AH1-327 Phase I Study Report

v1.00 released 2025-10-29 21:29

Hardin Switch 345 kV

8.44 MW Capacity / 0.0 MW Energy

Introduction

This Phase I System Impact Study Report (PH1) has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, sections 307 and 308 for New Service Requests (projects) in Transition Cycle 2. The Project Developer/Eligible Customer (developer) is Hardin Solar Energy III LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is American Electric Power.

Preface

The Phase I System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle executive summary format and (ii) an individual project-level basis. The Phase I System Impact Study Results (for both the executive summary and individual reports) will be publicly available on PJM’s website. Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.3, PJM takes the following actions during the Phase I System Impact Study:
  1. PJM studies each New Service Request on a summer peak, winter peak and light load RTEP base case study. The case year is dependent on the new services cycle under study. PJM will identify the base case year to be used in the study of a specific cycle on its website.
  2. PJM will only perform load flow analysis during the Phase I System Impact Study.
  3. In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with Affected System impacts and provides each Affected System Operator with a list of New Service Request in the Cycle with potential impacts to their respective system.
  4. PJM will create both the short circuit and stability base cases to be used in the Phase II System Impact Study.
  5. The Phase I System Impact Study results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.
The Transmission Owner takes the following actions during the Phase I System Impact Study:
  1. Identify required Interconnection Facilities to accommodate the New Service Request.
  2. Identify required Network Upgrades to mitigate system violations from the Phase I System Impact Study.
  3. Provide planning-level preliminary estimates of Interconnection Facilities and Network Upgrades including scope, cost and elapsed time to complete the work.

Decision Point I Requirements

At the close of Phase I System Impact Study, PJM will initiate Decision Point I (DP1). During DP1, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.A.1. Additional information on these elements is available in PJM Manual 14H sections 4.4, 6, and 7.

Allowable project modifications at Decision Point I are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

General

The Project Developer has proposed an uprate to a planned/existing Solar facility located in the American Electric Power zone — Hardin County, Ohio. This project is an increase to the developer’s AD2-086/AE1-090 project(s), which will share the same Point of Interconnection. The AH1-327 project is a 8.44 MW Capacity only uprate to the previous project(s). The total installed facilities will have a capability of 250.0 MW with 158.44 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AH1-327
Project Name:
Hardin Switch 345 kV
Project Developer Name:
Hardin Solar Energy III LLC
State:
Ohio
County:
Hardin
Transmission Owner:
American Electric Power
MFO:
250.0
MWE:
0.0
MWC:
8.44
Fuel Type:
Solar
Basecase Study Year:
2028

Physical Interconnection Facility Study

Physical Interconnection Facilities Study is not performed as part of the Phase I System Impact Study. Physical Interconnection Facilities Study will commence in the Phase II System Impact Study.

Point of Interconnection

AH1-327 will interconnect on the American Electric Power transmission system at the Hardin 345 kV Station.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In the Phase I SIS, the costs shown are subject to change as a result of a facility study performed by the TO during the Phase II or Phase III System Impact Study.

Based on the Phase I SIS results, the AH1-327 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit are also shown below.

Cost Summary
DescriptionCost Allocated to AH1-327Cost Subject to Readiness*
Transmission Owner Interconnection Facilities (TOIF)$0$0
Other Scope$0$0
Option To Build Oversight$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$0$0
Network Upgrades$0$0
System Reliability Network Upgrades
Steady State Thermal & Voltage (SP & LL)$0$0
Transient Stability$0$0
Short Circuit$0$0
Transmission Owner Analysis
SubRegional$0$0
Distribution$0$0
Affected System Reinforcements
AFS - PJM Violatons$0$0
AFS - Non-PJM Violations$0$0
Total$0$0

* Contributes to calculation for Readiness Deposit #2 (RD2). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim deliverability study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 309 (Decision Point I) A.1.a.i and PJM Manual 14H, section 6.2, Readiness Deposit #2 (RD2) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point I (DP1), the Project Developer or Eligible Customer is required to submit Readiness Deposit #2, which is calculated as 10% of cost allocation for required Phase I Network Upgrades minus Readiness Deposit #1.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Readiness Deposit #2 Due for Project AH1-327

Readiness Deposit #2 has been calculated for the project based on the Phase I System Impact Study results and is shown in the table below. This Readiness Deposit #2 must be provided at Decision Point I through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit
Project ID10% of cost allocation for Phase I Network UpgradesReadiness Deposit #1 Received (RD1)Readiness Deposit #2 (RD2) for AH1-327 Project due at DP1
ABA - B
AH1-327$0$33,760$0

Note: Failure to provide an acceptable form of Readiness Deposit #2 by the end of Decision Point I will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Physical Interconnection
RTEP IDDescriptionTotal Cost ($USD)Allocated Cost ($USD)
(Pending)no interconnections facilities required to support the interconnection$0 $0

Based on the scope of work for the Interconnection Facilities, it is expected to take 0 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

The schedule for any required Network Impact Reinforcements will be more clearly identified in the Phase II and Phase III System Impact Studies.

Transmission Owner Analysis

No Transmission Owner impacts identified.

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. AEP interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Meteorological Data Reporting Requirement
The solar generation facility shall provide the Transmission Provider with site-specific meteorological data including:
  • Temperature (degrees Fahrenheit)
  • Atmospheric Pressure (hectopascals)
  • Irradiance
  • Forced outage data
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AH1-327 was evaluated as a 0.0 MW (8.44 MW Capacity) injection in the AEP area.

AH1-327 was evaluated as part of a plant. The plant consists of AH1-327. The total Energy output of the plant was evaluated at its maximum seasonal capability of 250.0 MW (0.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AP
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
AP_P1-2_MP-500-028_SRT-A
SingleAC120.65 %3792.0B4574.960.95
GD2AP
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
AP_P1-3_MP-765-502T_SRT-A
SingleAC120.64 %3792.0B4574.630.95
GD2AP
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
AP_P1-3_MP-765-502T_SRT-A
SingleAC139.36 %3792.0B5284.610.92
GD2AP
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
AP_P1-2_MP-500-028_SRT-A
SingleAC139.32 %3792.0B5282.910.92
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P1-2_MP-500-007A_SRT-A
SingleAC130.62 %3729.0B4870.981.12
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P1-2_MP-500-008A_SRT-SL
SingleAC124.1 %3729.0B4627.61.08
GD2ATSI
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line
ATSI_P1-2_TE-345-602_SRT-A
SingleAC142.52 %1683.0B2398.590.58
GD2ATSI
02DAV-BE-02HAYES 345.0 kV Ckt 1 line
ATSI_P1-2_OEC-345-825_SRT-A
SingleAC136.86 %1892.0B2589.310.52
GD2ATSI
02DAV-BE-02HAYES 345.0 kV Ckt 1 line
ATSI_P1-2_OEC-345-824_SRT-A
SingleAC136.39 %1892.0B2580.580.52
GD2ATSI
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line
ATSI_P1-2_OEC-345-810_SRT-A
SingleAC136.64 %1646.0B2249.010.5
GD2ATSI
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line
ATSI_P1-2_OEC-345-809_SRT-A
SingleAC128.94 %1646.0B2122.340.51
GD2ATSI
02HAYES-02BEAVER 345.0 kV Ckt 1 line
ATSI_P1-2_OEC-345-825_SRT-A
SingleAC136.05 %1878.0B2554.950.55
GD2ATSI
02HAYES-02BEAVER 345.0 kV Ckt 1 line
ATSI_P1-2_OEC-345-824_SRT-A
SingleAC135.68 %1878.0B2548.090.55
GD2ATSI
02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line
ATSI_P1-2_TE-345-601_SRT-A
SingleAC113.99 %1878.0B2140.730.62
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P1-2_MP-500-007A_SRT-A
SingleAC131.92 %3792.0B5002.281.12
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P1-2_MP-500-008A_SRT-SL
SingleAC125.38 %3792.0B4754.331.08
GD2AEP
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
AP_P1-3_MP-765-501T_SRT-A
SingleAC118.76 %4142.0B4919.181.38
GD2AEP
05MALIS-05VASSEL 765.0 kV Ckt 1 line
AEP_P1-2_#706_SRT-A
SingleAC114.0 %4142.0B4722.061.38
GD2AEP
05MALIS-05VASSEL 765.0 kV Ckt 1 line
AEP_P1-2_#708_11_SRT-A
SingleAC110.34 %4142.0B4570.10.92
GD2AEP
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
AEP_P1-2_#706_SRT-A
SingleAC116.18 %4571.0B5310.771.31
GD2AEP
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
AEP_P1-2_#728_584_SRT-A
SingleAC111.32 %4571.0B5088.241.03
GD2AEP
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
AEP_P1-2_#706_SRT-A
SingleAC116.43 %4571.0B5322.011.31
GD2AEP
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
AEP_P1-2_#728_584_SRT-A
SingleAC111.46 %4571.0B5094.731.03
GD2ATSI
AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line
ATSI_P1-2_OEC-345-810_SRT-A
SingleAC123.08 %1798.0B2212.910.5
GD2ATSI
AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line
ATSI_P1-2_OEC-345-809_SRT-A
SingleAC117.76 %1798.0B2117.360.51

Details for 01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-028_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-028_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.65 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4574.96
MW Contribution:0.95
Bus #Bus NameTypeMW Contribution
964601AG1-323 GEN
Solar/Wind Harmer
2.731
964601AG1-323 GEN
Solar/Wind Harmer
1.82
270224U2-072_GEN2
Solar/Wind Harmer
0.001
938701AE1-092 GEN
Solar/Wind Harmer
10.928
25194408D.CRK1
Adder
7.324
24728905RICHG2
Adder
3.587
970883AG2-550 GEN
Solar/Wind Harmer
6.617
926881AC1-175 GEN
Solar/Wind Harmer
0.001
960971AF2-388 GEN
Solar/Wind Harmer
3.871
270599AE1-208 GEN
Solar/Wind Harmer
6.026
24318805MLG1
50/50
6.637
972173AH1-669 GEN
Solar/Wind Harmer
3.569
24686405CER G5
Adder
8.342
253338AC1-165 GEN
Solar/Wind Harmer
0.003
970191AG2-125 GEN
Solar/Wind Harmer
1.745
270222AC2-111 GEN
Solar/Wind Harmer
3.385
270004AE1-209 GEN
Solar/Wind Harmer
1.427
270356AE2-297 GEN
Solar/Wind Harmer
0.009
971617AH1-308 GEN
Solar/Wind Harmer
5.478
959331AF2-224 GEN
Solar/Wind Harmer
4.573
270191TR4_S_V150
Solar/Wind Harmer
0.001
270491AE1-102 GEN2
Solar/Wind Harmer
0.843
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24642205MAYFLWER
Adder
0.585
274753CRETE EC ;3U
Adder
7.553
270258AD1-119 GEN
Solar/Wind Harmer
0.002
972038AH1-567 GEN2
Adder
0.333
270053AF1-130 C
Solar/Wind Harmer
1.432
238118U2-030_1
Solar/Wind Helper
0.318
238148AE2-230_GEN2
Solar/Wind Helper
0.429
237038AE2-054 C
Solar/Wind Helper
0.235
23779801AA1-109
Solar/Wind Helper
0.166
971073AG2-665 GEN
Solar/Wind Harmer
6.448
942861AE2-305 GEN
Solar/Wind Harmer
5.482
270518AE2-148 GEN
Solar/Wind Harmer
0.606
25326109MON D
Adder
1.288
25183208HLCRTG
Solar/Wind Harmer
0.011
972159AH1-661 GEN
Adder
0.972
252509AD1-136 GEN
Solar/Wind Harmer
0.034
970329AG2-216 GEN
Solar/Wind Harmer
2.92
25194508D.CRK3
Adder
1.369
24728805RICHG1
Adder
3.587
970885AG2-551 GEN
Solar/Wind Harmer
2.206
270383AD1-128 GEN
Solar/Wind Harmer
0.004
24379505HDWTR1G C
Solar/Wind Harmer
0.002
944541AF1-119 GEN
Solar/Wind Harmer
0.442
270201AC2-176 GEN
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
0.494
960441AF2-335 GEN
Solar/Wind Harmer
6.577
270031AE2-169
Solar/Wind Harmer
3.616
945421AF1-207 GEN
Solar/Wind Harmer
0.001
971199AH1-059 GEN
Solar/Wind Harmer
2.587
339221AD2-048_GEN
Solar/Wind Harmer
0.004
965791AG1-447 GEN
Solar/Wind Harmer
5.91
247620Y3-023
Adder
0.425
270526AF1-158 GEN
Solar/Wind Harmer
0.008
972045AH1-571 GEN
Solar/Wind Harmer
1.341
24441505OLIV SLR
Solar/Wind Harmer
0
276843GEN-1.7
Solar/Wind Harmer
0.206
958011AF2-095 GEN
Solar/Wind Harmer
9.182
241960AC2-195 GEN
Solar/Wind Harmer
0.005
944971AF1-162 GEN
Solar/Wind Harmer
6.345
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
971573AH1-285 GEN
Solar/Wind Harmer
1.18
958491AF2-143 GEN
Solar/Wind Harmer
9.485
235063AE1-101 C2
Solar/Wind Helper
1.433
237001AB1-127_GEN
Solar/Wind Helper
0.381
237034AC2-136 C
Solar/Wind Helper
0.194
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
961821AG1-024 GEN
Solar/Wind Harmer
4.271
270432AC2-029 GEN
Solar/Wind Harmer
3.168
270269AC2-059
Solar/Wind Harmer
0.004
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
945631AF1-228 GEN
Solar/Wind Harmer
0
270340AC2-060 GEN
Solar/Wind Harmer
0.008
241972AD1-140 GEN
Solar/Wind Harmer
0.755
270578AF1-285 GEN2
Solar/Wind Harmer
0.455
253400AC2-068 GEN
Solar/Wind Harmer
0.859
25196508WSDLE4
Adder
8.216
972163AH1-664 GEN
Solar/Wind Harmer
7.37
965101AG1-375 GEN
Solar/Wind Harmer
6.597
970115AG2-085 GEN
Solar/Wind Harmer
2.631
971609AH1-304 GEN
Solar/Wind Harmer
1.074
24699105WLD G1 C
Solar/Wind Harmer
0.001
965041AG1-368 GEN
Solar/Wind Harmer
6.496
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
24386205FR-12G C
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
963841AG1-237 GEN
Solar/Wind Harmer
2.789
24477305BRIDGE
Adder
0.321
274776LINCOLN ;7U
Adder
7.74
274814UNIV PK N;0U
Adder
4.624
274807UNIV PK N;3U
Adder
4.614
274805UNIV PK N;1U
Adder
4.594
274687WILL CNTY;4U
Adder
25.484
274687WILL CNTY;4U
Adder
25.484
274731ELWOOD EC;2P
Adder
14.987
274733ELWOOD EC;3P
Adder
14.987
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
276882AE2-255 GEN
Solar/Wind Harmer
0.739
23750501ELLIOTTS
Solar/Wind Helper
0.636
238152AF2-075_GEN
Solar/Wind Helper
0.611
23546401DTGZ2-030
Solar/Wind Helper
0.077
3138216PACIFIC
Solar/Wind Helper
0.038
23684201S70BUS2
50/50
0.305
270512AE1-227 GEN2
Solar/Wind Harmer
1.892
971191AH1-055 GEN
Solar/Wind Harmer
18.65
252510AF1-249 C
Solar/Wind Harmer
0.052
270485AE1-090_GEN
Solar/Wind Harmer
0.001
25196008MFTGT1
Adder
1.289
970243AG2-164 GEN
Solar/Wind Harmer
3.888
972167AH1-666 GEN
Solar/Wind Harmer
5.306
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
9.887
270043AE2-236 GEN
Solar/Wind Harmer
4.199
965021AG1-366 GEN
Solar/Wind Harmer
2.178
945111AF1-176 GEN
Solar/Wind Harmer
5.203
274772LINCOLN ;3U
Adder
7.74
274724RIVER EC ;11
Adder
16.226
274802UNIV PARK;5U
Adder
5.329
970941AG2-585 GEN
Solar/Wind Harmer
7.971
276897AD1-100 C
Solar/Wind Harmer
0.008
274800UNIV PARK;3U
Adder
5.327
24441205WTRV SLR C
Solar/Wind Harmer
0
276893AG1-478 C
Solar/Wind Harmer
0.252
274729ELWOOD EC;1P
Adder
14.987
276805AD2-038 GEN
Solar/Wind Harmer
0.002
237048AF1-022 C
Solar/Wind Helper
0.17
970077AG2-063 GEN
Solar/Wind Harmer
4.025
972269AH1-719 GEN
Adder
2.302
962581AG1-107 GEN
Solar/Wind Harmer
0.001
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
270186AC1-089 GEN
Solar/Wind Harmer
0.004
253378AE2-206_GEN
Solar/Wind Harmer
0.004
25326509SID D
Adder
1.268
970239AG2-162 GEN
Solar/Wind Harmer
1.662
270209AC1-174_GEN
Solar/Wind Harmer
0.001
970825AG2-519 GEN
Solar/Wind Harmer
7.293
942221AE2-234 GEN
Solar/Wind Harmer
0.033
970321AG2-212 GEN
Solar/Wind Harmer
2.844
970611AG2-400 GEN
Solar/Wind Harmer
6.533
246938BC-WTG3
Solar/Wind Harmer
0.235
246937BC-WTG2
Solar/Wind Harmer
0.263
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
970235AG2-159 GEN
Solar/Wind Harmer
3.948
970235AG2-159 GEN
Solar/Wind Harmer
2.265
270007AE1-245 C
Solar/Wind Harmer
0.002
970241AG2-163 GEN
Solar/Wind Harmer
3.747
957891AF2-083 GEN
Solar/Wind Harmer
0.001
274770LINCOLN ;1U
Adder
7.74
274771LINCOLN ;2U
Adder
7.74
970623AG2-406 GEN
Solar/Wind Harmer
1.169
274808UNIV PK N;4U
Adder
4.563
274888KELLY CRK;1U
Solar/Wind Harmer
0.375
972259AH1-714 GEN
Adder
17.426
970107AG2-081 GEN
Solar/Wind Harmer
1.909
960161AF2-307 GEN
Solar/Wind Harmer
4.195
238175AF1-290_GEN
Solar/Wind Helper
0.13
235020AA1-095 C
Solar/Wind Helper
0.045
962691AG1-118 GEN
Solar/Wind Harmer
7.548
270459AD2-067 GEN
Solar/Wind Harmer
0
23559101PLEAS2
50/50
11.891
23562301OGROV1
50/50
2.291
970149AG2-104 GEN
Solar/Wind Harmer
32.932
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
270510AE1-227 GEN1
Solar/Wind Harmer
1.892
927014AC1-188 GEN
Solar/Wind Harmer
0.004
270263AC1-001 GEN
Solar/Wind Harmer
0.716
270159DARBY CT4
Adder
8.94
253325AC1-069 GEN
Solar/Wind Harmer
0.011
970593AG2-378 GEN
Solar/Wind Harmer
1.575
270223U2-072_GEN1
Solar/Wind Harmer
0.001
970773AG2-487 GEN
Solar/Wind Harmer
1.163
970091AG2-072 GEN
Adder
72.107
24791305MDL-5G
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.406
970373AG2-245 GEN
Solar/Wind Harmer
13.568
963741AG1-226 GEN
Solar/Wind Harmer
15.2
943021AE2-325 GEN
Solar/Wind Harmer
3.342
941551AE2-152 GEN
Solar/Wind Harmer
0
970627AG2-408 GEN
Solar/Wind Harmer
1.96
966841AG1-555 GEN
Solar/Wind Harmer
0.73
270216AD2-079_GEN
Solar/Wind Harmer
0.001
972043AH1-570 GEN
Solar/Wind Harmer
1.674
961051AF2-396 GEN
Solar/Wind Harmer
12.817
961051AF2-396 GEN
Solar/Wind Harmer
8.545
274803UNIV PARK;6U
Adder
5.329
274887GEN-1.85
Solar/Wind Harmer
0.168
945391AF1-204 GEN
Solar/Wind Harmer
6.775
958481AF2-142 GEN
Solar/Wind Harmer
9.506
274862TOP CROP ;2U
Solar/Wind Harmer
0.857
274879MINONK ;1U
Solar/Wind Harmer
0.267
23585401KL_K28_T16
Solar/Wind Helper
1.442
23777901MDS_W4-102
Solar/Wind Helper
0.151
237002AB1-128_GEN
Solar/Wind Helper
0.382
237006AB1-125 GEN
Solar/Wind Helper
0.106
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Harmer
0.006
270520AE2-214 GEN
Solar/Wind Harmer
0.011
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
270158DARBY CT3
Adder
8.918
971985AH1-537 GEN
Solar/Wind Harmer
2.087
253349AC2-067 GEN
Solar/Wind Harmer
2.136
24721905FLATG4
Adder
24.202
970153AG2-106 GEN
Solar/Wind Harmer
19.471
241955AC1-078 GEN
Solar/Wind Harmer
0.006
241974AD2-163_GEN2
Solar/Wind Harmer
0.005
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
8.886
253370AE2-315 SEC1
Adder
1.959
253371AE2-315 SEC2
Adder
1.853
25194608D.CRK4
Adder
1.592
946031AF1-268 GEN
Solar/Wind Harmer
6.268
970289AG2-191 GEN
Solar/Wind Harmer
0.722
970291AG2-192 GEN
Solar/Wind Harmer
0.656
247642Z2-115 C
Solar/Wind Harmer
0.003
24728505AND G1
Adder
3.565
24755605MDL-5G
Solar/Wind Harmer
0.001
270535AF1-215 GEN1
Solar/Wind Harmer
0.008
247643Z2-116 C
Solar/Wind Harmer
0
276806AD2-047 C O1
Solar/Wind Harmer
3.613
943121AE2-341 GEN
Solar/Wind Harmer
10.635
943591AF1-030 GEN
Solar/Wind Harmer
7.072
964991AG1-363 GEN
Solar/Wind Helper
4.266
316097T157 G90
Solar/Wind Helper
1.323
237080AD1-060 GEN
Solar/Wind Helper
0.294
970879AG2-548 GEN
Solar/Wind Harmer
6.448
940611AE2-048 GEN
Solar/Wind Harmer
17.483
941391AE2-136 GEN
Solar/Wind Harmer
9.848
270156DARBY CT1
Adder
9.085
270157DARBY CT2
Adder
9.063
270367AC2-061_GEN
Solar/Wind Harmer
0.005
25196408WSDLE3
Adder
8.545
25196308WSDLE2
Adder
8.471
25196208WSDLE1
Adder
8.45
25196708WSDLE6
Adder
8.428
25196108MFTGT2
Adder
1.467
25196108MFTGT2
Adder
1.362
971673AH1-337 GEN
Solar/Wind Harmer
4.312
270543AE2-219 C
Solar/Wind Harmer
0.004
270240V3-007_GEN2
Solar/Wind Harmer
0.002
24729505KEY G4
Adder
6.141
270071AF1-092 GEN
Solar/Wind Harmer
12.598
270594AE1-207 GEN
Solar/Wind Harmer
7.357
270435AC2-044 GEN
Solar/Wind Harmer
0.821
24691005MDL-2G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
247607V1-011 GEN
Solar/Wind Harmer
0.001
971771AH1-392 GEN
Solar/Wind Harmer
6.442
971769AH1-391 GEN
Solar/Wind Harmer
7.189
274728ELWOOD EC;5P
Adder
14.987
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
238126S14_GEN_1
Solar/Wind Helper
0.764
23684101S70BUS1
50/50
0.299
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
25196808ZIMRHP
Adder
73.247
25196008MFTGT1
Adder
1.331
970333AG2-219 GEN
Solar/Wind Harmer
4.752
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
2.859
945371AF1-202 GEN
Solar/Wind Harmer
0.001
270005AE1-210 C O1
Solar/Wind Harmer
1.427
970825AG2-519 GEN
Solar/Wind Harmer
2.336
270032AE2-172
Solar/Wind Harmer
4.379
965011AG1-365 GEN
Solar/Wind Harmer
6.533
246936BC-WTG1
Solar/Wind Harmer
0.263
270489AE1-102 GEN1
Solar/Wind Harmer
0.843
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.087
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
24387305FR-4G C
Solar/Wind Harmer
0.002
945111AF1-176 GEN
Solar/Wind Harmer
11.453
270505AE1-170 C O1
Solar/Wind Harmer
6.739
274773LINCOLN ;4U
Adder
7.74
274774LINCOLN ;5U
Adder
7.74
274751CRETE EC ;1U
Adder
7.553
274723RIVER EC ;12
Adder
16.418
274801UNIV PARK;4U
Adder
5.327
971997AH1-543 GEN
Solar/Wind Harmer
3.315
23751201ROTHROCK
Solar/Wind Helper
0.849
23583801GRNGAP
Solar/Wind Helper
4.948
238149AF1-291A_GEN
Solar/Wind Helper
0.122
237061AD1-155 GEN
Solar/Wind Helper
0.046
238221AF1-254 C O1
Solar/Wind Helper
0.235
276691AA1-018 GEN1
Solar/Wind Harmer
0.768
23562501BACKB
Solar/Wind Helper
1.042
235054AD2-180 GEN
Solar/Wind Helper
1.935
238108AE1-109 GEN1
Solar/Wind Helper
0.102
235531U2-073 GEN
Solar/Wind Helper
3.033
23559001PLEAS1
50/50
11.891
23562401OGROV2
50/50
2.277
961921AG1-034 GEN
Solar/Wind Harmer
6.407
270291AC1-194 GEN
Solar/Wind Harmer
5.661
270273AD2-016 GEN
Solar/Wind Harmer
0.74
942051AE2-217 GEN
Solar/Wind Harmer
12.683
24686205CER G4
Adder
8.375
253333AC1-068 GEN
Solar/Wind Harmer
0.011
970605AG2-385 GEN
Solar/Wind Harmer
4.258
253415AE1-040 GEN
Solar/Wind Harmer
0.003
253406AD2-031_GEN
Solar/Wind Harmer
0.512
270391AF1-285 GEN3
Solar/Wind Harmer
0.455
25196608WSDLE5
Adder
8.301
970519AG2-331 GEN
Solar/Wind Harmer
17.281
970699AG2-449 GEN
Solar/Wind Harmer
1.662
958171AF2-111 GEN
Solar/Wind Harmer
16.577
944531AF1-118 GEN
Solar/Wind Harmer
29.606
270437AC2-090 C
Solar/Wind Harmer
0.003
958821AF2-173 GEN
Solar/Wind Harmer
9.221
970513AG2-328 GEN
Solar/Wind Harmer
2.844
970517AG2-330 GEN
Solar/Wind Harmer
17.067
270247TR4_N_V136
Solar/Wind Harmer
0.042
970349AG2-230 GEN
Solar/Wind Harmer
9.745
24728705AND G3
Adder
7.455
970031AG2-029 GEN
Solar/Wind Harmer
4.207
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.466
274752CRETE EC ;2U
Adder
7.553
970193AG2-126 GEN
Solar/Wind Harmer
9.564
972228AH1-698 GEN2
Adder
3.385
274826FISK ;BP
Adder
10.003
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
20.817
274730ELWOOD EC;6P
Adder
14.987
270404AC1-167 GEN
Solar/Wind Harmer
0.003
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
23750701CROSSCHOOL
Solar/Wind Helper
1.364
238127S14_GEN_2
Solar/Wind Helper
0.764
235062AE1-101 C1
Solar/Wind Helper
1.433
270317AD1-130_GEN
Solar/Wind Harmer
0.01
971029AG2-637 GEN
Solar/Wind Harmer
9.944
972165AH1-665 GEN
Solar/Wind Harmer
5.903
945581AF1-223 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0.001
965051AG1-369 GEN
Solar/Wind Harmer
3.247
971347AH1-153 GEN
Solar/Wind Harmer
9.745
971611AH1-305 GEN
Solar/Wind Harmer
3.852
24697605MDL-3G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0.001
971619AH1-309 GEN
Solar/Wind Harmer
2.888
274775LINCOLN ;6U
Adder
7.74
274777LINCOLN ;8U
Adder
7.74
972037AH1-567 GEN1
Adder
0.167
960591AF2-350 GEN
Solar/Wind Harmer
6.377
970833AG2-524 GEN
Solar/Wind Harmer
6.995
970833AG2-524 GEN
Solar/Wind Harmer
4.664
276868AE1-113 GEN
Solar/Wind Harmer
1.267
238208AF1-136 C
Solar/Wind Helper
0.19
962761AG1-125 GEN
Solar/Wind Harmer
30.492
24686505CER G6
Adder
8.408
25326309TAIT D
Adder
1.071
252507AC2-088 GEN
Solar/Wind Harmer
0.308
270462AD2-086
Solar/Wind Harmer
0.014
247536S-71 GEN
Solar/Wind Harmer
0.266
970245AG2-165 GEN
Solar/Wind Harmer
2.844
276903AD2-071 C
Solar/Wind Harmer
7.32
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270063AE2-323 C
Solar/Wind Harmer
0.005
339216AC1-074 GEN
Solar/Wind Harmer
0.177
24385905FR-11G C
Solar/Wind Harmer
0.002
274754CRETE EC ;4U
Adder
7.553
274732ELWOOD EC;7P
Adder
8.75
939401AE1-172 GEN
Solar/Wind Harmer
4.75
944231AF1-091 GEN
Solar/Wind Harmer
1.688
238117U2-030
Solar/Wind Helper
0.318
238147AE2-230_GEN1
Solar/Wind Helper
0.427
235067AD1-061 GEN
Solar/Wind Helper
0.427
962771AG1-126 GEN
Solar/Wind Harmer
30.492
970689AG2-444 GEN
Solar/Wind Harmer
14.59
972203AH1-686 GEN
Adder
2.352
270284AF1-227 GEN1
Solar/Wind Harmer
0.009
253383AE2-342_GEN
Solar/Wind Harmer
0.002
241973AD2-163_GEN1
Solar/Wind Harmer
0.005
943861AF1-054 GEN
Solar/Wind Harmer
2.706
943851AF1-053 GEN
Solar/Wind Harmer
1.874
253372AE2-315 SEC3
Adder
1.853
253372AE2-315 SEC3
Adder
1.853
25306009OHH W.
Adder
2.812
252524AE2-267 GEN
Solar/Wind Harmer
0.002
270302AB2-170 GEN
Solar/Wind Harmer
0.004
971653AH1-327 GEN
Solar/Wind Harmer
0.947
270024AE2-089 GEN
Solar/Wind Harmer
0.007
970289AG2-191 GEN
Solar/Wind Harmer
1.247
963791AG1-232 GEN
Solar/Wind Harmer
8.837
957201AF2-014 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.008
274811UNIV PK N;7U
Adder
4.584
972227AH1-698 GEN1
Adder
2.383
274827FISK ;RP
Adder
7.089
970179AG2-119 GEN
Solar/Wind Harmer
5.69
274735ELWOOD EC;4P
Adder
14.987
970169AG2-114 GEN
Solar/Wind Harmer
6.327
238109AE1-109 GEN2
Solar/Wind Helper
0.102
238110AE1-109 GEN3
Solar/Wind Helper
0.102
24721705FLATG2
Adder
24.202
970155AG2-107 GEN
Solar/Wind Harmer
19.471
970947AG2-589 GEN
Solar/Wind Harmer
0.243
270349AD2-093_GEN
Solar/Wind Harmer
0.005
24686105CER G3
Adder
8.419
253343AC1-166 GEN
Solar/Wind Harmer
0.003
24723205RIVRG3
Adder
18.885
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.836
253370AE2-315 SEC1
Adder
1.959
253371AE2-315 SEC2
Adder
1.853
960071AF2-298 GEN
Solar/Wind Harmer
3.39
25194608D.CRK4
Adder
1.592
945681AF1-233 GEN
Solar/Wind Harmer
12.498
971995AH1-542 GEN
Solar/Wind Harmer
2.424
970613AG2-401 GEN
Solar/Wind Harmer
4.843
965651AG1-433 GEN
Solar/Wind Harmer
1.936
965031AG1-367 GEN
Solar/Wind Harmer
6.586
970291AG2-192 GEN
Solar/Wind Harmer
0.853
247521TR3_G114
Solar/Wind Harmer
0.237
270246TR4_N_V150
Solar/Wind Harmer
0.042
965421AG1-410 GEN
Solar/Wind Harmer
19.465
24728605AND G2
Adder
3.565
24695305TIMB G C
Solar/Wind Harmer
0.002
270055AF2-134 C O1
Solar/Wind Harmer
0.005
24639705ELKHART HY
Adder
0.142
270449AD2-020 GEN
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0.003
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.584
276776AD2-060 GEN
Solar/Wind Harmer
0.666
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
276901AD2-066 C O1
Solar/Wind Harmer
0.006
23751101LEADS_P59
Solar/Wind Helper
1.597
316095T157 G97
Solar/Wind Helper
1.323
238185AF2-356 C
Solar/Wind Helper
2.474
237030AB1-096 C
Solar/Wind Helper
0.061
24318905MLG2
50/50
4.855
270471AD2-092_GEN
Solar/Wind Harmer
0.005
24685805CER G1
Adder
8.364
24685905CER G2
Adder
8.364
24723005RIVRG1
Adder
18.885
24723105RIVRG2
Adder
18.885
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
253370AE2-315 SEC1
Adder
1.959
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
25322209TAIT E
Adder
9.53
25322209TAIT E
Adder
9.316
971655AH1-328 GEN
Solar/Wind Harmer
2.415
252519AF1-045_GEN
Solar/Wind Harmer
5.902
252516AE2-318_GEN
Solar/Wind Harmer
5.235
276820AF1-078_GEN
Solar/Wind Harmer
0.002
247621Y3-024
Adder
0.228
971613AH1-306 GEN
Solar/Wind Harmer
3.153
965681AG1-436 GEN
Solar/Wind Harmer
8.059
270444AC2-157 GEN1
Solar/Wind Harmer
0.003
971587AH1-292 GEN
Solar/Wind Harmer
4.687
971125AH1-004 GEN
Solar/Wind Harmer
2.546
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
238120AE2-309 GEN
Solar/Wind Helper
0.483
238169AE2-226 GEN1
Solar/Wind Helper
0.6
238170AE2-226 GEN2
Solar/Wind Helper
0.6
23777801MSM_W1-116
Solar/Wind Helper
0.098
237025AB1-124 C
Solar/Wind Helper
0.142
237085AD2-009_GEN
Solar/Wind Helper
1.425
316411AF1-147_GEN1
Solar/Wind Helper
0.754
316415AF1-147_GEN2
Solar/Wind Helper
0.754
944201AF1-088_MTX
Adder
106.522
957141AF2-008_MTX
Adder
53.261
NYPJM->LTFIMP_NY
CLTF
4.491
LGEELTFEXP_LGEE->PJM
CLTF
6.272
WECLTFEXP_WEC->PJM
CLTF
3.434
AG2-052LTFEXP_AG2-052->PJM
LTF
0.214
AH1-155LTFEXP_AH1-155->PJM
LTF
0.321
CBM West 1LTFEXP_CBM-W1->PJM
CBM
126.393
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.84
MECLTFEXP_MEC->PJM
CLTF
14.465
SIGELTFEXP_SIGE->PJM
CLTF
0.467
LAGNLTFEXP_LAGN->PJM
CLTF
14.169
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.052
TVALTFEXP_TVA->PJM
CLTF
7.036
CPLELTFEXP_CPLE->PJM
CLTF
1.288
CBM West 2LTFEXP_CBM-W2->PJM
CBM
105.476

