U
Adder
3.32
972259AH1-714 GEN
Adder
10.15
274674JOLIET 9 ;6U
Adder
8.171
970321AG2-212 GEN
Solar/Wind Harmer
9.439
274847GR RIDGE ;BU
Solar/Wind Harmer
2.67
958481AF2-142 GEN
Solar/Wind Harmer
7.871
274861TOP CROP ;1U
Solar/Wind Harmer
3.179
274862TOP CROP ;2U
Solar/Wind Harmer
2.655
942221AE2-234 GEN
Solar/Wind Harmer
0.383
274696ROCKY RD ;4P
Adder
5.943
274695ROCKY RD ;2P
Adder
5.806
274693ROCKY RD ;1P
Adder
5.749
274697ROCKY RD ;3P
Adder
1.577
274683WAUKEGAN ;8U
Adder
10.982
274683WAUKEGAN ;8U
Adder
9.257
274764LEE CO EC;5U
Adder
4.71
274765LEE CO EC;6U
Adder
4.71
274762LEE CO EC;3U
Adder
4.699
274763LEE CO EC;4U
Adder
4.655
972267AH1-718 GEN
Adder
2.09
247621Y3-024
Adder
0.116
25326509SID D
Adder
0.615
203947AF1-006 C
Solar/Wind Helper
0.391
203980AG1-197 GEN
Solar/Wind Helper
0.255
203979AG1-198 GEN
Solar/Wind Helper
0.199
241967AE2-285_GEN
Solar/Wind Helper
0.345
241801AE1-079 GEN
Solar/Wind Helper
0.134
241985AE1-237 GEN
Solar/Wind Helper
0.134
962101AG1-054 GEN
Solar/Wind Helper
0.332
946381AF1-302 GEN
Solar/Wind Helper
0.105
238217AF1-153 C O1
Solar/Wind Helper
0.112
971573AH1-285 GEN
Solar/Wind Harmer
0.21
23929302BS-PKR
50/50
2.766
241832AE2-181_GEN
Solar/Wind Harmer
1.995
958321AF2-126 GEN
Solar/Wind Harmer
1.459
23906502RICHG2&3
Adder
1.342
270541AE2-072 C
Solar/Wind Harmer
4.431
270575GUS2 35KV
Solar/Wind Harmer
9.732
970217AG2-149 GEN
Solar/Wind Harmer
24.885
247604X1-042
Adder
0.304
270044AE2-322 C
Solar/Wind Harmer
0.942
270404AC1-167 GEN
Solar/Wind Harmer
0.785
24441205WTRV SLR C
Solar/Wind Harmer
0.096
270258AD1-119 GEN
Solar/Wind Harmer
1.934
270491AE1-102 GEN2
Solar/Wind Harmer
0.866
945111AF1-176 GEN
Solar/Wind Harmer
3.753
958091AF2-103 GEN
Solar/Wind Harmer
0.107
270588AE1-091_GEN
Solar/Wind Harmer
7.25
24642205MAYFLWER
Adder
0.41
247643Z2-116 C
Solar/Wind Harmer
0.044
970031AG2-029 GEN
Solar/Wind Harmer
18.979
270191TR4_S_V150
Solar/Wind Harmer
1.869
270247TR4_N_V136
Solar/Wind Harmer
0.53
959331AF2-224 GEN
Solar/Wind Harmer
6.101
965021AG1-366 GEN
Solar/Wind Harmer
1.419
270485AE1-090_GEN
Solar/Wind Harmer
0.359
970349AG2-230 GEN
Solar/Wind Harmer
8.822
270043AE2-236 GEN
Solar/Wind Harmer
3.209
270535AF1-215 GEN1
Solar/Wind Harmer
2.537
942871AE2-306 GEN
Solar/Wind Harmer
0.5
270391AF1-285 GEN3
Solar/Wind Harmer
0.257
972231SS25-0005
Solar/Wind Harmer
5.226
972181SS23-001
Solar/Wind Harmer
3.267
274752CRETE EC ;2U
Adder
2.692
274753CRETE EC ;3U
Adder
2.692
964401AG1-302 GEN
Solar/Wind Harmer
4.978
274724RIVER EC ;11
Adder
9.677
959141AF2-205 GEN
Solar/Wind Harmer
3.265
274802UNIV PARK;5U
Adder
3.139
274826FISK ;BP
Adder
5.884
274800UNIV PARK;3U
Adder
3.129
972038AH1-567 GEN2
Adder
0.196
276772AC2-154 GEN
Solar/Wind Harmer
1.494
276806AD2-047 C O1
Solar/Wind Harmer
5.733
970941AG2-585 GEN
Solar/Wind Harmer
6.698
274772LINCOLN ;3U
Adder
3.32
972228AH1-698 GEN2
Adder
1.979
274676JOLIET 29;8U
Adder
15.729
276897AD1-100 C
Solar/Wind Harmer
15.411
939351AE1-166 GEN
Solar/Wind Harmer
3.149
276893AG1-478 C
Solar/Wind Harmer
0.222
274729ELWOOD EC;1P
Adder
8.724
274730ELWOOD EC;6P
Adder
8.724
274734ELWOOD EC;8P
Adder
8.724
274736ELWOOD EC;9P
Adder
8.724
970707AG2-453 GEN
Solar/Wind Harmer
14.858
970513AG2-328 GEN
Solar/Wind Harmer
9.439
970517AG2-330 GEN
Solar/Wind Harmer
8.561
943121AE2-341 GEN
Solar/Wind Harmer
7.872
943591AF1-030 GEN
Solar/Wind Harmer
5.248
276694AA1-018 GEN2
Solar/Wind Harmer
3.311
274682WAUKEGAN ;7U
Adder
9.374
972236AH1-702 GEN2
Adder
1.118
274760LEE CO EC;1U
Adder
4.699
274767LEE CO EC;8U
Adder
4.644
24728705AND G3
Adder
3.481
24728505AND G1
Adder
1.664
962511AG1-100 GEN
Solar/Wind Helper
0.351
203830AF1-094 GEN
Solar/Wind Helper
0.331
959441AF2-235 GEN
Solar/Wind Helper
0.15
254305AE2-115 C
Solar/Wind Helper
0.114
20334926Z1-069 C
Solar/Wind Helper
0.646
991177J1571 G
External Queue
15.818673133850098
990527J1329
External Queue
2.0267114639282227
990142J1224
External Queue
14.81525993347168
991182J1586 G
External Queue
28.164417266845703
LAGNLTFEXP_LAGN->PJM
CLTF
6.068
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.404
TVALTFEXP_TVA->PJM
CLTF
2.778
CPLELTFEXP_CPLE->PJM
CLTF
0.732
CBM West 2LTFEXP_CBM-W2->PJM
CBM
47.597
NYPJM->LTFIMP_NY
CLTF
1.967
LGEELTFEXP_LGEE->PJM
CLTF
2.403
WECLTFEXP_WEC->PJM
CLTF
1.948
AG2-052LTFEXP_AG2-052->PJM
LTF
0.125
AH1-155LTFEXP_AH1-155->PJM
LTF
0.188
CBM West 1LTFEXP_CBM-W1->PJM
CBM
112.978
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.921
MECLTFEXP_MEC->PJM
CLTF
7.642
SIGELTFEXP_SIGE->PJM
CLTF
0.2

Details for 02BAY SH-02DAV-BE 345.0 kV Ckt 1 line l/o ATSI_P2-3_TE-345-014_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_TE-345-014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:146.58 %
Rating:1683.0 MVA
Rating Type:B
MVA to Mitigate:2466.97
MW Contribution:15.4
Bus #Bus NameTypeMW Contribution
24189902OREGON_CT2
50/50
4.123
23856402BAYSG1
50/50
1.571
23888702TROY G3
50/50
1.536
972253AH1-711 GEN
50/50
46.923
23920202STRYCT
50/50
1.926
241808AF1-120 C
Solar/Wind Harmer
1.246
241858AF1-205_GEN
Solar/Wind Harmer
5.409
241840AF1-064_GEN
Solar/Wind Harmer
1.361
972301AH1-735 GEN
Adder
6.723
23906402RICHG1
Adder
1.345
23906502RICHG2&3
Adder
1.342
270361_3
Solar/Wind Harmer
8.261
960841AF2-375 GEN
Solar/Wind Harmer
3.668
970515AG2-329 GEN
Solar/Wind Harmer
11.285
944231AF1-091 GEN
Solar/Wind Harmer
2.737
247522W1-056 GEN
Solar/Wind Harmer
1.61
270449AD2-020 GEN
Solar/Wind Harmer
1.903
943021AE2-325 GEN
Solar/Wind Harmer
2.473
246936BC-WTG1
Solar/Wind Harmer
2.606
270489AE1-102 GEN1
Solar/Wind Harmer
0.866
945111AF1-176 GEN
Solar/Wind Harmer
11.84
270505AE1-170 C O1
Solar/Wind Harmer
9.954
965421AG1-410 GEN
Solar/Wind Harmer
19.819
972211AH1-690 GEN
50/50
445.147
23888502TROY G1
50/50
1.536
23888602TROY G2
50/50
1.536
970817AG2-515 GEN
Solar/Wind Harmer
14.306
945411AF1-206 GEN
Solar/Wind Harmer
8.348
945641AF1-229 GEN
Solar/Wind Harmer
3.836
24639705ELKHART HY
Adder
0.099
24695305TIMB G C
Solar/Wind Harmer
3.527
270063AE2-323 C
Solar/Wind Harmer
1.394
247521TR3_G114
Solar/Wind Harmer
2.094
270246TR4_N_V150
Solar/Wind Harmer
0.53
965011AG1-365 GEN
Solar/Wind Harmer
6.101
270462AD2-086
Solar/Wind Harmer
4.126
970373AG2-245 GEN
Solar/Wind Harmer
11.954
270055AF2-134 C O1
Solar/Wind Harmer
1.691
270223U2-072_GEN1
Solar/Wind Harmer
1.091
270578AF1-285 GEN2
Solar/Wind Harmer
0.667
270391AF1-285 GEN3
Solar/Wind Harmer
0.667
274751CRETE EC ;1U
Adder
2.692
274754CRETE EC ;4U
Adder
2.692
958381AF2-132 GEN
Solar/Wind Harmer
4.978
964861AG1-349 GEN
Solar/Wind Harmer
4.305
971917AH1-482 GEN
Solar/Wind Harmer
4.968
274723RIVER EC ;12
Adder
9.794
274812UNIV PK N;8U
Adder
2.725
276164X3-005 C
Solar/Wind Harmer
0.381
274801UNIV PARK;4U
Adder
3.129
276776AD2-060 GEN
Solar/Wind Harmer
0.227
972207SS24-0001
Solar/Wind Harmer
11.806
274773LINCOLN ;4U
Adder
3.32
274774LINCOLN ;5U
Adder
3.32
940581AE2-045 GEN
Solar/Wind Harmer
5.461
971605AH1-302 GEN
Solar/Wind Harmer
4.67
274676JOLIET 29;8U
Adder
16.311
941551AE2-152 GEN
Solar/Wind Harmer
2.408
274732ELWOOD EC;7P
Adder
8.724
274674JOLIET 9 ;6U
Adder
8.171
970245AG2-165 GEN
Solar/Wind Harmer
9.439
274871GR RIDGE ;2U
Solar/Wind Harmer
4.059
274745AC1-111 GEN9
Adder
2.935
276691AA1-018 GEN1
Solar/Wind Harmer
0.244
274682WAUKEGAN ;7U
Adder
9.374
274828WAUKEGAN ;BP
Adder
5.756
274822ROCKFORD ;11
Adder
10.025
972235AH1-702 GEN1
Adder
1.285
274761LEE CO EC;2U
Adder
4.699
274766LEE CO EC;7U
Adder
4.644
24728605AND G2
Adder
1.664
241885AC2-103 GEN1
Solar/Wind Helper
6.853
241807AE2-176_GEN
Solar/Wind Helper
1.649
961971AG1-040 GEN
Solar/Wind Helper
0.343
203835AF1-098 GEN
Solar/Wind Helper
1.35
203860AG1-193 C
Solar/Wind Helper
0.152
241966AE1-183 GEN
Solar/Wind Helper
0.132
254303AC2-168 GEN
Solar/Wind Helper
0.077
270499AE1-146 GEN
Solar/Wind Harmer
2.323
971549AH1-272 GEN
Solar/Wind Harmer
15.402
270297AD1-101 GEN
Solar/Wind Harmer
2.057
944161AF1-084 GEN
Solar/Wind Harmer
1.521
957201AF2-014 GEN
Solar/Wind Harmer
3.02
270435AC2-044 GEN
Solar/Wind Harmer
1.332
247607V1-011 GEN
Solar/Wind Harmer
2.612
971771AH1-392 GEN
Solar/Wind Harmer
5.663
965041AG1-368 GEN
Solar/Wind Harmer
6.272
965051AG1-369 GEN
Solar/Wind Harmer
3.11
966831AG1-554 GEN
Solar/Wind Harmer
0.741
971989AH1-539 GEN
Solar/Wind Harmer
8.012
971769AH1-391 GEN
Solar/Wind Harmer
6.143
270302AB2-170 GEN
Solar/Wind Harmer
4.96
270317AD1-130_GEN
Solar/Wind Harmer
1.901
960681AF2-359 GEN
Solar/Wind Harmer
2.234
971347AH1-153 GEN
Solar/Wind Harmer
8.822
963791AG1-232 GEN
Solar/Wind Harmer
7.644
971567AH1-282 GEN
Solar/Wind Harmer
8.457
270536AF1-215 GEN2
Solar/Wind Harmer
2.537
270578AF1-285 GEN2
Solar/Wind Harmer
0.257
274814UNIV PK N;0U
Adder
2.749
274807UNIV PK N;3U
Adder
2.743
274805UNIV PK N;1U
Adder
2.731
274811UNIV PK N;7U
Adder
2.725
270071AF1-092 GEN
Solar/Wind Harmer
8.161
958391AF2-133 GEN
Solar/Wind Harmer
4.933
972037AH1-567 GEN1
Adder
0.099
274827FISK ;RP
Adder
4.17
960591AF2-350 GEN
Solar/Wind Harmer
5.359
274775LINCOLN ;6U
Adder
3.32
274776LINCOLN ;7U
Adder
3.32
274777LINCOLN ;8U
Adder
3.32
972227AH1-698 GEN1
Adder
1.394
274687WILL CNTY;4U
Adder
14.885
274687WILL CNTY;4U
Adder
14.885
274675JOLIET 29;7U
Adder
16.311
274675JOLIET 29;7U
Adder
15.729
274731ELWOOD EC;2P
Adder
8.724
274733ELWOOD EC;3P
Adder
8.724
274735ELWOOD EC;4P
Adder
8.724
274728ELWOOD EC;5P
Adder
8.724
970833AG2-524 GEN
Solar/Wind Harmer
4.611
970833AG2-524 GEN
Solar/Wind Harmer
2.145
274746AC1-111 G10
Adder
2.935
274744AC1-111 GEN8
Adder
2.935
274823ROCKFORD ;21
Adder
9.952
24729505KEY G4
Adder
3.297
241886AC2-103 GEN2
Solar/Wind Helper
6.853
241982AE2-343 S C
Solar/Wind Helper
0.12
254304AE2-114 C
Solar/Wind Helper
0.114
203846AF2-130 C
Solar/Wind Helper
0.251
241997AF1-093 GEN
Solar/Wind Helper
0.132
203804AE2-113_GEN
Solar/Wind Helper
0.87
24190002OREGON_ST1
50/50
5.547
24189802OREGON_CT1
50/50
4.208
23888802TROY G4
50/50
1.536
241996AE2-282_GEN
Solar/Wind Harmer
2.235
971677AH1-339 GEN
Solar/Wind Harmer
6.71
961051AF2-396 GEN
Solar/Wind Harmer
10.687
961051AF2-396 GEN
Solar/Wind Harmer
4.971
246938BC-WTG3
Solar/Wind Harmer
2.651
246937BC-WTG2
Solar/Wind Harmer
2.606
960981AF2-389 GEN
Solar/Wind Harmer
1
957891AF2-083 GEN
Solar/Wind Harmer
2.231
270007AE1-245 C
Solar/Wind Harmer
3.918
942801AE2-298 GEN
Solar/Wind Harmer
0.99
247620Y3-023
Adder
0.296
270216AD2-079_GEN
Solar/Wind Harmer
0.386
270526AF1-158 GEN
Solar/Wind Harmer
2.804
24441505OLIV SLR
Solar/Wind Harmer
0.082
970611AG2-400 GEN
Solar/Wind Harmer
6.101
965681AG1-436 GEN
Solar/Wind Harmer
7.392
965791AG1-447 GEN
Solar/Wind Harmer
3.782
270224U2-072_GEN2
Solar/Wind Harmer
1.091
270227U2-072_GEN3
Solar/Wind Harmer
1.091
270228U2-072_GEN4
Solar/Wind Harmer
1.091
270231U2-072_GEN5
Solar/Wind Harmer
1.091
274808UNIV PK N;4U
Adder
2.713
274803UNIV PARK;6U
Adder
3.139
274888KELLY CRK;1U
Solar/Wind Harmer
3.164
274887GEN-1.85
Solar/Wind Harmer
2.856
276843GEN-1.7
Solar/Wind Harmer
0.307
958011AF2-095 GEN
Solar/Wind Harmer
7.717
274770LINCOLN ;1U
Adder
3.32
274771LINCOLN ;2U
Adder
3.32
972259AH1-714 GEN
Adder
10.15
274674JOLIET 9 ;6U
Adder
8.171
970321AG2-212 GEN
Solar/Wind Harmer
9.439
274847GR RIDGE ;BU
Solar/Wind Harmer
2.67
958481AF2-142 GEN
Solar/Wind Harmer
7.871
274861TOP CROP ;1U
Solar/Wind Harmer
3.179
274862TOP CROP ;2U
Solar/Wind Harmer
2.655
942221AE2-234 GEN
Solar/Wind Harmer
0.383
274696ROCKY RD ;4P
Adder
5.943
274695ROCKY RD ;2P
Adder
5.806
274693ROCKY RD ;1P
Adder
5.749
274697ROCKY RD ;3P
Adder
1.577
274683WAUKEGAN ;8U
Adder
10.982
274683WAUKEGAN ;8U
Adder
9.257
274764LEE CO EC;5U
Adder
4.71
274765LEE CO EC;6U
Adder
4.71
274762LEE CO EC;3U
Adder
4.699
274763LEE CO EC;4U
Adder
4.655
972267AH1-718 GEN
Adder
2.09
247621Y3-024
Adder
0.116
25326509SID D
Adder
0.615
203947AF1-006 C
Solar/Wind Helper
0.391
203980AG1-197 GEN
Solar/Wind Helper
0.255
203979AG1-198 GEN
Solar/Wind Helper
0.199
241967AE2-285_GEN
Solar/Wind Helper
0.345
241801AE1-079 GEN
Solar/Wind Helper
0.134
241985AE1-237 GEN
Solar/Wind Helper
0.134
962101AG1-054 GEN
Solar/Wind Helper
0.332
946381AF1-302 GEN
Solar/Wind Helper
0.105
238217AF1-153 C O1
Solar/Wind Helper
0.112
971573AH1-285 GEN
Solar/Wind Harmer
0.21
23929302BS-PKR
50/50
2.766
241832AE2-181_GEN
Solar/Wind Harmer
1.995
958321AF2-126 GEN
Solar/Wind Harmer
1.459
23906502RICHG2&3
Adder
1.342
270541AE2-072 C
Solar/Wind Harmer
4.431
270575GUS2 35KV
Solar/Wind Harmer
9.732
970217AG2-149 GEN
Solar/Wind Harmer
24.885
247604X1-042
Adder
0.304
270044AE2-322 C
Solar/Wind Harmer
0.942
270404AC1-167 GEN
Solar/Wind Harmer
0.785
24441205WTRV SLR C
Solar/Wind Harmer
0.096
270258AD1-119 GEN
Solar/Wind Harmer
1.934
270491AE1-102 GEN2
Solar/Wind Harmer
0.866
945111AF1-176 GEN
Solar/Wind Harmer
3.753
958091AF2-103 GEN
Solar/Wind Harmer
0.107
270588AE1-091_GEN
Solar/Wind Harmer
7.25
24642205MAYFLWER
Adder
0.41
247643Z2-116 C
Solar/Wind Harmer
0.044
970031AG2-029 GEN
Solar/Wind Harmer
18.979
270191TR4_S_V150
Solar/Wind Harmer
1.869
270247TR4_N_V136
Solar/Wind Harmer
0.53
959331AF2-224 GEN
Solar/Wind Harmer
6.101
965021AG1-366 GEN
Solar/Wind Harmer
1.419
270485AE1-090_GEN
Solar/Wind Harmer
0.359
970349AG2-230 GEN
Solar/Wind Harmer
8.822
270043AE2-236 GEN
Solar/Wind Harmer
3.209
270535AF1-215 GEN1
Solar/Wind Harmer
2.537
942871AE2-306 GEN
Solar/Wind Harmer
0.5
270391AF1-285 GEN3
Solar/Wind Harmer
0.257
972231SS25-0005
Solar/Wind Harmer
5.226
972181SS23-001
Solar/Wind Harmer
3.267
274752CRETE EC ;2U
Adder
2.692
274753CRETE EC ;3U
Adder
2.692
964401AG1-302 GEN
Solar/Wind Harmer
4.978
274724RIVER EC ;11
Adder
9.677
959141AF2-205 GEN
Solar/Wind Harmer
3.265
274802UNIV PARK;5U
Adder
3.139
274826FISK ;BP
Adder
5.884
274800UNIV PARK;3U
Adder
3.129
972038AH1-567 GEN2
Adder
0.196
276772AC2-154 GEN
Solar/Wind Harmer
1.494
276806AD2-047 C O1
Solar/Wind Harmer
5.733
970941AG2-585 GEN
Solar/Wind Harmer
6.698
274772LINCOLN ;3U
Adder
3.32
972228AH1-698 GEN2
Adder
1.979
274676JOLIET 29;8U
Adder
15.728
276897AD1-100 C
Solar/Wind Harmer
15.411
939351AE1-166 GEN
Solar/Wind Harmer
3.149
276893AG1-478 C
Solar/Wind Harmer
0.222
274729ELWOOD EC;1P
Adder
8.724
274730ELWOOD EC;6P
Adder
8.724
274734ELWOOD EC;8P
Adder
8.724
274736ELWOOD EC;9P
Adder
8.724
970707AG2-453 GEN
Solar/Wind Harmer
14.858
970513AG2-328 GEN
Solar/Wind Harmer
9.439
970517AG2-330 GEN
Solar/Wind Harmer
8.561
943121AE2-341 GEN
Solar/Wind Harmer
7.872
943591AF1-030 GEN
Solar/Wind Harmer
5.248
276694AA1-018 GEN2
Solar/Wind Harmer
3.311
274682WAUKEGAN ;7U
Adder
9.374
972236AH1-702 GEN2
Adder
1.118
274760LEE CO EC;1U
Adder
4.699
274767LEE CO EC;8U
Adder
4.644
24728705AND G3
Adder
3.481
24728505AND G1
Adder
1.664
962511AG1-100 GEN
Solar/Wind Helper
0.351
203830AF1-094 GEN
Solar/Wind Helper
0.331
959441AF2-235 GEN
Solar/Wind Helper
0.15
254305AE2-115 C
Solar/Wind Helper
0.114
20334926Z1-069 C
Solar/Wind Helper
0.646
991177J1571 G
External Queue
15.818490982055664
990527J1329
External Queue
2.026688814163208
990142J1224
External Queue
14.815095901489258
991182J1586 G
External Queue
28.164098739624023
LAGNLTFEXP_LAGN->PJM
CLTF
6.068
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.404
TVALTFEXP_TVA->PJM
CLTF
2.778
CPLELTFEXP_CPLE->PJM
CLTF
0.732
CBM West 2LTFEXP_CBM-W2->PJM
CBM
47.596
NYPJM->LTFIMP_NY
CLTF
1.967
LGEELTFEXP_LGEE->PJM
CLTF
2.403
WECLTFEXP_WEC->PJM
CLTF
1.948
AG2-052LTFEXP_AG2-052->PJM
LTF
0.125
AH1-155LTFEXP_AH1-155->PJM
LTF
0.188
CBM West 1LTFEXP_CBM-W1->PJM
CBM
112.977
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.92
MECLTFEXP_MEC->PJM
CLTF
7.642
SIGELTFEXP_SIGE->PJM
CLTF
0.2

Details for 02BAY SH-02DAV-BE 345.0 kV Ckt 1 line l/o ATSI_P2-3_TE-345-009_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_TE-345-009_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:146.4 %
Rating:1683.0 MVA
Rating Type:B
MVA to Mitigate:2463.99
MW Contribution:15.38
Bus #Bus NameTypeMW Contribution
972211AH1-690 GEN
50/50
445.374
23888502TROY G1
50/50
1.526
23888602TROY G2
50/50
1.526
970817AG2-515 GEN
Solar/Wind Harmer
14.26
945411AF1-206 GEN
Solar/Wind Harmer
8.353
945641AF1-229 GEN
Solar/Wind Harmer
3.828
270499AE1-146 GEN
Solar/Wind Harmer
2.325
971549AH1-272 GEN
Solar/Wind Harmer
15.383
270297AD1-101 GEN
Solar/Wind Harmer
2.057
944161AF1-084 GEN
Solar/Wind Harmer
1.52
957201AF2-014 GEN
Solar/Wind Harmer
3.017
270435AC2-044 GEN
Solar/Wind Harmer
1.33
247607V1-011 GEN
Solar/Wind Harmer
2.61
971771AH1-392 GEN
Solar/Wind Harmer
5.656
965041AG1-368 GEN
Solar/Wind Harmer
6.266
965051AG1-369 GEN
Solar/Wind Harmer
3.107
966831AG1-554 GEN
Solar/Wind Harmer
0.741
971989AH1-539 GEN
Solar/Wind Harmer
8.008
971769AH1-391 GEN
Solar/Wind Harmer
6.135
270302AB2-170 GEN
Solar/Wind Harmer
4.953
270317AD1-130_GEN
Solar/Wind Harmer
1.899
24189902OREGON_CT2
50/50
4.125
23856402BAYSG1
50/50
1.577
23888702TROY G3
50/50
1.526
972253AH1-711 GEN
50/50
46.611
23920202STRYCT
50/50
1.928
241808AF1-120 C
Solar/Wind Harmer
1.247
241858AF1-205_GEN
Solar/Wind Harmer
5.419
241840AF1-064_GEN
Solar/Wind Harmer
1.367
972301AH1-735 GEN
Adder
6.727
23906402RICHG1
Adder
1.345
23906502RICHG2&3
Adder
1.343
270361_3
Solar/Wind Harmer
8.271
960841AF2-375 GEN
Solar/Wind Harmer
3.672
970515AG2-329 GEN
Solar/Wind Harmer
11.264
944231AF1-091 GEN
Solar/Wind Harmer
2.736
247522W1-056 GEN
Solar/Wind Harmer
1.61
270449AD2-020 GEN
Solar/Wind Harmer
1.901
943021AE2-325 GEN
Solar/Wind Harmer
2.47
246936BC-WTG1
Solar/Wind Harmer
2.603
270489AE1-102 GEN1
Solar/Wind Harmer
0.865
945111AF1-176 GEN
Solar/Wind Harmer
11.826
270505AE1-170 C O1
Solar/Wind Harmer
9.942
965421AG1-410 GEN
Solar/Wind Harmer
19.794
24639705ELKHART HY
Adder
0.098
24695305TIMB G C
Solar/Wind Harmer
3.523
270063AE2-323 C
Solar/Wind Harmer
1.392
247521TR3_G114
Solar/Wind Harmer
2.092
270246TR4_N_V150
Solar/Wind Harmer
0.529
965011AG1-365 GEN
Solar/Wind Harmer
6.095
270462AD2-086
Solar/Wind Harmer
4.12
970373AG2-245 GEN
Solar/Wind Harmer
11.94
270055AF2-134 C O1
Solar/Wind Harmer
1.689
270223U2-072_GEN1
Solar/Wind Harmer
1.089
270578AF1-285 GEN2
Solar/Wind Harmer
0.666
270391AF1-285 GEN3
Solar/Wind Harmer
0.666
274751CRETE EC ;1U
Adder
2.689
274754CRETE EC ;4U
Adder
2.689
958381AF2-132 GEN
Solar/Wind Harmer
4.972
964861AG1-349 GEN
Solar/Wind Harmer
4.3
971917AH1-482 GEN
Solar/Wind Harmer
4.962
274723RIVER EC ;12
Adder
9.782
274812UNIV PK N;8U
Adder
2.722
276164X3-005 C
Solar/Wind Harmer
0.38
274801UNIV PARK;4U
Adder
3.125
276776AD2-060 GEN
Solar/Wind Harmer
0.226
972207SS24-0001
Solar/Wind Harmer
11.792
274773LINCOLN ;4U
Adder
3.317
274774LINCOLN ;5U
Adder
3.317
940581AE2-045 GEN
Solar/Wind Harmer
5.455
971605AH1-302 GEN
Solar/Wind Harmer
4.664
274676JOLIET 29;8U
Adder
16.292
941551AE2-152 GEN
Solar/Wind Harmer
2.406
274732ELWOOD EC;7P
Adder
8.714
274674JOLIET 9 ;6U
Adder
8.161
970245AG2-165 GEN
Solar/Wind Harmer
9.428
274871GR RIDGE ;2U
Solar/Wind Harmer
4.054
274745AC1-111 GEN9
Adder
2.931
276691AA1-018 GEN1
Solar/Wind Harmer
0.244
274682WAUKEGAN ;7U
Adder
9.363
274828WAUKEGAN ;BP
Adder
5.75
274822ROCKFORD ;11
Adder
10.013
972235AH1-702 GEN1
Adder
1.284
274761LEE CO EC;2U
Adder
4.693
274766LEE CO EC;7U
Adder
4.638
24728605AND G2
Adder
1.662
241885AC2-103 GEN1
Solar/Wind Helper
6.849
241807AE2-176_GEN
Solar/Wind Helper
1.64
961971AG1-040 GEN
Solar/Wind Helper
0.342
203835AF1-098 GEN
Solar/Wind Helper
1.348
203860AG1-193 C
Solar/Wind Helper
0.152
241966AE1-183 GEN
Solar/Wind Helper
0.132
254303AC2-168 GEN
Solar/Wind Helper
0.077
960681AF2-359 GEN
Solar/Wind Harmer
2.232
971347AH1-153 GEN
Solar/Wind Harmer
8.811
963791AG1-232 GEN
Solar/Wind Harmer
7.636
971567AH1-282 GEN
Solar/Wind Harmer
8.442
270536AF1-215 GEN2
Solar/Wind Harmer
2.534
270578AF1-285 GEN2
Solar/Wind Harmer
0.256
274814UNIV PK N;0U
Adder
2.746
274807UNIV PK N;3U
Adder
2.74
274805UNIV PK N;1U
Adder
2.728
274811UNIV PK N;7U
Adder
2.722
270071AF1-092 GEN
Solar/Wind Harmer
8.152
958391AF2-133 GEN
Solar/Wind Harmer
4.927
972037AH1-567 GEN1
Adder
0.098
274827FISK ;RP
Adder
4.165
960591AF2-350 GEN
Solar/Wind Harmer
5.352
274775LINCOLN ;6U
Adder
3.317
274776LINCOLN ;7U
Adder
3.317
274777LINCOLN ;8U
Adder
3.317
972227AH1-698 GEN1
Adder
1.392
274687WILL CNTY;4U
Adder
14.867
274687WILL CNTY;4U
Adder
14.867
274675JOLIET 29;7U
Adder
16.292
274675JOLIET 29;7U
Adder
15.71
274728ELWOOD EC;5P
Adder
8.714
274731ELWOOD EC;2P
Adder
8.713
274733ELWOOD EC;3P
Adder
8.713
274735ELWOOD EC;4P
Adder
8.713
970833AG2-524 GEN
Solar/Wind Harmer
4.606
970833AG2-524 GEN
Solar/Wind Harmer
2.142
274746AC1-111 G10
Adder
2.931
274744AC1-111 GEN8
Adder
2.931
274823ROCKFORD ;21
Adder
9.941
24729505KEY G4
Adder
3.294
241886AC2-103 GEN2
Solar/Wind Helper
6.849
241982AE2-343 S C
Solar/Wind Helper
0.12
254304AE2-114 C
Solar/Wind Helper
0.114
203846AF2-130 C
Solar/Wind Helper
0.251
241997AF1-093 GEN
Solar/Wind Helper
0.132
203804AE2-113_GEN
Solar/Wind Helper
0.869
24190002OREGON_ST1
50/50
5.55
24189802OREGON_CT1
50/50
4.21
23888802TROY G4
50/50
1.526
241996AE2-282_GEN
Solar/Wind Harmer
2.237
971677AH1-339 GEN
Solar/Wind Harmer
6.708
961051AF2-396 GEN
Solar/Wind Harmer
10.675
961051AF2-396 GEN
Solar/Wind Harmer
4.965
246938BC-WTG3
Solar/Wind Harmer
2.648
246937BC-WTG2
Solar/Wind Harmer
2.603
960981AF2-389 GEN
Solar/Wind Harmer
0.999
957891AF2-083 GEN
Solar/Wind Harmer
2.228
270007AE1-245 C
Solar/Wind Harmer
3.915
942801AE2-298 GEN
Solar/Wind Harmer
0.989
247620Y3-023
Adder
0.296
270216AD2-079_GEN
Solar/Wind Harmer
0.386
270526AF1-158 GEN
Solar/Wind Harmer
2.801
24441505OLIV SLR
Solar/Wind Harmer
0.082
970611AG2-400 GEN
Solar/Wind Harmer
6.095
965681AG1-436 GEN
Solar/Wind Harmer
7.384
965791AG1-447 GEN
Solar/Wind Harmer
3.778
270224U2-072_GEN2
Solar/Wind Harmer
1.089
270227U2-072_GEN3
Solar/Wind Harmer
1.089
270228U2-072_GEN4
Solar/Wind Harmer
1.089
270231U2-072_GEN5
Solar/Wind Harmer
1.089
274808UNIV PK N;4U
Adder
2.71
274803UNIV PARK;6U
Adder
3.135
274888KELLY CRK;1U
Solar/Wind Harmer
3.16
274887GEN-1.85
Solar/Wind Harmer
2.853
276843GEN-1.7
Solar/Wind Harmer
0.307
958011AF2-095 GEN
Solar/Wind Harmer
7.707
274770LINCOLN ;1U
Adder
3.317
274771LINCOLN ;2U
Adder
3.317
972259AH1-714 GEN
Adder
10.138
274674JOLIET 9 ;6U
Adder
8.161
970321AG2-212 GEN
Solar/Wind Harmer
9.428
274847GR RIDGE ;BU
Solar/Wind Harmer
2.667
958481AF2-142 GEN
Solar/Wind Harmer
7.862
274861TOP CROP ;1U
Solar/Wind Harmer
3.176
274862TOP CROP ;2U
Solar/Wind Harmer
2.652
942221AE2-234 GEN
Solar/Wind Harmer
0.383
274696ROCKY RD ;4P
Adder
5.936
274695ROCKY RD ;2P
Adder
5.799
274693ROCKY RD ;1P
Adder
5.742
274697ROCKY RD ;3P
Adder
1.575
274683WAUKEGAN ;8U
Adder
10.969
274683WAUKEGAN ;8U
Adder
9.246
274764LEE CO EC;5U
Adder
4.704
274765LEE CO EC;6U
Adder
4.704
274762LEE CO EC;3U
Adder
4.693
274763LEE CO EC;4U
Adder
4.649
972267AH1-718 GEN
Adder
2.087
247621Y3-024
Adder
0.115
25326509SID D
Adder
0.615
203947AF1-006 C
Solar/Wind Helper
0.391
203980AG1-197 GEN
Solar/Wind Helper
0.255
203979AG1-198 GEN
Solar/Wind Helper
0.198
241801AE1-079 GEN
Solar/Wind Helper
0.134
23929302BS-PKR
50/50
2.775
241832AE2-181_GEN
Solar/Wind Harmer
1.996
958321AF2-126 GEN
Solar/Wind Harmer
1.466
23906502RICHG2&3
Adder
1.343
270541AE2-072 C
Solar/Wind Harmer
4.433
270575GUS2 35KV
Solar/Wind Harmer
9.743
970217AG2-149 GEN
Solar/Wind Harmer
24.838
247604X1-042
Adder
0.303
270044AE2-322 C
Solar/Wind Harmer
0.942
270404AC1-167 GEN
Solar/Wind Harmer
0.784
24441205WTRV SLR C
Solar/Wind Harmer
0.096
270258AD1-119 GEN
Solar/Wind Harmer
1.933
270491AE1-102 GEN2
Solar/Wind Harmer
0.865
945111AF1-176 GEN
Solar/Wind Harmer
3.748
958091AF2-103 GEN
Solar/Wind Harmer
0.107
270588AE1-091_GEN
Solar/Wind Harmer
7.246
24642205MAYFLWER
Adder
0.41
247643Z2-116 C
Solar/Wind Harmer
0.044
970031AG2-029 GEN
Solar/Wind Harmer
18.957
270191TR4_S_V150
Solar/Wind Harmer
1.867
270247TR4_N_V136
Solar/Wind Harmer
0.529
959331AF2-224 GEN
Solar/Wind Harmer
6.095
965021AG1-366 GEN
Solar/Wind Harmer
1.417
270485AE1-090_GEN
Solar/Wind Harmer
0.358
970349AG2-230 GEN
Solar/Wind Harmer
8.811
270043AE2-236 GEN
Solar/Wind Harmer
3.205
270535AF1-215 GEN1
Solar/Wind Harmer
2.534
942871AE2-306 GEN
Solar/Wind Harmer
0.5
270391AF1-285 GEN3
Solar/Wind Harmer
0.256
972231SS25-0005
Solar/Wind Harmer
5.22
972181SS23-001
Solar/Wind Harmer
3.263
274752CRETE EC ;2U
Adder
2.689
274753CRETE EC ;3U
Adder
2.689
964401AG1-302 GEN
Solar/Wind Harmer
4.972
274724RIVER EC ;11
Adder
9.666
959141AF2-205 GEN
Solar/Wind Harmer
3.261
274802UNIV PARK;5U
Adder
3.135
274826FISK ;BP
Adder
5.877
274800UNIV PARK;3U
Adder
3.125
972038AH1-567 GEN2
Adder
0.196
276772AC2-154 GEN
Solar/Wind Harmer
1.493
276806AD2-047 C O1
Solar/Wind Harmer
5.726
970941AG2-585 GEN
Solar/Wind Harmer
6.69
274772LINCOLN ;3U
Adder
3.317
972228AH1-698 GEN2
Adder
1.977
274676JOLIET 29;8U
Adder
15.71
276897AD1-100 C
Solar/Wind Harmer
15.393
939351AE1-166 GEN
Solar/Wind Harmer
3.145
276893AG1-478 C
Solar/Wind Harmer
0.221
274730ELWOOD EC;6P
Adder
8.714
274734ELWOOD EC;8P
Adder
8.714
274736ELWOOD EC;9P
Adder
8.714
274729ELWOOD EC;1P
Adder
8.713
970707AG2-453 GEN
Solar/Wind Harmer
14.84
970513AG2-328 GEN
Solar/Wind Harmer
9.428
970517AG2-330 GEN
Solar/Wind Harmer
8.551
943121AE2-341 GEN
Solar/Wind Harmer
7.863
943591AF1-030 GEN
Solar/Wind Harmer
5.242
276694AA1-018 GEN2
Solar/Wind Harmer
3.307
274682WAUKEGAN ;7U
Adder
9.363
972236AH1-702 GEN2
Adder
1.116
274760LEE CO EC;1U
Adder
4.693
274767LEE CO EC;8U
Adder
4.638
24728705AND G3
Adder
3.477
24728505AND G1
Adder
1.662
962511AG1-100 GEN
Solar/Wind Helper
0.35
203830AF1-094 GEN
Solar/Wind Helper
0.331
959441AF2-235 GEN
Solar/Wind Helper
0.15
254305AE2-115 C
Solar/Wind Helper
0.114
20334926Z1-069 C
Solar/Wind Helper
0.646
241967AE2-285_GEN
Solar/Wind Helper
0.345
241985AE1-237 GEN
Solar/Wind Helper
0.134
962101AG1-054 GEN
Solar/Wind Helper
0.332
946381AF1-302 GEN
Solar/Wind Helper
0.105
238217AF1-153 C O1
Solar/Wind Helper
0.111
971573AH1-285 GEN
Solar/Wind Harmer
0.21
991177J1571 G
External Queue
15.792752265930176
990527J1329
External Queue
2.0234405994415283
990142J1224
External Queue
14.791350364685059
991182J1586 G
External Queue
28.11846351623535
LAGNLTFEXP_LAGN->PJM
CLTF
6.061
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.4
TVALTFEXP_TVA->PJM
CLTF
2.775
CPLELTFEXP_CPLE->PJM
CLTF
0.731
CBM West 2LTFEXP_CBM-W2->PJM
CBM
47.539
NYPJM->LTFIMP_NY
CLTF
1.965
LGEELTFEXP_LGEE->PJM
CLTF
2.4
WECLTFEXP_WEC->PJM
CLTF
1.946
AG2-052LTFEXP_AG2-052->PJM
LTF
0.125
AH1-155LTFEXP_AH1-155->PJM
LTF
0.187
CBM West 1LTFEXP_CBM-W1->PJM
CBM
112.86
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.907
MECLTFEXP_MEC->PJM
CLTF
7.633
SIGELTFEXP_SIGE->PJM
CLTF
0.2

Details for 02BAY SH-02DAV-BE 345.0 kV Ckt 1 line l/o ATSI_P1-2_TE-345-602_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_TE-345-602_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:142.52 %
Rating:1683.0 MVA
Rating Type:B
MVA to Mitigate:2398.59
MW Contribution:11.98
Bus #Bus NameTypeMW Contribution
23929302BS-PKR
50/50
2.775
241832AE2-181_GEN
Solar/Wind Harmer
0.004
958321AF2-126 GEN
Solar/Wind Harmer
1.136
23906502RICHG2&3
Adder
1.343
270541AE2-072 C
Solar/Wind Harmer
0.008
270575GUS2 35KV
Solar/Wind Harmer
4.521
970217AG2-149 GEN
Solar/Wind Harmer
4.693
247604X1-042
Adder
0.303
270404AC1-167 GEN
Solar/Wind Harmer
0.002
24441205WTRV SLR C
Solar/Wind Harmer
0
270258AD1-119 GEN
Solar/Wind Harmer
0.001
270491AE1-102 GEN2
Solar/Wind Harmer
0.603
945111AF1-176 GEN
Solar/Wind Harmer
3.748
270588AE1-091_GEN
Solar/Wind Harmer
3.595
24642205MAYFLWER
Adder
0.41
247643Z2-116 C
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
2.866
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.028
959331AF2-224 GEN
Solar/Wind Harmer
2.976
965021AG1-366 GEN
Solar/Wind Harmer
1.417
270485AE1-090_GEN
Solar/Wind Harmer
0.001
970349AG2-230 GEN
Solar/Wind Harmer
6.147
270043AE2-236 GEN
Solar/Wind Harmer
2.609
270535AF1-215 GEN1
Solar/Wind Harmer
0.005
270391AF1-285 GEN3
Solar/Wind Harmer
0.256
274752CRETE EC ;2U
Adder
4.532
274753CRETE EC ;3U
Adder
4.532
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274724RIVER EC ;11
Adder
9.666
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
274802UNIV PARK;5U
Adder
3.135
274826FISK ;BP
Adder
5.877
274800UNIV PARK;3U
Adder
3.125
972038AH1-567 GEN2
Adder
0.196
276806AD2-047 C O1
Solar/Wind Harmer
2.116
970941AG2-585 GEN
Solar/Wind Harmer
4.668
274772LINCOLN ;3U
Adder
4.515
972228AH1-698 GEN2
Adder
1.977
274676JOLIET 29;8U
Adder
15.71
276897AD1-100 C
Solar/Wind Harmer
0.005
939351AE1-166 GEN
Solar/Wind Harmer
0
276893AG1-478 C
Solar/Wind Harmer
0.147
274730ELWOOD EC;6P
Adder
8.714
274734ELWOOD EC;8P
Adder
8.714
274736ELWOOD EC;9P
Adder
8.714
274729ELWOOD EC;1P
Adder
8.713
970707AG2-453 GEN
Solar/Wind Harmer
12.079
970513AG2-328 GEN
Solar/Wind Harmer
1.596
970517AG2-330 GEN
Solar/Wind Harmer
9.577
943121AE2-341 GEN
Solar/Wind Harmer
6.132
943591AF1-030 GEN
Solar/Wind Harmer
4.078
276694AA1-018 GEN2
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
9.363
276805AD2-038 GEN
Solar/Wind Harmer
0.001
274872LEEDK;1U
Solar/Wind Harmer
0.132
24755605MDL-5G
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.599
971617AH1-308 GEN
Solar/Wind Harmer
2.996
276889AE2-281 GEN
Solar/Wind Harmer
0
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.382
274855GSG-6 ;RU
Solar/Wind Harmer
0.131
274850MENDOTA H;RU
Solar/Wind Harmer
0.042
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.064
944531AF1-118 GEN
Solar/Wind Harmer
16.023
959091AF2-200 GEN
Solar/Wind Harmer
7.133
972236AH1-702 GEN2
Adder
1.116
970571AG2-364 GEN
Solar/Wind Harmer
7.107
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
4.693
274767LEE CO EC;8U
Adder
1.086
276157O29GEN1
Solar/Wind Harmer
0.565
274878BISHOP HL;2U
Solar/Wind Harmer
0.117
942111AE2-223 GEN
Solar/Wind Harmer
1.128
274853TWINGROVE;U1
Solar/Wind Harmer
0.001
965091AG1-374 GEN
Solar/Wind Harmer
10.299
959611AF2-252 GEN
Solar/Wind Harmer
1.144
965931AG1-462 GEN
Solar/Wind Harmer
8.719
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
5.066
247642Z2-115 C
Solar/Wind Harmer
0.001
970289AG2-191 GEN
Solar/Wind Harmer
0.368
970291AG2-192 GEN
Solar/Wind Harmer
0.334
276686W4-005 GEN3
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.121
971993AH1-541 GEN
Solar/Wind Harmer
1.533
270377AD1-106 GEN
Solar/Wind Harmer
1.25
276621W2-048 GEN
Solar/Wind Harmer
0.166
276838X2-022 GEN2
Solar/Wind Harmer
0.185
946031AF1-268 GEN
Solar/Wind Harmer
3.103
958821AF2-173 GEN
Solar/Wind Harmer
4.521
270004AE1-209 GEN
Solar/Wind Harmer
0.7
962511AG1-100 GEN
Solar/Wind Helper
0.35
203830AF1-094 GEN
Solar/Wind Helper
0.331
959441AF2-235 GEN
Solar/Wind Helper
0.15
254305AE2-115 C
Solar/Wind Helper
0.114
20334926Z1-069 C
Solar/Wind Helper
0.646
972211AH1-690 GEN
50/50
445.374
23888502TROY G1
50/50
1.526
23888602TROY G2
50/50
1.526
970817AG2-515 GEN
Solar/Wind Harmer
9.949
945411AF1-206 GEN
Solar/Wind Harmer
-0.001
945641AF1-229 GEN
Solar/Wind Harmer
0.001
270499AE1-146 GEN
Solar/Wind Harmer
0.029
971549AH1-272 GEN
Solar/Wind Harmer
11.98
270297AD1-101 GEN
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.588
971619AH1-309 GEN
Solar/Wind Harmer
2.081
247607V1-011 GEN
Solar/Wind Harmer
0.001
971771AH1-392 GEN
Solar/Wind Harmer
4.385
965041AG1-368 GEN
Solar/Wind Harmer
4.372
965051AG1-369 GEN
Solar/Wind Harmer
2.168
971989AH1-539 GEN
Solar/Wind Harmer
1.862
971769AH1-391 GEN
Solar/Wind Harmer
4.78
270302AB2-170 GEN
Solar/Wind Harmer
0.003
270317AD1-130_GEN
Solar/Wind Harmer
0.006
971653AH1-327 GEN
Solar/Wind Harmer
0.58
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971347AH1-153 GEN
Solar/Wind Harmer
6.147
963791AG1-232 GEN
Solar/Wind Harmer
5.327
971567AH1-282 GEN
Solar/Wind Harmer
5.89
270536AF1-215 GEN2
Solar/Wind Harmer
0.005
270578AF1-285 GEN2
Solar/Wind Harmer
0.256
274814UNIV PK N;0U
Adder
2.746
274807UNIV PK N;3U
Adder
2.74
274805UNIV PK N;1U
Adder
2.728
274811UNIV PK N;7U
Adder
2.722
270071AF1-092 GEN
Solar/Wind Harmer
7.267
958391AF2-133 GEN
Solar/Wind Harmer
0.001
972037AH1-567 GEN1
Adder
0.098
274827FISK ;RP
Adder
4.165
960591AF2-350 GEN
Solar/Wind Harmer
3.734
274775LINCOLN ;6U
Adder
4.515
274776LINCOLN ;7U
Adder
4.515
274777LINCOLN ;8U
Adder
4.515
971611AH1-305 GEN
Solar/Wind Harmer
2.222
972227AH1-698 GEN1
Adder
1.392
274687WILL CNTY;4U
Adder
14.867
274687WILL CNTY;4U
Adder
14.867
274675JOLIET 29;7U
Adder
16.292
274675JOLIET 29;7U
Adder
15.71
274728ELWOOD EC;5P
Adder
8.714
274731ELWOOD EC;2P
Adder
8.713
274733ELWOOD EC;3P
Adder
8.713
274735ELWOOD EC;4P
Adder
8.713
970833AG2-524 GEN
Solar/Wind Harmer
4.049
970833AG2-524 GEN
Solar/Wind Harmer
2.699
274746AC1-111 G10
Adder
2.931
274744AC1-111 GEN8
Adder
2.931
276868AE1-113 GEN
Solar/Wind Harmer
0.724
276882AE2-255 GEN
Solar/Wind Harmer
0.422
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0.004
971177AH1-047 GEN
Solar/Wind Harmer
2.216
971411AH1-196 GEN
Solar/Wind Harmer
5.375
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
1.396
971171AH1-044 GEN
Solar/Wind Harmer
7.133
274823ROCKFORD ;21
Adder
9.941
926823AC1-168 GEN
Solar/Wind Harmer
0.603
970169AG2-114 GEN
Solar/Wind Harmer
3.546
276612AE2-035 GEN
Solar/Wind Harmer
0.001
24729505KEY G4
Adder
3.294
971681AH1-341 GEN
Solar/Wind Harmer
5.682
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
24387005FR-3G C
Solar/Wind Harmer
0.001
961011AF2-392 GEN
Solar/Wind Harmer
2.056
957751AF2-069 GEN
Solar/Wind Harmer
0.115
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
276655WTG1_EQ
Solar/Wind Harmer
0.001
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.644
941731AE2-173 GEN
Solar/Wind Harmer
2.892
963841AG1-237 GEN
Solar/Wind Harmer
1.492
946321AF1-296 GEN
Solar/Wind Harmer
1.922
965101AG1-375 GEN
Solar/Wind Harmer
3.421
971609AH1-304 GEN
Solar/Wind Harmer
0.55
945581AF1-223 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.635
276785W4-005 GEN1
Solar/Wind Harmer
0
276174W4-005 GEN2
Solar/Wind Harmer
0
276849AB2-070 GEN2
Solar/Wind Harmer
0.121
276848AB2-070 GEN3
Solar/Wind Harmer
0.12
270594AE1-207 GEN
Solar/Wind Harmer
3.716
970115AG2-085 GEN
Solar/Wind Harmer
1.302
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0
241886AC2-103 GEN2
Solar/Wind Helper
6.849
241982AE2-343 S C
Solar/Wind Helper
0.12
254304AE2-114 C
Solar/Wind Helper
0.114
203846AF2-130 C
Solar/Wind Helper
0.251
241997AF1-093 GEN
Solar/Wind Helper
0.132
203804AE2-113_GEN
Solar/Wind Helper
0.869
24189902OREGON_CT2
50/50
4.125
23856402BAYSG1
50/50
1.577
23888702TROY G3
50/50
1.526
972253AH1-711 GEN
50/50
46.611
23920202STRYCT
50/50
1.928
241808AF1-120 C
Solar/Wind Harmer
0.003
241858AF1-205_GEN
Solar/Wind Harmer
3.78
241840AF1-064_GEN
Solar/Wind Harmer
0.004
972301AH1-735 GEN
Adder
6.727
23906402RICHG1
Adder
1.345
23906502RICHG2&3
Adder
1.343
270361_3
Solar/Wind Harmer
4.521
960841AF2-375 GEN
Solar/Wind Harmer
-0.002
970515AG2-329 GEN
Solar/Wind Harmer
14.08
944231AF1-091 GEN
Solar/Wind Harmer
1.351
247522W1-056 GEN
Solar/Wind Harmer
0.001
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.47
246936BC-WTG1
Solar/Wind Harmer
0.188
270489AE1-102 GEN1
Solar/Wind Harmer
0.603
945111AF1-176 GEN
Solar/Wind Harmer
8.251
270505AE1-170 C O1
Solar/Wind Harmer
4.856
965421AG1-410 GEN
Solar/Wind Harmer
13.81
24639705ELKHART HY
Adder
0.098
24695305TIMB G C
Solar/Wind Harmer
0.001
270063AE2-323 C
Solar/Wind Harmer
0.004
247521TR3_G114
Solar/Wind Harmer
0.158
270246TR4_N_V150
Solar/Wind Harmer
0.028
965011AG1-365 GEN
Solar/Wind Harmer
4.252
270462AD2-086
Solar/Wind Harmer
0.009
970373AG2-245 GEN
Solar/Wind Harmer
8.33
270055AF2-134 C O1
Solar/Wind Harmer
0.003
270223U2-072_GEN1
Solar/Wind Harmer
0
274751CRETE EC ;1U
Adder
4.532
274754CRETE EC ;4U
Adder
4.532
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
4.962
274723RIVER EC ;12
Adder
9.782
274812UNIV PK N;8U
Adder
2.722
276164X3-005 C
Solar/Wind Harmer
0
274801UNIV PARK;4U
Adder
3.125
276776AD2-060 GEN
Solar/Wind Harmer
0.39
274773LINCOLN ;4U
Adder
4.515
274774LINCOLN ;5U
Adder
4.515
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
4.664
274676JOLIET 29;8U
Adder
16.292
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
8.714
274674JOLIET 9 ;6U
Adder
8.161
970245AG2-165 GEN
Solar/Wind Harmer
1.596
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
2.931
276691AA1-018 GEN1
Solar/Wind Harmer
0.443
274682WAUKEGAN ;7U
Adder
9.363
274828WAUKEGAN ;BP
Adder
5.75
276901AD2-066 C O1
Solar/Wind Harmer
0.004
939401AE1-172 GEN
Solar/Wind Harmer
2.703
962781AG1-127 GEN
Solar/Wind Harmer
3.433
274872LEEDK;1U
Solar/Wind Harmer
0.002
24791305MDL-5G
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
1.887
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
276861AD2-134 GEN
Solar/Wind Harmer
0.064
957471AF2-041 GEN
Solar/Wind Harmer
10.7
959081AF2-199 GEN
Solar/Wind Harmer
3.567
971067AG2-660 GEN
Solar/Wind Harmer
1.189
274822ROCKFORD ;11
Adder
10.013
972235AH1-702 GEN1
Adder
1.284
970569AG2-363 GEN
Solar/Wind Harmer
10.66
970819AG2-516 GEN
Solar/Wind Harmer
4.256
971475AH1-234 GEN
Solar/Wind Harmer
1.718
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
4.693
274766LEE CO EC;7U
Adder
4.638
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.001
276158O29GEN2
Solar/Wind Harmer
0
274877BISHOP HL;1U
Solar/Wind Harmer
0.117
276726Z2-087_GEN
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
4.858
965651AG1-433 GEN
Solar/Wind Harmer
1.012
274854TWINGROVE;U2
Solar/Wind Harmer
0.001
958861AF2-177 GEN
Solar/Wind Harmer
1.482
963741AG1-226 GEN
Solar/Wind Harmer
7.999
972175AH1-670 GEN
Solar/Wind Harmer
2.788
945371AF1-202 GEN
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.435
274880W4-005 GEN4
Solar/Wind Harmer
0
270032AE2-172
Solar/Wind Harmer
2.212
963831AG1-236 GEN
Solar/Wind Harmer
1.29
247536S-71 GEN
Solar/Wind Harmer
0.132
276615X2-022 GEN
Solar/Wind Harmer
0.034
276903AD2-071 C
Solar/Wind Harmer
3.649
970825AG2-519 GEN
Solar/Wind Harmer
1.153
270005AE1-210 C O1
Solar/Wind Harmer
0.7
241885AC2-103 GEN1
Solar/Wind Helper
6.849
241807AE2-176_GEN
Solar/Wind Helper
1.64
961971AG1-040 GEN
Solar/Wind Helper
0.342
203835AF1-098 GEN
Solar/Wind Helper
1.348
203860AG1-193 C
Solar/Wind Helper
0.152
241966AE1-183 GEN
Solar/Wind Helper
0.132
254303AC2-168 GEN
Solar/Wind Helper
0.077
965031AG1-367 GEN
Solar/Wind Harmer
0.798
24190002OREGON_ST1
50/50
5.55
24189802OREGON_CT1
50/50
4.21
23888802TROY G4
50/50
1.526
241996AE2-282_GEN
Solar/Wind Harmer
0.006
971677AH1-339 GEN
Solar/Wind Harmer
0.659
970621AG2-405 GEN
Solar/Wind Harmer
0.944
970623AG2-406 GEN
Solar/Wind Harmer
0.885
961051AF2-396 GEN
Solar/Wind Harmer
9.384
961051AF2-396 GEN
Solar/Wind Harmer
6.256
246938BC-WTG3
Solar/Wind Harmer
0.168
246937BC-WTG2
Solar/Wind Harmer
0.188
957891AF2-083 GEN
Solar/Wind Harmer
0.001
270007AE1-245 C
Solar/Wind Harmer
0.001
247620Y3-023
Adder
0.296
270216AD2-079_GEN
Solar/Wind Harmer
0.001
270526AF1-158 GEN
Solar/Wind Harmer
0.005
24441505OLIV SLR
Solar/Wind Harmer
0
970611AG2-400 GEN
Solar/Wind Harmer
4.252
970627AG2-408 GEN
Solar/Wind Harmer
1.276
965681AG1-436 GEN
Solar/Wind Harmer
5.151
965791AG1-447 GEN
Solar/Wind Harmer
3.778
270224U2-072_GEN2
Solar/Wind Harmer
0
270227U2-072_GEN3
Solar/Wind Harmer
0
270228U2-072_GEN4
Solar/Wind Harmer
0
270231U2-072_GEN5
Solar/Wind Harmer
0
274808UNIV PK N;4U
Adder
2.71
274803UNIV PARK;6U
Adder
3.135
274888KELLY CRK;1U
Solar/Wind Harmer
0.219
274887GEN-1.85
Solar/Wind Harmer
0.098
276843GEN-1.7
Solar/Wind Harmer
0.121
958011AF2-095 GEN
Solar/Wind Harmer
5.377
274770LINCOLN ;1U
Adder
4.515
274771LINCOLN ;2U
Adder
4.515
972259AH1-714 GEN
Adder
10.138
274674JOLIET 9 ;6U
Adder
8.161
970321AG2-212 GEN
Solar/Wind Harmer
1.596
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
958481AF2-142 GEN
Solar/Wind Harmer
5.485
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.495
942221AE2-234 GEN
Solar/Wind Harmer
0.018
971573AH1-285 GEN
Solar/Wind Harmer
0.679
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
274696ROCKY RD ;4P
Adder
5.936
274695ROCKY RD ;2P
Adder
5.799
274693ROCKY RD ;1P
Adder
5.742
274697ROCKY RD ;3P
Adder
1.575
274683WAUKEGAN ;8U
Adder
10.969
274683WAUKEGAN ;8U
Adder
9.246
958491AF2-143 GEN
Solar/Wind Harmer
5.438
962691AG1-118 GEN
Solar/Wind Harmer
10.84
274879MINONK ;1U
Solar/Wind Harmer
0.152
970921AG2-575 GEN
Solar/Wind Harmer
3.608
970921AG2-575 GEN
Solar/Wind Harmer
1.203
942991AE2-321 GEN
Solar/Wind Harmer
4.013
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
971333AH1-146 GEN
Solar/Wind Harmer
7.161
971335AH1-147 GEN
Solar/Wind Harmer
7.161
971341AH1-150 GEN
Solar/Wind Harmer
7.133
971343AH1-151 GEN
Solar/Wind Harmer
7.133
274856ECOGROVE ;U1
Solar/Wind Harmer
0.084
276611AD2-172 GEN
Solar/Wind Harmer
0.001
938861AE1-114 GEN
Solar/Wind Harmer
1.999
274764LEE CO EC;5U
Adder
4.704
274765LEE CO EC;6U
Adder
4.704
274762LEE CO EC;3U
Adder
4.693
274763LEE CO EC;4U
Adder
4.649
276603SUBLETTE C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.397
274851PROVIDENC;RU
Solar/Wind Harmer
0
274849CRESCENT ;1U
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.137
276646AC1-214 GEN2
Solar/Wind Harmer
0.137
276741O09 GEN1
Solar/Wind Harmer
0.124
276708O09 GEN2
Solar/Wind Harmer
0.124
276782AC1-033 GEN
Solar/Wind Harmer
0.001
944541AF1-119 GEN
Solar/Wind Harmer
0.231
960971AF2-388 GEN
Solar/Wind Harmer
2.024
960611AF2-352 GEN
Solar/Wind Harmer
1.144
970241AG2-163 GEN
Solar/Wind Harmer
1.972
270201AC2-176 GEN
Solar/Wind Harmer
0.001
270599AE1-208 GEN
Solar/Wind Harmer
3.085
270031AE2-169
Solar/Wind Harmer
1.851
964611AG1-324 GEN
Solar/Wind Harmer
0.251
971613AH1-306 GEN
Solar/Wind Harmer
1.593
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
971231AH1-075 GEN
Solar/Wind Harmer
0.377
960441AF2-335 GEN
Solar/Wind Harmer
3.255
970825AG2-519 GEN
Solar/Wind Harmer
3.6
203947AF1-006 C
Solar/Wind Helper
0.391
203980AG1-197 GEN
Solar/Wind Helper
0.255
203979AG1-198 GEN
Solar/Wind Helper
0.198
241801AE1-079 GEN
Solar/Wind Helper
0.134
241967AE2-285_GEN
Solar/Wind Helper
0.345
241985AE1-237 GEN
Solar/Wind Helper
0.134
962101AG1-054 GEN
Solar/Wind Helper
0.332
946381AF1-302 GEN
Solar/Wind Helper
0.105
238217AF1-153 C O1
Solar/Wind Helper
0.111
991177J1571 G
External Queue
15.792752265930176
990527J1329
External Queue
2.0234405994415283
990142J1224
External Queue
14.791350364685059
991182J1586 G
External Queue
28.11846351623535
LAGNLTFEXP_LAGN->PJM
CLTF
6.061
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.4
TVALTFEXP_TVA->PJM
CLTF
2.775
CPLELTFEXP_CPLE->PJM
CLTF
0.731
CBM West 2LTFEXP_CBM-W2->PJM
CBM
47.539
NYPJM->LTFIMP_NY
CLTF
1.965
LGEELTFEXP_LGEE->PJM
CLTF
2.4
WECLTFEXP_WEC->PJM
CLTF
1.946
AG2-052LTFEXP_AG2-052->PJM
LTF
0.125
AH1-155LTFEXP_AH1-155->PJM
LTF
0.187
CBM West 1LTFEXP_CBM-W1->PJM
CBM
112.86
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.907
MECLTFEXP_MEC->PJM
CLTF
7.633
SIGELTFEXP_SIGE->PJM
CLTF
0.2

Details for 02BEAVER-02CARLIL 345.0 kV Ckt 1 line l/o ATSI_P7-1_OEC-345-002_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02BEAVER-02CARLIL 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P7-1_OEC-345-002_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:109.31 %
Rating:1745.0 MVA
Rating Type:B
MVA to Mitigate:1907.45
MW Contribution:11.15
Bus #Bus NameTypeMW Contribution
23867002DVBSG1
50/50
10.407
972211AH1-690 GEN
50/50
238.133
241886AC2-103 GEN2
Solar/Wind Harmer
14.419
24191202EL_AA1-006
Adder
0.297
970817AG2-515 GEN
Solar/Wind Harmer
13.044
945411AF1-206 GEN
Solar/Wind Harmer
7.213
270499AE1-146 GEN
Solar/Wind Harmer
2.343
945641AF1-229 GEN
Solar/Wind Harmer
3.229
970159AG2-109 GEN
Solar/Wind Harmer
3.418
270297AD1-101 GEN
Solar/Wind Harmer
1.75
971549AH1-272 GEN
Solar/Wind Harmer
11.155
966831AG1-554 GEN
Solar/Wind Harmer
0.704
971989AH1-539 GEN
Solar/Wind Harmer
7.613
971567AH1-282 GEN
Solar/Wind Harmer
8.024
247607V1-011 GEN
Solar/Wind Harmer
2.098
957201AF2-014 GEN
Solar/Wind Harmer
2.368
270435AC2-044 GEN
Solar/Wind Harmer
1.044
944161AF1-084 GEN
Solar/Wind Harmer
1.106
965041AG1-368 GEN
Solar/Wind Harmer
4.881
965051AG1-369 GEN
Solar/Wind Harmer
2.43
270302AB2-170 GEN
Solar/Wind Harmer
3.966
270317AD1-130_GEN
Solar/Wind Harmer
1.52
971219AH1-069 GEN
Solar/Wind Harmer
0.796
971771AH1-392 GEN
Solar/Wind Harmer
4.129
971769AH1-391 GEN
Solar/Wind Harmer
4.471
270578AF1-285 GEN2
Solar/Wind Harmer
0.204
970179AG2-119 GEN
Solar/Wind Harmer
3.495
963791AG1-232 GEN
Solar/Wind Harmer
5.807
960681AF2-359 GEN
Solar/Wind Harmer
1.625
241982AE2-343 S C
Solar/Wind Helper
0.109
254304AE2-114 C
Solar/Wind Helper
0.104
241997AF1-093 GEN
Solar/Wind Helper
0.121
23917402WLORG-5
50/50
1.527
23917102WLORG-2
50/50
1.505
966321AG1-501 GEN
50/50
1.834
957111AF2-005 GEN
50/50
1.467
24189902OREGON_CT2
50/50
2.208
23856402BAYSG1
50/50
1.196
241885AC2-103 GEN1
Solar/Wind Harmer
14.419
241807AE2-176_GEN
Solar/Wind Harmer
6.057
972253AH1-711 GEN
Adder
43.699
241858AF1-205_GEN
Solar/Wind Harmer
4.928
241808AF1-120 C
Solar/Wind Harmer
1.077
23920202STRYCT
Adder
1.608
241840AF1-064_GEN
Solar/Wind Harmer
1.274
972301AH1-735 GEN
Adder
5.944
23906402RICHG1
Adder
1.189
23906502RICHG2&3
Adder
1.187
270361_3
Solar/Wind Harmer
8.521
960841AF2-375 GEN
Solar/Wind Harmer
3.749
270428AC2-015 C
Solar/Wind Harmer
4.415
247522W1-056 GEN
Solar/Wind Harmer
1.589
970515AG2-329 GEN
Solar/Wind Harmer
10.227
970905AG2-564 GEN
Solar/Wind Harmer
3.497
944231AF1-091 GEN
Solar/Wind Harmer
2.19
241847AF2-150_GEN
Solar/Wind Harmer
2.294
246936BC-WTG1
Solar/Wind Harmer
2.043
270489AE1-102 GEN1
Solar/Wind Harmer
0.679
965421AG1-410 GEN
Solar/Wind Harmer
15.499
24695305TIMB G C
Solar/Wind Harmer
2.781
270449AD2-020 GEN
Solar/Wind Harmer
1.385
943021AE2-325 GEN
Solar/Wind Harmer
1.799
247521TR3_G114
Solar/Wind Harmer
1.636
270246TR4_N_V150
Solar/Wind Harmer
0.414
945111AF1-176 GEN
Solar/Wind Harmer
8.634
270505AE1-170 C O1
Solar/Wind Harmer
7.249
270462AD2-086
Solar/Wind Harmer
3.299
24639705ELKHART HY
Adder
0.072
270063AE2-323 C
Solar/Wind Harmer
1.038
971221AH1-070 GEN
Solar/Wind Harmer
0.796
965011AG1-365 GEN
Solar/Wind Harmer
4.645
241813AF1-122_GEN
Solar/Wind Harmer
2.935
270223U2-072_GEN1
Solar/Wind Harmer
0.868
270578AF1-285 GEN2
Solar/Wind Harmer
0.531
270391AF1-285 GEN3
Solar/Wind Harmer
0.531
961971AG1-040 GEN
Solar/Wind Helper
0.251
203835AF1-098 GEN
Solar/Wind Helper
0.992
241966AE1-183 GEN
Solar/Wind Helper
0.121
23917202WLORG-3
50/50
1.553
23917302WLORG-4
50/50
1.519
966311AG1-500 GEN
50/50
141.29
23857202WLORG-B
50/50
9.372
24190002OREGON_ST1
50/50
2.971
24189802OREGON_CT1
50/50
2.254
241996AE2-282_GEN
Solar/Wind Harmer
1.931
971677AH1-339 GEN
Solar/Wind Harmer
6.773
270007AE1-245 C
Solar/Wind Harmer
3.147
942801AE2-298 GEN
Solar/Wind Harmer
0.797
246938BC-WTG3
Solar/Wind Harmer
2.078
246937BC-WTG2
Solar/Wind Harmer
2.043
971231AH1-075 GEN
Solar/Wind Harmer
0.399
961051AF2-396 GEN
Solar/Wind Harmer
7.783
961051AF2-396 GEN
Solar/Wind Harmer
3.62
960981AF2-389 GEN
Solar/Wind Harmer
0.728
957071AF2-004 GEN
50/50
12.095
23917502WLORG-6
50/50
0.764
23857102WLORG-A
50/50
9.096
23929302BS-PKR
50/50
2.106
241832AE2-181_GEN
Solar/Wind Harmer
1.75
958321AF2-126 GEN
Solar/Wind Harmer
1.366
23906502RICHG2&3
Adder
1.187
270575GUS2 35KV
Solar/Wind Harmer
10.039
270541AE2-072 C
Solar/Wind Harmer
3.99
970217AG2-149 GEN
Solar/Wind Harmer
22.552
270588AE1-091_GEN
Solar/Wind Harmer
6.591
270044AE2-322 C
Solar/Wind Harmer
0.769
270404AC1-167 GEN
Solar/Wind Harmer
0.641
270258AD1-119 GEN
Solar/Wind Harmer
1.565
961961AG1-039 GEN
Solar/Wind Harmer
1.583
958091AF2-103 GEN
Solar/Wind Harmer
0.086
247604X1-042
Adder
0.22
270491AE1-102 GEN2
Solar/Wind Harmer
0.679
24441205WTRV SLR C
Solar/Wind Harmer
0.07
270377AD1-106 GEN
Solar/Wind Harmer
3.082
270191TR4_S_V150
Solar/Wind Harmer
1.46
270247TR4_N_V136
Solar/Wind Harmer
0.414
945111AF1-176 GEN
Solar/Wind Harmer
2.737
270485AE1-090_GEN
Solar/Wind Harmer
0.287
24642205MAYFLWER
Adder
0.299
970031AG2-029 GEN
Solar/Wind Harmer
14.083
247643Z2-116 C
Solar/Wind Harmer
0.032
959331AF2-224 GEN
Solar/Wind Harmer
4.645
965021AG1-366 GEN
Solar/Wind Harmer
1.08
970065AG2-057 GEN
Solar/Wind Harmer
0.459
942871AE2-306 GEN
Solar/Wind Harmer
0.398
270391AF1-285 GEN3
Solar/Wind Harmer
0.204
270043AE2-236 GEN
Solar/Wind Harmer
2.394
962511AG1-100 GEN
Solar/Wind Helper
0.255
203830AF1-094 GEN
Solar/Wind Helper
0.245
254305AE2-115 C
Solar/Wind Helper
0.104
959441AF2-235 GEN
Solar/Wind Helper
0.115
957891AF2-083 GEN
Solar/Wind Harmer
1.625
247620Y3-023
Adder
0.218
270216AD2-079_GEN
Solar/Wind Harmer
0.283
970611AG2-400 GEN
Solar/Wind Harmer
4.645
971201AH1-060 GEN
Solar/Wind Harmer
0.917
270526AF1-158 GEN
Solar/Wind Harmer
2.042
24441505OLIV SLR
Solar/Wind Harmer
0.06
270224U2-072_GEN2
Solar/Wind Harmer
0.868
270227U2-072_GEN3
Solar/Wind Harmer
0.868
270228U2-072_GEN4
Solar/Wind Harmer
0.868
270231U2-072_GEN5
Solar/Wind Harmer
0.868
241960AC2-195 GEN
Solar/Wind Harmer
1.215
965681AG1-436 GEN
Solar/Wind Harmer
5.376
965791AG1-447 GEN
Solar/Wind Harmer
2.75
203947AF1-006 C
Solar/Wind Helper
0.283
241967AE2-285_GEN
Solar/Wind Helper
0.314
241801AE1-079 GEN
Solar/Wind Helper
0.122
203980AG1-197 GEN
Solar/Wind Helper
0.188
241985AE1-237 GEN
Solar/Wind Helper
0.122
203979AG1-198 GEN
Solar/Wind Helper
0.147
962101AG1-054 GEN
Solar/Wind Helper
0.304
203860AG1-193 C
Solar/Wind Helper
0.116
254303AC2-168 GEN
Solar/Wind Helper
0.071
991177J1571 G
External Queue
13.065269470214844
990527J1329
External Queue
1.536989450454712
990142J1224
External Queue
11.235392570495605
LAGNLTFEXP_LAGN->PJM
CLTF
4.111
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.536
TVALTFEXP_TVA->PJM
CLTF
1.857
CPLELTFEXP_CPLE->PJM
CLTF
0.14
CBM West 2LTFEXP_CBM-W2->PJM
CBM
33.236
NYPJM->LTFIMP_NY
CLTF
1.797
LGEELTFEXP_LGEE->PJM
CLTF
1.709
WECLTFEXP_WEC->PJM
CLTF
1.408
AG2-052LTFEXP_AG2-052->PJM
LTF
0.091
AH1-155LTFEXP_AH1-155->PJM
LTF
0.136
CBM West 1LTFEXP_CBM-W1->PJM
CBM
79.335
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.4
MECLTFEXP_MEC->PJM
CLTF
5.472
SIGELTFEXP_SIGE->PJM
CLTF
0.142

Details for 02BEAVER-02LAKEAVE 345.0 kV Ckt 1 line l/o ATSI_P2-3_OEC-345-901_SRT-SL


Base Case Flowgate

Area:ATSI
Facility Description:
02BEAVER-02LAKEAVE 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_OEC-345-901_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.76 %
Rating:1720.0 MVA
Rating Type:B
MVA to Mitigate:1956.7
MW Contribution:10.15
Bus #Bus NameTypeMW Contribution
957071AF2-004 GEN
50/50
10.742
23929302BS-PKR
50/50
1.836
241832AE2-181_GEN
Solar/Wind Harmer
1.539
958321AF2-126 GEN
Solar/Wind Harmer
1.2
23906502RICHG2&3
Adder
1.05
270575GUS2 35KV
Solar/Wind Harmer
8.781
23857102WLORG-A
Adder
4.299
270541AE2-072 C
Solar/Wind Harmer
3.537
970217AG2-149 GEN
Solar/Wind Harmer
19.929
270588AE1-091_GEN
Solar/Wind Harmer
5.941
270044AE2-322 C
Solar/Wind Harmer
0.699
270404AC1-167 GEN
Solar/Wind Harmer
0.582
270258AD1-119 GEN
Solar/Wind Harmer
1.426
958091AF2-103 GEN
Solar/Wind Harmer
0.078
247604X1-042
Adder
0.202
23917402WLORG-5
50/50
1.356
23917102WLORG-2
50/50
1.337
24189902OREGON_CT2
50/50
1.94
23856402BAYSG1
50/50
1.043
241885AC2-103 GEN1
Solar/Wind Harmer
12.757
241807AE2-176_GEN
Solar/Wind Harmer
5.062
972253AH1-711 GEN
Adder
38.383
241858AF1-205_GEN
Solar/Wind Harmer
4.326
241808AF1-120 C
Solar/Wind Harmer
0.946
23920202STRYCT
Adder
1.415
241840AF1-064_GEN
Solar/Wind Harmer
1.119
972301AH1-735 GEN
Adder
5.258
23906402RICHG1
Adder
1.052
23906502RICHG2&3
Adder
1.05
270361_3
Solar/Wind Harmer
7.454
960841AF2-375 GEN
Solar/Wind Harmer
3.283
966321AG1-501 GEN
Adder
0.867
957111AF2-005 GEN
Adder
0.693
270428AC2-015 C
Solar/Wind Harmer
3.75
247522W1-056 GEN
Solar/Wind Harmer
1.41
970515AG2-329 GEN
Solar/Wind Harmer
9.037
970905AG2-564 GEN
Solar/Wind Harmer
2.954
944231AF1-091 GEN
Solar/Wind Harmer
1.993
241847AF2-150_GEN
Solar/Wind Harmer
1.989
246936BC-WTG1
Solar/Wind Harmer
1.873
270489AE1-102 GEN1
Solar/Wind Harmer
0.622
965421AG1-410 GEN
Solar/Wind Harmer
14.219
24695305TIMB G C
Solar/Wind Harmer
2.555
270449AD2-020 GEN
Solar/Wind Harmer
1.277
943021AE2-325 GEN
Solar/Wind Harmer
1.659
247521TR3_G114
Solar/Wind Harmer
1.508
270246TR4_N_V150
Solar/Wind Harmer
0.381
945111AF1-176 GEN
Solar/Wind Harmer
7.974
270505AE1-170 C O1
Solar/Wind Harmer
6.696
270462AD2-086
Solar/Wind Harmer
3.05
24639705ELKHART HY
Adder
0.067
270063AE2-323 C
Solar/Wind Harmer
0.96
965011AG1-365 GEN
Solar/Wind Harmer
4.301
961971AG1-040 GEN
Solar/Wind Helper
0.397
203835AF1-098 GEN
Solar/Wind Helper
1.566
203860AG1-193 C
Solar/Wind Helper
0.172
241966AE1-183 GEN
Solar/Wind Helper
0.118
203954AE2-126 C
Solar/Wind Helper
0.23
254303AC2-168 GEN
Solar/Wind Helper
0.068
961961AG1-039 GEN
Solar/Wind Harmer
1.372
270491AE1-102 GEN2
Solar/Wind Harmer
0.622
24441205WTRV SLR C
Solar/Wind Harmer
0.064
270377AD1-106 GEN
Solar/Wind Harmer
2.793
270191TR4_S_V150
Solar/Wind Harmer
1.345
270247TR4_N_V136
Solar/Wind Harmer
0.381
945111AF1-176 GEN
Solar/Wind Harmer
2.527
270485AE1-090_GEN
Solar/Wind Harmer
0.265
24642205MAYFLWER
Adder
0.277
970031AG2-029 GEN
Solar/Wind Harmer
13.034
247643Z2-116 C
Solar/Wind Harmer
0.03
959331AF2-224 GEN
Solar/Wind Harmer
4.301
965021AG1-366 GEN
Solar/Wind Harmer
1
962511AG1-100 GEN
Solar/Wind Helper
0.409
203830AF1-094 GEN
Solar/Wind Helper
0.382
959441AF2-235 GEN
Solar/Wind Helper
0.168
20334926Z1-069 C
Solar/Wind Helper
0.688
254305AE2-115 C
Solar/Wind Helper
0.102
23867002DVBSG1
50/50
9.149
972211AH1-690 GEN
50/50
209.151
241886AC2-103 GEN2
Solar/Wind Harmer
12.757
970817AG2-515 GEN
Solar/Wind Harmer
11.458
24191202EL_AA1-006
Adder
0.247
945411AF1-206 GEN
Solar/Wind Harmer
6.338
270499AE1-146 GEN
Solar/Wind Harmer
2.056
945641AF1-229 GEN
Solar/Wind Harmer
2.848
970159AG2-109 GEN
Solar/Wind Harmer
2.554
270297AD1-101 GEN
Solar/Wind Harmer
1.58
971549AH1-272 GEN
Solar/Wind Harmer
10.147
966831AG1-554 GEN
Solar/Wind Harmer
0.634
971989AH1-539 GEN
Solar/Wind Harmer
6.852
247607V1-011 GEN
Solar/Wind Harmer
1.919
971567AH1-282 GEN
Solar/Wind Harmer
7.189
957201AF2-014 GEN
Solar/Wind Harmer
2.171
270435AC2-044 GEN
Solar/Wind Harmer
0.957
944161AF1-084 GEN
Solar/Wind Harmer
1.019
965041AG1-368 GEN
Solar/Wind Harmer
4.498
965051AG1-369 GEN
Solar/Wind Harmer
2.239
270302AB2-170 GEN
Solar/Wind Harmer
3.666
270317AD1-130_GEN
Solar/Wind Harmer
1.405
203846AF2-130 C
Solar/Wind Helper
0.272
203804AE2-113_GEN
Solar/Wind Helper
0.933
241982AE2-343 S C
Solar/Wind Helper
0.107
254304AE2-114 C
Solar/Wind Helper
0.102
241997AF1-093 GEN
Solar/Wind Helper
0.118
23917202WLORG-3
50/50
1.38
23917302WLORG-4
50/50
1.349
966311AG1-500 GEN
50/50
125.486
24190002OREGON_ST1
50/50
2.61
24189802OREGON_CT1
50/50
1.98
241996AE2-282_GEN
Solar/Wind Harmer
1.697
23857202WLORG-B
Adder
4.429
971677AH1-339 GEN
Solar/Wind Harmer
5.947
270007AE1-245 C
Solar/Wind Harmer
2.879
942801AE2-298 GEN
Solar/Wind Harmer
0.729
246938BC-WTG3
Solar/Wind Harmer
1.905
246937BC-WTG2
Solar/Wind Harmer
1.873
961051AF2-396 GEN
Solar/Wind Harmer
7.181
961051AF2-396 GEN
Solar/Wind Harmer
3.34
971231AH1-075 GEN
Solar/Wind Harmer
0.362
960981AF2-389 GEN
Solar/Wind Harmer
0.673
957891AF2-083 GEN
Solar/Wind Harmer
1.501
247620Y3-023
Adder
0.202
270216AD2-079_GEN
Solar/Wind Harmer
0.262
970611AG2-400 GEN
Solar/Wind Harmer
4.301
203947AF1-006 C
Solar/Wind Helper
0.458
203980AG1-197 GEN
Solar/Wind Helper
0.296
203979AG1-198 GEN
Solar/Wind Helper
0.229
241967AE2-285_GEN
Solar/Wind Helper
0.308
241801AE1-079 GEN
Solar/Wind Helper
0.12
241985AE1-237 GEN
Solar/Wind Helper
0.119
946381AF1-302 GEN
Solar/Wind Helper
0.11
238217AF1-153 C O1
Solar/Wind Helper
0.118
962101AG1-054 GEN
Solar/Wind Helper
0.295
991177J1571 G
External Queue
11.149422645568848
990527J1329
External Queue
1.3126888275146484
990142J1224
External Queue
9.595755577087402
LAGNLTFEXP_LAGN->PJM
CLTF
4.111
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.004
TVALTFEXP_TVA->PJM
CLTF
1.884
CPLELTFEXP_CPLE->PJM
CLTF
0.338
CBM West 2LTFEXP_CBM-W2->PJM
CBM
32.563
NYPJM->LTFIMP_NY
CLTF
1.974
LGEELTFEXP_LGEE->PJM
CLTF
1.688
WECLTFEXP_WEC->PJM
CLTF
1.329
AG2-052LTFEXP_AG2-052->PJM
LTF
0.085
AH1-155LTFEXP_AH1-155->PJM
LTF
0.128
CBM West 1LTFEXP_CBM-W1->PJM
CBM
72.576
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.464
MECLTFEXP_MEC->PJM
CLTF
5.219
SIGELTFEXP_SIGE->PJM
CLTF
0.139

Details for 02BEAVER-02LAKEAVE 345.0 kV Ckt 1 line l/o ATSI_P2-3_OEC-345-007A_SRT-SL


Base Case Flowgate

Area:ATSI
Facility Description:
02BEAVER-02LAKEAVE 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_OEC-345-007A_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.78 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:1967.82
MW Contribution:10.19
Bus #Bus NameTypeMW Contribution
957071AF2-004 GEN
50/50
11.332
23929302BS-PKR
Adder
1.735
241832AE2-181_GEN
Solar/Wind Harmer
1.549
958321AF2-126 GEN
Solar/Wind Harmer
1.204
23906502RICHG2&3
Adder
1.054
270575GUS2 35KV
Solar/Wind Harmer
8.659
270541AE2-072 C
Solar/Wind Harmer
3.532
970217AG2-149 GEN
Solar/Wind Harmer
19.363
270588AE1-091_GEN
Solar/Wind Harmer
5.847
270044AE2-322 C
Solar/Wind Harmer
0.698
270404AC1-167 GEN
Solar/Wind Harmer
0.581
270258AD1-119 GEN
Solar/Wind Harmer
1.423
247604X1-042
Adder
0.202
958091AF2-103 GEN
Solar/Wind Harmer
0.078
270491AE1-102 GEN2
Solar/Wind Harmer
0.62
24441205WTRV SLR C
Solar/Wind Harmer
0.064
945111AF1-176 GEN
Solar/Wind Harmer
2.531
270191TR4_S_V150
Solar/Wind Harmer
1.341
270247TR4_N_V136
Solar/Wind Harmer
0.38
961961AG1-039 GEN
Solar/Wind Harmer
1.258
24642205MAYFLWER
Adder
0.277
270377AD1-106 GEN
Solar/Wind Harmer
2.69
270485AE1-090_GEN
Solar/Wind Harmer
0.263
970031AG2-029 GEN
Solar/Wind Harmer
13.034
247643Z2-116 C
Solar/Wind Harmer
0.03
962511AG1-100 GEN
Solar/Wind Helper
0.406
203830AF1-094 GEN
Solar/Wind Helper
0.379
959441AF2-235 GEN
Solar/Wind Helper
0.167
20334926Z1-069 C
Solar/Wind Helper
0.684
254305AE2-115 C
Solar/Wind Helper
0.101
23917402WLORG-5
50/50
1.431
23917102WLORG-2
50/50
1.41
24189902OREGON_CT2
50/50
1.967
241885AC2-103 GEN1
Solar/Wind Harmer
13.312
241807AE2-176_GEN
Solar/Wind Harmer
4.79
972253AH1-711 GEN
Adder
38.846
241858AF1-205_GEN
Solar/Wind Harmer
4.354
241808AF1-120 C
Solar/Wind Harmer
0.952
23920202STRYCT
Adder
1.423
241840AF1-064_GEN
Solar/Wind Harmer
1.123
972301AH1-735 GEN
Adder
5.278
23906402RICHG1
Adder
1.056
23906502RICHG2&3
Adder
1.054
270361_3
Solar/Wind Harmer
7.35
960841AF2-375 GEN
Solar/Wind Harmer
3.239
270428AC2-015 C
Solar/Wind Harmer
3.47
247522W1-056 GEN
Solar/Wind Harmer
1.38
970515AG2-329 GEN
Solar/Wind Harmer
8.781
970905AG2-564 GEN
Solar/Wind Harmer
2.663
944231AF1-091 GEN
Solar/Wind Harmer
1.994
246936BC-WTG1
Solar/Wind Harmer
1.867
270489AE1-102 GEN1
Solar/Wind Harmer
0.62
965421AG1-410 GEN
Solar/Wind Harmer
14.177
24695305TIMB G C
Solar/Wind Harmer
2.547
270449AD2-020 GEN
Solar/Wind Harmer
1.279
943021AE2-325 GEN
Solar/Wind Harmer
1.662
945111AF1-176 GEN
Solar/Wind Harmer
7.986
247521TR3_G114
Solar/Wind Harmer
1.503
270246TR4_N_V150
Solar/Wind Harmer
0.38
270505AE1-170 C O1
Solar/Wind Harmer
6.706
241847AF2-150_GEN
Solar/Wind Harmer
1.823
24639705ELKHART HY
Adder
0.067
270063AE2-323 C
Solar/Wind Harmer
0.96
270462AD2-086
Solar/Wind Harmer
3.029
961971AG1-040 GEN
Solar/Wind Helper
0.395
203835AF1-098 GEN
Solar/Wind Helper
1.556
203860AG1-193 C
Solar/Wind Helper
0.17
241966AE1-183 GEN
Solar/Wind Helper
0.117
203954AE2-126 C
Solar/Wind Helper
0.228
254303AC2-168 GEN
Solar/Wind Helper
0.067
23917202WLORG-3
50/50
1.455
23917302WLORG-4
50/50
1.423
966311AG1-500 GEN
50/50
132.376
24190002OREGON_ST1
50/50
2.646
24189802OREGON_CT1
50/50
2.007
241996AE2-282_GEN
Solar/Wind Harmer
1.708
971677AH1-339 GEN
Solar/Wind Harmer
5.827
270007AE1-245 C
Solar/Wind Harmer
2.868
942801AE2-298 GEN
Solar/Wind Harmer
0.727
246938BC-WTG3
Solar/Wind Harmer
1.899
246937BC-WTG2
Solar/Wind Harmer
1.867
961051AF2-396 GEN
Solar/Wind Harmer
7.193
961051AF2-396 GEN
Solar/Wind Harmer
3.346
960981AF2-389 GEN
Solar/Wind Harmer
0.674
957891AF2-083 GEN
Solar/Wind Harmer
1.504
247620Y3-023
Adder
0.202
971231AH1-075 GEN
Solar/Wind Harmer
0.349
270216AD2-079_GEN
Solar/Wind Harmer
0.262
203947AF1-006 C
Solar/Wind Helper
0.455
203980AG1-197 GEN
Solar/Wind Helper
0.294
203979AG1-198 GEN
Solar/Wind Helper
0.227
241801AE1-079 GEN
Solar/Wind Helper
0.119
241967AE2-285_GEN
Solar/Wind Helper
0.305
241985AE1-237 GEN
Solar/Wind Helper
0.118
946381AF1-302 GEN
Solar/Wind Helper
0.109
238217AF1-153 C O1
Solar/Wind Helper
0.117
962101AG1-054 GEN
Solar/Wind Helper
0.293
23867002DVBSG1
50/50
9.378
972211AH1-690 GEN
50/50
212.091
241886AC2-103 GEN2
Solar/Wind Harmer
13.312
970817AG2-515 GEN
Solar/Wind Harmer
11.575
945411AF1-206 GEN
Solar/Wind Harmer
6.379
24191202EL_AA1-006
Adder
0.223
270499AE1-146 GEN
Solar/Wind Harmer
2.029
945641AF1-229 GEN
Solar/Wind Harmer
2.819
270297AD1-101 GEN
Solar/Wind Harmer
1.573
971549AH1-272 GEN
Solar/Wind Harmer
10.193
966831AG1-554 GEN
Solar/Wind Harmer
0.62
971989AH1-539 GEN
Solar/Wind Harmer
6.706
247607V1-011 GEN
Solar/Wind Harmer
1.912
957201AF2-014 GEN
Solar/Wind Harmer
2.164
270435AC2-044 GEN
Solar/Wind Harmer
0.954
944161AF1-084 GEN
Solar/Wind Harmer
1.021
971567AH1-282 GEN
Solar/Wind Harmer
6.891
970159AG2-109 GEN
Solar/Wind Harmer
1.835
965041AG1-368 GEN
Solar/Wind Harmer
4.486
965051AG1-369 GEN
Solar/Wind Harmer
2.232
270302AB2-170 GEN
Solar/Wind Harmer
3.641
270317AD1-130_GEN
Solar/Wind Harmer
1.396
203846AF2-130 C
Solar/Wind Helper
0.27
203804AE2-113_GEN
Solar/Wind Helper
0.928
241982AE2-343 S C
Solar/Wind Helper
0.106
254304AE2-114 C
Solar/Wind Helper
0.101
241997AF1-093 GEN
Solar/Wind Helper
0.117
991177J1571 G
External Queue
11.313738822937012
990527J1329
External Queue
1.333598017692566
990142J1224
External Queue
9.748601913452148
LAGNLTFEXP_LAGN->PJM
CLTF
4.085
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.967
TVALTFEXP_TVA->PJM
CLTF
1.87
CPLELTFEXP_CPLE->PJM
CLTF
0.326
CBM West 2LTFEXP_CBM-W2->PJM
CBM
32.394
NYPJM->LTFIMP_NY
CLTF
1.964
LGEELTFEXP_LGEE->PJM
CLTF
1.675
WECLTFEXP_WEC->PJM
CLTF
1.327
AG2-052LTFEXP_AG2-052->PJM
LTF
0.085
AH1-155LTFEXP_AH1-155->PJM
LTF
0.128
CBM West 1LTFEXP_CBM-W1->PJM
CBM
72.887
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.407
MECLTFEXP_MEC->PJM
CLTF
5.205
SIGELTFEXP_SIGE->PJM
CLTF
0.138

Details for 02BEAVER-02LAKEAVE 345.0 kV Ckt 1 line l/o ATSI_P2-3_OEC-345-031_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02BEAVER-02LAKEAVE 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_OEC-345-031_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.84 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:1893.72
MW Contribution:10.06
Bus #Bus NameTypeMW Contribution
23917402WLORG-5
50/50
1.318
23917102WLORG-2
50/50
1.299
24189902OREGON_CT2
50/50
1.916
23856402BAYSG1
50/50
1.035
241885AC2-103 GEN1
Solar/Wind Harmer
12.452
241807AE2-176_GEN
Solar/Wind Harmer
5.144
972253AH1-711 GEN
Adder
37.939
241858AF1-205_GEN
Solar/Wind Harmer
4.286
241808AF1-120 C
Solar/Wind Harmer
0.937
23920202STRYCT
Adder
1.402
241840AF1-064_GEN
Solar/Wind Harmer
1.11
966321AG1-501 GEN
Adder
1.036
957111AF2-005 GEN
Adder
0.829
972301AH1-735 GEN
Adder
5.214
23906402RICHG1
Adder
1.043
23906502RICHG2&3
Adder
1.042
270361_3
Solar/Wind Harmer
7.442
960841AF2-375 GEN
Solar/Wind Harmer
3.277
270428AC2-015 C
Solar/Wind Harmer
3.83
247522W1-056 GEN
Solar/Wind Harmer
1.411
970515AG2-329 GEN
Solar/Wind Harmer
9.065
970905AG2-564 GEN
Solar/Wind Harmer
3.041
944231AF1-091 GEN
Solar/Wind Harmer
1.98
241847AF2-150_GEN
Solar/Wind Harmer
2.034
246936BC-WTG1
Solar/Wind Harmer
1.863
270489AE1-102 GEN1
Solar/Wind Harmer
0.619
965421AG1-410 GEN
Solar/Wind Harmer
14.14
24695305TIMB G C
Solar/Wind Harmer
2.541
270449AD2-020 GEN
Solar/Wind Harmer
1.268
943021AE2-325 GEN
Solar/Wind Harmer
1.647
247521TR3_G114
Solar/Wind Harmer
1.5
270246TR4_N_V150
Solar/Wind Harmer
0.379
945111AF1-176 GEN
Solar/Wind Harmer
7.917
270505AE1-170 C O1
Solar/Wind Harmer
6.647
270462AD2-086
Solar/Wind Harmer
3.037
24639705ELKHART HY
Adder
0.066
270063AE2-323 C
Solar/Wind Harmer
0.954
961971AG1-040 GEN
Solar/Wind Helper
0.397
203835AF1-098 GEN
Solar/Wind Helper
1.564
203860AG1-193 C
Solar/Wind Helper
0.171
241966AE1-183 GEN
Solar/Wind Helper
0.118
203954AE2-126 C
Solar/Wind Helper
0.229
254303AC2-168 GEN
Solar/Wind Helper
0.068
23867002DVBSG1
50/50
8.998
972211AH1-690 GEN
50/50
206.563
24191202EL_AA1-006
50/50
0.275
241886AC2-103 GEN2
Solar/Wind Harmer
12.452
970817AG2-515 GEN
Solar/Wind Harmer
11.334
945411AF1-206 GEN
Solar/Wind Harmer
6.279
270499AE1-146 GEN
Solar/Wind Harmer
2.052
945641AF1-229 GEN
Solar/Wind Harmer
2.838
970159AG2-109 GEN
Solar/Wind Harmer
2.868
270297AD1-101 GEN
Solar/Wind Harmer
1.572
971549AH1-272 GEN
Solar/Wind Harmer
10.061
966831AG1-554 GEN
Solar/Wind Harmer
0.634
971989AH1-539 GEN
Solar/Wind Harmer
6.861
971567AH1-282 GEN
Solar/Wind Harmer
7.246
247607V1-011 GEN
Solar/Wind Harmer
1.909
957201AF2-014 GEN
Solar/Wind Harmer
2.159
270435AC2-044 GEN
Solar/Wind Harmer
0.952
944161AF1-084 GEN
Solar/Wind Harmer
1.011
965041AG1-368 GEN
Solar/Wind Harmer
4.473
965051AG1-369 GEN
Solar/Wind Harmer
2.227
270302AB2-170 GEN
Solar/Wind Harmer
3.651
270317AD1-130_GEN
Solar/Wind Harmer
1.4
203846AF2-130 C
Solar/Wind Helper
0.271
203804AE2-113_GEN
Solar/Wind Helper
0.931
241982AE2-343 S C
Solar/Wind Helper
0.107
254304AE2-114 C
Solar/Wind Helper
0.102
241997AF1-093 GEN
Solar/Wind Helper
0.118
957071AF2-004 GEN
50/50
10.437
23929302BS-PKR
50/50
1.821
241832AE2-181_GEN
Solar/Wind Harmer
1.524
958321AF2-126 GEN
Solar/Wind Harmer
1.19
23857102WLORG-A
Adder
5.14
23906502RICHG2&3
Adder
1.042
270575GUS2 35KV
Solar/Wind Harmer
8.767
270541AE2-072 C
Solar/Wind Harmer
3.515
970217AG2-149 GEN
Solar/Wind Harmer
19.989
270588AE1-091_GEN
Solar/Wind Harmer
5.936
270044AE2-322 C
Solar/Wind Harmer
0.695
270404AC1-167 GEN
Solar/Wind Harmer
0.579
270258AD1-119 GEN
Solar/Wind Harmer
1.418
961961AG1-039 GEN
Solar/Wind Harmer
1.403
958091AF2-103 GEN
Solar/Wind Harmer
0.078
247604X1-042
Adder
0.2
270491AE1-102 GEN2
Solar/Wind Harmer
0.619
24441205WTRV SLR C
Solar/Wind Harmer
0.064
270377AD1-106 GEN
Solar/Wind Harmer
2.813
270191TR4_S_V150
Solar/Wind Harmer
1.338
270247TR4_N_V136
Solar/Wind Harmer
0.379
945111AF1-176 GEN
Solar/Wind Harmer
2.509
270485AE1-090_GEN
Solar/Wind Harmer
0.264
24642205MAYFLWER
Adder
0.275
970031AG2-029 GEN
Solar/Wind Harmer
12.948
962511AG1-100 GEN
Solar/Wind Helper
0.408
203830AF1-094 GEN
Solar/Wind Helper
0.381
959441AF2-235 GEN
Solar/Wind Helper
0.168
20334926Z1-069 C
Solar/Wind Helper
0.686
254305AE2-115 C
Solar/Wind Helper
0.102
23917202WLORG-3
50/50
1.34
23917302WLORG-4
50/50
1.311
966311AG1-500 GEN
50/50
121.92
24190002OREGON_ST1
50/50
2.577
24189802OREGON_CT1
50/50
1.955
241996AE2-282_GEN
Solar/Wind Harmer
1.681
23857202WLORG-B
Adder
5.296
971677AH1-339 GEN
Solar/Wind Harmer
5.951
270007AE1-245 C
Solar/Wind Harmer
2.864
942801AE2-298 GEN
Solar/Wind Harmer
0.726
246938BC-WTG3
Solar/Wind Harmer
1.895
246937BC-WTG2
Solar/Wind Harmer
1.863
971231AH1-075 GEN
Solar/Wind Harmer
0.364
961051AF2-396 GEN
Solar/Wind Harmer
7.128
961051AF2-396 GEN
Solar/Wind Harmer
3.316
960981AF2-389 GEN
Solar/Wind Harmer
0.668
957891AF2-083 GEN
Solar/Wind Harmer
1.491
247620Y3-023
Adder
0.2
203947AF1-006 C
Solar/Wind Helper
0.458
203980AG1-197 GEN
Solar/Wind Helper
0.295
203979AG1-198 GEN
Solar/Wind Helper
0.229
241801AE1-079 GEN
Solar/Wind Helper
0.119
241967AE2-285_GEN
Solar/Wind Helper
0.307
241985AE1-237 GEN
Solar/Wind Helper
0.119
946381AF1-302 GEN
Solar/Wind Helper
0.11
238217AF1-153 C O1
Solar/Wind Helper
0.117
962101AG1-054 GEN
Solar/Wind Helper
0.294
991177J1571 G
External Queue
11.006390571594238
990527J1329
External Queue
1.2952468395233154
990142J1224
External Queue
9.468253135681152
LAGNLTFEXP_LAGN->PJM
CLTF
4.096
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.011
TVALTFEXP_TVA->PJM
CLTF
1.879
CPLELTFEXP_CPLE->PJM
CLTF
0.342
CBM West 2LTFEXP_CBM-W2->PJM
CBM
32.428
NYPJM->LTFIMP_NY
CLTF
1.967
LGEELTFEXP_LGEE->PJM
CLTF
1.683
WECLTFEXP_WEC->PJM
CLTF
1.321
AG2-052LTFEXP_AG2-052->PJM
LTF
0.085
AH1-155LTFEXP_AH1-155->PJM
LTF
0.127
CBM West 1LTFEXP_CBM-W1->PJM
CBM
71.973
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.443
MECLTFEXP_MEC->PJM
CLTF
5.19
SIGELTFEXP_SIGE->PJM
CLTF
0.138

Details for 02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line l/o ATSI_P2-3_OEC-345-002_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line
Contingency Name:
ATSI_P2-3_OEC-345-002_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:174.17 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:3270.93
MW Contribution:14.21
Bus #Bus NameTypeMW Contribution
23917402WLORG-5
50/50
1.92
23917102WLORG-2
50/50
1.892
24189902OREGON_CT2
50/50
2.76
23856402BAYSG1
50/50
1.489
241885AC2-103 GEN1
Solar/Wind Harmer
18.089
241807AE2-176_GEN
Solar/Wind Harmer
7.368
972253AH1-711 GEN
Adder
54.605
241858AF1-205_GEN
Solar/Wind Harmer
6.156
966321AG1-501 GEN
Adder
1.655
957071AF2-004 GEN
50/50
15.205
23929302BS-PKR
50/50
2.62
23857102WLORG-A
Adder
8.207
241832AE2-181_GEN
Solar/Wind Harmer
2.188
958321AF2-126 GEN
Solar/Wind Harmer
1.707
23906502RICHG2&3
Adder
1.489
270575GUS2 35KV
Solar/Wind Harmer
12.516
270541AE2-072 C
Solar/Wind Harmer
5.011
970217AG2-149 GEN
Solar/Wind Harmer
28.273
270588AE1-091_GEN
Solar/Wind Harmer
8.353
270044AE2-322 C
Solar/Wind Harmer
0.979
270404AC1-167 GEN
Solar/Wind Harmer
0.816
270258AD1-119 GEN
Solar/Wind Harmer
1.996
961961AG1-039 GEN
Solar/Wind Harmer
1.964
958091AF2-103 GEN
Solar/Wind Harmer
0.109
247604X1-042
Adder
0.282
270491AE1-102 GEN2
Solar/Wind Harmer
0.868
24441205WTRV SLR C
Solar/Wind Harmer
0.089
270377AD1-106 GEN
Solar/Wind Harmer
3.918
270191TR4_S_V150
Solar/Wind Harmer
1.873
270247TR4_N_V136
Solar/Wind Harmer
0.531
945111AF1-176 GEN
Solar/Wind Harmer
3.515
270485AE1-090_GEN
Solar/Wind Harmer
0.369
24642205MAYFLWER
Adder
0.384
970031AG2-029 GEN
Solar/Wind Harmer
18.113
247643Z2-116 C
Solar/Wind Harmer
0.042
959331AF2-224 GEN
Solar/Wind Harmer
5.975
965021AG1-366 GEN
Solar/Wind Harmer
1.39
970065AG2-057 GEN
Solar/Wind Harmer
0.575
942871AE2-306 GEN
Solar/Wind Harmer
0.514
270391AF1-285 GEN3
Solar/Wind Harmer
0.264
270043AE2-236 GEN
Solar/Wind Harmer
3.089
970349AG2-230 GEN
Solar/Wind Harmer
8.3
270535AF1-215 GEN1
Solar/Wind Harmer
2.387
972231SS25-0005
Solar/Wind Harmer
4.917
972181SS23-001
Solar/Wind Harmer
3.073
274752CRETE EC ;2U
Adder
2.532
274753CRETE EC ;3U
Adder
2.532
964401AG1-302 GEN
Solar/Wind Harmer
4.687
274724RIVER EC ;11
Adder
9.105
959141AF2-205 GEN
Solar/Wind Harmer
3.076
274802UNIV PARK;5U
Adder
2.953
274826FISK ;BP
Adder
5.536
274800UNIV PARK;3U
Adder
2.944
972038AH1-567 GEN2
Adder
0.184
276772AC2-154 GEN
Solar/Wind Harmer
1.406
276806AD2-047 C O1
Solar/Wind Harmer
5.394
970941AG2-585 GEN
Solar/Wind Harmer
6.303
274772LINCOLN ;3U
Adder
3.125
971617AH1-308 GEN
Solar/Wind Harmer
2.93
972228AH1-698 GEN2
Adder
1.862
274676JOLIET 29;8U
Adder
14.797
276897AD1-100 C
Solar/Wind Harmer
14.503
939351AE1-166 GEN
Solar/Wind Harmer
2.963
276893AG1-478 C
Solar/Wind Harmer
0.209
970707AG2-453 GEN
Solar/Wind Harmer
13.981
274729ELWOOD EC;1P
Adder
8.208
274730ELWOOD EC;6P
Adder
8.208
274734ELWOOD EC;8P
Adder
8.208
274736ELWOOD EC;9P
Adder
8.208
970513AG2-328 GEN
Solar/Wind Harmer
8.906
970517AG2-330 GEN
Solar/Wind Harmer
8.078
274682WAUKEGAN ;7U
Adder
8.816
972236AH1-702 GEN2
Adder
1.051
274760LEE CO EC;1U
Adder
4.416
962511AG1-100 GEN
Solar/Wind Helper
0.462
203830AF1-094 GEN
Solar/Wind Helper
0.435
959441AF2-235 GEN
Solar/Wind Helper
0.196
254305AE2-115 C
Solar/Wind Helper
0.138
20334926Z1-069 C
Solar/Wind Helper
0.837
203854AF2-039 C
Solar/Wind Helper
0.18
203818AF1-086 GEN
Solar/Wind Helper
0.912
238202AE2-262_GEN
Solar/Wind Helper
0.528
941421AE2-139 GEN
Solar/Wind Helper
1.203
235058AG1-386 C
Solar/Wind Helper
0.205
200917MEHOOPANY_G
Solar/Wind Helper
1.091
23867002DVBSG1
50/50
13.011
972211AH1-690 GEN
50/50
297.552
241886AC2-103 GEN2
Solar/Wind Harmer
18.089
24191202EL_AA1-006
Adder
0.36
970817AG2-515 GEN
Solar/Wind Harmer
16.3
945411AF1-206 GEN
Solar/Wind Harmer
9.015
270499AE1-146 GEN
Solar/Wind Harmer
2.926
945641AF1-229 GEN
Solar/Wind Harmer
4.044
970159AG2-109 GEN
Solar/Wind Harmer
3.924
270297AD1-101 GEN
Solar/Wind Harmer
2.22
971549AH1-272 GEN
Solar/Wind Harmer
14.209
966831AG1-554 GEN
Solar/Wind Harmer
0.892
971989AH1-539 GEN
Solar/Wind Harmer
9.641
247607V1-011 GEN
Solar/Wind Harmer
2.681
971567AH1-282 GEN
Solar/Wind Harmer
10.136
957201AF2-014 GEN
Solar/Wind Harmer
3.029
270435AC2-044 GEN
Solar/Wind Harmer
1.336
944161AF1-084 GEN
Solar/Wind Harmer
1.419
965041AG1-368 GEN
Solar/Wind Harmer
6.263
965051AG1-369 GEN
Solar/Wind Harmer
3.117
270302AB2-170 GEN
Solar/Wind Harmer
5.097
270317AD1-130_GEN
Solar/Wind Harmer
1.954
971771AH1-392 GEN
Solar/Wind Harmer
5.317
971769AH1-391 GEN
Solar/Wind Harmer
5.763
270578AF1-285 GEN2
Solar/Wind Harmer
0.264
960681AF2-359 GEN
Solar/Wind Harmer
2.098
963791AG1-232 GEN
Solar/Wind Harmer
7.497
971347AH1-153 GEN
Solar/Wind Harmer
8.3
970179AG2-119 GEN
Solar/Wind Harmer
4.411
971219AH1-069 GEN
Solar/Wind Harmer
0.907
270536AF1-215 GEN2
Solar/Wind Harmer
2.387
270071AF1-092 GEN
Solar/Wind Harmer
7.858
958391AF2-133 GEN
Solar/Wind Harmer
4.646
274814UNIV PK N;0U
Adder
2.586
274807UNIV PK N;3U
Adder
2.581
274805UNIV PK N;1U
Adder
2.569
274811UNIV PK N;7U
Adder
2.564
972037AH1-567 GEN1
Adder
0.093
274827FISK ;RP
Adder
3.924
960591AF2-350 GEN
Solar/Wind Harmer
5.042
274775LINCOLN ;6U
Adder
3.125
274776LINCOLN ;7U
Adder
3.125
274777LINCOLN ;8U
Adder
3.125
270024AE2-089 GEN
Solar/Wind Harmer
2.366
972227AH1-698 GEN1
Adder
1.311
274687WILL CNTY;4U
Adder
14.004
274687WILL CNTY;4U
Adder
14.004
274675JOLIET 29;7U
Adder
15.345
274675JOLIET 29;7U
Adder
14.797
274731ELWOOD EC;2P
Adder
8.208
274733ELWOOD EC;3P
Adder
8.208
274735ELWOOD EC;4P
Adder
8.208
274728ELWOOD EC;5P
Adder
8.208
274746AC1-111 G10
Adder
2.761
274744AC1-111 GEN8
Adder
2.761
24729505KEY G4
Adder
3.179
274823ROCKFORD ;21
Adder
9.356
203846AF2-130 C
Solar/Wind Helper
0.325
241982AE2-343 S C
Solar/Wind Helper
0.145
254304AE2-114 C
Solar/Wind Helper
0.138
241997AF1-093 GEN
Solar/Wind Helper
0.16
203804AE2-113_GEN
Solar/Wind Helper
1.128
203855AF2-088 C
Solar/Wind Helper
0.087
20090526Q36
Solar/Wind Helper
0.548
203993AD2-133_GEN1
Solar/Wind Helper
0.548
20091526CHSTN_FL
Solar/Wind Helper
0.29
20092526R32
Solar/Wind Helper
0.563
203961AE2-224 GEN
Solar/Wind Helper
1.164
941231AE2-117 GEN
Solar/Wind Helper
0.227
970833AG2-524 GEN
Solar/Wind Harmer
1.943
23917202WLORG-3
50/50
1.953
23917302WLORG-4
50/50
1.91
966311AG1-500 GEN
50/50
177.624
24190002OREGON_ST1
50/50
3.713
24189802OREGON_CT1
50/50
2.816
23857202WLORG-B
Adder
8.455
241996AE2-282_GEN
Solar/Wind Harmer
2.414
971677AH1-339 GEN
Solar/Wind Harmer
8.462
270007AE1-245 C
Solar/Wind Harmer
4.022
942801AE2-298 GEN
Solar/Wind Harmer
1.019
246938BC-WTG3
Solar/Wind Harmer
2.659
246937BC-WTG2
Solar/Wind Harmer
2.614
971231AH1-075 GEN
Solar/Wind Harmer
0.508
961051AF2-396 GEN
Solar/Wind Harmer
9.992
961051AF2-396 GEN
Solar/Wind Harmer
4.648
960981AF2-389 GEN
Solar/Wind Harmer
0.936
957891AF2-083 GEN
Solar/Wind Harmer
2.088
247620Y3-023
Adder
0.281
270216AD2-079_GEN
Solar/Wind Harmer
0.363
970611AG2-400 GEN
Solar/Wind Harmer
5.975
270526AF1-158 GEN
Solar/Wind Harmer
2.631
24441505OLIV SLR
Solar/Wind Harmer
0.077
971201AH1-060 GEN
Solar/Wind Harmer
1.151
270224U2-072_GEN2
Solar/Wind Harmer
1.12
270227U2-072_GEN3
Solar/Wind Harmer
1.12
270228U2-072_GEN4
Solar/Wind Harmer
1.12
270231U2-072_GEN5
Solar/Wind Harmer
1.12
965681AG1-436 GEN
Solar/Wind Harmer
6.942
965791AG1-447 GEN
Solar/Wind Harmer
3.552
241960AC2-195 GEN
Solar/Wind Harmer
1.533
274808UNIV PK N;4U
Adder
2.553
942221AE2-234 GEN
Solar/Wind Harmer
0.373
274803UNIV PARK;6U
Adder
2.953
274888KELLY CRK;1U
Solar/Wind Harmer
2.977
274887GEN-1.85
Solar/Wind Harmer
2.688
276843GEN-1.7
Solar/Wind Harmer
0.289
958011AF2-095 GEN
Solar/Wind Harmer
7.261
274770LINCOLN ;1U
Adder
3.125
274771LINCOLN ;2U
Adder
3.125
972259AH1-714 GEN
Adder
9.55
274674JOLIET 9 ;6U
Adder
7.687
970321AG2-212 GEN
Solar/Wind Harmer
8.906
274696ROCKY RD ;4P
Adder
5.589
274695ROCKY RD ;2P
Adder
5.46
274693ROCKY RD ;1P
Adder
5.407
274697ROCKY RD ;3P
Adder
1.483
274683WAUKEGAN ;8U
Adder
10.328
274683WAUKEGAN ;8U
Adder
8.706
25326509SID D
Adder
0.633
274764LEE CO EC;5U
Adder
4.426
274765LEE CO EC;6U
Adder
4.426
203947AF1-006 C
Solar/Wind Helper
0.516
203980AG1-197 GEN
Solar/Wind Helper
0.336
203979AG1-198 GEN
Solar/Wind Helper
0.261
241967AE2-285_GEN
Solar/Wind Helper
0.417
241801AE1-079 GEN
Solar/Wind Helper
0.162
241985AE1-237 GEN
Solar/Wind Helper
0.162
962101AG1-054 GEN
Solar/Wind Helper
0.402
946381AF1-302 GEN
Solar/Wind Helper
0.136
238217AF1-153 C O1
Solar/Wind Helper
0.144
20398826ARMNA MT
Solar/Wind Helper
0.849
203853AF1-134 C O1
Solar/Wind Helper
0.264
203952AE2-129 C
Solar/Wind Helper
0.257
203946AE2-131 C
Solar/Wind Helper
0.258
946071AF1-272 GEN
Solar/Wind Helper
1.356
203940AF1-140 C
Solar/Wind Helper
0.192
20084626FORWARD
Solar/Wind Helper
0.17
20088626ARWF_N39
Solar/Wind Helper
0.584
20303426NA_O38_P22
Solar/Wind Helper
0.479
20088926STNY CRK
Solar/Wind Helper
0.38
20083426SW_E13_K22
Solar/Wind Helper
0.025
957111AF2-005 GEN
Adder
1.324
241808AF1-120 C
Solar/Wind Harmer
1.346
23920202STRYCT
Adder
2.011
241840AF1-064_GEN
Solar/Wind Harmer
1.592
972301AH1-735 GEN
Adder
7.456
23906402RICHG1
Adder
1.491
23906502RICHG2&3
Adder
1.489
270361_3
Solar/Wind Harmer
10.624
960841AF2-375 GEN
Solar/Wind Harmer
4.677
270428AC2-015 C
Solar/Wind Harmer
5.418
247522W1-056 GEN
Solar/Wind Harmer
1.996
970515AG2-329 GEN
Solar/Wind Harmer
12.822
970905AG2-564 GEN
Solar/Wind Harmer
4.278
944231AF1-091 GEN
Solar/Wind Harmer
2.791
241847AF2-150_GEN
Solar/Wind Harmer
2.847
246936BC-WTG1
Solar/Wind Harmer
2.614
270489AE1-102 GEN1
Solar/Wind Harmer
0.868
965421AG1-410 GEN
Solar/Wind Harmer
19.836
24695305TIMB G C
Solar/Wind Harmer
3.562
270449AD2-020 GEN
Solar/Wind Harmer
1.777
943021AE2-325 GEN
Solar/Wind Harmer
2.309
247521TR3_G114
Solar/Wind Harmer
2.099
270246TR4_N_V150
Solar/Wind Harmer
0.531
945111AF1-176 GEN
Solar/Wind Harmer
11.092
270505AE1-170 C O1
Solar/Wind Harmer
9.313
270462AD2-086
Solar/Wind Harmer
4.24
24639705ELKHART HY
Adder
0.093
270063AE2-323 C
Solar/Wind Harmer
1.334
965011AG1-365 GEN
Solar/Wind Harmer
5.975
241813AF1-122_GEN
Solar/Wind Harmer
3.682
270223U2-072_GEN1
Solar/Wind Harmer
1.12
270578AF1-285 GEN2
Solar/Wind Harmer
0.685
270391AF1-285 GEN3
Solar/Wind Harmer
0.685
970373AG2-245 GEN
Solar/Wind Harmer
11.24
971221AH1-070 GEN
Solar/Wind Harmer
0.907
270055AF2-134 C O1
Solar/Wind Harmer
1.591
274751CRETE EC ;1U
Adder
2.532
274754CRETE EC ;4U
Adder
2.532
958381AF2-132 GEN
Solar/Wind Harmer
4.687
964861AG1-349 GEN
Solar/Wind Harmer
4.054
971917AH1-482 GEN
Solar/Wind Harmer
4.678
274723RIVER EC ;12
Adder
9.215
274812UNIV PK N;8U
Adder
2.564
276164X3-005 C
Solar/Wind Harmer
0.358
274801UNIV PARK;4U
Adder
2.944
940581AE2-045 GEN
Solar/Wind Harmer
5.147
971605AH1-302 GEN
Solar/Wind Harmer
4.401
276776AD2-060 GEN
Solar/Wind Harmer
0.213
972207SS24-0001
Solar/Wind Harmer
11.112
274773LINCOLN ;4U
Adder
3.125
274774LINCOLN ;5U
Adder
3.125
274676JOLIET 29;8U
Adder
15.345
941551AE2-152 GEN
Solar/Wind Harmer
2.266
274732ELWOOD EC;7P
Adder
8.208
274674JOLIET 9 ;6U
Adder
7.687
970245AG2-165 GEN
Solar/Wind Harmer
8.906
274745AC1-111 GEN9
Adder
2.761
274682WAUKEGAN ;7U
Adder
8.816
274828WAUKEGAN ;BP
Adder
5.414
274822ROCKFORD ;11
Adder
9.424
972235AH1-702 GEN1
Adder
1.208
274761LEE CO EC;2U
Adder
2.885
961971AG1-040 GEN
Solar/Wind Helper
0.451
203835AF1-098 GEN
Solar/Wind Helper
1.778
203860AG1-193 C
Solar/Wind Helper
0.199
241966AE1-183 GEN
Solar/Wind Helper
0.16
254303AC2-168 GEN
Solar/Wind Helper
0.093
203954AE2-126 C
Solar/Wind Helper
0.282
959471AF2-238 GEN
Solar/Wind Helper
0.26
238206AE2-263_GEN
Solar/Wind Helper
0.502
20094526CT_V3-030
Solar/Wind Helper
0.243
20088826HIGHLAND
Solar/Wind Helper
0.435
964201AG1-281 GEN
Solar/Wind Helper
0.234
964391AG1-301 GEN
Solar/Wind Helper
0.226
970833AG2-524 GEN
Solar/Wind Harmer
0.904
991177J1571 G
External Queue
16.072763442993164
990527J1329
External Queue
1.891624927520752
990142J1224
External Queue
13.827776908874512
991182J1586 G
External Queue
25.886547088623047
LAGNLTFEXP_LAGN->PJM
CLTF
5.524
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.427
TVALTFEXP_TVA->PJM
CLTF
2.517
CPLELTFEXP_CPLE->PJM
CLTF
0.342
CBM West 2LTFEXP_CBM-W2->PJM
CBM
44.143
NYPJM->LTFIMP_NY
CLTF
2.552
LGEELTFEXP_LGEE->PJM
CLTF
2.281
WECLTFEXP_WEC->PJM
CLTF
1.831
AG2-052LTFEXP_AG2-052->PJM
LTF
0.118
AH1-155LTFEXP_AH1-155->PJM
LTF
0.177
CBM West 1LTFEXP_CBM-W1->PJM
CBM
101.376
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.995
MECLTFEXP_MEC->PJM
CLTF
7.157
SIGELTFEXP_SIGE->PJM
CLTF
0.189

Details for 02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line l/o ATSI_P2-3_OEC-345-003_SRT-SL


Base Case Flowgate

Area:ATSI
Facility Description:
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line
Contingency Name:
ATSI_P2-3_OEC-345-003_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.76 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:1967.48
MW Contribution:10.2
Bus #Bus NameTypeMW Contribution
23867002DVBSG1
50/50
9.2
972211AH1-690 GEN
50/50
210.311
241886AC2-103 GEN2
Solar/Wind Harmer
12.828
970817AG2-515 GEN
Solar/Wind Harmer
11.522
24191202EL_AA1-006
Adder
0.249
945411AF1-206 GEN
Solar/Wind Harmer
6.374
270499AE1-146 GEN
Solar/Wind Harmer
2.067
945641AF1-229 GEN
Solar/Wind Harmer
2.863
970159AG2-109 GEN
Solar/Wind Harmer
2.569
270297AD1-101 GEN
Solar/Wind Harmer
1.589
971549AH1-272 GEN
Solar/Wind Harmer
10.203
966831AG1-554 GEN
Solar/Wind Harmer
0.637
971989AH1-539 GEN
Solar/Wind Harmer
6.89
247607V1-011 GEN
Solar/Wind Harmer
1.93
971567AH1-282 GEN
Solar/Wind Harmer
7.229
957201AF2-014 GEN
Solar/Wind Harmer
2.183
270435AC2-044 GEN
Solar/Wind Harmer
0.963
944161AF1-084 GEN
Solar/Wind Harmer
1.025
965041AG1-368 GEN
Solar/Wind Harmer
4.523
965051AG1-369 GEN
Solar/Wind Harmer
2.252
270302AB2-170 GEN
Solar/Wind Harmer
3.686
270317AD1-130_GEN
Solar/Wind Harmer
1.413
203846AF2-130 C
Solar/Wind Helper
0.273
203804AE2-113_GEN
Solar/Wind Helper
0.939
241982AE2-343 S C
Solar/Wind Helper
0.108
254304AE2-114 C
Solar/Wind Helper
0.103
241997AF1-093 GEN
Solar/Wind Helper
0.119
23917402WLORG-5
50/50
1.364
23917102WLORG-2
50/50
1.344
24189902OREGON_CT2
50/50
1.95
23856402BAYSG1
50/50
1.049
241885AC2-103 GEN1
Solar/Wind Harmer
12.828
241807AE2-176_GEN
Solar/Wind Harmer
5.09
972253AH1-711 GEN
Adder
38.596
241858AF1-205_GEN
Solar/Wind Harmer
4.35
241808AF1-120 C
Solar/Wind Harmer
0.951
23920202STRYCT
Adder
1.423
241840AF1-064_GEN
Solar/Wind Harmer
1.126
972301AH1-735 GEN
Adder
5.287
23906402RICHG1
Adder
1.057
23906502RICHG2&3
Adder
1.056
270361_3
Solar/Wind Harmer
7.495
960841AF2-375 GEN
Solar/Wind Harmer
3.301
966321AG1-501 GEN
Adder
0.871
957111AF2-005 GEN
Adder
0.697
270428AC2-015 C
Solar/Wind Harmer
3.771
247522W1-056 GEN
Solar/Wind Harmer
1.418
970515AG2-329 GEN
Solar/Wind Harmer
9.087
970905AG2-564 GEN
Solar/Wind Harmer
2.97
944231AF1-091 GEN
Solar/Wind Harmer
2.004
241847AF2-150_GEN
Solar/Wind Harmer
2
246936BC-WTG1
Solar/Wind Harmer
1.883
270489AE1-102 GEN1
Solar/Wind Harmer
0.626
965421AG1-410 GEN
Solar/Wind Harmer
14.298
24695305TIMB G C
Solar/Wind Harmer
2.569
270449AD2-020 GEN
Solar/Wind Harmer
1.284
943021AE2-325 GEN
Solar/Wind Harmer
1.668
247521TR3_G114
Solar/Wind Harmer
1.516
270246TR4_N_V150
Solar/Wind Harmer
0.384
945111AF1-176 GEN
Solar/Wind Harmer
8.018
270505AE1-170 C O1
Solar/Wind Harmer
6.733
270462AD2-086
Solar/Wind Harmer
3.066
24639705ELKHART HY
Adder
0.067
270063AE2-323 C
Solar/Wind Harmer
0.965
965011AG1-365 GEN
Solar/Wind Harmer
4.324
961971AG1-040 GEN
Solar/Wind Helper
0.4
203835AF1-098 GEN
Solar/Wind Helper
1.575
203860AG1-193 C
Solar/Wind Helper
0.173
241966AE1-183 GEN
Solar/Wind Helper
0.119
203954AE2-126 C
Solar/Wind Helper
0.231
254303AC2-168 GEN
Solar/Wind Helper
0.068
23917202WLORG-3
50/50
1.387
23917302WLORG-4
50/50
1.357
966311AG1-500 GEN
50/50
126.182
24190002OREGON_ST1
50/50
2.624
24189802OREGON_CT1
50/50
1.991
241996AE2-282_GEN
Solar/Wind Harmer
1.706
23857202WLORG-B
Adder
4.453
971677AH1-339 GEN
Solar/Wind Harmer
5.98
270007AE1-245 C
Solar/Wind Harmer
2.895
942801AE2-298 GEN
Solar/Wind Harmer
0.734
246938BC-WTG3
Solar/Wind Harmer
1.916
246937BC-WTG2
Solar/Wind Harmer
1.883
961051AF2-396 GEN
Solar/Wind Harmer
7.22
961051AF2-396 GEN
Solar/Wind Harmer
3.358
971231AH1-075 GEN
Solar/Wind Harmer
0.364
960981AF2-389 GEN
Solar/Wind Harmer
0.677
957891AF2-083 GEN
Solar/Wind Harmer
1.51
247620Y3-023
Adder
0.203
270216AD2-079_GEN
Solar/Wind Harmer
0.263
970611AG2-400 GEN
Solar/Wind Harmer
4.324
203947AF1-006 C
Solar/Wind Helper
0.461
203980AG1-197 GEN
Solar/Wind Helper
0.297
203979AG1-198 GEN
Solar/Wind Helper
0.23
241967AE2-285_GEN
Solar/Wind Helper
0.309
957071AF2-004 GEN
50/50
10.802
23929302BS-PKR
50/50
1.846
241832AE2-181_GEN
Solar/Wind Harmer
1.547
958321AF2-126 GEN
Solar/Wind Harmer
1.207
23906502RICHG2&3
Adder
1.056
270575GUS2 35KV
Solar/Wind Harmer
8.83
23857102WLORG-A
Adder
4.322
270541AE2-072 C
Solar/Wind Harmer
3.557
970217AG2-149 GEN
Solar/Wind Harmer
20.039
270588AE1-091_GEN
Solar/Wind Harmer
5.974
270044AE2-322 C
Solar/Wind Harmer
0.703
270404AC1-167 GEN
Solar/Wind Harmer
0.585
270258AD1-119 GEN
Solar/Wind Harmer
1.434
958091AF2-103 GEN
Solar/Wind Harmer
0.079
247604X1-042
Adder
0.203
961961AG1-039 GEN
Solar/Wind Harmer
1.38
270491AE1-102 GEN2
Solar/Wind Harmer
0.626
24441205WTRV SLR C
Solar/Wind Harmer
0.064
270377AD1-106 GEN
Solar/Wind Harmer
2.809
270191TR4_S_V150
Solar/Wind Harmer
1.353
270247TR4_N_V136
Solar/Wind Harmer
0.384
945111AF1-176 GEN
Solar/Wind Harmer
2.541
270485AE1-090_GEN
Solar/Wind Harmer
0.267
24642205MAYFLWER
Adder
0.278
970031AG2-029 GEN
Solar/Wind Harmer
13.106
247643Z2-116 C
Solar/Wind Harmer
0.03
959331AF2-224 GEN
Solar/Wind Harmer
4.324
965021AG1-366 GEN
Solar/Wind Harmer
1.006
962511AG1-100 GEN
Solar/Wind Helper
0.411
203830AF1-094 GEN
Solar/Wind Helper
0.384
959441AF2-235 GEN
Solar/Wind Helper
0.169
20334926Z1-069 C
Solar/Wind Helper
0.692
254305AE2-115 C
Solar/Wind Helper
0.103
241801AE1-079 GEN
Solar/Wind Helper
0.12
241985AE1-237 GEN
Solar/Wind Helper
0.12
946381AF1-302 GEN
Solar/Wind Helper
0.111
238217AF1-153 C O1
Solar/Wind Helper
0.118
962101AG1-054 GEN
Solar/Wind Helper
0.297
991177J1571 G
External Queue
11.211230278015137
990527J1329
External Queue
1.3199658393859863
990142J1224
External Queue
9.648950576782227
LAGNLTFEXP_LAGN->PJM
CLTF
4.134
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.016
TVALTFEXP_TVA->PJM
CLTF
1.895
CPLELTFEXP_CPLE->PJM
CLTF
0.34
CBM West 2LTFEXP_CBM-W2->PJM
CBM
32.744
NYPJM->LTFIMP_NY
CLTF
1.985
LGEELTFEXP_LGEE->PJM
CLTF
1.697
WECLTFEXP_WEC->PJM
CLTF
1.336
AG2-052LTFEXP_AG2-052->PJM
LTF
0.086
AH1-155LTFEXP_AH1-155->PJM
LTF
0.129
CBM West 1LTFEXP_CBM-W1->PJM
CBM
72.978
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.506
MECLTFEXP_MEC->PJM
CLTF
5.248
SIGELTFEXP_SIGE->PJM
CLTF
0.14

Details for 02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line l/o ATSI_P2-3_OEC-345-028_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line
Contingency Name:
ATSI_P2-3_OEC-345-028_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.37 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:1903.65
MW Contribution:10.11
Bus #Bus NameTypeMW Contribution
23867002DVBSG1
50/50
9.044
972211AH1-690 GEN
50/50
207.621
24191202EL_AA1-006
50/50
0.277
241886AC2-103 GEN2
Solar/Wind Harmer
12.516
970817AG2-515 GEN
Solar/Wind Harmer
11.392
945411AF1-206 GEN
Solar/Wind Harmer
6.311
270499AE1-146 GEN
Solar/Wind Harmer
2.062
945641AF1-229 GEN
Solar/Wind Harmer
2.852
970159AG2-109 GEN
Solar/Wind Harmer
2.883
270297AD1-101 GEN
Solar/Wind Harmer
1.58
971549AH1-272 GEN
Solar/Wind Harmer
10.113
23917402WLORG-5
50/50
1.325
23917102WLORG-2
50/50
1.305
24189902OREGON_CT2
50/50
1.926
23856402BAYSG1
50/50
1.04
241885AC2-103 GEN1
Solar/Wind Harmer
12.516
241807AE2-176_GEN
Solar/Wind Harmer
5.17
972253AH1-711 GEN
Adder
38.133
241858AF1-205_GEN
Solar/Wind Harmer
4.307
241808AF1-120 C
Solar/Wind Harmer
0.942
23920202STRYCT
Adder
1.409
241840AF1-064_GEN
Solar/Wind Harmer
1.116
966321AG1-501 GEN
Adder
1.042
957111AF2-005 GEN
Adder
0.833
972301AH1-735 GEN
Adder
5.24
23906402RICHG1
Adder
1.048
23906502RICHG2&3
Adder
1.047
270361_3
Solar/Wind Harmer
7.48
960841AF2-375 GEN
Solar/Wind Harmer
3.294
270428AC2-015 C
Solar/Wind Harmer
3.85
247522W1-056 GEN
Solar/Wind Harmer
1.419
970515AG2-329 GEN
Solar/Wind Harmer
9.111
970905AG2-564 GEN
Solar/Wind Harmer
3.056
944231AF1-091 GEN
Solar/Wind Harmer
1.99
241847AF2-150_GEN
Solar/Wind Harmer
2.044
246936BC-WTG1
Solar/Wind Harmer
1.872
270489AE1-102 GEN1
Solar/Wind Harmer
0.622
965421AG1-410 GEN
Solar/Wind Harmer
14.212
24695305TIMB G C
Solar/Wind Harmer
2.554
270449AD2-020 GEN
Solar/Wind Harmer
1.274
943021AE2-325 GEN
Solar/Wind Harmer
1.655
247521TR3_G114
Solar/Wind Harmer
1.507
270246TR4_N_V150
Solar/Wind Harmer
0.381
945111AF1-176 GEN
Solar/Wind Harmer
7.958
270505AE1-170 C O1
Solar/Wind Harmer
6.681
270462AD2-086
Solar/Wind Harmer
3.053
24639705ELKHART HY
Adder
0.067
270063AE2-323 C
Solar/Wind Harmer
0.958
961971AG1-040 GEN
Solar/Wind Helper
0.399
203835AF1-098 GEN
Solar/Wind Helper
1.572
203860AG1-193 C
Solar/Wind Helper
0.172
241966AE1-183 GEN
Solar/Wind Helper
0.118
203954AE2-126 C
Solar/Wind Helper
0.231
254303AC2-168 GEN
Solar/Wind Helper
0.068
966831AG1-554 GEN
Solar/Wind Harmer
0.638
971989AH1-539 GEN
Solar/Wind Harmer
6.896
971567AH1-282 GEN
Solar/Wind Harmer
7.283
247607V1-011 GEN
Solar/Wind Harmer
1.919
957201AF2-014 GEN
Solar/Wind Harmer
2.17
270435AC2-044 GEN
Solar/Wind Harmer
0.957
944161AF1-084 GEN
Solar/Wind Harmer
1.017
965041AG1-368 GEN
Solar/Wind Harmer
4.496
965051AG1-369 GEN
Solar/Wind Harmer
2.238
270302AB2-170 GEN
Solar/Wind Harmer
3.67
270317AD1-130_GEN
Solar/Wind Harmer
1.407
203846AF2-130 C
Solar/Wind Helper
0.273
203804AE2-113_GEN
Solar/Wind Helper
0.936
241982AE2-343 S C
Solar/Wind Helper
0.107
254304AE2-114 C
Solar/Wind Helper
0.102
241997AF1-093 GEN
Solar/Wind Helper
0.118
957071AF2-004 GEN
50/50
10.49
23929302BS-PKR
50/50
1.83
241832AE2-181_GEN
Solar/Wind Harmer
1.532
958321AF2-126 GEN
Solar/Wind Harmer
1.196
23857102WLORG-A
Adder
5.166
23906502RICHG2&3
Adder
1.047
270575GUS2 35KV
Solar/Wind Harmer
8.812
270541AE2-072 C
Solar/Wind Harmer
3.533
970217AG2-149 GEN
Solar/Wind Harmer
20.092
270588AE1-091_GEN
Solar/Wind Harmer
5.966
270044AE2-322 C
Solar/Wind Harmer
0.698
270404AC1-167 GEN
Solar/Wind Harmer
0.582
270258AD1-119 GEN
Solar/Wind Harmer
1.425
961961AG1-039 GEN
Solar/Wind Harmer
1.41
958091AF2-103 GEN
Solar/Wind Harmer
0.078
247604X1-042
Adder
0.201
270491AE1-102 GEN2
Solar/Wind Harmer
0.622
24441205WTRV SLR C
Solar/Wind Harmer
0.064
270377AD1-106 GEN
Solar/Wind Harmer
2.828
270191TR4_S_V150
Solar/Wind Harmer
1.345
270247TR4_N_V136
Solar/Wind Harmer
0.381
945111AF1-176 GEN
Solar/Wind Harmer
2.522
270485AE1-090_GEN
Solar/Wind Harmer
0.265
24642205MAYFLWER
Adder
0.276
970031AG2-029 GEN
Solar/Wind Harmer
13.014
247643Z2-116 C
Solar/Wind Harmer
0.03
962511AG1-100 GEN
Solar/Wind Helper
0.41
203830AF1-094 GEN
Solar/Wind Helper
0.383
959441AF2-235 GEN
Solar/Wind Helper
0.169
20334926Z1-069 C
Solar/Wind Helper
0.69
254305AE2-115 C
Solar/Wind Helper
0.102
23917202WLORG-3
50/50
1.347
23917302WLORG-4
50/50
1.318
966311AG1-500 GEN
50/50
122.544
24190002OREGON_ST1
50/50
2.591
24189802OREGON_CT1
50/50
1.965
241996AE2-282_GEN
Solar/Wind Harmer
1.69
23857202WLORG-B
Adder
5.323
971677AH1-339 GEN
Solar/Wind Harmer
5.982
270007AE1-245 C
Solar/Wind Harmer
2.879
942801AE2-298 GEN
Solar/Wind Harmer
0.729
246938BC-WTG3
Solar/Wind Harmer
1.904
246937BC-WTG2
Solar/Wind Harmer
1.872
971231AH1-075 GEN
Solar/Wind Harmer
0.366
961051AF2-396 GEN
Solar/Wind Harmer
7.165
961051AF2-396 GEN
Solar/Wind Harmer
3.333
960981AF2-389 GEN
Solar/Wind Harmer
0.672
957891AF2-083 GEN
Solar/Wind Harmer
1.498
247620Y3-023
Adder
0.202
270216AD2-079_GEN
Solar/Wind Harmer
0.261
203947AF1-006 C
Solar/Wind Helper
0.46
203980AG1-197 GEN
Solar/Wind Helper
0.297
203979AG1-198 GEN
Solar/Wind Helper
0.23
241967AE2-285_GEN
Solar/Wind Helper
0.308
241801AE1-079 GEN
Solar/Wind Helper
0.12
241985AE1-237 GEN
Solar/Wind Helper
0.12
946381AF1-302 GEN
Solar/Wind Helper
0.11
238217AF1-153 C O1
Solar/Wind Helper
0.118
962101AG1-054 GEN
Solar/Wind Helper
0.296
991177J1571 G
External Queue
11.062751770019531
990527J1329
External Queue
1.3018794059753418
990142J1224
External Queue
9.516737937927246
LAGNLTFEXP_LAGN->PJM
CLTF
4.117
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.021
TVALTFEXP_TVA->PJM
CLTF
1.889
CPLELTFEXP_CPLE->PJM
CLTF
0.344
CBM West 2LTFEXP_CBM-W2->PJM
CBM
32.594
NYPJM->LTFIMP_NY
CLTF
1.977
LGEELTFEXP_LGEE->PJM
CLTF
1.691
WECLTFEXP_WEC->PJM
CLTF
1.328
AG2-052LTFEXP_AG2-052->PJM
LTF
0.085
AH1-155LTFEXP_AH1-155->PJM
LTF
0.128
CBM West 1LTFEXP_CBM-W1->PJM
CBM
72.342
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.481
MECLTFEXP_MEC->PJM
CLTF
5.217
SIGELTFEXP_SIGE->PJM
CLTF
0.139

Details for 02DAV-BE-02HAYES 345.0 kV Ckt 1 line l/o ATSI_P2-3_OEC-345-005_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02DAV-BE-02HAYES 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_OEC-345-005_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:149.08 %
Rating:1892.0 MVA
Rating Type:B
MVA to Mitigate:2820.59
MW Contribution:13.41
Bus #Bus NameTypeMW Contribution
24189902OREGON_CT2
50/50
2.842
23888702TROY G3
50/50
1.9
972253AH1-711 GEN
50/50
58.047
23856402BAYSG1
50/50
1.206
23920202STRYCT
50/50
1.925
241885AC2-103 GEN1
Solar/Wind Harmer
15.652
241858AF1-205_GEN
Solar/Wind Harmer
5.546
241808AF1-120 C
Solar/Wind Harmer
1.217
241840AF1-064_GEN
Solar/Wind Harmer
1.355
972301AH1-735 GEN
Adder
6.637
23906402RICHG1
Adder
1.327
23906502RICHG2&3
Adder
1.324
270361_3
Solar/Wind Harmer
7.399
960841AF2-375 GEN
Solar/Wind Harmer
3.289
970515AG2-329 GEN
Solar/Wind Harmer
10.155
944231AF1-091 GEN
Solar/Wind Harmer
2.497
247522W1-056 GEN
Solar/Wind Harmer
1.426
246936BC-WTG1
Solar/Wind Harmer
2.308
270489AE1-102 GEN1
Solar/Wind Harmer
0.767
270449AD2-020 GEN
Solar/Wind Harmer
1.647
943021AE2-325 GEN
Solar/Wind Harmer
2.14
965421AG1-410 GEN
Solar/Wind Harmer
17.537
945111AF1-176 GEN
Solar/Wind Harmer
10.248
270505AE1-170 C O1
Solar/Wind Harmer
8.61
24695305TIMB G C
Solar/Wind Harmer
3.122
24639705ELKHART HY
Adder
0.085
270063AE2-323 C
Solar/Wind Harmer
1.215
247521TR3_G114
Solar/Wind Harmer
1.846
270246TR4_N_V150
Solar/Wind Harmer
0.467
965011AG1-365 GEN
Solar/Wind Harmer
5.341
270462AD2-086
Solar/Wind Harmer
3.647
970373AG2-245 GEN
Solar/Wind Harmer
10.266
270223U2-072_GEN1
Solar/Wind Harmer
0.959
270578AF1-285 GEN2
Solar/Wind Harmer
0.586
270391AF1-285 GEN3
Solar/Wind Harmer
0.586
270055AF2-134 C O1
Solar/Wind Harmer
1.451
274751CRETE EC ;1U
Adder
2.308
274754CRETE EC ;4U
Adder
2.308
958381AF2-132 GEN
Solar/Wind Harmer
4.267
964861AG1-349 GEN
Solar/Wind Harmer
3.69
971917AH1-482 GEN
Solar/Wind Harmer
4.258
274723RIVER EC ;12
Adder
8.392
274812UNIV PK N;8U
Adder
2.335
276164X3-005 C
Solar/Wind Harmer
0.326
274801UNIV PARK;4U
Adder
2.678
276776AD2-060 GEN
Solar/Wind Harmer
0.194
940581AE2-045 GEN
Solar/Wind Harmer
4.675
972207SS24-0001
Solar/Wind Harmer
10.104
274773LINCOLN ;4U
Adder
2.842
274774LINCOLN ;5U
Adder
2.842
971605AH1-302 GEN
Solar/Wind Harmer
3.998
274676JOLIET 29;8U
Adder
13.952
941551AE2-152 GEN
Solar/Wind Harmer
2.06
274732ELWOOD EC;7P
Adder
7.461
274674JOLIET 9 ;6U
Adder
6.988
970245AG2-165 GEN
Solar/Wind Harmer
8.074
274871GR RIDGE ;2U
Solar/Wind Harmer
3.47
274745AC1-111 GEN9
Adder
2.508
276691AA1-018 GEN1
Solar/Wind Harmer
0.209
274682WAUKEGAN ;7U
Adder
8.008
274828WAUKEGAN ;BP
Adder
4.917
274822ROCKFORD ;11
Adder
8.551
972235AH1-702 GEN1
Adder
1.096
274761LEE CO EC;2U
Adder
4.005
274766LEE CO EC;7U
Adder
3.958
241807AE2-176_GEN
Solar/Wind Helper
2.243
961971AG1-040 GEN
Solar/Wind Helper
0.336
203835AF1-098 GEN
Solar/Wind Helper
1.324
203860AG1-193 C
Solar/Wind Helper
0.15
241966AE1-183 GEN
Solar/Wind Helper
0.132
254303AC2-168 GEN
Solar/Wind Helper
0.077
203954AE2-126 C
Solar/Wind Helper
0.22
23929302BS-PKR
50/50
2.123
241832AE2-181_GEN
Solar/Wind Harmer
1.981
958321AF2-126 GEN
Solar/Wind Harmer
1.453
23906502RICHG2&3
Adder
1.324
270541AE2-072 C
Solar/Wind Harmer
4.225
23867002DVBSG1
50/50
15.541
972211AH1-690 GEN
50/50
306.568
23888502TROY G1
50/50
1.9
23888602TROY G2
50/50
1.9
241886AC2-103 GEN2
Solar/Wind Harmer
15.652
970817AG2-515 GEN
Solar/Wind Harmer
15.768
945411AF1-206 GEN
Solar/Wind Harmer
8.154
945641AF1-229 GEN
Solar/Wind Harmer
3.506
270499AE1-146 GEN
Solar/Wind Harmer
2.087
971549AH1-272 GEN
Solar/Wind Harmer
13.415
270297AD1-101 GEN
Solar/Wind Harmer
1.871
944161AF1-084 GEN
Solar/Wind Harmer
1.317
957201AF2-014 GEN
Solar/Wind Harmer
2.676
270435AC2-044 GEN
Solar/Wind Harmer
1.18
247607V1-011 GEN
Solar/Wind Harmer
2.325
965041AG1-368 GEN
Solar/Wind Harmer
5.531
965051AG1-369 GEN
Solar/Wind Harmer
2.742
966831AG1-554 GEN
Solar/Wind Harmer
0.652
971989AH1-539 GEN
Solar/Wind Harmer
7.048
971771AH1-392 GEN
Solar/Wind Harmer
4.891
971769AH1-391 GEN
Solar/Wind Harmer
5.295
270302AB2-170 GEN
Solar/Wind Harmer
4.384
270317AD1-130_GEN
Solar/Wind Harmer
1.681
960681AF2-359 GEN
Solar/Wind Harmer
1.922
971347AH1-153 GEN
Solar/Wind Harmer
7.592
971567AH1-282 GEN
Solar/Wind Harmer
7.444
963791AG1-232 GEN
Solar/Wind Harmer
6.663
270578AF1-285 GEN2
Solar/Wind Harmer
0.225
270536AF1-215 GEN2
Solar/Wind Harmer
2.176
270071AF1-092 GEN
Solar/Wind Harmer
7.051
274814UNIV PK N;0U
Adder
2.355
24190002OREGON_ST1
50/50
3.824
24189802OREGON_CT1
50/50
2.901
23888802TROY G4
50/50
1.9
241996AE2-282_GEN
Solar/Wind Harmer
2.183
971677AH1-339 GEN
Solar/Wind Harmer
5.955
246938BC-WTG3
Solar/Wind Harmer
2.348
246937BC-WTG2
Solar/Wind Harmer
2.308
270007AE1-245 C
Solar/Wind Harmer
3.488
942801AE2-298 GEN
Solar/Wind Harmer
0.883
961051AF2-396 GEN
Solar/Wind Harmer
9.249
961051AF2-396 GEN
Solar/Wind Harmer
4.302
960981AF2-389 GEN
Solar/Wind Harmer
0.865
957891AF2-083 GEN
Solar/Wind Harmer
1.929
247620Y3-023
Adder
0.257
270216AD2-079_GEN
Solar/Wind Harmer
0.334
970611AG2-400 GEN
Solar/Wind Harmer
5.341
270526AF1-158 GEN
Solar/Wind Harmer
2.418
24441505OLIV SLR
Solar/Wind Harmer
0.071
965681AG1-436 GEN
Solar/Wind Harmer
6.36
965791AG1-447 GEN
Solar/Wind Harmer
3.254
270224U2-072_GEN2
Solar/Wind Harmer
0.959
270227U2-072_GEN3
Solar/Wind Harmer
0.959
270228U2-072_GEN4
Solar/Wind Harmer
0.959
270231U2-072_GEN5
Solar/Wind Harmer
0.959
274808UNIV PK N;4U
Adder
2.324
274803UNIV PARK;6U
Adder
2.687
274888KELLY CRK;1U
Solar/Wind Harmer
2.708
274887GEN-1.85
Solar/Wind Harmer
2.444
276843GEN-1.7
Solar/Wind Harmer
0.263
958011AF2-095 GEN
Solar/Wind Harmer
6.604
274770LINCOLN ;1U
Adder
2.842
274771LINCOLN ;2U
Adder
2.842
972259AH1-714 GEN
Adder
8.682
274674JOLIET 9 ;6U
Adder
6.988
942221AE2-234 GEN
Solar/Wind Harmer
0.331
970321AG2-212 GEN
Solar/Wind Harmer
8.074
274847GR RIDGE ;BU
Solar/Wind Harmer
2.283
274696ROCKY RD ;4P
Adder
5.076
274695ROCKY RD ;2P
Adder
4.959
274693ROCKY RD ;1P
Adder
4.91
274697ROCKY RD ;3P
Adder
1.347
274683WAUKEGAN ;8U
Adder
9.38
274683WAUKEGAN ;8U
Adder
7.907
274764LEE CO EC;5U
Adder
4.014
274765LEE CO EC;6U
Adder
4.014
274762LEE CO EC;3U
Adder
4.005
274763LEE CO EC;4U
Adder
3.967
203947AF1-006 C
Solar/Wind Helper
0.382
203980AG1-197 GEN
Solar/Wind Helper
0.25
203979AG1-198 GEN
Solar/Wind Helper
0.195
241967AE2-285_GEN
Solar/Wind Helper
0.343
241801AE1-079 GEN
Solar/Wind Helper
0.133
241985AE1-237 GEN
Solar/Wind Helper
0.133
962101AG1-054 GEN
Solar/Wind Helper
0.331
946381AF1-302 GEN
Solar/Wind Helper
0.106
238217AF1-153 C O1
Solar/Wind Helper
0.113
958481AF2-142 GEN
Solar/Wind Harmer
6.617
270575GUS2 35KV
Solar/Wind Harmer
8.717
970217AG2-149 GEN
Solar/Wind Harmer
22.392
270044AE2-322 C
Solar/Wind Harmer
0.856
270404AC1-167 GEN
Solar/Wind Harmer
0.713
247604X1-042
Adder
0.263
270258AD1-119 GEN
Solar/Wind Harmer
1.747
24441205WTRV SLR C
Solar/Wind Harmer
0.083
270491AE1-102 GEN2
Solar/Wind Harmer
0.767
958091AF2-103 GEN
Solar/Wind Harmer
0.095
270588AE1-091_GEN
Solar/Wind Harmer
6.43
945111AF1-176 GEN
Solar/Wind Harmer
3.248
24642205MAYFLWER
Adder
0.355
247643Z2-116 C
Solar/Wind Harmer
0.038
970031AG2-029 GEN
Solar/Wind Harmer
16.505
270191TR4_S_V150
Solar/Wind Harmer
1.647
270247TR4_N_V136
Solar/Wind Harmer
0.467
959331AF2-224 GEN
Solar/Wind Harmer
5.341
965021AG1-366 GEN
Solar/Wind Harmer
1.242
270485AE1-090_GEN
Solar/Wind Harmer
0.317
270043AE2-236 GEN
Solar/Wind Harmer
2.786
970349AG2-230 GEN
Solar/Wind Harmer
7.592
942871AE2-306 GEN
Solar/Wind Harmer
0.44
270391AF1-285 GEN3
Solar/Wind Harmer
0.225
270535AF1-215 GEN1
Solar/Wind Harmer
2.176
972231SS25-0005
Solar/Wind Harmer
4.48
972181SS23-001
Solar/Wind Harmer
2.8
274752CRETE EC ;2U
Adder
2.308
274753CRETE EC ;3U
Adder
2.308
964401AG1-302 GEN
Solar/Wind Harmer
4.267
274724RIVER EC ;11
Adder
8.292
959141AF2-205 GEN
Solar/Wind Harmer
2.796
274802UNIV PARK;5U
Adder
2.687
274826FISK ;BP
Adder
5.037
274800UNIV PARK;3U
Adder
2.678
972038AH1-567 GEN2
Adder
0.168
276772AC2-154 GEN
Solar/Wind Harmer
1.279
276806AD2-047 C O1
Solar/Wind Harmer
4.906
970941AG2-585 GEN
Solar/Wind Harmer
5.733
274772LINCOLN ;3U
Adder
2.842
972228AH1-698 GEN2
Adder
1.694
274676JOLIET 29;8U
Adder
13.453
276897AD1-100 C
Solar/Wind Harmer
13.182
939351AE1-166 GEN
Solar/Wind Harmer
2.693
276893AG1-478 C
Solar/Wind Harmer
0.19
274729ELWOOD EC;1P
Adder
7.461
274730ELWOOD EC;6P
Adder
7.461
274807UNIV PK N;3U
Adder
2.35
274805UNIV PK N;1U
Adder
2.34
274811UNIV PK N;7U
Adder
2.335
958391AF2-133 GEN
Solar/Wind Harmer
4.226
972037AH1-567 GEN1
Adder
0.084
274827FISK ;RP
Adder
3.57
960591AF2-350 GEN
Solar/Wind Harmer
4.586
274775LINCOLN ;6U
Adder
2.842
274776LINCOLN ;7U
Adder
2.842
274777LINCOLN ;8U
Adder
2.842
972227AH1-698 GEN1
Adder
1.192
274687WILL CNTY;4U
Adder
12.733
274687WILL CNTY;4U
Adder
12.733
274675JOLIET 29;7U
Adder
13.952
274675JOLIET 29;7U
Adder
13.453
274731ELWOOD EC;2P
Adder
7.461
274733ELWOOD EC;3P
Adder
7.461
274735ELWOOD EC;4P
Adder
7.461
274728ELWOOD EC;5P
Adder
7.461
970833AG2-524 GEN
Solar/Wind Harmer
3.942
970833AG2-524 GEN
Solar/Wind Harmer
1.834
274746AC1-111 G10
Adder
2.508
274744AC1-111 GEN8
Adder
2.508
24729505KEY G4
Adder
2.834
274823ROCKFORD ;21
Adder
8.489
241982AE2-343 S C
Solar/Wind Helper
0.119
254304AE2-114 C
Solar/Wind Helper
0.114
203846AF2-130 C
Solar/Wind Helper
0.25
241997AF1-093 GEN
Solar/Wind Helper
0.132
203804AE2-113_GEN
Solar/Wind Helper
0.874
274734ELWOOD EC;8P
Adder
7.461
274736ELWOOD EC;9P
Adder
7.461
970707AG2-453 GEN
Solar/Wind Harmer
12.707
970513AG2-328 GEN
Solar/Wind Harmer
8.074
970517AG2-330 GEN
Solar/Wind Harmer
7.323
943121AE2-341 GEN
Solar/Wind Harmer
6.728
943591AF1-030 GEN
Solar/Wind Harmer
4.485
276694AA1-018 GEN2
Solar/Wind Harmer
2.83
274682WAUKEGAN ;7U
Adder
8.008
972236AH1-702 GEN2
Adder
0.953
274760LEE CO EC;1U
Adder
4.005
274767LEE CO EC;8U
Adder
3.958
962511AG1-100 GEN
Solar/Wind Helper
0.343
203830AF1-094 GEN
Solar/Wind Helper
0.325
959441AF2-235 GEN
Solar/Wind Helper
0.148
254305AE2-115 C
Solar/Wind Helper
0.114
20334926Z1-069 C
Solar/Wind Helper
0.651
991177J1571 G
External Queue
15.847536087036133
990527J1329
External Queue
1.9070898294448853
990142J1224
External Queue
13.940826416015625
991182J1586 G
External Queue
26.137367248535156
LAGNLTFEXP_LAGN->PJM
CLTF
4.896
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.089
TVALTFEXP_TVA->PJM
CLTF
2.214
CPLELTFEXP_CPLE->PJM
CLTF
0.293
CBM West 2LTFEXP_CBM-W2->PJM
CBM
39.259
NYPJM->LTFIMP_NY
CLTF
2.051
LGEELTFEXP_LGEE->PJM
CLTF
1.986
WECLTFEXP_WEC->PJM
CLTF
1.661
AG2-052LTFEXP_AG2-052->PJM
LTF
0.107
AH1-155LTFEXP_AH1-155->PJM
LTF
0.161
CBM West 1LTFEXP_CBM-W1->PJM
CBM
95.867
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.771
MECLTFEXP_MEC->PJM
CLTF
6.458
SIGELTFEXP_SIGE->PJM
CLTF
0.166

Details for 02DAV-BE-02HAYES 345.0 kV Ckt 1 line l/o ATSI_P2-3_OEC-345-006_SRT-SL


Base Case Flowgate

Area:ATSI
Facility Description:
02DAV-BE-02HAYES 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_OEC-345-006_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:146.41 %
Rating:1892.0 MVA
Rating Type:B
MVA to Mitigate:2770.12
MW Contribution:13.49
Bus #Bus NameTypeMW Contribution
23929302BS-PKR
50/50
2.132
241832AE2-181_GEN
Solar/Wind Harmer
1.988
958321AF2-126 GEN
Solar/Wind Harmer
1.459
23906502RICHG2&3
Adder
1.33
270541AE2-072 C
Solar/Wind Harmer
4.248
270575GUS2 35KV
Solar/Wind Harmer
8.782
970217AG2-149 GEN
Solar/Wind Harmer
22.6
270044AE2-322 C
Solar/Wind Harmer
0.862
270404AC1-167 GEN
Solar/Wind Harmer
0.718
247604X1-042
Adder
0.265
270258AD1-119 GEN
Solar/Wind Harmer
1.76
24441205WTRV SLR C
Solar/Wind Harmer
0.084
270491AE1-102 GEN2
Solar/Wind Harmer
0.773
958091AF2-103 GEN
Solar/Wind Harmer
0.096
270588AE1-091_GEN
Solar/Wind Harmer
6.489
945111AF1-176 GEN
Solar/Wind Harmer
3.272
24642205MAYFLWER
Adder
0.357
247643Z2-116 C
Solar/Wind Harmer
0.039
970031AG2-029 GEN
Solar/Wind Harmer
16.631
270191TR4_S_V150
Solar/Wind Harmer
1.66
270247TR4_N_V136
Solar/Wind Harmer
0.471
959331AF2-224 GEN
Solar/Wind Harmer
5.384
965021AG1-366 GEN
Solar/Wind Harmer
1.252
270485AE1-090_GEN
Solar/Wind Harmer
0.32
270043AE2-236 GEN
Solar/Wind Harmer
2.809
970349AG2-230 GEN
Solar/Wind Harmer
7.655
942871AE2-306 GEN
Solar/Wind Harmer
0.444
270391AF1-285 GEN3
Solar/Wind Harmer
0.228
270535AF1-215 GEN1
Solar/Wind Harmer
2.195
972231SS25-0005
Solar/Wind Harmer
4.519
972181SS23-001
Solar/Wind Harmer
2.825
274752CRETE EC ;2U
Adder
2.328
274753CRETE EC ;3U
Adder
2.328
964401AG1-302 GEN
Solar/Wind Harmer
4.304
274724RIVER EC ;11
Adder
8.365
959141AF2-205 GEN
Solar/Wind Harmer
2.821
274802UNIV PARK;5U
Adder
2.711
274826FISK ;BP
Adder
5.082
274800UNIV PARK;3U
Adder
2.702
972038AH1-567 GEN2
Adder
0.169
276772AC2-154 GEN
Solar/Wind Harmer
1.29
23867002DVBSG1
50/50
15.56
972211AH1-690 GEN
50/50
307.318
23888502TROY G1
50/50
1.906
23888602TROY G2
50/50
1.906
241886AC2-103 GEN2
Solar/Wind Harmer
15.671
970817AG2-515 GEN
Solar/Wind Harmer
15.816
945411AF1-206 GEN
Solar/Wind Harmer
8.184
945641AF1-229 GEN
Solar/Wind Harmer
3.527
270499AE1-146 GEN
Solar/Wind Harmer
2.102
971549AH1-272 GEN
Solar/Wind Harmer
13.494
270297AD1-101 GEN
Solar/Wind Harmer
1.884
944161AF1-084 GEN
Solar/Wind Harmer
1.326
957201AF2-014 GEN
Solar/Wind Harmer
2.696
270435AC2-044 GEN
Solar/Wind Harmer
1.189
247607V1-011 GEN
Solar/Wind Harmer
2.343
965041AG1-368 GEN
Solar/Wind Harmer
5.574
965051AG1-369 GEN
Solar/Wind Harmer
2.764
966831AG1-554 GEN
Solar/Wind Harmer
0.658
971989AH1-539 GEN
Solar/Wind Harmer
7.12
971771AH1-392 GEN
Solar/Wind Harmer
4.928
971769AH1-391 GEN
Solar/Wind Harmer
5.337
270302AB2-170 GEN
Solar/Wind Harmer
4.422
270317AD1-130_GEN
Solar/Wind Harmer
1.695
960681AF2-359 GEN
Solar/Wind Harmer
1.938
971347AH1-153 GEN
Solar/Wind Harmer
7.655
971567AH1-282 GEN
Solar/Wind Harmer
7.54
24189902OREGON_CT2
50/50
2.849
23888702TROY G3
50/50
1.906
972253AH1-711 GEN
50/50
58.205
23856402BAYSG1
50/50
1.211
23920202STRYCT
50/50
1.932
241885AC2-103 GEN1
Solar/Wind Harmer
15.671
241858AF1-205_GEN
Solar/Wind Harmer
5.566
241808AF1-120 C
Solar/Wind Harmer
1.222
241840AF1-064_GEN
Solar/Wind Harmer
1.361
972301AH1-735 GEN
Adder
6.666
23906402RICHG1
Adder
1.333
23906502RICHG2&3
Adder
1.33
270361_3
Solar/Wind Harmer
7.454
960841AF2-375 GEN
Solar/Wind Harmer
3.314
970515AG2-329 GEN
Solar/Wind Harmer
10.249
944231AF1-091 GEN
Solar/Wind Harmer
2.514
247522W1-056 GEN
Solar/Wind Harmer
1.44
246936BC-WTG1
Solar/Wind Harmer
2.326
270489AE1-102 GEN1
Solar/Wind Harmer
0.773
270449AD2-020 GEN
Solar/Wind Harmer
1.659
943021AE2-325 GEN
Solar/Wind Harmer
2.155
965421AG1-410 GEN
Solar/Wind Harmer
17.671
945111AF1-176 GEN
Solar/Wind Harmer
10.323
270505AE1-170 C O1
Solar/Wind Harmer
8.673
24695305TIMB G C
Solar/Wind Harmer
3.146
24639705ELKHART HY
Adder
0.086
270063AE2-323 C
Solar/Wind Harmer
1.224
247521TR3_G114
Solar/Wind Harmer
1.861
270246TR4_N_V150
Solar/Wind Harmer
0.471
965011AG1-365 GEN
Solar/Wind Harmer
5.384
270462AD2-086
Solar/Wind Harmer
3.678
970373AG2-245 GEN
Solar/Wind Harmer
10.352
270223U2-072_GEN1
Solar/Wind Harmer
0.967
270578AF1-285 GEN2
Solar/Wind Harmer
0.592
270391AF1-285 GEN3
Solar/Wind Harmer
0.592
270055AF2-134 C O1
Solar/Wind Harmer
1.463
274751CRETE EC ;1U
Adder
2.328
274754CRETE EC ;4U
Adder
2.328
276806AD2-047 C O1
Solar/Wind Harmer
4.95
970941AG2-585 GEN
Solar/Wind Harmer
5.784
274772LINCOLN ;3U
Adder
2.867
972228AH1-698 GEN2
Adder
1.709
274676JOLIET 29;8U
Adder
13.575
276897AD1-100 C
Solar/Wind Harmer
13.3
939351AE1-166 GEN
Solar/Wind Harmer
2.718
276893AG1-478 C
Solar/Wind Harmer
0.191
274729ELWOOD EC;1P
Adder
7.528
274730ELWOOD EC;6P
Adder
7.529
274734ELWOOD EC;8P
Adder
7.529
274736ELWOOD EC;9P
Adder
7.529
970707AG2-453 GEN
Solar/Wind Harmer
12.822
970513AG2-328 GEN
Solar/Wind Harmer
8.148
970517AG2-330 GEN
Solar/Wind Harmer
7.39
943121AE2-341 GEN
Solar/Wind Harmer
6.789
943591AF1-030 GEN
Solar/Wind Harmer
4.526
276694AA1-018 GEN2
Solar/Wind Harmer
2.856
274682WAUKEGAN ;7U
Adder
8.081
963791AG1-232 GEN
Solar/Wind Harmer
6.721
270578AF1-285 GEN2
Solar/Wind Harmer
0.228
270536AF1-215 GEN2
Solar/Wind Harmer
2.195
270071AF1-092 GEN
Solar/Wind Harmer
7.114
274814UNIV PK N;0U
Adder
2.376
274807UNIV PK N;3U
Adder
2.371
274805UNIV PK N;1U
Adder
2.36
274811UNIV PK N;7U
Adder
2.355
958391AF2-133 GEN
Solar/Wind Harmer
4.264
972037AH1-567 GEN1
Adder
0.085
274827FISK ;RP
Adder
3.602
960591AF2-350 GEN
Solar/Wind Harmer
4.627
274775LINCOLN ;6U
Adder
2.867
274776LINCOLN ;7U
Adder
2.867
274777LINCOLN ;8U
Adder
2.867
972227AH1-698 GEN1
Adder
1.203
274687WILL CNTY;4U
Adder
12.848
274687WILL CNTY;4U
Adder
12.848
274675JOLIET 29;7U
Adder
14.077
274675JOLIET 29;7U
Adder
13.575
274731ELWOOD EC;2P
Adder
7.528
274733ELWOOD EC;3P
Adder
7.528
274735ELWOOD EC;4P
Adder
7.528
274728ELWOOD EC;5P
Adder
7.529
970833AG2-524 GEN
Solar/Wind Harmer
3.978
970833AG2-524 GEN
Solar/Wind Harmer
1.85
274746AC1-111 G10
Adder
2.531
274744AC1-111 GEN8
Adder
2.531
24729505KEY G4
Adder
2.861
274823ROCKFORD ;21
Adder
8.568
241982AE2-343 S C
Solar/Wind Helper
0.119
254304AE2-114 C
Solar/Wind Helper
0.113
203846AF2-130 C
Solar/Wind Helper
0.249
241997AF1-093 GEN
Solar/Wind Helper
0.131
203804AE2-113_GEN
Solar/Wind Helper
0.87
958381AF2-132 GEN
Solar/Wind Harmer
4.304
964861AG1-349 GEN
Solar/Wind Harmer
3.722
971917AH1-482 GEN
Solar/Wind Harmer
4.295
274723RIVER EC ;12
Adder
8.466
274812UNIV PK N;8U
Adder
2.355
276164X3-005 C
Solar/Wind Harmer
0.329
274801UNIV PARK;4U
Adder
2.702
276776AD2-060 GEN
Solar/Wind Harmer
0.196
940581AE2-045 GEN
Solar/Wind Harmer
4.717
972207SS24-0001
Solar/Wind Harmer
10.194
274773LINCOLN ;4U
Adder
2.867
274774LINCOLN ;5U
Adder
2.867
971605AH1-302 GEN
Solar/Wind Harmer
4.034
274676JOLIET 29;8U
Adder
14.077
941551AE2-152 GEN
Solar/Wind Harmer
2.079
274732ELWOOD EC;7P
Adder
7.529
274674JOLIET 9 ;6U
Adder
7.051
970245AG2-165 GEN
Solar/Wind Harmer
8.148
274871GR RIDGE ;2U
Solar/Wind Harmer
3.502
274745AC1-111 GEN9
Adder
2.531
276691AA1-018 GEN1
Solar/Wind Harmer
0.211
274682WAUKEGAN ;7U
Adder
8.081
274828WAUKEGAN ;BP
Adder
4.962
274822ROCKFORD ;11
Adder
8.631
972235AH1-702 GEN1
Adder
1.107
274761LEE CO EC;2U
Adder
4.043
274766LEE CO EC;7U
Adder
3.995
241807AE2-176_GEN
Solar/Wind Helper
2.224
961971AG1-040 GEN
Solar/Wind Helper
0.335
203835AF1-098 GEN
Solar/Wind Helper
1.322
203860AG1-193 C
Solar/Wind Helper
0.15
241966AE1-183 GEN
Solar/Wind Helper
0.131
254303AC2-168 GEN
Solar/Wind Helper
0.076
24190002OREGON_ST1
50/50
3.833
24189802OREGON_CT1
50/50
2.908
23888802TROY G4
50/50
1.906
241996AE2-282_GEN
Solar/Wind Harmer
2.191
971677AH1-339 GEN
Solar/Wind Harmer
6.006
246938BC-WTG3
Solar/Wind Harmer
2.366
246937BC-WTG2
Solar/Wind Harmer
2.326
270007AE1-245 C
Solar/Wind Harmer
3.514
942801AE2-298 GEN
Solar/Wind Harmer
0.89
961051AF2-396 GEN
Solar/Wind Harmer
9.316
961051AF2-396 GEN
Solar/Wind Harmer
4.333
960981AF2-389 GEN
Solar/Wind Harmer
0.871
957891AF2-083 GEN
Solar/Wind Harmer
1.944
247620Y3-023
Adder
0.259
270216AD2-079_GEN
Solar/Wind Harmer
0.337
970611AG2-400 GEN
Solar/Wind Harmer
5.384
270526AF1-158 GEN
Solar/Wind Harmer
2.437
24441505OLIV SLR
Solar/Wind Harmer
0.071
965681AG1-436 GEN
Solar/Wind Harmer
6.412
965791AG1-447 GEN
Solar/Wind Harmer
3.281
270224U2-072_GEN2
Solar/Wind Harmer
0.967
270227U2-072_GEN3
Solar/Wind Harmer
0.967
270228U2-072_GEN4
Solar/Wind Harmer
0.967
270231U2-072_GEN5
Solar/Wind Harmer
0.967
274808UNIV PK N;4U
Adder
2.345
274803UNIV PARK;6U
Adder
2.711
274888KELLY CRK;1U
Solar/Wind Harmer
2.732
274887GEN-1.85
Solar/Wind Harmer
2.466
276843GEN-1.7
Solar/Wind Harmer
0.265
958011AF2-095 GEN
Solar/Wind Harmer
6.663
274770LINCOLN ;1U
Adder
2.867
274771LINCOLN ;2U
Adder
2.867
972259AH1-714 GEN
Adder
8.76
274674JOLIET 9 ;6U
Adder
7.051
942221AE2-234 GEN
Solar/Wind Harmer
0.334
970321AG2-212 GEN
Solar/Wind Harmer
8.148
274847GR RIDGE ;BU
Solar/Wind Harmer
2.304
274695ROCKY RD ;2P
Adder
5.005
274693ROCKY RD ;1P
Adder
4.956
274697ROCKY RD ;3P
Adder
1.36
274696ROCKY RD ;4P
Adder
5.123
274683WAUKEGAN ;8U
Adder
9.466
274683WAUKEGAN ;8U
Adder
7.98
274764LEE CO EC;5U
Adder
4.052
274765LEE CO EC;6U
Adder
4.052
274762LEE CO EC;3U
Adder
4.043
274763LEE CO EC;4U
Adder
4.004
972267AH1-718 GEN
Adder
1.797
203947AF1-006 C
Solar/Wind Helper
0.382
203980AG1-197 GEN
Solar/Wind Helper
0.25
203979AG1-198 GEN
Solar/Wind Helper
0.195
241967AE2-285_GEN
Solar/Wind Helper
0.342
241801AE1-079 GEN
Solar/Wind Helper
0.133
241985AE1-237 GEN
Solar/Wind Helper
0.132
962101AG1-054 GEN
Solar/Wind Helper
0.33
946381AF1-302 GEN
Solar/Wind Helper
0.106
238217AF1-153 C O1
Solar/Wind Helper
0.112
958481AF2-142 GEN
Solar/Wind Harmer
6.677
972236AH1-702 GEN2
Adder
0.962
274760LEE CO EC;1U
Adder
4.043
274767LEE CO EC;8U
Adder
3.995
962511AG1-100 GEN
Solar/Wind Helper
0.343
203830AF1-094 GEN
Solar/Wind Helper
0.325
959441AF2-235 GEN
Solar/Wind Helper
0.148
254305AE2-115 C
Solar/Wind Helper
0.113
20334926Z1-069 C
Solar/Wind Helper
0.648
991177J1571 G
External Queue
15.857954978942871
990527J1329
External Queue
1.9081761837005615
990142J1224
External Queue
13.94876766204834
991182J1586 G
External Queue
26.15285873413086
LAGNLTFEXP_LAGN->PJM
CLTF
4.973
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.195
TVALTFEXP_TVA->PJM
CLTF
2.252
CPLELTFEXP_CPLE->PJM
CLTF
0.33
CBM West 2LTFEXP_CBM-W2->PJM
CBM
39.785
NYPJM->LTFIMP_NY
CLTF
2.036
LGEELTFEXP_LGEE->PJM
CLTF
2.013
WECLTFEXP_WEC->PJM
CLTF
1.677
AG2-052LTFEXP_AG2-052->PJM
LTF
0.108
AH1-155LTFEXP_AH1-155->PJM
LTF
0.162
CBM West 1LTFEXP_CBM-W1->PJM
CBM
96.478
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.917
MECLTFEXP_MEC->PJM
CLTF
6.526
SIGELTFEXP_SIGE->PJM
CLTF
0.169

Details for 02DAV-BE-02HAYES 345.0 kV Ckt 1 line l/o ATSI_P2-3_TE-345-010A_SRT-SL


Base Case Flowgate

Area:ATSI
Facility Description:
02DAV-BE-02HAYES 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_TE-345-010A_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:144.5 %
Rating:1892.0 MVA
Rating Type:B
MVA to Mitigate:2733.88
MW Contribution:13.49
Bus #Bus NameTypeMW Contribution
24189902OREGON_CT2
50/50
2.849
23888702TROY G3
50/50
1.905
972253AH1-711 GEN
50/50
58.19
23856402BAYSG1
50/50
1.21
23920202STRYCT
50/50
1.931
241858AF1-205_GEN
Solar/Wind Harmer
5.563
241808AF1-120 C
Solar/Wind Harmer
1.221
241840AF1-064_GEN
Solar/Wind Harmer
1.36
972301AH1-735 GEN
Adder
6.662
23906402RICHG1
Adder
1.332
23906502RICHG2&3
Adder
1.329
270361_3
Solar/Wind Harmer
7.436
960841AF2-375 GEN
Solar/Wind Harmer
3.306
970515AG2-329 GEN
Solar/Wind Harmer
10.216
944231AF1-091 GEN
Solar/Wind Harmer
2.513
247522W1-056 GEN
Solar/Wind Harmer
1.436
246936BC-WTG1
Solar/Wind Harmer
2.325
270489AE1-102 GEN1
Solar/Wind Harmer
0.772
270449AD2-020 GEN
Solar/Wind Harmer
1.659
943021AE2-325 GEN
Solar/Wind Harmer
2.155
965421AG1-410 GEN
Solar/Wind Harmer
17.664
945111AF1-176 GEN
Solar/Wind Harmer
10.323
270505AE1-170 C O1
Solar/Wind Harmer
8.673
24695305TIMB G C
Solar/Wind Harmer
3.145
24639705ELKHART HY
Adder
0.086
270063AE2-323 C
Solar/Wind Harmer
1.224
247521TR3_G114
Solar/Wind Harmer
1.86
270246TR4_N_V150
Solar/Wind Harmer
0.471
965011AG1-365 GEN
Solar/Wind Harmer
5.383
270462AD2-086
Solar/Wind Harmer
3.676
970373AG2-245 GEN
Solar/Wind Harmer
10.354
270223U2-072_GEN1
Solar/Wind Harmer
0.967
270578AF1-285 GEN2
Solar/Wind Harmer
0.591
270391AF1-285 GEN3
Solar/Wind Harmer
0.591
270055AF2-134 C O1
Solar/Wind Harmer
1.463
274751CRETE EC ;1U
Adder
2.328
274754CRETE EC ;4U
Adder
2.328
958381AF2-132 GEN
Solar/Wind Harmer
4.305
964861AG1-349 GEN
Solar/Wind Harmer
3.723
971917AH1-482 GEN
Solar/Wind Harmer
4.296
274723RIVER EC ;12
Adder
8.468
274812UNIV PK N;8U
Adder
2.356
276164X3-005 C
Solar/Wind Harmer
0.329
274801UNIV PARK;4U
Adder
2.703
276776AD2-060 GEN
Solar/Wind Harmer
0.196
940581AE2-045 GEN
Solar/Wind Harmer
4.718
972207SS24-0001
Solar/Wind Harmer
10.197
274773LINCOLN ;4U
Adder
2.868
274774LINCOLN ;5U
Adder
2.868
971605AH1-302 GEN
Solar/Wind Harmer
4.035
274676JOLIET 29;8U
Adder
14.081
941551AE2-152 GEN
Solar/Wind Harmer
2.079
274732ELWOOD EC;7P
Adder
7.531
274674JOLIET 9 ;6U
Adder
7.053
970245AG2-165 GEN
Solar/Wind Harmer
8.15
274871GR RIDGE ;2U
Solar/Wind Harmer
3.503
274745AC1-111 GEN9
Adder
2.532
276691AA1-018 GEN1
Solar/Wind Harmer
0.211
274682WAUKEGAN ;7U
Adder
8.083
274828WAUKEGAN ;BP
Adder
4.964
274822ROCKFORD ;11
Adder
8.634
972235AH1-702 GEN1
Adder
1.107
274761LEE CO EC;2U
Adder
4.044
274766LEE CO EC;7U
Adder
3.996
241885AC2-103 GEN1
Solar/Wind Helper
3.958
241807AE2-176_GEN
Solar/Wind Helper
2.236
961971AG1-040 GEN
Solar/Wind Helper
0.334
203835AF1-098 GEN
Solar/Wind Helper
1.316
203860AG1-193 C
Solar/Wind Helper
0.149
241966AE1-183 GEN
Solar/Wind Helper
0.131
254303AC2-168 GEN
Solar/Wind Helper
0.076
23867002DVBSG1
50/50
15.565
972211AH1-690 GEN
50/50
307.274
23888502TROY G1
50/50
1.905
23888602TROY G2
50/50
1.905
970817AG2-515 GEN
Solar/Wind Harmer
15.811
945411AF1-206 GEN
Solar/Wind Harmer
8.18
945641AF1-229 GEN
Solar/Wind Harmer
3.521
270499AE1-146 GEN
Solar/Wind Harmer
2.097
971549AH1-272 GEN
Solar/Wind Harmer
13.494
270297AD1-101 GEN
Solar/Wind Harmer
1.883
944161AF1-084 GEN
Solar/Wind Harmer
1.326
957201AF2-014 GEN
Solar/Wind Harmer
2.695
270435AC2-044 GEN
Solar/Wind Harmer
1.188
247607V1-011 GEN
Solar/Wind Harmer
2.341
965041AG1-368 GEN
Solar/Wind Harmer
5.573
965051AG1-369 GEN
Solar/Wind Harmer
2.763
966831AG1-554 GEN
Solar/Wind Harmer
0.657
971989AH1-539 GEN
Solar/Wind Harmer
7.103
971771AH1-392 GEN
Solar/Wind Harmer
4.929
971769AH1-391 GEN
Solar/Wind Harmer
5.338
270302AB2-170 GEN
Solar/Wind Harmer
4.419
270317AD1-130_GEN
Solar/Wind Harmer
1.694
960681AF2-359 GEN
Solar/Wind Harmer
1.938
971347AH1-153 GEN
Solar/Wind Harmer
7.656
971567AH1-282 GEN
Solar/Wind Harmer
7.507
963791AG1-232 GEN
Solar/Wind Harmer
6.72
270578AF1-285 GEN2
Solar/Wind Harmer
0.227
270536AF1-215 GEN2
Solar/Wind Harmer
2.195
270071AF1-092 GEN
Solar/Wind Harmer
7.115
274814UNIV PK N;0U
Adder
2.376
274807UNIV PK N;3U
Adder
2.371
274805UNIV PK N;1U
Adder
2.361
274811UNIV PK N;7U
Adder
2.356
958391AF2-133 GEN
Solar/Wind Harmer
4.265
972037AH1-567 GEN1
Adder
0.085
274827FISK ;RP
Adder
3.602
960591AF2-350 GEN
Solar/Wind Harmer
4.628
274775LINCOLN ;6U
Adder
2.868
274776LINCOLN ;7U
Adder
2.868
274777LINCOLN ;8U
Adder
2.868
972227AH1-698 GEN1
Adder
1.203
274687WILL CNTY;4U
Adder
12.851
274687WILL CNTY;4U
Adder
12.851
274675JOLIET 29;7U
Adder
14.081
274675JOLIET 29;7U
Adder
13.578
274731ELWOOD EC;2P
Adder
7.53
274733ELWOOD EC;3P
Adder
7.53
274735ELWOOD EC;4P
Adder
7.53
274728ELWOOD EC;5P
Adder
7.531
970833AG2-524 GEN
Solar/Wind Harmer
3.979
970833AG2-524 GEN
Solar/Wind Harmer
1.851
274746AC1-111 G10
Adder
2.532
274744AC1-111 GEN8
Adder
2.532
24729505KEY G4
Adder
2.862
24190002OREGON_ST1
50/50
3.833
24189802OREGON_CT1
50/50
2.907
23888802TROY G4
50/50
1.905
241996AE2-282_GEN
Solar/Wind Harmer
2.19
971677AH1-339 GEN
Solar/Wind Harmer
5.988
246938BC-WTG3
Solar/Wind Harmer
2.365
246937BC-WTG2
Solar/Wind Harmer
2.325
270007AE1-245 C
Solar/Wind Harmer
3.513
942801AE2-298 GEN
Solar/Wind Harmer
0.889
961051AF2-396 GEN
Solar/Wind Harmer
9.316
961051AF2-396 GEN
Solar/Wind Harmer
4.333
960981AF2-389 GEN
Solar/Wind Harmer
0.871
957891AF2-083 GEN
Solar/Wind Harmer
1.944
247620Y3-023
Adder
0.259
270216AD2-079_GEN
Solar/Wind Harmer
0.337
970611AG2-400 GEN
Solar/Wind Harmer
5.383
270526AF1-158 GEN
Solar/Wind Harmer
2.438
24441505OLIV SLR
Solar/Wind Harmer
0.071
965681AG1-436 GEN
Solar/Wind Harmer
6.413
965791AG1-447 GEN
Solar/Wind Harmer
3.281
270224U2-072_GEN2
Solar/Wind Harmer
0.967
270227U2-072_GEN3
Solar/Wind Harmer
0.967
270228U2-072_GEN4
Solar/Wind Harmer
0.967
270231U2-072_GEN5
Solar/Wind Harmer
0.967
274808UNIV PK N;4U
Adder
2.345
274803UNIV PARK;6U
Adder
2.712
274888KELLY CRK;1U
Solar/Wind Harmer
2.733
274887GEN-1.85
Solar/Wind Harmer
2.467
276843GEN-1.7
Solar/Wind Harmer
0.265
958011AF2-095 GEN
Solar/Wind Harmer
6.665
274770LINCOLN ;1U
Adder
2.868
274771LINCOLN ;2U
Adder
2.868
972259AH1-714 GEN
Adder
8.763
274674JOLIET 9 ;6U
Adder
7.053
942221AE2-234 GEN
Solar/Wind Harmer
0.334
970321AG2-212 GEN
Solar/Wind Harmer
8.15
274847GR RIDGE ;BU
Solar/Wind Harmer
2.304
958481AF2-142 GEN
Solar/Wind Harmer
6.79
274861TOP CROP ;1U
Solar/Wind Harmer
2.743
274862TOP CROP ;2U
Solar/Wind Harmer
2.29
274696ROCKY RD ;4P
Adder
5.124
274695ROCKY RD ;2P
Adder
5.006
274693ROCKY RD ;1P
Adder
4.957
274697ROCKY RD ;3P
Adder
1.36
274683WAUKEGAN ;8U
Adder
9.469
274683WAUKEGAN ;8U
Adder
7.982
274764LEE CO EC;5U
Adder
4.053
274765LEE CO EC;6U
Adder
4.053
274762LEE CO EC;3U
Adder
4.044
274763LEE CO EC;4U
Adder
4.006
972267AH1-718 GEN
Adder
1.798
203947AF1-006 C
Solar/Wind Helper
0.38
203980AG1-197 GEN
Solar/Wind Helper
0.249
203979AG1-198 GEN
Solar/Wind Helper
0.194
241967AE2-285_GEN
Solar/Wind Helper
0.34
241801AE1-079 GEN
Solar/Wind Helper
0.132
241985AE1-237 GEN
Solar/Wind Helper
0.132
962101AG1-054 GEN
Solar/Wind Helper
0.328
946381AF1-302 GEN
Solar/Wind Helper
0.105
238217AF1-153 C O1
Solar/Wind Helper
0.111
945421AF1-207 GEN
Solar/Wind Harmer
0.181
23929302BS-PKR
50/50
2.13
241832AE2-181_GEN
Solar/Wind Harmer
1.987
958321AF2-126 GEN
Solar/Wind Harmer
1.458
23906502RICHG2&3
Adder
1.329
270541AE2-072 C
Solar/Wind Harmer
4.244
270575GUS2 35KV
Solar/Wind Harmer
8.76
970217AG2-149 GEN
Solar/Wind Harmer
22.527
270044AE2-322 C
Solar/Wind Harmer
0.862
270404AC1-167 GEN
Solar/Wind Harmer
0.718
247604X1-042
Adder
0.265
270258AD1-119 GEN
Solar/Wind Harmer
1.759
24441205WTRV SLR C
Solar/Wind Harmer
0.084
270491AE1-102 GEN2
Solar/Wind Harmer
0.772
958091AF2-103 GEN
Solar/Wind Harmer
0.096
270588AE1-091_GEN
Solar/Wind Harmer
6.477
945111AF1-176 GEN
Solar/Wind Harmer
3.272
24642205MAYFLWER
Adder
0.357
247643Z2-116 C
Solar/Wind Harmer
0.039
970031AG2-029 GEN
Solar/Wind Harmer
16.631
270191TR4_S_V150
Solar/Wind Harmer
1.66
270247TR4_N_V136
Solar/Wind Harmer
0.471
959331AF2-224 GEN
Solar/Wind Harmer
5.383
965021AG1-366 GEN
Solar/Wind Harmer
1.252
270485AE1-090_GEN
Solar/Wind Harmer
0.32
270043AE2-236 GEN
Solar/Wind Harmer
2.809
970349AG2-230 GEN
Solar/Wind Harmer
7.656
942871AE2-306 GEN
Solar/Wind Harmer
0.444
270391AF1-285 GEN3
Solar/Wind Harmer
0.227
270535AF1-215 GEN1
Solar/Wind Harmer
2.195
972231SS25-0005
Solar/Wind Harmer
4.52
972181SS23-001
Solar/Wind Harmer
2.825
274752CRETE EC ;2U
Adder
2.328
274753CRETE EC ;3U
Adder
2.328
964401AG1-302 GEN
Solar/Wind Harmer
4.305
274724RIVER EC ;11
Adder
8.367
959141AF2-205 GEN
Solar/Wind Harmer
2.822
274802UNIV PARK;5U
Adder
2.712
274826FISK ;BP
Adder
5.083
274800UNIV PARK;3U
Adder
2.703
972038AH1-567 GEN2
Adder
0.169
276772AC2-154 GEN
Solar/Wind Harmer
1.291
276806AD2-047 C O1
Solar/Wind Harmer
4.951
970941AG2-585 GEN
Solar/Wind Harmer
5.785
274772LINCOLN ;3U
Adder
2.868
972228AH1-698 GEN2
Adder
1.709
274676JOLIET 29;8U
Adder
13.578
276897AD1-100 C
Solar/Wind Harmer
13.304
939351AE1-166 GEN
Solar/Wind Harmer
2.718
276893AG1-478 C
Solar/Wind Harmer
0.191
274729ELWOOD EC;1P
Adder
7.53
274730ELWOOD EC;6P
Adder
7.531
274734ELWOOD EC;8P
Adder
7.531
274736ELWOOD EC;9P
Adder
7.531
970707AG2-453 GEN
Solar/Wind Harmer
12.825
970513AG2-328 GEN
Solar/Wind Harmer
8.15
970517AG2-330 GEN
Solar/Wind Harmer
7.392
943121AE2-341 GEN
Solar/Wind Harmer
6.791
943591AF1-030 GEN
Solar/Wind Harmer
4.527
276694AA1-018 GEN2
Solar/Wind Harmer
2.856
274682WAUKEGAN ;7U
Adder
8.083
274823ROCKFORD ;21
Adder
8.571
241886AC2-103 GEN2
Solar/Wind Helper
3.958
241982AE2-343 S C
Solar/Wind Helper
0.118
254304AE2-114 C
Solar/Wind Helper
0.113
203846AF2-130 C
Solar/Wind Helper
0.248
241997AF1-093 GEN
Solar/Wind Helper
0.131
203804AE2-113_GEN
Solar/Wind Helper
0.866
972236AH1-702 GEN2
Adder
0.963
274760LEE CO EC;1U
Adder
4.044
274767LEE CO EC;8U
Adder
3.996
962511AG1-100 GEN
Solar/Wind Helper
0.341
203830AF1-094 GEN
Solar/Wind Helper
0.323
959441AF2-235 GEN
Solar/Wind Helper
0.147
254305AE2-115 C
Solar/Wind Helper
0.113
20334926Z1-069 C
Solar/Wind Helper
0.645
991177J1571 G
External Queue
15.847536087036133
990527J1329
External Queue
1.9070898294448853
990142J1224
External Queue
13.940826416015625
991182J1586 G
External Queue
26.137367248535156
LAGNLTFEXP_LAGN->PJM
CLTF
4.982
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.217
TVALTFEXP_TVA->PJM
CLTF
2.257
CPLELTFEXP_CPLE->PJM
CLTF
0.339
CBM West 2LTFEXP_CBM-W2->PJM
CBM
39.829
NYPJM->LTFIMP_NY
CLTF
2.024
LGEELTFEXP_LGEE->PJM
CLTF
2.015
WECLTFEXP_WEC->PJM
CLTF
1.677
AG2-052LTFEXP_AG2-052->PJM
LTF
0.108
AH1-155LTFEXP_AH1-155->PJM
LTF
0.162
CBM West 1LTFEXP_CBM-W1->PJM
CBM
96.485
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.932
MECLTFEXP_MEC->PJM
CLTF
6.529
SIGELTFEXP_SIGE->PJM
CLTF
0.169

Details for 02DAV-BE-02HAYES 345.0 kV Ckt 1 line l/o ATSI_P1-2_OEC-345-825_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02DAV-BE-02HAYES 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_OEC-345-825_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:136.86 %
Rating:1892.0 MVA
Rating Type:B
MVA to Mitigate:2589.31
MW Contribution:10.49
Bus #Bus NameTypeMW Contribution
23929302BS-PKR
50/50
2.128
241832AE2-181_GEN
Solar/Wind Harmer
0.004
958321AF2-126 GEN
Solar/Wind Harmer
1.129
23906502RICHG2&3
Adder
1.328
270541AE2-072 C
Solar/Wind Harmer
0.008
270575GUS2 35KV
Solar/Wind Harmer
4.06
970217AG2-149 GEN
Solar/Wind Harmer
4.25
270404AC1-167 GEN
Solar/Wind Harmer
0.002
247604X1-042
Adder
0.264
270258AD1-119 GEN
Solar/Wind Harmer
0.001
24441205WTRV SLR C
Solar/Wind Harmer
0
270491AE1-102 GEN2
Solar/Wind Harmer
0.538
270588AE1-091_GEN
Solar/Wind Harmer
3.207
945111AF1-176 GEN
Solar/Wind Harmer
3.266
24642205MAYFLWER
Adder
0.357
247643Z2-116 C
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
2.509
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.025
959331AF2-224 GEN
Solar/Wind Harmer
2.624
965021AG1-366 GEN
Solar/Wind Harmer
1.25
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270043AE2-236 GEN
Solar/Wind Harmer
2.282
970349AG2-230 GEN
Solar/Wind Harmer
5.331
270391AF1-285 GEN3
Solar/Wind Harmer
0.227
270535AF1-215 GEN1
Solar/Wind Harmer
0.004
274752CRETE EC ;2U
Adder
3.916
274753CRETE EC ;3U
Adder
3.916
964401AG1-302 GEN
Solar/Wind Harmer
0
274724RIVER EC ;11
Adder
8.349
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
274802UNIV PARK;5U
Adder
2.706
274826FISK ;BP
Adder
5.072
274800UNIV PARK;3U
Adder
2.697
23867002DVBSG1
50/50
15.559
972211AH1-690 GEN
50/50
307.104
23888502TROY G1
50/50
1.904
23888602TROY G2
50/50
1.904
241886AC2-103 GEN2
Solar/Wind Harmer
-0.001
970817AG2-515 GEN
Solar/Wind Harmer
11.024
945411AF1-206 GEN
Solar/Wind Harmer
-0.001
945641AF1-229 GEN
Solar/Wind Harmer
0.001
270499AE1-146 GEN
Solar/Wind Harmer
0.026
971549AH1-272 GEN
Solar/Wind Harmer
10.494
270297AD1-101 GEN
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.524
247607V1-011 GEN
Solar/Wind Harmer
0.001
971619AH1-309 GEN
Solar/Wind Harmer
1.812
965041AG1-368 GEN
Solar/Wind Harmer
3.881
965051AG1-369 GEN
Solar/Wind Harmer
1.924
971989AH1-539 GEN
Solar/Wind Harmer
1.649
971771AH1-392 GEN
Solar/Wind Harmer
3.814
971769AH1-391 GEN
Solar/Wind Harmer
4.151
270302AB2-170 GEN
Solar/Wind Harmer
0.002
270317AD1-130_GEN
Solar/Wind Harmer
0.005
971653AH1-327 GEN
Solar/Wind Harmer
0.517
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971347AH1-153 GEN
Solar/Wind Harmer
5.331
971567AH1-282 GEN
Solar/Wind Harmer
5.227
24189902OREGON_CT2
50/50
2.847
23888702TROY G3
50/50
1.904
972253AH1-711 GEN
50/50
58.156
23856402BAYSG1
50/50
1.209
23920202STRYCT
50/50
1.93
241885AC2-103 GEN1
Solar/Wind Harmer
-0.001
241858AF1-205_GEN
Solar/Wind Harmer
3.878
241808AF1-120 C
Solar/Wind Harmer
0.003
241840AF1-064_GEN
Solar/Wind Harmer
0.004
972301AH1-735 GEN
Adder
6.656
23906402RICHG1
Adder
1.331
23906502RICHG2&3
Adder
1.328
270361_3
Solar/Wind Harmer
4.06
960841AF2-375 GEN
Solar/Wind Harmer
-0.001
970515AG2-329 GEN
Solar/Wind Harmer
12.751
944231AF1-091 GEN
Solar/Wind Harmer
1.239
247522W1-056 GEN
Solar/Wind Harmer
0.001
246936BC-WTG1
Solar/Wind Harmer
0.168
270489AE1-102 GEN1
Solar/Wind Harmer
0.538
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.152
965421AG1-410 GEN
Solar/Wind Harmer
12.302
945111AF1-176 GEN
Solar/Wind Harmer
7.189
270505AE1-170 C O1
Solar/Wind Harmer
4.228
24695305TIMB G C
Solar/Wind Harmer
0.001
24639705ELKHART HY
Adder
0.086
270063AE2-323 C
Solar/Wind Harmer
0.003
247521TR3_G114
Solar/Wind Harmer
0.14
270246TR4_N_V150
Solar/Wind Harmer
0.025
24190002OREGON_ST1
50/50
3.831
24189802OREGON_CT1
50/50
2.906
23888802TROY G4
50/50
1.904
241996AE2-282_GEN
Solar/Wind Harmer
0.006
971677AH1-339 GEN
Solar/Wind Harmer
0.588
970621AG2-405 GEN
Solar/Wind Harmer
0.863
970623AG2-406 GEN
Solar/Wind Harmer
0.804
246938BC-WTG3
Solar/Wind Harmer
0.15
246937BC-WTG2
Solar/Wind Harmer
0.168
270007AE1-245 C
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
8.176
961051AF2-396 GEN
Solar/Wind Harmer
5.45
957891AF2-083 GEN
Solar/Wind Harmer
0.001
247620Y3-023
Adder
0.259
270216AD2-079_GEN
Solar/Wind Harmer
0.001
970611AG2-400 GEN
Solar/Wind Harmer
3.749
970627AG2-408 GEN
Solar/Wind Harmer
1.125
270526AF1-158 GEN
Solar/Wind Harmer
0.005
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
4.465
965791AG1-447 GEN
Solar/Wind Harmer
3.275
270224U2-072_GEN2
Solar/Wind Harmer
0
270227U2-072_GEN3
Solar/Wind Harmer
0
270228U2-072_GEN4
Solar/Wind Harmer
0
270231U2-072_GEN5
Solar/Wind Harmer
0
274808UNIV PK N;4U
Adder
2.34
274803UNIV PARK;6U
Adder
2.706
274888KELLY CRK;1U
Solar/Wind Harmer
0.189
274887GEN-1.85
Solar/Wind Harmer
0.085
276843GEN-1.7
Solar/Wind Harmer
0.104
958011AF2-095 GEN
Solar/Wind Harmer
4.64
274770LINCOLN ;1U
Adder
3.895
972038AH1-567 GEN2
Adder
0.169
276806AD2-047 C O1
Solar/Wind Harmer
1.826
970941AG2-585 GEN
Solar/Wind Harmer
4.027
274772LINCOLN ;3U
Adder
3.895
972228AH1-698 GEN2
Adder
1.705
274676JOLIET 29;8U
Adder
13.548
276897AD1-100 C
Solar/Wind Harmer
0.004
939351AE1-166 GEN
Solar/Wind Harmer
0
276893AG1-478 C
Solar/Wind Harmer
0.126
274729ELWOOD EC;1P
Adder
7.514
274730ELWOOD EC;6P
Adder
7.514
274734ELWOOD EC;8P
Adder
7.514
274736ELWOOD EC;9P
Adder
7.514
970707AG2-453 GEN
Solar/Wind Harmer
10.416
970513AG2-328 GEN
Solar/Wind Harmer
1.377
970517AG2-330 GEN
Solar/Wind Harmer
8.26
943121AE2-341 GEN
Solar/Wind Harmer
5.284
943591AF1-030 GEN
Solar/Wind Harmer
3.514
276694AA1-018 GEN2
Solar/Wind Harmer
0
971617AH1-308 GEN
Solar/Wind Harmer
2.61
274682WAUKEGAN ;7U
Adder
8.065
276805AD2-038 GEN
Solar/Wind Harmer
0.001
944531AF1-118 GEN
Solar/Wind Harmer
13.898
274872LEEDK;1U
Solar/Wind Harmer
0.114
24755605MDL-5G
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.1
276889AE2-281 GEN
Solar/Wind Harmer
0
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.329
274855GSG-6 ;RU
Solar/Wind Harmer
0.113
274850MENDOTA H;RU
Solar/Wind Harmer
0.036
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.055
959091AF2-200 GEN
Solar/Wind Harmer
6.137
972236AH1-702 GEN2
Adder
0.96
970571AG2-364 GEN
Solar/Wind Harmer
6.113
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
4.035
276157O29GEN1
Solar/Wind Harmer
0.485
962511AG1-100 GEN
Solar/Wind Helper
0.342
203830AF1-094 GEN
Solar/Wind Helper
0.324
959441AF2-235 GEN
Solar/Wind Helper
0.147
254305AE2-115 C
Solar/Wind Helper
0.113
20334926Z1-069 C
Solar/Wind Helper
0.646
965011AG1-365 GEN
Solar/Wind Harmer
3.749
270462AD2-086
Solar/Wind Harmer
0.008
970373AG2-245 GEN
Solar/Wind Harmer
7.209
270223U2-072_GEN1
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0.003
274751CRETE EC ;1U
Adder
3.916
274754CRETE EC ;4U
Adder
3.916
958381AF2-132 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.287
274723RIVER EC ;12
Adder
8.45
274812UNIV PK N;8U
Adder
2.351
276164X3-005 C
Solar/Wind Harmer
0
274801UNIV PARK;4U
Adder
2.697
276776AD2-060 GEN
Solar/Wind Harmer
0.336
274773LINCOLN ;4U
Adder
3.895
274774LINCOLN ;5U
Adder
3.895
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
4.026
274676JOLIET 29;8U
Adder
14.05
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
7.514
274674JOLIET 9 ;6U
Adder
7.038
970245AG2-165 GEN
Solar/Wind Harmer
1.377
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
2.526
276691AA1-018 GEN1
Solar/Wind Harmer
0.382
274682WAUKEGAN ;7U
Adder
8.065
274828WAUKEGAN ;BP
Adder
4.952
276901AD2-066 C O1
Solar/Wind Harmer
0.003
939401AE1-172 GEN
Solar/Wind Harmer
2.328
962781AG1-127 GEN
Solar/Wind Harmer
2.956
274872LEEDK;1U
Solar/Wind Harmer
0.002
24791305MDL-5G
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
1.624
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
276861AD2-134 GEN
Solar/Wind Harmer
0.055
957471AF2-041 GEN
Solar/Wind Harmer
9.206
959081AF2-199 GEN
Solar/Wind Harmer
3.069
971067AG2-660 GEN
Solar/Wind Harmer
1.023
274822ROCKFORD ;11
Adder
8.614
972235AH1-702 GEN1
Adder
1.104
970569AG2-363 GEN
Solar/Wind Harmer
9.17
970819AG2-516 GEN
Solar/Wind Harmer
3.66
971475AH1-234 GEN
Solar/Wind Harmer
1.477
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
4.035
274766LEE CO EC;7U
Adder
2.419
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.001
276158O29GEN2
Solar/Wind Harmer
0
241807AE2-176_GEN
Solar/Wind Helper
2.238
961971AG1-040 GEN
Solar/Wind Helper
0.334
203835AF1-098 GEN
Solar/Wind Helper
1.318
203860AG1-193 C
Solar/Wind Helper
0.149
241966AE1-183 GEN
Solar/Wind Helper
0.131
254303AC2-168 GEN
Solar/Wind Helper
0.076
963791AG1-232 GEN
Solar/Wind Harmer
4.679
270578AF1-285 GEN2
Solar/Wind Harmer
0.227
270536AF1-215 GEN2
Solar/Wind Harmer
0.004
270071AF1-092 GEN
Solar/Wind Harmer
6.329
274814UNIV PK N;0U
Adder
2.371
274807UNIV PK N;3U
Adder
2.366
274805UNIV PK N;1U
Adder
2.356
274811UNIV PK N;7U
Adder
2.351
958391AF2-133 GEN
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.085
274827FISK ;RP
Adder
3.595
960591AF2-350 GEN
Solar/Wind Harmer
3.222
274775LINCOLN ;6U
Adder
3.895
274776LINCOLN ;7U
Adder
3.895
274777LINCOLN ;8U
Adder
3.895
971611AH1-305 GEN
Solar/Wind Harmer
1.917
972227AH1-698 GEN1
Adder
1.201
274687WILL CNTY;4U
Adder
12.823
274687WILL CNTY;4U
Adder
12.823
274675JOLIET 29;7U
Adder
14.05
274675JOLIET 29;7U
Adder
13.548
274731ELWOOD EC;2P
Adder
7.514
274733ELWOOD EC;3P
Adder
7.514
274735ELWOOD EC;4P
Adder
7.514
274728ELWOOD EC;5P
Adder
7.514
970833AG2-524 GEN
Solar/Wind Harmer
3.49
970833AG2-524 GEN
Solar/Wind Harmer
2.327
274746AC1-111 G10
Adder
2.526
274744AC1-111 GEN8
Adder
2.526
270024AE2-089 GEN
Solar/Wind Harmer
0.003
276868AE1-113 GEN
Solar/Wind Harmer
0.623
276882AE2-255 GEN
Solar/Wind Harmer
0.363
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0
270181AB1-006 GEN2
Solar/Wind Harmer
0
971177AH1-047 GEN
Solar/Wind Harmer
1.907
971411AH1-196 GEN
Solar/Wind Harmer
4.626
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
1.202
24729505KEY G4
Adder
2.855
971171AH1-044 GEN
Solar/Wind Harmer
6.137
274823ROCKFORD ;21
Adder
8.551
926823AC1-168 GEN
Solar/Wind Harmer
0.519
970169AG2-114 GEN
Solar/Wind Harmer
3.05
276612AE2-035 GEN
Solar/Wind Harmer
0.001
971681AH1-341 GEN
Solar/Wind Harmer
4.885
24386205FR-12G C
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
24387005FR-3G C
Solar/Wind Harmer
0.001
961011AF2-392 GEN
Solar/Wind Harmer
1.766
957751AF2-069 GEN
Solar/Wind Harmer
0.099
241982AE2-343 S C
Solar/Wind Helper
0.119
254304AE2-114 C
Solar/Wind Helper
0.113
203846AF2-130 C
Solar/Wind Helper
0.248
241997AF1-093 GEN
Solar/Wind Helper
0.131
203804AE2-113_GEN
Solar/Wind Helper
0.868
274771LINCOLN ;2U
Adder
3.895
972259AH1-714 GEN
Adder
8.743
274674JOLIET 9 ;6U
Adder
7.038
942221AE2-234 GEN
Solar/Wind Harmer
0.016
970321AG2-212 GEN
Solar/Wind Harmer
1.377
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
958481AF2-142 GEN
Solar/Wind Harmer
4.726
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.426
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
971573AH1-285 GEN
Solar/Wind Harmer
0.585
274696ROCKY RD ;4P
Adder
5.113
274695ROCKY RD ;2P
Adder
4.995
274693ROCKY RD ;1P
Adder
4.946
274697ROCKY RD ;3P
Adder
1.357
274683WAUKEGAN ;8U
Adder
9.448
274683WAUKEGAN ;8U
Adder
7.964
958491AF2-143 GEN
Solar/Wind Harmer
4.684
962691AG1-118 GEN
Solar/Wind Harmer
9.334
274879MINONK ;1U
Solar/Wind Harmer
0.131
970921AG2-575 GEN
Solar/Wind Harmer
3.106
970921AG2-575 GEN
Solar/Wind Harmer
1.035
942991AE2-321 GEN
Solar/Wind Harmer
3.454
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
971333AH1-146 GEN
Solar/Wind Harmer
6.163
971335AH1-147 GEN
Solar/Wind Harmer
6.163
971341AH1-150 GEN
Solar/Wind Harmer
6.137
971343AH1-151 GEN
Solar/Wind Harmer
6.137
274856ECOGROVE ;U1
Solar/Wind Harmer
0.072
276611AD2-172 GEN
Solar/Wind Harmer
0.001
938861AE1-114 GEN
Solar/Wind Harmer
1.719
274764LEE CO EC;5U
Adder
4.044
274765LEE CO EC;6U
Adder
4.044
274762LEE CO EC;3U
Adder
4.035
274763LEE CO EC;4U
Adder
3.996
276603SUBLETTE C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.342
274851PROVIDENC;RU
Solar/Wind Harmer
0
274849CRESCENT ;1U
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.118
276646AC1-214 GEN2
Solar/Wind Harmer
0.118
276741O09 GEN1
Solar/Wind Harmer
0.107
276708O09 GEN2
Solar/Wind Harmer
0.107
203947AF1-006 C
Solar/Wind Helper
0.381
203980AG1-197 GEN
Solar/Wind Helper
0.249
203979AG1-198 GEN
Solar/Wind Helper
0.194
241967AE2-285_GEN
Solar/Wind Helper
0.341
241801AE1-079 GEN
Solar/Wind Helper
0.133
241985AE1-237 GEN
Solar/Wind Helper
0.132
962101AG1-054 GEN
Solar/Wind Helper
0.329
946381AF1-302 GEN
Solar/Wind Helper
0.105
238217AF1-153 C O1
Solar/Wind Helper
0.112
991177J1571 G
External Queue
15.847536087036133
990527J1329
External Queue
1.9070898294448853
990142J1224
External Queue
13.940826416015625
991182J1586 G
External Queue
26.137367248535156
LAGNLTFEXP_LAGN->PJM
CLTF
4.961
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.186
TVALTFEXP_TVA->PJM
CLTF
2.246
CPLELTFEXP_CPLE->PJM
CLTF
0.328
CBM West 2LTFEXP_CBM-W2->PJM
CBM
39.692
NYPJM->LTFIMP_NY
CLTF
2.031
LGEELTFEXP_LGEE->PJM
CLTF
2.008
WECLTFEXP_WEC->PJM
CLTF
1.673
AG2-052LTFEXP_AG2-052->PJM
LTF
0.108
AH1-155LTFEXP_AH1-155->PJM
LTF
0.162
CBM West 1LTFEXP_CBM-W1->PJM
CBM
96.337
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.893
MECLTFEXP_MEC->PJM
CLTF
6.512
SIGELTFEXP_SIGE->PJM
CLTF
0.168

Details for 02DAV-BE-02HAYES 345.0 kV Ckt 1 line l/o ATSI_P1-2_OEC-345-824_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02DAV-BE-02HAYES 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_OEC-345-824_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:136.39 %
Rating:1892.0 MVA
Rating Type:B
MVA to Mitigate:2580.58
MW Contribution:10.51
Bus #Bus NameTypeMW Contribution
24189902OREGON_CT2
50/50
2.849
23888702TROY G3
50/50
1.905
972253AH1-711 GEN
50/50
58.19
23856402BAYSG1
50/50
1.21
23920202STRYCT
50/50
1.931
241858AF1-205_GEN
Solar/Wind Harmer
3.881
241808AF1-120 C
Solar/Wind Harmer
0.003
241840AF1-064_GEN
Solar/Wind Harmer
0.004
972301AH1-735 GEN
Adder
6.662
23906402RICHG1
Adder
1.332
23906502RICHG2&3
Adder
1.329
270361_3
Solar/Wind Harmer
4.064
960841AF2-375 GEN
Solar/Wind Harmer
-0.001
970515AG2-329 GEN
Solar/Wind Harmer
12.77
944231AF1-091 GEN
Solar/Wind Harmer
1.241
247522W1-056 GEN
Solar/Wind Harmer
0.001
246936BC-WTG1
Solar/Wind Harmer
0.168
270489AE1-102 GEN1
Solar/Wind Harmer
0.539
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.155
965421AG1-410 GEN
Solar/Wind Harmer
12.324
945111AF1-176 GEN
Solar/Wind Harmer
7.202
270505AE1-170 C O1
Solar/Wind Harmer
4.236
24695305TIMB G C
Solar/Wind Harmer
0.001
24639705ELKHART HY
Adder
0.086
270063AE2-323 C
Solar/Wind Harmer
0.003
247521TR3_G114
Solar/Wind Harmer
0.141
270246TR4_N_V150
Solar/Wind Harmer
0.025
965011AG1-365 GEN
Solar/Wind Harmer
3.756
270462AD2-086
Solar/Wind Harmer
0.008
970373AG2-245 GEN
Solar/Wind Harmer
7.224
270223U2-072_GEN1
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0.003
274751CRETE EC ;1U
Adder
3.925
274754CRETE EC ;4U
Adder
3.925
958381AF2-132 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.296
274723RIVER EC ;12
Adder
8.468
274812UNIV PK N;8U
Adder
2.356
276164X3-005 C
Solar/Wind Harmer
0
274801UNIV PARK;4U
Adder
2.703
276776AD2-060 GEN
Solar/Wind Harmer
0.337
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
274773LINCOLN ;4U
Adder
3.904
274774LINCOLN ;5U
Adder
3.904
971605AH1-302 GEN
Solar/Wind Harmer
4.035
274676JOLIET 29;8U
Adder
14.081
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
7.531
274674JOLIET 9 ;6U
Adder
7.053
970245AG2-165 GEN
Solar/Wind Harmer
1.38
23867002DVBSG1
50/50
15.565
972211AH1-690 GEN
50/50
307.274
23888502TROY G1
50/50
1.905
23888602TROY G2
50/50
1.905
970817AG2-515 GEN
Solar/Wind Harmer
11.031
945411AF1-206 GEN
Solar/Wind Harmer
-0.001
945641AF1-229 GEN
Solar/Wind Harmer
0.001
270499AE1-146 GEN
Solar/Wind Harmer
0.026
971549AH1-272 GEN
Solar/Wind Harmer
10.508
270297AD1-101 GEN
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.525
247607V1-011 GEN
Solar/Wind Harmer
0.001
971619AH1-309 GEN
Solar/Wind Harmer
1.815
965041AG1-368 GEN
Solar/Wind Harmer
3.888
965051AG1-369 GEN
Solar/Wind Harmer
1.928
971989AH1-539 GEN
Solar/Wind Harmer
1.652
971771AH1-392 GEN
Solar/Wind Harmer
3.821
971769AH1-391 GEN
Solar/Wind Harmer
4.158
270302AB2-170 GEN
Solar/Wind Harmer
0.002
270317AD1-130_GEN
Solar/Wind Harmer
0.005
971653AH1-327 GEN
Solar/Wind Harmer
0.518
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971347AH1-153 GEN
Solar/Wind Harmer
5.341
971567AH1-282 GEN
Solar/Wind Harmer
5.238
963791AG1-232 GEN
Solar/Wind Harmer
4.689
270578AF1-285 GEN2
Solar/Wind Harmer
0.227
270536AF1-215 GEN2
Solar/Wind Harmer
0.004
270071AF1-092 GEN
Solar/Wind Harmer
6.342
274814UNIV PK N;0U
Adder
2.376
274807UNIV PK N;3U
Adder
2.371
274805UNIV PK N;1U
Adder
2.361
274811UNIV PK N;7U
Adder
2.356
958391AF2-133 GEN
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.085
274827FISK ;RP
Adder
3.602
960591AF2-350 GEN
Solar/Wind Harmer
3.229
274775LINCOLN ;6U
Adder
3.904
274776LINCOLN ;7U
Adder
3.904
274777LINCOLN ;8U
Adder
3.904
971611AH1-305 GEN
Solar/Wind Harmer
1.922
972227AH1-698 GEN1
Adder
1.203
274687WILL CNTY;4U
Adder
12.851
274687WILL CNTY;4U
Adder
12.851
274675JOLIET 29;7U
Adder
14.081
274675JOLIET 29;7U
Adder
13.578
274731ELWOOD EC;2P
Adder
7.53
274733ELWOOD EC;3P
Adder
7.53
23929302BS-PKR
50/50
2.13
241832AE2-181_GEN
Solar/Wind Harmer
0.004
958321AF2-126 GEN
Solar/Wind Harmer
1.13
23906502RICHG2&3
Adder
1.329
270541AE2-072 C
Solar/Wind Harmer
0.008
270575GUS2 35KV
Solar/Wind Harmer
4.064
970217AG2-149 GEN
Solar/Wind Harmer
4.257
270404AC1-167 GEN
Solar/Wind Harmer
0.002
247604X1-042
Adder
0.265
270258AD1-119 GEN
Solar/Wind Harmer
0.001
24441205WTRV SLR C
Solar/Wind Harmer
0
270491AE1-102 GEN2
Solar/Wind Harmer
0.539
270588AE1-091_GEN
Solar/Wind Harmer
3.213
945111AF1-176 GEN
Solar/Wind Harmer
3.272
24642205MAYFLWER
Adder
0.357
247643Z2-116 C
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
2.514
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.025
959331AF2-224 GEN
Solar/Wind Harmer
2.629
965021AG1-366 GEN
Solar/Wind Harmer
1.252
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270043AE2-236 GEN
Solar/Wind Harmer
2.287
970349AG2-230 GEN
Solar/Wind Harmer
5.341
270391AF1-285 GEN3
Solar/Wind Harmer
0.227
270535AF1-215 GEN1
Solar/Wind Harmer
0.004
274752CRETE EC ;2U
Adder
3.925
274753CRETE EC ;3U
Adder
3.925
964401AG1-302 GEN
Solar/Wind Harmer
0
274724RIVER EC ;11
Adder
8.367
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
274802UNIV PARK;5U
Adder
2.712
274826FISK ;BP
Adder
5.083
274800UNIV PARK;3U
Adder
2.703
972038AH1-567 GEN2
Adder
0.169
276806AD2-047 C O1
Solar/Wind Harmer
1.83
970941AG2-585 GEN
Solar/Wind Harmer
4.036
274772LINCOLN ;3U
Adder
3.904
972228AH1-698 GEN2
Adder
1.709
274676JOLIET 29;8U
Adder
13.578
276897AD1-100 C
Solar/Wind Harmer
0.004
939351AE1-166 GEN
Solar/Wind Harmer
0
276893AG1-478 C
Solar/Wind Harmer
0.127
274729ELWOOD EC;1P
Adder
7.53
274730ELWOOD EC;6P
Adder
7.531
274734ELWOOD EC;8P
Adder
7.531
274736ELWOOD EC;9P
Adder
7.531
970707AG2-453 GEN
Solar/Wind Harmer
10.439
970513AG2-328 GEN
Solar/Wind Harmer
1.38
970517AG2-330 GEN
Solar/Wind Harmer
8.279
943121AE2-341 GEN
Solar/Wind Harmer
5.296
943591AF1-030 GEN
Solar/Wind Harmer
3.522
276694AA1-018 GEN2
Solar/Wind Harmer
0
971617AH1-308 GEN
Solar/Wind Harmer
2.616
274735ELWOOD EC;4P
Adder
7.53
274728ELWOOD EC;5P
Adder
7.531
970833AG2-524 GEN
Solar/Wind Harmer
3.498
970833AG2-524 GEN
Solar/Wind Harmer
2.332
274746AC1-111 G10
Adder
2.532
274744AC1-111 GEN8
Adder
2.532
270024AE2-089 GEN
Solar/Wind Harmer
0.003
276868AE1-113 GEN
Solar/Wind Harmer
0.625
276882AE2-255 GEN
Solar/Wind Harmer
0.364
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0
270181AB1-006 GEN2
Solar/Wind Harmer
0
971177AH1-047 GEN
Solar/Wind Harmer
1.911
971411AH1-196 GEN
Solar/Wind Harmer
4.636
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
1.204
24729505KEY G4
Adder
2.862
971171AH1-044 GEN
Solar/Wind Harmer
6.151
274823ROCKFORD ;21
Adder
8.571
926823AC1-168 GEN
Solar/Wind Harmer
0.52
970169AG2-114 GEN
Solar/Wind Harmer
3.057
276612AE2-035 GEN
Solar/Wind Harmer
0.001
971681AH1-341 GEN
Solar/Wind Harmer
4.897
24386205FR-12G C
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
24387005FR-3G C
Solar/Wind Harmer
0.001
961011AF2-392 GEN
Solar/Wind Harmer
1.771
957751AF2-069 GEN
Solar/Wind Harmer
0.099
241886AC2-103 GEN2
Solar/Wind Helper
3.958
241982AE2-343 S C
Solar/Wind Helper
0.118
254304AE2-114 C
Solar/Wind Helper
0.113
203846AF2-130 C
Solar/Wind Helper
0.248
241997AF1-093 GEN
Solar/Wind Helper
0.131
203804AE2-113_GEN
Solar/Wind Helper
0.866
24190002OREGON_ST1
50/50
3.833
24189802OREGON_CT1
50/50
2.907
23888802TROY G4
50/50
1.905
241996AE2-282_GEN
Solar/Wind Harmer
0.006
971677AH1-339 GEN
Solar/Wind Harmer
0.588
970621AG2-405 GEN
Solar/Wind Harmer
0.864
970623AG2-406 GEN
Solar/Wind Harmer
0.806
246938BC-WTG3
Solar/Wind Harmer
0.15
246937BC-WTG2
Solar/Wind Harmer
0.168
270007AE1-245 C
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
8.19
961051AF2-396 GEN
Solar/Wind Harmer
5.46
957891AF2-083 GEN
Solar/Wind Harmer
0.001
247620Y3-023
Adder
0.259
270216AD2-079_GEN
Solar/Wind Harmer
0.001
970611AG2-400 GEN
Solar/Wind Harmer
3.756
970627AG2-408 GEN
Solar/Wind Harmer
1.127
270526AF1-158 GEN
Solar/Wind Harmer
0.005
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
4.474
965791AG1-447 GEN
Solar/Wind Harmer
3.281
270224U2-072_GEN2
Solar/Wind Harmer
0
270227U2-072_GEN3
Solar/Wind Harmer
0
270228U2-072_GEN4
Solar/Wind Harmer
0
270231U2-072_GEN5
Solar/Wind Harmer
0
274808UNIV PK N;4U
Adder
2.345
274803UNIV PARK;6U
Adder
2.712
274888KELLY CRK;1U
Solar/Wind Harmer
0.19
274887GEN-1.85
Solar/Wind Harmer
0.085
276843GEN-1.7
Solar/Wind Harmer
0.105
958011AF2-095 GEN
Solar/Wind Harmer
4.65
274770LINCOLN ;1U
Adder
3.904
274771LINCOLN ;2U
Adder
3.904
972259AH1-714 GEN
Adder
8.763
274674JOLIET 9 ;6U
Adder
7.053
942221AE2-234 GEN
Solar/Wind Harmer
0.016
970321AG2-212 GEN
Solar/Wind Harmer
1.38
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
958481AF2-142 GEN
Solar/Wind Harmer
4.737
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
8.083
276805AD2-038 GEN
Solar/Wind Harmer
0.001
944531AF1-118 GEN
Solar/Wind Harmer
13.93
274872LEEDK;1U
Solar/Wind Harmer
0.114
24755605MDL-5G
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.107
276889AE2-281 GEN
Solar/Wind Harmer
0
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.33
274855GSG-6 ;RU
Solar/Wind Harmer
0.113
274850MENDOTA H;RU
Solar/Wind Harmer
0.036
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.055
959091AF2-200 GEN
Solar/Wind Harmer
6.151
970571AG2-364 GEN
Solar/Wind Harmer
6.128
972236AH1-702 GEN2
Adder
0.963
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
4.044
276157O29GEN1
Solar/Wind Harmer
0.487
962511AG1-100 GEN
Solar/Wind Helper
0.341
203830AF1-094 GEN
Solar/Wind Helper
0.323
959441AF2-235 GEN
Solar/Wind Helper
0.147
254305AE2-115 C
Solar/Wind Helper
0.113
20334926Z1-069 C
Solar/Wind Helper
0.645
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
2.532
276691AA1-018 GEN1
Solar/Wind Harmer
0.383
274682WAUKEGAN ;7U
Adder
8.083
274828WAUKEGAN ;BP
Adder
4.964
276901AD2-066 C O1
Solar/Wind Harmer
0.003
939401AE1-172 GEN
Solar/Wind Harmer
2.333
962781AG1-127 GEN
Solar/Wind Harmer
2.963
274872LEEDK;1U
Solar/Wind Harmer
0.002
24791305MDL-5G
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
1.628
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
276861AD2-134 GEN
Solar/Wind Harmer
0.055
957471AF2-041 GEN
Solar/Wind Harmer
9.227
959081AF2-199 GEN
Solar/Wind Harmer
3.076
971067AG2-660 GEN
Solar/Wind Harmer
1.025
274822ROCKFORD ;11
Adder
8.634
970569AG2-363 GEN
Solar/Wind Harmer
9.191
972235AH1-702 GEN1
Adder
1.107
970819AG2-516 GEN
Solar/Wind Harmer
3.668
971475AH1-234 GEN
Solar/Wind Harmer
1.481
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
4.044
274766LEE CO EC;7U
Adder
2.424
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.001
276158O29GEN2
Solar/Wind Harmer
0
241885AC2-103 GEN1
Solar/Wind Helper
3.958
241807AE2-176_GEN
Solar/Wind Helper
2.236
961971AG1-040 GEN
Solar/Wind Helper
0.334
203835AF1-098 GEN
Solar/Wind Helper
1.316
203860AG1-193 C
Solar/Wind Helper
0.149
241966AE1-183 GEN
Solar/Wind Helper
0.131
254303AC2-168 GEN
Solar/Wind Helper
0.076
274862TOP CROP ;2U
Solar/Wind Harmer
0.427
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
971573AH1-285 GEN
Solar/Wind Harmer
0.586
274696ROCKY RD ;4P
Adder
5.124
274695ROCKY RD ;2P
Adder
5.006
274693ROCKY RD ;1P
Adder
4.957
274697ROCKY RD ;3P
Adder
1.36
274683WAUKEGAN ;8U
Adder
9.469
274683WAUKEGAN ;8U
Adder
7.982
958491AF2-143 GEN
Solar/Wind Harmer
4.695
962691AG1-118 GEN
Solar/Wind Harmer
9.356
274879MINONK ;1U
Solar/Wind Harmer
0.131
970921AG2-575 GEN
Solar/Wind Harmer
3.113
970921AG2-575 GEN
Solar/Wind Harmer
1.038
942991AE2-321 GEN
Solar/Wind Harmer
3.462
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
971333AH1-146 GEN
Solar/Wind Harmer
6.177
971335AH1-147 GEN
Solar/Wind Harmer
6.177
971341AH1-150 GEN
Solar/Wind Harmer
6.151
971343AH1-151 GEN
Solar/Wind Harmer
6.151
274856ECOGROVE ;U1
Solar/Wind Harmer
0.072
276611AD2-172 GEN
Solar/Wind Harmer
0.001
938861AE1-114 GEN
Solar/Wind Harmer
1.723
274764LEE CO EC;5U
Adder
4.053
274765LEE CO EC;6U
Adder
4.053
274762LEE CO EC;3U
Adder
4.044
274763LEE CO EC;4U
Adder
4.006
276603SUBLETTE C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.342
274851PROVIDENC;RU
Solar/Wind Harmer
0
274849CRESCENT ;1U
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.118
276646AC1-214 GEN2
Solar/Wind Harmer
0.118
276741O09 GEN1
Solar/Wind Harmer
0.107
276708O09 GEN2
Solar/Wind Harmer
0.107
276782AC1-033 GEN
Solar/Wind Harmer
0
203947AF1-006 C
Solar/Wind Helper
0.38
203980AG1-197 GEN
Solar/Wind Helper
0.249
203979AG1-198 GEN
Solar/Wind Helper
0.194
241967AE2-285_GEN
Solar/Wind Helper
0.34
241801AE1-079 GEN
Solar/Wind Helper
0.132
241985AE1-237 GEN
Solar/Wind Helper
0.132
962101AG1-054 GEN
Solar/Wind Helper
0.328
946381AF1-302 GEN
Solar/Wind Helper
0.105
238217AF1-153 C O1
Solar/Wind Helper
0.111
991177J1571 G
External Queue
15.847536087036133
990527J1329
External Queue
1.9070898294448853
990142J1224
External Queue
13.940826416015625
991182J1586 G
External Queue
26.137367248535156
LAGNLTFEXP_LAGN->PJM
CLTF
4.982
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.217
TVALTFEXP_TVA->PJM
CLTF
2.257
CPLELTFEXP_CPLE->PJM
CLTF
0.339
CBM West 2LTFEXP_CBM-W2->PJM
CBM
39.829
NYPJM->LTFIMP_NY
CLTF
2.024
LGEELTFEXP_LGEE->PJM
CLTF
2.015
WECLTFEXP_WEC->PJM
CLTF
1.677
AG2-052LTFEXP_AG2-052->PJM
LTF
0.108
AH1-155LTFEXP_AH1-155->PJM
LTF
0.162
CBM West 1LTFEXP_CBM-W1->PJM
CBM
96.485
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.932
MECLTFEXP_MEC->PJM
CLTF
6.529
SIGELTFEXP_SIGE->PJM
CLTF
0.169

Details for 02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line l/o ATSI_P2-3_OEC-345-1152-F1_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_OEC-345-1152-F1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:155.03 %
Rating:1646.0 MVA
Rating Type:B
MVA to Mitigate:2551.84
MW Contribution:13.0
Bus #Bus NameTypeMW Contribution
23867002DVBSG1
50/50
14.157
972211AH1-690 GEN
50/50
290.294
23888502TROY G1
50/50
1.813
23888602TROY G2
50/50
1.813
970817AG2-515 GEN
Solar/Wind Harmer
15.206
945411AF1-206 GEN
Solar/Wind Harmer
8.026
945641AF1-229 GEN
Solar/Wind Harmer
3.439
24189902OREGON_CT2
50/50
2.691
23888702TROY G3
50/50
1.813
972253AH1-711 GEN
50/50
55.392
23856402BAYSG1
50/50
1.233
23920202STRYCT
50/50
1.896
241858AF1-205_GEN
Solar/Wind Harmer
5.467
241808AF1-120 C
Solar/Wind Harmer
1.198
241840AF1-064_GEN
Solar/Wind Harmer
1.359
972301AH1-735 GEN
Adder
6.555
23906402RICHG1
Adder
1.311
23906502RICHG2&3
Adder
1.308
270361_3
Solar/Wind Harmer
7.869
960841AF2-375 GEN
Solar/Wind Harmer
3.486
970515AG2-329 GEN
Solar/Wind Harmer
10.065
247522W1-056 GEN
Solar/Wind Harmer
1.487
944231AF1-091 GEN
Solar/Wind Harmer
2.457
246936BC-WTG1
Solar/Wind Harmer
2.274
270489AE1-102 GEN1
Solar/Wind Harmer
0.755
965421AG1-410 GEN
Solar/Wind Harmer
17.272
270449AD2-020 GEN
Solar/Wind Harmer
1.604
943021AE2-325 GEN
Solar/Wind Harmer
2.085
24695305TIMB G C
Solar/Wind Harmer
3.084
945111AF1-176 GEN
Solar/Wind Harmer
9.989
270505AE1-170 C O1
Solar/Wind Harmer
8.391
24639705ELKHART HY
Adder
0.083
247521TR3_G114
Solar/Wind Harmer
1.822
270246TR4_N_V150
Solar/Wind Harmer
0.461
270063AE2-323 C
Solar/Wind Harmer
1.189
965011AG1-365 GEN
Solar/Wind Harmer
5.249
270462AD2-086
Solar/Wind Harmer
3.612
270223U2-072_GEN1
Solar/Wind Harmer
0.951
270578AF1-285 GEN2
Solar/Wind Harmer
0.581
270391AF1-285 GEN3
Solar/Wind Harmer
0.581
970373AG2-245 GEN
Solar/Wind Harmer
10.039
270055AF2-134 C O1
Solar/Wind Harmer
1.419
274751CRETE EC ;1U
Adder
2.258
274754CRETE EC ;4U
Adder
2.258
958381AF2-132 GEN
Solar/Wind Harmer
4.176
964861AG1-349 GEN
Solar/Wind Harmer
3.612
971917AH1-482 GEN
Solar/Wind Harmer
4.168
274723RIVER EC ;12
Adder
8.214
274812UNIV PK N;8U
Adder
2.285
276164X3-005 C
Solar/Wind Harmer
0.319
274801UNIV PARK;4U
Adder
2.622
276776AD2-060 GEN
Solar/Wind Harmer
0.19
940581AE2-045 GEN
Solar/Wind Harmer
4.579
971605AH1-302 GEN
Solar/Wind Harmer
3.915
972207SS24-0001
Solar/Wind Harmer
9.894
274773LINCOLN ;4U
Adder
2.783
274774LINCOLN ;5U
Adder
2.783
274676JOLIET 29;8U
Adder
13.662
941551AE2-152 GEN
Solar/Wind Harmer
2.017
274732ELWOOD EC;7P
Adder
7.307
274674JOLIET 9 ;6U
Adder
6.844
970245AG2-165 GEN
Solar/Wind Harmer
7.911
274871GR RIDGE ;2U
Solar/Wind Harmer
3.399
274745AC1-111 GEN9
Adder
2.457
276691AA1-018 GEN1
Solar/Wind Harmer
0.205
274682WAUKEGAN ;7U
Adder
7.844
274828WAUKEGAN ;BP
Adder
4.817
241885AC2-103 GEN1
Solar/Wind Helper
9.152
961971AG1-040 GEN
Solar/Wind Helper
0.328
203835AF1-098 GEN
Solar/Wind Helper
1.294
203860AG1-193 C
Solar/Wind Helper
0.147
241966AE1-183 GEN
Solar/Wind Helper
0.128
254303AC2-168 GEN
Solar/Wind Helper
0.075
23929302BS-PKR
50/50
2.169
241832AE2-181_GEN
Solar/Wind Harmer
1.949
958321AF2-126 GEN
Solar/Wind Harmer
1.457
23906502RICHG2&3
Adder
1.308
270541AE2-072 C
Solar/Wind Harmer
4.233
270575GUS2 35KV
Solar/Wind Harmer
9.271
970217AG2-149 GEN
Solar/Wind Harmer
22.195
270044AE2-322 C
Solar/Wind Harmer
0.848
270404AC1-167 GEN
Solar/Wind Harmer
0.706
270258AD1-119 GEN
Solar/Wind Harmer
1.728
247604X1-042
Adder
0.256
24441205WTRV SLR C
Solar/Wind Harmer
0.081
270588AE1-091_GEN
Solar/Wind Harmer
6.56
958091AF2-103 GEN
Solar/Wind Harmer
0.094
270491AE1-102 GEN2
Solar/Wind Harmer
0.755
945111AF1-176 GEN
Solar/Wind Harmer
3.166
24642205MAYFLWER
Adder
0.346
270191TR4_S_V150
Solar/Wind Harmer
1.626
270247TR4_N_V136
Solar/Wind Harmer
0.461
970031AG2-029 GEN
Solar/Wind Harmer
16.144
247643Z2-116 C
Solar/Wind Harmer
0.037
959331AF2-224 GEN
Solar/Wind Harmer
5.249
965021AG1-366 GEN
Solar/Wind Harmer
1.221
270485AE1-090_GEN
Solar/Wind Harmer
0.314
270043AE2-236 GEN
Solar/Wind Harmer
2.733
970349AG2-230 GEN
Solar/Wind Harmer
7.421
942871AE2-306 GEN
Solar/Wind Harmer
0.436
270391AF1-285 GEN3
Solar/Wind Harmer
0.224
270535AF1-215 GEN1
Solar/Wind Harmer
2.129
972231SS25-0005
Solar/Wind Harmer
4.384
972181SS23-001
Solar/Wind Harmer
2.74
274752CRETE EC ;2U
Adder
2.258
274753CRETE EC ;3U
Adder
2.258
964401AG1-302 GEN
Solar/Wind Harmer
4.176
274724RIVER EC ;11
Adder
8.116
959141AF2-205 GEN
Solar/Wind Harmer
2.738
274802UNIV PARK;5U
Adder
2.631
274826FISK ;BP
Adder
4.931
274800UNIV PARK;3U
Adder
2.622
972038AH1-567 GEN2
Adder
0.164
276772AC2-154 GEN
Solar/Wind Harmer
1.252
276806AD2-047 C O1
Solar/Wind Harmer
4.804
970941AG2-585 GEN
Solar/Wind Harmer
5.613
274772LINCOLN ;3U
Adder
2.783
972228AH1-698 GEN2
Adder
1.658
274676JOLIET 29;8U
Adder
13.174
276897AD1-100 C
Solar/Wind Harmer
12.909
939351AE1-166 GEN
Solar/Wind Harmer
2.638
276893AG1-478 C
Solar/Wind Harmer
0.186
274730ELWOOD EC;6P
Adder
7.307
274734ELWOOD EC;8P
Adder
7.307
274736ELWOOD EC;9P
Adder
7.307
970707AG2-453 GEN
Solar/Wind Harmer
12.445
274729ELWOOD EC;1P
Adder
7.307
970513AG2-328 GEN
Solar/Wind Harmer
7.911
970517AG2-330 GEN
Solar/Wind Harmer
7.175
971617AH1-308 GEN
Solar/Wind Harmer
2.555
943121AE2-341 GEN
Solar/Wind Harmer
6.59
943591AF1-030 GEN
Solar/Wind Harmer
4.393
276694AA1-018 GEN2
Solar/Wind Harmer
2.772
274682WAUKEGAN ;7U
Adder
7.844
962511AG1-100 GEN
Solar/Wind Helper
0.336
203830AF1-094 GEN
Solar/Wind Helper
0.318
959441AF2-235 GEN
Solar/Wind Helper
0.144
254305AE2-115 C
Solar/Wind Helper
0.111
20334926Z1-069 C
Solar/Wind Helper
0.633
270499AE1-146 GEN
Solar/Wind Harmer
2.201
971549AH1-272 GEN
Solar/Wind Harmer
13.004
270297AD1-101 GEN
Solar/Wind Harmer
1.871
247607V1-011 GEN
Solar/Wind Harmer
2.303
957201AF2-014 GEN
Solar/Wind Harmer
2.636
270435AC2-044 GEN
Solar/Wind Harmer
1.162
944161AF1-084 GEN
Solar/Wind Harmer
1.282
966831AG1-554 GEN
Solar/Wind Harmer
0.674
971989AH1-539 GEN
Solar/Wind Harmer
7.284
965041AG1-368 GEN
Solar/Wind Harmer
5.453
965051AG1-369 GEN
Solar/Wind Harmer
2.706
971771AH1-392 GEN
Solar/Wind Harmer
4.773
270302AB2-170 GEN
Solar/Wind Harmer
4.342
270317AD1-130_GEN
Solar/Wind Harmer
1.665
971769AH1-391 GEN
Solar/Wind Harmer
5.17
971567AH1-282 GEN
Solar/Wind Harmer
7.463
960681AF2-359 GEN
Solar/Wind Harmer
1.878
971347AH1-153 GEN
Solar/Wind Harmer
7.421
963791AG1-232 GEN
Solar/Wind Harmer
6.559
270578AF1-285 GEN2
Solar/Wind Harmer
0.224
270536AF1-215 GEN2
Solar/Wind Harmer
2.129
270071AF1-092 GEN
Solar/Wind Harmer
6.925
274814UNIV PK N;0U
Adder
2.305
274807UNIV PK N;3U
Adder
2.3
274805UNIV PK N;1U
Adder
2.29
274811UNIV PK N;7U
Adder
2.285
958391AF2-133 GEN
Solar/Wind Harmer
4.138
972037AH1-567 GEN1
Adder
0.083
274827FISK ;RP
Adder
3.495
960591AF2-350 GEN
Solar/Wind Harmer
4.49
274775LINCOLN ;6U
Adder
2.783
274776LINCOLN ;7U
Adder
2.783
274777LINCOLN ;8U
Adder
2.783
972227AH1-698 GEN1
Adder
1.168
274687WILL CNTY;4U
Adder
12.469
274687WILL CNTY;4U
Adder
12.469
274675JOLIET 29;7U
Adder
13.662
274675JOLIET 29;7U
Adder
13.175
274728ELWOOD EC;5P
Adder
7.307
274731ELWOOD EC;2P
Adder
7.307
274733ELWOOD EC;3P
Adder
7.307
274735ELWOOD EC;4P
Adder
7.307
970833AG2-524 GEN
Solar/Wind Harmer
3.861
970833AG2-524 GEN
Solar/Wind Harmer
1.796
274746AC1-111 G10
Adder
2.457
274744AC1-111 GEN8
Adder
2.457
270024AE2-089 GEN
Solar/Wind Harmer
2.062
241886AC2-103 GEN2
Solar/Wind Helper
9.152
241982AE2-343 S C
Solar/Wind Helper
0.116
254304AE2-114 C
Solar/Wind Helper
0.111
203846AF2-130 C
Solar/Wind Helper
0.243
241997AF1-093 GEN
Solar/Wind Helper
0.128
203804AE2-113_GEN
Solar/Wind Helper
0.851
24190002OREGON_ST1
50/50
3.621
24189802OREGON_CT1
50/50
2.747
23888802TROY G4
50/50
1.813
241996AE2-282_GEN
Solar/Wind Harmer
2.149
971677AH1-339 GEN
Solar/Wind Harmer
6.251
270007AE1-245 C
Solar/Wind Harmer
3.456
246938BC-WTG3
Solar/Wind Harmer
2.313
246937BC-WTG2
Solar/Wind Harmer
2.274
942801AE2-298 GEN
Solar/Wind Harmer
0.875
961051AF2-396 GEN
Solar/Wind Harmer
9.012
961051AF2-396 GEN
Solar/Wind Harmer
4.192
960981AF2-389 GEN
Solar/Wind Harmer
0.843
957891AF2-083 GEN
Solar/Wind Harmer
1.881
247620Y3-023
Adder
0.251
270216AD2-079_GEN
Solar/Wind Harmer
0.326
970611AG2-400 GEN
Solar/Wind Harmer
5.249
270526AF1-158 GEN
Solar/Wind Harmer
2.361
24441505OLIV SLR
Solar/Wind Harmer
0.069
965681AG1-436 GEN
Solar/Wind Harmer
6.214
965791AG1-447 GEN
Solar/Wind Harmer
3.179
270224U2-072_GEN2
Solar/Wind Harmer
0.951
270227U2-072_GEN3
Solar/Wind Harmer
0.951
270228U2-072_GEN4
Solar/Wind Harmer
0.951
270231U2-072_GEN5
Solar/Wind Harmer
0.951
274808UNIV PK N;4U
Adder
2.275
274803UNIV PARK;6U
Adder
2.631
274888KELLY CRK;1U
Solar/Wind Harmer
2.651
274887GEN-1.85
Solar/Wind Harmer
2.393
276843GEN-1.7
Solar/Wind Harmer
0.258
958011AF2-095 GEN
Solar/Wind Harmer
6.466
274770LINCOLN ;1U
Adder
2.783
274771LINCOLN ;2U
Adder
2.783
972259AH1-714 GEN
Adder
8.502
942221AE2-234 GEN
Solar/Wind Harmer
0.326
274674JOLIET 9 ;6U
Adder
6.844
970321AG2-212 GEN
Solar/Wind Harmer
7.911
274847GR RIDGE ;BU
Solar/Wind Harmer
2.236
958481AF2-142 GEN
Solar/Wind Harmer
6.589
274696ROCKY RD ;4P
Adder
4.973
274695ROCKY RD ;2P
Adder
4.858
274693ROCKY RD ;1P
Adder
4.81
274697ROCKY RD ;3P
Adder
1.32
274683WAUKEGAN ;8U
Adder
9.189
274683WAUKEGAN ;8U
Adder
7.746
203947AF1-006 C
Solar/Wind Helper
0.374
203980AG1-197 GEN
Solar/Wind Helper
0.245
203979AG1-198 GEN
Solar/Wind Helper
0.191
241801AE1-079 GEN
Solar/Wind Helper
0.13
241967AE2-285_GEN
Solar/Wind Helper
0.334
241985AE1-237 GEN
Solar/Wind Helper
0.129
962101AG1-054 GEN
Solar/Wind Helper
0.322
946381AF1-302 GEN
Solar/Wind Helper
0.103
274861TOP CROP ;1U
Solar/Wind Harmer
0.243
274862TOP CROP ;2U
Solar/Wind Harmer
0.203
991177J1571 G
External Queue
15.212156295776367
990527J1329
External Queue
1.8186211585998535
990142J1224
External Queue
13.294119834899902
991182J1586 G
External Queue
24.90056610107422
LAGNLTFEXP_LAGN->PJM
CLTF
4.854
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.172
TVALTFEXP_TVA->PJM
CLTF
2.201
CPLELTFEXP_CPLE->PJM
CLTF
0.333
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.784
NYPJM->LTFIMP_NY
CLTF
1.985
LGEELTFEXP_LGEE->PJM
CLTF
1.969
WECLTFEXP_WEC->PJM
CLTF
1.628
AG2-052LTFEXP_AG2-052->PJM
LTF
0.105
AH1-155LTFEXP_AH1-155->PJM
LTF
0.157
CBM West 1LTFEXP_CBM-W1->PJM
CBM
92.92
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.716
MECLTFEXP_MEC->PJM
CLTF
6.343
SIGELTFEXP_SIGE->PJM
CLTF
0.165

Details for 02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line l/o ATSI_P2-3_OEC-345-1152-12_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_OEC-345-1152-12_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:155.03 %
Rating:1646.0 MVA
Rating Type:B
MVA to Mitigate:2551.84
MW Contribution:13.0
Bus #Bus NameTypeMW Contribution
23867002DVBSG1
50/50
14.157
972211AH1-690 GEN
50/50
290.294
23888502TROY G1
50/50
1.813
23888602TROY G2
50/50
1.813
970817AG2-515 GEN
Solar/Wind Harmer
15.206
945411AF1-206 GEN
Solar/Wind Harmer
8.026
945641AF1-229 GEN
Solar/Wind Harmer
3.439
270499AE1-146 GEN
Solar/Wind Harmer
2.201
971549AH1-272 GEN
Solar/Wind Harmer
13.004
270297AD1-101 GEN
Solar/Wind Harmer
1.871
247607V1-011 GEN
Solar/Wind Harmer
2.303
957201AF2-014 GEN
Solar/Wind Harmer
2.636
270435AC2-044 GEN
Solar/Wind Harmer
1.162
944161AF1-084 GEN
Solar/Wind Harmer
1.282
966831AG1-554 GEN
Solar/Wind Harmer
0.674
971989AH1-539 GEN
Solar/Wind Harmer
7.284
965041AG1-368 GEN
Solar/Wind Harmer
5.453
965051AG1-369 GEN
Solar/Wind Harmer
2.706
971771AH1-392 GEN
Solar/Wind Harmer
4.773
270302AB2-170 GEN
Solar/Wind Harmer
4.342
270317AD1-130_GEN
Solar/Wind Harmer
1.665
971769AH1-391 GEN
Solar/Wind Harmer
5.17
971567AH1-282 GEN
Solar/Wind Harmer
7.463
960681AF2-359 GEN
Solar/Wind Harmer
1.878
971347AH1-153 GEN
Solar/Wind Harmer
7.421
963791AG1-232 GEN
Solar/Wind Harmer
6.559
270578AF1-285 GEN2
Solar/Wind Harmer
0.224
270536AF1-215 GEN2
Solar/Wind Harmer
2.129
270071AF1-092 GEN
Solar/Wind Harmer
6.925
274814UNIV PK N;0U
Adder
2.305
274807UNIV PK N;3U
Adder
2.3
274805UNIV PK N;1U
Adder
2.29
274811UNIV PK N;7U
Adder
2.285
958391AF2-133 GEN
Solar/Wind Harmer
4.138
972037AH1-567 GEN1
Adder
0.083
274827FISK ;RP
Adder
3.495
960591AF2-350 GEN
Solar/Wind Harmer
4.49
274775LINCOLN ;6U
Adder
2.783
274776LINCOLN ;7U
Adder
2.783
274777LINCOLN ;8U
Adder
2.783
972227AH1-698 GEN1
Adder
1.168
274687WILL CNTY;4U
Adder
12.469
274687WILL CNTY;4U
Adder
12.469
274675JOLIET 29;7U
Adder
13.662
274675JOLIET 29;7U
Adder
13.175
274728ELWOOD EC;5P
Adder
7.307
274731ELWOOD EC;2P
Adder
7.307
274733ELWOOD EC;3P
Adder
7.307
274735ELWOOD EC;4P
Adder
7.307
970833AG2-524 GEN
Solar/Wind Harmer
3.861
970833AG2-524 GEN
Solar/Wind Harmer
1.796
274746AC1-111 G10
Adder
2.457
274744AC1-111 GEN8
Adder
2.457
270024AE2-089 GEN
Solar/Wind Harmer
2.062
241886AC2-103 GEN2
Solar/Wind Helper
9.152
241982AE2-343 S C
Solar/Wind Helper
0.116
254304AE2-114 C
Solar/Wind Helper
0.111
203846AF2-130 C
Solar/Wind Helper
0.243
241997AF1-093 GEN
Solar/Wind Helper
0.128
203804AE2-113_GEN
Solar/Wind Helper
0.851
24189902OREGON_CT2
50/50
2.691
23888702TROY G3
50/50
1.813
972253AH1-711 GEN
50/50
55.392
23856402BAYSG1
50/50
1.233
23920202STRYCT
50/50
1.896
241858AF1-205_GEN
Solar/Wind Harmer
5.467
241808AF1-120 C
Solar/Wind Harmer
1.198
241840AF1-064_GEN
Solar/Wind Harmer
1.359
972301AH1-735 GEN
Adder
6.555
23906402RICHG1
Adder
1.311
23906502RICHG2&3
Adder
1.308
270361_3
Solar/Wind Harmer
7.869
960841AF2-375 GEN
Solar/Wind Harmer
3.486
970515AG2-329 GEN
Solar/Wind Harmer
10.065
247522W1-056 GEN
Solar/Wind Harmer
1.487
944231AF1-091 GEN
Solar/Wind Harmer
2.457
246936BC-WTG1
Solar/Wind Harmer
2.274
270489AE1-102 GEN1
Solar/Wind Harmer
0.755
965421AG1-410 GEN
Solar/Wind Harmer
17.272
270449AD2-020 GEN
Solar/Wind Harmer
1.604
943021AE2-325 GEN
Solar/Wind Harmer
2.085
24695305TIMB G C
Solar/Wind Harmer
3.084
945111AF1-176 GEN
Solar/Wind Harmer
9.989
270505AE1-170 C O1
Solar/Wind Harmer
8.391
24639705ELKHART HY
Adder
0.083
247521TR3_G114
Solar/Wind Harmer
1.822
270246TR4_N_V150
Solar/Wind Harmer
0.461
270063AE2-323 C
Solar/Wind Harmer
1.189
965011AG1-365 GEN
Solar/Wind Harmer
5.249
270462AD2-086
Solar/Wind Harmer
3.612
270223U2-072_GEN1
Solar/Wind Harmer
0.951
270578AF1-285 GEN2
Solar/Wind Harmer
0.581
270391AF1-285 GEN3
Solar/Wind Harmer
0.581
970373AG2-245 GEN
Solar/Wind Harmer
10.039
270055AF2-134 C O1
Solar/Wind Harmer
1.419
274751CRETE EC ;1U
Adder
2.258
274754CRETE EC ;4U
Adder
2.258
958381AF2-132 GEN
Solar/Wind Harmer
4.176
964861AG1-349 GEN
Solar/Wind Harmer
3.612
971917AH1-482 GEN
Solar/Wind Harmer
4.168
274723RIVER EC ;12
Adder
8.214
274812UNIV PK N;8U
Adder
2.285
276164X3-005 C
Solar/Wind Harmer
0.319
274801UNIV PARK;4U
Adder
2.622
276776AD2-060 GEN
Solar/Wind Harmer
0.19
940581AE2-045 GEN
Solar/Wind Harmer
4.579
971605AH1-302 GEN
Solar/Wind Harmer
3.915
972207SS24-0001
Solar/Wind Harmer
9.894
274773LINCOLN ;4U
Adder
2.783
274774LINCOLN ;5U
Adder
2.783
274676JOLIET 29;8U
Adder
13.662
941551AE2-152 GEN
Solar/Wind Harmer
2.017
274732ELWOOD EC;7P
Adder
7.307
274674JOLIET 9 ;6U
Adder
6.844
970245AG2-165 GEN
Solar/Wind Harmer
7.911
274871GR RIDGE ;2U
Solar/Wind Harmer
3.399
274745AC1-111 GEN9
Adder
2.457
276691AA1-018 GEN1
Solar/Wind Harmer
0.205
274682WAUKEGAN ;7U
Adder
7.844
274828WAUKEGAN ;BP
Adder
4.817
241885AC2-103 GEN1
Solar/Wind Helper
9.152
961971AG1-040 GEN
Solar/Wind Helper
0.328
203835AF1-098 GEN
Solar/Wind Helper
1.294
203860AG1-193 C
Solar/Wind Helper
0.147
241966AE1-183 GEN
Solar/Wind Helper
0.128
254303AC2-168 GEN
Solar/Wind Helper
0.075
24190002OREGON_ST1
50/50
3.621
24189802OREGON_CT1
50/50
2.747
23888802TROY G4
50/50
1.813
241996AE2-282_GEN
Solar/Wind Harmer
2.149
971677AH1-339 GEN
Solar/Wind Harmer
6.251
270007AE1-245 C
Solar/Wind Harmer
3.456
246938BC-WTG3
Solar/Wind Harmer
2.313
246937BC-WTG2
Solar/Wind Harmer
2.274
942801AE2-298 GEN
Solar/Wind Harmer
0.875
961051AF2-396 GEN
Solar/Wind Harmer
9.012
961051AF2-396 GEN
Solar/Wind Harmer
4.192
960981AF2-389 GEN
Solar/Wind Harmer
0.843
957891AF2-083 GEN
Solar/Wind Harmer
1.881
247620Y3-023
Adder
0.251
270216AD2-079_GEN
Solar/Wind Harmer
0.326
970611AG2-400 GEN
Solar/Wind Harmer
5.249
270526AF1-158 GEN
Solar/Wind Harmer
2.361
24441505OLIV SLR
Solar/Wind Harmer
0.069
965681AG1-436 GEN
Solar/Wind Harmer
6.214
965791AG1-447 GEN
Solar/Wind Harmer
3.179
270224U2-072_GEN2
Solar/Wind Harmer
0.951
270227U2-072_GEN3
Solar/Wind Harmer
0.951
270228U2-072_GEN4
Solar/Wind Harmer
0.951
270231U2-072_GEN5
Solar/Wind Harmer
0.951
274808UNIV PK N;4U
Adder
2.275
274803UNIV PARK;6U
Adder
2.631
274888KELLY CRK;1U
Solar/Wind Harmer
2.651
274887GEN-1.85
Solar/Wind Harmer
2.393
276843GEN-1.7
Solar/Wind Harmer
0.258
958011AF2-095 GEN
Solar/Wind Harmer
6.466
274770LINCOLN ;1U
Adder
2.783
274771LINCOLN ;2U
Adder
2.783
972259AH1-714 GEN
Adder
8.502
942221AE2-234 GEN
Solar/Wind Harmer
0.326
274674JOLIET 9 ;6U
Adder
6.844
970321AG2-212 GEN
Solar/Wind Harmer
7.911
274847GR RIDGE ;BU
Solar/Wind Harmer
2.236
958481AF2-142 GEN
Solar/Wind Harmer
6.589
274696ROCKY RD ;4P
Adder
4.973
274695ROCKY RD ;2P
Adder
4.858
274693ROCKY RD ;1P
Adder
4.81
274697ROCKY RD ;3P
Adder
1.32
274683WAUKEGAN ;8U
Adder
9.189
274683WAUKEGAN ;8U
Adder
7.746
203947AF1-006 C
Solar/Wind Helper
0.374
203980AG1-197 GEN
Solar/Wind Helper
0.245
203979AG1-198 GEN
Solar/Wind Helper
0.191
241801AE1-079 GEN
Solar/Wind Helper
0.13
241967AE2-285_GEN
Solar/Wind Helper
0.334
241985AE1-237 GEN
Solar/Wind Helper
0.129
962101AG1-054 GEN
Solar/Wind Helper
0.322
946381AF1-302 GEN
Solar/Wind Helper
0.103
274861TOP CROP ;1U
Solar/Wind Harmer
0.243
274862TOP CROP ;2U
Solar/Wind Harmer
0.203
23929302BS-PKR
50/50
2.169
241832AE2-181_GEN
Solar/Wind Harmer
1.949
958321AF2-126 GEN
Solar/Wind Harmer
1.457
23906502RICHG2&3
Adder
1.308
270541AE2-072 C
Solar/Wind Harmer
4.233
270575GUS2 35KV
Solar/Wind Harmer
9.271
970217AG2-149 GEN
Solar/Wind Harmer
22.195
270044AE2-322 C
Solar/Wind Harmer
0.848
270404AC1-167 GEN
Solar/Wind Harmer
0.706
270258AD1-119 GEN
Solar/Wind Harmer
1.728
247604X1-042
Adder
0.256
24441205WTRV SLR C
Solar/Wind Harmer
0.081
270588AE1-091_GEN
Solar/Wind Harmer
6.56
958091AF2-103 GEN
Solar/Wind Harmer
0.094
270491AE1-102 GEN2
Solar/Wind Harmer
0.755
945111AF1-176 GEN
Solar/Wind Harmer
3.166
24642205MAYFLWER
Adder
0.346
270191TR4_S_V150
Solar/Wind Harmer
1.626
270247TR4_N_V136
Solar/Wind Harmer
0.461
970031AG2-029 GEN
Solar/Wind Harmer
16.144
247643Z2-116 C
Solar/Wind Harmer
0.037
959331AF2-224 GEN
Solar/Wind Harmer
5.249
965021AG1-366 GEN
Solar/Wind Harmer
1.221
270485AE1-090_GEN
Solar/Wind Harmer
0.314
270043AE2-236 GEN
Solar/Wind Harmer
2.733
970349AG2-230 GEN
Solar/Wind Harmer
7.421
942871AE2-306 GEN
Solar/Wind Harmer
0.436
270391AF1-285 GEN3
Solar/Wind Harmer
0.224
270535AF1-215 GEN1
Solar/Wind Harmer
2.129
972231SS25-0005
Solar/Wind Harmer
4.384
972181SS23-001
Solar/Wind Harmer
2.74
274752CRETE EC ;2U
Adder
2.258
274753CRETE EC ;3U
Adder
2.258
964401AG1-302 GEN
Solar/Wind Harmer
4.176
274724RIVER EC ;11
Adder
8.116
959141AF2-205 GEN
Solar/Wind Harmer
2.738
274802UNIV PARK;5U
Adder
2.631
274826FISK ;BP
Adder
4.931
274800UNIV PARK;3U
Adder
2.622
972038AH1-567 GEN2
Adder
0.164
276772AC2-154 GEN
Solar/Wind Harmer
1.252
276806AD2-047 C O1
Solar/Wind Harmer
4.804
970941AG2-585 GEN
Solar/Wind Harmer
5.613
274772LINCOLN ;3U
Adder
2.783
972228AH1-698 GEN2
Adder
1.658
274676JOLIET 29;8U
Adder
13.174
276897AD1-100 C
Solar/Wind Harmer
12.909
939351AE1-166 GEN
Solar/Wind Harmer
2.638
276893AG1-478 C
Solar/Wind Harmer
0.186
274730ELWOOD EC;6P
Adder
7.307
274734ELWOOD EC;8P
Adder
7.307
274736ELWOOD EC;9P
Adder
7.307
970707AG2-453 GEN
Solar/Wind Harmer
12.445
274729ELWOOD EC;1P
Adder
7.307
970513AG2-328 GEN
Solar/Wind Harmer
7.911
970517AG2-330 GEN
Solar/Wind Harmer
7.175
971617AH1-308 GEN
Solar/Wind Harmer
2.555
943121AE2-341 GEN
Solar/Wind Harmer
6.59
943591AF1-030 GEN
Solar/Wind Harmer
4.393
276694AA1-018 GEN2
Solar/Wind Harmer
2.772
274682WAUKEGAN ;7U
Adder
7.844
962511AG1-100 GEN
Solar/Wind Helper
0.336
203830AF1-094 GEN
Solar/Wind Helper
0.318
959441AF2-235 GEN
Solar/Wind Helper
0.144
254305AE2-115 C
Solar/Wind Helper
0.111
20334926Z1-069 C
Solar/Wind Helper
0.633
991177J1571 G
External Queue
15.212156295776367
990527J1329
External Queue
1.8186211585998535
990142J1224
External Queue
13.294119834899902
991182J1586 G
External Queue
24.90056610107422
LAGNLTFEXP_LAGN->PJM
CLTF
4.854
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.172
TVALTFEXP_TVA->PJM
CLTF
2.201
CPLELTFEXP_CPLE->PJM
CLTF
0.333
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.784
NYPJM->LTFIMP_NY
CLTF
1.985
LGEELTFEXP_LGEE->PJM
CLTF
1.969
WECLTFEXP_WEC->PJM
CLTF
1.628
AG2-052LTFEXP_AG2-052->PJM
LTF
0.105
AH1-155LTFEXP_AH1-155->PJM
LTF
0.157
CBM West 1LTFEXP_CBM-W1->PJM
CBM
92.92
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.716
MECLTFEXP_MEC->PJM
CLTF
6.343
SIGELTFEXP_SIGE->PJM
CLTF
0.165

