AH1-306 Phase I Study Report

v1.00 released 2025-10-29 20:13

Mississinewa-Gaston 138 kV

28.8 MW Capacity / 0.0 MW Energy

Introduction

This Phase I System Impact Study Report (PH1) has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, sections 307 and 308 for New Service Requests (projects) in Transition Cycle 2. The Project Developer/Eligible Customer (developer) is Golden Aster Solar Energy LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is American Electric Power.

Preface

The Phase I System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle executive summary format and (ii) an individual project-level basis. The Phase I System Impact Study Results (for both the executive summary and individual reports) will be publicly available on PJM’s website. Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.3, PJM takes the following actions during the Phase I System Impact Study:
  1. PJM studies each New Service Request on a summer peak, winter peak and light load RTEP base case study. The case year is dependent on the new services cycle under study. PJM will identify the base case year to be used in the study of a specific cycle on its website.
  2. PJM will only perform load flow analysis during the Phase I System Impact Study.
  3. In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with Affected System impacts and provides each Affected System Operator with a list of New Service Request in the Cycle with potential impacts to their respective system.
  4. PJM will create both the short circuit and stability base cases to be used in the Phase II System Impact Study.
  5. The Phase I System Impact Study results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.
The Transmission Owner takes the following actions during the Phase I System Impact Study:
  1. Identify required Interconnection Facilities to accommodate the New Service Request.
  2. Identify required Network Upgrades to mitigate system violations from the Phase I System Impact Study.
  3. Provide planning-level preliminary estimates of Interconnection Facilities and Network Upgrades including scope, cost and elapsed time to complete the work.

Decision Point I Requirements

At the close of Phase I System Impact Study, PJM will initiate Decision Point I (DP1). During DP1, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.A.1. Additional information on these elements is available in PJM Manual 14H sections 4.4, 6, and 7.

Allowable project modifications at Decision Point I are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

General

The Project Developer has proposed an uprate to a planned/existing Solar/Storage facility located in the American Electric Power zone — Grant County, Indiana. This project is an increase to the developer’s AE1-207/AE2-172 project(s), which will share the same Point of Interconnection. The AH1-306 project is a 28.8 MW Capacity only uprate to the previous project(s). The total installed facilities will have a capability of 200.0 MW with 136.0 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AH1-306
Project Name:
Mississinewa-Gaston 138 kV
Project Developer Name:
Golden Aster Solar Energy LLC
State:
Indiana
County:
Grant
Transmission Owner:
American Electric Power
MFO:
200.0
MWE:
0.0
MWC:
28.8
Fuel Type:
Solar
Basecase Study Year:
2028

Physical Interconnection Facility Study

Physical Interconnection Facilities Study is not performed as part of the Phase I System Impact Study. Physical Interconnection Facilities Study will commence in the Phase II System Impact Study.

Point of Interconnection

AH1-306 will interconnect on the American Electric Power transmission system by tapping the Mississinewa-Gaston 138 kV Line.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In the Phase I SIS, the costs shown are subject to change as a result of a facility study performed by the TO during the Phase II or Phase III System Impact Study.

Based on the Phase I SIS results, the AH1-306 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit are also shown below.

Cost Summary
DescriptionCost Allocated to AH1-306Cost Subject to Readiness*
Transmission Owner Interconnection Facilities (TOIF)$0$0
Other Scope$0$0
Option To Build Oversight$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$0$0
Network Upgrades$0$0
System Reliability Network Upgrades
Steady State Thermal & Voltage (SP & LL)$0$0
Transient Stability$0$0
Short Circuit$0$0
Transmission Owner Analysis
SubRegional$0$0
Distribution$0$0
Affected System Reinforcements
AFS - PJM Violatons$0$0
AFS - Non-PJM Violations$0$0
Total$0$0

* Contributes to calculation for Readiness Deposit #2 (RD2). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim deliverability study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 309 (Decision Point I) A.1.a.i and PJM Manual 14H, section 6.2, Readiness Deposit #2 (RD2) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point I (DP1), the Project Developer or Eligible Customer is required to submit Readiness Deposit #2, which is calculated as 10% of cost allocation for required Phase I Network Upgrades minus Readiness Deposit #1.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Readiness Deposit #2 Due for Project AH1-306

Readiness Deposit #2 has been calculated for the project based on the Phase I System Impact Study results and is shown in the table below. This Readiness Deposit #2 must be provided at Decision Point I through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit
Project ID10% of cost allocation for Phase I Network UpgradesReadiness Deposit #1 Received (RD1)Readiness Deposit #2 (RD2) for AH1-306 Project due at DP1
ABA - B
AH1-306$0$115,200$0

Note: Failure to provide an acceptable form of Readiness Deposit #2 by the end of Decision Point I will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Physical Interconnection
RTEP IDDescriptionTotal Cost ($USD)Allocated Cost ($USD)
(Pending)no interconnections facilities required to support the interconnection$0 $0

Based on the scope of work for the Interconnection Facilities, it is expected to take 0 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

The schedule for any required Network Impact Reinforcements will be more clearly identified in the Phase II and Phase III System Impact Studies.

Transmission Owner Analysis

No Transmission Owner impacts identified.

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. AEP interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Meteorological Data Reporting Requirement
The solar generation facility shall provide the Transmission Provider with site-specific meteorological data including:
  • Temperature (degrees Fahrenheit)
  • Atmospheric Pressure (hectopascals)
  • Irradiance
  • Forced outage data
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AH1-306 was evaluated as a 0.0 MW (28.8 MW Capacity) injection in the AEP area.

AH1-306 was evaluated as part of a plant. The plant consists of AH1-306. The total Energy output of the plant was evaluated at its maximum seasonal capability of 200.0 MW (0.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AP
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
AP_P1-2_MP-500-028_SRT-A
SingleAC120.65 %3792.0B4574.963.15
GD2AP
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
AP_P1-3_MP-765-502T_SRT-A
SingleAC120.64 %3792.0B4574.633.15
GD2AP
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
AP_P1-3_MP-765-502T_SRT-A
SingleAC139.36 %3792.0B5284.613.06
GD2AP
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
AP_P1-2_MP-500-028_SRT-A
SingleAC139.32 %3792.0B5282.913.06
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P1-2_MP-500-007A_SRT-A
SingleAC130.62 %3729.0B4870.983.51
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P1-2_MP-500-008A_SRT-SL
SingleAC124.1 %3729.0B4627.63.38
GD2ATSI
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line
ATSI_P1-2_TE-345-602_SRT-A
SingleAC142.52 %1683.0B2398.591.59
GD2ATSI
02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line
ATSI_P1-2_TE-345-601_SRT-A
SingleAC113.99 %1878.0B2140.731.64
GD2AEP
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC121.78 %1737.0B2115.32.43
GD2AEP
05CLOV17_XFL-05CLOVRD 345.0 kV Ckt 17 line
AEP_P1-3_#7421_05CLOVRD 765_14_SRT-A
SingleAC106.66 %2320.0B2474.481.51
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AP_P1-3_MP-765-501T_SRT-A
SingleAC121.06 %3393.4B4107.972.94
GD2AEP
05HANGRCK_RJ-05HANG R 765.0 kV Ckt Z1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC106.88 %4571.0B4885.664.37
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P1-2_MP-500-007A_SRT-A
SingleAC131.92 %3792.0B5002.283.51
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P1-2_MP-500-008A_SRT-SL
SingleAC125.38 %3792.0B4754.333.38
GD2AEP
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
AP_P1-3_MP-765-501T_SRT-A
SingleAC118.76 %4142.0B4919.184.13
GD2AEP
05MADDOX-05E LIMA 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC120.12 %2246.0B2697.982.33
GD2AEP
05MALIS-05VASSEL 765.0 kV Ckt 1 line
AP_P1-3_MP-765-501T_SRT-A
SingleAC130.8 %4142.0B5417.863.78
GD2AEP
05MALIS-05VASSEL 765.0 kV Ckt 1 line
AEP_P1-2_#706_SRT-A
SingleAC114.0 %4142.0B4722.063.94
GD2AEP
05MALIS-05VASSEL 765.0 kV Ckt 1 line
Base Case
SingleAC100.2 %4142.0A4150.443.03
GD2AEP
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
AP_P1-3_MP-765-501T_SRT-A
SingleAC130.64 %4571.0B5971.433.67
GD2AEP
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
AEP_P1-2_#706_SRT-A
SingleAC116.18 %4571.0B5310.773.93
GD2AEP
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Base Case
SingleAC114.73 %4047.0A4643.022.94
GD2AEP
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
AP_P1-3_MP-765-501T_SRT-A
SingleAC130.66 %4571.0B5972.543.67
GD2AEP
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
AEP_P1-2_#706_SRT-A
SingleAC116.43 %4571.0B5322.013.93
GD2AEP
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Base Case
SingleAC114.86 %4047.0A4648.252.94
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P1-2_#709_546_SRT-A
SingleAC145.65 %4142.0B6032.935.33
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P1-2_#6463_16757_SRT-A
SingleAC140.14 %4142.0B5804.665.04
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Base Case
SingleAC130.5 %4047.0A5281.194.58
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P1-2_#17217_SRT-A
SingleAC115.67 %5523.0B6388.324.53
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Base Case
SingleAC108.86 %4558.0A4961.853.12
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P1-2_#7422_16_SRT-A
SingleAC106.56 %5523.0B5885.343.77
GD2AEP
05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC132.35 %1868.0B2472.272.35
GD2AEP
05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer
AEP_P1-2_#7442_200545_SRT-A
SingleAC111.07 %3097.0B3439.744.23
GD2AEP
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line
AEP_P1-2_#709_546_SRT-A
SingleAC109.05 %5523.0B6022.775.33
GD2AEP
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line
AEP_P1-2_#6463_16757_SRT-A
SingleAC104.68 %5523.0B5781.35.04
GD2AEP/DEO&K
05TANNER-08M.FORT 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC118.23 %2317.0B2739.42.94
GD2AEP/DEO&K
05TANNER-08M.FORT 345.0 kV Ckt 1 line
DEOK_P1_EAST BEND-TERMINAL 4516_SRT-A
SingleAC100.05 %2317.0B2318.242.92
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC145.41 %1540.0B2239.272.14
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P1-2_#309_15_SRT-A
SingleAC141.78 %1540.0B2183.342.04
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
Base Case
SingleAC131.72 %1189.0A1566.091.81
GD2AEP/OVEC
06PIERCE-05MARQUI 345.0 kV Ckt 1 line
AEP_P1-2_#709_546_SRT-A
SingleAC101.36 %1540.0B1561.022.07
GD2AEP
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC138.82 %1868.0B2593.182.35

Details for 01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-028_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-028_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.65 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4574.96
MW Contribution:3.15
Bus #Bus NameTypeMW Contribution
23559101PLEAS2
50/50
11.891
23684101S70BUS1
50/50
0.299
23562301OGROV1
50/50
2.291
24721705FLATG2
Adder
24.202
962761AG1-125 GEN
Solar/Wind Harmer
30.492
970149AG2-104 GEN
Solar/Wind Harmer
32.932
970155AG2-107 GEN
Solar/Wind Harmer
19.471
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
270510AE1-227 GEN1
Solar/Wind Harmer
1.892
970947AG2-589 GEN
Solar/Wind Harmer
0.243
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
270349AD2-093_GEN
Solar/Wind Harmer
0.005
927014AC1-188 GEN
Solar/Wind Harmer
0.004
270263AC1-001 GEN
Solar/Wind Harmer
0.716
270159DARBY CT4
Adder
8.94
24686105CER G3
Adder
8.419
24686505CER G6
Adder
8.408
253343AC1-166 GEN
Solar/Wind Harmer
0.003
253325AC1-069 GEN
Solar/Wind Harmer
0.011
24723205RIVRG3
Adder
18.885
970593AG2-378 GEN
Solar/Wind Harmer
1.575
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.836
253370AE2-315 SEC1
Adder
1.959
253371AE2-315 SEC2
Adder
1.853
270223U2-072_GEN1
Solar/Wind Harmer
0.001
25326309TAIT D
Adder
1.071
960071AF2-298 GEN
Solar/Wind Harmer
3.39
252507AC2-088 GEN
Solar/Wind Harmer
0.308
25194608D.CRK4
Adder
1.592
25196808ZIMRHP
Adder
73.247
23559001PLEAS1
50/50
11.891
23684201S70BUS2
50/50
0.305
23562401OGROV2
50/50
2.277
24318805MLG1
50/50
6.637
24721905FLATG4
Adder
24.202
970153AG2-106 GEN
Solar/Wind Harmer
19.471
270512AE1-227 GEN2
Solar/Wind Harmer
1.892
971191AH1-055 GEN
Solar/Wind Harmer
18.65
961921AG1-034 GEN
Solar/Wind Harmer
6.407
270291AC1-194 GEN
Solar/Wind Harmer
5.661
270273AD2-016 GEN
Solar/Wind Harmer
0.74
972173AH1-669 GEN
Solar/Wind Harmer
3.569
241955AC1-078 GEN
Solar/Wind Harmer
0.006
942051AE2-217 GEN
Solar/Wind Harmer
12.683
24686205CER G4
Adder
8.375
24686405CER G5
Adder
8.342
241974AD2-163_GEN2
Solar/Wind Harmer
0.005
253338AC1-165 GEN
Solar/Wind Harmer
0.003
253333AC1-068 GEN
Solar/Wind Harmer
0.011
970605AG2-385 GEN
Solar/Wind Harmer
4.258
253415AE1-040 GEN
Solar/Wind Harmer
0.003
253406AD2-031_GEN
Solar/Wind Harmer
0.512
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
8.886
253370AE2-315 SEC1
Adder
1.959
253371AE2-315 SEC2
Adder
1.853
270391AF1-285 GEN3
Solar/Wind Harmer
0.455
970191AG2-125 GEN
Solar/Wind Harmer
1.745
252510AF1-249 C
Solar/Wind Harmer
0.052
25196608WSDLE5
Adder
8.301
25194608D.CRK4
Adder
1.592
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270222AC2-111 GEN
Solar/Wind Harmer
3.385
25196008MFTGT1
Adder
1.289
970243AG2-164 GEN
Solar/Wind Harmer
3.888
970519AG2-331 GEN
Solar/Wind Harmer
17.281
970699AG2-449 GEN
Solar/Wind Harmer
1.662
972167AH1-666 GEN
Solar/Wind Harmer
5.306
958171AF2-111 GEN
Solar/Wind Harmer
16.577
944531AF1-118 GEN
Solar/Wind Harmer
29.606
270437AC2-090 C
Solar/Wind Harmer
0.003
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
9.887
958821AF2-173 GEN
Solar/Wind Harmer
9.221
270004AE1-209 GEN
Solar/Wind Harmer
1.427
946031AF1-268 GEN
Solar/Wind Harmer
6.268
270356AE2-297 GEN
Solar/Wind Harmer
0.009
971617AH1-308 GEN
Solar/Wind Harmer
5.478
970513AG2-328 GEN
Solar/Wind Harmer
2.844
970517AG2-330 GEN
Solar/Wind Harmer
17.067
970289AG2-191 GEN
Solar/Wind Harmer
0.722
970291AG2-192 GEN
Solar/Wind Harmer
0.656
247642Z2-115 C
Solar/Wind Harmer
0.003
270043AE2-236 GEN
Solar/Wind Harmer
4.199
959331AF2-224 GEN
Solar/Wind Harmer
4.573
965021AG1-366 GEN
Solar/Wind Harmer
2.178
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.042
970349AG2-230 GEN
Solar/Wind Harmer
9.745
24728705AND G3
Adder
7.455
24728505AND G1
Adder
3.565
270491AE1-102 GEN2
Solar/Wind Harmer
0.843
970031AG2-029 GEN
Solar/Wind Harmer
4.207
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.466
964401AG1-302 GEN
Solar/Wind Harmer
0.001
270535AF1-215 GEN1
Solar/Wind Harmer
0.008
247643Z2-116 C
Solar/Wind Harmer
0
24642205MAYFLWER
Adder
0.585
945111AF1-176 GEN
Solar/Wind Harmer
5.203
274772LINCOLN ;3U
Adder
7.74
274752CRETE EC ;2U
Adder
7.553
274753CRETE EC ;3U
Adder
7.553
274724RIVER EC ;11
Adder
16.226
270258AD1-119 GEN
Solar/Wind Harmer
0.002
274802UNIV PARK;5U
Adder
5.329
276806AD2-047 C O1
Solar/Wind Harmer
3.613
970193AG2-126 GEN
Solar/Wind Harmer
9.564
970941AG2-585 GEN
Solar/Wind Harmer
7.971
972228AH1-698 GEN2
Adder
3.385
274826FISK ;BP
Adder
10.003
276897AD1-100 C
Solar/Wind Harmer
0.008
939351AE1-166 GEN
Solar/Wind Harmer
0
274800UNIV PARK;3U
Adder
5.327
972038AH1-567 GEN2
Adder
0.333
970707AG2-453 GEN
Solar/Wind Harmer
20.817
24441205WTRV SLR C
Solar/Wind Harmer
0
276893AG1-478 C
Solar/Wind Harmer
0.252
274729ELWOOD EC;1P
Adder
14.987
274730ELWOOD EC;6P
Adder
14.987
270404AC1-167 GEN
Solar/Wind Harmer
0.003
270053AF1-130 C
Solar/Wind Harmer
1.432
943121AE2-341 GEN
Solar/Wind Harmer
10.635
943591AF1-030 GEN
Solar/Wind Harmer
7.072
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
270462AD2-086
Solar/Wind Harmer
0.014
25196008MFTGT1
Adder
1.331
970333AG2-219 GEN
Solar/Wind Harmer
4.752
945681AF1-233 GEN
Solar/Wind Harmer
12.498
971995AH1-542 GEN
Solar/Wind Harmer
2.424
247536S-71 GEN
Solar/Wind Harmer
0.266
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.843
965651AG1-433 GEN
Solar/Wind Harmer
1.936
958861AF2-177 GEN
Solar/Wind Harmer
2.859
945371AF1-202 GEN
Solar/Wind Harmer
0.001
270005AE1-210 C O1
Solar/Wind Harmer
1.427
965031AG1-367 GEN
Solar/Wind Harmer
6.586
970773AG2-487 GEN
Solar/Wind Harmer
1.163
970825AG2-519 GEN
Solar/Wind Harmer
2.336
270032AE2-172
Solar/Wind Harmer
4.379
970245AG2-165 GEN
Solar/Wind Harmer
2.844
970291AG2-192 GEN
Solar/Wind Harmer
0.853
970091AG2-072 GEN
Adder
72.107
276903AD2-071 C
Solar/Wind Harmer
7.32
965011AG1-365 GEN
Solar/Wind Harmer
6.533
247521TR3_G114
Solar/Wind Harmer
0.237
270246TR4_N_V150
Solar/Wind Harmer
0.042
965421AG1-410 GEN
Solar/Wind Harmer
19.465
24728605AND G2
Adder
3.565
246936BC-WTG1
Solar/Wind Harmer
0.263
270489AE1-102 GEN1
Solar/Wind Harmer
0.843
24695305TIMB G C
Solar/Wind Harmer
0.002
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.087
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
24791305MDL-5G
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.406
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270063AE2-323 C
Solar/Wind Harmer
0.005
270055AF2-134 C O1
Solar/Wind Harmer
0.005
970373AG2-245 GEN
Solar/Wind Harmer
13.568
339216AC1-074 GEN
Solar/Wind Harmer
0.177
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.002
24639705ELKHART HY
Adder
0.142
963741AG1-226 GEN
Solar/Wind Harmer
15.2
945111AF1-176 GEN
Solar/Wind Harmer
11.453
270505AE1-170 C O1
Solar/Wind Harmer
6.739
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.342
274773LINCOLN ;4U
Adder
7.74
274774LINCOLN ;5U
Adder
7.74
274751CRETE EC ;1U
Adder
7.553
274754CRETE EC ;4U
Adder
7.553
274723RIVER EC ;12
Adder
16.418
270445AC2-157 GEN2
Solar/Wind Harmer
0.003
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.584
276776AD2-060 GEN
Solar/Wind Harmer
0.666
941551AE2-152 GEN
Solar/Wind Harmer
0
274801UNIV PARK;4U
Adder
5.327
274732ELWOOD EC;7P
Adder
8.75
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
939401AE1-172 GEN
Solar/Wind Harmer
4.75
276691AA1-018 GEN1
Solar/Wind Harmer
0.768
944231AF1-091 GEN
Solar/Wind Harmer
1.688
276901AD2-066 C O1
Solar/Wind Harmer
0.006
971997AH1-543 GEN
Solar/Wind Harmer
3.315
23751101LEADS_P59
Solar/Wind Helper
1.597
23751201ROTHROCK
Solar/Wind Helper
0.849
23562501BACKB
Solar/Wind Helper
1.042
23583801GRNGAP
Solar/Wind Helper
4.948
316095T157 G97
Solar/Wind Helper
1.323
238185AF2-356 C
Solar/Wind Helper
2.474
235054AD2-180 GEN
Solar/Wind Helper
1.935
238117U2-030
Solar/Wind Helper
0.318
238108AE1-109 GEN1
Solar/Wind Helper
0.102
235531U2-073 GEN
Solar/Wind Helper
3.033
238147AE2-230_GEN1
Solar/Wind Helper
0.427
238149AF1-291A_GEN
Solar/Wind Helper
0.122
237061AD1-155 GEN
Solar/Wind Helper
0.046
238221AF1-254 C O1
Solar/Wind Helper
0.235
235067AD1-061 GEN
Solar/Wind Helper
0.427
237030AB1-096 C
Solar/Wind Helper
0.061
276805AD2-038 GEN
Solar/Wind Harmer
0.002
964991AG1-363 GEN
Solar/Wind Helper
4.266
316097T157 G90
Solar/Wind Helper
1.323
23750701CROSSCHOOL
Solar/Wind Helper
1.364
238118U2-030_1
Solar/Wind Helper
0.318
238127S14_GEN_2
Solar/Wind Helper
0.764
238148AE2-230_GEN2
Solar/Wind Helper
0.429
237048AF1-022 C
Solar/Wind Helper
0.17
237080AD1-060 GEN
Solar/Wind Helper
0.294
237038AE2-054 C
Solar/Wind Helper
0.235
235062AE1-101 C1
Solar/Wind Helper
1.433
23779801AA1-109
Solar/Wind Helper
0.166
24318905MLG2
50/50
4.855
270471AD2-092_GEN
Solar/Wind Harmer
0.005
971073AG2-665 GEN
Solar/Wind Harmer
6.448
24685805CER G1
Adder
8.364
24685905CER G2
Adder
8.364
942861AE2-305 GEN
Solar/Wind Harmer
5.482
270518AE2-148 GEN
Solar/Wind Harmer
0.606
24723005RIVRG1
Adder
18.885
24723105RIVRG2
Adder
18.885
970077AG2-063 GEN
Solar/Wind Harmer
4.025
972269AH1-719 GEN
Adder
2.302
962581AG1-107 GEN
Solar/Wind Harmer
0.001
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
25326109MON D
Adder
1.288
964601AG1-323 GEN
Solar/Wind Harmer
2.731
964601AG1-323 GEN
Solar/Wind Harmer
1.82
253370AE2-315 SEC1
Adder
1.959
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
25322209TAIT E
Adder
9.53
25322209TAIT E
Adder
9.316
270186AC1-089 GEN
Solar/Wind Harmer
0.004
938701AE1-092 GEN
Solar/Wind Harmer
10.928
971655AH1-328 GEN
Solar/Wind Harmer
2.415
25183208HLCRTG
Solar/Wind Harmer
0.011
972159AH1-661 GEN
Adder
0.972
252509AD1-136 GEN
Solar/Wind Harmer
0.034
252519AF1-045_GEN
Solar/Wind Harmer
5.902
252516AE2-318_GEN
Solar/Wind Harmer
5.235
253378AE2-206_GEN
Solar/Wind Harmer
0.004
276820AF1-078_GEN
Solar/Wind Harmer
0.002
970329AG2-216 GEN
Solar/Wind Harmer
2.92
25194408D.CRK1
Adder
7.324
25194508D.CRK3
Adder
1.369
25326509SID D
Adder
1.268
970239AG2-162 GEN
Solar/Wind Harmer
1.662
24728805RICHG1
Adder
3.587
24728905RICHG2
Adder
3.587
970883AG2-550 GEN
Solar/Wind Harmer
6.617
970885AG2-551 GEN
Solar/Wind Harmer
2.206
270383AD1-128 GEN
Solar/Wind Harmer
0.004
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
944541AF1-119 GEN
Solar/Wind Harmer
0.442
960971AF2-388 GEN
Solar/Wind Harmer
3.871
247621Y3-024
Adder
0.228
270201AC2-176 GEN
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
0.494
970825AG2-519 GEN
Solar/Wind Harmer
7.293
960441AF2-335 GEN
Solar/Wind Harmer
6.577
270599AE1-208 GEN
Solar/Wind Harmer
6.026
270031AE2-169
Solar/Wind Harmer
3.616
942221AE2-234 GEN
Solar/Wind Harmer
0.033
971613AH1-306 GEN
Solar/Wind Harmer
3.153
970321AG2-212 GEN
Solar/Wind Harmer
2.844
970611AG2-400 GEN
Solar/Wind Harmer
6.533
970627AG2-408 GEN
Solar/Wind Harmer
1.96
246938BC-WTG3
Solar/Wind Harmer
0.235
246937BC-WTG2
Solar/Wind Harmer
0.263
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
970235AG2-159 GEN
Solar/Wind Harmer
3.948
970235AG2-159 GEN
Solar/Wind Harmer
2.265
971199AH1-059 GEN
Solar/Wind Harmer
2.587
339221AD2-048_GEN
Solar/Wind Harmer
0.004
966841AG1-555 GEN
Solar/Wind Harmer
0.73
965681AG1-436 GEN
Solar/Wind Harmer
8.059
965791AG1-447 GEN
Solar/Wind Harmer
5.91
270007AE1-245 C
Solar/Wind Harmer
0.002
270216AD2-079_GEN
Solar/Wind Harmer
0.001
247620Y3-023
Adder
0.425
270526AF1-158 GEN
Solar/Wind Harmer
0.008
972043AH1-570 GEN
Solar/Wind Harmer
1.674
972045AH1-571 GEN
Solar/Wind Harmer
1.341
24441505OLIV SLR
Solar/Wind Harmer
0
970241AG2-163 GEN
Solar/Wind Harmer
3.747
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
12.817
961051AF2-396 GEN
Solar/Wind Harmer
8.545
274770LINCOLN ;1U
Adder
7.74
274771LINCOLN ;2U
Adder
7.74
270444AC2-157 GEN1
Solar/Wind Harmer
0.003
971587AH1-292 GEN
Solar/Wind Harmer
4.687
970623AG2-406 GEN
Solar/Wind Harmer
1.169
274808UNIV PK N;4U
Adder
4.563
274803UNIV PARK;6U
Adder
5.329
274888KELLY CRK;1U
Solar/Wind Harmer
0.375
274887GEN-1.85
Solar/Wind Harmer
0.168
276843GEN-1.7
Solar/Wind Harmer
0.206
945391AF1-204 GEN
Solar/Wind Harmer
6.775
958011AF2-095 GEN
Solar/Wind Harmer
9.182
972259AH1-714 GEN
Adder
17.426
241960AC2-195 GEN
Solar/Wind Harmer
0.005
971125AH1-004 GEN
Solar/Wind Harmer
2.546
970107AG2-081 GEN
Solar/Wind Harmer
1.909
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
960161AF2-307 GEN
Solar/Wind Harmer
4.195
944971AF1-162 GEN
Solar/Wind Harmer
6.345
958481AF2-142 GEN
Solar/Wind Harmer
9.506
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.857
971573AH1-285 GEN
Solar/Wind Harmer
1.18
958491AF2-143 GEN
Solar/Wind Harmer
9.485
274879MINONK ;1U
Solar/Wind Harmer
0.267
23585401KL_K28_T16
Solar/Wind Helper
1.442
238120AE2-309 GEN
Solar/Wind Helper
0.483
238175AF1-290_GEN
Solar/Wind Helper
0.13
238169AE2-226 GEN1
Solar/Wind Helper
0.6
238170AE2-226 GEN2
Solar/Wind Helper
0.6
235020AA1-095 C
Solar/Wind Helper
0.045
23777901MDS_W4-102
Solar/Wind Helper
0.151
235063AE1-101 C2
Solar/Wind Helper
1.433
237002AB1-128_GEN
Solar/Wind Helper
0.382
237001AB1-127_GEN
Solar/Wind Helper
0.381
237034AC2-136 C
Solar/Wind Helper
0.194
23777801MSM_W1-116
Solar/Wind Helper
0.098
237025AB1-124 C
Solar/Wind Helper
0.142
237006AB1-125 GEN
Solar/Wind Helper
0.106
962691AG1-118 GEN
Solar/Wind Harmer
7.548
962771AG1-126 GEN
Solar/Wind Harmer
30.492
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Harmer
0.006
270520AE2-214 GEN
Solar/Wind Harmer
0.011
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
4.271
970879AG2-548 GEN
Solar/Wind Harmer
6.448
970689AG2-444 GEN
Solar/Wind Harmer
14.59
270432AC2-029 GEN
Solar/Wind Harmer
3.168
270269AC2-059
Solar/Wind Harmer
0.004
972203AH1-686 GEN
Adder
2.352
940611AE2-048 GEN
Solar/Wind Harmer
17.483
941391AE2-136 GEN
Solar/Wind Harmer
9.848
270284AF1-227 GEN1
Solar/Wind Harmer
0.009
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
270156DARBY CT1
Adder
9.085
270157DARBY CT2
Adder
9.063
270158DARBY CT3
Adder
8.918
945631AF1-228 GEN
Solar/Wind Harmer
0
253383AE2-342_GEN
Solar/Wind Harmer
0.002
241973AD2-163_GEN1
Solar/Wind Harmer
0.005
943861AF1-054 GEN
Solar/Wind Harmer
2.706
943851AF1-053 GEN
Solar/Wind Harmer
1.874
971985AH1-537 GEN
Solar/Wind Harmer
2.087
270340AC2-060 GEN
Solar/Wind Harmer
0.008
241972AD1-140 GEN
Solar/Wind Harmer
0.755
270367AC2-061_GEN
Solar/Wind Harmer
0.005
253372AE2-315 SEC3
Adder
1.853
253372AE2-315 SEC3
Adder
1.853
270578AF1-285 GEN2
Solar/Wind Harmer
0.455
25306009OHH W.
Adder
2.812
253349AC2-067 GEN
Solar/Wind Harmer
2.136
253400AC2-068 GEN
Solar/Wind Harmer
0.859
252524AE2-267 GEN
Solar/Wind Harmer
0.002
25196408WSDLE3
Adder
8.545
25196308WSDLE2
Adder
8.471
25196208WSDLE1
Adder
8.45
25196708WSDLE6
Adder
8.428
25196508WSDLE4
Adder
8.216
270302AB2-170 GEN
Solar/Wind Harmer
0.004
270317AD1-130_GEN
Solar/Wind Harmer
0.01
971653AH1-327 GEN
Solar/Wind Harmer
0.947
25196108MFTGT2
Adder
1.467
25196108MFTGT2
Adder
1.362
971673AH1-337 GEN
Solar/Wind Harmer
4.312
971029AG2-637 GEN
Solar/Wind Harmer
9.944
972163AH1-664 GEN
Solar/Wind Harmer
7.37
972165AH1-665 GEN
Solar/Wind Harmer
5.903
270543AE2-219 C
Solar/Wind Harmer
0.004
270240V3-007_GEN2
Solar/Wind Harmer
0.002
24729505KEY G4
Adder
6.141
965101AG1-375 GEN
Solar/Wind Harmer
6.597
945581AF1-223 GEN
Solar/Wind Harmer
0
970115AG2-085 GEN
Solar/Wind Harmer
2.631
270024AE2-089 GEN
Solar/Wind Harmer
0.007
971609AH1-304 GEN
Solar/Wind Harmer
1.074
270071AF1-092 GEN
Solar/Wind Harmer
12.598
270594AE1-207 GEN
Solar/Wind Harmer
7.357
970289AG2-191 GEN
Solar/Wind Harmer
1.247
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
8.837
965051AG1-369 GEN
Solar/Wind Harmer
3.247
971347AH1-153 GEN
Solar/Wind Harmer
9.745
965041AG1-368 GEN
Solar/Wind Harmer
6.496
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.821
971611AH1-305 GEN
Solar/Wind Harmer
3.852
958391AF2-133 GEN
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0.008
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
247607V1-011 GEN
Solar/Wind Harmer
0.001
971771AH1-392 GEN
Solar/Wind Harmer
6.442
971769AH1-391 GEN
Solar/Wind Harmer
7.189
963841AG1-237 GEN
Solar/Wind Harmer
2.789
24477305BRIDGE
Adder
0.321
971619AH1-309 GEN
Solar/Wind Harmer
2.888
274775LINCOLN ;6U
Adder
7.74
274776LINCOLN ;7U
Adder
7.74
274777LINCOLN ;8U
Adder
7.74
274814UNIV PK N;0U
Adder
4.624
274807UNIV PK N;3U
Adder
4.614
274805UNIV PK N;1U
Adder
4.594
274811UNIV PK N;7U
Adder
4.584
972037AH1-567 GEN1
Adder
0.167
960591AF2-350 GEN
Solar/Wind Harmer
6.377
972227AH1-698 GEN1
Adder
2.383
274827FISK ;RP
Adder
7.089
970179AG2-119 GEN
Solar/Wind Harmer
5.69
274687WILL CNTY;4U
Adder
25.484
274687WILL CNTY;4U
Adder
25.484
274731ELWOOD EC;2P
Adder
14.987
274733ELWOOD EC;3P
Adder
14.987
274735ELWOOD EC;4P
Adder
14.987
274728ELWOOD EC;5P
Adder
14.987
970833AG2-524 GEN
Solar/Wind Harmer
6.995
970833AG2-524 GEN
Solar/Wind Harmer
4.664
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
970169AG2-114 GEN
Solar/Wind Harmer
6.327
276868AE1-113 GEN
Solar/Wind Harmer
1.267
276882AE2-255 GEN
Solar/Wind Harmer
0.739
238109AE1-109 GEN2
Solar/Wind Helper
0.102
238110AE1-109 GEN3
Solar/Wind Helper
0.102
238126S14_GEN_1
Solar/Wind Helper
0.764
23750501ELLIOTTS
Solar/Wind Helper
0.636
238152AF2-075_GEN
Solar/Wind Helper
0.611
238208AF1-136 C
Solar/Wind Helper
0.19
23546401DTGZ2-030
Solar/Wind Helper
0.077
237085AD2-009_GEN
Solar/Wind Helper
1.425
3138216PACIFIC
Solar/Wind Helper
0.038
316411AF1-147_GEN1
Solar/Wind Helper
0.754
316415AF1-147_GEN2
Solar/Wind Helper
0.754
944201AF1-088_MTX
Adder
106.522
957141AF2-008_MTX
Adder
53.261
NYPJM->LTFIMP_NY
CLTF
4.491
LGEELTFEXP_LGEE->PJM
CLTF
6.272
WECLTFEXP_WEC->PJM
CLTF
3.434
AG2-052LTFEXP_AG2-052->PJM
LTF
0.214
AH1-155LTFEXP_AH1-155->PJM
LTF
0.321
LAGNLTFEXP_LAGN->PJM
CLTF
14.169
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.052
TVALTFEXP_TVA->PJM
CLTF
7.036
CBM West 1LTFEXP_CBM-W1->PJM
CBM
126.393
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.84
MECLTFEXP_MEC->PJM
CLTF
14.465
SIGELTFEXP_SIGE->PJM
CLTF
0.467
CPLELTFEXP_CPLE->PJM
CLTF
1.288
CBM West 2LTFEXP_CBM-W2->PJM
CBM
105.476

Details for 01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line l/o AP_P1-3_MP-765-502T_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-502T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.64 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4574.63
MW Contribution:3.15
Bus #Bus NameTypeMW Contribution
23559101PLEAS2
50/50
11.891
23684101S70BUS1
50/50
0.299
23562301OGROV1
50/50
2.291
24721705FLATG2
Adder
24.202
962761AG1-125 GEN
Solar/Wind Harmer
30.492
970149AG2-104 GEN
Solar/Wind Harmer
32.932
970155AG2-107 GEN
Solar/Wind Harmer
19.471
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
270510AE1-227 GEN1
Solar/Wind Harmer
1.892
970947AG2-589 GEN
Solar/Wind Harmer
0.243
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
270349AD2-093_GEN
Solar/Wind Harmer
0.005
927014AC1-188 GEN
Solar/Wind Harmer
0.004
270263AC1-001 GEN
Solar/Wind Harmer
0.716
270159DARBY CT4
Adder
8.94
24686105CER G3
Adder
8.419
24686505CER G6
Adder
8.408
253343AC1-166 GEN
Solar/Wind Harmer
0.003
253325AC1-069 GEN
Solar/Wind Harmer
0.011
24723205RIVRG3
Adder
18.885
970593AG2-378 GEN
Solar/Wind Harmer
1.575
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.836
253370AE2-315 SEC1
Adder
1.959
253371AE2-315 SEC2
Adder
1.853
23559001PLEAS1
50/50
11.891
23684201S70BUS2
50/50
0.305
23562401OGROV2
50/50
2.277
24318805MLG1
50/50
6.637
24721905FLATG4
Adder
24.202
970153AG2-106 GEN
Solar/Wind Harmer
19.471
270512AE1-227 GEN2
Solar/Wind Harmer
1.892
971191AH1-055 GEN
Solar/Wind Harmer
18.65
961921AG1-034 GEN
Solar/Wind Harmer
6.407
270291AC1-194 GEN
Solar/Wind Harmer
5.661
270273AD2-016 GEN
Solar/Wind Harmer
0.74
972173AH1-669 GEN
Solar/Wind Harmer
3.569
241955AC1-078 GEN
Solar/Wind Harmer
0.006
942051AE2-217 GEN
Solar/Wind Harmer
12.683
24686205CER G4
Adder
8.375
24686405CER G5
Adder
8.342
241974AD2-163_GEN2
Solar/Wind Harmer
0.005
253338AC1-165 GEN
Solar/Wind Harmer
0.003
253333AC1-068 GEN
Solar/Wind Harmer
0.011
970605AG2-385 GEN
Solar/Wind Harmer
4.258
253415AE1-040 GEN
Solar/Wind Harmer
0.003
253406AD2-031_GEN
Solar/Wind Harmer
0.512
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
8.886
253370AE2-315 SEC1
Adder
1.959
253371AE2-315 SEC2
Adder
1.853
270391AF1-285 GEN3
Solar/Wind Harmer
0.455
970191AG2-125 GEN
Solar/Wind Harmer
1.745
252510AF1-249 C
Solar/Wind Harmer
0.052
25196608WSDLE5
Adder
8.301
25194608D.CRK4
Adder
1.592
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270222AC2-111 GEN
Solar/Wind Harmer
3.385
25196008MFTGT1
Adder
1.289
970243AG2-164 GEN
Solar/Wind Harmer
3.888
970519AG2-331 GEN
Solar/Wind Harmer
17.281
970699AG2-449 GEN
Solar/Wind Harmer
1.662
972167AH1-666 GEN
Solar/Wind Harmer
5.306
958171AF2-111 GEN
Solar/Wind Harmer
16.577
944531AF1-118 GEN
Solar/Wind Harmer
29.606
270437AC2-090 C
Solar/Wind Harmer
0.003
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
9.887
958821AF2-173 GEN
Solar/Wind Harmer
9.221
270004AE1-209 GEN
Solar/Wind Harmer
1.427
946031AF1-268 GEN
Solar/Wind Harmer
6.268
270356AE2-297 GEN
Solar/Wind Harmer
0.009
971617AH1-308 GEN
Solar/Wind Harmer
5.478
970513AG2-328 GEN
Solar/Wind Harmer
2.844
970517AG2-330 GEN
Solar/Wind Harmer
17.067
970289AG2-191 GEN
Solar/Wind Harmer
0.722
970291AG2-192 GEN
Solar/Wind Harmer
0.656
247642Z2-115 C
Solar/Wind Harmer
0.003
270043AE2-236 GEN
Solar/Wind Harmer
4.199
959331AF2-224 GEN
Solar/Wind Harmer
4.573
965021AG1-366 GEN
Solar/Wind Harmer
2.178
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.042
970349AG2-230 GEN
Solar/Wind Harmer
9.745
24728705AND G3
Adder
7.455
24728505AND G1
Adder
3.565
270491AE1-102 GEN2
Solar/Wind Harmer
0.843
970031AG2-029 GEN
Solar/Wind Harmer
4.207
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.466
964401AG1-302 GEN
Solar/Wind Harmer
0.001
270535AF1-215 GEN1
Solar/Wind Harmer
0.008
247643Z2-116 C
Solar/Wind Harmer
0
24642205MAYFLWER
Adder
0.585
945111AF1-176 GEN
Solar/Wind Harmer
5.203
274772LINCOLN ;3U
Adder
7.74
274752CRETE EC ;2U
Adder
7.553
274753CRETE EC ;3U
Adder
7.553
274724RIVER EC ;11
Adder
16.226
270258AD1-119 GEN
Solar/Wind Harmer
0.002
274802UNIV PARK;5U
Adder
5.329
276806AD2-047 C O1
Solar/Wind Harmer
3.613
970193AG2-126 GEN
Solar/Wind Harmer
9.564
970941AG2-585 GEN
Solar/Wind Harmer
7.971
972228AH1-698 GEN2
Adder
3.385
274826FISK ;BP
Adder
10.003
276897AD1-100 C
Solar/Wind Harmer
0.008
939351AE1-166 GEN
Solar/Wind Harmer
0
274800UNIV PARK;3U
Adder
5.327
972038AH1-567 GEN2
Adder
0.333
970707AG2-453 GEN
Solar/Wind Harmer
20.817
24441205WTRV SLR C
Solar/Wind Harmer
0
276893AG1-478 C
Solar/Wind Harmer
0.252
274729ELWOOD EC;1P
Adder
14.987
274730ELWOOD EC;6P
Adder
14.987
270404AC1-167 GEN
Solar/Wind Harmer
0.003
270053AF1-130 C
Solar/Wind Harmer
1.432
270223U2-072_GEN1
Solar/Wind Harmer
0.001
25326309TAIT D
Adder
1.071
960071AF2-298 GEN
Solar/Wind Harmer
3.39
252507AC2-088 GEN
Solar/Wind Harmer
0.308
25194608D.CRK4
Adder
1.592
25196808ZIMRHP
Adder
73.247
270462AD2-086
Solar/Wind Harmer
0.014
25196008MFTGT1
Adder
1.331
970333AG2-219 GEN
Solar/Wind Harmer
4.752
945681AF1-233 GEN
Solar/Wind Harmer
12.498
971995AH1-542 GEN
Solar/Wind Harmer
2.424
247536S-71 GEN
Solar/Wind Harmer
0.266
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.843
965651AG1-433 GEN
Solar/Wind Harmer
1.936
958861AF2-177 GEN
Solar/Wind Harmer
2.859
945371AF1-202 GEN
Solar/Wind Harmer
0.001
270005AE1-210 C O1
Solar/Wind Harmer
1.427
965031AG1-367 GEN
Solar/Wind Harmer
6.586
970773AG2-487 GEN
Solar/Wind Harmer
1.163
970825AG2-519 GEN
Solar/Wind Harmer
2.336
270032AE2-172
Solar/Wind Harmer
4.379
970245AG2-165 GEN
Solar/Wind Harmer
2.844
970291AG2-192 GEN
Solar/Wind Harmer
0.853
970091AG2-072 GEN
Adder
72.107
276903AD2-071 C
Solar/Wind Harmer
7.32
965011AG1-365 GEN
Solar/Wind Harmer
6.533
247521TR3_G114
Solar/Wind Harmer
0.237
270246TR4_N_V150
Solar/Wind Harmer
0.042
965421AG1-410 GEN
Solar/Wind Harmer
19.465
24728605AND G2
Adder
3.565
246936BC-WTG1
Solar/Wind Harmer
0.263
270489AE1-102 GEN1
Solar/Wind Harmer
0.843
24695305TIMB G C
Solar/Wind Harmer
0.002
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.087
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
24791305MDL-5G
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.406
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270063AE2-323 C
Solar/Wind Harmer
0.005
270055AF2-134 C O1
Solar/Wind Harmer
0.005
970373AG2-245 GEN
Solar/Wind Harmer
13.568
339216AC1-074 GEN
Solar/Wind Harmer
0.177
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.002
24639705ELKHART HY
Adder
0.142
963741AG1-226 GEN
Solar/Wind Harmer
15.2
945111AF1-176 GEN
Solar/Wind Harmer
11.453
270505AE1-170 C O1
Solar/Wind Harmer
6.739
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.342
274773LINCOLN ;4U
Adder
7.74
274774LINCOLN ;5U
Adder
7.74
274751CRETE EC ;1U
Adder
7.553
274754CRETE EC ;4U
Adder
7.553
274723RIVER EC ;12
Adder
16.418
270445AC2-157 GEN2
Solar/Wind Harmer
0.003
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.584
276776AD2-060 GEN
Solar/Wind Harmer
0.666
941551AE2-152 GEN
Solar/Wind Harmer
0
274801UNIV PARK;4U
Adder
5.327
274732ELWOOD EC;7P
Adder
8.75
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
939401AE1-172 GEN
Solar/Wind Harmer
4.75
276691AA1-018 GEN1
Solar/Wind Harmer
0.768
944231AF1-091 GEN
Solar/Wind Harmer
1.688
276901AD2-066 C O1
Solar/Wind Harmer
0.006
971997AH1-543 GEN
Solar/Wind Harmer
3.315
23751101LEADS_P59
Solar/Wind Helper
1.597
23751201ROTHROCK
Solar/Wind Helper
0.849
23562501BACKB
Solar/Wind Helper
1.042
23583801GRNGAP
Solar/Wind Helper
4.948
316095T157 G97
Solar/Wind Helper
1.323
238185AF2-356 C
Solar/Wind Helper
2.474
235054AD2-180 GEN
Solar/Wind Helper
1.935
238117U2-030
Solar/Wind Helper
0.318
238108AE1-109 GEN1
Solar/Wind Helper
0.102
235531U2-073 GEN
Solar/Wind Helper
3.033
238147AE2-230_GEN1
Solar/Wind Helper
0.427
238149AF1-291A_GEN
Solar/Wind Helper
0.122
237061AD1-155 GEN
Solar/Wind Helper
0.046
238221AF1-254 C O1
Solar/Wind Helper
0.235
235067AD1-061 GEN
Solar/Wind Helper
0.427
237030AB1-096 C
Solar/Wind Helper
0.061
24318905MLG2
50/50
4.855
270471AD2-092_GEN
Solar/Wind Harmer
0.005
971073AG2-665 GEN
Solar/Wind Harmer
6.448
24685805CER G1
Adder
8.364
24685905CER G2
Adder
8.364
942861AE2-305 GEN
Solar/Wind Harmer
5.482
270518AE2-148 GEN
Solar/Wind Harmer
0.606
24723005RIVRG1
Adder
18.885
24723105RIVRG2
Adder
18.885
970077AG2-063 GEN
Solar/Wind Harmer
4.025
972269AH1-719 GEN
Adder
2.302
962581AG1-107 GEN
Solar/Wind Harmer
0.001
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
25326109MON D
Adder
1.288
964601AG1-323 GEN
Solar/Wind Harmer
2.731
964601AG1-323 GEN
Solar/Wind Harmer
1.82
253370AE2-315 SEC1
Adder
1.959
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
25322209TAIT E
Adder
9.53
25322209TAIT E
Adder
9.316
270186AC1-089 GEN
Solar/Wind Harmer
0.004
938701AE1-092 GEN
Solar/Wind Harmer
10.928
971655AH1-328 GEN
Solar/Wind Harmer
2.415
25183208HLCRTG
Solar/Wind Harmer
0.011
972159AH1-661 GEN
Adder
0.972
252509AD1-136 GEN
Solar/Wind Harmer
0.034
252519AF1-045_GEN
Solar/Wind Harmer
5.902
252516AE2-318_GEN
Solar/Wind Harmer
5.235
253378AE2-206_GEN
Solar/Wind Harmer
0.004
276820AF1-078_GEN
Solar/Wind Harmer
0.002
970329AG2-216 GEN
Solar/Wind Harmer
2.92
25194408D.CRK1
Adder
7.324
25194508D.CRK3
Adder
1.369
25326509SID D
Adder
1.268
970239AG2-162 GEN
Solar/Wind Harmer
1.662
24728805RICHG1
Adder
3.587
24728905RICHG2
Adder
3.587
970883AG2-550 GEN
Solar/Wind Harmer
6.617
970885AG2-551 GEN
Solar/Wind Harmer
2.206
270383AD1-128 GEN
Solar/Wind Harmer
0.004
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
944541AF1-119 GEN
Solar/Wind Harmer
0.442
960971AF2-388 GEN
Solar/Wind Harmer
3.871
247621Y3-024
Adder
0.228
270201AC2-176 GEN
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
0.494
970825AG2-519 GEN
Solar/Wind Harmer
7.293
960441AF2-335 GEN
Solar/Wind Harmer
6.577
270599AE1-208 GEN
Solar/Wind Harmer
6.026
270031AE2-169
Solar/Wind Harmer
3.616
942221AE2-234 GEN
Solar/Wind Harmer
0.033
971613AH1-306 GEN
Solar/Wind Harmer
3.153
970321AG2-212 GEN
Solar/Wind Harmer
2.844
970611AG2-400 GEN
Solar/Wind Harmer
6.533
970627AG2-408 GEN
Solar/Wind Harmer
1.96
246938BC-WTG3
Solar/Wind Harmer
0.235
246937BC-WTG2
Solar/Wind Harmer
0.263
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
970235AG2-159 GEN
Solar/Wind Harmer
3.948
970235AG2-159 GEN
Solar/Wind Harmer
2.265
971199AH1-059 GEN
Solar/Wind Harmer
2.587
339221AD2-048_GEN
Solar/Wind Harmer
0.004
966841AG1-555 GEN
Solar/Wind Harmer
0.73
965681AG1-436 GEN
Solar/Wind Harmer
8.059
965791AG1-447 GEN
Solar/Wind Harmer
5.91
270007AE1-245 C
Solar/Wind Harmer
0.002
270216AD2-079_GEN
Solar/Wind Harmer
0.001
247620Y3-023
Adder
0.425
270526AF1-158 GEN
Solar/Wind Harmer
0.008
972043AH1-570 GEN
Solar/Wind Harmer
1.674
972045AH1-571 GEN
Solar/Wind Harmer
1.341
24441505OLIV SLR
Solar/Wind Harmer
0
970241AG2-163 GEN
Solar/Wind Harmer
3.747
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
12.817
961051AF2-396 GEN
Solar/Wind Harmer
8.545
274770LINCOLN ;1U
Adder
7.74
274771LINCOLN ;2U
Adder
7.74
270444AC2-157 GEN1
Solar/Wind Harmer
0.003
971587AH1-292 GEN
Solar/Wind Harmer
4.687
970623AG2-406 GEN
Solar/Wind Harmer
1.169
274808UNIV PK N;4U
Adder
4.563
274803UNIV PARK;6U
Adder
5.329
274888KELLY CRK;1U
Solar/Wind Harmer
0.375
274887GEN-1.85
Solar/Wind Harmer
0.168
276843GEN-1.7
Solar/Wind Harmer
0.206
945391AF1-204 GEN
Solar/Wind Harmer
6.775
943121AE2-341 GEN
Solar/Wind Harmer
10.635
943591AF1-030 GEN
Solar/Wind Harmer
7.072
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
276805AD2-038 GEN
Solar/Wind Harmer
0.002
964991AG1-363 GEN
Solar/Wind Helper
4.266
316097T157 G90
Solar/Wind Helper
1.323
23750701CROSSCHOOL
Solar/Wind Helper
1.364
238118U2-030_1
Solar/Wind Helper
0.318
238127S14_GEN_2
Solar/Wind Helper
0.764
238148AE2-230_GEN2
Solar/Wind Helper
0.429
237048AF1-022 C
Solar/Wind Helper
0.17
237080AD1-060 GEN
Solar/Wind Helper
0.294
237038AE2-054 C
Solar/Wind Helper
0.235
235062AE1-101 C1
Solar/Wind Helper
1.433
23779801AA1-109
Solar/Wind Helper
0.166
958011AF2-095 GEN
Solar/Wind Harmer
9.182
972259AH1-714 GEN
Adder
17.426
241960AC2-195 GEN
Solar/Wind Harmer
0.005
971125AH1-004 GEN
Solar/Wind Harmer
2.546
970107AG2-081 GEN
Solar/Wind Harmer
1.909
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
960161AF2-307 GEN
Solar/Wind Harmer
4.195
944971AF1-162 GEN
Solar/Wind Harmer
6.345
958481AF2-142 GEN
Solar/Wind Harmer
9.506
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.857
971573AH1-285 GEN
Solar/Wind Harmer
1.18
958491AF2-143 GEN
Solar/Wind Harmer
9.485
274879MINONK ;1U
Solar/Wind Harmer
0.267
23585401KL_K28_T16
Solar/Wind Helper
1.442
238120AE2-309 GEN
Solar/Wind Helper
0.483
238175AF1-290_GEN
Solar/Wind Helper
0.13
238169AE2-226 GEN1
Solar/Wind Helper
0.6
238170AE2-226 GEN2
Solar/Wind Helper
0.6
235020AA1-095 C
Solar/Wind Helper
0.045
23777901MDS_W4-102
Solar/Wind Helper
0.151
235063AE1-101 C2
Solar/Wind Helper
1.433
237002AB1-128_GEN
Solar/Wind Helper
0.382
237001AB1-127_GEN
Solar/Wind Helper
0.381
237034AC2-136 C
Solar/Wind Helper
0.194
23777801MSM_W1-116
Solar/Wind Helper
0.098
237025AB1-124 C
Solar/Wind Helper
0.142
237006AB1-125 GEN
Solar/Wind Helper
0.106
962691AG1-118 GEN
Solar/Wind Harmer
7.548
962771AG1-126 GEN
Solar/Wind Harmer
30.492
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Harmer
0.006
270520AE2-214 GEN
Solar/Wind Harmer
0.011
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
4.271
970879AG2-548 GEN
Solar/Wind Harmer
6.448
970689AG2-444 GEN
Solar/Wind Harmer
14.59
270432AC2-029 GEN
Solar/Wind Harmer
3.168
270269AC2-059
Solar/Wind Harmer
0.004
972203AH1-686 GEN
Adder
2.352
940611AE2-048 GEN
Solar/Wind Harmer
17.483
941391AE2-136 GEN
Solar/Wind Harmer
9.848
270284AF1-227 GEN1
Solar/Wind Harmer
0.009
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
270156DARBY CT1
Adder
9.085
270157DARBY CT2
Adder
9.063
270158DARBY CT3
Adder
8.918
945631AF1-228 GEN
Solar/Wind Harmer
0
253383AE2-342_GEN
Solar/Wind Harmer
0.002
241973AD2-163_GEN1
Solar/Wind Harmer
0.005
943861AF1-054 GEN
Solar/Wind Harmer
2.706
943851AF1-053 GEN
Solar/Wind Harmer
1.874
971985AH1-537 GEN
Solar/Wind Harmer
2.087
270340AC2-060 GEN
Solar/Wind Harmer
0.008
241972AD1-140 GEN
Solar/Wind Harmer
0.755
270367AC2-061_GEN
Solar/Wind Harmer
0.005
253372AE2-315 SEC3
Adder
1.853
253372AE2-315 SEC3
Adder
1.853
270578AF1-285 GEN2
Solar/Wind Harmer
0.455
25306009OHH W.
Adder
2.812
253349AC2-067 GEN
Solar/Wind Harmer
2.136
253400AC2-068 GEN
Solar/Wind Harmer
0.859
252524AE2-267 GEN
Solar/Wind Harmer
0.002
25196408WSDLE3
Adder
8.545
25196308WSDLE2
Adder
8.471
25196208WSDLE1
Adder
8.45
25196708WSDLE6
Adder
8.428
25196508WSDLE4
Adder
8.216
270302AB2-170 GEN
Solar/Wind Harmer
0.004
270317AD1-130_GEN
Solar/Wind Harmer
0.01
971653AH1-327 GEN
Solar/Wind Harmer
0.947
25196108MFTGT2
Adder
1.467
25196108MFTGT2
Adder
1.362
971673AH1-337 GEN
Solar/Wind Harmer
4.312
971029AG2-637 GEN
Solar/Wind Harmer
9.944
972163AH1-664 GEN
Solar/Wind Harmer
7.37
972165AH1-665 GEN
Solar/Wind Harmer
5.903
270543AE2-219 C
Solar/Wind Harmer
0.004
270240V3-007_GEN2
Solar/Wind Harmer
0.002
24729505KEY G4
Adder
6.141
965101AG1-375 GEN
Solar/Wind Harmer
6.597
945581AF1-223 GEN
Solar/Wind Harmer
0
970115AG2-085 GEN
Solar/Wind Harmer
2.631
270024AE2-089 GEN
Solar/Wind Harmer
0.007
971609AH1-304 GEN
Solar/Wind Harmer
1.074
270071AF1-092 GEN
Solar/Wind Harmer
12.598
270594AE1-207 GEN
Solar/Wind Harmer
7.357
970289AG2-191 GEN
Solar/Wind Harmer
1.247
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
8.837
965051AG1-369 GEN
Solar/Wind Harmer
3.247
971347AH1-153 GEN
Solar/Wind Harmer
9.745
965041AG1-368 GEN
Solar/Wind Harmer
6.496
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.821
971611AH1-305 GEN
Solar/Wind Harmer
3.852
958391AF2-133 GEN
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0.008
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
247607V1-011 GEN
Solar/Wind Harmer
0.001
971771AH1-392 GEN
Solar/Wind Harmer
6.442
971769AH1-391 GEN
Solar/Wind Harmer
7.189
963841AG1-237 GEN
Solar/Wind Harmer
2.789
24477305BRIDGE
Adder
0.321
971619AH1-309 GEN
Solar/Wind Harmer
2.888
274775LINCOLN ;6U
Adder
7.74
274776LINCOLN ;7U
Adder
7.74
274777LINCOLN ;8U
Adder
7.74
274814UNIV PK N;0U
Adder
4.624
274807UNIV PK N;3U
Adder
4.614
274805UNIV PK N;1U
Adder
4.594
274811UNIV PK N;7U
Adder
4.584
972037AH1-567 GEN1
Adder
0.167
960591AF2-350 GEN
Solar/Wind Harmer
6.377
972227AH1-698 GEN1
Adder
2.383
274827FISK ;RP
Adder
7.089
970179AG2-119 GEN
Solar/Wind Harmer
5.69
274687WILL CNTY;4U
Adder
25.484
274687WILL CNTY;4U
Adder
25.484
274731ELWOOD EC;2P
Adder
14.987
274733ELWOOD EC;3P
Adder
14.987
274735ELWOOD EC;4P
Adder
14.987
274728ELWOOD EC;5P
Adder
14.987
970833AG2-524 GEN
Solar/Wind Harmer
6.995
970833AG2-524 GEN
Solar/Wind Harmer
4.664
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
970169AG2-114 GEN
Solar/Wind Harmer
6.327
276868AE1-113 GEN
Solar/Wind Harmer
1.267
276882AE2-255 GEN
Solar/Wind Harmer
0.739
238109AE1-109 GEN2
Solar/Wind Helper
0.102
238110AE1-109 GEN3
Solar/Wind Helper
0.102
238126S14_GEN_1
Solar/Wind Helper
0.764
23750501ELLIOTTS
Solar/Wind Helper
0.636
238152AF2-075_GEN
Solar/Wind Helper
0.611
238208AF1-136 C
Solar/Wind Helper
0.19
23546401DTGZ2-030
Solar/Wind Helper
0.077
237085AD2-009_GEN
Solar/Wind Helper
1.425
3138216PACIFIC
Solar/Wind Helper
0.038
316411AF1-147_GEN1
Solar/Wind Helper
0.754
316415AF1-147_GEN2
Solar/Wind Helper
0.754
944201AF1-088_MTX
Adder
106.522
957141AF2-008_MTX
Adder
53.261
NYPJM->LTFIMP_NY
CLTF
4.491
LGEELTFEXP_LGEE->PJM
CLTF
6.272
WECLTFEXP_WEC->PJM
CLTF
3.434
AG2-052LTFEXP_AG2-052->PJM
LTF
0.214
AH1-155LTFEXP_AH1-155->PJM
LTF
0.321
LAGNLTFEXP_LAGN->PJM
CLTF
14.169
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.052
TVALTFEXP_TVA->PJM
CLTF
7.036
CBM West 1LTFEXP_CBM-W1->PJM
CBM
126.393
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.84
MECLTFEXP_MEC->PJM
CLTF
14.465
SIGELTFEXP_SIGE->PJM
CLTF
0.467
CPLELTFEXP_CPLE->PJM
CLTF
1.288
CBM West 2LTFEXP_CBM-W2->PJM
CBM
105.476

Details for 01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line l/o AP_P1-3_MP-765-502T_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-502T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:139.36 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5284.61
MW Contribution:3.06
Bus #Bus NameTypeMW Contribution
962771AG1-126 GEN
Solar/Wind Harmer
29.494
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Harmer
0.006
970879AG2-548 GEN
Solar/Wind Harmer
6.304
940611AE2-048 GEN
Solar/Wind Harmer
17.215
941391AE2-136 GEN
Solar/Wind Harmer
9.698
270520AE2-214 GEN
Solar/Wind Harmer
0.011
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
4.145
972203AH1-686 GEN
Adder
2.298
270432AC2-029 GEN
Solar/Wind Harmer
3.085
970689AG2-444 GEN
Solar/Wind Harmer
14.206
270269AC2-059
Solar/Wind Harmer
0.004
270156DARBY CT1
Adder
8.832
270157DARBY CT2
Adder
8.81
270158DARBY CT3
Adder
8.67
945631AF1-228 GEN
Solar/Wind Harmer
0
270284AF1-227 GEN1
Solar/Wind Harmer
0.009
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
971985AH1-537 GEN
Solar/Wind Harmer
2.037
253383AE2-342_GEN
Solar/Wind Harmer
0.002
241973AD2-163_GEN1
Solar/Wind Harmer
0.005
943861AF1-054 GEN
Solar/Wind Harmer
2.627
943851AF1-053 GEN
Solar/Wind Harmer
1.82
270340AC2-060 GEN
Solar/Wind Harmer
0.008
24477305BRIDGE
Adder
0.338
241972AD1-140 GEN
Solar/Wind Harmer
0.734
270367AC2-061_GEN
Solar/Wind Harmer
0.005
253372AE2-315 SEC3
Adder
1.803
253372AE2-315 SEC3
Adder
1.803
25306009OHH W.
Adder
2.735
270578AF1-285 GEN2
Solar/Wind Harmer
0.44
253349AC2-067 GEN
Solar/Wind Harmer
2.077
253400AC2-068 GEN
Solar/Wind Harmer
0.835
252524AE2-267 GEN
Solar/Wind Harmer
0.002
25196408WSDLE3
Adder
8.32
25196308WSDLE2
Adder
8.248
25196208WSDLE1
Adder
8.227
25196708WSDLE6
Adder
8.207
25196508WSDLE4
Adder
8
270302AB2-170 GEN
Solar/Wind Harmer
0.004
270317AD1-130_GEN
Solar/Wind Harmer
0.009
971653AH1-327 GEN
Solar/Wind Harmer
0.917
25196108MFTGT2
Adder
1.429
25196108MFTGT2
Adder
1.327
972163AH1-664 GEN
Solar/Wind Harmer
7.187
972165AH1-665 GEN
Solar/Wind Harmer
5.756
971673AH1-337 GEN
Solar/Wind Harmer
4.191
971029AG2-637 GEN
Solar/Wind Harmer
9.664
270543AE2-219 C
Solar/Wind Harmer
0.004
270240V3-007_GEN2
Solar/Wind Harmer
0.002
24729505KEY G4
Adder
5.961
965101AG1-375 GEN
Solar/Wind Harmer
6.406
945581AF1-223 GEN
Solar/Wind Harmer
0
970115AG2-085 GEN
Solar/Wind Harmer
2.556
971609AH1-304 GEN
Solar/Wind Harmer
1.043
270024AE2-089 GEN
Solar/Wind Harmer
0.007
270594AE1-207 GEN
Solar/Wind Harmer
7.147
270071AF1-092 GEN
Solar/Wind Harmer
12.224
970289AG2-191 GEN
Solar/Wind Harmer
1.211
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
8.573
965051AG1-369 GEN
Solar/Wind Harmer
3.147
971347AH1-153 GEN
Solar/Wind Harmer
9.454
965041AG1-368 GEN
Solar/Wind Harmer
6.297
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
3.74
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.796
958391AF2-133 GEN
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.008
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
963841AG1-237 GEN
Solar/Wind Harmer
2.71
971771AH1-392 GEN
Solar/Wind Harmer
6.248
971769AH1-391 GEN
Solar/Wind Harmer
6.974
247607V1-011 GEN
Solar/Wind Harmer
0.001
971619AH1-309 GEN
Solar/Wind Harmer
2.801
274775LINCOLN ;6U
Adder
7.514
274776LINCOLN ;7U
Adder
7.514
274777LINCOLN ;8U
Adder
7.514
274814UNIV PK N;0U
Adder
4.489
274807UNIV PK N;3U
Adder
4.479
274805UNIV PK N;1U
Adder
4.459
274811UNIV PK N;7U
Adder
0.697
960591AF2-350 GEN
Solar/Wind Harmer
6.191
270399AC1-101 GEN
Solar/Wind Harmer
1.957
270400AC1-102 GEN
Solar/Wind Harmer
1.957
970833AG2-524 GEN
Solar/Wind Harmer
6.792
970833AG2-524 GEN
Solar/Wind Harmer
4.528
970179AG2-119 GEN
Solar/Wind Harmer
5.506
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
970169AG2-114 GEN
Solar/Wind Harmer
6.145
276868AE1-113 GEN
Solar/Wind Harmer
1.231
276882AE2-255 GEN
Solar/Wind Harmer
0.717
238152AF2-075_GEN
Solar/Wind Helper
0.593
23546401DTGZ2-030
Solar/Wind Helper
0.075
238109AE1-109 GEN2
Solar/Wind Helper
0.088
238110AE1-109 GEN3
Solar/Wind Helper
0.088
238208AF1-136 C
Solar/Wind Helper
0.18
237085AD2-009_GEN
Solar/Wind Helper
1.367
238126S14_GEN_1
Solar/Wind Helper
0.641
23559101PLEAS2
50/50
11.213
23684101S70BUS1
50/50
0.313
23562301OGROV1
50/50
2.427
24721705FLATG2
Adder
23.442
962761AG1-125 GEN
Solar/Wind Harmer
29.494
970149AG2-104 GEN
Solar/Wind Harmer
31.855
970155AG2-107 GEN
Solar/Wind Harmer
18.834
270510AE1-227 GEN1
Solar/Wind Harmer
1.907
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
970947AG2-589 GEN
Solar/Wind Harmer
0.239
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
927014AC1-188 GEN
Solar/Wind Harmer
0.004
270349AD2-093_GEN
Solar/Wind Harmer
0.005
270263AC1-001 GEN
Solar/Wind Harmer
0.698
24686105CER G3
Adder
8.253
24686505CER G6
Adder
8.242
270159DARBY CT4
Adder
8.691
24723205RIVRG3
Adder
18.473
253343AC1-166 GEN
Solar/Wind Harmer
0.003
253325AC1-069 GEN
Solar/Wind Harmer
0.011
970593AG2-378 GEN
Solar/Wind Harmer
1.53
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.657
253370AE2-315 SEC1
Adder
1.906
253371AE2-315 SEC2
Adder
1.803
25326309TAIT D
Adder
1.041
960071AF2-298 GEN
Solar/Wind Harmer
3.297
252507AC2-088 GEN
Solar/Wind Harmer
0.3
270223U2-072_GEN1
Solar/Wind Harmer
0.001
25194608D.CRK4
Adder
1.55
25196808ZIMRHP
Adder
71.347
270462AD2-086
Solar/Wind Harmer
0.014
25196008MFTGT1
Adder
1.296
970333AG2-219 GEN
Solar/Wind Harmer
4.624
945681AF1-233 GEN
Solar/Wind Harmer
12.186
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.707
247536S-71 GEN
Solar/Wind Harmer
0.258
965651AG1-433 GEN
Solar/Wind Harmer
1.879
958861AF2-177 GEN
Solar/Wind Harmer
2.776
945371AF1-202 GEN
Solar/Wind Harmer
0.001
971995AH1-542 GEN
Solar/Wind Harmer
2.347
970773AG2-487 GEN
Solar/Wind Harmer
1.131
270005AE1-210 C O1
Solar/Wind Harmer
1.387
965031AG1-367 GEN
Solar/Wind Harmer
6.4
970825AG2-519 GEN
Solar/Wind Harmer
2.27
970091AG2-072 GEN
Adder
70.193
270032AE2-172
Solar/Wind Harmer
4.254
970291AG2-192 GEN
Solar/Wind Harmer
0.829
970245AG2-165 GEN
Solar/Wind Harmer
2.761
276903AD2-071 C
Solar/Wind Harmer
7.113
965011AG1-365 GEN
Solar/Wind Harmer
6.333
247521TR3_G114
Solar/Wind Harmer
0.23
270246TR4_N_V150
Solar/Wind Harmer
0.041
24728605AND G2
Adder
3.466
339216AC1-074 GEN
Solar/Wind Harmer
0.172
965421AG1-410 GEN
Solar/Wind Harmer
18.858
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
7.853
246936BC-WTG1
Solar/Wind Harmer
0.255
24791305MDL-5G
Solar/Wind Harmer
0.001
270489AE1-102 GEN1
Solar/Wind Harmer
0.817
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.162
24695305TIMB G C
Solar/Wind Harmer
0.002
270055AF2-134 C O1
Solar/Wind Harmer
0.005
970373AG2-245 GEN
Solar/Wind Harmer
13.169
270063AE2-323 C
Solar/Wind Harmer
0.005
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.002
24639705ELKHART HY
Adder
0.137
963741AG1-226 GEN
Solar/Wind Harmer
14.772
945111AF1-176 GEN
Solar/Wind Harmer
11.105
270505AE1-170 C O1
Solar/Wind Harmer
6.535
270445AC2-157 GEN2
Solar/Wind Harmer
0.003
274773LINCOLN ;4U
Adder
7.514
274774LINCOLN ;5U
Adder
7.514
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.241
274751CRETE EC ;1U
Adder
7.332
274754CRETE EC ;4U
Adder
7.332
274723RIVER EC ;12
Adder
15.938
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.45
276776AD2-060 GEN
Solar/Wind Harmer
0.646
941551AE2-152 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
939401AE1-172 GEN
Solar/Wind Harmer
4.613
276691AA1-018 GEN1
Solar/Wind Harmer
0.745
276901AD2-066 C O1
Solar/Wind Harmer
0.006
944231AF1-091 GEN
Solar/Wind Harmer
1.635
971997AH1-543 GEN
Solar/Wind Harmer
3.22
23583801GRNGAP
Solar/Wind Helper
4.858
316095T157 G97
Solar/Wind Helper
1.299
238147AE2-230_GEN1
Solar/Wind Helper
0.415
238149AF1-291A_GEN
Solar/Wind Helper
0.119
238108AE1-109 GEN1
Solar/Wind Helper
0.088
237061AD1-155 GEN
Solar/Wind Helper
0.045
238185AF2-356 C
Solar/Wind Helper
1.996
238221AF1-254 C O1
Solar/Wind Helper
0.228
235067AD1-061 GEN
Solar/Wind Helper
0.412
235531U2-073 GEN
Solar/Wind Helper
2.523
238117U2-030
Solar/Wind Helper
0.26
970935AG2-582 GEN
50/50
1217.062
24318905MLG2
50/50
4.656
270471AD2-092_GEN
Solar/Wind Harmer
0.005
971073AG2-665 GEN
Solar/Wind Harmer
6.304
24685805CER G1
Adder
8.199
24685905CER G2
Adder
8.199
972269AH1-719 GEN
Adder
2.268
24723005RIVRG1
Adder
18.473
24723105RIVRG2
Adder
18.473
942861AE2-305 GEN
Solar/Wind Harmer
5.322
270518AE2-148 GEN
Solar/Wind Harmer
0.589
970077AG2-063 GEN
Solar/Wind Harmer
3.909
962581AG1-107 GEN
Solar/Wind Harmer
0.001
972159AH1-661 GEN
Adder
0.952
253394AE2-221_GEN
Solar/Wind Harmer
0.008
253398AE2-221_GEN2
Solar/Wind Harmer
0.008
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
270186AC1-089 GEN
Solar/Wind Harmer
0.004
25326109MON D
Adder
1.252
253370AE2-315 SEC1
Adder
1.906
25322209TAIT E
Adder
9.269
25322209TAIT E
Adder
9.061
25183208HLCRTG
Solar/Wind Harmer
0.01
964601AG1-323 GEN
Solar/Wind Harmer
2.647
964601AG1-323 GEN
Solar/Wind Harmer
1.765
252509AD1-136 GEN
Solar/Wind Harmer
0.033
252519AF1-045_GEN
Solar/Wind Harmer
5.748
252516AE2-318_GEN
Solar/Wind Harmer
5.098
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
938701AE1-092 GEN
Solar/Wind Harmer
10.591
971655AH1-328 GEN
Solar/Wind Harmer
2.34
25194408D.CRK1
Adder
7.132
25194508D.CRK3
Adder
1.333
253378AE2-206_GEN
Solar/Wind Harmer
0.003
276820AF1-078_GEN
Solar/Wind Harmer
0.002
970329AG2-216 GEN
Solar/Wind Harmer
2.833
25326509SID D
Adder
1.231
970239AG2-162 GEN
Solar/Wind Harmer
1.617
24728805RICHG1
Adder
3.489
24728905RICHG2
Adder
3.489
970883AG2-550 GEN
Solar/Wind Harmer
6.429
970885AG2-551 GEN
Solar/Wind Harmer
2.143
270383AD1-128 GEN
Solar/Wind Harmer
0.004
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
247621Y3-024
Adder
0.222
944541AF1-119 GEN
Solar/Wind Harmer
0.429
960971AF2-388 GEN
Solar/Wind Harmer
3.759
270201AC2-176 GEN
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
0.48
970825AG2-519 GEN
Solar/Wind Harmer
7.086
960441AF2-335 GEN
Solar/Wind Harmer
6.391
270599AE1-208 GEN
Solar/Wind Harmer
5.854
270031AE2-169
Solar/Wind Harmer
3.512
971613AH1-306 GEN
Solar/Wind Harmer
3.063
942221AE2-234 GEN
Solar/Wind Harmer
0.032
970321AG2-212 GEN
Solar/Wind Harmer
2.761
970611AG2-400 GEN
Solar/Wind Harmer
6.333
970627AG2-408 GEN
Solar/Wind Harmer
1.9
970235AG2-159 GEN
Solar/Wind Harmer
3.847
970235AG2-159 GEN
Solar/Wind Harmer
2.207
339221AD2-048_GEN
Solar/Wind Harmer
0.004
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
971199AH1-059 GEN
Solar/Wind Harmer
2.513
246938BC-WTG3
Solar/Wind Harmer
0.228
246937BC-WTG2
Solar/Wind Harmer
0.255
972043AH1-570 GEN
Solar/Wind Harmer
1.633
972045AH1-571 GEN
Solar/Wind Harmer
1.308
966841AG1-555 GEN
Solar/Wind Harmer
0.709
944971AF1-162 GEN
Solar/Wind Harmer
6.265
965681AG1-436 GEN
Solar/Wind Harmer
7.82
965791AG1-447 GEN
Solar/Wind Harmer
5.734
270216AD2-079_GEN
Solar/Wind Harmer
0.001
247620Y3-023
Adder
0.412
270526AF1-158 GEN
Solar/Wind Harmer
0.008
24441505OLIV SLR
Solar/Wind Harmer
0
270007AE1-245 C
Solar/Wind Harmer
0.002
970241AG2-163 GEN
Solar/Wind Harmer
3.641
957891AF2-083 GEN
Solar/Wind Harmer
0.001
270444AC2-157 GEN1
Solar/Wind Harmer
0.003
971587AH1-292 GEN
Solar/Wind Harmer
4.56
961051AF2-396 GEN
Solar/Wind Harmer
12.428
961051AF2-396 GEN
Solar/Wind Harmer
8.285
274770LINCOLN ;1U
Adder
7.514
274771LINCOLN ;2U
Adder
7.514
971125AH1-004 GEN
Solar/Wind Harmer
2.483
970107AG2-081 GEN
Solar/Wind Harmer
1.862
960161AF2-307 GEN
Solar/Wind Harmer
4.096
945391AF1-204 GEN
Solar/Wind Harmer
6.587
274888KELLY CRK;1U
Solar/Wind Harmer
0.364
274887GEN-1.85
Solar/Wind Harmer
0.163
276843GEN-1.7
Solar/Wind Harmer
0.2
958011AF2-095 GEN
Solar/Wind Harmer
8.915
970623AG2-406 GEN
Solar/Wind Harmer
1.132
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
241960AC2-195 GEN
Solar/Wind Harmer
0.005
958481AF2-142 GEN
Solar/Wind Harmer
9.231
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.833
971573AH1-285 GEN
Solar/Wind Harmer
1.146
958491AF2-143 GEN
Solar/Wind Harmer
9.212
274879MINONK ;1U
Solar/Wind Harmer
0.259
238175AF1-290_GEN
Solar/Wind Helper
0.126
238169AE2-226 GEN1
Solar/Wind Helper
0.582
238170AE2-226 GEN2
Solar/Wind Helper
0.582
235020AA1-095 C
Solar/Wind Helper
0.044
23777901MDS_W4-102
Solar/Wind Helper
0.146
238120AE2-309 GEN
Solar/Wind Helper
0.406
237034AC2-136 C
Solar/Wind Helper
0.189
237002AB1-128_GEN
Solar/Wind Helper
0.369
235063AE1-101 C2
Solar/Wind Helper
1.38
237001AB1-127_GEN
Solar/Wind Helper
0.368
23777801MSM_W1-116
Solar/Wind Helper
0.096
962691AG1-118 GEN
Solar/Wind Harmer
3.447
23559001PLEAS1
50/50
11.213
23684201S70BUS2
50/50
0.319
23562401OGROV2
50/50
2.411
24318805MLG1
50/50
6.319
24721905FLATG4
Adder
23.442
970153AG2-106 GEN
Solar/Wind Harmer
18.834
270512AE1-227 GEN2
Solar/Wind Harmer
1.907
971191AH1-055 GEN
Solar/Wind Harmer
18.237
270291AC1-194 GEN
Solar/Wind Harmer
5.533
961921AG1-034 GEN
Solar/Wind Harmer
6.218
270273AD2-016 GEN
Solar/Wind Harmer
0.721
972173AH1-669 GEN
Solar/Wind Harmer
3.478
241955AC1-078 GEN
Solar/Wind Harmer
0.006
24686205CER G4
Adder
8.21
24686405CER G5
Adder
8.177
942051AE2-217 GEN
Solar/Wind Harmer
12.316
253338AC1-165 GEN
Solar/Wind Harmer
0.003
253333AC1-068 GEN
Solar/Wind Harmer
0.011
241974AD2-163_GEN2
Solar/Wind Harmer
0.005
253415AE1-040 GEN
Solar/Wind Harmer
0.003
970605AG2-385 GEN
Solar/Wind Harmer
4.136
253406AD2-031_GEN
Solar/Wind Harmer
0.499
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
8.654
253370AE2-315 SEC1
Adder
1.906
253371AE2-315 SEC2
Adder
1.803
270391AF1-285 GEN3
Solar/Wind Harmer
0.44
970191AG2-125 GEN
Solar/Wind Harmer
1.697
252510AF1-249 C
Solar/Wind Harmer
0.051
25196608WSDLE5
Adder
8.083
25194608D.CRK4
Adder
1.55
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270222AC2-111 GEN
Solar/Wind Harmer
3.293
25196008MFTGT1
Adder
1.255
970243AG2-164 GEN
Solar/Wind Harmer
3.783
970519AG2-331 GEN
Solar/Wind Harmer
16.815
970699AG2-449 GEN
Solar/Wind Harmer
1.617
972167AH1-666 GEN
Solar/Wind Harmer
5.174
958171AF2-111 GEN
Solar/Wind Harmer
16.157
270437AC2-090 C
Solar/Wind Harmer
0.003
944531AF1-118 GEN
Solar/Wind Harmer
28.735
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
9.603
270356AE2-297 GEN
Solar/Wind Harmer
0.009
946031AF1-268 GEN
Solar/Wind Harmer
6.09
958821AF2-173 GEN
Solar/Wind Harmer
8.959
270004AE1-209 GEN
Solar/Wind Harmer
1.387
971617AH1-308 GEN
Solar/Wind Harmer
5.319
970289AG2-191 GEN
Solar/Wind Harmer
0.701
970291AG2-192 GEN
Solar/Wind Harmer
0.638
970513AG2-328 GEN
Solar/Wind Harmer
2.761
970517AG2-330 GEN
Solar/Wind Harmer
16.566
247642Z2-115 C
Solar/Wind Harmer
0.003
270043AE2-236 GEN
Solar/Wind Harmer
4.072
959331AF2-224 GEN
Solar/Wind Harmer
4.433
965021AG1-366 GEN
Solar/Wind Harmer
2.111
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.041
24728705AND G3
Adder
7.25
24728505AND G1
Adder
3.466
970349AG2-230 GEN
Solar/Wind Harmer
9.454
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.281
270491AE1-102 GEN2
Solar/Wind Harmer
0.817
964401AG1-302 GEN
Solar/Wind Harmer
0.001
970031AG2-029 GEN
Solar/Wind Harmer
4.079
270535AF1-215 GEN1
Solar/Wind Harmer
0.008
270053AF1-130 C
Solar/Wind Harmer
1.414
247643Z2-116 C
Solar/Wind Harmer
0
24642205MAYFLWER
Adder
0.568
945111AF1-176 GEN
Solar/Wind Harmer
5.045
274772LINCOLN ;3U
Adder
7.514
274752CRETE EC ;2U
Adder
7.332
274753CRETE EC ;3U
Adder
7.332
274724RIVER EC ;11
Adder
15.751
970193AG2-126 GEN
Solar/Wind Harmer
9.3
276806AD2-047 C O1
Solar/Wind Harmer
3.508
970941AG2-585 GEN
Solar/Wind Harmer
7.739
276897AD1-100 C
Solar/Wind Harmer
0.008
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
20.212
270258AD1-119 GEN
Solar/Wind Harmer
0.002
276893AG1-478 C
Solar/Wind Harmer
0.245
24441205WTRV SLR C
Solar/Wind Harmer
0
943121AE2-341 GEN
Solar/Wind Harmer
10.327
943591AF1-030 GEN
Solar/Wind Harmer
6.867
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
270404AC1-167 GEN
Solar/Wind Harmer
0.003
276805AD2-038 GEN
Solar/Wind Harmer
0.002
316097T157 G90
Solar/Wind Helper
1.299
964991AG1-363 GEN
Solar/Wind Helper
4.135
238148AE2-230_GEN2
Solar/Wind Helper
0.417
23750701CROSSCHOOL
Solar/Wind Helper
1.155
237080AD1-060 GEN
Solar/Wind Helper
0.284
237038AE2-054 C
Solar/Wind Helper
0.226
235062AE1-101 C1
Solar/Wind Helper
1.38
238127S14_GEN_2
Solar/Wind Helper
0.641
23779801AA1-109
Solar/Wind Helper
0.162
238118U2-030_1
Solar/Wind Helper
0.26
944201AF1-088_MTX
Adder
103.64
957141AF2-008_MTX
Adder
51.82
NYPJM->LTFIMP_NY
CLTF
4.417
LGEELTFEXP_LGEE->PJM
CLTF
6.111
WECLTFEXP_WEC->PJM
CLTF
3.336
AG2-052LTFEXP_AG2-052->PJM
LTF
0.208
AH1-155LTFEXP_AH1-155->PJM
LTF
0.312
LAGNLTFEXP_LAGN->PJM
CLTF
13.832
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.925
TVALTFEXP_TVA->PJM
CLTF
6.876
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.614
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.188
MECLTFEXP_MEC->PJM
CLTF
14.066
SIGELTFEXP_SIGE->PJM
CLTF
0.455
CPLELTFEXP_CPLE->PJM
CLTF
1.286
CBM West 2LTFEXP_CBM-W2->PJM
CBM
102.798

Details for 01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-028_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-028_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:139.32 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5282.91
MW Contribution:3.06
Bus #Bus NameTypeMW Contribution
962771AG1-126 GEN
Solar/Wind Harmer
29.494
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Harmer
0.006
970879AG2-548 GEN
Solar/Wind Harmer
6.304
940611AE2-048 GEN
Solar/Wind Harmer
17.215
941391AE2-136 GEN
Solar/Wind Harmer
9.698
270520AE2-214 GEN
Solar/Wind Harmer
0.011
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
4.145
972203AH1-686 GEN
Adder
2.298
270432AC2-029 GEN
Solar/Wind Harmer
3.085
970689AG2-444 GEN
Solar/Wind Harmer
14.206
270269AC2-059
Solar/Wind Harmer
0.004
270156DARBY CT1
Adder
8.832
270157DARBY CT2
Adder
8.81
270158DARBY CT3
Adder
8.67
945631AF1-228 GEN
Solar/Wind Harmer
0
270284AF1-227 GEN1
Solar/Wind Harmer
0.009
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
971985AH1-537 GEN
Solar/Wind Harmer
2.037
253383AE2-342_GEN
Solar/Wind Harmer
0.002
241973AD2-163_GEN1
Solar/Wind Harmer
0.005
943861AF1-054 GEN
Solar/Wind Harmer
2.627
943851AF1-053 GEN
Solar/Wind Harmer
1.82
270340AC2-060 GEN
Solar/Wind Harmer
0.008
24477305BRIDGE
Adder
0.338
241972AD1-140 GEN
Solar/Wind Harmer
0.734
270367AC2-061_GEN
Solar/Wind Harmer
0.005
253372AE2-315 SEC3
Adder
1.803
253372AE2-315 SEC3
Adder
1.803
25306009OHH W.
Adder
2.735
270578AF1-285 GEN2
Solar/Wind Harmer
0.44
253349AC2-067 GEN
Solar/Wind Harmer
2.077
253400AC2-068 GEN
Solar/Wind Harmer
0.835
252524AE2-267 GEN
Solar/Wind Harmer
0.002
25196408WSDLE3
Adder
8.32
25196308WSDLE2
Adder
8.248
25196208WSDLE1
Adder
8.227
25196708WSDLE6
Adder
8.207
25196508WSDLE4
Adder
8
270302AB2-170 GEN
Solar/Wind Harmer
0.004
270317AD1-130_GEN
Solar/Wind Harmer
0.009
971653AH1-327 GEN
Solar/Wind Harmer
0.917
25196108MFTGT2
Adder
1.429
25196108MFTGT2
Adder
1.327
972163AH1-664 GEN
Solar/Wind Harmer
7.187
972165AH1-665 GEN
Solar/Wind Harmer
5.756
971673AH1-337 GEN
Solar/Wind Harmer
4.191
971029AG2-637 GEN
Solar/Wind Harmer
9.664
270543AE2-219 C
Solar/Wind Harmer
0.004
270240V3-007_GEN2
Solar/Wind Harmer
0.002
24729505KEY G4
Adder
5.961
965101AG1-375 GEN
Solar/Wind Harmer
6.406
945581AF1-223 GEN
Solar/Wind Harmer
0
970115AG2-085 GEN
Solar/Wind Harmer
2.556
971609AH1-304 GEN
Solar/Wind Harmer
1.043
270024AE2-089 GEN
Solar/Wind Harmer
0.007
270594AE1-207 GEN
Solar/Wind Harmer
7.147
270071AF1-092 GEN
Solar/Wind Harmer
12.224
970289AG2-191 GEN
Solar/Wind Harmer
1.211
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
8.573
965051AG1-369 GEN
Solar/Wind Harmer
3.147
971347AH1-153 GEN
Solar/Wind Harmer
9.454
965041AG1-368 GEN
Solar/Wind Harmer
6.297
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
3.74
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.796
958391AF2-133 GEN
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.008
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
963841AG1-237 GEN
Solar/Wind Harmer
2.71
971771AH1-392 GEN
Solar/Wind Harmer
6.248
971769AH1-391 GEN
Solar/Wind Harmer
6.974
247607V1-011 GEN
Solar/Wind Harmer
0.001
971619AH1-309 GEN
Solar/Wind Harmer
2.801
274775LINCOLN ;6U
Adder
7.514
274776LINCOLN ;7U
Adder
7.514
274777LINCOLN ;8U
Adder
7.514
274814UNIV PK N;0U
Adder
4.489
274807UNIV PK N;3U
Adder
4.479
274805UNIV PK N;1U
Adder
4.459
274811UNIV PK N;7U
Adder
0.697
960591AF2-350 GEN
Solar/Wind Harmer
6.191
270399AC1-101 GEN
Solar/Wind Harmer
1.957
270400AC1-102 GEN
Solar/Wind Harmer
1.957
970833AG2-524 GEN
Solar/Wind Harmer
6.792
970833AG2-524 GEN
Solar/Wind Harmer
4.528
970179AG2-119 GEN
Solar/Wind Harmer
5.506
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
970169AG2-114 GEN
Solar/Wind Harmer
6.145
276868AE1-113 GEN
Solar/Wind Harmer
1.231
276882AE2-255 GEN
Solar/Wind Harmer
0.717
23559101PLEAS2
50/50
11.213
23684101S70BUS1
50/50
0.313
23562301OGROV1
50/50
2.427
24721705FLATG2
Adder
23.442
962761AG1-125 GEN
Solar/Wind Harmer
29.494
970149AG2-104 GEN
Solar/Wind Harmer
31.855
970155AG2-107 GEN
Solar/Wind Harmer
18.834
270510AE1-227 GEN1
Solar/Wind Harmer
1.907
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
970947AG2-589 GEN
Solar/Wind Harmer
0.239
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
927014AC1-188 GEN
Solar/Wind Harmer
0.004
270349AD2-093_GEN
Solar/Wind Harmer
0.005
270263AC1-001 GEN
Solar/Wind Harmer
0.698
24686105CER G3
Adder
8.253
24686505CER G6
Adder
8.242
270159DARBY CT4
Adder
8.691
24723205RIVRG3
Adder
18.473
253343AC1-166 GEN
Solar/Wind Harmer
0.003
253325AC1-069 GEN
Solar/Wind Harmer
0.011
970593AG2-378 GEN
Solar/Wind Harmer
1.53
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.657
253370AE2-315 SEC1
Adder
1.906
253371AE2-315 SEC2
Adder
1.803
25326309TAIT D
Adder
1.041
960071AF2-298 GEN
Solar/Wind Harmer
3.297
252507AC2-088 GEN
Solar/Wind Harmer
0.3
270223U2-072_GEN1
Solar/Wind Harmer
0.001
25194608D.CRK4
Adder
1.55
25196808ZIMRHP
Adder
71.347
270462AD2-086
Solar/Wind Harmer
0.014
25196008MFTGT1
Adder
1.296
970333AG2-219 GEN
Solar/Wind Harmer
4.624
945681AF1-233 GEN
Solar/Wind Harmer
12.186
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.707
247536S-71 GEN
Solar/Wind Harmer
0.258
965651AG1-433 GEN
Solar/Wind Harmer
1.879
958861AF2-177 GEN
Solar/Wind Harmer
2.776
945371AF1-202 GEN
Solar/Wind Harmer
0.001
971995AH1-542 GEN
Solar/Wind Harmer
2.347
970773AG2-487 GEN
Solar/Wind Harmer
1.131
270005AE1-210 C O1
Solar/Wind Harmer
1.387
965031AG1-367 GEN
Solar/Wind Harmer
6.4
970825AG2-519 GEN
Solar/Wind Harmer
2.27
970091AG2-072 GEN
Adder
70.193
270032AE2-172
Solar/Wind Harmer
4.254
970291AG2-192 GEN
Solar/Wind Harmer
0.829
970245AG2-165 GEN
Solar/Wind Harmer
2.761
276903AD2-071 C
Solar/Wind Harmer
7.113
965011AG1-365 GEN
Solar/Wind Harmer
6.333
247521TR3_G114
Solar/Wind Harmer
0.23
270246TR4_N_V150
Solar/Wind Harmer
0.041
24728605AND G2
Adder
3.466
339216AC1-074 GEN
Solar/Wind Harmer
0.172
965421AG1-410 GEN
Solar/Wind Harmer
18.858
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
7.853
246936BC-WTG1
Solar/Wind Harmer
0.255
24791305MDL-5G
Solar/Wind Harmer
0.001
970935AG2-582 GEN
50/50
1217.062
24318905MLG2
50/50
4.656
270471AD2-092_GEN
Solar/Wind Harmer
0.005
971073AG2-665 GEN
Solar/Wind Harmer
6.304
24685805CER G1
Adder
8.199
24685905CER G2
Adder
8.199
972269AH1-719 GEN
Adder
2.268
24723005RIVRG1
Adder
18.473
24723105RIVRG2
Adder
18.473
942861AE2-305 GEN
Solar/Wind Harmer
5.322
270518AE2-148 GEN
Solar/Wind Harmer
0.589
970077AG2-063 GEN
Solar/Wind Harmer
3.909
962581AG1-107 GEN
Solar/Wind Harmer
0.001
972159AH1-661 GEN
Adder
0.952
253394AE2-221_GEN
Solar/Wind Harmer
0.008
253398AE2-221_GEN2
Solar/Wind Harmer
0.008
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
270186AC1-089 GEN
Solar/Wind Harmer
0.004
25326109MON D
Adder
1.252
253370AE2-315 SEC1
Adder
1.906
25322209TAIT E
Adder
9.269
25322209TAIT E
Adder
9.061
25183208HLCRTG
Solar/Wind Harmer
0.01
964601AG1-323 GEN
Solar/Wind Harmer
2.647
964601AG1-323 GEN
Solar/Wind Harmer
1.765
252509AD1-136 GEN
Solar/Wind Harmer
0.033
252519AF1-045_GEN
Solar/Wind Harmer
5.748
252516AE2-318_GEN
Solar/Wind Harmer
5.098
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
938701AE1-092 GEN
Solar/Wind Harmer
10.591
971655AH1-328 GEN
Solar/Wind Harmer
2.34
25194408D.CRK1
Adder
7.132
25194508D.CRK3
Adder
1.333
253378AE2-206_GEN
Solar/Wind Harmer
0.003
276820AF1-078_GEN
Solar/Wind Harmer
0.002
970329AG2-216 GEN
Solar/Wind Harmer
2.833
25326509SID D
Adder
1.231
970239AG2-162 GEN
Solar/Wind Harmer
1.617
24728805RICHG1
Adder
3.489
24728905RICHG2
Adder
3.489
970883AG2-550 GEN
Solar/Wind Harmer
6.429
970885AG2-551 GEN
Solar/Wind Harmer
2.143
270383AD1-128 GEN
Solar/Wind Harmer
0.004
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
247621Y3-024
Adder
0.222
944541AF1-119 GEN
Solar/Wind Harmer
0.429
960971AF2-388 GEN
Solar/Wind Harmer
3.759
270201AC2-176 GEN
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
0.48
970825AG2-519 GEN
Solar/Wind Harmer
7.086
960441AF2-335 GEN
Solar/Wind Harmer
6.391
270599AE1-208 GEN
Solar/Wind Harmer
5.854
270031AE2-169
Solar/Wind Harmer
3.512
971613AH1-306 GEN
Solar/Wind Harmer
3.063
942221AE2-234 GEN
Solar/Wind Harmer
0.032
970321AG2-212 GEN
Solar/Wind Harmer
2.761
970611AG2-400 GEN
Solar/Wind Harmer
6.333
970627AG2-408 GEN
Solar/Wind Harmer
1.9
970235AG2-159 GEN
Solar/Wind Harmer
3.847
970235AG2-159 GEN
Solar/Wind Harmer
2.207
339221AD2-048_GEN
Solar/Wind Harmer
0.004
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
971199AH1-059 GEN
Solar/Wind Harmer
2.513
246938BC-WTG3
Solar/Wind Harmer
0.228
246937BC-WTG2
Solar/Wind Harmer
0.255
972043AH1-570 GEN
Solar/Wind Harmer
1.633
972045AH1-571 GEN
Solar/Wind Harmer
1.308
966841AG1-555 GEN
Solar/Wind Harmer
0.709
944971AF1-162 GEN
Solar/Wind Harmer
6.265
965681AG1-436 GEN
Solar/Wind Harmer
7.82
965791AG1-447 GEN
Solar/Wind Harmer
5.734
270216AD2-079_GEN
Solar/Wind Harmer
0.001
247620Y3-023
Adder
0.412
270526AF1-158 GEN
Solar/Wind Harmer
0.008
24441505OLIV SLR
Solar/Wind Harmer
0
270007AE1-245 C
Solar/Wind Harmer
0.002
970241AG2-163 GEN
Solar/Wind Harmer
3.641
957891AF2-083 GEN
Solar/Wind Harmer
0.001
270444AC2-157 GEN1
Solar/Wind Harmer
0.003
971587AH1-292 GEN
Solar/Wind Harmer
4.56
961051AF2-396 GEN
Solar/Wind Harmer
12.428
961051AF2-396 GEN
Solar/Wind Harmer
8.285
274770LINCOLN ;1U
Adder
7.514
274771LINCOLN ;2U
Adder
7.514
971125AH1-004 GEN
Solar/Wind Harmer
2.483
970107AG2-081 GEN
Solar/Wind Harmer
1.862
960161AF2-307 GEN
Solar/Wind Harmer
4.096
945391AF1-204 GEN
Solar/Wind Harmer
6.587
274888KELLY CRK;1U
Solar/Wind Harmer
0.364
274887GEN-1.85
Solar/Wind Harmer
0.163
276843GEN-1.7
Solar/Wind Harmer
0.2
958011AF2-095 GEN
Solar/Wind Harmer
8.915
970623AG2-406 GEN
Solar/Wind Harmer
1.132
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
241960AC2-195 GEN
Solar/Wind Harmer
0.005
958481AF2-142 GEN
Solar/Wind Harmer
9.231
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.833
971573AH1-285 GEN
Solar/Wind Harmer
1.146
958491AF2-143 GEN
Solar/Wind Harmer
9.212
274879MINONK ;1U
Solar/Wind Harmer
0.259
238175AF1-290_GEN
Solar/Wind Helper
0.126
238169AE2-226 GEN1
Solar/Wind Helper
0.582
238170AE2-226 GEN2
Solar/Wind Helper
0.582
235020AA1-095 C
Solar/Wind Helper
0.044
23559001PLEAS1
50/50
11.213
23684201S70BUS2
50/50
0.319
23562401OGROV2
50/50
2.411
24318805MLG1
50/50
6.319
24721905FLATG4
Adder
23.442
970153AG2-106 GEN
Solar/Wind Harmer
18.834
270512AE1-227 GEN2
Solar/Wind Harmer
1.907
971191AH1-055 GEN
Solar/Wind Harmer
18.237
270291AC1-194 GEN
Solar/Wind Harmer
5.533
961921AG1-034 GEN
Solar/Wind Harmer
6.218
270273AD2-016 GEN
Solar/Wind Harmer
0.721
972173AH1-669 GEN
Solar/Wind Harmer
3.478
241955AC1-078 GEN
Solar/Wind Harmer
0.006
24686205CER G4
Adder
8.21
24686405CER G5
Adder
8.177
942051AE2-217 GEN
Solar/Wind Harmer
12.316
253338AC1-165 GEN
Solar/Wind Harmer
0.003
253333AC1-068 GEN
Solar/Wind Harmer
0.011
241974AD2-163_GEN2
Solar/Wind Harmer
0.005
253415AE1-040 GEN
Solar/Wind Harmer
0.003
970605AG2-385 GEN
Solar/Wind Harmer
4.136
253406AD2-031_GEN
Solar/Wind Harmer
0.499
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
8.654
253370AE2-315 SEC1
Adder
1.906
253371AE2-315 SEC2
Adder
1.803
270391AF1-285 GEN3
Solar/Wind Harmer
0.44
970191AG2-125 GEN
Solar/Wind Harmer
1.697
252510AF1-249 C
Solar/Wind Harmer
0.051
25196608WSDLE5
Adder
8.083
25194608D.CRK4
Adder
1.55
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270222AC2-111 GEN
Solar/Wind Harmer
3.293
25196008MFTGT1
Adder
1.255
970243AG2-164 GEN
Solar/Wind Harmer
3.783
970519AG2-331 GEN
Solar/Wind Harmer
16.815
970699AG2-449 GEN
Solar/Wind Harmer
1.617
972167AH1-666 GEN
Solar/Wind Harmer
5.174
958171AF2-111 GEN
Solar/Wind Harmer
16.157
270437AC2-090 C
Solar/Wind Harmer
0.003
944531AF1-118 GEN
Solar/Wind Harmer
28.735
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
9.603
270356AE2-297 GEN
Solar/Wind Harmer
0.009
946031AF1-268 GEN
Solar/Wind Harmer
6.09
958821AF2-173 GEN
Solar/Wind Harmer
8.959
270004AE1-209 GEN
Solar/Wind Harmer
1.387
971617AH1-308 GEN
Solar/Wind Harmer
5.319
970289AG2-191 GEN
Solar/Wind Harmer
0.701
970291AG2-192 GEN
Solar/Wind Harmer
0.638
970513AG2-328 GEN
Solar/Wind Harmer
2.761
970517AG2-330 GEN
Solar/Wind Harmer
16.566
247642Z2-115 C
Solar/Wind Harmer
0.003
270043AE2-236 GEN
Solar/Wind Harmer
4.072
959331AF2-224 GEN
Solar/Wind Harmer
4.433
965021AG1-366 GEN
Solar/Wind Harmer
2.111
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.041
24728705AND G3
Adder
7.25
24728505AND G1
Adder
3.466
970349AG2-230 GEN
Solar/Wind Harmer
9.454
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.281
270491AE1-102 GEN2
Solar/Wind Harmer
0.817
964401AG1-302 GEN
Solar/Wind Harmer
0.001
970031AG2-029 GEN
Solar/Wind Harmer
4.079
270535AF1-215 GEN1
Solar/Wind Harmer
0.008
270053AF1-130 C
Solar/Wind Harmer
1.414
247643Z2-116 C
Solar/Wind Harmer
0
24642205MAYFLWER
Adder
0.568
945111AF1-176 GEN
Solar/Wind Harmer
5.045
274772LINCOLN ;3U
Adder
7.514
274752CRETE EC ;2U
Adder
7.332
274753CRETE EC ;3U
Adder
7.332
274724RIVER EC ;11
Adder
15.751
970193AG2-126 GEN
Solar/Wind Harmer
9.3
276806AD2-047 C O1
Solar/Wind Harmer
3.508
970941AG2-585 GEN
Solar/Wind Harmer
7.739
276897AD1-100 C
Solar/Wind Harmer
0.008
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
20.212
270258AD1-119 GEN
Solar/Wind Harmer
0.002
276893AG1-478 C
Solar/Wind Harmer
0.245
24441205WTRV SLR C
Solar/Wind Harmer
0
943121AE2-341 GEN
Solar/Wind Harmer
10.327
943591AF1-030 GEN
Solar/Wind Harmer
6.867
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
270404AC1-167 GEN
Solar/Wind Harmer
0.003
276805AD2-038 GEN
Solar/Wind Harmer
0.002
316097T157 G90
Solar/Wind Helper
1.299
964991AG1-363 GEN
Solar/Wind Helper
4.135
238148AE2-230_GEN2
Solar/Wind Helper
0.417
23750701CROSSCHOOL
Solar/Wind Helper
1.155
237080AD1-060 GEN
Solar/Wind Helper
0.284
237038AE2-054 C
Solar/Wind Helper
0.226
235062AE1-101 C1
Solar/Wind Helper
1.38
238127S14_GEN_2
Solar/Wind Helper
0.641
23779801AA1-109
Solar/Wind Helper
0.162
238118U2-030_1
Solar/Wind Helper
0.26
270489AE1-102 GEN1
Solar/Wind Harmer
0.817
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.162
24695305TIMB G C
Solar/Wind Harmer
0.002
270055AF2-134 C O1
Solar/Wind Harmer
0.005
970373AG2-245 GEN
Solar/Wind Harmer
13.169
270063AE2-323 C
Solar/Wind Harmer
0.005
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.002
24639705ELKHART HY
Adder
0.137
963741AG1-226 GEN
Solar/Wind Harmer
14.772
945111AF1-176 GEN
Solar/Wind Harmer
11.105
270505AE1-170 C O1
Solar/Wind Harmer
6.535
270445AC2-157 GEN2
Solar/Wind Harmer
0.003
274773LINCOLN ;4U
Adder
7.514
274774LINCOLN ;5U
Adder
7.514
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.241
274751CRETE EC ;1U
Adder
7.332
274754CRETE EC ;4U
Adder
7.332
274723RIVER EC ;12
Adder
15.938
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.45
276776AD2-060 GEN
Solar/Wind Harmer
0.646
941551AE2-152 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
939401AE1-172 GEN
Solar/Wind Harmer
4.613
276691AA1-018 GEN1
Solar/Wind Harmer
0.745
276901AD2-066 C O1
Solar/Wind Harmer
0.006
944231AF1-091 GEN
Solar/Wind Harmer
1.635
971997AH1-543 GEN
Solar/Wind Harmer
3.22
23583801GRNGAP
Solar/Wind Helper
4.858
316095T157 G97
Solar/Wind Helper
1.299
238147AE2-230_GEN1
Solar/Wind Helper
0.415
238149AF1-291A_GEN
Solar/Wind Helper
0.119
238108AE1-109 GEN1
Solar/Wind Helper
0.088
237061AD1-155 GEN
Solar/Wind Helper
0.045
238185AF2-356 C
Solar/Wind Helper
1.996
238221AF1-254 C O1
Solar/Wind Helper
0.228
235067AD1-061 GEN
Solar/Wind Helper
0.412
235531U2-073 GEN
Solar/Wind Helper
2.523
238117U2-030
Solar/Wind Helper
0.26
23777901MDS_W4-102
Solar/Wind Helper
0.146
238120AE2-309 GEN
Solar/Wind Helper
0.406
237034AC2-136 C
Solar/Wind Helper
0.189
237002AB1-128_GEN
Solar/Wind Helper
0.369
235063AE1-101 C2
Solar/Wind Helper
1.38
237001AB1-127_GEN
Solar/Wind Helper
0.368
23777801MSM_W1-116
Solar/Wind Helper
0.096
962691AG1-118 GEN
Solar/Wind Harmer
3.447
238152AF2-075_GEN
Solar/Wind Helper
0.593
23546401DTGZ2-030
Solar/Wind Helper
0.075
238109AE1-109 GEN2
Solar/Wind Helper
0.088
238110AE1-109 GEN3
Solar/Wind Helper
0.088
238208AF1-136 C
Solar/Wind Helper
0.18
237085AD2-009_GEN
Solar/Wind Helper
1.367
238126S14_GEN_1
Solar/Wind Helper
0.641
944201AF1-088_MTX
Adder
103.64
957141AF2-008_MTX
Adder
51.82
NYPJM->LTFIMP_NY
CLTF
4.417
LGEELTFEXP_LGEE->PJM
CLTF
6.111
WECLTFEXP_WEC->PJM
CLTF
3.336
AG2-052LTFEXP_AG2-052->PJM
LTF
0.208
AH1-155LTFEXP_AH1-155->PJM
LTF
0.312
LAGNLTFEXP_LAGN->PJM
CLTF
13.832
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.925
TVALTFEXP_TVA->PJM
CLTF
6.876
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.614
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.188
MECLTFEXP_MEC->PJM
CLTF
14.066
SIGELTFEXP_SIGE->PJM
CLTF
0.455
CPLELTFEXP_CPLE->PJM
CLTF
1.286
CBM West 2LTFEXP_CBM-W2->PJM
CBM
102.798

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-007A_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-007A_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:130.62 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4870.98
MW Contribution:3.51
Bus #Bus NameTypeMW Contribution
24318805MLG1
50/50
10.095
23559001PLEAS1
50/50
6.1
270051AF1-062 GEN
50/50
11.821
270475AD2-096_GEN
50/50
7.141
970153AG2-106 GEN
Solar/Wind Harmer
22.046
961921AG1-034 GEN
Solar/Wind Harmer
7.615
241955AC1-078 GEN
Solar/Wind Harmer
0.007
24721905FLATG4
Adder
23.918
241974AD2-163_GEN2
Solar/Wind Harmer
0.006
942051AE2-217 GEN
Solar/Wind Harmer
14.671
970605AG2-385 GEN
Solar/Wind Harmer
4.899
270391AF1-285 GEN3
Solar/Wind Harmer
0.536
253338AC1-165 GEN
Solar/Wind Harmer
0.003
253333AC1-068 GEN
Solar/Wind Harmer
0.012
270119AB2-067 GEN1
50/50
7.059
270120AB2-067 GEN2
50/50
7.059
24318905MLG2
50/50
7.071
270471AD2-092_GEN
Solar/Wind Harmer
0.006
942861AE2-305 GEN
Solar/Wind Harmer
6.335
970077AG2-063 GEN
Solar/Wind Harmer
4.631
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
938701AE1-092 GEN
Solar/Wind Harmer
12.917
971655AH1-328 GEN
Solar/Wind Harmer
2.854
964601AG1-323 GEN
Solar/Wind Harmer
3.215
964601AG1-323 GEN
Solar/Wind Harmer
2.143
270518AE2-148 GEN
Solar/Wind Harmer
0.691
972269AH1-719 GEN
Adder
2.584
972159AH1-661 GEN
Adder
1.118
253378AE2-206_GEN
Solar/Wind Harmer
0.004
276820AF1-078_GEN
Solar/Wind Harmer
0.002
970329AG2-216 GEN
Solar/Wind Harmer
3.354
971199AH1-059 GEN
Solar/Wind Harmer
3.09
241960AC2-195 GEN
Solar/Wind Harmer
0.006
25326509SID D
Adder
1.451
971073AG2-665 GEN
Solar/Wind Harmer
6.898
25326109MON D
Adder
1.443
25322209TAIT E
Adder
10.642
25322209TAIT E
Adder
10.403
971201AH1-060 GEN
Solar/Wind Harmer
1.52
253370AE2-315 SEC1
Adder
2.182
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
246938BC-WTG3
Solar/Wind Harmer
0.273
246937BC-WTG2
Solar/Wind Harmer
0.305
971231AH1-075 GEN
Solar/Wind Harmer
0.861
253317AC1-085 GEN4
Solar/Wind Harmer
0.005
970611AG2-400 GEN
Solar/Wind Harmer
7.488
970627AG2-408 GEN
Solar/Wind Harmer
2.246
270007AE1-245 C
Solar/Wind Harmer
0.002
962581AG1-107 GEN
Solar/Wind Harmer
0.002
25183208HLCRTG
Solar/Wind Harmer
0.012
944541AF1-119 GEN
Solar/Wind Harmer
0.497
960971AF2-388 GEN
Solar/Wind Harmer
4.347
970623AG2-406 GEN
Solar/Wind Harmer
1.356
942221AE2-234 GEN
Solar/Wind Harmer
0.037
252519AF1-045_GEN
Solar/Wind Harmer
6.44
252516AE2-318_GEN
Solar/Wind Harmer
5.712
247621Y3-024
Adder
0.255
970883AG2-550 GEN
Solar/Wind Harmer
7.389
970885AG2-551 GEN
Solar/Wind Harmer
2.463
270201AC2-176 GEN
Solar/Wind Harmer
0.001
25194408D.CRK1
Adder
8.004
25194508D.CRK3
Adder
1.496
970621AG2-405 GEN
Solar/Wind Harmer
1.351
964611AG1-324 GEN
Solar/Wind Harmer
0.553
252509AD1-136 GEN
Solar/Wind Harmer
0.037
970321AG2-212 GEN
Solar/Wind Harmer
3.191
270599AE1-208 GEN
Solar/Wind Harmer
6.737
270031AE2-169
Solar/Wind Harmer
4.042
270186AC1-089 GEN
Solar/Wind Harmer
0.004
270383AD1-128 GEN
Solar/Wind Harmer
0.004
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
970825AG2-519 GEN
Solar/Wind Harmer
8.127
247620Y3-023
Adder
0.484
960441AF2-335 GEN
Solar/Wind Harmer
7.33
270216AD2-079_GEN
Solar/Wind Harmer
0.001
971613AH1-306 GEN
Solar/Wind Harmer
3.512
24728805RICHG1
Adder
3.964
24728905RICHG2
Adder
3.964
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
14.589
961051AF2-396 GEN
Solar/Wind Harmer
9.726
270526AF1-158 GEN
Solar/Wind Harmer
0.009
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
9.095
965791AG1-447 GEN
Solar/Wind Harmer
6.67
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
970239AG2-162 GEN
Solar/Wind Harmer
1.797
274770LINCOLN ;1U
Adder
8.676
274771LINCOLN ;2U
Adder
8.676
966841AG1-555 GEN
Solar/Wind Harmer
0.81
274808UNIV PK N;4U
Adder
5.117
274803UNIV PARK;6U
Adder
5.97
274888KELLY CRK;1U
Solar/Wind Harmer
0.419
274887GEN-1.85
Solar/Wind Harmer
0.188
276843GEN-1.7
Solar/Wind Harmer
0.231
958011AF2-095 GEN
Solar/Wind Harmer
10.284
972259AH1-714 GEN
Adder
19.507
274674JOLIET 9 ;6U
Adder
15.704
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
970241AG2-163 GEN
Solar/Wind Harmer
4.144
958481AF2-142 GEN
Solar/Wind Harmer
10.621
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.958
971573AH1-285 GEN
Solar/Wind Harmer
1.319
274696ROCKY RD ;4P
Adder
11.537
274695ROCKY RD ;2P
Adder
11.271
274693ROCKY RD ;1P
Adder
11.16
274697ROCKY RD ;3P
Adder
3.062
958491AF2-143 GEN
Solar/Wind Harmer
10.588
274879MINONK ;1U
Solar/Wind Harmer
0.297
23585401KL_K28_T16
Solar/Wind Helper
1.482
238120AE2-309 GEN
Solar/Wind Helper
0.525
238175AF1-290_GEN
Solar/Wind Helper
0.153
238169AE2-226 GEN1
Solar/Wind Helper
0.701
238170AE2-226 GEN2
Solar/Wind Helper
0.701
235020AA1-095 C
Solar/Wind Helper
0.053
23777901MDS_W4-102
Solar/Wind Helper
0.177
237002AB1-128_GEN
Solar/Wind Helper
0.443
237034AC2-136 C
Solar/Wind Helper
0.227
235063AE1-101 C2
Solar/Wind Helper
1.659
237001AB1-127_GEN
Solar/Wind Helper
0.442
23777801MSM_W1-116
Solar/Wind Helper
0.114
237025AB1-124 C
Solar/Wind Helper
0.164
237006AB1-125 GEN
Solar/Wind Helper
0.123
226929AD2-058 GEN
Solar/Wind Helper
0.099
205916AD1-020 GEN
Solar/Wind Helper
1.713
20390526W1-045 C
Solar/Wind Helper
0.35
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
233987AB2-037 GEN
Solar/Wind Helper
2.342
233933AB2-153 GEN
Solar/Wind Helper
0.232
233944AB2-135 GEN
Solar/Wind Helper
0.588
232424Y1-079 C
Solar/Wind Helper
0.116
234036AF2-325 C
Solar/Wind Helper
0.042
233946AB2-136 GEN
Solar/Wind Helper
0.568
233901CHERRYDALE C
Solar/Wind Helper
0.232
232408W1-005 C
Solar/Wind Helper
0.507
232410W1-006 C
Solar/Wind Helper
0.507
233939AC1-091 C
Solar/Wind Helper
0.35
233970AC1-092 C
Solar/Wind Helper
0.35
315651AD1-115 GEN
Solar/Wind Helper
0.785
316447AC1-158 HLD
Solar/Wind Helper
2.845
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.04
219921AF1-264
Solar/Wind Helper
0.051
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.082
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.19
20716928W4-060COL
Solar/Wind Helper
0.051
218440SUMMTASSOC C
Solar/Wind Helper
0.016
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270273AD2-016 GEN
Solar/Wind Harmer
0.821
972173AH1-669 GEN
Solar/Wind Harmer
3.952
270291AC1-194 GEN
Solar/Wind Harmer
6.106
253415AE1-040 GEN
Solar/Wind Harmer
0.003
270512AE1-227 GEN2
Solar/Wind Harmer
1.963
970065AG2-057 GEN
Solar/Wind Harmer
0.76
253370AE2-315 SEC1
Adder
2.182
253371AE2-315 SEC2
Adder
2.063
253406AD2-031_GEN
Solar/Wind Harmer
0.563
970191AG2-125 GEN
Solar/Wind Harmer
1.945
270491AE1-102 GEN2
Solar/Wind Harmer
0.979
270377AD1-106 GEN
Solar/Wind Harmer
2.855
971191AH1-055 GEN
Solar/Wind Harmer
19.26
253316AC1-085 GEN3
Solar/Wind Harmer
0.005
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
9.749
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.048
959331AF2-224 GEN
Solar/Wind Harmer
5.242
965021AG1-366 GEN
Solar/Wind Harmer
2.496
270588AE1-091_GEN
Solar/Wind Harmer
5.845
944531AF1-118 GEN
Solar/Wind Harmer
33.395
270043AE2-236 GEN
Solar/Wind Harmer
4.777
270258AD1-119 GEN
Solar/Wind Harmer
0.002
971617AH1-308 GEN
Solar/Wind Harmer
6.173
25196608WSDLE5
Adder
9.077
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
252510AF1-249 C
Solar/Wind Harmer
0.057
957741AF2-068 GEN
Solar/Wind Harmer
11.081
25194608D.CRK4
Adder
1.74
270222AC2-111 GEN
Solar/Wind Harmer
3.739
970031AG2-029 GEN
Solar/Wind Harmer
4.795
270404AC1-167 GEN
Solar/Wind Harmer
0.003
970513AG2-328 GEN
Solar/Wind Harmer
3.191
970517AG2-330 GEN
Solar/Wind Harmer
19.146
970349AG2-230 GEN
Solar/Wind Harmer
11.025
946031AF1-268 GEN
Solar/Wind Harmer
6.992
958821AF2-173 GEN
Solar/Wind Harmer
10.273
270004AE1-209 GEN
Solar/Wind Harmer
1.59
270437AC2-090 C
Solar/Wind Harmer
0.003
247643Z2-116 C
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.804
970291AG2-192 GEN
Solar/Wind Harmer
0.731
247642Z2-115 C
Solar/Wind Harmer
0.003
945111AF1-176 GEN
Solar/Wind Harmer
5.919
24642205MAYFLWER
Adder
0.665
25196008MFTGT1
Adder
1.405
270356AE2-297 GEN
Solar/Wind Harmer
0.01
24441205WTRV SLR C
Solar/Wind Harmer
0
247604X1-042
Adder
0.433
270535AF1-215 GEN1
Solar/Wind Harmer
0.009
964401AG1-302 GEN
Solar/Wind Harmer
0.001
970217AG2-149 GEN
Solar/Wind Harmer
6.268
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
7.196
970243AG2-164 GEN
Solar/Wind Harmer
4.205
970519AG2-331 GEN
Solar/Wind Harmer
18.687
970699AG2-449 GEN
Solar/Wind Harmer
1.797
274752CRETE EC ;2U
Adder
8.477
274753CRETE EC ;3U
Adder
8.477
958171AF2-111 GEN
Solar/Wind Harmer
17.94
274772LINCOLN ;3U
Adder
8.676
274724RIVER EC ;11
Adder
18.203
972167AH1-666 GEN
Solar/Wind Harmer
5.717
24728705AND G3
Adder
8.214
274802UNIV PARK;5U
Adder
5.97
24728505AND G1
Adder
3.927
276806AD2-047 C O1
Solar/Wind Harmer
4.047
970941AG2-585 GEN
Solar/Wind Harmer
8.927
274826FISK ;BP
Adder
11.205
274800UNIV PARK;3U
Adder
5.966
972038AH1-567 GEN2
Adder
0.373
972228AH1-698 GEN2
Adder
3.79
276897AD1-100 C
Solar/Wind Harmer
0.009
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
970707AG2-453 GEN
Solar/Wind Harmer
23.303
274676JOLIET 29;8U
Adder
30.185
276893AG1-478 C
Solar/Wind Harmer
0.282
274729ELWOOD EC;1P
Adder
16.768
274730ELWOOD EC;6P
Adder
16.768
274734ELWOOD EC;8P
Adder
16.768
274736ELWOOD EC;9P
Adder
16.768
943121AE2-341 GEN
Solar/Wind Harmer
11.888
943591AF1-030 GEN
Solar/Wind Harmer
7.906
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
270541AE2-072 C
Solar/Wind Harmer
0.009
274682WAUKEGAN ;7U
Adder
9.728
276805AD2-038 GEN
Solar/Wind Harmer
0.002
964991AG1-363 GEN
Solar/Wind Helper
5.136
316097T157 G90
Solar/Wind Helper
1.504
23750701CROSSCHOOL
Solar/Wind Helper
1.502
238118U2-030_1
Solar/Wind Helper
0.341
238127S14_GEN_2
Solar/Wind Helper
0.827
238148AE2-230_GEN2
Solar/Wind Helper
0.497
237080AD1-060 GEN
Solar/Wind Helper
0.342
237038AE2-054 C
Solar/Wind Helper
0.272
235062AE1-101 C1
Solar/Wind Helper
1.659
23779801AA1-109
Solar/Wind Helper
0.193
237048AF1-022 C
Solar/Wind Helper
0.177
223401AF1-299 GEN
Solar/Wind Helper
0.367
316006AB2-029 C
Solar/Wind Helper
0.117
966131AG1-482 GEN
Solar/Wind Helper
0.137
233930AB2-032 GEN
Solar/Wind Helper
0.381
233915AB1-141 GEN
Solar/Wind Helper
0.502
962771AG1-126 GEN
Solar/Wind Harmer
34.524
972239AH1-704 GEN
Adder
2.689
270054AF2-122 C O1
Solar/Wind Harmer
0.007
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
5.077
270520AE2-214 GEN
Solar/Wind Harmer
0.013
270284AF1-227 GEN1
Solar/Wind Harmer
0.011
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
253383AE2-342_GEN
Solar/Wind Harmer
0.003
241973AD2-163_GEN1
Solar/Wind Harmer
0.006
945631AF1-228 GEN
Solar/Wind Harmer
0
943861AF1-054 GEN
Solar/Wind Harmer
3.127
943851AF1-053 GEN
Solar/Wind Harmer
2.166
270156DARBY CT1
Adder
10.409
270157DARBY CT2
Adder
10.383
270158DARBY CT3
Adder
10.218
970689AG2-444 GEN
Solar/Wind Harmer
16.436
270578AF1-285 GEN2
Solar/Wind Harmer
0.536
270432AC2-029 GEN
Solar/Wind Harmer
3.553
940611AE2-048 GEN
Solar/Wind Harmer
19.602
941391AE2-136 GEN
Solar/Wind Harmer
11.042
270302AB2-170 GEN
Solar/Wind Harmer
0.005
270317AD1-130_GEN
Solar/Wind Harmer
0.011
971653AH1-327 GEN
Solar/Wind Harmer
1.117
270269AC2-059
Solar/Wind Harmer
0.005
241972AD1-140 GEN
Solar/Wind Harmer
0.854
970179AG2-119 GEN
Solar/Wind Harmer
6.883
270340AC2-060 GEN
Solar/Wind Harmer
0.009
970879AG2-548 GEN
Solar/Wind Harmer
6.898
253372AE2-315 SEC3
Adder
2.063
253372AE2-315 SEC3
Adder
2.063
25306009OHH W.
Adder
3.13
253349AC2-067 GEN
Solar/Wind Harmer
2.381
253400AC2-068 GEN
Solar/Wind Harmer
0.958
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
0.953
965051AG1-369 GEN
Solar/Wind Harmer
3.739
965041AG1-368 GEN
Solar/Wind Harmer
7.471
247607V1-011 GEN
Solar/Wind Harmer
0.001
971567AH1-282 GEN
Solar/Wind Harmer
11.206
971989AH1-539 GEN
Solar/Wind Harmer
3.215
963791AG1-232 GEN
Solar/Wind Harmer
10.044
24729505KEY G4
Adder
6.919
270071AF1-092 GEN
Solar/Wind Harmer
14.245
971985AH1-537 GEN
Solar/Wind Harmer
2.206
270024AE2-089 GEN
Solar/Wind Harmer
0.008
270367AC2-061_GEN
Solar/Wind Harmer
0.006
965101AG1-375 GEN
Solar/Wind Harmer
7.401
971673AH1-337 GEN
Solar/Wind Harmer
4.804
252524AE2-267 GEN
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
9.344
25196308WSDLE2
Adder
9.263
25196208WSDLE1
Adder
9.24
25196708WSDLE6
Adder
9.217
25196508WSDLE4
Adder
8.984
971029AG2-637 GEN
Solar/Wind Harmer
11.085
270543AE2-219 C
Solar/Wind Harmer
0.004
945581AF1-223 GEN
Solar/Wind Harmer
0.001
270297AD1-101 GEN
Solar/Wind Harmer
0.002
971347AH1-153 GEN
Solar/Wind Harmer
11.025
971609AH1-304 GEN
Solar/Wind Harmer
1.2
270240V3-007_GEN2
Solar/Wind Harmer
0.002
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
970115AG2-085 GEN
Solar/Wind Harmer
2.932
270594AE1-207 GEN
Solar/Wind Harmer
8.194
970289AG2-191 GEN
Solar/Wind Harmer
1.389
971771AH1-392 GEN
Solar/Wind Harmer
7.306
971619AH1-309 GEN
Solar/Wind Harmer
3.285
971769AH1-391 GEN
Solar/Wind Harmer
8.134
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
25196108MFTGT2
Adder
1.599
25196108MFTGT2
Adder
1.484
270536AF1-215 GEN2
Solar/Wind Harmer
0.009
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
4.302
971549AH1-272 GEN
Solar/Wind Harmer
14.865
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
8.676
274776LINCOLN ;7U
Adder
8.676
274777LINCOLN ;8U
Adder
8.676
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
274814UNIV PK N;0U
Adder
5.184
274807UNIV PK N;3U
Adder
5.173
274805UNIV PK N;1U
Adder
5.15
274811UNIV PK N;7U
Adder
5.139
972037AH1-567 GEN1
Adder
0.187
960591AF2-350 GEN
Solar/Wind Harmer
7.141
274827FISK ;RP
Adder
7.941
972227AH1-698 GEN1
Adder
2.669
963841AG1-237 GEN
Solar/Wind Harmer
3.09
972163AH1-664 GEN
Solar/Wind Harmer
7.933
972165AH1-665 GEN
Solar/Wind Harmer
6.354
274687WILL CNTY;4U
Adder
28.523
274687WILL CNTY;4U
Adder
28.523
274675JOLIET 29;7U
Adder
31.303
274675JOLIET 29;7U
Adder
30.185
274731ELWOOD EC;2P
Adder
16.768
274733ELWOOD EC;3P
Adder
16.768
274735ELWOOD EC;4P
Adder
16.768
274728ELWOOD EC;5P
Adder
16.768
970833AG2-524 GEN
Solar/Wind Harmer
7.824
970833AG2-524 GEN
Solar/Wind Harmer
5.216
274746AC1-111 G10
Adder
5.679
274744AC1-111 GEN8
Adder
5.679
972203AH1-686 GEN
Adder
2.338
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
276868AE1-113 GEN
Solar/Wind Harmer
1.414
276882AE2-255 GEN
Solar/Wind Harmer
0.824
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238126S14_GEN_1
Solar/Wind Helper
0.827
238152AF2-075_GEN
Solar/Wind Helper
0.707
238208AF1-136 C
Solar/Wind Helper
0.22
23546401DTGZ2-030
Solar/Wind Helper
0.089
237085AD2-009_GEN
Solar/Wind Helper
1.649
3138216PACIFIC
Solar/Wind Helper
0.044
316411AF1-147_GEN1
Solar/Wind Helper
0.888
316415AF1-147_GEN2
Solar/Wind Helper
0.888
23750501ELLIOTTS
Solar/Wind Helper
0.638
959381AF2-229 GEN
Solar/Wind Helper
0.357
3141426STAFORD
Solar/Wind Helper
0.052
960921AF2-383 GEN
Solar/Wind Helper
0.364
205943AE1-185 GEN
Solar/Wind Helper
0.509
205932AD2-116_GEN
Solar/Wind Helper
0.509
205956AE1-196_GEN
Solar/Wind Helper
0.509
233935AB2-179 C
Solar/Wind Helper
1.269
232436AB1-176 C
Solar/Wind Helper
0.044
233923SMA
Solar/Wind Helper
0.958
233990AG1-397 GEN
Solar/Wind Helper
0.27
232432Z2-076 GEN
Solar/Wind Helper
0.067
234033AF1-007_GEN
Solar/Wind Helper
7.02
964001AG1-254 GEN
Solar/Wind Helper
0.955
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.115
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.08
203975AE1-071-GEN
Solar/Wind Helper
2.498
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.29
219620RIDERU C
Solar/Wind Helper
0.001
316164AC1-076 GEN
Solar/Wind Helper
1.096
20675528CPH_W2-050
Solar/Wind Helper
0.087
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
218524CNTRALGAS1 C
Solar/Wind Helper
0.16
966261AG1-495 GEN
Solar/Wind Helper
0.081
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20675928HOL_W4-097
Solar/Wind Helper
0.05
207484AF2-139 C O1
Solar/Wind Helper
0.084
20674828DL_W4-046
Solar/Wind Helper
0.008
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.136
20675128HRM_W1-127
Solar/Wind Helper
0.029
209116AE2-175 GEN
Solar/Wind Helper
1.778
20673828FLE_V3-070
Solar/Wind Helper
0.09
207442AE1-156 GEN
Solar/Wind Helper
0.326
20676128MHD_W3-029
Solar/Wind Helper
0.096
20671828STAW2-080
Solar/Wind Helper
0.027
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
207471AF2-354 C
Solar/Wind Helper
0.168
20674928WA_W3-044
Solar/Wind Helper
0.098
20676228FRD_X1-012
Solar/Wind Helper
0.092
964851AG1-348 GEN
Solar/Wind Helper
0.081
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.074
211065PSPA IPP
Solar/Wind Helper
0.151
211065PSPA IPP
Solar/Wind Helper
0.151
270166AC1-044 GEN3
50/50
7.059
23559101PLEAS2
50/50
6.1
962761AG1-125 GEN
Solar/Wind Harmer
34.524
970149AG2-104 GEN
Solar/Wind Harmer
37.287
970155AG2-107 GEN
Solar/Wind Harmer
22.046
270349AD2-093_GEN
Solar/Wind Harmer
0.006
24721705FLATG2
Adder
23.918
270159DARBY CT4
Adder
10.243
970593AG2-378 GEN
Solar/Wind Harmer
1.812
270223U2-072_GEN1
Solar/Wind Harmer
0.001
253343AC1-166 GEN
Solar/Wind Harmer
0.003
253325AC1-069 GEN
Solar/Wind Harmer
0.012
270462AD2-086
Solar/Wind Harmer
0.017
971995AH1-542 GEN
Solar/Wind Harmer
2.906
270263AC1-001 GEN
Solar/Wind Harmer
0.786
270510AE1-227 GEN1
Solar/Wind Harmer
1.963
25326309TAIT D
Adder
1.196
241813AF1-122_GEN
Solar/Wind Harmer
3.405
960071AF2-298 GEN
Solar/Wind Harmer
3.786
253370AE2-315 SEC1
Adder
2.182
253371AE2-315 SEC2
Adder
2.063
927014AC1-188 GEN
Solar/Wind Harmer
0.005
246936BC-WTG1
Solar/Wind Harmer
0.305
270489AE1-102 GEN1
Solar/Wind Harmer
0.979
965421AG1-410 GEN
Solar/Wind Harmer
22.57
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.499
247521TR3_G114
Solar/Wind Harmer
0.273
270246TR4_N_V150
Solar/Wind Harmer
0.048
965011AG1-365 GEN
Solar/Wind Harmer
7.488
24695305TIMB G C
Solar/Wind Harmer
0.002
965651AG1-433 GEN
Solar/Wind Harmer
2.174
958861AF2-177 GEN
Solar/Wind Harmer
3.207
247536S-71 GEN
Solar/Wind Harmer
0.297
25194608D.CRK4
Adder
1.74
945371AF1-202 GEN
Solar/Wind Harmer
0.001
252507AC2-088 GEN
Solar/Wind Harmer
0.335
270063AE2-323 C
Solar/Wind Harmer
0.006
970245AG2-165 GEN
Solar/Wind Harmer
3.191
970947AG2-589 GEN
Solar/Wind Harmer
0.245
270005AE1-210 C O1
Solar/Wind Harmer
1.59
232422X3-066 FULL
Solar/Wind Helper
0.114
232428Y3-058 C
Solar/Wind Helper
0.338
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
233998TM1NIN_3.36
Solar/Wind Helper
0.261
232404W1-003 C
Solar/Wind Helper
0.507
232434Z2-077 GEN
Solar/Wind Helper
0.127
233954AC2-188 GEN
Solar/Wind Helper
0.232
233950AC2-186 GEN
Solar/Wind Helper
0.116
233972AC1-094 C
Solar/Wind Helper
0.302
316045AC1-158 PL2
Solar/Wind Helper
4.138
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.23
228728W1-130C
Solar/Wind Helper
0.054
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219904AC1-010 C
Solar/Wind Helper
0.06
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.131
20720728JCB_W1-129
Solar/Wind Helper
0.057
316254AC1-120 GEN1
Solar/Wind Helper
1.059
207445AB1-138_GEN
Solar/Wind Helper
0.104
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.13
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.31
20715228NPK_W1-113
Solar/Wind Helper
0.078
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.495
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
207437AD2-070 GEN
Solar/Wind Helper
0.138
207518AF1-320_GEN
Solar/Wind Helper
1.571
20671928W4-073
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.029
965031AG1-367 GEN
Solar/Wind Harmer
7.338
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.378
970825AG2-519 GEN
Solar/Wind Harmer
2.603
25196808ZIMRHP
Adder
79.729
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
944231AF1-091 GEN
Solar/Wind Harmer
1.953
24639705ELKHART HY
Adder
0.161
270032AE2-172
Solar/Wind Harmer
4.877
970291AG2-192 GEN
Solar/Wind Harmer
0.95
945111AF1-176 GEN
Solar/Wind Harmer
13.03
270505AE1-170 C O1
Solar/Wind Harmer
7.665
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.805
276903AD2-071 C
Solar/Wind Harmer
8.137
25196008MFTGT1
Adder
1.45
247522W1-056 GEN
Solar/Wind Harmer
0.001
970773AG2-487 GEN
Solar/Wind Harmer
1.284
970373AG2-245 GEN
Solar/Wind Harmer
15.247
270055AF2-134 C O1
Solar/Wind Harmer
0.006
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.41
970515AG2-329 GEN
Solar/Wind Harmer
18.805
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
9.032
24791305MDL-5G
Solar/Wind Harmer
0.001
970333AG2-219 GEN
Solar/Wind Harmer
5.139
274751CRETE EC ;1U
Adder
8.477
274754CRETE EC ;4U
Adder
8.477
274773LINCOLN ;4U
Adder
8.676
274774LINCOLN ;5U
Adder
8.676
274723RIVER EC ;12
Adder
18.418
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
5.139
24728605AND G2
Adder
3.927
276776AD2-060 GEN
Solar/Wind Harmer
0.746
945681AF1-233 GEN
Solar/Wind Harmer
13.461
274801UNIV PARK;4U
Adder
5.966
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
31.303
274732ELWOOD EC;7P
Adder
16.768
274674JOLIET 9 ;6U
Adder
15.704
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
963741AG1-226 GEN
Solar/Wind Harmer
16.815
274745AC1-111 GEN9
Adder
5.679
939401AE1-172 GEN
Solar/Wind Harmer
5.301
276691AA1-018 GEN1
Solar/Wind Harmer
0.858
970091AG2-072 GEN
Adder
77.629
276901AD2-066 C O1
Solar/Wind Harmer
0.007
316095T157 G97
Solar/Wind Helper
1.504
23583801GRNGAP
Solar/Wind Helper
5.601
238185AF2-356 C
Solar/Wind Helper
2.646
238108AE1-109 GEN1
Solar/Wind Helper
0.114
235054AD2-180 GEN
Solar/Wind Helper
2.03
235531U2-073 GEN
Solar/Wind Helper
3.282
238117U2-030
Solar/Wind Helper
0.341
238147AE2-230_GEN1
Solar/Wind Helper
0.495
238149AF1-291A_GEN
Solar/Wind Helper
0.141
23751201ROTHROCK
Solar/Wind Helper
0.824
237061AD1-155 GEN
Solar/Wind Helper
0.053
23562501BACKB
Solar/Wind Helper
1.007
238221AF1-254 C O1
Solar/Wind Helper
0.274
235067AD1-061 GEN
Solar/Wind Helper
0.496
23751101LEADS_P59
Solar/Wind Helper
1.404
237030AB1-096 C
Solar/Wind Helper
0.071
3141196NOKESVL
Solar/Wind Helper
1.032
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.346
223402AF1-300 C
Solar/Wind Helper
0.367
205917AD1-020 ES
Solar/Wind Helper
0.368
233918AB1-142 GEN
Solar/Wind Helper
0.502
233982AB2-133 GEN
Solar/Wind Helper
0.358
233994AC2-023 GEN
Solar/Wind Helper
0.961
233996TM1833_GEN
Solar/Wind Helper
0.261
233997TMININ_4.2
Solar/Wind Helper
0.261
232406W1-004 FULL
Solar/Wind Helper
0.507
233940AF2-379 C
Solar/Wind Helper
0.062
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.232
233971AC1-093 C
Solar/Wind Helper
0.357
316044AC1-158 PL1
Solar/Wind Helper
1.293
316450AC1-158 RIC
Solar/Wind Helper
0.345
230430AE1-229_GEN
Solar/Wind Helper
3.372
230415AB2-049 C
Solar/Wind Helper
0.03
228729W2-030 C
Solar/Wind Helper
0.11
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.15
219291REEVESSOUT C
Solar/Wind Helper
0.011
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
219348LDSOLAR C
Solar/Wind Helper
0.114
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.063
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.353
219276PARKLANDSO C
Solar/Wind Helper
0.089
20714528FRN_Y2-051
Solar/Wind Helper
0.057
20720528MAN_W1-024
Solar/Wind Helper
0.028
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.027
219908AB1-139 C
Solar/Wind Helper
0.074
219249CENTRALDIV C
Solar/Wind Helper
0.01
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.089
971997AH1-543 GEN
Solar/Wind Harmer
2.724
NYPJM->LTFIMP_NY
CLTF
4.797
LGEELTFEXP_LGEE->PJM
CLTF
6.749
WECLTFEXP_WEC->PJM
CLTF
3.825
AG2-052LTFEXP_AG2-052->PJM
LTF
0.24
AH1-155LTFEXP_AH1-155->PJM
LTF
0.359
LAGNLTFEXP_LAGN->PJM
CLTF
14.837
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.802
TVALTFEXP_TVA->PJM
CLTF
7.293
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.078
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.1
MECLTFEXP_MEC->PJM
CLTF
15.901
SIGELTFEXP_SIGE->PJM
CLTF
0.505
CPLELTFEXP_CPLE->PJM
CLTF
0.624
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.816