Details for 01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line l/o AP_P1-3_MP-765-502T_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-502T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.64 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4574.63
MW Contribution:0.95
Bus #Bus NameTypeMW Contribution
24318805MLG1
50/50
6.637
972173AH1-669 GEN
Solar/Wind Harmer
3.569
24686405CER G5
Adder
8.342
253338AC1-165 GEN
Solar/Wind Harmer
0.003
970191AG2-125 GEN
Solar/Wind Harmer
1.745
270222AC2-111 GEN
Solar/Wind Harmer
3.385
270004AE1-209 GEN
Solar/Wind Harmer
1.427
270356AE2-297 GEN
Solar/Wind Harmer
0.009
971617AH1-308 GEN
Solar/Wind Harmer
5.478
959331AF2-224 GEN
Solar/Wind Harmer
4.573
270191TR4_S_V150
Solar/Wind Harmer
0.001
270491AE1-102 GEN2
Solar/Wind Harmer
0.843
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24642205MAYFLWER
Adder
0.585
274753CRETE EC ;3U
Adder
7.553
270258AD1-119 GEN
Solar/Wind Harmer
0.002
972038AH1-567 GEN2
Adder
0.333
270053AF1-130 C
Solar/Wind Harmer
1.432
238118U2-030_1
Solar/Wind Helper
0.318
238148AE2-230_GEN2
Solar/Wind Helper
0.429
237038AE2-054 C
Solar/Wind Helper
0.235
23779801AA1-109
Solar/Wind Helper
0.166
971073AG2-665 GEN
Solar/Wind Harmer
6.448
942861AE2-305 GEN
Solar/Wind Harmer
5.482
270518AE2-148 GEN
Solar/Wind Harmer
0.606
25326109MON D
Adder
1.288
25183208HLCRTG
Solar/Wind Harmer
0.011
972159AH1-661 GEN
Adder
0.972
252509AD1-136 GEN
Solar/Wind Harmer
0.034
970329AG2-216 GEN
Solar/Wind Harmer
2.92
25194508D.CRK3
Adder
1.369
24728805RICHG1
Adder
3.587
970885AG2-551 GEN
Solar/Wind Harmer
2.206
270383AD1-128 GEN
Solar/Wind Harmer
0.004
24379505HDWTR1G C
Solar/Wind Harmer
0.002
944541AF1-119 GEN
Solar/Wind Harmer
0.442
270201AC2-176 GEN
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
0.494
960441AF2-335 GEN
Solar/Wind Harmer
6.577
270031AE2-169
Solar/Wind Harmer
3.616
945421AF1-207 GEN
Solar/Wind Harmer
0.001
971199AH1-059 GEN
Solar/Wind Harmer
2.587
339221AD2-048_GEN
Solar/Wind Harmer
0.004
965791AG1-447 GEN
Solar/Wind Harmer
5.91
247620Y3-023
Adder
0.425
270526AF1-158 GEN
Solar/Wind Harmer
0.008
972045AH1-571 GEN
Solar/Wind Harmer
1.341
24441505OLIV SLR
Solar/Wind Harmer
0
276843GEN-1.7
Solar/Wind Harmer
0.206
958011AF2-095 GEN
Solar/Wind Harmer
9.182
241960AC2-195 GEN
Solar/Wind Harmer
0.005
944971AF1-162 GEN
Solar/Wind Harmer
6.345
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
971573AH1-285 GEN
Solar/Wind Harmer
1.18
958491AF2-143 GEN
Solar/Wind Harmer
9.485
235063AE1-101 C2
Solar/Wind Helper
1.433
237001AB1-127_GEN
Solar/Wind Helper
0.381
237034AC2-136 C
Solar/Wind Helper
0.194
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
961821AG1-024 GEN
Solar/Wind Harmer
4.271
270432AC2-029 GEN
Solar/Wind Harmer
3.168
270269AC2-059
Solar/Wind Harmer
0.004
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
945631AF1-228 GEN
Solar/Wind Harmer
0
270340AC2-060 GEN
Solar/Wind Harmer
0.008
241972AD1-140 GEN
Solar/Wind Harmer
0.755
270578AF1-285 GEN2
Solar/Wind Harmer
0.455
253400AC2-068 GEN
Solar/Wind Harmer
0.859
25196508WSDLE4
Adder
8.216
972163AH1-664 GEN
Solar/Wind Harmer
7.37
965101AG1-375 GEN
Solar/Wind Harmer
6.597
970115AG2-085 GEN
Solar/Wind Harmer
2.631
971609AH1-304 GEN
Solar/Wind Harmer
1.074
24699105WLD G1 C
Solar/Wind Harmer
0.001
965041AG1-368 GEN
Solar/Wind Harmer
6.496
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
24386205FR-12G C
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
963841AG1-237 GEN
Solar/Wind Harmer
2.789
24477305BRIDGE
Adder
0.321
274776LINCOLN ;7U
Adder
7.74
274814UNIV PK N;0U
Adder
4.624
274807UNIV PK N;3U
Adder
4.614
274805UNIV PK N;1U
Adder
4.594
274687WILL CNTY;4U
Adder
25.484
274687WILL CNTY;4U
Adder
25.484
274731ELWOOD EC;2P
Adder
14.987
274733ELWOOD EC;3P
Adder
14.987
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
276882AE2-255 GEN
Solar/Wind Harmer
0.739
23750501ELLIOTTS
Solar/Wind Helper
0.636
238152AF2-075_GEN
Solar/Wind Helper
0.611
23546401DTGZ2-030
Solar/Wind Helper
0.077
3138216PACIFIC
Solar/Wind Helper
0.038
23684201S70BUS2
50/50
0.305
270512AE1-227 GEN2
Solar/Wind Harmer
1.892
971191AH1-055 GEN
Solar/Wind Harmer
18.65
252510AF1-249 C
Solar/Wind Harmer
0.052
270485AE1-090_GEN
Solar/Wind Harmer
0.001
25196008MFTGT1
Adder
1.289
970243AG2-164 GEN
Solar/Wind Harmer
3.888
972167AH1-666 GEN
Solar/Wind Harmer
5.306
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
9.887
270043AE2-236 GEN
Solar/Wind Harmer
4.199
965021AG1-366 GEN
Solar/Wind Harmer
2.178
945111AF1-176 GEN
Solar/Wind Harmer
5.203
274772LINCOLN ;3U
Adder
7.74
274724RIVER EC ;11
Adder
16.226
274802UNIV PARK;5U
Adder
5.329
970941AG2-585 GEN
Solar/Wind Harmer
7.971
276897AD1-100 C
Solar/Wind Harmer
0.008
274800UNIV PARK;3U
Adder
5.327
24441205WTRV SLR C
Solar/Wind Harmer
0
276893AG1-478 C
Solar/Wind Harmer
0.252
970077AG2-063 GEN
Solar/Wind Harmer
4.025
972269AH1-719 GEN
Adder
2.302
962581AG1-107 GEN
Solar/Wind Harmer
0.001
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
270186AC1-089 GEN
Solar/Wind Harmer
0.004
253378AE2-206_GEN
Solar/Wind Harmer
0.004
25326509SID D
Adder
1.268
970239AG2-162 GEN
Solar/Wind Harmer
1.662
270209AC1-174_GEN
Solar/Wind Harmer
0.001
970825AG2-519 GEN
Solar/Wind Harmer
7.293
942221AE2-234 GEN
Solar/Wind Harmer
0.033
970321AG2-212 GEN
Solar/Wind Harmer
2.844
970611AG2-400 GEN
Solar/Wind Harmer
6.533
246938BC-WTG3
Solar/Wind Harmer
0.235
246937BC-WTG2
Solar/Wind Harmer
0.263
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
970235AG2-159 GEN
Solar/Wind Harmer
3.948
970235AG2-159 GEN
Solar/Wind Harmer
2.265
270007AE1-245 C
Solar/Wind Harmer
0.002
970241AG2-163 GEN
Solar/Wind Harmer
3.747
957891AF2-083 GEN
Solar/Wind Harmer
0.001
274770LINCOLN ;1U
Adder
7.74
274771LINCOLN ;2U
Adder
7.74
970623AG2-406 GEN
Solar/Wind Harmer
1.169
274808UNIV PK N;4U
Adder
4.563
274888KELLY CRK;1U
Solar/Wind Harmer
0.375
972259AH1-714 GEN
Adder
17.426
970107AG2-081 GEN
Solar/Wind Harmer
1.909
960161AF2-307 GEN
Solar/Wind Harmer
4.195
238175AF1-290_GEN
Solar/Wind Helper
0.13
235020AA1-095 C
Solar/Wind Helper
0.045
962691AG1-118 GEN
Solar/Wind Harmer
7.548
964601AG1-323 GEN
Solar/Wind Harmer
2.731
964601AG1-323 GEN
Solar/Wind Harmer
1.82
270224U2-072_GEN2
Solar/Wind Harmer
0.001
938701AE1-092 GEN
Solar/Wind Harmer
10.928
25194408D.CRK1
Adder
7.324
24728905RICHG2
Adder
3.587
970883AG2-550 GEN
Solar/Wind Harmer
6.617
926881AC1-175 GEN
Solar/Wind Harmer
0.001
960971AF2-388 GEN
Solar/Wind Harmer
3.871
270599AE1-208 GEN
Solar/Wind Harmer
6.026
970627AG2-408 GEN
Solar/Wind Harmer
1.96
966841AG1-555 GEN
Solar/Wind Harmer
0.73
24721905FLATG4
Adder
24.202
970153AG2-106 GEN
Solar/Wind Harmer
19.471
241955AC1-078 GEN
Solar/Wind Harmer
0.006
241974AD2-163_GEN2
Solar/Wind Harmer
0.005
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
8.886
253370AE2-315 SEC1
Adder
1.959
253371AE2-315 SEC2
Adder
1.853
23684101S70BUS1
50/50
0.299
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
25196808ZIMRHP
Adder
73.247
25196008MFTGT1
Adder
1.331
970333AG2-219 GEN
Solar/Wind Harmer
4.752
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
23559101PLEAS2
50/50
11.891
23562301OGROV1
50/50
2.291
970149AG2-104 GEN
Solar/Wind Harmer
32.932
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
270510AE1-227 GEN1
Solar/Wind Harmer
1.892
927014AC1-188 GEN
Solar/Wind Harmer
0.004
270263AC1-001 GEN
Solar/Wind Harmer
0.716
270159DARBY CT4
Adder
8.94
253325AC1-069 GEN
Solar/Wind Harmer
0.011
970593AG2-378 GEN
Solar/Wind Harmer
1.575
270223U2-072_GEN1
Solar/Wind Harmer
0.001
970773AG2-487 GEN
Solar/Wind Harmer
1.163
970091AG2-072 GEN
Adder
72.107
24791305MDL-5G
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.406
970373AG2-245 GEN
Solar/Wind Harmer
13.568
963741AG1-226 GEN
Solar/Wind Harmer
15.2
943021AE2-325 GEN
Solar/Wind Harmer
3.342
941551AE2-152 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.768
23562501BACKB
Solar/Wind Helper
1.042
235054AD2-180 GEN
Solar/Wind Helper
1.935
238108AE1-109 GEN1
Solar/Wind Helper
0.102
235531U2-073 GEN
Solar/Wind Helper
3.033
23559001PLEAS1
50/50
11.891
23562401OGROV2
50/50
2.277
961921AG1-034 GEN
Solar/Wind Harmer
6.407
270291AC1-194 GEN
Solar/Wind Harmer
5.661
270273AD2-016 GEN
Solar/Wind Harmer
0.74
942051AE2-217 GEN
Solar/Wind Harmer
12.683
24686205CER G4
Adder
8.375
253333AC1-068 GEN
Solar/Wind Harmer
0.011
970605AG2-385 GEN
Solar/Wind Harmer
4.258
253415AE1-040 GEN
Solar/Wind Harmer
0.003
253406AD2-031_GEN
Solar/Wind Harmer
0.512
270391AF1-285 GEN3
Solar/Wind Harmer
0.455
25196608WSDLE5
Adder
8.301
970519AG2-331 GEN
Solar/Wind Harmer
17.281
970699AG2-449 GEN
Solar/Wind Harmer
1.662
958171AF2-111 GEN
Solar/Wind Harmer
16.577
944531AF1-118 GEN
Solar/Wind Harmer
29.606
270437AC2-090 C
Solar/Wind Harmer
0.003
958821AF2-173 GEN
Solar/Wind Harmer
9.221
970513AG2-328 GEN
Solar/Wind Harmer
2.844
970517AG2-330 GEN
Solar/Wind Harmer
17.067
270247TR4_N_V136
Solar/Wind Harmer
0.042
970349AG2-230 GEN
Solar/Wind Harmer
9.745
24728705AND G3
Adder
7.455
970031AG2-029 GEN
Solar/Wind Harmer
4.207
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.466
274752CRETE EC ;2U
Adder
7.553
970193AG2-126 GEN
Solar/Wind Harmer
9.564
972228AH1-698 GEN2
Adder
3.385
274826FISK ;BP
Adder
10.003
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
20.817
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Harmer
0.006
270520AE2-214 GEN
Solar/Wind Harmer
0.011
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
270158DARBY CT3
Adder
8.918
971985AH1-537 GEN
Solar/Wind Harmer
2.087
253349AC2-067 GEN
Solar/Wind Harmer
2.136
270317AD1-130_GEN
Solar/Wind Harmer
0.01
971029AG2-637 GEN
Solar/Wind Harmer
9.944
972165AH1-665 GEN
Solar/Wind Harmer
5.903
945581AF1-223 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0.001
965051AG1-369 GEN
Solar/Wind Harmer
3.247
971347AH1-153 GEN
Solar/Wind Harmer
9.745
971611AH1-305 GEN
Solar/Wind Harmer
3.852
24697605MDL-3G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0.001
971619AH1-309 GEN
Solar/Wind Harmer
2.888
274775LINCOLN ;6U
Adder
7.74
274777LINCOLN ;8U
Adder
7.74
972037AH1-567 GEN1
Adder
0.167
960591AF2-350 GEN
Solar/Wind Harmer
6.377
970833AG2-524 GEN
Solar/Wind Harmer
6.995
970833AG2-524 GEN
Solar/Wind Harmer
4.664
276868AE1-113 GEN
Solar/Wind Harmer
1.267
238208AF1-136 C
Solar/Wind Helper
0.19
274730ELWOOD EC;6P
Adder
14.987
270404AC1-167 GEN
Solar/Wind Harmer
0.003
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
23750701CROSSCHOOL
Solar/Wind Helper
1.364
238127S14_GEN_2
Solar/Wind Helper
0.764
235062AE1-101 C1
Solar/Wind Helper
1.433
270216AD2-079_GEN
Solar/Wind Harmer
0.001
972043AH1-570 GEN
Solar/Wind Harmer
1.674
961051AF2-396 GEN
Solar/Wind Harmer
12.817
961051AF2-396 GEN
Solar/Wind Harmer
8.545
274803UNIV PARK;6U
Adder
5.329
274887GEN-1.85
Solar/Wind Harmer
0.168
945391AF1-204 GEN
Solar/Wind Harmer
6.775
958481AF2-142 GEN
Solar/Wind Harmer
9.506
274862TOP CROP ;2U
Solar/Wind Harmer
0.857
274879MINONK ;1U
Solar/Wind Harmer
0.267
23585401KL_K28_T16
Solar/Wind Helper
1.442
23777901MDS_W4-102
Solar/Wind Helper
0.151
237002AB1-128_GEN
Solar/Wind Helper
0.382
237006AB1-125 GEN
Solar/Wind Helper
0.106
962761AG1-125 GEN
Solar/Wind Harmer
30.492
24686505CER G6
Adder
8.408
25326309TAIT D
Adder
1.071
252507AC2-088 GEN
Solar/Wind Harmer
0.308
270462AD2-086
Solar/Wind Harmer
0.014
247536S-71 GEN
Solar/Wind Harmer
0.266
970245AG2-165 GEN
Solar/Wind Harmer
2.844
276903AD2-071 C
Solar/Wind Harmer
7.32
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270063AE2-323 C
Solar/Wind Harmer
0.005
339216AC1-074 GEN
Solar/Wind Harmer
0.177
24385905FR-11G C
Solar/Wind Harmer
0.002
274754CRETE EC ;4U
Adder
7.553
274732ELWOOD EC;7P
Adder
8.75
939401AE1-172 GEN
Solar/Wind Harmer
4.75
944231AF1-091 GEN
Solar/Wind Harmer
1.688
238117U2-030
Solar/Wind Helper
0.318
238147AE2-230_GEN1
Solar/Wind Helper
0.427
235067AD1-061 GEN
Solar/Wind Helper
0.427
25194608D.CRK4
Adder
1.592
946031AF1-268 GEN
Solar/Wind Harmer
6.268
970289AG2-191 GEN
Solar/Wind Harmer
0.722
970291AG2-192 GEN
Solar/Wind Harmer
0.656
247642Z2-115 C
Solar/Wind Harmer
0.003
24728505AND G1
Adder
3.565
24755605MDL-5G
Solar/Wind Harmer
0.001
270535AF1-215 GEN1
Solar/Wind Harmer
0.008
247643Z2-116 C
Solar/Wind Harmer
0
276806AD2-047 C O1
Solar/Wind Harmer
3.613
943121AE2-341 GEN
Solar/Wind Harmer
10.635
943591AF1-030 GEN
Solar/Wind Harmer
7.072
964991AG1-363 GEN
Solar/Wind Helper
4.266
316097T157 G90
Solar/Wind Helper
1.323
237080AD1-060 GEN
Solar/Wind Helper
0.294
962771AG1-126 GEN
Solar/Wind Harmer
30.492
970689AG2-444 GEN
Solar/Wind Harmer
14.59
972203AH1-686 GEN
Adder
2.352
270284AF1-227 GEN1
Solar/Wind Harmer
0.009
253383AE2-342_GEN
Solar/Wind Harmer
0.002
241973AD2-163_GEN1
Solar/Wind Harmer
0.005
943861AF1-054 GEN
Solar/Wind Harmer
2.706
943851AF1-053 GEN
Solar/Wind Harmer
1.874
253372AE2-315 SEC3
Adder
1.853
253372AE2-315 SEC3
Adder
1.853
25306009OHH W.
Adder
2.812
252524AE2-267 GEN
Solar/Wind Harmer
0.002
270302AB2-170 GEN
Solar/Wind Harmer
0.004
971653AH1-327 GEN
Solar/Wind Harmer
0.947
270024AE2-089 GEN
Solar/Wind Harmer
0.007
970289AG2-191 GEN
Solar/Wind Harmer
1.247
963791AG1-232 GEN
Solar/Wind Harmer
8.837
957201AF2-014 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.008
274811UNIV PK N;7U
Adder
4.584
972227AH1-698 GEN1
Adder
2.383
274827FISK ;RP
Adder
7.089
970179AG2-119 GEN
Solar/Wind Harmer
5.69
274735ELWOOD EC;4P
Adder
14.987
970169AG2-114 GEN
Solar/Wind Harmer
6.327
238109AE1-109 GEN2
Solar/Wind Helper
0.102
238110AE1-109 GEN3
Solar/Wind Helper
0.102
24721705FLATG2
Adder
24.202
970155AG2-107 GEN
Solar/Wind Harmer
19.471
970947AG2-589 GEN
Solar/Wind Harmer
0.243
270349AD2-093_GEN
Solar/Wind Harmer
0.005
24686105CER G3
Adder
8.419
253343AC1-166 GEN
Solar/Wind Harmer
0.003
24723205RIVRG3
Adder
18.885
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.836
253370AE2-315 SEC1
Adder
1.959
253371AE2-315 SEC2
Adder
1.853
960071AF2-298 GEN
Solar/Wind Harmer
3.39
25194608D.CRK4
Adder
1.592
945681AF1-233 GEN
Solar/Wind Harmer
12.498
971995AH1-542 GEN
Solar/Wind Harmer
2.424
970613AG2-401 GEN
Solar/Wind Harmer
4.843
965651AG1-433 GEN
Solar/Wind Harmer
1.936
965031AG1-367 GEN
Solar/Wind Harmer
6.586
970291AG2-192 GEN
Solar/Wind Harmer
0.853
247521TR3_G114
Solar/Wind Harmer
0.237
270246TR4_N_V150
Solar/Wind Harmer
0.042
965421AG1-410 GEN
Solar/Wind Harmer
19.465
24728605AND G2
Adder
3.565
24695305TIMB G C
Solar/Wind Harmer
0.002
270055AF2-134 C O1
Solar/Wind Harmer
0.005
24639705ELKHART HY
Adder
0.142
270449AD2-020 GEN
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0.003
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.584
276776AD2-060 GEN
Solar/Wind Harmer
0.666
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
276901AD2-066 C O1
Solar/Wind Harmer
0.006
23751101LEADS_P59
Solar/Wind Helper
1.597
316095T157 G97
Solar/Wind Helper
1.323
238185AF2-356 C
Solar/Wind Helper
2.474
237030AB1-096 C
Solar/Wind Helper
0.061
24318905MLG2
50/50
4.855
270471AD2-092_GEN
Solar/Wind Harmer
0.005
24685805CER G1
Adder
8.364
24685905CER G2
Adder
8.364
24723005RIVRG1
Adder
18.885
24723105RIVRG2
Adder
18.885
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
253370AE2-315 SEC1
Adder
1.959
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
25322209TAIT E
Adder
9.53
25322209TAIT E
Adder
9.316
971655AH1-328 GEN
Solar/Wind Harmer
2.415
252519AF1-045_GEN
Solar/Wind Harmer
5.902
252516AE2-318_GEN
Solar/Wind Harmer
5.235
276820AF1-078_GEN
Solar/Wind Harmer
0.002
247621Y3-024
Adder
0.228
971613AH1-306 GEN
Solar/Wind Harmer
3.153
965681AG1-436 GEN
Solar/Wind Harmer
8.059
270444AC2-157 GEN1
Solar/Wind Harmer
0.003
971587AH1-292 GEN
Solar/Wind Harmer
4.687
971125AH1-004 GEN
Solar/Wind Harmer
2.546
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
238120AE2-309 GEN
Solar/Wind Helper
0.483
238169AE2-226 GEN1
Solar/Wind Helper
0.6
238170AE2-226 GEN2
Solar/Wind Helper
0.6
23777801MSM_W1-116
Solar/Wind Helper
0.098
237025AB1-124 C
Solar/Wind Helper
0.142
270239V3-007_GEN1
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
2.859
945371AF1-202 GEN
Solar/Wind Harmer
0.001
270005AE1-210 C O1
Solar/Wind Harmer
1.427
970825AG2-519 GEN
Solar/Wind Harmer
2.336
270032AE2-172
Solar/Wind Harmer
4.379
965011AG1-365 GEN
Solar/Wind Harmer
6.533
246936BC-WTG1
Solar/Wind Harmer
0.263
270489AE1-102 GEN1
Solar/Wind Harmer
0.843
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.087
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
24387305FR-4G C
Solar/Wind Harmer
0.002
945111AF1-176 GEN
Solar/Wind Harmer
11.453
270505AE1-170 C O1
Solar/Wind Harmer
6.739
274773LINCOLN ;4U
Adder
7.74
274774LINCOLN ;5U
Adder
7.74
274751CRETE EC ;1U
Adder
7.553
274723RIVER EC ;12
Adder
16.418
274801UNIV PARK;4U
Adder
5.327
971997AH1-543 GEN
Solar/Wind Harmer
3.315
23751201ROTHROCK
Solar/Wind Helper
0.849
23583801GRNGAP
Solar/Wind Helper
4.948
238149AF1-291A_GEN
Solar/Wind Helper
0.122
237061AD1-155 GEN
Solar/Wind Helper
0.046
238221AF1-254 C O1
Solar/Wind Helper
0.235
274729ELWOOD EC;1P
Adder
14.987
276805AD2-038 GEN
Solar/Wind Harmer
0.002
237048AF1-022 C
Solar/Wind Helper
0.17
270459AD2-067 GEN
Solar/Wind Harmer
0
970879AG2-548 GEN
Solar/Wind Harmer
6.448
940611AE2-048 GEN
Solar/Wind Harmer
17.483
941391AE2-136 GEN
Solar/Wind Harmer
9.848
270156DARBY CT1
Adder
9.085
270157DARBY CT2
Adder
9.063
270367AC2-061_GEN
Solar/Wind Harmer
0.005
25196408WSDLE3
Adder
8.545
25196308WSDLE2
Adder
8.471
25196208WSDLE1
Adder
8.45
25196708WSDLE6
Adder
8.428
25196108MFTGT2
Adder
1.467
25196108MFTGT2
Adder
1.362
971673AH1-337 GEN
Solar/Wind Harmer
4.312
270543AE2-219 C
Solar/Wind Harmer
0.004
270240V3-007_GEN2
Solar/Wind Harmer
0.002
24729505KEY G4
Adder
6.141
270071AF1-092 GEN
Solar/Wind Harmer
12.598
270594AE1-207 GEN
Solar/Wind Harmer
7.357
270435AC2-044 GEN
Solar/Wind Harmer
0.821
24691005MDL-2G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
247607V1-011 GEN
Solar/Wind Harmer
0.001
971771AH1-392 GEN
Solar/Wind Harmer
6.442
971769AH1-391 GEN
Solar/Wind Harmer
7.189
274728ELWOOD EC;5P
Adder
14.987
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
238126S14_GEN_1
Solar/Wind Helper
0.764
237085AD2-009_GEN
Solar/Wind Helper
1.425
316411AF1-147_GEN1
Solar/Wind Helper
0.754
316415AF1-147_GEN2
Solar/Wind Helper
0.754
944201AF1-088_MTX
Adder
106.522
957141AF2-008_MTX
Adder
53.261
NYPJM->LTFIMP_NY
CLTF
4.491
LGEELTFEXP_LGEE->PJM
CLTF
6.272
WECLTFEXP_WEC->PJM
CLTF
3.434
AG2-052LTFEXP_AG2-052->PJM
LTF
0.214
AH1-155LTFEXP_AH1-155->PJM
LTF
0.321
CBM West 1LTFEXP_CBM-W1->PJM
CBM
126.393
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.84
MECLTFEXP_MEC->PJM
CLTF
14.465
SIGELTFEXP_SIGE->PJM
CLTF
0.467
LAGNLTFEXP_LAGN->PJM
CLTF
14.169
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.052
TVALTFEXP_TVA->PJM
CLTF
7.036
CPLELTFEXP_CPLE->PJM
CLTF
1.288
CBM West 2LTFEXP_CBM-W2->PJM
CBM
105.476

Details for 01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line l/o AP_P1-3_MP-765-502T_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-502T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:139.36 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5284.61
MW Contribution:0.92
Bus #Bus NameTypeMW Contribution
23559001PLEAS1
50/50
11.213
23562401OGROV2
50/50
2.411
270291AC1-194 GEN
Solar/Wind Harmer
5.533
961921AG1-034 GEN
Solar/Wind Harmer
6.218
270273AD2-016 GEN
Solar/Wind Harmer
0.721
24686205CER G4
Adder
8.21
942051AE2-217 GEN
Solar/Wind Harmer
12.316
253333AC1-068 GEN
Solar/Wind Harmer
0.011
253415AE1-040 GEN
Solar/Wind Harmer
0.003
970605AG2-385 GEN
Solar/Wind Harmer
4.136
253406AD2-031_GEN
Solar/Wind Harmer
0.499
270391AF1-285 GEN3
Solar/Wind Harmer
0.44
25196608WSDLE5
Adder
8.083
970519AG2-331 GEN
Solar/Wind Harmer
16.815
970699AG2-449 GEN
Solar/Wind Harmer
1.617
958171AF2-111 GEN
Solar/Wind Harmer
16.157
270437AC2-090 C
Solar/Wind Harmer
0.003
944531AF1-118 GEN
Solar/Wind Harmer
28.735
958821AF2-173 GEN
Solar/Wind Harmer
8.959
970513AG2-328 GEN
Solar/Wind Harmer
2.761
970517AG2-330 GEN
Solar/Wind Harmer
16.566
270247TR4_N_V136
Solar/Wind Harmer
0.041
24728705AND G3
Adder
7.25
970349AG2-230 GEN
Solar/Wind Harmer
9.454
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.281
970031AG2-029 GEN
Solar/Wind Harmer
4.079
274752CRETE EC ;2U
Adder
7.332
970193AG2-126 GEN
Solar/Wind Harmer
9.3
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
20.212
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
270404AC1-167 GEN
Solar/Wind Harmer
0.003
23750701CROSSCHOOL
Solar/Wind Helper
1.155
235062AE1-101 C1
Solar/Wind Helper
1.38
238127S14_GEN_2
Solar/Wind Helper
0.641
964601AG1-323 GEN
Solar/Wind Harmer
2.647
964601AG1-323 GEN
Solar/Wind Harmer
1.765
270224U2-072_GEN2
Solar/Wind Harmer
0.001
938701AE1-092 GEN
Solar/Wind Harmer
10.591
25194408D.CRK1
Adder
7.132
24728905RICHG2
Adder
3.489
970883AG2-550 GEN
Solar/Wind Harmer
6.429
926881AC1-175 GEN
Solar/Wind Harmer
0.001
960971AF2-388 GEN
Solar/Wind Harmer
3.759
270599AE1-208 GEN
Solar/Wind Harmer
5.854
970627AG2-408 GEN
Solar/Wind Harmer
1.9
972043AH1-570 GEN
Solar/Wind Harmer
1.633
966841AG1-555 GEN
Solar/Wind Harmer
0.709
270216AD2-079_GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
12.428
961051AF2-396 GEN
Solar/Wind Harmer
8.285
945391AF1-204 GEN
Solar/Wind Harmer
6.587
274887GEN-1.85
Solar/Wind Harmer
0.163
958481AF2-142 GEN
Solar/Wind Harmer
9.231
274862TOP CROP ;2U
Solar/Wind Harmer
0.833
274879MINONK ;1U
Solar/Wind Harmer
0.259
23777901MDS_W4-102
Solar/Wind Helper
0.146
237002AB1-128_GEN
Solar/Wind Helper
0.369
971073AG2-665 GEN
Solar/Wind Harmer
6.304
942861AE2-305 GEN
Solar/Wind Harmer
5.322
270518AE2-148 GEN
Solar/Wind Harmer
0.589
972159AH1-661 GEN
Adder
0.952
25326109MON D
Adder
1.252
25183208HLCRTG
Solar/Wind Harmer
0.01
252509AD1-136 GEN
Solar/Wind Harmer
0.033
25194508D.CRK3
Adder
1.333
970329AG2-216 GEN
Solar/Wind Harmer
2.833
24728805RICHG1
Adder
3.489
970885AG2-551 GEN
Solar/Wind Harmer
2.143
270383AD1-128 GEN
Solar/Wind Harmer
0.004
24379505HDWTR1G C
Solar/Wind Harmer
0.002
944541AF1-119 GEN
Solar/Wind Harmer
0.429
270201AC2-176 GEN
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
0.48
960441AF2-335 GEN
Solar/Wind Harmer
6.391
270031AE2-169
Solar/Wind Harmer
3.512
339221AD2-048_GEN
Solar/Wind Harmer
0.004
945421AF1-207 GEN
Solar/Wind Harmer
0.001
971199AH1-059 GEN
Solar/Wind Harmer
2.513
972045AH1-571 GEN
Solar/Wind Harmer
1.308
944971AF1-162 GEN
Solar/Wind Harmer
6.265
965791AG1-447 GEN
Solar/Wind Harmer
5.734
247620Y3-023
Adder
0.412
270526AF1-158 GEN
Solar/Wind Harmer
0.008
24441505OLIV SLR
Solar/Wind Harmer
0
276843GEN-1.7
Solar/Wind Harmer
0.2
958011AF2-095 GEN
Solar/Wind Harmer
8.915
241960AC2-195 GEN
Solar/Wind Harmer
0.005
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
971573AH1-285 GEN
Solar/Wind Harmer
1.146
958491AF2-143 GEN
Solar/Wind Harmer
9.212
237034AC2-136 C
Solar/Wind Helper
0.189
235063AE1-101 C2
Solar/Wind Helper
1.38
237001AB1-127_GEN
Solar/Wind Helper
0.368
24318805MLG1
50/50
6.319
972173AH1-669 GEN
Solar/Wind Harmer
3.478
24686405CER G5
Adder
8.177
253338AC1-165 GEN
Solar/Wind Harmer
0.003
970191AG2-125 GEN
Solar/Wind Harmer
1.697
270222AC2-111 GEN
Solar/Wind Harmer
3.293
270356AE2-297 GEN
Solar/Wind Harmer
0.009
270004AE1-209 GEN
Solar/Wind Harmer
1.387
971617AH1-308 GEN
Solar/Wind Harmer
5.319
959331AF2-224 GEN
Solar/Wind Harmer
4.433
270191TR4_S_V150
Solar/Wind Harmer
0.001
270491AE1-102 GEN2
Solar/Wind Harmer
0.817
964401AG1-302 GEN
Solar/Wind Harmer
0.001
270053AF1-130 C
Solar/Wind Harmer
1.414
24642205MAYFLWER
Adder
0.568
274753CRETE EC ;3U
Adder
7.332
270258AD1-119 GEN
Solar/Wind Harmer
0.002
238148AE2-230_GEN2
Solar/Wind Helper
0.417
237038AE2-054 C
Solar/Wind Helper
0.226
23779801AA1-109
Solar/Wind Helper
0.162
238118U2-030_1
Solar/Wind Helper
0.26
972269AH1-719 GEN
Adder
2.268
970077AG2-063 GEN
Solar/Wind Harmer
3.909
962581AG1-107 GEN
Solar/Wind Harmer
0.001
253394AE2-221_GEN
Solar/Wind Harmer
0.008
253398AE2-221_GEN2
Solar/Wind Harmer
0.008
270186AC1-089 GEN
Solar/Wind Harmer
0.004
253378AE2-206_GEN
Solar/Wind Harmer
0.003
25326509SID D
Adder
1.231
970239AG2-162 GEN
Solar/Wind Harmer
1.617
270209AC1-174_GEN
Solar/Wind Harmer
0.001
970825AG2-519 GEN
Solar/Wind Harmer
7.086
942221AE2-234 GEN
Solar/Wind Harmer
0.032
970321AG2-212 GEN
Solar/Wind Harmer
2.761
970611AG2-400 GEN
Solar/Wind Harmer
6.333
970235AG2-159 GEN
Solar/Wind Harmer
3.847
970235AG2-159 GEN
Solar/Wind Harmer
2.207
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
246938BC-WTG3
Solar/Wind Harmer
0.228
246937BC-WTG2
Solar/Wind Harmer
0.255
270007AE1-245 C
Solar/Wind Harmer
0.002
970241AG2-163 GEN
Solar/Wind Harmer
3.641
957891AF2-083 GEN
Solar/Wind Harmer
0.001
274770LINCOLN ;1U
Adder
7.514
274771LINCOLN ;2U
Adder
7.514
970107AG2-081 GEN
Solar/Wind Harmer
1.862
960161AF2-307 GEN
Solar/Wind Harmer
4.096
274888KELLY CRK;1U
Solar/Wind Harmer
0.364
970623AG2-406 GEN
Solar/Wind Harmer
1.132
238175AF1-290_GEN
Solar/Wind Helper
0.126
235020AA1-095 C
Solar/Wind Helper
0.044
962691AG1-118 GEN
Solar/Wind Harmer
3.447
23684201S70BUS2
50/50
0.319
270512AE1-227 GEN2
Solar/Wind Harmer
1.907
971191AH1-055 GEN
Solar/Wind Harmer
18.237
252510AF1-249 C
Solar/Wind Harmer
0.051
270485AE1-090_GEN
Solar/Wind Harmer
0.001
25196008MFTGT1
Adder
1.255
970243AG2-164 GEN
Solar/Wind Harmer
3.783
972167AH1-666 GEN
Solar/Wind Harmer
5.174
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
9.603
270043AE2-236 GEN
Solar/Wind Harmer
4.072
965021AG1-366 GEN
Solar/Wind Harmer
2.111
945111AF1-176 GEN
Solar/Wind Harmer
5.045
274772LINCOLN ;3U
Adder
7.514
274724RIVER EC ;11
Adder
15.751
970941AG2-585 GEN
Solar/Wind Harmer
7.739
276897AD1-100 C
Solar/Wind Harmer
0.008
276893AG1-478 C
Solar/Wind Harmer
0.245
24441205WTRV SLR C
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0.002
23684101S70BUS1
50/50
0.313
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
25196808ZIMRHP
Adder
71.347
25196008MFTGT1
Adder
1.296
970333AG2-219 GEN
Solar/Wind Harmer
4.624
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
2.776
945371AF1-202 GEN
Solar/Wind Harmer
0.001
270005AE1-210 C O1
Solar/Wind Harmer
1.387
970825AG2-519 GEN
Solar/Wind Harmer
2.27
270032AE2-172
Solar/Wind Harmer
4.254
965011AG1-365 GEN
Solar/Wind Harmer
6.333
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
7.853
246936BC-WTG1
Solar/Wind Harmer
0.255
270489AE1-102 GEN1
Solar/Wind Harmer
0.817
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
23559101PLEAS2
50/50
11.213
23562301OGROV1
50/50
2.427
970149AG2-104 GEN
Solar/Wind Harmer
31.855
270510AE1-227 GEN1
Solar/Wind Harmer
1.907
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
927014AC1-188 GEN
Solar/Wind Harmer
0.004
270263AC1-001 GEN
Solar/Wind Harmer
0.698
270159DARBY CT4
Adder
8.691
253325AC1-069 GEN
Solar/Wind Harmer
0.011
970593AG2-378 GEN
Solar/Wind Harmer
1.53
270223U2-072_GEN1
Solar/Wind Harmer
0.001
970773AG2-487 GEN
Solar/Wind Harmer
1.131
970091AG2-072 GEN
Adder
70.193
24791305MDL-5G
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.162
970373AG2-245 GEN
Solar/Wind Harmer
13.169
963741AG1-226 GEN
Solar/Wind Harmer
14.772
943021AE2-325 GEN
Solar/Wind Harmer
3.241
941551AE2-152 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.745
238108AE1-109 GEN1
Solar/Wind Helper
0.088
235531U2-073 GEN
Solar/Wind Helper
2.523
24387305FR-4G C
Solar/Wind Harmer
0.002
945111AF1-176 GEN
Solar/Wind Harmer
11.105
270505AE1-170 C O1
Solar/Wind Harmer
6.535
274773LINCOLN ;4U
Adder
7.514
274774LINCOLN ;5U
Adder
7.514
274751CRETE EC ;1U
Adder
7.332
274723RIVER EC ;12
Adder
15.938
971997AH1-543 GEN
Solar/Wind Harmer
3.22
23583801GRNGAP
Solar/Wind Helper
4.858
238149AF1-291A_GEN
Solar/Wind Helper
0.119
237061AD1-155 GEN
Solar/Wind Helper
0.045
238221AF1-254 C O1
Solar/Wind Helper
0.228
970879AG2-548 GEN
Solar/Wind Harmer
6.304
940611AE2-048 GEN
Solar/Wind Harmer
17.215
941391AE2-136 GEN
Solar/Wind Harmer
9.698
270459AD2-067 GEN
Solar/Wind Harmer
0
270156DARBY CT1
Adder
8.832
270157DARBY CT2
Adder
8.81
270367AC2-061_GEN
Solar/Wind Harmer
0.005
25196408WSDLE3
Adder
8.32
25196308WSDLE2
Adder
8.248
25196208WSDLE1
Adder
8.227
25196708WSDLE6
Adder
8.207
25196108MFTGT2
Adder
1.429
25196108MFTGT2
Adder
1.327
971673AH1-337 GEN
Solar/Wind Harmer
4.191
270543AE2-219 C
Solar/Wind Harmer
0.004
270240V3-007_GEN2
Solar/Wind Harmer
0.002
24729505KEY G4
Adder
5.961
270594AE1-207 GEN
Solar/Wind Harmer
7.147
270071AF1-092 GEN
Solar/Wind Harmer
12.224
24691005MDL-2G C
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
0.796
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
971771AH1-392 GEN
Solar/Wind Harmer
6.248
971769AH1-391 GEN
Solar/Wind Harmer
6.974
247607V1-011 GEN
Solar/Wind Harmer
0.001
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
237085AD2-009_GEN
Solar/Wind Helper
1.367
238126S14_GEN_1
Solar/Wind Helper
0.641
962761AG1-125 GEN
Solar/Wind Harmer
29.494
24686505CER G6
Adder
8.242
25326309TAIT D
Adder
1.041
252507AC2-088 GEN
Solar/Wind Harmer
0.3
270462AD2-086
Solar/Wind Harmer
0.014
247536S-71 GEN
Solar/Wind Harmer
0.258
970245AG2-165 GEN
Solar/Wind Harmer
2.761
276903AD2-071 C
Solar/Wind Harmer
7.113
339216AC1-074 GEN
Solar/Wind Harmer
0.172
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270063AE2-323 C
Solar/Wind Harmer
0.005
24385905FR-11G C
Solar/Wind Harmer
0.001
274754CRETE EC ;4U
Adder
7.332
939401AE1-172 GEN
Solar/Wind Harmer
4.613
944231AF1-091 GEN
Solar/Wind Harmer
1.635
238147AE2-230_GEN1
Solar/Wind Helper
0.415
235067AD1-061 GEN
Solar/Wind Helper
0.412
238117U2-030
Solar/Wind Helper
0.26
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Harmer
0.006
270520AE2-214 GEN
Solar/Wind Harmer
0.011
270158DARBY CT3
Adder
8.67
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
971985AH1-537 GEN
Solar/Wind Harmer
2.037
253349AC2-067 GEN
Solar/Wind Harmer
2.077
270317AD1-130_GEN
Solar/Wind Harmer
0.009
972165AH1-665 GEN
Solar/Wind Harmer
5.756
971029AG2-637 GEN
Solar/Wind Harmer
9.664
945581AF1-223 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0.001
965051AG1-369 GEN
Solar/Wind Harmer
3.147
971347AH1-153 GEN
Solar/Wind Harmer
9.454
971611AH1-305 GEN
Solar/Wind Harmer
3.74
24697605MDL-3G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0.001
971619AH1-309 GEN
Solar/Wind Harmer
2.801
274775LINCOLN ;6U
Adder
7.514
274777LINCOLN ;8U
Adder
7.514
960591AF2-350 GEN
Solar/Wind Harmer
6.191
270399AC1-101 GEN
Solar/Wind Harmer
1.957
970833AG2-524 GEN
Solar/Wind Harmer
6.792
970833AG2-524 GEN
Solar/Wind Harmer
4.528
276868AE1-113 GEN
Solar/Wind Harmer
1.231
238208AF1-136 C
Solar/Wind Helper
0.18
24721905FLATG4
Adder
23.442
970153AG2-106 GEN
Solar/Wind Harmer
18.834
241955AC1-078 GEN
Solar/Wind Harmer
0.006
241974AD2-163_GEN2
Solar/Wind Harmer
0.005
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
8.654
253370AE2-315 SEC1
Adder
1.906
253371AE2-315 SEC2
Adder
1.803
25194608D.CRK4
Adder
1.55
946031AF1-268 GEN
Solar/Wind Harmer
6.09
970289AG2-191 GEN
Solar/Wind Harmer
0.701
970291AG2-192 GEN
Solar/Wind Harmer
0.638
247642Z2-115 C
Solar/Wind Harmer
0.003
24728505AND G1
Adder
3.466
24755605MDL-5G
Solar/Wind Harmer
0.001
270535AF1-215 GEN1
Solar/Wind Harmer
0.008
247643Z2-116 C
Solar/Wind Harmer
0
276806AD2-047 C O1
Solar/Wind Harmer
3.508
943121AE2-341 GEN
Solar/Wind Harmer
10.327
943591AF1-030 GEN
Solar/Wind Harmer
6.867
316097T157 G90
Solar/Wind Helper
1.299
964991AG1-363 GEN
Solar/Wind Helper
4.135
237080AD1-060 GEN
Solar/Wind Helper
0.284
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
961821AG1-024 GEN
Solar/Wind Harmer
4.145
270432AC2-029 GEN
Solar/Wind Harmer
3.085
270269AC2-059
Solar/Wind Harmer
0.004
945631AF1-228 GEN
Solar/Wind Harmer
0
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270340AC2-060 GEN
Solar/Wind Harmer
0.008
24477305BRIDGE
Adder
0.338
241972AD1-140 GEN
Solar/Wind Harmer
0.734
270578AF1-285 GEN2
Solar/Wind Harmer
0.44
253400AC2-068 GEN
Solar/Wind Harmer
0.835
25196508WSDLE4
Adder
8
972163AH1-664 GEN
Solar/Wind Harmer
7.187
965101AG1-375 GEN
Solar/Wind Harmer
6.406
970115AG2-085 GEN
Solar/Wind Harmer
2.556
971609AH1-304 GEN
Solar/Wind Harmer
1.043
24699105WLD G1 C
Solar/Wind Harmer
0.001
965041AG1-368 GEN
Solar/Wind Harmer
6.297
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0
24697905MDL-4G C
Solar/Wind Harmer
0.001
24386205FR-12G C
Solar/Wind Harmer
0.001
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
963841AG1-237 GEN
Solar/Wind Harmer
2.71
274776LINCOLN ;7U
Adder
7.514
274814UNIV PK N;0U
Adder
4.489
274807UNIV PK N;3U
Adder
4.479
274805UNIV PK N;1U
Adder
4.459
270400AC1-102 GEN
Solar/Wind Harmer
1.957
276882AE2-255 GEN
Solar/Wind Harmer
0.717
238152AF2-075_GEN
Solar/Wind Helper
0.593
23546401DTGZ2-030
Solar/Wind Helper
0.075
24721705FLATG2
Adder
23.442
970155AG2-107 GEN
Solar/Wind Harmer
18.834
970947AG2-589 GEN
Solar/Wind Harmer
0.239
270349AD2-093_GEN
Solar/Wind Harmer
0.005
24686105CER G3
Adder
8.253
24723205RIVRG3
Adder
18.473
253343AC1-166 GEN
Solar/Wind Harmer
0.003
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.657
253370AE2-315 SEC1
Adder
1.906
253371AE2-315 SEC2
Adder
1.803
960071AF2-298 GEN
Solar/Wind Harmer
3.297
25194608D.CRK4
Adder
1.55
945681AF1-233 GEN
Solar/Wind Harmer
12.186
970613AG2-401 GEN
Solar/Wind Harmer
4.707
965651AG1-433 GEN
Solar/Wind Harmer
1.879
971995AH1-542 GEN
Solar/Wind Harmer
2.347
965031AG1-367 GEN
Solar/Wind Harmer
6.4
970291AG2-192 GEN
Solar/Wind Harmer
0.829
247521TR3_G114
Solar/Wind Harmer
0.23
270246TR4_N_V150
Solar/Wind Harmer
0.041
24728605AND G2
Adder
3.466
965421AG1-410 GEN
Solar/Wind Harmer
18.858
24695305TIMB G C
Solar/Wind Harmer
0.002
270055AF2-134 C O1
Solar/Wind Harmer
0.005
24639705ELKHART HY
Adder
0.137
270445AC2-157 GEN2
Solar/Wind Harmer
0.003
270449AD2-020 GEN
Solar/Wind Harmer
0
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.45
276776AD2-060 GEN
Solar/Wind Harmer
0.646
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
276901AD2-066 C O1
Solar/Wind Harmer
0.006
316095T157 G97
Solar/Wind Helper
1.299
238185AF2-356 C
Solar/Wind Helper
1.996
962771AG1-126 GEN
Solar/Wind Harmer
29.494
972203AH1-686 GEN
Adder
2.298
970689AG2-444 GEN
Solar/Wind Harmer
14.206
270284AF1-227 GEN1
Solar/Wind Harmer
0.009
253383AE2-342_GEN
Solar/Wind Harmer
0.002
241973AD2-163_GEN1
Solar/Wind Harmer
0.005
943861AF1-054 GEN
Solar/Wind Harmer
2.627
943851AF1-053 GEN
Solar/Wind Harmer
1.82
253372AE2-315 SEC3
Adder
1.803
253372AE2-315 SEC3
Adder
1.803
25306009OHH W.
Adder
2.735
252524AE2-267 GEN
Solar/Wind Harmer
0.002
270302AB2-170 GEN
Solar/Wind Harmer
0.004
971653AH1-327 GEN
Solar/Wind Harmer
0.917
270024AE2-089 GEN
Solar/Wind Harmer
0.007
970289AG2-191 GEN
Solar/Wind Harmer
1.211
963791AG1-232 GEN
Solar/Wind Harmer
8.573
957201AF2-014 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.008
274811UNIV PK N;7U
Adder
0.697
970179AG2-119 GEN
Solar/Wind Harmer
5.506
970169AG2-114 GEN
Solar/Wind Harmer
6.145
238109AE1-109 GEN2
Solar/Wind Helper
0.088
238110AE1-109 GEN3
Solar/Wind Helper
0.088
970935AG2-582 GEN
50/50
1217.062
24318905MLG2
50/50
4.656
270471AD2-092_GEN
Solar/Wind Harmer
0.005
24685805CER G1
Adder
8.199
24685905CER G2
Adder
8.199
24723005RIVRG1
Adder
18.473
24723105RIVRG2
Adder
18.473
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
253370AE2-315 SEC1
Adder
1.906
25322209TAIT E
Adder
9.269
25322209TAIT E
Adder
9.061
252519AF1-045_GEN
Solar/Wind Harmer
5.748
252516AE2-318_GEN
Solar/Wind Harmer
5.098
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
971655AH1-328 GEN
Solar/Wind Harmer
2.34
276820AF1-078_GEN
Solar/Wind Harmer
0.002
247621Y3-024
Adder
0.222
971613AH1-306 GEN
Solar/Wind Harmer
3.063
965681AG1-436 GEN
Solar/Wind Harmer
7.82
270444AC2-157 GEN1
Solar/Wind Harmer
0.003
971587AH1-292 GEN
Solar/Wind Harmer
4.56
971125AH1-004 GEN
Solar/Wind Harmer
2.483
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
238169AE2-226 GEN1
Solar/Wind Helper
0.582
238170AE2-226 GEN2
Solar/Wind Helper
0.582
238120AE2-309 GEN
Solar/Wind Helper
0.406
23777801MSM_W1-116
Solar/Wind Helper
0.096
944201AF1-088_MTX
Adder
103.64
957141AF2-008_MTX
Adder
51.82
NYPJM->LTFIMP_NY
CLTF
4.417
LGEELTFEXP_LGEE->PJM
CLTF
6.111
WECLTFEXP_WEC->PJM
CLTF
3.336
AG2-052LTFEXP_AG2-052->PJM
LTF
0.208
AH1-155LTFEXP_AH1-155->PJM
LTF
0.312
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.614
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.188
MECLTFEXP_MEC->PJM
CLTF
14.066
SIGELTFEXP_SIGE->PJM
CLTF
0.455
LAGNLTFEXP_LAGN->PJM
CLTF
13.832
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.925
TVALTFEXP_TVA->PJM
CLTF
6.876
CPLELTFEXP_CPLE->PJM
CLTF
1.286
CBM West 2LTFEXP_CBM-W2->PJM
CBM
102.798