Details for 02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line l/o ATSI_P2-3_TE-345-010B1_SRT-SL


Base Case Flowgate

Area:ATSI
Facility Description:
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_TE-345-010B1_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:153.46 %
Rating:1646.0 MVA
Rating Type:B
MVA to Mitigate:2525.94
MW Contribution:12.86
Bus #Bus NameTypeMW Contribution
23867002DVBSG1
50/50
14.11
972211AH1-690 GEN
50/50
287.754
23888502TROY G1
50/50
1.796
23888602TROY G2
50/50
1.796
970817AG2-515 GEN
Solar/Wind Harmer
15.035
945411AF1-206 GEN
Solar/Wind Harmer
7.914
945641AF1-229 GEN
Solar/Wind Harmer
3.393
270499AE1-146 GEN
Solar/Wind Harmer
2.151
971549AH1-272 GEN
Solar/Wind Harmer
12.855
270297AD1-101 GEN
Solar/Wind Harmer
1.842
247607V1-011 GEN
Solar/Wind Harmer
2.271
944161AF1-084 GEN
Solar/Wind Harmer
1.267
957201AF2-014 GEN
Solar/Wind Harmer
2.6
270435AC2-044 GEN
Solar/Wind Harmer
1.147
966831AG1-554 GEN
Solar/Wind Harmer
0.66
971989AH1-539 GEN
Solar/Wind Harmer
7.141
965041AG1-368 GEN
Solar/Wind Harmer
5.38
965051AG1-369 GEN
Solar/Wind Harmer
2.669
971771AH1-392 GEN
Solar/Wind Harmer
4.715
270302AB2-170 GEN
Solar/Wind Harmer
4.281
270317AD1-130_GEN
Solar/Wind Harmer
1.641
971769AH1-391 GEN
Solar/Wind Harmer
5.107
960681AF2-359 GEN
Solar/Wind Harmer
1.855
971567AH1-282 GEN
Solar/Wind Harmer
7.347
971347AH1-153 GEN
Solar/Wind Harmer
7.33
963791AG1-232 GEN
Solar/Wind Harmer
6.473
270578AF1-285 GEN2
Solar/Wind Harmer
0.22
270536AF1-215 GEN2
Solar/Wind Harmer
2.103
270071AF1-092 GEN
Solar/Wind Harmer
6.837
274814UNIV PK N;0U
Adder
2.277
274807UNIV PK N;3U
Adder
2.272
274805UNIV PK N;1U
Adder
2.262
274811UNIV PK N;7U
Adder
2.257
958391AF2-133 GEN
Solar/Wind Harmer
4.087
972037AH1-567 GEN1
Adder
0.082
274827FISK ;RP
Adder
3.452
960591AF2-350 GEN
Solar/Wind Harmer
4.435
274775LINCOLN ;6U
Adder
2.748
274776LINCOLN ;7U
Adder
2.748
274777LINCOLN ;8U
Adder
2.748
972227AH1-698 GEN1
Adder
1.153
274687WILL CNTY;4U
Adder
12.315
274687WILL CNTY;4U
Adder
12.315
274675JOLIET 29;7U
Adder
13.494
274675JOLIET 29;7U
Adder
13.012
274731ELWOOD EC;2P
Adder
7.217
274733ELWOOD EC;3P
Adder
7.217
274735ELWOOD EC;4P
Adder
7.217
274728ELWOOD EC;5P
Adder
7.217
970833AG2-524 GEN
Solar/Wind Harmer
3.814
970833AG2-524 GEN
Solar/Wind Harmer
1.774
274746AC1-111 G10
Adder
2.426
274744AC1-111 GEN8
Adder
2.426
241886AC2-103 GEN2
Solar/Wind Helper
9.126
241982AE2-343 S C
Solar/Wind Helper
0.114
254304AE2-114 C
Solar/Wind Helper
0.109
203846AF2-130 C
Solar/Wind Helper
0.24
241997AF1-093 GEN
Solar/Wind Helper
0.126
203804AE2-113_GEN
Solar/Wind Helper
0.838
270024AE2-089 GEN
Solar/Wind Harmer
0.078
23929302BS-PKR
50/50
2.128
241832AE2-181_GEN
Solar/Wind Harmer
1.922
958321AF2-126 GEN
Solar/Wind Harmer
1.433
23906502RICHG2&3
Adder
1.289
270541AE2-072 C
Solar/Wind Harmer
4.165
270575GUS2 35KV
Solar/Wind Harmer
9.05
970217AG2-149 GEN
Solar/Wind Harmer
21.874
270044AE2-322 C
Solar/Wind Harmer
0.836
270404AC1-167 GEN
Solar/Wind Harmer
0.696
270258AD1-119 GEN
Solar/Wind Harmer
1.704
247604X1-042
Adder
0.253
24441205WTRV SLR C
Solar/Wind Harmer
0.08
270588AE1-091_GEN
Solar/Wind Harmer
6.441
958091AF2-103 GEN
Solar/Wind Harmer
0.093
270491AE1-102 GEN2
Solar/Wind Harmer
0.745
945111AF1-176 GEN
Solar/Wind Harmer
3.128
24642205MAYFLWER
Adder
0.342
270191TR4_S_V150
Solar/Wind Harmer
1.604
270247TR4_N_V136
Solar/Wind Harmer
0.455
247643Z2-116 C
Solar/Wind Harmer
0.037
970031AG2-029 GEN
Solar/Wind Harmer
15.944
959331AF2-224 GEN
Solar/Wind Harmer
5.181
965021AG1-366 GEN
Solar/Wind Harmer
1.205
270485AE1-090_GEN
Solar/Wind Harmer
0.31
270043AE2-236 GEN
Solar/Wind Harmer
2.698
970349AG2-230 GEN
Solar/Wind Harmer
7.33
942871AE2-306 GEN
Solar/Wind Harmer
0.43
270391AF1-285 GEN3
Solar/Wind Harmer
0.22
270535AF1-215 GEN1
Solar/Wind Harmer
2.103
972231SS25-0005
Solar/Wind Harmer
4.331
972181SS23-001
Solar/Wind Harmer
2.707
274752CRETE EC ;2U
Adder
2.23
274753CRETE EC ;3U
Adder
2.23
964401AG1-302 GEN
Solar/Wind Harmer
4.125
274724RIVER EC ;11
Adder
8.016
959141AF2-205 GEN
Solar/Wind Harmer
2.704
274802UNIV PARK;5U
Adder
2.599
274826FISK ;BP
Adder
4.871
274800UNIV PARK;3U
Adder
2.59
972038AH1-567 GEN2
Adder
0.162
276772AC2-154 GEN
Solar/Wind Harmer
1.237
276806AD2-047 C O1
Solar/Wind Harmer
4.745
970941AG2-585 GEN
Solar/Wind Harmer
5.544
274772LINCOLN ;3U
Adder
2.748
972228AH1-698 GEN2
Adder
1.638
274676JOLIET 29;8U
Adder
13.012
276897AD1-100 C
Solar/Wind Harmer
12.75
939351AE1-166 GEN
Solar/Wind Harmer
2.605
276893AG1-478 C
Solar/Wind Harmer
0.183
274729ELWOOD EC;1P
Adder
7.217
274730ELWOOD EC;6P
Adder
7.217
274734ELWOOD EC;8P
Adder
7.217
274736ELWOOD EC;9P
Adder
7.217
970707AG2-453 GEN
Solar/Wind Harmer
12.291
970513AG2-328 GEN
Solar/Wind Harmer
7.813
970517AG2-330 GEN
Solar/Wind Harmer
7.086
943121AE2-341 GEN
Solar/Wind Harmer
6.509
943591AF1-030 GEN
Solar/Wind Harmer
4.339
276694AA1-018 GEN2
Solar/Wind Harmer
2.738
274682WAUKEGAN ;7U
Adder
7.748
962511AG1-100 GEN
Solar/Wind Helper
0.331
203830AF1-094 GEN
Solar/Wind Helper
0.313
959441AF2-235 GEN
Solar/Wind Helper
0.142
254305AE2-115 C
Solar/Wind Helper
0.109
971617AH1-308 GEN
Solar/Wind Harmer
0.096
24189902OREGON_CT2
50/50
2.668
23888702TROY G3
50/50
1.796
972253AH1-711 GEN
50/50
54.848
23856402BAYSG1
50/50
1.209
23920202STRYCT
50/50
1.869
241858AF1-205_GEN
Solar/Wind Harmer
5.389
241808AF1-120 C
Solar/Wind Harmer
1.181
241840AF1-064_GEN
Solar/Wind Harmer
1.337
972301AH1-735 GEN
Adder
6.461
23906402RICHG1
Adder
1.292
23906502RICHG2&3
Adder
1.289
270361_3
Solar/Wind Harmer
7.682
960841AF2-375 GEN
Solar/Wind Harmer
3.405
970515AG2-329 GEN
Solar/Wind Harmer
9.92
247522W1-056 GEN
Solar/Wind Harmer
1.456
944231AF1-091 GEN
Solar/Wind Harmer
2.424
246936BC-WTG1
Solar/Wind Harmer
2.243
270489AE1-102 GEN1
Solar/Wind Harmer
0.745
965421AG1-410 GEN
Solar/Wind Harmer
17.04
270449AD2-020 GEN
Solar/Wind Harmer
1.585
943021AE2-325 GEN
Solar/Wind Harmer
2.06
945111AF1-176 GEN
Solar/Wind Harmer
9.87
270505AE1-170 C O1
Solar/Wind Harmer
8.291
24695305TIMB G C
Solar/Wind Harmer
3.042
24639705ELKHART HY
Adder
0.082
247521TR3_G114
Solar/Wind Harmer
1.797
270246TR4_N_V150
Solar/Wind Harmer
0.455
270063AE2-323 C
Solar/Wind Harmer
1.174
965011AG1-365 GEN
Solar/Wind Harmer
5.181
270462AD2-086
Solar/Wind Harmer
3.561
270223U2-072_GEN1
Solar/Wind Harmer
0.937
270578AF1-285 GEN2
Solar/Wind Harmer
0.573
270391AF1-285 GEN3
Solar/Wind Harmer
0.573
970373AG2-245 GEN
Solar/Wind Harmer
9.916
270055AF2-134 C O1
Solar/Wind Harmer
1.402
274751CRETE EC ;1U
Adder
2.23
274754CRETE EC ;4U
Adder
2.23
958381AF2-132 GEN
Solar/Wind Harmer
4.125
964861AG1-349 GEN
Solar/Wind Harmer
3.567
971917AH1-482 GEN
Solar/Wind Harmer
4.117
274723RIVER EC ;12
Adder
8.113
274812UNIV PK N;8U
Adder
2.257
276164X3-005 C
Solar/Wind Harmer
0.315
274801UNIV PARK;4U
Adder
2.59
276776AD2-060 GEN
Solar/Wind Harmer
0.188
940581AE2-045 GEN
Solar/Wind Harmer
4.522
971605AH1-302 GEN
Solar/Wind Harmer
3.867
972207SS24-0001
Solar/Wind Harmer
9.772
274773LINCOLN ;4U
Adder
2.748
274774LINCOLN ;5U
Adder
2.748
274676JOLIET 29;8U
Adder
13.494
941551AE2-152 GEN
Solar/Wind Harmer
1.993
274732ELWOOD EC;7P
Adder
7.217
274674JOLIET 9 ;6U
Adder
6.759
970245AG2-165 GEN
Solar/Wind Harmer
7.813
274871GR RIDGE ;2U
Solar/Wind Harmer
3.357
274745AC1-111 GEN9
Adder
2.426
276691AA1-018 GEN1
Solar/Wind Harmer
0.202
274682WAUKEGAN ;7U
Adder
7.748
274828WAUKEGAN ;BP
Adder
4.757
241885AC2-103 GEN1
Solar/Wind Helper
9.126
961971AG1-040 GEN
Solar/Wind Helper
0.324
203835AF1-098 GEN
Solar/Wind Helper
1.276
203860AG1-193 C
Solar/Wind Helper
0.145
241966AE1-183 GEN
Solar/Wind Helper
0.126
241807AE2-176_GEN
Solar/Wind Helper
0.764
254303AC2-168 GEN
Solar/Wind Helper
0.074
24190002OREGON_ST1
50/50
3.59
24189802OREGON_CT1
50/50
2.723
23888802TROY G4
50/50
1.796
241996AE2-282_GEN
Solar/Wind Harmer
2.119
971677AH1-339 GEN
Solar/Wind Harmer
6.113
270007AE1-245 C
Solar/Wind Harmer
3.406
246938BC-WTG3
Solar/Wind Harmer
2.282
246937BC-WTG2
Solar/Wind Harmer
2.243
942801AE2-298 GEN
Solar/Wind Harmer
0.863
961051AF2-396 GEN
Solar/Wind Harmer
8.904
961051AF2-396 GEN
Solar/Wind Harmer
4.142
960981AF2-389 GEN
Solar/Wind Harmer
0.833
957891AF2-083 GEN
Solar/Wind Harmer
1.858
247620Y3-023
Adder
0.248
270216AD2-079_GEN
Solar/Wind Harmer
0.322
970611AG2-400 GEN
Solar/Wind Harmer
5.181
270526AF1-158 GEN
Solar/Wind Harmer
2.332
24441505OLIV SLR
Solar/Wind Harmer
0.068
965681AG1-436 GEN
Solar/Wind Harmer
6.139
965791AG1-447 GEN
Solar/Wind Harmer
3.141
270224U2-072_GEN2
Solar/Wind Harmer
0.937
270227U2-072_GEN3
Solar/Wind Harmer
0.937
270228U2-072_GEN4
Solar/Wind Harmer
0.937
270231U2-072_GEN5
Solar/Wind Harmer
0.937
274808UNIV PK N;4U
Adder
2.247
274803UNIV PARK;6U
Adder
2.599
274888KELLY CRK;1U
Solar/Wind Harmer
2.618
274887GEN-1.85
Solar/Wind Harmer
2.364
276843GEN-1.7
Solar/Wind Harmer
0.254
958011AF2-095 GEN
Solar/Wind Harmer
6.387
274770LINCOLN ;1U
Adder
2.748
274771LINCOLN ;2U
Adder
2.748
972259AH1-714 GEN
Adder
8.397
942221AE2-234 GEN
Solar/Wind Harmer
0.322
274674JOLIET 9 ;6U
Adder
6.759
970321AG2-212 GEN
Solar/Wind Harmer
7.813
274847GR RIDGE ;BU
Solar/Wind Harmer
2.208
958481AF2-142 GEN
Solar/Wind Harmer
6.507
274861TOP CROP ;1U
Solar/Wind Harmer
2.629
274862TOP CROP ;2U
Solar/Wind Harmer
2.195
274696ROCKY RD ;4P
Adder
4.912
274695ROCKY RD ;2P
Adder
4.798
274693ROCKY RD ;1P
Adder
4.751
274697ROCKY RD ;3P
Adder
1.303
274683WAUKEGAN ;8U
Adder
9.076
274683WAUKEGAN ;8U
Adder
7.65
203947AF1-006 C
Solar/Wind Helper
0.369
203980AG1-197 GEN
Solar/Wind Helper
0.241
203979AG1-198 GEN
Solar/Wind Helper
0.188
241801AE1-079 GEN
Solar/Wind Helper
0.128
241967AE2-285_GEN
Solar/Wind Helper
0.329
241985AE1-237 GEN
Solar/Wind Helper
0.128
962101AG1-054 GEN
Solar/Wind Helper
0.317
991177J1571 G
External Queue
15.044508934020996
990527J1329
External Queue
1.8002409934997559
990142J1224
External Queue
13.159761428833008
991182J1586 G
External Queue
24.65229034423828
LAGNLTFEXP_LAGN->PJM
CLTF
4.792
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.145
TVALTFEXP_TVA->PJM
CLTF
2.173
CPLELTFEXP_CPLE->PJM
CLTF
0.33
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.291
NYPJM->LTFIMP_NY
CLTF
1.957
LGEELTFEXP_LGEE->PJM
CLTF
1.943
WECLTFEXP_WEC->PJM
CLTF
1.608
AG2-052LTFEXP_AG2-052->PJM
LTF
0.104
AH1-155LTFEXP_AH1-155->PJM
LTF
0.155
CBM West 1LTFEXP_CBM-W1->PJM
CBM
91.866
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.603
MECLTFEXP_MEC->PJM
CLTF
6.264
SIGELTFEXP_SIGE->PJM
CLTF
0.162

Details for 02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line l/o ATSI_P2-3_TE-345-010B2_SRT-SL


Base Case Flowgate

Area:ATSI
Facility Description:
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_TE-345-010B2_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:153.46 %
Rating:1646.0 MVA
Rating Type:B
MVA to Mitigate:2525.94
MW Contribution:12.86
Bus #Bus NameTypeMW Contribution
23867002DVBSG1
50/50
14.11
972211AH1-690 GEN
50/50
287.754
23888502TROY G1
50/50
1.796
23888602TROY G2
50/50
1.796
970817AG2-515 GEN
Solar/Wind Harmer
15.035
945411AF1-206 GEN
Solar/Wind Harmer
7.914
945641AF1-229 GEN
Solar/Wind Harmer
3.393
270499AE1-146 GEN
Solar/Wind Harmer
2.151
971549AH1-272 GEN
Solar/Wind Harmer
12.855
270297AD1-101 GEN
Solar/Wind Harmer
1.842
247607V1-011 GEN
Solar/Wind Harmer
2.271
944161AF1-084 GEN
Solar/Wind Harmer
1.267
957201AF2-014 GEN
Solar/Wind Harmer
2.6
270435AC2-044 GEN
Solar/Wind Harmer
1.147
966831AG1-554 GEN
Solar/Wind Harmer
0.66
971989AH1-539 GEN
Solar/Wind Harmer
7.141
965041AG1-368 GEN
Solar/Wind Harmer
5.38
965051AG1-369 GEN
Solar/Wind Harmer
2.669
971771AH1-392 GEN
Solar/Wind Harmer
4.715
270302AB2-170 GEN
Solar/Wind Harmer
4.281
270317AD1-130_GEN
Solar/Wind Harmer
1.641
971769AH1-391 GEN
Solar/Wind Harmer
5.107
960681AF2-359 GEN
Solar/Wind Harmer
1.855
971567AH1-282 GEN
Solar/Wind Harmer
7.347
971347AH1-153 GEN
Solar/Wind Harmer
7.33
963791AG1-232 GEN
Solar/Wind Harmer
6.473
270578AF1-285 GEN2
Solar/Wind Harmer
0.22
270536AF1-215 GEN2
Solar/Wind Harmer
2.103
270071AF1-092 GEN
Solar/Wind Harmer
6.837
274814UNIV PK N;0U
Adder
2.277
274807UNIV PK N;3U
Adder
2.272
274805UNIV PK N;1U
Adder
2.262
274811UNIV PK N;7U
Adder
2.257
958391AF2-133 GEN
Solar/Wind Harmer
4.087
972037AH1-567 GEN1
Adder
0.082
274827FISK ;RP
Adder
3.452
960591AF2-350 GEN
Solar/Wind Harmer
4.435
274775LINCOLN ;6U
Adder
2.748
274776LINCOLN ;7U
Adder
2.748
274777LINCOLN ;8U
Adder
2.748
972227AH1-698 GEN1
Adder
1.153
274687WILL CNTY;4U
Adder
12.315
274687WILL CNTY;4U
Adder
12.315
274675JOLIET 29;7U
Adder
13.494
274675JOLIET 29;7U
Adder
13.012
274731ELWOOD EC;2P
Adder
7.217
274733ELWOOD EC;3P
Adder
7.217
274735ELWOOD EC;4P
Adder
7.217
274728ELWOOD EC;5P
Adder
7.217
970833AG2-524 GEN
Solar/Wind Harmer
3.814
970833AG2-524 GEN
Solar/Wind Harmer
1.774
274746AC1-111 G10
Adder
2.426
274744AC1-111 GEN8
Adder
2.426
241886AC2-103 GEN2
Solar/Wind Helper
9.126
241982AE2-343 S C
Solar/Wind Helper
0.114
254304AE2-114 C
Solar/Wind Helper
0.109
203846AF2-130 C
Solar/Wind Helper
0.24
241997AF1-093 GEN
Solar/Wind Helper
0.126
203804AE2-113_GEN
Solar/Wind Helper
0.838
270024AE2-089 GEN
Solar/Wind Harmer
0.078
24189902OREGON_CT2
50/50
2.668
23888702TROY G3
50/50
1.796
972253AH1-711 GEN
50/50
54.848
23856402BAYSG1
50/50
1.209
23920202STRYCT
50/50
1.869
241858AF1-205_GEN
Solar/Wind Harmer
5.389
241808AF1-120 C
Solar/Wind Harmer
1.181
241840AF1-064_GEN
Solar/Wind Harmer
1.337
972301AH1-735 GEN
Adder
6.461
23906402RICHG1
Adder
1.292
23906502RICHG2&3
Adder
1.289
270361_3
Solar/Wind Harmer
7.682
960841AF2-375 GEN
Solar/Wind Harmer
3.405
970515AG2-329 GEN
Solar/Wind Harmer
9.92
247522W1-056 GEN
Solar/Wind Harmer
1.456
944231AF1-091 GEN
Solar/Wind Harmer
2.424
246936BC-WTG1
Solar/Wind Harmer
2.243
270489AE1-102 GEN1
Solar/Wind Harmer
0.745
965421AG1-410 GEN
Solar/Wind Harmer
17.04
270449AD2-020 GEN
Solar/Wind Harmer
1.585
943021AE2-325 GEN
Solar/Wind Harmer
2.06
945111AF1-176 GEN
Solar/Wind Harmer
9.87
270505AE1-170 C O1
Solar/Wind Harmer
8.291
24695305TIMB G C
Solar/Wind Harmer
3.042
24639705ELKHART HY
Adder
0.082
247521TR3_G114
Solar/Wind Harmer
1.797
270246TR4_N_V150
Solar/Wind Harmer
0.455
270063AE2-323 C
Solar/Wind Harmer
1.174
965011AG1-365 GEN
Solar/Wind Harmer
5.181
270462AD2-086
Solar/Wind Harmer
3.561
270223U2-072_GEN1
Solar/Wind Harmer
0.937
270578AF1-285 GEN2
Solar/Wind Harmer
0.573
270391AF1-285 GEN3
Solar/Wind Harmer
0.573
970373AG2-245 GEN
Solar/Wind Harmer
9.916
270055AF2-134 C O1
Solar/Wind Harmer
1.402
274751CRETE EC ;1U
Adder
2.23
274754CRETE EC ;4U
Adder
2.23
958381AF2-132 GEN
Solar/Wind Harmer
4.125
964861AG1-349 GEN
Solar/Wind Harmer
3.567
971917AH1-482 GEN
Solar/Wind Harmer
4.117
274723RIVER EC ;12
Adder
8.113
274812UNIV PK N;8U
Adder
2.257
276164X3-005 C
Solar/Wind Harmer
0.315
274801UNIV PARK;4U
Adder
2.59
276776AD2-060 GEN
Solar/Wind Harmer
0.188
940581AE2-045 GEN
Solar/Wind Harmer
4.522
971605AH1-302 GEN
Solar/Wind Harmer
3.867
972207SS24-0001
Solar/Wind Harmer
9.772
274773LINCOLN ;4U
Adder
2.748
274774LINCOLN ;5U
Adder
2.748
274676JOLIET 29;8U
Adder
13.494
941551AE2-152 GEN
Solar/Wind Harmer
1.993
274732ELWOOD EC;7P
Adder
7.217
274674JOLIET 9 ;6U
Adder
6.759
970245AG2-165 GEN
Solar/Wind Harmer
7.813
274871GR RIDGE ;2U
Solar/Wind Harmer
3.357
274745AC1-111 GEN9
Adder
2.426
276691AA1-018 GEN1
Solar/Wind Harmer
0.202
274682WAUKEGAN ;7U
Adder
7.748
274828WAUKEGAN ;BP
Adder
4.757
241885AC2-103 GEN1
Solar/Wind Helper
9.126
961971AG1-040 GEN
Solar/Wind Helper
0.324
203835AF1-098 GEN
Solar/Wind Helper
1.276
203860AG1-193 C
Solar/Wind Helper
0.145
241966AE1-183 GEN
Solar/Wind Helper
0.126
241807AE2-176_GEN
Solar/Wind Helper
0.764
254303AC2-168 GEN
Solar/Wind Helper
0.074
24190002OREGON_ST1
50/50
3.59
24189802OREGON_CT1
50/50
2.723
23888802TROY G4
50/50
1.796
241996AE2-282_GEN
Solar/Wind Harmer
2.119
971677AH1-339 GEN
Solar/Wind Harmer
6.113
270007AE1-245 C
Solar/Wind Harmer
3.406
246938BC-WTG3
Solar/Wind Harmer
2.282
246937BC-WTG2
Solar/Wind Harmer
2.243
942801AE2-298 GEN
Solar/Wind Harmer
0.863
961051AF2-396 GEN
Solar/Wind Harmer
8.904
961051AF2-396 GEN
Solar/Wind Harmer
4.142
960981AF2-389 GEN
Solar/Wind Harmer
0.833
957891AF2-083 GEN
Solar/Wind Harmer
1.858
247620Y3-023
Adder
0.248
270216AD2-079_GEN
Solar/Wind Harmer
0.322
970611AG2-400 GEN
Solar/Wind Harmer
5.181
270526AF1-158 GEN
Solar/Wind Harmer
2.332
24441505OLIV SLR
Solar/Wind Harmer
0.068
965681AG1-436 GEN
Solar/Wind Harmer
6.139
965791AG1-447 GEN
Solar/Wind Harmer
3.141
270224U2-072_GEN2
Solar/Wind Harmer
0.937
270227U2-072_GEN3
Solar/Wind Harmer
0.937
270228U2-072_GEN4
Solar/Wind Harmer
0.937
270231U2-072_GEN5
Solar/Wind Harmer
0.937
274808UNIV PK N;4U
Adder
2.247
274803UNIV PARK;6U
Adder
2.599
274888KELLY CRK;1U
Solar/Wind Harmer
2.618
274887GEN-1.85
Solar/Wind Harmer
2.364
276843GEN-1.7
Solar/Wind Harmer
0.254
958011AF2-095 GEN
Solar/Wind Harmer
6.387
274770LINCOLN ;1U
Adder
2.748
274771LINCOLN ;2U
Adder
2.748
972259AH1-714 GEN
Adder
8.397
942221AE2-234 GEN
Solar/Wind Harmer
0.322
274674JOLIET 9 ;6U
Adder
6.759
970321AG2-212 GEN
Solar/Wind Harmer
7.813
274847GR RIDGE ;BU
Solar/Wind Harmer
2.208
958481AF2-142 GEN
Solar/Wind Harmer
6.507
274861TOP CROP ;1U
Solar/Wind Harmer
2.629
274862TOP CROP ;2U
Solar/Wind Harmer
2.195
274696ROCKY RD ;4P
Adder
4.912
274695ROCKY RD ;2P
Adder
4.798
274693ROCKY RD ;1P
Adder
4.751
274697ROCKY RD ;3P
Adder
1.303
274683WAUKEGAN ;8U
Adder
9.076
274683WAUKEGAN ;8U
Adder
7.65
203947AF1-006 C
Solar/Wind Helper
0.369
203980AG1-197 GEN
Solar/Wind Helper
0.241
203979AG1-198 GEN
Solar/Wind Helper
0.188
241801AE1-079 GEN
Solar/Wind Helper
0.128
241967AE2-285_GEN
Solar/Wind Helper
0.329
241985AE1-237 GEN
Solar/Wind Helper
0.128
962101AG1-054 GEN
Solar/Wind Helper
0.317
23929302BS-PKR
50/50
2.128
241832AE2-181_GEN
Solar/Wind Harmer
1.922
958321AF2-126 GEN
Solar/Wind Harmer
1.433
23906502RICHG2&3
Adder
1.289
270541AE2-072 C
Solar/Wind Harmer
4.165
270575GUS2 35KV
Solar/Wind Harmer
9.05
970217AG2-149 GEN
Solar/Wind Harmer
21.874
270044AE2-322 C
Solar/Wind Harmer
0.836
270404AC1-167 GEN
Solar/Wind Harmer
0.696
270258AD1-119 GEN
Solar/Wind Harmer
1.704
247604X1-042
Adder
0.253
24441205WTRV SLR C
Solar/Wind Harmer
0.08
270588AE1-091_GEN
Solar/Wind Harmer
6.441
958091AF2-103 GEN
Solar/Wind Harmer
0.093
270491AE1-102 GEN2
Solar/Wind Harmer
0.745
945111AF1-176 GEN
Solar/Wind Harmer
3.128
24642205MAYFLWER
Adder
0.342
270191TR4_S_V150
Solar/Wind Harmer
1.604
270247TR4_N_V136
Solar/Wind Harmer
0.455
247643Z2-116 C
Solar/Wind Harmer
0.037
970031AG2-029 GEN
Solar/Wind Harmer
15.944
959331AF2-224 GEN
Solar/Wind Harmer
5.181
965021AG1-366 GEN
Solar/Wind Harmer
1.205
270485AE1-090_GEN
Solar/Wind Harmer
0.31
270043AE2-236 GEN
Solar/Wind Harmer
2.698
970349AG2-230 GEN
Solar/Wind Harmer
7.33
942871AE2-306 GEN
Solar/Wind Harmer
0.43
270391AF1-285 GEN3
Solar/Wind Harmer
0.22
270535AF1-215 GEN1
Solar/Wind Harmer
2.103
972231SS25-0005
Solar/Wind Harmer
4.331
972181SS23-001
Solar/Wind Harmer
2.707
274752CRETE EC ;2U
Adder
2.23
274753CRETE EC ;3U
Adder
2.23
964401AG1-302 GEN
Solar/Wind Harmer
4.125
274724RIVER EC ;11
Adder
8.016
959141AF2-205 GEN
Solar/Wind Harmer
2.704
274802UNIV PARK;5U
Adder
2.599
274826FISK ;BP
Adder
4.871
274800UNIV PARK;3U
Adder
2.59
972038AH1-567 GEN2
Adder
0.162
276772AC2-154 GEN
Solar/Wind Harmer
1.237
276806AD2-047 C O1
Solar/Wind Harmer
4.745
970941AG2-585 GEN
Solar/Wind Harmer
5.544
274772LINCOLN ;3U
Adder
2.748
972228AH1-698 GEN2
Adder
1.638
274676JOLIET 29;8U
Adder
13.012
276897AD1-100 C
Solar/Wind Harmer
12.75
939351AE1-166 GEN
Solar/Wind Harmer
2.605
276893AG1-478 C
Solar/Wind Harmer
0.183
274729ELWOOD EC;1P
Adder
7.217
274730ELWOOD EC;6P
Adder
7.217
274734ELWOOD EC;8P
Adder
7.217
274736ELWOOD EC;9P
Adder
7.217
970707AG2-453 GEN
Solar/Wind Harmer
12.291
970513AG2-328 GEN
Solar/Wind Harmer
7.813
970517AG2-330 GEN
Solar/Wind Harmer
7.086
943121AE2-341 GEN
Solar/Wind Harmer
6.509
943591AF1-030 GEN
Solar/Wind Harmer
4.339
276694AA1-018 GEN2
Solar/Wind Harmer
2.738
274682WAUKEGAN ;7U
Adder
7.748
962511AG1-100 GEN
Solar/Wind Helper
0.331
203830AF1-094 GEN
Solar/Wind Helper
0.313
959441AF2-235 GEN
Solar/Wind Helper
0.142
254305AE2-115 C
Solar/Wind Helper
0.109
971617AH1-308 GEN
Solar/Wind Harmer
0.096
991177J1571 G
External Queue
15.044508934020996
990527J1329
External Queue
1.8002409934997559
990142J1224
External Queue
13.159761428833008
991182J1586 G
External Queue
24.65229034423828
LAGNLTFEXP_LAGN->PJM
CLTF
4.792
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.145
TVALTFEXP_TVA->PJM
CLTF
2.173
CPLELTFEXP_CPLE->PJM
CLTF
0.33
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.291
NYPJM->LTFIMP_NY
CLTF
1.957
LGEELTFEXP_LGEE->PJM
CLTF
1.943
WECLTFEXP_WEC->PJM
CLTF
1.608
AG2-052LTFEXP_AG2-052->PJM
LTF
0.104
AH1-155LTFEXP_AH1-155->PJM
LTF
0.155
CBM West 1LTFEXP_CBM-W1->PJM
CBM
91.866
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.603
MECLTFEXP_MEC->PJM
CLTF
6.264
SIGELTFEXP_SIGE->PJM
CLTF
0.162

Details for 02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line l/o ATSI_P2-3_OEC-345-1152-3_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_OEC-345-1152-3_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:151.55 %
Rating:1646.0 MVA
Rating Type:B
MVA to Mitigate:2494.57
MW Contribution:12.83
Bus #Bus NameTypeMW Contribution
23867002DVBSG1
50/50
13.074
972211AH1-690 GEN
50/50
280.319
23888502TROY G1
50/50
1.766
23888602TROY G2
50/50
1.766
970817AG2-515 GEN
Solar/Wind Harmer
14.976
945411AF1-206 GEN
Solar/Wind Harmer
8.075
945641AF1-229 GEN
Solar/Wind Harmer
3.442
270499AE1-146 GEN
Solar/Wind Harmer
2.365
971549AH1-272 GEN
Solar/Wind Harmer
12.831
270297AD1-101 GEN
Solar/Wind Harmer
1.906
966831AG1-554 GEN
Solar/Wind Harmer
0.708
971989AH1-539 GEN
Solar/Wind Harmer
7.656
247607V1-011 GEN
Solar/Wind Harmer
2.323
957201AF2-014 GEN
Solar/Wind Harmer
2.642
270435AC2-044 GEN
Solar/Wind Harmer
1.165
944161AF1-084 GEN
Solar/Wind Harmer
1.269
965041AG1-368 GEN
Solar/Wind Harmer
5.468
965051AG1-369 GEN
Solar/Wind Harmer
2.716
971771AH1-392 GEN
Solar/Wind Harmer
4.733
270302AB2-170 GEN
Solar/Wind Harmer
4.373
270317AD1-130_GEN
Solar/Wind Harmer
1.676
971769AH1-391 GEN
Solar/Wind Harmer
5.127
971567AH1-282 GEN
Solar/Wind Harmer
7.606
960681AF2-359 GEN
Solar/Wind Harmer
1.863
971347AH1-153 GEN
Solar/Wind Harmer
7.365
963791AG1-232 GEN
Solar/Wind Harmer
6.558
270578AF1-285 GEN2
Solar/Wind Harmer
0.225
270536AF1-215 GEN2
Solar/Wind Harmer
2.114
270071AF1-092 GEN
Solar/Wind Harmer
6.904
23929302BS-PKR
50/50
2.267
241832AE2-181_GEN
Solar/Wind Harmer
1.96
958321AF2-126 GEN
Solar/Wind Harmer
1.494
23906502RICHG2&3
Adder
1.32
270575GUS2 35KV
Solar/Wind Harmer
10.036
270541AE2-072 C
Solar/Wind Harmer
4.33
970217AG2-149 GEN
Solar/Wind Harmer
22.419
270044AE2-322 C
Solar/Wind Harmer
0.854
270404AC1-167 GEN
Solar/Wind Harmer
0.711
270258AD1-119 GEN
Solar/Wind Harmer
1.74
270588AE1-091_GEN
Solar/Wind Harmer
6.813
247604X1-042
Adder
0.253
24441205WTRV SLR C
Solar/Wind Harmer
0.08
958091AF2-103 GEN
Solar/Wind Harmer
0.095
270491AE1-102 GEN2
Solar/Wind Harmer
0.757
945111AF1-176 GEN
Solar/Wind Harmer
3.137
270191TR4_S_V150
Solar/Wind Harmer
1.632
270247TR4_N_V136
Solar/Wind Harmer
0.463
24642205MAYFLWER
Adder
0.343
970031AG2-029 GEN
Solar/Wind Harmer
16.05
247643Z2-116 C
Solar/Wind Harmer
0.037
959331AF2-224 GEN
Solar/Wind Harmer
5.243
965021AG1-366 GEN
Solar/Wind Harmer
1.219
270485AE1-090_GEN
Solar/Wind Harmer
0.316
270043AE2-236 GEN
Solar/Wind Harmer
2.723
970349AG2-230 GEN
Solar/Wind Harmer
7.365
942871AE2-306 GEN
Solar/Wind Harmer
0.439
270391AF1-285 GEN3
Solar/Wind Harmer
0.225
270377AD1-106 GEN
Solar/Wind Harmer
2.883
270535AF1-215 GEN1
Solar/Wind Harmer
2.114
972231SS25-0005
Solar/Wind Harmer
4.354
972181SS23-001
Solar/Wind Harmer
2.721
274752CRETE EC ;2U
Adder
2.243
274753CRETE EC ;3U
Adder
2.243
964401AG1-302 GEN
Solar/Wind Harmer
4.148
274724RIVER EC ;11
Adder
8.061
959141AF2-205 GEN
Solar/Wind Harmer
2.72
274802UNIV PARK;5U
Adder
2.613
274826FISK ;BP
Adder
4.899
274800UNIV PARK;3U
Adder
2.605
972038AH1-567 GEN2
Adder
0.163
276772AC2-154 GEN
Solar/Wind Harmer
1.244
276806AD2-047 C O1
Solar/Wind Harmer
4.772
970941AG2-585 GEN
Solar/Wind Harmer
5.576
274772LINCOLN ;3U
Adder
2.764
972228AH1-698 GEN2
Adder
1.647
274676JOLIET 29;8U
Adder
13.089
276897AD1-100 C
Solar/Wind Harmer
12.825
939351AE1-166 GEN
Solar/Wind Harmer
2.621
276893AG1-478 C
Solar/Wind Harmer
0.185
274729ELWOOD EC;1P
Adder
7.259
274730ELWOOD EC;6P
Adder
7.259
274734ELWOOD EC;8P
Adder
7.259
274736ELWOOD EC;9P
Adder
7.259
970707AG2-453 GEN
Solar/Wind Harmer
12.364
970513AG2-328 GEN
Solar/Wind Harmer
7.863
970517AG2-330 GEN
Solar/Wind Harmer
7.132
971617AH1-308 GEN
Solar/Wind Harmer
2.555
943121AE2-341 GEN
Solar/Wind Harmer
6.548
943591AF1-030 GEN
Solar/Wind Harmer
4.365
274682WAUKEGAN ;7U
Adder
7.794
962511AG1-100 GEN
Solar/Wind Helper
0.339
203830AF1-094 GEN
Solar/Wind Helper
0.321
959441AF2-235 GEN
Solar/Wind Helper
0.146
254305AE2-115 C
Solar/Wind Helper
0.111
20334926Z1-069 C
Solar/Wind Helper
0.639
276694AA1-018 GEN2
Solar/Wind Harmer
0.632
958391AF2-133 GEN
Solar/Wind Harmer
4.11
274814UNIV PK N;0U
Adder
2.289
274807UNIV PK N;3U
Adder
2.285
274805UNIV PK N;1U
Adder
2.275
274811UNIV PK N;7U
Adder
2.27
972037AH1-567 GEN1
Adder
0.082
274827FISK ;RP
Adder
3.472
960591AF2-350 GEN
Solar/Wind Harmer
4.461
274775LINCOLN ;6U
Adder
2.764
274776LINCOLN ;7U
Adder
2.764
274777LINCOLN ;8U
Adder
2.764
972227AH1-698 GEN1
Adder
1.16
274687WILL CNTY;4U
Adder
12.387
274687WILL CNTY;4U
Adder
12.387
274675JOLIET 29;7U
Adder
13.573
274675JOLIET 29;7U
Adder
13.089
274731ELWOOD EC;2P
Adder
7.259
274733ELWOOD EC;3P
Adder
7.259
274735ELWOOD EC;4P
Adder
7.259
274728ELWOOD EC;5P
Adder
7.259
270024AE2-089 GEN
Solar/Wind Harmer
2.063
970833AG2-524 GEN
Solar/Wind Harmer
3.836
970833AG2-524 GEN
Solar/Wind Harmer
1.784
274746AC1-111 G10
Adder
2.441
274744AC1-111 GEN8
Adder
2.441
241886AC2-103 GEN2
Solar/Wind Helper
9.447
241982AE2-343 S C
Solar/Wind Helper
0.117
254304AE2-114 C
Solar/Wind Helper
0.111
203846AF2-130 C
Solar/Wind Helper
0.246
241997AF1-093 GEN
Solar/Wind Helper
0.129
203804AE2-113_GEN
Solar/Wind Helper
0.858
24189902OREGON_CT2
50/50
2.599
23888702TROY G3
50/50
1.766
972253AH1-711 GEN
50/50
53.942
23856402BAYSG1
50/50
1.288
23920202STRYCT
50/50
1.908
241858AF1-205_GEN
Solar/Wind Harmer
5.509
241808AF1-120 C
Solar/Wind Harmer
1.205
241840AF1-064_GEN
Solar/Wind Harmer
1.394
972301AH1-735 GEN
Adder
6.613
23906402RICHG1
Adder
1.323
23906502RICHG2&3
Adder
1.32
270361_3
Solar/Wind Harmer
8.519
960841AF2-375 GEN
Solar/Wind Harmer
3.762
241807AE2-176_GEN
Solar/Wind Harmer
2.793
247522W1-056 GEN
Solar/Wind Harmer
1.578
970515AG2-329 GEN
Solar/Wind Harmer
10.167
944231AF1-091 GEN
Solar/Wind Harmer
2.462
246936BC-WTG1
Solar/Wind Harmer
2.279
270489AE1-102 GEN1
Solar/Wind Harmer
0.757
965421AG1-410 GEN
Solar/Wind Harmer
17.306
270449AD2-020 GEN
Solar/Wind Harmer
1.589
943021AE2-325 GEN
Solar/Wind Harmer
2.064
270428AC2-015 C
Solar/Wind Harmer
3.1
24695305TIMB G C
Solar/Wind Harmer
3.1
945111AF1-176 GEN
Solar/Wind Harmer
9.898
270505AE1-170 C O1
Solar/Wind Harmer
8.313
247521TR3_G114
Solar/Wind Harmer
1.829
270246TR4_N_V150
Solar/Wind Harmer
0.463
24639705ELKHART HY
Adder
0.083
270063AE2-323 C
Solar/Wind Harmer
1.182
965011AG1-365 GEN
Solar/Wind Harmer
5.243
270462AD2-086
Solar/Wind Harmer
3.638
270223U2-072_GEN1
Solar/Wind Harmer
0.958
270578AF1-285 GEN2
Solar/Wind Harmer
0.586
270391AF1-285 GEN3
Solar/Wind Harmer
0.586
970373AG2-245 GEN
Solar/Wind Harmer
9.966
270055AF2-134 C O1
Solar/Wind Harmer
1.409
274751CRETE EC ;1U
Adder
2.243
274754CRETE EC ;4U
Adder
2.243
958381AF2-132 GEN
Solar/Wind Harmer
4.148
964861AG1-349 GEN
Solar/Wind Harmer
3.588
971917AH1-482 GEN
Solar/Wind Harmer
4.14
274723RIVER EC ;12
Adder
8.158
274812UNIV PK N;8U
Adder
2.27
276164X3-005 C
Solar/Wind Harmer
0.317
274801UNIV PARK;4U
Adder
2.605
940581AE2-045 GEN
Solar/Wind Harmer
4.55
276776AD2-060 GEN
Solar/Wind Harmer
0.189
971605AH1-302 GEN
Solar/Wind Harmer
3.891
972207SS24-0001
Solar/Wind Harmer
9.829
274773LINCOLN ;4U
Adder
2.764
274774LINCOLN ;5U
Adder
2.764
274676JOLIET 29;8U
Adder
13.573
941551AE2-152 GEN
Solar/Wind Harmer
2.004
274732ELWOOD EC;7P
Adder
7.259
274674JOLIET 9 ;6U
Adder
6.799
970245AG2-165 GEN
Solar/Wind Harmer
7.863
274871GR RIDGE ;2U
Solar/Wind Harmer
3.377
970905AG2-564 GEN
Solar/Wind Harmer
2.194
274745AC1-111 GEN9
Adder
2.441
274682WAUKEGAN ;7U
Adder
7.794
274828WAUKEGAN ;BP
Adder
4.786
241885AC2-103 GEN1
Solar/Wind Helper
9.447
961971AG1-040 GEN
Solar/Wind Helper
0.332
203835AF1-098 GEN
Solar/Wind Helper
1.307
203860AG1-193 C
Solar/Wind Helper
0.148
241966AE1-183 GEN
Solar/Wind Helper
0.129
254303AC2-168 GEN
Solar/Wind Helper
0.075
276691AA1-018 GEN1
Solar/Wind Harmer
0.047
24190002OREGON_ST1
50/50
3.497
24189802OREGON_CT1
50/50
2.653
23888802TROY G4
50/50
1.766
241996AE2-282_GEN
Solar/Wind Harmer
2.162
971677AH1-339 GEN
Solar/Wind Harmer
6.682
270007AE1-245 C
Solar/Wind Harmer
3.485
942801AE2-298 GEN
Solar/Wind Harmer
0.882
246938BC-WTG3
Solar/Wind Harmer
2.318
246937BC-WTG2
Solar/Wind Harmer
2.279
961051AF2-396 GEN
Solar/Wind Harmer
8.926
961051AF2-396 GEN
Solar/Wind Harmer
4.152
960981AF2-389 GEN
Solar/Wind Harmer
0.835
957891AF2-083 GEN
Solar/Wind Harmer
1.863
247620Y3-023
Adder
0.25
270216AD2-079_GEN
Solar/Wind Harmer
0.324
970611AG2-400 GEN
Solar/Wind Harmer
5.243
270526AF1-158 GEN
Solar/Wind Harmer
2.341
24441505OLIV SLR
Solar/Wind Harmer
0.069
965681AG1-436 GEN
Solar/Wind Harmer
6.166
965791AG1-447 GEN
Solar/Wind Harmer
3.155
270224U2-072_GEN2
Solar/Wind Harmer
0.958
270227U2-072_GEN3
Solar/Wind Harmer
0.958
270228U2-072_GEN4
Solar/Wind Harmer
0.958
270231U2-072_GEN5
Solar/Wind Harmer
0.958
971231AH1-075 GEN
Solar/Wind Harmer
0.374
274808UNIV PK N;4U
Adder
2.26
274803UNIV PARK;6U
Adder
2.613
274888KELLY CRK;1U
Solar/Wind Harmer
2.634
274887GEN-1.85
Solar/Wind Harmer
2.378
276843GEN-1.7
Solar/Wind Harmer
0.256
958011AF2-095 GEN
Solar/Wind Harmer
6.424
274770LINCOLN ;1U
Adder
2.764
274771LINCOLN ;2U
Adder
2.764
942221AE2-234 GEN
Solar/Wind Harmer
0.326
972259AH1-714 GEN
Adder
8.447
274674JOLIET 9 ;6U
Adder
6.799
970321AG2-212 GEN
Solar/Wind Harmer
7.863
274847GR RIDGE ;BU
Solar/Wind Harmer
2.221
274696ROCKY RD ;4P
Adder
4.941
274695ROCKY RD ;2P
Adder
4.827
274693ROCKY RD ;1P
Adder
4.78
274697ROCKY RD ;3P
Adder
1.311
274683WAUKEGAN ;8U
Adder
9.13
274683WAUKEGAN ;8U
Adder
7.697
203947AF1-006 C
Solar/Wind Helper
0.378
203980AG1-197 GEN
Solar/Wind Helper
0.247
203979AG1-198 GEN
Solar/Wind Helper
0.193
241967AE2-285_GEN
Solar/Wind Helper
0.336
241801AE1-079 GEN
Solar/Wind Helper
0.131
241985AE1-237 GEN
Solar/Wind Helper
0.13
962101AG1-054 GEN
Solar/Wind Helper
0.324
946381AF1-302 GEN
Solar/Wind Helper
0.104
238217AF1-153 C O1
Solar/Wind Helper
0.11
991177J1571 G
External Queue
14.956707954406738
990527J1329
External Queue
1.7751743793487549
990142J1224
External Queue
12.976524353027344
991182J1586 G
External Queue
24.279396057128906
LAGNLTFEXP_LAGN->PJM
CLTF
4.838
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.167
TVALTFEXP_TVA->PJM
CLTF
2.196
CPLELTFEXP_CPLE->PJM
CLTF
0.331
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.653
NYPJM->LTFIMP_NY
CLTF
2
LGEELTFEXP_LGEE->PJM
CLTF
1.969
WECLTFEXP_WEC->PJM
CLTF
1.618
AG2-052LTFEXP_AG2-052->PJM
LTF
0.104
AH1-155LTFEXP_AH1-155->PJM
LTF
0.156
CBM West 1LTFEXP_CBM-W1->PJM
CBM
91.607
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.701
MECLTFEXP_MEC->PJM
CLTF
6.308
SIGELTFEXP_SIGE->PJM
CLTF
0.164

Details for 02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line l/o ATSI_P1-2_OEC-345-810_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_OEC-345-810_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:136.64 %
Rating:1646.0 MVA
Rating Type:B
MVA to Mitigate:2249.01
MW Contribution:10.01
Bus #Bus NameTypeMW Contribution
24189902OREGON_CT2
50/50
2.668
23888702TROY G3
50/50
1.796
972253AH1-711 GEN
50/50
54.848
23856402BAYSG1
50/50
1.209
23920202STRYCT
50/50
1.869
241858AF1-205_GEN
Solar/Wind Harmer
3.76
241808AF1-120 C
Solar/Wind Harmer
0.003
241840AF1-064_GEN
Solar/Wind Harmer
0.004
972301AH1-735 GEN
Adder
6.461
23906402RICHG1
Adder
1.292
23906502RICHG2&3
Adder
1.289
270361_3
Solar/Wind Harmer
4.199
960841AF2-375 GEN
Solar/Wind Harmer
-0.001
970515AG2-329 GEN
Solar/Wind Harmer
12.4
247522W1-056 GEN
Solar/Wind Harmer
0.001
944231AF1-091 GEN
Solar/Wind Harmer
1.197
246936BC-WTG1
Solar/Wind Harmer
0.162
270489AE1-102 GEN1
Solar/Wind Harmer
0.52
965421AG1-410 GEN
Solar/Wind Harmer
11.889
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.06
945111AF1-176 GEN
Solar/Wind Harmer
6.886
270505AE1-170 C O1
Solar/Wind Harmer
4.049
24695305TIMB G C
Solar/Wind Harmer
0.001
24639705ELKHART HY
Adder
0.082
247521TR3_G114
Solar/Wind Harmer
0.136
270246TR4_N_V150
Solar/Wind Harmer
0.024
270063AE2-323 C
Solar/Wind Harmer
0.003
965011AG1-365 GEN
Solar/Wind Harmer
3.614
270462AD2-086
Solar/Wind Harmer
0.007
270223U2-072_GEN1
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
6.918
270055AF2-134 C O1
Solar/Wind Harmer
0.003
274751CRETE EC ;1U
Adder
3.76
274754CRETE EC ;4U
Adder
3.76
958381AF2-132 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.117
274723RIVER EC ;12
Adder
8.113
274812UNIV PK N;8U
Adder
2.257
276164X3-005 C
Solar/Wind Harmer
0
274801UNIV PARK;4U
Adder
2.59
276776AD2-060 GEN
Solar/Wind Harmer
0.323
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
3.867
274773LINCOLN ;4U
Adder
3.741
274774LINCOLN ;5U
Adder
3.741
274676JOLIET 29;8U
Adder
13.494
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
7.217
274674JOLIET 9 ;6U
Adder
6.759
970245AG2-165 GEN
Solar/Wind Harmer
1.323
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
2.426
276691AA1-018 GEN1
Solar/Wind Harmer
0.367
274682WAUKEGAN ;7U
Adder
7.748
274828WAUKEGAN ;BP
Adder
4.757
241885AC2-103 GEN1
Solar/Wind Helper
9.126
961971AG1-040 GEN
Solar/Wind Helper
0.324
203835AF1-098 GEN
Solar/Wind Helper
1.276
203860AG1-193 C
Solar/Wind Helper
0.145
241966AE1-183 GEN
Solar/Wind Helper
0.126
241807AE2-176_GEN
Solar/Wind Helper
0.764
254303AC2-168 GEN
Solar/Wind Helper
0.074
23867002DVBSG1
50/50
14.11
972211AH1-690 GEN
50/50
287.754
23888502TROY G1
50/50
1.796
23888602TROY G2
50/50
1.796
970817AG2-515 GEN
Solar/Wind Harmer
10.489
945411AF1-206 GEN
Solar/Wind Harmer
-0.001
945641AF1-229 GEN
Solar/Wind Harmer
0.001
270499AE1-146 GEN
Solar/Wind Harmer
0.027
971549AH1-272 GEN
Solar/Wind Harmer
10.011
270297AD1-101 GEN
Solar/Wind Harmer
0.001
247607V1-011 GEN
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.507
971619AH1-309 GEN
Solar/Wind Harmer
1.735
971989AH1-539 GEN
Solar/Wind Harmer
1.661
965041AG1-368 GEN
Solar/Wind Harmer
3.753
965051AG1-369 GEN
Solar/Wind Harmer
1.862
971771AH1-392 GEN
Solar/Wind Harmer
3.655
270302AB2-170 GEN
Solar/Wind Harmer
0.002
270317AD1-130_GEN
Solar/Wind Harmer
0.005
971653AH1-327 GEN
Solar/Wind Harmer
0.502
971769AH1-391 GEN
Solar/Wind Harmer
3.979
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971567AH1-282 GEN
Solar/Wind Harmer
5.126
971347AH1-153 GEN
Solar/Wind Harmer
5.114
963791AG1-232 GEN
Solar/Wind Harmer
4.516
270578AF1-285 GEN2
Solar/Wind Harmer
0.22
270536AF1-215 GEN2
Solar/Wind Harmer
0.004
270071AF1-092 GEN
Solar/Wind Harmer
6.095
274814UNIV PK N;0U
Adder
2.277
274807UNIV PK N;3U
Adder
2.272
274805UNIV PK N;1U
Adder
2.262
274811UNIV PK N;7U
Adder
2.257
958391AF2-133 GEN
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.082
274827FISK ;RP
Adder
3.452
960591AF2-350 GEN
Solar/Wind Harmer
3.094
971611AH1-305 GEN
Solar/Wind Harmer
1.842
274775LINCOLN ;6U
Adder
3.741
274776LINCOLN ;7U
Adder
3.741
274777LINCOLN ;8U
Adder
3.741
972227AH1-698 GEN1
Adder
1.153
274687WILL CNTY;4U
Adder
12.315
274687WILL CNTY;4U
Adder
12.315
274675JOLIET 29;7U
Adder
13.494
274675JOLIET 29;7U
Adder
13.012
274731ELWOOD EC;2P
Adder
7.217
274733ELWOOD EC;3P
Adder
7.217
274735ELWOOD EC;4P
Adder
7.217
274728ELWOOD EC;5P
Adder
7.217
970833AG2-524 GEN
Solar/Wind Harmer
3.353
970833AG2-524 GEN
Solar/Wind Harmer
2.235
274746AC1-111 G10
Adder
2.426
274744AC1-111 GEN8
Adder
2.426
270024AE2-089 GEN
Solar/Wind Harmer
0.003
241886AC2-103 GEN2
Solar/Wind Helper
9.126
241982AE2-343 S C
Solar/Wind Helper
0.114
254304AE2-114 C
Solar/Wind Helper
0.109
203846AF2-130 C
Solar/Wind Helper
0.24
241997AF1-093 GEN
Solar/Wind Helper
0.126
203804AE2-113_GEN
Solar/Wind Helper
0.838
23929302BS-PKR
50/50
2.128
241832AE2-181_GEN
Solar/Wind Harmer
0.003
958321AF2-126 GEN
Solar/Wind Harmer
1.111
23906502RICHG2&3
Adder
1.289
270541AE2-072 C
Solar/Wind Harmer
0.008
270575GUS2 35KV
Solar/Wind Harmer
4.199
970217AG2-149 GEN
Solar/Wind Harmer
4.133
270404AC1-167 GEN
Solar/Wind Harmer
0.002
270258AD1-119 GEN
Solar/Wind Harmer
0.001
247604X1-042
Adder
0.253
24441205WTRV SLR C
Solar/Wind Harmer
0
270588AE1-091_GEN
Solar/Wind Harmer
3.195
270491AE1-102 GEN2
Solar/Wind Harmer
0.52
945111AF1-176 GEN
Solar/Wind Harmer
3.128
24642205MAYFLWER
Adder
0.342
270191TR4_S_V150
Solar/Wind Harmer
0
270247TR4_N_V136
Solar/Wind Harmer
0.024
247643Z2-116 C
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
2.41
959331AF2-224 GEN
Solar/Wind Harmer
2.53
965021AG1-366 GEN
Solar/Wind Harmer
1.205
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270043AE2-236 GEN
Solar/Wind Harmer
2.196
970349AG2-230 GEN
Solar/Wind Harmer
5.114
270391AF1-285 GEN3
Solar/Wind Harmer
0.22
270535AF1-215 GEN1
Solar/Wind Harmer
0.004
274752CRETE EC ;2U
Adder
3.76
274753CRETE EC ;3U
Adder
3.76
964401AG1-302 GEN
Solar/Wind Harmer
0
274724RIVER EC ;11
Adder
8.016
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
274802UNIV PARK;5U
Adder
2.599
274826FISK ;BP
Adder
4.871
274800UNIV PARK;3U
Adder
2.59
972038AH1-567 GEN2
Adder
0.162
276806AD2-047 C O1
Solar/Wind Harmer
1.753
970941AG2-585 GEN
Solar/Wind Harmer
3.868
274772LINCOLN ;3U
Adder
3.741
972228AH1-698 GEN2
Adder
1.638
274676JOLIET 29;8U
Adder
13.012
276897AD1-100 C
Solar/Wind Harmer
0.004
939351AE1-166 GEN
Solar/Wind Harmer
0
276893AG1-478 C
Solar/Wind Harmer
0.121
274729ELWOOD EC;1P
Adder
7.217
274730ELWOOD EC;6P
Adder
7.217
274734ELWOOD EC;8P
Adder
7.217
274736ELWOOD EC;9P
Adder
7.217
970707AG2-453 GEN
Solar/Wind Harmer
10.005
970513AG2-328 GEN
Solar/Wind Harmer
1.323
970517AG2-330 GEN
Solar/Wind Harmer
7.937
943121AE2-341 GEN
Solar/Wind Harmer
5.076
943591AF1-030 GEN
Solar/Wind Harmer
3.375
276694AA1-018 GEN2
Solar/Wind Harmer
0
971617AH1-308 GEN
Solar/Wind Harmer
2.521
274682WAUKEGAN ;7U
Adder
7.748
962511AG1-100 GEN
Solar/Wind Helper
0.331
203830AF1-094 GEN
Solar/Wind Helper
0.313
959441AF2-235 GEN
Solar/Wind Helper
0.142
254305AE2-115 C
Solar/Wind Helper
0.109
24190002OREGON_ST1
50/50
3.59
24189802OREGON_CT1
50/50
2.723
23888802TROY G4
50/50
1.796
241996AE2-282_GEN
Solar/Wind Harmer
0.005
971677AH1-339 GEN
Solar/Wind Harmer
0.601
970621AG2-405 GEN
Solar/Wind Harmer
0.845
970623AG2-406 GEN
Solar/Wind Harmer
0.78
270007AE1-245 C
Solar/Wind Harmer
0.001
246938BC-WTG3
Solar/Wind Harmer
0.145
246937BC-WTG2
Solar/Wind Harmer
0.162
961051AF2-396 GEN
Solar/Wind Harmer
7.827
961051AF2-396 GEN
Solar/Wind Harmer
5.218
957891AF2-083 GEN
Solar/Wind Harmer
0.001
247620Y3-023
Adder
0.248
270216AD2-079_GEN
Solar/Wind Harmer
0.001
970611AG2-400 GEN
Solar/Wind Harmer
3.614
970627AG2-408 GEN
Solar/Wind Harmer
1.084
270526AF1-158 GEN
Solar/Wind Harmer
0.004
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
4.283
965791AG1-447 GEN
Solar/Wind Harmer
3.141
270224U2-072_GEN2
Solar/Wind Harmer
0
270227U2-072_GEN3
Solar/Wind Harmer
0
270228U2-072_GEN4
Solar/Wind Harmer
0
270231U2-072_GEN5
Solar/Wind Harmer
0
274808UNIV PK N;4U
Adder
2.247
274803UNIV PARK;6U
Adder
2.599
274888KELLY CRK;1U
Solar/Wind Harmer
0.182
274887GEN-1.85
Solar/Wind Harmer
0.081
276843GEN-1.7
Solar/Wind Harmer
0.1
958011AF2-095 GEN
Solar/Wind Harmer
4.456
274770LINCOLN ;1U
Adder
3.741
274771LINCOLN ;2U
Adder
3.741
972259AH1-714 GEN
Adder
8.397
942221AE2-234 GEN
Solar/Wind Harmer
0.015
274674JOLIET 9 ;6U
Adder
6.759
970321AG2-212 GEN
Solar/Wind Harmer
1.323
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
958481AF2-142 GEN
Solar/Wind Harmer
4.54
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.409
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
971573AH1-285 GEN
Solar/Wind Harmer
0.562
274696ROCKY RD ;4P
Adder
4.912
274695ROCKY RD ;2P
Adder
4.798
274693ROCKY RD ;1P
Adder
4.751
274697ROCKY RD ;3P
Adder
1.303
274683WAUKEGAN ;8U
Adder
9.076
274683WAUKEGAN ;8U
Adder
7.65
203947AF1-006 C
Solar/Wind Helper
0.369
203980AG1-197 GEN
Solar/Wind Helper
0.241
203979AG1-198 GEN
Solar/Wind Helper
0.188
241801AE1-079 GEN
Solar/Wind Helper
0.128
241967AE2-285_GEN
Solar/Wind Helper
0.329
241985AE1-237 GEN
Solar/Wind Helper
0.128
962101AG1-054 GEN
Solar/Wind Helper
0.317
991177J1571 G
External Queue
15.044508934020996
990527J1329
External Queue
1.8002409934997559
990142J1224
External Queue
13.159761428833008
991182J1586 G
External Queue
24.65229034423828
LAGNLTFEXP_LAGN->PJM
CLTF
4.792
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.145
TVALTFEXP_TVA->PJM
CLTF
2.173
CPLELTFEXP_CPLE->PJM
CLTF
0.33
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.291
NYPJM->LTFIMP_NY
CLTF
1.957
LGEELTFEXP_LGEE->PJM
CLTF
1.943
WECLTFEXP_WEC->PJM
CLTF
1.608
AG2-052LTFEXP_AG2-052->PJM
LTF
0.104
AH1-155LTFEXP_AH1-155->PJM
LTF
0.155
CBM West 1LTFEXP_CBM-W1->PJM
CBM
91.866
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.603
MECLTFEXP_MEC->PJM
CLTF
6.264
SIGELTFEXP_SIGE->PJM
CLTF
0.162

Details for 02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line l/o ATSI_P1-2_OEC-345-809_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_OEC-345-809_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:128.94 %
Rating:1646.0 MVA
Rating Type:B
MVA to Mitigate:2122.34
MW Contribution:9.84
Bus #Bus NameTypeMW Contribution
23867002DVBSG1
50/50
12.729
972211AH1-690 GEN
50/50
275.118
23888502TROY G1
50/50
1.736
23888602TROY G2
50/50
1.736
970817AG2-515 GEN
Solar/Wind Harmer
10.289
945411AF1-206 GEN
Solar/Wind Harmer
-0.001
270499AE1-146 GEN
Solar/Wind Harmer
0.029
945641AF1-229 GEN
Solar/Wind Harmer
0.001
971549AH1-272 GEN
Solar/Wind Harmer
9.844
270297AD1-101 GEN
Solar/Wind Harmer
0.001
971989AH1-539 GEN
Solar/Wind Harmer
1.772
247607V1-011 GEN
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.508
971619AH1-309 GEN
Solar/Wind Harmer
1.715
965041AG1-368 GEN
Solar/Wind Harmer
3.769
965051AG1-369 GEN
Solar/Wind Harmer
1.872
971771AH1-392 GEN
Solar/Wind Harmer
3.617
270302AB2-170 GEN
Solar/Wind Harmer
0.002
270317AD1-130_GEN
Solar/Wind Harmer
0.005
971653AH1-327 GEN
Solar/Wind Harmer
0.506
24191202EL_AA1-006
Adder
0.112
971769AH1-391 GEN
Solar/Wind Harmer
3.938
971567AH1-282 GEN
Solar/Wind Harmer
5.256
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971347AH1-153 GEN
Solar/Wind Harmer
5.067
963791AG1-232 GEN
Solar/Wind Harmer
4.517
270578AF1-285 GEN2
Solar/Wind Harmer
0.223
270536AF1-215 GEN2
Solar/Wind Harmer
0.004
270071AF1-092 GEN
Solar/Wind Harmer
6.074
274814UNIV PK N;0U
Adder
2.258
274807UNIV PK N;3U
Adder
2.253
274805UNIV PK N;1U
Adder
2.243
274811UNIV PK N;7U
Adder
2.238
958391AF2-133 GEN
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.081
274827FISK ;RP
Adder
3.424
971611AH1-305 GEN
Solar/Wind Harmer
1.828
960591AF2-350 GEN
Solar/Wind Harmer
3.069
274775LINCOLN ;6U
Adder
3.711
274776LINCOLN ;7U
Adder
3.711
274777LINCOLN ;8U
Adder
3.711
23929302BS-PKR
50/50
2.254
241832AE2-181_GEN
Solar/Wind Harmer
0.003
958321AF2-126 GEN
Solar/Wind Harmer
1.148
23906502RICHG2&3
Adder
1.306
270575GUS2 35KV
Solar/Wind Harmer
4.656
270541AE2-072 C
Solar/Wind Harmer
0.008
970217AG2-149 GEN
Solar/Wind Harmer
4.19
270404AC1-167 GEN
Solar/Wind Harmer
0.002
270258AD1-119 GEN
Solar/Wind Harmer
0.001
270588AE1-091_GEN
Solar/Wind Harmer
3.358
247604X1-042
Adder
0.249
24441205WTRV SLR C
Solar/Wind Harmer
0
270491AE1-102 GEN2
Solar/Wind Harmer
0.522
945111AF1-176 GEN
Solar/Wind Harmer
3.093
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.024
24642205MAYFLWER
Adder
0.338
972227AH1-698 GEN1
Adder
1.144
274687WILL CNTY;4U
Adder
12.217
274687WILL CNTY;4U
Adder
12.217
274675JOLIET 29;7U
Adder
13.387
274675JOLIET 29;7U
Adder
12.909
274731ELWOOD EC;2P
Adder
7.16
274733ELWOOD EC;3P
Adder
7.16
274735ELWOOD EC;4P
Adder
7.16
274728ELWOOD EC;5P
Adder
7.16
270024AE2-089 GEN
Solar/Wind Harmer
0.003
970833AG2-524 GEN
Solar/Wind Harmer
3.326
970833AG2-524 GEN
Solar/Wind Harmer
2.217
274746AC1-111 G10
Adder
2.408
274744AC1-111 GEN8
Adder
2.408
241886AC2-103 GEN2
Solar/Wind Helper
9.503
241982AE2-343 S C
Solar/Wind Helper
0.116
254304AE2-114 C
Solar/Wind Helper
0.11
203846AF2-130 C
Solar/Wind Helper
0.243
241997AF1-093 GEN
Solar/Wind Helper
0.128
203804AE2-113_GEN
Solar/Wind Helper
0.848
970031AG2-029 GEN
Solar/Wind Harmer
2.393
247643Z2-116 C
Solar/Wind Harmer
0
959331AF2-224 GEN
Solar/Wind Harmer
2.528
965021AG1-366 GEN
Solar/Wind Harmer
1.204
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270043AE2-236 GEN
Solar/Wind Harmer
2.187
970349AG2-230 GEN
Solar/Wind Harmer
5.067
270391AF1-285 GEN3
Solar/Wind Harmer
0.223
270377AD1-106 GEN
Solar/Wind Harmer
1.238
270535AF1-215 GEN1
Solar/Wind Harmer
0.004
274752CRETE EC ;2U
Adder
3.728
274753CRETE EC ;3U
Adder
3.728
964401AG1-302 GEN
Solar/Wind Harmer
0
274724RIVER EC ;11
Adder
7.95
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
274802UNIV PARK;5U
Adder
2.577
274826FISK ;BP
Adder
4.831
274800UNIV PARK;3U
Adder
2.569
972038AH1-567 GEN2
Adder
0.161
276806AD2-047 C O1
Solar/Wind Harmer
1.739
970941AG2-585 GEN
Solar/Wind Harmer
3.837
274772LINCOLN ;3U
Adder
3.711
972228AH1-698 GEN2
Adder
1.625
274676JOLIET 29;8U
Adder
12.909
276897AD1-100 C
Solar/Wind Harmer
0.004
939351AE1-166 GEN
Solar/Wind Harmer
0
276893AG1-478 C
Solar/Wind Harmer
0.12
970707AG2-453 GEN
Solar/Wind Harmer
9.926
274729ELWOOD EC;1P
Adder
7.16
274730ELWOOD EC;6P
Adder
7.16
274734ELWOOD EC;8P
Adder
7.16
274736ELWOOD EC;9P
Adder
7.16
970513AG2-328 GEN
Solar/Wind Harmer
1.313
970517AG2-330 GEN
Solar/Wind Harmer
7.878
971617AH1-308 GEN
Solar/Wind Harmer
2.523
943121AE2-341 GEN
Solar/Wind Harmer
5.036
943591AF1-030 GEN
Solar/Wind Harmer
3.349
276694AA1-018 GEN2
Solar/Wind Harmer
0
962511AG1-100 GEN
Solar/Wind Helper
0.335
203830AF1-094 GEN
Solar/Wind Helper
0.317
959441AF2-235 GEN
Solar/Wind Helper
0.144
254305AE2-115 C
Solar/Wind Helper
0.11
20334926Z1-069 C
Solar/Wind Helper
0.632
24189902OREGON_CT2
50/50
2.551
23888702TROY G3
50/50
1.736
972253AH1-711 GEN
50/50
53.019
23856402BAYSG1
50/50
1.281
23920202STRYCT
50/50
1.886
241858AF1-205_GEN
Solar/Wind Harmer
3.799
241808AF1-120 C
Solar/Wind Harmer
0.003
241840AF1-064_GEN
Solar/Wind Harmer
0.004
972301AH1-735 GEN
Adder
6.539
23906402RICHG1
Adder
1.308
23906502RICHG2&3
Adder
1.306
270361_3
Solar/Wind Harmer
4.656
960841AF2-375 GEN
Solar/Wind Harmer
-0.002
241807AE2-176_GEN
Solar/Wind Harmer
0.004
247522W1-056 GEN
Solar/Wind Harmer
0.001
970515AG2-329 GEN
Solar/Wind Harmer
12.569
944231AF1-091 GEN
Solar/Wind Harmer
1.201
270428AC2-015 C
Solar/Wind Harmer
0.002
246936BC-WTG1
Solar/Wind Harmer
0.163
270489AE1-102 GEN1
Solar/Wind Harmer
0.522
965421AG1-410 GEN
Solar/Wind Harmer
11.925
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.035
24695305TIMB G C
Solar/Wind Harmer
0.001
945111AF1-176 GEN
Solar/Wind Harmer
6.808
270505AE1-170 C O1
Solar/Wind Harmer
4.002
247521TR3_G114
Solar/Wind Harmer
0.137
270246TR4_N_V150
Solar/Wind Harmer
0.024
24639705ELKHART HY
Adder
0.082
270063AE2-323 C
Solar/Wind Harmer
0.003
965011AG1-365 GEN
Solar/Wind Harmer
3.611
270462AD2-086
Solar/Wind Harmer
0.008
270223U2-072_GEN1
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
6.857
270055AF2-134 C O1
Solar/Wind Harmer
0.002
970905AG2-564 GEN
Solar/Wind Harmer
1.733
274751CRETE EC ;1U
Adder
3.728
274754CRETE EC ;4U
Adder
3.728
958381AF2-132 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.083
274723RIVER EC ;12
Adder
8.046
274812UNIV PK N;8U
Adder
2.238
276164X3-005 C
Solar/Wind Harmer
0
274801UNIV PARK;4U
Adder
2.569
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
3.837
276776AD2-060 GEN
Solar/Wind Harmer
0.32
274773LINCOLN ;4U
Adder
3.711
274774LINCOLN ;5U
Adder
3.711
274676JOLIET 29;8U
Adder
13.387
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
7.16
274674JOLIET 9 ;6U
Adder
6.706
970245AG2-165 GEN
Solar/Wind Harmer
1.313
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
2.408
276691AA1-018 GEN1
Solar/Wind Harmer
0.364
241885AC2-103 GEN1
Solar/Wind Helper
9.503
961971AG1-040 GEN
Solar/Wind Helper
0.328
203835AF1-098 GEN
Solar/Wind Helper
1.293
203860AG1-193 C
Solar/Wind Helper
0.146
241966AE1-183 GEN
Solar/Wind Helper
0.128
254303AC2-168 GEN
Solar/Wind Helper
0.074
24190002OREGON_ST1
50/50
3.432
24189802OREGON_CT1
50/50
2.603
23888802TROY G4
50/50
1.736
241996AE2-282_GEN
Solar/Wind Harmer
0.005
971677AH1-339 GEN
Solar/Wind Harmer
0.655
970621AG2-405 GEN
Solar/Wind Harmer
0.866
970623AG2-406 GEN
Solar/Wind Harmer
0.788
270007AE1-245 C
Solar/Wind Harmer
0.001
246938BC-WTG3
Solar/Wind Harmer
0.145
246937BC-WTG2
Solar/Wind Harmer
0.163
961051AF2-396 GEN
Solar/Wind Harmer
7.735
961051AF2-396 GEN
Solar/Wind Harmer
5.157
957891AF2-083 GEN
Solar/Wind Harmer
0.001
247620Y3-023
Adder
0.246
270216AD2-079_GEN
Solar/Wind Harmer
0.001
970611AG2-400 GEN
Solar/Wind Harmer
3.611
970627AG2-408 GEN
Solar/Wind Harmer
1.083
270526AF1-158 GEN
Solar/Wind Harmer
0.004
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
4.242
965791AG1-447 GEN
Solar/Wind Harmer
3.111
270224U2-072_GEN2
Solar/Wind Harmer
0
270227U2-072_GEN3
Solar/Wind Harmer
0
270228U2-072_GEN4
Solar/Wind Harmer
0
270231U2-072_GEN5
Solar/Wind Harmer
0
971231AH1-075 GEN
Solar/Wind Harmer
0.374
274808UNIV PK N;4U
Adder
2.229
274803UNIV PARK;6U
Adder
2.577
274888KELLY CRK;1U
Solar/Wind Harmer
0.18
274887GEN-1.85
Solar/Wind Harmer
0.081
276843GEN-1.7
Solar/Wind Harmer
0.099
958011AF2-095 GEN
Solar/Wind Harmer
4.42
274770LINCOLN ;1U
Adder
3.711
274771LINCOLN ;2U
Adder
3.711
942221AE2-234 GEN
Solar/Wind Harmer
0.015
972259AH1-714 GEN
Adder
8.331
274674JOLIET 9 ;6U
Adder
6.706
970321AG2-212 GEN
Solar/Wind Harmer
1.313
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
958481AF2-142 GEN
Solar/Wind Harmer
4.505
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.406
203947AF1-006 C
Solar/Wind Helper
0.374
203980AG1-197 GEN
Solar/Wind Helper
0.244
203979AG1-198 GEN
Solar/Wind Helper
0.19
241967AE2-285_GEN
Solar/Wind Helper
0.332
241801AE1-079 GEN
Solar/Wind Helper
0.129
241985AE1-237 GEN
Solar/Wind Helper
0.129
962101AG1-054 GEN
Solar/Wind Helper
0.321
946381AF1-302 GEN
Solar/Wind Helper
0.103
991177J1571 G
External Queue
14.724894523620605
990527J1329
External Queue
1.745489239692688
990142J1224
External Queue
12.759525299072266
991182J1586 G
External Queue
23.868927001953125
LAGNLTFEXP_LAGN->PJM
CLTF
4.775
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.139
TVALTFEXP_TVA->PJM
CLTF
2.168
CPLELTFEXP_CPLE->PJM
CLTF
0.326
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.144
NYPJM->LTFIMP_NY
CLTF
1.977
LGEELTFEXP_LGEE->PJM
CLTF
1.944
WECLTFEXP_WEC->PJM
CLTF
1.596
AG2-052LTFEXP_AG2-052->PJM
LTF
0.103
AH1-155LTFEXP_AH1-155->PJM
LTF
0.154
CBM West 1LTFEXP_CBM-W1->PJM
CBM
90.231
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.589
MECLTFEXP_MEC->PJM
CLTF
6.223
SIGELTFEXP_SIGE->PJM
CLTF
0.162

Details for 02HAYES-02BEAVER 345.0 kV Ckt 1 line l/o ATSI_P2-3_OEC-345-005_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02HAYES-02BEAVER 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_OEC-345-005_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:146.75 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:2755.89
MW Contribution:13.43
Bus #Bus NameTypeMW Contribution
23867002DVBSG1
50/50
12.801
972211AH1-690 GEN
50/50
288.187
23888502TROY G1
50/50
1.831
23888602TROY G2
50/50
1.831
23860102FRMENG 1
50/50
1.729
23860202FRMENG 2
50/50
1.729
24191202EL_AA1-006
50/50
0.333
241886AC2-103 GEN2
Solar/Wind Harmer
12.859
970817AG2-515 GEN
Solar/Wind Harmer
15.71
945411AF1-206 GEN
Solar/Wind Harmer
8.65
270499AE1-146 GEN
Solar/Wind Harmer
2.686
945641AF1-229 GEN
Solar/Wind Harmer
3.662
270297AD1-101 GEN
Solar/Wind Harmer
2.06
971549AH1-272 GEN
Solar/Wind Harmer
13.433
966831AG1-554 GEN
Solar/Wind Harmer
0.787
971989AH1-539 GEN
Solar/Wind Harmer
8.505
247607V1-011 GEN
Solar/Wind Harmer
2.482
957201AF2-014 GEN
Solar/Wind Harmer
2.805
270435AC2-044 GEN
Solar/Wind Harmer
1.237
944161AF1-084 GEN
Solar/Wind Harmer
1.331
965041AG1-368 GEN
Solar/Wind Harmer
5.807
965051AG1-369 GEN
Solar/Wind Harmer
2.887
270302AB2-170 GEN
Solar/Wind Harmer
4.661
270317AD1-130_GEN
Solar/Wind Harmer
1.787
971771AH1-392 GEN
Solar/Wind Harmer
4.969
971567AH1-282 GEN
Solar/Wind Harmer
8.2
971769AH1-391 GEN
Solar/Wind Harmer
5.381
960681AF2-359 GEN
Solar/Wind Harmer
1.956
270578AF1-285 GEN2
Solar/Wind Harmer
0.24
971347AH1-153 GEN
Solar/Wind Harmer
7.734
963791AG1-232 GEN
Solar/Wind Harmer
6.936
270536AF1-215 GEN2
Solar/Wind Harmer
2.22
270071AF1-092 GEN
Solar/Wind Harmer
7.277
958391AF2-133 GEN
Solar/Wind Harmer
4.316
274814UNIV PK N;0U
Adder
2.404
274807UNIV PK N;3U
Adder
2.399
274805UNIV PK N;1U
Adder
2.388
274811UNIV PK N;7U
Adder
2.383
972037AH1-567 GEN1
Adder
0.086
274827FISK ;RP
Adder
3.645
960591AF2-350 GEN
Solar/Wind Harmer
4.683
274775LINCOLN ;6U
Adder
2.903
274776LINCOLN ;7U
Adder
2.903
274777LINCOLN ;8U
Adder
2.903
972227AH1-698 GEN1
Adder
1.218
274687WILL CNTY;4U
Adder
13.005
274687WILL CNTY;4U
Adder
13.005
270024AE2-089 GEN
Solar/Wind Harmer
2.18
274675JOLIET 29;7U
Adder
14.25
274675JOLIET 29;7U
Adder
13.741
274731ELWOOD EC;2P
Adder
7.621
274733ELWOOD EC;3P
Adder
7.621
274735ELWOOD EC;4P
Adder
7.621
274728ELWOOD EC;5P
Adder
7.621
970833AG2-524 GEN
Solar/Wind Harmer
4.028
970833AG2-524 GEN
Solar/Wind Harmer
1.873
274746AC1-111 G10
Adder
2.563
274744AC1-111 GEN8
Adder
2.563
24729505KEY G4
Adder
2.933
274823ROCKFORD ;21
Adder
8.678
241982AE2-343 S C
Solar/Wind Helper
0.127
254304AE2-114 C
Solar/Wind Helper
0.121
203846AF2-130 C
Solar/Wind Helper
0.267
241997AF1-093 GEN
Solar/Wind Helper
0.14
203804AE2-113_GEN
Solar/Wind Helper
0.935
203855AF2-088 C
Solar/Wind Helper
0.073
24189902OREGON_CT2
50/50
2.672
23856402BAYSG1
50/50
1.43
23888702TROY G3
50/50
1.831
972253AH1-711 GEN
50/50
55.942
23860302FRMENG 3
50/50
3.53
23920202STRYCT
50/50
2.045
241885AC2-103 GEN1
Solar/Wind Harmer
12.859
241807AE2-176_GEN
Solar/Wind Harmer
7.277
241858AF1-205_GEN
Solar/Wind Harmer
5.91
241808AF1-120 C
Solar/Wind Harmer
1.291
241840AF1-064_GEN
Solar/Wind Harmer
1.52
972301AH1-735 GEN
Adder
7.097
23906402RICHG1
Adder
1.419
23906502RICHG2&3
Adder
1.417
270361_3
Solar/Wind Harmer
9.742
960841AF2-375 GEN
Solar/Wind Harmer
4.291
247522W1-056 GEN
Solar/Wind Harmer
1.77
270428AC2-015 C
Solar/Wind Harmer
4.143
970515AG2-329 GEN
Solar/Wind Harmer
10.896
944231AF1-091 GEN
Solar/Wind Harmer
2.617
246936BC-WTG1
Solar/Wind Harmer
2.42
270489AE1-102 GEN1
Solar/Wind Harmer
0.804
965421AG1-410 GEN
Solar/Wind Harmer
18.372
24695305TIMB G C
Solar/Wind Harmer
3.301
270449AD2-020 GEN
Solar/Wind Harmer
1.666
943021AE2-325 GEN
Solar/Wind Harmer
2.165
970905AG2-564 GEN
Solar/Wind Harmer
2.943
945111AF1-176 GEN
Solar/Wind Harmer
10.388
270505AE1-170 C O1
Solar/Wind Harmer
8.723
247521TR3_G114
Solar/Wind Harmer
1.944
270246TR4_N_V150
Solar/Wind Harmer
0.492
24639705ELKHART HY
Adder
0.087
270063AE2-323 C
Solar/Wind Harmer
1.245
270462AD2-086
Solar/Wind Harmer
3.878
965011AG1-365 GEN
Solar/Wind Harmer
5.544
270223U2-072_GEN1
Solar/Wind Harmer
1.021
270578AF1-285 GEN2
Solar/Wind Harmer
0.624
270391AF1-285 GEN3
Solar/Wind Harmer
0.624
970373AG2-245 GEN
Solar/Wind Harmer
10.463
270055AF2-134 C O1
Solar/Wind Harmer
1.48
274751CRETE EC ;1U
Adder
2.355
274754CRETE EC ;4U
Adder
2.355
958381AF2-132 GEN
Solar/Wind Harmer
4.356
964861AG1-349 GEN
Solar/Wind Harmer
3.767
971917AH1-482 GEN
Solar/Wind Harmer
4.347
274723RIVER EC ;12
Adder
8.566
274812UNIV PK N;8U
Adder
2.383
276164X3-005 C
Solar/Wind Harmer
0.333
241847AF2-150_GEN
Solar/Wind Harmer
1.954
274801UNIV PARK;4U
Adder
2.735
940581AE2-045 GEN
Solar/Wind Harmer
4.778
971605AH1-302 GEN
Solar/Wind Harmer
4.086
276776AD2-060 GEN
Solar/Wind Harmer
0.198
972207SS24-0001
Solar/Wind Harmer
10.32
274773LINCOLN ;4U
Adder
2.903
274774LINCOLN ;5U
Adder
2.903
274676JOLIET 29;8U
Adder
14.25
941551AE2-152 GEN
Solar/Wind Harmer
2.104
274732ELWOOD EC;7P
Adder
7.621
274674JOLIET 9 ;6U
Adder
7.138
970245AG2-165 GEN
Solar/Wind Harmer
8.259
274871GR RIDGE ;2U
Solar/Wind Harmer
3.545
274745AC1-111 GEN9
Adder
2.563
274682WAUKEGAN ;7U
Adder
8.182
274828WAUKEGAN ;BP
Adder
5.024
274822ROCKFORD ;11
Adder
8.741
972235AH1-702 GEN1
Adder
1.121
274761LEE CO EC;2U
Adder
4.095
274766LEE CO EC;7U
Adder
4.047
961971AG1-040 GEN
Solar/Wind Helper
0.361
203835AF1-098 GEN
Solar/Wind Helper
1.422
203860AG1-193 C
Solar/Wind Helper
0.161
241966AE1-183 GEN
Solar/Wind Helper
0.14
254303AC2-168 GEN
Solar/Wind Helper
0.082
203954AE2-126 C
Solar/Wind Helper
0.235
24190002OREGON_ST1
50/50
3.596
24189802OREGON_CT1
50/50
2.727
23888802TROY G4
50/50
1.831
241996AE2-282_GEN
Solar/Wind Harmer
2.316
971677AH1-339 GEN
Solar/Wind Harmer
7.553
270007AE1-245 C
Solar/Wind Harmer
3.723
942801AE2-298 GEN
Solar/Wind Harmer
0.943
246938BC-WTG3
Solar/Wind Harmer
2.462
246937BC-WTG2
Solar/Wind Harmer
2.42
961051AF2-396 GEN
Solar/Wind Harmer
9.365
961051AF2-396 GEN
Solar/Wind Harmer
4.356
960981AF2-389 GEN
Solar/Wind Harmer
0.877
957891AF2-083 GEN
Solar/Wind Harmer
1.955
247620Y3-023
Adder
0.262
270216AD2-079_GEN
Solar/Wind Harmer
0.34
970611AG2-400 GEN
Solar/Wind Harmer
5.544
270526AF1-158 GEN
Solar/Wind Harmer
2.458
24441505OLIV SLR
Solar/Wind Harmer
0.072
971231AH1-075 GEN
Solar/Wind Harmer
0.425
965681AG1-436 GEN
Solar/Wind Harmer
6.472
965791AG1-447 GEN
Solar/Wind Harmer
3.311
270224U2-072_GEN2
Solar/Wind Harmer
1.021
270227U2-072_GEN3
Solar/Wind Harmer
1.021
270228U2-072_GEN4
Solar/Wind Harmer
1.021
270231U2-072_GEN5
Solar/Wind Harmer
1.021
274808UNIV PK N;4U
Adder
2.372
274803UNIV PARK;6U
Adder
2.744
942221AE2-234 GEN
Solar/Wind Harmer
0.344
274888KELLY CRK;1U
Solar/Wind Harmer
2.765
274887GEN-1.85
Solar/Wind Harmer
2.496
276843GEN-1.7
Solar/Wind Harmer
0.269
958011AF2-095 GEN
Solar/Wind Harmer
6.744
274770LINCOLN ;1U
Adder
2.903
274771LINCOLN ;2U
Adder
2.903
972259AH1-714 GEN
Adder
8.868
274674JOLIET 9 ;6U
Adder
7.138
970321AG2-212 GEN
Solar/Wind Harmer
8.259
274847GR RIDGE ;BU
Solar/Wind Harmer
2.332
274696ROCKY RD ;4P
Adder
5.187
274695ROCKY RD ;2P
Adder
5.068
274693ROCKY RD ;1P
Adder
5.018
274697ROCKY RD ;3P
Adder
1.377
274683WAUKEGAN ;8U
Adder
9.585
274683WAUKEGAN ;8U
Adder
8.08
274764LEE CO EC;5U
Adder
4.104
274765LEE CO EC;6U
Adder
4.104
274762LEE CO EC;3U
Adder
4.095
274763LEE CO EC;4U
Adder
4.056
972267AH1-718 GEN
Adder
1.82
25326509SID D
Adder
0.57
203947AF1-006 C
Solar/Wind Helper
0.411
203980AG1-197 GEN
Solar/Wind Helper
0.269
203979AG1-198 GEN
Solar/Wind Helper
0.209
241967AE2-285_GEN
Solar/Wind Helper
0.365
241801AE1-079 GEN
Solar/Wind Helper
0.142
241985AE1-237 GEN
Solar/Wind Helper
0.142
962101AG1-054 GEN
Solar/Wind Helper
0.353
946381AF1-302 GEN
Solar/Wind Helper
0.113
238217AF1-153 C O1
Solar/Wind Helper
0.12
20398826ARMNA MT
Solar/Wind Helper
0.712
203853AF1-134 C O1
Solar/Wind Helper
0.222
23929302BS-PKR
50/50
2.517
241832AE2-181_GEN
Solar/Wind Harmer
2.098
958321AF2-126 GEN
Solar/Wind Harmer
1.63
23906502RICHG2&3
Adder
1.417
270575GUS2 35KV
Solar/Wind Harmer
11.477
270541AE2-072 C
Solar/Wind Harmer
4.706
970217AG2-149 GEN
Solar/Wind Harmer
24.027
270044AE2-322 C
Solar/Wind Harmer
0.913
270404AC1-167 GEN
Solar/Wind Harmer
0.76
270588AE1-091_GEN
Solar/Wind Harmer
7.489
270258AD1-119 GEN
Solar/Wind Harmer
1.858
247604X1-042
Adder
0.265
958091AF2-103 GEN
Solar/Wind Harmer
0.101
24441205WTRV SLR C
Solar/Wind Harmer
0.084
270491AE1-102 GEN2
Solar/Wind Harmer
0.804
945111AF1-176 GEN
Solar/Wind Harmer
3.292
270191TR4_S_V150
Solar/Wind Harmer
1.734
270247TR4_N_V136
Solar/Wind Harmer
0.492
24642205MAYFLWER
Adder
0.36
970031AG2-029 GEN
Solar/Wind Harmer
16.895
247643Z2-116 C
Solar/Wind Harmer
0.039
270485AE1-090_GEN
Solar/Wind Harmer
0.337
959331AF2-224 GEN
Solar/Wind Harmer
5.544
965021AG1-366 GEN
Solar/Wind Harmer
1.289
270377AD1-106 GEN
Solar/Wind Harmer
3.284
270043AE2-236 GEN
Solar/Wind Harmer
2.87
942871AE2-306 GEN
Solar/Wind Harmer
0.468
270391AF1-285 GEN3
Solar/Wind Harmer
0.24
970349AG2-230 GEN
Solar/Wind Harmer
7.734
270535AF1-215 GEN1
Solar/Wind Harmer
2.22
972231SS25-0005
Solar/Wind Harmer
4.572
972181SS23-001
Solar/Wind Harmer
2.857
274752CRETE EC ;2U
Adder
2.355
274753CRETE EC ;3U
Adder
2.355
964401AG1-302 GEN
Solar/Wind Harmer
4.356
274724RIVER EC ;11
Adder
8.463
959141AF2-205 GEN
Solar/Wind Harmer
2.857
274802UNIV PARK;5U
Adder
2.744
961961AG1-039 GEN
Solar/Wind Harmer
1.348
274826FISK ;BP
Adder
5.143
274800UNIV PARK;3U
Adder
2.735
972038AH1-567 GEN2
Adder
0.171
276772AC2-154 GEN
Solar/Wind Harmer
1.306
276806AD2-047 C O1
Solar/Wind Harmer
5.01
970941AG2-585 GEN
Solar/Wind Harmer
5.854
274772LINCOLN ;3U
Adder
2.903
972228AH1-698 GEN2
Adder
1.73
274676JOLIET 29;8U
Adder
13.741
971617AH1-308 GEN
Solar/Wind Harmer
2.7
276897AD1-100 C
Solar/Wind Harmer
13.466
939351AE1-166 GEN
Solar/Wind Harmer
2.751
276893AG1-478 C
Solar/Wind Harmer
0.194
274729ELWOOD EC;1P
Adder
7.621
274730ELWOOD EC;6P
Adder
7.621
274734ELWOOD EC;8P
Adder
7.621
274736ELWOOD EC;9P
Adder
7.621
970707AG2-453 GEN
Solar/Wind Harmer
12.981
970513AG2-328 GEN
Solar/Wind Harmer
8.259
970517AG2-330 GEN
Solar/Wind Harmer
7.49
274682WAUKEGAN ;7U
Adder
8.182
972236AH1-702 GEN2
Adder
0.975
274760LEE CO EC;1U
Adder
4.095
274767LEE CO EC;8U
Adder
4.047
962511AG1-100 GEN
Solar/Wind Helper
0.369
203830AF1-094 GEN
Solar/Wind Helper
0.349
959441AF2-235 GEN
Solar/Wind Helper
0.159
254305AE2-115 C
Solar/Wind Helper
0.121
20334926Z1-069 C
Solar/Wind Helper
0.696
203854AF2-039 C
Solar/Wind Helper
0.151
203818AF1-086 GEN
Solar/Wind Helper
0.772
943121AE2-341 GEN
Solar/Wind Harmer
2.136
943591AF1-030 GEN
Solar/Wind Harmer
1.424
991177J1571 G
External Queue
15.714932441711426
990527J1329
External Queue
1.8513455390930176
990142J1224
External Queue
13.53333568572998
991182J1586 G
External Queue
25.292837142944336
LAGNLTFEXP_LAGN->PJM
CLTF
5.047
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.15
TVALTFEXP_TVA->PJM
CLTF
2.288
CPLELTFEXP_CPLE->PJM
CLTF
0.293
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.459
NYPJM->LTFIMP_NY
CLTF
2.188
LGEELTFEXP_LGEE->PJM
CLTF
2.068
WECLTFEXP_WEC->PJM
CLTF
1.698
AG2-052LTFEXP_AG2-052->PJM
LTF
0.109
AH1-155LTFEXP_AH1-155->PJM
LTF
0.164
CBM West 1LTFEXP_CBM-W1->PJM
CBM
95.745
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.083
MECLTFEXP_MEC->PJM
CLTF
6.617
SIGELTFEXP_SIGE->PJM
CLTF
0.172

Details for 02HAYES-02BEAVER 345.0 kV Ckt 1 line l/o ATSI_P2-3_OEC-345-006_SRT-SL


Base Case Flowgate

Area:ATSI
Facility Description:
02HAYES-02BEAVER 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_OEC-345-006_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:144.08 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:2705.74
MW Contribution:13.58
Bus #Bus NameTypeMW Contribution
24189902OREGON_CT2
50/50
2.686
23856402BAYSG1
50/50
1.441
23888702TROY G3
50/50
1.842
972253AH1-711 GEN
50/50
56.254
23860302FRMENG 3
50/50
3.59
23920202STRYCT
50/50
2.06
241885AC2-103 GEN1
Solar/Wind Harmer
12.88
241807AE2-176_GEN
Solar/Wind Harmer
7.419
241858AF1-205_GEN
Solar/Wind Harmer
5.953
241808AF1-120 C
Solar/Wind Harmer
1.301
241840AF1-064_GEN
Solar/Wind Harmer
1.533
972301AH1-735 GEN
Adder
7.158
23906402RICHG1
Adder
1.432
23906502RICHG2&3
Adder
1.43
270361_3
Solar/Wind Harmer
9.878
960841AF2-375 GEN
Solar/Wind Harmer
4.35
247522W1-056 GEN
Solar/Wind Harmer
1.802
270428AC2-015 C
Solar/Wind Harmer
4.301
970515AG2-329 GEN
Solar/Wind Harmer
11.13
944231AF1-091 GEN
Solar/Wind Harmer
2.648
246936BC-WTG1
Solar/Wind Harmer
2.454
270489AE1-102 GEN1
Solar/Wind Harmer
0.815
965421AG1-410 GEN
Solar/Wind Harmer
18.626
970905AG2-564 GEN
Solar/Wind Harmer
3.098
24695305TIMB G C
Solar/Wind Harmer
3.347
270449AD2-020 GEN
Solar/Wind Harmer
1.687
943021AE2-325 GEN
Solar/Wind Harmer
2.193
945111AF1-176 GEN
Solar/Wind Harmer
10.521
270505AE1-170 C O1
Solar/Wind Harmer
8.835
247521TR3_G114
Solar/Wind Harmer
1.972
270246TR4_N_V150
Solar/Wind Harmer
0.499
24639705ELKHART HY
Adder
0.088
270063AE2-323 C
Solar/Wind Harmer
1.262
270462AD2-086
Solar/Wind Harmer
3.938
965011AG1-365 GEN
Solar/Wind Harmer
5.623
270223U2-072_GEN1
Solar/Wind Harmer
1.038
270578AF1-285 GEN2
Solar/Wind Harmer
0.635
23867002DVBSG1
50/50
12.822
972211AH1-690 GEN
50/50
289.616
23888502TROY G1
50/50
1.842
23888602TROY G2
50/50
1.842
23860102FRMENG 1
50/50
1.758
23860202FRMENG 2
50/50
1.758
24191202EL_AA1-006
50/50
0.345
241886AC2-103 GEN2
Solar/Wind Harmer
12.88
970817AG2-515 GEN
Solar/Wind Harmer
15.806
945411AF1-206 GEN
Solar/Wind Harmer
8.713
270499AE1-146 GEN
Solar/Wind Harmer
2.723
945641AF1-229 GEN
Solar/Wind Harmer
3.712
270297AD1-101 GEN
Solar/Wind Harmer
2.086
971549AH1-272 GEN
Solar/Wind Harmer
13.576
966831AG1-554 GEN
Solar/Wind Harmer
0.802
971989AH1-539 GEN
Solar/Wind Harmer
8.669
247607V1-011 GEN
Solar/Wind Harmer
2.516
957201AF2-014 GEN
Solar/Wind Harmer
2.844
270435AC2-044 GEN
Solar/Wind Harmer
1.254
944161AF1-084 GEN
Solar/Wind Harmer
1.348
965041AG1-368 GEN
Solar/Wind Harmer
5.889
965051AG1-369 GEN
Solar/Wind Harmer
2.928
270302AB2-170 GEN
Solar/Wind Harmer
4.734
270317AD1-130_GEN
Solar/Wind Harmer
1.815
971567AH1-282 GEN
Solar/Wind Harmer
8.435
971771AH1-392 GEN
Solar/Wind Harmer
5.035
971769AH1-391 GEN
Solar/Wind Harmer
5.455
960681AF2-359 GEN
Solar/Wind Harmer
1.984
270578AF1-285 GEN2
Solar/Wind Harmer
0.244
971347AH1-153 GEN
Solar/Wind Harmer
7.843
963791AG1-232 GEN
Solar/Wind Harmer
7.04
270536AF1-215 GEN2
Solar/Wind Harmer
2.253
270071AF1-092 GEN
Solar/Wind Harmer
7.388
958391AF2-133 GEN
Solar/Wind Harmer
4.381
274814UNIV PK N;0U
Adder
2.44
274807UNIV PK N;3U
Adder
2.434
274805UNIV PK N;1U
Adder
2.424
274811UNIV PK N;7U
Adder
2.419
972037AH1-567 GEN1
Adder
0.087
274827FISK ;RP
Adder
3.7
960591AF2-350 GEN
Solar/Wind Harmer
4.754
274775LINCOLN ;6U
Adder
2.947
274776LINCOLN ;7U
Adder
2.947
24190002OREGON_ST1
50/50
3.613
24189802OREGON_CT1
50/50
2.741
23888802TROY G4
50/50
1.842
241996AE2-282_GEN
Solar/Wind Harmer
2.333
971677AH1-339 GEN
Solar/Wind Harmer
7.68
270007AE1-245 C
Solar/Wind Harmer
3.775
942801AE2-298 GEN
Solar/Wind Harmer
0.956
246938BC-WTG3
Solar/Wind Harmer
2.496
246937BC-WTG2
Solar/Wind Harmer
2.454
961051AF2-396 GEN
Solar/Wind Harmer
9.484
961051AF2-396 GEN
Solar/Wind Harmer
4.411
960981AF2-389 GEN
Solar/Wind Harmer
0.888
957891AF2-083 GEN
Solar/Wind Harmer
1.981
247620Y3-023
Adder
0.266
270216AD2-079_GEN
Solar/Wind Harmer
0.344
970611AG2-400 GEN
Solar/Wind Harmer
5.623
270526AF1-158 GEN
Solar/Wind Harmer
2.491
971231AH1-075 GEN
Solar/Wind Harmer
0.437
24441505OLIV SLR
Solar/Wind Harmer
0.073
965681AG1-436 GEN
Solar/Wind Harmer
6.563
965791AG1-447 GEN
Solar/Wind Harmer
3.358
270224U2-072_GEN2
Solar/Wind Harmer
1.038
270227U2-072_GEN3
Solar/Wind Harmer
1.038
270228U2-072_GEN4
Solar/Wind Harmer
1.038
270231U2-072_GEN5
Solar/Wind Harmer
1.038
274808UNIV PK N;4U
Adder
2.408
274803UNIV PARK;6U
Adder
2.785
942221AE2-234 GEN
Solar/Wind Harmer
0.349
274888KELLY CRK;1U
Solar/Wind Harmer
2.807
274887GEN-1.85
Solar/Wind Harmer
2.534
276843GEN-1.7
Solar/Wind Harmer
0.273
958011AF2-095 GEN
Solar/Wind Harmer
6.846
274770LINCOLN ;1U
Adder
2.947
274771LINCOLN ;2U
Adder
2.947
972259AH1-714 GEN
Adder
9.004
274674JOLIET 9 ;6U
Adder
7.247
970321AG2-212 GEN
Solar/Wind Harmer
8.386
274847GR RIDGE ;BU
Solar/Wind Harmer
2.368
274696ROCKY RD ;4P
Adder
5.267
274695ROCKY RD ;2P
Adder
5.146
274693ROCKY RD ;1P
Adder
5.095
274697ROCKY RD ;3P
Adder
1.398
274683WAUKEGAN ;8U
Adder
9.733
274683WAUKEGAN ;8U
Adder
8.205
274764LEE CO EC;5U
Adder
4.169
274777LINCOLN ;8U
Adder
2.947
972227AH1-698 GEN1
Adder
1.236
274687WILL CNTY;4U
Adder
13.203
274687WILL CNTY;4U
Adder
13.203
270024AE2-089 GEN
Solar/Wind Harmer
2.215
274675JOLIET 29;7U
Adder
14.468
274675JOLIET 29;7U
Adder
13.951
274731ELWOOD EC;2P
Adder
7.738
274733ELWOOD EC;3P
Adder
7.738
274735ELWOOD EC;4P
Adder
7.738
274728ELWOOD EC;5P
Adder
7.738
970833AG2-524 GEN
Solar/Wind Harmer
4.089
970833AG2-524 GEN
Solar/Wind Harmer
1.902
274746AC1-111 G10
Adder
2.602
274744AC1-111 GEN8
Adder
2.602
24729505KEY G4
Adder
2.98
274823ROCKFORD ;21
Adder
8.814
241982AE2-343 S C
Solar/Wind Helper
0.127
254304AE2-114 C
Solar/Wind Helper
0.121
203846AF2-130 C
Solar/Wind Helper
0.268
241997AF1-093 GEN
Solar/Wind Helper
0.141
203804AE2-113_GEN
Solar/Wind Helper
0.937
203855AF2-088 C
Solar/Wind Helper
0.073
270391AF1-285 GEN3
Solar/Wind Harmer
0.635
970373AG2-245 GEN
Solar/Wind Harmer
10.614
270055AF2-134 C O1
Solar/Wind Harmer
1.502
241847AF2-150_GEN
Solar/Wind Harmer
2.052
274751CRETE EC ;1U
Adder
2.389
274754CRETE EC ;4U
Adder
2.389
958381AF2-132 GEN
Solar/Wind Harmer
4.421
964861AG1-349 GEN
Solar/Wind Harmer
3.823
971917AH1-482 GEN
Solar/Wind Harmer
4.412
274723RIVER EC ;12
Adder
8.693
274812UNIV PK N;8U
Adder
2.419
276164X3-005 C
Solar/Wind Harmer
0.338
274801UNIV PARK;4U
Adder
2.776
940581AE2-045 GEN
Solar/Wind Harmer
4.851
971605AH1-302 GEN
Solar/Wind Harmer
4.148
276776AD2-060 GEN
Solar/Wind Harmer
0.201
972207SS24-0001
Solar/Wind Harmer
10.477
274773LINCOLN ;4U
Adder
2.947
274774LINCOLN ;5U
Adder
2.947
274676JOLIET 29;8U
Adder
14.467
941551AE2-152 GEN
Solar/Wind Harmer
2.137
274732ELWOOD EC;7P
Adder
7.738
274674JOLIET 9 ;6U
Adder
7.247
970245AG2-165 GEN
Solar/Wind Harmer
8.386
274871GR RIDGE ;2U
Solar/Wind Harmer
3.6
274745AC1-111 GEN9
Adder
2.602
274682WAUKEGAN ;7U
Adder
8.309
274828WAUKEGAN ;BP
Adder
5.102
274822ROCKFORD ;11
Adder
8.879
972235AH1-702 GEN1
Adder
1.138
274761LEE CO EC;2U
Adder
4.16
274766LEE CO EC;7U
Adder
4.111
961971AG1-040 GEN
Solar/Wind Helper
0.363
203835AF1-098 GEN
Solar/Wind Helper
1.429
203860AG1-193 C
Solar/Wind Helper
0.162
241966AE1-183 GEN
Solar/Wind Helper
0.141
254303AC2-168 GEN
Solar/Wind Helper
0.082
203954AE2-126 C
Solar/Wind Helper
0.236
274765LEE CO EC;6U
Adder
4.169
274762LEE CO EC;3U
Adder
4.16
274763LEE CO EC;4U
Adder
4.12
972267AH1-718 GEN
Adder
1.849
25326509SID D
Adder
0.581
247621Y3-024
Adder
0.105
203947AF1-006 C
Solar/Wind Helper
0.413
203980AG1-197 GEN
Solar/Wind Helper
0.27
203979AG1-198 GEN
Solar/Wind Helper
0.21
241967AE2-285_GEN
Solar/Wind Helper
0.366
241801AE1-079 GEN
Solar/Wind Helper
0.143
241985AE1-237 GEN
Solar/Wind Helper
0.142
962101AG1-054 GEN
Solar/Wind Helper
0.354
946381AF1-302 GEN
Solar/Wind Helper
0.114
238217AF1-153 C O1
Solar/Wind Helper
0.12
20398826ARMNA MT
Solar/Wind Helper
0.713
203853AF1-134 C O1
Solar/Wind Helper
0.223
23929302BS-PKR
50/50
2.537
241832AE2-181_GEN
Solar/Wind Harmer
2.114
958321AF2-126 GEN
Solar/Wind Harmer
1.643
23906502RICHG2&3
Adder
1.43
270575GUS2 35KV
Solar/Wind Harmer
11.637
270541AE2-072 C
Solar/Wind Harmer
4.757
970217AG2-149 GEN
Solar/Wind Harmer
24.543
270044AE2-322 C
Solar/Wind Harmer
0.925
270404AC1-167 GEN
Solar/Wind Harmer
0.77
270588AE1-091_GEN
Solar/Wind Harmer
7.618
270258AD1-119 GEN
Solar/Wind Harmer
1.882
247604X1-042
Adder
0.268
958091AF2-103 GEN
Solar/Wind Harmer
0.103
24441205WTRV SLR C
Solar/Wind Harmer
0.085
270491AE1-102 GEN2
Solar/Wind Harmer
0.815
945111AF1-176 GEN
Solar/Wind Harmer
3.334
270191TR4_S_V150
Solar/Wind Harmer
1.759
270247TR4_N_V136
Solar/Wind Harmer
0.499
24642205MAYFLWER
Adder
0.364
970031AG2-029 GEN
Solar/Wind Harmer
17.123
247643Z2-116 C
Solar/Wind Harmer
0.04
270485AE1-090_GEN
Solar/Wind Harmer
0.342
959331AF2-224 GEN
Solar/Wind Harmer
5.623
965021AG1-366 GEN
Solar/Wind Harmer
1.308
270377AD1-106 GEN
Solar/Wind Harmer
3.371
270043AE2-236 GEN
Solar/Wind Harmer
2.911
942871AE2-306 GEN
Solar/Wind Harmer
0.476
270391AF1-285 GEN3
Solar/Wind Harmer
0.244
970349AG2-230 GEN
Solar/Wind Harmer
7.843
270535AF1-215 GEN1
Solar/Wind Harmer
2.253
961961AG1-039 GEN
Solar/Wind Harmer
1.415
972231SS25-0005
Solar/Wind Harmer
4.639
972181SS23-001
Solar/Wind Harmer
2.9
274752CRETE EC ;2U
Adder
2.389
274753CRETE EC ;3U
Adder
2.389
964401AG1-302 GEN
Solar/Wind Harmer
4.421
274724RIVER EC ;11
Adder
8.59
959141AF2-205 GEN
Solar/Wind Harmer
2.9
274802UNIV PARK;5U
Adder
2.785
274826FISK ;BP
Adder
5.221
274800UNIV PARK;3U
Adder
2.776
972038AH1-567 GEN2
Adder
0.174
276772AC2-154 GEN
Solar/Wind Harmer
1.326
276806AD2-047 C O1
Solar/Wind Harmer
5.086
970941AG2-585 GEN
Solar/Wind Harmer
5.943
274772LINCOLN ;3U
Adder
2.947
972228AH1-698 GEN2
Adder
1.756
971617AH1-308 GEN
Solar/Wind Harmer
2.744
274676JOLIET 29;8U
Adder
13.951
276897AD1-100 C
Solar/Wind Harmer
13.671
939351AE1-166 GEN
Solar/Wind Harmer
2.793
276893AG1-478 C
Solar/Wind Harmer
0.197
970707AG2-453 GEN
Solar/Wind Harmer
13.179
274729ELWOOD EC;1P
Adder
7.738
274730ELWOOD EC;6P
Adder
7.738
274734ELWOOD EC;8P
Adder
7.738
274736ELWOOD EC;9P
Adder
7.738
970513AG2-328 GEN
Solar/Wind Harmer
8.386
970517AG2-330 GEN
Solar/Wind Harmer
7.606
274682WAUKEGAN ;7U
Adder
8.309
972236AH1-702 GEN2
Adder
0.99
274760LEE CO EC;1U
Adder
4.16
274767LEE CO EC;8U
Adder
4.111
962511AG1-100 GEN
Solar/Wind Helper
0.371
203830AF1-094 GEN
Solar/Wind Helper
0.351
959441AF2-235 GEN
Solar/Wind Helper
0.159
254305AE2-115 C
Solar/Wind Helper
0.121
20334926Z1-069 C
Solar/Wind Helper
0.698
203854AF2-039 C
Solar/Wind Helper
0.151
203818AF1-086 GEN
Solar/Wind Helper
0.773
943121AE2-341 GEN
Solar/Wind Harmer
2.169
943591AF1-030 GEN
Solar/Wind Harmer
1.446
991177J1571 G
External Queue
15.754436492919922
990527J1329
External Queue
1.8554641008377075
990142J1224
External Queue
13.56344223022461
991182J1586 G
External Queue
25.351587295532227
LAGNLTFEXP_LAGN->PJM
CLTF
5.168
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.294
TVALTFEXP_TVA->PJM
CLTF
2.348
CPLELTFEXP_CPLE->PJM
CLTF
0.34
CBM West 2LTFEXP_CBM-W2->PJM
CBM
41.311
NYPJM->LTFIMP_NY
CLTF
2.183
LGEELTFEXP_LGEE->PJM
CLTF
2.114
WECLTFEXP_WEC->PJM
CLTF
1.725
AG2-052LTFEXP_AG2-052->PJM
LTF
0.111
AH1-155LTFEXP_AH1-155->PJM
LTF
0.167
CBM West 1LTFEXP_CBM-W1->PJM
CBM
96.822
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.312
MECLTFEXP_MEC->PJM
CLTF
6.73
SIGELTFEXP_SIGE->PJM
CLTF
0.176

Details for 02HAYES-02BEAVER 345.0 kV Ckt 1 line l/o ATSI_P2-3_TE-345-010A_SRT-SL


Base Case Flowgate

Area:ATSI
Facility Description:
02HAYES-02BEAVER 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_TE-345-010A_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:142.21 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:2670.76
MW Contribution:13.52
Bus #Bus NameTypeMW Contribution
24189902OREGON_CT2
50/50
2.68
23856402BAYSG1
50/50
1.434
23888702TROY G3
50/50
1.837
972253AH1-711 GEN
50/50
56.101
23860302FRMENG 3
50/50
3.54
23920202STRYCT
50/50
2.052
241807AE2-176_GEN
Solar/Wind Harmer
7.294
241858AF1-205_GEN
Solar/Wind Harmer
5.929
241808AF1-120 C
Solar/Wind Harmer
1.295
241840AF1-064_GEN
Solar/Wind Harmer
1.525
972301AH1-735 GEN
Adder
7.125
23906402RICHG1
Adder
1.425
23906502RICHG2&3
Adder
1.423
270361_3
Solar/Wind Harmer
9.783
960841AF2-375 GEN
Solar/Wind Harmer
4.309
247522W1-056 GEN
Solar/Wind Harmer
1.78
270428AC2-015 C
Solar/Wind Harmer
4.168
970515AG2-329 GEN
Solar/Wind Harmer
10.964
944231AF1-091 GEN
Solar/Wind Harmer
2.634
246936BC-WTG1
Solar/Wind Harmer
2.439
270489AE1-102 GEN1
Solar/Wind Harmer
0.81
965421AG1-410 GEN
Solar/Wind Harmer
18.512
24695305TIMB G C
Solar/Wind Harmer
3.326
270449AD2-020 GEN
Solar/Wind Harmer
1.68
943021AE2-325 GEN
Solar/Wind Harmer
2.182
970905AG2-564 GEN
Solar/Wind Harmer
2.966
945111AF1-176 GEN
Solar/Wind Harmer
10.472
270505AE1-170 C O1
Solar/Wind Harmer
8.793
247521TR3_G114
Solar/Wind Harmer
1.96
270246TR4_N_V150
Solar/Wind Harmer
0.496
24639705ELKHART HY
Adder
0.088
270063AE2-323 C
Solar/Wind Harmer
1.255
270462AD2-086
Solar/Wind Harmer
3.91
965011AG1-365 GEN
Solar/Wind Harmer
5.591
270223U2-072_GEN1
Solar/Wind Harmer
1.03
270578AF1-285 GEN2
Solar/Wind Harmer
0.63
270391AF1-285 GEN3
Solar/Wind Harmer
0.63
970373AG2-245 GEN
Solar/Wind Harmer
10.561
270055AF2-134 C O1
Solar/Wind Harmer
1.494
274751CRETE EC ;1U
Adder
2.377
274754CRETE EC ;4U
Adder
2.377
958381AF2-132 GEN
Solar/Wind Harmer
4.398
964861AG1-349 GEN
Solar/Wind Harmer
3.804
971917AH1-482 GEN
Solar/Wind Harmer
4.39
274723RIVER EC ;12
Adder
8.649
274812UNIV PK N;8U
Adder
2.406
276164X3-005 C
Solar/Wind Harmer
0.336
241847AF2-150_GEN
Solar/Wind Harmer
1.974
274801UNIV PARK;4U
Adder
2.762
940581AE2-045 GEN
Solar/Wind Harmer
4.826
971605AH1-302 GEN
Solar/Wind Harmer
4.126
276776AD2-060 GEN
Solar/Wind Harmer
0.2
972207SS24-0001
Solar/Wind Harmer
10.423
274773LINCOLN ;4U
Adder
2.932
274774LINCOLN ;5U
Adder
2.932
274676JOLIET 29;8U
Adder
14.394
941551AE2-152 GEN
Solar/Wind Harmer
2.126
274732ELWOOD EC;7P
Adder
7.698
274674JOLIET 9 ;6U
Adder
7.21
970245AG2-165 GEN
Solar/Wind Harmer
8.342
274871GR RIDGE ;2U
Solar/Wind Harmer
3.581
274745AC1-111 GEN9
Adder
2.589
274682WAUKEGAN ;7U
Adder
8.266
274828WAUKEGAN ;BP
Adder
5.076
274822ROCKFORD ;11
Adder
8.833
972235AH1-702 GEN1
Adder
1.133
274761LEE CO EC;2U
Adder
4.138
274766LEE CO EC;7U
Adder
4.089
241885AC2-103 GEN1
Solar/Wind Helper
4.614
961971AG1-040 GEN
Solar/Wind Helper
0.358
203835AF1-098 GEN
Solar/Wind Helper
1.412
203860AG1-193 C
Solar/Wind Helper
0.16
241966AE1-183 GEN
Solar/Wind Helper
0.139
254303AC2-168 GEN
Solar/Wind Helper
0.081
203954AE2-126 C
Solar/Wind Helper
0.233
24190002OREGON_ST1
50/50
3.605
24189802OREGON_CT1
50/50
2.735
23888802TROY G4
50/50
1.837
241996AE2-282_GEN
Solar/Wind Harmer
2.323
971677AH1-339 GEN
Solar/Wind Harmer
7.59
270007AE1-245 C
Solar/Wind Harmer
3.751
942801AE2-298 GEN
Solar/Wind Harmer
0.95
246938BC-WTG3
Solar/Wind Harmer
2.481
246937BC-WTG2
Solar/Wind Harmer
2.439
961051AF2-396 GEN
Solar/Wind Harmer
9.439
961051AF2-396 GEN
Solar/Wind Harmer
4.39
960981AF2-389 GEN
Solar/Wind Harmer
0.884
957891AF2-083 GEN
Solar/Wind Harmer
1.971
247620Y3-023
Adder
0.264
270216AD2-079_GEN
Solar/Wind Harmer
0.343
970611AG2-400 GEN
Solar/Wind Harmer
5.591
270526AF1-158 GEN
Solar/Wind Harmer
2.479
24441505OLIV SLR
Solar/Wind Harmer
0.073
971231AH1-075 GEN
Solar/Wind Harmer
0.429
965681AG1-436 GEN
Solar/Wind Harmer
6.531
965791AG1-447 GEN
Solar/Wind Harmer
3.341
270224U2-072_GEN2
Solar/Wind Harmer
1.03
270227U2-072_GEN3
Solar/Wind Harmer
1.03
270228U2-072_GEN4
Solar/Wind Harmer
1.03
270231U2-072_GEN5
Solar/Wind Harmer
1.03
274808UNIV PK N;4U
Adder
2.396
274803UNIV PARK;6U
Adder
2.771
942221AE2-234 GEN
Solar/Wind Harmer
0.347
274888KELLY CRK;1U
Solar/Wind Harmer
2.793
274887GEN-1.85
Solar/Wind Harmer
2.521
276843GEN-1.7
Solar/Wind Harmer
0.271
958011AF2-095 GEN
Solar/Wind Harmer
6.812
274770LINCOLN ;1U
Adder
2.932
274771LINCOLN ;2U
Adder
2.932
972259AH1-714 GEN
Adder
8.958
274674JOLIET 9 ;6U
Adder
7.21
970321AG2-212 GEN
Solar/Wind Harmer
8.342
274847GR RIDGE ;BU
Solar/Wind Harmer
2.356
274696ROCKY RD ;4P
Adder
5.24
274695ROCKY RD ;2P
Adder
5.12
274693ROCKY RD ;1P
Adder
5.069
274697ROCKY RD ;3P
Adder
1.391
274683WAUKEGAN ;8U
Adder
9.683
274683WAUKEGAN ;8U
Adder
8.163
274764LEE CO EC;5U
Adder
4.148
274765LEE CO EC;6U
Adder
4.148
274762LEE CO EC;3U
Adder
4.138
274763LEE CO EC;4U
Adder
4.099
972267AH1-718 GEN
Adder
1.84
25326509SID D
Adder
0.576
247621Y3-024
Adder
0.105
203947AF1-006 C
Solar/Wind Helper
0.408
203980AG1-197 GEN
Solar/Wind Helper
0.267
203979AG1-198 GEN
Solar/Wind Helper
0.208
241967AE2-285_GEN
Solar/Wind Helper
0.362
241801AE1-079 GEN
Solar/Wind Helper
0.141
241985AE1-237 GEN
Solar/Wind Helper
0.14
962101AG1-054 GEN
Solar/Wind Helper
0.35
946381AF1-302 GEN
Solar/Wind Helper
0.112
238217AF1-153 C O1
Solar/Wind Helper
0.119
20398826ARMNA MT
Solar/Wind Helper
0.704
23867002DVBSG1
50/50
12.828
972211AH1-690 GEN
50/50
288.97
23888502TROY G1
50/50
1.837
23888602TROY G2
50/50
1.837
23860102FRMENG 1
50/50
1.734
23860202FRMENG 2
50/50
1.734
24191202EL_AA1-006
50/50
0.334
970817AG2-515 GEN
Solar/Wind Harmer
15.756
945411AF1-206 GEN
Solar/Wind Harmer
8.678
270499AE1-146 GEN
Solar/Wind Harmer
2.698
945641AF1-229 GEN
Solar/Wind Harmer
3.679
270297AD1-101 GEN
Solar/Wind Harmer
2.073
971549AH1-272 GEN
Solar/Wind Harmer
13.52
966831AG1-554 GEN
Solar/Wind Harmer
0.792
971989AH1-539 GEN
Solar/Wind Harmer
8.566
247607V1-011 GEN
Solar/Wind Harmer
2.5
957201AF2-014 GEN
Solar/Wind Harmer
2.826
270435AC2-044 GEN
Solar/Wind Harmer
1.246
944161AF1-084 GEN
Solar/Wind Harmer
1.342
965041AG1-368 GEN
Solar/Wind Harmer
5.854
965051AG1-369 GEN
Solar/Wind Harmer
2.91
270302AB2-170 GEN
Solar/Wind Harmer
4.7
270317AD1-130_GEN
Solar/Wind Harmer
1.802
971771AH1-392 GEN
Solar/Wind Harmer
5.011
971567AH1-282 GEN
Solar/Wind Harmer
8.27
971769AH1-391 GEN
Solar/Wind Harmer
5.428
960681AF2-359 GEN
Solar/Wind Harmer
1.974
270578AF1-285 GEN2
Solar/Wind Harmer
0.242
971347AH1-153 GEN
Solar/Wind Harmer
7.804
963791AG1-232 GEN
Solar/Wind Harmer
7
270536AF1-215 GEN2
Solar/Wind Harmer
2.241
270071AF1-092 GEN
Solar/Wind Harmer
7.347
958391AF2-133 GEN
Solar/Wind Harmer
4.359
274814UNIV PK N;0U
Adder
2.427
274807UNIV PK N;3U
Adder
2.422
274805UNIV PK N;1U
Adder
2.412
274811UNIV PK N;7U
Adder
2.406
972037AH1-567 GEN1
Adder
0.087
274827FISK ;RP
Adder
3.681
960591AF2-350 GEN
Solar/Wind Harmer
4.73
274775LINCOLN ;6U
Adder
2.932
274776LINCOLN ;7U
Adder
2.932
274777LINCOLN ;8U
Adder
2.932
972227AH1-698 GEN1
Adder
1.23
274687WILL CNTY;4U
Adder
13.136
274687WILL CNTY;4U
Adder
13.136
270024AE2-089 GEN
Solar/Wind Harmer
2.202
274675JOLIET 29;7U
Adder
14.394
274675JOLIET 29;7U
Adder
13.88
274731ELWOOD EC;2P
Adder
7.698
274733ELWOOD EC;3P
Adder
7.698
274735ELWOOD EC;4P
Adder
7.698
274728ELWOOD EC;5P
Adder
7.698
970833AG2-524 GEN
Solar/Wind Harmer
4.069
970833AG2-524 GEN
Solar/Wind Harmer
1.892
274746AC1-111 G10
Adder
2.589
274744AC1-111 GEN8
Adder
2.589
24729505KEY G4
Adder
2.963
274823ROCKFORD ;21
Adder
8.769
241886AC2-103 GEN2
Solar/Wind Helper
4.614
241982AE2-343 S C
Solar/Wind Helper
0.126
254304AE2-114 C
Solar/Wind Helper
0.12
203846AF2-130 C
Solar/Wind Helper
0.265
241997AF1-093 GEN
Solar/Wind Helper
0.139
203804AE2-113_GEN
Solar/Wind Helper
0.926
203855AF2-088 C
Solar/Wind Helper
0.072
23929302BS-PKR
50/50
2.524
241832AE2-181_GEN
Solar/Wind Harmer
2.105
958321AF2-126 GEN
Solar/Wind Harmer
1.635
23906502RICHG2&3
Adder
1.423
270575GUS2 35KV
Solar/Wind Harmer
11.525
270541AE2-072 C
Solar/Wind Harmer
4.728
970217AG2-149 GEN
Solar/Wind Harmer
24.176
270044AE2-322 C
Solar/Wind Harmer
0.919
270404AC1-167 GEN
Solar/Wind Harmer
0.766
270588AE1-091_GEN
Solar/Wind Harmer
7.54
270258AD1-119 GEN
Solar/Wind Harmer
1.871
247604X1-042
Adder
0.267
958091AF2-103 GEN
Solar/Wind Harmer
0.102
24441205WTRV SLR C
Solar/Wind Harmer
0.084
270491AE1-102 GEN2
Solar/Wind Harmer
0.81
945111AF1-176 GEN
Solar/Wind Harmer
3.319
270191TR4_S_V150
Solar/Wind Harmer
1.748
270247TR4_N_V136
Solar/Wind Harmer
0.496
24642205MAYFLWER
Adder
0.363
970031AG2-029 GEN
Solar/Wind Harmer
17.036
247643Z2-116 C
Solar/Wind Harmer
0.039
270485AE1-090_GEN
Solar/Wind Harmer
0.34
959331AF2-224 GEN
Solar/Wind Harmer
5.591
965021AG1-366 GEN
Solar/Wind Harmer
1.3
270377AD1-106 GEN
Solar/Wind Harmer
3.313
270043AE2-236 GEN
Solar/Wind Harmer
2.896
942871AE2-306 GEN
Solar/Wind Harmer
0.472
270391AF1-285 GEN3
Solar/Wind Harmer
0.242
970349AG2-230 GEN
Solar/Wind Harmer
7.804
270535AF1-215 GEN1
Solar/Wind Harmer
2.241
972231SS25-0005
Solar/Wind Harmer
4.616
972181SS23-001
Solar/Wind Harmer
2.885
274752CRETE EC ;2U
Adder
2.377
274753CRETE EC ;3U
Adder
2.377
964401AG1-302 GEN
Solar/Wind Harmer
4.398
274724RIVER EC ;11
Adder
8.546
959141AF2-205 GEN
Solar/Wind Harmer
2.885
274802UNIV PARK;5U
Adder
2.771
961961AG1-039 GEN
Solar/Wind Harmer
1.361
274826FISK ;BP
Adder
5.194
274800UNIV PARK;3U
Adder
2.762
972038AH1-567 GEN2
Adder
0.173
276772AC2-154 GEN
Solar/Wind Harmer
1.319
276806AD2-047 C O1
Solar/Wind Harmer
5.06
970941AG2-585 GEN
Solar/Wind Harmer
5.913
274772LINCOLN ;3U
Adder
2.932
972228AH1-698 GEN2
Adder
1.747
274676JOLIET 29;8U
Adder
13.879
971617AH1-308 GEN
Solar/Wind Harmer
2.727
276897AD1-100 C
Solar/Wind Harmer
13.601
939351AE1-166 GEN
Solar/Wind Harmer
2.779
276893AG1-478 C
Solar/Wind Harmer
0.196
970707AG2-453 GEN
Solar/Wind Harmer
13.112
274729ELWOOD EC;1P
Adder
7.698
274730ELWOOD EC;6P
Adder
7.698
274734ELWOOD EC;8P
Adder
7.698
274736ELWOOD EC;9P
Adder
7.698
970513AG2-328 GEN
Solar/Wind Harmer
8.342
970517AG2-330 GEN
Solar/Wind Harmer
7.566
274682WAUKEGAN ;7U
Adder
8.266
972236AH1-702 GEN2
Adder
0.985
274760LEE CO EC;1U
Adder
4.138
274767LEE CO EC;8U
Adder
4.089
962511AG1-100 GEN
Solar/Wind Helper
0.366
203830AF1-094 GEN
Solar/Wind Helper
0.347
959441AF2-235 GEN
Solar/Wind Helper
0.157
254305AE2-115 C
Solar/Wind Helper
0.12
20334926Z1-069 C
Solar/Wind Helper
0.689
203854AF2-039 C
Solar/Wind Helper
0.149
943121AE2-341 GEN
Solar/Wind Harmer
5.427
943591AF1-030 GEN
Solar/Wind Harmer
3.618
991177J1571 G
External Queue
15.714932441711426
990527J1329
External Queue
1.8513455390930176
990142J1224
External Queue
13.53333568572998
991182J1586 G
External Queue
25.292837142944336
LAGNLTFEXP_LAGN->PJM
CLTF
5.142
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.292
TVALTFEXP_TVA->PJM
CLTF
2.336
CPLELTFEXP_CPLE->PJM
CLTF
0.344
CBM West 2LTFEXP_CBM-W2->PJM
CBM
41.091
NYPJM->LTFIMP_NY
CLTF
2.158
LGEELTFEXP_LGEE->PJM
CLTF
2.101
WECLTFEXP_WEC->PJM
CLTF
1.716
AG2-052LTFEXP_AG2-052->PJM
LTF
0.11
AH1-155LTFEXP_AH1-155->PJM
LTF
0.166
CBM West 1LTFEXP_CBM-W1->PJM
CBM
96.429
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.261
MECLTFEXP_MEC->PJM
CLTF
6.695
SIGELTFEXP_SIGE->PJM
CLTF
0.175

Details for 02HAYES-02BEAVER 345.0 kV Ckt 1 line l/o ATSI_P1-2_OEC-345-825_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02HAYES-02BEAVER 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_OEC-345-825_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:136.05 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:2554.95
MW Contribution:10.52
Bus #Bus NameTypeMW Contribution
24189902OREGON_CT2
50/50
2.678
23856402BAYSG1
50/50
1.433
23888702TROY G3
50/50
1.836
972253AH1-711 GEN
50/50
56.068
23860302FRMENG 3
50/50
3.538
23920202STRYCT
50/50
2.05
241885AC2-103 GEN1
Solar/Wind Harmer
-0.001
241807AE2-176_GEN
Solar/Wind Harmer
0.009
241858AF1-205_GEN
Solar/Wind Harmer
4.134
241808AF1-120 C
Solar/Wind Harmer
0.003
241840AF1-064_GEN
Solar/Wind Harmer
0.004
972301AH1-735 GEN
Adder
7.119
23906402RICHG1
Adder
1.424
23906502RICHG2&3
Adder
1.422
270361_3
Solar/Wind Harmer
5.343
960841AF2-375 GEN
Solar/Wind Harmer
-0.002
247522W1-056 GEN
Solar/Wind Harmer
0.001
270428AC2-015 C
Solar/Wind Harmer
0.003
970515AG2-329 GEN
Solar/Wind Harmer
13.687
944231AF1-091 GEN
Solar/Wind Harmer
1.299
246936BC-WTG1
Solar/Wind Harmer
0.176
270489AE1-102 GEN1
Solar/Wind Harmer
0.564
965421AG1-410 GEN
Solar/Wind Harmer
12.895
24695305TIMB G C
Solar/Wind Harmer
0.001
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.179
970905AG2-564 GEN
Solar/Wind Harmer
2.266
945111AF1-176 GEN
Solar/Wind Harmer
7.294
270505AE1-170 C O1
Solar/Wind Harmer
4.287
247521TR3_G114
Solar/Wind Harmer
0.148
270246TR4_N_V150
Solar/Wind Harmer
0.026
24639705ELKHART HY
Adder
0.087
270063AE2-323 C
Solar/Wind Harmer
0.003
270462AD2-086
Solar/Wind Harmer
0.008
965011AG1-365 GEN
Solar/Wind Harmer
3.894
270223U2-072_GEN1
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
7.354
270055AF2-134 C O1
Solar/Wind Harmer
0.003
274751CRETE EC ;1U
Adder
4
274754CRETE EC ;4U
Adder
4
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.381
274723RIVER EC ;12
Adder
8.632
274812UNIV PK N;8U
Adder
2.401
276164X3-005 C
Solar/Wind Harmer
0
274801UNIV PARK;4U
Adder
2.756
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
4.118
276776AD2-060 GEN
Solar/Wind Harmer
0.344
274773LINCOLN ;4U
Adder
3.982
274774LINCOLN ;5U
Adder
3.982
274676JOLIET 29;8U
Adder
14.364
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
7.682
274674JOLIET 9 ;6U
Adder
7.195
970245AG2-165 GEN
Solar/Wind Harmer
1.409
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
2.583
276691AA1-018 GEN1
Solar/Wind Harmer
0.39
274682WAUKEGAN ;7U
Adder
8.249
274828WAUKEGAN ;BP
Adder
5.065
276901AD2-066 C O1
Solar/Wind Harmer
0.003
939401AE1-172 GEN
Solar/Wind Harmer
2.382
962781AG1-127 GEN
Solar/Wind Harmer
3.024
24791305MDL-5G
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0.002
971997AH1-543 GEN
Solar/Wind Harmer
1.662
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
276861AD2-134 GEN
Solar/Wind Harmer
0.057
957471AF2-041 GEN
Solar/Wind Harmer
9.419
959081AF2-199 GEN
Solar/Wind Harmer
3.14
971067AG2-660 GEN
Solar/Wind Harmer
1.047
274822ROCKFORD ;11
Adder
8.814
970569AG2-363 GEN
Solar/Wind Harmer
9.385
972235AH1-702 GEN1
Adder
1.13
970819AG2-516 GEN
Solar/Wind Harmer
3.745
971475AH1-234 GEN
Solar/Wind Harmer
1.512
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
4.129
274766LEE CO EC;7U
Adder
0.439
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.001
965651AG1-433 GEN
Solar/Wind Harmer
0.908
276158O29GEN2
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
1.328
274877BISHOP HL;1U
Solar/Wind Harmer
0.103
276726Z2-087_GEN
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
4.276
274854TWINGROVE;U2
Solar/Wind Harmer
0.001
945371AF1-202 GEN
Solar/Wind Harmer
0
961971AG1-040 GEN
Solar/Wind Helper
0.359
203835AF1-098 GEN
Solar/Wind Helper
1.414
203860AG1-193 C
Solar/Wind Helper
0.16
241966AE1-183 GEN
Solar/Wind Helper
0.139
254303AC2-168 GEN
Solar/Wind Helper
0.081
203954AE2-126 C
Solar/Wind Helper
0.234
23867002DVBSG1
50/50
12.822
972211AH1-690 GEN
50/50
288.807
23888502TROY G1
50/50
1.836
23888602TROY G2
50/50
1.836
23860102FRMENG 1
50/50
1.733
23860202FRMENG 2
50/50
1.733
24191202EL_AA1-006
50/50
0.334
241886AC2-103 GEN2
Solar/Wind Harmer
-0.001
970817AG2-515 GEN
Solar/Wind Harmer
10.986
945411AF1-206 GEN
Solar/Wind Harmer
-0.001
270499AE1-146 GEN
Solar/Wind Harmer
0.033
945641AF1-229 GEN
Solar/Wind Harmer
0.001
270297AD1-101 GEN
Solar/Wind Harmer
0.001
971549AH1-272 GEN
Solar/Wind Harmer
10.515
971989AH1-539 GEN
Solar/Wind Harmer
1.989
247607V1-011 GEN
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.55
971619AH1-309 GEN
Solar/Wind Harmer
1.837
965041AG1-368 GEN
Solar/Wind Harmer
4.077
965051AG1-369 GEN
Solar/Wind Harmer
2.027
270302AB2-170 GEN
Solar/Wind Harmer
0.002
270317AD1-130_GEN
Solar/Wind Harmer
0.006
971653AH1-327 GEN
Solar/Wind Harmer
0.55
971771AH1-392 GEN
Solar/Wind Harmer
3.877
971567AH1-282 GEN
Solar/Wind Harmer
5.76
971769AH1-391 GEN
Solar/Wind Harmer
4.221
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
270578AF1-285 GEN2
Solar/Wind Harmer
0.242
971347AH1-153 GEN
Solar/Wind Harmer
5.434
963791AG1-232 GEN
Solar/Wind Harmer
4.874
270536AF1-215 GEN2
Solar/Wind Harmer
0.004
270071AF1-092 GEN
Solar/Wind Harmer
6.537
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274814UNIV PK N;0U
Adder
2.422
274807UNIV PK N;3U
Adder
2.417
274805UNIV PK N;1U
Adder
2.407
274811UNIV PK N;7U
Adder
2.401
972037AH1-567 GEN1
Adder
0.087
274827FISK ;RP
Adder
3.674
971611AH1-305 GEN
Solar/Wind Harmer
1.961
960591AF2-350 GEN
Solar/Wind Harmer
3.293
274775LINCOLN ;6U
Adder
3.982
274776LINCOLN ;7U
Adder
3.982
274777LINCOLN ;8U
Adder
3.982
972227AH1-698 GEN1
Adder
1.228
274687WILL CNTY;4U
Adder
13.109
274687WILL CNTY;4U
Adder
13.109
270024AE2-089 GEN
Solar/Wind Harmer
0.004
274675JOLIET 29;7U
Adder
14.364
274675JOLIET 29;7U
Adder
13.851
274731ELWOOD EC;2P
Adder
7.682
274733ELWOOD EC;3P
Adder
7.682
274735ELWOOD EC;4P
Adder
7.682
274728ELWOOD EC;5P
Adder
7.682
970833AG2-524 GEN
Solar/Wind Harmer
3.569
970833AG2-524 GEN
Solar/Wind Harmer
2.379
274746AC1-111 G10
Adder
2.583
274744AC1-111 GEN8
Adder
2.583
24729505KEY G4
Adder
2.957
276868AE1-113 GEN
Solar/Wind Harmer
0.638
276882AE2-255 GEN
Solar/Wind Harmer
0.372
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0
270181AB1-006 GEN2
Solar/Wind Harmer
0
971177AH1-047 GEN
Solar/Wind Harmer
1.951
971411AH1-196 GEN
Solar/Wind Harmer
4.733
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
1.229
971171AH1-044 GEN
Solar/Wind Harmer
6.279
274823ROCKFORD ;21
Adder
8.75
970169AG2-114 GEN
Solar/Wind Harmer
3.123
926823AC1-168 GEN
Solar/Wind Harmer
0.531
276612AE2-035 GEN
Solar/Wind Harmer
0.001
971681AH1-341 GEN
Solar/Wind Harmer
5
24386205FR-12G C
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
24387005FR-3G C
Solar/Wind Harmer
0.001
961011AF2-392 GEN
Solar/Wind Harmer
1.808
957751AF2-069 GEN
Solar/Wind Harmer
0.102
965101AG1-375 GEN
Solar/Wind Harmer
3.066
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
276655WTG1_EQ
Solar/Wind Harmer
0.001
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.207
941731AE2-173 GEN
Solar/Wind Harmer
2.545
963841AG1-237 GEN
Solar/Wind Harmer
1.315
971609AH1-304 GEN
Solar/Wind Harmer
0.493
946321AF1-296 GEN
Solar/Wind Harmer
1.689
945581AF1-223 GEN
Solar/Wind Harmer
0
241982AE2-343 S C
Solar/Wind Helper
0.126
254304AE2-114 C
Solar/Wind Helper
0.12
203846AF2-130 C
Solar/Wind Helper
0.266
241997AF1-093 GEN
Solar/Wind Helper
0.139
203804AE2-113_GEN
Solar/Wind Helper
0.928
203855AF2-088 C
Solar/Wind Helper
0.072
23929302BS-PKR
50/50
2.523
241832AE2-181_GEN
Solar/Wind Harmer
0.004
958321AF2-126 GEN
Solar/Wind Harmer
1.267
23906502RICHG2&3
Adder
1.422
270575GUS2 35KV
Solar/Wind Harmer
5.343
270541AE2-072 C
Solar/Wind Harmer
0.009
970217AG2-149 GEN
Solar/Wind Harmer
4.562
270404AC1-167 GEN
Solar/Wind Harmer
0.002
270588AE1-091_GEN
Solar/Wind Harmer
3.735
270258AD1-119 GEN
Solar/Wind Harmer
0.001
247604X1-042
Adder
0.266
24441205WTRV SLR C
Solar/Wind Harmer
0
270491AE1-102 GEN2
Solar/Wind Harmer
0.564
945111AF1-176 GEN
Solar/Wind Harmer
3.313
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.026
24642205MAYFLWER
Adder
0.362
970031AG2-029 GEN
Solar/Wind Harmer
2.571
247643Z2-116 C
Solar/Wind Harmer
0
270485AE1-090_GEN
Solar/Wind Harmer
0.001
959331AF2-224 GEN
Solar/Wind Harmer
2.726
965021AG1-366 GEN
Solar/Wind Harmer
1.298
270377AD1-106 GEN
Solar/Wind Harmer
1.42
270043AE2-236 GEN
Solar/Wind Harmer
2.353
270391AF1-285 GEN3
Solar/Wind Harmer
0.242
970349AG2-230 GEN
Solar/Wind Harmer
5.434
270535AF1-215 GEN1
Solar/Wind Harmer
0.004
274752CRETE EC ;2U
Adder
4
274753CRETE EC ;3U
Adder
4
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274724RIVER EC ;11
Adder
8.529
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
274802UNIV PARK;5U
Adder
2.765
274826FISK ;BP
Adder
5.184
274800UNIV PARK;3U
Adder
2.756
972038AH1-567 GEN2
Adder
0.173
276806AD2-047 C O1
Solar/Wind Harmer
1.866
970941AG2-585 GEN
Solar/Wind Harmer
4.117
274772LINCOLN ;3U
Adder
3.982
972228AH1-698 GEN2
Adder
1.743
274676JOLIET 29;8U
Adder
13.851
971617AH1-308 GEN
Solar/Wind Harmer
2.722
276897AD1-100 C
Solar/Wind Harmer
0.004
939351AE1-166 GEN
Solar/Wind Harmer
0
276893AG1-478 C
Solar/Wind Harmer
0.129
274729ELWOOD EC;1P
Adder
7.682
274730ELWOOD EC;6P
Adder
7.682
274734ELWOOD EC;8P
Adder
7.682
274736ELWOOD EC;9P
Adder
7.682
970707AG2-453 GEN
Solar/Wind Harmer
10.65
970513AG2-328 GEN
Solar/Wind Harmer
1.409
970517AG2-330 GEN
Solar/Wind Harmer
8.456
943121AE2-341 GEN
Solar/Wind Harmer
5.404
943591AF1-030 GEN
Solar/Wind Harmer
3.594
276694AA1-018 GEN2
Solar/Wind Harmer
0
944531AF1-118 GEN
Solar/Wind Harmer
14.389
274682WAUKEGAN ;7U
Adder
8.249
276805AD2-038 GEN
Solar/Wind Harmer
0.001
24755605MDL-5G
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.176
274872LEEDK;1U
Solar/Wind Harmer
0.116
276889AE2-281 GEN
Solar/Wind Harmer
0
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.336
274855GSG-6 ;RU
Solar/Wind Harmer
0.116
274850MENDOTA H;RU
Solar/Wind Harmer
0.037
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.057
959091AF2-200 GEN
Solar/Wind Harmer
6.279
970571AG2-364 GEN
Solar/Wind Harmer
6.257
972236AH1-702 GEN2
Adder
0.983
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
4.129
276157O29GEN1
Solar/Wind Harmer
0.497
274878BISHOP HL;2U
Solar/Wind Harmer
0.103
942111AE2-223 GEN
Solar/Wind Harmer
0.993
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
4.58
274853TWINGROVE;U1
Solar/Wind Harmer
0.001
965091AG1-374 GEN
Solar/Wind Harmer
9.061
959611AF2-252 GEN
Solar/Wind Harmer
1.007
965931AG1-462 GEN
Solar/Wind Harmer
7.661
247642Z2-115 C
Solar/Wind Harmer
0.001
962511AG1-100 GEN
Solar/Wind Helper
0.367
203830AF1-094 GEN
Solar/Wind Helper
0.347
959441AF2-235 GEN
Solar/Wind Helper
0.158
254305AE2-115 C
Solar/Wind Helper
0.12
20334926Z1-069 C
Solar/Wind Helper
0.691
203854AF2-039 C
Solar/Wind Helper
0.15
24190002OREGON_ST1
50/50
3.603
24189802OREGON_CT1
50/50
2.733
23888802TROY G4
50/50
1.836
241996AE2-282_GEN
Solar/Wind Harmer
0.006
971677AH1-339 GEN
Solar/Wind Harmer
0.745
970621AG2-405 GEN
Solar/Wind Harmer
0.95
970623AG2-406 GEN
Solar/Wind Harmer
0.856
270007AE1-245 C
Solar/Wind Harmer
0.001
246938BC-WTG3
Solar/Wind Harmer
0.157
246937BC-WTG2
Solar/Wind Harmer
0.176
961051AF2-396 GEN
Solar/Wind Harmer
8.284
961051AF2-396 GEN
Solar/Wind Harmer
5.523
957891AF2-083 GEN
Solar/Wind Harmer
0.001
247620Y3-023
Adder
0.264
270216AD2-079_GEN
Solar/Wind Harmer
0.001
970611AG2-400 GEN
Solar/Wind Harmer
3.894
970627AG2-408 GEN
Solar/Wind Harmer
1.168
270526AF1-158 GEN
Solar/Wind Harmer
0.005
24441505OLIV SLR
Solar/Wind Harmer
0
971231AH1-075 GEN
Solar/Wind Harmer
0.428
965681AG1-436 GEN
Solar/Wind Harmer
4.548
965791AG1-447 GEN
Solar/Wind Harmer
3.335
270224U2-072_GEN2
Solar/Wind Harmer
0
270227U2-072_GEN3
Solar/Wind Harmer
0
270228U2-072_GEN4
Solar/Wind Harmer
0
270231U2-072_GEN5
Solar/Wind Harmer
0
274808UNIV PK N;4U
Adder
2.391
274803UNIV PARK;6U
Adder
2.765
942221AE2-234 GEN
Solar/Wind Harmer
0.017
274888KELLY CRK;1U
Solar/Wind Harmer
0.193
274887GEN-1.85
Solar/Wind Harmer
0.087
276843GEN-1.7
Solar/Wind Harmer
0.107
958011AF2-095 GEN
Solar/Wind Harmer
4.742
274770LINCOLN ;1U
Adder
3.982
274771LINCOLN ;2U
Adder
3.982
972259AH1-714 GEN
Adder
8.939
274674JOLIET 9 ;6U
Adder
7.195
970321AG2-212 GEN
Solar/Wind Harmer
1.409
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
958481AF2-142 GEN
Solar/Wind Harmer
4.833
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.436
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
971573AH1-285 GEN
Solar/Wind Harmer
0.598
274696ROCKY RD ;4P
Adder
5.229
274695ROCKY RD ;2P
Adder
5.109
274693ROCKY RD ;1P
Adder
5.059
274697ROCKY RD ;3P
Adder
1.388
274683WAUKEGAN ;8U
Adder
9.663
274683WAUKEGAN ;8U
Adder
8.145
958491AF2-143 GEN
Solar/Wind Harmer
4.791
962691AG1-118 GEN
Solar/Wind Harmer
9.548
274879MINONK ;1U
Solar/Wind Harmer
0.134
970921AG2-575 GEN
Solar/Wind Harmer
3.177
970921AG2-575 GEN
Solar/Wind Harmer
1.059
942991AE2-321 GEN
Solar/Wind Harmer
3.534
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
971333AH1-146 GEN
Solar/Wind Harmer
6.305
971335AH1-147 GEN
Solar/Wind Harmer
6.305
971341AH1-150 GEN
Solar/Wind Harmer
6.279
971343AH1-151 GEN
Solar/Wind Harmer
6.279
274856ECOGROVE ;U1
Solar/Wind Harmer
0.074
276611AD2-172 GEN
Solar/Wind Harmer
0.001
938861AE1-114 GEN
Solar/Wind Harmer
1.759
274764LEE CO EC;5U
Adder
4.139
274765LEE CO EC;6U
Adder
4.139
274762LEE CO EC;3U
Adder
4.129
274763LEE CO EC;4U
Adder
4.09
966841AG1-555 GEN
Solar/Wind Harmer
0.35
944541AF1-119 GEN
Solar/Wind Harmer
0.207
276603SUBLETTE C
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
1.815
274851PROVIDENC;RU
Solar/Wind Harmer
0
274849CRESCENT ;1U
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.121
276646AC1-214 GEN2
Solar/Wind Harmer
0.121
276741O09 GEN1
Solar/Wind Harmer
0.109
276708O09 GEN2
Solar/Wind Harmer
0.109
276782AC1-033 GEN
Solar/Wind Harmer
0
270201AC2-176 GEN
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
0.227
253378AE2-206_GEN
Solar/Wind Harmer
0.002
276820AF1-078_GEN
Solar/Wind Harmer
0.001
970329AG2-216 GEN
Solar/Wind Harmer
1.305
960611AF2-352 GEN
Solar/Wind Harmer
1.007
270599AE1-208 GEN
Solar/Wind Harmer
2.766
270031AE2-169
Solar/Wind Harmer
1.66
203947AF1-006 C
Solar/Wind Helper
0.409
203980AG1-197 GEN
Solar/Wind Helper
0.267
203979AG1-198 GEN
Solar/Wind Helper
0.208
241967AE2-285_GEN
Solar/Wind Helper
0.363
241801AE1-079 GEN
Solar/Wind Helper
0.141
241985AE1-237 GEN
Solar/Wind Helper
0.141
962101AG1-054 GEN
Solar/Wind Helper
0.35
946381AF1-302 GEN
Solar/Wind Helper
0.113
238217AF1-153 C O1
Solar/Wind Helper
0.119
20398826ARMNA MT
Solar/Wind Helper
0.706
203853AF1-134 C O1
Solar/Wind Helper
0.221
991177J1571 G
External Queue
15.714932441711426
990527J1329
External Queue
1.8513455390930176
990142J1224
External Queue
13.53333568572998
991182J1586 G
External Queue
25.292837142944336
LAGNLTFEXP_LAGN->PJM
CLTF
5.122
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.262
TVALTFEXP_TVA->PJM
CLTF
2.326
CPLELTFEXP_CPLE->PJM
CLTF
0.333
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.959
NYPJM->LTFIMP_NY
CLTF
2.164
LGEELTFEXP_LGEE->PJM
CLTF
2.094
WECLTFEXP_WEC->PJM
CLTF
1.712
AG2-052LTFEXP_AG2-052->PJM
LTF
0.11
AH1-155LTFEXP_AH1-155->PJM
LTF
0.165
CBM West 1LTFEXP_CBM-W1->PJM
CBM
96.287
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.224
MECLTFEXP_MEC->PJM
CLTF
6.679
SIGELTFEXP_SIGE->PJM
CLTF
0.174

Details for 02HAYES-02BEAVER 345.0 kV Ckt 1 line l/o ATSI_P1-2_OEC-345-824_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02HAYES-02BEAVER 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_OEC-345-824_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:135.68 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:2548.09
MW Contribution:10.53
Bus #Bus NameTypeMW Contribution
24189902OREGON_CT2
50/50
2.68
23856402BAYSG1
50/50
1.434
23888702TROY G3
50/50
1.837
972253AH1-711 GEN
50/50
56.101
23860302FRMENG 3
50/50
3.54
23920202STRYCT
50/50
2.052
241807AE2-176_GEN
Solar/Wind Harmer
0.009
241858AF1-205_GEN
Solar/Wind Harmer
4.136
241808AF1-120 C
Solar/Wind Harmer
0.003
241840AF1-064_GEN
Solar/Wind Harmer
0.004
972301AH1-735 GEN
Adder
7.125
23906402RICHG1
Adder
1.425
23906502RICHG2&3
Adder
1.423
270361_3
Solar/Wind Harmer
5.347
960841AF2-375 GEN
Solar/Wind Harmer
-0.002
247522W1-056 GEN
Solar/Wind Harmer
0.001
270428AC2-015 C
Solar/Wind Harmer
0.003
970515AG2-329 GEN
Solar/Wind Harmer
13.704
944231AF1-091 GEN
Solar/Wind Harmer
1.301
246936BC-WTG1
Solar/Wind Harmer
0.176
270489AE1-102 GEN1
Solar/Wind Harmer
0.565
965421AG1-410 GEN
Solar/Wind Harmer
12.915
24695305TIMB G C
Solar/Wind Harmer
0.001
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.182
970905AG2-564 GEN
Solar/Wind Harmer
2.27
945111AF1-176 GEN
Solar/Wind Harmer
7.306
270505AE1-170 C O1
Solar/Wind Harmer
4.294
247521TR3_G114
Solar/Wind Harmer
0.148
270246TR4_N_V150
Solar/Wind Harmer
0.026
24639705ELKHART HY
Adder
0.088
270063AE2-323 C
Solar/Wind Harmer
0.003
270462AD2-086
Solar/Wind Harmer
0.008
965011AG1-365 GEN
Solar/Wind Harmer
3.901
270223U2-072_GEN1
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
7.368
270055AF2-134 C O1
Solar/Wind Harmer
0.003
274751CRETE EC ;1U
Adder
4.008
274754CRETE EC ;4U
Adder
4.008
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.39
274723RIVER EC ;12
Adder
8.649
274812UNIV PK N;8U
Adder
2.406
276164X3-005 C
Solar/Wind Harmer
0
274801UNIV PARK;4U
Adder
2.762
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
4.126
276776AD2-060 GEN
Solar/Wind Harmer
0.345
274773LINCOLN ;4U
Adder
3.991
274774LINCOLN ;5U
Adder
3.991
274676JOLIET 29;8U
Adder
14.394
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
7.698
274674JOLIET 9 ;6U
Adder
7.21
970245AG2-165 GEN
Solar/Wind Harmer
1.412
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
2.589
276691AA1-018 GEN1
Solar/Wind Harmer
0.391
274682WAUKEGAN ;7U
Adder
8.266
274828WAUKEGAN ;BP
Adder
5.076
276901AD2-066 C O1
Solar/Wind Harmer
0.003
939401AE1-172 GEN
Solar/Wind Harmer
2.387
962781AG1-127 GEN
Solar/Wind Harmer
3.03
24791305MDL-5G
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0.002
971997AH1-543 GEN
Solar/Wind Harmer
1.665
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
276861AD2-134 GEN
Solar/Wind Harmer
0.057
957471AF2-041 GEN
Solar/Wind Harmer
9.44
959081AF2-199 GEN
Solar/Wind Harmer
3.147
971067AG2-660 GEN
Solar/Wind Harmer
1.049
274822ROCKFORD ;11
Adder
8.833
970569AG2-363 GEN
Solar/Wind Harmer
9.405
972235AH1-702 GEN1
Adder
1.133
970819AG2-516 GEN
Solar/Wind Harmer
3.753
971475AH1-234 GEN
Solar/Wind Harmer
1.515
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
4.138
274766LEE CO EC;7U
Adder
0.44
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.001
965651AG1-433 GEN
Solar/Wind Harmer
0.909
276158O29GEN2
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
1.331
274877BISHOP HL;1U
Solar/Wind Harmer
0.103
276726Z2-087_GEN
Solar/Wind Harmer
0.001
23867002DVBSG1
50/50
12.828
972211AH1-690 GEN
50/50
288.97
23888502TROY G1
50/50
1.837
23888602TROY G2
50/50
1.837
23860102FRMENG 1
50/50
1.734
23860202FRMENG 2
50/50
1.734
24191202EL_AA1-006
50/50
0.334
970817AG2-515 GEN
Solar/Wind Harmer
10.993
945411AF1-206 GEN
Solar/Wind Harmer
-0.001
270499AE1-146 GEN
Solar/Wind Harmer
0.033
945641AF1-229 GEN
Solar/Wind Harmer
0.001
270297AD1-101 GEN
Solar/Wind Harmer
0.001
971549AH1-272 GEN
Solar/Wind Harmer
10.529
971989AH1-539 GEN
Solar/Wind Harmer
1.992
247607V1-011 GEN
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.551
971619AH1-309 GEN
Solar/Wind Harmer
1.84
965041AG1-368 GEN
Solar/Wind Harmer
4.084
965051AG1-369 GEN
Solar/Wind Harmer
2.03
270302AB2-170 GEN
Solar/Wind Harmer
0.002
270317AD1-130_GEN
Solar/Wind Harmer
0.006
971653AH1-327 GEN
Solar/Wind Harmer
0.551
971771AH1-392 GEN
Solar/Wind Harmer
3.884
971567AH1-282 GEN
Solar/Wind Harmer
5.77
971769AH1-391 GEN
Solar/Wind Harmer
4.229
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
270578AF1-285 GEN2
Solar/Wind Harmer
0.242
971347AH1-153 GEN
Solar/Wind Harmer
5.444
963791AG1-232 GEN
Solar/Wind Harmer
4.883
270536AF1-215 GEN2
Solar/Wind Harmer
0.004
270071AF1-092 GEN
Solar/Wind Harmer
6.55
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274814UNIV PK N;0U
Adder
2.427
274807UNIV PK N;3U
Adder
2.422
274805UNIV PK N;1U
Adder
2.412
274811UNIV PK N;7U
Adder
2.406
972037AH1-567 GEN1
Adder
0.087
274827FISK ;RP
Adder
3.681
971611AH1-305 GEN
Solar/Wind Harmer
1.965
960591AF2-350 GEN
Solar/Wind Harmer
3.3
274775LINCOLN ;6U
Adder
3.991
274776LINCOLN ;7U
Adder
3.991
274777LINCOLN ;8U
Adder
3.991
972227AH1-698 GEN1
Adder
1.23
274687WILL CNTY;4U
Adder
13.136
274687WILL CNTY;4U
Adder
13.136
270024AE2-089 GEN
Solar/Wind Harmer
0.004
274675JOLIET 29;7U
Adder
14.394
274675JOLIET 29;7U
Adder
13.88
274731ELWOOD EC;2P
Adder
7.698
274733ELWOOD EC;3P
Adder
7.698
274735ELWOOD EC;4P
Adder
7.698
274728ELWOOD EC;5P
Adder
7.698
970833AG2-524 GEN
Solar/Wind Harmer
3.577
970833AG2-524 GEN
Solar/Wind Harmer
2.384
274746AC1-111 G10
Adder
2.589
274744AC1-111 GEN8
Adder
2.589
24729505KEY G4
Adder
2.963
276868AE1-113 GEN
Solar/Wind Harmer
0.639
276882AE2-255 GEN
Solar/Wind Harmer
0.372
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0
270181AB1-006 GEN2
Solar/Wind Harmer
0
971177AH1-047 GEN
Solar/Wind Harmer
1.955
971411AH1-196 GEN
Solar/Wind Harmer
4.743
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
1.232
971171AH1-044 GEN
Solar/Wind Harmer
6.293
274823ROCKFORD ;21
Adder
8.769
970169AG2-114 GEN
Solar/Wind Harmer
3.129
926823AC1-168 GEN
Solar/Wind Harmer
0.532
276612AE2-035 GEN
Solar/Wind Harmer
0.001
971681AH1-341 GEN
Solar/Wind Harmer
5.011
24386205FR-12G C
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
24387005FR-3G C
Solar/Wind Harmer
0.001
961011AF2-392 GEN
Solar/Wind Harmer
1.812
957751AF2-069 GEN
Solar/Wind Harmer
0.102
965101AG1-375 GEN
Solar/Wind Harmer
3.072
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
276655WTG1_EQ
Solar/Wind Harmer
0.001
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.214
941731AE2-173 GEN
Solar/Wind Harmer
2.551
963841AG1-237 GEN
Solar/Wind Harmer
1.318
971609AH1-304 GEN
Solar/Wind Harmer
0.494
946321AF1-296 GEN
Solar/Wind Harmer
1.693
945581AF1-223 GEN
Solar/Wind Harmer
0
241886AC2-103 GEN2
Solar/Wind Helper
4.614
241982AE2-343 S C
Solar/Wind Helper
0.126
254304AE2-114 C
Solar/Wind Helper
0.12
203846AF2-130 C
Solar/Wind Helper
0.265
241997AF1-093 GEN
Solar/Wind Helper
0.139
203804AE2-113_GEN
Solar/Wind Helper
0.926
203855AF2-088 C
Solar/Wind Helper
0.072
23929302BS-PKR
50/50
2.524
241832AE2-181_GEN
Solar/Wind Harmer
0.004
958321AF2-126 GEN
Solar/Wind Harmer
1.268
23906502RICHG2&3
Adder
1.423
270575GUS2 35KV
Solar/Wind Harmer
5.347
270541AE2-072 C
Solar/Wind Harmer
0.009
970217AG2-149 GEN
Solar/Wind Harmer
4.568
270404AC1-167 GEN
Solar/Wind Harmer
0.002
270588AE1-091_GEN
Solar/Wind Harmer
3.741
270258AD1-119 GEN
Solar/Wind Harmer
0.001
247604X1-042
Adder
0.267
24441205WTRV SLR C
Solar/Wind Harmer
0
270491AE1-102 GEN2
Solar/Wind Harmer
0.565
945111AF1-176 GEN
Solar/Wind Harmer
3.319
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.026
24642205MAYFLWER
Adder
0.363
970031AG2-029 GEN
Solar/Wind Harmer
2.575
247643Z2-116 C
Solar/Wind Harmer
0
270485AE1-090_GEN
Solar/Wind Harmer
0.001
959331AF2-224 GEN
Solar/Wind Harmer
2.73
965021AG1-366 GEN
Solar/Wind Harmer
1.3
270377AD1-106 GEN
Solar/Wind Harmer
1.422
270043AE2-236 GEN
Solar/Wind Harmer
2.357
270391AF1-285 GEN3
Solar/Wind Harmer
0.242
970349AG2-230 GEN
Solar/Wind Harmer
5.444
270535AF1-215 GEN1
Solar/Wind Harmer
0.004
274752CRETE EC ;2U
Adder
4.008
274753CRETE EC ;3U
Adder
4.008
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274724RIVER EC ;11
Adder
8.546
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
274802UNIV PARK;5U
Adder
2.771
274826FISK ;BP
Adder
5.194
274800UNIV PARK;3U
Adder
2.762
972038AH1-567 GEN2
Adder
0.173
276806AD2-047 C O1
Solar/Wind Harmer
1.87
970941AG2-585 GEN
Solar/Wind Harmer
4.125
274772LINCOLN ;3U
Adder
3.991
972228AH1-698 GEN2
Adder
1.747
274676JOLIET 29;8U
Adder
13.879
971617AH1-308 GEN
Solar/Wind Harmer
2.727
276897AD1-100 C
Solar/Wind Harmer
0.004
939351AE1-166 GEN
Solar/Wind Harmer
0
276893AG1-478 C
Solar/Wind Harmer
0.13
970707AG2-453 GEN
Solar/Wind Harmer
10.672
274729ELWOOD EC;1P
Adder
7.698
274730ELWOOD EC;6P
Adder
7.698
274734ELWOOD EC;8P
Adder
7.698
274736ELWOOD EC;9P
Adder
7.698
970513AG2-328 GEN
Solar/Wind Harmer
1.412
970517AG2-330 GEN
Solar/Wind Harmer
8.474
943121AE2-341 GEN
Solar/Wind Harmer
5.415
943591AF1-030 GEN
Solar/Wind Harmer
3.601
276694AA1-018 GEN2
Solar/Wind Harmer
0
944531AF1-118 GEN
Solar/Wind Harmer
14.419
274682WAUKEGAN ;7U
Adder
8.266
276805AD2-038 GEN
Solar/Wind Harmer
0.001
24755605MDL-5G
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.183
274872LEEDK;1U
Solar/Wind Harmer
0.117
276889AE2-281 GEN
Solar/Wind Harmer
0
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.337
274855GSG-6 ;RU
Solar/Wind Harmer
0.116
274850MENDOTA H;RU
Solar/Wind Harmer
0.037
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.057
959091AF2-200 GEN
Solar/Wind Harmer
6.293
970571AG2-364 GEN
Solar/Wind Harmer
6.27
972236AH1-702 GEN2
Adder
0.985
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
4.138
276157O29GEN1
Solar/Wind Harmer
0.498
274878BISHOP HL;2U
Solar/Wind Harmer
0.103
942111AE2-223 GEN
Solar/Wind Harmer
0.995
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
4.59
274853TWINGROVE;U1
Solar/Wind Harmer
0.001
965091AG1-374 GEN
Solar/Wind Harmer
9.081
959611AF2-252 GEN
Solar/Wind Harmer
1.009
965931AG1-462 GEN
Solar/Wind Harmer
7.678
247642Z2-115 C
Solar/Wind Harmer
0.001
962511AG1-100 GEN
Solar/Wind Helper
0.366
203830AF1-094 GEN
Solar/Wind Helper
0.347
959441AF2-235 GEN
Solar/Wind Helper
0.157
254305AE2-115 C
Solar/Wind Helper
0.12
20334926Z1-069 C
Solar/Wind Helper
0.689
203854AF2-039 C
Solar/Wind Helper
0.149
939741AE1-205 GEN
Solar/Wind Harmer
4.286
274854TWINGROVE;U2
Solar/Wind Harmer
0.001
945371AF1-202 GEN
Solar/Wind Harmer
0
241885AC2-103 GEN1
Solar/Wind Helper
4.614
961971AG1-040 GEN
Solar/Wind Helper
0.358
203835AF1-098 GEN
Solar/Wind Helper
1.412
203860AG1-193 C
Solar/Wind Helper
0.16
241966AE1-183 GEN
Solar/Wind Helper
0.139
254303AC2-168 GEN
Solar/Wind Helper
0.081
203954AE2-126 C
Solar/Wind Helper
0.233
24190002OREGON_ST1
50/50
3.605
24189802OREGON_CT1
50/50
2.735
23888802TROY G4
50/50
1.837
241996AE2-282_GEN
Solar/Wind Harmer
0.006
971677AH1-339 GEN
Solar/Wind Harmer
0.746
970621AG2-405 GEN
Solar/Wind Harmer
0.951
970623AG2-406 GEN
Solar/Wind Harmer
0.857
270007AE1-245 C
Solar/Wind Harmer
0.001
246938BC-WTG3
Solar/Wind Harmer
0.158
246937BC-WTG2
Solar/Wind Harmer
0.176
961051AF2-396 GEN
Solar/Wind Harmer
8.298
961051AF2-396 GEN
Solar/Wind Harmer
5.532
957891AF2-083 GEN
Solar/Wind Harmer
0.001
247620Y3-023
Adder
0.264
270216AD2-079_GEN
Solar/Wind Harmer
0.001
970611AG2-400 GEN
Solar/Wind Harmer
3.901
970627AG2-408 GEN
Solar/Wind Harmer
1.17
270526AF1-158 GEN
Solar/Wind Harmer
0.005
24441505OLIV SLR
Solar/Wind Harmer
0
971231AH1-075 GEN
Solar/Wind Harmer
0.429
965681AG1-436 GEN
Solar/Wind Harmer
4.556
965791AG1-447 GEN
Solar/Wind Harmer
3.341
270224U2-072_GEN2
Solar/Wind Harmer
0
270227U2-072_GEN3
Solar/Wind Harmer
0
270228U2-072_GEN4
Solar/Wind Harmer
0
270231U2-072_GEN5
Solar/Wind Harmer
0
274808UNIV PK N;4U
Adder
2.396
274803UNIV PARK;6U
Adder
2.771
942221AE2-234 GEN
Solar/Wind Harmer
0.017
274888KELLY CRK;1U
Solar/Wind Harmer
0.194
274887GEN-1.85
Solar/Wind Harmer
0.087
276843GEN-1.7
Solar/Wind Harmer
0.107
958011AF2-095 GEN
Solar/Wind Harmer
4.752
274770LINCOLN ;1U
Adder
3.991
274771LINCOLN ;2U
Adder
3.991
972259AH1-714 GEN
Adder
8.958
274674JOLIET 9 ;6U
Adder
7.21
970321AG2-212 GEN
Solar/Wind Harmer
1.412
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
958481AF2-142 GEN
Solar/Wind Harmer
4.844
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.437
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
971573AH1-285 GEN
Solar/Wind Harmer
0.6
274696ROCKY RD ;4P
Adder
5.24
274695ROCKY RD ;2P
Adder
5.12
274693ROCKY RD ;1P
Adder
5.069
274697ROCKY RD ;3P
Adder
1.391
274683WAUKEGAN ;8U
Adder
9.683
274683WAUKEGAN ;8U
Adder
8.163
958491AF2-143 GEN
Solar/Wind Harmer
4.801
962691AG1-118 GEN
Solar/Wind Harmer
9.569
274879MINONK ;1U
Solar/Wind Harmer
0.134
970921AG2-575 GEN
Solar/Wind Harmer
3.184
970921AG2-575 GEN
Solar/Wind Harmer
1.061
942991AE2-321 GEN
Solar/Wind Harmer
3.541
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
971333AH1-146 GEN
Solar/Wind Harmer
6.319
971335AH1-147 GEN
Solar/Wind Harmer
6.319
971341AH1-150 GEN
Solar/Wind Harmer
6.293
971343AH1-151 GEN
Solar/Wind Harmer
6.293
274856ECOGROVE ;U1
Solar/Wind Harmer
0.074
276611AD2-172 GEN
Solar/Wind Harmer
0.001
938861AE1-114 GEN
Solar/Wind Harmer
1.763
274764LEE CO EC;5U
Adder
4.148
274765LEE CO EC;6U
Adder
4.148
274762LEE CO EC;3U
Adder
4.138
274763LEE CO EC;4U
Adder
4.099
966841AG1-555 GEN
Solar/Wind Harmer
0.351
944541AF1-119 GEN
Solar/Wind Harmer
0.208
276603SUBLETTE C
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
1.819
274851PROVIDENC;RU
Solar/Wind Harmer
0
274849CRESCENT ;1U
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.121
276646AC1-214 GEN2
Solar/Wind Harmer
0.121
276741O09 GEN1
Solar/Wind Harmer
0.11
276708O09 GEN2
Solar/Wind Harmer
0.11
276782AC1-033 GEN
Solar/Wind Harmer
0
270201AC2-176 GEN
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
0.227
253378AE2-206_GEN
Solar/Wind Harmer
0.002
276820AF1-078_GEN
Solar/Wind Harmer
0.001
970329AG2-216 GEN
Solar/Wind Harmer
1.308
960611AF2-352 GEN
Solar/Wind Harmer
1.009
270599AE1-208 GEN
Solar/Wind Harmer
2.772
270031AE2-169
Solar/Wind Harmer
1.663
203947AF1-006 C
Solar/Wind Helper
0.408
203980AG1-197 GEN
Solar/Wind Helper
0.267
203979AG1-198 GEN
Solar/Wind Helper
0.208
241967AE2-285_GEN
Solar/Wind Helper
0.362
241801AE1-079 GEN
Solar/Wind Helper
0.141
241985AE1-237 GEN
Solar/Wind Helper
0.14
962101AG1-054 GEN
Solar/Wind Helper
0.35
946381AF1-302 GEN
Solar/Wind Helper
0.112
238217AF1-153 C O1
Solar/Wind Helper
0.119
20398826ARMNA MT
Solar/Wind Helper
0.704
991177J1571 G
External Queue
15.714932441711426
990527J1329
External Queue
1.8513455390930176
990142J1224
External Queue
13.53333568572998
991182J1586 G
External Queue
25.292837142944336
LAGNLTFEXP_LAGN->PJM
CLTF
5.142
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.292
TVALTFEXP_TVA->PJM
CLTF
2.336
CPLELTFEXP_CPLE->PJM
CLTF
0.344
CBM West 2LTFEXP_CBM-W2->PJM
CBM
41.091
NYPJM->LTFIMP_NY
CLTF
2.158
LGEELTFEXP_LGEE->PJM
CLTF
2.101
WECLTFEXP_WEC->PJM
CLTF
1.716
AG2-052LTFEXP_AG2-052->PJM
LTF
0.11
AH1-155LTFEXP_AH1-155->PJM
LTF
0.166
CBM West 1LTFEXP_CBM-W1->PJM
CBM
96.429
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.261
MECLTFEXP_MEC->PJM
CLTF
6.695
SIGELTFEXP_SIGE->PJM
CLTF
0.175

Details for 02LALLENDORF-05FOSTOR 345.0 kV Ckt 1 line l/o ATSI_P7-1_TE-345-021_SRT-A-1


Base Case Flowgate

Area:AEP/ATSI
Facility Description:
02LALLENDORF-05FOSTOR 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P7-1_TE-345-021_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:124.85 %
Rating:1409.0 MVA
Rating Type:B
MVA to Mitigate:1759.15
MW Contribution:9.68
Bus #Bus NameTypeMW Contribution
972211AH1-690 GEN
50/50
788.046
971549AH1-272 GEN
Solar/Wind Harmer
9.679
945641AF1-229 GEN
Solar/Wind Helper
1.292
270499AE1-146 GEN
Solar/Wind Helper
1.518
24189902OREGON_CT2
50/50
7.319
960841AF2-375 GEN
Solar/Wind Helper
1.005
247522W1-056 GEN
Solar/Wind Helper
0.609
24190002OREGON_ST1
50/50
9.847
24189802OREGON_CT1
50/50
7.469
991177J1571 G
External Queue
11.570172309875488
990527J1329
External Queue
2.09696888923645
990142J1224
External Queue
15.328842163085938
991182J1586 G
External Queue
29.999971389770508
LAGNLTFEXP_LAGN->PJM
CLTF
0.887
TVALTFEXP_TVA->PJM
CLTF
0.274
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.544
NYPJM->LTFIMP_NY
CLTF
0.462
LGEELTFEXP_LGEE->PJM
CLTF
0.155
WECLTFEXP_WEC->PJM
CLTF
0.632
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.188
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.094
CBM West 1LTFEXP_CBM-W1->PJM
CBM
79.953
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.997
MECLTFEXP_MEC->PJM
CLTF
2.173
SIGELTFEXP_SIGE->PJM
CLTF
0.028

Details for 02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line l/o ATSI_P2-3_TE-345-007_SRT-SL


Base Case Flowgate

Area:ATSI
Facility Description:
02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_TE-345-007_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:137.87 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:2589.19
MW Contribution:14.84
Bus #Bus NameTypeMW Contribution
23888502TROY G1
50/50
2.619
23888602TROY G2
50/50
2.619
972211AH1-690 GEN
50/50
230.612
23906902RICHG6
50/50
1.023
23906702RICHG4
50/50
1.02
23906802RICHG5
50/50
0.745
970817AG2-515 GEN
Solar/Wind Harmer
20.387
945411AF1-206 GEN
Solar/Wind Harmer
9.795
945641AF1-229 GEN
Solar/Wind Harmer
4.031
270499AE1-146 GEN
Solar/Wind Harmer
2.505
971549AH1-272 GEN
Solar/Wind Harmer
14.838
270297AD1-101 GEN
Solar/Wind Harmer
2.213
247607V1-011 GEN
Solar/Wind Harmer
2.706
957201AF2-014 GEN
Solar/Wind Harmer
3.088
270435AC2-044 GEN
Solar/Wind Harmer
1.362
944161AF1-084 GEN
Solar/Wind Harmer
1.473
966831AG1-554 GEN
Solar/Wind Harmer
0.779
971989AH1-539 GEN
Solar/Wind Harmer
8.419
965041AG1-368 GEN
Solar/Wind Harmer
6.392
965051AG1-369 GEN
Solar/Wind Harmer
3.172
971771AH1-392 GEN
Solar/Wind Harmer
5.509
270302AB2-170 GEN
Solar/Wind Harmer
5.12
270317AD1-130_GEN
Solar/Wind Harmer
1.963
971769AH1-391 GEN
Solar/Wind Harmer
5.97
971567AH1-282 GEN
Solar/Wind Harmer
8.782
960681AF2-359 GEN
Solar/Wind Harmer
2.172
971347AH1-153 GEN
Solar/Wind Harmer
8.587
963791AG1-232 GEN
Solar/Wind Harmer
7.686
270578AF1-285 GEN2
Solar/Wind Harmer
0.264
270536AF1-215 GEN2
Solar/Wind Harmer
2.468
270071AF1-092 GEN
Solar/Wind Harmer
8.09
274814UNIV PK N;0U
Adder
2.675
274807UNIV PK N;3U
Adder
2.669
274805UNIV PK N;1U
Adder
2.658
274811UNIV PK N;7U
Adder
2.652
958391AF2-133 GEN
Solar/Wind Harmer
4.803
972037AH1-567 GEN1
Adder
0.096
274827FISK ;RP
Adder
4.058
960591AF2-350 GEN
Solar/Wind Harmer
5.215
274775LINCOLN ;6U
Adder
3.232
274776LINCOLN ;7U
Adder
3.232
274777LINCOLN ;8U
Adder
3.232
972227AH1-698 GEN1
Adder
1.356
274687WILL CNTY;4U
Adder
14.483
274687WILL CNTY;4U
Adder
14.483
274675JOLIET 29;7U
Adder
15.87
274675JOLIET 29;7U
Adder
15.304
274731ELWOOD EC;2P
Adder
8.488
274733ELWOOD EC;3P
Adder
8.488
274735ELWOOD EC;4P
Adder
8.488
274728ELWOOD EC;5P
Adder
8.488
270024AE2-089 GEN
Solar/Wind Harmer
2.42
970833AG2-524 GEN
Solar/Wind Harmer
4.486
970833AG2-524 GEN
Solar/Wind Harmer
2.087
274746AC1-111 G10
Adder
2.855
274744AC1-111 GEN8
Adder
2.855
24729505KEY G4
Adder
3.263
274823ROCKFORD ;21
Adder
9.678
241886AC2-103 GEN2
Solar/Wind Helper
7.132
241982AE2-343 S C
Solar/Wind Helper
0.128
254304AE2-114 C
Solar/Wind Helper
0.122
203846AF2-130 C
Solar/Wind Helper
0.268
241997AF1-093 GEN
Solar/Wind Helper
0.141
203804AE2-113_GEN
Solar/Wind Helper
0.933
203855AF2-088 C
Solar/Wind Helper
0.072
23888802TROY G4
50/50
2.619
24190002OREGON_ST1
50/50
2.882
24189802OREGON_CT1
50/50
2.186
241996AE2-282_GEN
Solar/Wind Harmer
2.622
971677AH1-339 GEN
Solar/Wind Harmer
7.096
270007AE1-245 C
Solar/Wind Harmer
4.06
942801AE2-298 GEN
Solar/Wind Harmer
1.031
246938BC-WTG3
Solar/Wind Harmer
2.71
246937BC-WTG2
Solar/Wind Harmer
2.664
961051AF2-396 GEN
Solar/Wind Harmer
10.367
961051AF2-396 GEN
Solar/Wind Harmer
4.822
960981AF2-389 GEN
Solar/Wind Harmer
0.971
957891AF2-083 GEN
Solar/Wind Harmer
2.166
247620Y3-023
Adder
0.291
270216AD2-079_GEN
Solar/Wind Harmer
0.377
970611AG2-400 GEN
Solar/Wind Harmer
6.135
270526AF1-158 GEN
Solar/Wind Harmer
2.726
24441505OLIV SLR
Solar/Wind Harmer
0.08
965681AG1-436 GEN
Solar/Wind Harmer
7.186
965791AG1-447 GEN
Solar/Wind Harmer
3.677
270224U2-072_GEN2
Solar/Wind Harmer
1.122
270227U2-072_GEN3
Solar/Wind Harmer
1.122
270228U2-072_GEN4
Solar/Wind Harmer
1.122
270231U2-072_GEN5
Solar/Wind Harmer
1.122
274808UNIV PK N;4U
Adder
2.64
274803UNIV PARK;6U
Adder
3.055
942221AE2-234 GEN
Solar/Wind Harmer
0.382
274888KELLY CRK;1U
Solar/Wind Harmer
3.079
274887GEN-1.85
Solar/Wind Harmer
2.779
276843GEN-1.7
Solar/Wind Harmer
0.299
958011AF2-095 GEN
Solar/Wind Harmer
7.509
274770LINCOLN ;1U
Adder
3.232
274771LINCOLN ;2U
Adder
3.232
972259AH1-714 GEN
Adder
9.876
274674JOLIET 9 ;6U
Adder
7.95
970321AG2-212 GEN
Solar/Wind Harmer
9.194
274847GR RIDGE ;BU
Solar/Wind Harmer
2.598
958481AF2-142 GEN
Solar/Wind Harmer
7.657
274696ROCKY RD ;4P
Adder
5.781
274695ROCKY RD ;2P
Adder
5.647
274693ROCKY RD ;1P
Adder
5.592
274697ROCKY RD ;3P
Adder
1.534
274683WAUKEGAN ;8U
Adder
10.682
274683WAUKEGAN ;8U
Adder
9.004
274764LEE CO EC;5U
Adder
4.579
274765LEE CO EC;6U
Adder
4.579
274762LEE CO EC;3U
Adder
4.569
274763LEE CO EC;4U
Adder
4.525
972267AH1-718 GEN
Adder
2.031
247621Y3-024
Adder
0.115
25326509SID D
Adder
0.626
203947AF1-006 C
Solar/Wind Helper
0.414
203980AG1-197 GEN
Solar/Wind Helper
0.271
203979AG1-198 GEN
Solar/Wind Helper
0.211
241967AE2-285_GEN
Solar/Wind Helper
0.368
241801AE1-079 GEN
Solar/Wind Helper
0.143
241985AE1-237 GEN
Solar/Wind Helper
0.143
962101AG1-054 GEN
Solar/Wind Helper
0.354
946381AF1-302 GEN
Solar/Wind Helper
0.113
238217AF1-153 C O1
Solar/Wind Helper
0.12
20398826ARMNA MT
Solar/Wind Helper
0.707
203853AF1-134 C O1
Solar/Wind Helper
0.221
274861TOP CROP ;1U
Solar/Wind Harmer
0.282
274862TOP CROP ;2U
Solar/Wind Harmer
0.236
23906502RICHG2&3
50/50
1.719
241832AE2-181_GEN
Solar/Wind Harmer
2.411
958321AF2-126 GEN
Solar/Wind Harmer
1.797
23929302BS-PKR
Adder
1.928
270541AE2-072 C
Solar/Wind Harmer
5.113
270575GUS2 35KV
Solar/Wind Harmer
10.488
970217AG2-149 GEN
Solar/Wind Harmer
26.038
270044AE2-322 C
Solar/Wind Harmer
1.007
270404AC1-167 GEN
Solar/Wind Harmer
0.839
270258AD1-119 GEN
Solar/Wind Harmer
2.048
247604X1-042
Adder
0.293
270588AE1-091_GEN
Solar/Wind Harmer
7.623
24441205WTRV SLR C
Solar/Wind Harmer
0.093
958091AF2-103 GEN
Solar/Wind Harmer
0.111
270491AE1-102 GEN2
Solar/Wind Harmer
0.885
945111AF1-176 GEN
Solar/Wind Harmer
3.646
270191TR4_S_V150
Solar/Wind Harmer
1.906
270247TR4_N_V136
Solar/Wind Harmer
0.54
24642205MAYFLWER
Adder
0.399
970031AG2-029 GEN
Solar/Wind Harmer
18.728
247643Z2-116 C
Solar/Wind Harmer
0.043
959331AF2-224 GEN
Solar/Wind Harmer
6.135
965021AG1-366 GEN
Solar/Wind Harmer
1.427
270485AE1-090_GEN
Solar/Wind Harmer
0.37
270043AE2-236 GEN
Solar/Wind Harmer
3.186
970349AG2-230 GEN
Solar/Wind Harmer
8.587
942871AE2-306 GEN
Solar/Wind Harmer
0.515
270391AF1-285 GEN3
Solar/Wind Harmer
0.264
270535AF1-215 GEN1
Solar/Wind Harmer
2.468
972231SS25-0005
Solar/Wind Harmer
5.086
972181SS23-001
Solar/Wind Harmer
3.179
274752CRETE EC ;2U
Adder
2.62
274753CRETE EC ;3U
Adder
2.62
964401AG1-302 GEN
Solar/Wind Harmer
4.846
274724RIVER EC ;11
Adder
9.418
959141AF2-205 GEN
Solar/Wind Harmer
3.179
274802UNIV PARK;5U
Adder
3.055
274826FISK ;BP
Adder
5.726
274800UNIV PARK;3U
Adder
3.045
972038AH1-567 GEN2
Adder
0.191
276772AC2-154 GEN
Solar/Wind Harmer
1.454
276806AD2-047 C O1
Solar/Wind Harmer
5.578
970941AG2-585 GEN
Solar/Wind Harmer
6.518
274772LINCOLN ;3U
Adder
3.232
972228AH1-698 GEN2
Adder
1.926
274676JOLIET 29;8U
Adder
15.304
276897AD1-100 C
Solar/Wind Harmer
14.996
939351AE1-166 GEN
Solar/Wind Harmer
3.064
276893AG1-478 C
Solar/Wind Harmer
0.216
274729ELWOOD EC;1P
Adder
8.488
274730ELWOOD EC;6P
Adder
8.488
274734ELWOOD EC;8P
Adder
8.488
274736ELWOOD EC;9P
Adder
8.488
970707AG2-453 GEN
Solar/Wind Harmer
14.457
971617AH1-308 GEN
Solar/Wind Harmer
2.998
970513AG2-328 GEN
Solar/Wind Harmer
9.194
970517AG2-330 GEN
Solar/Wind Harmer
8.339
943121AE2-341 GEN
Solar/Wind Harmer
7.659
943591AF1-030 GEN
Solar/Wind Harmer
5.106
276694AA1-018 GEN2
Solar/Wind Harmer
3.221
274682WAUKEGAN ;7U
Adder
9.118
972236AH1-702 GEN2
Adder
1.087
274760LEE CO EC;1U
Adder
4.569
274767LEE CO EC;8U
Adder
4.515
962511AG1-100 GEN
Solar/Wind Helper
0.372
203830AF1-094 GEN
Solar/Wind Helper
0.352
959441AF2-235 GEN
Solar/Wind Helper
0.159
254305AE2-115 C
Solar/Wind Helper
0.122
20334926Z1-069 C
Solar/Wind Helper
0.694
203854AF2-039 C
Solar/Wind Helper
0.15
23888702TROY G3
50/50
2.619
972253AH1-711 GEN
50/50
79.996
23920202STRYCT
50/50
2.358
24189902OREGON_CT2
50/50
2.142
972301AH1-735 GEN
50/50
8.615
23906402RICHG1
50/50
1.723
23906502RICHG2&3
50/50
1.719
241858AF1-205_GEN
Solar/Wind Harmer
6.914
241808AF1-120 C
Solar/Wind Harmer
1.462
241840AF1-064_GEN
Solar/Wind Harmer
1.676
270361_3
Solar/Wind Harmer
8.902
960841AF2-375 GEN
Solar/Wind Harmer
3.954
970515AG2-329 GEN
Solar/Wind Harmer
11.808
944231AF1-091 GEN
Solar/Wind Harmer
2.931
247522W1-056 GEN
Solar/Wind Harmer
1.705
246936BC-WTG1
Solar/Wind Harmer
2.664
270489AE1-102 GEN1
Solar/Wind Harmer
0.885
965421AG1-410 GEN
Solar/Wind Harmer
20.233
270449AD2-020 GEN
Solar/Wind Harmer
1.844
943021AE2-325 GEN
Solar/Wind Harmer
2.397
24695305TIMB G C
Solar/Wind Harmer
3.619
945111AF1-176 GEN
Solar/Wind Harmer
11.504
270505AE1-170 C O1
Solar/Wind Harmer
9.66
247521TR3_G114
Solar/Wind Harmer
2.136
270246TR4_N_V150
Solar/Wind Harmer
0.54
24639705ELKHART HY
Adder
0.096
270063AE2-323 C
Solar/Wind Harmer
1.381
965011AG1-365 GEN
Solar/Wind Harmer
6.135
270462AD2-086
Solar/Wind Harmer
4.259
270223U2-072_GEN1
Solar/Wind Harmer
1.122
270578AF1-285 GEN2
Solar/Wind Harmer
0.686
270391AF1-285 GEN3
Solar/Wind Harmer
0.686
970373AG2-245 GEN
Solar/Wind Harmer
11.628
270055AF2-134 C O1
Solar/Wind Harmer
1.645
274751CRETE EC ;1U
Adder
2.62
274754CRETE EC ;4U
Adder
2.62
958381AF2-132 GEN
Solar/Wind Harmer
4.846
964861AG1-349 GEN
Solar/Wind Harmer
4.191
971917AH1-482 GEN
Solar/Wind Harmer
4.836
274723RIVER EC ;12
Adder
9.531
274812UNIV PK N;8U
Adder
2.652
276164X3-005 C
Solar/Wind Harmer
0.371
274801UNIV PARK;4U
Adder
3.045
940581AE2-045 GEN
Solar/Wind Harmer
5.319
971605AH1-302 GEN
Solar/Wind Harmer
4.548
276776AD2-060 GEN
Solar/Wind Harmer
0.22
972207SS24-0001
Solar/Wind Harmer
11.49
274773LINCOLN ;4U
Adder
3.232
274774LINCOLN ;5U
Adder
3.232
274676JOLIET 29;8U
Adder
15.87
941551AE2-152 GEN
Solar/Wind Harmer
2.344
274732ELWOOD EC;7P
Adder
8.488
274674JOLIET 9 ;6U
Adder
7.95
970245AG2-165 GEN
Solar/Wind Harmer
9.194
274871GR RIDGE ;2U
Solar/Wind Harmer
3.949
274745AC1-111 GEN9
Adder
2.855
276691AA1-018 GEN1
Solar/Wind Harmer
0.238
274682WAUKEGAN ;7U
Adder
9.118
274828WAUKEGAN ;BP
Adder
5.599
274822ROCKFORD ;11
Adder
9.749
972235AH1-702 GEN1
Adder
1.25
274761LEE CO EC;2U
Adder
4.569
274766LEE CO EC;7U
Adder
4.515
241885AC2-103 GEN1
Solar/Wind Helper
7.132
241807AE2-176_GEN
Solar/Wind Helper
1.736
961971AG1-040 GEN
Solar/Wind Helper
0.363
203835AF1-098 GEN
Solar/Wind Helper
1.432
203860AG1-193 C
Solar/Wind Helper
0.162
241966AE1-183 GEN
Solar/Wind Helper
0.141
254303AC2-168 GEN
Solar/Wind Helper
0.082
203954AE2-126 C
Solar/Wind Helper
0.234
991177J1571 G
External Queue
18.513126373291016
990527J1329
External Queue
2.100800037384033
990142J1224
External Queue
15.35684871673584
991182J1586 G
External Queue
28.404245376586914
LAGNLTFEXP_LAGN->PJM
CLTF
5.797
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.925
TVALTFEXP_TVA->PJM
CLTF
2.645
CPLELTFEXP_CPLE->PJM
CLTF
0.546
CBM West 2LTFEXP_CBM-W2->PJM
CBM
45.898
NYPJM->LTFIMP_NY
CLTF
2.147
LGEELTFEXP_LGEE->PJM
CLTF
2.336
WECLTFEXP_WEC->PJM
CLTF
1.894
AG2-052LTFEXP_AG2-052->PJM
LTF
0.122
AH1-155LTFEXP_AH1-155->PJM
LTF
0.183
CBM West 1LTFEXP_CBM-W1->PJM
CBM
103.982
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.444
MECLTFEXP_MEC->PJM
CLTF
7.414
SIGELTFEXP_SIGE->PJM
CLTF
0.194

Details for 02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line l/o ATSI_P2-3_TE-345-004_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_TE-345-004_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:118.2 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:2219.8
MW Contribution:15.24
Bus #Bus NameTypeMW Contribution
23888502TROY G1
50/50
2.643
23888602TROY G2
50/50
2.643
972211AH1-690 GEN
50/50
234.319
23906902RICHG6
50/50
1.04
23906702RICHG4
50/50
1.037
23906802RICHG5
50/50
0.758
970817AG2-515 GEN
Solar/Wind Harmer
20.605
945411AF1-206 GEN
Solar/Wind Harmer
9.926
945641AF1-229 GEN
Solar/Wind Harmer
4.111
270499AE1-146 GEN
Solar/Wind Harmer
2.56
971549AH1-272 GEN
Solar/Wind Harmer
15.244
270297AD1-101 GEN
Solar/Wind Harmer
2.274
247607V1-011 GEN
Solar/Wind Harmer
2.793
957201AF2-014 GEN
Solar/Wind Harmer
3.188
270435AC2-044 GEN
Solar/Wind Harmer
1.406
944161AF1-084 GEN
Solar/Wind Harmer
1.521
966831AG1-554 GEN
Solar/Wind Harmer
0.805
971989AH1-539 GEN
Solar/Wind Harmer
8.703
965041AG1-368 GEN
Solar/Wind Harmer
6.611
965051AG1-369 GEN
Solar/Wind Harmer
3.281
971771AH1-392 GEN
Solar/Wind Harmer
5.707
270302AB2-170 GEN
Solar/Wind Harmer
5.304
270317AD1-130_GEN
Solar/Wind Harmer
2.033
971769AH1-391 GEN
Solar/Wind Harmer
6.189
971567AH1-282 GEN
Solar/Wind Harmer
9.111
960681AF2-359 GEN
Solar/Wind Harmer
2.255
971347AH1-153 GEN
Solar/Wind Harmer
8.916
963791AG1-232 GEN
Solar/Wind Harmer
7.982
270578AF1-285 GEN2
Solar/Wind Harmer
0.274
270536AF1-215 GEN2
Solar/Wind Harmer
2.568
270071AF1-092 GEN
Solar/Wind Harmer
8.419
274814UNIV PK N;0U
Adder
2.786
274807UNIV PK N;3U
Adder
2.78
274805UNIV PK N;1U
Adder
2.768
274811UNIV PK N;7U
Adder
2.762
958391AF2-133 GEN
Solar/Wind Harmer
5.002
972037AH1-567 GEN1
Adder
0.1
274827FISK ;RP
Adder
4.228
960591AF2-350 GEN
Solar/Wind Harmer
5.434
274775LINCOLN ;6U
Adder
3.367
274776LINCOLN ;7U
Adder
3.367
274777LINCOLN ;8U
Adder
3.367
972227AH1-698 GEN1
Adder
1.413
274687WILL CNTY;4U
Adder
15.096
274687WILL CNTY;4U
Adder
15.096
274675JOLIET 29;7U
Adder
16.543
274675JOLIET 29;7U
Adder
15.952
274731ELWOOD EC;2P
Adder
8.849
274733ELWOOD EC;3P
Adder
8.849
274735ELWOOD EC;4P
Adder
8.849
274728ELWOOD EC;5P
Adder
8.849
270024AE2-089 GEN
Solar/Wind Harmer
2.523
970833AG2-524 GEN
Solar/Wind Harmer
4.678
970833AG2-524 GEN
Solar/Wind Harmer
2.176
274746AC1-111 G10
Adder
2.978
274744AC1-111 GEN8
Adder
2.978
24729505KEY G4
Adder
3.405
274823ROCKFORD ;21
Adder
10.105
241886AC2-103 GEN2
Solar/Wind Helper
7.083
241982AE2-343 S C
Solar/Wind Helper
0.123
254304AE2-114 C
Solar/Wind Helper
0.117
203846AF2-130 C
Solar/Wind Helper
0.257
241997AF1-093 GEN
Solar/Wind Helper
0.136
203804AE2-113_GEN
Solar/Wind Helper
0.892
23888802TROY G4
50/50
2.643
24190002OREGON_ST1
50/50
2.928
24189802OREGON_CT1
50/50
2.221
241996AE2-282_GEN
Solar/Wind Harmer
2.658
971677AH1-339 GEN
Solar/Wind Harmer
7.272
270007AE1-245 C
Solar/Wind Harmer
4.19
942801AE2-298 GEN
Solar/Wind Harmer
1.064
246938BC-WTG3
Solar/Wind Harmer
2.798
246937BC-WTG2
Solar/Wind Harmer
2.75
961051AF2-396 GEN
Solar/Wind Harmer
10.715
961051AF2-396 GEN
Solar/Wind Harmer
4.984
960981AF2-389 GEN
Solar/Wind Harmer
1.004
957891AF2-083 GEN
Solar/Wind Harmer
2.24
247620Y3-023
Adder
0.301
270216AD2-079_GEN
Solar/Wind Harmer
0.39
970611AG2-400 GEN
Solar/Wind Harmer
6.354
270526AF1-158 GEN
Solar/Wind Harmer
2.826
24441505OLIV SLR
Solar/Wind Harmer
0.083
965681AG1-436 GEN
Solar/Wind Harmer
7.46
965791AG1-447 GEN
Solar/Wind Harmer
3.817
270224U2-072_GEN2
Solar/Wind Harmer
1.166
270227U2-072_GEN3
Solar/Wind Harmer
1.166
270228U2-072_GEN4
Solar/Wind Harmer
1.166
270231U2-072_GEN5
Solar/Wind Harmer
1.166
274808UNIV PK N;4U
Adder
2.75
274803UNIV PARK;6U
Adder
3.182
942221AE2-234 GEN
Solar/Wind Harmer
0.398
274888KELLY CRK;1U
Solar/Wind Harmer
3.208
274887GEN-1.85
Solar/Wind Harmer
2.896
276843GEN-1.7
Solar/Wind Harmer
0.312
958011AF2-095 GEN
Solar/Wind Harmer
7.825
274770LINCOLN ;1U
Adder
3.367
274771LINCOLN ;2U
Adder
3.367
972259AH1-714 GEN
Adder
10.294
274674JOLIET 9 ;6U
Adder
8.288
970321AG2-212 GEN
Solar/Wind Harmer
9.586
274847GR RIDGE ;BU
Solar/Wind Harmer
2.709
958481AF2-142 GEN
Solar/Wind Harmer
7.986
274696ROCKY RD ;4P
Adder
6.031
274695ROCKY RD ;2P
Adder
5.892
274693ROCKY RD ;1P
Adder
5.834
274697ROCKY RD ;3P
Adder
1.6
274683WAUKEGAN ;8U
Adder
11.144
274683WAUKEGAN ;8U
Adder
9.394
274764LEE CO EC;5U
Adder
4.784
274765LEE CO EC;6U
Adder
4.784
274762LEE CO EC;3U
Adder
4.773
274763LEE CO EC;4U
Adder
4.728
972267AH1-718 GEN
Adder
2.123
247621Y3-024
Adder
0.12
25326509SID D
Adder
0.655
203947AF1-006 C
Solar/Wind Helper
0.402
203980AG1-197 GEN
Solar/Wind Helper
0.262
203979AG1-198 GEN
Solar/Wind Helper
0.204
241801AE1-079 GEN
Solar/Wind Helper
0.138
241967AE2-285_GEN
Solar/Wind Helper
0.354
241985AE1-237 GEN
Solar/Wind Helper
0.137
962101AG1-054 GEN
Solar/Wind Helper
0.34
946381AF1-302 GEN
Solar/Wind Helper
0.108
238217AF1-153 C O1
Solar/Wind Helper
0.114
274861TOP CROP ;1U
Solar/Wind Harmer
0.294
274862TOP CROP ;2U
Solar/Wind Harmer
0.246
23906502RICHG2&3
50/50
1.747
241832AE2-181_GEN
Solar/Wind Harmer
2.443
958321AF2-126 GEN
Solar/Wind Harmer
1.823
23929302BS-PKR
Adder
1.959
270541AE2-072 C
Solar/Wind Harmer
5.213
270575GUS2 35KV
Solar/Wind Harmer
10.713
970217AG2-149 GEN
Solar/Wind Harmer
26.741
270044AE2-322 C
Solar/Wind Harmer
1.036
270404AC1-167 GEN
Solar/Wind Harmer
0.862
270258AD1-119 GEN
Solar/Wind Harmer
2.11
247604X1-042
Adder
0.302
270588AE1-091_GEN
Solar/Wind Harmer
7.864
24441205WTRV SLR C
Solar/Wind Harmer
0.096
958091AF2-103 GEN
Solar/Wind Harmer
0.114
270491AE1-102 GEN2
Solar/Wind Harmer
0.914
945111AF1-176 GEN
Solar/Wind Harmer
3.77
270191TR4_S_V150
Solar/Wind Harmer
1.971
270247TR4_N_V136
Solar/Wind Harmer
0.559
24642205MAYFLWER
Adder
0.413
970031AG2-029 GEN
Solar/Wind Harmer
19.386
247643Z2-116 C
Solar/Wind Harmer
0.045
959331AF2-224 GEN
Solar/Wind Harmer
6.354
965021AG1-366 GEN
Solar/Wind Harmer
1.478
270485AE1-090_GEN
Solar/Wind Harmer
0.384
270043AE2-236 GEN
Solar/Wind Harmer
3.307
970349AG2-230 GEN
Solar/Wind Harmer
8.916
942871AE2-306 GEN
Solar/Wind Harmer
0.535
270391AF1-285 GEN3
Solar/Wind Harmer
0.274
270535AF1-215 GEN1
Solar/Wind Harmer
2.568
972231SS25-0005
Solar/Wind Harmer
5.294
972181SS23-001
Solar/Wind Harmer
3.309
274752CRETE EC ;2U
Adder
2.727
274753CRETE EC ;3U
Adder
2.727
964401AG1-302 GEN
Solar/Wind Harmer
5.045
274724RIVER EC ;11
Adder
9.806
959141AF2-205 GEN
Solar/Wind Harmer
3.312
274802UNIV PARK;5U
Adder
3.182
274826FISK ;BP
Adder
5.966
274800UNIV PARK;3U
Adder
3.173
972038AH1-567 GEN2
Adder
0.199
276772AC2-154 GEN
Solar/Wind Harmer
1.515
276806AD2-047 C O1
Solar/Wind Harmer
5.813
970941AG2-585 GEN
Solar/Wind Harmer
6.792
274772LINCOLN ;3U
Adder
3.367
972228AH1-698 GEN2
Adder
2.007
274676JOLIET 29;8U
Adder
15.952
276897AD1-100 C
Solar/Wind Harmer
15.633
939351AE1-166 GEN
Solar/Wind Harmer
3.194
276893AG1-478 C
Solar/Wind Harmer
0.225
274729ELWOOD EC;1P
Adder
8.849
274730ELWOOD EC;6P
Adder
8.849
274734ELWOOD EC;8P
Adder
8.849
274736ELWOOD EC;9P
Adder
8.849
970707AG2-453 GEN
Solar/Wind Harmer
15.071
971617AH1-308 GEN
Solar/Wind Harmer
3.125
970513AG2-328 GEN
Solar/Wind Harmer
9.586
970517AG2-330 GEN
Solar/Wind Harmer
8.694
943121AE2-341 GEN
Solar/Wind Harmer
7.988
943591AF1-030 GEN
Solar/Wind Harmer
5.325
276694AA1-018 GEN2
Solar/Wind Harmer
3.36
274682WAUKEGAN ;7U
Adder
9.512
972236AH1-702 GEN2
Adder
1.135
274760LEE CO EC;1U
Adder
4.773
274767LEE CO EC;8U
Adder
4.716
24728705AND G3
Adder
3.588
24728505AND G1
Adder
1.715
962511AG1-100 GEN
Solar/Wind Helper
0.361
203830AF1-094 GEN
Solar/Wind Helper
0.34
959441AF2-235 GEN
Solar/Wind Helper
0.154
254305AE2-115 C
Solar/Wind Helper
0.117
20334926Z1-069 C
Solar/Wind Helper
0.662
23888702TROY G3
50/50
2.643
972253AH1-711 GEN
50/50
80.74
23920202STRYCT
50/50
2.39
24189902OREGON_CT2
50/50
2.177
972301AH1-735 GEN
50/50
8.755
23906402RICHG1
50/50
1.751
23906502RICHG2&3
50/50
1.747
241858AF1-205_GEN
Solar/Wind Harmer
7.001
241808AF1-120 C
Solar/Wind Harmer
1.482
241840AF1-064_GEN
Solar/Wind Harmer
1.7
270361_3
Solar/Wind Harmer
9.093
960841AF2-375 GEN
Solar/Wind Harmer
4.04
970515AG2-329 GEN
Solar/Wind Harmer
12.127
944231AF1-091 GEN
Solar/Wind Harmer
3.014
247522W1-056 GEN
Solar/Wind Harmer
1.754
246936BC-WTG1
Solar/Wind Harmer
2.75
270489AE1-102 GEN1
Solar/Wind Harmer
0.914
965421AG1-410 GEN
Solar/Wind Harmer
20.891
270449AD2-020 GEN
Solar/Wind Harmer
1.906
943021AE2-325 GEN
Solar/Wind Harmer
2.476
24695305TIMB G C
Solar/Wind Harmer
3.74
945111AF1-176 GEN
Solar/Wind Harmer
11.896
270505AE1-170 C O1
Solar/Wind Harmer
9.989
247521TR3_G114
Solar/Wind Harmer
2.21
270246TR4_N_V150
Solar/Wind Harmer
0.559
24639705ELKHART HY
Adder
0.1
270063AE2-323 C
Solar/Wind Harmer
1.43
965011AG1-365 GEN
Solar/Wind Harmer
6.354
270462AD2-086
Solar/Wind Harmer
4.412
270223U2-072_GEN1
Solar/Wind Harmer
1.166
270578AF1-285 GEN2
Solar/Wind Harmer
0.713
270391AF1-285 GEN3
Solar/Wind Harmer
0.713
970373AG2-245 GEN
Solar/Wind Harmer
12.089
270055AF2-134 C O1
Solar/Wind Harmer
1.712
274751CRETE EC ;1U
Adder
2.727
274754CRETE EC ;4U
Adder
2.727
958381AF2-132 GEN
Solar/Wind Harmer
5.045
964861AG1-349 GEN
Solar/Wind Harmer
4.363
971917AH1-482 GEN
Solar/Wind Harmer
5.035
274723RIVER EC ;12
Adder
9.924
274812UNIV PK N;8U
Adder
2.762
276164X3-005 C
Solar/Wind Harmer
0.386
274801UNIV PARK;4U
Adder
3.173
940581AE2-045 GEN
Solar/Wind Harmer
5.542
971605AH1-302 GEN
Solar/Wind Harmer
4.739
276776AD2-060 GEN
Solar/Wind Harmer
0.23
972207SS24-0001
Solar/Wind Harmer
11.973
274773LINCOLN ;4U
Adder
3.367
274774LINCOLN ;5U
Adder
3.367
274676JOLIET 29;8U
Adder
16.543
941551AE2-152 GEN
Solar/Wind Harmer
2.443
274732ELWOOD EC;7P
Adder
8.849
274674JOLIET 9 ;6U
Adder
8.288
970245AG2-165 GEN
Solar/Wind Harmer
9.586
274871GR RIDGE ;2U
Solar/Wind Harmer
4.118
274745AC1-111 GEN9
Adder
2.978
276691AA1-018 GEN1
Solar/Wind Harmer
0.248
274682WAUKEGAN ;7U
Adder
9.512
274828WAUKEGAN ;BP
Adder
5.842
274822ROCKFORD ;11
Adder
10.179
972235AH1-702 GEN1
Adder
1.305
274761LEE CO EC;2U
Adder
4.773
274766LEE CO EC;7U
Adder
4.716
24728605AND G2
Adder
1.715
241885AC2-103 GEN1
Solar/Wind Helper
7.083
241807AE2-176_GEN
Solar/Wind Helper
1.702
961971AG1-040 GEN
Solar/Wind Helper
0.352
203835AF1-098 GEN
Solar/Wind Helper
1.388
203860AG1-193 C
Solar/Wind Helper
0.156
241966AE1-183 GEN
Solar/Wind Helper
0.136
254303AC2-168 GEN
Solar/Wind Helper
0.079
203954AE2-126 C
Solar/Wind Helper
0.223
944201AF1-088_MTX
Adder
0.5
991177J1571 G
External Queue
18.512771606445312
990527J1329
External Queue
2.100818634033203
990142J1224
External Queue
15.356985092163086
991182J1586 G
External Queue
28.40474510192871
LAGNLTFEXP_LAGN->PJM
CLTF
6.243
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.59
TVALTFEXP_TVA->PJM
CLTF
2.868
CPLELTFEXP_CPLE->PJM
CLTF
0.787
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.861
NYPJM->LTFIMP_NY
CLTF
2.006
LGEELTFEXP_LGEE->PJM
CLTF
2.488
WECLTFEXP_WEC->PJM
CLTF
1.978
AG2-052LTFEXP_AG2-052->PJM
LTF
0.127
AH1-155LTFEXP_AH1-155->PJM
LTF
0.19
CBM West 1LTFEXP_CBM-W1->PJM
CBM
107.194
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.28
MECLTFEXP_MEC->PJM
CLTF
7.783
SIGELTFEXP_SIGE->PJM
CLTF
0.206

Details for 02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line l/o ATSI_P2-3_TE-345-005_SRT-SL


Base Case Flowgate

Area:ATSI
Facility Description:
02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_TE-345-005_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:118.2 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:2219.73
MW Contribution:15.24
Bus #Bus NameTypeMW Contribution
23888502TROY G1
50/50
2.643
23888602TROY G2
50/50
2.643
972211AH1-690 GEN
50/50
234.282
23906902RICHG6
50/50
1.04
23906702RICHG4
50/50
1.037
23906802RICHG5
50/50
0.758
970817AG2-515 GEN
Solar/Wind Harmer
20.606
945411AF1-206 GEN
Solar/Wind Harmer
9.927
945641AF1-229 GEN
Solar/Wind Harmer
4.111
270499AE1-146 GEN
Solar/Wind Harmer
2.56
971549AH1-272 GEN
Solar/Wind Harmer
15.243
270297AD1-101 GEN
Solar/Wind Harmer
2.274
247607V1-011 GEN
Solar/Wind Harmer
2.793
957201AF2-014 GEN
Solar/Wind Harmer
3.188
270435AC2-044 GEN
Solar/Wind Harmer
1.406
944161AF1-084 GEN
Solar/Wind Harmer
1.521
966831AG1-554 GEN
Solar/Wind Harmer
0.805
971989AH1-539 GEN
Solar/Wind Harmer
8.703
965041AG1-368 GEN
Solar/Wind Harmer
6.611
965051AG1-369 GEN
Solar/Wind Harmer
3.281
971771AH1-392 GEN
Solar/Wind Harmer
5.706
270302AB2-170 GEN
Solar/Wind Harmer
5.304
270317AD1-130_GEN
Solar/Wind Harmer
2.033
971769AH1-391 GEN
Solar/Wind Harmer
6.189
971567AH1-282 GEN
Solar/Wind Harmer
9.111
960681AF2-359 GEN
Solar/Wind Harmer
2.255
971347AH1-153 GEN
Solar/Wind Harmer
8.916
963791AG1-232 GEN
Solar/Wind Harmer
7.982
270578AF1-285 GEN2
Solar/Wind Harmer
0.274
270536AF1-215 GEN2
Solar/Wind Harmer
2.568
270071AF1-092 GEN
Solar/Wind Harmer
8.419
274814UNIV PK N;0U
Adder
2.786
274807UNIV PK N;3U
Adder
2.78
274805UNIV PK N;1U
Adder
2.768
274811UNIV PK N;7U
Adder
2.762
958391AF2-133 GEN
Solar/Wind Harmer
5.002
972037AH1-567 GEN1
Adder
0.1
274827FISK ;RP
Adder
4.228
960591AF2-350 GEN
Solar/Wind Harmer
5.434
274775LINCOLN ;6U
Adder
3.367
274776LINCOLN ;7U
Adder
3.367
274777LINCOLN ;8U
Adder
3.367
972227AH1-698 GEN1
Adder
1.413
274687WILL CNTY;4U
Adder
15.095
274687WILL CNTY;4U
Adder
15.095
274675JOLIET 29;7U
Adder
16.543
274675JOLIET 29;7U
Adder
15.952
274731ELWOOD EC;2P
Adder
8.848
274733ELWOOD EC;3P
Adder
8.848
274735ELWOOD EC;4P
Adder
8.848
274728ELWOOD EC;5P
Adder
8.849
270024AE2-089 GEN
Solar/Wind Harmer
2.523
970833AG2-524 GEN
Solar/Wind Harmer
4.678
970833AG2-524 GEN
Solar/Wind Harmer
2.176
274746AC1-111 G10
Adder
2.978
274744AC1-111 GEN8
Adder
2.978
24729505KEY G4
Adder
3.405
274823ROCKFORD ;21
Adder
10.105
241886AC2-103 GEN2
Solar/Wind Helper
7.083
241982AE2-343 S C
Solar/Wind Helper
0.123
254304AE2-114 C
Solar/Wind Helper
0.117
203846AF2-130 C
Solar/Wind Helper
0.257
241997AF1-093 GEN
Solar/Wind Helper
0.136
23888802TROY G4
50/50
2.643
24190002OREGON_ST1
50/50
2.928
24189802OREGON_CT1
50/50
2.221
241996AE2-282_GEN
Solar/Wind Harmer
2.658
971677AH1-339 GEN
Solar/Wind Harmer
7.271
270007AE1-245 C
Solar/Wind Harmer
4.19
942801AE2-298 GEN
Solar/Wind Harmer
1.064
246938BC-WTG3
Solar/Wind Harmer
2.798
246937BC-WTG2
Solar/Wind Harmer
2.75
961051AF2-396 GEN
Solar/Wind Harmer
10.715
961051AF2-396 GEN
Solar/Wind Harmer
4.984
960981AF2-389 GEN
Solar/Wind Harmer
1.004
957891AF2-083 GEN
Solar/Wind Harmer
2.24
247620Y3-023
Adder
0.301
270216AD2-079_GEN
Solar/Wind Harmer
0.39
970611AG2-400 GEN
Solar/Wind Harmer
6.354
270526AF1-158 GEN
Solar/Wind Harmer
2.826
24441505OLIV SLR
Solar/Wind Harmer
0.083
965681AG1-436 GEN
Solar/Wind Harmer
7.46
965791AG1-447 GEN
Solar/Wind Harmer
3.817
270224U2-072_GEN2
Solar/Wind Harmer
1.166
270227U2-072_GEN3
Solar/Wind Harmer
1.166
270228U2-072_GEN4
Solar/Wind Harmer
1.166
270231U2-072_GEN5
Solar/Wind Harmer
1.166
274808UNIV PK N;4U
Adder
2.75
274803UNIV PARK;6U
Adder
3.182
942221AE2-234 GEN
Solar/Wind Harmer
0.398
274888KELLY CRK;1U
Solar/Wind Harmer
3.208
274887GEN-1.85
Solar/Wind Harmer
2.896
276843GEN-1.7
Solar/Wind Harmer
0.312
958011AF2-095 GEN
Solar/Wind Harmer
7.825
274770LINCOLN ;1U
Adder
3.367
274771LINCOLN ;2U
Adder
3.367
972259AH1-714 GEN
Adder
10.294
274674JOLIET 9 ;6U
Adder
8.288
970321AG2-212 GEN
Solar/Wind Harmer
9.586
274847GR RIDGE ;BU
Solar/Wind Harmer
2.709
958481AF2-142 GEN
Solar/Wind Harmer
7.986
274695ROCKY RD ;2P
Adder
5.891
274693ROCKY RD ;1P
Adder
5.833
274697ROCKY RD ;3P
Adder
1.6
274696ROCKY RD ;4P
Adder
6.03
274683WAUKEGAN ;8U
Adder
11.144
274683WAUKEGAN ;8U
Adder
9.394
274764LEE CO EC;5U
Adder
4.784
274765LEE CO EC;6U
Adder
4.784
274762LEE CO EC;3U
Adder
4.772
274763LEE CO EC;4U
Adder
4.727
972267AH1-718 GEN
Adder
2.123
23906502RICHG2&3
50/50
1.747
241832AE2-181_GEN
Solar/Wind Harmer
2.444
958321AF2-126 GEN
Solar/Wind Harmer
1.823
23929302BS-PKR
Adder
1.959
270541AE2-072 C
Solar/Wind Harmer
5.213
270575GUS2 35KV
Solar/Wind Harmer
10.713
970217AG2-149 GEN
Solar/Wind Harmer
26.74
270044AE2-322 C
Solar/Wind Harmer
1.036
270404AC1-167 GEN
Solar/Wind Harmer
0.862
270258AD1-119 GEN
Solar/Wind Harmer
2.11
247604X1-042
Adder
0.302
270588AE1-091_GEN
Solar/Wind Harmer
7.864
24441205WTRV SLR C
Solar/Wind Harmer
0.096
958091AF2-103 GEN
Solar/Wind Harmer
0.114
270491AE1-102 GEN2
Solar/Wind Harmer
0.914
945111AF1-176 GEN
Solar/Wind Harmer
3.77
270191TR4_S_V150
Solar/Wind Harmer
1.971
270247TR4_N_V136
Solar/Wind Harmer
0.559
24642205MAYFLWER
Adder
0.413
970031AG2-029 GEN
Solar/Wind Harmer
19.386
247643Z2-116 C
Solar/Wind Harmer
0.045
959331AF2-224 GEN
Solar/Wind Harmer
6.354
965021AG1-366 GEN
Solar/Wind Harmer
1.478
270485AE1-090_GEN
Solar/Wind Harmer
0.384
270043AE2-236 GEN
Solar/Wind Harmer
3.307
970349AG2-230 GEN
Solar/Wind Harmer
8.916
942871AE2-306 GEN
Solar/Wind Harmer
0.535
270391AF1-285 GEN3
Solar/Wind Harmer
0.274
270535AF1-215 GEN1
Solar/Wind Harmer
2.568
972231SS25-0005
Solar/Wind Harmer
5.294
972181SS23-001
Solar/Wind Harmer
3.309
274752CRETE EC ;2U
Adder
2.727
274753CRETE EC ;3U
Adder
2.727
964401AG1-302 GEN
Solar/Wind Harmer
5.044
274724RIVER EC ;11
Adder
9.806
959141AF2-205 GEN
Solar/Wind Harmer
3.312
274802UNIV PARK;5U
Adder
3.182
274826FISK ;BP
Adder
5.966
274800UNIV PARK;3U
Adder
3.173
972038AH1-567 GEN2
Adder
0.199
276772AC2-154 GEN
Solar/Wind Harmer
1.515
276806AD2-047 C O1
Solar/Wind Harmer
5.813
970941AG2-585 GEN
Solar/Wind Harmer
6.792
274772LINCOLN ;3U
Adder
3.367
972228AH1-698 GEN2
Adder
2.007
274676JOLIET 29;8U
Adder
15.952
276897AD1-100 C
Solar/Wind Harmer
15.632
939351AE1-166 GEN
Solar/Wind Harmer
3.194
276893AG1-478 C
Solar/Wind Harmer
0.225
274729ELWOOD EC;1P
Adder
8.848
274730ELWOOD EC;6P
Adder
8.849
274734ELWOOD EC;8P
Adder
8.849
274736ELWOOD EC;9P
Adder
8.849
970707AG2-453 GEN
Solar/Wind Harmer
15.071
971617AH1-308 GEN
Solar/Wind Harmer
3.125
970513AG2-328 GEN
Solar/Wind Harmer
9.586
970517AG2-330 GEN
Solar/Wind Harmer
8.694
943121AE2-341 GEN
Solar/Wind Harmer
7.988
943591AF1-030 GEN
Solar/Wind Harmer
5.325
276694AA1-018 GEN2
Solar/Wind Harmer
3.36
274682WAUKEGAN ;7U
Adder
9.512
972236AH1-702 GEN2
Adder
1.135
274760LEE CO EC;1U
Adder
4.772
274767LEE CO EC;8U
Adder
4.716
24728705AND G3
Adder
3.588
24728505AND G1
Adder
1.715
962511AG1-100 GEN
Solar/Wind Helper
0.361
203830AF1-094 GEN
Solar/Wind Helper
0.34
959441AF2-235 GEN
Solar/Wind Helper
0.154
254305AE2-115 C
Solar/Wind Helper
0.117
20334926Z1-069 C
Solar/Wind Helper
0.662
247621Y3-024
Adder
0.12
25326509SID D
Adder
0.655
203947AF1-006 C
Solar/Wind Helper
0.402
203980AG1-197 GEN
Solar/Wind Helper
0.262
203979AG1-198 GEN
Solar/Wind Helper
0.204
241967AE2-285_GEN
Solar/Wind Helper
0.354
241801AE1-079 GEN
Solar/Wind Helper
0.138
241985AE1-237 GEN
Solar/Wind Helper
0.137
962101AG1-054 GEN
Solar/Wind Helper
0.34
946381AF1-302 GEN
Solar/Wind Helper
0.108
238217AF1-153 C O1
Solar/Wind Helper
0.114
274861TOP CROP ;1U
Solar/Wind Harmer
0.294
274862TOP CROP ;2U
Solar/Wind Harmer
0.246
203804AE2-113_GEN
Solar/Wind Helper
0.892
23888702TROY G3
50/50
2.643
972253AH1-711 GEN
50/50
80.741
23920202STRYCT
50/50
2.39
24189902OREGON_CT2
50/50
2.176
972301AH1-735 GEN
50/50
8.755
23906402RICHG1
50/50
1.751
23906502RICHG2&3
50/50
1.747
241858AF1-205_GEN
Solar/Wind Harmer
7.002
241808AF1-120 C
Solar/Wind Harmer
1.482
241840AF1-064_GEN
Solar/Wind Harmer
1.7
270361_3
Solar/Wind Harmer
9.093
960841AF2-375 GEN
Solar/Wind Harmer
4.04
970515AG2-329 GEN
Solar/Wind Harmer
12.126
944231AF1-091 GEN
Solar/Wind Harmer
3.014
247522W1-056 GEN
Solar/Wind Harmer
1.754
246936BC-WTG1
Solar/Wind Harmer
2.75
270489AE1-102 GEN1
Solar/Wind Harmer
0.914
965421AG1-410 GEN
Solar/Wind Harmer
20.891
270449AD2-020 GEN
Solar/Wind Harmer
1.906
943021AE2-325 GEN
Solar/Wind Harmer
2.476
24695305TIMB G C
Solar/Wind Harmer
3.74
945111AF1-176 GEN
Solar/Wind Harmer
11.896
270505AE1-170 C O1
Solar/Wind Harmer
9.988
247521TR3_G114
Solar/Wind Harmer
2.21
270246TR4_N_V150
Solar/Wind Harmer
0.559
24639705ELKHART HY
Adder
0.1
270063AE2-323 C
Solar/Wind Harmer
1.43
965011AG1-365 GEN
Solar/Wind Harmer
6.354
270462AD2-086
Solar/Wind Harmer
4.412
270223U2-072_GEN1
Solar/Wind Harmer
1.166
270578AF1-285 GEN2
Solar/Wind Harmer
0.713
270391AF1-285 GEN3
Solar/Wind Harmer
0.713
970373AG2-245 GEN
Solar/Wind Harmer
12.088
270055AF2-134 C O1
Solar/Wind Harmer
1.712
274751CRETE EC ;1U
Adder
2.727
274754CRETE EC ;4U
Adder
2.727
958381AF2-132 GEN
Solar/Wind Harmer
5.044
964861AG1-349 GEN
Solar/Wind Harmer
4.363
971917AH1-482 GEN
Solar/Wind Harmer
5.035
274723RIVER EC ;12
Adder
9.924
274812UNIV PK N;8U
Adder
2.762
276164X3-005 C
Solar/Wind Harmer
0.386
274801UNIV PARK;4U
Adder
3.173
940581AE2-045 GEN
Solar/Wind Harmer
5.542
971605AH1-302 GEN
Solar/Wind Harmer
4.739
276776AD2-060 GEN
Solar/Wind Harmer
0.23
972207SS24-0001
Solar/Wind Harmer
11.973
274773LINCOLN ;4U
Adder
3.367
274774LINCOLN ;5U
Adder
3.367
274676JOLIET 29;8U
Adder
16.543
941551AE2-152 GEN
Solar/Wind Harmer
2.443
274732ELWOOD EC;7P
Adder
8.849
274674JOLIET 9 ;6U
Adder
8.288
970245AG2-165 GEN
Solar/Wind Harmer
9.586
274871GR RIDGE ;2U
Solar/Wind Harmer
4.118
274745AC1-111 GEN9
Adder
2.978
276691AA1-018 GEN1
Solar/Wind Harmer
0.248
274682WAUKEGAN ;7U
Adder
9.512
274828WAUKEGAN ;BP
Adder
5.841
274822ROCKFORD ;11
Adder
10.179
972235AH1-702 GEN1
Adder
1.305
274761LEE CO EC;2U
Adder
4.772
274766LEE CO EC;7U
Adder
4.716
24728605AND G2
Adder
1.715
241885AC2-103 GEN1
Solar/Wind Helper
7.083
241807AE2-176_GEN
Solar/Wind Helper
1.701
961971AG1-040 GEN
Solar/Wind Helper
0.352
203835AF1-098 GEN
Solar/Wind Helper
1.388
203860AG1-193 C
Solar/Wind Helper
0.156
241966AE1-183 GEN
Solar/Wind Helper
0.136
254303AC2-168 GEN
Solar/Wind Helper
0.079
203954AE2-126 C
Solar/Wind Helper
0.223
944201AF1-088_MTX
Adder
0.5
991177J1571 G
External Queue
18.513126373291016
990527J1329
External Queue
2.100800037384033
990142J1224
External Queue
15.35684871673584
991182J1586 G
External Queue
28.404245376586914
LAGNLTFEXP_LAGN->PJM
CLTF
6.243
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.59
TVALTFEXP_TVA->PJM
CLTF
2.868
CPLELTFEXP_CPLE->PJM
CLTF
0.787
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.86
NYPJM->LTFIMP_NY
CLTF
2.006
LGEELTFEXP_LGEE->PJM
CLTF
2.487
WECLTFEXP_WEC->PJM
CLTF
1.978
AG2-052LTFEXP_AG2-052->PJM
LTF
0.127
AH1-155LTFEXP_AH1-155->PJM
LTF
0.19
CBM West 1LTFEXP_CBM-W1->PJM
CBM
107.191
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.28
MECLTFEXP_MEC->PJM
CLTF
7.783
SIGELTFEXP_SIGE->PJM
CLTF
0.206

Details for 02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line l/o ATSI_P2-3_TE-345-006_SRT-SL


Base Case Flowgate

Area:ATSI
Facility Description:
02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_TE-345-006_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:118.2 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:2219.73
MW Contribution:15.24
Bus #Bus NameTypeMW Contribution
23906502RICHG2&3
50/50
1.747
241832AE2-181_GEN
Solar/Wind Harmer
2.444
958321AF2-126 GEN
Solar/Wind Harmer
1.823
23929302BS-PKR
Adder
1.959
270541AE2-072 C
Solar/Wind Harmer
5.213
270575GUS2 35KV
Solar/Wind Harmer
10.713
970217AG2-149 GEN
Solar/Wind Harmer
26.74
270044AE2-322 C
Solar/Wind Harmer
1.036
270404AC1-167 GEN
Solar/Wind Harmer
0.862
270258AD1-119 GEN
Solar/Wind Harmer
2.11
247604X1-042
Adder
0.302
270588AE1-091_GEN
Solar/Wind Harmer
7.864
24441205WTRV SLR C
Solar/Wind Harmer
0.096
958091AF2-103 GEN
Solar/Wind Harmer
0.114
270491AE1-102 GEN2
Solar/Wind Harmer
0.914
945111AF1-176 GEN
Solar/Wind Harmer
3.77
270191TR4_S_V150
Solar/Wind Harmer
1.971
270247TR4_N_V136
Solar/Wind Harmer
0.559
24642205MAYFLWER
Adder
0.413
970031AG2-029 GEN
Solar/Wind Harmer
19.386
247643Z2-116 C
Solar/Wind Harmer
0.045
959331AF2-224 GEN
Solar/Wind Harmer
6.354
965021AG1-366 GEN
Solar/Wind Harmer
1.478
270485AE1-090_GEN
Solar/Wind Harmer
0.384
270043AE2-236 GEN
Solar/Wind Harmer
3.307
970349AG2-230 GEN
Solar/Wind Harmer
8.916
942871AE2-306 GEN
Solar/Wind Harmer
0.535
270391AF1-285 GEN3
Solar/Wind Harmer
0.274
270535AF1-215 GEN1
Solar/Wind Harmer
2.568
972231SS25-0005
Solar/Wind Harmer
5.294
972181SS23-001
Solar/Wind Harmer
3.309
274752CRETE EC ;2U
Adder
2.727
274753CRETE EC ;3U
Adder
2.727
964401AG1-302 GEN
Solar/Wind Harmer
5.044
274724RIVER EC ;11
Adder
9.806
959141AF2-205 GEN
Solar/Wind Harmer
3.312
274802UNIV PARK;5U
Adder
3.182
274826FISK ;BP
Adder
5.966
274800UNIV PARK;3U
Adder
3.173
972038AH1-567 GEN2
Adder
0.199
276772AC2-154 GEN
Solar/Wind Harmer
1.515
276806AD2-047 C O1
Solar/Wind Harmer
5.813
970941AG2-585 GEN
Solar/Wind Harmer
6.792
274772LINCOLN ;3U
Adder
3.367
972228AH1-698 GEN2
Adder
2.007
274676JOLIET 29;8U
Adder
15.952
276897AD1-100 C
Solar/Wind Harmer
15.632
939351AE1-166 GEN
Solar/Wind Harmer
3.194
276893AG1-478 C
Solar/Wind Harmer
0.225
274729ELWOOD EC;1P
Adder
8.848
274730ELWOOD EC;6P
Adder
8.849
274734ELWOOD EC;8P
Adder
8.849
274736ELWOOD EC;9P
Adder
8.849
970707AG2-453 GEN
Solar/Wind Harmer
15.071
971617AH1-308 GEN
Solar/Wind Harmer
3.125
970513AG2-328 GEN
Solar/Wind Harmer
9.586
970517AG2-330 GEN
Solar/Wind Harmer
8.694
943121AE2-341 GEN
Solar/Wind Harmer
7.988
943591AF1-030 GEN
Solar/Wind Harmer
5.325
276694AA1-018 GEN2
Solar/Wind Harmer
3.36
274682WAUKEGAN ;7U
Adder
9.512
972236AH1-702 GEN2
Adder
1.135
274760LEE CO EC;1U
Adder
4.772
274767LEE CO EC;8U
Adder
4.716
24728705AND G3
Adder
3.588
24728505AND G1
Adder
1.715
962511AG1-100 GEN
Solar/Wind Helper
0.361
203830AF1-094 GEN
Solar/Wind Helper
0.34
959441AF2-235 GEN
Solar/Wind Helper
0.154
254305AE2-115 C
Solar/Wind Helper
0.117
20334926Z1-069 C
Solar/Wind Helper
0.662
23888802TROY G4
50/50
2.643
24190002OREGON_ST1
50/50
2.928
24189802OREGON_CT1
50/50
2.221
241996AE2-282_GEN
Solar/Wind Harmer
2.658
971677AH1-339 GEN
Solar/Wind Harmer
7.271
270007AE1-245 C
Solar/Wind Harmer
4.19
942801AE2-298 GEN
Solar/Wind Harmer
1.064
246938BC-WTG3
Solar/Wind Harmer
2.798
246937BC-WTG2
Solar/Wind Harmer
2.75
961051AF2-396 GEN
Solar/Wind Harmer
10.715
961051AF2-396 GEN
Solar/Wind Harmer
4.984
960981AF2-389 GEN
Solar/Wind Harmer
1.004
957891AF2-083 GEN
Solar/Wind Harmer
2.24
247620Y3-023
Adder
0.301
270216AD2-079_GEN
Solar/Wind Harmer
0.39
970611AG2-400 GEN
Solar/Wind Harmer
6.354
270526AF1-158 GEN
Solar/Wind Harmer
2.826
24441505OLIV SLR
Solar/Wind Harmer
0.083
965681AG1-436 GEN
Solar/Wind Harmer
7.46
965791AG1-447 GEN
Solar/Wind Harmer
3.817
270224U2-072_GEN2
Solar/Wind Harmer
1.166
270227U2-072_GEN3
Solar/Wind Harmer
1.166
270228U2-072_GEN4
Solar/Wind Harmer
1.166
270231U2-072_GEN5
Solar/Wind Harmer
1.166
274808UNIV PK N;4U
Adder
2.75
274803UNIV PARK;6U
Adder
3.182
942221AE2-234 GEN
Solar/Wind Harmer
0.398
274888KELLY CRK;1U
Solar/Wind Harmer
3.208
274887GEN-1.85
Solar/Wind Harmer
2.896
276843GEN-1.7
Solar/Wind Harmer
0.312
958011AF2-095 GEN
Solar/Wind Harmer
7.825
274770LINCOLN ;1U
Adder
3.367
274771LINCOLN ;2U
Adder
3.367
972259AH1-714 GEN
Adder
10.294
274674JOLIET 9 ;6U
Adder
8.288
970321AG2-212 GEN
Solar/Wind Harmer
9.586
274847GR RIDGE ;BU
Solar/Wind Harmer
2.709
958481AF2-142 GEN
Solar/Wind Harmer
7.986
274695ROCKY RD ;2P
Adder
5.891
274693ROCKY RD ;1P
Adder
5.833
274697ROCKY RD ;3P
Adder
1.6
274696ROCKY RD ;4P
Adder
6.03
274683WAUKEGAN ;8U
Adder
11.144
274683WAUKEGAN ;8U
Adder
9.394
274764LEE CO EC;5U
Adder
4.784
274765LEE CO EC;6U
Adder
4.784
274762LEE CO EC;3U
Adder
4.772
274763LEE CO EC;4U
Adder
4.727
972267AH1-718 GEN
Adder
2.123
247621Y3-024
Adder
0.12
25326509SID D
Adder
0.655
203947AF1-006 C
Solar/Wind Helper
0.402
203980AG1-197 GEN
Solar/Wind Helper
0.262
203979AG1-198 GEN
Solar/Wind Helper
0.204
241967AE2-285_GEN
Solar/Wind Helper
0.354
241801AE1-079 GEN
Solar/Wind Helper
0.138
241985AE1-237 GEN
Solar/Wind Helper
0.137
962101AG1-054 GEN
Solar/Wind Helper
0.34
946381AF1-302 GEN
Solar/Wind Helper
0.108
238217AF1-153 C O1
Solar/Wind Helper
0.114
274861TOP CROP ;1U
Solar/Wind Harmer
0.294
274862TOP CROP ;2U
Solar/Wind Harmer
0.246
23888502TROY G1
50/50
2.643
23888602TROY G2
50/50
2.643
972211AH1-690 GEN
50/50
234.282
23906902RICHG6
50/50
1.04
23906702RICHG4
50/50
1.037
23906802RICHG5
50/50
0.758
970817AG2-515 GEN
Solar/Wind Harmer
20.606
945411AF1-206 GEN
Solar/Wind Harmer
9.927
945641AF1-229 GEN
Solar/Wind Harmer
4.111
270499AE1-146 GEN
Solar/Wind Harmer
2.56
971549AH1-272 GEN
Solar/Wind Harmer
15.243
270297AD1-101 GEN
Solar/Wind Harmer
2.274
247607V1-011 GEN
Solar/Wind Harmer
2.793
957201AF2-014 GEN
Solar/Wind Harmer
3.188
270435AC2-044 GEN
Solar/Wind Harmer
1.406
944161AF1-084 GEN
Solar/Wind Harmer
1.521
966831AG1-554 GEN
Solar/Wind Harmer
0.805
971989AH1-539 GEN
Solar/Wind Harmer
8.703
965041AG1-368 GEN
Solar/Wind Harmer
6.611
965051AG1-369 GEN
Solar/Wind Harmer
3.281
971771AH1-392 GEN
Solar/Wind Harmer
5.706
270302AB2-170 GEN
Solar/Wind Harmer
5.304
270317AD1-130_GEN
Solar/Wind Harmer
2.033
971769AH1-391 GEN
Solar/Wind Harmer
6.189
971567AH1-282 GEN
Solar/Wind Harmer
9.111
960681AF2-359 GEN
Solar/Wind Harmer
2.255
971347AH1-153 GEN
Solar/Wind Harmer
8.916
963791AG1-232 GEN
Solar/Wind Harmer
7.982
270578AF1-285 GEN2
Solar/Wind Harmer
0.274
270536AF1-215 GEN2
Solar/Wind Harmer
2.568
270071AF1-092 GEN
Solar/Wind Harmer
8.419
274814UNIV PK N;0U
Adder
2.786
274807UNIV PK N;3U
Adder
2.78
274805UNIV PK N;1U
Adder
2.768
274811UNIV PK N;7U
Adder
2.762
958391AF2-133 GEN
Solar/Wind Harmer
5.002
972037AH1-567 GEN1
Adder
0.1
274827FISK ;RP
Adder
4.228
960591AF2-350 GEN
Solar/Wind Harmer
5.434
274775LINCOLN ;6U
Adder
3.367
274776LINCOLN ;7U
Adder
3.367
274777LINCOLN ;8U
Adder
3.367
972227AH1-698 GEN1
Adder
1.413
274687WILL CNTY;4U
Adder
15.095
274687WILL CNTY;4U
Adder
15.095
274675JOLIET 29;7U
Adder
16.543
274675JOLIET 29;7U
Adder
15.952
274731ELWOOD EC;2P
Adder
8.848
274733ELWOOD EC;3P
Adder
8.848
274735ELWOOD EC;4P
Adder
8.848
274728ELWOOD EC;5P
Adder
8.849
270024AE2-089 GEN
Solar/Wind Harmer
2.523
970833AG2-524 GEN
Solar/Wind Harmer
4.678
970833AG2-524 GEN
Solar/Wind Harmer
2.176
274746AC1-111 G10
Adder
2.978
274744AC1-111 GEN8
Adder
2.978
24729505KEY G4
Adder
3.405
274823ROCKFORD ;21
Adder
10.105
241886AC2-103 GEN2
Solar/Wind Helper
7.083
241982AE2-343 S C
Solar/Wind Helper
0.123
254304AE2-114 C
Solar/Wind Helper
0.117
203846AF2-130 C
Solar/Wind Helper
0.257
241997AF1-093 GEN
Solar/Wind Helper
0.136
203804AE2-113_GEN
Solar/Wind Helper
0.892
23888702TROY G3
50/50
2.643
972253AH1-711 GEN
50/50
80.741
23920202STRYCT
50/50
2.39
24189902OREGON_CT2
50/50
2.176
972301AH1-735 GEN
50/50
8.755
23906402RICHG1
50/50
1.751
23906502RICHG2&3
50/50
1.747
241858AF1-205_GEN
Solar/Wind Harmer
7.002
241808AF1-120 C
Solar/Wind Harmer
1.482
241840AF1-064_GEN
Solar/Wind Harmer
1.7
270361_3
Solar/Wind Harmer
9.093
960841AF2-375 GEN
Solar/Wind Harmer
4.04
970515AG2-329 GEN
Solar/Wind Harmer
12.126
944231AF1-091 GEN
Solar/Wind Harmer
3.014
247522W1-056 GEN
Solar/Wind Harmer
1.754
246936BC-WTG1
Solar/Wind Harmer
2.75
270489AE1-102 GEN1
Solar/Wind Harmer
0.914
965421AG1-410 GEN
Solar/Wind Harmer
20.891
270449AD2-020 GEN
Solar/Wind Harmer
1.906
943021AE2-325 GEN
Solar/Wind Harmer
2.476
24695305TIMB G C
Solar/Wind Harmer
3.74
945111AF1-176 GEN
Solar/Wind Harmer
11.896
270505AE1-170 C O1
Solar/Wind Harmer
9.988
247521TR3_G114
Solar/Wind Harmer
2.21
270246TR4_N_V150
Solar/Wind Harmer
0.559
24639705ELKHART HY
Adder
0.1
270063AE2-323 C
Solar/Wind Harmer
1.43
965011AG1-365 GEN
Solar/Wind Harmer
6.354
270462AD2-086
Solar/Wind Harmer
4.412
270223U2-072_GEN1
Solar/Wind Harmer
1.166
270578AF1-285 GEN2
Solar/Wind Harmer
0.713
270391AF1-285 GEN3
Solar/Wind Harmer
0.713
970373AG2-245 GEN
Solar/Wind Harmer
12.088
270055AF2-134 C O1
Solar/Wind Harmer
1.712
274751CRETE EC ;1U
Adder
2.727
274754CRETE EC ;4U
Adder
2.727
958381AF2-132 GEN
Solar/Wind Harmer
5.044
964861AG1-349 GEN
Solar/Wind Harmer
4.363
971917AH1-482 GEN
Solar/Wind Harmer
5.035
274723RIVER EC ;12
Adder
9.924
274812UNIV PK N;8U
Adder
2.762
276164X3-005 C
Solar/Wind Harmer
0.386
274801UNIV PARK;4U
Adder
3.173
940581AE2-045 GEN
Solar/Wind Harmer
5.542
971605AH1-302 GEN
Solar/Wind Harmer
4.739
276776AD2-060 GEN
Solar/Wind Harmer
0.23
972207SS24-0001
Solar/Wind Harmer
11.973
274773LINCOLN ;4U
Adder
3.367
274774LINCOLN ;5U
Adder
3.367
274676JOLIET 29;8U
Adder
16.543
941551AE2-152 GEN
Solar/Wind Harmer
2.443
274732ELWOOD EC;7P
Adder
8.849
274674JOLIET 9 ;6U
Adder
8.288
970245AG2-165 GEN
Solar/Wind Harmer
9.586
274871GR RIDGE ;2U
Solar/Wind Harmer
4.118
274745AC1-111 GEN9
Adder
2.978
276691AA1-018 GEN1
Solar/Wind Harmer
0.248
274682WAUKEGAN ;7U
Adder
9.512
274828WAUKEGAN ;BP
Adder
5.841
274822ROCKFORD ;11
Adder
10.179
972235AH1-702 GEN1
Adder
1.305
274761LEE CO EC;2U
Adder
4.772
274766LEE CO EC;7U
Adder
4.716
24728605AND G2
Adder
1.715
241885AC2-103 GEN1
Solar/Wind Helper
7.083
241807AE2-176_GEN
Solar/Wind Helper
1.701
961971AG1-040 GEN
Solar/Wind Helper
0.352
203835AF1-098 GEN
Solar/Wind Helper
1.388
203860AG1-193 C
Solar/Wind Helper
0.156
241966AE1-183 GEN
Solar/Wind Helper
0.136
254303AC2-168 GEN
Solar/Wind Helper
0.079
203954AE2-126 C
Solar/Wind Helper
0.223
944201AF1-088_MTX
Adder
0.5
991177J1571 G
External Queue
18.513126373291016
990527J1329
External Queue
2.100800037384033
990142J1224
External Queue
15.35684871673584
991182J1586 G
External Queue
28.404245376586914
LAGNLTFEXP_LAGN->PJM
CLTF
6.243
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.59
TVALTFEXP_TVA->PJM
CLTF
2.868
CPLELTFEXP_CPLE->PJM
CLTF
0.787
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.86
NYPJM->LTFIMP_NY
CLTF
2.006
LGEELTFEXP_LGEE->PJM
CLTF
2.487
WECLTFEXP_WEC->PJM
CLTF
1.978
AG2-052LTFEXP_AG2-052->PJM
LTF
0.127
AH1-155LTFEXP_AH1-155->PJM
LTF
0.19
CBM West 1LTFEXP_CBM-W1->PJM
CBM
107.191
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.28
MECLTFEXP_MEC->PJM
CLTF
7.783
SIGELTFEXP_SIGE->PJM
CLTF
0.206

Details for 02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line l/o ATSI_P1-2_TE-345-601_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_TE-345-601_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.99 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:2140.73
MW Contribution:11.87
Bus #Bus NameTypeMW Contribution
23888702TROY G3
50/50
2.643
972253AH1-711 GEN
50/50
80.741
23920202STRYCT
50/50
2.39
24189902OREGON_CT2
50/50
2.176
972301AH1-735 GEN
50/50
8.755
23906402RICHG1
50/50
1.751
23906502RICHG2&3
50/50
1.747
241858AF1-205_GEN
Solar/Wind Harmer
4.885
241808AF1-120 C
Solar/Wind Harmer
0.004
241840AF1-064_GEN
Solar/Wind Harmer
0.005
270361_3
Solar/Wind Harmer
4.971
960841AF2-375 GEN
Solar/Wind Harmer
-0.002
970515AG2-329 GEN
Solar/Wind Harmer
15.158
944231AF1-091 GEN
Solar/Wind Harmer
1.488
247522W1-056 GEN
Solar/Wind Harmer
0.001
246936BC-WTG1
Solar/Wind Harmer
0.199
270489AE1-102 GEN1
Solar/Wind Harmer
0.637
965421AG1-410 GEN
Solar/Wind Harmer
14.575
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.476
24695305TIMB G C
Solar/Wind Harmer
0.001
945111AF1-176 GEN
Solar/Wind Harmer
8.299
270505AE1-170 C O1
Solar/Wind Harmer
4.878
247521TR3_G114
Solar/Wind Harmer
0.167
270246TR4_N_V150
Solar/Wind Harmer
0.03
24639705ELKHART HY
Adder
0.1
270063AE2-323 C
Solar/Wind Harmer
0.004
23888502TROY G1
50/50
2.643
23888602TROY G2
50/50
2.643
972211AH1-690 GEN
50/50
234.282
23906902RICHG6
50/50
1.04
23906702RICHG4
50/50
1.037
23906802RICHG5
50/50
0.758
970817AG2-515 GEN
Solar/Wind Harmer
14.376
945411AF1-206 GEN
Solar/Wind Harmer
-0.001
945641AF1-229 GEN
Solar/Wind Harmer
0.001
270499AE1-146 GEN
Solar/Wind Harmer
0.032
971549AH1-272 GEN
Solar/Wind Harmer
11.871
270297AD1-101 GEN
Solar/Wind Harmer
0.001
247607V1-011 GEN
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.621
23888802TROY G4
50/50
2.643
24190002OREGON_ST1
50/50
2.928
24189802OREGON_CT1
50/50
2.221
241996AE2-282_GEN
Solar/Wind Harmer
0.007
971677AH1-339 GEN
Solar/Wind Harmer
0.714
970621AG2-405 GEN
Solar/Wind Harmer
1.043
970623AG2-406 GEN
Solar/Wind Harmer
0.966
270007AE1-245 C
Solar/Wind Harmer
0.001
246938BC-WTG3
Solar/Wind Harmer
0.178
246937BC-WTG2
Solar/Wind Harmer
0.199
961051AF2-396 GEN
Solar/Wind Harmer
9.419
961051AF2-396 GEN
Solar/Wind Harmer
6.28
957891AF2-083 GEN
Solar/Wind Harmer
0.001
247620Y3-023
Adder
0.301
270216AD2-079_GEN
Solar/Wind Harmer
0.001
970611AG2-400 GEN
Solar/Wind Harmer
4.433
970627AG2-408 GEN
Solar/Wind Harmer
1.33
270526AF1-158 GEN
Solar/Wind Harmer
0.005
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
5.205
965791AG1-447 GEN
Solar/Wind Harmer
3.817
270224U2-072_GEN2
Solar/Wind Harmer
0
270227U2-072_GEN3
Solar/Wind Harmer
0
270228U2-072_GEN4
Solar/Wind Harmer
0
270231U2-072_GEN5
Solar/Wind Harmer
0
274808UNIV PK N;4U
Adder
2.75
274803UNIV PARK;6U
Adder
3.182
942221AE2-234 GEN
Solar/Wind Harmer
0.019
274888KELLY CRK;1U
Solar/Wind Harmer
0.223
274887GEN-1.85
Solar/Wind Harmer
0.1
276843GEN-1.7
Solar/Wind Harmer
0.123
958011AF2-095 GEN
Solar/Wind Harmer
5.459
274770LINCOLN ;1U
Adder
4.584
274771LINCOLN ;2U
Adder
4.584
972259AH1-714 GEN
Adder
10.294
274674JOLIET 9 ;6U
Adder
8.288
970321AG2-212 GEN
Solar/Wind Harmer
1.623
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
958481AF2-142 GEN
Solar/Wind Harmer
5.572
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.503
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
971573AH1-285 GEN
Solar/Wind Harmer
0.69
274695ROCKY RD ;2P
Adder
5.891
274693ROCKY RD ;1P
Adder
5.833
274697ROCKY RD ;3P
Adder
1.6
274696ROCKY RD ;4P
Adder
6.03
274683WAUKEGAN ;8U
Adder
11.144
274683WAUKEGAN ;8U
Adder
9.394
958491AF2-143 GEN
Solar/Wind Harmer
5.526
962691AG1-118 GEN
Solar/Wind Harmer
11.015
274879MINONK ;1U
Solar/Wind Harmer
0.155
970921AG2-575 GEN
Solar/Wind Harmer
3.666
971989AH1-539 GEN
Solar/Wind Harmer
2.024
971619AH1-309 GEN
Solar/Wind Harmer
2.091
965041AG1-368 GEN
Solar/Wind Harmer
4.612
965051AG1-369 GEN
Solar/Wind Harmer
2.289
971771AH1-392 GEN
Solar/Wind Harmer
4.424
270302AB2-170 GEN
Solar/Wind Harmer
0.003
270317AD1-130_GEN
Solar/Wind Harmer
0.006
971653AH1-327 GEN
Solar/Wind Harmer
0.621
971769AH1-391 GEN
Solar/Wind Harmer
4.822
971567AH1-282 GEN
Solar/Wind Harmer
6.357
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971347AH1-153 GEN
Solar/Wind Harmer
6.22
963791AG1-232 GEN
Solar/Wind Harmer
5.569
270578AF1-285 GEN2
Solar/Wind Harmer
0.274
270536AF1-215 GEN2
Solar/Wind Harmer
0.005
270071AF1-092 GEN
Solar/Wind Harmer
7.505
274814UNIV PK N;0U
Adder
2.786
274807UNIV PK N;3U
Adder
2.78
274805UNIV PK N;1U
Adder
2.768
274811UNIV PK N;7U
Adder
2.762
958391AF2-133 GEN
Solar/Wind Harmer
0.001
972037AH1-567 GEN1
Adder
0.1
274827FISK ;RP
Adder
4.228
971611AH1-305 GEN
Solar/Wind Harmer
2.257
960591AF2-350 GEN
Solar/Wind Harmer
3.791
274775LINCOLN ;6U
Adder
4.584
274776LINCOLN ;7U
Adder
4.584
274777LINCOLN ;8U
Adder
4.584
972227AH1-698 GEN1
Adder
1.413
274687WILL CNTY;4U
Adder
15.095
274687WILL CNTY;4U
Adder
15.095
274675JOLIET 29;7U
Adder
16.543
274675JOLIET 29;7U
Adder
15.952
274731ELWOOD EC;2P
Adder
8.848
274733ELWOOD EC;3P
Adder
8.848
274735ELWOOD EC;4P
Adder
8.848
274728ELWOOD EC;5P
Adder
8.849
270024AE2-089 GEN
Solar/Wind Harmer
0.004
970833AG2-524 GEN
Solar/Wind Harmer
4.112
970833AG2-524 GEN
Solar/Wind Harmer
2.741
274746AC1-111 G10
Adder
2.978
274744AC1-111 GEN8
Adder
2.978
276868AE1-113 GEN
Solar/Wind Harmer
0.736
276882AE2-255 GEN
Solar/Wind Harmer
0.429
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
24729505KEY G4
Adder
3.405
971177AH1-047 GEN
Solar/Wind Harmer
2.252
971411AH1-196 GEN
Solar/Wind Harmer
5.463
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
1.419
971171AH1-044 GEN
Solar/Wind Harmer
7.251
274823ROCKFORD ;21
Adder
10.105
926823AC1-168 GEN
Solar/Wind Harmer
0.613
970169AG2-114 GEN
Solar/Wind Harmer
3.606
276612AE2-035 GEN
Solar/Wind Harmer
0.001
971681AH1-341 GEN
Solar/Wind Harmer
5.777
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
24387005FR-3G C
Solar/Wind Harmer
0.001
961011AF2-392 GEN
Solar/Wind Harmer
2.09
957751AF2-069 GEN
Solar/Wind Harmer
0.117
965101AG1-375 GEN
Solar/Wind Harmer
3.538
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
276655WTG1_EQ
Solar/Wind Harmer
0.001
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.709
941731AE2-173 GEN
Solar/Wind Harmer
2.944
963841AG1-237 GEN
Solar/Wind Harmer
1.521
946321AF1-296 GEN
Solar/Wind Harmer
1.955
971609AH1-304 GEN
Solar/Wind Harmer
0.569
945581AF1-223 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.655
270594AE1-207 GEN
Solar/Wind Harmer
3.835
276785W4-005 GEN1
Solar/Wind Harmer
0
276174W4-005 GEN2
Solar/Wind Harmer
0
276849AB2-070 GEN2
Solar/Wind Harmer
0.123
276848AB2-070 GEN3
Solar/Wind Harmer
0.123
970115AG2-085 GEN
Solar/Wind Harmer
1.349
270543AE2-219 C
Solar/Wind Harmer
0.002
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0
241886AC2-103 GEN2
Solar/Wind Helper
7.083
241982AE2-343 S C
Solar/Wind Helper
0.123
254304AE2-114 C
Solar/Wind Helper
0.117
203846AF2-130 C
Solar/Wind Helper
0.257
241997AF1-093 GEN
Solar/Wind Helper
0.136
203804AE2-113_GEN
Solar/Wind Helper
0.892
965011AG1-365 GEN
Solar/Wind Harmer
4.433
270462AD2-086
Solar/Wind Harmer
0.009
270223U2-072_GEN1
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
8.434
270055AF2-134 C O1
Solar/Wind Harmer
0.003
274751CRETE EC ;1U
Adder
4.596
274754CRETE EC ;4U
Adder
4.596
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
5.035
274723RIVER EC ;12
Adder
9.924
274812UNIV PK N;8U
Adder
2.762
276164X3-005 C
Solar/Wind Harmer
0
274801UNIV PARK;4U
Adder
3.173
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
4.739
276776AD2-060 GEN
Solar/Wind Harmer
0.396
274773LINCOLN ;4U
Adder
4.584
274774LINCOLN ;5U
Adder
4.584
274676JOLIET 29;8U
Adder
16.543
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
8.849
274674JOLIET 9 ;6U
Adder
8.288
970245AG2-165 GEN
Solar/Wind Harmer
1.623
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
2.978
276691AA1-018 GEN1
Solar/Wind Harmer
0.45
274682WAUKEGAN ;7U
Adder
9.512
274828WAUKEGAN ;BP
Adder
5.841
276901AD2-066 C O1
Solar/Wind Harmer
0.004
939401AE1-172 GEN
Solar/Wind Harmer
2.747
962781AG1-127 GEN
Solar/Wind Harmer
3.489
24791305MDL-5G
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0.002
971997AH1-543 GEN
Solar/Wind Harmer
1.918
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
276861AD2-134 GEN
Solar/Wind Harmer
0.065
957471AF2-041 GEN
Solar/Wind Harmer
10.876
959081AF2-199 GEN
Solar/Wind Harmer
3.625
971067AG2-660 GEN
Solar/Wind Harmer
1.208
274822ROCKFORD ;11
Adder
10.179
970569AG2-363 GEN
Solar/Wind Harmer
10.839
972235AH1-702 GEN1
Adder
1.305
970819AG2-516 GEN
Solar/Wind Harmer
4.326
971475AH1-234 GEN
Solar/Wind Harmer
1.747
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
4.772
274766LEE CO EC;7U
Adder
4.716
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.001
965651AG1-433 GEN
Solar/Wind Harmer
1.047
276158O29GEN2
Solar/Wind Harmer
0
274877BISHOP HL;1U
Solar/Wind Harmer
0.119
958861AF2-177 GEN
Solar/Wind Harmer
1.533
276726Z2-087_GEN
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
4.946
274854TWINGROVE;U2
Solar/Wind Harmer
0.001
945371AF1-202 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
8.165
970291AG2-192 GEN
Solar/Wind Harmer
0.448
972175AH1-670 GEN
Solar/Wind Harmer
2.841
247536S-71 GEN
Solar/Wind Harmer
0.138
270032AE2-172
Solar/Wind Harmer
2.283
274880W4-005 GEN4
Solar/Wind Harmer
0
963831AG1-236 GEN
Solar/Wind Harmer
1.315
276903AD2-071 C
Solar/Wind Harmer
3.766
970825AG2-519 GEN
Solar/Wind Harmer
1.195
276615X2-022 GEN
Solar/Wind Harmer
0.035
241885AC2-103 GEN1
Solar/Wind Helper
7.083
241807AE2-176_GEN
Solar/Wind Helper
1.701
961971AG1-040 GEN
Solar/Wind Helper
0.352
203835AF1-098 GEN
Solar/Wind Helper
1.388
203860AG1-193 C
Solar/Wind Helper
0.156
241966AE1-183 GEN
Solar/Wind Helper
0.136
254303AC2-168 GEN
Solar/Wind Helper
0.079
203954AE2-126 C
Solar/Wind Helper
0.223
23906502RICHG2&3
50/50
1.747
241832AE2-181_GEN
Solar/Wind Harmer
0.004
958321AF2-126 GEN
Solar/Wind Harmer
1.413
23929302BS-PKR
Adder
1.959
270541AE2-072 C
Solar/Wind Harmer
0.01
270575GUS2 35KV
Solar/Wind Harmer
4.971
970217AG2-149 GEN
Solar/Wind Harmer
5.053
270404AC1-167 GEN
Solar/Wind Harmer
0.002
270258AD1-119 GEN
Solar/Wind Harmer
0.001
247604X1-042
Adder
0.302
270588AE1-091_GEN
Solar/Wind Harmer
3.901
24441205WTRV SLR C
Solar/Wind Harmer
0
270491AE1-102 GEN2
Solar/Wind Harmer
0.637
945111AF1-176 GEN
Solar/Wind Harmer
3.77
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.03
24642205MAYFLWER
Adder
0.413
970031AG2-029 GEN
Solar/Wind Harmer
2.93
247643Z2-116 C
Solar/Wind Harmer
0
959331AF2-224 GEN
Solar/Wind Harmer
3.103
965021AG1-366 GEN
Solar/Wind Harmer
1.478
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270043AE2-236 GEN
Solar/Wind Harmer
2.692
970349AG2-230 GEN
Solar/Wind Harmer
6.22
270391AF1-285 GEN3
Solar/Wind Harmer
0.274
270535AF1-215 GEN1
Solar/Wind Harmer
0.005
274752CRETE EC ;2U
Adder
4.596
274753CRETE EC ;3U
Adder
4.596
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274724RIVER EC ;11
Adder
9.806
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
274802UNIV PARK;5U
Adder
3.182
274826FISK ;BP
Adder
5.966
274800UNIV PARK;3U
Adder
3.173
972038AH1-567 GEN2
Adder
0.199
276806AD2-047 C O1
Solar/Wind Harmer
2.148
970941AG2-585 GEN
Solar/Wind Harmer
4.739
274772LINCOLN ;3U
Adder
4.584
972228AH1-698 GEN2
Adder
2.007
274676JOLIET 29;8U
Adder
15.952
276897AD1-100 C
Solar/Wind Harmer
0.005
939351AE1-166 GEN
Solar/Wind Harmer
0
276893AG1-478 C
Solar/Wind Harmer
0.149
274729ELWOOD EC;1P
Adder
8.848
274730ELWOOD EC;6P
Adder
8.849
274734ELWOOD EC;8P
Adder
8.849
274736ELWOOD EC;9P
Adder
8.849
970707AG2-453 GEN
Solar/Wind Harmer
12.267
971617AH1-308 GEN
Solar/Wind Harmer
3.125
970513AG2-328 GEN
Solar/Wind Harmer
1.623
970517AG2-330 GEN
Solar/Wind Harmer
9.737
943121AE2-341 GEN
Solar/Wind Harmer
6.229
943591AF1-030 GEN
Solar/Wind Harmer
4.142
276694AA1-018 GEN2
Solar/Wind Harmer
0
944531AF1-118 GEN
Solar/Wind Harmer
16.565
274682WAUKEGAN ;7U
Adder
9.512
276805AD2-038 GEN
Solar/Wind Harmer
0.001
24755605MDL-5G
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.663
274872LEEDK;1U
Solar/Wind Harmer
0.134
276889AE2-281 GEN
Solar/Wind Harmer
0
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.388
274855GSG-6 ;RU
Solar/Wind Harmer
0.133
274850MENDOTA H;RU
Solar/Wind Harmer
0.043
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.065
959091AF2-200 GEN
Solar/Wind Harmer
7.251
970571AG2-364 GEN
Solar/Wind Harmer
7.226
972236AH1-702 GEN2
Adder
1.135
270377AD1-106 GEN
Solar/Wind Harmer
1.364
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
4.772
274767LEE CO EC;8U
Adder
0.229
276157O29GEN1
Solar/Wind Harmer
0.575
274878BISHOP HL;2U
Solar/Wind Harmer
0.119
942111AE2-223 GEN
Solar/Wind Harmer
1.148
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
5.278
274853TWINGROVE;U1
Solar/Wind Harmer
0.001
965091AG1-374 GEN
Solar/Wind Harmer
10.488
959611AF2-252 GEN
Solar/Wind Harmer
1.165
965931AG1-462 GEN
Solar/Wind Harmer
8.873
247642Z2-115 C
Solar/Wind Harmer
0.002
970289AG2-191 GEN
Solar/Wind Harmer
0.379
970291AG2-192 GEN
Solar/Wind Harmer
0.345
276686W4-005 GEN3
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
1.563
276668AB2-070 GEN1
Solar/Wind Harmer
0.123
946031AF1-268 GEN
Solar/Wind Harmer
3.219
276621W2-048 GEN
Solar/Wind Harmer
0.169
276838X2-022 GEN2
Solar/Wind Harmer
0.189
962511AG1-100 GEN
Solar/Wind Helper
0.361
203830AF1-094 GEN
Solar/Wind Helper
0.34
959441AF2-235 GEN
Solar/Wind Helper
0.154
254305AE2-115 C
Solar/Wind Helper
0.117
20334926Z1-069 C
Solar/Wind Helper
0.662
958821AF2-173 GEN
Solar/Wind Harmer
1.049
970921AG2-575 GEN
Solar/Wind Harmer
1.222
942991AE2-321 GEN
Solar/Wind Harmer
4.078
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
971333AH1-146 GEN
Solar/Wind Harmer
7.279
971335AH1-147 GEN
Solar/Wind Harmer
7.279
971341AH1-150 GEN
Solar/Wind Harmer
7.251
971343AH1-151 GEN
Solar/Wind Harmer
7.251
274856ECOGROVE ;U1
Solar/Wind Harmer
0.085
276611AD2-172 GEN
Solar/Wind Harmer
0.001
971231AH1-075 GEN
Solar/Wind Harmer
0.412
938861AE1-114 GEN
Solar/Wind Harmer
2.033
274764LEE CO EC;5U
Adder
4.784
274765LEE CO EC;6U
Adder
4.784
274762LEE CO EC;3U
Adder
4.772
274763LEE CO EC;4U
Adder
4.727
966841AG1-555 GEN
Solar/Wind Harmer
0.405
276603SUBLETTE C
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.239
960971AF2-388 GEN
Solar/Wind Harmer
2.094
274851PROVIDENC;RU
Solar/Wind Harmer
0
274849CRESCENT ;1U
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.14
276646AC1-214 GEN2
Solar/Wind Harmer
0.14
276741O09 GEN1
Solar/Wind Harmer
0.127
276708O09 GEN2
Solar/Wind Harmer
0.127
276782AC1-033 GEN
Solar/Wind Harmer
0.001
270201AC2-176 GEN
Solar/Wind Harmer
0.001
960611AF2-352 GEN
Solar/Wind Harmer
1.165
964611AG1-324 GEN
Solar/Wind Harmer
0.262
270599AE1-208 GEN
Solar/Wind Harmer
3.195
270031AE2-169
Solar/Wind Harmer
1.917
970241AG2-163 GEN
Solar/Wind Harmer
2.013
253378AE2-206_GEN
Solar/Wind Harmer
0.002
276820AF1-078_GEN
Solar/Wind Harmer
0.001
970329AG2-216 GEN
Solar/Wind Harmer
1.487
971613AH1-306 GEN
Solar/Wind Harmer
1.644
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
960441AF2-335 GEN
Solar/Wind Harmer
3.372
970825AG2-519 GEN
Solar/Wind Harmer
3.73
970883AG2-550 GEN
Solar/Wind Harmer
3.346
970885AG2-551 GEN
Solar/Wind Harmer
1.115
203947AF1-006 C
Solar/Wind Helper
0.402
203980AG1-197 GEN
Solar/Wind Helper
0.262
203979AG1-198 GEN
Solar/Wind Helper
0.204
241967AE2-285_GEN
Solar/Wind Helper
0.354
241801AE1-079 GEN
Solar/Wind Helper
0.138
241985AE1-237 GEN
Solar/Wind Helper
0.137
962101AG1-054 GEN
Solar/Wind Helper
0.34
946381AF1-302 GEN
Solar/Wind Helper
0.108
238217AF1-153 C O1
Solar/Wind Helper
0.114
991177J1571 G
External Queue
18.513126373291016
990527J1329
External Queue
2.100800037384033
990142J1224
External Queue
15.35684871673584
991182J1586 G
External Queue
28.404245376586914
LAGNLTFEXP_LAGN->PJM
CLTF
6.243
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.59
TVALTFEXP_TVA->PJM
CLTF
2.868
CPLELTFEXP_CPLE->PJM
CLTF
0.787
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.86
NYPJM->LTFIMP_NY
CLTF
2.006
LGEELTFEXP_LGEE->PJM
CLTF
2.487
WECLTFEXP_WEC->PJM
CLTF
1.978
AG2-052LTFEXP_AG2-052->PJM
LTF
0.127
AH1-155LTFEXP_AH1-155->PJM
LTF
0.19
CBM West 1LTFEXP_CBM-W1->PJM
CBM
107.191
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.28
MECLTFEXP_MEC->PJM
CLTF
7.783
SIGELTFEXP_SIGE->PJM
CLTF
0.206