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-008A_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-008A_SRT-SL
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:124.1 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4627.6
MW Contribution:3.38
Bus #Bus NameTypeMW Contribution
270119AB2-067 GEN1
50/50
6.869
270120AB2-067 GEN2
50/50
6.869
24318905MLG2
50/50
6.89
270471AD2-092_GEN
Solar/Wind Harmer
0.006
942861AE2-305 GEN
Solar/Wind Harmer
6.118
970077AG2-063 GEN
Solar/Wind Harmer
4.471
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
938701AE1-092 GEN
Solar/Wind Harmer
12.484
971655AH1-328 GEN
Solar/Wind Harmer
2.758
964601AG1-323 GEN
Solar/Wind Harmer
3.106
964601AG1-323 GEN
Solar/Wind Harmer
2.071
270518AE2-148 GEN
Solar/Wind Harmer
0.667
972269AH1-719 GEN
Adder
2.501
972159AH1-661 GEN
Adder
1.082
253378AE2-206_GEN
Solar/Wind Harmer
0.004
276820AF1-078_GEN
Solar/Wind Harmer
0.002
970329AG2-216 GEN
Solar/Wind Harmer
3.237
971199AH1-059 GEN
Solar/Wind Harmer
2.99
241960AC2-195 GEN
Solar/Wind Harmer
0.006
970935AG2-582 GEN
Adder
242.403
25326509SID D
Adder
1.4
971073AG2-665 GEN
Solar/Wind Harmer
6.645
25326109MON D
Adder
1.391
971201AH1-060 GEN
Solar/Wind Harmer
1.471
25322209TAIT E
Adder
10.262
25322209TAIT E
Adder
10.031
253370AE2-315 SEC1
Adder
2.103
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
246938BC-WTG3
Solar/Wind Harmer
0.263
246937BC-WTG2
Solar/Wind Harmer
0.295
971231AH1-075 GEN
Solar/Wind Harmer
0.833
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
970611AG2-400 GEN
Solar/Wind Harmer
7.225
970627AG2-408 GEN
Solar/Wind Harmer
2.167
270007AE1-245 C
Solar/Wind Harmer
0.002
970623AG2-406 GEN
Solar/Wind Harmer
1.309
962581AG1-107 GEN
Solar/Wind Harmer
0.001
25183208HLCRTG
Solar/Wind Harmer
0.011
944541AF1-119 GEN
Solar/Wind Harmer
0.479
960971AF2-388 GEN
Solar/Wind Harmer
4.192
942221AE2-234 GEN
Solar/Wind Harmer
0.036
252519AF1-045_GEN
Solar/Wind Harmer
6.204
252516AE2-318_GEN
Solar/Wind Harmer
5.503
970621AG2-405 GEN
Solar/Wind Harmer
1.305
247621Y3-024
Adder
0.246
970883AG2-550 GEN
Solar/Wind Harmer
7.123
970885AG2-551 GEN
Solar/Wind Harmer
2.374
270201AC2-176 GEN
Solar/Wind Harmer
0.001
25194408D.CRK1
Adder
7.711
25194508D.CRK3
Adder
1.442
964611AG1-324 GEN
Solar/Wind Harmer
0.534
252509AD1-136 GEN
Solar/Wind Harmer
0.036
970321AG2-212 GEN
Solar/Wind Harmer
3.076
270599AE1-208 GEN
Solar/Wind Harmer
6.495
270031AE2-169
Solar/Wind Harmer
3.897
270383AD1-128 GEN
Solar/Wind Harmer
0.004
24318805MLG1
50/50
9.842
23559001PLEAS1
50/50
5.385
270051AF1-062 GEN
50/50
11.434
970153AG2-106 GEN
Solar/Wind Harmer
21.245
961921AG1-034 GEN
Solar/Wind Harmer
7.364
241955AC1-078 GEN
Solar/Wind Harmer
0.007
241974AD2-163_GEN2
Solar/Wind Harmer
0.006
942051AE2-217 GEN
Solar/Wind Harmer
14.169
24721905FLATG4
Adder
22.865
970605AG2-385 GEN
Solar/Wind Harmer
4.731
270391AF1-285 GEN3
Solar/Wind Harmer
0.518
253338AC1-165 GEN
Solar/Wind Harmer
0.003
253333AC1-068 GEN
Solar/Wind Harmer
0.012
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270273AD2-016 GEN
Solar/Wind Harmer
0.792
972173AH1-669 GEN
Solar/Wind Harmer
3.811
270512AE1-227 GEN2
Solar/Wind Harmer
1.904
270291AC1-194 GEN
Solar/Wind Harmer
5.884
253415AE1-040 GEN
Solar/Wind Harmer
0.003
970065AG2-057 GEN
Solar/Wind Harmer
0.735
253370AE2-315 SEC1
Adder
2.103
253371AE2-315 SEC2
Adder
1.989
970191AG2-125 GEN
Solar/Wind Harmer
1.876
253406AD2-031_GEN
Solar/Wind Harmer
0.543
270491AE1-102 GEN2
Solar/Wind Harmer
0.945
270377AD1-106 GEN
Solar/Wind Harmer
2.761
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.047
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
270166AC1-044 GEN3
50/50
6.869
23559101PLEAS2
50/50
5.385
270122AB2-093 CT
50/50
3.689
962761AG1-125 GEN
Solar/Wind Harmer
33.269
970149AG2-104 GEN
Solar/Wind Harmer
35.932
970155AG2-107 GEN
Solar/Wind Harmer
21.245
270349AD2-093_GEN
Solar/Wind Harmer
0.006
24721705FLATG2
Adder
22.865
270159DARBY CT4
Adder
9.89
970593AG2-378 GEN
Solar/Wind Harmer
1.75
270223U2-072_GEN1
Solar/Wind Harmer
0.001
253343AC1-166 GEN
Solar/Wind Harmer
0.003
253325AC1-069 GEN
Solar/Wind Harmer
0.012
270462AD2-086
Solar/Wind Harmer
0.016
971995AH1-542 GEN
Solar/Wind Harmer
2.81
270263AC1-001 GEN
Solar/Wind Harmer
0.758
270510AE1-227 GEN1
Solar/Wind Harmer
1.904
241813AF1-122_GEN
Solar/Wind Harmer
3.294
25326309TAIT D
Adder
1.153
960071AF2-298 GEN
Solar/Wind Harmer
3.651
253370AE2-315 SEC1
Adder
2.103
253371AE2-315 SEC2
Adder
1.989
927014AC1-188 GEN
Solar/Wind Harmer
0.004
246936BC-WTG1
Solar/Wind Harmer
0.295
270489AE1-102 GEN1
Solar/Wind Harmer
0.945
965421AG1-410 GEN
Solar/Wind Harmer
21.788
247521TR3_G114
Solar/Wind Harmer
0.263
270246TR4_N_V150
Solar/Wind Harmer
0.047
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.226
965011AG1-365 GEN
Solar/Wind Harmer
7.225
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
24695305TIMB G C
Solar/Wind Harmer
0.002
965651AG1-433 GEN
Solar/Wind Harmer
2.096
958861AF2-177 GEN
Solar/Wind Harmer
3.092
247536S-71 GEN
Solar/Wind Harmer
0.287
945371AF1-202 GEN
Solar/Wind Harmer
0.001
25194608D.CRK4
Adder
1.676
270063AE2-323 C
Solar/Wind Harmer
0.006
252507AC2-088 GEN
Solar/Wind Harmer
0.323
970245AG2-165 GEN
Solar/Wind Harmer
3.076
944231AF1-091 GEN
Solar/Wind Harmer
1.885
270005AE1-210 C O1
Solar/Wind Harmer
1.532
965031AG1-367 GEN
Solar/Wind Harmer
7.073
970947AG2-589 GEN
Solar/Wind Harmer
0.236
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.183
970825AG2-519 GEN
Solar/Wind Harmer
2.509
24639705ELKHART HY
Adder
0.155
25196808ZIMRHP
Adder
76.799
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
270032AE2-172
Solar/Wind Harmer
4.701
970291AG2-192 GEN
Solar/Wind Harmer
0.916
945111AF1-176 GEN
Solar/Wind Harmer
12.568
270505AE1-170 C O1
Solar/Wind Harmer
7.393
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.67
247522W1-056 GEN
Solar/Wind Harmer
0.001
276903AD2-071 C
Solar/Wind Harmer
7.842
25196008MFTGT1
Adder
1.397
970773AG2-487 GEN
Solar/Wind Harmer
1.237
970373AG2-245 GEN
Solar/Wind Harmer
14.699
970515AG2-329 GEN
Solar/Wind Harmer
18.197
270055AF2-134 C O1
Solar/Wind Harmer
0.005
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.071
946181AF1-283 GEN
Solar/Wind Harmer
9.394
959331AF2-224 GEN
Solar/Wind Harmer
5.057
965021AG1-366 GEN
Solar/Wind Harmer
2.408
270588AE1-091_GEN
Solar/Wind Harmer
5.649
971191AH1-055 GEN
Solar/Wind Harmer
18.515
944531AF1-118 GEN
Solar/Wind Harmer
32.203
270043AE2-236 GEN
Solar/Wind Harmer
4.607
270258AD1-119 GEN
Solar/Wind Harmer
0.002
971617AH1-308 GEN
Solar/Wind Harmer
5.953
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
10.684
270404AC1-167 GEN
Solar/Wind Harmer
0.003
25196608WSDLE5
Adder
8.745
252510AF1-249 C
Solar/Wind Harmer
0.055
970031AG2-029 GEN
Solar/Wind Harmer
4.625
25194608D.CRK4
Adder
1.676
270222AC2-111 GEN
Solar/Wind Harmer
3.603
970513AG2-328 GEN
Solar/Wind Harmer
3.076
970517AG2-330 GEN
Solar/Wind Harmer
18.457
970349AG2-230 GEN
Solar/Wind Harmer
10.632
946031AF1-268 GEN
Solar/Wind Harmer
6.74
958821AF2-173 GEN
Solar/Wind Harmer
9.902
270004AE1-209 GEN
Solar/Wind Harmer
1.532
270437AC2-090 C
Solar/Wind Harmer
0.003
247643Z2-116 C
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.775
970291AG2-192 GEN
Solar/Wind Harmer
0.705
945111AF1-176 GEN
Solar/Wind Harmer
5.709
247642Z2-115 C
Solar/Wind Harmer
0.003
24642205MAYFLWER
Adder
0.641
24441205WTRV SLR C
Solar/Wind Harmer
0
25196008MFTGT1
Adder
1.353
270356AE2-297 GEN
Solar/Wind Harmer
0.009
970217AG2-149 GEN
Solar/Wind Harmer
6.066
247604X1-042
Adder
0.418
270535AF1-215 GEN1
Solar/Wind Harmer
0.009
964401AG1-302 GEN
Solar/Wind Harmer
0.001
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.935
970243AG2-164 GEN
Solar/Wind Harmer
4.047
970519AG2-331 GEN
Solar/Wind Harmer
17.988
970699AG2-449 GEN
Solar/Wind Harmer
1.73
274752CRETE EC ;2U
Adder
8.172
274753CRETE EC ;3U
Adder
8.172
274772LINCOLN ;3U
Adder
8.364
274724RIVER EC ;11
Adder
17.549
958171AF2-111 GEN
Solar/Wind Harmer
17.278
274802UNIV PARK;5U
Adder
5.755
276806AD2-047 C O1
Solar/Wind Harmer
3.901
970941AG2-585 GEN
Solar/Wind Harmer
8.605
274826FISK ;BP
Adder
10.802
24728705AND G3
Adder
7.914
24728505AND G1
Adder
3.784
274800UNIV PARK;3U
Adder
5.751
972038AH1-567 GEN2
Adder
0.36
972228AH1-698 GEN2
Adder
3.654
972167AH1-666 GEN
Solar/Wind Harmer
5.505
276897AD1-100 C
Solar/Wind Harmer
0.009
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
22.464
274676JOLIET 29;8U
Adder
29.097
274729ELWOOD EC;1P
Adder
16.163
274730ELWOOD EC;6P
Adder
13.491
276893AG1-478 C
Solar/Wind Harmer
0.272
270541AE2-072 C
Solar/Wind Harmer
0.009
943121AE2-341 GEN
Solar/Wind Harmer
11.459
943591AF1-030 GEN
Solar/Wind Harmer
7.62
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
276805AD2-038 GEN
Solar/Wind Harmer
0.002
964991AG1-363 GEN
Solar/Wind Helper
4.969
316097T157 G90
Solar/Wind Helper
1.455
23750701CROSSCHOOL
Solar/Wind Helper
1.397
238148AE2-230_GEN2
Solar/Wind Helper
0.48
238127S14_GEN_2
Solar/Wind Helper
0.766
238118U2-030_1
Solar/Wind Helper
0.314
237080AD1-060 GEN
Solar/Wind Helper
0.33
237038AE2-054 C
Solar/Wind Helper
0.262
235062AE1-101 C1
Solar/Wind Helper
1.6
23779801AA1-109
Solar/Wind Helper
0.187
223401AF1-299 GEN
Solar/Wind Helper
0.355
316006AB2-029 C
Solar/Wind Helper
0.113
966131AG1-482 GEN
Solar/Wind Helper
0.132
237048AF1-022 C
Solar/Wind Helper
0.159
233930AB2-032 GEN
Solar/Wind Helper
0.368
233915AB1-141 GEN
Solar/Wind Helper
0.486
232422X3-066 FULL
Solar/Wind Helper
0.11
232426Y1-080 FULL
Solar/Wind Helper
0.038
233964AF2-378 GEN
Solar/Wind Helper
0.04
233998TM1NIN_3.36
Solar/Wind Helper
0.253
232404W1-003 C
Solar/Wind Helper
0.49
232428Y3-058 C
Solar/Wind Helper
0.327
232434Z2-077 GEN
Solar/Wind Helper
0.123
233954AC2-188 GEN
Solar/Wind Helper
0.225
233950AC2-186 GEN
Solar/Wind Helper
0.112
233972AC1-094 C
Solar/Wind Helper
0.292
316045AC1-158 PL2
Solar/Wind Helper
4.009
230511AF1-262
Solar/Wind Helper
0.014
230434AG1-499 GEN
Solar/Wind Helper
0.222
228728W1-130C
Solar/Wind Helper
0.052
219258KINSLEYDEP C
Solar/Wind Helper
0.074
219904AC1-010 C
Solar/Wind Helper
0.058
218660EHAMPSOLAR C
Solar/Wind Helper
0.032
219907AC1-030 C
Solar/Wind Helper
0.033
219686LUMSOLAR_N C
Solar/Wind Helper
0.038
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.706
24791305MDL-5G
Solar/Wind Harmer
0.001
970333AG2-219 GEN
Solar/Wind Harmer
4.947
274751CRETE EC ;1U
Adder
8.172
274754CRETE EC ;4U
Adder
8.172
274773LINCOLN ;4U
Adder
8.364
274774LINCOLN ;5U
Adder
8.364
274723RIVER EC ;12
Adder
17.756
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.954
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
276776AD2-060 GEN
Solar/Wind Harmer
0.719
24728605AND G2
Adder
3.784
274801UNIV PARK;4U
Adder
5.751
941551AE2-152 GEN
Solar/Wind Harmer
0.001
945681AF1-233 GEN
Solar/Wind Harmer
12.962
274676JOLIET 29;8U
Adder
30.175
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
963741AG1-226 GEN
Solar/Wind Harmer
16.202
939401AE1-172 GEN
Solar/Wind Harmer
5.109
276691AA1-018 GEN1
Solar/Wind Harmer
0.827
276901AD2-066 C O1
Solar/Wind Harmer
0.007
316095T157 G97
Solar/Wind Helper
1.455
23583801GRNGAP
Solar/Wind Helper
5.418
238108AE1-109 GEN1
Solar/Wind Helper
0.106
238185AF2-356 C
Solar/Wind Helper
2.425
238147AE2-230_GEN1
Solar/Wind Helper
0.478
238149AF1-291A_GEN
Solar/Wind Helper
0.137
235531U2-073 GEN
Solar/Wind Helper
3.034
235054AD2-180 GEN
Solar/Wind Helper
1.839
237061AD1-155 GEN
Solar/Wind Helper
0.051
238117U2-030
Solar/Wind Helper
0.314
238221AF1-254 C O1
Solar/Wind Helper
0.265
235067AD1-061 GEN
Solar/Wind Helper
0.478
237030AB1-096 C
Solar/Wind Helper
0.068
3141196NOKESVL
Solar/Wind Helper
0.999
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.335
223402AF1-300 C
Solar/Wind Helper
0.355
23751201ROTHROCK
Solar/Wind Helper
0.694
23562501BACKB
Solar/Wind Helper
0.842
205917AD1-020 ES
Solar/Wind Helper
0.356
233982AB2-133 GEN
Solar/Wind Helper
0.346
233918AB1-142 GEN
Solar/Wind Helper
0.486
233994AC2-023 GEN
Solar/Wind Helper
0.929
233996TM1833_GEN
Solar/Wind Helper
0.253
233997TMININ_4.2
Solar/Wind Helper
0.253
232406W1-004 FULL
Solar/Wind Helper
0.49
233940AF2-379 C
Solar/Wind Helper
0.06
234015AF2-250 C
Solar/Wind Helper
0.037
233952AC2-187 GEN
Solar/Wind Helper
0.225
233971AC1-093 C
Solar/Wind Helper
0.346
316044AC1-158 PL1
Solar/Wind Helper
1.252
316450AC1-158 RIC
Solar/Wind Helper
0.334
230430AE1-229_GEN
Solar/Wind Helper
3.26
230415AB2-049 C
Solar/Wind Helper
0.029
228729W2-030 C
Solar/Wind Helper
0.107
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.053
219912AD2-042 GEN
Solar/Wind Helper
0.145
219291REEVESSOUT C
Solar/Wind Helper
0.011
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.111
316170AC1-121 GEN2
Solar/Wind Helper
0.342
959561AF2-247 GEN
Solar/Wind Helper
0.02
20720828JCB_W4-025
Solar/Wind Helper
0.061
20716028EGP_W2-019
Solar/Wind Helper
0.018
20715028HAN_X4-015
Solar/Wind Helper
0.055
219276PARKLANDSO C
Solar/Wind Helper
0.086
20714528FRN_Y2-051
Solar/Wind Helper
0.055
20720528MAN_W1-024
Solar/Wind Helper
0.027
971997AH1-543 GEN
Solar/Wind Harmer
1.86
270186AC1-089 GEN
Solar/Wind Harmer
0.004
247620Y3-023
Adder
0.466
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
970825AG2-519 GEN
Solar/Wind Harmer
7.834
960441AF2-335 GEN
Solar/Wind Harmer
7.065
270216AD2-079_GEN
Solar/Wind Harmer
0.001
971613AH1-306 GEN
Solar/Wind Harmer
3.385
24728805RICHG1
Adder
3.82
24728905RICHG2
Adder
3.82
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
14.072
961051AF2-396 GEN
Solar/Wind Harmer
9.381
270526AF1-158 GEN
Solar/Wind Harmer
0.009
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
8.77
965791AG1-447 GEN
Solar/Wind Harmer
6.431
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
970239AG2-162 GEN
Solar/Wind Harmer
1.73
274770LINCOLN ;1U
Adder
8.364
274771LINCOLN ;2U
Adder
8.364
274808UNIV PK N;4U
Adder
4.933
966841AG1-555 GEN
Solar/Wind Harmer
0.781
274803UNIV PARK;6U
Adder
5.755
274888KELLY CRK;1U
Solar/Wind Harmer
0.404
274887GEN-1.85
Solar/Wind Harmer
0.181
276843GEN-1.7
Solar/Wind Harmer
0.223
958011AF2-095 GEN
Solar/Wind Harmer
9.913
972259AH1-714 GEN
Adder
18.805
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
970241AG2-163 GEN
Solar/Wind Harmer
3.993
958481AF2-142 GEN
Solar/Wind Harmer
10.238
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.923
971573AH1-285 GEN
Solar/Wind Harmer
1.271
971677AH1-339 GEN
Solar/Wind Harmer
0.768
958491AF2-143 GEN
Solar/Wind Harmer
10.205
274879MINONK ;1U
Solar/Wind Harmer
0.287
238175AF1-290_GEN
Solar/Wind Helper
0.148
238169AE2-226 GEN1
Solar/Wind Helper
0.677
238170AE2-226 GEN2
Solar/Wind Helper
0.677
238120AE2-309 GEN
Solar/Wind Helper
0.487
235020AA1-095 C
Solar/Wind Helper
0.051
23777901MDS_W4-102
Solar/Wind Helper
0.171
23585401KL_K28_T16
Solar/Wind Helper
1.328
237034AC2-136 C
Solar/Wind Helper
0.219
237002AB1-128_GEN
Solar/Wind Helper
0.427
235063AE1-101 C2
Solar/Wind Helper
1.6
237001AB1-127_GEN
Solar/Wind Helper
0.426
23777801MSM_W1-116
Solar/Wind Helper
0.11
237025AB1-124 C
Solar/Wind Helper
0.159
237006AB1-125 GEN
Solar/Wind Helper
0.119
226929AD2-058 GEN
Solar/Wind Helper
0.096
205916AD1-020 GEN
Solar/Wind Helper
1.656
20390526W1-045 C
Solar/Wind Helper
0.338
208835TUHI V3-051
Solar/Wind Helper
0.023
208835TUHI V3-051
Solar/Wind Helper
0.023
233987AB2-037 GEN
Solar/Wind Helper
2.264
233933AB2-153 GEN
Solar/Wind Helper
0.225
232424Y1-079 C
Solar/Wind Helper
0.112
233944AB2-135 GEN
Solar/Wind Helper
0.569
233946AB2-136 GEN
Solar/Wind Helper
0.549
234036AF2-325 C
Solar/Wind Helper
0.041
233901CHERRYDALE C
Solar/Wind Helper
0.225
232408W1-005 C
Solar/Wind Helper
0.49
232410W1-006 C
Solar/Wind Helper
0.49
233939AC1-091 C
Solar/Wind Helper
0.338
233970AC1-092 C
Solar/Wind Helper
0.338
315651AD1-115 GEN
Solar/Wind Helper
0.76
316447AC1-158 HLD
Solar/Wind Helper
2.756
230433AD2-135 GEN
Solar/Wind Helper
0.016
230407AD2-065 C
Solar/Wind Helper
0.039
219921AF1-264
Solar/Wind Helper
0.049
219615MILLCREEK C
Solar/Wind Helper
0.026
963401AG1-189 GEN
Solar/Wind Helper
0.054
963391AG1-188 GEN
Solar/Wind Helper
0.079
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.183
972239AH1-704 GEN
50/50
2.78
962771AG1-126 GEN
Solar/Wind Harmer
33.269
270459AD2-067 GEN
Solar/Wind Harmer
0
270054AF2-122 C O1
Solar/Wind Harmer
0.007
961821AG1-024 GEN
Solar/Wind Harmer
4.91
270520AE2-214 GEN
Solar/Wind Harmer
0.013
270284AF1-227 GEN1
Solar/Wind Harmer
0.01
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
253383AE2-342_GEN
Solar/Wind Harmer
0.003
241973AD2-163_GEN1
Solar/Wind Harmer
0.006
945631AF1-228 GEN
Solar/Wind Harmer
0
943861AF1-054 GEN
Solar/Wind Harmer
3.02
943851AF1-053 GEN
Solar/Wind Harmer
2.092
270156DARBY CT1
Adder
10.05
270157DARBY CT2
Adder
10.026
270158DARBY CT3
Adder
9.866
270578AF1-285 GEN2
Solar/Wind Harmer
0.518
970689AG2-444 GEN
Solar/Wind Harmer
15.861
270432AC2-029 GEN
Solar/Wind Harmer
3.428
940611AE2-048 GEN
Solar/Wind Harmer
18.967
941391AE2-136 GEN
Solar/Wind Harmer
10.684
270302AB2-170 GEN
Solar/Wind Harmer
0.005
270317AD1-130_GEN
Solar/Wind Harmer
0.011
971653AH1-327 GEN
Solar/Wind Harmer
1.08
270269AC2-059
Solar/Wind Harmer
0.004
241972AD1-140 GEN
Solar/Wind Harmer
0.824
970179AG2-119 GEN
Solar/Wind Harmer
6.658
270340AC2-060 GEN
Solar/Wind Harmer
0.009
970879AG2-548 GEN
Solar/Wind Harmer
6.645
253372AE2-315 SEC3
Adder
1.989
253372AE2-315 SEC3
Adder
1.989
25306009OHH W.
Adder
3.018
253349AC2-067 GEN
Solar/Wind Harmer
2.296
253400AC2-068 GEN
Solar/Wind Harmer
0.923
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
0.92
965051AG1-369 GEN
Solar/Wind Harmer
3.609
219304NAMERICA C
Solar/Wind Helper
0.127
316254AC1-120 GEN1
Solar/Wind Helper
1.026
20720728JCB_W1-129
Solar/Wind Helper
0.055
207445AB1-138_GEN
Solar/Wind Helper
0.101
963711AG1-223 GEN
Solar/Wind Helper
0.062
20714828MDF_W3-079
Solar/Wind Helper
0.126
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.299
20715228NPK_W1-113
Solar/Wind Helper
0.075
971567AH1-282 GEN
Solar/Wind Harmer
10.843
247607V1-011 GEN
Solar/Wind Harmer
0.001
965041AG1-368 GEN
Solar/Wind Harmer
7.21
971989AH1-539 GEN
Solar/Wind Harmer
3.109
963791AG1-232 GEN
Solar/Wind Harmer
9.689
24729505KEY G4
Adder
6.671
270071AF1-092 GEN
Solar/Wind Harmer
13.737
270024AE2-089 GEN
Solar/Wind Harmer
0.008
971985AH1-537 GEN
Solar/Wind Harmer
2.123
965101AG1-375 GEN
Solar/Wind Harmer
7.135
270297AD1-101 GEN
Solar/Wind Harmer
0.002
270367AC2-061_GEN
Solar/Wind Harmer
0.006
971673AH1-337 GEN
Solar/Wind Harmer
4.631
971029AG2-637 GEN
Solar/Wind Harmer
10.686
270543AE2-219 C
Solar/Wind Harmer
0.004
252524AE2-267 GEN
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
9.002
25196308WSDLE2
Adder
8.924
25196208WSDLE1
Adder
8.902
25196708WSDLE6
Adder
8.879
25196508WSDLE4
Adder
8.656
945581AF1-223 GEN
Solar/Wind Harmer
0.001
971347AH1-153 GEN
Solar/Wind Harmer
10.632
971609AH1-304 GEN
Solar/Wind Harmer
1.157
270240V3-007_GEN2
Solar/Wind Harmer
0.002
970115AG2-085 GEN
Solar/Wind Harmer
2.826
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
270594AE1-207 GEN
Solar/Wind Harmer
7.898
971771AH1-392 GEN
Solar/Wind Harmer
7.046
970289AG2-191 GEN
Solar/Wind Harmer
1.339
971619AH1-309 GEN
Solar/Wind Harmer
3.169
971769AH1-391 GEN
Solar/Wind Harmer
7.844
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
25196108MFTGT2
Adder
1.54
25196108MFTGT2
Adder
1.43
270536AF1-215 GEN2
Solar/Wind Harmer
0.009
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
4.146
971549AH1-272 GEN
Solar/Wind Harmer
14.344
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
8.364
274776LINCOLN ;7U
Adder
8.364
274777LINCOLN ;8U
Adder
8.364
274814UNIV PK N;0U
Adder
4.998
274807UNIV PK N;3U
Adder
4.987
274805UNIV PK N;1U
Adder
4.965
274811UNIV PK N;7U
Adder
4.954
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
972037AH1-567 GEN1
Adder
0.181
960591AF2-350 GEN
Solar/Wind Harmer
6.884
274827FISK ;RP
Adder
7.655
972227AH1-698 GEN1
Adder
2.573
963841AG1-237 GEN
Solar/Wind Harmer
2.978
274687WILL CNTY;4U
Adder
27.495
274687WILL CNTY;4U
Adder
27.495
274675JOLIET 29;7U
Adder
30.175
274675JOLIET 29;7U
Adder
29.097
972163AH1-664 GEN
Solar/Wind Harmer
7.639
972165AH1-665 GEN
Solar/Wind Harmer
6.118
274731ELWOOD EC;2P
Adder
16.163
274733ELWOOD EC;3P
Adder
16.163
274735ELWOOD EC;4P
Adder
16.163
274728ELWOOD EC;5P
Adder
16.163
970833AG2-524 GEN
Solar/Wind Harmer
7.542
970833AG2-524 GEN
Solar/Wind Harmer
5.028
945641AF1-229 GEN
Solar/Wind Harmer
0.001
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
276868AE1-113 GEN
Solar/Wind Harmer
1.363
276882AE2-255 GEN
Solar/Wind Harmer
0.794
238109AE1-109 GEN2
Solar/Wind Helper
0.106
238110AE1-109 GEN3
Solar/Wind Helper
0.106
238152AF2-075_GEN
Solar/Wind Helper
0.683
23546401DTGZ2-030
Solar/Wind Helper
0.086
238208AF1-136 C
Solar/Wind Helper
0.211
238126S14_GEN_1
Solar/Wind Helper
0.766
237085AD2-009_GEN
Solar/Wind Helper
1.588
3138216PACIFIC
Solar/Wind Helper
0.043
316411AF1-147_GEN1
Solar/Wind Helper
0.86
316415AF1-147_GEN2
Solar/Wind Helper
0.86
959381AF2-229 GEN
Solar/Wind Helper
0.345
23750501ELLIOTTS
Solar/Wind Helper
0.571
3141426STAFORD
Solar/Wind Helper
0.051
960921AF2-383 GEN
Solar/Wind Helper
0.352
205943AE1-185 GEN
Solar/Wind Helper
0.492
205956AE1-196_GEN
Solar/Wind Helper
0.492
205932AD2-116_GEN
Solar/Wind Helper
0.492
233935AB2-179 C
Solar/Wind Helper
1.227
232436AB1-176 C
Solar/Wind Helper
0.043
233923SMA
Solar/Wind Helper
0.927
233990AG1-397 GEN
Solar/Wind Helper
0.261
234033AF1-007_GEN
Solar/Wind Helper
6.787
232432Z2-076 GEN
Solar/Wind Helper
0.065
964001AG1-254 GEN
Solar/Wind Helper
0.924
228754AB1-001 C
Solar/Wind Helper
0.025
227927V4-067C
Solar/Wind Helper
0.01
219914AD2-027 C
Solar/Wind Helper
0.111
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.038
219607WPEMNERT C
Solar/Wind Helper
0.077
214067T20SOLAR
Solar/Wind Helper
0.011
203975AE1-071-GEN
Solar/Wind Helper
2.41
20715728PEM_W1-119
Solar/Wind Helper
0.093
20715828PEM_W1-120
Solar/Wind Helper
0.093
207459AE1-142 C O1
Solar/Wind Helper
0.28
316164AC1-076 GEN
Solar/Wind Helper
1.062
219620RIDERU C
Solar/Wind Helper
0.001
NYPJM->LTFIMP_NY
CLTF
4.628
LGEELTFEXP_LGEE->PJM
CLTF
6.497
WECLTFEXP_WEC->PJM
CLTF
3.686
AG2-052LTFEXP_AG2-052->PJM
LTF
0.231
AH1-155LTFEXP_AH1-155->PJM
LTF
0.346
LAGNLTFEXP_LAGN->PJM
CLTF
14.268
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.432
TVALTFEXP_TVA->PJM
CLTF
7.011
CBM West 1LTFEXP_CBM-W1->PJM
CBM
137.982
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.984
MECLTFEXP_MEC->PJM
CLTF
15.319
SIGELTFEXP_SIGE->PJM
CLTF
0.486
CPLELTFEXP_CPLE->PJM
CLTF
0.567
CBM West 2LTFEXP_CBM-W2->PJM
CBM
108.576

Details for 02BAY SH-02DAV-BE 345.0 kV Ckt 1 line l/o ATSI_P1-2_TE-345-602_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_TE-345-602_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:142.52 %
Rating:1683.0 MVA
Rating Type:B
MVA to Mitigate:2398.59
MW Contribution:1.59
Bus #Bus NameTypeMW Contribution
972211AH1-690 GEN
50/50
445.374
23888502TROY G1
50/50
1.526
23888602TROY G2
50/50
1.526
970817AG2-515 GEN
Solar/Wind Harmer
9.949
945411AF1-206 GEN
Solar/Wind Harmer
-0.001
945641AF1-229 GEN
Solar/Wind Harmer
0.001
270499AE1-146 GEN
Solar/Wind Harmer
0.029
971549AH1-272 GEN
Solar/Wind Harmer
11.98
270297AD1-101 GEN
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.588
971619AH1-309 GEN
Solar/Wind Harmer
2.081
247607V1-011 GEN
Solar/Wind Harmer
0.001
971771AH1-392 GEN
Solar/Wind Harmer
4.385
965041AG1-368 GEN
Solar/Wind Harmer
4.372
965051AG1-369 GEN
Solar/Wind Harmer
2.168
971989AH1-539 GEN
Solar/Wind Harmer
1.862
971769AH1-391 GEN
Solar/Wind Harmer
4.78
270302AB2-170 GEN
Solar/Wind Harmer
0.003
270317AD1-130_GEN
Solar/Wind Harmer
0.006
971653AH1-327 GEN
Solar/Wind Harmer
0.58
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971347AH1-153 GEN
Solar/Wind Harmer
6.147
963791AG1-232 GEN
Solar/Wind Harmer
5.327
971567AH1-282 GEN
Solar/Wind Harmer
5.89
270536AF1-215 GEN2
Solar/Wind Harmer
0.005
270578AF1-285 GEN2
Solar/Wind Harmer
0.256
274814UNIV PK N;0U
Adder
2.746
274807UNIV PK N;3U
Adder
2.74
274805UNIV PK N;1U
Adder
2.728
274811UNIV PK N;7U
Adder
2.722
270071AF1-092 GEN
Solar/Wind Harmer
7.267
958391AF2-133 GEN
Solar/Wind Harmer
0.001
972037AH1-567 GEN1
Adder
0.098
274827FISK ;RP
Adder
4.165
960591AF2-350 GEN
Solar/Wind Harmer
3.734
274775LINCOLN ;6U
Adder
4.515
274776LINCOLN ;7U
Adder
4.515
274777LINCOLN ;8U
Adder
4.515
971611AH1-305 GEN
Solar/Wind Harmer
2.222
972227AH1-698 GEN1
Adder
1.392
274687WILL CNTY;4U
Adder
14.867
274687WILL CNTY;4U
Adder
14.867
274675JOLIET 29;7U
Adder
16.292
274675JOLIET 29;7U
Adder
15.71
274728ELWOOD EC;5P
Adder
8.714
274731ELWOOD EC;2P
Adder
8.713
274733ELWOOD EC;3P
Adder
8.713
274735ELWOOD EC;4P
Adder
8.713
970833AG2-524 GEN
Solar/Wind Harmer
4.049
970833AG2-524 GEN
Solar/Wind Harmer
2.699
274746AC1-111 G10
Adder
2.931
274744AC1-111 GEN8
Adder
2.931
276868AE1-113 GEN
Solar/Wind Harmer
0.724
276882AE2-255 GEN
Solar/Wind Harmer
0.422
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0.004
971177AH1-047 GEN
Solar/Wind Harmer
2.216
971411AH1-196 GEN
Solar/Wind Harmer
5.375
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
1.396
971171AH1-044 GEN
Solar/Wind Harmer
7.133
274823ROCKFORD ;21
Adder
9.941
926823AC1-168 GEN
Solar/Wind Harmer
0.603
970169AG2-114 GEN
Solar/Wind Harmer
3.546
276612AE2-035 GEN
Solar/Wind Harmer
0.001
24729505KEY G4
Adder
3.294
971681AH1-341 GEN
Solar/Wind Harmer
5.682
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
24387005FR-3G C
Solar/Wind Harmer
0.001
961011AF2-392 GEN
Solar/Wind Harmer
2.056
957751AF2-069 GEN
Solar/Wind Harmer
0.115
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
276655WTG1_EQ
Solar/Wind Harmer
0.001
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.644
941731AE2-173 GEN
Solar/Wind Harmer
2.892
963841AG1-237 GEN
Solar/Wind Harmer
1.492
946321AF1-296 GEN
Solar/Wind Harmer
1.922
965101AG1-375 GEN
Solar/Wind Harmer
3.421
971609AH1-304 GEN
Solar/Wind Harmer
0.55
945581AF1-223 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.635
276785W4-005 GEN1
Solar/Wind Harmer
0
276174W4-005 GEN2
Solar/Wind Harmer
0
276849AB2-070 GEN2
Solar/Wind Harmer
0.121
276848AB2-070 GEN3
Solar/Wind Harmer
0.12
270594AE1-207 GEN
Solar/Wind Harmer
3.716
970115AG2-085 GEN
Solar/Wind Harmer
1.302
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0
241886AC2-103 GEN2
Solar/Wind Helper
6.849
241982AE2-343 S C
Solar/Wind Helper
0.12
254304AE2-114 C
Solar/Wind Helper
0.114
203846AF2-130 C
Solar/Wind Helper
0.251
241997AF1-093 GEN
Solar/Wind Helper
0.132
203804AE2-113_GEN
Solar/Wind Helper
0.869
24189902OREGON_CT2
50/50
4.125
23856402BAYSG1
50/50
1.577
23888702TROY G3
50/50
1.526
972253AH1-711 GEN
50/50
46.611
23920202STRYCT
50/50
1.928
241808AF1-120 C
Solar/Wind Harmer
0.003
241858AF1-205_GEN
Solar/Wind Harmer
3.78
241840AF1-064_GEN
Solar/Wind Harmer
0.004
972301AH1-735 GEN
Adder
6.727
23906402RICHG1
Adder
1.345
23906502RICHG2&3
Adder
1.343
270361_3
Solar/Wind Harmer
4.521
960841AF2-375 GEN
Solar/Wind Harmer
-0.002
970515AG2-329 GEN
Solar/Wind Harmer
14.08
944231AF1-091 GEN
Solar/Wind Harmer
1.351
247522W1-056 GEN
Solar/Wind Harmer
0.001
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.47
246936BC-WTG1
Solar/Wind Harmer
0.188
270489AE1-102 GEN1
Solar/Wind Harmer
0.603
945111AF1-176 GEN
Solar/Wind Harmer
8.251
270505AE1-170 C O1
Solar/Wind Harmer
4.856
965421AG1-410 GEN
Solar/Wind Harmer
13.81
24639705ELKHART HY
Adder
0.098
24695305TIMB G C
Solar/Wind Harmer
0.001
270063AE2-323 C
Solar/Wind Harmer
0.004
247521TR3_G114
Solar/Wind Harmer
0.158
270246TR4_N_V150
Solar/Wind Harmer
0.028
965011AG1-365 GEN
Solar/Wind Harmer
4.252
270462AD2-086
Solar/Wind Harmer
0.009
970373AG2-245 GEN
Solar/Wind Harmer
8.33
270055AF2-134 C O1
Solar/Wind Harmer
0.003
24190002OREGON_ST1
50/50
5.55
24189802OREGON_CT1
50/50
4.21
23888802TROY G4
50/50
1.526
241996AE2-282_GEN
Solar/Wind Harmer
0.006
971677AH1-339 GEN
Solar/Wind Harmer
0.659
970621AG2-405 GEN
Solar/Wind Harmer
0.944
970623AG2-406 GEN
Solar/Wind Harmer
0.885
961051AF2-396 GEN
Solar/Wind Harmer
9.384
961051AF2-396 GEN
Solar/Wind Harmer
6.256
246938BC-WTG3
Solar/Wind Harmer
0.168
246937BC-WTG2
Solar/Wind Harmer
0.188
957891AF2-083 GEN
Solar/Wind Harmer
0.001
270007AE1-245 C
Solar/Wind Harmer
0.001
247620Y3-023
Adder
0.296
270223U2-072_GEN1
Solar/Wind Harmer
0
274751CRETE EC ;1U
Adder
4.532
274754CRETE EC ;4U
Adder
4.532
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
4.962
274723RIVER EC ;12
Adder
9.782
274812UNIV PK N;8U
Adder
2.722
276164X3-005 C
Solar/Wind Harmer
0
274801UNIV PARK;4U
Adder
3.125
276776AD2-060 GEN
Solar/Wind Harmer
0.39
274773LINCOLN ;4U
Adder
4.515
274774LINCOLN ;5U
Adder
4.515
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
4.664
274676JOLIET 29;8U
Adder
16.292
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
8.714
274674JOLIET 9 ;6U
Adder
8.161
970245AG2-165 GEN
Solar/Wind Harmer
1.596
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
2.931
276691AA1-018 GEN1
Solar/Wind Harmer
0.443
274682WAUKEGAN ;7U
Adder
9.363
274828WAUKEGAN ;BP
Adder
5.75
276901AD2-066 C O1
Solar/Wind Harmer
0.004
939401AE1-172 GEN
Solar/Wind Harmer
2.703
962781AG1-127 GEN
Solar/Wind Harmer
3.433
274872LEEDK;1U
Solar/Wind Harmer
0.002
24791305MDL-5G
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
1.887
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
276861AD2-134 GEN
Solar/Wind Harmer
0.064
957471AF2-041 GEN
Solar/Wind Harmer
10.7
959081AF2-199 GEN
Solar/Wind Harmer
3.567
971067AG2-660 GEN
Solar/Wind Harmer
1.189
274822ROCKFORD ;11
Adder
10.013
972235AH1-702 GEN1
Adder
1.284
970569AG2-363 GEN
Solar/Wind Harmer
10.66
970819AG2-516 GEN
Solar/Wind Harmer
4.256
971475AH1-234 GEN
Solar/Wind Harmer
1.718
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
4.693
274766LEE CO EC;7U
Adder
4.638
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.001
276158O29GEN2
Solar/Wind Harmer
0
274877BISHOP HL;1U
Solar/Wind Harmer
0.117
276726Z2-087_GEN
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
4.858
965651AG1-433 GEN
Solar/Wind Harmer
1.012
274854TWINGROVE;U2
Solar/Wind Harmer
0.001
958861AF2-177 GEN
Solar/Wind Harmer
1.482
963741AG1-226 GEN
Solar/Wind Harmer
7.999
972175AH1-670 GEN
Solar/Wind Harmer
2.788
945371AF1-202 GEN
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.435
274880W4-005 GEN4
Solar/Wind Harmer
0
270032AE2-172
Solar/Wind Harmer
2.212
963831AG1-236 GEN
Solar/Wind Harmer
1.29
247536S-71 GEN
Solar/Wind Harmer
0.132
276615X2-022 GEN
Solar/Wind Harmer
0.034
276903AD2-071 C
Solar/Wind Harmer
3.649
970825AG2-519 GEN
Solar/Wind Harmer
1.153
270005AE1-210 C O1
Solar/Wind Harmer
0.7
241885AC2-103 GEN1
Solar/Wind Helper
6.849
241807AE2-176_GEN
Solar/Wind Helper
1.64
961971AG1-040 GEN
Solar/Wind Helper
0.342
203835AF1-098 GEN
Solar/Wind Helper
1.348
203860AG1-193 C
Solar/Wind Helper
0.152
241966AE1-183 GEN
Solar/Wind Helper
0.132
254303AC2-168 GEN
Solar/Wind Helper
0.077
965031AG1-367 GEN
Solar/Wind Harmer
0.798
270216AD2-079_GEN
Solar/Wind Harmer
0.001
270526AF1-158 GEN
Solar/Wind Harmer
0.005
24441505OLIV SLR
Solar/Wind Harmer
0
970611AG2-400 GEN
Solar/Wind Harmer
4.252
970627AG2-408 GEN
Solar/Wind Harmer
1.276
965681AG1-436 GEN
Solar/Wind Harmer
5.151
965791AG1-447 GEN
Solar/Wind Harmer
3.778
270224U2-072_GEN2
Solar/Wind Harmer
0
270227U2-072_GEN3
Solar/Wind Harmer
0
270228U2-072_GEN4
Solar/Wind Harmer
0
270231U2-072_GEN5
Solar/Wind Harmer
0
274808UNIV PK N;4U
Adder
2.71
274803UNIV PARK;6U
Adder
3.135
274888KELLY CRK;1U
Solar/Wind Harmer
0.219
274887GEN-1.85
Solar/Wind Harmer
0.098
276843GEN-1.7
Solar/Wind Harmer
0.121
958011AF2-095 GEN
Solar/Wind Harmer
5.377
274770LINCOLN ;1U
Adder
4.515
274771LINCOLN ;2U
Adder
4.515
972259AH1-714 GEN
Adder
10.138
274674JOLIET 9 ;6U
Adder
8.161
970321AG2-212 GEN
Solar/Wind Harmer
1.596
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
958481AF2-142 GEN
Solar/Wind Harmer
5.485
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.495
942221AE2-234 GEN
Solar/Wind Harmer
0.018
971573AH1-285 GEN
Solar/Wind Harmer
0.679
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
274696ROCKY RD ;4P
Adder
5.936
274695ROCKY RD ;2P
Adder
5.799
274693ROCKY RD ;1P
Adder
5.742
274697ROCKY RD ;3P
Adder
1.575
274683WAUKEGAN ;8U
Adder
10.969
274683WAUKEGAN ;8U
Adder
9.246
958491AF2-143 GEN
Solar/Wind Harmer
5.438
962691AG1-118 GEN
Solar/Wind Harmer
10.84
274879MINONK ;1U
Solar/Wind Harmer
0.152
970921AG2-575 GEN
Solar/Wind Harmer
3.608
970921AG2-575 GEN
Solar/Wind Harmer
1.203
942991AE2-321 GEN
Solar/Wind Harmer
4.013
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
971333AH1-146 GEN
Solar/Wind Harmer
7.161
971335AH1-147 GEN
Solar/Wind Harmer
7.161
971341AH1-150 GEN
Solar/Wind Harmer
7.133
971343AH1-151 GEN
Solar/Wind Harmer
7.133
274856ECOGROVE ;U1
Solar/Wind Harmer
0.084
276611AD2-172 GEN
Solar/Wind Harmer
0.001
938861AE1-114 GEN
Solar/Wind Harmer
1.999
274764LEE CO EC;5U
Adder
4.704
274765LEE CO EC;6U
Adder
4.704
274762LEE CO EC;3U
Adder
4.693
274763LEE CO EC;4U
Adder
4.649
276603SUBLETTE C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.397
274851PROVIDENC;RU
Solar/Wind Harmer
0
274849CRESCENT ;1U
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.137
276646AC1-214 GEN2
Solar/Wind Harmer
0.137
276741O09 GEN1
Solar/Wind Harmer
0.124
276708O09 GEN2
Solar/Wind Harmer
0.124
276782AC1-033 GEN
Solar/Wind Harmer
0.001
944541AF1-119 GEN
Solar/Wind Harmer
0.231
960971AF2-388 GEN
Solar/Wind Harmer
2.024
960611AF2-352 GEN
Solar/Wind Harmer
1.144
970241AG2-163 GEN
Solar/Wind Harmer
1.972
270201AC2-176 GEN
Solar/Wind Harmer
0.001
270599AE1-208 GEN
Solar/Wind Harmer
3.085
270031AE2-169
Solar/Wind Harmer
1.851
964611AG1-324 GEN
Solar/Wind Harmer
0.251
971613AH1-306 GEN
Solar/Wind Harmer
1.593
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
971231AH1-075 GEN
Solar/Wind Harmer
0.377
960441AF2-335 GEN
Solar/Wind Harmer
3.255
970825AG2-519 GEN
Solar/Wind Harmer
3.6
203947AF1-006 C
Solar/Wind Helper
0.391
203980AG1-197 GEN
Solar/Wind Helper
0.255
203979AG1-198 GEN
Solar/Wind Helper
0.198
241801AE1-079 GEN
Solar/Wind Helper
0.134
241967AE2-285_GEN
Solar/Wind Helper
0.345
241985AE1-237 GEN
Solar/Wind Helper
0.134
962101AG1-054 GEN
Solar/Wind Helper
0.332
946381AF1-302 GEN
Solar/Wind Helper
0.105
238217AF1-153 C O1
Solar/Wind Helper
0.111
23929302BS-PKR
50/50
2.775
241832AE2-181_GEN
Solar/Wind Harmer
0.004
958321AF2-126 GEN
Solar/Wind Harmer
1.136
23906502RICHG2&3
Adder
1.343
270541AE2-072 C
Solar/Wind Harmer
0.008
270575GUS2 35KV
Solar/Wind Harmer
4.521
970217AG2-149 GEN
Solar/Wind Harmer
4.693
247604X1-042
Adder
0.303
270404AC1-167 GEN
Solar/Wind Harmer
0.002
24441205WTRV SLR C
Solar/Wind Harmer
0
270258AD1-119 GEN
Solar/Wind Harmer
0.001
270491AE1-102 GEN2
Solar/Wind Harmer
0.603
945111AF1-176 GEN
Solar/Wind Harmer
3.748
270588AE1-091_GEN
Solar/Wind Harmer
3.595
24642205MAYFLWER
Adder
0.41
247643Z2-116 C
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
2.866
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.028
959331AF2-224 GEN
Solar/Wind Harmer
2.976
965021AG1-366 GEN
Solar/Wind Harmer
1.417
270485AE1-090_GEN
Solar/Wind Harmer
0.001
970349AG2-230 GEN
Solar/Wind Harmer
6.147
270043AE2-236 GEN
Solar/Wind Harmer
2.609
270535AF1-215 GEN1
Solar/Wind Harmer
0.005
270391AF1-285 GEN3
Solar/Wind Harmer
0.256
274752CRETE EC ;2U
Adder
4.532
274753CRETE EC ;3U
Adder
4.532
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274724RIVER EC ;11
Adder
9.666
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
274802UNIV PARK;5U
Adder
3.135
274826FISK ;BP
Adder
5.877
274800UNIV PARK;3U
Adder
3.125
972038AH1-567 GEN2
Adder
0.196
276806AD2-047 C O1
Solar/Wind Harmer
2.116
970941AG2-585 GEN
Solar/Wind Harmer
4.668
274772LINCOLN ;3U
Adder
4.515
972228AH1-698 GEN2
Adder
1.977
274676JOLIET 29;8U
Adder
15.71
276897AD1-100 C
Solar/Wind Harmer
0.005
939351AE1-166 GEN
Solar/Wind Harmer
0
276893AG1-478 C
Solar/Wind Harmer
0.147
274730ELWOOD EC;6P
Adder
8.714
274734ELWOOD EC;8P
Adder
8.714
274736ELWOOD EC;9P
Adder
8.714
274729ELWOOD EC;1P
Adder
8.713
970707AG2-453 GEN
Solar/Wind Harmer
12.079
970513AG2-328 GEN
Solar/Wind Harmer
1.596
970517AG2-330 GEN
Solar/Wind Harmer
9.577
943121AE2-341 GEN
Solar/Wind Harmer
6.132
943591AF1-030 GEN
Solar/Wind Harmer
4.078
276694AA1-018 GEN2
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
9.363
276805AD2-038 GEN
Solar/Wind Harmer
0.001
274872LEEDK;1U
Solar/Wind Harmer
0.132
24755605MDL-5G
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.599
971617AH1-308 GEN
Solar/Wind Harmer
2.996
276889AE2-281 GEN
Solar/Wind Harmer
0
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.382
274855GSG-6 ;RU
Solar/Wind Harmer
0.131
274850MENDOTA H;RU
Solar/Wind Harmer
0.042
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.064
944531AF1-118 GEN
Solar/Wind Harmer
16.023
959091AF2-200 GEN
Solar/Wind Harmer
7.133
972236AH1-702 GEN2
Adder
1.116
970571AG2-364 GEN
Solar/Wind Harmer
7.107
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
4.693
274767LEE CO EC;8U
Adder
1.086
276157O29GEN1
Solar/Wind Harmer
0.565
274878BISHOP HL;2U
Solar/Wind Harmer
0.117
942111AE2-223 GEN
Solar/Wind Harmer
1.128
274853TWINGROVE;U1
Solar/Wind Harmer
0.001
965091AG1-374 GEN
Solar/Wind Harmer
10.299
959611AF2-252 GEN
Solar/Wind Harmer
1.144
965931AG1-462 GEN
Solar/Wind Harmer
8.719
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
5.066
247642Z2-115 C
Solar/Wind Harmer
0.001
970289AG2-191 GEN
Solar/Wind Harmer
0.368
970291AG2-192 GEN
Solar/Wind Harmer
0.334
276686W4-005 GEN3
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.121
971993AH1-541 GEN
Solar/Wind Harmer
1.533
270377AD1-106 GEN
Solar/Wind Harmer
1.25
276621W2-048 GEN
Solar/Wind Harmer
0.166
276838X2-022 GEN2
Solar/Wind Harmer
0.185
946031AF1-268 GEN
Solar/Wind Harmer
3.103
958821AF2-173 GEN
Solar/Wind Harmer
4.521
270004AE1-209 GEN
Solar/Wind Harmer
0.7
962511AG1-100 GEN
Solar/Wind Helper
0.35
203830AF1-094 GEN
Solar/Wind Helper
0.331
959441AF2-235 GEN
Solar/Wind Helper
0.15
254305AE2-115 C
Solar/Wind Helper
0.114
20334926Z1-069 C
Solar/Wind Helper
0.646
990142J1224
External Queue
14.791350364685059
990527J1329
External Queue
2.0234405994415283
991177J1571 G
External Queue
15.792752265930176
991182J1586 G
External Queue
28.11846351623535
NYPJM->LTFIMP_NY
CLTF
1.965
LGEELTFEXP_LGEE->PJM
CLTF
2.4
WECLTFEXP_WEC->PJM
CLTF
1.946
AG2-052LTFEXP_AG2-052->PJM
LTF
0.125
AH1-155LTFEXP_AH1-155->PJM
LTF
0.187
LAGNLTFEXP_LAGN->PJM
CLTF
6.061
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.4
TVALTFEXP_TVA->PJM
CLTF
2.775
CBM West 1LTFEXP_CBM-W1->PJM
CBM
112.86
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.907
MECLTFEXP_MEC->PJM
CLTF
7.633
SIGELTFEXP_SIGE->PJM
CLTF
0.2
CPLELTFEXP_CPLE->PJM
CLTF
0.731
CBM West 2LTFEXP_CBM-W2->PJM
CBM
47.539

Details for 02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line l/o ATSI_P1-2_TE-345-601_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_TE-345-601_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.99 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:2140.73
MW Contribution:1.64
Bus #Bus NameTypeMW Contribution
23888702TROY G3
50/50
2.643
972253AH1-711 GEN
50/50
80.741
23920202STRYCT
50/50
2.39
24189902OREGON_CT2
50/50
2.176
972301AH1-735 GEN
50/50
8.755
23906402RICHG1
50/50
1.751
23906502RICHG2&3
50/50
1.747
241858AF1-205_GEN
Solar/Wind Harmer
4.885
241808AF1-120 C
Solar/Wind Harmer
0.004
241840AF1-064_GEN
Solar/Wind Harmer
0.005
270361_3
Solar/Wind Harmer
4.971
960841AF2-375 GEN
Solar/Wind Harmer
-0.002
970515AG2-329 GEN
Solar/Wind Harmer
15.158
944231AF1-091 GEN
Solar/Wind Harmer
1.488
247522W1-056 GEN
Solar/Wind Harmer
0.001
246936BC-WTG1
Solar/Wind Harmer
0.199
270489AE1-102 GEN1
Solar/Wind Harmer
0.637
965421AG1-410 GEN
Solar/Wind Harmer
14.575
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.476
24695305TIMB G C
Solar/Wind Harmer
0.001
945111AF1-176 GEN
Solar/Wind Harmer
8.299
270505AE1-170 C O1
Solar/Wind Harmer
4.878
247521TR3_G114
Solar/Wind Harmer
0.167
270246TR4_N_V150
Solar/Wind Harmer
0.03
24639705ELKHART HY
Adder
0.1
270063AE2-323 C
Solar/Wind Harmer
0.004
965011AG1-365 GEN
Solar/Wind Harmer
4.433
270462AD2-086
Solar/Wind Harmer
0.009
270223U2-072_GEN1
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
8.434
270055AF2-134 C O1
Solar/Wind Harmer
0.003
274751CRETE EC ;1U
Adder
4.596
274754CRETE EC ;4U
Adder
4.596
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
5.035
274723RIVER EC ;12
Adder
9.924
274812UNIV PK N;8U
Adder
2.762
276164X3-005 C
Solar/Wind Harmer
0
274801UNIV PARK;4U
Adder
3.173
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
4.739
276776AD2-060 GEN
Solar/Wind Harmer
0.396
274773LINCOLN ;4U
Adder
4.584
274774LINCOLN ;5U
Adder
4.584
274676JOLIET 29;8U
Adder
16.543
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
8.849
274674JOLIET 9 ;6U
Adder
8.288
970245AG2-165 GEN
Solar/Wind Harmer
1.623
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
2.978
23906502RICHG2&3
50/50
1.747
241832AE2-181_GEN
Solar/Wind Harmer
0.004
958321AF2-126 GEN
Solar/Wind Harmer
1.413
23929302BS-PKR
Adder
1.959
270541AE2-072 C
Solar/Wind Harmer
0.01
270575GUS2 35KV
Solar/Wind Harmer
4.971
970217AG2-149 GEN
Solar/Wind Harmer
5.053
23888502TROY G1
50/50
2.643
23888602TROY G2
50/50
2.643
972211AH1-690 GEN
50/50
234.282
23906902RICHG6
50/50
1.04
23906702RICHG4
50/50
1.037
23906802RICHG5
50/50
0.758
970817AG2-515 GEN
Solar/Wind Harmer
14.376
945411AF1-206 GEN
Solar/Wind Harmer
-0.001
945641AF1-229 GEN
Solar/Wind Harmer
0.001
270499AE1-146 GEN
Solar/Wind Harmer
0.032
971549AH1-272 GEN
Solar/Wind Harmer
11.871
270297AD1-101 GEN
Solar/Wind Harmer
0.001
247607V1-011 GEN
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.621
971989AH1-539 GEN
Solar/Wind Harmer
2.024
971619AH1-309 GEN
Solar/Wind Harmer
2.091
965041AG1-368 GEN
Solar/Wind Harmer
4.612
965051AG1-369 GEN
Solar/Wind Harmer
2.289
971771AH1-392 GEN
Solar/Wind Harmer
4.424
270302AB2-170 GEN
Solar/Wind Harmer
0.003
270317AD1-130_GEN
Solar/Wind Harmer
0.006
971653AH1-327 GEN
Solar/Wind Harmer
0.621
971769AH1-391 GEN
Solar/Wind Harmer
4.822
971567AH1-282 GEN
Solar/Wind Harmer
6.357
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971347AH1-153 GEN
Solar/Wind Harmer
6.22
963791AG1-232 GEN
Solar/Wind Harmer
5.569
270578AF1-285 GEN2
Solar/Wind Harmer
0.274
270536AF1-215 GEN2
Solar/Wind Harmer
0.005
270071AF1-092 GEN
Solar/Wind Harmer
7.505
274814UNIV PK N;0U
Adder
2.786
274807UNIV PK N;3U
Adder
2.78
274805UNIV PK N;1U
Adder
2.768
274811UNIV PK N;7U
Adder
2.762
958391AF2-133 GEN
Solar/Wind Harmer
0.001
972037AH1-567 GEN1
Adder
0.1
274827FISK ;RP
Adder
4.228
971611AH1-305 GEN
Solar/Wind Harmer
2.257
960591AF2-350 GEN
Solar/Wind Harmer
3.791
274775LINCOLN ;6U
Adder
4.584
274776LINCOLN ;7U
Adder
4.584
274777LINCOLN ;8U
Adder
4.584
972227AH1-698 GEN1
Adder
1.413
274687WILL CNTY;4U
Adder
15.095
274687WILL CNTY;4U
Adder
15.095
274675JOLIET 29;7U
Adder
16.543
270404AC1-167 GEN
Solar/Wind Harmer
0.002
270258AD1-119 GEN
Solar/Wind Harmer
0.001
247604X1-042
Adder
0.302
270588AE1-091_GEN
Solar/Wind Harmer
3.901
24441205WTRV SLR C
Solar/Wind Harmer
0
270491AE1-102 GEN2
Solar/Wind Harmer
0.637
945111AF1-176 GEN
Solar/Wind Harmer
3.77
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.03
24642205MAYFLWER
Adder
0.413
970031AG2-029 GEN
Solar/Wind Harmer
2.93
247643Z2-116 C
Solar/Wind Harmer
0
959331AF2-224 GEN
Solar/Wind Harmer
3.103
965021AG1-366 GEN
Solar/Wind Harmer
1.478
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270043AE2-236 GEN
Solar/Wind Harmer
2.692
970349AG2-230 GEN
Solar/Wind Harmer
6.22
270391AF1-285 GEN3
Solar/Wind Harmer
0.274
270535AF1-215 GEN1
Solar/Wind Harmer
0.005
274752CRETE EC ;2U
Adder
4.596
274753CRETE EC ;3U
Adder
4.596
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274724RIVER EC ;11
Adder
9.806
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
274802UNIV PARK;5U
Adder
3.182
274826FISK ;BP
Adder
5.966
274800UNIV PARK;3U
Adder
3.173
972038AH1-567 GEN2
Adder
0.199
276806AD2-047 C O1
Solar/Wind Harmer
2.148
970941AG2-585 GEN
Solar/Wind Harmer
4.739
274772LINCOLN ;3U
Adder
4.584
972228AH1-698 GEN2
Adder
2.007
274676JOLIET 29;8U
Adder
15.952
276897AD1-100 C
Solar/Wind Harmer
0.005
939351AE1-166 GEN
Solar/Wind Harmer
0
276893AG1-478 C
Solar/Wind Harmer
0.149
274729ELWOOD EC;1P
Adder
8.848
274730ELWOOD EC;6P
Adder
8.849
274734ELWOOD EC;8P
Adder
8.849
274736ELWOOD EC;9P
Adder
8.849
970707AG2-453 GEN
Solar/Wind Harmer
12.267
971617AH1-308 GEN
Solar/Wind Harmer
3.125
970513AG2-328 GEN
Solar/Wind Harmer
1.623
970517AG2-330 GEN
Solar/Wind Harmer
9.737
943121AE2-341 GEN
Solar/Wind Harmer
6.229
943591AF1-030 GEN
Solar/Wind Harmer
4.142
276694AA1-018 GEN2
Solar/Wind Harmer
0
944531AF1-118 GEN
Solar/Wind Harmer
16.565
274682WAUKEGAN ;7U
Adder
9.512
276805AD2-038 GEN
Solar/Wind Harmer
0.001
24755605MDL-5G
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.663
274872LEEDK;1U
Solar/Wind Harmer
0.134
276889AE2-281 GEN
Solar/Wind Harmer
0
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.388
274855GSG-6 ;RU
Solar/Wind Harmer
0.133
274850MENDOTA H;RU
Solar/Wind Harmer
0.043
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.065
959091AF2-200 GEN
Solar/Wind Harmer
7.251
970571AG2-364 GEN
Solar/Wind Harmer
7.226
972236AH1-702 GEN2
Adder
1.135
270377AD1-106 GEN
Solar/Wind Harmer
1.364
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
4.772
274767LEE CO EC;8U
Adder
0.229
276157O29GEN1
Solar/Wind Harmer
0.575
274878BISHOP HL;2U
Solar/Wind Harmer
0.119
942111AE2-223 GEN
Solar/Wind Harmer
1.148
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
5.278
274853TWINGROVE;U1
Solar/Wind Harmer
0.001
965091AG1-374 GEN
Solar/Wind Harmer
10.488
959611AF2-252 GEN
Solar/Wind Harmer
1.165
965931AG1-462 GEN
Solar/Wind Harmer
8.873
247642Z2-115 C
Solar/Wind Harmer
0.002
970289AG2-191 GEN
Solar/Wind Harmer
0.379
970291AG2-192 GEN
Solar/Wind Harmer
0.345
276686W4-005 GEN3
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
1.563
276668AB2-070 GEN1
Solar/Wind Harmer
0.123
946031AF1-268 GEN
Solar/Wind Harmer
3.219
276621W2-048 GEN
Solar/Wind Harmer
0.169
276838X2-022 GEN2
Solar/Wind Harmer
0.189
962511AG1-100 GEN
Solar/Wind Helper
0.361
203830AF1-094 GEN
Solar/Wind Helper
0.34
959441AF2-235 GEN
Solar/Wind Helper
0.154
254305AE2-115 C
Solar/Wind Helper
0.117
20334926Z1-069 C
Solar/Wind Helper
0.662
958821AF2-173 GEN
Solar/Wind Harmer
1.049
23888802TROY G4
50/50
2.643
24190002OREGON_ST1
50/50
2.928
24189802OREGON_CT1
50/50
2.221
241996AE2-282_GEN
Solar/Wind Harmer
0.007
971677AH1-339 GEN
Solar/Wind Harmer
0.714
970621AG2-405 GEN
Solar/Wind Harmer
1.043
970623AG2-406 GEN
Solar/Wind Harmer
0.966
270007AE1-245 C
Solar/Wind Harmer
0.001
246938BC-WTG3
Solar/Wind Harmer
0.178
246937BC-WTG2
Solar/Wind Harmer
0.199
961051AF2-396 GEN
Solar/Wind Harmer
9.419
961051AF2-396 GEN
Solar/Wind Harmer
6.28
957891AF2-083 GEN
Solar/Wind Harmer
0.001
247620Y3-023
Adder
0.301
270216AD2-079_GEN
Solar/Wind Harmer
0.001
970611AG2-400 GEN
Solar/Wind Harmer
4.433
970627AG2-408 GEN
Solar/Wind Harmer
1.33
270526AF1-158 GEN
Solar/Wind Harmer
0.005
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
5.205
965791AG1-447 GEN
Solar/Wind Harmer
3.817
270224U2-072_GEN2
Solar/Wind Harmer
0
270227U2-072_GEN3
Solar/Wind Harmer
0
270228U2-072_GEN4
Solar/Wind Harmer
0
270231U2-072_GEN5
Solar/Wind Harmer
0
274808UNIV PK N;4U
Adder
2.75
274803UNIV PARK;6U
Adder
3.182
942221AE2-234 GEN
Solar/Wind Harmer
0.019
274888KELLY CRK;1U
Solar/Wind Harmer
0.223
274887GEN-1.85
Solar/Wind Harmer
0.1
276843GEN-1.7
Solar/Wind Harmer
0.123
958011AF2-095 GEN
Solar/Wind Harmer
5.459
274770LINCOLN ;1U
Adder
4.584
274771LINCOLN ;2U
Adder
4.584
972259AH1-714 GEN
Adder
10.294
274674JOLIET 9 ;6U
Adder
8.288
970321AG2-212 GEN
Solar/Wind Harmer
1.623
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
958481AF2-142 GEN
Solar/Wind Harmer
5.572
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.503
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
971573AH1-285 GEN
Solar/Wind Harmer
0.69
274695ROCKY RD ;2P
Adder
5.891
274693ROCKY RD ;1P
Adder
5.833
274697ROCKY RD ;3P
Adder
1.6
274696ROCKY RD ;4P
Adder
6.03
274683WAUKEGAN ;8U
Adder
11.144
274683WAUKEGAN ;8U
Adder
9.394
958491AF2-143 GEN
Solar/Wind Harmer
5.526
962691AG1-118 GEN
Solar/Wind Harmer
11.015
274879MINONK ;1U
Solar/Wind Harmer
0.155
970921AG2-575 GEN
Solar/Wind Harmer
3.666
970921AG2-575 GEN
Solar/Wind Harmer
1.222
942991AE2-321 GEN
Solar/Wind Harmer
4.078
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
971333AH1-146 GEN
Solar/Wind Harmer
7.279
971335AH1-147 GEN
Solar/Wind Harmer
7.279
971341AH1-150 GEN
Solar/Wind Harmer
7.251
971343AH1-151 GEN
Solar/Wind Harmer
7.251
276691AA1-018 GEN1
Solar/Wind Harmer
0.45
274682WAUKEGAN ;7U
Adder
9.512
274828WAUKEGAN ;BP
Adder
5.841
276901AD2-066 C O1
Solar/Wind Harmer
0.004
939401AE1-172 GEN
Solar/Wind Harmer
2.747
962781AG1-127 GEN
Solar/Wind Harmer
3.489
24791305MDL-5G
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0.002
971997AH1-543 GEN
Solar/Wind Harmer
1.918
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
276861AD2-134 GEN
Solar/Wind Harmer
0.065
957471AF2-041 GEN
Solar/Wind Harmer
10.876
959081AF2-199 GEN
Solar/Wind Harmer
3.625
971067AG2-660 GEN
Solar/Wind Harmer
1.208
274822ROCKFORD ;11
Adder
10.179
970569AG2-363 GEN
Solar/Wind Harmer
10.839
972235AH1-702 GEN1
Adder
1.305
970819AG2-516 GEN
Solar/Wind Harmer
4.326
971475AH1-234 GEN
Solar/Wind Harmer
1.747
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
4.772
274766LEE CO EC;7U
Adder
4.716
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.001
965651AG1-433 GEN
Solar/Wind Harmer
1.047
276158O29GEN2
Solar/Wind Harmer
0
274877BISHOP HL;1U
Solar/Wind Harmer
0.119
958861AF2-177 GEN
Solar/Wind Harmer
1.533
276726Z2-087_GEN
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
4.946
274854TWINGROVE;U2
Solar/Wind Harmer
0.001
945371AF1-202 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
8.165
970291AG2-192 GEN
Solar/Wind Harmer
0.448
972175AH1-670 GEN
Solar/Wind Harmer
2.841
247536S-71 GEN
Solar/Wind Harmer
0.138
270032AE2-172
Solar/Wind Harmer
2.283
274880W4-005 GEN4
Solar/Wind Harmer
0
963831AG1-236 GEN
Solar/Wind Harmer
1.315
276903AD2-071 C
Solar/Wind Harmer
3.766
970825AG2-519 GEN
Solar/Wind Harmer
1.195
276615X2-022 GEN
Solar/Wind Harmer
0.035
241885AC2-103 GEN1
Solar/Wind Helper
7.083
241807AE2-176_GEN
Solar/Wind Helper
1.701
961971AG1-040 GEN
Solar/Wind Helper
0.352
203835AF1-098 GEN
Solar/Wind Helper
1.388
203860AG1-193 C
Solar/Wind Helper
0.156
241966AE1-183 GEN
Solar/Wind Helper
0.136
254303AC2-168 GEN
Solar/Wind Helper
0.079
203954AE2-126 C
Solar/Wind Helper
0.223
274856ECOGROVE ;U1
Solar/Wind Harmer
0.085
276611AD2-172 GEN
Solar/Wind Harmer
0.001
971231AH1-075 GEN
Solar/Wind Harmer
0.412
938861AE1-114 GEN
Solar/Wind Harmer
2.033
274764LEE CO EC;5U
Adder
4.784
274765LEE CO EC;6U
Adder
4.784
274762LEE CO EC;3U
Adder
4.772
274763LEE CO EC;4U
Adder
4.727
966841AG1-555 GEN
Solar/Wind Harmer
0.405
276603SUBLETTE C
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.239
960971AF2-388 GEN
Solar/Wind Harmer
2.094
274851PROVIDENC;RU
Solar/Wind Harmer
0
274849CRESCENT ;1U
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.14
276646AC1-214 GEN2
Solar/Wind Harmer
0.14
276741O09 GEN1
Solar/Wind Harmer
0.127
276708O09 GEN2
Solar/Wind Harmer
0.127
276782AC1-033 GEN
Solar/Wind Harmer
0.001
270201AC2-176 GEN
Solar/Wind Harmer
0.001
960611AF2-352 GEN
Solar/Wind Harmer
1.165
964611AG1-324 GEN
Solar/Wind Harmer
0.262
270599AE1-208 GEN
Solar/Wind Harmer
3.195
270031AE2-169
Solar/Wind Harmer
1.917
970241AG2-163 GEN
Solar/Wind Harmer
2.013
253378AE2-206_GEN
Solar/Wind Harmer
0.002
276820AF1-078_GEN
Solar/Wind Harmer
0.001
970329AG2-216 GEN
Solar/Wind Harmer
1.487
971613AH1-306 GEN
Solar/Wind Harmer
1.644
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
960441AF2-335 GEN
Solar/Wind Harmer
3.372
970825AG2-519 GEN
Solar/Wind Harmer
3.73
970883AG2-550 GEN
Solar/Wind Harmer
3.346
970885AG2-551 GEN
Solar/Wind Harmer
1.115
203947AF1-006 C
Solar/Wind Helper
0.402
203980AG1-197 GEN
Solar/Wind Helper
0.262
203979AG1-198 GEN
Solar/Wind Helper
0.204
241967AE2-285_GEN
Solar/Wind Helper
0.354
241801AE1-079 GEN
Solar/Wind Helper
0.138
241985AE1-237 GEN
Solar/Wind Helper
0.137
962101AG1-054 GEN
Solar/Wind Helper
0.34
946381AF1-302 GEN
Solar/Wind Helper
0.108
238217AF1-153 C O1
Solar/Wind Helper
0.114
274675JOLIET 29;7U
Adder
15.952
274731ELWOOD EC;2P
Adder
8.848
274733ELWOOD EC;3P
Adder
8.848
274735ELWOOD EC;4P
Adder
8.848
274728ELWOOD EC;5P
Adder
8.849
270024AE2-089 GEN
Solar/Wind Harmer
0.004
970833AG2-524 GEN
Solar/Wind Harmer
4.112
970833AG2-524 GEN
Solar/Wind Harmer
2.741
274746AC1-111 G10
Adder
2.978
274744AC1-111 GEN8
Adder
2.978
276868AE1-113 GEN
Solar/Wind Harmer
0.736
276882AE2-255 GEN
Solar/Wind Harmer
0.429
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
24729505KEY G4
Adder
3.405
971177AH1-047 GEN
Solar/Wind Harmer
2.252
971411AH1-196 GEN
Solar/Wind Harmer
5.463
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
1.419
971171AH1-044 GEN
Solar/Wind Harmer
7.251
274823ROCKFORD ;21
Adder
10.105
926823AC1-168 GEN
Solar/Wind Harmer
0.613
970169AG2-114 GEN
Solar/Wind Harmer
3.606
276612AE2-035 GEN
Solar/Wind Harmer
0.001
971681AH1-341 GEN
Solar/Wind Harmer
5.777
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
24387005FR-3G C
Solar/Wind Harmer
0.001
961011AF2-392 GEN
Solar/Wind Harmer
2.09
957751AF2-069 GEN
Solar/Wind Harmer
0.117
965101AG1-375 GEN
Solar/Wind Harmer
3.538
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
276655WTG1_EQ
Solar/Wind Harmer
0.001
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.709
941731AE2-173 GEN
Solar/Wind Harmer
2.944
963841AG1-237 GEN
Solar/Wind Harmer
1.521
946321AF1-296 GEN
Solar/Wind Harmer
1.955
971609AH1-304 GEN
Solar/Wind Harmer
0.569
945581AF1-223 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.655
270594AE1-207 GEN
Solar/Wind Harmer
3.835
276785W4-005 GEN1
Solar/Wind Harmer
0
276174W4-005 GEN2
Solar/Wind Harmer
0
276849AB2-070 GEN2
Solar/Wind Harmer
0.123
276848AB2-070 GEN3
Solar/Wind Harmer
0.123
970115AG2-085 GEN
Solar/Wind Harmer
1.349
270543AE2-219 C
Solar/Wind Harmer
0.002
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0
241886AC2-103 GEN2
Solar/Wind Helper
7.083
241982AE2-343 S C
Solar/Wind Helper
0.123
254304AE2-114 C
Solar/Wind Helper
0.117
203846AF2-130 C
Solar/Wind Helper
0.257
241997AF1-093 GEN
Solar/Wind Helper
0.136
203804AE2-113_GEN
Solar/Wind Helper
0.892
990142J1224
External Queue
15.35684871673584
990527J1329
External Queue
2.100800037384033
991177J1571 G
External Queue
18.513126373291016
991182J1586 G
External Queue
28.404245376586914
NYPJM->LTFIMP_NY
CLTF
2.006
LGEELTFEXP_LGEE->PJM
CLTF
2.487
WECLTFEXP_WEC->PJM
CLTF
1.978
AG2-052LTFEXP_AG2-052->PJM
LTF
0.127
AH1-155LTFEXP_AH1-155->PJM
LTF
0.19
LAGNLTFEXP_LAGN->PJM
CLTF
6.243
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.59
TVALTFEXP_TVA->PJM
CLTF
2.868
CBM West 1LTFEXP_CBM-W1->PJM
CBM
107.191
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.28
MECLTFEXP_MEC->PJM
CLTF
7.783
SIGELTFEXP_SIGE->PJM
CLTF
0.206
CPLELTFEXP_CPLE->PJM
CLTF
0.787
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.86

Details for 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:121.78 %
Rating:1737.0 MVA
Rating Type:B
MVA to Mitigate:2115.3
MW Contribution:2.43
Bus #Bus NameTypeMW Contribution
960861AF2-377 GEN
50/50
2.449
970521AG2-332 GEN
50/50
11.057
24639705ELKHART HY
50/50
0.153
270143AC1-141 CT2_
50/50
2.055
24344105CKG2
50/50
6.288
24307105BERRINSP G
50/50
0.018
965011AG1-365 GEN
Solar/Wind Harmer
13.913
270063AE2-323 C
Solar/Wind Harmer
0.006
247521TR3_G114
Solar/Wind Harmer
0.268
270246TR4_N_V150
Solar/Wind Harmer
0.047
944231AF1-091 GEN
Solar/Wind Harmer
1.894
24695305TIMB G C
Solar/Wind Harmer
0.002
965651AG1-433 GEN
Solar/Wind Harmer
1.883
958861AF2-177 GEN
Solar/Wind Harmer
2.703
945111AF1-176 GEN
Solar/Wind Harmer
10.846
270505AE1-170 C O1
Solar/Wind Harmer
6.228
945371AF1-202 GEN
Solar/Wind Harmer
0
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.049
970245AG2-165 GEN
Solar/Wind Harmer
2.372
970373AG2-245 GEN
Solar/Wind Harmer
11.463
274751CRETE EC ;1U
Adder
6.419
274754CRETE EC ;4U
Adder
6.419
274723RIVER EC ;12
Adder
13.914
274812UNIV PK N;8U
Adder
3.858
276164X3-005 C
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0.004
274773LINCOLN ;4U
Adder
6.474
274774LINCOLN ;5U
Adder
6.474
274801UNIV PARK;4U
Adder
4.433
276776AD2-060 GEN
Solar/Wind Harmer
0.553
970615AG2-402 GEN
50/50
4.638
24729405KEY G3
50/50
0.376
24729305KEY G2
50/50
0.369
24729205KEY G1
50/50
0.368
247620Y3-023
50/50
0.473
270102X2-052 ST
50/50
1.304
270100X2-052 CT1
50/50
1.202
270101X2-052 CT2
50/50
1.202
970611AG2-400 GEN
Solar/Wind Harmer
13.913
970627AG2-408 GEN
Solar/Wind Harmer
4.174
942221AE2-234 GEN
Solar/Wind Harmer
0.035
944541AF1-119 GEN
Solar/Wind Harmer
0.43
960971AF2-388 GEN
Solar/Wind Harmer
3.767
270216AD2-079_GEN
Solar/Wind Harmer
0.001
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
11.858
961051AF2-396 GEN
Solar/Wind Harmer
7.905
270526AF1-158 GEN
Solar/Wind Harmer
0.007
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
7.075
965791AG1-447 GEN
Solar/Wind Harmer
5.189
270599AE1-208 GEN
Solar/Wind Harmer
5.131
270031AE2-169
Solar/Wind Harmer
3.079
970321AG2-212 GEN
Solar/Wind Harmer
2.372
274808UNIV PK N;4U
Adder
3.841
970583AG2-370 GEN
50/50
2.859
960851AF2-376 GEN
50/50
2.155
24641605TWIN BRNCH
50/50
0.016
270142AC1-141 CT1_
50/50
2.055
24642205MAYFLWER
50/50
0.571
944961AF1-161 GEN
50/50
2.434
962601AG1-109 GEN
50/50
2.434
24344005CKG1
50/50
5.289
959331AF2-224 GEN
Solar/Wind Harmer
9.739
965021AG1-366 GEN
Solar/Wind Harmer
4.638
970031AG2-029 GEN
Solar/Wind Harmer
5.561
270043AE2-236 GEN
Solar/Wind Harmer
5.288
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.047
944531AF1-118 GEN
Solar/Wind Harmer
32.162
971617AH1-308 GEN
Solar/Wind Harmer
5.291
247643Z2-116 C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
4.927
970349AG2-230 GEN
Solar/Wind Harmer
8.913
24441205WTRV SLR C
Solar/Wind Harmer
0
970513AG2-328 GEN
Solar/Wind Harmer
2.372
970517AG2-330 GEN
Solar/Wind Harmer
14.231
274752CRETE EC ;2U
Adder
6.419
274753CRETE EC ;3U
Adder
6.419
274724RIVER EC ;11
Adder
13.745
247604X1-042
Adder
0.322
270535AF1-215 GEN1
Solar/Wind Harmer
0.007
274772LINCOLN ;3U
Adder
6.474
274802UNIV PARK;5U
Adder
4.445
274826FISK ;BP
Adder
8.338
274800UNIV PARK;3U
Adder
4.433
972038AH1-567 GEN2
Adder
0.277
276806AD2-047 C O1
Solar/Wind Harmer
3.002
970941AG2-585 GEN
Solar/Wind Harmer
6.622
964401AG1-302 GEN
Solar/Wind Harmer
0.001
972228AH1-698 GEN2
Adder
2.805
970707AG2-453 GEN
Solar/Wind Harmer
17.2
276897AD1-100 C
Solar/Wind Harmer
0.007
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
22.239
276893AG1-478 C
Solar/Wind Harmer
0.207
274729ELWOOD EC;1P
Adder
12.325
274730ELWOOD EC;6P
Adder
12.325
274734ELWOOD EC;8P
Adder
12.325
274736ELWOOD EC;9P
Adder
12.325
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
943121AE2-341 GEN
Solar/Wind Harmer
8.672
943591AF1-030 GEN
Solar/Wind Harmer
5.767
247642Z2-115 C
Solar/Wind Harmer
0.002
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
13.17
970289AG2-191 GEN
Solar/Wind Harmer
0.562
970291AG2-192 GEN
Solar/Wind Harmer
0.511
958821AF2-173 GEN
Solar/Wind Harmer
7.111
270004AE1-209 GEN
Solar/Wind Harmer
1.101
276805AD2-038 GEN
Solar/Wind Harmer
0.001
274872LEEDK;1U
Solar/Wind Harmer
0.185
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.534
274855GSG-6 ;RU
Solar/Wind Harmer
0.184
274850MENDOTA H;RU
Solar/Wind Harmer
0.059
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.09
276889AE2-281 GEN
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
4.985
959091AF2-200 GEN
Solar/Wind Harmer
9.953
972236AH1-702 GEN2
Adder
1.555
970571AG2-364 GEN
Solar/Wind Harmer
9.859
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
6.505
274767LEE CO EC;8U
Adder
6.428
946031AF1-268 GEN
Solar/Wind Harmer
4.635
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
7.294
276157O29GEN1
Solar/Wind Harmer
0.779
274878BISHOP HL;2U
Solar/Wind Harmer
0.161
942111AE2-223 GEN
Solar/Wind Harmer
1.543
965931AG1-462 GEN
Solar/Wind Harmer
11.906
274853TWINGROVE;U1
Solar/Wind Harmer
0.002
965091AG1-374 GEN
Solar/Wind Harmer
14.002
959611AF2-252 GEN
Solar/Wind Harmer
1.556
270437AC2-090 C
Solar/Wind Harmer
0.002
276686W4-005 GEN3
Solar/Wind Harmer
0.001
276668AB2-070 GEN1
Solar/Wind Harmer
0.161
971993AH1-541 GEN
Solar/Wind Harmer
2.041
276621W2-048 GEN
Solar/Wind Harmer
0.219
276838X2-022 GEN2
Solar/Wind Harmer
0.245
942481AE2-261 GEN
Solar/Wind Harmer
12.535
970193AG2-126 GEN
Solar/Wind Harmer
6.087
270404AC1-167 GEN
Solar/Wind Harmer
0.002
270258AD1-119 GEN
Solar/Wind Harmer
0.001
24728705AND G3
Adder
4.445
24728505AND G1
Adder
2.125
270356AE2-297 GEN
Solar/Wind Harmer
0.005
970243AG2-164 GEN
Solar/Wind Harmer
1.9
970519AG2-331 GEN
Solar/Wind Harmer
8.446
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
6.867
941551AE2-152 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
23.063
274674JOLIET 9 ;6U
Adder
11.55
274732ELWOOD EC;7P
Adder
12.325
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
6.476
274745AC1-111 GEN9
Adder
4.142
276691AA1-018 GEN1
Solar/Wind Harmer
0.622
274682WAUKEGAN ;7U
Adder
13.17
970291AG2-192 GEN
Solar/Wind Harmer
0.664
274828WAUKEGAN ;BP
Adder
8.084
270005AE1-210 C O1
Solar/Wind Harmer
1.101
965031AG1-367 GEN
Solar/Wind Harmer
5.08
962781AG1-127 GEN
Solar/Wind Harmer
4.819
939401AE1-172 GEN
Solar/Wind Harmer
3.786
276901AD2-066 C O1
Solar/Wind Harmer
0.005
270032AE2-172
Solar/Wind Harmer
3.37
274872LEEDK;1U
Solar/Wind Harmer
0.003
971997AH1-543 GEN
Solar/Wind Harmer
2.638
276861AD2-134 GEN
Solar/Wind Harmer
0.09
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
24791305MDL-5G
Solar/Wind Harmer
0.001
957471AF2-041 GEN
Solar/Wind Harmer
14.929
959081AF2-199 GEN
Solar/Wind Harmer
4.976
971067AG2-660 GEN
Solar/Wind Harmer
1.659
274822ROCKFORD ;11
Adder
13.956
970825AG2-519 GEN
Solar/Wind Harmer
1.759
972235AH1-702 GEN1
Adder
1.788
970819AG2-516 GEN
Solar/Wind Harmer
5.921
970569AG2-363 GEN
Solar/Wind Harmer
14.789
971475AH1-234 GEN
Solar/Wind Harmer
2.388
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
6.505
274766LEE CO EC;7U
Adder
6.428
276903AD2-071 C
Solar/Wind Harmer
5.417
276158O29GEN2
Solar/Wind Harmer
0.001
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.002
274877BISHOP HL;1U
Solar/Wind Harmer
0.161
276726Z2-087_GEN
Solar/Wind Harmer
0.002
939741AE1-205 GEN
Solar/Wind Harmer
6.647
274854TWINGROVE;U2
Solar/Wind Harmer
0.002
972175AH1-670 GEN
Solar/Wind Harmer
3.748
963741AG1-226 GEN
Solar/Wind Harmer
10.683
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
3.3
247536S-71 GEN
Solar/Wind Harmer
0.179
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
1.713
276615X2-022 GEN
Solar/Wind Harmer
0.046
965911AG1-460 GEN
Solar/Wind Harmer
0.838
24728605AND G2
Adder
2.125
970773AG2-487 GEN
Solar/Wind Harmer
0.635
270445AC2-157 GEN2
Solar/Wind Harmer
0.002
970333AG2-219 GEN
Solar/Wind Harmer
2.323
246936BC-WTG1
Solar/Wind Helper
10.843
270462AD2-086
Solar/Wind Helper
3.651
270223U2-072_GEN1
Solar/Wind Helper
0.855
270578AF1-285 GEN2
Solar/Wind Helper
0.579
270391AF1-285 GEN3
Solar/Wind Helper
0.579
247522W1-056 GEN
Solar/Wind Helper
1.138
960841AF2-375 GEN
Solar/Wind Helper
1.139
270349AD2-093_GEN
Solar/Wind Helper
0.817
970699AG2-449 GEN
Solar/Wind Harmer
0.812
270485AE1-090_GEN
Solar/Wind Helper
0.318
942871AE2-306 GEN
Solar/Wind Helper
0.434
270541AE2-072 C
Solar/Wind Helper
0.891
274770LINCOLN ;1U
Adder
6.474
274771LINCOLN ;2U
Adder
6.474
274803UNIV PARK;6U
Adder
4.445
274888KELLY CRK;1U
Solar/Wind Harmer
0.311
274887GEN-1.85
Solar/Wind Harmer
0.139
276843GEN-1.7
Solar/Wind Harmer
0.171
958011AF2-095 GEN
Solar/Wind Harmer
7.629
972259AH1-714 GEN
Adder
14.402
274674JOLIET 9 ;6U
Adder
11.55
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
971573AH1-285 GEN
Solar/Wind Harmer
0.959
958481AF2-142 GEN
Solar/Wind Harmer
7.707
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.695
274695ROCKY RD ;2P
Adder
8.163
274693ROCKY RD ;1P
Adder
8.082
274697ROCKY RD ;3P
Adder
2.217
274696ROCKY RD ;4P
Adder
8.355
274683WAUKEGAN ;8U
Adder
15.422
274683WAUKEGAN ;8U
Adder
13
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
962691AG1-118 GEN
Solar/Wind Harmer
15.227
958491AF2-143 GEN
Solar/Wind Harmer
7.614
970921AG2-575 GEN
Solar/Wind Harmer
5.064
970921AG2-575 GEN
Solar/Wind Harmer
1.688
971613AH1-306 GEN
Solar/Wind Harmer
2.426
274879MINONK ;1U
Solar/Wind Harmer
0.213
942991AE2-321 GEN
Solar/Wind Harmer
5.619
971333AH1-146 GEN
Solar/Wind Harmer
10.011
971335AH1-147 GEN
Solar/Wind Harmer
10.011
960441AF2-335 GEN
Solar/Wind Harmer
4.991
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
971341AH1-150 GEN
Solar/Wind Harmer
9.953
971343AH1-151 GEN
Solar/Wind Harmer
9.953
970825AG2-519 GEN
Solar/Wind Harmer
5.49
274856ECOGROVE ;U1
Solar/Wind Harmer
0.116
276611AD2-172 GEN
Solar/Wind Harmer
0.001
938861AE1-114 GEN
Solar/Wind Harmer
2.774
274764LEE CO EC;5U
Adder
6.52
274765LEE CO EC;6U
Adder
6.52
274762LEE CO EC;3U
Adder
6.505
274763LEE CO EC;4U
Adder
6.443
276603SUBLETTE C
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.365
270201AC2-176 GEN
Solar/Wind Harmer
0.001
972267AH1-718 GEN
Adder
2.883
276741O09 GEN1
Solar/Wind Harmer
0.172
276708O09 GEN2
Solar/Wind Harmer
0.172
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.189
276646AC1-214 GEN2
Solar/Wind Harmer
0.189
966841AG1-555 GEN
Solar/Wind Harmer
0.542
276782AC1-033 GEN
Solar/Wind Harmer
0.001
247621Y3-024
Adder
0.165
960611AF2-352 GEN
Solar/Wind Harmer
1.556
970241AG2-163 GEN
Solar/Wind Harmer
2.633
24379505HDWTR1G C
Solar/Wind Harmer
0.001
270209AC1-174_GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
270383AD1-128 GEN
Solar/Wind Harmer
0.003
276916AD2-100_GEN
Solar/Wind Harmer
8.729
276911AD2-131_GEN
Solar/Wind Harmer
0.575
970883AG2-550 GEN
Solar/Wind Harmer
4.063
970885AG2-551 GEN
Solar/Wind Harmer
1.354
945391AF1-204 GEN
Solar/Wind Harmer
4.312
970623AG2-406 GEN
Solar/Wind Harmer
0.709
270444AC2-157 GEN1
Solar/Wind Harmer
0.002
971587AH1-292 GEN
Solar/Wind Harmer
2.538
270007AE1-245 C
Solar/Wind Harmer
0.001
970239AG2-162 GEN
Solar/Wind Harmer
0.812
246938BC-WTG3
Solar/Wind Helper
11.029
246937BC-WTG2
Solar/Wind Helper
10.843
270224U2-072_GEN2
Solar/Wind Helper
0.855
270227U2-072_GEN3
Solar/Wind Helper
0.855
270228U2-072_GEN4
Solar/Wind Helper
0.855
270231U2-072_GEN5
Solar/Wind Helper
0.855
270471AD2-092_GEN
Solar/Wind Helper
0.817
253378AE2-206_GEN
Solar/Wind Helper
0.657
276820AF1-078_GEN
Solar/Wind Helper
0.307
241960AC2-195 GEN
Solar/Wind Helper
0.657
971599AH1-298 GEN
50/50
10.521
24729505KEY G4
50/50
6.883
24653605MOTTVILLE
50/50
0.004
270144AC1-141 ST1_
50/50
1.82
24643105BUCHANAN
50/50
0.011
963791AG1-232 GEN
Solar/Wind Harmer
11.809
965041AG1-368 GEN
Solar/Wind Harmer
8.577
270071AF1-092 GEN
Solar/Wind Harmer
14.687
965051AG1-369 GEN
Solar/Wind Harmer
3.667
270024AE2-089 GEN
Solar/Wind Harmer
0.007
965101AG1-375 GEN
Solar/Wind Harmer
6.239
971771AH1-392 GEN
Solar/Wind Harmer
5.998
971347AH1-153 GEN
Solar/Wind Harmer
8.913
971619AH1-309 GEN
Solar/Wind Harmer
2.669
945581AF1-223 GEN
Solar/Wind Harmer
0
971769AH1-391 GEN
Solar/Wind Harmer
6.451
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971609AH1-304 GEN
Solar/Wind Harmer
0.914
274814UNIV PK N;0U
Adder
3.891
274807UNIV PK N;3U
Adder
3.883
274805UNIV PK N;1U
Adder
3.866
274811UNIV PK N;7U
Adder
3.858
270536AF1-215 GEN2
Solar/Wind Harmer
0.007
274775LINCOLN ;6U
Adder
6.474
274776LINCOLN ;7U
Adder
6.474
274777LINCOLN ;8U
Adder
6.474
972037AH1-567 GEN1
Adder
0.14
274827FISK ;RP
Adder
5.909
960591AF2-350 GEN
Solar/Wind Harmer
5.298
972227AH1-698 GEN1
Adder
1.975
274687WILL CNTY;4U
Adder
21.05
274687WILL CNTY;4U
Adder
21.05
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274675JOLIET 29;7U
Adder
23.063
274675JOLIET 29;7U
Adder
22.239
274731ELWOOD EC;2P
Adder
12.325
274733ELWOOD EC;3P
Adder
12.325
274735ELWOOD EC;4P
Adder
12.325
274728ELWOOD EC;5P
Adder
12.325
970833AG2-524 GEN
Solar/Wind Harmer
5.728
970833AG2-524 GEN
Solar/Wind Harmer
3.819
971611AH1-305 GEN
Solar/Wind Harmer
3.084
274746AC1-111 G10
Adder
4.142
274744AC1-111 GEN8
Adder
4.142
970289AG2-191 GEN
Solar/Wind Harmer
0.971
270594AE1-207 GEN
Solar/Wind Harmer
5.661
276868AE1-113 GEN
Solar/Wind Harmer
1.012
276882AE2-255 GEN
Solar/Wind Harmer
0.59
971177AH1-047 GEN
Solar/Wind Harmer
3.102
971411AH1-196 GEN
Solar/Wind Harmer
7.515
971675AH1-338 GEN
Solar/Wind Harmer
1.952
970115AG2-085 GEN
Solar/Wind Harmer
1.996
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
9.953
274823ROCKFORD ;21
Adder
13.855
276612AE2-035 GEN
Solar/Wind Harmer
0.001
926823AC1-168 GEN
Solar/Wind Harmer
0.837
970169AG2-114 GEN
Solar/Wind Harmer
4.915
971681AH1-341 GEN
Solar/Wind Harmer
7.885
971549AH1-272 GEN
Solar/Wind Harmer
10.103
961011AF2-392 GEN
Solar/Wind Harmer
2.842
957751AF2-069 GEN
Solar/Wind Harmer
0.159
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
276655WTG1_EQ
Solar/Wind Harmer
0.002
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
4.986
941731AE2-173 GEN
Solar/Wind Harmer
3.957
946321AF1-296 GEN
Solar/Wind Harmer
2.629
963841AG1-237 GEN
Solar/Wind Harmer
2.014
270240V3-007_GEN2
Solar/Wind Harmer
0.001
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.161
276848AB2-070 GEN3
Solar/Wind Harmer
0.16
270543AE2-219 C
Solar/Wind Harmer
0.002
944221AF1-090 GEN
Solar/Wind Harmer
2.367
971029AG2-637 GEN
Solar/Wind Harmer
5.468
971673AH1-337 GEN
Solar/Wind Harmer
2.273
247607V1-011 GEN
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Helper
8.571
270317AD1-130_GEN
Solar/Wind Helper
4.044
966831AG1-554 GEN
Solar/Wind Helper
0.856
270284AF1-227 GEN1
Solar/Wind Helper
1.824
270286AF1-227 GEN2
Solar/Wind Helper
0.669
270287AF1-227 GEN3
Solar/Wind Helper
0.669
270499AE1-146 GEN
Solar/Wind Helper
1.895
945641AF1-229 GEN
Solar/Wind Helper
0.904
944201AF1-088_MTX
Adder
57.673
957141AF2-008_MTX
Adder
8.943
990792J1392
External Queue
5.474584102630615
990497J1323
External Queue
1.5914489030838013
NYPJM->LTFIMP_NY
CLTF
1.126
LGEELTFEXP_LGEE->PJM
CLTF
1.931
WECLTFEXP_WEC->PJM
CLTF
2.707
AG2-052LTFEXP_AG2-052->PJM
LTF
0.175
AH1-155LTFEXP_AH1-155->PJM
LTF
0.263
LAGNLTFEXP_LAGN->PJM
CLTF
6.132
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.094
TVALTFEXP_TVA->PJM
CLTF
2.49
CBM West 1LTFEXP_CBM-W1->PJM
CBM
72.466
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.567
MECLTFEXP_MEC->PJM
CLTF
10.019
SIGELTFEXP_SIGE->PJM
CLTF
0.208
CBM West 2LTFEXP_CBM-W2->PJM
CBM
52.858

Details for 05CLOV17_XFL-05CLOVRD 345.0 kV Ckt 17 line l/o AEP_P1-3_#7421_05CLOVRD 765_14_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05CLOV17_XFL-05CLOVRD 345.0 kV Ckt 17 line
Contingency Name:
AEP_P1-3_#7421_05CLOVRD 765_14_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.66 %
Rating:2320.0 MVA
Rating Type:B
MVA to Mitigate:2474.48
MW Contribution:1.51
Bus #Bus NameTypeMW Contribution
970563AG2-360 GEN
50/50
26.913
24689505VACITY
50/50
3.172
943031AE2-326 GEN
Solar/Wind Harmer
3.913
962751AG1-124 GEN
Solar/Wind Harmer
6.207
960911AF2-382 GEN
Solar/Wind Harmer
4.08
971461AH1-227 GEN
Solar/Wind Harmer
2.688
972103AH1-617 GEN
Solar/Wind Harmer
9.714
270053AF1-130 C
Solar/Wind Harmer
1.017
972273AH1-721 GEN
Adder
50.38
970273AG2-179 GEN
Solar/Wind Harmer
2.497
339250AF1-203 GEN
Solar/Wind Harmer
0.001
971155AH1-034 GEN
Solar/Wind Harmer
4.743
962251AG1-071 GEN
Solar/Wind Harmer
2.526
24686205CER G4
Adder
4.732
24686405CER G5
Adder
4.713
960741AF2-365 GEN
Solar/Wind Harmer
1.981
966571AG1-526 GEN
Solar/Wind Harmer
8.7
970093AG2-073 GEN
Solar/Wind Harmer
3.862
270030AE2-140 GEN
Solar/Wind Harmer
7.67
3429391JKCT 9G
Adder
4.484
972167AH1-666 GEN
Solar/Wind Harmer
2.764
958171AF2-111 GEN
Solar/Wind Harmer
8.53
970243AG2-164 GEN
Solar/Wind Harmer
1.988
970519AG2-331 GEN
Solar/Wind Harmer
8.834
970699AG2-449 GEN
Solar/Wind Harmer
0.849
942481AE2-261 GEN
Solar/Wind Harmer
10.086
276621W2-048 GEN
Solar/Wind Harmer
0.169
276838X2-022 GEN2
Solar/Wind Harmer
0.188
970193AG2-126 GEN
Solar/Wind Harmer
4.996
276668AB2-070 GEN1
Solar/Wind Harmer
0.121
276686W4-005 GEN3
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
1.536
965931AG1-462 GEN
Solar/Wind Harmer
8.444
25196008MFTGT1
Adder
0.634
24728705AND G3
Adder
3.77
24728505AND G1
Adder
1.803
274853TWINGROVE;U1
Solar/Wind Harmer
0.001
965091AG1-374 GEN
Solar/Wind Harmer
9.836
959611AF2-252 GEN
Solar/Wind Harmer
1.093
274878BISHOP HL;2U
Solar/Wind Harmer
0.11
276157O29GEN1
Solar/Wind Harmer
0.529
942111AE2-223 GEN
Solar/Wind Harmer
1.06
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
4.35
274767LEE CO EC;8U
Adder
4.299
24721905FLATG4
Adder
9.459
972236AH1-702 GEN2
Adder
1.02
970571AG2-364 GEN
Solar/Wind Harmer
6.485
959091AF2-200 GEN
Solar/Wind Harmer
6.478
274855GSG-6 ;RU
Solar/Wind Harmer
0.119
274850MENDOTA H;RU
Solar/Wind Harmer
0.038
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.058
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.345
276889AE2-281 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0.118
270356AE2-297 GEN
Solar/Wind Harmer
0.004
276805AD2-038 GEN
Solar/Wind Harmer
0.001
252510AF1-249 C
Solar/Wind Harmer
0.025
25194608D.CRK4
Adder
0.756
274682WAUKEGAN ;7U
Adder
8.262
25196608WSDLE5
Adder
3.936
276694AA1-018 GEN2
Solar/Wind Harmer
0
943121AE2-341 GEN
Solar/Wind Harmer
5.354
943591AF1-030 GEN
Solar/Wind Harmer
3.56
24755605MDL-5G
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.188
276893AG1-478 C
Solar/Wind Harmer
0.126
24735205WLF2G2
50/50
5.209
24728305BUCHG2
Adder
3.631
971687AH1-348 GEN
Solar/Wind Harmer
0.521
971403AH1-188 GEN
Solar/Wind Harmer
6.41
971315AH1-136 GEN
Solar/Wind Harmer
0.889
24723205RIVRG3
Adder
11.619
970273AG2-179 GEN
Solar/Wind Harmer
1.456
270336AE1-100 GEN
Solar/Wind Harmer
0.002
962241AG1-070 GEN
Solar/Wind Harmer
2.203
964901AG1-354 GEN
Solar/Wind Harmer
6.057
24686105CER G3
Adder
4.757
24686505CER G6
Adder
4.751
971821AH1-427 GEN
Solar/Wind Harmer
3.952
3429241JKCT 3G
Adder
6.434
971565AH1-281 GEN
Solar/Wind Harmer
0.752
3429421JKCT 10G
Adder
4.484
958131AF2-107 GEN
Solar/Wind Harmer
2.005
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
339216AC1-074 GEN
Solar/Wind Harmer
0.098
970091AG2-072 GEN
Adder
38.082
945681AF1-233 GEN
Solar/Wind Harmer
6.522
270445AC2-157 GEN2
Solar/Wind Harmer
0.002
970333AG2-219 GEN
Solar/Wind Harmer
2.429
965911AG1-460 GEN
Solar/Wind Harmer
0.675
276615X2-022 GEN
Solar/Wind Harmer
0.035
963831AG1-236 GEN
Solar/Wind Harmer
1.299
274880W4-005 GEN4
Solar/Wind Harmer
0
972175AH1-670 GEN
Solar/Wind Harmer
2.731
25196008MFTGT1
Adder
0.655
24728605AND G2
Adder
1.803
274854TWINGROVE;U2
Solar/Wind Harmer
0.001
274877BISHOP HL;1U
Solar/Wind Harmer
0.11
276158O29GEN2
Solar/Wind Harmer
0
25196808ZIMRHP
Adder
35.531
276726Z2-087_GEN
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
4.568
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
4.35
274766LEE CO EC;7U
Adder
4.299
963741AG1-226 GEN
Solar/Wind Harmer
7.717
24721705FLATG2
Adder
9.459
971475AH1-234 GEN
Solar/Wind Harmer
1.579
970819AG2-516 GEN
Solar/Wind Harmer
3.899
972235AH1-702 GEN1
Adder
1.172
274822ROCKFORD ;11
Adder
9.123
970569AG2-363 GEN
Solar/Wind Harmer
9.728
252507AC2-088 GEN
Solar/Wind Harmer
0.147
957471AF2-041 GEN
Solar/Wind Harmer
9.717
959081AF2-199 GEN
Solar/Wind Harmer
3.239
971067AG2-660 GEN
Solar/Wind Harmer
1.08
276861AD2-134 GEN
Solar/Wind Harmer
0.058
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
274872LEEDK;1U
Solar/Wind Harmer
0.002
971997AH1-543 GEN
Solar/Wind Harmer
1.69
962781AG1-127 GEN
Solar/Wind Harmer
3.063
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.001
276901AD2-066 C O1
Solar/Wind Harmer
0.003
970773AG2-487 GEN
Solar/Wind Harmer
0.568
25194608D.CRK4
Adder
0.756
274828WAUKEGAN ;BP
Adder
5.081
274682WAUKEGAN ;7U
Adder
8.262
939401AE1-172 GEN
Solar/Wind Harmer
2.398
276691AA1-018 GEN1
Solar/Wind Harmer
0.387
274745AC1-111 GEN9
Adder
2.558
24791305MDL-5G
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
3.539
276776AD2-060 GEN
Solar/Wind Harmer
0.33
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
3.162
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
2.313
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
3.94
970291AG2-192 GEN
Solar/Wind Harmer
0.41
276164X3-005 C
Solar/Wind Harmer
0
270032AE2-172
Solar/Wind Harmer
2.098
270005AE1-210 C O1
Solar/Wind Harmer
0.68
965031AG1-367 GEN
Solar/Wind Harmer
3.137
970825AG2-519 GEN
Solar/Wind Harmer
1.113
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.07
958381AF2-132 GEN
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0.002
315616AA1-038_C
Solar/Wind Helper
1.807
3148013FISHERV
Solar/Wind Helper
0.286
316499AE2-029_GEN
Solar/Wind Helper
0.937
3132273ORANGE
Solar/Wind Helper
0.03
3147666LOUISA
Solar/Wind Helper
0.335
237061AD1-155 GEN
Solar/Wind Helper
0.025
316170AC1-121 GEN2
Solar/Wind Helper
0.204
316313AB2-026
Solar/Wind Helper
0.2
316258AE1-075 C
Solar/Wind Helper
0.18
316405AF2-144 C
Solar/Wind Helper
0.15
3146776BUCKING
Solar/Wind Helper
0.045
966881AG1-559 GEN
Solar/Wind Helper
0.168
316473AC1-191 GEN
Solar/Wind Helper
0.759
23583801GRNGAP
Solar/Wind Helper
2.125
238147AE2-230_GEN1
Solar/Wind Helper
0.213
238149AF1-291A_GEN
Solar/Wind Helper
0.061
971277AH1-098 GEN
Solar/Wind Harmer
2.312
24728205BUCHG1
Adder
3.631
971225AH1-072 GEN
Solar/Wind Harmer
1.048
971227AH1-073 GEN
Solar/Wind Harmer
1.048
944971AF1-162 GEN
Solar/Wind Harmer
4.505
24723005RIVRG1
Adder
11.619
24723105RIVRG2
Adder
11.619
966021AG1-471 GEN
Solar/Wind Harmer
2.291
971485AH1-239 GEN
Solar/Wind Harmer
3.379
339255AE2-071 GEN
Solar/Wind Harmer
-0.067
964781AG1-341 GEN
Solar/Wind Harmer
4.307
971081AG2-670 GEN
Solar/Wind Harmer
2.998
24685805CER G1
Adder
4.726
24685905CER G2
Adder
4.726
970653AG2-424 GEN
Solar/Wind Harmer
1.862
970653AG2-424 GEN
Solar/Wind Harmer
0.965
960161AF2-307 GEN
Solar/Wind Harmer
2.512
942891AE2-308 GEN
Solar/Wind Harmer
3.8
964571AG1-320 GEN
Solar/Wind Harmer
3.444
971125AH1-004 GEN
Solar/Wind Harmer
1.465
970107AG2-081 GEN
Solar/Wind Harmer
1.099
972043AH1-570 GEN
Solar/Wind Harmer
0.938
972045AH1-571 GEN
Solar/Wind Harmer
0.752
339221AD2-048_GEN
Solar/Wind Harmer
0.002
970235AG2-159 GEN
Solar/Wind Harmer
2.143
970235AG2-159 GEN
Solar/Wind Harmer
1.23
270444AC2-157 GEN1
Solar/Wind Harmer
0.002
971587AH1-292 GEN
Solar/Wind Harmer
2.506
970239AG2-162 GEN
Solar/Wind Harmer
0.849
276916AD2-100_GEN
Solar/Wind Harmer
7.098
276911AD2-131_GEN
Solar/Wind Harmer
0.468
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
945391AF1-204 GEN
Solar/Wind Harmer
3.539
270186AC1-089 GEN
Solar/Wind Harmer
0.002
960611AF2-352 GEN
Solar/Wind Harmer
1.093
276782AC1-033 GEN
Solar/Wind Harmer
0
276741O09 GEN1
Solar/Wind Harmer
0.117
276708O09 GEN2
Solar/Wind Harmer
0.117
972267AH1-718 GEN
Adder
1.953
274851PROVIDENC;RU
Solar/Wind Harmer
0
274849CRESCENT ;1U
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.128
276646AC1-214 GEN2
Solar/Wind Harmer
0.128
276603SUBLETTE C
Solar/Wind Harmer
0
274764LEE CO EC;5U
Adder
4.36
274765LEE CO EC;6U
Adder
4.36
274762LEE CO EC;3U
Adder
4.35
274763LEE CO EC;4U
Adder
4.309
970241AG2-163 GEN
Solar/Wind Harmer
1.902
938861AE1-114 GEN
Solar/Wind Harmer
1.846
274856ECOGROVE ;U1
Solar/Wind Harmer
0.077
276611AD2-172 GEN
Solar/Wind Harmer
0.001
252509AD1-136 GEN
Solar/Wind Harmer
0.016
971341AH1-150 GEN
Solar/Wind Harmer
6.478
971343AH1-151 GEN
Solar/Wind Harmer
6.478
971333AH1-146 GEN
Solar/Wind Harmer
6.465
971335AH1-147 GEN
Solar/Wind Harmer
6.465
962581AG1-107 GEN
Solar/Wind Harmer
0.001
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
942991AE2-321 GEN
Solar/Wind Harmer
3.603
970921AG2-575 GEN
Solar/Wind Harmer
3.218
970921AG2-575 GEN
Solar/Wind Harmer
1.073
274879MINONK ;1U
Solar/Wind Harmer
0.136
966841AG1-555 GEN
Solar/Wind Harmer
0.364
962691AG1-118 GEN
Solar/Wind Harmer
9.647
958491AF2-143 GEN
Solar/Wind Harmer
4.817
252519AF1-045_GEN
Solar/Wind Harmer
2.794
252516AE2-318_GEN
Solar/Wind Harmer
2.478
25183208HLCRTG
Solar/Wind Harmer
0.005
25194408D.CRK1
Adder
3.478
25194508D.CRK3
Adder
0.65
274683WAUKEGAN ;8U
Adder
9.693
274683WAUKEGAN ;8U
Adder
8.17
274696ROCKY RD ;4P
Adder
5.238
274695ROCKY RD ;2P
Adder
5.117
274693ROCKY RD ;1P
Adder
5.067
274697ROCKY RD ;3P
Adder
1.39
971573AH1-285 GEN
Solar/Wind Harmer
0.596
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.433
958481AF2-142 GEN
Solar/Wind Harmer
4.797
24728805RICHG1
Adder
1.728
24728905RICHG2
Adder
1.728
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
274888KELLY CRK;1U
Solar/Wind Harmer
0.186
274887GEN-1.85
Solar/Wind Harmer
0.083
276843GEN-1.7
Solar/Wind Harmer
0.102
958011AF2-095 GEN
Solar/Wind Harmer
4.555
24735105WLF2G1
50/50
5.209
24734705WLF1G3
50/50
5.198
24734805WLF1G4
50/50
5.198
24734905WLF1G5
50/50
5.198
966391AG1-508 GEN
Solar/Wind Harmer
0.87
971981AH1-535 GEN
Solar/Wind Harmer
3.673
971313AH1-133 GEN
Solar/Wind Harmer
5.384
970281AG2-184 GEN
Solar/Wind Harmer
10.199
972143AH1-644 GEN
Solar/Wind Harmer
5.262
270399AC1-101 GEN
Solar/Wind Harmer
1.445
270400AC1-102 GEN
Solar/Wind Harmer
1.445
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
965401AG1-405 GEN
Solar/Wind Harmer
2.362
965411AG1-406 GEN
Solar/Wind Harmer
1.519
972203AH1-686 GEN
Adder
1.34
339211AE2-254 GEN
Solar/Wind Harmer
0.002
970455AG2-298 GEN
Solar/Wind Harmer
2.533
3429211JKCT 2G
Adder
6.351
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
972163AH1-664 GEN
Solar/Wind Harmer
3.866
972165AH1-665 GEN
Solar/Wind Harmer
3.096
944221AF1-090 GEN
Solar/Wind Harmer
1.996
276849AB2-070 GEN2
Solar/Wind Harmer
0.121
276848AB2-070 GEN3
Solar/Wind Harmer
0.121
276785W4-005 GEN1
Solar/Wind Harmer
0
276174W4-005 GEN2
Solar/Wind Harmer
0
946321AF1-296 GEN
Solar/Wind Harmer
1.851
25196108MFTGT2
Adder
0.722
25196108MFTGT2
Adder
0.67
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
961011AF2-392 GEN
Solar/Wind Harmer
1.918
957751AF2-069 GEN
Solar/Wind Harmer
0.108
276655WTG1_EQ
Solar/Wind Harmer
0.001
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.426
941731AE2-173 GEN
Solar/Wind Harmer
2.719
971681AH1-341 GEN
Solar/Wind Harmer
5.244
270367AC2-061_GEN
Solar/Wind Harmer
0.003
276612AE2-035 GEN
Solar/Wind Harmer
0.001
274823ROCKFORD ;21
Adder
9.057
926823AC1-168 GEN
Solar/Wind Harmer
0.551
963841AG1-237 GEN
Solar/Wind Harmer
1.404
971171AH1-044 GEN
Solar/Wind Harmer
6.478
970169AG2-114 GEN
Solar/Wind Harmer
3.233
971675AH1-338 GEN
Solar/Wind Harmer
1.26
971411AH1-196 GEN
Solar/Wind Harmer
4.847
971177AH1-047 GEN
Solar/Wind Harmer
1.99
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
276868AE1-113 GEN
Solar/Wind Harmer
0.646
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
24387005FR-3G C
Solar/Wind Harmer
0.001
276882AE2-255 GEN
Solar/Wind Harmer
0.376
252524AE2-267 GEN
Solar/Wind Harmer
0.001
25196408WSDLE3
Adder
4.052
25196308WSDLE2
Adder
4.017
25196208WSDLE1
Adder
4.006
25196708WSDLE6
Adder
3.996
25196508WSDLE4
Adder
3.896
274746AC1-111 G10
Adder
2.558
274744AC1-111 GEN8
Adder
2.558
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0
270181AB1-006 GEN2
Solar/Wind Harmer
0
970833AG2-524 GEN
Solar/Wind Harmer
3.501
970833AG2-524 GEN
Solar/Wind Harmer
2.334
274731ELWOOD EC;2P
Adder
7.487
274733ELWOOD EC;3P
Adder
6.938
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0
960591AF2-350 GEN
Solar/Wind Harmer
3.163
270240V3-007_GEN2
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
1.877
970289AG2-191 GEN
Solar/Wind Harmer
0.599
971985AH1-537 GEN
Solar/Wind Harmer
0.937
270594AE1-207 GEN
Solar/Wind Harmer
3.524
958391AF2-133 GEN
Solar/Wind Harmer
0
970115AG2-085 GEN
Solar/Wind Harmer
1.255
270536AF1-215 GEN2
Solar/Wind Harmer
0.004
971609AH1-304 GEN
Solar/Wind Harmer
0.508
971673AH1-337 GEN
Solar/Wind Harmer
2.018
3148463FAIRFLD
Solar/Wind Helper
0.398
3148133STUARTS
Solar/Wind Helper
0.172
3148013FISHERV
Solar/Wind Helper
0.165
3138266HYDRAULIC
Solar/Wind Helper
0.011
3138266HYDRAULIC
Solar/Wind Helper
0.007
316164AC1-076 GEN
Solar/Wind Helper
0.618
23546401DTGZ2-030
Solar/Wind Helper
0.04
238152AF2-075_GEN
Solar/Wind Helper
0.304
316312AB1-027
Solar/Wind Helper
0.233
316233AE1-074 FULL
Solar/Wind Helper
0.179
3141426STAFORD
Solar/Wind Helper
0.025
316223AC1-118
Solar/Wind Helper
0.173
3141813NORNECK
Solar/Wind Helper
0.113
3143873LANEXA
Solar/Wind Helper
0.067
316059AD1-063 C
Solar/Wind Helper
0.112
971029AG2-637 GEN
Solar/Wind Harmer
4.547
316095T157 G97
Solar/Wind Helper
0.556
316044AC1-158 PL1
Solar/Wind Helper
0.659
316450AC1-158 RIC
Solar/Wind Helper
0.176
3141906WESTMOR
Solar/Wind Helper
0.046
3142946ENON
Solar/Wind Helper
0.038
3141196NOKESVL
Solar/Wind Helper
0.452
316404AE1-155 C
Solar/Wind Helper
0.945
316484AD2-074 GEN
Solar/Wind Helper
0.215
274729ELWOOD EC;1P
Adder
7.487
276897AD1-100 C
Solar/Wind Harmer
0.004
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
10.359
276806AD2-047 C O1
Solar/Wind Harmer
1.793
970941AG2-585 GEN
Solar/Wind Harmer
3.954
253316AC1-085 GEN3
Solar/Wind Harmer
0.002
253433AC1-085 GEN1
Solar/Wind Harmer
0.001
946181AF1-283 GEN
Solar/Wind Harmer
4.111
270222AC2-111 GEN
Solar/Wind Harmer
1.601
270437AC2-090 C
Solar/Wind Harmer
0.001
247642Z2-115 C
Solar/Wind Harmer
0.001
970289AG2-191 GEN
Solar/Wind Harmer
0.347
970291AG2-192 GEN
Solar/Wind Harmer
0.315
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
958821AF2-173 GEN
Solar/Wind Harmer
4.392
270004AE1-209 GEN
Solar/Wind Harmer
0.68
964401AG1-302 GEN
Solar/Wind Harmer
0
946031AF1-268 GEN
Solar/Wind Harmer
2.971
270535AF1-215 GEN1
Solar/Wind Harmer
0.004
253406AD2-031_GEN
Solar/Wind Harmer
0.232
971191AH1-055 GEN
Solar/Wind Harmer
7.979
3147983MERCK5
Solar/Wind Helper
0.107
316192AB2-158 GEN
Solar/Wind Helper
0.985
3147666LOUISA
Solar/Wind Helper
0.583
958121AF2-106 GEN
Solar/Wind Helper
1.048
316336AC2-165 C
Solar/Wind Helper
0.729
316254AC1-120 GEN1
Solar/Wind Helper
0.611
316322AB2-045
Solar/Wind Helper
0.14
3146776BUCKING
Solar/Wind Helper
0.05
238148AE2-230_GEN2
Solar/Wind Helper
0.214
316006AB2-029 C
Solar/Wind Helper
0.058
3142416OLDCHRC
Solar/Wind Helper
0.318
3142416OLDCHRC
Solar/Wind Helper
0.122
316097T157 G90
Solar/Wind Helper
0.556
316045AC1-158 PL2
Solar/Wind Helper
2.111
3143526WINTERP
Solar/Wind Helper
0.609
3143226MDLTHAN
Solar/Wind Helper
0.117
3142543TWELFTH
Solar/Wind Helper
0.011
316337AD2-073 GEN
Solar/Wind Helper
0.172
964211AG1-282 GEN
Solar/Wind Helper
0.152
3141726DUNNSVL
Solar/Wind Helper
0.452
3142433PROV 92
Solar/Wind Helper
0.448
3141766HARMONY
Solar/Wind Helper
0.022
253317AC1-085 GEN4
Solar/Wind Harmer
0.002
24379505HDWTR1G C
Solar/Wind Harmer
0.001
270209AC1-174_GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
971613AH1-306 GEN
Solar/Wind Harmer
1.51
270383AD1-128 GEN
Solar/Wind Harmer
0.002
960441AF2-335 GEN
Solar/Wind Harmer
3.136
970825AG2-519 GEN
Solar/Wind Harmer
3.475
253394AE2-221_GEN
Solar/Wind Harmer
0.004
253398AE2-221_GEN2
Solar/Wind Harmer
0.004
270599AE1-208 GEN
Solar/Wind Harmer
2.851
270031AE2-169
Solar/Wind Harmer
1.71
3132123MT JACKSON
Solar/Wind Helper
0.746
315821AE2-092 GEN
Solar/Wind Helper
1.824
966001AG1-469 GEN
Solar/Wind Helper
0.172
315651AD1-115 GEN
Solar/Wind Helper
0.441
3146776BUCKING
Solar/Wind Helper
0.504
3146776BUCKING
Solar/Wind Helper
0.041
966871AG1-558 GEN
Solar/Wind Helper
0.167
316468AD1-105 GEN
Solar/Wind Helper
0.61
316447AC1-158 HLD
Solar/Wind Helper
1.451
316075AC2-137 C
Solar/Wind Helper
0.179
3143526WINTERP
Solar/Wind Helper
0.609
3142946ENON
Solar/Wind Helper
0.011
316077AC2-138 C
Solar/Wind Helper
0.106
316487AF1-042 GEN
Solar/Wind Helper
0.113
944201AF1-088_MTX
Adder
56.965
957141AF2-008_MTX
Adder
28.482
NYPJM->LTFIMP_NY
CLTF
1.478
LGEELTFEXP_LGEE->PJM
CLTF
3.565
WECLTFEXP_WEC->PJM
CLTF
1.782
AG2-052LTFEXP_AG2-052->PJM
LTF
0.105
AH1-155LTFEXP_AH1-155->PJM
LTF
0.158
LAGNLTFEXP_LAGN->PJM
CLTF
11.707
CBM South 2LTFEXP_CBM-S2->PJM
CBM
15.107
TVALTFEXP_TVA->PJM
CLTF
6.219
CBM West 1LTFEXP_CBM-W1->PJM
CBM
64.396
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.657
MECLTFEXP_MEC->PJM
CLTF
8.32
SIGELTFEXP_SIGE->PJM
CLTF
0.271
CPLELTFEXP_CPLE->PJM
CLTF
3.112
CBM West 2LTFEXP_CBM-W2->PJM
CBM
73.214