Details for 01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-028_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-028_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:139.32 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5282.91
MW Contribution:0.92
Bus #Bus NameTypeMW Contribution
23559001PLEAS1
50/50
11.213
23562401OGROV2
50/50
2.411
270291AC1-194 GEN
Solar/Wind Harmer
5.533
961921AG1-034 GEN
Solar/Wind Harmer
6.218
270273AD2-016 GEN
Solar/Wind Harmer
0.721
24686205CER G4
Adder
8.21
942051AE2-217 GEN
Solar/Wind Harmer
12.316
253333AC1-068 GEN
Solar/Wind Harmer
0.011
253415AE1-040 GEN
Solar/Wind Harmer
0.003
970605AG2-385 GEN
Solar/Wind Harmer
4.136
253406AD2-031_GEN
Solar/Wind Harmer
0.499
270391AF1-285 GEN3
Solar/Wind Harmer
0.44
25196608WSDLE5
Adder
8.083
970519AG2-331 GEN
Solar/Wind Harmer
16.815
970699AG2-449 GEN
Solar/Wind Harmer
1.617
958171AF2-111 GEN
Solar/Wind Harmer
16.157
270437AC2-090 C
Solar/Wind Harmer
0.003
944531AF1-118 GEN
Solar/Wind Harmer
28.735
958821AF2-173 GEN
Solar/Wind Harmer
8.959
970513AG2-328 GEN
Solar/Wind Harmer
2.761
970517AG2-330 GEN
Solar/Wind Harmer
16.566
270247TR4_N_V136
Solar/Wind Harmer
0.041
24728705AND G3
Adder
7.25
970349AG2-230 GEN
Solar/Wind Harmer
9.454
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.281
970031AG2-029 GEN
Solar/Wind Harmer
4.079
274752CRETE EC ;2U
Adder
7.332
970193AG2-126 GEN
Solar/Wind Harmer
9.3
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
20.212
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
270404AC1-167 GEN
Solar/Wind Harmer
0.003
23750701CROSSCHOOL
Solar/Wind Helper
1.155
235062AE1-101 C1
Solar/Wind Helper
1.38
238127S14_GEN_2
Solar/Wind Helper
0.641
964601AG1-323 GEN
Solar/Wind Harmer
2.647
964601AG1-323 GEN
Solar/Wind Harmer
1.765
270224U2-072_GEN2
Solar/Wind Harmer
0.001
938701AE1-092 GEN
Solar/Wind Harmer
10.591
25194408D.CRK1
Adder
7.132
24728905RICHG2
Adder
3.489
970883AG2-550 GEN
Solar/Wind Harmer
6.429
926881AC1-175 GEN
Solar/Wind Harmer
0.001
960971AF2-388 GEN
Solar/Wind Harmer
3.759
270599AE1-208 GEN
Solar/Wind Harmer
5.854
970627AG2-408 GEN
Solar/Wind Harmer
1.9
972043AH1-570 GEN
Solar/Wind Harmer
1.633
966841AG1-555 GEN
Solar/Wind Harmer
0.709
270216AD2-079_GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
12.428
961051AF2-396 GEN
Solar/Wind Harmer
8.285
945391AF1-204 GEN
Solar/Wind Harmer
6.587
274887GEN-1.85
Solar/Wind Harmer
0.163
958481AF2-142 GEN
Solar/Wind Harmer
9.231
274862TOP CROP ;2U
Solar/Wind Harmer
0.833
274879MINONK ;1U
Solar/Wind Harmer
0.259
23777901MDS_W4-102
Solar/Wind Helper
0.146
237002AB1-128_GEN
Solar/Wind Helper
0.369
971073AG2-665 GEN
Solar/Wind Harmer
6.304
942861AE2-305 GEN
Solar/Wind Harmer
5.322
270518AE2-148 GEN
Solar/Wind Harmer
0.589
972159AH1-661 GEN
Adder
0.952
25326109MON D
Adder
1.252
25183208HLCRTG
Solar/Wind Harmer
0.01
252509AD1-136 GEN
Solar/Wind Harmer
0.033
25194508D.CRK3
Adder
1.333
970329AG2-216 GEN
Solar/Wind Harmer
2.833
24728805RICHG1
Adder
3.489
970885AG2-551 GEN
Solar/Wind Harmer
2.143
270383AD1-128 GEN
Solar/Wind Harmer
0.004
24379505HDWTR1G C
Solar/Wind Harmer
0.002
944541AF1-119 GEN
Solar/Wind Harmer
0.429
270201AC2-176 GEN
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
0.48
960441AF2-335 GEN
Solar/Wind Harmer
6.391
270031AE2-169
Solar/Wind Harmer
3.512
339221AD2-048_GEN
Solar/Wind Harmer
0.004
945421AF1-207 GEN
Solar/Wind Harmer
0.001
971199AH1-059 GEN
Solar/Wind Harmer
2.513
972045AH1-571 GEN
Solar/Wind Harmer
1.308
944971AF1-162 GEN
Solar/Wind Harmer
6.265
965791AG1-447 GEN
Solar/Wind Harmer
5.734
247620Y3-023
Adder
0.412
270526AF1-158 GEN
Solar/Wind Harmer
0.008
24441505OLIV SLR
Solar/Wind Harmer
0
276843GEN-1.7
Solar/Wind Harmer
0.2
958011AF2-095 GEN
Solar/Wind Harmer
8.915
241960AC2-195 GEN
Solar/Wind Harmer
0.005
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
971573AH1-285 GEN
Solar/Wind Harmer
1.146
958491AF2-143 GEN
Solar/Wind Harmer
9.212
237034AC2-136 C
Solar/Wind Helper
0.189
235063AE1-101 C2
Solar/Wind Helper
1.38
237001AB1-127_GEN
Solar/Wind Helper
0.368
24318805MLG1
50/50
6.319
972173AH1-669 GEN
Solar/Wind Harmer
3.478
24686405CER G5
Adder
8.177
253338AC1-165 GEN
Solar/Wind Harmer
0.003
970191AG2-125 GEN
Solar/Wind Harmer
1.697
270222AC2-111 GEN
Solar/Wind Harmer
3.293
270356AE2-297 GEN
Solar/Wind Harmer
0.009
270004AE1-209 GEN
Solar/Wind Harmer
1.387
971617AH1-308 GEN
Solar/Wind Harmer
5.319
959331AF2-224 GEN
Solar/Wind Harmer
4.433
270191TR4_S_V150
Solar/Wind Harmer
0.001
270491AE1-102 GEN2
Solar/Wind Harmer
0.817
964401AG1-302 GEN
Solar/Wind Harmer
0.001
270053AF1-130 C
Solar/Wind Harmer
1.414
24642205MAYFLWER
Adder
0.568
274753CRETE EC ;3U
Adder
7.332
270258AD1-119 GEN
Solar/Wind Harmer
0.002
238148AE2-230_GEN2
Solar/Wind Helper
0.417
237038AE2-054 C
Solar/Wind Helper
0.226
23779801AA1-109
Solar/Wind Helper
0.162
238118U2-030_1
Solar/Wind Helper
0.26
972269AH1-719 GEN
Adder
2.268
970077AG2-063 GEN
Solar/Wind Harmer
3.909
962581AG1-107 GEN
Solar/Wind Harmer
0.001
253394AE2-221_GEN
Solar/Wind Harmer
0.008
253398AE2-221_GEN2
Solar/Wind Harmer
0.008
270186AC1-089 GEN
Solar/Wind Harmer
0.004
253378AE2-206_GEN
Solar/Wind Harmer
0.003
25326509SID D
Adder
1.231
970239AG2-162 GEN
Solar/Wind Harmer
1.617
270209AC1-174_GEN
Solar/Wind Harmer
0.001
970825AG2-519 GEN
Solar/Wind Harmer
7.086
942221AE2-234 GEN
Solar/Wind Harmer
0.032
970321AG2-212 GEN
Solar/Wind Harmer
2.761
970611AG2-400 GEN
Solar/Wind Harmer
6.333
970235AG2-159 GEN
Solar/Wind Harmer
3.847
970235AG2-159 GEN
Solar/Wind Harmer
2.207
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
246938BC-WTG3
Solar/Wind Harmer
0.228
246937BC-WTG2
Solar/Wind Harmer
0.255
270007AE1-245 C
Solar/Wind Harmer
0.002
970241AG2-163 GEN
Solar/Wind Harmer
3.641
957891AF2-083 GEN
Solar/Wind Harmer
0.001
274770LINCOLN ;1U
Adder
7.514
274771LINCOLN ;2U
Adder
7.514
970107AG2-081 GEN
Solar/Wind Harmer
1.862
960161AF2-307 GEN
Solar/Wind Harmer
4.096
274888KELLY CRK;1U
Solar/Wind Harmer
0.364
970623AG2-406 GEN
Solar/Wind Harmer
1.132
238175AF1-290_GEN
Solar/Wind Helper
0.126
235020AA1-095 C
Solar/Wind Helper
0.044
962691AG1-118 GEN
Solar/Wind Harmer
3.447
23684201S70BUS2
50/50
0.319
270512AE1-227 GEN2
Solar/Wind Harmer
1.907
971191AH1-055 GEN
Solar/Wind Harmer
18.237
252510AF1-249 C
Solar/Wind Harmer
0.051
270485AE1-090_GEN
Solar/Wind Harmer
0.001
25196008MFTGT1
Adder
1.255
970243AG2-164 GEN
Solar/Wind Harmer
3.783
972167AH1-666 GEN
Solar/Wind Harmer
5.174
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
9.603
270043AE2-236 GEN
Solar/Wind Harmer
4.072
965021AG1-366 GEN
Solar/Wind Harmer
2.111
945111AF1-176 GEN
Solar/Wind Harmer
5.045
274772LINCOLN ;3U
Adder
7.514
274724RIVER EC ;11
Adder
15.751
970941AG2-585 GEN
Solar/Wind Harmer
7.739
276897AD1-100 C
Solar/Wind Harmer
0.008
276893AG1-478 C
Solar/Wind Harmer
0.245
24441205WTRV SLR C
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0.002
23559101PLEAS2
50/50
11.213
23562301OGROV1
50/50
2.427
970149AG2-104 GEN
Solar/Wind Harmer
31.855
270510AE1-227 GEN1
Solar/Wind Harmer
1.907
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
927014AC1-188 GEN
Solar/Wind Harmer
0.004
270263AC1-001 GEN
Solar/Wind Harmer
0.698
270159DARBY CT4
Adder
8.691
253325AC1-069 GEN
Solar/Wind Harmer
0.011
970593AG2-378 GEN
Solar/Wind Harmer
1.53
270223U2-072_GEN1
Solar/Wind Harmer
0.001
970773AG2-487 GEN
Solar/Wind Harmer
1.131
970091AG2-072 GEN
Adder
70.193
23684101S70BUS1
50/50
0.313
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
25196808ZIMRHP
Adder
71.347
25196008MFTGT1
Adder
1.296
970333AG2-219 GEN
Solar/Wind Harmer
4.624
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
2.776
945371AF1-202 GEN
Solar/Wind Harmer
0.001
270005AE1-210 C O1
Solar/Wind Harmer
1.387
970825AG2-519 GEN
Solar/Wind Harmer
2.27
270032AE2-172
Solar/Wind Harmer
4.254
965011AG1-365 GEN
Solar/Wind Harmer
6.333
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
7.853
246936BC-WTG1
Solar/Wind Harmer
0.255
270489AE1-102 GEN1
Solar/Wind Harmer
0.817
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
24387305FR-4G C
Solar/Wind Harmer
0.002
945111AF1-176 GEN
Solar/Wind Harmer
11.105
270505AE1-170 C O1
Solar/Wind Harmer
6.535
274773LINCOLN ;4U
Adder
7.514
274774LINCOLN ;5U
Adder
7.514
274751CRETE EC ;1U
Adder
7.332
274723RIVER EC ;12
Adder
15.938
971997AH1-543 GEN
Solar/Wind Harmer
3.22
23583801GRNGAP
Solar/Wind Helper
4.858
238149AF1-291A_GEN
Solar/Wind Helper
0.119
237061AD1-155 GEN
Solar/Wind Helper
0.045
238221AF1-254 C O1
Solar/Wind Helper
0.228
970879AG2-548 GEN
Solar/Wind Harmer
6.304
940611AE2-048 GEN
Solar/Wind Harmer
17.215
941391AE2-136 GEN
Solar/Wind Harmer
9.698
270459AD2-067 GEN
Solar/Wind Harmer
0
270156DARBY CT1
Adder
8.832
270157DARBY CT2
Adder
8.81
270367AC2-061_GEN
Solar/Wind Harmer
0.005
25196408WSDLE3
Adder
8.32
25196308WSDLE2
Adder
8.248
25196208WSDLE1
Adder
8.227
25196708WSDLE6
Adder
8.207
25196108MFTGT2
Adder
1.429
25196108MFTGT2
Adder
1.327
971673AH1-337 GEN
Solar/Wind Harmer
4.191
270543AE2-219 C
Solar/Wind Harmer
0.004
270240V3-007_GEN2
Solar/Wind Harmer
0.002
24729505KEY G4
Adder
5.961
270594AE1-207 GEN
Solar/Wind Harmer
7.147
270071AF1-092 GEN
Solar/Wind Harmer
12.224
24691005MDL-2G C
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
0.796
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
971771AH1-392 GEN
Solar/Wind Harmer
6.248
971769AH1-391 GEN
Solar/Wind Harmer
6.974
247607V1-011 GEN
Solar/Wind Harmer
0.001
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
237085AD2-009_GEN
Solar/Wind Helper
1.367
238126S14_GEN_1
Solar/Wind Helper
0.641
962761AG1-125 GEN
Solar/Wind Harmer
29.494
24686505CER G6
Adder
8.242
25326309TAIT D
Adder
1.041
252507AC2-088 GEN
Solar/Wind Harmer
0.3
270462AD2-086
Solar/Wind Harmer
0.014
247536S-71 GEN
Solar/Wind Harmer
0.258
970245AG2-165 GEN
Solar/Wind Harmer
2.761
276903AD2-071 C
Solar/Wind Harmer
7.113
339216AC1-074 GEN
Solar/Wind Harmer
0.172
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270063AE2-323 C
Solar/Wind Harmer
0.005
24385905FR-11G C
Solar/Wind Harmer
0.001
274754CRETE EC ;4U
Adder
7.332
939401AE1-172 GEN
Solar/Wind Harmer
4.613
944231AF1-091 GEN
Solar/Wind Harmer
1.635
238147AE2-230_GEN1
Solar/Wind Helper
0.415
235067AD1-061 GEN
Solar/Wind Helper
0.412
238117U2-030
Solar/Wind Helper
0.26
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Harmer
0.006
270520AE2-214 GEN
Solar/Wind Harmer
0.011
270158DARBY CT3
Adder
8.67
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
971985AH1-537 GEN
Solar/Wind Harmer
2.037
253349AC2-067 GEN
Solar/Wind Harmer
2.077
270317AD1-130_GEN
Solar/Wind Harmer
0.009
972165AH1-665 GEN
Solar/Wind Harmer
5.756
971029AG2-637 GEN
Solar/Wind Harmer
9.664
945581AF1-223 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0.001
965051AG1-369 GEN
Solar/Wind Harmer
3.147
971347AH1-153 GEN
Solar/Wind Harmer
9.454
971611AH1-305 GEN
Solar/Wind Harmer
3.74
24697605MDL-3G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0.001
971619AH1-309 GEN
Solar/Wind Harmer
2.801
274775LINCOLN ;6U
Adder
7.514
274777LINCOLN ;8U
Adder
7.514
960591AF2-350 GEN
Solar/Wind Harmer
6.191
270399AC1-101 GEN
Solar/Wind Harmer
1.957
970833AG2-524 GEN
Solar/Wind Harmer
6.792
970833AG2-524 GEN
Solar/Wind Harmer
4.528
276868AE1-113 GEN
Solar/Wind Harmer
1.231
238208AF1-136 C
Solar/Wind Helper
0.18
24721905FLATG4
Adder
23.442
970153AG2-106 GEN
Solar/Wind Harmer
18.834
241955AC1-078 GEN
Solar/Wind Harmer
0.006
241974AD2-163_GEN2
Solar/Wind Harmer
0.005
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
8.654
253370AE2-315 SEC1
Adder
1.906
253371AE2-315 SEC2
Adder
1.803
25194608D.CRK4
Adder
1.55
946031AF1-268 GEN
Solar/Wind Harmer
6.09
970289AG2-191 GEN
Solar/Wind Harmer
0.701
970291AG2-192 GEN
Solar/Wind Harmer
0.638
247642Z2-115 C
Solar/Wind Harmer
0.003
24728505AND G1
Adder
3.466
24755605MDL-5G
Solar/Wind Harmer
0.001
270535AF1-215 GEN1
Solar/Wind Harmer
0.008
247643Z2-116 C
Solar/Wind Harmer
0
276806AD2-047 C O1
Solar/Wind Harmer
3.508
943121AE2-341 GEN
Solar/Wind Harmer
10.327
943591AF1-030 GEN
Solar/Wind Harmer
6.867
316097T157 G90
Solar/Wind Helper
1.299
964991AG1-363 GEN
Solar/Wind Helper
4.135
237080AD1-060 GEN
Solar/Wind Helper
0.284
24791305MDL-5G
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.162
970373AG2-245 GEN
Solar/Wind Harmer
13.169
963741AG1-226 GEN
Solar/Wind Harmer
14.772
943021AE2-325 GEN
Solar/Wind Harmer
3.241
941551AE2-152 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.745
238108AE1-109 GEN1
Solar/Wind Helper
0.088
235531U2-073 GEN
Solar/Wind Helper
2.523
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
961821AG1-024 GEN
Solar/Wind Harmer
4.145
270432AC2-029 GEN
Solar/Wind Harmer
3.085
270269AC2-059
Solar/Wind Harmer
0.004
945631AF1-228 GEN
Solar/Wind Harmer
0
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270340AC2-060 GEN
Solar/Wind Harmer
0.008
24477305BRIDGE
Adder
0.338
241972AD1-140 GEN
Solar/Wind Harmer
0.734
270578AF1-285 GEN2
Solar/Wind Harmer
0.44
253400AC2-068 GEN
Solar/Wind Harmer
0.835
25196508WSDLE4
Adder
8
972163AH1-664 GEN
Solar/Wind Harmer
7.187
965101AG1-375 GEN
Solar/Wind Harmer
6.406
970115AG2-085 GEN
Solar/Wind Harmer
2.556
971609AH1-304 GEN
Solar/Wind Harmer
1.043
24699105WLD G1 C
Solar/Wind Harmer
0.001
965041AG1-368 GEN
Solar/Wind Harmer
6.297
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0
24697905MDL-4G C
Solar/Wind Harmer
0.001
24386205FR-12G C
Solar/Wind Harmer
0.001
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
963841AG1-237 GEN
Solar/Wind Harmer
2.71
274776LINCOLN ;7U
Adder
7.514
274814UNIV PK N;0U
Adder
4.489
274807UNIV PK N;3U
Adder
4.479
274805UNIV PK N;1U
Adder
4.459
270400AC1-102 GEN
Solar/Wind Harmer
1.957
276882AE2-255 GEN
Solar/Wind Harmer
0.717
238152AF2-075_GEN
Solar/Wind Helper
0.593
23546401DTGZ2-030
Solar/Wind Helper
0.075
24721705FLATG2
Adder
23.442
970155AG2-107 GEN
Solar/Wind Harmer
18.834
970947AG2-589 GEN
Solar/Wind Harmer
0.239
270349AD2-093_GEN
Solar/Wind Harmer
0.005
24686105CER G3
Adder
8.253
24723205RIVRG3
Adder
18.473
253343AC1-166 GEN
Solar/Wind Harmer
0.003
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.657
253370AE2-315 SEC1
Adder
1.906
253371AE2-315 SEC2
Adder
1.803
960071AF2-298 GEN
Solar/Wind Harmer
3.297
25194608D.CRK4
Adder
1.55
945681AF1-233 GEN
Solar/Wind Harmer
12.186
970613AG2-401 GEN
Solar/Wind Harmer
4.707
965651AG1-433 GEN
Solar/Wind Harmer
1.879
971995AH1-542 GEN
Solar/Wind Harmer
2.347
965031AG1-367 GEN
Solar/Wind Harmer
6.4
970291AG2-192 GEN
Solar/Wind Harmer
0.829
247521TR3_G114
Solar/Wind Harmer
0.23
270246TR4_N_V150
Solar/Wind Harmer
0.041
24728605AND G2
Adder
3.466
965421AG1-410 GEN
Solar/Wind Harmer
18.858
24695305TIMB G C
Solar/Wind Harmer
0.002
270055AF2-134 C O1
Solar/Wind Harmer
0.005
24639705ELKHART HY
Adder
0.137
270445AC2-157 GEN2
Solar/Wind Harmer
0.003
270449AD2-020 GEN
Solar/Wind Harmer
0
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.45
276776AD2-060 GEN
Solar/Wind Harmer
0.646
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
276901AD2-066 C O1
Solar/Wind Harmer
0.006
316095T157 G97
Solar/Wind Helper
1.299
238185AF2-356 C
Solar/Wind Helper
1.996
962771AG1-126 GEN
Solar/Wind Harmer
29.494
972203AH1-686 GEN
Adder
2.298
970689AG2-444 GEN
Solar/Wind Harmer
14.206
270284AF1-227 GEN1
Solar/Wind Harmer
0.009
253383AE2-342_GEN
Solar/Wind Harmer
0.002
241973AD2-163_GEN1
Solar/Wind Harmer
0.005
943861AF1-054 GEN
Solar/Wind Harmer
2.627
943851AF1-053 GEN
Solar/Wind Harmer
1.82
253372AE2-315 SEC3
Adder
1.803
253372AE2-315 SEC3
Adder
1.803
25306009OHH W.
Adder
2.735
252524AE2-267 GEN
Solar/Wind Harmer
0.002
270302AB2-170 GEN
Solar/Wind Harmer
0.004
971653AH1-327 GEN
Solar/Wind Harmer
0.917
270024AE2-089 GEN
Solar/Wind Harmer
0.007
970289AG2-191 GEN
Solar/Wind Harmer
1.211
963791AG1-232 GEN
Solar/Wind Harmer
8.573
957201AF2-014 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.008
274811UNIV PK N;7U
Adder
0.697
970179AG2-119 GEN
Solar/Wind Harmer
5.506
970169AG2-114 GEN
Solar/Wind Harmer
6.145
238109AE1-109 GEN2
Solar/Wind Helper
0.088
238110AE1-109 GEN3
Solar/Wind Helper
0.088
970935AG2-582 GEN
50/50
1217.062
24318905MLG2
50/50
4.656
270471AD2-092_GEN
Solar/Wind Harmer
0.005
24685805CER G1
Adder
8.199
24685905CER G2
Adder
8.199
24723005RIVRG1
Adder
18.473
24723105RIVRG2
Adder
18.473
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
253370AE2-315 SEC1
Adder
1.906
25322209TAIT E
Adder
9.269
25322209TAIT E
Adder
9.061
252519AF1-045_GEN
Solar/Wind Harmer
5.748
252516AE2-318_GEN
Solar/Wind Harmer
5.098
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
971655AH1-328 GEN
Solar/Wind Harmer
2.34
276820AF1-078_GEN
Solar/Wind Harmer
0.002
247621Y3-024
Adder
0.222
971613AH1-306 GEN
Solar/Wind Harmer
3.063
965681AG1-436 GEN
Solar/Wind Harmer
7.82
270444AC2-157 GEN1
Solar/Wind Harmer
0.003
971587AH1-292 GEN
Solar/Wind Harmer
4.56
971125AH1-004 GEN
Solar/Wind Harmer
2.483
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
238169AE2-226 GEN1
Solar/Wind Helper
0.582
238170AE2-226 GEN2
Solar/Wind Helper
0.582
238120AE2-309 GEN
Solar/Wind Helper
0.406
23777801MSM_W1-116
Solar/Wind Helper
0.096
944201AF1-088_MTX
Adder
103.64
957141AF2-008_MTX
Adder
51.82
NYPJM->LTFIMP_NY
CLTF
4.417
LGEELTFEXP_LGEE->PJM
CLTF
6.111
WECLTFEXP_WEC->PJM
CLTF
3.336
AG2-052LTFEXP_AG2-052->PJM
LTF
0.208
AH1-155LTFEXP_AH1-155->PJM
LTF
0.312
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.614
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.188
MECLTFEXP_MEC->PJM
CLTF
14.066
SIGELTFEXP_SIGE->PJM
CLTF
0.455
LAGNLTFEXP_LAGN->PJM
CLTF
13.832
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.925
TVALTFEXP_TVA->PJM
CLTF
6.876
CPLELTFEXP_CPLE->PJM
CLTF
1.286
CBM West 2LTFEXP_CBM-W2->PJM
CBM
102.798

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-007A_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-007A_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:130.62 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4870.98
MW Contribution:1.12
Bus #Bus NameTypeMW Contribution
962771AG1-126 GEN
Solar/Wind Harmer
34.524
270284AF1-227 GEN1
Solar/Wind Harmer
0.011
253383AE2-342_GEN
Solar/Wind Harmer
0.003
241973AD2-163_GEN1
Solar/Wind Harmer
0.006
943861AF1-054 GEN
Solar/Wind Harmer
3.127
943851AF1-053 GEN
Solar/Wind Harmer
2.166
970689AG2-444 GEN
Solar/Wind Harmer
16.436
270302AB2-170 GEN
Solar/Wind Harmer
0.005
971653AH1-327 GEN
Solar/Wind Harmer
1.117
970179AG2-119 GEN
Solar/Wind Harmer
6.883
253372AE2-315 SEC3
Adder
2.063
253372AE2-315 SEC3
Adder
2.063
25306009OHH W.
Adder
3.13
957201AF2-014 GEN
Solar/Wind Harmer
0.001
971989AH1-539 GEN
Solar/Wind Harmer
3.215
963791AG1-232 GEN
Solar/Wind Harmer
10.044
270024AE2-089 GEN
Solar/Wind Harmer
0.008
252524AE2-267 GEN
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
1.389
270536AF1-215 GEN2
Solar/Wind Harmer
0.009
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274811UNIV PK N;7U
Adder
5.139
274827FISK ;RP
Adder
7.941
972227AH1-698 GEN1
Adder
2.669
274735ELWOOD EC;4P
Adder
16.768
274744AC1-111 GEN8
Adder
5.679
972203AH1-686 GEN
Adder
2.338
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
959381AF2-229 GEN
Solar/Wind Helper
0.357
960921AF2-383 GEN
Solar/Wind Helper
0.364
205932AD2-116_GEN
Solar/Wind Helper
0.509
232432Z2-076 GEN
Solar/Wind Helper
0.067
234033AF1-007_GEN
Solar/Wind Helper
7.02
203975AE1-071-GEN
Solar/Wind Helper
2.498
966261AG1-495 GEN
Solar/Wind Helper
0.081
20674828DL_W4-046
Solar/Wind Helper
0.008
207408W3-077 C
Solar/Wind Helper
0.084
970155AG2-107 GEN
Solar/Wind Harmer
22.046
270349AD2-093_GEN
Solar/Wind Harmer
0.006
24721705FLATG2
Adder
23.918
253343AC1-166 GEN
Solar/Wind Harmer
0.003
971995AH1-542 GEN
Solar/Wind Harmer
2.906
960071AF2-298 GEN
Solar/Wind Harmer
3.786
253370AE2-315 SEC1
Adder
2.182
253371AE2-315 SEC2
Adder
2.063
965421AG1-410 GEN
Solar/Wind Harmer
22.57
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.499
247521TR3_G114
Solar/Wind Harmer
0.273
270246TR4_N_V150
Solar/Wind Harmer
0.048
24695305TIMB G C
Solar/Wind Harmer
0.002
965651AG1-433 GEN
Solar/Wind Harmer
2.174
25194608D.CRK4
Adder
1.74
970947AG2-589 GEN
Solar/Wind Harmer
0.245
965031AG1-367 GEN
Solar/Wind Harmer
7.338
970613AG2-401 GEN
Solar/Wind Harmer
5.378
24639705ELKHART HY
Adder
0.161
970291AG2-192 GEN
Solar/Wind Harmer
0.95
270449AD2-020 GEN
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0.006
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
5.139
24728605AND G2
Adder
3.927
276776AD2-060 GEN
Solar/Wind Harmer
0.746
945681AF1-233 GEN
Solar/Wind Harmer
13.461
274676JOLIET 29;8U
Adder
31.303
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
274745AC1-111 GEN9
Adder
5.679
276901AD2-066 C O1
Solar/Wind Harmer
0.007
316095T157 G97
Solar/Wind Helper
1.504
238185AF2-356 C
Solar/Wind Helper
2.646
23751101LEADS_P59
Solar/Wind Helper
1.404
237030AB1-096 C
Solar/Wind Helper
0.071
227287AC2-120 GEN
Solar/Wind Helper
0.346
233996TM1833_GEN
Solar/Wind Helper
0.261
232406W1-004 FULL
Solar/Wind Helper
0.507
230430AE1-229_GEN
Solar/Wind Helper
3.372
230415AB2-049 C
Solar/Wind Helper
0.03
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.15
219291REEVESSOUT C
Solar/Wind Helper
0.011
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
20720828JCB_W4-025
Solar/Wind Helper
0.063
20714528FRN_Y2-051
Solar/Wind Helper
0.057
218438BLK ROCK C
Solar/Wind Helper
0.027
219919AE1-041 FULL
Solar/Wind Helper
0.004
20674628WNG_W3-110
Solar/Wind Helper
0.089
942861AE2-305 GEN
Solar/Wind Harmer
6.335
270518AE2-148 GEN
Solar/Wind Harmer
0.691
972159AH1-661 GEN
Adder
1.118
970329AG2-216 GEN
Solar/Wind Harmer
3.354
971199AH1-059 GEN
Solar/Wind Harmer
3.09
241960AC2-195 GEN
Solar/Wind Harmer
0.006
971073AG2-665 GEN
Solar/Wind Harmer
6.898
25326109MON D
Adder
1.443
971231AH1-075 GEN
Solar/Wind Harmer
0.861
25183208HLCRTG
Solar/Wind Harmer
0.012
944541AF1-119 GEN
Solar/Wind Harmer
0.497
24318805MLG1
50/50
10.095
270475AD2-096_GEN
50/50
7.141
253338AC1-165 GEN
Solar/Wind Harmer
0.003
972173AH1-669 GEN
Solar/Wind Harmer
3.952
970191AG2-125 GEN
Solar/Wind Harmer
1.945
270491AE1-102 GEN2
Solar/Wind Harmer
0.979
270191TR4_S_V150
Solar/Wind Harmer
0.001
959331AF2-224 GEN
Solar/Wind Harmer
5.242
270258AD1-119 GEN
Solar/Wind Harmer
0.002
971617AH1-308 GEN
Solar/Wind Harmer
6.173
270222AC2-111 GEN
Solar/Wind Harmer
3.739
270004AE1-209 GEN
Solar/Wind Harmer
1.59
24642205MAYFLWER
Adder
0.665
270356AE2-297 GEN
Solar/Wind Harmer
0.01
964401AG1-302 GEN
Solar/Wind Harmer
0.001
970217AG2-149 GEN
Solar/Wind Harmer
6.268
274753CRETE EC ;3U
Adder
8.477
972038AH1-567 GEN2
Adder
0.373
238118U2-030_1
Solar/Wind Helper
0.341
238148AE2-230_GEN2
Solar/Wind Helper
0.497
237038AE2-054 C
Solar/Wind Helper
0.272
23779801AA1-109
Solar/Wind Helper
0.193
316006AB2-029 C
Solar/Wind Helper
0.117
316045AC1-158 PL2
Solar/Wind Helper
4.138
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.131
207445AB1-138_GEN
Solar/Wind Helper
0.104
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
970885AG2-551 GEN
Solar/Wind Harmer
2.463
270201AC2-176 GEN
Solar/Wind Harmer
0.001
25194508D.CRK3
Adder
1.496
964611AG1-324 GEN
Solar/Wind Harmer
0.553
252509AD1-136 GEN
Solar/Wind Harmer
0.037
270031AE2-169
Solar/Wind Harmer
4.042
270383AD1-128 GEN
Solar/Wind Harmer
0.004
24379505HDWTR1G C
Solar/Wind Harmer
0.002
247620Y3-023
Adder
0.484
960441AF2-335 GEN
Solar/Wind Harmer
7.33
24728805RICHG1
Adder
3.964
270526AF1-158 GEN
Solar/Wind Harmer
0.009
24441505OLIV SLR
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
6.67
945421AF1-207 GEN
Solar/Wind Harmer
0.001
276843GEN-1.7
Solar/Wind Harmer
0.231
958011AF2-095 GEN
Solar/Wind Harmer
10.284
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
971573AH1-285 GEN
Solar/Wind Harmer
1.319
274695ROCKY RD ;2P
Adder
11.271
958491AF2-143 GEN
Solar/Wind Harmer
10.588
237034AC2-136 C
Solar/Wind Helper
0.227
235063AE1-101 C2
Solar/Wind Helper
1.659
237001AB1-127_GEN
Solar/Wind Helper
0.442
226929AD2-058 GEN
Solar/Wind Helper
0.099
233987AB2-037 GEN
Solar/Wind Helper
2.342
234036AF2-325 C
Solar/Wind Helper
0.042
233901CHERRYDALE C
Solar/Wind Helper
0.232
20720628TIN_W1-124
Solar/Wind Helper
0.19
207442AE1-156 GEN
Solar/Wind Helper
0.326
20671828STAW2-080
Solar/Wind Helper
0.027
20674128FR_U2-059
Solar/Wind Helper
0.004
211065PSPA IPP
Solar/Wind Helper
0.151
211065PSPA IPP
Solar/Wind Helper
0.151
972239AH1-704 GEN
Adder
2.689
961821AG1-024 GEN
Solar/Wind Harmer
5.077
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
945631AF1-228 GEN
Solar/Wind Harmer
0
270578AF1-285 GEN2
Solar/Wind Harmer
0.536
270432AC2-029 GEN
Solar/Wind Harmer
3.553
270269AC2-059
Solar/Wind Harmer
0.005
241972AD1-140 GEN
Solar/Wind Harmer
0.854
270340AC2-060 GEN
Solar/Wind Harmer
0.009
253400AC2-068 GEN
Solar/Wind Harmer
0.958
965041AG1-368 GEN
Solar/Wind Harmer
7.471
965101AG1-375 GEN
Solar/Wind Harmer
7.401
25196508WSDLE4
Adder
8.984
270297AD1-101 GEN
Solar/Wind Harmer
0.002
971609AH1-304 GEN
Solar/Wind Harmer
1.2
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
970115AG2-085 GEN
Solar/Wind Harmer
2.932
24699105WLD G1 C
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
274776LINCOLN ;7U
Adder
8.676
24386205FR-12G C
Solar/Wind Harmer
0.001
274814UNIV PK N;0U
Adder
5.184
274807UNIV PK N;3U
Adder
5.173
274805UNIV PK N;1U
Adder
5.15
963841AG1-237 GEN
Solar/Wind Harmer
3.09
972163AH1-664 GEN
Solar/Wind Harmer
7.933
274687WILL CNTY;4U
Adder
28.523
274687WILL CNTY;4U
Adder
28.523
274731ELWOOD EC;2P
Adder
16.768
274733ELWOOD EC;3P
Adder
16.768
274746AC1-111 G10
Adder
5.679
276882AE2-255 GEN
Solar/Wind Harmer
0.824
238152AF2-075_GEN
Solar/Wind Helper
0.707
23546401DTGZ2-030
Solar/Wind Helper
0.089
3138216PACIFIC
Solar/Wind Helper
0.044
23750501ELLIOTTS
Solar/Wind Helper
0.638
205956AE1-196_GEN
Solar/Wind Helper
0.509
233935AB2-179 C
Solar/Wind Helper
1.269
232436AB1-176 C
Solar/Wind Helper
0.044
233923SMA
Solar/Wind Helper
0.958
219914AD2-027 C
Solar/Wind Helper
0.115
219607WPEMNERT C
Solar/Wind Helper
0.08
20715728PEM_W1-119
Solar/Wind Helper
0.096
316164AC1-076 GEN
Solar/Wind Helper
1.096
20675528CPH_W2-050
Solar/Wind Helper
0.087
218524CNTRALGAS1 C
Solar/Wind Helper
0.16
207530AG1-191 GEN
Solar/Wind Helper
0.066
20675128HRM_W1-127
Solar/Wind Helper
0.029
270051AF1-062 GEN
50/50
11.821
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270512AE1-227 GEN2
Solar/Wind Harmer
1.963
970065AG2-057 GEN
Solar/Wind Harmer
0.76
971191AH1-055 GEN
Solar/Wind Harmer
19.26
965021AG1-366 GEN
Solar/Wind Harmer
2.496
270043AE2-236 GEN
Solar/Wind Harmer
4.777
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
252510AF1-249 C
Solar/Wind Harmer
0.057
957741AF2-068 GEN
Solar/Wind Harmer
11.081
945111AF1-176 GEN
Solar/Wind Harmer
5.919
25196008MFTGT1
Adder
1.405
24441205WTRV SLR C
Solar/Wind Harmer
0
970243AG2-164 GEN
Solar/Wind Harmer
4.205
274772LINCOLN ;3U
Adder
8.676
274724RIVER EC ;11
Adder
18.203
972167AH1-666 GEN
Solar/Wind Harmer
5.717
274802UNIV PARK;5U
Adder
5.97
970941AG2-585 GEN
Solar/Wind Harmer
8.927
274800UNIV PARK;3U
Adder
5.966
276897AD1-100 C
Solar/Wind Harmer
0.009
276893AG1-478 C
Solar/Wind Harmer
0.282
274729ELWOOD EC;1P
Adder
16.768
276805AD2-038 GEN
Solar/Wind Harmer
0.002
237048AF1-022 C
Solar/Wind Helper
0.177
233930AB2-032 GEN
Solar/Wind Helper
0.381
233954AC2-188 GEN
Solar/Wind Helper
0.232
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.23
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219907AC1-030 C
Solar/Wind Helper
0.034
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
207437AD2-070 GEN
Solar/Wind Helper
0.138
20671928W4-073
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.029
270459AD2-067 GEN
Solar/Wind Harmer
0
270156DARBY CT1
Adder
10.409
270157DARBY CT2
Adder
10.383
940611AE2-048 GEN
Solar/Wind Harmer
19.602
941391AE2-136 GEN
Solar/Wind Harmer
11.042
970879AG2-548 GEN
Solar/Wind Harmer
6.898
270435AC2-044 GEN
Solar/Wind Harmer
0.953
247607V1-011 GEN
Solar/Wind Harmer
0.001
971567AH1-282 GEN
Solar/Wind Harmer
11.206
24729505KEY G4
Adder
6.919
270071AF1-092 GEN
Solar/Wind Harmer
14.245
270367AC2-061_GEN
Solar/Wind Harmer
0.006
971673AH1-337 GEN
Solar/Wind Harmer
4.804
25196408WSDLE3
Adder
9.344
25196308WSDLE2
Adder
9.263
25196208WSDLE1
Adder
9.24
25196708WSDLE6
Adder
9.217
270543AE2-219 C
Solar/Wind Harmer
0.004
270240V3-007_GEN2
Solar/Wind Harmer
0.002
270594AE1-207 GEN
Solar/Wind Harmer
8.194
971771AH1-392 GEN
Solar/Wind Harmer
7.306
971769AH1-391 GEN
Solar/Wind Harmer
8.134
25196108MFTGT2
Adder
1.599
25196108MFTGT2
Adder
1.484
971549AH1-272 GEN
Solar/Wind Harmer
14.865
24691005MDL-2G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
274728ELWOOD EC;5P
Adder
16.768
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
238126S14_GEN_1
Solar/Wind Helper
0.827
237085AD2-009_GEN
Solar/Wind Helper
1.649
316411AF1-147_GEN1
Solar/Wind Helper
0.888
316415AF1-147_GEN2
Solar/Wind Helper
0.888
3141426STAFORD
Solar/Wind Helper
0.052
228754AB1-001 C
Solar/Wind Helper
0.026
219272CLEANLIGHT C
Solar/Wind Helper
0.025
270119AB2-067 GEN1
50/50
7.059
970077AG2-063 GEN
Solar/Wind Harmer
4.631
972269AH1-719 GEN
Adder
2.584
253378AE2-206_GEN
Solar/Wind Harmer
0.004
25326509SID D
Adder
1.451
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
246938BC-WTG3
Solar/Wind Harmer
0.273
246937BC-WTG2
Solar/Wind Harmer
0.305
970611AG2-400 GEN
Solar/Wind Harmer
7.488
270007AE1-245 C
Solar/Wind Harmer
0.002
962581AG1-107 GEN
Solar/Wind Harmer
0.002
970623AG2-406 GEN
Solar/Wind Harmer
1.356
942221AE2-234 GEN
Solar/Wind Harmer
0.037
970621AG2-405 GEN
Solar/Wind Harmer
1.351
970321AG2-212 GEN
Solar/Wind Harmer
3.191
270186AC1-089 GEN
Solar/Wind Harmer
0.004
270209AC1-174_GEN
Solar/Wind Harmer
0.001
970825AG2-519 GEN
Solar/Wind Harmer
8.127
957891AF2-083 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
970239AG2-162 GEN
Solar/Wind Harmer
1.797
274770LINCOLN ;1U
Adder
8.676
274771LINCOLN ;2U
Adder
8.676
274808UNIV PK N;4U
Adder
5.117
274888KELLY CRK;1U
Solar/Wind Harmer
0.419
972259AH1-714 GEN
Adder
19.507
970241AG2-163 GEN
Solar/Wind Harmer
4.144
274696ROCKY RD ;4P
Adder
11.537
274697ROCKY RD ;3P
Adder
3.062
238175AF1-290_GEN
Solar/Wind Helper
0.153
235020AA1-095 C
Solar/Wind Helper
0.053
205916AD1-020 GEN
Solar/Wind Helper
1.713
20390526W1-045 C
Solar/Wind Helper
0.35
233933AB2-153 GEN
Solar/Wind Helper
0.232
233944AB2-135 GEN
Solar/Wind Helper
0.588
233946AB2-136 GEN
Solar/Wind Helper
0.568
232408W1-005 C
Solar/Wind Helper
0.507
232410W1-006 C
Solar/Wind Helper
0.507
233939AC1-091 C
Solar/Wind Helper
0.35
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.082
20716928W4-060COL
Solar/Wind Helper
0.051
20673828FLE_V3-070
Solar/Wind Helper
0.09
20676128MHD_W3-029
Solar/Wind Helper
0.096
217081WEATEXAS C
Solar/Wind Helper
0.013
207471AF2-354 C
Solar/Wind Helper
0.168
20676228FRD_X1-012
Solar/Wind Helper
0.092
23559101PLEAS2
50/50
6.1
970149AG2-104 GEN
Solar/Wind Harmer
37.287
270159DARBY CT4
Adder
10.243
970593AG2-378 GEN
Solar/Wind Harmer
1.812
270223U2-072_GEN1
Solar/Wind Harmer
0.001
253325AC1-069 GEN
Solar/Wind Harmer
0.012
270263AC1-001 GEN
Solar/Wind Harmer
0.786
270510AE1-227 GEN1
Solar/Wind Harmer
1.963
927014AC1-188 GEN
Solar/Wind Harmer
0.005
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
943021AE2-325 GEN
Solar/Wind Harmer
3.805
970773AG2-487 GEN
Solar/Wind Harmer
1.284
970373AG2-245 GEN
Solar/Wind Harmer
15.247
971917AH1-482 GEN
Solar/Wind Harmer
9.41
970515AG2-329 GEN
Solar/Wind Harmer
18.805
24791305MDL-5G
Solar/Wind Harmer
0.001
941551AE2-152 GEN
Solar/Wind Harmer
0.001
963741AG1-226 GEN
Solar/Wind Harmer
16.815
276691AA1-018 GEN1
Solar/Wind Harmer
0.858
970091AG2-072 GEN
Adder
77.629
238108AE1-109 GEN1
Solar/Wind Helper
0.114
235054AD2-180 GEN
Solar/Wind Helper
2.03
235531U2-073 GEN
Solar/Wind Helper
3.282
23562501BACKB
Solar/Wind Helper
1.007
205917AD1-020 ES
Solar/Wind Helper
0.368
233918AB1-142 GEN
Solar/Wind Helper
0.502
233994AC2-023 GEN
Solar/Wind Helper
0.961
233997TMININ_4.2
Solar/Wind Helper
0.261
233971AC1-093 C
Solar/Wind Helper
0.357
228729W2-030 C
Solar/Wind Helper
0.11
219348LDSOLAR C
Solar/Wind Helper
0.114
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715028HAN_X4-015
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.353
219249CENTRALDIV C
Solar/Wind Helper
0.01
217211CAMDEN ST C
Solar/Wind Helper
0.005
23559001PLEAS1
50/50
6.1
961921AG1-034 GEN
Solar/Wind Harmer
7.615
942051AE2-217 GEN
Solar/Wind Harmer
14.671
970605AG2-385 GEN
Solar/Wind Harmer
4.899
270054AF2-122 C O1
Solar/Wind Harmer
0.007
270520AE2-214 GEN
Solar/Wind Harmer
0.013
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
270158DARBY CT3
Adder
10.218
270317AD1-130_GEN
Solar/Wind Harmer
0.011
253349AC2-067 GEN
Solar/Wind Harmer
2.381
965051AG1-369 GEN
Solar/Wind Harmer
3.739
971985AH1-537 GEN
Solar/Wind Harmer
2.206
971029AG2-637 GEN
Solar/Wind Harmer
11.085
945581AF1-223 GEN
Solar/Wind Harmer
0.001
971347AH1-153 GEN
Solar/Wind Harmer
11.025
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
971619AH1-309 GEN
Solar/Wind Harmer
3.285
24725505WLD G2 C
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
4.302
24697605MDL-3G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
8.676
274777LINCOLN ;8U
Adder
8.676
24386405FR-21G C
Solar/Wind Harmer
0.001
972037AH1-567 GEN1
Adder
0.187
960591AF2-350 GEN
Solar/Wind Harmer
7.141
972165AH1-665 GEN
Solar/Wind Harmer
6.354
274675JOLIET 29;7U
Adder
31.303
270120AB2-067 GEN2
50/50
7.059
270224U2-072_GEN2
Solar/Wind Harmer
0.001
938701AE1-092 GEN
Solar/Wind Harmer
12.917
964601AG1-323 GEN
Solar/Wind Harmer
3.215
964601AG1-323 GEN
Solar/Wind Harmer
2.143
971201AH1-060 GEN
Solar/Wind Harmer
1.52
970627AG2-408 GEN
Solar/Wind Harmer
2.246
960971AF2-388 GEN
Solar/Wind Harmer
4.347
970883AG2-550 GEN
Solar/Wind Harmer
7.389
25194408D.CRK1
Adder
8.004
270599AE1-208 GEN
Solar/Wind Harmer
6.737
926881AC1-175 GEN
Solar/Wind Harmer
0.001
270216AD2-079_GEN
Solar/Wind Harmer
0.001
24728905RICHG2
Adder
3.964
961051AF2-396 GEN
Solar/Wind Harmer
14.589
961051AF2-396 GEN
Solar/Wind Harmer
9.726
966841AG1-555 GEN
Solar/Wind Harmer
0.81
274803UNIV PARK;6U
Adder
5.97
274887GEN-1.85
Solar/Wind Harmer
0.188
274674JOLIET 9 ;6U
Adder
15.704
958481AF2-142 GEN
Solar/Wind Harmer
10.621
274862TOP CROP ;2U
Solar/Wind Harmer
0.958
274693ROCKY RD ;1P
Adder
11.16
274879MINONK ;1U
Solar/Wind Harmer
0.297
23585401KL_K28_T16
Solar/Wind Helper
1.482
23777901MDS_W4-102
Solar/Wind Helper
0.177
237002AB1-128_GEN
Solar/Wind Helper
0.443
237006AB1-125 GEN
Solar/Wind Helper
0.123
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
232424Y1-079 C
Solar/Wind Helper
0.116
233970AC1-092 C
Solar/Wind Helper
0.35
230433AD2-135 GEN
Solar/Wind Helper
0.017
219921AF1-264
Solar/Wind Helper
0.051
219615MILLCREEK C
Solar/Wind Helper
0.027
20674928WA_W3-044
Solar/Wind Helper
0.098
270391AF1-285 GEN3
Solar/Wind Harmer
0.536
253333AC1-068 GEN
Solar/Wind Harmer
0.012
270273AD2-016 GEN
Solar/Wind Harmer
0.821
270291AC1-194 GEN
Solar/Wind Harmer
6.106
253415AE1-040 GEN
Solar/Wind Harmer
0.003
253406AD2-031_GEN
Solar/Wind Harmer
0.563
270377AD1-106 GEN
Solar/Wind Harmer
2.855
270247TR4_N_V136
Solar/Wind Harmer
0.048
944531AF1-118 GEN
Solar/Wind Harmer
33.395
25196608WSDLE5
Adder
9.077
970031AG2-029 GEN
Solar/Wind Harmer
4.795
270404AC1-167 GEN
Solar/Wind Harmer
0.003
970513AG2-328 GEN
Solar/Wind Harmer
3.191
970517AG2-330 GEN
Solar/Wind Harmer
19.146
970349AG2-230 GEN
Solar/Wind Harmer
11.025
958821AF2-173 GEN
Solar/Wind Harmer
10.273
270437AC2-090 C
Solar/Wind Harmer
0.003
247604X1-042
Adder
0.433
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
970781AG2-491 GEN
Solar/Wind Harmer
7.196
970519AG2-331 GEN
Solar/Wind Harmer
18.687
970699AG2-449 GEN
Solar/Wind Harmer
1.797
274752CRETE EC ;2U
Adder
8.477
958171AF2-111 GEN
Solar/Wind Harmer
17.94
24728705AND G3
Adder
8.214
274826FISK ;BP
Adder
11.205
972228AH1-698 GEN2
Adder
3.79
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
970707AG2-453 GEN
Solar/Wind Harmer
23.303
274730ELWOOD EC;6P
Adder
16.768
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
270541AE2-072 C
Solar/Wind Harmer
0.009
23750701CROSSCHOOL
Solar/Wind Helper
1.502
238127S14_GEN_2
Solar/Wind Helper
0.827
235062AE1-101 C1
Solar/Wind Helper
1.659
223401AF1-299 GEN
Solar/Wind Helper
0.367
233915AB1-141 GEN
Solar/Wind Helper
0.502
232428Y3-058 C
Solar/Wind Helper
0.338
233998TM1NIN_3.36
Solar/Wind Helper
0.261
232404W1-003 C
Solar/Wind Helper
0.507
233950AC2-186 GEN
Solar/Wind Helper
0.116
233972AC1-094 C
Solar/Wind Helper
0.302
228728W1-130C
Solar/Wind Helper
0.054
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
316254AC1-120 GEN1
Solar/Wind Helper
1.059
963711AG1-223 GEN
Solar/Wind Helper
0.064
207454AA2-184 E
Solar/Wind Helper
0.31
20715228NPK_W1-113
Solar/Wind Helper
0.078
20675428EAM_W2-061
Solar/Wind Helper
0.016
207518AF1-320_GEN
Solar/Wind Helper
1.571
970153AG2-106 GEN
Solar/Wind Harmer
22.046
241955AC1-078 GEN
Solar/Wind Harmer
0.007
24721905FLATG4
Adder
23.918
241974AD2-163_GEN2
Solar/Wind Harmer
0.006
253370AE2-315 SEC1
Adder
2.182
253371AE2-315 SEC2
Adder
2.063
253316AC1-085 GEN3
Solar/Wind Harmer
0.005
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
9.749
270588AE1-091_GEN
Solar/Wind Harmer
5.845
25194608D.CRK4
Adder
1.74
946031AF1-268 GEN
Solar/Wind Harmer
6.992
247643Z2-116 C
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.804
970291AG2-192 GEN
Solar/Wind Harmer
0.731
247642Z2-115 C
Solar/Wind Harmer
0.003
270535AF1-215 GEN1
Solar/Wind Harmer
0.009
24755605MDL-5G
Solar/Wind Harmer
0.001
24728505AND G1
Adder
3.927
276806AD2-047 C O1
Solar/Wind Harmer
4.047
274676JOLIET 29;8U
Adder
30.185
274734ELWOOD EC;8P
Adder
16.768
274736ELWOOD EC;9P
Adder
16.768
943121AE2-341 GEN
Solar/Wind Harmer
11.888
943591AF1-030 GEN
Solar/Wind Harmer
7.906
274682WAUKEGAN ;7U
Adder
9.728
964991AG1-363 GEN
Solar/Wind Helper
5.136
316097T157 G90
Solar/Wind Helper
1.504
237080AD1-060 GEN
Solar/Wind Helper
0.342
966131AG1-482 GEN
Solar/Wind Helper
0.137
232422X3-066 FULL
Solar/Wind Helper
0.114
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
232434Z2-077 GEN
Solar/Wind Helper
0.127
219904AC1-010 C
Solar/Wind Helper
0.06
20720728JCB_W1-129
Solar/Wind Helper
0.057
20714828MDF_W3-079
Solar/Wind Helper
0.13
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.495
217208PARK ELE C
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.074
24318905MLG2
50/50
7.071
270471AD2-092_GEN
Solar/Wind Harmer
0.006
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
971655AH1-328 GEN
Solar/Wind Harmer
2.854
276820AF1-078_GEN
Solar/Wind Harmer
0.002
25322209TAIT E
Adder
10.642
25322209TAIT E
Adder
10.403
253370AE2-315 SEC1
Adder
2.182
253317AC1-085 GEN4
Solar/Wind Harmer
0.005
252519AF1-045_GEN
Solar/Wind Harmer
6.44
252516AE2-318_GEN
Solar/Wind Harmer
5.712
247621Y3-024
Adder
0.255
971613AH1-306 GEN
Solar/Wind Harmer
3.512
965681AG1-436 GEN
Solar/Wind Harmer
9.095
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
238120AE2-309 GEN
Solar/Wind Helper
0.525
238169AE2-226 GEN1
Solar/Wind Helper
0.701
238170AE2-226 GEN2
Solar/Wind Helper
0.701
23777801MSM_W1-116
Solar/Wind Helper
0.114
237025AB1-124 C
Solar/Wind Helper
0.164
315651AD1-115 GEN
Solar/Wind Helper
0.785
316447AC1-158 HLD
Solar/Wind Helper
2.845
230407AD2-065 C
Solar/Wind Helper
0.04
20714928UPF_X1-085
Solar/Wind Helper
0.005
218440SUMMTASSOC C
Solar/Wind Helper
0.016
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
964851AG1-348 GEN
Solar/Wind Helper
0.081
270166AC1-044 GEN3
50/50
7.059
246936BC-WTG1
Solar/Wind Harmer
0.305
270489AE1-102 GEN1
Solar/Wind Harmer
0.979
965011AG1-365 GEN
Solar/Wind Harmer
7.488
958861AF2-177 GEN
Solar/Wind Harmer
3.207
945371AF1-202 GEN
Solar/Wind Harmer
0.001
270005AE1-210 C O1
Solar/Wind Harmer
1.59
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
2.603
25196808ZIMRHP
Adder
79.729
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
270032AE2-172
Solar/Wind Harmer
4.877
945111AF1-176 GEN
Solar/Wind Harmer
13.03
270505AE1-170 C O1
Solar/Wind Harmer
7.665
25196008MFTGT1
Adder
1.45
247522W1-056 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
9.032
970333AG2-219 GEN
Solar/Wind Harmer
5.139
274751CRETE EC ;1U
Adder
8.477
274773LINCOLN ;4U
Adder
8.676
274774LINCOLN ;5U
Adder
8.676
274723RIVER EC ;12
Adder
18.418
24387305FR-4G C
Solar/Wind Harmer
0.003
274801UNIV PARK;4U
Adder
5.966
23583801GRNGAP
Solar/Wind Helper
5.601
238149AF1-291A_GEN
Solar/Wind Helper
0.141
23751201ROTHROCK
Solar/Wind Helper
0.824
237061AD1-155 GEN
Solar/Wind Helper
0.053
238221AF1-254 C O1
Solar/Wind Helper
0.274
3141196NOKESVL
Solar/Wind Helper
1.032
226910AB2-157 C
Solar/Wind Helper
0.014
223402AF1-300 C
Solar/Wind Helper
0.367
233982AB2-133 GEN
Solar/Wind Helper
0.358
233940AF2-379 C
Solar/Wind Helper
0.062
233952AC2-187 GEN
Solar/Wind Helper
0.232
219623KINSLEYBEA C
Solar/Wind Helper
0.002
20716028EGP_W2-019
Solar/Wind Helper
0.019
219612MATRIX C
Solar/Wind Helper
0.024
219908AB1-139 C
Solar/Wind Helper
0.074
20673728F2S_V4-070
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
971997AH1-543 GEN
Solar/Wind Harmer
2.724
20675928HOL_W4-097
Solar/Wind Helper
0.05
207484AF2-139 C O1
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.136
209116AE2-175 GEN
Solar/Wind Helper
1.778
274675JOLIET 29;7U
Adder
30.185
970833AG2-524 GEN
Solar/Wind Harmer
7.824
970833AG2-524 GEN
Solar/Wind Harmer
5.216
276868AE1-113 GEN
Solar/Wind Harmer
1.414
238208AF1-136 C
Solar/Wind Helper
0.22
205943AE1-185 GEN
Solar/Wind Helper
0.509
233990AG1-397 GEN
Solar/Wind Helper
0.27
964001AG1-254 GEN
Solar/Wind Helper
0.955
227927V4-067C
Solar/Wind Helper
0.01
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
214067T20SOLAR
Solar/Wind Helper
0.011
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.29
219620RIDERU C
Solar/Wind Helper
0.001
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
20676328BVR_Y1-020
Solar/Wind Helper
0.027
962761AG1-125 GEN
Solar/Wind Harmer
34.524
270462AD2-086
Solar/Wind Harmer
0.017
25326309TAIT D
Adder
1.196
241813AF1-122_GEN
Solar/Wind Harmer
3.405
247536S-71 GEN
Solar/Wind Harmer
0.297
252507AC2-088 GEN
Solar/Wind Harmer
0.335
270063AE2-323 C
Solar/Wind Harmer
0.006
970245AG2-165 GEN
Solar/Wind Harmer
3.191
944231AF1-091 GEN
Solar/Wind Harmer
1.953
276903AD2-071 C
Solar/Wind Harmer
8.137
958381AF2-132 GEN
Solar/Wind Harmer
0.001
274754CRETE EC ;4U
Adder
8.477
24385905FR-11G C
Solar/Wind Harmer
0.002
274732ELWOOD EC;7P
Adder
16.768
274674JOLIET 9 ;6U
Adder
15.704
939401AE1-172 GEN
Solar/Wind Harmer
5.301
238117U2-030
Solar/Wind Helper
0.341
238147AE2-230_GEN1
Solar/Wind Helper
0.495
235067AD1-061 GEN
Solar/Wind Helper
0.496
234015AF2-250 C
Solar/Wind Helper
0.038
316044AC1-158 PL1
Solar/Wind Helper
1.293
316450AC1-158 RIC
Solar/Wind Helper
0.345
219276PARKLANDSO C
Solar/Wind Helper
0.089
20720528MAN_W1-024
Solar/Wind Helper
0.028
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
NYPJM->LTFIMP_NY
CLTF
4.797
LGEELTFEXP_LGEE->PJM
CLTF
6.749
WECLTFEXP_WEC->PJM
CLTF
3.825
AG2-052LTFEXP_AG2-052->PJM
LTF
0.24
AH1-155LTFEXP_AH1-155->PJM
LTF
0.359
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.078
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.1
MECLTFEXP_MEC->PJM
CLTF
15.901
SIGELTFEXP_SIGE->PJM
CLTF
0.505
LAGNLTFEXP_LAGN->PJM
CLTF
14.837
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.802
TVALTFEXP_TVA->PJM
CLTF
7.293
CPLELTFEXP_CPLE->PJM
CLTF
0.624
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.816