Details for 02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line l/o ATSI_P7-1_TE-345-021_SRT-A-1


Base Case Flowgate

Area:ATSI
Facility Description:
02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P7-1_TE-345-021_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:109.02 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:2047.43
MW Contribution:13.11
Bus #Bus NameTypeMW Contribution
23888502TROY G1
50/50
2.569
23888602TROY G2
50/50
2.569
972211AH1-690 GEN
50/50
211.679
23906902RICHG6
50/50
0.775
23906702RICHG4
50/50
0.773
23906802RICHG5
50/50
0.564
970817AG2-515 GEN
Solar/Wind Harmer
17.825
945411AF1-206 GEN
Solar/Wind Harmer
6.384
945641AF1-229 GEN
Solar/Wind Harmer
3.799
270499AE1-146 GEN
Solar/Wind Harmer
2.114
971549AH1-272 GEN
Solar/Wind Harmer
13.108
270297AD1-101 GEN
Solar/Wind Harmer
1.882
957201AF2-014 GEN
Solar/Wind Harmer
2.802
270435AC2-044 GEN
Solar/Wind Harmer
1.235
247607V1-011 GEN
Solar/Wind Harmer
2.395
944161AF1-084 GEN
Solar/Wind Harmer
1.31
966831AG1-554 GEN
Solar/Wind Harmer
0.689
971989AH1-539 GEN
Solar/Wind Harmer
7.445
965041AG1-368 GEN
Solar/Wind Harmer
5.685
965051AG1-369 GEN
Solar/Wind Harmer
2.828
270302AB2-170 GEN
Solar/Wind Harmer
4.729
270317AD1-130_GEN
Solar/Wind Harmer
1.813
971567AH1-282 GEN
Solar/Wind Harmer
8.37
971771AH1-392 GEN
Solar/Wind Harmer
4.919
971769AH1-391 GEN
Solar/Wind Harmer
5.338
270578AF1-285 GEN2
Solar/Wind Harmer
0.244
960681AF2-359 GEN
Solar/Wind Harmer
1.946
971347AH1-153 GEN
Solar/Wind Harmer
7.697
963791AG1-232 GEN
Solar/Wind Harmer
6.886
270536AF1-215 GEN2
Solar/Wind Harmer
2.218
270071AF1-092 GEN
Solar/Wind Harmer
7.266
274814UNIV PK N;0U
Adder
2.407
274807UNIV PK N;3U
Adder
2.402
274805UNIV PK N;1U
Adder
2.392
274811UNIV PK N;7U
Adder
2.386
958391AF2-133 GEN
Solar/Wind Harmer
4.322
972037AH1-567 GEN1
Adder
0.086
274827FISK ;RP
Adder
3.654
960591AF2-350 GEN
Solar/Wind Harmer
4.697
274775LINCOLN ;6U
Adder
2.911
274776LINCOLN ;7U
Adder
2.911
274777LINCOLN ;8U
Adder
2.911
972227AH1-698 GEN1
Adder
1.222
274687WILL CNTY;4U
Adder
13.048
274687WILL CNTY;4U
Adder
13.048
274675JOLIET 29;7U
Adder
14.3
274675JOLIET 29;7U
Adder
13.789
274728ELWOOD EC;5P
Adder
7.649
274731ELWOOD EC;2P
Adder
7.649
274733ELWOOD EC;3P
Adder
7.649
274735ELWOOD EC;4P
Adder
7.649
270024AE2-089 GEN
Solar/Wind Harmer
2.183
970833AG2-524 GEN
Solar/Wind Harmer
4.044
970833AG2-524 GEN
Solar/Wind Harmer
1.881
274746AC1-111 G10
Adder
2.574
274744AC1-111 GEN8
Adder
2.574
24729505KEY G4
Adder
2.948
274823ROCKFORD ;21
Adder
8.739
241886AC2-103 GEN2
Solar/Wind Helper
5.94
241982AE2-343 S C
Solar/Wind Helper
0.106
254304AE2-114 C
Solar/Wind Helper
0.101
203846AF2-130 C
Solar/Wind Helper
0.222
241997AF1-093 GEN
Solar/Wind Helper
0.117
23906502RICHG2&3
50/50
1.301
241832AE2-181_GEN
Solar/Wind Harmer
1.668
958321AF2-126 GEN
Solar/Wind Harmer
1.231
270541AE2-072 C
Solar/Wind Harmer
4.058
270575GUS2 35KV
Solar/Wind Harmer
8.824
970217AG2-149 GEN
Solar/Wind Harmer
24.659
270044AE2-322 C
Solar/Wind Harmer
0.857
270404AC1-167 GEN
Solar/Wind Harmer
0.713
270258AD1-119 GEN
Solar/Wind Harmer
1.762
247604X1-042
Adder
0.26
270491AE1-102 GEN2
Solar/Wind Harmer
0.803
270588AE1-091_GEN
Solar/Wind Harmer
6.773
24441205WTRV SLR C
Solar/Wind Harmer
0.082
958091AF2-103 GEN
Solar/Wind Harmer
0.098
945111AF1-176 GEN
Solar/Wind Harmer
3.248
270191TR4_S_V150
Solar/Wind Harmer
1.699
270247TR4_N_V136
Solar/Wind Harmer
0.482
23888802TROY G4
50/50
2.569
24190002OREGON_ST1
50/50
2.645
24189802OREGON_CT1
50/50
2.007
241996AE2-282_GEN
Solar/Wind Harmer
1.709
971677AH1-339 GEN
Solar/Wind Harmer
6.229
246938BC-WTG3
Solar/Wind Harmer
2.459
246937BC-WTG2
Solar/Wind Harmer
2.417
270007AE1-245 C
Solar/Wind Harmer
3.593
942801AE2-298 GEN
Solar/Wind Harmer
0.907
961051AF2-396 GEN
Solar/Wind Harmer
9.231
961051AF2-396 GEN
Solar/Wind Harmer
4.293
960981AF2-389 GEN
Solar/Wind Harmer
0.865
957891AF2-083 GEN
Solar/Wind Harmer
1.93
247620Y3-023
Adder
0.259
270216AD2-079_GEN
Solar/Wind Harmer
0.336
970611AG2-400 GEN
Solar/Wind Harmer
5.502
270526AF1-158 GEN
Solar/Wind Harmer
2.437
24441505OLIV SLR
Solar/Wind Harmer
0.072
270224U2-072_GEN2
Solar/Wind Harmer
1.039
270227U2-072_GEN3
Solar/Wind Harmer
1.039
270228U2-072_GEN4
Solar/Wind Harmer
1.039
270231U2-072_GEN5
Solar/Wind Harmer
1.039
965681AG1-436 GEN
Solar/Wind Harmer
6.439
965791AG1-447 GEN
Solar/Wind Harmer
3.294
274808UNIV PK N;4U
Adder
2.376
274803UNIV PARK;6U
Adder
2.75
274888KELLY CRK;1U
Solar/Wind Harmer
2.773
274887GEN-1.85
Solar/Wind Harmer
2.503
276843GEN-1.7
Solar/Wind Harmer
0.269
942221AE2-234 GEN
Solar/Wind Harmer
0.344
958011AF2-095 GEN
Solar/Wind Harmer
6.763
274770LINCOLN ;1U
Adder
2.911
274771LINCOLN ;2U
Adder
2.911
972259AH1-714 GEN
Adder
8.899
274674JOLIET 9 ;6U
Adder
7.164
970321AG2-212 GEN
Solar/Wind Harmer
8.289
274847GR RIDGE ;BU
Solar/Wind Harmer
2.342
958481AF2-142 GEN
Solar/Wind Harmer
6.904
274696ROCKY RD ;4P
Adder
5.214
274695ROCKY RD ;2P
Adder
5.094
274693ROCKY RD ;1P
Adder
5.044
274697ROCKY RD ;3P
Adder
1.384
274683WAUKEGAN ;8U
Adder
9.635
274683WAUKEGAN ;8U
Adder
8.122
274764LEE CO EC;5U
Adder
4.138
274765LEE CO EC;6U
Adder
4.138
274762LEE CO EC;3U
Adder
4.128
274763LEE CO EC;4U
Adder
4.089
972267AH1-718 GEN
Adder
1.836
25326509SID D
Adder
0.577
247621Y3-024
Adder
0.104
203947AF1-006 C
Solar/Wind Helper
0.347
203980AG1-197 GEN
Solar/Wind Helper
0.226
203979AG1-198 GEN
Solar/Wind Helper
0.176
241967AE2-285_GEN
Solar/Wind Helper
0.305
241801AE1-079 GEN
Solar/Wind Helper
0.119
241985AE1-237 GEN
Solar/Wind Helper
0.118
962101AG1-054 GEN
Solar/Wind Helper
0.293
274861TOP CROP ;1U
Solar/Wind Harmer
0.254
274862TOP CROP ;2U
Solar/Wind Harmer
0.213
270485AE1-090_GEN
Solar/Wind Harmer
0.342
24642205MAYFLWER
Adder
0.356
970031AG2-029 GEN
Solar/Wind Harmer
16.707
247643Z2-116 C
Solar/Wind Harmer
0.039
959331AF2-224 GEN
Solar/Wind Harmer
5.502
965021AG1-366 GEN
Solar/Wind Harmer
1.28
942871AE2-306 GEN
Solar/Wind Harmer
0.477
270391AF1-285 GEN3
Solar/Wind Harmer
0.244
270043AE2-236 GEN
Solar/Wind Harmer
2.848
970349AG2-230 GEN
Solar/Wind Harmer
7.697
270535AF1-215 GEN1
Solar/Wind Harmer
2.218
972231SS25-0005
Solar/Wind Harmer
4.574
972181SS23-001
Solar/Wind Harmer
2.859
274752CRETE EC ;2U
Adder
2.356
274753CRETE EC ;3U
Adder
2.356
964401AG1-302 GEN
Solar/Wind Harmer
4.359
274724RIVER EC ;11
Adder
8.473
959141AF2-205 GEN
Solar/Wind Harmer
2.862
274802UNIV PARK;5U
Adder
2.75
274826FISK ;BP
Adder
5.156
274800UNIV PARK;3U
Adder
2.742
972038AH1-567 GEN2
Adder
0.172
276772AC2-154 GEN
Solar/Wind Harmer
1.31
276806AD2-047 C O1
Solar/Wind Harmer
5.024
970941AG2-585 GEN
Solar/Wind Harmer
5.871
274772LINCOLN ;3U
Adder
2.911
972228AH1-698 GEN2
Adder
1.735
274676JOLIET 29;8U
Adder
13.789
276897AD1-100 C
Solar/Wind Harmer
13.513
939351AE1-166 GEN
Solar/Wind Harmer
2.761
276893AG1-478 C
Solar/Wind Harmer
0.194
274730ELWOOD EC;6P
Adder
7.649
274734ELWOOD EC;8P
Adder
7.649
274736ELWOOD EC;9P
Adder
7.649
970707AG2-453 GEN
Solar/Wind Harmer
13.028
274729ELWOOD EC;1P
Adder
7.649
971617AH1-308 GEN
Solar/Wind Harmer
2.704
970513AG2-328 GEN
Solar/Wind Harmer
8.289
970517AG2-330 GEN
Solar/Wind Harmer
7.518
943121AE2-341 GEN
Solar/Wind Harmer
6.906
943591AF1-030 GEN
Solar/Wind Harmer
4.604
276694AA1-018 GEN2
Solar/Wind Harmer
2.905
274682WAUKEGAN ;7U
Adder
8.225
972236AH1-702 GEN2
Adder
0.982
274760LEE CO EC;1U
Adder
4.128
274767LEE CO EC;8U
Adder
4.079
962511AG1-100 GEN
Solar/Wind Helper
0.311
203830AF1-094 GEN
Solar/Wind Helper
0.294
959441AF2-235 GEN
Solar/Wind Helper
0.133
254305AE2-115 C
Solar/Wind Helper
0.101
23888702TROY G3
50/50
2.569
972253AH1-711 GEN
50/50
78.462
24189902OREGON_CT2
50/50
1.966
23920202STRYCT
50/50
1.673
972301AH1-735 GEN
50/50
6.522
23906402RICHG1
50/50
1.304
23906502RICHG2&3
50/50
1.301
241858AF1-205_GEN
Solar/Wind Harmer
5.012
241808AF1-120 C
Solar/Wind Harmer
0.953
241840AF1-064_GEN
Solar/Wind Harmer
1.148
270361_3
Solar/Wind Harmer
7.49
960841AF2-375 GEN
Solar/Wind Harmer
3.331
970515AG2-329 GEN
Solar/Wind Harmer
11.182
247522W1-056 GEN
Solar/Wind Harmer
1.488
944231AF1-091 GEN
Solar/Wind Harmer
2.464
246936BC-WTG1
Solar/Wind Harmer
2.417
270489AE1-102 GEN1
Solar/Wind Harmer
0.803
965421AG1-410 GEN
Solar/Wind Harmer
18.338
270449AD2-020 GEN
Solar/Wind Harmer
1.642
943021AE2-325 GEN
Solar/Wind Harmer
2.133
24695305TIMB G C
Solar/Wind Harmer
3.212
945111AF1-176 GEN
Solar/Wind Harmer
10.248
270505AE1-170 C O1
Solar/Wind Harmer
8.607
247521TR3_G114
Solar/Wind Harmer
1.904
270246TR4_N_V150
Solar/Wind Harmer
0.482
270462AD2-086
Solar/Wind Harmer
3.934
24639705ELKHART HY
Adder
0.086
270063AE2-323 C
Solar/Wind Harmer
1.226
965011AG1-365 GEN
Solar/Wind Harmer
5.502
270223U2-072_GEN1
Solar/Wind Harmer
1.039
270578AF1-285 GEN2
Solar/Wind Harmer
0.635
270391AF1-285 GEN3
Solar/Wind Harmer
0.635
970373AG2-245 GEN
Solar/Wind Harmer
10.44
270055AF2-134 C O1
Solar/Wind Harmer
1.479
274751CRETE EC ;1U
Adder
2.356
274754CRETE EC ;4U
Adder
2.356
958381AF2-132 GEN
Solar/Wind Harmer
4.359
964861AG1-349 GEN
Solar/Wind Harmer
3.77
971917AH1-482 GEN
Solar/Wind Harmer
4.351
274723RIVER EC ;12
Adder
8.575
274812UNIV PK N;8U
Adder
2.386
276164X3-005 C
Solar/Wind Harmer
0.334
274801UNIV PARK;4U
Adder
2.742
940581AE2-045 GEN
Solar/Wind Harmer
4.791
971605AH1-302 GEN
Solar/Wind Harmer
4.097
276776AD2-060 GEN
Solar/Wind Harmer
0.199
972207SS24-0001
Solar/Wind Harmer
10.349
274773LINCOLN ;4U
Adder
2.911
274774LINCOLN ;5U
Adder
2.911
274676JOLIET 29;8U
Adder
14.3
941551AE2-152 GEN
Solar/Wind Harmer
2.112
274732ELWOOD EC;7P
Adder
7.649
274674JOLIET 9 ;6U
Adder
7.164
970245AG2-165 GEN
Solar/Wind Harmer
8.289
274871GR RIDGE ;2U
Solar/Wind Harmer
3.56
274745AC1-111 GEN9
Adder
2.574
276691AA1-018 GEN1
Solar/Wind Harmer
0.214
274682WAUKEGAN ;7U
Adder
8.225
274828WAUKEGAN ;BP
Adder
5.051
274822ROCKFORD ;11
Adder
8.803
972235AH1-702 GEN1
Adder
1.129
274761LEE CO EC;2U
Adder
4.128
274766LEE CO EC;7U
Adder
4.079
241885AC2-103 GEN1
Solar/Wind Helper
5.94
241807AE2-176_GEN
Solar/Wind Helper
1.896
961971AG1-040 GEN
Solar/Wind Helper
0.304
203835AF1-098 GEN
Solar/Wind Helper
1.197
203860AG1-193 C
Solar/Wind Helper
0.135
241966AE1-183 GEN
Solar/Wind Helper
0.117
254303AC2-168 GEN
Solar/Wind Helper
0.068
991177J1571 G
External Queue
14.387535095214844
990527J1329
External Queue
1.7516577243804932
990142J1224
External Queue
12.804616928100586
991182J1586 G
External Queue
24.285308837890625
LAGNLTFEXP_LAGN->PJM
CLTF
5.44
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.193
TVALTFEXP_TVA->PJM
CLTF
2.504
CPLELTFEXP_CPLE->PJM
CLTF
0.714
CBM West 2LTFEXP_CBM-W2->PJM
CBM
42.488
NYPJM->LTFIMP_NY
CLTF
1.719
LGEELTFEXP_LGEE->PJM
CLTF
2.17
WECLTFEXP_WEC->PJM
CLTF
1.711
AG2-052LTFEXP_AG2-052->PJM
LTF
0.11
AH1-155LTFEXP_AH1-155->PJM
LTF
0.164
CBM West 1LTFEXP_CBM-W1->PJM
CBM
92.185
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.846
MECLTFEXP_MEC->PJM
CLTF
6.742
SIGELTFEXP_SIGE->PJM
CLTF
0.179

Details for 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:121.78 %
Rating:1737.0 MVA
Rating Type:B
MVA to Mitigate:2115.3
MW Contribution:10.1
Bus #Bus NameTypeMW Contribution
960861AF2-377 GEN
50/50
2.449
970521AG2-332 GEN
50/50
11.057
24639705ELKHART HY
50/50
0.153
270143AC1-141 CT2_
50/50
2.055
24344105CKG2
50/50
6.288
24307105BERRINSP G
50/50
0.018
965011AG1-365 GEN
Solar/Wind Harmer
13.913
270063AE2-323 C
Solar/Wind Harmer
0.006
247521TR3_G114
Solar/Wind Harmer
0.268
270246TR4_N_V150
Solar/Wind Harmer
0.047
944231AF1-091 GEN
Solar/Wind Harmer
1.894
24695305TIMB G C
Solar/Wind Harmer
0.002
965651AG1-433 GEN
Solar/Wind Harmer
1.883
958861AF2-177 GEN
Solar/Wind Harmer
2.703
945111AF1-176 GEN
Solar/Wind Harmer
10.846
270505AE1-170 C O1
Solar/Wind Harmer
6.228
945371AF1-202 GEN
Solar/Wind Harmer
0
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.049
970245AG2-165 GEN
Solar/Wind Harmer
2.372
970373AG2-245 GEN
Solar/Wind Harmer
11.463
274751CRETE EC ;1U
Adder
6.419
274754CRETE EC ;4U
Adder
6.419
274723RIVER EC ;12
Adder
13.914
274812UNIV PK N;8U
Adder
3.858
276164X3-005 C
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0.004
274773LINCOLN ;4U
Adder
6.474
274774LINCOLN ;5U
Adder
6.474
274801UNIV PARK;4U
Adder
4.433
276776AD2-060 GEN
Solar/Wind Harmer
0.553
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
6.867
941551AE2-152 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
23.063
274674JOLIET 9 ;6U
Adder
11.55
274732ELWOOD EC;7P
Adder
12.325
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
6.476
274745AC1-111 GEN9
Adder
4.142
276691AA1-018 GEN1
Solar/Wind Harmer
0.622
274682WAUKEGAN ;7U
Adder
13.17
970291AG2-192 GEN
Solar/Wind Harmer
0.664
274828WAUKEGAN ;BP
Adder
8.084
270005AE1-210 C O1
Solar/Wind Harmer
1.101
965031AG1-367 GEN
Solar/Wind Harmer
5.08
962781AG1-127 GEN
Solar/Wind Harmer
4.819
939401AE1-172 GEN
Solar/Wind Harmer
3.786
276901AD2-066 C O1
Solar/Wind Harmer
0.005
270032AE2-172
Solar/Wind Harmer
3.37
274872LEEDK;1U
Solar/Wind Harmer
0.003
971997AH1-543 GEN
Solar/Wind Harmer
2.638
276861AD2-134 GEN
Solar/Wind Harmer
0.09
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
970583AG2-370 GEN
50/50
2.859
960851AF2-376 GEN
50/50
2.155
24641605TWIN BRNCH
50/50
0.016
270142AC1-141 CT1_
50/50
2.055
24642205MAYFLWER
50/50
0.571
944961AF1-161 GEN
50/50
2.434
962601AG1-109 GEN
50/50
2.434
24344005CKG1
50/50
5.289
959331AF2-224 GEN
Solar/Wind Harmer
9.739
965021AG1-366 GEN
Solar/Wind Harmer
4.638
970031AG2-029 GEN
Solar/Wind Harmer
5.561
270043AE2-236 GEN
Solar/Wind Harmer
5.288
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.047
944531AF1-118 GEN
Solar/Wind Harmer
32.162
971617AH1-308 GEN
Solar/Wind Harmer
5.291
247643Z2-116 C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
4.927
970349AG2-230 GEN
Solar/Wind Harmer
8.913
24441205WTRV SLR C
Solar/Wind Harmer
0
970513AG2-328 GEN
Solar/Wind Harmer
2.372
970517AG2-330 GEN
Solar/Wind Harmer
14.231
274752CRETE EC ;2U
Adder
6.419
274753CRETE EC ;3U
Adder
6.419
274724RIVER EC ;11
Adder
13.745
247604X1-042
Adder
0.322
270535AF1-215 GEN1
Solar/Wind Harmer
0.007
274772LINCOLN ;3U
Adder
6.474
274802UNIV PARK;5U
Adder
4.445
274826FISK ;BP
Adder
8.338
274800UNIV PARK;3U
Adder
4.433
972038AH1-567 GEN2
Adder
0.277
276806AD2-047 C O1
Solar/Wind Harmer
3.002
970941AG2-585 GEN
Solar/Wind Harmer
6.622
964401AG1-302 GEN
Solar/Wind Harmer
0.001
972228AH1-698 GEN2
Adder
2.805
970707AG2-453 GEN
Solar/Wind Harmer
17.2
276897AD1-100 C
Solar/Wind Harmer
0.007
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
22.239
276893AG1-478 C
Solar/Wind Harmer
0.207
274729ELWOOD EC;1P
Adder
12.325
274730ELWOOD EC;6P
Adder
12.325
274734ELWOOD EC;8P
Adder
12.325
274736ELWOOD EC;9P
Adder
12.325
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
943121AE2-341 GEN
Solar/Wind Harmer
8.672
943591AF1-030 GEN
Solar/Wind Harmer
5.767
247642Z2-115 C
Solar/Wind Harmer
0.002
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
13.17
970289AG2-191 GEN
Solar/Wind Harmer
0.562
970291AG2-192 GEN
Solar/Wind Harmer
0.511
958821AF2-173 GEN
Solar/Wind Harmer
7.111
270004AE1-209 GEN
Solar/Wind Harmer
1.101
276805AD2-038 GEN
Solar/Wind Harmer
0.001
274872LEEDK;1U
Solar/Wind Harmer
0.185
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.534
274855GSG-6 ;RU
Solar/Wind Harmer
0.184
274850MENDOTA H;RU
Solar/Wind Harmer
0.059
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.09
276889AE2-281 GEN
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
4.985
959091AF2-200 GEN
Solar/Wind Harmer
9.953
972236AH1-702 GEN2
Adder
1.555
970571AG2-364 GEN
Solar/Wind Harmer
9.859
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
6.505
274767LEE CO EC;8U
Adder
6.428
946031AF1-268 GEN
Solar/Wind Harmer
4.635
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
7.294
276157O29GEN1
Solar/Wind Harmer
0.779
274878BISHOP HL;2U
Solar/Wind Harmer
0.161
942111AE2-223 GEN
Solar/Wind Harmer
1.543
965931AG1-462 GEN
Solar/Wind Harmer
11.906
274853TWINGROVE;U1
Solar/Wind Harmer
0.002
965091AG1-374 GEN
Solar/Wind Harmer
14.002
959611AF2-252 GEN
Solar/Wind Harmer
1.556
270437AC2-090 C
Solar/Wind Harmer
0.002
276686W4-005 GEN3
Solar/Wind Harmer
0.001
276668AB2-070 GEN1
Solar/Wind Harmer
0.161
970615AG2-402 GEN
50/50
4.638
24729405KEY G3
50/50
0.376
24729305KEY G2
50/50
0.369
24729205KEY G1
50/50
0.368
247620Y3-023
50/50
0.473
270102X2-052 ST
50/50
1.304
270100X2-052 CT1
50/50
1.202
270101X2-052 CT2
50/50
1.202
970611AG2-400 GEN
Solar/Wind Harmer
13.913
970627AG2-408 GEN
Solar/Wind Harmer
4.174
942221AE2-234 GEN
Solar/Wind Harmer
0.035
944541AF1-119 GEN
Solar/Wind Harmer
0.43
960971AF2-388 GEN
Solar/Wind Harmer
3.767
270216AD2-079_GEN
Solar/Wind Harmer
0.001
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
11.858
961051AF2-396 GEN
Solar/Wind Harmer
7.905
270526AF1-158 GEN
Solar/Wind Harmer
0.007
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
7.075
965791AG1-447 GEN
Solar/Wind Harmer
5.189
270599AE1-208 GEN
Solar/Wind Harmer
5.131
270031AE2-169
Solar/Wind Harmer
3.079
970321AG2-212 GEN
Solar/Wind Harmer
2.372
971599AH1-298 GEN
50/50
10.521
24729505KEY G4
50/50
6.883
24653605MOTTVILLE
50/50
0.004
270144AC1-141 ST1_
50/50
1.82
24643105BUCHANAN
50/50
0.011
963791AG1-232 GEN
Solar/Wind Harmer
11.809
965041AG1-368 GEN
Solar/Wind Harmer
8.577
270071AF1-092 GEN
Solar/Wind Harmer
14.687
965051AG1-369 GEN
Solar/Wind Harmer
3.667
270024AE2-089 GEN
Solar/Wind Harmer
0.007
965101AG1-375 GEN
Solar/Wind Harmer
6.239
971771AH1-392 GEN
Solar/Wind Harmer
5.998
971347AH1-153 GEN
Solar/Wind Harmer
8.913
971619AH1-309 GEN
Solar/Wind Harmer
2.669
945581AF1-223 GEN
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
2.041
276621W2-048 GEN
Solar/Wind Harmer
0.219
276838X2-022 GEN2
Solar/Wind Harmer
0.245
942481AE2-261 GEN
Solar/Wind Harmer
12.535
970193AG2-126 GEN
Solar/Wind Harmer
6.087
270404AC1-167 GEN
Solar/Wind Harmer
0.002
270258AD1-119 GEN
Solar/Wind Harmer
0.001
24728705AND G3
Adder
4.445
24728505AND G1
Adder
2.125
270356AE2-297 GEN
Solar/Wind Harmer
0.005
970243AG2-164 GEN
Solar/Wind Harmer
1.9
970519AG2-331 GEN
Solar/Wind Harmer
8.446
970699AG2-449 GEN
Solar/Wind Harmer
0.812
270485AE1-090_GEN
Solar/Wind Helper
0.318
942871AE2-306 GEN
Solar/Wind Helper
0.434
270541AE2-072 C
Solar/Wind Helper
0.891
971769AH1-391 GEN
Solar/Wind Harmer
6.451
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971609AH1-304 GEN
Solar/Wind Harmer
0.914
274814UNIV PK N;0U
Adder
3.891
274807UNIV PK N;3U
Adder
3.883
274805UNIV PK N;1U
Adder
3.866
274811UNIV PK N;7U
Adder
3.858
270536AF1-215 GEN2
Solar/Wind Harmer
0.007
274775LINCOLN ;6U
Adder
6.474
274776LINCOLN ;7U
Adder
6.474
274777LINCOLN ;8U
Adder
6.474
972037AH1-567 GEN1
Adder
0.14
274827FISK ;RP
Adder
5.909
960591AF2-350 GEN
Solar/Wind Harmer
5.298
972227AH1-698 GEN1
Adder
1.975
274687WILL CNTY;4U
Adder
21.05
274687WILL CNTY;4U
Adder
21.05
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274675JOLIET 29;7U
Adder
23.063
274675JOLIET 29;7U
Adder
22.239
274731ELWOOD EC;2P
Adder
12.325
274733ELWOOD EC;3P
Adder
12.325
274735ELWOOD EC;4P
Adder
12.325
274728ELWOOD EC;5P
Adder
12.325
970833AG2-524 GEN
Solar/Wind Harmer
5.728
970833AG2-524 GEN
Solar/Wind Harmer
3.819
971611AH1-305 GEN
Solar/Wind Harmer
3.084
274746AC1-111 G10
Adder
4.142
274744AC1-111 GEN8
Adder
4.142
970289AG2-191 GEN
Solar/Wind Harmer
0.971
270594AE1-207 GEN
Solar/Wind Harmer
5.661
276868AE1-113 GEN
Solar/Wind Harmer
1.012
276882AE2-255 GEN
Solar/Wind Harmer
0.59
971177AH1-047 GEN
Solar/Wind Harmer
3.102
971411AH1-196 GEN
Solar/Wind Harmer
7.515
971675AH1-338 GEN
Solar/Wind Harmer
1.952
970115AG2-085 GEN
Solar/Wind Harmer
1.996
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
9.953
274823ROCKFORD ;21
Adder
13.855
276612AE2-035 GEN
Solar/Wind Harmer
0.001
926823AC1-168 GEN
Solar/Wind Harmer
0.837
970169AG2-114 GEN
Solar/Wind Harmer
4.915
971681AH1-341 GEN
Solar/Wind Harmer
7.885
971549AH1-272 GEN
Solar/Wind Harmer
10.103
961011AF2-392 GEN
Solar/Wind Harmer
2.842
957751AF2-069 GEN
Solar/Wind Harmer
0.159
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
276655WTG1_EQ
Solar/Wind Harmer
0.002
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
4.986
941731AE2-173 GEN
Solar/Wind Harmer
3.957
946321AF1-296 GEN
Solar/Wind Harmer
2.629
963841AG1-237 GEN
Solar/Wind Harmer
2.014
270240V3-007_GEN2
Solar/Wind Harmer
0.001
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.161
276848AB2-070 GEN3
Solar/Wind Harmer
0.16
270543AE2-219 C
Solar/Wind Harmer
0.002
944221AF1-090 GEN
Solar/Wind Harmer
2.367
971029AG2-637 GEN
Solar/Wind Harmer
5.468
971673AH1-337 GEN
Solar/Wind Harmer
2.273
247607V1-011 GEN
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Helper
8.571
270317AD1-130_GEN
Solar/Wind Helper
4.044
966831AG1-554 GEN
Solar/Wind Helper
0.856
270284AF1-227 GEN1
Solar/Wind Helper
1.824
270286AF1-227 GEN2
Solar/Wind Helper
0.669
270287AF1-227 GEN3
Solar/Wind Helper
0.669
270499AE1-146 GEN
Solar/Wind Helper
1.895
945641AF1-229 GEN
Solar/Wind Helper
0.904
24791305MDL-5G
Solar/Wind Harmer
0.001
957471AF2-041 GEN
Solar/Wind Harmer
14.929
959081AF2-199 GEN
Solar/Wind Harmer
4.976
971067AG2-660 GEN
Solar/Wind Harmer
1.659
274822ROCKFORD ;11
Adder
13.956
970825AG2-519 GEN
Solar/Wind Harmer
1.759
972235AH1-702 GEN1
Adder
1.788
970819AG2-516 GEN
Solar/Wind Harmer
5.921
970569AG2-363 GEN
Solar/Wind Harmer
14.789
971475AH1-234 GEN
Solar/Wind Harmer
2.388
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
6.505
274766LEE CO EC;7U
Adder
6.428
276903AD2-071 C
Solar/Wind Harmer
5.417
276158O29GEN2
Solar/Wind Harmer
0.001
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.002
274877BISHOP HL;1U
Solar/Wind Harmer
0.161
276726Z2-087_GEN
Solar/Wind Harmer
0.002
939741AE1-205 GEN
Solar/Wind Harmer
6.647
274854TWINGROVE;U2
Solar/Wind Harmer
0.002
972175AH1-670 GEN
Solar/Wind Harmer
3.748
963741AG1-226 GEN
Solar/Wind Harmer
10.683
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
3.3
247536S-71 GEN
Solar/Wind Harmer
0.179
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
1.713
276615X2-022 GEN
Solar/Wind Harmer
0.046
965911AG1-460 GEN
Solar/Wind Harmer
0.838
24728605AND G2
Adder
2.125
970773AG2-487 GEN
Solar/Wind Harmer
0.635
270445AC2-157 GEN2
Solar/Wind Harmer
0.002
970333AG2-219 GEN
Solar/Wind Harmer
2.323
246936BC-WTG1
Solar/Wind Helper
10.843
270462AD2-086
Solar/Wind Helper
3.651
270223U2-072_GEN1
Solar/Wind Helper
0.855
270578AF1-285 GEN2
Solar/Wind Helper
0.579
270391AF1-285 GEN3
Solar/Wind Helper
0.579
247522W1-056 GEN
Solar/Wind Helper
1.138
960841AF2-375 GEN
Solar/Wind Helper
1.139
270349AD2-093_GEN
Solar/Wind Helper
0.817
274808UNIV PK N;4U
Adder
3.841
274770LINCOLN ;1U
Adder
6.474
274771LINCOLN ;2U
Adder
6.474
274803UNIV PARK;6U
Adder
4.445
274888KELLY CRK;1U
Solar/Wind Harmer
0.311
274887GEN-1.85
Solar/Wind Harmer
0.139
276843GEN-1.7
Solar/Wind Harmer
0.171
958011AF2-095 GEN
Solar/Wind Harmer
7.629
972259AH1-714 GEN
Adder
14.402
274674JOLIET 9 ;6U
Adder
11.55
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
971573AH1-285 GEN
Solar/Wind Harmer
0.959
958481AF2-142 GEN
Solar/Wind Harmer
7.707
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.695
274695ROCKY RD ;2P
Adder
8.163
274693ROCKY RD ;1P
Adder
8.082
274697ROCKY RD ;3P
Adder
2.217
274696ROCKY RD ;4P
Adder
8.355
274683WAUKEGAN ;8U
Adder
15.422
274683WAUKEGAN ;8U
Adder
13
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
962691AG1-118 GEN
Solar/Wind Harmer
15.227
958491AF2-143 GEN
Solar/Wind Harmer
7.614
970921AG2-575 GEN
Solar/Wind Harmer
5.064
970921AG2-575 GEN
Solar/Wind Harmer
1.688
971613AH1-306 GEN
Solar/Wind Harmer
2.426
274879MINONK ;1U
Solar/Wind Harmer
0.213
942991AE2-321 GEN
Solar/Wind Harmer
5.619
971333AH1-146 GEN
Solar/Wind Harmer
10.011
971335AH1-147 GEN
Solar/Wind Harmer
10.011
960441AF2-335 GEN
Solar/Wind Harmer
4.991
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
971341AH1-150 GEN
Solar/Wind Harmer
9.953
971343AH1-151 GEN
Solar/Wind Harmer
9.953
970825AG2-519 GEN
Solar/Wind Harmer
5.49
274856ECOGROVE ;U1
Solar/Wind Harmer
0.116
276611AD2-172 GEN
Solar/Wind Harmer
0.001
938861AE1-114 GEN
Solar/Wind Harmer
2.774
274764LEE CO EC;5U
Adder
6.52
274765LEE CO EC;6U
Adder
6.52
274762LEE CO EC;3U
Adder
6.505
274763LEE CO EC;4U
Adder
6.443
276603SUBLETTE C
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.365
270201AC2-176 GEN
Solar/Wind Harmer
0.001
972267AH1-718 GEN
Adder
2.883
276741O09 GEN1
Solar/Wind Harmer
0.172
276708O09 GEN2
Solar/Wind Harmer
0.172
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.189
276646AC1-214 GEN2
Solar/Wind Harmer
0.189
966841AG1-555 GEN
Solar/Wind Harmer
0.542
276782AC1-033 GEN
Solar/Wind Harmer
0.001
247621Y3-024
Adder
0.165
960611AF2-352 GEN
Solar/Wind Harmer
1.556
970241AG2-163 GEN
Solar/Wind Harmer
2.633
24379505HDWTR1G C
Solar/Wind Harmer
0.001
270209AC1-174_GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
270383AD1-128 GEN
Solar/Wind Harmer
0.003
276916AD2-100_GEN
Solar/Wind Harmer
8.729
276911AD2-131_GEN
Solar/Wind Harmer
0.575
970883AG2-550 GEN
Solar/Wind Harmer
4.063
970885AG2-551 GEN
Solar/Wind Harmer
1.354
945391AF1-204 GEN
Solar/Wind Harmer
4.312
970623AG2-406 GEN
Solar/Wind Harmer
0.709
270444AC2-157 GEN1
Solar/Wind Harmer
0.002
971587AH1-292 GEN
Solar/Wind Harmer
2.538
270007AE1-245 C
Solar/Wind Harmer
0.001
970239AG2-162 GEN
Solar/Wind Harmer
0.812
246938BC-WTG3
Solar/Wind Helper
11.029
246937BC-WTG2
Solar/Wind Helper
10.843
270224U2-072_GEN2
Solar/Wind Helper
0.855
270227U2-072_GEN3
Solar/Wind Helper
0.855
270228U2-072_GEN4
Solar/Wind Helper
0.855
270231U2-072_GEN5
Solar/Wind Helper
0.855
270471AD2-092_GEN
Solar/Wind Helper
0.817
253378AE2-206_GEN
Solar/Wind Helper
0.657
276820AF1-078_GEN
Solar/Wind Helper
0.307
241960AC2-195 GEN
Solar/Wind Helper
0.657
944201AF1-088_MTX
Adder
57.673
957141AF2-008_MTX
Adder
8.943
990792J1392
External Queue
5.474584102630615
990497J1323
External Queue
1.5914489030838013
LAGNLTFEXP_LAGN->PJM
CLTF
6.132
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.094
TVALTFEXP_TVA->PJM
CLTF
2.49
CBM West 2LTFEXP_CBM-W2->PJM
CBM
52.858
NYPJM->LTFIMP_NY
CLTF
1.126
LGEELTFEXP_LGEE->PJM
CLTF
1.931
WECLTFEXP_WEC->PJM
CLTF
2.707
AG2-052LTFEXP_AG2-052->PJM
LTF
0.175
AH1-155LTFEXP_AH1-155->PJM
LTF
0.263
CBM West 1LTFEXP_CBM-W1->PJM
CBM
72.466
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.567
MECLTFEXP_MEC->PJM
CLTF
10.019
SIGELTFEXP_SIGE->PJM
CLTF
0.208

Details for 05BOKESCRK-05MARYSV 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05BOKESCRK-05MARYSV 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7445_05MARYSV 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.99 %
Rating:1302.0 MVA
Rating Type:B
MVA to Mitigate:1536.23
MW Contribution:8.28
Bus #Bus NameTypeMW Contribution
965431AG1-411 GEN
50/50
12.58
24727105RPMNG2
50/50
0.95
942871AE2-306 GEN
Solar/Wind Harmer
3.979
270391AF1-285 GEN3
Solar/Wind Harmer
2.041
270485AE1-090_GEN
Solar/Wind Harmer
2.304
270491AE1-102 GEN2
Solar/Wind Harmer
1.46
270588AE1-091_GEN
Solar/Wind Harmer
10.946
270541AE2-072 C
Solar/Wind Harmer
3.904
958091AF2-103 GEN
Solar/Wind Harmer
0.136
270575GUS2 35KV
Solar/Wind Harmer
7.614
270258AD1-119 GEN
Solar/Wind Harmer
2.055
270044AE2-322 C
Solar/Wind Harmer
0.958
270404AC1-167 GEN
Solar/Wind Harmer
0.797
270191TR4_S_V150
Solar/Wind Harmer
2.148
270247TR4_N_V136
Solar/Wind Harmer
0.609
959331AF2-224 GEN
Solar/Wind Harmer
6.922
965021AG1-366 GEN
Solar/Wind Harmer
1.61
23906502RICHG2&3
Adder
0.822
958321AF2-126 GEN
Solar/Wind Harmer
0.806
241832AE2-181_GEN
Solar/Wind Harmer
0.902
23929302BS-PKR
Adder
0.782
970031AG2-029 GEN
Solar/Wind Harmer
15.427
270043AE2-236 GEN
Solar/Wind Harmer
2.738
270377AD1-106 GEN
Solar/Wind Harmer
2.718
945111AF1-176 GEN
Solar/Wind Harmer
2.442
247643Z2-116 C
Solar/Wind Harmer
0.03
971617AH1-308 GEN
Solar/Wind Harmer
2.507
270466AD2-091
50/50
22.116
270224U2-072_GEN2
Solar/Wind Harmer
8.675
270227U2-072_GEN3
Solar/Wind Harmer
8.675
270228U2-072_GEN4
Solar/Wind Harmer
8.675
270231U2-072_GEN5
Solar/Wind Harmer
8.675
246938BC-WTG3
Solar/Wind Harmer
4.471
246937BC-WTG2
Solar/Wind Harmer
4.395
270007AE1-245 C
Solar/Wind Harmer
4.993
942801AE2-298 GEN
Solar/Wind Harmer
1.179
970611AG2-400 GEN
Solar/Wind Harmer
6.922
971677AH1-339 GEN
Solar/Wind Harmer
5.222
241996AE2-282_GEN
Solar/Wind Harmer
0.963
247620Y3-023
Adder
0.211
971231AH1-075 GEN
Solar/Wind Harmer
0.352
270036AE2-216 BAT
50/50
24.327
24727205RPMNG3
50/50
0.942
270284AF1-227 GEN1
Solar/Wind Harmer
35.4
270286AF1-227 GEN2
Solar/Wind Harmer
13.096
270287AF1-227 GEN3
Solar/Wind Harmer
13.096
270578AF1-285 GEN2
Solar/Wind Harmer
2.041
270302AB2-170 GEN
Solar/Wind Harmer
31.863
270317AD1-130_GEN
Solar/Wind Harmer
12.215
957201AF2-014 GEN
Solar/Wind Harmer
5.094
270435AC2-044 GEN
Solar/Wind Harmer
2.246
270297AD1-101 GEN
Solar/Wind Harmer
2.352
247607V1-011 GEN
Solar/Wind Harmer
3.327
966831AG1-554 GEN
Solar/Wind Harmer
0.997
971989AH1-539 GEN
Solar/Wind Harmer
10.779
270499AE1-146 GEN
Solar/Wind Harmer
2.04
965051AG1-369 GEN
Solar/Wind Harmer
3.576
965041AG1-368 GEN
Solar/Wind Harmer
7.155
945411AF1-206 GEN
Solar/Wind Harmer
3.599
970817AG2-515 GEN
Solar/Wind Harmer
5.709
972211AH1-690 GEN
Adder
87.557
963791AG1-232 GEN
Solar/Wind Harmer
7.374
945641AF1-229 GEN
Solar/Wind Harmer
1.909
270071AF1-092 GEN
Solar/Wind Harmer
6.82
971549AH1-272 GEN
Solar/Wind Harmer
8.28
270024AE2-089 GEN
Solar/Wind Harmer
2.024
270520AE2-214 GEN
Solar/Wind Helper
2.538
270054AF2-122 C O1
Solar/Wind Helper
0.659
24727005RPMNG1
50/50
0.947
270223U2-072_GEN1
Solar/Wind Harmer
8.675
270578AF1-285 GEN2
Solar/Wind Harmer
5.305
270391AF1-285 GEN3
Solar/Wind Harmer
5.305
270462AD2-086
Solar/Wind Harmer
26.506
246936BC-WTG1
Solar/Wind Harmer
4.395
270489AE1-102 GEN1
Solar/Wind Harmer
1.46
965421AG1-410 GEN
Solar/Wind Harmer
32.457
247522W1-056 GEN
Solar/Wind Harmer
1.843
960841AF2-375 GEN
Solar/Wind Harmer
3.015
24695305TIMB G C
Solar/Wind Harmer
4.219
270361_3
Solar/Wind Harmer
6.463
247521TR3_G114
Solar/Wind Harmer
2.408
270246TR4_N_V150
Solar/Wind Harmer
0.609
965011AG1-365 GEN
Solar/Wind Harmer
6.922
23906502RICHG2&3
Adder
0.822
972301AH1-735 GEN
Adder
4.089
23906402RICHG1
Adder
0.818
241840AF1-064_GEN
Solar/Wind Harmer
0.752
23920202STRYCT
Adder
0.86
944231AF1-091 GEN
Solar/Wind Harmer
2.303
241808AF1-120 C
Solar/Wind Harmer
0.537
241858AF1-205_GEN
Solar/Wind Harmer
2.383
972253AH1-711 GEN
Adder
18.549
270063AE2-323 C
Solar/Wind Harmer
1.091
24639705ELKHART HY
Adder
0.068
945111AF1-176 GEN
Solar/Wind Harmer
7.706
270349AD2-093_GEN
Solar/Wind Helper
1.798
942221AE2-234 GEN
Solar/Wind Harmer
0.32
270216AD2-079_GEN
Solar/Wind Harmer
0.262
270471AD2-092_GEN
Solar/Wind Helper
1.798
946101AF1-275 GEN
Solar/Wind Helper
0.318
LAGNLTFEXP_LAGN->PJM
CLTF
2.114
TVALTFEXP_TVA->PJM
CLTF
0.753
CBM West 2LTFEXP_CBM-W2->PJM
CBM
20.723
NYPJM->LTFIMP_NY
CLTF
0.798
LGEELTFEXP_LGEE->PJM
CLTF
0.744
WECLTFEXP_WEC->PJM
CLTF
1.222
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.369
AG2-052LTFEXP_AG2-052->PJM
LTF
0.08
AH1-155LTFEXP_AH1-155->PJM
LTF
0.12
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.177
CBM West 1LTFEXP_CBM-W1->PJM
CBM
51.204
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.052
MECLTFEXP_MEC->PJM
CLTF
4.384
SIGELTFEXP_SIGE->PJM
CLTF
0.085

Details for 05BOKESCRK-05MARYSV 345.0 kV Ckt 1 line l/o AEP_P4_#7441_05SORENS 765_J1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05BOKESCRK-05MARYSV 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7441_05SORENS 765_J1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.86 %
Rating:1302.0 MVA
Rating Type:B
MVA to Mitigate:1443.45
MW Contribution:8.65
Bus #Bus NameTypeMW Contribution
24727005RPMNG1
50/50
0.986
270223U2-072_GEN1
Solar/Wind Harmer
8.881
270578AF1-285 GEN2
Solar/Wind Harmer
5.431
270391AF1-285 GEN3
Solar/Wind Harmer
5.431
270462AD2-086
Solar/Wind Harmer
27.18
246936BC-WTG1
Solar/Wind Harmer
4.579
270489AE1-102 GEN1
Solar/Wind Harmer
1.521
965421AG1-410 GEN
Solar/Wind Harmer
33.814
247522W1-056 GEN
Solar/Wind Harmer
1.977
960841AF2-375 GEN
Solar/Wind Harmer
3.224
24695305TIMB G C
Solar/Wind Harmer
4.424
270361_3
Solar/Wind Harmer
6.922
247521TR3_G114
Solar/Wind Harmer
2.532
270246TR4_N_V150
Solar/Wind Harmer
0.641
23906502RICHG2&3
Adder
0.873
965011AG1-365 GEN
Solar/Wind Harmer
7.215
972301AH1-735 GEN
Adder
4.34
23906402RICHG1
Adder
0.868
241840AF1-064_GEN
Solar/Wind Harmer
0.802
23920202STRYCT
Adder
0.918
944231AF1-091 GEN
Solar/Wind Harmer
2.414
241808AF1-120 C
Solar/Wind Harmer
0.574
241858AF1-205_GEN
Solar/Wind Harmer
2.55
972253AH1-711 GEN
Adder
19.928
270063AE2-323 C
Solar/Wind Harmer
1.135
24639705ELKHART HY
Adder
0.071
945111AF1-176 GEN
Solar/Wind Harmer
8.008
270449AD2-020 GEN
Solar/Wind Harmer
1.247
943021AE2-325 GEN
Solar/Wind Harmer
1.62
270505AE1-170 C O1
Solar/Wind Harmer
6.636
270428AC2-015 C
Solar/Wind Harmer
2.363
270349AD2-093_GEN
Solar/Wind Helper
1.579
965431AG1-411 GEN
50/50
13.106
24727105RPMNG2
50/50
0.99
942871AE2-306 GEN
Solar/Wind Harmer
4.074
270391AF1-285 GEN3
Solar/Wind Harmer
2.089
270485AE1-090_GEN
Solar/Wind Harmer
2.363
270491AE1-102 GEN2
Solar/Wind Harmer
1.521
270588AE1-091_GEN
Solar/Wind Harmer
11.649
270541AE2-072 C
Solar/Wind Harmer
4.133
958091AF2-103 GEN
Solar/Wind Harmer
0.143
270575GUS2 35KV
Solar/Wind Harmer
8.155
270258AD1-119 GEN
Solar/Wind Harmer
2.165
270044AE2-322 C
Solar/Wind Harmer
1.008
270404AC1-167 GEN
Solar/Wind Harmer
0.84
270191TR4_S_V150
Solar/Wind Harmer
2.259
270247TR4_N_V136
Solar/Wind Harmer
0.641
23906502RICHG2&3
Adder
0.873
959331AF2-224 GEN
Solar/Wind Harmer
7.215
965021AG1-366 GEN
Solar/Wind Harmer
1.678
958321AF2-126 GEN
Solar/Wind Harmer
0.86
241832AE2-181_GEN
Solar/Wind Harmer
0.964
23929302BS-PKR
Adder
0.842
970031AG2-029 GEN
Solar/Wind Harmer
16.057
270043AE2-236 GEN
Solar/Wind Harmer
2.85
270377AD1-106 GEN
Solar/Wind Harmer
3.103
971617AH1-308 GEN
Solar/Wind Harmer
2.638
945111AF1-176 GEN
Solar/Wind Harmer
2.538
247643Z2-116 C
Solar/Wind Harmer
0.031
247604X1-042
Adder
0.185
270036AE2-216 BAT
50/50
24.946
24727205RPMNG3
50/50
0.982
270284AF1-227 GEN1
Solar/Wind Harmer
36.123
270286AF1-227 GEN2
Solar/Wind Harmer
13.364
270287AF1-227 GEN3
Solar/Wind Harmer
13.364
270578AF1-285 GEN2
Solar/Wind Harmer
2.089
270302AB2-170 GEN
Solar/Wind Harmer
32.674
270317AD1-130_GEN
Solar/Wind Harmer
12.526
957201AF2-014 GEN
Solar/Wind Harmer
5.307
270435AC2-044 GEN
Solar/Wind Harmer
2.34
966831AG1-554 GEN
Solar/Wind Harmer
1.072
971989AH1-539 GEN
Solar/Wind Harmer
11.594
270297AD1-101 GEN
Solar/Wind Harmer
2.489
247607V1-011 GEN
Solar/Wind Harmer
3.496
270499AE1-146 GEN
Solar/Wind Harmer
2.176
270466AD2-091
50/50
22.679
270224U2-072_GEN2
Solar/Wind Harmer
8.881
270227U2-072_GEN3
Solar/Wind Harmer
8.881
270228U2-072_GEN4
Solar/Wind Harmer
8.881
270231U2-072_GEN5
Solar/Wind Harmer
8.881
246938BC-WTG3
Solar/Wind Harmer
4.658
246937BC-WTG2
Solar/Wind Harmer
4.579
270007AE1-245 C
Solar/Wind Harmer
5.246
942801AE2-298 GEN
Solar/Wind Harmer
1.244
970611AG2-400 GEN
Solar/Wind Harmer
7.215
971677AH1-339 GEN
Solar/Wind Harmer
5.666
241996AE2-282_GEN
Solar/Wind Harmer
1.03
971231AH1-075 GEN
Solar/Wind Harmer
0.402
247620Y3-023
Adder
0.219
942221AE2-234 GEN
Solar/Wind Harmer
0.335
270216AD2-079_GEN
Solar/Wind Harmer
0.272
961051AF2-396 GEN
Solar/Wind Harmer
7.083
961051AF2-396 GEN
Solar/Wind Harmer
3.295
960981AF2-389 GEN
Solar/Wind Harmer
0.67
957891AF2-083 GEN
Solar/Wind Harmer
1.495
270471AD2-092_GEN
Solar/Wind Helper
1.579
24441205WTRV SLR C
Solar/Wind Harmer
0.06
944531AF1-118 GEN
Solar/Wind Harmer
15.258
24642205MAYFLWER
Adder
0.276
965051AG1-369 GEN
Solar/Wind Harmer
3.76
965041AG1-368 GEN
Solar/Wind Harmer
7.49
945411AF1-206 GEN
Solar/Wind Harmer
3.846
970817AG2-515 GEN
Solar/Wind Harmer
6.123
972211AH1-690 GEN
Adder
94.166
945641AF1-229 GEN
Solar/Wind Harmer
2.109
963791AG1-232 GEN
Solar/Wind Harmer
7.721
270071AF1-092 GEN
Solar/Wind Harmer
7.086
971549AH1-272 GEN
Solar/Wind Harmer
8.654
270024AE2-089 GEN
Solar/Wind Harmer
2.13
944161AF1-084 GEN
Solar/Wind Harmer
0.983
971771AH1-392 GEN
Solar/Wind Harmer
3.88
LAGNLTFEXP_LAGN->PJM
CLTF
1.858
TVALTFEXP_TVA->PJM
CLTF
0.593
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CBM West 2LTFEXP_CBM-W2->PJM
CBM
19.885
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.774
LGEELTFEXP_LGEE->PJM
CLTF
0.737
WECLTFEXP_WEC->PJM
CLTF
1.252
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.545
AG2-052LTFEXP_AG2-052->PJM
LTF
0.082
AH1-155LTFEXP_AH1-155->PJM
LTF
0.124
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.293
CBM West 1LTFEXP_CBM-W1->PJM
CBM
53.067
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.552
MECLTFEXP_MEC->PJM
CLTF
4.428
SIGELTFEXP_SIGE->PJM
CLTF
0.085

Details for 05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#709_546_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:107.02 %
Rating:5001.0 MVA
Rating Type:B
MVA to Mitigate:5352.14
MW Contribution:19.84
Bus #Bus NameTypeMW Contribution
274775LINCOLN ;6U
50/50
17.85
274776LINCOLN ;7U
50/50
17.85
274777LINCOLN ;8U
50/50
17.85
971347AH1-153 GEN
Solar/Wind Harmer
21.507
972227AH1-698 GEN1
Adder
4.91
960591AF2-350 GEN
Solar/Wind Harmer
13.078
970833AG2-524 GEN
Solar/Wind Harmer
14.352
970833AG2-524 GEN
Solar/Wind Harmer
9.568
274827FISK ;RP
Adder
14.495
274675JOLIET 29;7U
Adder
57.233
274675JOLIET 29;7U
Adder
55.189
972037AH1-567 GEN1
Adder
0.341
274687WILL CNTY;4U
Adder
52.082
274687WILL CNTY;4U
Adder
52.082
274746AC1-111 G10
Adder
10.407
274744AC1-111 GEN8
Adder
10.407
274731ELWOOD EC;2P
Adder
30.563
274733ELWOOD EC;3P
Adder
30.563
274735ELWOOD EC;4P
Adder
30.563
274728ELWOOD EC;5P
Adder
30.562
960681AF2-359 GEN
Solar/Wind Harmer
-0.002
274814UNIV PK N;0U
Adder
9.363
274807UNIV PK N;3U
Adder
9.343
274805UNIV PK N;1U
Adder
9.302
274811UNIV PK N;7U
Adder
9.282
971177AH1-047 GEN
Solar/Wind Harmer
7.706
971675AH1-338 GEN
Solar/Wind Harmer
4.855
971411AH1-196 GEN
Solar/Wind Harmer
18.647
276868AE1-113 GEN
Solar/Wind Harmer
2.486
276882AE2-255 GEN
Solar/Wind Harmer
1.449
971171AH1-044 GEN
Solar/Wind Harmer
24.671
274823ROCKFORD ;21
Adder
34.283
274863CRW1-WTG
Solar/Wind Harmer
0.004
274864CRW2-WTG
Solar/Wind Harmer
0.004
971769AH1-391 GEN
Solar/Wind Harmer
13.669
276612AE2-035 GEN
Solar/Wind Harmer
0.003
971681AH1-341 GEN
Solar/Wind Harmer
19.428
926823AC1-168 GEN
Solar/Wind Harmer
2.047
970169AG2-114 GEN
Solar/Wind Harmer
11.99
24344105CKG2
50/50
18.673
274773LINCOLN ;4U
50/50
17.85
274774LINCOLN ;5U
50/50
17.85
970245AG2-165 GEN
Solar/Wind Harmer
7.237
941551AE2-152 GEN
Solar/Wind Harmer
0.001
276164X3-005 C
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
1.365
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
274801UNIV PARK;4U
Adder
10.893
274676JOLIET 29;8U
Adder
57.231
274723RIVER EC ;12
Adder
33.419
274674JOLIET 9 ;6U
Adder
28.688
274745AC1-111 GEN9
Adder
10.407
274732ELWOOD EC;7P
Adder
30.562
274812UNIV PK N;8U
Adder
9.282
274751CRETE EC ;1U
Adder
15.16
274754CRETE EC ;4U
Adder
15.16
274682WAUKEGAN ;7U
Adder
32.772
274828WAUKEGAN ;BP
Adder
20.11
962781AG1-127 GEN
Solar/Wind Harmer
12.035
274872LEEDK;1U
Solar/Wind Harmer
0.008
276691AA1-018 GEN1
Solar/Wind Harmer
1.527
939401AE1-172 GEN
Solar/Wind Harmer
9.369
276901AD2-066 C O1
Solar/Wind Harmer
0.012
276861AD2-134 GEN
Solar/Wind Harmer
0.223
971997AH1-543 GEN
Solar/Wind Harmer
6.52
957471AF2-041 GEN
Solar/Wind Harmer
37.007
959081AF2-199 GEN
Solar/Wind Harmer
12.336
971067AG2-660 GEN
Solar/Wind Harmer
4.112
274822ROCKFORD ;11
Adder
34.533
972235AH1-702 GEN1
Adder
4.422
970819AG2-516 GEN
Solar/Wind Harmer
14.623
276876AE1-163_GEN2
Solar/Wind Harmer
0.003
970373AG2-245 GEN
Solar/Wind Harmer
25.567
971475AH1-234 GEN
Solar/Wind Harmer
5.893
970569AG2-363 GEN
Solar/Wind Harmer
36.013
274857EASY ROAD;U1
Solar/Wind Harmer
0.002
274761LEE CO EC;2U
Adder
16.006
274766LEE CO EC;7U
Adder
15.817
270055AF2-134 C O1
Solar/Wind Harmer
0.009
276158O29GEN2
Solar/Wind Harmer
0.001
274877BISHOP HL;1U
Solar/Wind Harmer
0.39
958381AF2-132 GEN
Solar/Wind Harmer
0.002
964861AG1-349 GEN
Solar/Wind Harmer
-0.002
971917AH1-482 GEN
Solar/Wind Harmer
15.002
276726Z2-087_GEN
Solar/Wind Harmer
0.004
939741AE1-205 GEN
Solar/Wind Harmer
15.902
270505AE1-170 C O1
Solar/Wind Harmer
11.776
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
13.971
274854TWINGROVE;U2
Solar/Wind Harmer
0.005
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
5.775
945111AF1-176 GEN
Solar/Wind Harmer
18.947
972175AH1-670 GEN
Solar/Wind Harmer
8.763
24791305MDL-5G
Solar/Wind Harmer
0.001
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
3.936
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.004
276615X2-022 GEN
Solar/Wind Harmer
0.104
965911AG1-460 GEN
Solar/Wind Harmer
1.891
24639705ELKHART HY
Adder
0.206
970333AG2-219 GEN
Solar/Wind Harmer
6.645
963741AG1-226 GEN
Solar/Wind Harmer
21.75
970091AG2-072 GEN
Adder
82.54
270445AC2-157 GEN2
Solar/Wind Harmer
0.003
270063AE2-323 C
Solar/Wind Harmer
0.005
274772LINCOLN ;3U
50/50
17.85
970513AG2-328 GEN
Solar/Wind Harmer
7.237
970517AG2-330 GEN
Solar/Wind Harmer
43.42
970349AG2-230 GEN
Solar/Wind Harmer
21.507
970707AG2-453 GEN
Solar/Wind Harmer
44.024
972228AH1-698 GEN2
Adder
6.973
276897AD1-100 C
Solar/Wind Harmer
0.017
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
276806AD2-047 C O1
Solar/Wind Harmer
7.411
970941AG2-585 GEN
Solar/Wind Harmer
16.347
943121AE2-341 GEN
Solar/Wind Harmer
21.899
943591AF1-030 GEN
Solar/Wind Harmer
14.563
274800UNIV PARK;3U
Adder
10.893
972038AH1-567 GEN2
Adder
0.682
274826FISK ;BP
Adder
20.453
274724RIVER EC ;11
Adder
33.063
274676JOLIET 29;8U
Adder
55.187
274802UNIV PARK;5U
Adder
10.868
274729ELWOOD EC;1P
Adder
30.563
274730ELWOOD EC;6P
Adder
30.562
274734ELWOOD EC;8P
Adder
30.562
274736ELWOOD EC;9P
Adder
30.562
276893AG1-478 C
Solar/Wind Harmer
0.513
274752CRETE EC ;2U
Adder
15.16
274753CRETE EC ;3U
Adder
15.16
274682WAUKEGAN ;7U
Adder
32.772
274872LEEDK;1U
Solar/Wind Harmer
0.462
276694AA1-018 GEN2
Solar/Wind Harmer
0.002
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
1.329
274855GSG-6 ;RU
Solar/Wind Harmer
0.457
274850MENDOTA H;RU
Solar/Wind Harmer
0.147
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.223
276805AD2-038 GEN
Solar/Wind Harmer
0.004
959091AF2-200 GEN
Solar/Wind Harmer
24.671
972236AH1-702 GEN2
Adder
3.845
276889AE2-281 GEN
Solar/Wind Harmer
0.001
970571AG2-364 GEN
Solar/Wind Harmer
24.008
274858EASY ROAD;U2
Solar/Wind Harmer
0.002
274760LEE CO EC;1U
Adder
16.006
274767LEE CO EC;8U
Adder
15.817
270535AF1-215 GEN1
Solar/Wind Harmer
0.015
276157O29GEN1
Solar/Wind Harmer
1.906
274878BISHOP HL;2U
Solar/Wind Harmer
0.39
964401AG1-302 GEN
Solar/Wind Harmer
0.002
24642205MAYFLWER
Adder
1.04
942111AE2-223 GEN
Solar/Wind Harmer
3.691
965931AG1-462 GEN
Solar/Wind Harmer
28.855
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
247604X1-042
Adder
0.671
24441205WTRV SLR C
Solar/Wind Harmer
0
274853TWINGROVE;U1
Solar/Wind Harmer
0.004
965091AG1-374 GEN
Solar/Wind Harmer
33.249
959611AF2-252 GEN
Solar/Wind Harmer
3.694
945111AF1-176 GEN
Solar/Wind Harmer
8.607
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
10.541
247643Z2-116 C
Solar/Wind Harmer
0
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
4.7
276668AB2-070 GEN1
Solar/Wind Harmer
0.371
276621W2-048 GEN
Solar/Wind Harmer
0.501
276838X2-022 GEN2
Solar/Wind Harmer
0.559
942481AE2-261 GEN
Solar/Wind Harmer
28.269
970243AG2-164 GEN
Solar/Wind Harmer
5.436
970519AG2-331 GEN
Solar/Wind Harmer
24.162
970699AG2-449 GEN
Solar/Wind Harmer
2.323
970193AG2-126 GEN
Solar/Wind Harmer
11.787
961011AF2-392 GEN
Solar/Wind Harmer
6.975
270536AF1-215 GEN2
Solar/Wind Harmer
0.015
957751AF2-069 GEN
Solar/Wind Harmer
0.386
274848CAMPGROVE;RU
Solar/Wind Harmer
0.002
971771AH1-392 GEN
Solar/Wind Harmer
11.509
958391AF2-133 GEN
Solar/Wind Harmer
0.002
946321AF1-296 GEN
Solar/Wind Harmer
6.384
276655WTG1_EQ
Solar/Wind Harmer
0.005
276656WTG2_EQ
Solar/Wind Harmer
0.001
959341AF2-225 GEN
Solar/Wind Harmer
11.926
941731AE2-173 GEN
Solar/Wind Harmer
9.465
971619AH1-309 GEN
Solar/Wind Harmer
5.047
971611AH1-305 GEN
Solar/Wind Harmer
6.654
24690905MDL-1G C
Solar/Wind Harmer
0.003
270180AB1-006 GEN1
Solar/Wind Harmer
0.003
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.002
270181AB1-006 GEN2
Solar/Wind Harmer
0
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.371
276848AB2-070 GEN3
Solar/Wind Harmer
0.369
24386205FR-12G C
Solar/Wind Harmer
0.002
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.002
971549AH1-272 GEN
Solar/Wind Harmer
19.837
963841AG1-237 GEN
Solar/Wind Harmer
4.152
944221AF1-090 GEN
Solar/Wind Harmer
5.24
274770LINCOLN ;1U
50/50
17.85
274771LINCOLN ;2U
50/50
17.85
274661LASCO STA;2U
50/50
13.726
972259AH1-714 GEN
50/50
38.528
274660LASCO STA;1U
50/50
13.902
970321AG2-212 GEN
Solar/Wind Harmer
7.237
274888KELLY CRK;1U
Solar/Wind Harmer
0.768
274887GEN-1.85
Solar/Wind Harmer
0.344
276843GEN-1.7
Solar/Wind Harmer
0.423
958011AF2-095 GEN
Solar/Wind Harmer
18.832
274847GR RIDGE ;BU
Solar/Wind Harmer
0.005
274803UNIV PARK;6U
Adder
10.868
274674JOLIET 9 ;6U
Adder
28.688
971573AH1-285 GEN
Solar/Wind Harmer
2.415
965681AG1-436 GEN
Solar/Wind Harmer
16.18
965791AG1-447 GEN
Solar/Wind Harmer
11.865
274808UNIV PK N;4U
Adder
9.241
274695ROCKY RD ;2P
Adder
20.397
274693ROCKY RD ;1P
Adder
20.196
274697ROCKY RD ;3P
Adder
5.541
274696ROCKY RD ;4P
Adder
20.877
274683WAUKEGAN ;8U
Adder
38.365
274683WAUKEGAN ;8U
Adder
32.34
962691AG1-118 GEN
Solar/Wind Harmer
38.059
970921AG2-575 GEN
Solar/Wind Harmer
12.646
970921AG2-575 GEN
Solar/Wind Harmer
4.215
958481AF2-142 GEN
Solar/Wind Harmer
18.909
274861TOP CROP ;1U
Solar/Wind Harmer
0.003
274862TOP CROP ;2U
Solar/Wind Harmer
1.704
942991AE2-321 GEN
Solar/Wind Harmer
13.961
971333AH1-146 GEN
Solar/Wind Harmer
24.851
971335AH1-147 GEN
Solar/Wind Harmer
24.851
958491AF2-143 GEN
Solar/Wind Harmer
18.638
274879MINONK ;1U
Solar/Wind Harmer
0.523
971341AH1-150 GEN
Solar/Wind Harmer
24.671
971343AH1-151 GEN
Solar/Wind Harmer
24.671
24441505OLIV SLR
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0.003
274856ECOGROVE ;U1
Solar/Wind Harmer
0.287
276611AD2-172 GEN
Solar/Wind Harmer
0.003
270526AF1-158 GEN
Solar/Wind Harmer
0.015
938861AE1-114 GEN
Solar/Wind Harmer
6.835
274764LEE CO EC;5U
Adder
16.043
274765LEE CO EC;6U
Adder
16.043
274762LEE CO EC;3U
Adder
16.006
274763LEE CO EC;4U
Adder
15.855
276603SUBLETTE C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
7.071
276741O09 GEN1
Solar/Wind Harmer
0.42
276708O09 GEN2
Solar/Wind Harmer
0.42
274851PROVIDENC;RU
Solar/Wind Harmer
0.002
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.46
276646AC1-214 GEN2
Solar/Wind Harmer
0.46
276782AC1-033 GEN
Solar/Wind Harmer
0.002
960611AF2-352 GEN
Solar/Wind Harmer
3.694
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
21.794
961051AF2-396 GEN
Solar/Wind Harmer
14.53
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
270216AD2-079_GEN
Solar/Wind Harmer
0.002
276763AC1-053 GEN1
Solar/Wind Harmer
0.002
276764AC1-053 GEN2
Solar/Wind Harmer
0.002
966841AG1-555 GEN
Solar/Wind Harmer
1.132
276916AD2-100_GEN
Solar/Wind Harmer
19.606
276911AD2-131_GEN
Solar/Wind Harmer
1.292
970239AG2-162 GEN
Solar/Wind Harmer
2.323
970241AG2-163 GEN
Solar/Wind Harmer
5.361
247620Y3-023
Adder
0.558
945391AF1-204 GEN
Solar/Wind Harmer
8.349
270444AC2-157 GEN1
Solar/Wind Harmer
0.003
971587AH1-292 GEN
Solar/Wind Harmer
5.427
944201AF1-088_MTX
Adder
123.331
957141AF2-008_MTX
Adder
2.025
LAGNLTFEXP_LAGN->PJM
CLTF
11.269
TVALTFEXP_TVA->PJM
CLTF
3.981
CBM West 2LTFEXP_CBM-W2->PJM
CBM
99.862
NYPJM->LTFIMP_NY
CLTF
2.757
LGEELTFEXP_LGEE->PJM
CLTF
3.235
WECLTFEXP_WEC->PJM
CLTF
6.675
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.012
AG2-052LTFEXP_AG2-052->PJM
LTF
0.385
AH1-155LTFEXP_AH1-155->PJM
LTF
0.577
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.458
CBM West 1LTFEXP_CBM-W1->PJM
CBM
183.505
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.444
MECLTFEXP_MEC->PJM
CLTF
23.446
SIGELTFEXP_SIGE->PJM
CLTF
0.348

Details for 05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line l/o Base Case


Base Case Flowgate

Area:AEP
Facility Description:
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.56 %
Rating:4558.0 MVA
Rating Type:A
MVA to Mitigate:4583.47
MW Contribution:17.65
Bus #Bus NameTypeMW Contribution
24344105CKG2
50/50
17.317
274773LINCOLN ;4U
50/50
16.207
274774LINCOLN ;5U
50/50
16.207
970245AG2-165 GEN
Solar/Wind Harmer
6.588
941551AE2-152 GEN
Solar/Wind Harmer
0.001
276164X3-005 C
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
1.232
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
274801UNIV PARK;4U
Adder
9.826
274676JOLIET 29;8U
Adder
51.63
274723RIVER EC ;12
Adder
30.145
274674JOLIET 9 ;6U
Adder
25.873
274745AC1-111 GEN9
Adder
9.39
274732ELWOOD EC;7P
Adder
27.553
274812UNIV PK N;8U
Adder
8.365
274751CRETE EC ;1U
Adder
13.652
274772LINCOLN ;3U
50/50
16.207
970513AG2-328 GEN
Solar/Wind Harmer
6.588
970517AG2-330 GEN
Solar/Wind Harmer
39.528
970349AG2-230 GEN
Solar/Wind Harmer
19.648
970707AG2-453 GEN
Solar/Wind Harmer
39.858
972228AH1-698 GEN2
Adder
6.293
276897AD1-100 C
Solar/Wind Harmer
0.016
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
276806AD2-047 C O1
Solar/Wind Harmer
6.686
970941AG2-585 GEN
Solar/Wind Harmer
14.748
943121AE2-341 GEN
Solar/Wind Harmer
19.773
943591AF1-030 GEN
Solar/Wind Harmer
13.149
274826FISK ;BP
Adder
18.452
274800UNIV PARK;3U
Adder
9.826
972038AH1-567 GEN2
Adder
0.615
274724RIVER EC ;11
Adder
29.828
274676JOLIET 29;8U
Adder
49.786
274802UNIV PARK;5U
Adder
9.801
274729ELWOOD EC;1P
Adder
27.554
274730ELWOOD EC;6P
Adder
27.553
274734ELWOOD EC;8P
Adder
27.553
274736ELWOOD EC;9P
Adder
27.553
276893AG1-478 C
Solar/Wind Harmer
0.462
274752CRETE EC ;2U
Adder
13.652
274753CRETE EC ;3U
Adder
13.652
274682WAUKEGAN ;7U
Adder
29.523
274872LEEDK;1U
Solar/Wind Harmer
0.416
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274770LINCOLN ;1U
50/50
16.207
274771LINCOLN ;2U
50/50
16.207
274661LASCO STA;2U
50/50
12.405
972259AH1-714 GEN
50/50
34.82
274660LASCO STA;1U
50/50
12.564
970321AG2-212 GEN
Solar/Wind Harmer
6.588
274888KELLY CRK;1U
Solar/Wind Harmer
0.693
274887GEN-1.85
Solar/Wind Harmer
0.311
276843GEN-1.7
Solar/Wind Harmer
0.382
958011AF2-095 GEN
Solar/Wind Harmer
16.99
274847GR RIDGE ;BU
Solar/Wind Harmer
0.004
274803UNIV PARK;6U
Adder
9.801
274674JOLIET 9 ;6U
Adder
25.873
971573AH1-285 GEN
Solar/Wind Harmer
2.179
965681AG1-436 GEN
Solar/Wind Harmer
14.586
274775LINCOLN ;6U
50/50
16.207
274776LINCOLN ;7U
50/50
16.207
274777LINCOLN ;8U
50/50
16.207
971347AH1-153 GEN
Solar/Wind Harmer
19.648
972227AH1-698 GEN1
Adder
4.431
960591AF2-350 GEN
Solar/Wind Harmer
11.798
970833AG2-524 GEN
Solar/Wind Harmer
12.946
970833AG2-524 GEN
Solar/Wind Harmer
8.631
274827FISK ;RP
Adder
13.077
274675JOLIET 29;7U
Adder
51.632
274675JOLIET 29;7U
Adder
49.788
274687WILL CNTY;4U
Adder
46.979
274687WILL CNTY;4U
Adder
46.979
972037AH1-567 GEN1
Adder
0.308
274746AC1-111 G10
Adder
9.39
274744AC1-111 GEN8
Adder
9.39
274731ELWOOD EC;2P
Adder
27.554
274733ELWOOD EC;3P
Adder
27.554
274735ELWOOD EC;4P
Adder
27.554
274728ELWOOD EC;5P
Adder
27.553
960681AF2-359 GEN
Solar/Wind Harmer
-0.002
274814UNIV PK N;0U
Adder
8.438
274807UNIV PK N;3U
Adder
8.42
274805UNIV PK N;1U
Adder
8.384
274811UNIV PK N;7U
Adder
8.365
971177AH1-047 GEN
Solar/Wind Harmer
6.932
971675AH1-338 GEN
Solar/Wind Harmer
4.366
971411AH1-196 GEN
Solar/Wind Harmer
16.767
276868AE1-113 GEN
Solar/Wind Harmer
2.231
276882AE2-255 GEN
Solar/Wind Harmer
1.3
971171AH1-044 GEN
Solar/Wind Harmer
22.166
274823ROCKFORD ;21
Adder
30.795
971769AH1-391 GEN
Solar/Wind Harmer
12.285
274863CRW1-WTG
Solar/Wind Harmer
0.003
274864CRW2-WTG
Solar/Wind Harmer
0.003
276612AE2-035 GEN
Solar/Wind Harmer
0.003
971681AH1-341 GEN
Solar/Wind Harmer
17.421
926823AC1-168 GEN
Solar/Wind Harmer
1.83
970169AG2-114 GEN
Solar/Wind Harmer
10.676
961011AF2-392 GEN
Solar/Wind Harmer
6.245
270536AF1-215 GEN2
Solar/Wind Harmer
0.013
957751AF2-069 GEN
Solar/Wind Harmer
0.344
971771AH1-392 GEN
Solar/Wind Harmer
10.304
274848CAMPGROVE;RU
Solar/Wind Harmer
0.002
946321AF1-296 GEN
Solar/Wind Harmer
5.695
971619AH1-309 GEN
Solar/Wind Harmer
4.519
276655WTG1_EQ
Solar/Wind Harmer
0.004
276656WTG2_EQ
Solar/Wind Harmer
0.001
959341AF2-225 GEN
Solar/Wind Harmer
10.525
941731AE2-173 GEN
Solar/Wind Harmer
8.353
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
5.748
24690905MDL-1G C
Solar/Wind Harmer
0.003
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.321
276848AB2-070 GEN3
Solar/Wind Harmer
0.32
971549AH1-272 GEN
Solar/Wind Harmer
17.65
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
963841AG1-237 GEN
Solar/Wind Harmer
3.464
944221AF1-090 GEN
Solar/Wind Harmer
4.433
274754CRETE EC ;4U
Adder
13.652
274682WAUKEGAN ;7U
Adder
29.523
274828WAUKEGAN ;BP
Adder
18.114
962781AG1-127 GEN
Solar/Wind Harmer
10.836
274872LEEDK;1U
Solar/Wind Harmer
0.007
276691AA1-018 GEN1
Solar/Wind Harmer
1.373
939401AE1-172 GEN
Solar/Wind Harmer
8.394
276861AD2-134 GEN
Solar/Wind Harmer
0.201
276901AD2-066 C O1
Solar/Wind Harmer
0.011
971997AH1-543 GEN
Solar/Wind Harmer
5.85
957471AF2-041 GEN
Solar/Wind Harmer
33.25
959081AF2-199 GEN
Solar/Wind Harmer
11.083
971067AG2-660 GEN
Solar/Wind Harmer
3.694
274822ROCKFORD ;11
Adder
31.02
972235AH1-702 GEN1
Adder
3.971
970819AG2-516 GEN
Solar/Wind Harmer
13.127
276876AE1-163_GEN2
Solar/Wind Harmer
0.003
971475AH1-234 GEN
Solar/Wind Harmer
5.289
970373AG2-245 GEN
Solar/Wind Harmer
22.658
274857EASY ROAD;U1
Solar/Wind Harmer
0.002
274761LEE CO EC;2U
Adder
14.347
274766LEE CO EC;7U
Adder
14.178
970569AG2-363 GEN
Solar/Wind Harmer
32.191
276158O29GEN2
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0.008
274877BISHOP HL;1U
Solar/Wind Harmer
0.348
958381AF2-132 GEN
Solar/Wind Harmer
0.002
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
13.088
270505AE1-170 C O1
Solar/Wind Harmer
10.544
276726Z2-087_GEN
Solar/Wind Harmer
0.003
939741AE1-205 GEN
Solar/Wind Harmer
14.034
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
5.167
274854TWINGROVE;U2
Solar/Wind Harmer
0.004
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
12.069
945111AF1-176 GEN
Solar/Wind Harmer
16.867
972175AH1-670 GEN
Solar/Wind Harmer
7.647
24791305MDL-5G
Solar/Wind Harmer
0.001
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
3.406
276615X2-022 GEN
Solar/Wind Harmer
0.09
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
24639705ELKHART HY
Adder
0.181
965911AG1-460 GEN
Solar/Wind Harmer
1.619
963741AG1-226 GEN
Solar/Wind Harmer
18.007
970333AG2-219 GEN
Solar/Wind Harmer
4.589
965791AG1-447 GEN
Solar/Wind Harmer
10.696
274808UNIV PK N;4U
Adder
8.329
274695ROCKY RD ;2P
Adder
18.381
274693ROCKY RD ;1P
Adder
18.201
274697ROCKY RD ;3P
Adder
4.993
274696ROCKY RD ;4P
Adder
18.814
274683WAUKEGAN ;8U
Adder
34.557
274683WAUKEGAN ;8U
Adder
29.13
962691AG1-118 GEN
Solar/Wind Harmer
34.279
970921AG2-575 GEN
Solar/Wind Harmer
11.387
970921AG2-575 GEN
Solar/Wind Harmer
3.796
958481AF2-142 GEN
Solar/Wind Harmer
16.996
274861TOP CROP ;1U
Solar/Wind Harmer
0.003
274862TOP CROP ;2U
Solar/Wind Harmer
1.531
942991AE2-321 GEN
Solar/Wind Harmer
12.559
971333AH1-146 GEN
Solar/Wind Harmer
22.345
971335AH1-147 GEN
Solar/Wind Harmer
22.345
958491AF2-143 GEN
Solar/Wind Harmer
16.726
274879MINONK ;1U
Solar/Wind Harmer
0.469
971341AH1-150 GEN
Solar/Wind Harmer
22.166
971343AH1-151 GEN
Solar/Wind Harmer
22.166
24441505OLIV SLR
Solar/Wind Harmer
0
274856ECOGROVE ;U1
Solar/Wind Harmer
0.257
276611AD2-172 GEN
Solar/Wind Harmer
0.003
276872AE1-163_GEN1
Solar/Wind Harmer
0.003
270526AF1-158 GEN
Solar/Wind Harmer
0.014
938861AE1-114 GEN
Solar/Wind Harmer
6.129
274764LEE CO EC;5U
Adder
14.381
274765LEE CO EC;6U
Adder
14.381
274762LEE CO EC;3U
Adder
14.347
274763LEE CO EC;4U
Adder
14.212
276603SUBLETTE C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
6.33
276741O09 GEN1
Solar/Wind Harmer
0.375
276708O09 GEN2
Solar/Wind Harmer
0.375
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.41
276646AC1-214 GEN2
Solar/Wind Harmer
0.41
276782AC1-033 GEN
Solar/Wind Harmer
0.002
957891AF2-083 GEN
Solar/Wind Harmer
0.001
960611AF2-352 GEN
Solar/Wind Harmer
3.248
961051AF2-396 GEN
Solar/Wind Harmer
19.465
961051AF2-396 GEN
Solar/Wind Harmer
12.976
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
270216AD2-079_GEN
Solar/Wind Harmer
0.001
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
966841AG1-555 GEN
Solar/Wind Harmer
0.952
276916AD2-100_GEN
Solar/Wind Harmer
16.743
276911AD2-131_GEN
Solar/Wind Harmer
1.103
970241AG2-163 GEN
Solar/Wind Harmer
4.438
247620Y3-023
Adder
0.483
970239AG2-162 GEN
Solar/Wind Harmer
1.604
945391AF1-204 GEN
Solar/Wind Harmer
6.689
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
1.195
274855GSG-6 ;RU
Solar/Wind Harmer
0.41
274850MENDOTA H;RU
Solar/Wind Harmer
0.132
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.201
276805AD2-038 GEN
Solar/Wind Harmer
0.003
959091AF2-200 GEN
Solar/Wind Harmer
22.166
972236AH1-702 GEN2
Adder
3.453
276889AE2-281 GEN
Solar/Wind Harmer
0.001
274858EASY ROAD;U2
Solar/Wind Harmer
0.002
274760LEE CO EC;1U
Adder
14.347
274767LEE CO EC;8U
Adder
14.178
970571AG2-364 GEN
Solar/Wind Harmer
21.461
276157O29GEN1
Solar/Wind Harmer
1.704
270535AF1-215 GEN1
Solar/Wind Harmer
0.013
274878BISHOP HL;2U
Solar/Wind Harmer
0.348
24642205MAYFLWER
Adder
0.931
247604X1-042
Adder
0.603
964401AG1-302 GEN
Solar/Wind Harmer
0.002
965931AG1-462 GEN
Solar/Wind Harmer
25.726
24441205WTRV SLR C
Solar/Wind Harmer
0
942111AE2-223 GEN
Solar/Wind Harmer
3.258
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
274853TWINGROVE;U1
Solar/Wind Harmer
0.004
965091AG1-374 GEN
Solar/Wind Harmer
29.234
959611AF2-252 GEN
Solar/Wind Harmer
3.248
945111AF1-176 GEN
Solar/Wind Harmer
7.662
247643Z2-116 C
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
8.96
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
4.071
276668AB2-070 GEN1
Solar/Wind Harmer
0.321
276621W2-048 GEN
Solar/Wind Harmer
0.432
276838X2-022 GEN2
Solar/Wind Harmer
0.483
942481AE2-261 GEN
Solar/Wind Harmer
24.202
970243AG2-164 GEN
Solar/Wind Harmer
3.754
970519AG2-331 GEN
Solar/Wind Harmer
16.686
970699AG2-449 GEN
Solar/Wind Harmer
1.604
970193AG2-126 GEN
Solar/Wind Harmer
9.444
LAGNLTFEXP_LAGN->PJM
CLTF
9.627
TVALTFEXP_TVA->PJM
CLTF
3.333
CBM West 2LTFEXP_CBM-W2->PJM
CBM
82.442
NYPJM->LTFIMP_NY
CLTF
2.408
LGEELTFEXP_LGEE->PJM
CLTF
1.951
WECLTFEXP_WEC->PJM
CLTF
5.994
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.701
AG2-052LTFEXP_AG2-052->PJM
LTF
0.34
AH1-155LTFEXP_AH1-155->PJM
LTF
0.51
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.284
CBM West 1LTFEXP_CBM-W1->PJM
CBM
161.728
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.182
MECLTFEXP_MEC->PJM
CLTF
20.685
SIGELTFEXP_SIGE->PJM
CLTF
0.251

Details for 05FLTLCK-05GAVIN_RF 765.0 kV Ckt 1 line l/o AEP_P4_#8075_05MARYSV 765_A2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05FLTLCK-05GAVIN_RF 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#8075_05MARYSV 765_A2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.34 %
Rating:4349.0 MVA
Rating Type:B
MVA to Mitigate:4494.08
MW Contribution:23.44
Bus #Bus NameTypeMW Contribution
24721805FLATG3
50/50
8.432
24721705FLATG2
50/50
154.591
24344105CKG2
50/50
11.53
270143AC1-141 CT2_
50/50
3.334
24639705ELKHART HY
50/50
0.224
970521AG2-332 GEN
50/50
15.95
24307105BERRINSP G
50/50
0.03
24722005FLATG5
50/50
8.432
24721905FLATG4
50/50
154.591
270142AC1-141 CT1_
50/50
3.334
24344005CKG1
50/50
9.104
24641605TWIN BRNCH
50/50
0.024
24642205MAYFLWER
50/50
0.927
944961AF1-161 GEN
50/50
3.972
962601AG1-109 GEN
50/50
3.972
247604X1-042
50/50
0.589
970153AG2-106 GEN
Solar/Wind Harmer
75.966
970349AG2-230 GEN
Solar/Wind Harmer
22.036
270043AE2-236 GEN
Solar/Wind Harmer
7.928
970513AG2-328 GEN
Solar/Wind Harmer
25.325
970517AG2-330 GEN
Solar/Wind Harmer
22.969
247643Z2-116 C
Solar/Wind Harmer
0.097
945111AF1-176 GEN
Solar/Wind Harmer
7.764
970031AG2-029 GEN
Solar/Wind Harmer
40.661
24441205WTRV SLR C
Solar/Wind Harmer
0.181
944531AF1-118 GEN
Solar/Wind Harmer
46.957
959331AF2-224 GEN
Solar/Wind Harmer
13.218
965021AG1-366 GEN
Solar/Wind Harmer
3.074
274772LINCOLN ;3U
Adder
8.163
274724RIVER EC ;11
Adder
23.052
972231SS25-0005
Solar/Wind Harmer
12.334
972181SS23-001
Solar/Wind Harmer
7.709
274752CRETE EC ;2U
Adder
6.353
274753CRETE EC ;3U
Adder
6.353
970707AG2-453 GEN
Solar/Wind Harmer
36.006
274802UNIV PARK;5U
Adder
7.474
274826FISK ;BP
Adder
14.031
276772AC2-154 GEN
Solar/Wind Harmer
3.569
276806AD2-047 C O1
Solar/Wind Harmer
13.693
970941AG2-585 GEN
Solar/Wind Harmer
16
274800UNIV PARK;3U
Adder
7.462
972038AH1-567 GEN2
Adder
0.467
972228AH1-698 GEN2
Adder
4.737
276897AD1-100 C
Solar/Wind Harmer
36.905
939351AE1-166 GEN
Solar/Wind Harmer
7.541
274676JOLIET 29;8U
Adder
37.492
274729ELWOOD EC;1P
Adder
20.768
274730ELWOOD EC;6P
Adder
20.768
274734ELWOOD EC;8P
Adder
20.768
274736ELWOOD EC;9P
Adder
20.768
276893AG1-478 C
Solar/Wind Harmer
0.527
270535AF1-215 GEN1
Solar/Wind Harmer
5.712
943121AE2-341 GEN
Solar/Wind Harmer
18.813
943591AF1-030 GEN
Solar/Wind Harmer
12.542
276694AA1-018 GEN2
Solar/Wind Harmer
7.785
274682WAUKEGAN ;7U
Adder
22.136
964401AG1-302 GEN
Solar/Wind Harmer
11.14
274872LEEDK;1U
Solar/Wind Harmer
0.311
276805AD2-038 GEN
Solar/Wind Harmer
6.236
276799AD1-013 GEN
Solar/Wind Harmer
2.659
946671AF1-331 GEN
Solar/Wind Harmer
0.503
959141AF2-205 GEN
Solar/Wind Harmer
7.265
274855GSG-6 ;RU
Solar/Wind Harmer
4.438
274850MENDOTA H;RU
Solar/Wind Harmer
3.086
276602WESTBROOK C
Solar/Wind Harmer
2.554
276863AD2-134 GEN
Solar/Wind Harmer
2.146
972236AH1-702 GEN2
Adder
2.595
274760LEE CO EC;1U
Adder
10.813
274767LEE CO EC;8U
Adder
10.686
962761AG1-125 GEN
Solar/Wind Harmer
174.214
970149AG2-104 GEN
Solar/Wind Harmer
215.155
970155AG2-107 GEN
Solar/Wind Harmer
75.966
970245AG2-165 GEN
Solar/Wind Harmer
25.325
270505AE1-170 C O1
Solar/Wind Harmer
20.687
945111AF1-176 GEN
Solar/Wind Harmer
24.498
270063AE2-323 C
Solar/Wind Harmer
3.019
270449AD2-020 GEN
Solar/Wind Harmer
3.83
943021AE2-325 GEN
Solar/Wind Harmer
4.976
965011AG1-365 GEN
Solar/Wind Harmer
13.218
972207SS24-0001
Solar/Wind Harmer
29.024
274773LINCOLN ;4U
Adder
8.163
274774LINCOLN ;5U
Adder
8.163
274723RIVER EC ;12
Adder
23.321
274751CRETE EC ;1U
Adder
6.353
274754CRETE EC ;4U
Adder
6.353
276164X3-005 C
Solar/Wind Harmer
0.91
970373AG2-245 GEN
Solar/Wind Harmer
27.1
274812UNIV PK N;8U
Adder
6.463
276776AD2-060 GEN
Solar/Wind Harmer
0.541
274801UNIV PARK;4U
Adder
7.462
941551AE2-152 GEN
Solar/Wind Harmer
5.768
274676JOLIET 29;8U
Adder
38.881
274674JOLIET 9 ;6U
Adder
19.473
274732ELWOOD EC;7P
Adder
20.768
274871GR RIDGE ;2U
Solar/Wind Harmer
9.692
270055AF2-134 C O1
Solar/Wind Harmer
3.807
274745AC1-111 GEN9
Adder
6.996
276691AA1-018 GEN1
Solar/Wind Harmer
0.574
274682WAUKEGAN ;7U
Adder
22.136
274828WAUKEGAN ;BP
Adder
13.584
958381AF2-132 GEN
Solar/Wind Harmer
11.14
964861AG1-349 GEN
Solar/Wind Harmer
9.628
971917AH1-482 GEN
Solar/Wind Harmer
11.111
960751AF2-366 GEN
Solar/Wind Harmer
3.499
962781AG1-127 GEN
Solar/Wind Harmer
11.598
939401AE1-172 GEN
Solar/Wind Harmer
16.958
274872LEEDK;1U
Solar/Wind Harmer
9.989
965651AG1-433 GEN
Solar/Wind Harmer
6.647
276901AD2-066 C O1
Solar/Wind Harmer
4.262
971997AH1-543 GEN
Solar/Wind Harmer
18.988
276861AD2-134 GEN
Solar/Wind Harmer
2.146
274822ROCKFORD ;11
Adder
23.305
972235AH1-702 GEN1
Adder
2.984
274761LEE CO EC;2U
Adder
10.813
274766LEE CO EC;7U
Adder
10.686
270102X2-052 ST
50/50
2.201
270100X2-052 CT1
50/50
2.028
270101X2-052 CT2
50/50
2.028
247620Y3-023
50/50
0.669
970615AG2-402 GEN
50/50
3.074
970321AG2-212 GEN
Solar/Wind Harmer
25.325
270216AD2-079_GEN
Solar/Wind Harmer
0.841
957891AF2-083 GEN
Solar/Wind Harmer
4.643
960981AF2-389 GEN
Solar/Wind Harmer
2.08
270526AF1-158 GEN
Solar/Wind Harmer
6.237
24441505OLIV SLR
Solar/Wind Harmer
0.183
961051AF2-396 GEN
Solar/Wind Harmer
21.727
961051AF2-396 GEN
Solar/Wind Harmer
10.106
965681AG1-436 GEN
Solar/Wind Harmer
17.064
965791AG1-447 GEN
Solar/Wind Harmer
8.731
970611AG2-400 GEN
Solar/Wind Harmer
13.218
274770LINCOLN ;1U
Adder
8.163
274771LINCOLN ;2U
Adder
8.163
274808UNIV PK N;4U
Adder
6.434
274803UNIV PARK;6U
Adder
7.474
972259AH1-714 GEN
Adder
24.421
274888KELLY CRK;1U
Solar/Wind Harmer
7.557
274887GEN-1.85
Solar/Wind Harmer
6.822
276843GEN-1.7
Solar/Wind Harmer
0.734
958011AF2-095 GEN
Solar/Wind Harmer
18.431
274674JOLIET 9 ;6U
Adder
19.473
274847GR RIDGE ;BU
Solar/Wind Harmer
6.376
971573AH1-285 GEN
Solar/Wind Harmer
10.712
274696ROCKY RD ;4P
Adder
14.064
274695ROCKY RD ;2P
Adder
13.74
274693ROCKY RD ;1P
Adder
13.605
274697ROCKY RD ;3P
Adder
3.732
958481AF2-142 GEN
Solar/Wind Harmer
18.503
274861TOP CROP ;1U
Solar/Wind Harmer
7.47
274862TOP CROP ;2U
Solar/Wind Harmer
6.238
274683WAUKEGAN ;8U
Adder
25.914
274683WAUKEGAN ;8U
Adder
21.844
962691AG1-118 GEN
Solar/Wind Harmer
36.699
970921AG2-575 GEN
Solar/Wind Harmer
12.196
970921AG2-575 GEN
Solar/Wind Harmer
2.836
944541AF1-119 GEN
Solar/Wind Harmer
5.094
960971AF2-388 GEN
Solar/Wind Harmer
13.293
958491AF2-143 GEN
Solar/Wind Harmer
18.234
942991AE2-321 GEN
Solar/Wind Harmer
12.086
274879MINONK ;1U
Solar/Wind Harmer
8.155
274764LEE CO EC;5U
Adder
10.839
274765LEE CO EC;6U
Adder
10.839
274762LEE CO EC;3U
Adder
10.813
274763LEE CO EC;4U
Adder
10.711
972267AH1-718 GEN
Adder
4.78
247621Y3-024
Adder
0.217
971333AH1-146 GEN
Solar/Wind Harmer
8.998
971335AH1-147 GEN
Solar/Wind Harmer
8.998
24721605FLATG1
50/50
8.432
971599AH1-298 GEN
50/50
13.812
270144AC1-141 ST1_
50/50
2.953
24653605MOTTVILLE
50/50
0.005
24643105BUCHANAN
50/50
0.018
962771AG1-126 GEN
Solar/Wind Harmer
174.214
971347AH1-153 GEN
Solar/Wind Harmer
22.036
270071AF1-092 GEN
Solar/Wind Harmer
20.801
971771AH1-392 GEN
Solar/Wind Harmer
12.478
971769AH1-391 GEN
Solar/Wind Harmer
13.692
960681AF2-359 GEN
Solar/Wind Harmer
5.157
944161AF1-084 GEN
Solar/Wind Harmer
3.004
274775LINCOLN ;6U
Adder
8.163
274776LINCOLN ;7U
Adder
8.163
274777LINCOLN ;8U
Adder
8.163
24729505KEY G4
Adder
8.488
274814UNIV PK N;0U
Adder
6.519
274807UNIV PK N;3U
Adder
6.505
274805UNIV PK N;1U
Adder
6.477
274811UNIV PK N;7U
Adder
6.463
972037AH1-567 GEN1
Adder
0.235
274827FISK ;RP
Adder
9.944
960591AF2-350 GEN
Solar/Wind Harmer
12.8
972227AH1-698 GEN1
Adder
3.335
274687WILL CNTY;4U
Adder
35.465
274687WILL CNTY;4U
Adder
35.465
274675JOLIET 29;7U
Adder
38.882
274675JOLIET 29;7U
Adder
37.493
971549AH1-272 GEN
Solar/Wind Harmer
23.441
274731ELWOOD EC;2P
Adder
20.768
274733ELWOOD EC;3P
Adder
20.768
274735ELWOOD EC;4P
Adder
20.768
274728ELWOOD EC;5P
Adder
20.768
970833AG2-524 GEN
Solar/Wind Harmer
11.011
970833AG2-524 GEN
Solar/Wind Harmer
5.121
270536AF1-215 GEN2
Solar/Wind Harmer
5.712
274746AC1-111 G10
Adder
6.996
274744AC1-111 GEN8
Adder
6.996
958711AF2-162 GEN
Solar/Wind Harmer
1.23
958391AF2-133 GEN
Solar/Wind Harmer
11.003
276868AE1-113 GEN
Solar/Wind Harmer
12.231
276882AE2-255 GEN
Solar/Wind Harmer
4.077
971177AH1-047 GEN
Solar/Wind Harmer
7.079
971411AH1-196 GEN
Solar/Wind Harmer
18.031
971675AH1-338 GEN
Solar/Wind Harmer
21.635
274823ROCKFORD ;21
Adder
23.136
LAGNLTFEXP_LAGN->PJM
CLTF
6.748
TVALTFEXP_TVA->PJM
CLTF
2.171
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CBM West 2LTFEXP_CBM-W2->PJM
CBM
70.171
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
NYPJM->LTFIMP_NY
CLTF
2.159
LGEELTFEXP_LGEE->PJM
CLTF
2.657
WECLTFEXP_WEC->PJM
CLTF
4.511
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.689
AG2-052LTFEXP_AG2-052->PJM
LTF
0.285
AH1-155LTFEXP_AH1-155->PJM
LTF
0.428
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.936
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.15
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.3
MECLTFEXP_MEC->PJM
CLTF
15.891
SIGELTFEXP_SIGE->PJM
CLTF
0.293

Details for 05GUNN RD SW-05BOKESCRK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05GUNN RD SW-05BOKESCRK 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7445_05MARYSV 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.83 %
Rating:1301.0 MVA
Rating Type:B
MVA to Mitigate:1324.81
MW Contribution:8.46
Bus #Bus NameTypeMW Contribution
965431AG1-411 GEN
50/50
12.696
24727105RPMNG2
50/50
0.96
942871AE2-306 GEN
Solar/Wind Harmer
3.988
270391AF1-285 GEN3
Solar/Wind Harmer
2.045
270485AE1-090_GEN
Solar/Wind Harmer
2.31
270491AE1-102 GEN2
Solar/Wind Harmer
1.473
270588AE1-091_GEN
Solar/Wind Harmer
11.055
270541AE2-072 C
Solar/Wind Harmer
3.949
958091AF2-103 GEN
Solar/Wind Harmer
0.137
270575GUS2 35KV
Solar/Wind Harmer
7.716
270258AD1-119 GEN
Solar/Wind Harmer
2.083
270044AE2-322 C
Solar/Wind Harmer
0.971
270404AC1-167 GEN
Solar/Wind Harmer
0.808
270191TR4_S_V150
Solar/Wind Harmer
2.178
24727005RPMNG1
50/50
0.956
270223U2-072_GEN1
Solar/Wind Harmer
8.695
270578AF1-285 GEN2
Solar/Wind Harmer
5.317
270391AF1-285 GEN3
Solar/Wind Harmer
5.317
270462AD2-086
Solar/Wind Harmer
26.575
270466AD2-091
50/50
22.173
270224U2-072_GEN2
Solar/Wind Harmer
8.695
270227U2-072_GEN3
Solar/Wind Harmer
8.695
270228U2-072_GEN4
Solar/Wind Harmer
8.695
270231U2-072_GEN5
Solar/Wind Harmer
8.695
246938BC-WTG3
Solar/Wind Harmer
4.511
246937BC-WTG2
Solar/Wind Harmer
4.434
270007AE1-245 C
Solar/Wind Harmer
5.052
942801AE2-298 GEN
Solar/Wind Harmer
1.194
970611AG2-400 GEN
Solar/Wind Harmer
7.021
971677AH1-339 GEN
Solar/Wind Harmer
5.301
241996AE2-282_GEN
Solar/Wind Harmer
0.979
247620Y3-023
Adder
0.215
971231AH1-075 GEN
Solar/Wind Harmer
0.36
942221AE2-234 GEN
Solar/Wind Harmer
0.327
270216AD2-079_GEN
Solar/Wind Harmer
0.268
961051AF2-396 GEN
Solar/Wind Harmer
6.972
961051AF2-396 GEN
Solar/Wind Harmer
3.243
960981AF2-389 GEN
Solar/Wind Harmer
0.66
957891AF2-083 GEN
Solar/Wind Harmer
1.473
270471AD2-092_GEN
Solar/Wind Helper
1.782
946101AF1-275 GEN
Solar/Wind Helper
0.312
270036AE2-216 BAT
50/50
24.391
24727205RPMNG3
50/50
0.952
270578AF1-285 GEN2
Solar/Wind Harmer
2.045
270302AB2-170 GEN
Solar/Wind Harmer
31.946
270317AD1-130_GEN
Solar/Wind Harmer
12.246
957201AF2-014 GEN
Solar/Wind Harmer
5.139
270435AC2-044 GEN
Solar/Wind Harmer
2.266
270297AD1-101 GEN
Solar/Wind Harmer
2.38
247607V1-011 GEN
Solar/Wind Harmer
3.367
966831AG1-554 GEN
Solar/Wind Harmer
1.009
971989AH1-539 GEN
Solar/Wind Harmer
10.907
270499AE1-146 GEN
Solar/Wind Harmer
2.064
965051AG1-369 GEN
Solar/Wind Harmer
3.625
965041AG1-368 GEN
Solar/Wind Harmer
7.254
945411AF1-206 GEN
Solar/Wind Harmer
3.658
970817AG2-515 GEN
Solar/Wind Harmer
5.808
972211AH1-690 GEN
Adder
89.121
963791AG1-232 GEN
Solar/Wind Harmer
7.507
945641AF1-229 GEN
Solar/Wind Harmer
1.945
270071AF1-092 GEN
Solar/Wind Harmer
6.969
971549AH1-272 GEN
Solar/Wind Harmer
8.464
246936BC-WTG1
Solar/Wind Harmer
4.434
270489AE1-102 GEN1
Solar/Wind Harmer
1.473
965421AG1-410 GEN
Solar/Wind Harmer
32.755
247522W1-056 GEN
Solar/Wind Harmer
1.866
960841AF2-375 GEN
Solar/Wind Harmer
3.054
24695305TIMB G C
Solar/Wind Harmer
4.274
270361_3
Solar/Wind Harmer
6.549
247521TR3_G114
Solar/Wind Harmer
2.441
270246TR4_N_V150
Solar/Wind Harmer
0.618
965011AG1-365 GEN
Solar/Wind Harmer
7.021
23906502RICHG2&3
Adder
0.834
972301AH1-735 GEN
Adder
4.148
23906402RICHG1
Adder
0.83
241840AF1-064_GEN
Solar/Wind Harmer
0.763
23920202STRYCT
Adder
0.874
944231AF1-091 GEN
Solar/Wind Harmer
2.34
241808AF1-120 C
Solar/Wind Harmer
0.546
241858AF1-205_GEN
Solar/Wind Harmer
2.423
972253AH1-711 GEN
Adder
18.867
270063AE2-323 C
Solar/Wind Harmer
1.113
24639705ELKHART HY
Adder
0.07
945111AF1-176 GEN
Solar/Wind Harmer
7.883
270449AD2-020 GEN
Solar/Wind Harmer
1.227
943021AE2-325 GEN
Solar/Wind Harmer
1.594
270505AE1-170 C O1
Solar/Wind Harmer
6.536
270349AD2-093_GEN
Solar/Wind Helper
1.782
270024AE2-089 GEN
Solar/Wind Harmer
2.07
944161AF1-084 GEN
Solar/Wind Harmer
0.967
270284AF1-227 GEN1
Solar/Wind Helper
5.57
270286AF1-227 GEN2
Solar/Wind Helper
2.043
270287AF1-227 GEN3
Solar/Wind Helper
2.043
270520AE2-214 GEN
Solar/Wind Helper
2.488
270054AF2-122 C O1
Solar/Wind Helper
0.645
270247TR4_N_V136
Solar/Wind Harmer
0.618
959331AF2-224 GEN
Solar/Wind Harmer
7.021
965021AG1-366 GEN
Solar/Wind Harmer
1.633
23906502RICHG2&3
Adder
0.834
958321AF2-126 GEN
Solar/Wind Harmer
0.818
241832AE2-181_GEN
Solar/Wind Harmer
0.917
23929302BS-PKR
Adder
0.797
970031AG2-029 GEN
Solar/Wind Harmer
15.724
270043AE2-236 GEN
Solar/Wind Harmer
2.792
270377AD1-106 GEN
Solar/Wind Harmer
2.779
945111AF1-176 GEN
Solar/Wind Harmer
2.498
247643Z2-116 C
Solar/Wind Harmer
0.031
971617AH1-308 GEN
Solar/Wind Harmer
2.565
247604X1-042
Adder
0.182
24441205WTRV SLR C
Solar/Wind Harmer
0.059
LAGNLTFEXP_LAGN->PJM
CLTF
2.316
TVALTFEXP_TVA->PJM
CLTF
0.854
CBM West 2LTFEXP_CBM-W2->PJM
CBM
22.063
NYPJM->LTFIMP_NY
CLTF
0.734
LGEELTFEXP_LGEE->PJM
CLTF
0.812
WECLTFEXP_WEC->PJM
CLTF
1.26
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.302
AG2-052LTFEXP_AG2-052->PJM
LTF
0.082
AH1-155LTFEXP_AH1-155->PJM
LTF
0.124
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.137
CBM West 1LTFEXP_CBM-W1->PJM
CBM
52.655
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.43
MECLTFEXP_MEC->PJM
CLTF
4.551
SIGELTFEXP_SIGE->PJM
CLTF
0.09

Details for 05HANGRCK_RJ-05HANG R 765.0 kV Ckt Z1 line l/o AEP_P1-2_#7441_100545_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05HANGRCK_RJ-05HANG R 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.88 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:4885.66
MW Contribution:17.28
Bus #Bus NameTypeMW Contribution
24344205RKG1
50/50
10.236
24344205RKG1
50/50
10.215
24344305RKG2
50/50
10.196
270393AB1-087 CT1
50/50
3.172
270394AB1-087 ST1
50/50
3.172
24690905MDL-1G C
Solar/Wind Harmer
0.003
270180AB1-006 GEN1
Solar/Wind Harmer
0.003
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.002
270181AB1-006 GEN2
Solar/Wind Harmer
0
24386205FR-12G C
Solar/Wind Harmer
0.002
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.002
963841AG1-237 GEN
Solar/Wind Harmer
4.805
971611AH1-305 GEN
Solar/Wind Harmer
6.537
958391AF2-133 GEN
Solar/Wind Harmer
0.002
270536AF1-215 GEN2
Solar/Wind Harmer
0.013
960681AF2-359 GEN
Solar/Wind Harmer
-0.002
971347AH1-153 GEN
Solar/Wind Harmer
14.79
274775LINCOLN ;6U
Adder
11.903
274776LINCOLN ;7U
Adder
11.903
274777LINCOLN ;8U
Adder
11.903
276655WTG1_EQ
Solar/Wind Harmer
0.004
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
10.288
941731AE2-173 GEN
Solar/Wind Harmer
8.165
274863CRW1-WTG
Solar/Wind Harmer
0.003
274864CRW2-WTG
Solar/Wind Harmer
0.003
970169AG2-114 GEN
Solar/Wind Harmer
9.776
972227AH1-698 GEN1
Adder
3.652
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
274814UNIV PK N;0U
Adder
7.072
274807UNIV PK N;3U
Adder
7.056
274805UNIV PK N;1U
Adder
7.026
274811UNIV PK N;7U
Adder
7.01
960591AF2-350 GEN
Solar/Wind Harmer
9.764
276849AB2-070 GEN2
Solar/Wind Harmer
0.356
276848AB2-070 GEN3
Solar/Wind Harmer
0.354
972037AH1-567 GEN1
Adder
0.256
274827FISK ;RP
Adder
10.835
970833AG2-524 GEN
Solar/Wind Harmer
10.702
970833AG2-524 GEN
Solar/Wind Harmer
7.134
274731ELWOOD EC;2P
Adder
22.909
274733ELWOOD EC;3P
Adder
22.909
274735ELWOOD EC;4P
Adder
22.909
274728ELWOOD EC;5P
Adder
22.908
274687WILL CNTY;4U
Adder
38.91
274687WILL CNTY;4U
Adder
38.91
274675JOLIET 29;7U
Adder
42.703
274675JOLIET 29;7U
Adder
41.178
971769AH1-391 GEN
Solar/Wind Harmer
10.786
274746AC1-111 G10
Adder
7.736
274744AC1-111 GEN8
Adder
7.736
944221AF1-090 GEN
Solar/Wind Harmer
5.66
276868AE1-113 GEN
Solar/Wind Harmer
1.928
276882AE2-255 GEN
Solar/Wind Harmer
1.124
970091AG2-072 GEN
50/50
198.882
270407AB1-088 ST1
50/50
3.172
970333AG2-219 GEN
Solar/Wind Harmer
12.809
270445AC2-157 GEN2
Solar/Wind Harmer
0.006
970245AG2-165 GEN
Solar/Wind Harmer
4.889
24791305MDL-5G
Solar/Wind Harmer
0.001
24385905FR-11G C
Solar/Wind Harmer
0.003
24387305FR-4G C
Solar/Wind Harmer
0.004
963741AG1-226 GEN
Solar/Wind Harmer
26.02
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
13.725
964861AG1-349 GEN
Solar/Wind Harmer
-0.002
971917AH1-482 GEN
Solar/Wind Harmer
13.986
958381AF2-132 GEN
Solar/Wind Harmer
0.002
270055AF2-134 C O1
Solar/Wind Harmer
0.008
970373AG2-245 GEN
Solar/Wind Harmer
21.781
274773LINCOLN ;4U
Adder
11.903
274774LINCOLN ;5U
Adder
11.903
276726Z2-087_GEN
Solar/Wind Harmer
0.003
939741AE1-205 GEN
Solar/Wind Harmer
13.718
939401AE1-172 GEN
Solar/Wind Harmer
7.325
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274751CRETE EC ;1U
Adder
11.551
274754CRETE EC ;4U
Adder
11.551
274854TWINGROVE;U2
Solar/Wind Harmer
0.004
972175AH1-670 GEN
Solar/Wind Harmer
8.079
274723RIVER EC ;12
Adder
25.097
274880W4-005 GEN4
Solar/Wind Harmer
0.001
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
7.01
276776AD2-060 GEN
Solar/Wind Harmer
1.019
274801UNIV PARK;4U
Adder
8.146
963831AG1-236 GEN
Solar/Wind Harmer
3.802
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
274732ELWOOD EC;7P
Adder
22.908
276615X2-022 GEN
Solar/Wind Harmer
0.102
274674JOLIET 9 ;6U
Adder
21.442
274676JOLIET 29;8U
Adder
42.703
276691AA1-018 GEN1
Solar/Wind Harmer
1.17
274745AC1-111 GEN9
Adder
7.736
965911AG1-460 GEN
Solar/Wind Harmer
1.93
276901AD2-066 C O1
Solar/Wind Harmer
0.01
971997AH1-543 GEN
Solar/Wind Harmer
5.053
274682WAUKEGAN ;7U
Adder
24.679
276876AE1-163_GEN2
Solar/Wind Harmer
0.003
274828WAUKEGAN ;BP
Adder
15.157
970569AG2-363 GEN
Solar/Wind Harmer
28.645
962781AG1-127 GEN
Solar/Wind Harmer
9.085
274872LEEDK;1U
Solar/Wind Harmer
0.006
276861AD2-134 GEN
Solar/Wind Harmer
0.17
957471AF2-041 GEN
Solar/Wind Harmer
28.383
959081AF2-199 GEN
Solar/Wind Harmer
9.461
971067AG2-660 GEN
Solar/Wind Harmer
3.154
970291AG2-192 GEN
Solar/Wind Harmer
1.229
274877BISHOP HL;1U
Solar/Wind Harmer
0.317
274822ROCKFORD ;11
Adder
26.534
972235AH1-702 GEN1
Adder
3.404
970819AG2-516 GEN
Solar/Wind Harmer
11.285
971475AH1-234 GEN
Solar/Wind Harmer
4.553
274857EASY ROAD;U1
Solar/Wind Harmer
0.002
276158O29GEN2
Solar/Wind Harmer
0.001
270505AE1-170 C O1
Solar/Wind Harmer
9.741
945111AF1-176 GEN
Solar/Wind Harmer
16.452
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
4.8
270032AE2-172
Solar/Wind Harmer
6.065
276903AD2-071 C
Solar/Wind Harmer
10.136
270063AE2-323 C
Solar/Wind Harmer
0.007
965651AG1-433 GEN
Solar/Wind Harmer
2.403
958861AF2-177 GEN
Solar/Wind Harmer
3.539
945371AF1-202 GEN
Solar/Wind Harmer
0.001
970825AG2-519 GEN
Solar/Wind Harmer
2.846
270005AE1-210 C O1
Solar/Wind Harmer
1.734
965031AG1-367 GEN
Solar/Wind Harmer
8.001
970773AG2-487 GEN
Solar/Wind Harmer
1.37
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0.001
970613AG2-401 GEN
Solar/Wind Harmer
5.665
965011AG1-365 GEN
Solar/Wind Harmer
7.456
247536S-71 GEN
Solar/Wind Harmer
0.284
944231AF1-091 GEN
Solar/Wind Harmer
1.864
971565AH1-281 GEN
Solar/Wind Harmer
1.306
247521TR3_G114
Solar/Wind Harmer
0.234
270246TR4_N_V150
Solar/Wind Harmer
0.041
24695305TIMB G C
Solar/Wind Harmer
0.002
942601AE2-276 GEN
50/50
10.552
970239AG2-162 GEN
Solar/Wind Harmer
4.479
270444AC2-157 GEN1
Solar/Wind Harmer
0.006
971587AH1-292 GEN
Solar/Wind Harmer
9.286
970321AG2-212 GEN
Solar/Wind Harmer
4.889
24344305RKG2
50/50
10.006
270406AB1-088 CT1
50/50
3.172
970243AG2-164 GEN
Solar/Wind Harmer
10.48
970519AG2-331 GEN
Solar/Wind Harmer
46.579
970699AG2-449 GEN
Solar/Wind Harmer
4.479
970513AG2-328 GEN
Solar/Wind Harmer
4.889
970517AG2-330 GEN
Solar/Wind Harmer
29.332
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
11.21
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
964401AG1-302 GEN
Solar/Wind Harmer
0.002
970193AG2-126 GEN
Solar/Wind Harmer
16.013
270535AF1-215 GEN1
Solar/Wind Harmer
0.013
970349AG2-230 GEN
Solar/Wind Harmer
14.79
274772LINCOLN ;3U
Adder
11.903
942111AE2-223 GEN
Solar/Wind Harmer
3.184
276897AD1-100 C
Solar/Wind Harmer
0.013
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
247642Z2-115 C
Solar/Wind Harmer
0.004
274752CRETE EC ;2U
Adder
11.551
274753CRETE EC ;3U
Adder
11.551
274853TWINGROVE;U1
Solar/Wind Harmer
0.004
965091AG1-374 GEN
Solar/Wind Harmer
29.335
959611AF2-252 GEN
Solar/Wind Harmer
3.259
274724RIVER EC ;11
Adder
24.801
972228AH1-698 GEN2
Adder
5.187
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
4.513
276806AD2-047 C O1
Solar/Wind Harmer
5.533
970941AG2-585 GEN
Solar/Wind Harmer
12.205
276668AB2-070 GEN1
Solar/Wind Harmer
0.356
970707AG2-453 GEN
Solar/Wind Harmer
31.865
274802UNIV PARK;5U
Adder
8.15
274800UNIV PARK;3U
Adder
8.146
972038AH1-567 GEN2
Adder
0.51
274826FISK ;BP
Adder
15.289
274729ELWOOD EC;1P
Adder
22.909
274730ELWOOD EC;6P
Adder
22.908
274734ELWOOD EC;8P
Adder
22.908
274736ELWOOD EC;9P
Adder
22.908
276893AG1-478 C
Solar/Wind Harmer
0.385
276621W2-048 GEN
Solar/Wind Harmer
0.49
276838X2-022 GEN2
Solar/Wind Harmer
0.547
274676JOLIET 29;8U
Adder
41.178
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
943121AE2-341 GEN
Solar/Wind Harmer
16.19
943591AF1-030 GEN
Solar/Wind Harmer
10.767
942481AE2-261 GEN
Solar/Wind Harmer
28.852
276805AD2-038 GEN
Solar/Wind Harmer
0.003
274682WAUKEGAN ;7U
Adder
24.679
276889AE2-281 GEN
Solar/Wind Harmer
0.001
970571AG2-364 GEN
Solar/Wind Harmer
19.097
274872LEEDK;1U
Solar/Wind Harmer
0.35
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
1.013
274855GSG-6 ;RU
Solar/Wind Harmer
0.348
274850MENDOTA H;RU
Solar/Wind Harmer
0.112
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.17
959091AF2-200 GEN
Solar/Wind Harmer
18.922
970289AG2-191 GEN
Solar/Wind Harmer
1.04
970291AG2-192 GEN
Solar/Wind Harmer
0.945
274878BISHOP HL;2U
Solar/Wind Harmer
0.317
972236AH1-702 GEN2
Adder
2.96
24642205MAYFLWER
Adder
0.856
274858EASY ROAD;U2
Solar/Wind Harmer
0.002
276157O29GEN1
Solar/Wind Harmer
1.512
247643Z2-116 C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
7.473
965931AG1-462 GEN
Solar/Wind Harmer
23.338
24441205WTRV SLR C
Solar/Wind Harmer
0
270043AE2-236 GEN
Solar/Wind Harmer
5.542
970031AG2-029 GEN
Solar/Wind Harmer
5.595
944531AF1-118 GEN
Solar/Wind Harmer
37.201
958821AF2-173 GEN
Solar/Wind Harmer
11.202
270004AE1-209 GEN
Solar/Wind Harmer
1.734
946031AF1-268 GEN
Solar/Wind Harmer
7.423
270356AE2-297 GEN
Solar/Wind Harmer
0.01
270437AC2-090 C
Solar/Wind Harmer
0.003
959331AF2-224 GEN
Solar/Wind Harmer
5.219
965021AG1-366 GEN
Solar/Wind Harmer
2.485
971617AH1-308 GEN
Solar/Wind Harmer
6.14
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
10.942
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.041
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
966841AG1-555 GEN
Solar/Wind Harmer
1.266
970241AG2-163 GEN
Solar/Wind Harmer
6.413
945391AF1-204 GEN
Solar/Wind Harmer
11.343
965681AG1-436 GEN
Solar/Wind Harmer
12.338
965791AG1-447 GEN
Solar/Wind Harmer
9.048
274770LINCOLN ;1U
Adder
11.903
274771LINCOLN ;2U
Adder
11.903
960611AF2-352 GEN
Solar/Wind Harmer
3.259
274808UNIV PK N;4U
Adder
6.98
274888KELLY CRK;1U
Solar/Wind Harmer
0.573
274887GEN-1.85
Solar/Wind Harmer
0.257
276843GEN-1.7
Solar/Wind Harmer
0.316
958011AF2-095 GEN
Solar/Wind Harmer
14.061
972259AH1-714 GEN
Adder
26.685
274803UNIV PARK;6U
Adder
8.15
276763AC1-053 GEN1
Solar/Wind Harmer
0.002
276764AC1-053 GEN2
Solar/Wind Harmer
0.002
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
274674JOLIET 9 ;6U
Adder
21.442
24441505OLIV SLR
Solar/Wind Harmer
0
958481AF2-142 GEN
Solar/Wind Harmer
14.489
274861TOP CROP ;1U
Solar/Wind Harmer
0.003
274862TOP CROP ;2U
Solar/Wind Harmer
1.307
276916AD2-100_GEN
Solar/Wind Harmer
20.263
276911AD2-131_GEN
Solar/Wind Harmer
1.335
971573AH1-285 GEN
Solar/Wind Harmer
1.794
958491AF2-143 GEN
Solar/Wind Harmer
14.439
270526AF1-158 GEN
Solar/Wind Harmer
0.012
274879MINONK ;1U
Solar/Wind Harmer
0.405
274696ROCKY RD ;4P
Adder
15.67
274695ROCKY RD ;2P
Adder
15.309
274693ROCKY RD ;1P
Adder
15.158
274697ROCKY RD ;3P
Adder
4.159
276872AE1-163_GEN1
Solar/Wind Harmer
0.003
274683WAUKEGAN ;8U
Adder
28.915
274683WAUKEGAN ;8U
Adder
24.374
962691AG1-118 GEN
Solar/Wind Harmer
28.676
970921AG2-575 GEN
Solar/Wind Harmer
9.546
970921AG2-575 GEN
Solar/Wind Harmer
3.182
942991AE2-321 GEN
Solar/Wind Harmer
10.614
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.373
276646AC1-214 GEN2
Solar/Wind Harmer
0.373
971333AH1-146 GEN
Solar/Wind Harmer
18.962
971335AH1-147 GEN
Solar/Wind Harmer
18.962
971341AH1-150 GEN
Solar/Wind Harmer
18.922
971343AH1-151 GEN
Solar/Wind Harmer
18.922
276782AC1-033 GEN
Solar/Wind Harmer
0.001
274856ECOGROVE ;U1
Solar/Wind Harmer
0.222
276611AD2-172 GEN
Solar/Wind Harmer
0.003
938861AE1-114 GEN
Solar/Wind Harmer
5.315
276603SUBLETTE C
Solar/Wind Harmer
0
274764LEE CO EC;5U
Adder
12.51
274765LEE CO EC;6U
Adder
9.439
276741O09 GEN1
Solar/Wind Harmer
0.333
276708O09 GEN2
Solar/Wind Harmer
0.333
270216AD2-079_GEN
Solar/Wind Harmer
0.001
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
18.41
961051AF2-396 GEN
Solar/Wind Harmer
12.273
971613AH1-306 GEN
Solar/Wind Harmer
4.367
944541AF1-119 GEN
Solar/Wind Harmer
0.549
960971AF2-388 GEN
Solar/Wind Harmer
4.806
270599AE1-208 GEN
Solar/Wind Harmer
7.51
270031AE2-169
Solar/Wind Harmer
4.506
926823AC1-168 GEN
Solar/Wind Harmer
1.627
971177AH1-047 GEN
Solar/Wind Harmer
5.86
971675AH1-338 GEN
Solar/Wind Harmer
3.702
957751AF2-069 GEN
Solar/Wind Harmer
0.313
971771AH1-392 GEN
Solar/Wind Harmer
9.483
971411AH1-196 GEN
Solar/Wind Harmer
14.224
971171AH1-044 GEN
Solar/Wind Harmer
18.922
274848CAMPGROVE;RU
Solar/Wind Harmer
0.002
970289AG2-191 GEN
Solar/Wind Harmer
1.796
274823ROCKFORD ;21
Adder
26.341
276612AE2-035 GEN
Solar/Wind Harmer
0.003
971681AH1-341 GEN
Solar/Wind Harmer
15.111
961011AF2-392 GEN
Solar/Wind Harmer
5.479
971619AH1-309 GEN
Solar/Wind Harmer
4.175
270071AF1-092 GEN
Solar/Wind Harmer
17.687
946321AF1-296 GEN
Solar/Wind Harmer
5.141
270594AE1-207 GEN
Solar/Wind Harmer
10.19
24725505WLD G2 C
Solar/Wind Harmer
0.002
24699105WLD G1 C
Solar/Wind Harmer
0.001
971549AH1-272 GEN
Solar/Wind Harmer
17.277
971609AH1-304 GEN
Solar/Wind Harmer
1.338
965101AG1-375 GEN
Solar/Wind Harmer
8.167
945581AF1-223 GEN
Solar/Wind Harmer
0.001
970115AG2-085 GEN
Solar/Wind Harmer
3.229
270240V3-007_GEN2
Solar/Wind Harmer
0.002
963791AG1-232 GEN
Solar/Wind Harmer
10.035
270024AE2-089 GEN
Solar/Wind Harmer
0.008
960441AF2-335 GEN
Solar/Wind Harmer
8.073
970825AG2-519 GEN
Solar/Wind Harmer
8.886
942221AE2-234 GEN
Solar/Wind Harmer
0.04
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
970611AG2-400 GEN
Solar/Wind Harmer
7.456
970627AG2-408 GEN
Solar/Wind Harmer
2.237
270383AD1-128 GEN
Solar/Wind Harmer
0.005
964611AG1-324 GEN
Solar/Wind Harmer
0.555
270201AC2-176 GEN
Solar/Wind Harmer
0.001
970883AG2-550 GEN
Solar/Wind Harmer
6.873
970885AG2-551 GEN
Solar/Wind Harmer
2.291
964571AG1-320 GEN
Solar/Wind Harmer
6.134
970235AG2-159 GEN
Solar/Wind Harmer
3.809
970235AG2-159 GEN
Solar/Wind Harmer
2.185
970653AG2-424 GEN
Solar/Wind Harmer
2.907
970653AG2-424 GEN
Solar/Wind Harmer
1.506
270543AE2-219 C
Solar/Wind Harmer
0.004
965041AG1-368 GEN
Solar/Wind Harmer
6.799
971029AG2-637 GEN
Solar/Wind Harmer
9.99
971673AH1-337 GEN
Solar/Wind Harmer
4.275
965051AG1-369 GEN
Solar/Wind Harmer
3.198
970455AG2-298 GEN
Solar/Wind Harmer
4.116
944201AF1-088_MTX
50/50
211.042
957141AF2-008_MTX
50/50
105.521
LAGNLTFEXP_LAGN->PJM
CLTF
11.815
TVALTFEXP_TVA->PJM
CLTF
4.631
CBM West 2LTFEXP_CBM-W2->PJM
CBM
121.55
NYPJM->LTFIMP_NY
CLTF
2.584
LGEELTFEXP_LGEE->PJM
CLTF
8.153
WECLTFEXP_WEC->PJM
CLTF
5.142
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.945
AG2-052LTFEXP_AG2-052->PJM
LTF
0.335
AH1-155LTFEXP_AH1-155->PJM
LTF
0.503
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.059
CBM West 1LTFEXP_CBM-W1->PJM
CBM
162.55
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.289
MECLTFEXP_MEC->PJM
CLTF
20.301
SIGELTFEXP_SIGE->PJM
CLTF
0.641

Details for 05HYATT-05VASSEL 345.0 kV Ckt 1 line l/o AEP_P4_#9728_05MALIS 138_L1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05HYATT-05VASSEL 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#9728_05MALIS 138_L1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:124.65 %
Rating:1409.0 MVA
Rating Type:B
MVA to Mitigate:1756.35
MW Contribution:6.33
Bus #Bus NameTypeMW Contribution
270475AD2-096_GEN
50/50
7.813
942871AE2-306 GEN
Solar/Wind Harmer
0.907
270391AF1-285 GEN3
Solar/Wind Harmer
0.465
241974AD2-163_GEN2
Solar/Wind Harmer
1.957
270466AD2-091
50/50
5.429
270471AD2-092_GEN
Solar/Wind Harmer
4.882
938701AE1-092 GEN
Solar/Wind Harmer
21.983
964601AG1-323 GEN
Solar/Wind Harmer
3.2
964601AG1-323 GEN
Solar/Wind Harmer
1.488
270224U2-072_GEN2
Solar/Wind Harmer
1.977
270227U2-072_GEN3
Solar/Wind Harmer
1.977
270228U2-072_GEN4
Solar/Wind Harmer
1.977
270231U2-072_GEN5
Solar/Wind Harmer
1.977
946101AF1-275 GEN
Solar/Wind Harmer
1.348
241960AC2-195 GEN
Solar/Wind Harmer
2.362
971201AH1-060 GEN
Solar/Wind Harmer
1.534
970077AG2-063 GEN
Solar/Wind Harmer
3.836
253378AE2-206_GEN
Solar/Wind Harmer
2.399
276820AF1-078_GEN
Solar/Wind Harmer
1.066
25326509SID D
Adder
0.833
246938BC-WTG3
Solar/Wind Harmer
2.396
246937BC-WTG2
Solar/Wind Harmer
2.355
270007AE1-245 C
Solar/Wind Harmer
3.344
270036AE2-216 BAT
50/50
5.972
270284AF1-227 GEN1
Solar/Wind Harmer
6.854
270286AF1-227 GEN2
Solar/Wind Harmer
2.536
270287AF1-227 GEN3
Solar/Wind Harmer
2.536
270578AF1-285 GEN2
Solar/Wind Harmer
0.465
241973AD2-163_GEN1
Solar/Wind Harmer
1.957
270302AB2-170 GEN
Solar/Wind Harmer
7.822
270317AD1-130_GEN
Solar/Wind Harmer
2.998
270520AE2-214 GEN
Solar/Wind Harmer
5.402
970179AG2-119 GEN
Solar/Wind Harmer
6.794
962771AG1-126 GEN
Solar/Wind Harmer
20.924
957201AF2-014 GEN
Solar/Wind Harmer
2.73
270435AC2-044 GEN
Solar/Wind Harmer
1.204
241972AD1-140 GEN
Solar/Wind Harmer
2.573
247607V1-011 GEN
Solar/Wind Harmer
2.229
965051AG1-369 GEN
Solar/Wind Harmer
2.769
270297AD1-101 GEN
Solar/Wind Harmer
1.544
965041AG1-368 GEN
Solar/Wind Harmer
5.379
945631AF1-228 GEN
Solar/Wind Harmer
2.515
270156DARBY CT1
Adder
4.69
270157DARBY CT2
Adder
4.678
270158DARBY CT3
Adder
4.603
943861AF1-054 GEN
Solar/Wind Harmer
1.939
943851AF1-053 GEN
Solar/Wind Harmer
0.937
963791AG1-232 GEN
Solar/Wind Harmer
6.797
270071AF1-092 GEN
Solar/Wind Harmer
7.236
270024AE2-089 GEN
Solar/Wind Harmer
2.257
24729505KEY G4
Adder
3.093
253349AC2-067 GEN
Solar/Wind Harmer
2.35
253400AC2-068 GEN
Solar/Wind Harmer
0.945
961761AG1-017 GEN
Solar/Wind Harmer
0.2
958711AF2-162 GEN
Solar/Wind Harmer
0.472
25306009OHH W.
Adder
1.34
253372AE2-315 SEC3
Adder
0.879
253372AE2-315 SEC3
Adder
0.879
965101AG1-375 GEN
Solar/Wind Harmer
4.631
971347AH1-153 GEN
Solar/Wind Harmer
6.938
971771AH1-392 GEN
Solar/Wind Harmer
4.117
270543AE2-219 C
Solar/Wind Harmer
2.339
945581AF1-223 GEN
Solar/Wind Harmer
2.071
944161AF1-084 GEN
Solar/Wind Harmer
1.002
971769AH1-391 GEN
Solar/Wind Harmer
4.525
971029AG2-637 GEN
Solar/Wind Harmer
6.782
971673AH1-337 GEN
Solar/Wind Harmer
2.073
253383AE2-342_GEN
Solar/Wind Harmer
0.399
960681AF2-359 GEN
Solar/Wind Harmer
1.7
970115AG2-085 GEN
Solar/Wind Harmer
1.77
274775LINCOLN ;6U
Adder
3.698
274776LINCOLN ;7U
Adder
3.698
274777LINCOLN ;8U
Adder
3.698
274814UNIV PK N;0U
Adder
2.205
274807UNIV PK N;3U
Adder
2.2
274805UNIV PK N;1U
Adder
2.19
274811UNIV PK N;7U
Adder
2.185
972037AH1-567 GEN1
Adder
0.08
274827FISK ;RP
Adder
3.37
972227AH1-698 GEN1
Adder
1.131
274687WILL CNTY;4U
Adder
12.072
274687WILL CNTY;4U
Adder
12.072
274675JOLIET 29;7U
Adder
13.243
274675JOLIET 29;7U
Adder
12.77
274731ELWOOD EC;2P
Adder
7.088
274733ELWOOD EC;3P
Adder
7.088
274735ELWOOD EC;4P
Adder
7.088
274728ELWOOD EC;5P
Adder
7.088
270054AF2-122 C O1
Solar/Wind Helper
0.823
971549AH1-272 GEN
Solar/Wind Harmer
6.331
270485AE1-090_GEN
Solar/Wind Harmer
0.566
942051AE2-217 GEN
Solar/Wind Harmer
13.984
970065AG2-057 GEN
Solar/Wind Harmer
0.767
970605AG2-385 GEN
Solar/Wind Harmer
3.836
241955AC1-078 GEN
Solar/Wind Harmer
5.001
970153AG2-106 GEN
Solar/Wind Harmer
9.124
270491AE1-102 GEN2
Solar/Wind Harmer
0.782
958091AF2-103 GEN
Solar/Wind Harmer
0.091
270191TR4_S_V150
Solar/Wind Harmer
1.663
270247TR4_N_V136
Solar/Wind Harmer
0.472
270258AD1-119 GEN
Solar/Wind Harmer
1.498
959331AF2-224 GEN
Solar/Wind Harmer
5.315
965021AG1-366 GEN
Solar/Wind Harmer
1.236
270044AE2-322 C
Solar/Wind Harmer
0.691
270404AC1-167 GEN
Solar/Wind Harmer
0.576
270588AE1-091_GEN
Solar/Wind Harmer
5.503
270043AE2-236 GEN
Solar/Wind Harmer
2.714
253338AC1-165 GEN
Solar/Wind Harmer
0.526
253333AC1-068 GEN
Solar/Wind Harmer
0.507
970031AG2-029 GEN
Solar/Wind Harmer
14.514
971617AH1-308 GEN
Solar/Wind Harmer
2.796
944531AF1-118 GEN
Solar/Wind Harmer
16.819
270541AE2-072 C
Solar/Wind Harmer
2.163
962031AG1-047 GEN
Solar/Wind Harmer
1.413
957741AF2-068 GEN
Solar/Wind Harmer
7.01
253303V4-073 C
Solar/Wind Harmer
0.054
253370AE2-315 SEC1
Adder
0.929
253371AE2-315 SEC2
Adder
0.879
970349AG2-230 GEN
Solar/Wind Harmer
6.938
247643Z2-116 C
Solar/Wind Harmer
0.032
945111AF1-176 GEN
Solar/Wind Harmer
2.591
24642205MAYFLWER
Adder
0.29
970513AG2-328 GEN
Solar/Wind Harmer
8.061
970517AG2-330 GEN
Solar/Wind Harmer
7.311
24441205WTRV SLR C
Solar/Wind Harmer
0.061
247604X1-042
Adder
0.187
946031AF1-268 GEN
Solar/Wind Harmer
3.715
958821AF2-173 GEN
Solar/Wind Harmer
6.18
270004AE1-209 GEN
Solar/Wind Harmer
2.413
274752CRETE EC ;2U
Adder
3.613
274753CRETE EC ;3U
Adder
3.613
274772LINCOLN ;3U
Adder
3.698
274724RIVER EC ;11
Adder
7.758
274802UNIV PARK;5U
Adder
2.533
274826FISK ;BP
Adder
4.755
274800UNIV PARK;3U
Adder
2.53
972038AH1-567 GEN2
Adder
0.158
972228AH1-698 GEN2
Adder
1.606
274676JOLIET 29;8U
Adder
12.77
274729ELWOOD EC;1P
Adder
7.088
274730ELWOOD EC;6P
Adder
7.088
274734ELWOOD EC;8P
Adder
7.088
274736ELWOOD EC;9P
Adder
7.088
270349AD2-093_GEN
Solar/Wind Harmer
4.882
971995AH1-542 GEN
Solar/Wind Harmer
11.801
270223U2-072_GEN1
Solar/Wind Harmer
1.977
270578AF1-285 GEN2
Solar/Wind Harmer
1.209
270391AF1-285 GEN3
Solar/Wind Harmer
1.209
270462AD2-086
Solar/Wind Harmer
6.507
241813AF1-122_GEN
Solar/Wind Harmer
4.908
970593AG2-378 GEN
Solar/Wind Harmer
1.421
962761AG1-125 GEN
Solar/Wind Harmer
20.924
970149AG2-104 GEN
Solar/Wind Harmer
25.841
970155AG2-107 GEN
Solar/Wind Harmer
9.124
246936BC-WTG1
Solar/Wind Harmer
2.355
270489AE1-102 GEN1
Solar/Wind Harmer
0.782
965421AG1-410 GEN
Solar/Wind Harmer
17.855
247521TR3_G114
Solar/Wind Harmer
1.865
270246TR4_N_V150
Solar/Wind Harmer
0.472
24695305TIMB G C
Solar/Wind Harmer
3.018
965011AG1-365 GEN
Solar/Wind Harmer
5.315
270159DARBY CT4
Adder
4.615
944231AF1-091 GEN
Solar/Wind Harmer
1.845
253343AC1-166 GEN
Solar/Wind Harmer
0.526
253325AC1-069 GEN
Solar/Wind Harmer
0.507
960071AF2-298 GEN
Solar/Wind Harmer
2.404
25326309TAIT D
Adder
0.526
270063AE2-323 C
Solar/Wind Harmer
1.058
965651AG1-433 GEN
Solar/Wind Harmer
2.549
24639705ELKHART HY
Adder
0.071
253370AE2-315 SEC1
Adder
0.929
253371AE2-315 SEC2
Adder
0.879
958861AF2-177 GEN
Solar/Wind Harmer
5.061
247536S-71 GEN
Solar/Wind Harmer
1.868
945111AF1-176 GEN
Solar/Wind Harmer
8.176
270505AE1-170 C O1
Solar/Wind Harmer
6.853
945371AF1-202 GEN
Solar/Wind Harmer
3.186
270449AD2-020 GEN
Solar/Wind Harmer
1.276
943021AE2-325 GEN
Solar/Wind Harmer
1.657
970245AG2-165 GEN
Solar/Wind Harmer
8.061
970825AG2-519 GEN
Solar/Wind Harmer
1.042
270005AE1-210 C O1
Solar/Wind Harmer
2.413
965031AG1-367 GEN
Solar/Wind Harmer
4.414
970373AG2-245 GEN
Solar/Wind Harmer
9.267
274751CRETE EC ;1U
Adder
3.613
274754CRETE EC ;4U
Adder
3.613
274773LINCOLN ;4U
Adder
3.698
274774LINCOLN ;5U
Adder
3.698
274723RIVER EC ;12
Adder
7.85
274812UNIV PK N;8U
Adder
2.185
274801UNIV PARK;4U
Adder
2.53
274676JOLIET 29;8U
Adder
13.243
274674JOLIET 9 ;6U
Adder
6.64
274732ELWOOD EC;7P
Adder
7.088
942801AE2-298 GEN
Solar/Wind Harmer
0.852
970611AG2-400 GEN
Solar/Wind Harmer
5.315
270518AE2-148 GEN
Solar/Wind Harmer
6.282
942861AE2-305 GEN
Solar/Wind Harmer
3.928
25326109MON D
Adder
0.653
25322209TAIT E
Adder
4.68
25322209TAIT E
Adder
4.575
942221AE2-234 GEN
Solar/Wind Harmer
0.35
247620Y3-023
Adder
0.215
270201AC2-176 GEN
Solar/Wind Harmer
2.402
944541AF1-119 GEN
Solar/Wind Harmer
1.954
960971AF2-388 GEN
Solar/Wind Harmer
5.098
247621Y3-024
Adder
0.112
253370AE2-315 SEC1
Adder
0.929
964611AG1-324 GEN
Solar/Wind Harmer
0.546
964611AG1-324 GEN
Solar/Wind Harmer
0.242
270216AD2-079_GEN
Solar/Wind Harmer
0.28
960981AF2-389 GEN
Solar/Wind Harmer
0.691
957891AF2-083 GEN
Solar/Wind Harmer
1.542
970883AG2-550 GEN
Solar/Wind Harmer
4.568
970885AG2-551 GEN
Solar/Wind Harmer
1.062
961051AF2-396 GEN
Solar/Wind Harmer
7.242
961051AF2-396 GEN
Solar/Wind Harmer
3.368
270526AF1-158 GEN
Solar/Wind Harmer
2.06
24441505OLIV SLR
Solar/Wind Harmer
0.061
970321AG2-212 GEN
Solar/Wind Harmer
8.061
270599AE1-208 GEN
Solar/Wind Harmer
3.679
270031AE2-169
Solar/Wind Harmer
3.679
965681AG1-436 GEN
Solar/Wind Harmer
5.624
965791AG1-447 GEN
Solar/Wind Harmer
2.877
970825AG2-519 GEN
Solar/Wind Harmer
4.672
960441AF2-335 GEN
Solar/Wind Harmer
4.424
274770LINCOLN ;1U
Adder
3.698
274771LINCOLN ;2U
Adder
3.698
274808UNIV PK N;4U
Adder
2.176
274803UNIV PARK;6U
Adder
2.533
972259AH1-714 GEN
Adder
8.267
274674JOLIET 9 ;6U
Adder
6.64
LAGNLTFEXP_LAGN->PJM
CLTF
5.126
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.351
TVALTFEXP_TVA->PJM
CLTF
2.378
CPLELTFEXP_CPLE->PJM
CLTF
0.349
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.92
NYPJM->LTFIMP_NY
CLTF
1.307
LGEELTFEXP_LGEE->PJM
CLTF
2.299
WECLTFEXP_WEC->PJM
CLTF
1.593
AG2-052LTFEXP_AG2-052->PJM
LTF
0.101
AH1-155LTFEXP_AH1-155->PJM
LTF
0.151
CBM West 1LTFEXP_CBM-W1->PJM
CBM
56.507
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.587
MECLTFEXP_MEC->PJM
CLTF
6.34
SIGELTFEXP_SIGE->PJM
CLTF
0.182

Details for 05HYATT-05VASSEL 345.0 kV Ckt 1 line l/o AEP_P4_#9730_05MALIS 138_P1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05HYATT-05VASSEL 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#9730_05MALIS 138_P1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:124.16 %
Rating:1409.0 MVA
Rating Type:B
MVA to Mitigate:1749.36
MW Contribution:6.32
Bus #Bus NameTypeMW Contribution
270036AE2-216 BAT
50/50
5.958
270284AF1-227 GEN1
Solar/Wind Harmer
6.838
270286AF1-227 GEN2
Solar/Wind Harmer
2.53
270287AF1-227 GEN3
Solar/Wind Harmer
2.53
270578AF1-285 GEN2
Solar/Wind Harmer
0.464
241973AD2-163_GEN1
Solar/Wind Harmer
1.951
270302AB2-170 GEN
Solar/Wind Harmer
7.804
270317AD1-130_GEN
Solar/Wind Harmer
2.992
270520AE2-214 GEN
Solar/Wind Harmer
5.387
970179AG2-119 GEN
Solar/Wind Harmer
6.779
962771AG1-126 GEN
Solar/Wind Harmer
20.876
957201AF2-014 GEN
Solar/Wind Harmer
2.724
270435AC2-044 GEN
Solar/Wind Harmer
1.201
241972AD1-140 GEN
Solar/Wind Harmer
2.566
247607V1-011 GEN
Solar/Wind Harmer
2.224
965051AG1-369 GEN
Solar/Wind Harmer
2.763
270297AD1-101 GEN
Solar/Wind Harmer
1.54
965041AG1-368 GEN
Solar/Wind Harmer
5.367
945631AF1-228 GEN
Solar/Wind Harmer
2.511
270156DARBY CT1
Adder
4.681
270157DARBY CT2
Adder
4.67
270158DARBY CT3
Adder
4.595
963791AG1-232 GEN
Solar/Wind Harmer
6.783
943861AF1-054 GEN
Solar/Wind Harmer
1.926
943851AF1-053 GEN
Solar/Wind Harmer
0.931
270071AF1-092 GEN
Solar/Wind Harmer
7.22
270024AE2-089 GEN
Solar/Wind Harmer
2.252
24729505KEY G4
Adder
3.086
253349AC2-067 GEN
Solar/Wind Harmer
2.345
253400AC2-068 GEN
Solar/Wind Harmer
0.943
961761AG1-017 GEN
Solar/Wind Harmer
0.2
958711AF2-162 GEN
Solar/Wind Harmer
0.471
25306009OHH W.
Adder
1.337
253372AE2-315 SEC3
Adder
0.877
253372AE2-315 SEC3
Adder
0.877
965101AG1-375 GEN
Solar/Wind Harmer
4.621
971347AH1-153 GEN
Solar/Wind Harmer
6.923
971771AH1-392 GEN
Solar/Wind Harmer
4.108
270543AE2-219 C
Solar/Wind Harmer
2.334
945581AF1-223 GEN
Solar/Wind Harmer
2.066
944161AF1-084 GEN
Solar/Wind Harmer
1
270349AD2-093_GEN
Solar/Wind Harmer
4.871
971995AH1-542 GEN
Solar/Wind Harmer
11.773
270223U2-072_GEN1
Solar/Wind Harmer
1.972
270578AF1-285 GEN2
Solar/Wind Harmer
1.206
270391AF1-285 GEN3
Solar/Wind Harmer
1.206
270462AD2-086
Solar/Wind Harmer
6.492
241813AF1-122_GEN
Solar/Wind Harmer
4.897
970593AG2-378 GEN
Solar/Wind Harmer
1.416
962761AG1-125 GEN
Solar/Wind Harmer
20.876
970149AG2-104 GEN
Solar/Wind Harmer
25.782
970155AG2-107 GEN
Solar/Wind Harmer
9.103
246936BC-WTG1
Solar/Wind Harmer
2.35
971769AH1-391 GEN
Solar/Wind Harmer
4.515
971029AG2-637 GEN
Solar/Wind Harmer
6.767
971673AH1-337 GEN
Solar/Wind Harmer
2.069
960681AF2-359 GEN
Solar/Wind Harmer
1.696
253383AE2-342_GEN
Solar/Wind Harmer
0.396
970115AG2-085 GEN
Solar/Wind Harmer
1.766
274775LINCOLN ;6U
Adder
3.69
274776LINCOLN ;7U
Adder
3.69
274777LINCOLN ;8U
Adder
3.69
274814UNIV PK N;0U
Adder
2.2
274807UNIV PK N;3U
Adder
2.195
274805UNIV PK N;1U
Adder
2.186
274811UNIV PK N;7U
Adder
2.181
972037AH1-567 GEN1
Adder
0.079
270489AE1-102 GEN1
Solar/Wind Harmer
0.781
965421AG1-410 GEN
Solar/Wind Harmer
17.815
247521TR3_G114
Solar/Wind Harmer
1.86
270246TR4_N_V150
Solar/Wind Harmer
0.471
24695305TIMB G C
Solar/Wind Harmer
3.012
965011AG1-365 GEN
Solar/Wind Harmer
5.303
270159DARBY CT4
Adder
4.607
944231AF1-091 GEN
Solar/Wind Harmer
1.841
253343AC1-166 GEN
Solar/Wind Harmer
0.525
253325AC1-069 GEN
Solar/Wind Harmer
0.506
960071AF2-298 GEN
Solar/Wind Harmer
2.398
25326309TAIT D
Adder
0.525
270063AE2-323 C
Solar/Wind Harmer
1.055
965651AG1-433 GEN
Solar/Wind Harmer
2.544
24639705ELKHART HY
Adder
0.071
253370AE2-315 SEC1
Adder
0.927
253371AE2-315 SEC2
Adder
0.877
958861AF2-177 GEN
Solar/Wind Harmer
5.05
247536S-71 GEN
Solar/Wind Harmer
1.864
945111AF1-176 GEN
Solar/Wind Harmer
8.158
270475AD2-096_GEN
50/50
7.794
942871AE2-306 GEN
Solar/Wind Harmer
0.905
270391AF1-285 GEN3
Solar/Wind Harmer
0.464
241974AD2-163_GEN2
Solar/Wind Harmer
1.951
270485AE1-090_GEN
Solar/Wind Harmer
0.564
942051AE2-217 GEN
Solar/Wind Harmer
13.946
970065AG2-057 GEN
Solar/Wind Harmer
0.765
970605AG2-385 GEN
Solar/Wind Harmer
3.824
241955AC1-078 GEN
Solar/Wind Harmer
4.991
970153AG2-106 GEN
Solar/Wind Harmer
9.103
270491AE1-102 GEN2
Solar/Wind Harmer
0.781
958091AF2-103 GEN
Solar/Wind Harmer
0.091
270191TR4_S_V150
Solar/Wind Harmer
1.66
270247TR4_N_V136
Solar/Wind Harmer
0.471
270258AD1-119 GEN
Solar/Wind Harmer
1.494
959331AF2-224 GEN
Solar/Wind Harmer
5.303
965021AG1-366 GEN
Solar/Wind Harmer
1.233
270044AE2-322 C
Solar/Wind Harmer
0.69
270404AC1-167 GEN
Solar/Wind Harmer
0.574
270588AE1-091_GEN
Solar/Wind Harmer
5.492
270043AE2-236 GEN
Solar/Wind Harmer
2.708
253338AC1-165 GEN
Solar/Wind Harmer
0.525
253333AC1-068 GEN
Solar/Wind Harmer
0.506
970031AG2-029 GEN
Solar/Wind Harmer
14.483
971617AH1-308 GEN
Solar/Wind Harmer
2.79
944531AF1-118 GEN
Solar/Wind Harmer
16.782
270541AE2-072 C
Solar/Wind Harmer
2.158
962031AG1-047 GEN
Solar/Wind Harmer
1.409
957741AF2-068 GEN
Solar/Wind Harmer
6.995
253303V4-073 C
Solar/Wind Harmer
0.054
253370AE2-315 SEC1
Adder
0.927
253371AE2-315 SEC2
Adder
0.877
970349AG2-230 GEN
Solar/Wind Harmer
6.923
247643Z2-116 C
Solar/Wind Harmer
0.032
945111AF1-176 GEN
Solar/Wind Harmer
2.586
24642205MAYFLWER
Adder
0.289
970513AG2-328 GEN
Solar/Wind Harmer
8.044
970517AG2-330 GEN
Solar/Wind Harmer
7.296
24441205WTRV SLR C
Solar/Wind Harmer
0.061
247604X1-042
Adder
0.186
946031AF1-268 GEN
Solar/Wind Harmer
3.707
958821AF2-173 GEN
Solar/Wind Harmer
6.167
270004AE1-209 GEN
Solar/Wind Harmer
2.407
274752CRETE EC ;2U
Adder
3.605
274753CRETE EC ;3U
Adder
3.605
274772LINCOLN ;3U
Adder
3.69
274724RIVER EC ;11
Adder
7.742
274802UNIV PARK;5U
Adder
2.528
274826FISK ;BP
Adder
4.745
274800UNIV PARK;3U
Adder
2.525
972038AH1-567 GEN2
Adder
0.158
972228AH1-698 GEN2
Adder
1.603
274676JOLIET 29;8U
Adder
12.743
274729ELWOOD EC;1P
Adder
7.072
274730ELWOOD EC;6P
Adder
7.073
274734ELWOOD EC;8P
Adder
7.073
274736ELWOOD EC;9P
Adder
7.073
270466AD2-091
50/50
5.416
270471AD2-092_GEN
Solar/Wind Harmer
4.871
938701AE1-092 GEN
Solar/Wind Harmer
21.927
964601AG1-323 GEN
Solar/Wind Harmer
3.191
964601AG1-323 GEN
Solar/Wind Harmer
1.484
270224U2-072_GEN2
Solar/Wind Harmer
1.972
270227U2-072_GEN3
Solar/Wind Harmer
1.972
270228U2-072_GEN4
Solar/Wind Harmer
1.972
270231U2-072_GEN5
Solar/Wind Harmer
1.972
274827FISK ;RP
Adder
3.363
972227AH1-698 GEN1
Adder
1.129
274687WILL CNTY;4U
Adder
12.046
274687WILL CNTY;4U
Adder
12.046
274675JOLIET 29;7U
Adder
13.215
274675JOLIET 29;7U
Adder
12.743
274731ELWOOD EC;2P
Adder
7.072
274733ELWOOD EC;3P
Adder
7.072
274735ELWOOD EC;4P
Adder
7.072
274728ELWOOD EC;5P
Adder
7.073
270054AF2-122 C O1
Solar/Wind Helper
0.817
971549AH1-272 GEN
Solar/Wind Harmer
6.317
270505AE1-170 C O1
Solar/Wind Harmer
6.839
945371AF1-202 GEN
Solar/Wind Harmer
3.179
270449AD2-020 GEN
Solar/Wind Harmer
1.273
943021AE2-325 GEN
Solar/Wind Harmer
1.654
970245AG2-165 GEN
Solar/Wind Harmer
8.044
970825AG2-519 GEN
Solar/Wind Harmer
1.04
270005AE1-210 C O1
Solar/Wind Harmer
2.407
965031AG1-367 GEN
Solar/Wind Harmer
4.405
970373AG2-245 GEN
Solar/Wind Harmer
9.248
274751CRETE EC ;1U
Adder
3.605
274754CRETE EC ;4U
Adder
3.605
274773LINCOLN ;4U
Adder
3.69
274774LINCOLN ;5U
Adder
3.69
274723RIVER EC ;12
Adder
7.833
274812UNIV PK N;8U
Adder
2.181
274801UNIV PARK;4U
Adder
2.525
274676JOLIET 29;8U
Adder
13.215
274674JOLIET 9 ;6U
Adder
6.626
274732ELWOOD EC;7P
Adder
7.073
946101AF1-275 GEN
Solar/Wind Harmer
1.344
241960AC2-195 GEN
Solar/Wind Harmer
2.356
971201AH1-060 GEN
Solar/Wind Harmer
1.53
970077AG2-063 GEN
Solar/Wind Harmer
3.824
253378AE2-206_GEN
Solar/Wind Harmer
2.393
276820AF1-078_GEN
Solar/Wind Harmer
1.063
25326509SID D
Adder
0.831
246938BC-WTG3
Solar/Wind Harmer
2.391
246937BC-WTG2
Solar/Wind Harmer
2.35
270007AE1-245 C
Solar/Wind Harmer
3.337
942801AE2-298 GEN
Solar/Wind Harmer
0.85
970611AG2-400 GEN
Solar/Wind Harmer
5.303
270518AE2-148 GEN
Solar/Wind Harmer
6.27
942861AE2-305 GEN
Solar/Wind Harmer
3.903
25326109MON D
Adder
0.652
25322209TAIT E
Adder
4.67
25322209TAIT E
Adder
4.565
942221AE2-234 GEN
Solar/Wind Harmer
0.35
247620Y3-023
Adder
0.215
270201AC2-176 GEN
Solar/Wind Harmer
2.397
944541AF1-119 GEN
Solar/Wind Harmer
1.949
960971AF2-388 GEN
Solar/Wind Harmer
5.087
247621Y3-024
Adder
0.112
253370AE2-315 SEC1
Adder
0.927
964611AG1-324 GEN
Solar/Wind Harmer
0.545
964611AG1-324 GEN
Solar/Wind Harmer
0.242
270216AD2-079_GEN
Solar/Wind Harmer
0.279
960981AF2-389 GEN
Solar/Wind Harmer
0.69
957891AF2-083 GEN
Solar/Wind Harmer
1.539
970883AG2-550 GEN
Solar/Wind Harmer
4.558
970885AG2-551 GEN
Solar/Wind Harmer
1.06
961051AF2-396 GEN
Solar/Wind Harmer
7.227
961051AF2-396 GEN
Solar/Wind Harmer
3.361
270526AF1-158 GEN
Solar/Wind Harmer
2.056
24441505OLIV SLR
Solar/Wind Harmer
0.06
970321AG2-212 GEN
Solar/Wind Harmer
8.044
270599AE1-208 GEN
Solar/Wind Harmer
3.671
270031AE2-169
Solar/Wind Harmer
3.671
965681AG1-436 GEN
Solar/Wind Harmer
5.612
965791AG1-447 GEN
Solar/Wind Harmer
2.871
970825AG2-519 GEN
Solar/Wind Harmer
4.662
960441AF2-335 GEN
Solar/Wind Harmer
4.415
274770LINCOLN ;1U
Adder
3.69
274771LINCOLN ;2U
Adder
3.69
274808UNIV PK N;4U
Adder
2.171
274803UNIV PARK;6U
Adder
2.528
972259AH1-714 GEN
Adder
8.249
274674JOLIET 9 ;6U
Adder
6.626
LAGNLTFEXP_LAGN->PJM
CLTF
5.116
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.348
TVALTFEXP_TVA->PJM
CLTF
2.374
CPLELTFEXP_CPLE->PJM
CLTF
0.349
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.837
NYPJM->LTFIMP_NY
CLTF
1.305
LGEELTFEXP_LGEE->PJM
CLTF
2.295
WECLTFEXP_WEC->PJM
CLTF
1.59
AG2-052LTFEXP_AG2-052->PJM
LTF
0.1
AH1-155LTFEXP_AH1-155->PJM
LTF
0.151
CBM West 1LTFEXP_CBM-W1->PJM
CBM
56.388
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.568
MECLTFEXP_MEC->PJM
CLTF
6.327
SIGELTFEXP_SIGE->PJM
CLTF
0.182

Details for 05HYATT-05VASSEL 345.0 kV Ckt 1 line l/o AEP_P4_#9729_05MALIS 138_M1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05HYATT-05VASSEL 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#9729_05MALIS 138_M1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:124.05 %
Rating:1409.0 MVA
Rating Type:B
MVA to Mitigate:1747.91
MW Contribution:6.31
Bus #Bus NameTypeMW Contribution
270475AD2-096_GEN
50/50
7.79
942871AE2-306 GEN
Solar/Wind Harmer
0.904
270391AF1-285 GEN3
Solar/Wind Harmer
0.464
241974AD2-163_GEN2
Solar/Wind Harmer
1.95
270485AE1-090_GEN
Solar/Wind Harmer
0.564
942051AE2-217 GEN
Solar/Wind Harmer
13.937
970065AG2-057 GEN
Solar/Wind Harmer
0.765
970605AG2-385 GEN
Solar/Wind Harmer
3.821
241955AC1-078 GEN
Solar/Wind Harmer
4.989
970153AG2-106 GEN
Solar/Wind Harmer
9.098
270491AE1-102 GEN2
Solar/Wind Harmer
0.78
958091AF2-103 GEN
Solar/Wind Harmer
0.091
270191TR4_S_V150
Solar/Wind Harmer
1.659
270247TR4_N_V136
Solar/Wind Harmer
0.47
270258AD1-119 GEN
Solar/Wind Harmer
1.494
959331AF2-224 GEN
Solar/Wind Harmer
5.301
965021AG1-366 GEN
Solar/Wind Harmer
1.233
270044AE2-322 C
Solar/Wind Harmer
0.689
270404AC1-167 GEN
Solar/Wind Harmer
0.574
270588AE1-091_GEN
Solar/Wind Harmer
5.49
270043AE2-236 GEN
Solar/Wind Harmer
2.707
253338AC1-165 GEN
Solar/Wind Harmer
0.525
253333AC1-068 GEN
Solar/Wind Harmer
0.506
970031AG2-029 GEN
Solar/Wind Harmer
14.476
971617AH1-308 GEN
Solar/Wind Harmer
2.788
944531AF1-118 GEN
Solar/Wind Harmer
16.774
270541AE2-072 C
Solar/Wind Harmer
2.157
962031AG1-047 GEN
Solar/Wind Harmer
1.409
957741AF2-068 GEN
Solar/Wind Harmer
6.991
253303V4-073 C
Solar/Wind Harmer
0.054
253370AE2-315 SEC1
Adder
0.926
253371AE2-315 SEC2
Adder
0.876
970349AG2-230 GEN
Solar/Wind Harmer
6.92
247643Z2-116 C
Solar/Wind Harmer
0.032
945111AF1-176 GEN
Solar/Wind Harmer
2.584
24642205MAYFLWER
Adder
0.289
970513AG2-328 GEN
Solar/Wind Harmer
8.04
970517AG2-330 GEN
Solar/Wind Harmer
7.292
24441205WTRV SLR C
Solar/Wind Harmer
0.061
247604X1-042
Adder
0.186
946031AF1-268 GEN
Solar/Wind Harmer
3.705
958821AF2-173 GEN
Solar/Wind Harmer
6.164
270004AE1-209 GEN
Solar/Wind Harmer
2.406
274752CRETE EC ;2U
Adder
3.603
274753CRETE EC ;3U
Adder
3.603
274772LINCOLN ;3U
Adder
3.688
274724RIVER EC ;11
Adder
7.738
274802UNIV PARK;5U
Adder
2.527
274826FISK ;BP
Adder
4.742
274800UNIV PARK;3U
Adder
2.524
972038AH1-567 GEN2
Adder
0.158
972228AH1-698 GEN2
Adder
1.602
274676JOLIET 29;8U
Adder
12.736
274729ELWOOD EC;1P
Adder
7.069
274730ELWOOD EC;6P
Adder
7.069
274734ELWOOD EC;8P
Adder
7.069
274736ELWOOD EC;9P
Adder
7.069
270036AE2-216 BAT
50/50
5.955
270284AF1-227 GEN1
Solar/Wind Harmer
6.834
270286AF1-227 GEN2
Solar/Wind Harmer
2.528
270287AF1-227 GEN3
Solar/Wind Harmer
2.528
270578AF1-285 GEN2
Solar/Wind Harmer
0.464
241973AD2-163_GEN1
Solar/Wind Harmer
1.95
270302AB2-170 GEN
Solar/Wind Harmer
7.799
270317AD1-130_GEN
Solar/Wind Harmer
2.99
270520AE2-214 GEN
Solar/Wind Harmer
5.383
970179AG2-119 GEN
Solar/Wind Harmer
6.775
962771AG1-126 GEN
Solar/Wind Harmer
20.865
957201AF2-014 GEN
Solar/Wind Harmer
2.722
270435AC2-044 GEN
Solar/Wind Harmer
1.201
241972AD1-140 GEN
Solar/Wind Harmer
2.565
247607V1-011 GEN
Solar/Wind Harmer
2.223
965051AG1-369 GEN
Solar/Wind Harmer
2.761
270297AD1-101 GEN
Solar/Wind Harmer
1.539
965041AG1-368 GEN
Solar/Wind Harmer
5.365
945631AF1-228 GEN
Solar/Wind Harmer
2.51
270156DARBY CT1
Adder
4.68
270157DARBY CT2
Adder
4.668
270158DARBY CT3
Adder
4.594
963791AG1-232 GEN
Solar/Wind Harmer
6.779
943861AF1-054 GEN
Solar/Wind Harmer
1.923
943851AF1-053 GEN
Solar/Wind Harmer
0.929
270071AF1-092 GEN
Solar/Wind Harmer
7.217
270024AE2-089 GEN
Solar/Wind Harmer
2.251
24729505KEY G4
Adder
3.085
253349AC2-067 GEN
Solar/Wind Harmer
2.344
253400AC2-068 GEN
Solar/Wind Harmer
0.943
961761AG1-017 GEN
Solar/Wind Harmer
0.199
958711AF2-162 GEN
Solar/Wind Harmer
0.471
25306009OHH W.
Adder
1.337
253372AE2-315 SEC3
Adder
0.876
253372AE2-315 SEC3
Adder
0.876
965101AG1-375 GEN
Solar/Wind Harmer
4.618
971347AH1-153 GEN
Solar/Wind Harmer
6.92
971771AH1-392 GEN
Solar/Wind Harmer
4.106
270543AE2-219 C
Solar/Wind Harmer
2.333
945581AF1-223 GEN
Solar/Wind Harmer
2.065
944161AF1-084 GEN
Solar/Wind Harmer
1
971769AH1-391 GEN
Solar/Wind Harmer
4.513
971029AG2-637 GEN
Solar/Wind Harmer
6.764
971673AH1-337 GEN
Solar/Wind Harmer
2.068
960681AF2-359 GEN
Solar/Wind Harmer
1.695
253383AE2-342_GEN
Solar/Wind Harmer
0.395
970115AG2-085 GEN
Solar/Wind Harmer
1.765
274775LINCOLN ;6U
Adder
3.688
274776LINCOLN ;7U
Adder
3.688
274777LINCOLN ;8U
Adder
3.688
274814UNIV PK N;0U
Adder
2.199
274807UNIV PK N;3U
Adder
2.194
274805UNIV PK N;1U
Adder
2.185
274811UNIV PK N;7U
Adder
2.18
972037AH1-567 GEN1
Adder
0.079
274827FISK ;RP
Adder
3.361
972227AH1-698 GEN1
Adder
1.128
274687WILL CNTY;4U
Adder
12.041
274687WILL CNTY;4U
Adder
12.041
274675JOLIET 29;7U
Adder
13.208
274675JOLIET 29;7U
Adder
12.736
274731ELWOOD EC;2P
Adder
7.069
274733ELWOOD EC;3P
Adder
7.069
274735ELWOOD EC;4P
Adder
7.069
274728ELWOOD EC;5P
Adder
7.069
270054AF2-122 C O1
Solar/Wind Helper
0.816
971549AH1-272 GEN
Solar/Wind Harmer
6.314
270349AD2-093_GEN
Solar/Wind Harmer
4.868
971995AH1-542 GEN
Solar/Wind Harmer
11.766
270223U2-072_GEN1
Solar/Wind Harmer
1.971
270578AF1-285 GEN2
Solar/Wind Harmer
1.206
270391AF1-285 GEN3
Solar/Wind Harmer
1.206
270462AD2-086
Solar/Wind Harmer
6.488
241813AF1-122_GEN
Solar/Wind Harmer
4.895
970593AG2-378 GEN
Solar/Wind Harmer
1.415
962761AG1-125 GEN
Solar/Wind Harmer
20.865
970149AG2-104 GEN
Solar/Wind Harmer
25.768
970155AG2-107 GEN
Solar/Wind Harmer
9.098
246936BC-WTG1
Solar/Wind Harmer
2.349
270489AE1-102 GEN1
Solar/Wind Harmer
0.78
965421AG1-410 GEN
Solar/Wind Harmer
17.806
247521TR3_G114
Solar/Wind Harmer
1.86
270246TR4_N_V150
Solar/Wind Harmer
0.47
24695305TIMB G C
Solar/Wind Harmer
3.01
965011AG1-365 GEN
Solar/Wind Harmer
5.301
270159DARBY CT4
Adder
4.605
944231AF1-091 GEN
Solar/Wind Harmer
1.84
253343AC1-166 GEN
Solar/Wind Harmer
0.525
253325AC1-069 GEN
Solar/Wind Harmer
0.506
960071AF2-298 GEN
Solar/Wind Harmer
2.397
25326309TAIT D
Adder
0.525
270063AE2-323 C
Solar/Wind Harmer
1.055
965651AG1-433 GEN
Solar/Wind Harmer
2.542
24639705ELKHART HY
Adder
0.071
253370AE2-315 SEC1
Adder
0.926
253371AE2-315 SEC2
Adder
0.876
958861AF2-177 GEN
Solar/Wind Harmer
5.048
247536S-71 GEN
Solar/Wind Harmer
1.863
945111AF1-176 GEN
Solar/Wind Harmer
8.154
270505AE1-170 C O1
Solar/Wind Harmer
6.835
945371AF1-202 GEN
Solar/Wind Harmer
3.177
270449AD2-020 GEN
Solar/Wind Harmer
1.272
943021AE2-325 GEN
Solar/Wind Harmer
1.653
970245AG2-165 GEN
Solar/Wind Harmer
8.04
970825AG2-519 GEN
Solar/Wind Harmer
1.04
270005AE1-210 C O1
Solar/Wind Harmer
2.406
965031AG1-367 GEN
Solar/Wind Harmer
4.403
970373AG2-245 GEN
Solar/Wind Harmer
9.243
274751CRETE EC ;1U
Adder
3.603
274754CRETE EC ;4U
Adder
3.603
274773LINCOLN ;4U
Adder
3.688
274774LINCOLN ;5U
Adder
3.688
274723RIVER EC ;12
Adder
7.829
274812UNIV PK N;8U
Adder
2.18
274801UNIV PARK;4U
Adder
2.524
274676JOLIET 29;8U
Adder
13.208
274674JOLIET 9 ;6U
Adder
6.622
274732ELWOOD EC;7P
Adder
7.069
270466AD2-091
50/50
5.413
270471AD2-092_GEN
Solar/Wind Harmer
4.868
938701AE1-092 GEN
Solar/Wind Harmer
21.914
964601AG1-323 GEN
Solar/Wind Harmer
3.189
964601AG1-323 GEN
Solar/Wind Harmer
1.483
270224U2-072_GEN2
Solar/Wind Harmer
1.971
270227U2-072_GEN3
Solar/Wind Harmer
1.971
270228U2-072_GEN4
Solar/Wind Harmer
1.971
270231U2-072_GEN5
Solar/Wind Harmer
1.971
946101AF1-275 GEN
Solar/Wind Harmer
1.343
241960AC2-195 GEN
Solar/Wind Harmer
2.355
971201AH1-060 GEN
Solar/Wind Harmer
1.53
970077AG2-063 GEN
Solar/Wind Harmer
3.821
253378AE2-206_GEN
Solar/Wind Harmer
2.391
276820AF1-078_GEN
Solar/Wind Harmer
1.062
25326509SID D
Adder
0.831
246938BC-WTG3
Solar/Wind Harmer
2.389
246937BC-WTG2
Solar/Wind Harmer
2.349
270007AE1-245 C
Solar/Wind Harmer
3.335
942801AE2-298 GEN
Solar/Wind Harmer
0.849
970611AG2-400 GEN
Solar/Wind Harmer
5.301
270518AE2-148 GEN
Solar/Wind Harmer
6.267
942861AE2-305 GEN
Solar/Wind Harmer
3.897
25326109MON D
Adder
0.651
25322209TAIT E
Adder
4.667
25322209TAIT E
Adder
4.562
942221AE2-234 GEN
Solar/Wind Harmer
0.349
247620Y3-023
Adder
0.215
270201AC2-176 GEN
Solar/Wind Harmer
2.396
944541AF1-119 GEN
Solar/Wind Harmer
1.948
960971AF2-388 GEN
Solar/Wind Harmer
5.085
247621Y3-024
Adder
0.112
253370AE2-315 SEC1
Adder
0.926
964611AG1-324 GEN
Solar/Wind Harmer
0.545
964611AG1-324 GEN
Solar/Wind Harmer
0.242
270216AD2-079_GEN
Solar/Wind Harmer
0.279
957891AF2-083 GEN
Solar/Wind Harmer
1.538
960981AF2-389 GEN
Solar/Wind Harmer
0.689
970883AG2-550 GEN
Solar/Wind Harmer
4.556
970885AG2-551 GEN
Solar/Wind Harmer
1.06
961051AF2-396 GEN
Solar/Wind Harmer
7.223
961051AF2-396 GEN
Solar/Wind Harmer
3.36
270526AF1-158 GEN
Solar/Wind Harmer
2.055
24441505OLIV SLR
Solar/Wind Harmer
0.06
970321AG2-212 GEN
Solar/Wind Harmer
8.04
270599AE1-208 GEN
Solar/Wind Harmer
3.669
270031AE2-169
Solar/Wind Harmer
3.669
965681AG1-436 GEN
Solar/Wind Harmer
5.609
965791AG1-447 GEN
Solar/Wind Harmer
2.87
970825AG2-519 GEN
Solar/Wind Harmer
4.659
960441AF2-335 GEN
Solar/Wind Harmer
4.412
274770LINCOLN ;1U
Adder
3.688
274771LINCOLN ;2U
Adder
3.688
274808UNIV PK N;4U
Adder
2.17
274803UNIV PARK;6U
Adder
2.527
972259AH1-714 GEN
Adder
8.245
274674JOLIET 9 ;6U
Adder
6.622
LAGNLTFEXP_LAGN->PJM
CLTF
5.114
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.347
TVALTFEXP_TVA->PJM
CLTF
2.373
CPLELTFEXP_CPLE->PJM
CLTF
0.349
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.818
NYPJM->LTFIMP_NY
CLTF
1.304
LGEELTFEXP_LGEE->PJM
CLTF
2.294
WECLTFEXP_WEC->PJM
CLTF
1.589
AG2-052LTFEXP_AG2-052->PJM
LTF
0.1
AH1-155LTFEXP_AH1-155->PJM
LTF
0.15
CBM West 1LTFEXP_CBM-W1->PJM
CBM
56.361
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.564
MECLTFEXP_MEC->PJM
CLTF
6.323
SIGELTFEXP_SIGE->PJM
CLTF
0.181

Details for 05HYATT-05VASSEL 345.0 kV Ckt 1 line l/o AEP_P2-2_#7222_05MALIS 765_1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05HYATT-05VASSEL 345.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#7222_05MALIS 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:112.44 %
Rating:1409.0 MVA
Rating Type:B
MVA to Mitigate:1584.27
MW Contribution:6.29
Bus #Bus NameTypeMW Contribution
270036AE2-216 BAT
50/50
5.929
270284AF1-227 GEN1
Solar/Wind Harmer
6.804
270286AF1-227 GEN2
Solar/Wind Harmer
2.517
270287AF1-227 GEN3
Solar/Wind Harmer
2.517
270578AF1-285 GEN2
Solar/Wind Harmer
0.462
241973AD2-163_GEN1
Solar/Wind Harmer
1.939
270302AB2-170 GEN
Solar/Wind Harmer
7.765
270317AD1-130_GEN
Solar/Wind Harmer
2.977
270520AE2-214 GEN
Solar/Wind Harmer
5.355
970179AG2-119 GEN
Solar/Wind Harmer
6.746
962771AG1-126 GEN
Solar/Wind Harmer
20.775
957201AF2-014 GEN
Solar/Wind Harmer
2.711
270435AC2-044 GEN
Solar/Wind Harmer
1.195
270466AD2-091
50/50
5.39
270471AD2-092_GEN
Solar/Wind Harmer
4.846
938701AE1-092 GEN
Solar/Wind Harmer
21.808
964601AG1-323 GEN
Solar/Wind Harmer
3.173
964601AG1-323 GEN
Solar/Wind Harmer
1.476
270224U2-072_GEN2
Solar/Wind Harmer
1.963
270227U2-072_GEN3
Solar/Wind Harmer
1.963
270228U2-072_GEN4
Solar/Wind Harmer
1.963
270231U2-072_GEN5
Solar/Wind Harmer
1.963
946101AF1-275 GEN
Solar/Wind Harmer
1.336
241960AC2-195 GEN
Solar/Wind Harmer
2.345
971201AH1-060 GEN
Solar/Wind Harmer
1.523
970077AG2-063 GEN
Solar/Wind Harmer
3.797
253378AE2-206_GEN
Solar/Wind Harmer
2.379
276820AF1-078_GEN
Solar/Wind Harmer
1.057
25326509SID D
Adder
0.827
246938BC-WTG3
Solar/Wind Harmer
2.379
246937BC-WTG2
Solar/Wind Harmer
2.339
270007AE1-245 C
Solar/Wind Harmer
3.321
942801AE2-298 GEN
Solar/Wind Harmer
0.846
970611AG2-400 GEN
Solar/Wind Harmer
5.279
270518AE2-148 GEN
Solar/Wind Harmer
6.245
942861AE2-305 GEN
Solar/Wind Harmer
3.849
25326109MON D
Adder
0.648
25322209TAIT E
Adder
4.647
25322209TAIT E
Adder
4.543
942221AE2-234 GEN
Solar/Wind Harmer
0.348
247620Y3-023
Adder
0.214
270201AC2-176 GEN
Solar/Wind Harmer
2.386
944541AF1-119 GEN
Solar/Wind Harmer
1.941
960971AF2-388 GEN
Solar/Wind Harmer
5.064
247621Y3-024
Adder
0.111
253370AE2-315 SEC1
Adder
0.923
964611AG1-324 GEN
Solar/Wind Harmer
0.542
964611AG1-324 GEN
Solar/Wind Harmer
0.241
270216AD2-079_GEN
Solar/Wind Harmer
0.278
960981AF2-389 GEN
Solar/Wind Harmer
0.686
957891AF2-083 GEN
Solar/Wind Harmer
1.532
970883AG2-550 GEN
Solar/Wind Harmer
4.537
970885AG2-551 GEN
Solar/Wind Harmer
1.055
961051AF2-396 GEN
Solar/Wind Harmer
7.194
961051AF2-396 GEN
Solar/Wind Harmer
3.346
270526AF1-158 GEN
Solar/Wind Harmer
2.047
24441505OLIV SLR
Solar/Wind Harmer
0.06
970321AG2-212 GEN
Solar/Wind Harmer
8.007
270599AE1-208 GEN
Solar/Wind Harmer
3.654
270031AE2-169
Solar/Wind Harmer
3.654
965681AG1-436 GEN
Solar/Wind Harmer
5.586
965791AG1-447 GEN
Solar/Wind Harmer
2.858
970825AG2-519 GEN
Solar/Wind Harmer
4.641
960441AF2-335 GEN
Solar/Wind Harmer
4.395
274770LINCOLN ;1U
Adder
3.673
274771LINCOLN ;2U
Adder
3.673
274808UNIV PK N;4U
Adder
2.161
274803UNIV PARK;6U
Adder
2.517
972259AH1-714 GEN
Adder
8.212
241972AD1-140 GEN
Solar/Wind Harmer
2.551
247607V1-011 GEN
Solar/Wind Harmer
2.214
965051AG1-369 GEN
Solar/Wind Harmer
2.75
270297AD1-101 GEN
Solar/Wind Harmer
1.533
965041AG1-368 GEN
Solar/Wind Harmer
5.342
945631AF1-228 GEN
Solar/Wind Harmer
2.501
270156DARBY CT1
Adder
4.664
270157DARBY CT2
Adder
4.653
270158DARBY CT3
Adder
4.578
963791AG1-232 GEN
Solar/Wind Harmer
6.751
943861AF1-054 GEN
Solar/Wind Harmer
1.9
943851AF1-053 GEN
Solar/Wind Harmer
0.918
270071AF1-092 GEN
Solar/Wind Harmer
7.187
270024AE2-089 GEN
Solar/Wind Harmer
2.242
24729505KEY G4
Adder
3.072
253349AC2-067 GEN
Solar/Wind Harmer
2.334
253400AC2-068 GEN
Solar/Wind Harmer
0.939
961761AG1-017 GEN
Solar/Wind Harmer
0.199
958711AF2-162 GEN
Solar/Wind Harmer
0.469
25306009OHH W.
Adder
1.331
253372AE2-315 SEC3
Adder
0.873
253372AE2-315 SEC3
Adder
0.873
965101AG1-375 GEN
Solar/Wind Harmer
4.6
971347AH1-153 GEN
Solar/Wind Harmer
6.892
971771AH1-392 GEN
Solar/Wind Harmer
4.09
270543AE2-219 C
Solar/Wind Harmer
2.323
945581AF1-223 GEN
Solar/Wind Harmer
2.057
944161AF1-084 GEN
Solar/Wind Harmer
0.996
971769AH1-391 GEN
Solar/Wind Harmer
4.495
971029AG2-637 GEN
Solar/Wind Harmer
6.737
971673AH1-337 GEN
Solar/Wind Harmer
2.06
960681AF2-359 GEN
Solar/Wind Harmer
1.688
970115AG2-085 GEN
Solar/Wind Harmer
1.758
253383AE2-342_GEN
Solar/Wind Harmer
0.388
274775LINCOLN ;6U
Adder
3.673
274776LINCOLN ;7U
Adder
3.673
274777LINCOLN ;8U
Adder
3.673
274814UNIV PK N;0U
Adder
2.19
274807UNIV PK N;3U
Adder
2.185
274805UNIV PK N;1U
Adder
2.176
274811UNIV PK N;7U
Adder
2.171
972037AH1-567 GEN1
Adder
0.079
274827FISK ;RP
Adder
3.347
972227AH1-698 GEN1
Adder
1.124
270054AF2-122 C O1
Solar/Wind Helper
0.806
971549AH1-272 GEN
Solar/Wind Harmer
6.289
270349AD2-093_GEN
Solar/Wind Harmer
4.846
971995AH1-542 GEN
Solar/Wind Harmer
11.714
270223U2-072_GEN1
Solar/Wind Harmer
1.963
270578AF1-285 GEN2
Solar/Wind Harmer
1.2
270391AF1-285 GEN3
Solar/Wind Harmer
1.2
270462AD2-086
Solar/Wind Harmer
6.46
241813AF1-122_GEN
Solar/Wind Harmer
4.874
970593AG2-378 GEN
Solar/Wind Harmer
1.406
962761AG1-125 GEN
Solar/Wind Harmer
20.775
970149AG2-104 GEN
Solar/Wind Harmer
25.657
970155AG2-107 GEN
Solar/Wind Harmer
9.059
246936BC-WTG1
Solar/Wind Harmer
2.339
270489AE1-102 GEN1
Solar/Wind Harmer
0.777
965421AG1-410 GEN
Solar/Wind Harmer
17.731
247521TR3_G114
Solar/Wind Harmer
1.852
270246TR4_N_V150
Solar/Wind Harmer
0.468
24695305TIMB G C
Solar/Wind Harmer
2.998
965011AG1-365 GEN
Solar/Wind Harmer
5.279
270159DARBY CT4
Adder
4.59
944231AF1-091 GEN
Solar/Wind Harmer
1.832
253343AC1-166 GEN
Solar/Wind Harmer
0.523
253325AC1-069 GEN
Solar/Wind Harmer
0.505
960071AF2-298 GEN
Solar/Wind Harmer
2.387
25326309TAIT D
Adder
0.523
270063AE2-323 C
Solar/Wind Harmer
1.051
965651AG1-433 GEN
Solar/Wind Harmer
2.532
24639705ELKHART HY
Adder
0.071
253370AE2-315 SEC1
Adder
0.923
253371AE2-315 SEC2
Adder
0.873
958861AF2-177 GEN
Solar/Wind Harmer
5.028
247536S-71 GEN
Solar/Wind Harmer
1.856
945111AF1-176 GEN
Solar/Wind Harmer
8.121
270505AE1-170 C O1
Solar/Wind Harmer
6.807
945371AF1-202 GEN
Solar/Wind Harmer
3.165
270449AD2-020 GEN
Solar/Wind Harmer
1.267
943021AE2-325 GEN
Solar/Wind Harmer
1.646
970245AG2-165 GEN
Solar/Wind Harmer
8.007
970825AG2-519 GEN
Solar/Wind Harmer
1.035
270005AE1-210 C O1
Solar/Wind Harmer
2.397
965031AG1-367 GEN
Solar/Wind Harmer
4.385
970373AG2-245 GEN
Solar/Wind Harmer
9.206
274751CRETE EC ;1U
Adder
3.589
274754CRETE EC ;4U
Adder
3.589
274773LINCOLN ;4U
Adder
3.673
274774LINCOLN ;5U
Adder
3.673
274723RIVER EC ;12
Adder
7.798
274812UNIV PK N;8U
Adder
2.171
274801UNIV PARK;4U
Adder
2.514
270475AD2-096_GEN
50/50
7.755
942871AE2-306 GEN
Solar/Wind Harmer
0.9
270391AF1-285 GEN3
Solar/Wind Harmer
0.462
241974AD2-163_GEN2
Solar/Wind Harmer
1.939
270485AE1-090_GEN
Solar/Wind Harmer
0.562
942051AE2-217 GEN
Solar/Wind Harmer
13.864
970065AG2-057 GEN
Solar/Wind Harmer
0.762
970605AG2-385 GEN
Solar/Wind Harmer
3.797
241955AC1-078 GEN
Solar/Wind Harmer
4.97
970153AG2-106 GEN
Solar/Wind Harmer
9.059
270491AE1-102 GEN2
Solar/Wind Harmer
0.777
958091AF2-103 GEN
Solar/Wind Harmer
0.09
270191TR4_S_V150
Solar/Wind Harmer
1.652
270247TR4_N_V136
Solar/Wind Harmer
0.468
270258AD1-119 GEN
Solar/Wind Harmer
1.487
959331AF2-224 GEN
Solar/Wind Harmer
5.279
965021AG1-366 GEN
Solar/Wind Harmer
1.228
270044AE2-322 C
Solar/Wind Harmer
0.687
270404AC1-167 GEN
Solar/Wind Harmer
0.572
270588AE1-091_GEN
Solar/Wind Harmer
5.47
270043AE2-236 GEN
Solar/Wind Harmer
2.696
253338AC1-165 GEN
Solar/Wind Harmer
0.523
253333AC1-068 GEN
Solar/Wind Harmer
0.505
970031AG2-029 GEN
Solar/Wind Harmer
14.416
971617AH1-308 GEN
Solar/Wind Harmer
2.777
944531AF1-118 GEN
Solar/Wind Harmer
16.706
270541AE2-072 C
Solar/Wind Harmer
2.148
962031AG1-047 GEN
Solar/Wind Harmer
1.403
957741AF2-068 GEN
Solar/Wind Harmer
6.963
253303V4-073 C
Solar/Wind Harmer
0.053
253370AE2-315 SEC1
Adder
0.923
253371AE2-315 SEC2
Adder
0.873
970349AG2-230 GEN
Solar/Wind Harmer
6.892
247643Z2-116 C
Solar/Wind Harmer
0.032
945111AF1-176 GEN
Solar/Wind Harmer
2.574
24642205MAYFLWER
Adder
0.288
970513AG2-328 GEN
Solar/Wind Harmer
8.007
970517AG2-330 GEN
Solar/Wind Harmer
7.263
24441205WTRV SLR C
Solar/Wind Harmer
0.06
247604X1-042
Adder
0.185
946031AF1-268 GEN
Solar/Wind Harmer
3.69
958821AF2-173 GEN
Solar/Wind Harmer
6.139
270004AE1-209 GEN
Solar/Wind Harmer
2.397
274752CRETE EC ;2U
Adder
3.589
274753CRETE EC ;3U
Adder
3.589
274772LINCOLN ;3U
Adder
3.673
274724RIVER EC ;11
Adder
7.706
274802UNIV PARK;5U
Adder
2.517
274826FISK ;BP
Adder
4.723
274800UNIV PARK;3U
Adder
2.514
972038AH1-567 GEN2
Adder
0.157
972228AH1-698 GEN2
Adder
1.596
LAGNLTFEXP_LAGN->PJM
CLTF
5.094
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.339
TVALTFEXP_TVA->PJM
CLTF
2.364
CPLELTFEXP_CPLE->PJM
CLTF
0.348
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.662
NYPJM->LTFIMP_NY
CLTF
1.299
LGEELTFEXP_LGEE->PJM
CLTF
2.285
WECLTFEXP_WEC->PJM
CLTF
1.583
AG2-052LTFEXP_AG2-052->PJM
LTF
0.1
AH1-155LTFEXP_AH1-155->PJM
LTF
0.15
CBM West 1LTFEXP_CBM-W1->PJM
CBM
56.137
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.529
MECLTFEXP_MEC->PJM
CLTF
6.298
SIGELTFEXP_SIGE->PJM
CLTF
0.181

Details for 05HYATT-05VASSEL 345.0 kV Ckt 1 line l/o AEP_P4_#7222_05MALIS 765_D_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05HYATT-05VASSEL 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7222_05MALIS 765_D_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.42 %
Rating:1409.0 MVA
Rating Type:B
MVA to Mitigate:1584.05
MW Contribution:6.29
Bus #Bus NameTypeMW Contribution
270036AE2-216 BAT
50/50
5.929
270284AF1-227 GEN1
Solar/Wind Harmer
6.804
270286AF1-227 GEN2
Solar/Wind Harmer
2.517
270287AF1-227 GEN3
Solar/Wind Harmer
2.517
270578AF1-285 GEN2
Solar/Wind Harmer
0.462
241973AD2-163_GEN1
Solar/Wind Harmer
1.939
270302AB2-170 GEN
Solar/Wind Harmer
7.765
270317AD1-130_GEN
Solar/Wind Harmer
2.977
270520AE2-214 GEN
Solar/Wind Harmer
5.355
970179AG2-119 GEN
Solar/Wind Harmer
6.746
962771AG1-126 GEN
Solar/Wind Harmer
20.775
957201AF2-014 GEN
Solar/Wind Harmer
2.711
270435AC2-044 GEN
Solar/Wind Harmer
1.195
241972AD1-140 GEN
Solar/Wind Harmer
2.551
247607V1-011 GEN
Solar/Wind Harmer
2.214
965051AG1-369 GEN
Solar/Wind Harmer
2.75
270297AD1-101 GEN
Solar/Wind Harmer
1.533
965041AG1-368 GEN
Solar/Wind Harmer
5.342
945631AF1-228 GEN
Solar/Wind Harmer
2.501
270156DARBY CT1
Adder
4.664
270157DARBY CT2
Adder
4.653
270158DARBY CT3
Adder
4.578
963791AG1-232 GEN
Solar/Wind Harmer
6.751
943861AF1-054 GEN
Solar/Wind Harmer
1.9
943851AF1-053 GEN
Solar/Wind Harmer
0.918
270071AF1-092 GEN
Solar/Wind Harmer
7.187
270024AE2-089 GEN
Solar/Wind Harmer
2.242
24729505KEY G4
Adder
3.072
253349AC2-067 GEN
Solar/Wind Harmer
2.334
253400AC2-068 GEN
Solar/Wind Harmer
0.939
961761AG1-017 GEN
Solar/Wind Harmer
0.199
958711AF2-162 GEN
Solar/Wind Harmer
0.469
25306009OHH W.
Adder
1.331
253372AE2-315 SEC3
Adder
0.873
253372AE2-315 SEC3
Adder
0.873
965101AG1-375 GEN
Solar/Wind Harmer
4.6
971347AH1-153 GEN
Solar/Wind Harmer
6.892
971771AH1-392 GEN
Solar/Wind Harmer
4.09
270543AE2-219 C
Solar/Wind Harmer
2.323
945581AF1-223 GEN
Solar/Wind Harmer
2.057
944161AF1-084 GEN
Solar/Wind Harmer
0.996
971769AH1-391 GEN
Solar/Wind Harmer
4.495
971029AG2-637 GEN
Solar/Wind Harmer
6.737
971673AH1-337 GEN
Solar/Wind Harmer
2.06
960681AF2-359 GEN
Solar/Wind Harmer
1.688
970115AG2-085 GEN
Solar/Wind Harmer
1.758
253383AE2-342_GEN
Solar/Wind Harmer
0.388
274775LINCOLN ;6U
Adder
3.673
274776LINCOLN ;7U
Adder
3.673
274777LINCOLN ;8U
Adder
3.673
274814UNIV PK N;0U
Adder
2.19
274807UNIV PK N;3U
Adder
2.185
274805UNIV PK N;1U
Adder
2.176
274811UNIV PK N;7U
Adder
2.171
972037AH1-567 GEN1
Adder
0.079
274827FISK ;RP
Adder
3.347
972227AH1-698 GEN1
Adder
1.124
270054AF2-122 C O1
Solar/Wind Helper
0.806
971549AH1-272 GEN
Solar/Wind Harmer
6.289
270475AD2-096_GEN
50/50
7.755
942871AE2-306 GEN
Solar/Wind Harmer
0.9
270391AF1-285 GEN3
Solar/Wind Harmer
0.462
241974AD2-163_GEN2
Solar/Wind Harmer
1.939
270485AE1-090_GEN
Solar/Wind Harmer
0.562
942051AE2-217 GEN
Solar/Wind Harmer
13.864
970065AG2-057 GEN
Solar/Wind Harmer
0.762
970605AG2-385 GEN
Solar/Wind Harmer
3.797
241955AC1-078 GEN
Solar/Wind Harmer
4.97
970153AG2-106 GEN
Solar/Wind Harmer
9.059
270491AE1-102 GEN2
Solar/Wind Harmer
0.777
958091AF2-103 GEN
Solar/Wind Harmer
0.09
270191TR4_S_V150
Solar/Wind Harmer
1.652
270247TR4_N_V136
Solar/Wind Harmer
0.468
270258AD1-119 GEN
Solar/Wind Harmer
1.487
959331AF2-224 GEN
Solar/Wind Harmer
5.279
965021AG1-366 GEN
Solar/Wind Harmer
1.228
270044AE2-322 C
Solar/Wind Harmer
0.687
270349AD2-093_GEN
Solar/Wind Harmer
4.846
971995AH1-542 GEN
Solar/Wind Harmer
11.714
270223U2-072_GEN1
Solar/Wind Harmer
1.963
270578AF1-285 GEN2
Solar/Wind Harmer
1.2
270391AF1-285 GEN3
Solar/Wind Harmer
1.2
270462AD2-086
Solar/Wind Harmer
6.46
241813AF1-122_GEN
Solar/Wind Harmer
4.874
970593AG2-378 GEN
Solar/Wind Harmer
1.406
962761AG1-125 GEN
Solar/Wind Harmer
20.775
970149AG2-104 GEN
Solar/Wind Harmer
25.657
970155AG2-107 GEN
Solar/Wind Harmer
9.059
246936BC-WTG1
Solar/Wind Harmer
2.339
270489AE1-102 GEN1
Solar/Wind Harmer
0.777
965421AG1-410 GEN
Solar/Wind Harmer
17.731
247521TR3_G114
Solar/Wind Harmer
1.852
270246TR4_N_V150
Solar/Wind Harmer
0.468
24695305TIMB G C
Solar/Wind Harmer
2.998
965011AG1-365 GEN
Solar/Wind Harmer
5.279
270159DARBY CT4
Adder
4.59
944231AF1-091 GEN
Solar/Wind Harmer
1.832
253343AC1-166 GEN
Solar/Wind Harmer
0.523
253325AC1-069 GEN
Solar/Wind Harmer
0.505
960071AF2-298 GEN
Solar/Wind Harmer
2.387
25326309TAIT D
Adder
0.523
270063AE2-323 C
Solar/Wind Harmer
1.051
965651AG1-433 GEN
Solar/Wind Harmer
2.532
24639705ELKHART HY
Adder
0.071
253370AE2-315 SEC1
Adder
0.923
253371AE2-315 SEC2
Adder
0.873
958861AF2-177 GEN
Solar/Wind Harmer
5.028
247536S-71 GEN
Solar/Wind Harmer
1.856
945111AF1-176 GEN
Solar/Wind Harmer
8.121
270505AE1-170 C O1
Solar/Wind Harmer
6.807
945371AF1-202 GEN
Solar/Wind Harmer
3.165
270449AD2-020 GEN
Solar/Wind Harmer
1.267
943021AE2-325 GEN
Solar/Wind Harmer
1.646
970245AG2-165 GEN
Solar/Wind Harmer
8.007
970825AG2-519 GEN
Solar/Wind Harmer
1.035
270005AE1-210 C O1
Solar/Wind Harmer
2.397
270404AC1-167 GEN
Solar/Wind Harmer
0.572
270588AE1-091_GEN
Solar/Wind Harmer
5.47
270043AE2-236 GEN
Solar/Wind Harmer
2.696
253338AC1-165 GEN
Solar/Wind Harmer
0.523
253333AC1-068 GEN
Solar/Wind Harmer
0.505
970031AG2-029 GEN
Solar/Wind Harmer
14.416
971617AH1-308 GEN
Solar/Wind Harmer
2.777
944531AF1-118 GEN
Solar/Wind Harmer
16.706
270541AE2-072 C
Solar/Wind Harmer
2.148
962031AG1-047 GEN
Solar/Wind Harmer
1.403
957741AF2-068 GEN
Solar/Wind Harmer
6.963
253303V4-073 C
Solar/Wind Harmer
0.053
253370AE2-315 SEC1
Adder
0.923
253371AE2-315 SEC2
Adder
0.873
970349AG2-230 GEN
Solar/Wind Harmer
6.892
247643Z2-116 C
Solar/Wind Harmer
0.032
945111AF1-176 GEN
Solar/Wind Harmer
2.574
24642205MAYFLWER
Adder
0.288
970513AG2-328 GEN
Solar/Wind Harmer
8.007
970517AG2-330 GEN
Solar/Wind Harmer
7.263
24441205WTRV SLR C
Solar/Wind Harmer
0.06
247604X1-042
Adder
0.185
946031AF1-268 GEN
Solar/Wind Harmer
3.69
958821AF2-173 GEN
Solar/Wind Harmer
6.139
270004AE1-209 GEN
Solar/Wind Harmer
2.397
274752CRETE EC ;2U
Adder
3.589
274753CRETE EC ;3U
Adder
3.589
274772LINCOLN ;3U
Adder
3.673
274724RIVER EC ;11
Adder
7.706
274802UNIV PARK;5U
Adder
2.517
274826FISK ;BP
Adder
4.723
274800UNIV PARK;3U
Adder
2.514
972038AH1-567 GEN2
Adder
0.157
972228AH1-698 GEN2
Adder
1.596
965031AG1-367 GEN
Solar/Wind Harmer
4.385
970373AG2-245 GEN
Solar/Wind Harmer
9.206
274751CRETE EC ;1U
Adder
3.589
274754CRETE EC ;4U
Adder
3.589
274773LINCOLN ;4U
Adder
3.673
274774LINCOLN ;5U
Adder
3.673
274723RIVER EC ;12
Adder
7.798
274812UNIV PK N;8U
Adder
2.171
274801UNIV PARK;4U
Adder
2.514
270466AD2-091
50/50
5.39
270471AD2-092_GEN
Solar/Wind Harmer
4.846
938701AE1-092 GEN
Solar/Wind Harmer
21.808
964601AG1-323 GEN
Solar/Wind Harmer
3.173
964601AG1-323 GEN
Solar/Wind Harmer
1.476
270224U2-072_GEN2
Solar/Wind Harmer
1.963
270227U2-072_GEN3
Solar/Wind Harmer
1.963
270228U2-072_GEN4
Solar/Wind Harmer
1.963
270231U2-072_GEN5
Solar/Wind Harmer
1.963
946101AF1-275 GEN
Solar/Wind Harmer
1.336
241960AC2-195 GEN
Solar/Wind Harmer
2.345
971201AH1-060 GEN
Solar/Wind Harmer
1.523
970077AG2-063 GEN
Solar/Wind Harmer
3.797
253378AE2-206_GEN
Solar/Wind Harmer
2.379
276820AF1-078_GEN
Solar/Wind Harmer
1.057
25326509SID D
Adder
0.827
246938BC-WTG3
Solar/Wind Harmer
2.379
246937BC-WTG2
Solar/Wind Harmer
2.339
270007AE1-245 C
Solar/Wind Harmer
3.321
942801AE2-298 GEN
Solar/Wind Harmer
0.846
970611AG2-400 GEN
Solar/Wind Harmer
5.279
270518AE2-148 GEN
Solar/Wind Harmer
6.245
942861AE2-305 GEN
Solar/Wind Harmer
3.849
25326109MON D
Adder
0.648
25322209TAIT E
Adder
4.647
25322209TAIT E
Adder
4.543
942221AE2-234 GEN
Solar/Wind Harmer
0.348
247620Y3-023
Adder
0.214
270201AC2-176 GEN
Solar/Wind Harmer
2.386
944541AF1-119 GEN
Solar/Wind Harmer
1.941
960971AF2-388 GEN
Solar/Wind Harmer
5.064
247621Y3-024
Adder
0.111
253370AE2-315 SEC1
Adder
0.923
964611AG1-324 GEN
Solar/Wind Harmer
0.542
964611AG1-324 GEN
Solar/Wind Harmer
0.241
270216AD2-079_GEN
Solar/Wind Harmer
0.278
960981AF2-389 GEN
Solar/Wind Harmer
0.686
957891AF2-083 GEN
Solar/Wind Harmer
1.532
970883AG2-550 GEN
Solar/Wind Harmer
4.537
970885AG2-551 GEN
Solar/Wind Harmer
1.055
961051AF2-396 GEN
Solar/Wind Harmer
7.194
961051AF2-396 GEN
Solar/Wind Harmer
3.346
270526AF1-158 GEN
Solar/Wind Harmer
2.047
24441505OLIV SLR
Solar/Wind Harmer
0.06
970321AG2-212 GEN
Solar/Wind Harmer
8.007
270599AE1-208 GEN
Solar/Wind Harmer
3.654
270031AE2-169
Solar/Wind Harmer
3.654
965681AG1-436 GEN
Solar/Wind Harmer
5.586
965791AG1-447 GEN
Solar/Wind Harmer
2.858
970825AG2-519 GEN
Solar/Wind Harmer
4.641
960441AF2-335 GEN
Solar/Wind Harmer
4.395
274770LINCOLN ;1U
Adder
3.673
274771LINCOLN ;2U
Adder
3.673
274808UNIV PK N;4U
Adder
2.161
274803UNIV PARK;6U
Adder
2.517
972259AH1-714 GEN
Adder
8.212
LAGNLTFEXP_LAGN->PJM
CLTF
5.094
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.339
TVALTFEXP_TVA->PJM
CLTF
2.364
CPLELTFEXP_CPLE->PJM
CLTF
0.348
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.662
NYPJM->LTFIMP_NY
CLTF
1.299
LGEELTFEXP_LGEE->PJM
CLTF
2.285
WECLTFEXP_WEC->PJM
CLTF
1.583
AG2-052LTFEXP_AG2-052->PJM
LTF
0.1
AH1-155LTFEXP_AH1-155->PJM
LTF
0.15
CBM West 1LTFEXP_CBM-W1->PJM
CBM
56.137
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.529
MECLTFEXP_MEC->PJM
CLTF
6.298
SIGELTFEXP_SIGE->PJM
CLTF
0.181

Details for 05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P1-2_#709_546_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer
Contingency Name:
AEP_P1-2_#709_546_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.09 %
Rating:3039.0 MVA
Rating Type:B
MVA to Mitigate:3588.67
MW Contribution:10.16
Bus #Bus NameTypeMW Contribution
24344305RKG2
50/50
10.991
270406AB1-088 CT1
50/50
2.508
970243AG2-164 GEN
Solar/Wind Harmer
12.117
970519AG2-331 GEN
Solar/Wind Harmer
53.854
970699AG2-449 GEN
Solar/Wind Harmer
5.178
970513AG2-328 GEN
Solar/Wind Harmer
3.606
970517AG2-330 GEN
Solar/Wind Harmer
21.635
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
8.058
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
964401AG1-302 GEN
Solar/Wind Harmer
0.001
270535AF1-215 GEN1
Solar/Wind Harmer
0.009
970193AG2-126 GEN
Solar/Wind Harmer
9.211
970349AG2-230 GEN
Solar/Wind Harmer
9.104
274772LINCOLN ;3U
Adder
7.237
274752CRETE EC ;2U
Adder
7.047
274753CRETE EC ;3U
Adder
7.047
274724RIVER EC ;11
Adder
15.065
276897AD1-100 C
Solar/Wind Harmer
0.008
939351AE1-166 GEN
Solar/Wind Harmer
0
972228AH1-698 GEN2
Adder
3.132
276806AD2-047 C O1
Solar/Wind Harmer
3.342
970941AG2-585 GEN
Solar/Wind Harmer
7.373
274802UNIV PARK;5U
Adder
4.928
274800UNIV PARK;3U
Adder
4.918
972038AH1-567 GEN2
Adder
0.308
274826FISK ;BP
Adder
9.234
970707AG2-453 GEN
Solar/Wind Harmer
19.213
274729ELWOOD EC;1P
Adder
13.765
274730ELWOOD EC;6P
Adder
13.765
274734ELWOOD EC;8P
Adder
13.765
274736ELWOOD EC;9P
Adder
13.765
276893AG1-478 C
Solar/Wind Harmer
0.231
274676JOLIET 29;8U
Adder
24.747
943121AE2-341 GEN
Solar/Wind Harmer
9.668
943591AF1-030 GEN
Solar/Wind Harmer
6.429
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
942111AE2-223 GEN
Solar/Wind Harmer
1.868
276805AD2-038 GEN
Solar/Wind Harmer
0.002
274853TWINGROVE;U1
Solar/Wind Harmer
0.002
965091AG1-374 GEN
Solar/Wind Harmer
17.118
959611AF2-252 GEN
Solar/Wind Harmer
1.902
274682WAUKEGAN ;7U
Adder
14.638
24642205MAYFLWER
Adder
0.516
276889AE2-281 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0.206
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
2.595
276668AB2-070 GEN1
Solar/Wind Harmer
0.205
970571AG2-364 GEN
Solar/Wind Harmer
11.181
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.595
274855GSG-6 ;RU
Solar/Wind Harmer
0.204
274850MENDOTA H;RU
Solar/Wind Harmer
0.066
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.1
276621W2-048 GEN
Solar/Wind Harmer
0.28
276838X2-022 GEN2
Solar/Wind Harmer
0.313
959091AF2-200 GEN
Solar/Wind Harmer
11.069
247643Z2-116 C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
4.439
274878BISHOP HL;2U
Solar/Wind Harmer
0.183
942481AE2-261 GEN
Solar/Wind Harmer
16.292
24441205WTRV SLR C
Solar/Wind Harmer
0
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
276157O29GEN1
Solar/Wind Harmer
0.872
965931AG1-462 GEN
Solar/Wind Harmer
13.177
247642Z2-115 C
Solar/Wind Harmer
0.002
970031AG2-029 GEN
Solar/Wind Harmer
2.905
270043AE2-236 GEN
Solar/Wind Harmer
2.56
970289AG2-191 GEN
Solar/Wind Harmer
0.413
970291AG2-192 GEN
Solar/Wind Harmer
0.376
959331AF2-224 GEN
Solar/Wind Harmer
2.131
965021AG1-366 GEN
Solar/Wind Harmer
1.015
252510AF1-249 C
Solar/Wind Helper
0.376
253406AD2-031_GEN
Solar/Wind Helper
0.712
253415AE1-040 GEN
Solar/Wind Helper
0.483
339250AF1-203 GEN
Solar/Wind Helper
0.118
253338AC1-165 GEN
Solar/Wind Helper
0.467
253333AC1-068 GEN
Solar/Wind Helper
0.484
24344205RKG1
50/50
11.244
24344205RKG1
50/50
11.22
24344305RKG2
50/50
11.199
270393AB1-087 CT1
50/50
2.508
270394AB1-087 ST1
50/50
2.508
970541AG2-344 GEN
50/50
10.209
970539AG2-343 GEN
50/50
9.364
970543AG2-345 GEN
50/50
4.682
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
4.647
958391AF2-133 GEN
Solar/Wind Harmer
0.001
963841AG1-237 GEN
Solar/Wind Harmer
3.256
270536AF1-215 GEN2
Solar/Wind Harmer
0.009
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971347AH1-153 GEN
Solar/Wind Harmer
9.104
274775LINCOLN ;6U
Adder
7.237
274776LINCOLN ;7U
Adder
7.237
274777LINCOLN ;8U
Adder
7.237
971769AH1-391 GEN
Solar/Wind Harmer
6.648
274814UNIV PK N;0U
Adder
4.294
274807UNIV PK N;3U
Adder
4.285
274805UNIV PK N;1U
Adder
4.266
274811UNIV PK N;7U
Adder
4.257
972227AH1-698 GEN1
Adder
2.206
960591AF2-350 GEN
Solar/Wind Harmer
5.898
972037AH1-567 GEN1
Adder
0.155
274827FISK ;RP
Adder
6.544
274687WILL CNTY;4U
Adder
23.403
274687WILL CNTY;4U
Adder
23.403
274731ELWOOD EC;2P
Adder
13.765
274733ELWOOD EC;3P
Adder
13.765
274735ELWOOD EC;4P
Adder
13.765
274728ELWOOD EC;5P
Adder
13.765
970833AG2-524 GEN
Solar/Wind Harmer
6.424
970833AG2-524 GEN
Solar/Wind Harmer
4.282
274675JOLIET 29;7U
Adder
25.664
274675JOLIET 29;7U
Adder
24.747
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
970169AG2-114 GEN
Solar/Wind Harmer
5.784
274746AC1-111 G10
Adder
4.62
274744AC1-111 GEN8
Adder
4.62
276655WTG1_EQ
Solar/Wind Harmer
0.002
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
6.036
941731AE2-173 GEN
Solar/Wind Harmer
4.79
971771AH1-392 GEN
Solar/Wind Harmer
5.725
276868AE1-113 GEN
Solar/Wind Harmer
1.14
276882AE2-255 GEN
Solar/Wind Harmer
0.664
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.205
276848AB2-070 GEN3
Solar/Wind Harmer
0.204
926823AC1-168 GEN
Solar/Wind Harmer
0.954
971177AH1-047 GEN
Solar/Wind Harmer
3.447
971675AH1-338 GEN
Solar/Wind Harmer
2.173
971411AH1-196 GEN
Solar/Wind Harmer
8.347
971619AH1-309 GEN
Solar/Wind Harmer
2.5
971171AH1-044 GEN
Solar/Wind Harmer
11.069
274823ROCKFORD ;21
Adder
15.377
957751AF2-069 GEN
Solar/Wind Harmer
0.182
276612AE2-035 GEN
Solar/Wind Harmer
0.001
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
971681AH1-341 GEN
Solar/Wind Harmer
8.765
944221AF1-090 GEN
Solar/Wind Harmer
3.172
961011AF2-392 GEN
Solar/Wind Harmer
3.16
946321AF1-296 GEN
Solar/Wind Harmer
2.912
971549AH1-272 GEN
Solar/Wind Harmer
10.16
270071AF1-092 GEN
Solar/Wind Harmer
8.874
970289AG2-191 GEN
Solar/Wind Harmer
0.714
252524AE2-267 GEN
Solar/Wind Helper
0.465
339243AC2-075 GEN1
Solar/Wind Helper
0.336
339211AE2-254 GEN
Solar/Wind Helper
0.447
270367AC2-061_GEN
Solar/Wind Helper
1.692
270340AC2-060 GEN
Solar/Wind Helper
1.094
241972AD1-140 GEN
Solar/Wind Helper
2.07
970091AG2-072 GEN
50/50
218.455
270407AB1-088 ST1
50/50
2.508
970023AG2-014 GEN
50/50
2.686
970783AG2-492 GEN
50/50
2.686
24344105CKG2
50/50
6.851
970333AG2-219 GEN
Solar/Wind Harmer
14.81
270445AC2-157 GEN2
Solar/Wind Harmer
0.004
970245AG2-165 GEN
Solar/Wind Harmer
3.606
24791305MDL-5G
Solar/Wind Harmer
0.001
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
9.756
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.732
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0.006
963741AG1-226 GEN
Solar/Wind Harmer
17.046
970373AG2-245 GEN
Solar/Wind Harmer
14.55
274773LINCOLN ;4U
Adder
7.237
274774LINCOLN ;5U
Adder
7.237
274751CRETE EC ;1U
Adder
7.047
274754CRETE EC ;4U
Adder
7.047
274723RIVER EC ;12
Adder
15.25
274812UNIV PK N;8U
Adder
4.257
276164X3-005 C
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
0.616
274801UNIV PARK;4U
Adder
4.918
939401AE1-172 GEN
Solar/Wind Harmer
4.373
274732ELWOOD EC;7P
Adder
13.765
274674JOLIET 9 ;6U
Adder
12.881
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
25.663
274745AC1-111 GEN9
Adder
4.62
276691AA1-018 GEN1
Solar/Wind Harmer
0.697
276726Z2-087_GEN
Solar/Wind Harmer
0.002
939741AE1-205 GEN
Solar/Wind Harmer
8.048
276901AD2-066 C O1
Solar/Wind Harmer
0.006
274854TWINGROVE;U2
Solar/Wind Harmer
0.002
971997AH1-543 GEN
Solar/Wind Harmer
2.988
274682WAUKEGAN ;7U
Adder
14.638
274828WAUKEGAN ;BP
Adder
8.984
972175AH1-670 GEN
Solar/Wind Harmer
4.678
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
962781AG1-127 GEN
Solar/Wind Harmer
5.364
274872LEEDK;1U
Solar/Wind Harmer
0.003
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
2.181
970569AG2-363 GEN
Solar/Wind Harmer
16.771
276861AD2-134 GEN
Solar/Wind Harmer
0.1
270505AE1-170 C O1
Solar/Wind Harmer
5.832
276615X2-022 GEN
Solar/Wind Harmer
0.058
957471AF2-041 GEN
Solar/Wind Harmer
16.603
959081AF2-199 GEN
Solar/Wind Harmer
5.534
971067AG2-660 GEN
Solar/Wind Harmer
1.845
274822ROCKFORD ;11
Adder
1.007
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.872
945111AF1-176 GEN
Solar/Wind Harmer
9.771
970819AG2-516 GEN
Solar/Wind Harmer
6.568
274877BISHOP HL;1U
Solar/Wind Harmer
0.183
971475AH1-234 GEN
Solar/Wind Harmer
2.645
965911AG1-460 GEN
Solar/Wind Harmer
1.09
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
276158O29GEN2
Solar/Wind Harmer
0.001
270063AE2-323 C
Solar/Wind Harmer
0.004
970291AG2-192 GEN
Solar/Wind Harmer
0.488
965011AG1-365 GEN
Solar/Wind Harmer
3.044
944231AF1-091 GEN
Solar/Wind Harmer
0.807
252507AC2-088 GEN
Solar/Wind Helper
1.471
339216AC1-074 GEN
Solar/Wind Helper
1.461
943111AE2-339 GEN
Solar/Wind Helper
0.643
339241AF1-083 GEN
Solar/Wind Helper
0.405
253343AC1-166 GEN
Solar/Wind Helper
0.467
253325AC1-069 GEN
Solar/Wind Helper
0.484
942601AE2-276 GEN
50/50
8.344
270102X2-052 ST
50/50
1.424
270100X2-052 CT1
50/50
1.312
270101X2-052 CT2
50/50
1.312
970239AG2-162 GEN
Solar/Wind Harmer
5.178
270444AC2-157 GEN1
Solar/Wind Harmer
0.004
971587AH1-292 GEN
Solar/Wind Harmer
7.343
970321AG2-212 GEN
Solar/Wind Harmer
3.606
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
966841AG1-555 GEN
Solar/Wind Harmer
0.888
970241AG2-163 GEN
Solar/Wind Harmer
4.202
965681AG1-436 GEN
Solar/Wind Harmer
7.741
965791AG1-447 GEN
Solar/Wind Harmer
5.677
945391AF1-204 GEN
Solar/Wind Harmer
6.524
274770LINCOLN ;1U
Adder
7.237
274771LINCOLN ;2U
Adder
7.237
24441505OLIV SLR
Solar/Wind Harmer
0
274808UNIV PK N;4U
Adder
4.239
270526AF1-158 GEN
Solar/Wind Harmer
0.007
274888KELLY CRK;1U
Solar/Wind Harmer
0.346
274887GEN-1.85
Solar/Wind Harmer
0.155
276843GEN-1.7
Solar/Wind Harmer
0.191
958011AF2-095 GEN
Solar/Wind Harmer
8.493
274803UNIV PARK;6U
Adder
4.928
972259AH1-714 GEN
Adder
16.092
274674JOLIET 9 ;6U
Adder
12.881
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
958481AF2-142 GEN
Solar/Wind Harmer
8.633
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.778
971573AH1-285 GEN
Solar/Wind Harmer
1.068
958491AF2-143 GEN
Solar/Wind Harmer
8.559
960611AF2-352 GEN
Solar/Wind Harmer
1.902
274695ROCKY RD ;2P
Adder
9.087
274693ROCKY RD ;1P
Adder
8.997
274697ROCKY RD ;3P
Adder
2.468
274696ROCKY RD ;4P
Adder
9.301
274879MINONK ;1U
Solar/Wind Harmer
0.24
274683WAUKEGAN ;8U
Adder
17.139
274683WAUKEGAN ;8U
Adder
14.447
962691AG1-118 GEN
Solar/Wind Harmer
16.954
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
970921AG2-575 GEN
Solar/Wind Harmer
5.636
970921AG2-575 GEN
Solar/Wind Harmer
1.879
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
942991AE2-321 GEN
Solar/Wind Harmer
6.244
971333AH1-146 GEN
Solar/Wind Harmer
11.124
971335AH1-147 GEN
Solar/Wind Harmer
11.124
957891AF2-083 GEN
Solar/Wind Harmer
0.001
971341AH1-150 GEN
Solar/Wind Harmer
11.069
971343AH1-151 GEN
Solar/Wind Harmer
11.069
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.216
276646AC1-214 GEN2
Solar/Wind Harmer
0.216
961051AF2-396 GEN
Solar/Wind Harmer
10.985
961051AF2-396 GEN
Solar/Wind Harmer
7.324
270216AD2-079_GEN
Solar/Wind Harmer
0.001
274856ECOGROVE ;U1
Solar/Wind Harmer
0.129
276611AD2-172 GEN
Solar/Wind Harmer
0.001
276782AC1-033 GEN
Solar/Wind Harmer
0.001
276916AD2-100_GEN
Solar/Wind Harmer
11.423
276911AD2-131_GEN
Solar/Wind Harmer
0.752
938861AE1-114 GEN
Solar/Wind Harmer
3.082
276603SUBLETTE C
Solar/Wind Harmer
0
276741O09 GEN1
Solar/Wind Harmer
0.192
276708O09 GEN2
Solar/Wind Harmer
0.192
970611AG2-400 GEN
Solar/Wind Harmer
3.044
970627AG2-408 GEN
Solar/Wind Harmer
0.913
252509AD1-136 GEN
Solar/Wind Helper
0.21
339221AD2-048_GEN
Solar/Wind Helper
1.206
25183208HLCRTG
Solar/Wind Helper
2.027
270186AC1-089 GEN
Solar/Wind Helper
0.821
253394AE2-221_GEN
Solar/Wind Helper
1.236
253398AE2-221_GEN2
Solar/Wind Helper
1.236
962581AG1-107 GEN
Solar/Wind Helper
0.907
961491AF2-440 GEN
Solar/Wind Helper
0.037
339236AF1-050_GEN
Solar/Wind Helper
0.406
339231AF1-038_GEN
Solar/Wind Helper
0.396
339255AE2-071 GEN
Solar/Wind Helper
0.206
270518AE2-148 GEN
Solar/Wind Helper
5.626
944201AF1-088_MTX
50/50
166.885
957141AF2-008_MTX
50/50
83.443
991312J1772
External Queue
12.355378150939941
991112J1481
External Queue
17.5482177734375
950011AG9-010
External Queue
6.204055309295654
991082J1475 G
External Queue
6.161812782287598
955142J992
External Queue
11.408185005187988
990742J1381
External Queue
17.5482177734375
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
9.981
BlueGrassPJM->LTFIMP_BlueG
CLTF
28.615
LAGNLTFEXP_LAGN->PJM
CLTF
2.246
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CBM West 2LTFEXP_CBM-W2->PJM
CBM
34.176
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
NYPJM->LTFIMP_NY
CLTF
1.043
WECLTFEXP_WEC->PJM
CLTF
2.99
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.226
AG2-052LTFEXP_AG2-052->PJM
LTF
0.2
AH1-155LTFEXP_AH1-155->PJM
LTF
0.301
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.745
CBM West 1LTFEXP_CBM-W1->PJM
CBM
81.126
MECLTFEXP_MEC->PJM
CLTF
10.584

Details for 05JEFRSO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#709_546_SRT-A


Base Case Flowgate

Area:AEP/OVEC
Facility Description:
05JEFRSO-06CLIFTY 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#709_546_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:127.46 %
Rating:2826.0 MVA
Rating Type:B
MVA to Mitigate:3601.92
MW Contribution:10.16
Bus #Bus NameTypeMW Contribution
24344205RKG1
50/50
11.244
24344205RKG1
50/50
11.22
24344305RKG2
50/50
11.199
270393AB1-087 CT1
50/50
2.508
270394AB1-087 ST1
50/50
2.508
970541AG2-344 GEN
50/50
10.209
970539AG2-343 GEN
50/50
9.364
970543AG2-345 GEN
50/50
4.682
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
4.647
958391AF2-133 GEN
Solar/Wind Harmer
0.001
963841AG1-237 GEN
Solar/Wind Harmer
3.256
270536AF1-215 GEN2
Solar/Wind Harmer
0.009
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971347AH1-153 GEN
Solar/Wind Harmer
9.104
274775LINCOLN ;6U
Adder
7.237
274776LINCOLN ;7U
Adder
7.237
274777LINCOLN ;8U
Adder
7.237
971769AH1-391 GEN
Solar/Wind Harmer
6.648
274814UNIV PK N;0U
Adder
4.294
274807UNIV PK N;3U
Adder
4.285
274805UNIV PK N;1U
Adder
4.266
274811UNIV PK N;7U
Adder
4.257
972227AH1-698 GEN1
Adder
2.206
960591AF2-350 GEN
Solar/Wind Harmer
5.898
972037AH1-567 GEN1
Adder
0.155
274827FISK ;RP
Adder
6.544
274687WILL CNTY;4U
Adder
23.403
274687WILL CNTY;4U
Adder
23.403
274731ELWOOD EC;2P
Adder
13.765
274733ELWOOD EC;3P
Adder
13.765
274735ELWOOD EC;4P
Adder
13.765
274728ELWOOD EC;5P
Adder
13.765
970833AG2-524 GEN
Solar/Wind Harmer
6.424
970833AG2-524 GEN
Solar/Wind Harmer
4.282
274675JOLIET 29;7U
Adder
25.664
274675JOLIET 29;7U
Adder
24.747
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
970169AG2-114 GEN
Solar/Wind Harmer
5.784
274746AC1-111 G10
Adder
4.62
274744AC1-111 GEN8
Adder
4.62
276655WTG1_EQ
Solar/Wind Harmer
0.002
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
6.036
941731AE2-173 GEN
Solar/Wind Harmer
4.79
971771AH1-392 GEN
Solar/Wind Harmer
5.725
276868AE1-113 GEN
Solar/Wind Harmer
1.14
276882AE2-255 GEN
Solar/Wind Harmer
0.664
276785W4-005 GEN1
Solar/Wind Harmer
0.001
942601AE2-276 GEN
50/50
8.344
270102X2-052 ST
50/50
1.424
970091AG2-072 GEN
50/50
218.455
270407AB1-088 ST1
50/50
2.508
970023AG2-014 GEN
50/50
2.686
970783AG2-492 GEN
50/50
2.686
24344105CKG2
50/50
6.851
970333AG2-219 GEN
Solar/Wind Harmer
14.81
270445AC2-157 GEN2
Solar/Wind Harmer
0.004
970245AG2-165 GEN
Solar/Wind Harmer
3.606
24791305MDL-5G
Solar/Wind Harmer
0.001
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
9.756
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.732
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0.006
963741AG1-226 GEN
Solar/Wind Harmer
17.046
970373AG2-245 GEN
Solar/Wind Harmer
14.55
274773LINCOLN ;4U
Adder
7.237
274774LINCOLN ;5U
Adder
7.237
274751CRETE EC ;1U
Adder
7.047
274754CRETE EC ;4U
Adder
7.047
274723RIVER EC ;12
Adder
15.25
274812UNIV PK N;8U
Adder
4.257
276164X3-005 C
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
0.616
274801UNIV PARK;4U
Adder
4.918
939401AE1-172 GEN
Solar/Wind Harmer
4.373
274732ELWOOD EC;7P
Adder
13.765
274674JOLIET 9 ;6U
Adder
12.881
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
25.663
274745AC1-111 GEN9
Adder
4.62
276691AA1-018 GEN1
Solar/Wind Harmer
0.697
276726Z2-087_GEN
Solar/Wind Harmer
0.002
939741AE1-205 GEN
Solar/Wind Harmer
8.048
276901AD2-066 C O1
Solar/Wind Harmer
0.006
274854TWINGROVE;U2
Solar/Wind Harmer
0.002
971997AH1-543 GEN
Solar/Wind Harmer
2.988
274682WAUKEGAN ;7U
Adder
14.638
274828WAUKEGAN ;BP
Adder
8.984
972175AH1-670 GEN
Solar/Wind Harmer
4.678
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
962781AG1-127 GEN
Solar/Wind Harmer
5.364
274872LEEDK;1U
Solar/Wind Harmer
0.003
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
2.181
970569AG2-363 GEN
Solar/Wind Harmer
16.771
276861AD2-134 GEN
Solar/Wind Harmer
0.1
270505AE1-170 C O1
Solar/Wind Harmer
5.832
276615X2-022 GEN
Solar/Wind Harmer
0.058
957471AF2-041 GEN
Solar/Wind Harmer
16.603
959081AF2-199 GEN
Solar/Wind Harmer
5.534
971067AG2-660 GEN
Solar/Wind Harmer
1.845
274822ROCKFORD ;11
Adder
1.007
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.872
945111AF1-176 GEN
Solar/Wind Harmer
9.771
970819AG2-516 GEN
Solar/Wind Harmer
6.568
274877BISHOP HL;1U
Solar/Wind Harmer
0.183
971475AH1-234 GEN
Solar/Wind Harmer
2.645
965911AG1-460 GEN
Solar/Wind Harmer
1.09
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
276158O29GEN2
Solar/Wind Harmer
0.001
270063AE2-323 C
Solar/Wind Harmer
0.004
970291AG2-192 GEN
Solar/Wind Harmer
0.488
965011AG1-365 GEN
Solar/Wind Harmer
3.044
944231AF1-091 GEN
Solar/Wind Harmer
0.807
252507AC2-088 GEN
Solar/Wind Helper
1.471
339216AC1-074 GEN
Solar/Wind Helper
1.461
943111AE2-339 GEN
Solar/Wind Helper
0.643
339241AF1-083 GEN
Solar/Wind Helper
0.405
253343AC1-166 GEN
Solar/Wind Helper
0.467
253325AC1-069 GEN
Solar/Wind Helper
0.484
24344305RKG2
50/50
10.991
270406AB1-088 CT1
50/50
2.508
970243AG2-164 GEN
Solar/Wind Harmer
12.117
970519AG2-331 GEN
Solar/Wind Harmer
53.854
970699AG2-449 GEN
Solar/Wind Harmer
5.178
970513AG2-328 GEN
Solar/Wind Harmer
3.606
970517AG2-330 GEN
Solar/Wind Harmer
21.635
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
8.058
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
964401AG1-302 GEN
Solar/Wind Harmer
0.001
270535AF1-215 GEN1
Solar/Wind Harmer
0.009
970193AG2-126 GEN
Solar/Wind Harmer
9.211
970349AG2-230 GEN
Solar/Wind Harmer
9.104
274772LINCOLN ;3U
Adder
7.237
274752CRETE EC ;2U
Adder
7.047
274753CRETE EC ;3U
Adder
7.047
274724RIVER EC ;11
Adder
15.065
276897AD1-100 C
Solar/Wind Harmer
0.008
939351AE1-166 GEN
Solar/Wind Harmer
0
972228AH1-698 GEN2
Adder
3.132
276806AD2-047 C O1
Solar/Wind Harmer
3.342
970941AG2-585 GEN
Solar/Wind Harmer
7.373
274802UNIV PARK;5U
Adder
4.928
274800UNIV PARK;3U
Adder
4.918
972038AH1-567 GEN2
Adder
0.308
274826FISK ;BP
Adder
9.234
970707AG2-453 GEN
Solar/Wind Harmer
19.213
274729ELWOOD EC;1P
Adder
13.765
274730ELWOOD EC;6P
Adder
13.765
274734ELWOOD EC;8P
Adder
13.765
274736ELWOOD EC;9P
Adder
13.765
276893AG1-478 C
Solar/Wind Harmer
0.231
274676JOLIET 29;8U
Adder
24.747
943121AE2-341 GEN
Solar/Wind Harmer
9.668
943591AF1-030 GEN
Solar/Wind Harmer
6.429
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
942111AE2-223 GEN
Solar/Wind Harmer
1.868
276805AD2-038 GEN
Solar/Wind Harmer
0.002
274853TWINGROVE;U1
Solar/Wind Harmer
0.002
965091AG1-374 GEN
Solar/Wind Harmer
17.118
959611AF2-252 GEN
Solar/Wind Harmer
1.902
274682WAUKEGAN ;7U
Adder
14.638
24642205MAYFLWER
Adder
0.516
276889AE2-281 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0.206
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
2.595
276668AB2-070 GEN1
Solar/Wind Harmer
0.205
970571AG2-364 GEN
Solar/Wind Harmer
11.181
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.595
274855GSG-6 ;RU
Solar/Wind Harmer
0.204
274850MENDOTA H;RU
Solar/Wind Harmer
0.066
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.1
276621W2-048 GEN
Solar/Wind Harmer
0.28
276838X2-022 GEN2
Solar/Wind Harmer
0.313
959091AF2-200 GEN
Solar/Wind Harmer
11.069
247643Z2-116 C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
4.439
274878BISHOP HL;2U
Solar/Wind Harmer
0.183
942481AE2-261 GEN
Solar/Wind Harmer
16.292
24441205WTRV SLR C
Solar/Wind Harmer
0
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
276157O29GEN1
Solar/Wind Harmer
0.872
965931AG1-462 GEN
Solar/Wind Harmer
13.177
247642Z2-115 C
Solar/Wind Harmer
0.002
970031AG2-029 GEN
Solar/Wind Harmer
2.905
270043AE2-236 GEN
Solar/Wind Harmer
2.56
970289AG2-191 GEN
Solar/Wind Harmer
0.413
970291AG2-192 GEN
Solar/Wind Harmer
0.376
959331AF2-224 GEN
Solar/Wind Harmer
2.131
965021AG1-366 GEN
Solar/Wind Harmer
1.015
252510AF1-249 C
Solar/Wind Helper
0.376
253406AD2-031_GEN
Solar/Wind Helper
0.712
253415AE1-040 GEN
Solar/Wind Helper
0.483
339250AF1-203 GEN
Solar/Wind Helper
0.118
253338AC1-165 GEN
Solar/Wind Helper
0.467
253333AC1-068 GEN
Solar/Wind Helper
0.484
270100X2-052 CT1
50/50
1.312
270101X2-052 CT2
50/50
1.312
970239AG2-162 GEN
Solar/Wind Harmer
5.178
270444AC2-157 GEN1
Solar/Wind Harmer
0.004
971587AH1-292 GEN
Solar/Wind Harmer
7.343
970321AG2-212 GEN
Solar/Wind Harmer
3.606
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
966841AG1-555 GEN
Solar/Wind Harmer
0.888
970241AG2-163 GEN
Solar/Wind Harmer
4.202
965681AG1-436 GEN
Solar/Wind Harmer
7.741
965791AG1-447 GEN
Solar/Wind Harmer
5.677
945391AF1-204 GEN
Solar/Wind Harmer
6.524
274770LINCOLN ;1U
Adder
7.237
274771LINCOLN ;2U
Adder
7.237
24441505OLIV SLR
Solar/Wind Harmer
0
274808UNIV PK N;4U
Adder
4.239
270526AF1-158 GEN
Solar/Wind Harmer
0.007
274888KELLY CRK;1U
Solar/Wind Harmer
0.346
274887GEN-1.85
Solar/Wind Harmer
0.155
276843GEN-1.7
Solar/Wind Harmer
0.191
958011AF2-095 GEN
Solar/Wind Harmer
8.493
274803UNIV PARK;6U
Adder
4.928
972259AH1-714 GEN
Adder
16.092
274674JOLIET 9 ;6U
Adder
12.881
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
958481AF2-142 GEN
Solar/Wind Harmer
8.633
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.778
971573AH1-285 GEN
Solar/Wind Harmer
1.068
958491AF2-143 GEN
Solar/Wind Harmer
8.559
960611AF2-352 GEN
Solar/Wind Harmer
1.902
274695ROCKY RD ;2P
Adder
9.087
274693ROCKY RD ;1P
Adder
8.997
274697ROCKY RD ;3P
Adder
2.468
274696ROCKY RD ;4P
Adder
9.301
274879MINONK ;1U
Solar/Wind Harmer
0.24
274683WAUKEGAN ;8U
Adder
17.139
274683WAUKEGAN ;8U
Adder
14.447
962691AG1-118 GEN
Solar/Wind Harmer
16.954
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
970921AG2-575 GEN
Solar/Wind Harmer
5.636
970921AG2-575 GEN
Solar/Wind Harmer
1.879
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
942991AE2-321 GEN
Solar/Wind Harmer
6.244
971333AH1-146 GEN
Solar/Wind Harmer
11.124
971335AH1-147 GEN
Solar/Wind Harmer
11.124
957891AF2-083 GEN
Solar/Wind Harmer
0.001
971341AH1-150 GEN
Solar/Wind Harmer
11.069
971343AH1-151 GEN
Solar/Wind Harmer
11.069
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.216
276646AC1-214 GEN2
Solar/Wind Harmer
0.216
961051AF2-396 GEN
Solar/Wind Harmer
10.985
961051AF2-396 GEN
Solar/Wind Harmer
7.324
270216AD2-079_GEN
Solar/Wind Harmer
0.001
274856ECOGROVE ;U1
Solar/Wind Harmer
0.129
276611AD2-172 GEN
Solar/Wind Harmer
0.001
276782AC1-033 GEN
Solar/Wind Harmer
0.001
276916AD2-100_GEN
Solar/Wind Harmer
11.423
276911AD2-131_GEN
Solar/Wind Harmer
0.752
938861AE1-114 GEN
Solar/Wind Harmer
3.082
276603SUBLETTE C
Solar/Wind Harmer
0
276741O09 GEN1
Solar/Wind Harmer
0.192
276708O09 GEN2
Solar/Wind Harmer
0.192
970611AG2-400 GEN
Solar/Wind Harmer
3.044
970627AG2-408 GEN
Solar/Wind Harmer
0.913
252509AD1-136 GEN
Solar/Wind Helper
0.21
339221AD2-048_GEN
Solar/Wind Helper
1.206
25183208HLCRTG
Solar/Wind Helper
2.027
270186AC1-089 GEN
Solar/Wind Helper
0.821
253394AE2-221_GEN
Solar/Wind Helper
1.236
253398AE2-221_GEN2
Solar/Wind Helper
1.236
962581AG1-107 GEN
Solar/Wind Helper
0.907
961491AF2-440 GEN
Solar/Wind Helper
0.037
339236AF1-050_GEN
Solar/Wind Helper
0.406
339231AF1-038_GEN
Solar/Wind Helper
0.396
339255AE2-071 GEN
Solar/Wind Helper
0.206
270518AE2-148 GEN
Solar/Wind Helper
5.626
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.205
276848AB2-070 GEN3
Solar/Wind Harmer
0.204
926823AC1-168 GEN
Solar/Wind Harmer
0.954
971177AH1-047 GEN
Solar/Wind Harmer
3.447
971675AH1-338 GEN
Solar/Wind Harmer
2.173
971411AH1-196 GEN
Solar/Wind Harmer
8.347
971619AH1-309 GEN
Solar/Wind Harmer
2.5
971171AH1-044 GEN
Solar/Wind Harmer
11.069
274823ROCKFORD ;21
Adder
15.377
957751AF2-069 GEN
Solar/Wind Harmer
0.182
276612AE2-035 GEN
Solar/Wind Harmer
0.001
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
971681AH1-341 GEN
Solar/Wind Harmer
8.765
944221AF1-090 GEN
Solar/Wind Harmer
3.172
961011AF2-392 GEN
Solar/Wind Harmer
3.16
946321AF1-296 GEN
Solar/Wind Harmer
2.912
971549AH1-272 GEN
Solar/Wind Harmer
10.16
270071AF1-092 GEN
Solar/Wind Harmer
8.874
970289AG2-191 GEN
Solar/Wind Harmer
0.714
252524AE2-267 GEN
Solar/Wind Helper
0.465
339243AC2-075 GEN1
Solar/Wind Helper
0.336
339211AE2-254 GEN
Solar/Wind Helper
0.447
270367AC2-061_GEN
Solar/Wind Helper
1.692
270340AC2-060 GEN
Solar/Wind Helper
1.094
241972AD1-140 GEN
Solar/Wind Helper
2.07
944201AF1-088_MTX
50/50
166.885
957141AF2-008_MTX
50/50
83.443
991312J1772
External Queue
12.355378150939941
991112J1481
External Queue
17.5482177734375
950011AG9-010
External Queue
6.204055309295654
991082J1475 G
External Queue
6.161812782287598
955142J992
External Queue
11.408185005187988
990742J1381
External Queue
17.5482177734375
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
9.981
BlueGrassPJM->LTFIMP_BlueG
CLTF
28.615
LAGNLTFEXP_LAGN->PJM
CLTF
2.246
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CBM West 2LTFEXP_CBM-W2->PJM
CBM
34.176
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
NYPJM->LTFIMP_NY
CLTF
1.043
WECLTFEXP_WEC->PJM
CLTF
2.99
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.226
AG2-052LTFEXP_AG2-052->PJM
LTF
0.2
AH1-155LTFEXP_AH1-155->PJM
LTF
0.301
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.745
CBM West 1LTFEXP_CBM-W1->PJM
CBM
81.126
MECLTFEXP_MEC->PJM
CLTF
10.584