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AP_P1-3_MP-765-501T_SRT-A


Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-501T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:121.06 %
Rating:3393.4 MVA
Rating Type:B
MVA to Mitigate:4107.97
MW Contribution:2.94
Bus #Bus NameTypeMW Contribution
970479AG2-310 GEN
50/50
20.255
270205AE1-176
50/50
0.006
24288905REUSENS
50/50
0.057
24684605SMG4
50/50
2.239
966251AG1-494 GEN
50/50
4.388
24728405LEESVG
50/50
0.297
24415905BUCK
50/50
0.034
971367AH1-164 GEN
Solar/Wind Harmer
4.886
971329AH1-144 GEN
Solar/Wind Harmer
11.568
3147312GRETNA
Solar/Wind Harmer
0.047
941821AE2-187 GEN
Solar/Wind Harmer
7.452
270197AD1-017 GEN1
Solar/Wind Harmer
1.429
270336AE1-100 GEN
Solar/Wind Harmer
0.006
943811AF1-049 GEN
Solar/Wind Harmer
-0.002
24728305BUCHG2
Adder
6.75
270018AE2-047 C O1
Solar/Wind Harmer
0.004
958131AF2-107 GEN
Solar/Wind Harmer
5.339
24735205WLF2G2
Adder
8.023
971687AH1-348 GEN
Solar/Wind Harmer
0.948
971403AH1-188 GEN
Solar/Wind Harmer
13.153
24723205RIVRG3
Adder
22.954
971315AH1-136 GEN
Solar/Wind Harmer
1.695
24686105CER G3
Adder
9.887
24686505CER G6
Adder
9.874
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
24721705FLATG2
Adder
21.686
970947AG2-589 GEN
Solar/Wind Harmer
0.249
970273AG2-179 GEN
Solar/Wind Harmer
2.581
971821AH1-427 GEN
Solar/Wind Harmer
7.218
964901AG1-354 GEN
Solar/Wind Harmer
10.814
962241AG1-070 GEN
Solar/Wind Harmer
3.92
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
3429241JKCT 3G
Adder
12.029
3429421JKCT 10G
Adder
8.402
971565AH1-281 GEN
Solar/Wind Harmer
1.396
339216AC1-074 GEN
Solar/Wind Harmer
0.187
945681AF1-233 GEN
Solar/Wind Harmer
12.782
927014AC1-188 GEN
Solar/Wind Harmer
0.004
970823AG2-518 GEN
50/50
8.384
247619Y1-049
50/50
0.913
24684705SMG5
50/50
0.856
970481AG2-311 GEN
50/50
11.937
24728405LEESVG
50/50
0.295
24416005BYLLESBY
50/50
0.031
3151561HALLBR1
50/50
0.57
970563AG2-360 GEN
50/50
45.829
962751AG1-124 GEN
Solar/Wind Harmer
12.893
958121AF2-106 GEN
Solar/Wind Harmer
0.001
270173AC1-122 GEN
Solar/Wind Harmer
0.677
971331AH1-145 GEN
Solar/Wind Harmer
18.361
943031AE2-326 GEN
Solar/Wind Harmer
6.784
3147312GRETNA
Solar/Wind Harmer
0.186
3146802CHATHAM
Solar/Wind Harmer
0.175
941801AE2-185 GEN
Solar/Wind Harmer
7.452
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
3147123OTTER R
Solar/Wind Harmer
0.13
270346AE1-212 GEN
Solar/Wind Harmer
9.542
270030AE2-140 GEN
Solar/Wind Harmer
21.578
960911AF2-382 GEN
Solar/Wind Harmer
7.638
270016AE1-250 BESS
Solar/Wind Harmer
0.006
970913AG2-568 GEN
Solar/Wind Harmer
7.677
971461AH1-227 GEN
Solar/Wind Harmer
4.886
970223AG2-152 GEN
Solar/Wind Harmer
12.358
270053AF1-130 C
Solar/Wind Harmer
2.047
972103AH1-617 GEN
Solar/Wind Harmer
18.024
24686205CER G4
Adder
9.835
24686405CER G5
Adder
9.796
972273AH1-721 GEN
Adder
89.316
24721905FLATG4
Adder
21.686
970273AG2-179 GEN
Solar/Wind Harmer
4.425
339250AF1-203 GEN
Solar/Wind Harmer
0.001
971155AH1-034 GEN
Solar/Wind Harmer
8.427
962251AG1-071 GEN
Solar/Wind Harmer
4.496
966571AG1-526 GEN
Solar/Wind Harmer
15.967
970093AG2-073 GEN
Solar/Wind Harmer
7.166
960741AF2-365 GEN
Solar/Wind Harmer
3.563
3429391JKCT 9G
Adder
8.402
971191AH1-055 GEN
Solar/Wind Harmer
18.055
972167AH1-666 GEN
Solar/Wind Harmer
5.419
958171AF2-111 GEN
Solar/Wind Harmer
16.681
970243AG2-164 GEN
Solar/Wind Harmer
3.891
970519AG2-331 GEN
Solar/Wind Harmer
17.292
970699AG2-449 GEN
Solar/Wind Harmer
1.663
25196008MFTGT1
Adder
1.252
252510AF1-249 C
Solar/Wind Harmer
0.05
25194608D.CRK4
Adder
1.508
25196608WSDLE5
Adder
7.849
970193AG2-126 GEN
Solar/Wind Harmer
9.55
942481AE2-261 GEN
Solar/Wind Harmer
18.997
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
8.231
24728705AND G3
Adder
7.277
24728505AND G1
Adder
3.48
276621W2-048 GEN
Solar/Wind Harmer
0.318
276838X2-022 GEN2
Solar/Wind Harmer
0.355
276686W4-005 GEN3
Solar/Wind Harmer
0.001
276668AB2-070 GEN1
Solar/Wind Harmer
0.229
971993AH1-541 GEN
Solar/Wind Harmer
2.905
270356AE2-297 GEN
Solar/Wind Harmer
0.008
253406AD2-031_GEN
Solar/Wind Harmer
0.467
270222AC2-111 GEN
Solar/Wind Harmer
3.158
965931AG1-462 GEN
Solar/Wind Harmer
15.879
270291AC1-194 GEN
Solar/Wind Harmer
4.924
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
965091AG1-374 GEN
Solar/Wind Harmer
18.654
959611AF2-252 GEN
Solar/Wind Harmer
2.073
942111AE2-223 GEN
Solar/Wind Harmer
2.013
274878BISHOP HL;2U
Solar/Wind Harmer
0.208
276157O29GEN1
Solar/Wind Harmer
0.999
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
8.222
274767LEE CO EC;8U
Adder
8.125
270437AC2-090 C
Solar/Wind Harmer
0.003
970571AG2-364 GEN
Solar/Wind Harmer
12.296
253415AE1-040 GEN
Solar/Wind Harmer
0.002
972236AH1-702 GEN2
Adder
1.93
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.144
959091AF2-200 GEN
Solar/Wind Harmer
12.273
276889AE2-281 GEN
Solar/Wind Harmer
0.001
274855GSG-6 ;RU
Solar/Wind Harmer
0.225
274850MENDOTA H;RU
Solar/Wind Harmer
0.072
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.11
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.654
247642Z2-115 C
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
0.673
970291AG2-192 GEN
Solar/Wind Harmer
0.612
274872LEEDK;1U
Solar/Wind Harmer
0.224
958821AF2-173 GEN
Solar/Wind Harmer
8.556
270004AE1-209 GEN
Solar/Wind Harmer
1.324
276805AD2-038 GEN
Solar/Wind Harmer
0.002
274682WAUKEGAN ;7U
Adder
15.703
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
946031AF1-268 GEN
Solar/Wind Harmer
5.79
943121AE2-341 GEN
Solar/Wind Harmer
10.192
943591AF1-030 GEN
Solar/Wind Harmer
6.778
274729ELWOOD EC;1P
Adder
13.481
970091AG2-072 GEN
Adder
74.012
970333AG2-219 GEN
Solar/Wind Harmer
4.755
270445AC2-157 GEN2
Solar/Wind Harmer
0.003
25196808ZIMRHP
Adder
70.616
252507AC2-088 GEN
Solar/Wind Harmer
0.295
25196008MFTGT1
Adder
1.293
25194608D.CRK4
Adder
1.508
965911AG1-460 GEN
Solar/Wind Harmer
1.271
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.331
24728605AND G2
Adder
3.48
276615X2-022 GEN
Solar/Wind Harmer
0.066
963831AG1-236 GEN
Solar/Wind Harmer
2.455
274880W4-005 GEN4
Solar/Wind Harmer
0.001
970773AG2-487 GEN
Solar/Wind Harmer
1.107
963741AG1-226 GEN
Solar/Wind Harmer
14.811
972175AH1-670 GEN
Solar/Wind Harmer
5.171
274854TWINGROVE;U2
Solar/Wind Harmer
0.003
276726Z2-087_GEN
Solar/Wind Harmer
0.002
939741AE1-205 GEN
Solar/Wind Harmer
8.673
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.002
274877BISHOP HL;1U
Solar/Wind Harmer
0.208
276158O29GEN2
Solar/Wind Harmer
0.001
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
8.222
274766LEE CO EC;7U
Adder
8.125
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.519
276903AD2-071 C
Solar/Wind Harmer
6.874
971475AH1-234 GEN
Solar/Wind Harmer
2.986
970819AG2-516 GEN
Solar/Wind Harmer
7.379
970569AG2-363 GEN
Solar/Wind Harmer
18.444
972235AH1-702 GEN1
Adder
2.22
24791305MDL-5G
Solar/Wind Harmer
0.001
274822ROCKFORD ;11
Adder
17.275
957471AF2-041 GEN
Solar/Wind Harmer
18.409
959081AF2-199 GEN
Solar/Wind Harmer
6.136
971067AG2-660 GEN
Solar/Wind Harmer
2.045
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
276861AD2-134 GEN
Solar/Wind Harmer
0.11
970291AG2-192 GEN
Solar/Wind Harmer
0.796
971997AH1-543 GEN
Solar/Wind Harmer
3.211
270032AE2-172
Solar/Wind Harmer
4.079
270263AC1-001 GEN
Solar/Wind Harmer
0.614
274872LEEDK;1U
Solar/Wind Harmer
0.004
270005AE1-210 C O1
Solar/Wind Harmer
1.324
965031AG1-367 GEN
Solar/Wind Harmer
6.111
962781AG1-127 GEN
Solar/Wind Harmer
5.815
276901AD2-066 C O1
Solar/Wind Harmer
0.006
939401AE1-172 GEN
Solar/Wind Harmer
4.568
970825AG2-519 GEN
Solar/Wind Harmer
2.167
274828WAUKEGAN ;BP
Adder
9.655
274682WAUKEGAN ;7U
Adder
15.703
276691AA1-018 GEN1
Solar/Wind Harmer
0.737
274745AC1-111 GEN9
Adder
4.87
315616AA1-038_C
Solar/Wind Helper
3.293
3148013FISHERV
Solar/Wind Helper
0.523
316499AE2-029_GEN
Solar/Wind Helper
1.725
3132273ORANGE
Solar/Wind Helper
0.056
3147666LOUISA
Solar/Wind Helper
0.625
237061AD1-155 GEN
Solar/Wind Helper
0.05
316170AC1-121 GEN2
Solar/Wind Helper
0.386
23583801GRNGAP
Solar/Wind Helper
4.287
316095T157 G97
Solar/Wind Helper
1.125
238147AE2-230_GEN1
Solar/Wind Helper
0.421
238149AF1-291A_GEN
Solar/Wind Helper
0.12
316313AB2-026
Solar/Wind Helper
0.354
316258AE1-075 C
Solar/Wind Helper
0.319
316405AF2-144 C
Solar/Wind Helper
0.265
966881AG1-559 GEN
Solar/Wind Helper
0.313
316473AC1-191 GEN
Solar/Wind Helper
1.387
316044AC1-158 PL1
Solar/Wind Helper
1.257
316450AC1-158 RIC
Solar/Wind Helper
0.335
3147983MERCK5
Solar/Wind Helper
0.198
316192AB2-158 GEN
Solar/Wind Helper
1.838
3147666LOUISA
Solar/Wind Helper
1.088
316254AC1-120 GEN1
Solar/Wind Helper
1.159
316097T157 G90
Solar/Wind Helper
1.125
238148AE2-230_GEN2
Solar/Wind Helper
0.423
316336AC2-165 C
Solar/Wind Helper
1.285
316006AB2-029 C
Solar/Wind Helper
0.112
316045AC1-158 PL2
Solar/Wind Helper
4.023
24290605CLAY-1
50/50
0.255
24290605CLAY-1
50/50
0.255
24290705CLAY-2
50/50
0.255
24290705CLAY-2
50/50
0.255
24684405SMG2
50/50
2.224
24684505SMG3
50/50
1.376
24684305SMG1
50/50
0.806
270583AD2-179 GEN
Solar/Wind Harmer
14.457
971277AH1-098 GEN
Solar/Wind Harmer
5.177
316217AC1-145 GEN
Solar/Wind Harmer
0.003
316197AC1-042 GEN
Solar/Wind Harmer
0.002
942671AE2-283 GEN
Solar/Wind Harmer
5.796
24728205BUCHG1
Adder
6.75
270013AE1-250 PV
Solar/Wind Harmer
0.006
971225AH1-072 GEN
Solar/Wind Harmer
1.905
971227AH1-073 GEN
Solar/Wind Harmer
1.905
944971AF1-162 GEN
Solar/Wind Harmer
9.068
24723005RIVRG1
Adder
22.954
24723105RIVRG2
Adder
22.954
24685805CER G1
Adder
9.822
24685905CER G2
Adder
9.822
942751AE2-291 GEN
Solar/Wind Harmer
7.887
966021AG1-471 GEN
Solar/Wind Harmer
4.013
971485AH1-239 GEN
Solar/Wind Harmer
5.928
960161AF2-307 GEN
Solar/Wind Harmer
4.775
339255AE2-071 GEN
Solar/Wind Harmer
-0.119
964781AG1-341 GEN
Solar/Wind Harmer
7.653
971081AG2-670 GEN
Solar/Wind Harmer
5.396
942891AE2-308 GEN
Solar/Wind Harmer
7.099
970653AG2-424 GEN
Solar/Wind Harmer
3.405
970653AG2-424 GEN
Solar/Wind Harmer
1.764
964571AG1-320 GEN
Solar/Wind Harmer
6.361
971125AH1-004 GEN
Solar/Wind Harmer
2.777
970107AG2-081 GEN
Solar/Wind Harmer
2.083
972043AH1-570 GEN
Solar/Wind Harmer
1.796
972045AH1-571 GEN
Solar/Wind Harmer
1.439
339221AD2-048_GEN
Solar/Wind Harmer
0.004
970235AG2-159 GEN
Solar/Wind Harmer
4.126
970235AG2-159 GEN
Solar/Wind Harmer
2.367
270186AC1-089 GEN
Solar/Wind Harmer
0.004
970239AG2-162 GEN
Solar/Wind Harmer
1.663
962581AG1-107 GEN
Solar/Wind Harmer
0.001
270444AC2-157 GEN1
Solar/Wind Harmer
0.003
971587AH1-292 GEN
Solar/Wind Harmer
4.8
252509AD1-136 GEN
Solar/Wind Harmer
0.033
25183208HLCRTG
Solar/Wind Harmer
0.01
252519AF1-045_GEN
Solar/Wind Harmer
5.589
252516AE2-318_GEN
Solar/Wind Harmer
4.958
25194408D.CRK1
Adder
6.938
25194508D.CRK3
Adder
1.297
971073AG2-665 GEN
Solar/Wind Harmer
5.761
945391AF1-204 GEN
Solar/Wind Harmer
6.765
276916AD2-100_GEN
Solar/Wind Harmer
13.364
276911AD2-131_GEN
Solar/Wind Harmer
0.88
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
970241AG2-163 GEN
Solar/Wind Harmer
3.651
24728805RICHG1
Adder
3.384
24728905RICHG2
Adder
3.384
253394AE2-221_GEN
Solar/Wind Harmer
0.008
253398AE2-221_GEN2
Solar/Wind Harmer
0.008
960251AF2-316 GEN
Solar/Wind Harmer
8.583
960201AF2-311 GEN
Solar/Wind Harmer
5.708
960611AF2-352 GEN
Solar/Wind Harmer
2.073
966841AG1-555 GEN
Solar/Wind Harmer
0.701
276782AC1-033 GEN
Solar/Wind Harmer
0.001
276741O09 GEN1
Solar/Wind Harmer
0.22
276708O09 GEN2
Solar/Wind Harmer
0.22
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.243
276646AC1-214 GEN2
Solar/Wind Harmer
0.243
972267AH1-718 GEN
Adder
3.688
276603SUBLETTE C
Solar/Wind Harmer
0
274764LEE CO EC;5U
Adder
8.241
274765LEE CO EC;6U
Adder
8.241
274762LEE CO EC;3U
Adder
8.222
274763LEE CO EC;4U
Adder
8.144
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
938861AE1-114 GEN
Solar/Wind Harmer
3.491
274856ECOGROVE ;U1
Solar/Wind Harmer
0.145
276611AD2-172 GEN
Solar/Wind Harmer
0.002
270383AD1-128 GEN
Solar/Wind Harmer
0.004
971341AH1-150 GEN
Solar/Wind Harmer
12.273
971343AH1-151 GEN
Solar/Wind Harmer
12.273
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
971333AH1-146 GEN
Solar/Wind Harmer
12.256
971335AH1-147 GEN
Solar/Wind Harmer
12.256
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
942991AE2-321 GEN
Solar/Wind Harmer
6.834
971613AH1-306 GEN
Solar/Wind Harmer
2.937
274879MINONK ;1U
Solar/Wind Harmer
0.258
970921AG2-575 GEN
Solar/Wind Harmer
6.111
970921AG2-575 GEN
Solar/Wind Harmer
2.037
962691AG1-118 GEN
Solar/Wind Harmer
18.322
958491AF2-143 GEN
Solar/Wind Harmer
9.158
960441AF2-335 GEN
Solar/Wind Harmer
6.106
970825AG2-519 GEN
Solar/Wind Harmer
6.767
274683WAUKEGAN ;8U
Adder
18.419
274683WAUKEGAN ;8U
Adder
15.526
274696ROCKY RD ;4P
Adder
9.957
274695ROCKY RD ;2P
Adder
9.727
274693ROCKY RD ;1P
Adder
9.632
274697ROCKY RD ;3P
Adder
2.642
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.824
958481AF2-142 GEN
Solar/Wind Harmer
9.131
971573AH1-285 GEN
Solar/Wind Harmer
1.134
3132123MT JACKSON
Solar/Wind Helper
1.389
315821AE2-092 GEN
Solar/Wind Helper
3.216
966001AG1-469 GEN
Solar/Wind Helper
0.32
315651AD1-115 GEN
Solar/Wind Helper
0.837
966871AG1-558 GEN
Solar/Wind Helper
0.306
316447AC1-158 HLD
Solar/Wind Helper
2.766
316468AD1-105 GEN
Solar/Wind Helper
1.124
971543AH1-269 GEN
50/50
12.247
966391AG1-508 GEN
Solar/Wind Harmer
1.993
270069AE2-166 C O1
Solar/Wind Harmer
0.008
971313AH1-133 GEN
Solar/Wind Harmer
10.952
24734705WLF1G3
Adder
8.194
24734805WLF1G4
Adder
8.194
24734905WLF1G5
Adder
8.194
270132AB1-180 C
Adder
0.169
24735105WLF2G1
Adder
8.023
270399AC1-101 GEN
Solar/Wind Harmer
2.892
270400AC1-102 GEN
Solar/Wind Harmer
2.892
941621AE2-160 GEN
Adder
4.285
957241AF2-018 GEN
Solar/Wind Harmer
-0.002
970281AG2-184 GEN
Solar/Wind Harmer
18.925
972143AH1-644 GEN
Solar/Wind Harmer
9.763
971981AH1-535 GEN
Solar/Wind Harmer
5.843
971061AG2-657 GEN
Solar/Wind Harmer
5.368
24477305BRIDGE
Adder
0.419
972203AH1-686 GEN
Adder
2.704
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
965401AG1-405 GEN
Solar/Wind Harmer
4.227
965411AG1-406 GEN
Solar/Wind Harmer
2.719
339211AE2-254 GEN
Solar/Wind Harmer
0.003
3429211JKCT 2G
Adder
11.873
970455AG2-298 GEN
Solar/Wind Harmer
4.677
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
972163AH1-664 GEN
Solar/Wind Harmer
7.568
972165AH1-665 GEN
Solar/Wind Harmer
6.061
971985AH1-537 GEN
Solar/Wind Harmer
2.011
270367AC2-061_GEN
Solar/Wind Harmer
0.005
316123AC1-075 GEN
Solar/Wind Harmer
0.168
970165AG2-112 GEN
Solar/Wind Harmer
0.998
970163AG2-111 GEN
Solar/Wind Harmer
0.952
25196108MFTGT2
Adder
1.425
25196108MFTGT2
Adder
1.324
970879AG2-548 GEN
Solar/Wind Harmer
5.761
944221AF1-090 GEN
Solar/Wind Harmer
3.754
252524AE2-267 GEN
Solar/Wind Harmer
0.002
25196408WSDLE3
Adder
8.08
25196308WSDLE2
Adder
8.01
25196208WSDLE1
Adder
7.99
25196708WSDLE6
Adder
7.97
25196508WSDLE4
Adder
7.769
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.229
276848AB2-070 GEN3
Solar/Wind Harmer
0.228
963841AG1-237 GEN
Solar/Wind Harmer
2.698
946321AF1-296 GEN
Solar/Wind Harmer
3.483
270340AC2-060 GEN
Solar/Wind Harmer
0.007
276655WTG1_EQ
Solar/Wind Harmer
0.002
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
6.505
941731AE2-173 GEN
Solar/Wind Harmer
5.162
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
957751AF2-069 GEN
Solar/Wind Harmer
0.204
961011AF2-392 GEN
Solar/Wind Harmer
3.623
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
270240V3-007_GEN2
Solar/Wind Harmer
0.002
971681AH1-341 GEN
Solar/Wind Harmer
9.917
276612AE2-035 GEN
Solar/Wind Harmer
0.002
926823AC1-168 GEN
Solar/Wind Harmer
1.045
970169AG2-114 GEN
Solar/Wind Harmer
6.149
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274823ROCKFORD ;21
Adder
17.15
971171AH1-044 GEN
Solar/Wind Harmer
12.273
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
971675AH1-338 GEN
Solar/Wind Harmer
2.39
971411AH1-196 GEN
Solar/Wind Harmer
9.19
970289AG2-191 GEN
Solar/Wind Harmer
1.163
971177AH1-047 GEN
Solar/Wind Harmer
3.774
270594AE1-207 GEN
Solar/Wind Harmer
6.853
276868AE1-113 GEN
Solar/Wind Harmer
1.227
276882AE2-255 GEN
Solar/Wind Harmer
0.715
970115AG2-085 GEN
Solar/Wind Harmer
2.442
971673AH1-337 GEN
Solar/Wind Harmer
3.956
274746AC1-111 G10
Adder
4.87
274744AC1-111 GEN8
Adder
4.87
25306009OHH W.
Adder
2.505
3148463FAIRFLD
Solar/Wind Helper
0.726
3148133STUARTS
Solar/Wind Helper
0.313
3148013FISHERV
Solar/Wind Helper
0.3
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
23546401DTGZ2-030
Solar/Wind Helper
0.078
316164AC1-076 GEN
Solar/Wind Helper
1.172
238152AF2-075_GEN
Solar/Wind Helper
0.602
971029AG2-637 GEN
Solar/Wind Harmer
2.803
944201AF1-088_MTX
Adder
109.09
957141AF2-008_MTX
Adder
54.545
NYPJM->LTFIMP_NY
CLTF
3.248
LGEELTFEXP_LGEE->PJM
CLTF
6.763
WECLTFEXP_WEC->PJM
CLTF
3.371
AG2-052LTFEXP_AG2-052->PJM
LTF
0.202
AH1-155LTFEXP_AH1-155->PJM
LTF
0.303
LAGNLTFEXP_LAGN->PJM
CLTF
20.28
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.555
TVALTFEXP_TVA->PJM
CLTF
10.606
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.415
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.315
MECLTFEXP_MEC->PJM
CLTF
15.415
SIGELTFEXP_SIGE->PJM
CLTF
0.508
CPLELTFEXP_CPLE->PJM
CLTF
6.226
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.111

Details for 05HANGRCK_RJ-05HANG R 765.0 kV Ckt Z1 line l/o AEP_P1-2_#7441_100545_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05HANGRCK_RJ-05HANG R 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.88 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:4885.66
MW Contribution:4.37
Bus #Bus NameTypeMW Contribution
970091AG2-072 GEN
50/50
198.882
270407AB1-088 ST1
50/50
3.172
970333AG2-219 GEN
Solar/Wind Harmer
12.809
270445AC2-157 GEN2
Solar/Wind Harmer
0.006
970245AG2-165 GEN
Solar/Wind Harmer
4.889
24791305MDL-5G
Solar/Wind Harmer
0.001
24385905FR-11G C
Solar/Wind Harmer
0.003
24387305FR-4G C
Solar/Wind Harmer
0.004
963741AG1-226 GEN
Solar/Wind Harmer
26.02
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
13.725
964861AG1-349 GEN
Solar/Wind Harmer
-0.002
971917AH1-482 GEN
Solar/Wind Harmer
13.986
958381AF2-132 GEN
Solar/Wind Harmer
0.002
270055AF2-134 C O1
Solar/Wind Harmer
0.008
970373AG2-245 GEN
Solar/Wind Harmer
21.781
274773LINCOLN ;4U
Adder
11.903
274774LINCOLN ;5U
Adder
11.903
276726Z2-087_GEN
Solar/Wind Harmer
0.003
939741AE1-205 GEN
Solar/Wind Harmer
13.718
939401AE1-172 GEN
Solar/Wind Harmer
7.325
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274751CRETE EC ;1U
Adder
11.551
274754CRETE EC ;4U
Adder
11.551
274854TWINGROVE;U2
Solar/Wind Harmer
0.004
972175AH1-670 GEN
Solar/Wind Harmer
8.079
274723RIVER EC ;12
Adder
25.097
274880W4-005 GEN4
Solar/Wind Harmer
0.001
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
7.01
276776AD2-060 GEN
Solar/Wind Harmer
1.019
274801UNIV PARK;4U
Adder
8.146
963831AG1-236 GEN
Solar/Wind Harmer
3.802
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
274732ELWOOD EC;7P
Adder
22.908
276615X2-022 GEN
Solar/Wind Harmer
0.102
274674JOLIET 9 ;6U
Adder
21.442
274676JOLIET 29;8U
Adder
42.703
276691AA1-018 GEN1
Solar/Wind Harmer
1.17
274745AC1-111 GEN9
Adder
7.736
965911AG1-460 GEN
Solar/Wind Harmer
1.93
276901AD2-066 C O1
Solar/Wind Harmer
0.01
971997AH1-543 GEN
Solar/Wind Harmer
5.053
274682WAUKEGAN ;7U
Adder
24.679
276876AE1-163_GEN2
Solar/Wind Harmer
0.003
274828WAUKEGAN ;BP
Adder
15.157
970569AG2-363 GEN
Solar/Wind Harmer
28.645
962781AG1-127 GEN
Solar/Wind Harmer
9.085
274872LEEDK;1U
Solar/Wind Harmer
0.006
276861AD2-134 GEN
Solar/Wind Harmer
0.17
957471AF2-041 GEN
Solar/Wind Harmer
28.383
959081AF2-199 GEN
Solar/Wind Harmer
9.461
971067AG2-660 GEN
Solar/Wind Harmer
3.154
970291AG2-192 GEN
Solar/Wind Harmer
1.229
274877BISHOP HL;1U
Solar/Wind Harmer
0.317
274822ROCKFORD ;11
Adder
26.534
972235AH1-702 GEN1
Adder
3.404
970819AG2-516 GEN
Solar/Wind Harmer
11.285
971475AH1-234 GEN
Solar/Wind Harmer
4.553
274857EASY ROAD;U1
Solar/Wind Harmer
0.002
276158O29GEN2
Solar/Wind Harmer
0.001
270505AE1-170 C O1
Solar/Wind Harmer
9.741
945111AF1-176 GEN
Solar/Wind Harmer
16.452
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
4.8
270032AE2-172
Solar/Wind Harmer
6.065
276903AD2-071 C
Solar/Wind Harmer
10.136
270063AE2-323 C
Solar/Wind Harmer
0.007
965651AG1-433 GEN
Solar/Wind Harmer
2.403
958861AF2-177 GEN
Solar/Wind Harmer
3.539
945371AF1-202 GEN
Solar/Wind Harmer
0.001
970825AG2-519 GEN
Solar/Wind Harmer
2.846
270005AE1-210 C O1
Solar/Wind Harmer
1.734
965031AG1-367 GEN
Solar/Wind Harmer
8.001
970773AG2-487 GEN
Solar/Wind Harmer
1.37
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0.001
970613AG2-401 GEN
Solar/Wind Harmer
5.665
965011AG1-365 GEN
Solar/Wind Harmer
7.456
247536S-71 GEN
Solar/Wind Harmer
0.284
944231AF1-091 GEN
Solar/Wind Harmer
1.864
971565AH1-281 GEN
Solar/Wind Harmer
1.306
942601AE2-276 GEN
50/50
10.552
970239AG2-162 GEN
Solar/Wind Harmer
4.479
270444AC2-157 GEN1
Solar/Wind Harmer
0.006
971587AH1-292 GEN
Solar/Wind Harmer
9.286
970321AG2-212 GEN
Solar/Wind Harmer
4.889
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
966841AG1-555 GEN
Solar/Wind Harmer
1.266
970241AG2-163 GEN
Solar/Wind Harmer
6.413
945391AF1-204 GEN
Solar/Wind Harmer
11.343
965681AG1-436 GEN
Solar/Wind Harmer
12.338
965791AG1-447 GEN
Solar/Wind Harmer
9.048
274770LINCOLN ;1U
Adder
11.903
274771LINCOLN ;2U
Adder
11.903
960611AF2-352 GEN
Solar/Wind Harmer
3.259
274808UNIV PK N;4U
Adder
6.98
274888KELLY CRK;1U
Solar/Wind Harmer
0.573
274887GEN-1.85
Solar/Wind Harmer
0.257
276843GEN-1.7
Solar/Wind Harmer
0.316
958011AF2-095 GEN
Solar/Wind Harmer
14.061
972259AH1-714 GEN
Adder
26.685
274803UNIV PARK;6U
Adder
8.15
276763AC1-053 GEN1
Solar/Wind Harmer
0.002
276764AC1-053 GEN2
Solar/Wind Harmer
0.002
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
274674JOLIET 9 ;6U
Adder
21.442
24441505OLIV SLR
Solar/Wind Harmer
0
958481AF2-142 GEN
Solar/Wind Harmer
14.489
274861TOP CROP ;1U
Solar/Wind Harmer
0.003
274862TOP CROP ;2U
Solar/Wind Harmer
1.307
276916AD2-100_GEN
Solar/Wind Harmer
20.263
276911AD2-131_GEN
Solar/Wind Harmer
1.335
971573AH1-285 GEN
Solar/Wind Harmer
1.794
958491AF2-143 GEN
Solar/Wind Harmer
14.439
270526AF1-158 GEN
Solar/Wind Harmer
0.012
274879MINONK ;1U
Solar/Wind Harmer
0.405
274696ROCKY RD ;4P
Adder
15.67
274695ROCKY RD ;2P
Adder
15.309
274693ROCKY RD ;1P
Adder
15.158
274697ROCKY RD ;3P
Adder
4.159
276872AE1-163_GEN1
Solar/Wind Harmer
0.003
274683WAUKEGAN ;8U
Adder
28.915
274683WAUKEGAN ;8U
Adder
24.374
962691AG1-118 GEN
Solar/Wind Harmer
28.676
970921AG2-575 GEN
Solar/Wind Harmer
9.546
970921AG2-575 GEN
Solar/Wind Harmer
3.182
942991AE2-321 GEN
Solar/Wind Harmer
10.614
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.373
276646AC1-214 GEN2
Solar/Wind Harmer
0.373
971333AH1-146 GEN
Solar/Wind Harmer
18.962
971335AH1-147 GEN
Solar/Wind Harmer
18.962
971341AH1-150 GEN
Solar/Wind Harmer
18.922
971343AH1-151 GEN
Solar/Wind Harmer
18.922
276782AC1-033 GEN
Solar/Wind Harmer
0.001
274856ECOGROVE ;U1
Solar/Wind Harmer
0.222
276611AD2-172 GEN
Solar/Wind Harmer
0.003
938861AE1-114 GEN
Solar/Wind Harmer
5.315
276603SUBLETTE C
Solar/Wind Harmer
0
274764LEE CO EC;5U
Adder
12.51
274765LEE CO EC;6U
Adder
9.439
276741O09 GEN1
Solar/Wind Harmer
0.333
276708O09 GEN2
Solar/Wind Harmer
0.333
270216AD2-079_GEN
Solar/Wind Harmer
0.001
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
18.41
961051AF2-396 GEN
Solar/Wind Harmer
12.273
971613AH1-306 GEN
Solar/Wind Harmer
4.367
944541AF1-119 GEN
Solar/Wind Harmer
0.549
960971AF2-388 GEN
Solar/Wind Harmer
4.806
270599AE1-208 GEN
Solar/Wind Harmer
7.51
270031AE2-169
Solar/Wind Harmer
4.506
960441AF2-335 GEN
Solar/Wind Harmer
8.073
970825AG2-519 GEN
Solar/Wind Harmer
8.886
942221AE2-234 GEN
Solar/Wind Harmer
0.04
24379505HDWTR1G C
Solar/Wind Harmer
0.002
24344305RKG2
50/50
10.006
270406AB1-088 CT1
50/50
3.172
970243AG2-164 GEN
Solar/Wind Harmer
10.48
970519AG2-331 GEN
Solar/Wind Harmer
46.579
970699AG2-449 GEN
Solar/Wind Harmer
4.479
970513AG2-328 GEN
Solar/Wind Harmer
4.889
970517AG2-330 GEN
Solar/Wind Harmer
29.332
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
11.21
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
964401AG1-302 GEN
Solar/Wind Harmer
0.002
970193AG2-126 GEN
Solar/Wind Harmer
16.013
270535AF1-215 GEN1
Solar/Wind Harmer
0.013
970349AG2-230 GEN
Solar/Wind Harmer
14.79
274772LINCOLN ;3U
Adder
11.903
942111AE2-223 GEN
Solar/Wind Harmer
3.184
276897AD1-100 C
Solar/Wind Harmer
0.013
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
247642Z2-115 C
Solar/Wind Harmer
0.004
274752CRETE EC ;2U
Adder
11.551
274753CRETE EC ;3U
Adder
11.551
274853TWINGROVE;U1
Solar/Wind Harmer
0.004
965091AG1-374 GEN
Solar/Wind Harmer
29.335
959611AF2-252 GEN
Solar/Wind Harmer
3.259
274724RIVER EC ;11
Adder
24.801
972228AH1-698 GEN2
Adder
5.187
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
4.513
276806AD2-047 C O1
Solar/Wind Harmer
5.533
970941AG2-585 GEN
Solar/Wind Harmer
12.205
276668AB2-070 GEN1
Solar/Wind Harmer
0.356
970707AG2-453 GEN
Solar/Wind Harmer
31.865
274802UNIV PARK;5U
Adder
8.15
274800UNIV PARK;3U
Adder
8.146
972038AH1-567 GEN2
Adder
0.51
274826FISK ;BP
Adder
15.289
274729ELWOOD EC;1P
Adder
22.909
274730ELWOOD EC;6P
Adder
22.908
274734ELWOOD EC;8P
Adder
22.908
274736ELWOOD EC;9P
Adder
22.908
276893AG1-478 C
Solar/Wind Harmer
0.385
276621W2-048 GEN
Solar/Wind Harmer
0.49
276838X2-022 GEN2
Solar/Wind Harmer
0.547
274676JOLIET 29;8U
Adder
41.178
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
943121AE2-341 GEN
Solar/Wind Harmer
16.19
943591AF1-030 GEN
Solar/Wind Harmer
10.767
942481AE2-261 GEN
Solar/Wind Harmer
28.852
276805AD2-038 GEN
Solar/Wind Harmer
0.003
274682WAUKEGAN ;7U
Adder
24.679
276889AE2-281 GEN
Solar/Wind Harmer
0.001
970571AG2-364 GEN
Solar/Wind Harmer
19.097
274872LEEDK;1U
Solar/Wind Harmer
0.35
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
1.013
274855GSG-6 ;RU
Solar/Wind Harmer
0.348
274850MENDOTA H;RU
Solar/Wind Harmer
0.112
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.17
959091AF2-200 GEN
Solar/Wind Harmer
18.922
970289AG2-191 GEN
Solar/Wind Harmer
1.04
970291AG2-192 GEN
Solar/Wind Harmer
0.945
274878BISHOP HL;2U
Solar/Wind Harmer
0.317
972236AH1-702 GEN2
Adder
2.96
24642205MAYFLWER
Adder
0.856
274858EASY ROAD;U2
Solar/Wind Harmer
0.002
276157O29GEN1
Solar/Wind Harmer
1.512
247643Z2-116 C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
7.473
965931AG1-462 GEN
Solar/Wind Harmer
23.338
24441205WTRV SLR C
Solar/Wind Harmer
0
270043AE2-236 GEN
Solar/Wind Harmer
5.542
970031AG2-029 GEN
Solar/Wind Harmer
5.595
944531AF1-118 GEN
Solar/Wind Harmer
37.201
958821AF2-173 GEN
Solar/Wind Harmer
11.202
270004AE1-209 GEN
Solar/Wind Harmer
1.734
946031AF1-268 GEN
Solar/Wind Harmer
7.423
270356AE2-297 GEN
Solar/Wind Harmer
0.01
270437AC2-090 C
Solar/Wind Harmer
0.003
959331AF2-224 GEN
Solar/Wind Harmer
5.219
965021AG1-366 GEN
Solar/Wind Harmer
2.485
971617AH1-308 GEN
Solar/Wind Harmer
6.14
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
10.942
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.041
24344205RKG1
50/50
10.236
24344205RKG1
50/50
10.215
24344305RKG2
50/50
10.196
270393AB1-087 CT1
50/50
3.172
270394AB1-087 ST1
50/50
3.172
24690905MDL-1G C
Solar/Wind Harmer
0.003
270180AB1-006 GEN1
Solar/Wind Harmer
0.003
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.002
270181AB1-006 GEN2
Solar/Wind Harmer
0
24386205FR-12G C
Solar/Wind Harmer
0.002
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.002
963841AG1-237 GEN
Solar/Wind Harmer
4.805
971611AH1-305 GEN
Solar/Wind Harmer
6.537
958391AF2-133 GEN
Solar/Wind Harmer
0.002
270536AF1-215 GEN2
Solar/Wind Harmer
0.013
960681AF2-359 GEN
Solar/Wind Harmer
-0.002
971347AH1-153 GEN
Solar/Wind Harmer
14.79
274775LINCOLN ;6U
Adder
11.903
274776LINCOLN ;7U
Adder
11.903
274777LINCOLN ;8U
Adder
11.903
276655WTG1_EQ
Solar/Wind Harmer
0.004
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
10.288
941731AE2-173 GEN
Solar/Wind Harmer
8.165
274863CRW1-WTG
Solar/Wind Harmer
0.003
274864CRW2-WTG
Solar/Wind Harmer
0.003
970169AG2-114 GEN
Solar/Wind Harmer
9.776
972227AH1-698 GEN1
Adder
3.652
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
274814UNIV PK N;0U
Adder
7.072
274807UNIV PK N;3U
Adder
7.056
274805UNIV PK N;1U
Adder
7.026
274811UNIV PK N;7U
Adder
7.01
960591AF2-350 GEN
Solar/Wind Harmer
9.764
276849AB2-070 GEN2
Solar/Wind Harmer
0.356
276848AB2-070 GEN3
Solar/Wind Harmer
0.354
972037AH1-567 GEN1
Adder
0.256
274827FISK ;RP
Adder
10.835
970833AG2-524 GEN
Solar/Wind Harmer
10.702
970833AG2-524 GEN
Solar/Wind Harmer
7.134
274731ELWOOD EC;2P
Adder
22.909
274733ELWOOD EC;3P
Adder
22.909
274735ELWOOD EC;4P
Adder
22.909
274728ELWOOD EC;5P
Adder
22.908
274687WILL CNTY;4U
Adder
38.91
274687WILL CNTY;4U
Adder
38.91
274675JOLIET 29;7U
Adder
42.703
274675JOLIET 29;7U
Adder
41.178
971769AH1-391 GEN
Solar/Wind Harmer
10.786
274746AC1-111 G10
Adder
7.736
274744AC1-111 GEN8
Adder
7.736
944221AF1-090 GEN
Solar/Wind Harmer
5.66
276868AE1-113 GEN
Solar/Wind Harmer
1.928
276882AE2-255 GEN
Solar/Wind Harmer
1.124
926823AC1-168 GEN
Solar/Wind Harmer
1.627
971177AH1-047 GEN
Solar/Wind Harmer
5.86
971675AH1-338 GEN
Solar/Wind Harmer
3.702
957751AF2-069 GEN
Solar/Wind Harmer
0.313
971771AH1-392 GEN
Solar/Wind Harmer
9.483
971411AH1-196 GEN
Solar/Wind Harmer
14.224
971171AH1-044 GEN
Solar/Wind Harmer
18.922
274848CAMPGROVE;RU
Solar/Wind Harmer
0.002
970289AG2-191 GEN
Solar/Wind Harmer
1.796
247521TR3_G114
Solar/Wind Harmer
0.234
270246TR4_N_V150
Solar/Wind Harmer
0.041
24695305TIMB G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
970611AG2-400 GEN
Solar/Wind Harmer
7.456
970627AG2-408 GEN
Solar/Wind Harmer
2.237
270383AD1-128 GEN
Solar/Wind Harmer
0.005
964611AG1-324 GEN
Solar/Wind Harmer
0.555
270201AC2-176 GEN
Solar/Wind Harmer
0.001
970883AG2-550 GEN
Solar/Wind Harmer
6.873
970885AG2-551 GEN
Solar/Wind Harmer
2.291
964571AG1-320 GEN
Solar/Wind Harmer
6.134
970235AG2-159 GEN
Solar/Wind Harmer
3.809
970235AG2-159 GEN
Solar/Wind Harmer
2.185
970653AG2-424 GEN
Solar/Wind Harmer
2.907
970653AG2-424 GEN
Solar/Wind Harmer
1.506
274823ROCKFORD ;21
Adder
26.341
276612AE2-035 GEN
Solar/Wind Harmer
0.003
971681AH1-341 GEN
Solar/Wind Harmer
15.111
961011AF2-392 GEN
Solar/Wind Harmer
5.479
971619AH1-309 GEN
Solar/Wind Harmer
4.175
270071AF1-092 GEN
Solar/Wind Harmer
17.687
946321AF1-296 GEN
Solar/Wind Harmer
5.141
270594AE1-207 GEN
Solar/Wind Harmer
10.19
24725505WLD G2 C
Solar/Wind Harmer
0.002
24699105WLD G1 C
Solar/Wind Harmer
0.001
971549AH1-272 GEN
Solar/Wind Harmer
17.277
971609AH1-304 GEN
Solar/Wind Harmer
1.338
965101AG1-375 GEN
Solar/Wind Harmer
8.167
945581AF1-223 GEN
Solar/Wind Harmer
0.001
970115AG2-085 GEN
Solar/Wind Harmer
3.229
270240V3-007_GEN2
Solar/Wind Harmer
0.002
963791AG1-232 GEN
Solar/Wind Harmer
10.035
270024AE2-089 GEN
Solar/Wind Harmer
0.008
270543AE2-219 C
Solar/Wind Harmer
0.004
965041AG1-368 GEN
Solar/Wind Harmer
6.799
971029AG2-637 GEN
Solar/Wind Harmer
9.99
971673AH1-337 GEN
Solar/Wind Harmer
4.275
965051AG1-369 GEN
Solar/Wind Harmer
3.198
970455AG2-298 GEN
Solar/Wind Harmer
4.116
944201AF1-088_MTX
50/50
211.042
957141AF2-008_MTX
50/50
105.521
NYPJM->LTFIMP_NY
CLTF
2.584
LGEELTFEXP_LGEE->PJM
CLTF
8.153
WECLTFEXP_WEC->PJM
CLTF
5.142
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.945
AG2-052LTFEXP_AG2-052->PJM
LTF
0.335
AH1-155LTFEXP_AH1-155->PJM
LTF
0.503
LAGNLTFEXP_LAGN->PJM
CLTF
11.815
TVALTFEXP_TVA->PJM
CLTF
4.631
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.059
CBM West 1LTFEXP_CBM-W1->PJM
CBM
162.55
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.289
MECLTFEXP_MEC->PJM
CLTF
20.301
SIGELTFEXP_SIGE->PJM
CLTF
0.641
CBM West 2LTFEXP_CBM-W2->PJM
CBM
121.55

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P1-2_MP-500-007A_SRT-A


Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P1-2_MP-500-007A_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:131.92 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5002.28
MW Contribution:3.51
Bus #Bus NameTypeMW Contribution
270119AB2-067 GEN1
50/50
7.059
270120AB2-067 GEN2
50/50
7.059
24318905MLG2
50/50
7.071
270471AD2-092_GEN
Solar/Wind Harmer
0.006
942861AE2-305 GEN
Solar/Wind Harmer
6.335
970077AG2-063 GEN
Solar/Wind Harmer
4.631
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
938701AE1-092 GEN
Solar/Wind Harmer
12.917
971655AH1-328 GEN
Solar/Wind Harmer
2.854
964601AG1-323 GEN
Solar/Wind Harmer
3.215
964601AG1-323 GEN
Solar/Wind Harmer
2.143
270518AE2-148 GEN
Solar/Wind Harmer
0.691
972269AH1-719 GEN
Adder
2.584
972159AH1-661 GEN
Adder
1.118
253378AE2-206_GEN
Solar/Wind Harmer
0.004
276820AF1-078_GEN
Solar/Wind Harmer
0.002
970329AG2-216 GEN
Solar/Wind Harmer
3.354
971199AH1-059 GEN
Solar/Wind Harmer
3.09
241960AC2-195 GEN
Solar/Wind Harmer
0.006
25326509SID D
Adder
1.451
971073AG2-665 GEN
Solar/Wind Harmer
6.898
25326109MON D
Adder
1.443
25322209TAIT E
Adder
10.642
25322209TAIT E
Adder
10.403
971201AH1-060 GEN
Solar/Wind Harmer
1.52
253370AE2-315 SEC1
Adder
2.182
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
246938BC-WTG3
Solar/Wind Harmer
0.273
246937BC-WTG2
Solar/Wind Harmer
0.305
971231AH1-075 GEN
Solar/Wind Harmer
0.861
253317AC1-085 GEN4
Solar/Wind Harmer
0.005
970611AG2-400 GEN
Solar/Wind Harmer
7.488
970627AG2-408 GEN
Solar/Wind Harmer
2.246
270007AE1-245 C
Solar/Wind Harmer
0.002
962581AG1-107 GEN
Solar/Wind Harmer
0.002
25183208HLCRTG
Solar/Wind Harmer
0.012
944541AF1-119 GEN
Solar/Wind Harmer
0.497
960971AF2-388 GEN
Solar/Wind Harmer
4.347
970623AG2-406 GEN
Solar/Wind Harmer
1.356
942221AE2-234 GEN
Solar/Wind Harmer
0.037
252519AF1-045_GEN
Solar/Wind Harmer
6.44
252516AE2-318_GEN
Solar/Wind Harmer
5.712
247621Y3-024
Adder
0.255
970883AG2-550 GEN
Solar/Wind Harmer
7.389
970885AG2-551 GEN
Solar/Wind Harmer
2.463
270201AC2-176 GEN
Solar/Wind Harmer
0.001
25194408D.CRK1
Adder
8.004
25194508D.CRK3
Adder
1.496
970621AG2-405 GEN
Solar/Wind Harmer
1.351
964611AG1-324 GEN
Solar/Wind Harmer
0.553
252509AD1-136 GEN
Solar/Wind Harmer
0.037
970321AG2-212 GEN
Solar/Wind Harmer
3.191
270599AE1-208 GEN
Solar/Wind Harmer
6.737
270031AE2-169
Solar/Wind Harmer
4.042
270186AC1-089 GEN
Solar/Wind Harmer
0.004
270383AD1-128 GEN
Solar/Wind Harmer
0.004
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
970825AG2-519 GEN
Solar/Wind Harmer
8.127
247620Y3-023
Adder
0.484
960441AF2-335 GEN
Solar/Wind Harmer
7.33
270216AD2-079_GEN
Solar/Wind Harmer
0.001
971613AH1-306 GEN
Solar/Wind Harmer
3.512
24728805RICHG1
Adder
3.964
24728905RICHG2
Adder
3.964
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
14.589
961051AF2-396 GEN
Solar/Wind Harmer
9.726
270526AF1-158 GEN
Solar/Wind Harmer
0.009
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
9.095
965791AG1-447 GEN
Solar/Wind Harmer
6.67
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
970239AG2-162 GEN
Solar/Wind Harmer
1.797
274770LINCOLN ;1U
Adder
8.676
274771LINCOLN ;2U
Adder
8.676
966841AG1-555 GEN
Solar/Wind Harmer
0.81
274808UNIV PK N;4U
Adder
5.117
274803UNIV PARK;6U
Adder
5.97
274888KELLY CRK;1U
Solar/Wind Harmer
0.419
274887GEN-1.85
Solar/Wind Harmer
0.188
276843GEN-1.7
Solar/Wind Harmer
0.231
958011AF2-095 GEN
Solar/Wind Harmer
10.284
972259AH1-714 GEN
Adder
19.507
274674JOLIET 9 ;6U
Adder
15.704
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
970241AG2-163 GEN
Solar/Wind Harmer
4.144
958481AF2-142 GEN
Solar/Wind Harmer
10.621
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.958
971573AH1-285 GEN
Solar/Wind Harmer
1.319
274696ROCKY RD ;4P
Adder
11.537
274695ROCKY RD ;2P
Adder
11.271
274693ROCKY RD ;1P
Adder
11.16
274697ROCKY RD ;3P
Adder
3.062
958491AF2-143 GEN
Solar/Wind Harmer
10.588
274879MINONK ;1U
Solar/Wind Harmer
0.297
23585401KL_K28_T16
Solar/Wind Helper
1.482
238120AE2-309 GEN
Solar/Wind Helper
0.525
238175AF1-290_GEN
Solar/Wind Helper
0.153
238169AE2-226 GEN1
Solar/Wind Helper
0.701
238170AE2-226 GEN2
Solar/Wind Helper
0.701
235020AA1-095 C
Solar/Wind Helper
0.053
23777901MDS_W4-102
Solar/Wind Helper
0.177
237002AB1-128_GEN
Solar/Wind Helper
0.443
237034AC2-136 C
Solar/Wind Helper
0.227
235063AE1-101 C2
Solar/Wind Helper
1.659
237001AB1-127_GEN
Solar/Wind Helper
0.442
23777801MSM_W1-116
Solar/Wind Helper
0.114
237025AB1-124 C
Solar/Wind Helper
0.164
237006AB1-125 GEN
Solar/Wind Helper
0.123
226929AD2-058 GEN
Solar/Wind Helper
0.099
205916AD1-020 GEN
Solar/Wind Helper
1.713
20390526W1-045 C
Solar/Wind Helper
0.35
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
233987AB2-037 GEN
Solar/Wind Helper
2.342
233933AB2-153 GEN
Solar/Wind Helper
0.232
233944AB2-135 GEN
Solar/Wind Helper
0.588
232424Y1-079 C
Solar/Wind Helper
0.116
234036AF2-325 C
Solar/Wind Helper
0.042
233946AB2-136 GEN
Solar/Wind Helper
0.568
233901CHERRYDALE C
Solar/Wind Helper
0.232
232408W1-005 C
Solar/Wind Helper
0.507
232410W1-006 C
Solar/Wind Helper
0.507
233939AC1-091 C
Solar/Wind Helper
0.35
233970AC1-092 C
Solar/Wind Helper
0.35
315651AD1-115 GEN
Solar/Wind Helper
0.785
316447AC1-158 HLD
Solar/Wind Helper
2.845
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.04
219921AF1-264
Solar/Wind Helper
0.051
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.082
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.19
20716928W4-060COL
Solar/Wind Helper
0.051
218440SUMMTASSOC C
Solar/Wind Helper
0.016
20673828FLE_V3-070
Solar/Wind Helper
0.09
207442AE1-156 GEN
Solar/Wind Helper
0.326
20676128MHD_W3-029
Solar/Wind Helper
0.096
20671828STAW2-080
Solar/Wind Helper
0.027
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
207471AF2-354 C
Solar/Wind Helper
0.168
20674928WA_W3-044
Solar/Wind Helper
0.098
20676228FRD_X1-012
Solar/Wind Helper
0.092
964851AG1-348 GEN
Solar/Wind Helper
0.081
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.074
211065PSPA IPP
Solar/Wind Helper
0.151
211065PSPA IPP
Solar/Wind Helper
0.151
962771AG1-126 GEN
Solar/Wind Harmer
34.524
972239AH1-704 GEN
Adder
2.689
270054AF2-122 C O1
Solar/Wind Harmer
0.007
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
5.077
270520AE2-214 GEN
Solar/Wind Harmer
0.013
270284AF1-227 GEN1
Solar/Wind Harmer
0.011
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
253383AE2-342_GEN
Solar/Wind Harmer
0.003
241973AD2-163_GEN1
Solar/Wind Harmer
0.006
945631AF1-228 GEN
Solar/Wind Harmer
0
943861AF1-054 GEN
Solar/Wind Harmer
3.127
943851AF1-053 GEN
Solar/Wind Harmer
2.166
270156DARBY CT1
Adder
10.409
270157DARBY CT2
Adder
10.383
270158DARBY CT3
Adder
10.218
970689AG2-444 GEN
Solar/Wind Harmer
16.436
270578AF1-285 GEN2
Solar/Wind Harmer
0.536
270432AC2-029 GEN
Solar/Wind Harmer
3.553
940611AE2-048 GEN
Solar/Wind Harmer
19.602
941391AE2-136 GEN
Solar/Wind Harmer
11.042
270302AB2-170 GEN
Solar/Wind Harmer
0.005
270317AD1-130_GEN
Solar/Wind Harmer
0.011
971653AH1-327 GEN
Solar/Wind Harmer
1.117
270269AC2-059
Solar/Wind Harmer
0.005
241972AD1-140 GEN
Solar/Wind Harmer
0.854
970179AG2-119 GEN
Solar/Wind Harmer
6.883
270340AC2-060 GEN
Solar/Wind Harmer
0.009
970879AG2-548 GEN
Solar/Wind Harmer
6.898
253372AE2-315 SEC3
Adder
2.063
253372AE2-315 SEC3
Adder
2.063
25306009OHH W.
Adder
3.13
253349AC2-067 GEN
Solar/Wind Harmer
2.381
253400AC2-068 GEN
Solar/Wind Harmer
0.958
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
0.953
965051AG1-369 GEN
Solar/Wind Harmer
3.739
965041AG1-368 GEN
Solar/Wind Harmer
7.471
247607V1-011 GEN
Solar/Wind Harmer
0.001
971567AH1-282 GEN
Solar/Wind Harmer
11.206
971989AH1-539 GEN
Solar/Wind Harmer
3.215
963791AG1-232 GEN
Solar/Wind Harmer
10.044
24729505KEY G4
Adder
6.919
270071AF1-092 GEN
Solar/Wind Harmer
14.245
971985AH1-537 GEN
Solar/Wind Harmer
2.206
270024AE2-089 GEN
Solar/Wind Harmer
0.008
270367AC2-061_GEN
Solar/Wind Harmer
0.006
965101AG1-375 GEN
Solar/Wind Harmer
7.401
971673AH1-337 GEN
Solar/Wind Harmer
4.804
252524AE2-267 GEN
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
9.344
25196308WSDLE2
Adder
9.263
25196208WSDLE1
Adder
9.24
25196708WSDLE6
Adder
9.217
25196508WSDLE4
Adder
8.984
971029AG2-637 GEN
Solar/Wind Harmer
11.085
270543AE2-219 C
Solar/Wind Harmer
0.004
945581AF1-223 GEN
Solar/Wind Harmer
0.001
270297AD1-101 GEN
Solar/Wind Harmer
0.002
971347AH1-153 GEN
Solar/Wind Harmer
11.025
971609AH1-304 GEN
Solar/Wind Harmer
1.2
270240V3-007_GEN2
Solar/Wind Harmer
0.002
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
970115AG2-085 GEN
Solar/Wind Harmer
2.932
270594AE1-207 GEN
Solar/Wind Harmer
8.194
970289AG2-191 GEN
Solar/Wind Harmer
1.389
971771AH1-392 GEN
Solar/Wind Harmer
7.306
971619AH1-309 GEN
Solar/Wind Harmer
3.285
971769AH1-391 GEN
Solar/Wind Harmer
8.134
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
25196108MFTGT2
Adder
1.599
25196108MFTGT2
Adder
1.484
270536AF1-215 GEN2
Solar/Wind Harmer
0.009
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
4.302
971549AH1-272 GEN
Solar/Wind Harmer
14.865
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
8.676
274776LINCOLN ;7U
Adder
8.676
274777LINCOLN ;8U
Adder
8.676
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
274814UNIV PK N;0U
Adder
5.184
274807UNIV PK N;3U
Adder
5.173
274805UNIV PK N;1U
Adder
5.15
274811UNIV PK N;7U
Adder
5.139
972037AH1-567 GEN1
Adder
0.187
960591AF2-350 GEN
Solar/Wind Harmer
7.141
274827FISK ;RP
Adder
7.941
972227AH1-698 GEN1
Adder
2.669
963841AG1-237 GEN
Solar/Wind Harmer
3.09
972163AH1-664 GEN
Solar/Wind Harmer
7.933
972165AH1-665 GEN
Solar/Wind Harmer
6.354
274687WILL CNTY;4U
Adder
28.523
274687WILL CNTY;4U
Adder
28.523
274675JOLIET 29;7U
Adder
31.303
274675JOLIET 29;7U
Adder
30.185
274731ELWOOD EC;2P
Adder
16.768
274733ELWOOD EC;3P
Adder
16.768
274735ELWOOD EC;4P
Adder
16.768
274728ELWOOD EC;5P
Adder
16.768
970833AG2-524 GEN
Solar/Wind Harmer
7.824
970833AG2-524 GEN
Solar/Wind Harmer
5.216
274746AC1-111 G10
Adder
5.679
274744AC1-111 GEN8
Adder
5.679
972203AH1-686 GEN
Adder
2.338
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
276868AE1-113 GEN
Solar/Wind Harmer
1.414
276882AE2-255 GEN
Solar/Wind Harmer
0.824
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238126S14_GEN_1
Solar/Wind Helper
0.827
238152AF2-075_GEN
Solar/Wind Helper
0.707
238208AF1-136 C
Solar/Wind Helper
0.22
23546401DTGZ2-030
Solar/Wind Helper
0.089
237085AD2-009_GEN
Solar/Wind Helper
1.649
3138216PACIFIC
Solar/Wind Helper
0.044
316411AF1-147_GEN1
Solar/Wind Helper
0.888
316415AF1-147_GEN2
Solar/Wind Helper
0.888
23750501ELLIOTTS
Solar/Wind Helper
0.638
959381AF2-229 GEN
Solar/Wind Helper
0.357
3141426STAFORD
Solar/Wind Helper
0.052
960921AF2-383 GEN
Solar/Wind Helper
0.364
205943AE1-185 GEN
Solar/Wind Helper
0.509
205932AD2-116_GEN
Solar/Wind Helper
0.509
205956AE1-196_GEN
Solar/Wind Helper
0.509
233935AB2-179 C
Solar/Wind Helper
1.269
232436AB1-176 C
Solar/Wind Helper
0.044
233923SMA
Solar/Wind Helper
0.958
233990AG1-397 GEN
Solar/Wind Helper
0.27
232432Z2-076 GEN
Solar/Wind Helper
0.067
234033AF1-007_GEN
Solar/Wind Helper
7.02
964001AG1-254 GEN
Solar/Wind Helper
0.955
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.115
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.08
203975AE1-071-GEN
Solar/Wind Helper
2.498
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.29
219620RIDERU C
Solar/Wind Helper
0.001
316164AC1-076 GEN
Solar/Wind Helper
1.096
20675528CPH_W2-050
Solar/Wind Helper
0.087
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
218524CNTRALGAS1 C
Solar/Wind Helper
0.16
966261AG1-495 GEN
Solar/Wind Helper
0.081
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20675928HOL_W4-097
Solar/Wind Helper
0.05
207484AF2-139 C O1
Solar/Wind Helper
0.084
20674828DL_W4-046
Solar/Wind Helper
0.008
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.136
20675128HRM_W1-127
Solar/Wind Helper
0.029
209116AE2-175 GEN
Solar/Wind Helper
1.778
24318805MLG1
50/50
10.095
23559001PLEAS1
50/50
6.1
270051AF1-062 GEN
50/50
11.821
270475AD2-096_GEN
50/50
7.141
970153AG2-106 GEN
Solar/Wind Harmer
22.046
961921AG1-034 GEN
Solar/Wind Harmer
7.615
241955AC1-078 GEN
Solar/Wind Harmer
0.007
24721905FLATG4
Adder
23.918
241974AD2-163_GEN2
Solar/Wind Harmer
0.006
942051AE2-217 GEN
Solar/Wind Harmer
14.671
970605AG2-385 GEN
Solar/Wind Harmer
4.899
270391AF1-285 GEN3
Solar/Wind Harmer
0.536
253338AC1-165 GEN
Solar/Wind Harmer
0.003
253333AC1-068 GEN
Solar/Wind Harmer
0.012
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270273AD2-016 GEN
Solar/Wind Harmer
0.821
972173AH1-669 GEN
Solar/Wind Harmer
3.952
270291AC1-194 GEN
Solar/Wind Harmer
6.106
253415AE1-040 GEN
Solar/Wind Harmer
0.003
270512AE1-227 GEN2
Solar/Wind Harmer
1.963
970065AG2-057 GEN
Solar/Wind Harmer
0.76
253370AE2-315 SEC1
Adder
2.182
253371AE2-315 SEC2
Adder
2.063
253406AD2-031_GEN
Solar/Wind Harmer
0.563
970191AG2-125 GEN
Solar/Wind Harmer
1.945
270491AE1-102 GEN2
Solar/Wind Harmer
0.979
270377AD1-106 GEN
Solar/Wind Harmer
2.855
971191AH1-055 GEN
Solar/Wind Harmer
19.26
253316AC1-085 GEN3
Solar/Wind Harmer
0.005
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
9.749
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.048
959331AF2-224 GEN
Solar/Wind Harmer
5.242
965021AG1-366 GEN
Solar/Wind Harmer
2.496
270588AE1-091_GEN
Solar/Wind Harmer
5.845
944531AF1-118 GEN
Solar/Wind Harmer
33.395
270043AE2-236 GEN
Solar/Wind Harmer
4.777
270258AD1-119 GEN
Solar/Wind Harmer
0.002
971617AH1-308 GEN
Solar/Wind Harmer
6.173
25196608WSDLE5
Adder
9.077
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
252510AF1-249 C
Solar/Wind Harmer
0.057
957741AF2-068 GEN
Solar/Wind Harmer
11.081
25194608D.CRK4
Adder
1.74
270222AC2-111 GEN
Solar/Wind Harmer
3.739
970031AG2-029 GEN
Solar/Wind Harmer
4.795
270404AC1-167 GEN
Solar/Wind Harmer
0.003
970513AG2-328 GEN
Solar/Wind Harmer
3.191
970517AG2-330 GEN
Solar/Wind Harmer
19.146
970349AG2-230 GEN
Solar/Wind Harmer
11.025
946031AF1-268 GEN
Solar/Wind Harmer
6.992
958821AF2-173 GEN
Solar/Wind Harmer
10.273
270004AE1-209 GEN
Solar/Wind Harmer
1.59
270437AC2-090 C
Solar/Wind Harmer
0.003
247643Z2-116 C
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.804
970291AG2-192 GEN
Solar/Wind Harmer
0.731
247642Z2-115 C
Solar/Wind Harmer
0.003
945111AF1-176 GEN
Solar/Wind Harmer
5.919
24642205MAYFLWER
Adder
0.665
25196008MFTGT1
Adder
1.405
270356AE2-297 GEN
Solar/Wind Harmer
0.01
24441205WTRV SLR C
Solar/Wind Harmer
0
247604X1-042
Adder
0.433
270535AF1-215 GEN1
Solar/Wind Harmer
0.009
964401AG1-302 GEN
Solar/Wind Harmer
0.001
970217AG2-149 GEN
Solar/Wind Harmer
6.268
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
7.196
970243AG2-164 GEN
Solar/Wind Harmer
4.205
970519AG2-331 GEN
Solar/Wind Harmer
18.687
970699AG2-449 GEN
Solar/Wind Harmer
1.797
274752CRETE EC ;2U
Adder
8.477
274753CRETE EC ;3U
Adder
8.477
958171AF2-111 GEN
Solar/Wind Harmer
17.94
274772LINCOLN ;3U
Adder
8.676
274724RIVER EC ;11
Adder
18.203
972167AH1-666 GEN
Solar/Wind Harmer
5.717
24728705AND G3
Adder
8.214
274802UNIV PARK;5U
Adder
5.97
24728505AND G1
Adder
3.927
276806AD2-047 C O1
Solar/Wind Harmer
4.047
970941AG2-585 GEN
Solar/Wind Harmer
8.927
274826FISK ;BP
Adder
11.205
274800UNIV PARK;3U
Adder
5.966
972038AH1-567 GEN2
Adder
0.373
972228AH1-698 GEN2
Adder
3.79
276897AD1-100 C
Solar/Wind Harmer
0.009
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
970707AG2-453 GEN
Solar/Wind Harmer
23.303
274676JOLIET 29;8U
Adder
30.185
276893AG1-478 C
Solar/Wind Harmer
0.282
274729ELWOOD EC;1P
Adder
16.768
274730ELWOOD EC;6P
Adder
16.768
274734ELWOOD EC;8P
Adder
16.768
274736ELWOOD EC;9P
Adder
16.768
943121AE2-341 GEN
Solar/Wind Harmer
11.888
943591AF1-030 GEN
Solar/Wind Harmer
7.906
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
270541AE2-072 C
Solar/Wind Harmer
0.009
274682WAUKEGAN ;7U
Adder
9.728
276805AD2-038 GEN
Solar/Wind Harmer
0.002
964991AG1-363 GEN
Solar/Wind Helper
5.136
316097T157 G90
Solar/Wind Helper
1.504
23750701CROSSCHOOL
Solar/Wind Helper
1.502
238118U2-030_1
Solar/Wind Helper
0.341
238127S14_GEN_2
Solar/Wind Helper
0.827
238148AE2-230_GEN2
Solar/Wind Helper
0.497
237080AD1-060 GEN
Solar/Wind Helper
0.342
237038AE2-054 C
Solar/Wind Helper
0.272
235062AE1-101 C1
Solar/Wind Helper
1.659
23779801AA1-109
Solar/Wind Helper
0.193
237048AF1-022 C
Solar/Wind Helper
0.177
223401AF1-299 GEN
Solar/Wind Helper
0.367
316006AB2-029 C
Solar/Wind Helper
0.117
966131AG1-482 GEN
Solar/Wind Helper
0.137
233930AB2-032 GEN
Solar/Wind Helper
0.381
233915AB1-141 GEN
Solar/Wind Helper
0.502
232422X3-066 FULL
Solar/Wind Helper
0.114
232428Y3-058 C
Solar/Wind Helper
0.338
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
233998TM1NIN_3.36
Solar/Wind Helper
0.261
232404W1-003 C
Solar/Wind Helper
0.507
232434Z2-077 GEN
Solar/Wind Helper
0.127
233954AC2-188 GEN
Solar/Wind Helper
0.232
233950AC2-186 GEN
Solar/Wind Helper
0.116
233972AC1-094 C
Solar/Wind Helper
0.302
316045AC1-158 PL2
Solar/Wind Helper
4.138
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.23
228728W1-130C
Solar/Wind Helper
0.054
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219904AC1-010 C
Solar/Wind Helper
0.06
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.131
20720728JCB_W1-129
Solar/Wind Helper
0.057
316254AC1-120 GEN1
Solar/Wind Helper
1.059
207445AB1-138_GEN
Solar/Wind Helper
0.104
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.13
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.31
20715228NPK_W1-113
Solar/Wind Helper
0.078
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.495
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
207437AD2-070 GEN
Solar/Wind Helper
0.138
207518AF1-320_GEN
Solar/Wind Helper
1.571
20671928W4-073
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.029
270166AC1-044 GEN3
50/50
7.059
23559101PLEAS2
50/50
6.1
962761AG1-125 GEN
Solar/Wind Harmer
34.524
970149AG2-104 GEN
Solar/Wind Harmer
37.287
970155AG2-107 GEN
Solar/Wind Harmer
22.046
270349AD2-093_GEN
Solar/Wind Harmer
0.006
24721705FLATG2
Adder
23.918
270159DARBY CT4
Adder
10.243
970593AG2-378 GEN
Solar/Wind Harmer
1.812
270223U2-072_GEN1
Solar/Wind Harmer
0.001
253343AC1-166 GEN
Solar/Wind Harmer
0.003
253325AC1-069 GEN
Solar/Wind Harmer
0.012
270462AD2-086
Solar/Wind Harmer
0.017
971995AH1-542 GEN
Solar/Wind Harmer
2.906
270263AC1-001 GEN
Solar/Wind Harmer
0.786
270510AE1-227 GEN1
Solar/Wind Harmer
1.963
25326309TAIT D
Adder
1.196
241813AF1-122_GEN
Solar/Wind Harmer
3.405
960071AF2-298 GEN
Solar/Wind Harmer
3.786
253370AE2-315 SEC1
Adder
2.182
253371AE2-315 SEC2
Adder
2.063
927014AC1-188 GEN
Solar/Wind Harmer
0.005
246936BC-WTG1
Solar/Wind Harmer
0.305
270489AE1-102 GEN1
Solar/Wind Harmer
0.979
965421AG1-410 GEN
Solar/Wind Harmer
22.57
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.499
247521TR3_G114
Solar/Wind Harmer
0.273
270246TR4_N_V150
Solar/Wind Harmer
0.048
965011AG1-365 GEN
Solar/Wind Harmer
7.488
24695305TIMB G C
Solar/Wind Harmer
0.002
965651AG1-433 GEN
Solar/Wind Harmer
2.174
958861AF2-177 GEN
Solar/Wind Harmer
3.207
247536S-71 GEN
Solar/Wind Harmer
0.297
25194608D.CRK4
Adder
1.74
945371AF1-202 GEN
Solar/Wind Harmer
0.001
252507AC2-088 GEN
Solar/Wind Harmer
0.335
270063AE2-323 C
Solar/Wind Harmer
0.006
970245AG2-165 GEN
Solar/Wind Harmer
3.191
970947AG2-589 GEN
Solar/Wind Harmer
0.245
270005AE1-210 C O1
Solar/Wind Harmer
1.59
965031AG1-367 GEN
Solar/Wind Harmer
7.338
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.378
970825AG2-519 GEN
Solar/Wind Harmer
2.603
25196808ZIMRHP
Adder
79.729
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
944231AF1-091 GEN
Solar/Wind Harmer
1.953
24639705ELKHART HY
Adder
0.161
270032AE2-172
Solar/Wind Harmer
4.877
970291AG2-192 GEN
Solar/Wind Harmer
0.95
945111AF1-176 GEN
Solar/Wind Harmer
13.03
270505AE1-170 C O1
Solar/Wind Harmer
7.665
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.805
276903AD2-071 C
Solar/Wind Harmer
8.137
25196008MFTGT1
Adder
1.45
247522W1-056 GEN
Solar/Wind Harmer
0.001
970773AG2-487 GEN
Solar/Wind Harmer
1.284
970373AG2-245 GEN
Solar/Wind Harmer
15.247
270055AF2-134 C O1
Solar/Wind Harmer
0.006
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.41
970515AG2-329 GEN
Solar/Wind Harmer
18.805
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
9.032
24791305MDL-5G
Solar/Wind Harmer
0.001
970333AG2-219 GEN
Solar/Wind Harmer
5.139
274751CRETE EC ;1U
Adder
8.477
274754CRETE EC ;4U
Adder
8.477
274773LINCOLN ;4U
Adder
8.676
274774LINCOLN ;5U
Adder
8.676
274723RIVER EC ;12
Adder
18.418
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
5.139
24728605AND G2
Adder
3.927
276776AD2-060 GEN
Solar/Wind Harmer
0.746
945681AF1-233 GEN
Solar/Wind Harmer
13.461
274801UNIV PARK;4U
Adder
5.966
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
31.303
274732ELWOOD EC;7P
Adder
16.768
274674JOLIET 9 ;6U
Adder
15.704
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
963741AG1-226 GEN
Solar/Wind Harmer
16.815
274745AC1-111 GEN9
Adder
5.679
939401AE1-172 GEN
Solar/Wind Harmer
5.301
276691AA1-018 GEN1
Solar/Wind Harmer
0.858
970091AG2-072 GEN
Adder
77.629
276901AD2-066 C O1
Solar/Wind Harmer
0.007
316095T157 G97
Solar/Wind Helper
1.504
23583801GRNGAP
Solar/Wind Helper
5.601
238185AF2-356 C
Solar/Wind Helper
2.646
238108AE1-109 GEN1
Solar/Wind Helper
0.114
235054AD2-180 GEN
Solar/Wind Helper
2.03
235531U2-073 GEN
Solar/Wind Helper
3.282
238117U2-030
Solar/Wind Helper
0.341
238147AE2-230_GEN1
Solar/Wind Helper
0.495
238149AF1-291A_GEN
Solar/Wind Helper
0.141
23751201ROTHROCK
Solar/Wind Helper
0.824
237061AD1-155 GEN
Solar/Wind Helper
0.053
23562501BACKB
Solar/Wind Helper
1.007
238221AF1-254 C O1
Solar/Wind Helper
0.274
235067AD1-061 GEN
Solar/Wind Helper
0.496
23751101LEADS_P59
Solar/Wind Helper
1.404
237030AB1-096 C
Solar/Wind Helper
0.071
3141196NOKESVL
Solar/Wind Helper
1.032
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.346
223402AF1-300 C
Solar/Wind Helper
0.367
205917AD1-020 ES
Solar/Wind Helper
0.368
233918AB1-142 GEN
Solar/Wind Helper
0.502
233982AB2-133 GEN
Solar/Wind Helper
0.358
233994AC2-023 GEN
Solar/Wind Helper
0.961
233996TM1833_GEN
Solar/Wind Helper
0.261
233997TMININ_4.2
Solar/Wind Helper
0.261
232406W1-004 FULL
Solar/Wind Helper
0.507
233940AF2-379 C
Solar/Wind Helper
0.062
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.232
233971AC1-093 C
Solar/Wind Helper
0.357
316044AC1-158 PL1
Solar/Wind Helper
1.293
316450AC1-158 RIC
Solar/Wind Helper
0.345
230430AE1-229_GEN
Solar/Wind Helper
3.372
230415AB2-049 C
Solar/Wind Helper
0.03
228729W2-030 C
Solar/Wind Helper
0.11
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.15
219291REEVESSOUT C
Solar/Wind Helper
0.011
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
219348LDSOLAR C
Solar/Wind Helper
0.114
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.063
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.353
219276PARKLANDSO C
Solar/Wind Helper
0.089
20714528FRN_Y2-051
Solar/Wind Helper
0.057
20720528MAN_W1-024
Solar/Wind Helper
0.028
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.027
219908AB1-139 C
Solar/Wind Helper
0.074
219249CENTRALDIV C
Solar/Wind Helper
0.01
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.089
971997AH1-543 GEN
Solar/Wind Harmer
2.724
NYPJM->LTFIMP_NY
CLTF
4.797
LGEELTFEXP_LGEE->PJM
CLTF
6.749
WECLTFEXP_WEC->PJM
CLTF
3.825
AG2-052LTFEXP_AG2-052->PJM
LTF
0.24
AH1-155LTFEXP_AH1-155->PJM
LTF
0.359
LAGNLTFEXP_LAGN->PJM
CLTF
14.837
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.802
TVALTFEXP_TVA->PJM
CLTF
7.293
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.078
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.1
MECLTFEXP_MEC->PJM
CLTF
15.901
SIGELTFEXP_SIGE->PJM
CLTF
0.505
CPLELTFEXP_CPLE->PJM
CLTF
0.624
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.816

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P1-2_MP-500-008A_SRT-SL


Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P1-2_MP-500-008A_SRT-SL
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:125.38 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4754.33
MW Contribution:3.38
Bus #Bus NameTypeMW Contribution
972239AH1-704 GEN
50/50
2.78
962771AG1-126 GEN
Solar/Wind Harmer
33.269
270459AD2-067 GEN
Solar/Wind Harmer
0
270054AF2-122 C O1
Solar/Wind Harmer
0.007
961821AG1-024 GEN
Solar/Wind Harmer
4.91
270520AE2-214 GEN
Solar/Wind Harmer
0.013
270284AF1-227 GEN1
Solar/Wind Harmer
0.01
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
253383AE2-342_GEN
Solar/Wind Harmer
0.003
241973AD2-163_GEN1
Solar/Wind Harmer
0.006
945631AF1-228 GEN
Solar/Wind Harmer
0
943861AF1-054 GEN
Solar/Wind Harmer
3.02
943851AF1-053 GEN
Solar/Wind Harmer
2.092
270156DARBY CT1
Adder
10.05
270157DARBY CT2
Adder
10.026
270158DARBY CT3
Adder
9.866
270578AF1-285 GEN2
Solar/Wind Harmer
0.518
970689AG2-444 GEN
Solar/Wind Harmer
15.861
270432AC2-029 GEN
Solar/Wind Harmer
3.428
940611AE2-048 GEN
Solar/Wind Harmer
18.967
941391AE2-136 GEN
Solar/Wind Harmer
10.684
270302AB2-170 GEN
Solar/Wind Harmer
0.005
270317AD1-130_GEN
Solar/Wind Harmer
0.011
971653AH1-327 GEN
Solar/Wind Harmer
1.08
270269AC2-059
Solar/Wind Harmer
0.004
241972AD1-140 GEN
Solar/Wind Harmer
0.824
970179AG2-119 GEN
Solar/Wind Harmer
6.658
270340AC2-060 GEN
Solar/Wind Harmer
0.009
970879AG2-548 GEN
Solar/Wind Harmer
6.645
253372AE2-315 SEC3
Adder
1.989
253372AE2-315 SEC3
Adder
1.989
25306009OHH W.
Adder
3.018
253349AC2-067 GEN
Solar/Wind Harmer
2.296
253400AC2-068 GEN
Solar/Wind Harmer
0.923
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
0.92
965051AG1-369 GEN
Solar/Wind Harmer
3.609
971567AH1-282 GEN
Solar/Wind Harmer
10.843
247607V1-011 GEN
Solar/Wind Harmer
0.001
965041AG1-368 GEN
Solar/Wind Harmer
7.21
971989AH1-539 GEN
Solar/Wind Harmer
3.109
963791AG1-232 GEN
Solar/Wind Harmer
9.689
24729505KEY G4
Adder
6.671
270071AF1-092 GEN
Solar/Wind Harmer
13.737
270024AE2-089 GEN
Solar/Wind Harmer
0.008
971985AH1-537 GEN
Solar/Wind Harmer
2.123
965101AG1-375 GEN
Solar/Wind Harmer
7.135
270297AD1-101 GEN
Solar/Wind Harmer
0.002
270367AC2-061_GEN
Solar/Wind Harmer
0.006
971673AH1-337 GEN
Solar/Wind Harmer
4.631
971029AG2-637 GEN
Solar/Wind Harmer
10.686
270543AE2-219 C
Solar/Wind Harmer
0.004
252524AE2-267 GEN
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
9.002
25196308WSDLE2
Adder
8.924
25196208WSDLE1
Adder
8.902
25196708WSDLE6
Adder
8.879
25196508WSDLE4
Adder
8.656
945581AF1-223 GEN
Solar/Wind Harmer
0.001
971347AH1-153 GEN
Solar/Wind Harmer
10.632
971609AH1-304 GEN
Solar/Wind Harmer
1.157
270240V3-007_GEN2
Solar/Wind Harmer
0.002
970115AG2-085 GEN
Solar/Wind Harmer
2.826
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
270594AE1-207 GEN
Solar/Wind Harmer
7.898
971771AH1-392 GEN
Solar/Wind Harmer
7.046
970289AG2-191 GEN
Solar/Wind Harmer
1.339
971619AH1-309 GEN
Solar/Wind Harmer
3.169
971769AH1-391 GEN
Solar/Wind Harmer
7.844
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
25196108MFTGT2
Adder
1.54
25196108MFTGT2
Adder
1.43
270536AF1-215 GEN2
Solar/Wind Harmer
0.009
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
4.146
971549AH1-272 GEN
Solar/Wind Harmer
14.344
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
8.364
274776LINCOLN ;7U
Adder
8.364
270166AC1-044 GEN3
50/50
6.869
24318805MLG1
50/50
9.842
23559001PLEAS1
50/50
5.385
270051AF1-062 GEN
50/50
11.434
970153AG2-106 GEN
Solar/Wind Harmer
21.245
961921AG1-034 GEN
Solar/Wind Harmer
7.364
241955AC1-078 GEN
Solar/Wind Harmer
0.007
241974AD2-163_GEN2
Solar/Wind Harmer
0.006
942051AE2-217 GEN
Solar/Wind Harmer
14.169
24721905FLATG4
Adder
22.865
970605AG2-385 GEN
Solar/Wind Harmer
4.731
270391AF1-285 GEN3
Solar/Wind Harmer
0.518
253338AC1-165 GEN
Solar/Wind Harmer
0.003
253333AC1-068 GEN
Solar/Wind Harmer
0.012
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270273AD2-016 GEN
Solar/Wind Harmer
0.792
972173AH1-669 GEN
Solar/Wind Harmer
3.811
270512AE1-227 GEN2
Solar/Wind Harmer
1.904
270291AC1-194 GEN
Solar/Wind Harmer
5.884
253415AE1-040 GEN
Solar/Wind Harmer
0.003
970065AG2-057 GEN
Solar/Wind Harmer
0.735
253370AE2-315 SEC1
Adder
2.103
253371AE2-315 SEC2
Adder
1.989
970191AG2-125 GEN
Solar/Wind Harmer
1.876
253406AD2-031_GEN
Solar/Wind Harmer
0.543
270491AE1-102 GEN2
Solar/Wind Harmer
0.945
270377AD1-106 GEN
Solar/Wind Harmer
2.761
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.047
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
9.394
959331AF2-224 GEN
Solar/Wind Harmer
5.057
965021AG1-366 GEN
Solar/Wind Harmer
2.408
270588AE1-091_GEN
Solar/Wind Harmer
5.649
971191AH1-055 GEN
Solar/Wind Harmer
18.515
944531AF1-118 GEN
Solar/Wind Harmer
32.203
270043AE2-236 GEN
Solar/Wind Harmer
4.607
270258AD1-119 GEN
Solar/Wind Harmer
0.002
971617AH1-308 GEN
Solar/Wind Harmer
5.953
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
10.684
270404AC1-167 GEN
Solar/Wind Harmer
0.003
25196608WSDLE5
Adder
8.745
252510AF1-249 C
Solar/Wind Harmer
0.055
970031AG2-029 GEN
Solar/Wind Harmer
4.625
25194608D.CRK4
Adder
1.676
270222AC2-111 GEN
Solar/Wind Harmer
3.603
970513AG2-328 GEN
Solar/Wind Harmer
3.076
970517AG2-330 GEN
Solar/Wind Harmer
18.457
970349AG2-230 GEN
Solar/Wind Harmer
10.632
946031AF1-268 GEN
Solar/Wind Harmer
6.74
958821AF2-173 GEN
Solar/Wind Harmer
9.902
270004AE1-209 GEN
Solar/Wind Harmer
1.532
270437AC2-090 C
Solar/Wind Harmer
0.003
247643Z2-116 C
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.775
970291AG2-192 GEN
Solar/Wind Harmer
0.705
945111AF1-176 GEN
Solar/Wind Harmer
5.709
247642Z2-115 C
Solar/Wind Harmer
0.003
24642205MAYFLWER
Adder
0.641
24441205WTRV SLR C
Solar/Wind Harmer
0
25196008MFTGT1
Adder
1.353
270356AE2-297 GEN
Solar/Wind Harmer
0.009
970217AG2-149 GEN
Solar/Wind Harmer
6.066
247604X1-042
Adder
0.418
270535AF1-215 GEN1
Solar/Wind Harmer
0.009
964401AG1-302 GEN
Solar/Wind Harmer
0.001
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
24755605MDL-5G
Solar/Wind Harmer
0.001
23559101PLEAS2
50/50
5.385
270122AB2-093 CT
50/50
3.689
962761AG1-125 GEN
Solar/Wind Harmer
33.269
970149AG2-104 GEN
Solar/Wind Harmer
35.932
970155AG2-107 GEN
Solar/Wind Harmer
21.245
270349AD2-093_GEN
Solar/Wind Harmer
0.006
24721705FLATG2
Adder
22.865
270159DARBY CT4
Adder
9.89
970593AG2-378 GEN
Solar/Wind Harmer
1.75
270223U2-072_GEN1
Solar/Wind Harmer
0.001
253343AC1-166 GEN
Solar/Wind Harmer
0.003
253325AC1-069 GEN
Solar/Wind Harmer
0.012
270462AD2-086
Solar/Wind Harmer
0.016
971995AH1-542 GEN
Solar/Wind Harmer
2.81
270263AC1-001 GEN
Solar/Wind Harmer
0.758
270510AE1-227 GEN1
Solar/Wind Harmer
1.904
241813AF1-122_GEN
Solar/Wind Harmer
3.294
25326309TAIT D
Adder
1.153
960071AF2-298 GEN
Solar/Wind Harmer
3.651
253370AE2-315 SEC1
Adder
2.103
253371AE2-315 SEC2
Adder
1.989
927014AC1-188 GEN
Solar/Wind Harmer
0.004
246936BC-WTG1
Solar/Wind Harmer
0.295
270489AE1-102 GEN1
Solar/Wind Harmer
0.945
965421AG1-410 GEN
Solar/Wind Harmer
21.788
247521TR3_G114
Solar/Wind Harmer
0.263
270246TR4_N_V150
Solar/Wind Harmer
0.047
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.226
965011AG1-365 GEN
Solar/Wind Harmer
7.225
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
24695305TIMB G C
Solar/Wind Harmer
0.002
965651AG1-433 GEN
Solar/Wind Harmer
2.096
958861AF2-177 GEN
Solar/Wind Harmer
3.092
247536S-71 GEN
Solar/Wind Harmer
0.287
945371AF1-202 GEN
Solar/Wind Harmer
0.001
25194608D.CRK4
Adder
1.676
270063AE2-323 C
Solar/Wind Harmer
0.006
252507AC2-088 GEN
Solar/Wind Harmer
0.323
970245AG2-165 GEN
Solar/Wind Harmer
3.076
944231AF1-091 GEN
Solar/Wind Harmer
1.885
270005AE1-210 C O1
Solar/Wind Harmer
1.532
965031AG1-367 GEN
Solar/Wind Harmer
7.073
970947AG2-589 GEN
Solar/Wind Harmer
0.236
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.183
970825AG2-519 GEN
Solar/Wind Harmer
2.509
24639705ELKHART HY
Adder
0.155
25196808ZIMRHP
Adder
76.799
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
270032AE2-172
Solar/Wind Harmer
4.701
970291AG2-192 GEN
Solar/Wind Harmer
0.916
945111AF1-176 GEN
Solar/Wind Harmer
12.568
270505AE1-170 C O1
Solar/Wind Harmer
7.393
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.67
247522W1-056 GEN
Solar/Wind Harmer
0.001
276903AD2-071 C
Solar/Wind Harmer
7.842
25196008MFTGT1
Adder
1.397
970773AG2-487 GEN
Solar/Wind Harmer
1.237
970373AG2-245 GEN
Solar/Wind Harmer
14.699
970515AG2-329 GEN
Solar/Wind Harmer
18.197
270055AF2-134 C O1
Solar/Wind Harmer
0.005
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.071
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.706
24791305MDL-5G
Solar/Wind Harmer
0.001
970333AG2-219 GEN
Solar/Wind Harmer
4.947
274751CRETE EC ;1U
Adder
8.172
274754CRETE EC ;4U
Adder
8.172
274773LINCOLN ;4U
Adder
8.364
274774LINCOLN ;5U
Adder
8.364
274723RIVER EC ;12
Adder
17.756
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.954
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
276776AD2-060 GEN
Solar/Wind Harmer
0.719
24728605AND G2
Adder
3.784
274801UNIV PARK;4U
Adder
5.751
941551AE2-152 GEN
Solar/Wind Harmer
0.001
945681AF1-233 GEN
Solar/Wind Harmer
12.962
274676JOLIET 29;8U
Adder
30.175
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
963741AG1-226 GEN
Solar/Wind Harmer
16.202
939401AE1-172 GEN
Solar/Wind Harmer
5.109
276691AA1-018 GEN1
Solar/Wind Harmer
0.827
276901AD2-066 C O1
Solar/Wind Harmer
0.007
316095T157 G97
Solar/Wind Helper
1.455
23583801GRNGAP
Solar/Wind Helper
5.418
238108AE1-109 GEN1
Solar/Wind Helper
0.106
238185AF2-356 C
Solar/Wind Helper
2.425
238147AE2-230_GEN1
Solar/Wind Helper
0.478
238149AF1-291A_GEN
Solar/Wind Helper
0.137
235531U2-073 GEN
Solar/Wind Helper
3.034
235054AD2-180 GEN
Solar/Wind Helper
1.839
237061AD1-155 GEN
Solar/Wind Helper
0.051
238117U2-030
Solar/Wind Helper
0.314
238221AF1-254 C O1
Solar/Wind Helper
0.265
235067AD1-061 GEN
Solar/Wind Helper
0.478
237030AB1-096 C
Solar/Wind Helper
0.068
3141196NOKESVL
Solar/Wind Helper
0.999
226910AB2-157 C
Solar/Wind Helper
0.014
270119AB2-067 GEN1
50/50
6.869
270120AB2-067 GEN2
50/50
6.869
24318905MLG2
50/50
6.89
270471AD2-092_GEN
Solar/Wind Harmer
0.006
942861AE2-305 GEN
Solar/Wind Harmer
6.118
970077AG2-063 GEN
Solar/Wind Harmer
4.471
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
938701AE1-092 GEN
Solar/Wind Harmer
12.484
971655AH1-328 GEN
Solar/Wind Harmer
2.758
964601AG1-323 GEN
Solar/Wind Harmer
3.106
964601AG1-323 GEN
Solar/Wind Harmer
2.071
270518AE2-148 GEN
Solar/Wind Harmer
0.667
972269AH1-719 GEN
Adder
2.501
972159AH1-661 GEN
Adder
1.082
253378AE2-206_GEN
Solar/Wind Harmer
0.004
276820AF1-078_GEN
Solar/Wind Harmer
0.002
970329AG2-216 GEN
Solar/Wind Harmer
3.237
971199AH1-059 GEN
Solar/Wind Harmer
2.99
241960AC2-195 GEN
Solar/Wind Harmer
0.006
970935AG2-582 GEN
Adder
242.403
25326509SID D
Adder
1.4
971073AG2-665 GEN
Solar/Wind Harmer
6.645
25326109MON D
Adder
1.391
971201AH1-060 GEN
Solar/Wind Harmer
1.471
25322209TAIT E
Adder
10.262
25322209TAIT E
Adder
10.031
253370AE2-315 SEC1
Adder
2.103
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
246938BC-WTG3
Solar/Wind Harmer
0.263
246937BC-WTG2
Solar/Wind Harmer
0.295
971231AH1-075 GEN
Solar/Wind Harmer
0.833
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
970611AG2-400 GEN
Solar/Wind Harmer
7.225
970627AG2-408 GEN
Solar/Wind Harmer
2.167
270007AE1-245 C
Solar/Wind Harmer
0.002
970623AG2-406 GEN
Solar/Wind Harmer
1.309
962581AG1-107 GEN
Solar/Wind Harmer
0.001
25183208HLCRTG
Solar/Wind Harmer
0.011
944541AF1-119 GEN
Solar/Wind Harmer
0.479
960971AF2-388 GEN
Solar/Wind Harmer
4.192
942221AE2-234 GEN
Solar/Wind Harmer
0.036
252519AF1-045_GEN
Solar/Wind Harmer
6.204
252516AE2-318_GEN
Solar/Wind Harmer
5.503
970621AG2-405 GEN
Solar/Wind Harmer
1.305
247621Y3-024
Adder
0.246
970883AG2-550 GEN
Solar/Wind Harmer
7.123
970885AG2-551 GEN
Solar/Wind Harmer
2.374
270201AC2-176 GEN
Solar/Wind Harmer
0.001
25194408D.CRK1
Adder
7.711
25194508D.CRK3
Adder
1.442
964611AG1-324 GEN
Solar/Wind Harmer
0.534
252509AD1-136 GEN
Solar/Wind Harmer
0.036
970321AG2-212 GEN
Solar/Wind Harmer
3.076
270599AE1-208 GEN
Solar/Wind Harmer
6.495
270031AE2-169
Solar/Wind Harmer
3.897
270383AD1-128 GEN
Solar/Wind Harmer
0.004
270186AC1-089 GEN
Solar/Wind Harmer
0.004
247620Y3-023
Adder
0.466
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
970825AG2-519 GEN
Solar/Wind Harmer
7.834
960441AF2-335 GEN
Solar/Wind Harmer
7.065
270216AD2-079_GEN
Solar/Wind Harmer
0.001
971613AH1-306 GEN
Solar/Wind Harmer
3.385
24728805RICHG1
Adder
3.82
24728905RICHG2
Adder
3.82
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
14.072
961051AF2-396 GEN
Solar/Wind Harmer
9.381
270526AF1-158 GEN
Solar/Wind Harmer
0.009
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
8.77
965791AG1-447 GEN
Solar/Wind Harmer
6.431
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
970239AG2-162 GEN
Solar/Wind Harmer
1.73
274770LINCOLN ;1U
Adder
8.364
274771LINCOLN ;2U
Adder
8.364
274808UNIV PK N;4U
Adder
4.933
966841AG1-555 GEN
Solar/Wind Harmer
0.781
274803UNIV PARK;6U
Adder
5.755
274888KELLY CRK;1U
Solar/Wind Harmer
0.404
274887GEN-1.85
Solar/Wind Harmer
0.181
276843GEN-1.7
Solar/Wind Harmer
0.223
958011AF2-095 GEN
Solar/Wind Harmer
9.913
972259AH1-714 GEN
Adder
18.805
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
970241AG2-163 GEN
Solar/Wind Harmer
3.993
958481AF2-142 GEN
Solar/Wind Harmer
10.238
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.923
971573AH1-285 GEN
Solar/Wind Harmer
1.271
971677AH1-339 GEN
Solar/Wind Harmer
0.768
958491AF2-143 GEN
Solar/Wind Harmer
10.205
274879MINONK ;1U
Solar/Wind Harmer
0.287
238175AF1-290_GEN
Solar/Wind Helper
0.148
238169AE2-226 GEN1
Solar/Wind Helper
0.677
238170AE2-226 GEN2
Solar/Wind Helper
0.677
238120AE2-309 GEN
Solar/Wind Helper
0.487
235020AA1-095 C
Solar/Wind Helper
0.051
23777901MDS_W4-102
Solar/Wind Helper
0.171
23585401KL_K28_T16
Solar/Wind Helper
1.328
237034AC2-136 C
Solar/Wind Helper
0.219
237002AB1-128_GEN
Solar/Wind Helper
0.427
235063AE1-101 C2
Solar/Wind Helper
1.6
237001AB1-127_GEN
Solar/Wind Helper
0.426
23777801MSM_W1-116
Solar/Wind Helper
0.11
237025AB1-124 C
Solar/Wind Helper
0.159
237006AB1-125 GEN
Solar/Wind Helper
0.119
226929AD2-058 GEN
Solar/Wind Helper
0.096
205916AD1-020 GEN
Solar/Wind Helper
1.656
20390526W1-045 C
Solar/Wind Helper
0.338
208835TUHI V3-051
Solar/Wind Helper
0.023
208835TUHI V3-051
Solar/Wind Helper
0.023
233987AB2-037 GEN
Solar/Wind Helper
2.264
233933AB2-153 GEN
Solar/Wind Helper
0.225
232424Y1-079 C
Solar/Wind Helper
0.112
233944AB2-135 GEN
Solar/Wind Helper
0.569
233946AB2-136 GEN
Solar/Wind Helper
0.549
234036AF2-325 C
Solar/Wind Helper
0.041
233901CHERRYDALE C
Solar/Wind Helper
0.225
232408W1-005 C
Solar/Wind Helper
0.49
232410W1-006 C
Solar/Wind Helper
0.49
233939AC1-091 C
Solar/Wind Helper
0.338
233970AC1-092 C
Solar/Wind Helper
0.338
315651AD1-115 GEN
Solar/Wind Helper
0.76
316447AC1-158 HLD
Solar/Wind Helper
2.756
230433AD2-135 GEN
Solar/Wind Helper
0.016
230407AD2-065 C
Solar/Wind Helper
0.039
219921AF1-264
Solar/Wind Helper
0.049
219615MILLCREEK C
Solar/Wind Helper
0.026
963401AG1-189 GEN
Solar/Wind Helper
0.054
963391AG1-188 GEN
Solar/Wind Helper
0.079
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.183
970781AG2-491 GEN
Solar/Wind Harmer
6.935
970243AG2-164 GEN
Solar/Wind Harmer
4.047
970519AG2-331 GEN
Solar/Wind Harmer
17.988
970699AG2-449 GEN
Solar/Wind Harmer
1.73
274752CRETE EC ;2U
Adder
8.172
274753CRETE EC ;3U
Adder
8.172
274772LINCOLN ;3U
Adder
8.364
274724RIVER EC ;11
Adder
17.549
958171AF2-111 GEN
Solar/Wind Harmer
17.278
274802UNIV PARK;5U
Adder
5.755
276806AD2-047 C O1
Solar/Wind Harmer
3.901
970941AG2-585 GEN
Solar/Wind Harmer
8.605
274826FISK ;BP
Adder
10.802
24728705AND G3
Adder
7.914
24728505AND G1
Adder
3.784
274800UNIV PARK;3U
Adder
5.751
972038AH1-567 GEN2
Adder
0.36
972228AH1-698 GEN2
Adder
3.654
972167AH1-666 GEN
Solar/Wind Harmer
5.505
276897AD1-100 C
Solar/Wind Harmer
0.009
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
22.464
274676JOLIET 29;8U
Adder
29.097
274729ELWOOD EC;1P
Adder
16.163
274730ELWOOD EC;6P
Adder
13.491
276893AG1-478 C
Solar/Wind Harmer
0.272
270541AE2-072 C
Solar/Wind Harmer
0.009
943121AE2-341 GEN
Solar/Wind Harmer
11.459
943591AF1-030 GEN
Solar/Wind Harmer
7.62
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
276805AD2-038 GEN
Solar/Wind Harmer
0.002
964991AG1-363 GEN
Solar/Wind Helper
4.969
316097T157 G90
Solar/Wind Helper
1.455
23750701CROSSCHOOL
Solar/Wind Helper
1.397
238148AE2-230_GEN2
Solar/Wind Helper
0.48
238127S14_GEN_2
Solar/Wind Helper
0.766
238118U2-030_1
Solar/Wind Helper
0.314
237080AD1-060 GEN
Solar/Wind Helper
0.33
237038AE2-054 C
Solar/Wind Helper
0.262
235062AE1-101 C1
Solar/Wind Helper
1.6
23779801AA1-109
Solar/Wind Helper
0.187
223401AF1-299 GEN
Solar/Wind Helper
0.355
316006AB2-029 C
Solar/Wind Helper
0.113
966131AG1-482 GEN
Solar/Wind Helper
0.132
237048AF1-022 C
Solar/Wind Helper
0.159
233930AB2-032 GEN
Solar/Wind Helper
0.368
233915AB1-141 GEN
Solar/Wind Helper
0.486
232422X3-066 FULL
Solar/Wind Helper
0.11
232426Y1-080 FULL
Solar/Wind Helper
0.038
233964AF2-378 GEN
Solar/Wind Helper
0.04
233998TM1NIN_3.36
Solar/Wind Helper
0.253
232404W1-003 C
Solar/Wind Helper
0.49
232428Y3-058 C
Solar/Wind Helper
0.327
232434Z2-077 GEN
Solar/Wind Helper
0.123
233954AC2-188 GEN
Solar/Wind Helper
0.225
233950AC2-186 GEN
Solar/Wind Helper
0.112
233972AC1-094 C
Solar/Wind Helper
0.292
316045AC1-158 PL2
Solar/Wind Helper
4.009
230511AF1-262
Solar/Wind Helper
0.014
230434AG1-499 GEN
Solar/Wind Helper
0.222
228728W1-130C
Solar/Wind Helper
0.052
219258KINSLEYDEP C
Solar/Wind Helper
0.074
219904AC1-010 C
Solar/Wind Helper
0.058
218660EHAMPSOLAR C
Solar/Wind Helper
0.032
219907AC1-030 C
Solar/Wind Helper
0.033
219686LUMSOLAR_N C
Solar/Wind Helper
0.038
219304NAMERICA C
Solar/Wind Helper
0.127
316254AC1-120 GEN1
Solar/Wind Helper
1.026
20720728JCB_W1-129
Solar/Wind Helper
0.055
207445AB1-138_GEN
Solar/Wind Helper
0.101
963711AG1-223 GEN
Solar/Wind Helper
0.062
20714828MDF_W3-079
Solar/Wind Helper
0.126
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.299
20715228NPK_W1-113
Solar/Wind Helper
0.075
227287AC2-120 GEN
Solar/Wind Helper
0.335
223402AF1-300 C
Solar/Wind Helper
0.355
23751201ROTHROCK
Solar/Wind Helper
0.694
23562501BACKB
Solar/Wind Helper
0.842
205917AD1-020 ES
Solar/Wind Helper
0.356
233982AB2-133 GEN
Solar/Wind Helper
0.346
233918AB1-142 GEN
Solar/Wind Helper
0.486
233994AC2-023 GEN
Solar/Wind Helper
0.929
233996TM1833_GEN
Solar/Wind Helper
0.253
233997TMININ_4.2
Solar/Wind Helper
0.253
232406W1-004 FULL
Solar/Wind Helper
0.49
233940AF2-379 C
Solar/Wind Helper
0.06
234015AF2-250 C
Solar/Wind Helper
0.037
233952AC2-187 GEN
Solar/Wind Helper
0.225
233971AC1-093 C
Solar/Wind Helper
0.346
316044AC1-158 PL1
Solar/Wind Helper
1.252
316450AC1-158 RIC
Solar/Wind Helper
0.334
230430AE1-229_GEN
Solar/Wind Helper
3.26
230415AB2-049 C
Solar/Wind Helper
0.029
228729W2-030 C
Solar/Wind Helper
0.107
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.053
219912AD2-042 GEN
Solar/Wind Helper
0.145
219291REEVESSOUT C
Solar/Wind Helper
0.011
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.111
316170AC1-121 GEN2
Solar/Wind Helper
0.342
959561AF2-247 GEN
Solar/Wind Helper
0.02
20720828JCB_W4-025
Solar/Wind Helper
0.061
20716028EGP_W2-019
Solar/Wind Helper
0.018
20715028HAN_X4-015
Solar/Wind Helper
0.055
219276PARKLANDSO C
Solar/Wind Helper
0.086
20714528FRN_Y2-051
Solar/Wind Helper
0.055
20720528MAN_W1-024
Solar/Wind Helper
0.027
971997AH1-543 GEN
Solar/Wind Harmer
1.86
274777LINCOLN ;8U
Adder
8.364
274814UNIV PK N;0U
Adder
4.998
274807UNIV PK N;3U
Adder
4.987
274805UNIV PK N;1U
Adder
4.965
274811UNIV PK N;7U
Adder
4.954
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
972037AH1-567 GEN1
Adder
0.181
960591AF2-350 GEN
Solar/Wind Harmer
6.884
274827FISK ;RP
Adder
7.655
972227AH1-698 GEN1
Adder
2.573
963841AG1-237 GEN
Solar/Wind Harmer
2.978
274687WILL CNTY;4U
Adder
27.495
274687WILL CNTY;4U
Adder
27.495
274675JOLIET 29;7U
Adder
30.175
274675JOLIET 29;7U
Adder
29.097
972163AH1-664 GEN
Solar/Wind Harmer
7.639
972165AH1-665 GEN
Solar/Wind Harmer
6.118
274731ELWOOD EC;2P
Adder
16.163
274733ELWOOD EC;3P
Adder
16.163
274735ELWOOD EC;4P
Adder
16.163
274728ELWOOD EC;5P
Adder
16.163
970833AG2-524 GEN
Solar/Wind Harmer
7.542
970833AG2-524 GEN
Solar/Wind Harmer
5.028
945641AF1-229 GEN
Solar/Wind Harmer
0.001
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
276868AE1-113 GEN
Solar/Wind Harmer
1.363
276882AE2-255 GEN
Solar/Wind Harmer
0.794
238109AE1-109 GEN2
Solar/Wind Helper
0.106
238110AE1-109 GEN3
Solar/Wind Helper
0.106
238152AF2-075_GEN
Solar/Wind Helper
0.683
23546401DTGZ2-030
Solar/Wind Helper
0.086
238208AF1-136 C
Solar/Wind Helper
0.211
238126S14_GEN_1
Solar/Wind Helper
0.766
237085AD2-009_GEN
Solar/Wind Helper
1.588
3138216PACIFIC
Solar/Wind Helper
0.043
316411AF1-147_GEN1
Solar/Wind Helper
0.86
316415AF1-147_GEN2
Solar/Wind Helper
0.86
959381AF2-229 GEN
Solar/Wind Helper
0.345
23750501ELLIOTTS
Solar/Wind Helper
0.571
3141426STAFORD
Solar/Wind Helper
0.051
960921AF2-383 GEN
Solar/Wind Helper
0.352
205943AE1-185 GEN
Solar/Wind Helper
0.492
205956AE1-196_GEN
Solar/Wind Helper
0.492
205932AD2-116_GEN
Solar/Wind Helper
0.492
233935AB2-179 C
Solar/Wind Helper
1.227
232436AB1-176 C
Solar/Wind Helper
0.043
233923SMA
Solar/Wind Helper
0.927
233990AG1-397 GEN
Solar/Wind Helper
0.261
234033AF1-007_GEN
Solar/Wind Helper
6.787
232432Z2-076 GEN
Solar/Wind Helper
0.065
964001AG1-254 GEN
Solar/Wind Helper
0.924
228754AB1-001 C
Solar/Wind Helper
0.025
227927V4-067C
Solar/Wind Helper
0.01
219914AD2-027 C
Solar/Wind Helper
0.111
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.038
219607WPEMNERT C
Solar/Wind Helper
0.077
214067T20SOLAR
Solar/Wind Helper
0.011
203975AE1-071-GEN
Solar/Wind Helper
2.41
20715728PEM_W1-119
Solar/Wind Helper
0.093
20715828PEM_W1-120
Solar/Wind Helper
0.093
207459AE1-142 C O1
Solar/Wind Helper
0.28
316164AC1-076 GEN
Solar/Wind Helper
1.062
219620RIDERU C
Solar/Wind Helper
0.001
NYPJM->LTFIMP_NY
CLTF
4.628
LGEELTFEXP_LGEE->PJM
CLTF
6.497
WECLTFEXP_WEC->PJM
CLTF
3.686
AG2-052LTFEXP_AG2-052->PJM
LTF
0.231
AH1-155LTFEXP_AH1-155->PJM
LTF
0.346
LAGNLTFEXP_LAGN->PJM
CLTF
14.268
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.432
TVALTFEXP_TVA->PJM
CLTF
7.011
CBM West 1LTFEXP_CBM-W1->PJM
CBM
137.982
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.984
MECLTFEXP_MEC->PJM
CLTF
15.319
SIGELTFEXP_SIGE->PJM
CLTF
0.486
CPLELTFEXP_CPLE->PJM
CLTF
0.567
CBM West 2LTFEXP_CBM-W2->PJM
CBM
108.576

Details for 05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line l/o AP_P1-3_MP-765-501T_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AP_P1-3_MP-765-501T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.76 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4919.18
MW Contribution:4.13
Bus #Bus NameTypeMW Contribution
270166AC1-044 GEN3
50/50
18.401
270159DARBY CT4
50/50
13.494
962761AG1-125 GEN
Solar/Wind Harmer
50.586
970149AG2-104 GEN
Solar/Wind Harmer
54.635
970155AG2-107 GEN
Solar/Wind Harmer
32.303
270349AD2-093_GEN
Solar/Wind Harmer
0.009
270223U2-072_GEN1
Solar/Wind Harmer
0.001
970593AG2-378 GEN
Solar/Wind Harmer
2.27
270462AD2-086
Solar/Wind Harmer
0.021
253343AC1-166 GEN
Solar/Wind Harmer
0.004
253325AC1-069 GEN
Solar/Wind Harmer
0.015
25326309TAIT D
Adder
1.4
960071AF2-298 GEN
Solar/Wind Harmer
4.426
965011AG1-365 GEN
Solar/Wind Harmer
8.881
253370AE2-315 SEC1
Adder
2.545
253371AE2-315 SEC2
Adder
2.407
965651AG1-433 GEN
Solar/Wind Harmer
2.599
970245AG2-165 GEN
Solar/Wind Harmer
3.83
958861AF2-177 GEN
Solar/Wind Harmer
3.827
971995AH1-542 GEN
Solar/Wind Harmer
3.236
945371AF1-202 GEN
Solar/Wind Harmer
0.001
247521TR3_G114
Solar/Wind Harmer
0.319
270246TR4_N_V150
Solar/Wind Harmer
0.056
24721705FLATG2
Adder
25.369
965421AG1-410 GEN
Solar/Wind Harmer
26.181
270119AB2-067 GEN1
50/50
18.401
270120AB2-067 GEN2
50/50
18.401
270160DARBY CT5
50/50
0.735
270161DARBY CT6
50/50
0.725
270466AD2-091
50/50
8.176
270471AD2-092_GEN
Solar/Wind Harmer
0.009
942861AE2-305 GEN
Solar/Wind Harmer
8.094
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
970077AG2-063 GEN
Solar/Wind Harmer
5.8
270518AE2-148 GEN
Solar/Wind Harmer
0.847
964601AG1-323 GEN
Solar/Wind Harmer
3.902
964601AG1-323 GEN
Solar/Wind Harmer
2.601
938701AE1-092 GEN
Solar/Wind Harmer
15.513
971655AH1-328 GEN
Solar/Wind Harmer
3.428
253378AE2-206_GEN
Solar/Wind Harmer
0.005
276820AF1-078_GEN
Solar/Wind Harmer
0.002
970329AG2-216 GEN
Solar/Wind Harmer
4.005
25326509SID D
Adder
1.713
25326109MON D
Adder
1.698
25322209TAIT E
Adder
12.455
25322209TAIT E
Adder
12.175
970611AG2-400 GEN
Solar/Wind Harmer
8.881
970627AG2-408 GEN
Solar/Wind Harmer
2.664
253370AE2-315 SEC1
Adder
2.545
944541AF1-119 GEN
Solar/Wind Harmer
0.594
960971AF2-388 GEN
Solar/Wind Harmer
5.197
970321AG2-212 GEN
Solar/Wind Harmer
3.83
942221AE2-234 GEN
Solar/Wind Harmer
0.044
246938BC-WTG3
Solar/Wind Harmer
0.316
246937BC-WTG2
Solar/Wind Harmer
0.353
270599AE1-208 GEN
Solar/Wind Harmer
7.961
270031AE2-169
Solar/Wind Harmer
4.777
253394AE2-221_GEN
Solar/Wind Harmer
0.011
253398AE2-221_GEN2
Solar/Wind Harmer
0.011
270201AC2-176 GEN
Solar/Wind Harmer
0.002
964611AG1-324 GEN
Solar/Wind Harmer
0.65
247621Y3-024
Adder
0.3
970883AG2-550 GEN
Solar/Wind Harmer
8.648
970885AG2-551 GEN
Solar/Wind Harmer
2.883
970825AG2-519 GEN
Solar/Wind Harmer
9.566
960441AF2-335 GEN
Solar/Wind Harmer
8.628
971613AH1-306 GEN
Solar/Wind Harmer
4.135
270383AD1-128 GEN
Solar/Wind Harmer
0.005
24379505HDWTR1G C
Solar/Wind Harmer
0.003
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
965681AG1-436 GEN
Solar/Wind Harmer
10.743
965791AG1-447 GEN
Solar/Wind Harmer
7.878
270216AD2-079_GEN
Solar/Wind Harmer
0.001
253317AC1-085 GEN4
Solar/Wind Harmer
0.005
247620Y3-023
Adder
0.565
270526AF1-158 GEN
Solar/Wind Harmer
0.011
24441505OLIV SLR
Solar/Wind Harmer
0
274770LINCOLN ;1U
Adder
10.354
274771LINCOLN ;2U
Adder
10.354
270007AE1-245 C
Solar/Wind Harmer
0.002
274808UNIV PK N;4U
Adder
6.08
274888KELLY CRK;1U
Solar/Wind Harmer
0.499
274887GEN-1.85
Solar/Wind Harmer
0.224
276843GEN-1.7
Solar/Wind Harmer
0.275
972259AH1-714 GEN
Adder
23.234
958011AF2-095 GEN
Solar/Wind Harmer
12.235
274803UNIV PARK;6U
Adder
7.1
957891AF2-083 GEN
Solar/Wind Harmer
0.001
24728805RICHG1
Adder
4.598
24728905RICHG2
Adder
4.598
274674JOLIET 9 ;6U
Adder
18.689
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
961051AF2-396 GEN
Solar/Wind Harmer
16.913
961051AF2-396 GEN
Solar/Wind Harmer
11.276
971573AH1-285 GEN
Solar/Wind Harmer
1.571
958481AF2-142 GEN
Solar/Wind Harmer
12.626
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
1.139
274696ROCKY RD ;4P
Adder
13.733
274695ROCKY RD ;2P
Adder
13.416
274693ROCKY RD ;1P
Adder
13.284
274697ROCKY RD ;3P
Adder
3.645
274683WAUKEGAN ;8U
Adder
25.365
274683WAUKEGAN ;8U
Adder
21.381
25183208HLCRTG
Solar/Wind Harmer
0.013
958491AF2-143 GEN
Solar/Wind Harmer
12.583
962691AG1-118 GEN
Solar/Wind Harmer
25.162
966841AG1-555 GEN
Solar/Wind Harmer
0.948
970921AG2-575 GEN
Solar/Wind Harmer
8.38
970921AG2-575 GEN
Solar/Wind Harmer
2.793
274879MINONK ;1U
Solar/Wind Harmer
0.353
25194408D.CRK1
Adder
9.077
25194508D.CRK3
Adder
1.697
252519AF1-045_GEN
Solar/Wind Harmer
7.283
252516AE2-318_GEN
Solar/Wind Harmer
6.46
942991AE2-321 GEN
Solar/Wind Harmer
9.334
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
971333AH1-146 GEN
Solar/Wind Harmer
16.689
971335AH1-147 GEN
Solar/Wind Harmer
16.689
971341AH1-150 GEN
Solar/Wind Harmer
16.66
971343AH1-151 GEN
Solar/Wind Harmer
16.66
970623AG2-406 GEN
Solar/Wind Harmer
1.522
970241AG2-163 GEN
Solar/Wind Harmer
4.844
23652301WDPWR_K20
Solar/Wind Helper
0.137
241967AE2-285_GEN
Solar/Wind Helper
0.621
241801AE1-079 GEN
Solar/Wind Helper
0.242
241985AE1-237 GEN
Solar/Wind Helper
0.242
962101AG1-054 GEN
Solar/Wind Helper
0.632
946071AF1-272 GEN
Solar/Wind Helper
2.567
23585401KL_K28_T16
Solar/Wind Helper
1.167
203955AF1-039 C O1
Solar/Wind Helper
0.346
944781AF1-143 GEN
Solar/Wind Helper
2.312
20083426SW_E13_K22
Solar/Wind Helper
0.053
20084626FORWARD
Solar/Wind Helper
0.336
20088926STNY CRK
Solar/Wind Helper
0.77
203940AF1-140 C
Solar/Wind Helper
0.374
20088626ARWF_N39
Solar/Wind Helper
1.147
20303426NA_O38_P22
Solar/Wind Helper
0.94
946381AF1-302 GEN
Solar/Wind Helper
0.21
203853AF1-134 C O1
Solar/Wind Helper
0.452
203952AE2-129 C
Solar/Wind Helper
0.447
203946AE2-131 C
Solar/Wind Helper
0.448
238120AE2-309 GEN
Solar/Wind Helper
0.401
238217AF1-153 C O1
Solar/Wind Helper
0.223
20398826ARMNA MT
Solar/Wind Helper
1.407
270156DARBY CT1
50/50
13.713
270157DARBY CT2
50/50
13.679
270158DARBY CT3
50/50
13.461
270036AE2-216 BAT
50/50
8.994
962771AG1-126 GEN
Solar/Wind Harmer
50.586
270284AF1-227 GEN1
Solar/Wind Harmer
0.014
270286AF1-227 GEN2
Solar/Wind Harmer
0.006
270287AF1-227 GEN3
Solar/Wind Harmer
0.006
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
6.623
270520AE2-214 GEN
Solar/Wind Harmer
0.017
270054AF2-122 C O1
Solar/Wind Harmer
0.009
253383AE2-342_GEN
Solar/Wind Harmer
0.004
241973AD2-163_GEN1
Solar/Wind Harmer
0.008
943861AF1-054 GEN
Solar/Wind Harmer
3.995
943851AF1-053 GEN
Solar/Wind Harmer
2.767
270578AF1-285 GEN2
Solar/Wind Harmer
0.678
945631AF1-228 GEN
Solar/Wind Harmer
0
270302AB2-170 GEN
Solar/Wind Harmer
0.006
270317AD1-130_GEN
Solar/Wind Harmer
0.014
971653AH1-327 GEN
Solar/Wind Harmer
1.38
241972AD1-140 GEN
Solar/Wind Harmer
1.032
970689AG2-444 GEN
Solar/Wind Harmer
19.097
270432AC2-029 GEN
Solar/Wind Harmer
4.134
270269AC2-059
Solar/Wind Harmer
0.005
24729505KEY G4
Adder
8.316
270071AF1-092 GEN
Solar/Wind Harmer
17.084
253372AE2-315 SEC3
Adder
2.407
253372AE2-315 SEC3
Adder
2.407
965101AG1-375 GEN
Solar/Wind Harmer
8.831
25306009OHH W.
Adder
3.647
253349AC2-067 GEN
Solar/Wind Harmer
2.778
253400AC2-068 GEN
Solar/Wind Harmer
1.117
945581AF1-223 GEN
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
11.841
971347AH1-153 GEN
Solar/Wind Harmer
13.153
965051AG1-369 GEN
Solar/Wind Harmer
4.367
965041AG1-368 GEN
Solar/Wind Harmer
8.719
270024AE2-089 GEN
Solar/Wind Harmer
0.009
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
1.103
270340AC2-060 GEN
Solar/Wind Harmer
0.01
971609AH1-304 GEN
Solar/Wind Harmer
1.419
270543AE2-219 C
Solar/Wind Harmer
0.005
971029AG2-637 GEN
Solar/Wind Harmer
12.951
971673AH1-337 GEN
Solar/Wind Harmer
5.609
970115AG2-085 GEN
Solar/Wind Harmer
3.451
270594AE1-207 GEN
Solar/Wind Harmer
9.648
970289AG2-191 GEN
Solar/Wind Harmer
1.635
270240V3-007_GEN2
Solar/Wind Harmer
0.003
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971771AH1-392 GEN
Solar/Wind Harmer
8.573
971769AH1-391 GEN
Solar/Wind Harmer
9.561
274775LINCOLN ;6U
Adder
10.354
274776LINCOLN ;7U
Adder
10.354
274777LINCOLN ;8U
Adder
10.354
24725505WLD G2 C
Solar/Wind Harmer
0.002
24699105WLD G1 C
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.011
247607V1-011 GEN
Solar/Wind Harmer
0.001
274814UNIV PK N;0U
Adder
6.16
274807UNIV PK N;3U
Adder
6.147
274805UNIV PK N;1U
Adder
6.12
274811UNIV PK N;7U
Adder
6.107
958391AF2-133 GEN
Solar/Wind Harmer
0.001
960591AF2-350 GEN
Solar/Wind Harmer
8.497
972227AH1-698 GEN1
Adder
3.176
972037AH1-567 GEN1
Adder
0.223
274827FISK ;RP
Adder
9.447
971619AH1-309 GEN
Solar/Wind Harmer
3.821
971611AH1-305 GEN
Solar/Wind Harmer
5.053
274687WILL CNTY;4U
Adder
33.939
274687WILL CNTY;4U
Adder
33.939
274675JOLIET 29;7U
Adder
37.252
274675JOLIET 29;7U
Adder
35.922
274731ELWOOD EC;2P
Adder
19.951
274733ELWOOD EC;3P
Adder
19.951
274735ELWOOD EC;4P
Adder
19.951
274728ELWOOD EC;5P
Adder
19.951
970833AG2-524 GEN
Solar/Wind Harmer
9.313
970833AG2-524 GEN
Solar/Wind Harmer
6.209
274746AC1-111 G10
Adder
6.762
274744AC1-111 GEN8
Adder
6.762
24690905MDL-1G C
Solar/Wind Harmer
0.003
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274863CRW1-WTG
Solar/Wind Harmer
0.003
274864CRW2-WTG
Solar/Wind Harmer
0.003
252524AE2-267 GEN
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
10.608
25196308WSDLE2
Adder
10.516
25196208WSDLE1
Adder
10.49
25196708WSDLE6
Adder
10.463
25196508WSDLE4
Adder
10.2
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
276868AE1-113 GEN
Solar/Wind Harmer
1.681
276882AE2-255 GEN
Solar/Wind Harmer
0.979
970169AG2-114 GEN
Solar/Wind Harmer
8.358
971177AH1-047 GEN
Solar/Wind Harmer
5.154
971675AH1-338 GEN
Solar/Wind Harmer
3.256
971411AH1-196 GEN
Solar/Wind Harmer
12.519
963841AG1-237 GEN
Solar/Wind Harmer
3.615
971171AH1-044 GEN
Solar/Wind Harmer
16.66
926823AC1-168 GEN
Solar/Wind Harmer
1.415
274823ROCKFORD ;21
Adder
23.229
254304AE2-114 C
Solar/Wind Helper
0.214
241982AE2-343 S C
Solar/Wind Helper
0.217
241997AF1-093 GEN
Solar/Wind Helper
0.248
23750501ELLIOTTS
Solar/Wind Helper
0.61
20092526R32
Solar/Wind Helper
1.098
203961AE2-224 GEN
Solar/Wind Helper
2.278
20091526CHSTN_FL
Solar/Wind Helper
0.55
20090526Q36
Solar/Wind Helper
0.985
203993AD2-133_GEN1
Solar/Wind Helper
0.985
203846AF2-130 C
Solar/Wind Helper
0.425
238126S14_GEN_1
Solar/Wind Helper
0.64
941231AE2-117 GEN
Solar/Wind Helper
0.447
203855AF2-088 C
Solar/Wind Helper
0.144
203804AE2-113_GEN
Solar/Wind Helper
1.639
246936BC-WTG1
Solar/Wind Harmer
0.353
270489AE1-102 GEN1
Solar/Wind Harmer
1.132
247536S-71 GEN
Solar/Wind Harmer
0.349
270005AE1-210 C O1
Solar/Wind Harmer
1.875
965031AG1-367 GEN
Solar/Wind Harmer
8.654
270063AE2-323 C
Solar/Wind Harmer
0.007
24695305TIMB G C
Solar/Wind Harmer
0.002
970825AG2-519 GEN
Solar/Wind Harmer
3.064
270263AC1-001 GEN
Solar/Wind Harmer
0.865
270032AE2-172
Solar/Wind Harmer
5.743
970291AG2-192 GEN
Solar/Wind Harmer
1.119
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0.001
970613AG2-401 GEN
Solar/Wind Harmer
6.306
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
8.568
24639705ELKHART HY
Adder
0.188
276903AD2-071 C
Solar/Wind Harmer
9.56
274773LINCOLN ;4U
Adder
10.354
274774LINCOLN ;5U
Adder
10.354
970373AG2-245 GEN
Solar/Wind Harmer
17.958
270055AF2-134 C O1
Solar/Wind Harmer
0.007
274723RIVER EC ;12
Adder
21.894
274751CRETE EC ;1U
Adder
10.063
274754CRETE EC ;4U
Adder
10.063
276164X3-005 C
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
11.064
274812UNIV PK N;8U
Adder
6.107
276776AD2-060 GEN
Solar/Wind Harmer
0.887
274801UNIV PARK;4U
Adder
7.097
941551AE2-152 GEN
Solar/Wind Harmer
0.001
945111AF1-176 GEN
Solar/Wind Harmer
15.149
270505AE1-170 C O1
Solar/Wind Harmer
8.915
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
10.609
274676JOLIET 29;8U
Adder
37.252
274674JOLIET 9 ;6U
Adder
18.689
274732ELWOOD EC;7P
Adder
19.951
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
970773AG2-487 GEN
Solar/Wind Harmer
1.492
274745AC1-111 GEN9
Adder
6.762
24791305MDL-5G
Solar/Wind Harmer
0.001
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
4.404
939401AE1-172 GEN
Solar/Wind Harmer
6.298
276691AA1-018 GEN1
Solar/Wind Harmer
1.02
274682WAUKEGAN ;7U
Adder
21.642
274828WAUKEGAN ;BP
Adder
13.296
276901AD2-066 C O1
Solar/Wind Harmer
0.008
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
962781AG1-127 GEN
Solar/Wind Harmer
7.975
971997AH1-543 GEN
Solar/Wind Harmer
4.396
25194608D.CRK4
Adder
1.973
274872LEEDK;1U
Solar/Wind Harmer
0.005
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
276861AD2-134 GEN
Solar/Wind Harmer
0.15
957471AF2-041 GEN
Solar/Wind Harmer
24.989
959081AF2-199 GEN
Solar/Wind Harmer
8.33
971067AG2-660 GEN
Solar/Wind Harmer
2.777
970569AG2-363 GEN
Solar/Wind Harmer
24.96
24728605AND G2
Adder
4.573
274822ROCKFORD ;11
Adder
23.399
972235AH1-702 GEN1
Adder
3.003
963741AG1-226 GEN
Solar/Wind Harmer
19.652
25196808ZIMRHP
Adder
58.315
254303AC2-168 GEN
Solar/Wind Helper
0.155
237046AF1-021 C
Solar/Wind Helper
0.463
241966AE1-183 GEN
Solar/Wind Helper
0.248
238185AF2-356 C
Solar/Wind Helper
2.025
20089226LOOKOUT
Solar/Wind Helper
0.542
20088826HIGHLAND
Solar/Wind Helper
0.847
20094526CT_V3-030
Solar/Wind Helper
0.446
235054AD2-180 GEN
Solar/Wind Helper
1.566
964201AG1-281 GEN
Solar/Wind Helper
0.457
238117U2-030
Solar/Wind Helper
0.269
235531U2-073 GEN
Solar/Wind Helper
2.545
964391AG1-301 GEN
Solar/Wind Helper
0.446
203954AE2-126 C
Solar/Wind Helper
0.443
23751201ROTHROCK
Solar/Wind Helper
0.652
238206AE2-263_GEN
Solar/Wind Helper
0.858
970819AG2-516 GEN
Solar/Wind Harmer
7.858
270051AF1-062 GEN
50/50
17.076
270475AD2-096_GEN
50/50
10.066
970153AG2-106 GEN
Solar/Wind Harmer
32.303
961921AG1-034 GEN
Solar/Wind Harmer
9.935
241955AC1-078 GEN
Solar/Wind Harmer
0.009
241974AD2-163_GEN2
Solar/Wind Harmer
0.008
942051AE2-217 GEN
Solar/Wind Harmer
18.548
270391AF1-285 GEN3
Solar/Wind Harmer
0.678
970605AG2-385 GEN
Solar/Wind Harmer
6.136
270485AE1-090_GEN
Solar/Wind Harmer
0.001
253338AC1-165 GEN
Solar/Wind Harmer
0.004
253333AC1-068 GEN
Solar/Wind Harmer
0.015
270273AD2-016 GEN
Solar/Wind Harmer
0.935
944531AF1-118 GEN
Solar/Wind Harmer
40.219
972173AH1-669 GEN
Solar/Wind Harmer
4.474
270043AE2-236 GEN
Solar/Wind Harmer
5.712
959331AF2-224 GEN
Solar/Wind Harmer
6.217
965021AG1-366 GEN
Solar/Wind Harmer
2.96
253370AE2-315 SEC1
Adder
2.545
253371AE2-315 SEC2
Adder
2.407
970513AG2-328 GEN
Solar/Wind Harmer
3.83
970517AG2-330 GEN
Solar/Wind Harmer
22.981
970191AG2-125 GEN
Solar/Wind Harmer
2.269
253415AE1-040 GEN
Solar/Wind Harmer
0.004
970349AG2-230 GEN
Solar/Wind Harmer
13.153
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.056
24721905FLATG4
Adder
25.369
971617AH1-308 GEN
Solar/Wind Harmer
7.263
270491AE1-102 GEN2
Solar/Wind Harmer
1.132
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
13.019
970031AG2-029 GEN
Solar/Wind Harmer
5.627
958821AF2-173 GEN
Solar/Wind Harmer
12.116
270004AE1-209 GEN
Solar/Wind Harmer
1.875
946031AF1-268 GEN
Solar/Wind Harmer
8.226
253406AD2-031_GEN
Solar/Wind Harmer
0.643
970289AG2-191 GEN
Solar/Wind Harmer
0.947
970291AG2-192 GEN
Solar/Wind Harmer
0.861
247642Z2-115 C
Solar/Wind Harmer
0.004
270437AC2-090 C
Solar/Wind Harmer
0.004
247643Z2-116 C
Solar/Wind Harmer
0
253316AC1-085 GEN3
Solar/Wind Harmer
0.005
253433AC1-085 GEN1
Solar/Wind Harmer
0.004
946181AF1-283 GEN
Solar/Wind Harmer
11.138
274772LINCOLN ;3U
Adder
10.354
270535AF1-215 GEN1
Solar/Wind Harmer
0.011
270222AC2-111 GEN
Solar/Wind Harmer
4.32
274724RIVER EC ;11
Adder
21.639
274752CRETE EC ;2U
Adder
10.063
274753CRETE EC ;3U
Adder
10.063
24642205MAYFLWER
Adder
0.776
964401AG1-302 GEN
Solar/Wind Harmer
0.001
970707AG2-453 GEN
Solar/Wind Harmer
27.781
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
276806AD2-047 C O1
Solar/Wind Harmer
4.815
970941AG2-585 GEN
Solar/Wind Harmer
10.621
274802UNIV PARK;5U
Adder
7.1
972228AH1-698 GEN2
Adder
4.511
274826FISK ;BP
Adder
13.329
274800UNIV PARK;3U
Adder
7.097
972038AH1-567 GEN2
Adder
0.444
276897AD1-100 C
Solar/Wind Harmer
0.011
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
945111AF1-176 GEN
Solar/Wind Harmer
6.882
274676JOLIET 29;8U
Adder
35.922
274729ELWOOD EC;1P
Adder
19.951
274730ELWOOD EC;6P
Adder
19.951
274734ELWOOD EC;8P
Adder
19.951
274736ELWOOD EC;9P
Adder
19.951
276893AG1-478 C
Solar/Wind Harmer
0.336
943121AE2-341 GEN
Solar/Wind Harmer
14.16
943591AF1-030 GEN
Solar/Wind Harmer
9.416
270356AE2-297 GEN
Solar/Wind Harmer
0.011
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
8.438
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
21.642
25196608WSDLE5
Adder
10.305
276805AD2-038 GEN
Solar/Wind Harmer
0.002
25194608D.CRK4
Adder
1.973
274872LEEDK;1U
Solar/Wind Harmer
0.307
252510AF1-249 C
Solar/Wind Harmer
0.065
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
0.891
276889AE2-281 GEN
Solar/Wind Harmer
0.001
274855GSG-6 ;RU
Solar/Wind Harmer
0.306
274850MENDOTA H;RU
Solar/Wind Harmer
0.098
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.15
959091AF2-200 GEN
Solar/Wind Harmer
16.66
24441205WTRV SLR C
Solar/Wind Harmer
0
970571AG2-364 GEN
Solar/Wind Harmer
16.64
24728705AND G3
Adder
9.564
24728505AND G1
Adder
4.573
270258AD1-119 GEN
Solar/Wind Harmer
0.002
972236AH1-702 GEN2
Adder
2.611
235058AG1-386 C
Solar/Wind Helper
0.453
237048AF1-022 C
Solar/Wind Helper
0.176
254305AE2-115 C
Solar/Wind Helper
0.214
237043AE2-125 C
Solar/Wind Helper
0.172
964991AG1-363 GEN
Solar/Wind Helper
3.577
202652Y1-033 WT C
Solar/Wind Helper
0.525
20089126CSLMN_L13
Solar/Wind Helper
0.557
20089026BF_G21_K23
Solar/Wind Helper
0.441
23750701CROSSCHOOL
Solar/Wind Helper
1.122
203818AF1-086 GEN
Solar/Wind Helper
1.594
238118U2-030_1
Solar/Wind Helper
0.269
238127S14_GEN_2
Solar/Wind Helper
0.64
203854AF2-039 C
Solar/Wind Helper
0.3
20334926Z1-069 C
Solar/Wind Helper
1.268
238202AE2-262_GEN
Solar/Wind Helper
0.902
NYPJM->LTFIMP_NY
CLTF
5.332
LGEELTFEXP_LGEE->PJM
CLTF
7.674
WECLTFEXP_WEC->PJM
CLTF
4.549
AG2-052LTFEXP_AG2-052->PJM
LTF
0.283
AH1-155LTFEXP_AH1-155->PJM
LTF
0.424
LAGNLTFEXP_LAGN->PJM
CLTF
17.886
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.768
TVALTFEXP_TVA->PJM
CLTF
8.721
CBM West 1LTFEXP_CBM-W1->PJM
CBM
155.754
CBM South 1LTFEXP_CBM-S1->PJM
CBM
34.409
MECLTFEXP_MEC->PJM
CLTF
18.875
SIGELTFEXP_SIGE->PJM
CLTF
0.583
CPLELTFEXP_CPLE->PJM
CLTF
2.705
CBM West 2LTFEXP_CBM-W2->PJM
CBM
133.737