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-008A_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-008A_SRT-SL
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:124.1 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4627.6
MW Contribution:1.08
Bus #Bus NameTypeMW Contribution
970155AG2-107 GEN
Solar/Wind Harmer
21.245
270349AD2-093_GEN
Solar/Wind Harmer
0.006
942861AE2-305 GEN
Solar/Wind Harmer
6.118
270518AE2-148 GEN
Solar/Wind Harmer
0.667
972159AH1-661 GEN
Adder
1.082
970329AG2-216 GEN
Solar/Wind Harmer
3.237
971199AH1-059 GEN
Solar/Wind Harmer
2.99
241960AC2-195 GEN
Solar/Wind Harmer
0.006
971073AG2-665 GEN
Solar/Wind Harmer
6.645
25326109MON D
Adder
1.391
971231AH1-075 GEN
Solar/Wind Harmer
0.833
25183208HLCRTG
Solar/Wind Harmer
0.011
944541AF1-119 GEN
Solar/Wind Harmer
0.479
970885AG2-551 GEN
Solar/Wind Harmer
2.374
270201AC2-176 GEN
Solar/Wind Harmer
0.001
25194508D.CRK3
Adder
1.442
964611AG1-324 GEN
Solar/Wind Harmer
0.534
252509AD1-136 GEN
Solar/Wind Harmer
0.036
270031AE2-169
Solar/Wind Harmer
3.897
270383AD1-128 GEN
Solar/Wind Harmer
0.004
247620Y3-023
Adder
0.466
24379505HDWTR1G C
Solar/Wind Harmer
0.002
960441AF2-335 GEN
Solar/Wind Harmer
7.065
24728805RICHG1
Adder
3.82
270526AF1-158 GEN
Solar/Wind Harmer
0.009
24441505OLIV SLR
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
6.431
945421AF1-207 GEN
Solar/Wind Harmer
0.001
276843GEN-1.7
Solar/Wind Harmer
0.223
958011AF2-095 GEN
Solar/Wind Harmer
9.913
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
971573AH1-285 GEN
Solar/Wind Harmer
1.271
958491AF2-143 GEN
Solar/Wind Harmer
10.205
237034AC2-136 C
Solar/Wind Helper
0.219
235063AE1-101 C2
Solar/Wind Helper
1.6
237001AB1-127_GEN
Solar/Wind Helper
0.426
226929AD2-058 GEN
Solar/Wind Helper
0.096
233987AB2-037 GEN
Solar/Wind Helper
2.264
234036AF2-325 C
Solar/Wind Helper
0.041
233901CHERRYDALE C
Solar/Wind Helper
0.225
20720628TIN_W1-124
Solar/Wind Helper
0.183
23559001PLEAS1
50/50
5.385
961921AG1-034 GEN
Solar/Wind Harmer
7.364
942051AE2-217 GEN
Solar/Wind Harmer
14.169
970605AG2-385 GEN
Solar/Wind Harmer
4.731
270391AF1-285 GEN3
Solar/Wind Harmer
0.518
253333AC1-068 GEN
Solar/Wind Harmer
0.012
270273AD2-016 GEN
Solar/Wind Harmer
0.792
270291AC1-194 GEN
Solar/Wind Harmer
5.884
253415AE1-040 GEN
Solar/Wind Harmer
0.003
253406AD2-031_GEN
Solar/Wind Harmer
0.543
270120AB2-067 GEN2
50/50
6.869
270224U2-072_GEN2
Solar/Wind Harmer
0.001
938701AE1-092 GEN
Solar/Wind Harmer
12.484
964601AG1-323 GEN
Solar/Wind Harmer
3.106
964601AG1-323 GEN
Solar/Wind Harmer
2.071
971201AH1-060 GEN
Solar/Wind Harmer
1.471
970627AG2-408 GEN
Solar/Wind Harmer
2.167
960971AF2-388 GEN
Solar/Wind Harmer
4.192
970883AG2-550 GEN
Solar/Wind Harmer
7.123
25194408D.CRK1
Adder
7.711
270599AE1-208 GEN
Solar/Wind Harmer
6.495
926881AC1-175 GEN
Solar/Wind Harmer
0.001
270216AD2-079_GEN
Solar/Wind Harmer
0.001
24728905RICHG2
Adder
3.82
961051AF2-396 GEN
Solar/Wind Harmer
14.072
961051AF2-396 GEN
Solar/Wind Harmer
9.381
966841AG1-555 GEN
Solar/Wind Harmer
0.781
274803UNIV PARK;6U
Adder
5.755
274887GEN-1.85
Solar/Wind Harmer
0.181
958481AF2-142 GEN
Solar/Wind Harmer
10.238
274862TOP CROP ;2U
Solar/Wind Harmer
0.923
274879MINONK ;1U
Solar/Wind Harmer
0.287
23777901MDS_W4-102
Solar/Wind Helper
0.171
23585401KL_K28_T16
Solar/Wind Helper
1.328
237002AB1-128_GEN
Solar/Wind Helper
0.427
237006AB1-125 GEN
Solar/Wind Helper
0.119
208835TUHI V3-051
Solar/Wind Helper
0.023
208835TUHI V3-051
Solar/Wind Helper
0.023
232424Y1-079 C
Solar/Wind Helper
0.112
233970AC1-092 C
Solar/Wind Helper
0.338
230433AD2-135 GEN
Solar/Wind Helper
0.016
219921AF1-264
Solar/Wind Helper
0.049
219615MILLCREEK C
Solar/Wind Helper
0.026
970153AG2-106 GEN
Solar/Wind Harmer
21.245
23559101PLEAS2
50/50
5.385
270122AB2-093 CT
50/50
3.689
970149AG2-104 GEN
Solar/Wind Harmer
35.932
270159DARBY CT4
Adder
9.89
970593AG2-378 GEN
Solar/Wind Harmer
1.75
270223U2-072_GEN1
Solar/Wind Harmer
0.001
253325AC1-069 GEN
Solar/Wind Harmer
0.012
270263AC1-001 GEN
Solar/Wind Harmer
0.758
270510AE1-227 GEN1
Solar/Wind Harmer
1.904
927014AC1-188 GEN
Solar/Wind Harmer
0.004
24318805MLG1
50/50
9.842
253338AC1-165 GEN
Solar/Wind Harmer
0.003
972173AH1-669 GEN
Solar/Wind Harmer
3.811
970191AG2-125 GEN
Solar/Wind Harmer
1.876
270491AE1-102 GEN2
Solar/Wind Harmer
0.945
270191TR4_S_V150
Solar/Wind Harmer
0.001
959331AF2-224 GEN
Solar/Wind Harmer
5.057
270258AD1-119 GEN
Solar/Wind Harmer
0.002
971617AH1-308 GEN
Solar/Wind Harmer
5.953
270222AC2-111 GEN
Solar/Wind Harmer
3.603
270004AE1-209 GEN
Solar/Wind Harmer
1.532
24642205MAYFLWER
Adder
0.641
270356AE2-297 GEN
Solar/Wind Harmer
0.009
970217AG2-149 GEN
Solar/Wind Harmer
6.066
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274753CRETE EC ;3U
Adder
8.172
972038AH1-567 GEN2
Adder
0.36
238148AE2-230_GEN2
Solar/Wind Helper
0.48
238118U2-030_1
Solar/Wind Helper
0.314
237038AE2-054 C
Solar/Wind Helper
0.262
23779801AA1-109
Solar/Wind Helper
0.187
316006AB2-029 C
Solar/Wind Helper
0.113
316045AC1-158 PL2
Solar/Wind Helper
4.009
219686LUMSOLAR_N C
Solar/Wind Helper
0.038
219304NAMERICA C
Solar/Wind Helper
0.127
207445AB1-138_GEN
Solar/Wind Helper
0.101
270119AB2-067 GEN1
50/50
6.869
970077AG2-063 GEN
Solar/Wind Harmer
4.471
972269AH1-719 GEN
Adder
2.501
253378AE2-206_GEN
Solar/Wind Harmer
0.004
25326509SID D
Adder
1.4
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
246938BC-WTG3
Solar/Wind Harmer
0.263
246937BC-WTG2
Solar/Wind Harmer
0.295
970611AG2-400 GEN
Solar/Wind Harmer
7.225
270007AE1-245 C
Solar/Wind Harmer
0.002
970623AG2-406 GEN
Solar/Wind Harmer
1.309
962581AG1-107 GEN
Solar/Wind Harmer
0.001
942221AE2-234 GEN
Solar/Wind Harmer
0.036
970621AG2-405 GEN
Solar/Wind Harmer
1.305
970321AG2-212 GEN
Solar/Wind Harmer
3.076
270186AC1-089 GEN
Solar/Wind Harmer
0.004
270209AC1-174_GEN
Solar/Wind Harmer
0.001
970825AG2-519 GEN
Solar/Wind Harmer
7.834
957891AF2-083 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
970239AG2-162 GEN
Solar/Wind Harmer
1.73
972239AH1-704 GEN
50/50
2.78
961821AG1-024 GEN
Solar/Wind Harmer
4.91
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
945631AF1-228 GEN
Solar/Wind Harmer
0
270578AF1-285 GEN2
Solar/Wind Harmer
0.518
270432AC2-029 GEN
Solar/Wind Harmer
3.428
270269AC2-059
Solar/Wind Harmer
0.004
241972AD1-140 GEN
Solar/Wind Harmer
0.824
270340AC2-060 GEN
Solar/Wind Harmer
0.009
253400AC2-068 GEN
Solar/Wind Harmer
0.923
965041AG1-368 GEN
Solar/Wind Harmer
7.21
965101AG1-375 GEN
Solar/Wind Harmer
7.135
270297AD1-101 GEN
Solar/Wind Harmer
0.002
25196508WSDLE4
Adder
8.656
971609AH1-304 GEN
Solar/Wind Harmer
1.157
970115AG2-085 GEN
Solar/Wind Harmer
2.826
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
274776LINCOLN ;7U
Adder
8.364
274814UNIV PK N;0U
Adder
4.998
274807UNIV PK N;3U
Adder
4.987
274805UNIV PK N;1U
Adder
4.965
24386205FR-12G C
Solar/Wind Harmer
0.001
963841AG1-237 GEN
Solar/Wind Harmer
2.978
274687WILL CNTY;4U
Adder
27.495
274687WILL CNTY;4U
Adder
27.495
972163AH1-664 GEN
Solar/Wind Harmer
7.639
274731ELWOOD EC;2P
Adder
16.163
274733ELWOOD EC;3P
Adder
16.163
276882AE2-255 GEN
Solar/Wind Harmer
0.794
238152AF2-075_GEN
Solar/Wind Helper
0.683
23546401DTGZ2-030
Solar/Wind Helper
0.086
3138216PACIFIC
Solar/Wind Helper
0.043
23750501ELLIOTTS
Solar/Wind Helper
0.571
205956AE1-196_GEN
Solar/Wind Helper
0.492
233935AB2-179 C
Solar/Wind Helper
1.227
232436AB1-176 C
Solar/Wind Helper
0.043
233923SMA
Solar/Wind Helper
0.927
219914AD2-027 C
Solar/Wind Helper
0.111
219607WPEMNERT C
Solar/Wind Helper
0.077
20715728PEM_W1-119
Solar/Wind Helper
0.093
316164AC1-076 GEN
Solar/Wind Helper
1.062
270166AC1-044 GEN3
50/50
6.869
246936BC-WTG1
Solar/Wind Harmer
0.295
270489AE1-102 GEN1
Solar/Wind Harmer
0.945
965011AG1-365 GEN
Solar/Wind Harmer
7.225
958861AF2-177 GEN
Solar/Wind Harmer
3.092
945371AF1-202 GEN
Solar/Wind Harmer
0.001
270005AE1-210 C O1
Solar/Wind Harmer
1.532
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
2.509
25196808ZIMRHP
Adder
76.799
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
270032AE2-172
Solar/Wind Harmer
4.701
945111AF1-176 GEN
Solar/Wind Harmer
12.568
270505AE1-170 C O1
Solar/Wind Harmer
7.393
247522W1-056 GEN
Solar/Wind Harmer
0.001
25196008MFTGT1
Adder
1.397
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.706
270051AF1-062 GEN
50/50
11.434
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270512AE1-227 GEN2
Solar/Wind Harmer
1.904
970065AG2-057 GEN
Solar/Wind Harmer
0.735
965021AG1-366 GEN
Solar/Wind Harmer
2.408
971191AH1-055 GEN
Solar/Wind Harmer
18.515
270043AE2-236 GEN
Solar/Wind Harmer
4.607
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
10.684
252510AF1-249 C
Solar/Wind Harmer
0.055
945111AF1-176 GEN
Solar/Wind Harmer
5.709
24441205WTRV SLR C
Solar/Wind Harmer
0
25196008MFTGT1
Adder
1.353
970243AG2-164 GEN
Solar/Wind Harmer
4.047
274772LINCOLN ;3U
Adder
8.364
274724RIVER EC ;11
Adder
17.549
274802UNIV PARK;5U
Adder
5.755
970941AG2-585 GEN
Solar/Wind Harmer
8.605
274800UNIV PARK;3U
Adder
5.751
972167AH1-666 GEN
Solar/Wind Harmer
5.505
276897AD1-100 C
Solar/Wind Harmer
0.009
274729ELWOOD EC;1P
Adder
16.163
276893AG1-478 C
Solar/Wind Harmer
0.272
276805AD2-038 GEN
Solar/Wind Harmer
0.002
237048AF1-022 C
Solar/Wind Helper
0.159
233930AB2-032 GEN
Solar/Wind Helper
0.368
233954AC2-188 GEN
Solar/Wind Helper
0.225
230511AF1-262
Solar/Wind Helper
0.014
230434AG1-499 GEN
Solar/Wind Helper
0.222
219258KINSLEYDEP C
Solar/Wind Helper
0.074
219907AC1-030 C
Solar/Wind Helper
0.033
274770LINCOLN ;1U
Adder
8.364
274771LINCOLN ;2U
Adder
8.364
274808UNIV PK N;4U
Adder
4.933
274888KELLY CRK;1U
Solar/Wind Harmer
0.404
972259AH1-714 GEN
Adder
18.805
970241AG2-163 GEN
Solar/Wind Harmer
3.993
238175AF1-290_GEN
Solar/Wind Helper
0.148
235020AA1-095 C
Solar/Wind Helper
0.051
205916AD1-020 GEN
Solar/Wind Helper
1.656
20390526W1-045 C
Solar/Wind Helper
0.338
233933AB2-153 GEN
Solar/Wind Helper
0.225
233944AB2-135 GEN
Solar/Wind Helper
0.569
233946AB2-136 GEN
Solar/Wind Helper
0.549
232408W1-005 C
Solar/Wind Helper
0.49
232410W1-006 C
Solar/Wind Helper
0.49
233939AC1-091 C
Solar/Wind Helper
0.338
963401AG1-189 GEN
Solar/Wind Helper
0.054
963391AG1-188 GEN
Solar/Wind Helper
0.079
270459AD2-067 GEN
Solar/Wind Harmer
0
270156DARBY CT1
Adder
10.05
270157DARBY CT2
Adder
10.026
940611AE2-048 GEN
Solar/Wind Harmer
18.967
941391AE2-136 GEN
Solar/Wind Harmer
10.684
970879AG2-548 GEN
Solar/Wind Harmer
6.645
270435AC2-044 GEN
Solar/Wind Harmer
0.92
971567AH1-282 GEN
Solar/Wind Harmer
10.843
247607V1-011 GEN
Solar/Wind Harmer
0.001
24729505KEY G4
Adder
6.671
270071AF1-092 GEN
Solar/Wind Harmer
13.737
270367AC2-061_GEN
Solar/Wind Harmer
0.006
971673AH1-337 GEN
Solar/Wind Harmer
4.631
270543AE2-219 C
Solar/Wind Harmer
0.004
25196408WSDLE3
Adder
9.002
25196308WSDLE2
Adder
8.924
25196208WSDLE1
Adder
8.902
25196708WSDLE6
Adder
8.879
270240V3-007_GEN2
Solar/Wind Harmer
0.002
270594AE1-207 GEN
Solar/Wind Harmer
7.898
971771AH1-392 GEN
Solar/Wind Harmer
7.046
971769AH1-391 GEN
Solar/Wind Harmer
7.844
25196108MFTGT2
Adder
1.54
25196108MFTGT2
Adder
1.43
971549AH1-272 GEN
Solar/Wind Harmer
14.344
24691005MDL-2G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
274728ELWOOD EC;5P
Adder
16.163
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
238126S14_GEN_1
Solar/Wind Helper
0.766
237085AD2-009_GEN
Solar/Wind Helper
1.588
316411AF1-147_GEN1
Solar/Wind Helper
0.86
316415AF1-147_GEN2
Solar/Wind Helper
0.86
3141426STAFORD
Solar/Wind Helper
0.051
228754AB1-001 C
Solar/Wind Helper
0.025
219272CLEANLIGHT C
Solar/Wind Helper
0.025
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
943021AE2-325 GEN
Solar/Wind Harmer
3.67
970773AG2-487 GEN
Solar/Wind Harmer
1.237
970373AG2-245 GEN
Solar/Wind Harmer
14.699
970515AG2-329 GEN
Solar/Wind Harmer
18.197
971917AH1-482 GEN
Solar/Wind Harmer
9.071
24791305MDL-5G
Solar/Wind Harmer
0.001
941551AE2-152 GEN
Solar/Wind Harmer
0.001
963741AG1-226 GEN
Solar/Wind Harmer
16.202
276691AA1-018 GEN1
Solar/Wind Harmer
0.827
238108AE1-109 GEN1
Solar/Wind Helper
0.106
235531U2-073 GEN
Solar/Wind Helper
3.034
235054AD2-180 GEN
Solar/Wind Helper
1.839
23562501BACKB
Solar/Wind Helper
0.842
205917AD1-020 ES
Solar/Wind Helper
0.356
233918AB1-142 GEN
Solar/Wind Helper
0.486
233994AC2-023 GEN
Solar/Wind Helper
0.929
233997TMININ_4.2
Solar/Wind Helper
0.253
233971AC1-093 C
Solar/Wind Helper
0.346
228729W2-030 C
Solar/Wind Helper
0.107
219348LDSOLAR C
Solar/Wind Helper
0.111
316170AC1-121 GEN2
Solar/Wind Helper
0.342
959561AF2-247 GEN
Solar/Wind Helper
0.02
20715028HAN_X4-015
Solar/Wind Helper
0.055
270054AF2-122 C O1
Solar/Wind Harmer
0.007
270520AE2-214 GEN
Solar/Wind Harmer
0.013
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
270158DARBY CT3
Adder
9.866
270317AD1-130_GEN
Solar/Wind Harmer
0.011
253349AC2-067 GEN
Solar/Wind Harmer
2.296
965051AG1-369 GEN
Solar/Wind Harmer
3.609
971985AH1-537 GEN
Solar/Wind Harmer
2.123
971029AG2-637 GEN
Solar/Wind Harmer
10.686
945581AF1-223 GEN
Solar/Wind Harmer
0.001
971347AH1-153 GEN
Solar/Wind Harmer
10.632
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
971619AH1-309 GEN
Solar/Wind Harmer
3.169
24725505WLD G2 C
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
4.146
24697605MDL-3G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
8.364
274777LINCOLN ;8U
Adder
8.364
24386405FR-21G C
Solar/Wind Harmer
0.001
972037AH1-567 GEN1
Adder
0.181
960591AF2-350 GEN
Solar/Wind Harmer
6.884
274675JOLIET 29;7U
Adder
30.175
274675JOLIET 29;7U
Adder
29.097
972165AH1-665 GEN
Solar/Wind Harmer
6.118
970833AG2-524 GEN
Solar/Wind Harmer
7.542
970833AG2-524 GEN
Solar/Wind Harmer
5.028
945641AF1-229 GEN
Solar/Wind Harmer
0.001
276868AE1-113 GEN
Solar/Wind Harmer
1.363
238208AF1-136 C
Solar/Wind Helper
0.211
205943AE1-185 GEN
Solar/Wind Helper
0.492
233990AG1-397 GEN
Solar/Wind Helper
0.261
964001AG1-254 GEN
Solar/Wind Helper
0.924
227927V4-067C
Solar/Wind Helper
0.01
219688LUMSOLAR_S C
Solar/Wind Helper
0.038
214067T20SOLAR
Solar/Wind Helper
0.011
20715828PEM_W1-120
Solar/Wind Helper
0.093
207459AE1-142 C O1
Solar/Wind Helper
0.28
219620RIDERU C
Solar/Wind Helper
0.001
24318905MLG2
50/50
6.89
270471AD2-092_GEN
Solar/Wind Harmer
0.006
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
971655AH1-328 GEN
Solar/Wind Harmer
2.758
276820AF1-078_GEN
Solar/Wind Harmer
0.002
970935AG2-582 GEN
Adder
242.403
25322209TAIT E
Adder
10.262
25322209TAIT E
Adder
10.031
253370AE2-315 SEC1
Adder
2.103
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
252519AF1-045_GEN
Solar/Wind Harmer
6.204
252516AE2-318_GEN
Solar/Wind Harmer
5.503
247621Y3-024
Adder
0.246
971613AH1-306 GEN
Solar/Wind Harmer
3.385
965681AG1-436 GEN
Solar/Wind Harmer
8.77
241955AC1-078 GEN
Solar/Wind Harmer
0.007
241974AD2-163_GEN2
Solar/Wind Harmer
0.006
24721905FLATG4
Adder
22.865
253370AE2-315 SEC1
Adder
2.103
253371AE2-315 SEC2
Adder
1.989
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
9.394
270588AE1-091_GEN
Solar/Wind Harmer
5.649
25194608D.CRK4
Adder
1.676
946031AF1-268 GEN
Solar/Wind Harmer
6.74
247643Z2-116 C
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.775
970291AG2-192 GEN
Solar/Wind Harmer
0.705
247642Z2-115 C
Solar/Wind Harmer
0.003
270535AF1-215 GEN1
Solar/Wind Harmer
0.009
24755605MDL-5G
Solar/Wind Harmer
0.001
276806AD2-047 C O1
Solar/Wind Harmer
3.901
24728505AND G1
Adder
3.784
274676JOLIET 29;8U
Adder
29.097
943121AE2-341 GEN
Solar/Wind Harmer
11.459
943591AF1-030 GEN
Solar/Wind Harmer
7.62
964991AG1-363 GEN
Solar/Wind Helper
4.969
316097T157 G90
Solar/Wind Helper
1.455
237080AD1-060 GEN
Solar/Wind Helper
0.33
966131AG1-482 GEN
Solar/Wind Helper
0.132
232422X3-066 FULL
Solar/Wind Helper
0.11
232426Y1-080 FULL
Solar/Wind Helper
0.038
233964AF2-378 GEN
Solar/Wind Helper
0.04
232434Z2-077 GEN
Solar/Wind Helper
0.123
219904AC1-010 C
Solar/Wind Helper
0.058
20720728JCB_W1-129
Solar/Wind Helper
0.055
20714828MDF_W3-079
Solar/Wind Helper
0.126
219680HOPEWELLV C1
Solar/Wind Helper
0.003
970333AG2-219 GEN
Solar/Wind Harmer
4.947
274751CRETE EC ;1U
Adder
8.172
274773LINCOLN ;4U
Adder
8.364
274774LINCOLN ;5U
Adder
8.364
274723RIVER EC ;12
Adder
17.756
24387305FR-4G C
Solar/Wind Harmer
0.003
274801UNIV PARK;4U
Adder
5.751
23583801GRNGAP
Solar/Wind Helper
5.418
238149AF1-291A_GEN
Solar/Wind Helper
0.137
237061AD1-155 GEN
Solar/Wind Helper
0.051
238221AF1-254 C O1
Solar/Wind Helper
0.265
3141196NOKESVL
Solar/Wind Helper
0.999
226910AB2-157 C
Solar/Wind Helper
0.014
223402AF1-300 C
Solar/Wind Helper
0.355
23751201ROTHROCK
Solar/Wind Helper
0.694
233982AB2-133 GEN
Solar/Wind Helper
0.346
233940AF2-379 C
Solar/Wind Helper
0.06
233952AC2-187 GEN
Solar/Wind Helper
0.225
219623KINSLEYBEA C
Solar/Wind Helper
0.002
20716028EGP_W2-019
Solar/Wind Helper
0.018
971997AH1-543 GEN
Solar/Wind Harmer
1.86
962761AG1-125 GEN
Solar/Wind Harmer
33.269
270462AD2-086
Solar/Wind Harmer
0.016
241813AF1-122_GEN
Solar/Wind Harmer
3.294
25326309TAIT D
Adder
1.153
247536S-71 GEN
Solar/Wind Harmer
0.287
270063AE2-323 C
Solar/Wind Harmer
0.006
252507AC2-088 GEN
Solar/Wind Harmer
0.323
970245AG2-165 GEN
Solar/Wind Harmer
3.076
944231AF1-091 GEN
Solar/Wind Harmer
1.885
276903AD2-071 C
Solar/Wind Harmer
7.842
958381AF2-132 GEN
Solar/Wind Harmer
0.001
274754CRETE EC ;4U
Adder
8.172
24385905FR-11G C
Solar/Wind Harmer
0.002
939401AE1-172 GEN
Solar/Wind Harmer
5.109
238147AE2-230_GEN1
Solar/Wind Helper
0.478
238117U2-030
Solar/Wind Helper
0.314
235067AD1-061 GEN
Solar/Wind Helper
0.478
234015AF2-250 C
Solar/Wind Helper
0.037
316044AC1-158 PL1
Solar/Wind Helper
1.252
316450AC1-158 RIC
Solar/Wind Helper
0.334
219276PARKLANDSO C
Solar/Wind Helper
0.086
20720528MAN_W1-024
Solar/Wind Helper
0.027
270377AD1-106 GEN
Solar/Wind Harmer
2.761
270247TR4_N_V136
Solar/Wind Harmer
0.047
944531AF1-118 GEN
Solar/Wind Harmer
32.203
270404AC1-167 GEN
Solar/Wind Harmer
0.003
25196608WSDLE5
Adder
8.745
970031AG2-029 GEN
Solar/Wind Harmer
4.625
970513AG2-328 GEN
Solar/Wind Harmer
3.076
970517AG2-330 GEN
Solar/Wind Harmer
18.457
970349AG2-230 GEN
Solar/Wind Harmer
10.632
958821AF2-173 GEN
Solar/Wind Harmer
9.902
270437AC2-090 C
Solar/Wind Harmer
0.003
247604X1-042
Adder
0.418
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
970781AG2-491 GEN
Solar/Wind Harmer
6.935
970519AG2-331 GEN
Solar/Wind Harmer
17.988
970699AG2-449 GEN
Solar/Wind Harmer
1.73
274752CRETE EC ;2U
Adder
8.172
958171AF2-111 GEN
Solar/Wind Harmer
17.278
274826FISK ;BP
Adder
10.802
24728705AND G3
Adder
7.914
972228AH1-698 GEN2
Adder
3.654
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
22.464
274730ELWOOD EC;6P
Adder
13.491
270541AE2-072 C
Solar/Wind Harmer
0.009
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
23750701CROSSCHOOL
Solar/Wind Helper
1.397
238127S14_GEN_2
Solar/Wind Helper
0.766
235062AE1-101 C1
Solar/Wind Helper
1.6
223401AF1-299 GEN
Solar/Wind Helper
0.355
233915AB1-141 GEN
Solar/Wind Helper
0.486
233998TM1NIN_3.36
Solar/Wind Helper
0.253
232404W1-003 C
Solar/Wind Helper
0.49
232428Y3-058 C
Solar/Wind Helper
0.327
233950AC2-186 GEN
Solar/Wind Helper
0.112
233972AC1-094 C
Solar/Wind Helper
0.292
228728W1-130C
Solar/Wind Helper
0.052
218660EHAMPSOLAR C
Solar/Wind Helper
0.032
316254AC1-120 GEN1
Solar/Wind Helper
1.026
963711AG1-223 GEN
Solar/Wind Helper
0.062
207454AA2-184 E
Solar/Wind Helper
0.299
20715228NPK_W1-113
Solar/Wind Helper
0.075
962771AG1-126 GEN
Solar/Wind Harmer
33.269
270284AF1-227 GEN1
Solar/Wind Harmer
0.01
253383AE2-342_GEN
Solar/Wind Harmer
0.003
241973AD2-163_GEN1
Solar/Wind Harmer
0.006
943861AF1-054 GEN
Solar/Wind Harmer
3.02
943851AF1-053 GEN
Solar/Wind Harmer
2.092
970689AG2-444 GEN
Solar/Wind Harmer
15.861
270302AB2-170 GEN
Solar/Wind Harmer
0.005
971653AH1-327 GEN
Solar/Wind Harmer
1.08
970179AG2-119 GEN
Solar/Wind Harmer
6.658
253372AE2-315 SEC3
Adder
1.989
253372AE2-315 SEC3
Adder
1.989
25306009OHH W.
Adder
3.018
957201AF2-014 GEN
Solar/Wind Harmer
0.001
971989AH1-539 GEN
Solar/Wind Harmer
3.109
963791AG1-232 GEN
Solar/Wind Harmer
9.689
270024AE2-089 GEN
Solar/Wind Harmer
0.008
252524AE2-267 GEN
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
1.339
270536AF1-215 GEN2
Solar/Wind Harmer
0.009
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274811UNIV PK N;7U
Adder
4.954
274827FISK ;RP
Adder
7.655
972227AH1-698 GEN1
Adder
2.573
274735ELWOOD EC;4P
Adder
16.163
238109AE1-109 GEN2
Solar/Wind Helper
0.106
238110AE1-109 GEN3
Solar/Wind Helper
0.106
959381AF2-229 GEN
Solar/Wind Helper
0.345
960921AF2-383 GEN
Solar/Wind Helper
0.352
205932AD2-116_GEN
Solar/Wind Helper
0.492
234033AF1-007_GEN
Solar/Wind Helper
6.787
232432Z2-076 GEN
Solar/Wind Helper
0.065
203975AE1-071-GEN
Solar/Wind Helper
2.41
24721705FLATG2
Adder
22.865
253343AC1-166 GEN
Solar/Wind Harmer
0.003
971995AH1-542 GEN
Solar/Wind Harmer
2.81
960071AF2-298 GEN
Solar/Wind Harmer
3.651
253370AE2-315 SEC1
Adder
2.103
253371AE2-315 SEC2
Adder
1.989
965421AG1-410 GEN
Solar/Wind Harmer
21.788
247521TR3_G114
Solar/Wind Harmer
0.263
270246TR4_N_V150
Solar/Wind Harmer
0.047
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.226
24695305TIMB G C
Solar/Wind Harmer
0.002
965651AG1-433 GEN
Solar/Wind Harmer
2.096
25194608D.CRK4
Adder
1.676
965031AG1-367 GEN
Solar/Wind Harmer
7.073
970947AG2-589 GEN
Solar/Wind Harmer
0.236
970613AG2-401 GEN
Solar/Wind Harmer
5.183
24639705ELKHART HY
Adder
0.155
970291AG2-192 GEN
Solar/Wind Harmer
0.916
270449AD2-020 GEN
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0.005
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.954
276776AD2-060 GEN
Solar/Wind Harmer
0.719
24728605AND G2
Adder
3.784
945681AF1-233 GEN
Solar/Wind Harmer
12.962
274676JOLIET 29;8U
Adder
30.175
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
276901AD2-066 C O1
Solar/Wind Harmer
0.007
316095T157 G97
Solar/Wind Helper
1.455
238185AF2-356 C
Solar/Wind Helper
2.425
237030AB1-096 C
Solar/Wind Helper
0.068
227287AC2-120 GEN
Solar/Wind Helper
0.335
233996TM1833_GEN
Solar/Wind Helper
0.253
232406W1-004 FULL
Solar/Wind Helper
0.49
230430AE1-229_GEN
Solar/Wind Helper
3.26
230415AB2-049 C
Solar/Wind Helper
0.029
219766PARADISE C
Solar/Wind Helper
0.053
219912AD2-042 GEN
Solar/Wind Helper
0.145
219291REEVESSOUT C
Solar/Wind Helper
0.011
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.04
20720828JCB_W4-025
Solar/Wind Helper
0.061
20714528FRN_Y2-051
Solar/Wind Helper
0.055
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
971677AH1-339 GEN
Solar/Wind Harmer
0.768
238169AE2-226 GEN1
Solar/Wind Helper
0.677
238170AE2-226 GEN2
Solar/Wind Helper
0.677
238120AE2-309 GEN
Solar/Wind Helper
0.487
23777801MSM_W1-116
Solar/Wind Helper
0.11
237025AB1-124 C
Solar/Wind Helper
0.159
315651AD1-115 GEN
Solar/Wind Helper
0.76
316447AC1-158 HLD
Solar/Wind Helper
2.756
230407AD2-065 C
Solar/Wind Helper
0.039
20714928UPF_X1-085
Solar/Wind Helper
0.005
NYPJM->LTFIMP_NY
CLTF
4.628
LGEELTFEXP_LGEE->PJM
CLTF
6.497
WECLTFEXP_WEC->PJM
CLTF
3.686
AG2-052LTFEXP_AG2-052->PJM
LTF
0.231
AH1-155LTFEXP_AH1-155->PJM
LTF
0.346
CBM West 1LTFEXP_CBM-W1->PJM
CBM
137.982
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.984
MECLTFEXP_MEC->PJM
CLTF
15.319
SIGELTFEXP_SIGE->PJM
CLTF
0.486
LAGNLTFEXP_LAGN->PJM
CLTF
14.268
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.432
TVALTFEXP_TVA->PJM
CLTF
7.011
CPLELTFEXP_CPLE->PJM
CLTF
0.567
CBM West 2LTFEXP_CBM-W2->PJM
CBM
108.576