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P1-2_MP-500-007A_SRT-A


Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P1-2_MP-500-007A_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:131.92 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5002.28
MW Contribution:14.87
Bus #Bus NameTypeMW Contribution
962771AG1-126 GEN
Solar/Wind Harmer
34.524
972239AH1-704 GEN
Adder
2.689
270054AF2-122 C O1
Solar/Wind Harmer
0.007
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
5.077
270520AE2-214 GEN
Solar/Wind Harmer
0.013
270284AF1-227 GEN1
Solar/Wind Harmer
0.011
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
253383AE2-342_GEN
Solar/Wind Harmer
0.003
241973AD2-163_GEN1
Solar/Wind Harmer
0.006
945631AF1-228 GEN
Solar/Wind Harmer
0
943861AF1-054 GEN
Solar/Wind Harmer
3.127
943851AF1-053 GEN
Solar/Wind Harmer
2.166
270156DARBY CT1
Adder
10.409
270157DARBY CT2
Adder
10.383
270158DARBY CT3
Adder
10.218
970689AG2-444 GEN
Solar/Wind Harmer
16.436
270578AF1-285 GEN2
Solar/Wind Harmer
0.536
270432AC2-029 GEN
Solar/Wind Harmer
3.553
940611AE2-048 GEN
Solar/Wind Harmer
19.602
941391AE2-136 GEN
Solar/Wind Harmer
11.042
270302AB2-170 GEN
Solar/Wind Harmer
0.005
270317AD1-130_GEN
Solar/Wind Harmer
0.011
971653AH1-327 GEN
Solar/Wind Harmer
1.117
270269AC2-059
Solar/Wind Harmer
0.005
241972AD1-140 GEN
Solar/Wind Harmer
0.854
970179AG2-119 GEN
Solar/Wind Harmer
6.883
270340AC2-060 GEN
Solar/Wind Harmer
0.009
970879AG2-548 GEN
Solar/Wind Harmer
6.898
253372AE2-315 SEC3
Adder
2.063
253372AE2-315 SEC3
Adder
2.063
25306009OHH W.
Adder
3.13
253349AC2-067 GEN
Solar/Wind Harmer
2.381
253400AC2-068 GEN
Solar/Wind Harmer
0.958
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
0.953
965051AG1-369 GEN
Solar/Wind Harmer
3.739
965041AG1-368 GEN
Solar/Wind Harmer
7.471
247607V1-011 GEN
Solar/Wind Harmer
0.001
971567AH1-282 GEN
Solar/Wind Harmer
11.206
971989AH1-539 GEN
Solar/Wind Harmer
3.215
963791AG1-232 GEN
Solar/Wind Harmer
10.044
24729505KEY G4
Adder
6.919
270071AF1-092 GEN
Solar/Wind Harmer
14.245
971985AH1-537 GEN
Solar/Wind Harmer
2.206
270024AE2-089 GEN
Solar/Wind Harmer
0.008
270367AC2-061_GEN
Solar/Wind Harmer
0.006
965101AG1-375 GEN
Solar/Wind Harmer
7.401
971673AH1-337 GEN
Solar/Wind Harmer
4.804
252524AE2-267 GEN
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
9.344
25196308WSDLE2
Adder
9.263
25196208WSDLE1
Adder
9.24
25196708WSDLE6
Adder
9.217
25196508WSDLE4
Adder
8.984
971029AG2-637 GEN
Solar/Wind Harmer
11.085
270543AE2-219 C
Solar/Wind Harmer
0.004
945581AF1-223 GEN
Solar/Wind Harmer
0.001
270297AD1-101 GEN
Solar/Wind Harmer
0.002
971347AH1-153 GEN
Solar/Wind Harmer
11.025
971609AH1-304 GEN
Solar/Wind Harmer
1.2
270240V3-007_GEN2
Solar/Wind Harmer
0.002
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
970115AG2-085 GEN
Solar/Wind Harmer
2.932
270594AE1-207 GEN
Solar/Wind Harmer
8.194
970289AG2-191 GEN
Solar/Wind Harmer
1.389
971771AH1-392 GEN
Solar/Wind Harmer
7.306
971619AH1-309 GEN
Solar/Wind Harmer
3.285
971769AH1-391 GEN
Solar/Wind Harmer
8.134
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
25196108MFTGT2
Adder
1.599
25196108MFTGT2
Adder
1.484
270536AF1-215 GEN2
Solar/Wind Harmer
0.009
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
4.302
971549AH1-272 GEN
Solar/Wind Harmer
14.865
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
8.676
274776LINCOLN ;7U
Adder
8.676
274777LINCOLN ;8U
Adder
8.676
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
274814UNIV PK N;0U
Adder
5.184
274807UNIV PK N;3U
Adder
5.173
274805UNIV PK N;1U
Adder
5.15
274811UNIV PK N;7U
Adder
5.139
972037AH1-567 GEN1
Adder
0.187
960591AF2-350 GEN
Solar/Wind Harmer
7.141
274827FISK ;RP
Adder
7.941
972227AH1-698 GEN1
Adder
2.669
963841AG1-237 GEN
Solar/Wind Harmer
3.09
972163AH1-664 GEN
Solar/Wind Harmer
7.933
972165AH1-665 GEN
Solar/Wind Harmer
6.354
274687WILL CNTY;4U
Adder
28.523
274687WILL CNTY;4U
Adder
28.523
274675JOLIET 29;7U
Adder
31.303
274675JOLIET 29;7U
Adder
30.185
274731ELWOOD EC;2P
Adder
16.768
274733ELWOOD EC;3P
Adder
16.768
274735ELWOOD EC;4P
Adder
16.768
274728ELWOOD EC;5P
Adder
16.768
970833AG2-524 GEN
Solar/Wind Harmer
7.824
970833AG2-524 GEN
Solar/Wind Harmer
5.216
274746AC1-111 G10
Adder
5.679
274744AC1-111 GEN8
Adder
5.679
972203AH1-686 GEN
Adder
2.338
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
276868AE1-113 GEN
Solar/Wind Harmer
1.414
276882AE2-255 GEN
Solar/Wind Harmer
0.824
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238126S14_GEN_1
Solar/Wind Helper
0.827
238152AF2-075_GEN
Solar/Wind Helper
0.707
238208AF1-136 C
Solar/Wind Helper
0.22
23546401DTGZ2-030
Solar/Wind Helper
0.089
237085AD2-009_GEN
Solar/Wind Helper
1.649
3138216PACIFIC
Solar/Wind Helper
0.044
316411AF1-147_GEN1
Solar/Wind Helper
0.888
316415AF1-147_GEN2
Solar/Wind Helper
0.888
23750501ELLIOTTS
Solar/Wind Helper
0.638
959381AF2-229 GEN
Solar/Wind Helper
0.357
24318805MLG1
50/50
10.095
23559001PLEAS1
50/50
6.1
270051AF1-062 GEN
50/50
11.821
270475AD2-096_GEN
50/50
7.141
970153AG2-106 GEN
Solar/Wind Harmer
22.046
961921AG1-034 GEN
Solar/Wind Harmer
7.615
241955AC1-078 GEN
Solar/Wind Harmer
0.007
24721905FLATG4
Adder
23.918
241974AD2-163_GEN2
Solar/Wind Harmer
0.006
942051AE2-217 GEN
Solar/Wind Harmer
14.671
970605AG2-385 GEN
Solar/Wind Harmer
4.899
270391AF1-285 GEN3
Solar/Wind Harmer
0.536
253338AC1-165 GEN
Solar/Wind Harmer
0.003
253333AC1-068 GEN
Solar/Wind Harmer
0.012
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270273AD2-016 GEN
Solar/Wind Harmer
0.821
972173AH1-669 GEN
Solar/Wind Harmer
3.952
270291AC1-194 GEN
Solar/Wind Harmer
6.106
253415AE1-040 GEN
Solar/Wind Harmer
0.003
270512AE1-227 GEN2
Solar/Wind Harmer
1.963
970065AG2-057 GEN
Solar/Wind Harmer
0.76
253370AE2-315 SEC1
Adder
2.182
253371AE2-315 SEC2
Adder
2.063
253406AD2-031_GEN
Solar/Wind Harmer
0.563
970191AG2-125 GEN
Solar/Wind Harmer
1.945
270491AE1-102 GEN2
Solar/Wind Harmer
0.979
270377AD1-106 GEN
Solar/Wind Harmer
2.855
971191AH1-055 GEN
Solar/Wind Harmer
19.26
253316AC1-085 GEN3
Solar/Wind Harmer
0.005
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
9.749
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.048
959331AF2-224 GEN
Solar/Wind Harmer
5.242
965021AG1-366 GEN
Solar/Wind Harmer
2.496
270588AE1-091_GEN
Solar/Wind Harmer
5.845
944531AF1-118 GEN
Solar/Wind Harmer
33.395
270043AE2-236 GEN
Solar/Wind Harmer
4.777
270258AD1-119 GEN
Solar/Wind Harmer
0.002
971617AH1-308 GEN
Solar/Wind Harmer
6.173
25196608WSDLE5
Adder
9.077
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
252510AF1-249 C
Solar/Wind Harmer
0.057
957741AF2-068 GEN
Solar/Wind Harmer
11.081
25194608D.CRK4
Adder
1.74
270222AC2-111 GEN
Solar/Wind Harmer
3.739
970031AG2-029 GEN
Solar/Wind Harmer
4.795
270404AC1-167 GEN
Solar/Wind Harmer
0.003
970513AG2-328 GEN
Solar/Wind Harmer
3.191
970517AG2-330 GEN
Solar/Wind Harmer
19.146
970349AG2-230 GEN
Solar/Wind Harmer
11.025
946031AF1-268 GEN
Solar/Wind Harmer
6.992
958821AF2-173 GEN
Solar/Wind Harmer
10.273
270004AE1-209 GEN
Solar/Wind Harmer
1.59
270437AC2-090 C
Solar/Wind Harmer
0.003
247643Z2-116 C
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.804
970291AG2-192 GEN
Solar/Wind Harmer
0.731
247642Z2-115 C
Solar/Wind Harmer
0.003
945111AF1-176 GEN
Solar/Wind Harmer
5.919
24642205MAYFLWER
Adder
0.665
25196008MFTGT1
Adder
1.405
270356AE2-297 GEN
Solar/Wind Harmer
0.01
24441205WTRV SLR C
Solar/Wind Harmer
0
247604X1-042
Adder
0.433
270535AF1-215 GEN1
Solar/Wind Harmer
0.009
964401AG1-302 GEN
Solar/Wind Harmer
0.001
970217AG2-149 GEN
Solar/Wind Harmer
6.268
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
7.196
970243AG2-164 GEN
Solar/Wind Harmer
4.205
970519AG2-331 GEN
Solar/Wind Harmer
18.687
970699AG2-449 GEN
Solar/Wind Harmer
1.797
274752CRETE EC ;2U
Adder
8.477
274753CRETE EC ;3U
Adder
8.477
958171AF2-111 GEN
Solar/Wind Harmer
17.94
274772LINCOLN ;3U
Adder
8.676
274724RIVER EC ;11
Adder
18.203
972167AH1-666 GEN
Solar/Wind Harmer
5.717
24728705AND G3
Adder
8.214
274802UNIV PARK;5U
Adder
5.97
24728505AND G1
Adder
3.927
276806AD2-047 C O1
Solar/Wind Harmer
4.047
970941AG2-585 GEN
Solar/Wind Harmer
8.927
274826FISK ;BP
Adder
11.205
274800UNIV PARK;3U
Adder
5.966
972038AH1-567 GEN2
Adder
0.373
972228AH1-698 GEN2
Adder
3.79
276897AD1-100 C
Solar/Wind Harmer
0.009
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
970707AG2-453 GEN
Solar/Wind Harmer
23.303
274676JOLIET 29;8U
Adder
30.185
276893AG1-478 C
Solar/Wind Harmer
0.282
274729ELWOOD EC;1P
Adder
16.768
274730ELWOOD EC;6P
Adder
16.768
274734ELWOOD EC;8P
Adder
16.768
274736ELWOOD EC;9P
Adder
16.768
943121AE2-341 GEN
Solar/Wind Harmer
11.888
943591AF1-030 GEN
Solar/Wind Harmer
7.906
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
270541AE2-072 C
Solar/Wind Harmer
0.009
274682WAUKEGAN ;7U
Adder
9.728
276805AD2-038 GEN
Solar/Wind Harmer
0.002
964991AG1-363 GEN
Solar/Wind Helper
5.136
316097T157 G90
Solar/Wind Helper
1.504
23750701CROSSCHOOL
Solar/Wind Helper
1.502
238118U2-030_1
Solar/Wind Helper
0.341
238127S14_GEN_2
Solar/Wind Helper
0.827
238148AE2-230_GEN2
Solar/Wind Helper
0.497
237080AD1-060 GEN
Solar/Wind Helper
0.342
237038AE2-054 C
Solar/Wind Helper
0.272
235062AE1-101 C1
Solar/Wind Helper
1.659
23779801AA1-109
Solar/Wind Helper
0.193
237048AF1-022 C
Solar/Wind Helper
0.177
223401AF1-299 GEN
Solar/Wind Helper
0.367
316006AB2-029 C
Solar/Wind Helper
0.117
966131AG1-482 GEN
Solar/Wind Helper
0.137
233930AB2-032 GEN
Solar/Wind Helper
0.381
233915AB1-141 GEN
Solar/Wind Helper
0.502
232422X3-066 FULL
Solar/Wind Helper
0.114
232428Y3-058 C
Solar/Wind Helper
0.338
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
233998TM1NIN_3.36
Solar/Wind Helper
0.261
232404W1-003 C
Solar/Wind Helper
0.507
232434Z2-077 GEN
Solar/Wind Helper
0.127
233954AC2-188 GEN
Solar/Wind Helper
0.232
233950AC2-186 GEN
Solar/Wind Helper
0.116
233972AC1-094 C
Solar/Wind Helper
0.302
316045AC1-158 PL2
Solar/Wind Helper
4.138
230511AF1-262
Solar/Wind Helper
0.015
270166AC1-044 GEN3
50/50
7.059
23559101PLEAS2
50/50
6.1
962761AG1-125 GEN
Solar/Wind Harmer
34.524
970149AG2-104 GEN
Solar/Wind Harmer
37.287
970155AG2-107 GEN
Solar/Wind Harmer
22.046
270349AD2-093_GEN
Solar/Wind Harmer
0.006
24721705FLATG2
Adder
23.918
270159DARBY CT4
Adder
10.243
970593AG2-378 GEN
Solar/Wind Harmer
1.812
270223U2-072_GEN1
Solar/Wind Harmer
0.001
253343AC1-166 GEN
Solar/Wind Harmer
0.003
253325AC1-069 GEN
Solar/Wind Harmer
0.012
270462AD2-086
Solar/Wind Harmer
0.017
971995AH1-542 GEN
Solar/Wind Harmer
2.906
270263AC1-001 GEN
Solar/Wind Harmer
0.786
270510AE1-227 GEN1
Solar/Wind Harmer
1.963
25326309TAIT D
Adder
1.196
241813AF1-122_GEN
Solar/Wind Harmer
3.405
960071AF2-298 GEN
Solar/Wind Harmer
3.786
253370AE2-315 SEC1
Adder
2.182
253371AE2-315 SEC2
Adder
2.063
927014AC1-188 GEN
Solar/Wind Harmer
0.005
246936BC-WTG1
Solar/Wind Harmer
0.305
270489AE1-102 GEN1
Solar/Wind Harmer
0.979
965421AG1-410 GEN
Solar/Wind Harmer
22.57
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.499
247521TR3_G114
Solar/Wind Harmer
0.273
270246TR4_N_V150
Solar/Wind Harmer
0.048
965011AG1-365 GEN
Solar/Wind Harmer
7.488
24695305TIMB G C
Solar/Wind Harmer
0.002
965651AG1-433 GEN
Solar/Wind Harmer
2.174
958861AF2-177 GEN
Solar/Wind Harmer
3.207
247536S-71 GEN
Solar/Wind Harmer
0.297
25194608D.CRK4
Adder
1.74
945371AF1-202 GEN
Solar/Wind Harmer
0.001
252507AC2-088 GEN
Solar/Wind Harmer
0.335
270063AE2-323 C
Solar/Wind Harmer
0.006
970245AG2-165 GEN
Solar/Wind Harmer
3.191
970947AG2-589 GEN
Solar/Wind Harmer
0.245
270005AE1-210 C O1
Solar/Wind Harmer
1.59
965031AG1-367 GEN
Solar/Wind Harmer
7.338
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.378
970825AG2-519 GEN
Solar/Wind Harmer
2.603
25196808ZIMRHP
Adder
79.729
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
944231AF1-091 GEN
Solar/Wind Harmer
1.953
24639705ELKHART HY
Adder
0.161
270032AE2-172
Solar/Wind Harmer
4.877
970291AG2-192 GEN
Solar/Wind Harmer
0.95
945111AF1-176 GEN
Solar/Wind Harmer
13.03
270505AE1-170 C O1
Solar/Wind Harmer
7.665
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.805
276903AD2-071 C
Solar/Wind Harmer
8.137
25196008MFTGT1
Adder
1.45
247522W1-056 GEN
Solar/Wind Harmer
0.001
970773AG2-487 GEN
Solar/Wind Harmer
1.284
970373AG2-245 GEN
Solar/Wind Harmer
15.247
270055AF2-134 C O1
Solar/Wind Harmer
0.006
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.41
970515AG2-329 GEN
Solar/Wind Harmer
18.805
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
9.032
24791305MDL-5G
Solar/Wind Harmer
0.001
970333AG2-219 GEN
Solar/Wind Harmer
5.139
274751CRETE EC ;1U
Adder
8.477
274754CRETE EC ;4U
Adder
8.477
274773LINCOLN ;4U
Adder
8.676
274774LINCOLN ;5U
Adder
8.676
274723RIVER EC ;12
Adder
18.418
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
5.139
24728605AND G2
Adder
3.927
276776AD2-060 GEN
Solar/Wind Harmer
0.746
945681AF1-233 GEN
Solar/Wind Harmer
13.461
274801UNIV PARK;4U
Adder
5.966
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
31.303
274732ELWOOD EC;7P
Adder
16.768
274674JOLIET 9 ;6U
Adder
15.704
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
963741AG1-226 GEN
Solar/Wind Harmer
16.815
274745AC1-111 GEN9
Adder
5.679
939401AE1-172 GEN
Solar/Wind Harmer
5.301
276691AA1-018 GEN1
Solar/Wind Harmer
0.858
970091AG2-072 GEN
Adder
77.629
276901AD2-066 C O1
Solar/Wind Harmer
0.007
316095T157 G97
Solar/Wind Helper
1.504
23583801GRNGAP
Solar/Wind Helper
5.601
238185AF2-356 C
Solar/Wind Helper
2.646
238108AE1-109 GEN1
Solar/Wind Helper
0.114
235054AD2-180 GEN
Solar/Wind Helper
2.03
235531U2-073 GEN
Solar/Wind Helper
3.282
238117U2-030
Solar/Wind Helper
0.341
238147AE2-230_GEN1
Solar/Wind Helper
0.495
238149AF1-291A_GEN
Solar/Wind Helper
0.141
23751201ROTHROCK
Solar/Wind Helper
0.824
237061AD1-155 GEN
Solar/Wind Helper
0.053
23562501BACKB
Solar/Wind Helper
1.007
238221AF1-254 C O1
Solar/Wind Helper
0.274
235067AD1-061 GEN
Solar/Wind Helper
0.496
23751101LEADS_P59
Solar/Wind Helper
1.404
237030AB1-096 C
Solar/Wind Helper
0.071
3141196NOKESVL
Solar/Wind Helper
1.032
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.346
223402AF1-300 C
Solar/Wind Helper
0.367
205917AD1-020 ES
Solar/Wind Helper
0.368
233918AB1-142 GEN
Solar/Wind Helper
0.502
233982AB2-133 GEN
Solar/Wind Helper
0.358
233994AC2-023 GEN
Solar/Wind Helper
0.961
233996TM1833_GEN
Solar/Wind Helper
0.261
233997TMININ_4.2
Solar/Wind Helper
0.261
232406W1-004 FULL
Solar/Wind Helper
0.507
233940AF2-379 C
Solar/Wind Helper
0.062
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.232
233971AC1-093 C
Solar/Wind Helper
0.357
316044AC1-158 PL1
Solar/Wind Helper
1.293
316450AC1-158 RIC
Solar/Wind Helper
0.345
230430AE1-229_GEN
Solar/Wind Helper
3.372
230415AB2-049 C
Solar/Wind Helper
0.03
228729W2-030 C
Solar/Wind Helper
0.11
3141426STAFORD
Solar/Wind Helper
0.052
960921AF2-383 GEN
Solar/Wind Helper
0.364
205943AE1-185 GEN
Solar/Wind Helper
0.509
205932AD2-116_GEN
Solar/Wind Helper
0.509
205956AE1-196_GEN
Solar/Wind Helper
0.509
233935AB2-179 C
Solar/Wind Helper
1.269
232436AB1-176 C
Solar/Wind Helper
0.044
233923SMA
Solar/Wind Helper
0.958
233990AG1-397 GEN
Solar/Wind Helper
0.27
232432Z2-076 GEN
Solar/Wind Helper
0.067
234033AF1-007_GEN
Solar/Wind Helper
7.02
964001AG1-254 GEN
Solar/Wind Helper
0.955
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.115
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.08
203975AE1-071-GEN
Solar/Wind Helper
2.498
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.29
219620RIDERU C
Solar/Wind Helper
0.001
316164AC1-076 GEN
Solar/Wind Helper
1.096
20675528CPH_W2-050
Solar/Wind Helper
0.087
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
218524CNTRALGAS1 C
Solar/Wind Helper
0.16
966261AG1-495 GEN
Solar/Wind Helper
0.081
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20675928HOL_W4-097
Solar/Wind Helper
0.05
207484AF2-139 C O1
Solar/Wind Helper
0.084
20674828DL_W4-046
Solar/Wind Helper
0.008
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.136
20675128HRM_W1-127
Solar/Wind Helper
0.029
209116AE2-175 GEN
Solar/Wind Helper
1.778
230434AG1-499 GEN
Solar/Wind Helper
0.23
228728W1-130C
Solar/Wind Helper
0.054
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219904AC1-010 C
Solar/Wind Helper
0.06
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.131
20720728JCB_W1-129
Solar/Wind Helper
0.057
316254AC1-120 GEN1
Solar/Wind Helper
1.059
207445AB1-138_GEN
Solar/Wind Helper
0.104
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.13
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.31
20715228NPK_W1-113
Solar/Wind Helper
0.078
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.495
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
207437AD2-070 GEN
Solar/Wind Helper
0.138
207518AF1-320_GEN
Solar/Wind Helper
1.571
20671928W4-073
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.029
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.15
219291REEVESSOUT C
Solar/Wind Helper
0.011
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
219348LDSOLAR C
Solar/Wind Helper
0.114
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.063
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.353
219276PARKLANDSO C
Solar/Wind Helper
0.089
20714528FRN_Y2-051
Solar/Wind Helper
0.057
20720528MAN_W1-024
Solar/Wind Helper
0.028
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.027
219908AB1-139 C
Solar/Wind Helper
0.074
219249CENTRALDIV C
Solar/Wind Helper
0.01
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.089
971997AH1-543 GEN
Solar/Wind Harmer
2.724
270119AB2-067 GEN1
50/50
7.059
270120AB2-067 GEN2
50/50
7.059
24318905MLG2
50/50
7.071
270471AD2-092_GEN
Solar/Wind Harmer
0.006
942861AE2-305 GEN
Solar/Wind Harmer
6.335
970077AG2-063 GEN
Solar/Wind Harmer
4.631
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
938701AE1-092 GEN
Solar/Wind Harmer
12.917
971655AH1-328 GEN
Solar/Wind Harmer
2.854
964601AG1-323 GEN
Solar/Wind Harmer
3.215
964601AG1-323 GEN
Solar/Wind Harmer
2.143
270518AE2-148 GEN
Solar/Wind Harmer
0.691
972269AH1-719 GEN
Adder
2.584
972159AH1-661 GEN
Adder
1.118
253378AE2-206_GEN
Solar/Wind Harmer
0.004
276820AF1-078_GEN
Solar/Wind Harmer
0.002
970329AG2-216 GEN
Solar/Wind Harmer
3.354
971199AH1-059 GEN
Solar/Wind Harmer
3.09
241960AC2-195 GEN
Solar/Wind Harmer
0.006
25326509SID D
Adder
1.451
971073AG2-665 GEN
Solar/Wind Harmer
6.898
25326109MON D
Adder
1.443
25322209TAIT E
Adder
10.642
25322209TAIT E
Adder
10.403
971201AH1-060 GEN
Solar/Wind Harmer
1.52
253370AE2-315 SEC1
Adder
2.182
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
246938BC-WTG3
Solar/Wind Harmer
0.273
246937BC-WTG2
Solar/Wind Harmer
0.305
971231AH1-075 GEN
Solar/Wind Harmer
0.861
253317AC1-085 GEN4
Solar/Wind Harmer
0.005
970611AG2-400 GEN
Solar/Wind Harmer
7.488
970627AG2-408 GEN
Solar/Wind Harmer
2.246
270007AE1-245 C
Solar/Wind Harmer
0.002
962581AG1-107 GEN
Solar/Wind Harmer
0.002
25183208HLCRTG
Solar/Wind Harmer
0.012
944541AF1-119 GEN
Solar/Wind Harmer
0.497
960971AF2-388 GEN
Solar/Wind Harmer
4.347
970623AG2-406 GEN
Solar/Wind Harmer
1.356
942221AE2-234 GEN
Solar/Wind Harmer
0.037
252519AF1-045_GEN
Solar/Wind Harmer
6.44
252516AE2-318_GEN
Solar/Wind Harmer
5.712
247621Y3-024
Adder
0.255
970883AG2-550 GEN
Solar/Wind Harmer
7.389
970885AG2-551 GEN
Solar/Wind Harmer
2.463
270201AC2-176 GEN
Solar/Wind Harmer
0.001
25194408D.CRK1
Adder
8.004
25194508D.CRK3
Adder
1.496
970621AG2-405 GEN
Solar/Wind Harmer
1.351
964611AG1-324 GEN
Solar/Wind Harmer
0.553
252509AD1-136 GEN
Solar/Wind Harmer
0.037
970321AG2-212 GEN
Solar/Wind Harmer
3.191
270599AE1-208 GEN
Solar/Wind Harmer
6.737
270031AE2-169
Solar/Wind Harmer
4.042
270186AC1-089 GEN
Solar/Wind Harmer
0.004
270383AD1-128 GEN
Solar/Wind Harmer
0.004
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
970825AG2-519 GEN
Solar/Wind Harmer
8.127
247620Y3-023
Adder
0.484
960441AF2-335 GEN
Solar/Wind Harmer
7.33
270216AD2-079_GEN
Solar/Wind Harmer
0.001
971613AH1-306 GEN
Solar/Wind Harmer
3.512
24728805RICHG1
Adder
3.964
24728905RICHG2
Adder
3.964
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
14.589
961051AF2-396 GEN
Solar/Wind Harmer
9.726
270526AF1-158 GEN
Solar/Wind Harmer
0.009
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
9.095
965791AG1-447 GEN
Solar/Wind Harmer
6.67
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
970239AG2-162 GEN
Solar/Wind Harmer
1.797
274770LINCOLN ;1U
Adder
8.676
274771LINCOLN ;2U
Adder
8.676
966841AG1-555 GEN
Solar/Wind Harmer
0.81
274808UNIV PK N;4U
Adder
5.117
274803UNIV PARK;6U
Adder
5.97
274888KELLY CRK;1U
Solar/Wind Harmer
0.419
274887GEN-1.85
Solar/Wind Harmer
0.188
276843GEN-1.7
Solar/Wind Harmer
0.231
958011AF2-095 GEN
Solar/Wind Harmer
10.284
972259AH1-714 GEN
Adder
19.507
274674JOLIET 9 ;6U
Adder
15.704
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
970241AG2-163 GEN
Solar/Wind Harmer
4.144
958481AF2-142 GEN
Solar/Wind Harmer
10.621
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.958
971573AH1-285 GEN
Solar/Wind Harmer
1.319
274696ROCKY RD ;4P
Adder
11.537
274695ROCKY RD ;2P
Adder
11.271
274693ROCKY RD ;1P
Adder
11.16
274697ROCKY RD ;3P
Adder
3.062
958491AF2-143 GEN
Solar/Wind Harmer
10.588
274879MINONK ;1U
Solar/Wind Harmer
0.297
23585401KL_K28_T16
Solar/Wind Helper
1.482
238120AE2-309 GEN
Solar/Wind Helper
0.525
238175AF1-290_GEN
Solar/Wind Helper
0.153
238169AE2-226 GEN1
Solar/Wind Helper
0.701
238170AE2-226 GEN2
Solar/Wind Helper
0.701
235020AA1-095 C
Solar/Wind Helper
0.053
23777901MDS_W4-102
Solar/Wind Helper
0.177
237002AB1-128_GEN
Solar/Wind Helper
0.443
237034AC2-136 C
Solar/Wind Helper
0.227
235063AE1-101 C2
Solar/Wind Helper
1.659
237001AB1-127_GEN
Solar/Wind Helper
0.442
23777801MSM_W1-116
Solar/Wind Helper
0.114
237025AB1-124 C
Solar/Wind Helper
0.164
237006AB1-125 GEN
Solar/Wind Helper
0.123
226929AD2-058 GEN
Solar/Wind Helper
0.099
205916AD1-020 GEN
Solar/Wind Helper
1.713
20390526W1-045 C
Solar/Wind Helper
0.35
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
233987AB2-037 GEN
Solar/Wind Helper
2.342
233933AB2-153 GEN
Solar/Wind Helper
0.232
233944AB2-135 GEN
Solar/Wind Helper
0.588
232424Y1-079 C
Solar/Wind Helper
0.116
234036AF2-325 C
Solar/Wind Helper
0.042
233946AB2-136 GEN
Solar/Wind Helper
0.568
233901CHERRYDALE C
Solar/Wind Helper
0.232
232408W1-005 C
Solar/Wind Helper
0.507
232410W1-006 C
Solar/Wind Helper
0.507
233939AC1-091 C
Solar/Wind Helper
0.35
233970AC1-092 C
Solar/Wind Helper
0.35
315651AD1-115 GEN
Solar/Wind Helper
0.785
316447AC1-158 HLD
Solar/Wind Helper
2.845
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.04
219921AF1-264
Solar/Wind Helper
0.051
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.082
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.19
20716928W4-060COL
Solar/Wind Helper
0.051
218440SUMMTASSOC C
Solar/Wind Helper
0.016
20673828FLE_V3-070
Solar/Wind Helper
0.09
207442AE1-156 GEN
Solar/Wind Helper
0.326
20676128MHD_W3-029
Solar/Wind Helper
0.096
20671828STAW2-080
Solar/Wind Helper
0.027
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
207471AF2-354 C
Solar/Wind Helper
0.168
20674928WA_W3-044
Solar/Wind Helper
0.098
20676228FRD_X1-012
Solar/Wind Helper
0.092
964851AG1-348 GEN
Solar/Wind Helper
0.081
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.074
211065PSPA IPP
Solar/Wind Helper
0.151
211065PSPA IPP
Solar/Wind Helper
0.151
LAGNLTFEXP_LAGN->PJM
CLTF
14.837
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.802
TVALTFEXP_TVA->PJM
CLTF
7.293
CPLELTFEXP_CPLE->PJM
CLTF
0.624
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.816
NYPJM->LTFIMP_NY
CLTF
4.797
LGEELTFEXP_LGEE->PJM
CLTF
6.749
WECLTFEXP_WEC->PJM
CLTF
3.825
AG2-052LTFEXP_AG2-052->PJM
LTF
0.24
AH1-155LTFEXP_AH1-155->PJM
LTF
0.359
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.078
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.1
MECLTFEXP_MEC->PJM
CLTF
15.901
SIGELTFEXP_SIGE->PJM
CLTF
0.505

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P1-2_MP-500-008A_SRT-SL


Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P1-2_MP-500-008A_SRT-SL
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:125.38 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4754.33
MW Contribution:14.34
Bus #Bus NameTypeMW Contribution
972239AH1-704 GEN
50/50
2.78
962771AG1-126 GEN
Solar/Wind Harmer
33.269
270459AD2-067 GEN
Solar/Wind Harmer
0
270054AF2-122 C O1
Solar/Wind Harmer
0.007
961821AG1-024 GEN
Solar/Wind Harmer
4.91
270520AE2-214 GEN
Solar/Wind Harmer
0.013
270284AF1-227 GEN1
Solar/Wind Harmer
0.01
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
253383AE2-342_GEN
Solar/Wind Harmer
0.003
241973AD2-163_GEN1
Solar/Wind Harmer
0.006
945631AF1-228 GEN
Solar/Wind Harmer
0
943861AF1-054 GEN
Solar/Wind Harmer
3.02
943851AF1-053 GEN
Solar/Wind Harmer
2.092
270156DARBY CT1
Adder
10.05
270157DARBY CT2
Adder
10.026
270158DARBY CT3
Adder
9.866
270578AF1-285 GEN2
Solar/Wind Harmer
0.518
970689AG2-444 GEN
Solar/Wind Harmer
15.861
270432AC2-029 GEN
Solar/Wind Harmer
3.428
940611AE2-048 GEN
Solar/Wind Harmer
18.967
941391AE2-136 GEN
Solar/Wind Harmer
10.684
270302AB2-170 GEN
Solar/Wind Harmer
0.005
270317AD1-130_GEN
Solar/Wind Harmer
0.011
971653AH1-327 GEN
Solar/Wind Harmer
1.08
270269AC2-059
Solar/Wind Harmer
0.004
241972AD1-140 GEN
Solar/Wind Harmer
0.824
970179AG2-119 GEN
Solar/Wind Harmer
6.658
270340AC2-060 GEN
Solar/Wind Harmer
0.009
970879AG2-548 GEN
Solar/Wind Harmer
6.645
253372AE2-315 SEC3
Adder
1.989
253372AE2-315 SEC3
Adder
1.989
25306009OHH W.
Adder
3.018
253349AC2-067 GEN
Solar/Wind Harmer
2.296
253400AC2-068 GEN
Solar/Wind Harmer
0.923
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
0.92
965051AG1-369 GEN
Solar/Wind Harmer
3.609
971567AH1-282 GEN
Solar/Wind Harmer
10.843
247607V1-011 GEN
Solar/Wind Harmer
0.001
965041AG1-368 GEN
Solar/Wind Harmer
7.21
971989AH1-539 GEN
Solar/Wind Harmer
3.109
963791AG1-232 GEN
Solar/Wind Harmer
9.689
24729505KEY G4
Adder
6.671
270071AF1-092 GEN
Solar/Wind Harmer
13.737
270024AE2-089 GEN
Solar/Wind Harmer
0.008
971985AH1-537 GEN
Solar/Wind Harmer
2.123
965101AG1-375 GEN
Solar/Wind Harmer
7.135
270297AD1-101 GEN
Solar/Wind Harmer
0.002
270367AC2-061_GEN
Solar/Wind Harmer
0.006
971673AH1-337 GEN
Solar/Wind Harmer
4.631
971029AG2-637 GEN
Solar/Wind Harmer
10.686
270543AE2-219 C
Solar/Wind Harmer
0.004
252524AE2-267 GEN
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
9.002
25196308WSDLE2
Adder
8.924
25196208WSDLE1
Adder
8.902
25196708WSDLE6
Adder
8.879
25196508WSDLE4
Adder
8.656
945581AF1-223 GEN
Solar/Wind Harmer
0.001
971347AH1-153 GEN
Solar/Wind Harmer
10.632
971609AH1-304 GEN
Solar/Wind Harmer
1.157
270240V3-007_GEN2
Solar/Wind Harmer
0.002
970115AG2-085 GEN
Solar/Wind Harmer
2.826
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
270594AE1-207 GEN
Solar/Wind Harmer
7.898
971771AH1-392 GEN
Solar/Wind Harmer
7.046
970289AG2-191 GEN
Solar/Wind Harmer
1.339
971619AH1-309 GEN
Solar/Wind Harmer
3.169
971769AH1-391 GEN
Solar/Wind Harmer
7.844
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
25196108MFTGT2
Adder
1.54
25196108MFTGT2
Adder
1.43
270536AF1-215 GEN2
Solar/Wind Harmer
0.009
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
4.146
971549AH1-272 GEN
Solar/Wind Harmer
14.344
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
8.364
274776LINCOLN ;7U
Adder
8.364
274777LINCOLN ;8U
Adder
8.364
274814UNIV PK N;0U
Adder
4.998
274807UNIV PK N;3U
Adder
4.987
274805UNIV PK N;1U
Adder
4.965
274811UNIV PK N;7U
Adder
4.954
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
972037AH1-567 GEN1
Adder
0.181
960591AF2-350 GEN
Solar/Wind Harmer
6.884
274827FISK ;RP
Adder
7.655
972227AH1-698 GEN1
Adder
2.573
963841AG1-237 GEN
Solar/Wind Harmer
2.978
274687WILL CNTY;4U
Adder
27.495
274687WILL CNTY;4U
Adder
27.495
274675JOLIET 29;7U
Adder
30.175
274675JOLIET 29;7U
Adder
29.097
972163AH1-664 GEN
Solar/Wind Harmer
7.639
972165AH1-665 GEN
Solar/Wind Harmer
6.118
274731ELWOOD EC;2P
Adder
16.163
274733ELWOOD EC;3P
Adder
16.163
274735ELWOOD EC;4P
Adder
16.163
274728ELWOOD EC;5P
Adder
16.163
970833AG2-524 GEN
Solar/Wind Harmer
7.542
970833AG2-524 GEN
Solar/Wind Harmer
5.028
945641AF1-229 GEN
Solar/Wind Harmer
0.001
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
276868AE1-113 GEN
Solar/Wind Harmer
1.363
276882AE2-255 GEN
Solar/Wind Harmer
0.794
238109AE1-109 GEN2
Solar/Wind Helper
0.106
238110AE1-109 GEN3
Solar/Wind Helper
0.106
238152AF2-075_GEN
Solar/Wind Helper
0.683
23546401DTGZ2-030
Solar/Wind Helper
0.086
238208AF1-136 C
Solar/Wind Helper
0.211
238126S14_GEN_1
Solar/Wind Helper
0.766
237085AD2-009_GEN
Solar/Wind Helper
1.588
3138216PACIFIC
Solar/Wind Helper
0.043
316411AF1-147_GEN1
Solar/Wind Helper
0.86
316415AF1-147_GEN2
Solar/Wind Helper
0.86
959381AF2-229 GEN
Solar/Wind Helper
0.345
23750501ELLIOTTS
Solar/Wind Helper
0.571
3141426STAFORD
Solar/Wind Helper
0.051
960921AF2-383 GEN
Solar/Wind Helper
0.352
205943AE1-185 GEN
Solar/Wind Helper
0.492
205956AE1-196_GEN
Solar/Wind Helper
0.492
24318805MLG1
50/50
9.842
23559001PLEAS1
50/50
5.385
270051AF1-062 GEN
50/50
11.434
970153AG2-106 GEN
Solar/Wind Harmer
21.245
961921AG1-034 GEN
Solar/Wind Harmer
7.364
241955AC1-078 GEN
Solar/Wind Harmer
0.007
241974AD2-163_GEN2
Solar/Wind Harmer
0.006
942051AE2-217 GEN
Solar/Wind Harmer
14.169
24721905FLATG4
Adder
22.865
970605AG2-385 GEN
Solar/Wind Harmer
4.731
270391AF1-285 GEN3
Solar/Wind Harmer
0.518
253338AC1-165 GEN
Solar/Wind Harmer
0.003
253333AC1-068 GEN
Solar/Wind Harmer
0.012
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270273AD2-016 GEN
Solar/Wind Harmer
0.792
972173AH1-669 GEN
Solar/Wind Harmer
3.811
270512AE1-227 GEN2
Solar/Wind Harmer
1.904
270291AC1-194 GEN
Solar/Wind Harmer
5.884
253415AE1-040 GEN
Solar/Wind Harmer
0.003
970065AG2-057 GEN
Solar/Wind Harmer
0.735
253370AE2-315 SEC1
Adder
2.103
253371AE2-315 SEC2
Adder
1.989
970191AG2-125 GEN
Solar/Wind Harmer
1.876
253406AD2-031_GEN
Solar/Wind Harmer
0.543
270491AE1-102 GEN2
Solar/Wind Harmer
0.945
270377AD1-106 GEN
Solar/Wind Harmer
2.761
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.047
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
9.394
959331AF2-224 GEN
Solar/Wind Harmer
5.057
965021AG1-366 GEN
Solar/Wind Harmer
2.408
270588AE1-091_GEN
Solar/Wind Harmer
5.649
971191AH1-055 GEN
Solar/Wind Harmer
18.515
944531AF1-118 GEN
Solar/Wind Harmer
32.203
270043AE2-236 GEN
Solar/Wind Harmer
4.607
270258AD1-119 GEN
Solar/Wind Harmer
0.002
971617AH1-308 GEN
Solar/Wind Harmer
5.953
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
10.684
270404AC1-167 GEN
Solar/Wind Harmer
0.003
25196608WSDLE5
Adder
8.745
252510AF1-249 C
Solar/Wind Harmer
0.055
970031AG2-029 GEN
Solar/Wind Harmer
4.625
25194608D.CRK4
Adder
1.676
270222AC2-111 GEN
Solar/Wind Harmer
3.603
970513AG2-328 GEN
Solar/Wind Harmer
3.076
970517AG2-330 GEN
Solar/Wind Harmer
18.457
970349AG2-230 GEN
Solar/Wind Harmer
10.632
946031AF1-268 GEN
Solar/Wind Harmer
6.74
958821AF2-173 GEN
Solar/Wind Harmer
9.902
270004AE1-209 GEN
Solar/Wind Harmer
1.532
270437AC2-090 C
Solar/Wind Harmer
0.003
247643Z2-116 C
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.775
970291AG2-192 GEN
Solar/Wind Harmer
0.705
945111AF1-176 GEN
Solar/Wind Harmer
5.709
247642Z2-115 C
Solar/Wind Harmer
0.003
24642205MAYFLWER
Adder
0.641
24441205WTRV SLR C
Solar/Wind Harmer
0
25196008MFTGT1
Adder
1.353
270356AE2-297 GEN
Solar/Wind Harmer
0.009
970217AG2-149 GEN
Solar/Wind Harmer
6.066
247604X1-042
Adder
0.418
270535AF1-215 GEN1
Solar/Wind Harmer
0.009
964401AG1-302 GEN
Solar/Wind Harmer
0.001
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.935
970243AG2-164 GEN
Solar/Wind Harmer
4.047
970519AG2-331 GEN
Solar/Wind Harmer
17.988
970699AG2-449 GEN
Solar/Wind Harmer
1.73
274752CRETE EC ;2U
Adder
8.172
274753CRETE EC ;3U
Adder
8.172
274772LINCOLN ;3U
Adder
8.364
274724RIVER EC ;11
Adder
17.549
958171AF2-111 GEN
Solar/Wind Harmer
17.278
274802UNIV PARK;5U
Adder
5.755
276806AD2-047 C O1
Solar/Wind Harmer
3.901
970941AG2-585 GEN
Solar/Wind Harmer
8.605
274826FISK ;BP
Adder
10.802
24728705AND G3
Adder
7.914
24728505AND G1
Adder
3.784
274800UNIV PARK;3U
Adder
5.751
972038AH1-567 GEN2
Adder
0.36
972228AH1-698 GEN2
Adder
3.654
972167AH1-666 GEN
Solar/Wind Harmer
5.505
276897AD1-100 C
Solar/Wind Harmer
0.009
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
22.464
274676JOLIET 29;8U
Adder
29.097
274729ELWOOD EC;1P
Adder
16.163
274730ELWOOD EC;6P
Adder
13.491
276893AG1-478 C
Solar/Wind Harmer
0.272
270541AE2-072 C
Solar/Wind Harmer
0.009
943121AE2-341 GEN
Solar/Wind Harmer
11.459
943591AF1-030 GEN
Solar/Wind Harmer
7.62
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
276805AD2-038 GEN
Solar/Wind Harmer
0.002
964991AG1-363 GEN
Solar/Wind Helper
4.969
316097T157 G90
Solar/Wind Helper
1.455
23750701CROSSCHOOL
Solar/Wind Helper
1.397
238148AE2-230_GEN2
Solar/Wind Helper
0.48
238127S14_GEN_2
Solar/Wind Helper
0.766
238118U2-030_1
Solar/Wind Helper
0.314
237080AD1-060 GEN
Solar/Wind Helper
0.33
237038AE2-054 C
Solar/Wind Helper
0.262
235062AE1-101 C1
Solar/Wind Helper
1.6
23779801AA1-109
Solar/Wind Helper
0.187
223401AF1-299 GEN
Solar/Wind Helper
0.355
316006AB2-029 C
Solar/Wind Helper
0.113
966131AG1-482 GEN
Solar/Wind Helper
0.132
237048AF1-022 C
Solar/Wind Helper
0.159
233930AB2-032 GEN
Solar/Wind Helper
0.368
233915AB1-141 GEN
Solar/Wind Helper
0.486
232422X3-066 FULL
Solar/Wind Helper
0.11
232426Y1-080 FULL
Solar/Wind Helper
0.038
233964AF2-378 GEN
Solar/Wind Helper
0.04
233998TM1NIN_3.36
Solar/Wind Helper
0.253
232404W1-003 C
Solar/Wind Helper
0.49
232428Y3-058 C
Solar/Wind Helper
0.327
232434Z2-077 GEN
Solar/Wind Helper
0.123
233954AC2-188 GEN
Solar/Wind Helper
0.225
233950AC2-186 GEN
Solar/Wind Helper
0.112
233972AC1-094 C
Solar/Wind Helper
0.292
316045AC1-158 PL2
Solar/Wind Helper
4.009
230511AF1-262
Solar/Wind Helper
0.014
230434AG1-499 GEN
Solar/Wind Helper
0.222
228728W1-130C
Solar/Wind Helper
0.052
219258KINSLEYDEP C
Solar/Wind Helper
0.074
219904AC1-010 C
Solar/Wind Helper
0.058
218660EHAMPSOLAR C
Solar/Wind Helper
0.032
219907AC1-030 C
Solar/Wind Helper
0.033
219686LUMSOLAR_N C
Solar/Wind Helper
0.038
219304NAMERICA C
Solar/Wind Helper
0.127
316254AC1-120 GEN1
Solar/Wind Helper
1.026
20720728JCB_W1-129
Solar/Wind Helper
0.055
207445AB1-138_GEN
Solar/Wind Helper
0.101
963711AG1-223 GEN
Solar/Wind Helper
0.062
20714828MDF_W3-079
Solar/Wind Helper
0.126
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.299
20715228NPK_W1-113
Solar/Wind Helper
0.075
205932AD2-116_GEN
Solar/Wind Helper
0.492
233935AB2-179 C
Solar/Wind Helper
1.227
232436AB1-176 C
Solar/Wind Helper
0.043
233923SMA
Solar/Wind Helper
0.927
233990AG1-397 GEN
Solar/Wind Helper
0.261
234033AF1-007_GEN
Solar/Wind Helper
6.787
232432Z2-076 GEN
Solar/Wind Helper
0.065
964001AG1-254 GEN
Solar/Wind Helper
0.924
228754AB1-001 C
Solar/Wind Helper
0.025
227927V4-067C
Solar/Wind Helper
0.01
219914AD2-027 C
Solar/Wind Helper
0.111
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.038
219607WPEMNERT C
Solar/Wind Helper
0.077
214067T20SOLAR
Solar/Wind Helper
0.011
203975AE1-071-GEN
Solar/Wind Helper
2.41
20715728PEM_W1-119
Solar/Wind Helper
0.093
20715828PEM_W1-120
Solar/Wind Helper
0.093
207459AE1-142 C O1
Solar/Wind Helper
0.28
316164AC1-076 GEN
Solar/Wind Helper
1.062
219620RIDERU C
Solar/Wind Helper
0.001
270166AC1-044 GEN3
50/50
6.869
23559101PLEAS2
50/50
5.385
270122AB2-093 CT
50/50
3.689
962761AG1-125 GEN
Solar/Wind Harmer
33.269
970149AG2-104 GEN
Solar/Wind Harmer
35.932
970155AG2-107 GEN
Solar/Wind Harmer
21.245
270349AD2-093_GEN
Solar/Wind Harmer
0.006
24721705FLATG2
Adder
22.865
270159DARBY CT4
Adder
9.89
970593AG2-378 GEN
Solar/Wind Harmer
1.75
270223U2-072_GEN1
Solar/Wind Harmer
0.001
253343AC1-166 GEN
Solar/Wind Harmer
0.003
253325AC1-069 GEN
Solar/Wind Harmer
0.012
270462AD2-086
Solar/Wind Harmer
0.016
971995AH1-542 GEN
Solar/Wind Harmer
2.81
270263AC1-001 GEN
Solar/Wind Harmer
0.758
270510AE1-227 GEN1
Solar/Wind Harmer
1.904
241813AF1-122_GEN
Solar/Wind Harmer
3.294
25326309TAIT D
Adder
1.153
960071AF2-298 GEN
Solar/Wind Harmer
3.651
253370AE2-315 SEC1
Adder
2.103
253371AE2-315 SEC2
Adder
1.989
927014AC1-188 GEN
Solar/Wind Harmer
0.004
246936BC-WTG1
Solar/Wind Harmer
0.295
270489AE1-102 GEN1
Solar/Wind Harmer
0.945
965421AG1-410 GEN
Solar/Wind Harmer
21.788
247521TR3_G114
Solar/Wind Harmer
0.263
270246TR4_N_V150
Solar/Wind Harmer
0.047
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.226
965011AG1-365 GEN
Solar/Wind Harmer
7.225
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
24695305TIMB G C
Solar/Wind Harmer
0.002
965651AG1-433 GEN
Solar/Wind Harmer
2.096
958861AF2-177 GEN
Solar/Wind Harmer
3.092
247536S-71 GEN
Solar/Wind Harmer
0.287
945371AF1-202 GEN
Solar/Wind Harmer
0.001
25194608D.CRK4
Adder
1.676
270063AE2-323 C
Solar/Wind Harmer
0.006
252507AC2-088 GEN
Solar/Wind Harmer
0.323
970245AG2-165 GEN
Solar/Wind Harmer
3.076
944231AF1-091 GEN
Solar/Wind Harmer
1.885
270005AE1-210 C O1
Solar/Wind Harmer
1.532
965031AG1-367 GEN
Solar/Wind Harmer
7.073
970947AG2-589 GEN
Solar/Wind Harmer
0.236
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.183
970825AG2-519 GEN
Solar/Wind Harmer
2.509
24639705ELKHART HY
Adder
0.155
25196808ZIMRHP
Adder
76.799
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
270032AE2-172
Solar/Wind Harmer
4.701
970291AG2-192 GEN
Solar/Wind Harmer
0.916
945111AF1-176 GEN
Solar/Wind Harmer
12.568
270505AE1-170 C O1
Solar/Wind Harmer
7.393
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.67
247522W1-056 GEN
Solar/Wind Harmer
0.001
276903AD2-071 C
Solar/Wind Harmer
7.842
25196008MFTGT1
Adder
1.397
970773AG2-487 GEN
Solar/Wind Harmer
1.237
970373AG2-245 GEN
Solar/Wind Harmer
14.699
970515AG2-329 GEN
Solar/Wind Harmer
18.197
270055AF2-134 C O1
Solar/Wind Harmer
0.005
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.071
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.706
24791305MDL-5G
Solar/Wind Harmer
0.001
970333AG2-219 GEN
Solar/Wind Harmer
4.947
274751CRETE EC ;1U
Adder
8.172
274754CRETE EC ;4U
Adder
8.172
274773LINCOLN ;4U
Adder
8.364
274774LINCOLN ;5U
Adder
8.364
274723RIVER EC ;12
Adder
17.756
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.954
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
276776AD2-060 GEN
Solar/Wind Harmer
0.719
24728605AND G2
Adder
3.784
274801UNIV PARK;4U
Adder
5.751
941551AE2-152 GEN
Solar/Wind Harmer
0.001
945681AF1-233 GEN
Solar/Wind Harmer
12.962
274676JOLIET 29;8U
Adder
30.175
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
963741AG1-226 GEN
Solar/Wind Harmer
16.202
939401AE1-172 GEN
Solar/Wind Harmer
5.109
276691AA1-018 GEN1
Solar/Wind Harmer
0.827
276901AD2-066 C O1
Solar/Wind Harmer
0.007
316095T157 G97
Solar/Wind Helper
1.455
23583801GRNGAP
Solar/Wind Helper
5.418
238108AE1-109 GEN1
Solar/Wind Helper
0.106
238185AF2-356 C
Solar/Wind Helper
2.425
238147AE2-230_GEN1
Solar/Wind Helper
0.478
238149AF1-291A_GEN
Solar/Wind Helper
0.137
235531U2-073 GEN
Solar/Wind Helper
3.034
235054AD2-180 GEN
Solar/Wind Helper
1.839
237061AD1-155 GEN
Solar/Wind Helper
0.051
238117U2-030
Solar/Wind Helper
0.314
238221AF1-254 C O1
Solar/Wind Helper
0.265
235067AD1-061 GEN
Solar/Wind Helper
0.478
237030AB1-096 C
Solar/Wind Helper
0.068
3141196NOKESVL
Solar/Wind Helper
0.999
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.335
223402AF1-300 C
Solar/Wind Helper
0.355
23751201ROTHROCK
Solar/Wind Helper
0.694
23562501BACKB
Solar/Wind Helper
0.842
205917AD1-020 ES
Solar/Wind Helper
0.356
233982AB2-133 GEN
Solar/Wind Helper
0.346
233918AB1-142 GEN
Solar/Wind Helper
0.486
233994AC2-023 GEN
Solar/Wind Helper
0.929
233996TM1833_GEN
Solar/Wind Helper
0.253
233997TMININ_4.2
Solar/Wind Helper
0.253
232406W1-004 FULL
Solar/Wind Helper
0.49
233940AF2-379 C
Solar/Wind Helper
0.06
234015AF2-250 C
Solar/Wind Helper
0.037
233952AC2-187 GEN
Solar/Wind Helper
0.225
233971AC1-093 C
Solar/Wind Helper
0.346
316044AC1-158 PL1
Solar/Wind Helper
1.252
316450AC1-158 RIC
Solar/Wind Helper
0.334
230430AE1-229_GEN
Solar/Wind Helper
3.26
230415AB2-049 C
Solar/Wind Helper
0.029
228729W2-030 C
Solar/Wind Helper
0.107
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.053
219912AD2-042 GEN
Solar/Wind Helper
0.145
219291REEVESSOUT C
Solar/Wind Helper
0.011
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.111
316170AC1-121 GEN2
Solar/Wind Helper
0.342
959561AF2-247 GEN
Solar/Wind Helper
0.02
20720828JCB_W4-025
Solar/Wind Helper
0.061
20716028EGP_W2-019
Solar/Wind Helper
0.018
20715028HAN_X4-015
Solar/Wind Helper
0.055
270119AB2-067 GEN1
50/50
6.869
270120AB2-067 GEN2
50/50
6.869
24318905MLG2
50/50
6.89
270471AD2-092_GEN
Solar/Wind Harmer
0.006
942861AE2-305 GEN
Solar/Wind Harmer
6.118
970077AG2-063 GEN
Solar/Wind Harmer
4.471
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
938701AE1-092 GEN
Solar/Wind Harmer
12.484
971655AH1-328 GEN
Solar/Wind Harmer
2.758
964601AG1-323 GEN
Solar/Wind Harmer
3.106
964601AG1-323 GEN
Solar/Wind Harmer
2.071
270518AE2-148 GEN
Solar/Wind Harmer
0.667
972269AH1-719 GEN
Adder
2.501
972159AH1-661 GEN
Adder
1.082
253378AE2-206_GEN
Solar/Wind Harmer
0.004
276820AF1-078_GEN
Solar/Wind Harmer
0.002
970329AG2-216 GEN
Solar/Wind Harmer
3.237
971199AH1-059 GEN
Solar/Wind Harmer
2.99
241960AC2-195 GEN
Solar/Wind Harmer
0.006
970935AG2-582 GEN
Adder
242.403
25326509SID D
Adder
1.4
971073AG2-665 GEN
Solar/Wind Harmer
6.645
25326109MON D
Adder
1.391
971201AH1-060 GEN
Solar/Wind Harmer
1.471
25322209TAIT E
Adder
10.262
25322209TAIT E
Adder
10.031
253370AE2-315 SEC1
Adder
2.103
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
246938BC-WTG3
Solar/Wind Harmer
0.263
246937BC-WTG2
Solar/Wind Harmer
0.295
971231AH1-075 GEN
Solar/Wind Harmer
0.833
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
970611AG2-400 GEN
Solar/Wind Harmer
7.225
970627AG2-408 GEN
Solar/Wind Harmer
2.167
270007AE1-245 C
Solar/Wind Harmer
0.002
970623AG2-406 GEN
Solar/Wind Harmer
1.309
962581AG1-107 GEN
Solar/Wind Harmer
0.001
25183208HLCRTG
Solar/Wind Harmer
0.011
944541AF1-119 GEN
Solar/Wind Harmer
0.479
960971AF2-388 GEN
Solar/Wind Harmer
4.192
942221AE2-234 GEN
Solar/Wind Harmer
0.036
252519AF1-045_GEN
Solar/Wind Harmer
6.204
252516AE2-318_GEN
Solar/Wind Harmer
5.503
970621AG2-405 GEN
Solar/Wind Harmer
1.305
247621Y3-024
Adder
0.246
970883AG2-550 GEN
Solar/Wind Harmer
7.123
970885AG2-551 GEN
Solar/Wind Harmer
2.374
270201AC2-176 GEN
Solar/Wind Harmer
0.001
25194408D.CRK1
Adder
7.711
25194508D.CRK3
Adder
1.442
964611AG1-324 GEN
Solar/Wind Harmer
0.534
252509AD1-136 GEN
Solar/Wind Harmer
0.036
970321AG2-212 GEN
Solar/Wind Harmer
3.076
270599AE1-208 GEN
Solar/Wind Harmer
6.495
270031AE2-169
Solar/Wind Harmer
3.897
270383AD1-128 GEN
Solar/Wind Harmer
0.004
270186AC1-089 GEN
Solar/Wind Harmer
0.004
247620Y3-023
Adder
0.466
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
970825AG2-519 GEN
Solar/Wind Harmer
7.834
960441AF2-335 GEN
Solar/Wind Harmer
7.065
270216AD2-079_GEN
Solar/Wind Harmer
0.001
971613AH1-306 GEN
Solar/Wind Harmer
3.385
24728805RICHG1
Adder
3.82
24728905RICHG2
Adder
3.82
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
14.072
961051AF2-396 GEN
Solar/Wind Harmer
9.381
270526AF1-158 GEN
Solar/Wind Harmer
0.009
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
8.77
965791AG1-447 GEN
Solar/Wind Harmer
6.431
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
970239AG2-162 GEN
Solar/Wind Harmer
1.73
274770LINCOLN ;1U
Adder
8.364
274771LINCOLN ;2U
Adder
8.364
274808UNIV PK N;4U
Adder
4.933
966841AG1-555 GEN
Solar/Wind Harmer
0.781
274803UNIV PARK;6U
Adder
5.755
274888KELLY CRK;1U
Solar/Wind Harmer
0.404
274887GEN-1.85
Solar/Wind Harmer
0.181
276843GEN-1.7
Solar/Wind Harmer
0.223
958011AF2-095 GEN
Solar/Wind Harmer
9.913
972259AH1-714 GEN
Adder
18.805
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
970241AG2-163 GEN
Solar/Wind Harmer
3.993
958481AF2-142 GEN
Solar/Wind Harmer
10.238
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.923
971573AH1-285 GEN
Solar/Wind Harmer
1.271
971677AH1-339 GEN
Solar/Wind Harmer
0.768
958491AF2-143 GEN
Solar/Wind Harmer
10.205
274879MINONK ;1U
Solar/Wind Harmer
0.287
238175AF1-290_GEN
Solar/Wind Helper
0.148
238169AE2-226 GEN1
Solar/Wind Helper
0.677
238170AE2-226 GEN2
Solar/Wind Helper
0.677
238120AE2-309 GEN
Solar/Wind Helper
0.487
235020AA1-095 C
Solar/Wind Helper
0.051
23777901MDS_W4-102
Solar/Wind Helper
0.171
23585401KL_K28_T16
Solar/Wind Helper
1.328
237034AC2-136 C
Solar/Wind Helper
0.219
237002AB1-128_GEN
Solar/Wind Helper
0.427
235063AE1-101 C2
Solar/Wind Helper
1.6
237001AB1-127_GEN
Solar/Wind Helper
0.426
23777801MSM_W1-116
Solar/Wind Helper
0.11
237025AB1-124 C
Solar/Wind Helper
0.159
237006AB1-125 GEN
Solar/Wind Helper
0.119
226929AD2-058 GEN
Solar/Wind Helper
0.096
205916AD1-020 GEN
Solar/Wind Helper
1.656
20390526W1-045 C
Solar/Wind Helper
0.338
208835TUHI V3-051
Solar/Wind Helper
0.023
208835TUHI V3-051
Solar/Wind Helper
0.023
233987AB2-037 GEN
Solar/Wind Helper
2.264
233933AB2-153 GEN
Solar/Wind Helper
0.225
232424Y1-079 C
Solar/Wind Helper
0.112
233944AB2-135 GEN
Solar/Wind Helper
0.569
233946AB2-136 GEN
Solar/Wind Helper
0.549
234036AF2-325 C
Solar/Wind Helper
0.041
233901CHERRYDALE C
Solar/Wind Helper
0.225
232408W1-005 C
Solar/Wind Helper
0.49
232410W1-006 C
Solar/Wind Helper
0.49
233939AC1-091 C
Solar/Wind Helper
0.338
233970AC1-092 C
Solar/Wind Helper
0.338
315651AD1-115 GEN
Solar/Wind Helper
0.76
316447AC1-158 HLD
Solar/Wind Helper
2.756
230433AD2-135 GEN
Solar/Wind Helper
0.016
230407AD2-065 C
Solar/Wind Helper
0.039
219921AF1-264
Solar/Wind Helper
0.049
219615MILLCREEK C
Solar/Wind Helper
0.026
963401AG1-189 GEN
Solar/Wind Helper
0.054
963391AG1-188 GEN
Solar/Wind Helper
0.079
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.183
219276PARKLANDSO C
Solar/Wind Helper
0.086
20714528FRN_Y2-051
Solar/Wind Helper
0.055
20720528MAN_W1-024
Solar/Wind Helper
0.027
971997AH1-543 GEN
Solar/Wind Harmer
1.86
LAGNLTFEXP_LAGN->PJM
CLTF
14.268
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.432
TVALTFEXP_TVA->PJM
CLTF
7.011
CPLELTFEXP_CPLE->PJM
CLTF
0.567
CBM West 2LTFEXP_CBM-W2->PJM
CBM
108.576
NYPJM->LTFIMP_NY
CLTF
4.628
LGEELTFEXP_LGEE->PJM
CLTF
6.497
WECLTFEXP_WEC->PJM
CLTF
3.686
AG2-052LTFEXP_AG2-052->PJM
LTF
0.231
AH1-155LTFEXP_AH1-155->PJM
LTF
0.346
CBM West 1LTFEXP_CBM-W1->PJM
CBM
137.982
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.984
MECLTFEXP_MEC->PJM
CLTF
15.319
SIGELTFEXP_SIGE->PJM
CLTF
0.486

Details for 05MADDOX-05E LIMA 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MADDOX-05E LIMA 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.12 %
Rating:2246.0 MVA
Rating Type:B
MVA to Mitigate:2697.98
MW Contribution:9.68
Bus #Bus NameTypeMW Contribution
965431AG1-411 GEN
50/50
45.318
24727105RPMNG2
50/50
3.312
970583AG2-370 GEN
50/50
2.791
270491AE1-102 GEN2
Solar/Wind Harmer
3.72
959331AF2-224 GEN
Solar/Wind Harmer
9.596
965021AG1-366 GEN
Solar/Wind Harmer
4.57
970031AG2-029 GEN
Solar/Wind Harmer
5.428
270043AE2-236 GEN
Solar/Wind Harmer
5.157
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.046
944531AF1-118 GEN
Solar/Wind Harmer
31.245
971617AH1-308 GEN
Solar/Wind Harmer
5.12
247643Z2-116 C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
4.761
970349AG2-230 GEN
Solar/Wind Harmer
8.606
24642205MAYFLWER
Adder
0.519
24441205WTRV SLR C
Solar/Wind Harmer
0
970513AG2-328 GEN
Solar/Wind Harmer
2.283
970517AG2-330 GEN
Solar/Wind Harmer
13.699
274752CRETE EC ;2U
Adder
6.177
274753CRETE EC ;3U
Adder
6.177
274724RIVER EC ;11
Adder
13.226
247604X1-042
Adder
0.309
270535AF1-215 GEN1
Solar/Wind Harmer
0.006
274772LINCOLN ;3U
Adder
6.227
274802UNIV PARK;5U
Adder
4.274
274826FISK ;BP
Adder
8.017
274800UNIV PARK;3U
Adder
4.262
972038AH1-567 GEN2
Adder
0.267
276806AD2-047 C O1
Solar/Wind Harmer
2.886
970941AG2-585 GEN
Solar/Wind Harmer
6.366
964401AG1-302 GEN
Solar/Wind Harmer
0.001
972228AH1-698 GEN2
Adder
2.696
970707AG2-453 GEN
Solar/Wind Harmer
16.532
276897AD1-100 C
Solar/Wind Harmer
0.007
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
21.371
276893AG1-478 C
Solar/Wind Harmer
0.199
274729ELWOOD EC;1P
Adder
11.842
274730ELWOOD EC;6P
Adder
11.843
274734ELWOOD EC;8P
Adder
11.843
274736ELWOOD EC;9P
Adder
11.843
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
943121AE2-341 GEN
Solar/Wind Harmer
8.328
943591AF1-030 GEN
Solar/Wind Harmer
5.538
24727205RPMNG3
50/50
3.285
971599AH1-298 GEN
50/50
10.265
24729505KEY G4
50/50
6.681
957201AF2-014 GEN
Solar/Wind Harmer
0.002
270435AC2-044 GEN
Solar/Wind Harmer
3.625
963791AG1-232 GEN
Solar/Wind Harmer
11.533
965041AG1-368 GEN
Solar/Wind Harmer
8.372
270071AF1-092 GEN
Solar/Wind Harmer
14.295
965051AG1-369 GEN
Solar/Wind Harmer
3.565
270024AE2-089 GEN
Solar/Wind Harmer
0.007
965101AG1-375 GEN
Solar/Wind Harmer
6.034
971771AH1-392 GEN
Solar/Wind Harmer
5.793
971347AH1-153 GEN
Solar/Wind Harmer
8.606
971619AH1-309 GEN
Solar/Wind Harmer
2.577
945581AF1-223 GEN
Solar/Wind Harmer
0
971769AH1-391 GEN
Solar/Wind Harmer
6.222
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971609AH1-304 GEN
Solar/Wind Harmer
0.881
274814UNIV PK N;0U
Adder
3.743
274807UNIV PK N;3U
Adder
3.735
274805UNIV PK N;1U
Adder
3.719
274811UNIV PK N;7U
Adder
3.711
270536AF1-215 GEN2
Solar/Wind Harmer
0.006
274775LINCOLN ;6U
Adder
6.227
274776LINCOLN ;7U
Adder
6.227
274777LINCOLN ;8U
Adder
6.227
972037AH1-567 GEN1
Adder
0.134
274827FISK ;RP
Adder
5.682
960591AF2-350 GEN
Solar/Wind Harmer
5.093
972227AH1-698 GEN1
Adder
1.898
274687WILL CNTY;4U
Adder
20.23
274687WILL CNTY;4U
Adder
20.23
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274675JOLIET 29;7U
Adder
22.163
274675JOLIET 29;7U
Adder
21.371
274731ELWOOD EC;2P
Adder
11.842
274733ELWOOD EC;3P
Adder
11.842
274735ELWOOD EC;4P
Adder
11.842
274728ELWOOD EC;5P
Adder
11.843
970833AG2-524 GEN
Solar/Wind Harmer
5.503
970833AG2-524 GEN
Solar/Wind Harmer
3.669
971611AH1-305 GEN
Solar/Wind Harmer
2.963
274746AC1-111 G10
Adder
3.978
274744AC1-111 GEN8
Adder
3.978
970289AG2-191 GEN
Solar/Wind Harmer
0.932
270594AE1-207 GEN
Solar/Wind Harmer
5.432
276868AE1-113 GEN
Solar/Wind Harmer
0.971
276882AE2-255 GEN
Solar/Wind Harmer
0.566
971177AH1-047 GEN
Solar/Wind Harmer
2.975
971411AH1-196 GEN
Solar/Wind Harmer
7.208
971675AH1-338 GEN
Solar/Wind Harmer
1.873
970115AG2-085 GEN
Solar/Wind Harmer
1.915
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
9.543
274823ROCKFORD ;21
Adder
13.283
276612AE2-035 GEN
Solar/Wind Harmer
0.001
926823AC1-168 GEN
Solar/Wind Harmer
0.802
970169AG2-114 GEN
Solar/Wind Harmer
4.71
971681AH1-341 GEN
Solar/Wind Harmer
7.556
971549AH1-272 GEN
Solar/Wind Harmer
9.681
961011AF2-392 GEN
Solar/Wind Harmer
2.722
957751AF2-069 GEN
Solar/Wind Harmer
0.152
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
276655WTG1_EQ
Solar/Wind Harmer
0.002
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
4.771
941731AE2-173 GEN
Solar/Wind Harmer
3.786
946321AF1-296 GEN
Solar/Wind Harmer
2.514
963841AG1-237 GEN
Solar/Wind Harmer
1.925
270240V3-007_GEN2
Solar/Wind Harmer
0.001
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.154
276848AB2-070 GEN3
Solar/Wind Harmer
0.153
270543AE2-219 C
Solar/Wind Harmer
0.002
944221AF1-090 GEN
Solar/Wind Harmer
2.247
971029AG2-637 GEN
Solar/Wind Harmer
5.161
971673AH1-337 GEN
Solar/Wind Harmer
2.14
247607V1-011 GEN
Solar/Wind Harmer
0.001
270317AD1-130_GEN
Solar/Wind Helper
4.139
966831AG1-554 GEN
Solar/Wind Helper
0.884
270284AF1-227 GEN1
Solar/Wind Helper
1.894
270286AF1-227 GEN2
Solar/Wind Helper
0.695
270287AF1-227 GEN3
Solar/Wind Helper
0.695
270499AE1-146 GEN
Solar/Wind Helper
1.973
945641AF1-229 GEN
Solar/Wind Helper
0.949
24727005RPMNG1
50/50
3.301
960861AF2-377 GEN
50/50
2.381
970521AG2-332 GEN
50/50
10.716
24639705ELKHART HY
50/50
0.148
246936BC-WTG1
Solar/Wind Harmer
1.161
270489AE1-102 GEN1
Solar/Wind Harmer
3.72
965421AG1-410 GEN
Solar/Wind Harmer
81.572
965011AG1-365 GEN
Solar/Wind Harmer
13.709
270063AE2-323 C
Solar/Wind Harmer
0.006
247521TR3_G114
Solar/Wind Harmer
0.26
270246TR4_N_V150
Solar/Wind Harmer
0.046
944231AF1-091 GEN
Solar/Wind Harmer
1.84
24695305TIMB G C
Solar/Wind Harmer
0.002
965651AG1-433 GEN
Solar/Wind Harmer
1.823
958861AF2-177 GEN
Solar/Wind Harmer
2.615
945111AF1-176 GEN
Solar/Wind Harmer
10.481
270505AE1-170 C O1
Solar/Wind Harmer
6.013
945371AF1-202 GEN
Solar/Wind Harmer
0
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.942
970245AG2-165 GEN
Solar/Wind Harmer
2.283
970373AG2-245 GEN
Solar/Wind Harmer
11.033
274751CRETE EC ;1U
Adder
6.177
274754CRETE EC ;4U
Adder
6.177
274723RIVER EC ;12
Adder
13.388
274812UNIV PK N;8U
Adder
3.711
276164X3-005 C
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0.004
274773LINCOLN ;4U
Adder
6.227
274774LINCOLN ;5U
Adder
6.227
274801UNIV PARK;4U
Adder
4.262
276776AD2-060 GEN
Solar/Wind Harmer
0.532
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
6.6
941551AE2-152 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
22.162
274674JOLIET 9 ;6U
Adder
11.098
274732ELWOOD EC;7P
Adder
11.843
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
6.22
274745AC1-111 GEN9
Adder
3.978
276691AA1-018 GEN1
Solar/Wind Harmer
0.598
274682WAUKEGAN ;7U
Adder
12.642
970291AG2-192 GEN
Solar/Wind Harmer
0.638
274828WAUKEGAN ;BP
Adder
7.76
270005AE1-210 C O1
Solar/Wind Harmer
1.056
965031AG1-367 GEN
Solar/Wind Harmer
4.875
962781AG1-127 GEN
Solar/Wind Harmer
4.624
939401AE1-172 GEN
Solar/Wind Harmer
3.633
276901AD2-066 C O1
Solar/Wind Harmer
0.005
270032AE2-172
Solar/Wind Harmer
3.233
274872LEEDK;1U
Solar/Wind Harmer
0.003
971997AH1-543 GEN
Solar/Wind Harmer
2.531
276861AD2-134 GEN
Solar/Wind Harmer
0.086
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
24791305MDL-5G
Solar/Wind Harmer
0.001
957471AF2-041 GEN
Solar/Wind Harmer
14.315
959081AF2-199 GEN
Solar/Wind Harmer
4.772
971067AG2-660 GEN
Solar/Wind Harmer
1.591
274822ROCKFORD ;11
Adder
13.38
970825AG2-519 GEN
Solar/Wind Harmer
1.686
972235AH1-702 GEN1
Adder
1.714
970819AG2-516 GEN
Solar/Wind Harmer
5.675
970569AG2-363 GEN
Solar/Wind Harmer
14.175
971475AH1-234 GEN
Solar/Wind Harmer
2.289
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
6.232
274766LEE CO EC;7U
Adder
6.158
276903AD2-071 C
Solar/Wind Harmer
5.188
276158O29GEN2
Solar/Wind Harmer
0.001
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.002
274877BISHOP HL;1U
Solar/Wind Harmer
0.154
276726Z2-087_GEN
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
6.361
274854TWINGROVE;U2
Solar/Wind Harmer
0.002
972175AH1-670 GEN
Solar/Wind Harmer
3.579
963741AG1-226 GEN
Solar/Wind Harmer
10.198
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
3.15
247536S-71 GEN
Solar/Wind Harmer
0.171
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
1.633
276615X2-022 GEN
Solar/Wind Harmer
0.043
965911AG1-460 GEN
Solar/Wind Harmer
0.798
24728605AND G2
Adder
2.013
970773AG2-487 GEN
Solar/Wind Harmer
0.599
270445AC2-157 GEN2
Solar/Wind Harmer
0.001
970333AG2-219 GEN
Solar/Wind Harmer
2.176
270462AD2-086
Solar/Wind Helper
3.736
270223U2-072_GEN1
Solar/Wind Helper
0.877
270578AF1-285 GEN2
Solar/Wind Helper
0.594
270391AF1-285 GEN3
Solar/Wind Helper
0.594
247522W1-056 GEN
Solar/Wind Helper
1.179
960841AF2-375 GEN
Solar/Wind Helper
1.188
270349AD2-093_GEN
Solar/Wind Helper
0.862
970615AG2-402 GEN
50/50
4.57
24729405KEY G3
50/50
0.365
24729305KEY G2
50/50
0.359
24729205KEY G1
50/50
0.357
247620Y3-023
50/50
0.459
246938BC-WTG3
Solar/Wind Harmer
1.037
246937BC-WTG2
Solar/Wind Harmer
1.161
970611AG2-400 GEN
Solar/Wind Harmer
13.709
970627AG2-408 GEN
Solar/Wind Harmer
4.113
942221AE2-234 GEN
Solar/Wind Harmer
0.034
944541AF1-119 GEN
Solar/Wind Harmer
0.416
960971AF2-388 GEN
Solar/Wind Harmer
3.647
270216AD2-079_GEN
Solar/Wind Harmer
0.001
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
11.449
961051AF2-396 GEN
Solar/Wind Harmer
7.632
270526AF1-158 GEN
Solar/Wind Harmer
0.007
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
6.819
965791AG1-447 GEN
Solar/Wind Harmer
5.001
270599AE1-208 GEN
Solar/Wind Harmer
4.943
270031AE2-169
Solar/Wind Harmer
2.966
970321AG2-212 GEN
Solar/Wind Harmer
2.283
274808UNIV PK N;4U
Adder
3.694
274770LINCOLN ;1U
Adder
6.227
274771LINCOLN ;2U
Adder
6.227
274803UNIV PARK;6U
Adder
4.274
274888KELLY CRK;1U
Solar/Wind Harmer
0.299
274887GEN-1.85
Solar/Wind Harmer
0.134
276843GEN-1.7
Solar/Wind Harmer
0.165
958011AF2-095 GEN
Solar/Wind Harmer
7.334
972259AH1-714 GEN
Adder
13.842
274674JOLIET 9 ;6U
Adder
11.098
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
971573AH1-285 GEN
Solar/Wind Harmer
0.921
958481AF2-142 GEN
Solar/Wind Harmer
7.4
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.667
274696ROCKY RD ;4P
Adder
8.021
274695ROCKY RD ;2P
Adder
7.836
274693ROCKY RD ;1P
Adder
7.759
274697ROCKY RD ;3P
Adder
2.129
274683WAUKEGAN ;8U
Adder
14.804
274683WAUKEGAN ;8U
Adder
12.479
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
962691AG1-118 GEN
Solar/Wind Harmer
14.613
958491AF2-143 GEN
Solar/Wind Harmer
7.306
970921AG2-575 GEN
Solar/Wind Harmer
4.859
970921AG2-575 GEN
Solar/Wind Harmer
1.62
971613AH1-306 GEN
Solar/Wind Harmer
2.328
274879MINONK ;1U
Solar/Wind Harmer
0.204
942991AE2-321 GEN
Solar/Wind Harmer
5.39
971333AH1-146 GEN
Solar/Wind Harmer
9.601
971335AH1-147 GEN
Solar/Wind Harmer
9.601
960441AF2-335 GEN
Solar/Wind Harmer
4.786
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
971341AH1-150 GEN
Solar/Wind Harmer
9.543
971343AH1-151 GEN
Solar/Wind Harmer
9.543
970825AG2-519 GEN
Solar/Wind Harmer
5.263
274856ECOGROVE ;U1
Solar/Wind Harmer
0.111
276611AD2-172 GEN
Solar/Wind Harmer
0.001
938861AE1-114 GEN
Solar/Wind Harmer
2.658
274764LEE CO EC;5U
Adder
6.246
274765LEE CO EC;6U
Adder
6.246
274762LEE CO EC;3U
Adder
6.232
274763LEE CO EC;4U
Adder
6.173
276603SUBLETTE C
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.349
270201AC2-176 GEN
Solar/Wind Harmer
0.001
972267AH1-718 GEN
Adder
2.761
276741O09 GEN1
Solar/Wind Harmer
0.164
276708O09 GEN2
Solar/Wind Harmer
0.164
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.181
276646AC1-214 GEN2
Solar/Wind Harmer
0.181
966841AG1-555 GEN
Solar/Wind Harmer
0.519
276782AC1-033 GEN
Solar/Wind Harmer
0.001
247621Y3-024
Adder
0.158
960611AF2-352 GEN
Solar/Wind Harmer
1.488
970241AG2-163 GEN
Solar/Wind Harmer
2.514
24379505HDWTR1G C
Solar/Wind Harmer
0.001
270209AC1-174_GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
270383AD1-128 GEN
Solar/Wind Harmer
0.002
276916AD2-100_GEN
Solar/Wind Harmer
8.299
276911AD2-131_GEN
Solar/Wind Harmer
0.547
970883AG2-550 GEN
Solar/Wind Harmer
3.858
970885AG2-551 GEN
Solar/Wind Harmer
1.286
945391AF1-204 GEN
Solar/Wind Harmer
4.094
970623AG2-406 GEN
Solar/Wind Harmer
0.671
270444AC2-157 GEN1
Solar/Wind Harmer
0.001
971587AH1-292 GEN
Solar/Wind Harmer
2.387
270007AE1-245 C
Solar/Wind Harmer
0.001
970239AG2-162 GEN
Solar/Wind Harmer
0.761
270224U2-072_GEN2
Solar/Wind Helper
0.877
270227U2-072_GEN3
Solar/Wind Helper
0.877
270228U2-072_GEN4
Solar/Wind Helper
0.877
270231U2-072_GEN5
Solar/Wind Helper
0.877
270471AD2-092_GEN
Solar/Wind Helper
0.862
253378AE2-206_GEN
Solar/Wind Helper
0.694
276820AF1-078_GEN
Solar/Wind Helper
0.324
241960AC2-195 GEN
Solar/Wind Helper
0.702
247642Z2-115 C
Solar/Wind Harmer
0.002
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
12.642
970289AG2-191 GEN
Solar/Wind Harmer
0.539
970291AG2-192 GEN
Solar/Wind Harmer
0.49
958821AF2-173 GEN
Solar/Wind Harmer
6.825
270004AE1-209 GEN
Solar/Wind Harmer
1.056
276805AD2-038 GEN
Solar/Wind Harmer
0.001
274872LEEDK;1U
Solar/Wind Harmer
0.178
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.512
274855GSG-6 ;RU
Solar/Wind Harmer
0.176
274850MENDOTA H;RU
Solar/Wind Harmer
0.057
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.086
276889AE2-281 GEN
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
4.78
959091AF2-200 GEN
Solar/Wind Harmer
9.543
972236AH1-702 GEN2
Adder
1.491
970571AG2-364 GEN
Solar/Wind Harmer
9.45
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
6.232
274767LEE CO EC;8U
Adder
6.158
946031AF1-268 GEN
Solar/Wind Harmer
4.44
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
6.987
276157O29GEN1
Solar/Wind Harmer
0.746
274878BISHOP HL;2U
Solar/Wind Harmer
0.154
942111AE2-223 GEN
Solar/Wind Harmer
1.477
965931AG1-462 GEN
Solar/Wind Harmer
11.384
274853TWINGROVE;U1
Solar/Wind Harmer
0.002
965091AG1-374 GEN
Solar/Wind Harmer
13.388
959611AF2-252 GEN
Solar/Wind Harmer
1.488
270437AC2-090 C
Solar/Wind Harmer
0.002
276686W4-005 GEN3
Solar/Wind Harmer
0.001
276668AB2-070 GEN1
Solar/Wind Harmer
0.154
971993AH1-541 GEN
Solar/Wind Harmer
1.946
276621W2-048 GEN
Solar/Wind Harmer
0.209
276838X2-022 GEN2
Solar/Wind Harmer
0.233
942481AE2-261 GEN
Solar/Wind Harmer
11.923
970193AG2-126 GEN
Solar/Wind Harmer
5.78
270404AC1-167 GEN
Solar/Wind Harmer
0.002
270258AD1-119 GEN
Solar/Wind Harmer
0.001
24728705AND G3
Adder
4.21
24728505AND G1
Adder
2.013
270356AE2-297 GEN
Solar/Wind Harmer
0.005
970243AG2-164 GEN
Solar/Wind Harmer
1.781
970519AG2-331 GEN
Solar/Wind Harmer
7.913
970699AG2-449 GEN
Solar/Wind Harmer
0.761
270485AE1-090_GEN
Solar/Wind Helper
0.325
942871AE2-306 GEN
Solar/Wind Helper
0.446
270541AE2-072 C
Solar/Wind Helper
0.947
944201AF1-088_MTX
Adder
54.26
957141AF2-008_MTX
Adder
17.407
990792J1392
External Queue
5.474584102630615
990497J1323
External Queue
1.5914489030838013
LAGNLTFEXP_LAGN->PJM
CLTF
5.535
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.203
TVALTFEXP_TVA->PJM
CLTF
2.191
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.893
NYPJM->LTFIMP_NY
CLTF
1.315
LGEELTFEXP_LGEE->PJM
CLTF
1.728
WECLTFEXP_WEC->PJM
CLTF
2.594
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.108
AG2-052LTFEXP_AG2-052->PJM
LTF
0.168
AH1-155LTFEXP_AH1-155->PJM
LTF
0.252
CBM West 1LTFEXP_CBM-W1->PJM
CBM
68.17
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.448
MECLTFEXP_MEC->PJM
CLTF
9.525
SIGELTFEXP_SIGE->PJM
CLTF
0.193

Details for 05MALIS-05VASSEL 765.0 kV Ckt 1 line l/o AP_P1-3_MP-765-501T_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MALIS-05VASSEL 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-501T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:130.8 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:5417.86
MW Contribution:16.34
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
1.721
971599AH1-298 GEN
50/50
12.006
962771AG1-126 GEN
Solar/Wind Harmer
74.429
971347AH1-153 GEN
Solar/Wind Harmer
13.852
270071AF1-092 GEN
Solar/Wind Harmer
17.275
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
274775LINCOLN ;6U
Adder
10.698
274776LINCOLN ;7U
Adder
10.698
274777LINCOLN ;8U
Adder
10.698
971771AH1-392 GEN
Solar/Wind Harmer
8.844
971769AH1-391 GEN
Solar/Wind Harmer
9.861
24729505KEY G4
Adder
8.122
274814UNIV PK N;0U
Adder
6.324
274807UNIV PK N;3U
Adder
6.31
274805UNIV PK N;1U
Adder
6.283
274811UNIV PK N;7U
Adder
6.269
971619AH1-309 GEN
Solar/Wind Harmer
3.929
274827FISK ;RP
Adder
9.695
972037AH1-567 GEN1
Adder
0.229
960591AF2-350 GEN
Solar/Wind Harmer
8.717
972227AH1-698 GEN1
Adder
3.259
274687WILL CNTY;4U
Adder
34.788
274687WILL CNTY;4U
Adder
34.788
274675JOLIET 29;7U
Adder
38.179
274675JOLIET 29;7U
Adder
36.815
274731ELWOOD EC;2P
Adder
20.43
274733ELWOOD EC;3P
Adder
20.43
274735ELWOOD EC;4P
Adder
20.43
274728ELWOOD EC;5P
Adder
20.43
970833AG2-524 GEN
Solar/Wind Harmer
9.537
970833AG2-524 GEN
Solar/Wind Harmer
6.358
274746AC1-111 G10
Adder
6.922
274744AC1-111 GEN8
Adder
6.922
270536AF1-215 GEN2
Solar/Wind Harmer
0.011
958391AF2-133 GEN
Solar/Wind Harmer
0.001
276868AE1-113 GEN
Solar/Wind Harmer
1.708
276882AE2-255 GEN
Solar/Wind Harmer
0.995
971177AH1-047 GEN
Solar/Wind Harmer
5.247
971675AH1-338 GEN
Solar/Wind Harmer
3.312
971411AH1-196 GEN
Solar/Wind Harmer
12.736
274863CRW1-WTG
Solar/Wind Harmer
0.003
274864CRW2-WTG
Solar/Wind Harmer
0.003
971611AH1-305 GEN
Solar/Wind Harmer
5.049
971171AH1-044 GEN
Solar/Wind Harmer
16.925
274823ROCKFORD ;21
Adder
23.589
970169AG2-114 GEN
Solar/Wind Harmer
8.416
276612AE2-035 GEN
Solar/Wind Harmer
0.002
926823AC1-168 GEN
Solar/Wind Harmer
1.43
971681AH1-341 GEN
Solar/Wind Harmer
13.508
961011AF2-392 GEN
Solar/Wind Harmer
4.894
965101AG1-375 GEN
Solar/Wind Harmer
8.339
24690905MDL-1G C
Solar/Wind Harmer
0.003
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
957751AF2-069 GEN
Solar/Wind Harmer
0.274
274848CAMPGROVE;RU
Solar/Wind Harmer
0.002
276655WTG1_EQ
Solar/Wind Harmer
0.003
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
8.681
941731AE2-173 GEN
Solar/Wind Harmer
6.89
946321AF1-296 GEN
Solar/Wind Harmer
4.595
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
945581AF1-223 GEN
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
10.958
963841AG1-237 GEN
Solar/Wind Harmer
3.497
965041AG1-368 GEN
Solar/Wind Harmer
8.037
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.291
276848AB2-070 GEN3
Solar/Wind Harmer
0.289
970289AG2-191 GEN
Solar/Wind Harmer
1.512
971549AH1-272 GEN
Solar/Wind Harmer
16.344
971609AH1-304 GEN
Solar/Wind Harmer
1.291
270594AE1-207 GEN
Solar/Wind Harmer
8.813
965051AG1-369 GEN
Solar/Wind Harmer
3.913
270284AF1-227 GEN1
Solar/Wind Harmer
0.01
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
270024AE2-089 GEN
Solar/Wind Harmer
0.008
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
944221AF1-090 GEN
Solar/Wind Harmer
4.485
970115AG2-085 GEN
Solar/Wind Harmer
3.056
24722005FLATG5
50/50
1.721
24721905FLATG4
50/50
31.554
970153AG2-106 GEN
Solar/Wind Harmer
47.528
970513AG2-328 GEN
Solar/Wind Harmer
4.024
970517AG2-330 GEN
Solar/Wind Harmer
24.143
970349AG2-230 GEN
Solar/Wind Harmer
13.852
270043AE2-236 GEN
Solar/Wind Harmer
5.825
274772LINCOLN ;3U
Adder
10.698
944531AF1-118 GEN
Solar/Wind Harmer
39.627
247643Z2-116 C
Solar/Wind Harmer
0
274724RIVER EC ;11
Adder
22.251
24642205MAYFLWER
Adder
0.798
274752CRETE EC ;2U
Adder
10.335
274753CRETE EC ;3U
Adder
10.335
970707AG2-453 GEN
Solar/Wind Harmer
28.578
274826FISK ;BP
Adder
13.679
274802UNIV PARK;5U
Adder
7.284
276806AD2-047 C O1
Solar/Wind Harmer
4.94
970941AG2-585 GEN
Solar/Wind Harmer
10.896
972228AH1-698 GEN2
Adder
4.628
274800UNIV PARK;3U
Adder
7.282
972038AH1-567 GEN2
Adder
0.456
945111AF1-176 GEN
Solar/Wind Harmer
7.057
276897AD1-100 C
Solar/Wind Harmer
0.012
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
970031AG2-029 GEN
Solar/Wind Harmer
5.65
274676JOLIET 29;8U
Adder
36.815
274729ELWOOD EC;1P
Adder
20.43
274730ELWOOD EC;6P
Adder
20.43
274734ELWOOD EC;8P
Adder
20.43
274736ELWOOD EC;9P
Adder
20.43
276893AG1-478 C
Solar/Wind Harmer
0.344
943121AE2-341 GEN
Solar/Wind Harmer
14.504
943591AF1-030 GEN
Solar/Wind Harmer
9.645
270535AF1-215 GEN1
Solar/Wind Harmer
0.011
959331AF2-224 GEN
Solar/Wind Harmer
6.029
965021AG1-366 GEN
Solar/Wind Harmer
2.871
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
22.097
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274872LEEDK;1U
Solar/Wind Harmer
0.313
276805AD2-038 GEN
Solar/Wind Harmer
0.002
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
24441205WTRV SLR C
Solar/Wind Harmer
0
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
0.906
274855GSG-6 ;RU
Solar/Wind Harmer
0.311
274850MENDOTA H;RU
Solar/Wind Harmer
0.1
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.152
24721805FLATG3
50/50
1.721
24721705FLATG2
50/50
31.554
24344105CKG2
50/50
10.231
962761AG1-125 GEN
Solar/Wind Harmer
74.429
970149AG2-104 GEN
Solar/Wind Harmer
80.386
970155AG2-107 GEN
Solar/Wind Harmer
47.528
970245AG2-165 GEN
Solar/Wind Harmer
4.024
274773LINCOLN ;4U
Adder
10.698
274774LINCOLN ;5U
Adder
10.698
274723RIVER EC ;12
Adder
22.511
24639705ELKHART HY
Adder
0.193
276164X3-005 C
Solar/Wind Harmer
0
274751CRETE EC ;1U
Adder
10.335
274754CRETE EC ;4U
Adder
10.335
274812UNIV PK N;8U
Adder
6.269
270063AE2-323 C
Solar/Wind Harmer
0.007
270505AE1-170 C O1
Solar/Wind Harmer
9.167
276776AD2-060 GEN
Solar/Wind Harmer
0.91
274801UNIV PARK;4U
Adder
7.282
970373AG2-245 GEN
Solar/Wind Harmer
18.295
945111AF1-176 GEN
Solar/Wind Harmer
15.535
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
38.179
274674JOLIET 9 ;6U
Adder
19.145
274732ELWOOD EC;7P
Adder
20.43
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
4.514
274745AC1-111 GEN9
Adder
6.922
270055AF2-134 C O1
Solar/Wind Harmer
0.007
965011AG1-365 GEN
Solar/Wind Harmer
8.612
276691AA1-018 GEN1
Solar/Wind Harmer
1.04
274682WAUKEGAN ;7U
Adder
22.097
274828WAUKEGAN ;BP
Adder
13.572
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
11.134
939401AE1-172 GEN
Solar/Wind Harmer
6.393
962781AG1-127 GEN
Solar/Wind Harmer
8.132
274872LEEDK;1U
Solar/Wind Harmer
0.005
276901AD2-066 C O1
Solar/Wind Harmer
0.008
971997AH1-543 GEN
Solar/Wind Harmer
4.464
959091AF2-200 GEN
Solar/Wind Harmer
16.925
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
2.65
247604X1-042
Adder
0.502
970571AG2-364 GEN
Solar/Wind Harmer
16.817
274858EASY ROAD;U2
Solar/Wind Harmer
0.002
274760LEE CO EC;1U
Adder
11.164
274767LEE CO EC;8U
Adder
11.032
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
8.324
276157O29GEN1
Solar/Wind Harmer
1.345
274878BISHOP HL;2U
Solar/Wind Harmer
0.279
942111AE2-223 GEN
Solar/Wind Harmer
2.687
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
965091AG1-374 GEN
Solar/Wind Harmer
24.591
959611AF2-252 GEN
Solar/Wind Harmer
2.732
965931AG1-462 GEN
Solar/Wind Harmer
20.863
247642Z2-115 C
Solar/Wind Harmer
0.003
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
3.685
276668AB2-070 GEN1
Solar/Wind Harmer
0.291
970289AG2-191 GEN
Solar/Wind Harmer
0.875
970291AG2-192 GEN
Solar/Wind Harmer
0.796
276621W2-048 GEN
Solar/Wind Harmer
0.399
276838X2-022 GEN2
Solar/Wind Harmer
0.445
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.051
942481AE2-261 GEN
Solar/Wind Harmer
23.26
958821AF2-173 GEN
Solar/Wind Harmer
10.805
270004AE1-209 GEN
Solar/Wind Harmer
1.672
971617AH1-308 GEN
Solar/Wind Harmer
6.396
970193AG2-126 GEN
Solar/Wind Harmer
11.433
946031AF1-268 GEN
Solar/Wind Harmer
7.175
970243AG2-164 GEN
Solar/Wind Harmer
1.523
970519AG2-331 GEN
Solar/Wind Harmer
6.77
970699AG2-449 GEN
Solar/Wind Harmer
0.651
276861AD2-134 GEN
Solar/Wind Harmer
0.152
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
10.6
957471AF2-041 GEN
Solar/Wind Harmer
25.388
959081AF2-199 GEN
Solar/Wind Harmer
8.463
971067AG2-660 GEN
Solar/Wind Harmer
2.821
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
274822ROCKFORD ;11
Adder
23.761
965651AG1-433 GEN
Solar/Wind Harmer
2.475
972235AH1-702 GEN1
Adder
3.048
970819AG2-516 GEN
Solar/Wind Harmer
10.106
970569AG2-363 GEN
Solar/Wind Harmer
25.226
971475AH1-234 GEN
Solar/Wind Harmer
4.081
274857EASY ROAD;U1
Solar/Wind Harmer
0.002
274761LEE CO EC;2U
Adder
11.164
274766LEE CO EC;7U
Adder
11.032
958861AF2-177 GEN
Solar/Wind Harmer
3.614
24791305MDL-5G
Solar/Wind Harmer
0.001
276158O29GEN2
Solar/Wind Harmer
0.001
274877BISHOP HL;1U
Solar/Wind Harmer
0.279
270349AD2-093_GEN
Solar/Wind Harmer
0.006
276726Z2-087_GEN
Solar/Wind Harmer
0.003
939741AE1-205 GEN
Solar/Wind Harmer
11.575
274854TWINGROVE;U2
Solar/Wind Harmer
0.004
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
945371AF1-202 GEN
Solar/Wind Harmer
0.001
972175AH1-670 GEN
Solar/Wind Harmer
6.679
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963741AG1-226 GEN
Solar/Wind Harmer
18.86
970291AG2-192 GEN
Solar/Wind Harmer
1.034
963831AG1-236 GEN
Solar/Wind Harmer
3.102
276615X2-022 GEN
Solar/Wind Harmer
0.083
270032AE2-172
Solar/Wind Harmer
5.246
247521TR3_G114
Solar/Wind Harmer
0.286
270246TR4_N_V150
Solar/Wind Harmer
0.051
965911AG1-460 GEN
Solar/Wind Harmer
1.556
276903AD2-071 C
Solar/Wind Harmer
8.661
270005AE1-210 C O1
Solar/Wind Harmer
1.672
965031AG1-367 GEN
Solar/Wind Harmer
7.718
944231AF1-091 GEN
Solar/Wind Harmer
2.052
24695305TIMB G C
Solar/Wind Harmer
0.002
970825AG2-519 GEN
Solar/Wind Harmer
2.704
970333AG2-219 GEN
Solar/Wind Harmer
1.862
270102X2-052 ST
50/50
2.042
270100X2-052 CT1
50/50
1.881
270101X2-052 CT2
50/50
1.881
970321AG2-212 GEN
Solar/Wind Harmer
4.024
965681AG1-436 GEN
Solar/Wind Harmer
11.102
965791AG1-447 GEN
Solar/Wind Harmer
8.141
274770LINCOLN ;1U
Adder
10.698
274771LINCOLN ;2U
Adder
10.698
270526AF1-158 GEN
Solar/Wind Harmer
0.011
24441505OLIV SLR
Solar/Wind Harmer
0
270216AD2-079_GEN
Solar/Wind Harmer
0.001
274808UNIV PK N;4U
Adder
6.241
957891AF2-083 GEN
Solar/Wind Harmer
0.001
972259AH1-714 GEN
Adder
23.861
247620Y3-023
Adder
0.576
274803UNIV PARK;6U
Adder
7.284
274888KELLY CRK;1U
Solar/Wind Harmer
0.512
274887GEN-1.85
Solar/Wind Harmer
0.23
276843GEN-1.7
Solar/Wind Harmer
0.282
958011AF2-095 GEN
Solar/Wind Harmer
12.553
274674JOLIET 9 ;6U
Adder
19.145
961051AF2-396 GEN
Solar/Wind Harmer
17.339
961051AF2-396 GEN
Solar/Wind Harmer
11.56
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
971573AH1-285 GEN
Solar/Wind Harmer
1.607
970611AG2-400 GEN
Solar/Wind Harmer
8.612
970627AG2-408 GEN
Solar/Wind Harmer
2.584
274695ROCKY RD ;2P
Adder
13.703
274693ROCKY RD ;1P
Adder
13.569
274697ROCKY RD ;3P
Adder
3.723
274696ROCKY RD ;4P
Adder
14.027
958481AF2-142 GEN
Solar/Wind Harmer
12.872
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
1.161
274683WAUKEGAN ;8U
Adder
25.892
274683WAUKEGAN ;8U
Adder
21.826
962691AG1-118 GEN
Solar/Wind Harmer
25.667
970921AG2-575 GEN
Solar/Wind Harmer
8.545
970921AG2-575 GEN
Solar/Wind Harmer
2.848
958491AF2-143 GEN
Solar/Wind Harmer
12.795
274879MINONK ;1U
Solar/Wind Harmer
0.359
942991AE2-321 GEN
Solar/Wind Harmer
9.503
971333AH1-146 GEN
Solar/Wind Harmer
16.975
971335AH1-147 GEN
Solar/Wind Harmer
16.975
971341AH1-150 GEN
Solar/Wind Harmer
16.925
971343AH1-151 GEN
Solar/Wind Harmer
16.925
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
944541AF1-119 GEN
Solar/Wind Harmer
0.565
960971AF2-388 GEN
Solar/Wind Harmer
4.95
274856ECOGROVE ;U1
Solar/Wind Harmer
0.198
276611AD2-172 GEN
Solar/Wind Harmer
0.002
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
938861AE1-114 GEN
Solar/Wind Harmer
4.753
274764LEE CO EC;5U
Adder
11.19
274765LEE CO EC;6U
Adder
11.19
274762LEE CO EC;3U
Adder
11.164
274763LEE CO EC;4U
Adder
11.058
276603SUBLETTE C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
4.971
276741O09 GEN1
Solar/Wind Harmer
0.296
276708O09 GEN2
Solar/Wind Harmer
0.296
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.327
276646AC1-214 GEN2
Solar/Wind Harmer
0.327
276782AC1-033 GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.006
960611AF2-352 GEN
Solar/Wind Harmer
2.732
966841AG1-555 GEN
Solar/Wind Harmer
0.926
942221AE2-234 GEN
Solar/Wind Harmer
0.041
970241AG2-163 GEN
Solar/Wind Harmer
4.649
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
270599AE1-208 GEN
Solar/Wind Harmer
7.244
270031AE2-169
Solar/Wind Harmer
4.346
971613AH1-306 GEN
Solar/Wind Harmer
3.777
276916AD2-100_GEN
Solar/Wind Harmer
16.273
276911AD2-131_GEN
Solar/Wind Harmer
1.072
960441AF2-335 GEN
Solar/Wind Harmer
7.639
945391AF1-204 GEN
Solar/Wind Harmer
8.098
970825AG2-519 GEN
Solar/Wind Harmer
8.443
970239AG2-162 GEN
Solar/Wind Harmer
0.651
944201AF1-088_MTX
Adder
121.789
957141AF2-008_MTX
Adder
33.652
LAGNLTFEXP_LAGN->PJM
CLTF
16.714
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.261
TVALTFEXP_TVA->PJM
CLTF
7.962
CPLELTFEXP_CPLE->PJM
CLTF
3.263
CBM West 2LTFEXP_CBM-W2->PJM
CBM
123.519
NYPJM->LTFIMP_NY
CLTF
3.894
LGEELTFEXP_LGEE->PJM
CLTF
5.997
WECLTFEXP_WEC->PJM
CLTF
4.617
AG2-052LTFEXP_AG2-052->PJM
LTF
0.285
AH1-155LTFEXP_AH1-155->PJM
LTF
0.427
CBM West 1LTFEXP_CBM-W1->PJM
CBM
148.673
CBM South 1LTFEXP_CBM-S1->PJM
CBM
30.42
MECLTFEXP_MEC->PJM
CLTF
18.605
SIGELTFEXP_SIGE->PJM
CLTF
0.498

Details for 05MALIS-05VASSEL 765.0 kV Ckt 1 line l/o AEP_P4_#706_05GAVIN 765_C1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MALIS-05VASSEL 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#706_05GAVIN 765_C1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.53 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4826.48
MW Contribution:24.6
Bus #Bus NameTypeMW Contribution
24722005FLATG5
50/50
4.694
24721905FLATG4
50/50
86.059
270475AD2-096_GEN
50/50
10.488
270142AC1-141 CT1_
50/50
3.444
24721605FLATG1
50/50
4.694
971599AH1-298 GEN
50/50
14.063
270144AC1-141 ST1_
50/50
3.051
24653605MOTTVILLE
50/50
0.005
24643105BUCHANAN
50/50
0.018
270036AE2-216 BAT
50/50
8.975
962771AG1-126 GEN
Solar/Wind Harmer
129.902
270284AF1-227 GEN1
Solar/Wind Harmer
9.474
270286AF1-227 GEN2
Solar/Wind Harmer
3.505
270287AF1-227 GEN3
Solar/Wind Harmer
3.505
971347AH1-153 GEN
Solar/Wind Harmer
22.443
270578AF1-285 GEN2
Solar/Wind Harmer
0.683
270071AF1-092 GEN
Solar/Wind Harmer
21.965
971771AH1-392 GEN
Solar/Wind Harmer
12.923
971769AH1-391 GEN
Solar/Wind Harmer
14.204
960681AF2-359 GEN
Solar/Wind Harmer
5.35
944161AF1-084 GEN
Solar/Wind Harmer
3.119
270302AB2-170 GEN
Solar/Wind Harmer
11.755
270317AD1-130_GEN
Solar/Wind Harmer
4.507
24729505KEY G4
Adder
9.092
965041AG1-368 GEN
Solar/Wind Harmer
13.959
274775LINCOLN ;6U
Adder
8.527
274776LINCOLN ;7U
Adder
8.527
274777LINCOLN ;8U
Adder
8.527
965051AG1-369 GEN
Solar/Wind Harmer
6.856
274814UNIV PK N;0U
Adder
6.852
274807UNIV PK N;3U
Adder
6.837
274805UNIV PK N;1U
Adder
6.807
274811UNIV PK N;7U
Adder
6.792
972037AH1-567 GEN1
Adder
0.247
274827FISK ;RP
Adder
10.465
960591AF2-350 GEN
Solar/Wind Harmer
13.475
972227AH1-698 GEN1
Adder
3.512
957201AF2-014 GEN
Solar/Wind Harmer
6.1
270435AC2-044 GEN
Solar/Wind Harmer
2.69
963791AG1-232 GEN
Solar/Wind Harmer
18.134
274687WILL CNTY;4U
Adder
37.406
274687WILL CNTY;4U
Adder
37.406
274675JOLIET 29;7U
Adder
41.022
274675JOLIET 29;7U
Adder
39.557
270536AF1-215 GEN2
Solar/Wind Harmer
6.069
274731ELWOOD EC;2P
Adder
21.93
274733ELWOOD EC;3P
Adder
21.93
274735ELWOOD EC;4P
Adder
21.93
274728ELWOOD EC;5P
Adder
21.93
970833AG2-524 GEN
Solar/Wind Harmer
11.63
970833AG2-524 GEN
Solar/Wind Harmer
5.409
971549AH1-272 GEN
Solar/Wind Harmer
24.604
958711AF2-162 GEN
Solar/Wind Harmer
1.345
274746AC1-111 G10
Adder
7.401
274744AC1-111 GEN8
Adder
7.401
965101AG1-375 GEN
Solar/Wind Harmer
13.06
958391AF2-133 GEN
Solar/Wind Harmer
11.816
274823ROCKFORD ;21
Adder
24.797
24641605TWIN BRNCH
50/50
0.025
24344005CKG1
50/50
9.376
24642205MAYFLWER
50/50
0.961
944961AF1-161 GEN
50/50
4.122
962601AG1-109 GEN
50/50
4.122
970153AG2-106 GEN
Solar/Wind Harmer
56.644
270043AE2-236 GEN
Solar/Wind Harmer
8.306
970349AG2-230 GEN
Solar/Wind Harmer
22.443
959331AF2-224 GEN
Solar/Wind Harmer
14.786
965021AG1-366 GEN
Solar/Wind Harmer
3.439
942871AE2-306 GEN
Solar/Wind Harmer
1.331
270391AF1-285 GEN3
Solar/Wind Harmer
0.683
970513AG2-328 GEN
Solar/Wind Harmer
26.004
970517AG2-330 GEN
Solar/Wind Harmer
23.585
970031AG2-029 GEN
Solar/Wind Harmer
43.335
247643Z2-116 C
Solar/Wind Harmer
0.101
944531AF1-118 GEN
Solar/Wind Harmer
49.96
945111AF1-176 GEN
Solar/Wind Harmer
8.066
270485AE1-090_GEN
Solar/Wind Harmer
0.85
24441205WTRV SLR C
Solar/Wind Harmer
0.189
247604X1-042
Adder
0.578
274772LINCOLN ;3U
Adder
8.527
270191TR4_S_V150
Solar/Wind Harmer
4.119
270247TR4_N_V136
Solar/Wind Harmer
1.168
274724RIVER EC ;11
Adder
24.177
972231SS25-0005
Solar/Wind Harmer
12.946
972181SS23-001
Solar/Wind Harmer
8.091
274752CRETE EC ;2U
Adder
6.668
274753CRETE EC ;3U
Adder
6.668
970707AG2-453 GEN
Solar/Wind Harmer
37.832
274802UNIV PARK;5U
Adder
7.866
274826FISK ;BP
Adder
14.766
276772AC2-154 GEN
Solar/Wind Harmer
3.758
276806AD2-047 C O1
Solar/Wind Harmer
14.415
970941AG2-585 GEN
Solar/Wind Harmer
16.843
274800UNIV PARK;3U
Adder
7.856
972038AH1-567 GEN2
Adder
0.492
972228AH1-698 GEN2
Adder
4.987
270491AE1-102 GEN2
Solar/Wind Harmer
1.748
276897AD1-100 C
Solar/Wind Harmer
38.911
939351AE1-166 GEN
Solar/Wind Harmer
7.95
274676JOLIET 29;8U
Adder
39.557
270535AF1-215 GEN1
Solar/Wind Harmer
6.069
274729ELWOOD EC;1P
Adder
21.93
274730ELWOOD EC;6P
Adder
21.93
274734ELWOOD EC;8P
Adder
21.93
274736ELWOOD EC;9P
Adder
21.93
276893AG1-478 C
Solar/Wind Harmer
0.557
943121AE2-341 GEN
Solar/Wind Harmer
19.89
943591AF1-030 GEN
Solar/Wind Harmer
13.26
964401AG1-302 GEN
Solar/Wind Harmer
11.919
276694AA1-018 GEN2
Solar/Wind Harmer
8.271
274682WAUKEGAN ;7U
Adder
23.511
972236AH1-702 GEN2
Adder
2.783
274760LEE CO EC;1U
Adder
11.654
274767LEE CO EC;8U
Adder
11.517
24728705AND G3
Adder
7.997
24728505AND G1
Adder
3.824
24721805FLATG3
50/50
4.694
24721705FLATG2
50/50
86.059
24344105CKG2
50/50
11.607
270143AC1-141 CT2_
50/50
3.444
24639705ELKHART HY
50/50
0.234
970521AG2-332 GEN
50/50
16.668
24307105BERRINSP G
50/50
0.031
962761AG1-125 GEN
Solar/Wind Harmer
129.902
970149AG2-104 GEN
Solar/Wind Harmer
160.43
970155AG2-107 GEN
Solar/Wind Harmer
56.644
270349AD2-093_GEN
Solar/Wind Harmer
6.554
965011AG1-365 GEN
Solar/Wind Harmer
14.786
270223U2-072_GEN1
Solar/Wind Harmer
2.903
270578AF1-285 GEN2
Solar/Wind Harmer
1.775
270391AF1-285 GEN3
Solar/Wind Harmer
1.775
970245AG2-165 GEN
Solar/Wind Harmer
26.004
270063AE2-323 C
Solar/Wind Harmer
3.194
270505AE1-170 C O1
Solar/Wind Harmer
21.434
945111AF1-176 GEN
Solar/Wind Harmer
25.451
270449AD2-020 GEN
Solar/Wind Harmer
3.975
943021AE2-325 GEN
Solar/Wind Harmer
5.164
270462AD2-086
Solar/Wind Harmer
9.779
972207SS24-0001
Solar/Wind Harmer
30.317
274773LINCOLN ;4U
Adder
8.527
274774LINCOLN ;5U
Adder
8.527
247521TR3_G114
Solar/Wind Harmer
4.617
270246TR4_N_V150
Solar/Wind Harmer
1.168
274723RIVER EC ;12
Adder
24.46
274751CRETE EC ;1U
Adder
6.668
274754CRETE EC ;4U
Adder
6.668
970373AG2-245 GEN
Solar/Wind Harmer
28.573
276164X3-005 C
Solar/Wind Harmer
0.955
965421AG1-410 GEN
Solar/Wind Harmer
40.731
274812UNIV PK N;8U
Adder
6.792
24695305TIMB G C
Solar/Wind Harmer
7.439
276776AD2-060 GEN
Solar/Wind Harmer
0.57
274801UNIV PARK;4U
Adder
7.856
246936BC-WTG1
Solar/Wind Harmer
5.263
270489AE1-102 GEN1
Solar/Wind Harmer
1.748
941551AE2-152 GEN
Solar/Wind Harmer
6.081
944231AF1-091 GEN
Solar/Wind Harmer
5.048
274676JOLIET 29;8U
Adder
41.022
270055AF2-134 C O1
Solar/Wind Harmer
4.045
274674JOLIET 9 ;6U
Adder
20.555
274732ELWOOD EC;7P
Adder
21.93
274871GR RIDGE ;2U
Solar/Wind Harmer
10.239
965651AG1-433 GEN
Solar/Wind Harmer
7.266
274745AC1-111 GEN9
Adder
7.401
958381AF2-132 GEN
Solar/Wind Harmer
11.919
964861AG1-349 GEN
Solar/Wind Harmer
10.309
971917AH1-482 GEN
Solar/Wind Harmer
11.896
276691AA1-018 GEN1
Solar/Wind Harmer
0.61
274682WAUKEGAN ;7U
Adder
23.511
274828WAUKEGAN ;BP
Adder
14.433
958861AF2-177 GEN
Solar/Wind Harmer
14.275
274822ROCKFORD ;11
Adder
24.978
972235AH1-702 GEN1
Adder
3.201
274761LEE CO EC;2U
Adder
11.654
274766LEE CO EC;7U
Adder
11.517
24728605AND G2
Adder
3.824
960751AF2-366 GEN
Solar/Wind Harmer
3.375
962781AG1-127 GEN
Solar/Wind Harmer
11.186
970615AG2-402 GEN
50/50
3.439
247620Y3-023
50/50
0.701
270102X2-052 ST
50/50
2.279
270100X2-052 CT1
50/50
2.1
270101X2-052 CT2
50/50
2.1
270471AD2-092_GEN
Solar/Wind Harmer
6.554
970611AG2-400 GEN
Solar/Wind Harmer
14.786
270224U2-072_GEN2
Solar/Wind Harmer
2.903
270227U2-072_GEN3
Solar/Wind Harmer
2.903
270228U2-072_GEN4
Solar/Wind Harmer
2.903
270231U2-072_GEN5
Solar/Wind Harmer
2.903
970321AG2-212 GEN
Solar/Wind Harmer
26.004
270216AD2-079_GEN
Solar/Wind Harmer
0.873
957891AF2-083 GEN
Solar/Wind Harmer
4.815
960981AF2-389 GEN
Solar/Wind Harmer
2.158
270526AF1-158 GEN
Solar/Wind Harmer
6.468
961051AF2-396 GEN
Solar/Wind Harmer
22.558
961051AF2-396 GEN
Solar/Wind Harmer
10.492
24441505OLIV SLR
Solar/Wind Harmer
0.19
965681AG1-436 GEN
Solar/Wind Harmer
17.703
965791AG1-447 GEN
Solar/Wind Harmer
9.057
274770LINCOLN ;1U
Adder
8.527
274771LINCOLN ;2U
Adder
8.527
274808UNIV PK N;4U
Adder
6.763
274803UNIV PARK;6U
Adder
7.866
274888KELLY CRK;1U
Solar/Wind Harmer
7.955
274887GEN-1.85
Solar/Wind Harmer
7.182
276843GEN-1.7
Solar/Wind Harmer
0.773
958011AF2-095 GEN
Solar/Wind Harmer
19.404
972259AH1-714 GEN
Adder
25.697
246938BC-WTG3
Solar/Wind Harmer
5.354
246937BC-WTG2
Solar/Wind Harmer
5.263
274674JOLIET 9 ;6U
Adder
20.555
274847GR RIDGE ;BU
Solar/Wind Harmer
6.735
944541AF1-119 GEN
Solar/Wind Harmer
5.569
960971AF2-388 GEN
Solar/Wind Harmer
14.532
971573AH1-285 GEN
Solar/Wind Harmer
11.345
958481AF2-142 GEN
Solar/Wind Harmer
19.659
274696ROCKY RD ;4P
Adder
14.93
274695ROCKY RD ;2P
Adder
14.586
274693ROCKY RD ;1P
Adder
14.442
274697ROCKY RD ;3P
Adder
3.962
274861TOP CROP ;1U
Solar/Wind Harmer
7.938
274862TOP CROP ;2U
Solar/Wind Harmer
6.628
274683WAUKEGAN ;8U
Adder
27.535
274683WAUKEGAN ;8U
Adder
23.211
962691AG1-118 GEN
Solar/Wind Harmer
39.042
942221AE2-234 GEN
Solar/Wind Harmer
0.953
274764LEE CO EC;5U
Adder
11.682
274765LEE CO EC;6U
Adder
11.682
274762LEE CO EC;3U
Adder
11.654
274763LEE CO EC;4U
Adder
11.544
972267AH1-718 GEN
Adder
5.169
247621Y3-024
Adder
0.268
970921AG2-575 GEN
Solar/Wind Harmer
11.763
970921AG2-575 GEN
Solar/Wind Harmer
2.735
944201AF1-088_MTX
Adder
108.034
957141AF2-008_MTX
Adder
1.852
LAGNLTFEXP_LAGN->PJM
CLTF
11.481
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.982
TVALTFEXP_TVA->PJM
CLTF
4.813
CBM West 2LTFEXP_CBM-W2->PJM
CBM
98.823
NYPJM->LTFIMP_NY
CLTF
3.072
LGEELTFEXP_LGEE->PJM
CLTF
4.553
WECLTFEXP_WEC->PJM
CLTF
4.843
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.157
AG2-052LTFEXP_AG2-052->PJM
LTF
0.305
AH1-155LTFEXP_AH1-155->PJM
LTF
0.457
CBM West 1LTFEXP_CBM-W1->PJM
CBM
159.327
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.302
MECLTFEXP_MEC->PJM
CLTF
18.121
SIGELTFEXP_SIGE->PJM
CLTF
0.416

Details for 05MALIS-05VASSEL 765.0 kV Ckt 1 line l/o AEP_P1-2_#706_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MALIS-05VASSEL 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#706_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.0 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4722.06
MW Contribution:19.16
Bus #Bus NameTypeMW Contribution
24722005FLATG5
50/50
4.694
24721905FLATG4
50/50
86.059
270475AD2-096_GEN
50/50
10.488
270142AC1-141 CT1_
50/50
3.444
24641605TWIN BRNCH
50/50
0.025
24344005CKG1
50/50
9.376
24642205MAYFLWER
50/50
0.961
944961AF1-161 GEN
50/50
4.122
962601AG1-109 GEN
50/50
4.122
970153AG2-106 GEN
Solar/Wind Harmer
69.955
270043AE2-236 GEN
Solar/Wind Harmer
6.761
970349AG2-230 GEN
Solar/Wind Harmer
15.658
959331AF2-224 GEN
Solar/Wind Harmer
7.221
965021AG1-366 GEN
Solar/Wind Harmer
3.439
270391AF1-285 GEN3
Solar/Wind Harmer
0.683
970513AG2-328 GEN
Solar/Wind Harmer
4.403
970517AG2-330 GEN
Solar/Wind Harmer
26.415
970031AG2-029 GEN
Solar/Wind Harmer
6.551
247643Z2-116 C
Solar/Wind Harmer
0
944531AF1-118 GEN
Solar/Wind Harmer
44.632
945111AF1-176 GEN
Solar/Wind Harmer
8.066
270485AE1-090_GEN
Solar/Wind Harmer
0.001
24441205WTRV SLR C
Solar/Wind Harmer
0
247604X1-042
Adder
0.578
274772LINCOLN ;3U
Adder
11.607
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.062
274724RIVER EC ;11
Adder
24.177
24721605FLATG1
50/50
4.694
971599AH1-298 GEN
50/50
14.063
270144AC1-141 ST1_
50/50
3.051
24653605MOTTVILLE
50/50
0.005
24643105BUCHANAN
50/50
0.018
270036AE2-216 BAT
50/50
8.975
962771AG1-126 GEN
Solar/Wind Harmer
109.549
270284AF1-227 GEN1
Solar/Wind Harmer
0.015
270286AF1-227 GEN2
Solar/Wind Harmer
0.006
270287AF1-227 GEN3
Solar/Wind Harmer
0.006
971347AH1-153 GEN
Solar/Wind Harmer
15.658
270578AF1-285 GEN2
Solar/Wind Harmer
0.683
270071AF1-092 GEN
Solar/Wind Harmer
19.582
971771AH1-392 GEN
Solar/Wind Harmer
10.018
971619AH1-309 GEN
Solar/Wind Harmer
4.486
971769AH1-391 GEN
Solar/Wind Harmer
11.066
960681AF2-359 GEN
Solar/Wind Harmer
-0.002
270302AB2-170 GEN
Solar/Wind Harmer
0.006
270317AD1-130_GEN
Solar/Wind Harmer
0.014
971653AH1-327 GEN
Solar/Wind Harmer
1.377
24729505KEY G4
Adder
9.092
965041AG1-368 GEN
Solar/Wind Harmer
9.739
274752CRETE EC ;2U
Adder
11.24
274753CRETE EC ;3U
Adder
11.24
970707AG2-453 GEN
Solar/Wind Harmer
30.794
274802UNIV PARK;5U
Adder
7.866
274826FISK ;BP
Adder
14.766
276806AD2-047 C O1
Solar/Wind Harmer
5.327
970941AG2-585 GEN
Solar/Wind Harmer
11.751
274800UNIV PARK;3U
Adder
7.856
972038AH1-567 GEN2
Adder
0.492
972228AH1-698 GEN2
Adder
4.987
24721805FLATG3
50/50
4.694
24721705FLATG2
50/50
86.059
24344105CKG2
50/50
11.607
270143AC1-141 CT2_
50/50
3.444
24639705ELKHART HY
50/50
0.234
970521AG2-332 GEN
50/50
16.668
24307105BERRINSP G
50/50
0.031
962761AG1-125 GEN
Solar/Wind Harmer
109.549
970149AG2-104 GEN
Solar/Wind Harmer
118.317
970155AG2-107 GEN
Solar/Wind Harmer
69.955
270349AD2-093_GEN
Solar/Wind Harmer
0.009
965011AG1-365 GEN
Solar/Wind Harmer
10.316
270223U2-072_GEN1
Solar/Wind Harmer
0.001
970245AG2-165 GEN
Solar/Wind Harmer
4.403
270063AE2-323 C
Solar/Wind Harmer
0.008
270505AE1-170 C O1
Solar/Wind Harmer
10.468
945111AF1-176 GEN
Solar/Wind Harmer
17.757
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
5.164
270462AD2-086
Solar/Wind Harmer
0.02
274773LINCOLN ;4U
Adder
11.607
274774LINCOLN ;5U
Adder
11.607
247521TR3_G114
Solar/Wind Harmer
0.349
270246TR4_N_V150
Solar/Wind Harmer
0.062
274723RIVER EC ;12
Adder
24.46
274751CRETE EC ;1U
Adder
11.24
274754CRETE EC ;4U
Adder
11.24
970373AG2-245 GEN
Solar/Wind Harmer
19.935
276164X3-005 C
Solar/Wind Harmer
0
965421AG1-410 GEN
Solar/Wind Harmer
28.417
274812UNIV PK N;8U
Adder
6.792
24695305TIMB G C
Solar/Wind Harmer
0.002
276776AD2-060 GEN
Solar/Wind Harmer
0.981
274801UNIV PARK;4U
Adder
7.856
246936BC-WTG1
Solar/Wind Harmer
0.381
270489AE1-102 GEN1
Solar/Wind Harmer
1.22
941551AE2-152 GEN
Solar/Wind Harmer
0.001
944231AF1-091 GEN
Solar/Wind Harmer
2.492
274676JOLIET 29;8U
Adder
41.022
270055AF2-134 C O1
Solar/Wind Harmer
0.007
274674JOLIET 9 ;6U
Adder
20.555
274732ELWOOD EC;7P
Adder
21.93
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
965651AG1-433 GEN
Solar/Wind Harmer
2.721
274745AC1-111 GEN9
Adder
7.401
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
11.896
970615AG2-402 GEN
50/50
3.439
247620Y3-023
50/50
0.701
270102X2-052 ST
50/50
2.279
270100X2-052 CT1
50/50
2.1
270101X2-052 CT2
50/50
2.1
270471AD2-092_GEN
Solar/Wind Harmer
0.009
970611AG2-400 GEN
Solar/Wind Harmer
10.316
970627AG2-408 GEN
Solar/Wind Harmer
3.095
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
970321AG2-212 GEN
Solar/Wind Harmer
4.403
270216AD2-079_GEN
Solar/Wind Harmer
0.002
957891AF2-083 GEN
Solar/Wind Harmer
0.001
270526AF1-158 GEN
Solar/Wind Harmer
0.012
961051AF2-396 GEN
Solar/Wind Harmer
19.83
961051AF2-396 GEN
Solar/Wind Harmer
13.22
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
12.351
965791AG1-447 GEN
Solar/Wind Harmer
9.057
274770LINCOLN ;1U
Adder
11.607
274771LINCOLN ;2U
Adder
11.607
274808UNIV PK N;4U
Adder
6.763
274803UNIV PARK;6U
Adder
7.866
274888KELLY CRK;1U
Solar/Wind Harmer
0.552
274887GEN-1.85
Solar/Wind Harmer
0.248
276843GEN-1.7
Solar/Wind Harmer
0.304
958011AF2-095 GEN
Solar/Wind Harmer
13.537
972259AH1-714 GEN
Adder
25.697
246938BC-WTG3
Solar/Wind Harmer
0.34
246937BC-WTG2
Solar/Wind Harmer
0.381
274674JOLIET 9 ;6U
Adder
20.555
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
944541AF1-119 GEN
Solar/Wind Harmer
0.622
960971AF2-388 GEN
Solar/Wind Harmer
5.442
971573AH1-285 GEN
Solar/Wind Harmer
1.715
958481AF2-142 GEN
Solar/Wind Harmer
13.715
274696ROCKY RD ;4P
Adder
14.93
274695ROCKY RD ;2P
Adder
14.586
274775LINCOLN ;6U
Adder
11.607
274776LINCOLN ;7U
Adder
11.607
274777LINCOLN ;8U
Adder
11.607
965051AG1-369 GEN
Solar/Wind Harmer
4.783
274814UNIV PK N;0U
Adder
6.852
274807UNIV PK N;3U
Adder
6.837
274805UNIV PK N;1U
Adder
6.807
274811UNIV PK N;7U
Adder
6.792
972037AH1-567 GEN1
Adder
0.247
274827FISK ;RP
Adder
10.465
960591AF2-350 GEN
Solar/Wind Harmer
9.401
972227AH1-698 GEN1
Adder
3.512
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
1.189
963791AG1-232 GEN
Solar/Wind Harmer
12.652
274687WILL CNTY;4U
Adder
37.406
274687WILL CNTY;4U
Adder
37.406
274675JOLIET 29;7U
Adder
41.022
274675JOLIET 29;7U
Adder
39.557
270536AF1-215 GEN2
Solar/Wind Harmer
0.012
274731ELWOOD EC;2P
Adder
21.93
274733ELWOOD EC;3P
Adder
21.93
274735ELWOOD EC;4P
Adder
21.93
274728ELWOOD EC;5P
Adder
21.93
970833AG2-524 GEN
Solar/Wind Harmer
10.224
970833AG2-524 GEN
Solar/Wind Harmer
6.816
971549AH1-272 GEN
Solar/Wind Harmer
19.16
274746AC1-111 G10
Adder
7.401
274744AC1-111 GEN8
Adder
7.401
965101AG1-375 GEN
Solar/Wind Harmer
9.112
958391AF2-133 GEN
Solar/Wind Harmer
0.001
276868AE1-113 GEN
Solar/Wind Harmer
1.807
276882AE2-255 GEN
Solar/Wind Harmer
1.053
971177AH1-047 GEN
Solar/Wind Harmer
5.547
247607V1-011 GEN
Solar/Wind Harmer
0.001
971411AH1-196 GEN
Solar/Wind Harmer
13.442
971675AH1-338 GEN
Solar/Wind Harmer
3.495
971611AH1-305 GEN
Solar/Wind Harmer
5.332
274863CRW1-WTG
Solar/Wind Harmer
0.003
274864CRW2-WTG
Solar/Wind Harmer
0.003
971171AH1-044 GEN
Solar/Wind Harmer
17.815
274823ROCKFORD ;21
Adder
24.797
276612AE2-035 GEN
Solar/Wind Harmer
0.002
926823AC1-168 GEN
Solar/Wind Harmer
1.498
970169AG2-114 GEN
Solar/Wind Harmer
8.81
945581AF1-223 GEN
Solar/Wind Harmer
0.001
971681AH1-341 GEN
Solar/Wind Harmer
14.125
961011AF2-392 GEN
Solar/Wind Harmer
5.094
957751AF2-069 GEN
Solar/Wind Harmer
0.285
24690905MDL-1G C
Solar/Wind Harmer
0.003
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0.002
276655WTG1_EQ
Solar/Wind Harmer
0.003
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
8.957
941731AE2-173 GEN
Solar/Wind Harmer
7.108
270024AE2-089 GEN
Solar/Wind Harmer
0.009
946321AF1-296 GEN
Solar/Wind Harmer
4.721
971609AH1-304 GEN
Solar/Wind Harmer
1.376
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
970289AG2-191 GEN
Solar/Wind Harmer
1.575
270594AE1-207 GEN
Solar/Wind Harmer
9.184
963841AG1-237 GEN
Solar/Wind Harmer
3.53
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
970115AG2-085 GEN
Solar/Wind Harmer
3.191
276849AB2-070 GEN2
Solar/Wind Harmer
0.291
276848AB2-070 GEN3
Solar/Wind Harmer
0.29
270297AD1-101 GEN
Solar/Wind Harmer
0.002
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
270491AE1-102 GEN2
Solar/Wind Harmer
1.22
276897AD1-100 C
Solar/Wind Harmer
0.012
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
274676JOLIET 29;8U
Adder
39.557
270535AF1-215 GEN1
Solar/Wind Harmer
0.012
274729ELWOOD EC;1P
Adder
21.93
274730ELWOOD EC;6P
Adder
21.93
274734ELWOOD EC;8P
Adder
21.93
274736ELWOOD EC;9P
Adder
21.93
276893AG1-478 C
Solar/Wind Harmer
0.369
943121AE2-341 GEN
Solar/Wind Harmer
15.511
943591AF1-030 GEN
Solar/Wind Harmer
10.315
964401AG1-302 GEN
Solar/Wind Harmer
0.001
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
23.511
276805AD2-038 GEN
Solar/Wind Harmer
0.003
274872LEEDK;1U
Solar/Wind Harmer
0.331
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
0.956
274855GSG-6 ;RU
Solar/Wind Harmer
0.329
274850MENDOTA H;RU
Solar/Wind Harmer
0.106
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.161
959091AF2-200 GEN
Solar/Wind Harmer
17.815
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
2.783
270258AD1-119 GEN
Solar/Wind Harmer
0.002
970571AG2-364 GEN
Solar/Wind Harmer
17.623
270404AC1-167 GEN
Solar/Wind Harmer
0.004
274858EASY ROAD;U2
Solar/Wind Harmer
0.002
274760LEE CO EC;1U
Adder
11.654
274767LEE CO EC;8U
Adder
11.517
276157O29GEN1
Solar/Wind Harmer
1.397
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
8.621
274878BISHOP HL;2U
Solar/Wind Harmer
0.289
942111AE2-223 GEN
Solar/Wind Harmer
2.772
971617AH1-308 GEN
Solar/Wind Harmer
7.081
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
965091AG1-374 GEN
Solar/Wind Harmer
25.189
959611AF2-252 GEN
Solar/Wind Harmer
2.799
965931AG1-462 GEN
Solar/Wind Harmer
21.385
247642Z2-115 C
Solar/Wind Harmer
0.004
970289AG2-191 GEN
Solar/Wind Harmer
0.912
970291AG2-192 GEN
Solar/Wind Harmer
0.829
958821AF2-173 GEN
Solar/Wind Harmer
11.29
270004AE1-209 GEN
Solar/Wind Harmer
1.747
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
3.686
276668AB2-070 GEN1
Solar/Wind Harmer
0.291
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
11.901
946031AF1-268 GEN
Solar/Wind Harmer
7.527
276621W2-048 GEN
Solar/Wind Harmer
0.396
276838X2-022 GEN2
Solar/Wind Harmer
0.442
942481AE2-261 GEN
Solar/Wind Harmer
22.745
24728705AND G3
Adder
7.997
24728505AND G1
Adder
3.824
276691AA1-018 GEN1
Solar/Wind Harmer
1.108
274682WAUKEGAN ;7U
Adder
23.511
274828WAUKEGAN ;BP
Adder
14.433
958861AF2-177 GEN
Solar/Wind Harmer
3.948
962781AG1-127 GEN
Solar/Wind Harmer
8.621
939401AE1-172 GEN
Solar/Wind Harmer
6.775
274872LEEDK;1U
Solar/Wind Harmer
0.006
276901AD2-066 C O1
Solar/Wind Harmer
0.009
971997AH1-543 GEN
Solar/Wind Harmer
4.718
276861AD2-134 GEN
Solar/Wind Harmer
0.161
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
11.195
957471AF2-041 GEN
Solar/Wind Harmer
26.723
959081AF2-199 GEN
Solar/Wind Harmer
8.908
971067AG2-660 GEN
Solar/Wind Harmer
2.969
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
274822ROCKFORD ;11
Adder
24.978
972235AH1-702 GEN1
Adder
3.201
970819AG2-516 GEN
Solar/Wind Harmer
10.6
970569AG2-363 GEN
Solar/Wind Harmer
26.435
971475AH1-234 GEN
Solar/Wind Harmer
4.275
945371AF1-202 GEN
Solar/Wind Harmer
0.001
274857EASY ROAD;U1
Solar/Wind Harmer
0.002
274761LEE CO EC;2U
Adder
11.654
274766LEE CO EC;7U
Adder
11.517
276158O29GEN2
Solar/Wind Harmer
0.001
24791305MDL-5G
Solar/Wind Harmer
0.001
274877BISHOP HL;1U
Solar/Wind Harmer
0.289
276726Z2-087_GEN
Solar/Wind Harmer
0.003
939741AE1-205 GEN
Solar/Wind Harmer
11.942
274854TWINGROVE;U2
Solar/Wind Harmer
0.004
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
970291AG2-192 GEN
Solar/Wind Harmer
1.078
270032AE2-172
Solar/Wind Harmer
5.467
972175AH1-670 GEN
Solar/Wind Harmer
6.757
270005AE1-210 C O1
Solar/Wind Harmer
1.747
965031AG1-367 GEN
Solar/Wind Harmer
8.064
276903AD2-071 C
Solar/Wind Harmer
8.911
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963741AG1-226 GEN
Solar/Wind Harmer
18.836
970825AG2-519 GEN
Solar/Wind Harmer
2.823
963831AG1-236 GEN
Solar/Wind Harmer
3.095
276615X2-022 GEN
Solar/Wind Harmer
0.082
965911AG1-460 GEN
Solar/Wind Harmer
1.521
247536S-71 GEN
Solar/Wind Harmer
0.305
24728605AND G2
Adder
3.824
274693ROCKY RD ;1P
Adder
14.442
274697ROCKY RD ;3P
Adder
3.962
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
1.237
274683WAUKEGAN ;8U
Adder
27.535
274683WAUKEGAN ;8U
Adder
23.211
962691AG1-118 GEN
Solar/Wind Harmer
27.238
942221AE2-234 GEN
Solar/Wind Harmer
0.045
970921AG2-575 GEN
Solar/Wind Harmer
9.059
970921AG2-575 GEN
Solar/Wind Harmer
3.02
958491AF2-143 GEN
Solar/Wind Harmer
13.566
274879MINONK ;1U
Solar/Wind Harmer
0.38
942991AE2-321 GEN
Solar/Wind Harmer
10.048
270007AE1-245 C
Solar/Wind Harmer
0.002
971333AH1-146 GEN
Solar/Wind Harmer
17.91
971335AH1-147 GEN
Solar/Wind Harmer
17.91
971341AH1-150 GEN
Solar/Wind Harmer
17.815
971343AH1-151 GEN
Solar/Wind Harmer
17.815
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
970623AG2-406 GEN
Solar/Wind Harmer
1.621
274856ECOGROVE ;U1
Solar/Wind Harmer
0.208
276611AD2-172 GEN
Solar/Wind Harmer
0.002
938861AE1-114 GEN
Solar/Wind Harmer
4.97
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
274764LEE CO EC;5U
Adder
11.682
274765LEE CO EC;6U
Adder
11.682
274762LEE CO EC;3U
Adder
11.654
274763LEE CO EC;4U
Adder
11.544
276603SUBLETTE C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
5.169
276741O09 GEN1
Solar/Wind Harmer
0.308
276708O09 GEN2
Solar/Wind Harmer
0.308
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.339
276646AC1-214 GEN2
Solar/Wind Harmer
0.339
276782AC1-033 GEN
Solar/Wind Harmer
0.001
270599AE1-208 GEN
Solar/Wind Harmer
7.723
270031AE2-169
Solar/Wind Harmer
4.634
960611AF2-352 GEN
Solar/Wind Harmer
2.799
966841AG1-555 GEN
Solar/Wind Harmer
0.944
971613AH1-306 GEN
Solar/Wind Harmer
3.936
960441AF2-335 GEN
Solar/Wind Harmer
7.977
970241AG2-163 GEN
Solar/Wind Harmer
4.643
970825AG2-519 GEN
Solar/Wind Harmer
8.815
970621AG2-405 GEN
Solar/Wind Harmer
1.453
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
270201AC2-176 GEN
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
0.595
247621Y3-024
Adder
0.268
276916AD2-100_GEN
Solar/Wind Harmer
12.804
276911AD2-131_GEN
Solar/Wind Harmer
0.843
944201AF1-088_MTX
Adder
80.786
LAGNLTFEXP_LAGN->PJM
CLTF
11.481
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.982
TVALTFEXP_TVA->PJM
CLTF
4.813
CBM West 2LTFEXP_CBM-W2->PJM
CBM
98.823
NYPJM->LTFIMP_NY
CLTF
3.072
LGEELTFEXP_LGEE->PJM
CLTF
4.553
WECLTFEXP_WEC->PJM
CLTF
4.843
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.157
AG2-052LTFEXP_AG2-052->PJM
LTF
0.305
AH1-155LTFEXP_AH1-155->PJM
LTF
0.457
CBM West 1LTFEXP_CBM-W1->PJM
CBM
159.327
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.302
MECLTFEXP_MEC->PJM
CLTF
18.121
SIGELTFEXP_SIGE->PJM
CLTF
0.416

Details for 05MALIS-05VASSEL 765.0 kV Ckt 1 line l/o ATSI_P7-1_TE-345-027A_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MALIS-05VASSEL 765.0 kV Ckt 1 line
Contingency Name:
ATSI_P7-1_TE-345-027A_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:107.84 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4466.89
MW Contribution:19.68
Bus #Bus NameTypeMW Contribution
270142AC1-141 CT1_
50/50
2.745
24641605TWIN BRNCH
50/50
0.02
24344005CKG1
50/50
7.486
24642205MAYFLWER
50/50
0.768
944961AF1-161 GEN
50/50
3.289
962601AG1-109 GEN
50/50
3.289
970153AG2-106 GEN
Solar/Wind Harmer
35.618
970349AG2-230 GEN
Solar/Wind Harmer
17.891
270043AE2-236 GEN
Solar/Wind Harmer
6.493
970513AG2-328 GEN
Solar/Wind Harmer
21.006
970517AG2-330 GEN
Solar/Wind Harmer
19.052
247643Z2-116 C
Solar/Wind Harmer
0.08
945111AF1-176 GEN
Solar/Wind Harmer
6.428
970031AG2-029 GEN
Solar/Wind Harmer
34.05
959331AF2-224 GEN
Solar/Wind Harmer
11.324
965021AG1-366 GEN
Solar/Wind Harmer
2.634
944531AF1-118 GEN
Solar/Wind Harmer
39.305
274772LINCOLN ;3U
Adder
6.925
24441205WTRV SLR C
Solar/Wind Harmer
0.151
247604X1-042
Adder
0.462
274724RIVER EC ;11
Adder
19.633
972231SS25-0005
Solar/Wind Harmer
10.51
972181SS23-001
Solar/Wind Harmer
6.569
274752CRETE EC ;2U
Adder
5.413
274753CRETE EC ;3U
Adder
5.413
970707AG2-453 GEN
Solar/Wind Harmer
30.834
274802UNIV PARK;5U
Adder
6.406
274826FISK ;BP
Adder
12.027
276772AC2-154 GEN
Solar/Wind Harmer
3.062
276806AD2-047 C O1
Solar/Wind Harmer
11.745
970941AG2-585 GEN
Solar/Wind Harmer
13.724
274800UNIV PARK;3U
Adder
6.4
972038AH1-567 GEN2
Adder
0.401
972228AH1-698 GEN2
Adder
4.065
276897AD1-100 C
Solar/Wind Harmer
31.748
939351AE1-166 GEN
Solar/Wind Harmer
6.487
274676JOLIET 29;8U
Adder
32.29
274729ELWOOD EC;1P
Adder
17.909
274730ELWOOD EC;6P
Adder
17.909
274734ELWOOD EC;8P
Adder
17.909
274736ELWOOD EC;9P
Adder
17.909
276893AG1-478 C
Solar/Wind Harmer
0.455
270535AF1-215 GEN1
Solar/Wind Harmer
4.946
943121AE2-341 GEN
Solar/Wind Harmer
16.272
943591AF1-030 GEN
Solar/Wind Harmer
10.848
964401AG1-302 GEN
Solar/Wind Harmer
9.751
276694AA1-018 GEN2
Solar/Wind Harmer
6.779
274682WAUKEGAN ;7U
Adder
19.286
274872LEEDK;1U
Solar/Wind Harmer
0.273
276805AD2-038 GEN
Solar/Wind Harmer
5.464
959141AF2-205 GEN
Solar/Wind Harmer
6.424
276799AD1-013 GEN
Solar/Wind Harmer
2.339
946671AF1-331 GEN
Solar/Wind Harmer
0.443
274855GSG-6 ;RU
Solar/Wind Harmer
3.907
274850MENDOTA H;RU
Solar/Wind Harmer
2.716
276602WESTBROOK C
Solar/Wind Harmer
2.249
276863AD2-134 GEN
Solar/Wind Harmer
1.889
972236AH1-702 GEN2
Adder
2.298
274760LEE CO EC;1U
Adder
9.652
274767LEE CO EC;8U
Adder
9.538
24721905FLATG4
Adder
18.408
270102X2-052 ST
50/50
1.83
270100X2-052 CT1
50/50
1.686
270101X2-052 CT2
50/50
1.686
247620Y3-023
50/50
0.556
971599AH1-298 GEN
50/50
10.933
270144AC1-141 ST1_
50/50
2.431
24653605MOTTVILLE
50/50
0.004
24643105BUCHANAN
50/50
0.015
962771AG1-126 GEN
Solar/Wind Harmer
81.683
971347AH1-153 GEN
Solar/Wind Harmer
17.891
270071AF1-092 GEN
Solar/Wind Harmer
17.328
971771AH1-392 GEN
Solar/Wind Harmer
10.32
960681AF2-359 GEN
Solar/Wind Harmer
4.303
971769AH1-391 GEN
Solar/Wind Harmer
11.39
944161AF1-084 GEN
Solar/Wind Harmer
2.49
274775LINCOLN ;6U
Adder
6.925
274776LINCOLN ;7U
Adder
6.925
274777LINCOLN ;8U
Adder
6.925
24729505KEY G4
Adder
7.169
274814UNIV PK N;0U
Adder
5.572
274807UNIV PK N;3U
Adder
5.56
274805UNIV PK N;1U
Adder
5.536
274811UNIV PK N;7U
Adder
5.523
972037AH1-567 GEN1
Adder
0.201
274827FISK ;RP
Adder
8.524
960591AF2-350 GEN
Solar/Wind Harmer
10.979
972227AH1-698 GEN1
Adder
2.862
274687WILL CNTY;4U
Adder
30.524
274687WILL CNTY;4U
Adder
30.524
274675JOLIET 29;7U
Adder
33.487
274675JOLIET 29;7U
Adder
32.291
274731ELWOOD EC;2P
Adder
17.909
24344105CKG2
50/50
9.236
270143AC1-141 CT2_
50/50
2.745
24639705ELKHART HY
50/50
0.186
970521AG2-332 GEN
50/50
13.241
24307105BERRINSP G
50/50
0.025
962761AG1-125 GEN
Solar/Wind Harmer
81.683
970149AG2-104 GEN
Solar/Wind Harmer
100.878
970155AG2-107 GEN
Solar/Wind Harmer
35.618
970245AG2-165 GEN
Solar/Wind Harmer
21.006
270063AE2-323 C
Solar/Wind Harmer
2.513
270505AE1-170 C O1
Solar/Wind Harmer
17.093
945111AF1-176 GEN
Solar/Wind Harmer
20.281
965011AG1-365 GEN
Solar/Wind Harmer
11.324
270449AD2-020 GEN
Solar/Wind Harmer
3.171
943021AE2-325 GEN
Solar/Wind Harmer
4.12
972207SS24-0001
Solar/Wind Harmer
24.622
274773LINCOLN ;4U
Adder
6.925
274774LINCOLN ;5U
Adder
6.925
270349AD2-093_GEN
Solar/Wind Harmer
4.046
274723RIVER EC ;12
Adder
19.863
274751CRETE EC ;1U
Adder
5.413
274754CRETE EC ;4U
Adder
5.413
276164X3-005 C
Solar/Wind Harmer
0.776
970373AG2-245 GEN
Solar/Wind Harmer
23.188
274812UNIV PK N;8U
Adder
5.523
276776AD2-060 GEN
Solar/Wind Harmer
0.464
274801UNIV PARK;4U
Adder
6.4
941551AE2-152 GEN
Solar/Wind Harmer
4.962
274676JOLIET 29;8U
Adder
33.486
274674JOLIET 9 ;6U
Adder
16.785
274732ELWOOD EC;7P
Adder
17.909
270055AF2-134 C O1
Solar/Wind Harmer
3.297
274871GR RIDGE ;2U
Solar/Wind Harmer
8.367
274745AC1-111 GEN9
Adder
6.056
958381AF2-132 GEN
Solar/Wind Harmer
9.751
276691AA1-018 GEN1
Solar/Wind Harmer
0.5
964861AG1-349 GEN
Solar/Wind Harmer
8.438
971917AH1-482 GEN
Solar/Wind Harmer
9.737
274682WAUKEGAN ;7U
Adder
19.286
274828WAUKEGAN ;BP
Adder
11.843
960751AF2-366 GEN
Solar/Wind Harmer
3.061
962781AG1-127 GEN
Solar/Wind Harmer
10.147
939401AE1-172 GEN
Solar/Wind Harmer
14.86
274872LEEDK;1U
Solar/Wind Harmer
8.749
276901AD2-066 C O1
Solar/Wind Harmer
3.738
971997AH1-543 GEN
Solar/Wind Harmer
16.692
276861AD2-134 GEN
Solar/Wind Harmer
1.889
970615AG2-402 GEN
50/50
2.634
970321AG2-212 GEN
Solar/Wind Harmer
21.006
270216AD2-079_GEN
Solar/Wind Harmer
0.695
270526AF1-158 GEN
Solar/Wind Harmer
5.182
965681AG1-436 GEN
Solar/Wind Harmer
14.237
965791AG1-447 GEN
Solar/Wind Harmer
7.284
24441505OLIV SLR
Solar/Wind Harmer
0.153
957891AF2-083 GEN
Solar/Wind Harmer
3.84
960981AF2-389 GEN
Solar/Wind Harmer
1.721
961051AF2-396 GEN
Solar/Wind Harmer
17.989
961051AF2-396 GEN
Solar/Wind Harmer
8.367
970611AG2-400 GEN
Solar/Wind Harmer
11.324
274770LINCOLN ;1U
Adder
6.925
274771LINCOLN ;2U
Adder
6.925
270471AD2-092_GEN
Solar/Wind Harmer
4.046
274808UNIV PK N;4U
Adder
5.499
274803UNIV PARK;6U
Adder
6.406
972259AH1-714 GEN
Adder
20.95
274888KELLY CRK;1U
Solar/Wind Harmer
6.482
274887GEN-1.85
Solar/Wind Harmer
5.852
276843GEN-1.7
Solar/Wind Harmer
0.63
958011AF2-095 GEN
Solar/Wind Harmer
15.81
274674JOLIET 9 ;6U
Adder
16.785
274847GR RIDGE ;BU
Solar/Wind Harmer
5.504
971573AH1-285 GEN
Solar/Wind Harmer
9.291
274695ROCKY RD ;2P
Adder
11.962
274693ROCKY RD ;1P
Adder
11.844
274697ROCKY RD ;3P
Adder
3.25
274696ROCKY RD ;4P
Adder
12.244
958481AF2-142 GEN
Solar/Wind Harmer
16.113
274861TOP CROP ;1U
Solar/Wind Harmer
6.507
274862TOP CROP ;2U
Solar/Wind Harmer
5.433
274683WAUKEGAN ;8U
Adder
22.593
274683WAUKEGAN ;8U
Adder
19.044
962691AG1-118 GEN
Solar/Wind Harmer
32.066
970921AG2-575 GEN
Solar/Wind Harmer
10.67
970921AG2-575 GEN
Solar/Wind Harmer
2.481
958491AF2-143 GEN
Solar/Wind Harmer
15.976
274879MINONK ;1U
Solar/Wind Harmer
7.163
942991AE2-321 GEN
Solar/Wind Harmer
10.613
274764LEE CO EC;5U
Adder
9.675
274765LEE CO EC;6U
Adder
9.675
274762LEE CO EC;3U
Adder
9.652
274763LEE CO EC;4U
Adder
9.561
972267AH1-718 GEN
Adder
4.289
247621Y3-024
Adder
0.213
971333AH1-146 GEN
Solar/Wind Harmer
10.211
971335AH1-147 GEN
Solar/Wind Harmer
10.211
274822ROCKFORD ;11
Adder
20.615
972235AH1-702 GEN1
Adder
2.643
274761LEE CO EC;2U
Adder
9.652
274766LEE CO EC;7U
Adder
9.538
24721705FLATG2
Adder
18.408
274733ELWOOD EC;3P
Adder
17.909
274735ELWOOD EC;4P
Adder
17.909
274728ELWOOD EC;5P
Adder
17.909
270536AF1-215 GEN2
Solar/Wind Harmer
4.946
970833AG2-524 GEN
Solar/Wind Harmer
9.503
970833AG2-524 GEN
Solar/Wind Harmer
4.42
274746AC1-111 G10
Adder
6.056
274744AC1-111 GEN8
Adder
6.056
958391AF2-133 GEN
Solar/Wind Harmer
9.687
971549AH1-272 GEN
Solar/Wind Harmer
19.683
276868AE1-113 GEN
Solar/Wind Harmer
10.743
276882AE2-255 GEN
Solar/Wind Harmer
3.581
971177AH1-047 GEN
Solar/Wind Harmer
6.217
965041AG1-368 GEN
Solar/Wind Harmer
10.597
971675AH1-338 GEN
Solar/Wind Harmer
19.042
971411AH1-196 GEN
Solar/Wind Harmer
15.869
274823ROCKFORD ;21
Adder
20.465
LAGNLTFEXP_LAGN->PJM
CLTF
12.189
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.026
TVALTFEXP_TVA->PJM
CLTF
5.551
CPLELTFEXP_CPLE->PJM
CLTF
1.446
CBM West 2LTFEXP_CBM-W2->PJM
CBM
94.727
NYPJM->LTFIMP_NY
CLTF
2.961
LGEELTFEXP_LGEE->PJM
CLTF
4.354
WECLTFEXP_WEC->PJM
CLTF
4.001
AG2-052LTFEXP_AG2-052->PJM
LTF
0.249
AH1-155LTFEXP_AH1-155->PJM
LTF
0.374
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.664
CBM South 1LTFEXP_CBM-S1->PJM
CBM
21.379
MECLTFEXP_MEC->PJM
CLTF
15.566
SIGELTFEXP_SIGE->PJM
CLTF
0.382

Details for 05MALIS-05VASSEL 765.0 kV Ckt 1 line l/o ATSI_P7-1_TE-345-030_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MALIS-05VASSEL 765.0 kV Ckt 1 line
Contingency Name:
ATSI_P7-1_TE-345-030_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:107.63 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4457.9
MW Contribution:19.63
Bus #Bus NameTypeMW Contribution
971599AH1-298 GEN
50/50
10.925
270144AC1-141 ST1_
50/50
2.427
24653605MOTTVILLE
50/50
0.004
24643105BUCHANAN
50/50
0.015
962771AG1-126 GEN
Solar/Wind Harmer
81.688
270102X2-052 ST
50/50
1.828
270100X2-052 CT1
50/50
1.684
270101X2-052 CT2
50/50
1.684
247620Y3-023
50/50
0.555
970615AG2-402 GEN
50/50
2.632
970321AG2-212 GEN
Solar/Wind Harmer
20.986
270216AD2-079_GEN
Solar/Wind Harmer
0.694
270526AF1-158 GEN
Solar/Wind Harmer
5.175
965681AG1-436 GEN
Solar/Wind Harmer
14.219
965791AG1-447 GEN
Solar/Wind Harmer
7.275
24441505OLIV SLR
Solar/Wind Harmer
0.152
957891AF2-083 GEN
Solar/Wind Harmer
3.834
960981AF2-389 GEN
Solar/Wind Harmer
1.718
970611AG2-400 GEN
Solar/Wind Harmer
11.318
961051AF2-396 GEN
Solar/Wind Harmer
17.96
961051AF2-396 GEN
Solar/Wind Harmer
8.353
274770LINCOLN ;1U
Adder
6.918
274771LINCOLN ;2U
Adder
6.918
270471AD2-092_GEN
Solar/Wind Harmer
4.048
274808UNIV PK N;4U
Adder
5.493
274803UNIV PARK;6U
Adder
6.399
972259AH1-714 GEN
Adder
20.928
274888KELLY CRK;1U
Solar/Wind Harmer
6.475
274887GEN-1.85
Solar/Wind Harmer
5.846
276843GEN-1.7
Solar/Wind Harmer
0.629
958011AF2-095 GEN
Solar/Wind Harmer
15.793
274674JOLIET 9 ;6U
Adder
16.767
274847GR RIDGE ;BU
Solar/Wind Harmer
5.498
971573AH1-285 GEN
Solar/Wind Harmer
9.282
274695ROCKY RD ;2P
Adder
11.949
270142AC1-141 CT1_
50/50
2.74
24641605TWIN BRNCH
50/50
0.02
24344005CKG1
50/50
7.473
24642205MAYFLWER
50/50
0.767
944961AF1-161 GEN
50/50
3.283
962601AG1-109 GEN
50/50
3.283
970153AG2-106 GEN
Solar/Wind Harmer
35.62
970349AG2-230 GEN
Solar/Wind Harmer
17.87
270043AE2-236 GEN
Solar/Wind Harmer
6.488
970513AG2-328 GEN
Solar/Wind Harmer
20.986
970517AG2-330 GEN
Solar/Wind Harmer
19.034
247643Z2-116 C
Solar/Wind Harmer
0.08
945111AF1-176 GEN
Solar/Wind Harmer
6.417
970031AG2-029 GEN
Solar/Wind Harmer
34.012
959331AF2-224 GEN
Solar/Wind Harmer
11.318
965021AG1-366 GEN
Solar/Wind Harmer
2.632
944531AF1-118 GEN
Solar/Wind Harmer
39.282
274693ROCKY RD ;1P
Adder
11.832
274697ROCKY RD ;3P
Adder
3.246
274696ROCKY RD ;4P
Adder
12.231
958481AF2-142 GEN
Solar/Wind Harmer
16.096
274861TOP CROP ;1U
Solar/Wind Harmer
6.5
274862TOP CROP ;2U
Solar/Wind Harmer
5.428
274683WAUKEGAN ;8U
Adder
22.569
274683WAUKEGAN ;8U
Adder
19.024
962691AG1-118 GEN
Solar/Wind Harmer
32.032
970921AG2-575 GEN
Solar/Wind Harmer
10.658
970921AG2-575 GEN
Solar/Wind Harmer
2.479
958491AF2-143 GEN
Solar/Wind Harmer
15.959
274879MINONK ;1U
Solar/Wind Harmer
7.155
942991AE2-321 GEN
Solar/Wind Harmer
10.602
274764LEE CO EC;5U
Adder
9.665
274765LEE CO EC;6U
Adder
9.665
274762LEE CO EC;3U
Adder
9.642
274763LEE CO EC;4U
Adder
9.551
972267AH1-718 GEN
Adder
4.285
247621Y3-024
Adder
0.212
971333AH1-146 GEN
Solar/Wind Harmer
10.2
971335AH1-147 GEN
Solar/Wind Harmer
10.2
24344105CKG2
50/50
9.225
270143AC1-141 CT2_
50/50
2.74
24639705ELKHART HY
50/50
0.186
970521AG2-332 GEN
50/50
13.223
24307105BERRINSP G
50/50
0.025
962761AG1-125 GEN
Solar/Wind Harmer
81.688
970149AG2-104 GEN
Solar/Wind Harmer
100.885
970155AG2-107 GEN
Solar/Wind Harmer
35.62
970245AG2-165 GEN
Solar/Wind Harmer
20.986
270063AE2-323 C
Solar/Wind Harmer
2.51
270505AE1-170 C O1
Solar/Wind Harmer
17.065
945111AF1-176 GEN
Solar/Wind Harmer
20.248
965011AG1-365 GEN
Solar/Wind Harmer
11.318
270449AD2-020 GEN
Solar/Wind Harmer
3.166
943021AE2-325 GEN
Solar/Wind Harmer
4.113
972207SS24-0001
Solar/Wind Harmer
24.596
274773LINCOLN ;4U
Adder
6.918
971347AH1-153 GEN
Solar/Wind Harmer
17.87
270071AF1-092 GEN
Solar/Wind Harmer
17.316
971771AH1-392 GEN
Solar/Wind Harmer
10.305
960681AF2-359 GEN
Solar/Wind Harmer
4.298
971769AH1-391 GEN
Solar/Wind Harmer
11.374
944161AF1-084 GEN
Solar/Wind Harmer
2.485
274775LINCOLN ;6U
Adder
6.918
274776LINCOLN ;7U
Adder
6.918
274777LINCOLN ;8U
Adder
6.918
24729505KEY G4
Adder
7.164
274814UNIV PK N;0U
Adder
5.566
274807UNIV PK N;3U
Adder
5.554
274805UNIV PK N;1U
Adder
5.529
274811UNIV PK N;7U
Adder
5.517
972037AH1-567 GEN1
Adder
0.201
274827FISK ;RP
Adder
8.515
960591AF2-350 GEN
Solar/Wind Harmer
10.967
972227AH1-698 GEN1
Adder
2.859
274687WILL CNTY;4U
Adder
30.491
274687WILL CNTY;4U
Adder
30.491
274675JOLIET 29;7U
Adder
33.451
274675JOLIET 29;7U
Adder
32.256
274731ELWOOD EC;2P
Adder
17.89
274733ELWOOD EC;3P
Adder
17.89
274735ELWOOD EC;4P
Adder
17.89
274774LINCOLN ;5U
Adder
6.918
270349AD2-093_GEN
Solar/Wind Harmer
4.048
274723RIVER EC ;12
Adder
19.841
274751CRETE EC ;1U
Adder
5.407
274754CRETE EC ;4U
Adder
5.407
276164X3-005 C
Solar/Wind Harmer
0.776
970373AG2-245 GEN
Solar/Wind Harmer
23.16
274812UNIV PK N;8U
Adder
5.517
276776AD2-060 GEN
Solar/Wind Harmer
0.464
274801UNIV PARK;4U
Adder
6.393
941551AE2-152 GEN
Solar/Wind Harmer
4.956
274676JOLIET 29;8U
Adder
33.45
274674JOLIET 9 ;6U
Adder
16.767
274732ELWOOD EC;7P
Adder
17.89
270055AF2-134 C O1
Solar/Wind Harmer
3.293
274871GR RIDGE ;2U
Solar/Wind Harmer
8.358
274745AC1-111 GEN9
Adder
6.049
958381AF2-132 GEN
Solar/Wind Harmer
9.74
276691AA1-018 GEN1
Solar/Wind Harmer
0.5
964861AG1-349 GEN
Solar/Wind Harmer
8.428
971917AH1-482 GEN
Solar/Wind Harmer
9.726
274682WAUKEGAN ;7U
Adder
19.266
274828WAUKEGAN ;BP
Adder
11.83
960751AF2-366 GEN
Solar/Wind Harmer
3.058
962781AG1-127 GEN
Solar/Wind Harmer
10.136
939401AE1-172 GEN
Solar/Wind Harmer
14.845
274872LEEDK;1U
Solar/Wind Harmer
8.74
276901AD2-066 C O1
Solar/Wind Harmer
3.734
971997AH1-543 GEN
Solar/Wind Harmer
16.675
276861AD2-134 GEN
Solar/Wind Harmer
1.887
274822ROCKFORD ;11
Adder
20.593
972235AH1-702 GEN1
Adder
2.64
274761LEE CO EC;2U
Adder
9.642
274766LEE CO EC;7U
Adder
9.528
24721705FLATG2
Adder
18.409
274728ELWOOD EC;5P
Adder
17.89
270536AF1-215 GEN2
Solar/Wind Harmer
4.94
970833AG2-524 GEN
Solar/Wind Harmer
9.493
970833AG2-524 GEN
Solar/Wind Harmer
4.415
274746AC1-111 G10
Adder
6.049
274744AC1-111 GEN8
Adder
6.049
958391AF2-133 GEN
Solar/Wind Harmer
9.676
971549AH1-272 GEN
Solar/Wind Harmer
19.628
276868AE1-113 GEN
Solar/Wind Harmer
10.732
276882AE2-255 GEN
Solar/Wind Harmer
3.577
971177AH1-047 GEN
Solar/Wind Harmer
6.211
965041AG1-368 GEN
Solar/Wind Harmer
10.596
971675AH1-338 GEN
Solar/Wind Harmer
19.022
971411AH1-196 GEN
Solar/Wind Harmer
15.852
274823ROCKFORD ;21
Adder
20.444
274772LINCOLN ;3U
Adder
6.918
24441205WTRV SLR C
Solar/Wind Harmer
0.15
274724RIVER EC ;11
Adder
19.611
247604X1-042
Adder
0.461
972231SS25-0005
Solar/Wind Harmer
10.498
972181SS23-001
Solar/Wind Harmer
6.562
274752CRETE EC ;2U
Adder
5.407
274753CRETE EC ;3U
Adder
5.407
970707AG2-453 GEN
Solar/Wind Harmer
30.801
274802UNIV PARK;5U
Adder
6.399
274826FISK ;BP
Adder
12.014
276772AC2-154 GEN
Solar/Wind Harmer
3.058
276806AD2-047 C O1
Solar/Wind Harmer
11.733
970941AG2-585 GEN
Solar/Wind Harmer
13.709
274800UNIV PARK;3U
Adder
6.393
972038AH1-567 GEN2
Adder
0.4
972228AH1-698 GEN2
Adder
4.06
276897AD1-100 C
Solar/Wind Harmer
31.714
939351AE1-166 GEN
Solar/Wind Harmer
6.48
274676JOLIET 29;8U
Adder
32.256
274729ELWOOD EC;1P
Adder
17.89
274730ELWOOD EC;6P
Adder
17.89
274734ELWOOD EC;8P
Adder
17.89
274736ELWOOD EC;9P
Adder
17.89
276893AG1-478 C
Solar/Wind Harmer
0.454
270535AF1-215 GEN1
Solar/Wind Harmer
4.94
943121AE2-341 GEN
Solar/Wind Harmer
16.255
943591AF1-030 GEN
Solar/Wind Harmer
10.837
964401AG1-302 GEN
Solar/Wind Harmer
9.74
276694AA1-018 GEN2
Solar/Wind Harmer
6.772
274682WAUKEGAN ;7U
Adder
19.266
274872LEEDK;1U
Solar/Wind Harmer
0.272
276805AD2-038 GEN
Solar/Wind Harmer
5.458
959141AF2-205 GEN
Solar/Wind Harmer
6.417
276799AD1-013 GEN
Solar/Wind Harmer
2.337
946671AF1-331 GEN
Solar/Wind Harmer
0.443
274855GSG-6 ;RU
Solar/Wind Harmer
3.903
274850MENDOTA H;RU
Solar/Wind Harmer
2.714
276602WESTBROOK C
Solar/Wind Harmer
2.246
276863AD2-134 GEN
Solar/Wind Harmer
1.887
972236AH1-702 GEN2
Adder
2.296
274760LEE CO EC;1U
Adder
9.642
274767LEE CO EC;8U
Adder
9.528
24721905FLATG4
Adder
18.409
LAGNLTFEXP_LAGN->PJM
CLTF
12.179
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.018
TVALTFEXP_TVA->PJM
CLTF
5.547
CPLELTFEXP_CPLE->PJM
CLTF
1.443
CBM West 2LTFEXP_CBM-W2->PJM
CBM
94.648
NYPJM->LTFIMP_NY
CLTF
2.965
LGEELTFEXP_LGEE->PJM
CLTF
4.351
WECLTFEXP_WEC->PJM
CLTF
3.997
AG2-052LTFEXP_AG2-052->PJM
LTF
0.249
AH1-155LTFEXP_AH1-155->PJM
LTF
0.373
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.246
CBM South 1LTFEXP_CBM-S1->PJM
CBM
21.364
MECLTFEXP_MEC->PJM
CLTF
15.551
SIGELTFEXP_SIGE->PJM
CLTF
0.382

Details for 05MALIS-05VASSEL 765.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:AEP
Facility Description:
05MALIS-05VASSEL 765.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.2 %
Rating:4142.0 MVA
Rating Type:A
MVA to Mitigate:4150.44
MW Contribution:14.03
Bus #Bus NameTypeMW Contribution
971599AH1-298 GEN
50/50
10.4
270144AC1-141 ST1_
50/50
2.281
24653605MOTTVILLE
50/50
0.004
24643105BUCHANAN
50/50
0.014
962771AG1-126 GEN
Solar/Wind Harmer
68.224
971347AH1-153 GEN
Solar/Wind Harmer
11.817
270071AF1-092 GEN
Solar/Wind Harmer
14.657
971771AH1-392 GEN
Solar/Wind Harmer
7.525
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971769AH1-391 GEN
Solar/Wind Harmer
8.356
971619AH1-309 GEN
Solar/Wind Harmer
3.352
274775LINCOLN ;6U
Adder
8.941
274776LINCOLN ;7U
Adder
8.941
274777LINCOLN ;8U
Adder
8.941
24729505KEY G4
Adder
6.812
274814UNIV PK N;0U
Adder
5.276
274807UNIV PK N;3U
Adder
5.265
274805UNIV PK N;1U
Adder
5.242
274811UNIV PK N;7U
Adder
5.23
274827FISK ;RP
Adder
8.075
972037AH1-567 GEN1
Adder
0.19
960591AF2-350 GEN
Solar/Wind Harmer
7.258
972227AH1-698 GEN1
Adder
2.712
274687WILL CNTY;4U
Adder
28.924
274687WILL CNTY;4U
Adder
28.924
274675JOLIET 29;7U
Adder
31.734
274675JOLIET 29;7U
Adder
30.6
274731ELWOOD EC;2P
Adder
16.971
274733ELWOOD EC;3P
Adder
16.971
274735ELWOOD EC;4P
Adder
16.971
274728ELWOOD EC;5P
Adder
16.972
970833AG2-524 GEN
Solar/Wind Harmer
7.918
970833AG2-524 GEN
Solar/Wind Harmer
5.279
270536AF1-215 GEN2
Solar/Wind Harmer
0.009
274746AC1-111 G10
Adder
5.741
274744AC1-111 GEN8
Adder
5.741
958391AF2-133 GEN
Solar/Wind Harmer
0.001
276868AE1-113 GEN
Solar/Wind Harmer
1.408
276882AE2-255 GEN
Solar/Wind Harmer
0.821
971177AH1-047 GEN
Solar/Wind Harmer
4.327
270284AF1-227 GEN1
Solar/Wind Harmer
0.009
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
971675AH1-338 GEN
Solar/Wind Harmer
2.729
971411AH1-196 GEN
Solar/Wind Harmer
10.494
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
971611AH1-305 GEN
Solar/Wind Harmer
4.147
971171AH1-044 GEN
Solar/Wind Harmer
13.927
274823ROCKFORD ;21
Adder
19.398
276612AE2-035 GEN
Solar/Wind Harmer
0.002
965041AG1-368 GEN
Solar/Wind Harmer
6.907
926823AC1-168 GEN
Solar/Wind Harmer
1.173
970169AG2-114 GEN
Solar/Wind Harmer
6.898
971681AH1-341 GEN
Solar/Wind Harmer
11.079
965101AG1-375 GEN
Solar/Wind Harmer
6.878
963791AG1-232 GEN
Solar/Wind Harmer
9.223
961011AF2-392 GEN
Solar/Wind Harmer
4.004
957751AF2-069 GEN
Solar/Wind Harmer
0.224
971549AH1-272 GEN
Solar/Wind Harmer
14.025
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
965051AG1-369 GEN
Solar/Wind Harmer
3.359
276655WTG1_EQ
Solar/Wind Harmer
0.003
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.06
941731AE2-173 GEN
Solar/Wind Harmer
5.603
946321AF1-296 GEN
Solar/Wind Harmer
3.736
945581AF1-223 GEN
Solar/Wind Harmer
0.001
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
963841AG1-237 GEN
Solar/Wind Harmer
2.803
970289AG2-191 GEN
Solar/Wind Harmer
1.217
971609AH1-304 GEN
Solar/Wind Harmer
1.046
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.808
276849AB2-070 GEN2
Solar/Wind Harmer
0.233
276848AB2-070 GEN3
Solar/Wind Harmer
0.232
270594AE1-207 GEN
Solar/Wind Harmer
7.078
270024AE2-089 GEN
Solar/Wind Harmer
0.007
270578AF1-285 GEN2
Solar/Wind Harmer
0.412
247607V1-011 GEN
Solar/Wind Harmer
0.001
970115AG2-085 GEN
Solar/Wind Harmer
2.44
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
24344105CKG2
50/50
8.761
270143AC1-141 CT2_
50/50
2.576
24639705ELKHART HY
50/50
0.174
970521AG2-332 GEN
50/50
12.426
962761AG1-125 GEN
Solar/Wind Harmer
68.224
970149AG2-104 GEN
Solar/Wind Harmer
73.684
970155AG2-107 GEN
Solar/Wind Harmer
43.566
970245AG2-165 GEN
Solar/Wind Harmer
3.385
270349AD2-093_GEN
Solar/Wind Harmer
0.006
270063AE2-323 C
Solar/Wind Harmer
0.006
270505AE1-170 C O1
Solar/Wind Harmer
7.821
965011AG1-365 GEN
Solar/Wind Harmer
7.432
945111AF1-176 GEN
Solar/Wind Harmer
13.254
274773LINCOLN ;4U
Adder
8.941
274774LINCOLN ;5U
Adder
8.941
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
3.852
274723RIVER EC ;12
Adder
18.809
274751CRETE EC ;1U
Adder
8.637
274754CRETE EC ;4U
Adder
8.637
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
5.23
970373AG2-245 GEN
Solar/Wind Harmer
15.278
276776AD2-060 GEN
Solar/Wind Harmer
0.758
274801UNIV PARK;4U
Adder
6.064
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
31.733
274674JOLIET 9 ;6U
Adder
15.907
274732ELWOOD EC;7P
Adder
16.972
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0.006
274745AC1-111 GEN9
Adder
5.741
276691AA1-018 GEN1
Solar/Wind Harmer
0.86
274682WAUKEGAN ;7U
Adder
18.28
274828WAUKEGAN ;BP
Adder
11.225
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.202
962781AG1-127 GEN
Solar/Wind Harmer
6.715
939401AE1-172 GEN
Solar/Wind Harmer
5.274
274872LEEDK;1U
Solar/Wind Harmer
0.004
276901AD2-066 C O1
Solar/Wind Harmer
0.007
971997AH1-543 GEN
Solar/Wind Harmer
3.679
276861AD2-134 GEN
Solar/Wind Harmer
0.125
965651AG1-433 GEN
Solar/Wind Harmer
2.05
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.708
957471AF2-041 GEN
Solar/Wind Harmer
20.89
959081AF2-199 GEN
Solar/Wind Harmer
6.963
971067AG2-660 GEN
Solar/Wind Harmer
2.321
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
274822ROCKFORD ;11
Adder
19.54
972235AH1-702 GEN1
Adder
2.505
970819AG2-516 GEN
Solar/Wind Harmer
8.301
971475AH1-234 GEN
Solar/Wind Harmer
3.35
970569AG2-363 GEN
Solar/Wind Harmer
20.699
958861AF2-177 GEN
Solar/Wind Harmer
2.981
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
9.148
274766LEE CO EC;7U
Adder
9.041
276158O29GEN2
Solar/Wind Harmer
0.001
24791305MDL-5G
Solar/Wind Harmer
0.001
274877BISHOP HL;1U
Solar/Wind Harmer
0.227
247521TR3_G114
Solar/Wind Harmer
0.245
270246TR4_N_V150
Solar/Wind Harmer
0.043
276726Z2-087_GEN
Solar/Wind Harmer
0.002
939741AE1-205 GEN
Solar/Wind Harmer
9.414
945371AF1-202 GEN
Solar/Wind Harmer
0.001
944231AF1-091 GEN
Solar/Wind Harmer
1.771
274854TWINGROVE;U2
Solar/Wind Harmer
0.003
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.002
24695305TIMB G C
Solar/Wind Harmer
0.002
972175AH1-670 GEN
Solar/Wind Harmer
5.377
965421AG1-410 GEN
Solar/Wind Harmer
19.447
970291AG2-192 GEN
Solar/Wind Harmer
0.832
274880W4-005 GEN4
Solar/Wind Harmer
0.001
246936BC-WTG1
Solar/Wind Harmer
0.259
270489AE1-102 GEN1
Solar/Wind Harmer
0.83
963831AG1-236 GEN
Solar/Wind Harmer
2.479
963741AG1-226 GEN
Solar/Wind Harmer
15.028
270032AE2-172
Solar/Wind Harmer
4.213
276615X2-022 GEN
Solar/Wind Harmer
0.066
24721705FLATG2
Adder
18.123
270223U2-072_GEN1
Solar/Wind Harmer
0.001
276903AD2-071 C
Solar/Wind Harmer
6.907
270005AE1-210 C O1
Solar/Wind Harmer
1.338
965031AG1-367 GEN
Solar/Wind Harmer
6.174
965911AG1-460 GEN
Solar/Wind Harmer
1.231
970825AG2-519 GEN
Solar/Wind Harmer
2.158
270102X2-052 ST
50/50
1.727
270100X2-052 CT1
50/50
1.592
270101X2-052 CT2
50/50
1.592
247620Y3-023
50/50
0.521
970615AG2-402 GEN
50/50
2.477
970321AG2-212 GEN
Solar/Wind Harmer
3.385
270216AD2-079_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.006
965681AG1-436 GEN
Solar/Wind Harmer
9.376
965791AG1-447 GEN
Solar/Wind Harmer
6.876
270526AF1-158 GEN
Solar/Wind Harmer
0.009
24441505OLIV SLR
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
0.001
970611AG2-400 GEN
Solar/Wind Harmer
7.432
970627AG2-408 GEN
Solar/Wind Harmer
2.23
961051AF2-396 GEN
Solar/Wind Harmer
14.796
961051AF2-396 GEN
Solar/Wind Harmer
9.864
274770LINCOLN ;1U
Adder
8.941
274771LINCOLN ;2U
Adder
8.941
274808UNIV PK N;4U
Adder
5.207
972259AH1-714 GEN
Adder
19.859
274803UNIV PARK;6U
Adder
6.068
274888KELLY CRK;1U
Solar/Wind Harmer
0.426
274887GEN-1.85
Solar/Wind Harmer
0.191
276843GEN-1.7
Solar/Wind Harmer
0.235
958011AF2-095 GEN
Solar/Wind Harmer
10.451
274674JOLIET 9 ;6U
Adder
15.907
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
971573AH1-285 GEN
Solar/Wind Harmer
1.332
274695ROCKY RD ;2P
Adder
11.339
274693ROCKY RD ;1P
Adder
11.227
274697ROCKY RD ;3P
Adder
3.08
274696ROCKY RD ;4P
Adder
11.606
958481AF2-142 GEN
Solar/Wind Harmer
10.652
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.96
274683WAUKEGAN ;8U
Adder
21.414
274683WAUKEGAN ;8U
Adder
18.051
962691AG1-118 GEN
Solar/Wind Harmer
21.207
970921AG2-575 GEN
Solar/Wind Harmer
7.056
970921AG2-575 GEN
Solar/Wind Harmer
2.352
958491AF2-143 GEN
Solar/Wind Harmer
10.561
942991AE2-321 GEN
Solar/Wind Harmer
7.837
274879MINONK ;1U
Solar/Wind Harmer
0.296
971333AH1-146 GEN
Solar/Wind Harmer
13.985
971335AH1-147 GEN
Solar/Wind Harmer
13.985
944541AF1-119 GEN
Solar/Wind Harmer
0.468
960971AF2-388 GEN
Solar/Wind Harmer
4.1
971341AH1-150 GEN
Solar/Wind Harmer
13.927
971343AH1-151 GEN
Solar/Wind Harmer
13.927
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
274856ECOGROVE ;U1
Solar/Wind Harmer
0.163
276611AD2-172 GEN
Solar/Wind Harmer
0.002
938861AE1-114 GEN
Solar/Wind Harmer
3.898
274764LEE CO EC;5U
Adder
9.17
274765LEE CO EC;6U
Adder
9.17
274762LEE CO EC;3U
Adder
9.148
274763LEE CO EC;4U
Adder
9.062
276603SUBLETTE C
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
972267AH1-718 GEN
Adder
4.066
276741O09 GEN1
Solar/Wind Harmer
0.242
276708O09 GEN2
Solar/Wind Harmer
0.242
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.267
276646AC1-214 GEN2
Solar/Wind Harmer
0.267
276782AC1-033 GEN
Solar/Wind Harmer
0.001
942221AE2-234 GEN
Solar/Wind Harmer
0.034
960611AF2-352 GEN
Solar/Wind Harmer
2.214
966841AG1-555 GEN
Solar/Wind Harmer
0.746
270599AE1-208 GEN
Solar/Wind Harmer
5.869
270031AE2-169
Solar/Wind Harmer
3.522
246938BC-WTG3
Solar/Wind Harmer
0.231
246937BC-WTG2
Solar/Wind Harmer
0.259
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
970241AG2-163 GEN
Solar/Wind Harmer
3.704
971613AH1-306 GEN
Solar/Wind Harmer
3.033
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
270007AE1-245 C
Solar/Wind Harmer
0.002
276916AD2-100_GEN
Solar/Wind Harmer
12.852
276911AD2-131_GEN
Solar/Wind Harmer
0.847
960441AF2-335 GEN
Solar/Wind Harmer
6.101
970623AG2-406 GEN
Solar/Wind Harmer
1.115
970825AG2-519 GEN
Solar/Wind Harmer
6.738
270142AC1-141 CT1_
50/50
2.576
24641605TWIN BRNCH
50/50
0.019
270475AD2-096_GEN
50/50
6.265
24344005CKG1
50/50
7.016
24642205MAYFLWER
50/50
0.721
970153AG2-106 GEN
Solar/Wind Harmer
43.566
970349AG2-230 GEN
Solar/Wind Harmer
11.817
970513AG2-328 GEN
Solar/Wind Harmer
3.385
970517AG2-330 GEN
Solar/Wind Harmer
20.307
270043AE2-236 GEN
Solar/Wind Harmer
5
247643Z2-116 C
Solar/Wind Harmer
0
944531AF1-118 GEN
Solar/Wind Harmer
33.376
970031AG2-029 GEN
Solar/Wind Harmer
4.834
959331AF2-224 GEN
Solar/Wind Harmer
5.202
965021AG1-366 GEN
Solar/Wind Harmer
2.477
945111AF1-176 GEN
Solar/Wind Harmer
6.021
274772LINCOLN ;3U
Adder
8.941
274724RIVER EC ;11
Adder
18.592
274752CRETE EC ;2U
Adder
8.637
274753CRETE EC ;3U
Adder
8.637
970707AG2-453 GEN
Solar/Wind Harmer
23.798
274826FISK ;BP
Adder
11.395
274802UNIV PARK;5U
Adder
6.068
276806AD2-047 C O1
Solar/Wind Harmer
4.113
970941AG2-585 GEN
Solar/Wind Harmer
9.072
274800UNIV PARK;3U
Adder
6.064
972038AH1-567 GEN2
Adder
0.38
972228AH1-698 GEN2
Adder
3.852
24441205WTRV SLR C
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
0.01
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
274676JOLIET 29;8U
Adder
30.6
274729ELWOOD EC;1P
Adder
16.971
274730ELWOOD EC;6P
Adder
16.972
274734ELWOOD EC;8P
Adder
16.972
274736ELWOOD EC;9P
Adder
16.972
276893AG1-478 C
Solar/Wind Harmer
0.285
247604X1-042
Adder
0.429
270535AF1-215 GEN1
Solar/Wind Harmer
0.009
943121AE2-341 GEN
Solar/Wind Harmer
12.031
943591AF1-030 GEN
Solar/Wind Harmer
8
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
18.28
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274872LEEDK;1U
Solar/Wind Harmer
0.258
276805AD2-038 GEN
Solar/Wind Harmer
0.002
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.747
274855GSG-6 ;RU
Solar/Wind Harmer
0.257
274850MENDOTA H;RU
Solar/Wind Harmer
0.082
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.125
959091AF2-200 GEN
Solar/Wind Harmer
13.927
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
2.178
970571AG2-364 GEN
Solar/Wind Harmer
13.8
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
9.148
274767LEE CO EC;8U
Adder
9.041
276157O29GEN1
Solar/Wind Harmer
1.1
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.767
274878BISHOP HL;2U
Solar/Wind Harmer
0.227
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.043
942111AE2-223 GEN
Solar/Wind Harmer
2.185
965931AG1-462 GEN
Solar/Wind Harmer
16.944
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
965091AG1-374 GEN
Solar/Wind Harmer
19.925
959611AF2-252 GEN
Solar/Wind Harmer
2.214
247642Z2-115 C
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
0.704
970291AG2-192 GEN
Solar/Wind Harmer
0.64
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
2.949
270491AE1-102 GEN2
Solar/Wind Harmer
0.83
276668AB2-070 GEN1
Solar/Wind Harmer
0.233
276621W2-048 GEN
Solar/Wind Harmer
0.318
276838X2-022 GEN2
Solar/Wind Harmer
0.355
971617AH1-308 GEN
Solar/Wind Harmer
5.233
24721905FLATG4
Adder
18.123
270391AF1-285 GEN3
Solar/Wind Harmer
0.412
958821AF2-173 GEN
Solar/Wind Harmer
8.644
270004AE1-209 GEN
Solar/Wind Harmer
1.338
942481AE2-261 GEN
Solar/Wind Harmer
18.406
270258AD1-119 GEN
Solar/Wind Harmer
0.002
270404AC1-167 GEN
Solar/Wind Harmer
0.003
946031AF1-268 GEN
Solar/Wind Harmer
5.724
LAGNLTFEXP_LAGN->PJM
CLTF
11.568
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.749
TVALTFEXP_TVA->PJM
CLTF
5.27
CPLELTFEXP_CPLE->PJM
CLTF
1.403
CBM West 2LTFEXP_CBM-W2->PJM
CBM
89.76
NYPJM->LTFIMP_NY
CLTF
2.707
LGEELTFEXP_LGEE->PJM
CLTF
4.102
WECLTFEXP_WEC->PJM
CLTF
3.793
AG2-052LTFEXP_AG2-052->PJM
LTF
0.236
AH1-155LTFEXP_AH1-155->PJM
LTF
0.353
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.695
CBM South 1LTFEXP_CBM-S1->PJM
CBM
20.264
MECLTFEXP_MEC->PJM
CLTF
14.753
SIGELTFEXP_SIGE->PJM
CLTF
0.361

Details for 05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line l/o AP_P1-3_MP-765-501T_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Contingency Name:
AP_P1-3_MP-765-501T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:130.64 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5971.43
MW Contribution:16.35
Bus #Bus NameTypeMW Contribution
24722005FLATG5
50/50
1.795
24721905FLATG4
50/50
32.905
970153AG2-106 GEN
Solar/Wind Harmer
51.584
970513AG2-328 GEN
Solar/Wind Harmer
4.074
970517AG2-330 GEN
Solar/Wind Harmer
24.444
24721605FLATG1
50/50
1.795
971599AH1-298 GEN
50/50
12.157
962771AG1-126 GEN
Solar/Wind Harmer
80.781
971347AH1-153 GEN
Solar/Wind Harmer
14.036
270071AF1-092 GEN
Solar/Wind Harmer
17.319
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971771AH1-392 GEN
Solar/Wind Harmer
8.916
274775LINCOLN ;6U
Adder
10.782
274776LINCOLN ;7U
Adder
10.782
274777LINCOLN ;8U
Adder
10.782
971769AH1-391 GEN
Solar/Wind Harmer
9.94
971619AH1-309 GEN
Solar/Wind Harmer
3.958
274814UNIV PK N;0U
Adder
6.363
274807UNIV PK N;3U
Adder
6.35
274805UNIV PK N;1U
Adder
6.322
274811UNIV PK N;7U
Adder
6.308
274827FISK ;RP
Adder
9.754
972037AH1-567 GEN1
Adder
0.23
960591AF2-350 GEN
Solar/Wind Harmer
8.77
972227AH1-698 GEN1
Adder
3.278
274687WILL CNTY;4U
Adder
34.988
274687WILL CNTY;4U
Adder
34.988
274675JOLIET 29;7U
Adder
38.397
274675JOLIET 29;7U
Adder
37.026
274731ELWOOD EC;2P
Adder
20.542
274733ELWOOD EC;3P
Adder
20.542
274735ELWOOD EC;4P
Adder
20.542
274728ELWOOD EC;5P
Adder
20.542
970833AG2-524 GEN
Solar/Wind Harmer
9.589
970833AG2-524 GEN
Solar/Wind Harmer
6.393
274746AC1-111 G10
Adder
6.959
274744AC1-111 GEN8
Adder
6.959
24729505KEY G4
Adder
8.06
270536AF1-215 GEN2
Solar/Wind Harmer
0.011
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971177AH1-047 GEN
Solar/Wind Harmer
5.267
276868AE1-113 GEN
Solar/Wind Harmer
1.713
276882AE2-255 GEN
Solar/Wind Harmer
0.998
971675AH1-338 GEN
Solar/Wind Harmer
3.323
971411AH1-196 GEN
Solar/Wind Harmer
12.781
274863CRW1-WTG
Solar/Wind Harmer
0.003
274864CRW2-WTG
Solar/Wind Harmer
0.003
971171AH1-044 GEN
Solar/Wind Harmer
16.979
971611AH1-305 GEN
Solar/Wind Harmer
5.045
274823ROCKFORD ;21
Adder
23.66
276612AE2-035 GEN
Solar/Wind Harmer
0.002
926823AC1-168 GEN
Solar/Wind Harmer
1.432
970169AG2-114 GEN
Solar/Wind Harmer
8.423
971681AH1-341 GEN
Solar/Wind Harmer
13.539
961011AF2-392 GEN
Solar/Wind Harmer
4.902
957751AF2-069 GEN
Solar/Wind Harmer
0.275
24690905MDL-1G C
Solar/Wind Harmer
0.003
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0.002
276655WTG1_EQ
Solar/Wind Harmer
0.003
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
8.664
941731AE2-173 GEN
Solar/Wind Harmer
6.876
946321AF1-296 GEN
Solar/Wind Harmer
4.594
965101AG1-375 GEN
Solar/Wind Harmer
8.195
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
963841AG1-237 GEN
Solar/Wind Harmer
3.463
945581AF1-223 GEN
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
10.716
971549AH1-272 GEN
Solar/Wind Harmer
16.349
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.289
276848AB2-070 GEN3
Solar/Wind Harmer
0.287
965041AG1-368 GEN
Solar/Wind Harmer
7.862
970289AG2-191 GEN
Solar/Wind Harmer
1.476
971609AH1-304 GEN
Solar/Wind Harmer
1.254
270594AE1-207 GEN
Solar/Wind Harmer
8.574
965051AG1-369 GEN
Solar/Wind Harmer
3.795
944221AF1-090 GEN
Solar/Wind Harmer
4.425
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
270024AE2-089 GEN
Solar/Wind Harmer
0.008
970115AG2-085 GEN
Solar/Wind Harmer
2.943
270054AF2-122 C O1
Solar/Wind Helper
1.539
970349AG2-230 GEN
Solar/Wind Harmer
14.036
270043AE2-236 GEN
Solar/Wind Harmer
5.854
274772LINCOLN ;3U
Adder
10.782
247643Z2-116 C
Solar/Wind Harmer
0
24642205MAYFLWER
Adder
0.804
274724RIVER EC ;11
Adder
22.4
970707AG2-453 GEN
Solar/Wind Harmer
28.77
274752CRETE EC ;2U
Adder
10.401
274753CRETE EC ;3U
Adder
10.401
944531AF1-118 GEN
Solar/Wind Harmer
39.427
274826FISK ;BP
Adder
13.763
274802UNIV PARK;5U
Adder
7.329
276806AD2-047 C O1
Solar/Wind Harmer
4.97
970941AG2-585 GEN
Solar/Wind Harmer
10.962
972228AH1-698 GEN2
Adder
4.656
274800UNIV PARK;3U
Adder
7.326
972038AH1-567 GEN2
Adder
0.459
945111AF1-176 GEN
Solar/Wind Harmer
7.104
276897AD1-100 C
Solar/Wind Harmer
0.012
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
274676JOLIET 29;8U
Adder
37.026
274729ELWOOD EC;1P
Adder
20.542
274730ELWOOD EC;6P
Adder
20.542
274734ELWOOD EC;8P
Adder
20.542
274736ELWOOD EC;9P
Adder
20.542
276893AG1-478 C
Solar/Wind Harmer
0.345
970031AG2-029 GEN
Solar/Wind Harmer
5.657
943121AE2-341 GEN
Solar/Wind Harmer
14.583
943591AF1-030 GEN
Solar/Wind Harmer
9.698
270535AF1-215 GEN1
Solar/Wind Harmer
0.011
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
22.199
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274872LEEDK;1U
Solar/Wind Harmer
0.314
276805AD2-038 GEN
Solar/Wind Harmer
0.003
959331AF2-224 GEN
Solar/Wind Harmer
5.981
965021AG1-366 GEN
Solar/Wind Harmer
2.848
24441205WTRV SLR C
Solar/Wind Harmer
0
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
0.909
274855GSG-6 ;RU
Solar/Wind Harmer
0.313
274850MENDOTA H;RU
Solar/Wind Harmer
0.1
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.153
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
959091AF2-200 GEN
Solar/Wind Harmer
16.979
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
2.658
247604X1-042
Adder
0.505
970571AG2-364 GEN
Solar/Wind Harmer
16.847
274858EASY ROAD;U2
Solar/Wind Harmer
0.002
274760LEE CO EC;1U
Adder
11.187
274767LEE CO EC;8U
Adder
11.055
276157O29GEN1
Solar/Wind Harmer
1.347
274878BISHOP HL;2U
Solar/Wind Harmer
0.279
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
8.289
942111AE2-223 GEN
Solar/Wind Harmer
2.682
965931AG1-462 GEN
Solar/Wind Harmer
20.855
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
965091AG1-374 GEN
Solar/Wind Harmer
24.514
959611AF2-252 GEN
Solar/Wind Harmer
2.724
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
3.657
276668AB2-070 GEN1
Solar/Wind Harmer
0.289
247642Z2-115 C
Solar/Wind Harmer
0.003
276621W2-048 GEN
Solar/Wind Harmer
0.395
276838X2-022 GEN2
Solar/Wind Harmer
0.442
970289AG2-191 GEN
Solar/Wind Harmer
0.855
970291AG2-192 GEN
Solar/Wind Harmer
0.777
942481AE2-261 GEN
Solar/Wind Harmer
23.013
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.049
970193AG2-126 GEN
Solar/Wind Harmer
11.195
958821AF2-173 GEN
Solar/Wind Harmer
10.43
270004AE1-209 GEN
Solar/Wind Harmer
1.614
971617AH1-308 GEN
Solar/Wind Harmer
6.153
970243AG2-164 GEN
Solar/Wind Harmer
3.851
970519AG2-331 GEN
Solar/Wind Harmer
17.115
970699AG2-449 GEN
Solar/Wind Harmer
1.646
24721805FLATG3
50/50
1.795
24721705FLATG2
50/50
32.905
24344105CKG2
50/50
10.4
962761AG1-125 GEN
Solar/Wind Harmer
80.781
970149AG2-104 GEN
Solar/Wind Harmer
87.246
970155AG2-107 GEN
Solar/Wind Harmer
51.584
970245AG2-165 GEN
Solar/Wind Harmer
4.074
274773LINCOLN ;4U
Adder
10.782
274774LINCOLN ;5U
Adder
10.782
274723RIVER EC ;12
Adder
22.661
24639705ELKHART HY
Adder
0.194
276164X3-005 C
Solar/Wind Harmer
0
274751CRETE EC ;1U
Adder
10.401
274754CRETE EC ;4U
Adder
10.401
270505AE1-170 C O1
Solar/Wind Harmer
9.235
274812UNIV PK N;8U
Adder
6.308
276776AD2-060 GEN
Solar/Wind Harmer
0.916
274801UNIV PARK;4U
Adder
7.326
945111AF1-176 GEN
Solar/Wind Harmer
15.639
270063AE2-323 C
Solar/Wind Harmer
0.007
941551AE2-152 GEN
Solar/Wind Harmer
0.001
970373AG2-245 GEN
Solar/Wind Harmer
18.378
274676JOLIET 29;8U
Adder
38.397
274674JOLIET 9 ;6U
Adder
19.252
274732ELWOOD EC;7P
Adder
20.542
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
4.544
274745AC1-111 GEN9
Adder
6.959
270055AF2-134 C O1
Solar/Wind Harmer
0.007
276691AA1-018 GEN1
Solar/Wind Harmer
1.044
274682WAUKEGAN ;7U
Adder
22.199
274828WAUKEGAN ;BP
Adder
13.634
958381AF2-132 GEN
Solar/Wind Harmer
0.001
962781AG1-127 GEN
Solar/Wind Harmer
8.166
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
11.147
939401AE1-172 GEN
Solar/Wind Harmer
6.413
274872LEEDK;1U
Solar/Wind Harmer
0.005
276901AD2-066 C O1
Solar/Wind Harmer
0.008
965011AG1-365 GEN
Solar/Wind Harmer
8.544
971997AH1-543 GEN
Solar/Wind Harmer
4.478
276861AD2-134 GEN
Solar/Wind Harmer
0.153
957471AF2-041 GEN
Solar/Wind Harmer
25.469
959081AF2-199 GEN
Solar/Wind Harmer
8.49
971067AG2-660 GEN
Solar/Wind Harmer
2.83
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
10.593
274822ROCKFORD ;11
Adder
23.833
972235AH1-702 GEN1
Adder
3.057
970819AG2-516 GEN
Solar/Wind Harmer
10.134
971475AH1-234 GEN
Solar/Wind Harmer
4.092
970569AG2-363 GEN
Solar/Wind Harmer
25.271
274857EASY ROAD;U1
Solar/Wind Harmer
0.002
274761LEE CO EC;2U
Adder
11.187
274766LEE CO EC;7U
Adder
11.055
276158O29GEN2
Solar/Wind Harmer
0.001
965651AG1-433 GEN
Solar/Wind Harmer
2.438
274877BISHOP HL;1U
Solar/Wind Harmer
0.279
24791305MDL-5G
Solar/Wind Harmer
0.001
276726Z2-087_GEN
Solar/Wind Harmer
0.003
939741AE1-205 GEN
Solar/Wind Harmer
11.552
958861AF2-177 GEN
Solar/Wind Harmer
3.551
274854TWINGROVE;U2
Solar/Wind Harmer
0.003
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
972175AH1-670 GEN
Solar/Wind Harmer
6.643
945371AF1-202 GEN
Solar/Wind Harmer
0.001
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
3.078
963741AG1-226 GEN
Solar/Wind Harmer
18.629
276615X2-022 GEN
Solar/Wind Harmer
0.082
970291AG2-192 GEN
Solar/Wind Harmer
1.01
965911AG1-460 GEN
Solar/Wind Harmer
1.539
270032AE2-172
Solar/Wind Harmer
5.104
247521TR3_G114
Solar/Wind Harmer
0.277
270246TR4_N_V150
Solar/Wind Harmer
0.049
944231AF1-091 GEN
Solar/Wind Harmer
2.021
276903AD2-071 C
Solar/Wind Harmer
8.405
270005AE1-210 C O1
Solar/Wind Harmer
1.614
965031AG1-367 GEN
Solar/Wind Harmer
7.45
24695305TIMB G C
Solar/Wind Harmer
0.002
970333AG2-219 GEN
Solar/Wind Harmer
4.707
270102X2-052 ST
50/50
2.06
270100X2-052 CT1
50/50
1.898
270101X2-052 CT2
50/50
1.898
970321AG2-212 GEN
Solar/Wind Harmer
4.074
965681AG1-436 GEN
Solar/Wind Harmer
11.195
965791AG1-447 GEN
Solar/Wind Harmer
8.21
274770LINCOLN ;1U
Adder
10.782
274771LINCOLN ;2U
Adder
10.782
270526AF1-158 GEN
Solar/Wind Harmer
0.011
24441505OLIV SLR
Solar/Wind Harmer
0
270216AD2-079_GEN
Solar/Wind Harmer
0.001
957891AF2-083 GEN
Solar/Wind Harmer
0.001
274808UNIV PK N;4U
Adder
6.281
972259AH1-714 GEN
Adder
24.011
274803UNIV PARK;6U
Adder
7.329
274888KELLY CRK;1U
Solar/Wind Harmer
0.515
274887GEN-1.85
Solar/Wind Harmer
0.231
276843GEN-1.7
Solar/Wind Harmer
0.284
958011AF2-095 GEN
Solar/Wind Harmer
12.628
247620Y3-023
Adder
0.578
961051AF2-396 GEN
Solar/Wind Harmer
17.455
961051AF2-396 GEN
Solar/Wind Harmer
11.637
274674JOLIET 9 ;6U
Adder
19.252
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
971573AH1-285 GEN
Solar/Wind Harmer
1.615
274696ROCKY RD ;4P
Adder
14.093
274695ROCKY RD ;2P
Adder
13.768
274693ROCKY RD ;1P
Adder
13.632
274697ROCKY RD ;3P
Adder
3.74
958481AF2-142 GEN
Solar/Wind Harmer
12.927
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
1.166
274683WAUKEGAN ;8U
Adder
26.009
274683WAUKEGAN ;8U
Adder
21.925
962691AG1-118 GEN
Solar/Wind Harmer
25.779
970921AG2-575 GEN
Solar/Wind Harmer
8.581
970921AG2-575 GEN
Solar/Wind Harmer
2.86
958491AF2-143 GEN
Solar/Wind Harmer
12.84
970611AG2-400 GEN
Solar/Wind Harmer
8.544
970627AG2-408 GEN
Solar/Wind Harmer
2.563
942991AE2-321 GEN
Solar/Wind Harmer
9.539
274879MINONK ;1U
Solar/Wind Harmer
0.36
971333AH1-146 GEN
Solar/Wind Harmer
17.035
971335AH1-147 GEN
Solar/Wind Harmer
17.035
971341AH1-150 GEN
Solar/Wind Harmer
16.979
971343AH1-151 GEN
Solar/Wind Harmer
16.979
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
274856ECOGROVE ;U1
Solar/Wind Harmer
0.199
276611AD2-172 GEN
Solar/Wind Harmer
0.002
938861AE1-114 GEN
Solar/Wind Harmer
4.764
274764LEE CO EC;5U
Adder
11.213
274765LEE CO EC;6U
Adder
11.213
274762LEE CO EC;3U
Adder
11.187
274763LEE CO EC;4U
Adder
11.081
276603SUBLETTE C
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
972267AH1-718 GEN
Adder
4.979
276741O09 GEN1
Solar/Wind Harmer
0.297
276708O09 GEN2
Solar/Wind Harmer
0.297
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.327
276646AC1-214 GEN2
Solar/Wind Harmer
0.327
944541AF1-119 GEN
Solar/Wind Harmer
0.557
960971AF2-388 GEN
Solar/Wind Harmer
4.876
276782AC1-033 GEN
Solar/Wind Harmer
0.001
960611AF2-352 GEN
Solar/Wind Harmer
2.724
966841AG1-555 GEN
Solar/Wind Harmer
0.919
942221AE2-234 GEN
Solar/Wind Harmer
0.04
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
970241AG2-163 GEN
Solar/Wind Harmer
4.592
270599AE1-208 GEN
Solar/Wind Harmer
7.039
270031AE2-169
Solar/Wind Harmer
4.223
276916AD2-100_GEN
Solar/Wind Harmer
16.09
276911AD2-131_GEN
Solar/Wind Harmer
1.06
971613AH1-306 GEN
Solar/Wind Harmer
3.675
945391AF1-204 GEN
Solar/Wind Harmer
7.93
960441AF2-335 GEN
Solar/Wind Harmer
7.358
970239AG2-162 GEN
Solar/Wind Harmer
1.646
944201AF1-088_MTX
Adder
118.46
957141AF2-008_MTX
Adder
32.732
LAGNLTFEXP_LAGN->PJM
CLTF
16.296
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.027
TVALTFEXP_TVA->PJM
CLTF
7.706
CPLELTFEXP_CPLE->PJM
CLTF
3.24
CBM West 2LTFEXP_CBM-W2->PJM
CBM
120.262
NYPJM->LTFIMP_NY
CLTF
3.756
LGEELTFEXP_LGEE->PJM
CLTF
5.526
WECLTFEXP_WEC->PJM
CLTF
4.63
AG2-052LTFEXP_AG2-052->PJM
LTF
0.285
AH1-155LTFEXP_AH1-155->PJM
LTF
0.428
CBM West 1LTFEXP_CBM-W1->PJM
CBM
146.812
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.167
MECLTFEXP_MEC->PJM
CLTF
18.496
SIGELTFEXP_SIGE->PJM
CLTF
0.474

Details for 05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line l/o AEP_P1-2_#706_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#706_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.18 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5310.77
MW Contribution:19.68
Bus #Bus NameTypeMW Contribution
24722005FLATG5
50/50
5.145
24721905FLATG4
50/50
94.33
270475AD2-096_GEN
50/50
10.026
270142AC1-141 CT1_
50/50
3.558
24641605TWIN BRNCH
50/50
0.026
24344005CKG1
50/50
9.691
24642205MAYFLWER
50/50
0.992
944961AF1-161 GEN
50/50
4.253
962601AG1-109 GEN
50/50
4.253
247604X1-042
50/50
0.632
970153AG2-106 GEN
Solar/Wind Harmer
76.659
270043AE2-236 GEN
Solar/Wind Harmer
6.969
970349AG2-230 GEN
Solar/Wind Harmer
16.236
959331AF2-224 GEN
Solar/Wind Harmer
7.376
965021AG1-366 GEN
Solar/Wind Harmer
3.512
970513AG2-328 GEN
Solar/Wind Harmer
4.559
970517AG2-330 GEN
Solar/Wind Harmer
27.357
247643Z2-116 C
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
6.732
945111AF1-176 GEN
Solar/Wind Harmer
8.323
944531AF1-118 GEN
Solar/Wind Harmer
45.595
24441205WTRV SLR C
Solar/Wind Harmer
0
274772LINCOLN ;3U
Adder
11.972
274724RIVER EC ;11
Adder
24.913
274752CRETE EC ;2U
Adder
11.58
274753CRETE EC ;3U
Adder
11.58
270391AF1-285 GEN3
Solar/Wind Harmer
0.651
970707AG2-453 GEN
Solar/Wind Harmer
31.724
274802UNIV PARK;5U
Adder
8.1
274826FISK ;BP
Adder
15.205
274800UNIV PARK;3U
Adder
8.089
972038AH1-567 GEN2
Adder
0.506
276806AD2-047 C O1
Solar/Wind Harmer
5.485
970941AG2-585 GEN
Solar/Wind Harmer
12.1
972228AH1-698 GEN2
Adder
5.135
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.062
276897AD1-100 C
Solar/Wind Harmer
0.013
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
274676JOLIET 29;8U
Adder
40.714
274730ELWOOD EC;6P
Adder
22.567
274734ELWOOD EC;8P
Adder
22.567
274736ELWOOD EC;9P
Adder
22.567
274729ELWOOD EC;1P
Adder
22.566
276893AG1-478 C
Solar/Wind Harmer
0.379
270535AF1-215 GEN1
Solar/Wind Harmer
0.012
943121AE2-341 GEN
Solar/Wind Harmer
15.96
943591AF1-030 GEN
Solar/Wind Harmer
10.614
964401AG1-302 GEN
Solar/Wind Harmer
0.001
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
24.169
270491AE1-102 GEN2
Solar/Wind Harmer
1.214
270485AE1-090_GEN
Solar/Wind Harmer
0.001
276805AD2-038 GEN
Solar/Wind Harmer
0.003
274872LEEDK;1U
Solar/Wind Harmer
0.341
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
0.982
274855GSG-6 ;RU
Solar/Wind Harmer
0.337
274850MENDOTA H;RU
Solar/Wind Harmer
0.108
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.165
959091AF2-200 GEN
Solar/Wind Harmer
18.285
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
2.856
970571AG2-364 GEN
Solar/Wind Harmer
18.064
274858EASY ROAD;U2
Solar/Wind Harmer
0.002
274760LEE CO EC;1U
Adder
11.947
274767LEE CO EC;8U
Adder
11.806
276157O29GEN1
Solar/Wind Harmer
1.431
270258AD1-119 GEN
Solar/Wind Harmer
0.002
274878BISHOP HL;2U
Solar/Wind Harmer
0.295
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
8.785
270404AC1-167 GEN
Solar/Wind Harmer
0.004
942111AE2-223 GEN
Solar/Wind Harmer
2.831
965931AG1-462 GEN
Solar/Wind Harmer
21.861
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
965091AG1-374 GEN
Solar/Wind Harmer
25.685
959611AF2-252 GEN
Solar/Wind Harmer
2.854
971617AH1-308 GEN
Solar/Wind Harmer
7.03
247642Z2-115 C
Solar/Wind Harmer
0.004
970289AG2-191 GEN
Solar/Wind Harmer
0.914
970291AG2-192 GEN
Solar/Wind Harmer
0.831
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
3.74
276668AB2-070 GEN1
Solar/Wind Harmer
0.295
958821AF2-173 GEN
Solar/Wind Harmer
11.2
270004AE1-209 GEN
Solar/Wind Harmer
1.733
276621W2-048 GEN
Solar/Wind Harmer
0.401
276838X2-022 GEN2
Solar/Wind Harmer
0.448
946031AF1-268 GEN
Solar/Wind Harmer
7.422
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
11.672
942481AE2-261 GEN
Solar/Wind Harmer
22.986
24728705AND G3
Adder
7.82
24728505AND G1
Adder
3.739
24721605FLATG1
50/50
5.145
971599AH1-298 GEN
50/50
14.587
270144AC1-141 ST1_
50/50
3.152
24653605MOTTVILLE
50/50
0.006
24643105BUCHANAN
50/50
0.019
962771AG1-126 GEN
Solar/Wind Harmer
120.047
270284AF1-227 GEN1
Solar/Wind Harmer
0.014
270286AF1-227 GEN2
Solar/Wind Harmer
0.006
270287AF1-227 GEN3
Solar/Wind Harmer
0.006
971347AH1-153 GEN
Solar/Wind Harmer
16.236
270071AF1-092 GEN
Solar/Wind Harmer
20.132
971771AH1-392 GEN
Solar/Wind Harmer
10.346
971619AH1-309 GEN
Solar/Wind Harmer
4.631
971769AH1-391 GEN
Solar/Wind Harmer
11.424
960681AF2-359 GEN
Solar/Wind Harmer
-0.002
24729505KEY G4
Adder
9.267
274775LINCOLN ;6U
Adder
11.972
274776LINCOLN ;7U
Adder
11.972
274777LINCOLN ;8U
Adder
11.972
965041AG1-368 GEN
Solar/Wind Harmer
9.847
270578AF1-285 GEN2
Solar/Wind Harmer
0.651
274814UNIV PK N;0U
Adder
7.057
274807UNIV PK N;3U
Adder
7.042
274805UNIV PK N;1U
Adder
7.011
274811UNIV PK N;7U
Adder
6.996
972037AH1-567 GEN1
Adder
0.254
274827FISK ;RP
Adder
10.776
960591AF2-350 GEN
Solar/Wind Harmer
9.68
972227AH1-698 GEN1
Adder
3.616
965051AG1-369 GEN
Solar/Wind Harmer
4.807
274687WILL CNTY;4U
Adder
38.503
274687WILL CNTY;4U
Adder
38.503
274675JOLIET 29;7U
Adder
42.223
274675JOLIET 29;7U
Adder
40.715
274728ELWOOD EC;5P
Adder
22.567
274731ELWOOD EC;2P
Adder
22.566
274733ELWOOD EC;3P
Adder
22.566
274735ELWOOD EC;4P
Adder
22.566
270536AF1-215 GEN2
Solar/Wind Harmer
0.012
970833AG2-524 GEN
Solar/Wind Harmer
10.52
970833AG2-524 GEN
Solar/Wind Harmer
7.013
971549AH1-272 GEN
Solar/Wind Harmer
19.681
274746AC1-111 G10
Adder
7.614
274744AC1-111 GEN8
Adder
7.614
963791AG1-232 GEN
Solar/Wind Harmer
12.76
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
1.183
270302AB2-170 GEN
Solar/Wind Harmer
0.006
270317AD1-130_GEN
Solar/Wind Harmer
0.013
971653AH1-327 GEN
Solar/Wind Harmer
1.314
958391AF2-133 GEN
Solar/Wind Harmer
0.001
276868AE1-113 GEN
Solar/Wind Harmer
1.855
276882AE2-255 GEN
Solar/Wind Harmer
1.081
971177AH1-047 GEN
Solar/Wind Harmer
5.697
965101AG1-375 GEN
Solar/Wind Harmer
9.202
971411AH1-196 GEN
Solar/Wind Harmer
13.802
971675AH1-338 GEN
Solar/Wind Harmer
3.588
274863CRW1-WTG
Solar/Wind Harmer
0.003
274864CRW2-WTG
Solar/Wind Harmer
0.003
971611AH1-305 GEN
Solar/Wind Harmer
5.454
971171AH1-044 GEN
Solar/Wind Harmer
18.285
274823ROCKFORD ;21
Adder
25.447
276612AE2-035 GEN
Solar/Wind Harmer
0.002
926823AC1-168 GEN
Solar/Wind Harmer
1.535
970169AG2-114 GEN
Solar/Wind Harmer
9.023
971681AH1-341 GEN
Solar/Wind Harmer
14.483
247607V1-011 GEN
Solar/Wind Harmer
0.001
961011AF2-392 GEN
Solar/Wind Harmer
5.219
945581AF1-223 GEN
Solar/Wind Harmer
0.001
957751AF2-069 GEN
Solar/Wind Harmer
0.292
24690905MDL-1G C
Solar/Wind Harmer
0.003
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0.002
276655WTG1_EQ
Solar/Wind Harmer
0.003
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
9.145
941731AE2-173 GEN
Solar/Wind Harmer
7.258
946321AF1-296 GEN
Solar/Wind Harmer
4.827
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
270024AE2-089 GEN
Solar/Wind Harmer
0.009
971609AH1-304 GEN
Solar/Wind Harmer
1.375
970289AG2-191 GEN
Solar/Wind Harmer
1.578
963841AG1-237 GEN
Solar/Wind Harmer
3.575
270594AE1-207 GEN
Solar/Wind Harmer
9.172
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.295
276848AB2-070 GEN3
Solar/Wind Harmer
0.294
970115AG2-085 GEN
Solar/Wind Harmer
3.159
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
270297AD1-101 GEN
Solar/Wind Harmer
0.002
24721805FLATG3
50/50
5.145
24721705FLATG2
50/50
94.33
24344105CKG2
50/50
12.069
270143AC1-141 CT2_
50/50
3.558
24639705ELKHART HY
50/50
0.241
970521AG2-332 GEN
50/50
17.184
24307105BERRINSP G
50/50
0.032
962761AG1-125 GEN
Solar/Wind Harmer
120.047
970149AG2-104 GEN
Solar/Wind Harmer
129.655
970155AG2-107 GEN
Solar/Wind Harmer
76.659
270349AD2-093_GEN
Solar/Wind Harmer
0.009
965011AG1-365 GEN
Solar/Wind Harmer
10.537
970245AG2-165 GEN
Solar/Wind Harmer
4.559
270063AE2-323 C
Solar/Wind Harmer
0.008
270505AE1-170 C O1
Solar/Wind Harmer
10.806
945111AF1-176 GEN
Solar/Wind Harmer
18.321
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
5.329
274773LINCOLN ;4U
Adder
11.972
274774LINCOLN ;5U
Adder
11.972
274723RIVER EC ;12
Adder
25.205
274751CRETE EC ;1U
Adder
11.58
274754CRETE EC ;4U
Adder
11.58
270223U2-072_GEN1
Solar/Wind Harmer
0.001
276164X3-005 C
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
20.506
274812UNIV PK N;8U
Adder
6.996
274801UNIV PARK;4U
Adder
8.089
276776AD2-060 GEN
Solar/Wind Harmer
1.011
247521TR3_G114
Solar/Wind Harmer
0.351
270246TR4_N_V150
Solar/Wind Harmer
0.062
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
42.222
274674JOLIET 9 ;6U
Adder
21.154
274732ELWOOD EC;7P
Adder
22.567
270055AF2-134 C O1
Solar/Wind Harmer
0.007
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
274745AC1-111 GEN9
Adder
7.614
944231AF1-091 GEN
Solar/Wind Harmer
2.532
24695305TIMB G C
Solar/Wind Harmer
0.002
965421AG1-410 GEN
Solar/Wind Harmer
28.36
958381AF2-132 GEN
Solar/Wind Harmer
0.001
276691AA1-018 GEN1
Solar/Wind Harmer
1.138
965651AG1-433 GEN
Solar/Wind Harmer
2.755
274682WAUKEGAN ;7U
Adder
24.169
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
12.195
274828WAUKEGAN ;BP
Adder
14.836
246936BC-WTG1
Solar/Wind Harmer
0.379
270489AE1-102 GEN1
Solar/Wind Harmer
1.214
270462AD2-086
Solar/Wind Harmer
0.02
962781AG1-127 GEN
Solar/Wind Harmer
8.858
939401AE1-172 GEN
Solar/Wind Harmer
6.954
274872LEEDK;1U
Solar/Wind Harmer
0.006
276901AD2-066 C O1
Solar/Wind Harmer
0.009
971997AH1-543 GEN
Solar/Wind Harmer
4.843
958861AF2-177 GEN
Solar/Wind Harmer
3.987
276861AD2-134 GEN
Solar/Wind Harmer
0.165
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
11.452
957471AF2-041 GEN
Solar/Wind Harmer
27.428
959081AF2-199 GEN
Solar/Wind Harmer
9.143
971067AG2-660 GEN
Solar/Wind Harmer
3.048
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
274822ROCKFORD ;11
Adder
25.633
972235AH1-702 GEN1
Adder
3.284
970819AG2-516 GEN
Solar/Wind Harmer
10.874
971475AH1-234 GEN
Solar/Wind Harmer
4.385
970569AG2-363 GEN
Solar/Wind Harmer
27.095
274857EASY ROAD;U1
Solar/Wind Harmer
0.002
274761LEE CO EC;2U
Adder
11.947
274766LEE CO EC;7U
Adder
11.806
276158O29GEN2
Solar/Wind Harmer
0.001
945371AF1-202 GEN
Solar/Wind Harmer
0.001
274877BISHOP HL;1U
Solar/Wind Harmer
0.295
24791305MDL-5G
Solar/Wind Harmer
0.001
276726Z2-087_GEN
Solar/Wind Harmer
0.003
939741AE1-205 GEN
Solar/Wind Harmer
12.194
274854TWINGROVE;U2
Solar/Wind Harmer
0.004
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
972175AH1-670 GEN
Solar/Wind Harmer
6.873
970291AG2-192 GEN
Solar/Wind Harmer
1.08
270032AE2-172
Solar/Wind Harmer
5.46
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
3.14
963741AG1-226 GEN
Solar/Wind Harmer
19.026
270005AE1-210 C O1
Solar/Wind Harmer
1.733
965031AG1-367 GEN
Solar/Wind Harmer
8
276615X2-022 GEN
Solar/Wind Harmer
0.084
276903AD2-071 C
Solar/Wind Harmer
8.872
970825AG2-519 GEN
Solar/Wind Harmer
2.793
965911AG1-460 GEN
Solar/Wind Harmer
1.538
24728605AND G2
Adder
3.739
970615AG2-402 GEN
50/50
3.512
247620Y3-023
50/50
0.722
270102X2-052 ST
50/50
2.354
270100X2-052 CT1
50/50
2.169
270101X2-052 CT2
50/50
2.169
270471AD2-092_GEN
Solar/Wind Harmer
0.009
970611AG2-400 GEN
Solar/Wind Harmer
10.537
970627AG2-408 GEN
Solar/Wind Harmer
3.161
970321AG2-212 GEN
Solar/Wind Harmer
4.559
270216AD2-079_GEN
Solar/Wind Harmer
0.002
957891AF2-083 GEN
Solar/Wind Harmer
0.001
270526AF1-158 GEN
Solar/Wind Harmer
0.013
24441505OLIV SLR
Solar/Wind Harmer
0
961051AF2-396 GEN
Solar/Wind Harmer
20.46
961051AF2-396 GEN
Solar/Wind Harmer
13.64
965681AG1-436 GEN
Solar/Wind Harmer
12.752
965791AG1-447 GEN
Solar/Wind Harmer
9.351
274770LINCOLN ;1U
Adder
11.972
274771LINCOLN ;2U
Adder
11.972
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
274808UNIV PK N;4U
Adder
6.965
274803UNIV PARK;6U
Adder
8.1
274888KELLY CRK;1U
Solar/Wind Harmer
0.568
274887GEN-1.85
Solar/Wind Harmer
0.255
276843GEN-1.7
Solar/Wind Harmer
0.313
958011AF2-095 GEN
Solar/Wind Harmer
13.939
972259AH1-714 GEN
Adder
26.463
274674JOLIET 9 ;6U
Adder
21.154
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
971573AH1-285 GEN
Solar/Wind Harmer
1.764
958481AF2-142 GEN
Solar/Wind Harmer
14.096
274695ROCKY RD ;2P
Adder
14.996
274693ROCKY RD ;1P
Adder
14.848
274697ROCKY RD ;3P
Adder
4.074
274696ROCKY RD ;4P
Adder
15.349
274861TOP CROP ;1U
Solar/Wind Harmer
0.003
274862TOP CROP ;2U
Solar/Wind Harmer
1.271
944541AF1-119 GEN
Solar/Wind Harmer
0.629
960971AF2-388 GEN
Solar/Wind Harmer
5.509
274683WAUKEGAN ;8U
Adder
28.303
274683WAUKEGAN ;8U
Adder
23.858
246938BC-WTG3
Solar/Wind Harmer
0.338
246937BC-WTG2
Solar/Wind Harmer
0.379
962691AG1-118 GEN
Solar/Wind Harmer
27.992
970921AG2-575 GEN
Solar/Wind Harmer
9.308
970921AG2-575 GEN
Solar/Wind Harmer
3.103
958491AF2-143 GEN
Solar/Wind Harmer
13.931
274879MINONK ;1U
Solar/Wind Harmer
0.39
942991AE2-321 GEN
Solar/Wind Harmer
10.32
971333AH1-146 GEN
Solar/Wind Harmer
18.389
971335AH1-147 GEN
Solar/Wind Harmer
18.389
971341AH1-150 GEN
Solar/Wind Harmer
18.285
971343AH1-151 GEN
Solar/Wind Harmer
18.285
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
942221AE2-234 GEN
Solar/Wind Harmer
0.046
274856ECOGROVE ;U1
Solar/Wind Harmer
0.213
276611AD2-172 GEN
Solar/Wind Harmer
0.002
938861AE1-114 GEN
Solar/Wind Harmer
5.096
274764LEE CO EC;5U
Adder
11.975
274765LEE CO EC;6U
Adder
11.975
274762LEE CO EC;3U
Adder
11.947
274763LEE CO EC;4U
Adder
11.834
276603SUBLETTE C
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
270007AE1-245 C
Solar/Wind Harmer
0.002
972267AH1-718 GEN
Adder
5.295
276741O09 GEN1
Solar/Wind Harmer
0.315
276708O09 GEN2
Solar/Wind Harmer
0.315
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.347
276646AC1-214 GEN2
Solar/Wind Harmer
0.347
970623AG2-406 GEN
Solar/Wind Harmer
1.614
276782AC1-033 GEN
Solar/Wind Harmer
0.001
960611AF2-352 GEN
Solar/Wind Harmer
2.854
966841AG1-555 GEN
Solar/Wind Harmer
0.959
270599AE1-208 GEN
Solar/Wind Harmer
7.715
270031AE2-169
Solar/Wind Harmer
4.629
971613AH1-306 GEN
Solar/Wind Harmer
3.931
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
970241AG2-163 GEN
Solar/Wind Harmer
4.69
960441AF2-335 GEN
Solar/Wind Harmer
7.897
970825AG2-519 GEN
Solar/Wind Harmer
8.719
964611AG1-324 GEN
Solar/Wind Harmer
0.584
270201AC2-176 GEN
Solar/Wind Harmer
0.001
970621AG2-405 GEN
Solar/Wind Harmer
1.413
247621Y3-024
Adder
0.262
276916AD2-100_GEN
Solar/Wind Harmer
13.41
276911AD2-131_GEN
Solar/Wind Harmer
0.883
944201AF1-088_MTX
Adder
85.667
LAGNLTFEXP_LAGN->PJM
CLTF
11.144
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.328
TVALTFEXP_TVA->PJM
CLTF
4.56
CBM West 2LTFEXP_CBM-W2->PJM
CBM
96.989
NYPJM->LTFIMP_NY
CLTF
2.99
LGEELTFEXP_LGEE->PJM
CLTF
4.155
WECLTFEXP_WEC->PJM
CLTF
4.968
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.286
AG2-052LTFEXP_AG2-052->PJM
LTF
0.312
AH1-155LTFEXP_AH1-155->PJM
LTF
0.469
CBM West 1LTFEXP_CBM-W1->PJM
CBM
161.402
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.132
MECLTFEXP_MEC->PJM
CLTF
18.394
SIGELTFEXP_SIGE->PJM
CLTF
0.399

Details for 05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line l/o Base Case


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.73 %
Rating:4047.0 MVA
Rating Type:A
MVA to Mitigate:4643.02
MW Contribution:14.03
Bus #Bus NameTypeMW Contribution
971599AH1-298 GEN
50/50
10.558
270144AC1-141 ST1_
50/50
2.306
24643105BUCHANAN
50/50
0.014
24653605MOTTVILLE
50/50
0.004
274775LINCOLN ;6U
50/50
9.593
274776LINCOLN ;7U
50/50
9.593
274777LINCOLN ;8U
50/50
9.593
962771AG1-126 GEN
Solar/Wind Harmer
74.603
971347AH1-153 GEN
Solar/Wind Harmer
12.013
270071AF1-092 GEN
Solar/Wind Harmer
14.717
971771AH1-392 GEN
Solar/Wind Harmer
7.604
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971769AH1-391 GEN
Solar/Wind Harmer
8.444
971619AH1-309 GEN
Solar/Wind Harmer
3.384
274814UNIV PK N;0U
Adder
5.324
274807UNIV PK N;3U
Adder
5.313
274805UNIV PK N;1U
Adder
5.29
274811UNIV PK N;7U
Adder
5.278
274827FISK ;RP
Adder
8.149
972037AH1-567 GEN1
Adder
0.192
960591AF2-350 GEN
Solar/Wind Harmer
7.323
972227AH1-698 GEN1
Adder
2.737
274687WILL CNTY;4U
Adder
29.176
274687WILL CNTY;4U
Adder
29.176
274675JOLIET 29;7U
Adder
32.008
274675JOLIET 29;7U
Adder
30.865
24729505KEY G4
Adder
6.759
274731ELWOOD EC;2P
Adder
17.114
274733ELWOOD EC;3P
Adder
17.114
274735ELWOOD EC;4P
Adder
17.114
274728ELWOOD EC;5P
Adder
17.114
970833AG2-524 GEN
Solar/Wind Harmer
7.985
970833AG2-524 GEN
Solar/Wind Harmer
5.323
274746AC1-111 G10
Adder
5.788
274744AC1-111 GEN8
Adder
5.788
270536AF1-215 GEN2
Solar/Wind Harmer
0.009
971177AH1-047 GEN
Solar/Wind Harmer
4.355
958391AF2-133 GEN
Solar/Wind Harmer
0.001
276868AE1-113 GEN
Solar/Wind Harmer
1.417
276882AE2-255 GEN
Solar/Wind Harmer
0.825
971675AH1-338 GEN
Solar/Wind Harmer
2.746
971411AH1-196 GEN
Solar/Wind Harmer
10.56
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
971171AH1-044 GEN
Solar/Wind Harmer
14.009
274823ROCKFORD ;21
Adder
19.51
971611AH1-305 GEN
Solar/Wind Harmer
4.152
276612AE2-035 GEN
Solar/Wind Harmer
0.002
926823AC1-168 GEN
Solar/Wind Harmer
1.178
970169AG2-114 GEN
Solar/Wind Harmer
6.92
971681AH1-341 GEN
Solar/Wind Harmer
11.133
961011AF2-392 GEN
Solar/Wind Harmer
4.021
957751AF2-069 GEN
Solar/Wind Harmer
0.225
971549AH1-272 GEN
Solar/Wind Harmer
14.034
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
965101AG1-375 GEN
Solar/Wind Harmer
6.746
965041AG1-368 GEN
Solar/Wind Harmer
6.733
276655WTG1_EQ
Solar/Wind Harmer
0.003
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.06
941731AE2-173 GEN
Solar/Wind Harmer
5.603
946321AF1-296 GEN
Solar/Wind Harmer
3.744
963791AG1-232 GEN
Solar/Wind Harmer
8.989
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
945581AF1-223 GEN
Solar/Wind Harmer
0
965051AG1-369 GEN
Solar/Wind Harmer
3.241
963841AG1-237 GEN
Solar/Wind Harmer
2.776
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.231
276848AB2-070 GEN3
Solar/Wind Harmer
0.23
970289AG2-191 GEN
Solar/Wind Harmer
1.184
971609AH1-304 GEN
Solar/Wind Harmer
1.011
270594AE1-207 GEN
Solar/Wind Harmer
6.856
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.765
270284AF1-227 GEN1
Solar/Wind Harmer
0.008
270142AC1-141 CT1_
50/50
2.603
24641605TWIN BRNCH
50/50
0.019
24344005CKG1
50/50
7.096
24642205MAYFLWER
50/50
0.728
274772LINCOLN ;3U
50/50
9.593
970153AG2-106 GEN
Solar/Wind Harmer
47.639
970349AG2-230 GEN
Solar/Wind Harmer
12.013
970513AG2-328 GEN
Solar/Wind Harmer
3.44
970517AG2-330 GEN
Solar/Wind Harmer
20.64
270043AE2-236 GEN
Solar/Wind Harmer
5.033
247643Z2-116 C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
6.073
970031AG2-029 GEN
Solar/Wind Harmer
4.844
944531AF1-118 GEN
Solar/Wind Harmer
33.218
274724RIVER EC ;11
Adder
18.771
274752CRETE EC ;2U
Adder
8.717
274753CRETE EC ;3U
Adder
8.717
959331AF2-224 GEN
Solar/Wind Harmer
5.157
965021AG1-366 GEN
Solar/Wind Harmer
2.455
970707AG2-453 GEN
Solar/Wind Harmer
24.03
274826FISK ;BP
Adder
11.498
274802UNIV PARK;5U
Adder
6.123
276806AD2-047 C O1
Solar/Wind Harmer
4.15
970941AG2-585 GEN
Solar/Wind Harmer
9.154
274800UNIV PARK;3U
Adder
6.118
972038AH1-567 GEN2
Adder
0.383
972228AH1-698 GEN2
Adder
3.887
24441205WTRV SLR C
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
0.01
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
274676JOLIET 29;8U
Adder
30.865
274729ELWOOD EC;1P
Adder
17.114
274730ELWOOD EC;6P
Adder
17.114
274734ELWOOD EC;8P
Adder
17.114
274736ELWOOD EC;9P
Adder
17.114
276893AG1-478 C
Solar/Wind Harmer
0.288
943121AE2-341 GEN
Solar/Wind Harmer
12.132
943591AF1-030 GEN
Solar/Wind Harmer
8.068
247604X1-042
Adder
0.432
270535AF1-215 GEN1
Solar/Wind Harmer
0.009
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
18.416
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274872LEEDK;1U
Solar/Wind Harmer
0.26
276805AD2-038 GEN
Solar/Wind Harmer
0.002
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.751
274855GSG-6 ;RU
Solar/Wind Harmer
0.258
274850MENDOTA H;RU
Solar/Wind Harmer
0.083
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.126
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
959091AF2-200 GEN
Solar/Wind Harmer
14.009
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
2.191
970571AG2-364 GEN
Solar/Wind Harmer
13.859
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
9.191
274767LEE CO EC;8U
Adder
9.083
276157O29GEN1
Solar/Wind Harmer
1.104
274878BISHOP HL;2U
Solar/Wind Harmer
0.228
24721905FLATG4
Adder
19.64
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.747
942111AE2-223 GEN
Solar/Wind Harmer
2.185
24344105CKG2
50/50
8.939
270143AC1-141 CT2_
50/50
2.603
24639705ELKHART HY
50/50
0.176
970521AG2-332 GEN
50/50
12.519
274773LINCOLN ;4U
50/50
9.593
274774LINCOLN ;5U
50/50
9.593
962761AG1-125 GEN
Solar/Wind Harmer
74.603
970149AG2-104 GEN
Solar/Wind Harmer
80.573
970155AG2-107 GEN
Solar/Wind Harmer
47.639
970245AG2-165 GEN
Solar/Wind Harmer
3.44
270505AE1-170 C O1
Solar/Wind Harmer
7.896
270063AE2-323 C
Solar/Wind Harmer
0.006
945111AF1-176 GEN
Solar/Wind Harmer
13.37
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
3.886
274723RIVER EC ;12
Adder
18.99
274751CRETE EC ;1U
Adder
8.717
274754CRETE EC ;4U
Adder
8.717
276164X3-005 C
Solar/Wind Harmer
0
965011AG1-365 GEN
Solar/Wind Harmer
7.366
274812UNIV PK N;8U
Adder
5.278
970373AG2-245 GEN
Solar/Wind Harmer
15.386
276776AD2-060 GEN
Solar/Wind Harmer
0.765
274801UNIV PARK;4U
Adder
6.118
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
32.008
274674JOLIET 9 ;6U
Adder
16.042
274732ELWOOD EC;7P
Adder
17.114
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
274745AC1-111 GEN9
Adder
5.788
270055AF2-134 C O1
Solar/Wind Harmer
0.006
276691AA1-018 GEN1
Solar/Wind Harmer
0.866
274682WAUKEGAN ;7U
Adder
18.416
274828WAUKEGAN ;BP
Adder
11.308
958381AF2-132 GEN
Solar/Wind Harmer
0.001
962781AG1-127 GEN
Solar/Wind Harmer
6.763
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.233
274872LEEDK;1U
Solar/Wind Harmer
0.004
939401AE1-172 GEN
Solar/Wind Harmer
5.304
276901AD2-066 C O1
Solar/Wind Harmer
0.007
971997AH1-543 GEN
Solar/Wind Harmer
3.701
276861AD2-134 GEN
Solar/Wind Harmer
0.126
957471AF2-041 GEN
Solar/Wind Harmer
21.014
959081AF2-199 GEN
Solar/Wind Harmer
7.005
971067AG2-660 GEN
Solar/Wind Harmer
2.335
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
274822ROCKFORD ;11
Adder
19.652
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.717
972235AH1-702 GEN1
Adder
2.519
970819AG2-516 GEN
Solar/Wind Harmer
8.346
971475AH1-234 GEN
Solar/Wind Harmer
3.368
970569AG2-363 GEN
Solar/Wind Harmer
20.788
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
9.191
274766LEE CO EC;7U
Adder
9.083
965651AG1-433 GEN
Solar/Wind Harmer
2.017
276158O29GEN2
Solar/Wind Harmer
0.001
274877BISHOP HL;1U
Solar/Wind Harmer
0.228
24721705FLATG2
Adder
19.64
24791305MDL-5G
Solar/Wind Harmer
0.001
958861AF2-177 GEN
Solar/Wind Harmer
2.923
276726Z2-087_GEN
Solar/Wind Harmer
0.002
939741AE1-205 GEN
Solar/Wind Harmer
9.413
274854TWINGROVE;U2
Solar/Wind Harmer
0.003
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.002
944231AF1-091 GEN
Solar/Wind Harmer
1.739
945371AF1-202 GEN
Solar/Wind Harmer
0.001
247521TR3_G114
Solar/Wind Harmer
0.237
270246TR4_N_V150
Solar/Wind Harmer
0.042
972175AH1-670 GEN
Solar/Wind Harmer
5.355
270349AD2-093_GEN
Solar/Wind Harmer
0.005
24695305TIMB G C
Solar/Wind Harmer
0.002
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
2.462
963741AG1-226 GEN
Solar/Wind Harmer
14.839
276615X2-022 GEN
Solar/Wind Harmer
0.066
970291AG2-192 GEN
Solar/Wind Harmer
0.81
965421AG1-410 GEN
Solar/Wind Harmer
18.496
270032AE2-172
Solar/Wind Harmer
4.081
965911AG1-460 GEN
Solar/Wind Harmer
1.218
246936BC-WTG1
Solar/Wind Harmer
0.245
270489AE1-102 GEN1
Solar/Wind Harmer
0.785
270286AF1-227 GEN2
Solar/Wind Harmer
0.003
270287AF1-227 GEN3
Solar/Wind Harmer
0.003
270054AF2-122 C O1
Solar/Wind Helper
1.65
270102X2-052 ST
50/50
1.747
270100X2-052 CT1
50/50
1.61
270101X2-052 CT2
50/50
1.61
247620Y3-023
50/50
0.525
274770LINCOLN ;1U
50/50
9.593
274771LINCOLN ;2U
50/50
9.593
970321AG2-212 GEN
Solar/Wind Harmer
3.44
270216AD2-079_GEN
Solar/Wind Harmer
0.001
965681AG1-436 GEN
Solar/Wind Harmer
9.481
965791AG1-447 GEN
Solar/Wind Harmer
6.953
270526AF1-158 GEN
Solar/Wind Harmer
0.009
24441505OLIV SLR
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
14.924
961051AF2-396 GEN
Solar/Wind Harmer
9.95
970611AG2-400 GEN
Solar/Wind Harmer
7.366
970627AG2-408 GEN
Solar/Wind Harmer
2.21
274808UNIV PK N;4U
Adder
5.255
972259AH1-714 GEN
Adder
20.044
274803UNIV PARK;6U
Adder
6.123
274888KELLY CRK;1U
Solar/Wind Harmer
0.43
274887GEN-1.85
Solar/Wind Harmer
0.193
276843GEN-1.7
Solar/Wind Harmer
0.237
958011AF2-095 GEN
Solar/Wind Harmer
10.545
274674JOLIET 9 ;6U
Adder
16.042
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
971573AH1-285 GEN
Solar/Wind Harmer
1.342
274695ROCKY RD ;2P
Adder
11.425
274693ROCKY RD ;1P
Adder
11.312
274697ROCKY RD ;3P
Adder
3.104
274696ROCKY RD ;4P
Adder
11.694
958481AF2-142 GEN
Solar/Wind Harmer
10.727
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.967
274683WAUKEGAN ;8U
Adder
21.572
274683WAUKEGAN ;8U
Adder
18.184
962691AG1-118 GEN
Solar/Wind Harmer
21.36
970921AG2-575 GEN
Solar/Wind Harmer
7.106
970921AG2-575 GEN
Solar/Wind Harmer
2.369
958491AF2-143 GEN
Solar/Wind Harmer
10.627
942991AE2-321 GEN
Solar/Wind Harmer
7.889
274879MINONK ;1U
Solar/Wind Harmer
0.298
971333AH1-146 GEN
Solar/Wind Harmer
14.073
971335AH1-147 GEN
Solar/Wind Harmer
14.073
971341AH1-150 GEN
Solar/Wind Harmer
14.009
971343AH1-151 GEN
Solar/Wind Harmer
14.009
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
274856ECOGROVE ;U1
Solar/Wind Harmer
0.164
276611AD2-172 GEN
Solar/Wind Harmer
0.002
938861AE1-114 GEN
Solar/Wind Harmer
3.917
274764LEE CO EC;5U
Adder
9.213
274765LEE CO EC;6U
Adder
9.213
274762LEE CO EC;3U
Adder
9.191
274763LEE CO EC;4U
Adder
9.105
276603SUBLETTE C
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.461
960971AF2-388 GEN
Solar/Wind Harmer
4.033
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
972267AH1-718 GEN
Adder
4.082
276741O09 GEN1
Solar/Wind Harmer
0.243
276708O09 GEN2
Solar/Wind Harmer
0.243
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.268
276646AC1-214 GEN2
Solar/Wind Harmer
0.268
276782AC1-033 GEN
Solar/Wind Harmer
0.001
960611AF2-352 GEN
Solar/Wind Harmer
2.211
942221AE2-234 GEN
Solar/Wind Harmer
0.033
966841AG1-555 GEN
Solar/Wind Harmer
0.741
270471AD2-092_GEN
Solar/Wind Harmer
0.005
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
970241AG2-163 GEN
Solar/Wind Harmer
3.657
270599AE1-208 GEN
Solar/Wind Harmer
5.676
270031AE2-169
Solar/Wind Harmer
3.406
971613AH1-306 GEN
Solar/Wind Harmer
2.938
276916AD2-100_GEN
Solar/Wind Harmer
12.71
276911AD2-131_GEN
Solar/Wind Harmer
0.837
246938BC-WTG3
Solar/Wind Harmer
0.219
246937BC-WTG2
Solar/Wind Harmer
0.245
965931AG1-462 GEN
Solar/Wind Harmer
16.976
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
965091AG1-374 GEN
Solar/Wind Harmer
19.897
959611AF2-252 GEN
Solar/Wind Harmer
2.211
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.042
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
2.93
276668AB2-070 GEN1
Solar/Wind Harmer
0.231
247642Z2-115 C
Solar/Wind Harmer
0.003
276621W2-048 GEN
Solar/Wind Harmer
0.316
276838X2-022 GEN2
Solar/Wind Harmer
0.352
970289AG2-191 GEN
Solar/Wind Harmer
0.686
970291AG2-192 GEN
Solar/Wind Harmer
0.623
942481AE2-261 GEN
Solar/Wind Harmer
18.215
270491AE1-102 GEN2
Solar/Wind Harmer
0.785
LAGNLTFEXP_LAGN->PJM
CLTF
11.239
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.669
TVALTFEXP_TVA->PJM
CLTF
5.062
CPLELTFEXP_CPLE->PJM
CLTF
1.429
CBM West 2LTFEXP_CBM-W2->PJM
CBM
87.023
NYPJM->LTFIMP_NY
CLTF
2.589
LGEELTFEXP_LGEE->PJM
CLTF
3.659
WECLTFEXP_WEC->PJM
CLTF
3.814
AG2-052LTFEXP_AG2-052->PJM
LTF
0.236
AH1-155LTFEXP_AH1-155->PJM
LTF
0.355
CBM West 1LTFEXP_CBM-W1->PJM
CBM
120.019
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.189
MECLTFEXP_MEC->PJM
CLTF
14.69
SIGELTFEXP_SIGE->PJM
CLTF
0.339

Details for 05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line l/o ATSI_P7-1_TE-345-027A_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Contingency Name:
ATSI_P7-1_TE-345-027A_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:109.99 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5027.51
MW Contribution:15.97
Bus #Bus NameTypeMW Contribution
971599AH1-298 GEN
50/50
11.057
270144AC1-141 ST1_
50/50
2.446
24643105BUCHANAN
50/50
0.015
24653605MOTTVILLE
50/50
0.004
962771AG1-126 GEN
Solar/Wind Harmer
89.197
971347AH1-153 GEN
Solar/Wind Harmer
18.111
270071AF1-092 GEN
Solar/Wind Harmer
17.338
971771AH1-392 GEN
Solar/Wind Harmer
10.383
960681AF2-359 GEN
Solar/Wind Harmer
4.333
971769AH1-391 GEN
Solar/Wind Harmer
11.46
944161AF1-084 GEN
Solar/Wind Harmer
2.498
274775LINCOLN ;6U
Adder
6.975
274776LINCOLN ;7U
Adder
6.975
274777LINCOLN ;8U
Adder
6.975
274814UNIV PK N;0U
Adder
5.601
274807UNIV PK N;3U
Adder
5.589
274805UNIV PK N;1U
Adder
5.565
274811UNIV PK N;7U
Adder
5.552
972037AH1-567 GEN1
Adder
0.202
274827FISK ;RP
Adder
8.568
960591AF2-350 GEN
Solar/Wind Harmer
11.036
972227AH1-698 GEN1
Adder
2.877
274687WILL CNTY;4U
Adder
30.673
274687WILL CNTY;4U
Adder
30.673
274675JOLIET 29;7U
Adder
33.649
274675JOLIET 29;7U
Adder
32.447
274731ELWOOD EC;2P
Adder
17.991
274733ELWOOD EC;3P
Adder
17.991
274735ELWOOD EC;4P
Adder
17.991
274728ELWOOD EC;5P
Adder
17.991
970833AG2-524 GEN
Solar/Wind Harmer
9.547
970833AG2-524 GEN
Solar/Wind Harmer
4.44
24729505KEY G4
Adder
7.093
270536AF1-215 GEN2
Solar/Wind Harmer
4.953
274746AC1-111 G10
Adder
6.083
274744AC1-111 GEN8
Adder
6.083
958391AF2-133 GEN
Solar/Wind Harmer
9.677
971177AH1-047 GEN
Solar/Wind Harmer
6.235
276868AE1-113 GEN
Solar/Wind Harmer
10.768
276882AE2-255 GEN
Solar/Wind Harmer
3.589
971411AH1-196 GEN
Solar/Wind Harmer
15.911
971675AH1-338 GEN
Solar/Wind Harmer
19.093
274823ROCKFORD ;21
Adder
20.508
270054AF2-122 C O1
Solar/Wind Helper
1.62
971549AH1-272 GEN
Solar/Wind Harmer
15.966
24344105CKG2
50/50
9.384
270143AC1-141 CT2_
50/50
2.761
24639705ELKHART HY
50/50
0.186
970521AG2-332 GEN
50/50
13.281
24307105BERRINSP G
50/50
0.025
962761AG1-125 GEN
Solar/Wind Harmer
89.197
970149AG2-104 GEN
Solar/Wind Harmer
110.158
970155AG2-107 GEN
Solar/Wind Harmer
38.894
970245AG2-165 GEN
Solar/Wind Harmer
21.268
270505AE1-170 C O1
Solar/Wind Harmer
17.176
945111AF1-176 GEN
Solar/Wind Harmer
20.364
270063AE2-323 C
Solar/Wind Harmer
2.513
270449AD2-020 GEN
Solar/Wind Harmer
3.183
943021AE2-325 GEN
Solar/Wind Harmer
4.136
972207SS24-0001
Solar/Wind Harmer
24.8
274773LINCOLN ;4U
Adder
6.975
274774LINCOLN ;5U
Adder
6.975
965011AG1-365 GEN
Solar/Wind Harmer
11.187
274723RIVER EC ;12
Adder
19.976
274751CRETE EC ;1U
Adder
5.442
274754CRETE EC ;4U
Adder
5.442
276164X3-005 C
Solar/Wind Harmer
0.781
274812UNIV PK N;8U
Adder
5.552
970373AG2-245 GEN
Solar/Wind Harmer
23.259
276776AD2-060 GEN
Solar/Wind Harmer
0.467
274801UNIV PARK;4U
Adder
6.433
941551AE2-152 GEN
Solar/Wind Harmer
4.986
274676JOLIET 29;8U
Adder
33.648
274674JOLIET 9 ;6U
Adder
16.864
274732ELWOOD EC;7P
Adder
17.991
274871GR RIDGE ;2U
Solar/Wind Harmer
8.406
270055AF2-134 C O1
Solar/Wind Harmer
3.301
274745AC1-111 GEN9
Adder
6.083
276691AA1-018 GEN1
Solar/Wind Harmer
0.502
274682WAUKEGAN ;7U
Adder
19.358
274828WAUKEGAN ;BP
Adder
11.886
958381AF2-132 GEN
Solar/Wind Harmer
9.749
964861AG1-349 GEN
Solar/Wind Harmer
8.434
971917AH1-482 GEN
Solar/Wind Harmer
9.733
960751AF2-366 GEN
Solar/Wind Harmer
3.071
962781AG1-127 GEN
Solar/Wind Harmer
10.181
274872LEEDK;1U
Solar/Wind Harmer
8.777
939401AE1-172 GEN
Solar/Wind Harmer
14.891
276901AD2-066 C O1
Solar/Wind Harmer
3.747
971997AH1-543 GEN
Solar/Wind Harmer
16.729
276861AD2-134 GEN
Solar/Wind Harmer
1.894
274822ROCKFORD ;11
Adder
20.658
972235AH1-702 GEN1
Adder
2.648
274761LEE CO EC;2U
Adder
9.662
274766LEE CO EC;7U
Adder
9.549
24721705FLATG2
Adder
19.907
270102X2-052 ST
50/50
1.844
270100X2-052 CT1
50/50
1.699
270101X2-052 CT2
50/50
1.699
247620Y3-023
50/50
0.557
970321AG2-212 GEN
Solar/Wind Harmer
21.268
270216AD2-079_GEN
Solar/Wind Harmer
0.699
270526AF1-158 GEN
Solar/Wind Harmer
5.214
965681AG1-436 GEN
Solar/Wind Harmer
14.336
965791AG1-447 GEN
Solar/Wind Harmer
7.335
24441505OLIV SLR
Solar/Wind Harmer
0.154
957891AF2-083 GEN
Solar/Wind Harmer
3.858
960981AF2-389 GEN
Solar/Wind Harmer
1.729
961051AF2-396 GEN
Solar/Wind Harmer
18.061
961051AF2-396 GEN
Solar/Wind Harmer
8.401
274770LINCOLN ;1U
Adder
6.975
274771LINCOLN ;2U
Adder
6.975
970611AG2-400 GEN
Solar/Wind Harmer
11.187
274808UNIV PK N;4U
Adder
5.528
274803UNIV PARK;6U
Adder
6.439
972259AH1-714 GEN
Adder
21.064
274888KELLY CRK;1U
Solar/Wind Harmer
6.515
274887GEN-1.85
Solar/Wind Harmer
5.882
276843GEN-1.7
Solar/Wind Harmer
0.633
958011AF2-095 GEN
Solar/Wind Harmer
15.891
274674JOLIET 9 ;6U
Adder
16.864
274847GR RIDGE ;BU
Solar/Wind Harmer
5.529
971573AH1-285 GEN
Solar/Wind Harmer
9.332
274695ROCKY RD ;2P
Adder
12.008
274693ROCKY RD ;1P
Adder
11.89
274697ROCKY RD ;3P
Adder
3.262
274696ROCKY RD ;4P
Adder
12.291
958481AF2-142 GEN
Solar/Wind Harmer
16.166
274861TOP CROP ;1U
Solar/Wind Harmer
6.528
274862TOP CROP ;2U
Solar/Wind Harmer
5.451
274683WAUKEGAN ;8U
Adder
22.675
274683WAUKEGAN ;8U
Adder
19.114
962691AG1-118 GEN
Solar/Wind Harmer
32.178
970921AG2-575 GEN
Solar/Wind Harmer
10.705
970921AG2-575 GEN
Solar/Wind Harmer
2.49
958491AF2-143 GEN
Solar/Wind Harmer
16.016
942991AE2-321 GEN
Solar/Wind Harmer
10.644
274879MINONK ;1U
Solar/Wind Harmer
7.179
971333AH1-146 GEN
Solar/Wind Harmer
21.203
971335AH1-147 GEN
Solar/Wind Harmer
21.203
274764LEE CO EC;5U
Adder
9.685
274765LEE CO EC;6U
Adder
9.685
274762LEE CO EC;3U
Adder
9.662
274763LEE CO EC;4U
Adder
9.571
972267AH1-718 GEN
Adder
4.292
270142AC1-141 CT1_
50/50
2.761
24344005CKG1
50/50
7.535
24641605TWIN BRNCH
50/50
0.02
24642205MAYFLWER
50/50
0.772
944961AF1-161 GEN
50/50
3.302
962601AG1-109 GEN
50/50
3.302
970153AG2-106 GEN
Solar/Wind Harmer
38.894
970349AG2-230 GEN
Solar/Wind Harmer
18.111
970513AG2-328 GEN
Solar/Wind Harmer
21.268
970517AG2-330 GEN
Solar/Wind Harmer
19.29
270043AE2-236 GEN
Solar/Wind Harmer
6.511
247643Z2-116 C
Solar/Wind Harmer
0.08
945111AF1-176 GEN
Solar/Wind Harmer
6.454
970031AG2-029 GEN
Solar/Wind Harmer
33.986
274772LINCOLN ;3U
Adder
6.975
24441205WTRV SLR C
Solar/Wind Harmer
0.151
959331AF2-224 GEN
Solar/Wind Harmer
11.187
965021AG1-366 GEN
Solar/Wind Harmer
2.602
274724RIVER EC ;11
Adder
19.746
944531AF1-118 GEN
Solar/Wind Harmer
39.003
972231SS25-0005
Solar/Wind Harmer
10.567
972181SS23-001
Solar/Wind Harmer
6.604
274752CRETE EC ;2U
Adder
5.442
274753CRETE EC ;3U
Adder
5.442
247604X1-042
Adder
0.463
970707AG2-453 GEN
Solar/Wind Harmer
31.017
274802UNIV PARK;5U
Adder
6.439
274826FISK ;BP
Adder
12.09
276772AC2-154 GEN
Solar/Wind Harmer
3.077
276806AD2-047 C O1
Solar/Wind Harmer
11.806
970941AG2-585 GEN
Solar/Wind Harmer
13.795
274800UNIV PARK;3U
Adder
6.433
972038AH1-567 GEN2
Adder
0.403
972228AH1-698 GEN2
Adder
4.086
276897AD1-100 C
Solar/Wind Harmer
31.901
939351AE1-166 GEN
Solar/Wind Harmer
6.518
274676JOLIET 29;8U
Adder
32.446
274729ELWOOD EC;1P
Adder
17.991
274730ELWOOD EC;6P
Adder
17.991
274734ELWOOD EC;8P
Adder
17.991
274736ELWOOD EC;9P
Adder
17.991
276893AG1-478 C
Solar/Wind Harmer
0.457
270535AF1-215 GEN1
Solar/Wind Harmer
4.953
943121AE2-341 GEN
Solar/Wind Harmer
16.349
943591AF1-030 GEN
Solar/Wind Harmer
10.899
276694AA1-018 GEN2
Solar/Wind Harmer
6.801
274682WAUKEGAN ;7U
Adder
19.358
964401AG1-302 GEN
Solar/Wind Harmer
9.749
274872LEEDK;1U
Solar/Wind Harmer
0.273
276805AD2-038 GEN
Solar/Wind Harmer
5.478
276799AD1-013 GEN
Solar/Wind Harmer
2.346
946671AF1-331 GEN
Solar/Wind Harmer
0.444
959141AF2-205 GEN
Solar/Wind Harmer
6.413
274855GSG-6 ;RU
Solar/Wind Harmer
3.917
274850MENDOTA H;RU
Solar/Wind Harmer
2.724
276602WESTBROOK C
Solar/Wind Harmer
2.255
276863AD2-134 GEN
Solar/Wind Harmer
1.894
972236AH1-702 GEN2
Adder
2.303
274760LEE CO EC;1U
Adder
9.662
274767LEE CO EC;8U
Adder
9.549
24721905FLATG4
Adder
19.907
LAGNLTFEXP_LAGN->PJM
CLTF
11.82
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.928
TVALTFEXP_TVA->PJM
CLTF
5.326
CPLELTFEXP_CPLE->PJM
CLTF
1.469
CBM West 2LTFEXP_CBM-W2->PJM
CBM
91.671
NYPJM->LTFIMP_NY
CLTF
2.826
LGEELTFEXP_LGEE->PJM
CLTF
3.895
WECLTFEXP_WEC->PJM
CLTF
4.009
AG2-052LTFEXP_AG2-052->PJM
LTF
0.249
AH1-155LTFEXP_AH1-155->PJM
LTF
0.373
CBM West 1LTFEXP_CBM-W1->PJM
CBM
131.22
CBM South 1LTFEXP_CBM-S1->PJM
CBM
20.233
MECLTFEXP_MEC->PJM
CLTF
15.452
SIGELTFEXP_SIGE->PJM
CLTF
0.358

Details for 05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line l/o ATSI_P7-1_TE-345-030_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Contingency Name:
ATSI_P7-1_TE-345-030_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:109.75 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5016.84
MW Contribution:15.91
Bus #Bus NameTypeMW Contribution
270142AC1-141 CT1_
50/50
2.756
24344005CKG1
50/50
7.52
24641605TWIN BRNCH
50/50
0.02
24642205MAYFLWER
50/50
0.771
944961AF1-161 GEN
50/50
3.295
962601AG1-109 GEN
50/50
3.295
970153AG2-106 GEN
Solar/Wind Harmer
38.893
970349AG2-230 GEN
Solar/Wind Harmer
18.083
971599AH1-298 GEN
50/50
11.045
270144AC1-141 ST1_
50/50
2.441
24643105BUCHANAN
50/50
0.015
24653605MOTTVILLE
50/50
0.004
962771AG1-126 GEN
Solar/Wind Harmer
89.195
971347AH1-153 GEN
Solar/Wind Harmer
18.083
270071AF1-092 GEN
Solar/Wind Harmer
17.32
971771AH1-392 GEN
Solar/Wind Harmer
10.364
960681AF2-359 GEN
Solar/Wind Harmer
4.326
971769AH1-391 GEN
Solar/Wind Harmer
11.44
944161AF1-084 GEN
Solar/Wind Harmer
2.493
274775LINCOLN ;6U
Adder
6.965
274776LINCOLN ;7U
Adder
6.965
274777LINCOLN ;8U
Adder
6.965
274814UNIV PK N;0U
Adder
5.593
274807UNIV PK N;3U
Adder
5.581
274805UNIV PK N;1U
Adder
5.557
274811UNIV PK N;7U
Adder
5.544
972037AH1-567 GEN1
Adder
0.202
274827FISK ;RP
Adder
8.556
960591AF2-350 GEN
Solar/Wind Harmer
11.02
972227AH1-698 GEN1
Adder
2.873
274687WILL CNTY;4U
Adder
30.629
274687WILL CNTY;4U
Adder
30.629
274675JOLIET 29;7U
Adder
33.601
274675JOLIET 29;7U
Adder
32.401
274731ELWOOD EC;2P
Adder
17.966
274733ELWOOD EC;3P
Adder
17.966
274735ELWOOD EC;4P
Adder
17.966
274728ELWOOD EC;5P
Adder
17.966
24729505KEY G4
Adder
7.087
970833AG2-524 GEN
Solar/Wind Harmer
9.533
970833AG2-524 GEN
Solar/Wind Harmer
4.434
270536AF1-215 GEN2
Solar/Wind Harmer
4.945
274746AC1-111 G10
Adder
6.074
274744AC1-111 GEN8
Adder
6.074
958391AF2-133 GEN
Solar/Wind Harmer
9.662
971177AH1-047 GEN
Solar/Wind Harmer
6.227
276868AE1-113 GEN
Solar/Wind Harmer
10.752
276882AE2-255 GEN
Solar/Wind Harmer
3.584
971675AH1-338 GEN
Solar/Wind Harmer
19.066
971411AH1-196 GEN
Solar/Wind Harmer
15.889
274823ROCKFORD ;21
Adder
20.48
270054AF2-122 C O1
Solar/Wind Helper
1.619
971549AH1-272 GEN
Solar/Wind Harmer
15.913
24344105CKG2
50/50
9.37
270143AC1-141 CT2_
50/50
2.756
24639705ELKHART HY
50/50
0.186
970521AG2-332 GEN
50/50
13.258
24307105BERRINSP G
50/50
0.025
962761AG1-125 GEN
Solar/Wind Harmer
89.195
970149AG2-104 GEN
Solar/Wind Harmer
110.156
970155AG2-107 GEN
Solar/Wind Harmer
38.893
970245AG2-165 GEN
Solar/Wind Harmer
21.241
270505AE1-170 C O1
Solar/Wind Harmer
17.142
945111AF1-176 GEN
Solar/Wind Harmer
20.324
270063AE2-323 C
Solar/Wind Harmer
2.509
270449AD2-020 GEN
Solar/Wind Harmer
3.177
943021AE2-325 GEN
Solar/Wind Harmer
4.128
972207SS24-0001
Solar/Wind Harmer
24.765
274773LINCOLN ;4U
Adder
6.965
274774LINCOLN ;5U
Adder
6.965
965011AG1-365 GEN
Solar/Wind Harmer
11.176
274723RIVER EC ;12
Adder
19.947
274751CRETE EC ;1U
Adder
5.434
274754CRETE EC ;4U
Adder
5.434
276164X3-005 C
Solar/Wind Harmer
0.78
274812UNIV PK N;8U
Adder
5.544
970373AG2-245 GEN
Solar/Wind Harmer
23.222
276776AD2-060 GEN
Solar/Wind Harmer
0.466
274801UNIV PARK;4U
Adder
6.424
270102X2-052 ST
50/50
1.841
270100X2-052 CT1
50/50
1.696
270101X2-052 CT2
50/50
1.696
247620Y3-023
50/50
0.556
970321AG2-212 GEN
Solar/Wind Harmer
21.241
270216AD2-079_GEN
Solar/Wind Harmer
0.697
270526AF1-158 GEN
Solar/Wind Harmer
5.205
965681AG1-436 GEN
Solar/Wind Harmer
14.313
965791AG1-447 GEN
Solar/Wind Harmer
7.323
24441505OLIV SLR
Solar/Wind Harmer
0.153
957891AF2-083 GEN
Solar/Wind Harmer
3.85
960981AF2-389 GEN
Solar/Wind Harmer
1.725
961051AF2-396 GEN
Solar/Wind Harmer
18.024
961051AF2-396 GEN
Solar/Wind Harmer
8.383
274770LINCOLN ;1U
Adder
6.965
274771LINCOLN ;2U
Adder
6.965
970611AG2-400 GEN
Solar/Wind Harmer
11.176
274808UNIV PK N;4U
Adder
5.52
274803UNIV PARK;6U
Adder
6.43
972259AH1-714 GEN
Adder
21.035
274888KELLY CRK;1U
Solar/Wind Harmer
6.506
274887GEN-1.85
Solar/Wind Harmer
5.874
276843GEN-1.7
Solar/Wind Harmer
0.632
958011AF2-095 GEN
Solar/Wind Harmer
15.869
274674JOLIET 9 ;6U
Adder
16.84
274847GR RIDGE ;BU
Solar/Wind Harmer
5.521
971573AH1-285 GEN
Solar/Wind Harmer
9.319
274696ROCKY RD ;4P
Adder
12.274
274695ROCKY RD ;2P
Adder
11.991
274693ROCKY RD ;1P
Adder
11.873
274697ROCKY RD ;3P
Adder
3.257
958481AF2-142 GEN
Solar/Wind Harmer
16.143
274861TOP CROP ;1U
Solar/Wind Harmer
6.519
274862TOP CROP ;2U
Solar/Wind Harmer
5.443
274683WAUKEGAN ;8U
Adder
22.643
274683WAUKEGAN ;8U
Adder
19.087
962691AG1-118 GEN
Solar/Wind Harmer
32.133
970921AG2-575 GEN
Solar/Wind Harmer
10.69
970921AG2-575 GEN
Solar/Wind Harmer
2.486
958491AF2-143 GEN
Solar/Wind Harmer
15.994
942991AE2-321 GEN
Solar/Wind Harmer
10.629
274879MINONK ;1U
Solar/Wind Harmer
7.169
971333AH1-146 GEN
Solar/Wind Harmer
21.173
971335AH1-147 GEN
Solar/Wind Harmer
21.173
274764LEE CO EC;5U
Adder
9.672
274765LEE CO EC;6U
Adder
9.672
274762LEE CO EC;3U
Adder
9.649
274763LEE CO EC;4U
Adder
9.558
972267AH1-718 GEN
Adder
4.286
970513AG2-328 GEN
Solar/Wind Harmer
21.241
970517AG2-330 GEN
Solar/Wind Harmer
19.266
270043AE2-236 GEN
Solar/Wind Harmer
6.503
247643Z2-116 C
Solar/Wind Harmer
0.08
945111AF1-176 GEN
Solar/Wind Harmer
6.441
970031AG2-029 GEN
Solar/Wind Harmer
33.933
274772LINCOLN ;3U
Adder
6.965
959331AF2-224 GEN
Solar/Wind Harmer
11.176
965021AG1-366 GEN
Solar/Wind Harmer
2.599
24441205WTRV SLR C
Solar/Wind Harmer
0.151
274724RIVER EC ;11
Adder
19.717
944531AF1-118 GEN
Solar/Wind Harmer
38.966
972231SS25-0005
Solar/Wind Harmer
10.551
972181SS23-001
Solar/Wind Harmer
6.594
274752CRETE EC ;2U
Adder
5.434
274753CRETE EC ;3U
Adder
5.434
247604X1-042
Adder
0.461
970707AG2-453 GEN
Solar/Wind Harmer
30.974
274802UNIV PARK;5U
Adder
6.43
274826FISK ;BP
Adder
12.073
276772AC2-154 GEN
Solar/Wind Harmer
3.073
276806AD2-047 C O1
Solar/Wind Harmer
11.789
970941AG2-585 GEN
Solar/Wind Harmer
13.775
274800UNIV PARK;3U
Adder
6.424
972038AH1-567 GEN2
Adder
0.402
972228AH1-698 GEN2
Adder
4.08
276897AD1-100 C
Solar/Wind Harmer
31.856
939351AE1-166 GEN
Solar/Wind Harmer
6.509
274676JOLIET 29;8U
Adder
32.4
274729ELWOOD EC;1P
Adder
17.966
274730ELWOOD EC;6P
Adder
17.966
274734ELWOOD EC;8P
Adder
17.966
274736ELWOOD EC;9P
Adder
17.966
276893AG1-478 C
Solar/Wind Harmer
0.456
270535AF1-215 GEN1
Solar/Wind Harmer
4.945
943121AE2-341 GEN
Solar/Wind Harmer
16.326
943591AF1-030 GEN
Solar/Wind Harmer
10.884
276694AA1-018 GEN2
Solar/Wind Harmer
6.792
274682WAUKEGAN ;7U
Adder
19.331
964401AG1-302 GEN
Solar/Wind Harmer
9.734
274872LEEDK;1U
Solar/Wind Harmer
0.273
276805AD2-038 GEN
Solar/Wind Harmer
5.47
276799AD1-013 GEN
Solar/Wind Harmer
2.342
946671AF1-331 GEN
Solar/Wind Harmer
0.444
959141AF2-205 GEN
Solar/Wind Harmer
6.404
274855GSG-6 ;RU
Solar/Wind Harmer
3.911
274850MENDOTA H;RU
Solar/Wind Harmer
2.72
276602WESTBROOK C
Solar/Wind Harmer
2.251
276863AD2-134 GEN
Solar/Wind Harmer
1.892
972236AH1-702 GEN2
Adder
2.3
274760LEE CO EC;1U
Adder
9.649
274767LEE CO EC;8U
Adder
9.535
24721905FLATG4
Adder
19.906
941551AE2-152 GEN
Solar/Wind Harmer
4.979
274676JOLIET 29;8U
Adder
33.6
274674JOLIET 9 ;6U
Adder
16.84
274732ELWOOD EC;7P
Adder
17.966
274871GR RIDGE ;2U
Solar/Wind Harmer
8.394
270055AF2-134 C O1
Solar/Wind Harmer
3.296
274745AC1-111 GEN9
Adder
6.074
276691AA1-018 GEN1
Solar/Wind Harmer
0.501
274682WAUKEGAN ;7U
Adder
19.331
274828WAUKEGAN ;BP
Adder
11.869
958381AF2-132 GEN
Solar/Wind Harmer
9.734
964861AG1-349 GEN
Solar/Wind Harmer
8.422
971917AH1-482 GEN
Solar/Wind Harmer
9.718
960751AF2-366 GEN
Solar/Wind Harmer
3.067
962781AG1-127 GEN
Solar/Wind Harmer
10.166
274872LEEDK;1U
Solar/Wind Harmer
8.765
939401AE1-172 GEN
Solar/Wind Harmer
14.87
276901AD2-066 C O1
Solar/Wind Harmer
3.742
971997AH1-543 GEN
Solar/Wind Harmer
16.706
276861AD2-134 GEN
Solar/Wind Harmer
1.892
274822ROCKFORD ;11
Adder
20.629
972235AH1-702 GEN1
Adder
2.644
274761LEE CO EC;2U
Adder
9.649
274766LEE CO EC;7U
Adder
9.535
24721705FLATG2
Adder
19.906
LAGNLTFEXP_LAGN->PJM
CLTF
11.806
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.918
TVALTFEXP_TVA->PJM
CLTF
5.319
CPLELTFEXP_CPLE->PJM
CLTF
1.466
CBM West 2LTFEXP_CBM-W2->PJM
CBM
91.557
NYPJM->LTFIMP_NY
CLTF
2.828
LGEELTFEXP_LGEE->PJM
CLTF
3.891
WECLTFEXP_WEC->PJM
CLTF
4.003
AG2-052LTFEXP_AG2-052->PJM
LTF
0.249
AH1-155LTFEXP_AH1-155->PJM
LTF
0.373
CBM West 1LTFEXP_CBM-W1->PJM
CBM
130.734
CBM South 1LTFEXP_CBM-S1->PJM
CBM
20.209
MECLTFEXP_MEC->PJM
CLTF
15.431
SIGELTFEXP_SIGE->PJM
CLTF
0.358