Details for 05MADDOX-05E LIMA 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MADDOX-05E LIMA 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.12 %
Rating:2246.0 MVA
Rating Type:B
MVA to Mitigate:2697.98
MW Contribution:2.33
Bus #Bus NameTypeMW Contribution
24727005RPMNG1
50/50
3.301
960861AF2-377 GEN
50/50
2.381
970521AG2-332 GEN
50/50
10.716
24639705ELKHART HY
50/50
0.148
246936BC-WTG1
Solar/Wind Harmer
1.161
270489AE1-102 GEN1
Solar/Wind Harmer
3.72
965421AG1-410 GEN
Solar/Wind Harmer
81.572
965011AG1-365 GEN
Solar/Wind Harmer
13.709
270063AE2-323 C
Solar/Wind Harmer
0.006
247521TR3_G114
Solar/Wind Harmer
0.26
270246TR4_N_V150
Solar/Wind Harmer
0.046
944231AF1-091 GEN
Solar/Wind Harmer
1.84
24695305TIMB G C
Solar/Wind Harmer
0.002
965651AG1-433 GEN
Solar/Wind Harmer
1.823
958861AF2-177 GEN
Solar/Wind Harmer
2.615
945111AF1-176 GEN
Solar/Wind Harmer
10.481
270505AE1-170 C O1
Solar/Wind Harmer
6.013
945371AF1-202 GEN
Solar/Wind Harmer
0
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.942
970245AG2-165 GEN
Solar/Wind Harmer
2.283
970373AG2-245 GEN
Solar/Wind Harmer
11.033
274751CRETE EC ;1U
Adder
6.177
274754CRETE EC ;4U
Adder
6.177
274723RIVER EC ;12
Adder
13.388
274812UNIV PK N;8U
Adder
3.711
276164X3-005 C
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0.004
274773LINCOLN ;4U
Adder
6.227
274774LINCOLN ;5U
Adder
6.227
274801UNIV PARK;4U
Adder
4.262
276776AD2-060 GEN
Solar/Wind Harmer
0.532
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
6.6
941551AE2-152 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
22.162
274674JOLIET 9 ;6U
Adder
11.098
274732ELWOOD EC;7P
Adder
11.843
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
6.22
274745AC1-111 GEN9
Adder
3.978
276691AA1-018 GEN1
Solar/Wind Harmer
0.598
274682WAUKEGAN ;7U
Adder
12.642
970291AG2-192 GEN
Solar/Wind Harmer
0.638
274828WAUKEGAN ;BP
Adder
7.76
270005AE1-210 C O1
Solar/Wind Harmer
1.056
965031AG1-367 GEN
Solar/Wind Harmer
4.875
962781AG1-127 GEN
Solar/Wind Harmer
4.624
939401AE1-172 GEN
Solar/Wind Harmer
3.633
276901AD2-066 C O1
Solar/Wind Harmer
0.005
270032AE2-172
Solar/Wind Harmer
3.233
274872LEEDK;1U
Solar/Wind Harmer
0.003
971997AH1-543 GEN
Solar/Wind Harmer
2.531
276861AD2-134 GEN
Solar/Wind Harmer
0.086
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
24791305MDL-5G
Solar/Wind Harmer
0.001
957471AF2-041 GEN
Solar/Wind Harmer
14.315
959081AF2-199 GEN
Solar/Wind Harmer
4.772
971067AG2-660 GEN
Solar/Wind Harmer
1.591
274822ROCKFORD ;11
Adder
13.38
970825AG2-519 GEN
Solar/Wind Harmer
1.686
972235AH1-702 GEN1
Adder
1.714
970819AG2-516 GEN
Solar/Wind Harmer
5.675
970569AG2-363 GEN
Solar/Wind Harmer
14.175
971475AH1-234 GEN
Solar/Wind Harmer
2.289
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
6.232
274766LEE CO EC;7U
Adder
6.158
276903AD2-071 C
Solar/Wind Harmer
5.188
276158O29GEN2
Solar/Wind Harmer
0.001
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.002
274877BISHOP HL;1U
Solar/Wind Harmer
0.154
276726Z2-087_GEN
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
6.361
274854TWINGROVE;U2
Solar/Wind Harmer
0.002
972175AH1-670 GEN
Solar/Wind Harmer
3.579
963741AG1-226 GEN
Solar/Wind Harmer
10.198
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
3.15
247536S-71 GEN
Solar/Wind Harmer
0.171
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
1.633
276615X2-022 GEN
Solar/Wind Harmer
0.043
965911AG1-460 GEN
Solar/Wind Harmer
0.798
24728605AND G2
Adder
2.013
970773AG2-487 GEN
Solar/Wind Harmer
0.599
270445AC2-157 GEN2
Solar/Wind Harmer
0.001
970333AG2-219 GEN
Solar/Wind Harmer
2.176
270462AD2-086
Solar/Wind Helper
3.736
270223U2-072_GEN1
Solar/Wind Helper
0.877
270578AF1-285 GEN2
Solar/Wind Helper
0.594
270391AF1-285 GEN3
Solar/Wind Helper
0.594
247522W1-056 GEN
Solar/Wind Helper
1.179
960841AF2-375 GEN
Solar/Wind Helper
1.188
270349AD2-093_GEN
Solar/Wind Helper
0.862
965431AG1-411 GEN
50/50
45.318
24727105RPMNG2
50/50
3.312
970583AG2-370 GEN
50/50
2.791
270491AE1-102 GEN2
Solar/Wind Harmer
3.72
959331AF2-224 GEN
Solar/Wind Harmer
9.596
965021AG1-366 GEN
Solar/Wind Harmer
4.57
970031AG2-029 GEN
Solar/Wind Harmer
5.428
270043AE2-236 GEN
Solar/Wind Harmer
5.157
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.046
944531AF1-118 GEN
Solar/Wind Harmer
31.245
971617AH1-308 GEN
Solar/Wind Harmer
5.12
247643Z2-116 C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
4.761
970349AG2-230 GEN
Solar/Wind Harmer
8.606
24642205MAYFLWER
Adder
0.519
24441205WTRV SLR C
Solar/Wind Harmer
0
970513AG2-328 GEN
Solar/Wind Harmer
2.283
970517AG2-330 GEN
Solar/Wind Harmer
13.699
274752CRETE EC ;2U
Adder
6.177
274753CRETE EC ;3U
Adder
6.177
274724RIVER EC ;11
Adder
13.226
247604X1-042
Adder
0.309
270535AF1-215 GEN1
Solar/Wind Harmer
0.006
274772LINCOLN ;3U
Adder
6.227
274802UNIV PARK;5U
Adder
4.274
274826FISK ;BP
Adder
8.017
274800UNIV PARK;3U
Adder
4.262
972038AH1-567 GEN2
Adder
0.267
276806AD2-047 C O1
Solar/Wind Harmer
2.886
970941AG2-585 GEN
Solar/Wind Harmer
6.366
964401AG1-302 GEN
Solar/Wind Harmer
0.001
972228AH1-698 GEN2
Adder
2.696
970707AG2-453 GEN
Solar/Wind Harmer
16.532
276897AD1-100 C
Solar/Wind Harmer
0.007
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
21.371
276893AG1-478 C
Solar/Wind Harmer
0.199
274729ELWOOD EC;1P
Adder
11.842
274730ELWOOD EC;6P
Adder
11.843
274734ELWOOD EC;8P
Adder
11.843
274736ELWOOD EC;9P
Adder
11.843
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
943121AE2-341 GEN
Solar/Wind Harmer
8.328
943591AF1-030 GEN
Solar/Wind Harmer
5.538
247642Z2-115 C
Solar/Wind Harmer
0.002
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
12.642
970289AG2-191 GEN
Solar/Wind Harmer
0.539
970291AG2-192 GEN
Solar/Wind Harmer
0.49
958821AF2-173 GEN
Solar/Wind Harmer
6.825
270004AE1-209 GEN
Solar/Wind Harmer
1.056
276805AD2-038 GEN
Solar/Wind Harmer
0.001
274872LEEDK;1U
Solar/Wind Harmer
0.178
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.512
274855GSG-6 ;RU
Solar/Wind Harmer
0.176
274850MENDOTA H;RU
Solar/Wind Harmer
0.057
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.086
276889AE2-281 GEN
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
4.78
959091AF2-200 GEN
Solar/Wind Harmer
9.543
972236AH1-702 GEN2
Adder
1.491
970571AG2-364 GEN
Solar/Wind Harmer
9.45
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
6.232
274767LEE CO EC;8U
Adder
6.158
946031AF1-268 GEN
Solar/Wind Harmer
4.44
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
6.987
276157O29GEN1
Solar/Wind Harmer
0.746
274878BISHOP HL;2U
Solar/Wind Harmer
0.154
942111AE2-223 GEN
Solar/Wind Harmer
1.477
965931AG1-462 GEN
Solar/Wind Harmer
11.384
274853TWINGROVE;U1
Solar/Wind Harmer
0.002
965091AG1-374 GEN
Solar/Wind Harmer
13.388
959611AF2-252 GEN
Solar/Wind Harmer
1.488
270437AC2-090 C
Solar/Wind Harmer
0.002
276686W4-005 GEN3
Solar/Wind Harmer
0.001
276668AB2-070 GEN1
Solar/Wind Harmer
0.154
971993AH1-541 GEN
Solar/Wind Harmer
1.946
276621W2-048 GEN
Solar/Wind Harmer
0.209
276838X2-022 GEN2
Solar/Wind Harmer
0.233
942481AE2-261 GEN
Solar/Wind Harmer
11.923
970193AG2-126 GEN
Solar/Wind Harmer
5.78
270404AC1-167 GEN
Solar/Wind Harmer
0.002
270258AD1-119 GEN
Solar/Wind Harmer
0.001
24728705AND G3
Adder
4.21
24728505AND G1
Adder
2.013
970615AG2-402 GEN
50/50
4.57
24729405KEY G3
50/50
0.365
24729305KEY G2
50/50
0.359
24729205KEY G1
50/50
0.357
247620Y3-023
50/50
0.459
246938BC-WTG3
Solar/Wind Harmer
1.037
246937BC-WTG2
Solar/Wind Harmer
1.161
970611AG2-400 GEN
Solar/Wind Harmer
13.709
970627AG2-408 GEN
Solar/Wind Harmer
4.113
942221AE2-234 GEN
Solar/Wind Harmer
0.034
944541AF1-119 GEN
Solar/Wind Harmer
0.416
960971AF2-388 GEN
Solar/Wind Harmer
3.647
270216AD2-079_GEN
Solar/Wind Harmer
0.001
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
11.449
961051AF2-396 GEN
Solar/Wind Harmer
7.632
270526AF1-158 GEN
Solar/Wind Harmer
0.007
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
6.819
965791AG1-447 GEN
Solar/Wind Harmer
5.001
270599AE1-208 GEN
Solar/Wind Harmer
4.943
270031AE2-169
Solar/Wind Harmer
2.966
970321AG2-212 GEN
Solar/Wind Harmer
2.283
274808UNIV PK N;4U
Adder
3.694
274770LINCOLN ;1U
Adder
6.227
274771LINCOLN ;2U
Adder
6.227
274803UNIV PARK;6U
Adder
4.274
274888KELLY CRK;1U
Solar/Wind Harmer
0.299
274887GEN-1.85
Solar/Wind Harmer
0.134
276843GEN-1.7
Solar/Wind Harmer
0.165
958011AF2-095 GEN
Solar/Wind Harmer
7.334
972259AH1-714 GEN
Adder
13.842
274674JOLIET 9 ;6U
Adder
11.098
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
971573AH1-285 GEN
Solar/Wind Harmer
0.921
958481AF2-142 GEN
Solar/Wind Harmer
7.4
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.667
274696ROCKY RD ;4P
Adder
8.021
274695ROCKY RD ;2P
Adder
7.836
274693ROCKY RD ;1P
Adder
7.759
274697ROCKY RD ;3P
Adder
2.129
274683WAUKEGAN ;8U
Adder
14.804
274683WAUKEGAN ;8U
Adder
12.479
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
962691AG1-118 GEN
Solar/Wind Harmer
14.613
958491AF2-143 GEN
Solar/Wind Harmer
7.306
970921AG2-575 GEN
Solar/Wind Harmer
4.859
970921AG2-575 GEN
Solar/Wind Harmer
1.62
971613AH1-306 GEN
Solar/Wind Harmer
2.328
274879MINONK ;1U
Solar/Wind Harmer
0.204
942991AE2-321 GEN
Solar/Wind Harmer
5.39
971333AH1-146 GEN
Solar/Wind Harmer
9.601
971335AH1-147 GEN
Solar/Wind Harmer
9.601
960441AF2-335 GEN
Solar/Wind Harmer
4.786
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
971341AH1-150 GEN
Solar/Wind Harmer
9.543
971343AH1-151 GEN
Solar/Wind Harmer
9.543
970825AG2-519 GEN
Solar/Wind Harmer
5.263
274856ECOGROVE ;U1
Solar/Wind Harmer
0.111
276611AD2-172 GEN
Solar/Wind Harmer
0.001
938861AE1-114 GEN
Solar/Wind Harmer
2.658
274764LEE CO EC;5U
Adder
6.246
274765LEE CO EC;6U
Adder
6.246
274762LEE CO EC;3U
Adder
6.232
274763LEE CO EC;4U
Adder
6.173
276603SUBLETTE C
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.349
270201AC2-176 GEN
Solar/Wind Harmer
0.001
972267AH1-718 GEN
Adder
2.761
276741O09 GEN1
Solar/Wind Harmer
0.164
276708O09 GEN2
Solar/Wind Harmer
0.164
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.181
276646AC1-214 GEN2
Solar/Wind Harmer
0.181
966841AG1-555 GEN
Solar/Wind Harmer
0.519
276782AC1-033 GEN
Solar/Wind Harmer
0.001
247621Y3-024
Adder
0.158
960611AF2-352 GEN
Solar/Wind Harmer
1.488
970241AG2-163 GEN
Solar/Wind Harmer
2.514
24379505HDWTR1G C
Solar/Wind Harmer
0.001
270209AC1-174_GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
270383AD1-128 GEN
Solar/Wind Harmer
0.002
276916AD2-100_GEN
Solar/Wind Harmer
8.299
276911AD2-131_GEN
Solar/Wind Harmer
0.547
970883AG2-550 GEN
Solar/Wind Harmer
3.858
970885AG2-551 GEN
Solar/Wind Harmer
1.286
945391AF1-204 GEN
Solar/Wind Harmer
4.094
970623AG2-406 GEN
Solar/Wind Harmer
0.671
270444AC2-157 GEN1
Solar/Wind Harmer
0.001
971587AH1-292 GEN
Solar/Wind Harmer
2.387
270007AE1-245 C
Solar/Wind Harmer
0.001
970239AG2-162 GEN
Solar/Wind Harmer
0.761
270224U2-072_GEN2
Solar/Wind Helper
0.877
270227U2-072_GEN3
Solar/Wind Helper
0.877
270228U2-072_GEN4
Solar/Wind Helper
0.877
270231U2-072_GEN5
Solar/Wind Helper
0.877
270471AD2-092_GEN
Solar/Wind Helper
0.862
253378AE2-206_GEN
Solar/Wind Helper
0.694
276820AF1-078_GEN
Solar/Wind Helper
0.324
241960AC2-195 GEN
Solar/Wind Helper
0.702
24727205RPMNG3
50/50
3.285
971599AH1-298 GEN
50/50
10.265
24729505KEY G4
50/50
6.681
957201AF2-014 GEN
Solar/Wind Harmer
0.002
270435AC2-044 GEN
Solar/Wind Harmer
3.625
963791AG1-232 GEN
Solar/Wind Harmer
11.533
965041AG1-368 GEN
Solar/Wind Harmer
8.372
270071AF1-092 GEN
Solar/Wind Harmer
14.295
965051AG1-369 GEN
Solar/Wind Harmer
3.565
270024AE2-089 GEN
Solar/Wind Harmer
0.007
965101AG1-375 GEN
Solar/Wind Harmer
6.034
971771AH1-392 GEN
Solar/Wind Harmer
5.793
971347AH1-153 GEN
Solar/Wind Harmer
8.606
971619AH1-309 GEN
Solar/Wind Harmer
2.577
945581AF1-223 GEN
Solar/Wind Harmer
0
971769AH1-391 GEN
Solar/Wind Harmer
6.222
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971609AH1-304 GEN
Solar/Wind Harmer
0.881
274814UNIV PK N;0U
Adder
3.743
274807UNIV PK N;3U
Adder
3.735
274805UNIV PK N;1U
Adder
3.719
274811UNIV PK N;7U
Adder
3.711
270536AF1-215 GEN2
Solar/Wind Harmer
0.006
274775LINCOLN ;6U
Adder
6.227
274776LINCOLN ;7U
Adder
6.227
274777LINCOLN ;8U
Adder
6.227
972037AH1-567 GEN1
Adder
0.134
274827FISK ;RP
Adder
5.682
960591AF2-350 GEN
Solar/Wind Harmer
5.093
972227AH1-698 GEN1
Adder
1.898
274687WILL CNTY;4U
Adder
20.23
274687WILL CNTY;4U
Adder
20.23
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274675JOLIET 29;7U
Adder
22.163
274675JOLIET 29;7U
Adder
21.371
274731ELWOOD EC;2P
Adder
11.842
274733ELWOOD EC;3P
Adder
11.842
274735ELWOOD EC;4P
Adder
11.842
274728ELWOOD EC;5P
Adder
11.843
970833AG2-524 GEN
Solar/Wind Harmer
5.503
970833AG2-524 GEN
Solar/Wind Harmer
3.669
971611AH1-305 GEN
Solar/Wind Harmer
2.963
274746AC1-111 G10
Adder
3.978
274744AC1-111 GEN8
Adder
3.978
970289AG2-191 GEN
Solar/Wind Harmer
0.932
270594AE1-207 GEN
Solar/Wind Harmer
5.432
276868AE1-113 GEN
Solar/Wind Harmer
0.971
276882AE2-255 GEN
Solar/Wind Harmer
0.566
971177AH1-047 GEN
Solar/Wind Harmer
2.975
971411AH1-196 GEN
Solar/Wind Harmer
7.208
971675AH1-338 GEN
Solar/Wind Harmer
1.873
970115AG2-085 GEN
Solar/Wind Harmer
1.915
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
9.543
274823ROCKFORD ;21
Adder
13.283
276612AE2-035 GEN
Solar/Wind Harmer
0.001
926823AC1-168 GEN
Solar/Wind Harmer
0.802
970169AG2-114 GEN
Solar/Wind Harmer
4.71
971681AH1-341 GEN
Solar/Wind Harmer
7.556
971549AH1-272 GEN
Solar/Wind Harmer
9.681
961011AF2-392 GEN
Solar/Wind Harmer
2.722
957751AF2-069 GEN
Solar/Wind Harmer
0.152
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
276655WTG1_EQ
Solar/Wind Harmer
0.002
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
4.771
941731AE2-173 GEN
Solar/Wind Harmer
3.786
946321AF1-296 GEN
Solar/Wind Harmer
2.514
963841AG1-237 GEN
Solar/Wind Harmer
1.925
270240V3-007_GEN2
Solar/Wind Harmer
0.001
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.154
276848AB2-070 GEN3
Solar/Wind Harmer
0.153
270543AE2-219 C
Solar/Wind Harmer
0.002
944221AF1-090 GEN
Solar/Wind Harmer
2.247
971029AG2-637 GEN
Solar/Wind Harmer
5.161
971673AH1-337 GEN
Solar/Wind Harmer
2.14
247607V1-011 GEN
Solar/Wind Harmer
0.001
270317AD1-130_GEN
Solar/Wind Helper
4.139
966831AG1-554 GEN
Solar/Wind Helper
0.884
270284AF1-227 GEN1
Solar/Wind Helper
1.894
270286AF1-227 GEN2
Solar/Wind Helper
0.695
270287AF1-227 GEN3
Solar/Wind Helper
0.695
270499AE1-146 GEN
Solar/Wind Helper
1.973
945641AF1-229 GEN
Solar/Wind Helper
0.949
270356AE2-297 GEN
Solar/Wind Harmer
0.005
970243AG2-164 GEN
Solar/Wind Harmer
1.781
970519AG2-331 GEN
Solar/Wind Harmer
7.913
970699AG2-449 GEN
Solar/Wind Harmer
0.761
270485AE1-090_GEN
Solar/Wind Helper
0.325
942871AE2-306 GEN
Solar/Wind Helper
0.446
270541AE2-072 C
Solar/Wind Helper
0.947
944201AF1-088_MTX
Adder
54.26
957141AF2-008_MTX
Adder
17.407
990792J1392
External Queue
5.474584102630615
990497J1323
External Queue
1.5914489030838013
NYPJM->LTFIMP_NY
CLTF
1.315
LGEELTFEXP_LGEE->PJM
CLTF
1.728
WECLTFEXP_WEC->PJM
CLTF
2.594
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.108
AG2-052LTFEXP_AG2-052->PJM
LTF
0.168
AH1-155LTFEXP_AH1-155->PJM
LTF
0.252
LAGNLTFEXP_LAGN->PJM
CLTF
5.535
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.203
TVALTFEXP_TVA->PJM
CLTF
2.191
CBM West 1LTFEXP_CBM-W1->PJM
CBM
68.17
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.448
MECLTFEXP_MEC->PJM
CLTF
9.525
SIGELTFEXP_SIGE->PJM
CLTF
0.193
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.893

Details for 05MALIS-05VASSEL 765.0 kV Ckt 1 line l/o AP_P1-3_MP-765-501T_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MALIS-05VASSEL 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-501T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:130.8 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:5417.86
MW Contribution:3.78
Bus #Bus NameTypeMW Contribution
270102X2-052 ST
50/50
2.042
270100X2-052 CT1
50/50
1.881
270101X2-052 CT2
50/50
1.881
970321AG2-212 GEN
Solar/Wind Harmer
4.024
965681AG1-436 GEN
Solar/Wind Harmer
11.102
965791AG1-447 GEN
Solar/Wind Harmer
8.141
274770LINCOLN ;1U
Adder
10.698
274771LINCOLN ;2U
Adder
10.698
270526AF1-158 GEN
Solar/Wind Harmer
0.011
24441505OLIV SLR
Solar/Wind Harmer
0
270216AD2-079_GEN
Solar/Wind Harmer
0.001
274808UNIV PK N;4U
Adder
6.241
957891AF2-083 GEN
Solar/Wind Harmer
0.001
972259AH1-714 GEN
Adder
23.861
247620Y3-023
Adder
0.576
274803UNIV PARK;6U
Adder
7.284
274888KELLY CRK;1U
Solar/Wind Harmer
0.512
274887GEN-1.85
Solar/Wind Harmer
0.23
276843GEN-1.7
Solar/Wind Harmer
0.282
958011AF2-095 GEN
Solar/Wind Harmer
12.553
274674JOLIET 9 ;6U
Adder
19.145
961051AF2-396 GEN
Solar/Wind Harmer
17.339
961051AF2-396 GEN
Solar/Wind Harmer
11.56
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
971573AH1-285 GEN
Solar/Wind Harmer
1.607
970611AG2-400 GEN
Solar/Wind Harmer
8.612
970627AG2-408 GEN
Solar/Wind Harmer
2.584
274695ROCKY RD ;2P
Adder
13.703
274693ROCKY RD ;1P
Adder
13.569
274697ROCKY RD ;3P
Adder
3.723
274696ROCKY RD ;4P
Adder
14.027
958481AF2-142 GEN
Solar/Wind Harmer
12.872
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
1.161
274683WAUKEGAN ;8U
Adder
25.892
274683WAUKEGAN ;8U
Adder
21.826
962691AG1-118 GEN
Solar/Wind Harmer
25.667
970921AG2-575 GEN
Solar/Wind Harmer
8.545
970921AG2-575 GEN
Solar/Wind Harmer
2.848
958491AF2-143 GEN
Solar/Wind Harmer
12.795
274879MINONK ;1U
Solar/Wind Harmer
0.359
942991AE2-321 GEN
Solar/Wind Harmer
9.503
971333AH1-146 GEN
Solar/Wind Harmer
16.975
971335AH1-147 GEN
Solar/Wind Harmer
16.975
971341AH1-150 GEN
Solar/Wind Harmer
16.925
971343AH1-151 GEN
Solar/Wind Harmer
16.925
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
944541AF1-119 GEN
Solar/Wind Harmer
0.565
960971AF2-388 GEN
Solar/Wind Harmer
4.95
274856ECOGROVE ;U1
Solar/Wind Harmer
0.198
276611AD2-172 GEN
Solar/Wind Harmer
0.002
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
938861AE1-114 GEN
Solar/Wind Harmer
4.753
274764LEE CO EC;5U
Adder
11.19
274765LEE CO EC;6U
Adder
11.19
274762LEE CO EC;3U
Adder
11.164
274763LEE CO EC;4U
Adder
11.058
276603SUBLETTE C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
4.971
276741O09 GEN1
Solar/Wind Harmer
0.296
276708O09 GEN2
Solar/Wind Harmer
0.296
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.327
276646AC1-214 GEN2
Solar/Wind Harmer
0.327
276782AC1-033 GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.006
960611AF2-352 GEN
Solar/Wind Harmer
2.732
966841AG1-555 GEN
Solar/Wind Harmer
0.926
942221AE2-234 GEN
Solar/Wind Harmer
0.041
970241AG2-163 GEN
Solar/Wind Harmer
4.649
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
24721605FLATG1
50/50
1.721
971599AH1-298 GEN
50/50
12.006
962771AG1-126 GEN
Solar/Wind Harmer
74.429
971347AH1-153 GEN
Solar/Wind Harmer
13.852
270071AF1-092 GEN
Solar/Wind Harmer
17.275
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
274775LINCOLN ;6U
Adder
10.698
274776LINCOLN ;7U
Adder
10.698
274777LINCOLN ;8U
Adder
10.698
971771AH1-392 GEN
Solar/Wind Harmer
8.844
971769AH1-391 GEN
Solar/Wind Harmer
9.861
24729505KEY G4
Adder
8.122
274814UNIV PK N;0U
Adder
6.324
274807UNIV PK N;3U
Adder
6.31
274805UNIV PK N;1U
Adder
6.283
274811UNIV PK N;7U
Adder
6.269
971619AH1-309 GEN
Solar/Wind Harmer
3.929
274827FISK ;RP
Adder
9.695
972037AH1-567 GEN1
Adder
0.229
960591AF2-350 GEN
Solar/Wind Harmer
8.717
972227AH1-698 GEN1
Adder
3.259
274687WILL CNTY;4U
Adder
34.788
274687WILL CNTY;4U
Adder
34.788
274675JOLIET 29;7U
Adder
38.179
274675JOLIET 29;7U
Adder
36.815
274731ELWOOD EC;2P
Adder
20.43
274733ELWOOD EC;3P
Adder
20.43
274735ELWOOD EC;4P
Adder
20.43
274728ELWOOD EC;5P
Adder
20.43
970833AG2-524 GEN
Solar/Wind Harmer
9.537
970833AG2-524 GEN
Solar/Wind Harmer
6.358
274746AC1-111 G10
Adder
6.922
274744AC1-111 GEN8
Adder
6.922
270536AF1-215 GEN2
Solar/Wind Harmer
0.011
958391AF2-133 GEN
Solar/Wind Harmer
0.001
276868AE1-113 GEN
Solar/Wind Harmer
1.708
276882AE2-255 GEN
Solar/Wind Harmer
0.995
971177AH1-047 GEN
Solar/Wind Harmer
5.247
971675AH1-338 GEN
Solar/Wind Harmer
3.312
971411AH1-196 GEN
Solar/Wind Harmer
12.736
274863CRW1-WTG
Solar/Wind Harmer
0.003
274864CRW2-WTG
Solar/Wind Harmer
0.003
971611AH1-305 GEN
Solar/Wind Harmer
5.049
971171AH1-044 GEN
Solar/Wind Harmer
16.925
274823ROCKFORD ;21
Adder
23.589
970169AG2-114 GEN
Solar/Wind Harmer
8.416
276612AE2-035 GEN
Solar/Wind Harmer
0.002
926823AC1-168 GEN
Solar/Wind Harmer
1.43
971681AH1-341 GEN
Solar/Wind Harmer
13.508
961011AF2-392 GEN
Solar/Wind Harmer
4.894
965101AG1-375 GEN
Solar/Wind Harmer
8.339
24690905MDL-1G C
Solar/Wind Harmer
0.003
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
957751AF2-069 GEN
Solar/Wind Harmer
0.274
274848CAMPGROVE;RU
Solar/Wind Harmer
0.002
276655WTG1_EQ
Solar/Wind Harmer
0.003
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
8.681
941731AE2-173 GEN
Solar/Wind Harmer
6.89
946321AF1-296 GEN
Solar/Wind Harmer
4.595
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
945581AF1-223 GEN
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
10.958
963841AG1-237 GEN
Solar/Wind Harmer
3.497
965041AG1-368 GEN
Solar/Wind Harmer
8.037
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.291
276848AB2-070 GEN3
Solar/Wind Harmer
0.289
970289AG2-191 GEN
Solar/Wind Harmer
1.512
971549AH1-272 GEN
Solar/Wind Harmer
16.344
971609AH1-304 GEN
Solar/Wind Harmer
1.291
270594AE1-207 GEN
Solar/Wind Harmer
8.813
965051AG1-369 GEN
Solar/Wind Harmer
3.913
270284AF1-227 GEN1
Solar/Wind Harmer
0.01
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
270024AE2-089 GEN
Solar/Wind Harmer
0.008
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
944221AF1-090 GEN
Solar/Wind Harmer
4.485
970115AG2-085 GEN
Solar/Wind Harmer
3.056
270599AE1-208 GEN
Solar/Wind Harmer
7.244
270031AE2-169
Solar/Wind Harmer
4.346
971613AH1-306 GEN
Solar/Wind Harmer
3.777
276916AD2-100_GEN
Solar/Wind Harmer
16.273
276911AD2-131_GEN
Solar/Wind Harmer
1.072
960441AF2-335 GEN
Solar/Wind Harmer
7.639
945391AF1-204 GEN
Solar/Wind Harmer
8.098
970825AG2-519 GEN
Solar/Wind Harmer
8.443
970239AG2-162 GEN
Solar/Wind Harmer
0.651
24722005FLATG5
50/50
1.721
24721905FLATG4
50/50
31.554
970153AG2-106 GEN
Solar/Wind Harmer
47.528
970513AG2-328 GEN
Solar/Wind Harmer
4.024
970517AG2-330 GEN
Solar/Wind Harmer
24.143
970349AG2-230 GEN
Solar/Wind Harmer
13.852
270043AE2-236 GEN
Solar/Wind Harmer
5.825
274772LINCOLN ;3U
Adder
10.698
944531AF1-118 GEN
Solar/Wind Harmer
39.627
247643Z2-116 C
Solar/Wind Harmer
0
274724RIVER EC ;11
Adder
22.251
24642205MAYFLWER
Adder
0.798
274752CRETE EC ;2U
Adder
10.335
274753CRETE EC ;3U
Adder
10.335
970707AG2-453 GEN
Solar/Wind Harmer
28.578
274826FISK ;BP
Adder
13.679
274802UNIV PARK;5U
Adder
7.284
276806AD2-047 C O1
Solar/Wind Harmer
4.94
970941AG2-585 GEN
Solar/Wind Harmer
10.896
972228AH1-698 GEN2
Adder
4.628
274800UNIV PARK;3U
Adder
7.282
972038AH1-567 GEN2
Adder
0.456
945111AF1-176 GEN
Solar/Wind Harmer
7.057
276897AD1-100 C
Solar/Wind Harmer
0.012
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
970031AG2-029 GEN
Solar/Wind Harmer
5.65
274676JOLIET 29;8U
Adder
36.815
274729ELWOOD EC;1P
Adder
20.43
274730ELWOOD EC;6P
Adder
20.43
274734ELWOOD EC;8P
Adder
20.43
274736ELWOOD EC;9P
Adder
20.43
276893AG1-478 C
Solar/Wind Harmer
0.344
943121AE2-341 GEN
Solar/Wind Harmer
14.504
943591AF1-030 GEN
Solar/Wind Harmer
9.645
270535AF1-215 GEN1
Solar/Wind Harmer
0.011
959331AF2-224 GEN
Solar/Wind Harmer
6.029
965021AG1-366 GEN
Solar/Wind Harmer
2.871
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
22.097
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274872LEEDK;1U
Solar/Wind Harmer
0.313
276805AD2-038 GEN
Solar/Wind Harmer
0.002
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
24441205WTRV SLR C
Solar/Wind Harmer
0
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
0.906
274855GSG-6 ;RU
Solar/Wind Harmer
0.311
274850MENDOTA H;RU
Solar/Wind Harmer
0.1
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.152
959091AF2-200 GEN
Solar/Wind Harmer
16.925
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
2.65
247604X1-042
Adder
0.502
970571AG2-364 GEN
Solar/Wind Harmer
16.817
274858EASY ROAD;U2
Solar/Wind Harmer
0.002
274760LEE CO EC;1U
Adder
11.164
274767LEE CO EC;8U
Adder
11.032
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
8.324
276157O29GEN1
Solar/Wind Harmer
1.345
274878BISHOP HL;2U
Solar/Wind Harmer
0.279
942111AE2-223 GEN
Solar/Wind Harmer
2.687
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
965091AG1-374 GEN
Solar/Wind Harmer
24.591
959611AF2-252 GEN
Solar/Wind Harmer
2.732
965931AG1-462 GEN
Solar/Wind Harmer
20.863
247642Z2-115 C
Solar/Wind Harmer
0.003
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
3.685
276668AB2-070 GEN1
Solar/Wind Harmer
0.291
970289AG2-191 GEN
Solar/Wind Harmer
0.875
970291AG2-192 GEN
Solar/Wind Harmer
0.796
276621W2-048 GEN
Solar/Wind Harmer
0.399
276838X2-022 GEN2
Solar/Wind Harmer
0.445
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.051
942481AE2-261 GEN
Solar/Wind Harmer
23.26
958821AF2-173 GEN
Solar/Wind Harmer
10.805
270004AE1-209 GEN
Solar/Wind Harmer
1.672
971617AH1-308 GEN
Solar/Wind Harmer
6.396
970193AG2-126 GEN
Solar/Wind Harmer
11.433
946031AF1-268 GEN
Solar/Wind Harmer
7.175
970243AG2-164 GEN
Solar/Wind Harmer
1.523
970519AG2-331 GEN
Solar/Wind Harmer
6.77
970699AG2-449 GEN
Solar/Wind Harmer
0.651
24721805FLATG3
50/50
1.721
24721705FLATG2
50/50
31.554
24344105CKG2
50/50
10.231
962761AG1-125 GEN
Solar/Wind Harmer
74.429
970149AG2-104 GEN
Solar/Wind Harmer
80.386
970155AG2-107 GEN
Solar/Wind Harmer
47.528
970245AG2-165 GEN
Solar/Wind Harmer
4.024
274773LINCOLN ;4U
Adder
10.698
274774LINCOLN ;5U
Adder
10.698
274723RIVER EC ;12
Adder
22.511
24639705ELKHART HY
Adder
0.193
276164X3-005 C
Solar/Wind Harmer
0
274751CRETE EC ;1U
Adder
10.335
274754CRETE EC ;4U
Adder
10.335
274812UNIV PK N;8U
Adder
6.269
270063AE2-323 C
Solar/Wind Harmer
0.007
270505AE1-170 C O1
Solar/Wind Harmer
9.167
276776AD2-060 GEN
Solar/Wind Harmer
0.91
274801UNIV PARK;4U
Adder
7.282
970373AG2-245 GEN
Solar/Wind Harmer
18.295
945111AF1-176 GEN
Solar/Wind Harmer
15.535
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
38.179
274674JOLIET 9 ;6U
Adder
19.145
274732ELWOOD EC;7P
Adder
20.43
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
4.514
274745AC1-111 GEN9
Adder
6.922
270055AF2-134 C O1
Solar/Wind Harmer
0.007
965011AG1-365 GEN
Solar/Wind Harmer
8.612
276691AA1-018 GEN1
Solar/Wind Harmer
1.04
274682WAUKEGAN ;7U
Adder
22.097
274828WAUKEGAN ;BP
Adder
13.572
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
11.134
939401AE1-172 GEN
Solar/Wind Harmer
6.393
962781AG1-127 GEN
Solar/Wind Harmer
8.132
274872LEEDK;1U
Solar/Wind Harmer
0.005
276901AD2-066 C O1
Solar/Wind Harmer
0.008
971997AH1-543 GEN
Solar/Wind Harmer
4.464
276861AD2-134 GEN
Solar/Wind Harmer
0.152
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
10.6
957471AF2-041 GEN
Solar/Wind Harmer
25.388
959081AF2-199 GEN
Solar/Wind Harmer
8.463
971067AG2-660 GEN
Solar/Wind Harmer
2.821
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
274822ROCKFORD ;11
Adder
23.761
965651AG1-433 GEN
Solar/Wind Harmer
2.475
972235AH1-702 GEN1
Adder
3.048
970819AG2-516 GEN
Solar/Wind Harmer
10.106
970569AG2-363 GEN
Solar/Wind Harmer
25.226
971475AH1-234 GEN
Solar/Wind Harmer
4.081
274857EASY ROAD;U1
Solar/Wind Harmer
0.002
274761LEE CO EC;2U
Adder
11.164
274766LEE CO EC;7U
Adder
11.032
958861AF2-177 GEN
Solar/Wind Harmer
3.614
24791305MDL-5G
Solar/Wind Harmer
0.001
276158O29GEN2
Solar/Wind Harmer
0.001
274877BISHOP HL;1U
Solar/Wind Harmer
0.279
270349AD2-093_GEN
Solar/Wind Harmer
0.006
276726Z2-087_GEN
Solar/Wind Harmer
0.003
939741AE1-205 GEN
Solar/Wind Harmer
11.575
274854TWINGROVE;U2
Solar/Wind Harmer
0.004
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
945371AF1-202 GEN
Solar/Wind Harmer
0.001
972175AH1-670 GEN
Solar/Wind Harmer
6.679
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963741AG1-226 GEN
Solar/Wind Harmer
18.86
970291AG2-192 GEN
Solar/Wind Harmer
1.034
963831AG1-236 GEN
Solar/Wind Harmer
3.102
276615X2-022 GEN
Solar/Wind Harmer
0.083
270032AE2-172
Solar/Wind Harmer
5.246
247521TR3_G114
Solar/Wind Harmer
0.286
270246TR4_N_V150
Solar/Wind Harmer
0.051
965911AG1-460 GEN
Solar/Wind Harmer
1.556
276903AD2-071 C
Solar/Wind Harmer
8.661
270005AE1-210 C O1
Solar/Wind Harmer
1.672
965031AG1-367 GEN
Solar/Wind Harmer
7.718
944231AF1-091 GEN
Solar/Wind Harmer
2.052
24695305TIMB G C
Solar/Wind Harmer
0.002
970825AG2-519 GEN
Solar/Wind Harmer
2.704
970333AG2-219 GEN
Solar/Wind Harmer
1.862
944201AF1-088_MTX
Adder
121.789
957141AF2-008_MTX
Adder
33.652
NYPJM->LTFIMP_NY
CLTF
3.894
LGEELTFEXP_LGEE->PJM
CLTF
5.997
WECLTFEXP_WEC->PJM
CLTF
4.617
AG2-052LTFEXP_AG2-052->PJM
LTF
0.285
AH1-155LTFEXP_AH1-155->PJM
LTF
0.427
LAGNLTFEXP_LAGN->PJM
CLTF
16.714
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.261
TVALTFEXP_TVA->PJM
CLTF
7.962
CBM West 1LTFEXP_CBM-W1->PJM
CBM
148.673
CBM South 1LTFEXP_CBM-S1->PJM
CBM
30.42
MECLTFEXP_MEC->PJM
CLTF
18.605
SIGELTFEXP_SIGE->PJM
CLTF
0.498
CPLELTFEXP_CPLE->PJM
CLTF
3.263
CBM West 2LTFEXP_CBM-W2->PJM
CBM
123.519

Details for 05MALIS-05VASSEL 765.0 kV Ckt 1 line l/o AEP_P1-2_#706_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MALIS-05VASSEL 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#706_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.0 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4722.06
MW Contribution:3.94
Bus #Bus NameTypeMW Contribution
970615AG2-402 GEN
50/50
3.439
247620Y3-023
50/50
0.701
270102X2-052 ST
50/50
2.279
270100X2-052 CT1
50/50
2.1
270101X2-052 CT2
50/50
2.1
270471AD2-092_GEN
Solar/Wind Harmer
0.009
970611AG2-400 GEN
Solar/Wind Harmer
10.316
970627AG2-408 GEN
Solar/Wind Harmer
3.095
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
970321AG2-212 GEN
Solar/Wind Harmer
4.403
270216AD2-079_GEN
Solar/Wind Harmer
0.002
957891AF2-083 GEN
Solar/Wind Harmer
0.001
270526AF1-158 GEN
Solar/Wind Harmer
0.012
961051AF2-396 GEN
Solar/Wind Harmer
19.83
961051AF2-396 GEN
Solar/Wind Harmer
13.22
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
12.351
965791AG1-447 GEN
Solar/Wind Harmer
9.057
274770LINCOLN ;1U
Adder
11.607
274771LINCOLN ;2U
Adder
11.607
274808UNIV PK N;4U
Adder
6.763
274803UNIV PARK;6U
Adder
7.866
274888KELLY CRK;1U
Solar/Wind Harmer
0.552
274887GEN-1.85
Solar/Wind Harmer
0.248
276843GEN-1.7
Solar/Wind Harmer
0.304
958011AF2-095 GEN
Solar/Wind Harmer
13.537
972259AH1-714 GEN
Adder
25.697
246938BC-WTG3
Solar/Wind Harmer
0.34
246937BC-WTG2
Solar/Wind Harmer
0.381
274674JOLIET 9 ;6U
Adder
20.555
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
944541AF1-119 GEN
Solar/Wind Harmer
0.622
960971AF2-388 GEN
Solar/Wind Harmer
5.442
971573AH1-285 GEN
Solar/Wind Harmer
1.715
958481AF2-142 GEN
Solar/Wind Harmer
13.715
274696ROCKY RD ;4P
Adder
14.93
274695ROCKY RD ;2P
Adder
14.586
274693ROCKY RD ;1P
Adder
14.442
274697ROCKY RD ;3P
Adder
3.962
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
1.237
274683WAUKEGAN ;8U
Adder
27.535
274683WAUKEGAN ;8U
Adder
23.211
962691AG1-118 GEN
Solar/Wind Harmer
27.238
942221AE2-234 GEN
Solar/Wind Harmer
0.045
970921AG2-575 GEN
Solar/Wind Harmer
9.059
970921AG2-575 GEN
Solar/Wind Harmer
3.02
24721805FLATG3
50/50
4.694
24721705FLATG2
50/50
86.059
24344105CKG2
50/50
11.607
270143AC1-141 CT2_
50/50
3.444
24639705ELKHART HY
50/50
0.234
970521AG2-332 GEN
50/50
16.668
24307105BERRINSP G
50/50
0.031
962761AG1-125 GEN
Solar/Wind Harmer
109.549
970149AG2-104 GEN
Solar/Wind Harmer
118.317
970155AG2-107 GEN
Solar/Wind Harmer
69.955
270349AD2-093_GEN
Solar/Wind Harmer
0.009
965011AG1-365 GEN
Solar/Wind Harmer
10.316
270223U2-072_GEN1
Solar/Wind Harmer
0.001
970245AG2-165 GEN
Solar/Wind Harmer
4.403
270063AE2-323 C
Solar/Wind Harmer
0.008
270505AE1-170 C O1
Solar/Wind Harmer
10.468
945111AF1-176 GEN
Solar/Wind Harmer
17.757
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
5.164
270462AD2-086
Solar/Wind Harmer
0.02
274773LINCOLN ;4U
Adder
11.607
274774LINCOLN ;5U
Adder
11.607
247521TR3_G114
Solar/Wind Harmer
0.349
270246TR4_N_V150
Solar/Wind Harmer
0.062
274723RIVER EC ;12
Adder
24.46
274751CRETE EC ;1U
Adder
11.24
274754CRETE EC ;4U
Adder
11.24
970373AG2-245 GEN
Solar/Wind Harmer
19.935
276164X3-005 C
Solar/Wind Harmer
0
965421AG1-410 GEN
Solar/Wind Harmer
28.417
274812UNIV PK N;8U
Adder
6.792
24695305TIMB G C
Solar/Wind Harmer
0.002
276776AD2-060 GEN
Solar/Wind Harmer
0.981
274801UNIV PARK;4U
Adder
7.856
246936BC-WTG1
Solar/Wind Harmer
0.381
270489AE1-102 GEN1
Solar/Wind Harmer
1.22
941551AE2-152 GEN
Solar/Wind Harmer
0.001
944231AF1-091 GEN
Solar/Wind Harmer
2.492
274676JOLIET 29;8U
Adder
41.022
270055AF2-134 C O1
Solar/Wind Harmer
0.007
274674JOLIET 9 ;6U
Adder
20.555
274732ELWOOD EC;7P
Adder
21.93
24721605FLATG1
50/50
4.694
971599AH1-298 GEN
50/50
14.063
270144AC1-141 ST1_
50/50
3.051
24653605MOTTVILLE
50/50
0.005
24643105BUCHANAN
50/50
0.018
270036AE2-216 BAT
50/50
8.975
962771AG1-126 GEN
Solar/Wind Harmer
109.549
270284AF1-227 GEN1
Solar/Wind Harmer
0.015
270286AF1-227 GEN2
Solar/Wind Harmer
0.006
270287AF1-227 GEN3
Solar/Wind Harmer
0.006
971347AH1-153 GEN
Solar/Wind Harmer
15.658
270578AF1-285 GEN2
Solar/Wind Harmer
0.683
270071AF1-092 GEN
Solar/Wind Harmer
19.582
971771AH1-392 GEN
Solar/Wind Harmer
10.018
971619AH1-309 GEN
Solar/Wind Harmer
4.486
971769AH1-391 GEN
Solar/Wind Harmer
11.066
960681AF2-359 GEN
Solar/Wind Harmer
-0.002
270302AB2-170 GEN
Solar/Wind Harmer
0.006
270317AD1-130_GEN
Solar/Wind Harmer
0.014
971653AH1-327 GEN
Solar/Wind Harmer
1.377
24729505KEY G4
Adder
9.092
965041AG1-368 GEN
Solar/Wind Harmer
9.739
274775LINCOLN ;6U
Adder
11.607
274776LINCOLN ;7U
Adder
11.607
274777LINCOLN ;8U
Adder
11.607
965051AG1-369 GEN
Solar/Wind Harmer
4.783
274814UNIV PK N;0U
Adder
6.852
274807UNIV PK N;3U
Adder
6.837
274805UNIV PK N;1U
Adder
6.807
274811UNIV PK N;7U
Adder
6.792
972037AH1-567 GEN1
Adder
0.247
274827FISK ;RP
Adder
10.465
960591AF2-350 GEN
Solar/Wind Harmer
9.401
972227AH1-698 GEN1
Adder
3.512
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
1.189
963791AG1-232 GEN
Solar/Wind Harmer
12.652
274687WILL CNTY;4U
Adder
37.406
274687WILL CNTY;4U
Adder
37.406
274675JOLIET 29;7U
Adder
41.022
274675JOLIET 29;7U
Adder
39.557
270536AF1-215 GEN2
Solar/Wind Harmer
0.012
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
965651AG1-433 GEN
Solar/Wind Harmer
2.721
274745AC1-111 GEN9
Adder
7.401
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
11.896
276691AA1-018 GEN1
Solar/Wind Harmer
1.108
274682WAUKEGAN ;7U
Adder
23.511
274828WAUKEGAN ;BP
Adder
14.433
958861AF2-177 GEN
Solar/Wind Harmer
3.948
962781AG1-127 GEN
Solar/Wind Harmer
8.621
939401AE1-172 GEN
Solar/Wind Harmer
6.775
274872LEEDK;1U
Solar/Wind Harmer
0.006
276901AD2-066 C O1
Solar/Wind Harmer
0.009
971997AH1-543 GEN
Solar/Wind Harmer
4.718
276861AD2-134 GEN
Solar/Wind Harmer
0.161
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
11.195
957471AF2-041 GEN
Solar/Wind Harmer
26.723
959081AF2-199 GEN
Solar/Wind Harmer
8.908
971067AG2-660 GEN
Solar/Wind Harmer
2.969
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
274822ROCKFORD ;11
Adder
24.978
972235AH1-702 GEN1
Adder
3.201
970819AG2-516 GEN
Solar/Wind Harmer
10.6
970569AG2-363 GEN
Solar/Wind Harmer
26.435
971475AH1-234 GEN
Solar/Wind Harmer
4.275
945371AF1-202 GEN
Solar/Wind Harmer
0.001
274857EASY ROAD;U1
Solar/Wind Harmer
0.002
274761LEE CO EC;2U
Adder
11.654
274766LEE CO EC;7U
Adder
11.517
276158O29GEN2
Solar/Wind Harmer
0.001
24791305MDL-5G
Solar/Wind Harmer
0.001
274877BISHOP HL;1U
Solar/Wind Harmer
0.289
276726Z2-087_GEN
Solar/Wind Harmer
0.003
939741AE1-205 GEN
Solar/Wind Harmer
11.942
274854TWINGROVE;U2
Solar/Wind Harmer
0.004
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
970291AG2-192 GEN
Solar/Wind Harmer
1.078
270032AE2-172
Solar/Wind Harmer
5.467
972175AH1-670 GEN
Solar/Wind Harmer
6.757
270005AE1-210 C O1
Solar/Wind Harmer
1.747
965031AG1-367 GEN
Solar/Wind Harmer
8.064
276903AD2-071 C
Solar/Wind Harmer
8.911
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963741AG1-226 GEN
Solar/Wind Harmer
18.836
970825AG2-519 GEN
Solar/Wind Harmer
2.823
963831AG1-236 GEN
Solar/Wind Harmer
3.095
276615X2-022 GEN
Solar/Wind Harmer
0.082
965911AG1-460 GEN
Solar/Wind Harmer
1.521
247536S-71 GEN
Solar/Wind Harmer
0.305
24728605AND G2
Adder
3.824
24722005FLATG5
50/50
4.694
24721905FLATG4
50/50
86.059
270475AD2-096_GEN
50/50
10.488
270142AC1-141 CT1_
50/50
3.444
24641605TWIN BRNCH
50/50
0.025
24344005CKG1
50/50
9.376
24642205MAYFLWER
50/50
0.961
944961AF1-161 GEN
50/50
4.122
962601AG1-109 GEN
50/50
4.122
970153AG2-106 GEN
Solar/Wind Harmer
69.955
270043AE2-236 GEN
Solar/Wind Harmer
6.761
970349AG2-230 GEN
Solar/Wind Harmer
15.658
959331AF2-224 GEN
Solar/Wind Harmer
7.221
965021AG1-366 GEN
Solar/Wind Harmer
3.439
270391AF1-285 GEN3
Solar/Wind Harmer
0.683
970513AG2-328 GEN
Solar/Wind Harmer
4.403
970517AG2-330 GEN
Solar/Wind Harmer
26.415
970031AG2-029 GEN
Solar/Wind Harmer
6.551
247643Z2-116 C
Solar/Wind Harmer
0
944531AF1-118 GEN
Solar/Wind Harmer
44.632
945111AF1-176 GEN
Solar/Wind Harmer
8.066
270485AE1-090_GEN
Solar/Wind Harmer
0.001
24441205WTRV SLR C
Solar/Wind Harmer
0
247604X1-042
Adder
0.578
274772LINCOLN ;3U
Adder
11.607
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.062
274724RIVER EC ;11
Adder
24.177
274752CRETE EC ;2U
Adder
11.24
274753CRETE EC ;3U
Adder
11.24
970707AG2-453 GEN
Solar/Wind Harmer
30.794
274802UNIV PARK;5U
Adder
7.866
274826FISK ;BP
Adder
14.766
276806AD2-047 C O1
Solar/Wind Harmer
5.327
970941AG2-585 GEN
Solar/Wind Harmer
11.751
274800UNIV PARK;3U
Adder
7.856
972038AH1-567 GEN2
Adder
0.492
972228AH1-698 GEN2
Adder
4.987
270491AE1-102 GEN2
Solar/Wind Harmer
1.22
276897AD1-100 C
Solar/Wind Harmer
0.012
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
274676JOLIET 29;8U
Adder
39.557
270535AF1-215 GEN1
Solar/Wind Harmer
0.012
274729ELWOOD EC;1P
Adder
21.93
274730ELWOOD EC;6P
Adder
21.93
274734ELWOOD EC;8P
Adder
21.93
274736ELWOOD EC;9P
Adder
21.93
276893AG1-478 C
Solar/Wind Harmer
0.369
943121AE2-341 GEN
Solar/Wind Harmer
15.511
943591AF1-030 GEN
Solar/Wind Harmer
10.315
964401AG1-302 GEN
Solar/Wind Harmer
0.001
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
23.511
276805AD2-038 GEN
Solar/Wind Harmer
0.003
274872LEEDK;1U
Solar/Wind Harmer
0.331
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
0.956
274855GSG-6 ;RU
Solar/Wind Harmer
0.329
274850MENDOTA H;RU
Solar/Wind Harmer
0.106
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.161
959091AF2-200 GEN
Solar/Wind Harmer
17.815
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
2.783
270258AD1-119 GEN
Solar/Wind Harmer
0.002
970571AG2-364 GEN
Solar/Wind Harmer
17.623
270404AC1-167 GEN
Solar/Wind Harmer
0.004
274858EASY ROAD;U2
Solar/Wind Harmer
0.002
274760LEE CO EC;1U
Adder
11.654
274767LEE CO EC;8U
Adder
11.517
276157O29GEN1
Solar/Wind Harmer
1.397
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
8.621
274878BISHOP HL;2U
Solar/Wind Harmer
0.289
942111AE2-223 GEN
Solar/Wind Harmer
2.772
971617AH1-308 GEN
Solar/Wind Harmer
7.081
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
965091AG1-374 GEN
Solar/Wind Harmer
25.189
959611AF2-252 GEN
Solar/Wind Harmer
2.799
965931AG1-462 GEN
Solar/Wind Harmer
21.385
247642Z2-115 C
Solar/Wind Harmer
0.004
970289AG2-191 GEN
Solar/Wind Harmer
0.912
970291AG2-192 GEN
Solar/Wind Harmer
0.829
958821AF2-173 GEN
Solar/Wind Harmer
11.29
270004AE1-209 GEN
Solar/Wind Harmer
1.747
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
3.686
276668AB2-070 GEN1
Solar/Wind Harmer
0.291
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
11.901
946031AF1-268 GEN
Solar/Wind Harmer
7.527
276621W2-048 GEN
Solar/Wind Harmer
0.396
276838X2-022 GEN2
Solar/Wind Harmer
0.442
942481AE2-261 GEN
Solar/Wind Harmer
22.745
24728705AND G3
Adder
7.997
24728505AND G1
Adder
3.824
274731ELWOOD EC;2P
Adder
21.93
274733ELWOOD EC;3P
Adder
21.93
274735ELWOOD EC;4P
Adder
21.93
274728ELWOOD EC;5P
Adder
21.93
970833AG2-524 GEN
Solar/Wind Harmer
10.224
970833AG2-524 GEN
Solar/Wind Harmer
6.816
971549AH1-272 GEN
Solar/Wind Harmer
19.16
274746AC1-111 G10
Adder
7.401
274744AC1-111 GEN8
Adder
7.401
965101AG1-375 GEN
Solar/Wind Harmer
9.112
958391AF2-133 GEN
Solar/Wind Harmer
0.001
276868AE1-113 GEN
Solar/Wind Harmer
1.807
276882AE2-255 GEN
Solar/Wind Harmer
1.053
971177AH1-047 GEN
Solar/Wind Harmer
5.547
247607V1-011 GEN
Solar/Wind Harmer
0.001
971411AH1-196 GEN
Solar/Wind Harmer
13.442
971675AH1-338 GEN
Solar/Wind Harmer
3.495
971611AH1-305 GEN
Solar/Wind Harmer
5.332
274863CRW1-WTG
Solar/Wind Harmer
0.003
274864CRW2-WTG
Solar/Wind Harmer
0.003
971171AH1-044 GEN
Solar/Wind Harmer
17.815
274823ROCKFORD ;21
Adder
24.797
276612AE2-035 GEN
Solar/Wind Harmer
0.002
926823AC1-168 GEN
Solar/Wind Harmer
1.498
970169AG2-114 GEN
Solar/Wind Harmer
8.81
945581AF1-223 GEN
Solar/Wind Harmer
0.001
971681AH1-341 GEN
Solar/Wind Harmer
14.125
961011AF2-392 GEN
Solar/Wind Harmer
5.094
957751AF2-069 GEN
Solar/Wind Harmer
0.285
24690905MDL-1G C
Solar/Wind Harmer
0.003
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0.002
276655WTG1_EQ
Solar/Wind Harmer
0.003
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
8.957
941731AE2-173 GEN
Solar/Wind Harmer
7.108
270024AE2-089 GEN
Solar/Wind Harmer
0.009
946321AF1-296 GEN
Solar/Wind Harmer
4.721
971609AH1-304 GEN
Solar/Wind Harmer
1.376
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
970289AG2-191 GEN
Solar/Wind Harmer
1.575
270594AE1-207 GEN
Solar/Wind Harmer
9.184
963841AG1-237 GEN
Solar/Wind Harmer
3.53
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
970115AG2-085 GEN
Solar/Wind Harmer
3.191
276849AB2-070 GEN2
Solar/Wind Harmer
0.291
276848AB2-070 GEN3
Solar/Wind Harmer
0.29
270297AD1-101 GEN
Solar/Wind Harmer
0.002
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
958491AF2-143 GEN
Solar/Wind Harmer
13.566
274879MINONK ;1U
Solar/Wind Harmer
0.38
942991AE2-321 GEN
Solar/Wind Harmer
10.048
270007AE1-245 C
Solar/Wind Harmer
0.002
971333AH1-146 GEN
Solar/Wind Harmer
17.91
971335AH1-147 GEN
Solar/Wind Harmer
17.91
971341AH1-150 GEN
Solar/Wind Harmer
17.815
971343AH1-151 GEN
Solar/Wind Harmer
17.815
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
970623AG2-406 GEN
Solar/Wind Harmer
1.621
274856ECOGROVE ;U1
Solar/Wind Harmer
0.208
276611AD2-172 GEN
Solar/Wind Harmer
0.002
938861AE1-114 GEN
Solar/Wind Harmer
4.97
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
274764LEE CO EC;5U
Adder
11.682
274765LEE CO EC;6U
Adder
11.682
274762LEE CO EC;3U
Adder
11.654
274763LEE CO EC;4U
Adder
11.544
276603SUBLETTE C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
5.169
276741O09 GEN1
Solar/Wind Harmer
0.308
276708O09 GEN2
Solar/Wind Harmer
0.308
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.339
276646AC1-214 GEN2
Solar/Wind Harmer
0.339
276782AC1-033 GEN
Solar/Wind Harmer
0.001
270599AE1-208 GEN
Solar/Wind Harmer
7.723
270031AE2-169
Solar/Wind Harmer
4.634
960611AF2-352 GEN
Solar/Wind Harmer
2.799
966841AG1-555 GEN
Solar/Wind Harmer
0.944
971613AH1-306 GEN
Solar/Wind Harmer
3.936
960441AF2-335 GEN
Solar/Wind Harmer
7.977
970241AG2-163 GEN
Solar/Wind Harmer
4.643
970825AG2-519 GEN
Solar/Wind Harmer
8.815
970621AG2-405 GEN
Solar/Wind Harmer
1.453
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
270201AC2-176 GEN
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
0.595
247621Y3-024
Adder
0.268
276916AD2-100_GEN
Solar/Wind Harmer
12.804
276911AD2-131_GEN
Solar/Wind Harmer
0.843
944201AF1-088_MTX
Adder
80.786
NYPJM->LTFIMP_NY
CLTF
3.072
LGEELTFEXP_LGEE->PJM
CLTF
4.553
WECLTFEXP_WEC->PJM
CLTF
4.843
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.157
AG2-052LTFEXP_AG2-052->PJM
LTF
0.305
AH1-155LTFEXP_AH1-155->PJM
LTF
0.457
LAGNLTFEXP_LAGN->PJM
CLTF
11.481
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.982
TVALTFEXP_TVA->PJM
CLTF
4.813
CBM West 1LTFEXP_CBM-W1->PJM
CBM
159.327
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.302
MECLTFEXP_MEC->PJM
CLTF
18.121
SIGELTFEXP_SIGE->PJM
CLTF
0.416
CBM West 2LTFEXP_CBM-W2->PJM
CBM
98.823

Details for 05MALIS-05VASSEL 765.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:AEP
Facility Description:
05MALIS-05VASSEL 765.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.2 %
Rating:4142.0 MVA
Rating Type:A
MVA to Mitigate:4150.44
MW Contribution:3.03
Bus #Bus NameTypeMW Contribution
270142AC1-141 CT1_
50/50
2.576
24641605TWIN BRNCH
50/50
0.019
270475AD2-096_GEN
50/50
6.265
24344005CKG1
50/50
7.016
24642205MAYFLWER
50/50
0.721
970153AG2-106 GEN
Solar/Wind Harmer
43.566
970349AG2-230 GEN
Solar/Wind Harmer
11.817
970513AG2-328 GEN
Solar/Wind Harmer
3.385
970517AG2-330 GEN
Solar/Wind Harmer
20.307
270043AE2-236 GEN
Solar/Wind Harmer
5
247643Z2-116 C
Solar/Wind Harmer
0
944531AF1-118 GEN
Solar/Wind Harmer
33.376
970031AG2-029 GEN
Solar/Wind Harmer
4.834
959331AF2-224 GEN
Solar/Wind Harmer
5.202
965021AG1-366 GEN
Solar/Wind Harmer
2.477
945111AF1-176 GEN
Solar/Wind Harmer
6.021
274772LINCOLN ;3U
Adder
8.941
274724RIVER EC ;11
Adder
18.592
274752CRETE EC ;2U
Adder
8.637
274753CRETE EC ;3U
Adder
8.637
970707AG2-453 GEN
Solar/Wind Harmer
23.798
274826FISK ;BP
Adder
11.395
274802UNIV PARK;5U
Adder
6.068
276806AD2-047 C O1
Solar/Wind Harmer
4.113
970941AG2-585 GEN
Solar/Wind Harmer
9.072
274800UNIV PARK;3U
Adder
6.064
972038AH1-567 GEN2
Adder
0.38
972228AH1-698 GEN2
Adder
3.852
24441205WTRV SLR C
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
0.01
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
274676JOLIET 29;8U
Adder
30.6
274729ELWOOD EC;1P
Adder
16.971
274730ELWOOD EC;6P
Adder
16.972
274734ELWOOD EC;8P
Adder
16.972
274736ELWOOD EC;9P
Adder
16.972
276893AG1-478 C
Solar/Wind Harmer
0.285
247604X1-042
Adder
0.429
270535AF1-215 GEN1
Solar/Wind Harmer
0.009
943121AE2-341 GEN
Solar/Wind Harmer
12.031
943591AF1-030 GEN
Solar/Wind Harmer
8
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
18.28
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274872LEEDK;1U
Solar/Wind Harmer
0.258
276805AD2-038 GEN
Solar/Wind Harmer
0.002
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.747
274855GSG-6 ;RU
Solar/Wind Harmer
0.257
274850MENDOTA H;RU
Solar/Wind Harmer
0.082
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.125
959091AF2-200 GEN
Solar/Wind Harmer
13.927
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
2.178
970571AG2-364 GEN
Solar/Wind Harmer
13.8
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
9.148
274767LEE CO EC;8U
Adder
9.041
276157O29GEN1
Solar/Wind Harmer
1.1
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.767
274878BISHOP HL;2U
Solar/Wind Harmer
0.227
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.043
942111AE2-223 GEN
Solar/Wind Harmer
2.185
965931AG1-462 GEN
Solar/Wind Harmer
16.944
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
965091AG1-374 GEN
Solar/Wind Harmer
19.925
959611AF2-252 GEN
Solar/Wind Harmer
2.214
247642Z2-115 C
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
0.704
970291AG2-192 GEN
Solar/Wind Harmer
0.64
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
2.949
270491AE1-102 GEN2
Solar/Wind Harmer
0.83
276668AB2-070 GEN1
Solar/Wind Harmer
0.233
276621W2-048 GEN
Solar/Wind Harmer
0.318
276838X2-022 GEN2
Solar/Wind Harmer
0.355
971617AH1-308 GEN
Solar/Wind Harmer
5.233
24721905FLATG4
Adder
18.123
270391AF1-285 GEN3
Solar/Wind Harmer
0.412
958821AF2-173 GEN
Solar/Wind Harmer
8.644
971599AH1-298 GEN
50/50
10.4
270144AC1-141 ST1_
50/50
2.281
24653605MOTTVILLE
50/50
0.004
24643105BUCHANAN
50/50
0.014
962771AG1-126 GEN
Solar/Wind Harmer
68.224
971347AH1-153 GEN
Solar/Wind Harmer
11.817
270071AF1-092 GEN
Solar/Wind Harmer
14.657
971771AH1-392 GEN
Solar/Wind Harmer
7.525
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971769AH1-391 GEN
Solar/Wind Harmer
8.356
971619AH1-309 GEN
Solar/Wind Harmer
3.352
274775LINCOLN ;6U
Adder
8.941
274776LINCOLN ;7U
Adder
8.941
274777LINCOLN ;8U
Adder
8.941
24729505KEY G4
Adder
6.812
274814UNIV PK N;0U
Adder
5.276
274807UNIV PK N;3U
Adder
5.265
274805UNIV PK N;1U
Adder
5.242
274811UNIV PK N;7U
Adder
5.23
274827FISK ;RP
Adder
8.075
972037AH1-567 GEN1
Adder
0.19
960591AF2-350 GEN
Solar/Wind Harmer
7.258
972227AH1-698 GEN1
Adder
2.712
274687WILL CNTY;4U
Adder
28.924
274687WILL CNTY;4U
Adder
28.924
274675JOLIET 29;7U
Adder
31.734
274675JOLIET 29;7U
Adder
30.6
274731ELWOOD EC;2P
Adder
16.971
274733ELWOOD EC;3P
Adder
16.971
274735ELWOOD EC;4P
Adder
16.971
274728ELWOOD EC;5P
Adder
16.972
970833AG2-524 GEN
Solar/Wind Harmer
7.918
970833AG2-524 GEN
Solar/Wind Harmer
5.279
270536AF1-215 GEN2
Solar/Wind Harmer
0.009
274746AC1-111 G10
Adder
5.741
274744AC1-111 GEN8
Adder
5.741
958391AF2-133 GEN
Solar/Wind Harmer
0.001
276868AE1-113 GEN
Solar/Wind Harmer
1.408
276882AE2-255 GEN
Solar/Wind Harmer
0.821
971177AH1-047 GEN
Solar/Wind Harmer
4.327
270284AF1-227 GEN1
Solar/Wind Harmer
0.009
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
971675AH1-338 GEN
Solar/Wind Harmer
2.729
971411AH1-196 GEN
Solar/Wind Harmer
10.494
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
971611AH1-305 GEN
Solar/Wind Harmer
4.147
971171AH1-044 GEN
Solar/Wind Harmer
13.927
274823ROCKFORD ;21
Adder
19.398
276612AE2-035 GEN
Solar/Wind Harmer
0.002
965041AG1-368 GEN
Solar/Wind Harmer
6.907
926823AC1-168 GEN
Solar/Wind Harmer
1.173
970169AG2-114 GEN
Solar/Wind Harmer
6.898
971681AH1-341 GEN
Solar/Wind Harmer
11.079
965101AG1-375 GEN
Solar/Wind Harmer
6.878
963791AG1-232 GEN
Solar/Wind Harmer
9.223
961011AF2-392 GEN
Solar/Wind Harmer
4.004
957751AF2-069 GEN
Solar/Wind Harmer
0.224
971549AH1-272 GEN
Solar/Wind Harmer
14.025
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
965051AG1-369 GEN
Solar/Wind Harmer
3.359
276655WTG1_EQ
Solar/Wind Harmer
0.003
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.06
941731AE2-173 GEN
Solar/Wind Harmer
5.603
946321AF1-296 GEN
Solar/Wind Harmer
3.736
945581AF1-223 GEN
Solar/Wind Harmer
0.001
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
963841AG1-237 GEN
Solar/Wind Harmer
2.803
970289AG2-191 GEN
Solar/Wind Harmer
1.217
971609AH1-304 GEN
Solar/Wind Harmer
1.046
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.808
276849AB2-070 GEN2
Solar/Wind Harmer
0.233
276848AB2-070 GEN3
Solar/Wind Harmer
0.232
270594AE1-207 GEN
Solar/Wind Harmer
7.078
270024AE2-089 GEN
Solar/Wind Harmer
0.007
270578AF1-285 GEN2
Solar/Wind Harmer
0.412
247607V1-011 GEN
Solar/Wind Harmer
0.001
970115AG2-085 GEN
Solar/Wind Harmer
2.44
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
270102X2-052 ST
50/50
1.727
270100X2-052 CT1
50/50
1.592
270101X2-052 CT2
50/50
1.592
247620Y3-023
50/50
0.521
970615AG2-402 GEN
50/50
2.477
970321AG2-212 GEN
Solar/Wind Harmer
3.385
270216AD2-079_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.006
965681AG1-436 GEN
Solar/Wind Harmer
9.376
965791AG1-447 GEN
Solar/Wind Harmer
6.876
270526AF1-158 GEN
Solar/Wind Harmer
0.009
24441505OLIV SLR
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
0.001
970611AG2-400 GEN
Solar/Wind Harmer
7.432
970627AG2-408 GEN
Solar/Wind Harmer
2.23
961051AF2-396 GEN
Solar/Wind Harmer
14.796
961051AF2-396 GEN
Solar/Wind Harmer
9.864
274770LINCOLN ;1U
Adder
8.941
274771LINCOLN ;2U
Adder
8.941
274808UNIV PK N;4U
Adder
5.207
972259AH1-714 GEN
Adder
19.859
274803UNIV PARK;6U
Adder
6.068
274888KELLY CRK;1U
Solar/Wind Harmer
0.426
274887GEN-1.85
Solar/Wind Harmer
0.191
276843GEN-1.7
Solar/Wind Harmer
0.235
958011AF2-095 GEN
Solar/Wind Harmer
10.451
274674JOLIET 9 ;6U
Adder
15.907
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
971573AH1-285 GEN
Solar/Wind Harmer
1.332
274695ROCKY RD ;2P
Adder
11.339
274693ROCKY RD ;1P
Adder
11.227
274697ROCKY RD ;3P
Adder
3.08
274696ROCKY RD ;4P
Adder
11.606
958481AF2-142 GEN
Solar/Wind Harmer
10.652
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.96
274683WAUKEGAN ;8U
Adder
21.414
274683WAUKEGAN ;8U
Adder
18.051
962691AG1-118 GEN
Solar/Wind Harmer
21.207
970921AG2-575 GEN
Solar/Wind Harmer
7.056
970921AG2-575 GEN
Solar/Wind Harmer
2.352
958491AF2-143 GEN
Solar/Wind Harmer
10.561
942991AE2-321 GEN
Solar/Wind Harmer
7.837
274879MINONK ;1U
Solar/Wind Harmer
0.296
971333AH1-146 GEN
Solar/Wind Harmer
13.985
971335AH1-147 GEN
Solar/Wind Harmer
13.985
944541AF1-119 GEN
Solar/Wind Harmer
0.468
960971AF2-388 GEN
Solar/Wind Harmer
4.1
971341AH1-150 GEN
Solar/Wind Harmer
13.927
971343AH1-151 GEN
Solar/Wind Harmer
13.927
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
274856ECOGROVE ;U1
Solar/Wind Harmer
0.163
276611AD2-172 GEN
Solar/Wind Harmer
0.002
938861AE1-114 GEN
Solar/Wind Harmer
3.898
274764LEE CO EC;5U
Adder
9.17
274765LEE CO EC;6U
Adder
9.17
274762LEE CO EC;3U
Adder
9.148
274763LEE CO EC;4U
Adder
9.062
276603SUBLETTE C
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
972267AH1-718 GEN
Adder
4.066
276741O09 GEN1
Solar/Wind Harmer
0.242
276708O09 GEN2
Solar/Wind Harmer
0.242
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.267
276646AC1-214 GEN2
Solar/Wind Harmer
0.267
276782AC1-033 GEN
Solar/Wind Harmer
0.001
942221AE2-234 GEN
Solar/Wind Harmer
0.034
960611AF2-352 GEN
Solar/Wind Harmer
2.214
966841AG1-555 GEN
Solar/Wind Harmer
0.746
270599AE1-208 GEN
Solar/Wind Harmer
5.869
270031AE2-169
Solar/Wind Harmer
3.522
246938BC-WTG3
Solar/Wind Harmer
0.231
246937BC-WTG2
Solar/Wind Harmer
0.259
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
970241AG2-163 GEN
Solar/Wind Harmer
3.704
971613AH1-306 GEN
Solar/Wind Harmer
3.033
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
270007AE1-245 C
Solar/Wind Harmer
0.002
276916AD2-100_GEN
Solar/Wind Harmer
12.852
276911AD2-131_GEN
Solar/Wind Harmer
0.847
24344105CKG2
50/50
8.761
270143AC1-141 CT2_
50/50
2.576
24639705ELKHART HY
50/50
0.174
970521AG2-332 GEN
50/50
12.426
962761AG1-125 GEN
Solar/Wind Harmer
68.224
970149AG2-104 GEN
Solar/Wind Harmer
73.684
970155AG2-107 GEN
Solar/Wind Harmer
43.566
970245AG2-165 GEN
Solar/Wind Harmer
3.385
270349AD2-093_GEN
Solar/Wind Harmer
0.006
270063AE2-323 C
Solar/Wind Harmer
0.006
270505AE1-170 C O1
Solar/Wind Harmer
7.821
965011AG1-365 GEN
Solar/Wind Harmer
7.432
945111AF1-176 GEN
Solar/Wind Harmer
13.254
274773LINCOLN ;4U
Adder
8.941
274774LINCOLN ;5U
Adder
8.941
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
3.852
274723RIVER EC ;12
Adder
18.809
274751CRETE EC ;1U
Adder
8.637
274754CRETE EC ;4U
Adder
8.637
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
5.23
970373AG2-245 GEN
Solar/Wind Harmer
15.278
276776AD2-060 GEN
Solar/Wind Harmer
0.758
274801UNIV PARK;4U
Adder
6.064
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
31.733
274674JOLIET 9 ;6U
Adder
15.907
274732ELWOOD EC;7P
Adder
16.972
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0.006
274745AC1-111 GEN9
Adder
5.741
276691AA1-018 GEN1
Solar/Wind Harmer
0.86
274682WAUKEGAN ;7U
Adder
18.28
274828WAUKEGAN ;BP
Adder
11.225
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.202
962781AG1-127 GEN
Solar/Wind Harmer
6.715
939401AE1-172 GEN
Solar/Wind Harmer
5.274
274872LEEDK;1U
Solar/Wind Harmer
0.004
276901AD2-066 C O1
Solar/Wind Harmer
0.007
971997AH1-543 GEN
Solar/Wind Harmer
3.679
276861AD2-134 GEN
Solar/Wind Harmer
0.125
965651AG1-433 GEN
Solar/Wind Harmer
2.05
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.708
957471AF2-041 GEN
Solar/Wind Harmer
20.89
959081AF2-199 GEN
Solar/Wind Harmer
6.963
971067AG2-660 GEN
Solar/Wind Harmer
2.321
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
274822ROCKFORD ;11
Adder
19.54
972235AH1-702 GEN1
Adder
2.505
970819AG2-516 GEN
Solar/Wind Harmer
8.301
971475AH1-234 GEN
Solar/Wind Harmer
3.35
970569AG2-363 GEN
Solar/Wind Harmer
20.699
958861AF2-177 GEN
Solar/Wind Harmer
2.981
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
9.148
274766LEE CO EC;7U
Adder
9.041
276158O29GEN2
Solar/Wind Harmer
0.001
24791305MDL-5G
Solar/Wind Harmer
0.001
274877BISHOP HL;1U
Solar/Wind Harmer
0.227
247521TR3_G114
Solar/Wind Harmer
0.245
270246TR4_N_V150
Solar/Wind Harmer
0.043
276726Z2-087_GEN
Solar/Wind Harmer
0.002
939741AE1-205 GEN
Solar/Wind Harmer
9.414
945371AF1-202 GEN
Solar/Wind Harmer
0.001
944231AF1-091 GEN
Solar/Wind Harmer
1.771
274854TWINGROVE;U2
Solar/Wind Harmer
0.003
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.002
24695305TIMB G C
Solar/Wind Harmer
0.002
972175AH1-670 GEN
Solar/Wind Harmer
5.377
965421AG1-410 GEN
Solar/Wind Harmer
19.447
970291AG2-192 GEN
Solar/Wind Harmer
0.832
274880W4-005 GEN4
Solar/Wind Harmer
0.001
246936BC-WTG1
Solar/Wind Harmer
0.259
270489AE1-102 GEN1
Solar/Wind Harmer
0.83
963831AG1-236 GEN
Solar/Wind Harmer
2.479
963741AG1-226 GEN
Solar/Wind Harmer
15.028
270032AE2-172
Solar/Wind Harmer
4.213
276615X2-022 GEN
Solar/Wind Harmer
0.066
24721705FLATG2
Adder
18.123
270223U2-072_GEN1
Solar/Wind Harmer
0.001
276903AD2-071 C
Solar/Wind Harmer
6.907
270005AE1-210 C O1
Solar/Wind Harmer
1.338
965031AG1-367 GEN
Solar/Wind Harmer
6.174
965911AG1-460 GEN
Solar/Wind Harmer
1.231
970825AG2-519 GEN
Solar/Wind Harmer
2.158
960441AF2-335 GEN
Solar/Wind Harmer
6.101
970623AG2-406 GEN
Solar/Wind Harmer
1.115
970825AG2-519 GEN
Solar/Wind Harmer
6.738
270004AE1-209 GEN
Solar/Wind Harmer
1.338
942481AE2-261 GEN
Solar/Wind Harmer
18.406
270258AD1-119 GEN
Solar/Wind Harmer
0.002
270404AC1-167 GEN
Solar/Wind Harmer
0.003
946031AF1-268 GEN
Solar/Wind Harmer
5.724
NYPJM->LTFIMP_NY
CLTF
2.707
LGEELTFEXP_LGEE->PJM
CLTF
4.102
WECLTFEXP_WEC->PJM
CLTF
3.793
AG2-052LTFEXP_AG2-052->PJM
LTF
0.236
AH1-155LTFEXP_AH1-155->PJM
LTF
0.353
LAGNLTFEXP_LAGN->PJM
CLTF
11.568
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.749
TVALTFEXP_TVA->PJM
CLTF
5.27
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.695
CBM South 1LTFEXP_CBM-S1->PJM
CBM
20.264
MECLTFEXP_MEC->PJM
CLTF
14.753
SIGELTFEXP_SIGE->PJM
CLTF
0.361
CPLELTFEXP_CPLE->PJM
CLTF
1.403
CBM West 2LTFEXP_CBM-W2->PJM
CBM
89.76

Details for 05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line l/o AP_P1-3_MP-765-501T_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Contingency Name:
AP_P1-3_MP-765-501T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:130.64 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5971.43
MW Contribution:3.67
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
1.795
971599AH1-298 GEN
50/50
12.157
962771AG1-126 GEN
Solar/Wind Harmer
80.781
971347AH1-153 GEN
Solar/Wind Harmer
14.036
270071AF1-092 GEN
Solar/Wind Harmer
17.319
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971771AH1-392 GEN
Solar/Wind Harmer
8.916
274775LINCOLN ;6U
Adder
10.782
274776LINCOLN ;7U
Adder
10.782
274777LINCOLN ;8U
Adder
10.782
971769AH1-391 GEN
Solar/Wind Harmer
9.94
971619AH1-309 GEN
Solar/Wind Harmer
3.958
274814UNIV PK N;0U
Adder
6.363
274807UNIV PK N;3U
Adder
6.35
274805UNIV PK N;1U
Adder
6.322
274811UNIV PK N;7U
Adder
6.308
274827FISK ;RP
Adder
9.754
972037AH1-567 GEN1
Adder
0.23
960591AF2-350 GEN
Solar/Wind Harmer
8.77
972227AH1-698 GEN1
Adder
3.278
274687WILL CNTY;4U
Adder
34.988
270102X2-052 ST
50/50
2.06
270100X2-052 CT1
50/50
1.898
270101X2-052 CT2
50/50
1.898
970321AG2-212 GEN
Solar/Wind Harmer
4.074
965681AG1-436 GEN
Solar/Wind Harmer
11.195
965791AG1-447 GEN
Solar/Wind Harmer
8.21
274770LINCOLN ;1U
Adder
10.782
274771LINCOLN ;2U
Adder
10.782
270526AF1-158 GEN
Solar/Wind Harmer
0.011
24441505OLIV SLR
Solar/Wind Harmer
0
270216AD2-079_GEN
Solar/Wind Harmer
0.001
957891AF2-083 GEN
Solar/Wind Harmer
0.001
274808UNIV PK N;4U
Adder
6.281
972259AH1-714 GEN
Adder
24.011
274803UNIV PARK;6U
Adder
7.329
274888KELLY CRK;1U
Solar/Wind Harmer
0.515
24722005FLATG5
50/50
1.795
24721905FLATG4
50/50
32.905
970153AG2-106 GEN
Solar/Wind Harmer
51.584
970513AG2-328 GEN
Solar/Wind Harmer
4.074
970517AG2-330 GEN
Solar/Wind Harmer
24.444
970349AG2-230 GEN
Solar/Wind Harmer
14.036
270043AE2-236 GEN
Solar/Wind Harmer
5.854
274772LINCOLN ;3U
Adder
10.782
247643Z2-116 C
Solar/Wind Harmer
0
24642205MAYFLWER
Adder
0.804
274724RIVER EC ;11
Adder
22.4
970707AG2-453 GEN
Solar/Wind Harmer
28.77
274752CRETE EC ;2U
Adder
10.401
274753CRETE EC ;3U
Adder
10.401
944531AF1-118 GEN
Solar/Wind Harmer
39.427
274826FISK ;BP
Adder
13.763
274802UNIV PARK;5U
Adder
7.329
276806AD2-047 C O1
Solar/Wind Harmer
4.97
970941AG2-585 GEN
Solar/Wind Harmer
10.962
972228AH1-698 GEN2
Adder
4.656
274800UNIV PARK;3U
Adder
7.326
972038AH1-567 GEN2
Adder
0.459
945111AF1-176 GEN
Solar/Wind Harmer
7.104
276897AD1-100 C
Solar/Wind Harmer
0.012
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
274676JOLIET 29;8U
Adder
37.026
274729ELWOOD EC;1P
Adder
20.542
274730ELWOOD EC;6P
Adder
20.542
274734ELWOOD EC;8P
Adder
20.542
274736ELWOOD EC;9P
Adder
20.542
276893AG1-478 C
Solar/Wind Harmer
0.345
970031AG2-029 GEN
Solar/Wind Harmer
5.657
943121AE2-341 GEN
Solar/Wind Harmer
14.583
943591AF1-030 GEN
Solar/Wind Harmer
9.698
270535AF1-215 GEN1
Solar/Wind Harmer
0.011
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
22.199
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274872LEEDK;1U
Solar/Wind Harmer
0.314
276805AD2-038 GEN
Solar/Wind Harmer
0.003
959331AF2-224 GEN
Solar/Wind Harmer
5.981
965021AG1-366 GEN
Solar/Wind Harmer
2.848
24441205WTRV SLR C
Solar/Wind Harmer
0
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
0.909
274855GSG-6 ;RU
Solar/Wind Harmer
0.313
274850MENDOTA H;RU
Solar/Wind Harmer
0.1
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.153
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
959091AF2-200 GEN
Solar/Wind Harmer
16.979
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
2.658
247604X1-042
Adder
0.505
970571AG2-364 GEN
Solar/Wind Harmer
16.847
274858EASY ROAD;U2
Solar/Wind Harmer
0.002
274760LEE CO EC;1U
Adder
11.187
274767LEE CO EC;8U
Adder
11.055
276157O29GEN1
Solar/Wind Harmer
1.347
274878BISHOP HL;2U
Solar/Wind Harmer
0.279
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
8.289
942111AE2-223 GEN
Solar/Wind Harmer
2.682
965931AG1-462 GEN
Solar/Wind Harmer
20.855
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
965091AG1-374 GEN
Solar/Wind Harmer
24.514
959611AF2-252 GEN
Solar/Wind Harmer
2.724
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
3.657
276668AB2-070 GEN1
Solar/Wind Harmer
0.289
247642Z2-115 C
Solar/Wind Harmer
0.003
276621W2-048 GEN
Solar/Wind Harmer
0.395
276838X2-022 GEN2
Solar/Wind Harmer
0.442
970289AG2-191 GEN
Solar/Wind Harmer
0.855
970291AG2-192 GEN
Solar/Wind Harmer
0.777
942481AE2-261 GEN
Solar/Wind Harmer
23.013
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.049
970193AG2-126 GEN
Solar/Wind Harmer
11.195
958821AF2-173 GEN
Solar/Wind Harmer
10.43
270004AE1-209 GEN
Solar/Wind Harmer
1.614
971617AH1-308 GEN
Solar/Wind Harmer
6.153
970243AG2-164 GEN
Solar/Wind Harmer
3.851
970519AG2-331 GEN
Solar/Wind Harmer
17.115
970699AG2-449 GEN
Solar/Wind Harmer
1.646
274887GEN-1.85
Solar/Wind Harmer
0.231
276843GEN-1.7
Solar/Wind Harmer
0.284
958011AF2-095 GEN
Solar/Wind Harmer
12.628
247620Y3-023
Adder
0.578
961051AF2-396 GEN
Solar/Wind Harmer
17.455
961051AF2-396 GEN
Solar/Wind Harmer
11.637
274674JOLIET 9 ;6U
Adder
19.252
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
971573AH1-285 GEN
Solar/Wind Harmer
1.615
274696ROCKY RD ;4P
Adder
14.093
274695ROCKY RD ;2P
Adder
13.768
274693ROCKY RD ;1P
Adder
13.632
274697ROCKY RD ;3P
Adder
3.74
958481AF2-142 GEN
Solar/Wind Harmer
12.927
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
1.166
274683WAUKEGAN ;8U
Adder
26.009
274683WAUKEGAN ;8U
Adder
21.925
962691AG1-118 GEN
Solar/Wind Harmer
25.779
970921AG2-575 GEN
Solar/Wind Harmer
8.581
970921AG2-575 GEN
Solar/Wind Harmer
2.86
958491AF2-143 GEN
Solar/Wind Harmer
12.84
970611AG2-400 GEN
Solar/Wind Harmer
8.544
970627AG2-408 GEN
Solar/Wind Harmer
2.563
942991AE2-321 GEN
Solar/Wind Harmer
9.539
274879MINONK ;1U
Solar/Wind Harmer
0.36
971333AH1-146 GEN
Solar/Wind Harmer
17.035
971335AH1-147 GEN
Solar/Wind Harmer
17.035
971341AH1-150 GEN
Solar/Wind Harmer
16.979
971343AH1-151 GEN
Solar/Wind Harmer
16.979
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
274856ECOGROVE ;U1
Solar/Wind Harmer
0.199
276611AD2-172 GEN
Solar/Wind Harmer
0.002
938861AE1-114 GEN
Solar/Wind Harmer
4.764
274764LEE CO EC;5U
Adder
11.213
274765LEE CO EC;6U
Adder
11.213
274762LEE CO EC;3U
Adder
11.187
274763LEE CO EC;4U
Adder
11.081
276603SUBLETTE C
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
972267AH1-718 GEN
Adder
4.979
276741O09 GEN1
Solar/Wind Harmer
0.297
276708O09 GEN2
Solar/Wind Harmer
0.297
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.327
276646AC1-214 GEN2
Solar/Wind Harmer
0.327
944541AF1-119 GEN
Solar/Wind Harmer
0.557
960971AF2-388 GEN
Solar/Wind Harmer
4.876
276782AC1-033 GEN
Solar/Wind Harmer
0.001
960611AF2-352 GEN
Solar/Wind Harmer
2.724
966841AG1-555 GEN
Solar/Wind Harmer
0.919
942221AE2-234 GEN
Solar/Wind Harmer
0.04
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
970241AG2-163 GEN
Solar/Wind Harmer
4.592
270599AE1-208 GEN
Solar/Wind Harmer
7.039
270031AE2-169
Solar/Wind Harmer
4.223
276916AD2-100_GEN
Solar/Wind Harmer
16.09
276911AD2-131_GEN
Solar/Wind Harmer
1.06
971613AH1-306 GEN
Solar/Wind Harmer
3.675
945391AF1-204 GEN
Solar/Wind Harmer
7.93
960441AF2-335 GEN
Solar/Wind Harmer
7.358
970239AG2-162 GEN
Solar/Wind Harmer
1.646
24721805FLATG3
50/50
1.795
24721705FLATG2
50/50
32.905
24344105CKG2
50/50
10.4
962761AG1-125 GEN
Solar/Wind Harmer
80.781
970149AG2-104 GEN
Solar/Wind Harmer
87.246
970155AG2-107 GEN
Solar/Wind Harmer
51.584
970245AG2-165 GEN
Solar/Wind Harmer
4.074
274773LINCOLN ;4U
Adder
10.782
274774LINCOLN ;5U
Adder
10.782
274723RIVER EC ;12
Adder
22.661
24639705ELKHART HY
Adder
0.194
276164X3-005 C
Solar/Wind Harmer
0
274751CRETE EC ;1U
Adder
10.401
274754CRETE EC ;4U
Adder
10.401
270505AE1-170 C O1
Solar/Wind Harmer
9.235
274812UNIV PK N;8U
Adder
6.308
276776AD2-060 GEN
Solar/Wind Harmer
0.916
274801UNIV PARK;4U
Adder
7.326
945111AF1-176 GEN
Solar/Wind Harmer
15.639
270063AE2-323 C
Solar/Wind Harmer
0.007
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274687WILL CNTY;4U
Adder
34.988
274675JOLIET 29;7U
Adder
38.397
274675JOLIET 29;7U
Adder
37.026
274731ELWOOD EC;2P
Adder
20.542
274733ELWOOD EC;3P
Adder
20.542
274735ELWOOD EC;4P
Adder
20.542
274728ELWOOD EC;5P
Adder
20.542
970833AG2-524 GEN
Solar/Wind Harmer
9.589
970833AG2-524 GEN
Solar/Wind Harmer
6.393
274746AC1-111 G10
Adder
6.959
274744AC1-111 GEN8
Adder
6.959
24729505KEY G4
Adder
8.06
270536AF1-215 GEN2
Solar/Wind Harmer
0.011
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971177AH1-047 GEN
Solar/Wind Harmer
5.267
276868AE1-113 GEN
Solar/Wind Harmer
1.713
276882AE2-255 GEN
Solar/Wind Harmer
0.998
971675AH1-338 GEN
Solar/Wind Harmer
3.323
971411AH1-196 GEN
Solar/Wind Harmer
12.781
274863CRW1-WTG
Solar/Wind Harmer
0.003
274864CRW2-WTG
Solar/Wind Harmer
0.003
971171AH1-044 GEN
Solar/Wind Harmer
16.979
971611AH1-305 GEN
Solar/Wind Harmer
5.045
274823ROCKFORD ;21
Adder
23.66
276612AE2-035 GEN
Solar/Wind Harmer
0.002
926823AC1-168 GEN
Solar/Wind Harmer
1.432
970169AG2-114 GEN
Solar/Wind Harmer
8.423
971681AH1-341 GEN
Solar/Wind Harmer
13.539
961011AF2-392 GEN
Solar/Wind Harmer
4.902
957751AF2-069 GEN
Solar/Wind Harmer
0.275
24690905MDL-1G C
Solar/Wind Harmer
0.003
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0.002
276655WTG1_EQ
Solar/Wind Harmer
0.003
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
8.664
941731AE2-173 GEN
Solar/Wind Harmer
6.876
946321AF1-296 GEN
Solar/Wind Harmer
4.594
965101AG1-375 GEN
Solar/Wind Harmer
8.195
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
963841AG1-237 GEN
Solar/Wind Harmer
3.463
945581AF1-223 GEN
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
10.716
971549AH1-272 GEN
Solar/Wind Harmer
16.349
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.289
276848AB2-070 GEN3
Solar/Wind Harmer
0.287
965041AG1-368 GEN
Solar/Wind Harmer
7.862
970289AG2-191 GEN
Solar/Wind Harmer
1.476
971609AH1-304 GEN
Solar/Wind Harmer
1.254
270594AE1-207 GEN
Solar/Wind Harmer
8.574
965051AG1-369 GEN
Solar/Wind Harmer
3.795
944221AF1-090 GEN
Solar/Wind Harmer
4.425
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
270024AE2-089 GEN
Solar/Wind Harmer
0.008
970115AG2-085 GEN
Solar/Wind Harmer
2.943
270054AF2-122 C O1
Solar/Wind Helper
1.539
970373AG2-245 GEN
Solar/Wind Harmer
18.378
274676JOLIET 29;8U
Adder
38.397
274674JOLIET 9 ;6U
Adder
19.252
274732ELWOOD EC;7P
Adder
20.542
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
4.544
274745AC1-111 GEN9
Adder
6.959
270055AF2-134 C O1
Solar/Wind Harmer
0.007
276691AA1-018 GEN1
Solar/Wind Harmer
1.044
274682WAUKEGAN ;7U
Adder
22.199
274828WAUKEGAN ;BP
Adder
13.634
958381AF2-132 GEN
Solar/Wind Harmer
0.001
962781AG1-127 GEN
Solar/Wind Harmer
8.166
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
11.147
939401AE1-172 GEN
Solar/Wind Harmer
6.413
274872LEEDK;1U
Solar/Wind Harmer
0.005
276901AD2-066 C O1
Solar/Wind Harmer
0.008
965011AG1-365 GEN
Solar/Wind Harmer
8.544
971997AH1-543 GEN
Solar/Wind Harmer
4.478
276861AD2-134 GEN
Solar/Wind Harmer
0.153
957471AF2-041 GEN
Solar/Wind Harmer
25.469
959081AF2-199 GEN
Solar/Wind Harmer
8.49
971067AG2-660 GEN
Solar/Wind Harmer
2.83
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
10.593
274822ROCKFORD ;11
Adder
23.833
972235AH1-702 GEN1
Adder
3.057
970819AG2-516 GEN
Solar/Wind Harmer
10.134
971475AH1-234 GEN
Solar/Wind Harmer
4.092
970569AG2-363 GEN
Solar/Wind Harmer
25.271
274857EASY ROAD;U1
Solar/Wind Harmer
0.002
274761LEE CO EC;2U
Adder
11.187
274766LEE CO EC;7U
Adder
11.055
276158O29GEN2
Solar/Wind Harmer
0.001
965651AG1-433 GEN
Solar/Wind Harmer
2.438
274877BISHOP HL;1U
Solar/Wind Harmer
0.279
24791305MDL-5G
Solar/Wind Harmer
0.001
276726Z2-087_GEN
Solar/Wind Harmer
0.003
939741AE1-205 GEN
Solar/Wind Harmer
11.552
958861AF2-177 GEN
Solar/Wind Harmer
3.551
274854TWINGROVE;U2
Solar/Wind Harmer
0.003
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
972175AH1-670 GEN
Solar/Wind Harmer
6.643
945371AF1-202 GEN
Solar/Wind Harmer
0.001
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
3.078
963741AG1-226 GEN
Solar/Wind Harmer
18.629
276615X2-022 GEN
Solar/Wind Harmer
0.082
970291AG2-192 GEN
Solar/Wind Harmer
1.01
965911AG1-460 GEN
Solar/Wind Harmer
1.539
270032AE2-172
Solar/Wind Harmer
5.104
247521TR3_G114
Solar/Wind Harmer
0.277
270246TR4_N_V150
Solar/Wind Harmer
0.049
944231AF1-091 GEN
Solar/Wind Harmer
2.021
276903AD2-071 C
Solar/Wind Harmer
8.405
270005AE1-210 C O1
Solar/Wind Harmer
1.614
965031AG1-367 GEN
Solar/Wind Harmer
7.45
24695305TIMB G C
Solar/Wind Harmer
0.002
970333AG2-219 GEN
Solar/Wind Harmer
4.707
944201AF1-088_MTX
Adder
118.46
957141AF2-008_MTX
Adder
32.732
NYPJM->LTFIMP_NY
CLTF
3.756
LGEELTFEXP_LGEE->PJM
CLTF
5.526
WECLTFEXP_WEC->PJM
CLTF
4.63
AG2-052LTFEXP_AG2-052->PJM
LTF
0.285
AH1-155LTFEXP_AH1-155->PJM
LTF
0.428
LAGNLTFEXP_LAGN->PJM
CLTF
16.296
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.027
TVALTFEXP_TVA->PJM
CLTF
7.706
CBM West 1LTFEXP_CBM-W1->PJM
CBM
146.812
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.167
MECLTFEXP_MEC->PJM
CLTF
18.496
SIGELTFEXP_SIGE->PJM
CLTF
0.474
CPLELTFEXP_CPLE->PJM
CLTF
3.24
CBM West 2LTFEXP_CBM-W2->PJM
CBM
120.262

Details for 05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line l/o AEP_P1-2_#706_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#706_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.18 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5310.77
MW Contribution:3.93
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
5.145
971599AH1-298 GEN
50/50
14.587
270144AC1-141 ST1_
50/50
3.152
24653605MOTTVILLE
50/50
0.006
24643105BUCHANAN
50/50
0.019
962771AG1-126 GEN
Solar/Wind Harmer
120.047
270284AF1-227 GEN1
Solar/Wind Harmer
0.014
270286AF1-227 GEN2
Solar/Wind Harmer
0.006
270287AF1-227 GEN3
Solar/Wind Harmer
0.006
971347AH1-153 GEN
Solar/Wind Harmer
16.236
270071AF1-092 GEN
Solar/Wind Harmer
20.132
971771AH1-392 GEN
Solar/Wind Harmer
10.346
971619AH1-309 GEN
Solar/Wind Harmer
4.631
971769AH1-391 GEN
Solar/Wind Harmer
11.424
960681AF2-359 GEN
Solar/Wind Harmer
-0.002
24729505KEY G4
Adder
9.267
274775LINCOLN ;6U
Adder
11.972
274776LINCOLN ;7U
Adder
11.972
274777LINCOLN ;8U
Adder
11.972
965041AG1-368 GEN
Solar/Wind Harmer
9.847
270578AF1-285 GEN2
Solar/Wind Harmer
0.651
274814UNIV PK N;0U
Adder
7.057
274807UNIV PK N;3U
Adder
7.042
274805UNIV PK N;1U
Adder
7.011
274811UNIV PK N;7U
Adder
6.996
972037AH1-567 GEN1
Adder
0.254
274827FISK ;RP
Adder
10.776
960591AF2-350 GEN
Solar/Wind Harmer
9.68
972227AH1-698 GEN1
Adder
3.616
965051AG1-369 GEN
Solar/Wind Harmer
4.807
274687WILL CNTY;4U
Adder
38.503
274687WILL CNTY;4U
Adder
38.503
274675JOLIET 29;7U
Adder
42.223
274675JOLIET 29;7U
Adder
40.715
274728ELWOOD EC;5P
Adder
22.567
274731ELWOOD EC;2P
Adder
22.566
274733ELWOOD EC;3P
Adder
22.566
274735ELWOOD EC;4P
Adder
22.566
270536AF1-215 GEN2
Solar/Wind Harmer
0.012
970833AG2-524 GEN
Solar/Wind Harmer
10.52
970833AG2-524 GEN
Solar/Wind Harmer
7.013
971549AH1-272 GEN
Solar/Wind Harmer
19.681
274746AC1-111 G10
Adder
7.614
274744AC1-111 GEN8
Adder
7.614
963791AG1-232 GEN
Solar/Wind Harmer
12.76
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
1.183
270302AB2-170 GEN
Solar/Wind Harmer
0.006
270317AD1-130_GEN
Solar/Wind Harmer
0.013
971653AH1-327 GEN
Solar/Wind Harmer
1.314
958391AF2-133 GEN
Solar/Wind Harmer
0.001
276868AE1-113 GEN
Solar/Wind Harmer
1.855
276882AE2-255 GEN
Solar/Wind Harmer
1.081
971177AH1-047 GEN
Solar/Wind Harmer
5.697
965101AG1-375 GEN
Solar/Wind Harmer
9.202
971411AH1-196 GEN
Solar/Wind Harmer
13.802
971675AH1-338 GEN
Solar/Wind Harmer
3.588
274863CRW1-WTG
Solar/Wind Harmer
0.003
274864CRW2-WTG
Solar/Wind Harmer
0.003
971611AH1-305 GEN
Solar/Wind Harmer
5.454
971171AH1-044 GEN
Solar/Wind Harmer
18.285
274823ROCKFORD ;21
Adder
25.447
276612AE2-035 GEN
Solar/Wind Harmer
0.002
926823AC1-168 GEN
Solar/Wind Harmer
1.535
970169AG2-114 GEN
Solar/Wind Harmer
9.023
971681AH1-341 GEN
Solar/Wind Harmer
14.483
247607V1-011 GEN
Solar/Wind Harmer
0.001
961011AF2-392 GEN
Solar/Wind Harmer
5.219
945581AF1-223 GEN
Solar/Wind Harmer
0.001
957751AF2-069 GEN
Solar/Wind Harmer
0.292
24690905MDL-1G C
Solar/Wind Harmer
0.003
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0.002
276655WTG1_EQ
Solar/Wind Harmer
0.003
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
9.145
941731AE2-173 GEN
Solar/Wind Harmer
7.258
946321AF1-296 GEN
Solar/Wind Harmer
4.827
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
270024AE2-089 GEN
Solar/Wind Harmer
0.009
971609AH1-304 GEN
Solar/Wind Harmer
1.375
970289AG2-191 GEN
Solar/Wind Harmer
1.578
963841AG1-237 GEN
Solar/Wind Harmer
3.575
270594AE1-207 GEN
Solar/Wind Harmer
9.172
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.295
276848AB2-070 GEN3
Solar/Wind Harmer
0.294
970115AG2-085 GEN
Solar/Wind Harmer
3.159
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
270297AD1-101 GEN
Solar/Wind Harmer
0.002
970615AG2-402 GEN
50/50
3.512
247620Y3-023
50/50
0.722
270102X2-052 ST
50/50
2.354
270100X2-052 CT1
50/50
2.169
270101X2-052 CT2
50/50
2.169
270471AD2-092_GEN
Solar/Wind Harmer
0.009
970611AG2-400 GEN
Solar/Wind Harmer
10.537
970627AG2-408 GEN
Solar/Wind Harmer
3.161
970321AG2-212 GEN
Solar/Wind Harmer
4.559
270216AD2-079_GEN
Solar/Wind Harmer
0.002
957891AF2-083 GEN
Solar/Wind Harmer
0.001
270526AF1-158 GEN
Solar/Wind Harmer
0.013
24441505OLIV SLR
Solar/Wind Harmer
0
961051AF2-396 GEN
Solar/Wind Harmer
20.46
961051AF2-396 GEN
Solar/Wind Harmer
13.64
965681AG1-436 GEN
Solar/Wind Harmer
12.752
965791AG1-447 GEN
Solar/Wind Harmer
9.351
274770LINCOLN ;1U
Adder
11.972
274771LINCOLN ;2U
Adder
11.972
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
274808UNIV PK N;4U
Adder
6.965
274803UNIV PARK;6U
Adder
8.1
274888KELLY CRK;1U
Solar/Wind Harmer
0.568
274887GEN-1.85
Solar/Wind Harmer
0.255
276843GEN-1.7
Solar/Wind Harmer
0.313
958011AF2-095 GEN
Solar/Wind Harmer
13.939
972259AH1-714 GEN
Adder
26.463
274674JOLIET 9 ;6U
Adder
21.154
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
971573AH1-285 GEN
Solar/Wind Harmer
1.764
958481AF2-142 GEN
Solar/Wind Harmer
14.096
274695ROCKY RD ;2P
Adder
14.996
274693ROCKY RD ;1P
Adder
14.848
274697ROCKY RD ;3P
Adder
4.074
274696ROCKY RD ;4P
Adder
15.349
274861TOP CROP ;1U
Solar/Wind Harmer
0.003
274862TOP CROP ;2U
Solar/Wind Harmer
1.271
944541AF1-119 GEN
Solar/Wind Harmer
0.629
960971AF2-388 GEN
Solar/Wind Harmer
5.509
274683WAUKEGAN ;8U
Adder
28.303
274683WAUKEGAN ;8U
Adder
23.858
246938BC-WTG3
Solar/Wind Harmer
0.338
246937BC-WTG2
Solar/Wind Harmer
0.379
962691AG1-118 GEN
Solar/Wind Harmer
27.992
970921AG2-575 GEN
Solar/Wind Harmer
9.308
970921AG2-575 GEN
Solar/Wind Harmer
3.103
958491AF2-143 GEN
Solar/Wind Harmer
13.931
274879MINONK ;1U
Solar/Wind Harmer
0.39
942991AE2-321 GEN
Solar/Wind Harmer
10.32
971333AH1-146 GEN
Solar/Wind Harmer
18.389
971335AH1-147 GEN
Solar/Wind Harmer
18.389
971341AH1-150 GEN
Solar/Wind Harmer
18.285
971343AH1-151 GEN
Solar/Wind Harmer
18.285
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
942221AE2-234 GEN
Solar/Wind Harmer
0.046
274856ECOGROVE ;U1
Solar/Wind Harmer
0.213
276611AD2-172 GEN
Solar/Wind Harmer
0.002
938861AE1-114 GEN
Solar/Wind Harmer
5.096
274764LEE CO EC;5U
Adder
11.975
274765LEE CO EC;6U
Adder
11.975
274762LEE CO EC;3U
Adder
11.947
274763LEE CO EC;4U
Adder
11.834
276603SUBLETTE C
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
270007AE1-245 C
Solar/Wind Harmer
0.002
972267AH1-718 GEN
Adder
5.295
276741O09 GEN1
Solar/Wind Harmer
0.315
276708O09 GEN2
Solar/Wind Harmer
0.315
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.347
276646AC1-214 GEN2
Solar/Wind Harmer
0.347
970623AG2-406 GEN
Solar/Wind Harmer
1.614
276782AC1-033 GEN
Solar/Wind Harmer
0.001
960611AF2-352 GEN
Solar/Wind Harmer
2.854
966841AG1-555 GEN
Solar/Wind Harmer
0.959
270599AE1-208 GEN
Solar/Wind Harmer
7.715
270031AE2-169
Solar/Wind Harmer
4.629
971613AH1-306 GEN
Solar/Wind Harmer
3.931
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
970241AG2-163 GEN
Solar/Wind Harmer
4.69
960441AF2-335 GEN
Solar/Wind Harmer
7.897
970825AG2-519 GEN
Solar/Wind Harmer
8.719
964611AG1-324 GEN
Solar/Wind Harmer
0.584
270201AC2-176 GEN
Solar/Wind Harmer
0.001
970621AG2-405 GEN
Solar/Wind Harmer
1.413
247621Y3-024
Adder
0.262
276916AD2-100_GEN
Solar/Wind Harmer
13.41
276911AD2-131_GEN
Solar/Wind Harmer
0.883
24721805FLATG3
50/50
5.145
24721705FLATG2
50/50
94.33
24344105CKG2
50/50
12.069
270143AC1-141 CT2_
50/50
3.558
24639705ELKHART HY
50/50
0.241
970521AG2-332 GEN
50/50
17.184
24307105BERRINSP G
50/50
0.032
962761AG1-125 GEN
Solar/Wind Harmer
120.047
970149AG2-104 GEN
Solar/Wind Harmer
129.655
970155AG2-107 GEN
Solar/Wind Harmer
76.659
270349AD2-093_GEN
Solar/Wind Harmer
0.009
965011AG1-365 GEN
Solar/Wind Harmer
10.537
970245AG2-165 GEN
Solar/Wind Harmer
4.559
270063AE2-323 C
Solar/Wind Harmer
0.008
270505AE1-170 C O1
Solar/Wind Harmer
10.806
945111AF1-176 GEN
Solar/Wind Harmer
18.321
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
5.329
274773LINCOLN ;4U
Adder
11.972
274774LINCOLN ;5U
Adder
11.972
274723RIVER EC ;12
Adder
25.205
274751CRETE EC ;1U
Adder
11.58
274754CRETE EC ;4U
Adder
11.58
270223U2-072_GEN1
Solar/Wind Harmer
0.001
276164X3-005 C
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
20.506
274812UNIV PK N;8U
Adder
6.996
274801UNIV PARK;4U
Adder
8.089
276776AD2-060 GEN
Solar/Wind Harmer
1.011
247521TR3_G114
Solar/Wind Harmer
0.351
270246TR4_N_V150
Solar/Wind Harmer
0.062
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
42.222
274674JOLIET 9 ;6U
Adder
21.154
274732ELWOOD EC;7P
Adder
22.567
270055AF2-134 C O1
Solar/Wind Harmer
0.007
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
274745AC1-111 GEN9
Adder
7.614
944231AF1-091 GEN
Solar/Wind Harmer
2.532
24695305TIMB G C
Solar/Wind Harmer
0.002
965421AG1-410 GEN
Solar/Wind Harmer
28.36
958381AF2-132 GEN
Solar/Wind Harmer
0.001
276691AA1-018 GEN1
Solar/Wind Harmer
1.138
965651AG1-433 GEN
Solar/Wind Harmer
2.755
274682WAUKEGAN ;7U
Adder
24.169
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
12.195
274828WAUKEGAN ;BP
Adder
14.836
246936BC-WTG1
Solar/Wind Harmer
0.379
270489AE1-102 GEN1
Solar/Wind Harmer
1.214
270462AD2-086
Solar/Wind Harmer
0.02
962781AG1-127 GEN
Solar/Wind Harmer
8.858
939401AE1-172 GEN
Solar/Wind Harmer
6.954
274872LEEDK;1U
Solar/Wind Harmer
0.006
276901AD2-066 C O1
Solar/Wind Harmer
0.009
971997AH1-543 GEN
Solar/Wind Harmer
4.843
958861AF2-177 GEN
Solar/Wind Harmer
3.987
276861AD2-134 GEN
Solar/Wind Harmer
0.165
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
11.452
957471AF2-041 GEN
Solar/Wind Harmer
27.428
959081AF2-199 GEN
Solar/Wind Harmer
9.143
971067AG2-660 GEN
Solar/Wind Harmer
3.048
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
274822ROCKFORD ;11
Adder
25.633
972235AH1-702 GEN1
Adder
3.284
970819AG2-516 GEN
Solar/Wind Harmer
10.874
971475AH1-234 GEN
Solar/Wind Harmer
4.385
970569AG2-363 GEN
Solar/Wind Harmer
27.095
274857EASY ROAD;U1
Solar/Wind Harmer
0.002
274761LEE CO EC;2U
Adder
11.947
274766LEE CO EC;7U
Adder
11.806
276158O29GEN2
Solar/Wind Harmer
0.001
945371AF1-202 GEN
Solar/Wind Harmer
0.001
274877BISHOP HL;1U
Solar/Wind Harmer
0.295
24791305MDL-5G
Solar/Wind Harmer
0.001
276726Z2-087_GEN
Solar/Wind Harmer
0.003
939741AE1-205 GEN
Solar/Wind Harmer
12.194
274854TWINGROVE;U2
Solar/Wind Harmer
0.004
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
972175AH1-670 GEN
Solar/Wind Harmer
6.873
970291AG2-192 GEN
Solar/Wind Harmer
1.08
270032AE2-172
Solar/Wind Harmer
5.46
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
3.14
963741AG1-226 GEN
Solar/Wind Harmer
19.026
270005AE1-210 C O1
Solar/Wind Harmer
1.733
965031AG1-367 GEN
Solar/Wind Harmer
8
276615X2-022 GEN
Solar/Wind Harmer
0.084
276903AD2-071 C
Solar/Wind Harmer
8.872
970825AG2-519 GEN
Solar/Wind Harmer
2.793
965911AG1-460 GEN
Solar/Wind Harmer
1.538
24728605AND G2
Adder
3.739
24722005FLATG5
50/50
5.145
24721905FLATG4
50/50
94.33
270475AD2-096_GEN
50/50
10.026
270142AC1-141 CT1_
50/50
3.558
24641605TWIN BRNCH
50/50
0.026
24344005CKG1
50/50
9.691
24642205MAYFLWER
50/50
0.992
944961AF1-161 GEN
50/50
4.253
962601AG1-109 GEN
50/50
4.253
247604X1-042
50/50
0.632
970153AG2-106 GEN
Solar/Wind Harmer
76.659
270043AE2-236 GEN
Solar/Wind Harmer
6.969
970349AG2-230 GEN
Solar/Wind Harmer
16.236
959331AF2-224 GEN
Solar/Wind Harmer
7.376
965021AG1-366 GEN
Solar/Wind Harmer
3.512
970513AG2-328 GEN
Solar/Wind Harmer
4.559
970517AG2-330 GEN
Solar/Wind Harmer
27.357
247643Z2-116 C
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
6.732
945111AF1-176 GEN
Solar/Wind Harmer
8.323
944531AF1-118 GEN
Solar/Wind Harmer
45.595
24441205WTRV SLR C
Solar/Wind Harmer
0
274772LINCOLN ;3U
Adder
11.972
274724RIVER EC ;11
Adder
24.913
274752CRETE EC ;2U
Adder
11.58
274753CRETE EC ;3U
Adder
11.58
270391AF1-285 GEN3
Solar/Wind Harmer
0.651
970707AG2-453 GEN
Solar/Wind Harmer
31.724
274802UNIV PARK;5U
Adder
8.1
274826FISK ;BP
Adder
15.205
274800UNIV PARK;3U
Adder
8.089
972038AH1-567 GEN2
Adder
0.506
276806AD2-047 C O1
Solar/Wind Harmer
5.485
970941AG2-585 GEN
Solar/Wind Harmer
12.1
972228AH1-698 GEN2
Adder
5.135
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.062
276897AD1-100 C
Solar/Wind Harmer
0.013
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
274676JOLIET 29;8U
Adder
40.714
274730ELWOOD EC;6P
Adder
22.567
274734ELWOOD EC;8P
Adder
22.567
274736ELWOOD EC;9P
Adder
22.567
274729ELWOOD EC;1P
Adder
22.566
276893AG1-478 C
Solar/Wind Harmer
0.379
270535AF1-215 GEN1
Solar/Wind Harmer
0.012
943121AE2-341 GEN
Solar/Wind Harmer
15.96
943591AF1-030 GEN
Solar/Wind Harmer
10.614
964401AG1-302 GEN
Solar/Wind Harmer
0.001
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
24.169
270491AE1-102 GEN2
Solar/Wind Harmer
1.214
270485AE1-090_GEN
Solar/Wind Harmer
0.001
276805AD2-038 GEN
Solar/Wind Harmer
0.003
274872LEEDK;1U
Solar/Wind Harmer
0.341
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
0.982
274855GSG-6 ;RU
Solar/Wind Harmer
0.337
274850MENDOTA H;RU
Solar/Wind Harmer
0.108
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.165
959091AF2-200 GEN
Solar/Wind Harmer
18.285
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
2.856
970571AG2-364 GEN
Solar/Wind Harmer
18.064
274858EASY ROAD;U2
Solar/Wind Harmer
0.002
274760LEE CO EC;1U
Adder
11.947
274767LEE CO EC;8U
Adder
11.806
276157O29GEN1
Solar/Wind Harmer
1.431
270258AD1-119 GEN
Solar/Wind Harmer
0.002
274878BISHOP HL;2U
Solar/Wind Harmer
0.295
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
8.785
270404AC1-167 GEN
Solar/Wind Harmer
0.004
942111AE2-223 GEN
Solar/Wind Harmer
2.831
965931AG1-462 GEN
Solar/Wind Harmer
21.861
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
965091AG1-374 GEN
Solar/Wind Harmer
25.685
959611AF2-252 GEN
Solar/Wind Harmer
2.854
971617AH1-308 GEN
Solar/Wind Harmer
7.03
247642Z2-115 C
Solar/Wind Harmer
0.004
970289AG2-191 GEN
Solar/Wind Harmer
0.914
970291AG2-192 GEN
Solar/Wind Harmer
0.831
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
3.74
276668AB2-070 GEN1
Solar/Wind Harmer
0.295
958821AF2-173 GEN
Solar/Wind Harmer
11.2
270004AE1-209 GEN
Solar/Wind Harmer
1.733
276621W2-048 GEN
Solar/Wind Harmer
0.401
276838X2-022 GEN2
Solar/Wind Harmer
0.448
946031AF1-268 GEN
Solar/Wind Harmer
7.422
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
11.672
942481AE2-261 GEN
Solar/Wind Harmer
22.986
24728705AND G3
Adder
7.82
24728505AND G1
Adder
3.739
944201AF1-088_MTX
Adder
85.667
NYPJM->LTFIMP_NY
CLTF
2.99
LGEELTFEXP_LGEE->PJM
CLTF
4.155
WECLTFEXP_WEC->PJM
CLTF
4.968
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.286
AG2-052LTFEXP_AG2-052->PJM
LTF
0.312
AH1-155LTFEXP_AH1-155->PJM
LTF
0.469
LAGNLTFEXP_LAGN->PJM
CLTF
11.144
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.328
TVALTFEXP_TVA->PJM
CLTF
4.56
CBM West 1LTFEXP_CBM-W1->PJM
CBM
161.402
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.132
MECLTFEXP_MEC->PJM
CLTF
18.394
SIGELTFEXP_SIGE->PJM
CLTF
0.399
CBM West 2LTFEXP_CBM-W2->PJM
CBM
96.989