Details for 02BAY SH-02DAV-BE 345.0 kV Ckt 1 line l/o ATSI_P1-2_TE-345-602_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_TE-345-602_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:142.52 %
Rating:1683.0 MVA
Rating Type:B
MVA to Mitigate:2398.59
MW Contribution:0.58
Bus #Bus NameTypeMW Contribution
270541AE2-072 C
Solar/Wind Harmer
0.008
247604X1-042
Adder
0.303
270404AC1-167 GEN
Solar/Wind Harmer
0.002
970031AG2-029 GEN
Solar/Wind Harmer
2.866
270247TR4_N_V136
Solar/Wind Harmer
0.028
970349AG2-230 GEN
Solar/Wind Harmer
6.147
270391AF1-285 GEN3
Solar/Wind Harmer
0.256
274752CRETE EC ;2U
Adder
4.532
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
274826FISK ;BP
Adder
5.877
972228AH1-698 GEN2
Adder
1.977
939351AE1-166 GEN
Solar/Wind Harmer
0
274730ELWOOD EC;6P
Adder
8.714
970707AG2-453 GEN
Solar/Wind Harmer
12.079
970513AG2-328 GEN
Solar/Wind Harmer
1.596
970517AG2-330 GEN
Solar/Wind Harmer
9.577
276694AA1-018 GEN2
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.599
274855GSG-6 ;RU
Solar/Wind Harmer
0.131
944531AF1-118 GEN
Solar/Wind Harmer
16.023
274853TWINGROVE;U1
Solar/Wind Harmer
0.001
959611AF2-252 GEN
Solar/Wind Harmer
1.144
270377AD1-106 GEN
Solar/Wind Harmer
1.25
958821AF2-173 GEN
Solar/Wind Harmer
4.521
254305AE2-115 C
Solar/Wind Helper
0.114
24189802OREGON_CT1
50/50
4.21
961051AF2-396 GEN
Solar/Wind Harmer
9.384
961051AF2-396 GEN
Solar/Wind Harmer
6.256
270216AD2-079_GEN
Solar/Wind Harmer
0.001
970627AG2-408 GEN
Solar/Wind Harmer
1.276
270224U2-072_GEN2
Solar/Wind Harmer
0
274803UNIV PARK;6U
Adder
3.135
274887GEN-1.85
Solar/Wind Harmer
0.098
274674JOLIET 9 ;6U
Adder
8.161
958481AF2-142 GEN
Solar/Wind Harmer
5.485
274862TOP CROP ;2U
Solar/Wind Harmer
0.495
274693ROCKY RD ;1P
Adder
5.742
274683WAUKEGAN ;8U
Adder
10.969
274683WAUKEGAN ;8U
Adder
9.246
274879MINONK ;1U
Solar/Wind Harmer
0.152
970921AG2-575 GEN
Solar/Wind Harmer
3.608
970921AG2-575 GEN
Solar/Wind Harmer
1.203
971335AH1-147 GEN
Solar/Wind Harmer
7.161
274764LEE CO EC;5U
Adder
4.704
966841AG1-555 GEN
Solar/Wind Harmer
0.397
276708O09 GEN2
Solar/Wind Harmer
0.124
276782AC1-033 GEN
Solar/Wind Harmer
0.001
960971AF2-388 GEN
Solar/Wind Harmer
2.024
960611AF2-352 GEN
Solar/Wind Harmer
1.144
270599AE1-208 GEN
Solar/Wind Harmer
3.085
203947AF1-006 C
Solar/Wind Helper
0.391
241967AE2-285_GEN
Solar/Wind Helper
0.345
23888802TROY G4
50/50
1.526
247620Y3-023
Adder
0.296
270526AF1-158 GEN
Solar/Wind Harmer
0.005
24441505OLIV SLR
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
3.778
276843GEN-1.7
Solar/Wind Harmer
0.121
958011AF2-095 GEN
Solar/Wind Harmer
5.377
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
971573AH1-285 GEN
Solar/Wind Harmer
0.679
945421AF1-207 GEN
Solar/Wind Harmer
0
274695ROCKY RD ;2P
Adder
5.799
958491AF2-143 GEN
Solar/Wind Harmer
5.438
942991AE2-321 GEN
Solar/Wind Harmer
4.013
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
971333AH1-146 GEN
Solar/Wind Harmer
7.161
274765LEE CO EC;6U
Adder
4.704
274763LEE CO EC;4U
Adder
4.649
274851PROVIDENC;RU
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
0.137
944541AF1-119 GEN
Solar/Wind Harmer
0.231
270201AC2-176 GEN
Solar/Wind Harmer
0.001
270031AE2-169
Solar/Wind Harmer
1.851
964611AG1-324 GEN
Solar/Wind Harmer
0.251
971231AH1-075 GEN
Solar/Wind Harmer
0.377
960441AF2-335 GEN
Solar/Wind Harmer
3.255
946381AF1-302 GEN
Solar/Wind Helper
0.105
238217AF1-153 C O1
Solar/Wind Helper
0.111
23929302BS-PKR
50/50
2.775
958321AF2-126 GEN
Solar/Wind Harmer
1.136
270575GUS2 35KV
Solar/Wind Harmer
4.521
970217AG2-149 GEN
Solar/Wind Harmer
4.693
270258AD1-119 GEN
Solar/Wind Harmer
0.001
270491AE1-102 GEN2
Solar/Wind Harmer
0.603
24642205MAYFLWER
Adder
0.41
270191TR4_S_V150
Solar/Wind Harmer
0.001
959331AF2-224 GEN
Solar/Wind Harmer
2.976
274753CRETE EC ;3U
Adder
4.532
964401AG1-302 GEN
Solar/Wind Harmer
0.001
972038AH1-567 GEN2
Adder
0.196
274872LEEDK;1U
Solar/Wind Harmer
0.132
971617AH1-308 GEN
Solar/Wind Harmer
2.996
972236AH1-702 GEN2
Adder
1.116
274760LEE CO EC;1U
Adder
4.693
274878BISHOP HL;2U
Solar/Wind Harmer
0.117
965091AG1-374 GEN
Solar/Wind Harmer
10.299
965931AG1-462 GEN
Solar/Wind Harmer
8.719
276686W4-005 GEN3
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
0.7
962511AG1-100 GEN
Solar/Wind Helper
0.35
959441AF2-235 GEN
Solar/Wind Helper
0.15
20334926Z1-069 C
Solar/Wind Helper
0.646
241996AE2-282_GEN
Solar/Wind Harmer
0.006
970621AG2-405 GEN
Solar/Wind Harmer
0.944
970623AG2-406 GEN
Solar/Wind Harmer
0.885
246938BC-WTG3
Solar/Wind Harmer
0.168
246937BC-WTG2
Solar/Wind Harmer
0.188
957891AF2-083 GEN
Solar/Wind Harmer
0.001
270007AE1-245 C
Solar/Wind Harmer
0.001
970611AG2-400 GEN
Solar/Wind Harmer
4.252
274808UNIV PK N;4U
Adder
2.71
274888KELLY CRK;1U
Solar/Wind Harmer
0.219
274770LINCOLN ;1U
Adder
4.515
274771LINCOLN ;2U
Adder
4.515
972259AH1-714 GEN
Adder
10.138
970321AG2-212 GEN
Solar/Wind Harmer
1.596
942221AE2-234 GEN
Solar/Wind Harmer
0.018
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
274696ROCKY RD ;4P
Adder
5.936
274697ROCKY RD ;3P
Adder
1.575
962691AG1-118 GEN
Solar/Wind Harmer
10.84
274856ECOGROVE ;U1
Solar/Wind Harmer
0.084
276611AD2-172 GEN
Solar/Wind Harmer
0.001
938861AE1-114 GEN
Solar/Wind Harmer
1.999
274762LEE CO EC;3U
Adder
4.693
276603SUBLETTE C
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.137
970241AG2-163 GEN
Solar/Wind Harmer
1.972
970825AG2-519 GEN
Solar/Wind Harmer
3.6
241985AE1-237 GEN
Solar/Wind Helper
0.134
962101AG1-054 GEN
Solar/Wind Helper
0.332
241832AE2-181_GEN
Solar/Wind Harmer
0.004
24441205WTRV SLR C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
3.748
965021AG1-366 GEN
Solar/Wind Harmer
1.417
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270043AE2-236 GEN
Solar/Wind Harmer
2.609
274724RIVER EC ;11
Adder
9.666
274802UNIV PARK;5U
Adder
3.135
274800UNIV PARK;3U
Adder
3.125
970941AG2-585 GEN
Solar/Wind Harmer
4.668
274772LINCOLN ;3U
Adder
4.515
276897AD1-100 C
Solar/Wind Harmer
0.005
276893AG1-478 C
Solar/Wind Harmer
0.147
274729ELWOOD EC;1P
Adder
8.713
276805AD2-038 GEN
Solar/Wind Harmer
0.001
276889AE2-281 GEN
Solar/Wind Harmer
0
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.382
274850MENDOTA H;RU
Solar/Wind Harmer
0.042
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.064
970571AG2-364 GEN
Solar/Wind Harmer
7.107
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
276157O29GEN1
Solar/Wind Harmer
0.565
942111AE2-223 GEN
Solar/Wind Harmer
1.128
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
5.066
971993AH1-541 GEN
Solar/Wind Harmer
1.533
276621W2-048 GEN
Solar/Wind Harmer
0.166
276838X2-022 GEN2
Solar/Wind Harmer
0.185
23888702TROY G3
50/50
1.526
972253AH1-711 GEN
50/50
46.611
960841AF2-375 GEN
Solar/Wind Harmer
-0.002
247522W1-056 GEN
Solar/Wind Harmer
0.001
246936BC-WTG1
Solar/Wind Harmer
0.188
270489AE1-102 GEN1
Solar/Wind Harmer
0.603
945111AF1-176 GEN
Solar/Wind Harmer
8.251
270505AE1-170 C O1
Solar/Wind Harmer
4.856
965011AG1-365 GEN
Solar/Wind Harmer
4.252
274751CRETE EC ;1U
Adder
4.532
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
274723RIVER EC ;12
Adder
9.782
274801UNIV PARK;4U
Adder
3.125
274773LINCOLN ;4U
Adder
4.515
274774LINCOLN ;5U
Adder
4.515
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
4.664
971997AH1-543 GEN
Solar/Wind Harmer
1.887
276861AD2-134 GEN
Solar/Wind Harmer
0.064
970569AG2-363 GEN
Solar/Wind Harmer
10.66
274761LEE CO EC;2U
Adder
4.693
24387305FR-4G C
Solar/Wind Harmer
0.001
276158O29GEN2
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
4.858
958861AF2-177 GEN
Solar/Wind Harmer
1.482
972175AH1-670 GEN
Solar/Wind Harmer
2.788
945371AF1-202 GEN
Solar/Wind Harmer
0
274880W4-005 GEN4
Solar/Wind Harmer
0
270032AE2-172
Solar/Wind Harmer
2.212
970825AG2-519 GEN
Solar/Wind Harmer
1.153
270005AE1-210 C O1
Solar/Wind Harmer
0.7
241885AC2-103 GEN1
Solar/Wind Helper
6.849
961971AG1-040 GEN
Solar/Wind Helper
0.342
254303AC2-168 GEN
Solar/Wind Helper
0.077
23920202STRYCT
50/50
1.928
970515AG2-329 GEN
Solar/Wind Harmer
14.08
943021AE2-325 GEN
Solar/Wind Harmer
2.47
970373AG2-245 GEN
Solar/Wind Harmer
8.33
270223U2-072_GEN1
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.962
941551AE2-152 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.443
274872LEEDK;1U
Solar/Wind Harmer
0.002
24791305MDL-5G
Solar/Wind Harmer
0
959081AF2-199 GEN
Solar/Wind Harmer
3.567
971067AG2-660 GEN
Solar/Wind Harmer
1.189
274822ROCKFORD ;11
Adder
10.013
970819AG2-516 GEN
Solar/Wind Harmer
4.256
971475AH1-234 GEN
Solar/Wind Harmer
1.718
276726Z2-087_GEN
Solar/Wind Harmer
0.001
274854TWINGROVE;U2
Solar/Wind Harmer
0.001
963741AG1-226 GEN
Solar/Wind Harmer
7.999
23888502TROY G1
50/50
1.526
23888602TROY G2
50/50
1.526
971549AH1-272 GEN
Solar/Wind Harmer
11.98
270435AC2-044 GEN
Solar/Wind Harmer
0.588
247607V1-011 GEN
Solar/Wind Harmer
0.001
971771AH1-392 GEN
Solar/Wind Harmer
4.385
971769AH1-391 GEN
Solar/Wind Harmer
4.78
971567AH1-282 GEN
Solar/Wind Harmer
5.89
270071AF1-092 GEN
Solar/Wind Harmer
7.267
274728ELWOOD EC;5P
Adder
8.714
24691005MDL-2G C
Solar/Wind Harmer
0.001
971177AH1-047 GEN
Solar/Wind Harmer
2.216
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
276612AE2-035 GEN
Solar/Wind Harmer
0.001
24729505KEY G4
Adder
3.294
971681AH1-341 GEN
Solar/Wind Harmer
5.682
24386605FR-22G C
Solar/Wind Harmer
0
24387005FR-3G C
Solar/Wind Harmer
0.001
957751AF2-069 GEN
Solar/Wind Harmer
0.115
276174W4-005 GEN2
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
3.716
241886AC2-103 GEN2
Solar/Wind Helper
6.849
23856402BAYSG1
50/50
1.577
241808AF1-120 C
Solar/Wind Harmer
0.003
241858AF1-205_GEN
Solar/Wind Harmer
3.78
972301AH1-735 GEN
Adder
6.727
270361_3
Solar/Wind Harmer
4.521
944231AF1-091 GEN
Solar/Wind Harmer
1.351
270063AE2-323 C
Solar/Wind Harmer
0.004
270462AD2-086
Solar/Wind Harmer
0.009
274754CRETE EC ;4U
Adder
4.532
958381AF2-132 GEN
Solar/Wind Harmer
0.001
274732ELWOOD EC;7P
Adder
8.714
274674JOLIET 9 ;6U
Adder
8.161
970245AG2-165 GEN
Solar/Wind Harmer
1.596
939401AE1-172 GEN
Solar/Wind Harmer
2.703
962781AG1-127 GEN
Solar/Wind Harmer
3.433
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
972235AH1-702 GEN1
Adder
1.284
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274766LEE CO EC;7U
Adder
4.638
24385905FR-11G C
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
1.29
247536S-71 GEN
Solar/Wind Harmer
0.132
276615X2-022 GEN
Solar/Wind Harmer
0.034
276903AD2-071 C
Solar/Wind Harmer
3.649
945641AF1-229 GEN
Solar/Wind Harmer
0.001
971619AH1-309 GEN
Solar/Wind Harmer
2.081
965051AG1-369 GEN
Solar/Wind Harmer
2.168
270317AD1-130_GEN
Solar/Wind Harmer
0.006
971347AH1-153 GEN
Solar/Wind Harmer
6.147
972037AH1-567 GEN1
Adder
0.098
960591AF2-350 GEN
Solar/Wind Harmer
3.734
274775LINCOLN ;6U
Adder
4.515
274777LINCOLN ;8U
Adder
4.515
971611AH1-305 GEN
Solar/Wind Harmer
2.222
274675JOLIET 29;7U
Adder
16.292
274675JOLIET 29;7U
Adder
15.71
970833AG2-524 GEN
Solar/Wind Harmer
4.049
970833AG2-524 GEN
Solar/Wind Harmer
2.699
276868AE1-113 GEN
Solar/Wind Harmer
0.724
24697605MDL-3G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
971411AH1-196 GEN
Solar/Wind Harmer
5.375
971675AH1-338 GEN
Solar/Wind Harmer
1.396
971171AH1-044 GEN
Solar/Wind Harmer
7.133
274823ROCKFORD ;21
Adder
9.941
24386405FR-21G C
Solar/Wind Harmer
0
276656WTG2_EQ
Solar/Wind Harmer
0
941731AE2-173 GEN
Solar/Wind Harmer
2.892
946321AF1-296 GEN
Solar/Wind Harmer
1.922
945581AF1-223 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0.001
203846AF2-130 C
Solar/Wind Helper
0.251
23906502RICHG2&3
Adder
1.343
270588AE1-091_GEN
Solar/Wind Harmer
3.595
247643Z2-116 C
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0.005
276806AD2-047 C O1
Solar/Wind Harmer
2.116
274676JOLIET 29;8U
Adder
15.71
274734ELWOOD EC;8P
Adder
8.714
274736ELWOOD EC;9P
Adder
8.714
943121AE2-341 GEN
Solar/Wind Harmer
6.132
943591AF1-030 GEN
Solar/Wind Harmer
4.078
274682WAUKEGAN ;7U
Adder
9.363
24755605MDL-5G
Solar/Wind Harmer
0
959091AF2-200 GEN
Solar/Wind Harmer
7.133
274767LEE CO EC;8U
Adder
1.086
247642Z2-115 C
Solar/Wind Harmer
0.001
970289AG2-191 GEN
Solar/Wind Harmer
0.368
970291AG2-192 GEN
Solar/Wind Harmer
0.334
276668AB2-070 GEN1
Solar/Wind Harmer
0.121
946031AF1-268 GEN
Solar/Wind Harmer
3.103
203830AF1-094 GEN
Solar/Wind Helper
0.331
972211AH1-690 GEN
50/50
445.374
970817AG2-515 GEN
Solar/Wind Harmer
9.949
945411AF1-206 GEN
Solar/Wind Harmer
-0.001
270499AE1-146 GEN
Solar/Wind Harmer
0.029
270297AD1-101 GEN
Solar/Wind Harmer
0.001
965041AG1-368 GEN
Solar/Wind Harmer
4.372
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
270578AF1-285 GEN2
Solar/Wind Harmer
0.256
274814UNIV PK N;0U
Adder
2.746
274807UNIV PK N;3U
Adder
2.74
274805UNIV PK N;1U
Adder
2.728
274776LINCOLN ;7U
Adder
4.515
274687WILL CNTY;4U
Adder
14.867
274687WILL CNTY;4U
Adder
14.867
274731ELWOOD EC;2P
Adder
8.713
274733ELWOOD EC;3P
Adder
8.713
274746AC1-111 G10
Adder
2.931
276882AE2-255 GEN
Solar/Wind Harmer
0.422
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24697905MDL-4G C
Solar/Wind Harmer
0.001
926823AC1-168 GEN
Solar/Wind Harmer
0.603
24386205FR-12G C
Solar/Wind Harmer
0.001
276655WTG1_EQ
Solar/Wind Harmer
0.001
963841AG1-237 GEN
Solar/Wind Harmer
1.492
965101AG1-375 GEN
Solar/Wind Harmer
3.421
971609AH1-304 GEN
Solar/Wind Harmer
0.55
970115AG2-085 GEN
Solar/Wind Harmer
1.302
24699105WLD G1 C
Solar/Wind Harmer
0
241982AE2-343 S C
Solar/Wind Helper
0.12
254304AE2-114 C
Solar/Wind Helper
0.114
24189902OREGON_CT2
50/50
4.125
241840AF1-064_GEN
Solar/Wind Harmer
0.004
23906402RICHG1
Adder
1.345
23906502RICHG2&3
Adder
1.343
270449AD2-020 GEN
Solar/Wind Harmer
0
965421AG1-410 GEN
Solar/Wind Harmer
13.81
24639705ELKHART HY
Adder
0.098
24695305TIMB G C
Solar/Wind Harmer
0.001
247521TR3_G114
Solar/Wind Harmer
0.158
270246TR4_N_V150
Solar/Wind Harmer
0.028
270055AF2-134 C O1
Solar/Wind Harmer
0.003
274812UNIV PK N;8U
Adder
2.722
276164X3-005 C
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
0.39
274676JOLIET 29;8U
Adder
16.292
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
2.931
274682WAUKEGAN ;7U
Adder
9.363
274828WAUKEGAN ;BP
Adder
5.75
276901AD2-066 C O1
Solar/Wind Harmer
0.004
957471AF2-041 GEN
Solar/Wind Harmer
10.7
274877BISHOP HL;1U
Solar/Wind Harmer
0.117
965651AG1-433 GEN
Solar/Wind Harmer
1.012
970291AG2-192 GEN
Solar/Wind Harmer
0.435
241807AE2-176_GEN
Solar/Wind Helper
1.64
203835AF1-098 GEN
Solar/Wind Helper
1.348
203860AG1-193 C
Solar/Wind Helper
0.152
241966AE1-183 GEN
Solar/Wind Helper
0.132
965031AG1-367 GEN
Solar/Wind Harmer
0.798
957201AF2-014 GEN
Solar/Wind Harmer
0
971989AH1-539 GEN
Solar/Wind Harmer
1.862
270302AB2-170 GEN
Solar/Wind Harmer
0.003
971653AH1-327 GEN
Solar/Wind Harmer
0.58
963791AG1-232 GEN
Solar/Wind Harmer
5.327
270536AF1-215 GEN2
Solar/Wind Harmer
0.005
274811UNIV PK N;7U
Adder
2.722
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274827FISK ;RP
Adder
4.165
972227AH1-698 GEN1
Adder
1.392
274735ELWOOD EC;4P
Adder
8.713
274744AC1-111 GEN8
Adder
2.931
270024AE2-089 GEN
Solar/Wind Harmer
0.004
970169AG2-114 GEN
Solar/Wind Harmer
3.546
961011AF2-392 GEN
Solar/Wind Harmer
2.056
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
959341AF2-225 GEN
Solar/Wind Harmer
3.644
970289AG2-191 GEN
Solar/Wind Harmer
0.635
276785W4-005 GEN1
Solar/Wind Harmer
0
276849AB2-070 GEN2
Solar/Wind Harmer
0.121
276848AB2-070 GEN3
Solar/Wind Harmer
0.12
241997AF1-093 GEN
Solar/Wind Helper
0.132
203804AE2-113_GEN
Solar/Wind Helper
0.869
24190002OREGON_ST1
50/50
5.55
971677AH1-339 GEN
Solar/Wind Harmer
0.659
965681AG1-436 GEN
Solar/Wind Harmer
5.151
270227U2-072_GEN3
Solar/Wind Harmer
0
270228U2-072_GEN4
Solar/Wind Harmer
0
270231U2-072_GEN5
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
971341AH1-150 GEN
Solar/Wind Harmer
7.133
971343AH1-151 GEN
Solar/Wind Harmer
7.133
274849CRESCENT ;1U
Solar/Wind Harmer
0
276741O09 GEN1
Solar/Wind Harmer
0.124
971613AH1-306 GEN
Solar/Wind Harmer
1.593
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
203980AG1-197 GEN
Solar/Wind Helper
0.255
203979AG1-198 GEN
Solar/Wind Helper
0.198
241801AE1-079 GEN
Solar/Wind Helper
0.134
990142J1224
External Queue
14.791350364685059
991177J1571 G
External Queue
15.792752265930176
991182J1586 G
External Queue
28.11846351623535
990527J1329
External Queue
2.0234405994415283
NYPJM->LTFIMP_NY
CLTF
1.965
LGEELTFEXP_LGEE->PJM
CLTF
2.4
WECLTFEXP_WEC->PJM
CLTF
1.946
AG2-052LTFEXP_AG2-052->PJM
LTF
0.125
AH1-155LTFEXP_AH1-155->PJM
LTF
0.187
CBM West 1LTFEXP_CBM-W1->PJM
CBM
112.86
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.907
MECLTFEXP_MEC->PJM
CLTF
7.633
SIGELTFEXP_SIGE->PJM
CLTF
0.2
LAGNLTFEXP_LAGN->PJM
CLTF
6.061
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.4
TVALTFEXP_TVA->PJM
CLTF
2.775
CPLELTFEXP_CPLE->PJM
CLTF
0.731
CBM West 2LTFEXP_CBM-W2->PJM
CBM
47.539

Details for 02DAV-BE-02HAYES 345.0 kV Ckt 1 line l/o ATSI_P1-2_OEC-345-825_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02DAV-BE-02HAYES 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_OEC-345-825_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:136.86 %
Rating:1892.0 MVA
Rating Type:B
MVA to Mitigate:2589.31
MW Contribution:0.52
Bus #Bus NameTypeMW Contribution
270541AE2-072 C
Solar/Wind Harmer
0.008
270404AC1-167 GEN
Solar/Wind Harmer
0.002
247604X1-042
Adder
0.264
970031AG2-029 GEN
Solar/Wind Harmer
2.509
270247TR4_N_V136
Solar/Wind Harmer
0.025
970349AG2-230 GEN
Solar/Wind Harmer
5.331
270391AF1-285 GEN3
Solar/Wind Harmer
0.227
274752CRETE EC ;2U
Adder
3.916
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
274826FISK ;BP
Adder
5.072
972228AH1-698 GEN2
Adder
1.705
939351AE1-166 GEN
Solar/Wind Harmer
0
274730ELWOOD EC;6P
Adder
7.514
970707AG2-453 GEN
Solar/Wind Harmer
10.416
970513AG2-328 GEN
Solar/Wind Harmer
1.377
970517AG2-330 GEN
Solar/Wind Harmer
8.26
276694AA1-018 GEN2
Solar/Wind Harmer
0
944531AF1-118 GEN
Solar/Wind Harmer
13.898
970781AG2-491 GEN
Solar/Wind Harmer
3.1
274855GSG-6 ;RU
Solar/Wind Harmer
0.113
254305AE2-115 C
Solar/Wind Helper
0.113
24189802OREGON_CT1
50/50
2.906
961051AF2-396 GEN
Solar/Wind Harmer
8.176
961051AF2-396 GEN
Solar/Wind Harmer
5.45
270216AD2-079_GEN
Solar/Wind Harmer
0.001
970627AG2-408 GEN
Solar/Wind Harmer
1.125
23888802TROY G4
50/50
1.904
247620Y3-023
Adder
0.259
270526AF1-158 GEN
Solar/Wind Harmer
0.005
24441505OLIV SLR
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
3.275
276843GEN-1.7
Solar/Wind Harmer
0.104
958011AF2-095 GEN
Solar/Wind Harmer
4.64
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
945421AF1-207 GEN
Solar/Wind Harmer
0
971573AH1-285 GEN
Solar/Wind Harmer
0.585
274695ROCKY RD ;2P
Adder
4.995
958491AF2-143 GEN
Solar/Wind Harmer
4.684
942991AE2-321 GEN
Solar/Wind Harmer
3.454
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
971333AH1-146 GEN
Solar/Wind Harmer
6.163
274765LEE CO EC;6U
Adder
4.044
274763LEE CO EC;4U
Adder
3.996
274851PROVIDENC;RU
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
0.118
946381AF1-302 GEN
Solar/Wind Helper
0.105
238217AF1-153 C O1
Solar/Wind Helper
0.112
23929302BS-PKR
50/50
2.128
958321AF2-126 GEN
Solar/Wind Harmer
1.129
270575GUS2 35KV
Solar/Wind Harmer
4.06
970217AG2-149 GEN
Solar/Wind Harmer
4.25
270258AD1-119 GEN
Solar/Wind Harmer
0.001
270491AE1-102 GEN2
Solar/Wind Harmer
0.538
24642205MAYFLWER
Adder
0.357
270191TR4_S_V150
Solar/Wind Harmer
0.001
959331AF2-224 GEN
Solar/Wind Harmer
2.624
274753CRETE EC ;3U
Adder
3.916
964401AG1-302 GEN
Solar/Wind Harmer
0
972038AH1-567 GEN2
Adder
0.169
971617AH1-308 GEN
Solar/Wind Harmer
2.61
274872LEEDK;1U
Solar/Wind Harmer
0.114
241996AE2-282_GEN
Solar/Wind Harmer
0.006
970621AG2-405 GEN
Solar/Wind Harmer
0.863
970623AG2-406 GEN
Solar/Wind Harmer
0.804
246938BC-WTG3
Solar/Wind Harmer
0.15
246937BC-WTG2
Solar/Wind Harmer
0.168
270007AE1-245 C
Solar/Wind Harmer
0.001
957891AF2-083 GEN
Solar/Wind Harmer
0.001
970611AG2-400 GEN
Solar/Wind Harmer
3.749
274808UNIV PK N;4U
Adder
2.34
274888KELLY CRK;1U
Solar/Wind Harmer
0.189
274770LINCOLN ;1U
Adder
3.895
274771LINCOLN ;2U
Adder
3.895
972259AH1-714 GEN
Adder
8.743
942221AE2-234 GEN
Solar/Wind Harmer
0.016
970321AG2-212 GEN
Solar/Wind Harmer
1.377
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
274696ROCKY RD ;4P
Adder
5.113
274697ROCKY RD ;3P
Adder
1.357
962691AG1-118 GEN
Solar/Wind Harmer
9.334
274856ECOGROVE ;U1
Solar/Wind Harmer
0.072
276611AD2-172 GEN
Solar/Wind Harmer
0.001
938861AE1-114 GEN
Solar/Wind Harmer
1.719
274762LEE CO EC;3U
Adder
4.035
276603SUBLETTE C
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.118
241985AE1-237 GEN
Solar/Wind Helper
0.132
962101AG1-054 GEN
Solar/Wind Helper
0.329
241832AE2-181_GEN
Solar/Wind Harmer
0.004
24441205WTRV SLR C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
3.266
965021AG1-366 GEN
Solar/Wind Harmer
1.25
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270043AE2-236 GEN
Solar/Wind Harmer
2.282
274724RIVER EC ;11
Adder
8.349
274802UNIV PARK;5U
Adder
2.706
274800UNIV PARK;3U
Adder
2.697
970941AG2-585 GEN
Solar/Wind Harmer
4.027
274772LINCOLN ;3U
Adder
3.895
276897AD1-100 C
Solar/Wind Harmer
0.004
276893AG1-478 C
Solar/Wind Harmer
0.126
274729ELWOOD EC;1P
Adder
7.514
276805AD2-038 GEN
Solar/Wind Harmer
0.001
276889AE2-281 GEN
Solar/Wind Harmer
0
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.329
274850MENDOTA H;RU
Solar/Wind Harmer
0.036
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.055
970571AG2-364 GEN
Solar/Wind Harmer
6.113
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
276157O29GEN1
Solar/Wind Harmer
0.485
972236AH1-702 GEN2
Adder
0.96
274760LEE CO EC;1U
Adder
4.035
962511AG1-100 GEN
Solar/Wind Helper
0.342
959441AF2-235 GEN
Solar/Wind Helper
0.147
20334926Z1-069 C
Solar/Wind Helper
0.646
23888702TROY G3
50/50
1.904
972253AH1-711 GEN
50/50
58.156
241885AC2-103 GEN1
Solar/Wind Harmer
-0.001
960841AF2-375 GEN
Solar/Wind Harmer
-0.001
247522W1-056 GEN
Solar/Wind Harmer
0.001
246936BC-WTG1
Solar/Wind Harmer
0.168
270489AE1-102 GEN1
Solar/Wind Harmer
0.538
945111AF1-176 GEN
Solar/Wind Harmer
7.189
270505AE1-170 C O1
Solar/Wind Harmer
4.228
965011AG1-365 GEN
Solar/Wind Harmer
3.749
274751CRETE EC ;1U
Adder
3.916
964861AG1-349 GEN
Solar/Wind Harmer
0
274723RIVER EC ;12
Adder
8.45
274801UNIV PARK;4U
Adder
2.697
274773LINCOLN ;4U
Adder
3.895
274774LINCOLN ;5U
Adder
3.895
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
4.026
971997AH1-543 GEN
Solar/Wind Harmer
1.624
276861AD2-134 GEN
Solar/Wind Harmer
0.055
970569AG2-363 GEN
Solar/Wind Harmer
9.17
274761LEE CO EC;2U
Adder
4.035
24387305FR-4G C
Solar/Wind Harmer
0.001
276158O29GEN2
Solar/Wind Harmer
0
961971AG1-040 GEN
Solar/Wind Helper
0.334
254303AC2-168 GEN
Solar/Wind Helper
0.076
23867002DVBSG1
50/50
15.559
23888502TROY G1
50/50
1.904
23888602TROY G2
50/50
1.904
241886AC2-103 GEN2
Solar/Wind Harmer
-0.001
971549AH1-272 GEN
Solar/Wind Harmer
10.494
270435AC2-044 GEN
Solar/Wind Harmer
0.524
247607V1-011 GEN
Solar/Wind Harmer
0.001
971771AH1-392 GEN
Solar/Wind Harmer
3.814
971769AH1-391 GEN
Solar/Wind Harmer
4.151
971567AH1-282 GEN
Solar/Wind Harmer
5.227
270071AF1-092 GEN
Solar/Wind Harmer
6.329
274728ELWOOD EC;5P
Adder
7.514
24691005MDL-2G C
Solar/Wind Harmer
0.001
971177AH1-047 GEN
Solar/Wind Harmer
1.907
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
24729505KEY G4
Adder
2.855
276612AE2-035 GEN
Solar/Wind Harmer
0.001
971681AH1-341 GEN
Solar/Wind Harmer
4.885
24386605FR-22G C
Solar/Wind Harmer
0
24387005FR-3G C
Solar/Wind Harmer
0.001
957751AF2-069 GEN
Solar/Wind Harmer
0.099
270224U2-072_GEN2
Solar/Wind Harmer
0
274803UNIV PARK;6U
Adder
2.706
274887GEN-1.85
Solar/Wind Harmer
0.085
274674JOLIET 9 ;6U
Adder
7.038
958481AF2-142 GEN
Solar/Wind Harmer
4.726
274862TOP CROP ;2U
Solar/Wind Harmer
0.426
274693ROCKY RD ;1P
Adder
4.946
274683WAUKEGAN ;8U
Adder
9.448
274683WAUKEGAN ;8U
Adder
7.964
274879MINONK ;1U
Solar/Wind Harmer
0.131
970921AG2-575 GEN
Solar/Wind Harmer
3.106
970921AG2-575 GEN
Solar/Wind Harmer
1.035
971335AH1-147 GEN
Solar/Wind Harmer
6.163
274764LEE CO EC;5U
Adder
4.044
966841AG1-555 GEN
Solar/Wind Harmer
0.342
276708O09 GEN2
Solar/Wind Harmer
0.107
203947AF1-006 C
Solar/Wind Helper
0.381
241967AE2-285_GEN
Solar/Wind Helper
0.341
23856402BAYSG1
50/50
1.209
241858AF1-205_GEN
Solar/Wind Harmer
3.878
241808AF1-120 C
Solar/Wind Harmer
0.003
972301AH1-735 GEN
Adder
6.656
270361_3
Solar/Wind Harmer
4.06
944231AF1-091 GEN
Solar/Wind Harmer
1.239
270063AE2-323 C
Solar/Wind Harmer
0.003
270462AD2-086
Solar/Wind Harmer
0.008
274754CRETE EC ;4U
Adder
3.916
958381AF2-132 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
7.514
274674JOLIET 9 ;6U
Adder
7.038
970245AG2-165 GEN
Solar/Wind Harmer
1.377
939401AE1-172 GEN
Solar/Wind Harmer
2.328
962781AG1-127 GEN
Solar/Wind Harmer
2.956
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
972235AH1-702 GEN1
Adder
1.104
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274766LEE CO EC;7U
Adder
2.419
24385905FR-11G C
Solar/Wind Harmer
0.001
945641AF1-229 GEN
Solar/Wind Harmer
0.001
971619AH1-309 GEN
Solar/Wind Harmer
1.812
965051AG1-369 GEN
Solar/Wind Harmer
1.924
270317AD1-130_GEN
Solar/Wind Harmer
0.005
971347AH1-153 GEN
Solar/Wind Harmer
5.331
972037AH1-567 GEN1
Adder
0.085
960591AF2-350 GEN
Solar/Wind Harmer
3.222
274775LINCOLN ;6U
Adder
3.895
274777LINCOLN ;8U
Adder
3.895
971611AH1-305 GEN
Solar/Wind Harmer
1.917
274675JOLIET 29;7U
Adder
14.05
274675JOLIET 29;7U
Adder
13.548
970833AG2-524 GEN
Solar/Wind Harmer
3.49
970833AG2-524 GEN
Solar/Wind Harmer
2.327
276868AE1-113 GEN
Solar/Wind Harmer
0.623
24697605MDL-3G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
971411AH1-196 GEN
Solar/Wind Harmer
4.626
971675AH1-338 GEN
Solar/Wind Harmer
1.202
971171AH1-044 GEN
Solar/Wind Harmer
6.137
274823ROCKFORD ;21
Adder
8.551
24386405FR-21G C
Solar/Wind Harmer
0
203846AF2-130 C
Solar/Wind Helper
0.248
23906502RICHG2&3
Adder
1.328
270588AE1-091_GEN
Solar/Wind Harmer
3.207
247643Z2-116 C
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0.004
276806AD2-047 C O1
Solar/Wind Harmer
1.826
274676JOLIET 29;8U
Adder
13.548
274734ELWOOD EC;8P
Adder
7.514
274736ELWOOD EC;9P
Adder
7.514
943121AE2-341 GEN
Solar/Wind Harmer
5.284
943591AF1-030 GEN
Solar/Wind Harmer
3.514
274682WAUKEGAN ;7U
Adder
8.065
24755605MDL-5G
Solar/Wind Harmer
0
959091AF2-200 GEN
Solar/Wind Harmer
6.137
203830AF1-094 GEN
Solar/Wind Helper
0.324
23920202STRYCT
50/50
1.93
970515AG2-329 GEN
Solar/Wind Harmer
12.751
943021AE2-325 GEN
Solar/Wind Harmer
2.152
970373AG2-245 GEN
Solar/Wind Harmer
7.209
270223U2-072_GEN1
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.287
941551AE2-152 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.382
274872LEEDK;1U
Solar/Wind Harmer
0.002
24791305MDL-5G
Solar/Wind Harmer
0
959081AF2-199 GEN
Solar/Wind Harmer
3.069
971067AG2-660 GEN
Solar/Wind Harmer
1.023
274822ROCKFORD ;11
Adder
8.614
970819AG2-516 GEN
Solar/Wind Harmer
3.66
971475AH1-234 GEN
Solar/Wind Harmer
1.477
972211AH1-690 GEN
50/50
307.104
970817AG2-515 GEN
Solar/Wind Harmer
11.024
945411AF1-206 GEN
Solar/Wind Harmer
-0.001
270499AE1-146 GEN
Solar/Wind Harmer
0.026
270297AD1-101 GEN
Solar/Wind Harmer
0.001
965041AG1-368 GEN
Solar/Wind Harmer
3.881
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
270578AF1-285 GEN2
Solar/Wind Harmer
0.227
274814UNIV PK N;0U
Adder
2.371
274807UNIV PK N;3U
Adder
2.366
274805UNIV PK N;1U
Adder
2.356
274776LINCOLN ;7U
Adder
3.895
274687WILL CNTY;4U
Adder
12.823
274687WILL CNTY;4U
Adder
12.823
274731ELWOOD EC;2P
Adder
7.514
274733ELWOOD EC;3P
Adder
7.514
274746AC1-111 G10
Adder
2.526
276882AE2-255 GEN
Solar/Wind Harmer
0.363
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24697905MDL-4G C
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
0.519
24386205FR-12G C
Solar/Wind Harmer
0
241982AE2-343 S C
Solar/Wind Helper
0.119
254304AE2-114 C
Solar/Wind Helper
0.113
24189902OREGON_CT2
50/50
2.847
241840AF1-064_GEN
Solar/Wind Harmer
0.004
23906402RICHG1
Adder
1.331
23906502RICHG2&3
Adder
1.328
270449AD2-020 GEN
Solar/Wind Harmer
0
965421AG1-410 GEN
Solar/Wind Harmer
12.302
24695305TIMB G C
Solar/Wind Harmer
0.001
24639705ELKHART HY
Adder
0.086
247521TR3_G114
Solar/Wind Harmer
0.14
270246TR4_N_V150
Solar/Wind Harmer
0.025
270055AF2-134 C O1
Solar/Wind Harmer
0.003
274812UNIV PK N;8U
Adder
2.351
276164X3-005 C
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
0.336
274676JOLIET 29;8U
Adder
14.05
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
2.526
274682WAUKEGAN ;7U
Adder
8.065
274828WAUKEGAN ;BP
Adder
4.952
276901AD2-066 C O1
Solar/Wind Harmer
0.003
957471AF2-041 GEN
Solar/Wind Harmer
9.206
241807AE2-176_GEN
Solar/Wind Helper
2.238
203835AF1-098 GEN
Solar/Wind Helper
1.318
203860AG1-193 C
Solar/Wind Helper
0.149
241966AE1-183 GEN
Solar/Wind Helper
0.131
957201AF2-014 GEN
Solar/Wind Harmer
0
971989AH1-539 GEN
Solar/Wind Harmer
1.649
270302AB2-170 GEN
Solar/Wind Harmer
0.002
971653AH1-327 GEN
Solar/Wind Harmer
0.517
963791AG1-232 GEN
Solar/Wind Harmer
4.679
270536AF1-215 GEN2
Solar/Wind Harmer
0.004
274811UNIV PK N;7U
Adder
2.351
958391AF2-133 GEN
Solar/Wind Harmer
0
274827FISK ;RP
Adder
3.595
972227AH1-698 GEN1
Adder
1.201
274735ELWOOD EC;4P
Adder
7.514
274744AC1-111 GEN8
Adder
2.526
270024AE2-089 GEN
Solar/Wind Harmer
0.003
970169AG2-114 GEN
Solar/Wind Harmer
3.05
961011AF2-392 GEN
Solar/Wind Harmer
1.766
241997AF1-093 GEN
Solar/Wind Helper
0.131
203804AE2-113_GEN
Solar/Wind Helper
0.868
24190002OREGON_ST1
50/50
3.831
971677AH1-339 GEN
Solar/Wind Harmer
0.588
965681AG1-436 GEN
Solar/Wind Harmer
4.465
270227U2-072_GEN3
Solar/Wind Harmer
0
270228U2-072_GEN4
Solar/Wind Harmer
0
270231U2-072_GEN5
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
971341AH1-150 GEN
Solar/Wind Harmer
6.137
971343AH1-151 GEN
Solar/Wind Harmer
6.137
274849CRESCENT ;1U
Solar/Wind Harmer
0
276741O09 GEN1
Solar/Wind Harmer
0.107
203980AG1-197 GEN
Solar/Wind Helper
0.249
203979AG1-198 GEN
Solar/Wind Helper
0.194
241801AE1-079 GEN
Solar/Wind Helper
0.133
990142J1224
External Queue
13.940826416015625
991177J1571 G
External Queue
15.847536087036133
991182J1586 G
External Queue
26.137367248535156
990527J1329
External Queue
1.9070898294448853
NYPJM->LTFIMP_NY
CLTF
2.031
LGEELTFEXP_LGEE->PJM
CLTF
2.008
WECLTFEXP_WEC->PJM
CLTF
1.673
AG2-052LTFEXP_AG2-052->PJM
LTF
0.108
AH1-155LTFEXP_AH1-155->PJM
LTF
0.162
CBM West 1LTFEXP_CBM-W1->PJM
CBM
96.337
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.893
MECLTFEXP_MEC->PJM
CLTF
6.512
SIGELTFEXP_SIGE->PJM
CLTF
0.168
LAGNLTFEXP_LAGN->PJM
CLTF
4.961
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.186
TVALTFEXP_TVA->PJM
CLTF
2.246
CPLELTFEXP_CPLE->PJM
CLTF
0.328
CBM West 2LTFEXP_CBM-W2->PJM
CBM
39.692