Details for 05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line l/o AP_P1-3_MP-765-501T_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-501T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:130.66 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5972.54
MW Contribution:16.35
Bus #Bus NameTypeMW Contribution
24722005FLATG5
50/50
1.795
24721905FLATG4
50/50
32.905
970153AG2-106 GEN
Solar/Wind Harmer
51.584
970513AG2-328 GEN
Solar/Wind Harmer
4.074
970517AG2-330 GEN
Solar/Wind Harmer
24.444
970349AG2-230 GEN
Solar/Wind Harmer
14.036
270043AE2-236 GEN
Solar/Wind Harmer
5.854
274772LINCOLN ;3U
Adder
10.782
247643Z2-116 C
Solar/Wind Harmer
0
24642205MAYFLWER
Adder
0.804
274724RIVER EC ;11
Adder
22.4
970707AG2-453 GEN
Solar/Wind Harmer
28.77
274752CRETE EC ;2U
Adder
10.401
274753CRETE EC ;3U
Adder
10.401
944531AF1-118 GEN
Solar/Wind Harmer
39.427
274826FISK ;BP
Adder
13.763
274802UNIV PARK;5U
Adder
7.329
276806AD2-047 C O1
Solar/Wind Harmer
4.97
970941AG2-585 GEN
Solar/Wind Harmer
10.962
972228AH1-698 GEN2
Adder
4.656
274800UNIV PARK;3U
Adder
7.326
972038AH1-567 GEN2
Adder
0.459
945111AF1-176 GEN
Solar/Wind Harmer
7.104
276897AD1-100 C
Solar/Wind Harmer
0.012
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
274676JOLIET 29;8U
Adder
37.026
274729ELWOOD EC;1P
Adder
20.542
274730ELWOOD EC;6P
Adder
20.542
274734ELWOOD EC;8P
Adder
20.542
274736ELWOOD EC;9P
Adder
20.542
276893AG1-478 C
Solar/Wind Harmer
0.345
970031AG2-029 GEN
Solar/Wind Harmer
5.657
943121AE2-341 GEN
Solar/Wind Harmer
14.583
943591AF1-030 GEN
Solar/Wind Harmer
9.698
270535AF1-215 GEN1
Solar/Wind Harmer
0.011
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
22.199
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274872LEEDK;1U
Solar/Wind Harmer
0.314
276805AD2-038 GEN
Solar/Wind Harmer
0.003
959331AF2-224 GEN
Solar/Wind Harmer
5.981
965021AG1-366 GEN
Solar/Wind Harmer
2.848
24441205WTRV SLR C
Solar/Wind Harmer
0
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
0.909
274855GSG-6 ;RU
Solar/Wind Harmer
0.313
274850MENDOTA H;RU
Solar/Wind Harmer
0.1
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.153
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
959091AF2-200 GEN
Solar/Wind Harmer
16.979
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
2.658
247604X1-042
Adder
0.505
970571AG2-364 GEN
Solar/Wind Harmer
16.847
274858EASY ROAD;U2
Solar/Wind Harmer
0.002
274760LEE CO EC;1U
Adder
11.187
274767LEE CO EC;8U
Adder
11.055
276157O29GEN1
Solar/Wind Harmer
1.347
274878BISHOP HL;2U
Solar/Wind Harmer
0.279
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
8.289
942111AE2-223 GEN
Solar/Wind Harmer
2.682
965931AG1-462 GEN
Solar/Wind Harmer
20.855
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
965091AG1-374 GEN
Solar/Wind Harmer
24.514
959611AF2-252 GEN
Solar/Wind Harmer
2.724
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
3.657
276668AB2-070 GEN1
Solar/Wind Harmer
0.289
247642Z2-115 C
Solar/Wind Harmer
0.003
276621W2-048 GEN
Solar/Wind Harmer
0.395
276838X2-022 GEN2
Solar/Wind Harmer
0.442
970289AG2-191 GEN
Solar/Wind Harmer
0.855
970291AG2-192 GEN
Solar/Wind Harmer
0.777
942481AE2-261 GEN
Solar/Wind Harmer
23.013
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.049
970193AG2-126 GEN
Solar/Wind Harmer
11.195
958821AF2-173 GEN
Solar/Wind Harmer
10.43
270004AE1-209 GEN
Solar/Wind Harmer
1.614
971617AH1-308 GEN
Solar/Wind Harmer
6.153
970243AG2-164 GEN
Solar/Wind Harmer
3.851
970519AG2-331 GEN
Solar/Wind Harmer
17.115
970699AG2-449 GEN
Solar/Wind Harmer
1.646
24721805FLATG3
50/50
1.795
24721705FLATG2
50/50
32.905
24344105CKG2
50/50
10.4
962761AG1-125 GEN
Solar/Wind Harmer
80.781
970149AG2-104 GEN
Solar/Wind Harmer
87.246
970155AG2-107 GEN
Solar/Wind Harmer
51.584
970245AG2-165 GEN
Solar/Wind Harmer
4.074
274773LINCOLN ;4U
Adder
10.782
274774LINCOLN ;5U
Adder
10.782
274723RIVER EC ;12
Adder
22.661
24639705ELKHART HY
Adder
0.194
276164X3-005 C
Solar/Wind Harmer
0
274751CRETE EC ;1U
Adder
10.401
274754CRETE EC ;4U
Adder
10.401
270505AE1-170 C O1
Solar/Wind Harmer
9.235
274812UNIV PK N;8U
Adder
6.308
276776AD2-060 GEN
Solar/Wind Harmer
0.916
274801UNIV PARK;4U
Adder
7.326
945111AF1-176 GEN
Solar/Wind Harmer
15.639
270063AE2-323 C
Solar/Wind Harmer
0.007
941551AE2-152 GEN
Solar/Wind Harmer
0.001
970373AG2-245 GEN
Solar/Wind Harmer
18.378
274676JOLIET 29;8U
Adder
38.397
274674JOLIET 9 ;6U
Adder
19.252
274732ELWOOD EC;7P
Adder
20.542
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
4.544
274745AC1-111 GEN9
Adder
6.959
270055AF2-134 C O1
Solar/Wind Harmer
0.007
276691AA1-018 GEN1
Solar/Wind Harmer
1.044
274682WAUKEGAN ;7U
Adder
22.199
274828WAUKEGAN ;BP
Adder
13.634
958381AF2-132 GEN
Solar/Wind Harmer
0.001
962781AG1-127 GEN
Solar/Wind Harmer
8.166
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
11.147
939401AE1-172 GEN
Solar/Wind Harmer
6.413
274872LEEDK;1U
Solar/Wind Harmer
0.005
276901AD2-066 C O1
Solar/Wind Harmer
0.008
965011AG1-365 GEN
Solar/Wind Harmer
8.544
971997AH1-543 GEN
Solar/Wind Harmer
4.478
276861AD2-134 GEN
Solar/Wind Harmer
0.153
957471AF2-041 GEN
Solar/Wind Harmer
25.469
959081AF2-199 GEN
Solar/Wind Harmer
8.49
971067AG2-660 GEN
Solar/Wind Harmer
2.83
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
10.593
274822ROCKFORD ;11
Adder
23.833
972235AH1-702 GEN1
Adder
3.057
970819AG2-516 GEN
Solar/Wind Harmer
10.134
971475AH1-234 GEN
Solar/Wind Harmer
4.092
970569AG2-363 GEN
Solar/Wind Harmer
25.271
274857EASY ROAD;U1
Solar/Wind Harmer
0.002
274761LEE CO EC;2U
Adder
11.187
274766LEE CO EC;7U
Adder
11.055
276158O29GEN2
Solar/Wind Harmer
0.001
965651AG1-433 GEN
Solar/Wind Harmer
2.438
274877BISHOP HL;1U
Solar/Wind Harmer
0.279
24791305MDL-5G
Solar/Wind Harmer
0.001
276726Z2-087_GEN
Solar/Wind Harmer
0.003
939741AE1-205 GEN
Solar/Wind Harmer
11.552
958861AF2-177 GEN
Solar/Wind Harmer
3.551
274854TWINGROVE;U2
Solar/Wind Harmer
0.003
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
972175AH1-670 GEN
Solar/Wind Harmer
6.643
945371AF1-202 GEN
Solar/Wind Harmer
0.001
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
3.078
963741AG1-226 GEN
Solar/Wind Harmer
18.629
276615X2-022 GEN
Solar/Wind Harmer
0.082
970291AG2-192 GEN
Solar/Wind Harmer
1.01
965911AG1-460 GEN
Solar/Wind Harmer
1.539
270032AE2-172
Solar/Wind Harmer
5.104
247521TR3_G114
Solar/Wind Harmer
0.277
24721605FLATG1
50/50
1.795
971599AH1-298 GEN
50/50
12.157
962771AG1-126 GEN
Solar/Wind Harmer
80.781
971347AH1-153 GEN
Solar/Wind Harmer
14.036
270071AF1-092 GEN
Solar/Wind Harmer
17.319
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971771AH1-392 GEN
Solar/Wind Harmer
8.916
274775LINCOLN ;6U
Adder
10.782
274776LINCOLN ;7U
Adder
10.782
274777LINCOLN ;8U
Adder
10.782
971769AH1-391 GEN
Solar/Wind Harmer
9.94
971619AH1-309 GEN
Solar/Wind Harmer
3.958
274814UNIV PK N;0U
Adder
6.363
274807UNIV PK N;3U
Adder
6.35
274805UNIV PK N;1U
Adder
6.322
274811UNIV PK N;7U
Adder
6.308
274827FISK ;RP
Adder
9.754
972037AH1-567 GEN1
Adder
0.23
960591AF2-350 GEN
Solar/Wind Harmer
8.77
972227AH1-698 GEN1
Adder
3.278
274687WILL CNTY;4U
Adder
34.988
274687WILL CNTY;4U
Adder
34.988
274675JOLIET 29;7U
Adder
38.397
274675JOLIET 29;7U
Adder
37.026
274731ELWOOD EC;2P
Adder
20.542
274733ELWOOD EC;3P
Adder
20.542
274735ELWOOD EC;4P
Adder
20.542
274728ELWOOD EC;5P
Adder
20.542
970833AG2-524 GEN
Solar/Wind Harmer
9.589
970833AG2-524 GEN
Solar/Wind Harmer
6.393
274746AC1-111 G10
Adder
6.959
274744AC1-111 GEN8
Adder
6.959
24729505KEY G4
Adder
8.06
270536AF1-215 GEN2
Solar/Wind Harmer
0.011
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971177AH1-047 GEN
Solar/Wind Harmer
5.267
276868AE1-113 GEN
Solar/Wind Harmer
1.713
276882AE2-255 GEN
Solar/Wind Harmer
0.998
971675AH1-338 GEN
Solar/Wind Harmer
3.323
971411AH1-196 GEN
Solar/Wind Harmer
12.781
274863CRW1-WTG
Solar/Wind Harmer
0.003
274864CRW2-WTG
Solar/Wind Harmer
0.003
971171AH1-044 GEN
Solar/Wind Harmer
16.979
971611AH1-305 GEN
Solar/Wind Harmer
5.045
274823ROCKFORD ;21
Adder
23.66
276612AE2-035 GEN
Solar/Wind Harmer
0.002
926823AC1-168 GEN
Solar/Wind Harmer
1.432
970169AG2-114 GEN
Solar/Wind Harmer
8.423
971681AH1-341 GEN
Solar/Wind Harmer
13.539
961011AF2-392 GEN
Solar/Wind Harmer
4.902
957751AF2-069 GEN
Solar/Wind Harmer
0.275
24690905MDL-1G C
Solar/Wind Harmer
0.003
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0.002
276655WTG1_EQ
Solar/Wind Harmer
0.003
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
8.664
941731AE2-173 GEN
Solar/Wind Harmer
6.876
946321AF1-296 GEN
Solar/Wind Harmer
4.594
965101AG1-375 GEN
Solar/Wind Harmer
8.195
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
963841AG1-237 GEN
Solar/Wind Harmer
3.463
945581AF1-223 GEN
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
10.716
971549AH1-272 GEN
Solar/Wind Harmer
16.349
276785W4-005 GEN1
Solar/Wind Harmer
0.001
270102X2-052 ST
50/50
2.06
270100X2-052 CT1
50/50
1.898
270101X2-052 CT2
50/50
1.898
970321AG2-212 GEN
Solar/Wind Harmer
4.074
965681AG1-436 GEN
Solar/Wind Harmer
11.195
965791AG1-447 GEN
Solar/Wind Harmer
8.21
274770LINCOLN ;1U
Adder
10.782
274771LINCOLN ;2U
Adder
10.782
270526AF1-158 GEN
Solar/Wind Harmer
0.011
24441505OLIV SLR
Solar/Wind Harmer
0
270216AD2-079_GEN
Solar/Wind Harmer
0.001
957891AF2-083 GEN
Solar/Wind Harmer
0.001
274808UNIV PK N;4U
Adder
6.281
972259AH1-714 GEN
Adder
24.011
274803UNIV PARK;6U
Adder
7.329
274888KELLY CRK;1U
Solar/Wind Harmer
0.515
274887GEN-1.85
Solar/Wind Harmer
0.231
276843GEN-1.7
Solar/Wind Harmer
0.284
958011AF2-095 GEN
Solar/Wind Harmer
12.628
247620Y3-023
Adder
0.578
961051AF2-396 GEN
Solar/Wind Harmer
17.455
961051AF2-396 GEN
Solar/Wind Harmer
11.637
274674JOLIET 9 ;6U
Adder
19.252
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
971573AH1-285 GEN
Solar/Wind Harmer
1.615
274696ROCKY RD ;4P
Adder
14.093
274695ROCKY RD ;2P
Adder
13.768
274693ROCKY RD ;1P
Adder
13.632
274697ROCKY RD ;3P
Adder
3.74
958481AF2-142 GEN
Solar/Wind Harmer
12.927
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
1.166
274683WAUKEGAN ;8U
Adder
26.009
274683WAUKEGAN ;8U
Adder
21.925
962691AG1-118 GEN
Solar/Wind Harmer
25.779
970921AG2-575 GEN
Solar/Wind Harmer
8.581
970921AG2-575 GEN
Solar/Wind Harmer
2.86
958491AF2-143 GEN
Solar/Wind Harmer
12.84
970611AG2-400 GEN
Solar/Wind Harmer
8.544
970627AG2-408 GEN
Solar/Wind Harmer
2.563
942991AE2-321 GEN
Solar/Wind Harmer
9.539
274879MINONK ;1U
Solar/Wind Harmer
0.36
971333AH1-146 GEN
Solar/Wind Harmer
17.035
971335AH1-147 GEN
Solar/Wind Harmer
17.035
971341AH1-150 GEN
Solar/Wind Harmer
16.979
971343AH1-151 GEN
Solar/Wind Harmer
16.979
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
274856ECOGROVE ;U1
Solar/Wind Harmer
0.199
276611AD2-172 GEN
Solar/Wind Harmer
0.002
938861AE1-114 GEN
Solar/Wind Harmer
4.764
274764LEE CO EC;5U
Adder
11.213
274765LEE CO EC;6U
Adder
11.213
274762LEE CO EC;3U
Adder
11.187
274763LEE CO EC;4U
Adder
11.081
276603SUBLETTE C
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
972267AH1-718 GEN
Adder
4.979
276741O09 GEN1
Solar/Wind Harmer
0.297
276708O09 GEN2
Solar/Wind Harmer
0.297
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.327
276646AC1-214 GEN2
Solar/Wind Harmer
0.327
944541AF1-119 GEN
Solar/Wind Harmer
0.557
960971AF2-388 GEN
Solar/Wind Harmer
4.876
276782AC1-033 GEN
Solar/Wind Harmer
0.001
960611AF2-352 GEN
Solar/Wind Harmer
2.724
966841AG1-555 GEN
Solar/Wind Harmer
0.919
942221AE2-234 GEN
Solar/Wind Harmer
0.04
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
970241AG2-163 GEN
Solar/Wind Harmer
4.592
270599AE1-208 GEN
Solar/Wind Harmer
7.039
270031AE2-169
Solar/Wind Harmer
4.223
276916AD2-100_GEN
Solar/Wind Harmer
16.09
276911AD2-131_GEN
Solar/Wind Harmer
1.06
971613AH1-306 GEN
Solar/Wind Harmer
3.675
945391AF1-204 GEN
Solar/Wind Harmer
7.93
960441AF2-335 GEN
Solar/Wind Harmer
7.358
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.289
276848AB2-070 GEN3
Solar/Wind Harmer
0.287
965041AG1-368 GEN
Solar/Wind Harmer
7.862
970289AG2-191 GEN
Solar/Wind Harmer
1.476
971609AH1-304 GEN
Solar/Wind Harmer
1.254
270594AE1-207 GEN
Solar/Wind Harmer
8.574
965051AG1-369 GEN
Solar/Wind Harmer
3.795
944221AF1-090 GEN
Solar/Wind Harmer
4.425
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
270024AE2-089 GEN
Solar/Wind Harmer
0.008
970115AG2-085 GEN
Solar/Wind Harmer
2.943
270054AF2-122 C O1
Solar/Wind Helper
1.539
270246TR4_N_V150
Solar/Wind Harmer
0.049
944231AF1-091 GEN
Solar/Wind Harmer
2.021
276903AD2-071 C
Solar/Wind Harmer
8.405
270005AE1-210 C O1
Solar/Wind Harmer
1.614
965031AG1-367 GEN
Solar/Wind Harmer
7.45
24695305TIMB G C
Solar/Wind Harmer
0.002
970333AG2-219 GEN
Solar/Wind Harmer
4.707
970239AG2-162 GEN
Solar/Wind Harmer
1.646
944201AF1-088_MTX
Adder
118.46
957141AF2-008_MTX
Adder
32.732
LAGNLTFEXP_LAGN->PJM
CLTF
16.296
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.027
TVALTFEXP_TVA->PJM
CLTF
7.706
CPLELTFEXP_CPLE->PJM
CLTF
3.24
CBM West 2LTFEXP_CBM-W2->PJM
CBM
120.262
NYPJM->LTFIMP_NY
CLTF
3.756
LGEELTFEXP_LGEE->PJM
CLTF
5.526
WECLTFEXP_WEC->PJM
CLTF
4.63
AG2-052LTFEXP_AG2-052->PJM
LTF
0.285
AH1-155LTFEXP_AH1-155->PJM
LTF
0.428
CBM West 1LTFEXP_CBM-W1->PJM
CBM
146.812
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.167
MECLTFEXP_MEC->PJM
CLTF
18.496
SIGELTFEXP_SIGE->PJM
CLTF
0.474

Details for 05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line l/o AEP_P1-2_#706_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#706_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.43 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5322.01
MW Contribution:19.68
Bus #Bus NameTypeMW Contribution
24721805FLATG3
50/50
5.145
24721705FLATG2
50/50
94.33
24344105CKG2
50/50
12.069
270143AC1-141 CT2_
50/50
3.558
24639705ELKHART HY
50/50
0.241
970521AG2-332 GEN
50/50
17.184
24721605FLATG1
50/50
5.145
971599AH1-298 GEN
50/50
14.587
270144AC1-141 ST1_
50/50
3.152
24653605MOTTVILLE
50/50
0.006
24643105BUCHANAN
50/50
0.019
962771AG1-126 GEN
Solar/Wind Harmer
120.047
270284AF1-227 GEN1
Solar/Wind Harmer
0.014
270286AF1-227 GEN2
Solar/Wind Harmer
0.006
270287AF1-227 GEN3
Solar/Wind Harmer
0.006
971347AH1-153 GEN
Solar/Wind Harmer
16.236
270071AF1-092 GEN
Solar/Wind Harmer
20.132
971771AH1-392 GEN
Solar/Wind Harmer
10.346
971619AH1-309 GEN
Solar/Wind Harmer
4.631
971769AH1-391 GEN
Solar/Wind Harmer
11.424
960681AF2-359 GEN
Solar/Wind Harmer
-0.002
24729505KEY G4
Adder
9.267
274775LINCOLN ;6U
Adder
11.972
274776LINCOLN ;7U
Adder
11.972
274777LINCOLN ;8U
Adder
11.972
965041AG1-368 GEN
Solar/Wind Harmer
9.847
270578AF1-285 GEN2
Solar/Wind Harmer
0.651
274814UNIV PK N;0U
Adder
7.057
274807UNIV PK N;3U
Adder
7.042
274805UNIV PK N;1U
Adder
7.011
274811UNIV PK N;7U
Adder
6.996
972037AH1-567 GEN1
Adder
0.254
274827FISK ;RP
Adder
10.776
960591AF2-350 GEN
Solar/Wind Harmer
9.68
972227AH1-698 GEN1
Adder
3.616
965051AG1-369 GEN
Solar/Wind Harmer
4.807
274687WILL CNTY;4U
Adder
38.503
274687WILL CNTY;4U
Adder
38.503
274675JOLIET 29;7U
Adder
42.223
274675JOLIET 29;7U
Adder
40.715
274728ELWOOD EC;5P
Adder
22.567
274731ELWOOD EC;2P
Adder
22.566
274733ELWOOD EC;3P
Adder
22.566
274735ELWOOD EC;4P
Adder
22.566
270536AF1-215 GEN2
Solar/Wind Harmer
0.012
970833AG2-524 GEN
Solar/Wind Harmer
10.52
970833AG2-524 GEN
Solar/Wind Harmer
7.013
971549AH1-272 GEN
Solar/Wind Harmer
19.681
274746AC1-111 G10
Adder
7.614
274744AC1-111 GEN8
Adder
7.614
963791AG1-232 GEN
Solar/Wind Harmer
12.76
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
1.183
270302AB2-170 GEN
Solar/Wind Harmer
0.006
270317AD1-130_GEN
Solar/Wind Harmer
0.013
971653AH1-327 GEN
Solar/Wind Harmer
1.314
958391AF2-133 GEN
Solar/Wind Harmer
0.001
276868AE1-113 GEN
Solar/Wind Harmer
1.855
276882AE2-255 GEN
Solar/Wind Harmer
1.081
971177AH1-047 GEN
Solar/Wind Harmer
5.697
965101AG1-375 GEN
Solar/Wind Harmer
9.202
971411AH1-196 GEN
Solar/Wind Harmer
13.802
971675AH1-338 GEN
Solar/Wind Harmer
3.588
274863CRW1-WTG
Solar/Wind Harmer
0.003
274864CRW2-WTG
Solar/Wind Harmer
0.003
971611AH1-305 GEN
Solar/Wind Harmer
5.454
971171AH1-044 GEN
Solar/Wind Harmer
18.285
274823ROCKFORD ;21
Adder
25.447
276612AE2-035 GEN
Solar/Wind Harmer
0.002
926823AC1-168 GEN
Solar/Wind Harmer
1.535
970169AG2-114 GEN
Solar/Wind Harmer
9.023
971681AH1-341 GEN
Solar/Wind Harmer
14.483
247607V1-011 GEN
Solar/Wind Harmer
0.001
961011AF2-392 GEN
Solar/Wind Harmer
5.219
945581AF1-223 GEN
Solar/Wind Harmer
0.001
970615AG2-402 GEN
50/50
3.512
247620Y3-023
50/50
0.722
270102X2-052 ST
50/50
2.354
270100X2-052 CT1
50/50
2.169
270101X2-052 CT2
50/50
2.169
270471AD2-092_GEN
Solar/Wind Harmer
0.009
970611AG2-400 GEN
Solar/Wind Harmer
10.537
970627AG2-408 GEN
Solar/Wind Harmer
3.161
970321AG2-212 GEN
Solar/Wind Harmer
4.559
270216AD2-079_GEN
Solar/Wind Harmer
0.002
957891AF2-083 GEN
Solar/Wind Harmer
0.001
270526AF1-158 GEN
Solar/Wind Harmer
0.013
24441505OLIV SLR
Solar/Wind Harmer
0
961051AF2-396 GEN
Solar/Wind Harmer
20.46
961051AF2-396 GEN
Solar/Wind Harmer
13.64
965681AG1-436 GEN
Solar/Wind Harmer
12.752
965791AG1-447 GEN
Solar/Wind Harmer
9.351
274770LINCOLN ;1U
Adder
11.972
274771LINCOLN ;2U
Adder
11.972
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
274808UNIV PK N;4U
Adder
6.965
274803UNIV PARK;6U
Adder
8.1
274888KELLY CRK;1U
Solar/Wind Harmer
0.568
274887GEN-1.85
Solar/Wind Harmer
0.255
276843GEN-1.7
Solar/Wind Harmer
0.313
958011AF2-095 GEN
Solar/Wind Harmer
13.939
972259AH1-714 GEN
Adder
26.463
274674JOLIET 9 ;6U
Adder
21.154
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
971573AH1-285 GEN
Solar/Wind Harmer
1.764
958481AF2-142 GEN
Solar/Wind Harmer
14.096
274695ROCKY RD ;2P
Adder
14.996
274693ROCKY RD ;1P
Adder
14.848
274697ROCKY RD ;3P
Adder
4.074
274696ROCKY RD ;4P
Adder
15.349
274861TOP CROP ;1U
Solar/Wind Harmer
0.003
274862TOP CROP ;2U
Solar/Wind Harmer
1.271
944541AF1-119 GEN
Solar/Wind Harmer
0.629
960971AF2-388 GEN
Solar/Wind Harmer
5.509
274683WAUKEGAN ;8U
Adder
28.303
274683WAUKEGAN ;8U
Adder
23.858
246938BC-WTG3
Solar/Wind Harmer
0.338
246937BC-WTG2
Solar/Wind Harmer
0.379
962691AG1-118 GEN
Solar/Wind Harmer
27.992
970921AG2-575 GEN
Solar/Wind Harmer
9.308
970921AG2-575 GEN
Solar/Wind Harmer
3.103
958491AF2-143 GEN
Solar/Wind Harmer
13.931
274879MINONK ;1U
Solar/Wind Harmer
0.39
942991AE2-321 GEN
Solar/Wind Harmer
10.32
971333AH1-146 GEN
Solar/Wind Harmer
18.389
971335AH1-147 GEN
Solar/Wind Harmer
18.389
971341AH1-150 GEN
Solar/Wind Harmer
18.285
971343AH1-151 GEN
Solar/Wind Harmer
18.285
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
942221AE2-234 GEN
Solar/Wind Harmer
0.046
274856ECOGROVE ;U1
Solar/Wind Harmer
0.213
276611AD2-172 GEN
Solar/Wind Harmer
0.002
938861AE1-114 GEN
Solar/Wind Harmer
5.096
274764LEE CO EC;5U
Adder
11.975
274765LEE CO EC;6U
Adder
11.975
274762LEE CO EC;3U
Adder
11.947
274763LEE CO EC;4U
Adder
11.834
276603SUBLETTE C
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
270007AE1-245 C
Solar/Wind Harmer
0.002
972267AH1-718 GEN
Adder
5.295
276741O09 GEN1
Solar/Wind Harmer
0.315
276708O09 GEN2
Solar/Wind Harmer
0.315
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.347
24307105BERRINSP G
50/50
0.032
962761AG1-125 GEN
Solar/Wind Harmer
120.047
970149AG2-104 GEN
Solar/Wind Harmer
129.655
970155AG2-107 GEN
Solar/Wind Harmer
76.659
270349AD2-093_GEN
Solar/Wind Harmer
0.009
965011AG1-365 GEN
Solar/Wind Harmer
10.537
970245AG2-165 GEN
Solar/Wind Harmer
4.559
270063AE2-323 C
Solar/Wind Harmer
0.008
270505AE1-170 C O1
Solar/Wind Harmer
10.806
945111AF1-176 GEN
Solar/Wind Harmer
18.321
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
5.329
274773LINCOLN ;4U
Adder
11.972
274774LINCOLN ;5U
Adder
11.972
274723RIVER EC ;12
Adder
25.205
274751CRETE EC ;1U
Adder
11.58
274754CRETE EC ;4U
Adder
11.58
270223U2-072_GEN1
Solar/Wind Harmer
0.001
276164X3-005 C
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
20.506
274812UNIV PK N;8U
Adder
6.996
274801UNIV PARK;4U
Adder
8.089
276776AD2-060 GEN
Solar/Wind Harmer
1.011
247521TR3_G114
Solar/Wind Harmer
0.351
270246TR4_N_V150
Solar/Wind Harmer
0.062
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
42.222
274674JOLIET 9 ;6U
Adder
21.154
274732ELWOOD EC;7P
Adder
22.567
270055AF2-134 C O1
Solar/Wind Harmer
0.007
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
274745AC1-111 GEN9
Adder
7.614
944231AF1-091 GEN
Solar/Wind Harmer
2.532
24695305TIMB G C
Solar/Wind Harmer
0.002
965421AG1-410 GEN
Solar/Wind Harmer
28.36
958381AF2-132 GEN
Solar/Wind Harmer
0.001
276691AA1-018 GEN1
Solar/Wind Harmer
1.138
965651AG1-433 GEN
Solar/Wind Harmer
2.755
274682WAUKEGAN ;7U
Adder
24.169
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
12.195
274828WAUKEGAN ;BP
Adder
14.836
246936BC-WTG1
Solar/Wind Harmer
0.379
270489AE1-102 GEN1
Solar/Wind Harmer
1.214
270462AD2-086
Solar/Wind Harmer
0.02
962781AG1-127 GEN
Solar/Wind Harmer
8.858
939401AE1-172 GEN
Solar/Wind Harmer
6.954
274872LEEDK;1U
Solar/Wind Harmer
0.006
276901AD2-066 C O1
Solar/Wind Harmer
0.009
971997AH1-543 GEN
Solar/Wind Harmer
4.843
958861AF2-177 GEN
Solar/Wind Harmer
3.987
276861AD2-134 GEN
Solar/Wind Harmer
0.165
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
11.452
957471AF2-041 GEN
Solar/Wind Harmer
27.428
959081AF2-199 GEN
Solar/Wind Harmer
9.143
971067AG2-660 GEN
Solar/Wind Harmer
3.048
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
274822ROCKFORD ;11
Adder
25.633
972235AH1-702 GEN1
Adder
3.284
970819AG2-516 GEN
Solar/Wind Harmer
10.874
971475AH1-234 GEN
Solar/Wind Harmer
4.385
970569AG2-363 GEN
Solar/Wind Harmer
27.095
274857EASY ROAD;U1
Solar/Wind Harmer
0.002
274761LEE CO EC;2U
Adder
11.947
274766LEE CO EC;7U
Adder
11.806
276158O29GEN2
Solar/Wind Harmer
0.001
945371AF1-202 GEN
Solar/Wind Harmer
0.001
274877BISHOP HL;1U
Solar/Wind Harmer
0.295
24791305MDL-5G
Solar/Wind Harmer
0.001
276726Z2-087_GEN
Solar/Wind Harmer
0.003
939741AE1-205 GEN
Solar/Wind Harmer
12.194
274854TWINGROVE;U2
Solar/Wind Harmer
0.004
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
972175AH1-670 GEN
Solar/Wind Harmer
6.873
970291AG2-192 GEN
Solar/Wind Harmer
1.08
270032AE2-172
Solar/Wind Harmer
5.46
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
3.14
963741AG1-226 GEN
Solar/Wind Harmer
19.026
270005AE1-210 C O1
Solar/Wind Harmer
1.733
965031AG1-367 GEN
Solar/Wind Harmer
8
276615X2-022 GEN
Solar/Wind Harmer
0.084
276903AD2-071 C
Solar/Wind Harmer
8.872
970825AG2-519 GEN
Solar/Wind Harmer
2.793
965911AG1-460 GEN
Solar/Wind Harmer
1.538
24728605AND G2
Adder
3.739
957751AF2-069 GEN
Solar/Wind Harmer
0.292
24690905MDL-1G C
Solar/Wind Harmer
0.003
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0.002
276655WTG1_EQ
Solar/Wind Harmer
0.003
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
9.145
941731AE2-173 GEN
Solar/Wind Harmer
7.258
946321AF1-296 GEN
Solar/Wind Harmer
4.827
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
270024AE2-089 GEN
Solar/Wind Harmer
0.009
971609AH1-304 GEN
Solar/Wind Harmer
1.375
970289AG2-191 GEN
Solar/Wind Harmer
1.578
963841AG1-237 GEN
Solar/Wind Harmer
3.575
270594AE1-207 GEN
Solar/Wind Harmer
9.172
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.295
276848AB2-070 GEN3
Solar/Wind Harmer
0.294
970115AG2-085 GEN
Solar/Wind Harmer
3.159
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
270297AD1-101 GEN
Solar/Wind Harmer
0.002
24722005FLATG5
50/50
5.145
24721905FLATG4
50/50
94.33
270475AD2-096_GEN
50/50
10.026
270142AC1-141 CT1_
50/50
3.558
24641605TWIN BRNCH
50/50
0.026
24344005CKG1
50/50
9.691
24642205MAYFLWER
50/50
0.992
944961AF1-161 GEN
50/50
4.253
962601AG1-109 GEN
50/50
4.253
247604X1-042
50/50
0.632
970153AG2-106 GEN
Solar/Wind Harmer
76.659
270043AE2-236 GEN
Solar/Wind Harmer
6.969
970349AG2-230 GEN
Solar/Wind Harmer
16.236
959331AF2-224 GEN
Solar/Wind Harmer
7.376
965021AG1-366 GEN
Solar/Wind Harmer
3.512
970513AG2-328 GEN
Solar/Wind Harmer
4.559
970517AG2-330 GEN
Solar/Wind Harmer
27.357
247643Z2-116 C
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
6.732
945111AF1-176 GEN
Solar/Wind Harmer
8.323
944531AF1-118 GEN
Solar/Wind Harmer
45.595
24441205WTRV SLR C
Solar/Wind Harmer
0
274772LINCOLN ;3U
Adder
11.972
274724RIVER EC ;11
Adder
24.913
276646AC1-214 GEN2
Solar/Wind Harmer
0.347
970623AG2-406 GEN
Solar/Wind Harmer
1.614
276782AC1-033 GEN
Solar/Wind Harmer
0.001
960611AF2-352 GEN
Solar/Wind Harmer
2.854
966841AG1-555 GEN
Solar/Wind Harmer
0.959
270599AE1-208 GEN
Solar/Wind Harmer
7.715
270031AE2-169
Solar/Wind Harmer
4.629
971613AH1-306 GEN
Solar/Wind Harmer
3.931
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
970241AG2-163 GEN
Solar/Wind Harmer
4.69
960441AF2-335 GEN
Solar/Wind Harmer
7.897
970825AG2-519 GEN
Solar/Wind Harmer
8.719
964611AG1-324 GEN
Solar/Wind Harmer
0.584
270201AC2-176 GEN
Solar/Wind Harmer
0.001
970621AG2-405 GEN
Solar/Wind Harmer
1.413
247621Y3-024
Adder
0.262
276916AD2-100_GEN
Solar/Wind Harmer
13.41
276911AD2-131_GEN
Solar/Wind Harmer
0.883
274752CRETE EC ;2U
Adder
11.58
274753CRETE EC ;3U
Adder
11.58
270391AF1-285 GEN3
Solar/Wind Harmer
0.651
970707AG2-453 GEN
Solar/Wind Harmer
31.724
274802UNIV PARK;5U
Adder
8.1
274826FISK ;BP
Adder
15.205
274800UNIV PARK;3U
Adder
8.089
972038AH1-567 GEN2
Adder
0.506
276806AD2-047 C O1
Solar/Wind Harmer
5.485
970941AG2-585 GEN
Solar/Wind Harmer
12.1
972228AH1-698 GEN2
Adder
5.135
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.062
276897AD1-100 C
Solar/Wind Harmer
0.013
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
274676JOLIET 29;8U
Adder
40.714
274730ELWOOD EC;6P
Adder
22.567
274734ELWOOD EC;8P
Adder
22.567
274736ELWOOD EC;9P
Adder
22.567
274729ELWOOD EC;1P
Adder
22.566
276893AG1-478 C
Solar/Wind Harmer
0.379
270535AF1-215 GEN1
Solar/Wind Harmer
0.012
943121AE2-341 GEN
Solar/Wind Harmer
15.96
943591AF1-030 GEN
Solar/Wind Harmer
10.614
964401AG1-302 GEN
Solar/Wind Harmer
0.001
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
24.169
270491AE1-102 GEN2
Solar/Wind Harmer
1.214
270485AE1-090_GEN
Solar/Wind Harmer
0.001
276805AD2-038 GEN
Solar/Wind Harmer
0.003
274872LEEDK;1U
Solar/Wind Harmer
0.341
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
0.982
274855GSG-6 ;RU
Solar/Wind Harmer
0.337
274850MENDOTA H;RU
Solar/Wind Harmer
0.108
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.165
959091AF2-200 GEN
Solar/Wind Harmer
18.285
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
2.856
970571AG2-364 GEN
Solar/Wind Harmer
18.064
274858EASY ROAD;U2
Solar/Wind Harmer
0.002
274760LEE CO EC;1U
Adder
11.947
274767LEE CO EC;8U
Adder
11.806
276157O29GEN1
Solar/Wind Harmer
1.431
270258AD1-119 GEN
Solar/Wind Harmer
0.002
274878BISHOP HL;2U
Solar/Wind Harmer
0.295
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
8.785
270404AC1-167 GEN
Solar/Wind Harmer
0.004
942111AE2-223 GEN
Solar/Wind Harmer
2.831
965931AG1-462 GEN
Solar/Wind Harmer
21.861
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
965091AG1-374 GEN
Solar/Wind Harmer
25.685
959611AF2-252 GEN
Solar/Wind Harmer
2.854
971617AH1-308 GEN
Solar/Wind Harmer
7.03
247642Z2-115 C
Solar/Wind Harmer
0.004
970289AG2-191 GEN
Solar/Wind Harmer
0.914
970291AG2-192 GEN
Solar/Wind Harmer
0.831
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
3.74
276668AB2-070 GEN1
Solar/Wind Harmer
0.295
958821AF2-173 GEN
Solar/Wind Harmer
11.2
270004AE1-209 GEN
Solar/Wind Harmer
1.733
276621W2-048 GEN
Solar/Wind Harmer
0.401
276838X2-022 GEN2
Solar/Wind Harmer
0.448
946031AF1-268 GEN
Solar/Wind Harmer
7.422
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
11.672
942481AE2-261 GEN
Solar/Wind Harmer
22.986
24728705AND G3
Adder
7.82
24728505AND G1
Adder
3.739
944201AF1-088_MTX
Adder
85.667
LAGNLTFEXP_LAGN->PJM
CLTF
11.144
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.328
TVALTFEXP_TVA->PJM
CLTF
4.56
CBM West 2LTFEXP_CBM-W2->PJM
CBM
96.989
NYPJM->LTFIMP_NY
CLTF
2.99
LGEELTFEXP_LGEE->PJM
CLTF
4.155
WECLTFEXP_WEC->PJM
CLTF
4.968
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.286
AG2-052LTFEXP_AG2-052->PJM
LTF
0.312
AH1-155LTFEXP_AH1-155->PJM
LTF
0.469
CBM West 1LTFEXP_CBM-W1->PJM
CBM
161.402
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.132
MECLTFEXP_MEC->PJM
CLTF
18.394
SIGELTFEXP_SIGE->PJM
CLTF
0.399

Details for 05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.86 %
Rating:4047.0 MVA
Rating Type:A
MVA to Mitigate:4648.25
MW Contribution:14.03
Bus #Bus NameTypeMW Contribution
24344105CKG2
50/50
8.939
270143AC1-141 CT2_
50/50
2.603
24639705ELKHART HY
50/50
0.176
970521AG2-332 GEN
50/50
12.519
274773LINCOLN ;4U
50/50
9.593
274774LINCOLN ;5U
50/50
9.593
962761AG1-125 GEN
Solar/Wind Harmer
74.603
970149AG2-104 GEN
Solar/Wind Harmer
80.573
970155AG2-107 GEN
Solar/Wind Harmer
47.639
970245AG2-165 GEN
Solar/Wind Harmer
3.44
270505AE1-170 C O1
Solar/Wind Harmer
7.896
270063AE2-323 C
Solar/Wind Harmer
0.006
945111AF1-176 GEN
Solar/Wind Harmer
13.37
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
3.886
274723RIVER EC ;12
Adder
18.99
274751CRETE EC ;1U
Adder
8.717
274754CRETE EC ;4U
Adder
8.717
971599AH1-298 GEN
50/50
10.558
270144AC1-141 ST1_
50/50
2.306
24643105BUCHANAN
50/50
0.014
24653605MOTTVILLE
50/50
0.004
274775LINCOLN ;6U
50/50
9.593
274776LINCOLN ;7U
50/50
9.593
274777LINCOLN ;8U
50/50
9.593
962771AG1-126 GEN
Solar/Wind Harmer
74.603
971347AH1-153 GEN
Solar/Wind Harmer
12.013
270071AF1-092 GEN
Solar/Wind Harmer
14.717
971771AH1-392 GEN
Solar/Wind Harmer
7.604
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971769AH1-391 GEN
Solar/Wind Harmer
8.444
971619AH1-309 GEN
Solar/Wind Harmer
3.384
274814UNIV PK N;0U
Adder
5.324
274807UNIV PK N;3U
Adder
5.313
274805UNIV PK N;1U
Adder
5.29
274811UNIV PK N;7U
Adder
5.278
274827FISK ;RP
Adder
8.149
972037AH1-567 GEN1
Adder
0.192
960591AF2-350 GEN
Solar/Wind Harmer
7.323
972227AH1-698 GEN1
Adder
2.737
274687WILL CNTY;4U
Adder
29.176
274687WILL CNTY;4U
Adder
29.176
274675JOLIET 29;7U
Adder
32.008
274675JOLIET 29;7U
Adder
30.865
24729505KEY G4
Adder
6.759
274731ELWOOD EC;2P
Adder
17.114
274733ELWOOD EC;3P
Adder
17.114
274735ELWOOD EC;4P
Adder
17.114
274728ELWOOD EC;5P
Adder
17.114
970833AG2-524 GEN
Solar/Wind Harmer
7.985
970833AG2-524 GEN
Solar/Wind Harmer
5.323
274746AC1-111 G10
Adder
5.788
274744AC1-111 GEN8
Adder
5.788
270536AF1-215 GEN2
Solar/Wind Harmer
0.009
971177AH1-047 GEN
Solar/Wind Harmer
4.355
958391AF2-133 GEN
Solar/Wind Harmer
0.001
276868AE1-113 GEN
Solar/Wind Harmer
1.417
276882AE2-255 GEN
Solar/Wind Harmer
0.825
971675AH1-338 GEN
Solar/Wind Harmer
2.746
971411AH1-196 GEN
Solar/Wind Harmer
10.56
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
971171AH1-044 GEN
Solar/Wind Harmer
14.009
274823ROCKFORD ;21
Adder
19.51
971611AH1-305 GEN
Solar/Wind Harmer
4.152
276612AE2-035 GEN
Solar/Wind Harmer
0.002
926823AC1-168 GEN
Solar/Wind Harmer
1.178
970169AG2-114 GEN
Solar/Wind Harmer
6.92
971681AH1-341 GEN
Solar/Wind Harmer
11.133
961011AF2-392 GEN
Solar/Wind Harmer
4.021
957751AF2-069 GEN
Solar/Wind Harmer
0.225
971549AH1-272 GEN
Solar/Wind Harmer
14.034
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
965101AG1-375 GEN
Solar/Wind Harmer
6.746
965041AG1-368 GEN
Solar/Wind Harmer
6.733
276655WTG1_EQ
Solar/Wind Harmer
0.003
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.06
941731AE2-173 GEN
Solar/Wind Harmer
5.603
946321AF1-296 GEN
Solar/Wind Harmer
3.744
963791AG1-232 GEN
Solar/Wind Harmer
8.989
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
945581AF1-223 GEN
Solar/Wind Harmer
0
965051AG1-369 GEN
Solar/Wind Harmer
3.241
963841AG1-237 GEN
Solar/Wind Harmer
2.776
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.231
276848AB2-070 GEN3
Solar/Wind Harmer
0.23
970289AG2-191 GEN
Solar/Wind Harmer
1.184
971609AH1-304 GEN
Solar/Wind Harmer
1.011
270594AE1-207 GEN
Solar/Wind Harmer
6.856
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.765
270284AF1-227 GEN1
Solar/Wind Harmer
0.008
270286AF1-227 GEN2
Solar/Wind Harmer
0.003
270287AF1-227 GEN3
Solar/Wind Harmer
0.003
270054AF2-122 C O1
Solar/Wind Helper
1.65
276164X3-005 C
Solar/Wind Harmer
0
965011AG1-365 GEN
Solar/Wind Harmer
7.366
274812UNIV PK N;8U
Adder
5.278
970373AG2-245 GEN
Solar/Wind Harmer
15.386
276776AD2-060 GEN
Solar/Wind Harmer
0.765
274801UNIV PARK;4U
Adder
6.118
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
32.008
274674JOLIET 9 ;6U
Adder
16.042
274732ELWOOD EC;7P
Adder
17.114
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
274745AC1-111 GEN9
Adder
5.788
270055AF2-134 C O1
Solar/Wind Harmer
0.006
276691AA1-018 GEN1
Solar/Wind Harmer
0.866
274682WAUKEGAN ;7U
Adder
18.416
274828WAUKEGAN ;BP
Adder
11.308
958381AF2-132 GEN
Solar/Wind Harmer
0.001
962781AG1-127 GEN
Solar/Wind Harmer
6.763
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.233
274872LEEDK;1U
Solar/Wind Harmer
0.004
939401AE1-172 GEN
Solar/Wind Harmer
5.304
276901AD2-066 C O1
Solar/Wind Harmer
0.007
971997AH1-543 GEN
Solar/Wind Harmer
3.701
276861AD2-134 GEN
Solar/Wind Harmer
0.126
957471AF2-041 GEN
Solar/Wind Harmer
21.014
959081AF2-199 GEN
Solar/Wind Harmer
7.005
971067AG2-660 GEN
Solar/Wind Harmer
2.335
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
274822ROCKFORD ;11
Adder
19.652
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.717
972235AH1-702 GEN1
Adder
2.519
970819AG2-516 GEN
Solar/Wind Harmer
8.346
971475AH1-234 GEN
Solar/Wind Harmer
3.368
970569AG2-363 GEN
Solar/Wind Harmer
20.788
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
9.191
274766LEE CO EC;7U
Adder
9.083
965651AG1-433 GEN
Solar/Wind Harmer
2.017
276158O29GEN2
Solar/Wind Harmer
0.001
274877BISHOP HL;1U
Solar/Wind Harmer
0.228
24721705FLATG2
Adder
19.64
24791305MDL-5G
Solar/Wind Harmer
0.001
958861AF2-177 GEN
Solar/Wind Harmer
2.923
276726Z2-087_GEN
Solar/Wind Harmer
0.002
939741AE1-205 GEN
Solar/Wind Harmer
9.413
274854TWINGROVE;U2
Solar/Wind Harmer
0.003
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.002
944231AF1-091 GEN
Solar/Wind Harmer
1.739
945371AF1-202 GEN
Solar/Wind Harmer
0.001
247521TR3_G114
Solar/Wind Harmer
0.237
270246TR4_N_V150
Solar/Wind Harmer
0.042
972175AH1-670 GEN
Solar/Wind Harmer
5.355
270349AD2-093_GEN
Solar/Wind Harmer
0.005
24695305TIMB G C
Solar/Wind Harmer
0.002
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
2.462
963741AG1-226 GEN
Solar/Wind Harmer
14.839
276615X2-022 GEN
Solar/Wind Harmer
0.066
970291AG2-192 GEN
Solar/Wind Harmer
0.81
965421AG1-410 GEN
Solar/Wind Harmer
18.496
270032AE2-172
Solar/Wind Harmer
4.081
965911AG1-460 GEN
Solar/Wind Harmer
1.218
246936BC-WTG1
Solar/Wind Harmer
0.245
270489AE1-102 GEN1
Solar/Wind Harmer
0.785
270102X2-052 ST
50/50
1.747
270100X2-052 CT1
50/50
1.61
270101X2-052 CT2
50/50
1.61
247620Y3-023
50/50
0.525
274770LINCOLN ;1U
50/50
9.593
274771LINCOLN ;2U
50/50
9.593
970321AG2-212 GEN
Solar/Wind Harmer
3.44
270216AD2-079_GEN
Solar/Wind Harmer
0.001
965681AG1-436 GEN
Solar/Wind Harmer
9.481
965791AG1-447 GEN
Solar/Wind Harmer
6.953
270526AF1-158 GEN
Solar/Wind Harmer
0.009
24441505OLIV SLR
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
14.924
961051AF2-396 GEN
Solar/Wind Harmer
9.95
970611AG2-400 GEN
Solar/Wind Harmer
7.366
970627AG2-408 GEN
Solar/Wind Harmer
2.21
274808UNIV PK N;4U
Adder
5.255
972259AH1-714 GEN
Adder
20.044
274803UNIV PARK;6U
Adder
6.123
274888KELLY CRK;1U
Solar/Wind Harmer
0.43
274887GEN-1.85
Solar/Wind Harmer
0.193
276843GEN-1.7
Solar/Wind Harmer
0.237
958011AF2-095 GEN
Solar/Wind Harmer
10.545
274674JOLIET 9 ;6U
Adder
16.042
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
971573AH1-285 GEN
Solar/Wind Harmer
1.342
274695ROCKY RD ;2P
Adder
11.425
274693ROCKY RD ;1P
Adder
11.312
274697ROCKY RD ;3P
Adder
3.104
274696ROCKY RD ;4P
Adder
11.694
958481AF2-142 GEN
Solar/Wind Harmer
10.727
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.967
274683WAUKEGAN ;8U
Adder
21.572
274683WAUKEGAN ;8U
Adder
18.184
962691AG1-118 GEN
Solar/Wind Harmer
21.36
970921AG2-575 GEN
Solar/Wind Harmer
7.106
970921AG2-575 GEN
Solar/Wind Harmer
2.369
958491AF2-143 GEN
Solar/Wind Harmer
10.627
942991AE2-321 GEN
Solar/Wind Harmer
7.889
274879MINONK ;1U
Solar/Wind Harmer
0.298
971333AH1-146 GEN
Solar/Wind Harmer
14.073
971335AH1-147 GEN
Solar/Wind Harmer
14.073
971341AH1-150 GEN
Solar/Wind Harmer
14.009
971343AH1-151 GEN
Solar/Wind Harmer
14.009
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
274856ECOGROVE ;U1
Solar/Wind Harmer
0.164
276611AD2-172 GEN
Solar/Wind Harmer
0.002
938861AE1-114 GEN
Solar/Wind Harmer
3.917
274764LEE CO EC;5U
Adder
9.213
274765LEE CO EC;6U
Adder
9.213
274762LEE CO EC;3U
Adder
9.191
274763LEE CO EC;4U
Adder
9.105
276603SUBLETTE C
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.461
960971AF2-388 GEN
Solar/Wind Harmer
4.033
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
972267AH1-718 GEN
Adder
4.082
276741O09 GEN1
Solar/Wind Harmer
0.243
276708O09 GEN2
Solar/Wind Harmer
0.243
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.268
276646AC1-214 GEN2
Solar/Wind Harmer
0.268
276782AC1-033 GEN
Solar/Wind Harmer
0.001
960611AF2-352 GEN
Solar/Wind Harmer
2.211
942221AE2-234 GEN
Solar/Wind Harmer
0.033
966841AG1-555 GEN
Solar/Wind Harmer
0.741
270471AD2-092_GEN
Solar/Wind Harmer
0.005
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
970241AG2-163 GEN
Solar/Wind Harmer
3.657
270599AE1-208 GEN
Solar/Wind Harmer
5.676
270031AE2-169
Solar/Wind Harmer
3.406
971613AH1-306 GEN
Solar/Wind Harmer
2.938
276916AD2-100_GEN
Solar/Wind Harmer
12.71
276911AD2-131_GEN
Solar/Wind Harmer
0.837
246938BC-WTG3
Solar/Wind Harmer
0.219
246937BC-WTG2
Solar/Wind Harmer
0.245
270142AC1-141 CT1_
50/50
2.603
24641605TWIN BRNCH
50/50
0.019
24344005CKG1
50/50
7.096
24642205MAYFLWER
50/50
0.728
274772LINCOLN ;3U
50/50
9.593
970153AG2-106 GEN
Solar/Wind Harmer
47.639
970349AG2-230 GEN
Solar/Wind Harmer
12.013
970513AG2-328 GEN
Solar/Wind Harmer
3.44
970517AG2-330 GEN
Solar/Wind Harmer
20.64
270043AE2-236 GEN
Solar/Wind Harmer
5.033
247643Z2-116 C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
6.073
970031AG2-029 GEN
Solar/Wind Harmer
4.844
944531AF1-118 GEN
Solar/Wind Harmer
33.218
274724RIVER EC ;11
Adder
18.771
274752CRETE EC ;2U
Adder
8.717
274753CRETE EC ;3U
Adder
8.717
959331AF2-224 GEN
Solar/Wind Harmer
5.157
965021AG1-366 GEN
Solar/Wind Harmer
2.455
970707AG2-453 GEN
Solar/Wind Harmer
24.03
274826FISK ;BP
Adder
11.498
274802UNIV PARK;5U
Adder
6.123
276806AD2-047 C O1
Solar/Wind Harmer
4.15
970941AG2-585 GEN
Solar/Wind Harmer
9.154
274800UNIV PARK;3U
Adder
6.118
972038AH1-567 GEN2
Adder
0.383
972228AH1-698 GEN2
Adder
3.887
24441205WTRV SLR C
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
0.01
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
274676JOLIET 29;8U
Adder
30.865
274729ELWOOD EC;1P
Adder
17.114
274730ELWOOD EC;6P
Adder
17.114
274734ELWOOD EC;8P
Adder
17.114
274736ELWOOD EC;9P
Adder
17.114
276893AG1-478 C
Solar/Wind Harmer
0.288
943121AE2-341 GEN
Solar/Wind Harmer
12.132
943591AF1-030 GEN
Solar/Wind Harmer
8.068
247604X1-042
Adder
0.432
270535AF1-215 GEN1
Solar/Wind Harmer
0.009
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
18.416
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274872LEEDK;1U
Solar/Wind Harmer
0.26
276805AD2-038 GEN
Solar/Wind Harmer
0.002
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.751
274855GSG-6 ;RU
Solar/Wind Harmer
0.258
274850MENDOTA H;RU
Solar/Wind Harmer
0.083
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.126
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
959091AF2-200 GEN
Solar/Wind Harmer
14.009
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
2.191
970571AG2-364 GEN
Solar/Wind Harmer
13.859
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
9.191
274767LEE CO EC;8U
Adder
9.083
276157O29GEN1
Solar/Wind Harmer
1.104
274878BISHOP HL;2U
Solar/Wind Harmer
0.228
24721905FLATG4
Adder
19.64
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.747
942111AE2-223 GEN
Solar/Wind Harmer
2.185
965931AG1-462 GEN
Solar/Wind Harmer
16.976
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
965091AG1-374 GEN
Solar/Wind Harmer
19.897
959611AF2-252 GEN
Solar/Wind Harmer
2.211
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.042
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
2.93
276668AB2-070 GEN1
Solar/Wind Harmer
0.231
247642Z2-115 C
Solar/Wind Harmer
0.003
276621W2-048 GEN
Solar/Wind Harmer
0.316
276838X2-022 GEN2
Solar/Wind Harmer
0.352
970289AG2-191 GEN
Solar/Wind Harmer
0.686
970291AG2-192 GEN
Solar/Wind Harmer
0.623
942481AE2-261 GEN
Solar/Wind Harmer
18.215
270491AE1-102 GEN2
Solar/Wind Harmer
0.785
LAGNLTFEXP_LAGN->PJM
CLTF
11.239
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.669
TVALTFEXP_TVA->PJM
CLTF
5.062
CPLELTFEXP_CPLE->PJM
CLTF
1.429
CBM West 2LTFEXP_CBM-W2->PJM
CBM
87.023
NYPJM->LTFIMP_NY
CLTF
2.589
LGEELTFEXP_LGEE->PJM
CLTF
3.659
WECLTFEXP_WEC->PJM
CLTF
3.814
AG2-052LTFEXP_AG2-052->PJM
LTF
0.236
AH1-155LTFEXP_AH1-155->PJM
LTF
0.355
CBM West 1LTFEXP_CBM-W1->PJM
CBM
120.019
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.189
MECLTFEXP_MEC->PJM
CLTF
14.69
SIGELTFEXP_SIGE->PJM
CLTF
0.339

Details for 05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line l/o ATSI_P7-1_TE-345-027A_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Contingency Name:
ATSI_P7-1_TE-345-027A_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:110.09 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5032.32
MW Contribution:15.97
Bus #Bus NameTypeMW Contribution
24344105CKG2
50/50
9.384
270143AC1-141 CT2_
50/50
2.761
24639705ELKHART HY
50/50
0.186
970521AG2-332 GEN
50/50
13.281
24307105BERRINSP G
50/50
0.025
962761AG1-125 GEN
Solar/Wind Harmer
89.197
970149AG2-104 GEN
Solar/Wind Harmer
110.158
970155AG2-107 GEN
Solar/Wind Harmer
38.894
970245AG2-165 GEN
Solar/Wind Harmer
21.268
270505AE1-170 C O1
Solar/Wind Harmer
17.176
945111AF1-176 GEN
Solar/Wind Harmer
20.364
270063AE2-323 C
Solar/Wind Harmer
2.513
270449AD2-020 GEN
Solar/Wind Harmer
3.183
943021AE2-325 GEN
Solar/Wind Harmer
4.136
972207SS24-0001
Solar/Wind Harmer
24.8
274773LINCOLN ;4U
Adder
6.975
274774LINCOLN ;5U
Adder
6.975
965011AG1-365 GEN
Solar/Wind Harmer
11.187
274723RIVER EC ;12
Adder
19.976
274751CRETE EC ;1U
Adder
5.442
274754CRETE EC ;4U
Adder
5.442
276164X3-005 C
Solar/Wind Harmer
0.781
274812UNIV PK N;8U
Adder
5.552
970373AG2-245 GEN
Solar/Wind Harmer
23.259
276776AD2-060 GEN
Solar/Wind Harmer
0.467
274801UNIV PARK;4U
Adder
6.433
941551AE2-152 GEN
Solar/Wind Harmer
4.986
274676JOLIET 29;8U
Adder
33.648
274674JOLIET 9 ;6U
Adder
16.864
274732ELWOOD EC;7P
Adder
17.991
274871GR RIDGE ;2U
Solar/Wind Harmer
8.406
270055AF2-134 C O1
Solar/Wind Harmer
3.301
274745AC1-111 GEN9
Adder
6.083
276691AA1-018 GEN1
Solar/Wind Harmer
0.502
274682WAUKEGAN ;7U
Adder
19.358
274828WAUKEGAN ;BP
Adder
11.886
958381AF2-132 GEN
Solar/Wind Harmer
9.749
964861AG1-349 GEN
Solar/Wind Harmer
8.434
971917AH1-482 GEN
Solar/Wind Harmer
9.733
971599AH1-298 GEN
50/50
11.057
270144AC1-141 ST1_
50/50
2.446
24643105BUCHANAN
50/50
0.015
24653605MOTTVILLE
50/50
0.004
962771AG1-126 GEN
Solar/Wind Harmer
89.197
971347AH1-153 GEN
Solar/Wind Harmer
18.111
270071AF1-092 GEN
Solar/Wind Harmer
17.338
971771AH1-392 GEN
Solar/Wind Harmer
10.383
960681AF2-359 GEN
Solar/Wind Harmer
4.333
971769AH1-391 GEN
Solar/Wind Harmer
11.46
944161AF1-084 GEN
Solar/Wind Harmer
2.498
274775LINCOLN ;6U
Adder
6.975
274776LINCOLN ;7U
Adder
6.975
274777LINCOLN ;8U
Adder
6.975
274814UNIV PK N;0U
Adder
5.601
274807UNIV PK N;3U
Adder
5.589
274805UNIV PK N;1U
Adder
5.565
274811UNIV PK N;7U
Adder
5.552
972037AH1-567 GEN1
Adder
0.202
274827FISK ;RP
Adder
8.568
960591AF2-350 GEN
Solar/Wind Harmer
11.036
972227AH1-698 GEN1
Adder
2.877
274687WILL CNTY;4U
Adder
30.673
274687WILL CNTY;4U
Adder
30.673
274675JOLIET 29;7U
Adder
33.649
274675JOLIET 29;7U
Adder
32.447
274731ELWOOD EC;2P
Adder
17.991
274733ELWOOD EC;3P
Adder
17.991
274735ELWOOD EC;4P
Adder
17.991
274728ELWOOD EC;5P
Adder
17.991
970833AG2-524 GEN
Solar/Wind Harmer
9.547
970833AG2-524 GEN
Solar/Wind Harmer
4.44
24729505KEY G4
Adder
7.093
270536AF1-215 GEN2
Solar/Wind Harmer
4.953
274746AC1-111 G10
Adder
6.083
274744AC1-111 GEN8
Adder
6.083
958391AF2-133 GEN
Solar/Wind Harmer
9.677
971177AH1-047 GEN
Solar/Wind Harmer
6.235
276868AE1-113 GEN
Solar/Wind Harmer
10.768
276882AE2-255 GEN
Solar/Wind Harmer
3.589
270142AC1-141 CT1_
50/50
2.761
24344005CKG1
50/50
7.535
24641605TWIN BRNCH
50/50
0.02
24642205MAYFLWER
50/50
0.772
944961AF1-161 GEN
50/50
3.302
962601AG1-109 GEN
50/50
3.302
970153AG2-106 GEN
Solar/Wind Harmer
38.894
970349AG2-230 GEN
Solar/Wind Harmer
18.111
970513AG2-328 GEN
Solar/Wind Harmer
21.268
970517AG2-330 GEN
Solar/Wind Harmer
19.29
270043AE2-236 GEN
Solar/Wind Harmer
6.511
247643Z2-116 C
Solar/Wind Harmer
0.08
945111AF1-176 GEN
Solar/Wind Harmer
6.454
970031AG2-029 GEN
Solar/Wind Harmer
33.986
274772LINCOLN ;3U
Adder
6.975
24441205WTRV SLR C
Solar/Wind Harmer
0.151
959331AF2-224 GEN
Solar/Wind Harmer
11.187
965021AG1-366 GEN
Solar/Wind Harmer
2.602
274724RIVER EC ;11
Adder
19.746
944531AF1-118 GEN
Solar/Wind Harmer
39.003
972231SS25-0005
Solar/Wind Harmer
10.567
972181SS23-001
Solar/Wind Harmer
6.604
274752CRETE EC ;2U
Adder
5.442
274753CRETE EC ;3U
Adder
5.442
247604X1-042
Adder
0.463
970707AG2-453 GEN
Solar/Wind Harmer
31.017
274802UNIV PARK;5U
Adder
6.439
274826FISK ;BP
Adder
12.09
276772AC2-154 GEN
Solar/Wind Harmer
3.077
276806AD2-047 C O1
Solar/Wind Harmer
11.806
970941AG2-585 GEN
Solar/Wind Harmer
13.795
274800UNIV PARK;3U
Adder
6.433
972038AH1-567 GEN2
Adder
0.403
972228AH1-698 GEN2
Adder
4.086
276897AD1-100 C
Solar/Wind Harmer
31.901
939351AE1-166 GEN
Solar/Wind Harmer
6.518
274676JOLIET 29;8U
Adder
32.446
274729ELWOOD EC;1P
Adder
17.991
274730ELWOOD EC;6P
Adder
17.991
274734ELWOOD EC;8P
Adder
17.991
274736ELWOOD EC;9P
Adder
17.991
276893AG1-478 C
Solar/Wind Harmer
0.457
270535AF1-215 GEN1
Solar/Wind Harmer
4.953
943121AE2-341 GEN
Solar/Wind Harmer
16.349
943591AF1-030 GEN
Solar/Wind Harmer
10.899
276694AA1-018 GEN2
Solar/Wind Harmer
6.801
274682WAUKEGAN ;7U
Adder
19.358
964401AG1-302 GEN
Solar/Wind Harmer
9.749
274872LEEDK;1U
Solar/Wind Harmer
0.273
276805AD2-038 GEN
Solar/Wind Harmer
5.478
276799AD1-013 GEN
Solar/Wind Harmer
2.346
946671AF1-331 GEN
Solar/Wind Harmer
0.444
959141AF2-205 GEN
Solar/Wind Harmer
6.413
274855GSG-6 ;RU
Solar/Wind Harmer
3.917
274850MENDOTA H;RU
Solar/Wind Harmer
2.724
276602WESTBROOK C
Solar/Wind Harmer
2.255
276863AD2-134 GEN
Solar/Wind Harmer
1.894
972236AH1-702 GEN2
Adder
2.303
274760LEE CO EC;1U
Adder
9.662
274767LEE CO EC;8U
Adder
9.549
24721905FLATG4
Adder
19.907
270102X2-052 ST
50/50
1.844
270100X2-052 CT1
50/50
1.699
270101X2-052 CT2
50/50
1.699
247620Y3-023
50/50
0.557
970321AG2-212 GEN
Solar/Wind Harmer
21.268
270216AD2-079_GEN
Solar/Wind Harmer
0.699
270526AF1-158 GEN
Solar/Wind Harmer
5.214
965681AG1-436 GEN
Solar/Wind Harmer
14.336
965791AG1-447 GEN
Solar/Wind Harmer
7.335
24441505OLIV SLR
Solar/Wind Harmer
0.154
957891AF2-083 GEN
Solar/Wind Harmer
3.858
960981AF2-389 GEN
Solar/Wind Harmer
1.729
971411AH1-196 GEN
Solar/Wind Harmer
15.911
971675AH1-338 GEN
Solar/Wind Harmer
19.093
274823ROCKFORD ;21
Adder
20.508
270054AF2-122 C O1
Solar/Wind Helper
1.62
971549AH1-272 GEN
Solar/Wind Harmer
15.966
960751AF2-366 GEN
Solar/Wind Harmer
3.071
962781AG1-127 GEN
Solar/Wind Harmer
10.181
274872LEEDK;1U
Solar/Wind Harmer
8.777
939401AE1-172 GEN
Solar/Wind Harmer
14.891
276901AD2-066 C O1
Solar/Wind Harmer
3.747
971997AH1-543 GEN
Solar/Wind Harmer
16.729
276861AD2-134 GEN
Solar/Wind Harmer
1.894
274822ROCKFORD ;11
Adder
20.658
972235AH1-702 GEN1
Adder
2.648
274761LEE CO EC;2U
Adder
9.662
274766LEE CO EC;7U
Adder
9.549
24721705FLATG2
Adder
19.907
961051AF2-396 GEN
Solar/Wind Harmer
18.061
961051AF2-396 GEN
Solar/Wind Harmer
8.401
274770LINCOLN ;1U
Adder
6.975
274771LINCOLN ;2U
Adder
6.975
970611AG2-400 GEN
Solar/Wind Harmer
11.187
274808UNIV PK N;4U
Adder
5.528
274803UNIV PARK;6U
Adder
6.439
972259AH1-714 GEN
Adder
21.064
274888KELLY CRK;1U
Solar/Wind Harmer
6.515
274887GEN-1.85
Solar/Wind Harmer
5.882
276843GEN-1.7
Solar/Wind Harmer
0.633
958011AF2-095 GEN
Solar/Wind Harmer
15.891
274674JOLIET 9 ;6U
Adder
16.864
274847GR RIDGE ;BU
Solar/Wind Harmer
5.529
971573AH1-285 GEN
Solar/Wind Harmer
9.332
274695ROCKY RD ;2P
Adder
12.008
274693ROCKY RD ;1P
Adder
11.89
274697ROCKY RD ;3P
Adder
3.262
274696ROCKY RD ;4P
Adder
12.291
958481AF2-142 GEN
Solar/Wind Harmer
16.166
274861TOP CROP ;1U
Solar/Wind Harmer
6.528
274862TOP CROP ;2U
Solar/Wind Harmer
5.451
274683WAUKEGAN ;8U
Adder
22.675
274683WAUKEGAN ;8U
Adder
19.114
962691AG1-118 GEN
Solar/Wind Harmer
32.178
970921AG2-575 GEN
Solar/Wind Harmer
10.705
970921AG2-575 GEN
Solar/Wind Harmer
2.49
958491AF2-143 GEN
Solar/Wind Harmer
16.016
942991AE2-321 GEN
Solar/Wind Harmer
10.644
274879MINONK ;1U
Solar/Wind Harmer
7.179
971333AH1-146 GEN
Solar/Wind Harmer
21.203
971335AH1-147 GEN
Solar/Wind Harmer
21.203
274764LEE CO EC;5U
Adder
9.685
274765LEE CO EC;6U
Adder
9.685
274762LEE CO EC;3U
Adder
9.662
274763LEE CO EC;4U
Adder
9.571
972267AH1-718 GEN
Adder
4.292
LAGNLTFEXP_LAGN->PJM
CLTF
11.82
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.928
TVALTFEXP_TVA->PJM
CLTF
5.326
CPLELTFEXP_CPLE->PJM
CLTF
1.469
CBM West 2LTFEXP_CBM-W2->PJM
CBM
91.671
NYPJM->LTFIMP_NY
CLTF
2.826
LGEELTFEXP_LGEE->PJM
CLTF
3.895
WECLTFEXP_WEC->PJM
CLTF
4.009
AG2-052LTFEXP_AG2-052->PJM
LTF
0.249
AH1-155LTFEXP_AH1-155->PJM
LTF
0.373
CBM West 1LTFEXP_CBM-W1->PJM
CBM
131.22
CBM South 1LTFEXP_CBM-S1->PJM
CBM
20.233
MECLTFEXP_MEC->PJM
CLTF
15.452
SIGELTFEXP_SIGE->PJM
CLTF
0.358

Details for 05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line l/o ATSI_P7-1_TE-345-030_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Contingency Name:
ATSI_P7-1_TE-345-030_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:109.86 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5021.72
MW Contribution:15.91
Bus #Bus NameTypeMW Contribution
971599AH1-298 GEN
50/50
11.045
270144AC1-141 ST1_
50/50
2.441
24643105BUCHANAN
50/50
0.015
24653605MOTTVILLE
50/50
0.004
962771AG1-126 GEN
Solar/Wind Harmer
89.195
971347AH1-153 GEN
Solar/Wind Harmer
18.083
270071AF1-092 GEN
Solar/Wind Harmer
17.32
971771AH1-392 GEN
Solar/Wind Harmer
10.364
960681AF2-359 GEN
Solar/Wind Harmer
4.326
971769AH1-391 GEN
Solar/Wind Harmer
11.44
944161AF1-084 GEN
Solar/Wind Harmer
2.493
274775LINCOLN ;6U
Adder
6.965
274776LINCOLN ;7U
Adder
6.965
274777LINCOLN ;8U
Adder
6.965
274814UNIV PK N;0U
Adder
5.593
274807UNIV PK N;3U
Adder
5.581
274805UNIV PK N;1U
Adder
5.557
274811UNIV PK N;7U
Adder
5.544
972037AH1-567 GEN1
Adder
0.202
274827FISK ;RP
Adder
8.556
960591AF2-350 GEN
Solar/Wind Harmer
11.02
972227AH1-698 GEN1
Adder
2.873
274687WILL CNTY;4U
Adder
30.629
274687WILL CNTY;4U
Adder
30.629
274675JOLIET 29;7U
Adder
33.601
274675JOLIET 29;7U
Adder
32.401
274731ELWOOD EC;2P
Adder
17.966
274733ELWOOD EC;3P
Adder
17.966
274735ELWOOD EC;4P
Adder
17.966
274728ELWOOD EC;5P
Adder
17.966
24729505KEY G4
Adder
7.087
970833AG2-524 GEN
Solar/Wind Harmer
9.533
970833AG2-524 GEN
Solar/Wind Harmer
4.434
270536AF1-215 GEN2
Solar/Wind Harmer
4.945
274746AC1-111 G10
Adder
6.074
274744AC1-111 GEN8
Adder
6.074
958391AF2-133 GEN
Solar/Wind Harmer
9.662
971177AH1-047 GEN
Solar/Wind Harmer
6.227
276868AE1-113 GEN
Solar/Wind Harmer
10.752
276882AE2-255 GEN
Solar/Wind Harmer
3.584
971675AH1-338 GEN
Solar/Wind Harmer
19.066
971411AH1-196 GEN
Solar/Wind Harmer
15.889
274823ROCKFORD ;21
Adder
20.48
270054AF2-122 C O1
Solar/Wind Helper
1.619
971549AH1-272 GEN
Solar/Wind Harmer
15.913
24344105CKG2
50/50
9.37
270143AC1-141 CT2_
50/50
2.756
24639705ELKHART HY
50/50
0.186
970521AG2-332 GEN
50/50
13.258
24307105BERRINSP G
50/50
0.025
962761AG1-125 GEN
Solar/Wind Harmer
89.195
970149AG2-104 GEN
Solar/Wind Harmer
110.156
970155AG2-107 GEN
Solar/Wind Harmer
38.893
970245AG2-165 GEN
Solar/Wind Harmer
21.241
270505AE1-170 C O1
Solar/Wind Harmer
17.142
945111AF1-176 GEN
Solar/Wind Harmer
20.324
270063AE2-323 C
Solar/Wind Harmer
2.509
270449AD2-020 GEN
Solar/Wind Harmer
3.177
943021AE2-325 GEN
Solar/Wind Harmer
4.128
972207SS24-0001
Solar/Wind Harmer
24.765
274773LINCOLN ;4U
Adder
6.965
274774LINCOLN ;5U
Adder
6.965
965011AG1-365 GEN
Solar/Wind Harmer
11.176
274723RIVER EC ;12
Adder
19.947
274751CRETE EC ;1U
Adder
5.434
274754CRETE EC ;4U
Adder
5.434
276164X3-005 C
Solar/Wind Harmer
0.78
274812UNIV PK N;8U
Adder
5.544
970373AG2-245 GEN
Solar/Wind Harmer
23.222
276776AD2-060 GEN
Solar/Wind Harmer
0.466
274801UNIV PARK;4U
Adder
6.424
941551AE2-152 GEN
Solar/Wind Harmer
4.979
274676JOLIET 29;8U
Adder
33.6
274674JOLIET 9 ;6U
Adder
16.84
274732ELWOOD EC;7P
Adder
17.966
274871GR RIDGE ;2U
Solar/Wind Harmer
8.394
270055AF2-134 C O1
Solar/Wind Harmer
3.296
274745AC1-111 GEN9
Adder
6.074
276691AA1-018 GEN1
Solar/Wind Harmer
0.501
274682WAUKEGAN ;7U
Adder
19.331
274828WAUKEGAN ;BP
Adder
11.869
958381AF2-132 GEN
Solar/Wind Harmer
9.734
964861AG1-349 GEN
Solar/Wind Harmer
8.422
971917AH1-482 GEN
Solar/Wind Harmer
9.718
960751AF2-366 GEN
Solar/Wind Harmer
3.067
962781AG1-127 GEN
Solar/Wind Harmer
10.166
274872LEEDK;1U
Solar/Wind Harmer
8.765
939401AE1-172 GEN
Solar/Wind Harmer
14.87
276901AD2-066 C O1
Solar/Wind Harmer
3.742
971997AH1-543 GEN
Solar/Wind Harmer
16.706
276861AD2-134 GEN
Solar/Wind Harmer
1.892
274822ROCKFORD ;11
Adder
20.629
972235AH1-702 GEN1
Adder
2.644
274761LEE CO EC;2U
Adder
9.649
274766LEE CO EC;7U
Adder
9.535
24721705FLATG2
Adder
19.906
270102X2-052 ST
50/50
1.841
270100X2-052 CT1
50/50
1.696
270101X2-052 CT2
50/50
1.696
247620Y3-023
50/50
0.556
970321AG2-212 GEN
Solar/Wind Harmer
21.241
270216AD2-079_GEN
Solar/Wind Harmer
0.697
270526AF1-158 GEN
Solar/Wind Harmer
5.205
965681AG1-436 GEN
Solar/Wind Harmer
14.313
965791AG1-447 GEN
Solar/Wind Harmer
7.323
24441505OLIV SLR
Solar/Wind Harmer
0.153
957891AF2-083 GEN
Solar/Wind Harmer
3.85
960981AF2-389 GEN
Solar/Wind Harmer
1.725
961051AF2-396 GEN
Solar/Wind Harmer
18.024
961051AF2-396 GEN
Solar/Wind Harmer
8.383
274770LINCOLN ;1U
Adder
6.965
274771LINCOLN ;2U
Adder
6.965
970611AG2-400 GEN
Solar/Wind Harmer
11.176
274808UNIV PK N;4U
Adder
5.52
274803UNIV PARK;6U
Adder
6.43
972259AH1-714 GEN
Adder
21.035
274888KELLY CRK;1U
Solar/Wind Harmer
6.506
274887GEN-1.85
Solar/Wind Harmer
5.874
276843GEN-1.7
Solar/Wind Harmer
0.632
958011AF2-095 GEN
Solar/Wind Harmer
15.869
274674JOLIET 9 ;6U
Adder
16.84
274847GR RIDGE ;BU
Solar/Wind Harmer
5.521
971573AH1-285 GEN
Solar/Wind Harmer
9.319
274696ROCKY RD ;4P
Adder
12.274
274695ROCKY RD ;2P
Adder
11.991
274693ROCKY RD ;1P
Adder
11.873
274697ROCKY RD ;3P
Adder
3.257
958481AF2-142 GEN
Solar/Wind Harmer
16.143
274861TOP CROP ;1U
Solar/Wind Harmer
6.519
274862TOP CROP ;2U
Solar/Wind Harmer
5.443
274683WAUKEGAN ;8U
Adder
22.643
274683WAUKEGAN ;8U
Adder
19.087
962691AG1-118 GEN
Solar/Wind Harmer
32.133
970921AG2-575 GEN
Solar/Wind Harmer
10.69
970921AG2-575 GEN
Solar/Wind Harmer
2.486
958491AF2-143 GEN
Solar/Wind Harmer
15.994
942991AE2-321 GEN
Solar/Wind Harmer
10.629
274879MINONK ;1U
Solar/Wind Harmer
7.169
971333AH1-146 GEN
Solar/Wind Harmer
21.173
971335AH1-147 GEN
Solar/Wind Harmer
21.173
274764LEE CO EC;5U
Adder
9.672
274765LEE CO EC;6U
Adder
9.672
274762LEE CO EC;3U
Adder
9.649
274763LEE CO EC;4U
Adder
9.558
972267AH1-718 GEN
Adder
4.286
270142AC1-141 CT1_
50/50
2.756
24344005CKG1
50/50
7.52
24641605TWIN BRNCH
50/50
0.02
24642205MAYFLWER
50/50
0.771
944961AF1-161 GEN
50/50
3.295
962601AG1-109 GEN
50/50
3.295
970153AG2-106 GEN
Solar/Wind Harmer
38.893
970349AG2-230 GEN
Solar/Wind Harmer
18.083
970513AG2-328 GEN
Solar/Wind Harmer
21.241
970517AG2-330 GEN
Solar/Wind Harmer
19.266
270043AE2-236 GEN
Solar/Wind Harmer
6.503
247643Z2-116 C
Solar/Wind Harmer
0.08
945111AF1-176 GEN
Solar/Wind Harmer
6.441
970031AG2-029 GEN
Solar/Wind Harmer
33.933
274772LINCOLN ;3U
Adder
6.965
959331AF2-224 GEN
Solar/Wind Harmer
11.176
965021AG1-366 GEN
Solar/Wind Harmer
2.599
24441205WTRV SLR C
Solar/Wind Harmer
0.151
274724RIVER EC ;11
Adder
19.717
944531AF1-118 GEN
Solar/Wind Harmer
38.966
972231SS25-0005
Solar/Wind Harmer
10.551
972181SS23-001
Solar/Wind Harmer
6.594
274752CRETE EC ;2U
Adder
5.434
274753CRETE EC ;3U
Adder
5.434
247604X1-042
Adder
0.461
970707AG2-453 GEN
Solar/Wind Harmer
30.974
274802UNIV PARK;5U
Adder
6.43
274826FISK ;BP
Adder
12.073
276772AC2-154 GEN
Solar/Wind Harmer
3.073
276806AD2-047 C O1
Solar/Wind Harmer
11.789
970941AG2-585 GEN
Solar/Wind Harmer
13.775
274800UNIV PARK;3U
Adder
6.424
972038AH1-567 GEN2
Adder
0.402
972228AH1-698 GEN2
Adder
4.08
276897AD1-100 C
Solar/Wind Harmer
31.856
939351AE1-166 GEN
Solar/Wind Harmer
6.509
274676JOLIET 29;8U
Adder
32.4
274729ELWOOD EC;1P
Adder
17.966
274730ELWOOD EC;6P
Adder
17.966
274734ELWOOD EC;8P
Adder
17.966
274736ELWOOD EC;9P
Adder
17.966
276893AG1-478 C
Solar/Wind Harmer
0.456
270535AF1-215 GEN1
Solar/Wind Harmer
4.945
943121AE2-341 GEN
Solar/Wind Harmer
16.326
943591AF1-030 GEN
Solar/Wind Harmer
10.884
276694AA1-018 GEN2
Solar/Wind Harmer
6.792
274682WAUKEGAN ;7U
Adder
19.331
964401AG1-302 GEN
Solar/Wind Harmer
9.734
274872LEEDK;1U
Solar/Wind Harmer
0.273
276805AD2-038 GEN
Solar/Wind Harmer
5.47
276799AD1-013 GEN
Solar/Wind Harmer
2.342
946671AF1-331 GEN
Solar/Wind Harmer
0.444
959141AF2-205 GEN
Solar/Wind Harmer
6.404
274855GSG-6 ;RU
Solar/Wind Harmer
3.911
274850MENDOTA H;RU
Solar/Wind Harmer
2.72
276602WESTBROOK C
Solar/Wind Harmer
2.251
276863AD2-134 GEN
Solar/Wind Harmer
1.892
972236AH1-702 GEN2
Adder
2.3
274760LEE CO EC;1U
Adder
9.649
274767LEE CO EC;8U
Adder
9.535
24721905FLATG4
Adder
19.906
LAGNLTFEXP_LAGN->PJM
CLTF
11.806
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.918
TVALTFEXP_TVA->PJM
CLTF
5.319
CPLELTFEXP_CPLE->PJM
CLTF
1.466
CBM West 2LTFEXP_CBM-W2->PJM
CBM
91.557
NYPJM->LTFIMP_NY
CLTF
2.828
LGEELTFEXP_LGEE->PJM
CLTF
3.891
WECLTFEXP_WEC->PJM
CLTF
4.003
AG2-052LTFEXP_AG2-052->PJM
LTF
0.249
AH1-155LTFEXP_AH1-155->PJM
LTF
0.373
CBM West 1LTFEXP_CBM-W1->PJM
CBM
130.734
CBM South 1LTFEXP_CBM-S1->PJM
CBM
20.209
MECLTFEXP_MEC->PJM
CLTF
15.431
SIGELTFEXP_SIGE->PJM
CLTF
0.358

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#709_546_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:145.65 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:6032.93
MW Contribution:26.67
Bus #Bus NameTypeMW Contribution
24344005CKG1
50/50
13.628
270142AC1-141 CT1_
50/50
4.979
24641605TWIN BRNCH
50/50
0.036
24642205MAYFLWER
50/50
1.39
274772LINCOLN ;3U
50/50
18.26
970513AG2-328 GEN
Solar/Wind Harmer
6.717
970517AG2-330 GEN
Solar/Wind Harmer
40.303
970349AG2-230 GEN
Solar/Wind Harmer
23.209
270043AE2-236 GEN
Solar/Wind Harmer
9.37
247643Z2-116 C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
11.566
274724RIVER EC ;11
Adder
35.644
274752CRETE EC ;2U
Adder
16.552
274753CRETE EC ;3U
Adder
16.552
24441205WTRV SLR C
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
45.547
274802UNIV PARK;5U
Adder
11.601
274826FISK ;BP
Adder
21.78
276806AD2-047 C O1
Solar/Wind Harmer
7.862
970941AG2-585 GEN
Solar/Wind Harmer
17.342
972228AH1-698 GEN2
Adder
7.363
274800UNIV PARK;3U
Adder
11.588
972038AH1-567 GEN2
Adder
0.725
276897AD1-100 C
Solar/Wind Harmer
0.018
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
247604X1-042
Adder
0.825
270535AF1-215 GEN1
Solar/Wind Harmer
0.017
274676JOLIET 29;8U
Adder
58.35
970031AG2-029 GEN
Solar/Wind Harmer
8.936
274729ELWOOD EC;1P
Adder
32.348
274730ELWOOD EC;6P
Adder
32.348
274734ELWOOD EC;8P
Adder
32.348
274736ELWOOD EC;9P
Adder
32.348
276893AG1-478 C
Solar/Wind Harmer
0.544
944531AF1-118 GEN
Solar/Wind Harmer
61.488
943121AE2-341 GEN
Solar/Wind Harmer
22.888
943591AF1-030 GEN
Solar/Wind Harmer
15.221
964401AG1-302 GEN
Solar/Wind Harmer
0.002
276694AA1-018 GEN2
Solar/Wind Harmer
0.002
274682WAUKEGAN ;7U
Adder
34.62
959141AF2-205 GEN
Solar/Wind Harmer
-0.003
276805AD2-038 GEN
Solar/Wind Harmer
0.004
274872LEEDK;1U
Solar/Wind Harmer
0.488
276799AD1-013 GEN
Solar/Wind Harmer
0.003
946671AF1-331 GEN
Solar/Wind Harmer
1.406
274855GSG-6 ;RU
Solar/Wind Harmer
0.483
274850MENDOTA H;RU
Solar/Wind Harmer
0.155
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.236
959091AF2-200 GEN
Solar/Wind Harmer
26.172
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
4.086
970571AG2-364 GEN
Solar/Wind Harmer
25.867
274858EASY ROAD;U2
Solar/Wind Harmer
0.003
274760LEE CO EC;1U
Adder
17.083
274767LEE CO EC;8U
Adder
16.882
24755605MDL-5G
Solar/Wind Harmer
0.002
970781AG2-491 GEN
Solar/Wind Harmer
12.802
959331AF2-224 GEN
Solar/Wind Harmer
8.908
965021AG1-366 GEN
Solar/Wind Harmer
4.242
276157O29GEN1
Solar/Wind Harmer
2.046
274878BISHOP HL;2U
Solar/Wind Harmer
0.423
942111AE2-223 GEN
Solar/Wind Harmer
4.067
274853TWINGROVE;U1
Solar/Wind Harmer
0.005
965091AG1-374 GEN
Solar/Wind Harmer
36.906
959611AF2-252 GEN
Solar/Wind Harmer
4.101
965931AG1-462 GEN
Solar/Wind Harmer
31.198
247642Z2-115 C
Solar/Wind Harmer
0.005
276686W4-005 GEN3
Solar/Wind Harmer
0.002
971993AH1-541 GEN
Solar/Wind Harmer
5.377
276668AB2-070 GEN1
Solar/Wind Harmer
0.424
276621W2-048 GEN
Solar/Wind Harmer
0.577
276838X2-022 GEN2
Solar/Wind Harmer
0.644
970289AG2-191 GEN
Solar/Wind Harmer
1.253
970291AG2-192 GEN
Solar/Wind Harmer
1.139
942481AE2-261 GEN
Solar/Wind Harmer
33.028
970243AG2-164 GEN
Solar/Wind Harmer
6.289
970519AG2-331 GEN
Solar/Wind Harmer
27.951
970699AG2-449 GEN
Solar/Wind Harmer
2.688
970193AG2-126 GEN
Solar/Wind Harmer
15.928
971599AH1-298 GEN
50/50
19.983
270144AC1-141 ST1_
50/50
4.41
24643105BUCHANAN
50/50
0.026
274775LINCOLN ;6U
50/50
18.26
274776LINCOLN ;7U
50/50
18.26
274777LINCOLN ;8U
50/50
18.26
24653605MOTTVILLE
50/50
0.008
971347AH1-153 GEN
Solar/Wind Harmer
23.209
960681AF2-359 GEN
Solar/Wind Harmer
-0.002
971771AH1-392 GEN
Solar/Wind Harmer
14.529
971769AH1-391 GEN
Solar/Wind Harmer
16.154
971619AH1-309 GEN
Solar/Wind Harmer
6.462
270071AF1-092 GEN
Solar/Wind Harmer
27.514
274814UNIV PK N;0U
Adder
10.098
274807UNIV PK N;3U
Adder
10.076
274805UNIV PK N;1U
Adder
10.033
274811UNIV PK N;7U
Adder
10.011
972037AH1-567 GEN1
Adder
0.364
274827FISK ;RP
Adder
15.436
960591AF2-350 GEN
Solar/Wind Harmer
13.873
972227AH1-698 GEN1
Adder
5.185
270536AF1-215 GEN2
Solar/Wind Harmer
0.017
274687WILL CNTY;4U
Adder
55.173
274687WILL CNTY;4U
Adder
55.173
274675JOLIET 29;7U
Adder
60.513
274675JOLIET 29;7U
Adder
58.351
274731ELWOOD EC;2P
Adder
32.348
274733ELWOOD EC;3P
Adder
32.348
274735ELWOOD EC;4P
Adder
32.348
274728ELWOOD EC;5P
Adder
32.348
970833AG2-524 GEN
Solar/Wind Harmer
15.09
970833AG2-524 GEN
Solar/Wind Harmer
10.06
274746AC1-111 G10
Adder
10.916
274744AC1-111 GEN8
Adder
10.916
958391AF2-133 GEN
Solar/Wind Harmer
0.002
24729505KEY G4
Adder
12.474
971611AH1-305 GEN
Solar/Wind Harmer
7.91
276868AE1-113 GEN
Solar/Wind Harmer
2.657
276882AE2-255 GEN
Solar/Wind Harmer
1.548
971177AH1-047 GEN
Solar/Wind Harmer
8.156
971675AH1-338 GEN
Solar/Wind Harmer
5.138
971411AH1-196 GEN
Solar/Wind Harmer
19.757
274863CRW1-WTG
Solar/Wind Harmer
0.004
274864CRW2-WTG
Solar/Wind Harmer
0.004
971171AH1-044 GEN
Solar/Wind Harmer
26.172
274823ROCKFORD ;21
Adder
36.411
970169AG2-114 GEN
Solar/Wind Harmer
12.957
276612AE2-035 GEN
Solar/Wind Harmer
0.003
926823AC1-168 GEN
Solar/Wind Harmer
2.2
971549AH1-272 GEN
Solar/Wind Harmer
26.668
971681AH1-341 GEN
Solar/Wind Harmer
20.716
24690905MDL-1G C
Solar/Wind Harmer
0.004
270180AB1-006 GEN1
Solar/Wind Harmer
0.003
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.003
24697605MDL-3G C
Solar/Wind Harmer
0.003
24697905MDL-4G C
Solar/Wind Harmer
0.002
270181AB1-006 GEN2
Solar/Wind Harmer
0
961011AF2-392 GEN
Solar/Wind Harmer
7.462
957751AF2-069 GEN
Solar/Wind Harmer
0.418
274848CAMPGROVE;RU
Solar/Wind Harmer
0.002
276655WTG1_EQ
Solar/Wind Harmer
0.005
276656WTG2_EQ
Solar/Wind Harmer
0.001
959341AF2-225 GEN
Solar/Wind Harmer
13.14
941731AE2-173 GEN
Solar/Wind Harmer
10.429
24386205FR-12G C
Solar/Wind Harmer
0.002
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.002
946321AF1-296 GEN
Solar/Wind Harmer
6.891
965101AG1-375 GEN
Solar/Wind Harmer
12.296
963841AG1-237 GEN
Solar/Wind Harmer
5.208
945581AF1-223 GEN
Solar/Wind Harmer
0.001
276785W4-005 GEN1
Solar/Wind Harmer
0.002
276174W4-005 GEN2
Solar/Wind Harmer
0.002
276849AB2-070 GEN2
Solar/Wind Harmer
0.424
276848AB2-070 GEN3
Solar/Wind Harmer
0.422
963791AG1-232 GEN
Solar/Wind Harmer
15.504
970289AG2-191 GEN
Solar/Wind Harmer
2.164
270594AE1-207 GEN
Solar/Wind Harmer
12.434
971609AH1-304 GEN
Solar/Wind Harmer
1.81
965041AG1-368 GEN
Solar/Wind Harmer
11.055
944221AF1-090 GEN
Solar/Wind Harmer
6.244
24725505WLD G2 C
Solar/Wind Harmer
0.002
24699105WLD G1 C
Solar/Wind Harmer
0.002
970115AG2-085 GEN
Solar/Wind Harmer
4.131
270024AE2-089 GEN
Solar/Wind Harmer
0.011
965051AG1-369 GEN
Solar/Wind Harmer
5.072
270240V3-007_GEN2
Solar/Wind Harmer
0.003
270543AE2-219 C
Solar/Wind Harmer
0.005
247607V1-011 GEN
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
1.018
971029AG2-637 GEN
Solar/Wind Harmer
11.658
971673AH1-337 GEN
Solar/Wind Harmer
4.919
24344105CKG2
50/50
17.41
270143AC1-141 CT2_
50/50
4.979
24639705ELKHART HY
50/50
0.333
274773LINCOLN ;4U
50/50
18.26
274774LINCOLN ;5U
50/50
18.26
970521AG2-332 GEN
50/50
23.674
970245AG2-165 GEN
Solar/Wind Harmer
6.717
270505AE1-170 C O1
Solar/Wind Harmer
15.077
945111AF1-176 GEN
Solar/Wind Harmer
25.462
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
7.414
274723RIVER EC ;12
Adder
36.059
970373AG2-245 GEN
Solar/Wind Harmer
29.431
274751CRETE EC ;1U
Adder
16.552
274754CRETE EC ;4U
Adder
16.552
276164X3-005 C
Solar/Wind Harmer
0
270063AE2-323 C
Solar/Wind Harmer
0.011
274812UNIV PK N;8U
Adder
10.011
276776AD2-060 GEN
Solar/Wind Harmer
1.448
274801UNIV PARK;4U
Adder
11.588
941551AE2-152 GEN
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0.011
274676JOLIET 29;8U
Adder
60.512
274674JOLIET 9 ;6U
Adder
30.323
274732ELWOOD EC;7P
Adder
32.348
274871GR RIDGE ;2U
Solar/Wind Harmer
0.002
274745AC1-111 GEN9
Adder
10.916
958381AF2-132 GEN
Solar/Wind Harmer
0.002
964861AG1-349 GEN
Solar/Wind Harmer
-0.002
971917AH1-482 GEN
Solar/Wind Harmer
17.617
276691AA1-018 GEN1
Solar/Wind Harmer
1.631
274682WAUKEGAN ;7U
Adder
34.62
274828WAUKEGAN ;BP
Adder
21.25
939401AE1-172 GEN
Solar/Wind Harmer
9.985
962781AG1-127 GEN
Solar/Wind Harmer
12.689
274872LEEDK;1U
Solar/Wind Harmer
0.008
940581AE2-045 GEN
Solar/Wind Harmer
-0.003
971605AH1-302 GEN
Solar/Wind Harmer
16.609
276901AD2-066 C O1
Solar/Wind Harmer
0.013
971997AH1-543 GEN
Solar/Wind Harmer
6.942
276861AD2-134 GEN
Solar/Wind Harmer
0.236
957471AF2-041 GEN
Solar/Wind Harmer
39.258
959081AF2-199 GEN
Solar/Wind Harmer
13.086
971067AG2-660 GEN
Solar/Wind Harmer
4.362
276876AE1-163_GEN2
Solar/Wind Harmer
0.003
274822ROCKFORD ;11
Adder
36.677
972235AH1-702 GEN1
Adder
4.699
970819AG2-516 GEN
Solar/Wind Harmer
15.555
970569AG2-363 GEN
Solar/Wind Harmer
38.8
971475AH1-234 GEN
Solar/Wind Harmer
6.272
274857EASY ROAD;U1
Solar/Wind Harmer
0.003
274761LEE CO EC;2U
Adder
17.083
274766LEE CO EC;7U
Adder
16.882
24791305MDL-5G
Solar/Wind Harmer
0.002
965011AG1-365 GEN
Solar/Wind Harmer
12.726
276158O29GEN2
Solar/Wind Harmer
0.001
274877BISHOP HL;1U
Solar/Wind Harmer
0.423
965651AG1-433 GEN
Solar/Wind Harmer
3.688
276726Z2-087_GEN
Solar/Wind Harmer
0.004
939741AE1-205 GEN
Solar/Wind Harmer
17.52
24385905FR-11G C
Solar/Wind Harmer
0.003
24387305FR-4G C
Solar/Wind Harmer
0.005
274854TWINGROVE;U2
Solar/Wind Harmer
0.005
958861AF2-177 GEN
Solar/Wind Harmer
5.328
972175AH1-670 GEN
Solar/Wind Harmer
9.878
945371AF1-202 GEN
Solar/Wind Harmer
0.001
963741AG1-226 GEN
Solar/Wind Harmer
27.693
274880W4-005 GEN4
Solar/Wind Harmer
0.002
963831AG1-236 GEN
Solar/Wind Harmer
4.513
276615X2-022 GEN
Solar/Wind Harmer
0.12
944231AF1-091 GEN
Solar/Wind Harmer
3.041
970291AG2-192 GEN
Solar/Wind Harmer
1.481
270032AE2-172
Solar/Wind Harmer
7.401
965911AG1-460 GEN
Solar/Wind Harmer
2.209
276903AD2-071 C
Solar/Wind Harmer
12.04
970333AG2-219 GEN
Solar/Wind Harmer
7.687
270005AE1-210 C O1
Solar/Wind Harmer
2.283
965031AG1-367 GEN
Solar/Wind Harmer
10.536
970825AG2-519 GEN
Solar/Wind Harmer
3.643
247521TR3_G114
Solar/Wind Harmer
0.37
270246TR4_N_V150
Solar/Wind Harmer
0.066
24695305TIMB G C
Solar/Wind Harmer
0.003
270445AC2-157 GEN2
Solar/Wind Harmer
0.004
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0.001
970613AG2-401 GEN
Solar/Wind Harmer
7.029
247536S-71 GEN
Solar/Wind Harmer
0.355
965421AG1-410 GEN
Solar/Wind Harmer
25.459
970773AG2-487 GEN
Solar/Wind Harmer
1.469
246936BC-WTG1
Solar/Wind Harmer
0.326
270489AE1-102 GEN1
Solar/Wind Harmer
1.045
270349AD2-093_GEN
Solar/Wind Helper
1.548
270102X2-052 ST
50/50
3.353
270100X2-052 CT1
50/50
3.09
270101X2-052 CT2
50/50
3.09
274770LINCOLN ;1U
50/50
18.26
274771LINCOLN ;2U
50/50
18.26
970321AG2-212 GEN
Solar/Wind Harmer
6.717
965681AG1-436 GEN
Solar/Wind Harmer
18.169
965791AG1-447 GEN
Solar/Wind Harmer
13.324
270526AF1-158 GEN
Solar/Wind Harmer
0.018
24441505OLIV SLR
Solar/Wind Harmer
0
270216AD2-079_GEN
Solar/Wind Harmer
0.002
957891AF2-083 GEN
Solar/Wind Harmer
0.002
961051AF2-396 GEN
Solar/Wind Harmer
28.457
961051AF2-396 GEN
Solar/Wind Harmer
18.971
247620Y3-023
Adder
0.932
274808UNIV PK N;4U
Adder
9.967
972259AH1-714 GEN
Adder
37.97
274803UNIV PARK;6U
Adder
11.601
274888KELLY CRK;1U
Solar/Wind Harmer
0.815
274887GEN-1.85
Solar/Wind Harmer
0.365
276843GEN-1.7
Solar/Wind Harmer
0.449
958011AF2-095 GEN
Solar/Wind Harmer
19.978
274674JOLIET 9 ;6U
Adder
30.323
274847GR RIDGE ;BU
Solar/Wind Harmer
0.005
971573AH1-285 GEN
Solar/Wind Harmer
2.529
274695ROCKY RD ;2P
Adder
21.486
274693ROCKY RD ;1P
Adder
21.275
274697ROCKY RD ;3P
Adder
5.837
274696ROCKY RD ;4P
Adder
21.993
958481AF2-142 GEN
Solar/Wind Harmer
20.192
274861TOP CROP ;1U
Solar/Wind Harmer
0.004
274862TOP CROP ;2U
Solar/Wind Harmer
1.82
274683WAUKEGAN ;8U
Adder
40.539
274683WAUKEGAN ;8U
Adder
34.173
962691AG1-118 GEN
Solar/Wind Harmer
40.102
970921AG2-575 GEN
Solar/Wind Harmer
13.333
970921AG2-575 GEN
Solar/Wind Harmer
4.444
958491AF2-143 GEN
Solar/Wind Harmer
19.955
274879MINONK ;1U
Solar/Wind Harmer
0.559
942991AE2-321 GEN
Solar/Wind Harmer
14.775
971333AH1-146 GEN
Solar/Wind Harmer
26.325
971335AH1-147 GEN
Solar/Wind Harmer
26.325
971341AH1-150 GEN
Solar/Wind Harmer
26.172
971343AH1-151 GEN
Solar/Wind Harmer
26.172
276872AE1-163_GEN1
Solar/Wind Harmer
0.003
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.003
274856ECOGROVE ;U1
Solar/Wind Harmer
0.305
276611AD2-172 GEN
Solar/Wind Harmer
0.003
938861AE1-114 GEN
Solar/Wind Harmer
7.288
274764LEE CO EC;5U
Adder
17.123
274765LEE CO EC;6U
Adder
17.123
274762LEE CO EC;3U
Adder
17.083
274763LEE CO EC;4U
Adder
16.922
276603SUBLETTE C
Solar/Wind Harmer
0
970611AG2-400 GEN
Solar/Wind Harmer
12.726
970627AG2-408 GEN
Solar/Wind Harmer
3.818
972267AH1-718 GEN
Adder
7.569
276741O09 GEN1
Solar/Wind Harmer
0.451
276708O09 GEN2
Solar/Wind Harmer
0.451
274851PROVIDENC;RU
Solar/Wind Harmer
0.002
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.497
276646AC1-214 GEN2
Solar/Wind Harmer
0.497
276782AC1-033 GEN
Solar/Wind Harmer
0.002
944541AF1-119 GEN
Solar/Wind Harmer
0.842
960971AF2-388 GEN
Solar/Wind Harmer
7.376
966841AG1-555 GEN
Solar/Wind Harmer
1.399
960611AF2-352 GEN
Solar/Wind Harmer
4.101
970241AG2-163 GEN
Solar/Wind Harmer
6.826
942221AE2-234 GEN
Solar/Wind Harmer
0.059
276763AC1-053 GEN1
Solar/Wind Harmer
0.002
276764AC1-053 GEN2
Solar/Wind Harmer
0.002
971613AH1-306 GEN
Solar/Wind Harmer
5.329
270599AE1-208 GEN
Solar/Wind Harmer
10.158
270031AE2-169
Solar/Wind Harmer
6.095
276916AD2-100_GEN
Solar/Wind Harmer
23.006
276911AD2-131_GEN
Solar/Wind Harmer
1.515
970239AG2-162 GEN
Solar/Wind Harmer
2.688
945391AF1-204 GEN
Solar/Wind Harmer
11.282
960441AF2-335 GEN
Solar/Wind Harmer
10.327
970825AG2-519 GEN
Solar/Wind Harmer
11.373
270444AC2-157 GEN1
Solar/Wind Harmer
0.004
971587AH1-292 GEN
Solar/Wind Harmer
7.189
24379505HDWTR1G C
Solar/Wind Harmer
0.003
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
0.716
270201AC2-176 GEN
Solar/Wind Harmer
0.002
270383AD1-128 GEN
Solar/Wind Harmer
0.005
970623AG2-406 GEN
Solar/Wind Harmer
1.6
970883AG2-550 GEN
Solar/Wind Harmer
8.324
970885AG2-551 GEN
Solar/Wind Harmer
2.775
270007AE1-245 C
Solar/Wind Harmer
0.002
246938BC-WTG3
Solar/Wind Harmer
0.291
246937BC-WTG2
Solar/Wind Harmer
0.326
270471AD2-092_GEN
Solar/Wind Helper
1.548
958821AF2-173 GEN
Solar/Wind Harmer
14.751
270004AE1-209 GEN
Solar/Wind Harmer
2.283
971617AH1-308 GEN
Solar/Wind Harmer
8.548
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.066
946031AF1-268 GEN
Solar/Wind Harmer
9.517
270437AC2-090 C
Solar/Wind Harmer
0.004
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
14.144
270404AC1-167 GEN
Solar/Wind Harmer
0.004
270258AD1-119 GEN
Solar/Wind Harmer
0.002
270356AE2-297 GEN
Solar/Wind Harmer
0.011
270491AE1-102 GEN2
Solar/Wind Harmer
1.045
944201AF1-088_MTX
Adder
163.382
957141AF2-008_MTX
Adder
69.441
LAGNLTFEXP_LAGN->PJM
CLTF
14.15
TVALTFEXP_TVA->PJM
CLTF
5.408
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.138
NYPJM->LTFIMP_NY
CLTF
3.386
LGEELTFEXP_LGEE->PJM
CLTF
5.588
WECLTFEXP_WEC->PJM
CLTF
7.104
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.19
AG2-052LTFEXP_AG2-052->PJM
LTF
0.447
AH1-155LTFEXP_AH1-155->PJM
LTF
0.671
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.516
CBM West 1LTFEXP_CBM-W1->PJM
CBM
217.631
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.154
MECLTFEXP_MEC->PJM
CLTF
26.031
SIGELTFEXP_SIGE->PJM
CLTF
0.551

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P4_#2995_05E LIMA 345_M_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#2995_05E LIMA 345_M_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:145.3 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:6018.36
MW Contribution:32.93
Bus #Bus NameTypeMW Contribution
971599AH1-298 GEN
50/50
20.529
24727205RPMNG3
50/50
2.029
270144AC1-141 ST1_
50/50
4.29
24653605MOTTVILLE
50/50
0.008
24643105BUCHANAN
50/50
0.025
957201AF2-014 GEN
Solar/Wind Harmer
9.733
270435AC2-044 GEN
Solar/Wind Harmer
4.292
971347AH1-153 GEN
Solar/Wind Harmer
32.134
270071AF1-092 GEN
Solar/Wind Harmer
31.087
971771AH1-392 GEN
Solar/Wind Harmer
18.192
971769AH1-391 GEN
Solar/Wind Harmer
19.979
960681AF2-359 GEN
Solar/Wind Harmer
7.542
944161AF1-084 GEN
Solar/Wind Harmer
4.339
274775LINCOLN ;6U
Adder
12.031
274776LINCOLN ;7U
Adder
12.031
274777LINCOLN ;8U
Adder
12.031
24729505KEY G4
Adder
12.581
274814UNIV PK N;0U
Adder
9.617
274807UNIV PK N;3U
Adder
9.597
274805UNIV PK N;1U
Adder
9.555
274811UNIV PK N;7U
Adder
9.534
972037AH1-567 GEN1
Adder
0.346
274827FISK ;RP
Adder
14.684
960591AF2-350 GEN
Solar/Wind Harmer
18.903
972227AH1-698 GEN1
Adder
4.926
274687WILL CNTY;4U
Adder
52.424
274687WILL CNTY;4U
Adder
52.424
274675JOLIET 29;7U
Adder
57.484
274675JOLIET 29;7U
Adder
55.431
274728ELWOOD EC;5P
Adder
30.711
274731ELWOOD EC;2P
Adder
30.71
274733ELWOOD EC;3P
Adder
30.71
274735ELWOOD EC;4P
Adder
30.71
970833AG2-524 GEN
Solar/Wind Harmer
16.286
970833AG2-524 GEN
Solar/Wind Harmer
7.575
270536AF1-215 GEN2
Solar/Wind Harmer
8.428
274746AC1-111 G10
Adder
10.357
274744AC1-111 GEN8
Adder
10.357
958711AF2-162 GEN
Solar/Wind Harmer
1.82
958391AF2-133 GEN
Solar/Wind Harmer
16.304
971177AH1-047 GEN
Solar/Wind Harmer
10.518
24344105CKG2
50/50
16.752
24727005RPMNG1
50/50
2.039
270143AC1-141 CT2_
50/50
4.843
24639705ELKHART HY
50/50
0.328
970521AG2-332 GEN
50/50
23.389
24307105BERRINSP G
50/50
0.043
965011AG1-365 GEN
Solar/Wind Harmer
21.485
965421AG1-410 GEN
Solar/Wind Harmer
64.386
246936BC-WTG1
Solar/Wind Harmer
8.398
270489AE1-102 GEN1
Solar/Wind Harmer
2.79
970245AG2-165 GEN
Solar/Wind Harmer
37.203
270063AE2-323 C
Solar/Wind Harmer
4.466
270505AE1-170 C O1
Solar/Wind Harmer
30.011
945111AF1-176 GEN
Solar/Wind Harmer
35.611
270449AD2-020 GEN
Solar/Wind Harmer
5.542
943021AE2-325 GEN
Solar/Wind Harmer
7.201
972207SS24-0001
Solar/Wind Harmer
42.777
274773LINCOLN ;4U
Adder
12.031
274774LINCOLN ;5U
Adder
12.031
274723RIVER EC ;12
Adder
34.382
274751CRETE EC ;1U
Adder
9.363
274754CRETE EC ;4U
Adder
9.363
276164X3-005 C
Solar/Wind Harmer
1.342
274812UNIV PK N;8U
Adder
9.534
970373AG2-245 GEN
Solar/Wind Harmer
39.866
276776AD2-060 GEN
Solar/Wind Harmer
0.799
274801UNIV PARK;4U
Adder
11.02
941551AE2-152 GEN
Solar/Wind Harmer
8.523
274676JOLIET 29;8U
Adder
57.483
274674JOLIET 9 ;6U
Adder
28.794
274732ELWOOD EC;7P
Adder
30.711
274871GR RIDGE ;2U
Solar/Wind Harmer
14.337
270055AF2-134 C O1
Solar/Wind Harmer
5.618
274745AC1-111 GEN9
Adder
10.357
276691AA1-018 GEN1
Solar/Wind Harmer
0.851
274682WAUKEGAN ;7U
Adder
32.824
274828WAUKEGAN ;BP
Adder
20.145
958381AF2-132 GEN
Solar/Wind Harmer
16.482
964861AG1-349 GEN
Solar/Wind Harmer
14.25
971917AH1-482 GEN
Solar/Wind Harmer
16.444
960751AF2-366 GEN
Solar/Wind Harmer
5.194
962781AG1-127 GEN
Solar/Wind Harmer
17.216
274872LEEDK;1U
Solar/Wind Harmer
14.832
939401AE1-172 GEN
Solar/Wind Harmer
25.153
276901AD2-066 C O1
Solar/Wind Harmer
6.326
965651AG1-433 GEN
Solar/Wind Harmer
9.83
971997AH1-543 GEN
Solar/Wind Harmer
28.2
276861AD2-134 GEN
Solar/Wind Harmer
3.19
274822ROCKFORD ;11
Adder
34.687
972235AH1-702 GEN1
Adder
4.443
274761LEE CO EC;2U
Adder
16.13
274766LEE CO EC;7U
Adder
15.94
24728605AND G2
Adder
4.583
270349AD2-093_GEN
Solar/Wind Helper
1.743
957471AF2-041 GEN
Solar/Wind Harmer
19.968
970615AG2-402 GEN
50/50
4.996
270102X2-052 ST
50/50
3.216
270100X2-052 CT1
50/50
2.963
270101X2-052 CT2
50/50
2.963
247620Y3-023
50/50
0.981
970611AG2-400 GEN
Solar/Wind Harmer
21.485
246938BC-WTG3
Solar/Wind Harmer
8.542
246937BC-WTG2
Solar/Wind Harmer
8.398
970321AG2-212 GEN
Solar/Wind Harmer
37.203
270216AD2-079_GEN
Solar/Wind Harmer
1.229
270526AF1-158 GEN
Solar/Wind Harmer
9.099
957891AF2-083 GEN
Solar/Wind Harmer
6.742
960981AF2-389 GEN
Solar/Wind Harmer
3.021
24441505OLIV SLR
Solar/Wind Harmer
0.268
965681AG1-436 GEN
Solar/Wind Harmer
24.955
965791AG1-447 GEN
Solar/Wind Harmer
12.768
961051AF2-396 GEN
Solar/Wind Harmer
31.495
961051AF2-396 GEN
Solar/Wind Harmer
14.649
274770LINCOLN ;1U
Adder
12.031
274771LINCOLN ;2U
Adder
12.031
274808UNIV PK N;4U
Adder
9.492
274803UNIV PARK;6U
Adder
11.035
972259AH1-714 GEN
Adder
36.075
274888KELLY CRK;1U
Solar/Wind Harmer
11.16
274887GEN-1.85
Solar/Wind Harmer
10.076
276843GEN-1.7
Solar/Wind Harmer
1.084
958011AF2-095 GEN
Solar/Wind Harmer
27.22
274674JOLIET 9 ;6U
Adder
28.794
274847GR RIDGE ;BU
Solar/Wind Harmer
9.431
971573AH1-285 GEN
Solar/Wind Harmer
15.868
274695ROCKY RD ;2P
Adder
20.37
274693ROCKY RD ;1P
Adder
20.17
274697ROCKY RD ;3P
Adder
5.534
274696ROCKY RD ;4P
Adder
20.85
958481AF2-142 GEN
Solar/Wind Harmer
27.421
274861TOP CROP ;1U
Solar/Wind Harmer
11.071
274862TOP CROP ;2U
Solar/Wind Harmer
9.244
274683WAUKEGAN ;8U
Adder
38.432
274683WAUKEGAN ;8U
Adder
32.396
962691AG1-118 GEN
Solar/Wind Harmer
54.457
970921AG2-575 GEN
Solar/Wind Harmer
18.103
970921AG2-575 GEN
Solar/Wind Harmer
4.21
958491AF2-143 GEN
Solar/Wind Harmer
27.059
944541AF1-119 GEN
Solar/Wind Harmer
7.534
960971AF2-388 GEN
Solar/Wind Harmer
19.66
24727105RPMNG2
50/50
2.046
965431AG1-411 GEN
50/50
24.956
24641605TWIN BRNCH
50/50
0.035
270142AC1-141 CT1_
50/50
4.843
24344005CKG1
50/50
13.154
24642205MAYFLWER
50/50
1.348
944961AF1-161 GEN
50/50
5.748
962601AG1-109 GEN
50/50
5.748
270043AE2-236 GEN
Solar/Wind Harmer
11.825
959331AF2-224 GEN
Solar/Wind Harmer
21.485
965021AG1-366 GEN
Solar/Wind Harmer
4.996
270491AE1-102 GEN2
Solar/Wind Harmer
2.79
970349AG2-230 GEN
Solar/Wind Harmer
32.134
970513AG2-328 GEN
Solar/Wind Harmer
37.203
970517AG2-330 GEN
Solar/Wind Harmer
33.742
970031AG2-029 GEN
Solar/Wind Harmer
61.231
247643Z2-116 C
Solar/Wind Harmer
0.141
945111AF1-176 GEN
Solar/Wind Harmer
11.286
944531AF1-118 GEN
Solar/Wind Harmer
69.657
274772LINCOLN ;3U
Adder
12.031
24441205WTRV SLR C
Solar/Wind Harmer
0.261
274724RIVER EC ;11
Adder
33.985
972231SS25-0005
Solar/Wind Harmer
18.18
972181SS23-001
Solar/Wind Harmer
11.362
274752CRETE EC ;2U
Adder
9.363
274753CRETE EC ;3U
Adder
9.363
247604X1-042
Adder
0.795
970707AG2-453 GEN
Solar/Wind Harmer
53.178
274802UNIV PARK;5U
Adder
11.035
274826FISK ;BP
Adder
20.719
276772AC2-154 GEN
Solar/Wind Harmer
5.271
276806AD2-047 C O1
Solar/Wind Harmer
20.222
970941AG2-585 GEN
Solar/Wind Harmer
23.629
274800UNIV PARK;3U
Adder
11.02
972038AH1-567 GEN2
Adder
0.69
972228AH1-698 GEN2
Adder
6.996
276897AD1-100 C
Solar/Wind Harmer
54.537
939351AE1-166 GEN
Solar/Wind Harmer
11.143
274676JOLIET 29;8U
Adder
55.43
274730ELWOOD EC;6P
Adder
30.711
274734ELWOOD EC;8P
Adder
30.711
274736ELWOOD EC;9P
Adder
30.711
274729ELWOOD EC;1P
Adder
30.71
276893AG1-478 C
Solar/Wind Harmer
0.78
943121AE2-341 GEN
Solar/Wind Harmer
27.85
943591AF1-030 GEN
Solar/Wind Harmer
18.567
270535AF1-215 GEN1
Solar/Wind Harmer
8.428
276694AA1-018 GEN2
Solar/Wind Harmer
11.537
274682WAUKEGAN ;7U
Adder
32.824
964401AG1-302 GEN
Solar/Wind Harmer
16.482
274872LEEDK;1U
Solar/Wind Harmer
0.462
276805AD2-038 GEN
Solar/Wind Harmer
9.254
276799AD1-013 GEN
Solar/Wind Harmer
3.952
946671AF1-331 GEN
Solar/Wind Harmer
0.748
274855GSG-6 ;RU
Solar/Wind Harmer
6.597
274850MENDOTA H;RU
Solar/Wind Harmer
4.587
276602WESTBROOK C
Solar/Wind Harmer
3.797
276863AD2-134 GEN
Solar/Wind Harmer
3.19
959141AF2-205 GEN
Solar/Wind Harmer
10.776
972236AH1-702 GEN2
Adder
3.863
274760LEE CO EC;1U
Adder
16.13
274767LEE CO EC;8U
Adder
15.94
24728705AND G3
Adder
9.586
24728505AND G1
Adder
4.583
959091AF2-200 GEN
Solar/Wind Harmer
13.312
942991AE2-321 GEN
Solar/Wind Harmer
17.957
274879MINONK ;1U
Solar/Wind Harmer
12.109
971333AH1-146 GEN
Solar/Wind Harmer
35.709
971335AH1-147 GEN
Solar/Wind Harmer
35.709
274764LEE CO EC;5U
Adder
16.168
274765LEE CO EC;6U
Adder
16.168
274762LEE CO EC;3U
Adder
16.13
274763LEE CO EC;4U
Adder
15.978
972267AH1-718 GEN
Adder
7.14
247621Y3-024
Adder
0.307
270471AD2-092_GEN
Solar/Wind Helper
1.743
971341AH1-150 GEN
Solar/Wind Harmer
13.312
971343AH1-151 GEN
Solar/Wind Harmer
13.312
276868AE1-113 GEN
Solar/Wind Harmer
18.162
276882AE2-255 GEN
Solar/Wind Harmer
6.054
971411AH1-196 GEN
Solar/Wind Harmer
26.803
971675AH1-338 GEN
Solar/Wind Harmer
32.161
971549AH1-272 GEN
Solar/Wind Harmer
32.93
274863CRW1-WTG
Solar/Wind Harmer
9.908
274864CRW2-WTG
Solar/Wind Harmer
9.908
274823ROCKFORD ;21
Adder
34.435
270284AF1-227 GEN1
Solar/Wind Helper
2.32
270286AF1-227 GEN2
Solar/Wind Helper
0.851
270287AF1-227 GEN3
Solar/Wind Helper
0.851
270054AF2-122 C O1
Solar/Wind Helper
1.203
971171AH1-044 GEN
Solar/Wind Harmer
13.312
959081AF2-199 GEN
Solar/Wind Harmer
6.656
971067AG2-660 GEN
Solar/Wind Harmer
1.548
944201AF1-088_MTX
Adder
133.023
957141AF2-008_MTX
Adder
52.933
LAGNLTFEXP_LAGN->PJM
CLTF
13.148
TVALTFEXP_TVA->PJM
CLTF
5.021
CBM West 2LTFEXP_CBM-W2->PJM
CBM
118.577
NYPJM->LTFIMP_NY
CLTF
3.196
LGEELTFEXP_LGEE->PJM
CLTF
4.313
WECLTFEXP_WEC->PJM
CLTF
6.719
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.8
AG2-052LTFEXP_AG2-052->PJM
LTF
0.422
AH1-155LTFEXP_AH1-155->PJM
LTF
0.633
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.282
CBM West 1LTFEXP_CBM-W1->PJM
CBM
201.554
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.706
MECLTFEXP_MEC->PJM
CLTF
24.31
SIGELTFEXP_SIGE->PJM
CLTF
0.467

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P7-1_#11010___SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P7-1_#11010___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:141.23 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:5849.93
MW Contribution:32.98
Bus #Bus NameTypeMW Contribution
970615AG2-402 GEN
50/50
4.782
270102X2-052 ST
50/50
3.225
270100X2-052 CT1
50/50
2.972
270101X2-052 CT2
50/50
2.972
247620Y3-023
50/50
0.979
24729405KEY G3
50/50
0.737
24729305KEY G2
50/50
0.724
24729205KEY G1
50/50
0.721
970321AG2-212 GEN
Solar/Wind Harmer
37.354
970611AG2-400 GEN
Solar/Wind Harmer
20.561
270216AD2-079_GEN
Solar/Wind Harmer
1.23
270142AC1-141 CT1_
50/50
4.85
24641605TWIN BRNCH
50/50
0.035
24344005CKG1
50/50
13.183
24642205MAYFLWER
50/50
1.35
944961AF1-161 GEN
50/50
5.755
962601AG1-109 GEN
50/50
5.755
270043AE2-236 GEN
Solar/Wind Harmer
11.845
970349AG2-230 GEN
Solar/Wind Harmer
32.247
970513AG2-328 GEN
Solar/Wind Harmer
37.354
970517AG2-330 GEN
Solar/Wind Harmer
33.879
959331AF2-224 GEN
Solar/Wind Harmer
20.561
965021AG1-366 GEN
Solar/Wind Harmer
4.782
247643Z2-116 C
Solar/Wind Harmer
0.142
970031AG2-029 GEN
Solar/Wind Harmer
60.641
944531AF1-118 GEN
Solar/Wind Harmer
70.444
945111AF1-176 GEN
Solar/Wind Harmer
11.293
274772LINCOLN ;3U
Adder
12.075
24441205WTRV SLR C
Solar/Wind Harmer
0.261
274724RIVER EC ;11
Adder
34.095
972231SS25-0005
Solar/Wind Harmer
18.237
972181SS23-001
Solar/Wind Harmer
11.398
274752CRETE EC ;2U
Adder
9.392
274753CRETE EC ;3U
Adder
9.392
247604X1-042
Adder
0.796
970707AG2-453 GEN
Solar/Wind Harmer
53.373
274802UNIV PARK;5U
Adder
11.073
274826FISK ;BP
Adder
20.79
276772AC2-154 GEN
Solar/Wind Harmer
5.29
276806AD2-047 C O1
Solar/Wind Harmer
20.292
970941AG2-585 GEN
Solar/Wind Harmer
23.711
274800UNIV PARK;3U
Adder
11.059
972038AH1-567 GEN2
Adder
0.692
972228AH1-698 GEN2
Adder
7.021
276897AD1-100 C
Solar/Wind Harmer
54.734
939351AE1-166 GEN
Solar/Wind Harmer
11.184
274676JOLIET 29;8U
Adder
55.629
274730ELWOOD EC;6P
Adder
30.821
274734ELWOOD EC;8P
Adder
30.821
274736ELWOOD EC;9P
Adder
30.821
274729ELWOOD EC;1P
Adder
30.821
276893AG1-478 C
Solar/Wind Harmer
0.783
943121AE2-341 GEN
Solar/Wind Harmer
27.954
943591AF1-030 GEN
Solar/Wind Harmer
18.636
270535AF1-215 GEN1
Solar/Wind Harmer
8.453
276694AA1-018 GEN2
Solar/Wind Harmer
11.579
274682WAUKEGAN ;7U
Adder
32.947
964401AG1-302 GEN
Solar/Wind Harmer
16.533
274872LEEDK;1U
Solar/Wind Harmer
0.464
276805AD2-038 GEN
Solar/Wind Harmer
9.289
276799AD1-013 GEN
Solar/Wind Harmer
3.967
946671AF1-331 GEN
Solar/Wind Harmer
0.751
274855GSG-6 ;RU
Solar/Wind Harmer
6.623
274850MENDOTA H;RU
Solar/Wind Harmer
4.605
276602WESTBROOK C
Solar/Wind Harmer
3.812
276863AD2-134 GEN
Solar/Wind Harmer
3.203
959141AF2-205 GEN
Solar/Wind Harmer
10.81
972236AH1-702 GEN2
Adder
3.879
274760LEE CO EC;1U
Adder
16.195
274767LEE CO EC;8U
Adder
16.004
24728705AND G3
Adder
9.666
24728505AND G1
Adder
4.622
959091AF2-200 GEN
Solar/Wind Harmer
28.198
971599AH1-298 GEN
50/50
20.751
270144AC1-141 ST1_
50/50
4.296
24653605MOTTVILLE
50/50
0.008
24643105BUCHANAN
50/50
0.026
24729505KEY G4
50/50
13.5
971347AH1-153 GEN
Solar/Wind Harmer
32.247
270071AF1-092 GEN
Solar/Wind Harmer
31.239
971771AH1-392 GEN
Solar/Wind Harmer
18.224
971769AH1-391 GEN
Solar/Wind Harmer
20.026
960681AF2-359 GEN
Solar/Wind Harmer
7.564
944161AF1-084 GEN
Solar/Wind Harmer
4.344
274775LINCOLN ;6U
Adder
12.075
274776LINCOLN ;7U
Adder
12.075
274777LINCOLN ;8U
Adder
12.075
274814UNIV PK N;0U
Adder
9.649
274807UNIV PK N;3U
Adder
9.628
274805UNIV PK N;1U
Adder
9.586
274811UNIV PK N;7U
Adder
9.565
972037AH1-567 GEN1
Adder
0.348
274827FISK ;RP
Adder
14.734
960591AF2-350 GEN
Solar/Wind Harmer
18.969
972227AH1-698 GEN1
Adder
4.944
274687WILL CNTY;4U
Adder
52.61
274687WILL CNTY;4U
Adder
52.61
24344105CKG2
50/50
16.81
270143AC1-141 CT2_
50/50
4.85
24639705ELKHART HY
50/50
0.328
970521AG2-332 GEN
50/50
23.355
24307105BERRINSP G
50/50
0.043
970245AG2-165 GEN
Solar/Wind Harmer
37.354
965011AG1-365 GEN
Solar/Wind Harmer
20.561
270063AE2-323 C
Solar/Wind Harmer
4.439
270505AE1-170 C O1
Solar/Wind Harmer
30.051
945111AF1-176 GEN
Solar/Wind Harmer
35.632
270449AD2-020 GEN
Solar/Wind Harmer
5.549
943021AE2-325 GEN
Solar/Wind Harmer
7.21
972207SS24-0001
Solar/Wind Harmer
42.931
274773LINCOLN ;4U
Adder
12.075
274774LINCOLN ;5U
Adder
12.075
274723RIVER EC ;12
Adder
34.493
274751CRETE EC ;1U
Adder
9.392
274754CRETE EC ;4U
Adder
9.392
276164X3-005 C
Solar/Wind Harmer
1.346
274812UNIV PK N;8U
Adder
9.565
970373AG2-245 GEN
Solar/Wind Harmer
39.985
276776AD2-060 GEN
Solar/Wind Harmer
0.802
274801UNIV PARK;4U
Adder
11.059
941551AE2-152 GEN
Solar/Wind Harmer
8.554
274676JOLIET 29;8U
Adder
57.689
274674JOLIET 9 ;6U
Adder
28.897
274732ELWOOD EC;7P
Adder
30.821
274871GR RIDGE ;2U
Solar/Wind Harmer
14.39
270055AF2-134 C O1
Solar/Wind Harmer
5.635
274745AC1-111 GEN9
Adder
10.396
276691AA1-018 GEN1
Solar/Wind Harmer
0.854
270526AF1-158 GEN
Solar/Wind Harmer
9.119
24441505OLIV SLR
Solar/Wind Harmer
0.268
965681AG1-436 GEN
Solar/Wind Harmer
25.028
965791AG1-447 GEN
Solar/Wind Harmer
12.805
957891AF2-083 GEN
Solar/Wind Harmer
6.749
960981AF2-389 GEN
Solar/Wind Harmer
3.024
961051AF2-396 GEN
Solar/Wind Harmer
31.526
961051AF2-396 GEN
Solar/Wind Harmer
14.663
274770LINCOLN ;1U
Adder
12.075
274771LINCOLN ;2U
Adder
12.075
274808UNIV PK N;4U
Adder
9.523
274803UNIV PARK;6U
Adder
11.073
972259AH1-714 GEN
Adder
36.205
274888KELLY CRK;1U
Solar/Wind Harmer
11.199
274887GEN-1.85
Solar/Wind Harmer
10.111
276843GEN-1.7
Solar/Wind Harmer
1.088
958011AF2-095 GEN
Solar/Wind Harmer
27.315
274674JOLIET 9 ;6U
Adder
28.897
274847GR RIDGE ;BU
Solar/Wind Harmer
9.466
971573AH1-285 GEN
Solar/Wind Harmer
15.928
274695ROCKY RD ;2P
Adder
20.447
274693ROCKY RD ;1P
Adder
20.246
274697ROCKY RD ;3P
Adder
5.555
274696ROCKY RD ;4P
Adder
20.929
958481AF2-142 GEN
Solar/Wind Harmer
27.523
274861TOP CROP ;1U
Solar/Wind Harmer
11.112
274862TOP CROP ;2U
Solar/Wind Harmer
9.279
274683WAUKEGAN ;8U
Adder
38.577
274683WAUKEGAN ;8U
Adder
32.519
962691AG1-118 GEN
Solar/Wind Harmer
54.666
944541AF1-119 GEN
Solar/Wind Harmer
7.616
960971AF2-388 GEN
Solar/Wind Harmer
19.875
970921AG2-575 GEN
Solar/Wind Harmer
18.172
970921AG2-575 GEN
Solar/Wind Harmer
4.226
958491AF2-143 GEN
Solar/Wind Harmer
27.161
942991AE2-321 GEN
Solar/Wind Harmer
18.026
274879MINONK ;1U
Solar/Wind Harmer
12.156
971333AH1-146 GEN
Solar/Wind Harmer
35.848
971335AH1-147 GEN
Solar/Wind Harmer
35.848
274764LEE CO EC;5U
Adder
16.233
274765LEE CO EC;6U
Adder
16.233
274762LEE CO EC;3U
Adder
16.195
274763LEE CO EC;4U
Adder
16.043
972267AH1-718 GEN
Adder
7.169
247621Y3-024
Adder
0.306
270471AD2-092_GEN
Solar/Wind Helper
1.724
971341AH1-150 GEN
Solar/Wind Harmer
28.198
971343AH1-151 GEN
Solar/Wind Harmer
28.198
274675JOLIET 29;7U
Adder
57.69
274675JOLIET 29;7U
Adder
55.63
274728ELWOOD EC;5P
Adder
30.821
274731ELWOOD EC;2P
Adder
30.821
274733ELWOOD EC;3P
Adder
30.821
274735ELWOOD EC;4P
Adder
30.821
970833AG2-524 GEN
Solar/Wind Harmer
16.346
970833AG2-524 GEN
Solar/Wind Harmer
7.603
270536AF1-215 GEN2
Solar/Wind Harmer
8.453
274746AC1-111 G10
Adder
10.396
274744AC1-111 GEN8
Adder
10.396
958711AF2-162 GEN
Solar/Wind Harmer
1.84
958391AF2-133 GEN
Solar/Wind Harmer
16.354
971177AH1-047 GEN
Solar/Wind Harmer
10.559
276868AE1-113 GEN
Solar/Wind Harmer
18.232
276882AE2-255 GEN
Solar/Wind Harmer
6.078
971411AH1-196 GEN
Solar/Wind Harmer
26.908
971675AH1-338 GEN
Solar/Wind Harmer
32.287
971549AH1-272 GEN
Solar/Wind Harmer
32.985
274863CRW1-WTG
Solar/Wind Harmer
9.948
274864CRW2-WTG
Solar/Wind Harmer
9.948
274823ROCKFORD ;21
Adder
34.571
270284AF1-227 GEN1
Solar/Wind Helper
2.284
270286AF1-227 GEN2
Solar/Wind Helper
0.838
270287AF1-227 GEN3
Solar/Wind Helper
0.838
270054AF2-122 C O1
Solar/Wind Helper
1.189
971171AH1-044 GEN
Solar/Wind Harmer
28.198
274682WAUKEGAN ;7U
Adder
32.947
274828WAUKEGAN ;BP
Adder
20.221
958381AF2-132 GEN
Solar/Wind Harmer
16.533
964861AG1-349 GEN
Solar/Wind Harmer
14.293
971917AH1-482 GEN
Solar/Wind Harmer
16.494
965651AG1-433 GEN
Solar/Wind Harmer
9.938
960751AF2-366 GEN
Solar/Wind Harmer
5.214
962781AG1-127 GEN
Solar/Wind Harmer
17.282
274872LEEDK;1U
Solar/Wind Harmer
14.889
939401AE1-172 GEN
Solar/Wind Harmer
25.25
276901AD2-066 C O1
Solar/Wind Harmer
6.35
971997AH1-543 GEN
Solar/Wind Harmer
28.31
276861AD2-134 GEN
Solar/Wind Harmer
3.203
274822ROCKFORD ;11
Adder
34.824
972235AH1-702 GEN1
Adder
4.461
274761LEE CO EC;2U
Adder
16.195
274766LEE CO EC;7U
Adder
16.004
24728605AND G2
Adder
4.622
970091AG2-072 GEN
Adder
1.052
270349AD2-093_GEN
Solar/Wind Helper
1.724
957471AF2-041 GEN
Solar/Wind Harmer
42.297
959081AF2-199 GEN
Solar/Wind Harmer
14.099
971067AG2-660 GEN
Solar/Wind Harmer
3.279
944201AF1-088_MTX
Adder
133.959
957141AF2-008_MTX
Adder
66.98
LAGNLTFEXP_LAGN->PJM
CLTF
13.321
TVALTFEXP_TVA->PJM
CLTF
5.11
CBM West 2LTFEXP_CBM-W2->PJM
CBM
119.715
NYPJM->LTFIMP_NY
CLTF
3.14
LGEELTFEXP_LGEE->PJM
CLTF
4.376
WECLTFEXP_WEC->PJM
CLTF
6.746
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.739
AG2-052LTFEXP_AG2-052->PJM
LTF
0.423
AH1-155LTFEXP_AH1-155->PJM
LTF
0.635
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.245
CBM West 1LTFEXP_CBM-W1->PJM
CBM
202.385
CBM South 1LTFEXP_CBM-S1->PJM
CBM
20.042
MECLTFEXP_MEC->PJM
CLTF
24.435
SIGELTFEXP_SIGE->PJM
CLTF
0.471

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P1-2_#6463_16757_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#6463_16757_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:140.14 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:5804.66
MW Contribution:25.63
Bus #Bus NameTypeMW Contribution
971599AH1-298 GEN
50/50
20.512
24727205RPMNG3
50/50
2.026
270144AC1-141 ST1_
50/50
4.287
24653605MOTTVILLE
50/50
0.008
24643105BUCHANAN
50/50
0.025
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
1.893
971347AH1-153 GEN
Solar/Wind Harmer
22.406
270071AF1-092 GEN
Solar/Wind Harmer
27.685
971771AH1-392 GEN
Solar/Wind Harmer
14.093
971619AH1-309 GEN
Solar/Wind Harmer
6.277
971769AH1-391 GEN
Solar/Wind Harmer
15.555
960681AF2-359 GEN
Solar/Wind Harmer
-0.002
274775LINCOLN ;6U
Adder
16.368
274776LINCOLN ;7U
Adder
16.368
274777LINCOLN ;8U
Adder
16.368
24729505KEY G4
Adder
12.57
274814UNIV PK N;0U
Adder
9.612
274807UNIV PK N;3U
Adder
9.591
274805UNIV PK N;1U
Adder
9.549
274811UNIV PK N;7U
Adder
9.528
972037AH1-567 GEN1
Adder
0.346
274827FISK ;RP
Adder
14.675
960591AF2-350 GEN
Solar/Wind Harmer
13.18
972227AH1-698 GEN1
Adder
4.923
274687WILL CNTY;4U
Adder
52.393
274687WILL CNTY;4U
Adder
52.393
274675JOLIET 29;7U
Adder
57.451
274675JOLIET 29;7U
Adder
55.399
274731ELWOOD EC;2P
Adder
30.692
274733ELWOOD EC;3P
Adder
30.692
274735ELWOOD EC;4P
Adder
30.692
274728ELWOOD EC;5P
Adder
30.693
970833AG2-524 GEN
Solar/Wind Harmer
14.308
970833AG2-524 GEN
Solar/Wind Harmer
9.539
270536AF1-215 GEN2
Solar/Wind Harmer
0.016
274746AC1-111 G10
Adder
10.351
274744AC1-111 GEN8
Adder
10.351
958391AF2-133 GEN
Solar/Wind Harmer
0.002
971177AH1-047 GEN
Solar/Wind Harmer
7.718
276868AE1-113 GEN
Solar/Wind Harmer
2.511
276882AE2-255 GEN
Solar/Wind Harmer
1.463
971411AH1-196 GEN
Solar/Wind Harmer
18.689
971675AH1-338 GEN
Solar/Wind Harmer
4.859
971549AH1-272 GEN
Solar/Wind Harmer
25.626
274863CRW1-WTG
Solar/Wind Harmer
0.004
274864CRW2-WTG
Solar/Wind Harmer
0.004
971171AH1-044 GEN
Solar/Wind Harmer
24.739
274823ROCKFORD ;21
Adder
34.415
971611AH1-305 GEN
Solar/Wind Harmer
7.323
963791AG1-232 GEN
Solar/Wind Harmer
16.568
276612AE2-035 GEN
Solar/Wind Harmer
0.003
965101AG1-375 GEN
Solar/Wind Harmer
12.216
926823AC1-168 GEN
Solar/Wind Harmer
2.071
970169AG2-114 GEN
Solar/Wind Harmer
12.156
971681AH1-341 GEN
Solar/Wind Harmer
19.553
961011AF2-392 GEN
Solar/Wind Harmer
7.036
965041AG1-368 GEN
Solar/Wind Harmer
11.932
957751AF2-069 GEN
Solar/Wind Harmer
0.392
274848CAMPGROVE;RU
Solar/Wind Harmer
0.002
24690905MDL-1G C
Solar/Wind Harmer
0.004
270180AB1-006 GEN1
Solar/Wind Harmer
0.003
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.002
270181AB1-006 GEN2
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0.005
276656WTG2_EQ
Solar/Wind Harmer
0.001
959341AF2-225 GEN
Solar/Wind Harmer
12.245
941731AE2-173 GEN
Solar/Wind Harmer
9.718
945581AF1-223 GEN
Solar/Wind Harmer
0.001
946321AF1-296 GEN
Solar/Wind Harmer
6.48
24386205FR-12G C
Solar/Wind Harmer
0.002
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.002
963841AG1-237 GEN
Solar/Wind Harmer
4.707
971609AH1-304 GEN
Solar/Wind Harmer
1.767
965051AG1-369 GEN
Solar/Wind Harmer
5.379
970289AG2-191 GEN
Solar/Wind Harmer
2.036
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.39
276848AB2-070 GEN3
Solar/Wind Harmer
0.388
270594AE1-207 GEN
Solar/Wind Harmer
11.748
270024AE2-089 GEN
Solar/Wind Harmer
0.011
970115AG2-085 GEN
Solar/Wind Harmer
3.968
24725505WLD G2 C
Solar/Wind Harmer
0.002
24699105WLD G1 C
Solar/Wind Harmer
0.001
944221AF1-090 GEN
Solar/Wind Harmer
5.647
24344105CKG2
50/50
16.743
24727005RPMNG1
50/50
2.036
270143AC1-141 CT2_
50/50
4.84
24639705ELKHART HY
50/50
0.328
970521AG2-332 GEN
50/50
23.369
24307105BERRINSP G
50/50
0.043
965011AG1-365 GEN
Solar/Wind Harmer
14.965
965421AG1-410 GEN
Solar/Wind Harmer
44.849
246936BC-WTG1
Solar/Wind Harmer
0.606
270489AE1-102 GEN1
Solar/Wind Harmer
1.943
970245AG2-165 GEN
Solar/Wind Harmer
6.295
270063AE2-323 C
Solar/Wind Harmer
0.012
270505AE1-170 C O1
Solar/Wind Harmer
14.646
945111AF1-176 GEN
Solar/Wind Harmer
24.826
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
7.196
274773LINCOLN ;4U
Adder
16.368
274774LINCOLN ;5U
Adder
16.368
274723RIVER EC ;12
Adder
34.361
274751CRETE EC ;1U
Adder
15.774
274754CRETE EC ;4U
Adder
15.774
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
9.528
970373AG2-245 GEN
Solar/Wind Harmer
27.796
274801UNIV PARK;4U
Adder
11.014
276776AD2-060 GEN
Solar/Wind Harmer
1.376
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
57.45
274674JOLIET 9 ;6U
Adder
28.777
274732ELWOOD EC;7P
Adder
30.693
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0.01
274745AC1-111 GEN9
Adder
10.351
276691AA1-018 GEN1
Solar/Wind Harmer
1.544
274682WAUKEGAN ;7U
Adder
32.805
274828WAUKEGAN ;BP
Adder
20.134
958381AF2-132 GEN
Solar/Wind Harmer
0.002
964861AG1-349 GEN
Solar/Wind Harmer
-0.002
971917AH1-482 GEN
Solar/Wind Harmer
16.434
962781AG1-127 GEN
Solar/Wind Harmer
12.012
274872LEEDK;1U
Solar/Wind Harmer
0.008
939401AE1-172 GEN
Solar/Wind Harmer
9.413
276901AD2-066 C O1
Solar/Wind Harmer
0.012
965651AG1-433 GEN
Solar/Wind Harmer
3.678
971997AH1-543 GEN
Solar/Wind Harmer
6.554
276861AD2-134 GEN
Solar/Wind Harmer
0.223
957471AF2-041 GEN
Solar/Wind Harmer
37.108
959081AF2-199 GEN
Solar/Wind Harmer
12.369
971067AG2-660 GEN
Solar/Wind Harmer
4.123
276876AE1-163_GEN2
Solar/Wind Harmer
0.003
274822ROCKFORD ;11
Adder
34.667
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
15.377
972235AH1-702 GEN1
Adder
4.441
970819AG2-516 GEN
Solar/Wind Harmer
14.695
958861AF2-177 GEN
Solar/Wind Harmer
5.294
971475AH1-234 GEN
Solar/Wind Harmer
5.925
970569AG2-363 GEN
Solar/Wind Harmer
36.555
274857EASY ROAD;U1
Solar/Wind Harmer
0.002
274761LEE CO EC;2U
Adder
16.12
274766LEE CO EC;7U
Adder
15.93
276158O29GEN2
Solar/Wind Harmer
0.001
944231AF1-091 GEN
Solar/Wind Harmer
3.153
274877BISHOP HL;1U
Solar/Wind Harmer
0.397
24791305MDL-5G
Solar/Wind Harmer
0.002
276726Z2-087_GEN
Solar/Wind Harmer
0.004
939741AE1-205 GEN
Solar/Wind Harmer
16.327
945371AF1-202 GEN
Solar/Wind Harmer
0.001
274854TWINGROVE;U2
Solar/Wind Harmer
0.005
24385905FR-11G C
Solar/Wind Harmer
0.003
24387305FR-4G C
Solar/Wind Harmer
0.004
972175AH1-670 GEN
Solar/Wind Harmer
9.129
247521TR3_G114
Solar/Wind Harmer
0.393
270246TR4_N_V150
Solar/Wind Harmer
0.07
970291AG2-192 GEN
Solar/Wind Harmer
1.393
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
4.146
963741AG1-226 GEN
Solar/Wind Harmer
24.913
276615X2-022 GEN
Solar/Wind Harmer
0.11
270032AE2-172
Solar/Wind Harmer
6.993
24695305TIMB G C
Solar/Wind Harmer
0.003
270005AE1-210 C O1
Solar/Wind Harmer
2.203
965031AG1-367 GEN
Solar/Wind Harmer
10.168
276903AD2-071 C
Solar/Wind Harmer
11.298
965911AG1-460 GEN
Solar/Wind Harmer
2.014
970825AG2-519 GEN
Solar/Wind Harmer
3.499
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0.001
970613AG2-401 GEN
Solar/Wind Harmer
6.684
247536S-71 GEN
Solar/Wind Harmer
0.341
24728605AND G2
Adder
4.579
270445AC2-157 GEN2
Solar/Wind Harmer
0.004
970333AG2-219 GEN
Solar/Wind Harmer
5.528
970615AG2-402 GEN
50/50
4.988
270102X2-052 ST
50/50
3.214
270100X2-052 CT1
50/50
2.961
270101X2-052 CT2
50/50
2.961
247620Y3-023
50/50
0.98
970611AG2-400 GEN
Solar/Wind Harmer
14.965
970627AG2-408 GEN
Solar/Wind Harmer
4.49
246938BC-WTG3
Solar/Wind Harmer
0.542
246937BC-WTG2
Solar/Wind Harmer
0.606
970321AG2-212 GEN
Solar/Wind Harmer
6.295
270216AD2-079_GEN
Solar/Wind Harmer
0.002
270526AF1-158 GEN
Solar/Wind Harmer
0.017
957891AF2-083 GEN
Solar/Wind Harmer
0.002
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
17.4
965791AG1-447 GEN
Solar/Wind Harmer
12.76
961051AF2-396 GEN
Solar/Wind Harmer
27.667
961051AF2-396 GEN
Solar/Wind Harmer
18.445
274770LINCOLN ;1U
Adder
16.368
274771LINCOLN ;2U
Adder
16.368
274808UNIV PK N;4U
Adder
9.487
274803UNIV PARK;6U
Adder
11.029
972259AH1-714 GEN
Adder
36.054
274888KELLY CRK;1U
Solar/Wind Harmer
0.774
274887GEN-1.85
Solar/Wind Harmer
0.347
276843GEN-1.7
Solar/Wind Harmer
0.427
958011AF2-095 GEN
Solar/Wind Harmer
18.98
274674JOLIET 9 ;6U
Adder
28.777
274847GR RIDGE ;BU
Solar/Wind Harmer
0.005
971573AH1-285 GEN
Solar/Wind Harmer
2.397
274695ROCKY RD ;2P
Adder
20.358
274693ROCKY RD ;1P
Adder
20.158
274697ROCKY RD ;3P
Adder
5.53
274696ROCKY RD ;4P
Adder
20.838
958481AF2-142 GEN
Solar/Wind Harmer
19.12
274861TOP CROP ;1U
Solar/Wind Harmer
0.003
274862TOP CROP ;2U
Solar/Wind Harmer
1.724
274683WAUKEGAN ;8U
Adder
38.41
274683WAUKEGAN ;8U
Adder
32.378
962691AG1-118 GEN
Solar/Wind Harmer
37.971
970921AG2-575 GEN
Solar/Wind Harmer
12.623
970921AG2-575 GEN
Solar/Wind Harmer
4.208
958491AF2-143 GEN
Solar/Wind Harmer
18.868
944541AF1-119 GEN
Solar/Wind Harmer
0.84
960971AF2-388 GEN
Solar/Wind Harmer
7.355
942991AE2-321 GEN
Solar/Wind Harmer
13.981
274879MINONK ;1U
Solar/Wind Harmer
0.528
971333AH1-146 GEN
Solar/Wind Harmer
24.899
971335AH1-147 GEN
Solar/Wind Harmer
24.899
971341AH1-150 GEN
Solar/Wind Harmer
24.739
971343AH1-151 GEN
Solar/Wind Harmer
24.739
276872AE1-163_GEN1
Solar/Wind Harmer
0.003
274856ECOGROVE ;U1
Solar/Wind Harmer
0.288
276611AD2-172 GEN
Solar/Wind Harmer
0.003
938861AE1-114 GEN
Solar/Wind Harmer
6.879
274764LEE CO EC;5U
Adder
16.158
274765LEE CO EC;6U
Adder
16.158
274762LEE CO EC;3U
Adder
16.12
274763LEE CO EC;4U
Adder
15.968
276603SUBLETTE C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
7.136
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.003
276741O09 GEN1
Solar/Wind Harmer
0.425
276708O09 GEN2
Solar/Wind Harmer
0.425
274851PROVIDENC;RU
Solar/Wind Harmer
0.002
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.467
276646AC1-214 GEN2
Solar/Wind Harmer
0.467
942221AE2-234 GEN
Solar/Wind Harmer
0.059
276782AC1-033 GEN
Solar/Wind Harmer
0.002
960611AF2-352 GEN
Solar/Wind Harmer
3.81
966841AG1-555 GEN
Solar/Wind Harmer
1.27
270599AE1-208 GEN
Solar/Wind Harmer
9.916
270031AE2-169
Solar/Wind Harmer
5.95
276763AC1-053 GEN1
Solar/Wind Harmer
0.002
276764AC1-053 GEN2
Solar/Wind Harmer
0.002
970241AG2-163 GEN
Solar/Wind Harmer
6.141
971613AH1-306 GEN
Solar/Wind Harmer
5.035
276916AD2-100_GEN
Solar/Wind Harmer
20.939
276911AD2-131_GEN
Solar/Wind Harmer
1.379
960441AF2-335 GEN
Solar/Wind Harmer
9.92
970825AG2-519 GEN
Solar/Wind Harmer
10.923
945391AF1-204 GEN
Solar/Wind Harmer
9.973
964611AG1-324 GEN
Solar/Wind Harmer
0.694
270201AC2-176 GEN
Solar/Wind Harmer
0.002
24379505HDWTR1G C
Solar/Wind Harmer
0.003
24727105RPMNG2
50/50
2.043
965431AG1-411 GEN
50/50
24.916
270142AC1-141 CT1_
50/50
4.84
24641605TWIN BRNCH
50/50
0.035
24344005CKG1
50/50
13.145
24642205MAYFLWER
50/50
1.347
944961AF1-161 GEN
50/50
5.744
962601AG1-109 GEN
50/50
5.744
270043AE2-236 GEN
Solar/Wind Harmer
9.614
959331AF2-224 GEN
Solar/Wind Harmer
10.476
965021AG1-366 GEN
Solar/Wind Harmer
4.988
270491AE1-102 GEN2
Solar/Wind Harmer
1.943
970349AG2-230 GEN
Solar/Wind Harmer
22.406
970513AG2-328 GEN
Solar/Wind Harmer
6.295
970517AG2-330 GEN
Solar/Wind Harmer
37.773
970031AG2-029 GEN
Solar/Wind Harmer
9.246
247643Z2-116 C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
11.278
944531AF1-118 GEN
Solar/Wind Harmer
62.173
274772LINCOLN ;3U
Adder
16.368
24441205WTRV SLR C
Solar/Wind Harmer
0
274724RIVER EC ;11
Adder
33.965
274752CRETE EC ;2U
Adder
15.774
274753CRETE EC ;3U
Adder
15.774
247604X1-042
Adder
0.795
970707AG2-453 GEN
Solar/Wind Harmer
43.26
274802UNIV PARK;5U
Adder
11.029
274826FISK ;BP
Adder
20.707
274800UNIV PARK;3U
Adder
11.014
972038AH1-567 GEN2
Adder
0.689
276806AD2-047 C O1
Solar/Wind Harmer
7.469
970941AG2-585 GEN
Solar/Wind Harmer
16.476
972228AH1-698 GEN2
Adder
6.992
276897AD1-100 C
Solar/Wind Harmer
0.017
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
274676JOLIET 29;8U
Adder
55.398
274729ELWOOD EC;1P
Adder
30.692
274730ELWOOD EC;6P
Adder
30.693
274734ELWOOD EC;8P
Adder
30.693
274736ELWOOD EC;9P
Adder
30.693
276893AG1-478 C
Solar/Wind Harmer
0.516
943121AE2-341 GEN
Solar/Wind Harmer
21.706
943591AF1-030 GEN
Solar/Wind Harmer
14.435
270535AF1-215 GEN1
Solar/Wind Harmer
0.016
276694AA1-018 GEN2
Solar/Wind Harmer
0.002
274682WAUKEGAN ;7U
Adder
32.805
964401AG1-302 GEN
Solar/Wind Harmer
0.002
274872LEEDK;1U
Solar/Wind Harmer
0.462
276805AD2-038 GEN
Solar/Wind Harmer
0.004
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
1.33
274855GSG-6 ;RU
Solar/Wind Harmer
0.457
274850MENDOTA H;RU
Solar/Wind Harmer
0.147
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.223
959141AF2-205 GEN
Solar/Wind Harmer
-0.003
959091AF2-200 GEN
Solar/Wind Harmer
24.739
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
3.861
970571AG2-364 GEN
Solar/Wind Harmer
24.37
274858EASY ROAD;U2
Solar/Wind Harmer
0.002
274760LEE CO EC;1U
Adder
16.12
274767LEE CO EC;8U
Adder
15.93
276157O29GEN1
Solar/Wind Harmer
1.927
274878BISHOP HL;2U
Solar/Wind Harmer
0.397
24755605MDL-5G
Solar/Wind Harmer
0.002
970781AG2-491 GEN
Solar/Wind Harmer
11.712
942111AE2-223 GEN
Solar/Wind Harmer
3.79
965931AG1-462 GEN
Solar/Wind Harmer
29.323
274853TWINGROVE;U1
Solar/Wind Harmer
0.005
965091AG1-374 GEN
Solar/Wind Harmer
34.294
959611AF2-252 GEN
Solar/Wind Harmer
3.81
247642Z2-115 C
Solar/Wind Harmer
0.005
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.07
970289AG2-191 GEN
Solar/Wind Harmer
1.179
970291AG2-192 GEN
Solar/Wind Harmer
1.072
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
4.944
276668AB2-070 GEN1
Solar/Wind Harmer
0.39
276621W2-048 GEN
Solar/Wind Harmer
0.529
276838X2-022 GEN2
Solar/Wind Harmer
0.591
971617AH1-308 GEN
Solar/Wind Harmer
8.654
958821AF2-173 GEN
Solar/Wind Harmer
14.235
270004AE1-209 GEN
Solar/Wind Harmer
2.203
942481AE2-261 GEN
Solar/Wind Harmer
30.115
946031AF1-268 GEN
Solar/Wind Harmer
9.153
970193AG2-126 GEN
Solar/Wind Harmer
14.08
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
13.732
270437AC2-090 C
Solar/Wind Harmer
0.004
270404AC1-167 GEN
Solar/Wind Harmer
0.004
270258AD1-119 GEN
Solar/Wind Harmer
0.002
24728705AND G3
Adder
9.578
24728505AND G1
Adder
4.579
970243AG2-164 GEN
Solar/Wind Harmer
4.523
970519AG2-331 GEN
Solar/Wind Harmer
20.102
970699AG2-449 GEN
Solar/Wind Harmer
1.933
270356AE2-297 GEN
Solar/Wind Harmer
0.01
970773AG2-487 GEN
Solar/Wind Harmer
1.34
270349AD2-093_GEN
Solar/Wind Helper
1.737
270240V3-007_GEN2
Solar/Wind Harmer
0.003
247607V1-011 GEN
Solar/Wind Harmer
0.001
270543AE2-219 C
Solar/Wind Harmer
0.005
971029AG2-637 GEN
Solar/Wind Harmer
10.94
971673AH1-337 GEN
Solar/Wind Harmer
4.593
270284AF1-227 GEN1
Solar/Wind Helper
2.302
270286AF1-227 GEN2
Solar/Wind Helper
0.844
270287AF1-227 GEN3
Solar/Wind Helper
0.844
270054AF2-122 C O1
Solar/Wind Helper
1.201
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
247621Y3-024
Adder
0.306
970623AG2-406 GEN
Solar/Wind Harmer
1.558
270383AD1-128 GEN
Solar/Wind Harmer
0.005
270444AC2-157 GEN1
Solar/Wind Harmer
0.004
971587AH1-292 GEN
Solar/Wind Harmer
5.849
970883AG2-550 GEN
Solar/Wind Harmer
7.917
970885AG2-551 GEN
Solar/Wind Harmer
2.639
270007AE1-245 C
Solar/Wind Harmer
0.002
970239AG2-162 GEN
Solar/Wind Harmer
1.933
270471AD2-092_GEN
Solar/Wind Helper
1.737
944201AF1-088_MTX
Adder
132.938
957141AF2-008_MTX
Adder
17.09
LAGNLTFEXP_LAGN->PJM
CLTF
13.14
TVALTFEXP_TVA->PJM
CLTF
5.018
CBM West 2LTFEXP_CBM-W2->PJM
CBM
118.505
NYPJM->LTFIMP_NY
CLTF
3.194
LGEELTFEXP_LGEE->PJM
CLTF
4.31
WECLTFEXP_WEC->PJM
CLTF
6.715
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.799
AG2-052LTFEXP_AG2-052->PJM
LTF
0.422
AH1-155LTFEXP_AH1-155->PJM
LTF
0.632
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.281
CBM West 1LTFEXP_CBM-W1->PJM
CBM
201.431
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.695
MECLTFEXP_MEC->PJM
CLTF
24.295
SIGELTFEXP_SIGE->PJM
CLTF
0.466

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P7-1_#17567_SRT-SL


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P7-1_#17567_SRT-SL
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:140.03 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:5799.9
MW Contribution:32.89
Bus #Bus NameTypeMW Contribution
270102X2-052 ST
50/50
3.121
270100X2-052 CT1
50/50
2.876
270101X2-052 CT2
50/50
2.876
247620Y3-023
50/50
0.945
970615AG2-402 GEN
50/50
4.377
970321AG2-212 GEN
Solar/Wind Harmer
36.028
270216AD2-079_GEN
Solar/Wind Harmer
1.189
270526AF1-158 GEN
Solar/Wind Harmer
8.831
957891AF2-083 GEN
Solar/Wind Harmer
6.556
960981AF2-389 GEN
Solar/Wind Harmer
2.938
24441505OLIV SLR
Solar/Wind Harmer
0.26
965681AG1-436 GEN
Solar/Wind Harmer
24.212
965791AG1-447 GEN
Solar/Wind Harmer
12.387
961051AF2-396 GEN
Solar/Wind Harmer
30.667
961051AF2-396 GEN
Solar/Wind Harmer
14.264
970611AG2-400 GEN
Solar/Wind Harmer
18.821
24344105CKG2
50/50
16.266
270143AC1-141 CT2_
50/50
4.706
24639705ELKHART HY
50/50
0.317
970521AG2-332 GEN
50/50
22.545
24307105BERRINSP G
50/50
0.042
970245AG2-165 GEN
Solar/Wind Harmer
36.028
270505AE1-170 C O1
Solar/Wind Harmer
29.203
945111AF1-176 GEN
Solar/Wind Harmer
34.591
270063AE2-323 C
Solar/Wind Harmer
4.268
270449AD2-020 GEN
Solar/Wind Harmer
5.404
943021AE2-325 GEN
Solar/Wind Harmer
7.022
965011AG1-365 GEN
Solar/Wind Harmer
18.821
972207SS24-0001
Solar/Wind Harmer
41.419
274773LINCOLN ;4U
Adder
11.65
274774LINCOLN ;5U
Adder
11.65
274723RIVER EC ;12
Adder
33.283
274751CRETE EC ;1U
Adder
9.065
274754CRETE EC ;4U
Adder
9.065
276164X3-005 C
Solar/Wind Harmer
1.299
274812UNIV PK N;8U
Adder
9.23
970373AG2-245 GEN
Solar/Wind Harmer
38.641
274801UNIV PARK;4U
Adder
10.668
276776AD2-060 GEN
Solar/Wind Harmer
0.774
941551AE2-152 GEN
Solar/Wind Harmer
8.252
971599AH1-298 GEN
50/50
19.41
270144AC1-141 ST1_
50/50
4.168
24643105BUCHANAN
50/50
0.025
24653605MOTTVILLE
50/50
0.007
971347AH1-153 GEN
Solar/Wind Harmer
31.136
270071AF1-092 GEN
Solar/Wind Harmer
29.457
971771AH1-392 GEN
Solar/Wind Harmer
17.645
971769AH1-391 GEN
Solar/Wind Harmer
19.396
960681AF2-359 GEN
Solar/Wind Harmer
7.318
944161AF1-084 GEN
Solar/Wind Harmer
4.238
274775LINCOLN ;6U
Adder
11.65
274776LINCOLN ;7U
Adder
11.65
274777LINCOLN ;8U
Adder
11.65
24729505KEY G4
Adder
11.965
274814UNIV PK N;0U
Adder
9.311
274807UNIV PK N;3U
Adder
9.29
274805UNIV PK N;1U
Adder
9.25
274811UNIV PK N;7U
Adder
9.23
972037AH1-567 GEN1
Adder
0.335
274827FISK ;RP
Adder
14.215
960591AF2-350 GEN
Solar/Wind Harmer
18.3
972227AH1-698 GEN1
Adder
4.769
274687WILL CNTY;4U
Adder
50.75
274687WILL CNTY;4U
Adder
50.75
274675JOLIET 29;7U
Adder
55.649
274675JOLIET 29;7U
Adder
53.661
274731ELWOOD EC;2P
Adder
29.73
274733ELWOOD EC;3P
Adder
29.73
274735ELWOOD EC;4P
Adder
29.73
274728ELWOOD EC;5P
Adder
29.73
970833AG2-524 GEN
Solar/Wind Harmer
15.767
970833AG2-524 GEN
Solar/Wind Harmer
7.333
270536AF1-215 GEN2
Solar/Wind Harmer
8.164
274746AC1-111 G10
Adder
10.026
274744AC1-111 GEN8
Adder
10.026
971549AH1-272 GEN
Solar/Wind Harmer
32.892
958391AF2-133 GEN
Solar/Wind Harmer
15.781
971177AH1-047 GEN
Solar/Wind Harmer
10.18
276868AE1-113 GEN
Solar/Wind Harmer
17.58
276882AE2-255 GEN
Solar/Wind Harmer
5.86
971411AH1-196 GEN
Solar/Wind Harmer
25.942
971675AH1-338 GEN
Solar/Wind Harmer
31.127
274863CRW1-WTG
Solar/Wind Harmer
9.592
274864CRW2-WTG
Solar/Wind Harmer
9.592
958711AF2-162 GEN
Solar/Wind Harmer
1.737
274823ROCKFORD ;21
Adder
33.326
270054AF2-122 C O1
Solar/Wind Helper
1.3
971171AH1-044 GEN
Solar/Wind Harmer
27.184
270142AC1-141 CT1_
50/50
4.706
24344005CKG1
50/50
12.844
24641605TWIN BRNCH
50/50
0.034
24642205MAYFLWER
50/50
1.31
944961AF1-161 GEN
50/50
5.605
962601AG1-109 GEN
50/50
5.605
970349AG2-230 GEN
Solar/Wind Harmer
31.136
270043AE2-236 GEN
Solar/Wind Harmer
11.189
970513AG2-328 GEN
Solar/Wind Harmer
36.028
970517AG2-330 GEN
Solar/Wind Harmer
32.677
247643Z2-116 C
Solar/Wind Harmer
0.137
945111AF1-176 GEN
Solar/Wind Harmer
10.963
970031AG2-029 GEN
Solar/Wind Harmer
57.557
24441205WTRV SLR C
Solar/Wind Harmer
0.256
944531AF1-118 GEN
Solar/Wind Harmer
66.164
959331AF2-224 GEN
Solar/Wind Harmer
18.821
965021AG1-366 GEN
Solar/Wind Harmer
4.377
274772LINCOLN ;3U
Adder
11.65
247604X1-042
Adder
0.782
274724RIVER EC ;11
Adder
32.899
972231SS25-0005
Solar/Wind Harmer
17.6
972181SS23-001
Solar/Wind Harmer
11
274752CRETE EC ;2U
Adder
9.065
274753CRETE EC ;3U
Adder
9.065
970707AG2-453 GEN
Solar/Wind Harmer
51.485
274802UNIV PARK;5U
Adder
10.683
274826FISK ;BP
Adder
20.057
970941AG2-585 GEN
Solar/Wind Harmer
22.875
274800UNIV PARK;3U
Adder
10.668
972038AH1-567 GEN2
Adder
0.668
276772AC2-154 GEN
Solar/Wind Harmer
5.103
276806AD2-047 C O1
Solar/Wind Harmer
19.577
972228AH1-698 GEN2
Adder
6.773
276897AD1-100 C
Solar/Wind Harmer
52.8
939351AE1-166 GEN
Solar/Wind Harmer
10.788
274676JOLIET 29;8U
Adder
53.66
274729ELWOOD EC;1P
Adder
29.73
274730ELWOOD EC;6P
Adder
29.73
274734ELWOOD EC;8P
Adder
29.73
274736ELWOOD EC;9P
Adder
29.73
276893AG1-478 C
Solar/Wind Harmer
0.755
943121AE2-341 GEN
Solar/Wind Harmer
26.96
943591AF1-030 GEN
Solar/Wind Harmer
17.973
270535AF1-215 GEN1
Solar/Wind Harmer
8.164
276694AA1-018 GEN2
Solar/Wind Harmer
11.167
274682WAUKEGAN ;7U
Adder
31.772
964401AG1-302 GEN
Solar/Wind Harmer
15.959
274872LEEDK;1U
Solar/Wind Harmer
0.447
276805AD2-038 GEN
Solar/Wind Harmer
8.958
276799AD1-013 GEN
Solar/Wind Harmer
3.825
946671AF1-331 GEN
Solar/Wind Harmer
0.724
274855GSG-6 ;RU
Solar/Wind Harmer
6.385
274850MENDOTA H;RU
Solar/Wind Harmer
4.44
276602WESTBROOK C
Solar/Wind Harmer
3.675
276863AD2-134 GEN
Solar/Wind Harmer
3.088
959141AF2-205 GEN
Solar/Wind Harmer
10.429
972236AH1-702 GEN2
Adder
3.739
274760LEE CO EC;1U
Adder
15.609
274767LEE CO EC;8U
Adder
15.425
24728705AND G3
Adder
9.344
24728505AND G1
Adder
4.468
959091AF2-200 GEN
Solar/Wind Harmer
27.184
274770LINCOLN ;1U
Adder
11.65
274771LINCOLN ;2U
Adder
11.65
274808UNIV PK N;4U
Adder
9.189
274803UNIV PARK;6U
Adder
10.683
972259AH1-714 GEN
Adder
34.925
274888KELLY CRK;1U
Solar/Wind Harmer
10.804
274887GEN-1.85
Solar/Wind Harmer
9.754
276843GEN-1.7
Solar/Wind Harmer
1.049
958011AF2-095 GEN
Solar/Wind Harmer
26.352
274674JOLIET 9 ;6U
Adder
27.874
274847GR RIDGE ;BU
Solar/Wind Harmer
9.13
971573AH1-285 GEN
Solar/Wind Harmer
15.361
274695ROCKY RD ;2P
Adder
19.718
274693ROCKY RD ;1P
Adder
19.524
274697ROCKY RD ;3P
Adder
5.356
274696ROCKY RD ;4P
Adder
20.183
958481AF2-142 GEN
Solar/Wind Harmer
26.544
274861TOP CROP ;1U
Solar/Wind Harmer
10.717
274862TOP CROP ;2U
Solar/Wind Harmer
8.949
274683WAUKEGAN ;8U
Adder
37.2
274683WAUKEGAN ;8U
Adder
31.358
962691AG1-118 GEN
Solar/Wind Harmer
52.711
970921AG2-575 GEN
Solar/Wind Harmer
17.522
970921AG2-575 GEN
Solar/Wind Harmer
4.075
958491AF2-143 GEN
Solar/Wind Harmer
26.192
942991AE2-321 GEN
Solar/Wind Harmer
17.38
274879MINONK ;1U
Solar/Wind Harmer
11.721
971333AH1-146 GEN
Solar/Wind Harmer
34.561
971335AH1-147 GEN
Solar/Wind Harmer
34.561
944541AF1-119 GEN
Solar/Wind Harmer
7.192
960971AF2-388 GEN
Solar/Wind Harmer
18.769
274764LEE CO EC;5U
Adder
15.646
274765LEE CO EC;6U
Adder
15.646
274762LEE CO EC;3U
Adder
15.609
274763LEE CO EC;4U
Adder
15.462
972267AH1-718 GEN
Adder
6.909
247621Y3-024
Adder
0.305
270471AD2-092_GEN
Solar/Wind Helper
2.215
971341AH1-150 GEN
Solar/Wind Harmer
27.184
971343AH1-151 GEN
Solar/Wind Harmer
27.184
274676JOLIET 29;8U
Adder
55.648
274674JOLIET 9 ;6U
Adder
27.874
274732ELWOOD EC;7P
Adder
29.73
274871GR RIDGE ;2U
Solar/Wind Harmer
13.88
270055AF2-134 C O1
Solar/Wind Harmer
5.442
274745AC1-111 GEN9
Adder
10.026
276691AA1-018 GEN1
Solar/Wind Harmer
0.824
274682WAUKEGAN ;7U
Adder
31.772
274828WAUKEGAN ;BP
Adder
19.5
958381AF2-132 GEN
Solar/Wind Harmer
15.959
964861AG1-349 GEN
Solar/Wind Harmer
13.796
971917AH1-482 GEN
Solar/Wind Harmer
15.92
960751AF2-366 GEN
Solar/Wind Harmer
5.027
962781AG1-127 GEN
Solar/Wind Harmer
16.663
274872LEEDK;1U
Solar/Wind Harmer
14.356
939401AE1-172 GEN
Solar/Wind Harmer
24.351
276901AD2-066 C O1
Solar/Wind Harmer
6.124
971997AH1-543 GEN
Solar/Wind Harmer
27.297
276861AD2-134 GEN
Solar/Wind Harmer
3.088
965651AG1-433 GEN
Solar/Wind Harmer
9.384
274822ROCKFORD ;11
Adder
33.569
972235AH1-702 GEN1
Adder
4.3
274761LEE CO EC;2U
Adder
15.609
274766LEE CO EC;7U
Adder
15.425
24728605AND G2
Adder
4.468
972301AH1-735 GEN
Adder
2.524
270349AD2-093_GEN
Solar/Wind Helper
2.215
957471AF2-041 GEN
Solar/Wind Harmer
40.776
959081AF2-199 GEN
Solar/Wind Harmer
13.592
971067AG2-660 GEN
Solar/Wind Harmer
3.161
944201AF1-088_MTX
Adder
128.814
957141AF2-008_MTX
Adder
64.407
LAGNLTFEXP_LAGN->PJM
CLTF
12.499
TVALTFEXP_TVA->PJM
CLTF
4.733
CBM West 2LTFEXP_CBM-W2->PJM
CBM
114.06
NYPJM->LTFIMP_NY
CLTF
3.145
LGEELTFEXP_LGEE->PJM
CLTF
4.258
WECLTFEXP_WEC->PJM
CLTF
6.502
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.96
AG2-052LTFEXP_AG2-052->PJM
LTF
0.408
AH1-155LTFEXP_AH1-155->PJM
LTF
0.612
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.385
CBM West 1LTFEXP_CBM-W1->PJM
CBM
204.072
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.768
MECLTFEXP_MEC->PJM
CLTF
23.493
SIGELTFEXP_SIGE->PJM
CLTF
0.454

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P2-2_#16655_05GUNN RD SW 345_2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P2-2_#16655_05GUNN RD SW 345_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:135.98 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:5632.19
MW Contribution:31.81
Bus #Bus NameTypeMW Contribution
24344005CKG1
50/50
12.539
270142AC1-141 CT1_
50/50
4.589
24641605TWIN BRNCH
50/50
0.033
24642205MAYFLWER
50/50
1.278
944961AF1-161 GEN
50/50
5.457
962601AG1-109 GEN
50/50
5.457
970349AG2-230 GEN
Solar/Wind Harmer
30.529
970513AG2-328 GEN
Solar/Wind Harmer
35.447
970517AG2-330 GEN
Solar/Wind Harmer
32.149
270043AE2-236 GEN
Solar/Wind Harmer
10.823
247643Z2-116 C
Solar/Wind Harmer
0.133
945111AF1-176 GEN
Solar/Wind Harmer
10.67
970031AG2-029 GEN
Solar/Wind Harmer
55.416
24441205WTRV SLR C
Solar/Wind Harmer
0.249
274772LINCOLN ;3U
Adder
11.428
944531AF1-118 GEN
Solar/Wind Harmer
64.152
247604X1-042
Adder
0.761
274724RIVER EC ;11
Adder
32.23
972231SS25-0005
Solar/Wind Harmer
17.235
972181SS23-001
Solar/Wind Harmer
10.772
274752CRETE EC ;2U
Adder
8.877
274753CRETE EC ;3U
Adder
8.877
970707AG2-453 GEN
Solar/Wind Harmer
50.49
274802UNIV PARK;5U
Adder
10.468
274826FISK ;BP
Adder
19.655
276772AC2-154 GEN
Solar/Wind Harmer
5.001
276806AD2-047 C O1
Solar/Wind Harmer
19.185
970941AG2-585 GEN
Solar/Wind Harmer
22.418
274800UNIV PARK;3U
Adder
10.455
972038AH1-567 GEN2
Adder
0.654
972228AH1-698 GEN2
Adder
6.639
276897AD1-100 C
Solar/Wind Harmer
51.755
939351AE1-166 GEN
Solar/Wind Harmer
10.575
274676JOLIET 29;8U
Adder
52.592
274729ELWOOD EC;1P
Adder
29.137
274730ELWOOD EC;6P
Adder
29.138
274734ELWOOD EC;8P
Adder
29.138
274736ELWOOD EC;9P
Adder
29.138
276893AG1-478 C
Solar/Wind Harmer
0.74
959331AF2-224 GEN
Solar/Wind Harmer
17.715
965021AG1-366 GEN
Solar/Wind Harmer
4.12
943121AE2-341 GEN
Solar/Wind Harmer
26.432
943591AF1-030 GEN
Solar/Wind Harmer
17.621
270535AF1-215 GEN1
Solar/Wind Harmer
7.981
276694AA1-018 GEN2
Solar/Wind Harmer
10.942
274682WAUKEGAN ;7U
Adder
31.14
964401AG1-302 GEN
Solar/Wind Harmer
15.597
274872LEEDK;1U
Solar/Wind Harmer
0.438
276805AD2-038 GEN
Solar/Wind Harmer
8.776
276799AD1-013 GEN
Solar/Wind Harmer
3.749
946671AF1-331 GEN
Solar/Wind Harmer
0.71
274855GSG-6 ;RU
Solar/Wind Harmer
6.258
274850MENDOTA H;RU
Solar/Wind Harmer
4.351
276602WESTBROOK C
Solar/Wind Harmer
3.602
276863AD2-134 GEN
Solar/Wind Harmer
3.026
959141AF2-205 GEN
Solar/Wind Harmer
10.19
972236AH1-702 GEN2
Adder
3.664
274760LEE CO EC;1U
Adder
15.294
274767LEE CO EC;8U
Adder
15.114
24728705AND G3
Adder
8.991
24728505AND G1
Adder
4.299
959091AF2-200 GEN
Solar/Wind Harmer
32.581
24344105CKG2
50/50
15.989
270143AC1-141 CT2_
50/50
4.589
24639705ELKHART HY
50/50
0.308
970521AG2-332 GEN
50/50
21.897
24307105BERRINSP G
50/50
0.041
970245AG2-165 GEN
Solar/Wind Harmer
35.447
270505AE1-170 C O1
Solar/Wind Harmer
28.453
945111AF1-176 GEN
Solar/Wind Harmer
33.668
270449AD2-020 GEN
Solar/Wind Harmer
5.261
943021AE2-325 GEN
Solar/Wind Harmer
6.837
270063AE2-323 C
Solar/Wind Harmer
4.119
972207SS24-0001
Solar/Wind Harmer
40.631
274773LINCOLN ;4U
Adder
11.428
274774LINCOLN ;5U
Adder
11.428
274723RIVER EC ;12
Adder
32.605
274751CRETE EC ;1U
Adder
8.877
274754CRETE EC ;4U
Adder
8.877
276164X3-005 C
Solar/Wind Harmer
1.273
274812UNIV PK N;8U
Adder
9.041
970373AG2-245 GEN
Solar/Wind Harmer
37.783
276776AD2-060 GEN
Solar/Wind Harmer
0.758
274801UNIV PARK;4U
Adder
10.455
941551AE2-152 GEN
Solar/Wind Harmer
8.088
274676JOLIET 29;8U
Adder
54.54
274674JOLIET 9 ;6U
Adder
27.32
274732ELWOOD EC;7P
Adder
29.138
965011AG1-365 GEN
Solar/Wind Harmer
17.715
274871GR RIDGE ;2U
Solar/Wind Harmer
13.606
274745AC1-111 GEN9
Adder
9.829
270055AF2-134 C O1
Solar/Wind Harmer
5.32
276691AA1-018 GEN1
Solar/Wind Harmer
0.807
274682WAUKEGAN ;7U
Adder
31.14
274828WAUKEGAN ;BP
Adder
19.112
958381AF2-132 GEN
Solar/Wind Harmer
15.597
960751AF2-366 GEN
Solar/Wind Harmer
4.928
962781AG1-127 GEN
Solar/Wind Harmer
16.333
964861AG1-349 GEN
Solar/Wind Harmer
13.483
971917AH1-482 GEN
Solar/Wind Harmer
15.559
274872LEEDK;1U
Solar/Wind Harmer
14.071
939401AE1-172 GEN
Solar/Wind Harmer
23.859
276901AD2-066 C O1
Solar/Wind Harmer
6
971997AH1-543 GEN
Solar/Wind Harmer
26.748
276861AD2-134 GEN
Solar/Wind Harmer
3.026
274822ROCKFORD ;11
Adder
32.898
972235AH1-702 GEN1
Adder
4.214
274761LEE CO EC;2U
Adder
15.294
274766LEE CO EC;7U
Adder
15.114
24728605AND G2
Adder
4.299
970091AG2-072 GEN
Adder
4.41
270349AD2-093_GEN
Solar/Wind Helper
1.84
957471AF2-041 GEN
Solar/Wind Harmer
48.872
959081AF2-199 GEN
Solar/Wind Harmer
16.291
971067AG2-660 GEN
Solar/Wind Harmer
3.789
270102X2-052 ST
50/50
3.054
270100X2-052 CT1
50/50
2.814
270101X2-052 CT2
50/50
2.814
247620Y3-023
50/50
0.917
970321AG2-212 GEN
Solar/Wind Harmer
35.447
270216AD2-079_GEN
Solar/Wind Harmer
1.158
270526AF1-158 GEN
Solar/Wind Harmer
8.625
965681AG1-436 GEN
Solar/Wind Harmer
23.689
965791AG1-447 GEN
Solar/Wind Harmer
12.12
24441505OLIV SLR
Solar/Wind Harmer
0.254
957891AF2-083 GEN
Solar/Wind Harmer
6.386
960981AF2-389 GEN
Solar/Wind Harmer
2.861
961051AF2-396 GEN
Solar/Wind Harmer
29.854
961051AF2-396 GEN
Solar/Wind Harmer
13.886
274770LINCOLN ;1U
Adder
11.428
274771LINCOLN ;2U
Adder
11.428
274808UNIV PK N;4U
Adder
9.002
274803UNIV PARK;6U
Adder
10.468
972259AH1-714 GEN
Adder
34.24
274888KELLY CRK;1U
Solar/Wind Harmer
10.588
274887GEN-1.85
Solar/Wind Harmer
9.559
971599AH1-298 GEN
50/50
18.905
270144AC1-141 ST1_
50/50
4.065
24643105BUCHANAN
50/50
0.024
24653605MOTTVILLE
50/50
0.007
971347AH1-153 GEN
Solar/Wind Harmer
30.529
971771AH1-392 GEN
Solar/Wind Harmer
17.216
270071AF1-092 GEN
Solar/Wind Harmer
28.557
960681AF2-359 GEN
Solar/Wind Harmer
7.16
971769AH1-391 GEN
Solar/Wind Harmer
18.948
944161AF1-084 GEN
Solar/Wind Harmer
4.125
274775LINCOLN ;6U
Adder
11.428
274776LINCOLN ;7U
Adder
11.428
274777LINCOLN ;8U
Adder
11.428
274814UNIV PK N;0U
Adder
9.121
274807UNIV PK N;3U
Adder
9.101
274805UNIV PK N;1U
Adder
9.061
274811UNIV PK N;7U
Adder
9.041
972037AH1-567 GEN1
Adder
0.329
274827FISK ;RP
Adder
13.93
960591AF2-350 GEN
Solar/Wind Harmer
17.934
972227AH1-698 GEN1
Adder
4.674
24729505KEY G4
Adder
11.594
274687WILL CNTY;4U
Adder
49.737
274687WILL CNTY;4U
Adder
49.737
274675JOLIET 29;7U
Adder
54.541
274675JOLIET 29;7U
Adder
52.593
274731ELWOOD EC;2P
Adder
29.137
274733ELWOOD EC;3P
Adder
29.137
274735ELWOOD EC;4P
Adder
29.137
274728ELWOOD EC;5P
Adder
29.138
970833AG2-524 GEN
Solar/Wind Harmer
15.455
970833AG2-524 GEN
Solar/Wind Harmer
7.188
274746AC1-111 G10
Adder
9.829
274744AC1-111 GEN8
Adder
9.829
270536AF1-215 GEN2
Solar/Wind Harmer
7.981
971549AH1-272 GEN
Solar/Wind Harmer
31.811
971177AH1-047 GEN
Solar/Wind Harmer
9.977
276868AE1-113 GEN
Solar/Wind Harmer
17.225
276882AE2-255 GEN
Solar/Wind Harmer
5.742
958391AF2-133 GEN
Solar/Wind Harmer
15.422
971411AH1-196 GEN
Solar/Wind Harmer
25.424
971675AH1-338 GEN
Solar/Wind Harmer
30.507
274863CRW1-WTG
Solar/Wind Harmer
9.397
274864CRW2-WTG
Solar/Wind Harmer
9.397
274823ROCKFORD ;21
Adder
32.659
270284AF1-227 GEN1
Solar/Wind Helper
2.861
270286AF1-227 GEN2
Solar/Wind Helper
1.049
270287AF1-227 GEN3
Solar/Wind Helper
1.049
270054AF2-122 C O1
Solar/Wind Helper
1.201
971171AH1-044 GEN
Solar/Wind Harmer
32.581
276843GEN-1.7
Solar/Wind Harmer
1.029
958011AF2-095 GEN
Solar/Wind Harmer
25.825
274674JOLIET 9 ;6U
Adder
27.32
970611AG2-400 GEN
Solar/Wind Harmer
17.715
274847GR RIDGE ;BU
Solar/Wind Harmer
8.95
971573AH1-285 GEN
Solar/Wind Harmer
15.059
274695ROCKY RD ;2P
Adder
19.327
274693ROCKY RD ;1P
Adder
19.137
274697ROCKY RD ;3P
Adder
5.25
274696ROCKY RD ;4P
Adder
19.783
958481AF2-142 GEN
Solar/Wind Harmer
26.008
274861TOP CROP ;1U
Solar/Wind Harmer
10.5
274862TOP CROP ;2U
Solar/Wind Harmer
8.768
274683WAUKEGAN ;8U
Adder
36.461
274683WAUKEGAN ;8U
Adder
30.735
962691AG1-118 GEN
Solar/Wind Harmer
51.667
970921AG2-575 GEN
Solar/Wind Harmer
17.175
970921AG2-575 GEN
Solar/Wind Harmer
3.994
958491AF2-143 GEN
Solar/Wind Harmer
25.662
942991AE2-321 GEN
Solar/Wind Harmer
17.034
274879MINONK ;1U
Solar/Wind Harmer
11.484
971333AH1-146 GEN
Solar/Wind Harmer
33.871
971335AH1-147 GEN
Solar/Wind Harmer
33.871
274764LEE CO EC;5U
Adder
15.33
274765LEE CO EC;6U
Adder
15.33
274762LEE CO EC;3U
Adder
15.294
274763LEE CO EC;4U
Adder
15.15
972267AH1-718 GEN
Adder
6.769
247621Y3-024
Adder
0.286
270471AD2-092_GEN
Solar/Wind Helper
1.84
971341AH1-150 GEN
Solar/Wind Harmer
32.581
971343AH1-151 GEN
Solar/Wind Harmer
32.581
944201AF1-088_MTX
Adder
125.321
957141AF2-008_MTX
Adder
62.661
LAGNLTFEXP_LAGN->PJM
CLTF
12.243
TVALTFEXP_TVA->PJM
CLTF
4.635
CBM West 2LTFEXP_CBM-W2->PJM
CBM
111.242
NYPJM->LTFIMP_NY
CLTF
3.027
LGEELTFEXP_LGEE->PJM
CLTF
4.067
WECLTFEXP_WEC->PJM
CLTF
6.372
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.882
AG2-052LTFEXP_AG2-052->PJM
LTF
0.399
AH1-155LTFEXP_AH1-155->PJM
LTF
0.599
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.344
CBM West 1LTFEXP_CBM-W1->PJM
CBM
197.094
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.275
MECLTFEXP_MEC->PJM
CLTF
22.999
SIGELTFEXP_SIGE->PJM
CLTF
0.439

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P2-2_#16654_05GUNN RD SW 345_1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P2-2_#16654_05GUNN RD SW 345_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:135.75 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:5622.57
MW Contribution:31.83
Bus #Bus NameTypeMW Contribution
24344005CKG1
50/50
12.545
270142AC1-141 CT1_
50/50
4.591
24641605TWIN BRNCH
50/50
0.033
24642205MAYFLWER
50/50
1.278
944961AF1-161 GEN
50/50
5.46
962601AG1-109 GEN
50/50
5.46
970349AG2-230 GEN
Solar/Wind Harmer
30.544
970513AG2-328 GEN
Solar/Wind Harmer
35.465
970517AG2-330 GEN
Solar/Wind Harmer
32.166
270043AE2-236 GEN
Solar/Wind Harmer
10.829
247643Z2-116 C
Solar/Wind Harmer
0.133
945111AF1-176 GEN
Solar/Wind Harmer
10.676
970031AG2-029 GEN
Solar/Wind Harmer
55.447
24441205WTRV SLR C
Solar/Wind Harmer
0.249
274772LINCOLN ;3U
Adder
11.434
944531AF1-118 GEN
Solar/Wind Harmer
64.187
247604X1-042
Adder
0.761
274724RIVER EC ;11
Adder
32.247
972231SS25-0005
Solar/Wind Harmer
17.245
972181SS23-001
Solar/Wind Harmer
10.778
274752CRETE EC ;2U
Adder
8.882
274753CRETE EC ;3U
Adder
8.882
970707AG2-453 GEN
Solar/Wind Harmer
50.518
274802UNIV PARK;5U
Adder
10.474
274826FISK ;BP
Adder
19.666
276772AC2-154 GEN
Solar/Wind Harmer
5.004
276806AD2-047 C O1
Solar/Wind Harmer
19.196
970941AG2-585 GEN
Solar/Wind Harmer
22.43
274800UNIV PARK;3U
Adder
10.46
972038AH1-567 GEN2
Adder
0.655
972228AH1-698 GEN2
Adder
6.643
276897AD1-100 C
Solar/Wind Harmer
51.784
939351AE1-166 GEN
Solar/Wind Harmer
10.581
274676JOLIET 29;8U
Adder
52.622
24344105CKG2
50/50
15.997
270143AC1-141 CT2_
50/50
4.591
24639705ELKHART HY
50/50
0.308
971599AH1-298 GEN
50/50
18.913
270144AC1-141 ST1_
50/50
4.067
24643105BUCHANAN
50/50
0.024
24653605MOTTVILLE
50/50
0.007
971347AH1-153 GEN
Solar/Wind Harmer
30.544
971771AH1-392 GEN
Solar/Wind Harmer
17.225
270071AF1-092 GEN
Solar/Wind Harmer
28.572
960681AF2-359 GEN
Solar/Wind Harmer
7.163
971769AH1-391 GEN
Solar/Wind Harmer
18.958
944161AF1-084 GEN
Solar/Wind Harmer
4.127
274775LINCOLN ;6U
Adder
11.434
274776LINCOLN ;7U
Adder
11.434
274777LINCOLN ;8U
Adder
11.434
274814UNIV PK N;0U
Adder
9.126
274807UNIV PK N;3U
Adder
9.106
274805UNIV PK N;1U
Adder
9.066
274811UNIV PK N;7U
Adder
9.046
972037AH1-567 GEN1
Adder
0.329
274827FISK ;RP
Adder
13.937
960591AF2-350 GEN
Solar/Wind Harmer
17.944
972227AH1-698 GEN1
Adder
4.677
24729505KEY G4
Adder
11.601
274687WILL CNTY;4U
Adder
49.765
274687WILL CNTY;4U
Adder
49.765
274675JOLIET 29;7U
Adder
54.572
274675JOLIET 29;7U
Adder
52.623
274728ELWOOD EC;5P
Adder
29.154
274731ELWOOD EC;2P
Adder
29.154
274733ELWOOD EC;3P
Adder
29.154
274735ELWOOD EC;4P
Adder
29.154
970833AG2-524 GEN
Solar/Wind Harmer
15.464
970833AG2-524 GEN
Solar/Wind Harmer
7.192
274746AC1-111 G10
Adder
9.834
274744AC1-111 GEN8
Adder
9.834
270536AF1-215 GEN2
Solar/Wind Harmer
7.986
971549AH1-272 GEN
Solar/Wind Harmer
31.829
971177AH1-047 GEN
Solar/Wind Harmer
9.983
276868AE1-113 GEN
Solar/Wind Harmer
17.235
276882AE2-255 GEN
Solar/Wind Harmer
5.745
958391AF2-133 GEN
Solar/Wind Harmer
15.431
971411AH1-196 GEN
Solar/Wind Harmer
25.439
971675AH1-338 GEN
Solar/Wind Harmer
30.526
274863CRW1-WTG
Solar/Wind Harmer
9.402
274864CRW2-WTG
Solar/Wind Harmer
9.402
274823ROCKFORD ;21
Adder
32.679
270284AF1-227 GEN1
Solar/Wind Helper
2.858
270286AF1-227 GEN2
Solar/Wind Helper
1.048
270287AF1-227 GEN3
Solar/Wind Helper
1.048
270054AF2-122 C O1
Solar/Wind Helper
1.2
971171AH1-044 GEN
Solar/Wind Harmer
32.601
270102X2-052 ST
50/50
3.055
270100X2-052 CT1
50/50
2.815
270101X2-052 CT2
50/50
2.815
247620Y3-023
50/50
0.917
970321AG2-212 GEN
Solar/Wind Harmer
35.465
270216AD2-079_GEN
Solar/Wind Harmer
1.158
270526AF1-158 GEN
Solar/Wind Harmer
8.63
965681AG1-436 GEN
Solar/Wind Harmer
23.702
965791AG1-447 GEN
Solar/Wind Harmer
12.126
24441505OLIV SLR
Solar/Wind Harmer
0.254
957891AF2-083 GEN
Solar/Wind Harmer
6.389
960981AF2-389 GEN
Solar/Wind Harmer
2.863
961051AF2-396 GEN
Solar/Wind Harmer
29.87
961051AF2-396 GEN
Solar/Wind Harmer
13.893
274770LINCOLN ;1U
Adder
11.434
274771LINCOLN ;2U
Adder
11.434
274808UNIV PK N;4U
Adder
9.007
274803UNIV PARK;6U
Adder
10.474
972259AH1-714 GEN
Adder
34.259
274888KELLY CRK;1U
Solar/Wind Harmer
10.594
274887GEN-1.85
Solar/Wind Harmer
9.565
276843GEN-1.7
Solar/Wind Harmer
1.029
958011AF2-095 GEN
Solar/Wind Harmer
25.84
274674JOLIET 9 ;6U
Adder
27.335
970611AG2-400 GEN
Solar/Wind Harmer
17.725
274847GR RIDGE ;BU
Solar/Wind Harmer
8.955
971573AH1-285 GEN
Solar/Wind Harmer
15.068
274695ROCKY RD ;2P
Adder
19.338
274693ROCKY RD ;1P
Adder
19.148
274697ROCKY RD ;3P
Adder
5.253
274696ROCKY RD ;4P
Adder
19.794
958481AF2-142 GEN
Solar/Wind Harmer
26.023
274861TOP CROP ;1U
Solar/Wind Harmer
10.506
274862TOP CROP ;2U
Solar/Wind Harmer
8.773
274683WAUKEGAN ;8U
Adder
36.482
274683WAUKEGAN ;8U
Adder
30.752
962691AG1-118 GEN
Solar/Wind Harmer
51.697
970921AG2-575 GEN
Solar/Wind Harmer
17.185
970921AG2-575 GEN
Solar/Wind Harmer
3.996
958491AF2-143 GEN
Solar/Wind Harmer
25.677
942991AE2-321 GEN
Solar/Wind Harmer
17.044
274879MINONK ;1U
Solar/Wind Harmer
11.491
971333AH1-146 GEN
Solar/Wind Harmer
33.891
971335AH1-147 GEN
Solar/Wind Harmer
33.891
274764LEE CO EC;5U
Adder
15.34
274765LEE CO EC;6U
Adder
15.34
274762LEE CO EC;3U
Adder
15.304
274763LEE CO EC;4U
Adder
15.16
972267AH1-718 GEN
Adder
6.773
247621Y3-024
Adder
0.286
270471AD2-092_GEN
Solar/Wind Helper
1.839
270224U2-072_GEN2
Solar/Wind Helper
0.897
270227U2-072_GEN3
Solar/Wind Helper
0.897
270228U2-072_GEN4
Solar/Wind Helper
0.897
270231U2-072_GEN5
Solar/Wind Helper
0.897
971341AH1-150 GEN
Solar/Wind Harmer
32.601
971343AH1-151 GEN
Solar/Wind Harmer
32.601
274730ELWOOD EC;6P
Adder
29.154
274734ELWOOD EC;8P
Adder
29.154
274736ELWOOD EC;9P
Adder
29.154
274729ELWOOD EC;1P
Adder
29.154
276893AG1-478 C
Solar/Wind Harmer
0.74
959331AF2-224 GEN
Solar/Wind Harmer
17.725
965021AG1-366 GEN
Solar/Wind Harmer
4.122
943121AE2-341 GEN
Solar/Wind Harmer
26.447
943591AF1-030 GEN
Solar/Wind Harmer
17.631
970521AG2-332 GEN
50/50
21.908
24307105BERRINSP G
50/50
0.041
970245AG2-165 GEN
Solar/Wind Harmer
35.465
270505AE1-170 C O1
Solar/Wind Harmer
28.468
945111AF1-176 GEN
Solar/Wind Harmer
33.686
270449AD2-020 GEN
Solar/Wind Harmer
5.264
943021AE2-325 GEN
Solar/Wind Harmer
6.84
270063AE2-323 C
Solar/Wind Harmer
4.121
972207SS24-0001
Solar/Wind Harmer
40.653
274773LINCOLN ;4U
Adder
11.434
274774LINCOLN ;5U
Adder
11.434
274723RIVER EC ;12
Adder
32.623
274751CRETE EC ;1U
Adder
8.882
274754CRETE EC ;4U
Adder
8.882
276164X3-005 C
Solar/Wind Harmer
1.273
274812UNIV PK N;8U
Adder
9.046
970373AG2-245 GEN
Solar/Wind Harmer
37.804
276776AD2-060 GEN
Solar/Wind Harmer
0.759
274801UNIV PARK;4U
Adder
10.46
941551AE2-152 GEN
Solar/Wind Harmer
8.093
274676JOLIET 29;8U
Adder
54.571
274674JOLIET 9 ;6U
Adder
27.335
274732ELWOOD EC;7P
Adder
29.154
965011AG1-365 GEN
Solar/Wind Harmer
17.725
274871GR RIDGE ;2U
Solar/Wind Harmer
13.613
274745AC1-111 GEN9
Adder
9.834
270055AF2-134 C O1
Solar/Wind Harmer
5.323
276691AA1-018 GEN1
Solar/Wind Harmer
0.808
274682WAUKEGAN ;7U
Adder
31.159
274828WAUKEGAN ;BP
Adder
19.123
958381AF2-132 GEN
Solar/Wind Harmer
15.606
960751AF2-366 GEN
Solar/Wind Harmer
4.93
962781AG1-127 GEN
Solar/Wind Harmer
16.343
964861AG1-349 GEN
Solar/Wind Harmer
13.491
971917AH1-482 GEN
Solar/Wind Harmer
15.568
274872LEEDK;1U
Solar/Wind Harmer
14.079
939401AE1-172 GEN
Solar/Wind Harmer
23.873
276901AD2-066 C O1
Solar/Wind Harmer
6.004
971997AH1-543 GEN
Solar/Wind Harmer
26.764
276861AD2-134 GEN
Solar/Wind Harmer
3.028
274822ROCKFORD ;11
Adder
32.918
972235AH1-702 GEN1
Adder
4.216
274761LEE CO EC;2U
Adder
15.304
274766LEE CO EC;7U
Adder
15.124
24728605AND G2
Adder
4.303
970091AG2-072 GEN
Adder
4.415
270349AD2-093_GEN
Solar/Wind Helper
1.839
270223U2-072_GEN1
Solar/Wind Helper
0.897
270578AF1-285 GEN2
Solar/Wind Helper
0.608
270391AF1-285 GEN3
Solar/Wind Helper
0.608
957471AF2-041 GEN
Solar/Wind Harmer
48.901
959081AF2-199 GEN
Solar/Wind Harmer
16.3
971067AG2-660 GEN
Solar/Wind Harmer
3.791
270535AF1-215 GEN1
Solar/Wind Harmer
7.986
276694AA1-018 GEN2
Solar/Wind Harmer
10.948
274682WAUKEGAN ;7U
Adder
31.159
964401AG1-302 GEN
Solar/Wind Harmer
15.606
274872LEEDK;1U
Solar/Wind Harmer
0.439
276805AD2-038 GEN
Solar/Wind Harmer
8.782
276799AD1-013 GEN
Solar/Wind Harmer
3.751
946671AF1-331 GEN
Solar/Wind Harmer
0.71
274855GSG-6 ;RU
Solar/Wind Harmer
6.262
274850MENDOTA H;RU
Solar/Wind Harmer
4.354
276602WESTBROOK C
Solar/Wind Harmer
3.604
276863AD2-134 GEN
Solar/Wind Harmer
3.028
959141AF2-205 GEN
Solar/Wind Harmer
10.197
972236AH1-702 GEN2
Adder
3.666
274760LEE CO EC;1U
Adder
15.304
274767LEE CO EC;8U
Adder
15.124
24728705AND G3
Adder
8.999
24728505AND G1
Adder
4.303
942871AE2-306 GEN
Solar/Wind Helper
0.456
959091AF2-200 GEN
Solar/Wind Harmer
32.601
944201AF1-088_MTX
Adder
125.438
957141AF2-008_MTX
Adder
62.719
LAGNLTFEXP_LAGN->PJM
CLTF
12.264
TVALTFEXP_TVA->PJM
CLTF
4.645
CBM West 2LTFEXP_CBM-W2->PJM
CBM
111.378
NYPJM->LTFIMP_NY
CLTF
3.02
LGEELTFEXP_LGEE->PJM
CLTF
4.074
WECLTFEXP_WEC->PJM
CLTF
6.376
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.875
AG2-052LTFEXP_AG2-052->PJM
LTF
0.399
AH1-155LTFEXP_AH1-155->PJM
LTF
0.599
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.34
CBM West 1LTFEXP_CBM-W1->PJM
CBM
197.241
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.313
MECLTFEXP_MEC->PJM
CLTF
23.016
SIGELTFEXP_SIGE->PJM
CLTF
0.44

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o Base Case


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:130.5 %
Rating:4047.0 MVA
Rating Type:A
MVA to Mitigate:5281.19
MW Contribution:23.96
Bus #Bus NameTypeMW Contribution
971599AH1-298 GEN
50/50
18.435
270144AC1-141 ST1_
50/50
3.968
24643105BUCHANAN
50/50
0.024
24653605MOTTVILLE
50/50
0.007
971347AH1-153 GEN
Solar/Wind Harmer
20.909
971771AH1-392 GEN
Solar/Wind Harmer
13.038
960681AF2-359 GEN
Solar/Wind Harmer
-0.002
971769AH1-391 GEN
Solar/Wind Harmer
14.442
270071AF1-092 GEN
Solar/Wind Harmer
24.752
971619AH1-309 GEN
Solar/Wind Harmer
5.808
274775LINCOLN ;6U
Adder
15.292
274776LINCOLN ;7U
Adder
15.292
274777LINCOLN ;8U
Adder
15.292
274814UNIV PK N;0U
Adder
8.954
274807UNIV PK N;3U
Adder
8.935
274805UNIV PK N;1U
Adder
8.896
274811UNIV PK N;7U
Adder
8.876
972037AH1-567 GEN1
Adder
0.323
274827FISK ;RP
Adder
13.681
960591AF2-350 GEN
Solar/Wind Harmer
12.291
972227AH1-698 GEN1
Adder
4.592
274687WILL CNTY;4U
Adder
48.86
274687WILL CNTY;4U
Adder
48.86
274675JOLIET 29;7U
Adder
53.583
274675JOLIET 29;7U
Adder
51.669
274728ELWOOD EC;5P
Adder
28.626
274731ELWOOD EC;2P
Adder
28.625
274733ELWOOD EC;3P
Adder
28.625
274735ELWOOD EC;4P
Adder
28.625
24729505KEY G4
Adder
11.296
970833AG2-524 GEN
Solar/Wind Harmer
13.35
970833AG2-524 GEN
Solar/Wind Harmer
8.9
274746AC1-111 G10
Adder
9.659
274744AC1-111 GEN8
Adder
9.659
270536AF1-215 GEN2
Solar/Wind Harmer
0.015
971177AH1-047 GEN
Solar/Wind Harmer
7.198
276868AE1-113 GEN
Solar/Wind Harmer
2.341
276882AE2-255 GEN
Solar/Wind Harmer
1.364
958391AF2-133 GEN
Solar/Wind Harmer
0.002
971675AH1-338 GEN
Solar/Wind Harmer
4.532
971411AH1-196 GEN
Solar/Wind Harmer
17.431
971549AH1-272 GEN
Solar/Wind Harmer
23.961
274863CRW1-WTG
Solar/Wind Harmer
0.004
274864CRW2-WTG
Solar/Wind Harmer
0.004
971171AH1-044 GEN
Solar/Wind Harmer
23.073
274823ROCKFORD ;21
Adder
32.096
971611AH1-305 GEN
Solar/Wind Harmer
6.79
276612AE2-035 GEN
Solar/Wind Harmer
0.003
926823AC1-168 GEN
Solar/Wind Harmer
1.931
970169AG2-114 GEN
Solar/Wind Harmer
11.331
971681AH1-341 GEN
Solar/Wind Harmer
18.233
961011AF2-392 GEN
Solar/Wind Harmer
6.56
957751AF2-069 GEN
Solar/Wind Harmer
0.366
965101AG1-375 GEN
Solar/Wind Harmer
11.003
274848CAMPGROVE;RU
Solar/Wind Harmer
0.002
276655WTG1_EQ
Solar/Wind Harmer
0.004
276656WTG2_EQ
Solar/Wind Harmer
0.001
959341AF2-225 GEN
Solar/Wind Harmer
11.407
24344005CKG1
50/50
12.252
270142AC1-141 CT1_
50/50
4.479
24641605TWIN BRNCH
50/50
0.032
24642205MAYFLWER
50/50
1.247
944961AF1-161 GEN
50/50
5.318
962601AG1-109 GEN
50/50
5.318
970349AG2-230 GEN
Solar/Wind Harmer
20.909
970513AG2-328 GEN
Solar/Wind Harmer
5.915
970517AG2-330 GEN
Solar/Wind Harmer
35.487
270043AE2-236 GEN
Solar/Wind Harmer
8.538
247643Z2-116 C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
10.397
274772LINCOLN ;3U
Adder
15.292
24441205WTRV SLR C
Solar/Wind Harmer
0
274724RIVER EC ;11
Adder
31.641
944531AF1-118 GEN
Solar/Wind Harmer
55.84
274752CRETE EC ;2U
Adder
14.685
274753CRETE EC ;3U
Adder
14.685
970031AG2-029 GEN
Solar/Wind Harmer
8.073
247604X1-042
Adder
0.74
970707AG2-453 GEN
Solar/Wind Harmer
40.394
274802UNIV PARK;5U
Adder
10.281
274826FISK ;BP
Adder
19.304
276806AD2-047 C O1
Solar/Wind Harmer
6.965
970941AG2-585 GEN
Solar/Wind Harmer
15.363
274800UNIV PARK;3U
Adder
10.269
972038AH1-567 GEN2
Adder
0.643
972228AH1-698 GEN2
Adder
6.522
276897AD1-100 C
Solar/Wind Harmer
0.016
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
274676JOLIET 29;8U
Adder
51.668
274730ELWOOD EC;6P
Adder
28.626
274734ELWOOD EC;8P
Adder
28.626
274736ELWOOD EC;9P
Adder
28.626
274729ELWOOD EC;1P
Adder
28.625
276893AG1-478 C
Solar/Wind Harmer
0.481
943121AE2-341 GEN
Solar/Wind Harmer
20.258
943591AF1-030 GEN
Solar/Wind Harmer
13.472
270535AF1-215 GEN1
Solar/Wind Harmer
0.015
276694AA1-018 GEN2
Solar/Wind Harmer
0.002
274682WAUKEGAN ;7U
Adder
30.6
964401AG1-302 GEN
Solar/Wind Harmer
0.002
274872LEEDK;1U
Solar/Wind Harmer
0.431
276805AD2-038 GEN
Solar/Wind Harmer
0.003
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
1.24
274855GSG-6 ;RU
Solar/Wind Harmer
0.426
274850MENDOTA H;RU
Solar/Wind Harmer
0.137
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.208
959331AF2-224 GEN
Solar/Wind Harmer
8.128
965021AG1-366 GEN
Solar/Wind Harmer
3.871
959091AF2-200 GEN
Solar/Wind Harmer
23.073
959141AF2-205 GEN
Solar/Wind Harmer
-0.003
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
3.601
970571AG2-364 GEN
Solar/Wind Harmer
22.715
274858EASY ROAD;U2
Solar/Wind Harmer
0.002
274760LEE CO EC;1U
Adder
15.031
274767LEE CO EC;8U
Adder
14.854
276157O29GEN1
Solar/Wind Harmer
1.797
274878BISHOP HL;2U
Solar/Wind Harmer
0.37
942111AE2-223 GEN
Solar/Wind Harmer
3.531
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
10.846
965931AG1-462 GEN
Solar/Wind Harmer
27.328
274853TWINGROVE;U1
Solar/Wind Harmer
0.004
965091AG1-374 GEN
Solar/Wind Harmer
31.938
959611AF2-252 GEN
Solar/Wind Harmer
3.549
247642Z2-115 C
Solar/Wind Harmer
0.004
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
4.599
276668AB2-070 GEN1
Solar/Wind Harmer
0.363
970289AG2-191 GEN
Solar/Wind Harmer
1.074
970291AG2-192 GEN
Solar/Wind Harmer
0.977
276621W2-048 GEN
Solar/Wind Harmer
0.492
276838X2-022 GEN2
Solar/Wind Harmer
0.549
942481AE2-261 GEN
Solar/Wind Harmer
27.997
958821AF2-173 GEN
Solar/Wind Harmer
12.883
270004AE1-209 GEN
Solar/Wind Harmer
1.994
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.059
971617AH1-308 GEN
Solar/Wind Harmer
7.545
946031AF1-268 GEN
Solar/Wind Harmer
8.268
970193AG2-126 GEN
Solar/Wind Harmer
13.029
270437AC2-090 C
Solar/Wind Harmer
0.004
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
12.308
270404AC1-167 GEN
Solar/Wind Harmer
0.003
270258AD1-119 GEN
Solar/Wind Harmer
0.002
24728705AND G3
Adder
8.781
24728505AND G1
Adder
4.198
970243AG2-164 GEN
Solar/Wind Harmer
4.208
970519AG2-331 GEN
Solar/Wind Harmer
18.702
970699AG2-449 GEN
Solar/Wind Harmer
1.798
270491AE1-102 GEN2
Solar/Wind Harmer
0.934
270356AE2-297 GEN
Solar/Wind Harmer
0.009
941731AE2-173 GEN
Solar/Wind Harmer
9.053
24690905MDL-1G C
Solar/Wind Harmer
0.003
270180AB1-006 GEN1
Solar/Wind Harmer
0.003
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.002
270181AB1-006 GEN2
Solar/Wind Harmer
0
946321AF1-296 GEN
Solar/Wind Harmer
6.04
945581AF1-223 GEN
Solar/Wind Harmer
0.001
24386205FR-12G C
Solar/Wind Harmer
0.002
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.002
963791AG1-232 GEN
Solar/Wind Harmer
13.932
963841AG1-237 GEN
Solar/Wind Harmer
4.358
965041AG1-368 GEN
Solar/Wind Harmer
10.015
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.363
276848AB2-070 GEN3
Solar/Wind Harmer
0.361
970289AG2-191 GEN
Solar/Wind Harmer
1.856
971609AH1-304 GEN
Solar/Wind Harmer
1.589
270594AE1-207 GEN
Solar/Wind Harmer
10.691
965051AG1-369 GEN
Solar/Wind Harmer
4.577
270024AE2-089 GEN
Solar/Wind Harmer
0.01
24725505WLD G2 C
Solar/Wind Harmer
0.002
24699105WLD G1 C
Solar/Wind Harmer
0.001
970115AG2-085 GEN
Solar/Wind Harmer
3.587
944221AF1-090 GEN
Solar/Wind Harmer
5.246
270240V3-007_GEN2
Solar/Wind Harmer
0.002
247607V1-011 GEN
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
0.91
270543AE2-219 C
Solar/Wind Harmer
0.004
971029AG2-637 GEN
Solar/Wind Harmer
9.925
24344105CKG2
50/50
15.732
270143AC1-141 CT2_
50/50
4.479
24639705ELKHART HY
50/50
0.3
970521AG2-332 GEN
50/50
21.293
24307105BERRINSP G
50/50
0.04
970245AG2-165 GEN
Solar/Wind Harmer
5.915
270505AE1-170 C O1
Solar/Wind Harmer
13.553
945111AF1-176 GEN
Solar/Wind Harmer
22.888
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
6.663
274773LINCOLN ;4U
Adder
15.292
274774LINCOLN ;5U
Adder
15.292
270063AE2-323 C
Solar/Wind Harmer
0.01
274723RIVER EC ;12
Adder
32.009
274751CRETE EC ;1U
Adder
14.685
274754CRETE EC ;4U
Adder
14.685
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
8.876
970373AG2-245 GEN
Solar/Wind Harmer
25.833
276776AD2-060 GEN
Solar/Wind Harmer
1.283
274801UNIV PARK;4U
Adder
10.269
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
53.582
274674JOLIET 9 ;6U
Adder
26.84
274732ELWOOD EC;7P
Adder
28.626
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
274745AC1-111 GEN9
Adder
9.659
270055AF2-134 C O1
Solar/Wind Harmer
0.009
276691AA1-018 GEN1
Solar/Wind Harmer
1.44
274682WAUKEGAN ;7U
Adder
30.6
274828WAUKEGAN ;BP
Adder
18.78
962781AG1-127 GEN
Solar/Wind Harmer
11.207
958381AF2-132 GEN
Solar/Wind Harmer
0.002
274872LEEDK;1U
Solar/Wind Harmer
0.007
939401AE1-172 GEN
Solar/Wind Harmer
8.779
964861AG1-349 GEN
Solar/Wind Harmer
-0.002
971917AH1-482 GEN
Solar/Wind Harmer
15.25
276901AD2-066 C O1
Solar/Wind Harmer
0.012
971997AH1-543 GEN
Solar/Wind Harmer
6.112
276861AD2-134 GEN
Solar/Wind Harmer
0.208
965011AG1-365 GEN
Solar/Wind Harmer
11.612
957471AF2-041 GEN
Solar/Wind Harmer
34.609
959081AF2-199 GEN
Solar/Wind Harmer
11.536
971067AG2-660 GEN
Solar/Wind Harmer
3.845
276876AE1-163_GEN2
Solar/Wind Harmer
0.003
274822ROCKFORD ;11
Adder
32.33
972235AH1-702 GEN1
Adder
4.141
970819AG2-516 GEN
Solar/Wind Harmer
13.704
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
14.256
971475AH1-234 GEN
Solar/Wind Harmer
5.525
970569AG2-363 GEN
Solar/Wind Harmer
34.072
965651AG1-433 GEN
Solar/Wind Harmer
3.31
274857EASY ROAD;U1
Solar/Wind Harmer
0.002
274761LEE CO EC;2U
Adder
15.031
274766LEE CO EC;7U
Adder
14.854
276158O29GEN2
Solar/Wind Harmer
0.001
274877BISHOP HL;1U
Solar/Wind Harmer
0.37
958861AF2-177 GEN
Solar/Wind Harmer
4.768
276726Z2-087_GEN
Solar/Wind Harmer
0.004
939741AE1-205 GEN
Solar/Wind Harmer
15.209
24791305MDL-5G
Solar/Wind Harmer
0.001
274854TWINGROVE;U2
Solar/Wind Harmer
0.005
945371AF1-202 GEN
Solar/Wind Harmer
0.001
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.004
944231AF1-091 GEN
Solar/Wind Harmer
2.757
972175AH1-670 GEN
Solar/Wind Harmer
8.498
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
3.857
970291AG2-192 GEN
Solar/Wind Harmer
1.27
276615X2-022 GEN
Solar/Wind Harmer
0.102
963741AG1-226 GEN
Solar/Wind Harmer
23.062
270032AE2-172
Solar/Wind Harmer
6.364
965911AG1-460 GEN
Solar/Wind Harmer
1.873
276903AD2-071 C
Solar/Wind Harmer
10.292
270005AE1-210 C O1
Solar/Wind Harmer
1.994
965031AG1-367 GEN
Solar/Wind Harmer
9.202
247521TR3_G114
Solar/Wind Harmer
0.334
270246TR4_N_V150
Solar/Wind Harmer
0.059
24695305TIMB G C
Solar/Wind Harmer
0.002
970825AG2-519 GEN
Solar/Wind Harmer
3.164
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0.001
970613AG2-401 GEN
Solar/Wind Harmer
6.065
24728605AND G2
Adder
4.198
247536S-71 GEN
Solar/Wind Harmer
0.307
965421AG1-410 GEN
Solar/Wind Harmer
22.83
270445AC2-157 GEN2
Solar/Wind Harmer
0.003
970333AG2-219 GEN
Solar/Wind Harmer
5.143
246936BC-WTG1
Solar/Wind Harmer
0.291
270489AE1-102 GEN1
Solar/Wind Harmer
0.934
970773AG2-487 GEN
Solar/Wind Harmer
1.226
270349AD2-093_GEN
Solar/Wind Helper
1.564
270102X2-052 ST
50/50
2.992
270100X2-052 CT1
50/50
2.757
270101X2-052 CT2
50/50
2.757
247620Y3-023
50/50
0.89
970321AG2-212 GEN
Solar/Wind Harmer
5.915
270216AD2-079_GEN
Solar/Wind Harmer
0.002
965681AG1-436 GEN
Solar/Wind Harmer
16.197
965791AG1-447 GEN
Solar/Wind Harmer
11.878
270526AF1-158 GEN
Solar/Wind Harmer
0.016
24441505OLIV SLR
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
0.002
961051AF2-396 GEN
Solar/Wind Harmer
25.575
961051AF2-396 GEN
Solar/Wind Harmer
17.05
274770LINCOLN ;1U
Adder
15.292
274771LINCOLN ;2U
Adder
15.292
274808UNIV PK N;4U
Adder
8.838
972259AH1-714 GEN
Adder
33.646
274803UNIV PARK;6U
Adder
10.281
274888KELLY CRK;1U
Solar/Wind Harmer
0.722
274887GEN-1.85
Solar/Wind Harmer
0.324
276843GEN-1.7
Solar/Wind Harmer
0.398
958011AF2-095 GEN
Solar/Wind Harmer
17.698
274674JOLIET 9 ;6U
Adder
26.84
274847GR RIDGE ;BU
Solar/Wind Harmer
0.004
971573AH1-285 GEN
Solar/Wind Harmer
2.237
274695ROCKY RD ;2P
Adder
18.993
274693ROCKY RD ;1P
Adder
18.806
274697ROCKY RD ;3P
Adder
5.159
274696ROCKY RD ;4P
Adder
19.441
958481AF2-142 GEN
Solar/Wind Harmer
17.825
274861TOP CROP ;1U
Solar/Wind Harmer
0.003
274862TOP CROP ;2U
Solar/Wind Harmer
1.607
274683WAUKEGAN ;8U
Adder
35.828
274683WAUKEGAN ;8U
Adder
30.201
962691AG1-118 GEN
Solar/Wind Harmer
35.425
970921AG2-575 GEN
Solar/Wind Harmer
11.776
970921AG2-575 GEN
Solar/Wind Harmer
3.925
958491AF2-143 GEN
Solar/Wind Harmer
17.589
942991AE2-321 GEN
Solar/Wind Harmer
13.041
274879MINONK ;1U
Solar/Wind Harmer
0.492
970611AG2-400 GEN
Solar/Wind Harmer
11.612
970627AG2-408 GEN
Solar/Wind Harmer
3.484
971333AH1-146 GEN
Solar/Wind Harmer
23.223
971335AH1-147 GEN
Solar/Wind Harmer
23.223
971341AH1-150 GEN
Solar/Wind Harmer
23.073
971343AH1-151 GEN
Solar/Wind Harmer
23.073
276872AE1-163_GEN1
Solar/Wind Harmer
0.003
274856ECOGROVE ;U1
Solar/Wind Harmer
0.269
276611AD2-172 GEN
Solar/Wind Harmer
0.003
938861AE1-114 GEN
Solar/Wind Harmer
6.415
944541AF1-119 GEN
Solar/Wind Harmer
0.756
960971AF2-388 GEN
Solar/Wind Harmer
6.621
274764LEE CO EC;5U
Adder
15.066
274765LEE CO EC;6U
Adder
15.066
274762LEE CO EC;3U
Adder
15.031
274763LEE CO EC;4U
Adder
14.889
276603SUBLETTE C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
6.653
276741O09 GEN1
Solar/Wind Harmer
0.396
276708O09 GEN2
Solar/Wind Harmer
0.396
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.436
276646AC1-214 GEN2
Solar/Wind Harmer
0.436
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
276782AC1-033 GEN
Solar/Wind Harmer
0.002
960611AF2-352 GEN
Solar/Wind Harmer
3.549
942221AE2-234 GEN
Solar/Wind Harmer
0.052
966841AG1-555 GEN
Solar/Wind Harmer
1.176
276763AC1-053 GEN1
Solar/Wind Harmer
0.002
276764AC1-053 GEN2
Solar/Wind Harmer
0.002
970241AG2-163 GEN
Solar/Wind Harmer
5.684
270599AE1-208 GEN
Solar/Wind Harmer
8.918
270031AE2-169
Solar/Wind Harmer
5.351
971613AH1-306 GEN
Solar/Wind Harmer
4.582
276916AD2-100_GEN
Solar/Wind Harmer
19.464
276911AD2-131_GEN
Solar/Wind Harmer
1.282
960441AF2-335 GEN
Solar/Wind Harmer
8.968
970825AG2-519 GEN
Solar/Wind Harmer
9.877
945391AF1-204 GEN
Solar/Wind Harmer
9.229
964611AG1-324 GEN
Solar/Wind Harmer
0.623
24379505HDWTR1G C
Solar/Wind Harmer
0.003
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
270201AC2-176 GEN
Solar/Wind Harmer
0.001
247621Y3-024
Adder
0.274
970623AG2-406 GEN
Solar/Wind Harmer
1.433
270383AD1-128 GEN
Solar/Wind Harmer
0.005
270444AC2-157 GEN1
Solar/Wind Harmer
0.003
971587AH1-292 GEN
Solar/Wind Harmer
5.417
270007AE1-245 C
Solar/Wind Harmer
0.002
970239AG2-162 GEN
Solar/Wind Harmer
1.798
246938BC-WTG3
Solar/Wind Harmer
0.26
246937BC-WTG2
Solar/Wind Harmer
0.291
970883AG2-550 GEN
Solar/Wind Harmer
7.146
970885AG2-551 GEN
Solar/Wind Harmer
2.382
270471AD2-092_GEN
Solar/Wind Helper
1.564
971673AH1-337 GEN
Solar/Wind Harmer
4.175
944201AF1-088_MTX
Adder
123.107
957141AF2-008_MTX
Adder
33.614
LAGNLTFEXP_LAGN->PJM
CLTF
12.118
TVALTFEXP_TVA->PJM
CLTF
4.605
CBM West 2LTFEXP_CBM-W2->PJM
CBM
109.586
NYPJM->LTFIMP_NY
CLTF
2.955
LGEELTFEXP_LGEE->PJM
CLTF
4
WECLTFEXP_WEC->PJM
CLTF
6.262
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.805
AG2-052LTFEXP_AG2-052->PJM
LTF
0.392
AH1-155LTFEXP_AH1-155->PJM
LTF
0.587
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.3
CBM West 1LTFEXP_CBM-W1->PJM
CBM
190.688
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.117
MECLTFEXP_MEC->PJM
CLTF
22.614
SIGELTFEXP_SIGE->PJM
CLTF
0.431

Details for 05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:132.35 %
Rating:1868.0 MVA
Rating Type:B
MVA to Mitigate:2472.27
MW Contribution:9.79
Bus #Bus NameTypeMW Contribution
24727205RPMNG3
50/50
3.292
971599AH1-298 GEN
50/50
10.333
24729505KEY G4
50/50
6.735
24653605MOTTVILLE
50/50
0.003
963791AG1-232 GEN
Solar/Wind Harmer
11.606
965041AG1-368 GEN
Solar/Wind Harmer
8.426
270071AF1-092 GEN
Solar/Wind Harmer
14.399
965051AG1-369 GEN
Solar/Wind Harmer
3.592
270024AE2-089 GEN
Solar/Wind Harmer
0.007
965101AG1-375 GEN
Solar/Wind Harmer
6.088
971771AH1-392 GEN
Solar/Wind Harmer
5.847
971347AH1-153 GEN
Solar/Wind Harmer
8.688
971619AH1-309 GEN
Solar/Wind Harmer
2.601
945581AF1-223 GEN
Solar/Wind Harmer
0
971769AH1-391 GEN
Solar/Wind Harmer
6.283
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971609AH1-304 GEN
Solar/Wind Harmer
0.89
274814UNIV PK N;0U
Adder
3.782
274807UNIV PK N;3U
Adder
3.774
274805UNIV PK N;1U
Adder
3.758
274811UNIV PK N;7U
Adder
3.75
270536AF1-215 GEN2
Solar/Wind Harmer
0.007
274775LINCOLN ;6U
Adder
6.292
274776LINCOLN ;7U
Adder
6.292
274777LINCOLN ;8U
Adder
6.292
972037AH1-567 GEN1
Adder
0.136
274827FISK ;RP
Adder
5.742
960591AF2-350 GEN
Solar/Wind Harmer
5.147
972227AH1-698 GEN1
Adder
1.919
274687WILL CNTY;4U
Adder
20.447
274687WILL CNTY;4U
Adder
20.447
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274675JOLIET 29;7U
Adder
22.401
274675JOLIET 29;7U
Adder
21.601
274728ELWOOD EC;5P
Adder
11.97
274731ELWOOD EC;2P
Adder
11.97
274733ELWOOD EC;3P
Adder
11.97
274735ELWOOD EC;4P
Adder
11.97
970833AG2-524 GEN
Solar/Wind Harmer
5.563
970833AG2-524 GEN
Solar/Wind Harmer
3.709
971611AH1-305 GEN
Solar/Wind Harmer
2.995
274746AC1-111 G10
Adder
4.021
274744AC1-111 GEN8
Adder
4.021
970289AG2-191 GEN
Solar/Wind Harmer
0.942
270594AE1-207 GEN
Solar/Wind Harmer
5.492
276868AE1-113 GEN
Solar/Wind Harmer
0.982
276882AE2-255 GEN
Solar/Wind Harmer
0.572
971177AH1-047 GEN
Solar/Wind Harmer
3.009
971411AH1-196 GEN
Solar/Wind Harmer
7.289
971675AH1-338 GEN
Solar/Wind Harmer
1.894
970115AG2-085 GEN
Solar/Wind Harmer
1.936
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24727105RPMNG2
50/50
3.32
970583AG2-370 GEN
50/50
2.809
960851AF2-376 GEN
50/50
2.105
24641605TWIN BRNCH
50/50
0.015
24727005RPMNG1
50/50
3.308
960861AF2-377 GEN
50/50
2.399
970521AG2-332 GEN
50/50
10.806
24639705ELKHART HY
50/50
0.149
965011AG1-365 GEN
Solar/Wind Harmer
13.763
270063AE2-323 C
Solar/Wind Harmer
0.006
247521TR3_G114
Solar/Wind Harmer
0.262
270246TR4_N_V150
Solar/Wind Harmer
0.046
944231AF1-091 GEN
Solar/Wind Harmer
1.854
24695305TIMB G C
Solar/Wind Harmer
0.002
965651AG1-433 GEN
Solar/Wind Harmer
1.839
958861AF2-177 GEN
Solar/Wind Harmer
2.638
945111AF1-176 GEN
Solar/Wind Harmer
10.578
270505AE1-170 C O1
Solar/Wind Harmer
6.07
945371AF1-202 GEN
Solar/Wind Harmer
0
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.97
970245AG2-165 GEN
Solar/Wind Harmer
2.307
970373AG2-245 GEN
Solar/Wind Harmer
11.147
274751CRETE EC ;1U
Adder
6.241
274754CRETE EC ;4U
Adder
6.241
274723RIVER EC ;12
Adder
13.527
274812UNIV PK N;8U
Adder
3.75
276164X3-005 C
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0.004
274773LINCOLN ;4U
Adder
6.292
274774LINCOLN ;5U
Adder
6.292
274801UNIV PARK;4U
Adder
4.307
276776AD2-060 GEN
Solar/Wind Harmer
0.537
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
6.671
941551AE2-152 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
22.401
274674JOLIET 9 ;6U
Adder
11.217
274732ELWOOD EC;7P
Adder
11.97
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
6.288
274745AC1-111 GEN9
Adder
4.021
276691AA1-018 GEN1
Solar/Wind Harmer
0.604
274682WAUKEGAN ;7U
Adder
12.782
970291AG2-192 GEN
Solar/Wind Harmer
0.645
274828WAUKEGAN ;BP
Adder
7.846
270005AE1-210 C O1
Solar/Wind Harmer
1.068
965031AG1-367 GEN
Solar/Wind Harmer
4.929
962781AG1-127 GEN
Solar/Wind Harmer
4.676
939401AE1-172 GEN
Solar/Wind Harmer
3.674
276901AD2-066 C O1
Solar/Wind Harmer
0.005
270032AE2-172
Solar/Wind Harmer
3.269
274872LEEDK;1U
Solar/Wind Harmer
0.003
971997AH1-543 GEN
Solar/Wind Harmer
2.559
276861AD2-134 GEN
Solar/Wind Harmer
0.087
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
24791305MDL-5G
Solar/Wind Harmer
0.001
957471AF2-041 GEN
Solar/Wind Harmer
14.477
959081AF2-199 GEN
Solar/Wind Harmer
4.826
971067AG2-660 GEN
Solar/Wind Harmer
1.609
274822ROCKFORD ;11
Adder
13.533
970825AG2-519 GEN
Solar/Wind Harmer
1.705
972235AH1-702 GEN1
Adder
1.734
970819AG2-516 GEN
Solar/Wind Harmer
5.74
970569AG2-363 GEN
Solar/Wind Harmer
14.338
971475AH1-234 GEN
Solar/Wind Harmer
2.315
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
6.304
274766LEE CO EC;7U
Adder
6.23
276903AD2-071 C
Solar/Wind Harmer
5.249
276158O29GEN2
Solar/Wind Harmer
0.001
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.002
274877BISHOP HL;1U
Solar/Wind Harmer
0.156
276726Z2-087_GEN
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
6.437
274854TWINGROVE;U2
Solar/Wind Harmer
0.002
972175AH1-670 GEN
Solar/Wind Harmer
3.624
963741AG1-226 GEN
Solar/Wind Harmer
10.327
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
3.19
247536S-71 GEN
Solar/Wind Harmer
0.173
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
1.654
276615X2-022 GEN
Solar/Wind Harmer
0.044
965911AG1-460 GEN
Solar/Wind Harmer
0.808
24728605AND G2
Adder
2.043
970773AG2-487 GEN
Solar/Wind Harmer
0.609
270445AC2-157 GEN2
Solar/Wind Harmer
0.001
970333AG2-219 GEN
Solar/Wind Harmer
2.215
246936BC-WTG1
Solar/Wind Helper
10.895
270462AD2-086
Solar/Wind Helper
3.714
270223U2-072_GEN1
Solar/Wind Helper
0.871
270578AF1-285 GEN2
Solar/Wind Helper
0.59
270391AF1-285 GEN3
Solar/Wind Helper
0.59
247522W1-056 GEN
Solar/Wind Helper
1.168
960841AF2-375 GEN
Solar/Wind Helper
1.175
270349AD2-093_GEN
Solar/Wind Helper
0.85
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
9.652
274823ROCKFORD ;21
Adder
13.435
276612AE2-035 GEN
Solar/Wind Harmer
0.001
926823AC1-168 GEN
Solar/Wind Harmer
0.811
970169AG2-114 GEN
Solar/Wind Harmer
4.764
971681AH1-341 GEN
Solar/Wind Harmer
7.643
971549AH1-272 GEN
Solar/Wind Harmer
9.793
961011AF2-392 GEN
Solar/Wind Harmer
2.754
957751AF2-069 GEN
Solar/Wind Harmer
0.154
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
276655WTG1_EQ
Solar/Wind Harmer
0.002
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
4.828
941731AE2-173 GEN
Solar/Wind Harmer
3.831
946321AF1-296 GEN
Solar/Wind Harmer
2.545
963841AG1-237 GEN
Solar/Wind Harmer
1.949
270240V3-007_GEN2
Solar/Wind Harmer
0.001
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.156
276848AB2-070 GEN3
Solar/Wind Harmer
0.155
270543AE2-219 C
Solar/Wind Harmer
0.002
944221AF1-090 GEN
Solar/Wind Harmer
2.279
971029AG2-637 GEN
Solar/Wind Harmer
5.242
971673AH1-337 GEN
Solar/Wind Harmer
2.175
247607V1-011 GEN
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Helper
8.613
270317AD1-130_GEN
Solar/Wind Helper
4.113
966831AG1-554 GEN
Solar/Wind Helper
0.876
270284AF1-227 GEN1
Solar/Wind Helper
1.876
270286AF1-227 GEN2
Solar/Wind Helper
0.688
270287AF1-227 GEN3
Solar/Wind Helper
0.688
270499AE1-146 GEN
Solar/Wind Helper
1.952
945641AF1-229 GEN
Solar/Wind Helper
0.937
959331AF2-224 GEN
Solar/Wind Harmer
9.634
965021AG1-366 GEN
Solar/Wind Harmer
4.588
970031AG2-029 GEN
Solar/Wind Harmer
5.463
270043AE2-236 GEN
Solar/Wind Harmer
5.191
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.046
944531AF1-118 GEN
Solar/Wind Harmer
31.488
971617AH1-308 GEN
Solar/Wind Harmer
5.166
247643Z2-116 C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
4.805
970349AG2-230 GEN
Solar/Wind Harmer
8.688
24642205MAYFLWER
Adder
0.524
24441205WTRV SLR C
Solar/Wind Harmer
0
970513AG2-328 GEN
Solar/Wind Harmer
2.307
970517AG2-330 GEN
Solar/Wind Harmer
13.84
274752CRETE EC ;2U
Adder
6.241
274753CRETE EC ;3U
Adder
6.241
274724RIVER EC ;11
Adder
13.364
247604X1-042
Adder
0.313
270535AF1-215 GEN1
Solar/Wind Harmer
0.007
274772LINCOLN ;3U
Adder
6.292
274802UNIV PARK;5U
Adder
4.319
274826FISK ;BP
Adder
8.102
274800UNIV PARK;3U
Adder
4.307
972038AH1-567 GEN2
Adder
0.27
276806AD2-047 C O1
Solar/Wind Harmer
2.917
970941AG2-585 GEN
Solar/Wind Harmer
6.434
964401AG1-302 GEN
Solar/Wind Harmer
0.001
972228AH1-698 GEN2
Adder
2.725
970707AG2-453 GEN
Solar/Wind Harmer
16.709
276897AD1-100 C
Solar/Wind Harmer
0.007
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
21.601
276893AG1-478 C
Solar/Wind Harmer
0.201
274730ELWOOD EC;6P
Adder
11.97
274734ELWOOD EC;8P
Adder
11.97
274736ELWOOD EC;9P
Adder
11.97
274729ELWOOD EC;1P
Adder
11.97
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
943121AE2-341 GEN
Solar/Wind Harmer
8.419
943591AF1-030 GEN
Solar/Wind Harmer
5.599
247642Z2-115 C
Solar/Wind Harmer
0.002
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
12.782
970289AG2-191 GEN
Solar/Wind Harmer
0.545
970291AG2-192 GEN
Solar/Wind Harmer
0.496
958821AF2-173 GEN
Solar/Wind Harmer
6.901
270004AE1-209 GEN
Solar/Wind Harmer
1.068
276805AD2-038 GEN
Solar/Wind Harmer
0.001
274872LEEDK;1U
Solar/Wind Harmer
0.18
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.518
274855GSG-6 ;RU
Solar/Wind Harmer
0.178
274850MENDOTA H;RU
Solar/Wind Harmer
0.057
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.087
276889AE2-281 GEN
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
4.834
959091AF2-200 GEN
Solar/Wind Harmer
9.652
972236AH1-702 GEN2
Adder
1.508
970571AG2-364 GEN
Solar/Wind Harmer
9.558
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
6.304
274767LEE CO EC;8U
Adder
6.23
946031AF1-268 GEN
Solar/Wind Harmer
4.492
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
7.069
276157O29GEN1
Solar/Wind Harmer
0.755
274878BISHOP HL;2U
Solar/Wind Harmer
0.156
942111AE2-223 GEN
Solar/Wind Harmer
1.494
965931AG1-462 GEN
Solar/Wind Harmer
11.522
274853TWINGROVE;U1
Solar/Wind Harmer
0.002
965091AG1-374 GEN
Solar/Wind Harmer
13.551
959611AF2-252 GEN
Solar/Wind Harmer
1.506
270437AC2-090 C
Solar/Wind Harmer
0.002
276686W4-005 GEN3
Solar/Wind Harmer
0.001
276668AB2-070 GEN1
Solar/Wind Harmer
0.156
971993AH1-541 GEN
Solar/Wind Harmer
1.971
276621W2-048 GEN
Solar/Wind Harmer
0.211
276838X2-022 GEN2
Solar/Wind Harmer
0.236
942481AE2-261 GEN
Solar/Wind Harmer
12.085
970193AG2-126 GEN
Solar/Wind Harmer
5.861
270404AC1-167 GEN
Solar/Wind Harmer
0.002
270258AD1-119 GEN
Solar/Wind Harmer
0.001
24728705AND G3
Adder
4.272
24728505AND G1
Adder
2.043
270356AE2-297 GEN
Solar/Wind Harmer
0.005
970243AG2-164 GEN
Solar/Wind Harmer
1.812
970519AG2-331 GEN
Solar/Wind Harmer
8.054
970699AG2-449 GEN
Solar/Wind Harmer
0.774
270485AE1-090_GEN
Solar/Wind Helper
0.323
942871AE2-306 GEN
Solar/Wind Helper
0.443
270541AE2-072 C
Solar/Wind Helper
0.932
970615AG2-402 GEN
50/50
4.588
24729405KEY G3
50/50
0.368
24729305KEY G2
50/50
0.361
24729205KEY G1
50/50
0.36
247620Y3-023
50/50
0.463
970611AG2-400 GEN
Solar/Wind Harmer
13.763
970627AG2-408 GEN
Solar/Wind Harmer
4.129
942221AE2-234 GEN
Solar/Wind Harmer
0.034
944541AF1-119 GEN
Solar/Wind Harmer
0.42
960971AF2-388 GEN
Solar/Wind Harmer
3.679
270216AD2-079_GEN
Solar/Wind Harmer
0.001
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
11.557
961051AF2-396 GEN
Solar/Wind Harmer
7.705
270526AF1-158 GEN
Solar/Wind Harmer
0.007
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
6.887
965791AG1-447 GEN
Solar/Wind Harmer
5.051
270599AE1-208 GEN
Solar/Wind Harmer
4.993
270031AE2-169
Solar/Wind Harmer
2.996
970321AG2-212 GEN
Solar/Wind Harmer
2.307
274808UNIV PK N;4U
Adder
3.733
274770LINCOLN ;1U
Adder
6.292
274771LINCOLN ;2U
Adder
6.292
274803UNIV PARK;6U
Adder
4.319
274888KELLY CRK;1U
Solar/Wind Harmer
0.302
274887GEN-1.85
Solar/Wind Harmer
0.136
276843GEN-1.7
Solar/Wind Harmer
0.167
958011AF2-095 GEN
Solar/Wind Harmer
7.412
972259AH1-714 GEN
Adder
13.99
274674JOLIET 9 ;6U
Adder
11.217
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
971573AH1-285 GEN
Solar/Wind Harmer
0.931
958481AF2-142 GEN
Solar/Wind Harmer
7.482
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.675
274695ROCKY RD ;2P
Adder
7.922
274693ROCKY RD ;1P
Adder
7.844
274697ROCKY RD ;3P
Adder
2.152
274696ROCKY RD ;4P
Adder
8.109
274683WAUKEGAN ;8U
Adder
14.968
274683WAUKEGAN ;8U
Adder
12.617
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
962691AG1-118 GEN
Solar/Wind Harmer
14.776
958491AF2-143 GEN
Solar/Wind Harmer
7.388
970921AG2-575 GEN
Solar/Wind Harmer
4.913
970921AG2-575 GEN
Solar/Wind Harmer
1.638
971613AH1-306 GEN
Solar/Wind Harmer
2.354
274879MINONK ;1U
Solar/Wind Harmer
0.207
942991AE2-321 GEN
Solar/Wind Harmer
5.451
971333AH1-146 GEN
Solar/Wind Harmer
9.71
971335AH1-147 GEN
Solar/Wind Harmer
9.71
960441AF2-335 GEN
Solar/Wind Harmer
4.841
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
971341AH1-150 GEN
Solar/Wind Harmer
9.652
971343AH1-151 GEN
Solar/Wind Harmer
9.652
970825AG2-519 GEN
Solar/Wind Harmer
5.324
274856ECOGROVE ;U1
Solar/Wind Harmer
0.113
276611AD2-172 GEN
Solar/Wind Harmer
0.001
938861AE1-114 GEN
Solar/Wind Harmer
2.689
274764LEE CO EC;5U
Adder
6.319
274765LEE CO EC;6U
Adder
6.319
274762LEE CO EC;3U
Adder
6.304
274763LEE CO EC;4U
Adder
6.245
276603SUBLETTE C
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.354
270201AC2-176 GEN
Solar/Wind Harmer
0.001
972267AH1-718 GEN
Adder
2.793
276741O09 GEN1
Solar/Wind Harmer
0.166
276708O09 GEN2
Solar/Wind Harmer
0.166
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.183
276646AC1-214 GEN2
Solar/Wind Harmer
0.183
966841AG1-555 GEN
Solar/Wind Harmer
0.525
276782AC1-033 GEN
Solar/Wind Harmer
0.001
247621Y3-024
Adder
0.16
960611AF2-352 GEN
Solar/Wind Harmer
1.506
970241AG2-163 GEN
Solar/Wind Harmer
2.545
24379505HDWTR1G C
Solar/Wind Harmer
0.001
270209AC1-174_GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
270383AD1-128 GEN
Solar/Wind Harmer
0.002
276916AD2-100_GEN
Solar/Wind Harmer
8.413
276911AD2-131_GEN
Solar/Wind Harmer
0.554
970883AG2-550 GEN
Solar/Wind Harmer
3.912
970885AG2-551 GEN
Solar/Wind Harmer
1.304
945391AF1-204 GEN
Solar/Wind Harmer
4.152
970623AG2-406 GEN
Solar/Wind Harmer
0.681
270444AC2-157 GEN1
Solar/Wind Harmer
0.001
971587AH1-292 GEN
Solar/Wind Harmer
2.427
270007AE1-245 C
Solar/Wind Harmer
0.001
970239AG2-162 GEN
Solar/Wind Harmer
0.774
246938BC-WTG3
Solar/Wind Helper
11.083
246937BC-WTG2
Solar/Wind Helper
10.895
270224U2-072_GEN2
Solar/Wind Helper
0.871
270227U2-072_GEN3
Solar/Wind Helper
0.871
270228U2-072_GEN4
Solar/Wind Helper
0.871
270231U2-072_GEN5
Solar/Wind Helper
0.871
270471AD2-092_GEN
Solar/Wind Helper
0.85
253378AE2-206_GEN
Solar/Wind Helper
0.684
276820AF1-078_GEN
Solar/Wind Helper
0.319
241960AC2-195 GEN
Solar/Wind Helper
0.69
944201AF1-088_MTX
Adder
55.165
957141AF2-008_MTX
Adder
22.101
990792J1392
External Queue
5.474584102630615
990497J1323
External Queue
1.5914489030838013
LAGNLTFEXP_LAGN->PJM
CLTF
5.694
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.439
TVALTFEXP_TVA->PJM
CLTF
2.27
CBM West 2LTFEXP_CBM-W2->PJM
CBM
49.944
NYPJM->LTFIMP_NY
CLTF
1.265
LGEELTFEXP_LGEE->PJM
CLTF
1.782
WECLTFEXP_WEC->PJM
CLTF
2.624
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.056
AG2-052LTFEXP_AG2-052->PJM
LTF
0.17
AH1-155LTFEXP_AH1-155->PJM
LTF
0.255
CBM West 1LTFEXP_CBM-W1->PJM
CBM
69.309
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.744
MECLTFEXP_MEC->PJM
CLTF
9.656
SIGELTFEXP_SIGE->PJM
CLTF
0.197

Details for 05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer l/o AEP_P4_#7443_05DUMONT 765_A_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer
Contingency Name:
AEP_P4_#7443_05DUMONT 765_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.16 %
Rating:3097.0 MVA
Rating Type:B
MVA to Mitigate:3597.55
MW Contribution:21.94
Bus #Bus NameTypeMW Contribution
970583AG2-370 GEN
50/50
3.654
960851AF2-376 GEN
50/50
3.29
24727105RPMNG2
50/50
1.31
24641605TWIN BRNCH
50/50
0.024
944531AF1-118 GEN
Solar/Wind Harmer
69.986
270043AE2-236 GEN
Solar/Wind Harmer
10.796
959331AF2-224 GEN
Solar/Wind Harmer
18.221
965021AG1-366 GEN
Solar/Wind Harmer
4.237
970031AG2-029 GEN
Solar/Wind Harmer
49.52
270191TR4_S_V150
Solar/Wind Harmer
4.359
270247TR4_N_V136
Solar/Wind Harmer
1.236
958821AF2-173 GEN
Solar/Wind Harmer
19.357
270004AE1-209 GEN
Solar/Wind Harmer
7.556
971617AH1-308 GEN
Solar/Wind Harmer
7.974
247643Z2-116 C
Solar/Wind Harmer
0.094
945111AF1-176 GEN
Solar/Wind Harmer
7.419
946031AF1-268 GEN
Solar/Wind Harmer
10.671
24642205MAYFLWER
Adder
0.811
970349AG2-230 GEN
Solar/Wind Harmer
18.754
970289AG2-191 GEN
Solar/Wind Harmer
0.958
970291AG2-192 GEN
Solar/Wind Harmer
0.871
24441205WTRV SLR C
Solar/Wind Harmer
0.167
270437AC2-090 C
Solar/Wind Harmer
6.912
247642Z2-115 C
Solar/Wind Harmer
0.079
270044AE2-322 C
Solar/Wind Harmer
1.621
971599AH1-298 GEN
50/50
20.233
24729505KEY G4
50/50
13.359
24727205RPMNG3
50/50
1.299
24653605MOTTVILLE
50/50
0.005
270071AF1-092 GEN
Solar/Wind Harmer
28.446
958711AF2-162 GEN
Solar/Wind Harmer
1.798
965101AG1-375 GEN
Solar/Wind Harmer
17.237
945581AF1-223 GEN
Solar/Wind Harmer
7.354
963791AG1-232 GEN
Solar/Wind Harmer
21.417
965041AG1-368 GEN
Solar/Wind Harmer
15.714
965051AG1-369 GEN
Solar/Wind Harmer
7.257
270024AE2-089 GEN
Solar/Wind Harmer
6.437
970115AG2-085 GEN
Solar/Wind Harmer
5.221
971771AH1-392 GEN
Solar/Wind Harmer
11.61
944161AF1-084 GEN
Solar/Wind Harmer
2.8
270594AE1-207 GEN
Solar/Wind Harmer
18.528
971347AH1-153 GEN
Solar/Wind Harmer
18.754
965461AG1-414 GEN
Solar/Wind Harmer
2.831
970289AG2-191 GEN
Solar/Wind Harmer
2.373
270240V3-007_GEN2
Solar/Wind Harmer
7.66
971769AH1-391 GEN
Solar/Wind Harmer
12.335
961761AG1-017 GEN
Solar/Wind Harmer
0.526
960681AF2-359 GEN
Solar/Wind Harmer
4.523
24725505WLD G2 C
Solar/Wind Harmer
4.748
24699105WLD G1 C
Solar/Wind Harmer
4.693
957201AF2-014 GEN
Solar/Wind Harmer
5.389
270435AC2-044 GEN
Solar/Wind Harmer
2.377
971549AH1-272 GEN
Solar/Wind Harmer
21.937
247607V1-011 GEN
Solar/Wind Harmer
4.688
270536AF1-215 GEN2
Solar/Wind Harmer
5.134
274814UNIV PK N;0U
Adder
5.591
274807UNIV PK N;3U
Adder
5.579
274805UNIV PK N;1U
Adder
5.554
274811UNIV PK N;7U
Adder
5.542
958391AF2-133 GEN
Solar/Wind Harmer
9.99
972037AH1-567 GEN1
Adder
0.2
274827FISK ;RP
Adder
8.463
274775LINCOLN ;6U
Adder
6.747
274776LINCOLN ;7U
Adder
6.747
274777LINCOLN ;8U
Adder
6.747
960591AF2-350 GEN
Solar/Wind Harmer
10.866
972227AH1-698 GEN1
Adder
2.823
274687WILL CNTY;4U
Adder
30.105
274687WILL CNTY;4U
Adder
30.105
274675JOLIET 29;7U
Adder
32.967
274675JOLIET 29;7U
Adder
31.79
274728ELWOOD EC;5P
Adder
17.624
274731ELWOOD EC;2P
Adder
17.623
274733ELWOOD EC;3P
Adder
17.623
274735ELWOOD EC;4P
Adder
17.623
270543AE2-219 C
Solar/Wind Harmer
5.485
970833AG2-524 GEN
Solar/Wind Harmer
9.303
970833AG2-524 GEN
Solar/Wind Harmer
4.327
274746AC1-111 G10
Adder
5.907
274744AC1-111 GEN8
Adder
5.907
274823ROCKFORD ;21
Adder
19.792
270054AF2-122 C O1
Solar/Wind Helper
0.777
270284AF1-227 GEN1
Solar/Wind Helper
1.165
270286AF1-227 GEN2
Solar/Wind Helper
0.427
270404AC1-167 GEN
Solar/Wind Harmer
1.35
962031AG1-047 GEN
Solar/Wind Harmer
3.717
957741AF2-068 GEN
Solar/Wind Harmer
18.445
270258AD1-119 GEN
Solar/Wind Harmer
3.413
247604X1-042
Adder
0.507
270491AE1-102 GEN2
Solar/Wind Harmer
1.545
958091AF2-103 GEN
Solar/Wind Harmer
0.191
270535AF1-215 GEN1
Solar/Wind Harmer
5.134
972231SS25-0005
Solar/Wind Harmer
10.654
972181SS23-001
Solar/Wind Harmer
6.659
274752CRETE EC ;2U
Adder
5.487
274753CRETE EC ;3U
Adder
5.487
274724RIVER EC ;11
Adder
19.749
964401AG1-302 GEN
Solar/Wind Harmer
10.079
959141AF2-205 GEN
Solar/Wind Harmer
6.613
274802UNIV PARK;5U
Adder
6.37
274826FISK ;BP
Adder
11.941
274800UNIV PARK;3U
Adder
6.347
972038AH1-567 GEN2
Adder
0.397
274772LINCOLN ;3U
Adder
6.747
276772AC2-154 GEN
Solar/Wind Harmer
3.03
276806AD2-047 C O1
Solar/Wind Harmer
11.624
970941AG2-585 GEN
Solar/Wind Harmer
13.583
972228AH1-698 GEN2
Adder
4.009
970513AG2-328 GEN
Solar/Wind Harmer
19.29
970517AG2-330 GEN
Solar/Wind Harmer
17.496
274676JOLIET 29;8U
Adder
31.789
276897AD1-100 C
Solar/Wind Harmer
31.167
939351AE1-166 GEN
Solar/Wind Harmer
6.368
970707AG2-453 GEN
Solar/Wind Harmer
30.052
276893AG1-478 C
Solar/Wind Harmer
0.448
274730ELWOOD EC;6P
Adder
17.624
274734ELWOOD EC;8P
Adder
17.624
274736ELWOOD EC;9P
Adder
17.624
274729ELWOOD EC;1P
Adder
17.623
274682WAUKEGAN ;7U
Adder
18.807
972236AH1-702 GEN2
Adder
2.221
274760LEE CO EC;1U
Adder
9.299
274767LEE CO EC;8U
Adder
9.189
24728705AND G3
Adder
7.723
24728505AND G1
Adder
3.693
23906502RICHG2&3
Adder
0.873
960861AF2-377 GEN
50/50
3.382
970521AG2-332 GEN
50/50
16.176
24639705ELKHART HY
50/50
0.225
24727005RPMNG1
50/50
1.305
960791AF2-370 GEN
50/50
3.035
965011AG1-365 GEN
Solar/Wind Harmer
18.221
965651AG1-433 GEN
Solar/Wind Harmer
9.713
958861AF2-177 GEN
Solar/Wind Harmer
18.841
945371AF1-202 GEN
Solar/Wind Harmer
11.314
944231AF1-091 GEN
Solar/Wind Harmer
5.796
270063AE2-323 C
Solar/Wind Harmer
3.37
247521TR3_G114
Solar/Wind Harmer
4.887
270246TR4_N_V150
Solar/Wind Harmer
1.236
24695305TIMB G C
Solar/Wind Harmer
7.786
270005AE1-210 C O1
Solar/Wind Harmer
7.556
965031AG1-367 GEN
Solar/Wind Harmer
13.826
945111AF1-176 GEN
Solar/Wind Harmer
23.41
970825AG2-519 GEN
Solar/Wind Harmer
3.074
270505AE1-170 C O1
Solar/Wind Harmer
19.365
270449AD2-020 GEN
Solar/Wind Harmer
3.585
943021AE2-325 GEN
Solar/Wind Harmer
4.658
270032AE2-172
Solar/Wind Harmer
5.863
965421AG1-410 GEN
Solar/Wind Harmer
37.469
970291AG2-192 GEN
Solar/Wind Harmer
1.623
942081AE2-220 GEN
Solar/Wind Harmer
7.915
270239V3-007_GEN1
Solar/Wind Harmer
2.13
276903AD2-071 C
Solar/Wind Harmer
12.035
246936BC-WTG1
Solar/Wind Harmer
4.65
270489AE1-102 GEN1
Solar/Wind Harmer
1.545
970373AG2-245 GEN
Solar/Wind Harmer
24.186
247536S-71 GEN
Solar/Wind Harmer
4.625
270055AF2-134 C O1
Solar/Wind Harmer
3.422
274751CRETE EC ;1U
Adder
5.487
274754CRETE EC ;4U
Adder
5.487
274723RIVER EC ;12
Adder
19.991
958381AF2-132 GEN
Solar/Wind Harmer
10.079
964861AG1-349 GEN
Solar/Wind Harmer
8.717
971917AH1-482 GEN
Solar/Wind Harmer
10.06
274812UNIV PK N;8U
Adder
5.542
276164X3-005 C
Solar/Wind Harmer
0.775
274801UNIV PARK;4U
Adder
6.347
972207SS24-0001
Solar/Wind Harmer
23.99
274773LINCOLN ;4U
Adder
6.747
274774LINCOLN ;5U
Adder
6.747
276776AD2-060 GEN
Solar/Wind Harmer
0.459
940581AE2-045 GEN
Solar/Wind Harmer
11.063
971605AH1-302 GEN
Solar/Wind Harmer
9.46
970245AG2-165 GEN
Solar/Wind Harmer
19.29
274676JOLIET 29;8U
Adder
32.967
941551AE2-152 GEN
Solar/Wind Harmer
4.871
274674JOLIET 9 ;6U
Adder
16.509
274732ELWOOD EC;7P
Adder
17.624
274871GR RIDGE ;2U
Solar/Wind Harmer
8.188
274745AC1-111 GEN9
Adder
5.907
274682WAUKEGAN ;7U
Adder
18.807
274828WAUKEGAN ;BP
Adder
11.544
274822ROCKFORD ;11
Adder
19.937
972235AH1-702 GEN1
Adder
2.555
274761LEE CO EC;2U
Adder
9.299
274766LEE CO EC;7U
Adder
9.189
24728605AND G2
Adder
3.693
972301AH1-735 GEN
Adder
4.399
23906402RICHG1
Adder
0.88
23906502RICHG2&3
Adder
0.873
970091AG2-072 GEN
Adder
0.148
270349AD2-093_GEN
Solar/Wind Helper
1.076
270287AF1-227 GEN3
Solar/Wind Helper
0.427
270520AE2-214 GEN
Solar/Wind Helper
2.4
24729405KEY G3
50/50
0.729
24729305KEY G2
50/50
0.717
24729205KEY G1
50/50
0.713
970615AG2-402 GEN
50/50
4.237
247620Y3-023
50/50
0.69
970611AG2-400 GEN
Solar/Wind Harmer
18.221
944541AF1-119 GEN
Solar/Wind Harmer
7.444
960971AF2-388 GEN
Solar/Wind Harmer
19.425
942221AE2-234 GEN
Solar/Wind Harmer
1.156
270599AE1-208 GEN
Solar/Wind Harmer
11.731
270031AE2-169
Solar/Wind Harmer
11.731
270216AD2-079_GEN
Solar/Wind Harmer
0.818
960441AF2-335 GEN
Solar/Wind Harmer
13.052
970825AG2-519 GEN
Solar/Wind Harmer
13.779
960981AF2-389 GEN
Solar/Wind Harmer
1.96
957891AF2-083 GEN
Solar/Wind Harmer
4.37
961051AF2-396 GEN
Solar/Wind Harmer
20.497
961051AF2-396 GEN
Solar/Wind Harmer
9.534
270526AF1-158 GEN
Solar/Wind Harmer
5.655
964611AG1-324 GEN
Solar/Wind Harmer
1.464
964611AG1-324 GEN
Solar/Wind Harmer
0.65
24379505HDWTR1G C
Solar/Wind Harmer
9.79
270209AC1-174_GEN
Solar/Wind Harmer
6.909
926881AC1-175 GEN
Solar/Wind Harmer
6.909
24441505OLIV SLR
Solar/Wind Harmer
0.165
270201AC2-176 GEN
Solar/Wind Harmer
6.321
965681AG1-436 GEN
Solar/Wind Harmer
14.967
965791AG1-447 GEN
Solar/Wind Harmer
7.657
246938BC-WTG3
Solar/Wind Harmer
4.73
246937BC-WTG2
Solar/Wind Harmer
4.65
247621Y3-024
Adder
0.286
270007AE1-245 C
Solar/Wind Harmer
7.028
270383AD1-128 GEN
Solar/Wind Harmer
6.977
274808UNIV PK N;4U
Adder
5.518
942801AE2-298 GEN
Solar/Wind Harmer
1.657
274803UNIV PARK;6U
Adder
6.37
274770LINCOLN ;1U
Adder
6.747
274771LINCOLN ;2U
Adder
6.747
274888KELLY CRK;1U
Solar/Wind Harmer
6.415
274887GEN-1.85
Solar/Wind Harmer
5.792
276843GEN-1.7
Solar/Wind Harmer
0.623
958011AF2-095 GEN
Solar/Wind Harmer
15.647
970321AG2-212 GEN
Solar/Wind Harmer
19.29
972259AH1-714 GEN
Adder
20.537
274674JOLIET 9 ;6U
Adder
16.509
970883AG2-550 GEN
Solar/Wind Harmer
10.712
970885AG2-551 GEN
Solar/Wind Harmer
2.491
274847GR RIDGE ;BU
Solar/Wind Harmer
5.386
945421AF1-207 GEN
Solar/Wind Harmer
14.883
274696ROCKY RD ;4P
Adder
11.924
274695ROCKY RD ;2P
Adder
11.649
274693ROCKY RD ;1P
Adder
11.534
274697ROCKY RD ;3P
Adder
3.165
274683WAUKEGAN ;8U
Adder
22.024
274683WAUKEGAN ;8U
Adder
18.565
274764LEE CO EC;5U
Adder
9.321
274765LEE CO EC;6U
Adder
9.321
274762LEE CO EC;3U
Adder
9.299
274763LEE CO EC;4U
Adder
9.211
972267AH1-718 GEN
Adder
4.123
24728805RICHG1
Adder
3.034
24728905RICHG2
Adder
3.034
270471AD2-092_GEN
Solar/Wind Helper
1.076
946101AF1-275 GEN
Solar/Wind Helper
0.301
957841AF2-078 GEN
Solar/Wind Harmer
2.133
944201AF1-088_MTX
Adder
86.769
957141AF2-008_MTX
Adder
43.385
990497J1323
External Queue
1.917611837387085
LAGNLTFEXP_LAGN->PJM
CLTF
8.254
TVALTFEXP_TVA->PJM
CLTF
3.263
CBM West 2LTFEXP_CBM-W2->PJM
CBM
76.552
NYPJM->LTFIMP_NY
CLTF
1.999
LGEELTFEXP_LGEE->PJM
CLTF
3.213
WECLTFEXP_WEC->PJM
CLTF
3.867
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.533
AG2-052LTFEXP_AG2-052->PJM
LTF
0.256
AH1-155LTFEXP_AH1-155->PJM
LTF
0.384
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.192
CBM West 1LTFEXP_CBM-W1->PJM
CBM
126.594
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.211
MECLTFEXP_MEC->PJM
CLTF
14.346
SIGELTFEXP_SIGE->PJM
CLTF
0.331