Details for 05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line l/o Base Case


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.73 %
Rating:4047.0 MVA
Rating Type:A
MVA to Mitigate:4643.02
MW Contribution:2.94
Bus #Bus NameTypeMW Contribution
270102X2-052 ST
50/50
1.747
270100X2-052 CT1
50/50
1.61
270101X2-052 CT2
50/50
1.61
247620Y3-023
50/50
0.525
274770LINCOLN ;1U
50/50
9.593
274771LINCOLN ;2U
50/50
9.593
970321AG2-212 GEN
Solar/Wind Harmer
3.44
270216AD2-079_GEN
Solar/Wind Harmer
0.001
965681AG1-436 GEN
Solar/Wind Harmer
9.481
965791AG1-447 GEN
Solar/Wind Harmer
6.953
270526AF1-158 GEN
Solar/Wind Harmer
0.009
24441505OLIV SLR
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
14.924
961051AF2-396 GEN
Solar/Wind Harmer
9.95
970611AG2-400 GEN
Solar/Wind Harmer
7.366
970627AG2-408 GEN
Solar/Wind Harmer
2.21
274808UNIV PK N;4U
Adder
5.255
972259AH1-714 GEN
Adder
20.044
274803UNIV PARK;6U
Adder
6.123
274888KELLY CRK;1U
Solar/Wind Harmer
0.43
274887GEN-1.85
Solar/Wind Harmer
0.193
276843GEN-1.7
Solar/Wind Harmer
0.237
958011AF2-095 GEN
Solar/Wind Harmer
10.545
274674JOLIET 9 ;6U
Adder
16.042
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
971573AH1-285 GEN
Solar/Wind Harmer
1.342
274695ROCKY RD ;2P
Adder
11.425
274693ROCKY RD ;1P
Adder
11.312
274697ROCKY RD ;3P
Adder
3.104
274696ROCKY RD ;4P
Adder
11.694
958481AF2-142 GEN
Solar/Wind Harmer
10.727
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.967
274683WAUKEGAN ;8U
Adder
21.572
274683WAUKEGAN ;8U
Adder
18.184
962691AG1-118 GEN
Solar/Wind Harmer
21.36
970921AG2-575 GEN
Solar/Wind Harmer
7.106
970921AG2-575 GEN
Solar/Wind Harmer
2.369
958491AF2-143 GEN
Solar/Wind Harmer
10.627
942991AE2-321 GEN
Solar/Wind Harmer
7.889
274879MINONK ;1U
Solar/Wind Harmer
0.298
971333AH1-146 GEN
Solar/Wind Harmer
14.073
971335AH1-147 GEN
Solar/Wind Harmer
14.073
971341AH1-150 GEN
Solar/Wind Harmer
14.009
971343AH1-151 GEN
Solar/Wind Harmer
14.009
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
274856ECOGROVE ;U1
Solar/Wind Harmer
0.164
276611AD2-172 GEN
Solar/Wind Harmer
0.002
938861AE1-114 GEN
Solar/Wind Harmer
3.917
274764LEE CO EC;5U
Adder
9.213
274765LEE CO EC;6U
Adder
9.213
274762LEE CO EC;3U
Adder
9.191
274763LEE CO EC;4U
Adder
9.105
276603SUBLETTE C
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.461
960971AF2-388 GEN
Solar/Wind Harmer
4.033
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
972267AH1-718 GEN
Adder
4.082
276741O09 GEN1
Solar/Wind Harmer
0.243
276708O09 GEN2
Solar/Wind Harmer
0.243
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.268
276646AC1-214 GEN2
Solar/Wind Harmer
0.268
276782AC1-033 GEN
Solar/Wind Harmer
0.001
960611AF2-352 GEN
Solar/Wind Harmer
2.211
942221AE2-234 GEN
Solar/Wind Harmer
0.033
966841AG1-555 GEN
Solar/Wind Harmer
0.741
270471AD2-092_GEN
Solar/Wind Harmer
0.005
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
970241AG2-163 GEN
Solar/Wind Harmer
3.657
270599AE1-208 GEN
Solar/Wind Harmer
5.676
270031AE2-169
Solar/Wind Harmer
3.406
971613AH1-306 GEN
Solar/Wind Harmer
2.938
276916AD2-100_GEN
Solar/Wind Harmer
12.71
276911AD2-131_GEN
Solar/Wind Harmer
0.837
246938BC-WTG3
Solar/Wind Harmer
0.219
246937BC-WTG2
Solar/Wind Harmer
0.245
24344105CKG2
50/50
8.939
270143AC1-141 CT2_
50/50
2.603
24639705ELKHART HY
50/50
0.176
970521AG2-332 GEN
50/50
12.519
274773LINCOLN ;4U
50/50
9.593
274774LINCOLN ;5U
50/50
9.593
962761AG1-125 GEN
Solar/Wind Harmer
74.603
970149AG2-104 GEN
Solar/Wind Harmer
80.573
970155AG2-107 GEN
Solar/Wind Harmer
47.639
970245AG2-165 GEN
Solar/Wind Harmer
3.44
270505AE1-170 C O1
Solar/Wind Harmer
7.896
270063AE2-323 C
Solar/Wind Harmer
0.006
945111AF1-176 GEN
Solar/Wind Harmer
13.37
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
3.886
274723RIVER EC ;12
Adder
18.99
274751CRETE EC ;1U
Adder
8.717
274754CRETE EC ;4U
Adder
8.717
276164X3-005 C
Solar/Wind Harmer
0
965011AG1-365 GEN
Solar/Wind Harmer
7.366
274812UNIV PK N;8U
Adder
5.278
970373AG2-245 GEN
Solar/Wind Harmer
15.386
276776AD2-060 GEN
Solar/Wind Harmer
0.765
274801UNIV PARK;4U
Adder
6.118
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
32.008
274674JOLIET 9 ;6U
Adder
16.042
274732ELWOOD EC;7P
Adder
17.114
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
274745AC1-111 GEN9
Adder
5.788
270055AF2-134 C O1
Solar/Wind Harmer
0.006
276691AA1-018 GEN1
Solar/Wind Harmer
0.866
274682WAUKEGAN ;7U
Adder
18.416
274828WAUKEGAN ;BP
Adder
11.308
958381AF2-132 GEN
Solar/Wind Harmer
0.001
962781AG1-127 GEN
Solar/Wind Harmer
6.763
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.233
274872LEEDK;1U
Solar/Wind Harmer
0.004
939401AE1-172 GEN
Solar/Wind Harmer
5.304
276901AD2-066 C O1
Solar/Wind Harmer
0.007
971997AH1-543 GEN
Solar/Wind Harmer
3.701
276861AD2-134 GEN
Solar/Wind Harmer
0.126
957471AF2-041 GEN
Solar/Wind Harmer
21.014
959081AF2-199 GEN
Solar/Wind Harmer
7.005
971067AG2-660 GEN
Solar/Wind Harmer
2.335
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
274822ROCKFORD ;11
Adder
19.652
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.717
972235AH1-702 GEN1
Adder
2.519
970819AG2-516 GEN
Solar/Wind Harmer
8.346
971475AH1-234 GEN
Solar/Wind Harmer
3.368
970569AG2-363 GEN
Solar/Wind Harmer
20.788
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
9.191
274766LEE CO EC;7U
Adder
9.083
965651AG1-433 GEN
Solar/Wind Harmer
2.017
276158O29GEN2
Solar/Wind Harmer
0.001
274877BISHOP HL;1U
Solar/Wind Harmer
0.228
24721705FLATG2
Adder
19.64
24791305MDL-5G
Solar/Wind Harmer
0.001
958861AF2-177 GEN
Solar/Wind Harmer
2.923
276726Z2-087_GEN
Solar/Wind Harmer
0.002
939741AE1-205 GEN
Solar/Wind Harmer
9.413
274854TWINGROVE;U2
Solar/Wind Harmer
0.003
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.002
944231AF1-091 GEN
Solar/Wind Harmer
1.739
945371AF1-202 GEN
Solar/Wind Harmer
0.001
247521TR3_G114
Solar/Wind Harmer
0.237
270246TR4_N_V150
Solar/Wind Harmer
0.042
972175AH1-670 GEN
Solar/Wind Harmer
5.355
270349AD2-093_GEN
Solar/Wind Harmer
0.005
24695305TIMB G C
Solar/Wind Harmer
0.002
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
2.462
963741AG1-226 GEN
Solar/Wind Harmer
14.839
276615X2-022 GEN
Solar/Wind Harmer
0.066
970291AG2-192 GEN
Solar/Wind Harmer
0.81
965421AG1-410 GEN
Solar/Wind Harmer
18.496
270032AE2-172
Solar/Wind Harmer
4.081
965911AG1-460 GEN
Solar/Wind Harmer
1.218
246936BC-WTG1
Solar/Wind Harmer
0.245
270489AE1-102 GEN1
Solar/Wind Harmer
0.785
971599AH1-298 GEN
50/50
10.558
270144AC1-141 ST1_
50/50
2.306
24643105BUCHANAN
50/50
0.014
24653605MOTTVILLE
50/50
0.004
274775LINCOLN ;6U
50/50
9.593
274776LINCOLN ;7U
50/50
9.593
274777LINCOLN ;8U
50/50
9.593
962771AG1-126 GEN
Solar/Wind Harmer
74.603
971347AH1-153 GEN
Solar/Wind Harmer
12.013
270071AF1-092 GEN
Solar/Wind Harmer
14.717
971771AH1-392 GEN
Solar/Wind Harmer
7.604
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971769AH1-391 GEN
Solar/Wind Harmer
8.444
971619AH1-309 GEN
Solar/Wind Harmer
3.384
274814UNIV PK N;0U
Adder
5.324
274807UNIV PK N;3U
Adder
5.313
274805UNIV PK N;1U
Adder
5.29
274811UNIV PK N;7U
Adder
5.278
274827FISK ;RP
Adder
8.149
972037AH1-567 GEN1
Adder
0.192
960591AF2-350 GEN
Solar/Wind Harmer
7.323
972227AH1-698 GEN1
Adder
2.737
274687WILL CNTY;4U
Adder
29.176
274687WILL CNTY;4U
Adder
29.176
274675JOLIET 29;7U
Adder
32.008
274675JOLIET 29;7U
Adder
30.865
24729505KEY G4
Adder
6.759
274731ELWOOD EC;2P
Adder
17.114
274733ELWOOD EC;3P
Adder
17.114
274735ELWOOD EC;4P
Adder
17.114
274728ELWOOD EC;5P
Adder
17.114
970833AG2-524 GEN
Solar/Wind Harmer
7.985
970833AG2-524 GEN
Solar/Wind Harmer
5.323
274746AC1-111 G10
Adder
5.788
274744AC1-111 GEN8
Adder
5.788
270536AF1-215 GEN2
Solar/Wind Harmer
0.009
971177AH1-047 GEN
Solar/Wind Harmer
4.355
958391AF2-133 GEN
Solar/Wind Harmer
0.001
276868AE1-113 GEN
Solar/Wind Harmer
1.417
276882AE2-255 GEN
Solar/Wind Harmer
0.825
971675AH1-338 GEN
Solar/Wind Harmer
2.746
971411AH1-196 GEN
Solar/Wind Harmer
10.56
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
971171AH1-044 GEN
Solar/Wind Harmer
14.009
274823ROCKFORD ;21
Adder
19.51
971611AH1-305 GEN
Solar/Wind Harmer
4.152
276612AE2-035 GEN
Solar/Wind Harmer
0.002
926823AC1-168 GEN
Solar/Wind Harmer
1.178
970169AG2-114 GEN
Solar/Wind Harmer
6.92
971681AH1-341 GEN
Solar/Wind Harmer
11.133
961011AF2-392 GEN
Solar/Wind Harmer
4.021
957751AF2-069 GEN
Solar/Wind Harmer
0.225
971549AH1-272 GEN
Solar/Wind Harmer
14.034
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
965101AG1-375 GEN
Solar/Wind Harmer
6.746
965041AG1-368 GEN
Solar/Wind Harmer
6.733
276655WTG1_EQ
Solar/Wind Harmer
0.003
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.06
941731AE2-173 GEN
Solar/Wind Harmer
5.603
946321AF1-296 GEN
Solar/Wind Harmer
3.744
963791AG1-232 GEN
Solar/Wind Harmer
8.989
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
945581AF1-223 GEN
Solar/Wind Harmer
0
965051AG1-369 GEN
Solar/Wind Harmer
3.241
963841AG1-237 GEN
Solar/Wind Harmer
2.776
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.231
276848AB2-070 GEN3
Solar/Wind Harmer
0.23
970289AG2-191 GEN
Solar/Wind Harmer
1.184
971609AH1-304 GEN
Solar/Wind Harmer
1.011
270594AE1-207 GEN
Solar/Wind Harmer
6.856
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.765
270284AF1-227 GEN1
Solar/Wind Harmer
0.008
270286AF1-227 GEN2
Solar/Wind Harmer
0.003
270287AF1-227 GEN3
Solar/Wind Harmer
0.003
270054AF2-122 C O1
Solar/Wind Helper
1.65
270142AC1-141 CT1_
50/50
2.603
24641605TWIN BRNCH
50/50
0.019
24344005CKG1
50/50
7.096
24642205MAYFLWER
50/50
0.728
274772LINCOLN ;3U
50/50
9.593
970153AG2-106 GEN
Solar/Wind Harmer
47.639
970349AG2-230 GEN
Solar/Wind Harmer
12.013
970513AG2-328 GEN
Solar/Wind Harmer
3.44
970517AG2-330 GEN
Solar/Wind Harmer
20.64
270043AE2-236 GEN
Solar/Wind Harmer
5.033
247643Z2-116 C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
6.073
970031AG2-029 GEN
Solar/Wind Harmer
4.844
944531AF1-118 GEN
Solar/Wind Harmer
33.218
274724RIVER EC ;11
Adder
18.771
274752CRETE EC ;2U
Adder
8.717
274753CRETE EC ;3U
Adder
8.717
959331AF2-224 GEN
Solar/Wind Harmer
5.157
965021AG1-366 GEN
Solar/Wind Harmer
2.455
970707AG2-453 GEN
Solar/Wind Harmer
24.03
274826FISK ;BP
Adder
11.498
274802UNIV PARK;5U
Adder
6.123
276806AD2-047 C O1
Solar/Wind Harmer
4.15
970941AG2-585 GEN
Solar/Wind Harmer
9.154
274800UNIV PARK;3U
Adder
6.118
972038AH1-567 GEN2
Adder
0.383
972228AH1-698 GEN2
Adder
3.887
24441205WTRV SLR C
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
0.01
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
274676JOLIET 29;8U
Adder
30.865
274729ELWOOD EC;1P
Adder
17.114
274730ELWOOD EC;6P
Adder
17.114
274734ELWOOD EC;8P
Adder
17.114
274736ELWOOD EC;9P
Adder
17.114
276893AG1-478 C
Solar/Wind Harmer
0.288
943121AE2-341 GEN
Solar/Wind Harmer
12.132
943591AF1-030 GEN
Solar/Wind Harmer
8.068
247604X1-042
Adder
0.432
270535AF1-215 GEN1
Solar/Wind Harmer
0.009
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
18.416
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274872LEEDK;1U
Solar/Wind Harmer
0.26
276805AD2-038 GEN
Solar/Wind Harmer
0.002
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.751
274855GSG-6 ;RU
Solar/Wind Harmer
0.258
274850MENDOTA H;RU
Solar/Wind Harmer
0.083
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.126
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
959091AF2-200 GEN
Solar/Wind Harmer
14.009
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
2.191
970571AG2-364 GEN
Solar/Wind Harmer
13.859
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
9.191
274767LEE CO EC;8U
Adder
9.083
276157O29GEN1
Solar/Wind Harmer
1.104
274878BISHOP HL;2U
Solar/Wind Harmer
0.228
24721905FLATG4
Adder
19.64
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.747
942111AE2-223 GEN
Solar/Wind Harmer
2.185
965931AG1-462 GEN
Solar/Wind Harmer
16.976
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
965091AG1-374 GEN
Solar/Wind Harmer
19.897
959611AF2-252 GEN
Solar/Wind Harmer
2.211
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.042
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
2.93
276668AB2-070 GEN1
Solar/Wind Harmer
0.231
247642Z2-115 C
Solar/Wind Harmer
0.003
276621W2-048 GEN
Solar/Wind Harmer
0.316
276838X2-022 GEN2
Solar/Wind Harmer
0.352
970289AG2-191 GEN
Solar/Wind Harmer
0.686
970291AG2-192 GEN
Solar/Wind Harmer
0.623
942481AE2-261 GEN
Solar/Wind Harmer
18.215
270491AE1-102 GEN2
Solar/Wind Harmer
0.785
NYPJM->LTFIMP_NY
CLTF
2.589
LGEELTFEXP_LGEE->PJM
CLTF
3.659
WECLTFEXP_WEC->PJM
CLTF
3.814
AG2-052LTFEXP_AG2-052->PJM
LTF
0.236
AH1-155LTFEXP_AH1-155->PJM
LTF
0.355
LAGNLTFEXP_LAGN->PJM
CLTF
11.239
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.669
TVALTFEXP_TVA->PJM
CLTF
5.062
CBM West 1LTFEXP_CBM-W1->PJM
CBM
120.019
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.189
MECLTFEXP_MEC->PJM
CLTF
14.69
SIGELTFEXP_SIGE->PJM
CLTF
0.339
CPLELTFEXP_CPLE->PJM
CLTF
1.429
CBM West 2LTFEXP_CBM-W2->PJM
CBM
87.023

Details for 05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line l/o AP_P1-3_MP-765-501T_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-501T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:130.66 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5972.54
MW Contribution:3.67
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
1.795
971599AH1-298 GEN
50/50
12.157
962771AG1-126 GEN
Solar/Wind Harmer
80.781
971347AH1-153 GEN
Solar/Wind Harmer
14.036
270071AF1-092 GEN
Solar/Wind Harmer
17.319
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971771AH1-392 GEN
Solar/Wind Harmer
8.916
274775LINCOLN ;6U
Adder
10.782
274776LINCOLN ;7U
Adder
10.782
274777LINCOLN ;8U
Adder
10.782
971769AH1-391 GEN
Solar/Wind Harmer
9.94
971619AH1-309 GEN
Solar/Wind Harmer
3.958
274814UNIV PK N;0U
Adder
6.363
274807UNIV PK N;3U
Adder
6.35
274805UNIV PK N;1U
Adder
6.322
274811UNIV PK N;7U
Adder
6.308
274827FISK ;RP
Adder
9.754
972037AH1-567 GEN1
Adder
0.23
960591AF2-350 GEN
Solar/Wind Harmer
8.77
972227AH1-698 GEN1
Adder
3.278
274687WILL CNTY;4U
Adder
34.988
274687WILL CNTY;4U
Adder
34.988
274675JOLIET 29;7U
Adder
38.397
274675JOLIET 29;7U
Adder
37.026
274731ELWOOD EC;2P
Adder
20.542
274733ELWOOD EC;3P
Adder
20.542
274735ELWOOD EC;4P
Adder
20.542
274728ELWOOD EC;5P
Adder
20.542
970833AG2-524 GEN
Solar/Wind Harmer
9.589
970833AG2-524 GEN
Solar/Wind Harmer
6.393
274746AC1-111 G10
Adder
6.959
274744AC1-111 GEN8
Adder
6.959
24729505KEY G4
Adder
8.06
270536AF1-215 GEN2
Solar/Wind Harmer
0.011
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971177AH1-047 GEN
Solar/Wind Harmer
5.267
276868AE1-113 GEN
Solar/Wind Harmer
1.713
276882AE2-255 GEN
Solar/Wind Harmer
0.998
971675AH1-338 GEN
Solar/Wind Harmer
3.323
971411AH1-196 GEN
Solar/Wind Harmer
12.781
274863CRW1-WTG
Solar/Wind Harmer
0.003
274864CRW2-WTG
Solar/Wind Harmer
0.003
971171AH1-044 GEN
Solar/Wind Harmer
16.979
971611AH1-305 GEN
Solar/Wind Harmer
5.045
274823ROCKFORD ;21
Adder
23.66
276612AE2-035 GEN
Solar/Wind Harmer
0.002
926823AC1-168 GEN
Solar/Wind Harmer
1.432
970169AG2-114 GEN
Solar/Wind Harmer
8.423
971681AH1-341 GEN
Solar/Wind Harmer
13.539
961011AF2-392 GEN
Solar/Wind Harmer
4.902
957751AF2-069 GEN
Solar/Wind Harmer
0.275
24690905MDL-1G C
Solar/Wind Harmer
0.003
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0.002
276655WTG1_EQ
Solar/Wind Harmer
0.003
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
8.664
941731AE2-173 GEN
Solar/Wind Harmer
6.876
946321AF1-296 GEN
Solar/Wind Harmer
4.594
965101AG1-375 GEN
Solar/Wind Harmer
8.195
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
963841AG1-237 GEN
Solar/Wind Harmer
3.463
945581AF1-223 GEN
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
10.716
971549AH1-272 GEN
Solar/Wind Harmer
16.349
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.289
276848AB2-070 GEN3
Solar/Wind Harmer
0.287
965041AG1-368 GEN
Solar/Wind Harmer
7.862
970289AG2-191 GEN
Solar/Wind Harmer
1.476
971609AH1-304 GEN
Solar/Wind Harmer
1.254
270594AE1-207 GEN
Solar/Wind Harmer
8.574
965051AG1-369 GEN
Solar/Wind Harmer
3.795
944221AF1-090 GEN
Solar/Wind Harmer
4.425
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
270024AE2-089 GEN
Solar/Wind Harmer
0.008
970115AG2-085 GEN
Solar/Wind Harmer
2.943
270054AF2-122 C O1
Solar/Wind Helper
1.539
270102X2-052 ST
50/50
2.06
270100X2-052 CT1
50/50
1.898
270101X2-052 CT2
50/50
1.898
970321AG2-212 GEN
Solar/Wind Harmer
4.074
965681AG1-436 GEN
Solar/Wind Harmer
11.195
965791AG1-447 GEN
Solar/Wind Harmer
8.21
274770LINCOLN ;1U
Adder
10.782
274771LINCOLN ;2U
Adder
10.782
270526AF1-158 GEN
Solar/Wind Harmer
0.011
24441505OLIV SLR
Solar/Wind Harmer
0
270216AD2-079_GEN
Solar/Wind Harmer
0.001
957891AF2-083 GEN
Solar/Wind Harmer
0.001
274808UNIV PK N;4U
Adder
6.281
972259AH1-714 GEN
Adder
24.011
274803UNIV PARK;6U
Adder
7.329
274888KELLY CRK;1U
Solar/Wind Harmer
0.515
274887GEN-1.85
Solar/Wind Harmer
0.231
276843GEN-1.7
Solar/Wind Harmer
0.284
958011AF2-095 GEN
Solar/Wind Harmer
12.628
247620Y3-023
Adder
0.578
961051AF2-396 GEN
Solar/Wind Harmer
17.455
961051AF2-396 GEN
Solar/Wind Harmer
11.637
274674JOLIET 9 ;6U
Adder
19.252
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
971573AH1-285 GEN
Solar/Wind Harmer
1.615
274696ROCKY RD ;4P
Adder
14.093
274695ROCKY RD ;2P
Adder
13.768
274693ROCKY RD ;1P
Adder
13.632
274697ROCKY RD ;3P
Adder
3.74
958481AF2-142 GEN
Solar/Wind Harmer
12.927
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
1.166
274683WAUKEGAN ;8U
Adder
26.009
274683WAUKEGAN ;8U
Adder
21.925
962691AG1-118 GEN
Solar/Wind Harmer
25.779
970921AG2-575 GEN
Solar/Wind Harmer
8.581
970921AG2-575 GEN
Solar/Wind Harmer
2.86
958491AF2-143 GEN
Solar/Wind Harmer
12.84
970611AG2-400 GEN
Solar/Wind Harmer
8.544
970627AG2-408 GEN
Solar/Wind Harmer
2.563
942991AE2-321 GEN
Solar/Wind Harmer
9.539
274879MINONK ;1U
Solar/Wind Harmer
0.36
971333AH1-146 GEN
Solar/Wind Harmer
17.035
971335AH1-147 GEN
Solar/Wind Harmer
17.035
971341AH1-150 GEN
Solar/Wind Harmer
16.979
971343AH1-151 GEN
Solar/Wind Harmer
16.979
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
274856ECOGROVE ;U1
Solar/Wind Harmer
0.199
276611AD2-172 GEN
Solar/Wind Harmer
0.002
938861AE1-114 GEN
Solar/Wind Harmer
4.764
274764LEE CO EC;5U
Adder
11.213
274765LEE CO EC;6U
Adder
11.213
274762LEE CO EC;3U
Adder
11.187
274763LEE CO EC;4U
Adder
11.081
276603SUBLETTE C
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
972267AH1-718 GEN
Adder
4.979
276741O09 GEN1
Solar/Wind Harmer
0.297
276708O09 GEN2
Solar/Wind Harmer
0.297
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.327
276646AC1-214 GEN2
Solar/Wind Harmer
0.327
944541AF1-119 GEN
Solar/Wind Harmer
0.557
960971AF2-388 GEN
Solar/Wind Harmer
4.876
276782AC1-033 GEN
Solar/Wind Harmer
0.001
960611AF2-352 GEN
Solar/Wind Harmer
2.724
966841AG1-555 GEN
Solar/Wind Harmer
0.919
942221AE2-234 GEN
Solar/Wind Harmer
0.04
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
970241AG2-163 GEN
Solar/Wind Harmer
4.592
270599AE1-208 GEN
Solar/Wind Harmer
7.039
270031AE2-169
Solar/Wind Harmer
4.223
276916AD2-100_GEN
Solar/Wind Harmer
16.09
276911AD2-131_GEN
Solar/Wind Harmer
1.06
971613AH1-306 GEN
Solar/Wind Harmer
3.675
945391AF1-204 GEN
Solar/Wind Harmer
7.93
960441AF2-335 GEN
Solar/Wind Harmer
7.358
970239AG2-162 GEN
Solar/Wind Harmer
1.646
24722005FLATG5
50/50
1.795
24721905FLATG4
50/50
32.905
970153AG2-106 GEN
Solar/Wind Harmer
51.584
970513AG2-328 GEN
Solar/Wind Harmer
4.074
970517AG2-330 GEN
Solar/Wind Harmer
24.444
970349AG2-230 GEN
Solar/Wind Harmer
14.036
270043AE2-236 GEN
Solar/Wind Harmer
5.854
274772LINCOLN ;3U
Adder
10.782
247643Z2-116 C
Solar/Wind Harmer
0
24642205MAYFLWER
Adder
0.804
274724RIVER EC ;11
Adder
22.4
970707AG2-453 GEN
Solar/Wind Harmer
28.77
274752CRETE EC ;2U
Adder
10.401
274753CRETE EC ;3U
Adder
10.401
944531AF1-118 GEN
Solar/Wind Harmer
39.427
274826FISK ;BP
Adder
13.763
274802UNIV PARK;5U
Adder
7.329
276806AD2-047 C O1
Solar/Wind Harmer
4.97
970941AG2-585 GEN
Solar/Wind Harmer
10.962
972228AH1-698 GEN2
Adder
4.656
274800UNIV PARK;3U
Adder
7.326
972038AH1-567 GEN2
Adder
0.459
945111AF1-176 GEN
Solar/Wind Harmer
7.104
276897AD1-100 C
Solar/Wind Harmer
0.012
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
274676JOLIET 29;8U
Adder
37.026
274729ELWOOD EC;1P
Adder
20.542
274730ELWOOD EC;6P
Adder
20.542
274734ELWOOD EC;8P
Adder
20.542
274736ELWOOD EC;9P
Adder
20.542
276893AG1-478 C
Solar/Wind Harmer
0.345
970031AG2-029 GEN
Solar/Wind Harmer
5.657
943121AE2-341 GEN
Solar/Wind Harmer
14.583
943591AF1-030 GEN
Solar/Wind Harmer
9.698
270535AF1-215 GEN1
Solar/Wind Harmer
0.011
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
22.199
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274872LEEDK;1U
Solar/Wind Harmer
0.314
276805AD2-038 GEN
Solar/Wind Harmer
0.003
959331AF2-224 GEN
Solar/Wind Harmer
5.981
965021AG1-366 GEN
Solar/Wind Harmer
2.848
24441205WTRV SLR C
Solar/Wind Harmer
0
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
0.909
274855GSG-6 ;RU
Solar/Wind Harmer
0.313
274850MENDOTA H;RU
Solar/Wind Harmer
0.1
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.153
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
959091AF2-200 GEN
Solar/Wind Harmer
16.979
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
2.658
247604X1-042
Adder
0.505
970571AG2-364 GEN
Solar/Wind Harmer
16.847
274858EASY ROAD;U2
Solar/Wind Harmer
0.002
274760LEE CO EC;1U
Adder
11.187
274767LEE CO EC;8U
Adder
11.055
276157O29GEN1
Solar/Wind Harmer
1.347
274878BISHOP HL;2U
Solar/Wind Harmer
0.279
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
8.289
942111AE2-223 GEN
Solar/Wind Harmer
2.682
965931AG1-462 GEN
Solar/Wind Harmer
20.855
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
965091AG1-374 GEN
Solar/Wind Harmer
24.514
959611AF2-252 GEN
Solar/Wind Harmer
2.724
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
3.657
276668AB2-070 GEN1
Solar/Wind Harmer
0.289
247642Z2-115 C
Solar/Wind Harmer
0.003
276621W2-048 GEN
Solar/Wind Harmer
0.395
276838X2-022 GEN2
Solar/Wind Harmer
0.442
970289AG2-191 GEN
Solar/Wind Harmer
0.855
970291AG2-192 GEN
Solar/Wind Harmer
0.777
942481AE2-261 GEN
Solar/Wind Harmer
23.013
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.049
970193AG2-126 GEN
Solar/Wind Harmer
11.195
958821AF2-173 GEN
Solar/Wind Harmer
10.43
270004AE1-209 GEN
Solar/Wind Harmer
1.614
971617AH1-308 GEN
Solar/Wind Harmer
6.153
970243AG2-164 GEN
Solar/Wind Harmer
3.851
970519AG2-331 GEN
Solar/Wind Harmer
17.115
970699AG2-449 GEN
Solar/Wind Harmer
1.646
24721805FLATG3
50/50
1.795
24721705FLATG2
50/50
32.905
24344105CKG2
50/50
10.4
962761AG1-125 GEN
Solar/Wind Harmer
80.781
970149AG2-104 GEN
Solar/Wind Harmer
87.246
970155AG2-107 GEN
Solar/Wind Harmer
51.584
970245AG2-165 GEN
Solar/Wind Harmer
4.074
274773LINCOLN ;4U
Adder
10.782
274774LINCOLN ;5U
Adder
10.782
274723RIVER EC ;12
Adder
22.661
24639705ELKHART HY
Adder
0.194
276164X3-005 C
Solar/Wind Harmer
0
274751CRETE EC ;1U
Adder
10.401
274754CRETE EC ;4U
Adder
10.401
270505AE1-170 C O1
Solar/Wind Harmer
9.235
274812UNIV PK N;8U
Adder
6.308
276776AD2-060 GEN
Solar/Wind Harmer
0.916
274801UNIV PARK;4U
Adder
7.326
945111AF1-176 GEN
Solar/Wind Harmer
15.639
270063AE2-323 C
Solar/Wind Harmer
0.007
941551AE2-152 GEN
Solar/Wind Harmer
0.001
970373AG2-245 GEN
Solar/Wind Harmer
18.378
274676JOLIET 29;8U
Adder
38.397
274674JOLIET 9 ;6U
Adder
19.252
274732ELWOOD EC;7P
Adder
20.542
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
4.544
274745AC1-111 GEN9
Adder
6.959
270055AF2-134 C O1
Solar/Wind Harmer
0.007
276691AA1-018 GEN1
Solar/Wind Harmer
1.044
274682WAUKEGAN ;7U
Adder
22.199
274828WAUKEGAN ;BP
Adder
13.634
958381AF2-132 GEN
Solar/Wind Harmer
0.001
962781AG1-127 GEN
Solar/Wind Harmer
8.166
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
11.147
939401AE1-172 GEN
Solar/Wind Harmer
6.413
274872LEEDK;1U
Solar/Wind Harmer
0.005
276901AD2-066 C O1
Solar/Wind Harmer
0.008
965011AG1-365 GEN
Solar/Wind Harmer
8.544
971997AH1-543 GEN
Solar/Wind Harmer
4.478
276861AD2-134 GEN
Solar/Wind Harmer
0.153
957471AF2-041 GEN
Solar/Wind Harmer
25.469
959081AF2-199 GEN
Solar/Wind Harmer
8.49
971067AG2-660 GEN
Solar/Wind Harmer
2.83
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
10.593
274822ROCKFORD ;11
Adder
23.833
972235AH1-702 GEN1
Adder
3.057
970819AG2-516 GEN
Solar/Wind Harmer
10.134
971475AH1-234 GEN
Solar/Wind Harmer
4.092
970569AG2-363 GEN
Solar/Wind Harmer
25.271
274857EASY ROAD;U1
Solar/Wind Harmer
0.002
274761LEE CO EC;2U
Adder
11.187
274766LEE CO EC;7U
Adder
11.055
276158O29GEN2
Solar/Wind Harmer
0.001
965651AG1-433 GEN
Solar/Wind Harmer
2.438
274877BISHOP HL;1U
Solar/Wind Harmer
0.279
24791305MDL-5G
Solar/Wind Harmer
0.001
276726Z2-087_GEN
Solar/Wind Harmer
0.003
939741AE1-205 GEN
Solar/Wind Harmer
11.552
958861AF2-177 GEN
Solar/Wind Harmer
3.551
274854TWINGROVE;U2
Solar/Wind Harmer
0.003
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
972175AH1-670 GEN
Solar/Wind Harmer
6.643
945371AF1-202 GEN
Solar/Wind Harmer
0.001
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
3.078
963741AG1-226 GEN
Solar/Wind Harmer
18.629
276615X2-022 GEN
Solar/Wind Harmer
0.082
970291AG2-192 GEN
Solar/Wind Harmer
1.01
965911AG1-460 GEN
Solar/Wind Harmer
1.539
270032AE2-172
Solar/Wind Harmer
5.104
247521TR3_G114
Solar/Wind Harmer
0.277
270246TR4_N_V150
Solar/Wind Harmer
0.049
944231AF1-091 GEN
Solar/Wind Harmer
2.021
276903AD2-071 C
Solar/Wind Harmer
8.405
270005AE1-210 C O1
Solar/Wind Harmer
1.614
965031AG1-367 GEN
Solar/Wind Harmer
7.45
24695305TIMB G C
Solar/Wind Harmer
0.002
970333AG2-219 GEN
Solar/Wind Harmer
4.707
944201AF1-088_MTX
Adder
118.46
957141AF2-008_MTX
Adder
32.732
NYPJM->LTFIMP_NY
CLTF
3.756
LGEELTFEXP_LGEE->PJM
CLTF
5.526
WECLTFEXP_WEC->PJM
CLTF
4.63
AG2-052LTFEXP_AG2-052->PJM
LTF
0.285
AH1-155LTFEXP_AH1-155->PJM
LTF
0.428
LAGNLTFEXP_LAGN->PJM
CLTF
16.296
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.027
TVALTFEXP_TVA->PJM
CLTF
7.706
CBM West 1LTFEXP_CBM-W1->PJM
CBM
146.812
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.167
MECLTFEXP_MEC->PJM
CLTF
18.496
SIGELTFEXP_SIGE->PJM
CLTF
0.474
CPLELTFEXP_CPLE->PJM
CLTF
3.24
CBM West 2LTFEXP_CBM-W2->PJM
CBM
120.262

Details for 05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line l/o AEP_P1-2_#706_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#706_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.43 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5322.01
MW Contribution:3.93
Bus #Bus NameTypeMW Contribution
970615AG2-402 GEN
50/50
3.512
247620Y3-023
50/50
0.722
270102X2-052 ST
50/50
2.354
270100X2-052 CT1
50/50
2.169
270101X2-052 CT2
50/50
2.169
270471AD2-092_GEN
Solar/Wind Harmer
0.009
970611AG2-400 GEN
Solar/Wind Harmer
10.537
970627AG2-408 GEN
Solar/Wind Harmer
3.161
970321AG2-212 GEN
Solar/Wind Harmer
4.559
270216AD2-079_GEN
Solar/Wind Harmer
0.002
957891AF2-083 GEN
Solar/Wind Harmer
0.001
270526AF1-158 GEN
Solar/Wind Harmer
0.013
24441505OLIV SLR
Solar/Wind Harmer
0
961051AF2-396 GEN
Solar/Wind Harmer
20.46
961051AF2-396 GEN
Solar/Wind Harmer
13.64
965681AG1-436 GEN
Solar/Wind Harmer
12.752
965791AG1-447 GEN
Solar/Wind Harmer
9.351
274770LINCOLN ;1U
Adder
11.972
274771LINCOLN ;2U
Adder
11.972
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
274808UNIV PK N;4U
Adder
6.965
274803UNIV PARK;6U
Adder
8.1
274888KELLY CRK;1U
Solar/Wind Harmer
0.568
274887GEN-1.85
Solar/Wind Harmer
0.255
276843GEN-1.7
Solar/Wind Harmer
0.313
958011AF2-095 GEN
Solar/Wind Harmer
13.939
972259AH1-714 GEN
Adder
26.463
274674JOLIET 9 ;6U
Adder
21.154
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
971573AH1-285 GEN
Solar/Wind Harmer
1.764
958481AF2-142 GEN
Solar/Wind Harmer
14.096
274695ROCKY RD ;2P
Adder
14.996
274693ROCKY RD ;1P
Adder
14.848
274697ROCKY RD ;3P
Adder
4.074
274696ROCKY RD ;4P
Adder
15.349
274861TOP CROP ;1U
Solar/Wind Harmer
0.003
274862TOP CROP ;2U
Solar/Wind Harmer
1.271
944541AF1-119 GEN
Solar/Wind Harmer
0.629
960971AF2-388 GEN
Solar/Wind Harmer
5.509
274683WAUKEGAN ;8U
Adder
28.303
274683WAUKEGAN ;8U
Adder
23.858
246938BC-WTG3
Solar/Wind Harmer
0.338
246937BC-WTG2
Solar/Wind Harmer
0.379
962691AG1-118 GEN
Solar/Wind Harmer
27.992
970921AG2-575 GEN
Solar/Wind Harmer
9.308
970921AG2-575 GEN
Solar/Wind Harmer
3.103
958491AF2-143 GEN
Solar/Wind Harmer
13.931
274879MINONK ;1U
Solar/Wind Harmer
0.39
942991AE2-321 GEN
Solar/Wind Harmer
10.32
971333AH1-146 GEN
Solar/Wind Harmer
18.389
971335AH1-147 GEN
Solar/Wind Harmer
18.389
971341AH1-150 GEN
Solar/Wind Harmer
18.285
971343AH1-151 GEN
Solar/Wind Harmer
18.285
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
942221AE2-234 GEN
Solar/Wind Harmer
0.046
274856ECOGROVE ;U1
Solar/Wind Harmer
0.213
276611AD2-172 GEN
Solar/Wind Harmer
0.002
938861AE1-114 GEN
Solar/Wind Harmer
5.096
24721605FLATG1
50/50
5.145
971599AH1-298 GEN
50/50
14.587
270144AC1-141 ST1_
50/50
3.152
24653605MOTTVILLE
50/50
0.006
24643105BUCHANAN
50/50
0.019
962771AG1-126 GEN
Solar/Wind Harmer
120.047
270284AF1-227 GEN1
Solar/Wind Harmer
0.014
270286AF1-227 GEN2
Solar/Wind Harmer
0.006
270287AF1-227 GEN3
Solar/Wind Harmer
0.006
971347AH1-153 GEN
Solar/Wind Harmer
16.236
270071AF1-092 GEN
Solar/Wind Harmer
20.132
971771AH1-392 GEN
Solar/Wind Harmer
10.346
971619AH1-309 GEN
Solar/Wind Harmer
4.631
971769AH1-391 GEN
Solar/Wind Harmer
11.424
960681AF2-359 GEN
Solar/Wind Harmer
-0.002
24729505KEY G4
Adder
9.267
274775LINCOLN ;6U
Adder
11.972
274776LINCOLN ;7U
Adder
11.972
274777LINCOLN ;8U
Adder
11.972
965041AG1-368 GEN
Solar/Wind Harmer
9.847
270578AF1-285 GEN2
Solar/Wind Harmer
0.651
274814UNIV PK N;0U
Adder
7.057
274807UNIV PK N;3U
Adder
7.042
274805UNIV PK N;1U
Adder
7.011
274811UNIV PK N;7U
Adder
6.996
972037AH1-567 GEN1
Adder
0.254
274827FISK ;RP
Adder
10.776
960591AF2-350 GEN
Solar/Wind Harmer
9.68
972227AH1-698 GEN1
Adder
3.616
965051AG1-369 GEN
Solar/Wind Harmer
4.807
274687WILL CNTY;4U
Adder
38.503
274687WILL CNTY;4U
Adder
38.503
274675JOLIET 29;7U
Adder
42.223
274675JOLIET 29;7U
Adder
40.715
274728ELWOOD EC;5P
Adder
22.567
274731ELWOOD EC;2P
Adder
22.566
274733ELWOOD EC;3P
Adder
22.566
274735ELWOOD EC;4P
Adder
22.566
270536AF1-215 GEN2
Solar/Wind Harmer
0.012
970833AG2-524 GEN
Solar/Wind Harmer
10.52
970833AG2-524 GEN
Solar/Wind Harmer
7.013
971549AH1-272 GEN
Solar/Wind Harmer
19.681
274746AC1-111 G10
Adder
7.614
274744AC1-111 GEN8
Adder
7.614
963791AG1-232 GEN
Solar/Wind Harmer
12.76
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
1.183
270302AB2-170 GEN
Solar/Wind Harmer
0.006
270317AD1-130_GEN
Solar/Wind Harmer
0.013
971653AH1-327 GEN
Solar/Wind Harmer
1.314
958391AF2-133 GEN
Solar/Wind Harmer
0.001
276868AE1-113 GEN
Solar/Wind Harmer
1.855
276882AE2-255 GEN
Solar/Wind Harmer
1.081
971177AH1-047 GEN
Solar/Wind Harmer
5.697
965101AG1-375 GEN
Solar/Wind Harmer
9.202
971411AH1-196 GEN
Solar/Wind Harmer
13.802
971675AH1-338 GEN
Solar/Wind Harmer
3.588
274863CRW1-WTG
Solar/Wind Harmer
0.003
274864CRW2-WTG
Solar/Wind Harmer
0.003
971611AH1-305 GEN
Solar/Wind Harmer
5.454
971171AH1-044 GEN
Solar/Wind Harmer
18.285
274823ROCKFORD ;21
Adder
25.447
276612AE2-035 GEN
Solar/Wind Harmer
0.002
926823AC1-168 GEN
Solar/Wind Harmer
1.535
970169AG2-114 GEN
Solar/Wind Harmer
9.023
971681AH1-341 GEN
Solar/Wind Harmer
14.483
247607V1-011 GEN
Solar/Wind Harmer
0.001
961011AF2-392 GEN
Solar/Wind Harmer
5.219
945581AF1-223 GEN
Solar/Wind Harmer
0.001
957751AF2-069 GEN
Solar/Wind Harmer
0.292
24690905MDL-1G C
Solar/Wind Harmer
0.003
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0.002
276655WTG1_EQ
Solar/Wind Harmer
0.003
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
9.145
941731AE2-173 GEN
Solar/Wind Harmer
7.258
946321AF1-296 GEN
Solar/Wind Harmer
4.827
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
270024AE2-089 GEN
Solar/Wind Harmer
0.009
971609AH1-304 GEN
Solar/Wind Harmer
1.375
970289AG2-191 GEN
Solar/Wind Harmer
1.578
963841AG1-237 GEN
Solar/Wind Harmer
3.575
270594AE1-207 GEN
Solar/Wind Harmer
9.172
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.295
276848AB2-070 GEN3
Solar/Wind Harmer
0.294
970115AG2-085 GEN
Solar/Wind Harmer
3.159
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
270297AD1-101 GEN
Solar/Wind Harmer
0.002
274764LEE CO EC;5U
Adder
11.975
274765LEE CO EC;6U
Adder
11.975
274762LEE CO EC;3U
Adder
11.947
274763LEE CO EC;4U
Adder
11.834
276603SUBLETTE C
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
270007AE1-245 C
Solar/Wind Harmer
0.002
972267AH1-718 GEN
Adder
5.295
276741O09 GEN1
Solar/Wind Harmer
0.315
276708O09 GEN2
Solar/Wind Harmer
0.315
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.347
276646AC1-214 GEN2
Solar/Wind Harmer
0.347
970623AG2-406 GEN
Solar/Wind Harmer
1.614
276782AC1-033 GEN
Solar/Wind Harmer
0.001
960611AF2-352 GEN
Solar/Wind Harmer
2.854
966841AG1-555 GEN
Solar/Wind Harmer
0.959
270599AE1-208 GEN
Solar/Wind Harmer
7.715
270031AE2-169
Solar/Wind Harmer
4.629
971613AH1-306 GEN
Solar/Wind Harmer
3.931
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
970241AG2-163 GEN
Solar/Wind Harmer
4.69
960441AF2-335 GEN
Solar/Wind Harmer
7.897
970825AG2-519 GEN
Solar/Wind Harmer
8.719
964611AG1-324 GEN
Solar/Wind Harmer
0.584
270201AC2-176 GEN
Solar/Wind Harmer
0.001
970621AG2-405 GEN
Solar/Wind Harmer
1.413
247621Y3-024
Adder
0.262
276916AD2-100_GEN
Solar/Wind Harmer
13.41
276911AD2-131_GEN
Solar/Wind Harmer
0.883
24721805FLATG3
50/50
5.145
24721705FLATG2
50/50
94.33
24344105CKG2
50/50
12.069
270143AC1-141 CT2_
50/50
3.558
24639705ELKHART HY
50/50
0.241
970521AG2-332 GEN
50/50
17.184
24307105BERRINSP G
50/50
0.032
962761AG1-125 GEN
Solar/Wind Harmer
120.047
970149AG2-104 GEN
Solar/Wind Harmer
129.655
970155AG2-107 GEN
Solar/Wind Harmer
76.659
270349AD2-093_GEN
Solar/Wind Harmer
0.009
965011AG1-365 GEN
Solar/Wind Harmer
10.537
970245AG2-165 GEN
Solar/Wind Harmer
4.559
270063AE2-323 C
Solar/Wind Harmer
0.008
270505AE1-170 C O1
Solar/Wind Harmer
10.806
945111AF1-176 GEN
Solar/Wind Harmer
18.321
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
5.329
274773LINCOLN ;4U
Adder
11.972
274774LINCOLN ;5U
Adder
11.972
274723RIVER EC ;12
Adder
25.205
274751CRETE EC ;1U
Adder
11.58
274754CRETE EC ;4U
Adder
11.58
270223U2-072_GEN1
Solar/Wind Harmer
0.001
276164X3-005 C
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
20.506
274812UNIV PK N;8U
Adder
6.996
274801UNIV PARK;4U
Adder
8.089
276776AD2-060 GEN
Solar/Wind Harmer
1.011
247521TR3_G114
Solar/Wind Harmer
0.351
270246TR4_N_V150
Solar/Wind Harmer
0.062
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
42.222
274674JOLIET 9 ;6U
Adder
21.154
274732ELWOOD EC;7P
Adder
22.567
270055AF2-134 C O1
Solar/Wind Harmer
0.007
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
274745AC1-111 GEN9
Adder
7.614
944231AF1-091 GEN
Solar/Wind Harmer
2.532
24695305TIMB G C
Solar/Wind Harmer
0.002
965421AG1-410 GEN
Solar/Wind Harmer
28.36
958381AF2-132 GEN
Solar/Wind Harmer
0.001
276691AA1-018 GEN1
Solar/Wind Harmer
1.138
965651AG1-433 GEN
Solar/Wind Harmer
2.755
274682WAUKEGAN ;7U
Adder
24.169
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
12.195
274828WAUKEGAN ;BP
Adder
14.836
246936BC-WTG1
Solar/Wind Harmer
0.379
270489AE1-102 GEN1
Solar/Wind Harmer
1.214
270462AD2-086
Solar/Wind Harmer
0.02
962781AG1-127 GEN
Solar/Wind Harmer
8.858
939401AE1-172 GEN
Solar/Wind Harmer
6.954
274872LEEDK;1U
Solar/Wind Harmer
0.006
276901AD2-066 C O1
Solar/Wind Harmer
0.009
971997AH1-543 GEN
Solar/Wind Harmer
4.843
958861AF2-177 GEN
Solar/Wind Harmer
3.987
276861AD2-134 GEN
Solar/Wind Harmer
0.165
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
11.452
957471AF2-041 GEN
Solar/Wind Harmer
27.428
959081AF2-199 GEN
Solar/Wind Harmer
9.143
971067AG2-660 GEN
Solar/Wind Harmer
3.048
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
274822ROCKFORD ;11
Adder
25.633
972235AH1-702 GEN1
Adder
3.284
970819AG2-516 GEN
Solar/Wind Harmer
10.874
971475AH1-234 GEN
Solar/Wind Harmer
4.385
970569AG2-363 GEN
Solar/Wind Harmer
27.095
274857EASY ROAD;U1
Solar/Wind Harmer
0.002
274761LEE CO EC;2U
Adder
11.947
274766LEE CO EC;7U
Adder
11.806
276158O29GEN2
Solar/Wind Harmer
0.001
945371AF1-202 GEN
Solar/Wind Harmer
0.001
274877BISHOP HL;1U
Solar/Wind Harmer
0.295
24791305MDL-5G
Solar/Wind Harmer
0.001
276726Z2-087_GEN
Solar/Wind Harmer
0.003
939741AE1-205 GEN
Solar/Wind Harmer
12.194
274854TWINGROVE;U2
Solar/Wind Harmer
0.004
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
972175AH1-670 GEN
Solar/Wind Harmer
6.873
970291AG2-192 GEN
Solar/Wind Harmer
1.08
270032AE2-172
Solar/Wind Harmer
5.46
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
3.14
963741AG1-226 GEN
Solar/Wind Harmer
19.026
270005AE1-210 C O1
Solar/Wind Harmer
1.733
965031AG1-367 GEN
Solar/Wind Harmer
8
276615X2-022 GEN
Solar/Wind Harmer
0.084
276903AD2-071 C
Solar/Wind Harmer
8.872
970825AG2-519 GEN
Solar/Wind Harmer
2.793
965911AG1-460 GEN
Solar/Wind Harmer
1.538
24728605AND G2
Adder
3.739
24722005FLATG5
50/50
5.145
24721905FLATG4
50/50
94.33
270475AD2-096_GEN
50/50
10.026
270142AC1-141 CT1_
50/50
3.558
24641605TWIN BRNCH
50/50
0.026
24344005CKG1
50/50
9.691
24642205MAYFLWER
50/50
0.992
944961AF1-161 GEN
50/50
4.253
962601AG1-109 GEN
50/50
4.253
247604X1-042
50/50
0.632
970153AG2-106 GEN
Solar/Wind Harmer
76.659
270043AE2-236 GEN
Solar/Wind Harmer
6.969
970349AG2-230 GEN
Solar/Wind Harmer
16.236
959331AF2-224 GEN
Solar/Wind Harmer
7.376
965021AG1-366 GEN
Solar/Wind Harmer
3.512
970513AG2-328 GEN
Solar/Wind Harmer
4.559
970517AG2-330 GEN
Solar/Wind Harmer
27.357
247643Z2-116 C
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
6.732
945111AF1-176 GEN
Solar/Wind Harmer
8.323
944531AF1-118 GEN
Solar/Wind Harmer
45.595
24441205WTRV SLR C
Solar/Wind Harmer
0
274772LINCOLN ;3U
Adder
11.972
274724RIVER EC ;11
Adder
24.913
274752CRETE EC ;2U
Adder
11.58
274753CRETE EC ;3U
Adder
11.58
270391AF1-285 GEN3
Solar/Wind Harmer
0.651
970707AG2-453 GEN
Solar/Wind Harmer
31.724
274802UNIV PARK;5U
Adder
8.1
274826FISK ;BP
Adder
15.205
274800UNIV PARK;3U
Adder
8.089
972038AH1-567 GEN2
Adder
0.506
276806AD2-047 C O1
Solar/Wind Harmer
5.485
970941AG2-585 GEN
Solar/Wind Harmer
12.1
972228AH1-698 GEN2
Adder
5.135
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.062
276897AD1-100 C
Solar/Wind Harmer
0.013
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
274676JOLIET 29;8U
Adder
40.714
274730ELWOOD EC;6P
Adder
22.567
274734ELWOOD EC;8P
Adder
22.567
274736ELWOOD EC;9P
Adder
22.567
274729ELWOOD EC;1P
Adder
22.566
276893AG1-478 C
Solar/Wind Harmer
0.379
270535AF1-215 GEN1
Solar/Wind Harmer
0.012
943121AE2-341 GEN
Solar/Wind Harmer
15.96
943591AF1-030 GEN
Solar/Wind Harmer
10.614
964401AG1-302 GEN
Solar/Wind Harmer
0.001
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
24.169
270491AE1-102 GEN2
Solar/Wind Harmer
1.214
270485AE1-090_GEN
Solar/Wind Harmer
0.001
276805AD2-038 GEN
Solar/Wind Harmer
0.003
274872LEEDK;1U
Solar/Wind Harmer
0.341
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
0.982
274855GSG-6 ;RU
Solar/Wind Harmer
0.337
274850MENDOTA H;RU
Solar/Wind Harmer
0.108
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.165
959091AF2-200 GEN
Solar/Wind Harmer
18.285
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
2.856
970571AG2-364 GEN
Solar/Wind Harmer
18.064
274858EASY ROAD;U2
Solar/Wind Harmer
0.002
274760LEE CO EC;1U
Adder
11.947
274767LEE CO EC;8U
Adder
11.806
276157O29GEN1
Solar/Wind Harmer
1.431
270258AD1-119 GEN
Solar/Wind Harmer
0.002
274878BISHOP HL;2U
Solar/Wind Harmer
0.295
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
8.785
270404AC1-167 GEN
Solar/Wind Harmer
0.004
942111AE2-223 GEN
Solar/Wind Harmer
2.831
965931AG1-462 GEN
Solar/Wind Harmer
21.861
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
965091AG1-374 GEN
Solar/Wind Harmer
25.685
959611AF2-252 GEN
Solar/Wind Harmer
2.854
971617AH1-308 GEN
Solar/Wind Harmer
7.03
247642Z2-115 C
Solar/Wind Harmer
0.004
970289AG2-191 GEN
Solar/Wind Harmer
0.914
970291AG2-192 GEN
Solar/Wind Harmer
0.831
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
3.74
276668AB2-070 GEN1
Solar/Wind Harmer
0.295
958821AF2-173 GEN
Solar/Wind Harmer
11.2
270004AE1-209 GEN
Solar/Wind Harmer
1.733
276621W2-048 GEN
Solar/Wind Harmer
0.401
276838X2-022 GEN2
Solar/Wind Harmer
0.448
946031AF1-268 GEN
Solar/Wind Harmer
7.422
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
11.672
942481AE2-261 GEN
Solar/Wind Harmer
22.986
24728705AND G3
Adder
7.82
24728505AND G1
Adder
3.739
944201AF1-088_MTX
Adder
85.667
NYPJM->LTFIMP_NY
CLTF
2.99
LGEELTFEXP_LGEE->PJM
CLTF
4.155
WECLTFEXP_WEC->PJM
CLTF
4.968
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.286
AG2-052LTFEXP_AG2-052->PJM
LTF
0.312
AH1-155LTFEXP_AH1-155->PJM
LTF
0.469
LAGNLTFEXP_LAGN->PJM
CLTF
11.144
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.328
TVALTFEXP_TVA->PJM
CLTF
4.56
CBM West 1LTFEXP_CBM-W1->PJM
CBM
161.402
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.132
MECLTFEXP_MEC->PJM
CLTF
18.394
SIGELTFEXP_SIGE->PJM
CLTF
0.399
CBM West 2LTFEXP_CBM-W2->PJM
CBM
96.989

Details for 05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.86 %
Rating:4047.0 MVA
Rating Type:A
MVA to Mitigate:4648.25
MW Contribution:2.94
Bus #Bus NameTypeMW Contribution
971599AH1-298 GEN
50/50
10.558
270144AC1-141 ST1_
50/50
2.306
24643105BUCHANAN
50/50
0.014
24653605MOTTVILLE
50/50
0.004
274775LINCOLN ;6U
50/50
9.593
274776LINCOLN ;7U
50/50
9.593
274777LINCOLN ;8U
50/50
9.593
962771AG1-126 GEN
Solar/Wind Harmer
74.603
971347AH1-153 GEN
Solar/Wind Harmer
12.013
270102X2-052 ST
50/50
1.747
270100X2-052 CT1
50/50
1.61
270101X2-052 CT2
50/50
1.61
247620Y3-023
50/50
0.525
274770LINCOLN ;1U
50/50
9.593
274771LINCOLN ;2U
50/50
9.593
970321AG2-212 GEN
Solar/Wind Harmer
3.44
270216AD2-079_GEN
Solar/Wind Harmer
0.001
965681AG1-436 GEN
Solar/Wind Harmer
9.481
965791AG1-447 GEN
Solar/Wind Harmer
6.953
270526AF1-158 GEN
Solar/Wind Harmer
0.009
24441505OLIV SLR
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
14.924
961051AF2-396 GEN
Solar/Wind Harmer
9.95
970611AG2-400 GEN
Solar/Wind Harmer
7.366
970627AG2-408 GEN
Solar/Wind Harmer
2.21
274808UNIV PK N;4U
Adder
5.255
972259AH1-714 GEN
Adder
20.044
274803UNIV PARK;6U
Adder
6.123
274888KELLY CRK;1U
Solar/Wind Harmer
0.43
274887GEN-1.85
Solar/Wind Harmer
0.193
276843GEN-1.7
Solar/Wind Harmer
0.237
958011AF2-095 GEN
Solar/Wind Harmer
10.545
274674JOLIET 9 ;6U
Adder
16.042
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
971573AH1-285 GEN
Solar/Wind Harmer
1.342
274695ROCKY RD ;2P
Adder
11.425
274693ROCKY RD ;1P
Adder
11.312
274697ROCKY RD ;3P
Adder
3.104
274696ROCKY RD ;4P
Adder
11.694
958481AF2-142 GEN
Solar/Wind Harmer
10.727
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.967
274683WAUKEGAN ;8U
Adder
21.572
274683WAUKEGAN ;8U
Adder
18.184
962691AG1-118 GEN
Solar/Wind Harmer
21.36
970921AG2-575 GEN
Solar/Wind Harmer
7.106
970921AG2-575 GEN
Solar/Wind Harmer
2.369
958491AF2-143 GEN
Solar/Wind Harmer
10.627
942991AE2-321 GEN
Solar/Wind Harmer
7.889
274879MINONK ;1U
Solar/Wind Harmer
0.298
971333AH1-146 GEN
Solar/Wind Harmer
14.073
971335AH1-147 GEN
Solar/Wind Harmer
14.073
971341AH1-150 GEN
Solar/Wind Harmer
14.009
971343AH1-151 GEN
Solar/Wind Harmer
14.009
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
274856ECOGROVE ;U1
Solar/Wind Harmer
0.164
276611AD2-172 GEN
Solar/Wind Harmer
0.002
938861AE1-114 GEN
Solar/Wind Harmer
3.917
274764LEE CO EC;5U
Adder
9.213
274765LEE CO EC;6U
Adder
9.213
274762LEE CO EC;3U
Adder
9.191
274763LEE CO EC;4U
Adder
9.105
276603SUBLETTE C
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.461
960971AF2-388 GEN
Solar/Wind Harmer
4.033
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
972267AH1-718 GEN
Adder
4.082
276741O09 GEN1
Solar/Wind Harmer
0.243
276708O09 GEN2
Solar/Wind Harmer
0.243
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.268
276646AC1-214 GEN2
Solar/Wind Harmer
0.268
276782AC1-033 GEN
Solar/Wind Harmer
0.001
960611AF2-352 GEN
Solar/Wind Harmer
2.211
942221AE2-234 GEN
Solar/Wind Harmer
0.033
966841AG1-555 GEN
Solar/Wind Harmer
0.741
270471AD2-092_GEN
Solar/Wind Harmer
0.005
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
970241AG2-163 GEN
Solar/Wind Harmer
3.657
270599AE1-208 GEN
Solar/Wind Harmer
5.676
270031AE2-169
Solar/Wind Harmer
3.406
971613AH1-306 GEN
Solar/Wind Harmer
2.938
276916AD2-100_GEN
Solar/Wind Harmer
12.71
276911AD2-131_GEN
Solar/Wind Harmer
0.837
246938BC-WTG3
Solar/Wind Harmer
0.219
246937BC-WTG2
Solar/Wind Harmer
0.245
24344105CKG2
50/50
8.939
270143AC1-141 CT2_
50/50
2.603
24639705ELKHART HY
50/50
0.176
970521AG2-332 GEN
50/50
12.519
274773LINCOLN ;4U
50/50
9.593
274774LINCOLN ;5U
50/50
9.593
962761AG1-125 GEN
Solar/Wind Harmer
74.603
970149AG2-104 GEN
Solar/Wind Harmer
80.573
970155AG2-107 GEN
Solar/Wind Harmer
47.639
970245AG2-165 GEN
Solar/Wind Harmer
3.44
270505AE1-170 C O1
Solar/Wind Harmer
7.896
270063AE2-323 C
Solar/Wind Harmer
0.006
945111AF1-176 GEN
Solar/Wind Harmer
13.37
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
3.886
274723RIVER EC ;12
Adder
18.99
274751CRETE EC ;1U
Adder
8.717
274754CRETE EC ;4U
Adder
8.717
276164X3-005 C
Solar/Wind Harmer
0
965011AG1-365 GEN
Solar/Wind Harmer
7.366
274812UNIV PK N;8U
Adder
5.278
970373AG2-245 GEN
Solar/Wind Harmer
15.386
276776AD2-060 GEN
Solar/Wind Harmer
0.765
274801UNIV PARK;4U
Adder
6.118
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
32.008
274674JOLIET 9 ;6U
Adder
16.042
274732ELWOOD EC;7P
Adder
17.114
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
274745AC1-111 GEN9
Adder
5.788
270055AF2-134 C O1
Solar/Wind Harmer
0.006
276691AA1-018 GEN1
Solar/Wind Harmer
0.866
274682WAUKEGAN ;7U
Adder
18.416
274828WAUKEGAN ;BP
Adder
11.308
958381AF2-132 GEN
Solar/Wind Harmer
0.001
962781AG1-127 GEN
Solar/Wind Harmer
6.763
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.233
274872LEEDK;1U
Solar/Wind Harmer
0.004
939401AE1-172 GEN
Solar/Wind Harmer
5.304
276901AD2-066 C O1
Solar/Wind Harmer
0.007
971997AH1-543 GEN
Solar/Wind Harmer
3.701
276861AD2-134 GEN
Solar/Wind Harmer
0.126
957471AF2-041 GEN
Solar/Wind Harmer
21.014
959081AF2-199 GEN
Solar/Wind Harmer
7.005
971067AG2-660 GEN
Solar/Wind Harmer
2.335
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
274822ROCKFORD ;11
Adder
19.652
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.717
972235AH1-702 GEN1
Adder
2.519
970819AG2-516 GEN
Solar/Wind Harmer
8.346
971475AH1-234 GEN
Solar/Wind Harmer
3.368
970569AG2-363 GEN
Solar/Wind Harmer
20.788
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
9.191
274766LEE CO EC;7U
Adder
9.083
965651AG1-433 GEN
Solar/Wind Harmer
2.017
276158O29GEN2
Solar/Wind Harmer
0.001
274877BISHOP HL;1U
Solar/Wind Harmer
0.228
24721705FLATG2
Adder
19.64
24791305MDL-5G
Solar/Wind Harmer
0.001
958861AF2-177 GEN
Solar/Wind Harmer
2.923
276726Z2-087_GEN
Solar/Wind Harmer
0.002
939741AE1-205 GEN
Solar/Wind Harmer
9.413
274854TWINGROVE;U2
Solar/Wind Harmer
0.003
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.002
944231AF1-091 GEN
Solar/Wind Harmer
1.739
945371AF1-202 GEN
Solar/Wind Harmer
0.001
247521TR3_G114
Solar/Wind Harmer
0.237
270246TR4_N_V150
Solar/Wind Harmer
0.042
972175AH1-670 GEN
Solar/Wind Harmer
5.355
270349AD2-093_GEN
Solar/Wind Harmer
0.005
24695305TIMB G C
Solar/Wind Harmer
0.002
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
2.462
963741AG1-226 GEN
Solar/Wind Harmer
14.839
276615X2-022 GEN
Solar/Wind Harmer
0.066
970291AG2-192 GEN
Solar/Wind Harmer
0.81
965421AG1-410 GEN
Solar/Wind Harmer
18.496
270032AE2-172
Solar/Wind Harmer
4.081
965911AG1-460 GEN
Solar/Wind Harmer
1.218
246936BC-WTG1
Solar/Wind Harmer
0.245
270489AE1-102 GEN1
Solar/Wind Harmer
0.785
270071AF1-092 GEN
Solar/Wind Harmer
14.717
971771AH1-392 GEN
Solar/Wind Harmer
7.604
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971769AH1-391 GEN
Solar/Wind Harmer
8.444
971619AH1-309 GEN
Solar/Wind Harmer
3.384
274814UNIV PK N;0U
Adder
5.324
274807UNIV PK N;3U
Adder
5.313
274805UNIV PK N;1U
Adder
5.29
274811UNIV PK N;7U
Adder
5.278
274827FISK ;RP
Adder
8.149
972037AH1-567 GEN1
Adder
0.192
960591AF2-350 GEN
Solar/Wind Harmer
7.323
972227AH1-698 GEN1
Adder
2.737
274687WILL CNTY;4U
Adder
29.176
274687WILL CNTY;4U
Adder
29.176
274675JOLIET 29;7U
Adder
32.008
274675JOLIET 29;7U
Adder
30.865
24729505KEY G4
Adder
6.759
274731ELWOOD EC;2P
Adder
17.114
274733ELWOOD EC;3P
Adder
17.114
274735ELWOOD EC;4P
Adder
17.114
274728ELWOOD EC;5P
Adder
17.114
970833AG2-524 GEN
Solar/Wind Harmer
7.985
970833AG2-524 GEN
Solar/Wind Harmer
5.323
274746AC1-111 G10
Adder
5.788
274744AC1-111 GEN8
Adder
5.788
270536AF1-215 GEN2
Solar/Wind Harmer
0.009
971177AH1-047 GEN
Solar/Wind Harmer
4.355
958391AF2-133 GEN
Solar/Wind Harmer
0.001
276868AE1-113 GEN
Solar/Wind Harmer
1.417
276882AE2-255 GEN
Solar/Wind Harmer
0.825
971675AH1-338 GEN
Solar/Wind Harmer
2.746
971411AH1-196 GEN
Solar/Wind Harmer
10.56
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
971171AH1-044 GEN
Solar/Wind Harmer
14.009
274823ROCKFORD ;21
Adder
19.51
971611AH1-305 GEN
Solar/Wind Harmer
4.152
276612AE2-035 GEN
Solar/Wind Harmer
0.002
926823AC1-168 GEN
Solar/Wind Harmer
1.178
970169AG2-114 GEN
Solar/Wind Harmer
6.92
971681AH1-341 GEN
Solar/Wind Harmer
11.133
961011AF2-392 GEN
Solar/Wind Harmer
4.021
957751AF2-069 GEN
Solar/Wind Harmer
0.225
971549AH1-272 GEN
Solar/Wind Harmer
14.034
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
965101AG1-375 GEN
Solar/Wind Harmer
6.746
965041AG1-368 GEN
Solar/Wind Harmer
6.733
276655WTG1_EQ
Solar/Wind Harmer
0.003
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.06
941731AE2-173 GEN
Solar/Wind Harmer
5.603
946321AF1-296 GEN
Solar/Wind Harmer
3.744
963791AG1-232 GEN
Solar/Wind Harmer
8.989
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
945581AF1-223 GEN
Solar/Wind Harmer
0
965051AG1-369 GEN
Solar/Wind Harmer
3.241
963841AG1-237 GEN
Solar/Wind Harmer
2.776
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.231
276848AB2-070 GEN3
Solar/Wind Harmer
0.23
970289AG2-191 GEN
Solar/Wind Harmer
1.184
971609AH1-304 GEN
Solar/Wind Harmer
1.011
270594AE1-207 GEN
Solar/Wind Harmer
6.856
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.765
270284AF1-227 GEN1
Solar/Wind Harmer
0.008
270286AF1-227 GEN2
Solar/Wind Harmer
0.003
270287AF1-227 GEN3
Solar/Wind Harmer
0.003
270054AF2-122 C O1
Solar/Wind Helper
1.65
270142AC1-141 CT1_
50/50
2.603
24641605TWIN BRNCH
50/50
0.019
24344005CKG1
50/50
7.096
24642205MAYFLWER
50/50
0.728
274772LINCOLN ;3U
50/50
9.593
970153AG2-106 GEN
Solar/Wind Harmer
47.639
970349AG2-230 GEN
Solar/Wind Harmer
12.013
970513AG2-328 GEN
Solar/Wind Harmer
3.44
970517AG2-330 GEN
Solar/Wind Harmer
20.64
270043AE2-236 GEN
Solar/Wind Harmer
5.033
247643Z2-116 C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
6.073
970031AG2-029 GEN
Solar/Wind Harmer
4.844
944531AF1-118 GEN
Solar/Wind Harmer
33.218
274724RIVER EC ;11
Adder
18.771
274752CRETE EC ;2U
Adder
8.717
274753CRETE EC ;3U
Adder
8.717
959331AF2-224 GEN
Solar/Wind Harmer
5.157
965021AG1-366 GEN
Solar/Wind Harmer
2.455
970707AG2-453 GEN
Solar/Wind Harmer
24.03
274826FISK ;BP
Adder
11.498
274802UNIV PARK;5U
Adder
6.123
276806AD2-047 C O1
Solar/Wind Harmer
4.15
970941AG2-585 GEN
Solar/Wind Harmer
9.154
274800UNIV PARK;3U
Adder
6.118
972038AH1-567 GEN2
Adder
0.383
972228AH1-698 GEN2
Adder
3.887
24441205WTRV SLR C
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
0.01
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
274676JOLIET 29;8U
Adder
30.865
274729ELWOOD EC;1P
Adder
17.114
274730ELWOOD EC;6P
Adder
17.114
274734ELWOOD EC;8P
Adder
17.114
274736ELWOOD EC;9P
Adder
17.114
276893AG1-478 C
Solar/Wind Harmer
0.288
943121AE2-341 GEN
Solar/Wind Harmer
12.132
943591AF1-030 GEN
Solar/Wind Harmer
8.068
247604X1-042
Adder
0.432
270535AF1-215 GEN1
Solar/Wind Harmer
0.009
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
18.416
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274872LEEDK;1U
Solar/Wind Harmer
0.26
276805AD2-038 GEN
Solar/Wind Harmer
0.002
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.751
274855GSG-6 ;RU
Solar/Wind Harmer
0.258
274850MENDOTA H;RU
Solar/Wind Harmer
0.083
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.126
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
959091AF2-200 GEN
Solar/Wind Harmer
14.009
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
2.191
970571AG2-364 GEN
Solar/Wind Harmer
13.859
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
9.191
274767LEE CO EC;8U
Adder
9.083
276157O29GEN1
Solar/Wind Harmer
1.104
274878BISHOP HL;2U
Solar/Wind Harmer
0.228
24721905FLATG4
Adder
19.64
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.747
942111AE2-223 GEN
Solar/Wind Harmer
2.185
965931AG1-462 GEN
Solar/Wind Harmer
16.976
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
965091AG1-374 GEN
Solar/Wind Harmer
19.897
959611AF2-252 GEN
Solar/Wind Harmer
2.211
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.042
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
2.93
276668AB2-070 GEN1
Solar/Wind Harmer
0.231
247642Z2-115 C
Solar/Wind Harmer
0.003
276621W2-048 GEN
Solar/Wind Harmer
0.316
276838X2-022 GEN2
Solar/Wind Harmer
0.352
970289AG2-191 GEN
Solar/Wind Harmer
0.686
970291AG2-192 GEN
Solar/Wind Harmer
0.623
942481AE2-261 GEN
Solar/Wind Harmer
18.215
270491AE1-102 GEN2
Solar/Wind Harmer
0.785
NYPJM->LTFIMP_NY
CLTF
2.589
LGEELTFEXP_LGEE->PJM
CLTF
3.659
WECLTFEXP_WEC->PJM
CLTF
3.814
AG2-052LTFEXP_AG2-052->PJM
LTF
0.236
AH1-155LTFEXP_AH1-155->PJM
LTF
0.355
LAGNLTFEXP_LAGN->PJM
CLTF
11.239
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.669
TVALTFEXP_TVA->PJM
CLTF
5.062
CBM West 1LTFEXP_CBM-W1->PJM
CBM
120.019
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.189
MECLTFEXP_MEC->PJM
CLTF
14.69
SIGELTFEXP_SIGE->PJM
CLTF
0.339
CPLELTFEXP_CPLE->PJM
CLTF
1.429
CBM West 2LTFEXP_CBM-W2->PJM
CBM
87.023

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#709_546_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:145.65 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:6032.93
MW Contribution:5.33
Bus #Bus NameTypeMW Contribution
24344105CKG2
50/50
17.41
270143AC1-141 CT2_
50/50
4.979
24639705ELKHART HY
50/50
0.333
274773LINCOLN ;4U
50/50
18.26
274774LINCOLN ;5U
50/50
18.26
970521AG2-332 GEN
50/50
23.674
970245AG2-165 GEN
Solar/Wind Harmer
6.717
270505AE1-170 C O1
Solar/Wind Harmer
15.077
945111AF1-176 GEN
Solar/Wind Harmer
25.462
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
7.414
274723RIVER EC ;12
Adder
36.059
970373AG2-245 GEN
Solar/Wind Harmer
29.431
274751CRETE EC ;1U
Adder
16.552
274754CRETE EC ;4U
Adder
16.552
276164X3-005 C
Solar/Wind Harmer
0
270063AE2-323 C
Solar/Wind Harmer
0.011
274812UNIV PK N;8U
Adder
10.011
276776AD2-060 GEN
Solar/Wind Harmer
1.448
274801UNIV PARK;4U
Adder
11.588
941551AE2-152 GEN
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0.011
274676JOLIET 29;8U
Adder
60.512
274674JOLIET 9 ;6U
Adder
30.323
274732ELWOOD EC;7P
Adder
32.348
274871GR RIDGE ;2U
Solar/Wind Harmer
0.002
274745AC1-111 GEN9
Adder
10.916
958381AF2-132 GEN
Solar/Wind Harmer
0.002
964861AG1-349 GEN
Solar/Wind Harmer
-0.002
971917AH1-482 GEN
Solar/Wind Harmer
17.617
276691AA1-018 GEN1
Solar/Wind Harmer
1.631
274682WAUKEGAN ;7U
Adder
34.62
274828WAUKEGAN ;BP
Adder
21.25
939401AE1-172 GEN
Solar/Wind Harmer
9.985
962781AG1-127 GEN
Solar/Wind Harmer
12.689
274872LEEDK;1U
Solar/Wind Harmer
0.008
940581AE2-045 GEN
Solar/Wind Harmer
-0.003
971605AH1-302 GEN
Solar/Wind Harmer
16.609
276901AD2-066 C O1
Solar/Wind Harmer
0.013
971997AH1-543 GEN
Solar/Wind Harmer
6.942
276861AD2-134 GEN
Solar/Wind Harmer
0.236
957471AF2-041 GEN
Solar/Wind Harmer
39.258
959081AF2-199 GEN
Solar/Wind Harmer
13.086
971067AG2-660 GEN
Solar/Wind Harmer
4.362
276876AE1-163_GEN2
Solar/Wind Harmer
0.003
274822ROCKFORD ;11
Adder
36.677
972235AH1-702 GEN1
Adder
4.699
970819AG2-516 GEN
Solar/Wind Harmer
15.555
970569AG2-363 GEN
Solar/Wind Harmer
38.8
971475AH1-234 GEN
Solar/Wind Harmer
6.272
274857EASY ROAD;U1
Solar/Wind Harmer
0.003
274761LEE CO EC;2U
Adder
17.083
274766LEE CO EC;7U
Adder
16.882
24791305MDL-5G
Solar/Wind Harmer
0.002
965011AG1-365 GEN
Solar/Wind Harmer
12.726
276158O29GEN2
Solar/Wind Harmer
0.001
274877BISHOP HL;1U
Solar/Wind Harmer
0.423
965651AG1-433 GEN
Solar/Wind Harmer
3.688
276726Z2-087_GEN
Solar/Wind Harmer
0.004
939741AE1-205 GEN
Solar/Wind Harmer
17.52
24385905FR-11G C
Solar/Wind Harmer
0.003
24387305FR-4G C
Solar/Wind Harmer
0.005
274854TWINGROVE;U2
Solar/Wind Harmer
0.005
958861AF2-177 GEN
Solar/Wind Harmer
5.328
972175AH1-670 GEN
Solar/Wind Harmer
9.878
945371AF1-202 GEN
Solar/Wind Harmer
0.001
963741AG1-226 GEN
Solar/Wind Harmer
27.693
274880W4-005 GEN4
Solar/Wind Harmer
0.002
963831AG1-236 GEN
Solar/Wind Harmer
4.513
276615X2-022 GEN
Solar/Wind Harmer
0.12
944231AF1-091 GEN
Solar/Wind Harmer
3.041
970291AG2-192 GEN
Solar/Wind Harmer
1.481
270032AE2-172
Solar/Wind Harmer
7.401
965911AG1-460 GEN
Solar/Wind Harmer
2.209
276903AD2-071 C
Solar/Wind Harmer
12.04
970333AG2-219 GEN
Solar/Wind Harmer
7.687
270005AE1-210 C O1
Solar/Wind Harmer
2.283
965031AG1-367 GEN
Solar/Wind Harmer
10.536
970825AG2-519 GEN
Solar/Wind Harmer
3.643
247521TR3_G114
Solar/Wind Harmer
0.37
270246TR4_N_V150
Solar/Wind Harmer
0.066
24695305TIMB G C
Solar/Wind Harmer
0.003
270445AC2-157 GEN2
Solar/Wind Harmer
0.004
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0.001
970613AG2-401 GEN
Solar/Wind Harmer
7.029
247536S-71 GEN
Solar/Wind Harmer
0.355
965421AG1-410 GEN
Solar/Wind Harmer
25.459
970773AG2-487 GEN
Solar/Wind Harmer
1.469
246936BC-WTG1
Solar/Wind Harmer
0.326
270489AE1-102 GEN1
Solar/Wind Harmer
1.045
270349AD2-093_GEN
Solar/Wind Helper
1.548
270102X2-052 ST
50/50
3.353
270100X2-052 CT1
50/50
3.09
270101X2-052 CT2
50/50
3.09
274770LINCOLN ;1U
50/50
18.26
274771LINCOLN ;2U
50/50
18.26
970321AG2-212 GEN
Solar/Wind Harmer
6.717
965681AG1-436 GEN
Solar/Wind Harmer
18.169
965791AG1-447 GEN
Solar/Wind Harmer
13.324
270526AF1-158 GEN
Solar/Wind Harmer
0.018
24441505OLIV SLR
Solar/Wind Harmer
0
270216AD2-079_GEN
Solar/Wind Harmer
0.002
957891AF2-083 GEN
Solar/Wind Harmer
0.002
961051AF2-396 GEN
Solar/Wind Harmer
28.457
961051AF2-396 GEN
Solar/Wind Harmer
18.971
247620Y3-023
Adder
0.932
274808UNIV PK N;4U
Adder
9.967
972259AH1-714 GEN
Adder
37.97
274803UNIV PARK;6U
Adder
11.601
274888KELLY CRK;1U
Solar/Wind Harmer
0.815
274887GEN-1.85
Solar/Wind Harmer
0.365
276843GEN-1.7
Solar/Wind Harmer
0.449
958011AF2-095 GEN
Solar/Wind Harmer
19.978
274674JOLIET 9 ;6U
Adder
30.323
274847GR RIDGE ;BU
Solar/Wind Harmer
0.005
971573AH1-285 GEN
Solar/Wind Harmer
2.529
274695ROCKY RD ;2P
Adder
21.486
274693ROCKY RD ;1P
Adder
21.275
274697ROCKY RD ;3P
Adder
5.837
274696ROCKY RD ;4P
Adder
21.993
958481AF2-142 GEN
Solar/Wind Harmer
20.192
274861TOP CROP ;1U
Solar/Wind Harmer
0.004
274862TOP CROP ;2U
Solar/Wind Harmer
1.82
274683WAUKEGAN ;8U
Adder
40.539
274683WAUKEGAN ;8U
Adder
34.173
962691AG1-118 GEN
Solar/Wind Harmer
40.102
970921AG2-575 GEN
Solar/Wind Harmer
13.333
970921AG2-575 GEN
Solar/Wind Harmer
4.444
958491AF2-143 GEN
Solar/Wind Harmer
19.955
274879MINONK ;1U
Solar/Wind Harmer
0.559
942991AE2-321 GEN
Solar/Wind Harmer
14.775
971333AH1-146 GEN
Solar/Wind Harmer
26.325
971335AH1-147 GEN
Solar/Wind Harmer
26.325
971341AH1-150 GEN
Solar/Wind Harmer
26.172
971343AH1-151 GEN
Solar/Wind Harmer
26.172
276872AE1-163_GEN1
Solar/Wind Harmer
0.003
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.003
274856ECOGROVE ;U1
Solar/Wind Harmer
0.305
276611AD2-172 GEN
Solar/Wind Harmer
0.003
938861AE1-114 GEN
Solar/Wind Harmer
7.288
274764LEE CO EC;5U
Adder
17.123
274765LEE CO EC;6U
Adder
17.123
274762LEE CO EC;3U
Adder
17.083
274763LEE CO EC;4U
Adder
16.922
276603SUBLETTE C
Solar/Wind Harmer
0
970611AG2-400 GEN
Solar/Wind Harmer
12.726
970627AG2-408 GEN
Solar/Wind Harmer
3.818
972267AH1-718 GEN
Adder
7.569
276741O09 GEN1
Solar/Wind Harmer
0.451
276708O09 GEN2
Solar/Wind Harmer
0.451
274851PROVIDENC;RU
Solar/Wind Harmer
0.002
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.497
276646AC1-214 GEN2
Solar/Wind Harmer
0.497
276782AC1-033 GEN
Solar/Wind Harmer
0.002
944541AF1-119 GEN
Solar/Wind Harmer
0.842
960971AF2-388 GEN
Solar/Wind Harmer
7.376
966841AG1-555 GEN
Solar/Wind Harmer
1.399
960611AF2-352 GEN
Solar/Wind Harmer
4.101
970241AG2-163 GEN
Solar/Wind Harmer
6.826
942221AE2-234 GEN
Solar/Wind Harmer
0.059
276763AC1-053 GEN1
Solar/Wind Harmer
0.002
276764AC1-053 GEN2
Solar/Wind Harmer
0.002
971613AH1-306 GEN
Solar/Wind Harmer
5.329
270599AE1-208 GEN
Solar/Wind Harmer
10.158
270031AE2-169
Solar/Wind Harmer
6.095
276916AD2-100_GEN
Solar/Wind Harmer
23.006
276911AD2-131_GEN
Solar/Wind Harmer
1.515
970239AG2-162 GEN
Solar/Wind Harmer
2.688
945391AF1-204 GEN
Solar/Wind Harmer
11.282
960441AF2-335 GEN
Solar/Wind Harmer
10.327
970825AG2-519 GEN
Solar/Wind Harmer
11.373
270444AC2-157 GEN1
Solar/Wind Harmer
0.004
971587AH1-292 GEN
Solar/Wind Harmer
7.189
24379505HDWTR1G C
Solar/Wind Harmer
0.003
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
0.716
270201AC2-176 GEN
Solar/Wind Harmer
0.002
270383AD1-128 GEN
Solar/Wind Harmer
0.005
970623AG2-406 GEN
Solar/Wind Harmer
1.6
970883AG2-550 GEN
Solar/Wind Harmer
8.324
970885AG2-551 GEN
Solar/Wind Harmer
2.775
270007AE1-245 C
Solar/Wind Harmer
0.002
246938BC-WTG3
Solar/Wind Harmer
0.291
246937BC-WTG2
Solar/Wind Harmer
0.326
270471AD2-092_GEN
Solar/Wind Helper
1.548
971599AH1-298 GEN
50/50
19.983
270144AC1-141 ST1_
50/50
4.41
24643105BUCHANAN
50/50
0.026
274775LINCOLN ;6U
50/50
18.26
274776LINCOLN ;7U
50/50
18.26
274777LINCOLN ;8U
50/50
18.26
24653605MOTTVILLE
50/50
0.008
971347AH1-153 GEN
Solar/Wind Harmer
23.209
960681AF2-359 GEN
Solar/Wind Harmer
-0.002
971771AH1-392 GEN
Solar/Wind Harmer
14.529
971769AH1-391 GEN
Solar/Wind Harmer
16.154
971619AH1-309 GEN
Solar/Wind Harmer
6.462
270071AF1-092 GEN
Solar/Wind Harmer
27.514
274814UNIV PK N;0U
Adder
10.098
274807UNIV PK N;3U
Adder
10.076
274805UNIV PK N;1U
Adder
10.033
274811UNIV PK N;7U
Adder
10.011
972037AH1-567 GEN1
Adder
0.364
274827FISK ;RP
Adder
15.436
960591AF2-350 GEN
Solar/Wind Harmer
13.873
972227AH1-698 GEN1
Adder
5.185
270536AF1-215 GEN2
Solar/Wind Harmer
0.017
274687WILL CNTY;4U
Adder
55.173
274687WILL CNTY;4U
Adder
55.173
274675JOLIET 29;7U
Adder
60.513
274675JOLIET 29;7U
Adder
58.351
274731ELWOOD EC;2P
Adder
32.348
274733ELWOOD EC;3P
Adder
32.348
274735ELWOOD EC;4P
Adder
32.348
274728ELWOOD EC;5P
Adder
32.348
970833AG2-524 GEN
Solar/Wind Harmer
15.09
970833AG2-524 GEN
Solar/Wind Harmer
10.06
274746AC1-111 G10
Adder
10.916
274744AC1-111 GEN8
Adder
10.916
958391AF2-133 GEN
Solar/Wind Harmer
0.002
24729505KEY G4
Adder
12.474
971611AH1-305 GEN
Solar/Wind Harmer
7.91
276868AE1-113 GEN
Solar/Wind Harmer
2.657
276882AE2-255 GEN
Solar/Wind Harmer
1.548
971177AH1-047 GEN
Solar/Wind Harmer
8.156
971675AH1-338 GEN
Solar/Wind Harmer
5.138
971411AH1-196 GEN
Solar/Wind Harmer
19.757
274863CRW1-WTG
Solar/Wind Harmer
0.004
274864CRW2-WTG
Solar/Wind Harmer
0.004
971171AH1-044 GEN
Solar/Wind Harmer
26.172
274823ROCKFORD ;21
Adder
36.411
970169AG2-114 GEN
Solar/Wind Harmer
12.957
276612AE2-035 GEN
Solar/Wind Harmer
0.003
926823AC1-168 GEN
Solar/Wind Harmer
2.2
971549AH1-272 GEN
Solar/Wind Harmer
26.668
971681AH1-341 GEN
Solar/Wind Harmer
20.716
24690905MDL-1G C
Solar/Wind Harmer
0.004
270180AB1-006 GEN1
Solar/Wind Harmer
0.003
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.003
24697605MDL-3G C
Solar/Wind Harmer
0.003
24697905MDL-4G C
Solar/Wind Harmer
0.002
270181AB1-006 GEN2
Solar/Wind Harmer
0
961011AF2-392 GEN
Solar/Wind Harmer
7.462
957751AF2-069 GEN
Solar/Wind Harmer
0.418
274848CAMPGROVE;RU
Solar/Wind Harmer
0.002
276655WTG1_EQ
Solar/Wind Harmer
0.005
276656WTG2_EQ
Solar/Wind Harmer
0.001
959341AF2-225 GEN
Solar/Wind Harmer
13.14
941731AE2-173 GEN
Solar/Wind Harmer
10.429
24386205FR-12G C
Solar/Wind Harmer
0.002
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.002
946321AF1-296 GEN
Solar/Wind Harmer
6.891
965101AG1-375 GEN
Solar/Wind Harmer
12.296
963841AG1-237 GEN
Solar/Wind Harmer
5.208
945581AF1-223 GEN
Solar/Wind Harmer
0.001
276785W4-005 GEN1
Solar/Wind Harmer
0.002
276174W4-005 GEN2
Solar/Wind Harmer
0.002
276849AB2-070 GEN2
Solar/Wind Harmer
0.424
276848AB2-070 GEN3
Solar/Wind Harmer
0.422
963791AG1-232 GEN
Solar/Wind Harmer
15.504
970289AG2-191 GEN
Solar/Wind Harmer
2.164
270594AE1-207 GEN
Solar/Wind Harmer
12.434
971609AH1-304 GEN
Solar/Wind Harmer
1.81
965041AG1-368 GEN
Solar/Wind Harmer
11.055
944221AF1-090 GEN
Solar/Wind Harmer
6.244
24725505WLD G2 C
Solar/Wind Harmer
0.002
24699105WLD G1 C
Solar/Wind Harmer
0.002
970115AG2-085 GEN
Solar/Wind Harmer
4.131
270024AE2-089 GEN
Solar/Wind Harmer
0.011
965051AG1-369 GEN
Solar/Wind Harmer
5.072
270240V3-007_GEN2
Solar/Wind Harmer
0.003
270543AE2-219 C
Solar/Wind Harmer
0.005
247607V1-011 GEN
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
1.018
971029AG2-637 GEN
Solar/Wind Harmer
11.658
971673AH1-337 GEN
Solar/Wind Harmer
4.919
24344005CKG1
50/50
13.628
270142AC1-141 CT1_
50/50
4.979
24641605TWIN BRNCH
50/50
0.036
24642205MAYFLWER
50/50
1.39
274772LINCOLN ;3U
50/50
18.26
970513AG2-328 GEN
Solar/Wind Harmer
6.717
970517AG2-330 GEN
Solar/Wind Harmer
40.303
970349AG2-230 GEN
Solar/Wind Harmer
23.209
270043AE2-236 GEN
Solar/Wind Harmer
9.37
247643Z2-116 C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
11.566
274724RIVER EC ;11
Adder
35.644
274752CRETE EC ;2U
Adder
16.552
274753CRETE EC ;3U
Adder
16.552
24441205WTRV SLR C
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
45.547
274802UNIV PARK;5U
Adder
11.601
274826FISK ;BP
Adder
21.78
276806AD2-047 C O1
Solar/Wind Harmer
7.862
970941AG2-585 GEN
Solar/Wind Harmer
17.342
972228AH1-698 GEN2
Adder
7.363
274800UNIV PARK;3U
Adder
11.588
972038AH1-567 GEN2
Adder
0.725
276897AD1-100 C
Solar/Wind Harmer
0.018
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
247604X1-042
Adder
0.825
270535AF1-215 GEN1
Solar/Wind Harmer
0.017
274676JOLIET 29;8U
Adder
58.35
970031AG2-029 GEN
Solar/Wind Harmer
8.936
274729ELWOOD EC;1P
Adder
32.348
274730ELWOOD EC;6P
Adder
32.348
274734ELWOOD EC;8P
Adder
32.348
274736ELWOOD EC;9P
Adder
32.348
276893AG1-478 C
Solar/Wind Harmer
0.544
944531AF1-118 GEN
Solar/Wind Harmer
61.488
943121AE2-341 GEN
Solar/Wind Harmer
22.888
943591AF1-030 GEN
Solar/Wind Harmer
15.221
964401AG1-302 GEN
Solar/Wind Harmer
0.002
276694AA1-018 GEN2
Solar/Wind Harmer
0.002
274682WAUKEGAN ;7U
Adder
34.62
959141AF2-205 GEN
Solar/Wind Harmer
-0.003
276805AD2-038 GEN
Solar/Wind Harmer
0.004
274872LEEDK;1U
Solar/Wind Harmer
0.488
276799AD1-013 GEN
Solar/Wind Harmer
0.003
946671AF1-331 GEN
Solar/Wind Harmer
1.406
274855GSG-6 ;RU
Solar/Wind Harmer
0.483
274850MENDOTA H;RU
Solar/Wind Harmer
0.155
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.236
959091AF2-200 GEN
Solar/Wind Harmer
26.172
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
4.086
970571AG2-364 GEN
Solar/Wind Harmer
25.867
274858EASY ROAD;U2
Solar/Wind Harmer
0.003
274760LEE CO EC;1U
Adder
17.083
274767LEE CO EC;8U
Adder
16.882
24755605MDL-5G
Solar/Wind Harmer
0.002
970781AG2-491 GEN
Solar/Wind Harmer
12.802
959331AF2-224 GEN
Solar/Wind Harmer
8.908
965021AG1-366 GEN
Solar/Wind Harmer
4.242
276157O29GEN1
Solar/Wind Harmer
2.046
274878BISHOP HL;2U
Solar/Wind Harmer
0.423
942111AE2-223 GEN
Solar/Wind Harmer
4.067
274853TWINGROVE;U1
Solar/Wind Harmer
0.005
965091AG1-374 GEN
Solar/Wind Harmer
36.906
959611AF2-252 GEN
Solar/Wind Harmer
4.101
965931AG1-462 GEN
Solar/Wind Harmer
31.198
247642Z2-115 C
Solar/Wind Harmer
0.005
276686W4-005 GEN3
Solar/Wind Harmer
0.002
971993AH1-541 GEN
Solar/Wind Harmer
5.377
276668AB2-070 GEN1
Solar/Wind Harmer
0.424
276621W2-048 GEN
Solar/Wind Harmer
0.577
276838X2-022 GEN2
Solar/Wind Harmer
0.644
970289AG2-191 GEN
Solar/Wind Harmer
1.253
970291AG2-192 GEN
Solar/Wind Harmer
1.139
942481AE2-261 GEN
Solar/Wind Harmer
33.028
970243AG2-164 GEN
Solar/Wind Harmer
6.289
970519AG2-331 GEN
Solar/Wind Harmer
27.951
970699AG2-449 GEN
Solar/Wind Harmer
2.688
970193AG2-126 GEN
Solar/Wind Harmer
15.928
958821AF2-173 GEN
Solar/Wind Harmer
14.751
270004AE1-209 GEN
Solar/Wind Harmer
2.283
971617AH1-308 GEN
Solar/Wind Harmer
8.548
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.066
946031AF1-268 GEN
Solar/Wind Harmer
9.517
270437AC2-090 C
Solar/Wind Harmer
0.004
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
14.144
270404AC1-167 GEN
Solar/Wind Harmer
0.004
270258AD1-119 GEN
Solar/Wind Harmer
0.002
270356AE2-297 GEN
Solar/Wind Harmer
0.011
270491AE1-102 GEN2
Solar/Wind Harmer
1.045
944201AF1-088_MTX
Adder
163.382
957141AF2-008_MTX
Adder
69.441
NYPJM->LTFIMP_NY
CLTF
3.386
LGEELTFEXP_LGEE->PJM
CLTF
5.588
WECLTFEXP_WEC->PJM
CLTF
7.104
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.19
AG2-052LTFEXP_AG2-052->PJM
LTF
0.447
AH1-155LTFEXP_AH1-155->PJM
LTF
0.671
LAGNLTFEXP_LAGN->PJM
CLTF
14.15
TVALTFEXP_TVA->PJM
CLTF
5.408
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.516
CBM West 1LTFEXP_CBM-W1->PJM
CBM
217.631
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.154
MECLTFEXP_MEC->PJM
CLTF
26.031
SIGELTFEXP_SIGE->PJM
CLTF
0.551
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.138

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P1-2_#6463_16757_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#6463_16757_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:140.14 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:5804.66
MW Contribution:5.04
Bus #Bus NameTypeMW Contribution
971599AH1-298 GEN
50/50
20.512
24727205RPMNG3
50/50
2.026
270144AC1-141 ST1_
50/50
4.287
24653605MOTTVILLE
50/50
0.008
24643105BUCHANAN
50/50
0.025
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
1.893
971347AH1-153 GEN
Solar/Wind Harmer
22.406
270071AF1-092 GEN
Solar/Wind Harmer
27.685
971771AH1-392 GEN
Solar/Wind Harmer
14.093
971619AH1-309 GEN
Solar/Wind Harmer
6.277
971769AH1-391 GEN
Solar/Wind Harmer
15.555
960681AF2-359 GEN
Solar/Wind Harmer
-0.002
274775LINCOLN ;6U
Adder
16.368
274776LINCOLN ;7U
Adder
16.368
274777LINCOLN ;8U
Adder
16.368
24729505KEY G4
Adder
12.57
274814UNIV PK N;0U
Adder
9.612
274807UNIV PK N;3U
Adder
9.591
274805UNIV PK N;1U
Adder
9.549
274811UNIV PK N;7U
Adder
9.528
972037AH1-567 GEN1
Adder
0.346
274827FISK ;RP
Adder
14.675
960591AF2-350 GEN
Solar/Wind Harmer
13.18
972227AH1-698 GEN1
Adder
4.923
274687WILL CNTY;4U
Adder
52.393
274687WILL CNTY;4U
Adder
52.393
274675JOLIET 29;7U
Adder
57.451
274675JOLIET 29;7U
Adder
55.399
274731ELWOOD EC;2P
Adder
30.692
274733ELWOOD EC;3P
Adder
30.692
274735ELWOOD EC;4P
Adder
30.692
274728ELWOOD EC;5P
Adder
30.693
970833AG2-524 GEN
Solar/Wind Harmer
14.308
970833AG2-524 GEN
Solar/Wind Harmer
9.539
270536AF1-215 GEN2
Solar/Wind Harmer
0.016
274746AC1-111 G10
Adder
10.351
274744AC1-111 GEN8
Adder
10.351
958391AF2-133 GEN
Solar/Wind Harmer
0.002
971177AH1-047 GEN
Solar/Wind Harmer
7.718
276868AE1-113 GEN
Solar/Wind Harmer
2.511
276882AE2-255 GEN
Solar/Wind Harmer
1.463
971411AH1-196 GEN
Solar/Wind Harmer
18.689
971675AH1-338 GEN
Solar/Wind Harmer
4.859
971549AH1-272 GEN
Solar/Wind Harmer
25.626
274863CRW1-WTG
Solar/Wind Harmer
0.004
274864CRW2-WTG
Solar/Wind Harmer
0.004
971171AH1-044 GEN
Solar/Wind Harmer
24.739
274823ROCKFORD ;21
Adder
34.415
971611AH1-305 GEN
Solar/Wind Harmer
7.323
963791AG1-232 GEN
Solar/Wind Harmer
16.568
276612AE2-035 GEN
Solar/Wind Harmer
0.003
965101AG1-375 GEN
Solar/Wind Harmer
12.216
926823AC1-168 GEN
Solar/Wind Harmer
2.071
970169AG2-114 GEN
Solar/Wind Harmer
12.156
971681AH1-341 GEN
Solar/Wind Harmer
19.553
961011AF2-392 GEN
Solar/Wind Harmer
7.036
965041AG1-368 GEN
Solar/Wind Harmer
11.932
957751AF2-069 GEN
Solar/Wind Harmer
0.392
274848CAMPGROVE;RU
Solar/Wind Harmer
0.002
24690905MDL-1G C
Solar/Wind Harmer
0.004
270180AB1-006 GEN1
Solar/Wind Harmer
0.003
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.002
270181AB1-006 GEN2
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0.005
276656WTG2_EQ
Solar/Wind Harmer
0.001
959341AF2-225 GEN
Solar/Wind Harmer
12.245
941731AE2-173 GEN
Solar/Wind Harmer
9.718
945581AF1-223 GEN
Solar/Wind Harmer
0.001
946321AF1-296 GEN
Solar/Wind Harmer
6.48
24386205FR-12G C
Solar/Wind Harmer
0.002
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.002
963841AG1-237 GEN
Solar/Wind Harmer
4.707
971609AH1-304 GEN
Solar/Wind Harmer
1.767
965051AG1-369 GEN
Solar/Wind Harmer
5.379
970289AG2-191 GEN
Solar/Wind Harmer
2.036
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.39
276848AB2-070 GEN3
Solar/Wind Harmer
0.388
270594AE1-207 GEN
Solar/Wind Harmer
11.748
270024AE2-089 GEN
Solar/Wind Harmer
0.011
970115AG2-085 GEN
Solar/Wind Harmer
3.968
24725505WLD G2 C
Solar/Wind Harmer
0.002
24699105WLD G1 C
Solar/Wind Harmer
0.001
944221AF1-090 GEN
Solar/Wind Harmer
5.647
270240V3-007_GEN2
Solar/Wind Harmer
0.003
247607V1-011 GEN
Solar/Wind Harmer
0.001
270543AE2-219 C
Solar/Wind Harmer
0.005
971029AG2-637 GEN
Solar/Wind Harmer
10.94
971673AH1-337 GEN
Solar/Wind Harmer
4.593
270284AF1-227 GEN1
Solar/Wind Helper
2.302
270286AF1-227 GEN2
Solar/Wind Helper
0.844
270287AF1-227 GEN3
Solar/Wind Helper
0.844
270054AF2-122 C O1
Solar/Wind Helper
1.201
24344105CKG2
50/50
16.743
24727005RPMNG1
50/50
2.036
270143AC1-141 CT2_
50/50
4.84
24639705ELKHART HY
50/50
0.328
970521AG2-332 GEN
50/50
23.369
24307105BERRINSP G
50/50
0.043
965011AG1-365 GEN
Solar/Wind Harmer
14.965
965421AG1-410 GEN
Solar/Wind Harmer
44.849
246936BC-WTG1
Solar/Wind Harmer
0.606
270489AE1-102 GEN1
Solar/Wind Harmer
1.943
970245AG2-165 GEN
Solar/Wind Harmer
6.295
270063AE2-323 C
Solar/Wind Harmer
0.012
270505AE1-170 C O1
Solar/Wind Harmer
14.646
945111AF1-176 GEN
Solar/Wind Harmer
24.826
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
7.196
274773LINCOLN ;4U
Adder
16.368
274774LINCOLN ;5U
Adder
16.368
274723RIVER EC ;12
Adder
34.361
274751CRETE EC ;1U
Adder
15.774
274754CRETE EC ;4U
Adder
15.774
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
9.528
970373AG2-245 GEN
Solar/Wind Harmer
27.796
274801UNIV PARK;4U
Adder
11.014
276776AD2-060 GEN
Solar/Wind Harmer
1.376
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
57.45
274674JOLIET 9 ;6U
Adder
28.777
274732ELWOOD EC;7P
Adder
30.693
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0.01
274745AC1-111 GEN9
Adder
10.351
276691AA1-018 GEN1
Solar/Wind Harmer
1.544
274682WAUKEGAN ;7U
Adder
32.805
274828WAUKEGAN ;BP
Adder
20.134
958381AF2-132 GEN
Solar/Wind Harmer
0.002
964861AG1-349 GEN
Solar/Wind Harmer
-0.002
971917AH1-482 GEN
Solar/Wind Harmer
16.434
962781AG1-127 GEN
Solar/Wind Harmer
12.012
274872LEEDK;1U
Solar/Wind Harmer
0.008
939401AE1-172 GEN
Solar/Wind Harmer
9.413
276901AD2-066 C O1
Solar/Wind Harmer
0.012
965651AG1-433 GEN
Solar/Wind Harmer
3.678
971997AH1-543 GEN
Solar/Wind Harmer
6.554
276861AD2-134 GEN
Solar/Wind Harmer
0.223
957471AF2-041 GEN
Solar/Wind Harmer
37.108
959081AF2-199 GEN
Solar/Wind Harmer
12.369
971067AG2-660 GEN
Solar/Wind Harmer
4.123
276876AE1-163_GEN2
Solar/Wind Harmer
0.003
274822ROCKFORD ;11
Adder
34.667
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
15.377
972235AH1-702 GEN1
Adder
4.441
970819AG2-516 GEN
Solar/Wind Harmer
14.695
958861AF2-177 GEN
Solar/Wind Harmer
5.294
971475AH1-234 GEN
Solar/Wind Harmer
5.925
970569AG2-363 GEN
Solar/Wind Harmer
36.555
274857EASY ROAD;U1
Solar/Wind Harmer
0.002
274761LEE CO EC;2U
Adder
16.12
274766LEE CO EC;7U
Adder
15.93
276158O29GEN2
Solar/Wind Harmer
0.001
944231AF1-091 GEN
Solar/Wind Harmer
3.153
274877BISHOP HL;1U
Solar/Wind Harmer
0.397
24791305MDL-5G
Solar/Wind Harmer
0.002
276726Z2-087_GEN
Solar/Wind Harmer
0.004
939741AE1-205 GEN
Solar/Wind Harmer
16.327
945371AF1-202 GEN
Solar/Wind Harmer
0.001
274854TWINGROVE;U2
Solar/Wind Harmer
0.005
24385905FR-11G C
Solar/Wind Harmer
0.003
24387305FR-4G C
Solar/Wind Harmer
0.004
972175AH1-670 GEN
Solar/Wind Harmer
9.129
247521TR3_G114
Solar/Wind Harmer
0.393
270246TR4_N_V150
Solar/Wind Harmer
0.07
970291AG2-192 GEN
Solar/Wind Harmer
1.393
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
4.146
963741AG1-226 GEN
Solar/Wind Harmer
24.913
276615X2-022 GEN
Solar/Wind Harmer
0.11
270032AE2-172
Solar/Wind Harmer
6.993
24695305TIMB G C
Solar/Wind Harmer
0.003
270005AE1-210 C O1
Solar/Wind Harmer
2.203
965031AG1-367 GEN
Solar/Wind Harmer
10.168
276903AD2-071 C
Solar/Wind Harmer
11.298
965911AG1-460 GEN
Solar/Wind Harmer
2.014
970825AG2-519 GEN
Solar/Wind Harmer
3.499
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0.001
970613AG2-401 GEN
Solar/Wind Harmer
6.684
247536S-71 GEN
Solar/Wind Harmer
0.341
24728605AND G2
Adder
4.579
270445AC2-157 GEN2
Solar/Wind Harmer
0.004
970333AG2-219 GEN
Solar/Wind Harmer
5.528
970773AG2-487 GEN
Solar/Wind Harmer
1.34
270349AD2-093_GEN
Solar/Wind Helper
1.737
970615AG2-402 GEN
50/50
4.988
270102X2-052 ST
50/50
3.214
270100X2-052 CT1
50/50
2.961
270101X2-052 CT2
50/50
2.961
247620Y3-023
50/50
0.98
970611AG2-400 GEN
Solar/Wind Harmer
14.965
970627AG2-408 GEN
Solar/Wind Harmer
4.49
246938BC-WTG3
Solar/Wind Harmer
0.542
246937BC-WTG2
Solar/Wind Harmer
0.606
970321AG2-212 GEN
Solar/Wind Harmer
6.295
270216AD2-079_GEN
Solar/Wind Harmer
0.002
270526AF1-158 GEN
Solar/Wind Harmer
0.017
957891AF2-083 GEN
Solar/Wind Harmer
0.002
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
17.4
965791AG1-447 GEN
Solar/Wind Harmer
12.76
961051AF2-396 GEN
Solar/Wind Harmer
27.667
961051AF2-396 GEN
Solar/Wind Harmer
18.445
274770LINCOLN ;1U
Adder
16.368
274771LINCOLN ;2U
Adder
16.368
274808UNIV PK N;4U
Adder
9.487
274803UNIV PARK;6U
Adder
11.029
972259AH1-714 GEN
Adder
36.054
274888KELLY CRK;1U
Solar/Wind Harmer
0.774
274887GEN-1.85
Solar/Wind Harmer
0.347
276843GEN-1.7
Solar/Wind Harmer
0.427
958011AF2-095 GEN
Solar/Wind Harmer
18.98
274674JOLIET 9 ;6U
Adder
28.777
274847GR RIDGE ;BU
Solar/Wind Harmer
0.005
971573AH1-285 GEN
Solar/Wind Harmer
2.397
274695ROCKY RD ;2P
Adder
20.358
274693ROCKY RD ;1P
Adder
20.158
274697ROCKY RD ;3P
Adder
5.53
274696ROCKY RD ;4P
Adder
20.838
958481AF2-142 GEN
Solar/Wind Harmer
19.12
274861TOP CROP ;1U
Solar/Wind Harmer
0.003
274862TOP CROP ;2U
Solar/Wind Harmer
1.724
274683WAUKEGAN ;8U
Adder
38.41
274683WAUKEGAN ;8U
Adder
32.378
962691AG1-118 GEN
Solar/Wind Harmer
37.971
970921AG2-575 GEN
Solar/Wind Harmer
12.623
970921AG2-575 GEN
Solar/Wind Harmer
4.208
958491AF2-143 GEN
Solar/Wind Harmer
18.868
944541AF1-119 GEN
Solar/Wind Harmer
0.84
960971AF2-388 GEN
Solar/Wind Harmer
7.355
942991AE2-321 GEN
Solar/Wind Harmer
13.981
274879MINONK ;1U
Solar/Wind Harmer
0.528
971333AH1-146 GEN
Solar/Wind Harmer
24.899
971335AH1-147 GEN
Solar/Wind Harmer
24.899
971341AH1-150 GEN
Solar/Wind Harmer
24.739
971343AH1-151 GEN
Solar/Wind Harmer
24.739
276872AE1-163_GEN1
Solar/Wind Harmer
0.003
274856ECOGROVE ;U1
Solar/Wind Harmer
0.288
276611AD2-172 GEN
Solar/Wind Harmer
0.003
938861AE1-114 GEN
Solar/Wind Harmer
6.879
274764LEE CO EC;5U
Adder
16.158
274765LEE CO EC;6U
Adder
16.158
274762LEE CO EC;3U
Adder
16.12
274763LEE CO EC;4U
Adder
15.968
276603SUBLETTE C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
7.136
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.003
276741O09 GEN1
Solar/Wind Harmer
0.425
276708O09 GEN2
Solar/Wind Harmer
0.425
274851PROVIDENC;RU
Solar/Wind Harmer
0.002
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.467
276646AC1-214 GEN2
Solar/Wind Harmer
0.467
942221AE2-234 GEN
Solar/Wind Harmer
0.059
276782AC1-033 GEN
Solar/Wind Harmer
0.002
960611AF2-352 GEN
Solar/Wind Harmer
3.81
966841AG1-555 GEN
Solar/Wind Harmer
1.27
270599AE1-208 GEN
Solar/Wind Harmer
9.916
270031AE2-169
Solar/Wind Harmer
5.95
276763AC1-053 GEN1
Solar/Wind Harmer
0.002
276764AC1-053 GEN2
Solar/Wind Harmer
0.002
970241AG2-163 GEN
Solar/Wind Harmer
6.141
971613AH1-306 GEN
Solar/Wind Harmer
5.035
276916AD2-100_GEN
Solar/Wind Harmer
20.939
276911AD2-131_GEN
Solar/Wind Harmer
1.379
960441AF2-335 GEN
Solar/Wind Harmer
9.92
970825AG2-519 GEN
Solar/Wind Harmer
10.923
945391AF1-204 GEN
Solar/Wind Harmer
9.973
964611AG1-324 GEN
Solar/Wind Harmer
0.694
270201AC2-176 GEN
Solar/Wind Harmer
0.002
24379505HDWTR1G C
Solar/Wind Harmer
0.003
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
247621Y3-024
Adder
0.306
970623AG2-406 GEN
Solar/Wind Harmer
1.558
270383AD1-128 GEN
Solar/Wind Harmer
0.005
270444AC2-157 GEN1
Solar/Wind Harmer
0.004
971587AH1-292 GEN
Solar/Wind Harmer
5.849
970883AG2-550 GEN
Solar/Wind Harmer
7.917
970885AG2-551 GEN
Solar/Wind Harmer
2.639
270007AE1-245 C
Solar/Wind Harmer
0.002
970239AG2-162 GEN
Solar/Wind Harmer
1.933
270471AD2-092_GEN
Solar/Wind Helper
1.737
24727105RPMNG2
50/50
2.043
965431AG1-411 GEN
50/50
24.916
270142AC1-141 CT1_
50/50
4.84
24641605TWIN BRNCH
50/50
0.035
24344005CKG1
50/50
13.145
24642205MAYFLWER
50/50
1.347
944961AF1-161 GEN
50/50
5.744
962601AG1-109 GEN
50/50
5.744
270043AE2-236 GEN
Solar/Wind Harmer
9.614
959331AF2-224 GEN
Solar/Wind Harmer
10.476
965021AG1-366 GEN
Solar/Wind Harmer
4.988
270491AE1-102 GEN2
Solar/Wind Harmer
1.943
970349AG2-230 GEN
Solar/Wind Harmer
22.406
970513AG2-328 GEN
Solar/Wind Harmer
6.295
970517AG2-330 GEN
Solar/Wind Harmer
37.773
970031AG2-029 GEN
Solar/Wind Harmer
9.246
247643Z2-116 C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
11.278
944531AF1-118 GEN
Solar/Wind Harmer
62.173
274772LINCOLN ;3U
Adder
16.368
24441205WTRV SLR C
Solar/Wind Harmer
0
274724RIVER EC ;11
Adder
33.965
274752CRETE EC ;2U
Adder
15.774
274753CRETE EC ;3U
Adder
15.774
247604X1-042
Adder
0.795
970707AG2-453 GEN
Solar/Wind Harmer
43.26
274802UNIV PARK;5U
Adder
11.029
274826FISK ;BP
Adder
20.707
274800UNIV PARK;3U
Adder
11.014
972038AH1-567 GEN2
Adder
0.689
276806AD2-047 C O1
Solar/Wind Harmer
7.469
970941AG2-585 GEN
Solar/Wind Harmer
16.476
972228AH1-698 GEN2
Adder
6.992
276897AD1-100 C
Solar/Wind Harmer
0.017
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
274676JOLIET 29;8U
Adder
55.398
274729ELWOOD EC;1P
Adder
30.692
274730ELWOOD EC;6P
Adder
30.693
274734ELWOOD EC;8P
Adder
30.693
274736ELWOOD EC;9P
Adder
30.693
276893AG1-478 C
Solar/Wind Harmer
0.516
943121AE2-341 GEN
Solar/Wind Harmer
21.706
943591AF1-030 GEN
Solar/Wind Harmer
14.435
270535AF1-215 GEN1
Solar/Wind Harmer
0.016
276694AA1-018 GEN2
Solar/Wind Harmer
0.002
274682WAUKEGAN ;7U
Adder
32.805
964401AG1-302 GEN
Solar/Wind Harmer
0.002
274872LEEDK;1U
Solar/Wind Harmer
0.462
276805AD2-038 GEN
Solar/Wind Harmer
0.004
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
1.33
274855GSG-6 ;RU
Solar/Wind Harmer
0.457
274850MENDOTA H;RU
Solar/Wind Harmer
0.147
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.223
959141AF2-205 GEN
Solar/Wind Harmer
-0.003
959091AF2-200 GEN
Solar/Wind Harmer
24.739
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
3.861
970571AG2-364 GEN
Solar/Wind Harmer
24.37
274858EASY ROAD;U2
Solar/Wind Harmer
0.002
274760LEE CO EC;1U
Adder
16.12
274767LEE CO EC;8U
Adder
15.93
276157O29GEN1
Solar/Wind Harmer
1.927
274878BISHOP HL;2U
Solar/Wind Harmer
0.397
24755605MDL-5G
Solar/Wind Harmer
0.002
970781AG2-491 GEN
Solar/Wind Harmer
11.712
942111AE2-223 GEN
Solar/Wind Harmer
3.79
965931AG1-462 GEN
Solar/Wind Harmer
29.323
274853TWINGROVE;U1
Solar/Wind Harmer
0.005
965091AG1-374 GEN
Solar/Wind Harmer
34.294
959611AF2-252 GEN
Solar/Wind Harmer
3.81
247642Z2-115 C
Solar/Wind Harmer
0.005
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.07
970289AG2-191 GEN
Solar/Wind Harmer
1.179
970291AG2-192 GEN
Solar/Wind Harmer
1.072
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
4.944
276668AB2-070 GEN1
Solar/Wind Harmer
0.39
276621W2-048 GEN
Solar/Wind Harmer
0.529
276838X2-022 GEN2
Solar/Wind Harmer
0.591
971617AH1-308 GEN
Solar/Wind Harmer
8.654
958821AF2-173 GEN
Solar/Wind Harmer
14.235
270004AE1-209 GEN
Solar/Wind Harmer
2.203
942481AE2-261 GEN
Solar/Wind Harmer
30.115
946031AF1-268 GEN
Solar/Wind Harmer
9.153
970193AG2-126 GEN
Solar/Wind Harmer
14.08
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
13.732
270437AC2-090 C
Solar/Wind Harmer
0.004
270404AC1-167 GEN
Solar/Wind Harmer
0.004
270258AD1-119 GEN
Solar/Wind Harmer
0.002
24728705AND G3
Adder
9.578
24728505AND G1
Adder
4.579
970243AG2-164 GEN
Solar/Wind Harmer
4.523
970519AG2-331 GEN
Solar/Wind Harmer
20.102
970699AG2-449 GEN
Solar/Wind Harmer
1.933
270356AE2-297 GEN
Solar/Wind Harmer
0.01
944201AF1-088_MTX
Adder
132.938
957141AF2-008_MTX
Adder
17.09
NYPJM->LTFIMP_NY
CLTF
3.194
LGEELTFEXP_LGEE->PJM
CLTF
4.31
WECLTFEXP_WEC->PJM
CLTF
6.715
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.799
AG2-052LTFEXP_AG2-052->PJM
LTF
0.422
AH1-155LTFEXP_AH1-155->PJM
LTF
0.632
LAGNLTFEXP_LAGN->PJM
CLTF
13.14
TVALTFEXP_TVA->PJM
CLTF
5.018
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.281
CBM West 1LTFEXP_CBM-W1->PJM
CBM
201.431
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.695
MECLTFEXP_MEC->PJM
CLTF
24.295
SIGELTFEXP_SIGE->PJM
CLTF
0.466
CBM West 2LTFEXP_CBM-W2->PJM
CBM
118.505