Details for 02DAV-BE-02HAYES 345.0 kV Ckt 1 line l/o ATSI_P1-2_OEC-345-824_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02DAV-BE-02HAYES 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_OEC-345-824_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:136.39 %
Rating:1892.0 MVA
Rating Type:B
MVA to Mitigate:2580.58
MW Contribution:0.52
Bus #Bus NameTypeMW Contribution
241832AE2-181_GEN
Solar/Wind Harmer
0.004
24441205WTRV SLR C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
3.272
965021AG1-366 GEN
Solar/Wind Harmer
1.252
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270043AE2-236 GEN
Solar/Wind Harmer
2.287
274724RIVER EC ;11
Adder
8.367
274802UNIV PARK;5U
Adder
2.712
274800UNIV PARK;3U
Adder
2.703
970941AG2-585 GEN
Solar/Wind Harmer
4.036
274772LINCOLN ;3U
Adder
3.904
276897AD1-100 C
Solar/Wind Harmer
0.004
276893AG1-478 C
Solar/Wind Harmer
0.127
274729ELWOOD EC;1P
Adder
7.53
276805AD2-038 GEN
Solar/Wind Harmer
0.001
276889AE2-281 GEN
Solar/Wind Harmer
0
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.33
274850MENDOTA H;RU
Solar/Wind Harmer
0.036
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.055
970571AG2-364 GEN
Solar/Wind Harmer
6.128
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
276157O29GEN1
Solar/Wind Harmer
0.487
23929302BS-PKR
50/50
2.13
958321AF2-126 GEN
Solar/Wind Harmer
1.13
270575GUS2 35KV
Solar/Wind Harmer
4.064
970217AG2-149 GEN
Solar/Wind Harmer
4.257
270258AD1-119 GEN
Solar/Wind Harmer
0.001
270491AE1-102 GEN2
Solar/Wind Harmer
0.539
24642205MAYFLWER
Adder
0.357
270191TR4_S_V150
Solar/Wind Harmer
0.001
959331AF2-224 GEN
Solar/Wind Harmer
2.629
274753CRETE EC ;3U
Adder
3.925
964401AG1-302 GEN
Solar/Wind Harmer
0
972038AH1-567 GEN2
Adder
0.169
971617AH1-308 GEN
Solar/Wind Harmer
2.616
274872LEEDK;1U
Solar/Wind Harmer
0.114
972236AH1-702 GEN2
Adder
0.963
274760LEE CO EC;1U
Adder
4.044
962511AG1-100 GEN
Solar/Wind Helper
0.341
959441AF2-235 GEN
Solar/Wind Helper
0.147
20334926Z1-069 C
Solar/Wind Helper
0.645
23867002DVBSG1
50/50
15.565
23888502TROY G1
50/50
1.905
23888602TROY G2
50/50
1.905
971549AH1-272 GEN
Solar/Wind Harmer
10.508
270435AC2-044 GEN
Solar/Wind Harmer
0.525
247607V1-011 GEN
Solar/Wind Harmer
0.001
971771AH1-392 GEN
Solar/Wind Harmer
3.821
971769AH1-391 GEN
Solar/Wind Harmer
4.158
971567AH1-282 GEN
Solar/Wind Harmer
5.238
270071AF1-092 GEN
Solar/Wind Harmer
6.342
274728ELWOOD EC;5P
Adder
7.531
24691005MDL-2G C
Solar/Wind Harmer
0.001
971177AH1-047 GEN
Solar/Wind Harmer
1.911
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
24189802OREGON_CT1
50/50
2.907
961051AF2-396 GEN
Solar/Wind Harmer
8.19
961051AF2-396 GEN
Solar/Wind Harmer
5.46
270216AD2-079_GEN
Solar/Wind Harmer
0.001
970627AG2-408 GEN
Solar/Wind Harmer
1.127
270224U2-072_GEN2
Solar/Wind Harmer
0
274803UNIV PARK;6U
Adder
2.712
274887GEN-1.85
Solar/Wind Harmer
0.085
274674JOLIET 9 ;6U
Adder
7.053
958481AF2-142 GEN
Solar/Wind Harmer
4.737
274862TOP CROP ;2U
Solar/Wind Harmer
0.427
274693ROCKY RD ;1P
Adder
4.957
274683WAUKEGAN ;8U
Adder
9.469
274683WAUKEGAN ;8U
Adder
7.982
274879MINONK ;1U
Solar/Wind Harmer
0.131
970921AG2-575 GEN
Solar/Wind Harmer
3.113
970921AG2-575 GEN
Solar/Wind Harmer
1.038
971335AH1-147 GEN
Solar/Wind Harmer
6.177
274764LEE CO EC;5U
Adder
4.053
966841AG1-555 GEN
Solar/Wind Harmer
0.342
276708O09 GEN2
Solar/Wind Harmer
0.107
23856402BAYSG1
50/50
1.21
241858AF1-205_GEN
Solar/Wind Harmer
3.881
241808AF1-120 C
Solar/Wind Harmer
0.003
972301AH1-735 GEN
Adder
6.662
270361_3
Solar/Wind Harmer
4.064
944231AF1-091 GEN
Solar/Wind Harmer
1.241
270063AE2-323 C
Solar/Wind Harmer
0.003
270462AD2-086
Solar/Wind Harmer
0.008
274754CRETE EC ;4U
Adder
3.925
958381AF2-132 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
7.531
274674JOLIET 9 ;6U
Adder
7.053
970245AG2-165 GEN
Solar/Wind Harmer
1.38
939401AE1-172 GEN
Solar/Wind Harmer
2.333
962781AG1-127 GEN
Solar/Wind Harmer
2.963
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
972235AH1-702 GEN1
Adder
1.107
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274766LEE CO EC;7U
Adder
2.424
24385905FR-11G C
Solar/Wind Harmer
0.001
945641AF1-229 GEN
Solar/Wind Harmer
0.001
971619AH1-309 GEN
Solar/Wind Harmer
1.815
965051AG1-369 GEN
Solar/Wind Harmer
1.928
270317AD1-130_GEN
Solar/Wind Harmer
0.005
971347AH1-153 GEN
Solar/Wind Harmer
5.341
972037AH1-567 GEN1
Adder
0.085
960591AF2-350 GEN
Solar/Wind Harmer
3.229
274775LINCOLN ;6U
Adder
3.904
274777LINCOLN ;8U
Adder
3.904
971611AH1-305 GEN
Solar/Wind Harmer
1.922
274675JOLIET 29;7U
Adder
14.081
23906502RICHG2&3
Adder
1.329
270588AE1-091_GEN
Solar/Wind Harmer
3.213
247643Z2-116 C
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0.004
276806AD2-047 C O1
Solar/Wind Harmer
1.83
274676JOLIET 29;8U
Adder
13.578
274734ELWOOD EC;8P
Adder
7.531
274736ELWOOD EC;9P
Adder
7.531
943121AE2-341 GEN
Solar/Wind Harmer
5.296
943591AF1-030 GEN
Solar/Wind Harmer
3.522
274682WAUKEGAN ;7U
Adder
8.083
24755605MDL-5G
Solar/Wind Harmer
0
959091AF2-200 GEN
Solar/Wind Harmer
6.151
274675JOLIET 29;7U
Adder
13.578
270541AE2-072 C
Solar/Wind Harmer
0.008
270404AC1-167 GEN
Solar/Wind Harmer
0.002
247604X1-042
Adder
0.265
970031AG2-029 GEN
Solar/Wind Harmer
2.514
270247TR4_N_V136
Solar/Wind Harmer
0.025
970349AG2-230 GEN
Solar/Wind Harmer
5.341
270391AF1-285 GEN3
Solar/Wind Harmer
0.227
274752CRETE EC ;2U
Adder
3.925
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
274826FISK ;BP
Adder
5.083
972228AH1-698 GEN2
Adder
1.709
939351AE1-166 GEN
Solar/Wind Harmer
0
274730ELWOOD EC;6P
Adder
7.531
970707AG2-453 GEN
Solar/Wind Harmer
10.439
970513AG2-328 GEN
Solar/Wind Harmer
1.38
970517AG2-330 GEN
Solar/Wind Harmer
8.279
276694AA1-018 GEN2
Solar/Wind Harmer
0
944531AF1-118 GEN
Solar/Wind Harmer
13.93
970781AG2-491 GEN
Solar/Wind Harmer
3.107
274855GSG-6 ;RU
Solar/Wind Harmer
0.113
254305AE2-115 C
Solar/Wind Helper
0.113
24729505KEY G4
Adder
2.862
276612AE2-035 GEN
Solar/Wind Harmer
0.001
241996AE2-282_GEN
Solar/Wind Harmer
0.006
970621AG2-405 GEN
Solar/Wind Harmer
0.864
970623AG2-406 GEN
Solar/Wind Harmer
0.806
246938BC-WTG3
Solar/Wind Harmer
0.15
246937BC-WTG2
Solar/Wind Harmer
0.168
270007AE1-245 C
Solar/Wind Harmer
0.001
957891AF2-083 GEN
Solar/Wind Harmer
0.001
970611AG2-400 GEN
Solar/Wind Harmer
3.756
274808UNIV PK N;4U
Adder
2.345
274888KELLY CRK;1U
Solar/Wind Harmer
0.19
274770LINCOLN ;1U
Adder
3.904
274771LINCOLN ;2U
Adder
3.904
972259AH1-714 GEN
Adder
8.763
942221AE2-234 GEN
Solar/Wind Harmer
0.016
970321AG2-212 GEN
Solar/Wind Harmer
1.38
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
274696ROCKY RD ;4P
Adder
5.124
274697ROCKY RD ;3P
Adder
1.36
962691AG1-118 GEN
Solar/Wind Harmer
9.356
274856ECOGROVE ;U1
Solar/Wind Harmer
0.072
276611AD2-172 GEN
Solar/Wind Harmer
0.001
938861AE1-114 GEN
Solar/Wind Harmer
1.723
274762LEE CO EC;3U
Adder
4.044
276603SUBLETTE C
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.118
241985AE1-237 GEN
Solar/Wind Helper
0.132
962101AG1-054 GEN
Solar/Wind Helper
0.328
23920202STRYCT
50/50
1.931
970515AG2-329 GEN
Solar/Wind Harmer
12.77
943021AE2-325 GEN
Solar/Wind Harmer
2.155
970373AG2-245 GEN
Solar/Wind Harmer
7.224
270223U2-072_GEN1
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.296
941551AE2-152 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.383
274872LEEDK;1U
Solar/Wind Harmer
0.002
24791305MDL-5G
Solar/Wind Harmer
0
959081AF2-199 GEN
Solar/Wind Harmer
3.076
971067AG2-660 GEN
Solar/Wind Harmer
1.025
274822ROCKFORD ;11
Adder
8.634
970819AG2-516 GEN
Solar/Wind Harmer
3.668
971475AH1-234 GEN
Solar/Wind Harmer
1.481
972211AH1-690 GEN
50/50
307.274
970817AG2-515 GEN
Solar/Wind Harmer
11.031
945411AF1-206 GEN
Solar/Wind Harmer
-0.001
270499AE1-146 GEN
Solar/Wind Harmer
0.026
270297AD1-101 GEN
Solar/Wind Harmer
0.001
965041AG1-368 GEN
Solar/Wind Harmer
3.888
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
270578AF1-285 GEN2
Solar/Wind Harmer
0.227
274814UNIV PK N;0U
Adder
2.376
274807UNIV PK N;3U
Adder
2.371
274805UNIV PK N;1U
Adder
2.361
274776LINCOLN ;7U
Adder
3.904
274687WILL CNTY;4U
Adder
12.851
274687WILL CNTY;4U
Adder
12.851
274731ELWOOD EC;2P
Adder
7.53
274733ELWOOD EC;3P
Adder
7.53
274746AC1-111 G10
Adder
2.532
276882AE2-255 GEN
Solar/Wind Harmer
0.364
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24697905MDL-4G C
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
0.52
24386205FR-12G C
Solar/Wind Harmer
0
241982AE2-343 S C
Solar/Wind Helper
0.118
254304AE2-114 C
Solar/Wind Helper
0.113
23888802TROY G4
50/50
1.905
247620Y3-023
Adder
0.259
270526AF1-158 GEN
Solar/Wind Harmer
0.005
24441505OLIV SLR
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
3.281
276843GEN-1.7
Solar/Wind Harmer
0.105
958011AF2-095 GEN
Solar/Wind Harmer
4.65
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
945421AF1-207 GEN
Solar/Wind Harmer
0
971573AH1-285 GEN
Solar/Wind Harmer
0.586
274695ROCKY RD ;2P
Adder
5.006
958491AF2-143 GEN
Solar/Wind Harmer
4.695
942991AE2-321 GEN
Solar/Wind Harmer
3.462
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
971333AH1-146 GEN
Solar/Wind Harmer
6.177
274765LEE CO EC;6U
Adder
4.053
274763LEE CO EC;4U
Adder
4.006
274851PROVIDENC;RU
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
0.118
946381AF1-302 GEN
Solar/Wind Helper
0.105
238217AF1-153 C O1
Solar/Wind Helper
0.111
203830AF1-094 GEN
Solar/Wind Helper
0.323
957201AF2-014 GEN
Solar/Wind Harmer
0
971989AH1-539 GEN
Solar/Wind Harmer
1.652
270302AB2-170 GEN
Solar/Wind Harmer
0.002
971653AH1-327 GEN
Solar/Wind Harmer
0.518
963791AG1-232 GEN
Solar/Wind Harmer
4.689
270536AF1-215 GEN2
Solar/Wind Harmer
0.004
274811UNIV PK N;7U
Adder
2.356
958391AF2-133 GEN
Solar/Wind Harmer
0
274827FISK ;RP
Adder
3.602
972227AH1-698 GEN1
Adder
1.203
274735ELWOOD EC;4P
Adder
7.53
274744AC1-111 GEN8
Adder
2.532
270024AE2-089 GEN
Solar/Wind Harmer
0.003
970169AG2-114 GEN
Solar/Wind Harmer
3.057
961011AF2-392 GEN
Solar/Wind Harmer
1.771
241997AF1-093 GEN
Solar/Wind Helper
0.131
203804AE2-113_GEN
Solar/Wind Helper
0.866
24190002OREGON_ST1
50/50
3.833
971677AH1-339 GEN
Solar/Wind Harmer
0.588
965681AG1-436 GEN
Solar/Wind Harmer
4.474
270227U2-072_GEN3
Solar/Wind Harmer
0
270228U2-072_GEN4
Solar/Wind Harmer
0
270231U2-072_GEN5
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
971341AH1-150 GEN
Solar/Wind Harmer
6.151
971343AH1-151 GEN
Solar/Wind Harmer
6.151
274849CRESCENT ;1U
Solar/Wind Harmer
0
276741O09 GEN1
Solar/Wind Harmer
0.107
203980AG1-197 GEN
Solar/Wind Helper
0.249
203979AG1-198 GEN
Solar/Wind Helper
0.194
241801AE1-079 GEN
Solar/Wind Helper
0.132
24189902OREGON_CT2
50/50
2.849
241840AF1-064_GEN
Solar/Wind Harmer
0.004
23906402RICHG1
Adder
1.332
23906502RICHG2&3
Adder
1.329
270449AD2-020 GEN
Solar/Wind Harmer
0
965421AG1-410 GEN
Solar/Wind Harmer
12.324
24695305TIMB G C
Solar/Wind Harmer
0.001
24639705ELKHART HY
Adder
0.086
247521TR3_G114
Solar/Wind Harmer
0.141
270246TR4_N_V150
Solar/Wind Harmer
0.025
270055AF2-134 C O1
Solar/Wind Harmer
0.003
274812UNIV PK N;8U
Adder
2.356
276164X3-005 C
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
0.337
274676JOLIET 29;8U
Adder
14.081
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
2.532
274682WAUKEGAN ;7U
Adder
8.083
274828WAUKEGAN ;BP
Adder
4.964
276901AD2-066 C O1
Solar/Wind Harmer
0.003
957471AF2-041 GEN
Solar/Wind Harmer
9.227
241807AE2-176_GEN
Solar/Wind Helper
2.236
203835AF1-098 GEN
Solar/Wind Helper
1.316
203860AG1-193 C
Solar/Wind Helper
0.149
241966AE1-183 GEN
Solar/Wind Helper
0.131
23888702TROY G3
50/50
1.905
972253AH1-711 GEN
50/50
58.19
960841AF2-375 GEN
Solar/Wind Harmer
-0.001
247522W1-056 GEN
Solar/Wind Harmer
0.001
246936BC-WTG1
Solar/Wind Harmer
0.168
270489AE1-102 GEN1
Solar/Wind Harmer
0.539
945111AF1-176 GEN
Solar/Wind Harmer
7.202
270505AE1-170 C O1
Solar/Wind Harmer
4.236
965011AG1-365 GEN
Solar/Wind Harmer
3.756
274751CRETE EC ;1U
Adder
3.925
964861AG1-349 GEN
Solar/Wind Harmer
0
274723RIVER EC ;12
Adder
8.468
274801UNIV PARK;4U
Adder
2.703
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
274773LINCOLN ;4U
Adder
3.904
274774LINCOLN ;5U
Adder
3.904
971605AH1-302 GEN
Solar/Wind Harmer
4.035
971997AH1-543 GEN
Solar/Wind Harmer
1.628
276861AD2-134 GEN
Solar/Wind Harmer
0.055
970569AG2-363 GEN
Solar/Wind Harmer
9.191
274761LEE CO EC;2U
Adder
4.044
24387305FR-4G C
Solar/Wind Harmer
0.001
276158O29GEN2
Solar/Wind Harmer
0
241885AC2-103 GEN1
Solar/Wind Helper
3.958
961971AG1-040 GEN
Solar/Wind Helper
0.334
254303AC2-168 GEN
Solar/Wind Helper
0.076
971681AH1-341 GEN
Solar/Wind Harmer
4.897
24386605FR-22G C
Solar/Wind Harmer
0
24387005FR-3G C
Solar/Wind Harmer
0.001
957751AF2-069 GEN
Solar/Wind Harmer
0.099
241886AC2-103 GEN2
Solar/Wind Helper
3.958
970833AG2-524 GEN
Solar/Wind Harmer
3.498
970833AG2-524 GEN
Solar/Wind Harmer
2.332
276868AE1-113 GEN
Solar/Wind Harmer
0.625
24697605MDL-3G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
971411AH1-196 GEN
Solar/Wind Harmer
4.636
971675AH1-338 GEN
Solar/Wind Harmer
1.204
971171AH1-044 GEN
Solar/Wind Harmer
6.151
274823ROCKFORD ;21
Adder
8.571
24386405FR-21G C
Solar/Wind Harmer
0
203846AF2-130 C
Solar/Wind Helper
0.248
276782AC1-033 GEN
Solar/Wind Harmer
0
203947AF1-006 C
Solar/Wind Helper
0.38
241967AE2-285_GEN
Solar/Wind Helper
0.34
990142J1224
External Queue
13.940826416015625
991177J1571 G
External Queue
15.847536087036133
991182J1586 G
External Queue
26.137367248535156
990527J1329
External Queue
1.9070898294448853
NYPJM->LTFIMP_NY
CLTF
2.024
LGEELTFEXP_LGEE->PJM
CLTF
2.015
WECLTFEXP_WEC->PJM
CLTF
1.677
AG2-052LTFEXP_AG2-052->PJM
LTF
0.108
AH1-155LTFEXP_AH1-155->PJM
LTF
0.162
CBM West 1LTFEXP_CBM-W1->PJM
CBM
96.485
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.932
MECLTFEXP_MEC->PJM
CLTF
6.529
SIGELTFEXP_SIGE->PJM
CLTF
0.169
LAGNLTFEXP_LAGN->PJM
CLTF
4.982
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.217
TVALTFEXP_TVA->PJM
CLTF
2.257
CPLELTFEXP_CPLE->PJM
CLTF
0.339
CBM West 2LTFEXP_CBM-W2->PJM
CBM
39.829

Details for 02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line l/o ATSI_P1-2_OEC-345-810_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_OEC-345-810_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:136.64 %
Rating:1646.0 MVA
Rating Type:B
MVA to Mitigate:2249.01
MW Contribution:0.5
Bus #Bus NameTypeMW Contribution
270541AE2-072 C
Solar/Wind Harmer
0.008
270404AC1-167 GEN
Solar/Wind Harmer
0.002
247604X1-042
Adder
0.253
270247TR4_N_V136
Solar/Wind Harmer
0.024
970031AG2-029 GEN
Solar/Wind Harmer
2.41
970349AG2-230 GEN
Solar/Wind Harmer
5.114
270391AF1-285 GEN3
Solar/Wind Harmer
0.22
274752CRETE EC ;2U
Adder
3.76
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
274826FISK ;BP
Adder
4.871
972228AH1-698 GEN2
Adder
1.638
939351AE1-166 GEN
Solar/Wind Harmer
0
274730ELWOOD EC;6P
Adder
7.217
970707AG2-453 GEN
Solar/Wind Harmer
10.005
23888802TROY G4
50/50
1.796
247620Y3-023
Adder
0.248
270526AF1-158 GEN
Solar/Wind Harmer
0.004
24441505OLIV SLR
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
3.141
276843GEN-1.7
Solar/Wind Harmer
0.1
958011AF2-095 GEN
Solar/Wind Harmer
4.456
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
945421AF1-207 GEN
Solar/Wind Harmer
0
971573AH1-285 GEN
Solar/Wind Harmer
0.562
274695ROCKY RD ;2P
Adder
4.798
241996AE2-282_GEN
Solar/Wind Harmer
0.005
970621AG2-405 GEN
Solar/Wind Harmer
0.845
970623AG2-406 GEN
Solar/Wind Harmer
0.78
270007AE1-245 C
Solar/Wind Harmer
0.001
246938BC-WTG3
Solar/Wind Harmer
0.145
246937BC-WTG2
Solar/Wind Harmer
0.162
957891AF2-083 GEN
Solar/Wind Harmer
0.001
970611AG2-400 GEN
Solar/Wind Harmer
3.614
274808UNIV PK N;4U
Adder
2.247
274888KELLY CRK;1U
Solar/Wind Harmer
0.182
274770LINCOLN ;1U
Adder
3.741
274771LINCOLN ;2U
Adder
3.741
972259AH1-714 GEN
Adder
8.397
942221AE2-234 GEN
Solar/Wind Harmer
0.015
241832AE2-181_GEN
Solar/Wind Harmer
0.003
24441205WTRV SLR C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
3.128
965021AG1-366 GEN
Solar/Wind Harmer
1.205
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270043AE2-236 GEN
Solar/Wind Harmer
2.196
274724RIVER EC ;11
Adder
8.016
274802UNIV PARK;5U
Adder
2.599
274800UNIV PARK;3U
Adder
2.59
970941AG2-585 GEN
Solar/Wind Harmer
3.868
274772LINCOLN ;3U
Adder
3.741
276897AD1-100 C
Solar/Wind Harmer
0.004
276893AG1-478 C
Solar/Wind Harmer
0.121
274729ELWOOD EC;1P
Adder
7.217
23929302BS-PKR
50/50
2.128
958321AF2-126 GEN
Solar/Wind Harmer
1.111
270575GUS2 35KV
Solar/Wind Harmer
4.199
970217AG2-149 GEN
Solar/Wind Harmer
4.133
270258AD1-119 GEN
Solar/Wind Harmer
0.001
270491AE1-102 GEN2
Solar/Wind Harmer
0.52
24642205MAYFLWER
Adder
0.342
270191TR4_S_V150
Solar/Wind Harmer
0
959331AF2-224 GEN
Solar/Wind Harmer
2.53
274753CRETE EC ;3U
Adder
3.76
964401AG1-302 GEN
Solar/Wind Harmer
0
972038AH1-567 GEN2
Adder
0.162
971617AH1-308 GEN
Solar/Wind Harmer
2.521
962511AG1-100 GEN
Solar/Wind Helper
0.331
959441AF2-235 GEN
Solar/Wind Helper
0.142
23888702TROY G3
50/50
1.796
972253AH1-711 GEN
50/50
54.848
960841AF2-375 GEN
Solar/Wind Harmer
-0.001
247522W1-056 GEN
Solar/Wind Harmer
0.001
246936BC-WTG1
Solar/Wind Harmer
0.162
270489AE1-102 GEN1
Solar/Wind Harmer
0.52
945111AF1-176 GEN
Solar/Wind Harmer
6.886
270505AE1-170 C O1
Solar/Wind Harmer
4.049
965011AG1-365 GEN
Solar/Wind Harmer
3.614
274751CRETE EC ;1U
Adder
3.76
964861AG1-349 GEN
Solar/Wind Harmer
0
274723RIVER EC ;12
Adder
8.113
274801UNIV PARK;4U
Adder
2.59
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
23867002DVBSG1
50/50
14.11
23888502TROY G1
50/50
1.796
23888602TROY G2
50/50
1.796
971549AH1-272 GEN
Solar/Wind Harmer
10.011
247607V1-011 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
0.507
971771AH1-392 GEN
Solar/Wind Harmer
3.655
971769AH1-391 GEN
Solar/Wind Harmer
3.979
971567AH1-282 GEN
Solar/Wind Harmer
5.126
270071AF1-092 GEN
Solar/Wind Harmer
6.095
274728ELWOOD EC;5P
Adder
7.217
241886AC2-103 GEN2
Solar/Wind Helper
9.126
24189802OREGON_CT1
50/50
2.723
961051AF2-396 GEN
Solar/Wind Harmer
7.827
961051AF2-396 GEN
Solar/Wind Harmer
5.218
270216AD2-079_GEN
Solar/Wind Harmer
0.001
970627AG2-408 GEN
Solar/Wind Harmer
1.084
270224U2-072_GEN2
Solar/Wind Harmer
0
274803UNIV PARK;6U
Adder
2.599
274887GEN-1.85
Solar/Wind Harmer
0.081
274674JOLIET 9 ;6U
Adder
6.759
958481AF2-142 GEN
Solar/Wind Harmer
4.54
274862TOP CROP ;2U
Solar/Wind Harmer
0.409
274693ROCKY RD ;1P
Adder
4.751
274683WAUKEGAN ;8U
Adder
9.076
274683WAUKEGAN ;8U
Adder
7.65
203947AF1-006 C
Solar/Wind Helper
0.369
241967AE2-285_GEN
Solar/Wind Helper
0.329
23856402BAYSG1
50/50
1.209
241858AF1-205_GEN
Solar/Wind Harmer
3.76
241808AF1-120 C
Solar/Wind Harmer
0.003
972301AH1-735 GEN
Adder
6.461
270361_3
Solar/Wind Harmer
4.199
944231AF1-091 GEN
Solar/Wind Harmer
1.197
270063AE2-323 C
Solar/Wind Harmer
0.003
270462AD2-086
Solar/Wind Harmer
0.007
274754CRETE EC ;4U
Adder
3.76
958381AF2-132 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
7.217
274674JOLIET 9 ;6U
Adder
6.759
970245AG2-165 GEN
Solar/Wind Harmer
1.323
945641AF1-229 GEN
Solar/Wind Harmer
0.001
971619AH1-309 GEN
Solar/Wind Harmer
1.735
965051AG1-369 GEN
Solar/Wind Harmer
1.862
270317AD1-130_GEN
Solar/Wind Harmer
0.005
971347AH1-153 GEN
Solar/Wind Harmer
5.114
972037AH1-567 GEN1
Adder
0.082
960591AF2-350 GEN
Solar/Wind Harmer
3.094
971611AH1-305 GEN
Solar/Wind Harmer
1.842
274775LINCOLN ;6U
Adder
3.741
274777LINCOLN ;8U
Adder
3.741
274675JOLIET 29;7U
Adder
13.494
274675JOLIET 29;7U
Adder
13.012
970833AG2-524 GEN
Solar/Wind Harmer
3.353
970833AG2-524 GEN
Solar/Wind Harmer
2.235
203846AF2-130 C
Solar/Wind Helper
0.24
23906502RICHG2&3
Adder
1.289
270588AE1-091_GEN
Solar/Wind Harmer
3.195
247643Z2-116 C
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0.004
276806AD2-047 C O1
Solar/Wind Harmer
1.753
274676JOLIET 29;8U
Adder
13.012
274734ELWOOD EC;8P
Adder
7.217
274736ELWOOD EC;9P
Adder
7.217
943121AE2-341 GEN
Solar/Wind Harmer
5.076
943591AF1-030 GEN
Solar/Wind Harmer
3.375
274682WAUKEGAN ;7U
Adder
7.748
203830AF1-094 GEN
Solar/Wind Helper
0.313
970513AG2-328 GEN
Solar/Wind Harmer
1.323
970517AG2-330 GEN
Solar/Wind Harmer
7.937
276694AA1-018 GEN2
Solar/Wind Harmer
0
254305AE2-115 C
Solar/Wind Helper
0.109
970321AG2-212 GEN
Solar/Wind Harmer
1.323
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
274696ROCKY RD ;4P
Adder
4.912
274697ROCKY RD ;3P
Adder
1.303
241985AE1-237 GEN
Solar/Wind Helper
0.128
962101AG1-054 GEN
Solar/Wind Helper
0.317
23920202STRYCT
50/50
1.869
970515AG2-329 GEN
Solar/Wind Harmer
12.4
943021AE2-325 GEN
Solar/Wind Harmer
2.06
270223U2-072_GEN1
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
6.918
971917AH1-482 GEN
Solar/Wind Harmer
4.117
941551AE2-152 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.367
972211AH1-690 GEN
50/50
287.754
970817AG2-515 GEN
Solar/Wind Harmer
10.489
945411AF1-206 GEN
Solar/Wind Harmer
-0.001
270499AE1-146 GEN
Solar/Wind Harmer
0.027
270297AD1-101 GEN
Solar/Wind Harmer
0.001
965041AG1-368 GEN
Solar/Wind Harmer
3.753
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
270578AF1-285 GEN2
Solar/Wind Harmer
0.22
274814UNIV PK N;0U
Adder
2.277
274807UNIV PK N;3U
Adder
2.272
274805UNIV PK N;1U
Adder
2.262
274776LINCOLN ;7U
Adder
3.741
274687WILL CNTY;4U
Adder
12.315
274687WILL CNTY;4U
Adder
12.315
274731ELWOOD EC;2P
Adder
7.217
274733ELWOOD EC;3P
Adder
7.217
274746AC1-111 G10
Adder
2.426
241982AE2-343 S C
Solar/Wind Helper
0.114
254304AE2-114 C
Solar/Wind Helper
0.109
24189902OREGON_CT2
50/50
2.668
241840AF1-064_GEN
Solar/Wind Harmer
0.004
23906402RICHG1
Adder
1.292
23906502RICHG2&3
Adder
1.289
965421AG1-410 GEN
Solar/Wind Harmer
11.889
270449AD2-020 GEN
Solar/Wind Harmer
0
24695305TIMB G C
Solar/Wind Harmer
0.001
24639705ELKHART HY
Adder
0.082
247521TR3_G114
Solar/Wind Harmer
0.136
270246TR4_N_V150
Solar/Wind Harmer
0.024
957201AF2-014 GEN
Solar/Wind Harmer
0
971989AH1-539 GEN
Solar/Wind Harmer
1.661
270302AB2-170 GEN
Solar/Wind Harmer
0.002
971653AH1-327 GEN
Solar/Wind Harmer
0.502
963791AG1-232 GEN
Solar/Wind Harmer
4.516
270536AF1-215 GEN2
Solar/Wind Harmer
0.004
274811UNIV PK N;7U
Adder
2.257
958391AF2-133 GEN
Solar/Wind Harmer
0
274827FISK ;RP
Adder
3.452
972227AH1-698 GEN1
Adder
1.153
274735ELWOOD EC;4P
Adder
7.217
274744AC1-111 GEN8
Adder
2.426
270024AE2-089 GEN
Solar/Wind Harmer
0.003
241997AF1-093 GEN
Solar/Wind Helper
0.126
203804AE2-113_GEN
Solar/Wind Helper
0.838
24190002OREGON_ST1
50/50
3.59
971677AH1-339 GEN
Solar/Wind Harmer
0.601
965681AG1-436 GEN
Solar/Wind Harmer
4.283
270227U2-072_GEN3
Solar/Wind Harmer
0
270228U2-072_GEN4
Solar/Wind Harmer
0
270231U2-072_GEN5
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
203980AG1-197 GEN
Solar/Wind Helper
0.241
203979AG1-198 GEN
Solar/Wind Helper
0.188
241801AE1-079 GEN
Solar/Wind Helper
0.128
270055AF2-134 C O1
Solar/Wind Harmer
0.003
274812UNIV PK N;8U
Adder
2.257
276164X3-005 C
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
0.323
274676JOLIET 29;8U
Adder
13.494
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
2.426
274682WAUKEGAN ;7U
Adder
7.748
274828WAUKEGAN ;BP
Adder
4.757
203835AF1-098 GEN
Solar/Wind Helper
1.276
203860AG1-193 C
Solar/Wind Helper
0.145
241966AE1-183 GEN
Solar/Wind Helper
0.126
241807AE2-176_GEN
Solar/Wind Helper
0.764
971605AH1-302 GEN
Solar/Wind Harmer
3.867
274773LINCOLN ;4U
Adder
3.741
274774LINCOLN ;5U
Adder
3.741
241885AC2-103 GEN1
Solar/Wind Helper
9.126
961971AG1-040 GEN
Solar/Wind Helper
0.324
254303AC2-168 GEN
Solar/Wind Helper
0.074
990142J1224
External Queue
13.159761428833008
991177J1571 G
External Queue
15.044508934020996
991182J1586 G
External Queue
24.65229034423828
990527J1329
External Queue
1.8002409934997559
NYPJM->LTFIMP_NY
CLTF
1.957
LGEELTFEXP_LGEE->PJM
CLTF
1.943
WECLTFEXP_WEC->PJM
CLTF
1.608
AG2-052LTFEXP_AG2-052->PJM
LTF
0.104
AH1-155LTFEXP_AH1-155->PJM
LTF
0.155
CBM West 1LTFEXP_CBM-W1->PJM
CBM
91.866
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.603
MECLTFEXP_MEC->PJM
CLTF
6.264
SIGELTFEXP_SIGE->PJM
CLTF
0.162
LAGNLTFEXP_LAGN->PJM
CLTF
4.792
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.145
TVALTFEXP_TVA->PJM
CLTF
2.173
CPLELTFEXP_CPLE->PJM
CLTF
0.33
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.291

Details for 02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line l/o ATSI_P1-2_OEC-345-809_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_OEC-345-809_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:128.94 %
Rating:1646.0 MVA
Rating Type:B
MVA to Mitigate:2122.34
MW Contribution:0.51
Bus #Bus NameTypeMW Contribution
971989AH1-539 GEN
Solar/Wind Harmer
1.772
957201AF2-014 GEN
Solar/Wind Harmer
0
270302AB2-170 GEN
Solar/Wind Harmer
0.002
971653AH1-327 GEN
Solar/Wind Harmer
0.506
963791AG1-232 GEN
Solar/Wind Harmer
4.517
270536AF1-215 GEN2
Solar/Wind Harmer
0.004
274811UNIV PK N;7U
Adder
2.238
958391AF2-133 GEN
Solar/Wind Harmer
0
274827FISK ;RP
Adder
3.424
972227AH1-698 GEN1
Adder
1.144
274735ELWOOD EC;4P
Adder
7.16
270024AE2-089 GEN
Solar/Wind Harmer
0.003
274744AC1-111 GEN8
Adder
2.408
241997AF1-093 GEN
Solar/Wind Helper
0.128
203804AE2-113_GEN
Solar/Wind Helper
0.848
24189902OREGON_CT2
50/50
2.551
241840AF1-064_GEN
Solar/Wind Harmer
0.004
23906402RICHG1
Adder
1.308
23906502RICHG2&3
Adder
1.306
241807AE2-176_GEN
Solar/Wind Harmer
0.004
270428AC2-015 C
Solar/Wind Harmer
0.002
965421AG1-410 GEN
Solar/Wind Harmer
11.925
270449AD2-020 GEN
Solar/Wind Harmer
0
24695305TIMB G C
Solar/Wind Harmer
0.001
247521TR3_G114
Solar/Wind Harmer
0.137
270246TR4_N_V150
Solar/Wind Harmer
0.024
24639705ELKHART HY
Adder
0.082
270055AF2-134 C O1
Solar/Wind Harmer
0.002
274812UNIV PK N;8U
Adder
2.238
276164X3-005 C
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
0.32
274676JOLIET 29;8U
Adder
13.387
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
2.408
203835AF1-098 GEN
Solar/Wind Helper
1.293
203860AG1-193 C
Solar/Wind Helper
0.146
241966AE1-183 GEN
Solar/Wind Helper
0.128
23929302BS-PKR
50/50
2.254
958321AF2-126 GEN
Solar/Wind Harmer
1.148
270575GUS2 35KV
Solar/Wind Harmer
4.656
970217AG2-149 GEN
Solar/Wind Harmer
4.19
270258AD1-119 GEN
Solar/Wind Harmer
0.001
270491AE1-102 GEN2
Solar/Wind Harmer
0.522
270191TR4_S_V150
Solar/Wind Harmer
0.001
24642205MAYFLWER
Adder
0.338
959331AF2-224 GEN
Solar/Wind Harmer
2.528
274753CRETE EC ;3U
Adder
3.728
964401AG1-302 GEN
Solar/Wind Harmer
0
972038AH1-567 GEN2
Adder
0.161
971617AH1-308 GEN
Solar/Wind Harmer
2.523
962511AG1-100 GEN
Solar/Wind Helper
0.335
959441AF2-235 GEN
Solar/Wind Helper
0.144
20334926Z1-069 C
Solar/Wind Helper
0.632
23888802TROY G4
50/50
1.736
247620Y3-023
Adder
0.246
270526AF1-158 GEN
Solar/Wind Harmer
0.004
24441505OLIV SLR
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
3.111
971231AH1-075 GEN
Solar/Wind Harmer
0.374
276843GEN-1.7
Solar/Wind Harmer
0.099
958011AF2-095 GEN
Solar/Wind Harmer
4.42
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
946381AF1-302 GEN
Solar/Wind Helper
0.103
972211AH1-690 GEN
50/50
275.118
970817AG2-515 GEN
Solar/Wind Harmer
10.289
945411AF1-206 GEN
Solar/Wind Harmer
-0.001
270499AE1-146 GEN
Solar/Wind Harmer
0.029
270297AD1-101 GEN
Solar/Wind Harmer
0.001
965041AG1-368 GEN
Solar/Wind Harmer
3.769
24191202EL_AA1-006
Adder
0.112
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
270578AF1-285 GEN2
Solar/Wind Harmer
0.223
274814UNIV PK N;0U
Adder
2.258
274807UNIV PK N;3U
Adder
2.253
274805UNIV PK N;1U
Adder
2.243
274776LINCOLN ;7U
Adder
3.711
274687WILL CNTY;4U
Adder
12.217
274687WILL CNTY;4U
Adder
12.217
274731ELWOOD EC;2P
Adder
7.16
274733ELWOOD EC;3P
Adder
7.16
274746AC1-111 G10
Adder
2.408
241982AE2-343 S C
Solar/Wind Helper
0.116
254304AE2-114 C
Solar/Wind Helper
0.11
241832AE2-181_GEN
Solar/Wind Harmer
0.003
241996AE2-282_GEN
Solar/Wind Harmer
0.005
970621AG2-405 GEN
Solar/Wind Harmer
0.866
970623AG2-406 GEN
Solar/Wind Harmer
0.788
270007AE1-245 C
Solar/Wind Harmer
0.001
246938BC-WTG3
Solar/Wind Harmer
0.145
246937BC-WTG2
Solar/Wind Harmer
0.163
957891AF2-083 GEN
Solar/Wind Harmer
0.001
970611AG2-400 GEN
Solar/Wind Harmer
3.611
274808UNIV PK N;4U
Adder
2.229
274888KELLY CRK;1U
Solar/Wind Harmer
0.18
274770LINCOLN ;1U
Adder
3.711
274771LINCOLN ;2U
Adder
3.711
942221AE2-234 GEN
Solar/Wind Harmer
0.015
972259AH1-714 GEN
Adder
8.331
970321AG2-212 GEN
Solar/Wind Harmer
1.313
241985AE1-237 GEN
Solar/Wind Helper
0.129
962101AG1-054 GEN
Solar/Wind Helper
0.321
270541AE2-072 C
Solar/Wind Harmer
0.008
270404AC1-167 GEN
Solar/Wind Harmer
0.002
247604X1-042
Adder
0.249
270247TR4_N_V136
Solar/Wind Harmer
0.024
970031AG2-029 GEN
Solar/Wind Harmer
2.393
970349AG2-230 GEN
Solar/Wind Harmer
5.067
270391AF1-285 GEN3
Solar/Wind Harmer
0.223
270377AD1-106 GEN
Solar/Wind Harmer
1.238
274752CRETE EC ;2U
Adder
3.728
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
274826FISK ;BP
Adder
4.831
972228AH1-698 GEN2
Adder
1.625
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
9.926
274730ELWOOD EC;6P
Adder
7.16
970513AG2-328 GEN
Solar/Wind Harmer
1.313
970517AG2-330 GEN
Solar/Wind Harmer
7.878
276694AA1-018 GEN2
Solar/Wind Harmer
0
254305AE2-115 C
Solar/Wind Helper
0.11
23906502RICHG2&3
Adder
1.306
270588AE1-091_GEN
Solar/Wind Harmer
3.358
247643Z2-116 C
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0.004
276806AD2-047 C O1
Solar/Wind Harmer
1.739
274676JOLIET 29;8U
Adder
12.909
274734ELWOOD EC;8P
Adder
7.16
274736ELWOOD EC;9P
Adder
7.16
943121AE2-341 GEN
Solar/Wind Harmer
5.036
943591AF1-030 GEN
Solar/Wind Harmer
3.349
203830AF1-094 GEN
Solar/Wind Helper
0.317
24189802OREGON_CT1
50/50
2.603
961051AF2-396 GEN
Solar/Wind Harmer
7.735
961051AF2-396 GEN
Solar/Wind Harmer
5.157
270216AD2-079_GEN
Solar/Wind Harmer
0.001
970627AG2-408 GEN
Solar/Wind Harmer
1.083
270224U2-072_GEN2
Solar/Wind Harmer
0
274803UNIV PARK;6U
Adder
2.577
274887GEN-1.85
Solar/Wind Harmer
0.081
274674JOLIET 9 ;6U
Adder
6.706
958481AF2-142 GEN
Solar/Wind Harmer
4.505
274862TOP CROP ;2U
Solar/Wind Harmer
0.406
203947AF1-006 C
Solar/Wind Helper
0.374
241967AE2-285_GEN
Solar/Wind Helper
0.332
24190002OREGON_ST1
50/50
3.432
971677AH1-339 GEN
Solar/Wind Harmer
0.655
965681AG1-436 GEN
Solar/Wind Harmer
4.242
270227U2-072_GEN3
Solar/Wind Harmer
0
270228U2-072_GEN4
Solar/Wind Harmer
0
270231U2-072_GEN5
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
203980AG1-197 GEN
Solar/Wind Helper
0.244
203979AG1-198 GEN
Solar/Wind Helper
0.19
241801AE1-079 GEN
Solar/Wind Helper
0.129
23920202STRYCT
50/50
1.886
970515AG2-329 GEN
Solar/Wind Harmer
12.569
943021AE2-325 GEN
Solar/Wind Harmer
2.035
270223U2-072_GEN1
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
6.857
971917AH1-482 GEN
Solar/Wind Harmer
4.083
941551AE2-152 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.364
23888702TROY G3
50/50
1.736
972253AH1-711 GEN
50/50
53.019
960841AF2-375 GEN
Solar/Wind Harmer
-0.002
247522W1-056 GEN
Solar/Wind Harmer
0.001
246936BC-WTG1
Solar/Wind Harmer
0.163
270489AE1-102 GEN1
Solar/Wind Harmer
0.522
945111AF1-176 GEN
Solar/Wind Harmer
6.808
270505AE1-170 C O1
Solar/Wind Harmer
4.002
965011AG1-365 GEN
Solar/Wind Harmer
3.611
970905AG2-564 GEN
Solar/Wind Harmer
1.733
274751CRETE EC ;1U
Adder
3.728
964861AG1-349 GEN
Solar/Wind Harmer
0
274723RIVER EC ;12
Adder
8.046
274801UNIV PARK;4U
Adder
2.569
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
3.837
274773LINCOLN ;4U
Adder
3.711
274774LINCOLN ;5U
Adder
3.711
241885AC2-103 GEN1
Solar/Wind Helper
9.503
961971AG1-040 GEN
Solar/Wind Helper
0.328
254303AC2-168 GEN
Solar/Wind Helper
0.074
24441205WTRV SLR C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
3.093
965021AG1-366 GEN
Solar/Wind Harmer
1.204
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270043AE2-236 GEN
Solar/Wind Harmer
2.187
274724RIVER EC ;11
Adder
7.95
274802UNIV PARK;5U
Adder
2.577
274800UNIV PARK;3U
Adder
2.569
970941AG2-585 GEN
Solar/Wind Harmer
3.837
274772LINCOLN ;3U
Adder
3.711
276897AD1-100 C
Solar/Wind Harmer
0.004
276893AG1-478 C
Solar/Wind Harmer
0.12
274729ELWOOD EC;1P
Adder
7.16
23867002DVBSG1
50/50
12.729
23888502TROY G1
50/50
1.736
23888602TROY G2
50/50
1.736
971549AH1-272 GEN
Solar/Wind Harmer
9.844
247607V1-011 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
0.508
971771AH1-392 GEN
Solar/Wind Harmer
3.617
971769AH1-391 GEN
Solar/Wind Harmer
3.938
971567AH1-282 GEN
Solar/Wind Harmer
5.256
270071AF1-092 GEN
Solar/Wind Harmer
6.074
274728ELWOOD EC;5P
Adder
7.16
241886AC2-103 GEN2
Solar/Wind Helper
9.503
945641AF1-229 GEN
Solar/Wind Harmer
0.001
971619AH1-309 GEN
Solar/Wind Harmer
1.715
965051AG1-369 GEN
Solar/Wind Harmer
1.872
270317AD1-130_GEN
Solar/Wind Harmer
0.005
971347AH1-153 GEN
Solar/Wind Harmer
5.067
972037AH1-567 GEN1
Adder
0.081
971611AH1-305 GEN
Solar/Wind Harmer
1.828
960591AF2-350 GEN
Solar/Wind Harmer
3.069
274775LINCOLN ;6U
Adder
3.711
274777LINCOLN ;8U
Adder
3.711
274675JOLIET 29;7U
Adder
13.387
274675JOLIET 29;7U
Adder
12.909
970833AG2-524 GEN
Solar/Wind Harmer
3.326
970833AG2-524 GEN
Solar/Wind Harmer
2.217
203846AF2-130 C
Solar/Wind Helper
0.243
23856402BAYSG1
50/50
1.281
241858AF1-205_GEN
Solar/Wind Harmer
3.799
241808AF1-120 C
Solar/Wind Harmer
0.003
972301AH1-735 GEN
Adder
6.539
270361_3
Solar/Wind Harmer
4.656
944231AF1-091 GEN
Solar/Wind Harmer
1.201
270063AE2-323 C
Solar/Wind Harmer
0.003
270462AD2-086
Solar/Wind Harmer
0.008
274754CRETE EC ;4U
Adder
3.728
958381AF2-132 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
7.16
274674JOLIET 9 ;6U
Adder
6.706
970245AG2-165 GEN
Solar/Wind Harmer
1.313
990142J1224
External Queue
12.759525299072266
991177J1571 G
External Queue
14.724894523620605
991182J1586 G
External Queue
23.868927001953125
990527J1329
External Queue
1.745489239692688
NYPJM->LTFIMP_NY
CLTF
1.977
LGEELTFEXP_LGEE->PJM
CLTF
1.944
WECLTFEXP_WEC->PJM
CLTF
1.596
AG2-052LTFEXP_AG2-052->PJM
LTF
0.103
AH1-155LTFEXP_AH1-155->PJM
LTF
0.154
CBM West 1LTFEXP_CBM-W1->PJM
CBM
90.231
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.589
MECLTFEXP_MEC->PJM
CLTF
6.223
SIGELTFEXP_SIGE->PJM
CLTF
0.162
LAGNLTFEXP_LAGN->PJM
CLTF
4.775
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.139
TVALTFEXP_TVA->PJM
CLTF
2.168
CPLELTFEXP_CPLE->PJM
CLTF
0.326
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.144