Details for 05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer l/o AEP_P4_#7442_05SORENS 765_K2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer
Contingency Name:
AEP_P4_#7442_05SORENS 765_K2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.09 %
Rating:3097.0 MVA
Rating Type:B
MVA to Mitigate:3595.31
MW Contribution:21.78
Bus #Bus NameTypeMW Contribution
971599AH1-298 GEN
50/50
20.218
24729505KEY G4
50/50
13.356
24727205RPMNG3
50/50
1.297
24653605MOTTVILLE
50/50
0.005
270071AF1-092 GEN
Solar/Wind Harmer
28.449
958711AF2-162 GEN
Solar/Wind Harmer
1.798
965101AG1-375 GEN
Solar/Wind Harmer
17.236
945581AF1-223 GEN
Solar/Wind Harmer
7.355
963791AG1-232 GEN
Solar/Wind Harmer
21.4
965041AG1-368 GEN
Solar/Wind Harmer
15.694
965051AG1-369 GEN
Solar/Wind Harmer
7.247
270024AE2-089 GEN
Solar/Wind Harmer
6.436
970115AG2-085 GEN
Solar/Wind Harmer
5.224
971771AH1-392 GEN
Solar/Wind Harmer
11.55
270594AE1-207 GEN
Solar/Wind Harmer
18.557
970583AG2-370 GEN
50/50
3.65
960851AF2-376 GEN
50/50
3.285
24727105RPMNG2
50/50
1.308
24641605TWIN BRNCH
50/50
0.023
944531AF1-118 GEN
Solar/Wind Harmer
69.966
270043AE2-236 GEN
Solar/Wind Harmer
10.785
959331AF2-224 GEN
Solar/Wind Harmer
18.199
965021AG1-366 GEN
Solar/Wind Harmer
4.232
970031AG2-029 GEN
Solar/Wind Harmer
49.401
270191TR4_S_V150
Solar/Wind Harmer
4.354
270247TR4_N_V136
Solar/Wind Harmer
1.235
958821AF2-173 GEN
Solar/Wind Harmer
19.364
270004AE1-209 GEN
Solar/Wind Harmer
7.559
971617AH1-308 GEN
Solar/Wind Harmer
7.972
247643Z2-116 C
Solar/Wind Harmer
0.093
945111AF1-176 GEN
Solar/Wind Harmer
7.359
946031AF1-268 GEN
Solar/Wind Harmer
10.676
24642205MAYFLWER
Adder
0.806
970349AG2-230 GEN
Solar/Wind Harmer
18.804
970289AG2-191 GEN
Solar/Wind Harmer
0.96
970291AG2-192 GEN
Solar/Wind Harmer
0.873
247642Z2-115 C
Solar/Wind Harmer
0.079
960861AF2-377 GEN
50/50
3.377
970521AG2-332 GEN
50/50
16.09
24639705ELKHART HY
50/50
0.224
24727005RPMNG1
50/50
1.303
960791AF2-370 GEN
50/50
3.037
965011AG1-365 GEN
Solar/Wind Harmer
18.199
965651AG1-433 GEN
Solar/Wind Harmer
9.712
958861AF2-177 GEN
Solar/Wind Harmer
18.84
945371AF1-202 GEN
Solar/Wind Harmer
11.315
944231AF1-091 GEN
Solar/Wind Harmer
5.785
270063AE2-323 C
Solar/Wind Harmer
3.359
247521TR3_G114
Solar/Wind Harmer
4.88
270246TR4_N_V150
Solar/Wind Harmer
1.235
24695305TIMB G C
Solar/Wind Harmer
7.775
270005AE1-210 C O1
Solar/Wind Harmer
7.559
965031AG1-367 GEN
Solar/Wind Harmer
13.832
970825AG2-519 GEN
Solar/Wind Harmer
3.076
945111AF1-176 GEN
Solar/Wind Harmer
23.221
270505AE1-170 C O1
Solar/Wind Harmer
19.191
270449AD2-020 GEN
Solar/Wind Harmer
3.551
943021AE2-325 GEN
Solar/Wind Harmer
4.614
270032AE2-172
Solar/Wind Harmer
5.873
970291AG2-192 GEN
Solar/Wind Harmer
1.626
965421AG1-410 GEN
Solar/Wind Harmer
37.41
942081AE2-220 GEN
Solar/Wind Harmer
7.919
270239V3-007_GEN1
Solar/Wind Harmer
2.131
276903AD2-071 C
Solar/Wind Harmer
12.055
246936BC-WTG1
Solar/Wind Harmer
4.642
270489AE1-102 GEN1
Solar/Wind Harmer
1.542
970373AG2-245 GEN
Solar/Wind Harmer
24.151
247536S-71 GEN
Solar/Wind Harmer
4.626
270055AF2-134 C O1
Solar/Wind Harmer
3.42
274751CRETE EC ;1U
Adder
5.501
24729405KEY G3
50/50
0.729
24729305KEY G2
50/50
0.717
24729205KEY G1
50/50
0.713
970615AG2-402 GEN
50/50
4.232
247620Y3-023
50/50
0.687
970611AG2-400 GEN
Solar/Wind Harmer
18.199
944541AF1-119 GEN
Solar/Wind Harmer
7.443
960971AF2-388 GEN
Solar/Wind Harmer
19.424
942221AE2-234 GEN
Solar/Wind Harmer
1.156
270599AE1-208 GEN
Solar/Wind Harmer
11.735
270031AE2-169
Solar/Wind Harmer
11.735
270216AD2-079_GEN
Solar/Wind Harmer
0.814
960441AF2-335 GEN
Solar/Wind Harmer
13.06
970825AG2-519 GEN
Solar/Wind Harmer
13.786
960981AF2-389 GEN
Solar/Wind Harmer
1.943
957891AF2-083 GEN
Solar/Wind Harmer
4.334
961051AF2-396 GEN
Solar/Wind Harmer
20.314
961051AF2-396 GEN
Solar/Wind Harmer
9.449
964611AG1-324 GEN
Solar/Wind Harmer
1.464
964611AG1-324 GEN
Solar/Wind Harmer
0.65
270526AF1-158 GEN
Solar/Wind Harmer
5.631
24379505HDWTR1G C
Solar/Wind Harmer
9.795
270209AC1-174_GEN
Solar/Wind Harmer
6.913
926881AC1-175 GEN
Solar/Wind Harmer
6.913
270201AC2-176 GEN
Solar/Wind Harmer
6.323
24441505OLIV SLR
Solar/Wind Harmer
0.165
965681AG1-436 GEN
Solar/Wind Harmer
14.927
965791AG1-447 GEN
Solar/Wind Harmer
7.637
247621Y3-024
Adder
0.286
246938BC-WTG3
Solar/Wind Harmer
4.722
246937BC-WTG2
Solar/Wind Harmer
4.642
270007AE1-245 C
Solar/Wind Harmer
7.017
270383AD1-128 GEN
Solar/Wind Harmer
6.981
274808UNIV PK N;4U
Adder
5.536
274803UNIV PARK;6U
Adder
6.395
274770LINCOLN ;1U
Adder
6.786
274771LINCOLN ;2U
Adder
6.786
942801AE2-298 GEN
Solar/Wind Harmer
1.654
970321AG2-212 GEN
Solar/Wind Harmer
19.508
274888KELLY CRK;1U
Solar/Wind Harmer
6.442
274887GEN-1.85
Solar/Wind Harmer
5.816
276843GEN-1.7
Solar/Wind Harmer
0.626
958011AF2-095 GEN
Solar/Wind Harmer
15.713
972259AH1-714 GEN
Adder
20.637
274674JOLIET 9 ;6U
Adder
16.583
970883AG2-550 GEN
Solar/Wind Harmer
10.716
970885AG2-551 GEN
Solar/Wind Harmer
2.492
274847GR RIDGE ;BU
Solar/Wind Harmer
5.412
945421AF1-207 GEN
Solar/Wind Harmer
14.915
274695ROCKY RD ;2P
Adder
11.705
274693ROCKY RD ;1P
Adder
11.59
274697ROCKY RD ;3P
Adder
3.18
274696ROCKY RD ;4P
Adder
11.982
274683WAUKEGAN ;8U
Adder
22.127
274683WAUKEGAN ;8U
Adder
18.652
274764LEE CO EC;5U
Adder
9.365
274765LEE CO EC;6U
Adder
9.365
274762LEE CO EC;3U
Adder
9.343
274763LEE CO EC;4U
Adder
9.255
972267AH1-718 GEN
Adder
4.143
24728805RICHG1
Adder
3.037
24728905RICHG2
Adder
3.037
270471AD2-092_GEN
Solar/Wind Helper
1.077
946101AF1-275 GEN
Solar/Wind Helper
0.301
957841AF2-078 GEN
Solar/Wind Harmer
2.137
270437AC2-090 C
Solar/Wind Harmer
6.916
270044AE2-322 C
Solar/Wind Harmer
1.618
270404AC1-167 GEN
Solar/Wind Harmer
1.347
962031AG1-047 GEN
Solar/Wind Harmer
3.717
957741AF2-068 GEN
Solar/Wind Harmer
18.448
24441205WTRV SLR C
Solar/Wind Harmer
0.165
270258AD1-119 GEN
Solar/Wind Harmer
3.407
247604X1-042
Adder
0.501
270491AE1-102 GEN2
Solar/Wind Harmer
1.542
958091AF2-103 GEN
Solar/Wind Harmer
0.191
270535AF1-215 GEN1
Solar/Wind Harmer
5.131
972231SS25-0005
Solar/Wind Harmer
10.68
972181SS23-001
Solar/Wind Harmer
6.675
274752CRETE EC ;2U
Adder
5.501
274753CRETE EC ;3U
Adder
5.501
274724RIVER EC ;11
Adder
19.816
964401AG1-302 GEN
Solar/Wind Harmer
10.08
274802UNIV PARK;5U
Adder
6.395
274826FISK ;BP
Adder
11.989
959141AF2-205 GEN
Solar/Wind Harmer
6.618
274772LINCOLN ;3U
Adder
6.786
274800UNIV PARK;3U
Adder
6.373
972038AH1-567 GEN2
Adder
0.399
970513AG2-328 GEN
Solar/Wind Harmer
19.508
970517AG2-330 GEN
Solar/Wind Harmer
17.693
276772AC2-154 GEN
Solar/Wind Harmer
3.043
276806AD2-047 C O1
Solar/Wind Harmer
11.673
970941AG2-585 GEN
Solar/Wind Harmer
13.64
972228AH1-698 GEN2
Adder
4.027
274676JOLIET 29;8U
Adder
31.93
276897AD1-100 C
Solar/Wind Harmer
31.315
939351AE1-166 GEN
Solar/Wind Harmer
6.398
970707AG2-453 GEN
Solar/Wind Harmer
30.212
276893AG1-478 C
Solar/Wind Harmer
0.45
274730ELWOOD EC;6P
Adder
17.702
274734ELWOOD EC;8P
Adder
17.702
274736ELWOOD EC;9P
Adder
17.702
274729ELWOOD EC;1P
Adder
17.701
274682WAUKEGAN ;7U
Adder
18.895
972236AH1-702 GEN2
Adder
2.232
274760LEE CO EC;1U
Adder
9.343
274767LEE CO EC;8U
Adder
9.233
24728705AND G3
Adder
7.738
24728505AND G1
Adder
3.7
23906502RICHG2&3
Adder
0.869
944161AF1-084 GEN
Solar/Wind Harmer
2.773
971347AH1-153 GEN
Solar/Wind Harmer
18.804
965461AG1-414 GEN
Solar/Wind Harmer
2.837
970289AG2-191 GEN
Solar/Wind Harmer
2.377
270240V3-007_GEN2
Solar/Wind Harmer
7.664
961761AG1-017 GEN
Solar/Wind Harmer
0.526
971769AH1-391 GEN
Solar/Wind Harmer
12.286
24725505WLD G2 C
Solar/Wind Harmer
4.756
24699105WLD G1 C
Solar/Wind Harmer
4.7
960681AF2-359 GEN
Solar/Wind Harmer
4.511
957201AF2-014 GEN
Solar/Wind Harmer
5.38
270435AC2-044 GEN
Solar/Wind Harmer
2.373
247607V1-011 GEN
Solar/Wind Harmer
4.68
971549AH1-272 GEN
Solar/Wind Harmer
21.784
270536AF1-215 GEN2
Solar/Wind Harmer
5.131
274814UNIV PK N;0U
Adder
5.609
274807UNIV PK N;3U
Adder
5.596
274805UNIV PK N;1U
Adder
5.572
274811UNIV PK N;7U
Adder
5.56
958391AF2-133 GEN
Solar/Wind Harmer
9.994
972037AH1-567 GEN1
Adder
0.201
274827FISK ;RP
Adder
8.497
274775LINCOLN ;6U
Adder
6.786
274776LINCOLN ;7U
Adder
6.786
274777LINCOLN ;8U
Adder
6.786
960591AF2-350 GEN
Solar/Wind Harmer
10.912
972227AH1-698 GEN1
Adder
2.835
274687WILL CNTY;4U
Adder
30.235
274687WILL CNTY;4U
Adder
30.235
274675JOLIET 29;7U
Adder
33.113
274675JOLIET 29;7U
Adder
31.93
274728ELWOOD EC;5P
Adder
17.702
274731ELWOOD EC;2P
Adder
17.701
274733ELWOOD EC;3P
Adder
17.701
274735ELWOOD EC;4P
Adder
17.701
270543AE2-219 C
Solar/Wind Harmer
5.487
970833AG2-524 GEN
Solar/Wind Harmer
9.348
970833AG2-524 GEN
Solar/Wind Harmer
4.348
274746AC1-111 G10
Adder
5.936
274744AC1-111 GEN8
Adder
5.936
274823ROCKFORD ;21
Adder
19.887
270054AF2-122 C O1
Solar/Wind Helper
0.778
270284AF1-227 GEN1
Solar/Wind Helper
1.167
270286AF1-227 GEN2
Solar/Wind Helper
0.428
270287AF1-227 GEN3
Solar/Wind Helper
0.428
270520AE2-214 GEN
Solar/Wind Helper
2.4
274754CRETE EC ;4U
Adder
5.501
274723RIVER EC ;12
Adder
20.057
958381AF2-132 GEN
Solar/Wind Harmer
10.08
274812UNIV PK N;8U
Adder
5.56
964861AG1-349 GEN
Solar/Wind Harmer
8.718
971917AH1-482 GEN
Solar/Wind Harmer
10.061
276164X3-005 C
Solar/Wind Harmer
0.778
972207SS24-0001
Solar/Wind Harmer
24.127
274773LINCOLN ;4U
Adder
6.786
274774LINCOLN ;5U
Adder
6.786
274801UNIV PARK;4U
Adder
6.373
970245AG2-165 GEN
Solar/Wind Harmer
19.508
276776AD2-060 GEN
Solar/Wind Harmer
0.461
940581AE2-045 GEN
Solar/Wind Harmer
11.076
971605AH1-302 GEN
Solar/Wind Harmer
9.471
274676JOLIET 29;8U
Adder
33.113
941551AE2-152 GEN
Solar/Wind Harmer
4.894
274674JOLIET 9 ;6U
Adder
16.583
274732ELWOOD EC;7P
Adder
17.702
274871GR RIDGE ;2U
Solar/Wind Harmer
8.227
274745AC1-111 GEN9
Adder
5.936
274682WAUKEGAN ;7U
Adder
18.895
274828WAUKEGAN ;BP
Adder
11.599
274822ROCKFORD ;11
Adder
20.032
972235AH1-702 GEN1
Adder
2.567
274761LEE CO EC;2U
Adder
9.343
274766LEE CO EC;7U
Adder
9.233
24728605AND G2
Adder
3.7
972301AH1-735 GEN
Adder
4.377
23906402RICHG1
Adder
0.875
23906502RICHG2&3
Adder
0.869
970091AG2-072 GEN
Adder
0.149
270349AD2-093_GEN
Solar/Wind Helper
1.077
944201AF1-088_MTX
Adder
87.117
957141AF2-008_MTX
Adder
43.559
990497J1323
External Queue
1.901388168334961
LAGNLTFEXP_LAGN->PJM
CLTF
8.301
TVALTFEXP_TVA->PJM
CLTF
3.284
CBM West 2LTFEXP_CBM-W2->PJM
CBM
76.901
NYPJM->LTFIMP_NY
CLTF
2
LGEELTFEXP_LGEE->PJM
CLTF
3.227
WECLTFEXP_WEC->PJM
CLTF
3.885
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.527
AG2-052LTFEXP_AG2-052->PJM
LTF
0.257
AH1-155LTFEXP_AH1-155->PJM
LTF
0.385
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.188
CBM West 1LTFEXP_CBM-W1->PJM
CBM
126.569
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.288
MECLTFEXP_MEC->PJM
CLTF
14.414
SIGELTFEXP_SIGE->PJM
CLTF
0.332

Details for 05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer l/o AEP_P4_#7444_05DUMONT 765_A2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer
Contingency Name:
AEP_P4_#7444_05DUMONT 765_A2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.9 %
Rating:3097.0 MVA
Rating Type:B
MVA to Mitigate:3589.56
MW Contribution:21.97
Bus #Bus NameTypeMW Contribution
971599AH1-298 GEN
50/50
20.277
24729505KEY G4
50/50
13.379
24727205RPMNG3
50/50
1.301
24653605MOTTVILLE
50/50
0.005
270071AF1-092 GEN
Solar/Wind Harmer
28.477
958711AF2-162 GEN
Solar/Wind Harmer
1.801
965101AG1-375 GEN
Solar/Wind Harmer
17.262
945581AF1-223 GEN
Solar/Wind Harmer
7.365
963791AG1-232 GEN
Solar/Wind Harmer
21.446
965041AG1-368 GEN
Solar/Wind Harmer
15.736
965051AG1-369 GEN
Solar/Wind Harmer
7.267
270024AE2-089 GEN
Solar/Wind Harmer
6.446
970115AG2-085 GEN
Solar/Wind Harmer
5.227
971771AH1-392 GEN
Solar/Wind Harmer
11.649
971347AH1-153 GEN
Solar/Wind Harmer
19.196
970583AG2-370 GEN
50/50
3.66
960851AF2-376 GEN
50/50
3.295
24727105RPMNG2
50/50
1.312
24641605TWIN BRNCH
50/50
0.024
944531AF1-118 GEN
Solar/Wind Harmer
70.092
270043AE2-236 GEN
Solar/Wind Harmer
10.813
959331AF2-224 GEN
Solar/Wind Harmer
18.246
965021AG1-366 GEN
Solar/Wind Harmer
4.243
970031AG2-029 GEN
Solar/Wind Harmer
49.558
270191TR4_S_V150
Solar/Wind Harmer
4.366
270247TR4_N_V136
Solar/Wind Harmer
1.238
958821AF2-173 GEN
Solar/Wind Harmer
19.383
270004AE1-209 GEN
Solar/Wind Harmer
7.567
971617AH1-308 GEN
Solar/Wind Harmer
7.985
247643Z2-116 C
Solar/Wind Harmer
0.094
945111AF1-176 GEN
Solar/Wind Harmer
7.407
946031AF1-268 GEN
Solar/Wind Harmer
10.685
970349AG2-230 GEN
Solar/Wind Harmer
19.196
24642205MAYFLWER
Adder
0.812
970289AG2-191 GEN
Solar/Wind Harmer
0.959
970291AG2-192 GEN
Solar/Wind Harmer
0.872
270437AC2-090 C
Solar/Wind Harmer
6.922
247642Z2-115 C
Solar/Wind Harmer
0.079
270044AE2-322 C
Solar/Wind Harmer
1.623
270404AC1-167 GEN
Solar/Wind Harmer
1.352
24441205WTRV SLR C
Solar/Wind Harmer
0.166
962031AG1-047 GEN
Solar/Wind Harmer
3.722
957741AF2-068 GEN
Solar/Wind Harmer
18.469
270258AD1-119 GEN
Solar/Wind Harmer
3.418
247604X1-042
Adder
0.504
270491AE1-102 GEN2
Solar/Wind Harmer
1.547
958091AF2-103 GEN
Solar/Wind Harmer
0.192
270535AF1-215 GEN1
Solar/Wind Harmer
5.155
972231SS25-0005
Solar/Wind Harmer
10.698
972181SS23-001
Solar/Wind Harmer
6.686
274752CRETE EC ;2U
Adder
5.51
274753CRETE EC ;3U
Adder
5.51
274724RIVER EC ;11
Adder
19.836
964401AG1-302 GEN
Solar/Wind Harmer
10.112
959141AF2-205 GEN
Solar/Wind Harmer
6.631
274802UNIV PARK;5U
Adder
6.39
274826FISK ;BP
Adder
11.978
274800UNIV PARK;3U
Adder
6.366
972038AH1-567 GEN2
Adder
0.398
274772LINCOLN ;3U
Adder
6.754
276772AC2-154 GEN
Solar/Wind Harmer
3.039
276806AD2-047 C O1
Solar/Wind Harmer
11.656
970941AG2-585 GEN
Solar/Wind Harmer
13.62
972228AH1-698 GEN2
Adder
4.019
274676JOLIET 29;8U
Adder
31.865
276897AD1-100 C
Solar/Wind Harmer
31.229
939351AE1-166 GEN
Solar/Wind Harmer
6.381
276893AG1-478 C
Solar/Wind Harmer
0.449
970707AG2-453 GEN
Solar/Wind Harmer
30.091
274730ELWOOD EC;6P
Adder
17.665
274734ELWOOD EC;8P
Adder
17.665
274736ELWOOD EC;9P
Adder
17.665
274729ELWOOD EC;1P
Adder
17.664
970513AG2-328 GEN
Solar/Wind Harmer
19.169
970517AG2-330 GEN
Solar/Wind Harmer
17.386
274682WAUKEGAN ;7U
Adder
18.845
972236AH1-702 GEN2
Adder
2.226
274760LEE CO EC;1U
Adder
9.316
274767LEE CO EC;8U
Adder
9.206
24728705AND G3
Adder
7.73
24728505AND G1
Adder
3.696
23906502RICHG2&3
Adder
0.873
960861AF2-377 GEN
50/50
3.387
970521AG2-332 GEN
50/50
16.194
24639705ELKHART HY
50/50
0.225
24727005RPMNG1
50/50
1.307
960791AF2-370 GEN
50/50
3.039
965011AG1-365 GEN
Solar/Wind Harmer
18.246
965651AG1-433 GEN
Solar/Wind Harmer
9.727
958861AF2-177 GEN
Solar/Wind Harmer
18.868
945371AF1-202 GEN
Solar/Wind Harmer
11.33
944231AF1-091 GEN
Solar/Wind Harmer
5.803
270063AE2-323 C
Solar/Wind Harmer
3.379
247521TR3_G114
Solar/Wind Harmer
4.894
270246TR4_N_V150
Solar/Wind Harmer
1.238
24695305TIMB G C
Solar/Wind Harmer
7.798
270005AE1-210 C O1
Solar/Wind Harmer
7.567
965031AG1-367 GEN
Solar/Wind Harmer
13.845
945111AF1-176 GEN
Solar/Wind Harmer
23.371
970825AG2-519 GEN
Solar/Wind Harmer
3.078
270505AE1-170 C O1
Solar/Wind Harmer
19.319
270449AD2-020 GEN
Solar/Wind Harmer
3.573
943021AE2-325 GEN
Solar/Wind Harmer
4.643
270032AE2-172
Solar/Wind Harmer
5.867
965421AG1-410 GEN
Solar/Wind Harmer
37.525
970291AG2-192 GEN
Solar/Wind Harmer
1.624
942081AE2-220 GEN
Solar/Wind Harmer
7.926
270239V3-007_GEN1
Solar/Wind Harmer
2.133
276903AD2-071 C
Solar/Wind Harmer
12.042
246936BC-WTG1
Solar/Wind Harmer
4.657
270489AE1-102 GEN1
Solar/Wind Harmer
1.547
970373AG2-245 GEN
Solar/Wind Harmer
24.301
247536S-71 GEN
Solar/Wind Harmer
4.631
270055AF2-134 C O1
Solar/Wind Harmer
3.436
274751CRETE EC ;1U
Adder
5.51
274754CRETE EC ;4U
Adder
5.51
274723RIVER EC ;12
Adder
20.078
958381AF2-132 GEN
Solar/Wind Harmer
10.112
964861AG1-349 GEN
Solar/Wind Harmer
8.745
971917AH1-482 GEN
Solar/Wind Harmer
10.092
274812UNIV PK N;8U
Adder
5.562
276164X3-005 C
Solar/Wind Harmer
0.778
274801UNIV PARK;4U
Adder
6.366
972207SS24-0001
Solar/Wind Harmer
24.014
274773LINCOLN ;4U
Adder
6.754
274774LINCOLN ;5U
Adder
6.754
276776AD2-060 GEN
Solar/Wind Harmer
0.461
940581AE2-045 GEN
Solar/Wind Harmer
11.089
971605AH1-302 GEN
Solar/Wind Harmer
9.483
274676JOLIET 29;8U
Adder
33.046
941551AE2-152 GEN
Solar/Wind Harmer
4.881
274674JOLIET 9 ;6U
Adder
16.547
274732ELWOOD EC;7P
Adder
17.665
970245AG2-165 GEN
Solar/Wind Harmer
19.169
274871GR RIDGE ;2U
Solar/Wind Harmer
8.203
274745AC1-111 GEN9
Adder
5.917
274682WAUKEGAN ;7U
Adder
18.845
274828WAUKEGAN ;BP
Adder
11.568
274822ROCKFORD ;11
Adder
19.974
972235AH1-702 GEN1
Adder
2.559
274761LEE CO EC;2U
Adder
9.316
274766LEE CO EC;7U
Adder
9.206
24728605AND G2
Adder
3.696
972301AH1-735 GEN
Adder
4.398
23906402RICHG1
Adder
0.88
23906502RICHG2&3
Adder
0.873
970091AG2-072 GEN
Adder
0.148
270349AD2-093_GEN
Solar/Wind Helper
1.074
24729405KEY G3
50/50
0.73
24729305KEY G2
50/50
0.718
24729205KEY G1
50/50
0.714
970615AG2-402 GEN
50/50
4.243
247620Y3-023
50/50
0.692
970611AG2-400 GEN
Solar/Wind Harmer
18.246
944541AF1-119 GEN
Solar/Wind Harmer
7.455
960971AF2-388 GEN
Solar/Wind Harmer
19.454
942221AE2-234 GEN
Solar/Wind Harmer
1.157
270599AE1-208 GEN
Solar/Wind Harmer
11.746
270031AE2-169
Solar/Wind Harmer
11.746
270216AD2-079_GEN
Solar/Wind Harmer
0.821
960441AF2-335 GEN
Solar/Wind Harmer
13.068
970825AG2-519 GEN
Solar/Wind Harmer
13.796
960981AF2-389 GEN
Solar/Wind Harmer
1.957
957891AF2-083 GEN
Solar/Wind Harmer
4.363
961051AF2-396 GEN
Solar/Wind Harmer
20.443
961051AF2-396 GEN
Solar/Wind Harmer
9.508
270526AF1-158 GEN
Solar/Wind Harmer
5.679
964611AG1-324 GEN
Solar/Wind Harmer
1.466
964611AG1-324 GEN
Solar/Wind Harmer
0.651
24379505HDWTR1G C
Solar/Wind Harmer
9.803
270209AC1-174_GEN
Solar/Wind Harmer
6.918
926881AC1-175 GEN
Solar/Wind Harmer
6.918
24441505OLIV SLR
Solar/Wind Harmer
0.166
270201AC2-176 GEN
Solar/Wind Harmer
6.33
965681AG1-436 GEN
Solar/Wind Harmer
15.06
965791AG1-447 GEN
Solar/Wind Harmer
7.705
246938BC-WTG3
Solar/Wind Harmer
4.737
246937BC-WTG2
Solar/Wind Harmer
4.657
247621Y3-024
Adder
0.287
270007AE1-245 C
Solar/Wind Harmer
7.038
270383AD1-128 GEN
Solar/Wind Harmer
6.986
274808UNIV PK N;4U
Adder
5.537
942801AE2-298 GEN
Solar/Wind Harmer
1.659
274803UNIV PARK;6U
Adder
6.39
274770LINCOLN ;1U
Adder
6.754
274771LINCOLN ;2U
Adder
6.754
274888KELLY CRK;1U
Solar/Wind Harmer
6.433
274887GEN-1.85
Solar/Wind Harmer
5.808
276843GEN-1.7
Solar/Wind Harmer
0.625
958011AF2-095 GEN
Solar/Wind Harmer
15.69
972259AH1-714 GEN
Adder
20.574
274674JOLIET 9 ;6U
Adder
16.547
970321AG2-212 GEN
Solar/Wind Harmer
19.169
970883AG2-550 GEN
Solar/Wind Harmer
10.727
970885AG2-551 GEN
Solar/Wind Harmer
2.495
274847GR RIDGE ;BU
Solar/Wind Harmer
5.396
945421AF1-207 GEN
Solar/Wind Harmer
14.904
274695ROCKY RD ;2P
Adder
11.671
274693ROCKY RD ;1P
Adder
11.556
274697ROCKY RD ;3P
Adder
3.17
274696ROCKY RD ;4P
Adder
11.946
274683WAUKEGAN ;8U
Adder
22.068
274683WAUKEGAN ;8U
Adder
18.602
274764LEE CO EC;5U
Adder
9.338
274765LEE CO EC;6U
Adder
9.338
274762LEE CO EC;3U
Adder
9.316
274763LEE CO EC;4U
Adder
9.228
972267AH1-718 GEN
Adder
4.131
24728805RICHG1
Adder
3.038
24728905RICHG2
Adder
3.038
270471AD2-092_GEN
Solar/Wind Helper
1.074
946101AF1-275 GEN
Solar/Wind Helper
0.3
957841AF2-078 GEN
Solar/Wind Harmer
2.136
944161AF1-084 GEN
Solar/Wind Harmer
2.789
270594AE1-207 GEN
Solar/Wind Harmer
18.539
965461AG1-414 GEN
Solar/Wind Harmer
2.832
970289AG2-191 GEN
Solar/Wind Harmer
2.373
270240V3-007_GEN2
Solar/Wind Harmer
7.67
971769AH1-391 GEN
Solar/Wind Harmer
12.39
961761AG1-017 GEN
Solar/Wind Harmer
0.527
960681AF2-359 GEN
Solar/Wind Harmer
4.552
24725505WLD G2 C
Solar/Wind Harmer
4.752
24699105WLD G1 C
Solar/Wind Harmer
4.696
957201AF2-014 GEN
Solar/Wind Harmer
5.397
270435AC2-044 GEN
Solar/Wind Harmer
2.38
971549AH1-272 GEN
Solar/Wind Harmer
21.971
247607V1-011 GEN
Solar/Wind Harmer
4.695
270536AF1-215 GEN2
Solar/Wind Harmer
5.155
274814UNIV PK N;0U
Adder
5.61
274807UNIV PK N;3U
Adder
5.598
274805UNIV PK N;1U
Adder
5.574
274811UNIV PK N;7U
Adder
5.562
958391AF2-133 GEN
Solar/Wind Harmer
10.019
972037AH1-567 GEN1
Adder
0.201
274827FISK ;RP
Adder
8.489
274775LINCOLN ;6U
Adder
6.754
274776LINCOLN ;7U
Adder
6.754
274777LINCOLN ;8U
Adder
6.754
960591AF2-350 GEN
Solar/Wind Harmer
10.896
972227AH1-698 GEN1
Adder
2.829
274687WILL CNTY;4U
Adder
30.181
274687WILL CNTY;4U
Adder
30.181
274675JOLIET 29;7U
Adder
33.046
274675JOLIET 29;7U
Adder
31.866
274728ELWOOD EC;5P
Adder
17.665
274731ELWOOD EC;2P
Adder
17.664
274733ELWOOD EC;3P
Adder
17.664
274735ELWOOD EC;4P
Adder
17.664
270543AE2-219 C
Solar/Wind Harmer
5.493
970833AG2-524 GEN
Solar/Wind Harmer
9.321
970833AG2-524 GEN
Solar/Wind Harmer
4.335
274746AC1-111 G10
Adder
5.917
274744AC1-111 GEN8
Adder
5.917
274823ROCKFORD ;21
Adder
19.829
270054AF2-122 C O1
Solar/Wind Helper
0.776
270284AF1-227 GEN1
Solar/Wind Helper
1.163
270286AF1-227 GEN2
Solar/Wind Helper
0.426
270287AF1-227 GEN3
Solar/Wind Helper
0.426
270520AE2-214 GEN
Solar/Wind Helper
2.396
944201AF1-088_MTX
Adder
86.826
957141AF2-008_MTX
Adder
43.413
990497J1323
External Queue
1.9195195436477661
LAGNLTFEXP_LAGN->PJM
CLTF
8.272
TVALTFEXP_TVA->PJM
CLTF
3.271
CBM West 2LTFEXP_CBM-W2->PJM
CBM
76.674
NYPJM->LTFIMP_NY
CLTF
1.996
LGEELTFEXP_LGEE->PJM
CLTF
3.215
WECLTFEXP_WEC->PJM
CLTF
3.875
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.53
AG2-052LTFEXP_AG2-052->PJM
LTF
0.258
AH1-155LTFEXP_AH1-155->PJM
LTF
0.388
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.19
CBM West 1LTFEXP_CBM-W1->PJM
CBM
126.576
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.237
MECLTFEXP_MEC->PJM
CLTF
14.373
SIGELTFEXP_SIGE->PJM
CLTF
0.331

Details for 05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer l/o AEP_P1-2_#7442_200545_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer
Contingency Name:
AEP_P1-2_#7442_200545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.07 %
Rating:3097.0 MVA
Rating Type:B
MVA to Mitigate:3439.74
MW Contribution:16.96
Bus #Bus NameTypeMW Contribution
971599AH1-298 GEN
50/50
20.218
24729505KEY G4
50/50
13.356
24727205RPMNG3
50/50
1.297
24653605MOTTVILLE
50/50
0.005
270071AF1-092 GEN
Solar/Wind Harmer
25.362
965101AG1-375 GEN
Solar/Wind Harmer
12.025
945581AF1-223 GEN
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
14.93
965041AG1-368 GEN
Solar/Wind Harmer
10.949
965051AG1-369 GEN
Solar/Wind Harmer
5.056
971609AH1-304 GEN
Solar/Wind Harmer
1.641
270024AE2-089 GEN
Solar/Wind Harmer
0.01
970115AG2-085 GEN
Solar/Wind Harmer
3.655
971771AH1-392 GEN
Solar/Wind Harmer
8.953
971619AH1-309 GEN
Solar/Wind Harmer
4.017
270594AE1-207 GEN
Solar/Wind Harmer
9.866
971347AH1-153 GEN
Solar/Wind Harmer
13.119
970289AG2-191 GEN
Solar/Wind Harmer
1.658
270240V3-007_GEN2
Solar/Wind Harmer
0.003
971769AH1-391 GEN
Solar/Wind Harmer
9.572
24725505WLD G2 C
Solar/Wind Harmer
0.002
24699105WLD G1 C
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
1.048
247607V1-011 GEN
Solar/Wind Harmer
0.001
971549AH1-272 GEN
Solar/Wind Harmer
16.964
270536AF1-215 GEN2
Solar/Wind Harmer
0.01
274814UNIV PK N;0U
Adder
5.609
274807UNIV PK N;3U
Adder
5.596
274805UNIV PK N;1U
Adder
5.572
274811UNIV PK N;7U
Adder
5.56
958391AF2-133 GEN
Solar/Wind Harmer
0.001
972037AH1-567 GEN1
Adder
0.201
274827FISK ;RP
Adder
8.497
274775LINCOLN ;6U
Adder
9.237
274776LINCOLN ;7U
Adder
9.237
274777LINCOLN ;8U
Adder
9.237
960591AF2-350 GEN
Solar/Wind Harmer
7.613
972227AH1-698 GEN1
Adder
2.835
971611AH1-305 GEN
Solar/Wind Harmer
4.511
274687WILL CNTY;4U
Adder
30.235
274687WILL CNTY;4U
Adder
30.235
274675JOLIET 29;7U
Adder
33.113
274675JOLIET 29;7U
Adder
31.93
274728ELWOOD EC;5P
Adder
17.702
274731ELWOOD EC;2P
Adder
17.701
274733ELWOOD EC;3P
Adder
17.701
274735ELWOOD EC;4P
Adder
17.701
270543AE2-219 C
Solar/Wind Harmer
0.005
970833AG2-524 GEN
Solar/Wind Harmer
8.217
970833AG2-524 GEN
Solar/Wind Harmer
5.478
274746AC1-111 G10
Adder
5.936
274744AC1-111 GEN8
Adder
5.936
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
276868AE1-113 GEN
Solar/Wind Harmer
1.457
276882AE2-255 GEN
Solar/Wind Harmer
0.849
971177AH1-047 GEN
Solar/Wind Harmer
4.45
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
971411AH1-196 GEN
Solar/Wind Harmer
10.784
971675AH1-338 GEN
Solar/Wind Harmer
2.801
971171AH1-044 GEN
Solar/Wind Harmer
14.285
274823ROCKFORD ;21
Adder
19.887
970169AG2-114 GEN
Solar/Wind Harmer
7.099
926823AC1-168 GEN
Solar/Wind Harmer
1.205
276612AE2-035 GEN
Solar/Wind Harmer
0.002
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
971681AH1-341 GEN
Solar/Wind Harmer
11.326
961011AF2-392 GEN
Solar/Wind Harmer
4.084
957751AF2-069 GEN
Solar/Wind Harmer
0.229
971029AG2-637 GEN
Solar/Wind Harmer
10.391
276655WTG1_EQ
Solar/Wind Harmer
0.003
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.234
941731AE2-173 GEN
Solar/Wind Harmer
5.741
963841AG1-237 GEN
Solar/Wind Harmer
2.984
946321AF1-296 GEN
Solar/Wind Harmer
3.782
971673AH1-337 GEN
Solar/Wind Harmer
4.373
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.236
276848AB2-070 GEN3
Solar/Wind Harmer
0.235
944221AF1-090 GEN
Solar/Wind Harmer
3.489
270297AD1-101 GEN
Solar/Wind Harmer
0.001
945411AF1-206 GEN
Solar/Wind Harmer
0
270054AF2-122 C O1
Solar/Wind Helper
0.778
270284AF1-227 GEN1
Solar/Wind Helper
1.167
270286AF1-227 GEN2
Solar/Wind Helper
0.428
270287AF1-227 GEN3
Solar/Wind Helper
0.428
270520AE2-214 GEN
Solar/Wind Helper
2.4
960861AF2-377 GEN
50/50
3.377
970521AG2-332 GEN
50/50
16.09
24639705ELKHART HY
50/50
0.224
24727005RPMNG1
50/50
1.303
960791AF2-370 GEN
50/50
3.046
965011AG1-365 GEN
Solar/Wind Harmer
12.697
965651AG1-433 GEN
Solar/Wind Harmer
3.637
958861AF2-177 GEN
Solar/Wind Harmer
5.211
945371AF1-202 GEN
Solar/Wind Harmer
0.001
944231AF1-091 GEN
Solar/Wind Harmer
2.856
270063AE2-323 C
Solar/Wind Harmer
0.009
247521TR3_G114
Solar/Wind Harmer
0.369
270246TR4_N_V150
Solar/Wind Harmer
0.065
24695305TIMB G C
Solar/Wind Harmer
0.003
270005AE1-210 C O1
Solar/Wind Harmer
2.091
965031AG1-367 GEN
Solar/Wind Harmer
9.65
970825AG2-519 GEN
Solar/Wind Harmer
3.236
945111AF1-176 GEN
Solar/Wind Harmer
16.201
270505AE1-170 C O1
Solar/Wind Harmer
9.372
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
4.614
270032AE2-172
Solar/Wind Harmer
5.873
970291AG2-192 GEN
Solar/Wind Harmer
1.135
965421AG1-410 GEN
Solar/Wind Harmer
26.1
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0.001
970613AG2-401 GEN
Solar/Wind Harmer
6.336
276903AD2-071 C
Solar/Wind Harmer
9.392
246936BC-WTG1
Solar/Wind Harmer
0.336
270489AE1-102 GEN1
Solar/Wind Harmer
1.076
970373AG2-245 GEN
Solar/Wind Harmer
16.85
247536S-71 GEN
Solar/Wind Harmer
0.321
270055AF2-134 C O1
Solar/Wind Harmer
0.006
274751CRETE EC ;1U
Adder
9.273
274754CRETE EC ;4U
Adder
9.273
274723RIVER EC ;12
Adder
20.057
958381AF2-132 GEN
Solar/Wind Harmer
0.001
274812UNIV PK N;8U
Adder
5.56
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
10.061
276164X3-005 C
Solar/Wind Harmer
0
274773LINCOLN ;4U
Adder
9.237
274774LINCOLN ;5U
Adder
9.237
274801UNIV PARK;4U
Adder
6.373
970245AG2-165 GEN
Solar/Wind Harmer
3.303
276776AD2-060 GEN
Solar/Wind Harmer
0.795
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
9.471
274676JOLIET 29;8U
Adder
33.113
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274674JOLIET 9 ;6U
Adder
16.583
274732ELWOOD EC;7P
Adder
17.702
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
274745AC1-111 GEN9
Adder
5.936
276691AA1-018 GEN1
Solar/Wind Harmer
0.895
274682WAUKEGAN ;7U
Adder
18.895
274828WAUKEGAN ;BP
Adder
11.599
24791305MDL-5G
Solar/Wind Harmer
0.001
939401AE1-172 GEN
Solar/Wind Harmer
5.451
276901AD2-066 C O1
Solar/Wind Harmer
0.007
962781AG1-127 GEN
Solar/Wind Harmer
6.91
274872LEEDK;1U
Solar/Wind Harmer
0.004
971997AH1-543 GEN
Solar/Wind Harmer
3.793
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
276861AD2-134 GEN
Solar/Wind Harmer
0.129
957471AF2-041 GEN
Solar/Wind Harmer
21.427
959081AF2-199 GEN
Solar/Wind Harmer
7.142
971067AG2-660 GEN
Solar/Wind Harmer
2.381
274822ROCKFORD ;11
Adder
20.032
972235AH1-702 GEN1
Adder
2.567
970569AG2-363 GEN
Solar/Wind Harmer
21.31
970819AG2-516 GEN
Solar/Wind Harmer
8.5
971475AH1-234 GEN
Solar/Wind Harmer
3.428
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
9.343
274766LEE CO EC;7U
Adder
9.233
276158O29GEN2
Solar/Wind Harmer
0.001
274877BISHOP HL;1U
Solar/Wind Harmer
0.232
276726Z2-087_GEN
Solar/Wind Harmer
0.002
939741AE1-205 GEN
Solar/Wind Harmer
9.645
274854TWINGROVE;U2
Solar/Wind Harmer
0.003
24728605AND G2
Adder
3.7
963741AG1-226 GEN
Solar/Wind Harmer
15.923
970773AG2-487 GEN
Solar/Wind Harmer
1.185
972175AH1-670 GEN
Solar/Wind Harmer
5.466
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
2.507
276615X2-022 GEN
Solar/Wind Harmer
0.067
965911AG1-460 GEN
Solar/Wind Harmer
1.231
270445AC2-157 GEN2
Solar/Wind Harmer
0.002
970333AG2-219 GEN
Solar/Wind Harmer
3.324
241808AF1-120 C
Solar/Wind Harmer
0.001
241858AF1-205_GEN
Solar/Wind Harmer
1.342
241840AF1-064_GEN
Solar/Wind Harmer
0.001
270349AD2-093_GEN
Solar/Wind Helper
1.077
970583AG2-370 GEN
50/50
3.65
960851AF2-376 GEN
50/50
3.285
24727105RPMNG2
50/50
1.308
24641605TWIN BRNCH
50/50
0.023
944531AF1-118 GEN
Solar/Wind Harmer
62.505
270043AE2-236 GEN
Solar/Wind Harmer
8.778
959331AF2-224 GEN
Solar/Wind Harmer
8.888
965021AG1-366 GEN
Solar/Wind Harmer
4.232
970031AG2-029 GEN
Solar/Wind Harmer
7.468
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.065
958821AF2-173 GEN
Solar/Wind Harmer
13.51
270004AE1-209 GEN
Solar/Wind Harmer
2.091
971617AH1-308 GEN
Solar/Wind Harmer
7.972
247643Z2-116 C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
7.359
946031AF1-268 GEN
Solar/Wind Harmer
8.54
24642205MAYFLWER
Adder
0.806
970349AG2-230 GEN
Solar/Wind Harmer
13.119
970289AG2-191 GEN
Solar/Wind Harmer
0.96
970291AG2-192 GEN
Solar/Wind Harmer
0.873
247642Z2-115 C
Solar/Wind Harmer
0.004
270437AC2-090 C
Solar/Wind Harmer
0.004
270404AC1-167 GEN
Solar/Wind Harmer
0.004
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
12.871
24441205WTRV SLR C
Solar/Wind Harmer
0
270258AD1-119 GEN
Solar/Wind Harmer
0.002
247604X1-042
Adder
0.501
270491AE1-102 GEN2
Solar/Wind Harmer
1.076
270535AF1-215 GEN1
Solar/Wind Harmer
0.01
274752CRETE EC ;2U
Adder
9.273
274753CRETE EC ;3U
Adder
9.273
274724RIVER EC ;11
Adder
19.816
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274802UNIV PARK;5U
Adder
6.395
274826FISK ;BP
Adder
11.989
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
274772LINCOLN ;3U
Adder
9.237
274800UNIV PARK;3U
Adder
6.373
972038AH1-567 GEN2
Adder
0.399
970513AG2-328 GEN
Solar/Wind Harmer
3.303
970517AG2-330 GEN
Solar/Wind Harmer
19.816
276806AD2-047 C O1
Solar/Wind Harmer
4.314
970941AG2-585 GEN
Solar/Wind Harmer
9.516
972228AH1-698 GEN2
Adder
4.027
274676JOLIET 29;8U
Adder
31.93
276897AD1-100 C
Solar/Wind Harmer
0.01
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
970707AG2-453 GEN
Solar/Wind Harmer
24.591
276893AG1-478 C
Solar/Wind Harmer
0.298
274730ELWOOD EC;6P
Adder
17.702
274734ELWOOD EC;8P
Adder
17.702
274736ELWOOD EC;9P
Adder
17.702
274729ELWOOD EC;1P
Adder
17.701
943121AE2-341 GEN
Solar/Wind Harmer
12.419
943591AF1-030 GEN
Solar/Wind Harmer
8.259
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
18.895
276805AD2-038 GEN
Solar/Wind Harmer
0.002
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
7.294
274872LEEDK;1U
Solar/Wind Harmer
0.266
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.766
276889AE2-281 GEN
Solar/Wind Harmer
0.001
274855GSG-6 ;RU
Solar/Wind Harmer
0.263
274850MENDOTA H;RU
Solar/Wind Harmer
0.085
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.129
959091AF2-200 GEN
Solar/Wind Harmer
14.285
972236AH1-702 GEN2
Adder
2.232
970571AG2-364 GEN
Solar/Wind Harmer
14.206
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
9.343
274767LEE CO EC;8U
Adder
9.233
276157O29GEN1
Solar/Wind Harmer
1.121
274878BISHOP HL;2U
Solar/Wind Harmer
0.232
942111AE2-223 GEN
Solar/Wind Harmer
2.239
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
965091AG1-374 GEN
Solar/Wind Harmer
20.348
959611AF2-252 GEN
Solar/Wind Harmer
2.261
24728705AND G3
Adder
7.738
24728505AND G1
Adder
3.7
965931AG1-462 GEN
Solar/Wind Harmer
17.128
270356AE2-297 GEN
Solar/Wind Harmer
0.009
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
2.985
276668AB2-070 GEN1
Solar/Wind Harmer
0.236
276621W2-048 GEN
Solar/Wind Harmer
0.321
276838X2-022 GEN2
Solar/Wind Harmer
0.358
970193AG2-126 GEN
Solar/Wind Harmer
9.285
942481AE2-261 GEN
Solar/Wind Harmer
18.401
270222AC2-111 GEN
Solar/Wind Harmer
2.367
970243AG2-164 GEN
Solar/Wind Harmer
2.719
970519AG2-331 GEN
Solar/Wind Harmer
12.086
970699AG2-449 GEN
Solar/Wind Harmer
1.162
270541AE2-072 C
Solar/Wind Harmer
0.005
241832AE2-181_GEN
Solar/Wind Harmer
0.001
958321AF2-126 GEN
Solar/Wind Harmer
0.444
24729405KEY G3
50/50
0.729
24729305KEY G2
50/50
0.717
24729205KEY G1
50/50
0.713
970615AG2-402 GEN
50/50
4.232
247620Y3-023
50/50
0.687
970611AG2-400 GEN
Solar/Wind Harmer
12.697
970627AG2-408 GEN
Solar/Wind Harmer
3.809
944541AF1-119 GEN
Solar/Wind Harmer
0.831
960971AF2-388 GEN
Solar/Wind Harmer
7.274
942221AE2-234 GEN
Solar/Wind Harmer
0.055
270599AE1-208 GEN
Solar/Wind Harmer
9.209
270031AE2-169
Solar/Wind Harmer
5.525
270216AD2-079_GEN
Solar/Wind Harmer
0.001
960441AF2-335 GEN
Solar/Wind Harmer
9.138
970825AG2-519 GEN
Solar/Wind Harmer
10.102
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
17.858
961051AF2-396 GEN
Solar/Wind Harmer
11.905
971613AH1-306 GEN
Solar/Wind Harmer
4.228
964611AG1-324 GEN
Solar/Wind Harmer
0.65
270526AF1-158 GEN
Solar/Wind Harmer
0.011
24379505HDWTR1G C
Solar/Wind Harmer
0.003
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
270201AC2-176 GEN
Solar/Wind Harmer
0.002
24441505OLIV SLR
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.561
965681AG1-436 GEN
Solar/Wind Harmer
10.414
965791AG1-447 GEN
Solar/Wind Harmer
7.637
247621Y3-024
Adder
0.286
246938BC-WTG3
Solar/Wind Harmer
0.3
246937BC-WTG2
Solar/Wind Harmer
0.336
270007AE1-245 C
Solar/Wind Harmer
0.002
270383AD1-128 GEN
Solar/Wind Harmer
0.005
274808UNIV PK N;4U
Adder
5.536
274803UNIV PARK;6U
Adder
6.395
274770LINCOLN ;1U
Adder
9.237
274771LINCOLN ;2U
Adder
9.237
970321AG2-212 GEN
Solar/Wind Harmer
3.303
274888KELLY CRK;1U
Solar/Wind Harmer
0.447
274887GEN-1.85
Solar/Wind Harmer
0.2
276843GEN-1.7
Solar/Wind Harmer
0.246
958011AF2-095 GEN
Solar/Wind Harmer
10.963
972259AH1-714 GEN
Adder
20.637
274674JOLIET 9 ;6U
Adder
16.583
970883AG2-550 GEN
Solar/Wind Harmer
7.476
970885AG2-551 GEN
Solar/Wind Harmer
2.492
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
958481AF2-142 GEN
Solar/Wind Harmer
11.087
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
1
971573AH1-285 GEN
Solar/Wind Harmer
1.373
274695ROCKY RD ;2P
Adder
11.705
274693ROCKY RD ;1P
Adder
11.59
274697ROCKY RD ;3P
Adder
3.18
274696ROCKY RD ;4P
Adder
11.982
274683WAUKEGAN ;8U
Adder
22.127
274683WAUKEGAN ;8U
Adder
18.652
958491AF2-143 GEN
Solar/Wind Harmer
10.958
962691AG1-118 GEN
Solar/Wind Harmer
21.835
970921AG2-575 GEN
Solar/Wind Harmer
7.261
970921AG2-575 GEN
Solar/Wind Harmer
2.42
274879MINONK ;1U
Solar/Wind Harmer
0.306
942991AE2-321 GEN
Solar/Wind Harmer
8.062
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
971333AH1-146 GEN
Solar/Wind Harmer
14.365
971335AH1-147 GEN
Solar/Wind Harmer
14.365
971341AH1-150 GEN
Solar/Wind Harmer
14.285
971343AH1-151 GEN
Solar/Wind Harmer
14.285
274856ECOGROVE ;U1
Solar/Wind Harmer
0.167
276611AD2-172 GEN
Solar/Wind Harmer
0.002
966841AG1-555 GEN
Solar/Wind Harmer
0.798
938861AE1-114 GEN
Solar/Wind Harmer
3.985
274764LEE CO EC;5U
Adder
9.365
274765LEE CO EC;6U
Adder
9.365
274762LEE CO EC;3U
Adder
9.343
274763LEE CO EC;4U
Adder
9.255
276603SUBLETTE C
Solar/Wind Harmer
0
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.273
276646AC1-214 GEN2
Solar/Wind Harmer
0.273
972267AH1-718 GEN
Adder
4.143
276741O09 GEN1
Solar/Wind Harmer
0.247
276708O09 GEN2
Solar/Wind Harmer
0.247
276782AC1-033 GEN
Solar/Wind Harmer
0.001
960611AF2-352 GEN
Solar/Wind Harmer
2.261
970241AG2-163 GEN
Solar/Wind Harmer
3.925
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
945391AF1-204 GEN
Solar/Wind Harmer
6.577
276916AD2-100_GEN
Solar/Wind Harmer
12.826
276911AD2-131_GEN
Solar/Wind Harmer
0.845
970621AG2-405 GEN
Solar/Wind Harmer
1.049
24728805RICHG1
Adder
3.037
24728905RICHG2
Adder
3.037
270444AC2-157 GEN1
Solar/Wind Harmer
0.002
971587AH1-292 GEN
Solar/Wind Harmer
3.833
970239AG2-162 GEN
Solar/Wind Harmer
1.162
241996AE2-282_GEN
Solar/Wind Harmer
0.002
270471AD2-092_GEN
Solar/Wind Helper
1.077
946101AF1-275 GEN
Solar/Wind Helper
0.301
944201AF1-088_MTX
Adder
87.117
957141AF2-008_MTX
Adder
29.672
990792J1392
External Queue
6.540774822235107
991297J1743
External Queue
3.431180715560913
LAGNLTFEXP_LAGN->PJM
CLTF
8.301
TVALTFEXP_TVA->PJM
CLTF
3.284
CBM West 2LTFEXP_CBM-W2->PJM
CBM
76.901
NYPJM->LTFIMP_NY
CLTF
2
LGEELTFEXP_LGEE->PJM
CLTF
3.227
WECLTFEXP_WEC->PJM
CLTF
3.885
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.527
AG2-052LTFEXP_AG2-052->PJM
LTF
0.257
AH1-155LTFEXP_AH1-155->PJM
LTF
0.385
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.188
CBM West 1LTFEXP_CBM-W1->PJM
CBM
126.569
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.288
MECLTFEXP_MEC->PJM
CLTF
14.414
SIGELTFEXP_SIGE->PJM
CLTF
0.332

Details for 05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#709_546_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:109.05 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6022.77
MW Contribution:26.67
Bus #Bus NameTypeMW Contribution
971599AH1-298 GEN
50/50
19.983
270144AC1-141 ST1_
50/50
4.41
24643105BUCHANAN
50/50
0.026
274775LINCOLN ;6U
50/50
18.26
274776LINCOLN ;7U
50/50
18.26
274777LINCOLN ;8U
50/50
18.26
24653605MOTTVILLE
50/50
0.008
971347AH1-153 GEN
Solar/Wind Harmer
23.209
960681AF2-359 GEN
Solar/Wind Harmer
-0.002
971771AH1-392 GEN
Solar/Wind Harmer
14.529
971769AH1-391 GEN
Solar/Wind Harmer
16.154
971619AH1-309 GEN
Solar/Wind Harmer
6.462
270071AF1-092 GEN
Solar/Wind Harmer
27.514
274814UNIV PK N;0U
Adder
10.098
274807UNIV PK N;3U
Adder
10.076
274805UNIV PK N;1U
Adder
10.033
274811UNIV PK N;7U
Adder
10.011
972037AH1-567 GEN1
Adder
0.364
274827FISK ;RP
Adder
15.436
960591AF2-350 GEN
Solar/Wind Harmer
13.873
972227AH1-698 GEN1
Adder
5.185
270536AF1-215 GEN2
Solar/Wind Harmer
0.017
274687WILL CNTY;4U
Adder
55.173
274687WILL CNTY;4U
Adder
55.173
274675JOLIET 29;7U
Adder
60.513
274675JOLIET 29;7U
Adder
58.351
274731ELWOOD EC;2P
Adder
32.348
274733ELWOOD EC;3P
Adder
32.348
274735ELWOOD EC;4P
Adder
32.348
274728ELWOOD EC;5P
Adder
32.348
970833AG2-524 GEN
Solar/Wind Harmer
15.09
970833AG2-524 GEN
Solar/Wind Harmer
10.06
274746AC1-111 G10
Adder
10.916
274744AC1-111 GEN8
Adder
10.916
958391AF2-133 GEN
Solar/Wind Harmer
0.002
24729505KEY G4
Adder
12.474
971611AH1-305 GEN
Solar/Wind Harmer
7.91
276868AE1-113 GEN
Solar/Wind Harmer
2.657
276882AE2-255 GEN
Solar/Wind Harmer
1.548
971177AH1-047 GEN
Solar/Wind Harmer
8.156
971675AH1-338 GEN
Solar/Wind Harmer
5.138
971411AH1-196 GEN
Solar/Wind Harmer
19.757
274863CRW1-WTG
Solar/Wind Harmer
0.004
274864CRW2-WTG
Solar/Wind Harmer
0.004
971171AH1-044 GEN
Solar/Wind Harmer
26.172
274823ROCKFORD ;21
Adder
36.411
970169AG2-114 GEN
Solar/Wind Harmer
12.957
276612AE2-035 GEN
Solar/Wind Harmer
0.003
926823AC1-168 GEN
Solar/Wind Harmer
2.2
971549AH1-272 GEN
Solar/Wind Harmer
26.668
24344105CKG2
50/50
17.41
270143AC1-141 CT2_
50/50
4.979
24639705ELKHART HY
50/50
0.333
274773LINCOLN ;4U
50/50
18.26
274774LINCOLN ;5U
50/50
18.26
970521AG2-332 GEN
50/50
23.674
970245AG2-165 GEN
Solar/Wind Harmer
6.717
270505AE1-170 C O1
Solar/Wind Harmer
15.077
945111AF1-176 GEN
Solar/Wind Harmer
25.462
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
7.414
274723RIVER EC ;12
Adder
36.059
970373AG2-245 GEN
Solar/Wind Harmer
29.431
274751CRETE EC ;1U
Adder
16.552
274754CRETE EC ;4U
Adder
16.552
276164X3-005 C
Solar/Wind Harmer
0
270063AE2-323 C
Solar/Wind Harmer
0.011
274812UNIV PK N;8U
Adder
10.011
276776AD2-060 GEN
Solar/Wind Harmer
1.448
274801UNIV PARK;4U
Adder
11.588
941551AE2-152 GEN
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0.011
274676JOLIET 29;8U
Adder
60.512
274674JOLIET 9 ;6U
Adder
30.323
274732ELWOOD EC;7P
Adder
32.348
274871GR RIDGE ;2U
Solar/Wind Harmer
0.002
274745AC1-111 GEN9
Adder
10.916
958381AF2-132 GEN
Solar/Wind Harmer
0.002
964861AG1-349 GEN
Solar/Wind Harmer
-0.002
971917AH1-482 GEN
Solar/Wind Harmer
17.617
276691AA1-018 GEN1
Solar/Wind Harmer
1.631
274682WAUKEGAN ;7U
Adder
34.62
274828WAUKEGAN ;BP
Adder
21.25
939401AE1-172 GEN
Solar/Wind Harmer
9.985
962781AG1-127 GEN
Solar/Wind Harmer
12.689
274872LEEDK;1U
Solar/Wind Harmer
0.008
940581AE2-045 GEN
Solar/Wind Harmer
-0.003
971605AH1-302 GEN
Solar/Wind Harmer
16.609
276901AD2-066 C O1
Solar/Wind Harmer
0.013
971997AH1-543 GEN
Solar/Wind Harmer
6.942
276861AD2-134 GEN
Solar/Wind Harmer
0.236
957471AF2-041 GEN
Solar/Wind Harmer
39.258
959081AF2-199 GEN
Solar/Wind Harmer
13.086
971067AG2-660 GEN
Solar/Wind Harmer
4.362
276876AE1-163_GEN2
Solar/Wind Harmer
0.003
274822ROCKFORD ;11
Adder
36.677
972235AH1-702 GEN1
Adder
4.699
970819AG2-516 GEN
Solar/Wind Harmer
15.555
970569AG2-363 GEN
Solar/Wind Harmer
38.8
971475AH1-234 GEN
Solar/Wind Harmer
6.272
274857EASY ROAD;U1
Solar/Wind Harmer
0.003
274761LEE CO EC;2U
Adder
17.083
274766LEE CO EC;7U
Adder
16.882
24791305MDL-5G
Solar/Wind Harmer
0.002
965011AG1-365 GEN
Solar/Wind Harmer
12.726
276158O29GEN2
Solar/Wind Harmer
0.001
274877BISHOP HL;1U
Solar/Wind Harmer
0.423
965651AG1-433 GEN
Solar/Wind Harmer
3.688
276726Z2-087_GEN
Solar/Wind Harmer
0.004
939741AE1-205 GEN
Solar/Wind Harmer
17.52
24385905FR-11G C
Solar/Wind Harmer
0.003
24387305FR-4G C
Solar/Wind Harmer
0.005
274854TWINGROVE;U2
Solar/Wind Harmer
0.005
958861AF2-177 GEN
Solar/Wind Harmer
5.328
972175AH1-670 GEN
Solar/Wind Harmer
9.878
945371AF1-202 GEN
Solar/Wind Harmer
0.001
963741AG1-226 GEN
Solar/Wind Harmer
27.693
274880W4-005 GEN4
Solar/Wind Harmer
0.002
963831AG1-236 GEN
Solar/Wind Harmer
4.513
276615X2-022 GEN
Solar/Wind Harmer
0.12
944231AF1-091 GEN
Solar/Wind Harmer
3.041
970291AG2-192 GEN
Solar/Wind Harmer
1.481
270032AE2-172
Solar/Wind Harmer
7.401
965911AG1-460 GEN
Solar/Wind Harmer
2.209
276903AD2-071 C
Solar/Wind Harmer
12.04
970333AG2-219 GEN
Solar/Wind Harmer
7.687
270005AE1-210 C O1
Solar/Wind Harmer
2.283
965031AG1-367 GEN
Solar/Wind Harmer
10.536
970825AG2-519 GEN
Solar/Wind Harmer
3.643
247521TR3_G114
Solar/Wind Harmer
0.37
270246TR4_N_V150
Solar/Wind Harmer
0.066
24695305TIMB G C
Solar/Wind Harmer
0.003
270445AC2-157 GEN2
Solar/Wind Harmer
0.004
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0.001
970613AG2-401 GEN
Solar/Wind Harmer
7.029
247536S-71 GEN
Solar/Wind Harmer
0.355
965421AG1-410 GEN
Solar/Wind Harmer
25.459
970773AG2-487 GEN
Solar/Wind Harmer
1.469
246936BC-WTG1
Solar/Wind Harmer
0.326
270489AE1-102 GEN1
Solar/Wind Harmer
1.045
270349AD2-093_GEN
Solar/Wind Helper
1.548
971681AH1-341 GEN
Solar/Wind Harmer
20.716
24690905MDL-1G C
Solar/Wind Harmer
0.004
270180AB1-006 GEN1
Solar/Wind Harmer
0.003
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.003
24697605MDL-3G C
Solar/Wind Harmer
0.003
24697905MDL-4G C
Solar/Wind Harmer
0.002
270181AB1-006 GEN2
Solar/Wind Harmer
0
961011AF2-392 GEN
Solar/Wind Harmer
7.462
957751AF2-069 GEN
Solar/Wind Harmer
0.418
274848CAMPGROVE;RU
Solar/Wind Harmer
0.002
276655WTG1_EQ
Solar/Wind Harmer
0.005
276656WTG2_EQ
Solar/Wind Harmer
0.001
959341AF2-225 GEN
Solar/Wind Harmer
13.14
941731AE2-173 GEN
Solar/Wind Harmer
10.429
24386205FR-12G C
Solar/Wind Harmer
0.002
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.002
946321AF1-296 GEN
Solar/Wind Harmer
6.891
965101AG1-375 GEN
Solar/Wind Harmer
12.296
963841AG1-237 GEN
Solar/Wind Harmer
5.208
24344005CKG1
50/50
13.628
270142AC1-141 CT1_
50/50
4.979
24641605TWIN BRNCH
50/50
0.036
24642205MAYFLWER
50/50
1.39
274772LINCOLN ;3U
50/50
18.26
970513AG2-328 GEN
Solar/Wind Harmer
6.717
970517AG2-330 GEN
Solar/Wind Harmer
40.303
970349AG2-230 GEN
Solar/Wind Harmer
23.209
270043AE2-236 GEN
Solar/Wind Harmer
9.37
247643Z2-116 C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
11.566
274724RIVER EC ;11
Adder
35.644
274752CRETE EC ;2U
Adder
16.552
274753CRETE EC ;3U
Adder
16.552
24441205WTRV SLR C
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
45.547
274802UNIV PARK;5U
Adder
11.601
274826FISK ;BP
Adder
21.78
276806AD2-047 C O1
Solar/Wind Harmer
7.862
970941AG2-585 GEN
Solar/Wind Harmer
17.342
972228AH1-698 GEN2
Adder
7.363
274800UNIV PARK;3U
Adder
11.588
972038AH1-567 GEN2
Adder
0.725
276897AD1-100 C
Solar/Wind Harmer
0.018
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
247604X1-042
Adder
0.825
270535AF1-215 GEN1
Solar/Wind Harmer
0.017
274676JOLIET 29;8U
Adder
58.35
970031AG2-029 GEN
Solar/Wind Harmer
8.936
274729ELWOOD EC;1P
Adder
32.348
274730ELWOOD EC;6P
Adder
32.348
274734ELWOOD EC;8P
Adder
32.348
274736ELWOOD EC;9P
Adder
32.348
276893AG1-478 C
Solar/Wind Harmer
0.544
944531AF1-118 GEN
Solar/Wind Harmer
61.488
943121AE2-341 GEN
Solar/Wind Harmer
22.888
943591AF1-030 GEN
Solar/Wind Harmer
15.221
964401AG1-302 GEN
Solar/Wind Harmer
0.002
276694AA1-018 GEN2
Solar/Wind Harmer
0.002
274682WAUKEGAN ;7U
Adder
34.62
959141AF2-205 GEN
Solar/Wind Harmer
-0.003
276805AD2-038 GEN
Solar/Wind Harmer
0.004
274872LEEDK;1U
Solar/Wind Harmer
0.488
276799AD1-013 GEN
Solar/Wind Harmer
0.003
946671AF1-331 GEN
Solar/Wind Harmer
1.406
274855GSG-6 ;RU
Solar/Wind Harmer
0.483
274850MENDOTA H;RU
Solar/Wind Harmer
0.155
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.236
959091AF2-200 GEN
Solar/Wind Harmer
26.172
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
4.086
970571AG2-364 GEN
Solar/Wind Harmer
25.867
274858EASY ROAD;U2
Solar/Wind Harmer
0.003
274760LEE CO EC;1U
Adder
17.083
274767LEE CO EC;8U
Adder
16.882
24755605MDL-5G
Solar/Wind Harmer
0.002
970781AG2-491 GEN
Solar/Wind Harmer
12.802
959331AF2-224 GEN
Solar/Wind Harmer
8.908
965021AG1-366 GEN
Solar/Wind Harmer
4.242
276157O29GEN1
Solar/Wind Harmer
2.046
274878BISHOP HL;2U
Solar/Wind Harmer
0.423
942111AE2-223 GEN
Solar/Wind Harmer
4.067
274853TWINGROVE;U1
Solar/Wind Harmer
0.005
965091AG1-374 GEN
Solar/Wind Harmer
36.906
959611AF2-252 GEN
Solar/Wind Harmer
4.101
965931AG1-462 GEN
Solar/Wind Harmer
31.198
247642Z2-115 C
Solar/Wind Harmer
0.005
276686W4-005 GEN3
Solar/Wind Harmer
0.002
971993AH1-541 GEN
Solar/Wind Harmer
5.377
276668AB2-070 GEN1
Solar/Wind Harmer
0.424
276621W2-048 GEN
Solar/Wind Harmer
0.577
276838X2-022 GEN2
Solar/Wind Harmer
0.644
970289AG2-191 GEN
Solar/Wind Harmer
1.253
970291AG2-192 GEN
Solar/Wind Harmer
1.139
942481AE2-261 GEN
Solar/Wind Harmer
33.028
970243AG2-164 GEN
Solar/Wind Harmer
6.289
970519AG2-331 GEN
Solar/Wind Harmer
27.951
970699AG2-449 GEN
Solar/Wind Harmer
2.688
970193AG2-126 GEN
Solar/Wind Harmer
15.928
958821AF2-173 GEN
Solar/Wind Harmer
14.751
270004AE1-209 GEN
Solar/Wind Harmer
2.283
971617AH1-308 GEN
Solar/Wind Harmer
8.548
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.066
946031AF1-268 GEN
Solar/Wind Harmer
9.517
270437AC2-090 C
Solar/Wind Harmer
0.004
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
14.144
270404AC1-167 GEN
Solar/Wind Harmer
0.004
270258AD1-119 GEN
Solar/Wind Harmer
0.002
270356AE2-297 GEN
Solar/Wind Harmer
0.011
270491AE1-102 GEN2
Solar/Wind Harmer
1.045
270102X2-052 ST
50/50
3.353
270100X2-052 CT1
50/50
3.09
270101X2-052 CT2
50/50
3.09
274770LINCOLN ;1U
50/50
18.26
274771LINCOLN ;2U
50/50
18.26
970321AG2-212 GEN
Solar/Wind Harmer
6.717
965681AG1-436 GEN
Solar/Wind Harmer
18.169
965791AG1-447 GEN
Solar/Wind Harmer
13.324
270526AF1-158 GEN
Solar/Wind Harmer
0.018
24441505OLIV SLR
Solar/Wind Harmer
0
270216AD2-079_GEN
Solar/Wind Harmer
0.002
957891AF2-083 GEN
Solar/Wind Harmer
0.002
961051AF2-396 GEN
Solar/Wind Harmer
28.457
961051AF2-396 GEN
Solar/Wind Harmer
18.971
247620Y3-023
Adder
0.932
274808UNIV PK N;4U
Adder
9.967
972259AH1-714 GEN
Adder
37.97
274803UNIV PARK;6U
Adder
11.601
274888KELLY CRK;1U
Solar/Wind Harmer
0.815
274887GEN-1.85
Solar/Wind Harmer
0.365
276843GEN-1.7
Solar/Wind Harmer
0.449
958011AF2-095 GEN
Solar/Wind Harmer
19.978
274674JOLIET 9 ;6U
Adder
30.323
274847GR RIDGE ;BU
Solar/Wind Harmer
0.005
971573AH1-285 GEN
Solar/Wind Harmer
2.529
274695ROCKY RD ;2P
Adder
21.486
274693ROCKY RD ;1P
Adder
21.275
274697ROCKY RD ;3P
Adder
5.837
274696ROCKY RD ;4P
Adder
21.993
958481AF2-142 GEN
Solar/Wind Harmer
20.192
274861TOP CROP ;1U
Solar/Wind Harmer
0.004
274862TOP CROP ;2U
Solar/Wind Harmer
1.82
274683WAUKEGAN ;8U
Adder
40.539
274683WAUKEGAN ;8U
Adder
34.173
962691AG1-118 GEN
Solar/Wind Harmer
40.102
970921AG2-575 GEN
Solar/Wind Harmer
13.333
970921AG2-575 GEN
Solar/Wind Harmer
4.444
958491AF2-143 GEN
Solar/Wind Harmer
19.955
274879MINONK ;1U
Solar/Wind Harmer
0.559
942991AE2-321 GEN
Solar/Wind Harmer
14.775
971333AH1-146 GEN
Solar/Wind Harmer
26.325
971335AH1-147 GEN
Solar/Wind Harmer
26.325
971341AH1-150 GEN
Solar/Wind Harmer
26.172
971343AH1-151 GEN
Solar/Wind Harmer
26.172
276872AE1-163_GEN1
Solar/Wind Harmer
0.003
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.003
274856ECOGROVE ;U1
Solar/Wind Harmer
0.305
276611AD2-172 GEN
Solar/Wind Harmer
0.003
938861AE1-114 GEN
Solar/Wind Harmer
7.288
274764LEE CO EC;5U
Adder
17.123
274765LEE CO EC;6U
Adder
17.123
274762LEE CO EC;3U
Adder
17.083
274763LEE CO EC;4U
Adder
16.922
276603SUBLETTE C
Solar/Wind Harmer
0
970611AG2-400 GEN
Solar/Wind Harmer
12.726
970627AG2-408 GEN
Solar/Wind Harmer
3.818
972267AH1-718 GEN
Adder
7.569
276741O09 GEN1
Solar/Wind Harmer
0.451
276708O09 GEN2
Solar/Wind Harmer
0.451
274851PROVIDENC;RU
Solar/Wind Harmer
0.002
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.497
276646AC1-214 GEN2
Solar/Wind Harmer
0.497
276782AC1-033 GEN
Solar/Wind Harmer
0.002
944541AF1-119 GEN
Solar/Wind Harmer
0.842
960971AF2-388 GEN
Solar/Wind Harmer
7.376
966841AG1-555 GEN
Solar/Wind Harmer
1.399
960611AF2-352 GEN
Solar/Wind Harmer
4.101
970241AG2-163 GEN
Solar/Wind Harmer
6.826
942221AE2-234 GEN
Solar/Wind Harmer
0.059
276763AC1-053 GEN1
Solar/Wind Harmer
0.002
276764AC1-053 GEN2
Solar/Wind Harmer
0.002
971613AH1-306 GEN
Solar/Wind Harmer
5.329
270599AE1-208 GEN
Solar/Wind Harmer
10.158
270031AE2-169
Solar/Wind Harmer
6.095
276916AD2-100_GEN
Solar/Wind Harmer
23.006
276911AD2-131_GEN
Solar/Wind Harmer
1.515
970239AG2-162 GEN
Solar/Wind Harmer
2.688
945391AF1-204 GEN
Solar/Wind Harmer
11.282
960441AF2-335 GEN
Solar/Wind Harmer
10.327
970825AG2-519 GEN
Solar/Wind Harmer
11.373
270444AC2-157 GEN1
Solar/Wind Harmer
0.004
971587AH1-292 GEN
Solar/Wind Harmer
7.189
24379505HDWTR1G C
Solar/Wind Harmer
0.003
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
0.716
270201AC2-176 GEN
Solar/Wind Harmer
0.002
270383AD1-128 GEN
Solar/Wind Harmer
0.005
970623AG2-406 GEN
Solar/Wind Harmer
1.6
970883AG2-550 GEN
Solar/Wind Harmer
8.324
970885AG2-551 GEN
Solar/Wind Harmer
2.775
270007AE1-245 C
Solar/Wind Harmer
0.002
246938BC-WTG3
Solar/Wind Harmer
0.291
246937BC-WTG2
Solar/Wind Harmer
0.326
270471AD2-092_GEN
Solar/Wind Helper
1.548
945581AF1-223 GEN
Solar/Wind Harmer
0.001
276785W4-005 GEN1
Solar/Wind Harmer
0.002
276174W4-005 GEN2
Solar/Wind Harmer
0.002
276849AB2-070 GEN2
Solar/Wind Harmer
0.424
276848AB2-070 GEN3
Solar/Wind Harmer
0.422
963791AG1-232 GEN
Solar/Wind Harmer
15.504
970289AG2-191 GEN
Solar/Wind Harmer
2.164
270594AE1-207 GEN
Solar/Wind Harmer
12.434
971609AH1-304 GEN
Solar/Wind Harmer
1.81
965041AG1-368 GEN
Solar/Wind Harmer
11.055
944221AF1-090 GEN
Solar/Wind Harmer
6.244
24725505WLD G2 C
Solar/Wind Harmer
0.002
24699105WLD G1 C
Solar/Wind Harmer
0.002
970115AG2-085 GEN
Solar/Wind Harmer
4.131
270024AE2-089 GEN
Solar/Wind Harmer
0.011
965051AG1-369 GEN
Solar/Wind Harmer
5.072
270240V3-007_GEN2
Solar/Wind Harmer
0.003
270543AE2-219 C
Solar/Wind Harmer
0.005
247607V1-011 GEN
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
1.018
971029AG2-637 GEN
Solar/Wind Harmer
11.658
971673AH1-337 GEN
Solar/Wind Harmer
4.919
944201AF1-088_MTX
Adder
163.382
957141AF2-008_MTX
Adder
69.441
LAGNLTFEXP_LAGN->PJM
CLTF
14.15
TVALTFEXP_TVA->PJM
CLTF
5.408
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.138
NYPJM->LTFIMP_NY
CLTF
3.386
LGEELTFEXP_LGEE->PJM
CLTF
5.588
WECLTFEXP_WEC->PJM
CLTF
7.104
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.19
AG2-052LTFEXP_AG2-052->PJM
LTF
0.447
AH1-155LTFEXP_AH1-155->PJM
LTF
0.671
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.516
CBM West 1LTFEXP_CBM-W1->PJM
CBM
217.631
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.154
MECLTFEXP_MEC->PJM
CLTF
26.031
SIGELTFEXP_SIGE->PJM
CLTF
0.551

Details for 05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line l/o AEP_P4_#2995_05E LIMA 345_M_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#2995_05E LIMA 345_M_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.54 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5994.88
MW Contribution:32.93
Bus #Bus NameTypeMW Contribution
971599AH1-298 GEN
50/50
20.529
24727205RPMNG3
50/50
2.029
270144AC1-141 ST1_
50/50
4.29
24653605MOTTVILLE
50/50
0.008
24643105BUCHANAN
50/50
0.025
957201AF2-014 GEN
Solar/Wind Harmer
9.733
270435AC2-044 GEN
Solar/Wind Harmer
4.292
971347AH1-153 GEN
Solar/Wind Harmer
32.134
270071AF1-092 GEN
Solar/Wind Harmer
31.087
971771AH1-392 GEN
Solar/Wind Harmer
18.192
971769AH1-391 GEN
Solar/Wind Harmer
19.979
960681AF2-359 GEN
Solar/Wind Harmer
7.542
944161AF1-084 GEN
Solar/Wind Harmer
4.339
274775LINCOLN ;6U
Adder
12.031
274776LINCOLN ;7U
Adder
12.031
274777LINCOLN ;8U
Adder
12.031
24729505KEY G4
Adder
12.581
274814UNIV PK N;0U
Adder
9.617
274807UNIV PK N;3U
Adder
9.597
274805UNIV PK N;1U
Adder
9.555
274811UNIV PK N;7U
Adder
9.534
972037AH1-567 GEN1
Adder
0.346
274827FISK ;RP
Adder
14.684
960591AF2-350 GEN
Solar/Wind Harmer
18.903
972227AH1-698 GEN1
Adder
4.926
274687WILL CNTY;4U
Adder
52.424
274687WILL CNTY;4U
Adder
52.424
274675JOLIET 29;7U
Adder
57.484
274675JOLIET 29;7U
Adder
55.431
274728ELWOOD EC;5P
Adder
30.711
274731ELWOOD EC;2P
Adder
30.71
274733ELWOOD EC;3P
Adder
30.71
24727105RPMNG2
50/50
2.046
965431AG1-411 GEN
50/50
24.956
24641605TWIN BRNCH
50/50
0.035
270142AC1-141 CT1_
50/50
4.843
24344005CKG1
50/50
13.154
24642205MAYFLWER
50/50
1.348
944961AF1-161 GEN
50/50
5.748
962601AG1-109 GEN
50/50
5.748
270043AE2-236 GEN
Solar/Wind Harmer
11.825
959331AF2-224 GEN
Solar/Wind Harmer
21.485
965021AG1-366 GEN
Solar/Wind Harmer
4.996
270491AE1-102 GEN2
Solar/Wind Harmer
2.79
970349AG2-230 GEN
Solar/Wind Harmer
32.134
970513AG2-328 GEN
Solar/Wind Harmer
37.203
970517AG2-330 GEN
Solar/Wind Harmer
33.742
970031AG2-029 GEN
Solar/Wind Harmer
61.231
247643Z2-116 C
Solar/Wind Harmer
0.141
945111AF1-176 GEN
Solar/Wind Harmer
11.286
944531AF1-118 GEN
Solar/Wind Harmer
69.657
274772LINCOLN ;3U
Adder
12.031
24441205WTRV SLR C
Solar/Wind Harmer
0.261
274724RIVER EC ;11
Adder
33.985
972231SS25-0005
Solar/Wind Harmer
18.18
972181SS23-001
Solar/Wind Harmer
11.362
274752CRETE EC ;2U
Adder
9.363
274753CRETE EC ;3U
Adder
9.363
247604X1-042
Adder
0.795
274735ELWOOD EC;4P
Adder
30.71
970833AG2-524 GEN
Solar/Wind Harmer
16.286
970833AG2-524 GEN
Solar/Wind Harmer
7.575
270536AF1-215 GEN2
Solar/Wind Harmer
8.428
274746AC1-111 G10
Adder
10.357
274744AC1-111 GEN8
Adder
10.357
958711AF2-162 GEN
Solar/Wind Harmer
1.82
958391AF2-133 GEN
Solar/Wind Harmer
16.304
971177AH1-047 GEN
Solar/Wind Harmer
10.518
276868AE1-113 GEN
Solar/Wind Harmer
18.162
276882AE2-255 GEN
Solar/Wind Harmer
6.054
971411AH1-196 GEN
Solar/Wind Harmer
26.803
971675AH1-338 GEN
Solar/Wind Harmer
32.161
971549AH1-272 GEN
Solar/Wind Harmer
32.93
274863CRW1-WTG
Solar/Wind Harmer
9.908
274864CRW2-WTG
Solar/Wind Harmer
9.908
274823ROCKFORD ;21
Adder
34.435
270284AF1-227 GEN1
Solar/Wind Helper
2.32
270286AF1-227 GEN2
Solar/Wind Helper
0.851
270287AF1-227 GEN3
Solar/Wind Helper
0.851
270054AF2-122 C O1
Solar/Wind Helper
1.203
971171AH1-044 GEN
Solar/Wind Harmer
13.312
24344105CKG2
50/50
16.752
24727005RPMNG1
50/50
2.039
270143AC1-141 CT2_
50/50
4.843
24639705ELKHART HY
50/50
0.328
970521AG2-332 GEN
50/50
23.389
24307105BERRINSP G
50/50
0.043
965011AG1-365 GEN
Solar/Wind Harmer
21.485
965421AG1-410 GEN
Solar/Wind Harmer
64.386
246936BC-WTG1
Solar/Wind Harmer
8.398
270489AE1-102 GEN1
Solar/Wind Harmer
2.79
970245AG2-165 GEN
Solar/Wind Harmer
37.203
270063AE2-323 C
Solar/Wind Harmer
4.466
270505AE1-170 C O1
Solar/Wind Harmer
30.011
945111AF1-176 GEN
Solar/Wind Harmer
35.611
270449AD2-020 GEN
Solar/Wind Harmer
5.542
943021AE2-325 GEN
Solar/Wind Harmer
7.201
972207SS24-0001
Solar/Wind Harmer
42.777
274773LINCOLN ;4U
Adder
12.031
274774LINCOLN ;5U
Adder
12.031
274723RIVER EC ;12
Adder
34.382
274751CRETE EC ;1U
Adder
9.363
274754CRETE EC ;4U
Adder
9.363
276164X3-005 C
Solar/Wind Harmer
1.342
274812UNIV PK N;8U
Adder
9.534
970373AG2-245 GEN
Solar/Wind Harmer
39.866
276776AD2-060 GEN
Solar/Wind Harmer
0.799
274801UNIV PARK;4U
Adder
11.02
941551AE2-152 GEN
Solar/Wind Harmer
8.523
274676JOLIET 29;8U
Adder
57.483
274674JOLIET 9 ;6U
Adder
28.794
274732ELWOOD EC;7P
Adder
30.711
274871GR RIDGE ;2U
Solar/Wind Harmer
14.337
270055AF2-134 C O1
Solar/Wind Harmer
5.618
274745AC1-111 GEN9
Adder
10.357
276691AA1-018 GEN1
Solar/Wind Harmer
0.851
274682WAUKEGAN ;7U
Adder
32.824
274828WAUKEGAN ;BP
Adder
20.145
958381AF2-132 GEN
Solar/Wind Harmer
16.482
964861AG1-349 GEN
Solar/Wind Harmer
14.25
971917AH1-482 GEN
Solar/Wind Harmer
16.444
960751AF2-366 GEN
Solar/Wind Harmer
5.194
962781AG1-127 GEN
Solar/Wind Harmer
17.216
274872LEEDK;1U
Solar/Wind Harmer
14.832
939401AE1-172 GEN
Solar/Wind Harmer
25.153
276901AD2-066 C O1
Solar/Wind Harmer
6.326
965651AG1-433 GEN
Solar/Wind Harmer
9.83
971997AH1-543 GEN
Solar/Wind Harmer
28.2
276861AD2-134 GEN
Solar/Wind Harmer
3.19
274822ROCKFORD ;11
Adder
34.687
972235AH1-702 GEN1
Adder
4.443
274761LEE CO EC;2U
Adder
16.13
274766LEE CO EC;7U
Adder
15.94
24728605AND G2
Adder
4.583
270349AD2-093_GEN
Solar/Wind Helper
1.743
957471AF2-041 GEN
Solar/Wind Harmer
19.968
959081AF2-199 GEN
Solar/Wind Harmer
6.656
971067AG2-660 GEN
Solar/Wind Harmer
1.548
970615AG2-402 GEN
50/50
4.996
270102X2-052 ST
50/50
3.216
270100X2-052 CT1
50/50
2.963
270101X2-052 CT2
50/50
2.963
247620Y3-023
50/50
0.981
970611AG2-400 GEN
Solar/Wind Harmer
21.485
246938BC-WTG3
Solar/Wind Harmer
8.542
246937BC-WTG2
Solar/Wind Harmer
8.398
970321AG2-212 GEN
Solar/Wind Harmer
37.203
270216AD2-079_GEN
Solar/Wind Harmer
1.229
270526AF1-158 GEN
Solar/Wind Harmer
9.099
957891AF2-083 GEN
Solar/Wind Harmer
6.742
960981AF2-389 GEN
Solar/Wind Harmer
3.021
24441505OLIV SLR
Solar/Wind Harmer
0.268
965681AG1-436 GEN
Solar/Wind Harmer
24.955
965791AG1-447 GEN
Solar/Wind Harmer
12.768
961051AF2-396 GEN
Solar/Wind Harmer
31.495
961051AF2-396 GEN
Solar/Wind Harmer
14.649
274770LINCOLN ;1U
Adder
12.031
274771LINCOLN ;2U
Adder
12.031
274808UNIV PK N;4U
Adder
9.492
274803UNIV PARK;6U
Adder
11.035
972259AH1-714 GEN
Adder
36.075
274888KELLY CRK;1U
Solar/Wind Harmer
11.16
274887GEN-1.85
Solar/Wind Harmer
10.076
276843GEN-1.7
Solar/Wind Harmer
1.084
958011AF2-095 GEN
Solar/Wind Harmer
27.22
274674JOLIET 9 ;6U
Adder
28.794
274847GR RIDGE ;BU
Solar/Wind Harmer
9.431
971573AH1-285 GEN
Solar/Wind Harmer
15.868
274695ROCKY RD ;2P
Adder
20.37
274693ROCKY RD ;1P
Adder
20.17
274697ROCKY RD ;3P
Adder
5.534
274696ROCKY RD ;4P
Adder
20.85
958481AF2-142 GEN
Solar/Wind Harmer
27.421
274861TOP CROP ;1U
Solar/Wind Harmer
11.071
274862TOP CROP ;2U
Solar/Wind Harmer
9.244
274683WAUKEGAN ;8U
Adder
38.432
274683WAUKEGAN ;8U
Adder
32.396
962691AG1-118 GEN
Solar/Wind Harmer
54.457
970921AG2-575 GEN
Solar/Wind Harmer
18.103
970921AG2-575 GEN
Solar/Wind Harmer
4.21
958491AF2-143 GEN
Solar/Wind Harmer
27.059
944541AF1-119 GEN
Solar/Wind Harmer
7.534
960971AF2-388 GEN
Solar/Wind Harmer
19.66
942991AE2-321 GEN
Solar/Wind Harmer
17.957
274879MINONK ;1U
Solar/Wind Harmer
12.109
971333AH1-146 GEN
Solar/Wind Harmer
35.709
971335AH1-147 GEN
Solar/Wind Harmer
35.709
274764LEE CO EC;5U
Adder
16.168
274765LEE CO EC;6U
Adder
16.168
274762LEE CO EC;3U
Adder
16.13
274763LEE CO EC;4U
Adder
15.978
972267AH1-718 GEN
Adder
7.14
247621Y3-024
Adder
0.307
270471AD2-092_GEN
Solar/Wind Helper
1.743
971341AH1-150 GEN
Solar/Wind Harmer
13.312
971343AH1-151 GEN
Solar/Wind Harmer
13.312
970707AG2-453 GEN
Solar/Wind Harmer
53.178
274802UNIV PARK;5U
Adder
11.035
274826FISK ;BP
Adder
20.719
276772AC2-154 GEN
Solar/Wind Harmer
5.271
276806AD2-047 C O1
Solar/Wind Harmer
20.222
970941AG2-585 GEN
Solar/Wind Harmer
23.629
274800UNIV PARK;3U
Adder
11.02
972038AH1-567 GEN2
Adder
0.69
972228AH1-698 GEN2
Adder
6.996
276897AD1-100 C
Solar/Wind Harmer
54.537
939351AE1-166 GEN
Solar/Wind Harmer
11.143
274676JOLIET 29;8U
Adder
55.43
274730ELWOOD EC;6P
Adder
30.711
274734ELWOOD EC;8P
Adder
30.711
274736ELWOOD EC;9P
Adder
30.711
274729ELWOOD EC;1P
Adder
30.71
276893AG1-478 C
Solar/Wind Harmer
0.78
943121AE2-341 GEN
Solar/Wind Harmer
27.85
943591AF1-030 GEN
Solar/Wind Harmer
18.567
270535AF1-215 GEN1
Solar/Wind Harmer
8.428
276694AA1-018 GEN2
Solar/Wind Harmer
11.537
274682WAUKEGAN ;7U
Adder
32.824
964401AG1-302 GEN
Solar/Wind Harmer
16.482
274872LEEDK;1U
Solar/Wind Harmer
0.462
276805AD2-038 GEN
Solar/Wind Harmer
9.254
276799AD1-013 GEN
Solar/Wind Harmer
3.952
946671AF1-331 GEN
Solar/Wind Harmer
0.748
274855GSG-6 ;RU
Solar/Wind Harmer
6.597
274850MENDOTA H;RU
Solar/Wind Harmer
4.587
276602WESTBROOK C
Solar/Wind Harmer
3.797
276863AD2-134 GEN
Solar/Wind Harmer
3.19
959141AF2-205 GEN
Solar/Wind Harmer
10.776
972236AH1-702 GEN2
Adder
3.863
274760LEE CO EC;1U
Adder
16.13
274767LEE CO EC;8U
Adder
15.94
24728705AND G3
Adder
9.586
24728505AND G1
Adder
4.583
959091AF2-200 GEN
Solar/Wind Harmer
13.312
944201AF1-088_MTX
Adder
133.023
957141AF2-008_MTX
Adder
52.933
LAGNLTFEXP_LAGN->PJM
CLTF
13.148
TVALTFEXP_TVA->PJM
CLTF
5.021
CBM West 2LTFEXP_CBM-W2->PJM
CBM
118.577
NYPJM->LTFIMP_NY
CLTF
3.196
LGEELTFEXP_LGEE->PJM
CLTF
4.313
WECLTFEXP_WEC->PJM
CLTF
6.719
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.8
AG2-052LTFEXP_AG2-052->PJM
LTF
0.422
AH1-155LTFEXP_AH1-155->PJM
LTF
0.633
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.282
CBM West 1LTFEXP_CBM-W1->PJM
CBM
201.554
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.706
MECLTFEXP_MEC->PJM
CLTF
24.31
SIGELTFEXP_SIGE->PJM
CLTF
0.467

Details for 05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line l/o AEP_P7-1_#11010___SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P7-1_#11010___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:105.44 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5823.68
MW Contribution:32.98
Bus #Bus NameTypeMW Contribution
270142AC1-141 CT1_
50/50
4.85
24641605TWIN BRNCH
50/50
0.035
24344005CKG1
50/50
13.183
24642205MAYFLWER
50/50
1.35
944961AF1-161 GEN
50/50
5.755
962601AG1-109 GEN
50/50
5.755
270043AE2-236 GEN
Solar/Wind Harmer
11.845
970349AG2-230 GEN
Solar/Wind Harmer
32.247
970513AG2-328 GEN
Solar/Wind Harmer
37.354
970517AG2-330 GEN
Solar/Wind Harmer
33.879
959331AF2-224 GEN
Solar/Wind Harmer
20.561
965021AG1-366 GEN
Solar/Wind Harmer
4.782
247643Z2-116 C
Solar/Wind Harmer
0.142
970031AG2-029 GEN
Solar/Wind Harmer
60.641
944531AF1-118 GEN
Solar/Wind Harmer
70.444
945111AF1-176 GEN
Solar/Wind Harmer
11.293
274772LINCOLN ;3U
Adder
12.075
24441205WTRV SLR C
Solar/Wind Harmer
0.261
274724RIVER EC ;11
Adder
34.095
972231SS25-0005
Solar/Wind Harmer
18.237
972181SS23-001
Solar/Wind Harmer
11.398
274752CRETE EC ;2U
Adder
9.392
274753CRETE EC ;3U
Adder
9.392
247604X1-042
Adder
0.796
970707AG2-453 GEN
Solar/Wind Harmer
53.373
274802UNIV PARK;5U
Adder
11.073
970615AG2-402 GEN
50/50
4.782
270102X2-052 ST
50/50
3.225
270100X2-052 CT1
50/50
2.972
270101X2-052 CT2
50/50
2.972
247620Y3-023
50/50
0.979
24729405KEY G3
50/50
0.737
24729305KEY G2
50/50
0.724
24729205KEY G1
50/50
0.721
970321AG2-212 GEN
Solar/Wind Harmer
37.354
970611AG2-400 GEN
Solar/Wind Harmer
20.561
270216AD2-079_GEN
Solar/Wind Harmer
1.23
270526AF1-158 GEN
Solar/Wind Harmer
9.119
24441505OLIV SLR
Solar/Wind Harmer
0.268
965681AG1-436 GEN
Solar/Wind Harmer
25.028
965791AG1-447 GEN
Solar/Wind Harmer
12.805
957891AF2-083 GEN
Solar/Wind Harmer
6.749
960981AF2-389 GEN
Solar/Wind Harmer
3.024
961051AF2-396 GEN
Solar/Wind Harmer
31.526
961051AF2-396 GEN
Solar/Wind Harmer
14.663
274770LINCOLN ;1U
Adder
12.075
274771LINCOLN ;2U
Adder
12.075
274808UNIV PK N;4U
Adder
9.523
274803UNIV PARK;6U
Adder
11.073
972259AH1-714 GEN
Adder
36.205
274888KELLY CRK;1U
Solar/Wind Harmer
11.199
274887GEN-1.85
Solar/Wind Harmer
10.111
276843GEN-1.7
Solar/Wind Harmer
1.088
958011AF2-095 GEN
Solar/Wind Harmer
27.315
274674JOLIET 9 ;6U
Adder
28.897
274847GR RIDGE ;BU
Solar/Wind Harmer
9.466
971573AH1-285 GEN
Solar/Wind Harmer
15.928
274695ROCKY RD ;2P
Adder
20.447
274693ROCKY RD ;1P
Adder
20.246
274697ROCKY RD ;3P
Adder
5.555
274696ROCKY RD ;4P
Adder
20.929
958481AF2-142 GEN
Solar/Wind Harmer
27.523
274861TOP CROP ;1U
Solar/Wind Harmer
11.112
274862TOP CROP ;2U
Solar/Wind Harmer
9.279
274683WAUKEGAN ;8U
Adder
38.577
274683WAUKEGAN ;8U
Adder
32.519
962691AG1-118 GEN
Solar/Wind Harmer
54.666
944541AF1-119 GEN
Solar/Wind Harmer
7.616
960971AF2-388 GEN
Solar/Wind Harmer
19.875
970921AG2-575 GEN
Solar/Wind Harmer
18.172
970921AG2-575 GEN
Solar/Wind Harmer
4.226
958491AF2-143 GEN
Solar/Wind Harmer
27.161
942991AE2-321 GEN
Solar/Wind Harmer
18.026
274879MINONK ;1U
Solar/Wind Harmer
12.156
971333AH1-146 GEN
Solar/Wind Harmer
35.848
971335AH1-147 GEN
Solar/Wind Harmer
35.848
274764LEE CO EC;5U
Adder
16.233
274765LEE CO EC;6U
Adder
16.233
274762LEE CO EC;3U
Adder
16.195
274763LEE CO EC;4U
Adder
16.043
24344105CKG2
50/50
16.81
270143AC1-141 CT2_
50/50
4.85
24639705ELKHART HY
50/50
0.328
970521AG2-332 GEN
50/50
23.355
24307105BERRINSP G
50/50
0.043
970245AG2-165 GEN
Solar/Wind Harmer
37.354
965011AG1-365 GEN
Solar/Wind Harmer
20.561
270063AE2-323 C
Solar/Wind Harmer
4.439
270505AE1-170 C O1
Solar/Wind Harmer
30.051
945111AF1-176 GEN
Solar/Wind Harmer
35.632
270449AD2-020 GEN
Solar/Wind Harmer
5.549
943021AE2-325 GEN
Solar/Wind Harmer
7.21
972207SS24-0001
Solar/Wind Harmer
42.931
274773LINCOLN ;4U
Adder
12.075
274774LINCOLN ;5U
Adder
12.075
274723RIVER EC ;12
Adder
34.493
274751CRETE EC ;1U
Adder
9.392
274754CRETE EC ;4U
Adder
9.392
276164X3-005 C
Solar/Wind Harmer
1.346
274812UNIV PK N;8U
Adder
9.565
970373AG2-245 GEN
Solar/Wind Harmer
39.985
276776AD2-060 GEN
Solar/Wind Harmer
0.802
274801UNIV PARK;4U
Adder
11.059
941551AE2-152 GEN
Solar/Wind Harmer
8.554
274676JOLIET 29;8U
Adder
57.689
274674JOLIET 9 ;6U
Adder
28.897
274732ELWOOD EC;7P
Adder
30.821
274871GR RIDGE ;2U
Solar/Wind Harmer
14.39
270055AF2-134 C O1
Solar/Wind Harmer
5.635
274745AC1-111 GEN9
Adder
10.396
276691AA1-018 GEN1
Solar/Wind Harmer
0.854
274682WAUKEGAN ;7U
Adder
32.947
274828WAUKEGAN ;BP
Adder
20.221
958381AF2-132 GEN
Solar/Wind Harmer
16.533
964861AG1-349 GEN
Solar/Wind Harmer
14.293
971917AH1-482 GEN
Solar/Wind Harmer
16.494
965651AG1-433 GEN
Solar/Wind Harmer
9.938
960751AF2-366 GEN
Solar/Wind Harmer
5.214
962781AG1-127 GEN
Solar/Wind Harmer
17.282
274872LEEDK;1U
Solar/Wind Harmer
14.889
939401AE1-172 GEN
Solar/Wind Harmer
25.25
276901AD2-066 C O1
Solar/Wind Harmer
6.35
971997AH1-543 GEN
Solar/Wind Harmer
28.31
276861AD2-134 GEN
Solar/Wind Harmer
3.203
274822ROCKFORD ;11
Adder
34.824
972235AH1-702 GEN1
Adder
4.461
274761LEE CO EC;2U
Adder
16.195
274766LEE CO EC;7U
Adder
16.004
24728605AND G2
Adder
4.622
970091AG2-072 GEN
Adder
1.052
270349AD2-093_GEN
Solar/Wind Helper
1.724
957471AF2-041 GEN
Solar/Wind Harmer
42.297
959081AF2-199 GEN
Solar/Wind Harmer
14.099
971067AG2-660 GEN
Solar/Wind Harmer
3.279
971599AH1-298 GEN
50/50
20.751
270144AC1-141 ST1_
50/50
4.296
24653605MOTTVILLE
50/50
0.008
24643105BUCHANAN
50/50
0.026
24729505KEY G4
50/50
13.5
971347AH1-153 GEN
Solar/Wind Harmer
32.247
270071AF1-092 GEN
Solar/Wind Harmer
31.239
971771AH1-392 GEN
Solar/Wind Harmer
18.224
971769AH1-391 GEN
Solar/Wind Harmer
20.026
960681AF2-359 GEN
Solar/Wind Harmer
7.564
944161AF1-084 GEN
Solar/Wind Harmer
4.344
274775LINCOLN ;6U
Adder
12.075
274776LINCOLN ;7U
Adder
12.075
274777LINCOLN ;8U
Adder
12.075
274814UNIV PK N;0U
Adder
9.649
274807UNIV PK N;3U
Adder
9.628
274805UNIV PK N;1U
Adder
9.586
274811UNIV PK N;7U
Adder
9.565
972037AH1-567 GEN1
Adder
0.348
274827FISK ;RP
Adder
14.734
960591AF2-350 GEN
Solar/Wind Harmer
18.969
972227AH1-698 GEN1
Adder
4.944
274687WILL CNTY;4U
Adder
52.61
274687WILL CNTY;4U
Adder
52.61
274675JOLIET 29;7U
Adder
57.69
274675JOLIET 29;7U
Adder
55.63
274728ELWOOD EC;5P
Adder
30.821
274731ELWOOD EC;2P
Adder
30.821
274733ELWOOD EC;3P
Adder
30.821
274735ELWOOD EC;4P
Adder
30.821
970833AG2-524 GEN
Solar/Wind Harmer
16.346
970833AG2-524 GEN
Solar/Wind Harmer
7.603
270536AF1-215 GEN2
Solar/Wind Harmer
8.453
274746AC1-111 G10
Adder
10.396
274744AC1-111 GEN8
Adder
10.396
958711AF2-162 GEN
Solar/Wind Harmer
1.84
958391AF2-133 GEN
Solar/Wind Harmer
16.354
971177AH1-047 GEN
Solar/Wind Harmer
10.559
276868AE1-113 GEN
Solar/Wind Harmer
18.232
276882AE2-255 GEN
Solar/Wind Harmer
6.078
971411AH1-196 GEN
Solar/Wind Harmer
26.908
971675AH1-338 GEN
Solar/Wind Harmer
32.287
971549AH1-272 GEN
Solar/Wind Harmer
32.985
274863CRW1-WTG
Solar/Wind Harmer
9.948
274864CRW2-WTG
Solar/Wind Harmer
9.948
274823ROCKFORD ;21
Adder
34.571
270284AF1-227 GEN1
Solar/Wind Helper
2.284
270286AF1-227 GEN2
Solar/Wind Helper
0.838
270287AF1-227 GEN3
Solar/Wind Helper
0.838
270054AF2-122 C O1
Solar/Wind Helper
1.189
971171AH1-044 GEN
Solar/Wind Harmer
28.198
274826FISK ;BP
Adder
20.79
276772AC2-154 GEN
Solar/Wind Harmer
5.29
276806AD2-047 C O1
Solar/Wind Harmer
20.292
970941AG2-585 GEN
Solar/Wind Harmer
23.711
274800UNIV PARK;3U
Adder
11.059
972038AH1-567 GEN2
Adder
0.692
972228AH1-698 GEN2
Adder
7.021
276897AD1-100 C
Solar/Wind Harmer
54.734
939351AE1-166 GEN
Solar/Wind Harmer
11.184
274676JOLIET 29;8U
Adder
55.629
274730ELWOOD EC;6P
Adder
30.821
274734ELWOOD EC;8P
Adder
30.821
274736ELWOOD EC;9P
Adder
30.821
274729ELWOOD EC;1P
Adder
30.821
276893AG1-478 C
Solar/Wind Harmer
0.783
943121AE2-341 GEN
Solar/Wind Harmer
27.954
943591AF1-030 GEN
Solar/Wind Harmer
18.636
270535AF1-215 GEN1
Solar/Wind Harmer
8.453
276694AA1-018 GEN2
Solar/Wind Harmer
11.579
274682WAUKEGAN ;7U
Adder
32.947
964401AG1-302 GEN
Solar/Wind Harmer
16.533
274872LEEDK;1U
Solar/Wind Harmer
0.464
276805AD2-038 GEN
Solar/Wind Harmer
9.289
276799AD1-013 GEN
Solar/Wind Harmer
3.967
946671AF1-331 GEN
Solar/Wind Harmer
0.751
274855GSG-6 ;RU
Solar/Wind Harmer
6.623
274850MENDOTA H;RU
Solar/Wind Harmer
4.605
276602WESTBROOK C
Solar/Wind Harmer
3.812
276863AD2-134 GEN
Solar/Wind Harmer
3.203
959141AF2-205 GEN
Solar/Wind Harmer
10.81
972236AH1-702 GEN2
Adder
3.879
274760LEE CO EC;1U
Adder
16.195
274767LEE CO EC;8U
Adder
16.004
24728705AND G3
Adder
9.666
24728505AND G1
Adder
4.622
959091AF2-200 GEN
Solar/Wind Harmer
28.198
972267AH1-718 GEN
Adder
7.169
247621Y3-024
Adder
0.306
270471AD2-092_GEN
Solar/Wind Helper
1.724
971341AH1-150 GEN
Solar/Wind Harmer
28.198
971343AH1-151 GEN
Solar/Wind Harmer
28.198
944201AF1-088_MTX
Adder
133.959
957141AF2-008_MTX
Adder
66.98
LAGNLTFEXP_LAGN->PJM
CLTF
13.321
TVALTFEXP_TVA->PJM
CLTF
5.11
CBM West 2LTFEXP_CBM-W2->PJM
CBM
119.715
NYPJM->LTFIMP_NY
CLTF
3.14
LGEELTFEXP_LGEE->PJM
CLTF
4.376
WECLTFEXP_WEC->PJM
CLTF
6.746
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.739
AG2-052LTFEXP_AG2-052->PJM
LTF
0.423
AH1-155LTFEXP_AH1-155->PJM
LTF
0.635
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.245
CBM West 1LTFEXP_CBM-W1->PJM
CBM
202.385
CBM South 1LTFEXP_CBM-S1->PJM
CBM
20.042
MECLTFEXP_MEC->PJM
CLTF
24.435
SIGELTFEXP_SIGE->PJM
CLTF
0.471

Details for 05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line l/o AEP_P1-2_#6463_16757_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#6463_16757_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.68 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5781.3
MW Contribution:25.63
Bus #Bus NameTypeMW Contribution
24344105CKG2
50/50
16.743
24727105RPMNG2
50/50
2.043
965431AG1-411 GEN
50/50
24.916
270142AC1-141 CT1_
50/50
4.84
24641605TWIN BRNCH
50/50
0.035
24344005CKG1
50/50
13.145
24642205MAYFLWER
50/50
1.347
944961AF1-161 GEN
50/50
5.744
962601AG1-109 GEN
50/50
5.744
270043AE2-236 GEN
Solar/Wind Harmer
9.614
959331AF2-224 GEN
Solar/Wind Harmer
10.476
965021AG1-366 GEN
Solar/Wind Harmer
4.988
270491AE1-102 GEN2
Solar/Wind Harmer
1.943
970349AG2-230 GEN
Solar/Wind Harmer
22.406
970513AG2-328 GEN
Solar/Wind Harmer
6.295
970517AG2-330 GEN
Solar/Wind Harmer
37.773
970031AG2-029 GEN
Solar/Wind Harmer
9.246
247643Z2-116 C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
11.278
944531AF1-118 GEN
Solar/Wind Harmer
62.173
274772LINCOLN ;3U
Adder
16.368
24441205WTRV SLR C
Solar/Wind Harmer
0
274724RIVER EC ;11
Adder
33.965
274752CRETE EC ;2U
Adder
15.774
970615AG2-402 GEN
50/50
4.988
270102X2-052 ST
50/50
3.214
270100X2-052 CT1
50/50
2.961
270101X2-052 CT2
50/50
2.961
247620Y3-023
50/50
0.98
970611AG2-400 GEN
Solar/Wind Harmer
14.965
970627AG2-408 GEN
Solar/Wind Harmer
4.49
246938BC-WTG3
Solar/Wind Harmer
0.542
246937BC-WTG2
Solar/Wind Harmer
0.606
970321AG2-212 GEN
Solar/Wind Harmer
6.295
270216AD2-079_GEN
Solar/Wind Harmer
0.002
270526AF1-158 GEN
Solar/Wind Harmer
0.017
971599AH1-298 GEN
50/50
20.512
24727205RPMNG3
50/50
2.026
270144AC1-141 ST1_
50/50
4.287
24653605MOTTVILLE
50/50
0.008
24643105BUCHANAN
50/50
0.025
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
1.893
971347AH1-153 GEN
Solar/Wind Harmer
22.406
270071AF1-092 GEN
Solar/Wind Harmer
27.685
971771AH1-392 GEN
Solar/Wind Harmer
14.093
971619AH1-309 GEN
Solar/Wind Harmer
6.277
971769AH1-391 GEN
Solar/Wind Harmer
15.555
960681AF2-359 GEN
Solar/Wind Harmer
-0.002
274775LINCOLN ;6U
Adder
16.368
274776LINCOLN ;7U
Adder
16.368
274777LINCOLN ;8U
Adder
16.368
24729505KEY G4
Adder
12.57
274814UNIV PK N;0U
Adder
9.612
274807UNIV PK N;3U
Adder
9.591
274805UNIV PK N;1U
Adder
9.549
274811UNIV PK N;7U
Adder
9.528
972037AH1-567 GEN1
Adder
0.346
274827FISK ;RP
Adder
14.675
960591AF2-350 GEN
Solar/Wind Harmer
13.18
972227AH1-698 GEN1
Adder
4.923
274687WILL CNTY;4U
Adder
52.393
274687WILL CNTY;4U
Adder
52.393
274675JOLIET 29;7U
Adder
57.451
274675JOLIET 29;7U
Adder
55.399
274731ELWOOD EC;2P
Adder
30.692
274733ELWOOD EC;3P
Adder
30.692
274735ELWOOD EC;4P
Adder
30.692
274728ELWOOD EC;5P
Adder
30.693
970833AG2-524 GEN
Solar/Wind Harmer
14.308
970833AG2-524 GEN
Solar/Wind Harmer
9.539
270536AF1-215 GEN2
Solar/Wind Harmer
0.016
274746AC1-111 G10
Adder
10.351
274744AC1-111 GEN8
Adder
10.351
958391AF2-133 GEN
Solar/Wind Harmer
0.002
971177AH1-047 GEN
Solar/Wind Harmer
7.718
276868AE1-113 GEN
Solar/Wind Harmer
2.511
276882AE2-255 GEN
Solar/Wind Harmer
1.463
971411AH1-196 GEN
Solar/Wind Harmer
18.689
971675AH1-338 GEN
Solar/Wind Harmer
4.859
971549AH1-272 GEN
Solar/Wind Harmer
25.626
274863CRW1-WTG
Solar/Wind Harmer
0.004
274864CRW2-WTG
Solar/Wind Harmer
0.004
971171AH1-044 GEN
Solar/Wind Harmer
24.739
274823ROCKFORD ;21
Adder
34.415
971611AH1-305 GEN
Solar/Wind Harmer
7.323
963791AG1-232 GEN
Solar/Wind Harmer
16.568
276612AE2-035 GEN
Solar/Wind Harmer
0.003
965101AG1-375 GEN
Solar/Wind Harmer
12.216
926823AC1-168 GEN
Solar/Wind Harmer
2.071
970169AG2-114 GEN
Solar/Wind Harmer
12.156
971681AH1-341 GEN
Solar/Wind Harmer
19.553
961011AF2-392 GEN
Solar/Wind Harmer
7.036
965041AG1-368 GEN
Solar/Wind Harmer
11.932
957751AF2-069 GEN
Solar/Wind Harmer
0.392
274848CAMPGROVE;RU
Solar/Wind Harmer
0.002
24690905MDL-1G C
Solar/Wind Harmer
0.004
270180AB1-006 GEN1
Solar/Wind Harmer
0.003
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.002
270181AB1-006 GEN2
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0.005
276656WTG2_EQ
Solar/Wind Harmer
0.001
959341AF2-225 GEN
Solar/Wind Harmer
12.245
941731AE2-173 GEN
Solar/Wind Harmer
9.718
945581AF1-223 GEN
Solar/Wind Harmer
0.001
946321AF1-296 GEN
Solar/Wind Harmer
6.48
24386205FR-12G C
Solar/Wind Harmer
0.002
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.002
963841AG1-237 GEN
Solar/Wind Harmer
4.707
971609AH1-304 GEN
Solar/Wind Harmer
1.767
965051AG1-369 GEN
Solar/Wind Harmer
5.379
970289AG2-191 GEN
Solar/Wind Harmer
2.036
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.39
276848AB2-070 GEN3
Solar/Wind Harmer
0.388
270594AE1-207 GEN
Solar/Wind Harmer
11.748
270024AE2-089 GEN
Solar/Wind Harmer
0.011
970115AG2-085 GEN
Solar/Wind Harmer
3.968
24725505WLD G2 C
Solar/Wind Harmer
0.002
24699105WLD G1 C
Solar/Wind Harmer
0.001
944221AF1-090 GEN
Solar/Wind Harmer
5.647
270240V3-007_GEN2
Solar/Wind Harmer
0.003
247607V1-011 GEN
Solar/Wind Harmer
0.001
270543AE2-219 C
Solar/Wind Harmer
0.005
971029AG2-637 GEN
Solar/Wind Harmer
10.94
971673AH1-337 GEN
Solar/Wind Harmer
4.593
270284AF1-227 GEN1
Solar/Wind Helper
2.302
270286AF1-227 GEN2
Solar/Wind Helper
0.844
270287AF1-227 GEN3
Solar/Wind Helper
0.844
270054AF2-122 C O1
Solar/Wind Helper
1.201
274753CRETE EC ;3U
Adder
15.774
247604X1-042
Adder
0.795
970707AG2-453 GEN
Solar/Wind Harmer
43.26
274802UNIV PARK;5U
Adder
11.029
274826FISK ;BP
Adder
20.707
274800UNIV PARK;3U
Adder
11.014
972038AH1-567 GEN2
Adder
0.689
276806AD2-047 C O1
Solar/Wind Harmer
7.469
970941AG2-585 GEN
Solar/Wind Harmer
16.476
972228AH1-698 GEN2
Adder
6.992
276897AD1-100 C
Solar/Wind Harmer
0.017
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
274676JOLIET 29;8U
Adder
55.398
274729ELWOOD EC;1P
Adder
30.692
274730ELWOOD EC;6P
Adder
30.693
274734ELWOOD EC;8P
Adder
30.693
274736ELWOOD EC;9P
Adder
30.693
276893AG1-478 C
Solar/Wind Harmer
0.516
943121AE2-341 GEN
Solar/Wind Harmer
21.706
943591AF1-030 GEN
Solar/Wind Harmer
14.435
270535AF1-215 GEN1
Solar/Wind Harmer
0.016
276694AA1-018 GEN2
Solar/Wind Harmer
0.002
274682WAUKEGAN ;7U
Adder
32.805
964401AG1-302 GEN
Solar/Wind Harmer
0.002
274872LEEDK;1U
Solar/Wind Harmer
0.462
276805AD2-038 GEN
Solar/Wind Harmer
0.004
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
1.33
274855GSG-6 ;RU
Solar/Wind Harmer
0.457
274850MENDOTA H;RU
Solar/Wind Harmer
0.147
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.223
959141AF2-205 GEN
Solar/Wind Harmer
-0.003
959091AF2-200 GEN
Solar/Wind Harmer
24.739
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
3.861
970571AG2-364 GEN
Solar/Wind Harmer
24.37
274858EASY ROAD;U2
Solar/Wind Harmer
0.002
274760LEE CO EC;1U
Adder
16.12
274767LEE CO EC;8U
Adder
15.93
276157O29GEN1
Solar/Wind Harmer
1.927
274878BISHOP HL;2U
Solar/Wind Harmer
0.397
24755605MDL-5G
Solar/Wind Harmer
0.002
970781AG2-491 GEN
Solar/Wind Harmer
11.712
942111AE2-223 GEN
Solar/Wind Harmer
3.79
965931AG1-462 GEN
Solar/Wind Harmer
29.323
274853TWINGROVE;U1
Solar/Wind Harmer
0.005
965091AG1-374 GEN
Solar/Wind Harmer
34.294
959611AF2-252 GEN
Solar/Wind Harmer
3.81
247642Z2-115 C
Solar/Wind Harmer
0.005
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.07
970289AG2-191 GEN
Solar/Wind Harmer
1.179
970291AG2-192 GEN
Solar/Wind Harmer
1.072
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
4.944
276668AB2-070 GEN1
Solar/Wind Harmer
0.39
276621W2-048 GEN
Solar/Wind Harmer
0.529
276838X2-022 GEN2
Solar/Wind Harmer
0.591
971617AH1-308 GEN
Solar/Wind Harmer
8.654
958821AF2-173 GEN
Solar/Wind Harmer
14.235
270004AE1-209 GEN
Solar/Wind Harmer
2.203
942481AE2-261 GEN
Solar/Wind Harmer
30.115
946031AF1-268 GEN
Solar/Wind Harmer
9.153
970193AG2-126 GEN
Solar/Wind Harmer
14.08
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
13.732
270437AC2-090 C
Solar/Wind Harmer
0.004
270404AC1-167 GEN
Solar/Wind Harmer
0.004
270258AD1-119 GEN
Solar/Wind Harmer
0.002
24728705AND G3
Adder
9.578
24728505AND G1
Adder
4.579
970243AG2-164 GEN
Solar/Wind Harmer
4.523
970519AG2-331 GEN
Solar/Wind Harmer
20.102
970699AG2-449 GEN
Solar/Wind Harmer
1.933
270356AE2-297 GEN
Solar/Wind Harmer
0.01
24727005RPMNG1
50/50
2.036
270143AC1-141 CT2_
50/50
4.84
24639705ELKHART HY
50/50
0.328
970521AG2-332 GEN
50/50
23.369
24307105BERRINSP G
50/50
0.043
965011AG1-365 GEN
Solar/Wind Harmer
14.965
965421AG1-410 GEN
Solar/Wind Harmer
44.849
246936BC-WTG1
Solar/Wind Harmer
0.606
270489AE1-102 GEN1
Solar/Wind Harmer
1.943
970245AG2-165 GEN
Solar/Wind Harmer
6.295
270063AE2-323 C
Solar/Wind Harmer
0.012
270505AE1-170 C O1
Solar/Wind Harmer
14.646
945111AF1-176 GEN
Solar/Wind Harmer
24.826
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
7.196
274773LINCOLN ;4U
Adder
16.368
274774LINCOLN ;5U
Adder
16.368
274723RIVER EC ;12
Adder
34.361
274751CRETE EC ;1U
Adder
15.774
274754CRETE EC ;4U
Adder
15.774
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
9.528
970373AG2-245 GEN
Solar/Wind Harmer
27.796
274801UNIV PARK;4U
Adder
11.014
276776AD2-060 GEN
Solar/Wind Harmer
1.376
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
57.45
274674JOLIET 9 ;6U
Adder
28.777
274732ELWOOD EC;7P
Adder
30.693
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0.01
274745AC1-111 GEN9
Adder
10.351
276691AA1-018 GEN1
Solar/Wind Harmer
1.544
274682WAUKEGAN ;7U
Adder
32.805
274828WAUKEGAN ;BP
Adder
20.134
958381AF2-132 GEN
Solar/Wind Harmer
0.002
964861AG1-349 GEN
Solar/Wind Harmer
-0.002
971917AH1-482 GEN
Solar/Wind Harmer
16.434
962781AG1-127 GEN
Solar/Wind Harmer
12.012
274872LEEDK;1U
Solar/Wind Harmer
0.008
939401AE1-172 GEN
Solar/Wind Harmer
9.413
276901AD2-066 C O1
Solar/Wind Harmer
0.012
965651AG1-433 GEN
Solar/Wind Harmer
3.678
971997AH1-543 GEN
Solar/Wind Harmer
6.554
276861AD2-134 GEN
Solar/Wind Harmer
0.223
957471AF2-041 GEN
Solar/Wind Harmer
37.108
959081AF2-199 GEN
Solar/Wind Harmer
12.369
971067AG2-660 GEN
Solar/Wind Harmer
4.123
276876AE1-163_GEN2
Solar/Wind Harmer
0.003
274822ROCKFORD ;11
Adder
34.667
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
15.377
972235AH1-702 GEN1
Adder
4.441
970819AG2-516 GEN
Solar/Wind Harmer
14.695
958861AF2-177 GEN
Solar/Wind Harmer
5.294
971475AH1-234 GEN
Solar/Wind Harmer
5.925
970569AG2-363 GEN
Solar/Wind Harmer
36.555
274857EASY ROAD;U1
Solar/Wind Harmer
0.002
274761LEE CO EC;2U
Adder
16.12
274766LEE CO EC;7U
Adder
15.93
276158O29GEN2
Solar/Wind Harmer
0.001
944231AF1-091 GEN
Solar/Wind Harmer
3.153
274877BISHOP HL;1U
Solar/Wind Harmer
0.397
24791305MDL-5G
Solar/Wind Harmer
0.002
276726Z2-087_GEN
Solar/Wind Harmer
0.004
939741AE1-205 GEN
Solar/Wind Harmer
16.327
945371AF1-202 GEN
Solar/Wind Harmer
0.001
274854TWINGROVE;U2
Solar/Wind Harmer
0.005
24385905FR-11G C
Solar/Wind Harmer
0.003
24387305FR-4G C
Solar/Wind Harmer
0.004
972175AH1-670 GEN
Solar/Wind Harmer
9.129
247521TR3_G114
Solar/Wind Harmer
0.393
270246TR4_N_V150
Solar/Wind Harmer
0.07
970291AG2-192 GEN
Solar/Wind Harmer
1.393
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
4.146
963741AG1-226 GEN
Solar/Wind Harmer
24.913
276615X2-022 GEN
Solar/Wind Harmer
0.11
270032AE2-172
Solar/Wind Harmer
6.993
24695305TIMB G C
Solar/Wind Harmer
0.003
270005AE1-210 C O1
Solar/Wind Harmer
2.203
965031AG1-367 GEN
Solar/Wind Harmer
10.168
276903AD2-071 C
Solar/Wind Harmer
11.298
965911AG1-460 GEN
Solar/Wind Harmer
2.014
970825AG2-519 GEN
Solar/Wind Harmer
3.499
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0.001
970613AG2-401 GEN
Solar/Wind Harmer
6.684
247536S-71 GEN
Solar/Wind Harmer
0.341
24728605AND G2
Adder
4.579
270445AC2-157 GEN2
Solar/Wind Harmer
0.004
970333AG2-219 GEN
Solar/Wind Harmer
5.528
970773AG2-487 GEN
Solar/Wind Harmer
1.34
270349AD2-093_GEN
Solar/Wind Helper
1.737
957891AF2-083 GEN
Solar/Wind Harmer
0.002
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
17.4
965791AG1-447 GEN
Solar/Wind Harmer
12.76
961051AF2-396 GEN
Solar/Wind Harmer
27.667
961051AF2-396 GEN
Solar/Wind Harmer
18.445
274770LINCOLN ;1U
Adder
16.368
274771LINCOLN ;2U
Adder
16.368
274808UNIV PK N;4U
Adder
9.487
274803UNIV PARK;6U
Adder
11.029
972259AH1-714 GEN
Adder
36.054
274888KELLY CRK;1U
Solar/Wind Harmer
0.774
274887GEN-1.85
Solar/Wind Harmer
0.347
276843GEN-1.7
Solar/Wind Harmer
0.427
958011AF2-095 GEN
Solar/Wind Harmer
18.98
274674JOLIET 9 ;6U
Adder
28.777
274847GR RIDGE ;BU
Solar/Wind Harmer
0.005
971573AH1-285 GEN
Solar/Wind Harmer
2.397
274695ROCKY RD ;2P
Adder
20.358
274693ROCKY RD ;1P
Adder
20.158
274697ROCKY RD ;3P
Adder
5.53
274696ROCKY RD ;4P
Adder
20.838
958481AF2-142 GEN
Solar/Wind Harmer
19.12
274861TOP CROP ;1U
Solar/Wind Harmer
0.003
274862TOP CROP ;2U
Solar/Wind Harmer
1.724
274683WAUKEGAN ;8U
Adder
38.41
274683WAUKEGAN ;8U
Adder
32.378
962691AG1-118 GEN
Solar/Wind Harmer
37.971
970921AG2-575 GEN
Solar/Wind Harmer
12.623
970921AG2-575 GEN
Solar/Wind Harmer
4.208
958491AF2-143 GEN
Solar/Wind Harmer
18.868
944541AF1-119 GEN
Solar/Wind Harmer
0.84
960971AF2-388 GEN
Solar/Wind Harmer
7.355
942991AE2-321 GEN
Solar/Wind Harmer
13.981
274879MINONK ;1U
Solar/Wind Harmer
0.528
971333AH1-146 GEN
Solar/Wind Harmer
24.899
971335AH1-147 GEN
Solar/Wind Harmer
24.899
971341AH1-150 GEN
Solar/Wind Harmer
24.739
971343AH1-151 GEN
Solar/Wind Harmer
24.739
276872AE1-163_GEN1
Solar/Wind Harmer
0.003
274856ECOGROVE ;U1
Solar/Wind Harmer
0.288
276611AD2-172 GEN
Solar/Wind Harmer
0.003
938861AE1-114 GEN
Solar/Wind Harmer
6.879
274764LEE CO EC;5U
Adder
16.158
274765LEE CO EC;6U
Adder
16.158
274762LEE CO EC;3U
Adder
16.12
274763LEE CO EC;4U
Adder
15.968
276603SUBLETTE C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
7.136
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.003
276741O09 GEN1
Solar/Wind Harmer
0.425
276708O09 GEN2
Solar/Wind Harmer
0.425
274851PROVIDENC;RU
Solar/Wind Harmer
0.002
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.467
276646AC1-214 GEN2
Solar/Wind Harmer
0.467
942221AE2-234 GEN
Solar/Wind Harmer
0.059
276782AC1-033 GEN
Solar/Wind Harmer
0.002
960611AF2-352 GEN
Solar/Wind Harmer
3.81
966841AG1-555 GEN
Solar/Wind Harmer
1.27
270599AE1-208 GEN
Solar/Wind Harmer
9.916
270031AE2-169
Solar/Wind Harmer
5.95
276763AC1-053 GEN1
Solar/Wind Harmer
0.002
276764AC1-053 GEN2
Solar/Wind Harmer
0.002
970241AG2-163 GEN
Solar/Wind Harmer
6.141
971613AH1-306 GEN
Solar/Wind Harmer
5.035
276916AD2-100_GEN
Solar/Wind Harmer
20.939
276911AD2-131_GEN
Solar/Wind Harmer
1.379
960441AF2-335 GEN
Solar/Wind Harmer
9.92
970825AG2-519 GEN
Solar/Wind Harmer
10.923
945391AF1-204 GEN
Solar/Wind Harmer
9.973
964611AG1-324 GEN
Solar/Wind Harmer
0.694
270201AC2-176 GEN
Solar/Wind Harmer
0.002
24379505HDWTR1G C
Solar/Wind Harmer
0.003
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
247621Y3-024
Adder
0.306
970623AG2-406 GEN
Solar/Wind Harmer
1.558
270383AD1-128 GEN
Solar/Wind Harmer
0.005
270444AC2-157 GEN1
Solar/Wind Harmer
0.004
971587AH1-292 GEN
Solar/Wind Harmer
5.849
970883AG2-550 GEN
Solar/Wind Harmer
7.917
970885AG2-551 GEN
Solar/Wind Harmer
2.639
270007AE1-245 C
Solar/Wind Harmer
0.002
970239AG2-162 GEN
Solar/Wind Harmer
1.933
270471AD2-092_GEN
Solar/Wind Helper
1.737
944201AF1-088_MTX
Adder
132.938
957141AF2-008_MTX
Adder
17.09
LAGNLTFEXP_LAGN->PJM
CLTF
13.14
TVALTFEXP_TVA->PJM
CLTF
5.018
CBM West 2LTFEXP_CBM-W2->PJM
CBM
118.505
NYPJM->LTFIMP_NY
CLTF
3.194
LGEELTFEXP_LGEE->PJM
CLTF
4.31
WECLTFEXP_WEC->PJM
CLTF
6.715
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.799
AG2-052LTFEXP_AG2-052->PJM
LTF
0.422
AH1-155LTFEXP_AH1-155->PJM
LTF
0.632
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.281
CBM West 1LTFEXP_CBM-W1->PJM
CBM
201.431
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.695
MECLTFEXP_MEC->PJM
CLTF
24.295
SIGELTFEXP_SIGE->PJM
CLTF
0.466

Details for 05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line l/o AEP_P7-1_#17567_SRT-SL


Base Case Flowgate

Area:AEP
Facility Description:
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P7-1_#17567_SRT-SL
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:104.6 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5777.18
MW Contribution:32.89
Bus #Bus NameTypeMW Contribution
971599AH1-298 GEN
50/50
19.41
270144AC1-141 ST1_
50/50
4.168
24643105BUCHANAN
50/50
0.025
24653605MOTTVILLE
50/50
0.007
971347AH1-153 GEN
Solar/Wind Harmer
31.136
270071AF1-092 GEN
Solar/Wind Harmer
29.457
270102X2-052 ST
50/50
3.121
270100X2-052 CT1
50/50
2.876
270101X2-052 CT2
50/50
2.876
247620Y3-023
50/50
0.945
970615AG2-402 GEN
50/50
4.377
270142AC1-141 CT1_
50/50
4.706
24344005CKG1
50/50
12.844
24641605TWIN BRNCH
50/50
0.034
24642205MAYFLWER
50/50
1.31
944961AF1-161 GEN
50/50
5.605
962601AG1-109 GEN
50/50
5.605
970349AG2-230 GEN
Solar/Wind Harmer
31.136
270043AE2-236 GEN
Solar/Wind Harmer
11.189
970513AG2-328 GEN
Solar/Wind Harmer
36.028
970517AG2-330 GEN
Solar/Wind Harmer
32.677
247643Z2-116 C
Solar/Wind Harmer
0.137
945111AF1-176 GEN
Solar/Wind Harmer
10.963
970031AG2-029 GEN
Solar/Wind Harmer
57.557
24441205WTRV SLR C
Solar/Wind Harmer
0.256
944531AF1-118 GEN
Solar/Wind Harmer
66.164
959331AF2-224 GEN
Solar/Wind Harmer
18.821
965021AG1-366 GEN
Solar/Wind Harmer
4.377
274772LINCOLN ;3U
Adder
11.65
247604X1-042
Adder
0.782
274724RIVER EC ;11
Adder
32.899
972231SS25-0005
Solar/Wind Harmer
17.6
972181SS23-001
Solar/Wind Harmer
11
274752CRETE EC ;2U
Adder
9.065
274753CRETE EC ;3U
Adder
9.065
970707AG2-453 GEN
Solar/Wind Harmer
51.485
274802UNIV PARK;5U
Adder
10.683
274826FISK ;BP
Adder
20.057
970941AG2-585 GEN
Solar/Wind Harmer
22.875
274800UNIV PARK;3U
Adder
10.668
972038AH1-567 GEN2
Adder
0.668
276772AC2-154 GEN
Solar/Wind Harmer
5.103
276806AD2-047 C O1
Solar/Wind Harmer
19.577
972228AH1-698 GEN2
Adder
6.773
276897AD1-100 C
Solar/Wind Harmer
52.8
939351AE1-166 GEN
Solar/Wind Harmer
10.788
274676JOLIET 29;8U
Adder
53.66
274729ELWOOD EC;1P
Adder
29.73
274730ELWOOD EC;6P
Adder
29.73
274734ELWOOD EC;8P
Adder
29.73
274736ELWOOD EC;9P
Adder
29.73
276893AG1-478 C
Solar/Wind Harmer
0.755
943121AE2-341 GEN
Solar/Wind Harmer
26.96
943591AF1-030 GEN
Solar/Wind Harmer
17.973
270535AF1-215 GEN1
Solar/Wind Harmer
8.164
276694AA1-018 GEN2
Solar/Wind Harmer
11.167
274682WAUKEGAN ;7U
Adder
31.772
964401AG1-302 GEN
Solar/Wind Harmer
15.959
274872LEEDK;1U
Solar/Wind Harmer
0.447
970321AG2-212 GEN
Solar/Wind Harmer
36.028
270216AD2-079_GEN
Solar/Wind Harmer
1.189
270526AF1-158 GEN
Solar/Wind Harmer
8.831
957891AF2-083 GEN
Solar/Wind Harmer
6.556
960981AF2-389 GEN
Solar/Wind Harmer
2.938
24441505OLIV SLR
Solar/Wind Harmer
0.26
965681AG1-436 GEN
Solar/Wind Harmer
24.212
965791AG1-447 GEN
Solar/Wind Harmer
12.387
961051AF2-396 GEN
Solar/Wind Harmer
30.667
961051AF2-396 GEN
Solar/Wind Harmer
14.264
970611AG2-400 GEN
Solar/Wind Harmer
18.821
274770LINCOLN ;1U
Adder
11.65
274771LINCOLN ;2U
Adder
11.65
274808UNIV PK N;4U
Adder
9.189
274803UNIV PARK;6U
Adder
10.683
972259AH1-714 GEN
Adder
34.925
274888KELLY CRK;1U
Solar/Wind Harmer
10.804
274887GEN-1.85
Solar/Wind Harmer
9.754
276843GEN-1.7
Solar/Wind Harmer
1.049
958011AF2-095 GEN
Solar/Wind Harmer
26.352
274674JOLIET 9 ;6U
Adder
27.874
274847GR RIDGE ;BU
Solar/Wind Harmer
9.13
971573AH1-285 GEN
Solar/Wind Harmer
15.361
274695ROCKY RD ;2P
Adder
19.718
274693ROCKY RD ;1P
Adder
19.524
274697ROCKY RD ;3P
Adder
5.356
274696ROCKY RD ;4P
Adder
20.183
958481AF2-142 GEN
Solar/Wind Harmer
26.544
274861TOP CROP ;1U
Solar/Wind Harmer
10.717
274862TOP CROP ;2U
Solar/Wind Harmer
8.949
274683WAUKEGAN ;8U
Adder
37.2
274683WAUKEGAN ;8U
Adder
31.358
962691AG1-118 GEN
Solar/Wind Harmer
52.711
970921AG2-575 GEN
Solar/Wind Harmer
17.522
970921AG2-575 GEN
Solar/Wind Harmer
4.075
958491AF2-143 GEN
Solar/Wind Harmer
26.192
942991AE2-321 GEN
Solar/Wind Harmer
17.38
274879MINONK ;1U
Solar/Wind Harmer
11.721
971333AH1-146 GEN
Solar/Wind Harmer
34.561
971335AH1-147 GEN
Solar/Wind Harmer
34.561
944541AF1-119 GEN
Solar/Wind Harmer
7.192
960971AF2-388 GEN
Solar/Wind Harmer
18.769
274764LEE CO EC;5U
Adder
15.646
274765LEE CO EC;6U
Adder
15.646
274762LEE CO EC;3U
Adder
15.609
274763LEE CO EC;4U
Adder
15.462
972267AH1-718 GEN
Adder
6.909
247621Y3-024
Adder
0.305
270471AD2-092_GEN
Solar/Wind Helper
2.215
971341AH1-150 GEN
Solar/Wind Harmer
27.184
971771AH1-392 GEN
Solar/Wind Harmer
17.645
971769AH1-391 GEN
Solar/Wind Harmer
19.396
960681AF2-359 GEN
Solar/Wind Harmer
7.318
944161AF1-084 GEN
Solar/Wind Harmer
4.238
274775LINCOLN ;6U
Adder
11.65
274776LINCOLN ;7U
Adder
11.65
274777LINCOLN ;8U
Adder
11.65
24729505KEY G4
Adder
11.965
274814UNIV PK N;0U
Adder
9.311
274807UNIV PK N;3U
Adder
9.29
274805UNIV PK N;1U
Adder
9.25
274811UNIV PK N;7U
Adder
9.23
972037AH1-567 GEN1
Adder
0.335
274827FISK ;RP
Adder
14.215
960591AF2-350 GEN
Solar/Wind Harmer
18.3
972227AH1-698 GEN1
Adder
4.769
274687WILL CNTY;4U
Adder
50.75
274687WILL CNTY;4U
Adder
50.75
274675JOLIET 29;7U
Adder
55.649
274675JOLIET 29;7U
Adder
53.661
274731ELWOOD EC;2P
Adder
29.73
274733ELWOOD EC;3P
Adder
29.73
274735ELWOOD EC;4P
Adder
29.73
274728ELWOOD EC;5P
Adder
29.73
970833AG2-524 GEN
Solar/Wind Harmer
15.767
970833AG2-524 GEN
Solar/Wind Harmer
7.333
270536AF1-215 GEN2
Solar/Wind Harmer
8.164
274746AC1-111 G10
Adder
10.026
274744AC1-111 GEN8
Adder
10.026
971549AH1-272 GEN
Solar/Wind Harmer
32.892
958391AF2-133 GEN
Solar/Wind Harmer
15.781
971177AH1-047 GEN
Solar/Wind Harmer
10.18
276868AE1-113 GEN
Solar/Wind Harmer
17.58
276882AE2-255 GEN
Solar/Wind Harmer
5.86
971411AH1-196 GEN
Solar/Wind Harmer
25.942
971675AH1-338 GEN
Solar/Wind Harmer
31.127
274863CRW1-WTG
Solar/Wind Harmer
9.592
274864CRW2-WTG
Solar/Wind Harmer
9.592
958711AF2-162 GEN
Solar/Wind Harmer
1.737
274823ROCKFORD ;21
Adder
33.326
270054AF2-122 C O1
Solar/Wind Helper
1.3
971171AH1-044 GEN
Solar/Wind Harmer
27.184
971343AH1-151 GEN
Solar/Wind Harmer
27.184
276805AD2-038 GEN
Solar/Wind Harmer
8.958
276799AD1-013 GEN
Solar/Wind Harmer
3.825
946671AF1-331 GEN
Solar/Wind Harmer
0.724
274855GSG-6 ;RU
Solar/Wind Harmer
6.385
274850MENDOTA H;RU
Solar/Wind Harmer
4.44
276602WESTBROOK C
Solar/Wind Harmer
3.675
276863AD2-134 GEN
Solar/Wind Harmer
3.088
959141AF2-205 GEN
Solar/Wind Harmer
10.429
972236AH1-702 GEN2
Adder
3.739
274760LEE CO EC;1U
Adder
15.609
274767LEE CO EC;8U
Adder
15.425
24728705AND G3
Adder
9.344
24728505AND G1
Adder
4.468
959091AF2-200 GEN
Solar/Wind Harmer
27.184
24344105CKG2
50/50
16.266
270143AC1-141 CT2_
50/50
4.706
24639705ELKHART HY
50/50
0.317
970521AG2-332 GEN
50/50
22.545
24307105BERRINSP G
50/50
0.042
970245AG2-165 GEN
Solar/Wind Harmer
36.028
270505AE1-170 C O1
Solar/Wind Harmer
29.203
945111AF1-176 GEN
Solar/Wind Harmer
34.591
270063AE2-323 C
Solar/Wind Harmer
4.268
270449AD2-020 GEN
Solar/Wind Harmer
5.404
943021AE2-325 GEN
Solar/Wind Harmer
7.022
965011AG1-365 GEN
Solar/Wind Harmer
18.821
972207SS24-0001
Solar/Wind Harmer
41.419
274773LINCOLN ;4U
Adder
11.65
274774LINCOLN ;5U
Adder
11.65
274723RIVER EC ;12
Adder
33.283
274751CRETE EC ;1U
Adder
9.065
274754CRETE EC ;4U
Adder
9.065
276164X3-005 C
Solar/Wind Harmer
1.299
274812UNIV PK N;8U
Adder
9.23
970373AG2-245 GEN
Solar/Wind Harmer
38.641
274801UNIV PARK;4U
Adder
10.668
276776AD2-060 GEN
Solar/Wind Harmer
0.774
941551AE2-152 GEN
Solar/Wind Harmer
8.252
274676JOLIET 29;8U
Adder
55.648
274674JOLIET 9 ;6U
Adder
27.874
274732ELWOOD EC;7P
Adder
29.73
274871GR RIDGE ;2U
Solar/Wind Harmer
13.88
270055AF2-134 C O1
Solar/Wind Harmer
5.442
274745AC1-111 GEN9
Adder
10.026
276691AA1-018 GEN1
Solar/Wind Harmer
0.824
274682WAUKEGAN ;7U
Adder
31.772
274828WAUKEGAN ;BP
Adder
19.5
958381AF2-132 GEN
Solar/Wind Harmer
15.959
964861AG1-349 GEN
Solar/Wind Harmer
13.796
971917AH1-482 GEN
Solar/Wind Harmer
15.92
960751AF2-366 GEN
Solar/Wind Harmer
5.027
962781AG1-127 GEN
Solar/Wind Harmer
16.663
274872LEEDK;1U
Solar/Wind Harmer
14.356
939401AE1-172 GEN
Solar/Wind Harmer
24.351
276901AD2-066 C O1
Solar/Wind Harmer
6.124
971997AH1-543 GEN
Solar/Wind Harmer
27.297
276861AD2-134 GEN
Solar/Wind Harmer
3.088
965651AG1-433 GEN
Solar/Wind Harmer
9.384
274822ROCKFORD ;11
Adder
33.569
972235AH1-702 GEN1
Adder
4.3
274761LEE CO EC;2U
Adder
15.609
274766LEE CO EC;7U
Adder
15.425
24728605AND G2
Adder
4.468
972301AH1-735 GEN
Adder
2.524
270349AD2-093_GEN
Solar/Wind Helper
2.215
957471AF2-041 GEN
Solar/Wind Harmer
40.776
959081AF2-199 GEN
Solar/Wind Harmer
13.592
971067AG2-660 GEN
Solar/Wind Harmer
3.161
944201AF1-088_MTX
Adder
128.814
957141AF2-008_MTX
Adder
64.407
LAGNLTFEXP_LAGN->PJM
CLTF
12.499
TVALTFEXP_TVA->PJM
CLTF
4.733
CBM West 2LTFEXP_CBM-W2->PJM
CBM
114.06
NYPJM->LTFIMP_NY
CLTF
3.145
LGEELTFEXP_LGEE->PJM
CLTF
4.258
WECLTFEXP_WEC->PJM
CLTF
6.502
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.96
AG2-052LTFEXP_AG2-052->PJM
LTF
0.408
AH1-155LTFEXP_AH1-155->PJM
LTF
0.612
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.385
CBM West 1LTFEXP_CBM-W1->PJM
CBM
204.072
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.768
MECLTFEXP_MEC->PJM
CLTF
23.493
SIGELTFEXP_SIGE->PJM
CLTF
0.454

Details for 05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line l/o AEP_P2-2_#16655_05GUNN RD SW 345_2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P2-2_#16655_05GUNN RD SW 345_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:101.5 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5605.79
MW Contribution:31.81
Bus #Bus NameTypeMW Contribution
270102X2-052 ST
50/50
3.054
270100X2-052 CT1
50/50
2.814
270101X2-052 CT2
50/50
2.814
247620Y3-023
50/50
0.917
970321AG2-212 GEN
Solar/Wind Harmer
35.447
270216AD2-079_GEN
Solar/Wind Harmer
1.158
270526AF1-158 GEN
Solar/Wind Harmer
8.625
965681AG1-436 GEN
Solar/Wind Harmer
23.689
965791AG1-447 GEN
Solar/Wind Harmer
12.12
24441505OLIV SLR
Solar/Wind Harmer
0.254
957891AF2-083 GEN
Solar/Wind Harmer
6.386
960981AF2-389 GEN
Solar/Wind Harmer
2.861
961051AF2-396 GEN
Solar/Wind Harmer
29.854
961051AF2-396 GEN
Solar/Wind Harmer
13.886
274770LINCOLN ;1U
Adder
11.428
274771LINCOLN ;2U
Adder
11.428
274808UNIV PK N;4U
Adder
9.002
274803UNIV PARK;6U
Adder
10.468
972259AH1-714 GEN
Adder
34.24
274888KELLY CRK;1U
Solar/Wind Harmer
10.588
274887GEN-1.85
Solar/Wind Harmer
9.559
276843GEN-1.7
Solar/Wind Harmer
1.029
958011AF2-095 GEN
Solar/Wind Harmer
25.825
274674JOLIET 9 ;6U
Adder
27.32
970611AG2-400 GEN
Solar/Wind Harmer
17.715
274847GR RIDGE ;BU
Solar/Wind Harmer
8.95
971573AH1-285 GEN
Solar/Wind Harmer
15.059
274695ROCKY RD ;2P
Adder
19.327
274693ROCKY RD ;1P
Adder
19.137
274697ROCKY RD ;3P
Adder
5.25
274696ROCKY RD ;4P
Adder
19.783
971599AH1-298 GEN
50/50
18.905
270144AC1-141 ST1_
50/50
4.065
24643105BUCHANAN
50/50
0.024
24653605MOTTVILLE
50/50
0.007
971347AH1-153 GEN
Solar/Wind Harmer
30.529
971771AH1-392 GEN
Solar/Wind Harmer
17.216
270071AF1-092 GEN
Solar/Wind Harmer
28.557
960681AF2-359 GEN
Solar/Wind Harmer
7.16
971769AH1-391 GEN
Solar/Wind Harmer
18.948
944161AF1-084 GEN
Solar/Wind Harmer
4.125
274775LINCOLN ;6U
Adder
11.428
274776LINCOLN ;7U
Adder
11.428
274777LINCOLN ;8U
Adder
11.428
274814UNIV PK N;0U
Adder
9.121
274807UNIV PK N;3U
Adder
9.101
274805UNIV PK N;1U
Adder
9.061
274811UNIV PK N;7U
Adder
9.041
972037AH1-567 GEN1
Adder
0.329
274827FISK ;RP
Adder
13.93
960591AF2-350 GEN
Solar/Wind Harmer
17.934
972227AH1-698 GEN1
Adder
4.674
24729505KEY G4
Adder
11.594
274687WILL CNTY;4U
Adder
49.737
274687WILL CNTY;4U
Adder
49.737
274675JOLIET 29;7U
Adder
54.541
274675JOLIET 29;7U
Adder
52.593
274731ELWOOD EC;2P
Adder
29.137
274733ELWOOD EC;3P
Adder
29.137
274735ELWOOD EC;4P
Adder
29.137
274728ELWOOD EC;5P
Adder
29.138
970833AG2-524 GEN
Solar/Wind Harmer
15.455
970833AG2-524 GEN
Solar/Wind Harmer
7.188
274746AC1-111 G10
Adder
9.829
274744AC1-111 GEN8
Adder
9.829
270536AF1-215 GEN2
Solar/Wind Harmer
7.981
971549AH1-272 GEN
Solar/Wind Harmer
31.811
971177AH1-047 GEN
Solar/Wind Harmer
9.977
276868AE1-113 GEN
Solar/Wind Harmer
17.225
276882AE2-255 GEN
Solar/Wind Harmer
5.742
958391AF2-133 GEN
Solar/Wind Harmer
15.422
971411AH1-196 GEN
Solar/Wind Harmer
25.424
971675AH1-338 GEN
Solar/Wind Harmer
30.507
274863CRW1-WTG
Solar/Wind Harmer
9.397
274864CRW2-WTG
Solar/Wind Harmer
9.397
274823ROCKFORD ;21
Adder
32.659
270284AF1-227 GEN1
Solar/Wind Helper
2.861
270286AF1-227 GEN2
Solar/Wind Helper
1.049
270287AF1-227 GEN3
Solar/Wind Helper
1.049
270054AF2-122 C O1
Solar/Wind Helper
1.201
971171AH1-044 GEN
Solar/Wind Harmer
32.581
24344105CKG2
50/50
15.989
270143AC1-141 CT2_
50/50
4.589
24639705ELKHART HY
50/50
0.308
970521AG2-332 GEN
50/50
21.897
24307105BERRINSP G
50/50
0.041
970245AG2-165 GEN
Solar/Wind Harmer
35.447
270505AE1-170 C O1
Solar/Wind Harmer
28.453
945111AF1-176 GEN
Solar/Wind Harmer
33.668
270449AD2-020 GEN
Solar/Wind Harmer
5.261
943021AE2-325 GEN
Solar/Wind Harmer
6.837
270063AE2-323 C
Solar/Wind Harmer
4.119
972207SS24-0001
Solar/Wind Harmer
40.631
274773LINCOLN ;4U
Adder
11.428
274774LINCOLN ;5U
Adder
11.428
274723RIVER EC ;12
Adder
32.605
274751CRETE EC ;1U
Adder
8.877
274754CRETE EC ;4U
Adder
8.877
276164X3-005 C
Solar/Wind Harmer
1.273
274812UNIV PK N;8U
Adder
9.041
970373AG2-245 GEN
Solar/Wind Harmer
37.783
276776AD2-060 GEN
Solar/Wind Harmer
0.758
274801UNIV PARK;4U
Adder
10.455
941551AE2-152 GEN
Solar/Wind Harmer
8.088
274676JOLIET 29;8U
Adder
54.54
274674JOLIET 9 ;6U
Adder
27.32
274732ELWOOD EC;7P
Adder
29.138
965011AG1-365 GEN
Solar/Wind Harmer
17.715
274871GR RIDGE ;2U
Solar/Wind Harmer
13.606
274745AC1-111 GEN9
Adder
9.829
270055AF2-134 C O1
Solar/Wind Harmer
5.32
276691AA1-018 GEN1
Solar/Wind Harmer
0.807
274682WAUKEGAN ;7U
Adder
31.14
274828WAUKEGAN ;BP
Adder
19.112
958381AF2-132 GEN
Solar/Wind Harmer
15.597
960751AF2-366 GEN
Solar/Wind Harmer
4.928
962781AG1-127 GEN
Solar/Wind Harmer
16.333
964861AG1-349 GEN
Solar/Wind Harmer
13.483
971917AH1-482 GEN
Solar/Wind Harmer
15.559
274872LEEDK;1U
Solar/Wind Harmer
14.071
939401AE1-172 GEN
Solar/Wind Harmer
23.859
276901AD2-066 C O1
Solar/Wind Harmer
6
971997AH1-543 GEN
Solar/Wind Harmer
26.748
276861AD2-134 GEN
Solar/Wind Harmer
3.026
274822ROCKFORD ;11
Adder
32.898
972235AH1-702 GEN1
Adder
4.214
274761LEE CO EC;2U
Adder
15.294
274766LEE CO EC;7U
Adder
15.114
24728605AND G2
Adder
4.299
970091AG2-072 GEN
Adder
4.41
270349AD2-093_GEN
Solar/Wind Helper
1.84
957471AF2-041 GEN
Solar/Wind Harmer
48.872
959081AF2-199 GEN
Solar/Wind Harmer
16.291
971067AG2-660 GEN
Solar/Wind Harmer
3.789
958481AF2-142 GEN
Solar/Wind Harmer
26.008
274861TOP CROP ;1U
Solar/Wind Harmer
10.5
274862TOP CROP ;2U
Solar/Wind Harmer
8.768
274683WAUKEGAN ;8U
Adder
36.461
274683WAUKEGAN ;8U
Adder
30.735
962691AG1-118 GEN
Solar/Wind Harmer
51.667
970921AG2-575 GEN
Solar/Wind Harmer
17.175
970921AG2-575 GEN
Solar/Wind Harmer
3.994
958491AF2-143 GEN
Solar/Wind Harmer
25.662
942991AE2-321 GEN
Solar/Wind Harmer
17.034
274879MINONK ;1U
Solar/Wind Harmer
11.484
971333AH1-146 GEN
Solar/Wind Harmer
33.871
971335AH1-147 GEN
Solar/Wind Harmer
33.871
274764LEE CO EC;5U
Adder
15.33
274765LEE CO EC;6U
Adder
15.33
274762LEE CO EC;3U
Adder
15.294
274763LEE CO EC;4U
Adder
15.15
972267AH1-718 GEN
Adder
6.769
247621Y3-024
Adder
0.286
270471AD2-092_GEN
Solar/Wind Helper
1.84
971341AH1-150 GEN
Solar/Wind Harmer
32.581
971343AH1-151 GEN
Solar/Wind Harmer
32.581
24344005CKG1
50/50
12.539
270142AC1-141 CT1_
50/50
4.589
24641605TWIN BRNCH
50/50
0.033
24642205MAYFLWER
50/50
1.278
944961AF1-161 GEN
50/50
5.457
962601AG1-109 GEN
50/50
5.457
970349AG2-230 GEN
Solar/Wind Harmer
30.529
970513AG2-328 GEN
Solar/Wind Harmer
35.447
970517AG2-330 GEN
Solar/Wind Harmer
32.149
270043AE2-236 GEN
Solar/Wind Harmer
10.823
247643Z2-116 C
Solar/Wind Harmer
0.133
945111AF1-176 GEN
Solar/Wind Harmer
10.67
970031AG2-029 GEN
Solar/Wind Harmer
55.416
24441205WTRV SLR C
Solar/Wind Harmer
0.249
274772LINCOLN ;3U
Adder
11.428
944531AF1-118 GEN
Solar/Wind Harmer
64.152
247604X1-042
Adder
0.761
274724RIVER EC ;11
Adder
32.23
972231SS25-0005
Solar/Wind Harmer
17.235
972181SS23-001
Solar/Wind Harmer
10.772
274752CRETE EC ;2U
Adder
8.877
274753CRETE EC ;3U
Adder
8.877
970707AG2-453 GEN
Solar/Wind Harmer
50.49
274802UNIV PARK;5U
Adder
10.468
274826FISK ;BP
Adder
19.655
276772AC2-154 GEN
Solar/Wind Harmer
5.001
276806AD2-047 C O1
Solar/Wind Harmer
19.185
970941AG2-585 GEN
Solar/Wind Harmer
22.418
274800UNIV PARK;3U
Adder
10.455
972038AH1-567 GEN2
Adder
0.654
972228AH1-698 GEN2
Adder
6.639
276897AD1-100 C
Solar/Wind Harmer
51.755
939351AE1-166 GEN
Solar/Wind Harmer
10.575
274676JOLIET 29;8U
Adder
52.592
274729ELWOOD EC;1P
Adder
29.137
274730ELWOOD EC;6P
Adder
29.138
274734ELWOOD EC;8P
Adder
29.138
274736ELWOOD EC;9P
Adder
29.138
276893AG1-478 C
Solar/Wind Harmer
0.74
959331AF2-224 GEN
Solar/Wind Harmer
17.715
965021AG1-366 GEN
Solar/Wind Harmer
4.12
943121AE2-341 GEN
Solar/Wind Harmer
26.432
943591AF1-030 GEN
Solar/Wind Harmer
17.621
270535AF1-215 GEN1
Solar/Wind Harmer
7.981
276694AA1-018 GEN2
Solar/Wind Harmer
10.942
274682WAUKEGAN ;7U
Adder
31.14
964401AG1-302 GEN
Solar/Wind Harmer
15.597
274872LEEDK;1U
Solar/Wind Harmer
0.438
276805AD2-038 GEN
Solar/Wind Harmer
8.776
276799AD1-013 GEN
Solar/Wind Harmer
3.749
946671AF1-331 GEN
Solar/Wind Harmer
0.71
274855GSG-6 ;RU
Solar/Wind Harmer
6.258
274850MENDOTA H;RU
Solar/Wind Harmer
4.351
276602WESTBROOK C
Solar/Wind Harmer
3.602
276863AD2-134 GEN
Solar/Wind Harmer
3.026
959141AF2-205 GEN
Solar/Wind Harmer
10.19
972236AH1-702 GEN2
Adder
3.664
274760LEE CO EC;1U
Adder
15.294
274767LEE CO EC;8U
Adder
15.114
24728705AND G3
Adder
8.991
24728505AND G1
Adder
4.299
959091AF2-200 GEN
Solar/Wind Harmer
32.581
944201AF1-088_MTX
Adder
125.321
957141AF2-008_MTX
Adder
62.661
LAGNLTFEXP_LAGN->PJM
CLTF
12.243
TVALTFEXP_TVA->PJM
CLTF
4.635
CBM West 2LTFEXP_CBM-W2->PJM
CBM
111.242
NYPJM->LTFIMP_NY
CLTF
3.027
LGEELTFEXP_LGEE->PJM
CLTF
4.067
WECLTFEXP_WEC->PJM
CLTF
6.372
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.882
AG2-052LTFEXP_AG2-052->PJM
LTF
0.399
AH1-155LTFEXP_AH1-155->PJM
LTF
0.599
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.344
CBM West 1LTFEXP_CBM-W1->PJM
CBM
197.094
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.275
MECLTFEXP_MEC->PJM
CLTF
22.999
SIGELTFEXP_SIGE->PJM
CLTF
0.439

Details for 05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line l/o AEP_P2-2_#16654_05GUNN RD SW 345_1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P2-2_#16654_05GUNN RD SW 345_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:101.3 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5594.78
MW Contribution:31.83
Bus #Bus NameTypeMW Contribution
270102X2-052 ST
50/50
3.055
270100X2-052 CT1
50/50
2.815
270101X2-052 CT2
50/50
2.815
247620Y3-023
50/50
0.917
970321AG2-212 GEN
Solar/Wind Harmer
35.465
270216AD2-079_GEN
Solar/Wind Harmer
1.158
270526AF1-158 GEN
Solar/Wind Harmer
8.63
965681AG1-436 GEN
Solar/Wind Harmer
23.702
965791AG1-447 GEN
Solar/Wind Harmer
12.126
24441505OLIV SLR
Solar/Wind Harmer
0.254
957891AF2-083 GEN
Solar/Wind Harmer
6.389
960981AF2-389 GEN
Solar/Wind Harmer
2.863
961051AF2-396 GEN
Solar/Wind Harmer
29.87
961051AF2-396 GEN
Solar/Wind Harmer
13.893
274770LINCOLN ;1U
Adder
11.434
274771LINCOLN ;2U
Adder
11.434
274808UNIV PK N;4U
Adder
9.007
274803UNIV PARK;6U
Adder
10.474
972259AH1-714 GEN
Adder
34.259
274888KELLY CRK;1U
Solar/Wind Harmer
10.594
274887GEN-1.85
Solar/Wind Harmer
9.565
276843GEN-1.7
Solar/Wind Harmer
1.029
958011AF2-095 GEN
Solar/Wind Harmer
25.84
274674JOLIET 9 ;6U
Adder
27.335
970611AG2-400 GEN
Solar/Wind Harmer
17.725
274847GR RIDGE ;BU
Solar/Wind Harmer
8.955
971573AH1-285 GEN
Solar/Wind Harmer
15.068
274695ROCKY RD ;2P
Adder
19.338
274693ROCKY RD ;1P
Adder
19.148
274697ROCKY RD ;3P
Adder
5.253
274696ROCKY RD ;4P
Adder
19.794
958481AF2-142 GEN
Solar/Wind Harmer
26.023
274861TOP CROP ;1U
Solar/Wind Harmer
10.506
274862TOP CROP ;2U
Solar/Wind Harmer
8.773
274683WAUKEGAN ;8U
Adder
36.482
274683WAUKEGAN ;8U
Adder
30.752
962691AG1-118 GEN
Solar/Wind Harmer
51.697
970921AG2-575 GEN
Solar/Wind Harmer
17.185
970921AG2-575 GEN
Solar/Wind Harmer
3.996
958491AF2-143 GEN
Solar/Wind Harmer
25.677
942991AE2-321 GEN
Solar/Wind Harmer
17.044
274879MINONK ;1U
Solar/Wind Harmer
11.491
971333AH1-146 GEN
Solar/Wind Harmer
33.891
971335AH1-147 GEN
Solar/Wind Harmer
33.891
274764LEE CO EC;5U
Adder
15.34
274765LEE CO EC;6U
Adder
15.34
274762LEE CO EC;3U
Adder
15.304
274763LEE CO EC;4U
Adder
15.16
972267AH1-718 GEN
Adder
6.773
247621Y3-024
Adder
0.286
270471AD2-092_GEN
Solar/Wind Helper
1.839
270224U2-072_GEN2
Solar/Wind Helper
0.897
270227U2-072_GEN3
Solar/Wind Helper
0.897
270228U2-072_GEN4
Solar/Wind Helper
0.897
270231U2-072_GEN5
Solar/Wind Helper
0.897
971341AH1-150 GEN
Solar/Wind Harmer
32.601
971343AH1-151 GEN
Solar/Wind Harmer
32.601
24344005CKG1
50/50
12.545
270142AC1-141 CT1_
50/50
4.591
24641605TWIN BRNCH
50/50
0.033
24642205MAYFLWER
50/50
1.278
944961AF1-161 GEN
50/50
5.46
962601AG1-109 GEN
50/50
5.46
970349AG2-230 GEN
Solar/Wind Harmer
30.544
970513AG2-328 GEN
Solar/Wind Harmer
35.465
970517AG2-330 GEN
Solar/Wind Harmer
32.166
270043AE2-236 GEN
Solar/Wind Harmer
10.829
247643Z2-116 C
Solar/Wind Harmer
0.133
945111AF1-176 GEN
Solar/Wind Harmer
10.676
970031AG2-029 GEN
Solar/Wind Harmer
55.447
24441205WTRV SLR C
Solar/Wind Harmer
0.249
274772LINCOLN ;3U
Adder
11.434
944531AF1-118 GEN
Solar/Wind Harmer
64.187
247604X1-042
Adder
0.761
274724RIVER EC ;11
Adder
32.247
972231SS25-0005
Solar/Wind Harmer
17.245
972181SS23-001
Solar/Wind Harmer
10.778
274752CRETE EC ;2U
Adder
8.882
274753CRETE EC ;3U
Adder
8.882
970707AG2-453 GEN
Solar/Wind Harmer
50.518
274802UNIV PARK;5U
Adder
10.474
274826FISK ;BP
Adder
19.666
276772AC2-154 GEN
Solar/Wind Harmer
5.004
276806AD2-047 C O1
Solar/Wind Harmer
19.196
970941AG2-585 GEN
Solar/Wind Harmer
22.43
274800UNIV PARK;3U
Adder
10.46
972038AH1-567 GEN2
Adder
0.655
972228AH1-698 GEN2
Adder
6.643
276897AD1-100 C
Solar/Wind Harmer
51.784
939351AE1-166 GEN
Solar/Wind Harmer
10.581
274676JOLIET 29;8U
Adder
52.622
274730ELWOOD EC;6P
Adder
29.154
274734ELWOOD EC;8P
Adder
29.154
274736ELWOOD EC;9P
Adder
29.154
274729ELWOOD EC;1P
Adder
29.154
276893AG1-478 C
Solar/Wind Harmer
0.74
959331AF2-224 GEN
Solar/Wind Harmer
17.725
965021AG1-366 GEN
Solar/Wind Harmer
4.122
943121AE2-341 GEN
Solar/Wind Harmer
26.447
943591AF1-030 GEN
Solar/Wind Harmer
17.631
270535AF1-215 GEN1
Solar/Wind Harmer
7.986
276694AA1-018 GEN2
Solar/Wind Harmer
10.948
274682WAUKEGAN ;7U
Adder
31.159
964401AG1-302 GEN
Solar/Wind Harmer
15.606
274872LEEDK;1U
Solar/Wind Harmer
0.439
276805AD2-038 GEN
Solar/Wind Harmer
8.782
276799AD1-013 GEN
Solar/Wind Harmer
3.751
946671AF1-331 GEN
Solar/Wind Harmer
0.71
274855GSG-6 ;RU
Solar/Wind Harmer
6.262
274850MENDOTA H;RU
Solar/Wind Harmer
4.354
276602WESTBROOK C
Solar/Wind Harmer
3.604
276863AD2-134 GEN
Solar/Wind Harmer
3.028
959141AF2-205 GEN
Solar/Wind Harmer
10.197
972236AH1-702 GEN2
Adder
3.666
274760LEE CO EC;1U
Adder
15.304
274767LEE CO EC;8U
Adder
15.124
24728705AND G3
Adder
8.999
24728505AND G1
Adder
4.303
942871AE2-306 GEN
Solar/Wind Helper
0.456
959091AF2-200 GEN
Solar/Wind Harmer
32.601
971599AH1-298 GEN
50/50
18.913
270144AC1-141 ST1_
50/50
4.067
24643105BUCHANAN
50/50
0.024
24653605MOTTVILLE
50/50
0.007
971347AH1-153 GEN
Solar/Wind Harmer
30.544
971771AH1-392 GEN
Solar/Wind Harmer
17.225
270071AF1-092 GEN
Solar/Wind Harmer
28.572
960681AF2-359 GEN
Solar/Wind Harmer
7.163
971769AH1-391 GEN
Solar/Wind Harmer
18.958
944161AF1-084 GEN
Solar/Wind Harmer
4.127
274775LINCOLN ;6U
Adder
11.434
274776LINCOLN ;7U
Adder
11.434
274777LINCOLN ;8U
Adder
11.434
274814UNIV PK N;0U
Adder
9.126
274807UNIV PK N;3U
Adder
9.106
274805UNIV PK N;1U
Adder
9.066
274811UNIV PK N;7U
Adder
9.046
972037AH1-567 GEN1
Adder
0.329
274827FISK ;RP
Adder
13.937
960591AF2-350 GEN
Solar/Wind Harmer
17.944
972227AH1-698 GEN1
Adder
4.677
24729505KEY G4
Adder
11.601
274687WILL CNTY;4U
Adder
49.765
274687WILL CNTY;4U
Adder
49.765
274675JOLIET 29;7U
Adder
54.572
274675JOLIET 29;7U
Adder
52.623
274728ELWOOD EC;5P
Adder
29.154
274731ELWOOD EC;2P
Adder
29.154
274733ELWOOD EC;3P
Adder
29.154
274735ELWOOD EC;4P
Adder
29.154
970833AG2-524 GEN
Solar/Wind Harmer
15.464
970833AG2-524 GEN
Solar/Wind Harmer
7.192
274746AC1-111 G10
Adder
9.834
274744AC1-111 GEN8
Adder
9.834
270536AF1-215 GEN2
Solar/Wind Harmer
7.986
971549AH1-272 GEN
Solar/Wind Harmer
31.829
971177AH1-047 GEN
Solar/Wind Harmer
9.983
276868AE1-113 GEN
Solar/Wind Harmer
17.235
276882AE2-255 GEN
Solar/Wind Harmer
5.745
958391AF2-133 GEN
Solar/Wind Harmer
15.431
971411AH1-196 GEN
Solar/Wind Harmer
25.439
971675AH1-338 GEN
Solar/Wind Harmer
30.526
274863CRW1-WTG
Solar/Wind Harmer
9.402
274864CRW2-WTG
Solar/Wind Harmer
9.402
274823ROCKFORD ;21
Adder
32.679
270284AF1-227 GEN1
Solar/Wind Helper
2.858
270286AF1-227 GEN2
Solar/Wind Helper
1.048
270287AF1-227 GEN3
Solar/Wind Helper
1.048
270054AF2-122 C O1
Solar/Wind Helper
1.2
971171AH1-044 GEN
Solar/Wind Harmer
32.601
24344105CKG2
50/50
15.997
270143AC1-141 CT2_
50/50
4.591
24639705ELKHART HY
50/50
0.308
970521AG2-332 GEN
50/50
21.908
24307105BERRINSP G
50/50
0.041
970245AG2-165 GEN
Solar/Wind Harmer
35.465
270505AE1-170 C O1
Solar/Wind Harmer
28.468
945111AF1-176 GEN
Solar/Wind Harmer
33.686
270449AD2-020 GEN
Solar/Wind Harmer
5.264
943021AE2-325 GEN
Solar/Wind Harmer
6.84
270063AE2-323 C
Solar/Wind Harmer
4.121
972207SS24-0001
Solar/Wind Harmer
40.653
274773LINCOLN ;4U
Adder
11.434
274774LINCOLN ;5U
Adder
11.434
274723RIVER EC ;12
Adder
32.623
274751CRETE EC ;1U
Adder
8.882
274754CRETE EC ;4U
Adder
8.882
276164X3-005 C
Solar/Wind Harmer
1.273
274812UNIV PK N;8U
Adder
9.046
970373AG2-245 GEN
Solar/Wind Harmer
37.804
276776AD2-060 GEN
Solar/Wind Harmer
0.759
274801UNIV PARK;4U
Adder
10.46
941551AE2-152 GEN
Solar/Wind Harmer
8.093
274676JOLIET 29;8U
Adder
54.571
274674JOLIET 9 ;6U
Adder
27.335
274732ELWOOD EC;7P
Adder
29.154
965011AG1-365 GEN
Solar/Wind Harmer
17.725
274871GR RIDGE ;2U
Solar/Wind Harmer
13.613
274745AC1-111 GEN9
Adder
9.834
270055AF2-134 C O1
Solar/Wind Harmer
5.323
276691AA1-018 GEN1
Solar/Wind Harmer
0.808
274682WAUKEGAN ;7U
Adder
31.159
274828WAUKEGAN ;BP
Adder
19.123
958381AF2-132 GEN
Solar/Wind Harmer
15.606
960751AF2-366 GEN
Solar/Wind Harmer
4.93
962781AG1-127 GEN
Solar/Wind Harmer
16.343
964861AG1-349 GEN
Solar/Wind Harmer
13.491
971917AH1-482 GEN
Solar/Wind Harmer
15.568
274872LEEDK;1U
Solar/Wind Harmer
14.079
939401AE1-172 GEN
Solar/Wind Harmer
23.873
276901AD2-066 C O1
Solar/Wind Harmer
6.004
971997AH1-543 GEN
Solar/Wind Harmer
26.764
276861AD2-134 GEN
Solar/Wind Harmer
3.028
274822ROCKFORD ;11
Adder
32.918
972235AH1-702 GEN1
Adder
4.216
274761LEE CO EC;2U
Adder
15.304
274766LEE CO EC;7U
Adder
15.124
24728605AND G2
Adder
4.303
970091AG2-072 GEN
Adder
4.415
270349AD2-093_GEN
Solar/Wind Helper
1.839
270223U2-072_GEN1
Solar/Wind Helper
0.897
270578AF1-285 GEN2
Solar/Wind Helper
0.608
270391AF1-285 GEN3
Solar/Wind Helper
0.608
957471AF2-041 GEN
Solar/Wind Harmer
48.901
959081AF2-199 GEN
Solar/Wind Harmer
16.3
971067AG2-660 GEN
Solar/Wind Harmer
3.791
944201AF1-088_MTX
Adder
125.438
957141AF2-008_MTX
Adder
62.719
LAGNLTFEXP_LAGN->PJM
CLTF
12.264
TVALTFEXP_TVA->PJM
CLTF
4.645
CBM West 2LTFEXP_CBM-W2->PJM
CBM
111.378
NYPJM->LTFIMP_NY
CLTF
3.02
LGEELTFEXP_LGEE->PJM
CLTF
4.074
WECLTFEXP_WEC->PJM
CLTF
6.376
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.875
AG2-052LTFEXP_AG2-052->PJM
LTF
0.399
AH1-155LTFEXP_AH1-155->PJM
LTF
0.599
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.34
CBM West 1LTFEXP_CBM-W1->PJM
CBM
197.241
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.313
MECLTFEXP_MEC->PJM
CLTF
23.016
SIGELTFEXP_SIGE->PJM
CLTF
0.44

Details for 05TWIN B-05MERIDN 345.0 kV Ckt 1 line l/o AEP_P4_#7442_05SORENS 765_K2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05TWIN B-05MERIDN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7442_05SORENS 765_K2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.25 %
Rating:897.0 MVA
Rating Type:B
MVA to Mitigate:944.12
MW Contribution:11.69
Bus #Bus NameTypeMW Contribution
270216AD2-079_GEN
Solar/Wind Harmer
0.384
957891AF2-083 GEN
Solar/Wind Harmer
2.056
960981AF2-389 GEN
Solar/Wind Harmer
0.919
961051AF2-396 GEN
Solar/Wind Harmer
9.357
961051AF2-396 GEN
Solar/Wind Harmer
4.352
270526AF1-158 GEN
Solar/Wind Harmer
2.653
24441505OLIV SLR
Solar/Wind Harmer
0.076
965681AG1-436 GEN
Solar/Wind Harmer
6.639
965791AG1-447 GEN
Solar/Wind Harmer
3.397
247620Y3-023
Adder
0.207
970321AG2-212 GEN
Solar/Wind Harmer
7.759
274808UNIV PK N;4U
Adder
2.157
274770LINCOLN ;1U
Adder
2.675
274771LINCOLN ;2U
Adder
2.675
971341AH1-150 GEN
Solar/Wind Harmer
7.641
971343AH1-151 GEN
Solar/Wind Harmer
7.641
944541AF1-119 GEN
Solar/Wind Helper
1.949
247643Z2-116 C
Solar/Wind Harmer
0.045
970349AG2-230 GEN
Solar/Wind Harmer
9.46
24642205MAYFLWER
Adder
0.389
945111AF1-176 GEN
Solar/Wind Harmer
3.274
24441205WTRV SLR C
Solar/Wind Harmer
0.077
247604X1-042
Adder
0.231
274724RIVER EC ;11
Adder
7.812
972231SS25-0005
Solar/Wind Harmer
4.183
972181SS23-001
Solar/Wind Harmer
2.614
274752CRETE EC ;2U
Adder
2.154
274753CRETE EC ;3U
Adder
2.154
970513AG2-328 GEN
Solar/Wind Harmer
7.759
970517AG2-330 GEN
Solar/Wind Harmer
7.038
274772LINCOLN ;3U
Adder
2.675
274676JOLIET 29;8U
Adder
12.314
274730ELWOOD EC;6P
Adder
6.801
274734ELWOOD EC;8P
Adder
6.801
274736ELWOOD EC;9P
Adder
6.801
274729ELWOOD EC;1P
Adder
6.8
959091AF2-200 GEN
Solar/Wind Harmer
7.641
971771AH1-392 GEN
Solar/Wind Harmer
5.869
971549AH1-272 GEN
Solar/Wind Harmer
11.686
971347AH1-153 GEN
Solar/Wind Harmer
9.46
944161AF1-084 GEN
Solar/Wind Harmer
1.295
971769AH1-391 GEN
Solar/Wind Harmer
5.671
960681AF2-359 GEN
Solar/Wind Harmer
2.007
274814UNIV PK N;0U
Adder
2.185
274807UNIV PK N;3U
Adder
2.181
274805UNIV PK N;1U
Adder
2.171
274811UNIV PK N;7U
Adder
2.166
274775LINCOLN ;6U
Adder
2.675
274776LINCOLN ;7U
Adder
2.675
274777LINCOLN ;8U
Adder
2.675
274675JOLIET 29;7U
Adder
12.77
274675JOLIET 29;7U
Adder
12.314
274728ELWOOD EC;5P
Adder
6.801
274731ELWOOD EC;2P
Adder
6.8
274733ELWOOD EC;3P
Adder
6.8
274735ELWOOD EC;4P
Adder
6.8
971171AH1-044 GEN
Solar/Wind Harmer
7.641
958711AF2-162 GEN
Solar/Wind Helper
0.408
270505AE1-170 C O1
Solar/Wind Harmer
9.393
270449AD2-020 GEN
Solar/Wind Harmer
1.67
943021AE2-325 GEN
Solar/Wind Harmer
2.17
945111AF1-176 GEN
Solar/Wind Harmer
10.331
24639705ELKHART HY
Adder
0.081
970373AG2-245 GEN
Solar/Wind Harmer
9.629
274751CRETE EC ;1U
Adder
2.154
274754CRETE EC ;4U
Adder
2.154
274723RIVER EC ;12
Adder
7.891
970245AG2-165 GEN
Solar/Wind Harmer
7.759
276164X3-005 C
Solar/Wind Harmer
0.305
274812UNIV PK N;8U
Adder
2.166
972207SS24-0001
Solar/Wind Harmer
9.512
274773LINCOLN ;4U
Adder
2.675
274774LINCOLN ;5U
Adder
2.675
274676JOLIET 29;8U
Adder
12.77
274732ELWOOD EC;7P
Adder
6.801
957471AF2-041 GEN
Solar/Wind Harmer
11.462
959081AF2-199 GEN
Solar/Wind Harmer
3.821
971067AG2-660 GEN
Solar/Wind Harmer
0.889
LAGNLTFEXP_LAGN->PJM
CLTF
1.772
TVALTFEXP_TVA->PJM
CLTF
0.498
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.759
NYPJM->LTFIMP_NY
CLTF
0.536
LGEELTFEXP_LGEE->PJM
CLTF
0.029
WECLTFEXP_WEC->PJM
CLTF
1.446
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.243
AG2-052LTFEXP_AG2-052->PJM
LTF
0.093
AH1-155LTFEXP_AH1-155->PJM
LTF
0.14
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.122
CBM West 1LTFEXP_CBM-W1->PJM
CBM
43.515
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.56
MECLTFEXP_MEC->PJM
CLTF
4.764
SIGELTFEXP_SIGE->PJM
CLTF
0.026

Details for 18MOROCCO-02ALLEN 345.0 kV Ckt 1 line l/o ATSI_P2-3_TE-345-034T_SRT-A


Base Case Flowgate

Area:ATSI/METC
Facility Description:
18MOROCCO-02ALLEN 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_TE-345-034T_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.58 %
Rating:1793.0 MVA
Rating Type:B
MVA to Mitigate:1946.81
MW Contribution:20.2
Bus #Bus NameTypeMW Contribution
247604X1-042
Adder
0.358
24441205WTRV SLR C
Solar/Wind Harmer
0.11
945111AF1-176 GEN
Solar/Wind Harmer
3.927
24642205MAYFLWER
Adder
0.425
247643Z2-116 C
Solar/Wind Harmer
0.044
970349AG2-230 GEN
Solar/Wind Harmer
8.425
270535AF1-215 GEN1
Solar/Wind Harmer
2.357
970031AG2-029 GEN
Solar/Wind Harmer
15.546
972231SS25-0005
Solar/Wind Harmer
4.819
972181SS23-001
Solar/Wind Harmer
3.012
274752CRETE EC ;2U
Adder
2.482
274753CRETE EC ;3U
Adder
2.482
964401AG1-302 GEN
Solar/Wind Harmer
4.552
274724RIVER EC ;11
Adder
8.868
274802UNIV PARK;5U
Adder
2.854
274826FISK ;BP
Adder
5.344
274800UNIV PARK;3U
Adder
2.839
972038AH1-567 GEN2
Adder
0.178
959141AF2-205 GEN
Solar/Wind Harmer
2.942
276772AC2-154 GEN
Solar/Wind Harmer
1.354
276806AD2-047 C O1
Solar/Wind Harmer
5.193
970941AG2-585 GEN
Solar/Wind Harmer
6.068
274772LINCOLN ;3U
Adder
2.999
972228AH1-698 GEN2
Adder
1.79
274676JOLIET 29;8U
Adder
14.201
276893AG1-478 C
Solar/Wind Harmer
0.2
274729ELWOOD EC;1P
Adder
7.866
274730ELWOOD EC;6P
Adder
7.866
274734ELWOOD EC;8P
Adder
7.866
274736ELWOOD EC;9P
Adder
7.866
276897AD1-100 C
Solar/Wind Harmer
13.875
939351AE1-166 GEN
Solar/Wind Harmer
2.835
970707AG2-453 GEN
Solar/Wind Harmer
13.377
276694AA1-018 GEN2
Solar/Wind Harmer
2.97
943121AE2-341 GEN
Solar/Wind Harmer
7.059
943591AF1-030 GEN
Solar/Wind Harmer
4.706
274682WAUKEGAN ;7U
Adder
8.393
276805AD2-038 GEN
Solar/Wind Harmer
2.384
970513AG2-328 GEN
Solar/Wind Harmer
8.295
970517AG2-330 GEN
Solar/Wind Harmer
7.523
274872LEEDK;1U
Solar/Wind Harmer
0.118
276799AD1-013 GEN
Solar/Wind Harmer
1.01
946671AF1-331 GEN
Solar/Wind Harmer
0.191
274855GSG-6 ;RU
Solar/Wind Harmer
1.687
274850MENDOTA H;RU
Solar/Wind Harmer
1.173
276602WESTBROOK C
Solar/Wind Harmer
0.971
276863AD2-134 GEN
Solar/Wind Harmer
0.816
276889AE2-281 GEN
Solar/Wind Harmer
0.876
972236AH1-702 GEN2
Adder
0.991
274760LEE CO EC;1U
Adder
4.147
274767LEE CO EC;8U
Adder
4.098
241832AE2-181_GEN
Solar/Wind Helper
1.096
270541AE2-072 C
Solar/Wind Helper
1.484
959091AF2-200 GEN
Solar/Wind Harmer
4.171
270449AD2-020 GEN
Solar/Wind Harmer
2.069
943021AE2-325 GEN
Solar/Wind Harmer
2.688
270505AE1-170 C O1
Solar/Wind Harmer
10.556
945111AF1-176 GEN
Solar/Wind Harmer
12.391
24639705ELKHART HY
Adder
0.095
970373AG2-245 GEN
Solar/Wind Harmer
11.296
270055AF2-134 C O1
Solar/Wind Harmer
1.571
274751CRETE EC ;1U
Adder
2.482
274754CRETE EC ;4U
Adder
2.482
958381AF2-132 GEN
Solar/Wind Harmer
4.552
274723RIVER EC ;12
Adder
8.975
964861AG1-349 GEN
Solar/Wind Harmer
3.93
971917AH1-482 GEN
Solar/Wind Harmer
4.536
274812UNIV PK N;8U
Adder
2.494
270063AE2-323 C
Solar/Wind Harmer
1.09
276164X3-005 C
Solar/Wind Harmer
0.347
274801UNIV PARK;4U
Adder
2.839
276776AD2-060 GEN
Solar/Wind Harmer
0.205
972207SS24-0001
Solar/Wind Harmer
10.663
274773LINCOLN ;4U
Adder
2.999
274774LINCOLN ;5U
Adder
2.999
274676JOLIET 29;8U
Adder
14.726
274732ELWOOD EC;7P
Adder
7.866
274674JOLIET 9 ;6U
Adder
7.368
940581AE2-045 GEN
Solar/Wind Harmer
4.88
971605AH1-302 GEN
Solar/Wind Harmer
4.173
941551AE2-152 GEN
Solar/Wind Harmer
2.168
274871GR RIDGE ;2U
Solar/Wind Harmer
3.647
274745AC1-111 GEN9
Adder
2.633
276691AA1-018 GEN1
Solar/Wind Harmer
0.219
274682WAUKEGAN ;7U
Adder
8.393
274828WAUKEGAN ;BP
Adder
5.152
970245AG2-165 GEN
Solar/Wind Harmer
8.295
276901AD2-066 C O1
Solar/Wind Harmer
1.623
960751AF2-366 GEN
Solar/Wind Harmer
1.325
962781AG1-127 GEN
Solar/Wind Harmer
4.391
274872LEEDK;1U
Solar/Wind Harmer
3.784
939401AE1-172 GEN
Solar/Wind Harmer
6.411
971997AH1-543 GEN
Solar/Wind Harmer
7.215
276861AD2-134 GEN
Solar/Wind Harmer
0.816
276876AE1-163_GEN2
Solar/Wind Harmer
3.065
274822ROCKFORD ;11
Adder
8.894
972235AH1-702 GEN1
Adder
1.14
274761LEE CO EC;2U
Adder
4.147
274766LEE CO EC;7U
Adder
4.098
241808AF1-120 C
Solar/Wind Helper
1.428
241840AF1-064_GEN
Solar/Wind Helper
1.322
241807AE2-176_GEN
Solar/Wind Helper
1.436
241885AC2-103 GEN1
Solar/Wind Helper
1.906
960841AF2-375 GEN
Solar/Wind Helper
1.047
957471AF2-041 GEN
Solar/Wind Harmer
6.257
959081AF2-199 GEN
Solar/Wind Harmer
2.086
971067AG2-660 GEN
Solar/Wind Harmer
0.485
961051AF2-396 GEN
Solar/Wind Harmer
11.459
961051AF2-396 GEN
Solar/Wind Harmer
5.33
957891AF2-083 GEN
Solar/Wind Harmer
2.349
960981AF2-389 GEN
Solar/Wind Harmer
1.053
270216AD2-079_GEN
Solar/Wind Harmer
0.38
270526AF1-158 GEN
Solar/Wind Harmer
2.808
24441505OLIV SLR
Solar/Wind Harmer
0.082
247620Y3-023
Adder
0.274
965681AG1-436 GEN
Solar/Wind Harmer
7.212
965791AG1-447 GEN
Solar/Wind Harmer
3.69
274808UNIV PK N;4U
Adder
2.483
274803UNIV PARK;6U
Adder
2.854
274888KELLY CRK;1U
Solar/Wind Harmer
2.866
274887GEN-1.85
Solar/Wind Harmer
2.588
276843GEN-1.7
Solar/Wind Harmer
0.278
958011AF2-095 GEN
Solar/Wind Harmer
6.991
274770LINCOLN ;1U
Adder
2.999
274771LINCOLN ;2U
Adder
2.999
972259AH1-714 GEN
Adder
9.154
274674JOLIET 9 ;6U
Adder
7.368
274847GR RIDGE ;BU
Solar/Wind Harmer
2.399
958481AF2-142 GEN
Solar/Wind Harmer
7.06
274861TOP CROP ;1U
Solar/Wind Harmer
2.852
274862TOP CROP ;2U
Solar/Wind Harmer
2.382
971573AH1-285 GEN
Solar/Wind Harmer
4.028
274696ROCKY RD ;4P
Adder
5.317
274695ROCKY RD ;2P
Adder
5.195
274693ROCKY RD ;1P
Adder
5.144
274697ROCKY RD ;3P
Adder
1.411
274683WAUKEGAN ;8U
Adder
9.828
274683WAUKEGAN ;8U
Adder
8.285
958491AF2-143 GEN
Solar/Wind Harmer
6.97
970321AG2-212 GEN
Solar/Wind Harmer
8.295
962691AG1-118 GEN
Solar/Wind Harmer
13.883
970921AG2-575 GEN
Solar/Wind Harmer
4.617
970921AG2-575 GEN
Solar/Wind Harmer
1.074
274879MINONK ;1U
Solar/Wind Harmer
3.113
942991AE2-321 GEN
Solar/Wind Harmer
4.594
971333AH1-146 GEN
Solar/Wind Harmer
9.139
971335AH1-147 GEN
Solar/Wind Harmer
9.139
276872AE1-163_GEN1
Solar/Wind Harmer
3.065
945421AF1-207 GEN
Solar/Wind Harmer
6.406
957841AF2-078 GEN
Solar/Wind Harmer
2.757
274764LEE CO EC;5U
Adder
4.157
274765LEE CO EC;6U
Adder
4.157
274762LEE CO EC;3U
Adder
4.147
274763LEE CO EC;4U
Adder
4.108
972267AH1-718 GEN
Adder
1.839
241996AE2-282_GEN
Solar/Wind Helper
2.556
971341AH1-150 GEN
Solar/Wind Harmer
4.171
971343AH1-151 GEN
Solar/Wind Harmer
4.171
971549AH1-272 GEN
Solar/Wind Harmer
20.205
944161AF1-084 GEN
Solar/Wind Harmer
1.682
971771AH1-392 GEN
Solar/Wind Harmer
5.682
971769AH1-391 GEN
Solar/Wind Harmer
6.148
960681AF2-359 GEN
Solar/Wind Harmer
2.18
971347AH1-153 GEN
Solar/Wind Harmer
8.425
270536AF1-215 GEN2
Solar/Wind Harmer
2.357
274814UNIV PK N;0U
Adder
2.516
274807UNIV PK N;3U
Adder
2.51
274805UNIV PK N;1U
Adder
2.5
274811UNIV PK N;7U
Adder
2.494
958391AF2-133 GEN
Solar/Wind Harmer
4.473
972037AH1-567 GEN1
Adder
0.09
274827FISK ;RP
Adder
3.787
960591AF2-350 GEN
Solar/Wind Harmer
4.855
274775LINCOLN ;6U
Adder
2.999
274776LINCOLN ;7U
Adder
2.999
274777LINCOLN ;8U
Adder
2.999
972227AH1-698 GEN1
Adder
1.26
274687WILL CNTY;4U
Adder
13.454
274687WILL CNTY;4U
Adder
13.454
274675JOLIET 29;7U
Adder
14.727
274675JOLIET 29;7U
Adder
14.201
274731ELWOOD EC;2P
Adder
7.866
274733ELWOOD EC;3P
Adder
7.866
274735ELWOOD EC;4P
Adder
7.866
274728ELWOOD EC;5P
Adder
7.866
970833AG2-524 GEN
Solar/Wind Harmer
4.144
970833AG2-524 GEN
Solar/Wind Harmer
1.928
274746AC1-111 G10
Adder
2.633
274744AC1-111 GEN8
Adder
2.633
276868AE1-113 GEN
Solar/Wind Harmer
4.668
276882AE2-255 GEN
Solar/Wind Harmer
1.556
971177AH1-047 GEN
Solar/Wind Harmer
2.691
971411AH1-196 GEN
Solar/Wind Harmer
6.862
971675AH1-338 GEN
Solar/Wind Harmer
8.221
274823ROCKFORD ;21
Adder
8.829
945411AF1-206 GEN
Solar/Wind Helper
4.842
241886AC2-103 GEN2
Solar/Wind Helper
1.906
270499AE1-146 GEN
Solar/Wind Helper
1.599
945641AF1-229 GEN
Solar/Wind Helper
0.873
971171AH1-044 GEN
Solar/Wind Harmer
4.171
991177J1571 G
External Queue
62.399627685546875
990527J1329
External Queue
5.287156105041504
990142J1224
External Queue
38.64910888671875
991182J1586 G
External Queue
59.18217849731445
991227J1663 G
External Queue
12.7299222946167
LAGNLTFEXP_LAGN->PJM
CLTF
4.363
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.93
TVALTFEXP_TVA->PJM
CLTF
1.864
CPLELTFEXP_CPLE->PJM
CLTF
0.396
CBM West 2LTFEXP_CBM-W2->PJM
CBM
34.904
NYPJM->LTFIMP_NY
CLTF
0.9
LGEELTFEXP_LGEE->PJM
CLTF
1.381
WECLTFEXP_WEC->PJM
CLTF
1.727
AG2-052LTFEXP_AG2-052->PJM
LTF
0.112
AH1-155LTFEXP_AH1-155->PJM
LTF
0.168
CBM West 1LTFEXP_CBM-W1->PJM
CBM
149.957
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.099
MECLTFEXP_MEC->PJM
CLTF
6.451
SIGELTFEXP_SIGE->PJM
CLTF
0.132

Details for 18MOROCCO-02ALLEN 345.0 kV Ckt 1 line l/o ATSI_P2-3_TE-345-033T_SRT-A


Base Case Flowgate

Area:ATSI/METC
Facility Description:
18MOROCCO-02ALLEN 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_TE-345-033T_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.35 %
Rating:1793.0 MVA
Rating Type:B
MVA to Mitigate:1942.65
MW Contribution:20.17
Bus #Bus NameTypeMW Contribution
270449AD2-020 GEN
Solar/Wind Harmer
2.054
943021AE2-325 GEN
Solar/Wind Harmer
2.669
270505AE1-170 C O1
Solar/Wind Harmer
10.473
945111AF1-176 GEN
Solar/Wind Harmer
12.289
24639705ELKHART HY
Adder
0.094
970373AG2-245 GEN
Solar/Wind Harmer
11.153
270055AF2-134 C O1
Solar/Wind Harmer
1.55
274751CRETE EC ;1U
Adder
2.448
274754CRETE EC ;4U
Adder
2.448
958381AF2-132 GEN
Solar/Wind Harmer
4.488
274723RIVER EC ;12
Adder
8.849
964861AG1-349 GEN
Solar/Wind Harmer
3.875
971917AH1-482 GEN
Solar/Wind Harmer
4.471
274812UNIV PK N;8U
Adder
2.459
276164X3-005 C
Solar/Wind Harmer
0.342
270063AE2-323 C
Solar/Wind Harmer
1.072
274801UNIV PARK;4U
Adder
2.797
276776AD2-060 GEN
Solar/Wind Harmer
0.202
972207SS24-0001
Solar/Wind Harmer
10.506
274773LINCOLN ;4U
Adder
2.955
274774LINCOLN ;5U
Adder
2.955
274676JOLIET 29;8U
Adder
14.508
274732ELWOOD EC;7P
Adder
7.749
274674JOLIET 9 ;6U
Adder
7.258
940581AE2-045 GEN
Solar/Wind Harmer
4.806
971605AH1-302 GEN
Solar/Wind Harmer
4.11
941551AE2-152 GEN
Solar/Wind Harmer
2.136
274871GR RIDGE ;2U
Solar/Wind Harmer
3.592
274745AC1-111 GEN9
Adder
2.593
276691AA1-018 GEN1
Solar/Wind Harmer
0.216
274682WAUKEGAN ;7U
Adder
8.265
274828WAUKEGAN ;BP
Adder
5.073
970245AG2-165 GEN
Solar/Wind Harmer
8.162
276901AD2-066 C O1
Solar/Wind Harmer
1.598
960751AF2-366 GEN
Solar/Wind Harmer
1.304
962781AG1-127 GEN
Solar/Wind Harmer
4.323
274872LEEDK;1U
Solar/Wind Harmer
3.726
939401AE1-172 GEN
Solar/Wind Harmer
6.31
971997AH1-543 GEN
Solar/Wind Harmer
7.102
276861AD2-134 GEN
Solar/Wind Harmer
0.803
276876AE1-163_GEN2
Solar/Wind Harmer
3.017
274822ROCKFORD ;11
Adder
8.753
972235AH1-702 GEN1
Adder
1.122
274761LEE CO EC;2U
Adder
4.08
274766LEE CO EC;7U
Adder
4.032
241808AF1-120 C
Solar/Wind Helper
1.404
241840AF1-064_GEN
Solar/Wind Helper
1.299
241807AE2-176_GEN
Solar/Wind Helper
1.359
241885AC2-103 GEN1
Solar/Wind Helper
1.76
960841AF2-375 GEN
Solar/Wind Helper
1.115
957471AF2-041 GEN
Solar/Wind Harmer
6.159
959081AF2-199 GEN
Solar/Wind Harmer
2.053
971067AG2-660 GEN
Solar/Wind Harmer
0.477
961051AF2-396 GEN
Solar/Wind Harmer
11.373
961051AF2-396 GEN
Solar/Wind Harmer
5.29
957891AF2-083 GEN
Solar/Wind Harmer
2.33
960981AF2-389 GEN
Solar/Wind Harmer
1.044
270216AD2-079_GEN
Solar/Wind Harmer
0.376
270526AF1-158 GEN
Solar/Wind Harmer
2.78
24441505OLIV SLR
Solar/Wind Harmer
0.082
247620Y3-023
Adder
0.271
965681AG1-436 GEN
Solar/Wind Harmer
7.13
965791AG1-447 GEN
Solar/Wind Harmer
3.648
274808UNIV PK N;4U
Adder
2.448
274803UNIV PARK;6U
Adder
2.812
274888KELLY CRK;1U
Solar/Wind Harmer
2.824
274887GEN-1.85
Solar/Wind Harmer
2.55
276843GEN-1.7
Solar/Wind Harmer
0.274
958011AF2-095 GEN
Solar/Wind Harmer
6.888
274770LINCOLN ;1U
Adder
2.955
274771LINCOLN ;2U
Adder
2.955
972259AH1-714 GEN
Adder
9.018
274674JOLIET 9 ;6U
Adder
7.258
274847GR RIDGE ;BU
Solar/Wind Harmer
2.363
958481AF2-142 GEN
Solar/Wind Harmer
6.953
274861TOP CROP ;1U
Solar/Wind Harmer
2.809
274862TOP CROP ;2U
Solar/Wind Harmer
2.345
971573AH1-285 GEN
Solar/Wind Harmer
3.967
274696ROCKY RD ;4P
Adder
5.236
274695ROCKY RD ;2P
Adder
5.115
274693ROCKY RD ;1P
Adder
5.065
274697ROCKY RD ;3P
Adder
1.39
274683WAUKEGAN ;8U
Adder
9.678
274683WAUKEGAN ;8U
Adder
8.158
247604X1-042
Adder
0.356
24441205WTRV SLR C
Solar/Wind Harmer
0.11
945111AF1-176 GEN
Solar/Wind Harmer
3.895
24642205MAYFLWER
Adder
0.421
247643Z2-116 C
Solar/Wind Harmer
0.043
970349AG2-230 GEN
Solar/Wind Harmer
8.323
270535AF1-215 GEN1
Solar/Wind Harmer
2.325
970031AG2-029 GEN
Solar/Wind Harmer
15.287
972231SS25-0005
Solar/Wind Harmer
4.752
972181SS23-001
Solar/Wind Harmer
2.97
274752CRETE EC ;2U
Adder
2.448
274753CRETE EC ;3U
Adder
2.448
964401AG1-302 GEN
Solar/Wind Harmer
4.488
274724RIVER EC ;11
Adder
8.744
274802UNIV PARK;5U
Adder
2.812
274826FISK ;BP
Adder
5.266
274800UNIV PARK;3U
Adder
2.797
972038AH1-567 GEN2
Adder
0.175
959141AF2-205 GEN
Solar/Wind Harmer
2.898
276772AC2-154 GEN
Solar/Wind Harmer
1.334
276806AD2-047 C O1
Solar/Wind Harmer
5.117
970941AG2-585 GEN
Solar/Wind Harmer
5.98
274772LINCOLN ;3U
Adder
2.955
972228AH1-698 GEN2
Adder
1.764
274676JOLIET 29;8U
Adder
13.99
276893AG1-478 C
Solar/Wind Harmer
0.197
274729ELWOOD EC;1P
Adder
7.749
274730ELWOOD EC;6P
Adder
7.749
274734ELWOOD EC;8P
Adder
7.749
274736ELWOOD EC;9P
Adder
7.749
276897AD1-100 C
Solar/Wind Harmer
13.667
939351AE1-166 GEN
Solar/Wind Harmer
2.793
970707AG2-453 GEN
Solar/Wind Harmer
13.177
276694AA1-018 GEN2
Solar/Wind Harmer
2.925
943121AE2-341 GEN
Solar/Wind Harmer
6.952
943591AF1-030 GEN
Solar/Wind Harmer
4.635
274682WAUKEGAN ;7U
Adder
8.265
276805AD2-038 GEN
Solar/Wind Harmer
2.347
970513AG2-328 GEN
Solar/Wind Harmer
8.162
970517AG2-330 GEN
Solar/Wind Harmer
7.403
274872LEEDK;1U
Solar/Wind Harmer
0.116
276799AD1-013 GEN
Solar/Wind Harmer
0.994
946671AF1-331 GEN
Solar/Wind Harmer
0.188
274855GSG-6 ;RU
Solar/Wind Harmer
1.66
274850MENDOTA H;RU
Solar/Wind Harmer
1.154
276602WESTBROOK C
Solar/Wind Harmer
0.956
276863AD2-134 GEN
Solar/Wind Harmer
0.803
276889AE2-281 GEN
Solar/Wind Harmer
0.862
972236AH1-702 GEN2
Adder
0.975
274760LEE CO EC;1U
Adder
4.08
274767LEE CO EC;8U
Adder
4.032
241832AE2-181_GEN
Solar/Wind Helper
1.079
270541AE2-072 C
Solar/Wind Helper
1.503
959091AF2-200 GEN
Solar/Wind Harmer
4.106
958491AF2-143 GEN
Solar/Wind Harmer
6.863
970321AG2-212 GEN
Solar/Wind Harmer
8.162
962691AG1-118 GEN
Solar/Wind Harmer
13.669
970921AG2-575 GEN
Solar/Wind Harmer
4.546
970921AG2-575 GEN
Solar/Wind Harmer
1.057
274879MINONK ;1U
Solar/Wind Harmer
3.064
942991AE2-321 GEN
Solar/Wind Harmer
4.522
971333AH1-146 GEN
Solar/Wind Harmer
8.996
971335AH1-147 GEN
Solar/Wind Harmer
8.996
276872AE1-163_GEN1
Solar/Wind Harmer
3.017
945421AF1-207 GEN
Solar/Wind Harmer
6.302
957841AF2-078 GEN
Solar/Wind Harmer
2.712
274764LEE CO EC;5U
Adder
4.09
274765LEE CO EC;6U
Adder
4.09
274762LEE CO EC;3U
Adder
4.08
274763LEE CO EC;4U
Adder
4.042
972267AH1-718 GEN
Adder
1.809
241996AE2-282_GEN
Solar/Wind Helper
2.512
971341AH1-150 GEN
Solar/Wind Harmer
4.106
971343AH1-151 GEN
Solar/Wind Harmer
4.106
971549AH1-272 GEN
Solar/Wind Harmer
20.173
944161AF1-084 GEN
Solar/Wind Harmer
1.671
971771AH1-392 GEN
Solar/Wind Harmer
5.626
971769AH1-391 GEN
Solar/Wind Harmer
6.085
960681AF2-359 GEN
Solar/Wind Harmer
2.155
971347AH1-153 GEN
Solar/Wind Harmer
8.323
270536AF1-215 GEN2
Solar/Wind Harmer
2.325
274814UNIV PK N;0U
Adder
2.48
274807UNIV PK N;3U
Adder
2.475
274805UNIV PK N;1U
Adder
2.464
274811UNIV PK N;7U
Adder
2.459
958391AF2-133 GEN
Solar/Wind Harmer
4.409
972037AH1-567 GEN1
Adder
0.088
274827FISK ;RP
Adder
3.732
960591AF2-350 GEN
Solar/Wind Harmer
4.784
274775LINCOLN ;6U
Adder
2.955
274776LINCOLN ;7U
Adder
2.955
274777LINCOLN ;8U
Adder
2.955
972227AH1-698 GEN1
Adder
1.242
274687WILL CNTY;4U
Adder
13.255
274687WILL CNTY;4U
Adder
13.255
274675JOLIET 29;7U
Adder
14.508
274675JOLIET 29;7U
Adder
13.99
274731ELWOOD EC;2P
Adder
7.749
274733ELWOOD EC;3P
Adder
7.749
274735ELWOOD EC;4P
Adder
7.749
274728ELWOOD EC;5P
Adder
7.749
970833AG2-524 GEN
Solar/Wind Harmer
4.082
970833AG2-524 GEN
Solar/Wind Harmer
1.899
274746AC1-111 G10
Adder
2.593
274744AC1-111 GEN8
Adder
2.593
276868AE1-113 GEN
Solar/Wind Harmer
4.596
276882AE2-255 GEN
Solar/Wind Harmer
1.532
971177AH1-047 GEN
Solar/Wind Harmer
2.649
971411AH1-196 GEN
Solar/Wind Harmer
6.755
971675AH1-338 GEN
Solar/Wind Harmer
8.093
274823ROCKFORD ;21
Adder
8.69
945411AF1-206 GEN
Solar/Wind Helper
4.76
241886AC2-103 GEN2
Solar/Wind Helper
1.76
270499AE1-146 GEN
Solar/Wind Helper
1.702
945641AF1-229 GEN
Solar/Wind Helper
0.975
971171AH1-044 GEN
Solar/Wind Harmer
4.106
991177J1571 G
External Queue
62.85662078857422
990527J1329
External Queue
5.334218978881836
990142J1224
External Queue
38.99313735961914
991182J1586 G
External Queue
59.741127014160156
991227J1663 G
External Queue
12.83681869506836
LAGNLTFEXP_LAGN->PJM
CLTF
4.227
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.789
TVALTFEXP_TVA->PJM
CLTF
1.796
CPLELTFEXP_CPLE->PJM
CLTF
0.354
CBM West 2LTFEXP_CBM-W2->PJM
CBM
33.929
NYPJM->LTFIMP_NY
CLTF
0.875
LGEELTFEXP_LGEE->PJM
CLTF
1.321
WECLTFEXP_WEC->PJM
CLTF
1.7
AG2-052LTFEXP_AG2-052->PJM
LTF
0.111
AH1-155LTFEXP_AH1-155->PJM
LTF
0.166
CBM West 1LTFEXP_CBM-W1->PJM
CBM
149.7
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.83
MECLTFEXP_MEC->PJM
CLTF
6.33
SIGELTFEXP_SIGE->PJM
CLTF
0.128

Details for 19MON12-02LALLENDORF 345.0 kV Ckt 1 line l/o ATSI_P2-3_TE-345-023T_SRT-SL


Base Case Flowgate

Area:ATSI/ITCT
Facility Description:
19MON12-02LALLENDORF 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_TE-345-023T_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.29 %
Rating:1660.0 MVA
Rating Type:B
MVA to Mitigate:1946.94
MW Contribution:20.75
Bus #Bus NameTypeMW Contribution
971549AH1-272 GEN
Solar/Wind Harmer
20.75
944161AF1-084 GEN
Solar/Wind Harmer
1.752
971771AH1-392 GEN
Solar/Wind Harmer
5.93
971769AH1-391 GEN
Solar/Wind Harmer
6.412
960681AF2-359 GEN
Solar/Wind Harmer
2.273
971347AH1-153 GEN
Solar/Wind Harmer
8.79
270536AF1-215 GEN2
Solar/Wind Harmer
2.459
274814UNIV PK N;0U
Adder
2.626
274807UNIV PK N;3U
Adder
2.62
274805UNIV PK N;1U
Adder
2.609
274811UNIV PK N;7U
Adder
2.603
958391AF2-133 GEN
Solar/Wind Harmer
4.67
972037AH1-567 GEN1
Adder
0.094
274827FISK ;RP
Adder
3.953
960591AF2-350 GEN
Solar/Wind Harmer
5.068
274775LINCOLN ;6U
Adder
3.131
274776LINCOLN ;7U
Adder
3.131
274777LINCOLN ;8U
Adder
3.131
972227AH1-698 GEN1
Adder
1.316
274687WILL CNTY;4U
Adder
14.044
274687WILL CNTY;4U
Adder
14.044
274675JOLIET 29;7U
Adder
15.373
274675JOLIET 29;7U
Adder
14.824
274731ELWOOD EC;2P
Adder
8.211
274733ELWOOD EC;3P
Adder
8.211
274735ELWOOD EC;4P
Adder
8.211
274728ELWOOD EC;5P
Adder
8.212
970833AG2-524 GEN
Solar/Wind Harmer
4.326
970833AG2-524 GEN
Solar/Wind Harmer
2.012
274746AC1-111 G10
Adder
2.748
274744AC1-111 GEN8
Adder
2.748
276868AE1-113 GEN
Solar/Wind Harmer
4.873
276882AE2-255 GEN
Solar/Wind Harmer
1.625
971177AH1-047 GEN
Solar/Wind Harmer
2.809
971411AH1-196 GEN
Solar/Wind Harmer
7.163
971675AH1-338 GEN
Solar/Wind Harmer
8.582
274823ROCKFORD ;21
Adder
9.216
241886AC2-103 GEN2
Solar/Wind Helper
2.07
945411AF1-206 GEN
Solar/Wind Helper
1.882
945641AF1-229 GEN
Solar/Wind Helper
1.018
270499AE1-146 GEN
Solar/Wind Helper
1.555
971171AH1-044 GEN
Solar/Wind Harmer
4.354
247604X1-042
50/50
0.395
24441205WTRV SLR C
Solar/Wind Harmer
0.115
945111AF1-176 GEN
Solar/Wind Harmer
4.096
24642205MAYFLWER
Adder
0.443
247643Z2-116 C
Solar/Wind Harmer
0.046
970349AG2-230 GEN
Solar/Wind Harmer
8.79
970031AG2-029 GEN
Solar/Wind Harmer
16.396
270535AF1-215 GEN1
Solar/Wind Harmer
2.459
972231SS25-0005
Solar/Wind Harmer
5.029
972181SS23-001
Solar/Wind Harmer
3.143
274752CRETE EC ;2U
Adder
2.59
274753CRETE EC ;3U
Adder
2.59
964401AG1-302 GEN
Solar/Wind Harmer
4.752
274724RIVER EC ;11
Adder
9.257
274802UNIV PARK;5U
Adder
2.979
274826FISK ;BP
Adder
5.578
274800UNIV PARK;3U
Adder
2.963
972038AH1-567 GEN2
Adder
0.185
959141AF2-205 GEN
Solar/Wind Harmer
3.072
276772AC2-154 GEN
Solar/Wind Harmer
1.413
276806AD2-047 C O1
Solar/Wind Harmer
5.421
970941AG2-585 GEN
Solar/Wind Harmer
6.335
274772LINCOLN ;3U
Adder
3.131
972228AH1-698 GEN2
Adder
1.869
274676JOLIET 29;8U
Adder
14.823
276893AG1-478 C
Solar/Wind Harmer
0.209
274729ELWOOD EC;1P
Adder
8.211
274730ELWOOD EC;6P
Adder
8.212
274734ELWOOD EC;8P
Adder
8.212
274736ELWOOD EC;9P
Adder
8.212
276897AD1-100 C
Solar/Wind Harmer
14.484
939351AE1-166 GEN
Solar/Wind Harmer
2.96
970707AG2-453 GEN
Solar/Wind Harmer
13.965
276694AA1-018 GEN2
Solar/Wind Harmer
3.101
943121AE2-341 GEN
Solar/Wind Harmer
7.369
943591AF1-030 GEN
Solar/Wind Harmer
4.913
274682WAUKEGAN ;7U
Adder
8.761
970513AG2-328 GEN
Solar/Wind Harmer
8.665
970517AG2-330 GEN
Solar/Wind Harmer
7.859
276805AD2-038 GEN
Solar/Wind Harmer
2.488
274872LEEDK;1U
Solar/Wind Harmer
0.123
276799AD1-013 GEN
Solar/Wind Harmer
1.054
946671AF1-331 GEN
Solar/Wind Harmer
0.2
274855GSG-6 ;RU
Solar/Wind Harmer
1.76
274850MENDOTA H;RU
Solar/Wind Harmer
1.224
276602WESTBROOK C
Solar/Wind Harmer
1.013
276863AD2-134 GEN
Solar/Wind Harmer
0.851
276889AE2-281 GEN
Solar/Wind Harmer
0.914
972236AH1-702 GEN2
Adder
1.034
274760LEE CO EC;1U
Adder
4.329
274767LEE CO EC;8U
Adder
4.278
241832AE2-181_GEN
Solar/Wind Helper
0.429
959091AF2-200 GEN
Solar/Wind Harmer
4.354
270449AD2-020 GEN
Solar/Wind Harmer
2.155
943021AE2-325 GEN
Solar/Wind Harmer
2.8
270505AE1-170 C O1
Solar/Wind Harmer
11.001
945111AF1-176 GEN
Solar/Wind Harmer
12.923
24639705ELKHART HY
Adder
0.1
970373AG2-245 GEN
Solar/Wind Harmer
11.786
270055AF2-134 C O1
Solar/Wind Harmer
1.639
270063AE2-323 C
Solar/Wind Harmer
1.177
274751CRETE EC ;1U
Adder
2.59
274754CRETE EC ;4U
Adder
2.59
958381AF2-132 GEN
Solar/Wind Harmer
4.752
274723RIVER EC ;12
Adder
9.368
964861AG1-349 GEN
Solar/Wind Harmer
4.103
971917AH1-482 GEN
Solar/Wind Harmer
4.735
274812UNIV PK N;8U
Adder
2.603
276164X3-005 C
Solar/Wind Harmer
0.363
274801UNIV PARK;4U
Adder
2.963
276776AD2-060 GEN
Solar/Wind Harmer
0.214
972207SS24-0001
Solar/Wind Harmer
11.132
274773LINCOLN ;4U
Adder
3.131
274774LINCOLN ;5U
Adder
3.131
274676JOLIET 29;8U
Adder
15.372
940581AE2-045 GEN
Solar/Wind Harmer
5.096
971605AH1-302 GEN
Solar/Wind Harmer
4.358
274732ELWOOD EC;7P
Adder
8.212
274674JOLIET 9 ;6U
Adder
7.691
941551AE2-152 GEN
Solar/Wind Harmer
2.264
274871GR RIDGE ;2U
Solar/Wind Harmer
3.807
274745AC1-111 GEN9
Adder
2.748
276691AA1-018 GEN1
Solar/Wind Harmer
0.229
274682WAUKEGAN ;7U
Adder
8.761
274828WAUKEGAN ;BP
Adder
5.378
970245AG2-165 GEN
Solar/Wind Harmer
8.665
276901AD2-066 C O1
Solar/Wind Harmer
1.695
960751AF2-366 GEN
Solar/Wind Harmer
1.383
962781AG1-127 GEN
Solar/Wind Harmer
4.583
274872LEEDK;1U
Solar/Wind Harmer
3.95
939401AE1-172 GEN
Solar/Wind Harmer
6.693
971997AH1-543 GEN
Solar/Wind Harmer
7.532
276861AD2-134 GEN
Solar/Wind Harmer
0.851
276876AE1-163_GEN2
Solar/Wind Harmer
3.2
274822ROCKFORD ;11
Adder
9.283
972235AH1-702 GEN1
Adder
1.189
274761LEE CO EC;2U
Adder
4.329
274766LEE CO EC;7U
Adder
4.278
241885AC2-103 GEN1
Solar/Wind Helper
2.07
241807AE2-176_GEN
Solar/Wind Helper
1.363
241808AF1-120 C
Solar/Wind Helper
0.555
241840AF1-064_GEN
Solar/Wind Helper
0.673
960841AF2-375 GEN
Solar/Wind Helper
1.036
957471AF2-041 GEN
Solar/Wind Harmer
6.531
959081AF2-199 GEN
Solar/Wind Harmer
2.177
971067AG2-660 GEN
Solar/Wind Harmer
0.506
961051AF2-396 GEN
Solar/Wind Harmer
11.942
961051AF2-396 GEN
Solar/Wind Harmer
5.555
957891AF2-083 GEN
Solar/Wind Harmer
2.449
960981AF2-389 GEN
Solar/Wind Harmer
1.097
270216AD2-079_GEN
Solar/Wind Harmer
0.397
270526AF1-158 GEN
Solar/Wind Harmer
2.929
24441505OLIV SLR
Solar/Wind Harmer
0.086
247620Y3-023
Adder
0.289
965681AG1-436 GEN
Solar/Wind Harmer
7.521
965791AG1-447 GEN
Solar/Wind Harmer
3.848
274808UNIV PK N;4U
Adder
2.592
274803UNIV PARK;6U
Adder
2.979
274888KELLY CRK;1U
Solar/Wind Harmer
2.992
274887GEN-1.85
Solar/Wind Harmer
2.701
276843GEN-1.7
Solar/Wind Harmer
0.291
958011AF2-095 GEN
Solar/Wind Harmer
7.297
274770LINCOLN ;1U
Adder
3.131
274771LINCOLN ;2U
Adder
3.131
972259AH1-714 GEN
Adder
9.556
274674JOLIET 9 ;6U
Adder
7.691
274847GR RIDGE ;BU
Solar/Wind Harmer
2.504
958481AF2-142 GEN
Solar/Wind Harmer
7.37
274861TOP CROP ;1U
Solar/Wind Harmer
2.977
274862TOP CROP ;2U
Solar/Wind Harmer
2.486
971573AH1-285 GEN
Solar/Wind Harmer
4.205
274696ROCKY RD ;4P
Adder
5.551
274695ROCKY RD ;2P
Adder
5.423
274693ROCKY RD ;1P
Adder
5.369
274697ROCKY RD ;3P
Adder
1.473
274683WAUKEGAN ;8U
Adder
10.259
274683WAUKEGAN ;8U
Adder
8.648
970321AG2-212 GEN
Solar/Wind Harmer
8.665
958491AF2-143 GEN
Solar/Wind Harmer
7.276
962691AG1-118 GEN
Solar/Wind Harmer
14.492
970921AG2-575 GEN
Solar/Wind Harmer
4.82
970921AG2-575 GEN
Solar/Wind Harmer
1.121
274879MINONK ;1U
Solar/Wind Harmer
3.249
942991AE2-321 GEN
Solar/Wind Harmer
4.795
971333AH1-146 GEN
Solar/Wind Harmer
9.539
971335AH1-147 GEN
Solar/Wind Harmer
9.539
276872AE1-163_GEN1
Solar/Wind Harmer
3.2
945421AF1-207 GEN
Solar/Wind Harmer
6.692
957841AF2-078 GEN
Solar/Wind Harmer
2.88
274764LEE CO EC;5U
Adder
4.339
274765LEE CO EC;6U
Adder
4.339
274762LEE CO EC;3U
Adder
4.329
274763LEE CO EC;4U
Adder
4.288
972267AH1-718 GEN
Adder
1.919
241996AE2-282_GEN
Solar/Wind Helper
0.994
971341AH1-150 GEN
Solar/Wind Harmer
4.354
971343AH1-151 GEN
Solar/Wind Harmer
4.354
991177J1571 G
External Queue
36.20563507080078
990527J1329
External Queue
4.328737258911133
990142J1224
External Queue
31.64306640625
991182J1586 G
External Queue
55.963897705078125
991227J1663 G
External Queue
12.278471946716309
LAGNLTFEXP_LAGN->PJM
CLTF
4.532
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.937
TVALTFEXP_TVA->PJM
CLTF
1.933
CPLELTFEXP_CPLE->PJM
CLTF
0.382
CBM West 2LTFEXP_CBM-W2->PJM
CBM
36.37
NYPJM->LTFIMP_NY
CLTF
0.969
LGEELTFEXP_LGEE->PJM
CLTF
1.44
WECLTFEXP_WEC->PJM
CLTF
1.803
AG2-052LTFEXP_AG2-052->PJM
LTF
0.117
AH1-155LTFEXP_AH1-155->PJM
LTF
0.176
CBM West 1LTFEXP_CBM-W1->PJM
CBM
164.071
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.37
MECLTFEXP_MEC->PJM
CLTF
6.73
SIGELTFEXP_SIGE->PJM
CLTF
0.138

Details for 19MON12-02LALLENDORF 345.0 kV Ckt 1 line l/o ATSI_P2-3_TE-345-022T_SRT-A


Base Case Flowgate

Area:ATSI/ITCT
Facility Description:
19MON12-02LALLENDORF 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_TE-345-022T_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.16 %
Rating:1660.0 MVA
Rating Type:B
MVA to Mitigate:1944.85
MW Contribution:20.75
Bus #Bus NameTypeMW Contribution
971549AH1-272 GEN
Solar/Wind Harmer
20.75
944161AF1-084 GEN
Solar/Wind Harmer
1.752
971771AH1-392 GEN
Solar/Wind Harmer
5.93
971769AH1-391 GEN
Solar/Wind Harmer
6.412
960681AF2-359 GEN
Solar/Wind Harmer
2.273
971347AH1-153 GEN
Solar/Wind Harmer
8.791
270536AF1-215 GEN2
Solar/Wind Harmer
2.46
274814UNIV PK N;0U
Adder
2.626
274807UNIV PK N;3U
Adder
2.621
274805UNIV PK N;1U
Adder
2.609
274811UNIV PK N;7U
Adder
2.604
958391AF2-133 GEN
Solar/Wind Harmer
4.671
972037AH1-567 GEN1
Adder
0.094
274827FISK ;RP
Adder
3.954
960591AF2-350 GEN
Solar/Wind Harmer
5.068
274775LINCOLN ;6U
Adder
3.131
274776LINCOLN ;7U
Adder
3.131
274777LINCOLN ;8U
Adder
3.131
972227AH1-698 GEN1
Adder
1.316
274687WILL CNTY;4U
Adder
14.046
274687WILL CNTY;4U
Adder
14.046
274675JOLIET 29;7U
Adder
15.374
274675JOLIET 29;7U
Adder
14.825
274731ELWOOD EC;2P
Adder
8.212
274733ELWOOD EC;3P
Adder
8.212
274735ELWOOD EC;4P
Adder
8.212
274728ELWOOD EC;5P
Adder
8.213
970833AG2-524 GEN
Solar/Wind Harmer
4.327
970833AG2-524 GEN
Solar/Wind Harmer
2.012
274746AC1-111 G10
Adder
2.749
274744AC1-111 GEN8
Adder
2.749
276868AE1-113 GEN
Solar/Wind Harmer
4.874
276882AE2-255 GEN
Solar/Wind Harmer
1.625
971177AH1-047 GEN
Solar/Wind Harmer
2.809
971411AH1-196 GEN
Solar/Wind Harmer
7.164
971675AH1-338 GEN
Solar/Wind Harmer
8.583
274823ROCKFORD ;21
Adder
9.217
241886AC2-103 GEN2
Solar/Wind Helper
2.071
945411AF1-206 GEN
Solar/Wind Helper
1.844
945641AF1-229 GEN
Solar/Wind Helper
1.019
270499AE1-146 GEN
Solar/Wind Helper
1.555
971171AH1-044 GEN
Solar/Wind Harmer
4.355
247604X1-042
50/50
0.395
24441205WTRV SLR C
Solar/Wind Harmer
0.115
945111AF1-176 GEN
Solar/Wind Harmer
4.096
24642205MAYFLWER
Adder
0.443
247643Z2-116 C
Solar/Wind Harmer
0.046
970349AG2-230 GEN
Solar/Wind Harmer
8.791
970031AG2-029 GEN
Solar/Wind Harmer
16.401
270535AF1-215 GEN1
Solar/Wind Harmer
2.46
972231SS25-0005
Solar/Wind Harmer
5.03
972181SS23-001
Solar/Wind Harmer
3.144
274752CRETE EC ;2U
Adder
2.591
274753CRETE EC ;3U
Adder
2.591
964401AG1-302 GEN
Solar/Wind Harmer
4.753
274724RIVER EC ;11
Adder
9.258
274802UNIV PARK;5U
Adder
2.979
274826FISK ;BP
Adder
5.579
274800UNIV PARK;3U
Adder
2.963
972038AH1-567 GEN2
Adder
0.185
959141AF2-205 GEN
Solar/Wind Harmer
3.072
276772AC2-154 GEN
Solar/Wind Harmer
1.413
276806AD2-047 C O1
Solar/Wind Harmer
5.422
970941AG2-585 GEN
Solar/Wind Harmer
6.335
274772LINCOLN ;3U
Adder
3.131
972228AH1-698 GEN2
Adder
1.869
274676JOLIET 29;8U
Adder
14.825
276893AG1-478 C
Solar/Wind Harmer
0.209
274729ELWOOD EC;1P
Adder
8.212
274730ELWOOD EC;6P
Adder
8.213
274734ELWOOD EC;8P
Adder
8.213
274736ELWOOD EC;9P
Adder
8.213
276897AD1-100 C
Solar/Wind Harmer
14.486
939351AE1-166 GEN
Solar/Wind Harmer
2.96
970707AG2-453 GEN
Solar/Wind Harmer
13.966
276694AA1-018 GEN2
Solar/Wind Harmer
3.101
943121AE2-341 GEN
Solar/Wind Harmer
7.37
943591AF1-030 GEN
Solar/Wind Harmer
4.913
274682WAUKEGAN ;7U
Adder
8.762
970513AG2-328 GEN
Solar/Wind Harmer
8.666
970517AG2-330 GEN
Solar/Wind Harmer
7.86
276805AD2-038 GEN
Solar/Wind Harmer
2.489
274872LEEDK;1U
Solar/Wind Harmer
0.123
276799AD1-013 GEN
Solar/Wind Harmer
1.055
946671AF1-331 GEN
Solar/Wind Harmer
0.2
274855GSG-6 ;RU
Solar/Wind Harmer
1.761
274850MENDOTA H;RU
Solar/Wind Harmer
1.224
276602WESTBROOK C
Solar/Wind Harmer
1.013
276863AD2-134 GEN
Solar/Wind Harmer
0.851
276889AE2-281 GEN
Solar/Wind Harmer
0.914
972236AH1-702 GEN2
Adder
1.034
274760LEE CO EC;1U
Adder
4.329
274767LEE CO EC;8U
Adder
4.278
241832AE2-181_GEN
Solar/Wind Helper
0.421
959091AF2-200 GEN
Solar/Wind Harmer
4.355
270449AD2-020 GEN
Solar/Wind Harmer
2.155
943021AE2-325 GEN
Solar/Wind Harmer
2.801
270505AE1-170 C O1
Solar/Wind Harmer
11.002
945111AF1-176 GEN
Solar/Wind Harmer
12.924
24639705ELKHART HY
Adder
0.1
970373AG2-245 GEN
Solar/Wind Harmer
11.788
270055AF2-134 C O1
Solar/Wind Harmer
1.64
270063AE2-323 C
Solar/Wind Harmer
1.178
274751CRETE EC ;1U
Adder
2.591
274754CRETE EC ;4U
Adder
2.591
958381AF2-132 GEN
Solar/Wind Harmer
4.753
274723RIVER EC ;12
Adder
9.37
964861AG1-349 GEN
Solar/Wind Harmer
4.104
971917AH1-482 GEN
Solar/Wind Harmer
4.736
274812UNIV PK N;8U
Adder
2.604
276164X3-005 C
Solar/Wind Harmer
0.363
274801UNIV PARK;4U
Adder
2.963
276776AD2-060 GEN
Solar/Wind Harmer
0.214
972207SS24-0001
Solar/Wind Harmer
11.133
274773LINCOLN ;4U
Adder
3.131
274774LINCOLN ;5U
Adder
3.131
274676JOLIET 29;8U
Adder
15.374
940581AE2-045 GEN
Solar/Wind Harmer
5.097
971605AH1-302 GEN
Solar/Wind Harmer
4.358
274732ELWOOD EC;7P
Adder
8.213
274674JOLIET 9 ;6U
Adder
7.692
941551AE2-152 GEN
Solar/Wind Harmer
2.264
274871GR RIDGE ;2U
Solar/Wind Harmer
3.808
274745AC1-111 GEN9
Adder
2.749
276691AA1-018 GEN1
Solar/Wind Harmer
0.229
274682WAUKEGAN ;7U
Adder
8.762
274828WAUKEGAN ;BP
Adder
5.378
970245AG2-165 GEN
Solar/Wind Harmer
8.666
276901AD2-066 C O1
Solar/Wind Harmer
1.695
960751AF2-366 GEN
Solar/Wind Harmer
1.383
962781AG1-127 GEN
Solar/Wind Harmer
4.584
274872LEEDK;1U
Solar/Wind Harmer
3.951
939401AE1-172 GEN
Solar/Wind Harmer
6.694
971997AH1-543 GEN
Solar/Wind Harmer
7.533
276861AD2-134 GEN
Solar/Wind Harmer
0.851
276876AE1-163_GEN2
Solar/Wind Harmer
3.2
274822ROCKFORD ;11
Adder
9.285
972235AH1-702 GEN1
Adder
1.19
274761LEE CO EC;2U
Adder
4.329
274766LEE CO EC;7U
Adder
4.278
241885AC2-103 GEN1
Solar/Wind Helper
2.071
241807AE2-176_GEN
Solar/Wind Helper
1.362
241808AF1-120 C
Solar/Wind Helper
0.544
241840AF1-064_GEN
Solar/Wind Helper
0.672
960841AF2-375 GEN
Solar/Wind Helper
1.036
957471AF2-041 GEN
Solar/Wind Harmer
6.532
959081AF2-199 GEN
Solar/Wind Harmer
2.177
971067AG2-660 GEN
Solar/Wind Harmer
0.506
961051AF2-396 GEN
Solar/Wind Harmer
11.943
961051AF2-396 GEN
Solar/Wind Harmer
5.555
957891AF2-083 GEN
Solar/Wind Harmer
2.449
960981AF2-389 GEN
Solar/Wind Harmer
1.097
270216AD2-079_GEN
Solar/Wind Harmer
0.397
270526AF1-158 GEN
Solar/Wind Harmer
2.929
24441505OLIV SLR
Solar/Wind Harmer
0.086
247620Y3-023
Adder
0.289
965681AG1-436 GEN
Solar/Wind Harmer
7.522
965791AG1-447 GEN
Solar/Wind Harmer
3.849
274808UNIV PK N;4U
Adder
2.592
274803UNIV PARK;6U
Adder
2.979
274888KELLY CRK;1U
Solar/Wind Harmer
2.992
274887GEN-1.85
Solar/Wind Harmer
2.702
276843GEN-1.7
Solar/Wind Harmer
0.291
958011AF2-095 GEN
Solar/Wind Harmer
7.298
274770LINCOLN ;1U
Adder
3.131
274771LINCOLN ;2U
Adder
3.131
972259AH1-714 GEN
Adder
9.558
274674JOLIET 9 ;6U
Adder
7.692
274847GR RIDGE ;BU
Solar/Wind Harmer
2.505
274861TOP CROP ;1U
Solar/Wind Harmer
2.978
274862TOP CROP ;2U
Solar/Wind Harmer
2.486
958481AF2-142 GEN
Solar/Wind Harmer
7.371
971573AH1-285 GEN
Solar/Wind Harmer
4.206
274696ROCKY RD ;4P
Adder
5.551
274695ROCKY RD ;2P
Adder
5.423
274693ROCKY RD ;1P
Adder
5.37
274697ROCKY RD ;3P
Adder
1.473
274683WAUKEGAN ;8U
Adder
10.261
274683WAUKEGAN ;8U
Adder
8.649
970321AG2-212 GEN
Solar/Wind Harmer
8.666
958491AF2-143 GEN
Solar/Wind Harmer
7.277
962691AG1-118 GEN
Solar/Wind Harmer
14.494
970921AG2-575 GEN
Solar/Wind Harmer
4.82
970921AG2-575 GEN
Solar/Wind Harmer
1.121
274879MINONK ;1U
Solar/Wind Harmer
3.249
942991AE2-321 GEN
Solar/Wind Harmer
4.796
971333AH1-146 GEN
Solar/Wind Harmer
9.541
971335AH1-147 GEN
Solar/Wind Harmer
9.541
276872AE1-163_GEN1
Solar/Wind Harmer
3.2
945421AF1-207 GEN
Solar/Wind Harmer
6.693
957841AF2-078 GEN
Solar/Wind Harmer
2.88
274764LEE CO EC;5U
Adder
4.339
274765LEE CO EC;6U
Adder
4.339
274762LEE CO EC;3U
Adder
4.329
274763LEE CO EC;4U
Adder
4.288
972267AH1-718 GEN
Adder
1.919
241996AE2-282_GEN
Solar/Wind Helper
0.973
971341AH1-150 GEN
Solar/Wind Harmer
4.355
971343AH1-151 GEN
Solar/Wind Harmer
4.355
991177J1571 G
External Queue
36.20295715332031
990527J1329
External Queue
4.328125953674316
990142J1224
External Queue
31.638599395751953
991182J1586 G
External Queue
55.95536804199219
991227J1663 G
External Queue
12.277408599853516
LAGNLTFEXP_LAGN->PJM
CLTF
4.532
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.936
TVALTFEXP_TVA->PJM
CLTF
1.933
CPLELTFEXP_CPLE->PJM
CLTF
0.382
CBM West 2LTFEXP_CBM-W2->PJM
CBM
36.373
NYPJM->LTFIMP_NY
CLTF
0.97
LGEELTFEXP_LGEE->PJM
CLTF
1.44
WECLTFEXP_WEC->PJM
CLTF
1.803
AG2-052LTFEXP_AG2-052->PJM
LTF
0.117
AH1-155LTFEXP_AH1-155->PJM
LTF
0.176
CBM West 1LTFEXP_CBM-W1->PJM
CBM
164.076
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.371
MECLTFEXP_MEC->PJM
CLTF
6.731
SIGELTFEXP_SIGE->PJM
CLTF
0.138

Details for AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line l/o ATSI_P2-3_OEC-345-009_SRT-SL


Base Case Flowgate

Area:ATSI
Facility Description:
AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_OEC-345-009_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:165.39 %
Rating:1499.0 MVA
Rating Type:B
MVA to Mitigate:2479.15
MW Contribution:12.69
Bus #Bus NameTypeMW Contribution
23867002DVBSG1
50/50
12.736
972211AH1-690 GEN
50/50
275.935
23888502TROY G1
50/50
1.742
23888602TROY G2
50/50
1.742
23860102FRMENG 1
50/50
1.188
23860202FRMENG 2
50/50
1.188
241886AC2-103 GEN2
Solar/Wind Harmer
25.595
970817AG2-515 GEN
Solar/Wind Harmer
14.806
945411AF1-206 GEN
Solar/Wind Harmer
8.02
270499AE1-146 GEN
Solar/Wind Harmer
2.385
945641AF1-229 GEN
Solar/Wind Harmer
3.427
971549AH1-272 GEN
Solar/Wind Harmer
12.688
270297AD1-101 GEN
Solar/Wind Harmer
1.9
966831AG1-554 GEN
Solar/Wind Harmer
0.712
971989AH1-539 GEN
Solar/Wind Harmer
7.704
247607V1-011 GEN
Solar/Wind Harmer
2.309
957201AF2-014 GEN
Solar/Wind Harmer
2.623
270435AC2-044 GEN
Solar/Wind Harmer
1.157
24190002OREGON_ST1
50/50
3.442
24189802OREGON_CT1
50/50
2.611
23888802TROY G4
50/50
1.742
241996AE2-282_GEN
Solar/Wind Harmer
2.147
971677AH1-339 GEN
Solar/Wind Harmer
6.747
270007AE1-245 C
Solar/Wind Harmer
3.464
942801AE2-298 GEN
Solar/Wind Harmer
0.877
246938BC-WTG3
Solar/Wind Harmer
2.302
246937BC-WTG2
Solar/Wind Harmer
2.263
961051AF2-396 GEN
Solar/Wind Harmer
8.832
961051AF2-396 GEN
Solar/Wind Harmer
4.108
960981AF2-389 GEN
Solar/Wind Harmer
0.827
957891AF2-083 GEN
Solar/Wind Harmer
1.844
247620Y3-023
Adder
0.247
270216AD2-079_GEN
Solar/Wind Harmer
0.32
970611AG2-400 GEN
Solar/Wind Harmer
5.199
270526AF1-158 GEN
Solar/Wind Harmer
2.317
24441505OLIV SLR
Solar/Wind Harmer
0.068
965681AG1-436 GEN
Solar/Wind Harmer
6.102
965791AG1-447 GEN
Solar/Wind Harmer
3.122
270224U2-072_GEN2
Solar/Wind Harmer
0.952
270227U2-072_GEN3
Solar/Wind Harmer
0.952
270228U2-072_GEN4
Solar/Wind Harmer
0.952
270231U2-072_GEN5
Solar/Wind Harmer
0.952
971231AH1-075 GEN
Solar/Wind Harmer
0.379
274808UNIV PK N;4U
Adder
2.237
274803UNIV PARK;6U
Adder
2.587
274888KELLY CRK;1U
Solar/Wind Harmer
2.607
274887GEN-1.85
Solar/Wind Harmer
2.354
276843GEN-1.7
Solar/Wind Harmer
0.253
958011AF2-095 GEN
Solar/Wind Harmer
6.358
274770LINCOLN ;1U
Adder
2.736
274771LINCOLN ;2U
Adder
2.736
942221AE2-234 GEN
Solar/Wind Harmer
0.323
972259AH1-714 GEN
Adder
8.361
274674JOLIET 9 ;6U
Adder
6.73
970321AG2-212 GEN
Solar/Wind Harmer
7.784
274847GR RIDGE ;BU
Solar/Wind Harmer
2.199
203947AF1-006 C
Solar/Wind Helper
0.379
203980AG1-197 GEN
Solar/Wind Helper
0.248
203979AG1-198 GEN
Solar/Wind Helper
0.193
241967AE2-285_GEN
Solar/Wind Helper
0.337
241801AE1-079 GEN
Solar/Wind Helper
0.131
241985AE1-237 GEN
Solar/Wind Helper
0.131
23929302BS-PKR
50/50
2.268
241832AE2-181_GEN
Solar/Wind Harmer
1.946
958321AF2-126 GEN
Solar/Wind Harmer
1.49
23906502RICHG2&3
Adder
1.312
270575GUS2 35KV
Solar/Wind Harmer
10.14
270541AE2-072 C
Solar/Wind Harmer
4.319
970217AG2-149 GEN
Solar/Wind Harmer
22.462
270044AE2-322 C
Solar/Wind Harmer
0.849
270404AC1-167 GEN
Solar/Wind Harmer
0.707
270588AE1-091_GEN
Solar/Wind Harmer
6.832
270258AD1-119 GEN
Solar/Wind Harmer
1.729
247604X1-042
Adder
0.25
24441205WTRV SLR C
Solar/Wind Harmer
0.079
958091AF2-103 GEN
Solar/Wind Harmer
0.094
270491AE1-102 GEN2
Solar/Wind Harmer
0.752
945111AF1-176 GEN
Solar/Wind Harmer
3.104
270191TR4_S_V150
Solar/Wind Harmer
1.62
270247TR4_N_V136
Solar/Wind Harmer
0.459
24642205MAYFLWER
Adder
0.339
970031AG2-029 GEN
Solar/Wind Harmer
15.896
247643Z2-116 C
Solar/Wind Harmer
0.037
959331AF2-224 GEN
Solar/Wind Harmer
5.199
965021AG1-366 GEN
Solar/Wind Harmer
1.209
270485AE1-090_GEN
Solar/Wind Harmer
0.314
270043AE2-236 GEN
Solar/Wind Harmer
2.698
970349AG2-230 GEN
Solar/Wind Harmer
7.29
942871AE2-306 GEN
Solar/Wind Harmer
0.437
270391AF1-285 GEN3
Solar/Wind Harmer
0.224
270377AD1-106 GEN
Solar/Wind Harmer
2.928
270535AF1-215 GEN1
Solar/Wind Harmer
2.093
972231SS25-0005
Solar/Wind Harmer
4.31
972181SS23-001
Solar/Wind Harmer
2.694
274752CRETE EC ;2U
Adder
2.22
274753CRETE EC ;3U
Adder
2.22
964401AG1-302 GEN
Solar/Wind Harmer
4.106
274724RIVER EC ;11
Adder
7.979
959141AF2-205 GEN
Solar/Wind Harmer
2.693
274802UNIV PARK;5U
Adder
2.587
274826FISK ;BP
Adder
4.849
274800UNIV PARK;3U
Adder
2.578
972038AH1-567 GEN2
Adder
0.161
276772AC2-154 GEN
Solar/Wind Harmer
1.231
276806AD2-047 C O1
Solar/Wind Harmer
4.723
970941AG2-585 GEN
Solar/Wind Harmer
5.519
274772LINCOLN ;3U
Adder
2.736
972228AH1-698 GEN2
Adder
1.631
961961AG1-039 GEN
Solar/Wind Harmer
1.256
274676JOLIET 29;8U
Adder
12.955
276897AD1-100 C
Solar/Wind Harmer
12.695
944161AF1-084 GEN
Solar/Wind Harmer
1.256
24191202EL_AA1-006
Adder
0.123
965041AG1-368 GEN
Solar/Wind Harmer
5.428
965051AG1-369 GEN
Solar/Wind Harmer
2.697
971771AH1-392 GEN
Solar/Wind Harmer
4.684
270302AB2-170 GEN
Solar/Wind Harmer
4.348
270317AD1-130_GEN
Solar/Wind Harmer
1.667
971567AH1-282 GEN
Solar/Wind Harmer
7.657
971769AH1-391 GEN
Solar/Wind Harmer
5.074
960681AF2-359 GEN
Solar/Wind Harmer
1.844
971347AH1-153 GEN
Solar/Wind Harmer
7.29
963791AG1-232 GEN
Solar/Wind Harmer
6.504
270578AF1-285 GEN2
Solar/Wind Harmer
0.224
270536AF1-215 GEN2
Solar/Wind Harmer
2.093
270071AF1-092 GEN
Solar/Wind Harmer
6.841
274814UNIV PK N;0U
Adder
2.266
274807UNIV PK N;3U
Adder
2.261
274805UNIV PK N;1U
Adder
2.251
274811UNIV PK N;7U
Adder
2.246
958391AF2-133 GEN
Solar/Wind Harmer
4.069
972037AH1-567 GEN1
Adder
0.081
274827FISK ;RP
Adder
3.436
960591AF2-350 GEN
Solar/Wind Harmer
4.415
274775LINCOLN ;6U
Adder
2.736
274776LINCOLN ;7U
Adder
2.736
274777LINCOLN ;8U
Adder
2.736
972227AH1-698 GEN1
Adder
1.148
274687WILL CNTY;4U
Adder
12.261
274687WILL CNTY;4U
Adder
12.261
274675JOLIET 29;7U
Adder
13.435
274675JOLIET 29;7U
Adder
12.955
274728ELWOOD EC;5P
Adder
7.185
274731ELWOOD EC;2P
Adder
7.185
274733ELWOOD EC;3P
Adder
7.185
274735ELWOOD EC;4P
Adder
7.185
270024AE2-089 GEN
Solar/Wind Harmer
2.045
970833AG2-524 GEN
Solar/Wind Harmer
3.797
970833AG2-524 GEN
Solar/Wind Harmer
1.766
274746AC1-111 G10
Adder
2.416
274744AC1-111 GEN8
Adder
2.416
241982AE2-343 S C
Solar/Wind Helper
0.117
254304AE2-114 C
Solar/Wind Helper
0.112
203846AF2-130 C
Solar/Wind Helper
0.246
241997AF1-093 GEN
Solar/Wind Helper
0.129
203804AE2-113_GEN
Solar/Wind Helper
0.861
24189902OREGON_CT2
50/50
2.559
23888702TROY G3
50/50
1.742
972253AH1-711 GEN
50/50
53.201
23856402BAYSG1
50/50
1.289
23920202STRYCT
50/50
1.895
23860302FRMENG 3
50/50
2.426
241885AC2-103 GEN1
Solar/Wind Harmer
25.595
241858AF1-205_GEN
Solar/Wind Harmer
5.472
241808AF1-120 C
Solar/Wind Harmer
1.197
241840AF1-064_GEN
Solar/Wind Harmer
1.39
972301AH1-735 GEN
Adder
6.573
23906402RICHG1
Adder
1.315
23906502RICHG2&3
Adder
1.312
270361_3
Solar/Wind Harmer
8.607
960841AF2-375 GEN
Solar/Wind Harmer
3.799
241807AE2-176_GEN
Solar/Wind Harmer
3.58
247522W1-056 GEN
Solar/Wind Harmer
1.591
970515AG2-329 GEN
Solar/Wind Harmer
10.186
944231AF1-091 GEN
Solar/Wind Harmer
2.443
270428AC2-015 C
Solar/Wind Harmer
3.305
246936BC-WTG1
Solar/Wind Harmer
2.263
270489AE1-102 GEN1
Solar/Wind Harmer
0.752
965421AG1-410 GEN
Solar/Wind Harmer
17.181
270449AD2-020 GEN
Solar/Wind Harmer
1.572
943021AE2-325 GEN
Solar/Wind Harmer
2.042
24695305TIMB G C
Solar/Wind Harmer
3.08
945111AF1-176 GEN
Solar/Wind Harmer
9.795
270505AE1-170 C O1
Solar/Wind Harmer
8.226
247521TR3_G114
Solar/Wind Harmer
1.816
270246TR4_N_V150
Solar/Wind Harmer
0.459
24639705ELKHART HY
Adder
0.082
270063AE2-323 C
Solar/Wind Harmer
1.171
965011AG1-365 GEN
Solar/Wind Harmer
5.199
270462AD2-086
Solar/Wind Harmer
3.617
270223U2-072_GEN1
Solar/Wind Harmer
0.952
270578AF1-285 GEN2
Solar/Wind Harmer
0.582
270391AF1-285 GEN3
Solar/Wind Harmer
0.582
970905AG2-564 GEN
Solar/Wind Harmer
2.368
970373AG2-245 GEN
Solar/Wind Harmer
9.864
270055AF2-134 C O1
Solar/Wind Harmer
1.395
274751CRETE EC ;1U
Adder
2.22
274754CRETE EC ;4U
Adder
2.22
958381AF2-132 GEN
Solar/Wind Harmer
4.106
964861AG1-349 GEN
Solar/Wind Harmer
3.551
971917AH1-482 GEN
Solar/Wind Harmer
4.098
274723RIVER EC ;12
Adder
8.075
274812UNIV PK N;8U
Adder
2.246
276164X3-005 C
Solar/Wind Harmer
0.314
274801UNIV PARK;4U
Adder
2.578
940581AE2-045 GEN
Solar/Wind Harmer
4.504
276776AD2-060 GEN
Solar/Wind Harmer
0.187
971605AH1-302 GEN
Solar/Wind Harmer
3.851
972207SS24-0001
Solar/Wind Harmer
9.729
274773LINCOLN ;4U
Adder
2.736
274774LINCOLN ;5U
Adder
2.736
241847AF2-150_GEN
Solar/Wind Harmer
1.821
274676JOLIET 29;8U
Adder
13.435
941551AE2-152 GEN
Solar/Wind Harmer
1.984
274732ELWOOD EC;7P
Adder
7.185
274674JOLIET 9 ;6U
Adder
6.73
970245AG2-165 GEN
Solar/Wind Harmer
7.784
274871GR RIDGE ;2U
Solar/Wind Harmer
3.343
274745AC1-111 GEN9
Adder
2.416
961971AG1-040 GEN
Solar/Wind Helper
0.333
203835AF1-098 GEN
Solar/Wind Helper
1.311
203860AG1-193 C
Solar/Wind Helper
0.149
241966AE1-183 GEN
Solar/Wind Helper
0.129
254303AC2-168 GEN
Solar/Wind Helper
0.075
939351AE1-166 GEN
Solar/Wind Harmer
2.594
276893AG1-478 C
Solar/Wind Harmer
0.183
274730ELWOOD EC;6P
Adder
7.185
274734ELWOOD EC;8P
Adder
7.185
274736ELWOOD EC;9P
Adder
7.185
970707AG2-453 GEN
Solar/Wind Harmer
12.238
274729ELWOOD EC;1P
Adder
7.185
970513AG2-328 GEN
Solar/Wind Harmer
7.784
970517AG2-330 GEN
Solar/Wind Harmer
7.06
971617AH1-308 GEN
Solar/Wind Harmer
2.534
962511AG1-100 GEN
Solar/Wind Helper
0.34
203830AF1-094 GEN
Solar/Wind Helper
0.322
959441AF2-235 GEN
Solar/Wind Helper
0.146
254305AE2-115 C
Solar/Wind Helper
0.112
20334926Z1-069 C
Solar/Wind Helper
0.641
943121AE2-341 GEN
Solar/Wind Harmer
2.014
943591AF1-030 GEN
Solar/Wind Harmer
1.343
962101AG1-054 GEN
Solar/Wind Helper
0.325
946381AF1-302 GEN
Solar/Wind Helper
0.105
238217AF1-153 C O1
Solar/Wind Helper
0.111
991177J1571 G
External Queue
14.786787033081055
990527J1329
External Queue
1.7522491216659546
990142J1224
External Queue
12.808939933776855
991182J1586 G
External Queue
23.962841033935547
LAGNLTFEXP_LAGN->PJM
CLTF
4.78
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.107
TVALTFEXP_TVA->PJM
CLTF
2.169
CPLELTFEXP_CPLE->PJM
CLTF
0.311
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.23
NYPJM->LTFIMP_NY
CLTF
2.01
LGEELTFEXP_LGEE->PJM
CLTF
1.95
WECLTFEXP_WEC->PJM
CLTF
1.601
AG2-052LTFEXP_AG2-052->PJM
LTF
0.103
AH1-155LTFEXP_AH1-155->PJM
LTF
0.155
CBM West 1LTFEXP_CBM-W1->PJM
CBM
90.542
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.6
MECLTFEXP_MEC->PJM
CLTF
6.243
SIGELTFEXP_SIGE->PJM
CLTF
0.163

Details for AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line l/o ATSI_P2-3_OEC-345-1152-12_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_OEC-345-1152-12_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:145.45 %
Rating:1798.0 MVA
Rating Type:B
MVA to Mitigate:2615.26
MW Contribution:12.97
Bus #Bus NameTypeMW Contribution
23867002DVBSG1
50/50
14.146
972211AH1-690 GEN
50/50
289.964
23888502TROY G1
50/50
1.811
23888602TROY G2
50/50
1.811
241886AC2-103 GEN2
Solar/Wind Harmer
26.657
970817AG2-515 GEN
Solar/Wind Harmer
15.186
945411AF1-206 GEN
Solar/Wind Harmer
8.014
945641AF1-229 GEN
Solar/Wind Harmer
3.431
270499AE1-146 GEN
Solar/Wind Harmer
2.196
971549AH1-272 GEN
Solar/Wind Harmer
12.968
270297AD1-101 GEN
Solar/Wind Harmer
1.865
247607V1-011 GEN
Solar/Wind Harmer
2.296
957201AF2-014 GEN
Solar/Wind Harmer
2.627
270435AC2-044 GEN
Solar/Wind Harmer
1.158
944161AF1-084 GEN
Solar/Wind Harmer
1.278
966831AG1-554 GEN
Solar/Wind Harmer
0.671
971989AH1-539 GEN
Solar/Wind Harmer
7.259
965041AG1-368 GEN
Solar/Wind Harmer
5.434
965051AG1-369 GEN
Solar/Wind Harmer
2.696
971771AH1-392 GEN
Solar/Wind Harmer
4.755
270302AB2-170 GEN
Solar/Wind Harmer
4.326
270317AD1-130_GEN
Solar/Wind Harmer
1.658
971769AH1-391 GEN
Solar/Wind Harmer
5.15
971567AH1-282 GEN
Solar/Wind Harmer
7.434
960681AF2-359 GEN
Solar/Wind Harmer
1.871
971347AH1-153 GEN
Solar/Wind Harmer
7.391
963791AG1-232 GEN
Solar/Wind Harmer
6.533
270578AF1-285 GEN2
Solar/Wind Harmer
0.223
270536AF1-215 GEN2
Solar/Wind Harmer
2.12
270071AF1-092 GEN
Solar/Wind Harmer
6.896
274814UNIV PK N;0U
Adder
2.295
274807UNIV PK N;3U
Adder
2.29
274805UNIV PK N;1U
Adder
2.28
274811UNIV PK N;7U
Adder
2.275
958391AF2-133 GEN
Solar/Wind Harmer
4.12
972037AH1-567 GEN1
Adder
0.082
274827FISK ;RP
Adder
3.48
960591AF2-350 GEN
Solar/Wind Harmer
4.471
274775LINCOLN ;6U
Adder
2.77
24189902OREGON_CT2
50/50
2.688
23888702TROY G3
50/50
1.811
972253AH1-711 GEN
50/50
55.325
23856402BAYSG1
50/50
1.231
23920202STRYCT
50/50
1.893
241885AC2-103 GEN1
Solar/Wind Harmer
26.657
241858AF1-205_GEN
Solar/Wind Harmer
5.459
241808AF1-120 C
Solar/Wind Harmer
1.196
241840AF1-064_GEN
Solar/Wind Harmer
1.357
972301AH1-735 GEN
Adder
6.543
23906402RICHG1
Adder
1.309
23906502RICHG2&3
Adder
1.306
270361_3
Solar/Wind Harmer
7.852
960841AF2-375 GEN
Solar/Wind Harmer
3.479
970515AG2-329 GEN
Solar/Wind Harmer
10.037
247522W1-056 GEN
Solar/Wind Harmer
1.482
944231AF1-091 GEN
Solar/Wind Harmer
2.45
246936BC-WTG1
Solar/Wind Harmer
2.266
270489AE1-102 GEN1
Solar/Wind Harmer
0.753
965421AG1-410 GEN
Solar/Wind Harmer
17.213
270449AD2-020 GEN
Solar/Wind Harmer
1.599
943021AE2-325 GEN
Solar/Wind Harmer
2.077
24695305TIMB G C
Solar/Wind Harmer
3.074
945111AF1-176 GEN
Solar/Wind Harmer
9.954
270505AE1-170 C O1
Solar/Wind Harmer
8.362
24639705ELKHART HY
Adder
0.083
247521TR3_G114
Solar/Wind Harmer
1.816
270246TR4_N_V150
Solar/Wind Harmer
0.459
270063AE2-323 C
Solar/Wind Harmer
1.184
965011AG1-365 GEN
Solar/Wind Harmer
5.229
270462AD2-086
Solar/Wind Harmer
3.599
270223U2-072_GEN1
Solar/Wind Harmer
0.947
270578AF1-285 GEN2
Solar/Wind Harmer
0.579
270391AF1-285 GEN3
Solar/Wind Harmer
0.579
970373AG2-245 GEN
Solar/Wind Harmer
9.997
270055AF2-134 C O1
Solar/Wind Harmer
1.413
274751CRETE EC ;1U
Adder
2.249
274754CRETE EC ;4U
Adder
2.249
958381AF2-132 GEN
Solar/Wind Harmer
4.158
964861AG1-349 GEN
Solar/Wind Harmer
3.596
971917AH1-482 GEN
Solar/Wind Harmer
4.15
274723RIVER EC ;12
Adder
8.179
274812UNIV PK N;8U
Adder
2.275
276164X3-005 C
Solar/Wind Harmer
0.318
274801UNIV PARK;4U
Adder
2.611
276776AD2-060 GEN
Solar/Wind Harmer
0.189
940581AE2-045 GEN
Solar/Wind Harmer
4.559
972207SS24-0001
Solar/Wind Harmer
9.85
274773LINCOLN ;4U
Adder
2.77
274774LINCOLN ;5U
Adder
2.77
971605AH1-302 GEN
Solar/Wind Harmer
3.898
274676JOLIET 29;8U
Adder
13.602
941551AE2-152 GEN
Solar/Wind Harmer
2.009
274732ELWOOD EC;7P
Adder
7.275
274674JOLIET 9 ;6U
Adder
6.813
970245AG2-165 GEN
Solar/Wind Harmer
7.876
274871GR RIDGE ;2U
Solar/Wind Harmer
3.384
274745AC1-111 GEN9
Adder
2.446
276691AA1-018 GEN1
Solar/Wind Harmer
0.204
274682WAUKEGAN ;7U
Adder
7.809
274828WAUKEGAN ;BP
Adder
4.795
961971AG1-040 GEN
Solar/Wind Helper
0.329
203835AF1-098 GEN
Solar/Wind Helper
1.298
203860AG1-193 C
Solar/Wind Helper
0.147
241966AE1-183 GEN
Solar/Wind Helper
0.129
254303AC2-168 GEN
Solar/Wind Helper
0.075
274776LINCOLN ;7U
Adder
2.77
274777LINCOLN ;8U
Adder
2.77
972227AH1-698 GEN1
Adder
1.163
274687WILL CNTY;4U
Adder
12.414
274687WILL CNTY;4U
Adder
12.414
274675JOLIET 29;7U
Adder
13.602
274675JOLIET 29;7U
Adder
13.116
274728ELWOOD EC;5P
Adder
7.275
274731ELWOOD EC;2P
Adder
7.274
274733ELWOOD EC;3P
Adder
7.274
274735ELWOOD EC;4P
Adder
7.274
970833AG2-524 GEN
Solar/Wind Harmer
3.844
970833AG2-524 GEN
Solar/Wind Harmer
1.788
274746AC1-111 G10
Adder
2.446
274744AC1-111 GEN8
Adder
2.446
270024AE2-089 GEN
Solar/Wind Harmer
2.053
241982AE2-343 S C
Solar/Wind Helper
0.117
254304AE2-114 C
Solar/Wind Helper
0.111
203846AF2-130 C
Solar/Wind Helper
0.244
241997AF1-093 GEN
Solar/Wind Helper
0.129
203804AE2-113_GEN
Solar/Wind Helper
0.854
24190002OREGON_ST1
50/50
3.617
24189802OREGON_CT1
50/50
2.744
23888802TROY G4
50/50
1.811
241996AE2-282_GEN
Solar/Wind Harmer
2.146
971677AH1-339 GEN
Solar/Wind Harmer
6.235
270007AE1-245 C
Solar/Wind Harmer
3.444
246938BC-WTG3
Solar/Wind Harmer
2.305
246937BC-WTG2
Solar/Wind Harmer
2.266
942801AE2-298 GEN
Solar/Wind Harmer
0.872
961051AF2-396 GEN
Solar/Wind Harmer
8.981
961051AF2-396 GEN
Solar/Wind Harmer
4.177
960981AF2-389 GEN
Solar/Wind Harmer
0.84
957891AF2-083 GEN
Solar/Wind Harmer
1.874
247620Y3-023
Adder
0.25
270216AD2-079_GEN
Solar/Wind Harmer
0.325
970611AG2-400 GEN
Solar/Wind Harmer
5.229
270526AF1-158 GEN
Solar/Wind Harmer
2.352
24441505OLIV SLR
Solar/Wind Harmer
0.069
965681AG1-436 GEN
Solar/Wind Harmer
6.19
965791AG1-447 GEN
Solar/Wind Harmer
3.167
270224U2-072_GEN2
Solar/Wind Harmer
0.947
270227U2-072_GEN3
Solar/Wind Harmer
0.947
270228U2-072_GEN4
Solar/Wind Harmer
0.947
270231U2-072_GEN5
Solar/Wind Harmer
0.947
274808UNIV PK N;4U
Adder
2.265
274803UNIV PARK;6U
Adder
2.619
274888KELLY CRK;1U
Solar/Wind Harmer
2.639
274887GEN-1.85
Solar/Wind Harmer
2.383
276843GEN-1.7
Solar/Wind Harmer
0.256
958011AF2-095 GEN
Solar/Wind Harmer
6.438
274770LINCOLN ;1U
Adder
2.77
274771LINCOLN ;2U
Adder
2.77
972259AH1-714 GEN
Adder
8.465
942221AE2-234 GEN
Solar/Wind Harmer
0.325
274674JOLIET 9 ;6U
Adder
6.813
970321AG2-212 GEN
Solar/Wind Harmer
7.876
274847GR RIDGE ;BU
Solar/Wind Harmer
2.226
274695ROCKY RD ;2P
Adder
4.836
274693ROCKY RD ;1P
Adder
4.789
274697ROCKY RD ;3P
Adder
1.314
274696ROCKY RD ;4P
Adder
4.95
274683WAUKEGAN ;8U
Adder
9.148
274683WAUKEGAN ;8U
Adder
7.711
203947AF1-006 C
Solar/Wind Helper
0.375
203980AG1-197 GEN
Solar/Wind Helper
0.245
203979AG1-198 GEN
Solar/Wind Helper
0.191
241967AE2-285_GEN
Solar/Wind Helper
0.335
241801AE1-079 GEN
Solar/Wind Helper
0.13
241985AE1-237 GEN
Solar/Wind Helper
0.13
962101AG1-054 GEN
Solar/Wind Helper
0.323
946381AF1-302 GEN
Solar/Wind Helper
0.104
958481AF2-142 GEN
Solar/Wind Harmer
1.857
23929302BS-PKR
50/50
2.166
241832AE2-181_GEN
Solar/Wind Harmer
1.946
958321AF2-126 GEN
Solar/Wind Harmer
1.455
23906502RICHG2&3
Adder
1.306
270541AE2-072 C
Solar/Wind Harmer
4.224
270575GUS2 35KV
Solar/Wind Harmer
9.25
970217AG2-149 GEN
Solar/Wind Harmer
22.132
270044AE2-322 C
Solar/Wind Harmer
0.845
270404AC1-167 GEN
Solar/Wind Harmer
0.704
270258AD1-119 GEN
Solar/Wind Harmer
1.722
247604X1-042
Adder
0.255
24441205WTRV SLR C
Solar/Wind Harmer
0.081
270588AE1-091_GEN
Solar/Wind Harmer
6.538
958091AF2-103 GEN
Solar/Wind Harmer
0.094
270491AE1-102 GEN2
Solar/Wind Harmer
0.753
945111AF1-176 GEN
Solar/Wind Harmer
3.155
24642205MAYFLWER
Adder
0.345
270191TR4_S_V150
Solar/Wind Harmer
1.62
270247TR4_N_V136
Solar/Wind Harmer
0.459
970031AG2-029 GEN
Solar/Wind Harmer
16.085
247643Z2-116 C
Solar/Wind Harmer
0.037
959331AF2-224 GEN
Solar/Wind Harmer
5.229
965021AG1-366 GEN
Solar/Wind Harmer
1.216
270485AE1-090_GEN
Solar/Wind Harmer
0.313
270043AE2-236 GEN
Solar/Wind Harmer
2.722
970349AG2-230 GEN
Solar/Wind Harmer
7.391
942871AE2-306 GEN
Solar/Wind Harmer
0.434
270391AF1-285 GEN3
Solar/Wind Harmer
0.223
270535AF1-215 GEN1
Solar/Wind Harmer
2.12
972231SS25-0005
Solar/Wind Harmer
4.366
972181SS23-001
Solar/Wind Harmer
2.729
274752CRETE EC ;2U
Adder
2.249
274753CRETE EC ;3U
Adder
2.249
964401AG1-302 GEN
Solar/Wind Harmer
4.158
274724RIVER EC ;11
Adder
8.081
959141AF2-205 GEN
Solar/Wind Harmer
2.726
274802UNIV PARK;5U
Adder
2.619
274826FISK ;BP
Adder
4.91
274800UNIV PARK;3U
Adder
2.611
972038AH1-567 GEN2
Adder
0.163
276772AC2-154 GEN
Solar/Wind Harmer
1.247
276806AD2-047 C O1
Solar/Wind Harmer
4.783
970941AG2-585 GEN
Solar/Wind Harmer
5.588
274772LINCOLN ;3U
Adder
2.77
972228AH1-698 GEN2
Adder
1.651
274676JOLIET 29;8U
Adder
13.116
276897AD1-100 C
Solar/Wind Harmer
12.852
939351AE1-166 GEN
Solar/Wind Harmer
2.626
276893AG1-478 C
Solar/Wind Harmer
0.185
274730ELWOOD EC;6P
Adder
7.275
274734ELWOOD EC;8P
Adder
7.275
274736ELWOOD EC;9P
Adder
7.275
970707AG2-453 GEN
Solar/Wind Harmer
12.39
274729ELWOOD EC;1P
Adder
7.274
970513AG2-328 GEN
Solar/Wind Harmer
7.876
970517AG2-330 GEN
Solar/Wind Harmer
7.143
971617AH1-308 GEN
Solar/Wind Harmer
2.543
943121AE2-341 GEN
Solar/Wind Harmer
6.56
943591AF1-030 GEN
Solar/Wind Harmer
4.374
276694AA1-018 GEN2
Solar/Wind Harmer
2.759
274682WAUKEGAN ;7U
Adder
7.809
962511AG1-100 GEN
Solar/Wind Helper
0.337
203830AF1-094 GEN
Solar/Wind Helper
0.319
959441AF2-235 GEN
Solar/Wind Helper
0.145
254305AE2-115 C
Solar/Wind Helper
0.111
20334926Z1-069 C
Solar/Wind Helper
0.636
991177J1571 G
External Queue
15.212156295776367
990527J1329
External Queue
1.8186211585998535
990142J1224
External Queue
13.294119834899902
991182J1586 G
External Queue
24.90056610107422
LAGNLTFEXP_LAGN->PJM
CLTF
4.814
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.113
TVALTFEXP_TVA->PJM
CLTF
2.181
CPLELTFEXP_CPLE->PJM
CLTF
0.312
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.518
NYPJM->LTFIMP_NY
CLTF
1.998
LGEELTFEXP_LGEE->PJM
CLTF
1.955
WECLTFEXP_WEC->PJM
CLTF
1.62
AG2-052LTFEXP_AG2-052->PJM
LTF
0.104
AH1-155LTFEXP_AH1-155->PJM
LTF
0.157
CBM West 1LTFEXP_CBM-W1->PJM
CBM
92.632
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.641
MECLTFEXP_MEC->PJM
CLTF
6.31
SIGELTFEXP_SIGE->PJM
CLTF
0.163