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o Base Case


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:130.5 %
Rating:4047.0 MVA
Rating Type:A
MVA to Mitigate:5281.19
MW Contribution:4.58
Bus #Bus NameTypeMW Contribution
971599AH1-298 GEN
50/50
18.435
270144AC1-141 ST1_
50/50
3.968
24643105BUCHANAN
50/50
0.024
24653605MOTTVILLE
50/50
0.007
971347AH1-153 GEN
Solar/Wind Harmer
20.909
971771AH1-392 GEN
Solar/Wind Harmer
13.038
960681AF2-359 GEN
Solar/Wind Harmer
-0.002
971769AH1-391 GEN
Solar/Wind Harmer
14.442
270071AF1-092 GEN
Solar/Wind Harmer
24.752
971619AH1-309 GEN
Solar/Wind Harmer
5.808
274775LINCOLN ;6U
Adder
15.292
274776LINCOLN ;7U
Adder
15.292
274777LINCOLN ;8U
Adder
15.292
274814UNIV PK N;0U
Adder
8.954
274807UNIV PK N;3U
Adder
8.935
274805UNIV PK N;1U
Adder
8.896
274811UNIV PK N;7U
Adder
8.876
972037AH1-567 GEN1
Adder
0.323
274827FISK ;RP
Adder
13.681
960591AF2-350 GEN
Solar/Wind Harmer
12.291
972227AH1-698 GEN1
Adder
4.592
274687WILL CNTY;4U
Adder
48.86
274687WILL CNTY;4U
Adder
48.86
274675JOLIET 29;7U
Adder
53.583
274675JOLIET 29;7U
Adder
51.669
274728ELWOOD EC;5P
Adder
28.626
274731ELWOOD EC;2P
Adder
28.625
274733ELWOOD EC;3P
Adder
28.625
274735ELWOOD EC;4P
Adder
28.625
24729505KEY G4
Adder
11.296
970833AG2-524 GEN
Solar/Wind Harmer
13.35
970833AG2-524 GEN
Solar/Wind Harmer
8.9
274746AC1-111 G10
Adder
9.659
274744AC1-111 GEN8
Adder
9.659
270536AF1-215 GEN2
Solar/Wind Harmer
0.015
971177AH1-047 GEN
Solar/Wind Harmer
7.198
276868AE1-113 GEN
Solar/Wind Harmer
2.341
276882AE2-255 GEN
Solar/Wind Harmer
1.364
958391AF2-133 GEN
Solar/Wind Harmer
0.002
971675AH1-338 GEN
Solar/Wind Harmer
4.532
971411AH1-196 GEN
Solar/Wind Harmer
17.431
971549AH1-272 GEN
Solar/Wind Harmer
23.961
274863CRW1-WTG
Solar/Wind Harmer
0.004
274864CRW2-WTG
Solar/Wind Harmer
0.004
971171AH1-044 GEN
Solar/Wind Harmer
23.073
274823ROCKFORD ;21
Adder
32.096
971611AH1-305 GEN
Solar/Wind Harmer
6.79
276612AE2-035 GEN
Solar/Wind Harmer
0.003
926823AC1-168 GEN
Solar/Wind Harmer
1.931
970169AG2-114 GEN
Solar/Wind Harmer
11.331
971681AH1-341 GEN
Solar/Wind Harmer
18.233
961011AF2-392 GEN
Solar/Wind Harmer
6.56
957751AF2-069 GEN
Solar/Wind Harmer
0.366
965101AG1-375 GEN
Solar/Wind Harmer
11.003
274848CAMPGROVE;RU
Solar/Wind Harmer
0.002
276655WTG1_EQ
Solar/Wind Harmer
0.004
276656WTG2_EQ
Solar/Wind Harmer
0.001
959341AF2-225 GEN
Solar/Wind Harmer
11.407
941731AE2-173 GEN
Solar/Wind Harmer
9.053
24690905MDL-1G C
Solar/Wind Harmer
0.003
270180AB1-006 GEN1
Solar/Wind Harmer
0.003
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.002
270181AB1-006 GEN2
Solar/Wind Harmer
0
946321AF1-296 GEN
Solar/Wind Harmer
6.04
945581AF1-223 GEN
Solar/Wind Harmer
0.001
24386205FR-12G C
Solar/Wind Harmer
0.002
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.002
963791AG1-232 GEN
Solar/Wind Harmer
13.932
963841AG1-237 GEN
Solar/Wind Harmer
4.358
965041AG1-368 GEN
Solar/Wind Harmer
10.015
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.363
276848AB2-070 GEN3
Solar/Wind Harmer
0.361
970289AG2-191 GEN
Solar/Wind Harmer
1.856
971609AH1-304 GEN
Solar/Wind Harmer
1.589
270594AE1-207 GEN
Solar/Wind Harmer
10.691
965051AG1-369 GEN
Solar/Wind Harmer
4.577
270024AE2-089 GEN
Solar/Wind Harmer
0.01
24725505WLD G2 C
Solar/Wind Harmer
0.002
24699105WLD G1 C
Solar/Wind Harmer
0.001
970115AG2-085 GEN
Solar/Wind Harmer
3.587
944221AF1-090 GEN
Solar/Wind Harmer
5.246
270240V3-007_GEN2
Solar/Wind Harmer
0.002
247607V1-011 GEN
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
0.91
270543AE2-219 C
Solar/Wind Harmer
0.004
971029AG2-637 GEN
Solar/Wind Harmer
9.925
971673AH1-337 GEN
Solar/Wind Harmer
4.175
270102X2-052 ST
50/50
2.992
270100X2-052 CT1
50/50
2.757
270101X2-052 CT2
50/50
2.757
247620Y3-023
50/50
0.89
970321AG2-212 GEN
Solar/Wind Harmer
5.915
270216AD2-079_GEN
Solar/Wind Harmer
0.002
965681AG1-436 GEN
Solar/Wind Harmer
16.197
965791AG1-447 GEN
Solar/Wind Harmer
11.878
270526AF1-158 GEN
Solar/Wind Harmer
0.016
24441505OLIV SLR
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
0.002
961051AF2-396 GEN
Solar/Wind Harmer
25.575
961051AF2-396 GEN
Solar/Wind Harmer
17.05
274770LINCOLN ;1U
Adder
15.292
274771LINCOLN ;2U
Adder
15.292
274808UNIV PK N;4U
Adder
8.838
972259AH1-714 GEN
Adder
33.646
274803UNIV PARK;6U
Adder
10.281
274888KELLY CRK;1U
Solar/Wind Harmer
0.722
274887GEN-1.85
Solar/Wind Harmer
0.324
276843GEN-1.7
Solar/Wind Harmer
0.398
958011AF2-095 GEN
Solar/Wind Harmer
17.698
274674JOLIET 9 ;6U
Adder
26.84
274847GR RIDGE ;BU
Solar/Wind Harmer
0.004
971573AH1-285 GEN
Solar/Wind Harmer
2.237
274695ROCKY RD ;2P
Adder
18.993
274693ROCKY RD ;1P
Adder
18.806
274697ROCKY RD ;3P
Adder
5.159
274696ROCKY RD ;4P
Adder
19.441
958481AF2-142 GEN
Solar/Wind Harmer
17.825
274861TOP CROP ;1U
Solar/Wind Harmer
0.003
274862TOP CROP ;2U
Solar/Wind Harmer
1.607
274683WAUKEGAN ;8U
Adder
35.828
274683WAUKEGAN ;8U
Adder
30.201
962691AG1-118 GEN
Solar/Wind Harmer
35.425
970921AG2-575 GEN
Solar/Wind Harmer
11.776
970921AG2-575 GEN
Solar/Wind Harmer
3.925
958491AF2-143 GEN
Solar/Wind Harmer
17.589
942991AE2-321 GEN
Solar/Wind Harmer
13.041
274879MINONK ;1U
Solar/Wind Harmer
0.492
970611AG2-400 GEN
Solar/Wind Harmer
11.612
970627AG2-408 GEN
Solar/Wind Harmer
3.484
971333AH1-146 GEN
Solar/Wind Harmer
23.223
971335AH1-147 GEN
Solar/Wind Harmer
23.223
971341AH1-150 GEN
Solar/Wind Harmer
23.073
971343AH1-151 GEN
Solar/Wind Harmer
23.073
276872AE1-163_GEN1
Solar/Wind Harmer
0.003
274856ECOGROVE ;U1
Solar/Wind Harmer
0.269
276611AD2-172 GEN
Solar/Wind Harmer
0.003
938861AE1-114 GEN
Solar/Wind Harmer
6.415
944541AF1-119 GEN
Solar/Wind Harmer
0.756
960971AF2-388 GEN
Solar/Wind Harmer
6.621
274764LEE CO EC;5U
Adder
15.066
274765LEE CO EC;6U
Adder
15.066
274762LEE CO EC;3U
Adder
15.031
274763LEE CO EC;4U
Adder
14.889
276603SUBLETTE C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
6.653
276741O09 GEN1
Solar/Wind Harmer
0.396
276708O09 GEN2
Solar/Wind Harmer
0.396
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.436
276646AC1-214 GEN2
Solar/Wind Harmer
0.436
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
276782AC1-033 GEN
Solar/Wind Harmer
0.002
960611AF2-352 GEN
Solar/Wind Harmer
3.549
942221AE2-234 GEN
Solar/Wind Harmer
0.052
966841AG1-555 GEN
Solar/Wind Harmer
1.176
276763AC1-053 GEN1
Solar/Wind Harmer
0.002
276764AC1-053 GEN2
Solar/Wind Harmer
0.002
970241AG2-163 GEN
Solar/Wind Harmer
5.684
270599AE1-208 GEN
Solar/Wind Harmer
8.918
270031AE2-169
Solar/Wind Harmer
5.351
971613AH1-306 GEN
Solar/Wind Harmer
4.582
276916AD2-100_GEN
Solar/Wind Harmer
19.464
276911AD2-131_GEN
Solar/Wind Harmer
1.282
960441AF2-335 GEN
Solar/Wind Harmer
8.968
970825AG2-519 GEN
Solar/Wind Harmer
9.877
945391AF1-204 GEN
Solar/Wind Harmer
9.229
964611AG1-324 GEN
Solar/Wind Harmer
0.623
24379505HDWTR1G C
Solar/Wind Harmer
0.003
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
270201AC2-176 GEN
Solar/Wind Harmer
0.001
247621Y3-024
Adder
0.274
970623AG2-406 GEN
Solar/Wind Harmer
1.433
24344005CKG1
50/50
12.252
270142AC1-141 CT1_
50/50
4.479
24641605TWIN BRNCH
50/50
0.032
24642205MAYFLWER
50/50
1.247
944961AF1-161 GEN
50/50
5.318
962601AG1-109 GEN
50/50
5.318
970349AG2-230 GEN
Solar/Wind Harmer
20.909
970513AG2-328 GEN
Solar/Wind Harmer
5.915
970517AG2-330 GEN
Solar/Wind Harmer
35.487
270043AE2-236 GEN
Solar/Wind Harmer
8.538
247643Z2-116 C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
10.397
274772LINCOLN ;3U
Adder
15.292
24441205WTRV SLR C
Solar/Wind Harmer
0
274724RIVER EC ;11
Adder
31.641
944531AF1-118 GEN
Solar/Wind Harmer
55.84
274752CRETE EC ;2U
Adder
14.685
274753CRETE EC ;3U
Adder
14.685
970031AG2-029 GEN
Solar/Wind Harmer
8.073
247604X1-042
Adder
0.74
970707AG2-453 GEN
Solar/Wind Harmer
40.394
274802UNIV PARK;5U
Adder
10.281
274826FISK ;BP
Adder
19.304
276806AD2-047 C O1
Solar/Wind Harmer
6.965
970941AG2-585 GEN
Solar/Wind Harmer
15.363
274800UNIV PARK;3U
Adder
10.269
972038AH1-567 GEN2
Adder
0.643
972228AH1-698 GEN2
Adder
6.522
276897AD1-100 C
Solar/Wind Harmer
0.016
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
274676JOLIET 29;8U
Adder
51.668
274730ELWOOD EC;6P
Adder
28.626
274734ELWOOD EC;8P
Adder
28.626
274736ELWOOD EC;9P
Adder
28.626
274729ELWOOD EC;1P
Adder
28.625
276893AG1-478 C
Solar/Wind Harmer
0.481
943121AE2-341 GEN
Solar/Wind Harmer
20.258
943591AF1-030 GEN
Solar/Wind Harmer
13.472
270535AF1-215 GEN1
Solar/Wind Harmer
0.015
276694AA1-018 GEN2
Solar/Wind Harmer
0.002
274682WAUKEGAN ;7U
Adder
30.6
964401AG1-302 GEN
Solar/Wind Harmer
0.002
274872LEEDK;1U
Solar/Wind Harmer
0.431
276805AD2-038 GEN
Solar/Wind Harmer
0.003
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
1.24
274855GSG-6 ;RU
Solar/Wind Harmer
0.426
274850MENDOTA H;RU
Solar/Wind Harmer
0.137
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.208
959331AF2-224 GEN
Solar/Wind Harmer
8.128
965021AG1-366 GEN
Solar/Wind Harmer
3.871
959091AF2-200 GEN
Solar/Wind Harmer
23.073
959141AF2-205 GEN
Solar/Wind Harmer
-0.003
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
3.601
970571AG2-364 GEN
Solar/Wind Harmer
22.715
274858EASY ROAD;U2
Solar/Wind Harmer
0.002
274760LEE CO EC;1U
Adder
15.031
274767LEE CO EC;8U
Adder
14.854
276157O29GEN1
Solar/Wind Harmer
1.797
274878BISHOP HL;2U
Solar/Wind Harmer
0.37
24344105CKG2
50/50
15.732
270143AC1-141 CT2_
50/50
4.479
24639705ELKHART HY
50/50
0.3
970521AG2-332 GEN
50/50
21.293
24307105BERRINSP G
50/50
0.04
970245AG2-165 GEN
Solar/Wind Harmer
5.915
270505AE1-170 C O1
Solar/Wind Harmer
13.553
945111AF1-176 GEN
Solar/Wind Harmer
22.888
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
6.663
274773LINCOLN ;4U
Adder
15.292
274774LINCOLN ;5U
Adder
15.292
270063AE2-323 C
Solar/Wind Harmer
0.01
274723RIVER EC ;12
Adder
32.009
274751CRETE EC ;1U
Adder
14.685
274754CRETE EC ;4U
Adder
14.685
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
8.876
970373AG2-245 GEN
Solar/Wind Harmer
25.833
276776AD2-060 GEN
Solar/Wind Harmer
1.283
274801UNIV PARK;4U
Adder
10.269
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
53.582
274674JOLIET 9 ;6U
Adder
26.84
274732ELWOOD EC;7P
Adder
28.626
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
274745AC1-111 GEN9
Adder
9.659
270055AF2-134 C O1
Solar/Wind Harmer
0.009
276691AA1-018 GEN1
Solar/Wind Harmer
1.44
274682WAUKEGAN ;7U
Adder
30.6
274828WAUKEGAN ;BP
Adder
18.78
962781AG1-127 GEN
Solar/Wind Harmer
11.207
958381AF2-132 GEN
Solar/Wind Harmer
0.002
274872LEEDK;1U
Solar/Wind Harmer
0.007
939401AE1-172 GEN
Solar/Wind Harmer
8.779
964861AG1-349 GEN
Solar/Wind Harmer
-0.002
971917AH1-482 GEN
Solar/Wind Harmer
15.25
276901AD2-066 C O1
Solar/Wind Harmer
0.012
971997AH1-543 GEN
Solar/Wind Harmer
6.112
276861AD2-134 GEN
Solar/Wind Harmer
0.208
965011AG1-365 GEN
Solar/Wind Harmer
11.612
957471AF2-041 GEN
Solar/Wind Harmer
34.609
959081AF2-199 GEN
Solar/Wind Harmer
11.536
971067AG2-660 GEN
Solar/Wind Harmer
3.845
276876AE1-163_GEN2
Solar/Wind Harmer
0.003
274822ROCKFORD ;11
Adder
32.33
972235AH1-702 GEN1
Adder
4.141
970819AG2-516 GEN
Solar/Wind Harmer
13.704
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
14.256
971475AH1-234 GEN
Solar/Wind Harmer
5.525
970569AG2-363 GEN
Solar/Wind Harmer
34.072
965651AG1-433 GEN
Solar/Wind Harmer
3.31
274857EASY ROAD;U1
Solar/Wind Harmer
0.002
274761LEE CO EC;2U
Adder
15.031
274766LEE CO EC;7U
Adder
14.854
276158O29GEN2
Solar/Wind Harmer
0.001
274877BISHOP HL;1U
Solar/Wind Harmer
0.37
958861AF2-177 GEN
Solar/Wind Harmer
4.768
276726Z2-087_GEN
Solar/Wind Harmer
0.004
939741AE1-205 GEN
Solar/Wind Harmer
15.209
24791305MDL-5G
Solar/Wind Harmer
0.001
274854TWINGROVE;U2
Solar/Wind Harmer
0.005
945371AF1-202 GEN
Solar/Wind Harmer
0.001
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.004
944231AF1-091 GEN
Solar/Wind Harmer
2.757
972175AH1-670 GEN
Solar/Wind Harmer
8.498
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
3.857
970291AG2-192 GEN
Solar/Wind Harmer
1.27
276615X2-022 GEN
Solar/Wind Harmer
0.102
963741AG1-226 GEN
Solar/Wind Harmer
23.062
270032AE2-172
Solar/Wind Harmer
6.364
965911AG1-460 GEN
Solar/Wind Harmer
1.873
276903AD2-071 C
Solar/Wind Harmer
10.292
270005AE1-210 C O1
Solar/Wind Harmer
1.994
965031AG1-367 GEN
Solar/Wind Harmer
9.202
247521TR3_G114
Solar/Wind Harmer
0.334
270246TR4_N_V150
Solar/Wind Harmer
0.059
24695305TIMB G C
Solar/Wind Harmer
0.002
970825AG2-519 GEN
Solar/Wind Harmer
3.164
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0.001
970613AG2-401 GEN
Solar/Wind Harmer
6.065
24728605AND G2
Adder
4.198
247536S-71 GEN
Solar/Wind Harmer
0.307
965421AG1-410 GEN
Solar/Wind Harmer
22.83
270445AC2-157 GEN2
Solar/Wind Harmer
0.003
970333AG2-219 GEN
Solar/Wind Harmer
5.143
246936BC-WTG1
Solar/Wind Harmer
0.291
270489AE1-102 GEN1
Solar/Wind Harmer
0.934
970773AG2-487 GEN
Solar/Wind Harmer
1.226
270349AD2-093_GEN
Solar/Wind Helper
1.564
942111AE2-223 GEN
Solar/Wind Harmer
3.531
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
10.846
965931AG1-462 GEN
Solar/Wind Harmer
27.328
274853TWINGROVE;U1
Solar/Wind Harmer
0.004
965091AG1-374 GEN
Solar/Wind Harmer
31.938
959611AF2-252 GEN
Solar/Wind Harmer
3.549
247642Z2-115 C
Solar/Wind Harmer
0.004
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
4.599
276668AB2-070 GEN1
Solar/Wind Harmer
0.363
970289AG2-191 GEN
Solar/Wind Harmer
1.074
970291AG2-192 GEN
Solar/Wind Harmer
0.977
276621W2-048 GEN
Solar/Wind Harmer
0.492
276838X2-022 GEN2
Solar/Wind Harmer
0.549
942481AE2-261 GEN
Solar/Wind Harmer
27.997
958821AF2-173 GEN
Solar/Wind Harmer
12.883
270004AE1-209 GEN
Solar/Wind Harmer
1.994
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.059
971617AH1-308 GEN
Solar/Wind Harmer
7.545
946031AF1-268 GEN
Solar/Wind Harmer
8.268
970193AG2-126 GEN
Solar/Wind Harmer
13.029
270437AC2-090 C
Solar/Wind Harmer
0.004
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
12.308
270404AC1-167 GEN
Solar/Wind Harmer
0.003
270258AD1-119 GEN
Solar/Wind Harmer
0.002
24728705AND G3
Adder
8.781
24728505AND G1
Adder
4.198
970243AG2-164 GEN
Solar/Wind Harmer
4.208
970519AG2-331 GEN
Solar/Wind Harmer
18.702
970699AG2-449 GEN
Solar/Wind Harmer
1.798
270491AE1-102 GEN2
Solar/Wind Harmer
0.934
270356AE2-297 GEN
Solar/Wind Harmer
0.009
270383AD1-128 GEN
Solar/Wind Harmer
0.005
270444AC2-157 GEN1
Solar/Wind Harmer
0.003
971587AH1-292 GEN
Solar/Wind Harmer
5.417
270007AE1-245 C
Solar/Wind Harmer
0.002
970239AG2-162 GEN
Solar/Wind Harmer
1.798
246938BC-WTG3
Solar/Wind Harmer
0.26
246937BC-WTG2
Solar/Wind Harmer
0.291
970883AG2-550 GEN
Solar/Wind Harmer
7.146
970885AG2-551 GEN
Solar/Wind Harmer
2.382
270471AD2-092_GEN
Solar/Wind Helper
1.564
944201AF1-088_MTX
Adder
123.107
957141AF2-008_MTX
Adder
33.614
NYPJM->LTFIMP_NY
CLTF
2.955
LGEELTFEXP_LGEE->PJM
CLTF
4
WECLTFEXP_WEC->PJM
CLTF
6.262
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.805
AG2-052LTFEXP_AG2-052->PJM
LTF
0.392
AH1-155LTFEXP_AH1-155->PJM
LTF
0.587
LAGNLTFEXP_LAGN->PJM
CLTF
12.118
TVALTFEXP_TVA->PJM
CLTF
4.605
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.3
CBM West 1LTFEXP_CBM-W1->PJM
CBM
190.688
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.117
MECLTFEXP_MEC->PJM
CLTF
22.614
SIGELTFEXP_SIGE->PJM
CLTF
0.431
CBM West 2LTFEXP_CBM-W2->PJM
CBM
109.586

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P1-2_#17217_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#17217_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:115.67 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6388.32
MW Contribution:4.53
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
2.756
972203AH1-686 GEN
Adder
4.425
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
957241AF2-018 GEN
Solar/Wind Harmer
-0.002
270399AC1-101 GEN
Solar/Wind Harmer
3.805
270400AC1-102 GEN
Solar/Wind Harmer
3.805
962771AG1-126 GEN
Solar/Wind Harmer
46.194
24477305BRIDGE
Adder
0.588
970281AG2-184 GEN
Solar/Wind Harmer
22.926
972143AH1-644 GEN
Solar/Wind Harmer
11.827
971985AH1-537 GEN
Solar/Wind Harmer
3.245
941621AE2-160 GEN
Adder
5.057
971313AH1-133 GEN
Solar/Wind Harmer
10.378
270367AC2-061_GEN
Solar/Wind Harmer
0.008
970879AG2-548 GEN
Solar/Wind Harmer
9.191
972163AH1-664 GEN
Solar/Wind Harmer
11.344
972165AH1-665 GEN
Solar/Wind Harmer
9.085
339243AC2-075 GEN1
Solar/Wind Harmer
0.002
25196108MFTGT2
Adder
2.193
25196108MFTGT2
Adder
2.036
3429211JKCT 2G
Adder
16.676
252524AE2-267 GEN
Solar/Wind Harmer
0.004
25196408WSDLE3
Adder
12.579
25196308WSDLE2
Adder
12.47
25196208WSDLE1
Adder
12.439
25196708WSDLE6
Adder
12.407
25196508WSDLE4
Adder
12.095
24734705WLF1G3
Adder
8.198
24734805WLF1G4
Adder
8.198
24734905WLF1G5
Adder
8.198
270340AC2-060 GEN
Solar/Wind Harmer
0.011
270132AB1-180 C
Adder
0.17
339211AE2-254 GEN
Solar/Wind Harmer
0.004
24735105WLF2G1
Adder
8.08
970455AG2-298 GEN
Solar/Wind Harmer
6.495
965401AG1-405 GEN
Solar/Wind Harmer
5.522
965411AG1-406 GEN
Solar/Wind Harmer
3.552
270269AC2-059
Solar/Wind Harmer
0.006
971061AG2-657 GEN
Solar/Wind Harmer
6.031
270240V3-007_GEN2
Solar/Wind Harmer
0.003
253372AE2-315 SEC3
Adder
2.585
253372AE2-315 SEC3
Adder
2.585
25306009OHH W.
Adder
3.927
24725505WLD G2 C
Solar/Wind Harmer
0.002
24699105WLD G1 C
Solar/Wind Harmer
0.001
253349AC2-067 GEN
Solar/Wind Harmer
2.978
253400AC2-068 GEN
Solar/Wind Harmer
1.198
970289AG2-191 GEN
Solar/Wind Harmer
1.794
270594AE1-207 GEN
Solar/Wind Harmer
10.572
963841AG1-237 GEN
Solar/Wind Harmer
4.089
970115AG2-085 GEN
Solar/Wind Harmer
3.766
971673AH1-337 GEN
Solar/Wind Harmer
6.118
24386205FR-12G C
Solar/Wind Harmer
0.002
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.002
971029AG2-637 GEN
Solar/Wind Harmer
14.095
24690905MDL-1G C
Solar/Wind Harmer
0.003
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0.001
270543AE2-219 C
Solar/Wind Harmer
0.006
971609AH1-304 GEN
Solar/Wind Harmer
1.526
270432AC2-029 GEN
Solar/Wind Harmer
4.141
944221AF1-090 GEN
Solar/Wind Harmer
5.475
965101AG1-375 GEN
Solar/Wind Harmer
9.315
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.339
276848AB2-070 GEN3
Solar/Wind Harmer
0.337
971611AH1-305 GEN
Solar/Wind Harmer
5.525
958391AF2-133 GEN
Solar/Wind Harmer
0.001
276655WTG1_EQ
Solar/Wind Harmer
0.004
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
9.696
24729505KEY G4
Adder
8.586
941731AE2-173 GEN
Solar/Wind Harmer
7.695
966391AG1-508 GEN
Solar/Wind Harmer
1.427
970169AG2-114 GEN
Solar/Wind Harmer
9.2
274863CRW1-WTG
Solar/Wind Harmer
0.003
274864CRW2-WTG
Solar/Wind Harmer
0.003
241972AD1-140 GEN
Solar/Wind Harmer
1.003
274848CAMPGROVE;RU
Solar/Wind Harmer
0.002
957751AF2-069 GEN
Solar/Wind Harmer
0.302
270536AF1-215 GEN2
Solar/Wind Harmer
0.011
926823AC1-168 GEN
Solar/Wind Harmer
1.557
276868AE1-113 GEN
Solar/Wind Harmer
1.835
276882AE2-255 GEN
Solar/Wind Harmer
1.069
274775LINCOLN ;6U
Adder
11.055
274776LINCOLN ;7U
Adder
11.055
274777LINCOLN ;8U
Adder
11.055
970833AG2-524 GEN
Solar/Wind Harmer
10.052
970833AG2-524 GEN
Solar/Wind Harmer
6.701
274746AC1-111 G10
Adder
7.316
274744AC1-111 GEN8
Adder
7.316
961011AF2-392 GEN
Solar/Wind Harmer
5.358
971675AH1-338 GEN
Solar/Wind Harmer
3.562
274731ELWOOD EC;2P
Adder
21.509
274733ELWOOD EC;3P
Adder
13.442
23750501ELLIOTTS
Solar/Wind Helper
0.788
238126S14_GEN_1
Solar/Wind Helper
0.81
254304AE2-114 C
Solar/Wind Helper
0.239
241997AF1-093 GEN
Solar/Wind Helper
0.28
241982AE2-343 S C
Solar/Wind Helper
0.243
20092526R32
Solar/Wind Helper
1.311
203961AE2-224 GEN
Solar/Wind Helper
2.707
20091526CHSTN_FL
Solar/Wind Helper
0.654
238109AE1-109 GEN2
Solar/Wind Helper
0.102
238110AE1-109 GEN3
Solar/Wind Helper
0.102
20090526Q36
Solar/Wind Helper
1.167
203993AD2-133_GEN1
Solar/Wind Helper
1.167
941231AE2-117 GEN
Solar/Wind Helper
0.53
203846AF2-130 C
Solar/Wind Helper
0.497
203855AF2-088 C
Solar/Wind Helper
0.17
203804AE2-113_GEN
Solar/Wind Helper
1.924
959431AF2-234 GEN
Solar/Wind Helper
1
964051AG1-259 GEN
Solar/Wind Helper
0.075
964061AG1-260 GEN
Solar/Wind Helper
0.075
959421AF2-233 GEN
Solar/Wind Helper
0.5
961261AF2-417 GEN
Solar/Wind Helper
0.495
209116AE2-175 GEN
Solar/Wind Helper
1.966
20675128HRM_W1-127
Solar/Wind Helper
0.032
207408W3-077 C
Solar/Wind Helper
0.092
20675728RH_W2-091
Solar/Wind Helper
0.149
207484AF2-139 C O1
Solar/Wind Helper
0.092
203975AE1-071-GEN
Solar/Wind Helper
2.674
20674828DL_W4-046
Solar/Wind Helper
0.008
20675928HOL_W4-097
Solar/Wind Helper
0.055
20676328BVR_Y1-020
Solar/Wind Helper
0.029
238208AF1-136 C
Solar/Wind Helper
0.192
207530AG1-191 GEN
Solar/Wind Helper
0.072
966261AG1-495 GEN
Solar/Wind Helper
0.088
218524CNTRALGAS1 C
Solar/Wind Helper
0.173
20675528CPH_W2-050
Solar/Wind Helper
0.093
218526CNTRALGAS2 C
Solar/Wind Helper
0.173
219620RIDERU C
Solar/Wind Helper
0.001
207459AE1-142 C O1
Solar/Wind Helper
0.309
20715728PEM_W1-119
Solar/Wind Helper
0.102
20715828PEM_W1-120
Solar/Wind Helper
0.102
214067T20SOLAR
Solar/Wind Helper
0.012
959381AF2-229 GEN
Solar/Wind Helper
0.364
219607WPEMNERT C
Solar/Wind Helper
0.085
219688LUMSOLAR_S C
Solar/Wind Helper
0.042
219272CLEANLIGHT C
Solar/Wind Helper
0.027
219914AD2-027 C
Solar/Wind Helper
0.121
227927V4-067C
Solar/Wind Helper
0.011
228754AB1-001 C
Solar/Wind Helper
0.027
964001AG1-254 GEN
Solar/Wind Helper
1.003
234033AF1-007_GEN
Solar/Wind Helper
7.245
233923SMA
Solar/Wind Helper
0.989
233990AG1-397 GEN
Solar/Wind Helper
0.279
232432Z2-076 GEN
Solar/Wind Helper
0.069
237085AD2-009_GEN
Solar/Wind Helper
1.449
205932AD2-116_GEN
Solar/Wind Helper
0.523
205956AE1-196_GEN
Solar/Wind Helper
0.523
205943AE1-185 GEN
Solar/Wind Helper
0.523
232436AB1-176 C
Solar/Wind Helper
0.046
233935AB2-179 C
Solar/Wind Helper
1.307
960921AF2-383 GEN
Solar/Wind Helper
0.373
971171AH1-044 GEN
Solar/Wind Harmer
3.998
243186AF1-051 GEN
50/50
12.478
24723005RIVRG1
Adder
36.021
24723105RIVRG2
Adder
36.021
24685805CER G1
Adder
15.526
24685905CER G2
Adder
15.526
944971AF1-162 GEN
Solar/Wind Harmer
12.174
971225AH1-072 GEN
Solar/Wind Harmer
2.13
971227AH1-073 GEN
Solar/Wind Harmer
2.13
24728205BUCHG1
Adder
6.831
970239AG2-162 GEN
Solar/Wind Harmer
2.59
270186AC1-089 GEN
Solar/Wind Harmer
0.006
962581AG1-107 GEN
Solar/Wind Harmer
0.002
960161AF2-307 GEN
Solar/Wind Harmer
6.771
971073AG2-665 GEN
Solar/Wind Harmer
9.191
252509AD1-136 GEN
Solar/Wind Harmer
0.051
339221AD2-048_GEN
Solar/Wind Harmer
0.006
972043AH1-570 GEN
Solar/Wind Harmer
2.614
972045AH1-571 GEN
Solar/Wind Harmer
2.094
25183208HLCRTG
Solar/Wind Harmer
0.016
252519AF1-045_GEN
Solar/Wind Harmer
8.714
252516AE2-318_GEN
Solar/Wind Harmer
7.729
970235AG2-159 GEN
Solar/Wind Harmer
6.108
970235AG2-159 GEN
Solar/Wind Harmer
3.504
971125AH1-004 GEN
Solar/Wind Harmer
3.992
970107AG2-081 GEN
Solar/Wind Harmer
2.994
25194408D.CRK1
Adder
10.799
25194508D.CRK3
Adder
2.019
942891AE2-308 GEN
Solar/Wind Harmer
9.954
253317AC1-085 GEN4
Solar/Wind Harmer
0.006
270444AC2-157 GEN1
Solar/Wind Harmer
0.004
971587AH1-292 GEN
Solar/Wind Harmer
7.197
253394AE2-221_GEN
Solar/Wind Harmer
0.012
253398AE2-221_GEN2
Solar/Wind Harmer
0.012
964571AG1-320 GEN
Solar/Wind Harmer
8.854
970653AG2-424 GEN
Solar/Wind Harmer
4.654
970653AG2-424 GEN
Solar/Wind Harmer
2.412
24728805RICHG1
Adder
5.204
24728905RICHG2
Adder
5.204
971081AG2-670 GEN
Solar/Wind Harmer
7.154
945391AF1-204 GEN
Solar/Wind Harmer
10.131
24379505HDWTR1G C
Solar/Wind Harmer
0.003
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
253370AE2-315 SEC1
Adder
2.733
270383AD1-128 GEN
Solar/Wind Harmer
0.006
970241AG2-163 GEN
Solar/Wind Harmer
5.517
971613AH1-306 GEN
Solar/Wind Harmer
4.531
25322209TAIT E
Adder
13.187
25322209TAIT E
Adder
12.891
970825AG2-519 GEN
Solar/Wind Harmer
10.439
960441AF2-335 GEN
Solar/Wind Harmer
9.416
966841AG1-555 GEN
Solar/Wind Harmer
1.065
339255AE2-071 GEN
Solar/Wind Harmer
-0.154
970321AG2-212 GEN
Solar/Wind Harmer
4.056
971485AH1-239 GEN
Solar/Wind Harmer
7.489
964781AG1-341 GEN
Solar/Wind Harmer
9.922
966021AG1-471 GEN
Solar/Wind Harmer
5.054
25326109MON D
Adder
1.763
970883AG2-550 GEN
Solar/Wind Harmer
9.347
970885AG2-551 GEN
Solar/Wind Harmer
3.116
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
270599AE1-208 GEN
Solar/Wind Harmer
8.564
270031AE2-169
Solar/Wind Harmer
5.138
276916AD2-100_GEN
Solar/Wind Harmer
19.555
276911AD2-131_GEN
Solar/Wind Harmer
1.288
944541AF1-119 GEN
Solar/Wind Harmer
0.623
960971AF2-388 GEN
Solar/Wind Harmer
5.453
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
0.696
247621Y3-024
Adder
0.32
960611AF2-352 GEN
Solar/Wind Harmer
3.082
270201AC2-176 GEN
Solar/Wind Harmer
0.002
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.36
276646AC1-214 GEN2
Solar/Wind Harmer
0.36
276782AC1-033 GEN
Solar/Wind Harmer
0.001
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
274879MINONK ;1U
Solar/Wind Harmer
0.386
274770LINCOLN ;1U
Adder
11.055
274771LINCOLN ;2U
Adder
11.055
276741O09 GEN1
Solar/Wind Harmer
0.325
276708O09 GEN2
Solar/Wind Harmer
0.325
958491AF2-143 GEN
Solar/Wind Harmer
13.709
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
1.236
972259AH1-714 GEN
Adder
24.976
958481AF2-142 GEN
Solar/Wind Harmer
13.701
971573AH1-285 GEN
Solar/Wind Harmer
1.702
276603SUBLETTE C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
5.45
274696ROCKY RD ;4P
Adder
14.914
274695ROCKY RD ;2P
Adder
14.57
274693ROCKY RD ;1P
Adder
14.427
274764LEE CO EC;5U
Adder
12.204
274765LEE CO EC;6U
Adder
12.204
274762LEE CO EC;3U
Adder
12.175
274763LEE CO EC;4U
Adder
12.06
274697ROCKY RD ;3P
Adder
3.958
23652301WDPWR_K20
Solar/Wind Helper
0.168
23585401KL_K28_T16
Solar/Wind Helper
1.53
203955AF1-039 C O1
Solar/Wind Helper
0.432
944781AF1-143 GEN
Solar/Wind Helper
2.836
238120AE2-309 GEN
Solar/Wind Helper
0.507
962101AG1-054 GEN
Solar/Wind Helper
0.715
20083426SW_E13_K22
Solar/Wind Helper
0.064
241985AE1-237 GEN
Solar/Wind Helper
0.271
241967AE2-285_GEN
Solar/Wind Helper
0.696
241801AE1-079 GEN
Solar/Wind Helper
0.271
20088926STNY CRK
Solar/Wind Helper
0.928
946071AF1-272 GEN
Solar/Wind Helper
3.051
20084626FORWARD
Solar/Wind Helper
0.402
203940AF1-140 C
Solar/Wind Helper
0.446
20088626ARWF_N39
Solar/Wind Helper
1.362
20303426NA_O38_P22
Solar/Wind Helper
1.117
203853AF1-134 C O1
Solar/Wind Helper
0.534
946381AF1-302 GEN
Solar/Wind Helper
0.246
203952AE2-129 C
Solar/Wind Helper
0.529
203946AE2-131 C
Solar/Wind Helper
0.53
238217AF1-153 C O1
Solar/Wind Helper
0.262
20398826ARMNA MT
Solar/Wind Helper
1.656
209137AF2-361 C
Solar/Wind Helper
1.531
946751AF1-339 GEN
Solar/Wind Helper
0.5
209054AE2-059 GEN
Solar/Wind Helper
0.09
961431AF2-434 GEN
Solar/Wind Helper
0.499
208972BECR K09
Solar/Wind Helper
0.372
209029WAYMART-WD
Solar/Wind Helper
0.937
203979AG1-198 GEN
Solar/Wind Helper
0.297
211065PSPA IPP
Solar/Wind Helper
0.168
211065PSPA IPP
Solar/Wind Helper
0.168
203980AG1-197 GEN
Solar/Wind Helper
0.369
966111AG1-480 GEN
Solar/Wind Helper
0.082
20674128FR_U2-059
Solar/Wind Helper
0.004
964851AG1-348 GEN
Solar/Wind Helper
0.088
207471AF2-354 C
Solar/Wind Helper
0.184
20674928WA_W3-044
Solar/Wind Helper
0.107
20676228FRD_X1-012
Solar/Wind Helper
0.1
217204WCALDSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217081WEATEXAS C
Solar/Wind Helper
0.014
20671828STAW2-080
Solar/Wind Helper
0.029
207442AE1-156 GEN
Solar/Wind Helper
0.351
20676128MHD_W3-029
Solar/Wind Helper
0.103
20673828FLE_V3-070
Solar/Wind Helper
0.097
218440SUMMTASSOC C
Solar/Wind Helper
0.018
20716928W4-060COL
Solar/Wind Helper
0.055
20720628TIN_W1-124
Solar/Wind Helper
0.203
963391AG1-188 GEN
Solar/Wind Helper
0.088
20714928UPF_X1-085
Solar/Wind Helper
0.005
963401AG1-189 GEN
Solar/Wind Helper
0.06
20390526W1-045 C
Solar/Wind Helper
0.357
219615MILLCREEK C
Solar/Wind Helper
0.028
219921AF1-264
Solar/Wind Helper
0.054
203947AF1-006 C
Solar/Wind Helper
0.527
230407AD2-065 C
Solar/Wind Helper
0.042
230433AD2-135 GEN
Solar/Wind Helper
0.018
233939AC1-091 C
Solar/Wind Helper
0.361
233970AC1-092 C
Solar/Wind Helper
0.361
233901CHERRYDALE C
Solar/Wind Helper
0.24
232408W1-005 C
Solar/Wind Helper
0.523
232410W1-006 C
Solar/Wind Helper
0.523
233946AB2-136 GEN
Solar/Wind Helper
0.586
234036AF2-325 C
Solar/Wind Helper
0.043
233987AB2-037 GEN
Solar/Wind Helper
2.415
233944AB2-135 GEN
Solar/Wind Helper
0.607
232424Y1-079 C
Solar/Wind Helper
0.12
233933AB2-153 GEN
Solar/Wind Helper
0.24
235063AE1-101 C2
Solar/Wind Helper
1.463
205916AD1-020 GEN
Solar/Wind Helper
1.711
237002AB1-128_GEN
Solar/Wind Helper
0.388
237001AB1-127_GEN
Solar/Wind Helper
0.388
235020AA1-095 C
Solar/Wind Helper
0.045
23777901MDS_W4-102
Solar/Wind Helper
0.15
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
237034AC2-136 C
Solar/Wind Helper
0.194
238175AF1-290_GEN
Solar/Wind Helper
0.123
237025AB1-124 C
Solar/Wind Helper
0.145
237006AB1-125 GEN
Solar/Wind Helper
0.109
23777801MSM_W1-116
Solar/Wind Helper
0.1
238169AE2-226 GEN1
Solar/Wind Helper
0.555
238170AE2-226 GEN2
Solar/Wind Helper
0.555
971341AH1-150 GEN
Solar/Wind Harmer
3.998
971343AH1-151 GEN
Solar/Wind Harmer
3.998
24289405MTG1
50/50
11.351
243186AF1-051 GEN
50/50
12.478
24318705GVG2
50/50
11.615
24721805FLATG3
50/50
2.756
24721705FLATG2
50/50
50.519
24723205RIVRG3
Adder
36.021
24686105CER G3
Adder
15.629
24686505CER G6
Adder
15.608
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
970947AG2-589 GEN
Solar/Wind Harmer
0.412
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
971403AH1-188 GEN
Solar/Wind Harmer
16.785
962761AG1-125 GEN
Solar/Wind Harmer
46.194
970149AG2-104 GEN
Solar/Wind Harmer
49.891
970155AG2-107 GEN
Solar/Wind Harmer
29.498
971315AH1-136 GEN
Solar/Wind Harmer
2.232
927014AC1-188 GEN
Solar/Wind Harmer
0.007
971687AH1-348 GEN
Solar/Wind Harmer
1.067
24728305BUCHG2
Adder
6.831
970333AG2-219 GEN
Solar/Wind Harmer
7.406
970091AG2-072 GEN
Adder
113.581
945681AF1-233 GEN
Solar/Wind Harmer
19.197
252507AC2-088 GEN
Solar/Wind Harmer
0.46
25196808ZIMRHP
Adder
109.116
339216AC1-074 GEN
Solar/Wind Harmer
0.274
25196008MFTGT1
Adder
1.989
25194608D.CRK4
Adder
2.348
3429241JKCT 3G
Adder
16.894
3429421JKCT 10G
Adder
11.865
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
9.904
270263AC1-001 GEN
Solar/Wind Harmer
0.987
270445AC2-157 GEN2
Solar/Wind Harmer
0.004
971565AH1-281 GEN
Solar/Wind Harmer
1.958
971821AH1-427 GEN
Solar/Wind Harmer
9.786
24735205WLF2G2
Adder
8.08
970773AG2-487 GEN
Solar/Wind Harmer
1.7
24728605AND G2
Adder
5.27
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0.001
970613AG2-401 GEN
Solar/Wind Harmer
6.984
253370AE2-315 SEC1
Adder
2.733
253371AE2-315 SEC2
Adder
2.585
970273AG2-179 GEN
Solar/Wind Harmer
3.322
276903AD2-071 C
Solar/Wind Harmer
10.574
963741AG1-226 GEN
Solar/Wind Harmer
22.385
970291AG2-192 GEN
Solar/Wind Harmer
1.228
270005AE1-210 C O1
Solar/Wind Harmer
2.046
965031AG1-367 GEN
Solar/Wind Harmer
9.442
270032AE2-172
Solar/Wind Harmer
6.293
25326309TAIT D
Adder
1.481
964901AG1-354 GEN
Solar/Wind Harmer
14.138
960071AF2-298 GEN
Solar/Wind Harmer
4.694
970825AG2-519 GEN
Solar/Wind Harmer
3.343
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.004
24791305MDL-5G
Solar/Wind Harmer
0.001
970245AG2-165 GEN
Solar/Wind Harmer
4.056
962241AG1-070 GEN
Solar/Wind Harmer
5.098
945371AF1-202 GEN
Solar/Wind Harmer
0.001
958861AF2-177 GEN
Solar/Wind Harmer
4.037
965911AG1-460 GEN
Solar/Wind Harmer
1.861
247536S-71 GEN
Solar/Wind Harmer
0.374
965651AG1-433 GEN
Solar/Wind Harmer
2.727
276615X2-022 GEN
Solar/Wind Harmer
0.098
963831AG1-236 GEN
Solar/Wind Harmer
3.623
274880W4-005 GEN4
Solar/Wind Harmer
0.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
11.601
972175AH1-670 GEN
Solar/Wind Harmer
7.662
274854TWINGROVE;U2
Solar/Wind Harmer
0.004
276726Z2-087_GEN
Solar/Wind Harmer
0.003
939741AE1-205 GEN
Solar/Wind Harmer
12.928
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
11.983
958381AF2-132 GEN
Solar/Wind Harmer
0.001
939401AE1-172 GEN
Solar/Wind Harmer
6.864
270055AF2-134 C O1
Solar/Wind Harmer
0.007
274877BISHOP HL;1U
Solar/Wind Harmer
0.308
253343AC1-166 GEN
Solar/Wind Harmer
0.004
253325AC1-069 GEN
Solar/Wind Harmer
0.014
970569AG2-363 GEN
Solar/Wind Harmer
27.46
971997AH1-543 GEN
Solar/Wind Harmer
4.802
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
276901AD2-066 C O1
Solar/Wind Harmer
0.009
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274773LINCOLN ;4U
Adder
11.055
274774LINCOLN ;5U
Adder
11.055
276158O29GEN2
Solar/Wind Harmer
0.001
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
276691AA1-018 GEN1
Solar/Wind Harmer
1.106
274745AC1-111 GEN9
Adder
7.316
276861AD2-134 GEN
Solar/Wind Harmer
0.164
274872LEEDK;1U
Solar/Wind Harmer
0.006
274761LEE CO EC;2U
Adder
12.175
274766LEE CO EC;7U
Adder
12.032
237046AF1-021 C
Solar/Wind Helper
0.577
238185AF2-356 C
Solar/Wind Helper
2.612
23751201ROTHROCK
Solar/Wind Helper
0.878
235054AD2-180 GEN
Solar/Wind Helper
2.032
23562501BACKB
Solar/Wind Helper
1.07
238117U2-030
Solar/Wind Helper
0.343
235531U2-073 GEN
Solar/Wind Helper
3.23
20089226LOOKOUT
Solar/Wind Helper
0.665
254303AC2-168 GEN
Solar/Wind Helper
0.173
241966AE1-183 GEN
Solar/Wind Helper
0.28
23751101LEADS_P59
Solar/Wind Helper
1.483
20088826HIGHLAND
Solar/Wind Helper
1.011
20094526CT_V3-030
Solar/Wind Helper
0.53
964201AG1-281 GEN
Solar/Wind Helper
0.544
238108AE1-109 GEN1
Solar/Wind Helper
0.102
964391AG1-301 GEN
Solar/Wind Helper
0.529
203954AE2-126 C
Solar/Wind Helper
0.522
238206AE2-263_GEN
Solar/Wind Helper
1.011
959471AF2-238 GEN
Solar/Wind Helper
0.517
203860AG1-193 C
Solar/Wind Helper
0.254
209067AE2-060 GEN
Solar/Wind Helper
0.091
946691AF1-333 GEN
Solar/Wind Helper
0.5
946741AF1-338 GEN
Solar/Wind Helper
0.5
961421AF2-433 GEN
Solar/Wind Helper
0.499
957921AF2-086 GEN
Solar/Wind Helper
0.493
961331AF2-424 GEN
Solar/Wind Helper
0.499
209027LOR2_Q27
Solar/Wind Helper
1.165
963071AG1-156 GEN
Solar/Wind Helper
1.625
963161AG1-165 GEN
Solar/Wind Helper
0.496
316095T157 G97
Solar/Wind Helper
1.154
23583801GRNGAP
Solar/Wind Helper
4.282
961971AG1-040 GEN
Solar/Wind Helper
0.492
203835AF1-098 GEN
Solar/Wind Helper
1.958
20674628WNG_W3-110
Solar/Wind Helper
0.097
207510AF2-138 C
Solar/Wind Helper
0.088
20676728BRNX1-095
Solar/Wind Helper
0.032
217169METRODIV C
Solar/Wind Helper
0.004
217211CAMDEN ST C
Solar/Wind Helper
0.005
20673728F2S_V4-070
Solar/Wind Helper
0.032
219249CENTRALDIV C
Solar/Wind Helper
0.011
219908AB1-139 C
Solar/Wind Helper
0.079
219919AE1-041 FULL
Solar/Wind Helper
0.004
218438BLK ROCK C
Solar/Wind Helper
0.029
219612MATRIX C
Solar/Wind Helper
0.025
20720528MAN_W1-024
Solar/Wind Helper
0.03
20714528FRN_Y2-051
Solar/Wind Helper
0.061
219276PARKLANDSO C
Solar/Wind Helper
0.095
20720828JCB_W4-025
Solar/Wind Helper
0.067
20715028HAN_X4-015
Solar/Wind Helper
0.061
20716028EGP_W2-019
Solar/Wind Helper
0.02
959561AF2-247 GEN
Solar/Wind Helper
0.022
219348LDSOLAR C
Solar/Wind Helper
0.121
219906AC1-017 C
Solar/Wind Helper
0.044
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219291REEVESSOUT C
Solar/Wind Helper
0.012
219912AD2-042 GEN
Solar/Wind Helper
0.158
219766PARADISE C
Solar/Wind Helper
0.057
219623KINSLEYBEA C
Solar/Wind Helper
0.002
228729W2-030 C
Solar/Wind Helper
0.116
230415AB2-049 C
Solar/Wind Helper
0.032
230430AE1-229_GEN
Solar/Wind Helper
3.539
233971AC1-093 C
Solar/Wind Helper
0.369
233996TM1833_GEN
Solar/Wind Helper
0.27
233997TMININ_4.2
Solar/Wind Helper
0.27
233952AC2-187 GEN
Solar/Wind Helper
0.24
232406W1-004 FULL
Solar/Wind Helper
0.523
233940AF2-379 C
Solar/Wind Helper
0.064
234015AF2-250 C
Solar/Wind Helper
0.039
233994AC2-023 GEN
Solar/Wind Helper
0.992
233982AB2-133 GEN
Solar/Wind Helper
0.369
233918AB1-142 GEN
Solar/Wind Helper
0.518
235067AD1-061 GEN
Solar/Wind Helper
0.433
205917AD1-020 ES
Solar/Wind Helper
0.368
238221AF1-254 C O1
Solar/Wind Helper
0.236
237030AB1-096 C
Solar/Wind Helper
0.063
223402AF1-300 C
Solar/Wind Helper
0.338
957471AF2-041 GEN
Solar/Wind Harmer
5.997
959081AF2-199 GEN
Solar/Wind Harmer
1.999
971067AG2-660 GEN
Solar/Wind Harmer
0.666
24289405MTG1
50/50
11.351
24318705GVG2
50/50
11.615
24722005FLATG5
50/50
2.756
24721905FLATG4
50/50
50.519
24686205CER G4
Adder
15.547
24686405CER G5
Adder
15.485
270053AF1-130 C
Solar/Wind Harmer
2.748
970153AG2-106 GEN
Solar/Wind Harmer
29.498
971191AH1-055 GEN
Solar/Wind Harmer
30.005
970913AG2-568 GEN
Solar/Wind Harmer
8.769
972103AH1-617 GEN
Solar/Wind Harmer
21.835
960911AF2-382 GEN
Solar/Wind Harmer
8.035
971461AH1-227 GEN
Solar/Wind Harmer
5.464
970243AG2-164 GEN
Solar/Wind Harmer
6.06
970519AG2-331 GEN
Solar/Wind Harmer
26.931
970699AG2-449 GEN
Solar/Wind Harmer
2.59
972167AH1-666 GEN
Solar/Wind Harmer
8.145
958171AF2-111 GEN
Solar/Wind Harmer
25.128
252510AF1-249 C
Solar/Wind Harmer
0.077
25196008MFTGT1
Adder
1.926
25194608D.CRK4
Adder
2.348
25196608WSDLE5
Adder
12.22
3429391JKCT 9G
Adder
11.865
970093AG2-073 GEN
Solar/Wind Harmer
9.929
253316AC1-085 GEN3
Solar/Wind Harmer
0.006
253433AC1-085 GEN1
Solar/Wind Harmer
0.005
946181AF1-283 GEN
Solar/Wind Harmer
12.875
253406AD2-031_GEN
Solar/Wind Harmer
0.735
966571AG1-526 GEN
Solar/Wind Harmer
21.864
270291AC1-194 GEN
Solar/Wind Harmer
7.771
253415AE1-040 GEN
Solar/Wind Harmer
0.004
972173AH1-669 GEN
Solar/Wind Harmer
4.843
270222AC2-111 GEN
Solar/Wind Harmer
4.893
972273AH1-721 GEN
Adder
114.731
270273AD2-016 GEN
Solar/Wind Harmer
0.998
270356AE2-297 GEN
Solar/Wind Harmer
0.013
24728705AND G3
Adder
11.022
24728505AND G1
Adder
5.27
970193AG2-126 GEN
Solar/Wind Harmer
14.303
270437AC2-090 C
Solar/Wind Harmer
0.004
253370AE2-315 SEC1
Adder
2.733
253371AE2-315 SEC2
Adder
2.585
270346AE1-212 GEN
Solar/Wind Harmer
8.4
970273AG2-179 GEN
Solar/Wind Harmer
5.694
960741AF2-365 GEN
Solar/Wind Harmer
4.731
970191AG2-125 GEN
Solar/Wind Harmer
2.433
247642Z2-115 C
Solar/Wind Harmer
0.004
970289AG2-191 GEN
Solar/Wind Harmer
1.039
970291AG2-192 GEN
Solar/Wind Harmer
0.944
958821AF2-173 GEN
Solar/Wind Harmer
13.219
270004AE1-209 GEN
Solar/Wind Harmer
2.046
946031AF1-268 GEN
Solar/Wind Harmer
8.936
339250AF1-203 GEN
Solar/Wind Harmer
0.001
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
9.369
971155AH1-034 GEN
Solar/Wind Harmer
10.922
970513AG2-328 GEN
Solar/Wind Harmer
4.056
970517AG2-330 GEN
Solar/Wind Harmer
24.338
962251AG1-071 GEN
Solar/Wind Harmer
5.847
942481AE2-261 GEN
Solar/Wind Harmer
27.825
276621W2-048 GEN
Solar/Wind Harmer
0.469
276838X2-022 GEN2
Solar/Wind Harmer
0.523
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
4.291
276668AB2-070 GEN1
Solar/Wind Harmer
0.339
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
943031AE2-326 GEN
Solar/Wind Harmer
4.828
274853TWINGROVE;U1
Solar/Wind Harmer
0.004
965091AG1-374 GEN
Solar/Wind Harmer
27.736
959611AF2-252 GEN
Solar/Wind Harmer
3.082
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
13.864
942111AE2-223 GEN
Solar/Wind Harmer
3.001
964401AG1-302 GEN
Solar/Wind Harmer
0.001
944531AF1-118 GEN
Solar/Wind Harmer
41.286
270535AF1-215 GEN1
Solar/Wind Harmer
0.011
274878BISHOP HL;2U
Solar/Wind Harmer
0.308
253338AC1-165 GEN
Solar/Wind Harmer
0.004
253333AC1-068 GEN
Solar/Wind Harmer
0.014
970571AG2-364 GEN
Solar/Wind Harmer
18.307
276889AE2-281 GEN
Solar/Wind Harmer
0.001
276897AD1-100 C
Solar/Wind Harmer
0.012
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
274772LINCOLN ;3U
Adder
11.055
276805AD2-038 GEN
Solar/Wind Harmer
0.003
276157O29GEN1
Solar/Wind Harmer
1.478
970707AG2-453 GEN
Solar/Wind Harmer
29.848
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
943121AE2-341 GEN
Solar/Wind Harmer
15.314
943591AF1-030 GEN
Solar/Wind Harmer
10.184
274855GSG-6 ;RU
Solar/Wind Harmer
0.335
274850MENDOTA H;RU
Solar/Wind Harmer
0.108
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.164
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
0.974
274760LEE CO EC;1U
Adder
12.175
274767LEE CO EC;8U
Adder
12.032
274729ELWOOD EC;1P
Adder
21.509
237048AF1-022 C
Solar/Wind Helper
0.228
237043AE2-125 C
Solar/Wind Helper
0.207
235058AG1-386 C
Solar/Wind Helper
0.514
964991AG1-363 GEN
Solar/Wind Helper
4.415
23750701CROSSCHOOL
Solar/Wind Helper
1.427
238118U2-030_1
Solar/Wind Helper
0.343
202652Y1-033 WT C
Solar/Wind Helper
0.655
20089126CSLMN_L13
Solar/Wind Helper
0.683
20089026BF_G21_K23
Solar/Wind Helper
0.541
238127S14_GEN_2
Solar/Wind Helper
0.81
254305AE2-115 C
Solar/Wind Helper
0.239
203818AF1-086 GEN
Solar/Wind Helper
1.887
203854AF2-039 C
Solar/Wind Helper
0.354
20334926Z1-069 C
Solar/Wind Helper
1.49
238202AE2-262_GEN
Solar/Wind Helper
1.063
941421AE2-139 GEN
Solar/Wind Helper
2.573
959441AF2-235 GEN
Solar/Wind Helper
0.255
200917MEHOOPANY_G
Solar/Wind Helper
2.428
209071AE2-133 GEN
Solar/Wind Helper
0.09
946731AF1-337 GEN
Solar/Wind Helper
0.5
212507AE2-042_GEN
Solar/Wind Helper
1.772
961341AF2-425 GEN
Solar/Wind Helper
0.499
212266LOR1
Solar/Wind Helper
0.054
961301AF2-421 GEN
Solar/Wind Helper
0.496
963151AG1-164 GEN
Solar/Wind Helper
0.496
316097T157 G90
Solar/Wind Helper
1.154
203830AF1-094 GEN
Solar/Wind Helper
0.495
20671928W4-073
Solar/Wind Helper
0.098
207518AF1-320_GEN
Solar/Wind Helper
1.718
207437AD2-070 GEN
Solar/Wind Helper
0.15
20675828AU_W4-064
Solar/Wind Helper
0.032
207439AE1-081 C O1
Solar/Wind Helper
0.02
20674328GAR_V4-001
Solar/Wind Helper
0.024
217208PARK ELE C
Solar/Wind Helper
0.005
217209CENTRL HS C
Solar/Wind Helper
0.009
20676428JCR_X2-075
Solar/Wind Helper
0.073
207528AF2-192 GEN
Solar/Wind Helper
0.082
20673628F1S_V4-069
Solar/Wind Helper
0.032
20675428EAM_W2-061
Solar/Wind Helper
0.017
962511AG1-100 GEN
Solar/Wind Helper
0.488
217213AMBOY SO C
Solar/Wind Helper
0.031
218428ETC SOLAR C
Solar/Wind Helper
0.005
205941AD2-115 GEN
Solar/Wind Helper
0.531
20742028HF_AC1-207
Solar/Wind Helper
0.15
20715228NPK_W1-113
Solar/Wind Helper
0.083
207454AA2-184 E
Solar/Wind Helper
0.331
219680HOPEWELLV C1
Solar/Wind Helper
0.003
963711AG1-223 GEN
Solar/Wind Helper
0.068
20714828MDF_W3-079
Solar/Wind Helper
0.139
207445AB1-138_GEN
Solar/Wind Helper
0.111
20720728JCB_W1-129
Solar/Wind Helper
0.061
219304NAMERICA C
Solar/Wind Helper
0.139
219686LUMSOLAR_N C
Solar/Wind Helper
0.042
219907AC1-030 C
Solar/Wind Helper
0.036
218660EHAMPSOLAR C
Solar/Wind Helper
0.035
219904AC1-010 C
Solar/Wind Helper
0.064
219258KINSLEYDEP C
Solar/Wind Helper
0.081
228728W1-130C
Solar/Wind Helper
0.057
230434AG1-499 GEN
Solar/Wind Helper
0.241
230511AF1-262
Solar/Wind Helper
0.015
233972AC1-094 C
Solar/Wind Helper
0.312
233998TM1NIN_3.36
Solar/Wind Helper
0.27
233954AC2-188 GEN
Solar/Wind Helper
0.24
232404W1-003 C
Solar/Wind Helper
0.523
233950AC2-186 GEN
Solar/Wind Helper
0.12
232428Y3-058 C
Solar/Wind Helper
0.349
232434Z2-077 GEN
Solar/Wind Helper
0.131
232426Y1-080 FULL
Solar/Wind Helper
0.04
233964AF2-378 GEN
Solar/Wind Helper
0.043
232422X3-066 FULL
Solar/Wind Helper
0.118
233930AB2-032 GEN
Solar/Wind Helper
0.392
233915AB1-141 GEN
Solar/Wind Helper
0.518
966131AG1-482 GEN
Solar/Wind Helper
0.139
235062AE1-101 C1
Solar/Wind Helper
1.463
237038AE2-054 C
Solar/Wind Helper
0.238
237080AD1-060 GEN
Solar/Wind Helper
0.296
23779801AA1-109
Solar/Wind Helper
0.168
223401AF1-299 GEN
Solar/Wind Helper
0.338
959091AF2-200 GEN
Solar/Wind Harmer
3.998
944201AF1-088_MTX
Adder
163.563
957141AF2-008_MTX
Adder
81.782
NYPJM->LTFIMP_NY
CLTF
6.276
LGEELTFEXP_LGEE->PJM
CLTF
9.844
WECLTFEXP_WEC->PJM
CLTF
5.002
AG2-052LTFEXP_AG2-052->PJM
LTF
0.306
AH1-155LTFEXP_AH1-155->PJM
LTF
0.459
LAGNLTFEXP_LAGN->PJM
CLTF
24.864
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.24
TVALTFEXP_TVA->PJM
CLTF
12.63
CBM West 1LTFEXP_CBM-W1->PJM
CBM
170.264
CBM South 1LTFEXP_CBM-S1->PJM
CBM
48.581
MECLTFEXP_MEC->PJM
CLTF
21.939
SIGELTFEXP_SIGE->PJM
CLTF
0.729
CPLELTFEXP_CPLE->PJM
CLTF
6.557
CBM West 2LTFEXP_CBM-W2->PJM
CBM
173.156

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.86 %
Rating:4558.0 MVA
Rating Type:A
MVA to Mitigate:4961.85
MW Contribution:3.12
Bus #Bus NameTypeMW Contribution
24289405MTG1
50/50
10.907
243186AF1-051 GEN
50/50
11.679
24318705GVG2
50/50
10.872
24721805FLATG3
50/50
2.473
24721705FLATG2
50/50
45.331
24723205RIVRG3
Adder
32.794
24686105CER G3
Adder
14.139
24686505CER G6
Adder
14.12
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
970947AG2-589 GEN
Solar/Wind Harmer
0.368
971403AH1-188 GEN
Solar/Wind Harmer
15.305
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
24728305BUCHG2
Adder
6.221
971315AH1-136 GEN
Solar/Wind Harmer
1.928
971687AH1-348 GEN
Solar/Wind Harmer
0.947
927014AC1-188 GEN
Solar/Wind Harmer
0.005
24735205WLF2G2
Adder
7.162
971329AH1-144 GEN
Solar/Wind Harmer
6.901
970091AG2-072 GEN
Adder
86.947
970333AG2-219 GEN
Solar/Wind Harmer
5.608
945681AF1-233 GEN
Solar/Wind Harmer
14.563
3429241JKCT 3G
Adder
13.068
971821AH1-427 GEN
Solar/Wind Harmer
7.658
3429421JKCT 10G
Adder
9.139
339216AC1-074 GEN
Solar/Wind Harmer
0.209
970273AG2-179 GEN
Solar/Wind Harmer
2.644
971565AH1-281 GEN
Solar/Wind Harmer
1.508
252507AC2-088 GEN
Solar/Wind Harmer
0.341
964901AG1-354 GEN
Solar/Wind Harmer
11.154
25196808ZIMRHP
Adder
80.408
962241AG1-070 GEN
Solar/Wind Harmer
4.025
25196008MFTGT1
Adder
1.465
270445AC2-157 GEN2
Solar/Wind Harmer
0.003
25194608D.CRK4
Adder
1.71
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.086
962761AG1-125 GEN
Solar/Wind Harmer
27.465
970149AG2-104 GEN
Solar/Wind Harmer
29.663
970155AG2-107 GEN
Solar/Wind Harmer
17.538
270336AE1-100 GEN
Solar/Wind Harmer
0.004
270263AC1-001 GEN
Solar/Wind Harmer
0.699
24728605AND G2
Adder
3.761
970773AG2-487 GEN
Solar/Wind Harmer
1.204
971367AH1-164 GEN
Solar/Wind Harmer
2.344
963741AG1-226 GEN
Solar/Wind Harmer
15.844
965911AG1-460 GEN
Solar/Wind Harmer
1.332
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.849
276615X2-022 GEN
Solar/Wind Harmer
0.069
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.002
963831AG1-236 GEN
Solar/Wind Harmer
2.568
274880W4-005 GEN4
Solar/Wind Harmer
0.001
276903AD2-071 C
Solar/Wind Harmer
7.334
972175AH1-670 GEN
Solar/Wind Harmer
5.394
24791305MDL-5G
Solar/Wind Harmer
0.001
970291AG2-192 GEN
Solar/Wind Harmer
0.846
270032AE2-172
Solar/Wind Harmer
4.336
270005AE1-210 C O1
Solar/Wind Harmer
1.405
965031AG1-367 GEN
Solar/Wind Harmer
6.485
970825AG2-519 GEN
Solar/Wind Harmer
2.296
274854TWINGROVE;U2
Solar/Wind Harmer
0.003
253370AE2-315 SEC1
Adder
1.856
253371AE2-315 SEC2
Adder
1.755
276726Z2-087_GEN
Solar/Wind Harmer
0.002
939741AE1-205 GEN
Solar/Wind Harmer
9.009
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
7.976
274877BISHOP HL;1U
Solar/Wind Harmer
0.214
276158O29GEN2
Solar/Wind Harmer
0.001
960071AF2-298 GEN
Solar/Wind Harmer
3.157
25326309TAIT D
Adder
0.995
970569AG2-363 GEN
Solar/Wind Harmer
18.972
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
8.432
274766LEE CO EC;7U
Adder
8.332
945371AF1-202 GEN
Solar/Wind Harmer
0.001
247536S-71 GEN
Solar/Wind Harmer
0.254
971475AH1-234 GEN
Solar/Wind Harmer
3.061
970819AG2-516 GEN
Solar/Wind Harmer
7.565
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
972235AH1-702 GEN1
Adder
2.276
939401AE1-172 GEN
Solar/Wind Harmer
4.71
274822ROCKFORD ;11
Adder
17.71
957471AF2-041 GEN
Solar/Wind Harmer
18.878
959081AF2-199 GEN
Solar/Wind Harmer
6.293
971067AG2-660 GEN
Solar/Wind Harmer
2.098
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.18
971997AH1-543 GEN
Solar/Wind Harmer
3.301
274828WAUKEGAN ;BP
Adder
9.895
274682WAUKEGAN ;7U
Adder
16.093
274745AC1-111 GEN9
Adder
4.992
237046AF1-021 C
Solar/Wind Helper
0.433
238185AF2-356 C
Solar/Wind Helper
1.954
23751201ROTHROCK
Solar/Wind Helper
0.662
235054AD2-180 GEN
Solar/Wind Helper
1.52
23562501BACKB
Solar/Wind Helper
0.806
970245AG2-165 GEN
Solar/Wind Harmer
1.358
243186AF1-051 GEN
50/50
11.679
24723005RIVRG1
Adder
32.794
24723105RIVRG2
Adder
32.794
24685805CER G1
Adder
14.046
24685905CER G2
Adder
14.046
944971AF1-162 GEN
Solar/Wind Harmer
11.031
24728205BUCHG1
Adder
6.221
971225AH1-072 GEN
Solar/Wind Harmer
1.893
971227AH1-073 GEN
Solar/Wind Harmer
1.893
971277AH1-098 GEN
Solar/Wind Harmer
3.403
960161AF2-307 GEN
Solar/Wind Harmer
5.337
971073AG2-665 GEN
Solar/Wind Harmer
7.21
270583AD2-179 GEN
Solar/Wind Harmer
7.911
270186AC1-089 GEN
Solar/Wind Harmer
0.005
970239AG2-162 GEN
Solar/Wind Harmer
1.961
962581AG1-107 GEN
Solar/Wind Harmer
0.002
942891AE2-308 GEN
Solar/Wind Harmer
7.714
972043AH1-570 GEN
Solar/Wind Harmer
1.999
972045AH1-571 GEN
Solar/Wind Harmer
1.602
339221AD2-048_GEN
Solar/Wind Harmer
0.005
971125AH1-004 GEN
Solar/Wind Harmer
3.056
970107AG2-081 GEN
Solar/Wind Harmer
2.292
970235AG2-159 GEN
Solar/Wind Harmer
4.628
970235AG2-159 GEN
Solar/Wind Harmer
2.656
966021AG1-471 GEN
Solar/Wind Harmer
4.054
252509AD1-136 GEN
Solar/Wind Harmer
0.038
971485AH1-239 GEN
Solar/Wind Harmer
5.998
971081AG2-670 GEN
Solar/Wind Harmer
5.621
970653AG2-424 GEN
Solar/Wind Harmer
3.613
970653AG2-424 GEN
Solar/Wind Harmer
1.872
964571AG1-320 GEN
Solar/Wind Harmer
6.819
339255AE2-071 GEN
Solar/Wind Harmer
-0.122
964781AG1-341 GEN
Solar/Wind Harmer
7.848
25183208HLCRTG
Solar/Wind Harmer
0.011
252519AF1-045_GEN
Solar/Wind Harmer
6.373
252516AE2-318_GEN
Solar/Wind Harmer
5.653
270444AC2-157 GEN1
Solar/Wind Harmer
0.003
971587AH1-292 GEN
Solar/Wind Harmer
5.336
25194408D.CRK1
Adder
7.868
25194508D.CRK3
Adder
1.471
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
945391AF1-204 GEN
Solar/Wind Harmer
7.288
24728805RICHG1
Adder
3.669
24728905RICHG2
Adder
3.669
970241AG2-163 GEN
Solar/Wind Harmer
3.905
276916AD2-100_GEN
Solar/Wind Harmer
14.016
276911AD2-131_GEN
Solar/Wind Harmer
0.923
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
966841AG1-555 GEN
Solar/Wind Harmer
0.746
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
270383AD1-128 GEN
Solar/Wind Harmer
0.004
971613AH1-306 GEN
Solar/Wind Harmer
3.122
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
970825AG2-519 GEN
Solar/Wind Harmer
7.169
960441AF2-335 GEN
Solar/Wind Harmer
6.468
960611AF2-352 GEN
Solar/Wind Harmer
2.156
253370AE2-315 SEC1
Adder
1.856
970883AG2-550 GEN
Solar/Wind Harmer
6.374
970885AG2-551 GEN
Solar/Wind Harmer
2.125
276782AC1-033 GEN
Solar/Wind Harmer
0.001
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.25
276646AC1-214 GEN2
Solar/Wind Harmer
0.25
270599AE1-208 GEN
Solar/Wind Harmer
5.819
270031AE2-169
Solar/Wind Harmer
3.492
276741O09 GEN1
Solar/Wind Harmer
0.226
276708O09 GEN2
Solar/Wind Harmer
0.226
972267AH1-718 GEN
Adder
3.783
25322209TAIT E
Adder
8.86
25322209TAIT E
Adder
8.661
276603SUBLETTE C
Solar/Wind Harmer
0
274764LEE CO EC;5U
Adder
8.452
274765LEE CO EC;6U
Adder
8.452
274762LEE CO EC;3U
Adder
8.432
274763LEE CO EC;4U
Adder
8.352
938861AE1-114 GEN
Solar/Wind Harmer
3.58
274856ECOGROVE ;U1
Solar/Wind Harmer
0.149
276611AD2-172 GEN
Solar/Wind Harmer
0.002
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
971341AH1-150 GEN
Solar/Wind Harmer
12.585
971343AH1-151 GEN
Solar/Wind Harmer
12.585
247621Y3-024
Adder
0.216
274683WAUKEGAN ;8U
Adder
18.876
274683WAUKEGAN ;8U
Adder
15.912
274696ROCKY RD ;4P
Adder
10.207
274695ROCKY RD ;2P
Adder
9.971
274693ROCKY RD ;1P
Adder
9.873
274697ROCKY RD ;3P
Adder
2.709
23652301WDPWR_K20
Solar/Wind Helper
0.126
23585401KL_K28_T16
Solar/Wind Helper
1.149
970321AG2-212 GEN
Solar/Wind Harmer
1.358
24289405MTG1
50/50
10.907
24318705GVG2
50/50
10.872
24722005FLATG5
50/50
2.473
24721905FLATG4
50/50
45.331
24686205CER G4
Adder
14.065
24686405CER G5
Adder
14.009
270053AF1-130 C
Solar/Wind Harmer
2.49
970913AG2-568 GEN
Solar/Wind Harmer
8.136
971191AH1-055 GEN
Solar/Wind Harmer
25.624
960911AF2-382 GEN
Solar/Wind Harmer
7.284
972103AH1-617 GEN
Solar/Wind Harmer
19.189
971461AH1-227 GEN
Solar/Wind Harmer
4.855
270346AE1-212 GEN
Solar/Wind Harmer
7.86
943031AE2-326 GEN
Solar/Wind Harmer
4.498
971331AH1-145 GEN
Solar/Wind Harmer
10.953
247619Y1-049
Adder
0.497
958121AF2-106 GEN
Solar/Wind Harmer
0.001
970243AG2-164 GEN
Solar/Wind Harmer
4.588
970519AG2-331 GEN
Solar/Wind Harmer
20.392
970699AG2-449 GEN
Solar/Wind Harmer
1.961
970093AG2-073 GEN
Solar/Wind Harmer
7.734
972167AH1-666 GEN
Solar/Wind Harmer
6.174
972273AH1-721 GEN
Adder
91.659
966571AG1-526 GEN
Solar/Wind Harmer
17.032
3429391JKCT 9G
Adder
9.139
970273AG2-179 GEN
Solar/Wind Harmer
4.533
270291AC1-194 GEN
Solar/Wind Harmer
5.957
958171AF2-111 GEN
Solar/Wind Harmer
18.792
339250AF1-203 GEN
Solar/Wind Harmer
0.001
960741AF2-365 GEN
Solar/Wind Harmer
3.705
971155AH1-034 GEN
Solar/Wind Harmer
8.639
962251AG1-071 GEN
Solar/Wind Harmer
4.615
25196008MFTGT1
Adder
1.418
252510AF1-249 C
Solar/Wind Harmer
0.056
25194608D.CRK4
Adder
1.71
25196608WSDLE5
Adder
8.886
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
9.211
970153AG2-106 GEN
Solar/Wind Harmer
17.538
253406AD2-031_GEN
Solar/Wind Harmer
0.522
970193AG2-126 GEN
Solar/Wind Harmer
10.289
24728705AND G3
Adder
7.865
24728505AND G1
Adder
3.761
270356AE2-297 GEN
Solar/Wind Harmer
0.009
270222AC2-111 GEN
Solar/Wind Harmer
3.451
253415AE1-040 GEN
Solar/Wind Harmer
0.003
270030AE2-140 GEN
Solar/Wind Harmer
13.595
942481AE2-261 GEN
Solar/Wind Harmer
19.91
972173AH1-669 GEN
Solar/Wind Harmer
3.31
270437AC2-090 C
Solar/Wind Harmer
0.003
276621W2-048 GEN
Solar/Wind Harmer
0.333
276838X2-022 GEN2
Solar/Wind Harmer
0.372
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
3.038
276668AB2-070 GEN1
Solar/Wind Harmer
0.24
247642Z2-115 C
Solar/Wind Harmer
0.003
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.514
270273AD2-016 GEN
Solar/Wind Harmer
0.675
970289AG2-191 GEN
Solar/Wind Harmer
0.716
970291AG2-192 GEN
Solar/Wind Harmer
0.651
958821AF2-173 GEN
Solar/Wind Harmer
9.079
270004AE1-209 GEN
Solar/Wind Harmer
1.405
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
965091AG1-374 GEN
Solar/Wind Harmer
19.404
959611AF2-252 GEN
Solar/Wind Harmer
2.156
253370AE2-315 SEC1
Adder
1.856
253371AE2-315 SEC2
Adder
1.755
942111AE2-223 GEN
Solar/Wind Harmer
2.091
946031AF1-268 GEN
Solar/Wind Harmer
6.117
970191AG2-125 GEN
Solar/Wind Harmer
1.65
965931AG1-462 GEN
Solar/Wind Harmer
16.291
274878BISHOP HL;2U
Solar/Wind Harmer
0.214
276157O29GEN1
Solar/Wind Harmer
1.026
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
970571AG2-364 GEN
Solar/Wind Harmer
12.648
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
8.432
274767LEE CO EC;8U
Adder
8.332
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
1.979
959091AF2-200 GEN
Solar/Wind Harmer
12.585
274682WAUKEGAN ;7U
Adder
16.093
274729ELWOOD EC;1P
Adder
6.64
237048AF1-022 C
Solar/Wind Helper
0.172
237043AE2-125 C
Solar/Wind Helper
0.155
235058AG1-386 C
Solar/Wind Helper
0.383
970513AG2-328 GEN
Solar/Wind Harmer
1.358
970517AG2-330 GEN
Solar/Wind Harmer
8.151
24721605FLATG1
50/50
2.473
972203AH1-686 GEN
Adder
3.978
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
957241AF2-018 GEN
Solar/Wind Harmer
-0.002
24477305BRIDGE
Adder
0.546
270399AC1-101 GEN
Solar/Wind Harmer
3.444
270400AC1-102 GEN
Solar/Wind Harmer
3.444
941621AE2-160 GEN
Adder
4.703
970281AG2-184 GEN
Solar/Wind Harmer
20.149
972143AH1-644 GEN
Solar/Wind Harmer
10.394
971313AH1-133 GEN
Solar/Wind Harmer
9.492
270132AB1-180 C
Adder
0.159
971061AG2-657 GEN
Solar/Wind Harmer
5.654
24734705WLF1G3
Adder
7.306
24734805WLF1G4
Adder
7.306
24734905WLF1G5
Adder
7.306
971985AH1-537 GEN
Solar/Wind Harmer
2.617
24735105WLF2G1
Adder
7.162
966391AG1-508 GEN
Solar/Wind Harmer
1.328
970879AG2-548 GEN
Solar/Wind Harmer
7.21
971981AH1-535 GEN
Solar/Wind Harmer
5.272
270367AC2-061_GEN
Solar/Wind Harmer
0.006
972163AH1-664 GEN
Solar/Wind Harmer
8.62
972165AH1-665 GEN
Solar/Wind Harmer
6.904
3429211JKCT 2G
Adder
12.898
965401AG1-405 GEN
Solar/Wind Harmer
4.386
965411AG1-406 GEN
Solar/Wind Harmer
2.821
339211AE2-254 GEN
Solar/Wind Harmer
0.003
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
970455AG2-298 GEN
Solar/Wind Harmer
5.018
25196108MFTGT2
Adder
1.614
25196108MFTGT2
Adder
1.499
252524AE2-267 GEN
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
9.147
25196308WSDLE2
Adder
9.067
25196208WSDLE1
Adder
9.045
25196708WSDLE6
Adder
9.022
25196508WSDLE4
Adder
8.795
962771AG1-126 GEN
Solar/Wind Harmer
27.465
270340AC2-060 GEN
Solar/Wind Harmer
0.008
270069AE2-166 C O1
Solar/Wind Harmer
0.005
944221AF1-090 GEN
Solar/Wind Harmer
3.946
963841AG1-237 GEN
Solar/Wind Harmer
2.88
270240V3-007_GEN2
Solar/Wind Harmer
0.002
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.24
276848AB2-070 GEN3
Solar/Wind Harmer
0.239
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
270269AC2-059
Solar/Wind Harmer
0.004
970289AG2-191 GEN
Solar/Wind Harmer
1.237
270594AE1-207 GEN
Solar/Wind Harmer
7.284
25306009OHH W.
Adder
2.673
970115AG2-085 GEN
Solar/Wind Harmer
2.587
253372AE2-315 SEC3
Adder
1.755
253372AE2-315 SEC3
Adder
1.755
971673AH1-337 GEN
Solar/Wind Harmer
4.2
971029AG2-637 GEN
Solar/Wind Harmer
9.661
276655WTG1_EQ
Solar/Wind Harmer
0.003
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
6.757
941731AE2-173 GEN
Solar/Wind Harmer
5.363
253349AC2-067 GEN
Solar/Wind Harmer
2.02
253400AC2-068 GEN
Solar/Wind Harmer
0.812
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
946321AF1-296 GEN
Solar/Wind Harmer
3.573
971611AH1-305 GEN
Solar/Wind Harmer
3.799
270543AE2-219 C
Solar/Wind Harmer
0.004
957751AF2-069 GEN
Solar/Wind Harmer
0.21
970169AG2-114 GEN
Solar/Wind Harmer
6.359
971609AH1-304 GEN
Solar/Wind Harmer
1.037
961011AF2-392 GEN
Solar/Wind Harmer
3.717
926823AC1-168 GEN
Solar/Wind Harmer
1.076
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971681AH1-341 GEN
Solar/Wind Harmer
10.171
945581AF1-223 GEN
Solar/Wind Harmer
0
276612AE2-035 GEN
Solar/Wind Harmer
0.002
274823ROCKFORD ;21
Adder
17.581
971171AH1-044 GEN
Solar/Wind Harmer
12.585
274746AC1-111 G10
Adder
4.992
274744AC1-111 GEN8
Adder
4.992
23750501ELLIOTTS
Solar/Wind Helper
0.594
944201AF1-088_MTX
Adder
121.273
957141AF2-008_MTX
Adder
60.637
NYPJM->LTFIMP_NY
CLTF
4.59
LGEELTFEXP_LGEE->PJM
CLTF
7.503
WECLTFEXP_WEC->PJM
CLTF
3.454
AG2-052LTFEXP_AG2-052->PJM
LTF
0.209
AH1-155LTFEXP_AH1-155->PJM
LTF
0.313
LAGNLTFEXP_LAGN->PJM
CLTF
19.803
CBM South 2LTFEXP_CBM-S2->PJM
CBM
23.164
TVALTFEXP_TVA->PJM
CLTF
10.26
CBM West 1LTFEXP_CBM-W1->PJM
CBM
116.498
CBM South 1LTFEXP_CBM-S1->PJM
CBM
38.98
MECLTFEXP_MEC->PJM
CLTF
15.75
SIGELTFEXP_SIGE->PJM
CLTF
0.547
CPLELTFEXP_CPLE->PJM
CLTF
6.38
CBM West 2LTFEXP_CBM-W2->PJM
CBM
132.776

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P1-2_#7422_16_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7422_16_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.56 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5885.34
MW Contribution:3.77
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
2.714
972203AH1-686 GEN
Adder
4.544
957241AF2-018 GEN
Solar/Wind Harmer
-0.002
270399AC1-101 GEN
Solar/Wind Harmer
4.077
270400AC1-102 GEN
Solar/Wind Harmer
4.077
24477305BRIDGE
Adder
0.637
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
971313AH1-133 GEN
Solar/Wind Harmer
12.016
941621AE2-160 GEN
Adder
5.66
966391AG1-508 GEN
Solar/Wind Harmer
1.802
970281AG2-184 GEN
Solar/Wind Harmer
24.373
972143AH1-644 GEN
Solar/Wind Harmer
12.573
270132AB1-180 C
Adder
0.198
24734705WLF1G3
Adder
9.185
24734805WLF1G4
Adder
9.185
24734905WLF1G5
Adder
9.185
24735105WLF2G1
Adder
9.002
971061AG2-657 GEN
Solar/Wind Harmer
6.864
971985AH1-537 GEN
Solar/Wind Harmer
3.047
971981AH1-535 GEN
Solar/Wind Harmer
6.609
270069AE2-166 C O1
Solar/Wind Harmer
0.007
970879AG2-548 GEN
Solar/Wind Harmer
8.448
965401AG1-405 GEN
Solar/Wind Harmer
5.328
965411AG1-406 GEN
Solar/Wind Harmer
3.428
270367AC2-061_GEN
Solar/Wind Harmer
0.007
3429211JKCT 2G
Adder
15.52
339211AE2-254 GEN
Solar/Wind Harmer
0.004
972163AH1-664 GEN
Solar/Wind Harmer
10.275
972165AH1-665 GEN
Solar/Wind Harmer
8.229
339243AC2-075 GEN1
Solar/Wind Harmer
0.002
970455AG2-298 GEN
Solar/Wind Harmer
6.053
25196108MFTGT2
Adder
1.926
25196108MFTGT2
Adder
1.788
252524AE2-267 GEN
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
10.91
25196308WSDLE2
Adder
10.815
25196208WSDLE1
Adder
10.788
25196708WSDLE6
Adder
10.761
25196508WSDLE4
Adder
10.49
270340AC2-060 GEN
Solar/Wind Harmer
0.01
962771AG1-126 GEN
Solar/Wind Harmer
32.213
944221AF1-090 GEN
Solar/Wind Harmer
4.776
963841AG1-237 GEN
Solar/Wind Harmer
3.474
270240V3-007_GEN2
Solar/Wind Harmer
0.002
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.29
276848AB2-070 GEN3
Solar/Wind Harmer
0.289
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
1.493
270594AE1-207 GEN
Solar/Wind Harmer
8.791
270269AC2-059
Solar/Wind Harmer
0.004
970115AG2-085 GEN
Solar/Wind Harmer
3.124
276655WTG1_EQ
Solar/Wind Harmer
0.003
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
8.194
941731AE2-173 GEN
Solar/Wind Harmer
6.503
25306009OHH W.
Adder
3.223
971673AH1-337 GEN
Solar/Wind Harmer
5.07
253372AE2-315 SEC3
Adder
2.117
253372AE2-315 SEC3
Adder
2.117
971029AG2-637 GEN
Solar/Wind Harmer
11.666
946321AF1-296 GEN
Solar/Wind Harmer
4.345
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
253349AC2-067 GEN
Solar/Wind Harmer
2.438
253400AC2-068 GEN
Solar/Wind Harmer
0.981
957751AF2-069 GEN
Solar/Wind Harmer
0.255
971611AH1-305 GEN
Solar/Wind Harmer
4.596
970169AG2-114 GEN
Solar/Wind Harmer
7.718
270543AE2-219 C
Solar/Wind Harmer
0.005
961011AF2-392 GEN
Solar/Wind Harmer
4.519
926823AC1-168 GEN
Solar/Wind Harmer
1.307
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
971681AH1-341 GEN
Solar/Wind Harmer
12.366
971609AH1-304 GEN
Solar/Wind Harmer
1.254
276612AE2-035 GEN
Solar/Wind Harmer
0.002
274823ROCKFORD ;21
Adder
21.377
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971171AH1-044 GEN
Solar/Wind Harmer
15.301
971675AH1-338 GEN
Solar/Wind Harmer
2.979
945581AF1-223 GEN
Solar/Wind Harmer
0.001
274746AC1-111 G10
Adder
6.069
274744AC1-111 GEN8
Adder
6.069
23750501ELLIOTTS
Solar/Wind Helper
0.635
238126S14_GEN_1
Solar/Wind Helper
0.687
238109AE1-109 GEN2
Solar/Wind Helper
0.088
238110AE1-109 GEN3
Solar/Wind Helper
0.088
20092526R32
Solar/Wind Helper
1.053
24289405MTG1
50/50
11.79
243186AF1-051 GEN
50/50
12.748
24318705GVG2
50/50
11.866
24721805FLATG3
50/50
2.714
24721705FLATG2
50/50
49.755
24723205RIVRG3
Adder
37.637
24686105CER G3
Adder
16.224
24686505CER G6
Adder
16.203
971403AH1-188 GEN
Solar/Wind Harmer
18.202
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
970947AG2-589 GEN
Solar/Wind Harmer
0.42
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
24728305BUCHG2
Adder
7.763
971687AH1-348 GEN
Solar/Wind Harmer
1.161
971329AH1-144 GEN
Solar/Wind Harmer
9.676
971315AH1-136 GEN
Solar/Wind Harmer
2.301
24735205WLF2G2
Adder
9.002
927014AC1-188 GEN
Solar/Wind Harmer
0.006
971367AH1-164 GEN
Solar/Wind Harmer
3.536
270336AE1-100 GEN
Solar/Wind Harmer
0.005
970091AG2-072 GEN
Adder
103.033
970333AG2-219 GEN
Solar/Wind Harmer
6.64
3429241JKCT 3G
Adder
15.723
971821AH1-427 GEN
Solar/Wind Harmer
9.259
3429421JKCT 10G
Adder
10.993
945681AF1-233 GEN
Solar/Wind Harmer
17.357
970273AG2-179 GEN
Solar/Wind Harmer
3.221
943811AF1-049 GEN
Solar/Wind Harmer
-0.002
339216AC1-074 GEN
Solar/Wind Harmer
0.25
971565AH1-281 GEN
Solar/Wind Harmer
1.817
964901AG1-354 GEN
Solar/Wind Harmer
13.566
962241AG1-070 GEN
Solar/Wind Harmer
4.9
252507AC2-088 GEN
Solar/Wind Harmer
0.405
25196808ZIMRHP
Adder
95.812
25196008MFTGT1
Adder
1.747
270445AC2-157 GEN2
Solar/Wind Harmer
0.004
25194608D.CRK4
Adder
2.039
270018AE2-047 C O1
Solar/Wind Harmer
0.004
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
8.469
270263AC1-001 GEN
Solar/Wind Harmer
0.833
24728605AND G2
Adder
4.525
962761AG1-125 GEN
Solar/Wind Harmer
32.213
970149AG2-104 GEN
Solar/Wind Harmer
34.791
970155AG2-107 GEN
Solar/Wind Harmer
20.57
270197AD1-017 GEN1
Solar/Wind Harmer
1.016
3147312GRETNA
Solar/Wind Harmer
0.031
941821AE2-187 GEN
Solar/Wind Harmer
4.925
970773AG2-487 GEN
Solar/Wind Harmer
1.447
963741AG1-226 GEN
Solar/Wind Harmer
19.103
965911AG1-460 GEN
Solar/Wind Harmer
1.613
276615X2-022 GEN
Solar/Wind Harmer
0.084
963831AG1-236 GEN
Solar/Wind Harmer
3.11
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0.001
970613AG2-401 GEN
Solar/Wind Harmer
5.842
274880W4-005 GEN4
Solar/Wind Harmer
0.001
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
276903AD2-071 C
Solar/Wind Harmer
8.845
972175AH1-670 GEN
Solar/Wind Harmer
6.537
24791305MDL-5G
Solar/Wind Harmer
0.001
970291AG2-192 GEN
Solar/Wind Harmer
1.021
270032AE2-172
Solar/Wind Harmer
5.233
274854TWINGROVE;U2
Solar/Wind Harmer
0.003
270005AE1-210 C O1
Solar/Wind Harmer
1.696
965031AG1-367 GEN
Solar/Wind Harmer
7.829
970825AG2-519 GEN
Solar/Wind Harmer
2.773
276726Z2-087_GEN
Solar/Wind Harmer
0.003
939741AE1-205 GEN
Solar/Wind Harmer
10.926
253370AE2-315 SEC1
Adder
2.238
253371AE2-315 SEC2
Adder
2.117
274877BISHOP HL;1U
Solar/Wind Harmer
0.26
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
9.649
276158O29GEN2
Solar/Wind Harmer
0.001
274857EASY ROAD;U1
Solar/Wind Harmer
0.002
274761LEE CO EC;2U
Adder
10.252
274766LEE CO EC;7U
Adder
10.131
970569AG2-363 GEN
Solar/Wind Harmer
23.052
971475AH1-234 GEN
Solar/Wind Harmer
3.722
970819AG2-516 GEN
Solar/Wind Harmer
9.198
972235AH1-702 GEN1
Adder
2.767
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
960071AF2-298 GEN
Solar/Wind Harmer
3.815
25326309TAIT D
Adder
1.202
274822ROCKFORD ;11
Adder
21.533
957471AF2-041 GEN
Solar/Wind Harmer
22.952
959081AF2-199 GEN
Solar/Wind Harmer
7.651
971067AG2-660 GEN
Solar/Wind Harmer
2.55
939401AE1-172 GEN
Solar/Wind Harmer
5.72
971997AH1-543 GEN
Solar/Wind Harmer
4.011
276861AD2-134 GEN
Solar/Wind Harmer
0.137
945371AF1-202 GEN
Solar/Wind Harmer
0.001
274828WAUKEGAN ;BP
Adder
12.03
274682WAUKEGAN ;7U
Adder
19.567
274745AC1-111 GEN9
Adder
6.069
238185AF2-356 C
Solar/Wind Helper
2.176
237046AF1-021 C
Solar/Wind Helper
0.457
24289405MTG1
50/50
11.79
24318705GVG2
50/50
11.866
24722005FLATG5
50/50
2.714
24721905FLATG4
50/50
49.755
24686205CER G4
Adder
16.139
24686405CER G5
Adder
16.075
270053AF1-130 C
Solar/Wind Harmer
2.937
970913AG2-568 GEN
Solar/Wind Harmer
9.858
960911AF2-382 GEN
Solar/Wind Harmer
9.021
943031AE2-326 GEN
Solar/Wind Harmer
6.109
971461AH1-227 GEN
Solar/Wind Harmer
5.958
972103AH1-617 GEN
Solar/Wind Harmer
23.212
971331AH1-145 GEN
Solar/Wind Harmer
15.359
247619Y1-049
Adder
0.704
971191AH1-055 GEN
Solar/Wind Harmer
29.418
270346AE1-212 GEN
Solar/Wind Harmer
10.08
958121AF2-106 GEN
Solar/Wind Harmer
0.001
972273AH1-721 GEN
Adder
111.61
270030AE2-140 GEN
Solar/Wind Harmer
18.75
970093AG2-073 GEN
Solar/Wind Harmer
9.318
970243AG2-164 GEN
Solar/Wind Harmer
5.432
970519AG2-331 GEN
Solar/Wind Harmer
24.144
970699AG2-449 GEN
Solar/Wind Harmer
2.322
966571AG1-526 GEN
Solar/Wind Harmer
20.57
270173AC1-122 GEN
Solar/Wind Harmer
0.435
3429391JKCT 9G
Adder
10.993
970273AG2-179 GEN
Solar/Wind Harmer
5.522
972167AH1-666 GEN
Solar/Wind Harmer
7.359
962751AG1-124 GEN
Solar/Wind Harmer
8.092
339250AF1-203 GEN
Solar/Wind Harmer
0.001
971155AH1-034 GEN
Solar/Wind Harmer
10.521
960741AF2-365 GEN
Solar/Wind Harmer
4.499
962251AG1-071 GEN
Solar/Wind Harmer
5.619
958171AF2-111 GEN
Solar/Wind Harmer
22.442
270291AC1-194 GEN
Solar/Wind Harmer
7.02
25196008MFTGT1
Adder
1.692
252510AF1-249 C
Solar/Wind Harmer
0.067
25194608D.CRK4
Adder
2.039
25196608WSDLE5
Adder
10.598
253316AC1-085 GEN3
Solar/Wind Harmer
0.005
253433AC1-085 GEN1
Solar/Wind Harmer
0.004
946181AF1-283 GEN
Solar/Wind Harmer
11.009
253406AD2-031_GEN
Solar/Wind Harmer
0.624
970193AG2-126 GEN
Solar/Wind Harmer
12.39
24728705AND G3
Adder
9.464
24728505AND G1
Adder
4.525
970153AG2-106 GEN
Solar/Wind Harmer
20.57
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
3147312GRETNA
Solar/Wind Harmer
0.123
3146802CHATHAM
Solar/Wind Harmer
0.115
941801AE2-185 GEN
Solar/Wind Harmer
4.925
270356AE2-297 GEN
Solar/Wind Harmer
0.011
270222AC2-111 GEN
Solar/Wind Harmer
4.144
253415AE1-040 GEN
Solar/Wind Harmer
0.003
942481AE2-261 GEN
Solar/Wind Harmer
24.109
276621W2-048 GEN
Solar/Wind Harmer
0.403
276838X2-022 GEN2
Solar/Wind Harmer
0.45
270437AC2-090 C
Solar/Wind Harmer
0.004
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
3.68
276668AB2-070 GEN1
Solar/Wind Harmer
0.29
243186AF1-051 GEN
50/50
12.748
24723005RIVRG1
Adder
37.637
24723105RIVRG2
Adder
37.637
24685805CER G1
Adder
16.117
24685905CER G2
Adder
16.117
944971AF1-162 GEN
Solar/Wind Harmer
13.01
24728205BUCHG1
Adder
7.763
971225AH1-072 GEN
Solar/Wind Harmer
2.323
971227AH1-073 GEN
Solar/Wind Harmer
2.323
971277AH1-098 GEN
Solar/Wind Harmer
4.634
270583AD2-179 GEN
Solar/Wind Harmer
11.403
960161AF2-307 GEN
Solar/Wind Harmer
6.387
971073AG2-665 GEN
Solar/Wind Harmer
8.448
270186AC1-089 GEN
Solar/Wind Harmer
0.006
970239AG2-162 GEN
Solar/Wind Harmer
2.322
942891AE2-308 GEN
Solar/Wind Harmer
9.282
972043AH1-570 GEN
Solar/Wind Harmer
2.394
972045AH1-571 GEN
Solar/Wind Harmer
1.918
339221AD2-048_GEN
Solar/Wind Harmer
0.006
966021AG1-471 GEN
Solar/Wind Harmer
4.953
971125AH1-004 GEN
Solar/Wind Harmer
3.667
970107AG2-081 GEN
Solar/Wind Harmer
2.751
971485AH1-239 GEN
Solar/Wind Harmer
7.325
962581AG1-107 GEN
Solar/Wind Harmer
0.002
971081AG2-670 GEN
Solar/Wind Harmer
6.822
970235AG2-159 GEN
Solar/Wind Harmer
5.533
970235AG2-159 GEN
Solar/Wind Harmer
3.174
970653AG2-424 GEN
Solar/Wind Harmer
4.368
970653AG2-424 GEN
Solar/Wind Harmer
2.263
339255AE2-071 GEN
Solar/Wind Harmer
-0.148
964781AG1-341 GEN
Solar/Wind Harmer
9.557
964571AG1-320 GEN
Solar/Wind Harmer
8.226
252509AD1-136 GEN
Solar/Wind Harmer
0.045
25183208HLCRTG
Solar/Wind Harmer
0.014
252519AF1-045_GEN
Solar/Wind Harmer
7.591
252516AE2-318_GEN
Solar/Wind Harmer
6.733
270444AC2-157 GEN1
Solar/Wind Harmer
0.004
971587AH1-292 GEN
Solar/Wind Harmer
6.388
25194408D.CRK1
Adder
9.381
25194508D.CRK3
Adder
1.754
253317AC1-085 GEN4
Solar/Wind Harmer
0.005
945391AF1-204 GEN
Solar/Wind Harmer
8.776
253394AE2-221_GEN
Solar/Wind Harmer
0.01
253398AE2-221_GEN2
Solar/Wind Harmer
0.01
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.002
942671AE2-283 GEN
Solar/Wind Harmer
3.83
24728805RICHG1
Adder
4.412
24728905RICHG2
Adder
4.412
276916AD2-100_GEN
Solar/Wind Harmer
16.969
276911AD2-131_GEN
Solar/Wind Harmer
1.118
970241AG2-163 GEN
Solar/Wind Harmer
4.709
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
24379505HDWTR1G C
Solar/Wind Harmer
0.003
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
966841AG1-555 GEN
Solar/Wind Harmer
0.9
270383AD1-128 GEN
Solar/Wind Harmer
0.005
971613AH1-306 GEN
Solar/Wind Harmer
3.767
960611AF2-352 GEN
Solar/Wind Harmer
2.614
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
970825AG2-519 GEN
Solar/Wind Harmer
8.658
960441AF2-335 GEN
Solar/Wind Harmer
7.811
253370AE2-315 SEC1
Adder
2.238
276782AC1-033 GEN
Solar/Wind Harmer
0.001
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.304
276646AC1-214 GEN2
Solar/Wind Harmer
0.304
276741O09 GEN1
Solar/Wind Harmer
0.275
276708O09 GEN2
Solar/Wind Harmer
0.275
972267AH1-718 GEN
Adder
4.6
970883AG2-550 GEN
Solar/Wind Harmer
7.705
970885AG2-551 GEN
Solar/Wind Harmer
2.568
276603SUBLETTE C
Solar/Wind Harmer
0
274764LEE CO EC;5U
Adder
10.276
274765LEE CO EC;6U
Adder
10.276
274762LEE CO EC;3U
Adder
10.252
274763LEE CO EC;4U
Adder
10.155
938861AE1-114 GEN
Solar/Wind Harmer
4.353
270599AE1-208 GEN
Solar/Wind Harmer
7.04
270031AE2-169
Solar/Wind Harmer
4.224
274856ECOGROVE ;U1
Solar/Wind Harmer
0.181
276611AD2-172 GEN
Solar/Wind Harmer
0.002
25322209TAIT E
Adder
10.707
25322209TAIT E
Adder
10.466
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
270013AE1-250 PV
Solar/Wind Harmer
0.004
971341AH1-150 GEN
Solar/Wind Harmer
15.301
971343AH1-151 GEN
Solar/Wind Harmer
15.301
274683WAUKEGAN ;8U
Adder
22.951
274683WAUKEGAN ;8U
Adder
19.347
274696ROCKY RD ;4P
Adder
12.409
274695ROCKY RD ;2P
Adder
12.123
274693ROCKY RD ;1P
Adder
12.003
274697ROCKY RD ;3P
Adder
3.293
247621Y3-024
Adder
0.262
23585401KL_K28_T16
Solar/Wind Helper
1.267
23652301WDPWR_K20
Solar/Wind Helper
0.133
238120AE2-309 GEN
Solar/Wind Helper
0.43
203955AF1-039 C O1
Solar/Wind Helper
0.352
944781AF1-143 GEN
Solar/Wind Helper
2.298
20083426SW_E13_K22
Solar/Wind Helper
0.051
20088926STNY CRK
Solar/Wind Helper
0.747
20084626FORWARD
Solar/Wind Helper
0.323
946071AF1-272 GEN
Solar/Wind Helper
2.428
203940AF1-140 C
Solar/Wind Helper
0.359
235054AD2-180 GEN
Solar/Wind Helper
1.695
238117U2-030
Solar/Wind Helper
0.288
235531U2-073 GEN
Solar/Wind Helper
2.733
23751201ROTHROCK
Solar/Wind Helper
0.71
23562501BACKB
Solar/Wind Helper
0.864
23583801GRNGAP
Solar/Wind Helper
4.088
316095T157 G97
Solar/Wind Helper
1.094
238108AE1-109 GEN1
Solar/Wind Helper
0.088
20089226LOOKOUT
Solar/Wind Helper
0.539
20088826HIGHLAND
Solar/Wind Helper
0.812
972173AH1-669 GEN
Solar/Wind Harmer
3.965
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
7.866
247642Z2-115 C
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
0.864
970291AG2-192 GEN
Solar/Wind Harmer
0.786
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
965091AG1-374 GEN
Solar/Wind Harmer
23.525
959611AF2-252 GEN
Solar/Wind Harmer
2.614
958821AF2-173 GEN
Solar/Wind Harmer
10.961
270004AE1-209 GEN
Solar/Wind Harmer
1.696
270273AD2-016 GEN
Solar/Wind Harmer
0.81
942111AE2-223 GEN
Solar/Wind Harmer
2.536
253370AE2-315 SEC1
Adder
2.238
253371AE2-315 SEC2
Adder
2.117
965931AG1-462 GEN
Solar/Wind Harmer
19.808
946031AF1-268 GEN
Solar/Wind Harmer
7.391
3147123OTTER R
Solar/Wind Harmer
0.087
274878BISHOP HL;2U
Solar/Wind Harmer
0.26
970191AG2-125 GEN
Solar/Wind Harmer
1.992
276157O29GEN1
Solar/Wind Harmer
1.248
274858EASY ROAD;U2
Solar/Wind Harmer
0.002
274760LEE CO EC;1U
Adder
10.252
274767LEE CO EC;8U
Adder
10.131
970571AG2-364 GEN
Solar/Wind Harmer
15.368
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
972236AH1-702 GEN2
Adder
2.406
276889AE2-281 GEN
Solar/Wind Harmer
0.001
270016AE1-250 BESS
Solar/Wind Harmer
0.004
959091AF2-200 GEN
Solar/Wind Harmer
15.301
274855GSG-6 ;RU
Solar/Wind Harmer
0.28
274850MENDOTA H;RU
Solar/Wind Harmer
0.09
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.137
274682WAUKEGAN ;7U
Adder
19.567
274729ELWOOD EC;1P
Adder
8.072
237048AF1-022 C
Solar/Wind Helper
0.182
964991AG1-363 GEN
Solar/Wind Helper
3.709
23750701CROSSCHOOL
Solar/Wind Helper
1.197
238118U2-030_1
Solar/Wind Helper
0.288
238127S14_GEN_2
Solar/Wind Helper
0.687
237043AE2-125 C
Solar/Wind Helper
0.163
202652Y1-033 WT C
Solar/Wind Helper
0.534
316097T157 G90
Solar/Wind Helper
1.094
20089126CSLMN_L13
Solar/Wind Helper
0.554
20089026BF_G21_K23
Solar/Wind Helper
0.438
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
0.329
944201AF1-088_MTX
Adder
145.184
957141AF2-008_MTX
Adder
72.592
NYPJM->LTFIMP_NY
CLTF
5.271
LGEELTFEXP_LGEE->PJM
CLTF
8.989
WECLTFEXP_WEC->PJM
CLTF
4.2
AG2-052LTFEXP_AG2-052->PJM
LTF
0.253
AH1-155LTFEXP_AH1-155->PJM
LTF
0.38
LAGNLTFEXP_LAGN->PJM
CLTF
24.37
CBM South 2LTFEXP_CBM-S2->PJM
CBM
29.03
TVALTFEXP_TVA->PJM
CLTF
12.655
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.592
CBM South 1LTFEXP_CBM-S1->PJM
CBM
47.815
MECLTFEXP_MEC->PJM
CLTF
19.173
SIGELTFEXP_SIGE->PJM
CLTF
0.659
CPLELTFEXP_CPLE->PJM
CLTF
7.791
CBM West 2LTFEXP_CBM-W2->PJM
CBM
162.06

Details for 05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:132.35 %
Rating:1868.0 MVA
Rating Type:B
MVA to Mitigate:2472.27
MW Contribution:2.35
Bus #Bus NameTypeMW Contribution
970615AG2-402 GEN
50/50
4.588
24729405KEY G3
50/50
0.368
24729305KEY G2
50/50
0.361
24729205KEY G1
50/50
0.36
247620Y3-023
50/50
0.463
970611AG2-400 GEN
Solar/Wind Harmer
13.763
970627AG2-408 GEN
Solar/Wind Harmer
4.129
942221AE2-234 GEN
Solar/Wind Harmer
0.034
944541AF1-119 GEN
Solar/Wind Harmer
0.42
960971AF2-388 GEN
Solar/Wind Harmer
3.679
270216AD2-079_GEN
Solar/Wind Harmer
0.001
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
11.557
961051AF2-396 GEN
Solar/Wind Harmer
7.705
270526AF1-158 GEN
Solar/Wind Harmer
0.007
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
6.887
965791AG1-447 GEN
Solar/Wind Harmer
5.051
270599AE1-208 GEN
Solar/Wind Harmer
4.993
270031AE2-169
Solar/Wind Harmer
2.996
970321AG2-212 GEN
Solar/Wind Harmer
2.307
274808UNIV PK N;4U
Adder
3.733
274770LINCOLN ;1U
Adder
6.292
274771LINCOLN ;2U
Adder
6.292
274803UNIV PARK;6U
Adder
4.319
274888KELLY CRK;1U
Solar/Wind Harmer
0.302
274887GEN-1.85
Solar/Wind Harmer
0.136
276843GEN-1.7
Solar/Wind Harmer
0.167
958011AF2-095 GEN
Solar/Wind Harmer
7.412
972259AH1-714 GEN
Adder
13.99
274674JOLIET 9 ;6U
Adder
11.217
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
971573AH1-285 GEN
Solar/Wind Harmer
0.931
958481AF2-142 GEN
Solar/Wind Harmer
7.482
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.675
274695ROCKY RD ;2P
Adder
7.922
274693ROCKY RD ;1P
Adder
7.844
274697ROCKY RD ;3P
Adder
2.152
274696ROCKY RD ;4P
Adder
8.109
274683WAUKEGAN ;8U
Adder
14.968
274683WAUKEGAN ;8U
Adder
12.617
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
962691AG1-118 GEN
Solar/Wind Harmer
14.776
958491AF2-143 GEN
Solar/Wind Harmer
7.388
970921AG2-575 GEN
Solar/Wind Harmer
4.913
970921AG2-575 GEN
Solar/Wind Harmer
1.638
971613AH1-306 GEN
Solar/Wind Harmer
2.354
274879MINONK ;1U
Solar/Wind Harmer
0.207
942991AE2-321 GEN
Solar/Wind Harmer
5.451
971333AH1-146 GEN
Solar/Wind Harmer
9.71
971335AH1-147 GEN
Solar/Wind Harmer
9.71
960441AF2-335 GEN
Solar/Wind Harmer
4.841
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
971341AH1-150 GEN
Solar/Wind Harmer
9.652
971343AH1-151 GEN
Solar/Wind Harmer
9.652
970825AG2-519 GEN
Solar/Wind Harmer
5.324
274856ECOGROVE ;U1
Solar/Wind Harmer
0.113
276611AD2-172 GEN
Solar/Wind Harmer
0.001
938861AE1-114 GEN
Solar/Wind Harmer
2.689
274764LEE CO EC;5U
Adder
6.319
274765LEE CO EC;6U
Adder
6.319
274762LEE CO EC;3U
Adder
6.304
274763LEE CO EC;4U
Adder
6.245
276603SUBLETTE C
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.354
270201AC2-176 GEN
Solar/Wind Harmer
0.001
972267AH1-718 GEN
Adder
2.793
276741O09 GEN1
Solar/Wind Harmer
0.166
276708O09 GEN2
Solar/Wind Harmer
0.166
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.183
276646AC1-214 GEN2
Solar/Wind Harmer
0.183
966841AG1-555 GEN
Solar/Wind Harmer
0.525
276782AC1-033 GEN
Solar/Wind Harmer
0.001
247621Y3-024
Adder
0.16
960611AF2-352 GEN
Solar/Wind Harmer
1.506
970241AG2-163 GEN
Solar/Wind Harmer
2.545
24379505HDWTR1G C
Solar/Wind Harmer
0.001
270209AC1-174_GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
270383AD1-128 GEN
Solar/Wind Harmer
0.002
276916AD2-100_GEN
Solar/Wind Harmer
8.413
276911AD2-131_GEN
Solar/Wind Harmer
0.554
970883AG2-550 GEN
Solar/Wind Harmer
3.912
970885AG2-551 GEN
Solar/Wind Harmer
1.304
945391AF1-204 GEN
Solar/Wind Harmer
4.152
970623AG2-406 GEN
Solar/Wind Harmer
0.681
270444AC2-157 GEN1
Solar/Wind Harmer
0.001
971587AH1-292 GEN
Solar/Wind Harmer
2.427
270007AE1-245 C
Solar/Wind Harmer
0.001
970239AG2-162 GEN
Solar/Wind Harmer
0.774
246938BC-WTG3
Solar/Wind Helper
11.083
246937BC-WTG2
Solar/Wind Helper
10.895
270224U2-072_GEN2
Solar/Wind Helper
0.871
270227U2-072_GEN3
Solar/Wind Helper
0.871
270228U2-072_GEN4
Solar/Wind Helper
0.871
270231U2-072_GEN5
Solar/Wind Helper
0.871
270471AD2-092_GEN
Solar/Wind Helper
0.85
253378AE2-206_GEN
Solar/Wind Helper
0.684
276820AF1-078_GEN
Solar/Wind Helper
0.319
241960AC2-195 GEN
Solar/Wind Helper
0.69
24727205RPMNG3
50/50
3.292
971599AH1-298 GEN
50/50
10.333
24729505KEY G4
50/50
6.735
24653605MOTTVILLE
50/50
0.003
963791AG1-232 GEN
Solar/Wind Harmer
11.606
965041AG1-368 GEN
Solar/Wind Harmer
8.426
270071AF1-092 GEN
Solar/Wind Harmer
14.399
965051AG1-369 GEN
Solar/Wind Harmer
3.592
270024AE2-089 GEN
Solar/Wind Harmer
0.007
965101AG1-375 GEN
Solar/Wind Harmer
6.088
971771AH1-392 GEN
Solar/Wind Harmer
5.847
971347AH1-153 GEN
Solar/Wind Harmer
8.688
971619AH1-309 GEN
Solar/Wind Harmer
2.601
945581AF1-223 GEN
Solar/Wind Harmer
0
971769AH1-391 GEN
Solar/Wind Harmer
6.283
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971609AH1-304 GEN
Solar/Wind Harmer
0.89
274814UNIV PK N;0U
Adder
3.782
274807UNIV PK N;3U
Adder
3.774
274805UNIV PK N;1U
Adder
3.758
274811UNIV PK N;7U
Adder
3.75
270536AF1-215 GEN2
Solar/Wind Harmer
0.007
274775LINCOLN ;6U
Adder
6.292
274776LINCOLN ;7U
Adder
6.292
274777LINCOLN ;8U
Adder
6.292
972037AH1-567 GEN1
Adder
0.136
274827FISK ;RP
Adder
5.742
960591AF2-350 GEN
Solar/Wind Harmer
5.147
972227AH1-698 GEN1
Adder
1.919
274687WILL CNTY;4U
Adder
20.447
274687WILL CNTY;4U
Adder
20.447
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274675JOLIET 29;7U
Adder
22.401
274675JOLIET 29;7U
Adder
21.601
274728ELWOOD EC;5P
Adder
11.97
274731ELWOOD EC;2P
Adder
11.97
274733ELWOOD EC;3P
Adder
11.97
274735ELWOOD EC;4P
Adder
11.97
970833AG2-524 GEN
Solar/Wind Harmer
5.563
970833AG2-524 GEN
Solar/Wind Harmer
3.709
971611AH1-305 GEN
Solar/Wind Harmer
2.995
274746AC1-111 G10
Adder
4.021
274744AC1-111 GEN8
Adder
4.021
970289AG2-191 GEN
Solar/Wind Harmer
0.942
270594AE1-207 GEN
Solar/Wind Harmer
5.492
276868AE1-113 GEN
Solar/Wind Harmer
0.982
276882AE2-255 GEN
Solar/Wind Harmer
0.572
971177AH1-047 GEN
Solar/Wind Harmer
3.009
971411AH1-196 GEN
Solar/Wind Harmer
7.289
971675AH1-338 GEN
Solar/Wind Harmer
1.894
970115AG2-085 GEN
Solar/Wind Harmer
1.936
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
9.652
274823ROCKFORD ;21
Adder
13.435
276612AE2-035 GEN
Solar/Wind Harmer
0.001
926823AC1-168 GEN
Solar/Wind Harmer
0.811
970169AG2-114 GEN
Solar/Wind Harmer
4.764
971681AH1-341 GEN
Solar/Wind Harmer
7.643
971549AH1-272 GEN
Solar/Wind Harmer
9.793
961011AF2-392 GEN
Solar/Wind Harmer
2.754
957751AF2-069 GEN
Solar/Wind Harmer
0.154
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
276655WTG1_EQ
Solar/Wind Harmer
0.002
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
4.828
941731AE2-173 GEN
Solar/Wind Harmer
3.831
946321AF1-296 GEN
Solar/Wind Harmer
2.545
963841AG1-237 GEN
Solar/Wind Harmer
1.949
270240V3-007_GEN2
Solar/Wind Harmer
0.001
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.156
276848AB2-070 GEN3
Solar/Wind Harmer
0.155
270543AE2-219 C
Solar/Wind Harmer
0.002
944221AF1-090 GEN
Solar/Wind Harmer
2.279
971029AG2-637 GEN
Solar/Wind Harmer
5.242
971673AH1-337 GEN
Solar/Wind Harmer
2.175
247607V1-011 GEN
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Helper
8.613
270317AD1-130_GEN
Solar/Wind Helper
4.113
966831AG1-554 GEN
Solar/Wind Helper
0.876
270284AF1-227 GEN1
Solar/Wind Helper
1.876
270286AF1-227 GEN2
Solar/Wind Helper
0.688
270287AF1-227 GEN3
Solar/Wind Helper
0.688
270499AE1-146 GEN
Solar/Wind Helper
1.952
945641AF1-229 GEN
Solar/Wind Helper
0.937
24727105RPMNG2
50/50
3.32
970583AG2-370 GEN
50/50
2.809
960851AF2-376 GEN
50/50
2.105
24641605TWIN BRNCH
50/50
0.015
959331AF2-224 GEN
Solar/Wind Harmer
9.634
965021AG1-366 GEN
Solar/Wind Harmer
4.588
970031AG2-029 GEN
Solar/Wind Harmer
5.463
270043AE2-236 GEN
Solar/Wind Harmer
5.191
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.046
944531AF1-118 GEN
Solar/Wind Harmer
31.488
971617AH1-308 GEN
Solar/Wind Harmer
5.166
247643Z2-116 C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
4.805
970349AG2-230 GEN
Solar/Wind Harmer
8.688
24642205MAYFLWER
Adder
0.524
24441205WTRV SLR C
Solar/Wind Harmer
0
970513AG2-328 GEN
Solar/Wind Harmer
2.307
970517AG2-330 GEN
Solar/Wind Harmer
13.84
274752CRETE EC ;2U
Adder
6.241
274753CRETE EC ;3U
Adder
6.241
274724RIVER EC ;11
Adder
13.364
247604X1-042
Adder
0.313
270535AF1-215 GEN1
Solar/Wind Harmer
0.007
274772LINCOLN ;3U
Adder
6.292
274802UNIV PARK;5U
Adder
4.319
274826FISK ;BP
Adder
8.102
274800UNIV PARK;3U
Adder
4.307
972038AH1-567 GEN2
Adder
0.27
276806AD2-047 C O1
Solar/Wind Harmer
2.917
970941AG2-585 GEN
Solar/Wind Harmer
6.434
964401AG1-302 GEN
Solar/Wind Harmer
0.001
972228AH1-698 GEN2
Adder
2.725
970707AG2-453 GEN
Solar/Wind Harmer
16.709
276897AD1-100 C
Solar/Wind Harmer
0.007
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
21.601
276893AG1-478 C
Solar/Wind Harmer
0.201
274730ELWOOD EC;6P
Adder
11.97
274734ELWOOD EC;8P
Adder
11.97
274736ELWOOD EC;9P
Adder
11.97
274729ELWOOD EC;1P
Adder
11.97
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
943121AE2-341 GEN
Solar/Wind Harmer
8.419
943591AF1-030 GEN
Solar/Wind Harmer
5.599
247642Z2-115 C
Solar/Wind Harmer
0.002
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
12.782
970289AG2-191 GEN
Solar/Wind Harmer
0.545
970291AG2-192 GEN
Solar/Wind Harmer
0.496
958821AF2-173 GEN
Solar/Wind Harmer
6.901
270004AE1-209 GEN
Solar/Wind Harmer
1.068
276805AD2-038 GEN
Solar/Wind Harmer
0.001
274872LEEDK;1U
Solar/Wind Harmer
0.18
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.518
274855GSG-6 ;RU
Solar/Wind Harmer
0.178
274850MENDOTA H;RU
Solar/Wind Harmer
0.057
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.087
276889AE2-281 GEN
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
4.834
959091AF2-200 GEN
Solar/Wind Harmer
9.652
972236AH1-702 GEN2
Adder
1.508
970571AG2-364 GEN
Solar/Wind Harmer
9.558
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
6.304
274767LEE CO EC;8U
Adder
6.23
946031AF1-268 GEN
Solar/Wind Harmer
4.492
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
7.069
276157O29GEN1
Solar/Wind Harmer
0.755
274878BISHOP HL;2U
Solar/Wind Harmer
0.156
942111AE2-223 GEN
Solar/Wind Harmer
1.494
965931AG1-462 GEN
Solar/Wind Harmer
11.522
274853TWINGROVE;U1
Solar/Wind Harmer
0.002
965091AG1-374 GEN
Solar/Wind Harmer
13.551
959611AF2-252 GEN
Solar/Wind Harmer
1.506
270437AC2-090 C
Solar/Wind Harmer
0.002
276686W4-005 GEN3
Solar/Wind Harmer
0.001
276668AB2-070 GEN1
Solar/Wind Harmer
0.156
971993AH1-541 GEN
Solar/Wind Harmer
1.971
276621W2-048 GEN
Solar/Wind Harmer
0.211
276838X2-022 GEN2
Solar/Wind Harmer
0.236
942481AE2-261 GEN
Solar/Wind Harmer
12.085
970193AG2-126 GEN
Solar/Wind Harmer
5.861
270404AC1-167 GEN
Solar/Wind Harmer
0.002
270258AD1-119 GEN
Solar/Wind Harmer
0.001
24728705AND G3
Adder
4.272
24728505AND G1
Adder
2.043
270356AE2-297 GEN
Solar/Wind Harmer
0.005
970243AG2-164 GEN
Solar/Wind Harmer
1.812
970519AG2-331 GEN
Solar/Wind Harmer
8.054
970699AG2-449 GEN
Solar/Wind Harmer
0.774
270485AE1-090_GEN
Solar/Wind Helper
0.323
942871AE2-306 GEN
Solar/Wind Helper
0.443
270541AE2-072 C
Solar/Wind Helper
0.932
24727005RPMNG1
50/50
3.308
960861AF2-377 GEN
50/50
2.399
970521AG2-332 GEN
50/50
10.806
24639705ELKHART HY
50/50
0.149
965011AG1-365 GEN
Solar/Wind Harmer
13.763
270063AE2-323 C
Solar/Wind Harmer
0.006
247521TR3_G114
Solar/Wind Harmer
0.262
270246TR4_N_V150
Solar/Wind Harmer
0.046
944231AF1-091 GEN
Solar/Wind Harmer
1.854
24695305TIMB G C
Solar/Wind Harmer
0.002
965651AG1-433 GEN
Solar/Wind Harmer
1.839
958861AF2-177 GEN
Solar/Wind Harmer
2.638
945111AF1-176 GEN
Solar/Wind Harmer
10.578
270505AE1-170 C O1
Solar/Wind Harmer
6.07
945371AF1-202 GEN
Solar/Wind Harmer
0
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.97
970245AG2-165 GEN
Solar/Wind Harmer
2.307
970373AG2-245 GEN
Solar/Wind Harmer
11.147
274751CRETE EC ;1U
Adder
6.241
274754CRETE EC ;4U
Adder
6.241
274723RIVER EC ;12
Adder
13.527
274812UNIV PK N;8U
Adder
3.75
276164X3-005 C
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0.004
274773LINCOLN ;4U
Adder
6.292
274774LINCOLN ;5U
Adder
6.292
274801UNIV PARK;4U
Adder
4.307
276776AD2-060 GEN
Solar/Wind Harmer
0.537
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
6.671
941551AE2-152 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
22.401
274674JOLIET 9 ;6U
Adder
11.217
274732ELWOOD EC;7P
Adder
11.97
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
6.288
274745AC1-111 GEN9
Adder
4.021
276691AA1-018 GEN1
Solar/Wind Harmer
0.604
274682WAUKEGAN ;7U
Adder
12.782
970291AG2-192 GEN
Solar/Wind Harmer
0.645
274828WAUKEGAN ;BP
Adder
7.846
270005AE1-210 C O1
Solar/Wind Harmer
1.068
965031AG1-367 GEN
Solar/Wind Harmer
4.929
962781AG1-127 GEN
Solar/Wind Harmer
4.676
939401AE1-172 GEN
Solar/Wind Harmer
3.674
276901AD2-066 C O1
Solar/Wind Harmer
0.005
270032AE2-172
Solar/Wind Harmer
3.269
274872LEEDK;1U
Solar/Wind Harmer
0.003
971997AH1-543 GEN
Solar/Wind Harmer
2.559
276861AD2-134 GEN
Solar/Wind Harmer
0.087
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
24791305MDL-5G
Solar/Wind Harmer
0.001
957471AF2-041 GEN
Solar/Wind Harmer
14.477
959081AF2-199 GEN
Solar/Wind Harmer
4.826
971067AG2-660 GEN
Solar/Wind Harmer
1.609
274822ROCKFORD ;11
Adder
13.533
970825AG2-519 GEN
Solar/Wind Harmer
1.705
972235AH1-702 GEN1
Adder
1.734
970819AG2-516 GEN
Solar/Wind Harmer
5.74
970569AG2-363 GEN
Solar/Wind Harmer
14.338
971475AH1-234 GEN
Solar/Wind Harmer
2.315
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
6.304
274766LEE CO EC;7U
Adder
6.23
276903AD2-071 C
Solar/Wind Harmer
5.249
276158O29GEN2
Solar/Wind Harmer
0.001
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.002
274877BISHOP HL;1U
Solar/Wind Harmer
0.156
276726Z2-087_GEN
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
6.437
274854TWINGROVE;U2
Solar/Wind Harmer
0.002
972175AH1-670 GEN
Solar/Wind Harmer
3.624
963741AG1-226 GEN
Solar/Wind Harmer
10.327
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
3.19
247536S-71 GEN
Solar/Wind Harmer
0.173
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
1.654
276615X2-022 GEN
Solar/Wind Harmer
0.044
965911AG1-460 GEN
Solar/Wind Harmer
0.808
24728605AND G2
Adder
2.043
970773AG2-487 GEN
Solar/Wind Harmer
0.609
270445AC2-157 GEN2
Solar/Wind Harmer
0.001
970333AG2-219 GEN
Solar/Wind Harmer
2.215
246936BC-WTG1
Solar/Wind Helper
10.895
270462AD2-086
Solar/Wind Helper
3.714
270223U2-072_GEN1
Solar/Wind Helper
0.871
270578AF1-285 GEN2
Solar/Wind Helper
0.59
270391AF1-285 GEN3
Solar/Wind Helper
0.59
247522W1-056 GEN
Solar/Wind Helper
1.168
960841AF2-375 GEN
Solar/Wind Helper
1.175
270349AD2-093_GEN
Solar/Wind Helper
0.85
944201AF1-088_MTX
Adder
55.165
957141AF2-008_MTX
Adder
22.101
990792J1392
External Queue
5.474584102630615
990497J1323
External Queue
1.5914489030838013
NYPJM->LTFIMP_NY
CLTF
1.265
LGEELTFEXP_LGEE->PJM
CLTF
1.782
WECLTFEXP_WEC->PJM
CLTF
2.624
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.056
AG2-052LTFEXP_AG2-052->PJM
LTF
0.17
AH1-155LTFEXP_AH1-155->PJM
LTF
0.255
LAGNLTFEXP_LAGN->PJM
CLTF
5.694
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.439
TVALTFEXP_TVA->PJM
CLTF
2.27
CBM West 1LTFEXP_CBM-W1->PJM
CBM
69.309
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.744
MECLTFEXP_MEC->PJM
CLTF
9.656
SIGELTFEXP_SIGE->PJM
CLTF
0.197
CBM West 2LTFEXP_CBM-W2->PJM
CBM
49.944