Details for 02HAYES-02BEAVER 345.0 kV Ckt 1 line l/o ATSI_P1-2_OEC-345-825_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02HAYES-02BEAVER 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_OEC-345-825_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:136.05 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:2554.95
MW Contribution:0.55
Bus #Bus NameTypeMW Contribution
23929302BS-PKR
50/50
2.523
958321AF2-126 GEN
Solar/Wind Harmer
1.267
270575GUS2 35KV
Solar/Wind Harmer
5.343
970217AG2-149 GEN
Solar/Wind Harmer
4.562
270258AD1-119 GEN
Solar/Wind Harmer
0.001
270491AE1-102 GEN2
Solar/Wind Harmer
0.564
270191TR4_S_V150
Solar/Wind Harmer
0.001
24642205MAYFLWER
Adder
0.362
959331AF2-224 GEN
Solar/Wind Harmer
2.726
274753CRETE EC ;3U
Adder
4
964401AG1-302 GEN
Solar/Wind Harmer
0.001
972038AH1-567 GEN2
Adder
0.173
971617AH1-308 GEN
Solar/Wind Harmer
2.722
274872LEEDK;1U
Solar/Wind Harmer
0.116
23856402BAYSG1
50/50
1.433
241858AF1-205_GEN
Solar/Wind Harmer
4.134
241808AF1-120 C
Solar/Wind Harmer
0.003
972301AH1-735 GEN
Adder
7.119
270361_3
Solar/Wind Harmer
5.343
944231AF1-091 GEN
Solar/Wind Harmer
1.299
270063AE2-323 C
Solar/Wind Harmer
0.003
270462AD2-086
Solar/Wind Harmer
0.008
274754CRETE EC ;4U
Adder
4
958381AF2-132 GEN
Solar/Wind Harmer
0.001
274732ELWOOD EC;7P
Adder
7.682
274674JOLIET 9 ;6U
Adder
7.195
970245AG2-165 GEN
Solar/Wind Harmer
1.409
939401AE1-172 GEN
Solar/Wind Harmer
2.382
962781AG1-127 GEN
Solar/Wind Harmer
3.024
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
972235AH1-702 GEN1
Adder
1.13
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274766LEE CO EC;7U
Adder
0.439
24385905FR-11G C
Solar/Wind Harmer
0.001
270541AE2-072 C
Solar/Wind Harmer
0.009
270404AC1-167 GEN
Solar/Wind Harmer
0.002
247604X1-042
Adder
0.266
270247TR4_N_V136
Solar/Wind Harmer
0.026
970031AG2-029 GEN
Solar/Wind Harmer
2.571
270377AD1-106 GEN
Solar/Wind Harmer
1.42
270391AF1-285 GEN3
Solar/Wind Harmer
0.242
970349AG2-230 GEN
Solar/Wind Harmer
5.434
274752CRETE EC ;2U
Adder
4
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
274826FISK ;BP
Adder
5.184
972228AH1-698 GEN2
Adder
1.743
939351AE1-166 GEN
Solar/Wind Harmer
0
274730ELWOOD EC;6P
Adder
7.682
970707AG2-453 GEN
Solar/Wind Harmer
10.65
970513AG2-328 GEN
Solar/Wind Harmer
1.409
970517AG2-330 GEN
Solar/Wind Harmer
8.456
276694AA1-018 GEN2
Solar/Wind Harmer
0
944531AF1-118 GEN
Solar/Wind Harmer
14.389
970781AG2-491 GEN
Solar/Wind Harmer
3.176
274855GSG-6 ;RU
Solar/Wind Harmer
0.116
274853TWINGROVE;U1
Solar/Wind Harmer
0.001
959611AF2-252 GEN
Solar/Wind Harmer
1.007
254305AE2-115 C
Solar/Wind Helper
0.12
241996AE2-282_GEN
Solar/Wind Harmer
0.006
970621AG2-405 GEN
Solar/Wind Harmer
0.95
970623AG2-406 GEN
Solar/Wind Harmer
0.856
270007AE1-245 C
Solar/Wind Harmer
0.001
246938BC-WTG3
Solar/Wind Harmer
0.157
246937BC-WTG2
Solar/Wind Harmer
0.176
957891AF2-083 GEN
Solar/Wind Harmer
0.001
970611AG2-400 GEN
Solar/Wind Harmer
3.894
274808UNIV PK N;4U
Adder
2.391
942221AE2-234 GEN
Solar/Wind Harmer
0.017
274888KELLY CRK;1U
Solar/Wind Harmer
0.193
274770LINCOLN ;1U
Adder
3.982
274771LINCOLN ;2U
Adder
3.982
972259AH1-714 GEN
Adder
8.939
970321AG2-212 GEN
Solar/Wind Harmer
1.409
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
274696ROCKY RD ;4P
Adder
5.229
274697ROCKY RD ;3P
Adder
1.388
962691AG1-118 GEN
Solar/Wind Harmer
9.548
274856ECOGROVE ;U1
Solar/Wind Harmer
0.074
276611AD2-172 GEN
Solar/Wind Harmer
0.001
938861AE1-114 GEN
Solar/Wind Harmer
1.759
274762LEE CO EC;3U
Adder
4.129
276603SUBLETTE C
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.121
253378AE2-206_GEN
Solar/Wind Harmer
0.002
241985AE1-237 GEN
Solar/Wind Helper
0.141
962101AG1-054 GEN
Solar/Wind Helper
0.35
23920202STRYCT
50/50
2.05
970515AG2-329 GEN
Solar/Wind Harmer
13.687
943021AE2-325 GEN
Solar/Wind Harmer
2.179
270223U2-072_GEN1
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
7.354
971917AH1-482 GEN
Solar/Wind Harmer
4.381
941551AE2-152 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.39
24791305MDL-5G
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0.002
959081AF2-199 GEN
Solar/Wind Harmer
3.14
971067AG2-660 GEN
Solar/Wind Harmer
1.047
274822ROCKFORD ;11
Adder
8.814
970819AG2-516 GEN
Solar/Wind Harmer
3.745
971475AH1-234 GEN
Solar/Wind Harmer
1.512
276726Z2-087_GEN
Solar/Wind Harmer
0.001
274854TWINGROVE;U2
Solar/Wind Harmer
0.001
203954AE2-126 C
Solar/Wind Helper
0.234
972211AH1-690 GEN
50/50
288.807
24191202EL_AA1-006
50/50
0.334
970817AG2-515 GEN
Solar/Wind Harmer
10.986
945411AF1-206 GEN
Solar/Wind Harmer
-0.001
270499AE1-146 GEN
Solar/Wind Harmer
0.033
270297AD1-101 GEN
Solar/Wind Harmer
0.001
965041AG1-368 GEN
Solar/Wind Harmer
4.077
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
270578AF1-285 GEN2
Solar/Wind Harmer
0.242
274814UNIV PK N;0U
Adder
2.422
274807UNIV PK N;3U
Adder
2.417
274805UNIV PK N;1U
Adder
2.407
274776LINCOLN ;7U
Adder
3.982
274687WILL CNTY;4U
Adder
13.109
274687WILL CNTY;4U
Adder
13.109
274731ELWOOD EC;2P
Adder
7.682
274733ELWOOD EC;3P
Adder
7.682
274746AC1-111 G10
Adder
2.583
276882AE2-255 GEN
Solar/Wind Harmer
0.372
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24697905MDL-4G C
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
0.531
24386205FR-12G C
Solar/Wind Harmer
0
965101AG1-375 GEN
Solar/Wind Harmer
3.066
276655WTG1_EQ
Solar/Wind Harmer
0.001
963841AG1-237 GEN
Solar/Wind Harmer
1.315
971609AH1-304 GEN
Solar/Wind Harmer
0.493
241982AE2-343 S C
Solar/Wind Helper
0.126
254304AE2-114 C
Solar/Wind Helper
0.12
23888802TROY G4
50/50
1.836
247620Y3-023
Adder
0.264
270526AF1-158 GEN
Solar/Wind Harmer
0.005
24441505OLIV SLR
Solar/Wind Harmer
0
971231AH1-075 GEN
Solar/Wind Harmer
0.428
965791AG1-447 GEN
Solar/Wind Harmer
3.335
276843GEN-1.7
Solar/Wind Harmer
0.107
958011AF2-095 GEN
Solar/Wind Harmer
4.742
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
945421AF1-207 GEN
Solar/Wind Harmer
0
971573AH1-285 GEN
Solar/Wind Harmer
0.598
274695ROCKY RD ;2P
Adder
5.109
958491AF2-143 GEN
Solar/Wind Harmer
4.791
942991AE2-321 GEN
Solar/Wind Harmer
3.534
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
971333AH1-146 GEN
Solar/Wind Harmer
6.305
274765LEE CO EC;6U
Adder
4.139
274763LEE CO EC;4U
Adder
4.09
944541AF1-119 GEN
Solar/Wind Harmer
0.207
274851PROVIDENC;RU
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
0.121
270201AC2-176 GEN
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
0.227
970329AG2-216 GEN
Solar/Wind Harmer
1.305
270031AE2-169
Solar/Wind Harmer
1.66
946381AF1-302 GEN
Solar/Wind Helper
0.113
238217AF1-153 C O1
Solar/Wind Helper
0.119
23906502RICHG2&3
Adder
1.422
270588AE1-091_GEN
Solar/Wind Harmer
3.735
247643Z2-116 C
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0.004
276806AD2-047 C O1
Solar/Wind Harmer
1.866
274676JOLIET 29;8U
Adder
13.851
274734ELWOOD EC;8P
Adder
7.682
274736ELWOOD EC;9P
Adder
7.682
943121AE2-341 GEN
Solar/Wind Harmer
5.404
943591AF1-030 GEN
Solar/Wind Harmer
3.594
274682WAUKEGAN ;7U
Adder
8.249
24755605MDL-5G
Solar/Wind Harmer
0
959091AF2-200 GEN
Solar/Wind Harmer
6.279
247642Z2-115 C
Solar/Wind Harmer
0.001
203830AF1-094 GEN
Solar/Wind Helper
0.347
971989AH1-539 GEN
Solar/Wind Harmer
1.989
957201AF2-014 GEN
Solar/Wind Harmer
0
270302AB2-170 GEN
Solar/Wind Harmer
0.002
971653AH1-327 GEN
Solar/Wind Harmer
0.55
963791AG1-232 GEN
Solar/Wind Harmer
4.874
270536AF1-215 GEN2
Solar/Wind Harmer
0.004
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274811UNIV PK N;7U
Adder
2.401
274827FISK ;RP
Adder
3.674
972227AH1-698 GEN1
Adder
1.228
270024AE2-089 GEN
Solar/Wind Harmer
0.004
24190002OREGON_ST1
50/50
3.603
971677AH1-339 GEN
Solar/Wind Harmer
0.745
965681AG1-436 GEN
Solar/Wind Harmer
4.548
270227U2-072_GEN3
Solar/Wind Harmer
0
270228U2-072_GEN4
Solar/Wind Harmer
0
270231U2-072_GEN5
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
971341AH1-150 GEN
Solar/Wind Harmer
6.279
971343AH1-151 GEN
Solar/Wind Harmer
6.279
274849CRESCENT ;1U
Solar/Wind Harmer
0
276741O09 GEN1
Solar/Wind Harmer
0.109
276820AF1-078_GEN
Solar/Wind Harmer
0.001
203980AG1-197 GEN
Solar/Wind Helper
0.267
203979AG1-198 GEN
Solar/Wind Helper
0.208
241801AE1-079 GEN
Solar/Wind Helper
0.141
203853AF1-134 C O1
Solar/Wind Helper
0.221
24189902OREGON_CT2
50/50
2.678
241807AE2-176_GEN
Solar/Wind Harmer
0.009
241840AF1-064_GEN
Solar/Wind Harmer
0.004
23906402RICHG1
Adder
1.424
23906502RICHG2&3
Adder
1.422
270428AC2-015 C
Solar/Wind Harmer
0.003
965421AG1-410 GEN
Solar/Wind Harmer
12.895
24695305TIMB G C
Solar/Wind Harmer
0.001
270449AD2-020 GEN
Solar/Wind Harmer
0
247521TR3_G114
Solar/Wind Harmer
0.148
270246TR4_N_V150
Solar/Wind Harmer
0.026
24639705ELKHART HY
Adder
0.087
270055AF2-134 C O1
Solar/Wind Harmer
0.003
274812UNIV PK N;8U
Adder
2.401
276164X3-005 C
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
0.344
274676JOLIET 29;8U
Adder
14.364
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
2.583
274682WAUKEGAN ;7U
Adder
8.249
274828WAUKEGAN ;BP
Adder
5.065
276901AD2-066 C O1
Solar/Wind Harmer
0.003
957471AF2-041 GEN
Solar/Wind Harmer
9.419
965651AG1-433 GEN
Solar/Wind Harmer
0.908
274877BISHOP HL;1U
Solar/Wind Harmer
0.103
203835AF1-098 GEN
Solar/Wind Helper
1.414
203860AG1-193 C
Solar/Wind Helper
0.16
241966AE1-183 GEN
Solar/Wind Helper
0.139
274735ELWOOD EC;4P
Adder
7.682
274744AC1-111 GEN8
Adder
2.583
970169AG2-114 GEN
Solar/Wind Harmer
3.123
961011AF2-392 GEN
Solar/Wind Harmer
1.808
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
959341AF2-225 GEN
Solar/Wind Harmer
3.207
241997AF1-093 GEN
Solar/Wind Helper
0.139
203804AE2-113_GEN
Solar/Wind Helper
0.928
972236AH1-702 GEN2
Adder
0.983
274760LEE CO EC;1U
Adder
4.129
274878BISHOP HL;2U
Solar/Wind Harmer
0.103
965091AG1-374 GEN
Solar/Wind Harmer
9.061
965931AG1-462 GEN
Solar/Wind Harmer
7.661
962511AG1-100 GEN
Solar/Wind Helper
0.367
959441AF2-235 GEN
Solar/Wind Helper
0.158
20334926Z1-069 C
Solar/Wind Helper
0.691
203854AF2-039 C
Solar/Wind Helper
0.15
241832AE2-181_GEN
Solar/Wind Harmer
0.004
24441205WTRV SLR C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
3.313
270485AE1-090_GEN
Solar/Wind Harmer
0.001
965021AG1-366 GEN
Solar/Wind Harmer
1.298
270043AE2-236 GEN
Solar/Wind Harmer
2.353
274724RIVER EC ;11
Adder
8.529
274802UNIV PARK;5U
Adder
2.765
274800UNIV PARK;3U
Adder
2.756
970941AG2-585 GEN
Solar/Wind Harmer
4.117
274772LINCOLN ;3U
Adder
3.982
276897AD1-100 C
Solar/Wind Harmer
0.004
276893AG1-478 C
Solar/Wind Harmer
0.129
274729ELWOOD EC;1P
Adder
7.682
276805AD2-038 GEN
Solar/Wind Harmer
0.001
276889AE2-281 GEN
Solar/Wind Harmer
0
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.336
274850MENDOTA H;RU
Solar/Wind Harmer
0.037
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.057
970571AG2-364 GEN
Solar/Wind Harmer
6.257
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
276157O29GEN1
Solar/Wind Harmer
0.497
942111AE2-223 GEN
Solar/Wind Harmer
0.993
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
4.58
23888702TROY G3
50/50
1.836
972253AH1-711 GEN
50/50
56.068
23860302FRMENG 3
50/50
3.538
241885AC2-103 GEN1
Solar/Wind Harmer
-0.001
960841AF2-375 GEN
Solar/Wind Harmer
-0.002
247522W1-056 GEN
Solar/Wind Harmer
0.001
246936BC-WTG1
Solar/Wind Harmer
0.176
270489AE1-102 GEN1
Solar/Wind Harmer
0.564
970905AG2-564 GEN
Solar/Wind Harmer
2.266
945111AF1-176 GEN
Solar/Wind Harmer
7.294
270505AE1-170 C O1
Solar/Wind Harmer
4.287
965011AG1-365 GEN
Solar/Wind Harmer
3.894
274751CRETE EC ;1U
Adder
4
964861AG1-349 GEN
Solar/Wind Harmer
0
274723RIVER EC ;12
Adder
8.632
274801UNIV PARK;4U
Adder
2.756
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
4.118
274773LINCOLN ;4U
Adder
3.982
274774LINCOLN ;5U
Adder
3.982
971997AH1-543 GEN
Solar/Wind Harmer
1.662
276861AD2-134 GEN
Solar/Wind Harmer
0.057
970569AG2-363 GEN
Solar/Wind Harmer
9.385
274761LEE CO EC;2U
Adder
4.129
24387305FR-4G C
Solar/Wind Harmer
0.001
276158O29GEN2
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
1.328
939741AE1-205 GEN
Solar/Wind Harmer
4.276
945371AF1-202 GEN
Solar/Wind Harmer
0
961971AG1-040 GEN
Solar/Wind Helper
0.359
254303AC2-168 GEN
Solar/Wind Helper
0.081
23867002DVBSG1
50/50
12.822
23888502TROY G1
50/50
1.836
23888602TROY G2
50/50
1.836
23860102FRMENG 1
50/50
1.733
23860202FRMENG 2
50/50
1.733
241886AC2-103 GEN2
Solar/Wind Harmer
-0.001
971549AH1-272 GEN
Solar/Wind Harmer
10.515
247607V1-011 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
0.55
971771AH1-392 GEN
Solar/Wind Harmer
3.877
971567AH1-282 GEN
Solar/Wind Harmer
5.76
971769AH1-391 GEN
Solar/Wind Harmer
4.221
270071AF1-092 GEN
Solar/Wind Harmer
6.537
274728ELWOOD EC;5P
Adder
7.682
24729505KEY G4
Adder
2.957
24691005MDL-2G C
Solar/Wind Harmer
0.001
971177AH1-047 GEN
Solar/Wind Harmer
1.951
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
276612AE2-035 GEN
Solar/Wind Harmer
0.001
971681AH1-341 GEN
Solar/Wind Harmer
5
24386605FR-22G C
Solar/Wind Harmer
0
24387005FR-3G C
Solar/Wind Harmer
0.001
957751AF2-069 GEN
Solar/Wind Harmer
0.102
945641AF1-229 GEN
Solar/Wind Harmer
0.001
971619AH1-309 GEN
Solar/Wind Harmer
1.837
965051AG1-369 GEN
Solar/Wind Harmer
2.027
270317AD1-130_GEN
Solar/Wind Harmer
0.006
971347AH1-153 GEN
Solar/Wind Harmer
5.434
972037AH1-567 GEN1
Adder
0.087
971611AH1-305 GEN
Solar/Wind Harmer
1.961
960591AF2-350 GEN
Solar/Wind Harmer
3.293
274775LINCOLN ;6U
Adder
3.982
274777LINCOLN ;8U
Adder
3.982
274675JOLIET 29;7U
Adder
14.364
274675JOLIET 29;7U
Adder
13.851
970833AG2-524 GEN
Solar/Wind Harmer
3.569
970833AG2-524 GEN
Solar/Wind Harmer
2.379
276868AE1-113 GEN
Solar/Wind Harmer
0.638
24697605MDL-3G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
971411AH1-196 GEN
Solar/Wind Harmer
4.733
971675AH1-338 GEN
Solar/Wind Harmer
1.229
971171AH1-044 GEN
Solar/Wind Harmer
6.279
274823ROCKFORD ;21
Adder
8.75
24386405FR-21G C
Solar/Wind Harmer
0
276656WTG2_EQ
Solar/Wind Harmer
0
941731AE2-173 GEN
Solar/Wind Harmer
2.545
946321AF1-296 GEN
Solar/Wind Harmer
1.689
945581AF1-223 GEN
Solar/Wind Harmer
0
203846AF2-130 C
Solar/Wind Helper
0.266
203855AF2-088 C
Solar/Wind Helper
0.072
24189802OREGON_CT1
50/50
2.733
961051AF2-396 GEN
Solar/Wind Harmer
8.284
961051AF2-396 GEN
Solar/Wind Harmer
5.523
270216AD2-079_GEN
Solar/Wind Harmer
0.001
970627AG2-408 GEN
Solar/Wind Harmer
1.168
270224U2-072_GEN2
Solar/Wind Harmer
0
274803UNIV PARK;6U
Adder
2.765
274887GEN-1.85
Solar/Wind Harmer
0.087
274674JOLIET 9 ;6U
Adder
7.195
958481AF2-142 GEN
Solar/Wind Harmer
4.833
274862TOP CROP ;2U
Solar/Wind Harmer
0.436
274693ROCKY RD ;1P
Adder
5.059
274683WAUKEGAN ;8U
Adder
9.663
274683WAUKEGAN ;8U
Adder
8.145
274879MINONK ;1U
Solar/Wind Harmer
0.134
970921AG2-575 GEN
Solar/Wind Harmer
3.177
970921AG2-575 GEN
Solar/Wind Harmer
1.059
971335AH1-147 GEN
Solar/Wind Harmer
6.305
274764LEE CO EC;5U
Adder
4.139
966841AG1-555 GEN
Solar/Wind Harmer
0.35
960971AF2-388 GEN
Solar/Wind Harmer
1.815
276708O09 GEN2
Solar/Wind Harmer
0.109
276782AC1-033 GEN
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
1.007
270599AE1-208 GEN
Solar/Wind Harmer
2.766
203947AF1-006 C
Solar/Wind Helper
0.409
241967AE2-285_GEN
Solar/Wind Helper
0.363
20398826ARMNA MT
Solar/Wind Helper
0.706
990142J1224
External Queue
13.53333568572998
991177J1571 G
External Queue
15.714932441711426
991182J1586 G
External Queue
25.292837142944336
990527J1329
External Queue
1.8513455390930176
NYPJM->LTFIMP_NY
CLTF
2.164
LGEELTFEXP_LGEE->PJM
CLTF
2.094
WECLTFEXP_WEC->PJM
CLTF
1.712
AG2-052LTFEXP_AG2-052->PJM
LTF
0.11
AH1-155LTFEXP_AH1-155->PJM
LTF
0.165
CBM West 1LTFEXP_CBM-W1->PJM
CBM
96.287
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.224
MECLTFEXP_MEC->PJM
CLTF
6.679
SIGELTFEXP_SIGE->PJM
CLTF
0.174
LAGNLTFEXP_LAGN->PJM
CLTF
5.122
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.262
TVALTFEXP_TVA->PJM
CLTF
2.326
CPLELTFEXP_CPLE->PJM
CLTF
0.333
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.959

Details for 02HAYES-02BEAVER 345.0 kV Ckt 1 line l/o ATSI_P1-2_OEC-345-824_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02HAYES-02BEAVER 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_OEC-345-824_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:135.68 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:2548.09
MW Contribution:0.55
Bus #Bus NameTypeMW Contribution
23856402BAYSG1
50/50
1.434
270541AE2-072 C
Solar/Wind Harmer
0.009
270404AC1-167 GEN
Solar/Wind Harmer
0.002
247604X1-042
Adder
0.267
270247TR4_N_V136
Solar/Wind Harmer
0.026
970031AG2-029 GEN
Solar/Wind Harmer
2.575
270377AD1-106 GEN
Solar/Wind Harmer
1.422
270391AF1-285 GEN3
Solar/Wind Harmer
0.242
970349AG2-230 GEN
Solar/Wind Harmer
5.444
274752CRETE EC ;2U
Adder
4.008
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
274826FISK ;BP
Adder
5.194
972228AH1-698 GEN2
Adder
1.747
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
10.672
274730ELWOOD EC;6P
Adder
7.698
970513AG2-328 GEN
Solar/Wind Harmer
1.412
970517AG2-330 GEN
Solar/Wind Harmer
8.474
276694AA1-018 GEN2
Solar/Wind Harmer
0
944531AF1-118 GEN
Solar/Wind Harmer
14.419
970781AG2-491 GEN
Solar/Wind Harmer
3.183
274855GSG-6 ;RU
Solar/Wind Harmer
0.116
274853TWINGROVE;U1
Solar/Wind Harmer
0.001
959611AF2-252 GEN
Solar/Wind Harmer
1.009
254305AE2-115 C
Solar/Wind Helper
0.12
241996AE2-282_GEN
Solar/Wind Harmer
0.006
970621AG2-405 GEN
Solar/Wind Harmer
0.951
970623AG2-406 GEN
Solar/Wind Harmer
0.857
270007AE1-245 C
Solar/Wind Harmer
0.001
246938BC-WTG3
Solar/Wind Harmer
0.158
246937BC-WTG2
Solar/Wind Harmer
0.176
957891AF2-083 GEN
Solar/Wind Harmer
0.001
970611AG2-400 GEN
Solar/Wind Harmer
3.901
274808UNIV PK N;4U
Adder
2.396
942221AE2-234 GEN
Solar/Wind Harmer
0.017
274888KELLY CRK;1U
Solar/Wind Harmer
0.194
274770LINCOLN ;1U
Adder
3.991
274771LINCOLN ;2U
Adder
3.991
972259AH1-714 GEN
Adder
8.958
970321AG2-212 GEN
Solar/Wind Harmer
1.412
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
274696ROCKY RD ;4P
Adder
5.24
274697ROCKY RD ;3P
Adder
1.391
962691AG1-118 GEN
Solar/Wind Harmer
9.569
274856ECOGROVE ;U1
Solar/Wind Harmer
0.074
276611AD2-172 GEN
Solar/Wind Harmer
0.001
938861AE1-114 GEN
Solar/Wind Harmer
1.763
274762LEE CO EC;3U
Adder
4.138
276603SUBLETTE C
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.121
253378AE2-206_GEN
Solar/Wind Harmer
0.002
241985AE1-237 GEN
Solar/Wind Helper
0.14
962101AG1-054 GEN
Solar/Wind Helper
0.35
23920202STRYCT
50/50
2.052
970515AG2-329 GEN
Solar/Wind Harmer
13.704
943021AE2-325 GEN
Solar/Wind Harmer
2.182
270223U2-072_GEN1
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
7.368
971917AH1-482 GEN
Solar/Wind Harmer
4.39
941551AE2-152 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.391
24791305MDL-5G
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0.002
959081AF2-199 GEN
Solar/Wind Harmer
3.147
971067AG2-660 GEN
Solar/Wind Harmer
1.049
972211AH1-690 GEN
50/50
288.97
24191202EL_AA1-006
50/50
0.334
970817AG2-515 GEN
Solar/Wind Harmer
10.993
945411AF1-206 GEN
Solar/Wind Harmer
-0.001
270499AE1-146 GEN
Solar/Wind Harmer
0.033
270297AD1-101 GEN
Solar/Wind Harmer
0.001
965041AG1-368 GEN
Solar/Wind Harmer
4.084
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
270578AF1-285 GEN2
Solar/Wind Harmer
0.242
274814UNIV PK N;0U
Adder
2.427
274807UNIV PK N;3U
Adder
2.422
274805UNIV PK N;1U
Adder
2.412
274776LINCOLN ;7U
Adder
3.991
274687WILL CNTY;4U
Adder
13.136
274687WILL CNTY;4U
Adder
13.136
274731ELWOOD EC;2P
Adder
7.698
274733ELWOOD EC;3P
Adder
7.698
274746AC1-111 G10
Adder
2.589
276882AE2-255 GEN
Solar/Wind Harmer
0.372
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24697905MDL-4G C
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
0.532
24386205FR-12G C
Solar/Wind Harmer
0
965101AG1-375 GEN
Solar/Wind Harmer
3.072
276655WTG1_EQ
Solar/Wind Harmer
0.001
963841AG1-237 GEN
Solar/Wind Harmer
1.318
971609AH1-304 GEN
Solar/Wind Harmer
0.494
241982AE2-343 S C
Solar/Wind Helper
0.126
254304AE2-114 C
Solar/Wind Helper
0.12
23888802TROY G4
50/50
1.837
247620Y3-023
Adder
0.264
270526AF1-158 GEN
Solar/Wind Harmer
0.005
24441505OLIV SLR
Solar/Wind Harmer
0
971231AH1-075 GEN
Solar/Wind Harmer
0.429
965791AG1-447 GEN
Solar/Wind Harmer
3.341
276843GEN-1.7
Solar/Wind Harmer
0.107
958011AF2-095 GEN
Solar/Wind Harmer
4.752
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
945421AF1-207 GEN
Solar/Wind Harmer
0
971573AH1-285 GEN
Solar/Wind Harmer
0.6
274695ROCKY RD ;2P
Adder
5.12
958491AF2-143 GEN
Solar/Wind Harmer
4.801
942991AE2-321 GEN
Solar/Wind Harmer
3.541
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
971333AH1-146 GEN
Solar/Wind Harmer
6.319
274765LEE CO EC;6U
Adder
4.148
274763LEE CO EC;4U
Adder
4.099
944541AF1-119 GEN
Solar/Wind Harmer
0.208
274851PROVIDENC;RU
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
0.121
270201AC2-176 GEN
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
0.227
970329AG2-216 GEN
Solar/Wind Harmer
1.308
270031AE2-169
Solar/Wind Harmer
1.663
946381AF1-302 GEN
Solar/Wind Helper
0.112
238217AF1-153 C O1
Solar/Wind Helper
0.119
23906502RICHG2&3
Adder
1.423
270588AE1-091_GEN
Solar/Wind Harmer
3.741
247643Z2-116 C
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0.004
276806AD2-047 C O1
Solar/Wind Harmer
1.87
274676JOLIET 29;8U
Adder
13.879
274734ELWOOD EC;8P
Adder
7.698
274736ELWOOD EC;9P
Adder
7.698
943121AE2-341 GEN
Solar/Wind Harmer
5.415
943591AF1-030 GEN
Solar/Wind Harmer
3.601
274682WAUKEGAN ;7U
Adder
8.266
24755605MDL-5G
Solar/Wind Harmer
0
24190002OREGON_ST1
50/50
3.605
971677AH1-339 GEN
Solar/Wind Harmer
0.746
965681AG1-436 GEN
Solar/Wind Harmer
4.556
24189902OREGON_CT2
50/50
2.68
241807AE2-176_GEN
Solar/Wind Harmer
0.009
241840AF1-064_GEN
Solar/Wind Harmer
0.004
23906402RICHG1
Adder
1.425
23906502RICHG2&3
Adder
1.423
270428AC2-015 C
Solar/Wind Harmer
0.003
965421AG1-410 GEN
Solar/Wind Harmer
12.915
24695305TIMB G C
Solar/Wind Harmer
0.001
270449AD2-020 GEN
Solar/Wind Harmer
0
247521TR3_G114
Solar/Wind Harmer
0.148
270246TR4_N_V150
Solar/Wind Harmer
0.026
24639705ELKHART HY
Adder
0.088
270055AF2-134 C O1
Solar/Wind Harmer
0.003
274812UNIV PK N;8U
Adder
2.406
276164X3-005 C
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
0.345
274676JOLIET 29;8U
Adder
14.394
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
2.589
274682WAUKEGAN ;7U
Adder
8.266
274828WAUKEGAN ;BP
Adder
5.076
276901AD2-066 C O1
Solar/Wind Harmer
0.003
957471AF2-041 GEN
Solar/Wind Harmer
9.44
965651AG1-433 GEN
Solar/Wind Harmer
0.909
274877BISHOP HL;1U
Solar/Wind Harmer
0.103
203835AF1-098 GEN
Solar/Wind Helper
1.412
203860AG1-193 C
Solar/Wind Helper
0.16
241966AE1-183 GEN
Solar/Wind Helper
0.139
971989AH1-539 GEN
Solar/Wind Harmer
1.992
957201AF2-014 GEN
Solar/Wind Harmer
0
270302AB2-170 GEN
Solar/Wind Harmer
0.002
971653AH1-327 GEN
Solar/Wind Harmer
0.551
963791AG1-232 GEN
Solar/Wind Harmer
4.883
270536AF1-215 GEN2
Solar/Wind Harmer
0.004
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274811UNIV PK N;7U
Adder
2.406
274827FISK ;RP
Adder
3.681
972227AH1-698 GEN1
Adder
1.23
270024AE2-089 GEN
Solar/Wind Harmer
0.004
274735ELWOOD EC;4P
Adder
7.698
274744AC1-111 GEN8
Adder
2.589
970169AG2-114 GEN
Solar/Wind Harmer
3.129
961011AF2-392 GEN
Solar/Wind Harmer
1.812
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
959341AF2-225 GEN
Solar/Wind Harmer
3.214
241997AF1-093 GEN
Solar/Wind Helper
0.139
203804AE2-113_GEN
Solar/Wind Helper
0.926
959091AF2-200 GEN
Solar/Wind Harmer
6.293
247642Z2-115 C
Solar/Wind Harmer
0.001
203830AF1-094 GEN
Solar/Wind Helper
0.347
23929302BS-PKR
50/50
2.524
958321AF2-126 GEN
Solar/Wind Harmer
1.268
270575GUS2 35KV
Solar/Wind Harmer
5.347
970217AG2-149 GEN
Solar/Wind Harmer
4.568
270258AD1-119 GEN
Solar/Wind Harmer
0.001
270491AE1-102 GEN2
Solar/Wind Harmer
0.565
270191TR4_S_V150
Solar/Wind Harmer
0.001
24642205MAYFLWER
Adder
0.363
959331AF2-224 GEN
Solar/Wind Harmer
2.73
274753CRETE EC ;3U
Adder
4.008
964401AG1-302 GEN
Solar/Wind Harmer
0.001
972038AH1-567 GEN2
Adder
0.173
971617AH1-308 GEN
Solar/Wind Harmer
2.727
274872LEEDK;1U
Solar/Wind Harmer
0.117
972236AH1-702 GEN2
Adder
0.985
274760LEE CO EC;1U
Adder
4.138
274878BISHOP HL;2U
Solar/Wind Harmer
0.103
965091AG1-374 GEN
Solar/Wind Harmer
9.081
965931AG1-462 GEN
Solar/Wind Harmer
7.678
962511AG1-100 GEN
Solar/Wind Helper
0.366
959441AF2-235 GEN
Solar/Wind Helper
0.157
20334926Z1-069 C
Solar/Wind Helper
0.689
203854AF2-039 C
Solar/Wind Helper
0.149
241832AE2-181_GEN
Solar/Wind Harmer
0.004
24441205WTRV SLR C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
3.319
270485AE1-090_GEN
Solar/Wind Harmer
0.001
965021AG1-366 GEN
Solar/Wind Harmer
1.3
270043AE2-236 GEN
Solar/Wind Harmer
2.357
274724RIVER EC ;11
Adder
8.546
274802UNIV PARK;5U
Adder
2.771
274800UNIV PARK;3U
Adder
2.762
970941AG2-585 GEN
Solar/Wind Harmer
4.125
274772LINCOLN ;3U
Adder
3.991
276897AD1-100 C
Solar/Wind Harmer
0.004
276893AG1-478 C
Solar/Wind Harmer
0.13
274729ELWOOD EC;1P
Adder
7.698
276805AD2-038 GEN
Solar/Wind Harmer
0.001
276889AE2-281 GEN
Solar/Wind Harmer
0
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.337
274850MENDOTA H;RU
Solar/Wind Harmer
0.037
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.057
970571AG2-364 GEN
Solar/Wind Harmer
6.27
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
276157O29GEN1
Solar/Wind Harmer
0.498
942111AE2-223 GEN
Solar/Wind Harmer
0.995
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
4.59
23888702TROY G3
50/50
1.837
972253AH1-711 GEN
50/50
56.101
23860302FRMENG 3
50/50
3.54
960841AF2-375 GEN
Solar/Wind Harmer
-0.002
247522W1-056 GEN
Solar/Wind Harmer
0.001
246936BC-WTG1
Solar/Wind Harmer
0.176
270489AE1-102 GEN1
Solar/Wind Harmer
0.565
970905AG2-564 GEN
Solar/Wind Harmer
2.27
945111AF1-176 GEN
Solar/Wind Harmer
7.306
270505AE1-170 C O1
Solar/Wind Harmer
4.294
965011AG1-365 GEN
Solar/Wind Harmer
3.901
274751CRETE EC ;1U
Adder
4.008
964861AG1-349 GEN
Solar/Wind Harmer
0
274723RIVER EC ;12
Adder
8.649
274801UNIV PARK;4U
Adder
2.762
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
4.126
274773LINCOLN ;4U
Adder
3.991
274774LINCOLN ;5U
Adder
3.991
971997AH1-543 GEN
Solar/Wind Harmer
1.665
276861AD2-134 GEN
Solar/Wind Harmer
0.057
970569AG2-363 GEN
Solar/Wind Harmer
9.405
274761LEE CO EC;2U
Adder
4.138
24387305FR-4G C
Solar/Wind Harmer
0.001
276158O29GEN2
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
1.331
939741AE1-205 GEN
Solar/Wind Harmer
4.286
945371AF1-202 GEN
Solar/Wind Harmer
0
241885AC2-103 GEN1
Solar/Wind Helper
4.614
961971AG1-040 GEN
Solar/Wind Helper
0.358
254303AC2-168 GEN
Solar/Wind Helper
0.081
23867002DVBSG1
50/50
12.828
23888502TROY G1
50/50
1.837
23888602TROY G2
50/50
1.837
23860102FRMENG 1
50/50
1.734
23860202FRMENG 2
50/50
1.734
971549AH1-272 GEN
Solar/Wind Harmer
10.529
247607V1-011 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
0.551
971771AH1-392 GEN
Solar/Wind Harmer
3.884
971567AH1-282 GEN
Solar/Wind Harmer
5.77
971769AH1-391 GEN
Solar/Wind Harmer
4.229
270071AF1-092 GEN
Solar/Wind Harmer
6.55
274728ELWOOD EC;5P
Adder
7.698
24729505KEY G4
Adder
2.963
24691005MDL-2G C
Solar/Wind Harmer
0.001
971177AH1-047 GEN
Solar/Wind Harmer
1.955
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
276612AE2-035 GEN
Solar/Wind Harmer
0.001
971681AH1-341 GEN
Solar/Wind Harmer
5.011
24386605FR-22G C
Solar/Wind Harmer
0
24387005FR-3G C
Solar/Wind Harmer
0.001
957751AF2-069 GEN
Solar/Wind Harmer
0.102
241886AC2-103 GEN2
Solar/Wind Helper
4.614
274822ROCKFORD ;11
Adder
8.833
970819AG2-516 GEN
Solar/Wind Harmer
3.753
971475AH1-234 GEN
Solar/Wind Harmer
1.515
276726Z2-087_GEN
Solar/Wind Harmer
0.001
274854TWINGROVE;U2
Solar/Wind Harmer
0.001
203954AE2-126 C
Solar/Wind Helper
0.233
945641AF1-229 GEN
Solar/Wind Harmer
0.001
971619AH1-309 GEN
Solar/Wind Harmer
1.84
965051AG1-369 GEN
Solar/Wind Harmer
2.03
270317AD1-130_GEN
Solar/Wind Harmer
0.006
971347AH1-153 GEN
Solar/Wind Harmer
5.444
972037AH1-567 GEN1
Adder
0.087
971611AH1-305 GEN
Solar/Wind Harmer
1.965
960591AF2-350 GEN
Solar/Wind Harmer
3.3
274775LINCOLN ;6U
Adder
3.991
274777LINCOLN ;8U
Adder
3.991
274675JOLIET 29;7U
Adder
14.394
274675JOLIET 29;7U
Adder
13.88
970833AG2-524 GEN
Solar/Wind Harmer
3.577
970833AG2-524 GEN
Solar/Wind Harmer
2.384
276868AE1-113 GEN
Solar/Wind Harmer
0.639
24697605MDL-3G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
971411AH1-196 GEN
Solar/Wind Harmer
4.743
971675AH1-338 GEN
Solar/Wind Harmer
1.232
971171AH1-044 GEN
Solar/Wind Harmer
6.293
274823ROCKFORD ;21
Adder
8.769
24386405FR-21G C
Solar/Wind Harmer
0
276656WTG2_EQ
Solar/Wind Harmer
0
941731AE2-173 GEN
Solar/Wind Harmer
2.551
946321AF1-296 GEN
Solar/Wind Harmer
1.693
945581AF1-223 GEN
Solar/Wind Harmer
0
203846AF2-130 C
Solar/Wind Helper
0.265
203855AF2-088 C
Solar/Wind Helper
0.072
24189802OREGON_CT1
50/50
2.735
961051AF2-396 GEN
Solar/Wind Harmer
8.298
961051AF2-396 GEN
Solar/Wind Harmer
5.532
270216AD2-079_GEN
Solar/Wind Harmer
0.001
970627AG2-408 GEN
Solar/Wind Harmer
1.17
270224U2-072_GEN2
Solar/Wind Harmer
0
274803UNIV PARK;6U
Adder
2.771
274887GEN-1.85
Solar/Wind Harmer
0.087
274674JOLIET 9 ;6U
Adder
7.21
958481AF2-142 GEN
Solar/Wind Harmer
4.844
274862TOP CROP ;2U
Solar/Wind Harmer
0.437
274693ROCKY RD ;1P
Adder
5.069
274683WAUKEGAN ;8U
Adder
9.683
274683WAUKEGAN ;8U
Adder
8.163
274879MINONK ;1U
Solar/Wind Harmer
0.134
970921AG2-575 GEN
Solar/Wind Harmer
3.184
970921AG2-575 GEN
Solar/Wind Harmer
1.061
971335AH1-147 GEN
Solar/Wind Harmer
6.319
274764LEE CO EC;5U
Adder
4.148
966841AG1-555 GEN
Solar/Wind Harmer
0.351
960971AF2-388 GEN
Solar/Wind Harmer
1.819
276708O09 GEN2
Solar/Wind Harmer
0.11
276782AC1-033 GEN
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
1.009
270599AE1-208 GEN
Solar/Wind Harmer
2.772
203947AF1-006 C
Solar/Wind Helper
0.408
241967AE2-285_GEN
Solar/Wind Helper
0.362
20398826ARMNA MT
Solar/Wind Helper
0.704
270227U2-072_GEN3
Solar/Wind Harmer
0
270228U2-072_GEN4
Solar/Wind Harmer
0
270231U2-072_GEN5
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
971341AH1-150 GEN
Solar/Wind Harmer
6.293
971343AH1-151 GEN
Solar/Wind Harmer
6.293
274849CRESCENT ;1U
Solar/Wind Harmer
0
276741O09 GEN1
Solar/Wind Harmer
0.11
276820AF1-078_GEN
Solar/Wind Harmer
0.001
203980AG1-197 GEN
Solar/Wind Helper
0.267
203979AG1-198 GEN
Solar/Wind Helper
0.208
241801AE1-079 GEN
Solar/Wind Helper
0.141
241858AF1-205_GEN
Solar/Wind Harmer
4.136
241808AF1-120 C
Solar/Wind Harmer
0.003
972301AH1-735 GEN
Adder
7.125
270361_3
Solar/Wind Harmer
5.347
944231AF1-091 GEN
Solar/Wind Harmer
1.301
270063AE2-323 C
Solar/Wind Harmer
0.003
270462AD2-086
Solar/Wind Harmer
0.008
274754CRETE EC ;4U
Adder
4.008
958381AF2-132 GEN
Solar/Wind Harmer
0.001
274732ELWOOD EC;7P
Adder
7.698
274674JOLIET 9 ;6U
Adder
7.21
970245AG2-165 GEN
Solar/Wind Harmer
1.412
939401AE1-172 GEN
Solar/Wind Harmer
2.387
962781AG1-127 GEN
Solar/Wind Harmer
3.03
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
972235AH1-702 GEN1
Adder
1.133
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274766LEE CO EC;7U
Adder
0.44
24385905FR-11G C
Solar/Wind Harmer
0.001
990142J1224
External Queue
13.53333568572998
991177J1571 G
External Queue
15.714932441711426
991182J1586 G
External Queue
25.292837142944336
990527J1329
External Queue
1.8513455390930176
NYPJM->LTFIMP_NY
CLTF
2.158
LGEELTFEXP_LGEE->PJM
CLTF
2.101
WECLTFEXP_WEC->PJM
CLTF
1.716
AG2-052LTFEXP_AG2-052->PJM
LTF
0.11
AH1-155LTFEXP_AH1-155->PJM
LTF
0.166
CBM West 1LTFEXP_CBM-W1->PJM
CBM
96.429
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.261
MECLTFEXP_MEC->PJM
CLTF
6.695
SIGELTFEXP_SIGE->PJM
CLTF
0.175
LAGNLTFEXP_LAGN->PJM
CLTF
5.142
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.292
TVALTFEXP_TVA->PJM
CLTF
2.336
CPLELTFEXP_CPLE->PJM
CLTF
0.344
CBM West 2LTFEXP_CBM-W2->PJM
CBM
41.091