Details for AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line l/o ATSI_P2-3_OEC-345-1152-F1_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_OEC-345-1152-F1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:145.45 %
Rating:1798.0 MVA
Rating Type:B
MVA to Mitigate:2615.26
MW Contribution:12.97
Bus #Bus NameTypeMW Contribution
24189902OREGON_CT2
50/50
2.688
23888702TROY G3
50/50
1.811
972253AH1-711 GEN
50/50
55.325
23856402BAYSG1
50/50
1.231
23920202STRYCT
50/50
1.893
241885AC2-103 GEN1
Solar/Wind Harmer
26.657
241858AF1-205_GEN
Solar/Wind Harmer
5.459
241808AF1-120 C
Solar/Wind Harmer
1.196
241840AF1-064_GEN
Solar/Wind Harmer
1.357
972301AH1-735 GEN
Adder
6.543
23906402RICHG1
Adder
1.309
23906502RICHG2&3
Adder
1.306
270361_3
Solar/Wind Harmer
7.852
960841AF2-375 GEN
Solar/Wind Harmer
3.479
970515AG2-329 GEN
Solar/Wind Harmer
10.037
247522W1-056 GEN
Solar/Wind Harmer
1.482
944231AF1-091 GEN
Solar/Wind Harmer
2.45
246936BC-WTG1
Solar/Wind Harmer
2.266
270489AE1-102 GEN1
Solar/Wind Harmer
0.753
965421AG1-410 GEN
Solar/Wind Harmer
17.213
270449AD2-020 GEN
Solar/Wind Harmer
1.599
23867002DVBSG1
50/50
14.146
972211AH1-690 GEN
50/50
289.964
23888502TROY G1
50/50
1.811
23888602TROY G2
50/50
1.811
241886AC2-103 GEN2
Solar/Wind Harmer
26.657
970817AG2-515 GEN
Solar/Wind Harmer
15.186
945411AF1-206 GEN
Solar/Wind Harmer
8.014
945641AF1-229 GEN
Solar/Wind Harmer
3.431
270499AE1-146 GEN
Solar/Wind Harmer
2.196
971549AH1-272 GEN
Solar/Wind Harmer
12.968
270297AD1-101 GEN
Solar/Wind Harmer
1.865
247607V1-011 GEN
Solar/Wind Harmer
2.296
957201AF2-014 GEN
Solar/Wind Harmer
2.627
270435AC2-044 GEN
Solar/Wind Harmer
1.158
944161AF1-084 GEN
Solar/Wind Harmer
1.278
966831AG1-554 GEN
Solar/Wind Harmer
0.671
971989AH1-539 GEN
Solar/Wind Harmer
7.259
965041AG1-368 GEN
Solar/Wind Harmer
5.434
965051AG1-369 GEN
Solar/Wind Harmer
2.696
971771AH1-392 GEN
Solar/Wind Harmer
4.755
270302AB2-170 GEN
Solar/Wind Harmer
4.326
270317AD1-130_GEN
Solar/Wind Harmer
1.658
971769AH1-391 GEN
Solar/Wind Harmer
5.15
971567AH1-282 GEN
Solar/Wind Harmer
7.434
960681AF2-359 GEN
Solar/Wind Harmer
1.871
971347AH1-153 GEN
Solar/Wind Harmer
7.391
963791AG1-232 GEN
Solar/Wind Harmer
6.533
270578AF1-285 GEN2
Solar/Wind Harmer
0.223
270536AF1-215 GEN2
Solar/Wind Harmer
2.12
270071AF1-092 GEN
Solar/Wind Harmer
6.896
274814UNIV PK N;0U
Adder
2.295
274807UNIV PK N;3U
Adder
2.29
274805UNIV PK N;1U
Adder
2.28
274811UNIV PK N;7U
Adder
2.275
958391AF2-133 GEN
Solar/Wind Harmer
4.12
972037AH1-567 GEN1
Adder
0.082
274827FISK ;RP
Adder
3.48
960591AF2-350 GEN
Solar/Wind Harmer
4.471
274775LINCOLN ;6U
Adder
2.77
274776LINCOLN ;7U
Adder
2.77
274777LINCOLN ;8U
Adder
2.77
972227AH1-698 GEN1
Adder
1.163
274687WILL CNTY;4U
Adder
12.414
274687WILL CNTY;4U
Adder
12.414
274675JOLIET 29;7U
Adder
13.602
274675JOLIET 29;7U
Adder
13.116
274728ELWOOD EC;5P
Adder
7.275
274731ELWOOD EC;2P
Adder
7.274
274733ELWOOD EC;3P
Adder
7.274
274735ELWOOD EC;4P
Adder
7.274
970833AG2-524 GEN
Solar/Wind Harmer
3.844
970833AG2-524 GEN
Solar/Wind Harmer
1.788
274746AC1-111 G10
Adder
2.446
274744AC1-111 GEN8
Adder
2.446
270024AE2-089 GEN
Solar/Wind Harmer
2.053
241982AE2-343 S C
Solar/Wind Helper
0.117
254304AE2-114 C
Solar/Wind Helper
0.111
203846AF2-130 C
Solar/Wind Helper
0.244
241997AF1-093 GEN
Solar/Wind Helper
0.129
203804AE2-113_GEN
Solar/Wind Helper
0.854
943021AE2-325 GEN
Solar/Wind Harmer
2.077
24695305TIMB G C
Solar/Wind Harmer
3.074
945111AF1-176 GEN
Solar/Wind Harmer
9.954
270505AE1-170 C O1
Solar/Wind Harmer
8.362
24639705ELKHART HY
Adder
0.083
247521TR3_G114
Solar/Wind Harmer
1.816
270246TR4_N_V150
Solar/Wind Harmer
0.459
270063AE2-323 C
Solar/Wind Harmer
1.184
965011AG1-365 GEN
Solar/Wind Harmer
5.229
270462AD2-086
Solar/Wind Harmer
3.599
270223U2-072_GEN1
Solar/Wind Harmer
0.947
270578AF1-285 GEN2
Solar/Wind Harmer
0.579
270391AF1-285 GEN3
Solar/Wind Harmer
0.579
970373AG2-245 GEN
Solar/Wind Harmer
9.997
270055AF2-134 C O1
Solar/Wind Harmer
1.413
274751CRETE EC ;1U
Adder
2.249
274754CRETE EC ;4U
Adder
2.249
958381AF2-132 GEN
Solar/Wind Harmer
4.158
964861AG1-349 GEN
Solar/Wind Harmer
3.596
971917AH1-482 GEN
Solar/Wind Harmer
4.15
274723RIVER EC ;12
Adder
8.179
274812UNIV PK N;8U
Adder
2.275
276164X3-005 C
Solar/Wind Harmer
0.318
274801UNIV PARK;4U
Adder
2.611
276776AD2-060 GEN
Solar/Wind Harmer
0.189
940581AE2-045 GEN
Solar/Wind Harmer
4.559
972207SS24-0001
Solar/Wind Harmer
9.85
274773LINCOLN ;4U
Adder
2.77
274774LINCOLN ;5U
Adder
2.77
971605AH1-302 GEN
Solar/Wind Harmer
3.898
274676JOLIET 29;8U
Adder
13.602
941551AE2-152 GEN
Solar/Wind Harmer
2.009
274732ELWOOD EC;7P
Adder
7.275
274674JOLIET 9 ;6U
Adder
6.813
970245AG2-165 GEN
Solar/Wind Harmer
7.876
274871GR RIDGE ;2U
Solar/Wind Harmer
3.384
274745AC1-111 GEN9
Adder
2.446
276691AA1-018 GEN1
Solar/Wind Harmer
0.204
274682WAUKEGAN ;7U
Adder
7.809
274828WAUKEGAN ;BP
Adder
4.795
961971AG1-040 GEN
Solar/Wind Helper
0.329
203835AF1-098 GEN
Solar/Wind Helper
1.298
203860AG1-193 C
Solar/Wind Helper
0.147
241966AE1-183 GEN
Solar/Wind Helper
0.129
254303AC2-168 GEN
Solar/Wind Helper
0.075
23929302BS-PKR
50/50
2.166
241832AE2-181_GEN
Solar/Wind Harmer
1.946
958321AF2-126 GEN
Solar/Wind Harmer
1.455
23906502RICHG2&3
Adder
1.306
270541AE2-072 C
Solar/Wind Harmer
4.224
270575GUS2 35KV
Solar/Wind Harmer
9.25
970217AG2-149 GEN
Solar/Wind Harmer
22.132
270044AE2-322 C
Solar/Wind Harmer
0.845
270404AC1-167 GEN
Solar/Wind Harmer
0.704
270258AD1-119 GEN
Solar/Wind Harmer
1.722
247604X1-042
Adder
0.255
24441205WTRV SLR C
Solar/Wind Harmer
0.081
270588AE1-091_GEN
Solar/Wind Harmer
6.538
958091AF2-103 GEN
Solar/Wind Harmer
0.094
270491AE1-102 GEN2
Solar/Wind Harmer
0.753
945111AF1-176 GEN
Solar/Wind Harmer
3.155
24642205MAYFLWER
Adder
0.345
270191TR4_S_V150
Solar/Wind Harmer
1.62
270247TR4_N_V136
Solar/Wind Harmer
0.459
970031AG2-029 GEN
Solar/Wind Harmer
16.085
247643Z2-116 C
Solar/Wind Harmer
0.037
959331AF2-224 GEN
Solar/Wind Harmer
5.229
965021AG1-366 GEN
Solar/Wind Harmer
1.216
270485AE1-090_GEN
Solar/Wind Harmer
0.313
270043AE2-236 GEN
Solar/Wind Harmer
2.722
970349AG2-230 GEN
Solar/Wind Harmer
7.391
942871AE2-306 GEN
Solar/Wind Harmer
0.434
270391AF1-285 GEN3
Solar/Wind Harmer
0.223
24190002OREGON_ST1
50/50
3.617
24189802OREGON_CT1
50/50
2.744
23888802TROY G4
50/50
1.811
241996AE2-282_GEN
Solar/Wind Harmer
2.146
971677AH1-339 GEN
Solar/Wind Harmer
6.235
270007AE1-245 C
Solar/Wind Harmer
3.444
246938BC-WTG3
Solar/Wind Harmer
2.305
246937BC-WTG2
Solar/Wind Harmer
2.266
942801AE2-298 GEN
Solar/Wind Harmer
0.872
961051AF2-396 GEN
Solar/Wind Harmer
8.981
961051AF2-396 GEN
Solar/Wind Harmer
4.177
960981AF2-389 GEN
Solar/Wind Harmer
0.84
957891AF2-083 GEN
Solar/Wind Harmer
1.874
247620Y3-023
Adder
0.25
270216AD2-079_GEN
Solar/Wind Harmer
0.325
970611AG2-400 GEN
Solar/Wind Harmer
5.229
270526AF1-158 GEN
Solar/Wind Harmer
2.352
24441505OLIV SLR
Solar/Wind Harmer
0.069
965681AG1-436 GEN
Solar/Wind Harmer
6.19
965791AG1-447 GEN
Solar/Wind Harmer
3.167
270224U2-072_GEN2
Solar/Wind Harmer
0.947
270227U2-072_GEN3
Solar/Wind Harmer
0.947
270228U2-072_GEN4
Solar/Wind Harmer
0.947
270231U2-072_GEN5
Solar/Wind Harmer
0.947
274808UNIV PK N;4U
Adder
2.265
274803UNIV PARK;6U
Adder
2.619
274888KELLY CRK;1U
Solar/Wind Harmer
2.639
274887GEN-1.85
Solar/Wind Harmer
2.383
276843GEN-1.7
Solar/Wind Harmer
0.256
958011AF2-095 GEN
Solar/Wind Harmer
6.438
274770LINCOLN ;1U
Adder
2.77
274771LINCOLN ;2U
Adder
2.77
972259AH1-714 GEN
Adder
8.465
942221AE2-234 GEN
Solar/Wind Harmer
0.325
274674JOLIET 9 ;6U
Adder
6.813
970321AG2-212 GEN
Solar/Wind Harmer
7.876
274847GR RIDGE ;BU
Solar/Wind Harmer
2.226
274695ROCKY RD ;2P
Adder
4.836
274693ROCKY RD ;1P
Adder
4.789
274697ROCKY RD ;3P
Adder
1.314
274696ROCKY RD ;4P
Adder
4.95
274683WAUKEGAN ;8U
Adder
9.148
274683WAUKEGAN ;8U
Adder
7.711
203947AF1-006 C
Solar/Wind Helper
0.375
203980AG1-197 GEN
Solar/Wind Helper
0.245
203979AG1-198 GEN
Solar/Wind Helper
0.191
241967AE2-285_GEN
Solar/Wind Helper
0.335
241801AE1-079 GEN
Solar/Wind Helper
0.13
241985AE1-237 GEN
Solar/Wind Helper
0.13
962101AG1-054 GEN
Solar/Wind Helper
0.323
946381AF1-302 GEN
Solar/Wind Helper
0.104
958481AF2-142 GEN
Solar/Wind Harmer
1.857
270535AF1-215 GEN1
Solar/Wind Harmer
2.12
972231SS25-0005
Solar/Wind Harmer
4.366
972181SS23-001
Solar/Wind Harmer
2.729
274752CRETE EC ;2U
Adder
2.249
274753CRETE EC ;3U
Adder
2.249
964401AG1-302 GEN
Solar/Wind Harmer
4.158
274724RIVER EC ;11
Adder
8.081
959141AF2-205 GEN
Solar/Wind Harmer
2.726
274802UNIV PARK;5U
Adder
2.619
274826FISK ;BP
Adder
4.91
274800UNIV PARK;3U
Adder
2.611
972038AH1-567 GEN2
Adder
0.163
276772AC2-154 GEN
Solar/Wind Harmer
1.247
276806AD2-047 C O1
Solar/Wind Harmer
4.783
970941AG2-585 GEN
Solar/Wind Harmer
5.588
274772LINCOLN ;3U
Adder
2.77
972228AH1-698 GEN2
Adder
1.651
274676JOLIET 29;8U
Adder
13.116
276897AD1-100 C
Solar/Wind Harmer
12.852
939351AE1-166 GEN
Solar/Wind Harmer
2.626
276893AG1-478 C
Solar/Wind Harmer
0.185
274730ELWOOD EC;6P
Adder
7.275
274734ELWOOD EC;8P
Adder
7.275
274736ELWOOD EC;9P
Adder
7.275
970707AG2-453 GEN
Solar/Wind Harmer
12.39
274729ELWOOD EC;1P
Adder
7.274
970513AG2-328 GEN
Solar/Wind Harmer
7.876
970517AG2-330 GEN
Solar/Wind Harmer
7.143
971617AH1-308 GEN
Solar/Wind Harmer
2.543
943121AE2-341 GEN
Solar/Wind Harmer
6.56
943591AF1-030 GEN
Solar/Wind Harmer
4.374
276694AA1-018 GEN2
Solar/Wind Harmer
2.759
274682WAUKEGAN ;7U
Adder
7.809
962511AG1-100 GEN
Solar/Wind Helper
0.337
203830AF1-094 GEN
Solar/Wind Helper
0.319
959441AF2-235 GEN
Solar/Wind Helper
0.145
254305AE2-115 C
Solar/Wind Helper
0.111
20334926Z1-069 C
Solar/Wind Helper
0.636
991177J1571 G
External Queue
15.212156295776367
990527J1329
External Queue
1.8186211585998535
990142J1224
External Queue
13.294119834899902
991182J1586 G
External Queue
24.90056610107422
LAGNLTFEXP_LAGN->PJM
CLTF
4.814
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.113
TVALTFEXP_TVA->PJM
CLTF
2.181
CPLELTFEXP_CPLE->PJM
CLTF
0.312
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.518
NYPJM->LTFIMP_NY
CLTF
1.998
LGEELTFEXP_LGEE->PJM
CLTF
1.955
WECLTFEXP_WEC->PJM
CLTF
1.62
AG2-052LTFEXP_AG2-052->PJM
LTF
0.104
AH1-155LTFEXP_AH1-155->PJM
LTF
0.157
CBM West 1LTFEXP_CBM-W1->PJM
CBM
92.632
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.641
MECLTFEXP_MEC->PJM
CLTF
6.31
SIGELTFEXP_SIGE->PJM
CLTF
0.163

Details for AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line l/o ATSI_P2-3_OEC-345-1152-3_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_OEC-345-1152-3_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:142.16 %
Rating:1798.0 MVA
Rating Type:B
MVA to Mitigate:2556.01
MW Contribution:12.79
Bus #Bus NameTypeMW Contribution
24189902OREGON_CT2
50/50
2.596
23888702TROY G3
50/50
1.764
24190002OREGON_ST1
50/50
3.493
24189802OREGON_CT1
50/50
2.65
23888802TROY G4
50/50
1.764
241996AE2-282_GEN
Solar/Wind Harmer
2.159
971677AH1-339 GEN
Solar/Wind Harmer
6.666
270007AE1-245 C
Solar/Wind Harmer
3.473
942801AE2-298 GEN
Solar/Wind Harmer
0.88
246938BC-WTG3
Solar/Wind Harmer
2.311
246937BC-WTG2
Solar/Wind Harmer
2.271
961051AF2-396 GEN
Solar/Wind Harmer
8.895
961051AF2-396 GEN
Solar/Wind Harmer
4.137
960981AF2-389 GEN
Solar/Wind Harmer
0.832
957891AF2-083 GEN
Solar/Wind Harmer
1.857
247620Y3-023
Adder
0.249
270216AD2-079_GEN
Solar/Wind Harmer
0.322
970611AG2-400 GEN
Solar/Wind Harmer
5.223
270526AF1-158 GEN
Solar/Wind Harmer
2.332
24441505OLIV SLR
Solar/Wind Harmer
0.068
965681AG1-436 GEN
Solar/Wind Harmer
6.141
965791AG1-447 GEN
Solar/Wind Harmer
3.142
270224U2-072_GEN2
Solar/Wind Harmer
0.954
270227U2-072_GEN3
Solar/Wind Harmer
0.954
270228U2-072_GEN4
Solar/Wind Harmer
0.954
270231U2-072_GEN5
Solar/Wind Harmer
0.954
971231AH1-075 GEN
Solar/Wind Harmer
0.372
274808UNIV PK N;4U
Adder
2.25
274803UNIV PARK;6U
Adder
2.602
274888KELLY CRK;1U
Solar/Wind Harmer
2.622
274887GEN-1.85
Solar/Wind Harmer
2.367
276843GEN-1.7
Solar/Wind Harmer
0.255
958011AF2-095 GEN
Solar/Wind Harmer
6.395
274770LINCOLN ;1U
Adder
2.752
274771LINCOLN ;2U
Adder
2.752
942221AE2-234 GEN
Solar/Wind Harmer
0.324
972259AH1-714 GEN
Adder
8.409
274674JOLIET 9 ;6U
Adder
6.769
970321AG2-212 GEN
Solar/Wind Harmer
7.828
274847GR RIDGE ;BU
Solar/Wind Harmer
2.211
274696ROCKY RD ;4P
Adder
4.919
274695ROCKY RD ;2P
Adder
4.805
274693ROCKY RD ;1P
Adder
4.758
274697ROCKY RD ;3P
Adder
1.305
274683WAUKEGAN ;8U
Adder
9.089
274683WAUKEGAN ;8U
Adder
7.662
203947AF1-006 C
Solar/Wind Helper
0.379
23867002DVBSG1
50/50
13.062
972211AH1-690 GEN
50/50
279.989
23888502TROY G1
50/50
1.764
23888602TROY G2
50/50
1.764
241886AC2-103 GEN2
Solar/Wind Harmer
25.888
970817AG2-515 GEN
Solar/Wind Harmer
14.956
945411AF1-206 GEN
Solar/Wind Harmer
8.063
945641AF1-229 GEN
Solar/Wind Harmer
3.434
270499AE1-146 GEN
Solar/Wind Harmer
2.36
971549AH1-272 GEN
Solar/Wind Harmer
12.795
270297AD1-101 GEN
Solar/Wind Harmer
1.901
966831AG1-554 GEN
Solar/Wind Harmer
0.706
971989AH1-539 GEN
Solar/Wind Harmer
7.631
247607V1-011 GEN
Solar/Wind Harmer
2.315
957201AF2-014 GEN
Solar/Wind Harmer
2.633
270435AC2-044 GEN
Solar/Wind Harmer
1.161
944161AF1-084 GEN
Solar/Wind Harmer
1.265
965041AG1-368 GEN
Solar/Wind Harmer
5.449
965051AG1-369 GEN
Solar/Wind Harmer
2.706
971771AH1-392 GEN
Solar/Wind Harmer
4.715
270302AB2-170 GEN
Solar/Wind Harmer
4.356
270317AD1-130_GEN
Solar/Wind Harmer
1.67
971769AH1-391 GEN
Solar/Wind Harmer
5.107
971567AH1-282 GEN
Solar/Wind Harmer
7.577
960681AF2-359 GEN
Solar/Wind Harmer
1.856
971347AH1-153 GEN
Solar/Wind Harmer
7.336
963791AG1-232 GEN
Solar/Wind Harmer
6.532
270578AF1-285 GEN2
Solar/Wind Harmer
0.224
270536AF1-215 GEN2
Solar/Wind Harmer
2.105
270071AF1-092 GEN
Solar/Wind Harmer
6.875
274814UNIV PK N;0U
Adder
2.28
274807UNIV PK N;3U
Adder
2.275
274805UNIV PK N;1U
Adder
2.265
274811UNIV PK N;7U
Adder
2.26
958391AF2-133 GEN
Solar/Wind Harmer
4.092
972037AH1-567 GEN1
Adder
0.082
274827FISK ;RP
Adder
3.457
960591AF2-350 GEN
Solar/Wind Harmer
4.441
274775LINCOLN ;6U
Adder
2.752
274776LINCOLN ;7U
Adder
2.752
274777LINCOLN ;8U
Adder
2.752
972227AH1-698 GEN1
Adder
1.155
274687WILL CNTY;4U
Adder
12.332
274687WILL CNTY;4U
Adder
12.332
274675JOLIET 29;7U
Adder
13.513
274675JOLIET 29;7U
Adder
13.03
274731ELWOOD EC;2P
Adder
7.227
274733ELWOOD EC;3P
Adder
7.227
274735ELWOOD EC;4P
Adder
7.227
274728ELWOOD EC;5P
Adder
7.227
270024AE2-089 GEN
Solar/Wind Harmer
2.053
970833AG2-524 GEN
Solar/Wind Harmer
3.819
970833AG2-524 GEN
Solar/Wind Harmer
1.776
274746AC1-111 G10
Adder
2.43
274744AC1-111 GEN8
Adder
2.43
241982AE2-343 S C
Solar/Wind Helper
0.117
254304AE2-114 C
Solar/Wind Helper
0.112
203846AF2-130 C
Solar/Wind Helper
0.247
241997AF1-093 GEN
Solar/Wind Helper
0.13
203804AE2-113_GEN
Solar/Wind Helper
0.862
203980AG1-197 GEN
Solar/Wind Helper
0.248
203979AG1-198 GEN
Solar/Wind Helper
0.193
241967AE2-285_GEN
Solar/Wind Helper
0.337
241801AE1-079 GEN
Solar/Wind Helper
0.131
241985AE1-237 GEN
Solar/Wind Helper
0.131
962101AG1-054 GEN
Solar/Wind Helper
0.326
946381AF1-302 GEN
Solar/Wind Helper
0.105
238217AF1-153 C O1
Solar/Wind Helper
0.111
23929302BS-PKR
50/50
2.264
241832AE2-181_GEN
Solar/Wind Harmer
1.957
958321AF2-126 GEN
Solar/Wind Harmer
1.492
23906502RICHG2&3
Adder
1.318
270575GUS2 35KV
Solar/Wind Harmer
10.016
270541AE2-072 C
Solar/Wind Harmer
4.321
970217AG2-149 GEN
Solar/Wind Harmer
22.356
270044AE2-322 C
Solar/Wind Harmer
0.852
270404AC1-167 GEN
Solar/Wind Harmer
0.709
270258AD1-119 GEN
Solar/Wind Harmer
1.735
270588AE1-091_GEN
Solar/Wind Harmer
6.791
247604X1-042
Adder
0.252
24441205WTRV SLR C
Solar/Wind Harmer
0.08
958091AF2-103 GEN
Solar/Wind Harmer
0.095
270491AE1-102 GEN2
Solar/Wind Harmer
0.755
945111AF1-176 GEN
Solar/Wind Harmer
3.126
270191TR4_S_V150
Solar/Wind Harmer
1.626
270247TR4_N_V136
Solar/Wind Harmer
0.461
24642205MAYFLWER
Adder
0.342
970031AG2-029 GEN
Solar/Wind Harmer
15.991
247643Z2-116 C
Solar/Wind Harmer
0.037
959331AF2-224 GEN
Solar/Wind Harmer
5.223
965021AG1-366 GEN
Solar/Wind Harmer
1.215
270485AE1-090_GEN
Solar/Wind Harmer
0.315
270043AE2-236 GEN
Solar/Wind Harmer
2.712
970349AG2-230 GEN
Solar/Wind Harmer
7.336
942871AE2-306 GEN
Solar/Wind Harmer
0.438
270391AF1-285 GEN3
Solar/Wind Harmer
0.224
270377AD1-106 GEN
Solar/Wind Harmer
2.871
270535AF1-215 GEN1
Solar/Wind Harmer
2.105
972231SS25-0005
Solar/Wind Harmer
4.336
972181SS23-001
Solar/Wind Harmer
2.71
274752CRETE EC ;2U
Adder
2.233
274753CRETE EC ;3U
Adder
2.233
964401AG1-302 GEN
Solar/Wind Harmer
4.13
274724RIVER EC ;11
Adder
8.026
959141AF2-205 GEN
Solar/Wind Harmer
2.708
274802UNIV PARK;5U
Adder
2.602
274826FISK ;BP
Adder
4.877
274800UNIV PARK;3U
Adder
2.593
972038AH1-567 GEN2
Adder
0.162
276772AC2-154 GEN
Solar/Wind Harmer
1.239
276806AD2-047 C O1
Solar/Wind Harmer
4.751
970941AG2-585 GEN
Solar/Wind Harmer
5.551
274772LINCOLN ;3U
Adder
2.752
972228AH1-698 GEN2
Adder
1.64
274676JOLIET 29;8U
Adder
13.03
276897AD1-100 C
Solar/Wind Harmer
12.768
939351AE1-166 GEN
Solar/Wind Harmer
2.609
276893AG1-478 C
Solar/Wind Harmer
0.184
274729ELWOOD EC;1P
Adder
7.227
274730ELWOOD EC;6P
Adder
7.227
274734ELWOOD EC;8P
Adder
7.227
274736ELWOOD EC;9P
Adder
7.227
970707AG2-453 GEN
Solar/Wind Harmer
12.309
970513AG2-328 GEN
Solar/Wind Harmer
7.828
970517AG2-330 GEN
Solar/Wind Harmer
7.1
971617AH1-308 GEN
Solar/Wind Harmer
2.543
274682WAUKEGAN ;7U
Adder
7.759
962511AG1-100 GEN
Solar/Wind Helper
0.34
203830AF1-094 GEN
Solar/Wind Helper
0.322
959441AF2-235 GEN
Solar/Wind Helper
0.146
254305AE2-115 C
Solar/Wind Helper
0.112
20334926Z1-069 C
Solar/Wind Helper
0.642
943121AE2-341 GEN
Solar/Wind Harmer
3.856
943591AF1-030 GEN
Solar/Wind Harmer
2.571
972253AH1-711 GEN
50/50
53.875
23856402BAYSG1
50/50
1.286
23920202STRYCT
50/50
1.905
241885AC2-103 GEN1
Solar/Wind Harmer
25.888
241858AF1-205_GEN
Solar/Wind Harmer
5.501
241808AF1-120 C
Solar/Wind Harmer
1.204
241840AF1-064_GEN
Solar/Wind Harmer
1.392
972301AH1-735 GEN
Adder
6.601
23906402RICHG1
Adder
1.32
23906502RICHG2&3
Adder
1.318
270361_3
Solar/Wind Harmer
8.502
960841AF2-375 GEN
Solar/Wind Harmer
3.755
241807AE2-176_GEN
Solar/Wind Harmer
2.785
247522W1-056 GEN
Solar/Wind Harmer
1.573
970515AG2-329 GEN
Solar/Wind Harmer
10.138
944231AF1-091 GEN
Solar/Wind Harmer
2.455
246936BC-WTG1
Solar/Wind Harmer
2.271
270489AE1-102 GEN1
Solar/Wind Harmer
0.755
965421AG1-410 GEN
Solar/Wind Harmer
17.247
270449AD2-020 GEN
Solar/Wind Harmer
1.583
943021AE2-325 GEN
Solar/Wind Harmer
2.057
270428AC2-015 C
Solar/Wind Harmer
3.089
24695305TIMB G C
Solar/Wind Harmer
3.089
945111AF1-176 GEN
Solar/Wind Harmer
9.863
270505AE1-170 C O1
Solar/Wind Harmer
8.284
247521TR3_G114
Solar/Wind Harmer
1.822
270246TR4_N_V150
Solar/Wind Harmer
0.461
24639705ELKHART HY
Adder
0.082
270063AE2-323 C
Solar/Wind Harmer
1.178
965011AG1-365 GEN
Solar/Wind Harmer
5.223
270462AD2-086
Solar/Wind Harmer
3.624
270223U2-072_GEN1
Solar/Wind Harmer
0.954
270578AF1-285 GEN2
Solar/Wind Harmer
0.583
270391AF1-285 GEN3
Solar/Wind Harmer
0.583
970373AG2-245 GEN
Solar/Wind Harmer
9.924
270055AF2-134 C O1
Solar/Wind Harmer
1.403
274751CRETE EC ;1U
Adder
2.233
274754CRETE EC ;4U
Adder
2.233
958381AF2-132 GEN
Solar/Wind Harmer
4.13
964861AG1-349 GEN
Solar/Wind Harmer
3.572
971917AH1-482 GEN
Solar/Wind Harmer
4.122
274723RIVER EC ;12
Adder
8.123
274812UNIV PK N;8U
Adder
2.26
276164X3-005 C
Solar/Wind Harmer
0.316
274801UNIV PARK;4U
Adder
2.593
940581AE2-045 GEN
Solar/Wind Harmer
4.53
276776AD2-060 GEN
Solar/Wind Harmer
0.188
971605AH1-302 GEN
Solar/Wind Harmer
3.873
972207SS24-0001
Solar/Wind Harmer
9.786
274773LINCOLN ;4U
Adder
2.752
274774LINCOLN ;5U
Adder
2.752
274676JOLIET 29;8U
Adder
13.513
941551AE2-152 GEN
Solar/Wind Harmer
1.995
274732ELWOOD EC;7P
Adder
7.227
274674JOLIET 9 ;6U
Adder
6.769
970245AG2-165 GEN
Solar/Wind Harmer
7.828
274871GR RIDGE ;2U
Solar/Wind Harmer
3.362
970905AG2-564 GEN
Solar/Wind Harmer
2.184
274745AC1-111 GEN9
Adder
2.43
274682WAUKEGAN ;7U
Adder
7.759
274828WAUKEGAN ;BP
Adder
4.764
961971AG1-040 GEN
Solar/Wind Helper
0.333
203835AF1-098 GEN
Solar/Wind Helper
1.311
203860AG1-193 C
Solar/Wind Helper
0.149
241966AE1-183 GEN
Solar/Wind Helper
0.13
254303AC2-168 GEN
Solar/Wind Helper
0.075
991177J1571 G
External Queue
14.956707954406738
990527J1329
External Queue
1.7751743793487549
990142J1224
External Queue
12.976524353027344
991182J1586 G
External Queue
24.279396057128906
LAGNLTFEXP_LAGN->PJM
CLTF
4.798
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.107
TVALTFEXP_TVA->PJM
CLTF
2.176
CPLELTFEXP_CPLE->PJM
CLTF
0.309
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.387
NYPJM->LTFIMP_NY
CLTF
2.013
LGEELTFEXP_LGEE->PJM
CLTF
1.955
WECLTFEXP_WEC->PJM
CLTF
1.61
AG2-052LTFEXP_AG2-052->PJM
LTF
0.104
AH1-155LTFEXP_AH1-155->PJM
LTF
0.156
CBM West 1LTFEXP_CBM-W1->PJM
CBM
91.319
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.626
MECLTFEXP_MEC->PJM
CLTF
6.275
SIGELTFEXP_SIGE->PJM
CLTF
0.163

Details for AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line l/o ATSI_P2-3_TE-345-010B1_SRT-SL


Base Case Flowgate

Area:ATSI
Facility Description:
AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_TE-345-010B1_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:141.11 %
Rating:1798.0 MVA
Rating Type:B
MVA to Mitigate:2537.18
MW Contribution:12.82
Bus #Bus NameTypeMW Contribution
23867002DVBSG1
50/50
14.099
972211AH1-690 GEN
50/50
287.424
23888502TROY G1
50/50
1.793
23888602TROY G2
50/50
1.793
241886AC2-103 GEN2
Solar/Wind Harmer
26.725
970817AG2-515 GEN
Solar/Wind Harmer
15.015
945411AF1-206 GEN
Solar/Wind Harmer
7.902
945641AF1-229 GEN
Solar/Wind Harmer
3.386
270499AE1-146 GEN
Solar/Wind Harmer
2.146
971549AH1-272 GEN
Solar/Wind Harmer
12.819
270297AD1-101 GEN
Solar/Wind Harmer
1.836
247607V1-011 GEN
Solar/Wind Harmer
2.263
944161AF1-084 GEN
Solar/Wind Harmer
1.263
957201AF2-014 GEN
Solar/Wind Harmer
2.591
270435AC2-044 GEN
Solar/Wind Harmer
1.143
966831AG1-554 GEN
Solar/Wind Harmer
0.658
971989AH1-539 GEN
Solar/Wind Harmer
7.115
965041AG1-368 GEN
Solar/Wind Harmer
5.36
965051AG1-369 GEN
Solar/Wind Harmer
2.659
971771AH1-392 GEN
Solar/Wind Harmer
4.698
270302AB2-170 GEN
Solar/Wind Harmer
4.265
270317AD1-130_GEN
Solar/Wind Harmer
1.635
971769AH1-391 GEN
Solar/Wind Harmer
5.087
960681AF2-359 GEN
Solar/Wind Harmer
1.848
971567AH1-282 GEN
Solar/Wind Harmer
7.317
971347AH1-153 GEN
Solar/Wind Harmer
7.301
963791AG1-232 GEN
Solar/Wind Harmer
6.446
270578AF1-285 GEN2
Solar/Wind Harmer
0.22
270536AF1-215 GEN2
Solar/Wind Harmer
2.094
270071AF1-092 GEN
Solar/Wind Harmer
6.808
274814UNIV PK N;0U
Adder
2.267
274807UNIV PK N;3U
Adder
2.262
274805UNIV PK N;1U
Adder
2.252
274811UNIV PK N;7U
Adder
2.247
958391AF2-133 GEN
Solar/Wind Harmer
4.069
972037AH1-567 GEN1
Adder
0.081
274827FISK ;RP
Adder
3.437
960591AF2-350 GEN
Solar/Wind Harmer
4.415
274775LINCOLN ;6U
Adder
2.736
274776LINCOLN ;7U
Adder
2.736
274777LINCOLN ;8U
Adder
2.736
972227AH1-698 GEN1
Adder
1.148
274687WILL CNTY;4U
Adder
12.26
274687WILL CNTY;4U
Adder
12.26
274675JOLIET 29;7U
Adder
13.434
274675JOLIET 29;7U
Adder
12.954
274731ELWOOD EC;2P
Adder
7.184
274733ELWOOD EC;3P
Adder
7.184
274735ELWOOD EC;4P
Adder
7.184
274728ELWOOD EC;5P
Adder
7.185
970833AG2-524 GEN
Solar/Wind Harmer
3.797
970833AG2-524 GEN
Solar/Wind Harmer
1.766
274746AC1-111 G10
Adder
2.415
274744AC1-111 GEN8
Adder
2.415
241982AE2-343 S C
Solar/Wind Helper
0.115
254304AE2-114 C
Solar/Wind Helper
0.109
203846AF2-130 C
Solar/Wind Helper
0.241
241997AF1-093 GEN
Solar/Wind Helper
0.127
203804AE2-113_GEN
Solar/Wind Helper
0.842
24189902OREGON_CT2
50/50
2.665
23888702TROY G3
50/50
1.793
972253AH1-711 GEN
50/50
54.781
23856402BAYSG1
50/50
1.208
23920202STRYCT
50/50
1.866
241885AC2-103 GEN1
Solar/Wind Harmer
26.725
241858AF1-205_GEN
Solar/Wind Harmer
5.381
241808AF1-120 C
Solar/Wind Harmer
1.18
241840AF1-064_GEN
Solar/Wind Harmer
1.335
972301AH1-735 GEN
Adder
6.449
23906402RICHG1
Adder
1.29
23906502RICHG2&3
Adder
1.287
270361_3
Solar/Wind Harmer
7.665
960841AF2-375 GEN
Solar/Wind Harmer
3.397
970515AG2-329 GEN
Solar/Wind Harmer
9.891
247522W1-056 GEN
Solar/Wind Harmer
1.451
944231AF1-091 GEN
Solar/Wind Harmer
2.417
246936BC-WTG1
Solar/Wind Harmer
2.236
270489AE1-102 GEN1
Solar/Wind Harmer
0.743
965421AG1-410 GEN
Solar/Wind Harmer
16.981
270449AD2-020 GEN
Solar/Wind Harmer
1.58
943021AE2-325 GEN
Solar/Wind Harmer
2.053
945111AF1-176 GEN
Solar/Wind Harmer
9.834
270505AE1-170 C O1
Solar/Wind Harmer
8.262
24695305TIMB G C
Solar/Wind Harmer
3.031
24639705ELKHART HY
Adder
0.082
247521TR3_G114
Solar/Wind Harmer
1.791
270246TR4_N_V150
Solar/Wind Harmer
0.453
270063AE2-323 C
Solar/Wind Harmer
1.169
965011AG1-365 GEN
Solar/Wind Harmer
5.161
270462AD2-086
Solar/Wind Harmer
3.548
270223U2-072_GEN1
Solar/Wind Harmer
0.933
270578AF1-285 GEN2
Solar/Wind Harmer
0.571
270391AF1-285 GEN3
Solar/Wind Harmer
0.571
970373AG2-245 GEN
Solar/Wind Harmer
9.875
270055AF2-134 C O1
Solar/Wind Harmer
1.396
274751CRETE EC ;1U
Adder
2.221
274754CRETE EC ;4U
Adder
2.221
958381AF2-132 GEN
Solar/Wind Harmer
4.107
964861AG1-349 GEN
Solar/Wind Harmer
3.552
971917AH1-482 GEN
Solar/Wind Harmer
4.099
274723RIVER EC ;12
Adder
8.078
274812UNIV PK N;8U
Adder
2.247
276164X3-005 C
Solar/Wind Harmer
0.314
274801UNIV PARK;4U
Adder
2.578
276776AD2-060 GEN
Solar/Wind Harmer
0.187
940581AE2-045 GEN
Solar/Wind Harmer
4.502
971605AH1-302 GEN
Solar/Wind Harmer
3.85
972207SS24-0001
Solar/Wind Harmer
9.728
274773LINCOLN ;4U
Adder
2.736
274774LINCOLN ;5U
Adder
2.736
274676JOLIET 29;8U
Adder
13.434
941551AE2-152 GEN
Solar/Wind Harmer
1.984
274732ELWOOD EC;7P
Adder
7.185
274674JOLIET 9 ;6U
Adder
6.729
970245AG2-165 GEN
Solar/Wind Harmer
7.778
274871GR RIDGE ;2U
Solar/Wind Harmer
3.342
274745AC1-111 GEN9
Adder
2.415
276691AA1-018 GEN1
Solar/Wind Harmer
0.201
961971AG1-040 GEN
Solar/Wind Helper
0.325
203835AF1-098 GEN
Solar/Wind Helper
1.28
203860AG1-193 C
Solar/Wind Helper
0.145
241966AE1-183 GEN
Solar/Wind Helper
0.127
241807AE2-176_GEN
Solar/Wind Helper
0.767
254303AC2-168 GEN
Solar/Wind Helper
0.074
24190002OREGON_ST1
50/50
3.585
24189802OREGON_CT1
50/50
2.72
23888802TROY G4
50/50
1.793
241996AE2-282_GEN
Solar/Wind Harmer
2.116
971677AH1-339 GEN
Solar/Wind Harmer
6.097
270007AE1-245 C
Solar/Wind Harmer
3.395
246938BC-WTG3
Solar/Wind Harmer
2.274
246937BC-WTG2
Solar/Wind Harmer
2.236
942801AE2-298 GEN
Solar/Wind Harmer
0.86
961051AF2-396 GEN
Solar/Wind Harmer
8.873
961051AF2-396 GEN
Solar/Wind Harmer
4.127
960981AF2-389 GEN
Solar/Wind Harmer
0.83
957891AF2-083 GEN
Solar/Wind Harmer
1.852
247620Y3-023
Adder
0.247
270216AD2-079_GEN
Solar/Wind Harmer
0.321
970611AG2-400 GEN
Solar/Wind Harmer
5.161
270526AF1-158 GEN
Solar/Wind Harmer
2.323
24441505OLIV SLR
Solar/Wind Harmer
0.068
965681AG1-436 GEN
Solar/Wind Harmer
6.114
965791AG1-447 GEN
Solar/Wind Harmer
3.128
270224U2-072_GEN2
Solar/Wind Harmer
0.933
270227U2-072_GEN3
Solar/Wind Harmer
0.933
270228U2-072_GEN4
Solar/Wind Harmer
0.933
270231U2-072_GEN5
Solar/Wind Harmer
0.933
274808UNIV PK N;4U
Adder
2.237
274803UNIV PARK;6U
Adder
2.587
274888KELLY CRK;1U
Solar/Wind Harmer
2.607
274887GEN-1.85
Solar/Wind Harmer
2.354
276843GEN-1.7
Solar/Wind Harmer
0.253
958011AF2-095 GEN
Solar/Wind Harmer
6.358
274770LINCOLN ;1U
Adder
2.736
274771LINCOLN ;2U
Adder
2.736
972259AH1-714 GEN
Adder
8.36
942221AE2-234 GEN
Solar/Wind Harmer
0.32
274674JOLIET 9 ;6U
Adder
6.729
970321AG2-212 GEN
Solar/Wind Harmer
7.778
274847GR RIDGE ;BU
Solar/Wind Harmer
2.198
203947AF1-006 C
Solar/Wind Helper
0.37
23929302BS-PKR
50/50
2.125
241832AE2-181_GEN
Solar/Wind Harmer
1.919
958321AF2-126 GEN
Solar/Wind Harmer
1.431
23906502RICHG2&3
Adder
1.287
270541AE2-072 C
Solar/Wind Harmer
4.156
270575GUS2 35KV
Solar/Wind Harmer
9.03
970217AG2-149 GEN
Solar/Wind Harmer
21.811
270044AE2-322 C
Solar/Wind Harmer
0.833
270404AC1-167 GEN
Solar/Wind Harmer
0.694
270258AD1-119 GEN
Solar/Wind Harmer
1.698
247604X1-042
Adder
0.252
24441205WTRV SLR C
Solar/Wind Harmer
0.08
270588AE1-091_GEN
Solar/Wind Harmer
6.42
958091AF2-103 GEN
Solar/Wind Harmer
0.092
270491AE1-102 GEN2
Solar/Wind Harmer
0.743
945111AF1-176 GEN
Solar/Wind Harmer
3.117
24642205MAYFLWER
Adder
0.34
270191TR4_S_V150
Solar/Wind Harmer
1.598
270247TR4_N_V136
Solar/Wind Harmer
0.453
247643Z2-116 C
Solar/Wind Harmer
0.037
970031AG2-029 GEN
Solar/Wind Harmer
15.885
959331AF2-224 GEN
Solar/Wind Harmer
5.161
965021AG1-366 GEN
Solar/Wind Harmer
1.2
270485AE1-090_GEN
Solar/Wind Harmer
0.308
270043AE2-236 GEN
Solar/Wind Harmer
2.687
970349AG2-230 GEN
Solar/Wind Harmer
7.301
942871AE2-306 GEN
Solar/Wind Harmer
0.428
270391AF1-285 GEN3
Solar/Wind Harmer
0.22
270535AF1-215 GEN1
Solar/Wind Harmer
2.094
972231SS25-0005
Solar/Wind Harmer
4.312
972181SS23-001
Solar/Wind Harmer
2.695
274752CRETE EC ;2U
Adder
2.221
274753CRETE EC ;3U
Adder
2.221
964401AG1-302 GEN
Solar/Wind Harmer
4.107
274724RIVER EC ;11
Adder
7.981
959141AF2-205 GEN
Solar/Wind Harmer
2.692
274802UNIV PARK;5U
Adder
2.587
274826FISK ;BP
Adder
4.849
274800UNIV PARK;3U
Adder
2.578
972038AH1-567 GEN2
Adder
0.161
276772AC2-154 GEN
Solar/Wind Harmer
1.231
276806AD2-047 C O1
Solar/Wind Harmer
4.724
970941AG2-585 GEN
Solar/Wind Harmer
5.519
274772LINCOLN ;3U
Adder
2.736
972228AH1-698 GEN2
Adder
1.631
274676JOLIET 29;8U
Adder
12.954
276897AD1-100 C
Solar/Wind Harmer
12.693
939351AE1-166 GEN
Solar/Wind Harmer
2.593
276893AG1-478 C
Solar/Wind Harmer
0.183
274729ELWOOD EC;1P
Adder
7.184
274730ELWOOD EC;6P
Adder
7.185
274734ELWOOD EC;8P
Adder
7.185
274736ELWOOD EC;9P
Adder
7.185
970707AG2-453 GEN
Solar/Wind Harmer
12.236
970513AG2-328 GEN
Solar/Wind Harmer
7.778
970517AG2-330 GEN
Solar/Wind Harmer
7.054
943121AE2-341 GEN
Solar/Wind Harmer
6.479
943591AF1-030 GEN
Solar/Wind Harmer
4.319
276694AA1-018 GEN2
Solar/Wind Harmer
2.725
962511AG1-100 GEN
Solar/Wind Helper
0.332
203830AF1-094 GEN
Solar/Wind Helper
0.314
959441AF2-235 GEN
Solar/Wind Helper
0.143
254305AE2-115 C
Solar/Wind Helper
0.109
203980AG1-197 GEN
Solar/Wind Helper
0.242
203979AG1-198 GEN
Solar/Wind Helper
0.188
241967AE2-285_GEN
Solar/Wind Helper
0.33
241801AE1-079 GEN
Solar/Wind Helper
0.128
241985AE1-237 GEN
Solar/Wind Helper
0.128
962101AG1-054 GEN
Solar/Wind Helper
0.319
946381AF1-302 GEN
Solar/Wind Helper
0.102
958481AF2-142 GEN
Solar/Wind Harmer
6.372
991177J1571 G
External Queue
15.044508934020996
990527J1329
External Queue
1.8002409934997559
990142J1224
External Queue
13.159761428833008
991182J1586 G
External Queue
24.65229034423828
LAGNLTFEXP_LAGN->PJM
CLTF
4.752
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.085
TVALTFEXP_TVA->PJM
CLTF
2.153
CPLELTFEXP_CPLE->PJM
CLTF
0.308
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.025
NYPJM->LTFIMP_NY
CLTF
1.97
LGEELTFEXP_LGEE->PJM
CLTF
1.929
WECLTFEXP_WEC->PJM
CLTF
1.6
AG2-052LTFEXP_AG2-052->PJM
LTF
0.103
AH1-155LTFEXP_AH1-155->PJM
LTF
0.155
CBM West 1LTFEXP_CBM-W1->PJM
CBM
91.578
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.528
MECLTFEXP_MEC->PJM
CLTF
6.231
SIGELTFEXP_SIGE->PJM
CLTF
0.161

Details for AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line l/o ATSI_P1-2_OEC-345-810_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_OEC-345-810_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:123.08 %
Rating:1798.0 MVA
Rating Type:B
MVA to Mitigate:2212.91
MW Contribution:9.98
Bus #Bus NameTypeMW Contribution
23929302BS-PKR
50/50
2.125
241832AE2-181_GEN
Solar/Wind Harmer
0.003
958321AF2-126 GEN
Solar/Wind Harmer
1.109
24189902OREGON_CT2
50/50
2.665
23888702TROY G3
50/50
1.793
972253AH1-711 GEN
50/50
54.781
23856402BAYSG1
50/50
1.208
23920202STRYCT
50/50
1.866
241885AC2-103 GEN1
Solar/Wind Harmer
-0.001
241858AF1-205_GEN
Solar/Wind Harmer
3.754
241808AF1-120 C
Solar/Wind Harmer
0.003
241840AF1-064_GEN
Solar/Wind Harmer
0.004
972301AH1-735 GEN
Adder
6.449
23906402RICHG1
Adder
1.29
23906502RICHG2&3
Adder
1.287
24190002OREGON_ST1
50/50
3.585
24189802OREGON_CT1
50/50
2.72
23888802TROY G4
50/50
1.793
241996AE2-282_GEN
Solar/Wind Harmer
0.005
23906502RICHG2&3
Adder
1.287
270541AE2-072 C
Solar/Wind Harmer
0.008
270575GUS2 35KV
Solar/Wind Harmer
4.19
970217AG2-149 GEN
Solar/Wind Harmer
4.121
270404AC1-167 GEN
Solar/Wind Harmer
0.002
270258AD1-119 GEN
Solar/Wind Harmer
0.001
247604X1-042
Adder
0.252
24441205WTRV SLR C
Solar/Wind Harmer
0
270588AE1-091_GEN
Solar/Wind Harmer
3.185
270491AE1-102 GEN2
Solar/Wind Harmer
0.518
945111AF1-176 GEN
Solar/Wind Harmer
3.117
24642205MAYFLWER
Adder
0.34
270191TR4_S_V150
Solar/Wind Harmer
0
270247TR4_N_V136
Solar/Wind Harmer
0.024
247643Z2-116 C
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
2.401
959331AF2-224 GEN
Solar/Wind Harmer
2.52
965021AG1-366 GEN
Solar/Wind Harmer
1.2
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270043AE2-236 GEN
Solar/Wind Harmer
2.187
970349AG2-230 GEN
Solar/Wind Harmer
5.093
270391AF1-285 GEN3
Solar/Wind Harmer
0.22
270535AF1-215 GEN1
Solar/Wind Harmer
0.004
274752CRETE EC ;2U
Adder
3.744
274753CRETE EC ;3U
Adder
3.744
964401AG1-302 GEN
Solar/Wind Harmer
0
274724RIVER EC ;11
Adder
7.981
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
274802UNIV PARK;5U
Adder
2.587
274826FISK ;BP
Adder
4.849
274800UNIV PARK;3U
Adder
2.578
972038AH1-567 GEN2
Adder
0.161
276806AD2-047 C O1
Solar/Wind Harmer
1.746
970941AG2-585 GEN
Solar/Wind Harmer
3.851
274772LINCOLN ;3U
Adder
3.725
972228AH1-698 GEN2
Adder
1.631
274676JOLIET 29;8U
Adder
12.954
276897AD1-100 C
Solar/Wind Harmer
0.004
939351AE1-166 GEN
Solar/Wind Harmer
0
276893AG1-478 C
Solar/Wind Harmer
0.121
274729ELWOOD EC;1P
Adder
7.184
274730ELWOOD EC;6P
Adder
7.185
274734ELWOOD EC;8P
Adder
7.185
274736ELWOOD EC;9P
Adder
7.185
970707AG2-453 GEN
Solar/Wind Harmer
9.96
970513AG2-328 GEN
Solar/Wind Harmer
1.317
970517AG2-330 GEN
Solar/Wind Harmer
7.901
943121AE2-341 GEN
Solar/Wind Harmer
5.053
943591AF1-030 GEN
Solar/Wind Harmer
3.36
276694AA1-018 GEN2
Solar/Wind Harmer
0
971617AH1-308 GEN
Solar/Wind Harmer
2.509
962511AG1-100 GEN
Solar/Wind Helper
0.332
203830AF1-094 GEN
Solar/Wind Helper
0.314
959441AF2-235 GEN
Solar/Wind Helper
0.143
254305AE2-115 C
Solar/Wind Helper
0.109
23867002DVBSG1
50/50
14.099
972211AH1-690 GEN
50/50
287.424
23888502TROY G1
50/50
1.793
23888602TROY G2
50/50
1.793
241886AC2-103 GEN2
Solar/Wind Harmer
-0.001
970817AG2-515 GEN
Solar/Wind Harmer
10.476
945411AF1-206 GEN
Solar/Wind Harmer
-0.001
945641AF1-229 GEN
Solar/Wind Harmer
0.001
270499AE1-146 GEN
Solar/Wind Harmer
0.027
971549AH1-272 GEN
Solar/Wind Harmer
9.983
270297AD1-101 GEN
Solar/Wind Harmer
0.001
247607V1-011 GEN
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.505
971619AH1-309 GEN
Solar/Wind Harmer
1.729
971989AH1-539 GEN
Solar/Wind Harmer
1.655
965041AG1-368 GEN
Solar/Wind Harmer
3.74
965051AG1-369 GEN
Solar/Wind Harmer
1.855
971771AH1-392 GEN
Solar/Wind Harmer
3.641
270302AB2-170 GEN
Solar/Wind Harmer
0.002
270317AD1-130_GEN
Solar/Wind Harmer
0.005
971653AH1-327 GEN
Solar/Wind Harmer
0.5
971769AH1-391 GEN
Solar/Wind Harmer
3.963
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971567AH1-282 GEN
Solar/Wind Harmer
5.105
971347AH1-153 GEN
Solar/Wind Harmer
5.093
963791AG1-232 GEN
Solar/Wind Harmer
4.498
270578AF1-285 GEN2
Solar/Wind Harmer
0.22
270536AF1-215 GEN2
Solar/Wind Harmer
0.004
270071AF1-092 GEN
Solar/Wind Harmer
6.069
274814UNIV PK N;0U
Adder
2.267
274807UNIV PK N;3U
Adder
2.262
274805UNIV PK N;1U
Adder
2.252
274811UNIV PK N;7U
Adder
2.247
958391AF2-133 GEN
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.081
274827FISK ;RP
Adder
3.437
960591AF2-350 GEN
Solar/Wind Harmer
3.081
971611AH1-305 GEN
Solar/Wind Harmer
1.834
274775LINCOLN ;6U
Adder
3.725
274776LINCOLN ;7U
Adder
3.725
274777LINCOLN ;8U
Adder
3.725
972227AH1-698 GEN1
Adder
1.148
274687WILL CNTY;4U
Adder
12.26
274687WILL CNTY;4U
Adder
12.26
274675JOLIET 29;7U
Adder
13.434
274675JOLIET 29;7U
Adder
12.954
274731ELWOOD EC;2P
Adder
7.184
274733ELWOOD EC;3P
Adder
7.184
274735ELWOOD EC;4P
Adder
7.184
274728ELWOOD EC;5P
Adder
7.185
970833AG2-524 GEN
Solar/Wind Harmer
3.337
970833AG2-524 GEN
Solar/Wind Harmer
2.225
274746AC1-111 G10
Adder
2.415
274744AC1-111 GEN8
Adder
2.415
270024AE2-089 GEN
Solar/Wind Harmer
0.003
241982AE2-343 S C
Solar/Wind Helper
0.115
254304AE2-114 C
Solar/Wind Helper
0.109
203846AF2-130 C
Solar/Wind Helper
0.241
241997AF1-093 GEN
Solar/Wind Helper
0.127
203804AE2-113_GEN
Solar/Wind Helper
0.842
270361_3
Solar/Wind Harmer
4.19
960841AF2-375 GEN
Solar/Wind Harmer
-0.001
970515AG2-329 GEN
Solar/Wind Harmer
12.364
247522W1-056 GEN
Solar/Wind Harmer
0.001
944231AF1-091 GEN
Solar/Wind Harmer
1.193
246936BC-WTG1
Solar/Wind Harmer
0.162
270489AE1-102 GEN1
Solar/Wind Harmer
0.518
965421AG1-410 GEN
Solar/Wind Harmer
11.847
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.053
945111AF1-176 GEN
Solar/Wind Harmer
6.861
270505AE1-170 C O1
Solar/Wind Harmer
4.035
24695305TIMB G C
Solar/Wind Harmer
0.001
24639705ELKHART HY
Adder
0.082
247521TR3_G114
Solar/Wind Harmer
0.135
270246TR4_N_V150
Solar/Wind Harmer
0.024
270063AE2-323 C
Solar/Wind Harmer
0.003
965011AG1-365 GEN
Solar/Wind Harmer
3.601
270462AD2-086
Solar/Wind Harmer
0.007
270223U2-072_GEN1
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
6.889
270055AF2-134 C O1
Solar/Wind Harmer
0.002
274751CRETE EC ;1U
Adder
3.744
274754CRETE EC ;4U
Adder
3.744
958381AF2-132 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.099
274723RIVER EC ;12
Adder
8.078
274812UNIV PK N;8U
Adder
2.247
276164X3-005 C
Solar/Wind Harmer
0
274801UNIV PARK;4U
Adder
2.578
276776AD2-060 GEN
Solar/Wind Harmer
0.322
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
3.85
274773LINCOLN ;4U
Adder
3.725
274774LINCOLN ;5U
Adder
3.725
274676JOLIET 29;8U
Adder
13.434
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
7.185
274674JOLIET 9 ;6U
Adder
6.729
970245AG2-165 GEN
Solar/Wind Harmer
1.317
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
2.415
276691AA1-018 GEN1
Solar/Wind Harmer
0.365
961971AG1-040 GEN
Solar/Wind Helper
0.325
203835AF1-098 GEN
Solar/Wind Helper
1.28
203860AG1-193 C
Solar/Wind Helper
0.145
241966AE1-183 GEN
Solar/Wind Helper
0.127
241807AE2-176_GEN
Solar/Wind Helper
0.767
254303AC2-168 GEN
Solar/Wind Helper
0.074
971677AH1-339 GEN
Solar/Wind Harmer
0.599
970621AG2-405 GEN
Solar/Wind Harmer
0.843
970623AG2-406 GEN
Solar/Wind Harmer
0.778
270007AE1-245 C
Solar/Wind Harmer
0.001
246938BC-WTG3
Solar/Wind Harmer
0.144
246937BC-WTG2
Solar/Wind Harmer
0.162
961051AF2-396 GEN
Solar/Wind Harmer
7.8
961051AF2-396 GEN
Solar/Wind Harmer
5.2
957891AF2-083 GEN
Solar/Wind Harmer
0.001
247620Y3-023
Adder
0.247
270216AD2-079_GEN
Solar/Wind Harmer
0.001
970611AG2-400 GEN
Solar/Wind Harmer
3.601
970627AG2-408 GEN
Solar/Wind Harmer
1.08
270526AF1-158 GEN
Solar/Wind Harmer
0.004
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
4.266
965791AG1-447 GEN
Solar/Wind Harmer
3.128
270224U2-072_GEN2
Solar/Wind Harmer
0
270227U2-072_GEN3
Solar/Wind Harmer
0
270228U2-072_GEN4
Solar/Wind Harmer
0
270231U2-072_GEN5
Solar/Wind Harmer
0
274808UNIV PK N;4U
Adder
2.237
274803UNIV PARK;6U
Adder
2.587
274888KELLY CRK;1U
Solar/Wind Harmer
0.181
274887GEN-1.85
Solar/Wind Harmer
0.081
276843GEN-1.7
Solar/Wind Harmer
0.1
958011AF2-095 GEN
Solar/Wind Harmer
4.436
274770LINCOLN ;1U
Adder
3.725
274771LINCOLN ;2U
Adder
3.725
972259AH1-714 GEN
Adder
8.36
942221AE2-234 GEN
Solar/Wind Harmer
0.015
274674JOLIET 9 ;6U
Adder
6.729
970321AG2-212 GEN
Solar/Wind Harmer
1.317
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
958481AF2-142 GEN
Solar/Wind Harmer
4.519
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.408
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
971573AH1-285 GEN
Solar/Wind Harmer
0.56
203947AF1-006 C
Solar/Wind Helper
0.37
203980AG1-197 GEN
Solar/Wind Helper
0.242
203979AG1-198 GEN
Solar/Wind Helper
0.188
241967AE2-285_GEN
Solar/Wind Helper
0.33
241801AE1-079 GEN
Solar/Wind Helper
0.128
241985AE1-237 GEN
Solar/Wind Helper
0.128
962101AG1-054 GEN
Solar/Wind Helper
0.319
946381AF1-302 GEN
Solar/Wind Helper
0.102
991177J1571 G
External Queue
15.044508934020996
990527J1329
External Queue
1.8002409934997559
990142J1224
External Queue
13.159761428833008
991182J1586 G
External Queue
24.65229034423828
LAGNLTFEXP_LAGN->PJM
CLTF
4.752
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.085
TVALTFEXP_TVA->PJM
CLTF
2.153
CPLELTFEXP_CPLE->PJM
CLTF
0.308
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.025
NYPJM->LTFIMP_NY
CLTF
1.97
LGEELTFEXP_LGEE->PJM
CLTF
1.929
WECLTFEXP_WEC->PJM
CLTF
1.6
AG2-052LTFEXP_AG2-052->PJM
LTF
0.103
AH1-155LTFEXP_AH1-155->PJM
LTF
0.155
CBM West 1LTFEXP_CBM-W1->PJM
CBM
91.578
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.528
MECLTFEXP_MEC->PJM
CLTF
6.231
SIGELTFEXP_SIGE->PJM
CLTF
0.161

Details for AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line l/o ATSI_P1-2_OEC-345-809_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_OEC-345-809_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:117.76 %
Rating:1798.0 MVA
Rating Type:B
MVA to Mitigate:2117.36
MW Contribution:9.82
Bus #Bus NameTypeMW Contribution
23867002DVBSG1
50/50
12.718
972211AH1-690 GEN
50/50
274.788
23888502TROY G1
50/50
1.734
23888602TROY G2
50/50
1.734
241886AC2-103 GEN2
Solar/Wind Harmer
-0.001
970817AG2-515 GEN
Solar/Wind Harmer
10.276
945411AF1-206 GEN
Solar/Wind Harmer
-0.001
270499AE1-146 GEN
Solar/Wind Harmer
0.029
945641AF1-229 GEN
Solar/Wind Harmer
0.001
971549AH1-272 GEN
Solar/Wind Harmer
9.816
270297AD1-101 GEN
Solar/Wind Harmer
0.001
971989AH1-539 GEN
Solar/Wind Harmer
1.766
247607V1-011 GEN
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.507
971619AH1-309 GEN
Solar/Wind Harmer
1.709
965041AG1-368 GEN
Solar/Wind Harmer
3.755
965051AG1-369 GEN
Solar/Wind Harmer
1.865
971771AH1-392 GEN
Solar/Wind Harmer
3.604
270302AB2-170 GEN
Solar/Wind Harmer
0.002
270317AD1-130_GEN
Solar/Wind Harmer
0.005
971653AH1-327 GEN
Solar/Wind Harmer
0.505
24191202EL_AA1-006
Adder
0.112
971769AH1-391 GEN
Solar/Wind Harmer
3.923
971567AH1-282 GEN
Solar/Wind Harmer
5.235
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971347AH1-153 GEN
Solar/Wind Harmer
5.047
963791AG1-232 GEN
Solar/Wind Harmer
4.499
270578AF1-285 GEN2
Solar/Wind Harmer
0.222
270536AF1-215 GEN2
Solar/Wind Harmer
0.004
270071AF1-092 GEN
Solar/Wind Harmer
6.048
274814UNIV PK N;0U
Adder
2.248
274807UNIV PK N;3U
Adder
2.243
274805UNIV PK N;1U
Adder
2.233
274811UNIV PK N;7U
Adder
2.229
958391AF2-133 GEN
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.081
274827FISK ;RP
Adder
3.409
971611AH1-305 GEN
Solar/Wind Harmer
1.819
24189902OREGON_CT2
50/50
2.548
23888702TROY G3
50/50
1.734
972253AH1-711 GEN
50/50
52.952
23856402BAYSG1
50/50
1.279
23920202STRYCT
50/50
1.883
241885AC2-103 GEN1
Solar/Wind Harmer
-0.001
241858AF1-205_GEN
Solar/Wind Harmer
3.794
241808AF1-120 C
Solar/Wind Harmer
0.003
241840AF1-064_GEN
Solar/Wind Harmer
0.004
972301AH1-735 GEN
Adder
6.527
23906402RICHG1
Adder
1.305
23906502RICHG2&3
Adder
1.303
270361_3
Solar/Wind Harmer
4.647
960841AF2-375 GEN
Solar/Wind Harmer
-0.002
241807AE2-176_GEN
Solar/Wind Harmer
0.004
247522W1-056 GEN
Solar/Wind Harmer
0.001
970515AG2-329 GEN
Solar/Wind Harmer
12.533
944231AF1-091 GEN
Solar/Wind Harmer
1.197
270428AC2-015 C
Solar/Wind Harmer
0.002
246936BC-WTG1
Solar/Wind Harmer
0.162
270489AE1-102 GEN1
Solar/Wind Harmer
0.52
965421AG1-410 GEN
Solar/Wind Harmer
11.884
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.028
24695305TIMB G C
Solar/Wind Harmer
0.001
945111AF1-176 GEN
Solar/Wind Harmer
6.783
270505AE1-170 C O1
Solar/Wind Harmer
3.988
247521TR3_G114
Solar/Wind Harmer
0.136
270246TR4_N_V150
Solar/Wind Harmer
0.024
24639705ELKHART HY
Adder
0.081
270063AE2-323 C
Solar/Wind Harmer
0.003
965011AG1-365 GEN
Solar/Wind Harmer
3.597
270462AD2-086
Solar/Wind Harmer
0.008
270223U2-072_GEN1
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
6.828
270055AF2-134 C O1
Solar/Wind Harmer
0.002
970905AG2-564 GEN
Solar/Wind Harmer
1.725
274751CRETE EC ;1U
Adder
3.712
274754CRETE EC ;4U
Adder
3.712
958381AF2-132 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.065
274723RIVER EC ;12
Adder
8.011
274812UNIV PK N;8U
Adder
2.229
276164X3-005 C
Solar/Wind Harmer
0
274801UNIV PARK;4U
Adder
2.557
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
3.82
276776AD2-060 GEN
Solar/Wind Harmer
0.319
274773LINCOLN ;4U
Adder
3.695
274774LINCOLN ;5U
Adder
3.695
274676JOLIET 29;8U
Adder
13.326
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
7.127
274674JOLIET 9 ;6U
Adder
6.676
970245AG2-165 GEN
Solar/Wind Harmer
1.307
274871GR RIDGE ;2U
Solar/Wind Harmer
0
961971AG1-040 GEN
Solar/Wind Helper
0.329
203835AF1-098 GEN
Solar/Wind Helper
1.297
203860AG1-193 C
Solar/Wind Helper
0.147
241966AE1-183 GEN
Solar/Wind Helper
0.128
254303AC2-168 GEN
Solar/Wind Helper
0.075
960591AF2-350 GEN
Solar/Wind Harmer
3.056
274775LINCOLN ;6U
Adder
3.695
274776LINCOLN ;7U
Adder
3.695
274777LINCOLN ;8U
Adder
3.695
972227AH1-698 GEN1
Adder
1.139
274687WILL CNTY;4U
Adder
12.162
274687WILL CNTY;4U
Adder
12.162
274675JOLIET 29;7U
Adder
13.327
274675JOLIET 29;7U
Adder
12.851
274728ELWOOD EC;5P
Adder
7.127
274731ELWOOD EC;2P
Adder
7.127
274733ELWOOD EC;3P
Adder
7.127
274735ELWOOD EC;4P
Adder
7.127
270024AE2-089 GEN
Solar/Wind Harmer
0.003
970833AG2-524 GEN
Solar/Wind Harmer
3.311
970833AG2-524 GEN
Solar/Wind Harmer
2.207
241982AE2-343 S C
Solar/Wind Helper
0.116
254304AE2-114 C
Solar/Wind Helper
0.111
203846AF2-130 C
Solar/Wind Helper
0.244
241997AF1-093 GEN
Solar/Wind Helper
0.128
203804AE2-113_GEN
Solar/Wind Helper
0.852
24190002OREGON_ST1
50/50
3.428
24189802OREGON_CT1
50/50
2.6
23888802TROY G4
50/50
1.734
241996AE2-282_GEN
Solar/Wind Harmer
0.005
971677AH1-339 GEN
Solar/Wind Harmer
0.654
970621AG2-405 GEN
Solar/Wind Harmer
0.864
970623AG2-406 GEN
Solar/Wind Harmer
0.785
270007AE1-245 C
Solar/Wind Harmer
0.001
246938BC-WTG3
Solar/Wind Harmer
0.145
246937BC-WTG2
Solar/Wind Harmer
0.162
961051AF2-396 GEN
Solar/Wind Harmer
7.707
961051AF2-396 GEN
Solar/Wind Harmer
5.138
957891AF2-083 GEN
Solar/Wind Harmer
0.001
247620Y3-023
Adder
0.245
270216AD2-079_GEN
Solar/Wind Harmer
0.001
970611AG2-400 GEN
Solar/Wind Harmer
3.597
970627AG2-408 GEN
Solar/Wind Harmer
1.079
270526AF1-158 GEN
Solar/Wind Harmer
0.004
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
4.224
965791AG1-447 GEN
Solar/Wind Harmer
3.098
270224U2-072_GEN2
Solar/Wind Harmer
0
270227U2-072_GEN3
Solar/Wind Harmer
0
270228U2-072_GEN4
Solar/Wind Harmer
0
270231U2-072_GEN5
Solar/Wind Harmer
0
971231AH1-075 GEN
Solar/Wind Harmer
0.372
274808UNIV PK N;4U
Adder
2.219
274803UNIV PARK;6U
Adder
2.566
274888KELLY CRK;1U
Solar/Wind Harmer
0.179
274887GEN-1.85
Solar/Wind Harmer
0.08
276843GEN-1.7
Solar/Wind Harmer
0.099
958011AF2-095 GEN
Solar/Wind Harmer
4.4
274770LINCOLN ;1U
Adder
3.695
274771LINCOLN ;2U
Adder
3.695
942221AE2-234 GEN
Solar/Wind Harmer
0.015
972259AH1-714 GEN
Adder
8.293
274674JOLIET 9 ;6U
Adder
6.676
970321AG2-212 GEN
Solar/Wind Harmer
1.307
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
203947AF1-006 C
Solar/Wind Helper
0.375
203980AG1-197 GEN
Solar/Wind Helper
0.245
203979AG1-198 GEN
Solar/Wind Helper
0.191
241967AE2-285_GEN
Solar/Wind Helper
0.334
241801AE1-079 GEN
Solar/Wind Helper
0.13
241985AE1-237 GEN
Solar/Wind Helper
0.129
962101AG1-054 GEN
Solar/Wind Helper
0.322
946381AF1-302 GEN
Solar/Wind Helper
0.103
23929302BS-PKR
50/50
2.251
241832AE2-181_GEN
Solar/Wind Harmer
0.003
958321AF2-126 GEN
Solar/Wind Harmer
1.147
23906502RICHG2&3
Adder
1.303
270575GUS2 35KV
Solar/Wind Harmer
4.647
270541AE2-072 C
Solar/Wind Harmer
0.008
970217AG2-149 GEN
Solar/Wind Harmer
4.178
270404AC1-167 GEN
Solar/Wind Harmer
0.002
270258AD1-119 GEN
Solar/Wind Harmer
0.001
270588AE1-091_GEN
Solar/Wind Harmer
3.347
247604X1-042
Adder
0.248
24441205WTRV SLR C
Solar/Wind Harmer
0
270491AE1-102 GEN2
Solar/Wind Harmer
0.52
945111AF1-176 GEN
Solar/Wind Harmer
3.081
270191TR4_S_V150
Solar/Wind Harmer
0
270247TR4_N_V136
Solar/Wind Harmer
0.024
24642205MAYFLWER
Adder
0.337
970031AG2-029 GEN
Solar/Wind Harmer
2.384
247643Z2-116 C
Solar/Wind Harmer
0
959331AF2-224 GEN
Solar/Wind Harmer
2.518
965021AG1-366 GEN
Solar/Wind Harmer
1.199
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270043AE2-236 GEN
Solar/Wind Harmer
2.178
970349AG2-230 GEN
Solar/Wind Harmer
5.047
270391AF1-285 GEN3
Solar/Wind Harmer
0.222
270377AD1-106 GEN
Solar/Wind Harmer
1.233
270535AF1-215 GEN1
Solar/Wind Harmer
0.004
274752CRETE EC ;2U
Adder
3.712
274753CRETE EC ;3U
Adder
3.712
964401AG1-302 GEN
Solar/Wind Harmer
0
274724RIVER EC ;11
Adder
7.915
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
274802UNIV PARK;5U
Adder
2.566
274826FISK ;BP
Adder
4.81
274800UNIV PARK;3U
Adder
2.557
972038AH1-567 GEN2
Adder
0.16
276806AD2-047 C O1
Solar/Wind Harmer
1.732
970941AG2-585 GEN
Solar/Wind Harmer
3.82
274772LINCOLN ;3U
Adder
3.695
972228AH1-698 GEN2
Adder
1.618
274676JOLIET 29;8U
Adder
12.851
276897AD1-100 C
Solar/Wind Harmer
0.004
939351AE1-166 GEN
Solar/Wind Harmer
0
276893AG1-478 C
Solar/Wind Harmer
0.12
274730ELWOOD EC;6P
Adder
7.127
274734ELWOOD EC;8P
Adder
7.127
274736ELWOOD EC;9P
Adder
7.127
970707AG2-453 GEN
Solar/Wind Harmer
9.881
274729ELWOOD EC;1P
Adder
7.127
970513AG2-328 GEN
Solar/Wind Harmer
1.307
970517AG2-330 GEN
Solar/Wind Harmer
7.843
971617AH1-308 GEN
Solar/Wind Harmer
2.511
962511AG1-100 GEN
Solar/Wind Helper
0.336
203830AF1-094 GEN
Solar/Wind Helper
0.318
959441AF2-235 GEN
Solar/Wind Helper
0.145
254305AE2-115 C
Solar/Wind Helper
0.111
20334926Z1-069 C
Solar/Wind Helper
0.635
991177J1571 G
External Queue
14.724894523620605
990527J1329
External Queue
1.745489239692688
990142J1224
External Queue
12.759525299072266
991182J1586 G
External Queue
23.868927001953125
LAGNLTFEXP_LAGN->PJM
CLTF
4.735
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.079
TVALTFEXP_TVA->PJM
CLTF
2.148
CPLELTFEXP_CPLE->PJM
CLTF
0.305
CBM West 2LTFEXP_CBM-W2->PJM
CBM
37.878
NYPJM->LTFIMP_NY
CLTF
1.99
LGEELTFEXP_LGEE->PJM
CLTF
1.931
WECLTFEXP_WEC->PJM
CLTF
1.588
AG2-052LTFEXP_AG2-052->PJM
LTF
0.102
AH1-155LTFEXP_AH1-155->PJM
LTF
0.153
CBM West 1LTFEXP_CBM-W1->PJM
CBM
89.942
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.514
MECLTFEXP_MEC->PJM
CLTF
6.19
SIGELTFEXP_SIGE->PJM
CLTF
0.161

Details for AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:138.82 %
Rating:1868.0 MVA
Rating Type:B
MVA to Mitigate:2593.18
MW Contribution:9.79
Bus #Bus NameTypeMW Contribution
965431AG1-411 GEN
50/50
45.408
24727105RPMNG2
50/50
3.32
970583AG2-370 GEN
50/50
2.809
959331AF2-224 GEN
Solar/Wind Harmer
9.634
965021AG1-366 GEN
Solar/Wind Harmer
4.588
970031AG2-029 GEN
Solar/Wind Harmer
5.463
270043AE2-236 GEN
Solar/Wind Harmer
5.191
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.046
944531AF1-118 GEN
Solar/Wind Harmer
31.488
971617AH1-308 GEN
Solar/Wind Harmer
5.166
247643Z2-116 C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
4.805
970349AG2-230 GEN
Solar/Wind Harmer
8.688
24642205MAYFLWER
Adder
0.524
24441205WTRV SLR C
Solar/Wind Harmer
0
970513AG2-328 GEN
Solar/Wind Harmer
2.307
970517AG2-330 GEN
Solar/Wind Harmer
13.84
274752CRETE EC ;2U
Adder
6.241
274753CRETE EC ;3U
Adder
6.241
274724RIVER EC ;11
Adder
13.364
247604X1-042
Adder
0.313
270535AF1-215 GEN1
Solar/Wind Harmer
0.007
274772LINCOLN ;3U
Adder
6.292
274802UNIV PARK;5U
Adder
4.319
274826FISK ;BP
Adder
8.102
274800UNIV PARK;3U
Adder
4.307
972038AH1-567 GEN2
Adder
0.27
276806AD2-047 C O1
Solar/Wind Harmer
2.917
970941AG2-585 GEN
Solar/Wind Harmer
6.434
964401AG1-302 GEN
Solar/Wind Harmer
0.001
972228AH1-698 GEN2
Adder
2.725
970707AG2-453 GEN
Solar/Wind Harmer
16.709
276897AD1-100 C
Solar/Wind Harmer
0.007
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
21.601
276893AG1-478 C
Solar/Wind Harmer
0.201
274730ELWOOD EC;6P
Adder
11.97
274734ELWOOD EC;8P
Adder
11.97
274736ELWOOD EC;9P
Adder
11.97
274729ELWOOD EC;1P
Adder
11.97
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
943121AE2-341 GEN
Solar/Wind Harmer
8.419
943591AF1-030 GEN
Solar/Wind Harmer
5.599
247642Z2-115 C
Solar/Wind Harmer
0.002
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
12.782
970289AG2-191 GEN
Solar/Wind Harmer
0.545
970291AG2-192 GEN
Solar/Wind Harmer
0.496
958821AF2-173 GEN
Solar/Wind Harmer
6.901
270004AE1-209 GEN
Solar/Wind Harmer
1.068
276805AD2-038 GEN
Solar/Wind Harmer
0.001
274872LEEDK;1U
Solar/Wind Harmer
0.18
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.518
274855GSG-6 ;RU
Solar/Wind Harmer
0.178
274850MENDOTA H;RU
Solar/Wind Harmer
0.057
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.087
276889AE2-281 GEN
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
4.834
959091AF2-200 GEN
Solar/Wind Harmer
9.652
972236AH1-702 GEN2
Adder
1.508
970571AG2-364 GEN
Solar/Wind Harmer
9.558
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
6.304
274767LEE CO EC;8U
Adder
6.23
946031AF1-268 GEN
Solar/Wind Harmer
4.492
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
7.069
276157O29GEN1
Solar/Wind Harmer
0.755
274878BISHOP HL;2U
Solar/Wind Harmer
0.156
942111AE2-223 GEN
Solar/Wind Harmer
1.494
965931AG1-462 GEN
Solar/Wind Harmer
11.522
274853TWINGROVE;U1
Solar/Wind Harmer
0.002
24727005RPMNG1
50/50
3.308
960861AF2-377 GEN
50/50
2.399
970521AG2-332 GEN
50/50
10.806
24639705ELKHART HY
50/50
0.149
965421AG1-410 GEN
Solar/Wind Harmer
81.734
965011AG1-365 GEN
Solar/Wind Harmer
13.763
270063AE2-323 C
Solar/Wind Harmer
0.006
247521TR3_G114
Solar/Wind Harmer
0.262
270246TR4_N_V150
Solar/Wind Harmer
0.046
944231AF1-091 GEN
Solar/Wind Harmer
1.854
24695305TIMB G C
Solar/Wind Harmer
0.002
965651AG1-433 GEN
Solar/Wind Harmer
1.839
958861AF2-177 GEN
Solar/Wind Harmer
2.638
945111AF1-176 GEN
Solar/Wind Harmer
10.578
270505AE1-170 C O1
Solar/Wind Harmer
6.07
945371AF1-202 GEN
Solar/Wind Harmer
0
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.97
970245AG2-165 GEN
Solar/Wind Harmer
2.307
970373AG2-245 GEN
Solar/Wind Harmer
11.147
274751CRETE EC ;1U
Adder
6.241
274754CRETE EC ;4U
Adder
6.241
274723RIVER EC ;12
Adder
13.527
274812UNIV PK N;8U
Adder
3.75
276164X3-005 C
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0.004
274773LINCOLN ;4U
Adder
6.292
274774LINCOLN ;5U
Adder
6.292
274801UNIV PARK;4U
Adder
4.307
276776AD2-060 GEN
Solar/Wind Harmer
0.537
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
6.671
941551AE2-152 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
22.401
274674JOLIET 9 ;6U
Adder
11.217
274732ELWOOD EC;7P
Adder
11.97
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
6.288
274745AC1-111 GEN9
Adder
4.021
276691AA1-018 GEN1
Solar/Wind Harmer
0.604
274682WAUKEGAN ;7U
Adder
12.782
970291AG2-192 GEN
Solar/Wind Harmer
0.645
274828WAUKEGAN ;BP
Adder
7.846
270005AE1-210 C O1
Solar/Wind Harmer
1.068
965031AG1-367 GEN
Solar/Wind Harmer
4.929
962781AG1-127 GEN
Solar/Wind Harmer
4.676
939401AE1-172 GEN
Solar/Wind Harmer
3.674
276901AD2-066 C O1
Solar/Wind Harmer
0.005
270032AE2-172
Solar/Wind Harmer
3.269
274872LEEDK;1U
Solar/Wind Harmer
0.003
971997AH1-543 GEN
Solar/Wind Harmer
2.559
276861AD2-134 GEN
Solar/Wind Harmer
0.087
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
24791305MDL-5G
Solar/Wind Harmer
0.001
957471AF2-041 GEN
Solar/Wind Harmer
14.477
959081AF2-199 GEN
Solar/Wind Harmer
4.826
971067AG2-660 GEN
Solar/Wind Harmer
1.609
274822ROCKFORD ;11
Adder
13.533
970825AG2-519 GEN
Solar/Wind Harmer
1.705
972235AH1-702 GEN1
Adder
1.734
970819AG2-516 GEN
Solar/Wind Harmer
5.74
970569AG2-363 GEN
Solar/Wind Harmer
14.338
971475AH1-234 GEN
Solar/Wind Harmer
2.315
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
6.304
274766LEE CO EC;7U
Adder
6.23
276903AD2-071 C
Solar/Wind Harmer
5.249
276158O29GEN2
Solar/Wind Harmer
0.001
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.002
274877BISHOP HL;1U
Solar/Wind Harmer
0.156
276726Z2-087_GEN
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
6.437
274854TWINGROVE;U2
Solar/Wind Harmer
0.002
972175AH1-670 GEN
Solar/Wind Harmer
3.624
963741AG1-226 GEN
Solar/Wind Harmer
10.327
942081AE2-220 GEN
Solar/Wind Harmer
0
24727205RPMNG3
50/50
3.292
971599AH1-298 GEN
50/50
10.333
24729505KEY G4
50/50
6.735
24653605MOTTVILLE
50/50
0.003
963791AG1-232 GEN
Solar/Wind Harmer
11.606
965041AG1-368 GEN
Solar/Wind Harmer
8.426
270071AF1-092 GEN
Solar/Wind Harmer
14.399
965051AG1-369 GEN
Solar/Wind Harmer
3.592
270024AE2-089 GEN
Solar/Wind Harmer
0.007
965101AG1-375 GEN
Solar/Wind Harmer
6.088
971771AH1-392 GEN
Solar/Wind Harmer
5.847
971347AH1-153 GEN
Solar/Wind Harmer
8.688
971619AH1-309 GEN
Solar/Wind Harmer
2.601
945581AF1-223 GEN
Solar/Wind Harmer
0
971769AH1-391 GEN
Solar/Wind Harmer
6.283
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971609AH1-304 GEN
Solar/Wind Harmer
0.89
274814UNIV PK N;0U
Adder
3.782
274807UNIV PK N;3U
Adder
3.774
274805UNIV PK N;1U
Adder
3.758
274811UNIV PK N;7U
Adder
3.75
270536AF1-215 GEN2
Solar/Wind Harmer
0.007
274775LINCOLN ;6U
Adder
6.292
274776LINCOLN ;7U
Adder
6.292
274777LINCOLN ;8U
Adder
6.292
972037AH1-567 GEN1
Adder
0.136
274827FISK ;RP
Adder
5.742
960591AF2-350 GEN
Solar/Wind Harmer
5.147
972227AH1-698 GEN1
Adder
1.919
274687WILL CNTY;4U
Adder
20.447
274687WILL CNTY;4U
Adder
20.447
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274675JOLIET 29;7U
Adder
22.401
274675JOLIET 29;7U
Adder
21.601
274728ELWOOD EC;5P
Adder
11.97
274731ELWOOD EC;2P
Adder
11.97
274733ELWOOD EC;3P
Adder
11.97
274735ELWOOD EC;4P
Adder
11.97
970833AG2-524 GEN
Solar/Wind Harmer
5.563
970833AG2-524 GEN
Solar/Wind Harmer
3.709
971611AH1-305 GEN
Solar/Wind Harmer
2.995
274746AC1-111 G10
Adder
4.021
274744AC1-111 GEN8
Adder
4.021
970289AG2-191 GEN
Solar/Wind Harmer
0.942
270594AE1-207 GEN
Solar/Wind Harmer
5.492
276868AE1-113 GEN
Solar/Wind Harmer
0.982
276882AE2-255 GEN
Solar/Wind Harmer
0.572
971177AH1-047 GEN
Solar/Wind Harmer
3.009
971411AH1-196 GEN
Solar/Wind Harmer
7.289
971675AH1-338 GEN
Solar/Wind Harmer
1.894
970115AG2-085 GEN
Solar/Wind Harmer
1.936
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
9.652
274823ROCKFORD ;21
Adder
13.435
276612AE2-035 GEN
Solar/Wind Harmer
0.001
926823AC1-168 GEN
Solar/Wind Harmer
0.811
970169AG2-114 GEN
Solar/Wind Harmer
4.764
971681AH1-341 GEN
Solar/Wind Harmer
7.643
971549AH1-272 GEN
Solar/Wind Harmer
9.793
961011AF2-392 GEN
Solar/Wind Harmer
2.754
957751AF2-069 GEN
Solar/Wind Harmer
0.154
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
3.19
247536S-71 GEN
Solar/Wind Harmer
0.173
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
1.654
276615X2-022 GEN
Solar/Wind Harmer
0.044
965911AG1-460 GEN
Solar/Wind Harmer
0.808
24728605AND G2
Adder
2.043
970773AG2-487 GEN
Solar/Wind Harmer
0.609
270445AC2-157 GEN2
Solar/Wind Harmer
0.001
970333AG2-219 GEN
Solar/Wind Harmer
2.215
246936BC-WTG1
Solar/Wind Helper
10.895
270462AD2-086
Solar/Wind Helper
3.714
270223U2-072_GEN1
Solar/Wind Helper
0.871
270578AF1-285 GEN2
Solar/Wind Helper
0.59
270391AF1-285 GEN3
Solar/Wind Helper
0.59
247522W1-056 GEN
Solar/Wind Helper
1.168
960841AF2-375 GEN
Solar/Wind Helper
1.175
270349AD2-093_GEN
Solar/Wind Helper
0.85
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
276655WTG1_EQ
Solar/Wind Harmer
0.002
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
4.828
941731AE2-173 GEN
Solar/Wind Harmer
3.831
946321AF1-296 GEN
Solar/Wind Harmer
2.545
963841AG1-237 GEN
Solar/Wind Harmer
1.949
270240V3-007_GEN2
Solar/Wind Harmer
0.001
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.156
276848AB2-070 GEN3
Solar/Wind Harmer
0.155
270543AE2-219 C
Solar/Wind Harmer
0.002
944221AF1-090 GEN
Solar/Wind Harmer
2.279
971029AG2-637 GEN
Solar/Wind Harmer
5.242
971673AH1-337 GEN
Solar/Wind Harmer
2.175
247607V1-011 GEN
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Helper
8.613
270317AD1-130_GEN
Solar/Wind Helper
4.113
966831AG1-554 GEN
Solar/Wind Helper
0.876
270284AF1-227 GEN1
Solar/Wind Helper
1.876
270286AF1-227 GEN2
Solar/Wind Helper
0.688
270287AF1-227 GEN3
Solar/Wind Helper
0.688
270499AE1-146 GEN
Solar/Wind Helper
1.952
945641AF1-229 GEN
Solar/Wind Helper
0.937
965091AG1-374 GEN
Solar/Wind Harmer
13.551
959611AF2-252 GEN
Solar/Wind Harmer
1.506
270437AC2-090 C
Solar/Wind Harmer
0.002
276686W4-005 GEN3
Solar/Wind Harmer
0.001
276668AB2-070 GEN1
Solar/Wind Harmer
0.156
971993AH1-541 GEN
Solar/Wind Harmer
1.971
276621W2-048 GEN
Solar/Wind Harmer
0.211
276838X2-022 GEN2
Solar/Wind Harmer
0.236
942481AE2-261 GEN
Solar/Wind Harmer
12.085
970193AG2-126 GEN
Solar/Wind Harmer
5.861
270404AC1-167 GEN
Solar/Wind Harmer
0.002
270258AD1-119 GEN
Solar/Wind Harmer
0.001
24728705AND G3
Adder
4.272
24728505AND G1
Adder
2.043
270356AE2-297 GEN
Solar/Wind Harmer
0.005
970243AG2-164 GEN
Solar/Wind Harmer
1.812
970519AG2-331 GEN
Solar/Wind Harmer
8.054
970699AG2-449 GEN
Solar/Wind Harmer
0.774
270485AE1-090_GEN
Solar/Wind Helper
0.323
942871AE2-306 GEN
Solar/Wind Helper
0.443
270541AE2-072 C
Solar/Wind Helper
0.932
970615AG2-402 GEN
50/50
4.588
24729405KEY G3
50/50
0.368
24729305KEY G2
50/50
0.361
24729205KEY G1
50/50
0.36
247620Y3-023
50/50
0.463
970611AG2-400 GEN
Solar/Wind Harmer
13.763
970627AG2-408 GEN
Solar/Wind Harmer
4.129
942221AE2-234 GEN
Solar/Wind Harmer
0.034
944541AF1-119 GEN
Solar/Wind Harmer
0.42
960971AF2-388 GEN
Solar/Wind Harmer
3.679
270216AD2-079_GEN
Solar/Wind Harmer
0.001
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
11.557
961051AF2-396 GEN
Solar/Wind Harmer
7.705
270526AF1-158 GEN
Solar/Wind Harmer
0.007
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
6.887
965791AG1-447 GEN
Solar/Wind Harmer
5.051
270599AE1-208 GEN
Solar/Wind Harmer
4.993
270031AE2-169
Solar/Wind Harmer
2.996
970321AG2-212 GEN
Solar/Wind Harmer
2.307
274808UNIV PK N;4U
Adder
3.733
274770LINCOLN ;1U
Adder
6.292
274771LINCOLN ;2U
Adder
6.292
274803UNIV PARK;6U
Adder
4.319
274888KELLY CRK;1U
Solar/Wind Harmer
0.302
274887GEN-1.85
Solar/Wind Harmer
0.136
276843GEN-1.7
Solar/Wind Harmer
0.167
958011AF2-095 GEN
Solar/Wind Harmer
7.412
972259AH1-714 GEN
Adder
13.99
274674JOLIET 9 ;6U
Adder
11.217
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
971573AH1-285 GEN
Solar/Wind Harmer
0.931
958481AF2-142 GEN
Solar/Wind Harmer
7.482
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.675
274695ROCKY RD ;2P
Adder
7.922
274693ROCKY RD ;1P
Adder
7.844
274697ROCKY RD ;3P
Adder
2.152
274696ROCKY RD ;4P
Adder
8.109
274683WAUKEGAN ;8U
Adder
14.968
274683WAUKEGAN ;8U
Adder
12.617
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
962691AG1-118 GEN
Solar/Wind Harmer
14.776
958491AF2-143 GEN
Solar/Wind Harmer
7.388
970921AG2-575 GEN
Solar/Wind Harmer
4.913
970921AG2-575 GEN
Solar/Wind Harmer
1.638
971613AH1-306 GEN
Solar/Wind Harmer
2.354
274879MINONK ;1U
Solar/Wind Harmer
0.207
942991AE2-321 GEN
Solar/Wind Harmer
5.451
971333AH1-146 GEN
Solar/Wind Harmer
9.71
971335AH1-147 GEN
Solar/Wind Harmer
9.71
960441AF2-335 GEN
Solar/Wind Harmer
4.841
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
971341AH1-150 GEN
Solar/Wind Harmer
9.652
971343AH1-151 GEN
Solar/Wind Harmer
9.652
970825AG2-519 GEN
Solar/Wind Harmer
5.324
274856ECOGROVE ;U1
Solar/Wind Harmer
0.113
276611AD2-172 GEN
Solar/Wind Harmer
0.001
938861AE1-114 GEN
Solar/Wind Harmer
2.689
274764LEE CO EC;5U
Adder
6.319
274765LEE CO EC;6U
Adder
6.319
274762LEE CO EC;3U
Adder
6.304
274763LEE CO EC;4U
Adder
6.245
276603SUBLETTE C
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.354
270201AC2-176 GEN
Solar/Wind Harmer
0.001
972267AH1-718 GEN
Adder
2.793
276741O09 GEN1
Solar/Wind Harmer
0.166
276708O09 GEN2
Solar/Wind Harmer
0.166
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.183
276646AC1-214 GEN2
Solar/Wind Harmer
0.183
966841AG1-555 GEN
Solar/Wind Harmer
0.525
276782AC1-033 GEN
Solar/Wind Harmer
0.001
247621Y3-024
Adder
0.16
960611AF2-352 GEN
Solar/Wind Harmer
1.506
970241AG2-163 GEN
Solar/Wind Harmer
2.545
24379505HDWTR1G C
Solar/Wind Harmer
0.001
270209AC1-174_GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
270383AD1-128 GEN
Solar/Wind Harmer
0.002
276916AD2-100_GEN
Solar/Wind Harmer
8.413
276911AD2-131_GEN
Solar/Wind Harmer
0.554
970883AG2-550 GEN
Solar/Wind Harmer
3.912
970885AG2-551 GEN
Solar/Wind Harmer
1.304
945391AF1-204 GEN
Solar/Wind Harmer
4.152
970623AG2-406 GEN
Solar/Wind Harmer
0.681
270444AC2-157 GEN1
Solar/Wind Harmer
0.001
971587AH1-292 GEN
Solar/Wind Harmer
2.427
270007AE1-245 C
Solar/Wind Harmer
0.001
970239AG2-162 GEN
Solar/Wind Harmer
0.774
246938BC-WTG3
Solar/Wind Helper
11.083
246937BC-WTG2
Solar/Wind Helper
10.895
270224U2-072_GEN2
Solar/Wind Helper
0.871
270227U2-072_GEN3
Solar/Wind Helper
0.871
270228U2-072_GEN4
Solar/Wind Helper
0.871
270231U2-072_GEN5
Solar/Wind Helper
0.871
270471AD2-092_GEN
Solar/Wind Helper
0.85
253378AE2-206_GEN
Solar/Wind Helper
0.684
276820AF1-078_GEN
Solar/Wind Helper
0.319
241960AC2-195 GEN
Solar/Wind Helper
0.69
944201AF1-088_MTX
Adder
55.165
957141AF2-008_MTX
Adder
17.696
990792J1392
External Queue
5.474584102630615
990497J1323
External Queue
1.5914489030838013
LAGNLTFEXP_LAGN->PJM
CLTF
5.694
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.439
TVALTFEXP_TVA->PJM
CLTF
2.27
CBM West 2LTFEXP_CBM-W2->PJM
CBM
49.944
NYPJM->LTFIMP_NY
CLTF
1.265
LGEELTFEXP_LGEE->PJM
CLTF
1.782
WECLTFEXP_WEC->PJM
CLTF
2.624
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.056
AG2-052LTFEXP_AG2-052->PJM
LTF
0.17
AH1-155LTFEXP_AH1-155->PJM
LTF
0.255
CBM West 1LTFEXP_CBM-W1->PJM
CBM
69.309
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.744
MECLTFEXP_MEC->PJM
CLTF
9.656
SIGELTFEXP_SIGE->PJM
CLTF
0.197

Details for AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P7-1_#11087___SRT-A-1


Base Case Flowgate

Area:AEP
Facility Description:
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#11087___SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:101.08 %
Rating:1868.0 MVA
Rating Type:B
MVA to Mitigate:1888.24
MW Contribution:8.63
Bus #Bus NameTypeMW Contribution
24727205RPMNG3
50/50
3.181
24729505KEY G4
50/50
7.146
971599AH1-298 GEN
50/50
8.543
965041AG1-368 GEN
Solar/Wind Harmer
10.544
958711AF2-162 GEN
Solar/Wind Harmer
1.05
965101AG1-375 GEN
Solar/Wind Harmer
10.379
945581AF1-223 GEN
Solar/Wind Harmer
4.707
963791AG1-232 GEN
Solar/Wind Harmer
13.526
965051AG1-369 GEN
Solar/Wind Harmer
4.453
270071AF1-092 GEN
Solar/Wind Harmer
12.823
270024AE2-089 GEN
Solar/Wind Harmer
2.79
971771AH1-392 GEN
Solar/Wind Harmer
5.331
944161AF1-084 GEN
Solar/Wind Harmer
1.251
971347AH1-153 GEN
Solar/Wind Harmer
8.439
971769AH1-391 GEN
Solar/Wind Harmer
5.574
960681AF2-359 GEN
Solar/Wind Harmer
2.025
270536AF1-215 GEN2
Solar/Wind Harmer
2.284
274814UNIV PK N;0U
Adder
2.515
965431AG1-411 GEN
50/50
44.207
24727105RPMNG2
50/50
3.208
970583AG2-370 GEN
50/50
2.452
959331AF2-224 GEN
Solar/Wind Harmer
18.046
965021AG1-366 GEN
Solar/Wind Harmer
4.197
944531AF1-118 GEN
Solar/Wind Harmer
36.332
970031AG2-029 GEN
Solar/Wind Harmer
30.014
270043AE2-236 GEN
Solar/Wind Harmer
5.233
270191TR4_S_V150
Solar/Wind Harmer
2.675
270247TR4_N_V136
Solar/Wind Harmer
0.759
247643Z2-116 C
Solar/Wind Harmer
0.045
945111AF1-176 GEN
Solar/Wind Harmer
3.46
971617AH1-308 GEN
Solar/Wind Harmer
3.456
24642205MAYFLWER
Adder
0.37
970349AG2-230 GEN
Solar/Wind Harmer
8.439
24441205WTRV SLR C
Solar/Wind Harmer
0.073
247604X1-042
Adder
0.215
972231SS25-0005
Solar/Wind Harmer
4.809
972181SS23-001
Solar/Wind Harmer
3.005
274752CRETE EC ;2U
Adder
2.477
274753CRETE EC ;3U
Adder
2.477
270535AF1-215 GEN1
Solar/Wind Harmer
2.284
274724RIVER EC ;11
Adder
8.902
964401AG1-302 GEN
Solar/Wind Harmer
4.478
274802UNIV PARK;5U
Adder
2.857
274826FISK ;BP
Adder
5.355
274772LINCOLN ;3U
Adder
3.025
274800UNIV PARK;3U
Adder
2.844
972038AH1-567 GEN2
Adder
0.178
276772AC2-154 GEN
Solar/Wind Harmer
1.357
276806AD2-047 C O1
Solar/Wind Harmer
5.204
970941AG2-585 GEN
Solar/Wind Harmer
6.081
959141AF2-205 GEN
Solar/Wind Harmer
2.935
970513AG2-328 GEN
Solar/Wind Harmer
8.67
970517AG2-330 GEN
Solar/Wind Harmer
7.863
972228AH1-698 GEN2
Adder
1.793
274676JOLIET 29;8U
Adder
14.207
970707AG2-453 GEN
Solar/Wind Harmer
13.43
276897AD1-100 C
Solar/Wind Harmer
13.896
939351AE1-166 GEN
Solar/Wind Harmer
2.839
276893AG1-478 C
Solar/Wind Harmer
0.2
274729ELWOOD EC;1P
Adder
7.866
274730ELWOOD EC;6P
Adder
7.866
274807UNIV PK N;3U
Adder
2.51
274805UNIV PK N;1U
Adder
2.499
274811UNIV PK N;7U
Adder
2.494
972037AH1-567 GEN1
Adder
0.09
274827FISK ;RP
Adder
3.795
958391AF2-133 GEN
Solar/Wind Harmer
4.436
274775LINCOLN ;6U
Adder
3.025
274776LINCOLN ;7U
Adder
3.025
274777LINCOLN ;8U
Adder
3.025
960591AF2-350 GEN
Solar/Wind Harmer
4.865
972227AH1-698 GEN1
Adder
1.262
274687WILL CNTY;4U
Adder
13.462
274687WILL CNTY;4U
Adder
13.462
274675JOLIET 29;7U
Adder
14.733
274675JOLIET 29;7U
Adder
14.207
274731ELWOOD EC;2P
Adder
7.866
274733ELWOOD EC;3P
Adder
7.866
274735ELWOOD EC;4P
Adder
7.866
274728ELWOOD EC;5P
Adder
7.866
970833AG2-524 GEN
Solar/Wind Harmer
4.145
970833AG2-524 GEN
Solar/Wind Harmer
1.928
274746AC1-111 G10
Adder
2.631
274744AC1-111 GEN8
Adder
2.631
971549AH1-272 GEN
Solar/Wind Harmer
8.634
276868AE1-113 GEN
Solar/Wind Harmer
4.637
276882AE2-255 GEN
Solar/Wind Harmer
1.546
24690905MDL-1G C
Solar/Wind Harmer
3.673
270180AB1-006 GEN1
Solar/Wind Harmer
3.29
946581AF1-322 GEN
Solar/Wind Harmer
4.68
24691005MDL-2G C
Solar/Wind Harmer
1.692
24697605MDL-3G C
Solar/Wind Harmer
1.687
24697905MDL-4G C
Solar/Wind Harmer
1.05
270181AB1-006 GEN2
Solar/Wind Harmer
0.327
274823ROCKFORD ;21
Adder
8.751
957201AF2-014 GEN
Solar/Wind Helper
8.798
270317AD1-130_GEN
Solar/Wind Helper
3.912
966831AG1-554 GEN
Solar/Wind Helper
0.861
270499AE1-146 GEN
Solar/Wind Helper
1.974
270284AF1-227 GEN1
Solar/Wind Helper
1.548
270286AF1-227 GEN2
Solar/Wind Helper
0.568
270287AF1-227 GEN3
Solar/Wind Helper
0.568
945641AF1-229 GEN
Solar/Wind Helper
0.917
970615AG2-402 GEN
50/50
4.197
24729405KEY G3
50/50
0.39
24729305KEY G2
50/50
0.383
24729205KEY G1
50/50
0.382
970611AG2-400 GEN
Solar/Wind Harmer
18.046
944541AF1-119 GEN
Solar/Wind Harmer
4.347
960971AF2-388 GEN
Solar/Wind Harmer
11.345
247620Y3-023
Adder
0.331
942221AE2-234 GEN
Solar/Wind Harmer
0.505
270216AD2-079_GEN
Solar/Wind Harmer
0.39
960981AF2-389 GEN
Solar/Wind Harmer
0.9
957891AF2-083 GEN
Solar/Wind Harmer
2.004
961051AF2-396 GEN
Solar/Wind Harmer
9.367
961051AF2-396 GEN
Solar/Wind Harmer
4.357
270526AF1-158 GEN
Solar/Wind Harmer
2.564
24441505OLIV SLR
Solar/Wind Harmer
0.075
965681AG1-436 GEN
Solar/Wind Harmer
6.7
965791AG1-447 GEN
Solar/Wind Harmer
3.428
274808UNIV PK N;4U
Adder
2.483
274803UNIV PARK;6U
Adder
2.857
274770LINCOLN ;1U
Adder
3.025
274771LINCOLN ;2U
Adder
3.025
274888KELLY CRK;1U
Solar/Wind Harmer
2.872
274887GEN-1.85
Solar/Wind Harmer
2.593
276843GEN-1.7
Solar/Wind Harmer
0.279
958011AF2-095 GEN
Solar/Wind Harmer
7.005
970321AG2-212 GEN
Solar/Wind Harmer
8.67
972259AH1-714 GEN
Adder
9.178
274674JOLIET 9 ;6U
Adder
7.371
274847GR RIDGE ;BU
Solar/Wind Harmer
2.399
945421AF1-207 GEN
Solar/Wind Harmer
6.59
957841AF2-078 GEN
Solar/Wind Harmer
2.836
958481AF2-142 GEN
Solar/Wind Harmer
7.033
274861TOP CROP ;1U
Solar/Wind Harmer
2.84
274862TOP CROP ;2U
Solar/Wind Harmer
2.372
971573AH1-285 GEN
Solar/Wind Harmer
4.023
274696ROCKY RD ;4P
Adder
5.302
274695ROCKY RD ;2P
Adder
5.18
274693ROCKY RD ;1P
Adder
5.129
274697ROCKY RD ;3P
Adder
1.407
274683WAUKEGAN ;8U
Adder
9.793
274683WAUKEGAN ;8U
Adder
8.255
958491AF2-143 GEN
Solar/Wind Harmer
6.928
962691AG1-118 GEN
Solar/Wind Harmer
13.825
970921AG2-575 GEN
Solar/Wind Harmer
4.596
970921AG2-575 GEN
Solar/Wind Harmer
1.069
274879MINONK ;1U
Solar/Wind Harmer
3.091
274764LEE CO EC;5U
Adder
4.106
274765LEE CO EC;6U
Adder
4.106
274762LEE CO EC;3U
Adder
4.096
274763LEE CO EC;4U
Adder
4.057
972267AH1-718 GEN
Adder
1.812
246938BC-WTG3
Solar/Wind Helper
11.321
246937BC-WTG2
Solar/Wind Helper
11.129
270224U2-072_GEN2
Solar/Wind Helper
0.811
270227U2-072_GEN3
Solar/Wind Helper
0.811
270228U2-072_GEN4
Solar/Wind Helper
0.811
270231U2-072_GEN5
Solar/Wind Helper
0.811
253378AE2-206_GEN
Solar/Wind Helper
0.691
276820AF1-078_GEN
Solar/Wind Helper
0.323
942991AE2-321 GEN
Solar/Wind Harmer
3.656
274734ELWOOD EC;8P
Adder
7.866
274736ELWOOD EC;9P
Adder
7.866
943121AE2-341 GEN
Solar/Wind Harmer
7.058
943591AF1-030 GEN
Solar/Wind Harmer
4.706
276694AA1-018 GEN2
Solar/Wind Harmer
2.959
274682WAUKEGAN ;7U
Adder
8.364
276805AD2-038 GEN
Solar/Wind Harmer
2.369
274872LEEDK;1U
Solar/Wind Harmer
0.117
24755605MDL-5G
Solar/Wind Harmer
1.103
970781AG2-491 GEN
Solar/Wind Harmer
4.574
972236AH1-702 GEN2
Adder
0.982
274760LEE CO EC;1U
Adder
4.096
274767LEE CO EC;8U
Adder
4.048
270485AE1-090_GEN
Solar/Wind Helper
0.307
942871AE2-306 GEN
Solar/Wind Helper
0.412
270541AE2-072 C
Solar/Wind Helper
1.012
24727005RPMNG1
50/50
3.197
960861AF2-377 GEN
50/50
2.075
965421AG1-410 GEN
Solar/Wind Harmer
114.053
965011AG1-365 GEN
Solar/Wind Harmer
18.046
958861AF2-177 GEN
Solar/Wind Harmer
11.345
965651AG1-433 GEN
Solar/Wind Harmer
5.673
945371AF1-202 GEN
Solar/Wind Harmer
7.242
247521TR3_G114
Solar/Wind Harmer
2.998
270246TR4_N_V150
Solar/Wind Harmer
0.759
270063AE2-323 C
Solar/Wind Harmer
1.865
944231AF1-091 GEN
Solar/Wind Harmer
3.158
24695305TIMB G C
Solar/Wind Harmer
4.23
24639705ELKHART HY
Adder
0.105
945111AF1-176 GEN
Solar/Wind Harmer
10.917
270505AE1-170 C O1
Solar/Wind Harmer
8.812
270449AD2-020 GEN
Solar/Wind Harmer
1.618
943021AE2-325 GEN
Solar/Wind Harmer
2.102
970373AG2-245 GEN
Solar/Wind Harmer
10.773
274751CRETE EC ;1U
Adder
2.477
274754CRETE EC ;4U
Adder
2.477
274723RIVER EC ;12
Adder
9.014
270055AF2-134 C O1
Solar/Wind Harmer
1.522
274812UNIV PK N;8U
Adder
2.494
276164X3-005 C
Solar/Wind Harmer
0.349
958381AF2-132 GEN
Solar/Wind Harmer
4.478
964861AG1-349 GEN
Solar/Wind Harmer
3.873
971917AH1-482 GEN
Solar/Wind Harmer
4.469
972207SS24-0001
Solar/Wind Harmer
10.754
274773LINCOLN ;4U
Adder
3.025
274774LINCOLN ;5U
Adder
3.025
274801UNIV PARK;4U
Adder
2.844
276776AD2-060 GEN
Solar/Wind Harmer
0.206
970245AG2-165 GEN
Solar/Wind Harmer
8.67
940581AE2-045 GEN
Solar/Wind Harmer
4.907
971605AH1-302 GEN
Solar/Wind Harmer
4.196
274676JOLIET 29;8U
Adder
14.733
941551AE2-152 GEN
Solar/Wind Harmer
2.172
274674JOLIET 9 ;6U
Adder
7.371
274732ELWOOD EC;7P
Adder
7.866
274871GR RIDGE ;2U
Solar/Wind Harmer
3.648
274745AC1-111 GEN9
Adder
2.631
276691AA1-018 GEN1
Solar/Wind Harmer
0.218
274682WAUKEGAN ;7U
Adder
8.364
274828WAUKEGAN ;BP
Adder
5.133
960751AF2-366 GEN
Solar/Wind Harmer
1.319
962781AG1-127 GEN
Solar/Wind Harmer
4.371
276901AD2-066 C O1
Solar/Wind Harmer
1.614
274872LEEDK;1U
Solar/Wind Harmer
3.765
939401AE1-172 GEN
Solar/Wind Harmer
6.377
24791305MDL-5G
Solar/Wind Harmer
1.103
274822ROCKFORD ;11
Adder
8.814
972235AH1-702 GEN1
Adder
1.129
274761LEE CO EC;2U
Adder
4.096
274766LEE CO EC;7U
Adder
4.048
246936BC-WTG1
Solar/Wind Helper
11.129
270462AD2-086
Solar/Wind Helper
3.532
270223U2-072_GEN1
Solar/Wind Helper
0.811
270578AF1-285 GEN2
Solar/Wind Helper
0.549
270391AF1-285 GEN3
Solar/Wind Helper
0.549
247522W1-056 GEN
Solar/Wind Helper
1.16
960841AF2-375 GEN
Solar/Wind Helper
1.186
990792J1392
External Queue
5.376169204711914
990497J1323
External Queue
1.5628399848937988
LAGNLTFEXP_LAGN->PJM
CLTF
3.419
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.355
TVALTFEXP_TVA->PJM
CLTF
1.316
CBM West 2LTFEXP_CBM-W2->PJM
CBM
29.187
NYPJM->LTFIMP_NY
CLTF
0.799
LGEELTFEXP_LGEE->PJM
CLTF
0.799
WECLTFEXP_WEC->PJM
CLTF
1.71
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.01
AG2-052LTFEXP_AG2-052->PJM
LTF
0.113
AH1-155LTFEXP_AH1-155->PJM
LTF
0.169
CBM West 1LTFEXP_CBM-W1->PJM
CBM
41.914
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.838
MECLTFEXP_MEC->PJM
CLTF
6.152
SIGELTFEXP_SIGE->PJM
CLTF
0.101

Details for AG2-148 TP-02GALION 345.0 kV Ckt 1 line l/o ATSI_P7-1_TE-345-027A_SRT-A


Base Case Flowgate

Area:AEP/ATSI
Facility Description:
AG2-148 TP-02GALION 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P7-1_TE-345-027A_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:106.19 %
Rating:1308.0 MVA
Rating Type:B
MVA to Mitigate:1388.99
MW Contribution:9.06
Bus #Bus NameTypeMW Contribution
23888702TROY G3
50/50
1.547
972253AH1-711 GEN
50/50
47.255
24189902OREGON_CT2
50/50
2.124
23856402BAYSG1
50/50
1.067
23920202STRYCT
50/50
1.652
970515AG2-329 GEN
Solar/Wind Harmer
65.578
270361_3
Solar/Wind Harmer
11.019
960841AF2-375 GEN
Solar/Wind Harmer
4.812
241858AF1-205_GEN
Solar/Wind Harmer
4.763
241808AF1-120 C
Solar/Wind Harmer
1.035
241840AF1-064_GEN
Solar/Wind Harmer
1.239
247522W1-056 GEN
Solar/Wind Harmer
2.175
23906502RICHG2&3
Adder
1.164
972301AH1-735 GEN
Adder
5.82
23906402RICHG1
Adder
1.164
246936BC-WTG1
Solar/Wind Harmer
2.02
270489AE1-102 GEN1
Solar/Wind Harmer
0.671
965421AG1-410 GEN
Solar/Wind Harmer
15.09
944231AF1-091 GEN
Solar/Wind Harmer
1.879
270428AC2-015 C
Solar/Wind Harmer
2.682
241807AE2-176_GEN
Solar/Wind Harmer
1.803
24695305TIMB G C
Solar/Wind Harmer
2.462
270462AD2-086
Solar/Wind Harmer
3.011
958961AF2-187 GEN
Solar/Wind Helper
1.304
23888502TROY G1
50/50
1.547
23888602TROY G2
50/50
1.547
972211AH1-690 GEN
50/50
228.604
23867002DVBSG1
50/50
7.841
945641AF1-229 GEN
Solar/Wind Harmer
11.095
970817AG2-515 GEN
Solar/Wind Harmer
12.936
270499AE1-146 GEN
Solar/Wind Harmer
2.975
945411AF1-206 GEN
Solar/Wind Harmer
6.936
270297AD1-101 GEN
Solar/Wind Harmer
1.752
966831AG1-554 GEN
Solar/Wind Harmer
0.725
971989AH1-539 GEN
Solar/Wind Harmer
7.841
957201AF2-014 GEN
Solar/Wind Harmer
2.341
270435AC2-044 GEN
Solar/Wind Harmer
1.032
247607V1-011 GEN
Solar/Wind Harmer
1.952
971549AH1-272 GEN
Solar/Wind Harmer
9.056
270302AB2-170 GEN
Solar/Wind Harmer
3.619
270317AD1-130_GEN
Solar/Wind Harmer
1.387
23929302BS-PKR
50/50
1.879
970217AG2-149 GEN
Solar/Wind Harmer
144.609
270575GUS2 35KV
Solar/Wind Harmer
12.982
241832AE2-181_GEN
Solar/Wind Harmer
1.691
958321AF2-126 GEN
Solar/Wind Harmer
1.328
23906502RICHG2&3
Adder
1.164
270541AE2-072 C
Solar/Wind Harmer
4.235
270588AE1-091_GEN
Solar/Wind Harmer
7.004
270044AE2-322 C
Solar/Wind Harmer
0.704
270404AC1-167 GEN
Solar/Wind Harmer
0.586
270491AE1-102 GEN2
Solar/Wind Harmer
0.671
270258AD1-119 GEN
Solar/Wind Harmer
1.414
958091AF2-103 GEN
Solar/Wind Harmer
0.08
270485AE1-090_GEN
Solar/Wind Harmer
0.262
23888802TROY G4
50/50
1.547
24190002OREGON_ST1
50/50
2.858
24189802OREGON_CT1
50/50
2.168
971677AH1-339 GEN
Solar/Wind Harmer
12.459
241996AE2-282_GEN
Solar/Wind Harmer
1.857
246938BC-WTG3
Solar/Wind Harmer
2.055
246937BC-WTG2
Solar/Wind Harmer
2.02
270007AE1-245 C
Solar/Wind Harmer
2.929
942801AE2-298 GEN
Solar/Wind Harmer
0.723
241960AC2-195 GEN
Solar/Wind Helper
2.638
991177J1571 G
External Queue
14.578453063964844
990527J1329
External Queue
1.7149295806884766
990142J1224
External Queue
12.53613567352295
991182J1586 G
External Queue
23.483379364013672
LAGNLTFEXP_LAGN->PJM
CLTF
1.487
TVALTFEXP_TVA->PJM
CLTF
0.529
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.438
NYPJM->LTFIMP_NY
CLTF
0.701
LGEELTFEXP_LGEE->PJM
CLTF
0.514
WECLTFEXP_WEC->PJM
CLTF
0.87
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.264
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.125
CBM West 1LTFEXP_CBM-W1->PJM
CBM
61.62
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.137
MECLTFEXP_MEC->PJM
CLTF
3.106
SIGELTFEXP_SIGE->PJM
CLTF
0.058

Details for AG2-148 TP-02GALION 345.0 kV Ckt 1 line l/o ATSI_P7-1_TE-345-030_SRT-A


Base Case Flowgate

Area:AEP/ATSI
Facility Description:
AG2-148 TP-02GALION 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P7-1_TE-345-030_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:105.3 %
Rating:1308.0 MVA
Rating Type:B
MVA to Mitigate:1377.33
MW Contribution:8.87
Bus #Bus NameTypeMW Contribution
23888702TROY G3
50/50
1.513
972253AH1-711 GEN
50/50
46.215
24189902OREGON_CT2
50/50
2.065
23856402BAYSG1
50/50
1.078
23920202STRYCT
50/50
1.641
23860302FRMENG 3
50/50
2.311
970515AG2-329 GEN
Solar/Wind Harmer
65.528
270361_3
Solar/Wind Harmer
11.201
960841AF2-375 GEN
Solar/Wind Harmer
4.888
23888502TROY G1
50/50
1.513
23888602TROY G2
50/50
1.513
972211AH1-690 GEN
50/50
222.237
23867002DVBSG1
50/50
7.301
23860102FRMENG 1
50/50
1.131
23860202FRMENG 2
50/50
1.131
945641AF1-229 GEN
Solar/Wind Harmer
11.066
970817AG2-515 GEN
Solar/Wind Harmer
12.715
241886AC2-103 GEN2
Solar/Wind Harmer
7.319
270499AE1-146 GEN
Solar/Wind Harmer
3.019
945411AF1-206 GEN
Solar/Wind Harmer
6.885
24191202EL_AA1-006
Adder
0.154
270297AD1-101 GEN
Solar/Wind Harmer
1.749
966831AG1-554 GEN
Solar/Wind Harmer
0.732
971989AH1-539 GEN
Solar/Wind Harmer
7.919
957201AF2-014 GEN
Solar/Wind Harmer
2.32
270435AC2-044 GEN
Solar/Wind Harmer
1.023
247607V1-011 GEN
Solar/Wind Harmer
1.939
971549AH1-272 GEN
Solar/Wind Harmer
8.874
23929302BS-PKR
50/50
1.897
970217AG2-149 GEN
Solar/Wind Harmer
144.498
270575GUS2 35KV
Solar/Wind Harmer
13.195
241832AE2-181_GEN
Solar/Wind Harmer
1.678
958321AF2-126 GEN
Solar/Wind Harmer
1.33
23906502RICHG2&3
Adder
1.158
270541AE2-072 C
Solar/Wind Harmer
4.235
270588AE1-091_GEN
Solar/Wind Harmer
7.042
270044AE2-322 C
Solar/Wind Harmer
0.699
270404AC1-167 GEN
Solar/Wind Harmer
0.582
270491AE1-102 GEN2
Solar/Wind Harmer
0.665
270258AD1-119 GEN
Solar/Wind Harmer
1.404
958091AF2-103 GEN
Solar/Wind Harmer
0.079
23888802TROY G4
50/50
1.513
24190002OREGON_ST1
50/50
2.778
24189802OREGON_CT1
50/50
2.107
971677AH1-339 GEN
Solar/Wind Harmer
12.57
241996AE2-282_GEN
Solar/Wind Harmer
1.843
246938BC-WTG3
Solar/Wind Harmer
2.036
246937BC-WTG2
Solar/Wind Harmer
2.001
270007AE1-245 C
Solar/Wind Harmer
2.91
942801AE2-298 GEN
Solar/Wind Harmer
0.718
241960AC2-195 GEN
Solar/Wind Helper
2.635
241885AC2-103 GEN1
Solar/Wind Harmer
7.319
241858AF1-205_GEN
Solar/Wind Harmer
4.732
241808AF1-120 C
Solar/Wind Harmer
1.028
241840AF1-064_GEN
Solar/Wind Harmer
1.24
247522W1-056 GEN
Solar/Wind Harmer
2.197
23906502RICHG2&3
Adder
1.158
972301AH1-735 GEN
Adder
5.785
23906402RICHG1
Adder
1.157
241807AE2-176_GEN
Solar/Wind Harmer
3.394
270428AC2-015 C
Solar/Wind Harmer
2.976
246936BC-WTG1
Solar/Wind Harmer
2.001
270489AE1-102 GEN1
Solar/Wind Harmer
0.665
965421AG1-410 GEN
Solar/Wind Harmer
14.948
944231AF1-091 GEN
Solar/Wind Harmer
1.859
24695305TIMB G C
Solar/Wind Harmer
2.44
958961AF2-187 GEN
Solar/Wind Helper
1.26
991177J1571 G
External Queue
14.350388526916504
990527J1329
External Queue
1.6826814413070679
990142J1224
External Queue
12.300400733947754
991182J1586 G
External Queue
23.031686782836914
LAGNLTFEXP_LAGN->PJM
CLTF
1.435
TVALTFEXP_TVA->PJM
CLTF
0.506
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.02
NYPJM->LTFIMP_NY
CLTF
0.692
LGEELTFEXP_LGEE->PJM
CLTF
0.496
WECLTFEXP_WEC->PJM
CLTF
0.851
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.269
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.129
CBM West 1LTFEXP_CBM-W1->PJM
CBM
60.282
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.046
MECLTFEXP_MEC->PJM
CLTF
3.034
SIGELTFEXP_SIGE->PJM
CLTF
0.057

Details for AH1-690 TP-02BAY SH 345.0 kV Ckt 2 line l/o ATSI_P1-2_TE-345-606_SRT-A-1


Base Case Flowgate

Area:ATSI
Facility Description:
AH1-690 TP-02BAY SH 345.0 kV Ckt 2 line
Contingency Name:
ATSI_P1-2_TE-345-606_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.39 %
Rating:1774.0 MVA
Rating Type:B
MVA to Mitigate:1816.36
MW Contribution:7.71
Bus #Bus NameTypeMW Contribution
24189902OREGON_CT2
50/50
6.637
970515AG2-329 GEN
Solar/Wind Harmer
8.909
241885AC2-103 GEN1
Solar/Wind Helper
3.47
241807AE2-176_GEN
Solar/Wind Helper
1.924
241808AF1-120 C
Solar/Wind Helper
0.366
241840AF1-064_GEN
Solar/Wind Helper
0.496
247604X1-042
50/50
0.205
970217AG2-149 GEN
Solar/Wind Harmer
2.97
24441205WTRV SLR C
Solar/Wind Harmer
0
241832AE2-181_GEN
Solar/Wind Helper
0.274
972211AH1-690 GEN
50/50
717.964
945641AF1-229 GEN
Solar/Wind Harmer
0.001
971549AH1-272 GEN
Solar/Wind Harmer
7.71
241886AC2-103 GEN2
Solar/Wind Helper
3.47
945411AF1-206 GEN
Solar/Wind Helper
1.24
24190002OREGON_ST1
50/50
8.93
24189802OREGON_CT1
50/50
6.774
241996AE2-282_GEN
Solar/Wind Helper
0.654
LAGNLTFEXP_LAGN->PJM
CLTF
3.603
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.003
TVALTFEXP_TVA->PJM
CLTF
1.642
CPLELTFEXP_CPLE->PJM
CLTF
0.432
CBM West 2LTFEXP_CBM-W2->PJM
CBM
28.258
NYPJM->LTFIMP_NY
CLTF
1.135
LGEELTFEXP_LGEE->PJM
CLTF
1.403
WECLTFEXP_WEC->PJM
CLTF
1.177
AG2-052LTFEXP_AG2-052->PJM
LTF
0.076
AH1-155LTFEXP_AH1-155->PJM
LTF
0.113
CBM West 1LTFEXP_CBM-W1->PJM
CBM
81.793
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.436
MECLTFEXP_MEC->PJM
CLTF
4.596
SIGELTFEXP_SIGE->PJM
CLTF
0.118

Details for AH1-690 TP-02BAY SH 345.0 kV Ckt 2 line l/o ATSI_P2-3_TE-345-002_SRT-SL


Base Case Flowgate

Area:ATSI
Facility Description:
AH1-690 TP-02BAY SH 345.0 kV Ckt 2 line
Contingency Name:
ATSI_P2-3_TE-345-002_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.27 %
Rating:1720.0 MVA
Rating Type:B
MVA to Mitigate:1741.77
MW Contribution:9.87
Bus #Bus NameTypeMW Contribution
970217AG2-149 GEN
Solar/Wind Harmer
15.369
247604X1-042
Adder
0.193
24441205WTRV SLR C
Solar/Wind Harmer
0.061
24189902OREGON_CT2
50/50
6.343
970515AG2-329 GEN
Solar/Wind Harmer
6.97
241885AC2-103 GEN1
Solar/Wind Helper
3.545
241807AE2-176_GEN
Solar/Wind Helper
1.782
24190002OREGON_ST1
50/50
8.534
24189802OREGON_CT1
50/50
6.473
972211AH1-690 GEN
50/50
686.076
945641AF1-229 GEN
Solar/Wind Harmer
2.405
971549AH1-272 GEN
Solar/Wind Harmer
9.865
944161AF1-084 GEN
Solar/Wind Harmer
0.95
241886AC2-103 GEN2
Solar/Wind Helper
3.545
990527J1329
External Queue
1.0117015838623047
990142J1224
External Queue
7.395538330078125
LAGNLTFEXP_LAGN->PJM
CLTF
3.596
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.988
TVALTFEXP_TVA->PJM
CLTF
1.638
CPLELTFEXP_CPLE->PJM
CLTF
0.426
CBM West 2LTFEXP_CBM-W2->PJM
CBM
28.219
NYPJM->LTFIMP_NY
CLTF
1.14
LGEELTFEXP_LGEE->PJM
CLTF
1.401
WECLTFEXP_WEC->PJM
CLTF
1.176
AG2-052LTFEXP_AG2-052->PJM
LTF
0.075
AH1-155LTFEXP_AH1-155->PJM
LTF
0.113
CBM West 1LTFEXP_CBM-W1->PJM
CBM
80.917
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.423
MECLTFEXP_MEC->PJM
CLTF
4.59
SIGELTFEXP_SIGE->PJM
CLTF
0.117
CONTINGENCY 'AP_P1-2_MP-500-007A_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235235 CKT 1   /*01BELMNT     500.0 - 01FLINTRUN   500.0
END
CONTINGENCY 'AP_P1-2_MP-500-008A_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235235 TO BUS 235107 CKT 1          /*01FLINTRUN   500.0 - 01HARRSN     500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235107 TO BUS 235703 CKT 1 /*01HARRSN     500.0 - 01WYLIE R    500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235107 TO BUS 235703 CKT 1 /*01HARRSN     500.0 - 01WYLIE R    500.0
END
CONTINGENCY 'ATSI_P2-3_TE-345-008B_SRT-SL'
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 238889 CKT 1          /*02DAV-BE     345.0 - 02LEMOYN     345.0
 DISCONNECT BUS 238670                                          /*02DVBSG1      25.0
 REMOVE MACHINE 1 FROM BUS 238670                               /*02DVBSG1      25.0
 SET POSTCONTRATING 1646 BRANCH FROM BUS 238654 TO BUS 241877 CKT 1 /*02DAV-BE     345.0 - AC2-103 TAP  345.0
 SET POSTCONTRATING 1683 BRANCH FROM BUS 238654 TO BUS 238563 CKT 1 /*02DAV-BE     345.0 - 02BAY SH     345.0
 SET POSTCONTRATING 1720 BRANCH FROM BUS 238654 TO BUS 239289 CKT 1 /*02DAV-BE     345.0 - 02HAYES      345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 238654 TO BUS 238563 CKT 1 /*02DAV-BE     345.0 - 02BAY SH     345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 238654 TO BUS 239289 CKT 1 /*02DAV-BE     345.0 - 02HAYES      345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 238654 TO BUS 241877 CKT 1 /*02DAV-BE     345.0 - AC2-103 TAP  345.0
END
CONTINGENCY 'ATSI_P2-3_TE-345-013_SRT-SL'
 DISCONNECT BRANCH FROM BUS 238889 TO BUS 238654 CKT 1          /*02LEMOYN     345.0 - 02DAV-BE     345.0
 DISCONNECT BRANCH FROM BUS 238889 TO BUS 238890 CKT 2          /*02LEMOYN     345.0 - 02LEMOYN     138.0
 SET POSTCONTRATING 1646 BRANCH FROM BUS 238889 TO BUS 238961 CKT 1 /*02LEMOYN     345.0 - 02MIDWAY     345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 238889 TO BUS 238961 CKT 1 /*02LEMOYN     345.0 - 02MIDWAY     345.0
END
CONTINGENCY 'ATSI_P2-3_TE-345-014_SRT-A'
 DISCONNECT BRANCH FROM BUS 238889 TO BUS 238654 CKT 1   /*02LEMOYN     345.0 - 02DAV-BE     345.0
 DISCONNECT BRANCH FROM BUS 238889 TO BUS 238890 CKT 1   /*02LEMOYN     345.0 - 02LEMOYN     138.0
END
CONTINGENCY 'ATSI_P2-3_TE-345-009_SRT-A'
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 238889 CKT 1   /*02DAV-BE     345.0 - 02LEMOYN     345.0
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 238889 CKT 1   /*02DAV-BE     345.0 - 02LEMOYN     345.0
END
CONTINGENCY 'ATSI_P1-2_TE-345-602_SRT-A'
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 238889 CKT 1   /*02DAV-BE     345.0 - 02LEMOYN     345.0
END
CONTINGENCY 'ATSI_P7-1_OEC-345-002_SRT-A'
 DISCONNECT BRANCH FROM BUS 238569 TO BUS 239725 CKT 1   /*02BEAVER     345.0 - 02LAKEAVE    345.0
 DISCONNECT BRANCH FROM BUS 238569 TO BUS 239725 CKT 2   /*02BEAVER     345.0 - 02LAKEAVE    345.0
END
CONTINGENCY 'ATSI_P2-3_OEC-345-901_SRT-SL'
 DISCONNECT BRANCH FROM BUS 238569 TO BUS 239725 CKT 2          /*02BEAVER     345.0 - 02LAKEAVE    345.0
 SET POSTCONTRATING 1499 BRANCH FROM BUS 241877 TO BUS 238569 CKT 1 /*AC2-103 TAP  345.0 - 02BEAVER     345.0
 SET POSTCONTRATING 1720 BRANCH FROM BUS 239725 TO BUS 238569 CKT 1 /*02LAKEAVE    345.0 - 02BEAVER     345.0
 SET PRECONTRATING 1245 BRANCH FROM BUS 241877 TO BUS 238569 CKT 1 /*AC2-103 TAP  345.0 - 02BEAVER     345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 239725 TO BUS 238569 CKT 1 /*02LAKEAVE    345.0 - 02BEAVER     345.0
END
CONTINGENCY 'ATSI_P2-3_OEC-345-007A_SRT-SL'
 DISCONNECT BRANCH FROM BUS 238569 TO BUS 238570 CKT 2          /*02BEAVER     345.0 - 02BEAVER     138.0
 DISCONNECT BRANCH FROM BUS 238569 TO BUS 239725 CKT 2          /*02BEAVER     345.0 - 02LAKEAVE    345.0
 SET POSTCONTRATING 1499 BRANCH FROM BUS 241877 TO BUS 238569 CKT 1 /*AC2-103 TAP  345.0 - 02BEAVER     345.0
 SET PRECONTRATING 1245 BRANCH FROM BUS 241877 TO BUS 238569 CKT 1 /*AC2-103 TAP  345.0 - 02BEAVER     345.0
END
CONTINGENCY 'ATSI_P2-3_OEC-345-031_SRT-A'
 DISCONNECT BRANCH FROM BUS 239725 TO BUS 238569 CKT 2   /*02LAKEAVE    345.0 - 02BEAVER     345.0
 DISCONNECT BRANCH FROM BUS 239725 TO BUS 239726 CKT 1   /*02LAKEAVE    345.0 - 02LAKEAVE    138.0
END
CONTINGENCY 'ATSI_P2-3_OEC-345-002_SRT-A'
 DISCONNECT BRANCH FROM BUS 238569 TO BUS 238607 CKT 1   /*02BEAVER     345.0 - 02CARLIL     345.0
 DISCONNECT BRANCH FROM BUS 238569 TO BUS 239725 CKT 1   /*02BEAVER     345.0 - 02LAKEAVE    345.0
END
CONTINGENCY 'ATSI_P2-3_OEC-345-003_SRT-SL'
 DISCONNECT BRANCH FROM BUS 238569 TO BUS 239725 CKT 1          /*02BEAVER     345.0 - 02LAKEAVE    345.0
 SET POSTCONTRATING 1394 BRANCH FROM BUS 238607 TO BUS 238569 CKT 1 /*02CARLIL     345.0 - 02BEAVER     345.0
 SET POSTCONTRATING 1499 BRANCH FROM BUS 238566 TO BUS 238569 CKT 1 /*02WLORAIN    345.0 - 02BEAVER     345.0
 SET PRECONTRATING 1245 BRANCH FROM BUS 238566 TO BUS 238569 CKT 1 /*02WLORAIN    345.0 - 02BEAVER     345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 238607 TO BUS 238569 CKT 1 /*02CARLIL     345.0 - 02BEAVER     345.0
END
CONTINGENCY 'ATSI_P2-3_OEC-345-028_SRT-A'
 DISCONNECT BRANCH FROM BUS 239725 TO BUS 238569 CKT 1   /*02LAKEAVE    345.0 - 02BEAVER     345.0
 DISCONNECT BRANCH FROM BUS 239725 TO BUS 239726 CKT 1   /*02LAKEAVE    345.0 - 02LAKEAVE    138.0
END
CONTINGENCY 'ATSI_P2-3_OEC-345-005_SRT-A'
 DISCONNECT BRANCH FROM BUS 238566 TO BUS 239171 CKT 2   /*02WLORAIN    345.0 - 02WLORG-2     13.8
 DISCONNECT BRANCH FROM BUS 238566 TO BUS 239172 CKT 3   /*02WLORAIN    345.0 - 02WLORG-3     13.8
 DISCONNECT BRANCH FROM BUS 238566 TO BUS 239173 CKT 4   /*02WLORAIN    345.0 - 02WLORG-4     13.8
 DISCONNECT BRANCH FROM BUS 238566 TO BUS 239174 CKT 5   /*02WLORAIN    345.0 - 02WLORG-5     13.8
 DISCONNECT BRANCH FROM BUS 238569 TO BUS 238566 CKT 1   /*02BEAVER     345.0 - 02WLORAIN    345.0
 DISCONNECT BRANCH FROM BUS 238569 TO BUS 241877 CKT 1   /*02BEAVER     345.0 - AC2-103 TAP  345.0
 DISCONNECT BUS 239171                                   /*02WLORG-2     13.8
 DISCONNECT BUS 239172                                   /*02WLORG-3     13.8
 DISCONNECT BUS 239173                                   /*02WLORG-4     13.8
 DISCONNECT BUS 239174                                   /*02WLORG-5     13.8
 REMOVE MACHINE 2 FROM BUS 239171                        /*02WLORG-2     13.8
 REMOVE MACHINE 3 FROM BUS 239172                        /*02WLORG-3     13.8
 REMOVE MACHINE 4 FROM BUS 239173                        /*02WLORG-4     13.8
 REMOVE MACHINE 5 FROM BUS 239174                        /*02WLORG-5     13.8
END
CONTINGENCY 'ATSI_P2-3_OEC-345-006_SRT-SL'
 DISCONNECT BRANCH FROM BUS 238569 TO BUS 238570 CKT 2          /*02BEAVER     345.0 - 02BEAVER     138.0
 DISCONNECT BRANCH FROM BUS 238569 TO BUS 241877 CKT 1          /*02BEAVER     345.0 - AC2-103 TAP  345.0
 SET POSTCONTRATING 1646 BRANCH FROM BUS 239725 TO BUS 238569 CKT 2 /*02LAKEAVE    345.0 - 02BEAVER     345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 239725 TO BUS 238569 CKT 2 /*02LAKEAVE    345.0 - 02BEAVER     345.0
END
CONTINGENCY 'ATSI_P2-3_TE-345-010A_SRT-SL'
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 241877 CKT 1          /*02DAV-BE     345.0 - AC2-103 TAP  345.0
 SET POSTCONTRATING 1683 BRANCH FROM BUS 238654 TO BUS 238563 CKT 1 /*02DAV-BE     345.0 - 02BAY SH     345.0
 SET POSTCONTRATING 1878 BRANCH FROM BUS 238654 TO BUS 238889 CKT 1 /*02DAV-BE     345.0 - 02LEMOYN     345.0
 SET POSTCONTRATING 1892 BRANCH FROM BUS 238654 TO BUS 239289 CKT 1 /*02DAV-BE     345.0 - 02HAYES      345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 238654 TO BUS 238563 CKT 1 /*02DAV-BE     345.0 - 02BAY SH     345.0
 SET PRECONTRATING 1542 BRANCH FROM BUS 238654 TO BUS 238889 CKT 1 /*02DAV-BE     345.0 - 02LEMOYN     345.0
 SET PRECONTRATING 1555 BRANCH FROM BUS 238654 TO BUS 239289 CKT 1 /*02DAV-BE     345.0 - 02HAYES      345.0
END
CONTINGENCY 'ATSI_P1-2_OEC-345-825_SRT-A'
 DISCONNECT BRANCH FROM BUS 241877 TO BUS 238569 CKT 1   /*AC2-103 TAP  345.0 - 02BEAVER     345.0
END
CONTINGENCY 'ATSI_P1-2_OEC-345-824_SRT-A'
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 241877 CKT 1   /*02DAV-BE     345.0 - AC2-103 TAP  345.0
END
CONTINGENCY 'ATSI_P2-3_OEC-345-1152-F1_SRT-A'
 DISCONNECT BRANCH FROM BUS 239289 TO BUS 238654 CKT 1   /*02HAYES      345.0 - 02DAV-BE     345.0
 DISCONNECT BRANCH FROM BUS 239289 TO BUS 239290 CKT 2   /*02HAYES      345.0 - 02HAYES      138.0
END
CONTINGENCY 'ATSI_P2-3_OEC-345-1152-12_SRT-A'
 DISCONNECT BRANCH FROM BUS 239289 TO BUS 238654 CKT 1   /*02HAYES      345.0 - 02DAV-BE     345.0
 DISCONNECT BRANCH FROM BUS 239289 TO BUS 239290 CKT 1   /*02HAYES      345.0 - 02HAYES      138.0
END
CONTINGENCY 'ATSI_P2-3_TE-345-010B1_SRT-SL'
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 239289 CKT 1          /*02DAV-BE     345.0 - 02HAYES      345.0
 SET POSTCONTRATING 1683 BRANCH FROM BUS 238654 TO BUS 238563 CKT 1 /*02DAV-BE     345.0 - 02BAY SH     345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 238654 TO BUS 238563 CKT 1 /*02DAV-BE     345.0 - 02BAY SH     345.0
END
CONTINGENCY 'ATSI_P2-3_TE-345-010B2_SRT-SL'
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 239289 CKT 1          /*02DAV-BE     345.0 - 02HAYES      345.0
 SET POSTCONTRATING 1683 BRANCH FROM BUS 238654 TO BUS 238563 CKT 1 /*02DAV-BE     345.0 - 02BAY SH     345.0
 SET POSTCONTRATING 1878 BRANCH FROM BUS 238654 TO BUS 238889 CKT 1 /*02DAV-BE     345.0 - 02LEMOYN     345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 238654 TO BUS 238563 CKT 1 /*02DAV-BE     345.0 - 02BAY SH     345.0
 SET PRECONTRATING 1542 BRANCH FROM BUS 238654 TO BUS 238889 CKT 1 /*02DAV-BE     345.0 - 02LEMOYN     345.0
END
CONTINGENCY 'ATSI_P2-3_OEC-345-1152-3_SRT-A'
 DISCONNECT BRANCH FROM BUS 239289 TO BUS 238569 CKT 1   /*02HAYES      345.0 - 02BEAVER     345.0
 DISCONNECT BRANCH FROM BUS 239289 TO BUS 239290 CKT 1   /*02HAYES      345.0 - 02HAYES      138.0
END
CONTINGENCY 'ATSI_P1-2_OEC-345-810_SRT-A'
 DISCONNECT BRANCH FROM BUS 239289 TO BUS 238654 CKT 1   /*02HAYES      345.0 - 02DAV-BE     345.0
END
CONTINGENCY 'ATSI_P1-2_OEC-345-809_SRT-A'
 DISCONNECT BRANCH FROM BUS 239289 TO BUS 238569 CKT 1   /*02HAYES      345.0 - 02BEAVER     345.0
END
CONTINGENCY 'ATSI_P7-1_TE-345-021_SRT-A-1'
 DISCONNECT BRANCH FROM BUS 238563 TO BUS 972210 CKT 1   /*02BAY SH     345.0 - AH1-690 TP   345.0
 DISCONNECT BRANCH FROM BUS 238563 TO BUS 972210 CKT 2   /*02BAY SH     345.0 - AH1-690 TP   345.0
END
CONTINGENCY 'ATSI_P2-3_TE-345-007_SRT-SL'
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 238563 CKT 1          /*02DAV-BE     345.0 - 02BAY SH     345.0
 DISCONNECT BUS 238670                                          /*02DVBSG1      25.0
 REMOVE MACHINE 1 FROM BUS 238670                               /*02DVBSG1      25.0
 SET POSTCONTRATING 1720 BRANCH FROM BUS 238563 TO BUS 972210 CKT 2 /*02BAY SH     345.0 - AH1-690 TP   345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 238563 TO BUS 972210 CKT 2 /*02BAY SH     345.0 - AH1-690 TP   345.0
END
CONTINGENCY 'ATSI_P2-3_TE-345-004_SRT-A'
 DISCONNECT BRANCH FROM BUS 238563 TO BUS 238654 CKT 1   /*02BAY SH     345.0 - 02DAV-BE     345.0
 DISCONNECT BRANCH FROM BUS 238563 TO BUS 972210 CKT 2   /*02BAY SH     345.0 - AH1-690 TP   345.0
END
CONTINGENCY 'ATSI_P2-3_TE-345-005_SRT-SL'
 DISCONNECT BRANCH FROM BUS 238563 TO BUS 238654 CKT 1          /*02BAY SH     345.0 - 02DAV-BE     345.0
 REDUCE BUS 238563 SHUNT BY 100 PERCENT                         /*02BAY SH     345.0
 SET POSTCONTRATING 1720 BRANCH FROM BUS 238563 TO BUS 972210 CKT 2 /*02BAY SH     345.0 - AH1-690 TP   345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 238563 TO BUS 972210 CKT 2 /*02BAY SH     345.0 - AH1-690 TP   345.0
END
CONTINGENCY 'ATSI_P2-3_TE-345-006_SRT-SL'
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 238563 CKT 1          /*02DAV-BE     345.0 - 02BAY SH     345.0
 SET POSTCONTRATING 1646 BRANCH FROM BUS 238654 TO BUS 241877 CKT 1 /*02DAV-BE     345.0 - AC2-103 TAP  345.0
 SET POSTCONTRATING 1720 BRANCH FROM BUS 238563 TO BUS 972210 CKT 2 /*02BAY SH     345.0 - AH1-690 TP   345.0
 SET POSTCONTRATING 1720 BRANCH FROM BUS 238654 TO BUS 239289 CKT 1 /*02DAV-BE     345.0 - 02HAYES      345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 238563 TO BUS 972210 CKT 2 /*02BAY SH     345.0 - AH1-690 TP   345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 238654 TO BUS 239289 CKT 1 /*02DAV-BE     345.0 - 02HAYES      345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 238654 TO BUS 241877 CKT 1 /*02DAV-BE     345.0 - AC2-103 TAP  345.0
END
CONTINGENCY 'ATSI_P1-2_TE-345-601_SRT-A'
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 238563 CKT 1   /*02DAV-BE     345.0 - 02BAY SH     345.0
END
CONTINGENCY 'AEP_P1-2_#7441_100545_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
END
CONTINGENCY 'AEP_P4_#7445_05MARYSV 765_B_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290621 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RF 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 962760 TO BUS 290621 CKT 1    /*AG1-125 TP   765.0 - 05MARYSVL_RF 765.0
END
CONTINGENCY 'AEP_P4_#7441_05SORENS 765_J1_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
END
CONTINGENCY 'AEP_P1-2_#709_546_SRT-A'
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
END
CONTINGENCY 'AEP_P4_#8075_05MARYSV 765_A2_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 242939 CKT 2    /*05MARYSV     765.0 - 05MARYSV     345.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
END
CONTINGENCY 'AEP_P4_#9728_05MALIS 138_L1_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1    /*05MALIS      765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290237 CKT 1    /*05MALIS      765.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 243526 TO BUS 243537 CKT 2    /*05HYATT      138.0 - 05MALIS      138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT SR   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT ZB   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243538 TO BUS 290237 CKT 1    /*05MALISX     138.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 290237 TO BUS 290238 CKT 1    /*05MALIS 1EQ    1.0 - 05MALIS T1    13.8
END
CONTINGENCY 'AEP_P4_#9730_05MALIS 138_P1_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1    /*05MALIS      765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290237 CKT 1    /*05MALIS      765.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT SR   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT ZB   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243553 CKT 1    /*05MALIS      138.0 - 05POLARS     138.0
 OPEN BRANCH FROM BUS 243538 TO BUS 290237 CKT 1    /*05MALISX     138.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 290237 TO BUS 290238 CKT 1    /*05MALIS 1EQ    1.0 - 05MALIS T1    13.8
END
CONTINGENCY 'AEP_P4_#9729_05MALIS 138_M1_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1    /*05MALIS      765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290237 CKT 1    /*05MALIS      765.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 243526 TO BUS 243537 CKT 1    /*05HYATT      138.0 - 05MALIS      138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT SR   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT ZB   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243538 TO BUS 290237 CKT 1    /*05MALISX     138.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 290237 TO BUS 290238 CKT 1    /*05MALIS 1EQ    1.0 - 05MALIS T1    13.8
END
CONTINGENCY 'AEP_P2-2_#7222_05MALIS 765_1_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1    /*05MALIS      765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290237 CKT 1    /*05MALIS      765.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT SR   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT ZB   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243538 TO BUS 290237 CKT 1    /*05MALISX     138.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 290237 TO BUS 290238 CKT 1    /*05MALIS 1EQ    1.0 - 05MALIS T1    13.8
END
CONTINGENCY 'AEP_P4_#7222_05MALIS 765_D_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1    /*05MALIS      765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290237 CKT 1    /*05MALIS      765.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT SR   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT ZB   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243538 TO BUS 290237 CKT 1    /*05MALISX     138.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 290237 TO BUS 290238 CKT 1    /*05MALIS 1EQ    1.0 - 05MALIS T1    13.8
END
CONTINGENCY 'AP_P1-3_MP-765-501T_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1   /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                   /*05BELMON     765.0
END
CONTINGENCY 'AEP_P4_#706_05GAVIN 765_C1_SRT-A'
 OPEN BRANCH FROM BUS 242922 TO BUS 290622 CKT 1    /*05FLTLCK     765.0 - 05GAVIN_RF   765.0
 OPEN BRANCH FROM BUS 242923 TO BUS 290622 CKT Z1   /*05GAVIN      765.0 - 05GAVIN_RF   765.0
END
CONTINGENCY 'AEP_P1-2_#706_SRT-A'
 OPEN BRANCH FROM BUS 242922 TO BUS 290622 CKT 1    /*05FLTLCK     765.0 - 05GAVIN_RF   765.0
 OPEN BRANCH FROM BUS 242923 TO BUS 290622 CKT Z1   /*05GAVIN      765.0 - 05GAVIN_RF   765.0
END
CONTINGENCY 'ATSI_P7-1_TE-345-027A_SRT-A'
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 239289 CKT 1   /*02DAV-BE     345.0 - 02HAYES      345.0
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 241877 CKT 1   /*02DAV-BE     345.0 - AC2-103 TAP  345.0
END
CONTINGENCY 'ATSI_P7-1_TE-345-030_SRT-A'
 DISCONNECT BRANCH FROM BUS 239289 TO BUS 238569 CKT 1   /*02HAYES      345.0 - 02BEAVER     345.0
 DISCONNECT BRANCH FROM BUS 241877 TO BUS 238569 CKT 1   /*AC2-103 TAP  345.0 - 02BEAVER     345.0
END
CONTINGENCY 'AEP_P4_#2995_05E LIMA 345_M_SRT-A'
 OPEN BRANCH FROM BUS 242935 TO BUS 245128 CKT 2   /*05E LIMA     345.0 - 05E.LIMA 2EQ   1.0
 OPEN BRANCH FROM BUS 242935 TO BUS 246929 CKT 1   /*05E LIMA     345.0 - 05MADDOX     345.0
 OPEN BRANCH FROM BUS 242989 TO BUS 245128 CKT 2   /*05E LIMA     138.0 - 05E.LIMA 2EQ   1.0
 OPEN BRANCH FROM BUS 245128 TO BUS 245148 CKT 2   /*05E.LIMA 2EQ   1.0 - 05E.LIMA T2   13.8
END
CONTINGENCY 'AEP_P7-1_#11010___SRT-A'
 OPEN BRANCH FROM BUS 242933 TO BUS 243211 CKT 1   /*05RPMONE     345.0 - 05ALLEN      345.0
 OPEN BRANCH FROM BUS 243211 TO BUS 243232 CKT 1   /*05ALLEN      345.0 - 05SORENS     345.0
END
CONTINGENCY 'AEP_P1-2_#6463_16757_SRT-A'
 OPEN BRANCH FROM BUS 242935 TO BUS 246929 CKT 1   /*05E LIMA     345.0 - 05MADDOX     345.0
END
CONTINGENCY 'AEP_P7-1_#17567_SRT-SL'
 OPEN BRANCH FROM BUS 242939 TO BUS 242945 CKT 1   /*05MARYSV     345.0 - 05SW LIM     345.0
 OPEN BRANCH FROM BUS 242939 TO BUS 290984 CKT 1   /*05MARYSV     345.0 - 05BOKESCRK   345.0
END
CONTINGENCY 'AEP_P2-2_#16655_05GUNN RD SW 345_2_SRT-A'
 OPEN BRANCH FROM BUS 243903 TO BUS 290984 CKT 1   /*05GUNN RD SW 345.0 - 05BOKESCRK   345.0
END
CONTINGENCY 'AEP_P2-2_#16654_05GUNN RD SW 345_1_SRT-A'
 OPEN BRANCH FROM BUS 243902 TO BUS 243903 CKT 1   /*05HARDIN SW  345.0 - 05GUNN RD SW 345.0
END
CONTINGENCY 'AEP_P4_#7443_05DUMONT 765_A_SRT-A'
 OPEN BRANCH FROM BUS 243205 TO BUS 243206 CKT 1    /*05COOK       765.0 - 05DUMONT     765.0
 OPEN BRANCH FROM BUS 243206 TO BUS 290606 CKT Z1   /*05DUMONT     765.0 - 05DUMONT_RS  765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290606 CKT 1    /*05SORENS     765.0 - 05DUMONT_RS  765.0
END
CONTINGENCY 'AEP_P4_#7442_05SORENS 765_K2_SRT-A'
 OPEN BRANCH FROM BUS 243206 TO BUS 290606 CKT Z1   /*05DUMONT     765.0 - 05DUMONT_RS  765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290606 CKT 1    /*05SORENS     765.0 - 05DUMONT_RS  765.0
END
CONTINGENCY 'AEP_P4_#7444_05DUMONT 765_A2_SRT-A'
 OPEN BRANCH FROM BUS 243206 TO BUS 243641 CKT 2    /*05DUMONT     765.0 - 05DUMONT 2EQ   1.0
 OPEN BRANCH FROM BUS 243206 TO BUS 290606 CKT Z1   /*05DUMONT     765.0 - 05DUMONT_RS  765.0
 OPEN BRANCH FROM BUS 243219 TO BUS 243641 CKT 2    /*05DUMONT     345.0 - 05DUMONT 2EQ   1.0
 OPEN BRANCH FROM BUS 243641 TO BUS 243642 CKT 2    /*05DUMONT 2EQ   1.0 - 05DUMONT T2   34.5
 OPEN BRANCH FROM BUS 246999 TO BUS 290606 CKT 1    /*05SORENS     765.0 - 05DUMONT_RS  765.0
END
CONTINGENCY 'AEP_P1-2_#7442_200545_SRT-A'
 OPEN BRANCH FROM BUS 243206 TO BUS 290606 CKT Z1   /*05DUMONT     765.0 - 05DUMONT_RS  765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290606 CKT 1    /*05SORENS     765.0 - 05DUMONT_RS  765.0
END
CONTINGENCY 'ATSI_P2-3_TE-345-034T_SRT-A'
 DISCONNECT BRANCH FROM BUS 241901 TO BUS 242936 CKT 1   /*02LALLENDORF 345.0 - 05FOSTOR     345.0
 DISCONNECT BRANCH FROM BUS 241901 TO BUS 264612 CKT 1   /*02LALLENDORF 345.0 - 19MON12      345.0
END
CONTINGENCY 'ATSI_P2-3_TE-345-033T_SRT-A'
 DISCONNECT BRANCH FROM BUS 241901 TO BUS 264612 CKT 1   /*02LALLENDORF 345.0 - 19MON12      345.0
 DISCONNECT BRANCH FROM BUS 241901 TO BUS 972210 CKT 1   /*02LALLENDORF 345.0 - AH1-690 TP   345.0
END
CONTINGENCY 'ATSI_P2-3_TE-345-023T_SRT-SL'
 DISCONNECT BRANCH FROM BUS 238530 TO BUS 239344 CKT 3          /*02ALLEN      345.0 - 02ALLEN-2    138.0
 DISCONNECT BRANCH FROM BUS 238530 TO BUS 256583 CKT 1          /*02ALLEN      345.0 - 18MOROCCO    345.0
 SET POSTCONTRATING 1394 BRANCH FROM BUS 238530 TO BUS 238961 CKT 1 /*02ALLEN      345.0 - 02MIDWAY     345.0
 SET PRECONTRATING 1245 BRANCH FROM BUS 238530 TO BUS 238961 CKT 1 /*02ALLEN      345.0 - 02MIDWAY     345.0
END
CONTINGENCY 'ATSI_P2-3_TE-345-022T_SRT-A'
 DISCONNECT BRANCH FROM BUS 238530 TO BUS 239018 CKT 1   /*02ALLEN      345.0 - 02FULTON     345.0
 DISCONNECT BRANCH FROM BUS 238530 TO BUS 256583 CKT 1   /*02ALLEN      345.0 - 18MOROCCO    345.0
END
CONTINGENCY 'ATSI_P2-3_OEC-345-009_SRT-SL'
 DISCONNECT BRANCH FROM BUS 238569 TO BUS 238570 CKT 2          /*02BEAVER     345.0 - 02BEAVER     138.0
 DISCONNECT BRANCH FROM BUS 238569 TO BUS 239289 CKT 1          /*02BEAVER     345.0 - 02HAYES      345.0
 SET POSTCONTRATING 1499 BRANCH FROM BUS 241877 TO BUS 238569 CKT 1 /*AC2-103 TAP  345.0 - 02BEAVER     345.0
 SET POSTCONTRATING 1720 BRANCH FROM BUS 238607 TO BUS 238569 CKT 1 /*02CARLIL     345.0 - 02BEAVER     345.0
 SET POSTCONTRATING 1720 BRANCH FROM BUS 239725 TO BUS 238569 CKT 2 /*02LAKEAVE    345.0 - 02BEAVER     345.0
 SET PRECONTRATING 1245 BRANCH FROM BUS 241877 TO BUS 238569 CKT 1 /*AC2-103 TAP  345.0 - 02BEAVER     345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 238607 TO BUS 238569 CKT 1 /*02CARLIL     345.0 - 02BEAVER     345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 239725 TO BUS 238569 CKT 2 /*02LAKEAVE    345.0 - 02BEAVER     345.0
END
CONTINGENCY 'AEP_P7-1_#11087___SRT-A-1'
 OPEN BRANCH FROM BUS 243218 TO BUS 288691 CKT 1   /*05DESOTO     345.0 - 05WHIPPLEDTC 345.0
 OPEN BRANCH FROM BUS 243218 TO BUS 958860 CKT 2   /*05DESOTO     345.0 - AF2-177 TP   345.0
END
CONTINGENCY 'ATSI_P1-2_TE-345-606_SRT-A-1'
 DISCONNECT BRANCH FROM BUS 238563 TO BUS 972210 CKT 1   /*02BAY SH     345.0 - AH1-690 TP   345.0
END
CONTINGENCY 'ATSI_P2-3_TE-345-002_SRT-SL'
 DISCONNECT BRANCH FROM BUS 238563 TO BUS 238568 CKT 1          /*02BAY SH     345.0 - 02BAYSHO     138.0
 DISCONNECT BRANCH FROM BUS 238563 TO BUS 972210 CKT 1          /*02BAY SH     345.0 - AH1-690 TP   345.0
 SET POSTCONTRATING 1720 BRANCH FROM BUS 238563 TO BUS 972210 CKT 2 /*02BAY SH     345.0 - AH1-690 TP   345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 238563 TO BUS 972210 CKT 2 /*02BAY SH     345.0 - AH1-690 TP   345.0
END
235117 to 235111 ckt 1
238563 to 238654 ckt 1
238569 to 238607 ckt 1
238569 to 239725 ckt 1
238569 to 239725 ckt 2
238654 to 239289 ckt 1
238654 to 241877 ckt 1
239289 to 238569 ckt 1
241901 to 242936 ckt 1
238889 to 238654 ckt 1
243211 to 242933 ckt 1
290984 to 242939 ckt 1
243206 to 290606 ckt Z1
242922 to 290622 ckt 1
243903 to 290984 ckt 1
290618 to 242924 ckt Z1
243458 to 246752 ckt 1
243208 to 242865 ckt 2
242865 to 248000 ckt 1
242925 to 235117 ckt 1
246929 to 242935 ckt 1
242926 to 246751 ckt 1
242928 to 290620 ckt Z1
290620 to 242926 ckt 1
290608 to 242928 ckt Z1
242933 to 965420 ckt 1
243232 to 246999 ckt 3
246999 to 290607 ckt Z1
243234 to 243228 ckt 1
256583 to 238530 ckt 1
264612 to 241901 ckt 1
241877 to 238569 ckt 1
965420 to 246929 ckt 1
970214 to 238745 ckt 1
972210 to 238563 ckt 2

Winter Peak Analysis

The New Service Request AH1-272 was evaluated as a 185.0 MW (123.9 MW Capacity) injection in the AEP area.

AH1-272 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 185.0 MW (185.0 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AEP
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
AEP_P4_#7445_05MARYSV 765_B_SRT-A
BreakerAC120.08 %1737.0B2085.730.72
GD2AEP
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC117.93 %1737.0B2048.410.74
GD2AEP
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
AEP_P4_#7441_05SORENS 765_J1_SRT-A
BreakerAC115.82 %1737.0B2011.720.74
GD2AEP
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
AEP_P4_#7446_05MARYSV 765_B2_SRT-A
BreakerAC115.73 %1737.0B2010.180.7
GD2AEP
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line
AEP_P4_#6189_05HANG R 765_D1_SRT-A
BreakerAC102.6 %5133.0B5266.311.47
GD2AEP
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line
AEP_P4_#1760_05JEFRSO 765_A_SRT-A
BreakerAC102.42 %5133.0B5257.211.66
GD2AEP
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line
AEP_P4_#709_05HANG R 765_D2_SRT-A
BreakerAC101.4 %5133.0B5204.921.47
GD2AEP
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line
AEP_P1-2_#709_546_SRT-A
SingleAC101.4 %5133.0B5204.831.47
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P4_#7334_05JEFRSO 765_A2_SRT-A
BreakerAC114.0 %4961.0B5655.612.15
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P4_#6189_05HANG R 765_D1_SRT-A
BreakerAC104.24 %4961.0B5171.462.0
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P4_#709_05HANG R 765_D2_SRT-A
BreakerAC102.76 %4961.0B5098.142.0
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P1-2_#709_546_SRT-A
SingleAC102.76 %4961.0B5098.112.0
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P4_#1760_05JEFRSO 765_A_SRT-A
BreakerAC100.41 %4961.0B4981.372.15
GD2AEP
05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line
AEP_P4_#7445_05MARYSV 765_B_SRT-A
BreakerAC103.24 %2219.0B2290.850.72
GD2AEP
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
AEP_P4_#7445_05MARYSV 765_B_SRT-A
BreakerAC105.42 %2219.0B2339.210.72
GD2AEP
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
AEP_P4_#7441_05SORENS 765_J1_SRT-A
BreakerAC102.19 %2219.0B2267.590.74
GD2AEP
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC102.19 %2219.0B2267.560.74
GD2AEP
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
AEP_P4_#7446_05MARYSV 765_B2_SRT-A
BreakerAC101.94 %2219.0B2262.150.7

Details for 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7445_05MARYSV 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:120.08 %
Rating:1737.0 MVA
Rating Type:B
MVA to Mitigate:2085.73
MW Contribution:0.72
Bus #Bus NameTypeMW Contribution
24639705ELKHART HY
50/50
0.149
963791AG1-232 GEN
Solar/Wind Harmer
0.959
270246TR4_N_V150
Solar/Wind Harmer
1.16
24695305TIMB G C
Solar/Wind Harmer
9.67
270024AE2-089 GEN
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
0.572
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
943591AF1-030 GEN
Solar/Wind Harmer
0.419
972181SS23-001
Solar/Wind Harmer
0.44
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.3
970289AG2-191 GEN
Solar/Wind Harmer
0.078
24755605MDL-5G
Solar/Wind Harmer
3.34
959091AF2-200 GEN
Solar/Wind Harmer
0.805
946031AF1-268 GEN
Solar/Wind Harmer
0.324
274849CRESCENT ;1U
Solar/Wind Harmer
2.552
24729205KEY G1
50/50
6.679
270526AF1-158 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
0.927
964401AG1-302 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
8.196
270004AE1-209 GEN
Solar/Wind Harmer
6.381
274872LEEDK;1U
Solar/Wind Harmer
0.18
270180AB1-006 GEN1
Solar/Wind Harmer
9.491
24791305MDL-5G
Solar/Wind Harmer
3.34
959081AF2-199 GEN
Solar/Wind Harmer
0.403
971475AH1-234 GEN
Solar/Wind Harmer
0.892
247620Y3-023
50/50
0.46
965041AG1-368 GEN
Solar/Wind Harmer
0.694
971617AH1-308 GEN
Solar/Wind Harmer
5.12
943021AE2-325 GEN
Solar/Wind Harmer
2.954
958011AF2-095 GEN
Solar/Wind Harmer
0.618
971573AH1-285 GEN
Solar/Wind Harmer
0.358
945421AF1-207 GEN
Solar/Wind Harmer
0
274877BISHOP HL;1U
Solar/Wind Harmer
4.493
270349AD2-093_GEN
Solar/Wind Helper
0.444
970615AG2-402 GEN
50/50
4.56
24729405KEY G3
50/50
6.792
24729505KEY G4
50/50
6.679
960971AF2-388 GEN
Solar/Wind Harmer
16.226
970349AG2-230 GEN
Solar/Wind Harmer
0.722
971347AH1-153 GEN
Solar/Wind Harmer
0.722
961051AF2-396 GEN
Solar/Wind Harmer
0.958
961051AF2-396 GEN
Solar/Wind Harmer
7.664
270599AE1-208 GEN
Solar/Wind Harmer
0.368
970245AG2-165 GEN
Solar/Wind Harmer
0.887
972231SS25-0005
Solar/Wind Harmer
0.704
274862TOP CROP ;2U
Solar/Wind Harmer
6.808
970921AG2-575 GEN
Solar/Wind Harmer
0.41
960851AF2-376 GEN
50/50
2.066
965021AG1-366 GEN
Solar/Wind Harmer
4.56
958861AF2-177 GEN
Solar/Wind Harmer
15.756
945371AF1-202 GEN
Solar/Wind Harmer
7.43
276893AG1-478 C
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
24641605TWIN BRNCH
50/50
0.015
944531AF1-118 GEN
Solar/Wind Harmer
2.039
274887GEN-1.85
Solar/Wind Harmer
7.997
970707AG2-453 GEN
Solar/Wind Harmer
1.193
970833AG2-524 GEN
Solar/Wind Harmer
3.709
958481AF2-142 GEN
Solar/Wind Harmer
0.624
959331AF2-224 GEN
Solar/Wind Harmer
1.14
944541AF1-119 GEN
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
5.037
276843GEN-1.7
Solar/Wind Harmer
0.708
941551AE2-152 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
11.858
276882AE2-255 GEN
Solar/Wind Harmer
4.328
960441AF2-335 GEN
Solar/Wind Harmer
0.402
270223U2-072_GEN1
Solar/Wind Helper
0.141
966831AG1-554 GEN
Solar/Wind Helper
0.276
274854TWINGROVE;U2
Solar/Wind Harmer
6.161
970583AG2-370 GEN
50/50
2.775
970031AG2-029 GEN
Solar/Wind Harmer
2.089
270247TR4_N_V136
Solar/Wind Harmer
1.16
965051AG1-369 GEN
Solar/Wind Harmer
0.295
960591AF2-350 GEN
Solar/Wind Harmer
0.429
958381AF2-132 GEN
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
8.024
939401AE1-172 GEN
Solar/Wind Harmer
16.293
276876AE1-163_GEN2
Solar/Wind Harmer
9.042
274857EASY ROAD;U1
Solar/Wind Harmer
6.189
961761AG1-017 GEN
Solar/Wind Harmer
0.383
970921AG2-575 GEN
Solar/Wind Harmer
1.639
274879MINONK ;1U
Solar/Wind Harmer
9.594
971411AH1-196 GEN
Solar/Wind Harmer
0.608
274855GSG-6 ;RU
Solar/Wind Harmer
5.144
24386405FR-21G C
Solar/Wind Harmer
3.024
942871AE2-306 GEN
Solar/Wind Helper
0.211
945641AF1-229 GEN
Solar/Wind Helper
0.446
270541AE2-072 C
Solar/Wind Helper
0.447
270063AE2-323 C
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0
970513AG2-328 GEN
Solar/Wind Harmer
0.887
970517AG2-330 GEN
Solar/Wind Harmer
13.834
959141AF2-205 GEN
Solar/Wind Harmer
0
970833AG2-524 GEN
Solar/Wind Harmer
0.464
962781AG1-127 GEN
Solar/Wind Harmer
0.39
958821AF2-173 GEN
Solar/Wind Harmer
0.573
971335AH1-147 GEN
Solar/Wind Harmer
0.81
24697605MDL-3G C
Solar/Wind Harmer
5.058
270181AB1-006 GEN2
Solar/Wind Harmer
0.629
971171AH1-044 GEN
Solar/Wind Harmer
0.805
926823AC1-168 GEN
Solar/Wind Harmer
4.888
24385905FR-11G C
Solar/Wind Harmer
5.945
276782AC1-033 GEN
Solar/Wind Harmer
5.076
24725505WLD G2 C
Solar/Wind Harmer
4.997
946321AF1-296 GEN
Solar/Wind Harmer
11.312
958581AF2-149 GEN
Solar/Wind Helper
0.216
960611AF2-352 GEN
Solar/Wind Harmer
1.01
276868AE1-113 GEN
Solar/Wind Harmer
13.718
971675AH1-338 GEN
Solar/Wind Harmer
0.729
970781AG2-491 GEN
Solar/Wind Harmer
0.403
960791AF2-370 GEN
Solar/Wind Harmer
1.606
276903AD2-071 C
Solar/Wind Harmer
0.391
966841AG1-555 GEN
Solar/Wind Harmer
0
274853TWINGROVE;U1
Solar/Wind Harmer
9.31
270224U2-072_GEN2
Solar/Wind Helper
0.141
270391AF1-285 GEN3
Solar/Wind Helper
0.282
241847AF2-150_GEN
Solar/Wind Helper
0.259
965651AG1-433 GEN
Solar/Wind Harmer
8.113
270449AD2-020 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
9.816
943121AE2-341 GEN
Solar/Wind Harmer
0.628
970291AG2-192 GEN
Solar/Wind Harmer
0.054
970289AG2-191 GEN
Solar/Wind Harmer
0.544
957471AF2-041 GEN
Solar/Wind Harmer
1.208
274848CAMPGROVE;RU
Solar/Wind Harmer
7.026
959341AF2-225 GEN
Solar/Wind Harmer
0.576
957201AF2-014 GEN
Solar/Wind Helper
3.936
270284AF1-227 GEN1
Solar/Wind Helper
0.932
270428AC2-015 C
Solar/Wind Helper
0.365
276656WTG2_EQ
Solar/Wind Harmer
0.876
941731AE2-173 GEN
Solar/Wind Harmer
3.84
270462AD2-086
Solar/Wind Helper
1.767
270317AD1-130_GEN
Solar/Wind Helper
1.153
270287AF1-227 GEN3
Solar/Wind Helper
0.344
971599AH1-298 GEN
50/50
10.28
960861AF2-377 GEN
50/50
2.361
24729305KEY G2
50/50
6.792
970611AG2-400 GEN
Solar/Wind Harmer
1.14
270071AF1-092 GEN
Solar/Wind Harmer
0.935
970321AG2-212 GEN
Solar/Wind Harmer
0.887
270005AE1-210 C O1
Solar/Wind Harmer
6.381
276602WESTBROOK C
Solar/Wind Harmer
2.837
276645AC1-214 GEN1
Solar/Wind Harmer
1.672
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
0.583
24387305FR-4G C
Solar/Wind Harmer
4.536
24386605FR-22G C
Solar/Wind Harmer
3.024
24387005FR-3G C
Solar/Wind Harmer
2.994
942111AE2-223 GEN
Solar/Wind Harmer
8.986
960841AF2-375 GEN
Solar/Wind Helper
0.553
270043AE2-236 GEN
Solar/Wind Harmer
0.369
971771AH1-392 GEN
Solar/Wind Harmer
0.437
270505AE1-170 C O1
Solar/Wind Harmer
0.719
274888KELLY CRK;1U
Solar/Wind Harmer
8.705
970941AG2-585 GEN
Solar/Wind Harmer
0.536
971605AH1-302 GEN
Solar/Wind Harmer
6.289
276805AD2-038 GEN
Solar/Wind Harmer
7.442
274850MENDOTA H;RU
Solar/Wind Harmer
3.644
276861AD2-134 GEN
Solar/Wind Harmer
2.487
274864CRW2-WTG
Solar/Wind Harmer
7.63
970569AG2-363 GEN
Solar/Wind Harmer
1.196
274858EASY ROAD;U2
Solar/Wind Harmer
6.189
276157O29GEN1
Solar/Wind Harmer
5.697
957751AF2-069 GEN
Solar/Wind Harmer
0.51
939741AE1-205 GEN
Solar/Wind Harmer
0.768
246938BC-WTG3
Solar/Wind Helper
5.468
246936BC-WTG1
Solar/Wind Helper
5.531
24653605MOTTVILLE
50/50
0.003
965011AG1-365 GEN
Solar/Wind Harmer
1.14
945111AF1-176 GEN
Solar/Wind Harmer
0.877
945111AF1-176 GEN
Solar/Wind Harmer
4.78
957891AF2-083 GEN
Solar/Wind Harmer
0
971769AH1-391 GEN
Solar/Wind Harmer
0.467
964861AG1-349 GEN
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
43.563
940581AE2-045 GEN
Solar/Wind Harmer
0
971177AH1-047 GEN
Solar/Wind Harmer
0.239
970571AG2-364 GEN
Solar/Wind Harmer
0.798
970825AG2-519 GEN
Solar/Wind Harmer
0.442
970825AG2-519 GEN
Solar/Wind Harmer
1.697
971681AH1-341 GEN
Solar/Wind Harmer
0.594
938861AE1-114 GEN
Solar/Wind Harmer
9.271
276603SUBLETTE C
Solar/Wind Harmer
1.346
253378AE2-206_GEN
Solar/Wind Helper
0.334
962691AG1-118 GEN
Solar/Wind Harmer
1.232
270594AE1-207 GEN
Solar/Wind Harmer
0.652
270032AE2-172
Solar/Wind Harmer
3.259
971997AH1-543 GEN
Solar/Wind Harmer
0.64
276863AD2-134 GEN
Solar/Wind Harmer
2.487
274863CRW1-WTG
Solar/Wind Harmer
7.63
276889AE2-281 GEN
Solar/Wind Harmer
2.583
24691005MDL-2G C
Solar/Wind Harmer
5.066
274856ECOGROVE ;U1
Solar/Wind Harmer
4.672
971549AH1-272 GEN
Solar/Wind Harmer
0.724
276158O29GEN2
Solar/Wind Harmer
5.697
276708O09 GEN2
Solar/Wind Harmer
4.795
246937BC-WTG2
Solar/Wind Helper
5.531
270485AE1-090_GEN
Solar/Wind Helper
0.154
270191TR4_S_V150
Solar/Wind Harmer
6.398
965101AG1-375 GEN
Solar/Wind Harmer
0.505
960681AF2-359 GEN
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
0.368
971917AH1-482 GEN
Solar/Wind Harmer
6.668
276691AA1-018 GEN1
Solar/Wind Harmer
0.448
276872AE1-163_GEN1
Solar/Wind Harmer
9.042
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
10.622
971067AG2-660 GEN
Solar/Wind Harmer
1.611
970115AG2-085 GEN
Solar/Wind Harmer
0.161
276741O09 GEN1
Solar/Wind Harmer
4.795
276655WTG1_EQ
Solar/Wind Harmer
6.613
270578AF1-285 GEN2
Solar/Wind Helper
0.282
247522W1-056 GEN
Solar/Wind Helper
1.885
270286AF1-227 GEN2
Solar/Wind Helper
0.344
961961AG1-039 GEN
Solar/Wind Helper
0.165
241960AC2-195 GEN
Solar/Wind Helper
0.289
276646AC1-214 GEN2
Solar/Wind Harmer
1.672
24386205FR-12G C
Solar/Wind Harmer
3.157
276726Z2-087_GEN
Solar/Wind Harmer
9.984
958491AF2-143 GEN
Solar/Wind Harmer
0.616
942991AE2-321 GEN
Solar/Wind Harmer
0.407
971333AH1-146 GEN
Solar/Wind Harmer
0.81
24697905MDL-4G C
Solar/Wind Harmer
3.34
970819AG2-516 GEN
Solar/Wind Harmer
0.479
274851PROVIDENC;RU
Solar/Wind Harmer
3.693
964611AG1-324 GEN
Solar/Wind Harmer
0.35
270201AC2-176 GEN
Solar/Wind Harmer
6.57
274878BISHOP HL;2U
Solar/Wind Harmer
4.493
24699105WLD G1 C
Solar/Wind Harmer
4.967
965931AG1-462 GEN
Solar/Wind Harmer
0.963
270499AE1-146 GEN
Solar/Wind Helper
0.534
970521AG2-332 GEN
50/50
10.75
247521TR3_G114
Solar/Wind Harmer
8.58
276806AD2-047 C O1
Solar/Wind Harmer
13.208
958391AF2-133 GEN
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
7.511
247642Z2-115 C
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.495
971341AH1-150 GEN
Solar/Wind Harmer
0.805
270302AB2-170 GEN
Solar/Wind Helper
1.153
270231U2-072_GEN5
Solar/Wind Helper
0.141
270471AD2-092_GEN
Solar/Wind Helper
0.444
276901AD2-066 C O1
Solar/Wind Harmer
0
965031AG1-367 GEN
Solar/Wind Harmer
0.409
971343AH1-151 GEN
Solar/Wind Harmer
0.805
970169AG2-114 GEN
Solar/Wind Harmer
0.398
961011AF2-392 GEN
Solar/Wind Harmer
12.167
270227U2-072_GEN3
Solar/Wind Helper
0.141
270228U2-072_GEN4
Solar/Wind Helper
0.141
276820AF1-078_GEN
Solar/Wind Helper
0.151
957141AF2-008_MTX
Adder
27.929
944201AF1-088_MTX
Adder
55.858
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.201
WECLTFEXP_WEC->PJM
CLTF
2.632
SIGELTFEXP_SIGE->PJM
CLTF
0.2
CBM West 1LTFEXP_CBM-W1->PJM
CBM
72.501
NYPJM->LTFIMP_NY
CLTF
1.242
MECLTFEXP_MEC->PJM
CLTF
9.671
AG2-052LTFEXP_AG2-052->PJM
LTF
0.166
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.085
TVALTFEXP_TVA->PJM
CLTF
2.406
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
23.398
CBM West 2LTFEXP_CBM-W2->PJM
CBM
51.626
LGEELTFEXP_LGEE->PJM
CLTF
1.821
LAGNLTFEXP_LAGN->PJM
CLTF
5.9
AH1-155LTFEXP_AH1-155->PJM
LTF
0.248

Details for 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:117.93 %
Rating:1737.0 MVA
Rating Type:B
MVA to Mitigate:2048.41
MW Contribution:0.74
Bus #Bus NameTypeMW Contribution
24639705ELKHART HY
50/50
0.15
270142AC1-141 CT1_
50/50
2.02
270143AC1-141 CT2_
50/50
2.02
963791AG1-232 GEN
Solar/Wind Harmer
0.972
270246TR4_N_V150
Solar/Wind Harmer
1.186
24695305TIMB G C
Solar/Wind Harmer
9.919
270024AE2-089 GEN
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
0.578
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
943591AF1-030 GEN
Solar/Wind Harmer
0.422
965031AG1-367 GEN
Solar/Wind Harmer
0.414
276901AD2-066 C O1
Solar/Wind Harmer
0
971343AH1-151 GEN
Solar/Wind Harmer
0.811
970169AG2-114 GEN
Solar/Wind Harmer
0.401
961011AF2-392 GEN
Solar/Wind Harmer
12.249
270227U2-072_GEN3
Solar/Wind Helper
0.133
270228U2-072_GEN4
Solar/Wind Helper
0.133
276820AF1-078_GEN
Solar/Wind Helper
0.141
972181SS23-001
Solar/Wind Harmer
0.444
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.311
970289AG2-191 GEN
Solar/Wind Harmer
0.079
24755605MDL-5G
Solar/Wind Harmer
3.365
959091AF2-200 GEN
Solar/Wind Harmer
0.811
946031AF1-268 GEN
Solar/Wind Harmer
0.329
274849CRESCENT ;1U
Solar/Wind Harmer
2.569
274877BISHOP HL;1U
Solar/Wind Harmer
4.523
270349AD2-093_GEN
Solar/Wind Helper
0.383
24729205KEY G1
50/50
6.754
270526AF1-158 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
0.936
964401AG1-302 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
8.261
270004AE1-209 GEN
Solar/Wind Harmer
6.463
274872LEEDK;1U
Solar/Wind Harmer
0.181
270180AB1-006 GEN1
Solar/Wind Harmer
9.562
24791305MDL-5G
Solar/Wind Harmer
3.365
959081AF2-199 GEN
Solar/Wind Harmer
0.406
971475AH1-234 GEN
Solar/Wind Harmer
0.898
276646AC1-214 GEN2
Solar/Wind Harmer
1.683
24386205FR-12G C
Solar/Wind Harmer
3.179
276726Z2-087_GEN
Solar/Wind Harmer
10.052
247620Y3-023
50/50
0.466
270144AC1-141 ST1_
50/50
1.789
24642205MAYFLWER
50/50
0.618
962601AG1-109 GEN
50/50
2.389
965041AG1-368 GEN
Solar/Wind Harmer
0.706
270191TR4_S_V150
Solar/Wind Harmer
6.54
965101AG1-375 GEN
Solar/Wind Harmer
0.511
960681AF2-359 GEN
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
0.373
971917AH1-482 GEN
Solar/Wind Harmer
6.726
276691AA1-018 GEN1
Solar/Wind Harmer
0.451
970115AG2-085 GEN
Solar/Wind Harmer
0.163
276872AE1-163_GEN1
Solar/Wind Harmer
9.109
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
10.701
971067AG2-660 GEN
Solar/Wind Harmer
1.622
276741O09 GEN1
Solar/Wind Harmer
4.827
276655WTG1_EQ
Solar/Wind Harmer
6.657
270578AF1-285 GEN2
Solar/Wind Helper
0.267
247522W1-056 GEN
Solar/Wind Helper
1.806
270286AF1-227 GEN2
Solar/Wind Helper
0.313
961961AG1-039 GEN
Solar/Wind Helper
0.152
241960AC2-195 GEN
Solar/Wind Helper
0.26
971617AH1-308 GEN
Solar/Wind Harmer
5.201
943021AE2-325 GEN
Solar/Wind Harmer
2.992
958011AF2-095 GEN
Solar/Wind Harmer
0.623
971573AH1-285 GEN
Solar/Wind Harmer
0.361
945421AF1-207 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
0.621
942991AE2-321 GEN
Solar/Wind Harmer
0.41
971333AH1-146 GEN
Solar/Wind Harmer
0.816
24697905MDL-4G C
Solar/Wind Harmer
3.365
970819AG2-516 GEN
Solar/Wind Harmer
0.483
964611AG1-324 GEN
Solar/Wind Harmer
0.357
270201AC2-176 GEN
Solar/Wind Harmer
6.697
274851PROVIDENC;RU
Solar/Wind Harmer
3.718
274878BISHOP HL;2U
Solar/Wind Harmer
4.523
24699105WLD G1 C
Solar/Wind Harmer
5.025
270499AE1-146 GEN
Solar/Wind Helper
0.511
24344105CKG2
50/50
6.335
270101X2-052 CT2
50/50
1.18
959331AF2-224 GEN
Solar/Wind Harmer
1.15
944541AF1-119 GEN
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
5.09
276843GEN-1.7
Solar/Wind Harmer
0.714
941551AE2-152 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
11.948
276882AE2-255 GEN
Solar/Wind Harmer
4.361
960441AF2-335 GEN
Solar/Wind Harmer
0.407
270223U2-072_GEN1
Solar/Wind Helper
0.133
966831AG1-554 GEN
Solar/Wind Helper
0.265
274854TWINGROVE;U2
Solar/Wind Harmer
7.034
270102X2-052 ST
50/50
1.277
970901AG2-562 GEN
50/50
4.84
960971AF2-388 GEN
Solar/Wind Harmer
16.413
970349AG2-230 GEN
Solar/Wind Harmer
0.729
971347AH1-153 GEN
Solar/Wind Harmer
0.729
961051AF2-396 GEN
Solar/Wind Harmer
0.97
961051AF2-396 GEN
Solar/Wind Harmer
7.761
270599AE1-208 GEN
Solar/Wind Harmer
0.373
970245AG2-165 GEN
Solar/Wind Harmer
0.894
972231SS25-0005
Solar/Wind Harmer
0.71
274862TOP CROP ;2U
Solar/Wind Harmer
6.862
970921AG2-575 GEN
Solar/Wind Harmer
0.413
970921AG2-575 GEN
Solar/Wind Harmer
1.652
274879MINONK ;1U
Solar/Wind Harmer
9.667
971411AH1-196 GEN
Solar/Wind Harmer
0.613
274855GSG-6 ;RU
Solar/Wind Harmer
5.182
24386405FR-21G C
Solar/Wind Harmer
3.045
942871AE2-306 GEN
Solar/Wind Helper
0.2
945641AF1-229 GEN
Solar/Wind Helper
0.422
270541AE2-072 C
Solar/Wind Helper
0.42
970615AG2-402 GEN
50/50
4.602
24729405KEY G3
50/50
6.868
24729505KEY G4
50/50
6.754
944961AF1-161 GEN
50/50
2.389
270043AE2-236 GEN
Solar/Wind Harmer
0.373
971771AH1-392 GEN
Solar/Wind Harmer
0.442
270505AE1-170 C O1
Solar/Wind Harmer
0.728
274888KELLY CRK;1U
Solar/Wind Harmer
8.779
970941AG2-585 GEN
Solar/Wind Harmer
0.541
971605AH1-302 GEN
Solar/Wind Harmer
6.341
276805AD2-038 GEN
Solar/Wind Harmer
7.5
274850MENDOTA H;RU
Solar/Wind Harmer
3.67
276861AD2-134 GEN
Solar/Wind Harmer
2.505
274864CRW2-WTG
Solar/Wind Harmer
7.688
970569AG2-363 GEN
Solar/Wind Harmer
1.205
274858EASY ROAD;U2
Solar/Wind Harmer
6.231
276157O29GEN1
Solar/Wind Harmer
5.735
957751AF2-069 GEN
Solar/Wind Harmer
0.514
939741AE1-205 GEN
Solar/Wind Harmer
0.773
246938BC-WTG3
Solar/Wind Helper
5.433
246936BC-WTG1
Solar/Wind Helper
5.496
965651AG1-433 GEN
Solar/Wind Harmer
8.207
270449AD2-020 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
9.896
943121AE2-341 GEN
Solar/Wind Harmer
0.633
970291AG2-192 GEN
Solar/Wind Harmer
0.054
970289AG2-191 GEN
Solar/Wind Harmer
0.55
957471AF2-041 GEN
Solar/Wind Harmer
1.217
274848CAMPGROVE;RU
Solar/Wind Harmer
7.073
959341AF2-225 GEN
Solar/Wind Harmer
0.58
957201AF2-014 GEN
Solar/Wind Helper
3.911
270284AF1-227 GEN1
Solar/Wind Helper
0.847
270428AC2-015 C
Solar/Wind Helper
0.344
960851AF2-376 GEN
50/50
2.119
965021AG1-366 GEN
Solar/Wind Harmer
4.602
958861AF2-177 GEN
Solar/Wind Harmer
15.941
945371AF1-202 GEN
Solar/Wind Harmer
7.519
276893AG1-478 C
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
1.242
270594AE1-207 GEN
Solar/Wind Harmer
0.66
270032AE2-172
Solar/Wind Harmer
3.298
971997AH1-543 GEN
Solar/Wind Harmer
0.645
276863AD2-134 GEN
Solar/Wind Harmer
2.505
274863CRW1-WTG
Solar/Wind Harmer
7.688
276889AE2-281 GEN
Solar/Wind Harmer
2.603
24691005MDL-2G C
Solar/Wind Harmer
5.104
274856ECOGROVE ;U1
Solar/Wind Harmer
4.705
971549AH1-272 GEN
Solar/Wind Harmer
0.738
276158O29GEN2
Solar/Wind Harmer
5.735
276708O09 GEN2
Solar/Wind Harmer
4.827
246937BC-WTG2
Solar/Wind Helper
5.496
270485AE1-090_GEN
Solar/Wind Helper
0.147
270063AE2-323 C
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0
970513AG2-328 GEN
Solar/Wind Harmer
0.894
970517AG2-330 GEN
Solar/Wind Harmer
13.95
959141AF2-205 GEN
Solar/Wind Harmer
0
970833AG2-524 GEN
Solar/Wind Harmer
0.467
958821AF2-173 GEN
Solar/Wind Harmer
0.58
962781AG1-127 GEN
Solar/Wind Harmer
0.393
971335AH1-147 GEN
Solar/Wind Harmer
0.816
24697605MDL-3G C
Solar/Wind Harmer
5.096
270181AB1-006 GEN2
Solar/Wind Harmer
0.634
971171AH1-044 GEN
Solar/Wind Harmer
0.811
926823AC1-168 GEN
Solar/Wind Harmer
4.923
24385905FR-11G C
Solar/Wind Harmer
5.987
276782AC1-033 GEN
Solar/Wind Harmer
5.11
24725505WLD G2 C
Solar/Wind Harmer
5.056
946321AF1-296 GEN
Solar/Wind Harmer
11.381
960611AF2-352 GEN
Solar/Wind Harmer
1.153
24653605MOTTVILLE
50/50
0.003
270100X2-052 CT1
50/50
1.18
24307105BERRINSP G
50/50
0.017
965011AG1-365 GEN
Solar/Wind Harmer
1.15
945111AF1-176 GEN
Solar/Wind Harmer
0.888
945111AF1-176 GEN
Solar/Wind Harmer
4.84
957891AF2-083 GEN
Solar/Wind Harmer
0
971769AH1-391 GEN
Solar/Wind Harmer
0.472
964861AG1-349 GEN
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
43.926
940581AE2-045 GEN
Solar/Wind Harmer
0
971177AH1-047 GEN
Solar/Wind Harmer
0.24
970825AG2-519 GEN
Solar/Wind Harmer
0.448
970825AG2-519 GEN
Solar/Wind Harmer
1.72
970571AG2-364 GEN
Solar/Wind Harmer
0.803
971681AH1-341 GEN
Solar/Wind Harmer
0.599
938861AE1-114 GEN
Solar/Wind Harmer
9.335
276603SUBLETTE C
Solar/Wind Harmer
1.356
253378AE2-206_GEN
Solar/Wind Helper
0.312
24641605TWIN BRNCH
50/50
0.015
24643105BUCHANAN
50/50
0.011
24344005CKG1
50/50
7.905
944531AF1-118 GEN
Solar/Wind Harmer
2.062
274887GEN-1.85
Solar/Wind Harmer
8.065
970707AG2-453 GEN
Solar/Wind Harmer
1.203
970833AG2-524 GEN
Solar/Wind Harmer
3.74
958481AF2-142 GEN
Solar/Wind Harmer
0.629
276868AE1-113 GEN
Solar/Wind Harmer
13.822
971675AH1-338 GEN
Solar/Wind Harmer
0.735
960791AF2-370 GEN
Solar/Wind Harmer
1.628
970781AG2-491 GEN
Solar/Wind Harmer
0.406
276903AD2-071 C
Solar/Wind Harmer
0.395
966841AG1-555 GEN
Solar/Wind Harmer
0
274853TWINGROVE;U1
Solar/Wind Harmer
9.371
270224U2-072_GEN2
Solar/Wind Helper
0.133
270391AF1-285 GEN3
Solar/Wind Helper
0.267
241847AF2-150_GEN
Solar/Wind Helper
0.239
971599AH1-298 GEN
50/50
10.386
960861AF2-377 GEN
50/50
2.413
24729305KEY G2
50/50
6.868
970611AG2-400 GEN
Solar/Wind Harmer
1.15
270071AF1-092 GEN
Solar/Wind Harmer
0.944
970321AG2-212 GEN
Solar/Wind Harmer
0.894
270005AE1-210 C O1
Solar/Wind Harmer
6.463
276602WESTBROOK C
Solar/Wind Harmer
2.858
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
0.594
276645AC1-214 GEN1
Solar/Wind Harmer
1.683
24387305FR-4G C
Solar/Wind Harmer
4.568
24386605FR-22G C
Solar/Wind Harmer
3.045
24387005FR-3G C
Solar/Wind Harmer
3.015
942111AE2-223 GEN
Solar/Wind Harmer
9.047
960841AF2-375 GEN
Solar/Wind Helper
0.529
970583AG2-370 GEN
50/50
2.823
970031AG2-029 GEN
Solar/Wind Harmer
2.112
270247TR4_N_V136
Solar/Wind Harmer
1.186
965051AG1-369 GEN
Solar/Wind Harmer
0.301
960591AF2-350 GEN
Solar/Wind Harmer
0.432
958381AF2-132 GEN
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
8.088
939401AE1-172 GEN
Solar/Wind Harmer
16.42
276876AE1-163_GEN2
Solar/Wind Harmer
9.109
274857EASY ROAD;U1
Solar/Wind Harmer
6.231
961761AG1-017 GEN
Solar/Wind Harmer
0.391
276656WTG2_EQ
Solar/Wind Harmer
0.882
941731AE2-173 GEN
Solar/Wind Harmer
3.866
270462AD2-086
Solar/Wind Helper
1.688
270317AD1-130_GEN
Solar/Wind Helper
1.101
270287AF1-227 GEN3
Solar/Wind Helper
0.313
970521AG2-332 GEN
50/50
10.877
247521TR3_G114
Solar/Wind Harmer
8.771
276806AD2-047 C O1
Solar/Wind Harmer
13.32
958391AF2-133 GEN
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
7.573
247642Z2-115 C
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.5
971341AH1-150 GEN
Solar/Wind Harmer
0.811
270302AB2-170 GEN
Solar/Wind Helper
1.101
270231U2-072_GEN5
Solar/Wind Helper
0.133
270471AD2-092_GEN
Solar/Wind Helper
0.383
957141AF2-008_MTX
Adder
27.935
944201AF1-088_MTX
Adder
55.87
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.901
WECLTFEXP_WEC->PJM
CLTF
2.651
LAGNLTFEXP_LAGN->PJM
CLTF
5.747
AH1-155LTFEXP_AH1-155->PJM
LTF
0.251
CBM West 1LTFEXP_CBM-W1->PJM
CBM
73.505
NYPJM->LTFIMP_NY
CLTF
1.226
TVALTFEXP_TVA->PJM
CLTF
2.31
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
23.037
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.599
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.014
SIGELTFEXP_SIGE->PJM
CLTF
0.2
CBM West 2LTFEXP_CBM-W2->PJM
CBM
51.154
LGEELTFEXP_LGEE->PJM
CLTF
1.819
MECLTFEXP_MEC->PJM
CLTF
9.7
AG2-052LTFEXP_AG2-052->PJM
LTF
0.167

Details for 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7441_05SORENS 765_J1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7441_05SORENS 765_J1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.82 %
Rating:1737.0 MVA
Rating Type:B
MVA to Mitigate:2011.72
MW Contribution:0.74
Bus #Bus NameTypeMW Contribution
972181SS23-001
Solar/Wind Harmer
0.444
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.311
970289AG2-191 GEN
Solar/Wind Harmer
0.079
24755605MDL-5G
Solar/Wind Harmer
3.365
959091AF2-200 GEN
Solar/Wind Harmer
0.811
946031AF1-268 GEN
Solar/Wind Harmer
0.329
274849CRESCENT ;1U
Solar/Wind Harmer
2.569
274877BISHOP HL;1U
Solar/Wind Harmer
4.523
270349AD2-093_GEN
Solar/Wind Helper
0.383
959331AF2-224 GEN
Solar/Wind Harmer
1.15
944541AF1-119 GEN
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
5.09
276843GEN-1.7
Solar/Wind Harmer
0.714
941551AE2-152 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
11.948
276882AE2-255 GEN
Solar/Wind Harmer
4.361
960441AF2-335 GEN
Solar/Wind Harmer
0.407
270223U2-072_GEN1
Solar/Wind Helper
0.133
966831AG1-554 GEN
Solar/Wind Helper
0.265
274854TWINGROVE;U2
Solar/Wind Harmer
7.034
960971AF2-388 GEN
Solar/Wind Harmer
16.413
970349AG2-230 GEN
Solar/Wind Harmer
0.729
971347AH1-153 GEN
Solar/Wind Harmer
0.729
961051AF2-396 GEN
Solar/Wind Harmer
0.97
961051AF2-396 GEN
Solar/Wind Harmer
7.761
270599AE1-208 GEN
Solar/Wind Harmer
0.373
970245AG2-165 GEN
Solar/Wind Harmer
0.894
972231SS25-0005
Solar/Wind Harmer
0.71
274862TOP CROP ;2U
Solar/Wind Harmer
6.862
970921AG2-575 GEN
Solar/Wind Harmer
0.413
970921AG2-575 GEN
Solar/Wind Harmer
1.652
274879MINONK ;1U
Solar/Wind Harmer
9.667
971411AH1-196 GEN
Solar/Wind Harmer
0.613
274855GSG-6 ;RU
Solar/Wind Harmer
5.182
24386405FR-21G C
Solar/Wind Harmer
3.045
942871AE2-306 GEN
Solar/Wind Helper
0.2
945641AF1-229 GEN
Solar/Wind Helper
0.422
270541AE2-072 C
Solar/Wind Helper
0.42
270063AE2-323 C
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0
970513AG2-328 GEN
Solar/Wind Harmer
0.894
970517AG2-330 GEN
Solar/Wind Harmer
13.95
959141AF2-205 GEN
Solar/Wind Harmer
0
970833AG2-524 GEN
Solar/Wind Harmer
0.467
958821AF2-173 GEN
Solar/Wind Harmer
0.58
962781AG1-127 GEN
Solar/Wind Harmer
0.393
971335AH1-147 GEN
Solar/Wind Harmer
0.816
24697605MDL-3G C
Solar/Wind Harmer
5.096
270181AB1-006 GEN2
Solar/Wind Harmer
0.634
971171AH1-044 GEN
Solar/Wind Harmer
0.811
926823AC1-168 GEN
Solar/Wind Harmer
4.923
24385905FR-11G C
Solar/Wind Harmer
5.987
276782AC1-033 GEN
Solar/Wind Harmer
5.11
24725505WLD G2 C
Solar/Wind Harmer
5.056
946321AF1-296 GEN
Solar/Wind Harmer
11.381
960611AF2-352 GEN
Solar/Wind Harmer
1.153
24641605TWIN BRNCH
50/50
0.015
944531AF1-118 GEN
Solar/Wind Harmer
2.062
274887GEN-1.85
Solar/Wind Harmer
8.065
970707AG2-453 GEN
Solar/Wind Harmer
1.203
970833AG2-524 GEN
Solar/Wind Harmer
3.74
958481AF2-142 GEN
Solar/Wind Harmer
0.629
276868AE1-113 GEN
Solar/Wind Harmer
13.822
971675AH1-338 GEN
Solar/Wind Harmer
0.735
960791AF2-370 GEN
Solar/Wind Harmer
1.628
970781AG2-491 GEN
Solar/Wind Harmer
0.406
276903AD2-071 C
Solar/Wind Harmer
0.395
966841AG1-555 GEN
Solar/Wind Harmer
0
274853TWINGROVE;U1
Solar/Wind Harmer
9.371
270224U2-072_GEN2
Solar/Wind Helper
0.133
270391AF1-285 GEN3
Solar/Wind Helper
0.267
241847AF2-150_GEN
Solar/Wind Helper
0.239
965651AG1-433 GEN
Solar/Wind Harmer
8.207
270449AD2-020 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
9.896
943121AE2-341 GEN
Solar/Wind Harmer
0.633
970291AG2-192 GEN
Solar/Wind Harmer
0.054
970289AG2-191 GEN
Solar/Wind Harmer
0.55
957471AF2-041 GEN
Solar/Wind Harmer
1.217
274848CAMPGROVE;RU
Solar/Wind Harmer
7.073
959341AF2-225 GEN
Solar/Wind Harmer
0.58
957201AF2-014 GEN
Solar/Wind Helper
3.911
270284AF1-227 GEN1
Solar/Wind Helper
0.847
270428AC2-015 C
Solar/Wind Helper
0.344
970583AG2-370 GEN
50/50
2.823
970031AG2-029 GEN
Solar/Wind Harmer
2.112
270247TR4_N_V136
Solar/Wind Harmer
1.186
965051AG1-369 GEN
Solar/Wind Harmer
0.301
960591AF2-350 GEN
Solar/Wind Harmer
0.432
958381AF2-132 GEN
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
8.088
939401AE1-172 GEN
Solar/Wind Harmer
16.42
276876AE1-163_GEN2
Solar/Wind Harmer
9.109
274857EASY ROAD;U1
Solar/Wind Harmer
6.231
961761AG1-017 GEN
Solar/Wind Harmer
0.391
276656WTG2_EQ
Solar/Wind Harmer
0.882
941731AE2-173 GEN
Solar/Wind Harmer
3.866
270462AD2-086
Solar/Wind Helper
1.688
270317AD1-130_GEN
Solar/Wind Helper
1.101
270287AF1-227 GEN3
Solar/Wind Helper
0.313
971599AH1-298 GEN
50/50
10.386
960861AF2-377 GEN
50/50
2.413
24729305KEY G2
50/50
6.868
970611AG2-400 GEN
Solar/Wind Harmer
1.15
270071AF1-092 GEN
Solar/Wind Harmer
0.944
970321AG2-212 GEN
Solar/Wind Harmer
0.894
270005AE1-210 C O1
Solar/Wind Harmer
6.463
276602WESTBROOK C
Solar/Wind Harmer
2.858
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
0.594
970615AG2-402 GEN
50/50
4.602
24729405KEY G3
50/50
6.868
24729505KEY G4
50/50
6.754
270043AE2-236 GEN
Solar/Wind Harmer
0.373
971771AH1-392 GEN
Solar/Wind Harmer
0.442
270505AE1-170 C O1
Solar/Wind Harmer
0.728
274888KELLY CRK;1U
Solar/Wind Harmer
8.779
970941AG2-585 GEN
Solar/Wind Harmer
0.541
971605AH1-302 GEN
Solar/Wind Harmer
6.341
276805AD2-038 GEN
Solar/Wind Harmer
7.5
274850MENDOTA H;RU
Solar/Wind Harmer
3.67
276861AD2-134 GEN
Solar/Wind Harmer
2.505
274864CRW2-WTG
Solar/Wind Harmer
7.688
970569AG2-363 GEN
Solar/Wind Harmer
1.205
274858EASY ROAD;U2
Solar/Wind Harmer
6.231
276157O29GEN1
Solar/Wind Harmer
5.735
957751AF2-069 GEN
Solar/Wind Harmer
0.514
939741AE1-205 GEN
Solar/Wind Harmer
0.773
246938BC-WTG3
Solar/Wind Helper
5.433
246936BC-WTG1
Solar/Wind Helper
5.496
24653605MOTTVILLE
50/50
0.003
965011AG1-365 GEN
Solar/Wind Harmer
1.15
945111AF1-176 GEN
Solar/Wind Harmer
0.888
945111AF1-176 GEN
Solar/Wind Harmer
4.84
957891AF2-083 GEN
Solar/Wind Harmer
0
971769AH1-391 GEN
Solar/Wind Harmer
0.472
964861AG1-349 GEN
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
43.926
940581AE2-045 GEN
Solar/Wind Harmer
0
971177AH1-047 GEN
Solar/Wind Harmer
0.24
970825AG2-519 GEN
Solar/Wind Harmer
0.448
970825AG2-519 GEN
Solar/Wind Harmer
1.72
970571AG2-364 GEN
Solar/Wind Harmer
0.803
971681AH1-341 GEN
Solar/Wind Harmer
0.599
938861AE1-114 GEN
Solar/Wind Harmer
9.335
276603SUBLETTE C
Solar/Wind Harmer
1.356
253378AE2-206_GEN
Solar/Wind Helper
0.312
960851AF2-376 GEN
50/50
2.119
965021AG1-366 GEN
Solar/Wind Harmer
4.602
958861AF2-177 GEN
Solar/Wind Harmer
15.941
945371AF1-202 GEN
Solar/Wind Harmer
7.519
276893AG1-478 C
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
1.242
270594AE1-207 GEN
Solar/Wind Harmer
0.66
270032AE2-172
Solar/Wind Harmer
3.298
971997AH1-543 GEN
Solar/Wind Harmer
0.645
276863AD2-134 GEN
Solar/Wind Harmer
2.505
274863CRW1-WTG
Solar/Wind Harmer
7.688
276889AE2-281 GEN
Solar/Wind Harmer
2.603
24691005MDL-2G C
Solar/Wind Harmer
5.104
274856ECOGROVE ;U1
Solar/Wind Harmer
4.705
971549AH1-272 GEN
Solar/Wind Harmer
0.738
276158O29GEN2
Solar/Wind Harmer
5.735
276708O09 GEN2
Solar/Wind Harmer
4.827
246937BC-WTG2
Solar/Wind Helper
5.496
270485AE1-090_GEN
Solar/Wind Helper
0.147
276645AC1-214 GEN1
Solar/Wind Harmer
1.683
24387305FR-4G C
Solar/Wind Harmer
4.568
24386605FR-22G C
Solar/Wind Harmer
3.045
24387005FR-3G C
Solar/Wind Harmer
3.015
942111AE2-223 GEN
Solar/Wind Harmer
9.047
960841AF2-375 GEN
Solar/Wind Helper
0.529
247620Y3-023
50/50
0.466
965041AG1-368 GEN
Solar/Wind Harmer
0.706
270191TR4_S_V150
Solar/Wind Harmer
6.54
965101AG1-375 GEN
Solar/Wind Harmer
0.511
960681AF2-359 GEN
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
0.373
971917AH1-482 GEN
Solar/Wind Harmer
6.726
276691AA1-018 GEN1
Solar/Wind Harmer
0.451
970115AG2-085 GEN
Solar/Wind Harmer
0.163
276872AE1-163_GEN1
Solar/Wind Harmer
9.109
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
10.701
971067AG2-660 GEN
Solar/Wind Harmer
1.622
276741O09 GEN1
Solar/Wind Harmer
4.827
276655WTG1_EQ
Solar/Wind Harmer
6.657
270578AF1-285 GEN2
Solar/Wind Helper
0.267
247522W1-056 GEN
Solar/Wind Helper
1.806
270286AF1-227 GEN2
Solar/Wind Helper
0.313
961961AG1-039 GEN
Solar/Wind Helper
0.152
241960AC2-195 GEN
Solar/Wind Helper
0.26
24729205KEY G1
50/50
6.754
270526AF1-158 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
0.936
964401AG1-302 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
8.261
270004AE1-209 GEN
Solar/Wind Harmer
6.463
274872LEEDK;1U
Solar/Wind Harmer
0.181
270180AB1-006 GEN1
Solar/Wind Harmer
9.562
24791305MDL-5G
Solar/Wind Harmer
3.365
959081AF2-199 GEN
Solar/Wind Harmer
0.406
971475AH1-234 GEN
Solar/Wind Harmer
0.898
276646AC1-214 GEN2
Solar/Wind Harmer
1.683
24386205FR-12G C
Solar/Wind Harmer
3.179
276726Z2-087_GEN
Solar/Wind Harmer
10.052
971617AH1-308 GEN
Solar/Wind Harmer
5.201
943021AE2-325 GEN
Solar/Wind Harmer
2.992
958011AF2-095 GEN
Solar/Wind Harmer
0.623
971573AH1-285 GEN
Solar/Wind Harmer
0.361
945421AF1-207 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
0.621
942991AE2-321 GEN
Solar/Wind Harmer
0.41
971333AH1-146 GEN
Solar/Wind Harmer
0.816
24697905MDL-4G C
Solar/Wind Harmer
3.365
970819AG2-516 GEN
Solar/Wind Harmer
0.483
964611AG1-324 GEN
Solar/Wind Harmer
0.357
270201AC2-176 GEN
Solar/Wind Harmer
6.697
274851PROVIDENC;RU
Solar/Wind Harmer
3.718
274878BISHOP HL;2U
Solar/Wind Harmer
4.523
24699105WLD G1 C
Solar/Wind Harmer
5.025
270499AE1-146 GEN
Solar/Wind Helper
0.511
970521AG2-332 GEN
50/50
10.877
247521TR3_G114
Solar/Wind Harmer
8.771
276806AD2-047 C O1
Solar/Wind Harmer
13.32
958391AF2-133 GEN
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
7.573
247642Z2-115 C
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.5
971341AH1-150 GEN
Solar/Wind Harmer
0.811
270302AB2-170 GEN
Solar/Wind Helper
1.101
270231U2-072_GEN5
Solar/Wind Helper
0.133
270471AD2-092_GEN
Solar/Wind Helper
0.383
24639705ELKHART HY
50/50
0.15
963791AG1-232 GEN
Solar/Wind Harmer
0.972
270246TR4_N_V150
Solar/Wind Harmer
1.186
24695305TIMB G C
Solar/Wind Harmer
9.919
270024AE2-089 GEN
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
0.578
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
943591AF1-030 GEN
Solar/Wind Harmer
0.422
965031AG1-367 GEN
Solar/Wind Harmer
0.414
276901AD2-066 C O1
Solar/Wind Harmer
0
971343AH1-151 GEN
Solar/Wind Harmer
0.811
970169AG2-114 GEN
Solar/Wind Harmer
0.401
961011AF2-392 GEN
Solar/Wind Harmer
12.249
270227U2-072_GEN3
Solar/Wind Helper
0.133
270228U2-072_GEN4
Solar/Wind Helper
0.133
276820AF1-078_GEN
Solar/Wind Helper
0.141
944201AF1-088_MTX
Adder
55.87
957141AF2-008_MTX
Adder
27.935
CBM West 1LTFEXP_CBM-W1->PJM
CBM
73.505
NYPJM->LTFIMP_NY
CLTF
1.226
TVALTFEXP_TVA->PJM
CLTF
2.31
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
23.037
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.901
WECLTFEXP_WEC->PJM
CLTF
2.651
LAGNLTFEXP_LAGN->PJM
CLTF
5.747
AH1-155LTFEXP_AH1-155->PJM
LTF
0.251
CBM West 2LTFEXP_CBM-W2->PJM
CBM
51.154
LGEELTFEXP_LGEE->PJM
CLTF
1.819
MECLTFEXP_MEC->PJM
CLTF
9.7
AG2-052LTFEXP_AG2-052->PJM
LTF
0.167
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.599
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.014
SIGELTFEXP_SIGE->PJM
CLTF
0.2

Details for 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7446_05MARYSV 765_B2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.73 %
Rating:1737.0 MVA
Rating Type:B
MVA to Mitigate:2010.18
MW Contribution:0.7
Bus #Bus NameTypeMW Contribution
972181SS23-001
Solar/Wind Harmer
0.429
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.267
970289AG2-191 GEN
Solar/Wind Harmer
0.076
24755605MDL-5G
Solar/Wind Harmer
3.247
959091AF2-200 GEN
Solar/Wind Harmer
0.783
946031AF1-268 GEN
Solar/Wind Harmer
0.315
274849CRESCENT ;1U
Solar/Wind Harmer
2.48
274877BISHOP HL;1U
Solar/Wind Harmer
4.366
270349AD2-093_GEN
Solar/Wind Helper
0.507
959331AF2-224 GEN
Solar/Wind Harmer
1.126
944541AF1-119 GEN
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
4.913
276843GEN-1.7
Solar/Wind Harmer
0.69
941551AE2-152 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
11.537
276882AE2-255 GEN
Solar/Wind Harmer
4.21
960441AF2-335 GEN
Solar/Wind Harmer
0.39
270223U2-072_GEN1
Solar/Wind Helper
0.148
966831AG1-554 GEN
Solar/Wind Helper
0.282
274854TWINGROVE;U2
Solar/Wind Harmer
5.982
960971AF2-388 GEN
Solar/Wind Harmer
15.869
970349AG2-230 GEN
Solar/Wind Harmer
0.705
971347AH1-153 GEN
Solar/Wind Harmer
0.705
961051AF2-396 GEN
Solar/Wind Harmer
0.936
961051AF2-396 GEN
Solar/Wind Harmer
7.484
270599AE1-208 GEN
Solar/Wind Harmer
0.359
970245AG2-165 GEN
Solar/Wind Harmer
0.864
972231SS25-0005
Solar/Wind Harmer
0.686
274862TOP CROP ;2U
Solar/Wind Harmer
6.626
970921AG2-575 GEN
Solar/Wind Harmer
0.399
970921AG2-575 GEN
Solar/Wind Harmer
1.595
274879MINONK ;1U
Solar/Wind Harmer
9.334
971411AH1-196 GEN
Solar/Wind Harmer
0.592
274855GSG-6 ;RU
Solar/Wind Harmer
5.004
24386405FR-21G C
Solar/Wind Harmer
2.937
942871AE2-306 GEN
Solar/Wind Helper
0.222
945641AF1-229 GEN
Solar/Wind Helper
0.452
270541AE2-072 C
Solar/Wind Helper
0.467
270063AE2-323 C
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0
970513AG2-328 GEN
Solar/Wind Harmer
0.864
970517AG2-330 GEN
Solar/Wind Harmer
13.48
959141AF2-205 GEN
Solar/Wind Harmer
0
970833AG2-524 GEN
Solar/Wind Harmer
0.451
962781AG1-127 GEN
Solar/Wind Harmer
0.379
958821AF2-173 GEN
Solar/Wind Harmer
0.557
971335AH1-147 GEN
Solar/Wind Harmer
0.788
24697605MDL-3G C
Solar/Wind Harmer
4.918
270181AB1-006 GEN2
Solar/Wind Harmer
0.612
971171AH1-044 GEN
Solar/Wind Harmer
0.783
926823AC1-168 GEN
Solar/Wind Harmer
4.753
24385905FR-11G C
Solar/Wind Harmer
5.774
276782AC1-033 GEN
Solar/Wind Harmer
4.932
24725505WLD G2 C
Solar/Wind Harmer
4.854
946321AF1-296 GEN
Solar/Wind Harmer
10.986
958581AF2-149 GEN
Solar/Wind Helper
0.21
960611AF2-352 GEN
Solar/Wind Harmer
0.98
944531AF1-118 GEN
Solar/Wind Harmer
1.998
274887GEN-1.85
Solar/Wind Harmer
7.789
970707AG2-453 GEN
Solar/Wind Harmer
1.162
970833AG2-524 GEN
Solar/Wind Harmer
3.611
958481AF2-142 GEN
Solar/Wind Harmer
0.607
276868AE1-113 GEN
Solar/Wind Harmer
13.346
971675AH1-338 GEN
Solar/Wind Harmer
0.709
970781AG2-491 GEN
Solar/Wind Harmer
0.392
960791AF2-370 GEN
Solar/Wind Harmer
1.562
276903AD2-071 C
Solar/Wind Harmer
0.38
966841AG1-555 GEN
Solar/Wind Harmer
0
274853TWINGROVE;U1
Solar/Wind Harmer
9.04
270224U2-072_GEN2
Solar/Wind Helper
0.148
270391AF1-285 GEN3
Solar/Wind Helper
0.296
241847AF2-150_GEN
Solar/Wind Helper
0.259
965651AG1-433 GEN
Solar/Wind Harmer
7.934
270449AD2-020 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
9.557
943121AE2-341 GEN
Solar/Wind Harmer
0.611
970291AG2-192 GEN
Solar/Wind Harmer
0.052
970289AG2-191 GEN
Solar/Wind Harmer
0.529
957471AF2-041 GEN
Solar/Wind Harmer
1.175
274848CAMPGROVE;RU
Solar/Wind Harmer
6.827
959341AF2-225 GEN
Solar/Wind Harmer
0.56
957201AF2-014 GEN
Solar/Wind Helper
3.962
270284AF1-227 GEN1
Solar/Wind Helper
1.019
270428AC2-015 C
Solar/Wind Helper
0.368
253383AE2-342_GEN
Solar/Wind Helper
0.101
970583AG2-370 GEN
50/50
2.718
970031AG2-029 GEN
Solar/Wind Harmer
2.053
270247TR4_N_V136
Solar/Wind Harmer
1.13
965051AG1-369 GEN
Solar/Wind Harmer
0.287
960591AF2-350 GEN
Solar/Wind Harmer
0.418
958381AF2-132 GEN
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
7.81
939401AE1-172 GEN
Solar/Wind Harmer
15.852
276876AE1-163_GEN2
Solar/Wind Harmer
8.794
274857EASY ROAD;U1
Solar/Wind Harmer
6.016
961761AG1-017 GEN
Solar/Wind Harmer
0.372
276656WTG2_EQ
Solar/Wind Harmer
0.85
941731AE2-173 GEN
Solar/Wind Harmer
3.73
270462AD2-086
Solar/Wind Helper
1.844
270317AD1-130_GEN
Solar/Wind Helper
1.203
270287AF1-227 GEN3
Solar/Wind Helper
0.376
970615AG2-402 GEN
50/50
4.505
24729405KEY G3
50/50
6.653
24729505KEY G4
50/50
6.542
270043AE2-236 GEN
Solar/Wind Harmer
0.362
971771AH1-392 GEN
Solar/Wind Harmer
0.427
270505AE1-170 C O1
Solar/Wind Harmer
0.702
274888KELLY CRK;1U
Solar/Wind Harmer
8.479
970941AG2-585 GEN
Solar/Wind Harmer
0.522
971605AH1-302 GEN
Solar/Wind Harmer
6.121
276805AD2-038 GEN
Solar/Wind Harmer
7.241
274850MENDOTA H;RU
Solar/Wind Harmer
3.544
276861AD2-134 GEN
Solar/Wind Harmer
2.419
274864CRW2-WTG
Solar/Wind Harmer
7.421
970569AG2-363 GEN
Solar/Wind Harmer
1.163
274858EASY ROAD;U2
Solar/Wind Harmer
6.016
276157O29GEN1
Solar/Wind Harmer
5.536
957751AF2-069 GEN
Solar/Wind Harmer
0.496
939741AE1-205 GEN
Solar/Wind Harmer
0.746
246938BC-WTG3
Solar/Wind Helper
5.504
246936BC-WTG1
Solar/Wind Helper
5.567
24653605MOTTVILLE
50/50
0.003
965011AG1-365 GEN
Solar/Wind Harmer
1.126
945111AF1-176 GEN
Solar/Wind Harmer
0.857
945111AF1-176 GEN
Solar/Wind Harmer
4.67
957891AF2-083 GEN
Solar/Wind Harmer
0
971769AH1-391 GEN
Solar/Wind Harmer
0.456
964861AG1-349 GEN
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
42.42
940581AE2-045 GEN
Solar/Wind Harmer
0
971177AH1-047 GEN
Solar/Wind Harmer
0.232
970571AG2-364 GEN
Solar/Wind Harmer
0.776
970825AG2-519 GEN
Solar/Wind Harmer
0.43
970825AG2-519 GEN
Solar/Wind Harmer
1.65
971681AH1-341 GEN
Solar/Wind Harmer
0.578
938861AE1-114 GEN
Solar/Wind Harmer
9.013
276603SUBLETTE C
Solar/Wind Harmer
1.309
253378AE2-206_GEN
Solar/Wind Helper
0.35
960851AF2-376 GEN
50/50
2.006
965021AG1-366 GEN
Solar/Wind Harmer
4.505
958861AF2-177 GEN
Solar/Wind Harmer
15.401
945371AF1-202 GEN
Solar/Wind Harmer
7.254
276893AG1-478 C
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
1.199
957841AF2-078 GEN
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
0.634
270032AE2-172
Solar/Wind Harmer
3.17
971997AH1-543 GEN
Solar/Wind Harmer
0.623
276863AD2-134 GEN
Solar/Wind Harmer
2.419
274863CRW1-WTG
Solar/Wind Harmer
7.421
276889AE2-281 GEN
Solar/Wind Harmer
2.513
24691005MDL-2G C
Solar/Wind Harmer
4.926
274856ECOGROVE ;U1
Solar/Wind Harmer
4.543
971549AH1-272 GEN
Solar/Wind Harmer
0.704
276158O29GEN2
Solar/Wind Harmer
5.536
276708O09 GEN2
Solar/Wind Harmer
4.66
246937BC-WTG2
Solar/Wind Helper
5.567
270485AE1-090_GEN
Solar/Wind Helper
0.16
971599AH1-298 GEN
50/50
10.098
960861AF2-377 GEN
50/50
2.301
24729305KEY G2
50/50
6.653
970611AG2-400 GEN
Solar/Wind Harmer
1.126
270071AF1-092 GEN
Solar/Wind Harmer
0.917
970321AG2-212 GEN
Solar/Wind Harmer
0.864
270005AE1-210 C O1
Solar/Wind Harmer
6.21
276602WESTBROOK C
Solar/Wind Harmer
2.759
276645AC1-214 GEN1
Solar/Wind Harmer
1.624
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
0.566
24387305FR-4G C
Solar/Wind Harmer
4.405
24386605FR-22G C
Solar/Wind Harmer
2.937
24387005FR-3G C
Solar/Wind Harmer
2.908
942111AE2-223 GEN
Solar/Wind Harmer
8.728
960841AF2-375 GEN
Solar/Wind Helper
0.566
247620Y3-023
50/50
0.451
965041AG1-368 GEN
Solar/Wind Harmer
0.679
270191TR4_S_V150
Solar/Wind Harmer
6.235
965101AG1-375 GEN
Solar/Wind Harmer
0.494
960681AF2-359 GEN
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
0.359
971917AH1-482 GEN
Solar/Wind Harmer
6.492
276691AA1-018 GEN1
Solar/Wind Harmer
0.436
276872AE1-163_GEN1
Solar/Wind Harmer
8.794
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
10.326
971067AG2-660 GEN
Solar/Wind Harmer
1.567
970115AG2-085 GEN
Solar/Wind Harmer
0.156
276741O09 GEN1
Solar/Wind Harmer
4.66
276655WTG1_EQ
Solar/Wind Harmer
6.423
270578AF1-285 GEN2
Solar/Wind Helper
0.296
270286AF1-227 GEN2
Solar/Wind Helper
0.376
247522W1-056 GEN
Solar/Wind Helper
1.925
961961AG1-039 GEN
Solar/Wind Helper
0.165
241960AC2-195 GEN
Solar/Wind Helper
0.292
24729205KEY G1
50/50
6.542
270526AF1-158 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
0.904
964401AG1-302 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
7.977
270004AE1-209 GEN
Solar/Wind Harmer
6.21
274872LEEDK;1U
Solar/Wind Harmer
0.175
270180AB1-006 GEN1
Solar/Wind Harmer
9.228
24791305MDL-5G
Solar/Wind Harmer
3.247
959081AF2-199 GEN
Solar/Wind Harmer
0.392
971475AH1-234 GEN
Solar/Wind Harmer
0.867
276646AC1-214 GEN2
Solar/Wind Harmer
1.624
24386205FR-12G C
Solar/Wind Harmer
3.066
276726Z2-087_GEN
Solar/Wind Harmer
9.698
971617AH1-308 GEN
Solar/Wind Harmer
4.999
943021AE2-325 GEN
Solar/Wind Harmer
2.884
958011AF2-095 GEN
Solar/Wind Harmer
0.601
971573AH1-285 GEN
Solar/Wind Harmer
0.349
945421AF1-207 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
0.599
942991AE2-321 GEN
Solar/Wind Harmer
0.396
971333AH1-146 GEN
Solar/Wind Harmer
0.788
24697905MDL-4G C
Solar/Wind Harmer
3.247
970819AG2-516 GEN
Solar/Wind Harmer
0.466
274851PROVIDENC;RU
Solar/Wind Harmer
3.588
964611AG1-324 GEN
Solar/Wind Harmer
0.34
270201AC2-176 GEN
Solar/Wind Harmer
6.374
274878BISHOP HL;2U
Solar/Wind Harmer
4.366
24699105WLD G1 C
Solar/Wind Harmer
4.824
965931AG1-462 GEN
Solar/Wind Harmer
0.935
270499AE1-146 GEN
Solar/Wind Helper
0.547
970521AG2-332 GEN
50/50
10.52
247521TR3_G114
Solar/Wind Harmer
8.362
276806AD2-047 C O1
Solar/Wind Harmer
12.864
958391AF2-133 GEN
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
7.313
247642Z2-115 C
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.481
971341AH1-150 GEN
Solar/Wind Harmer
0.783
270302AB2-170 GEN
Solar/Wind Helper
1.203
270231U2-072_GEN5
Solar/Wind Helper
0.148
270471AD2-092_GEN
Solar/Wind Helper
0.507
24639705ELKHART HY
50/50
0.145
963791AG1-232 GEN
Solar/Wind Harmer
0.942
270246TR4_N_V150
Solar/Wind Harmer
1.13
24695305TIMB G C
Solar/Wind Harmer
9.393
270024AE2-089 GEN
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
0.558
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
943591AF1-030 GEN
Solar/Wind Harmer
0.408
276901AD2-066 C O1
Solar/Wind Harmer
0
965031AG1-367 GEN
Solar/Wind Harmer
0.398
971343AH1-151 GEN
Solar/Wind Harmer
0.783
970169AG2-114 GEN
Solar/Wind Harmer
0.387
961011AF2-392 GEN
Solar/Wind Harmer
11.826
270227U2-072_GEN3
Solar/Wind Helper
0.148
270228U2-072_GEN4
Solar/Wind Helper
0.148
276820AF1-078_GEN
Solar/Wind Helper
0.158
957141AF2-008_MTX
Adder
26.838
944201AF1-088_MTX
Adder
53.676
CBM West 2LTFEXP_CBM-W2->PJM
CBM
49.277
LGEELTFEXP_LGEE->PJM
CLTF
1.703
LAGNLTFEXP_LAGN->PJM
CLTF
5.561
AH1-155LTFEXP_AH1-155->PJM
LTF
0.242
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.712
TVALTFEXP_TVA->PJM
CLTF
2.237
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
23.26
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.562
WECLTFEXP_WEC->PJM
CLTF
2.559
SIGELTFEXP_SIGE->PJM
CLTF
0.191
CBM West 1LTFEXP_CBM-W1->PJM
CBM
69.912
NYPJM->LTFIMP_NY
CLTF
1.178
MECLTFEXP_MEC->PJM
CLTF
9.361
AG2-052LTFEXP_AG2-052->PJM
LTF
0.161

Details for 05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#6189_05HANG R 765_D1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.6 %
Rating:5133.0 MVA
Rating Type:B
MVA to Mitigate:5266.31
MW Contribution:1.47
Bus #Bus NameTypeMW Contribution
970707AG2-453 GEN
Solar/Wind Harmer
3.125
274887GEN-1.85
Solar/Wind Harmer
20.194
970833AG2-524 GEN
Solar/Wind Harmer
9.508
958481AF2-142 GEN
Solar/Wind Harmer
1.565
971675AH1-338 GEN
Solar/Wind Harmer
1.855
276868AE1-113 GEN
Solar/Wind Harmer
34.455
274853TWINGROVE;U1
Solar/Wind Harmer
22.608
970781AG2-491 GEN
Solar/Wind Harmer
0.872
966841AG1-555 GEN
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
5.617
965911AG1-460 GEN
Solar/Wind Harmer
1.874
970699AG2-449 GEN
Solar/Wind Harmer
0.844
274777LINCOLN ;8U
50/50
17.743
970245AG2-165 GEN
Solar/Wind Harmer
2.77
970349AG2-230 GEN
Solar/Wind Harmer
1.782
971347AH1-153 GEN
Solar/Wind Harmer
1.782
972231SS25-0005
Solar/Wind Harmer
1.7
970921AG2-575 GEN
Solar/Wind Harmer
1.047
970921AG2-575 GEN
Solar/Wind Harmer
4.187
274862TOP CROP ;2U
Solar/Wind Harmer
17.071
274855GSG-6 ;RU
Solar/Wind Harmer
13.081
971411AH1-196 GEN
Solar/Wind Harmer
1.544
274879MINONK ;1U
Solar/Wind Harmer
24.098
961051AF2-396 GEN
Solar/Wind Harmer
1.802
961051AF2-396 GEN
Solar/Wind Harmer
14.419
276763AC1-053 GEN1
Solar/Wind Harmer
10.839
24386405FR-21G C
Solar/Wind Harmer
6.45
274775LINCOLN ;6U
50/50
17.743
939351AE1-166 GEN
Solar/Wind Harmer
0
960591AF2-350 GEN
Solar/Wind Harmer
1.083
276694AA1-018 GEN2
Solar/Wind Harmer
20.135
939401AE1-172 GEN
Solar/Wind Harmer
41.242
276876AE1-163_GEN2
Solar/Wind Harmer
22.567
274857EASY ROAD;U1
Solar/Wind Harmer
15.572
958381AF2-132 GEN
Solar/Wind Harmer
0
276656WTG2_EQ
Solar/Wind Harmer
2.142
941731AE2-173 GEN
Solar/Wind Harmer
9.395
970519AG2-331 GEN
Solar/Wind Harmer
21.953
970513AG2-328 GEN
Solar/Wind Harmer
2.77
970517AG2-330 GEN
Solar/Wind Harmer
43.205
970833AG2-524 GEN
Solar/Wind Harmer
1.188
962781AG1-127 GEN
Solar/Wind Harmer
0.996
971335AH1-147 GEN
Solar/Wind Harmer
2.057
971171AH1-044 GEN
Solar/Wind Harmer
2.042
926823AC1-168 GEN
Solar/Wind Harmer
12.228
276782AC1-033 GEN
Solar/Wind Harmer
12.583
946321AF1-296 GEN
Solar/Wind Harmer
28.079
959141AF2-205 GEN
Solar/Wind Harmer
0
959611AF2-252 GEN
Solar/Wind Harmer
3.666
960611AF2-352 GEN
Solar/Wind Harmer
3.666
24697605MDL-3G C
Solar/Wind Harmer
10.929
270181AB1-006 GEN2
Solar/Wind Harmer
1.36
963831AG1-236 GEN
Solar/Wind Harmer
23.413
24385905FR-11G C
Solar/Wind Harmer
12.68
274770LINCOLN ;1U
50/50
17.743
274771LINCOLN ;2U
50/50
17.743
276897AD1-100 C
Solar/Wind Harmer
111.579
971177AH1-047 GEN
Solar/Wind Harmer
0.606
971769AH1-391 GEN
Solar/Wind Harmer
1.013
971681AH1-341 GEN
Solar/Wind Harmer
1.498
938861AE1-114 GEN
Solar/Wind Harmer
23.354
970571AG2-364 GEN
Solar/Wind Harmer
1.986
276603SUBLETTE C
Solar/Wind Harmer
3.386
964861AG1-349 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
1.567
945111AF1-176 GEN
Solar/Wind Harmer
8.54
972175AH1-670 GEN
Solar/Wind Harmer
34.173
276174W4-005 GEN2
Solar/Wind Harmer
8.359
276621W2-048 GEN
Solar/Wind Harmer
17.721
970321AG2-212 GEN
Solar/Wind Harmer
2.77
276602WESTBROOK C
Solar/Wind Harmer
7.213
276645AC1-214 GEN1
Solar/Wind Harmer
4.147
942111AE2-223 GEN
Solar/Wind Harmer
21.983
24387305FR-4G C
Solar/Wind Harmer
9.674
24386605FR-22G C
Solar/Wind Harmer
6.45
24387005FR-3G C
Solar/Wind Harmer
6.385
970333AG2-219 GEN
Solar/Wind Harmer
2.322
274773LINCOLN ;4U
50/50
17.743
972259AH1-714 GEN
50/50
37.165
276893AG1-478 C
Solar/Wind Harmer
-0.001
962691AG1-118 GEN
Solar/Wind Harmer
3.151
276863AD2-134 GEN
Solar/Wind Harmer
6.323
971997AH1-543 GEN
Solar/Wind Harmer
1.619
274863CRW1-WTG
Solar/Wind Harmer
19.177
276889AE2-281 GEN
Solar/Wind Harmer
6.448
274856ECOGROVE ;U1
Solar/Wind Harmer
11.794
276158O29GEN2
Solar/Wind Harmer
14.241
276708O09 GEN2
Solar/Wind Harmer
11.987
957841AF2-078 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
10.946
274880W4-005 GEN4
Solar/Wind Harmer
8.359
971993AH1-541 GEN
Solar/Wind Harmer
0.777
276838X2-022 GEN2
Solar/Wind Harmer
0.667
971549AH1-272 GEN
Solar/Wind Harmer
1.468
942481AE2-261 GEN
Solar/Wind Harmer
2.334
970239AG2-162 GEN
Solar/Wind Harmer
0.809
274772LINCOLN ;3U
50/50
17.743
274774LINCOLN ;5U
50/50
17.743
274660LASCO STA;1U
50/50
14.291
274888KELLY CRK;1U
Solar/Wind Harmer
21.983
970941AG2-585 GEN
Solar/Wind Harmer
1.354
274850MENDOTA H;RU
Solar/Wind Harmer
9.265
276861AD2-134 GEN
Solar/Wind Harmer
6.323
276805AD2-038 GEN
Solar/Wind Harmer
18.633
274864CRW2-WTG
Solar/Wind Harmer
19.177
274858EASY ROAD;U2
Solar/Wind Harmer
15.572
970569AG2-363 GEN
Solar/Wind Harmer
2.979
276157O29GEN1
Solar/Wind Harmer
14.241
957751AF2-069 GEN
Solar/Wind Harmer
1.266
971771AH1-392 GEN
Solar/Wind Harmer
0.857
939741AE1-205 GEN
Solar/Wind Harmer
1.879
270505AE1-170 C O1
Solar/Wind Harmer
1.392
971605AH1-302 GEN
Solar/Wind Harmer
13.868
276668AB2-070 GEN1
Solar/Wind Harmer
6.355
970243AG2-164 GEN
Solar/Wind Harmer
1.9
24344105CKG2
50/50
19.079
941551AE2-152 GEN
Solar/Wind Harmer
0
276843GEN-1.7
Solar/Wind Harmer
1.789
965791AG1-447 GEN
Solar/Wind Harmer
11.789
274872LEEDK;1U
Solar/Wind Harmer
30.269
276882AE2-255 GEN
Solar/Wind Harmer
10.87
274854TWINGROVE;U2
Solar/Wind Harmer
22.37
274776LINCOLN ;7U
50/50
17.743
274872LEEDK;1U
Solar/Wind Harmer
0.459
274861TOP CROP ;1U
Solar/Wind Harmer
20.552
959081AF2-199 GEN
Solar/Wind Harmer
1.021
970373AG2-245 GEN
Solar/Wind Harmer
2.116
971475AH1-234 GEN
Solar/Wind Harmer
2.251
270526AF1-158 GEN
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
4.147
964401AG1-302 GEN
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
24.426
270180AB1-006 GEN1
Solar/Wind Harmer
20.507
24791305MDL-5G
Solar/Wind Harmer
7.216
276764AC1-053 GEN2
Solar/Wind Harmer
10.839
24386205FR-12G C
Solar/Wind Harmer
6.733
276911AD2-131_GEN
Solar/Wind Harmer
0.385
274661LASCO STA;2U
50/50
14.329
958011AF2-095 GEN
Solar/Wind Harmer
1.559
971573AH1-285 GEN
Solar/Wind Harmer
0.923
942991AE2-321 GEN
Solar/Wind Harmer
1.035
971333AH1-146 GEN
Solar/Wind Harmer
2.057
958491AF2-143 GEN
Solar/Wind Harmer
1.543
970819AG2-516 GEN
Solar/Wind Harmer
1.21
274851PROVIDENC;RU
Solar/Wind Harmer
9.161
274878BISHOP HL;2U
Solar/Wind Harmer
11.138
965931AG1-462 GEN
Solar/Wind Harmer
2.385
965091AG1-374 GEN
Solar/Wind Harmer
2.75
943021AE2-325 GEN
Solar/Wind Harmer
5.731
945421AF1-207 GEN
Solar/Wind Harmer
0
24697905MDL-4G C
Solar/Wind Harmer
7.216
960681AF2-359 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.124
971067AG2-660 GEN
Solar/Wind Harmer
4.083
276872AE1-163_GEN1
Solar/Wind Harmer
22.567
276741O09 GEN1
Solar/Wind Harmer
11.987
971917AH1-482 GEN
Solar/Wind Harmer
14.894
276655WTG1_EQ
Solar/Wind Harmer
16.177
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
22.949
276686W4-005 GEN3
Solar/Wind Harmer
8.359
963841AG1-237 GEN
Solar/Wind Harmer
24.696
943591AF1-030 GEN
Solar/Wind Harmer
1.081
965681AG1-436 GEN
Solar/Wind Harmer
1.34
276901AD2-066 C O1
Solar/Wind Harmer
0
971343AH1-151 GEN
Solar/Wind Harmer
2.042
970169AG2-114 GEN
Solar/Wind Harmer
0.992
961011AF2-392 GEN
Solar/Wind Harmer
30.53
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
276785W4-005 GEN1
Solar/Wind Harmer
8.359
972207SS24-0001
Solar/Wind Harmer
3.457
972181SS23-001
Solar/Wind Harmer
1.063
959091AF2-200 GEN
Solar/Wind Harmer
2.042
270055AF2-134 C O1
Solar/Wind Harmer
0
274849CRESCENT ;1U
Solar/Wind Harmer
6.331
274877BISHOP HL;1U
Solar/Wind Harmer
11.138
24755605MDL-5G
Solar/Wind Harmer
7.216
276916AD2-100_GEN
Solar/Wind Harmer
1.619
943121AE2-341 GEN
Solar/Wind Harmer
1.622
274871GR RIDGE ;2U
Solar/Wind Harmer
25.172
957471AF2-041 GEN
Solar/Wind Harmer
3.063
274848CAMPGROVE;RU
Solar/Wind Harmer
17.376
959341AF2-225 GEN
Solar/Wind Harmer
1.409
270449AD2-020 GEN
Solar/Wind Harmer
0
276849AB2-070 GEN2
Solar/Wind Harmer
6.355
276806AD2-047 C O1
Solar/Wind Harmer
33.354
274847GR RIDGE ;BU
Solar/Wind Harmer
19.263
971341AH1-150 GEN
Solar/Wind Harmer
2.042
958391AF2-133 GEN
Solar/Wind Harmer
0
276848AB2-070 GEN3
Solar/Wind Harmer
6.357
957141AF2-008_MTX
Adder
60.972
944201AF1-088_MTX
Adder
121.944
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.805
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.089
LAGNLTFEXP_LAGN->PJM
CLTF
10.841
AH1-155LTFEXP_AH1-155->PJM
LTF
0.557
CBM West 1LTFEXP_CBM-W1->PJM
CBM
185.896
LGEELTFEXP_LGEE->PJM
CLTF
3.145
TVALTFEXP_TVA->PJM
CLTF
3.804
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
70.836
NYPJM->LTFIMP_NY
CLTF
2.833
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.505
SIGELTFEXP_SIGE->PJM
CLTF
0.342
CBM West 2LTFEXP_CBM-W2->PJM
CBM
99.217
WECLTFEXP_WEC->PJM
CLTF
6.639
MECLTFEXP_MEC->PJM
CLTF
23.06
AG2-052LTFEXP_AG2-052->PJM
LTF
0.372

Details for 05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#1760_05JEFRSO 765_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.42 %
Rating:5133.0 MVA
Rating Type:B
MVA to Mitigate:5257.21
MW Contribution:1.66
Bus #Bus NameTypeMW Contribution
965681AG1-436 GEN
Solar/Wind Harmer
1.485
943591AF1-030 GEN
Solar/Wind Harmer
1.17
276901AD2-066 C O1
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
971343AH1-151 GEN
Solar/Wind Harmer
2.199
970169AG2-114 GEN
Solar/Wind Harmer
1.062
961011AF2-392 GEN
Solar/Wind Harmer
32.759
276785W4-005 GEN1
Solar/Wind Harmer
8.725
972207SS24-0001
Solar/Wind Harmer
3.751
972181SS23-001
Solar/Wind Harmer
1.162
270055AF2-134 C O1
Solar/Wind Harmer
0
959091AF2-200 GEN
Solar/Wind Harmer
2.199
274849CRESCENT ;1U
Solar/Wind Harmer
6.772
274877BISHOP HL;1U
Solar/Wind Harmer
11.908
24755605MDL-5G
Solar/Wind Harmer
8.245
274776LINCOLN ;7U
50/50
19.255
970373AG2-245 GEN
Solar/Wind Harmer
2.378
274861TOP CROP ;1U
Solar/Wind Harmer
22.22
274872LEEDK;1U
Solar/Wind Harmer
0.495
270526AF1-158 GEN
Solar/Wind Harmer
0
959081AF2-199 GEN
Solar/Wind Harmer
1.099
964401AG1-302 GEN
Solar/Wind Harmer
0
971475AH1-234 GEN
Solar/Wind Harmer
2.422
276646AC1-214 GEN2
Solar/Wind Harmer
4.436
276726Z2-087_GEN
Solar/Wind Harmer
25.946
270180AB1-006 GEN1
Solar/Wind Harmer
23.431
24791305MDL-5G
Solar/Wind Harmer
8.245
24386205FR-12G C
Solar/Wind Harmer
7.542
276764AC1-053 GEN2
Solar/Wind Harmer
11.302
963741AG1-226 GEN
Solar/Wind Harmer
2.492
960681AF2-359 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.215
971067AG2-660 GEN
Solar/Wind Harmer
4.397
971917AH1-482 GEN
Solar/Wind Harmer
16.916
276872AE1-163_GEN1
Solar/Wind Harmer
24.282
276741O09 GEN1
Solar/Wind Harmer
12.847
276655WTG1_EQ
Solar/Wind Harmer
17.184
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
26.221
276686W4-005 GEN3
Solar/Wind Harmer
8.725
963841AG1-237 GEN
Solar/Wind Harmer
27.26
274661LASCO STA;2U
50/50
15.534
958011AF2-095 GEN
Solar/Wind Harmer
1.693
971573AH1-285 GEN
Solar/Wind Harmer
0.998
942991AE2-321 GEN
Solar/Wind Harmer
1.116
958491AF2-143 GEN
Solar/Wind Harmer
1.664
971333AH1-146 GEN
Solar/Wind Harmer
2.217
970819AG2-516 GEN
Solar/Wind Harmer
1.302
274851PROVIDENC;RU
Solar/Wind Harmer
9.799
945421AF1-207 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
11.908
943021AE2-325 GEN
Solar/Wind Harmer
6.426
965931AG1-462 GEN
Solar/Wind Harmer
2.547
24697905MDL-4G C
Solar/Wind Harmer
8.245
965091AG1-374 GEN
Solar/Wind Harmer
2.909
274777LINCOLN ;8U
50/50
19.255
270102X2-052 ST
50/50
3.287
970901AG2-562 GEN
50/50
12.454
970245AG2-165 GEN
Solar/Wind Harmer
3.135
970349AG2-230 GEN
Solar/Wind Harmer
1.965
971347AH1-153 GEN
Solar/Wind Harmer
1.965
972231SS25-0005
Solar/Wind Harmer
1.859
970921AG2-575 GEN
Solar/Wind Harmer
1.13
970921AG2-575 GEN
Solar/Wind Harmer
4.519
274862TOP CROP ;2U
Solar/Wind Harmer
18.457
274855GSG-6 ;RU
Solar/Wind Harmer
14.096
971411AH1-196 GEN
Solar/Wind Harmer
1.664
274879MINONK ;1U
Solar/Wind Harmer
25.976
274772LINCOLN ;3U
50/50
19.255
274774LINCOLN ;5U
50/50
19.255
274660LASCO STA;1U
50/50
15.494
970243AG2-164 GEN
Solar/Wind Harmer
3.497
274888KELLY CRK;1U
Solar/Wind Harmer
23.873
970941AG2-585 GEN
Solar/Wind Harmer
1.47
943121AE2-341 GEN
Solar/Wind Harmer
1.755
274871GR RIDGE ;2U
Solar/Wind Harmer
27.244
957471AF2-041 GEN
Solar/Wind Harmer
3.298
274850MENDOTA H;RU
Solar/Wind Harmer
9.983
276861AD2-134 GEN
Solar/Wind Harmer
6.814
276805AD2-038 GEN
Solar/Wind Harmer
20.107
274864CRW2-WTG
Solar/Wind Harmer
20.578
274858EASY ROAD;U2
Solar/Wind Harmer
16.727
970513AG2-328 GEN
Solar/Wind Harmer
3.135
970517AG2-330 GEN
Solar/Wind Harmer
48.901
970833AG2-524 GEN
Solar/Wind Harmer
1.286
962781AG1-127 GEN
Solar/Wind Harmer
1.074
274773LINCOLN ;4U
50/50
19.255
972259AH1-714 GEN
50/50
40.292
970239AG2-162 GEN
Solar/Wind Harmer
1.49
276893AG1-478 C
Solar/Wind Harmer
-0.001
962691AG1-118 GEN
Solar/Wind Harmer
3.401
276863AD2-134 GEN
Solar/Wind Harmer
6.814
971997AH1-543 GEN
Solar/Wind Harmer
1.743
274863CRW1-WTG
Solar/Wind Harmer
20.578
276889AE2-281 GEN
Solar/Wind Harmer
6.938
274856ECOGROVE ;U1
Solar/Wind Harmer
12.687
276158O29GEN2
Solar/Wind Harmer
15.263
971335AH1-147 GEN
Solar/Wind Harmer
2.217
971171AH1-044 GEN
Solar/Wind Harmer
2.199
926823AC1-168 GEN
Solar/Wind Harmer
13.121
959141AF2-205 GEN
Solar/Wind Harmer
0
276782AC1-033 GEN
Solar/Wind Harmer
13.453
946321AF1-296 GEN
Solar/Wind Harmer
30.005
24697605MDL-3G C
Solar/Wind Harmer
12.487
270181AB1-006 GEN2
Solar/Wind Harmer
1.553
959611AF2-252 GEN
Solar/Wind Harmer
3.879
960611AF2-352 GEN
Solar/Wind Harmer
3.879
24385905FR-11G C
Solar/Wind Harmer
14.202
963831AG1-236 GEN
Solar/Wind Harmer
24.413
274770LINCOLN ;1U
50/50
19.255
274771LINCOLN ;2U
50/50
19.255
270100X2-052 CT1
50/50
3.036
276897AD1-100 C
Solar/Wind Harmer
120.857
971769AH1-391 GEN
Solar/Wind Harmer
1.127
971177AH1-047 GEN
Solar/Wind Harmer
0.654
964861AG1-349 GEN
Solar/Wind Harmer
0
971681AH1-341 GEN
Solar/Wind Harmer
1.61
938861AE1-114 GEN
Solar/Wind Harmer
25.097
970571AG2-364 GEN
Solar/Wind Harmer
2.133
276603SUBLETTE C
Solar/Wind Harmer
3.635
940581AE2-045 GEN
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
1.764
945111AF1-176 GEN
Solar/Wind Harmer
9.614
972175AH1-670 GEN
Solar/Wind Harmer
35.909
276174W4-005 GEN2
Solar/Wind Harmer
8.725
276621W2-048 GEN
Solar/Wind Harmer
18.423
970699AG2-449 GEN
Solar/Wind Harmer
1.554
970707AG2-453 GEN
Solar/Wind Harmer
3.386
274887GEN-1.85
Solar/Wind Harmer
21.93
970833AG2-524 GEN
Solar/Wind Harmer
10.292
958481AF2-142 GEN
Solar/Wind Harmer
1.692
971675AH1-338 GEN
Solar/Wind Harmer
1.999
276868AE1-113 GEN
Solar/Wind Harmer
37.14
970781AG2-491 GEN
Solar/Wind Harmer
0.996
274853TWINGROVE;U1
Solar/Wind Harmer
23.921
966841AG1-555 GEN
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
5.839
24344105CKG2
50/50
20.836
270101X2-052 CT2
50/50
3.036
965791AG1-447 GEN
Solar/Wind Harmer
13.067
941551AE2-152 GEN
Solar/Wind Harmer
0
276843GEN-1.7
Solar/Wind Harmer
1.943
274872LEEDK;1U
Solar/Wind Harmer
32.656
276882AE2-255 GEN
Solar/Wind Harmer
11.717
274854TWINGROVE;U2
Solar/Wind Harmer
23.669
274775LINCOLN ;6U
50/50
19.255
970519AG2-331 GEN
Solar/Wind Harmer
40.415
939351AE1-166 GEN
Solar/Wind Harmer
0
960591AF2-350 GEN
Solar/Wind Harmer
1.176
276694AA1-018 GEN2
Solar/Wind Harmer
21.77
939401AE1-172 GEN
Solar/Wind Harmer
44.375
958381AF2-132 GEN
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
24.282
274857EASY ROAD;U1
Solar/Wind Harmer
16.727
276656WTG2_EQ
Solar/Wind Harmer
2.275
941731AE2-173 GEN
Solar/Wind Harmer
9.979
961051AF2-396 GEN
Solar/Wind Harmer
2.024
961051AF2-396 GEN
Solar/Wind Harmer
16.191
24386405FR-21G C
Solar/Wind Harmer
7.224
276763AC1-053 GEN1
Solar/Wind Harmer
11.302
270449AD2-020 GEN
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
18.56
959341AF2-225 GEN
Solar/Wind Harmer
1.497
276849AB2-070 GEN2
Solar/Wind Harmer
6.635
970321AG2-212 GEN
Solar/Wind Harmer
3.135
970333AG2-219 GEN
Solar/Wind Harmer
4.275
276602WESTBROOK C
Solar/Wind Harmer
7.773
276645AC1-214 GEN1
Solar/Wind Harmer
4.436
942111AE2-223 GEN
Solar/Wind Harmer
23.351
24387305FR-4G C
Solar/Wind Harmer
10.836
24386605FR-22G C
Solar/Wind Harmer
7.224
24387005FR-3G C
Solar/Wind Harmer
7.152
970569AG2-363 GEN
Solar/Wind Harmer
3.199
971771AH1-392 GEN
Solar/Wind Harmer
0.959
971605AH1-302 GEN
Solar/Wind Harmer
15.855
276157O29GEN1
Solar/Wind Harmer
15.263
270505AE1-170 C O1
Solar/Wind Harmer
1.559
957751AF2-069 GEN
Solar/Wind Harmer
1.354
939741AE1-205 GEN
Solar/Wind Harmer
1.996
276668AB2-070 GEN1
Solar/Wind Harmer
6.635
970241AG2-163 GEN
Solar/Wind Harmer
1.384
276708O09 GEN2
Solar/Wind Harmer
12.847
957841AF2-078 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
12.507
971549AH1-272 GEN
Solar/Wind Harmer
1.657
274880W4-005 GEN4
Solar/Wind Harmer
8.725
971993AH1-541 GEN
Solar/Wind Harmer
0.811
276838X2-022 GEN2
Solar/Wind Harmer
0.693
276806AD2-047 C O1
Solar/Wind Harmer
36.221
274847GR RIDGE ;BU
Solar/Wind Harmer
20.848
971341AH1-150 GEN
Solar/Wind Harmer
2.199
958391AF2-133 GEN
Solar/Wind Harmer
0
276848AB2-070 GEN3
Solar/Wind Harmer
6.637
944201AF1-088_MTX
Adder
101.469
957141AF2-008_MTX
Adder
50.735
NYPJM->LTFIMP_NY
CLTF
2.839
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.623
SIGELTFEXP_SIGE->PJM
CLTF
0.288
CBM West 2LTFEXP_CBM-W2->PJM
CBM
96.378
WECLTFEXP_WEC->PJM
CLTF
7.148
MECLTFEXP_MEC->PJM
CLTF
24.248
AG2-052LTFEXP_AG2-052->PJM
LTF
0.408
CBM West 1LTFEXP_CBM-W1->PJM
CBM
199.823
LGEELTFEXP_LGEE->PJM
CLTF
1.755
TVALTFEXP_TVA->PJM
CLTF
3.376
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
82.361
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.128
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.265
LAGNLTFEXP_LAGN->PJM
CLTF
10.375
AH1-155LTFEXP_AH1-155->PJM
LTF
0.612