Details for 05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer l/o AEP_P1-2_#7442_200545_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer
Contingency Name:
AEP_P1-2_#7442_200545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.07 %
Rating:3097.0 MVA
Rating Type:B
MVA to Mitigate:3439.74
MW Contribution:4.23
Bus #Bus NameTypeMW Contribution
970583AG2-370 GEN
50/50
3.65
960851AF2-376 GEN
50/50
3.285
24727105RPMNG2
50/50
1.308
24641605TWIN BRNCH
50/50
0.023
944531AF1-118 GEN
Solar/Wind Harmer
62.505
270043AE2-236 GEN
Solar/Wind Harmer
8.778
959331AF2-224 GEN
Solar/Wind Harmer
8.888
965021AG1-366 GEN
Solar/Wind Harmer
4.232
970031AG2-029 GEN
Solar/Wind Harmer
7.468
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.065
958821AF2-173 GEN
Solar/Wind Harmer
13.51
270004AE1-209 GEN
Solar/Wind Harmer
2.091
971617AH1-308 GEN
Solar/Wind Harmer
7.972
960861AF2-377 GEN
50/50
3.377
970521AG2-332 GEN
50/50
16.09
24639705ELKHART HY
50/50
0.224
24727005RPMNG1
50/50
1.303
960791AF2-370 GEN
50/50
3.046
965011AG1-365 GEN
Solar/Wind Harmer
12.697
965651AG1-433 GEN
Solar/Wind Harmer
3.637
958861AF2-177 GEN
Solar/Wind Harmer
5.211
945371AF1-202 GEN
Solar/Wind Harmer
0.001
944231AF1-091 GEN
Solar/Wind Harmer
2.856
270063AE2-323 C
Solar/Wind Harmer
0.009
247521TR3_G114
Solar/Wind Harmer
0.369
270246TR4_N_V150
Solar/Wind Harmer
0.065
24695305TIMB G C
Solar/Wind Harmer
0.003
270005AE1-210 C O1
Solar/Wind Harmer
2.091
965031AG1-367 GEN
Solar/Wind Harmer
9.65
970825AG2-519 GEN
Solar/Wind Harmer
3.236
945111AF1-176 GEN
Solar/Wind Harmer
16.201
270505AE1-170 C O1
Solar/Wind Harmer
9.372
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
4.614
270032AE2-172
Solar/Wind Harmer
5.873
970291AG2-192 GEN
Solar/Wind Harmer
1.135
965421AG1-410 GEN
Solar/Wind Harmer
26.1
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0.001
970613AG2-401 GEN
Solar/Wind Harmer
6.336
276903AD2-071 C
Solar/Wind Harmer
9.392
246936BC-WTG1
Solar/Wind Harmer
0.336
270489AE1-102 GEN1
Solar/Wind Harmer
1.076
970373AG2-245 GEN
Solar/Wind Harmer
16.85
247536S-71 GEN
Solar/Wind Harmer
0.321
270055AF2-134 C O1
Solar/Wind Harmer
0.006
274751CRETE EC ;1U
Adder
9.273
274754CRETE EC ;4U
Adder
9.273
274723RIVER EC ;12
Adder
20.057
958381AF2-132 GEN
Solar/Wind Harmer
0.001
274812UNIV PK N;8U
Adder
5.56
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
10.061
276164X3-005 C
Solar/Wind Harmer
0
274773LINCOLN ;4U
Adder
9.237
274774LINCOLN ;5U
Adder
9.237
274801UNIV PARK;4U
Adder
6.373
970245AG2-165 GEN
Solar/Wind Harmer
3.303
276776AD2-060 GEN
Solar/Wind Harmer
0.795
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
9.471
274676JOLIET 29;8U
Adder
33.113
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274674JOLIET 9 ;6U
Adder
16.583
274732ELWOOD EC;7P
Adder
17.702
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
274745AC1-111 GEN9
Adder
5.936
276691AA1-018 GEN1
Solar/Wind Harmer
0.895
24729405KEY G3
50/50
0.729
24729305KEY G2
50/50
0.717
24729205KEY G1
50/50
0.713
970615AG2-402 GEN
50/50
4.232
247620Y3-023
50/50
0.687
970611AG2-400 GEN
Solar/Wind Harmer
12.697
970627AG2-408 GEN
Solar/Wind Harmer
3.809
944541AF1-119 GEN
Solar/Wind Harmer
0.831
960971AF2-388 GEN
Solar/Wind Harmer
7.274
942221AE2-234 GEN
Solar/Wind Harmer
0.055
270599AE1-208 GEN
Solar/Wind Harmer
9.209
270031AE2-169
Solar/Wind Harmer
5.525
270216AD2-079_GEN
Solar/Wind Harmer
0.001
960441AF2-335 GEN
Solar/Wind Harmer
9.138
970825AG2-519 GEN
Solar/Wind Harmer
10.102
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
17.858
961051AF2-396 GEN
Solar/Wind Harmer
11.905
971613AH1-306 GEN
Solar/Wind Harmer
4.228
964611AG1-324 GEN
Solar/Wind Harmer
0.65
270526AF1-158 GEN
Solar/Wind Harmer
0.011
24379505HDWTR1G C
Solar/Wind Harmer
0.003
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
270201AC2-176 GEN
Solar/Wind Harmer
0.002
24441505OLIV SLR
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.561
965681AG1-436 GEN
Solar/Wind Harmer
10.414
965791AG1-447 GEN
Solar/Wind Harmer
7.637
247621Y3-024
Adder
0.286
246938BC-WTG3
Solar/Wind Harmer
0.3
246937BC-WTG2
Solar/Wind Harmer
0.336
270007AE1-245 C
Solar/Wind Harmer
0.002
270383AD1-128 GEN
Solar/Wind Harmer
0.005
274808UNIV PK N;4U
Adder
5.536
274803UNIV PARK;6U
Adder
6.395
274770LINCOLN ;1U
Adder
9.237
274771LINCOLN ;2U
Adder
9.237
970321AG2-212 GEN
Solar/Wind Harmer
3.303
274888KELLY CRK;1U
Solar/Wind Harmer
0.447
274887GEN-1.85
Solar/Wind Harmer
0.2
276843GEN-1.7
Solar/Wind Harmer
0.246
958011AF2-095 GEN
Solar/Wind Harmer
10.963
972259AH1-714 GEN
Adder
20.637
274674JOLIET 9 ;6U
Adder
16.583
970883AG2-550 GEN
Solar/Wind Harmer
7.476
970885AG2-551 GEN
Solar/Wind Harmer
2.492
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
958481AF2-142 GEN
Solar/Wind Harmer
11.087
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
1
971573AH1-285 GEN
Solar/Wind Harmer
1.373
274695ROCKY RD ;2P
Adder
11.705
274693ROCKY RD ;1P
Adder
11.59
274697ROCKY RD ;3P
Adder
3.18
274696ROCKY RD ;4P
Adder
11.982
274683WAUKEGAN ;8U
Adder
22.127
274683WAUKEGAN ;8U
Adder
18.652
958491AF2-143 GEN
Solar/Wind Harmer
10.958
962691AG1-118 GEN
Solar/Wind Harmer
21.835
970921AG2-575 GEN
Solar/Wind Harmer
7.261
970921AG2-575 GEN
Solar/Wind Harmer
2.42
274879MINONK ;1U
Solar/Wind Harmer
0.306
942991AE2-321 GEN
Solar/Wind Harmer
8.062
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
971333AH1-146 GEN
Solar/Wind Harmer
14.365
971335AH1-147 GEN
Solar/Wind Harmer
14.365
971341AH1-150 GEN
Solar/Wind Harmer
14.285
971343AH1-151 GEN
Solar/Wind Harmer
14.285
274856ECOGROVE ;U1
Solar/Wind Harmer
0.167
276611AD2-172 GEN
Solar/Wind Harmer
0.002
966841AG1-555 GEN
Solar/Wind Harmer
0.798
938861AE1-114 GEN
Solar/Wind Harmer
3.985
274764LEE CO EC;5U
Adder
9.365
274765LEE CO EC;6U
Adder
9.365
274762LEE CO EC;3U
Adder
9.343
274763LEE CO EC;4U
Adder
9.255
276603SUBLETTE C
Solar/Wind Harmer
0
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.273
276646AC1-214 GEN2
Solar/Wind Harmer
0.273
972267AH1-718 GEN
Adder
4.143
276741O09 GEN1
Solar/Wind Harmer
0.247
276708O09 GEN2
Solar/Wind Harmer
0.247
276782AC1-033 GEN
Solar/Wind Harmer
0.001
960611AF2-352 GEN
Solar/Wind Harmer
2.261
970241AG2-163 GEN
Solar/Wind Harmer
3.925
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
945391AF1-204 GEN
Solar/Wind Harmer
6.577
276916AD2-100_GEN
Solar/Wind Harmer
12.826
276911AD2-131_GEN
Solar/Wind Harmer
0.845
970621AG2-405 GEN
Solar/Wind Harmer
1.049
24728805RICHG1
Adder
3.037
24728905RICHG2
Adder
3.037
270444AC2-157 GEN1
Solar/Wind Harmer
0.002
971587AH1-292 GEN
Solar/Wind Harmer
3.833
970239AG2-162 GEN
Solar/Wind Harmer
1.162
241996AE2-282_GEN
Solar/Wind Harmer
0.002
270471AD2-092_GEN
Solar/Wind Helper
1.077
946101AF1-275 GEN
Solar/Wind Helper
0.301
247643Z2-116 C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
7.359
946031AF1-268 GEN
Solar/Wind Harmer
8.54
24642205MAYFLWER
Adder
0.806
970349AG2-230 GEN
Solar/Wind Harmer
13.119
970289AG2-191 GEN
Solar/Wind Harmer
0.96
970291AG2-192 GEN
Solar/Wind Harmer
0.873
247642Z2-115 C
Solar/Wind Harmer
0.004
270437AC2-090 C
Solar/Wind Harmer
0.004
270404AC1-167 GEN
Solar/Wind Harmer
0.004
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
12.871
24441205WTRV SLR C
Solar/Wind Harmer
0
270258AD1-119 GEN
Solar/Wind Harmer
0.002
247604X1-042
Adder
0.501
270491AE1-102 GEN2
Solar/Wind Harmer
1.076
270535AF1-215 GEN1
Solar/Wind Harmer
0.01
274752CRETE EC ;2U
Adder
9.273
274753CRETE EC ;3U
Adder
9.273
274724RIVER EC ;11
Adder
19.816
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274802UNIV PARK;5U
Adder
6.395
274826FISK ;BP
Adder
11.989
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
274772LINCOLN ;3U
Adder
9.237
274800UNIV PARK;3U
Adder
6.373
972038AH1-567 GEN2
Adder
0.399
970513AG2-328 GEN
Solar/Wind Harmer
3.303
970517AG2-330 GEN
Solar/Wind Harmer
19.816
276806AD2-047 C O1
Solar/Wind Harmer
4.314
970941AG2-585 GEN
Solar/Wind Harmer
9.516
972228AH1-698 GEN2
Adder
4.027
274676JOLIET 29;8U
Adder
31.93
276897AD1-100 C
Solar/Wind Harmer
0.01
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
970707AG2-453 GEN
Solar/Wind Harmer
24.591
276893AG1-478 C
Solar/Wind Harmer
0.298
274730ELWOOD EC;6P
Adder
17.702
274734ELWOOD EC;8P
Adder
17.702
274736ELWOOD EC;9P
Adder
17.702
274729ELWOOD EC;1P
Adder
17.701
943121AE2-341 GEN
Solar/Wind Harmer
12.419
943591AF1-030 GEN
Solar/Wind Harmer
8.259
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
18.895
276805AD2-038 GEN
Solar/Wind Harmer
0.002
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
7.294
274872LEEDK;1U
Solar/Wind Harmer
0.266
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.766
276889AE2-281 GEN
Solar/Wind Harmer
0.001
274855GSG-6 ;RU
Solar/Wind Harmer
0.263
274850MENDOTA H;RU
Solar/Wind Harmer
0.085
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.129
959091AF2-200 GEN
Solar/Wind Harmer
14.285
972236AH1-702 GEN2
Adder
2.232
970571AG2-364 GEN
Solar/Wind Harmer
14.206
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
9.343
274767LEE CO EC;8U
Adder
9.233
276157O29GEN1
Solar/Wind Harmer
1.121
274878BISHOP HL;2U
Solar/Wind Harmer
0.232
942111AE2-223 GEN
Solar/Wind Harmer
2.239
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
965091AG1-374 GEN
Solar/Wind Harmer
20.348
959611AF2-252 GEN
Solar/Wind Harmer
2.261
24728705AND G3
Adder
7.738
24728505AND G1
Adder
3.7
965931AG1-462 GEN
Solar/Wind Harmer
17.128
270356AE2-297 GEN
Solar/Wind Harmer
0.009
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
2.985
276668AB2-070 GEN1
Solar/Wind Harmer
0.236
276621W2-048 GEN
Solar/Wind Harmer
0.321
276838X2-022 GEN2
Solar/Wind Harmer
0.358
970193AG2-126 GEN
Solar/Wind Harmer
9.285
942481AE2-261 GEN
Solar/Wind Harmer
18.401
270222AC2-111 GEN
Solar/Wind Harmer
2.367
970243AG2-164 GEN
Solar/Wind Harmer
2.719
970519AG2-331 GEN
Solar/Wind Harmer
12.086
970699AG2-449 GEN
Solar/Wind Harmer
1.162
270541AE2-072 C
Solar/Wind Harmer
0.005
241832AE2-181_GEN
Solar/Wind Harmer
0.001
958321AF2-126 GEN
Solar/Wind Harmer
0.444
971599AH1-298 GEN
50/50
20.218
24729505KEY G4
50/50
13.356
24727205RPMNG3
50/50
1.297
24653605MOTTVILLE
50/50
0.005
270071AF1-092 GEN
Solar/Wind Harmer
25.362
965101AG1-375 GEN
Solar/Wind Harmer
12.025
945581AF1-223 GEN
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
14.93
965041AG1-368 GEN
Solar/Wind Harmer
10.949
965051AG1-369 GEN
Solar/Wind Harmer
5.056
971609AH1-304 GEN
Solar/Wind Harmer
1.641
270024AE2-089 GEN
Solar/Wind Harmer
0.01
970115AG2-085 GEN
Solar/Wind Harmer
3.655
971771AH1-392 GEN
Solar/Wind Harmer
8.953
971619AH1-309 GEN
Solar/Wind Harmer
4.017
270594AE1-207 GEN
Solar/Wind Harmer
9.866
971347AH1-153 GEN
Solar/Wind Harmer
13.119
970289AG2-191 GEN
Solar/Wind Harmer
1.658
270240V3-007_GEN2
Solar/Wind Harmer
0.003
971769AH1-391 GEN
Solar/Wind Harmer
9.572
24725505WLD G2 C
Solar/Wind Harmer
0.002
24699105WLD G1 C
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
1.048
247607V1-011 GEN
Solar/Wind Harmer
0.001
971549AH1-272 GEN
Solar/Wind Harmer
16.964
270536AF1-215 GEN2
Solar/Wind Harmer
0.01
274814UNIV PK N;0U
Adder
5.609
274807UNIV PK N;3U
Adder
5.596
274805UNIV PK N;1U
Adder
5.572
274811UNIV PK N;7U
Adder
5.56
958391AF2-133 GEN
Solar/Wind Harmer
0.001
972037AH1-567 GEN1
Adder
0.201
274827FISK ;RP
Adder
8.497
274775LINCOLN ;6U
Adder
9.237
274776LINCOLN ;7U
Adder
9.237
274777LINCOLN ;8U
Adder
9.237
960591AF2-350 GEN
Solar/Wind Harmer
7.613
972227AH1-698 GEN1
Adder
2.835
971611AH1-305 GEN
Solar/Wind Harmer
4.511
274687WILL CNTY;4U
Adder
30.235
274687WILL CNTY;4U
Adder
30.235
274675JOLIET 29;7U
Adder
33.113
274675JOLIET 29;7U
Adder
31.93
274728ELWOOD EC;5P
Adder
17.702
274731ELWOOD EC;2P
Adder
17.701
274733ELWOOD EC;3P
Adder
17.701
274735ELWOOD EC;4P
Adder
17.701
270543AE2-219 C
Solar/Wind Harmer
0.005
970833AG2-524 GEN
Solar/Wind Harmer
8.217
970833AG2-524 GEN
Solar/Wind Harmer
5.478
274746AC1-111 G10
Adder
5.936
274744AC1-111 GEN8
Adder
5.936
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
276868AE1-113 GEN
Solar/Wind Harmer
1.457
276882AE2-255 GEN
Solar/Wind Harmer
0.849
971177AH1-047 GEN
Solar/Wind Harmer
4.45
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
971411AH1-196 GEN
Solar/Wind Harmer
10.784
971675AH1-338 GEN
Solar/Wind Harmer
2.801
971171AH1-044 GEN
Solar/Wind Harmer
14.285
274823ROCKFORD ;21
Adder
19.887
970169AG2-114 GEN
Solar/Wind Harmer
7.099
926823AC1-168 GEN
Solar/Wind Harmer
1.205
276612AE2-035 GEN
Solar/Wind Harmer
0.002
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
971681AH1-341 GEN
Solar/Wind Harmer
11.326
961011AF2-392 GEN
Solar/Wind Harmer
4.084
957751AF2-069 GEN
Solar/Wind Harmer
0.229
971029AG2-637 GEN
Solar/Wind Harmer
10.391
276655WTG1_EQ
Solar/Wind Harmer
0.003
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.234
941731AE2-173 GEN
Solar/Wind Harmer
5.741
963841AG1-237 GEN
Solar/Wind Harmer
2.984
946321AF1-296 GEN
Solar/Wind Harmer
3.782
971673AH1-337 GEN
Solar/Wind Harmer
4.373
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.236
276848AB2-070 GEN3
Solar/Wind Harmer
0.235
944221AF1-090 GEN
Solar/Wind Harmer
3.489
270297AD1-101 GEN
Solar/Wind Harmer
0.001
945411AF1-206 GEN
Solar/Wind Harmer
0
270054AF2-122 C O1
Solar/Wind Helper
0.778
270284AF1-227 GEN1
Solar/Wind Helper
1.167
270286AF1-227 GEN2
Solar/Wind Helper
0.428
270287AF1-227 GEN3
Solar/Wind Helper
0.428
270520AE2-214 GEN
Solar/Wind Helper
2.4
274682WAUKEGAN ;7U
Adder
18.895
274828WAUKEGAN ;BP
Adder
11.599
24791305MDL-5G
Solar/Wind Harmer
0.001
939401AE1-172 GEN
Solar/Wind Harmer
5.451
276901AD2-066 C O1
Solar/Wind Harmer
0.007
962781AG1-127 GEN
Solar/Wind Harmer
6.91
274872LEEDK;1U
Solar/Wind Harmer
0.004
971997AH1-543 GEN
Solar/Wind Harmer
3.793
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
276861AD2-134 GEN
Solar/Wind Harmer
0.129
957471AF2-041 GEN
Solar/Wind Harmer
21.427
959081AF2-199 GEN
Solar/Wind Harmer
7.142
971067AG2-660 GEN
Solar/Wind Harmer
2.381
274822ROCKFORD ;11
Adder
20.032
972235AH1-702 GEN1
Adder
2.567
970569AG2-363 GEN
Solar/Wind Harmer
21.31
970819AG2-516 GEN
Solar/Wind Harmer
8.5
971475AH1-234 GEN
Solar/Wind Harmer
3.428
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
9.343
274766LEE CO EC;7U
Adder
9.233
276158O29GEN2
Solar/Wind Harmer
0.001
274877BISHOP HL;1U
Solar/Wind Harmer
0.232
276726Z2-087_GEN
Solar/Wind Harmer
0.002
939741AE1-205 GEN
Solar/Wind Harmer
9.645
274854TWINGROVE;U2
Solar/Wind Harmer
0.003
24728605AND G2
Adder
3.7
963741AG1-226 GEN
Solar/Wind Harmer
15.923
970773AG2-487 GEN
Solar/Wind Harmer
1.185
972175AH1-670 GEN
Solar/Wind Harmer
5.466
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
2.507
276615X2-022 GEN
Solar/Wind Harmer
0.067
965911AG1-460 GEN
Solar/Wind Harmer
1.231
270445AC2-157 GEN2
Solar/Wind Harmer
0.002
970333AG2-219 GEN
Solar/Wind Harmer
3.324
241808AF1-120 C
Solar/Wind Harmer
0.001
241858AF1-205_GEN
Solar/Wind Harmer
1.342
241840AF1-064_GEN
Solar/Wind Harmer
0.001
270349AD2-093_GEN
Solar/Wind Helper
1.077
944201AF1-088_MTX
Adder
87.117
957141AF2-008_MTX
Adder
29.672
990792J1392
External Queue
6.540774822235107
991297J1743
External Queue
3.431180715560913
NYPJM->LTFIMP_NY
CLTF
2
LGEELTFEXP_LGEE->PJM
CLTF
3.227
WECLTFEXP_WEC->PJM
CLTF
3.885
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.527
AG2-052LTFEXP_AG2-052->PJM
LTF
0.257
AH1-155LTFEXP_AH1-155->PJM
LTF
0.385
LAGNLTFEXP_LAGN->PJM
CLTF
8.301
TVALTFEXP_TVA->PJM
CLTF
3.284
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.188
CBM West 1LTFEXP_CBM-W1->PJM
CBM
126.569
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.288
MECLTFEXP_MEC->PJM
CLTF
14.414
SIGELTFEXP_SIGE->PJM
CLTF
0.332
CBM West 2LTFEXP_CBM-W2->PJM
CBM
76.901

Details for 05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#709_546_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:109.05 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6022.77
MW Contribution:5.33
Bus #Bus NameTypeMW Contribution
270102X2-052 ST
50/50
3.353
270100X2-052 CT1
50/50
3.09
270101X2-052 CT2
50/50
3.09
274770LINCOLN ;1U
50/50
18.26
274771LINCOLN ;2U
50/50
18.26
970321AG2-212 GEN
Solar/Wind Harmer
6.717
965681AG1-436 GEN
Solar/Wind Harmer
18.169
965791AG1-447 GEN
Solar/Wind Harmer
13.324
270526AF1-158 GEN
Solar/Wind Harmer
0.018
24441505OLIV SLR
Solar/Wind Harmer
0
270216AD2-079_GEN
Solar/Wind Harmer
0.002
957891AF2-083 GEN
Solar/Wind Harmer
0.002
961051AF2-396 GEN
Solar/Wind Harmer
28.457
961051AF2-396 GEN
Solar/Wind Harmer
18.971
247620Y3-023
Adder
0.932
274808UNIV PK N;4U
Adder
9.967
972259AH1-714 GEN
Adder
37.97
274803UNIV PARK;6U
Adder
11.601
274888KELLY CRK;1U
Solar/Wind Harmer
0.815
274887GEN-1.85
Solar/Wind Harmer
0.365
276843GEN-1.7
Solar/Wind Harmer
0.449
958011AF2-095 GEN
Solar/Wind Harmer
19.978
274674JOLIET 9 ;6U
Adder
30.323
274847GR RIDGE ;BU
Solar/Wind Harmer
0.005
971573AH1-285 GEN
Solar/Wind Harmer
2.529
274695ROCKY RD ;2P
Adder
21.486
274693ROCKY RD ;1P
Adder
21.275
274697ROCKY RD ;3P
Adder
5.837
274696ROCKY RD ;4P
Adder
21.993
958481AF2-142 GEN
Solar/Wind Harmer
20.192
274861TOP CROP ;1U
Solar/Wind Harmer
0.004
274862TOP CROP ;2U
Solar/Wind Harmer
1.82
274683WAUKEGAN ;8U
Adder
40.539
274683WAUKEGAN ;8U
Adder
34.173
962691AG1-118 GEN
Solar/Wind Harmer
40.102
970921AG2-575 GEN
Solar/Wind Harmer
13.333
970921AG2-575 GEN
Solar/Wind Harmer
4.444
958491AF2-143 GEN
Solar/Wind Harmer
19.955
274879MINONK ;1U
Solar/Wind Harmer
0.559
942991AE2-321 GEN
Solar/Wind Harmer
14.775
971333AH1-146 GEN
Solar/Wind Harmer
26.325
971335AH1-147 GEN
Solar/Wind Harmer
26.325
971341AH1-150 GEN
Solar/Wind Harmer
26.172
971343AH1-151 GEN
Solar/Wind Harmer
26.172
276872AE1-163_GEN1
Solar/Wind Harmer
0.003
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.003
274856ECOGROVE ;U1
Solar/Wind Harmer
0.305
276611AD2-172 GEN
Solar/Wind Harmer
0.003
938861AE1-114 GEN
Solar/Wind Harmer
7.288
274764LEE CO EC;5U
Adder
17.123
274765LEE CO EC;6U
Adder
17.123
274762LEE CO EC;3U
Adder
17.083
274763LEE CO EC;4U
Adder
16.922
276603SUBLETTE C
Solar/Wind Harmer
0
970611AG2-400 GEN
Solar/Wind Harmer
12.726
970627AG2-408 GEN
Solar/Wind Harmer
3.818
972267AH1-718 GEN
Adder
7.569
276741O09 GEN1
Solar/Wind Harmer
0.451
276708O09 GEN2
Solar/Wind Harmer
0.451
274851PROVIDENC;RU
Solar/Wind Harmer
0.002
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.497
24344005CKG1
50/50
13.628
270142AC1-141 CT1_
50/50
4.979
24641605TWIN BRNCH
50/50
0.036
24642205MAYFLWER
50/50
1.39
274772LINCOLN ;3U
50/50
18.26
970513AG2-328 GEN
Solar/Wind Harmer
6.717
970517AG2-330 GEN
Solar/Wind Harmer
40.303
970349AG2-230 GEN
Solar/Wind Harmer
23.209
270043AE2-236 GEN
Solar/Wind Harmer
9.37
247643Z2-116 C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
11.566
274724RIVER EC ;11
Adder
35.644
274752CRETE EC ;2U
Adder
16.552
274753CRETE EC ;3U
Adder
16.552
24441205WTRV SLR C
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
45.547
274802UNIV PARK;5U
Adder
11.601
274826FISK ;BP
Adder
21.78
276806AD2-047 C O1
Solar/Wind Harmer
7.862
970941AG2-585 GEN
Solar/Wind Harmer
17.342
972228AH1-698 GEN2
Adder
7.363
971599AH1-298 GEN
50/50
19.983
270144AC1-141 ST1_
50/50
4.41
24643105BUCHANAN
50/50
0.026
274775LINCOLN ;6U
50/50
18.26
274776LINCOLN ;7U
50/50
18.26
274777LINCOLN ;8U
50/50
18.26
24653605MOTTVILLE
50/50
0.008
971347AH1-153 GEN
Solar/Wind Harmer
23.209
960681AF2-359 GEN
Solar/Wind Harmer
-0.002
971771AH1-392 GEN
Solar/Wind Harmer
14.529
971769AH1-391 GEN
Solar/Wind Harmer
16.154
971619AH1-309 GEN
Solar/Wind Harmer
6.462
270071AF1-092 GEN
Solar/Wind Harmer
27.514
274814UNIV PK N;0U
Adder
10.098
274807UNIV PK N;3U
Adder
10.076
274805UNIV PK N;1U
Adder
10.033
274811UNIV PK N;7U
Adder
10.011
972037AH1-567 GEN1
Adder
0.364
274827FISK ;RP
Adder
15.436
960591AF2-350 GEN
Solar/Wind Harmer
13.873
972227AH1-698 GEN1
Adder
5.185
270536AF1-215 GEN2
Solar/Wind Harmer
0.017
274687WILL CNTY;4U
Adder
55.173
274687WILL CNTY;4U
Adder
55.173
274675JOLIET 29;7U
Adder
60.513
274675JOLIET 29;7U
Adder
58.351
274731ELWOOD EC;2P
Adder
32.348
274733ELWOOD EC;3P
Adder
32.348
274735ELWOOD EC;4P
Adder
32.348
274728ELWOOD EC;5P
Adder
32.348
970833AG2-524 GEN
Solar/Wind Harmer
15.09
970833AG2-524 GEN
Solar/Wind Harmer
10.06
274746AC1-111 G10
Adder
10.916
274744AC1-111 GEN8
Adder
10.916
958391AF2-133 GEN
Solar/Wind Harmer
0.002
24729505KEY G4
Adder
12.474
971611AH1-305 GEN
Solar/Wind Harmer
7.91
276868AE1-113 GEN
Solar/Wind Harmer
2.657
276882AE2-255 GEN
Solar/Wind Harmer
1.548
971177AH1-047 GEN
Solar/Wind Harmer
8.156
971675AH1-338 GEN
Solar/Wind Harmer
5.138
971411AH1-196 GEN
Solar/Wind Harmer
19.757
274863CRW1-WTG
Solar/Wind Harmer
0.004
274864CRW2-WTG
Solar/Wind Harmer
0.004
971171AH1-044 GEN
Solar/Wind Harmer
26.172
274823ROCKFORD ;21
Adder
36.411
970169AG2-114 GEN
Solar/Wind Harmer
12.957
276612AE2-035 GEN
Solar/Wind Harmer
0.003
926823AC1-168 GEN
Solar/Wind Harmer
2.2
24344105CKG2
50/50
17.41
270143AC1-141 CT2_
50/50
4.979
24639705ELKHART HY
50/50
0.333
274773LINCOLN ;4U
50/50
18.26
274774LINCOLN ;5U
50/50
18.26
970521AG2-332 GEN
50/50
23.674
970245AG2-165 GEN
Solar/Wind Harmer
6.717
270505AE1-170 C O1
Solar/Wind Harmer
15.077
945111AF1-176 GEN
Solar/Wind Harmer
25.462
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
7.414
274723RIVER EC ;12
Adder
36.059
970373AG2-245 GEN
Solar/Wind Harmer
29.431
274751CRETE EC ;1U
Adder
16.552
274754CRETE EC ;4U
Adder
16.552
276164X3-005 C
Solar/Wind Harmer
0
270063AE2-323 C
Solar/Wind Harmer
0.011
274812UNIV PK N;8U
Adder
10.011
276776AD2-060 GEN
Solar/Wind Harmer
1.448
274801UNIV PARK;4U
Adder
11.588
941551AE2-152 GEN
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0.011
274676JOLIET 29;8U
Adder
60.512
274674JOLIET 9 ;6U
Adder
30.323
274732ELWOOD EC;7P
Adder
32.348
274871GR RIDGE ;2U
Solar/Wind Harmer
0.002
274745AC1-111 GEN9
Adder
10.916
958381AF2-132 GEN
Solar/Wind Harmer
0.002
964861AG1-349 GEN
Solar/Wind Harmer
-0.002
971917AH1-482 GEN
Solar/Wind Harmer
17.617
276691AA1-018 GEN1
Solar/Wind Harmer
1.631
274682WAUKEGAN ;7U
Adder
34.62
274828WAUKEGAN ;BP
Adder
21.25
939401AE1-172 GEN
Solar/Wind Harmer
9.985
962781AG1-127 GEN
Solar/Wind Harmer
12.689
274872LEEDK;1U
Solar/Wind Harmer
0.008
940581AE2-045 GEN
Solar/Wind Harmer
-0.003
971605AH1-302 GEN
Solar/Wind Harmer
16.609
276901AD2-066 C O1
Solar/Wind Harmer
0.013
971997AH1-543 GEN
Solar/Wind Harmer
6.942
276861AD2-134 GEN
Solar/Wind Harmer
0.236
957471AF2-041 GEN
Solar/Wind Harmer
39.258
959081AF2-199 GEN
Solar/Wind Harmer
13.086
971067AG2-660 GEN
Solar/Wind Harmer
4.362
276876AE1-163_GEN2
Solar/Wind Harmer
0.003
274822ROCKFORD ;11
Adder
36.677
972235AH1-702 GEN1
Adder
4.699
970819AG2-516 GEN
Solar/Wind Harmer
15.555
970569AG2-363 GEN
Solar/Wind Harmer
38.8
971475AH1-234 GEN
Solar/Wind Harmer
6.272
274857EASY ROAD;U1
Solar/Wind Harmer
0.003
274761LEE CO EC;2U
Adder
17.083
274766LEE CO EC;7U
Adder
16.882
24791305MDL-5G
Solar/Wind Harmer
0.002
965011AG1-365 GEN
Solar/Wind Harmer
12.726
276158O29GEN2
Solar/Wind Harmer
0.001
274877BISHOP HL;1U
Solar/Wind Harmer
0.423
965651AG1-433 GEN
Solar/Wind Harmer
3.688
276726Z2-087_GEN
Solar/Wind Harmer
0.004
939741AE1-205 GEN
Solar/Wind Harmer
17.52
24385905FR-11G C
Solar/Wind Harmer
0.003
24387305FR-4G C
Solar/Wind Harmer
0.005
274854TWINGROVE;U2
Solar/Wind Harmer
0.005
958861AF2-177 GEN
Solar/Wind Harmer
5.328
972175AH1-670 GEN
Solar/Wind Harmer
9.878
945371AF1-202 GEN
Solar/Wind Harmer
0.001
963741AG1-226 GEN
Solar/Wind Harmer
27.693
274880W4-005 GEN4
Solar/Wind Harmer
0.002
963831AG1-236 GEN
Solar/Wind Harmer
4.513
276615X2-022 GEN
Solar/Wind Harmer
0.12
944231AF1-091 GEN
Solar/Wind Harmer
3.041
970291AG2-192 GEN
Solar/Wind Harmer
1.481
270032AE2-172
Solar/Wind Harmer
7.401
965911AG1-460 GEN
Solar/Wind Harmer
2.209
276903AD2-071 C
Solar/Wind Harmer
12.04
970333AG2-219 GEN
Solar/Wind Harmer
7.687
270005AE1-210 C O1
Solar/Wind Harmer
2.283
965031AG1-367 GEN
Solar/Wind Harmer
10.536
970825AG2-519 GEN
Solar/Wind Harmer
3.643
247521TR3_G114
Solar/Wind Harmer
0.37
270246TR4_N_V150
Solar/Wind Harmer
0.066
24695305TIMB G C
Solar/Wind Harmer
0.003
270445AC2-157 GEN2
Solar/Wind Harmer
0.004
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0.001
970613AG2-401 GEN
Solar/Wind Harmer
7.029
247536S-71 GEN
Solar/Wind Harmer
0.355
965421AG1-410 GEN
Solar/Wind Harmer
25.459
970773AG2-487 GEN
Solar/Wind Harmer
1.469
246936BC-WTG1
Solar/Wind Harmer
0.326
270489AE1-102 GEN1
Solar/Wind Harmer
1.045
270349AD2-093_GEN
Solar/Wind Helper
1.548
276646AC1-214 GEN2
Solar/Wind Harmer
0.497
276782AC1-033 GEN
Solar/Wind Harmer
0.002
944541AF1-119 GEN
Solar/Wind Harmer
0.842
960971AF2-388 GEN
Solar/Wind Harmer
7.376
966841AG1-555 GEN
Solar/Wind Harmer
1.399
960611AF2-352 GEN
Solar/Wind Harmer
4.101
970241AG2-163 GEN
Solar/Wind Harmer
6.826
942221AE2-234 GEN
Solar/Wind Harmer
0.059
276763AC1-053 GEN1
Solar/Wind Harmer
0.002
276764AC1-053 GEN2
Solar/Wind Harmer
0.002
971613AH1-306 GEN
Solar/Wind Harmer
5.329
270599AE1-208 GEN
Solar/Wind Harmer
10.158
270031AE2-169
Solar/Wind Harmer
6.095
276916AD2-100_GEN
Solar/Wind Harmer
23.006
276911AD2-131_GEN
Solar/Wind Harmer
1.515
970239AG2-162 GEN
Solar/Wind Harmer
2.688
945391AF1-204 GEN
Solar/Wind Harmer
11.282
960441AF2-335 GEN
Solar/Wind Harmer
10.327
970825AG2-519 GEN
Solar/Wind Harmer
11.373
270444AC2-157 GEN1
Solar/Wind Harmer
0.004
971587AH1-292 GEN
Solar/Wind Harmer
7.189
24379505HDWTR1G C
Solar/Wind Harmer
0.003
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
0.716
270201AC2-176 GEN
Solar/Wind Harmer
0.002
270383AD1-128 GEN
Solar/Wind Harmer
0.005
970623AG2-406 GEN
Solar/Wind Harmer
1.6
970883AG2-550 GEN
Solar/Wind Harmer
8.324
970885AG2-551 GEN
Solar/Wind Harmer
2.775
270007AE1-245 C
Solar/Wind Harmer
0.002
246938BC-WTG3
Solar/Wind Harmer
0.291
246937BC-WTG2
Solar/Wind Harmer
0.326
270471AD2-092_GEN
Solar/Wind Helper
1.548
274800UNIV PARK;3U
Adder
11.588
972038AH1-567 GEN2
Adder
0.725
276897AD1-100 C
Solar/Wind Harmer
0.018
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
247604X1-042
Adder
0.825
270535AF1-215 GEN1
Solar/Wind Harmer
0.017
274676JOLIET 29;8U
Adder
58.35
970031AG2-029 GEN
Solar/Wind Harmer
8.936
274729ELWOOD EC;1P
Adder
32.348
274730ELWOOD EC;6P
Adder
32.348
274734ELWOOD EC;8P
Adder
32.348
274736ELWOOD EC;9P
Adder
32.348
276893AG1-478 C
Solar/Wind Harmer
0.544
944531AF1-118 GEN
Solar/Wind Harmer
61.488
943121AE2-341 GEN
Solar/Wind Harmer
22.888
943591AF1-030 GEN
Solar/Wind Harmer
15.221
964401AG1-302 GEN
Solar/Wind Harmer
0.002
276694AA1-018 GEN2
Solar/Wind Harmer
0.002
274682WAUKEGAN ;7U
Adder
34.62
959141AF2-205 GEN
Solar/Wind Harmer
-0.003
276805AD2-038 GEN
Solar/Wind Harmer
0.004
274872LEEDK;1U
Solar/Wind Harmer
0.488
276799AD1-013 GEN
Solar/Wind Harmer
0.003
946671AF1-331 GEN
Solar/Wind Harmer
1.406
274855GSG-6 ;RU
Solar/Wind Harmer
0.483
274850MENDOTA H;RU
Solar/Wind Harmer
0.155
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.236
959091AF2-200 GEN
Solar/Wind Harmer
26.172
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
4.086
970571AG2-364 GEN
Solar/Wind Harmer
25.867
274858EASY ROAD;U2
Solar/Wind Harmer
0.003
274760LEE CO EC;1U
Adder
17.083
274767LEE CO EC;8U
Adder
16.882
24755605MDL-5G
Solar/Wind Harmer
0.002
970781AG2-491 GEN
Solar/Wind Harmer
12.802
959331AF2-224 GEN
Solar/Wind Harmer
8.908
965021AG1-366 GEN
Solar/Wind Harmer
4.242
276157O29GEN1
Solar/Wind Harmer
2.046
274878BISHOP HL;2U
Solar/Wind Harmer
0.423
942111AE2-223 GEN
Solar/Wind Harmer
4.067
274853TWINGROVE;U1
Solar/Wind Harmer
0.005
965091AG1-374 GEN
Solar/Wind Harmer
36.906
959611AF2-252 GEN
Solar/Wind Harmer
4.101
965931AG1-462 GEN
Solar/Wind Harmer
31.198
247642Z2-115 C
Solar/Wind Harmer
0.005
276686W4-005 GEN3
Solar/Wind Harmer
0.002
971993AH1-541 GEN
Solar/Wind Harmer
5.377
276668AB2-070 GEN1
Solar/Wind Harmer
0.424
276621W2-048 GEN
Solar/Wind Harmer
0.577
276838X2-022 GEN2
Solar/Wind Harmer
0.644
970289AG2-191 GEN
Solar/Wind Harmer
1.253
970291AG2-192 GEN
Solar/Wind Harmer
1.139
942481AE2-261 GEN
Solar/Wind Harmer
33.028
970243AG2-164 GEN
Solar/Wind Harmer
6.289
970519AG2-331 GEN
Solar/Wind Harmer
27.951
970699AG2-449 GEN
Solar/Wind Harmer
2.688
970193AG2-126 GEN
Solar/Wind Harmer
15.928
958821AF2-173 GEN
Solar/Wind Harmer
14.751
270004AE1-209 GEN
Solar/Wind Harmer
2.283
971617AH1-308 GEN
Solar/Wind Harmer
8.548
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.066
946031AF1-268 GEN
Solar/Wind Harmer
9.517
270437AC2-090 C
Solar/Wind Harmer
0.004
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
14.144
270404AC1-167 GEN
Solar/Wind Harmer
0.004
270258AD1-119 GEN
Solar/Wind Harmer
0.002
270356AE2-297 GEN
Solar/Wind Harmer
0.011
270491AE1-102 GEN2
Solar/Wind Harmer
1.045
971549AH1-272 GEN
Solar/Wind Harmer
26.668
971681AH1-341 GEN
Solar/Wind Harmer
20.716
24690905MDL-1G C
Solar/Wind Harmer
0.004
270180AB1-006 GEN1
Solar/Wind Harmer
0.003
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.003
24697605MDL-3G C
Solar/Wind Harmer
0.003
24697905MDL-4G C
Solar/Wind Harmer
0.002
270181AB1-006 GEN2
Solar/Wind Harmer
0
961011AF2-392 GEN
Solar/Wind Harmer
7.462
957751AF2-069 GEN
Solar/Wind Harmer
0.418
274848CAMPGROVE;RU
Solar/Wind Harmer
0.002
276655WTG1_EQ
Solar/Wind Harmer
0.005
276656WTG2_EQ
Solar/Wind Harmer
0.001
959341AF2-225 GEN
Solar/Wind Harmer
13.14
941731AE2-173 GEN
Solar/Wind Harmer
10.429
24386205FR-12G C
Solar/Wind Harmer
0.002
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.002
946321AF1-296 GEN
Solar/Wind Harmer
6.891
965101AG1-375 GEN
Solar/Wind Harmer
12.296
963841AG1-237 GEN
Solar/Wind Harmer
5.208
945581AF1-223 GEN
Solar/Wind Harmer
0.001
276785W4-005 GEN1
Solar/Wind Harmer
0.002
276174W4-005 GEN2
Solar/Wind Harmer
0.002
276849AB2-070 GEN2
Solar/Wind Harmer
0.424
276848AB2-070 GEN3
Solar/Wind Harmer
0.422
963791AG1-232 GEN
Solar/Wind Harmer
15.504
970289AG2-191 GEN
Solar/Wind Harmer
2.164
270594AE1-207 GEN
Solar/Wind Harmer
12.434
971609AH1-304 GEN
Solar/Wind Harmer
1.81
965041AG1-368 GEN
Solar/Wind Harmer
11.055
944221AF1-090 GEN
Solar/Wind Harmer
6.244
24725505WLD G2 C
Solar/Wind Harmer
0.002
24699105WLD G1 C
Solar/Wind Harmer
0.002
970115AG2-085 GEN
Solar/Wind Harmer
4.131
270024AE2-089 GEN
Solar/Wind Harmer
0.011
965051AG1-369 GEN
Solar/Wind Harmer
5.072
270240V3-007_GEN2
Solar/Wind Harmer
0.003
270543AE2-219 C
Solar/Wind Harmer
0.005
247607V1-011 GEN
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
1.018
971029AG2-637 GEN
Solar/Wind Harmer
11.658
971673AH1-337 GEN
Solar/Wind Harmer
4.919
944201AF1-088_MTX
Adder
163.382
957141AF2-008_MTX
Adder
69.441
NYPJM->LTFIMP_NY
CLTF
3.386
LGEELTFEXP_LGEE->PJM
CLTF
5.588
WECLTFEXP_WEC->PJM
CLTF
7.104
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.19
AG2-052LTFEXP_AG2-052->PJM
LTF
0.447
AH1-155LTFEXP_AH1-155->PJM
LTF
0.671
LAGNLTFEXP_LAGN->PJM
CLTF
14.15
TVALTFEXP_TVA->PJM
CLTF
5.408
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.516
CBM West 1LTFEXP_CBM-W1->PJM
CBM
217.631
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.154
MECLTFEXP_MEC->PJM
CLTF
26.031
SIGELTFEXP_SIGE->PJM
CLTF
0.551
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.138

Details for 05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line l/o AEP_P1-2_#6463_16757_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#6463_16757_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.68 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5781.3
MW Contribution:5.04
Bus #Bus NameTypeMW Contribution
971599AH1-298 GEN
50/50
20.512
24727205RPMNG3
50/50
2.026
270144AC1-141 ST1_
50/50
4.287
24653605MOTTVILLE
50/50
0.008
24643105BUCHANAN
50/50
0.025
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
1.893
971347AH1-153 GEN
Solar/Wind Harmer
22.406
270071AF1-092 GEN
Solar/Wind Harmer
27.685
971771AH1-392 GEN
Solar/Wind Harmer
14.093
971619AH1-309 GEN
Solar/Wind Harmer
6.277
971769AH1-391 GEN
Solar/Wind Harmer
15.555
960681AF2-359 GEN
Solar/Wind Harmer
-0.002
274775LINCOLN ;6U
Adder
16.368
274776LINCOLN ;7U
Adder
16.368
274777LINCOLN ;8U
Adder
16.368
24729505KEY G4
Adder
12.57
274814UNIV PK N;0U
Adder
9.612
274807UNIV PK N;3U
Adder
9.591
274805UNIV PK N;1U
Adder
9.549
274811UNIV PK N;7U
Adder
9.528
972037AH1-567 GEN1
Adder
0.346
274827FISK ;RP
Adder
14.675
960591AF2-350 GEN
Solar/Wind Harmer
13.18
972227AH1-698 GEN1
Adder
4.923
274687WILL CNTY;4U
Adder
52.393
274687WILL CNTY;4U
Adder
52.393
274675JOLIET 29;7U
Adder
57.451
274675JOLIET 29;7U
Adder
55.399
274731ELWOOD EC;2P
Adder
30.692
274733ELWOOD EC;3P
Adder
30.692
274735ELWOOD EC;4P
Adder
30.692
274728ELWOOD EC;5P
Adder
30.693
970833AG2-524 GEN
Solar/Wind Harmer
14.308
970833AG2-524 GEN
Solar/Wind Harmer
9.539
270536AF1-215 GEN2
Solar/Wind Harmer
0.016
274746AC1-111 G10
Adder
10.351
274744AC1-111 GEN8
Adder
10.351
958391AF2-133 GEN
Solar/Wind Harmer
0.002
971177AH1-047 GEN
Solar/Wind Harmer
7.718
276868AE1-113 GEN
Solar/Wind Harmer
2.511
276882AE2-255 GEN
Solar/Wind Harmer
1.463
971411AH1-196 GEN
Solar/Wind Harmer
18.689
971675AH1-338 GEN
Solar/Wind Harmer
4.859
971549AH1-272 GEN
Solar/Wind Harmer
25.626
274863CRW1-WTG
Solar/Wind Harmer
0.004
274864CRW2-WTG
Solar/Wind Harmer
0.004
971171AH1-044 GEN
Solar/Wind Harmer
24.739
274823ROCKFORD ;21
Adder
34.415
971611AH1-305 GEN
Solar/Wind Harmer
7.323
963791AG1-232 GEN
Solar/Wind Harmer
16.568
276612AE2-035 GEN
Solar/Wind Harmer
0.003
965101AG1-375 GEN
Solar/Wind Harmer
12.216
926823AC1-168 GEN
Solar/Wind Harmer
2.071
970169AG2-114 GEN
Solar/Wind Harmer
12.156
971681AH1-341 GEN
Solar/Wind Harmer
19.553
961011AF2-392 GEN
Solar/Wind Harmer
7.036
965041AG1-368 GEN
Solar/Wind Harmer
11.932
957751AF2-069 GEN
Solar/Wind Harmer
0.392
274848CAMPGROVE;RU
Solar/Wind Harmer
0.002
24690905MDL-1G C
Solar/Wind Harmer
0.004
270180AB1-006 GEN1
Solar/Wind Harmer
0.003
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.002
270181AB1-006 GEN2
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0.005
276656WTG2_EQ
Solar/Wind Harmer
0.001
959341AF2-225 GEN
Solar/Wind Harmer
12.245
941731AE2-173 GEN
Solar/Wind Harmer
9.718
945581AF1-223 GEN
Solar/Wind Harmer
0.001
946321AF1-296 GEN
Solar/Wind Harmer
6.48
24386205FR-12G C
Solar/Wind Harmer
0.002
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.002
963841AG1-237 GEN
Solar/Wind Harmer
4.707
971609AH1-304 GEN
Solar/Wind Harmer
1.767
965051AG1-369 GEN
Solar/Wind Harmer
5.379
970289AG2-191 GEN
Solar/Wind Harmer
2.036
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.39
276848AB2-070 GEN3
Solar/Wind Harmer
0.388
270594AE1-207 GEN
Solar/Wind Harmer
11.748
270024AE2-089 GEN
Solar/Wind Harmer
0.011
970115AG2-085 GEN
Solar/Wind Harmer
3.968
24725505WLD G2 C
Solar/Wind Harmer
0.002
970615AG2-402 GEN
50/50
4.988
270102X2-052 ST
50/50
3.214
270100X2-052 CT1
50/50
2.961
270101X2-052 CT2
50/50
2.961
247620Y3-023
50/50
0.98
970611AG2-400 GEN
Solar/Wind Harmer
14.965
970627AG2-408 GEN
Solar/Wind Harmer
4.49
246938BC-WTG3
Solar/Wind Harmer
0.542
246937BC-WTG2
Solar/Wind Harmer
0.606
970321AG2-212 GEN
Solar/Wind Harmer
6.295
270216AD2-079_GEN
Solar/Wind Harmer
0.002
270526AF1-158 GEN
Solar/Wind Harmer
0.017
957891AF2-083 GEN
Solar/Wind Harmer
0.002
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
17.4
965791AG1-447 GEN
Solar/Wind Harmer
12.76
961051AF2-396 GEN
Solar/Wind Harmer
27.667
961051AF2-396 GEN
Solar/Wind Harmer
18.445
274770LINCOLN ;1U
Adder
16.368
274771LINCOLN ;2U
Adder
16.368
274808UNIV PK N;4U
Adder
9.487
274803UNIV PARK;6U
Adder
11.029
972259AH1-714 GEN
Adder
36.054
274888KELLY CRK;1U
Solar/Wind Harmer
0.774
274887GEN-1.85
Solar/Wind Harmer
0.347
276843GEN-1.7
Solar/Wind Harmer
0.427
958011AF2-095 GEN
Solar/Wind Harmer
18.98
274674JOLIET 9 ;6U
Adder
28.777
274847GR RIDGE ;BU
Solar/Wind Harmer
0.005
971573AH1-285 GEN
Solar/Wind Harmer
2.397
274695ROCKY RD ;2P
Adder
20.358
274693ROCKY RD ;1P
Adder
20.158
274697ROCKY RD ;3P
Adder
5.53
274696ROCKY RD ;4P
Adder
20.838
958481AF2-142 GEN
Solar/Wind Harmer
19.12
274861TOP CROP ;1U
Solar/Wind Harmer
0.003
274862TOP CROP ;2U
Solar/Wind Harmer
1.724
274683WAUKEGAN ;8U
Adder
38.41
274683WAUKEGAN ;8U
Adder
32.378
962691AG1-118 GEN
Solar/Wind Harmer
37.971
970921AG2-575 GEN
Solar/Wind Harmer
12.623
970921AG2-575 GEN
Solar/Wind Harmer
4.208
958491AF2-143 GEN
Solar/Wind Harmer
18.868
944541AF1-119 GEN
Solar/Wind Harmer
0.84
960971AF2-388 GEN
Solar/Wind Harmer
7.355
942991AE2-321 GEN
Solar/Wind Harmer
13.981
274879MINONK ;1U
Solar/Wind Harmer
0.528
971333AH1-146 GEN
Solar/Wind Harmer
24.899
971335AH1-147 GEN
Solar/Wind Harmer
24.899
971341AH1-150 GEN
Solar/Wind Harmer
24.739
971343AH1-151 GEN
Solar/Wind Harmer
24.739
276872AE1-163_GEN1
Solar/Wind Harmer
0.003
274856ECOGROVE ;U1
Solar/Wind Harmer
0.288
276611AD2-172 GEN
Solar/Wind Harmer
0.003
938861AE1-114 GEN
Solar/Wind Harmer
6.879
274764LEE CO EC;5U
Adder
16.158
274765LEE CO EC;6U
Adder
16.158
274762LEE CO EC;3U
Adder
16.12
274763LEE CO EC;4U
Adder
15.968
276603SUBLETTE C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
7.136
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.003
276741O09 GEN1
Solar/Wind Harmer
0.425
276708O09 GEN2
Solar/Wind Harmer
0.425
274851PROVIDENC;RU
Solar/Wind Harmer
0.002
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.467
276646AC1-214 GEN2
Solar/Wind Harmer
0.467
942221AE2-234 GEN
Solar/Wind Harmer
0.059
276782AC1-033 GEN
Solar/Wind Harmer
0.002
960611AF2-352 GEN
Solar/Wind Harmer
3.81
966841AG1-555 GEN
Solar/Wind Harmer
1.27
270599AE1-208 GEN
Solar/Wind Harmer
9.916
270031AE2-169
Solar/Wind Harmer
5.95
276763AC1-053 GEN1
Solar/Wind Harmer
0.002
24699105WLD G1 C
Solar/Wind Harmer
0.001
944221AF1-090 GEN
Solar/Wind Harmer
5.647
270240V3-007_GEN2
Solar/Wind Harmer
0.003
247607V1-011 GEN
Solar/Wind Harmer
0.001
270543AE2-219 C
Solar/Wind Harmer
0.005
971029AG2-637 GEN
Solar/Wind Harmer
10.94
971673AH1-337 GEN
Solar/Wind Harmer
4.593
270284AF1-227 GEN1
Solar/Wind Helper
2.302
270286AF1-227 GEN2
Solar/Wind Helper
0.844
270287AF1-227 GEN3
Solar/Wind Helper
0.844
270054AF2-122 C O1
Solar/Wind Helper
1.201
24344105CKG2
50/50
16.743
24727005RPMNG1
50/50
2.036
270143AC1-141 CT2_
50/50
4.84
24639705ELKHART HY
50/50
0.328
970521AG2-332 GEN
50/50
23.369
24307105BERRINSP G
50/50
0.043
965011AG1-365 GEN
Solar/Wind Harmer
14.965
965421AG1-410 GEN
Solar/Wind Harmer
44.849
246936BC-WTG1
Solar/Wind Harmer
0.606
270489AE1-102 GEN1
Solar/Wind Harmer
1.943
970245AG2-165 GEN
Solar/Wind Harmer
6.295
270063AE2-323 C
Solar/Wind Harmer
0.012
270505AE1-170 C O1
Solar/Wind Harmer
14.646
945111AF1-176 GEN
Solar/Wind Harmer
24.826
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
7.196
274773LINCOLN ;4U
Adder
16.368
274774LINCOLN ;5U
Adder
16.368
274723RIVER EC ;12
Adder
34.361
274751CRETE EC ;1U
Adder
15.774
274754CRETE EC ;4U
Adder
15.774
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
9.528
970373AG2-245 GEN
Solar/Wind Harmer
27.796
274801UNIV PARK;4U
Adder
11.014
276776AD2-060 GEN
Solar/Wind Harmer
1.376
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
57.45
274674JOLIET 9 ;6U
Adder
28.777
274732ELWOOD EC;7P
Adder
30.693
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0.01
274745AC1-111 GEN9
Adder
10.351
276691AA1-018 GEN1
Solar/Wind Harmer
1.544
274682WAUKEGAN ;7U
Adder
32.805
274828WAUKEGAN ;BP
Adder
20.134
958381AF2-132 GEN
Solar/Wind Harmer
0.002
964861AG1-349 GEN
Solar/Wind Harmer
-0.002
971917AH1-482 GEN
Solar/Wind Harmer
16.434
962781AG1-127 GEN
Solar/Wind Harmer
12.012
274872LEEDK;1U
Solar/Wind Harmer
0.008
939401AE1-172 GEN
Solar/Wind Harmer
9.413
276901AD2-066 C O1
Solar/Wind Harmer
0.012
965651AG1-433 GEN
Solar/Wind Harmer
3.678
971997AH1-543 GEN
Solar/Wind Harmer
6.554
276861AD2-134 GEN
Solar/Wind Harmer
0.223
957471AF2-041 GEN
Solar/Wind Harmer
37.108
959081AF2-199 GEN
Solar/Wind Harmer
12.369
971067AG2-660 GEN
Solar/Wind Harmer
4.123
276876AE1-163_GEN2
Solar/Wind Harmer
0.003
274822ROCKFORD ;11
Adder
34.667
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
15.377
972235AH1-702 GEN1
Adder
4.441
970819AG2-516 GEN
Solar/Wind Harmer
14.695
958861AF2-177 GEN
Solar/Wind Harmer
5.294
971475AH1-234 GEN
Solar/Wind Harmer
5.925
970569AG2-363 GEN
Solar/Wind Harmer
36.555
274857EASY ROAD;U1
Solar/Wind Harmer
0.002
274761LEE CO EC;2U
Adder
16.12
274766LEE CO EC;7U
Adder
15.93
276158O29GEN2
Solar/Wind Harmer
0.001
944231AF1-091 GEN
Solar/Wind Harmer
3.153
274877BISHOP HL;1U
Solar/Wind Harmer
0.397
24791305MDL-5G
Solar/Wind Harmer
0.002
276726Z2-087_GEN
Solar/Wind Harmer
0.004
939741AE1-205 GEN
Solar/Wind Harmer
16.327
945371AF1-202 GEN
Solar/Wind Harmer
0.001
274854TWINGROVE;U2
Solar/Wind Harmer
0.005
24385905FR-11G C
Solar/Wind Harmer
0.003
24387305FR-4G C
Solar/Wind Harmer
0.004
972175AH1-670 GEN
Solar/Wind Harmer
9.129
247521TR3_G114
Solar/Wind Harmer
0.393
270246TR4_N_V150
Solar/Wind Harmer
0.07
970291AG2-192 GEN
Solar/Wind Harmer
1.393
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
4.146
963741AG1-226 GEN
Solar/Wind Harmer
24.913
276615X2-022 GEN
Solar/Wind Harmer
0.11
270032AE2-172
Solar/Wind Harmer
6.993
24695305TIMB G C
Solar/Wind Harmer
0.003
270005AE1-210 C O1
Solar/Wind Harmer
2.203
965031AG1-367 GEN
Solar/Wind Harmer
10.168
276903AD2-071 C
Solar/Wind Harmer
11.298
965911AG1-460 GEN
Solar/Wind Harmer
2.014
970825AG2-519 GEN
Solar/Wind Harmer
3.499
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0.001
970613AG2-401 GEN
Solar/Wind Harmer
6.684
247536S-71 GEN
Solar/Wind Harmer
0.341
24728605AND G2
Adder
4.579
270445AC2-157 GEN2
Solar/Wind Harmer
0.004
970333AG2-219 GEN
Solar/Wind Harmer
5.528
970773AG2-487 GEN
Solar/Wind Harmer
1.34
270349AD2-093_GEN
Solar/Wind Helper
1.737
24727105RPMNG2
50/50
2.043
965431AG1-411 GEN
50/50
24.916
270142AC1-141 CT1_
50/50
4.84
24641605TWIN BRNCH
50/50
0.035
24344005CKG1
50/50
13.145
24642205MAYFLWER
50/50
1.347
944961AF1-161 GEN
50/50
5.744
962601AG1-109 GEN
50/50
5.744
270043AE2-236 GEN
Solar/Wind Harmer
9.614
959331AF2-224 GEN
Solar/Wind Harmer
10.476
965021AG1-366 GEN
Solar/Wind Harmer
4.988
270491AE1-102 GEN2
Solar/Wind Harmer
1.943
970349AG2-230 GEN
Solar/Wind Harmer
22.406
970513AG2-328 GEN
Solar/Wind Harmer
6.295
970517AG2-330 GEN
Solar/Wind Harmer
37.773
970031AG2-029 GEN
Solar/Wind Harmer
9.246
247643Z2-116 C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
11.278
944531AF1-118 GEN
Solar/Wind Harmer
62.173
274772LINCOLN ;3U
Adder
16.368
24441205WTRV SLR C
Solar/Wind Harmer
0
274724RIVER EC ;11
Adder
33.965
274752CRETE EC ;2U
Adder
15.774
274753CRETE EC ;3U
Adder
15.774
247604X1-042
Adder
0.795
970707AG2-453 GEN
Solar/Wind Harmer
43.26
274802UNIV PARK;5U
Adder
11.029
274826FISK ;BP
Adder
20.707
274800UNIV PARK;3U
Adder
11.014
972038AH1-567 GEN2
Adder
0.689
276806AD2-047 C O1
Solar/Wind Harmer
7.469
970941AG2-585 GEN
Solar/Wind Harmer
16.476
972228AH1-698 GEN2
Adder
6.992
276897AD1-100 C
Solar/Wind Harmer
0.017
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
274676JOLIET 29;8U
Adder
55.398
274729ELWOOD EC;1P
Adder
30.692
274730ELWOOD EC;6P
Adder
30.693
274734ELWOOD EC;8P
Adder
30.693
274736ELWOOD EC;9P
Adder
30.693
276893AG1-478 C
Solar/Wind Harmer
0.516
943121AE2-341 GEN
Solar/Wind Harmer
21.706
943591AF1-030 GEN
Solar/Wind Harmer
14.435
270535AF1-215 GEN1
Solar/Wind Harmer
0.016
276694AA1-018 GEN2
Solar/Wind Harmer
0.002
274682WAUKEGAN ;7U
Adder
32.805
964401AG1-302 GEN
Solar/Wind Harmer
0.002
274872LEEDK;1U
Solar/Wind Harmer
0.462
276805AD2-038 GEN
Solar/Wind Harmer
0.004
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
1.33
274855GSG-6 ;RU
Solar/Wind Harmer
0.457
274850MENDOTA H;RU
Solar/Wind Harmer
0.147
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.223
959141AF2-205 GEN
Solar/Wind Harmer
-0.003
959091AF2-200 GEN
Solar/Wind Harmer
24.739
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
3.861
970571AG2-364 GEN
Solar/Wind Harmer
24.37
274858EASY ROAD;U2
Solar/Wind Harmer
0.002
274760LEE CO EC;1U
Adder
16.12
274767LEE CO EC;8U
Adder
15.93
276157O29GEN1
Solar/Wind Harmer
1.927
274878BISHOP HL;2U
Solar/Wind Harmer
0.397
24755605MDL-5G
Solar/Wind Harmer
0.002
970781AG2-491 GEN
Solar/Wind Harmer
11.712
942111AE2-223 GEN
Solar/Wind Harmer
3.79
965931AG1-462 GEN
Solar/Wind Harmer
29.323
274853TWINGROVE;U1
Solar/Wind Harmer
0.005
965091AG1-374 GEN
Solar/Wind Harmer
34.294
959611AF2-252 GEN
Solar/Wind Harmer
3.81
247642Z2-115 C
Solar/Wind Harmer
0.005
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.07
970289AG2-191 GEN
Solar/Wind Harmer
1.179
970291AG2-192 GEN
Solar/Wind Harmer
1.072
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
4.944
276668AB2-070 GEN1
Solar/Wind Harmer
0.39
276621W2-048 GEN
Solar/Wind Harmer
0.529
276838X2-022 GEN2
Solar/Wind Harmer
0.591
971617AH1-308 GEN
Solar/Wind Harmer
8.654
958821AF2-173 GEN
Solar/Wind Harmer
14.235
270004AE1-209 GEN
Solar/Wind Harmer
2.203
942481AE2-261 GEN
Solar/Wind Harmer
30.115
946031AF1-268 GEN
Solar/Wind Harmer
9.153
970193AG2-126 GEN
Solar/Wind Harmer
14.08
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
13.732
270437AC2-090 C
Solar/Wind Harmer
0.004
270404AC1-167 GEN
Solar/Wind Harmer
0.004
270258AD1-119 GEN
Solar/Wind Harmer
0.002
24728705AND G3
Adder
9.578
24728505AND G1
Adder
4.579
970243AG2-164 GEN
Solar/Wind Harmer
4.523
970519AG2-331 GEN
Solar/Wind Harmer
20.102
970699AG2-449 GEN
Solar/Wind Harmer
1.933
270356AE2-297 GEN
Solar/Wind Harmer
0.01
276764AC1-053 GEN2
Solar/Wind Harmer
0.002
970241AG2-163 GEN
Solar/Wind Harmer
6.141
971613AH1-306 GEN
Solar/Wind Harmer
5.035
276916AD2-100_GEN
Solar/Wind Harmer
20.939
276911AD2-131_GEN
Solar/Wind Harmer
1.379
960441AF2-335 GEN
Solar/Wind Harmer
9.92
970825AG2-519 GEN
Solar/Wind Harmer
10.923
945391AF1-204 GEN
Solar/Wind Harmer
9.973
964611AG1-324 GEN
Solar/Wind Harmer
0.694
270201AC2-176 GEN
Solar/Wind Harmer
0.002
24379505HDWTR1G C
Solar/Wind Harmer
0.003
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
247621Y3-024
Adder
0.306
970623AG2-406 GEN
Solar/Wind Harmer
1.558
270383AD1-128 GEN
Solar/Wind Harmer
0.005
270444AC2-157 GEN1
Solar/Wind Harmer
0.004
971587AH1-292 GEN
Solar/Wind Harmer
5.849
970883AG2-550 GEN
Solar/Wind Harmer
7.917
970885AG2-551 GEN
Solar/Wind Harmer
2.639
270007AE1-245 C
Solar/Wind Harmer
0.002
970239AG2-162 GEN
Solar/Wind Harmer
1.933
270471AD2-092_GEN
Solar/Wind Helper
1.737
944201AF1-088_MTX
Adder
132.938
957141AF2-008_MTX
Adder
17.09
NYPJM->LTFIMP_NY
CLTF
3.194
LGEELTFEXP_LGEE->PJM
CLTF
4.31
WECLTFEXP_WEC->PJM
CLTF
6.715
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.799
AG2-052LTFEXP_AG2-052->PJM
LTF
0.422
AH1-155LTFEXP_AH1-155->PJM
LTF
0.632
LAGNLTFEXP_LAGN->PJM
CLTF
13.14
TVALTFEXP_TVA->PJM
CLTF
5.018
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.281
CBM West 1LTFEXP_CBM-W1->PJM
CBM
201.431
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.695
MECLTFEXP_MEC->PJM
CLTF
24.295
SIGELTFEXP_SIGE->PJM
CLTF
0.466
CBM West 2LTFEXP_CBM-W2->PJM
CBM
118.505

Details for 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


Base Case Flowgate

Area:AEP/DEO&K
Facility Description:
05TANNER-08M.FORT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.23 %
Rating:2317.0 MVA
Rating Type:B
MVA to Mitigate:2739.4
MW Contribution:2.94
Bus #Bus NameTypeMW Contribution
25194708EBND2
50/50
6.266
24729405KEY G3
50/50
0.332
24729305KEY G2
50/50
0.327
24729205KEY G1
50/50
0.325
247621Y3-024
50/50
0.169
24379505HDWTR1G C
Solar/Wind Harmer
0.003
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
970825AG2-519 GEN
Solar/Wind Harmer
7.843
960441AF2-335 GEN
Solar/Wind Harmer
6.997
944541AF1-119 GEN
Solar/Wind Harmer
0.456
960971AF2-388 GEN
Solar/Wind Harmer
3.991
270599AE1-208 GEN
Solar/Wind Harmer
5.883
270031AE2-169
Solar/Wind Harmer
3.53
270383AD1-128 GEN
Solar/Wind Harmer
0.004
971613AH1-306 GEN
Solar/Wind Harmer
2.936
964611AG1-324 GEN
Solar/Wind Harmer
0.405
270201AC2-176 GEN
Solar/Wind Harmer
0.001
942221AE2-234 GEN
Solar/Wind Harmer
0.024
970883AG2-550 GEN
Solar/Wind Harmer
4.232
970885AG2-551 GEN
Solar/Wind Harmer
1.411
945391AF1-204 GEN
Solar/Wind Harmer
4.318
970241AG2-163 GEN
Solar/Wind Harmer
2.236
966841AG1-555 GEN
Solar/Wind Harmer
0.418
270444AC2-157 GEN1
Solar/Wind Harmer
0.002
971587AH1-292 GEN
Solar/Wind Harmer
2.691
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
970321AG2-212 GEN
Solar/Wind Harmer
1.517
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
960611AF2-352 GEN
Solar/Wind Harmer
1.141
274770LINCOLN ;1U
Adder
4.104
274771LINCOLN ;2U
Adder
4.104
276916AD2-100_GEN
Solar/Wind Harmer
7.107
276911AD2-131_GEN
Solar/Wind Harmer
0.468
965681AG1-436 GEN
Solar/Wind Harmer
4.229
965791AG1-447 GEN
Solar/Wind Harmer
3.101
274888KELLY CRK;1U
Solar/Wind Harmer
0.198
274887GEN-1.85
Solar/Wind Harmer
0.089
276843GEN-1.7
Solar/Wind Harmer
0.109
958011AF2-095 GEN
Solar/Wind Harmer
4.864
274808UNIV PK N;4U
Adder
2.412
972259AH1-714 GEN
Adder
9.225
274803UNIV PARK;6U
Adder
2.819
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
274674JOLIET 9 ;6U
Adder
7.422
24728805RICHG1
Adder
1.818
24728905RICHG2
Adder
1.818
958481AF2-142 GEN
Solar/Wind Harmer
5.024
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.453
958491AF2-143 GEN
Solar/Wind Harmer
5.012
24441505OLIV SLR
Solar/Wind Harmer
0
274879MINONK ;1U
Solar/Wind Harmer
0.141
270526AF1-158 GEN
Solar/Wind Harmer
0.004
971573AH1-285 GEN
Solar/Wind Harmer
0.621
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
274696ROCKY RD ;4P
Adder
5.432
274695ROCKY RD ;2P
Adder
5.307
274693ROCKY RD ;1P
Adder
5.255
274697ROCKY RD ;3P
Adder
1.442
274683WAUKEGAN ;8U
Adder
10.027
274683WAUKEGAN ;8U
Adder
8.452
962691AG1-118 GEN
Solar/Wind Harmer
9.946
970921AG2-575 GEN
Solar/Wind Harmer
3.312
970921AG2-575 GEN
Solar/Wind Harmer
1.104
270216AD2-079_GEN
Solar/Wind Harmer
0
274851PROVIDENC;RU
Solar/Wind Harmer
0
274849CRESCENT ;1U
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.13
276646AC1-214 GEN2
Solar/Wind Harmer
0.13
942991AE2-321 GEN
Solar/Wind Harmer
3.685
276782AC1-033 GEN
Solar/Wind Harmer
0
971333AH1-146 GEN
Solar/Wind Harmer
6.586
971335AH1-147 GEN
Solar/Wind Harmer
6.586
971341AH1-150 GEN
Solar/Wind Harmer
6.576
971343AH1-151 GEN
Solar/Wind Harmer
6.576
274856ECOGROVE ;U1
Solar/Wind Harmer
0.077
276611AD2-172 GEN
Solar/Wind Harmer
0.001
938861AE1-114 GEN
Solar/Wind Harmer
1.85
276741O09 GEN1
Solar/Wind Harmer
0.116
276708O09 GEN2
Solar/Wind Harmer
0.116
276603SUBLETTE C
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
0
961051AF2-396 GEN
Solar/Wind Harmer
6.438
961051AF2-396 GEN
Solar/Wind Harmer
4.292
970239AG2-162 GEN
Solar/Wind Harmer
0.797
25183208HLCRTG
Solar/Wind Helper
2.467
252509AD1-136 GEN
Solar/Wind Helper
0.194
253394AE2-221_GEN
Solar/Wind Helper
1.592
253398AE2-221_GEN2
Solar/Wind Helper
1.592
253378AE2-206_GEN
Solar/Wind Helper
0.968
276820AF1-078_GEN
Solar/Wind Helper
0.452
962581AG1-107 GEN
Solar/Wind Helper
1.007
961491AF2-440 GEN
Solar/Wind Helper
0.041
270186AC1-089 GEN
Solar/Wind Helper
0.814
270518AE2-148 GEN
Solar/Wind Helper
8.413
24726905LAWG2S
50/50
5.157
24726605LAWG1S
50/50
5.152
24726705LAWG2A
50/50
3.467
24726505LAWG1B
50/50
3.443
24726805LAWG2B
50/50
3.432
24729505KEY G4
50/50
6.086
270240V3-007_GEN2
Solar/Wind Harmer
0.003
945581AF1-223 GEN
Solar/Wind Harmer
0.001
965101AG1-375 GEN
Solar/Wind Harmer
7.011
970115AG2-085 GEN
Solar/Wind Harmer
2.799
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
971609AH1-304 GEN
Solar/Wind Harmer
1.048
270594AE1-207 GEN
Solar/Wind Harmer
6.851
970289AG2-191 GEN
Solar/Wind Harmer
1.096
270024AE2-089 GEN
Solar/Wind Harmer
0.005
270543AE2-219 C
Solar/Wind Harmer
0.003
270071AF1-092 GEN
Solar/Wind Harmer
7.808
971029AG2-637 GEN
Solar/Wind Harmer
5.775
963841AG1-237 GEN
Solar/Wind Harmer
1.631
963791AG1-232 GEN
Solar/Wind Harmer
5.031
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
24387005FR-3G C
Solar/Wind Harmer
0.001
971673AH1-337 GEN
Solar/Wind Harmer
2.397
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
971611AH1-305 GEN
Solar/Wind Harmer
2.115
958391AF2-133 GEN
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.004
276785W4-005 GEN1
Solar/Wind Harmer
0
276174W4-005 GEN2
Solar/Wind Harmer
0
276849AB2-070 GEN2
Solar/Wind Harmer
0.125
276848AB2-070 GEN3
Solar/Wind Harmer
0.125
276655WTG1_EQ
Solar/Wind Harmer
0.001
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.6
941731AE2-173 GEN
Solar/Wind Harmer
2.857
971347AH1-153 GEN
Solar/Wind Harmer
5.141
970169AG2-114 GEN
Solar/Wind Harmer
3.406
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
274775LINCOLN ;6U
Adder
4.104
274776LINCOLN ;7U
Adder
4.104
274777LINCOLN ;8U
Adder
4.104
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
972227AH1-698 GEN1
Adder
1.263
944221AF1-090 GEN
Solar/Wind Harmer
1.982
960591AF2-350 GEN
Solar/Wind Harmer
3.378
274814UNIV PK N;0U
Adder
2.444
274807UNIV PK N;3U
Adder
2.439
274805UNIV PK N;1U
Adder
2.428
274811UNIV PK N;7U
Adder
2.423
972037AH1-567 GEN1
Adder
0.088
274827FISK ;RP
Adder
3.748
970833AG2-524 GEN
Solar/Wind Harmer
3.704
970833AG2-524 GEN
Solar/Wind Harmer
2.47
274731ELWOOD EC;2P
Adder
7.93
274733ELWOOD EC;3P
Adder
7.93
274735ELWOOD EC;4P
Adder
7.93
274728ELWOOD EC;5P
Adder
7.929
274687WILL CNTY;4U
Adder
13.464
274687WILL CNTY;4U
Adder
13.464
274675JOLIET 29;7U
Adder
14.777
274675JOLIET 29;7U
Adder
14.249
274746AC1-111 G10
Adder
2.679
274744AC1-111 GEN8
Adder
2.679
971769AH1-391 GEN
Solar/Wind Harmer
3.73
276868AE1-113 GEN
Solar/Wind Harmer
0.67
276882AE2-255 GEN
Solar/Wind Harmer
0.39
926823AC1-168 GEN
Solar/Wind Harmer
0.566
971771AH1-392 GEN
Solar/Wind Harmer
3.324
957751AF2-069 GEN
Solar/Wind Harmer
0.109
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
971177AH1-047 GEN
Solar/Wind Harmer
2.035
971675AH1-338 GEN
Solar/Wind Harmer
1.286
971411AH1-196 GEN
Solar/Wind Harmer
4.94
971171AH1-044 GEN
Solar/Wind Harmer
6.576
276612AE2-035 GEN
Solar/Wind Harmer
0.001
971681AH1-341 GEN
Solar/Wind Harmer
5.259
961011AF2-392 GEN
Solar/Wind Harmer
1.909
971619AH1-309 GEN
Solar/Wind Harmer
1.46
946321AF1-296 GEN
Solar/Wind Harmer
1.796
252524AE2-267 GEN
Solar/Wind Helper
1.054
241972AD1-140 GEN
Solar/Wind Helper
3.429
270367AC2-061_GEN
Solar/Wind Helper
1.955
253383AE2-342_GEN
Solar/Wind Helper
0.463
270340AC2-060 GEN
Solar/Wind Helper
1.177
945631AF1-228 GEN
Solar/Wind Helper
1.077
241973AD2-163_GEN1
Solar/Wind Helper
1.018
24726405LAWG1A
50/50
3.336
961171AF2-408 GEN
50/50
9.412
960791AF2-370 GEN
50/50
2.332
24728605AND G2
50/50
3.373
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0.001
970613AG2-401 GEN
Solar/Wind Harmer
7.702
970773AG2-487 GEN
Solar/Wind Harmer
1.765
270005AE1-210 C O1
Solar/Wind Harmer
1.806
965031AG1-367 GEN
Solar/Wind Harmer
8.337
945371AF1-202 GEN
Solar/Wind Harmer
0.001
970825AG2-519 GEN
Solar/Wind Harmer
2.512
958861AF2-177 GEN
Solar/Wind Harmer
3.038
965651AG1-433 GEN
Solar/Wind Harmer
1.996
276903AD2-071 C
Solar/Wind Harmer
7.007
270032AE2-172
Solar/Wind Harmer
4.078
970291AG2-192 GEN
Solar/Wind Harmer
0.75
247536S-71 GEN
Solar/Wind Harmer
0.183
963741AG1-226 GEN
Solar/Wind Harmer
9.071
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.001
270445AC2-157 GEN2
Solar/Wind Harmer
0.002
24791305MDL-5G
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
4.442
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
4.575
958381AF2-132 GEN
Solar/Wind Harmer
0.001
970245AG2-165 GEN
Solar/Wind Harmer
1.517
270055AF2-134 C O1
Solar/Wind Harmer
0.003
970373AG2-245 GEN
Solar/Wind Harmer
7.265
274880W4-005 GEN4
Solar/Wind Harmer
0
972175AH1-670 GEN
Solar/Wind Harmer
2.835
276726Z2-087_GEN
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
4.8
963831AG1-236 GEN
Solar/Wind Harmer
1.336
274854TWINGROVE;U2
Solar/Wind Harmer
0.001
276615X2-022 GEN
Solar/Wind Harmer
0.036
939401AE1-172 GEN
Solar/Wind Harmer
2.544
274773LINCOLN ;4U
Adder
4.104
274774LINCOLN ;5U
Adder
4.104
941551AE2-152 GEN
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
0.677
274723RIVER EC ;12
Adder
8.679
276776AD2-060 GEN
Solar/Wind Harmer
0.353
274751CRETE EC ;1U
Adder
3.99
274754CRETE EC ;4U
Adder
3.99
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
2.423
274801UNIV PARK;4U
Adder
2.818
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
7.929
274674JOLIET 9 ;6U
Adder
7.422
274676JOLIET 29;8U
Adder
14.777
276901AD2-066 C O1
Solar/Wind Harmer
0.003
276691AA1-018 GEN1
Solar/Wind Harmer
0.406
971997AH1-543 GEN
Solar/Wind Harmer
1.755
274745AC1-111 GEN9
Adder
2.679
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
970569AG2-363 GEN
Solar/Wind Harmer
9.966
274682WAUKEGAN ;7U
Adder
8.557
274828WAUKEGAN ;BP
Adder
5.256
962781AG1-127 GEN
Solar/Wind Harmer
3.152
274872LEEDK;1U
Solar/Wind Harmer
0.002
970091AG2-072 GEN
Adder
34.24
276861AD2-134 GEN
Solar/Wind Harmer
0.059
274877BISHOP HL;1U
Solar/Wind Harmer
0.111
957471AF2-041 GEN
Solar/Wind Harmer
9.864
959081AF2-199 GEN
Solar/Wind Harmer
3.288
971067AG2-660 GEN
Solar/Wind Harmer
1.096
970819AG2-516 GEN
Solar/Wind Harmer
3.925
971475AH1-234 GEN
Solar/Wind Harmer
1.584
276158O29GEN2
Solar/Wind Harmer
0
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
270063AE2-323 C
Solar/Wind Harmer
0.003
270505AE1-170 C O1
Solar/Wind Harmer
3.407
945111AF1-176 GEN
Solar/Wind Harmer
5.786
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
1.673
970333AG2-219 GEN
Solar/Wind Harmer
2.279
252507AC2-088 GEN
Solar/Wind Helper
1.361
253343AC1-166 GEN
Solar/Wind Helper
0.58
253325AC1-069 GEN
Solar/Wind Helper
0.601
964351AG1-297 GEN
50/50
13.747
961161AF2-407 GEN
50/50
35.482
24728705AND G3
50/50
7.054
24728505AND G1
50/50
3.373
270437AC2-090 C
Solar/Wind Harmer
0.005
270356AE2-297 GEN
Solar/Wind Harmer
0.013
958821AF2-173 GEN
Solar/Wind Harmer
11.671
270004AE1-209 GEN
Solar/Wind Harmer
1.806
946031AF1-268 GEN
Solar/Wind Harmer
6.483
944531AF1-118 GEN
Solar/Wind Harmer
26.617
970289AG2-191 GEN
Solar/Wind Harmer
0.635
970291AG2-192 GEN
Solar/Wind Harmer
0.577
247642Z2-115 C
Solar/Wind Harmer
0.002
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
7.517
971617AH1-308 GEN
Solar/Wind Harmer
3.776
970193AG2-126 GEN
Solar/Wind Harmer
6.096
270043AE2-236 GEN
Solar/Wind Harmer
2.401
24755605MDL-5G
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.622
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
964401AG1-302 GEN
Solar/Wind Harmer
0.001
970513AG2-328 GEN
Solar/Wind Harmer
1.517
970517AG2-330 GEN
Solar/Wind Harmer
9.105
270535AF1-215 GEN1
Solar/Wind Harmer
0.004
276686W4-005 GEN3
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
1.587
276668AB2-070 GEN1
Solar/Wind Harmer
0.125
942111AE2-223 GEN
Solar/Wind Harmer
1.114
970349AG2-230 GEN
Solar/Wind Harmer
5.141
274853TWINGROVE;U1
Solar/Wind Harmer
0.001
965091AG1-374 GEN
Solar/Wind Harmer
10.269
959611AF2-252 GEN
Solar/Wind Harmer
1.141
276621W2-048 GEN
Solar/Wind Harmer
0.172
276838X2-022 GEN2
Solar/Wind Harmer
0.192
274772LINCOLN ;3U
Adder
4.104
276897AD1-100 C
Solar/Wind Harmer
0.005
939351AE1-166 GEN
Solar/Wind Harmer
0
942481AE2-261 GEN
Solar/Wind Harmer
10.124
274724RIVER EC ;11
Adder
8.577
972228AH1-698 GEN2
Adder
1.794
276806AD2-047 C O1
Solar/Wind Harmer
1.914
970941AG2-585 GEN
Solar/Wind Harmer
4.222
274752CRETE EC ;2U
Adder
3.99
274753CRETE EC ;3U
Adder
3.99
274802UNIV PARK;5U
Adder
2.819
274800UNIV PARK;3U
Adder
2.818
972038AH1-567 GEN2
Adder
0.176
274826FISK ;BP
Adder
5.288
970707AG2-453 GEN
Solar/Wind Harmer
11.009
276893AG1-478 C
Solar/Wind Harmer
0.133
274729ELWOOD EC;1P
Adder
7.93
274730ELWOOD EC;6P
Adder
7.929
274734ELWOOD EC;8P
Adder
7.929
274736ELWOOD EC;9P
Adder
7.929
274676JOLIET 29;8U
Adder
14.249
276694AA1-018 GEN2
Solar/Wind Harmer
0
943121AE2-341 GEN
Solar/Wind Harmer
5.605
943591AF1-030 GEN
Solar/Wind Harmer
3.727
276805AD2-038 GEN
Solar/Wind Harmer
0.001
276889AE2-281 GEN
Solar/Wind Harmer
0
970571AG2-364 GEN
Solar/Wind Harmer
6.644
274682WAUKEGAN ;7U
Adder
8.557
247643Z2-116 C
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
2.153
274872LEEDK;1U
Solar/Wind Harmer
0.121
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.352
274855GSG-6 ;RU
Solar/Wind Harmer
0.121
274850MENDOTA H;RU
Solar/Wind Harmer
0.039
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.059
274878BISHOP HL;2U
Solar/Wind Harmer
0.111
959091AF2-200 GEN
Solar/Wind Harmer
6.576
276157O29GEN1
Solar/Wind Harmer
0.527
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
945111AF1-176 GEN
Solar/Wind Harmer
2.628
965931AG1-462 GEN
Solar/Wind Harmer
8.158
270222AC2-111 GEN
Solar/Wind Harmer
1.616
970243AG2-164 GEN
Solar/Wind Harmer
1.864
970519AG2-331 GEN
Solar/Wind Harmer
8.287
970699AG2-449 GEN
Solar/Wind Harmer
0.797
24441205WTRV SLR C
Solar/Wind Harmer
0
252510AF1-249 C
Solar/Wind Helper
0.648
253406AD2-031_GEN
Solar/Wind Helper
0.903
253415AE1-040 GEN
Solar/Wind Helper
0.547
253338AC1-165 GEN
Solar/Wind Helper
0.58
253333AC1-068 GEN
Solar/Wind Helper
0.601
241974AD2-163_GEN2
Solar/Wind Helper
1.018
241955AC1-078 GEN
Solar/Wind Helper
0.969
944201AF1-088_MTX
Adder
61.158
957141AF2-008_MTX
Adder
30.579
NYPJM->LTFIMP_NY
CLTF
0.653
LGEELTFEXP_LGEE->PJM
CLTF
1.404
WECLTFEXP_WEC->PJM
CLTF
1.789
AG2-052LTFEXP_AG2-052->PJM
LTF
0.118
AH1-155LTFEXP_AH1-155->PJM
LTF
0.177
LAGNLTFEXP_LAGN->PJM
CLTF
4.763
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.507
TVALTFEXP_TVA->PJM
CLTF
1.913
CBM West 1LTFEXP_CBM-W1->PJM
CBM
54.258
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.271
MECLTFEXP_MEC->PJM
CLTF
7.181
SIGELTFEXP_SIGE->PJM
CLTF
0.234
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.453

Details for 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o DEOK_P1_EAST BEND-TERMINAL 4516_SRT-A


Base Case Flowgate

Area:AEP/DEO&K
Facility Description:
05TANNER-08M.FORT 345.0 kV Ckt 1 line
Contingency Name:
DEOK_P1_EAST BEND-TERMINAL 4516_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.05 %
Rating:2317.0 MVA
Rating Type:B
MVA to Mitigate:2318.24
MW Contribution:2.92
Bus #Bus NameTypeMW Contribution
24726905LAWG2S
50/50
5.818
24726605LAWG1S
50/50
5.812
24726705LAWG2A
50/50
3.911
24726405LAWG1A
50/50
3.764
961171AF2-408 GEN
50/50
9.769
960791AF2-370 GEN
50/50
2.385
24728605AND G2
50/50
3.45
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0.001
970613AG2-401 GEN
Solar/Wind Harmer
8.227
970773AG2-487 GEN
Solar/Wind Harmer
1.904
270005AE1-210 C O1
Solar/Wind Harmer
1.875
965031AG1-367 GEN
Solar/Wind Harmer
8.653
945371AF1-202 GEN
Solar/Wind Harmer
0.001
970825AG2-519 GEN
Solar/Wind Harmer
2.575
958861AF2-177 GEN
Solar/Wind Harmer
3.013
965651AG1-433 GEN
Solar/Wind Harmer
1.961
276903AD2-071 C
Solar/Wind Harmer
7.023
270032AE2-172
Solar/Wind Harmer
4.049
970291AG2-192 GEN
Solar/Wind Harmer
0.734
247536S-71 GEN
Solar/Wind Harmer
0.183
270445AC2-157 GEN2
Solar/Wind Harmer
0.002
963741AG1-226 GEN
Solar/Wind Harmer
8.041
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.001
970091AG2-072 GEN
Adder
34
24791305MDL-5G
Solar/Wind Harmer
0
252507AC2-088 GEN
Solar/Wind Helper
1.774
253343AC1-166 GEN
Solar/Wind Helper
0.648
253325AC1-069 GEN
Solar/Wind Helper
0.671
339216AC1-074 GEN
Solar/Wind Helper
0.968
943111AE2-339 GEN
Solar/Wind Helper
0.37
24726505LAWG1B
50/50
3.884
24726805LAWG2B
50/50
3.872
24729505KEY G4
50/50
5.792
270240V3-007_GEN2
Solar/Wind Harmer
0.003
945581AF1-223 GEN
Solar/Wind Harmer
0.001
970115AG2-085 GEN
Solar/Wind Harmer
2.862
965101AG1-375 GEN
Solar/Wind Harmer
6.952
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
971609AH1-304 GEN
Solar/Wind Harmer
1.047
270594AE1-207 GEN
Solar/Wind Harmer
6.802
970289AG2-191 GEN
Solar/Wind Harmer
1.073
270024AE2-089 GEN
Solar/Wind Harmer
0.005
270543AE2-219 C
Solar/Wind Harmer
0.003
971029AG2-637 GEN
Solar/Wind Harmer
5.79
971673AH1-337 GEN
Solar/Wind Harmer
2.403
270071AF1-092 GEN
Solar/Wind Harmer
6.489
963791AG1-232 GEN
Solar/Wind Harmer
4.447
963841AG1-237 GEN
Solar/Wind Harmer
1.425
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
24387005FR-3G C
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0
270181AB1-006 GEN2
Solar/Wind Harmer
0
252524AE2-267 GEN
Solar/Wind Helper
1.139
241972AD1-140 GEN
Solar/Wind Helper
3.771
270367AC2-061_GEN
Solar/Wind Helper
2.308
270340AC2-060 GEN
Solar/Wind Helper
1.341
945631AF1-228 GEN
Solar/Wind Helper
1.149
253383AE2-342_GEN
Solar/Wind Helper
0.467
241973AD2-163_GEN1
Solar/Wind Helper
1.045
339243AC2-075 GEN1
Solar/Wind Helper
0.223
25194708EBND2
50/50
13.331
24729405KEY G3
50/50
0.316
24729305KEY G2
50/50
0.311
24729205KEY G1
50/50
0.309
247621Y3-024
50/50
0.168
24379505HDWTR1G C
Solar/Wind Harmer
0.004
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
970825AG2-519 GEN
Solar/Wind Harmer
8.038
960441AF2-335 GEN
Solar/Wind Harmer
7.155
944541AF1-119 GEN
Solar/Wind Harmer
0.448
960971AF2-388 GEN
Solar/Wind Harmer
3.922
270599AE1-208 GEN
Solar/Wind Harmer
5.878
270031AE2-169
Solar/Wind Harmer
3.527
270383AD1-128 GEN
Solar/Wind Harmer
0.004
971613AH1-306 GEN
Solar/Wind Harmer
2.915
964611AG1-324 GEN
Solar/Wind Harmer
0.407
270201AC2-176 GEN
Solar/Wind Harmer
0.001
942221AE2-234 GEN
Solar/Wind Harmer
0.023
970883AG2-550 GEN
Solar/Wind Harmer
4.236
970885AG2-551 GEN
Solar/Wind Harmer
1.412
945391AF1-204 GEN
Solar/Wind Harmer
4.007
270444AC2-157 GEN1
Solar/Wind Harmer
0.002
971587AH1-292 GEN
Solar/Wind Harmer
2.513
24728805RICHG1
Adder
1.851
24728905RICHG2
Adder
1.851
970241AG2-163 GEN
Solar/Wind Harmer
1.982
966841AG1-555 GEN
Solar/Wind Harmer
0.359
25183208HLCRTG
Solar/Wind Helper
3.041
252509AD1-136 GEN
Solar/Wind Helper
0.253
253394AE2-221_GEN
Solar/Wind Helper
1.882
253398AE2-221_GEN2
Solar/Wind Helper
1.882
962581AG1-107 GEN
Solar/Wind Helper
1.183
961491AF2-440 GEN
Solar/Wind Helper
0.049
253378AE2-206_GEN
Solar/Wind Helper
1.009
276820AF1-078_GEN
Solar/Wind Helper
0.472
270186AC1-089 GEN
Solar/Wind Helper
0.977
270518AE2-148 GEN
Solar/Wind Helper
9.191
339221AD2-048_GEN
Solar/Wind Helper
0.797
964351AG1-297 GEN
50/50
15.023
961161AF2-407 GEN
50/50
36.754
24728705AND G3
50/50
7.214
24728505AND G1
50/50
3.45
270437AC2-090 C
Solar/Wind Harmer
0.005
270356AE2-297 GEN
Solar/Wind Harmer
0.014
958821AF2-173 GEN
Solar/Wind Harmer
12.115
270004AE1-209 GEN
Solar/Wind Harmer
1.875
946031AF1-268 GEN
Solar/Wind Harmer
6.644
970289AG2-191 GEN
Solar/Wind Harmer
0.621
970291AG2-192 GEN
Solar/Wind Harmer
0.565
944531AF1-118 GEN
Solar/Wind Harmer
24.99
247642Z2-115 C
Solar/Wind Harmer
0.002
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
7.511
971617AH1-308 GEN
Solar/Wind Harmer
3.633
970193AG2-126 GEN
Solar/Wind Harmer
5.656
270222AC2-111 GEN
Solar/Wind Harmer
1.665
24755605MDL-5G
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.044
252510AF1-249 C
Solar/Wind Helper
0.75
253406AD2-031_GEN
Solar/Wind Helper
1.05
253415AE1-040 GEN
Solar/Wind Helper
0.622
253338AC1-165 GEN
Solar/Wind Helper
0.648
253333AC1-068 GEN
Solar/Wind Helper
0.671
241974AD2-163_GEN2
Solar/Wind Helper
1.045
241955AC1-078 GEN
Solar/Wind Helper
0.988
944201AF1-088_MTX
Adder
57.114
957141AF2-008_MTX
Adder
28.557
NYPJM->LTFIMP_NY
CLTF
0.528
LGEELTFEXP_LGEE->PJM
CLTF
1.157
WECLTFEXP_WEC->PJM
CLTF
1.41
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.011
AG2-052LTFEXP_AG2-052->PJM
LTF
0.096
AH1-155LTFEXP_AH1-155->PJM
LTF
0.144
LAGNLTFEXP_LAGN->PJM
CLTF
4.021
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.318
TVALTFEXP_TVA->PJM
CLTF
1.602
CBM West 1LTFEXP_CBM-W1->PJM
CBM
42.67
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.072
MECLTFEXP_MEC->PJM
CLTF
5.881
SIGELTFEXP_SIGE->PJM
CLTF
0.223
CBM West 2LTFEXP_CBM-W2->PJM
CBM
43.536

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:145.41 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:2239.27
MW Contribution:2.14
Bus #Bus NameTypeMW Contribution
24803406KYGER 5HP
50/50
4.083
24803206KYGER 4HP
50/50
4.08
252507AC2-088 GEN
Solar/Wind Harmer
0.36
25196808ZIMRHP
Adder
79.423
25194608D.CRK4
Adder
1.69
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.992
25196008MFTGT1
Adder
1.369
945681AF1-233 GEN
Solar/Wind Harmer
12.039
339216AC1-074 GEN
Solar/Wind Harmer
0.167
270263AC1-001 GEN
Solar/Wind Harmer
0.584
253370AE2-315 SEC1
Adder
1.603
253371AE2-315 SEC2
Adder
1.517
25326309TAIT D
Adder
0.846
24803006KYGER 3HP
50/50
4.129
24802806KYGER 2HP
50/50
4.105
24802906KYGER 2LP
50/50
2.413
252509AD1-136 GEN
Solar/Wind Harmer
0.04
25183208HLCRTG
Solar/Wind Harmer
0.012
252519AF1-045_GEN
Solar/Wind Harmer
6.438
252516AE2-318_GEN
Solar/Wind Harmer
5.71
25194408D.CRK1
Adder
7.772
25194508D.CRK3
Adder
1.453
24802606KYGER 1HP
50/50
4.153
24802706KYGER 1LP
50/50
2.437
24803506KYGER 5LP
50/50
2.38
25016408BKJDB1
50/50
0.276
25183008BIOENL
50/50
0.03
971985AH1-537 GEN
Solar/Wind Harmer
5.764
252524AE2-267 GEN
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
9.062
25196308WSDLE2
Adder
8.983
25196208WSDLE1
Adder
8.961
25196708WSDLE6
Adder
8.938
25196508WSDLE4
Adder
8.713
25196108MFTGT2
Adder
1.509
25196108MFTGT2
Adder
1.402
972163AH1-664 GEN
Solar/Wind Harmer
7.031
972165AH1-665 GEN
Solar/Wind Harmer
5.631
270367AC2-061_GEN
Solar/Wind Harmer
0.005
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
270340AC2-060 GEN
Solar/Wind Harmer
0.007
270269AC2-059
Solar/Wind Harmer
0.003
253372AE2-315 SEC3
Adder
1.517
253372AE2-315 SEC3
Adder
1.517
25306009OHH W.
Adder
2.274
253349AC2-067 GEN
Solar/Wind Harmer
1.699
253400AC2-068 GEN
Solar/Wind Harmer
0.683
3429211JKCT 2G
Adder
8.726
270240V3-007_GEN2
Solar/Wind Harmer
0.002
970689AG2-444 GEN
Solar/Wind Harmer
10.333
971673AH1-337 GEN
Solar/Wind Harmer
3.282
971029AG2-637 GEN
Solar/Wind Harmer
7.495
270543AE2-219 C
Solar/Wind Harmer
0.003
970115AG2-085 GEN
Solar/Wind Harmer
1.879
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
970455AG2-298 GEN
Solar/Wind Harmer
3.046
339211AE2-254 GEN
Solar/Wind Harmer
0.002
945581AF1-223 GEN
Solar/Wind Harmer
0
270432AC2-029 GEN
Solar/Wind Harmer
2.004
971609AH1-304 GEN
Solar/Wind Harmer
0.735
270594AE1-207 GEN
Solar/Wind Harmer
5.001
241972AD1-140 GEN
Solar/Wind Harmer
0.486
965101AG1-375 GEN
Solar/Wind Harmer
4.42
970289AG2-191 GEN
Solar/Wind Harmer
0.831
270024AE2-089 GEN
Solar/Wind Harmer
0.005
24729505KEY G4
Adder
3.892
965401AG1-405 GEN
Solar/Wind Harmer
2.225
965411AG1-406 GEN
Solar/Wind Harmer
1.432
963841AG1-237 GEN
Solar/Wind Harmer
1.679
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
24387005FR-3G C
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
963791AG1-232 GEN
Solar/Wind Harmer
5.01
270071AF1-092 GEN
Solar/Wind Harmer
7.101
971611AH1-305 GEN
Solar/Wind Harmer
2.203
944221AF1-090 GEN
Solar/Wind Harmer
2.159
958391AF2-133 GEN
Solar/Wind Harmer
0.001
276785W4-005 GEN1
Solar/Wind Harmer
0
276174W4-005 GEN2
Solar/Wind Harmer
0
276849AB2-070 GEN2
Solar/Wind Harmer
0.134
276848AB2-070 GEN3
Solar/Wind Harmer
0.133
276655WTG1_EQ
Solar/Wind Harmer
0.001
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.804
941731AE2-173 GEN
Solar/Wind Harmer
3.019
270536AF1-215 GEN2
Solar/Wind Harmer
0.005
970169AG2-114 GEN
Solar/Wind Harmer
3.59
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
274775LINCOLN ;6U
Adder
4.276
274776LINCOLN ;7U
Adder
4.276
274777LINCOLN ;8U
Adder
4.276
926823AC1-168 GEN
Solar/Wind Harmer
0.6
972227AH1-698 GEN1
Adder
1.32
970833AG2-524 GEN
Solar/Wind Harmer
3.883
970833AG2-524 GEN
Solar/Wind Harmer
2.589
960591AF2-350 GEN
Solar/Wind Harmer
3.529
274731ELWOOD EC;2P
Adder
8.308
274733ELWOOD EC;3P
Adder
8.308
274735ELWOOD EC;4P
Adder
8.308
274728ELWOOD EC;5P
Adder
8.308
972037AH1-567 GEN1
Adder
0.092
276868AE1-113 GEN
Solar/Wind Harmer
0.707
276882AE2-255 GEN
Solar/Wind Harmer
0.412
957751AF2-069 GEN
Solar/Wind Harmer
0.116
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
274827FISK ;RP
Adder
3.916
274675JOLIET 29;7U
Adder
15.482
274675JOLIET 29;7U
Adder
14.929
274687WILL CNTY;4U
Adder
14.101
274687WILL CNTY;4U
Adder
7.883
971675AH1-338 GEN
Solar/Wind Harmer
1.363
971177AH1-047 GEN
Solar/Wind Harmer
2.154
971411AH1-196 GEN
Solar/Wind Harmer
5.236
971171AH1-044 GEN
Solar/Wind Harmer
6.979
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
270330AC1-082 GEN2
Solar/Wind Helper
0.043
270329AC1-082 GEN1
Solar/Wind Helper
0.206
971347AH1-153 GEN
Solar/Wind Harmer
0.971
3429421JKCT 10G
Adder
6.399
960071AF2-298 GEN
Solar/Wind Harmer
2.664
970773AG2-487 GEN
Solar/Wind Harmer
0.938
3429241JKCT 3G
Adder
8.84
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
3.753
270005AE1-210 C O1
Solar/Wind Harmer
1.038
965031AG1-367 GEN
Solar/Wind Harmer
4.789
24728605AND G2
Adder
2.624
970825AG2-519 GEN
Solar/Wind Harmer
1.675
971565AH1-281 GEN
Solar/Wind Harmer
0.942
247536S-71 GEN
Solar/Wind Harmer
0.189
945371AF1-202 GEN
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
5.056
971821AH1-427 GEN
Solar/Wind Harmer
4.468
270032AE2-172
Solar/Wind Harmer
2.977
958861AF2-177 GEN
Solar/Wind Harmer
1.915
970291AG2-192 GEN
Solar/Wind Harmer
0.569
965651AG1-433 GEN
Solar/Wind Harmer
1.28
970091AG2-072 GEN
Adder
45.505
253343AC1-166 GEN
Solar/Wind Harmer
0.002
253325AC1-069 GEN
Solar/Wind Harmer
0.006
270445AC2-157 GEN2
Solar/Wind Harmer
0.002
970333AG2-219 GEN
Solar/Wind Harmer
2.902
963741AG1-226 GEN
Solar/Wind Harmer
9.27
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.001
24791305MDL-5G
Solar/Wind Harmer
0.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
4.626
274880W4-005 GEN4
Solar/Wind Harmer
0
963831AG1-236 GEN
Solar/Wind Harmer
1.429
276615X2-022 GEN
Solar/Wind Harmer
0.038
965911AG1-460 GEN
Solar/Wind Harmer
0.732
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
4.754
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964901AG1-354 GEN
Solar/Wind Harmer
5.476
972175AH1-670 GEN
Solar/Wind Harmer
3.016
970245AG2-165 GEN
Solar/Wind Harmer
1.581
274854TWINGROVE;U2
Solar/Wind Harmer
0.002
276726Z2-087_GEN
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
5.072
270055AF2-134 C O1
Solar/Wind Harmer
0.003
970373AG2-245 GEN
Solar/Wind Harmer
7.519
939401AE1-172 GEN
Solar/Wind Harmer
2.671
970273AG2-179 GEN
Solar/Wind Harmer
1.245
941551AE2-152 GEN
Solar/Wind Harmer
0
274773LINCOLN ;4U
Adder
4.276
274774LINCOLN ;5U
Adder
4.276
276901AD2-066 C O1
Solar/Wind Harmer
0.003
971997AH1-543 GEN
Solar/Wind Harmer
1.852
274871GR RIDGE ;2U
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
0.368
274732ELWOOD EC;7P
Adder
8.308
274674JOLIET 9 ;6U
Adder
7.776
274801UNIV PARK;4U
Adder
2.945
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
276691AA1-018 GEN1
Solar/Wind Harmer
0.427
970569AG2-363 GEN
Solar/Wind Harmer
10.571
276164X3-005 C
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
15.482
962241AG1-070 GEN
Solar/Wind Harmer
1.916
274877BISHOP HL;1U
Solar/Wind Harmer
0.118
962781AG1-127 GEN
Solar/Wind Harmer
3.331
274872LEEDK;1U
Solar/Wind Harmer
0.002
276861AD2-134 GEN
Solar/Wind Harmer
0.063
957471AF2-041 GEN
Solar/Wind Harmer
10.469
959081AF2-199 GEN
Solar/Wind Harmer
3.49
971067AG2-660 GEN
Solar/Wind Harmer
1.163
960001AF2-291 GEN
Solar/Wind Helper
1.722
270331AC1-082 GEN3
Solar/Wind Helper
0.205
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
253394AE2-221_GEN
Solar/Wind Harmer
0.008
253398AE2-221_GEN2
Solar/Wind Harmer
0.008
270186AC1-089 GEN
Solar/Wind Harmer
0.004
970235AG2-159 GEN
Solar/Wind Harmer
3.745
970235AG2-159 GEN
Solar/Wind Harmer
2.149
962581AG1-107 GEN
Solar/Wind Harmer
0.001
339221AD2-048_GEN
Solar/Wind Harmer
0.004
972043AH1-570 GEN
Solar/Wind Harmer
1.516
972045AH1-571 GEN
Solar/Wind Harmer
1.215
971125AH1-004 GEN
Solar/Wind Harmer
2.272
970107AG2-081 GEN
Solar/Wind Harmer
1.704
253370AE2-315 SEC1
Adder
1.603
24728805RICHG1
Adder
2.949
24728905RICHG2
Adder
2.949
25322209TAIT E
Adder
7.54
25322209TAIT E
Adder
7.371
25326109MON D
Adder
0.986
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
942891AE2-308 GEN
Solar/Wind Harmer
5.114
270383AD1-128 GEN
Solar/Wind Harmer
0.003
970883AG2-550 GEN
Solar/Wind Harmer
4.843
970885AG2-551 GEN
Solar/Wind Harmer
1.614
960161AF2-307 GEN
Solar/Wind Harmer
3.166
970825AG2-519 GEN
Solar/Wind Harmer
5.23
960441AF2-335 GEN
Solar/Wind Harmer
4.696
247621Y3-024
Adder
0.159
964611AG1-324 GEN
Solar/Wind Harmer
0.342
270201AC2-176 GEN
Solar/Wind Harmer
0.001
270599AE1-208 GEN
Solar/Wind Harmer
4.125
270031AE2-169
Solar/Wind Harmer
2.475
964571AG1-320 GEN
Solar/Wind Harmer
4.08
971613AH1-306 GEN
Solar/Wind Harmer
2.143
944541AF1-119 GEN
Solar/Wind Harmer
0.292
960971AF2-388 GEN
Solar/Wind Harmer
2.559
970653AG2-424 GEN
Solar/Wind Harmer
2.067
970653AG2-424 GEN
Solar/Wind Harmer
1.071
942221AE2-234 GEN
Solar/Wind Harmer
0.02
270444AC2-157 GEN1
Solar/Wind Harmer
0.002
971587AH1-292 GEN
Solar/Wind Harmer
2.992
945391AF1-204 GEN
Solar/Wind Harmer
4.315
970239AG2-162 GEN
Solar/Wind Harmer
1.015
970241AG2-163 GEN
Solar/Wind Harmer
2.285
971081AG2-670 GEN
Solar/Wind Harmer
2.933
966841AG1-555 GEN
Solar/Wind Harmer
0.433
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
270518AE2-148 GEN
Solar/Wind Harmer
0.321
25326509SID D
Adder
0.697
276916AD2-100_GEN
Solar/Wind Harmer
7.697
276911AD2-131_GEN
Solar/Wind Harmer
0.507
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
970321AG2-212 GEN
Solar/Wind Harmer
1.581
960611AF2-352 GEN
Solar/Wind Harmer
1.21
274770LINCOLN ;1U
Adder
4.276
274771LINCOLN ;2U
Adder
4.276
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
274888KELLY CRK;1U
Solar/Wind Harmer
0.207
274887GEN-1.85
Solar/Wind Harmer
0.093
276843GEN-1.7
Solar/Wind Harmer
0.114
958011AF2-095 GEN
Solar/Wind Harmer
5.082
972259AH1-714 GEN
Adder
9.649
274674JOLIET 9 ;6U
Adder
7.776
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
958481AF2-142 GEN
Solar/Wind Harmer
5.285
958491AF2-143 GEN
Solar/Wind Harmer
5.285
274803UNIV PARK;6U
Adder
2.944
274879MINONK ;1U
Solar/Wind Harmer
0.149
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.477
274851PROVIDENC;RU
Solar/Wind Harmer
0
274849CRESCENT ;1U
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.139
276646AC1-214 GEN2
Solar/Wind Harmer
0.139
276782AC1-033 GEN
Solar/Wind Harmer
0.001
971573AH1-285 GEN
Solar/Wind Harmer
0.654
339255AE2-071 GEN
Solar/Wind Harmer
-0.058
962691AG1-118 GEN
Solar/Wind Harmer
10.504
970921AG2-575 GEN
Solar/Wind Harmer
3.5
970921AG2-575 GEN
Solar/Wind Harmer
1.167
964781AG1-341 GEN
Solar/Wind Harmer
3.707
942991AE2-321 GEN
Solar/Wind Harmer
3.901
971333AH1-146 GEN
Solar/Wind Harmer
6.981
971335AH1-147 GEN
Solar/Wind Harmer
6.981
971341AH1-150 GEN
Solar/Wind Harmer
6.979
971343AH1-151 GEN
Solar/Wind Harmer
6.979
237033AB1-150 GEN
Solar/Wind Helper
0.4
24803106KYGER 3LP
50/50
2.431
24803306KYGER 4LP
50/50
2.38
971191AH1-055 GEN
Solar/Wind Harmer
68.697
25194608D.CRK4
Adder
1.69
25196608WSDLE5
Adder
8.803
252510AF1-249 C
Solar/Wind Harmer
0.055
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
9.09
25196008MFTGT1
Adder
1.326
958171AF2-111 GEN
Solar/Wind Harmer
17.035
972167AH1-666 GEN
Solar/Wind Harmer
5.13
253406AD2-031_GEN
Solar/Wind Harmer
0.461
972173AH1-669 GEN
Solar/Wind Harmer
3.047
270222AC2-111 GEN
Solar/Wind Harmer
2.955
270273AD2-016 GEN
Solar/Wind Harmer
0.603
253415AE1-040 GEN
Solar/Wind Harmer
0.002
253370AE2-315 SEC1
Adder
1.603
253371AE2-315 SEC2
Adder
1.517
970191AG2-125 GEN
Solar/Wind Harmer
1.388
3429391JKCT 9G
Adder
6.399
270356AE2-297 GEN
Solar/Wind Harmer
0.007
270437AC2-090 C
Solar/Wind Harmer
0.002
970093AG2-073 GEN
Solar/Wind Harmer
4.888
958821AF2-173 GEN
Solar/Wind Harmer
6.704
270004AE1-209 GEN
Solar/Wind Harmer
1.038
24728705AND G3
Adder
5.489
24728505AND G1
Adder
2.624
966571AG1-526 GEN
Solar/Wind Harmer
10.492
946031AF1-268 GEN
Solar/Wind Harmer
4.488
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
6.776
970289AG2-191 GEN
Solar/Wind Harmer
0.481
970291AG2-192 GEN
Solar/Wind Harmer
0.437
247642Z2-115 C
Solar/Wind Harmer
0.002
971617AH1-308 GEN
Solar/Wind Harmer
3.507
944531AF1-118 GEN
Solar/Wind Harmer
18.471
253338AC1-165 GEN
Solar/Wind Harmer
0.002
253333AC1-068 GEN
Solar/Wind Harmer
0.006
970193AG2-126 GEN
Solar/Wind Harmer
6.091
970243AG2-164 GEN
Solar/Wind Harmer
2.375
970519AG2-331 GEN
Solar/Wind Harmer
10.553
970699AG2-449 GEN
Solar/Wind Harmer
1.015
960741AF2-365 GEN
Solar/Wind Harmer
1.902
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
3.773
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
276686W4-005 GEN3
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
1.693
276668AB2-070 GEN1
Solar/Wind Harmer
0.134
276621W2-048 GEN
Solar/Wind Harmer
0.185
276838X2-022 GEN2
Solar/Wind Harmer
0.206
942481AE2-261 GEN
Solar/Wind Harmer
10.947
964401AG1-302 GEN
Solar/Wind Harmer
0.001
970513AG2-328 GEN
Solar/Wind Harmer
1.581
970517AG2-330 GEN
Solar/Wind Harmer
9.486
972273AH1-721 GEN
Adder
43.396
274853TWINGROVE;U1
Solar/Wind Harmer
0.001
965091AG1-374 GEN
Solar/Wind Harmer
10.888
959611AF2-252 GEN
Solar/Wind Harmer
1.21
942111AE2-223 GEN
Solar/Wind Harmer
1.177
270535AF1-215 GEN1
Solar/Wind Harmer
0.005
970273AG2-179 GEN
Solar/Wind Harmer
2.134
276897AD1-100 C
Solar/Wind Harmer
0.005
939351AE1-166 GEN
Solar/Wind Harmer
0
274772LINCOLN ;3U
Adder
4.276
972228AH1-698 GEN2
Adder
1.875
276806AD2-047 C O1
Solar/Wind Harmer
2
970941AG2-585 GEN
Solar/Wind Harmer
4.411
274729ELWOOD EC;1P
Adder
8.308
276893AG1-478 C
Solar/Wind Harmer
0.14
274730ELWOOD EC;6P
Adder
8.308
274734ELWOOD EC;8P
Adder
8.308
274736ELWOOD EC;9P
Adder
8.308
970707AG2-453 GEN
Solar/Wind Harmer
11.517
274800UNIV PARK;3U
Adder
2.945
972038AH1-567 GEN2
Adder
0.184
276694AA1-018 GEN2
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0.001
276889AE2-281 GEN
Solar/Wind Harmer
0
970571AG2-364 GEN
Solar/Wind Harmer
7.047
274802UNIV PARK;5U
Adder
2.944
270043AE2-236 GEN
Solar/Wind Harmer
2.261
274826FISK ;BP
Adder
5.526
274676JOLIET 29;8U
Adder
14.929
962251AG1-071 GEN
Solar/Wind Harmer
2.197
274878BISHOP HL;2U
Solar/Wind Harmer
0.118
943121AE2-341 GEN
Solar/Wind Harmer
5.891
943591AF1-030 GEN
Solar/Wind Harmer
3.917
339250AF1-203 GEN
Solar/Wind Harmer
0.001
274872LEEDK;1U
Solar/Wind Harmer
0.128
971155AH1-034 GEN
Solar/Wind Harmer
4.077
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.373
274855GSG-6 ;RU
Solar/Wind Harmer
0.128
274850MENDOTA H;RU
Solar/Wind Harmer
0.041
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.063
959091AF2-200 GEN
Solar/Wind Harmer
6.979
235780M24_1
Solar/Wind Helper
0.99
970349AG2-230 GEN
Solar/Wind Harmer
0.971
944201AF1-088_MTX
Adder
67.999
957141AF2-008_MTX
Adder
33.999
NYPJM->LTFIMP_NY
CLTF
1.661
LGEELTFEXP_LGEE->PJM
CLTF
5.141
WECLTFEXP_WEC->PJM
CLTF
1.904
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.285
AG2-052LTFEXP_AG2-052->PJM
LTF
0.122
AH1-155LTFEXP_AH1-155->PJM
LTF
0.183
LAGNLTFEXP_LAGN->PJM
CLTF
6.556
TVALTFEXP_TVA->PJM
CLTF
3.109
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.042
CBM West 1LTFEXP_CBM-W1->PJM
CBM
72.325
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.636
MECLTFEXP_MEC->PJM
CLTF
8.008
SIGELTFEXP_SIGE->PJM
CLTF
0.331
CBM West 2LTFEXP_CBM-W2->PJM
CBM
58.397

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P1-2_#309_15_SRT-A


Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#309_15_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:141.78 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:2183.34
MW Contribution:2.04
Bus #Bus NameTypeMW Contribution
24802606KYGER 1HP
50/50
4.205
24802706KYGER 1LP
50/50
2.468
24803506KYGER 5LP
50/50
2.41
25016408BKJDB1
50/50
0.29
25183008BIOENL
50/50
0.032
971985AH1-537 GEN
Solar/Wind Harmer
5.902
252524AE2-267 GEN
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
9.532
25196308WSDLE2
Adder
9.449
25196208WSDLE1
Adder
9.426
25196708WSDLE6
Adder
9.402
25196508WSDLE4
Adder
9.165
25196108MFTGT2
Adder
1.577
25196108MFTGT2
Adder
1.464
972163AH1-664 GEN
Solar/Wind Harmer
7.374
972165AH1-665 GEN
Solar/Wind Harmer
5.906
270367AC2-061_GEN
Solar/Wind Harmer
0.005
270269AC2-059
Solar/Wind Harmer
0.004
270340AC2-060 GEN
Solar/Wind Harmer
0.007
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
253372AE2-315 SEC3
Adder
1.625
253372AE2-315 SEC3
Adder
1.625
25306009OHH W.
Adder
2.427
970689AG2-444 GEN
Solar/Wind Harmer
11.775
253349AC2-067 GEN
Solar/Wind Harmer
1.803
253400AC2-068 GEN
Solar/Wind Harmer
0.725
3429211JKCT 2G
Adder
8.965
270432AC2-029 GEN
Solar/Wind Harmer
2.302
971673AH1-337 GEN
Solar/Wind Harmer
3.274
270240V3-007_GEN2
Solar/Wind Harmer
0.001
971029AG2-637 GEN
Solar/Wind Harmer
7.455
241972AD1-140 GEN
Solar/Wind Harmer
0.537
270543AE2-219 C
Solar/Wind Harmer
0.003
970455AG2-298 GEN
Solar/Wind Harmer
3.084
339211AE2-254 GEN
Solar/Wind Harmer
0.002
970115AG2-085 GEN
Solar/Wind Harmer
1.802
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
270594AE1-207 GEN
Solar/Wind Harmer
4.766
971609AH1-304 GEN
Solar/Wind Harmer
0.693
945581AF1-223 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.789
965101AG1-375 GEN
Solar/Wind Harmer
4.056
270024AE2-089 GEN
Solar/Wind Harmer
0.004
965401AG1-405 GEN
Solar/Wind Harmer
2.199
965411AG1-406 GEN
Solar/Wind Harmer
1.415
270156DARBY CT1
Adder
4.836
270157DARBY CT2
Adder
4.825
270158DARBY CT3
Adder
4.747
24729505KEY G4
Adder
3.463
972203AH1-686 GEN
Adder
1.225
963841AG1-237 GEN
Solar/Wind Harmer
1.584
945631AF1-228 GEN
Solar/Wind Harmer
0
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
24387005FR-3G C
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
944221AF1-090 GEN
Solar/Wind Harmer
2.022
971611AH1-305 GEN
Solar/Wind Harmer
2.007
276785W4-005 GEN1
Solar/Wind Harmer
0
276174W4-005 GEN2
Solar/Wind Harmer
0
276849AB2-070 GEN2
Solar/Wind Harmer
0.123
276848AB2-070 GEN3
Solar/Wind Harmer
0.122
963791AG1-232 GEN
Solar/Wind Harmer
4.535
958391AF2-133 GEN
Solar/Wind Harmer
0
943861AF1-054 GEN
Solar/Wind Harmer
1.276
943851AF1-053 GEN
Solar/Wind Harmer
0.884
276655WTG1_EQ
Solar/Wind Harmer
0.001
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.422
941731AE2-173 GEN
Solar/Wind Harmer
2.716
270536AF1-215 GEN2
Solar/Wind Harmer
0.004
270071AF1-092 GEN
Solar/Wind Harmer
6.133
970169AG2-114 GEN
Solar/Wind Harmer
3.189
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
957751AF2-069 GEN
Solar/Wind Harmer
0.103
926823AC1-168 GEN
Solar/Wind Harmer
0.529
276868AE1-113 GEN
Solar/Wind Harmer
0.619
276882AE2-255 GEN
Solar/Wind Harmer
0.361
970833AG2-524 GEN
Solar/Wind Harmer
3.372
970833AG2-524 GEN
Solar/Wind Harmer
2.248
274731ELWOOD EC;2P
Adder
7.212
274733ELWOOD EC;3P
Adder
7.212
274735ELWOOD EC;4P
Adder
7.212
274728ELWOOD EC;5P
Adder
7.212
972227AH1-698 GEN1
Adder
1.144
960591AF2-350 GEN
Solar/Wind Harmer
3.057
961011AF2-392 GEN
Solar/Wind Harmer
1.791
274675JOLIET 29;7U
Adder
13.422
274675JOLIET 29;7U
Adder
12.942
274687WILL CNTY;4U
Adder
12.222
274687WILL CNTY;4U
Adder
12.222
971681AH1-341 GEN
Solar/Wind Harmer
4.912
274746AC1-111 G10
Adder
2.444
274744AC1-111 GEN8
Adder
2.444
971171AH1-044 GEN
Solar/Wind Harmer
6.1
971675AH1-338 GEN
Solar/Wind Harmer
1.189
972037AH1-567 GEN1
Adder
0.08
946321AF1-296 GEN
Solar/Wind Harmer
1.708
270330AC1-082 GEN2
Solar/Wind Helper
0.041
270329AC1-082 GEN1
Solar/Wind Helper
0.199
24803406KYGER 5HP
50/50
4.134
24803206KYGER 4HP
50/50
4.13
252507AC2-088 GEN
Solar/Wind Harmer
0.38
25196808ZIMRHP
Adder
83.68
25194608D.CRK4
Adder
1.777
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.481
25196008MFTGT1
Adder
1.431
945681AF1-233 GEN
Solar/Wind Harmer
12.638
270263AC1-001 GEN
Solar/Wind Harmer
0.653
339216AC1-074 GEN
Solar/Wind Harmer
0.174
253370AE2-315 SEC1
Adder
1.718
253371AE2-315 SEC2
Adder
1.625
25326309TAIT D
Adder
0.908
960071AF2-298 GEN
Solar/Wind Harmer
2.849
3429421JKCT 10G
Adder
6.595
3429241JKCT 3G
Adder
9.082
970773AG2-487 GEN
Solar/Wind Harmer
0.935
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
3.657
971565AH1-281 GEN
Solar/Wind Harmer
0.959
24728605AND G2
Adder
2.584
253343AC1-166 GEN
Solar/Wind Harmer
0.002
253325AC1-069 GEN
Solar/Wind Harmer
0.007
247536S-71 GEN
Solar/Wind Harmer
0.185
270005AE1-210 C O1
Solar/Wind Harmer
0.992
965031AG1-367 GEN
Solar/Wind Harmer
4.578
970825AG2-519 GEN
Solar/Wind Harmer
1.608
971821AH1-427 GEN
Solar/Wind Harmer
4.505
970091AG2-072 GEN
Adder
49.379
970333AG2-219 GEN
Solar/Wind Harmer
3.125
276903AD2-071 C
Solar/Wind Harmer
4.849
270032AE2-172
Solar/Wind Harmer
2.837
945371AF1-202 GEN
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.54
270445AC2-157 GEN2
Solar/Wind Harmer
0.002
958861AF2-177 GEN
Solar/Wind Harmer
1.758
965651AG1-433 GEN
Solar/Wind Harmer
1.166
270159DARBY CT4
Adder
4.759
963741AG1-226 GEN
Solar/Wind Harmer
8.802
970593AG2-378 GEN
Solar/Wind Harmer
0.808
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.001
964901AG1-354 GEN
Solar/Wind Harmer
5.358
24791305MDL-5G
Solar/Wind Harmer
0
970273AG2-179 GEN
Solar/Wind Harmer
1.212
962241AG1-070 GEN
Solar/Wind Harmer
1.862
965911AG1-460 GEN
Solar/Wind Harmer
0.679
276615X2-022 GEN
Solar/Wind Harmer
0.035
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
4.214
963831AG1-236 GEN
Solar/Wind Harmer
1.313
274880W4-005 GEN4
Solar/Wind Harmer
0
972175AH1-670 GEN
Solar/Wind Harmer
2.749
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.279
958381AF2-132 GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0.001
276726Z2-087_GEN
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
4.562
270055AF2-134 C O1
Solar/Wind Harmer
0.002
970373AG2-245 GEN
Solar/Wind Harmer
6.619
970245AG2-165 GEN
Solar/Wind Harmer
1.366
939401AE1-172 GEN
Solar/Wind Harmer
2.35
274877BISHOP HL;1U
Solar/Wind Harmer
0.105
970569AG2-363 GEN
Solar/Wind Harmer
9.313
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
971997AH1-543 GEN
Solar/Wind Harmer
1.624
276901AD2-066 C O1
Solar/Wind Harmer
0.003
941551AE2-152 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.372
276158O29GEN2
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
7.212
276776AD2-060 GEN
Solar/Wind Harmer
0.319
274674JOLIET 9 ;6U
Adder
6.747
274676JOLIET 29;8U
Adder
13.422
274801UNIV PARK;4U
Adder
2.55
274745AC1-111 GEN9
Adder
2.444
276861AD2-134 GEN
Solar/Wind Harmer
0.055
957471AF2-041 GEN
Solar/Wind Harmer
9.15
959081AF2-199 GEN
Solar/Wind Harmer
3.05
971067AG2-660 GEN
Solar/Wind Harmer
1.017
274872LEEDK;1U
Solar/Wind Harmer
0.002
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
962781AG1-127 GEN
Solar/Wind Harmer
2.901
960001AF2-291 GEN
Solar/Wind Helper
1.676
270331AC1-082 GEN3
Solar/Wind Helper
0.198
24803006KYGER 3HP
50/50
4.181
24802806KYGER 2HP
50/50
4.156
24802906KYGER 2LP
50/50
2.443
252509AD1-136 GEN
Solar/Wind Harmer
0.042
25183208HLCRTG
Solar/Wind Harmer
0.012
252519AF1-045_GEN
Solar/Wind Harmer
6.799
252516AE2-318_GEN
Solar/Wind Harmer
6.03
25194408D.CRK1
Adder
8.173
25194508D.CRK3
Adder
1.528
253317AC1-085 GEN4
Solar/Wind Harmer
0.005
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
270186AC1-089 GEN
Solar/Wind Harmer
0.004
962581AG1-107 GEN
Solar/Wind Harmer
0.001
970235AG2-159 GEN
Solar/Wind Harmer
3.893
970235AG2-159 GEN
Solar/Wind Harmer
2.234
339221AD2-048_GEN
Solar/Wind Harmer
0.004
972043AH1-570 GEN
Solar/Wind Harmer
1.576
972045AH1-571 GEN
Solar/Wind Harmer
1.263
253370AE2-315 SEC1
Adder
1.718
971125AH1-004 GEN
Solar/Wind Harmer
2.354
970107AG2-081 GEN
Solar/Wind Harmer
1.765
25322209TAIT E
Adder
8.088
25322209TAIT E
Adder
7.906
25326109MON D
Adder
1.064
24728805RICHG1
Adder
2.986
24728905RICHG2
Adder
2.986
942891AE2-308 GEN
Solar/Wind Harmer
5.244
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0.003
960161AF2-307 GEN
Solar/Wind Harmer
3.231
970883AG2-550 GEN
Solar/Wind Harmer
4.773
970885AG2-551 GEN
Solar/Wind Harmer
1.591
970825AG2-519 GEN
Solar/Wind Harmer
5.021
964571AG1-320 GEN
Solar/Wind Harmer
4.118
960441AF2-335 GEN
Solar/Wind Harmer
4.504
247621Y3-024
Adder
0.155
964611AG1-324 GEN
Solar/Wind Harmer
0.33
970239AG2-162 GEN
Solar/Wind Harmer
1.093
270201AC2-176 GEN
Solar/Wind Harmer
0.001
970653AG2-424 GEN
Solar/Wind Harmer
2.075
970653AG2-424 GEN
Solar/Wind Harmer
1.075
971613AH1-306 GEN
Solar/Wind Harmer
2.042
270518AE2-148 GEN
Solar/Wind Harmer
0.367
270599AE1-208 GEN
Solar/Wind Harmer
3.89
270031AE2-169
Solar/Wind Harmer
2.334
270444AC2-157 GEN1
Solar/Wind Harmer
0.002
971587AH1-292 GEN
Solar/Wind Harmer
3.032
25326509SID D
Adder
0.76
944541AF1-119 GEN
Solar/Wind Harmer
0.266
960971AF2-388 GEN
Solar/Wind Harmer
2.332
945391AF1-204 GEN
Solar/Wind Harmer
4.178
971081AG2-670 GEN
Solar/Wind Harmer
2.902
942221AE2-234 GEN
Solar/Wind Harmer
0.019
253378AE2-206_GEN
Solar/Wind Harmer
0.002
276820AF1-078_GEN
Solar/Wind Harmer
0.001
970329AG2-216 GEN
Solar/Wind Harmer
1.613
970241AG2-163 GEN
Solar/Wind Harmer
2.169
970077AG2-063 GEN
Solar/Wind Harmer
2.064
966841AG1-555 GEN
Solar/Wind Harmer
0.406
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
276916AD2-100_GEN
Solar/Wind Harmer
7.156
276911AD2-131_GEN
Solar/Wind Harmer
0.471
339255AE2-071 GEN
Solar/Wind Harmer
-0.056
964781AG1-341 GEN
Solar/Wind Harmer
3.601
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
942861AE2-305 GEN
Solar/Wind Harmer
2.586
960611AF2-352 GEN
Solar/Wind Harmer
1.093
970321AG2-212 GEN
Solar/Wind Harmer
1.366
274851PROVIDENC;RU
Solar/Wind Harmer
0
274849CRESCENT ;1U
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.123
276646AC1-214 GEN2
Solar/Wind Harmer
0.123
971485AH1-239 GEN
Solar/Wind Harmer
2.495
276782AC1-033 GEN
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
274879MINONK ;1U
Solar/Wind Harmer
0.13
958491AF2-143 GEN
Solar/Wind Harmer
4.624
966021AG1-471 GEN
Solar/Wind Harmer
1.664
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.416
958481AF2-142 GEN
Solar/Wind Harmer
4.61
276741O09 GEN1
Solar/Wind Harmer
0.109
276708O09 GEN2
Solar/Wind Harmer
0.109
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
274888KELLY CRK;1U
Solar/Wind Harmer
0.18
274887GEN-1.85
Solar/Wind Harmer
0.08
276843GEN-1.7
Solar/Wind Harmer
0.099
958011AF2-095 GEN
Solar/Wind Harmer
4.402
274674JOLIET 9 ;6U
Adder
6.747
972259AH1-714 GEN
Adder
8.351
276603SUBLETTE C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
1.821
971341AH1-150 GEN
Solar/Wind Harmer
6.1
971343AH1-151 GEN
Solar/Wind Harmer
6.1
274803UNIV PARK;6U
Adder
2.549
938861AE1-114 GEN
Solar/Wind Harmer
1.728
962691AG1-118 GEN
Solar/Wind Harmer
9.146
274764LEE CO EC;5U
Adder
4.075
274765LEE CO EC;6U
Adder
2.574
970921AG2-575 GEN
Solar/Wind Harmer
3.048
970921AG2-575 GEN
Solar/Wind Harmer
1.016
971573AH1-285 GEN
Solar/Wind Harmer
0.568
237033AB1-150 GEN
Solar/Wind Helper
0.403
971333AH1-146 GEN
Solar/Wind Harmer
3.002
971335AH1-147 GEN
Solar/Wind Harmer
3.002
24803106KYGER 3LP
50/50
2.461
24803306KYGER 4LP
50/50
2.41
971191AH1-055 GEN
Solar/Wind Harmer
70.447
25194608D.CRK4
Adder
1.777
25196608WSDLE5
Adder
9.26
252510AF1-249 C
Solar/Wind Harmer
0.058
253316AC1-085 GEN3
Solar/Wind Harmer
0.005
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
9.726
958171AF2-111 GEN
Solar/Wind Harmer
17.961
25196008MFTGT1
Adder
1.385
972173AH1-669 GEN
Solar/Wind Harmer
3.407
972167AH1-666 GEN
Solar/Wind Harmer
5.387
253406AD2-031_GEN
Solar/Wind Harmer
0.496
270273AD2-016 GEN
Solar/Wind Harmer
0.676
253415AE1-040 GEN
Solar/Wind Harmer
0.003
270222AC2-111 GEN
Solar/Wind Harmer
3.033
253370AE2-315 SEC1
Adder
1.718
253371AE2-315 SEC2
Adder
1.625
970191AG2-125 GEN
Solar/Wind Harmer
1.473
3429391JKCT 9G
Adder
6.595
270356AE2-297 GEN
Solar/Wind Harmer
0.007
270437AC2-090 C
Solar/Wind Harmer
0.002
970093AG2-073 GEN
Solar/Wind Harmer
4.986
966571AG1-526 GEN
Solar/Wind Harmer
10.654
24728705AND G3
Adder
5.404
24728505AND G1
Adder
2.584
253338AC1-165 GEN
Solar/Wind Harmer
0.002
253333AC1-068 GEN
Solar/Wind Harmer
0.007
958821AF2-173 GEN
Solar/Wind Harmer
6.409
270004AE1-209 GEN
Solar/Wind Harmer
0.992
946031AF1-268 GEN
Solar/Wind Harmer
4.321
970243AG2-164 GEN
Solar/Wind Harmer
2.557
970519AG2-331 GEN
Solar/Wind Harmer
11.364
970699AG2-449 GEN
Solar/Wind Harmer
1.093
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
6.542
970289AG2-191 GEN
Solar/Wind Harmer
0.457
970291AG2-192 GEN
Solar/Wind Harmer
0.416
247642Z2-115 C
Solar/Wind Harmer
0.002
971617AH1-308 GEN
Solar/Wind Harmer
3.313
970193AG2-126 GEN
Solar/Wind Harmer
5.898
960741AF2-365 GEN
Solar/Wind Harmer
1.874
944531AF1-118 GEN
Solar/Wind Harmer
16.287
970605AG2-385 GEN
Solar/Wind Harmer
2.184
972273AH1-721 GEN
Adder
42.389
24755605MDL-5G
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.498
970273AG2-179 GEN
Solar/Wind Harmer
2.077
962251AG1-071 GEN
Solar/Wind Harmer
2.135
339250AF1-203 GEN
Solar/Wind Harmer
0.001
942481AE2-261 GEN
Solar/Wind Harmer
10.156
971155AH1-034 GEN
Solar/Wind Harmer
3.958
276621W2-048 GEN
Solar/Wind Harmer
0.17
276838X2-022 GEN2
Solar/Wind Harmer
0.19
276686W4-005 GEN3
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
1.555
276668AB2-070 GEN1
Solar/Wind Harmer
0.123
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
964401AG1-302 GEN
Solar/Wind Harmer
0
274853TWINGROVE;U1
Solar/Wind Harmer
0.001
965091AG1-374 GEN
Solar/Wind Harmer
9.838
959611AF2-252 GEN
Solar/Wind Harmer
1.093
942111AE2-223 GEN
Solar/Wind Harmer
1.059
270535AF1-215 GEN1
Solar/Wind Harmer
0.004
970513AG2-328 GEN
Solar/Wind Harmer
1.366
970517AG2-330 GEN
Solar/Wind Harmer
8.195
274878BISHOP HL;2U
Solar/Wind Harmer
0.105
970571AG2-364 GEN
Solar/Wind Harmer
6.209
942051AE2-217 GEN
Solar/Wind Harmer
5.584
276889AE2-281 GEN
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0.001
276897AD1-100 C
Solar/Wind Harmer
0.004
939351AE1-166 GEN
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.496
276893AG1-478 C
Solar/Wind Harmer
0.121
274729ELWOOD EC;1P
Adder
7.212
274730ELWOOD EC;6P
Adder
7.212
274734ELWOOD EC;8P
Adder
7.212
274736ELWOOD EC;9P
Adder
7.212
972228AH1-698 GEN2
Adder
1.624
276806AD2-047 C O1
Solar/Wind Harmer
1.732
970941AG2-585 GEN
Solar/Wind Harmer
3.821
274676JOLIET 29;8U
Adder
12.942
274800UNIV PARK;3U
Adder
2.55
972038AH1-567 GEN2
Adder
0.16
274855GSG-6 ;RU
Solar/Wind Harmer
0.112
274850MENDOTA H;RU
Solar/Wind Harmer
0.036
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.055
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.325
959091AF2-200 GEN
Solar/Wind Harmer
6.1
274802UNIV PARK;5U
Adder
2.549
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
965931AG1-462 GEN
Solar/Wind Harmer
7.774
274872LEEDK;1U
Solar/Wind Harmer
0.112
235780M24_1
Solar/Wind Helper
0.999
944201AF1-088_MTX
Adder
68.911
957141AF2-008_MTX
Adder
34.455
NYPJM->LTFIMP_NY
CLTF
1.591
LGEELTFEXP_LGEE->PJM
CLTF
5.309
WECLTFEXP_WEC->PJM
CLTF
1.664
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.623
AG2-052LTFEXP_AG2-052->PJM
LTF
0.109
AH1-155LTFEXP_AH1-155->PJM
LTF
0.163
LAGNLTFEXP_LAGN->PJM
CLTF
5.672
TVALTFEXP_TVA->PJM
CLTF
2.671
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.271
CBM West 1LTFEXP_CBM-W1->PJM
CBM
65.759
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.454
MECLTFEXP_MEC->PJM
CLTF
7.145
SIGELTFEXP_SIGE->PJM
CLTF
0.331
CBM West 2LTFEXP_CBM-W2->PJM
CBM
53.937

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:131.72 %
Rating:1189.0 MVA
Rating Type:A
MVA to Mitigate:1566.09
MW Contribution:1.81
Bus #Bus NameTypeMW Contribution
24803006KYGER 3HP
50/50
4.149
24802806KYGER 2HP
50/50
4.125
24802906KYGER 2LP
50/50
2.425
252509AD1-136 GEN
Solar/Wind Harmer
0.04
25183208HLCRTG
Solar/Wind Harmer
0.012
252519AF1-045_GEN
Solar/Wind Harmer
6.35
252516AE2-318_GEN
Solar/Wind Harmer
5.632
25194408D.CRK1
Adder
7.616
25194508D.CRK3
Adder
1.424
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
253394AE2-221_GEN
Solar/Wind Harmer
0.008
253398AE2-221_GEN2
Solar/Wind Harmer
0.008
270186AC1-089 GEN
Solar/Wind Harmer
0.004
962581AG1-107 GEN
Solar/Wind Harmer
0.001
970235AG2-159 GEN
Solar/Wind Harmer
3.613
970235AG2-159 GEN
Solar/Wind Harmer
2.073
339221AD2-048_GEN
Solar/Wind Harmer
0.004
972043AH1-570 GEN
Solar/Wind Harmer
1.484
972045AH1-571 GEN
Solar/Wind Harmer
1.189
253370AE2-315 SEC1
Adder
1.592
971125AH1-004 GEN
Solar/Wind Harmer
2.215
970107AG2-081 GEN
Solar/Wind Harmer
1.662
25322209TAIT E
Adder
7.486
25322209TAIT E
Adder
7.317
25326109MON D
Adder
0.984
24728805RICHG1
Adder
2.73
24728905RICHG2
Adder
2.73
942891AE2-308 GEN
Solar/Wind Harmer
4.97
960161AF2-307 GEN
Solar/Wind Harmer
3.112
24379505HDWTR1G C
Solar/Wind Harmer
0.001
270209AC1-174_GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0.003
970883AG2-550 GEN
Solar/Wind Harmer
4.325
970885AG2-551 GEN
Solar/Wind Harmer
1.442
964571AG1-320 GEN
Solar/Wind Harmer
3.821
970825AG2-519 GEN
Solar/Wind Harmer
4.514
960441AF2-335 GEN
Solar/Wind Harmer
4.047
247621Y3-024
Adder
0.139
970653AG2-424 GEN
Solar/Wind Harmer
1.943
970653AG2-424 GEN
Solar/Wind Harmer
1.007
964611AG1-324 GEN
Solar/Wind Harmer
0.297
270201AC2-176 GEN
Solar/Wind Harmer
0.001
270518AE2-148 GEN
Solar/Wind Harmer
0.337
270599AE1-208 GEN
Solar/Wind Harmer
3.479
270031AE2-169
Solar/Wind Harmer
2.087
971613AH1-306 GEN
Solar/Wind Harmer
1.811
971081AG2-670 GEN
Solar/Wind Harmer
2.763
25326509SID D
Adder
0.693
270444AC2-157 GEN1
Solar/Wind Harmer
0.002
971587AH1-292 GEN
Solar/Wind Harmer
2.6
944541AF1-119 GEN
Solar/Wind Harmer
0.237
960971AF2-388 GEN
Solar/Wind Harmer
2.079
970239AG2-162 GEN
Solar/Wind Harmer
0.884
945391AF1-204 GEN
Solar/Wind Harmer
3.646
253378AE2-206_GEN
Solar/Wind Harmer
0.002
276820AF1-078_GEN
Solar/Wind Harmer
0.001
970329AG2-216 GEN
Solar/Wind Harmer
1.467
942221AE2-234 GEN
Solar/Wind Harmer
0.017
339255AE2-071 GEN
Solar/Wind Harmer
-0.054
970077AG2-063 GEN
Solar/Wind Harmer
1.879
964781AG1-341 GEN
Solar/Wind Harmer
3.457
970241AG2-163 GEN
Solar/Wind Harmer
1.873
966841AG1-555 GEN
Solar/Wind Harmer
0.348
971485AH1-239 GEN
Solar/Wind Harmer
2.448
966021AG1-471 GEN
Solar/Wind Harmer
1.637
942861AE2-305 GEN
Solar/Wind Harmer
2.346
237033AB1-150 GEN
Solar/Wind Helper
0.372
24802606KYGER 1HP
50/50
4.173
24802706KYGER 1LP
50/50
2.449
24803506KYGER 5LP
50/50
2.392
25016408BKJDB1
50/50
0.272
25183008BIOENL
50/50
0.03
971985AH1-537 GEN
Solar/Wind Harmer
5.759
252524AE2-267 GEN
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
8.879
25196308WSDLE2
Adder
8.801
25196208WSDLE1
Adder
8.779
25196708WSDLE6
Adder
8.757
25196508WSDLE4
Adder
8.537
25196108MFTGT2
Adder
1.463
25196108MFTGT2
Adder
1.358
972163AH1-664 GEN
Solar/Wind Harmer
6.955
972165AH1-665 GEN
Solar/Wind Harmer
5.57
270367AC2-061_GEN
Solar/Wind Harmer
0.005
270269AC2-059
Solar/Wind Harmer
0.003
270340AC2-060 GEN
Solar/Wind Harmer
0.007
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
253372AE2-315 SEC3
Adder
1.506
253372AE2-315 SEC3
Adder
1.506
25306009OHH W.
Adder
2.247
970689AG2-444 GEN
Solar/Wind Harmer
10.893
253349AC2-067 GEN
Solar/Wind Harmer
1.665
253400AC2-068 GEN
Solar/Wind Harmer
0.67
3429211JKCT 2G
Adder
8.494
270432AC2-029 GEN
Solar/Wind Harmer
2.121
971673AH1-337 GEN
Solar/Wind Harmer
2.979
241972AD1-140 GEN
Solar/Wind Harmer
0.495
270240V3-007_GEN2
Solar/Wind Harmer
0.001
971029AG2-637 GEN
Solar/Wind Harmer
6.776
339211AE2-254 GEN
Solar/Wind Harmer
0.002
270543AE2-219 C
Solar/Wind Harmer
0.003
970455AG2-298 GEN
Solar/Wind Harmer
2.878
970115AG2-085 GEN
Solar/Wind Harmer
1.619
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
971609AH1-304 GEN
Solar/Wind Harmer
0.62
270594AE1-207 GEN
Solar/Wind Harmer
4.227
945581AF1-223 GEN
Solar/Wind Harmer
0
965401AG1-405 GEN
Solar/Wind Harmer
2.132
965411AG1-406 GEN
Solar/Wind Harmer
1.371
970289AG2-191 GEN
Solar/Wind Harmer
0.697
965101AG1-375 GEN
Solar/Wind Harmer
3.623
270024AE2-089 GEN
Solar/Wind Harmer
0.004
270156DARBY CT1
Adder
4.415
270157DARBY CT2
Adder
4.404
270158DARBY CT3
Adder
4.334
24729505KEY G4
Adder
3.073
945631AF1-228 GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
1.363
24386205FR-12G C
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
24387005FR-3G C
Solar/Wind Harmer
0.001
944221AF1-090 GEN
Solar/Wind Harmer
1.779
943861AF1-054 GEN
Solar/Wind Harmer
1.158
943851AF1-053 GEN
Solar/Wind Harmer
0.802
270330AC1-082 GEN2
Solar/Wind Helper
0.041
270329AC1-082 GEN1
Solar/Wind Helper
0.199
24803106KYGER 3LP
50/50
2.442
24803306KYGER 4LP
50/50
2.392
971191AH1-055 GEN
Solar/Wind Harmer
69.07
25194608D.CRK4
Adder
1.656
25196608WSDLE5
Adder
8.625
252510AF1-249 C
Solar/Wind Harmer
0.054
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
9.086
958171AF2-111 GEN
Solar/Wind Harmer
16.854
25196008MFTGT1
Adder
1.285
972167AH1-666 GEN
Solar/Wind Harmer
5.077
972173AH1-669 GEN
Solar/Wind Harmer
3.165
253406AD2-031_GEN
Solar/Wind Harmer
0.462
270273AD2-016 GEN
Solar/Wind Harmer
0.628
253415AE1-040 GEN
Solar/Wind Harmer
0.002
253370AE2-315 SEC1
Adder
1.592
253371AE2-315 SEC2
Adder
1.506
270222AC2-111 GEN
Solar/Wind Harmer
2.79
970191AG2-125 GEN
Solar/Wind Harmer
1.36
3429391JKCT 9G
Adder
6.235
270356AE2-297 GEN
Solar/Wind Harmer
0.006
970093AG2-073 GEN
Solar/Wind Harmer
4.742
966571AG1-526 GEN
Solar/Wind Harmer
10.106
270437AC2-090 C
Solar/Wind Harmer
0.002
253338AC1-165 GEN
Solar/Wind Harmer
0.002
253333AC1-068 GEN
Solar/Wind Harmer
0.007
24728705AND G3
Adder
4.853
24728505AND G1
Adder
2.32
958821AF2-173 GEN
Solar/Wind Harmer
5.771
270004AE1-209 GEN
Solar/Wind Harmer
0.893
946031AF1-268 GEN
Solar/Wind Harmer
3.889
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
5.885
970289AG2-191 GEN
Solar/Wind Harmer
0.403
970291AG2-192 GEN
Solar/Wind Harmer
0.367
247642Z2-115 C
Solar/Wind Harmer
0.002
971617AH1-308 GEN
Solar/Wind Harmer
2.961
960741AF2-365 GEN
Solar/Wind Harmer
1.775
970243AG2-164 GEN
Solar/Wind Harmer
2.07
970519AG2-331 GEN
Solar/Wind Harmer
9.199
970699AG2-449 GEN
Solar/Wind Harmer
0.884
972273AH1-721 GEN
Adder
41.409
970193AG2-126 GEN
Solar/Wind Harmer
5.147
970273AG2-179 GEN
Solar/Wind Harmer
2.017
339250AF1-203 GEN
Solar/Wind Harmer
0
962251AG1-071 GEN
Solar/Wind Harmer
2.045
970605AG2-385 GEN
Solar/Wind Harmer
1.988
971155AH1-034 GEN
Solar/Wind Harmer
3.802
944531AF1-118 GEN
Solar/Wind Harmer
14.426
235780M24_1
Solar/Wind Helper
0.923
24803406KYGER 5HP
50/50
4.102
24803206KYGER 4HP
50/50
4.099
252507AC2-088 GEN
Solar/Wind Harmer
0.356
25196808ZIMRHP
Adder
78.156
25194608D.CRK4
Adder
1.656
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.99
25196008MFTGT1
Adder
1.327
945681AF1-233 GEN
Solar/Wind Harmer
11.914
270263AC1-001 GEN
Solar/Wind Harmer
0.606
339216AC1-074 GEN
Solar/Wind Harmer
0.163
253370AE2-315 SEC1
Adder
1.592
253371AE2-315 SEC2
Adder
1.506
25326309TAIT D
Adder
0.84
960071AF2-298 GEN
Solar/Wind Harmer
2.635
3429421JKCT 10G
Adder
6.235
3429241JKCT 3G
Adder
8.606
970773AG2-487 GEN
Solar/Wind Harmer
0.849
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
3.314
971565AH1-281 GEN
Solar/Wind Harmer
0.891
253343AC1-166 GEN
Solar/Wind Harmer
0.002
253325AC1-069 GEN
Solar/Wind Harmer
0.007
971821AH1-427 GEN
Solar/Wind Harmer
4.286
24728605AND G2
Adder
2.32
247536S-71 GEN
Solar/Wind Harmer
0.167
270005AE1-210 C O1
Solar/Wind Harmer
0.893
965031AG1-367 GEN
Solar/Wind Harmer
4.122
970825AG2-519 GEN
Solar/Wind Harmer
1.446
276903AD2-071 C
Solar/Wind Harmer
4.31
270032AE2-172
Solar/Wind Harmer
2.516
945371AF1-202 GEN
Solar/Wind Harmer
0
970091AG2-072 GEN
Adder
40.612
970291AG2-192 GEN
Solar/Wind Harmer
0.477
958861AF2-177 GEN
Solar/Wind Harmer
1.57
270445AC2-157 GEN2
Solar/Wind Harmer
0.002
965651AG1-433 GEN
Solar/Wind Harmer
1.04
970333AG2-219 GEN
Solar/Wind Harmer
2.53
270159DARBY CT4
Adder
4.344
964901AG1-354 GEN
Solar/Wind Harmer
5.126
970273AG2-179 GEN
Solar/Wind Harmer
1.177
962241AG1-070 GEN
Solar/Wind Harmer
1.783
970593AG2-378 GEN
Solar/Wind Harmer
0.735
963741AG1-226 GEN
Solar/Wind Harmer
7.599
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.001
960001AF2-291 GEN
Solar/Wind Helper
1.682
270331AC1-082 GEN3
Solar/Wind Helper
0.198
944201AF1-088_MTX
Adder
59.081
957141AF2-008_MTX
Adder
29.541
NYPJM->LTFIMP_NY
CLTF
1.447
LGEELTFEXP_LGEE->PJM
CLTF
4.851
WECLTFEXP_WEC->PJM
CLTF
1.45
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.226
AG2-052LTFEXP_AG2-052->PJM
LTF
0.094
AH1-155LTFEXP_AH1-155->PJM
LTF
0.141
LAGNLTFEXP_LAGN->PJM
CLTF
5.678
TVALTFEXP_TVA->PJM
CLTF
2.775
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.02
CBM West 1LTFEXP_CBM-W1->PJM
CBM
58.512
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.324
MECLTFEXP_MEC->PJM
CLTF
6.369
SIGELTFEXP_SIGE->PJM
CLTF
0.3
CBM West 2LTFEXP_CBM-W2->PJM
CBM
50.459

Details for 06PIERCE-05MARQUI 345.0 kV Ckt 1 line l/o AEP_P1-2_#709_546_SRT-A


Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06PIERCE-05MARQUI 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#709_546_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.36 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:1561.02
MW Contribution:2.07
Bus #Bus NameTypeMW Contribution
25016408BKJDB1
50/50
0.315
25196108MFTGT2
Adder
1.559
25196108MFTGT2
Adder
1.448
252524AE2-267 GEN
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
8.856
25196308WSDLE2
Adder
8.779
25196208WSDLE1
Adder
8.757
25196708WSDLE6
Adder
8.735
25196508WSDLE4
Adder
8.515
971985AH1-537 GEN
Solar/Wind Harmer
2.063
270240V3-007_GEN2
Solar/Wind Harmer
0.002
971673AH1-337 GEN
Solar/Wind Harmer
3.056
971029AG2-637 GEN
Solar/Wind Harmer
6.982
270543AE2-219 C
Solar/Wind Harmer
0.003
970115AG2-085 GEN
Solar/Wind Harmer
1.798
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
270594AE1-207 GEN
Solar/Wind Harmer
4.833
253349AC2-067 GEN
Solar/Wind Harmer
1.341
253400AC2-068 GEN
Solar/Wind Harmer
0.539
970289AG2-191 GEN
Solar/Wind Harmer
0.806
971609AH1-304 GEN
Solar/Wind Harmer
0.692
945581AF1-223 GEN
Solar/Wind Harmer
0
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
25306009OHH W.
Adder
1.706
253372AE2-315 SEC3
Adder
1.113
253372AE2-315 SEC3
Adder
1.113
965101AG1-375 GEN
Solar/Wind Harmer
4.064
970455AG2-298 GEN
Solar/Wind Harmer
2.674
963841AG1-237 GEN
Solar/Wind Harmer
1.675
270024AE2-089 GEN
Solar/Wind Harmer
0.004
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
24387005FR-3G C
Solar/Wind Harmer
0.001
24729505KEY G4
Adder
3.46
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
944221AF1-090 GEN
Solar/Wind Harmer
2.096
971611AH1-305 GEN
Solar/Wind Harmer
2.122
958391AF2-133 GEN
Solar/Wind Harmer
0.001
276785W4-005 GEN1
Solar/Wind Harmer
0
276174W4-005 GEN2
Solar/Wind Harmer
0
276849AB2-070 GEN2
Solar/Wind Harmer
0.127
276848AB2-070 GEN3
Solar/Wind Harmer
0.127
270536AF1-215 GEN2
Solar/Wind Harmer
0.004
276655WTG1_EQ
Solar/Wind Harmer
0.001
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.547
941731AE2-173 GEN
Solar/Wind Harmer
2.815
339211AE2-254 GEN
Solar/Wind Harmer
0.001
970169AG2-114 GEN
Solar/Wind Harmer
3.303
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
4.381
270071AF1-092 GEN
Solar/Wind Harmer
6.208
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
3429211JKCT 2G
Adder
5.399
957751AF2-069 GEN
Solar/Wind Harmer
0.106
926823AC1-168 GEN
Solar/Wind Harmer
0.547
276868AE1-113 GEN
Solar/Wind Harmer
0.639
276882AE2-255 GEN
Solar/Wind Harmer
0.373
970833AG2-524 GEN
Solar/Wind Harmer
3.487
970833AG2-524 GEN
Solar/Wind Harmer
2.324
274731ELWOOD EC;2P
Adder
7.457
274733ELWOOD EC;3P
Adder
7.457
274735ELWOOD EC;4P
Adder
7.457
972227AH1-698 GEN1
Adder
1.183
274728ELWOOD EC;5P
Adder
7.457
960591AF2-350 GEN
Solar/Wind Harmer
3.162
274675JOLIET 29;7U
Adder
13.874
274675JOLIET 29;7U
Adder
13.378
274687WILL CNTY;4U
Adder
12.634
274687WILL CNTY;4U
Adder
12.634
972037AH1-567 GEN1
Adder
0.083
274827FISK ;RP
Adder
3.505
274746AC1-111 G10
Adder
2.525
274744AC1-111 GEN8
Adder
2.525
274814UNIV PK N;0U
Adder
2.28
274807UNIV PK N;3U
Adder
2.275
274805UNIV PK N;1U
Adder
2.265
274811UNIV PK N;7U
Adder
2.261
274775LINCOLN ;6U
Adder
3.805
274776LINCOLN ;7U
Adder
3.805
274777LINCOLN ;8U
Adder
1.515
971675AH1-338 GEN
Solar/Wind Harmer
1.227
971171AH1-044 GEN
Solar/Wind Harmer
6.288
961011AF2-392 GEN
Solar/Wind Harmer
1.844
971681AH1-341 GEN
Solar/Wind Harmer
5.059
971177AH1-047 GEN
Solar/Wind Harmer
1.937
971411AH1-196 GEN
Solar/Wind Harmer
4.711
25196008MFTGT1
Adder
1.414
25196008MFTGT1
Adder
1.37
25196608WSDLE5
Adder
8.603
25194608D.CRK4
Adder
1.625
252510AF1-249 C
Solar/Wind Harmer
0.052
270222AC2-111 GEN
Solar/Wind Harmer
2.803
270356AE2-297 GEN
Solar/Wind Harmer
0.007
970243AG2-164 GEN
Solar/Wind Harmer
2.969
970519AG2-331 GEN
Solar/Wind Harmer
13.197
970699AG2-449 GEN
Solar/Wind Harmer
1.269
270437AC2-090 C
Solar/Wind Harmer
0.002
24728705AND G3
Adder
5.469
24728505AND G1
Adder
2.615
958821AF2-173 GEN
Solar/Wind Harmer
6.444
270004AE1-209 GEN
Solar/Wind Harmer
0.997
946031AF1-268 GEN
Solar/Wind Harmer
4.275
970191AG2-125 GEN
Solar/Wind Harmer
1.095
970289AG2-191 GEN
Solar/Wind Harmer
0.466
970291AG2-192 GEN
Solar/Wind Harmer
0.424
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
6.308
247642Z2-115 C
Solar/Wind Harmer
0.002
970193AG2-126 GEN
Solar/Wind Harmer
6.187
253370AE2-315 SEC1
Adder
1.177
253371AE2-315 SEC2
Adder
1.113
971617AH1-308 GEN
Solar/Wind Harmer
3.198
24755605MDL-5G
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.711
944531AF1-118 GEN
Solar/Wind Harmer
16.26
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
942481AE2-261 GEN
Solar/Wind Harmer
10.525
276621W2-048 GEN
Solar/Wind Harmer
0.176
276838X2-022 GEN2
Solar/Wind Harmer
0.197
276686W4-005 GEN3
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
1.613
276668AB2-070 GEN1
Solar/Wind Harmer
0.127
964401AG1-302 GEN
Solar/Wind Harmer
0.001
966571AG1-526 GEN
Solar/Wind Harmer
7.577
274853TWINGROVE;U1
Solar/Wind Harmer
0.001
965091AG1-374 GEN
Solar/Wind Harmer
10.199
959611AF2-252 GEN
Solar/Wind Harmer
1.133
270535AF1-215 GEN1
Solar/Wind Harmer
0.004
942111AE2-223 GEN
Solar/Wind Harmer
1.098
970513AG2-328 GEN
Solar/Wind Harmer
1.448
970517AG2-330 GEN
Solar/Wind Harmer
8.688
960741AF2-365 GEN
Solar/Wind Harmer
1.664
3429391JKCT 9G
Adder
3.902
274878BISHOP HL;2U
Solar/Wind Harmer
0.108
970571AG2-364 GEN
Solar/Wind Harmer
6.41
276889AE2-281 GEN
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0.001
276897AD1-100 C
Solar/Wind Harmer
0.004
939351AE1-166 GEN
Solar/Wind Harmer
0
970093AG2-073 GEN
Solar/Wind Harmer
3.181
276694AA1-018 GEN2
Solar/Wind Harmer
0
276893AG1-478 C
Solar/Wind Harmer
0.125
274729ELWOOD EC;1P
Adder
7.457
972228AH1-698 GEN2
Adder
1.68
274730ELWOOD EC;6P
Adder
7.457
274734ELWOOD EC;8P
Adder
7.457
274736ELWOOD EC;9P
Adder
7.457
276806AD2-047 C O1
Solar/Wind Harmer
1.792
970941AG2-585 GEN
Solar/Wind Harmer
3.953
276157O29GEN1
Solar/Wind Harmer
0.511
274800UNIV PARK;3U
Adder
2.637
972038AH1-567 GEN2
Adder
0.165
274676JOLIET 29;8U
Adder
13.378
274802UNIV PARK;5U
Adder
2.636
274826FISK ;BP
Adder
4.945
970707AG2-453 GEN
Solar/Wind Harmer
10.286
943121AE2-341 GEN
Solar/Wind Harmer
5.278
943591AF1-030 GEN
Solar/Wind Harmer
3.51
274772LINCOLN ;3U
Adder
3.805
274872LEEDK;1U
Solar/Wind Harmer
0.115
274855GSG-6 ;RU
Solar/Wind Harmer
0.115
274850MENDOTA H;RU
Solar/Wind Harmer
0.037
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.056
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.335
959091AF2-200 GEN
Solar/Wind Harmer
6.288
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
965931AG1-462 GEN
Solar/Wind Harmer
7.987
962251AG1-071 GEN
Solar/Wind Harmer
1.885
958171AF2-111 GEN
Solar/Wind Harmer
7.532
970349AG2-230 GEN
Solar/Wind Harmer
4.502
957541AF2-048 GEN
Solar/Wind Helper
0.879
270273AD2-016 GEN
Solar/Wind Helper
1.449
25194408D.CRK1
Adder
7.477
25194508D.CRK3
Adder
1.398
252509AD1-136 GEN
Solar/Wind Harmer
0.034
252519AF1-045_GEN
Solar/Wind Harmer
5.274
252516AE2-318_GEN
Solar/Wind Harmer
4.678
970235AG2-159 GEN
Solar/Wind Harmer
3.613
970235AG2-159 GEN
Solar/Wind Harmer
2.073
24728805RICHG1
Adder
2.818
24728905RICHG2
Adder
2.818
970239AG2-162 GEN
Solar/Wind Harmer
1.269
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
25183208HLCRTG
Solar/Wind Harmer
0.007
270383AD1-128 GEN
Solar/Wind Harmer
0.003
970825AG2-519 GEN
Solar/Wind Harmer
5.005
970883AG2-550 GEN
Solar/Wind Harmer
4.51
970885AG2-551 GEN
Solar/Wind Harmer
1.503
960441AF2-335 GEN
Solar/Wind Harmer
4.495
270444AC2-157 GEN1
Solar/Wind Harmer
0.002
971587AH1-292 GEN
Solar/Wind Harmer
3.281
971613AH1-306 GEN
Solar/Wind Harmer
2.071
247621Y3-024
Adder
0.148
964611AG1-324 GEN
Solar/Wind Harmer
0.32
270599AE1-208 GEN
Solar/Wind Harmer
3.883
270031AE2-169
Solar/Wind Harmer
2.33
270201AC2-176 GEN
Solar/Wind Harmer
0.001
945391AF1-204 GEN
Solar/Wind Harmer
4.382
964571AG1-320 GEN
Solar/Wind Harmer
3.758
253370AE2-315 SEC1
Adder
1.177
25322209TAIT E
Adder
5.698
25322209TAIT E
Adder
5.57
944541AF1-119 GEN
Solar/Wind Harmer
0.267
960971AF2-388 GEN
Solar/Wind Harmer
2.335
25326109MON D
Adder
0.742
339221AD2-048_GEN
Solar/Wind Harmer
0.002
970241AG2-163 GEN
Solar/Wind Harmer
2.29
966841AG1-555 GEN
Solar/Wind Harmer
0.43
970653AG2-424 GEN
Solar/Wind Harmer
1.834
970653AG2-424 GEN
Solar/Wind Harmer
0.95
942221AE2-234 GEN
Solar/Wind Harmer
0.018
971125AH1-004 GEN
Solar/Wind Harmer
1.469
970107AG2-081 GEN
Solar/Wind Harmer
1.102
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
972043AH1-570 GEN
Solar/Wind Harmer
0.949
972045AH1-571 GEN
Solar/Wind Harmer
0.76
276916AD2-100_GEN
Solar/Wind Harmer
7.418
276911AD2-131_GEN
Solar/Wind Harmer
0.489
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
960611AF2-352 GEN
Solar/Wind Harmer
1.133
970321AG2-212 GEN
Solar/Wind Harmer
1.448
942891AE2-308 GEN
Solar/Wind Harmer
3.277
971081AG2-670 GEN
Solar/Wind Harmer
2.441
274851PROVIDENC;RU
Solar/Wind Harmer
0
274849CRESCENT ;1U
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.127
276646AC1-214 GEN2
Solar/Wind Harmer
0.127
276782AC1-033 GEN
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
274879MINONK ;1U
Solar/Wind Harmer
0.134
958491AF2-143 GEN
Solar/Wind Harmer
4.777
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.43
958481AF2-142 GEN
Solar/Wind Harmer
4.764
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
274888KELLY CRK;1U
Solar/Wind Harmer
0.186
274887GEN-1.85
Solar/Wind Harmer
0.083
276843GEN-1.7
Solar/Wind Harmer
0.102
958011AF2-095 GEN
Solar/Wind Harmer
4.553
274674JOLIET 9 ;6U
Adder
6.975
276741O09 GEN1
Solar/Wind Harmer
0.113
276708O09 GEN2
Solar/Wind Harmer
0.113
972259AH1-714 GEN
Adder
8.636
274803UNIV PARK;6U
Adder
2.636
274808UNIV PK N;4U
Adder
2.251
971573AH1-285 GEN
Solar/Wind Harmer
0.586
274696ROCKY RD ;4P
Adder
5.14
274695ROCKY RD ;2P
Adder
5.022
274693ROCKY RD ;1P
Adder
4.972
276612AE2-035 GEN
Solar/Wind Harmer
0.001
946321AF1-296 GEN
Solar/Wind Harmer
1.755
241972AD1-140 GEN
Solar/Wind Harmer
0.34
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971769AH1-391 GEN
Solar/Wind Harmer
3.38
971347AH1-153 GEN
Solar/Wind Harmer
4.502
270330AC1-082 GEN2
Solar/Wind Helper
0.021
270329AC1-082 GEN1
Solar/Wind Helper
0.099
274697ROCKY RD ;3P
Adder
1.364
962691AG1-118 GEN
Solar/Wind Harmer
9.438
274770LINCOLN ;1U
Adder
3.805
274771LINCOLN ;2U
Adder
3.805
970921AG2-575 GEN
Solar/Wind Harmer
3.145
970921AG2-575 GEN
Solar/Wind Harmer
1.048
276603SUBLETTE C
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
6.288
971343AH1-151 GEN
Solar/Wind Harmer
6.288
942991AE2-321 GEN
Solar/Wind Harmer
3.508
971333AH1-146 GEN
Solar/Wind Harmer
6.283
971335AH1-147 GEN
Solar/Wind Harmer
6.283
938861AE1-114 GEN
Solar/Wind Harmer
1.78
274856ECOGROVE ;U1
Solar/Wind Harmer
0.074
276611AD2-172 GEN
Solar/Wind Harmer
0.001
965681AG1-436 GEN
Solar/Wind Harmer
3.864
965791AG1-447 GEN
Solar/Wind Harmer
2.834
24441505OLIV SLR
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0.004
25194608D.CRK4
Adder
1.625
252507AC2-088 GEN
Solar/Wind Harmer
0.307
25196808ZIMRHP
Adder
62.29
970773AG2-487 GEN
Solar/Wind Harmer
0.942
970091AG2-072 GEN
Adder
56.565
970333AG2-219 GEN
Solar/Wind Harmer
3.629
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
3.697
24728605AND G2
Adder
2.615
270005AE1-210 C O1
Solar/Wind Harmer
0.997
965031AG1-367 GEN
Solar/Wind Harmer
4.603
970825AG2-519 GEN
Solar/Wind Harmer
1.603
270445AC2-157 GEN2
Solar/Wind Harmer
0.002
276903AD2-071 C
Solar/Wind Harmer
4.926
247536S-71 GEN
Solar/Wind Harmer
0.176
270032AE2-172
Solar/Wind Harmer
2.877
970291AG2-192 GEN
Solar/Wind Harmer
0.551
971565AH1-281 GEN
Solar/Wind Harmer
0.847
945371AF1-202 GEN
Solar/Wind Harmer
0
339216AC1-074 GEN
Solar/Wind Harmer
0.113
960071AF2-298 GEN
Solar/Wind Harmer
2.043
253370AE2-315 SEC1
Adder
1.177
253371AE2-315 SEC2
Adder
1.113
25326309TAIT D
Adder
0.64
958861AF2-177 GEN
Solar/Wind Harmer
1.761
965651AG1-433 GEN
Solar/Wind Harmer
1.167
963741AG1-226 GEN
Solar/Wind Harmer
9.29
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.001
24791305MDL-5G
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
4.455
965911AG1-460 GEN
Solar/Wind Harmer
0.704
276615X2-022 GEN
Solar/Wind Harmer
0.037
274880W4-005 GEN4
Solar/Wind Harmer
0
963831AG1-236 GEN
Solar/Wind Harmer
1.362
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.508
958381AF2-132 GEN
Solar/Wind Harmer
0.001
972175AH1-670 GEN
Solar/Wind Harmer
2.851
274854TWINGROVE;U2
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0.003
276726Z2-087_GEN
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
4.729
970245AG2-165 GEN
Solar/Wind Harmer
1.448
971821AH1-427 GEN
Solar/Wind Harmer
3.331
970373AG2-245 GEN
Solar/Wind Harmer
6.927
3429421JKCT 10G
Adder
3.902
939401AE1-172 GEN
Solar/Wind Harmer
2.433
3429241JKCT 3G
Adder
5.47
274877BISHOP HL;1U
Solar/Wind Harmer
0.108
970569AG2-363 GEN
Solar/Wind Harmer
9.614
971997AH1-543 GEN
Solar/Wind Harmer
1.678
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
276901AD2-066 C O1
Solar/Wind Harmer
0.003
941551AE2-152 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.385
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
7.457
276776AD2-060 GEN
Solar/Wind Harmer
0.33
274674JOLIET 9 ;6U
Adder
6.975
276158O29GEN2
Solar/Wind Harmer
0
274801UNIV PARK;4U
Adder
2.637
274676JOLIET 29;8U
Adder
13.874
274745AC1-111 GEN9
Adder
2.525
274812UNIV PK N;8U
Adder
2.261
276164X3-005 C
Solar/Wind Harmer
0
274773LINCOLN ;4U
Adder
3.805
274774LINCOLN ;5U
Adder
3.805
274872LEEDK;1U
Solar/Wind Harmer
0.002
276861AD2-134 GEN
Solar/Wind Harmer
0.056
962781AG1-127 GEN
Solar/Wind Harmer
2.993
957471AF2-041 GEN
Solar/Wind Harmer
9.432
959081AF2-199 GEN
Solar/Wind Harmer
3.144
971067AG2-660 GEN
Solar/Wind Harmer
1.048
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
970819AG2-516 GEN
Solar/Wind Harmer
3.764
971475AH1-234 GEN
Solar/Wind Harmer
1.52
964901AG1-354 GEN
Solar/Wind Harmer
4.633
962241AG1-070 GEN
Solar/Wind Harmer
1.643
927014AC1-188 GEN
Solar/Wind Helper
0.876
270263AC1-001 GEN
Solar/Wind Helper
0.622
270331AC1-082 GEN3
Solar/Wind Helper
0.099
960001AF2-291 GEN
Solar/Wind Helper
0.551
944201AF1-088_MTX
Adder
74.561
957141AF2-008_MTX
Adder
37.28
NYPJM->LTFIMP_NY
CLTF
1.072
LGEELTFEXP_LGEE->PJM
CLTF
5.218
WECLTFEXP_WEC->PJM
CLTF
1.713
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.651
AG2-052LTFEXP_AG2-052->PJM
LTF
0.113
AH1-155LTFEXP_AH1-155->PJM
LTF
0.169
LAGNLTFEXP_LAGN->PJM
CLTF
5.322
TVALTFEXP_TVA->PJM
CLTF
2.383
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.331
CBM West 1LTFEXP_CBM-W1->PJM
CBM
55.91
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.478
MECLTFEXP_MEC->PJM
CLTF
7.273
SIGELTFEXP_SIGE->PJM
CLTF
0.331
CBM West 2LTFEXP_CBM-W2->PJM
CBM
53.307

Details for AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:138.82 %
Rating:1868.0 MVA
Rating Type:B
MVA to Mitigate:2593.18
MW Contribution:2.35
Bus #Bus NameTypeMW Contribution
965431AG1-411 GEN
50/50
45.408
24727105RPMNG2
50/50
3.32
970583AG2-370 GEN
50/50
2.809
959331AF2-224 GEN
Solar/Wind Harmer
9.634
965021AG1-366 GEN
Solar/Wind Harmer
4.588
970031AG2-029 GEN
Solar/Wind Harmer
5.463
270043AE2-236 GEN
Solar/Wind Harmer
5.191
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.046
944531AF1-118 GEN
Solar/Wind Harmer
31.488
971617AH1-308 GEN
Solar/Wind Harmer
5.166
247643Z2-116 C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
4.805
970349AG2-230 GEN
Solar/Wind Harmer
8.688
24642205MAYFLWER
Adder
0.524
24441205WTRV SLR C
Solar/Wind Harmer
0
970513AG2-328 GEN
Solar/Wind Harmer
2.307
970517AG2-330 GEN
Solar/Wind Harmer
13.84
274752CRETE EC ;2U
Adder
6.241
274753CRETE EC ;3U
Adder
6.241
274724RIVER EC ;11
Adder
13.364
247604X1-042
Adder
0.313
270535AF1-215 GEN1
Solar/Wind Harmer
0.007
274772LINCOLN ;3U
Adder
6.292
274802UNIV PARK;5U
Adder
4.319
274826FISK ;BP
Adder
8.102
274800UNIV PARK;3U
Adder
4.307
972038AH1-567 GEN2
Adder
0.27
276806AD2-047 C O1
Solar/Wind Harmer
2.917
970941AG2-585 GEN
Solar/Wind Harmer
6.434
964401AG1-302 GEN
Solar/Wind Harmer
0.001
972228AH1-698 GEN2
Adder
2.725
970707AG2-453 GEN
Solar/Wind Harmer
16.709
276897AD1-100 C
Solar/Wind Harmer
0.007
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
21.601
276893AG1-478 C
Solar/Wind Harmer
0.201
274730ELWOOD EC;6P
Adder
11.97
274734ELWOOD EC;8P
Adder
11.97
274736ELWOOD EC;9P
Adder
11.97
274729ELWOOD EC;1P
Adder
11.97
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
943121AE2-341 GEN
Solar/Wind Harmer
8.419
943591AF1-030 GEN
Solar/Wind Harmer
5.599
247642Z2-115 C
Solar/Wind Harmer
0.002
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
12.782
24727005RPMNG1
50/50
3.308
960861AF2-377 GEN
50/50
2.399
970521AG2-332 GEN
50/50
10.806
24639705ELKHART HY
50/50
0.149
965421AG1-410 GEN
Solar/Wind Harmer
81.734
965011AG1-365 GEN
Solar/Wind Harmer
13.763
270063AE2-323 C
Solar/Wind Harmer
0.006
247521TR3_G114
Solar/Wind Harmer
0.262
270246TR4_N_V150
Solar/Wind Harmer
0.046
944231AF1-091 GEN
Solar/Wind Harmer
1.854
24695305TIMB G C
Solar/Wind Harmer
0.002
965651AG1-433 GEN
Solar/Wind Harmer
1.839
958861AF2-177 GEN
Solar/Wind Harmer
2.638
945111AF1-176 GEN
Solar/Wind Harmer
10.578
270505AE1-170 C O1
Solar/Wind Harmer
6.07
945371AF1-202 GEN
Solar/Wind Harmer
0
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.97
970245AG2-165 GEN
Solar/Wind Harmer
2.307
970373AG2-245 GEN
Solar/Wind Harmer
11.147
274751CRETE EC ;1U
Adder
6.241
274754CRETE EC ;4U
Adder
6.241
274723RIVER EC ;12
Adder
13.527
274812UNIV PK N;8U
Adder
3.75
276164X3-005 C
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0.004
274773LINCOLN ;4U
Adder
6.292
274774LINCOLN ;5U
Adder
6.292
274801UNIV PARK;4U
Adder
4.307
276776AD2-060 GEN
Solar/Wind Harmer
0.537
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
6.671
941551AE2-152 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
22.401
274674JOLIET 9 ;6U
Adder
11.217
274732ELWOOD EC;7P
Adder
11.97
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
6.288
274745AC1-111 GEN9
Adder
4.021
276691AA1-018 GEN1
Solar/Wind Harmer
0.604
274682WAUKEGAN ;7U
Adder
12.782
970291AG2-192 GEN
Solar/Wind Harmer
0.645
274828WAUKEGAN ;BP
Adder
7.846
270005AE1-210 C O1
Solar/Wind Harmer
1.068
965031AG1-367 GEN
Solar/Wind Harmer
4.929
962781AG1-127 GEN
Solar/Wind Harmer
4.676
939401AE1-172 GEN
Solar/Wind Harmer
3.674
276901AD2-066 C O1
Solar/Wind Harmer
0.005
270032AE2-172
Solar/Wind Harmer
3.269
274872LEEDK;1U
Solar/Wind Harmer
0.003
971997AH1-543 GEN
Solar/Wind Harmer
2.559
276861AD2-134 GEN
Solar/Wind Harmer
0.087
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
24791305MDL-5G
Solar/Wind Harmer
0.001
957471AF2-041 GEN
Solar/Wind Harmer
14.477
959081AF2-199 GEN
Solar/Wind Harmer
4.826
971067AG2-660 GEN
Solar/Wind Harmer
1.609
274822ROCKFORD ;11
Adder
13.533
970825AG2-519 GEN
Solar/Wind Harmer
1.705
972235AH1-702 GEN1
Adder
1.734
970819AG2-516 GEN
Solar/Wind Harmer
5.74
970615AG2-402 GEN
50/50
4.588
24729405KEY G3
50/50
0.368
24729305KEY G2
50/50
0.361
24729205KEY G1
50/50
0.36
247620Y3-023
50/50
0.463
970611AG2-400 GEN
Solar/Wind Harmer
13.763
970627AG2-408 GEN
Solar/Wind Harmer
4.129
942221AE2-234 GEN
Solar/Wind Harmer
0.034
944541AF1-119 GEN
Solar/Wind Harmer
0.42
960971AF2-388 GEN
Solar/Wind Harmer
3.679
270216AD2-079_GEN
Solar/Wind Harmer
0.001
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
11.557
961051AF2-396 GEN
Solar/Wind Harmer
7.705
270526AF1-158 GEN
Solar/Wind Harmer
0.007
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
6.887
965791AG1-447 GEN
Solar/Wind Harmer
5.051
270599AE1-208 GEN
Solar/Wind Harmer
4.993
270031AE2-169
Solar/Wind Harmer
2.996
970321AG2-212 GEN
Solar/Wind Harmer
2.307
274808UNIV PK N;4U
Adder
3.733
274770LINCOLN ;1U
Adder
6.292
274771LINCOLN ;2U
Adder
6.292
274803UNIV PARK;6U
Adder
4.319
274888KELLY CRK;1U
Solar/Wind Harmer
0.302
274887GEN-1.85
Solar/Wind Harmer
0.136
276843GEN-1.7
Solar/Wind Harmer
0.167
958011AF2-095 GEN
Solar/Wind Harmer
7.412
972259AH1-714 GEN
Adder
13.99
274674JOLIET 9 ;6U
Adder
11.217
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
971573AH1-285 GEN
Solar/Wind Harmer
0.931
958481AF2-142 GEN
Solar/Wind Harmer
7.482
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.675
274695ROCKY RD ;2P
Adder
7.922
274693ROCKY RD ;1P
Adder
7.844
274697ROCKY RD ;3P
Adder
2.152
274696ROCKY RD ;4P
Adder
8.109
274683WAUKEGAN ;8U
Adder
14.968
274683WAUKEGAN ;8U
Adder
12.617
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
962691AG1-118 GEN
Solar/Wind Harmer
14.776
958491AF2-143 GEN
Solar/Wind Harmer
7.388
970921AG2-575 GEN
Solar/Wind Harmer
4.913
970921AG2-575 GEN
Solar/Wind Harmer
1.638
971613AH1-306 GEN
Solar/Wind Harmer
2.354
274879MINONK ;1U
Solar/Wind Harmer
0.207
942991AE2-321 GEN
Solar/Wind Harmer
5.451
971333AH1-146 GEN
Solar/Wind Harmer
9.71
971335AH1-147 GEN
Solar/Wind Harmer
9.71
960441AF2-335 GEN
Solar/Wind Harmer
4.841
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
971341AH1-150 GEN
Solar/Wind Harmer
9.652
971343AH1-151 GEN
Solar/Wind Harmer
9.652
970825AG2-519 GEN
Solar/Wind Harmer
5.324
274856ECOGROVE ;U1
Solar/Wind Harmer
0.113
276611AD2-172 GEN
Solar/Wind Harmer
0.001
938861AE1-114 GEN
Solar/Wind Harmer
2.689
274764LEE CO EC;5U
Adder
6.319
274765LEE CO EC;6U
Adder
6.319
274762LEE CO EC;3U
Adder
6.304
274763LEE CO EC;4U
Adder
6.245
276603SUBLETTE C
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.354
270201AC2-176 GEN
Solar/Wind Harmer
0.001
972267AH1-718 GEN
Adder
2.793
276741O09 GEN1
Solar/Wind Harmer
0.166
276708O09 GEN2
Solar/Wind Harmer
0.166
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.183
276646AC1-214 GEN2
Solar/Wind Harmer
0.183
966841AG1-555 GEN
Solar/Wind Harmer
0.525
276782AC1-033 GEN
Solar/Wind Harmer
0.001
247621Y3-024
Adder
0.16
960611AF2-352 GEN
Solar/Wind Harmer
1.506
970241AG2-163 GEN
Solar/Wind Harmer
2.545
24379505HDWTR1G C
Solar/Wind Harmer
0.001
270209AC1-174_GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
270383AD1-128 GEN
Solar/Wind Harmer
0.002
276916AD2-100_GEN
Solar/Wind Harmer
8.413
276911AD2-131_GEN
Solar/Wind Harmer
0.554
970883AG2-550 GEN
Solar/Wind Harmer
3.912
970885AG2-551 GEN
Solar/Wind Harmer
1.304
945391AF1-204 GEN
Solar/Wind Harmer
4.152
970623AG2-406 GEN
Solar/Wind Harmer
0.681
270444AC2-157 GEN1
Solar/Wind Harmer
0.001
971587AH1-292 GEN
Solar/Wind Harmer
2.427
270007AE1-245 C
Solar/Wind Harmer
0.001
970239AG2-162 GEN
Solar/Wind Harmer
0.774
246938BC-WTG3
Solar/Wind Helper
11.083
246937BC-WTG2
Solar/Wind Helper
10.895
270224U2-072_GEN2
Solar/Wind Helper
0.871
270227U2-072_GEN3
Solar/Wind Helper
0.871
270228U2-072_GEN4
Solar/Wind Helper
0.871
270231U2-072_GEN5
Solar/Wind Helper
0.871
270471AD2-092_GEN
Solar/Wind Helper
0.85
253378AE2-206_GEN
Solar/Wind Helper
0.684
276820AF1-078_GEN
Solar/Wind Helper
0.319
241960AC2-195 GEN
Solar/Wind Helper
0.69
24727205RPMNG3
50/50
3.292
971599AH1-298 GEN
50/50
10.333
24729505KEY G4
50/50
6.735
24653605MOTTVILLE
50/50
0.003
963791AG1-232 GEN
Solar/Wind Harmer
11.606
965041AG1-368 GEN
Solar/Wind Harmer
8.426
270071AF1-092 GEN
Solar/Wind Harmer
14.399
965051AG1-369 GEN
Solar/Wind Harmer
3.592
270024AE2-089 GEN
Solar/Wind Harmer
0.007
965101AG1-375 GEN
Solar/Wind Harmer
6.088
971771AH1-392 GEN
Solar/Wind Harmer
5.847
971347AH1-153 GEN
Solar/Wind Harmer
8.688
971619AH1-309 GEN
Solar/Wind Harmer
2.601
945581AF1-223 GEN
Solar/Wind Harmer
0
971769AH1-391 GEN
Solar/Wind Harmer
6.283
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971609AH1-304 GEN
Solar/Wind Harmer
0.89
274814UNIV PK N;0U
Adder
3.782
274807UNIV PK N;3U
Adder
3.774
274805UNIV PK N;1U
Adder
3.758
274811UNIV PK N;7U
Adder
3.75
270536AF1-215 GEN2
Solar/Wind Harmer
0.007
274775LINCOLN ;6U
Adder
6.292
274776LINCOLN ;7U
Adder
6.292
274777LINCOLN ;8U
Adder
6.292
972037AH1-567 GEN1
Adder
0.136
274827FISK ;RP
Adder
5.742
960591AF2-350 GEN
Solar/Wind Harmer
5.147
972227AH1-698 GEN1
Adder
1.919
274687WILL CNTY;4U
Adder
20.447
274687WILL CNTY;4U
Adder
20.447
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274675JOLIET 29;7U
Adder
22.401
274675JOLIET 29;7U
Adder
21.601
274728ELWOOD EC;5P
Adder
11.97
274731ELWOOD EC;2P
Adder
11.97
274733ELWOOD EC;3P
Adder
11.97
274735ELWOOD EC;4P
Adder
11.97
970833AG2-524 GEN
Solar/Wind Harmer
5.563
970833AG2-524 GEN
Solar/Wind Harmer
3.709
971611AH1-305 GEN
Solar/Wind Harmer
2.995
274746AC1-111 G10
Adder
4.021
274744AC1-111 GEN8
Adder
4.021
970289AG2-191 GEN
Solar/Wind Harmer
0.942
270594AE1-207 GEN
Solar/Wind Harmer
5.492
276868AE1-113 GEN
Solar/Wind Harmer
0.982
276882AE2-255 GEN
Solar/Wind Harmer
0.572
971177AH1-047 GEN
Solar/Wind Harmer
3.009
971411AH1-196 GEN
Solar/Wind Harmer
7.289
971675AH1-338 GEN
Solar/Wind Harmer
1.894
970115AG2-085 GEN
Solar/Wind Harmer
1.936
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
9.652
274823ROCKFORD ;21
Adder
13.435
276612AE2-035 GEN
Solar/Wind Harmer
0.001
926823AC1-168 GEN
Solar/Wind Harmer
0.811
970169AG2-114 GEN
Solar/Wind Harmer
4.764
971681AH1-341 GEN
Solar/Wind Harmer
7.643
971549AH1-272 GEN
Solar/Wind Harmer
9.793
961011AF2-392 GEN
Solar/Wind Harmer
2.754
957751AF2-069 GEN
Solar/Wind Harmer
0.154
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
276655WTG1_EQ
Solar/Wind Harmer
0.002
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
4.828
941731AE2-173 GEN
Solar/Wind Harmer
3.831
946321AF1-296 GEN
Solar/Wind Harmer
2.545
963841AG1-237 GEN
Solar/Wind Harmer
1.949
270240V3-007_GEN2
Solar/Wind Harmer
0.001
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.156
276848AB2-070 GEN3
Solar/Wind Harmer
0.155
270543AE2-219 C
Solar/Wind Harmer
0.002
944221AF1-090 GEN
Solar/Wind Harmer
2.279
971029AG2-637 GEN
Solar/Wind Harmer
5.242
971673AH1-337 GEN
Solar/Wind Harmer
2.175
247607V1-011 GEN
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Helper
8.613
270317AD1-130_GEN
Solar/Wind Helper
4.113
966831AG1-554 GEN
Solar/Wind Helper
0.876
270284AF1-227 GEN1
Solar/Wind Helper
1.876
270286AF1-227 GEN2
Solar/Wind Helper
0.688
270287AF1-227 GEN3
Solar/Wind Helper
0.688
270499AE1-146 GEN
Solar/Wind Helper
1.952
945641AF1-229 GEN
Solar/Wind Helper
0.937
970289AG2-191 GEN
Solar/Wind Harmer
0.545
970291AG2-192 GEN
Solar/Wind Harmer
0.496
958821AF2-173 GEN
Solar/Wind Harmer
6.901
270004AE1-209 GEN
Solar/Wind Harmer
1.068
276805AD2-038 GEN
Solar/Wind Harmer
0.001
274872LEEDK;1U
Solar/Wind Harmer
0.18
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.518
274855GSG-6 ;RU
Solar/Wind Harmer
0.178
274850MENDOTA H;RU
Solar/Wind Harmer
0.057
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.087
276889AE2-281 GEN
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
4.834
959091AF2-200 GEN
Solar/Wind Harmer
9.652
972236AH1-702 GEN2
Adder
1.508
970571AG2-364 GEN
Solar/Wind Harmer
9.558
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
6.304
274767LEE CO EC;8U
Adder
6.23
946031AF1-268 GEN
Solar/Wind Harmer
4.492
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
7.069
276157O29GEN1
Solar/Wind Harmer
0.755
274878BISHOP HL;2U
Solar/Wind Harmer
0.156
942111AE2-223 GEN
Solar/Wind Harmer
1.494
965931AG1-462 GEN
Solar/Wind Harmer
11.522
274853TWINGROVE;U1
Solar/Wind Harmer
0.002
965091AG1-374 GEN
Solar/Wind Harmer
13.551
959611AF2-252 GEN
Solar/Wind Harmer
1.506
270437AC2-090 C
Solar/Wind Harmer
0.002
276686W4-005 GEN3
Solar/Wind Harmer
0.001
276668AB2-070 GEN1
Solar/Wind Harmer
0.156
971993AH1-541 GEN
Solar/Wind Harmer
1.971
276621W2-048 GEN
Solar/Wind Harmer
0.211
276838X2-022 GEN2
Solar/Wind Harmer
0.236
942481AE2-261 GEN
Solar/Wind Harmer
12.085
970193AG2-126 GEN
Solar/Wind Harmer
5.861
270404AC1-167 GEN
Solar/Wind Harmer
0.002
270258AD1-119 GEN
Solar/Wind Harmer
0.001
24728705AND G3
Adder
4.272
24728505AND G1
Adder
2.043
270356AE2-297 GEN
Solar/Wind Harmer
0.005
970243AG2-164 GEN
Solar/Wind Harmer
1.812
970519AG2-331 GEN
Solar/Wind Harmer
8.054
970699AG2-449 GEN
Solar/Wind Harmer
0.774
270485AE1-090_GEN
Solar/Wind Helper
0.323
942871AE2-306 GEN
Solar/Wind Helper
0.443
270541AE2-072 C
Solar/Wind Helper
0.932
970569AG2-363 GEN
Solar/Wind Harmer
14.338
971475AH1-234 GEN
Solar/Wind Harmer
2.315
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
6.304
274766LEE CO EC;7U
Adder
6.23
276903AD2-071 C
Solar/Wind Harmer
5.249
276158O29GEN2
Solar/Wind Harmer
0.001
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.002
274877BISHOP HL;1U
Solar/Wind Harmer
0.156
276726Z2-087_GEN
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
6.437
274854TWINGROVE;U2
Solar/Wind Harmer
0.002
972175AH1-670 GEN
Solar/Wind Harmer
3.624
963741AG1-226 GEN
Solar/Wind Harmer
10.327
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
3.19
247536S-71 GEN
Solar/Wind Harmer
0.173
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
1.654
276615X2-022 GEN
Solar/Wind Harmer
0.044
965911AG1-460 GEN
Solar/Wind Harmer
0.808
24728605AND G2
Adder
2.043
970773AG2-487 GEN
Solar/Wind Harmer
0.609
270445AC2-157 GEN2
Solar/Wind Harmer
0.001
970333AG2-219 GEN
Solar/Wind Harmer
2.215
246936BC-WTG1
Solar/Wind Helper
10.895
270462AD2-086
Solar/Wind Helper
3.714
270223U2-072_GEN1
Solar/Wind Helper
0.871
270578AF1-285 GEN2
Solar/Wind Helper
0.59
270391AF1-285 GEN3
Solar/Wind Helper
0.59
247522W1-056 GEN
Solar/Wind Helper
1.168
960841AF2-375 GEN
Solar/Wind Helper
1.175
270349AD2-093_GEN
Solar/Wind Helper
0.85
944201AF1-088_MTX
Adder
55.165
957141AF2-008_MTX
Adder
17.696
990792J1392
External Queue
5.474584102630615
990497J1323
External Queue
1.5914489030838013
NYPJM->LTFIMP_NY
CLTF
1.265
LGEELTFEXP_LGEE->PJM
CLTF
1.782
WECLTFEXP_WEC->PJM
CLTF
2.624
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.056
AG2-052LTFEXP_AG2-052->PJM
LTF
0.17
AH1-155LTFEXP_AH1-155->PJM
LTF
0.255
LAGNLTFEXP_LAGN->PJM
CLTF
5.694
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.439
TVALTFEXP_TVA->PJM
CLTF
2.27
CBM West 1LTFEXP_CBM-W1->PJM
CBM
69.309
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.744
MECLTFEXP_MEC->PJM
CLTF
9.656
SIGELTFEXP_SIGE->PJM
CLTF
0.197
CBM West 2LTFEXP_CBM-W2->PJM
CBM
49.944
CONTINGENCY 'AP_P1-2_MP-500-028_SRT-A'
 DISCONNECT BRANCH FROM BUS 235111 TO BUS 235117 CKT 1   /*01 502 J     500.0 - 01KAMMER     500.0
 DISCONNECT BRANCH FROM BUS 235117 TO BUS 242925 CKT 1   /*01KAMMER     500.0 - 05KAMMER     765.0
END
CONTINGENCY 'AP_P1-3_MP-765-502T_SRT-A'
 DISCONNECT BRANCH FROM BUS 235117 TO BUS 242925 CKT 1   /*01KAMMER     500.0 - 05KAMMER     765.0
END
CONTINGENCY 'AP_P1-2_MP-500-007A_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235235 CKT 1   /*01BELMNT     500.0 - 01FLINTRUN   500.0
END
CONTINGENCY 'AP_P1-2_MP-500-008A_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235235 TO BUS 235107 CKT 1          /*01FLINTRUN   500.0 - 01HARRSN     500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235107 TO BUS 235703 CKT 1 /*01HARRSN     500.0 - 01WYLIE R    500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235107 TO BUS 235703 CKT 1 /*01HARRSN     500.0 - 01WYLIE R    500.0
END
CONTINGENCY 'ATSI_P1-2_TE-345-602_SRT-A'
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 238889 CKT 1   /*02DAV-BE     345.0 - 02LEMOYN     345.0
END
CONTINGENCY 'ATSI_P1-2_TE-345-601_SRT-A'
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 238563 CKT 1   /*02DAV-BE     345.0 - 02BAY SH     345.0
END
CONTINGENCY 'AEP_P1-2_#7441_100545_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
END
CONTINGENCY 'AEP_P1-3_#7421_05CLOVRD 765_14_SRT-A'
 OPEN BRANCH FROM BUS 242512 TO BUS 242519 CKT 14   /*05CLOVRD     765.0 - 05CLOVRD     500.0
END
CONTINGENCY 'AP_P1-3_MP-765-501T_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1   /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                   /*05BELMON     765.0
END
CONTINGENCY 'AEP_P1-2_#706_SRT-A'
 OPEN BRANCH FROM BUS 242922 TO BUS 290622 CKT 1    /*05FLTLCK     765.0 - 05GAVIN_RF   765.0
 OPEN BRANCH FROM BUS 242923 TO BUS 290622 CKT Z1   /*05GAVIN      765.0 - 05GAVIN_RF   765.0
END
CONTINGENCY 'AEP_P1-2_#709_546_SRT-A'
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
END
CONTINGENCY 'AEP_P1-2_#6463_16757_SRT-A'
 OPEN BRANCH FROM BUS 242935 TO BUS 246929 CKT 1   /*05E LIMA     345.0 - 05MADDOX     345.0
END
CONTINGENCY 'AEP_P1-2_#17217_SRT-A'
 OPEN BRANCH FROM BUS 242925 TO BUS 290623 CKT Z1   /*05KAMMER     765.0 - 05KAMMER_RG  765.0
 OPEN BRANCH FROM BUS 246526 TO BUS 290623 CKT 1    /*05GUERNSEY   765.0 - 05KAMMER_RG  765.0
END
CONTINGENCY 'AEP_P1-2_#7422_16_SRT-A'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1   /*05CLOVRD     500.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'AEP_P1-2_#7442_200545_SRT-A'
 OPEN BRANCH FROM BUS 243206 TO BUS 290606 CKT Z1   /*05DUMONT     765.0 - 05DUMONT_RS  765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290606 CKT 1    /*05SORENS     765.0 - 05DUMONT_RS  765.0
END
CONTINGENCY 'DEOK_P1_EAST BEND-TERMINAL 4516_SRT-A'
 OPEN BRANCH FROM BUS 249565 TO BUS 249575 CKT 1   /*08EBEND      345.0 - 08TERMNL     345.0
END
CONTINGENCY 'AEP_P1-2_#309_15_SRT-A'
 OPEN BRANCH FROM BUS 242510 TO BUS 242924 CKT 1   /*05BAKER      765.0 - 05HANG R     765.0
END
235102 to 235235 ckt 1
235235 to 235107 ckt 1
235117 to 235111 ckt 1
238563 to 238654 ckt 1
238889 to 238654 ckt 1
243211 to 242933 ckt 1
247977 to 242524 ckt 17
242519 to 314912 ckt 1
290618 to 242924 ckt Z1
242925 to 235117 ckt 1
290623 to 242925 ckt Z1
246929 to 242935 ckt 1
242926 to 246751 ckt 1
242928 to 290620 ckt Z1
290620 to 242926 ckt 1
290608 to 242928 ckt Z1
242516 to 242920 ckt 1
242933 to 965420 ckt 1
243232 to 246999 ckt 3
246999 to 290607 ckt Z1
243233 to 249567 ckt 1
248005 to 242528 ckt 1
248013 to 242938 ckt 1
965420 to 246929 ckt 1

Winter Peak Analysis

The New Service Request AH1-306 was evaluated as a 0.0 MW (28.8 MW Capacity) injection in the AEP area.

AH1-306 was evaluated as part of a plant. The plant consists of AH1-306. The total Energy output of the plant was evaluated at its maximum seasonal capability of 200.0 MW (0.0 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

(No impacts were found for this analysis)

Light Load Analysis

The New Service Request AH1-306 was evaluated as a 0.0 MW injection

AH1-306 was evaluated as part of a plant. The plant consists of AH1-306. The total Energy output of the plant was evaluated at its maximum seasonal capability of 200.0 MW (0.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

(No impacts were found for this analysis)

Short Circuit Analysis

Short Circuit analysis is not performed as part of the Phase I System Impact Study. Short Circuit analysis will commence in the Phase II System Impact Study.

Stability Analysis

Stability analysis is not performed as part of the Phase I System Impact Study. Stability analysis will commence in the Phase II System Impact Study.

Reactive Power Analysis

Reactive Power Analysis was not performed. This project is responsible for meeting all applicable power factor requirements.

Steady-State Voltage Analysis

Steady State Voltage Analysis is Not Required.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-018Powerton-Goodings GroveIn Service
AA1-038Lexington-Low Moor 230kVUnder Construction
AA1-095Halfway-Marlowe 34.5kVIn Service
AA2-184Atlantic-Red Bank 34kVIn Service
AB1-001Absecon 12 kVIn Service
AB1-006Meadow Lake 345kVIn Service
AB1-027Old Church 34.5 KVIn Service
AB1-087Sullivan 345kV #1Under Construction
AB1-088Sullivan 345kV #2Engineering & Procurement
AB1-096Carroll-Mt. Airy 34.5kVIn Service
AB1-124Carroll-Monocacy 34.5kVPartially in Service - Under Construction
AB1-125Carroll-Monocacy 34.5kVIn Service
AB1-127St. Thomas-Guilford 34.5kVIn Service
AB1-128St. Thomas-Mercersburg 34.5kVIn Service
AB1-138Navy 34.5kVIn Service
AB1-139Metuchen 26kVIn Service
AB1-141Church-Wye Mills 138 kV IIn Service
AB1-142Church-Wye Mills 138 kV IIIn Service
AB1-150Grassy Falls 138kVIn Service
AB1-176Price 25kV IIEngineering & Procurement
AB1-180Pine View 12kVIn Service
AB2-026Powhatan 34.5kVIn Service
AB2-029Remington 34.5kVIn Service
AB2-032Church-Wye Mills 138 kVIn Service
AB2-037Keeney-Steele 230kVUnder Construction
AB2-045Buckingham 34.5kVIn Service
AB2-049Gloucester Township 12kVIn Service
AB2-067Kammer-Vassell 765kVIn Service
AB2-070Mt. Pulaski-BrokawIn Service
AB2-093Ormet 138kVIn Service
AB2-133Chestertown 69kVUnder Construction
AB2-135Church-Kent 69kVIn Service
AB2-136Cambridge-West Cambridge 69kVUnder Construction
AB2-153Church-Wye Mills 138 kVIn Service
AB2-157Prince George's County 12kVIn Service
AB2-158Louisa-South Anna 230kVIn Service
AB2-170East Lima-Marysville 345kVIn Service
AB2-179Townsend 138kVIn Service
AC1-001Delano 138kVIn Service
AC1-010Gloucester 26kVUnder Construction
AC1-017Levittown 13 kVIn Service
AC1-030Cinnaminson 13kVIn Service
AC1-033Kewanee 138 kVIn Service
AC1-042Altavista-Mt. Airy 69kVIn Service
AC1-044Kammer-Vassell 765kVIn Service
AC1-053Lanesville-BrokawPartially in Service - Under Construction
AC1-068Atlanta 69kV IIn Service
AC1-069Atlanta 69kV IIIn Service
AC1-074Jacksonville-Renaker 138kV IIn Service
AC1-075Perth-Hickory Grove 115kVIn Service
AC1-076Locust Grove-Paytes 115kVIn Service
AC1-078Beatty-London 138kVIn Service
AC1-082Ravenswood-Hemlock 69kVUnder Construction
AC1-085Stuart-Clinton 345kVIn Service
AC1-089Hillsboro-Wildcat 138kVIn Service
AC1-091Cedar Creek 138kV IEngineering & Procurement
AC1-092Cedar Creek 138kV IIEngineering & Procurement
AC1-093Cedar Creek 138kV IIIEngineering & Procurement
AC1-094Cedar Creek 138kV IVEngineering & Procurement
AC1-101Johns Creek-Excel 138kV ISuspended
AC1-102Johns Creek-Excel 138kV IISuspended
AC1-111Aurora 138kVIn Service
AC1-118Westmoreland 34.5kVIn Service
AC1-120Mitchell-Mountain Run 115kVEngineering & Procurement
AC1-121Mitchell-Mountain Run 115kVEngineering & Procurement
AC1-122Smith Mountain-Candler's Mountain 138kVIn Service
AC1-141Cook-East Elkhart 345kVIn Service
AC1-145Gretna DP 69 kVIn Service
AC1-158Spotsylvania 500kVIn Service
AC1-165Atlanta 69kV IIIIn Service
AC1-166Atlanta 69kV IVIn Service
AC1-167Mark Center 69kVUnder Construction
AC1-168Kewanee-StreatorSuspended
AC1-174Losantville 345kVIn Service
AC1-175Losantville 345kVIn Service
AC1-188Rio-Lick 138kVEngineering & Procurement
AC1-191Elmont 115kVEngineering & Procurement
AC1-194Elk 138kVActive
AC1-214Crescent RidgeIn Service
AC2-023Hebron 69kVEngineering & Procurement
AC2-029Circleville 138kVSuspended
AC2-044Maddox Creek 345kVSuspended
AC2-059Biers Run-Circleville 138kVIn Service
AC2-060Buckskin 69kVIn Service
AC2-061Hillsboro-Clinton 138kVIn Service
AC2-067Camden-Crystal I 69kVEngineering & Procurement
AC2-068Camden-Crystal II 69kVEngineering & Procurement
AC2-075Jacksonville-Renaker 138 kVIn Service
AC2-088S. Bethel-Brown 69kVIn Service
AC2-090Losantville 345kVIn Service
AC2-103Beaver-Davis Besse 345 kV IEngineering & Procurement
AC2-111College Corner 138kVEngineering & Procurement
AC2-120Ripley 69kVIn Service
AC2-136East Hagerstown 12kVUnder Construction
AC2-137Elko 34.5kVIn Service
AC2-138Northern Neck 34.5kVIn Service
AC2-157Sullivan 345 kVUnder Construction
AC2-165Bremo-Powhatan 230kVSuspended
AC2-168Clinton 23kVIn Service
AC2-176Jay 138 kVIn Service
AC2-186Harrington 25kVUnder Construction
AC2-187Harrington 69kVUnder Construction
AC2-188Harrington 69 kVUnder Construction
AC2-195Galion-Roberts South 138 kVUnder Construction
AD1-013Twombly Road 138kVEngineering & Procurement
AD1-017Smith Mountain-Bearskin 138 kVIn Service
AD1-020Hunterstown-Lincoln 115 kVIn Service
AD1-060Mercersburg-Milnor 34.5 kVIn Service
AD1-061McConnelsburg-Mercersburg 34 kVIn Service
AD1-063Harmony Village 34.5 kVIn Service
AD1-100Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVUnder Construction
AD1-101Continental 69 kVIn Service
AD1-105Kings Dominion DP 115 kVUnder Construction
AD1-106North Waldo-Wild Creek 138 kVSuspended
AD1-115Mountain Run-Mitchell 115 kVEngineering & Procurement
AD1-119Payne 69 kVIn Service
AD1-128Modoc-Delaware 138 kVPartially in Service - Under Construction
AD1-130Hardin Switch 345 kVIn Service
AD1-136South Bethel-Brown 69 kVIn Service
AD1-140Greene-Clark 138 kVEngineering & Procurement
AD1-155Meadow Brook-Strasburg 138 kVIn Service
AD2-009McConnellsburg 138 kVIn Service
AD2-016Biers Run-Circleville 138 kVIn Service
AD2-020Valley 138 kVEngineering & Procurement
AD2-027Camden Switch 26 kVIn Service
AD2-031Martinsville-Wilmington 69 kVIn Service
AD2-038Powerton-Nevada 345 kVUnder Construction
AD2-042Camden Switch 26 kV IIIn Service
AD2-047Davis Creek 138 kVSuspended
AD2-048Cynthia-Headquarters 69 kVUnder Construction
AD2-058St. Barnabas 13 kVIn Service
AD2-060Davis Creek 138kVEngineering & Procurement
AD2-065Atco 12 kVIn Service
AD2-066Mazon-Crescent Ridge 138 kVEngineering & Procurement
AD2-067Centerburg 138kVEngineering & Procurement
AD2-070Gilbert-Morris Park 34.5kVIn Service
AD2-071Strawton-Deer Creek 138 kVSuspended
AD2-073Sanders DP 230 kVIn Service
AD2-074Garner DP-Lancaster 115 kVEngineering & Procurement
AD2-079Capitol Ave 34.5kVIn Service
AD2-086Hardin Switch 345 kVIn Service
AD2-091Hardin Tap 345kVSuspended
AD2-092Marysville 345kVUnder Construction
AD2-093Marysville 345kVUnder Construction
AD2-096Marysville 345kVSuspended
AD2-100Kincaid-Pana 345 kVSuspended
AD2-115Lyons-Moselem 69kVIn Service
AD2-116Hokes-Grantley 69 kVIn Service
AD2-131Kincaid-Pana 345kVSuspended
AD2-133Eagle Valley 115kVIn Service
AD2-134Shady OaksPartially in Service - Under Construction
AD2-135Williamstown 12kVPartially in Service - Under Construction
AD2-163Broadview-Tangy 138 kVIn Service
AD2-172Lena 138kVIn Service
AD2-179Morgans Cut-Glen Lyn 138kVSuspended
AD2-180Elk Garden-Parr Run 138kVIn Service
AE1-040Greenfield 69 kVIn Service
AE1-041Edison 4kVIn Service
AE1-071Shade Gap-Roxbury 115 kVIn Service
AE1-074Winterpock 34.5 kVUnder Construction
AE1-075Powhatan 34.5 kVIn Service
AE1-079Maysville-Sharon 69 kVUnder Construction
AE1-081Landing 12.47 kVIn Service
AE1-090Hardin Switch 345 kVIn Service
AE1-091West Newton-Lynn 138 kVSuspended
AE1-092Blue Jacket-Kirby 138 kVActive
AE1-100Axton 138 kVIn Service
AE1-101McConnellsburg-Texas Eastern 138 kVIn Service
AE1-102Maddox Creek 345 kVSuspended
AE1-109Frenchs Mill 34 kVIn Service
AE1-113Mole Creek 345 kVEngineering & Procurement
AE1-114Maryland-Lancaster 138 kVActive
AE1-142Manitou-Pleasant Plains 34.5 kVIn Service
AE1-146Ebersole #2-Fostoria Central 138 kVUnder Construction
AE1-155Garner-Northern Neck 115 kVIn Service
AE1-156Quakertown Solar II 34.5 kVPartially in Service - Under Construction
AE1-163Powerton-Nevada 345 kVEngineering & Procurement
AE1-166Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE1-170Kenzie Creek-Colby 138 kVSuspended
AE1-172Loretto-Wilton CenterActive
AE1-176Roanoke-Vinton 12 kV (Niagara Hydro)In Service
AE1-183Maysville-McDowell 69 kVEngineering & Procurement
AE1-185Hokes-Jackson 69 kVIn Service
AE1-196Hokes-Jackson 69 kV IIIn Service
AE1-205McLean 345 kVEngineering & Procurement
AE1-207Mississinewa-Gaston 138 kVSuspended
AE1-208Delaware-Van Buren 138 kVSuspended
AE1-209Desoto 345 kVSuspended
AE1-210Desoto 345 kVSuspended
AE1-212Grandview-Clifftop 138 kVSuspended
AE1-227South Cumberland 69 kVSuspended
AE1-229Deepwater-Upper Pittsgrove 138 kVSuspended
AE1-237Andover (Maysville) 69kV IUnder Construction
AE1-245Haviland 138 kVUnder Construction
AE1-250Smith Mountain-E. Danville 138 kVEngineering & Procurement
AE2-029Grottoes-Merck 115kVUnder Construction
AE2-035Lena 138 kVIn Service
AE2-042Milton 69 kVIn Service
AE2-045Olive-Reynolds 345 kVEngineering & Procurement
AE2-047Ridgeway-Solite 69 kVEngineering & Procurement
AE2-048Muskingum-W. Millersport 345 kVEngineering & Procurement
AE2-054Warfordsburg 34 kVIn Service
AE2-059Derry Tap-Derry Bus 69 kVIn Service
AE2-060Mifflintown Bus-Mifflintown Tap 69 kVIn Service
AE2-071Patton Rd-Summer Shade 69 kVIn Service
AE2-072East Leipsic-Richland 138 kVIn Service
AE2-089Pennville-Adams 138 kVEngineering & Procurement
AE2-092Kidds Store-Sherwood 115 kVEngineering & Procurement
AE2-113Farmers Valley-Ridgeway 115 kVUnder Construction
AE2-114Midland 23 kV IIn Service
AE2-115Midland 23 kV IIIn Service
AE2-117ABW Tap-Alexandria 46 kVSuspended
AE2-125Stahlstown-Ligonier 25 kVIn Service
AE2-126Dubois-Curwensville 34.5 kVIn Service
AE2-129Philipsburg-Clarence 34.5 kVIn Service
AE2-131Philipsburg-Karthaus 34.5Under Construction
AE2-133Penns Tap-Richfield Tie 69 kVIn Service
AE2-136Muskingum River-W. Millersport 345 kVEngineering & Procurement
AE2-139East Towanda-Grover 230 kVEngineering & Procurement
AE2-140Axton-Danville 138 kVSuspended
AE2-148Beatty-Greene 345 kVIn Service
AE2-152Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE2-160Kanawha River 138 kVEngineering & Procurement
AE2-166Stockton 138 kVSuspended
AE2-169Delaware-Van Buren 138 kVSuspended
AE2-172Mississinewa-Gaston 138 kVSuspended
AE2-173McLean 345 kVActive
AE2-175Jackson-Long Pond 69 kVPartially in Service - Under Construction
AE2-176Groton 138 kV SolarIn Service
AE2-181Snyder 69kVUnder Construction
AE2-185Gladys DP-Stonemill Switching Station 69 kVActive
AE2-187Shockoe DP-Chatham 69 kVActive
AE2-206East Sidney-Quincy 138 kVIn Service
AE2-214Cole 345 kVEngineering & Procurement
AE2-216Hardin Switch 345 kVEngineering & Procurement
AE2-217East Springfield-London 138 kVEngineering & Procurement
AE2-219Bluff Point-Randolph 138 kVSuspended
AE2-220Losantville 345 kVEngineering & Procurement
AE2-221Clinton-Stuart 345 kVUnder Construction
AE2-223McLean 345 kVActive
AE2-224Bear Rock-Johnstown 230 kVIn Service
AE2-226Millville-Old Chapel 138 kVEngineering & Procurement
AE2-230Bartonsville-Meadow Brook 138 kVIn Service
AE2-234Liberty Center-Buckeye Tap 69 kVEngineering & Procurement
AE2-236Columbia-Northeast 138 kVSuspended
AE2-254Garrard County-Tommy-Gooch 69 kVIn Service
AE2-255Molecreek 345 kVEngineering & Procurement
AE2-261Kincaid-Pana 345 kVActive
AE2-262Moshannon-Milesburg 230 kVEngineering & Procurement
AE2-263Moshannon-Milesburg 230 kV IIEngineering & Procurement
AE2-267Woodsdale 345 kVEngineering & Procurement
AE2-276Sullivan 345kVEngineering & Procurement
AE2-281Powerton-Nevada 345 kVEngineering & Procurement
AE2-282East Fayette 138 kVIn Service
AE2-283Gladys-Stone Mill 69 kVActive
AE2-285Maysville 69 kVEngineering & Procurement
AE2-291Grit DP-Perth 115 kVActive
AE2-297Madison-Tanners Creek 138 kVIn Service
AE2-305Givens-Mechanicsburg 138 kVEngineering & Procurement
AE2-306Gunn Road 345 kVUnder Construction
AE2-308Three Forks-Dale 138 kVActive
AE2-309Carlos Junction-Lonaconing 34.5 kVIn Service
AE2-315Yankee Tap 69 kVIn Service
AE2-318Ford-Cedarville 138 kVSuspended
AE2-321Belvidere-Marengo 138 kVActive
AE2-323Twin Branch-Guardian 138 kVUnder Construction
AE2-325Valley 138 kVActive
AE2-326Jacksons Ferry 138 kVEngineering & Procurement
AE2-339Avon 138 kVEngineering & Procurement
AE2-341Sandwich-Plano 138 kVActive
AE2-342Woodstock 69 kVEngineering & Procurement
AE2-343Andover (Maysville) 69 kV IIUnder Construction
AF1-006Fairview East 34.5 kVIn Service
AF1-007Indian River 230 kV ISuspended
AF1-021Bethelboro-Connellsville #1 25 kVIn Service
AF1-022Lake Lynn-Uniontown 25 kVIn Service
AF1-030Sandwich-Plano 138 kVActive
AF1-039Listonburg-Highpoint 24.9 kVIn Service
AF1-042Garner DP-Lancaster 115 kVEngineering & Procurement
AF1-045Cedarville-Ford 138 kVSuspended
AF1-049Berry Hill 138 kVUnder Construction
AF1-051Gavin 765 kVIn Service
AF1-053Givens-Mechanicsburg 138 kVEngineering & Procurement
AF1-054Givens-Mechanicsburg 138 kVEngineering & Procurement
AF1-062Jug Street 138 kVEngineering & Procurement
AF1-064Weston 69 kVUnder Construction
AF1-078East Sidney-Quincy 138 kVIn Service
AF1-086Madera-Westover South 115 kVUnder Construction
AF1-088Sullivan 345 kVActive
AF1-090Kincaid-PanaEngineering & Procurement
AF1-091Varner - Sowers 138 kVEngineering & Procurement
AF1-092Huntington Jct. 138 kVSuspended
AF1-093Henderson-Stoneboro 69 kVEngineering & Procurement
AF1-094Union City-Cambridge Springs 34.5 kVEngineering & Procurement
AF1-098Four Mile Jct-Corry East 115 kVEngineering & Procurement
AF1-118Sorenson-Desoto 345 kVEngineering & Procurement
AF1-119Keystone-Desoto 345 kVEngineering & Procurement
AF1-120East Fayette 2 138 kVIn Service
AF1-122Cardington-Liberty 69 kVSuspended
AF1-130Inez 138 kVSuspended
AF1-134Philipsburg-Madera 34.5 kVEngineering & Procurement
AF1-136Warfordsburg-Purcell Junction 34.5 kVEngineering & Procurement
AF1-140Claysburg 23 kVEngineering & Procurement
AF1-143Lick Run 115 kVEngineering & Procurement
AF1-147Poland Rd-Runway DP 230kVUnder Construction
AF1-153Motion-Ridgeway 46 kVSuspended
AF1-158Edison-Gravel Pit 138 kVIn Service
AF1-161Valley 138 kVActive
AF1-162Inez 138 kVEngineering & Procurement
AF1-176Corey 138 kVActive
AF1-202Keystone-Desoto 345 kVUnder Construction
AF1-203Patton Rd-Summer Shade 69 kVIn Service
AF1-204Eugene 345 kVActive
AF1-205Napoleon Muni 138 kVSuspended
AF1-206East Fayette 138 kVEngineering & Procurement
AF1-207Reynolds-Olive #1 345 kVEngineering & Procurement
AF1-215Olive-Reynolds 345 kVIn Service
AF1-223Keystone-Desoto 345 kVUnder Construction
AF1-227Marysville – Gunn Road 345 kVIn Service
AF1-228Beatty-Greene 345 kVEngineering & Procurement
AF1-229Galion-South Berwick 345 kVEngineering & Procurement
AF1-233Flemingsburg – Spurlock 138kVActive
AF1-249Nickel 12.47 kVIn Service
AF1-254Milnor-Huyetts 34.5 kVUnder Construction
AF1-262Upper Pittsgrove 12 kVIn Service
AF1-264Runnemede 13 kVIn Service
AF1-268Desoto-Jay 138 kVEngineering & Procurement
AF1-272Lucerne 115 kVEngineering & Procurement
AF1-275Cole 345 kVEngineering & Procurement
AF1-282Stuart-Clinton 345 kVEngineering & Procurement
AF1-283Stuart-Clinton 345 kVEngineering & Procurement
AF1-285Gunn Road 345 kVUnder Construction
AF1-290Feagans Mill-Millville 138 kVIn Service
AF1-291ABartonsville-Meadow Brook 138 kVIn Service
AF1-296Garden Plain 138 kVActive
AF1-299Otter Point 34.5 kV IIn Service
AF1-300Otter Point 34.5 kV IIIn Service
AF1-302Brookville-Squab Hollow 138 kVEngineering & Procurement
AF1-320Merrill Creek 115 kVEngineering & Procurement
AF1-322Meadow Lake 345 kVEngineering & Procurement
AF1-331Twombley RoadEngineering & Procurement
AF1-333Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF1-337Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF1-338Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF1-339Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF2-008Sullivan 345 kVActive
AF2-014Maddox Creek 345 kVEngineering & Procurement
AF2-018Inez 138 kVEngineering & Procurement
AF2-039Shawville-Clearfield 34.5 kVEngineering & Procurement
AF2-041Nelson-Electric Junction 345 kVActive
AF2-048Rio-Lick 138 kVEngineering & Procurement
AF2-068Jay 138 kVActive
AF2-069Crescent Ridge 138 kVActive
AF2-075Bartonsville-Meadow Brook 138 kV IIIIn Service
AF2-078Reynolds-Olive #1 345 kVEngineering & Procurement
AF2-083Kenzie Creek-Stone Lake 69 kVUnder Construction
AF2-086Scott Tap-Bowmans Mill Tap 69 kVEngineering & Procurement
AF2-088Shawville-Clearfield 34.5 kV IIEngineering & Procurement
AF2-095Davis Creek 138 kVActive
AF2-106Hazel Hollow-Glen Lyn #1 138 kVEngineering & Procurement
AF2-107Clifford 138 kVEngineering & Procurement
AF2-111North Clark-Spurlock 345 kVActive
AF2-122Kirk 138 kVUnder Construction
AF2-126Weston 69 kV IIActive
AF2-130Cobalt Corners 34.5 kVIn Service
AF2-132Reynolds-Olive #1 345 kVUnder Construction
AF2-133Reynolds-Olive #2 345 kVUnder Construction
AF2-134Olive-Reynolds #2 345 kVIn Service
AF2-138Flanders-West Wharton 34.5 kVIn Service
AF2-139Gilbert-Warren Glen 34.5 kVIn Service
AF2-142Nevada 345 kVActive
AF2-143Powerton-Nevada 345 kVActive
AF2-144Powhatan 34.5 kVIn Service
AF2-173Desoto 345 kVActive
AF2-177Sorenson-DeSoto #2 345 kVActive
AF2-192Frenchtown Solar-West Flemington 34.5 kVSuspended
AF2-199Nelson-Electric Junction 345 kVActive
AF2-200Nelson-Electric Junction 345 kVActive
AF2-205Olive-Reynolds #2 345 kVEngineering & Procurement
AF2-224Allen 345 kVEngineering & Procurement
AF2-225McLean 345 kVActive
AF2-229Roxbury 23 kVEngineering & Procurement
AF2-233Penns-Richfield Tie #1 69 kVEngineering & Procurement
AF2-234Sunbury Yard #1-Richfield Tie #2 69 kVEngineering & Procurement
AF2-235Titusville-Oil Creek 34.5 kVWithdrawn
AF2-238Mansfield-South Troy 34.5 kVEngineering & Procurement
AF2-247Bustleton 13.2 kVIn Service
AF2-250Edgewood 12 kV IIIIn Service
AF2-252Blue Mound 345 kVEngineering & Procurement
AF2-291Sporn South-Leon 138 kVEngineering & Procurement
AF2-298Crown-New Lebanon 69 kVEngineering & Procurement
AF2-307Hope-Belvins Valley Tap 69 kVActive
AF2-311Gilboa-Jones Branch 138 kVEngineering & Procurement
AF2-316Gilboa-Jones Branch 138 kV IIEngineering & Procurement
AF2-325Jacktown 12 kVEngineering & Procurement
AF2-335Delaware-Royerton 138 kVActive
AF2-350Kensington 138 kVActive
AF2-352Blue Mound 345 kVEngineering & Procurement
AF2-354Washington 34.5 kV IIEngineering & Procurement
AF2-356Albright-Mt. Zion 138 kVUnder Construction
AF2-359Olive-University Park 345 kVEngineering & Procurement
AF2-361Mifflintown Tap 69 kVEngineering & Procurement
AF2-365Munfordville KU Tap-Horse Cave Jct. 69 kVActive
AF2-370Delaware-Royerton 138 kVActive
AF2-375Ebersole-Fostoria 138 kVEngineering & Procurement
AF2-376Timber Switch 138 kVActive
AF2-377Logtown 138 kVEngineering & Procurement
AF2-378Cambridge 12 kVEngineering & Procurement
AF2-379Princess Anne 25 kVUnder Construction
AF2-382Hurley 69 kVEngineering & Procurement
AF2-383Tolna 115 kVWithdrawn
AF2-388Keystone-Desoto 345 kVActive
AF2-392Nelson-Dixon 138 kVActive
AF2-396Stinger 138 kVActive
AF2-407Fall Creek 345 kVActive
AF2-408Fall Creek 138 kVEngineering & Procurement
AF2-417West Damascus Tap-West Damascus 69 kVEngineering & Procurement
AF2-421East Hazelton-Weatherly Tap 69Engineering & Procurement
AF2-424Reed-Reed Tap #1 69 kVEngineering & Procurement
AF2-425Reed-Reed Tap#1 69 kVEngineering & Procurement
AF2-433Columbia-Geisinger Tap #1 69 kVEngineering & Procurement
AF2-434Columbia-Geisinger Tap #1 69 kVEngineering & Procurement
AF2-440Hillsboro-Middleboro 138 kVEngineering & Procurement
AG1-024Centerburg 138 kVEngineering & Procurement
AG1-034Centerburg 138 kVEngineering & Procurement
AG1-040Morgan Street-Mount Hope 34.5 kVEngineering & Procurement
AG1-047Jay 138 kVEngineering & Procurement
AG1-054Potter-Harlan 69 kVEngineering & Procurement
AG1-070Bon Ayr 69 kVActive
AG1-071Bon Ayr 69 kVActive
AG1-100Venango-Saegertown 34.5 kVEngineering & Procurement
AG1-107Hillsboro-Middleboro 138 kVEngineering & Procurement
AG1-109Valley 138 kVActive
AG1-118Sugar Grove-Waterman 138kVActive
AG1-124Gladstone 138 kVActive
AG1-125Marysville-Flatlick 765 kVEngineering & Procurement
AG1-126Marysville-Flatlick 765 kVEngineering & Procurement
AG1-127Crego Rd 138 kVActive
AG1-156Jack Frost-Lake Harmony 69 kVEngineering & Procurement
AG1-164East Hazelton-Weatherly Tap 69 kVEngineering & Procurement
AG1-165East Hazelton-Weatherly Tap 69 kVEngineering & Procurement
AG1-188Manitou-Oyster Creek 34.5 kVEngineering & Procurement
AG1-189Oyster Creek-Bamber Lake 34.5Engineering & Procurement
AG1-191Chester-Pohatcong Mountain 34.5 kVPartially in Service - Under Construction
AG1-193Utica Junction 34.5 kVSuspended
AG1-197Morgan Street-Cochranton 34.5 kVSuspended
AG1-198Union City 34.5 kVUnder Construction
AG1-223Larrabee-Allaire 34.5 kVUnder Construction
AG1-226Dequine-Eugene 345 kVActive
AG1-232Magley 138 kVEngineering & Procurement
AG1-236Lanesville-Brokaw 345 kVActive
AG1-237Dequine-Eugene 345 kVEngineering & Procurement
AG1-254Salem-Woodstown 69 kVEngineering & Procurement
AG1-259Sunbury-Dalmatia 69 kVEngineering & Procurement
AG1-260Sunbury-Dalmatia 69 kVEngineering & Procurement
AG1-281Claysburg-HCR Tap 46 kVEngineering & Procurement
AG1-282Dunnsville 34.5 kVEngineering & Procurement
AG1-297Hanna-Tanners Creek 345 kVActive
AG1-301Miller REC-Warrior Ridge 46 kVEngineering & Procurement
AG1-302Olive-Reynolds #1 345 kVUnder Construction
AG1-320Glendale-Stephensburg 69 kVActive
AG1-323Blue Jacket 138 kVActive
AG1-324Jay-Desoto 138 kVEngineering & Procurement
AG1-341Summer Shade 161 kVActive
AG1-348Pequest River-Washington 34.5 kVIn Service
AG1-349Olive-Reynolds #2 345 kVEngineering & Procurement
AG1-354Summershade-Green County 161 kVActive
AG1-363Black Oak-Hatfield 500 kVEngineering & Procurement
AG1-365Allen 345 kVEngineering & Procurement
AG1-366Allen 345 kVEngineering & Procurement
AG1-367DeSoto 345 kVActive
AG1-368Tillman 138 kVEngineering & Procurement
AG1-369Logtown 138 kVEngineering & Procurement
AG1-374Blue Mound 345 kVActive
AG1-375Sorenson-Desoto 345 kVActive
AG1-386Smith-Francis Junction 25 kVIn Service
AG1-397Walston 12 kVWithdrawn
AG1-405Walnut Grove-Asahi 69 kVActive
AG1-406Walnut Grove-Asahi 69 kVActive
AG1-410Maddox Creek-RP Mone 345 kVActive
AG1-411Maddox Creek-RP Mone 345 kVActive
AG1-433Keystone-DeSoto 345 kVActive
AG1-436Olive-University Park 345 kVActive
AG1-447Olive-University Park 345 kVActive
AG1-460Kincaid-Pana 345 kVActive
AG1-462Cordova 345 kVActive
AG1-469Gordonsville 34.5 kVEngineering & Procurement
AG1-471Up Church-Wayne County 69 kVActive
AG1-478Wilmington 34.5 kVEngineering & Procurement
AG1-480Shawnee 34.5 kVEngineering & Procurement
AG1-482Hamilton 115 kVWithdrawn
AG1-494Boxwood-Riverville 138 kVActive
AG1-495Gilbert-Rocktown 34.5 kVEngineering & Procurement
AG1-499Lambs 12.47 kVUnder Construction
AG1-508Point Lookout 69 kVEngineering & Procurement
AG1-526West Garrard 345 kVActive
AG1-554South Kenton 138 kVEngineering & Procurement
AG1-555Dequine 345 kVEngineering & Procurement
AG1-558Buckner 34.5 kVEngineering & Procurement
AG1-559Caroline Pines 22 kVEngineering & Procurement
AG2-029Forest G. Hipple-Collingwood 345 kVActive
AG2-057Cardington-Liberty 69 kV IIActive
AG2-063North Hampton 69 kVActive
AG2-072Rockport 765 kVActive
AG2-073Crooksville 69 kVActive
AG2-081Mt. Sterling-Fogg Pike 69 kVActive
AG2-085Delaware-Royerton 138 kVActive
AG2-104Marysville-Flatlick 765 kVActive
AG2-106Marysville-Flatlick 765 kVActive
AG2-107Marysville-Flatlick 765 kVActive
AG2-111Perth 34.5 kV Substation (Circuit 408)Active
AG2-112Perth 34.5 kV Substation (Circuit 404)Active
AG2-114Dresden-Pontiac Midpoint 345 kVActive
AG2-119Galion-Roberts South 138 kV IIActive
AG2-125Camden-Crystal 69 kVActive
AG2-126Eugene 345 kVActive
AG2-149Galion-South Berwick 345 kVActive
AG2-152Banister-Bear Skin 138 kVActive
AG2-159Williamstown 69 kVActive
AG2-162Jefferson-Greentown 765 kVActive
AG2-163Dequine-Eugene 345 kVActive
AG2-164Jefferson-Greentown 765 kVActive
AG2-165Dumont-Greentown 765 kVActive
AG2-179Sewellton Junction 69 kVActive
AG2-184Harbert Metering 138 kVActive
AG2-191Mississinewa 138 kVActive
AG2-192Mississinewa 138 kVActive
AG2-212Dumont-Greentown 765 kVActive
AG2-216East Sidney-Quincy 138 kVActive
AG2-219Jefferson-Greentown 765 kVActive
AG2-230Dumont 345 kVActive
AG2-245Olive - Reynolds #1 345 kVActive
AG2-298Sulphur Creek-Loretto 69 kVActive
AG2-310Matt Funk 138 kVActive
AG2-311Smith Mountain 138 kVActive
AG2-328Dumont - Greentown 765 kVActive
AG2-329S Berwick - Galion 345 kVActive
AG2-330Dumont - Greentown 765 kVActive
AG2-331Jefferson-Greentown 765 kVActive
AG2-332East Elkhart – Elcona Tap 138 kVActive
AG2-360Broadford 138 kVActive
AG2-363Powerton 345 kVActive
AG2-364Powerton 345 kVActive
AG2-370Tillman 138 kVActive
AG2-378North Hampton – Medway 69 kVActive
AG2-385North Hampton 69 kVActive
AG2-400Allen 345 kVActive
AG2-401Losantville 345 kVActive
AG2-402Allen 345 kVActive
AG2-405Continental 69 kVActive
AG2-406Payne 69 kVActive
AG2-408Allen 345 kVActive
AG2-424Magnolia - Summersville 69 kVActive
AG2-444Bixby - Biers Run 345 kVActive
AG2-449Jefferson-Greentown 765 kVActive
AG2-453Lasalle - Plano 345 kVActive
AG2-487Madison - Tanners Creek 138 kVActive
AG2-491Meadow Lake 345 kVActive
AG2-515Midway 345 kV IIIActive
AG2-516Pecatonica 138kVActive
AG2-518Tech Drive 138 kVActive
AG2-519Royerton - Desoto 138 kVActive
AG2-524LaSalle Station - Mazon 138 kVActive
AG2-548Corwin - Elk 138 kVActive
AG2-550Bluff Point - Randolph 138 kVActive
AG2-551Bluff Point - Randolph 138 kVActive
AG2-568Stink Run – Sundial 138 kVActive
AG2-575Crego Rd. 138 kVActive
AG2-582Flint Run 500 kVActive
AG2-585Kensington 138kVActive
AG2-589Ravenswood - Hemlock 69 kVActive
AG2-637Randolph - Hodgin 138 kVActive
AG2-657Kanawha River - Carbondale 138 kVActive
AG2-660Nelson-Electric Junction 345 kVActive
AG2-665Corwin - Elk 138 kVActive
AG2-670Green County -Taylor County Junction 161 kVActive
AH1-004Avon - Renaker 138 kVActive
AH1-034Patton Road Junction - Summer Shade 69 kVActive
AH1-044Nelson - Electric Junction 345 kVActive
AH1-047Marengo - Belvidere 138 kVActive
AH1-055Kyger Creek - Don Marquis 345 kVActive
AH1-059Sharp Road 69 kVActive
AH1-060Cardington-Liberty 69 kV IIIActive
AH1-072Red Onion - VC5 69 kVActive
AH1-073Red Onion - VC5 69 kVActive
AH1-075North Waldo - Wild Creek 138 kVActive
AH1-098Wolf Glade-West Carroll 138 kVActive
AH1-133Saltville - Tazewell 138 kVActive
AH1-136Falcon - Middle Creek 46 kVActive
AH1-144Peter's Mountain 138 kVActive
AH1-145Peter's Mountain 138 kVActive
AH1-146White Rock - Wayne 345 kVActive
AH1-147White Rock - Wayne 345 kVActive
AH1-150Nelson-Electric Junction 345 kVActive
AH1-151Nelson-Electric Junction 345 kVActive
AH1-153Dumont 345 kVActive
AH1-164Oak Level - Tank Hill 138 kVActive
AH1-188Pigeon Creek 138 kVActive
AH1-196Prairie 345 kVActive
AH1-227Flemming - Fremont 69 kVActive
AH1-234Wempletown - Paddock 345 kVActive
AH1-239Upchurch - Zula 69 kVActive
AH1-269Claytor 138 kVActive
AH1-272Argenta - Twin Branch 345 kVActive
AH1-281Bluegrass Parkway Tap - Woodlawn 69 kVActive
AH1-282Galion - Ohio Central 345 kVActive
AH1-285Sandwich 138 kVActive
AH1-292Sullivan 345 kVActive
AH1-298Meridian 345 kVActive
AH1-302Olive - Reynolds 345 kVActive
AH1-304Delaware-Van Buren 138 kVActive
AH1-305Olive - Reynolds 345 kVActive
AH1-308Pennville - Adams 138 kVActive
AH1-309Kenzie Creek-Colby 138 kVActive
AH1-327Hardin Switch 345 kVActive
AH1-328Blue Jacket - Kirby 138 kVActive
AH1-337Randolph - Hodgin 138 kVActive
AH1-338McGirr Rd - Ritchie Road 138kVActive
AH1-339West Crawford 69 kVActive
AH1-341Stillman - Dixon 138KVActive
AH1-348Pound 34.5 kVActive
AH1-391Olive 138 kVActive
AH1-392Gravel Pit-Kankakee 138 kVActive
AH1-427Tommy Gooch - Garrard County 69 kVActive
AH1-482Olive - Reynolds #2 345 kVActive
AH1-535Nagel - Cane River 230 kVActive
AH1-537Pierce - Kyger Creek 345 kVActive
AH1-539South Kenton 138 kVActive
AH1-541Chestnut 345 kVActive
AH1-542Crissinger-Kirby 138kVActive
AH1-543Mulberry – Tazewell 345 kVActive
AH1-567University Park 138 kVActive
AH1-570Headquarters - Millersburg Junction 69 kVActive
AH1-571Headquarters - Millersburg Junction 69 kVActive
AH1-617Harbert Metering 138 kVActive
AH1-644Spicewood Metering 138 kVActive
AH1-661Cannelville 12.47 kVActive
AH1-664Goddard-Plumville 138 kVActive
AH1-665Goddard-Plumsville 138 kV IIActive
AH1-666Flemingsburg - Spurlock 138 kVActive
AH1-669Circleville-Biers Run 138 kVActive
AH1-670Blue Mound-Chestnut 345 kVActive
AH1-686Hanging Rock 765 kVActive
AH1-690Bay Shore - Lallendorf 345 kVActive
AH1-698Braidwood 345 kVActive
AH1-702Byron 345 kVActive
AH1-704Hannibal 138 kVActive
AH1-711Lemoyne 345 kVActive
AH1-714Lasalle 345 kVActive
AH1-718Nelson 345 kVActive
AH1-719Beverly 345 kVActive
AH1-721Laurel-Cooper 161 kVActive
AH1-735Richland 138 kVActive
U2-030Four Mile Ridge Wind 138kVIn Service
U2-072East Lima-Marysville 345kVIn Service
U2-073Frostburg 138kV IIIn Service
V1-011Haviland 138kVIn Service
V3-007Desoto-Tanners Creek #1 345kVIn Service
V4-067Cates Road Egg Harbor Township 12kVDeactivated
W1-003Oak HallIn Service
W1-004Oak HallIn Service
W1-005Oak HallIn Service
W1-006Oak HallIn Service
W1-056Ada-Dunkirk 69kVIn Service
W1-130Vine Road 12kVIn Service
W2-030Egg Harbor TownshipIn Service
W2-048Brokaw-LanesvilleIn Service
W3-077Broadway-Stewartsville 34.5kVIn Service
W4-005Blue Mound-LathamIn Service
X1-042WatervlietIn Service
X2-022Brokaw-LanesvilleIn Service
X2-052Dumont-Olive 345kVIn Service
X3-005Wildwood 12kVIn Service
X3-066Church Hill 69kVIn Service
Y1-033Penn Mar-Rock Wood 115kVIn Service
Y1-049Wurno 34.5kVIn Service
Y1-079Wye Mills 69kVIn Service
Y1-080Dorchester 12kVIn Service
Y3-023Country Side 12kVIn Service
Y3-024Bluff Point 12kVIn Service
Y3-058Rockawalkin 69kVIn Service
Z2-076Worcester South 25kVIn Service
Z2-077Worcester North 25kVIn Service
Z2-087Pontiac MidPoint-Brokaw 345kVIn Service
Z2-115Deer Creek 12.47kVIn Service
Z2-116Twin Branch 12.47kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with potential Affected System impacts. PJM initiates coordination with each Affected System Operator by providing a list of New Service Requests in the Cycle with potential impacts to their respective system. If the Affected System Operator indicates an Affected System Study is required, PJM will notify the Project Developer or Eligible Customer of the need for an Affected System Study. See below if any Affected System Operator requires a study for this project:

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

No cost allocated system reinforcements were identified for this project in the Phase I System Impact Study load flow analysis.

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement: b4000.9
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.9
Title
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard (Projected ISD 6/1/2029)
Description
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard. Loop in the Doubs-Goose Creek 500 kV line, the Doubs-Aspen 500 kV line, and the Woodside-Goose Creek 500 kV line. Install two 765/500 kV transformer at Rocky Point substation. 765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-306 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-306 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)

System Reinforcement: b4000.8
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.8
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (DVP local area to Rocky Point, roughly 4.8 miles)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-306 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-306 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.1
Title
Add two 765 kV breakers at Amos Substation to expand the breaker and a half scheme to accommodate the new Amos-Welton Spring 765 kV line (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-306 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-306 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)

System Reinforcement: b4000.7
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.7
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line - in DVP local area/Millville to Lovettsville section, roughly 10.5 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-306 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-306 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.2
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.2
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - AEP Section of the line is 30 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-306 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-306 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.3
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.3
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - APS/FE Section of the line is 145 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-306 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-306 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)

System Reinforcement: b4000.4
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.4
Title
Construct a new 765 kV switchyard - Welton Spring (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-306 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-306 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)

System Reinforcement: b4000.5
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.5
Title
Install four 250 MVAR shunt capacitors, and a +/-500 MVAR STATCOM at Welton Spring 765 kV substation
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-306 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-306 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.11
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.11
Title
Expand Black Oak Substation & Loop in the 502 Jct-Woodside 500 kV line (Projected ISD 6/1/2029)
Description
Expand Black Oak Substation to accommodate the connection of the 502 Jct-Woodside 500 kV line and loop the 502 Jct-Woodside 500 kV line into the Black Oak substation by constructing ~0.85 miles of new 500 kV line into and out of Black Oak 500 kV substation
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-306 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-306 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)

System Reinforcement: b4000.10
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.10
Title
Install four 250 MVAR cap banks (two on 765 and two on 500 kV side) and a +/-500 MVAR STATCOM on the 765 kV Rocky Point yard
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-306 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-306 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.a
Title
Upgrade (4) 1024.5 ACAR 24/13 sub conductors at Davis Besse
Description
Upgrade (4) 1024.5 ACAR 24/13 sub conductors at Davis Besse
Total Cost ($USD)
$1,099,401
Allocated Cost ($USD)
$0
Time Estimate
14 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-306 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-306 could receive cost allocation. Although AH1-306 may not presently have cost responsibility for this upgrade, AH1-306 is a potential Aggregate Pool Contributor.

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.b
Title
Upgrade (3) 345kV bus and line side disconnect switches at Davis Besse substation at Davis Besse
Description
Upgrade (3) 345kV bus and line side disconnect switches at Davis Besse substation at Davis Besse
Total Cost ($USD)
$1,324,127
Allocated Cost ($USD)
$0
Time Estimate
37 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-306 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-306 could receive cost allocation. Although AH1-306 may not presently have cost responsibility for this upgrade, AH1-306 is a potential Aggregate Pool Contributor.

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.c
Title
Upgrade 345kV 1033.5 AAC 61 sub conductors at Davis Besse substation at Davis Besse
Description
Upgrade 345kV 1033.5 AAC 61 sub conductors at Davis Besse substation at Davis Besse
Total Cost ($USD)
$257,762
Allocated Cost ($USD)
$0
Time Estimate
13 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-306 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-306 could receive cost allocation. Although AH1-306 may not presently have cost responsibility for this upgrade, AH1-306 is a potential Aggregate Pool Contributor.

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.d
Title
Reconductor (possible rebuild) 345kV 20.75 miles of transmission line and line drops at both remote ends
Description
Reconductor (possible rebuild) 345kV 20.75 miles of transmission line and line drops at both remote ends using dual (2) 1590 54/19 "Falcon" ACSS
Total Cost ($USD)
$121,594,776
Allocated Cost ($USD)
$0
Time Estimate
71 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-306 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-306 could receive cost allocation. Although AH1-306 may not presently have cost responsibility for this upgrade, AH1-306 is a potential Aggregate Pool Contributor.

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.e
Title
Upgrade 345kV 3500 SAC 127 sub conductor at Davis Besse
Description
Upgrade 345kV 3500 SAC 127 sub conductor at Davis Besse
Total Cost ($USD)
$257,762
Allocated Cost ($USD)
$0
Time Estimate
13 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-306 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-306 could receive cost allocation. Although AH1-306 may not presently have cost responsibility for this upgrade, AH1-306 is a potential Aggregate Pool Contributor.

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.f
Title
Upgrade (2) 345kV Wave Traps at Bayshore and (2) at Davis Besse
Description
Upgrade (2) 345kV Wave Traps at Bayshore and (2) at Davis Besse
Total Cost ($USD)
$1,215,694
Allocated Cost ($USD)
$0
Time Estimate
22 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-306 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-306 could receive cost allocation. Although AH1-306 may not presently have cost responsibility for this upgrade, AH1-306 is a potential Aggregate Pool Contributor.

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.g
Title
Upgrade (2) 345kV circuit breakers at Bayshore and (2) at Davis Besse
Description
Upgrade (2) 345kV circuit breakers at Bayshore and (2) at Davis Besse
Total Cost ($USD)
$7,786,806
Allocated Cost ($USD)
$0
Time Estimate
60 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-306 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-306 could receive cost allocation. Although AH1-306 may not presently have cost responsibility for this upgrade, AH1-306 is a potential Aggregate Pool Contributor.

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.h
Title
Upgrade (8) 1590 AAC 61 sub conductor at BAYSHORE
Description
Upgrade (8) 1590 AAC 61 sub conductor at BAYSHORE
Total Cost ($USD)
$211,119
Allocated Cost ($USD)
$0
Time Estimate
13 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-306 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-306 could receive cost allocation. Although AH1-306 may not presently have cost responsibility for this upgrade, AH1-306 is a potential Aggregate Pool Contributor.

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.i
Title
Upgrade B34544 CT at BAYSHORE
Description
Upgrade B34544 CT at BAYSHORE
Total Cost ($USD)
$712,356
Allocated Cost ($USD)
$0
Time Estimate
20 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-306 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-306 could receive cost allocation. Although AH1-306 may not presently have cost responsibility for this upgrade, AH1-306 is a potential Aggregate Pool Contributor.

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.j
Title
Upgrade (1) 1590 ACSR 45/7 sub conductor at Davis Besse
Description
Upgrade (1) 1590 ACSR 45/7 sub conductor at Davis Besse
Total Cost ($USD)
$393,871
Allocated Cost ($USD)
$0
Time Estimate
13 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-306 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-306 could receive cost allocation. Although AH1-306 may not presently have cost responsibility for this upgrade, AH1-306 is a potential Aggregate Pool Contributor.

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.k
Title
Upgrade the B34545 and 34562 (4) Meter and (2) Relay Thermals at Bayshore and Davis Besse
Description
Upgrade the B34545 and 34562 (4) Meter and (2) Relay Thermals at Bayshore and Davis Besse
Total Cost ($USD)
$998,835
Allocated Cost ($USD)
$0
Time Estimate
19 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-306 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-306 could receive cost allocation. Although AH1-306 may not presently have cost responsibility for this upgrade, AH1-306 is a potential Aggregate Pool Contributor.

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-015.a
Title
Reconductor (possible rebuild) 21.68 miles of transmission line and (1) line drop (line drop at Lemoyne) on the Davis Besse - Lemoyne 345 kV
Description
Reconductor (possible rebuild) 21.68 miles of transmission line and (1) line drop (line drop at Lemoyne) on the Davis Besse - Lemoyne 345 kV using dual (2) 1272 54/19 "Pheasant" ACSS
Total Cost ($USD)
$126,131,949
Allocated Cost ($USD)
$0
Time Estimate
73 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-306 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-306 could receive cost allocation. Although AH1-306 may not presently have cost responsibility for this upgrade, AH1-306 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-02LEMOYN 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-015.b
Title
Upgrade (4) L300 wavetraps at Davis Besse and Lemoyne
Description
Upgrade (4) L300 wavetraps at Davis Besse and Lemoyne
Total Cost ($USD)
$1,132,675
Allocated Cost ($USD)
$0
Time Estimate
22 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-306 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-306 could receive cost allocation. Although AH1-306 may not presently have cost responsibility for this upgrade, AH1-306 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-02LEMOYN 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18693
Title
Greentown 765 kV to Marysville 765 kV - Greenfield Line
Description
Construct a new greenfield 765kV line from Greentown to Marysville (~160 miles). Install 2 new 765kV breakers at Marysville and 2 new 765kV breakers at Greentown. Install 765kV shunt reactors at both Marysville and Greentown The new 765kV line reduces equipment at Dumont to be replaced to CB A2 and switch A2S2. s3442.26 replaces Dumont 765kV CB A2 and A2S2 "CONTINGENCY 'AEP_P1-2_GREENTOWN TO MARYSVILLE 765_SRT-A' OPEN BRANCH FROM BUS 242928 TO BUS 243207 CKT 1 / 242928 05MARYSV 765 243207 05GRNTWN 765 1 END CONTINGENCY 'AEP_P4_GREENTOWN CB 765_SRT-A' OPEN BRANCH FROM BUS 242928 TO BUS 243207 CKT 1 / 242928 05MARYSV 765 243207 05GRNTWN 765 1 END CONTINGENCY 'AEP_P4_MARYSVILLE CB 765_SRT-A' OPEN BRANCH FROM BUS 242928 TO BUS 243207 CKT 1 / 242928 05MARYSV 765 243207 05GRNTWN 765 1 END"
Total Cost ($USD)
$1,000,000,000
Allocated Cost ($USD)
$0
Time Estimate
72 to 120 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-306 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-306 could receive cost allocation. Although AH1-306 may not presently have cost responsibility for this upgrade, AH1-306 is a potential Aggregate Pool Contributor.

FacilityContingency
05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer(Any)
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line(Any)

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18686
Title
05MADDOX 345.0 kV to 05E LIMA 345.0 kV ckt 1 - String the 2nd conductor
Description
AEP owned line; string the 2nd conductor (2-bundle 954 ACSS) ~30.28 miles on the double circuit line & six wire, At East Lima station replace sub conductor & relay trip limit and at Maddox Creek replace 5.0 IPS Sch. 40 bus work, sub conductor & relay trip limit
Total Cost ($USD)
$48,000,000
Allocated Cost ($USD)
$0
Time Estimate
24 to 36 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-306 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-306 could receive cost allocation. Although AH1-306 may not presently have cost responsibility for this upgrade, AH1-306 is a potential Aggregate Pool Contributor.

FacilityContingency
05E LIMA-05MADDOX 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18687
Title
05HANGRCK_RJ 765.0 kV to 05HANG R 765.0 kV ckt Z1 - Replace Equipment
Description
At Hanging Rock Station replace the following equipment: D1S1 PH A, D1S1 PH B, D1S1 PH C, D1S2 PH A, D1S2 PH B, D1S2 PH C, D2S1 PH A, D2S1 PH B, D2S1 PH C, D2S2 PH A, D2S2 PH B, D2S2 PH C, Jefferson Trap PH A, Jefferson Trap PH B, Jefferson Trap PH C
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$0
Time Estimate
30 to 36 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-306 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-306 could receive cost allocation. Although AH1-306 may not presently have cost responsibility for this upgrade, AH1-306 is a potential Aggregate Pool Contributor.

FacilityContingency
05HANG R-05HANGRCK_RJ 765.0 kV Ckt Z1 line(Any)

System Reinforcement: b4000.6
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.6
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (Welton Spring to DVP local area, roughly 21 miles) (VA Portion)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-306 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-306 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)

System Reinforcement: n7683
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n7683
Title
Rebuild/reconductor 3.05 mi. of the 1275 ACSR/PE 54/19 conductor with 2-954 ACSR 54/7 conductor size with a SN rating of 1410 MVA.
Description
Rebuild/reconductor 3.05 mi. of the 1275 ACSR/PE 54/19 conductor with 2-954 ACSR 54/7 conductor size with a SN rating of 1410 MVA.
Total Cost ($USD)
$18,460,000
Allocated Cost ($USD)
$0
Time Estimate
24 to 36 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-306 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-306 could receive cost allocation. Although AH1-306 may not presently have cost responsibility for this upgrade, AH1-306 is a potential Aggregate Pool Contributor.

FacilityContingency
05MADDOX-AG1-410 TP 345.0 kV Ckt 1 line(Any)

System Reinforcement: b3775.1
Type
Load Flow
TO
ComEd
RTEP ID / TO ID
b3775.1
Title
Swap the NIPSCO Green Acre Tap towers from the St. John-Green Acres-Olive 345 kV line
Description
Outside of the Green Acres substation, swap the NIPSCO Green Acre Tap towers from the St. John-Green Acres-Olive 345 kV line to the University Park N-Olive 345 kV line to create a University Park N-Green Acres-Olive and St. John-Olive 345 kV lines.
Cost Information
Time Estimate
Dec 01 2026

Not Contingent

Note: AH1-306 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-306 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05MADDOX-AG1-410 TP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18689
Title
AG1-410 TP 345.0 kV to 05MADDOX 345.0 kV ckt 1 - string the 2nd circuit
Description
AEP owned line; string the 2nd circuit on the rebuilt double circuit line, ~ 2.85 miles of 2-bundle 1590 ACSR conductor. At Maddox Creek: Replace 345kV circuit breaker B2, subconductor, disconnect switches.
Total Cost ($USD)
$7,250,000
Allocated Cost ($USD)
$0
Time Estimate
24 to 36 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-306 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-306 could receive cost allocation. Although AH1-306 may not presently have cost responsibility for this upgrade, AH1-306 is a potential Aggregate Pool Contributor.

FacilityContingency
05MADDOX-AG1-410 TP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18635
Title
05MARYSVL_RM 765.0 kV to 05MALIS 765.0 kV ckt 1 - Replace Equipment
Description
Replace wave tap at Maliszewski towards Marysville along with circuit breakers, disconnects, and Sub Conductor.
Total Cost ($USD)
$24,200,000
Allocated Cost ($USD)
$0
Time Estimate
24 to 36 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-306 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-306 could receive cost allocation. Although AH1-306 may not presently have cost responsibility for this upgrade, AH1-306 is a potential Aggregate Pool Contributor.

FacilityContingency
05MALIS-05MARYSVL_RM 765.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18653
Title
05MALIS 765.0 kV to 05VASSEL 765.0 kV ckt 1 - Replace Equipment
Description
Replace circuit breaker B, Disconnects, and reconductor between structures 432-453 to bring rating up to the sub conductor.
Total Cost ($USD)
$153,100,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-306 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-306 could receive cost allocation. Although AH1-306 may not presently have cost responsibility for this upgrade, AH1-306 is a potential Aggregate Pool Contributor.

FacilityContingency
05MALIS-05VASSEL 765.0 kV Ckt 1 line(Any)

System Reinforcement: s2213.9
Type
Load Flow
TO
AEP
RTEP ID / TO ID
s2213.9 / (Pending)
Title
Six-wire 71.5 miles of the Pierce-Don Marquis line. Construct 0.13 miles of line to tie into Don Marquis station.
Description
Six-wire 71.5 miles of the Pierce-Don Marquis line. Construct 0.13 miles of line to tie into Don Marquis station.
Cost Information
Time Estimate
Jun 01 2027

Not Contingent

Note: AH1-306 contributes to the loading of an overloaded facility that is being mitigated by a planned supplemental project. AH1-306 is not contingent on this supplemental project as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05MARQUI-06PIERCE 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18819
Title
06PIERCE 345kV to 05MARQUIS 345kV ckt 1 - Replace Equipment
Description
At Pierce replace the following equipment: Switch 444, 446, 447, and 449, Bus, Risers, Jumpers, Wave Trap, and Line Relay At Don Marquis 345kV replace the following equipment: Circuit Breaker B2, Risers, and Line Reactor.
Total Cost ($USD)
$3,300,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-306 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-306 could receive cost allocation. Although AH1-306 may not presently have cost responsibility for this upgrade, AH1-306 is a potential Aggregate Pool Contributor.

FacilityContingency
05MARQUI-06PIERCE 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18680
Title
05MARYSV 765.0 kV to 05MARYSVL_RM 765.0 kV ckt Z1 - Replace Equipment
Description
Replace wave trap and associated equipment on Marysville Reactor towards Maliszewski.
Total Cost ($USD)
$2,200,000
Allocated Cost ($USD)
$0
Time Estimate
24 to 36 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-306 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-306 could receive cost allocation. Although AH1-306 may not presently have cost responsibility for this upgrade, AH1-306 is a potential Aggregate Pool Contributor.

FacilityContingency
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line(Any)

System Reinforcement: b3878.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b3878.1
Title
Upgrade 765 kV circuit breakers 'B' and 'B2' to 5000A 50kA breakers at Marysville Station
Description
Upgrade 765 kV circuit breakers 'B' and 'B2' to 5000A 50kA breakers at Marysville Station. In addition, the project will upgrade the existing wavetrap towards Sorenson.
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-306 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-306 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05MARYSV-05MARYSVL_RS 765.0 kV Ckt Z1 line(Any)

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18659
Title
05MARYSVL_RS 765.0 kV to 05MARYSV 765.0 kV ckt Z1 - Replace Equipment
Description
Replace wave trap, CB-B, and disconnect swiches at Marysville.
Total Cost ($USD)
$9,500,000
Allocated Cost ($USD)
$0
Time Estimate
24 to 36 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-306 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-306 could receive cost allocation. Although AH1-306 may not presently have cost responsibility for this upgrade, AH1-306 is a potential Aggregate Pool Contributor.

FacilityContingency
05MARYSV-05MARYSVL_RS 765.0 kV Ckt Z1 line(Any)

System Reinforcement: b3851.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b3851.1 / B3851.1
Title
Rebuild Allen-RP Mone 345kV
Description
Rebuild Allen –R.P. Mone 345kV line (18.6 miles).
Cost Information
Time Estimate
Jun 01 2027

Not Contingent

Note: AH1-306 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-306 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05RPMONE-05ALLEN 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18707
Title
05ALLEN 345.0 kV to 05RPMONE 345.0 kV ckt 1 - Replace Equipment
Description
At RP Mone: Replace CB B and B2 and associated disconnect switches. Replace 2 - 1700 KCM AAC station conductor. At Allen: Replace the disconnect switches for CBs C and C2 at Allen. Replace 2 - 2000 KCM AAC station conductor. B3851.1 to rebuild the Allen - RP Mone line needs to be completed. CB B is also be proposed to be replaced on another flowgate
Total Cost ($USD)
$5,000,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-306 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-306 could receive cost allocation. Although AH1-306 may not presently have cost responsibility for this upgrade, AH1-306 is a potential Aggregate Pool Contributor.

FacilityContingency
05RPMONE-05ALLEN 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18732
Title
05RPMONE 345kV to AG1-410 TP 345kV ckt 1 - Replace Equipment
Description
At R.P. Mone: Replace 345kV circuit breakers B & B1, Bus bar 4 x 3/4 Ph C, angle bus buar 4x4x1/4 Ph B, sub conductor, disconnect switches on B and B1 breakers
Total Cost ($USD)
$4,500,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-306 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-306 could receive cost allocation. Although AH1-306 may not presently have cost responsibility for this upgrade, AH1-306 is a potential Aggregate Pool Contributor.

FacilityContingency
05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line(Any)

System Reinforcement: b3788.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b3788.1 / B3788.1
Title
Replace limiting station elements at Kyger Creek
Description
Upgrade existing 345 kV terminal equipment at Kyger Creek on the Kyger Creek-Sporn 345 kV line. Projected in-service date 6/1/2028 Replace AEP-owned station takeoff riser and breaker BB risers at OVEC-owned Kyger Creek station.
Cost Information
Time Estimate
Nov 18 2027

Not Contingent

Note: AH1-306 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-306 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05SPORN-06KYGER 345.0 kV Ckt 1 line(Any)

System Reinforcement: b3788.2
Type
Load Flow
TO
OVEC
RTEP ID / TO ID
b3788.2 / B3788.2
Title
Replace limiting station elements at Kyger Creek
Description
Upgrade existing 345 kV terminal equipment at Kyger Creek on the Kyger Creek-Sporn 345 kV line. Projected in-service date 6/1/2028 Replace OVEC-owned breaker AA risers, bus work, and breaker AA disconnect switches at OVEC-owned Kyger Creek station.
Cost Information
Time Estimate
Jun 01 2028

Not Contingent

Note: AH1-306 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-306 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05SPORN-06KYGER 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18751
Title
05KYGER 345kV to 05SPORN 345kV ckt 1 - Replace Equipment and Sag Study
Description
Sag study Sporn - Kyger Creek line and at Kyger Creek Replace the following equipment: 2156.0 KCM ACSR (84/19), 3000A Switch, CB-BB, 2870 MCM ACSR (Bus), GCB AA, Wave Trap, Line Relay/CT, Meters, Switch 104, and Switch 10
Total Cost ($USD)
$5,052,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 60 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-306 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-306 could receive cost allocation. Although AH1-306 may not presently have cost responsibility for this upgrade, AH1-306 is a potential Aggregate Pool Contributor.

FacilityContingency
05SPORN-06KYGER 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
DEOK
RTEP ID / TO ID
(Pending) / F4504
Title
DEOK New Sub and New 345kV Line from Tanner's Creek
Description
This Network Upgrade will be joint effort between DEOK & AEP to mitigate the Miami Fort - Tanner's Creek 345kV violations. DEOK Scope of Work: - DEOK will construct a new 5-breaker Ring Bus, 345kV Switching Station in Northern Kentucky called 'Idlewild'(Lat: 39° 5'15.11"N, Long: 84°49'10.14"W) - DEOK will loop the Tanner's Creek (AEP) - East Bend (DEOK) and Miami Fort (DEOK) - Terminal (DEOK) 345kV circuits into Idlewild Substation - In order to loop the Miami Fort - Terminal circuit into Idlewild Substation, DEOK will retire ~0.68 miles of the Miami Fort - Terminal circuit and add ~0.95 miles of new 345kV conductor (954ACSR 45x7, 2cond/ph, 100C). The new conductor will be built on existing DEOK easement. - DEOK will construct a new 345kV circuit from Idlewild substation to a pole that is just outside AEP's Tanner's Creek Substation. This circuit will be ~2.48 miles long with (1) Ohio River Crossing. The new 345kV circuit will be built will 954ACSS/TW, 2-conductor/phase, 200C conductor. Part of the new 345kV circuit will be built on existing DEOK easement, but DEOK will need to obtain ~1.0 mile of new easement. Line ownership for this new circuit will change at the tower which is just outside AEP's Tanner's Creek Substation in Lawrenceburg, Indiana.
Total Cost ($USD)
$72,000,000
Allocated Cost ($USD)
$0
Time Estimate
72 to 84 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-306 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-306 could receive cost allocation. Although AH1-306 may not presently have cost responsibility for this upgrade, AH1-306 is a potential Aggregate Pool Contributor.

FacilityContingency
05TANNER-08M.FORT 345.0 kV Ckt 1 lineAEP_P1-2_#7441_100545_SRT-A
05TANNER-08M.FORT 345.0 kV Ckt 1 lineAEP_P4_#7445_05MARYSV 765_B_SRT-A
05TANNER-08M.FORT 345.0 kV Ckt 1 lineAEP_P4_#7441_05SORENS 765_J1_SRT-A
05TANNER-08M.FORT 345.0 kV Ckt 1 lineAEP_P2-2_#9456_06DEARB1 345_1_SRT-A
05TANNER-08M.FORT 345.0 kV Ckt 1 lineAEP_P7-1_#485___SRT-A
05TANNER-08M.FORT 345.0 kV Ckt 1 lineAEP_P4_#7446_05MARYSV 765_B2_SRT-A
05TANNER-08M.FORT 345.0 kV Ckt 1 lineDEOK_P_4519BUFFCLIFTYPIERCEDEAR1OVEC_SRT-A
05TANNER-08M.FORT 345.0 kV Ckt 1 lineAEP_P4_#9456_06DEARB1 345_DC_SRT-A
05TANNER-08M.FORT 345.0 kV Ckt 1 lineDEOK_P4_1579_EASTBEND_SRT-A
05TANNER-08M.FORT 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18821
Title
AEP Reinforcements for DEOK New Sub and New 345kV Line from Tanner's Creek
Description
AEP Scope of Work: At Tanners Creek station- install a 345 kV circuit breaker "T", relocate Lawrenceburg #1 345 kV line (between breakers T and T2), relocate Miami Fort 345 kV line (between breakers T and T1), relocate formerly East Bend 345 kV line (to Idlewild Duke station) (between breakers S and S1), and install new Tanners Creek - Idlewild 345 kV line #2 (between breakers R and R1), ~0.35 miles of AEP install and ~2.48 miles of Duke install.
Total Cost ($USD)
$6,700,000
Allocated Cost ($USD)
$0
Time Estimate
72 to 84 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-306 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-306 could receive cost allocation. Although AH1-306 may not presently have cost responsibility for this upgrade, AH1-306 is a potential Aggregate Pool Contributor.

FacilityContingency
05TANNER-08M.FORT 345.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.357
Title
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Description
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-306 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-306 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.341
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.341
Title
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.
Description
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV substation and extend approximately 0.2 miles of conductor to fly-over the site.
Cost Information
Time Estimate
Jul 13 2029

Not Contingent

Note: AH1-306 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-306 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.342
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.342
Title
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Description
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Cost Information
Time Estimate
Jul 13 2029

Not Contingent

Note: AH1-306 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-306 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.355
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.355
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-306 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-306 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.325
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.325
Title
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Description
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Cost Information
Time Estimate
Feb 24 2029

Not Contingent

Note: AH1-306 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-306 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.326
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.326
Title
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Description
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Cost Information
Time Estimate
Feb 24 2029

Not Contingent

Note: AH1-306 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-306 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.327
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.327
Title
Upgrade/install equipment at Ladysmith Substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230 kV strings of breaker and a half scheme.
Description
Upgrade/install equipment at Ladysmith substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230kV strings of breaker and a half scheme.
Cost Information
Time Estimate
Feb 24 2029

Not Contingent

Note: AH1-306 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-306 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.344
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.344
Title
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AH1-306 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-306 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.345
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.345
Title
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AH1-306 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-306 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.346
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.346
Title
Cut-in 500kV line from Kraken substation into Yeat substation
Description
Cut-in 500kV line from Kraken substation into Yeat substation
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-306 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-306 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.348
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.348
Title
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.
Description
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers. A new redundant breaker ring will be added at Kraken to accommodate the new 500kV line from North Anna to Kraken.
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-306 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-306 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.349
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.349
Title
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Description
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AH1-306 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-306 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.351
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.351
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AH1-306 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-306 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.352
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.352
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AH1-306 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-306 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.350
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.350
Title
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Description
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AH1-306 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-306 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.356
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.356
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-306 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-306 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

Attachments

AH1-306 One Line Diagram

AH1-306 One Line Diagram.jpg
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.