Details for 05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line l/o AEP_P4_#709_05HANG R 765_D2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#709_05HANG R 765_D2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.4 %
Rating:5133.0 MVA
Rating Type:B
MVA to Mitigate:5204.92
MW Contribution:1.47
Bus #Bus NameTypeMW Contribution
970707AG2-453 GEN
Solar/Wind Harmer
3.132
274887GEN-1.85
Solar/Wind Harmer
20.241
970833AG2-524 GEN
Solar/Wind Harmer
9.53
958481AF2-142 GEN
Solar/Wind Harmer
1.569
971675AH1-338 GEN
Solar/Wind Harmer
1.859
276868AE1-113 GEN
Solar/Wind Harmer
34.539
274853TWINGROVE;U1
Solar/Wind Harmer
22.67
970781AG2-491 GEN
Solar/Wind Harmer
0.874
966841AG1-555 GEN
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
5.634
965911AG1-460 GEN
Solar/Wind Harmer
1.88
970699AG2-449 GEN
Solar/Wind Harmer
0.847
274777LINCOLN ;8U
50/50
17.782
970245AG2-165 GEN
Solar/Wind Harmer
2.775
970349AG2-230 GEN
Solar/Wind Harmer
1.786
971347AH1-153 GEN
Solar/Wind Harmer
1.786
972231SS25-0005
Solar/Wind Harmer
1.704
970921AG2-575 GEN
Solar/Wind Harmer
1.049
970921AG2-575 GEN
Solar/Wind Harmer
4.197
274862TOP CROP ;2U
Solar/Wind Harmer
17.112
274855GSG-6 ;RU
Solar/Wind Harmer
13.113
971411AH1-196 GEN
Solar/Wind Harmer
1.547
274879MINONK ;1U
Solar/Wind Harmer
24.157
961051AF2-396 GEN
Solar/Wind Harmer
1.807
961051AF2-396 GEN
Solar/Wind Harmer
14.459
276763AC1-053 GEN1
Solar/Wind Harmer
10.872
24386405FR-21G C
Solar/Wind Harmer
6.469
274775LINCOLN ;6U
50/50
17.782
939351AE1-166 GEN
Solar/Wind Harmer
0
960591AF2-350 GEN
Solar/Wind Harmer
1.085
276694AA1-018 GEN2
Solar/Wind Harmer
20.183
939401AE1-172 GEN
Solar/Wind Harmer
41.341
276876AE1-163_GEN2
Solar/Wind Harmer
22.622
274857EASY ROAD;U1
Solar/Wind Harmer
15.611
958381AF2-132 GEN
Solar/Wind Harmer
0
276656WTG2_EQ
Solar/Wind Harmer
2.148
941731AE2-173 GEN
Solar/Wind Harmer
9.419
970519AG2-331 GEN
Solar/Wind Harmer
22.024
970513AG2-328 GEN
Solar/Wind Harmer
2.775
970517AG2-330 GEN
Solar/Wind Harmer
43.283
970833AG2-524 GEN
Solar/Wind Harmer
1.191
962781AG1-127 GEN
Solar/Wind Harmer
0.998
971335AH1-147 GEN
Solar/Wind Harmer
2.062
971171AH1-044 GEN
Solar/Wind Harmer
2.047
926823AC1-168 GEN
Solar/Wind Harmer
12.258
276782AC1-033 GEN
Solar/Wind Harmer
12.616
946321AF1-296 GEN
Solar/Wind Harmer
28.153
959141AF2-205 GEN
Solar/Wind Harmer
0
959611AF2-252 GEN
Solar/Wind Harmer
3.676
960611AF2-352 GEN
Solar/Wind Harmer
3.676
24697605MDL-3G C
Solar/Wind Harmer
10.96
270181AB1-006 GEN2
Solar/Wind Harmer
1.363
963831AG1-236 GEN
Solar/Wind Harmer
23.483
24385905FR-11G C
Solar/Wind Harmer
12.718
274770LINCOLN ;1U
50/50
17.782
274771LINCOLN ;2U
50/50
17.782
276897AD1-100 C
Solar/Wind Harmer
111.834
971177AH1-047 GEN
Solar/Wind Harmer
0.608
971769AH1-391 GEN
Solar/Wind Harmer
1.016
971681AH1-341 GEN
Solar/Wind Harmer
1.501
938861AE1-114 GEN
Solar/Wind Harmer
23.412
970571AG2-364 GEN
Solar/Wind Harmer
1.991
276603SUBLETTE C
Solar/Wind Harmer
3.394
964861AG1-349 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
1.571
945111AF1-176 GEN
Solar/Wind Harmer
8.564
972175AH1-670 GEN
Solar/Wind Harmer
34.27
276174W4-005 GEN2
Solar/Wind Harmer
8.384
276621W2-048 GEN
Solar/Wind Harmer
17.775
970321AG2-212 GEN
Solar/Wind Harmer
2.775
276602WESTBROOK C
Solar/Wind Harmer
7.231
276645AC1-214 GEN1
Solar/Wind Harmer
4.158
942111AE2-223 GEN
Solar/Wind Harmer
22.042
24387305FR-4G C
Solar/Wind Harmer
9.704
24386605FR-22G C
Solar/Wind Harmer
6.469
24387005FR-3G C
Solar/Wind Harmer
6.404
970333AG2-219 GEN
Solar/Wind Harmer
2.329
274773LINCOLN ;4U
50/50
17.782
972259AH1-714 GEN
50/50
37.249
276893AG1-478 C
Solar/Wind Harmer
-0.001
962691AG1-118 GEN
Solar/Wind Harmer
3.158
276863AD2-134 GEN
Solar/Wind Harmer
6.339
971997AH1-543 GEN
Solar/Wind Harmer
1.623
274863CRW1-WTG
Solar/Wind Harmer
19.224
276889AE2-281 GEN
Solar/Wind Harmer
6.464
274856ECOGROVE ;U1
Solar/Wind Harmer
11.824
276158O29GEN2
Solar/Wind Harmer
14.278
276708O09 GEN2
Solar/Wind Harmer
12.017
957841AF2-078 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
10.978
274880W4-005 GEN4
Solar/Wind Harmer
8.384
971993AH1-541 GEN
Solar/Wind Harmer
0.779
276838X2-022 GEN2
Solar/Wind Harmer
0.669
971549AH1-272 GEN
Solar/Wind Harmer
1.473
942481AE2-261 GEN
Solar/Wind Harmer
2.342
970239AG2-162 GEN
Solar/Wind Harmer
0.812
274772LINCOLN ;3U
50/50
17.782
274774LINCOLN ;5U
50/50
17.782
274660LASCO STA;1U
50/50
14.324
274888KELLY CRK;1U
Solar/Wind Harmer
22.034
970941AG2-585 GEN
Solar/Wind Harmer
1.357
274850MENDOTA H;RU
Solar/Wind Harmer
9.287
276861AD2-134 GEN
Solar/Wind Harmer
6.339
276805AD2-038 GEN
Solar/Wind Harmer
18.679
274864CRW2-WTG
Solar/Wind Harmer
19.224
274858EASY ROAD;U2
Solar/Wind Harmer
15.611
970569AG2-363 GEN
Solar/Wind Harmer
2.987
276157O29GEN1
Solar/Wind Harmer
14.278
957751AF2-069 GEN
Solar/Wind Harmer
1.269
971771AH1-392 GEN
Solar/Wind Harmer
0.859
939741AE1-205 GEN
Solar/Wind Harmer
1.884
270505AE1-170 C O1
Solar/Wind Harmer
1.395
971605AH1-302 GEN
Solar/Wind Harmer
13.905
276668AB2-070 GEN1
Solar/Wind Harmer
6.374
970243AG2-164 GEN
Solar/Wind Harmer
1.906
24344105CKG2
50/50
19.112
941551AE2-152 GEN
Solar/Wind Harmer
0
276843GEN-1.7
Solar/Wind Harmer
1.793
965791AG1-447 GEN
Solar/Wind Harmer
11.817
274872LEEDK;1U
Solar/Wind Harmer
30.342
276882AE2-255 GEN
Solar/Wind Harmer
10.896
274854TWINGROVE;U2
Solar/Wind Harmer
22.431
274776LINCOLN ;7U
50/50
17.782
274872LEEDK;1U
Solar/Wind Harmer
0.46
274861TOP CROP ;1U
Solar/Wind Harmer
20.601
959081AF2-199 GEN
Solar/Wind Harmer
1.023
970373AG2-245 GEN
Solar/Wind Harmer
2.121
971475AH1-234 GEN
Solar/Wind Harmer
2.257
270526AF1-158 GEN
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
4.158
964401AG1-302 GEN
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
24.491
270180AB1-006 GEN1
Solar/Wind Harmer
20.566
24791305MDL-5G
Solar/Wind Harmer
7.237
276764AC1-053 GEN2
Solar/Wind Harmer
10.872
24386205FR-12G C
Solar/Wind Harmer
6.754
276911AD2-131_GEN
Solar/Wind Harmer
0.387
274661LASCO STA;2U
50/50
14.361
958011AF2-095 GEN
Solar/Wind Harmer
1.563
971573AH1-285 GEN
Solar/Wind Harmer
0.925
942991AE2-321 GEN
Solar/Wind Harmer
1.037
971333AH1-146 GEN
Solar/Wind Harmer
2.062
958491AF2-143 GEN
Solar/Wind Harmer
1.546
970819AG2-516 GEN
Solar/Wind Harmer
1.213
274851PROVIDENC;RU
Solar/Wind Harmer
9.184
274878BISHOP HL;2U
Solar/Wind Harmer
11.167
965931AG1-462 GEN
Solar/Wind Harmer
2.392
965091AG1-374 GEN
Solar/Wind Harmer
2.757
943021AE2-325 GEN
Solar/Wind Harmer
5.747
945421AF1-207 GEN
Solar/Wind Harmer
0
24697905MDL-4G C
Solar/Wind Harmer
7.237
960681AF2-359 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.126
971067AG2-660 GEN
Solar/Wind Harmer
4.093
276872AE1-163_GEN1
Solar/Wind Harmer
22.622
276741O09 GEN1
Solar/Wind Harmer
12.017
971917AH1-482 GEN
Solar/Wind Harmer
14.933
276655WTG1_EQ
Solar/Wind Harmer
16.22
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
23.015
276686W4-005 GEN3
Solar/Wind Harmer
8.384
963841AG1-237 GEN
Solar/Wind Harmer
24.774
943591AF1-030 GEN
Solar/Wind Harmer
1.084
965681AG1-436 GEN
Solar/Wind Harmer
1.343
276901AD2-066 C O1
Solar/Wind Harmer
0
971343AH1-151 GEN
Solar/Wind Harmer
2.047
970169AG2-114 GEN
Solar/Wind Harmer
0.995
961011AF2-392 GEN
Solar/Wind Harmer
30.607
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
276785W4-005 GEN1
Solar/Wind Harmer
8.384
972207SS24-0001
Solar/Wind Harmer
3.464
972181SS23-001
Solar/Wind Harmer
1.065
959091AF2-200 GEN
Solar/Wind Harmer
2.047
270055AF2-134 C O1
Solar/Wind Harmer
0
274849CRESCENT ;1U
Solar/Wind Harmer
6.347
274877BISHOP HL;1U
Solar/Wind Harmer
11.167
24755605MDL-5G
Solar/Wind Harmer
7.237
276916AD2-100_GEN
Solar/Wind Harmer
1.624
943121AE2-341 GEN
Solar/Wind Harmer
1.626
274871GR RIDGE ;2U
Solar/Wind Harmer
25.23
957471AF2-041 GEN
Solar/Wind Harmer
3.07
274848CAMPGROVE;RU
Solar/Wind Harmer
17.422
959341AF2-225 GEN
Solar/Wind Harmer
1.413
270449AD2-020 GEN
Solar/Wind Harmer
0
276849AB2-070 GEN2
Solar/Wind Harmer
6.374
276806AD2-047 C O1
Solar/Wind Harmer
33.431
274847GR RIDGE ;BU
Solar/Wind Harmer
19.307
971341AH1-150 GEN
Solar/Wind Harmer
2.047
958391AF2-133 GEN
Solar/Wind Harmer
0
276848AB2-070 GEN3
Solar/Wind Harmer
6.375
957141AF2-008_MTX
Adder
61.221
944201AF1-088_MTX
Adder
122.442
NYPJM->LTFIMP_NY
CLTF
2.805
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.487
SIGELTFEXP_SIGE->PJM
CLTF
0.344
CBM West 2LTFEXP_CBM-W2->PJM
CBM
99.796
WECLTFEXP_WEC->PJM
CLTF
6.655
MECLTFEXP_MEC->PJM
CLTF
23.133
AG2-052LTFEXP_AG2-052->PJM
LTF
0.373
CBM West 1LTFEXP_CBM-W1->PJM
CBM
186.523
LGEELTFEXP_LGEE->PJM
CLTF
3.175
TVALTFEXP_TVA->PJM
CLTF
3.848
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
70.836
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.969
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.06
LAGNLTFEXP_LAGN->PJM
CLTF
10.929
AH1-155LTFEXP_AH1-155->PJM
LTF
0.559

Details for 05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#709_546_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.4 %
Rating:5133.0 MVA
Rating Type:B
MVA to Mitigate:5204.83
MW Contribution:1.47
Bus #Bus NameTypeMW Contribution
943591AF1-030 GEN
Solar/Wind Harmer
1.084
965681AG1-436 GEN
Solar/Wind Harmer
1.343
276901AD2-066 C O1
Solar/Wind Harmer
0
971343AH1-151 GEN
Solar/Wind Harmer
2.047
970169AG2-114 GEN
Solar/Wind Harmer
0.995
961011AF2-392 GEN
Solar/Wind Harmer
30.607
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
276785W4-005 GEN1
Solar/Wind Harmer
8.384
972207SS24-0001
Solar/Wind Harmer
3.464
972181SS23-001
Solar/Wind Harmer
1.065
959091AF2-200 GEN
Solar/Wind Harmer
2.047
270055AF2-134 C O1
Solar/Wind Harmer
0
274849CRESCENT ;1U
Solar/Wind Harmer
6.347
274877BISHOP HL;1U
Solar/Wind Harmer
11.167
24755605MDL-5G
Solar/Wind Harmer
7.237
276916AD2-100_GEN
Solar/Wind Harmer
1.624
274776LINCOLN ;7U
50/50
17.782
274872LEEDK;1U
Solar/Wind Harmer
0.46
274861TOP CROP ;1U
Solar/Wind Harmer
20.601
959081AF2-199 GEN
Solar/Wind Harmer
1.023
970373AG2-245 GEN
Solar/Wind Harmer
2.121
971475AH1-234 GEN
Solar/Wind Harmer
2.257
270526AF1-158 GEN
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
4.158
964401AG1-302 GEN
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
24.491
270180AB1-006 GEN1
Solar/Wind Harmer
20.566
24791305MDL-5G
Solar/Wind Harmer
7.237
276764AC1-053 GEN2
Solar/Wind Harmer
10.872
24386205FR-12G C
Solar/Wind Harmer
6.754
276911AD2-131_GEN
Solar/Wind Harmer
0.387
960681AF2-359 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.126
971067AG2-660 GEN
Solar/Wind Harmer
4.093
276872AE1-163_GEN1
Solar/Wind Harmer
22.622
276741O09 GEN1
Solar/Wind Harmer
12.017
971917AH1-482 GEN
Solar/Wind Harmer
14.933
276655WTG1_EQ
Solar/Wind Harmer
16.22
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
23.015
276686W4-005 GEN3
Solar/Wind Harmer
8.384
963841AG1-237 GEN
Solar/Wind Harmer
24.774
274661LASCO STA;2U
50/50
14.361
958011AF2-095 GEN
Solar/Wind Harmer
1.563
971573AH1-285 GEN
Solar/Wind Harmer
0.925
942991AE2-321 GEN
Solar/Wind Harmer
1.037
971333AH1-146 GEN
Solar/Wind Harmer
2.062
958491AF2-143 GEN
Solar/Wind Harmer
1.546
970819AG2-516 GEN
Solar/Wind Harmer
1.213
274851PROVIDENC;RU
Solar/Wind Harmer
9.184
274878BISHOP HL;2U
Solar/Wind Harmer
11.167
965931AG1-462 GEN
Solar/Wind Harmer
2.392
965091AG1-374 GEN
Solar/Wind Harmer
2.757
943021AE2-325 GEN
Solar/Wind Harmer
5.747
945421AF1-207 GEN
Solar/Wind Harmer
0
24697905MDL-4G C
Solar/Wind Harmer
7.237
274772LINCOLN ;3U
50/50
17.782
274774LINCOLN ;5U
50/50
17.782
274660LASCO STA;1U
50/50
14.324
274888KELLY CRK;1U
Solar/Wind Harmer
22.034
970941AG2-585 GEN
Solar/Wind Harmer
1.357
274850MENDOTA H;RU
Solar/Wind Harmer
9.287
276861AD2-134 GEN
Solar/Wind Harmer
6.339
276805AD2-038 GEN
Solar/Wind Harmer
18.679
274864CRW2-WTG
Solar/Wind Harmer
19.224
274858EASY ROAD;U2
Solar/Wind Harmer
15.611
970569AG2-363 GEN
Solar/Wind Harmer
2.987
276157O29GEN1
Solar/Wind Harmer
14.278
957751AF2-069 GEN
Solar/Wind Harmer
1.269
971771AH1-392 GEN
Solar/Wind Harmer
0.859
939741AE1-205 GEN
Solar/Wind Harmer
1.884
270505AE1-170 C O1
Solar/Wind Harmer
1.395
971605AH1-302 GEN
Solar/Wind Harmer
13.905
276668AB2-070 GEN1
Solar/Wind Harmer
6.374
970243AG2-164 GEN
Solar/Wind Harmer
1.906
274777LINCOLN ;8U
50/50
17.782
970245AG2-165 GEN
Solar/Wind Harmer
2.775
970349AG2-230 GEN
Solar/Wind Harmer
1.786
971347AH1-153 GEN
Solar/Wind Harmer
1.786
972231SS25-0005
Solar/Wind Harmer
1.704
970921AG2-575 GEN
Solar/Wind Harmer
1.049
970921AG2-575 GEN
Solar/Wind Harmer
4.197
274862TOP CROP ;2U
Solar/Wind Harmer
17.112
274855GSG-6 ;RU
Solar/Wind Harmer
13.113
971411AH1-196 GEN
Solar/Wind Harmer
1.547
274879MINONK ;1U
Solar/Wind Harmer
24.157
961051AF2-396 GEN
Solar/Wind Harmer
1.807
961051AF2-396 GEN
Solar/Wind Harmer
14.459
276763AC1-053 GEN1
Solar/Wind Harmer
10.872
24386405FR-21G C
Solar/Wind Harmer
6.469
274773LINCOLN ;4U
50/50
17.782
972259AH1-714 GEN
50/50
37.249
276893AG1-478 C
Solar/Wind Harmer
-0.001
962691AG1-118 GEN
Solar/Wind Harmer
3.158
276863AD2-134 GEN
Solar/Wind Harmer
6.339
971997AH1-543 GEN
Solar/Wind Harmer
1.623
274863CRW1-WTG
Solar/Wind Harmer
19.224
276889AE2-281 GEN
Solar/Wind Harmer
6.464
274856ECOGROVE ;U1
Solar/Wind Harmer
11.824
276158O29GEN2
Solar/Wind Harmer
14.278
276708O09 GEN2
Solar/Wind Harmer
12.017
957841AF2-078 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
10.978
274880W4-005 GEN4
Solar/Wind Harmer
8.384
971993AH1-541 GEN
Solar/Wind Harmer
0.779
276838X2-022 GEN2
Solar/Wind Harmer
0.669
971549AH1-272 GEN
Solar/Wind Harmer
1.473
942481AE2-261 GEN
Solar/Wind Harmer
2.342
970239AG2-162 GEN
Solar/Wind Harmer
0.812
970513AG2-328 GEN
Solar/Wind Harmer
2.775
970517AG2-330 GEN
Solar/Wind Harmer
43.283
970833AG2-524 GEN
Solar/Wind Harmer
1.191
962781AG1-127 GEN
Solar/Wind Harmer
0.998
971335AH1-147 GEN
Solar/Wind Harmer
2.062
971171AH1-044 GEN
Solar/Wind Harmer
2.047
926823AC1-168 GEN
Solar/Wind Harmer
12.258
276782AC1-033 GEN
Solar/Wind Harmer
12.616
946321AF1-296 GEN
Solar/Wind Harmer
28.153
959141AF2-205 GEN
Solar/Wind Harmer
0
959611AF2-252 GEN
Solar/Wind Harmer
3.676
960611AF2-352 GEN
Solar/Wind Harmer
3.676
24697605MDL-3G C
Solar/Wind Harmer
10.96
270181AB1-006 GEN2
Solar/Wind Harmer
1.363
963831AG1-236 GEN
Solar/Wind Harmer
23.483
24385905FR-11G C
Solar/Wind Harmer
12.718
970707AG2-453 GEN
Solar/Wind Harmer
3.132
274887GEN-1.85
Solar/Wind Harmer
20.241
970833AG2-524 GEN
Solar/Wind Harmer
9.53
958481AF2-142 GEN
Solar/Wind Harmer
1.569
971675AH1-338 GEN
Solar/Wind Harmer
1.859
276868AE1-113 GEN
Solar/Wind Harmer
34.539
274853TWINGROVE;U1
Solar/Wind Harmer
22.67
970781AG2-491 GEN
Solar/Wind Harmer
0.874
966841AG1-555 GEN
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
5.634
965911AG1-460 GEN
Solar/Wind Harmer
1.88
970699AG2-449 GEN
Solar/Wind Harmer
0.847
24344105CKG2
50/50
19.112
941551AE2-152 GEN
Solar/Wind Harmer
0
276843GEN-1.7
Solar/Wind Harmer
1.793
965791AG1-447 GEN
Solar/Wind Harmer
11.817
274872LEEDK;1U
Solar/Wind Harmer
30.342
276882AE2-255 GEN
Solar/Wind Harmer
10.896
274854TWINGROVE;U2
Solar/Wind Harmer
22.431
274775LINCOLN ;6U
50/50
17.782
939351AE1-166 GEN
Solar/Wind Harmer
0
960591AF2-350 GEN
Solar/Wind Harmer
1.085
276694AA1-018 GEN2
Solar/Wind Harmer
20.183
939401AE1-172 GEN
Solar/Wind Harmer
41.341
276876AE1-163_GEN2
Solar/Wind Harmer
22.622
274857EASY ROAD;U1
Solar/Wind Harmer
15.611
958381AF2-132 GEN
Solar/Wind Harmer
0
276656WTG2_EQ
Solar/Wind Harmer
2.148
941731AE2-173 GEN
Solar/Wind Harmer
9.419
970519AG2-331 GEN
Solar/Wind Harmer
22.024
943121AE2-341 GEN
Solar/Wind Harmer
1.626
274871GR RIDGE ;2U
Solar/Wind Harmer
25.23
957471AF2-041 GEN
Solar/Wind Harmer
3.07
274848CAMPGROVE;RU
Solar/Wind Harmer
17.422
959341AF2-225 GEN
Solar/Wind Harmer
1.413
270449AD2-020 GEN
Solar/Wind Harmer
0
276849AB2-070 GEN2
Solar/Wind Harmer
6.374
970321AG2-212 GEN
Solar/Wind Harmer
2.775
276602WESTBROOK C
Solar/Wind Harmer
7.231
276645AC1-214 GEN1
Solar/Wind Harmer
4.158
942111AE2-223 GEN
Solar/Wind Harmer
22.042
24387305FR-4G C
Solar/Wind Harmer
9.704
24386605FR-22G C
Solar/Wind Harmer
6.469
24387005FR-3G C
Solar/Wind Harmer
6.404
970333AG2-219 GEN
Solar/Wind Harmer
2.329
274770LINCOLN ;1U
50/50
17.782
274771LINCOLN ;2U
50/50
17.782
276897AD1-100 C
Solar/Wind Harmer
111.834
971177AH1-047 GEN
Solar/Wind Harmer
0.608
971769AH1-391 GEN
Solar/Wind Harmer
1.016
971681AH1-341 GEN
Solar/Wind Harmer
1.501
938861AE1-114 GEN
Solar/Wind Harmer
23.412
970571AG2-364 GEN
Solar/Wind Harmer
1.991
276603SUBLETTE C
Solar/Wind Harmer
3.394
964861AG1-349 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
1.571
945111AF1-176 GEN
Solar/Wind Harmer
8.564
972175AH1-670 GEN
Solar/Wind Harmer
34.27
276174W4-005 GEN2
Solar/Wind Harmer
8.384
276621W2-048 GEN
Solar/Wind Harmer
17.775
276806AD2-047 C O1
Solar/Wind Harmer
33.431
274847GR RIDGE ;BU
Solar/Wind Harmer
19.307
971341AH1-150 GEN
Solar/Wind Harmer
2.047
958391AF2-133 GEN
Solar/Wind Harmer
0
276848AB2-070 GEN3
Solar/Wind Harmer
6.375
944201AF1-088_MTX
Adder
122.442
957141AF2-008_MTX
Adder
61.221
CBM West 2LTFEXP_CBM-W2->PJM
CBM
99.796
WECLTFEXP_WEC->PJM
CLTF
6.655
MECLTFEXP_MEC->PJM
CLTF
23.133
AG2-052LTFEXP_AG2-052->PJM
LTF
0.373
NYPJM->LTFIMP_NY
CLTF
2.805
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.487
SIGELTFEXP_SIGE->PJM
CLTF
0.344
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.969
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.06
LAGNLTFEXP_LAGN->PJM
CLTF
10.929
AH1-155LTFEXP_AH1-155->PJM
LTF
0.559
CBM West 1LTFEXP_CBM-W1->PJM
CBM
186.523
LGEELTFEXP_LGEE->PJM
CLTF
3.175
TVALTFEXP_TVA->PJM
CLTF
3.848
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
70.836

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P4_#7334_05JEFRSO 765_A2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#7334_05JEFRSO 765_A2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.0 %
Rating:4961.0 MVA
Rating Type:B
MVA to Mitigate:5655.61
MW Contribution:2.15
Bus #Bus NameTypeMW Contribution
972207SS24-0001
Solar/Wind Harmer
3.857
972181SS23-001
Solar/Wind Harmer
1.268
270055AF2-134 C O1
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
9.928
959091AF2-200 GEN
Solar/Wind Harmer
2.367
274849CRESCENT ;1U
Solar/Wind Harmer
7.509
274877BISHOP HL;1U
Solar/Wind Harmer
13.215
270349AD2-093_GEN
Solar/Wind Helper
0.709
24344105CKG2
50/50
19.281
270101X2-052 CT2
50/50
3.356
965791AG1-447 GEN
Solar/Wind Harmer
14.461
276843GEN-1.7
Solar/Wind Harmer
2.073
941551AE2-152 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
34.888
276882AE2-255 GEN
Solar/Wind Harmer
12.707
270102X2-052 ST
50/50
3.632
970901AG2-562 GEN
50/50
13.762
274777LINCOLN ;8U
50/50
19.802
970245AG2-165 GEN
Solar/Wind Harmer
2.856
970349AG2-230 GEN
Solar/Wind Harmer
2.086
971347AH1-153 GEN
Solar/Wind Harmer
2.086
961051AF2-396 GEN
Solar/Wind Harmer
2.556
961051AF2-396 GEN
Solar/Wind Harmer
20.451
972231SS25-0005
Solar/Wind Harmer
2.028
274862TOP CROP ;2U
Solar/Wind Harmer
19.941
970921AG2-575 GEN
Solar/Wind Harmer
1.206
970921AG2-575 GEN
Solar/Wind Harmer
4.823
274879MINONK ;1U
Solar/Wind Harmer
28.171
971411AH1-196 GEN
Solar/Wind Harmer
1.787
274855GSG-6 ;RU
Solar/Wind Harmer
15.127
24386405FR-21G C
Solar/Wind Harmer
9.043
960971AF2-388 GEN
Solar/Wind Harmer
33.549
270054AF2-122 C O1
Solar/Wind Helper
0.54
276763AC1-053 GEN1
Solar/Wind Harmer
9.884
970513AG2-328 GEN
Solar/Wind Harmer
2.856
970517AG2-330 GEN
Solar/Wind Harmer
44.557
959141AF2-205 GEN
Solar/Wind Harmer
0
270063AE2-323 C
Solar/Wind Harmer
0
970833AG2-524 GEN
Solar/Wind Harmer
1.365
962781AG1-127 GEN
Solar/Wind Harmer
1.147
24697605MDL-3G C
Solar/Wind Harmer
15.036
270181AB1-006 GEN2
Solar/Wind Harmer
1.871
971335AH1-147 GEN
Solar/Wind Harmer
2.381
971171AH1-044 GEN
Solar/Wind Harmer
2.367
926823AC1-168 GEN
Solar/Wind Harmer
14.39
24385905FR-11G C
Solar/Wind Harmer
17.778
276782AC1-033 GEN
Solar/Wind Harmer
14.93
959611AF2-252 GEN
Solar/Wind Harmer
4.483
960611AF2-352 GEN
Solar/Wind Harmer
4.483
946321AF1-296 GEN
Solar/Wind Harmer
33.152
24344005CKG1
50/50
22.413
24641605TWIN BRNCH
50/50
0.039
24643105BUCHANAN
50/50
0.028
970707AG2-453 GEN
Solar/Wind Harmer
3.529
274887GEN-1.85
Solar/Wind Harmer
23.402
970833AG2-524 GEN
Solar/Wind Harmer
10.921
970699AG2-449 GEN
Solar/Wind Harmer
1.469
958481AF2-142 GEN
Solar/Wind Harmer
1.827
970781AG2-491 GEN
Solar/Wind Harmer
1.199
276868AE1-113 GEN
Solar/Wind Harmer
40.278
971675AH1-338 GEN
Solar/Wind Harmer
2.144
944531AF1-118 GEN
Solar/Wind Harmer
4.133
270449AD2-020 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
28.905
943121AE2-341 GEN
Solar/Wind Harmer
1.851
957471AF2-041 GEN
Solar/Wind Harmer
3.55
966841AG1-555 GEN
Solar/Wind Harmer
0
274853TWINGROVE;U1
Solar/Wind Harmer
27.647
274775LINCOLN ;6U
50/50
19.802
960591AF2-350 GEN
Solar/Wind Harmer
1.255
958381AF2-132 GEN
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
970519AG2-331 GEN
Solar/Wind Harmer
38.197
970031AG2-029 GEN
Solar/Wind Harmer
3.667
276694AA1-018 GEN2
Solar/Wind Harmer
23.507
939401AE1-172 GEN
Solar/Wind Harmer
48.146
276876AE1-163_GEN2
Solar/Wind Harmer
26.538
274857EASY ROAD;U1
Solar/Wind Harmer
18.167
276656WTG2_EQ
Solar/Wind Harmer
2.597
941731AE2-173 GEN
Solar/Wind Harmer
11.391
274772LINCOLN ;3U
50/50
19.802
274774LINCOLN ;5U
50/50
19.802
971771AH1-392 GEN
Solar/Wind Harmer
1.176
270505AE1-170 C O1
Solar/Wind Harmer
1.935
270043AE2-236 GEN
Solar/Wind Harmer
0.707
274888KELLY CRK;1U
Solar/Wind Harmer
25.475
970941AG2-585 GEN
Solar/Wind Harmer
1.569
971605AH1-302 GEN
Solar/Wind Harmer
18.534
970243AG2-164 GEN
Solar/Wind Harmer
3.306
276805AD2-038 GEN
Solar/Wind Harmer
21.819
274864CRW2-WTG
Solar/Wind Harmer
22.565
274850MENDOTA H;RU
Solar/Wind Harmer
10.714
276861AD2-134 GEN
Solar/Wind Harmer
7.313
970569AG2-363 GEN
Solar/Wind Harmer
3.514
274858EASY ROAD;U2
Solar/Wind Harmer
18.167
957751AF2-069 GEN
Solar/Wind Harmer
1.501
276157O29GEN1
Solar/Wind Harmer
16.728
939741AE1-205 GEN
Solar/Wind Harmer
2.278
970241AG2-163 GEN
Solar/Wind Harmer
2.735
276668AB2-070 GEN1
Solar/Wind Harmer
8.046
270100X2-052 CT1
50/50
3.356
274770LINCOLN ;1U
50/50
19.802
274771LINCOLN ;2U
50/50
19.802
971769AH1-391 GEN
Solar/Wind Harmer
1.305
957891AF2-083 GEN
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
2.286
945111AF1-176 GEN
Solar/Wind Harmer
12.464
964861AG1-349 GEN
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
128.268
940581AE2-045 GEN
Solar/Wind Harmer
0
971177AH1-047 GEN
Solar/Wind Harmer
0.701
970571AG2-364 GEN
Solar/Wind Harmer
2.343
971681AH1-341 GEN
Solar/Wind Harmer
1.746
938861AE1-114 GEN
Solar/Wind Harmer
27.221
276603SUBLETTE C
Solar/Wind Harmer
3.953
965011AG1-365 GEN
Solar/Wind Harmer
1.115
972175AH1-670 GEN
Solar/Wind Harmer
42.535
276174W4-005 GEN2
Solar/Wind Harmer
10.58
274773LINCOLN ;4U
50/50
19.802
276893AG1-478 C
Solar/Wind Harmer
-0.001
970239AG2-162 GEN
Solar/Wind Harmer
1.408
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
3.627
24691005MDL-2G C
Solar/Wind Harmer
15.061
971997AH1-543 GEN
Solar/Wind Harmer
1.886
274863CRW1-WTG
Solar/Wind Harmer
22.565
276863AD2-134 GEN
Solar/Wind Harmer
7.313
276889AE2-281 GEN
Solar/Wind Harmer
7.582
274856ECOGROVE ;U1
Solar/Wind Harmer
13.719
971549AH1-272 GEN
Solar/Wind Harmer
2.146
276158O29GEN2
Solar/Wind Harmer
16.728
276708O09 GEN2
Solar/Wind Harmer
14.08
965021AG1-366 GEN
Solar/Wind Harmer
4.46
274880W4-005 GEN4
Solar/Wind Harmer
10.58
971993AH1-541 GEN
Solar/Wind Harmer
0.983
971599AH1-298 GEN
50/50
20.938
970321AG2-212 GEN
Solar/Wind Harmer
2.856
270071AF1-092 GEN
Solar/Wind Harmer
1.913
970333AG2-219 GEN
Solar/Wind Harmer
4.04
276602WESTBROOK C
Solar/Wind Harmer
8.341
24387305FR-4G C
Solar/Wind Harmer
13.565
24386605FR-22G C
Solar/Wind Harmer
9.043
24387005FR-3G C
Solar/Wind Harmer
8.953
276645AC1-214 GEN1
Solar/Wind Harmer
4.919
942111AE2-223 GEN
Solar/Wind Harmer
26.656
970611AG2-400 GEN
Solar/Wind Harmer
1.115
270144AC1-141 ST1_
50/50
4.757
24642205MAYFLWER
50/50
1.656
960681AF2-359 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
19.542
276691AA1-018 GEN1
Solar/Wind Harmer
1.312
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
31.574
276872AE1-163_GEN1
Solar/Wind Harmer
26.538
971067AG2-660 GEN
Solar/Wind Harmer
4.734
276741O09 GEN1
Solar/Wind Harmer
14.08
276655WTG1_EQ
Solar/Wind Harmer
19.616
963841AG1-237 GEN
Solar/Wind Harmer
35.114
276686W4-005 GEN3
Solar/Wind Harmer
10.58
274854TWINGROVE;U2
Solar/Wind Harmer
27.356
959331AF2-224 GEN
Solar/Wind Harmer
1.115
944541AF1-119 GEN
Solar/Wind Harmer
0
274776LINCOLN ;7U
50/50
19.802
270526AF1-158 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
2.694
964401AG1-302 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
24.007
274872LEEDK;1U
Solar/Wind Harmer
0.529
270180AB1-006 GEN1
Solar/Wind Harmer
28.214
24791305MDL-5G
Solar/Wind Harmer
9.928
959081AF2-199 GEN
Solar/Wind Harmer
1.183
971475AH1-234 GEN
Solar/Wind Harmer
2.618
24386205FR-12G C
Solar/Wind Harmer
9.441
276646AC1-214 GEN2
Solar/Wind Harmer
4.919
276726Z2-087_GEN
Solar/Wind Harmer
29.618
963741AG1-226 GEN
Solar/Wind Harmer
4.923
276764AC1-053 GEN2
Solar/Wind Harmer
9.884
943021AE2-325 GEN
Solar/Wind Harmer
7.995
958011AF2-095 GEN
Solar/Wind Harmer
1.807
971573AH1-285 GEN
Solar/Wind Harmer
1.055
945421AF1-207 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
1.806
24697905MDL-4G C
Solar/Wind Harmer
9.928
942991AE2-321 GEN
Solar/Wind Harmer
1.197
971333AH1-146 GEN
Solar/Wind Harmer
2.381
970819AG2-516 GEN
Solar/Wind Harmer
1.407
274851PROVIDENC;RU
Solar/Wind Harmer
10.865
274878BISHOP HL;2U
Solar/Wind Harmer
13.215
965091AG1-374 GEN
Solar/Wind Harmer
3.362
965931AG1-462 GEN
Solar/Wind Harmer
2.821
276806AD2-047 C O1
Solar/Wind Harmer
38.651
958391AF2-133 GEN
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
22.119
971341AH1-150 GEN
Solar/Wind Harmer
2.367
276848AB2-070 GEN3
Solar/Wind Harmer
8.048
270471AD2-092_GEN
Solar/Wind Helper
0.709
270142AC1-141 CT1_
50/50
5.371
270143AC1-141 CT2_
50/50
5.371
24639705ELKHART HY
50/50
0.358
965681AG1-436 GEN
Solar/Wind Harmer
1.643
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
943591AF1-030 GEN
Solar/Wind Harmer
1.234
276901AD2-066 C O1
Solar/Wind Harmer
0
971343AH1-151 GEN
Solar/Wind Harmer
2.367
970169AG2-114 GEN
Solar/Wind Harmer
1.177
961011AF2-392 GEN
Solar/Wind Harmer
35.715
276785W4-005 GEN1
Solar/Wind Harmer
10.58
959341AF2-225 GEN
Solar/Wind Harmer
1.709
274848CAMPGROVE;RU
Solar/Wind Harmer
20.674
965651AG1-433 GEN
Solar/Wind Harmer
16.774
276849AB2-070 GEN2
Solar/Wind Harmer
8.046
944201AF1-088_MTX
Adder
195.89
957141AF2-008_MTX
Adder
97.945
NYPJM->LTFIMP_NY
CLTF
3.498
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.601
SIGELTFEXP_SIGE->PJM
CLTF
0.546
CBM West 2LTFEXP_CBM-W2->PJM
CBM
140.353
WECLTFEXP_WEC->PJM
CLTF
7.718
MECLTFEXP_MEC->PJM
CLTF
28.039
AG2-052LTFEXP_AG2-052->PJM
LTF
0.481
CBM West 1LTFEXP_CBM-W1->PJM
CBM
237.091
LGEELTFEXP_LGEE->PJM
CLTF
4.156
TVALTFEXP_TVA->PJM
CLTF
5.396
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
50.705
CBM South 1LTFEXP_CBM-S1->PJM
CBM
20.703
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.329
LAGNLTFEXP_LAGN->PJM
CLTF
14.593
AH1-155LTFEXP_AH1-155->PJM
LTF
0.721

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#6189_05HANG R 765_D1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.24 %
Rating:4961.0 MVA
Rating Type:B
MVA to Mitigate:5171.46
MW Contribution:2.0
Bus #Bus NameTypeMW Contribution
270142AC1-141 CT1_
50/50
5.003
270143AC1-141 CT2_
50/50
5.003
24639705ELKHART HY
50/50
0.334
965681AG1-436 GEN
Solar/Wind Harmer
1.52
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
943591AF1-030 GEN
Solar/Wind Harmer
1.142
276901AD2-066 C O1
Solar/Wind Harmer
0
971343AH1-151 GEN
Solar/Wind Harmer
2.19
970169AG2-114 GEN
Solar/Wind Harmer
1.084
961011AF2-392 GEN
Solar/Wind Harmer
33.045
276785W4-005 GEN1
Solar/Wind Harmer
9.69
972207SS24-0001
Solar/Wind Harmer
3.572
972181SS23-001
Solar/Wind Harmer
1.173
270055AF2-134 C O1
Solar/Wind Harmer
0
959091AF2-200 GEN
Solar/Wind Harmer
2.19
24755605MDL-5G
Solar/Wind Harmer
8.873
274849CRESCENT ;1U
Solar/Wind Harmer
6.934
274877BISHOP HL;1U
Solar/Wind Harmer
12.205
270349AD2-093_GEN
Solar/Wind Helper
0.7
274776LINCOLN ;7U
50/50
18.334
270526AF1-158 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
2.463
964401AG1-302 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
22.199
274872LEEDK;1U
Solar/Wind Harmer
0.49
959081AF2-199 GEN
Solar/Wind Harmer
1.095
971475AH1-234 GEN
Solar/Wind Harmer
2.423
270180AB1-006 GEN1
Solar/Wind Harmer
25.216
24791305MDL-5G
Solar/Wind Harmer
8.873
276646AC1-214 GEN2
Solar/Wind Harmer
4.542
276726Z2-087_GEN
Solar/Wind Harmer
27.235
24386205FR-12G C
Solar/Wind Harmer
8.429
963741AG1-226 GEN
Solar/Wind Harmer
4.409
276764AC1-053 GEN2
Solar/Wind Harmer
5.055
270144AC1-141 ST1_
50/50
4.431
24642205MAYFLWER
50/50
1.54
960681AF2-359 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
17.692
276691AA1-018 GEN1
Solar/Wind Harmer
1.213
971067AG2-660 GEN
Solar/Wind Harmer
4.38
276872AE1-163_GEN1
Solar/Wind Harmer
24.524
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
28.218
276741O09 GEN1
Solar/Wind Harmer
13.022
276655WTG1_EQ
Solar/Wind Harmer
18.038
965101AG1-375 GEN
Solar/Wind Harmer
1.03
963841AG1-237 GEN
Solar/Wind Harmer
31.4
276686W4-005 GEN3
Solar/Wind Harmer
9.69
943021AE2-325 GEN
Solar/Wind Harmer
7.445
958011AF2-095 GEN
Solar/Wind Harmer
1.672
971573AH1-285 GEN
Solar/Wind Harmer
0.977
958491AF2-143 GEN
Solar/Wind Harmer
1.67
942991AE2-321 GEN
Solar/Wind Harmer
1.107
971333AH1-146 GEN
Solar/Wind Harmer
2.203
945421AF1-207 GEN
Solar/Wind Harmer
0
970819AG2-516 GEN
Solar/Wind Harmer
1.302
24697905MDL-4G C
Solar/Wind Harmer
8.873
274851PROVIDENC;RU
Solar/Wind Harmer
10.033
274878BISHOP HL;2U
Solar/Wind Harmer
12.205
965091AG1-374 GEN
Solar/Wind Harmer
3.089
965931AG1-462 GEN
Solar/Wind Harmer
2.61
24344105CKG2
50/50
17.939
270101X2-052 CT2
50/50
3.105
965791AG1-447 GEN
Solar/Wind Harmer
13.376
276843GEN-1.7
Solar/Wind Harmer
1.918
941551AE2-152 GEN
Solar/Wind Harmer
0
270102X2-052 ST
50/50
3.361
970901AG2-562 GEN
50/50
12.734
274777LINCOLN ;8U
50/50
18.334
970245AG2-165 GEN
Solar/Wind Harmer
2.593
970349AG2-230 GEN
Solar/Wind Harmer
1.941
971347AH1-153 GEN
Solar/Wind Harmer
1.941
961051AF2-396 GEN
Solar/Wind Harmer
2.381
961051AF2-396 GEN
Solar/Wind Harmer
19.048
972231SS25-0005
Solar/Wind Harmer
1.876
274862TOP CROP ;2U
Solar/Wind Harmer
18.439
970921AG2-575 GEN
Solar/Wind Harmer
1.116
970921AG2-575 GEN
Solar/Wind Harmer
4.463
274879MINONK ;1U
Solar/Wind Harmer
26.041
971411AH1-196 GEN
Solar/Wind Harmer
1.654
274855GSG-6 ;RU
Solar/Wind Harmer
13.998
960971AF2-388 GEN
Solar/Wind Harmer
32.84
24386405FR-21G C
Solar/Wind Harmer
8.074
276763AC1-053 GEN1
Solar/Wind Harmer
5.055
274772LINCOLN ;3U
50/50
18.334
274774LINCOLN ;5U
50/50
18.334
270043AE2-236 GEN
Solar/Wind Harmer
0.672
971771AH1-392 GEN
Solar/Wind Harmer
1.094
270505AE1-170 C O1
Solar/Wind Harmer
1.802
274888KELLY CRK;1U
Solar/Wind Harmer
23.567
970941AG2-585 GEN
Solar/Wind Harmer
1.451
276805AD2-038 GEN
Solar/Wind Harmer
20.171
971605AH1-302 GEN
Solar/Wind Harmer
16.681
274850MENDOTA H;RU
Solar/Wind Harmer
9.914
276861AD2-134 GEN
Solar/Wind Harmer
6.767
274864CRW2-WTG
Solar/Wind Harmer
20.812
970569AG2-363 GEN
Solar/Wind Harmer
3.247
274858EASY ROAD;U2
Solar/Wind Harmer
16.811
276157O29GEN1
Solar/Wind Harmer
15.471
957751AF2-069 GEN
Solar/Wind Harmer
1.386
939741AE1-205 GEN
Solar/Wind Harmer
2.095
970241AG2-163 GEN
Solar/Wind Harmer
2.45
276668AB2-070 GEN1
Solar/Wind Harmer
7.368
270449AD2-020 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
26.738
943121AE2-341 GEN
Solar/Wind Harmer
1.714
957471AF2-041 GEN
Solar/Wind Harmer
3.285
965651AG1-433 GEN
Solar/Wind Harmer
16.42
274848CAMPGROVE;RU
Solar/Wind Harmer
19.088
959341AF2-225 GEN
Solar/Wind Harmer
1.571
276849AB2-070 GEN2
Solar/Wind Harmer
7.368
274773LINCOLN ;4U
50/50
18.334
276893AG1-478 C
Solar/Wind Harmer
-0.001
962691AG1-118 GEN
Solar/Wind Harmer
3.356
971997AH1-543 GEN
Solar/Wind Harmer
1.743
276863AD2-134 GEN
Solar/Wind Harmer
6.767
274863CRW1-WTG
Solar/Wind Harmer
20.812
276889AE2-281 GEN
Solar/Wind Harmer
7.007
957841AF2-078 GEN
Solar/Wind Harmer
0
274856ECOGROVE ;U1
Solar/Wind Harmer
12.696
971549AH1-272 GEN
Solar/Wind Harmer
2
24691005MDL-2G C
Solar/Wind Harmer
13.46
965021AG1-366 GEN
Solar/Wind Harmer
4.261
276158O29GEN2
Solar/Wind Harmer
15.471
276708O09 GEN2
Solar/Wind Harmer
13.022
958861AF2-177 GEN
Solar/Wind Harmer
32.122
945371AF1-202 GEN
Solar/Wind Harmer
15.376
274880W4-005 GEN4
Solar/Wind Harmer
9.69
971993AH1-541 GEN
Solar/Wind Harmer
0.9
970513AG2-328 GEN
Solar/Wind Harmer
2.593
970517AG2-330 GEN
Solar/Wind Harmer
40.453
270063AE2-323 C
Solar/Wind Harmer
0
970833AG2-524 GEN
Solar/Wind Harmer
1.263
959141AF2-205 GEN
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
1.061
971335AH1-147 GEN
Solar/Wind Harmer
2.203
971171AH1-044 GEN
Solar/Wind Harmer
2.19
926823AC1-168 GEN
Solar/Wind Harmer
13.291
24697605MDL-3G C
Solar/Wind Harmer
13.438
270181AB1-006 GEN2
Solar/Wind Harmer
1.672
276782AC1-033 GEN
Solar/Wind Harmer
13.789
24385905FR-11G C
Solar/Wind Harmer
15.873
946321AF1-296 GEN
Solar/Wind Harmer
30.676
959611AF2-252 GEN
Solar/Wind Harmer
4.119
960611AF2-352 GEN
Solar/Wind Harmer
4.119
945581AF1-223 GEN
Solar/Wind Harmer
0
270100X2-052 CT1
50/50
3.105
274770LINCOLN ;1U
50/50
18.334
274771LINCOLN ;2U
50/50
18.334
24653605MOTTVILLE
50/50
0.007
971769AH1-391 GEN
Solar/Wind Harmer
1.21
957891AF2-083 GEN
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
2.13
945111AF1-176 GEN
Solar/Wind Harmer
11.613
276897AD1-100 C
Solar/Wind Harmer
118.617
964861AG1-349 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
971177AH1-047 GEN
Solar/Wind Harmer
0.649
970571AG2-364 GEN
Solar/Wind Harmer
2.164
971681AH1-341 GEN
Solar/Wind Harmer
1.615
24344005CKG1
50/50
20.846
24641605TWIN BRNCH
50/50
0.036
24643105BUCHANAN
50/50
0.026
970707AG2-453 GEN
Solar/Wind Harmer
3.267
274887GEN-1.85
Solar/Wind Harmer
21.649
944531AF1-118 GEN
Solar/Wind Harmer
4.019
970833AG2-524 GEN
Solar/Wind Harmer
10.102
958481AF2-142 GEN
Solar/Wind Harmer
1.69
276868AE1-113 GEN
Solar/Wind Harmer
37.233
971675AH1-338 GEN
Solar/Wind Harmer
1.984
970781AG2-491 GEN
Solar/Wind Harmer
1.072
966841AG1-555 GEN
Solar/Wind Harmer
0
274853TWINGROVE;U1
Solar/Wind Harmer
25.403
938861AE1-114 GEN
Solar/Wind Harmer
25.188
276603SUBLETTE C
Solar/Wind Harmer
3.658
965011AG1-365 GEN
Solar/Wind Harmer
1.065
972175AH1-670 GEN
Solar/Wind Harmer
39.016
276174W4-005 GEN2
Solar/Wind Harmer
9.69
274872LEEDK;1U
Solar/Wind Harmer
32.286
276882AE2-255 GEN
Solar/Wind Harmer
11.746
959331AF2-224 GEN
Solar/Wind Harmer
1.065
944541AF1-119 GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
25.135
274775LINCOLN ;6U
50/50
18.334
960591AF2-350 GEN
Solar/Wind Harmer
1.161
939351AE1-166 GEN
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
3.451
958381AF2-132 GEN
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
21.736
939401AE1-172 GEN
Solar/Wind Harmer
44.44
276876AE1-163_GEN2
Solar/Wind Harmer
24.524
274857EASY ROAD;U1
Solar/Wind Harmer
16.811
276656WTG2_EQ
Solar/Wind Harmer
2.388
941731AE2-173 GEN
Solar/Wind Harmer
10.475
970521AG2-332 GEN
50/50
23.771
276806AD2-047 C O1
Solar/Wind Harmer
35.756
274847GR RIDGE ;BU
Solar/Wind Harmer
20.461
958391AF2-133 GEN
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
2.19
247642Z2-115 C
Solar/Wind Harmer
-0.001
276848AB2-070 GEN3
Solar/Wind Harmer
7.37
270471AD2-092_GEN
Solar/Wind Helper
0.7
971599AH1-298 GEN
50/50
20.056
970321AG2-212 GEN
Solar/Wind Harmer
2.593
270071AF1-092 GEN
Solar/Wind Harmer
1.802
276602WESTBROOK C
Solar/Wind Harmer
7.719
970611AG2-400 GEN
Solar/Wind Harmer
1.065
276645AC1-214 GEN1
Solar/Wind Harmer
4.542
942111AE2-223 GEN
Solar/Wind Harmer
24.512
24387305FR-4G C
Solar/Wind Harmer
12.111
24386605FR-22G C
Solar/Wind Harmer
8.074
24387005FR-3G C
Solar/Wind Harmer
7.993
944201AF1-088_MTX
Adder
164.341
957141AF2-008_MTX
Adder
82.17
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.252
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.132
LAGNLTFEXP_LAGN->PJM
CLTF
14.106
AH1-155LTFEXP_AH1-155->PJM
LTF
0.661
CBM West 1LTFEXP_CBM-W1->PJM
CBM
221.335
LGEELTFEXP_LGEE->PJM
CLTF
5.67
TVALTFEXP_TVA->PJM
CLTF
5.42
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
42.769
NYPJM->LTFIMP_NY
CLTF
3.333
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.48
SIGELTFEXP_SIGE->PJM
CLTF
0.556
CBM West 2LTFEXP_CBM-W2->PJM
CBM
133.208
WECLTFEXP_WEC->PJM
CLTF
7.144
MECLTFEXP_MEC->PJM
CLTF
26.01
AG2-052LTFEXP_AG2-052->PJM
LTF
0.441

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P4_#709_05HANG R 765_D2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#709_05HANG R 765_D2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.76 %
Rating:4961.0 MVA
Rating Type:B
MVA to Mitigate:5098.14
MW Contribution:2.0
Bus #Bus NameTypeMW Contribution
270142AC1-141 CT1_
50/50
5.015
270143AC1-141 CT2_
50/50
5.015
24639705ELKHART HY
50/50
0.335
965681AG1-436 GEN
Solar/Wind Harmer
1.524
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
943591AF1-030 GEN
Solar/Wind Harmer
1.145
276901AD2-066 C O1
Solar/Wind Harmer
0
971343AH1-151 GEN
Solar/Wind Harmer
2.196
970169AG2-114 GEN
Solar/Wind Harmer
1.087
961011AF2-392 GEN
Solar/Wind Harmer
33.139
276785W4-005 GEN1
Solar/Wind Harmer
9.72
972207SS24-0001
Solar/Wind Harmer
3.581
972181SS23-001
Solar/Wind Harmer
1.176
270055AF2-134 C O1
Solar/Wind Harmer
0
959091AF2-200 GEN
Solar/Wind Harmer
2.196
24755605MDL-5G
Solar/Wind Harmer
8.898
274849CRESCENT ;1U
Solar/Wind Harmer
6.954
274877BISHOP HL;1U
Solar/Wind Harmer
12.24
270349AD2-093_GEN
Solar/Wind Helper
0.697
274776LINCOLN ;7U
50/50
18.381
270526AF1-158 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
2.469
964401AG1-302 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
22.259
274872LEEDK;1U
Solar/Wind Harmer
0.491
959081AF2-199 GEN
Solar/Wind Harmer
1.098
971475AH1-234 GEN
Solar/Wind Harmer
2.43
270180AB1-006 GEN1
Solar/Wind Harmer
25.287
24791305MDL-5G
Solar/Wind Harmer
8.898
276646AC1-214 GEN2
Solar/Wind Harmer
4.555
276726Z2-087_GEN
Solar/Wind Harmer
27.314
24386205FR-12G C
Solar/Wind Harmer
8.454
963741AG1-226 GEN
Solar/Wind Harmer
4.423
276764AC1-053 GEN2
Solar/Wind Harmer
5.071
270144AC1-141 ST1_
50/50
4.442
24642205MAYFLWER
50/50
1.544
960681AF2-359 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
17.74
276691AA1-018 GEN1
Solar/Wind Harmer
1.216
971067AG2-660 GEN
Solar/Wind Harmer
4.392
276872AE1-163_GEN1
Solar/Wind Harmer
24.592
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
28.298
276741O09 GEN1
Solar/Wind Harmer
13.059
276655WTG1_EQ
Solar/Wind Harmer
18.09
965101AG1-375 GEN
Solar/Wind Harmer
1.033
963841AG1-237 GEN
Solar/Wind Harmer
31.494
276686W4-005 GEN3
Solar/Wind Harmer
9.72
943021AE2-325 GEN
Solar/Wind Harmer
7.464
958011AF2-095 GEN
Solar/Wind Harmer
1.676
971573AH1-285 GEN
Solar/Wind Harmer
0.979
958491AF2-143 GEN
Solar/Wind Harmer
1.674
942991AE2-321 GEN
Solar/Wind Harmer
1.111
971333AH1-146 GEN
Solar/Wind Harmer
2.209
945421AF1-207 GEN
Solar/Wind Harmer
0
970819AG2-516 GEN
Solar/Wind Harmer
1.306
24697905MDL-4G C
Solar/Wind Harmer
8.898
274851PROVIDENC;RU
Solar/Wind Harmer
10.062
274878BISHOP HL;2U
Solar/Wind Harmer
12.24
965091AG1-374 GEN
Solar/Wind Harmer
3.098
965931AG1-462 GEN
Solar/Wind Harmer
2.618
270102X2-052 ST
50/50
3.369
970901AG2-562 GEN
50/50
12.765
274777LINCOLN ;8U
50/50
18.381
970245AG2-165 GEN
Solar/Wind Harmer
2.599
970349AG2-230 GEN
Solar/Wind Harmer
1.946
971347AH1-153 GEN
Solar/Wind Harmer
1.946
961051AF2-396 GEN
Solar/Wind Harmer
2.387
961051AF2-396 GEN
Solar/Wind Harmer
19.097
972231SS25-0005
Solar/Wind Harmer
1.881
274862TOP CROP ;2U
Solar/Wind Harmer
18.489
970921AG2-575 GEN
Solar/Wind Harmer
1.119
970921AG2-575 GEN
Solar/Wind Harmer
4.476
274879MINONK ;1U
Solar/Wind Harmer
26.112
971411AH1-196 GEN
Solar/Wind Harmer
1.658
274855GSG-6 ;RU
Solar/Wind Harmer
14.037
960971AF2-388 GEN
Solar/Wind Harmer
32.934
24386405FR-21G C
Solar/Wind Harmer
8.098
276763AC1-053 GEN1
Solar/Wind Harmer
5.071
274772LINCOLN ;3U
50/50
18.381
274774LINCOLN ;5U
50/50
18.381
270043AE2-236 GEN
Solar/Wind Harmer
0.674
971771AH1-392 GEN
Solar/Wind Harmer
1.097
270505AE1-170 C O1
Solar/Wind Harmer
1.807
274888KELLY CRK;1U
Solar/Wind Harmer
23.628
970941AG2-585 GEN
Solar/Wind Harmer
1.455
276805AD2-038 GEN
Solar/Wind Harmer
20.225
971605AH1-302 GEN
Solar/Wind Harmer
16.727
274850MENDOTA H;RU
Solar/Wind Harmer
9.942
276861AD2-134 GEN
Solar/Wind Harmer
6.785
274864CRW2-WTG
Solar/Wind Harmer
20.869
970569AG2-363 GEN
Solar/Wind Harmer
3.256
274858EASY ROAD;U2
Solar/Wind Harmer
16.859
276157O29GEN1
Solar/Wind Harmer
15.515
957751AF2-069 GEN
Solar/Wind Harmer
1.39
939741AE1-205 GEN
Solar/Wind Harmer
2.101
970241AG2-163 GEN
Solar/Wind Harmer
2.457
276668AB2-070 GEN1
Solar/Wind Harmer
7.391
270449AD2-020 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
26.808
943121AE2-341 GEN
Solar/Wind Harmer
1.718
957471AF2-041 GEN
Solar/Wind Harmer
3.294
965651AG1-433 GEN
Solar/Wind Harmer
16.467
274848CAMPGROVE;RU
Solar/Wind Harmer
19.143
959341AF2-225 GEN
Solar/Wind Harmer
1.576
276849AB2-070 GEN2
Solar/Wind Harmer
7.391
274773LINCOLN ;4U
50/50
18.381
276893AG1-478 C
Solar/Wind Harmer
-0.001
962691AG1-118 GEN
Solar/Wind Harmer
3.365
971997AH1-543 GEN
Solar/Wind Harmer
1.748
276863AD2-134 GEN
Solar/Wind Harmer
6.785
274863CRW1-WTG
Solar/Wind Harmer
20.869
276889AE2-281 GEN
Solar/Wind Harmer
7.026
957841AF2-078 GEN
Solar/Wind Harmer
0
274856ECOGROVE ;U1
Solar/Wind Harmer
12.731
971549AH1-272 GEN
Solar/Wind Harmer
2.005
24691005MDL-2G C
Solar/Wind Harmer
13.498
965021AG1-366 GEN
Solar/Wind Harmer
4.273
276158O29GEN2
Solar/Wind Harmer
15.515
276708O09 GEN2
Solar/Wind Harmer
13.059
958861AF2-177 GEN
Solar/Wind Harmer
32.216
945371AF1-202 GEN
Solar/Wind Harmer
15.423
274880W4-005 GEN4
Solar/Wind Harmer
9.72
971993AH1-541 GEN
Solar/Wind Harmer
0.903
970513AG2-328 GEN
Solar/Wind Harmer
2.599
970517AG2-330 GEN
Solar/Wind Harmer
40.548
270063AE2-323 C
Solar/Wind Harmer
0
970833AG2-524 GEN
Solar/Wind Harmer
1.266
959141AF2-205 GEN
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
1.064
971335AH1-147 GEN
Solar/Wind Harmer
2.209
971171AH1-044 GEN
Solar/Wind Harmer
2.196
926823AC1-168 GEN
Solar/Wind Harmer
13.329
24697605MDL-3G C
Solar/Wind Harmer
13.476
270181AB1-006 GEN2
Solar/Wind Harmer
1.676
276782AC1-033 GEN
Solar/Wind Harmer
13.828
24385905FR-11G C
Solar/Wind Harmer
15.919
946321AF1-296 GEN
Solar/Wind Harmer
30.766
959611AF2-252 GEN
Solar/Wind Harmer
4.131
960611AF2-352 GEN
Solar/Wind Harmer
4.131
945581AF1-223 GEN
Solar/Wind Harmer
0
24344005CKG1
50/50
20.898
24641605TWIN BRNCH
50/50
0.036
24643105BUCHANAN
50/50
0.026
970707AG2-453 GEN
Solar/Wind Harmer
3.275
274887GEN-1.85
Solar/Wind Harmer
21.706
944531AF1-118 GEN
Solar/Wind Harmer
4.029
970833AG2-524 GEN
Solar/Wind Harmer
10.129
958481AF2-142 GEN
Solar/Wind Harmer
1.694
270100X2-052 CT1
50/50
3.113
274770LINCOLN ;1U
50/50
18.381
274771LINCOLN ;2U
50/50
18.381
24653605MOTTVILLE
50/50
0.007
971769AH1-391 GEN
Solar/Wind Harmer
1.213
957891AF2-083 GEN
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
2.136
945111AF1-176 GEN
Solar/Wind Harmer
11.643
276897AD1-100 C
Solar/Wind Harmer
118.927
964861AG1-349 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
971177AH1-047 GEN
Solar/Wind Harmer
0.65
970571AG2-364 GEN
Solar/Wind Harmer
2.17
971681AH1-341 GEN
Solar/Wind Harmer
1.62
938861AE1-114 GEN
Solar/Wind Harmer
25.259
276603SUBLETTE C
Solar/Wind Harmer
3.668
965011AG1-365 GEN
Solar/Wind Harmer
1.068
972175AH1-670 GEN
Solar/Wind Harmer
39.134
276174W4-005 GEN2
Solar/Wind Harmer
9.72
276868AE1-113 GEN
Solar/Wind Harmer
37.335
971675AH1-338 GEN
Solar/Wind Harmer
1.99
970781AG2-491 GEN
Solar/Wind Harmer
1.075
966841AG1-555 GEN
Solar/Wind Harmer
0
274853TWINGROVE;U1
Solar/Wind Harmer
25.477
24344105CKG2
50/50
17.979
270101X2-052 CT2
50/50
3.113
965791AG1-447 GEN
Solar/Wind Harmer
13.41
276843GEN-1.7
Solar/Wind Harmer
1.923
941551AE2-152 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
32.374
276882AE2-255 GEN
Solar/Wind Harmer
11.778
959331AF2-224 GEN
Solar/Wind Harmer
1.068
944541AF1-119 GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
25.209
274775LINCOLN ;6U
50/50
18.381
960591AF2-350 GEN
Solar/Wind Harmer
1.164
939351AE1-166 GEN
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
3.46
958381AF2-132 GEN
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
21.795
939401AE1-172 GEN
Solar/Wind Harmer
44.561
276876AE1-163_GEN2
Solar/Wind Harmer
24.592
274857EASY ROAD;U1
Solar/Wind Harmer
16.859
276656WTG2_EQ
Solar/Wind Harmer
2.395
941731AE2-173 GEN
Solar/Wind Harmer
10.505
970521AG2-332 GEN
50/50
23.831
971599AH1-298 GEN
50/50
20.101
970321AG2-212 GEN
Solar/Wind Harmer
2.599
270071AF1-092 GEN
Solar/Wind Harmer
1.806
276602WESTBROOK C
Solar/Wind Harmer
7.74
970611AG2-400 GEN
Solar/Wind Harmer
1.068
276645AC1-214 GEN1
Solar/Wind Harmer
4.555
942111AE2-223 GEN
Solar/Wind Harmer
24.582
24387305FR-4G C
Solar/Wind Harmer
12.146
24386605FR-22G C
Solar/Wind Harmer
8.098
24387005FR-3G C
Solar/Wind Harmer
8.017
276806AD2-047 C O1
Solar/Wind Harmer
35.85
274847GR RIDGE ;BU
Solar/Wind Harmer
20.515
958391AF2-133 GEN
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
2.196
247642Z2-115 C
Solar/Wind Harmer
-0.001
276848AB2-070 GEN3
Solar/Wind Harmer
7.393
270471AD2-092_GEN
Solar/Wind Helper
0.697
944201AF1-088_MTX
Adder
164.946
957141AF2-008_MTX
Adder
82.473
CBM West 2LTFEXP_CBM-W2->PJM
CBM
133.912
WECLTFEXP_WEC->PJM
CLTF
7.164
MECLTFEXP_MEC->PJM
CLTF
26.098
AG2-052LTFEXP_AG2-052->PJM
LTF
0.442
NYPJM->LTFIMP_NY
CLTF
3.299
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.459
SIGELTFEXP_SIGE->PJM
CLTF
0.559
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.451
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.097
LAGNLTFEXP_LAGN->PJM
CLTF
14.212
AH1-155LTFEXP_AH1-155->PJM
LTF
0.663
CBM West 1LTFEXP_CBM-W1->PJM
CBM
222.098
LGEELTFEXP_LGEE->PJM
CLTF
5.706
TVALTFEXP_TVA->PJM
CLTF
5.473
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
42.769

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#709_546_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.76 %
Rating:4961.0 MVA
Rating Type:B
MVA to Mitigate:5098.11
MW Contribution:2.0
Bus #Bus NameTypeMW Contribution
270142AC1-141 CT1_
50/50
5.015
270143AC1-141 CT2_
50/50
5.015
24639705ELKHART HY
50/50
0.335
965681AG1-436 GEN
Solar/Wind Harmer
1.524
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
943591AF1-030 GEN
Solar/Wind Harmer
1.145
276901AD2-066 C O1
Solar/Wind Harmer
0
971343AH1-151 GEN
Solar/Wind Harmer
2.196
970169AG2-114 GEN
Solar/Wind Harmer
1.087
961011AF2-392 GEN
Solar/Wind Harmer
33.139
276785W4-005 GEN1
Solar/Wind Harmer
9.72
972207SS24-0001
Solar/Wind Harmer
3.581
972181SS23-001
Solar/Wind Harmer
1.176
270055AF2-134 C O1
Solar/Wind Harmer
0
959091AF2-200 GEN
Solar/Wind Harmer
2.196
24755605MDL-5G
Solar/Wind Harmer
8.898
274849CRESCENT ;1U
Solar/Wind Harmer
6.954
274877BISHOP HL;1U
Solar/Wind Harmer
12.24
270349AD2-093_GEN
Solar/Wind Helper
0.697
274776LINCOLN ;7U
50/50
18.381
270526AF1-158 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
2.469
964401AG1-302 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
22.259
274872LEEDK;1U
Solar/Wind Harmer
0.491
959081AF2-199 GEN
Solar/Wind Harmer
1.098
971475AH1-234 GEN
Solar/Wind Harmer
2.43
270180AB1-006 GEN1
Solar/Wind Harmer
25.287
24791305MDL-5G
Solar/Wind Harmer
8.898
276646AC1-214 GEN2
Solar/Wind Harmer
4.555
276726Z2-087_GEN
Solar/Wind Harmer
27.314
24386205FR-12G C
Solar/Wind Harmer
8.454
963741AG1-226 GEN
Solar/Wind Harmer
4.423
276764AC1-053 GEN2
Solar/Wind Harmer
5.071
270144AC1-141 ST1_
50/50
4.442
24642205MAYFLWER
50/50
1.544
960681AF2-359 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
17.74
276691AA1-018 GEN1
Solar/Wind Harmer
1.216
971067AG2-660 GEN
Solar/Wind Harmer
4.392
276872AE1-163_GEN1
Solar/Wind Harmer
24.592
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
28.298
276741O09 GEN1
Solar/Wind Harmer
13.059
276655WTG1_EQ
Solar/Wind Harmer
18.09
965101AG1-375 GEN
Solar/Wind Harmer
1.033
963841AG1-237 GEN
Solar/Wind Harmer
31.494
276686W4-005 GEN3
Solar/Wind Harmer
9.72
943021AE2-325 GEN
Solar/Wind Harmer
7.464
958011AF2-095 GEN
Solar/Wind Harmer
1.676
971573AH1-285 GEN
Solar/Wind Harmer
0.979
958491AF2-143 GEN
Solar/Wind Harmer
1.674
942991AE2-321 GEN
Solar/Wind Harmer
1.111
971333AH1-146 GEN
Solar/Wind Harmer
2.209
945421AF1-207 GEN
Solar/Wind Harmer
0
970819AG2-516 GEN
Solar/Wind Harmer
1.306
24697905MDL-4G C
Solar/Wind Harmer
8.898
274851PROVIDENC;RU
Solar/Wind Harmer
10.062
274878BISHOP HL;2U
Solar/Wind Harmer
12.24
965091AG1-374 GEN
Solar/Wind Harmer
3.098
965931AG1-462 GEN
Solar/Wind Harmer
2.618
24344105CKG2
50/50
17.979
270101X2-052 CT2
50/50
3.113
965791AG1-447 GEN
Solar/Wind Harmer
13.41
276843GEN-1.7
Solar/Wind Harmer
1.923
941551AE2-152 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
32.374
276882AE2-255 GEN
Solar/Wind Harmer
11.778
959331AF2-224 GEN
Solar/Wind Harmer
1.068
944541AF1-119 GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
25.209
270102X2-052 ST
50/50
3.369
970901AG2-562 GEN
50/50
12.765
274777LINCOLN ;8U
50/50
18.381
970245AG2-165 GEN
Solar/Wind Harmer
2.599
970349AG2-230 GEN
Solar/Wind Harmer
1.946
971347AH1-153 GEN
Solar/Wind Harmer
1.946
961051AF2-396 GEN
Solar/Wind Harmer
2.387
961051AF2-396 GEN
Solar/Wind Harmer
19.097
972231SS25-0005
Solar/Wind Harmer
1.881
274862TOP CROP ;2U
Solar/Wind Harmer
18.489
970921AG2-575 GEN
Solar/Wind Harmer
1.119
970921AG2-575 GEN
Solar/Wind Harmer
4.476
274879MINONK ;1U
Solar/Wind Harmer
26.112
971411AH1-196 GEN
Solar/Wind Harmer
1.658
274855GSG-6 ;RU
Solar/Wind Harmer
14.037
960971AF2-388 GEN
Solar/Wind Harmer
32.934
24386405FR-21G C
Solar/Wind Harmer
8.098
276763AC1-053 GEN1
Solar/Wind Harmer
5.071
274772LINCOLN ;3U
50/50
18.381
274774LINCOLN ;5U
50/50
18.381
270043AE2-236 GEN
Solar/Wind Harmer
0.674
971771AH1-392 GEN
Solar/Wind Harmer
1.097
270505AE1-170 C O1
Solar/Wind Harmer
1.807
274888KELLY CRK;1U
Solar/Wind Harmer
23.628
970941AG2-585 GEN
Solar/Wind Harmer
1.455
276805AD2-038 GEN
Solar/Wind Harmer
20.225
971605AH1-302 GEN
Solar/Wind Harmer
16.727
274850MENDOTA H;RU
Solar/Wind Harmer
9.942
276861AD2-134 GEN
Solar/Wind Harmer
6.785
274864CRW2-WTG
Solar/Wind Harmer
20.869
970569AG2-363 GEN
Solar/Wind Harmer
3.256
274858EASY ROAD;U2
Solar/Wind Harmer
16.859
276157O29GEN1
Solar/Wind Harmer
15.515
957751AF2-069 GEN
Solar/Wind Harmer
1.39
939741AE1-205 GEN
Solar/Wind Harmer
2.101
970241AG2-163 GEN
Solar/Wind Harmer
2.457
276668AB2-070 GEN1
Solar/Wind Harmer
7.391
270449AD2-020 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
26.808
943121AE2-341 GEN
Solar/Wind Harmer
1.718
957471AF2-041 GEN
Solar/Wind Harmer
3.294
965651AG1-433 GEN
Solar/Wind Harmer
16.467
274848CAMPGROVE;RU
Solar/Wind Harmer
19.143
959341AF2-225 GEN
Solar/Wind Harmer
1.576
276849AB2-070 GEN2
Solar/Wind Harmer
7.391
274773LINCOLN ;4U
50/50
18.381
276893AG1-478 C
Solar/Wind Harmer
-0.001
962691AG1-118 GEN
Solar/Wind Harmer
3.365
971997AH1-543 GEN
Solar/Wind Harmer
1.748
276863AD2-134 GEN
Solar/Wind Harmer
6.785
274863CRW1-WTG
Solar/Wind Harmer
20.869
276889AE2-281 GEN
Solar/Wind Harmer
7.026
957841AF2-078 GEN
Solar/Wind Harmer
0
274856ECOGROVE ;U1
Solar/Wind Harmer
12.731
971549AH1-272 GEN
Solar/Wind Harmer
2.005
24691005MDL-2G C
Solar/Wind Harmer
13.498
965021AG1-366 GEN
Solar/Wind Harmer
4.273
276158O29GEN2
Solar/Wind Harmer
15.515
276708O09 GEN2
Solar/Wind Harmer
13.059
958861AF2-177 GEN
Solar/Wind Harmer
32.216
945371AF1-202 GEN
Solar/Wind Harmer
15.423
274880W4-005 GEN4
Solar/Wind Harmer
9.72
971993AH1-541 GEN
Solar/Wind Harmer
0.903
970513AG2-328 GEN
Solar/Wind Harmer
2.599
970517AG2-330 GEN
Solar/Wind Harmer
40.548
270063AE2-323 C
Solar/Wind Harmer
0
970833AG2-524 GEN
Solar/Wind Harmer
1.266
959141AF2-205 GEN
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
1.064
971335AH1-147 GEN
Solar/Wind Harmer
2.209
971171AH1-044 GEN
Solar/Wind Harmer
2.196
926823AC1-168 GEN
Solar/Wind Harmer
13.329
24697605MDL-3G C
Solar/Wind Harmer
13.476
270181AB1-006 GEN2
Solar/Wind Harmer
1.676
276782AC1-033 GEN
Solar/Wind Harmer
13.828
24385905FR-11G C
Solar/Wind Harmer
15.919
946321AF1-296 GEN
Solar/Wind Harmer
30.766
959611AF2-252 GEN
Solar/Wind Harmer
4.131
960611AF2-352 GEN
Solar/Wind Harmer
4.131
945581AF1-223 GEN
Solar/Wind Harmer
0
270100X2-052 CT1
50/50
3.113
274770LINCOLN ;1U
50/50
18.381
274771LINCOLN ;2U
50/50
18.381
24653605MOTTVILLE
50/50
0.007
971769AH1-391 GEN
Solar/Wind Harmer
1.213
957891AF2-083 GEN
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
2.136
945111AF1-176 GEN
Solar/Wind Harmer
11.643
276897AD1-100 C
Solar/Wind Harmer
118.927
964861AG1-349 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
971177AH1-047 GEN
Solar/Wind Harmer
0.65
970571AG2-364 GEN
Solar/Wind Harmer
2.17
971681AH1-341 GEN
Solar/Wind Harmer
1.62
938861AE1-114 GEN
Solar/Wind Harmer
25.259
276603SUBLETTE C
Solar/Wind Harmer
3.668
965011AG1-365 GEN
Solar/Wind Harmer
1.068
972175AH1-670 GEN
Solar/Wind Harmer
39.134
276174W4-005 GEN2
Solar/Wind Harmer
9.72
24344005CKG1
50/50
20.898
24641605TWIN BRNCH
50/50
0.036
24643105BUCHANAN
50/50
0.026
970707AG2-453 GEN
Solar/Wind Harmer
3.275
274887GEN-1.85
Solar/Wind Harmer
21.706
944531AF1-118 GEN
Solar/Wind Harmer
4.029
970833AG2-524 GEN
Solar/Wind Harmer
10.129
958481AF2-142 GEN
Solar/Wind Harmer
1.694
276868AE1-113 GEN
Solar/Wind Harmer
37.335
971675AH1-338 GEN
Solar/Wind Harmer
1.99
970781AG2-491 GEN
Solar/Wind Harmer
1.075
966841AG1-555 GEN
Solar/Wind Harmer
0
274853TWINGROVE;U1
Solar/Wind Harmer
25.477
971599AH1-298 GEN
50/50
20.101
970321AG2-212 GEN
Solar/Wind Harmer
2.599
270071AF1-092 GEN
Solar/Wind Harmer
1.806
276602WESTBROOK C
Solar/Wind Harmer
7.74
970611AG2-400 GEN
Solar/Wind Harmer
1.068
276645AC1-214 GEN1
Solar/Wind Harmer
4.555
942111AE2-223 GEN
Solar/Wind Harmer
24.582
24387305FR-4G C
Solar/Wind Harmer
12.146
24386605FR-22G C
Solar/Wind Harmer
8.098
24387005FR-3G C
Solar/Wind Harmer
8.017
274775LINCOLN ;6U
50/50
18.381
960591AF2-350 GEN
Solar/Wind Harmer
1.164
939351AE1-166 GEN
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
3.46
958381AF2-132 GEN
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
21.795
939401AE1-172 GEN
Solar/Wind Harmer
44.561
276876AE1-163_GEN2
Solar/Wind Harmer
24.592
274857EASY ROAD;U1
Solar/Wind Harmer
16.859
276656WTG2_EQ
Solar/Wind Harmer
2.395
941731AE2-173 GEN
Solar/Wind Harmer
10.505
970521AG2-332 GEN
50/50
23.831
276806AD2-047 C O1
Solar/Wind Harmer
35.85
274847GR RIDGE ;BU
Solar/Wind Harmer
20.515
958391AF2-133 GEN
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
2.196
247642Z2-115 C
Solar/Wind Harmer
-0.001
276848AB2-070 GEN3
Solar/Wind Harmer
7.393
270471AD2-092_GEN
Solar/Wind Helper
0.697
944201AF1-088_MTX
Adder
164.946
957141AF2-008_MTX
Adder
82.473
NYPJM->LTFIMP_NY
CLTF
3.299
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.459
SIGELTFEXP_SIGE->PJM
CLTF
0.559
CBM West 2LTFEXP_CBM-W2->PJM
CBM
133.912
WECLTFEXP_WEC->PJM
CLTF
7.164
MECLTFEXP_MEC->PJM
CLTF
26.098
AG2-052LTFEXP_AG2-052->PJM
LTF
0.442
CBM West 1LTFEXP_CBM-W1->PJM
CBM
222.098
LGEELTFEXP_LGEE->PJM
CLTF
5.706
TVALTFEXP_TVA->PJM
CLTF
5.473
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
42.769
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.451
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.097
LAGNLTFEXP_LAGN->PJM
CLTF
14.212
AH1-155LTFEXP_AH1-155->PJM
LTF
0.663

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#1760_05JEFRSO 765_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.41 %
Rating:4961.0 MVA
Rating Type:B
MVA to Mitigate:4981.37
MW Contribution:2.15
Bus #Bus NameTypeMW Contribution
270142AC1-141 CT1_
50/50
5.381
270143AC1-141 CT2_
50/50
5.381
24639705ELKHART HY
50/50
0.359
965681AG1-436 GEN
Solar/Wind Harmer
1.638
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
943591AF1-030 GEN
Solar/Wind Harmer
1.214
276901AD2-066 C O1
Solar/Wind Harmer
0
971343AH1-151 GEN
Solar/Wind Harmer
2.318
970169AG2-114 GEN
Solar/Wind Harmer
1.141
961011AF2-392 GEN
Solar/Wind Harmer
34.864
270526AF1-158 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
8.008
958011AF2-095 GEN
Solar/Wind Harmer
1.781
971573AH1-285 GEN
Solar/Wind Harmer
1.038
945421AF1-207 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
1.769
942991AE2-321 GEN
Solar/Wind Harmer
1.174
972207SS24-0001
Solar/Wind Harmer
3.811
270055AF2-134 C O1
Solar/Wind Harmer
0
972181SS23-001
Solar/Wind Harmer
1.253
24755605MDL-5G
Solar/Wind Harmer
9.707
959091AF2-200 GEN
Solar/Wind Harmer
2.318
274849CRESCENT ;1U
Solar/Wind Harmer
7.294
274877BISHOP HL;1U
Solar/Wind Harmer
12.834
970289AG2-191 GEN
Solar/Wind Harmer
0.195
270349AD2-093_GEN
Solar/Wind Helper
0.687
270100X2-052 CT1
50/50
3.348
24653605MOTTVILLE
50/50
0.008
24307105BERRINSP G
50/50
0.048
971769AH1-391 GEN
Solar/Wind Harmer
1.303
957891AF2-083 GEN
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
2.29
945111AF1-176 GEN
Solar/Wind Harmer
12.484
964861AG1-349 GEN
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
126.162
940581AE2-045 GEN
Solar/Wind Harmer
0
971177AH1-047 GEN
Solar/Wind Harmer
0.687
970571AG2-364 GEN
Solar/Wind Harmer
2.284
971681AH1-341 GEN
Solar/Wind Harmer
1.706
938861AE1-114 GEN
Solar/Wind Harmer
26.61
276603SUBLETTE C
Solar/Wind Harmer
3.862
24344005CKG1
50/50
22.459
24641605TWIN BRNCH
50/50
0.039
24643105BUCHANAN
50/50
0.028
970699AG2-449 GEN
Solar/Wind Harmer
1.59
970707AG2-453 GEN
Solar/Wind Harmer
3.479
274887GEN-1.85
Solar/Wind Harmer
23.06
970833AG2-524 GEN
Solar/Wind Harmer
10.74
958481AF2-142 GEN
Solar/Wind Harmer
1.793
944531AF1-118 GEN
Solar/Wind Harmer
4.156
276868AE1-113 GEN
Solar/Wind Harmer
39.421
970781AG2-491 GEN
Solar/Wind Harmer
1.172
971675AH1-338 GEN
Solar/Wind Harmer
2.102
966841AG1-555 GEN
Solar/Wind Harmer
0
274853TWINGROVE;U1
Solar/Wind Harmer
26.481
24344105CKG2
50/50
19.362
270101X2-052 CT2
50/50
3.348
965791AG1-447 GEN
Solar/Wind Harmer
14.413
276843GEN-1.7
Solar/Wind Harmer
2.043
941551AE2-152 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
34.229
276882AE2-255 GEN
Solar/Wind Harmer
12.436
959331AF2-224 GEN
Solar/Wind Harmer
1.123
944541AF1-119 GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
26.202
270144AC1-141 ST1_
50/50
4.766
24642205MAYFLWER
50/50
1.656
970519AG2-331 GEN
Solar/Wind Harmer
41.339
958381AF2-132 GEN
Solar/Wind Harmer
0
960591AF2-350 GEN
Solar/Wind Harmer
1.237
939351AE1-166 GEN
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
3.677
276694AA1-018 GEN2
Solar/Wind Harmer
23.067
939401AE1-172 GEN
Solar/Wind Harmer
46.994
276876AE1-163_GEN2
Solar/Wind Harmer
25.923
274857EASY ROAD;U1
Solar/Wind Harmer
17.754
276656WTG2_EQ
Solar/Wind Harmer
2.498
941731AE2-173 GEN
Solar/Wind Harmer
10.954
270102X2-052 ST
50/50
3.624
970901AG2-562 GEN
50/50
13.732
970245AG2-165 GEN
Solar/Wind Harmer
2.888
970349AG2-230 GEN
Solar/Wind Harmer
2.09
971347AH1-153 GEN
Solar/Wind Harmer
2.09
961051AF2-396 GEN
Solar/Wind Harmer
2.561
961051AF2-396 GEN
Solar/Wind Harmer
20.485
972231SS25-0005
Solar/Wind Harmer
2.005
274862TOP CROP ;2U
Solar/Wind Harmer
19.567
970921AG2-575 GEN
Solar/Wind Harmer
1.183
970921AG2-575 GEN
Solar/Wind Harmer
4.733
274879MINONK ;1U
Solar/Wind Harmer
27.571
971411AH1-196 GEN
Solar/Wind Harmer
1.752
274855GSG-6 ;RU
Solar/Wind Harmer
14.825
24386405FR-21G C
Solar/Wind Harmer
8.703
960971AF2-388 GEN
Solar/Wind Harmer
33.741
970513AG2-328 GEN
Solar/Wind Harmer
2.888
970517AG2-330 GEN
Solar/Wind Harmer
45.053
270063AE2-323 C
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
970833AG2-524 GEN
Solar/Wind Harmer
1.342
962781AG1-127 GEN
Solar/Wind Harmer
1.125
24697605MDL-3G C
Solar/Wind Harmer
14.701
270181AB1-006 GEN2
Solar/Wind Harmer
1.829
971335AH1-147 GEN
Solar/Wind Harmer
2.334
971171AH1-044 GEN
Solar/Wind Harmer
2.318
926823AC1-168 GEN
Solar/Wind Harmer
14.021
24385905FR-11G C
Solar/Wind Harmer
17.109
276782AC1-033 GEN
Solar/Wind Harmer
14.5
946321AF1-296 GEN
Solar/Wind Harmer
32.251
959611AF2-252 GEN
Solar/Wind Harmer
4.294
960611AF2-352 GEN
Solar/Wind Harmer
4.294
944231AF1-091 GEN
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0
270449AD2-020 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
28.423
943121AE2-341 GEN
Solar/Wind Harmer
1.821
957471AF2-041 GEN
Solar/Wind Harmer
3.477
274848CAMPGROVE;RU
Solar/Wind Harmer
20.056
959341AF2-225 GEN
Solar/Wind Harmer
1.643
965651AG1-433 GEN
Solar/Wind Harmer
16.87
970291AG2-192 GEN
Solar/Wind Harmer
0.133
970289AG2-191 GEN
Solar/Wind Harmer
1.352
971599AH1-298 GEN
50/50
21.036
970321AG2-212 GEN
Solar/Wind Harmer
2.888
970333AG2-219 GEN
Solar/Wind Harmer
4.372
270071AF1-092 GEN
Solar/Wind Harmer
1.926
276602WESTBROOK C
Solar/Wind Harmer
8.175
970611AG2-400 GEN
Solar/Wind Harmer
1.123
24387305FR-4G C
Solar/Wind Harmer
13.054
24386605FR-22G C
Solar/Wind Harmer
8.703
24387005FR-3G C
Solar/Wind Harmer
8.616
276645AC1-214 GEN1
Solar/Wind Harmer
4.778
942111AE2-223 GEN
Solar/Wind Harmer
25.633
944961AF1-161 GEN
50/50
6.392
970243AG2-164 GEN
Solar/Wind Harmer
3.577
971771AH1-392 GEN
Solar/Wind Harmer
1.176
270505AE1-170 C O1
Solar/Wind Harmer
1.938
270043AE2-236 GEN
Solar/Wind Harmer
0.71
274888KELLY CRK;1U
Solar/Wind Harmer
25.103
970941AG2-585 GEN
Solar/Wind Harmer
1.546
971605AH1-302 GEN
Solar/Wind Harmer
18.291
276805AD2-038 GEN
Solar/Wind Harmer
21.371
274850MENDOTA H;RU
Solar/Wind Harmer
10.5
276861AD2-134 GEN
Solar/Wind Harmer
7.166
274864CRW2-WTG
Solar/Wind Harmer
21.955
970569AG2-363 GEN
Solar/Wind Harmer
3.426
274858EASY ROAD;U2
Solar/Wind Harmer
17.754
276157O29GEN1
Solar/Wind Harmer
16.305
957751AF2-069 GEN
Solar/Wind Harmer
1.458
939741AE1-205 GEN
Solar/Wind Harmer
2.191
970241AG2-163 GEN
Solar/Wind Harmer
2.585
965011AG1-365 GEN
Solar/Wind Harmer
1.123
972175AH1-670 GEN
Solar/Wind Harmer
40.448
276174W4-005 GEN2
Solar/Wind Harmer
7.56
970239AG2-162 GEN
Solar/Wind Harmer
1.524
276893AG1-478 C
Solar/Wind Harmer
-0.001
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
3.56
24691005MDL-2G C
Solar/Wind Harmer
14.724
971997AH1-543 GEN
Solar/Wind Harmer
1.844
276863AD2-134 GEN
Solar/Wind Harmer
7.166
971549AH1-272 GEN
Solar/Wind Harmer
2.153
274863CRW1-WTG
Solar/Wind Harmer
21.955
276889AE2-281 GEN
Solar/Wind Harmer
7.407
274856ECOGROVE ;U1
Solar/Wind Harmer
13.423
965021AG1-366 GEN
Solar/Wind Harmer
4.491
276158O29GEN2
Solar/Wind Harmer
16.305
276708O09 GEN2
Solar/Wind Harmer
13.724
958861AF2-177 GEN
Solar/Wind Harmer
32.945
945371AF1-202 GEN
Solar/Wind Harmer
15.713
274880W4-005 GEN4
Solar/Wind Harmer
7.56
962601AG1-109 GEN
50/50
6.392
960681AF2-359 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
19.33
276691AA1-018 GEN1
Solar/Wind Harmer
1.287
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
30.87
971067AG2-660 GEN
Solar/Wind Harmer
4.636
276872AE1-163_GEN1
Solar/Wind Harmer
25.923
276741O09 GEN1
Solar/Wind Harmer
13.724
276655WTG1_EQ
Solar/Wind Harmer
18.863
963841AG1-237 GEN
Solar/Wind Harmer
33.488
965101AG1-375 GEN
Solar/Wind Harmer
1.056
276686W4-005 GEN3
Solar/Wind Harmer
7.56
970373AG2-245 GEN
Solar/Wind Harmer
2.675
964401AG1-302 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
23.557
274872LEEDK;1U
Solar/Wind Harmer
0.519
270180AB1-006 GEN1
Solar/Wind Harmer
27.585
24791305MDL-5G
Solar/Wind Harmer
9.707
959081AF2-199 GEN
Solar/Wind Harmer
1.159
971475AH1-234 GEN
Solar/Wind Harmer
2.562
24386205FR-12G C
Solar/Wind Harmer
9.086
276646AC1-214 GEN2
Solar/Wind Harmer
4.778
276726Z2-087_GEN
Solar/Wind Harmer
28.481
963741AG1-226 GEN
Solar/Wind Harmer
4.654
24697905MDL-4G C
Solar/Wind Harmer
9.707
971333AH1-146 GEN
Solar/Wind Harmer
2.334
970819AG2-516 GEN
Solar/Wind Harmer
1.377
274851PROVIDENC;RU
Solar/Wind Harmer
10.555
274878BISHOP HL;2U
Solar/Wind Harmer
12.834
965931AG1-462 GEN
Solar/Wind Harmer
2.743
965091AG1-374 GEN
Solar/Wind Harmer
3.22
970521AG2-332 GEN
50/50
25.509
276806AD2-047 C O1
Solar/Wind Harmer
38.087
958391AF2-133 GEN
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
21.75
971341AH1-150 GEN
Solar/Wind Harmer
2.318
247642Z2-115 C
Solar/Wind Harmer
-0.001
970291AG2-192 GEN
Solar/Wind Harmer
1.229
270471AD2-092_GEN
Solar/Wind Helper
0.687
963791AG1-232 GEN
Solar/Wind Harmer
1.357
276785W4-005 GEN1
Solar/Wind Harmer
7.56
944201AF1-088_MTX
Adder
148.128
957141AF2-008_MTX
Adder
74.064
CBM West 1LTFEXP_CBM-W1->PJM
CBM
232.762
LGEELTFEXP_LGEE->PJM
CLTF
4.567
TVALTFEXP_TVA->PJM
CLTF
5.095
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
52.01
CBM South 1LTFEXP_CBM-S1->PJM
CBM
20.173
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.261
LAGNLTFEXP_LAGN->PJM
CLTF
13.768
AH1-155LTFEXP_AH1-155->PJM
LTF
0.706
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.171
WECLTFEXP_WEC->PJM
CLTF
7.559
MECLTFEXP_MEC->PJM
CLTF
26.993
AG2-052LTFEXP_AG2-052->PJM
LTF
0.47
NYPJM->LTFIMP_NY
CLTF
3.326
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.568
SIGELTFEXP_SIGE->PJM
CLTF
0.513

Details for 05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7445_05MARYSV 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.24 %
Rating:2219.0 MVA
Rating Type:B
MVA to Mitigate:2290.85
MW Contribution:0.72
Bus #Bus NameTypeMW Contribution
960971AF2-388 GEN
Solar/Wind Harmer
16.226
970349AG2-230 GEN
Solar/Wind Harmer
0.722
971347AH1-153 GEN
Solar/Wind Harmer
0.722
961051AF2-396 GEN
Solar/Wind Harmer
0.958
961051AF2-396 GEN
Solar/Wind Harmer
7.664
270599AE1-208 GEN
Solar/Wind Harmer
0.368
970245AG2-165 GEN
Solar/Wind Harmer
0.887
972231SS25-0005
Solar/Wind Harmer
0.704
274862TOP CROP ;2U
Solar/Wind Harmer
6.808
24641605TWIN BRNCH
50/50
0.015
944531AF1-118 GEN
Solar/Wind Harmer
2.039
274887GEN-1.85
Solar/Wind Harmer
7.997
970707AG2-453 GEN
Solar/Wind Harmer
1.193
970833AG2-524 GEN
Solar/Wind Harmer
3.709
958481AF2-142 GEN
Solar/Wind Harmer
0.624
276868AE1-113 GEN
Solar/Wind Harmer
13.718
971675AH1-338 GEN
Solar/Wind Harmer
0.729
970781AG2-491 GEN
Solar/Wind Harmer
0.403
960791AF2-370 GEN
Solar/Wind Harmer
1.606
276903AD2-071 C
Solar/Wind Harmer
0.391
966841AG1-555 GEN
Solar/Wind Harmer
0
274853TWINGROVE;U1
Solar/Wind Harmer
9.31
270224U2-072_GEN2
Solar/Wind Helper
0.141
270391AF1-285 GEN3
Solar/Wind Helper
0.282
241847AF2-150_GEN
Solar/Wind Helper
0.259
970921AG2-575 GEN
Solar/Wind Harmer
0.41
970921AG2-575 GEN
Solar/Wind Harmer
1.639
274879MINONK ;1U
Solar/Wind Harmer
9.594
971411AH1-196 GEN
Solar/Wind Harmer
0.608
274855GSG-6 ;RU
Solar/Wind Harmer
5.144
24386405FR-21G C
Solar/Wind Harmer
3.024
942871AE2-306 GEN
Solar/Wind Helper
0.211
945641AF1-229 GEN
Solar/Wind Helper
0.446
270541AE2-072 C
Solar/Wind Helper
0.447
970583AG2-370 GEN
50/50
2.775
970031AG2-029 GEN
Solar/Wind Harmer
2.089
270247TR4_N_V136
Solar/Wind Harmer
1.16
965051AG1-369 GEN
Solar/Wind Harmer
0.295
960591AF2-350 GEN
Solar/Wind Harmer
0.429
958381AF2-132 GEN
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
8.024
939401AE1-172 GEN
Solar/Wind Harmer
16.293
276876AE1-163_GEN2
Solar/Wind Harmer
9.042
274857EASY ROAD;U1
Solar/Wind Harmer
6.189
961761AG1-017 GEN
Solar/Wind Harmer
0.383
276656WTG2_EQ
Solar/Wind Harmer
0.876
941731AE2-173 GEN
Solar/Wind Harmer
3.84
270462AD2-086
Solar/Wind Helper
1.767
270317AD1-130_GEN
Solar/Wind Helper
1.153
270287AF1-227 GEN3
Solar/Wind Helper
0.344
270063AE2-323 C
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0
970513AG2-328 GEN
Solar/Wind Harmer
0.887
970517AG2-330 GEN
Solar/Wind Harmer
13.834
959141AF2-205 GEN
Solar/Wind Harmer
0
970833AG2-524 GEN
Solar/Wind Harmer
0.464
962781AG1-127 GEN
Solar/Wind Harmer
0.39
958821AF2-173 GEN
Solar/Wind Harmer
0.573
971335AH1-147 GEN
Solar/Wind Harmer
0.81
24697605MDL-3G C
Solar/Wind Harmer
5.058
270181AB1-006 GEN2
Solar/Wind Harmer
0.629
971171AH1-044 GEN
Solar/Wind Harmer
0.805
926823AC1-168 GEN
Solar/Wind Harmer
4.888
24385905FR-11G C
Solar/Wind Harmer
5.945
276782AC1-033 GEN
Solar/Wind Harmer
5.076
24725505WLD G2 C
Solar/Wind Harmer
4.997
946321AF1-296 GEN
Solar/Wind Harmer
11.312
958581AF2-149 GEN
Solar/Wind Helper
0.216
960611AF2-352 GEN
Solar/Wind Harmer
1.01
24653605MOTTVILLE
50/50
0.003
965011AG1-365 GEN
Solar/Wind Harmer
1.14
945111AF1-176 GEN
Solar/Wind Harmer
0.877
945111AF1-176 GEN
Solar/Wind Harmer
4.78
957891AF2-083 GEN
Solar/Wind Harmer
0
971769AH1-391 GEN
Solar/Wind Harmer
0.467
964861AG1-349 GEN
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
43.563
940581AE2-045 GEN
Solar/Wind Harmer
0
971177AH1-047 GEN
Solar/Wind Harmer
0.239
970571AG2-364 GEN
Solar/Wind Harmer
0.798
970825AG2-519 GEN
Solar/Wind Harmer
0.442
970825AG2-519 GEN
Solar/Wind Harmer
1.697
971681AH1-341 GEN
Solar/Wind Harmer
0.594
938861AE1-114 GEN
Solar/Wind Harmer
9.271
276603SUBLETTE C
Solar/Wind Harmer
1.346
253378AE2-206_GEN
Solar/Wind Helper
0.334
971599AH1-298 GEN
50/50
10.28
960861AF2-377 GEN
50/50
2.361
24729305KEY G2
50/50
6.792
970611AG2-400 GEN
Solar/Wind Harmer
1.14
270071AF1-092 GEN
Solar/Wind Harmer
0.935
970321AG2-212 GEN
Solar/Wind Harmer
0.887
270005AE1-210 C O1
Solar/Wind Harmer
6.381
276602WESTBROOK C
Solar/Wind Harmer
2.837
276645AC1-214 GEN1
Solar/Wind Harmer
1.672
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
0.583
24387305FR-4G C
Solar/Wind Harmer
4.536
24386605FR-22G C
Solar/Wind Harmer
3.024
24387005FR-3G C
Solar/Wind Harmer
2.994
942111AE2-223 GEN
Solar/Wind Harmer
8.986
960841AF2-375 GEN
Solar/Wind Helper
0.553
960851AF2-376 GEN
50/50
2.066
965021AG1-366 GEN
Solar/Wind Harmer
4.56
958861AF2-177 GEN
Solar/Wind Harmer
15.756
945371AF1-202 GEN
Solar/Wind Harmer
7.43
276893AG1-478 C
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
1.232
270594AE1-207 GEN
Solar/Wind Harmer
0.652
270032AE2-172
Solar/Wind Harmer
3.259
971997AH1-543 GEN
Solar/Wind Harmer
0.64
276863AD2-134 GEN
Solar/Wind Harmer
2.487
274863CRW1-WTG
Solar/Wind Harmer
7.63
276889AE2-281 GEN
Solar/Wind Harmer
2.583
24691005MDL-2G C
Solar/Wind Harmer
5.066
274856ECOGROVE ;U1
Solar/Wind Harmer
4.672
971549AH1-272 GEN
Solar/Wind Harmer
0.724
276158O29GEN2
Solar/Wind Harmer
5.697
276708O09 GEN2
Solar/Wind Harmer
4.795
246937BC-WTG2
Solar/Wind Helper
5.531
270485AE1-090_GEN
Solar/Wind Helper
0.154
970615AG2-402 GEN
50/50
4.56
24729405KEY G3
50/50
6.792
24729505KEY G4
50/50
6.679
270043AE2-236 GEN
Solar/Wind Harmer
0.369
971771AH1-392 GEN
Solar/Wind Harmer
0.437
270505AE1-170 C O1
Solar/Wind Harmer
0.719
274888KELLY CRK;1U
Solar/Wind Harmer
8.705
970941AG2-585 GEN
Solar/Wind Harmer
0.536
971605AH1-302 GEN
Solar/Wind Harmer
6.289
276805AD2-038 GEN
Solar/Wind Harmer
7.442
274850MENDOTA H;RU
Solar/Wind Harmer
3.644
276861AD2-134 GEN
Solar/Wind Harmer
2.487
274864CRW2-WTG
Solar/Wind Harmer
7.63
970569AG2-363 GEN
Solar/Wind Harmer
1.196
274858EASY ROAD;U2
Solar/Wind Harmer
6.189
276157O29GEN1
Solar/Wind Harmer
5.697
957751AF2-069 GEN
Solar/Wind Harmer
0.51
939741AE1-205 GEN
Solar/Wind Harmer
0.768
246938BC-WTG3
Solar/Wind Helper
5.468
246936BC-WTG1
Solar/Wind Helper
5.531
24727005RPMNG1
50/50
68.465
247620Y3-023
50/50
0.46
965041AG1-368 GEN
Solar/Wind Harmer
0.694
270191TR4_S_V150
Solar/Wind Harmer
6.398
965101AG1-375 GEN
Solar/Wind Harmer
0.505
960681AF2-359 GEN
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
0.368
971917AH1-482 GEN
Solar/Wind Harmer
6.668
276691AA1-018 GEN1
Solar/Wind Harmer
0.448
276872AE1-163_GEN1
Solar/Wind Harmer
9.042
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
10.622
971067AG2-660 GEN
Solar/Wind Harmer
1.611
970115AG2-085 GEN
Solar/Wind Harmer
0.161
276741O09 GEN1
Solar/Wind Harmer
4.795
276655WTG1_EQ
Solar/Wind Harmer
6.613
270578AF1-285 GEN2
Solar/Wind Helper
0.282
247522W1-056 GEN
Solar/Wind Helper
1.885
270286AF1-227 GEN2
Solar/Wind Helper
0.344
961961AG1-039 GEN
Solar/Wind Helper
0.165
241960AC2-195 GEN
Solar/Wind Helper
0.289
959331AF2-224 GEN
Solar/Wind Harmer
1.14
944541AF1-119 GEN
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
5.037
276843GEN-1.7
Solar/Wind Harmer
0.708
941551AE2-152 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
11.858
276882AE2-255 GEN
Solar/Wind Harmer
4.328
960441AF2-335 GEN
Solar/Wind Harmer
0.402
270223U2-072_GEN1
Solar/Wind Helper
0.141
966831AG1-554 GEN
Solar/Wind Helper
0.276
274854TWINGROVE;U2
Solar/Wind Harmer
6.161
24729205KEY G1
50/50
6.679
270526AF1-158 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
0.927
964401AG1-302 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
8.196
270004AE1-209 GEN
Solar/Wind Harmer
6.381
274872LEEDK;1U
Solar/Wind Harmer
0.18
270180AB1-006 GEN1
Solar/Wind Harmer
9.491
24791305MDL-5G
Solar/Wind Harmer
3.34
959081AF2-199 GEN
Solar/Wind Harmer
0.403
971475AH1-234 GEN
Solar/Wind Harmer
0.892
276646AC1-214 GEN2
Solar/Wind Harmer
1.672
24386205FR-12G C
Solar/Wind Harmer
3.157
276726Z2-087_GEN
Solar/Wind Harmer
9.984
971617AH1-308 GEN
Solar/Wind Harmer
5.12
943021AE2-325 GEN
Solar/Wind Harmer
2.954
958011AF2-095 GEN
Solar/Wind Harmer
0.618
971573AH1-285 GEN
Solar/Wind Harmer
0.358
945421AF1-207 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
0.616
942991AE2-321 GEN
Solar/Wind Harmer
0.407
971333AH1-146 GEN
Solar/Wind Harmer
0.81
24697905MDL-4G C
Solar/Wind Harmer
3.34
970819AG2-516 GEN
Solar/Wind Harmer
0.479
274851PROVIDENC;RU
Solar/Wind Harmer
3.693
964611AG1-324 GEN
Solar/Wind Harmer
0.35
270201AC2-176 GEN
Solar/Wind Harmer
6.57
274878BISHOP HL;2U
Solar/Wind Harmer
4.493
24699105WLD G1 C
Solar/Wind Harmer
4.967
965931AG1-462 GEN
Solar/Wind Harmer
0.963
270499AE1-146 GEN
Solar/Wind Helper
0.534
970521AG2-332 GEN
50/50
10.75
247521TR3_G114
Solar/Wind Harmer
8.58
276806AD2-047 C O1
Solar/Wind Harmer
13.208
958391AF2-133 GEN
Solar/Wind Harmer
0
24727205RPMNG3
50/50
68.465
24639705ELKHART HY
50/50
0.149
963791AG1-232 GEN
Solar/Wind Harmer
0.959
270246TR4_N_V150
Solar/Wind Harmer
1.16
24695305TIMB G C
Solar/Wind Harmer
9.67
270024AE2-089 GEN
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
0.572
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
943591AF1-030 GEN
Solar/Wind Harmer
0.419
276901AD2-066 C O1
Solar/Wind Harmer
0
965031AG1-367 GEN
Solar/Wind Harmer
0.409
971343AH1-151 GEN
Solar/Wind Harmer
0.805
970169AG2-114 GEN
Solar/Wind Harmer
0.398
961011AF2-392 GEN
Solar/Wind Harmer
12.167
270227U2-072_GEN3
Solar/Wind Helper
0.141
270228U2-072_GEN4
Solar/Wind Helper
0.141
276820AF1-078_GEN
Solar/Wind Helper
0.151
972181SS23-001
Solar/Wind Harmer
0.44
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.3
970289AG2-191 GEN
Solar/Wind Harmer
0.078
24755605MDL-5G
Solar/Wind Harmer
3.34
959091AF2-200 GEN
Solar/Wind Harmer
0.805
946031AF1-268 GEN
Solar/Wind Harmer
0.324
274849CRESCENT ;1U
Solar/Wind Harmer
2.552
274877BISHOP HL;1U
Solar/Wind Harmer
4.493
270349AD2-093_GEN
Solar/Wind Helper
0.444
24727105RPMNG2
50/50
68.465
965651AG1-433 GEN
Solar/Wind Harmer
8.113
270449AD2-020 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
9.816
943121AE2-341 GEN
Solar/Wind Harmer
0.628
970291AG2-192 GEN
Solar/Wind Harmer
0.054
970289AG2-191 GEN
Solar/Wind Harmer
0.544
957471AF2-041 GEN
Solar/Wind Harmer
1.208
274848CAMPGROVE;RU
Solar/Wind Harmer
7.026
959341AF2-225 GEN
Solar/Wind Harmer
0.576
957201AF2-014 GEN
Solar/Wind Helper
3.936
270284AF1-227 GEN1
Solar/Wind Helper
0.932
270428AC2-015 C
Solar/Wind Helper
0.365
274847GR RIDGE ;BU
Solar/Wind Harmer
7.511
247642Z2-115 C
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.495
971341AH1-150 GEN
Solar/Wind Harmer
0.805
270302AB2-170 GEN
Solar/Wind Helper
1.153
270231U2-072_GEN5
Solar/Wind Helper
0.141
270471AD2-092_GEN
Solar/Wind Helper
0.444
957141AF2-008_MTX
Adder
27.929
944201AF1-088_MTX
Adder
55.858
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.085
TVALTFEXP_TVA->PJM
CLTF
2.406
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
23.398
CBM West 2LTFEXP_CBM-W2->PJM
CBM
51.626
LGEELTFEXP_LGEE->PJM
CLTF
1.821
LAGNLTFEXP_LAGN->PJM
CLTF
5.9
AH1-155LTFEXP_AH1-155->PJM
LTF
0.248
CBM West 1LTFEXP_CBM-W1->PJM
CBM
72.501
NYPJM->LTFIMP_NY
CLTF
1.242
MECLTFEXP_MEC->PJM
CLTF
9.671
AG2-052LTFEXP_AG2-052->PJM
LTF
0.166
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.201
WECLTFEXP_WEC->PJM
CLTF
2.632
SIGELTFEXP_SIGE->PJM
CLTF
0.2

Details for AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7445_05MARYSV 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.42 %
Rating:2219.0 MVA
Rating Type:B
MVA to Mitigate:2339.21
MW Contribution:0.72
Bus #Bus NameTypeMW Contribution
965421AG1-410 GEN
Solar/Wind Harmer
6.773
972181SS23-001
Solar/Wind Harmer
0.44
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.3
970289AG2-191 GEN
Solar/Wind Harmer
0.078
24755605MDL-5G
Solar/Wind Harmer
3.34
959091AF2-200 GEN
Solar/Wind Harmer
0.805
946031AF1-268 GEN
Solar/Wind Harmer
0.324
274849CRESCENT ;1U
Solar/Wind Harmer
2.552
960971AF2-388 GEN
Solar/Wind Harmer
16.226
970349AG2-230 GEN
Solar/Wind Harmer
0.722
971347AH1-153 GEN
Solar/Wind Harmer
0.722
961051AF2-396 GEN
Solar/Wind Harmer
0.958
961051AF2-396 GEN
Solar/Wind Harmer
7.664
270599AE1-208 GEN
Solar/Wind Harmer
0.368
970245AG2-165 GEN
Solar/Wind Harmer
0.887
972231SS25-0005
Solar/Wind Harmer
0.704
274862TOP CROP ;2U
Solar/Wind Harmer
6.808
970921AG2-575 GEN
Solar/Wind Harmer
0.41
970921AG2-575 GEN
Solar/Wind Harmer
1.639
274879MINONK ;1U
Solar/Wind Harmer
9.594
971411AH1-196 GEN
Solar/Wind Harmer
0.608
274855GSG-6 ;RU
Solar/Wind Harmer
5.144
24386405FR-21G C
Solar/Wind Harmer
3.024
942871AE2-306 GEN
Solar/Wind Helper
0.211
945641AF1-229 GEN
Solar/Wind Helper
0.446
270541AE2-072 C
Solar/Wind Helper
0.447
270063AE2-323 C
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0
970513AG2-328 GEN
Solar/Wind Harmer
0.887
970517AG2-330 GEN
Solar/Wind Harmer
13.834
959141AF2-205 GEN
Solar/Wind Harmer
0
970833AG2-524 GEN
Solar/Wind Harmer
0.464
962781AG1-127 GEN
Solar/Wind Harmer
0.39
958821AF2-173 GEN
Solar/Wind Harmer
0.573
971335AH1-147 GEN
Solar/Wind Harmer
0.81
24697605MDL-3G C
Solar/Wind Harmer
5.058
270181AB1-006 GEN2
Solar/Wind Harmer
0.629
971171AH1-044 GEN
Solar/Wind Harmer
0.805
926823AC1-168 GEN
Solar/Wind Harmer
4.888
24385905FR-11G C
Solar/Wind Harmer
5.945
276782AC1-033 GEN
Solar/Wind Harmer
5.076
24725505WLD G2 C
Solar/Wind Harmer
4.997
946321AF1-296 GEN
Solar/Wind Harmer
11.312
958581AF2-149 GEN
Solar/Wind Helper
0.216
960611AF2-352 GEN
Solar/Wind Harmer
0.85
944531AF1-118 GEN
Solar/Wind Harmer
2.039
274887GEN-1.85
Solar/Wind Harmer
7.997
970707AG2-453 GEN
Solar/Wind Harmer
1.193
970833AG2-524 GEN
Solar/Wind Harmer
3.709
958481AF2-142 GEN
Solar/Wind Harmer
0.624
276868AE1-113 GEN
Solar/Wind Harmer
13.718
971675AH1-338 GEN
Solar/Wind Harmer
0.729
970781AG2-491 GEN
Solar/Wind Harmer
0.403
960791AF2-370 GEN
Solar/Wind Harmer
1.606
276903AD2-071 C
Solar/Wind Harmer
0.391
966841AG1-555 GEN
Solar/Wind Harmer
0
274853TWINGROVE;U1
Solar/Wind Harmer
9.31
270224U2-072_GEN2
Solar/Wind Helper
0.141
270391AF1-285 GEN3
Solar/Wind Helper
0.282
241847AF2-150_GEN
Solar/Wind Helper
0.259
970583AG2-370 GEN
50/50
2.775
970031AG2-029 GEN
Solar/Wind Harmer
2.089
270247TR4_N_V136
Solar/Wind Harmer
1.16
965051AG1-369 GEN
Solar/Wind Harmer
0.295
960591AF2-350 GEN
Solar/Wind Harmer
0.429
958381AF2-132 GEN
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
8.024
939401AE1-172 GEN
Solar/Wind Harmer
16.293
276876AE1-163_GEN2
Solar/Wind Harmer
9.042
274857EASY ROAD;U1
Solar/Wind Harmer
6.189
961761AG1-017 GEN
Solar/Wind Harmer
0.383
276656WTG2_EQ
Solar/Wind Harmer
0.876
941731AE2-173 GEN
Solar/Wind Harmer
3.84
270462AD2-086
Solar/Wind Helper
1.767
270317AD1-130_GEN
Solar/Wind Helper
1.153
270287AF1-227 GEN3
Solar/Wind Helper
0.344
970615AG2-402 GEN
50/50
4.56
24729405KEY G3
50/50
6.792
24729505KEY G4
50/50
6.679
270043AE2-236 GEN
Solar/Wind Harmer
0.369
971771AH1-392 GEN
Solar/Wind Harmer
0.437
270505AE1-170 C O1
Solar/Wind Harmer
0.719
24653605MOTTVILLE
50/50
0.003
965011AG1-365 GEN
Solar/Wind Harmer
1.14
945111AF1-176 GEN
Solar/Wind Harmer
0.877
945111AF1-176 GEN
Solar/Wind Harmer
4.78
957891AF2-083 GEN
Solar/Wind Harmer
0
971769AH1-391 GEN
Solar/Wind Harmer
0.467
964861AG1-349 GEN
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
43.563
940581AE2-045 GEN
Solar/Wind Harmer
0
971177AH1-047 GEN
Solar/Wind Harmer
0.239
970571AG2-364 GEN
Solar/Wind Harmer
0.798
970825AG2-519 GEN
Solar/Wind Harmer
0.442
970825AG2-519 GEN
Solar/Wind Harmer
1.697
971681AH1-341 GEN
Solar/Wind Harmer
0.594
938861AE1-114 GEN
Solar/Wind Harmer
9.271
276603SUBLETTE C
Solar/Wind Harmer
1.346
253378AE2-206_GEN
Solar/Wind Helper
0.334
965021AG1-366 GEN
Solar/Wind Harmer
4.56
958861AF2-177 GEN
Solar/Wind Harmer
15.756
945371AF1-202 GEN
Solar/Wind Harmer
7.43
276893AG1-478 C
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
1.232
270594AE1-207 GEN
Solar/Wind Harmer
0.652
270032AE2-172
Solar/Wind Harmer
3.259
971997AH1-543 GEN
Solar/Wind Harmer
0.64
276863AD2-134 GEN
Solar/Wind Harmer
2.487
274863CRW1-WTG
Solar/Wind Harmer
7.63
276889AE2-281 GEN
Solar/Wind Harmer
2.583
24691005MDL-2G C
Solar/Wind Harmer
5.066
274856ECOGROVE ;U1
Solar/Wind Harmer
4.672
971599AH1-298 GEN
50/50
10.28
960861AF2-377 GEN
50/50
2.361
24729305KEY G2
50/50
6.792
970611AG2-400 GEN
Solar/Wind Harmer
1.14
270071AF1-092 GEN
Solar/Wind Harmer
0.935
970321AG2-212 GEN
Solar/Wind Harmer
0.887
270005AE1-210 C O1
Solar/Wind Harmer
6.381
276602WESTBROOK C
Solar/Wind Harmer
2.837
276645AC1-214 GEN1
Solar/Wind Harmer
1.672
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
0.583
24387305FR-4G C
Solar/Wind Harmer
4.536
24386605FR-22G C
Solar/Wind Harmer
3.024
24387005FR-3G C
Solar/Wind Harmer
2.994
942111AE2-223 GEN
Solar/Wind Harmer
8.986
960841AF2-375 GEN
Solar/Wind Helper
0.553
971549AH1-272 GEN
Solar/Wind Harmer
0.724
276158O29GEN2
Solar/Wind Harmer
5.697
276708O09 GEN2
Solar/Wind Harmer
4.795
246937BC-WTG2
Solar/Wind Helper
5.531
270485AE1-090_GEN
Solar/Wind Helper
0.154
274888KELLY CRK;1U
Solar/Wind Harmer
8.705
970941AG2-585 GEN
Solar/Wind Harmer
0.536
971605AH1-302 GEN
Solar/Wind Harmer
6.289
276805AD2-038 GEN
Solar/Wind Harmer
7.442
274850MENDOTA H;RU
Solar/Wind Harmer
3.644
276861AD2-134 GEN
Solar/Wind Harmer
2.487
274864CRW2-WTG
Solar/Wind Harmer
7.63
970569AG2-363 GEN
Solar/Wind Harmer
1.196
274858EASY ROAD;U2
Solar/Wind Harmer
6.189
276157O29GEN1
Solar/Wind Harmer
5.697
957751AF2-069 GEN
Solar/Wind Harmer
0.51
939741AE1-205 GEN
Solar/Wind Harmer
0.768
246938BC-WTG3
Solar/Wind Helper
5.468
246936BC-WTG1
Solar/Wind Helper
5.531
24727005RPMNG1
50/50
68.465
247620Y3-023
50/50
0.46
965041AG1-368 GEN
Solar/Wind Harmer
0.694
270191TR4_S_V150
Solar/Wind Harmer
6.398
965101AG1-375 GEN
Solar/Wind Harmer
0.505
960681AF2-359 GEN
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
0.368
971917AH1-482 GEN
Solar/Wind Harmer
6.668
276691AA1-018 GEN1
Solar/Wind Harmer
0.448
276872AE1-163_GEN1
Solar/Wind Harmer
9.042
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
10.622
971067AG2-660 GEN
Solar/Wind Harmer
1.611
970115AG2-085 GEN
Solar/Wind Harmer
0.161
276741O09 GEN1
Solar/Wind Harmer
4.795
276655WTG1_EQ
Solar/Wind Harmer
6.613
270578AF1-285 GEN2
Solar/Wind Helper
0.282
247522W1-056 GEN
Solar/Wind Helper
1.885
270286AF1-227 GEN2
Solar/Wind Helper
0.344
961961AG1-039 GEN
Solar/Wind Helper
0.165
241960AC2-195 GEN
Solar/Wind Helper
0.289
959331AF2-224 GEN
Solar/Wind Harmer
1.14
944541AF1-119 GEN
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
5.037
276843GEN-1.7
Solar/Wind Harmer
0.708
941551AE2-152 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
11.858
276882AE2-255 GEN
Solar/Wind Harmer
4.328
960441AF2-335 GEN
Solar/Wind Harmer
0.402
270223U2-072_GEN1
Solar/Wind Helper
0.141
966831AG1-554 GEN
Solar/Wind Helper
0.276
274854TWINGROVE;U2
Solar/Wind Harmer
5.188
24729205KEY G1
50/50
6.679
270526AF1-158 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
0.927
964401AG1-302 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
8.196
270004AE1-209 GEN
Solar/Wind Harmer
6.381
274872LEEDK;1U
Solar/Wind Harmer
0.18
270180AB1-006 GEN1
Solar/Wind Harmer
9.491
24791305MDL-5G
Solar/Wind Harmer
3.34
959081AF2-199 GEN
Solar/Wind Harmer
0.403
971475AH1-234 GEN
Solar/Wind Harmer
0.892
276646AC1-214 GEN2
Solar/Wind Harmer
1.672
24386205FR-12G C
Solar/Wind Harmer
3.157
276726Z2-087_GEN
Solar/Wind Harmer
9.984
971617AH1-308 GEN
Solar/Wind Harmer
5.12
943021AE2-325 GEN
Solar/Wind Harmer
2.954
958011AF2-095 GEN
Solar/Wind Harmer
0.618
971573AH1-285 GEN
Solar/Wind Harmer
0.358
945421AF1-207 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
0.616
942991AE2-321 GEN
Solar/Wind Harmer
0.407
971333AH1-146 GEN
Solar/Wind Harmer
0.81
24697905MDL-4G C
Solar/Wind Harmer
3.34
970819AG2-516 GEN
Solar/Wind Harmer
0.479
274851PROVIDENC;RU
Solar/Wind Harmer
3.693
964611AG1-324 GEN
Solar/Wind Harmer
0.35
270201AC2-176 GEN
Solar/Wind Harmer
6.57
274878BISHOP HL;2U
Solar/Wind Harmer
4.493
24699105WLD G1 C
Solar/Wind Harmer
4.967
965931AG1-462 GEN
Solar/Wind Harmer
0.963
270499AE1-146 GEN
Solar/Wind Helper
0.534
970521AG2-332 GEN
50/50
10.75
247521TR3_G114
Solar/Wind Harmer
8.58
276806AD2-047 C O1
Solar/Wind Harmer
13.208
958391AF2-133 GEN
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
7.511
247642Z2-115 C
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.495
971341AH1-150 GEN
Solar/Wind Harmer
0.805
270302AB2-170 GEN
Solar/Wind Helper
1.153
270231U2-072_GEN5
Solar/Wind Helper
0.141
270471AD2-092_GEN
Solar/Wind Helper
0.444
965431AG1-411 GEN
50/50
45.157
24727205RPMNG3
50/50
68.465
24639705ELKHART HY
50/50
0.149
963791AG1-232 GEN
Solar/Wind Harmer
0.959
270246TR4_N_V150
Solar/Wind Harmer
1.16
24695305TIMB G C
Solar/Wind Harmer
9.67
270024AE2-089 GEN
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
0.572
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
943591AF1-030 GEN
Solar/Wind Harmer
0.419
276901AD2-066 C O1
Solar/Wind Harmer
0
965031AG1-367 GEN
Solar/Wind Harmer
0.409
971343AH1-151 GEN
Solar/Wind Harmer
0.805
970169AG2-114 GEN
Solar/Wind Harmer
0.398
961011AF2-392 GEN
Solar/Wind Harmer
12.167
270227U2-072_GEN3
Solar/Wind Helper
0.141
270228U2-072_GEN4
Solar/Wind Helper
0.141
276820AF1-078_GEN
Solar/Wind Helper
0.151
274877BISHOP HL;1U
Solar/Wind Harmer
4.493
270349AD2-093_GEN
Solar/Wind Helper
0.444
24727105RPMNG2
50/50
68.465
965651AG1-433 GEN
Solar/Wind Harmer
8.113
270449AD2-020 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
9.816
943121AE2-341 GEN
Solar/Wind Harmer
0.628
970291AG2-192 GEN
Solar/Wind Harmer
0.054
970289AG2-191 GEN
Solar/Wind Harmer
0.544
957471AF2-041 GEN
Solar/Wind Harmer
1.208
274848CAMPGROVE;RU
Solar/Wind Harmer
7.026
959341AF2-225 GEN
Solar/Wind Harmer
0.576
957201AF2-014 GEN
Solar/Wind Helper
3.936
270284AF1-227 GEN1
Solar/Wind Helper
0.932
270428AC2-015 C
Solar/Wind Helper
0.365
957141AF2-008_MTX
Adder
27.929
944201AF1-088_MTX
Adder
55.858
CBM West 1LTFEXP_CBM-W1->PJM
CBM
72.501
NYPJM->LTFIMP_NY
CLTF
1.242
MECLTFEXP_MEC->PJM
CLTF
9.671
AG2-052LTFEXP_AG2-052->PJM
LTF
0.166
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.201
WECLTFEXP_WEC->PJM
CLTF
2.632
SIGELTFEXP_SIGE->PJM
CLTF
0.2
CBM West 2LTFEXP_CBM-W2->PJM
CBM
51.626
LGEELTFEXP_LGEE->PJM
CLTF
1.821
LAGNLTFEXP_LAGN->PJM
CLTF
5.9
AH1-155LTFEXP_AH1-155->PJM
LTF
0.248
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.085
TVALTFEXP_TVA->PJM
CLTF
2.406
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
23.398

Details for AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7441_05SORENS 765_J1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7441_05SORENS 765_J1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.19 %
Rating:2219.0 MVA
Rating Type:B
MVA to Mitigate:2267.59
MW Contribution:0.74
Bus #Bus NameTypeMW Contribution
944531AF1-118 GEN
Solar/Wind Harmer
2.062
274887GEN-1.85
Solar/Wind Harmer
8.065
970707AG2-453 GEN
Solar/Wind Harmer
1.203
970833AG2-524 GEN
Solar/Wind Harmer
3.74
958481AF2-142 GEN
Solar/Wind Harmer
0.629
276868AE1-113 GEN
Solar/Wind Harmer
13.822
971675AH1-338 GEN
Solar/Wind Harmer
0.735
960791AF2-370 GEN
Solar/Wind Harmer
1.628
970781AG2-491 GEN
Solar/Wind Harmer
0.406
276903AD2-071 C
Solar/Wind Harmer
0.395
966841AG1-555 GEN
Solar/Wind Harmer
0
274853TWINGROVE;U1
Solar/Wind Harmer
9.371
270224U2-072_GEN2
Solar/Wind Helper
0.133
270391AF1-285 GEN3
Solar/Wind Helper
0.267
241847AF2-150_GEN
Solar/Wind Helper
0.239
960971AF2-388 GEN
Solar/Wind Harmer
16.413
970349AG2-230 GEN
Solar/Wind Harmer
0.729
971347AH1-153 GEN
Solar/Wind Harmer
0.729
961051AF2-396 GEN
Solar/Wind Harmer
0.97
961051AF2-396 GEN
Solar/Wind Harmer
7.761
270599AE1-208 GEN
Solar/Wind Harmer
0.373
970245AG2-165 GEN
Solar/Wind Harmer
0.894
972231SS25-0005
Solar/Wind Harmer
0.71
274862TOP CROP ;2U
Solar/Wind Harmer
6.862
970921AG2-575 GEN
Solar/Wind Harmer
0.413
970921AG2-575 GEN
Solar/Wind Harmer
1.652
274879MINONK ;1U
Solar/Wind Harmer
9.667
971411AH1-196 GEN
Solar/Wind Harmer
0.613
274855GSG-6 ;RU
Solar/Wind Harmer
5.182
24386405FR-21G C
Solar/Wind Harmer
3.045
942871AE2-306 GEN
Solar/Wind Helper
0.2
945641AF1-229 GEN
Solar/Wind Helper
0.422
270541AE2-072 C
Solar/Wind Helper
0.42
970583AG2-370 GEN
50/50
2.823
970031AG2-029 GEN
Solar/Wind Harmer
2.112
270247TR4_N_V136
Solar/Wind Harmer
1.186
965051AG1-369 GEN
Solar/Wind Harmer
0.301
960591AF2-350 GEN
Solar/Wind Harmer
0.432
958381AF2-132 GEN
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
8.088
939401AE1-172 GEN
Solar/Wind Harmer
16.42
276876AE1-163_GEN2
Solar/Wind Harmer
9.109
274857EASY ROAD;U1
Solar/Wind Harmer
6.231
961761AG1-017 GEN
Solar/Wind Harmer
0.391
276656WTG2_EQ
Solar/Wind Harmer
0.882
941731AE2-173 GEN
Solar/Wind Harmer
3.866
270462AD2-086
Solar/Wind Helper
1.688
270317AD1-130_GEN
Solar/Wind Helper
1.101
270287AF1-227 GEN3
Solar/Wind Helper
0.313
270063AE2-323 C
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0
970513AG2-328 GEN
Solar/Wind Harmer
0.894
970517AG2-330 GEN
Solar/Wind Harmer
13.95
959141AF2-205 GEN
Solar/Wind Harmer
0
970833AG2-524 GEN
Solar/Wind Harmer
0.467
958821AF2-173 GEN
Solar/Wind Harmer
0.58
962781AG1-127 GEN
Solar/Wind Harmer
0.393
971335AH1-147 GEN
Solar/Wind Harmer
0.816
24697605MDL-3G C
Solar/Wind Harmer
5.096
270181AB1-006 GEN2
Solar/Wind Harmer
0.634
971171AH1-044 GEN
Solar/Wind Harmer
0.811
926823AC1-168 GEN
Solar/Wind Harmer
4.923
24385905FR-11G C
Solar/Wind Harmer
5.987
276782AC1-033 GEN
Solar/Wind Harmer
5.11
24725505WLD G2 C
Solar/Wind Harmer
5.056
946321AF1-296 GEN
Solar/Wind Harmer
11.381
960611AF2-352 GEN
Solar/Wind Harmer
0.992
965011AG1-365 GEN
Solar/Wind Harmer
1.15
945111AF1-176 GEN
Solar/Wind Harmer
0.888
945111AF1-176 GEN
Solar/Wind Harmer
4.84
957891AF2-083 GEN
Solar/Wind Harmer
0
971769AH1-391 GEN
Solar/Wind Harmer
0.472
964861AG1-349 GEN
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
43.926
940581AE2-045 GEN
Solar/Wind Harmer
0
971177AH1-047 GEN
Solar/Wind Harmer
0.24
970825AG2-519 GEN
Solar/Wind Harmer
0.448
970825AG2-519 GEN
Solar/Wind Harmer
1.72
970571AG2-364 GEN
Solar/Wind Harmer
0.803
971681AH1-341 GEN
Solar/Wind Harmer
0.599
938861AE1-114 GEN
Solar/Wind Harmer
9.335
276603SUBLETTE C
Solar/Wind Harmer
1.356
253378AE2-206_GEN
Solar/Wind Helper
0.312
971599AH1-298 GEN
50/50
10.386
960861AF2-377 GEN
50/50
2.413
24729305KEY G2
50/50
6.868
970611AG2-400 GEN
Solar/Wind Harmer
1.15
270071AF1-092 GEN
Solar/Wind Harmer
0.944
970321AG2-212 GEN
Solar/Wind Harmer
0.894
270005AE1-210 C O1
Solar/Wind Harmer
6.463
276602WESTBROOK C
Solar/Wind Harmer
2.858
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
0.594
276645AC1-214 GEN1
Solar/Wind Harmer
1.683
24387305FR-4G C
Solar/Wind Harmer
4.568
24386605FR-22G C
Solar/Wind Harmer
3.045
24387005FR-3G C
Solar/Wind Harmer
3.015
942111AE2-223 GEN
Solar/Wind Harmer
9.047
960841AF2-375 GEN
Solar/Wind Helper
0.529
965021AG1-366 GEN
Solar/Wind Harmer
4.602
958861AF2-177 GEN
Solar/Wind Harmer
15.941
945371AF1-202 GEN
Solar/Wind Harmer
7.519
276893AG1-478 C
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
1.242
270594AE1-207 GEN
Solar/Wind Harmer
0.66
270032AE2-172
Solar/Wind Harmer
3.298
971997AH1-543 GEN
Solar/Wind Harmer
0.645
276863AD2-134 GEN
Solar/Wind Harmer
2.505
274863CRW1-WTG
Solar/Wind Harmer
7.688
276889AE2-281 GEN
Solar/Wind Harmer
2.603
24691005MDL-2G C
Solar/Wind Harmer
5.104
274856ECOGROVE ;U1
Solar/Wind Harmer
4.705
971549AH1-272 GEN
Solar/Wind Harmer
0.738
276158O29GEN2
Solar/Wind Harmer
5.735
276708O09 GEN2
Solar/Wind Harmer
4.827
246937BC-WTG2
Solar/Wind Helper
5.496
270485AE1-090_GEN
Solar/Wind Helper
0.147
970615AG2-402 GEN
50/50
4.602
24729405KEY G3
50/50
6.868
24729505KEY G4
50/50
6.754
270043AE2-236 GEN
Solar/Wind Harmer
0.373
971771AH1-392 GEN
Solar/Wind Harmer
0.442
270505AE1-170 C O1
Solar/Wind Harmer
0.728
274888KELLY CRK;1U
Solar/Wind Harmer
8.779
970941AG2-585 GEN
Solar/Wind Harmer
0.541
971605AH1-302 GEN
Solar/Wind Harmer
6.341
276805AD2-038 GEN
Solar/Wind Harmer
7.5
274850MENDOTA H;RU
Solar/Wind Harmer
3.67
276861AD2-134 GEN
Solar/Wind Harmer
2.505
274864CRW2-WTG
Solar/Wind Harmer
7.688
970569AG2-363 GEN
Solar/Wind Harmer
1.205
274858EASY ROAD;U2
Solar/Wind Harmer
6.231
276157O29GEN1
Solar/Wind Harmer
5.735
957751AF2-069 GEN
Solar/Wind Harmer
0.514
939741AE1-205 GEN
Solar/Wind Harmer
0.773
246938BC-WTG3
Solar/Wind Helper
5.433
246936BC-WTG1
Solar/Wind Helper
5.496
959331AF2-224 GEN
Solar/Wind Harmer
1.15
944541AF1-119 GEN
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
5.09
276843GEN-1.7
Solar/Wind Harmer
0.714
941551AE2-152 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
11.948
276882AE2-255 GEN
Solar/Wind Harmer
4.361
960441AF2-335 GEN
Solar/Wind Harmer
0.407
270223U2-072_GEN1
Solar/Wind Helper
0.133
966831AG1-554 GEN
Solar/Wind Helper
0.265
274854TWINGROVE;U2
Solar/Wind Harmer
6.054
24729205KEY G1
50/50
6.754
270526AF1-158 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
0.936
964401AG1-302 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
8.261
270004AE1-209 GEN
Solar/Wind Harmer
6.463
274872LEEDK;1U
Solar/Wind Harmer
0.181
270180AB1-006 GEN1
Solar/Wind Harmer
9.562
24791305MDL-5G
Solar/Wind Harmer
3.365
959081AF2-199 GEN
Solar/Wind Harmer
0.406
971475AH1-234 GEN
Solar/Wind Harmer
0.898
276646AC1-214 GEN2
Solar/Wind Harmer
1.683
24386205FR-12G C
Solar/Wind Harmer
3.179
276726Z2-087_GEN
Solar/Wind Harmer
10.052
971617AH1-308 GEN
Solar/Wind Harmer
5.201
943021AE2-325 GEN
Solar/Wind Harmer
2.992
958011AF2-095 GEN
Solar/Wind Harmer
0.623
971573AH1-285 GEN
Solar/Wind Harmer
0.361
945421AF1-207 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
0.621
942991AE2-321 GEN
Solar/Wind Harmer
0.41
971333AH1-146 GEN
Solar/Wind Harmer
0.816
24697905MDL-4G C
Solar/Wind Harmer
3.365
970819AG2-516 GEN
Solar/Wind Harmer
0.483
964611AG1-324 GEN
Solar/Wind Harmer
0.357
270201AC2-176 GEN
Solar/Wind Harmer
6.697
274851PROVIDENC;RU
Solar/Wind Harmer
3.718
274878BISHOP HL;2U
Solar/Wind Harmer
4.523
24699105WLD G1 C
Solar/Wind Harmer
5.025
270499AE1-146 GEN
Solar/Wind Helper
0.511
24727005RPMNG1
50/50
68.971
247620Y3-023
50/50
0.466
965041AG1-368 GEN
Solar/Wind Harmer
0.706
270191TR4_S_V150
Solar/Wind Harmer
6.54
965101AG1-375 GEN
Solar/Wind Harmer
0.511
960681AF2-359 GEN
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
0.373
971917AH1-482 GEN
Solar/Wind Harmer
6.726
276691AA1-018 GEN1
Solar/Wind Harmer
0.451
970115AG2-085 GEN
Solar/Wind Harmer
0.163
276872AE1-163_GEN1
Solar/Wind Harmer
9.109
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
10.701
971067AG2-660 GEN
Solar/Wind Harmer
1.622
276741O09 GEN1
Solar/Wind Harmer
4.827
276655WTG1_EQ
Solar/Wind Harmer
6.657
270578AF1-285 GEN2
Solar/Wind Helper
0.267
247522W1-056 GEN
Solar/Wind Helper
1.806
270286AF1-227 GEN2
Solar/Wind Helper
0.313
961961AG1-039 GEN
Solar/Wind Helper
0.152
241960AC2-195 GEN
Solar/Wind Helper
0.26
965431AG1-411 GEN
50/50
45.479
24727205RPMNG3
50/50
68.971
24639705ELKHART HY
50/50
0.15
963791AG1-232 GEN
Solar/Wind Harmer
0.972
270246TR4_N_V150
Solar/Wind Harmer
1.186
24695305TIMB G C
Solar/Wind Harmer
9.919
270024AE2-089 GEN
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
0.578
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
943591AF1-030 GEN
Solar/Wind Harmer
0.422
965031AG1-367 GEN
Solar/Wind Harmer
0.414
276901AD2-066 C O1
Solar/Wind Harmer
0
971343AH1-151 GEN
Solar/Wind Harmer
0.811
970169AG2-114 GEN
Solar/Wind Harmer
0.401
961011AF2-392 GEN
Solar/Wind Harmer
12.249
270227U2-072_GEN3
Solar/Wind Helper
0.133
270228U2-072_GEN4
Solar/Wind Helper
0.133
276820AF1-078_GEN
Solar/Wind Helper
0.141
965421AG1-410 GEN
Solar/Wind Harmer
6.822
972181SS23-001
Solar/Wind Harmer
0.444
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.311
970289AG2-191 GEN
Solar/Wind Harmer
0.079
24755605MDL-5G
Solar/Wind Harmer
3.365
959091AF2-200 GEN
Solar/Wind Harmer
0.811
946031AF1-268 GEN
Solar/Wind Harmer
0.329
274849CRESCENT ;1U
Solar/Wind Harmer
2.569
274877BISHOP HL;1U
Solar/Wind Harmer
4.523
270349AD2-093_GEN
Solar/Wind Helper
0.383
24727105RPMNG2
50/50
68.971
965651AG1-433 GEN
Solar/Wind Harmer
8.207
270449AD2-020 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
9.896
943121AE2-341 GEN
Solar/Wind Harmer
0.633
970291AG2-192 GEN
Solar/Wind Harmer
0.054
970289AG2-191 GEN
Solar/Wind Harmer
0.55
957471AF2-041 GEN
Solar/Wind Harmer
1.217
274848CAMPGROVE;RU
Solar/Wind Harmer
7.073
959341AF2-225 GEN
Solar/Wind Harmer
0.58
957201AF2-014 GEN
Solar/Wind Helper
3.911
270284AF1-227 GEN1
Solar/Wind Helper
0.847
270428AC2-015 C
Solar/Wind Helper
0.344
970521AG2-332 GEN
50/50
10.877
247521TR3_G114
Solar/Wind Harmer
8.771
276806AD2-047 C O1
Solar/Wind Harmer
13.32
958391AF2-133 GEN
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
7.573
247642Z2-115 C
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.5
971341AH1-150 GEN
Solar/Wind Harmer
0.811
270302AB2-170 GEN
Solar/Wind Helper
1.101
270231U2-072_GEN5
Solar/Wind Helper
0.133
270471AD2-092_GEN
Solar/Wind Helper
0.383
957141AF2-008_MTX
Adder
27.935
944201AF1-088_MTX
Adder
55.87
990497J1323
External Queue
0
CBM West 1LTFEXP_CBM-W1->PJM
CBM
73.505
NYPJM->LTFIMP_NY
CLTF
1.226
TVALTFEXP_TVA->PJM
CLTF
2.31
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
23.037
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.901
WECLTFEXP_WEC->PJM
CLTF
2.651
LAGNLTFEXP_LAGN->PJM
CLTF
5.747
AH1-155LTFEXP_AH1-155->PJM
LTF
0.251
CBM West 2LTFEXP_CBM-W2->PJM
CBM
51.154
LGEELTFEXP_LGEE->PJM
CLTF
1.819
MECLTFEXP_MEC->PJM
CLTF
9.7
AG2-052LTFEXP_AG2-052->PJM
LTF
0.167
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.599
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.014
SIGELTFEXP_SIGE->PJM
CLTF
0.2

Details for AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.19 %
Rating:2219.0 MVA
Rating Type:B
MVA to Mitigate:2267.56
MW Contribution:0.74
Bus #Bus NameTypeMW Contribution
965431AG1-411 GEN
50/50
45.479
24727205RPMNG3
50/50
68.971
24639705ELKHART HY
50/50
0.15
963791AG1-232 GEN
Solar/Wind Harmer
0.972
270246TR4_N_V150
Solar/Wind Harmer
1.186
24695305TIMB G C
Solar/Wind Harmer
9.919
270024AE2-089 GEN
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
0.578
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
943591AF1-030 GEN
Solar/Wind Harmer
0.422
965031AG1-367 GEN
Solar/Wind Harmer
0.414
276901AD2-066 C O1
Solar/Wind Harmer
0
971343AH1-151 GEN
Solar/Wind Harmer
0.811
970169AG2-114 GEN
Solar/Wind Harmer
0.401
961011AF2-392 GEN
Solar/Wind Harmer
12.249
270227U2-072_GEN3
Solar/Wind Helper
0.133
270228U2-072_GEN4
Solar/Wind Helper
0.133
276820AF1-078_GEN
Solar/Wind Helper
0.141
965421AG1-410 GEN
Solar/Wind Harmer
6.822
972181SS23-001
Solar/Wind Harmer
0.444
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.311
970289AG2-191 GEN
Solar/Wind Harmer
0.079
24755605MDL-5G
Solar/Wind Harmer
3.365
959091AF2-200 GEN
Solar/Wind Harmer
0.811
946031AF1-268 GEN
Solar/Wind Harmer
0.329
274849CRESCENT ;1U
Solar/Wind Harmer
2.569
274877BISHOP HL;1U
Solar/Wind Harmer
4.523
270349AD2-093_GEN
Solar/Wind Helper
0.383
24729205KEY G1
50/50
6.754
270526AF1-158 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
0.936
964401AG1-302 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
8.261
270004AE1-209 GEN
Solar/Wind Harmer
6.463
274872LEEDK;1U
Solar/Wind Harmer
0.181
270180AB1-006 GEN1
Solar/Wind Harmer
9.562
24791305MDL-5G
Solar/Wind Harmer
3.365
959081AF2-199 GEN
Solar/Wind Harmer
0.406
971475AH1-234 GEN
Solar/Wind Harmer
0.898
276646AC1-214 GEN2
Solar/Wind Harmer
1.683
24386205FR-12G C
Solar/Wind Harmer
3.179
276726Z2-087_GEN
Solar/Wind Harmer
10.052
24727005RPMNG1
50/50
68.971
247620Y3-023
50/50
0.466
965041AG1-368 GEN
Solar/Wind Harmer
0.706
270191TR4_S_V150
Solar/Wind Harmer
6.54
965101AG1-375 GEN
Solar/Wind Harmer
0.511
960681AF2-359 GEN
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
0.373
971917AH1-482 GEN
Solar/Wind Harmer
6.726
276691AA1-018 GEN1
Solar/Wind Harmer
0.451
970115AG2-085 GEN
Solar/Wind Harmer
0.163
276872AE1-163_GEN1
Solar/Wind Harmer
9.109
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
10.701
971067AG2-660 GEN
Solar/Wind Harmer
1.622
276741O09 GEN1
Solar/Wind Harmer
4.827
276655WTG1_EQ
Solar/Wind Harmer
6.657
270578AF1-285 GEN2
Solar/Wind Helper
0.267
247522W1-056 GEN
Solar/Wind Helper
1.806
270286AF1-227 GEN2
Solar/Wind Helper
0.313
961961AG1-039 GEN
Solar/Wind Helper
0.152
241960AC2-195 GEN
Solar/Wind Helper
0.26
971617AH1-308 GEN
Solar/Wind Harmer
5.201
943021AE2-325 GEN
Solar/Wind Harmer
2.992
958011AF2-095 GEN
Solar/Wind Harmer
0.623
971573AH1-285 GEN
Solar/Wind Harmer
0.361
945421AF1-207 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
0.621
942991AE2-321 GEN
Solar/Wind Harmer
0.41
971333AH1-146 GEN
Solar/Wind Harmer
0.816
24697905MDL-4G C
Solar/Wind Harmer
3.365
970819AG2-516 GEN
Solar/Wind Harmer
0.483
964611AG1-324 GEN
Solar/Wind Harmer
0.357
270201AC2-176 GEN
Solar/Wind Harmer
6.697
274851PROVIDENC;RU
Solar/Wind Harmer
3.718
274878BISHOP HL;2U
Solar/Wind Harmer
4.523
24699105WLD G1 C
Solar/Wind Harmer
5.025
270499AE1-146 GEN
Solar/Wind Helper
0.511
959331AF2-224 GEN
Solar/Wind Harmer
1.15
960971AF2-388 GEN
Solar/Wind Harmer
16.413
970349AG2-230 GEN
Solar/Wind Harmer
0.729
971347AH1-153 GEN
Solar/Wind Harmer
0.729
961051AF2-396 GEN
Solar/Wind Harmer
0.97
961051AF2-396 GEN
Solar/Wind Harmer
7.761
270599AE1-208 GEN
Solar/Wind Harmer
0.373
970245AG2-165 GEN
Solar/Wind Harmer
0.894
972231SS25-0005
Solar/Wind Harmer
0.71
274862TOP CROP ;2U
Solar/Wind Harmer
6.862
970921AG2-575 GEN
Solar/Wind Harmer
0.413
970921AG2-575 GEN
Solar/Wind Harmer
1.652
274879MINONK ;1U
Solar/Wind Harmer
9.667
971411AH1-196 GEN
Solar/Wind Harmer
0.613
274855GSG-6 ;RU
Solar/Wind Harmer
5.182
24386405FR-21G C
Solar/Wind Harmer
3.045
942871AE2-306 GEN
Solar/Wind Helper
0.2
945641AF1-229 GEN
Solar/Wind Helper
0.422
970615AG2-402 GEN
50/50
4.602
24729405KEY G3
50/50
6.868
24729505KEY G4
50/50
6.754
270043AE2-236 GEN
Solar/Wind Harmer
0.373
971771AH1-392 GEN
Solar/Wind Harmer
0.442
270505AE1-170 C O1
Solar/Wind Harmer
0.728
274888KELLY CRK;1U
Solar/Wind Harmer
8.779
970941AG2-585 GEN
Solar/Wind Harmer
0.541
971605AH1-302 GEN
Solar/Wind Harmer
6.341
276805AD2-038 GEN
Solar/Wind Harmer
7.5
274850MENDOTA H;RU
Solar/Wind Harmer
3.67
276861AD2-134 GEN
Solar/Wind Harmer
2.505
274864CRW2-WTG
Solar/Wind Harmer
7.688
970569AG2-363 GEN
Solar/Wind Harmer
1.205
274858EASY ROAD;U2
Solar/Wind Harmer
6.231
276157O29GEN1
Solar/Wind Harmer
5.735
957751AF2-069 GEN
Solar/Wind Harmer
0.514
939741AE1-205 GEN
Solar/Wind Harmer
0.773
246938BC-WTG3
Solar/Wind Helper
5.433
246936BC-WTG1
Solar/Wind Helper
5.496
24727105RPMNG2
50/50
68.971
965651AG1-433 GEN
Solar/Wind Harmer
8.207
270449AD2-020 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
9.896
943121AE2-341 GEN
Solar/Wind Harmer
0.633
970291AG2-192 GEN
Solar/Wind Harmer
0.054
970289AG2-191 GEN
Solar/Wind Harmer
0.55
957471AF2-041 GEN
Solar/Wind Harmer
1.217
274848CAMPGROVE;RU
Solar/Wind Harmer
7.073
959341AF2-225 GEN
Solar/Wind Harmer
0.58
957201AF2-014 GEN
Solar/Wind Helper
3.911
270284AF1-227 GEN1
Solar/Wind Helper
0.847
270428AC2-015 C
Solar/Wind Helper
0.344
965021AG1-366 GEN
Solar/Wind Harmer
4.602
958861AF2-177 GEN
Solar/Wind Harmer
15.941
945371AF1-202 GEN
Solar/Wind Harmer
7.519
270541AE2-072 C
Solar/Wind Helper
0.42
270063AE2-323 C
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
276893AG1-478 C
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
1.242
270594AE1-207 GEN
Solar/Wind Harmer
0.66
270032AE2-172
Solar/Wind Harmer
3.298
971997AH1-543 GEN
Solar/Wind Harmer
0.645
276863AD2-134 GEN
Solar/Wind Harmer
2.505
274863CRW1-WTG
Solar/Wind Harmer
7.688
276889AE2-281 GEN
Solar/Wind Harmer
2.603
24691005MDL-2G C
Solar/Wind Harmer
5.104
274856ECOGROVE ;U1
Solar/Wind Harmer
4.705
971549AH1-272 GEN
Solar/Wind Harmer
0.738
276158O29GEN2
Solar/Wind Harmer
5.735
276708O09 GEN2
Solar/Wind Harmer
4.827
246937BC-WTG2
Solar/Wind Helper
5.496
270485AE1-090_GEN
Solar/Wind Helper
0.147
965011AG1-365 GEN
Solar/Wind Harmer
1.15
945581AF1-223 GEN
Solar/Wind Harmer
0
970513AG2-328 GEN
Solar/Wind Harmer
0.894
970517AG2-330 GEN
Solar/Wind Harmer
13.95
959141AF2-205 GEN
Solar/Wind Harmer
0
970833AG2-524 GEN
Solar/Wind Harmer
0.467
958821AF2-173 GEN
Solar/Wind Harmer
0.58
962781AG1-127 GEN
Solar/Wind Harmer
0.393
971335AH1-147 GEN
Solar/Wind Harmer
0.816
24697605MDL-3G C
Solar/Wind Harmer
5.096
270181AB1-006 GEN2
Solar/Wind Harmer
0.634
971171AH1-044 GEN
Solar/Wind Harmer
0.811
926823AC1-168 GEN
Solar/Wind Harmer
4.923
24385905FR-11G C
Solar/Wind Harmer
5.987
276782AC1-033 GEN
Solar/Wind Harmer
5.11
24725505WLD G2 C
Solar/Wind Harmer
5.056
946321AF1-296 GEN
Solar/Wind Harmer
11.381
960611AF2-352 GEN
Solar/Wind Harmer
0.992
944531AF1-118 GEN
Solar/Wind Harmer
2.062
945111AF1-176 GEN
Solar/Wind Harmer
0.888
945111AF1-176 GEN
Solar/Wind Harmer
4.84
957891AF2-083 GEN
Solar/Wind Harmer
0
971769AH1-391 GEN
Solar/Wind Harmer
0.472
274887GEN-1.85
Solar/Wind Harmer
8.065
970707AG2-453 GEN
Solar/Wind Harmer
1.203
970833AG2-524 GEN
Solar/Wind Harmer
3.74
958481AF2-142 GEN
Solar/Wind Harmer
0.629
276868AE1-113 GEN
Solar/Wind Harmer
13.822
971675AH1-338 GEN
Solar/Wind Harmer
0.735
960791AF2-370 GEN
Solar/Wind Harmer
1.628
970781AG2-491 GEN
Solar/Wind Harmer
0.406
276903AD2-071 C
Solar/Wind Harmer
0.395
966841AG1-555 GEN
Solar/Wind Harmer
0
274853TWINGROVE;U1
Solar/Wind Harmer
9.371
270224U2-072_GEN2
Solar/Wind Helper
0.133
270391AF1-285 GEN3
Solar/Wind Helper
0.267
241847AF2-150_GEN
Solar/Wind Helper
0.239
944541AF1-119 GEN
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
5.09
276843GEN-1.7
Solar/Wind Harmer
0.714
941551AE2-152 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
11.948
276882AE2-255 GEN
Solar/Wind Harmer
4.361
960441AF2-335 GEN
Solar/Wind Harmer
0.407
270223U2-072_GEN1
Solar/Wind Helper
0.133
966831AG1-554 GEN
Solar/Wind Helper
0.265
274854TWINGROVE;U2
Solar/Wind Harmer
6.054
970583AG2-370 GEN
50/50
2.823
970031AG2-029 GEN
Solar/Wind Harmer
2.112
270247TR4_N_V136
Solar/Wind Harmer
1.186
965051AG1-369 GEN
Solar/Wind Harmer
0.301
960591AF2-350 GEN
Solar/Wind Harmer
0.432
958381AF2-132 GEN
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
8.088
939401AE1-172 GEN
Solar/Wind Harmer
16.42
276876AE1-163_GEN2
Solar/Wind Harmer
9.109
274857EASY ROAD;U1
Solar/Wind Harmer
6.231
961761AG1-017 GEN
Solar/Wind Harmer
0.391
276656WTG2_EQ
Solar/Wind Harmer
0.882
941731AE2-173 GEN
Solar/Wind Harmer
3.866
270462AD2-086
Solar/Wind Helper
1.688
270317AD1-130_GEN
Solar/Wind Helper
1.101
270287AF1-227 GEN3
Solar/Wind Helper
0.313
971599AH1-298 GEN
50/50
10.386
960861AF2-377 GEN
50/50
2.413
24729305KEY G2
50/50
6.868
970611AG2-400 GEN
Solar/Wind Harmer
1.15
270071AF1-092 GEN
Solar/Wind Harmer
0.944
970321AG2-212 GEN
Solar/Wind Harmer
0.894
270005AE1-210 C O1
Solar/Wind Harmer
6.463
276602WESTBROOK C
Solar/Wind Harmer
2.858
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
0.594
276645AC1-214 GEN1
Solar/Wind Harmer
1.683
24387305FR-4G C
Solar/Wind Harmer
4.568
24386605FR-22G C
Solar/Wind Harmer
3.045
24387005FR-3G C
Solar/Wind Harmer
3.015
942111AE2-223 GEN
Solar/Wind Harmer
9.047
960841AF2-375 GEN
Solar/Wind Helper
0.529
964861AG1-349 GEN
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
43.926
940581AE2-045 GEN
Solar/Wind Harmer
0
971177AH1-047 GEN
Solar/Wind Harmer
0.24
970825AG2-519 GEN
Solar/Wind Harmer
0.448
970825AG2-519 GEN
Solar/Wind Harmer
1.72
970571AG2-364 GEN
Solar/Wind Harmer
0.803
971681AH1-341 GEN
Solar/Wind Harmer
0.599
938861AE1-114 GEN
Solar/Wind Harmer
9.335
276603SUBLETTE C
Solar/Wind Harmer
1.356
253378AE2-206_GEN
Solar/Wind Helper
0.312
970521AG2-332 GEN
50/50
10.877
247521TR3_G114
Solar/Wind Harmer
8.771
276806AD2-047 C O1
Solar/Wind Harmer
13.32
958391AF2-133 GEN
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
7.573
247642Z2-115 C
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.5
971341AH1-150 GEN
Solar/Wind Harmer
0.811
270302AB2-170 GEN
Solar/Wind Helper
1.101
270231U2-072_GEN5
Solar/Wind Helper
0.133
270471AD2-092_GEN
Solar/Wind Helper
0.383
957141AF2-008_MTX
Adder
27.935
944201AF1-088_MTX
Adder
55.87
990497J1323
External Queue
0
CBM West 1LTFEXP_CBM-W1->PJM
CBM
73.505
NYPJM->LTFIMP_NY
CLTF
1.226
TVALTFEXP_TVA->PJM
CLTF
2.31
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
23.037
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.901
WECLTFEXP_WEC->PJM
CLTF
2.651
LAGNLTFEXP_LAGN->PJM
CLTF
5.747
AH1-155LTFEXP_AH1-155->PJM
LTF
0.251
CBM West 2LTFEXP_CBM-W2->PJM
CBM
51.154
LGEELTFEXP_LGEE->PJM
CLTF
1.819
MECLTFEXP_MEC->PJM
CLTF
9.7
AG2-052LTFEXP_AG2-052->PJM
LTF
0.167
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.599
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.014
SIGELTFEXP_SIGE->PJM
CLTF
0.2

Details for AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7446_05MARYSV 765_B2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.94 %
Rating:2219.0 MVA
Rating Type:B
MVA to Mitigate:2262.15
MW Contribution:0.7
Bus #Bus NameTypeMW Contribution
965431AG1-411 GEN
50/50
44.816
24727205RPMNG3
50/50
67.91
24639705ELKHART HY
50/50
0.145
963791AG1-232 GEN
Solar/Wind Harmer
0.942
270246TR4_N_V150
Solar/Wind Harmer
1.13
24695305TIMB G C
Solar/Wind Harmer
9.393
270024AE2-089 GEN
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
0.558
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
943591AF1-030 GEN
Solar/Wind Harmer
0.408
276901AD2-066 C O1
Solar/Wind Harmer
0
965031AG1-367 GEN
Solar/Wind Harmer
0.398
971343AH1-151 GEN
Solar/Wind Harmer
0.783
970169AG2-114 GEN
Solar/Wind Harmer
0.387
961011AF2-392 GEN
Solar/Wind Harmer
11.826
270227U2-072_GEN3
Solar/Wind Helper
0.148
270228U2-072_GEN4
Solar/Wind Helper
0.148
276820AF1-078_GEN
Solar/Wind Helper
0.158
965421AG1-410 GEN
Solar/Wind Harmer
6.722
972181SS23-001
Solar/Wind Harmer
0.429
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.267
970289AG2-191 GEN
Solar/Wind Harmer
0.076
24755605MDL-5G
Solar/Wind Harmer
3.247
959091AF2-200 GEN
Solar/Wind Harmer
0.783
946031AF1-268 GEN
Solar/Wind Harmer
0.315
274849CRESCENT ;1U
Solar/Wind Harmer
2.48
24729205KEY G1
50/50
6.542
270526AF1-158 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
0.904
964401AG1-302 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
7.977
270004AE1-209 GEN
Solar/Wind Harmer
6.21
274872LEEDK;1U
Solar/Wind Harmer
0.175
270180AB1-006 GEN1
Solar/Wind Harmer
9.228
24791305MDL-5G
Solar/Wind Harmer
3.247
959081AF2-199 GEN
Solar/Wind Harmer
0.392
971475AH1-234 GEN
Solar/Wind Harmer
0.867
276646AC1-214 GEN2
Solar/Wind Harmer
1.624
24386205FR-12G C
Solar/Wind Harmer
3.066
276726Z2-087_GEN
Solar/Wind Harmer
9.698
24727005RPMNG1
50/50
67.91
247620Y3-023
50/50
0.451
965041AG1-368 GEN
Solar/Wind Harmer
0.679
270191TR4_S_V150
Solar/Wind Harmer
6.235
965101AG1-375 GEN
Solar/Wind Harmer
0.494
960681AF2-359 GEN
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
0.359
971917AH1-482 GEN
Solar/Wind Harmer
6.492
276691AA1-018 GEN1
Solar/Wind Harmer
0.436
276872AE1-163_GEN1
Solar/Wind Harmer
8.794
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
10.326
971067AG2-660 GEN
Solar/Wind Harmer
1.567
970115AG2-085 GEN
Solar/Wind Harmer
0.156
276741O09 GEN1
Solar/Wind Harmer
4.66
276655WTG1_EQ
Solar/Wind Harmer
6.423
270578AF1-285 GEN2
Solar/Wind Helper
0.296
270286AF1-227 GEN2
Solar/Wind Helper
0.376
247522W1-056 GEN
Solar/Wind Helper
1.925
961961AG1-039 GEN
Solar/Wind Helper
0.165
971617AH1-308 GEN
Solar/Wind Harmer
4.999
943021AE2-325 GEN
Solar/Wind Harmer
2.884
958011AF2-095 GEN
Solar/Wind Harmer
0.601
971573AH1-285 GEN
Solar/Wind Harmer
0.349
945421AF1-207 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
0.599
942991AE2-321 GEN
Solar/Wind Harmer
0.396
971333AH1-146 GEN
Solar/Wind Harmer
0.788
24697905MDL-4G C
Solar/Wind Harmer
3.247
970819AG2-516 GEN
Solar/Wind Harmer
0.466
274851PROVIDENC;RU
Solar/Wind Harmer
3.588
964611AG1-324 GEN
Solar/Wind Harmer
0.34
270201AC2-176 GEN
Solar/Wind Harmer
6.374
274878BISHOP HL;2U
Solar/Wind Harmer
4.366
24699105WLD G1 C
Solar/Wind Harmer
4.824
965931AG1-462 GEN
Solar/Wind Harmer
0.935
270499AE1-146 GEN
Solar/Wind Helper
0.547
274877BISHOP HL;1U
Solar/Wind Harmer
4.366
270349AD2-093_GEN
Solar/Wind Helper
0.507
270063AE2-323 C
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0
970513AG2-328 GEN
Solar/Wind Harmer
0.864
970517AG2-330 GEN
Solar/Wind Harmer
13.48
959141AF2-205 GEN
Solar/Wind Harmer
0
24653605MOTTVILLE
50/50
0.003
965011AG1-365 GEN
Solar/Wind Harmer
1.126
945111AF1-176 GEN
Solar/Wind Harmer
0.857
945111AF1-176 GEN
Solar/Wind Harmer
4.67
957891AF2-083 GEN
Solar/Wind Harmer
0
971769AH1-391 GEN
Solar/Wind Harmer
0.456
964861AG1-349 GEN
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
42.42
940581AE2-045 GEN
Solar/Wind Harmer
0
971177AH1-047 GEN
Solar/Wind Harmer
0.232
970571AG2-364 GEN
Solar/Wind Harmer
0.776
970825AG2-519 GEN
Solar/Wind Harmer
0.43
970825AG2-519 GEN
Solar/Wind Harmer
1.65
971681AH1-341 GEN
Solar/Wind Harmer
0.578
938861AE1-114 GEN
Solar/Wind Harmer
9.013
276603SUBLETTE C
Solar/Wind Harmer
1.309
253378AE2-206_GEN
Solar/Wind Helper
0.35
944531AF1-118 GEN
Solar/Wind Harmer
1.998
274887GEN-1.85
Solar/Wind Harmer
7.789
970707AG2-453 GEN
Solar/Wind Harmer
1.162
970833AG2-524 GEN
Solar/Wind Harmer
3.611
958481AF2-142 GEN
Solar/Wind Harmer
0.607
276868AE1-113 GEN
Solar/Wind Harmer
13.346
971675AH1-338 GEN
Solar/Wind Harmer
0.709
970781AG2-491 GEN
Solar/Wind Harmer
0.392
960791AF2-370 GEN
Solar/Wind Harmer
1.562
276903AD2-071 C
Solar/Wind Harmer
0.38
966841AG1-555 GEN
Solar/Wind Harmer
0
274853TWINGROVE;U1
Solar/Wind Harmer
9.04
270224U2-072_GEN2
Solar/Wind Helper
0.148
270391AF1-285 GEN3
Solar/Wind Helper
0.296
241847AF2-150_GEN
Solar/Wind Helper
0.259
959331AF2-224 GEN
Solar/Wind Harmer
1.126
944541AF1-119 GEN
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
4.913
276843GEN-1.7
Solar/Wind Harmer
0.69
941551AE2-152 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
11.537
276882AE2-255 GEN
Solar/Wind Harmer
4.21
960441AF2-335 GEN
Solar/Wind Harmer
0.39
270223U2-072_GEN1
Solar/Wind Helper
0.148
966831AG1-554 GEN
Solar/Wind Helper
0.282
274854TWINGROVE;U2
Solar/Wind Harmer
5.038
241960AC2-195 GEN
Solar/Wind Helper
0.292
970583AG2-370 GEN
50/50
2.718
970031AG2-029 GEN
Solar/Wind Harmer
2.053
270247TR4_N_V136
Solar/Wind Harmer
1.13
965051AG1-369 GEN
Solar/Wind Harmer
0.287
960591AF2-350 GEN
Solar/Wind Harmer
0.418
958381AF2-132 GEN
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
7.81
939401AE1-172 GEN
Solar/Wind Harmer
15.852
276876AE1-163_GEN2
Solar/Wind Harmer
8.794
274857EASY ROAD;U1
Solar/Wind Harmer
6.016
961761AG1-017 GEN
Solar/Wind Harmer
0.372
276656WTG2_EQ
Solar/Wind Harmer
0.85
941731AE2-173 GEN
Solar/Wind Harmer
3.73
270462AD2-086
Solar/Wind Helper
1.844
270317AD1-130_GEN
Solar/Wind Helper
1.203
270287AF1-227 GEN3
Solar/Wind Helper
0.376
960971AF2-388 GEN
Solar/Wind Harmer
15.869
970349AG2-230 GEN
Solar/Wind Harmer
0.705
971347AH1-153 GEN
Solar/Wind Harmer
0.705
961051AF2-396 GEN
Solar/Wind Harmer
0.936
961051AF2-396 GEN
Solar/Wind Harmer
7.484
270599AE1-208 GEN
Solar/Wind Harmer
0.359
970245AG2-165 GEN
Solar/Wind Harmer
0.864
972231SS25-0005
Solar/Wind Harmer
0.686
274862TOP CROP ;2U
Solar/Wind Harmer
6.626
970921AG2-575 GEN
Solar/Wind Harmer
0.399
970921AG2-575 GEN
Solar/Wind Harmer
1.595
274879MINONK ;1U
Solar/Wind Harmer
9.334
971411AH1-196 GEN
Solar/Wind Harmer
0.592
274855GSG-6 ;RU
Solar/Wind Harmer
5.004
24386405FR-21G C
Solar/Wind Harmer
2.937
942871AE2-306 GEN
Solar/Wind Helper
0.222
945641AF1-229 GEN
Solar/Wind Helper
0.452
270541AE2-072 C
Solar/Wind Helper
0.467
970833AG2-524 GEN
Solar/Wind Harmer
0.451
962781AG1-127 GEN
Solar/Wind Harmer
0.379
958821AF2-173 GEN
Solar/Wind Harmer
0.557
971335AH1-147 GEN
Solar/Wind Harmer
0.788
24697605MDL-3G C
Solar/Wind Harmer
4.918
270181AB1-006 GEN2
Solar/Wind Harmer
0.612
971171AH1-044 GEN
Solar/Wind Harmer
0.783
926823AC1-168 GEN
Solar/Wind Harmer
4.753
24385905FR-11G C
Solar/Wind Harmer
5.774
276782AC1-033 GEN
Solar/Wind Harmer
4.932
24725505WLD G2 C
Solar/Wind Harmer
4.854
946321AF1-296 GEN
Solar/Wind Harmer
10.986
958581AF2-149 GEN
Solar/Wind Helper
0.21
960611AF2-352 GEN
Solar/Wind Harmer
0.826
24727105RPMNG2
50/50
67.91
965651AG1-433 GEN
Solar/Wind Harmer
7.934
270449AD2-020 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
9.557
943121AE2-341 GEN
Solar/Wind Harmer
0.611
970291AG2-192 GEN
Solar/Wind Harmer
0.052
970289AG2-191 GEN
Solar/Wind Harmer
0.529
957471AF2-041 GEN
Solar/Wind Harmer
1.175
274848CAMPGROVE;RU
Solar/Wind Harmer
6.827
959341AF2-225 GEN
Solar/Wind Harmer
0.56
957201AF2-014 GEN
Solar/Wind Helper
3.962
270284AF1-227 GEN1
Solar/Wind Helper
1.019
270428AC2-015 C
Solar/Wind Helper
0.368
253383AE2-342_GEN
Solar/Wind Helper
0.101
971599AH1-298 GEN
50/50
10.098
960861AF2-377 GEN
50/50
2.301
24729305KEY G2
50/50
6.653
970611AG2-400 GEN
Solar/Wind Harmer
1.126
270071AF1-092 GEN
Solar/Wind Harmer
0.917
970321AG2-212 GEN
Solar/Wind Harmer
0.864
270005AE1-210 C O1
Solar/Wind Harmer
6.21
276602WESTBROOK C
Solar/Wind Harmer
2.759
276645AC1-214 GEN1
Solar/Wind Harmer
1.624
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
0.566
24387305FR-4G C
Solar/Wind Harmer
4.405
24386605FR-22G C
Solar/Wind Harmer
2.937
24387005FR-3G C
Solar/Wind Harmer
2.908
942111AE2-223 GEN
Solar/Wind Harmer
8.728
960841AF2-375 GEN
Solar/Wind Helper
0.566
970615AG2-402 GEN
50/50
4.505
24729405KEY G3
50/50
6.653
24729505KEY G4
50/50
6.542
270043AE2-236 GEN
Solar/Wind Harmer
0.362
971771AH1-392 GEN
Solar/Wind Harmer
0.427
270505AE1-170 C O1
Solar/Wind Harmer
0.702
274888KELLY CRK;1U
Solar/Wind Harmer
8.479
970941AG2-585 GEN
Solar/Wind Harmer
0.522
971605AH1-302 GEN
Solar/Wind Harmer
6.121
276805AD2-038 GEN
Solar/Wind Harmer
7.241
274850MENDOTA H;RU
Solar/Wind Harmer
3.544
276861AD2-134 GEN
Solar/Wind Harmer
2.419
274864CRW2-WTG
Solar/Wind Harmer
7.421
970569AG2-363 GEN
Solar/Wind Harmer
1.163
274858EASY ROAD;U2
Solar/Wind Harmer
6.016
276157O29GEN1
Solar/Wind Harmer
5.536
957751AF2-069 GEN
Solar/Wind Harmer
0.496
939741AE1-205 GEN
Solar/Wind Harmer
0.746
246938BC-WTG3
Solar/Wind Helper
5.504
246936BC-WTG1
Solar/Wind Helper
5.567
965021AG1-366 GEN
Solar/Wind Harmer
4.505
958861AF2-177 GEN
Solar/Wind Harmer
15.401
945371AF1-202 GEN
Solar/Wind Harmer
7.254
276893AG1-478 C
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
1.199
957841AF2-078 GEN
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
0.634
270032AE2-172
Solar/Wind Harmer
3.17
971997AH1-543 GEN
Solar/Wind Harmer
0.623
276863AD2-134 GEN
Solar/Wind Harmer
2.419
274863CRW1-WTG
Solar/Wind Harmer
7.421
276889AE2-281 GEN
Solar/Wind Harmer
2.513
24691005MDL-2G C
Solar/Wind Harmer
4.926
274856ECOGROVE ;U1
Solar/Wind Harmer
4.543
971549AH1-272 GEN
Solar/Wind Harmer
0.704
276158O29GEN2
Solar/Wind Harmer
5.536
276708O09 GEN2
Solar/Wind Harmer
4.66
246937BC-WTG2
Solar/Wind Helper
5.567
270485AE1-090_GEN
Solar/Wind Helper
0.16
970521AG2-332 GEN
50/50
10.52
247521TR3_G114
Solar/Wind Harmer
8.362
276806AD2-047 C O1
Solar/Wind Harmer
12.864
958391AF2-133 GEN
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
7.313
247642Z2-115 C
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.481
971341AH1-150 GEN
Solar/Wind Harmer
0.783
270302AB2-170 GEN
Solar/Wind Helper
1.203
270231U2-072_GEN5
Solar/Wind Helper
0.148
270471AD2-092_GEN
Solar/Wind Helper
0.507
944201AF1-088_MTX
Adder
53.676
957141AF2-008_MTX
Adder
26.838
CBM West 2LTFEXP_CBM-W2->PJM
CBM
49.277
LGEELTFEXP_LGEE->PJM
CLTF
1.703
LAGNLTFEXP_LAGN->PJM
CLTF
5.561
AH1-155LTFEXP_AH1-155->PJM
LTF
0.242
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.712
TVALTFEXP_TVA->PJM
CLTF
2.237
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
23.26
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.562
WECLTFEXP_WEC->PJM
CLTF
2.559
SIGELTFEXP_SIGE->PJM
CLTF
0.191
CBM West 1LTFEXP_CBM-W1->PJM
CBM
69.912
NYPJM->LTFIMP_NY
CLTF
1.178
MECLTFEXP_MEC->PJM
CLTF
9.361
AG2-052LTFEXP_AG2-052->PJM
LTF
0.161
CONTINGENCY 'AEP_P4_#7445_05MARYSV 765_B_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290621 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RF 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 962760 TO BUS 290621 CKT 1    /*AG1-125 TP   765.0 - 05MARYSVL_RF 765.0
END
CONTINGENCY 'AEP_P1-2_#7441_100545_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
END
CONTINGENCY 'AEP_P4_#7441_05SORENS 765_J1_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
END
CONTINGENCY 'AEP_P4_#7446_05MARYSV 765_B2_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 242939 CKT 2    /*05MARYSV     765.0 - 05MARYSV     345.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
END
CONTINGENCY 'AEP_P4_#6189_05HANG R 765_D1_SRT-A'
 OPEN BRANCH FROM BUS 242921 TO BUS 242924 CKT 1    /*05CORNU      765.0 - 05HANG R     765.0
 OPEN BRANCH FROM BUS 242921 TO BUS 242934 CKT 1    /*05CORNU      765.0 - 05CORNU      345.0
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
 REMOVE UNIT 1A FROM BUS 247245                     /*05HRKG1A      18.0
 REMOVE UNIT 1B FROM BUS 247246                     /*05HRKG1B      18.0
 REMOVE UNIT 1S FROM BUS 247247                     /*05HRKG1S      18.0
 REMOVE UNIT 2A FROM BUS 247248                     /*05HRKG2A      18.0
 REMOVE UNIT 2B FROM BUS 247249                     /*05HRKG2B      18.0
 REMOVE UNIT 2S FROM BUS 247250                     /*05HRKG2S      18.0
END
CONTINGENCY 'AEP_P4_#1760_05JEFRSO 765_A_SRT-A'
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290599 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RG 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 970238 TO BUS 290599 CKT 1    /*AG2-162 TP   765.0 - 05JEFFRSN_RG 765.0
END
CONTINGENCY 'AEP_P4_#709_05HANG R 765_D2_SRT-A'
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
END
CONTINGENCY 'AEP_P1-2_#709_546_SRT-A'
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
END
CONTINGENCY 'AEP_P4_#7334_05JEFRSO 765_A2_SRT-A'
 OPEN BRANCH FROM BUS 242865 TO BUS 243208 CKT 2    /*05JEFRSO     345.0 - 05JEFRSO     765.0
 OPEN BRANCH FROM BUS 242865 TO BUS 248000 CKT 1    /*05JEFRSO     345.0 - 06CLIFTY     345.0
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
END
243211 to 242933 ckt 1
243206 to 290606 ckt Z1
290608 to 242928 ckt Z1
242933 to 965420 ckt 1
965420 to 246929 ckt 1

Light Load Analysis

The New Service Request AH1-272 was evaluated as a 185.0 MW injection

AH1-272 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 185.0 MW (185.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AEP/ATSI
02LALLENDORF-05FOSTOR 345.0 kV Ckt 1 line
ATSI_P7-1_TE-345-021_SRT-A-1
TowerAC112.05 %1409.0B1578.766.16

Details for 02LALLENDORF-05FOSTOR 345.0 kV Ckt 1 line l/o ATSI_P7-1_TE-345-021_SRT-A-1


Base Case Flowgate

Area:AEP/ATSI
Facility Description:
02LALLENDORF-05FOSTOR 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P7-1_TE-345-021_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:112.05 %
Rating:1409.0 MVA
Rating Type:B
MVA to Mitigate:1578.76
MW Contribution:6.16
Bus #Bus NameTypeMW Contribution
241847AF2-150_GEN
Solar/Wind Helper
1.298
270499AE1-146 GEN
Solar/Wind Helper
2.179
972211AH1-690 GEN
50/50
647.237
247522W1-056 GEN
Solar/Wind Helper
0.923
945641AF1-229 GEN
Solar/Wind Helper
3.188
960841AF2-375 GEN
Solar/Wind Helper
2.48
961961AG1-039 GEN
Solar/Wind Helper
0.826
971549AH1-272 GEN
Solar/Wind Harmer
6.162
990142J1224
External Queue
9.852609634399414
991177J1571 G
External Queue
7.456767559051514
991182J1586 G
External Queue
19.340486526489258
CBM West 1LTFEXP_CBM-W1->PJM
CBM
81.069
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.07
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.869
NYPJM->LTFIMP_NY
CLTF
0.483
LGEELTFEXP_LGEE->PJM
CLTF
0.159
WECLTFEXP_WEC->PJM
CLTF
0.621
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.208
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.106
TVALTFEXP_TVA->PJM
CLTF
0.231
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
MECLTFEXP_MEC->PJM
CLTF
2.112
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
0.835
SIGELTFEXP_SIGE->PJM
CLTF
0.027
CONTINGENCY 'ATSI_P7-1_TE-345-021_SRT-A-1'
 DISCONNECT BRANCH FROM BUS 238563 TO BUS 972210 CKT 1   /*02BAY SH     345.0 - AH1-690 TP   345.0
 DISCONNECT BRANCH FROM BUS 238563 TO BUS 972210 CKT 2   /*02BAY SH     345.0 - AH1-690 TP   345.0
END
241901 to 242936 ckt 1

Short Circuit Analysis

Short Circuit analysis is not performed as part of the Phase I System Impact Study. Short Circuit analysis will commence in the Phase II System Impact Study.

Stability Analysis

Stability analysis is not performed as part of the Phase I System Impact Study. Stability analysis will commence in the Phase II System Impact Study.

Reactive Power Analysis

Reactive Power analysis is not performed as part of the Phase I System Impact Study. Reactive Power analysis will commence in the Phase II System Impact Study.

Steady-State Voltage Analysis

Steady State Voltage Analysis is Not Required.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-018Powerton-Goodings GroveIn Service
AA1-095Halfway-Marlowe 34.5kVIn Service
AA2-184Atlantic-Red Bank 34kVIn Service
AB1-001Absecon 12 kVIn Service
AB1-006Meadow Lake 345kVIn Service
AB1-087Sullivan 345kV #1Under Construction
AB1-088Sullivan 345kV #2Engineering & Procurement
AB1-096Carroll-Mt. Airy 34.5kVIn Service
AB1-124Carroll-Monocacy 34.5kVPartially in Service - Under Construction
AB1-125Carroll-Monocacy 34.5kVIn Service
AB1-127St. Thomas-Guilford 34.5kVIn Service
AB1-128St. Thomas-Mercersburg 34.5kVIn Service
AB1-138Navy 34.5kVIn Service
AB1-139Metuchen 26kVIn Service
AB1-141Church-Wye Mills 138 kV IIn Service
AB1-142Church-Wye Mills 138 kV IIIn Service
AB1-176Price 25kV IIEngineering & Procurement
AB2-029Remington 34.5kVIn Service
AB2-032Church-Wye Mills 138 kVIn Service
AB2-037Keeney-Steele 230kVUnder Construction
AB2-049Gloucester Township 12kVIn Service
AB2-067Kammer-Vassell 765kVIn Service
AB2-070Mt. Pulaski-BrokawIn Service
AB2-093Ormet 138kVIn Service
AB2-133Chestertown 69kVUnder Construction
AB2-135Church-Kent 69kVIn Service
AB2-136Cambridge-West Cambridge 69kVUnder Construction
AB2-153Church-Wye Mills 138 kVIn Service
AB2-157Prince George's County 12kVIn Service
AB2-170East Lima-Marysville 345kVIn Service
AB2-179Townsend 138kVIn Service
AC1-001Delano 138kVIn Service
AC1-010Gloucester 26kVUnder Construction
AC1-017Levittown 13 kVIn Service
AC1-030Cinnaminson 13kVIn Service
AC1-033Kewanee 138 kVIn Service
AC1-044Kammer-Vassell 765kVIn Service
AC1-053Lanesville-BrokawPartially in Service - Under Construction
AC1-068Atlanta 69kV IIn Service
AC1-069Atlanta 69kV IIIn Service
AC1-074Jacksonville-Renaker 138kV IIn Service
AC1-076Locust Grove-Paytes 115kVIn Service
AC1-078Beatty-London 138kVIn Service
AC1-082Ravenswood-Hemlock 69kVUnder Construction
AC1-085Stuart-Clinton 345kVIn Service
AC1-089Hillsboro-Wildcat 138kVIn Service
AC1-091Cedar Creek 138kV IEngineering & Procurement
AC1-092Cedar Creek 138kV IIEngineering & Procurement
AC1-093Cedar Creek 138kV IIIEngineering & Procurement
AC1-094Cedar Creek 138kV IVEngineering & Procurement
AC1-111Aurora 138kVIn Service
AC1-120Mitchell-Mountain Run 115kVEngineering & Procurement
AC1-121Mitchell-Mountain Run 115kVEngineering & Procurement
AC1-141Cook-East Elkhart 345kVIn Service
AC1-158Spotsylvania 500kVIn Service
AC1-165Atlanta 69kV IIIIn Service
AC1-166Atlanta 69kV IVIn Service
AC1-167Mark Center 69kVUnder Construction
AC1-168Kewanee-StreatorSuspended
AC1-174Losantville 345kVIn Service
AC1-175Losantville 345kVIn Service
AC1-188Rio-Lick 138kVEngineering & Procurement
AC1-194Elk 138kVActive
AC1-214Crescent RidgeIn Service
AC2-015Chatfield-Howard 138kVPartially in Service - Under Construction
AC2-023Hebron 69kVEngineering & Procurement
AC2-029Circleville 138kVSuspended
AC2-044Maddox Creek 345kVSuspended
AC2-059Biers Run-Circleville 138kVIn Service
AC2-060Buckskin 69kVIn Service
AC2-061Hillsboro-Clinton 138kVIn Service
AC2-067Camden-Crystal I 69kVEngineering & Procurement
AC2-068Camden-Crystal II 69kVEngineering & Procurement
AC2-075Jacksonville-Renaker 138 kVIn Service
AC2-088S. Bethel-Brown 69kVIn Service
AC2-090Losantville 345kVIn Service
AC2-103Beaver-Davis Besse 345 kV IEngineering & Procurement
AC2-111College Corner 138kVEngineering & Procurement
AC2-120Ripley 69kVIn Service
AC2-136East Hagerstown 12kVUnder Construction
AC2-154Davis Creek 138kVEngineering & Procurement
AC2-157Sullivan 345 kVUnder Construction
AC2-168Clinton 23kVIn Service
AC2-176Jay 138 kVIn Service
AC2-186Harrington 25kVUnder Construction
AC2-187Harrington 69kVUnder Construction
AC2-188Harrington 69 kVUnder Construction
AC2-195Galion-Roberts South 138 kVUnder Construction
AD1-013Twombly Road 138kVEngineering & Procurement
AD1-020Hunterstown-Lincoln 115 kVIn Service
AD1-060Mercersburg-Milnor 34.5 kVIn Service
AD1-061McConnelsburg-Mercersburg 34 kVIn Service
AD1-100Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVUnder Construction
AD1-101Continental 69 kVIn Service
AD1-106North Waldo-Wild Creek 138 kVSuspended
AD1-115Mountain Run-Mitchell 115 kVEngineering & Procurement
AD1-119Payne 69 kVIn Service
AD1-128Modoc-Delaware 138 kVPartially in Service - Under Construction
AD1-130Hardin Switch 345 kVIn Service
AD1-136South Bethel-Brown 69 kVIn Service
AD1-140Greene-Clark 138 kVEngineering & Procurement
AD1-155Meadow Brook-Strasburg 138 kVIn Service
AD2-009McConnellsburg 138 kVIn Service
AD2-016Biers Run-Circleville 138 kVIn Service
AD2-020Valley 138 kVEngineering & Procurement
AD2-027Camden Switch 26 kVIn Service
AD2-031Martinsville-Wilmington 69 kVIn Service
AD2-038Powerton-Nevada 345 kVUnder Construction
AD2-042Camden Switch 26 kV IIIn Service
AD2-047Davis Creek 138 kVSuspended
AD2-048Cynthia-Headquarters 69 kVUnder Construction
AD2-058St. Barnabas 13 kVIn Service
AD2-060Davis Creek 138kVEngineering & Procurement
AD2-065Atco 12 kVIn Service
AD2-066Mazon-Crescent Ridge 138 kVEngineering & Procurement
AD2-067Centerburg 138kVEngineering & Procurement
AD2-070Gilbert-Morris Park 34.5kVIn Service
AD2-071Strawton-Deer Creek 138 kVSuspended
AD2-079Capitol Ave 34.5kVIn Service
AD2-086Hardin Switch 345 kVIn Service
AD2-091Hardin Tap 345kVSuspended
AD2-092Marysville 345kVUnder Construction
AD2-093Marysville 345kVUnder Construction
AD2-096Marysville 345kVSuspended
AD2-100Kincaid-Pana 345 kVSuspended
AD2-115Lyons-Moselem 69kVIn Service
AD2-116Hokes-Grantley 69 kVIn Service
AD2-131Kincaid-Pana 345kVSuspended
AD2-133Eagle Valley 115kVIn Service
AD2-134Shady OaksPartially in Service - Under Construction
AD2-135Williamstown 12kVPartially in Service - Under Construction
AD2-163Broadview-Tangy 138 kVIn Service
AD2-172Lena 138kVIn Service
AD2-180Elk Garden-Parr Run 138kVIn Service
AE1-040Greenfield 69 kVIn Service
AE1-041Edison 4kVIn Service
AE1-071Shade Gap-Roxbury 115 kVIn Service
AE1-079Maysville-Sharon 69 kVUnder Construction
AE1-081Landing 12.47 kVIn Service
AE1-090Hardin Switch 345 kVIn Service
AE1-091West Newton-Lynn 138 kVSuspended
AE1-092Blue Jacket-Kirby 138 kVActive
AE1-101McConnellsburg-Texas Eastern 138 kVIn Service
AE1-102Maddox Creek 345 kVSuspended
AE1-109Frenchs Mill 34 kVIn Service
AE1-113Mole Creek 345 kVEngineering & Procurement
AE1-114Maryland-Lancaster 138 kVActive
AE1-142Manitou-Pleasant Plains 34.5 kVIn Service
AE1-146Ebersole #2-Fostoria Central 138 kVUnder Construction
AE1-156Quakertown Solar II 34.5 kVPartially in Service - Under Construction
AE1-163Powerton-Nevada 345 kVEngineering & Procurement
AE1-166Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE1-170Kenzie Creek-Colby 138 kVSuspended
AE1-172Loretto-Wilton CenterActive
AE1-183Maysville-McDowell 69 kVEngineering & Procurement
AE1-185Hokes-Jackson 69 kVIn Service
AE1-196Hokes-Jackson 69 kV IIIn Service
AE1-205McLean 345 kVEngineering & Procurement
AE1-207Mississinewa-Gaston 138 kVSuspended
AE1-208Delaware-Van Buren 138 kVSuspended
AE1-209Desoto 345 kVSuspended
AE1-210Desoto 345 kVSuspended
AE1-227South Cumberland 69 kVSuspended
AE1-229Deepwater-Upper Pittsgrove 138 kVSuspended
AE1-237Andover (Maysville) 69kV IUnder Construction
AE1-245Haviland 138 kVUnder Construction
AE2-035Lena 138 kVIn Service
AE2-045Olive-Reynolds 345 kVEngineering & Procurement
AE2-048Muskingum-W. Millersport 345 kVEngineering & Procurement
AE2-054Warfordsburg 34 kVIn Service
AE2-071Patton Rd-Summer Shade 69 kVIn Service
AE2-072East Leipsic-Richland 138 kVIn Service
AE2-089Pennville-Adams 138 kVEngineering & Procurement
AE2-113Farmers Valley-Ridgeway 115 kVUnder Construction
AE2-114Midland 23 kV IIn Service
AE2-115Midland 23 kV IIIn Service
AE2-117ABW Tap-Alexandria 46 kVSuspended
AE2-126Dubois-Curwensville 34.5 kVIn Service
AE2-129Philipsburg-Clarence 34.5 kVIn Service
AE2-131Philipsburg-Karthaus 34.5Under Construction
AE2-136Muskingum River-W. Millersport 345 kVEngineering & Procurement
AE2-139East Towanda-Grover 230 kVEngineering & Procurement
AE2-148Beatty-Greene 345 kVIn Service
AE2-152Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE2-169Delaware-Van Buren 138 kVSuspended
AE2-172Mississinewa-Gaston 138 kVSuspended
AE2-173McLean 345 kVActive
AE2-175Jackson-Long Pond 69 kVPartially in Service - Under Construction
AE2-176Groton 138 kV SolarIn Service
AE2-181Snyder 69kVUnder Construction
AE2-206East Sidney-Quincy 138 kVIn Service
AE2-214Cole 345 kVEngineering & Procurement
AE2-216Hardin Switch 345 kVEngineering & Procurement
AE2-217East Springfield-London 138 kVEngineering & Procurement
AE2-219Bluff Point-Randolph 138 kVSuspended
AE2-220Losantville 345 kVEngineering & Procurement
AE2-221Clinton-Stuart 345 kVUnder Construction
AE2-223McLean 345 kVActive
AE2-224Bear Rock-Johnstown 230 kVIn Service
AE2-226Millville-Old Chapel 138 kVEngineering & Procurement
AE2-230Bartonsville-Meadow Brook 138 kVIn Service
AE2-234Liberty Center-Buckeye Tap 69 kVEngineering & Procurement
AE2-236Columbia-Northeast 138 kVSuspended
AE2-254Garrard County-Tommy-Gooch 69 kVIn Service
AE2-255Molecreek 345 kVEngineering & Procurement
AE2-261Kincaid-Pana 345 kVActive
AE2-262Moshannon-Milesburg 230 kVEngineering & Procurement
AE2-263Moshannon-Milesburg 230 kV IIEngineering & Procurement
AE2-267Woodsdale 345 kVEngineering & Procurement
AE2-276Sullivan 345kVEngineering & Procurement
AE2-281Powerton-Nevada 345 kVEngineering & Procurement
AE2-282East Fayette 138 kVIn Service
AE2-285Maysville 69 kVEngineering & Procurement
AE2-297Madison-Tanners Creek 138 kVIn Service
AE2-298Cavett Switch - West Van Wert 69 kVEngineering & Procurement
AE2-305Givens-Mechanicsburg 138 kVEngineering & Procurement
AE2-306Gunn Road 345 kVUnder Construction
AE2-309Carlos Junction-Lonaconing 34.5 kVIn Service
AE2-315Yankee Tap 69 kVIn Service
AE2-318Ford-Cedarville 138 kVSuspended
AE2-321Belvidere-Marengo 138 kVActive
AE2-322Mark Center 69 kVUnder Construction
AE2-323Twin Branch-Guardian 138 kVUnder Construction
AE2-325Valley 138 kVActive
AE2-339Avon 138 kVEngineering & Procurement
AE2-341Sandwich-Plano 138 kVActive
AE2-342Woodstock 69 kVEngineering & Procurement
AE2-343Andover (Maysville) 69 kV IIUnder Construction
AF1-006Fairview East 34.5 kVIn Service
AF1-007Indian River 230 kV ISuspended
AF1-022Lake Lynn-Uniontown 25 kVIn Service
AF1-030Sandwich-Plano 138 kVActive
AF1-038Sewellton Jct-Webbs Crossroads 69 kVEngineering & Procurement
AF1-045Cedarville-Ford 138 kVSuspended
AF1-050Summer Shade - Green County 161 kVEngineering & Procurement
AF1-053Givens-Mechanicsburg 138 kVEngineering & Procurement
AF1-054Givens-Mechanicsburg 138 kVEngineering & Procurement
AF1-062Jug Street 138 kVEngineering & Procurement
AF1-064Weston 69 kVUnder Construction
AF1-078East Sidney-Quincy 138 kVIn Service
AF1-083Green County-Saloma 161 kVEngineering & Procurement
AF1-084Hartford-Almena 69 kVEngineering & Procurement
AF1-086Madera-Westover South 115 kVUnder Construction
AF1-088Sullivan 345 kVActive
AF1-090Kincaid-PanaEngineering & Procurement
AF1-091Varner - Sowers 138 kVEngineering & Procurement
AF1-092Huntington Jct. 138 kVSuspended
AF1-093Henderson-Stoneboro 69 kVEngineering & Procurement
AF1-094Union City-Cambridge Springs 34.5 kVEngineering & Procurement
AF1-098Four Mile Jct-Corry East 115 kVEngineering & Procurement
AF1-118Sorenson-Desoto 345 kVEngineering & Procurement
AF1-119Keystone-Desoto 345 kVEngineering & Procurement
AF1-120East Fayette 2 138 kVIn Service
AF1-122Cardington-Liberty 69 kVSuspended
AF1-134Philipsburg-Madera 34.5 kVEngineering & Procurement
AF1-136Warfordsburg-Purcell Junction 34.5 kVEngineering & Procurement
AF1-140Claysburg 23 kVEngineering & Procurement
AF1-147Poland Rd-Runway DP 230kVUnder Construction
AF1-153Motion-Ridgeway 46 kVSuspended
AF1-158Edison-Gravel Pit 138 kVIn Service
AF1-161Valley 138 kVActive
AF1-176Corey 138 kVActive
AF1-202Keystone-Desoto 345 kVUnder Construction
AF1-203Patton Rd-Summer Shade 69 kVIn Service
AF1-204Eugene 345 kVActive
AF1-205Napoleon Muni 138 kVSuspended
AF1-206East Fayette 138 kVEngineering & Procurement
AF1-207Reynolds-Olive #1 345 kVEngineering & Procurement
AF1-215Olive-Reynolds 345 kVIn Service
AF1-223Keystone-Desoto 345 kVUnder Construction
AF1-227Marysville – Gunn Road 345 kVIn Service
AF1-228Beatty-Greene 345 kVEngineering & Procurement
AF1-229Galion-South Berwick 345 kVEngineering & Procurement
AF1-233Flemingsburg – Spurlock 138kVActive
AF1-249Nickel 12.47 kVIn Service
AF1-254Milnor-Huyetts 34.5 kVUnder Construction
AF1-262Upper Pittsgrove 12 kVIn Service
AF1-264Runnemede 13 kVIn Service
AF1-268Desoto-Jay 138 kVEngineering & Procurement
AF1-272Lucerne 115 kVEngineering & Procurement
AF1-275Cole 345 kVEngineering & Procurement
AF1-282Stuart-Clinton 345 kVEngineering & Procurement
AF1-283Stuart-Clinton 345 kVEngineering & Procurement
AF1-285Gunn Road 345 kVUnder Construction
AF1-290Feagans Mill-Millville 138 kVIn Service
AF1-291ABartonsville-Meadow Brook 138 kVIn Service
AF1-296Garden Plain 138 kVActive
AF1-299Otter Point 34.5 kV IIn Service
AF1-300Otter Point 34.5 kV IIIn Service
AF1-302Brookville-Squab Hollow 138 kVEngineering & Procurement
AF1-320Merrill Creek 115 kVEngineering & Procurement
AF1-322Meadow Lake 345 kVEngineering & Procurement
AF1-331Twombley RoadEngineering & Procurement
AF2-004Beaver 345 kVEngineering & Procurement
AF2-005Beaver 138 kVEngineering & Procurement
AF2-008Sullivan 345 kVActive
AF2-014Maddox Creek 345 kVEngineering & Procurement
AF2-039Shawville-Clearfield 34.5 kVEngineering & Procurement
AF2-041Nelson-Electric Junction 345 kVActive
AF2-068Jay 138 kVActive
AF2-069Crescent Ridge 138 kVActive
AF2-075Bartonsville-Meadow Brook 138 kV IIIIn Service
AF2-078Reynolds-Olive #1 345 kVEngineering & Procurement
AF2-083Kenzie Creek-Stone Lake 69 kVUnder Construction
AF2-088Shawville-Clearfield 34.5 kV IIEngineering & Procurement
AF2-095Davis Creek 138 kVActive
AF2-103Haviland 138 kVIn Service
AF2-111North Clark-Spurlock 345 kVActive
AF2-122Kirk 138 kVUnder Construction
AF2-126Weston 69 kV IIActive
AF2-130Cobalt Corners 34.5 kVIn Service
AF2-132Reynolds-Olive #1 345 kVUnder Construction
AF2-133Reynolds-Olive #2 345 kVUnder Construction
AF2-134Olive-Reynolds #2 345 kVIn Service
AF2-138Flanders-West Wharton 34.5 kVIn Service
AF2-139Gilbert-Warren Glen 34.5 kVIn Service
AF2-142Nevada 345 kVActive
AF2-143Powerton-Nevada 345 kVActive
AF2-149Sharp Road 69 kVEngineering & Procurement
AF2-150Galion 138 kVUnder Construction
AF2-162Keystone-Desoto 345 kVEngineering & Procurement
AF2-173Desoto 345 kVActive
AF2-177Sorenson-DeSoto #2 345 kVActive
AF2-187Brookside-Cloverdale 138 kVEngineering & Procurement
AF2-192Frenchtown Solar-West Flemington 34.5 kVSuspended
AF2-199Nelson-Electric Junction 345 kVActive
AF2-200Nelson-Electric Junction 345 kVActive
AF2-205Olive-Reynolds #2 345 kVEngineering & Procurement
AF2-224Allen 345 kVEngineering & Procurement
AF2-225McLean 345 kVActive
AF2-229Roxbury 23 kVEngineering & Procurement
AF2-235Titusville-Oil Creek 34.5 kVWithdrawn
AF2-238Mansfield-South Troy 34.5 kVEngineering & Procurement
AF2-247Bustleton 13.2 kVIn Service
AF2-250Edgewood 12 kV IIIIn Service
AF2-252Blue Mound 345 kVEngineering & Procurement
AF2-291Sporn South-Leon 138 kVEngineering & Procurement
AF2-298Crown-New Lebanon 69 kVEngineering & Procurement
AF2-325Jacktown 12 kVEngineering & Procurement
AF2-335Delaware-Royerton 138 kVActive
AF2-350Kensington 138 kVActive
AF2-352Blue Mound 345 kVEngineering & Procurement
AF2-354Washington 34.5 kV IIEngineering & Procurement
AF2-356Albright-Mt. Zion 138 kVUnder Construction
AF2-359Olive-University Park 345 kVEngineering & Procurement
AF2-366Crego Rd 138 kVEngineering & Procurement
AF2-370Delaware-Royerton 138 kVActive
AF2-375Ebersole-Fostoria 138 kVEngineering & Procurement
AF2-376Timber Switch 138 kVActive
AF2-377Logtown 138 kVEngineering & Procurement
AF2-378Cambridge 12 kVEngineering & Procurement
AF2-379Princess Anne 25 kVUnder Construction
AF2-383Tolna 115 kVWithdrawn
AF2-388Keystone-Desoto 345 kVActive
AF2-389Kenzie Creek-Stone Lake 69 kVWithdrawn
AF2-392Nelson-Dixon 138 kVActive
AF2-396Stinger 138 kVActive
AF2-440Hillsboro-Middleboro 138 kVEngineering & Procurement
AG1-017Jay 138 kVUnder Construction
AG1-024Centerburg 138 kVEngineering & Procurement
AG1-034Centerburg 138 kVEngineering & Procurement
AG1-039Galion 138 kV IIUnder Construction
AG1-040Morgan Street-Mount Hope 34.5 kVEngineering & Procurement
AG1-047Jay 138 kVEngineering & Procurement
AG1-054Potter-Harlan 69 kVEngineering & Procurement
AG1-100Venango-Saegertown 34.5 kVEngineering & Procurement
AG1-107Hillsboro-Middleboro 138 kVEngineering & Procurement
AG1-109Valley 138 kVActive
AG1-118Sugar Grove-Waterman 138kVActive
AG1-125Marysville-Flatlick 765 kVEngineering & Procurement
AG1-126Marysville-Flatlick 765 kVEngineering & Procurement
AG1-127Crego Rd 138 kVActive
AG1-188Manitou-Oyster Creek 34.5 kVEngineering & Procurement
AG1-189Oyster Creek-Bamber Lake 34.5Engineering & Procurement
AG1-191Chester-Pohatcong Mountain 34.5 kVPartially in Service - Under Construction
AG1-193Utica Junction 34.5 kVSuspended
AG1-197Morgan Street-Cochranton 34.5 kVSuspended
AG1-198Union City 34.5 kVUnder Construction
AG1-223Larrabee-Allaire 34.5 kVUnder Construction
AG1-226Dequine-Eugene 345 kVActive
AG1-232Magley 138 kVEngineering & Procurement
AG1-236Lanesville-Brokaw 345 kVActive
AG1-237Dequine-Eugene 345 kVEngineering & Procurement
AG1-254Salem-Woodstown 69 kVEngineering & Procurement
AG1-281Claysburg-HCR Tap 46 kVEngineering & Procurement
AG1-301Miller REC-Warrior Ridge 46 kVEngineering & Procurement
AG1-302Olive-Reynolds #1 345 kVUnder Construction
AG1-320Glendale-Stephensburg 69 kVActive
AG1-323Blue Jacket 138 kVActive
AG1-324Jay-Desoto 138 kVEngineering & Procurement
AG1-348Pequest River-Washington 34.5 kVIn Service
AG1-349Olive-Reynolds #2 345 kVEngineering & Procurement
AG1-363Black Oak-Hatfield 500 kVEngineering & Procurement
AG1-365Allen 345 kVEngineering & Procurement
AG1-366Allen 345 kVEngineering & Procurement
AG1-367DeSoto 345 kVActive
AG1-368Tillman 138 kVEngineering & Procurement
AG1-369Logtown 138 kVEngineering & Procurement
AG1-374Blue Mound 345 kVActive
AG1-375Sorenson-Desoto 345 kVActive
AG1-386Smith-Francis Junction 25 kVIn Service
AG1-397Walston 12 kVWithdrawn
AG1-410Maddox Creek-RP Mone 345 kVActive
AG1-411Maddox Creek-RP Mone 345 kVActive
AG1-414Mississinewa 138 kVEngineering & Procurement
AG1-433Keystone-DeSoto 345 kVActive
AG1-436Olive-University Park 345 kVActive
AG1-447Olive-University Park 345 kVActive
AG1-460Kincaid-Pana 345 kVActive
AG1-462Cordova 345 kVActive
AG1-478Wilmington 34.5 kVEngineering & Procurement
AG1-480Shawnee 34.5 kVEngineering & Procurement
AG1-482Hamilton 115 kVWithdrawn
AG1-495Gilbert-Rocktown 34.5 kVEngineering & Procurement
AG1-499Lambs 12.47 kVUnder Construction
AG1-500Beaver 345 kVEngineering & Procurement
AG1-501Beaver 138 kVEngineering & Procurement
AG1-554South Kenton 138 kVEngineering & Procurement
AG1-555Dequine 345 kVEngineering & Procurement
AG2-014Meadow Lake 345 kVActive
AG2-029Forest G. Hipple-Collingwood 345 kVActive
AG2-057Cardington-Liberty 69 kV IIActive
AG2-063North Hampton 69 kVActive
AG2-072Rockport 765 kVActive
AG2-085Delaware-Royerton 138 kVActive
AG2-104Marysville-Flatlick 765 kVActive
AG2-106Marysville-Flatlick 765 kVActive
AG2-107Marysville-Flatlick 765 kVActive
AG2-109Fitchville-New London 69 kVActive
AG2-114Dresden-Pontiac Midpoint 345 kVActive
AG2-119Galion-Roberts South 138 kV IIActive
AG2-125Camden-Crystal 69 kVActive
AG2-126Eugene 345 kVActive
AG2-149Galion-South Berwick 345 kVActive
AG2-159Williamstown 69 kVActive
AG2-162Jefferson-Greentown 765 kVActive
AG2-163Dequine-Eugene 345 kVActive
AG2-164Jefferson-Greentown 765 kVActive
AG2-165Dumont-Greentown 765 kVActive
AG2-191Mississinewa 138 kVActive
AG2-192Mississinewa 138 kVActive
AG2-212Dumont-Greentown 765 kVActive
AG2-216East Sidney-Quincy 138 kVActive
AG2-219Jefferson-Greentown 765 kVActive
AG2-230Dumont 345 kVActive
AG2-245Olive - Reynolds #1 345 kVActive
AG2-298Sulphur Creek-Loretto 69 kVActive
AG2-328Dumont - Greentown 765 kVActive
AG2-329S Berwick - Galion 345 kVActive
AG2-330Dumont - Greentown 765 kVActive
AG2-331Jefferson-Greentown 765 kVActive
AG2-332East Elkhart – Elcona Tap 138 kVActive
AG2-343Eugene - Dequine 345 kVActive
AG2-344Dequine 345 bkVActive
AG2-345Eugene - Dequine 345 kVActive
AG2-363Powerton 345 kVActive
AG2-364Powerton 345 kVActive
AG2-370Tillman 138 kVActive
AG2-378North Hampton – Medway 69 kVActive
AG2-385North Hampton 69 kVActive
AG2-400Allen 345 kVActive
AG2-401Losantville 345 kVActive
AG2-402Allen 345 kVActive
AG2-405Continental 69 kVActive
AG2-406Payne 69 kVActive
AG2-408Allen 345 kVActive
AG2-424Magnolia - Summersville 69 kVActive
AG2-444Bixby - Biers Run 345 kVActive
AG2-449Jefferson-Greentown 765 kVActive
AG2-453Lasalle - Plano 345 kVActive
AG2-487Madison - Tanners Creek 138 kVActive
AG2-491Meadow Lake 345 kVActive
AG2-492Meadow Lake 345 kVActive
AG2-515Midway 345 kV IIIActive
AG2-516Pecatonica 138kVActive
AG2-519Royerton - Desoto 138 kVActive
AG2-524LaSalle Station - Mazon 138 kVActive
AG2-548Corwin - Elk 138 kVActive
AG2-550Bluff Point - Randolph 138 kVActive
AG2-551Bluff Point - Randolph 138 kVActive
AG2-562Elderberry 345 kVActive
AG2-564Sulphur Springs 138 kVActive
AG2-575Crego Rd. 138 kVActive
AG2-582Flint Run 500 kVActive
AG2-585Kensington 138kVActive
AG2-589Ravenswood - Hemlock 69 kVActive
AG2-637Randolph - Hodgin 138 kVActive
AG2-660Nelson-Electric Junction 345 kVActive
AG2-665Corwin - Elk 138 kVActive
AH1-044Nelson - Electric Junction 345 kVActive
AH1-047Marengo - Belvidere 138 kVActive
AH1-055Kyger Creek - Don Marquis 345 kVActive
AH1-059Sharp Road 69 kVActive
AH1-060Cardington-Liberty 69 kV IIIActive
AH1-069Jerome – Mohicanville 69 kVActive
AH1-070Jerome – Mohicanville 69 kVActive
AH1-075North Waldo - Wild Creek 138 kVActive
AH1-146White Rock - Wayne 345 kVActive
AH1-147White Rock - Wayne 345 kVActive
AH1-150Nelson-Electric Junction 345 kVActive
AH1-151Nelson-Electric Junction 345 kVActive
AH1-153Dumont 345 kVActive
AH1-196Prairie 345 kVActive
AH1-234Wempletown - Paddock 345 kVActive
AH1-281Bluegrass Parkway Tap - Woodlawn 69 kVActive
AH1-282Galion - Ohio Central 345 kVActive
AH1-285Sandwich 138 kVActive
AH1-292Sullivan 345 kVActive
AH1-298Meridian 345 kVActive
AH1-302Olive - Reynolds 345 kVActive
AH1-304Delaware-Van Buren 138 kVActive
AH1-305Olive - Reynolds 345 kVActive
AH1-306Mississinewa-Gaston 138 kVActive
AH1-308Pennville - Adams 138 kVActive
AH1-309Kenzie Creek-Colby 138 kVActive
AH1-327Hardin Switch 345 kVActive
AH1-328Blue Jacket - Kirby 138 kVActive
AH1-337Randolph - Hodgin 138 kVActive
AH1-338McGirr Rd - Ritchie Road 138kVActive
AH1-339West Crawford 69 kVActive
AH1-341Stillman - Dixon 138KVActive
AH1-391Olive 138 kVActive
AH1-392Gravel Pit-Kankakee 138 kVActive
AH1-482Olive - Reynolds #2 345 kVActive
AH1-537Pierce - Kyger Creek 345 kVActive
AH1-539South Kenton 138 kVActive
AH1-541Chestnut 345 kVActive
AH1-542Crissinger-Kirby 138kVActive
AH1-543Mulberry – Tazewell 345 kVActive
AH1-567University Park 138 kVActive
AH1-661Cannelville 12.47 kVActive
AH1-664Goddard-Plumville 138 kVActive
AH1-665Goddard-Plumsville 138 kV IIActive
AH1-666Flemingsburg - Spurlock 138 kVActive
AH1-669Circleville-Biers Run 138 kVActive
AH1-670Blue Mound-Chestnut 345 kVActive
AH1-686Hanging Rock 765 kVActive
AH1-690Bay Shore - Lallendorf 345 kVActive
AH1-698Braidwood 345 kVActive
AH1-702Byron 345 kVActive
AH1-704Hannibal 138 kVActive
AH1-711Lemoyne 345 kVActive
AH1-714Lasalle 345 kVActive
AH1-718Nelson 345 kVActive
AH1-719Beverly 345 kVActive
AH1-735Richland 138 kVActive
U2-030Four Mile Ridge Wind 138kVIn Service
U2-072East Lima-Marysville 345kVIn Service
U2-073Frostburg 138kV IIIn Service
V1-011Haviland 138kVIn Service
V3-007Desoto-Tanners Creek #1 345kVIn Service
V4-067Cates Road Egg Harbor Township 12kVDeactivated
V4-073Yankee 12.5kVIn Service
W1-003Oak HallIn Service
W1-004Oak HallIn Service
W1-005Oak HallIn Service
W1-006Oak HallIn Service
W1-056Ada-Dunkirk 69kVIn Service
W1-130Vine Road 12kVIn Service
W2-030Egg Harbor TownshipIn Service
W2-048Brokaw-LanesvilleIn Service
W3-077Broadway-Stewartsville 34.5kVIn Service
W4-005Blue Mound-LathamIn Service
X1-042WatervlietIn Service
X2-022Brokaw-LanesvilleIn Service
X2-052Dumont-Olive 345kVIn Service
X3-005Wildwood 12kVIn Service
X3-066Church Hill 69kVIn Service
Y1-079Wye Mills 69kVIn Service
Y1-080Dorchester 12kVIn Service
Y3-023Country Side 12kVIn Service
Y3-024Bluff Point 12kVIn Service
Y3-058Rockawalkin 69kVIn Service
Z2-076Worcester South 25kVIn Service
Z2-077Worcester North 25kVIn Service
Z2-087Pontiac MidPoint-Brokaw 345kVIn Service
Z2-115Deer Creek 12.47kVIn Service
Z2-116Twin Branch 12.47kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)Identified Impacts

No cost allocated AFS Tie Line reinforcements were identified for this project in the Phase I System Impact Study load flow analysis.


System Reinforcement
Type
Load Flow
TO
METC
RTEP ID / TO ID
(Pending) / METC_TC1_16078
Title
Perform sag mitigation on Allen Junction - Morocco 345kV line. New ratings will be 1861/2124 MVA.
Description
Perform sag mitigation on Allen Junction - Morocco 345kV line. New ratings will be 1861/2124 MVA.
Total Cost ($USD)
$625,000
Allocated Cost ($USD)
$0
Time Estimate
18 Months

Contingent

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 may need this upgrade in-service to be deliverable to the PJM system. If AH1-272 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
02ALLEN-18MOROCCO 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ITCT
RTEP ID / TO ID
(Pending) / ITCT_TC1_15164
Title
Reconductor ITCT section of Lallendorf-Monroe line. Post upgrade ratings will be 1677/2124.
Description
Reconductor ITCT section of Lallendorf-Monroe line. Post upgrade ratings will be 1677/2124.
Total Cost ($USD)
$43,500,000
Allocated Cost ($USD)
$0
Time Estimate
36 Months

Contingent

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 may need this upgrade in-service to be deliverable to the PJM system. If AH1-272 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
02LALLENDORF-19MON12 345.0 kV Ckt 1 line(Any)

New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with potential Affected System impacts. PJM initiates coordination with each Affected System Operator by providing a list of New Service Requests in the Cycle with potential impacts to their respective system. If the Affected System Operator indicates an Affected System Study is required, PJM will notify the Project Developer or Eligible Customer of the need for an Affected System Study. See below if any Affected System Operator requires a study for this project:

Midcontinent Independent System Operator, Inc. (MISO)Study Pending
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

Based on the Phase I analysis results, this project may have a cost responsibility for the following System Reinforcements:

AH1-272 System Reinforcements:
TORTEP IDTitleAllocated Cost ($USD)
AEP(Pending) / AEP-TC2-1865105TWIN B 345.0 kV to 05MERIDN 345.0 kV ckt 1 - Sag Study$11,224
Grand Total:$11,224

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18651
Title
05TWIN B 345.0 kV to 05MERIDN 345.0 kV ckt 1 - Sag Study
Description
Perform a sag study and mitigate the sag de-rated 1275 ACSR/PE 54/19 conductor sections (~12.2 miles).
Total Cost ($USD)
$61,000
Allocated Cost ($USD)
$11,224
Time Estimate
36 to 48 Months

Contributor

FacilityContingency
05MERIDN-05TWIN B 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-165
7.8 MW12.2%$7,452
AG2-212
7.8 MW12.2%$7,452
AG2-230
9.5 MW14.9%$9,086
AG2-245
9.6 MW15.2%$9,248
AG2-328
7.8 MW12.2%$7,452
AH1-153
9.5 MW14.9%$9,086
AH1-272
11.7 MW18.4%$11,224

System Reinforcement: b4000.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.1
Title
Add two 765 kV breakers at Amos Substation to expand the breaker and a half scheme to accommodate the new Amos-Welton Spring 765 kV line (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-272 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-272 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.2
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.2
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - AEP Section of the line is 30 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-272 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-272 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)

System Reinforcement: b4000.3
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.3
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - APS/FE Section of the line is 145 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-272 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-272 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.4
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.4
Title
Construct a new 765 kV switchyard - Welton Spring (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-272 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-272 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.5
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.5
Title
Install four 250 MVAR shunt capacitors, and a +/-500 MVAR STATCOM at Welton Spring 765 kV substation
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-272 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-272 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.7
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.7
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line - in DVP local area/Millville to Lovettsville section, roughly 10.5 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-272 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-272 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)

System Reinforcement: b4000.8
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.8
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (DVP local area to Rocky Point, roughly 4.8 miles)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-272 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-272 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)

System Reinforcement: b4000.9
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.9
Title
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard (Projected ISD 6/1/2029)
Description
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard. Loop in the Doubs-Goose Creek 500 kV line, the Doubs-Aspen 500 kV line, and the Woodside-Goose Creek 500 kV line. Install two 765/500 kV transformer at Rocky Point substation. 765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-272 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-272 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.11
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.11
Title
Expand Black Oak Substation & Loop in the 502 Jct-Woodside 500 kV line (Projected ISD 6/1/2029)
Description
Expand Black Oak Substation to accommodate the connection of the 502 Jct-Woodside 500 kV line and loop the 502 Jct-Woodside 500 kV line into the Black Oak substation by constructing ~0.85 miles of new 500 kV line into and out of Black Oak 500 kV substation
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-272 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-272 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)

System Reinforcement: b4000.10
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.10
Title
Install four 250 MVAR cap banks (two on 765 and two on 500 kV side) and a +/-500 MVAR STATCOM on the 765 kV Rocky Point yard
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-272 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-272 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)

System Reinforcement: n9322.0
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
n9322.0 / TE-AG1-S-0012a
Title
Replace Four (4) disconnect switches, four (4) breaker leads, and one (1) meter, and reconductor two (2) transmission line drops on the Morocco 345 kV line terminal at Allen Junction.
Description
Replace (4) disconnect switches at Allen Junction Replace (4) breaker leads at Allen Junction Reconductor (2) TL Drops at Allen Junction Replace (1) meter at Allen Junction New FE Ratings 1868 / 2249 / 2586 MVA SN/SE/SLD
Total Cost ($USD)
$1,408,997
Allocated Cost ($USD)
$0
Time Estimate
38 Months

Contingent

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 may need this upgrade in-service to be deliverable to the PJM system. If AH1-272 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
02ALLEN-18MOROCCO 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.l
Title
Upgrade (5) 4.00 SPS AL PIPE 61 sub conductors at BAYSHORE on the Bayshore - Davis Besse 345kV line
Description
Upgrade (5) 4.00 SPS AL PIPE 61 sub conductors at BAYSHORE on the Bayshore - Davis Besse 345kV line
Total Cost ($USD)
$246,545
Allocated Cost ($USD)
$0
Time Estimate
14 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.m
Title
Upgrade (7) 3000A disconnect switches (D34545:N,S, D3454:W,E, A34673, D34561C, and 34623)and (2) B34545 impedance relays at Bayshore and Davis Besse
Description
Upgrade (7) 3000A disconnect switches (D34545:N,S, D3454:W,E, A34673, D34561C, and 34623)and (2) B34545 impedance relays at Bayshore and Davis Besse
Total Cost ($USD)
$3,544,138
Allocated Cost ($USD)
$0
Time Estimate
42 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.a
Title
Upgrade (4) 1024.5 ACAR 24/13 sub conductors at Davis Besse
Description
Upgrade (4) 1024.5 ACAR 24/13 sub conductors at Davis Besse
Total Cost ($USD)
$1,099,401
Allocated Cost ($USD)
$0
Time Estimate
14 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.b
Title
Upgrade (3) 345kV bus and line side disconnect switches at Davis Besse substation at Davis Besse
Description
Upgrade (3) 345kV bus and line side disconnect switches at Davis Besse substation at Davis Besse
Total Cost ($USD)
$1,324,127
Allocated Cost ($USD)
$0
Time Estimate
37 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.c
Title
Upgrade 345kV 1033.5 AAC 61 sub conductors at Davis Besse substation at Davis Besse
Description
Upgrade 345kV 1033.5 AAC 61 sub conductors at Davis Besse substation at Davis Besse
Total Cost ($USD)
$257,762
Allocated Cost ($USD)
$0
Time Estimate
13 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.d
Title
Reconductor (possible rebuild) 345kV 20.75 miles of transmission line and line drops at both remote ends
Description
Reconductor (possible rebuild) 345kV 20.75 miles of transmission line and line drops at both remote ends using dual (2) 1590 54/19 "Falcon" ACSS
Total Cost ($USD)
$121,594,776
Allocated Cost ($USD)
$0
Time Estimate
71 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.e
Title
Upgrade 345kV 3500 SAC 127 sub conductor at Davis Besse
Description
Upgrade 345kV 3500 SAC 127 sub conductor at Davis Besse
Total Cost ($USD)
$257,762
Allocated Cost ($USD)
$0
Time Estimate
13 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.f
Title
Upgrade (2) 345kV Wave Traps at Bayshore and (2) at Davis Besse
Description
Upgrade (2) 345kV Wave Traps at Bayshore and (2) at Davis Besse
Total Cost ($USD)
$1,215,694
Allocated Cost ($USD)
$0
Time Estimate
22 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.g
Title
Upgrade (2) 345kV circuit breakers at Bayshore and (2) at Davis Besse
Description
Upgrade (2) 345kV circuit breakers at Bayshore and (2) at Davis Besse
Total Cost ($USD)
$7,786,806
Allocated Cost ($USD)
$0
Time Estimate
60 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.h
Title
Upgrade (8) 1590 AAC 61 sub conductor at BAYSHORE
Description
Upgrade (8) 1590 AAC 61 sub conductor at BAYSHORE
Total Cost ($USD)
$211,119
Allocated Cost ($USD)
$0
Time Estimate
13 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.i
Title
Upgrade B34544 CT at BAYSHORE
Description
Upgrade B34544 CT at BAYSHORE
Total Cost ($USD)
$712,356
Allocated Cost ($USD)
$0
Time Estimate
20 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.j
Title
Upgrade (1) 1590 ACSR 45/7 sub conductor at Davis Besse
Description
Upgrade (1) 1590 ACSR 45/7 sub conductor at Davis Besse
Total Cost ($USD)
$393,871
Allocated Cost ($USD)
$0
Time Estimate
13 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.k
Title
Upgrade the B34545 and 34562 (4) Meter and (2) Relay Thermals at Bayshore and Davis Besse
Description
Upgrade the B34545 and 34562 (4) Meter and (2) Relay Thermals at Bayshore and Davis Besse
Total Cost ($USD)
$998,835
Allocated Cost ($USD)
$0
Time Estimate
19 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-017
Title
Upgrade (2) 2000A bus and line side disconnect switches at Bayshore
Description
Upgrade (2) 2000A bus and line side disconnect switches at Bayshore
Total Cost ($USD)
$948,616
Allocated Cost ($USD)
$0
Time Estimate
36 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02BAY SH-AH1-690 TP 345.0 kV Ckt 2 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-004.a
Title
Upgrade D120 and D125 disconnect switches at Beaver substation
Description
Upgrade D120 and D125 disconnect switches at Beaver substation
Total Cost ($USD)
$929,516
Allocated Cost ($USD)
$0
Time Estimate
22 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02CARLIL 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-004.b
Title
Upgrade (1) 3000 SAC 169 line drop at Beaver
Description
Upgrade (1) 3000 SAC 169 line drop at Beaver
Total Cost ($USD)
$263,169
Allocated Cost ($USD)
$0
Time Estimate
12 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02CARLIL 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-004.c
Title
Reconductor (possible rebuild) 18.22 miles of 954 ACSR 48/7 transmission line and (3) line drops at Beaver on the Beaver - Carlisle Ckt 1 345 kV
Description
Reconductor (possible rebuild) 18.22 miles of 954 ACSR 48/7 transmission line and (3) line drops at Beaver on the Beaver - Carlisle Ckt 1 345 kV using dual (2) 795 26/7 "Drake ACSS
Total Cost ($USD)
$109,211,408
Allocated Cost ($USD)
$0
Time Estimate
63 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02CARLIL 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-004.d
Title
Upgrade (1) 3500 SAC 127 D120-to-B121 breaker lead at Beaver
Description
Upgrade (1) 3500 SAC 127 D120-to-B121 breaker lead at Beaver
Total Cost ($USD)
$265,209
Allocated Cost ($USD)
$0
Time Estimate
12 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02CARLIL 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-014.a
Title
Reconductor (possible rebuild) 29.61 miles of transmission line and line drops ( line drops at Hayes) on the Beaver - Hayes Ckt 1 345 kV line
Description
Reconductor (possible rebuild) 29.61 miles of transmission line and line drops ( line drops at Hayes) on the Beaver - Hayes Ckt 1 345 kV line using dual (2) 954 54/7 "Cardinal" ACSS
Total Cost ($USD)
$175,902,477
Allocated Cost ($USD)
$0
Time Estimate
90 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-014.b
Title
Upgrade 3500 SAC (2) B3 and (2) B6 breaker leads at Hayes
Description
Upgrade 3500 SAC (2) B3 and (2) B6 breaker leads at Hayes
Total Cost ($USD)
$152,573
Allocated Cost ($USD)
$0
Time Estimate
18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-014.c
Title
Upgrade (2) L3000 wavetraps at Beaver and Hayes
Description
Upgrade (2) L3000 wavetraps at Beaver and Hayes
Total Cost ($USD)
$729,124
Allocated Cost ($USD)
$0
Time Estimate
18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-014.d
Title
Upgrade (4) circuit breakers at Beaver and Hayes (B88, B115, B3, B6)
Description
Upgrade (4) circuit breakers at Beaver and Hayes (B88, B115, B3, B6)
Total Cost ($USD)
$7,937,520
Allocated Cost ($USD)
$0
Time Estimate
60 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-014.e
Title
Upgrade the 1590 AAC (2) B88 and (2) B15 breaker leads at Beaver
Description
Upgrade the 1590 AAC (2) B88 and (2) B15 breaker leads at Beaver
Total Cost ($USD)
$152,573
Allocated Cost ($USD)
$0
Time Estimate
18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-014.f
Title
Upgrade the B6 CT at Hayes
Description
Upgrade the B6 CT at Hayes
Total Cost ($USD)
$727,300
Allocated Cost ($USD)
$0
Time Estimate
20 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-014.g
Title
Upgrade (3) 1590 AAC line drops at Beaver (line drop to WT, Phase 1&3 "B-B", and SHARED NODE TO: WT, PH 2 / 5" AL, PH 1&3)
Description
Upgrade (3) 1590 AAC line drops at Beaver (line drop to WT, Phase 1&3 "B-B", and SHARED NODE TO: WT, PH 2 / 5" AL, PH 1&3) using dual (2) 954 54/7 "Cardinal" ACSS
Total Cost ($USD)
$591,863
Allocated Cost ($USD)
$0
Time Estimate
18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-014.h
Title
Upgrade the B88 and B115 CTs at Beaver
Description
Upgrade the B88 and B115 CTs at Beaver
Total Cost ($USD)
$1,258,596
Allocated Cost ($USD)
$0
Time Estimate
21 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-014.i
Title
Upgrade the 10A B115 relay and B88 meter thermal at Beaver
Description
Upgrade the 10A B115 relay and B88 meter thermal at Beaver
Total Cost ($USD)
$509,895
Allocated Cost ($USD)
$0
Time Estimate
18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-014.j
Title
Upgrade the B88 and B3 impedance relays at Beaver and Hayes
Description
Upgrade the B88 and B3 impedance relays at Beaver and Hayes
Total Cost ($USD)
$1,019,790
Allocated Cost ($USD)
$0
Time Estimate
19 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-014.k
Title
Upgrade (9) 3000A disconnect switches at Beaver and Hayes (D:74,92,93,116,4,5,7,8,11)
Description
Upgrade (9) 3000A disconnect switches at Beaver and Hayes (D:74,92,93,116,4,5,7,8,11)
Total Cost ($USD)
$3,774,791
Allocated Cost ($USD)
$0
Time Estimate
29 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-005.a
Title
Upgrade (3) disconnect switches at Beaver (D:120,166,165)
Description
Upgrade (3) disconnect switches at Beaver (D:120,166,165)
Total Cost ($USD)
$1,350,788
Allocated Cost ($USD)
$0
Time Estimate
37 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-005.b
Title
Upgrade (4) 954 ACSR 45/7 overhead line and line drops at Beaver Substation
Description
Upgrade (4) 954 ACSR 45/7 overhead line and line drops at Beaver Substation
Total Cost ($USD)
$809,465
Allocated Cost ($USD)
$0
Time Estimate
15 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-005c
Title
Upgrade 3500 SAC 127 B161 (2) breaker leads and (1) B121-to-D120 breaker lead at Beaver
Description
Upgrade 3500 SAC 127 B161 (2) breaker leads and (1) B121-to-D120 breaker lead at Beaver
Total Cost ($USD)
$191,109
Allocated Cost ($USD)
$0
Time Estimate
11 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-005.d
Title
Reconductor (possible rebuild) 8.37 miles of 954 ACSR 48/7 transmission line on the Beaver - Lake Avenue Ckt 1 345 kV
Description
Reconductor (possible rebuild) 8.37 miles of 954 ACSR 48/7 transmission line on the Beaver - Lake Avenue Ckt 1 345 kV using dual (2) 954 54/7 "Cardinal" ACSS
Total Cost ($USD)
$50,053,445
Allocated Cost ($USD)
$0
Time Estimate
38 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 1 line(Any)

System Reinforcement: n9227.0
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
n9227.0 / TC1-ATSI-001.b
Title
Upgrade T-line drops, overhead substation conductor and TL reconductor
Description
Reconductor (possible rebuild) of 8.12 miles of dual transmission line and (2) single conductor line drops at Beaver on the Beaver-Lake Ave Ckt 2 345 kV line using triple (3) 1113 54/19 ""Finch"" ACSS"
Total Cost ($USD)
$48,873,856
Allocated Cost ($USD)
$0
Time Estimate
37 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-021.a
Title
Upgrade (4) circuit breakers at Beaver and Lake Ave (B:3,4,216,219)
Description
Upgrade (4) circuit breakers at Beaver and Lake Ave (B:3,4,216,219)
Total Cost ($USD)
$7,786,809
Allocated Cost ($USD)
$0
Time Estimate
56 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-021.b
Title
Upgrade 1590 AAC B3, B4, B216 and B219 breaker leads at Beaver and Lake Ave
Description
Upgrade 1590 AAC B3, B4, B216 and B219 breaker leads at Beaver and Lake Ave
Total Cost ($USD)
$305,540
Allocated Cost ($USD)
$0
Time Estimate
12 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-021.c
Title
Upgrade the (3) B216, B219 and B4 1500 CTs
Description
Upgrade the (3) B216, B219 and B4 1500 CTs
Total Cost ($USD)
$853,850
Allocated Cost ($USD)
$0
Time Estimate
16 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-021.d
Title
Upgrade (3) 1590 line drops at Beaver and Lake Ave
Description
Upgrade (3) 1590 line drops at Beaver and Lake Ave
Total Cost ($USD)
$690,685
Allocated Cost ($USD)
$0
Time Estimate
12 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-021.e
Title
Upgrade the (1) B219 1200 CT to PVD at Beaver
Description
Upgrade the (1) B219 1200 CT to PVD at Beaver
Total Cost ($USD)
$349,952
Allocated Cost ($USD)
$0
Time Estimate
16 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-021.f
Title
Upgrade the (1) B216 relay thermal at Beaver
Description
Upgrade the (1) B216 relay thermal at Beaver
Total Cost ($USD)
$509,895
Allocated Cost ($USD)
$0
Time Estimate
18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-021.g
Title
Upgrade (1) 4.00 SPS.AL PIPE at Beaver
Description
Upgrade (1) 4.00 SPS.AL PIPE at Beaver
Total Cost ($USD)
$178,089
Allocated Cost ($USD)
$0
Time Estimate
12 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-021.h
Title
Upgrade (9) disconnect switches at Beaver and Lake Ave (D: 19,20,21,22, 212,215,217,218,220)
Description
Upgrade (9) disconnect switches at Beaver and Lake Ave (D: 19,20,21,22, 212,215,217,218,220)
Total Cost ($USD)
$3,850,794
Allocated Cost ($USD)
$0
Time Estimate
39 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-021.i
Title
Upgrade the (2) B3 SEL411L impedance relays at Lake Ave
Description
Upgrade the (2) B3 SEL411L impedance relays at Lake Ave
Total Cost ($USD)
$509,895
Allocated Cost ($USD)
$0
Time Estimate
18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-021.j
Title
Upgrade (2) 2.50 SPS.AL PIPE SCCIR at Beaver
Description
Upgrade (2) 2.50 SPS.AL PIPE SCCIR at Beaver
Total Cost ($USD)
$173,391
Allocated Cost ($USD)
$0
Time Estimate
12 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-021.k
Title
Upgrade the (15) B216, B219, B3 and B4 2000 CTs at Beaver and Lake Ave
Description
Upgrade the (15) B216, B219, B3 and B4 2000 CTs at Beaver and Lake Ave
Total Cost ($USD)
$2,701,212
Allocated Cost ($USD)
$0
Time Estimate
17 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-021.l
Title
Upgrade the (2) B216 SEL411L impedance relays at Lake Ave
Description
Upgrade the (2) B216 SEL411L impedance relays at Lake Ave
Total Cost ($USD)
$509,895
Allocated Cost ($USD)
$0
Time Estimate
18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-021.m
Title
Upgrade (8) 5.00 SPS.AL PIPE SCCIR at Beaver
Description
Upgrade (8) 5.00 SPS.AL PIPE SCCIR at Beaver
Total Cost ($USD)
$250,039
Allocated Cost ($USD)
$0
Time Estimate
12 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-020.f
Title
Upgrade (2) B182 impedance relays at Beaver (SEL-321: Z2-BU & Z2-PR)
Description
Upgrade (2) B182 impedance relays at Beaver (SEL-321: Z2-BU & Z2-PR)
Total Cost ($USD)
$509,895
Allocated Cost ($USD)
$0
Time Estimate
19 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-020.g
Title
Upgrade (2) B185 and B182 revenue meter CTs at Beaver
Description
Upgrade (2) B185 and B182 revenue meter CTs at Beaver
Total Cost ($USD)
$1,258,596
Allocated Cost ($USD)
$0
Time Estimate
21 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-020.h
Title
Upgrade the B185 CT to PVD at Beaver
Description
Upgrade the B185 CT to PVD at Beaver
Total Cost ($USD)
$349,952
Allocated Cost ($USD)
$0
Time Estimate
17 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-020.i
Title
Upgrade B182 relay thermal at Beaver
Description
Upgrade B182 relay thermal at Beaver
Total Cost ($USD)
$509,895
Allocated Cost ($USD)
$0
Time Estimate
19 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-020.j
Title
Upgrade (2) B182 impedance relays at Beaver (SEL-321: Z4-BU & Z4-PR)
Description
Upgrade (2) B182 impedance relays at Beaver (SEL-321: Z4-BU & Z4-PR)
Total Cost ($USD)
$509,895
Allocated Cost ($USD)
$0
Time Estimate
19 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-020.a
Title
Upgrade B185 and B182 circuit breakers at Beaver
Description
Upgrade B185 and B182 circuit breakers at Beaver
Total Cost ($USD)
$3,893,404
Allocated Cost ($USD)
$0
Time Estimate
56 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-020.b
Title
Upgrade (4) disconnect switches at Beaver (D186,184,181,183)
Description
Upgrade (4) disconnect switches at Beaver (D186,184,181,183)
Total Cost ($USD)
$1,699,640
Allocated Cost ($USD)
$0
Time Estimate
25 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-020.c
Title
Upgrade 3000 AAC B185 and B185 breaker leads at Beaver
Description
Upgrade 3000 AAC B185 and B185 breaker leads at Beaver
Total Cost ($USD)
$187,449
Allocated Cost ($USD)
$0
Time Estimate
13 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-020.d
Title
Reconductor (possible rebuild) 29.61 miles of transmission line and (4) line drops beginning at Beaver towards Davis Besse on the Beaver - Davis Besse Ckt 1 345 kV line
Description
Reconductor (possible rebuild) 29.61 miles of transmission line and (4) line drops beginning at Beaver towards Davis Besse on the Beaver - Davis Besse Ckt 1 345 kV line using dual (2) 1590 54/19 "Falcon" ACSS
Total Cost ($USD)
$149,403,319
Allocated Cost ($USD)
$0
Time Estimate
82 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-020.e
Title
Upgrade (2) L3000 wavetraps at Beaver
Description
Upgrade (2) L3000 wavetraps at Beaver
Total Cost ($USD)
$620,600
Allocated Cost ($USD)
$0
Time Estimate
18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-006.a
Title
Reconductor (possible rebuild) 30.25 miles of 954 ACSR 48/7 transmission line and line drops (line drops at Davis Besse) on the Davis Besse-Hayes 345 kV line
Description
Reconductor (possible rebuild) 30.25 miles of 954 ACSR 48/7 transmission line and line drops (line drops at Davis Besse) on the Davis Besse-Hayes 345 kV line using dual (2) 1590 54/19 "Falcon" ACSS
Total Cost ($USD)
$179,916,169
Allocated Cost ($USD)
$0
Time Estimate
90 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-006.b
Title
Upgrade 3500 SAC 127 OVERHEAD PIPE to disc sw. 34625 at Davis Besse and B18 breaker leads at Hayes
Description
Upgrade 3500 SAC 127 OVERHEAD PIPE to disc sw. 34625 at Davis Besse and B18 breaker leads at Hayes
Total Cost ($USD)
$284,061
Allocated Cost ($USD)
$0
Time Estimate
18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-006.c
Title
Upgrade (2) Wave Traps at Davis Besse and (2) Wave Traps at Hayes
Description
Upgrade (2) Wave Traps at Davis Besse and (2) Wave Traps at Hayes
Total Cost ($USD)
$1,215,695
Allocated Cost ($USD)
$0
Time Estimate
20 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-006.d
Title
Upgrade (2) B18 & B12 345 kV Ciruit Breakers at Hayes
Description
Upgrade (2) B18 & B12 345 kV Ciruit Breakers at Hayes
Total Cost ($USD)
$3,893,404
Allocated Cost ($USD)
$0
Time Estimate
56 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-006.e
Title
Upgrade (2) B12 and B18 CTs at Hayes
Description
Upgrade (2) B12 and B18 CTs at Hayes
Total Cost ($USD)
$1,258,596
Allocated Cost ($USD)
$0
Time Estimate
21 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-006.f
Title
Upgrade (10) 1590 ACSR sub conductor (B66 and B67 breaker leads, wave trap subconductor, Overheadline-34625) at Davis Besse and B12 breaker leads at Hayes
Description
Upgrade (10) 1590 ACSR sub conductor (B66 and B67 breaker leads, wave trap subconductor, Overheadline-34625) at Davis Besse and B12 breaker leads at Hayes
Total Cost ($USD)
$305,149
Allocated Cost ($USD)
$0
Time Estimate
18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-006.g
Title
Upgrade B66 and B67 circuit breakers at Davis Besse substation
Description
Upgrade B66 and B67 circuit breakers at Davis Besse substation
Total Cost ($USD)
$3,893,404
Allocated Cost ($USD)
$0
Time Estimate
56 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-006.i
Title
Upgrade (2) 9.6 Ohms impedance relays at Hayes and (2) 12.9 Ohms impedance relays at Davis Besse
Description
Upgrade (2) 9.6 Ohms impedance relays at Hayes and (2) 12.9 Ohms impedance relays at Davis Besse
Total Cost ($USD)
$1,019,790
Allocated Cost ($USD)
$0
Time Estimate
19 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-006.h
Title
Upgrade B66 (1) meter and (1) relay thermals and B67 (1) meter thermal at Davis Besse substation
Description
Upgrade B66 (1) meter and (1) relay thermals and B67 (1) meter thermal at Davis Besse substation
Total Cost ($USD)
$852,462
Allocated Cost ($USD)
$0
Time Estimate
19 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-006.j
Title
Upgrade (6) disconnect switches at Davis Besse (D27,28,29,30,34625,37) and (5) disconnect switches at Hayes (D20,19,16,13,14)
Description
Upgrade (6) disconnect switches at Davis Besse (D27,28,29,30,34625,37) and (5) disconnect switches at Hayes (D20,19,16,13,14)
Total Cost ($USD)
$4,525,814
Allocated Cost ($USD)
$0
Time Estimate
31 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-006.k
Title
Upgrade (1) 1590 AACSR Phase A/C line drop at Davis Besse substation and (3) Phase 3 "B-B", Phase 1&2 "C-C", and shared node to wave trap line drops at Hayes
Description
Upgrade (1) 1590 AACSR Phase A/C line drop at Davis Besse substation and (3) Phase 3 "B-B", Phase 1&2 "C-C", and shared node to wave trap line drops at Hayes
Total Cost ($USD)
$855,032
Allocated Cost ($USD)
$0
Time Estimate
18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-015.c
Title
Upgrade (2) 3000A CBs at Davis Besse and (1) 3000A CB at Lemoyne
Description
Upgrade (2) 3000A CBs at Davis Besse and (1) 3000A CB at Lemoyne
Total Cost ($USD)
$5,962,261
Allocated Cost ($USD)
$0
Time Estimate
56 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-02LEMOYN 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-015.d
Title
Upgrade (12) dual 1590 ACSR SCCIR at Davis Besse and Lemoyne
Description
Upgrade (12) dual 1590 ACSR SCCIR at Davis Besse and Lemoyne
Total Cost ($USD)
$2,070,983
Allocated Cost ($USD)
$0
Time Estimate
12 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-02LEMOYN 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-015.e
Title
Upgrade (2) 8.6 Ohm impedance relays at Davis Besse and (2) 7.8 Ohm impedance relays at Lemoyne
Description
Upgrade (2) 8.6 Ohm impedance relays at Davis Besse and (2) 7.8 Ohm impedance relays at Lemoyne
Total Cost ($USD)
$1,019,790
Allocated Cost ($USD)
$0
Time Estimate
18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-02LEMOYN 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-015.f
Title
Upgrade the B34502 CB at Lemoyne
Description
Upgrade the B34502 CB at Lemoyne
Total Cost ($USD)
$2,068,856
Allocated Cost ($USD)
$0
Time Estimate
54 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-02LEMOYN 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-015.g
Title
Upgrade (2) B34501 and B34502 relay thermals at Lemoyne and (3) 34563 relay and meter thermals at Davis Besse
Description
Upgrade (2) B34501 and B34502 relay thermals at Lemoyne and (3) 34563 relay and meter thermals at Davis Besse
Total Cost ($USD)
$2,137,421
Allocated Cost ($USD)
$0
Time Estimate
20 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-02LEMOYN 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-015.h
Title
Upgrade (12) 4.00 SPS.AL PIPE at Lemoyne
Description
Upgrade (12) 4.00 SPS.AL PIPE at Lemoyne
Total Cost ($USD)
$961,300
Allocated Cost ($USD)
$0
Time Estimate
22 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-02LEMOYN 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-015.i
Title
Upgrade (10) 3000A bus and line side disconnect switches at Davis Besse and Lemoyne (34624, A34604, D345:63A,63B,64D,64C,01N,01S,02W,02E)
Description
Upgrade (10) 3000A bus and line side disconnect switches at Davis Besse and Lemoyne (34624, A34604, D345:63A,63B,64D,64C,01N,01S,02W,02E)
Total Cost ($USD)
$3,952,709
Allocated Cost ($USD)
$0
Time Estimate
29 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-02LEMOYN 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-015.a
Title
Reconductor (possible rebuild) 21.68 miles of transmission line and (1) line drop (line drop at Lemoyne) on the Davis Besse - Lemoyne 345 kV
Description
Reconductor (possible rebuild) 21.68 miles of transmission line and (1) line drop (line drop at Lemoyne) on the Davis Besse - Lemoyne 345 kV using dual (2) 1272 54/19 "Pheasant" ACSS
Total Cost ($USD)
$126,131,949
Allocated Cost ($USD)
$0
Time Estimate
73 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-02LEMOYN 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-015.b
Title
Upgrade (4) L300 wavetraps at Davis Besse and Lemoyne
Description
Upgrade (4) L300 wavetraps at Davis Besse and Lemoyne
Total Cost ($USD)
$1,132,675
Allocated Cost ($USD)
$0
Time Estimate
22 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-02LEMOYN 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-008.i
Title
Upgrade (4) 1590 ACSR 45/7 sub conductors at Davis Besse
Description
Upgrade (4) 1590 ACSR 45/7 sub conductors at Davis Besse
Total Cost ($USD)
$756,208
Allocated Cost ($USD)
$0
Time Estimate
13 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-008.j
Title
Upgrade (2) 13.03 Ohm B65 Impedance Relays at Davis Besse
Description
Upgrade (2) 13.03 Ohm B65 Impedance Relays at Davis Besse
Total Cost ($USD)
$509,895
Allocated Cost ($USD)
$0
Time Estimate
18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-008.k
Title
Upgrade (2) 6.65 Ohm B65 Impedance Relays at Davis Besse
Description
Upgrade (2) 6.65 Ohm B65 Impedance Relays at Davis Besse
Total Cost ($USD)
$509,895
Allocated Cost ($USD)
$0
Time Estimate
18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-008.l
Title
Upgrade Circuit Breaker B65 at Davis Besse
Description
Upgrade Circuit Breaker B65 at Davis Besse
Total Cost ($USD)
$2,068,856
Allocated Cost ($USD)
$0
Time Estimate
54 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-008.m
Title
Upgrade (2) B65 Meter Thermals at Davis Besse
Description
Upgrade (2) B65 Meter Thermals at Davis Besse
Total Cost ($USD)
$509,895
Allocated Cost ($USD)
$0
Time Estimate
18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-008.a
Title
Upgrade D41 and D42 disconnect switches at Davis Besse
Description
Upgrade D41 and D42 disconnect switches at Davis Besse
Total Cost ($USD)
$967,716
Allocated Cost ($USD)
$0
Time Estimate
36 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-008.b
Title
Upgrade (1) 1024 ACAR 6E550-52-1 "A" line drop at Davis Besse
Description
Upgrade (1) 1024 ACAR 6E550-52-1 "A" line drop at Davis Besse
Total Cost ($USD)
$263,169
Allocated Cost ($USD)
$0
Time Estimate
12 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-008.c
Title
Reconductor (possible rebuild) 15.6 miles of 954 ACSR 45/7 on the Davis Besse - AC2-103 Tap 345 kV line
Description
Reconductor (possible rebuild) 15.6 miles of 954 ACSR 45/7 on the Davis Besse - AC2-103 Tap 345 kV line using dual (2) 1272 54/19 "Pheasant" ACSS
Total Cost ($USD)
$91,775,258
Allocated Cost ($USD)
$0
Time Estimate
57 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-008.d
Title
Upgrade (2) 3500 SAC 127 line drops at Davis Besse
Description
Upgrade (2) 3500 SAC 127 line drops at Davis Besse
Total Cost ($USD)
$263,169
Allocated Cost ($USD)
$0
Time Estimate
12 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-008.e
Title
Upgrade 3500 SAC B65 breaker leads and subconductor (D42 to wave trap) at Davis Besse
Description
Upgrade 3500 SAC B65 breaker leads and subconductor (D42 to wave trap) at Davis Besse
Total Cost ($USD)
$197,592
Allocated Cost ($USD)
$0
Time Estimate
13 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-008.f
Title
Reconductor (possible rebuild) 18.7 miles of 954 ACSR 48/7 on the Davis Besse - AC2-103 TAP 345kV
Description
Reconductor (possible rebuild) 18.7 miles of 954 ACSR 48/7 on the Davis Besse - AC2-103 TAP 345kV using dual (2) 1272 54/19 "Pheasant" ACSS
Total Cost ($USD)
$111,822,087
Allocated Cost ($USD)
$0
Time Estimate
64 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-008.g
Title
Upgrade (2) Wave Traps at Davis Besse
Description
Upgrade (2) Wave Traps at Davis Besse
Total Cost ($USD)
$620,599
Allocated Cost ($USD)
$0
Time Estimate
20 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-008.h
Title
Upgrade Circuit Breaker 34564 at Davis Besse
Description
Upgrade Circuit Breaker 34564 at Davis Besse
Total Cost ($USD)
$2,068,856
Allocated Cost ($USD)
$0
Time Estimate
54 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement: n9675.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9675.0 / AEPO0035a
Title
Sag Study will be required on ACSR ~ 954 ~ 45/7, 18.3 miles line between South Berwick and Galion .
Description
Sag Study will be required on ACSR ~ 954 ~ 45/7, 18.3 miles line between South Berwick and Galion .The cost is expected to be 73,200.New Ratings after sag study : S/N: 1409 MVA S/E: 1887 MVA.Rebuild/Reconductor, cost : $ 36.6 million
Total Cost ($USD)
$229,320
Allocated Cost ($USD)
$0
Time Estimate
24 to 36 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02GALION-AG2-148 TP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-019
Title
Upgrade phase 2 wave trap at Galion
Description
Upgrade phase 2 wave trap at Galion
Total Cost ($USD)
$620,599
Allocated Cost ($USD)
$0
Time Estimate
18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02GALION-AG2-148 TP 345.0 kV Ckt 1 line(Any)

System Reinforcement: n9676.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9676.0 / AEPO0033a
Title
Sag Study will be required on 19.2 miles line between Fostoria and Lallen [...] tudy : S/N: 1409MVA S/E: 1887MVA.Rebuild/Reconductor, cost : $ 38.4 million
Description
Sag Study will be required on 19.2 miles line between Fostoria and Lallendorf .The cost is expected to be 76,800.New Ratings after sag study : S/N: 1409MVA S/E: 1887MVA.Rebuild/Reconductor, cost : $ 38.4 million
Total Cost ($USD)
$99,840
Allocated Cost ($USD)
$0
Time Estimate
24 to 36 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
02LALLENDORF-05FOSTOR 345.0 kV Ckt 1 line(Any)

System Reinforcement: n9228.0
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
n9228.0 / TC1-ATSI-002.b
Title
Rebuild 6.6 miles of the Lallendorf-Monroe 345 kV line and install OPGW. Replace line drops and wave traps at Lallendorf.
Description
Rebuild approximately 6.6 miles of the Lallendorf-Monroe 345 kV line from Lallendorf to the state line. Transfer and reuse approximately 0.9 miles of existing conductor on the Fostoria Central – Lallendorf 345 kV line to maintain double circuit with Lallendorf – Monroe line. Transfer and reuse approximately 5.7 miles of existing conductor on the Lemoyne – Majestic 345 kV line to maintain double circuit with Lallendorf – Monroe line. At Lallendorf substation, Replace line drops and (2) wave traps on the Monroe terminal.
Total Cost ($USD)
$38,362,639
Allocated Cost ($USD)
$0
Time Estimate
29 Months

Contingent

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 may need this upgrade in-service to be deliverable to the PJM system. If AH1-272 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
02LALLENDORF-19MON12 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18693
Title
Greentown 765 kV to Marysville 765 kV - Greenfield Line
Description
Construct a new greenfield 765kV line from Greentown to Marysville (~160 miles). Install 2 new 765kV breakers at Marysville and 2 new 765kV breakers at Greentown. Install 765kV shunt reactors at both Marysville and Greentown The new 765kV line reduces equipment at Dumont to be replaced to CB A2 and switch A2S2. s3442.26 replaces Dumont 765kV CB A2 and A2S2 "CONTINGENCY 'AEP_P1-2_GREENTOWN TO MARYSVILLE 765_SRT-A' OPEN BRANCH FROM BUS 242928 TO BUS 243207 CKT 1 / 242928 05MARYSV 765 243207 05GRNTWN 765 1 END CONTINGENCY 'AEP_P4_GREENTOWN CB 765_SRT-A' OPEN BRANCH FROM BUS 242928 TO BUS 243207 CKT 1 / 242928 05MARYSV 765 243207 05GRNTWN 765 1 END CONTINGENCY 'AEP_P4_MARYSVILLE CB 765_SRT-A' OPEN BRANCH FROM BUS 242928 TO BUS 243207 CKT 1 / 242928 05MARYSV 765 243207 05GRNTWN 765 1 END"
Total Cost ($USD)
$1,000,000,000
Allocated Cost ($USD)
$0
Time Estimate
72 to 120 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line(Any)
05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer(Any)
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line(Any)

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18686
Title
05MADDOX 345.0 kV to 05E LIMA 345.0 kV ckt 1 - String the 2nd conductor
Description
AEP owned line; string the 2nd conductor (2-bundle 954 ACSS) ~30.28 miles on the double circuit line & six wire, At East Lima station replace sub conductor & relay trip limit and at Maddox Creek replace 5.0 IPS Sch. 40 bus work, sub conductor & relay trip limit
Total Cost ($USD)
$48,000,000
Allocated Cost ($USD)
$0
Time Estimate
24 to 36 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
05E LIMA-05MADDOX 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18626
Title
05FLTLCK 765.0 kV to 05GAVIN_RF 765.0 kV ckt 1 - Replace Equipment
Description
At Flatlick Station replace the following equipment: CB-A, CB-B, GCB A PH. A, GCB A PH. B, GCB A PH. C, GCB B PH. A, GCB B PH. B, GCB B PH. C, Traps, CTTL 3000 Amps
Total Cost ($USD)
$2,000,000
Allocated Cost ($USD)
$0
Time Estimate
30 to 36 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
05FLTLCK-05GAVIN_RF 765.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18700
Title
05GUNN RD SW 345.0 kV to 05BOKESCRK 345.0 kV ckt 1- Rebuild
Description
AEP owned line, 16.54 miles of 345kV single circuit with PE conductor (1-1275 ACSR/PE 54/19) needs to be rebuilt
Total Cost ($USD)
$66,000,000
Allocated Cost ($USD)
$0
Time Estimate
24 to 36 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
05GUNN RD SW-05BOKESCRK 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18687
Title
05HANGRCK_RJ 765.0 kV to 05HANG R 765.0 kV ckt Z1 - Replace Equipment
Description
At Hanging Rock Station replace the following equipment: D1S1 PH A, D1S1 PH B, D1S1 PH C, D1S2 PH A, D1S2 PH B, D1S2 PH C, D2S1 PH A, D2S1 PH B, D2S1 PH C, D2S2 PH A, D2S2 PH B, D2S2 PH C, Jefferson Trap PH A, Jefferson Trap PH B, Jefferson Trap PH C
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$0
Time Estimate
30 to 36 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
05HANG R-05HANGRCK_RJ 765.0 kV Ckt Z1 line(Any)

System Reinforcement: n9243.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9243.0 / AEPSERG13
Title
Expand Jefferson 345 kV station. Install a second 765/345 kV 750 MVA transformer. Install a second Jefferson - Clifty Creek 345 kV single circuit ~0.8 miles.
Description
At the Jefferson Station: • Expand the northeast corner of the station • Remove Circuit breaker C1 • Install one (1) new 765/345 kV transformer and associated equipment • Install one (1) new 765 kV circuit breaker with associated control relaying and breaker disconnect switches • Install one (1) new 345 kV circuit breaker with associated control relaying and breaker disconnect switches • Install a new station service center At the Clifty Creek Station: • Extend 345 kV bus 1 and 2 to make room for a new breaker string • Move a section of the 138 kV bus underground to make room for the new breaker string • Relocate circuit breaker S to the new string • Install two (2) new 345 kV circuit breakers on the new string •Remove the existing Jefferson – Clifty Creek 345 kV line •Construct a new Jefferson – Clifty Creek 345 kV double circuit line •Evaluate line settings for all appropriate lines •Install direct fiber relaying between the Jefferson and Clifty Creek station •Associated conductors (buswork, ground grid, jumpers), telecom terminal equipment, insulators, arresters, foundations, and structures
Total Cost ($USD)
$200,238,000
Allocated Cost ($USD)
$0
Time Estimate
55 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
05JEFRSO-05JEFRSO 345.0/765.0 kV Ckt 2 transformer(Any)
05JEFRSO-06CLIFTY 345.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.6
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.6
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (Welton Spring to DVP local area, roughly 21 miles) (VA Portion)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-272 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-272 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)

System Reinforcement: n7683
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n7683
Title
Rebuild/reconductor 3.05 mi. of the 1275 ACSR/PE 54/19 conductor with 2-954 ACSR 54/7 conductor size with a SN rating of 1410 MVA.
Description
Rebuild/reconductor 3.05 mi. of the 1275 ACSR/PE 54/19 conductor with 2-954 ACSR 54/7 conductor size with a SN rating of 1410 MVA.
Total Cost ($USD)
$18,460,000
Allocated Cost ($USD)
$0
Time Estimate
24 to 36 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
05MADDOX-AG1-410 TP 345.0 kV Ckt 1 line(Any)

System Reinforcement: b3775.1
Type
Load Flow
TO
ComEd
RTEP ID / TO ID
b3775.1
Title
Swap the NIPSCO Green Acre Tap towers from the St. John-Green Acres-Olive 345 kV line
Description
Outside of the Green Acres substation, swap the NIPSCO Green Acre Tap towers from the St. John-Green Acres-Olive 345 kV line to the University Park N-Olive 345 kV line to create a University Park N-Green Acres-Olive and St. John-Olive 345 kV lines.
Cost Information
Time Estimate
Dec 01 2026

Not Contingent

Note: AH1-272 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-272 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05MADDOX-AG1-410 TP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18689
Title
AG1-410 TP 345.0 kV to 05MADDOX 345.0 kV ckt 1 - string the 2nd circuit
Description
AEP owned line; string the 2nd circuit on the rebuilt double circuit line, ~ 2.85 miles of 2-bundle 1590 ACSR conductor. At Maddox Creek: Replace 345kV circuit breaker B2, subconductor, disconnect switches.
Total Cost ($USD)
$7,250,000
Allocated Cost ($USD)
$0
Time Estimate
24 to 36 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
05MADDOX-AG1-410 TP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18635
Title
05MARYSVL_RM 765.0 kV to 05MALIS 765.0 kV ckt 1 - Replace Equipment
Description
Replace wave tap at Maliszewski towards Marysville along with circuit breakers, disconnects, and Sub Conductor.
Total Cost ($USD)
$24,200,000
Allocated Cost ($USD)
$0
Time Estimate
24 to 36 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
05MALIS-05MARYSVL_RM 765.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18653
Title
05MALIS 765.0 kV to 05VASSEL 765.0 kV ckt 1 - Replace Equipment
Description
Replace circuit breaker B, Disconnects, and reconductor between structures 432-453 to bring rating up to the sub conductor.
Total Cost ($USD)
$153,100,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
05MALIS-05VASSEL 765.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18733
Title
05BOKESCRK 345kV to 05MARYSV 345kV ckt 1 - Reconductor
Description
Reconductor line between Marysville - Boke Creek 345 kV due to paper expanded line. New line will be 2-954 ACSR RAIL
Total Cost ($USD)
$6,810,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 52 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
05MARYSV-05BOKESCRK 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18680
Title
05MARYSV 765.0 kV to 05MARYSVL_RM 765.0 kV ckt Z1 - Replace Equipment
Description
Replace wave trap and associated equipment on Marysville Reactor towards Maliszewski.
Total Cost ($USD)
$2,200,000
Allocated Cost ($USD)
$0
Time Estimate
24 to 36 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line(Any)

System Reinforcement: b3878.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b3878.1
Title
Upgrade 765 kV circuit breakers 'B' and 'B2' to 5000A 50kA breakers at Marysville Station
Description
Upgrade 765 kV circuit breakers 'B' and 'B2' to 5000A 50kA breakers at Marysville Station. In addition, the project will upgrade the existing wavetrap towards Sorenson.
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-272 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-272 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05MARYSV-05MARYSVL_RS 765.0 kV Ckt Z1 line(Any)

System Reinforcement: b3851.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b3851.1 / B3851.1
Title
Rebuild Allen-RP Mone 345kV
Description
Rebuild Allen –R.P. Mone 345kV line (18.6 miles).
Cost Information
Time Estimate
Jun 01 2027

Not Contingent

Note: AH1-272 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-272 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05RPMONE-05ALLEN 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18707
Title
05ALLEN 345.0 kV to 05RPMONE 345.0 kV ckt 1 - Replace Equipment
Description
At RP Mone: Replace CB B and B2 and associated disconnect switches. Replace 2 - 1700 KCM AAC station conductor. At Allen: Replace the disconnect switches for CBs C and C2 at Allen. Replace 2 - 2000 KCM AAC station conductor. B3851.1 to rebuild the Allen - RP Mone line needs to be completed. CB B is also be proposed to be replaced on another flowgate
Total Cost ($USD)
$5,000,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
05RPMONE-05ALLEN 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18732
Title
05RPMONE 345kV to AG1-410 TP 345kV ckt 1 - Replace Equipment
Description
At R.P. Mone: Replace 345kV circuit breakers B & B1, Bus bar 4 x 3/4 Ph C, angle bus buar 4x4x1/4 Ph B, sub conductor, disconnect switches on B and B1 breakers
Total Cost ($USD)
$4,500,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-272 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-272 could receive cost allocation. Although AH1-272 may not presently have cost responsibility for this upgrade, AH1-272 is a potential Aggregate Pool Contributor.

FacilityContingency
05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line(Any)
          New AG2-165 765kV swyd - AEP: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AG2-165, AG2-212, AG2-328
        

Attachments

AH1-272 One Line Diagram

AH1-272 One Line Diagram.jpg
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.