Details for 02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line l/o ATSI_P1-2_TE-345-601_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_TE-345-601_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.99 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:2140.73
MW Contribution:0.62
Bus #Bus NameTypeMW Contribution
23888802TROY G4
50/50
2.643
247620Y3-023
Adder
0.301
270526AF1-158 GEN
Solar/Wind Harmer
0.005
24441505OLIV SLR
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
3.817
276843GEN-1.7
Solar/Wind Harmer
0.123
958011AF2-095 GEN
Solar/Wind Harmer
5.459
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
945421AF1-207 GEN
Solar/Wind Harmer
0
971573AH1-285 GEN
Solar/Wind Harmer
0.69
274695ROCKY RD ;2P
Adder
5.891
958491AF2-143 GEN
Solar/Wind Harmer
5.526
942991AE2-321 GEN
Solar/Wind Harmer
4.078
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
971333AH1-146 GEN
Solar/Wind Harmer
7.279
971231AH1-075 GEN
Solar/Wind Harmer
0.412
274765LEE CO EC;6U
Adder
4.784
274763LEE CO EC;4U
Adder
4.727
944541AF1-119 GEN
Solar/Wind Harmer
0.239
274851PROVIDENC;RU
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
0.14
270201AC2-176 GEN
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
0.262
270031AE2-169
Solar/Wind Harmer
1.917
970329AG2-216 GEN
Solar/Wind Harmer
1.487
960441AF2-335 GEN
Solar/Wind Harmer
3.372
970885AG2-551 GEN
Solar/Wind Harmer
1.115
946381AF1-302 GEN
Solar/Wind Helper
0.108
238217AF1-153 C O1
Solar/Wind Helper
0.114
270541AE2-072 C
Solar/Wind Harmer
0.01
23906902RICHG6
50/50
1.04
23906702RICHG4
50/50
1.037
945641AF1-229 GEN
Solar/Wind Harmer
0.001
971619AH1-309 GEN
Solar/Wind Harmer
2.091
965051AG1-369 GEN
Solar/Wind Harmer
2.289
270317AD1-130_GEN
Solar/Wind Harmer
0.006
971347AH1-153 GEN
Solar/Wind Harmer
6.22
972037AH1-567 GEN1
Adder
0.1
971611AH1-305 GEN
Solar/Wind Harmer
2.257
960591AF2-350 GEN
Solar/Wind Harmer
3.791
274775LINCOLN ;6U
Adder
4.584
274777LINCOLN ;8U
Adder
4.584
274675JOLIET 29;7U
Adder
16.543
274675JOLIET 29;7U
Adder
15.952
970833AG2-524 GEN
Solar/Wind Harmer
4.112
970833AG2-524 GEN
Solar/Wind Harmer
2.741
276868AE1-113 GEN
Solar/Wind Harmer
0.736
24697605MDL-3G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
971411AH1-196 GEN
Solar/Wind Harmer
5.463
971675AH1-338 GEN
Solar/Wind Harmer
1.419
971171AH1-044 GEN
Solar/Wind Harmer
7.251
274823ROCKFORD ;21
Adder
10.105
24386405FR-21G C
Solar/Wind Harmer
0
276656WTG2_EQ
Solar/Wind Harmer
0
941731AE2-173 GEN
Solar/Wind Harmer
2.944
946321AF1-296 GEN
Solar/Wind Harmer
1.955
945581AF1-223 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0.001
203846AF2-130 C
Solar/Wind Helper
0.257
241996AE2-282_GEN
Solar/Wind Harmer
0.007
970621AG2-405 GEN
Solar/Wind Harmer
1.043
970623AG2-406 GEN
Solar/Wind Harmer
0.966
270007AE1-245 C
Solar/Wind Harmer
0.001
246938BC-WTG3
Solar/Wind Harmer
0.178
246937BC-WTG2
Solar/Wind Harmer
0.199
957891AF2-083 GEN
Solar/Wind Harmer
0.001
970611AG2-400 GEN
Solar/Wind Harmer
4.433
274808UNIV PK N;4U
Adder
2.75
942221AE2-234 GEN
Solar/Wind Harmer
0.019
274888KELLY CRK;1U
Solar/Wind Harmer
0.223
274770LINCOLN ;1U
Adder
4.584
274771LINCOLN ;2U
Adder
4.584
972259AH1-714 GEN
Adder
10.294
970321AG2-212 GEN
Solar/Wind Harmer
1.623
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
274697ROCKY RD ;3P
Adder
1.6
274696ROCKY RD ;4P
Adder
6.03
962691AG1-118 GEN
Solar/Wind Harmer
11.015
274856ECOGROVE ;U1
Solar/Wind Harmer
0.085
276611AD2-172 GEN
Solar/Wind Harmer
0.001
938861AE1-114 GEN
Solar/Wind Harmer
2.033
274762LEE CO EC;3U
Adder
4.772
276603SUBLETTE C
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.14
970241AG2-163 GEN
Solar/Wind Harmer
2.013
253378AE2-206_GEN
Solar/Wind Harmer
0.002
970825AG2-519 GEN
Solar/Wind Harmer
3.73
241985AE1-237 GEN
Solar/Wind Helper
0.137
962101AG1-054 GEN
Solar/Wind Helper
0.34
972211AH1-690 GEN
50/50
234.282
23906802RICHG5
50/50
0.758
970817AG2-515 GEN
Solar/Wind Harmer
14.376
945411AF1-206 GEN
Solar/Wind Harmer
-0.001
270499AE1-146 GEN
Solar/Wind Harmer
0.032
270297AD1-101 GEN
Solar/Wind Harmer
0.001
965041AG1-368 GEN
Solar/Wind Harmer
4.612
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
270578AF1-285 GEN2
Solar/Wind Harmer
0.274
274814UNIV PK N;0U
Adder
2.786
274807UNIV PK N;3U
Adder
2.78
274805UNIV PK N;1U
Adder
2.768
274776LINCOLN ;7U
Adder
4.584
274687WILL CNTY;4U
Adder
15.095
274687WILL CNTY;4U
Adder
15.095
274731ELWOOD EC;2P
Adder
8.848
274733ELWOOD EC;3P
Adder
8.848
274746AC1-111 G10
Adder
2.978
276882AE2-255 GEN
Solar/Wind Harmer
0.429
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24697905MDL-4G C
Solar/Wind Harmer
0.001
926823AC1-168 GEN
Solar/Wind Harmer
0.613
24386205FR-12G C
Solar/Wind Harmer
0.001
965101AG1-375 GEN
Solar/Wind Harmer
3.538
276655WTG1_EQ
Solar/Wind Harmer
0.001
963841AG1-237 GEN
Solar/Wind Harmer
1.521
971609AH1-304 GEN
Solar/Wind Harmer
0.569
970115AG2-085 GEN
Solar/Wind Harmer
1.349
24699105WLD G1 C
Solar/Wind Harmer
0
241982AE2-343 S C
Solar/Wind Helper
0.123
254304AE2-114 C
Solar/Wind Helper
0.117
957201AF2-014 GEN
Solar/Wind Harmer
0
971989AH1-539 GEN
Solar/Wind Harmer
2.024
270302AB2-170 GEN
Solar/Wind Harmer
0.003
971653AH1-327 GEN
Solar/Wind Harmer
0.621
963791AG1-232 GEN
Solar/Wind Harmer
5.569
270536AF1-215 GEN2
Solar/Wind Harmer
0.005
274811UNIV PK N;7U
Adder
2.762
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274827FISK ;RP
Adder
4.228
972227AH1-698 GEN1
Adder
1.413
274735ELWOOD EC;4P
Adder
8.848
270024AE2-089 GEN
Solar/Wind Harmer
0.004
274744AC1-111 GEN8
Adder
2.978
970169AG2-114 GEN
Solar/Wind Harmer
3.606
961011AF2-392 GEN
Solar/Wind Harmer
2.09
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
959341AF2-225 GEN
Solar/Wind Harmer
3.709
970289AG2-191 GEN
Solar/Wind Harmer
0.655
276785W4-005 GEN1
Solar/Wind Harmer
0
276849AB2-070 GEN2
Solar/Wind Harmer
0.123
276848AB2-070 GEN3
Solar/Wind Harmer
0.123
241997AF1-093 GEN
Solar/Wind Helper
0.136
203804AE2-113_GEN
Solar/Wind Helper
0.892
23906502RICHG2&3
50/50
1.747
270588AE1-091_GEN
Solar/Wind Harmer
3.901
247643Z2-116 C
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0.005
276806AD2-047 C O1
Solar/Wind Harmer
2.148
274676JOLIET 29;8U
Adder
15.952
274734ELWOOD EC;8P
Adder
8.849
274736ELWOOD EC;9P
Adder
8.849
943121AE2-341 GEN
Solar/Wind Harmer
6.229
943591AF1-030 GEN
Solar/Wind Harmer
4.142
274682WAUKEGAN ;7U
Adder
9.512
24755605MDL-5G
Solar/Wind Harmer
0
959091AF2-200 GEN
Solar/Wind Harmer
7.251
274767LEE CO EC;8U
Adder
0.229
247642Z2-115 C
Solar/Wind Harmer
0.002
970289AG2-191 GEN
Solar/Wind Harmer
0.379
970291AG2-192 GEN
Solar/Wind Harmer
0.345
276668AB2-070 GEN1
Solar/Wind Harmer
0.123
946031AF1-268 GEN
Solar/Wind Harmer
3.219
203830AF1-094 GEN
Solar/Wind Helper
0.34
23888702TROY G3
50/50
2.643
972253AH1-711 GEN
50/50
80.741
960841AF2-375 GEN
Solar/Wind Harmer
-0.002
247522W1-056 GEN
Solar/Wind Harmer
0.001
246936BC-WTG1
Solar/Wind Harmer
0.199
270489AE1-102 GEN1
Solar/Wind Harmer
0.637
945111AF1-176 GEN
Solar/Wind Harmer
8.299
270505AE1-170 C O1
Solar/Wind Harmer
4.878
965011AG1-365 GEN
Solar/Wind Harmer
4.433
274751CRETE EC ;1U
Adder
4.596
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
274723RIVER EC ;12
Adder
9.924
274801UNIV PARK;4U
Adder
3.173
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
4.739
274773LINCOLN ;4U
Adder
4.584
274774LINCOLN ;5U
Adder
4.584
971997AH1-543 GEN
Solar/Wind Harmer
1.918
276861AD2-134 GEN
Solar/Wind Harmer
0.065
970569AG2-363 GEN
Solar/Wind Harmer
10.839
274761LEE CO EC;2U
Adder
4.772
24387305FR-4G C
Solar/Wind Harmer
0.001
276158O29GEN2
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
1.533
939741AE1-205 GEN
Solar/Wind Harmer
4.946
945371AF1-202 GEN
Solar/Wind Harmer
0
972175AH1-670 GEN
Solar/Wind Harmer
2.841
270032AE2-172
Solar/Wind Harmer
2.283
23888502TROY G1
50/50
2.643
23888602TROY G2
50/50
2.643
971549AH1-272 GEN
Solar/Wind Harmer
11.871
247607V1-011 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
0.621
971771AH1-392 GEN
Solar/Wind Harmer
4.424
971769AH1-391 GEN
Solar/Wind Harmer
4.822
971567AH1-282 GEN
Solar/Wind Harmer
6.357
270071AF1-092 GEN
Solar/Wind Harmer
7.505
274728ELWOOD EC;5P
Adder
8.849
24691005MDL-2G C
Solar/Wind Harmer
0.001
24729505KEY G4
Adder
3.405
971177AH1-047 GEN
Solar/Wind Harmer
2.252
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
276612AE2-035 GEN
Solar/Wind Harmer
0.001
971681AH1-341 GEN
Solar/Wind Harmer
5.777
24386605FR-22G C
Solar/Wind Harmer
0
24387005FR-3G C
Solar/Wind Harmer
0.001
957751AF2-069 GEN
Solar/Wind Harmer
0.117
270594AE1-207 GEN
Solar/Wind Harmer
3.835
276174W4-005 GEN2
Solar/Wind Harmer
0
270543AE2-219 C
Solar/Wind Harmer
0.002
241886AC2-103 GEN2
Solar/Wind Helper
7.083
274880W4-005 GEN4
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
1.195
241885AC2-103 GEN1
Solar/Wind Helper
7.083
961971AG1-040 GEN
Solar/Wind Helper
0.352
254303AC2-168 GEN
Solar/Wind Helper
0.079
23920202STRYCT
50/50
2.39
970515AG2-329 GEN
Solar/Wind Harmer
15.158
943021AE2-325 GEN
Solar/Wind Harmer
2.476
270223U2-072_GEN1
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
8.434
971917AH1-482 GEN
Solar/Wind Harmer
5.035
941551AE2-152 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.45
24791305MDL-5G
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0.002
959081AF2-199 GEN
Solar/Wind Harmer
3.625
971067AG2-660 GEN
Solar/Wind Harmer
1.208
274822ROCKFORD ;11
Adder
10.179
970819AG2-516 GEN
Solar/Wind Harmer
4.326
971475AH1-234 GEN
Solar/Wind Harmer
1.747
276726Z2-087_GEN
Solar/Wind Harmer
0.001
274854TWINGROVE;U2
Solar/Wind Harmer
0.001
963741AG1-226 GEN
Solar/Wind Harmer
8.165
203954AE2-126 C
Solar/Wind Helper
0.223
24189902OREGON_CT2
50/50
2.176
23906402RICHG1
50/50
1.751
23906502RICHG2&3
50/50
1.747
241840AF1-064_GEN
Solar/Wind Harmer
0.005
965421AG1-410 GEN
Solar/Wind Harmer
14.575
270449AD2-020 GEN
Solar/Wind Harmer
0
24695305TIMB G C
Solar/Wind Harmer
0.001
247521TR3_G114
Solar/Wind Harmer
0.167
270246TR4_N_V150
Solar/Wind Harmer
0.03
24639705ELKHART HY
Adder
0.1
270055AF2-134 C O1
Solar/Wind Harmer
0.003
274812UNIV PK N;8U
Adder
2.762
276164X3-005 C
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
0.396
274676JOLIET 29;8U
Adder
16.543
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
2.978
274682WAUKEGAN ;7U
Adder
9.512
274828WAUKEGAN ;BP
Adder
5.841
276901AD2-066 C O1
Solar/Wind Harmer
0.004
957471AF2-041 GEN
Solar/Wind Harmer
10.876
965651AG1-433 GEN
Solar/Wind Harmer
1.047
274877BISHOP HL;1U
Solar/Wind Harmer
0.119
970291AG2-192 GEN
Solar/Wind Harmer
0.448
241807AE2-176_GEN
Solar/Wind Helper
1.701
203835AF1-098 GEN
Solar/Wind Helper
1.388
203860AG1-193 C
Solar/Wind Helper
0.156
241966AE1-183 GEN
Solar/Wind Helper
0.136
972301AH1-735 GEN
50/50
8.755
241858AF1-205_GEN
Solar/Wind Harmer
4.885
241808AF1-120 C
Solar/Wind Harmer
0.004
270361_3
Solar/Wind Harmer
4.971
944231AF1-091 GEN
Solar/Wind Harmer
1.488
270063AE2-323 C
Solar/Wind Harmer
0.004
270462AD2-086
Solar/Wind Harmer
0.009
274754CRETE EC ;4U
Adder
4.596
958381AF2-132 GEN
Solar/Wind Harmer
0.001
274732ELWOOD EC;7P
Adder
8.849
274674JOLIET 9 ;6U
Adder
8.288
970245AG2-165 GEN
Solar/Wind Harmer
1.623
939401AE1-172 GEN
Solar/Wind Harmer
2.747
962781AG1-127 GEN
Solar/Wind Harmer
3.489
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
972235AH1-702 GEN1
Adder
1.305
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274766LEE CO EC;7U
Adder
4.716
24385905FR-11G C
Solar/Wind Harmer
0.001
247536S-71 GEN
Solar/Wind Harmer
0.138
963831AG1-236 GEN
Solar/Wind Harmer
1.315
276903AD2-071 C
Solar/Wind Harmer
3.766
276615X2-022 GEN
Solar/Wind Harmer
0.035
24189802OREGON_CT1
50/50
2.221
961051AF2-396 GEN
Solar/Wind Harmer
9.419
961051AF2-396 GEN
Solar/Wind Harmer
6.28
270216AD2-079_GEN
Solar/Wind Harmer
0.001
970627AG2-408 GEN
Solar/Wind Harmer
1.33
270224U2-072_GEN2
Solar/Wind Harmer
0
274803UNIV PARK;6U
Adder
3.182
274887GEN-1.85
Solar/Wind Harmer
0.1
274674JOLIET 9 ;6U
Adder
8.288
958481AF2-142 GEN
Solar/Wind Harmer
5.572
274862TOP CROP ;2U
Solar/Wind Harmer
0.503
274693ROCKY RD ;1P
Adder
5.833
274683WAUKEGAN ;8U
Adder
11.144
274683WAUKEGAN ;8U
Adder
9.394
274879MINONK ;1U
Solar/Wind Harmer
0.155
970921AG2-575 GEN
Solar/Wind Harmer
3.666
970921AG2-575 GEN
Solar/Wind Harmer
1.222
971335AH1-147 GEN
Solar/Wind Harmer
7.279
274764LEE CO EC;5U
Adder
4.784
966841AG1-555 GEN
Solar/Wind Harmer
0.405
960971AF2-388 GEN
Solar/Wind Harmer
2.094
276708O09 GEN2
Solar/Wind Harmer
0.127
276782AC1-033 GEN
Solar/Wind Harmer
0.001
960611AF2-352 GEN
Solar/Wind Harmer
1.165
270599AE1-208 GEN
Solar/Wind Harmer
3.195
970883AG2-550 GEN
Solar/Wind Harmer
3.346
203947AF1-006 C
Solar/Wind Helper
0.402
241967AE2-285_GEN
Solar/Wind Helper
0.354
24190002OREGON_ST1
50/50
2.928
971677AH1-339 GEN
Solar/Wind Harmer
0.714
965681AG1-436 GEN
Solar/Wind Harmer
5.205
270227U2-072_GEN3
Solar/Wind Harmer
0
270228U2-072_GEN4
Solar/Wind Harmer
0
241832AE2-181_GEN
Solar/Wind Harmer
0.004
24441205WTRV SLR C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
3.77
965021AG1-366 GEN
Solar/Wind Harmer
1.478
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270043AE2-236 GEN
Solar/Wind Harmer
2.692
274724RIVER EC ;11
Adder
9.806
274802UNIV PARK;5U
Adder
3.182
274800UNIV PARK;3U
Adder
3.173
970941AG2-585 GEN
Solar/Wind Harmer
4.739
274772LINCOLN ;3U
Adder
4.584
276897AD1-100 C
Solar/Wind Harmer
0.005
276893AG1-478 C
Solar/Wind Harmer
0.149
274729ELWOOD EC;1P
Adder
8.848
276805AD2-038 GEN
Solar/Wind Harmer
0.001
276889AE2-281 GEN
Solar/Wind Harmer
0
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.388
274850MENDOTA H;RU
Solar/Wind Harmer
0.043
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.065
970571AG2-364 GEN
Solar/Wind Harmer
7.226
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
276157O29GEN1
Solar/Wind Harmer
0.575
942111AE2-223 GEN
Solar/Wind Harmer
1.148
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
5.278
971993AH1-541 GEN
Solar/Wind Harmer
1.563
276621W2-048 GEN
Solar/Wind Harmer
0.169
276838X2-022 GEN2
Solar/Wind Harmer
0.189
270404AC1-167 GEN
Solar/Wind Harmer
0.002
247604X1-042
Adder
0.302
270247TR4_N_V136
Solar/Wind Harmer
0.03
970031AG2-029 GEN
Solar/Wind Harmer
2.93
970349AG2-230 GEN
Solar/Wind Harmer
6.22
270391AF1-285 GEN3
Solar/Wind Harmer
0.274
274752CRETE EC ;2U
Adder
4.596
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
274826FISK ;BP
Adder
5.966
972228AH1-698 GEN2
Adder
2.007
939351AE1-166 GEN
Solar/Wind Harmer
0
274730ELWOOD EC;6P
Adder
8.849
970707AG2-453 GEN
Solar/Wind Harmer
12.267
970513AG2-328 GEN
Solar/Wind Harmer
1.623
970517AG2-330 GEN
Solar/Wind Harmer
9.737
276694AA1-018 GEN2
Solar/Wind Harmer
0
944531AF1-118 GEN
Solar/Wind Harmer
16.565
970781AG2-491 GEN
Solar/Wind Harmer
3.663
274855GSG-6 ;RU
Solar/Wind Harmer
0.133
270377AD1-106 GEN
Solar/Wind Harmer
1.364
274853TWINGROVE;U1
Solar/Wind Harmer
0.001
959611AF2-252 GEN
Solar/Wind Harmer
1.165
254305AE2-115 C
Solar/Wind Helper
0.117
958821AF2-173 GEN
Solar/Wind Harmer
1.049
958321AF2-126 GEN
Solar/Wind Harmer
1.413
23929302BS-PKR
Adder
1.959
270575GUS2 35KV
Solar/Wind Harmer
4.971
970217AG2-149 GEN
Solar/Wind Harmer
5.053
270258AD1-119 GEN
Solar/Wind Harmer
0.001
270491AE1-102 GEN2
Solar/Wind Harmer
0.637
270191TR4_S_V150
Solar/Wind Harmer
0.001
24642205MAYFLWER
Adder
0.413
959331AF2-224 GEN
Solar/Wind Harmer
3.103
274753CRETE EC ;3U
Adder
4.596
964401AG1-302 GEN
Solar/Wind Harmer
0.001
972038AH1-567 GEN2
Adder
0.199
971617AH1-308 GEN
Solar/Wind Harmer
3.125
274872LEEDK;1U
Solar/Wind Harmer
0.134
972236AH1-702 GEN2
Adder
1.135
274760LEE CO EC;1U
Adder
4.772
274878BISHOP HL;2U
Solar/Wind Harmer
0.119
965091AG1-374 GEN
Solar/Wind Harmer
10.488
965931AG1-462 GEN
Solar/Wind Harmer
8.873
276686W4-005 GEN3
Solar/Wind Harmer
0
962511AG1-100 GEN
Solar/Wind Helper
0.361
959441AF2-235 GEN
Solar/Wind Helper
0.154
20334926Z1-069 C
Solar/Wind Helper
0.662
270231U2-072_GEN5
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
971341AH1-150 GEN
Solar/Wind Harmer
7.251
971343AH1-151 GEN
Solar/Wind Harmer
7.251
274849CRESCENT ;1U
Solar/Wind Harmer
0
276741O09 GEN1
Solar/Wind Harmer
0.127
276820AF1-078_GEN
Solar/Wind Harmer
0.001
971613AH1-306 GEN
Solar/Wind Harmer
1.644
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
203980AG1-197 GEN
Solar/Wind Helper
0.262
203979AG1-198 GEN
Solar/Wind Helper
0.204
241801AE1-079 GEN
Solar/Wind Helper
0.138
990142J1224
External Queue
15.35684871673584
991177J1571 G
External Queue
18.513126373291016
991182J1586 G
External Queue
28.404245376586914
990527J1329
External Queue
2.100800037384033
NYPJM->LTFIMP_NY
CLTF
2.006
LGEELTFEXP_LGEE->PJM
CLTF
2.487
WECLTFEXP_WEC->PJM
CLTF
1.978
AG2-052LTFEXP_AG2-052->PJM
LTF
0.127
AH1-155LTFEXP_AH1-155->PJM
LTF
0.19
CBM West 1LTFEXP_CBM-W1->PJM
CBM
107.191
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.28
MECLTFEXP_MEC->PJM
CLTF
7.783
SIGELTFEXP_SIGE->PJM
CLTF
0.206
LAGNLTFEXP_LAGN->PJM
CLTF
6.243
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.59
TVALTFEXP_TVA->PJM
CLTF
2.868
CPLELTFEXP_CPLE->PJM
CLTF
0.787
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.86

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P1-2_MP-500-007A_SRT-A


Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P1-2_MP-500-007A_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:131.92 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5002.28
MW Contribution:1.12
Bus #Bus NameTypeMW Contribution
23559001PLEAS1
50/50
6.1
961921AG1-034 GEN
Solar/Wind Harmer
7.615
942051AE2-217 GEN
Solar/Wind Harmer
14.671
970605AG2-385 GEN
Solar/Wind Harmer
4.899
270391AF1-285 GEN3
Solar/Wind Harmer
0.536
253333AC1-068 GEN
Solar/Wind Harmer
0.012
270273AD2-016 GEN
Solar/Wind Harmer
0.821
270291AC1-194 GEN
Solar/Wind Harmer
6.106
253415AE1-040 GEN
Solar/Wind Harmer
0.003
253406AD2-031_GEN
Solar/Wind Harmer
0.563
270377AD1-106 GEN
Solar/Wind Harmer
2.855
270247TR4_N_V136
Solar/Wind Harmer
0.048
944531AF1-118 GEN
Solar/Wind Harmer
33.395
25196608WSDLE5
Adder
9.077
970031AG2-029 GEN
Solar/Wind Harmer
4.795
270404AC1-167 GEN
Solar/Wind Harmer
0.003
970513AG2-328 GEN
Solar/Wind Harmer
3.191
970517AG2-330 GEN
Solar/Wind Harmer
19.146
970349AG2-230 GEN
Solar/Wind Harmer
11.025
958821AF2-173 GEN
Solar/Wind Harmer
10.273
270437AC2-090 C
Solar/Wind Harmer
0.003
247604X1-042
Adder
0.433
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
970781AG2-491 GEN
Solar/Wind Harmer
7.196
970519AG2-331 GEN
Solar/Wind Harmer
18.687
970699AG2-449 GEN
Solar/Wind Harmer
1.797
274752CRETE EC ;2U
Adder
8.477
958171AF2-111 GEN
Solar/Wind Harmer
17.94
24728705AND G3
Adder
8.214
274826FISK ;BP
Adder
11.205
972228AH1-698 GEN2
Adder
3.79
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
270119AB2-067 GEN1
50/50
7.059
970077AG2-063 GEN
Solar/Wind Harmer
4.631
972269AH1-719 GEN
Adder
2.584
253378AE2-206_GEN
Solar/Wind Harmer
0.004
25326509SID D
Adder
1.451
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
246938BC-WTG3
Solar/Wind Harmer
0.273
246937BC-WTG2
Solar/Wind Harmer
0.305
970611AG2-400 GEN
Solar/Wind Harmer
7.488
270007AE1-245 C
Solar/Wind Harmer
0.002
962581AG1-107 GEN
Solar/Wind Harmer
0.002
970623AG2-406 GEN
Solar/Wind Harmer
1.356
942221AE2-234 GEN
Solar/Wind Harmer
0.037
970621AG2-405 GEN
Solar/Wind Harmer
1.351
972239AH1-704 GEN
Adder
2.689
961821AG1-024 GEN
Solar/Wind Harmer
5.077
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
945631AF1-228 GEN
Solar/Wind Harmer
0
270578AF1-285 GEN2
Solar/Wind Harmer
0.536
270432AC2-029 GEN
Solar/Wind Harmer
3.553
270269AC2-059
Solar/Wind Harmer
0.005
241972AD1-140 GEN
Solar/Wind Harmer
0.854
270340AC2-060 GEN
Solar/Wind Harmer
0.009
253400AC2-068 GEN
Solar/Wind Harmer
0.958
965041AG1-368 GEN
Solar/Wind Harmer
7.471
965101AG1-375 GEN
Solar/Wind Harmer
7.401
25196508WSDLE4
Adder
8.984
270297AD1-101 GEN
Solar/Wind Harmer
0.002
971609AH1-304 GEN
Solar/Wind Harmer
1.2
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
970115AG2-085 GEN
Solar/Wind Harmer
2.932
24699105WLD G1 C
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
274776LINCOLN ;7U
Adder
8.676
24386205FR-12G C
Solar/Wind Harmer
0.001
274814UNIV PK N;0U
Adder
5.184
274807UNIV PK N;3U
Adder
5.173
274805UNIV PK N;1U
Adder
5.15
963841AG1-237 GEN
Solar/Wind Harmer
3.09
972163AH1-664 GEN
Solar/Wind Harmer
7.933
274687WILL CNTY;4U
Adder
28.523
274687WILL CNTY;4U
Adder
28.523
274731ELWOOD EC;2P
Adder
16.768
274733ELWOOD EC;3P
Adder
16.768
274746AC1-111 G10
Adder
5.679
942861AE2-305 GEN
Solar/Wind Harmer
6.335
270518AE2-148 GEN
Solar/Wind Harmer
0.691
970155AG2-107 GEN
Solar/Wind Harmer
22.046
270349AD2-093_GEN
Solar/Wind Harmer
0.006
24721705FLATG2
Adder
23.918
253343AC1-166 GEN
Solar/Wind Harmer
0.003
971995AH1-542 GEN
Solar/Wind Harmer
2.906
960071AF2-298 GEN
Solar/Wind Harmer
3.786
253370AE2-315 SEC1
Adder
2.182
253371AE2-315 SEC2
Adder
2.063
965421AG1-410 GEN
Solar/Wind Harmer
22.57
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.499
247521TR3_G114
Solar/Wind Harmer
0.273
270246TR4_N_V150
Solar/Wind Harmer
0.048
24695305TIMB G C
Solar/Wind Harmer
0.002
965651AG1-433 GEN
Solar/Wind Harmer
2.174
25194608D.CRK4
Adder
1.74
970947AG2-589 GEN
Solar/Wind Harmer
0.245
965031AG1-367 GEN
Solar/Wind Harmer
7.338
970613AG2-401 GEN
Solar/Wind Harmer
5.378
24639705ELKHART HY
Adder
0.161
970291AG2-192 GEN
Solar/Wind Harmer
0.95
270449AD2-020 GEN
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0.006
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
5.139
24728605AND G2
Adder
3.927
276776AD2-060 GEN
Solar/Wind Harmer
0.746
945681AF1-233 GEN
Solar/Wind Harmer
13.461
274676JOLIET 29;8U
Adder
31.303
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
274745AC1-111 GEN9
Adder
5.679
276901AD2-066 C O1
Solar/Wind Harmer
0.007
316095T157 G97
Solar/Wind Helper
1.504
238185AF2-356 C
Solar/Wind Helper
2.646
23751101LEADS_P59
Solar/Wind Helper
1.404
237030AB1-096 C
Solar/Wind Helper
0.071
227287AC2-120 GEN
Solar/Wind Helper
0.346
233996TM1833_GEN
Solar/Wind Helper
0.261
232406W1-004 FULL
Solar/Wind Helper
0.507
230430AE1-229_GEN
Solar/Wind Helper
3.372
230415AB2-049 C
Solar/Wind Helper
0.03
962771AG1-126 GEN
Solar/Wind Harmer
34.524
270284AF1-227 GEN1
Solar/Wind Harmer
0.011
253383AE2-342_GEN
Solar/Wind Harmer
0.003
241973AD2-163_GEN1
Solar/Wind Harmer
0.006
943861AF1-054 GEN
Solar/Wind Harmer
3.127
943851AF1-053 GEN
Solar/Wind Harmer
2.166
970689AG2-444 GEN
Solar/Wind Harmer
16.436
270302AB2-170 GEN
Solar/Wind Harmer
0.005
971653AH1-327 GEN
Solar/Wind Harmer
1.117
970179AG2-119 GEN
Solar/Wind Harmer
6.883
253372AE2-315 SEC3
Adder
2.063
253372AE2-315 SEC3
Adder
2.063
25306009OHH W.
Adder
3.13
957201AF2-014 GEN
Solar/Wind Harmer
0.001
971989AH1-539 GEN
Solar/Wind Harmer
3.215
963791AG1-232 GEN
Solar/Wind Harmer
10.044
270024AE2-089 GEN
Solar/Wind Harmer
0.008
252524AE2-267 GEN
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
1.389
270536AF1-215 GEN2
Solar/Wind Harmer
0.009
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274811UNIV PK N;7U
Adder
5.139
274827FISK ;RP
Adder
7.941
972227AH1-698 GEN1
Adder
2.669
274735ELWOOD EC;4P
Adder
16.768
274744AC1-111 GEN8
Adder
5.679
972203AH1-686 GEN
Adder
2.338
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
959381AF2-229 GEN
Solar/Wind Helper
0.357
960921AF2-383 GEN
Solar/Wind Helper
0.364
205932AD2-116_GEN
Solar/Wind Helper
0.509
232432Z2-076 GEN
Solar/Wind Helper
0.067
234033AF1-007_GEN
Solar/Wind Helper
7.02
203975AE1-071-GEN
Solar/Wind Helper
2.498
966261AG1-495 GEN
Solar/Wind Helper
0.081
20674828DL_W4-046
Solar/Wind Helper
0.008
207408W3-077 C
Solar/Wind Helper
0.084
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.15
219291REEVESSOUT C
Solar/Wind Helper
0.011
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
20720828JCB_W4-025
Solar/Wind Helper
0.063
20714528FRN_Y2-051
Solar/Wind Helper
0.057
218438BLK ROCK C
Solar/Wind Helper
0.027
219919AE1-041 FULL
Solar/Wind Helper
0.004
20674628WNG_W3-110
Solar/Wind Helper
0.089
970153AG2-106 GEN
Solar/Wind Harmer
22.046
241955AC1-078 GEN
Solar/Wind Harmer
0.007
24721905FLATG4
Adder
23.918
241974AD2-163_GEN2
Solar/Wind Harmer
0.006
253370AE2-315 SEC1
Adder
2.182
253371AE2-315 SEC2
Adder
2.063
253316AC1-085 GEN3
Solar/Wind Harmer
0.005
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
9.749
270588AE1-091_GEN
Solar/Wind Harmer
5.845
25194608D.CRK4
Adder
1.74
946031AF1-268 GEN
Solar/Wind Harmer
6.992
247643Z2-116 C
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.804
970291AG2-192 GEN
Solar/Wind Harmer
0.731
247642Z2-115 C
Solar/Wind Harmer
0.003
270535AF1-215 GEN1
Solar/Wind Harmer
0.009
24755605MDL-5G
Solar/Wind Harmer
0.001
24728505AND G1
Adder
3.927
276806AD2-047 C O1
Solar/Wind Harmer
4.047
274676JOLIET 29;8U
Adder
30.185
972159AH1-661 GEN
Adder
1.118
970329AG2-216 GEN
Solar/Wind Harmer
3.354
971199AH1-059 GEN
Solar/Wind Harmer
3.09
241960AC2-195 GEN
Solar/Wind Harmer
0.006
971073AG2-665 GEN
Solar/Wind Harmer
6.898
25326109MON D
Adder
1.443
971231AH1-075 GEN
Solar/Wind Harmer
0.861
25183208HLCRTG
Solar/Wind Harmer
0.012
944541AF1-119 GEN
Solar/Wind Harmer
0.497
970885AG2-551 GEN
Solar/Wind Harmer
2.463
270201AC2-176 GEN
Solar/Wind Harmer
0.001
25194508D.CRK3
Adder
1.496
964611AG1-324 GEN
Solar/Wind Harmer
0.553
252509AD1-136 GEN
Solar/Wind Harmer
0.037
270031AE2-169
Solar/Wind Harmer
4.042
270383AD1-128 GEN
Solar/Wind Harmer
0.004
24379505HDWTR1G C
Solar/Wind Harmer
0.002
247620Y3-023
Adder
0.484
960441AF2-335 GEN
Solar/Wind Harmer
7.33
24728805RICHG1
Adder
3.964
270526AF1-158 GEN
Solar/Wind Harmer
0.009
24441505OLIV SLR
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
6.67
945421AF1-207 GEN
Solar/Wind Harmer
0.001
276843GEN-1.7
Solar/Wind Harmer
0.231
958011AF2-095 GEN
Solar/Wind Harmer
10.284
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
971573AH1-285 GEN
Solar/Wind Harmer
1.319
274695ROCKY RD ;2P
Adder
11.271
958491AF2-143 GEN
Solar/Wind Harmer
10.588
237034AC2-136 C
Solar/Wind Helper
0.227
235063AE1-101 C2
Solar/Wind Helper
1.659
237001AB1-127_GEN
Solar/Wind Helper
0.442
226929AD2-058 GEN
Solar/Wind Helper
0.099
233987AB2-037 GEN
Solar/Wind Helper
2.342
234036AF2-325 C
Solar/Wind Helper
0.042
233901CHERRYDALE C
Solar/Wind Helper
0.232
20720628TIN_W1-124
Solar/Wind Helper
0.19
207442AE1-156 GEN
Solar/Wind Helper
0.326
20671828STAW2-080
Solar/Wind Helper
0.027
20674128FR_U2-059
Solar/Wind Helper
0.004
211065PSPA IPP
Solar/Wind Helper
0.151
211065PSPA IPP
Solar/Wind Helper
0.151
24318805MLG1
50/50
10.095
270475AD2-096_GEN
50/50
7.141
253338AC1-165 GEN
Solar/Wind Harmer
0.003
972173AH1-669 GEN
Solar/Wind Harmer
3.952
970191AG2-125 GEN
Solar/Wind Harmer
1.945
270491AE1-102 GEN2
Solar/Wind Harmer
0.979
270191TR4_S_V150
Solar/Wind Harmer
0.001
959331AF2-224 GEN
Solar/Wind Harmer
5.242
270258AD1-119 GEN
Solar/Wind Harmer
0.002
971617AH1-308 GEN
Solar/Wind Harmer
6.173
270222AC2-111 GEN
Solar/Wind Harmer
3.739
270004AE1-209 GEN
Solar/Wind Harmer
1.59
24642205MAYFLWER
Adder
0.665
270356AE2-297 GEN
Solar/Wind Harmer
0.01
964401AG1-302 GEN
Solar/Wind Harmer
0.001
970217AG2-149 GEN
Solar/Wind Harmer
6.268
274753CRETE EC ;3U
Adder
8.477
972038AH1-567 GEN2
Adder
0.373
238118U2-030_1
Solar/Wind Helper
0.341
238148AE2-230_GEN2
Solar/Wind Helper
0.497
237038AE2-054 C
Solar/Wind Helper
0.272
23779801AA1-109
Solar/Wind Helper
0.193
316006AB2-029 C
Solar/Wind Helper
0.117
316045AC1-158 PL2
Solar/Wind Helper
4.138
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.131
207445AB1-138_GEN
Solar/Wind Helper
0.104
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
276882AE2-255 GEN
Solar/Wind Harmer
0.824
238152AF2-075_GEN
Solar/Wind Helper
0.707
23546401DTGZ2-030
Solar/Wind Helper
0.089
3138216PACIFIC
Solar/Wind Helper
0.044
23750501ELLIOTTS
Solar/Wind Helper
0.638
205956AE1-196_GEN
Solar/Wind Helper
0.509
233935AB2-179 C
Solar/Wind Helper
1.269
232436AB1-176 C
Solar/Wind Helper
0.044
233923SMA
Solar/Wind Helper
0.958
219914AD2-027 C
Solar/Wind Helper
0.115
219607WPEMNERT C
Solar/Wind Helper
0.08
20715728PEM_W1-119
Solar/Wind Helper
0.096
316164AC1-076 GEN
Solar/Wind Helper
1.096
20675528CPH_W2-050
Solar/Wind Helper
0.087
218524CNTRALGAS1 C
Solar/Wind Helper
0.16
207530AG1-191 GEN
Solar/Wind Helper
0.066
20675128HRM_W1-127
Solar/Wind Helper
0.029
970321AG2-212 GEN
Solar/Wind Harmer
3.191
270186AC1-089 GEN
Solar/Wind Harmer
0.004
270209AC1-174_GEN
Solar/Wind Harmer
0.001
970825AG2-519 GEN
Solar/Wind Harmer
8.127
957891AF2-083 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
970239AG2-162 GEN
Solar/Wind Harmer
1.797
274770LINCOLN ;1U
Adder
8.676
274771LINCOLN ;2U
Adder
8.676
274808UNIV PK N;4U
Adder
5.117
274888KELLY CRK;1U
Solar/Wind Harmer
0.419
972259AH1-714 GEN
Adder
19.507
970241AG2-163 GEN
Solar/Wind Harmer
4.144
274696ROCKY RD ;4P
Adder
11.537
274697ROCKY RD ;3P
Adder
3.062
238175AF1-290_GEN
Solar/Wind Helper
0.153
235020AA1-095 C
Solar/Wind Helper
0.053
205916AD1-020 GEN
Solar/Wind Helper
1.713
20390526W1-045 C
Solar/Wind Helper
0.35
233933AB2-153 GEN
Solar/Wind Helper
0.232
233944AB2-135 GEN
Solar/Wind Helper
0.588
233946AB2-136 GEN
Solar/Wind Helper
0.568
232408W1-005 C
Solar/Wind Helper
0.507
232410W1-006 C
Solar/Wind Helper
0.507
233939AC1-091 C
Solar/Wind Helper
0.35
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.082
20716928W4-060COL
Solar/Wind Helper
0.051
20673828FLE_V3-070
Solar/Wind Helper
0.09
270051AF1-062 GEN
50/50
11.821
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270512AE1-227 GEN2
Solar/Wind Harmer
1.963
970065AG2-057 GEN
Solar/Wind Harmer
0.76
971191AH1-055 GEN
Solar/Wind Harmer
19.26
965021AG1-366 GEN
Solar/Wind Harmer
2.496
270043AE2-236 GEN
Solar/Wind Harmer
4.777
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
252510AF1-249 C
Solar/Wind Harmer
0.057
957741AF2-068 GEN
Solar/Wind Harmer
11.081
945111AF1-176 GEN
Solar/Wind Harmer
5.919
25196008MFTGT1
Adder
1.405
24441205WTRV SLR C
Solar/Wind Harmer
0
970243AG2-164 GEN
Solar/Wind Harmer
4.205
274772LINCOLN ;3U
Adder
8.676
274724RIVER EC ;11
Adder
18.203
972167AH1-666 GEN
Solar/Wind Harmer
5.717
274802UNIV PARK;5U
Adder
5.97
970941AG2-585 GEN
Solar/Wind Harmer
8.927
274800UNIV PARK;3U
Adder
5.966
276897AD1-100 C
Solar/Wind Harmer
0.009
276893AG1-478 C
Solar/Wind Harmer
0.282
274729ELWOOD EC;1P
Adder
16.768
276805AD2-038 GEN
Solar/Wind Harmer
0.002
237048AF1-022 C
Solar/Wind Helper
0.177
233930AB2-032 GEN
Solar/Wind Helper
0.381
233954AC2-188 GEN
Solar/Wind Helper
0.232
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.23
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219907AC1-030 C
Solar/Wind Helper
0.034
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
207437AD2-070 GEN
Solar/Wind Helper
0.138
20671928W4-073
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.029
270166AC1-044 GEN3
50/50
7.059
246936BC-WTG1
Solar/Wind Harmer
0.305
270489AE1-102 GEN1
Solar/Wind Harmer
0.979
965011AG1-365 GEN
Solar/Wind Harmer
7.488
958861AF2-177 GEN
Solar/Wind Harmer
3.207
945371AF1-202 GEN
Solar/Wind Harmer
0.001
270005AE1-210 C O1
Solar/Wind Harmer
1.59
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
2.603
25196808ZIMRHP
Adder
79.729
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
270032AE2-172
Solar/Wind Harmer
4.877
945111AF1-176 GEN
Solar/Wind Harmer
13.03
270505AE1-170 C O1
Solar/Wind Harmer
7.665
25196008MFTGT1
Adder
1.45
247522W1-056 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
9.032
970333AG2-219 GEN
Solar/Wind Harmer
5.139
274751CRETE EC ;1U
Adder
8.477
274773LINCOLN ;4U
Adder
8.676
274774LINCOLN ;5U
Adder
8.676
274723RIVER EC ;12
Adder
18.418
24387305FR-4G C
Solar/Wind Harmer
0.003
274801UNIV PARK;4U
Adder
5.966
23583801GRNGAP
Solar/Wind Helper
5.601
238149AF1-291A_GEN
Solar/Wind Helper
0.141
23751201ROTHROCK
Solar/Wind Helper
0.824
237061AD1-155 GEN
Solar/Wind Helper
0.053
238221AF1-254 C O1
Solar/Wind Helper
0.274
3141196NOKESVL
Solar/Wind Helper
1.032
226910AB2-157 C
Solar/Wind Helper
0.014
223402AF1-300 C
Solar/Wind Helper
0.367
233982AB2-133 GEN
Solar/Wind Helper
0.358
233940AF2-379 C
Solar/Wind Helper
0.062
233952AC2-187 GEN
Solar/Wind Helper
0.232
219623KINSLEYBEA C
Solar/Wind Helper
0.002
20716028EGP_W2-019
Solar/Wind Helper
0.019
270459AD2-067 GEN
Solar/Wind Harmer
0
270156DARBY CT1
Adder
10.409
270157DARBY CT2
Adder
10.383
940611AE2-048 GEN
Solar/Wind Harmer
19.602
941391AE2-136 GEN
Solar/Wind Harmer
11.042
970879AG2-548 GEN
Solar/Wind Harmer
6.898
270435AC2-044 GEN
Solar/Wind Harmer
0.953
247607V1-011 GEN
Solar/Wind Harmer
0.001
971567AH1-282 GEN
Solar/Wind Harmer
11.206
24729505KEY G4
Adder
6.919
270071AF1-092 GEN
Solar/Wind Harmer
14.245
270367AC2-061_GEN
Solar/Wind Harmer
0.006
971673AH1-337 GEN
Solar/Wind Harmer
4.804
25196408WSDLE3
Adder
9.344
25196308WSDLE2
Adder
9.263
25196208WSDLE1
Adder
9.24
25196708WSDLE6
Adder
9.217
270543AE2-219 C
Solar/Wind Harmer
0.004
270240V3-007_GEN2
Solar/Wind Harmer
0.002
270594AE1-207 GEN
Solar/Wind Harmer
8.194
971771AH1-392 GEN
Solar/Wind Harmer
7.306
971769AH1-391 GEN
Solar/Wind Harmer
8.134
25196108MFTGT2
Adder
1.599
25196108MFTGT2
Adder
1.484
971549AH1-272 GEN
Solar/Wind Harmer
14.865
24691005MDL-2G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
274728ELWOOD EC;5P
Adder
16.768
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
238126S14_GEN_1
Solar/Wind Helper
0.827
237085AD2-009_GEN
Solar/Wind Helper
1.649
316411AF1-147_GEN1
Solar/Wind Helper
0.888
316415AF1-147_GEN2
Solar/Wind Helper
0.888
3141426STAFORD
Solar/Wind Helper
0.052
228754AB1-001 C
Solar/Wind Helper
0.026
219272CLEANLIGHT C
Solar/Wind Helper
0.025
20675928HOL_W4-097
Solar/Wind Helper
0.05
207484AF2-139 C O1
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.136
209116AE2-175 GEN
Solar/Wind Helper
1.778
20676128MHD_W3-029
Solar/Wind Helper
0.096
217081WEATEXAS C
Solar/Wind Helper
0.013
207471AF2-354 C
Solar/Wind Helper
0.168
20676228FRD_X1-012
Solar/Wind Helper
0.092
23559101PLEAS2
50/50
6.1
970149AG2-104 GEN
Solar/Wind Harmer
37.287
270159DARBY CT4
Adder
10.243
970593AG2-378 GEN
Solar/Wind Harmer
1.812
270223U2-072_GEN1
Solar/Wind Harmer
0.001
253325AC1-069 GEN
Solar/Wind Harmer
0.012
270263AC1-001 GEN
Solar/Wind Harmer
0.786
270510AE1-227 GEN1
Solar/Wind Harmer
1.963
927014AC1-188 GEN
Solar/Wind Harmer
0.005
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
943021AE2-325 GEN
Solar/Wind Harmer
3.805
970773AG2-487 GEN
Solar/Wind Harmer
1.284
970373AG2-245 GEN
Solar/Wind Harmer
15.247
971917AH1-482 GEN
Solar/Wind Harmer
9.41
970515AG2-329 GEN
Solar/Wind Harmer
18.805
24791305MDL-5G
Solar/Wind Harmer
0.001
941551AE2-152 GEN
Solar/Wind Harmer
0.001
963741AG1-226 GEN
Solar/Wind Harmer
16.815
276691AA1-018 GEN1
Solar/Wind Harmer
0.858
970091AG2-072 GEN
Adder
77.629
238108AE1-109 GEN1
Solar/Wind Helper
0.114
235054AD2-180 GEN
Solar/Wind Helper
2.03
235531U2-073 GEN
Solar/Wind Helper
3.282
23562501BACKB
Solar/Wind Helper
1.007
205917AD1-020 ES
Solar/Wind Helper
0.368
233918AB1-142 GEN
Solar/Wind Helper
0.502
233994AC2-023 GEN
Solar/Wind Helper
0.961
233997TMININ_4.2
Solar/Wind Helper
0.261
233971AC1-093 C
Solar/Wind Helper
0.357
228729W2-030 C
Solar/Wind Helper
0.11
219348LDSOLAR C
Solar/Wind Helper
0.114
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715028HAN_X4-015
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.353
219249CENTRALDIV C
Solar/Wind Helper
0.01
217211CAMDEN ST C
Solar/Wind Helper
0.005
970707AG2-453 GEN
Solar/Wind Harmer
23.303
274730ELWOOD EC;6P
Adder
16.768
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
270541AE2-072 C
Solar/Wind Harmer
0.009
23750701CROSSCHOOL
Solar/Wind Helper
1.502
238127S14_GEN_2
Solar/Wind Helper
0.827
235062AE1-101 C1
Solar/Wind Helper
1.659
223401AF1-299 GEN
Solar/Wind Helper
0.367
233915AB1-141 GEN
Solar/Wind Helper
0.502
232428Y3-058 C
Solar/Wind Helper
0.338
233998TM1NIN_3.36
Solar/Wind Helper
0.261
232404W1-003 C
Solar/Wind Helper
0.507
233950AC2-186 GEN
Solar/Wind Helper
0.116
233972AC1-094 C
Solar/Wind Helper
0.302
228728W1-130C
Solar/Wind Helper
0.054
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
316254AC1-120 GEN1
Solar/Wind Helper
1.059
963711AG1-223 GEN
Solar/Wind Helper
0.064
207454AA2-184 E
Solar/Wind Helper
0.31
20715228NPK_W1-113
Solar/Wind Helper
0.078
20675428EAM_W2-061
Solar/Wind Helper
0.016
207518AF1-320_GEN
Solar/Wind Helper
1.571
270054AF2-122 C O1
Solar/Wind Harmer
0.007
270520AE2-214 GEN
Solar/Wind Harmer
0.013
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
270158DARBY CT3
Adder
10.218
270317AD1-130_GEN
Solar/Wind Harmer
0.011
253349AC2-067 GEN
Solar/Wind Harmer
2.381
965051AG1-369 GEN
Solar/Wind Harmer
3.739
971985AH1-537 GEN
Solar/Wind Harmer
2.206
971029AG2-637 GEN
Solar/Wind Harmer
11.085
945581AF1-223 GEN
Solar/Wind Harmer
0.001
971347AH1-153 GEN
Solar/Wind Harmer
11.025
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
971619AH1-309 GEN
Solar/Wind Harmer
3.285
24725505WLD G2 C
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
4.302
24697605MDL-3G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
8.676
274777LINCOLN ;8U
Adder
8.676
24386405FR-21G C
Solar/Wind Harmer
0.001
972037AH1-567 GEN1
Adder
0.187
960591AF2-350 GEN
Solar/Wind Harmer
7.141
972165AH1-665 GEN
Solar/Wind Harmer
6.354
274675JOLIET 29;7U
Adder
31.303
274675JOLIET 29;7U
Adder
30.185
970833AG2-524 GEN
Solar/Wind Harmer
7.824
970833AG2-524 GEN
Solar/Wind Harmer
5.216
276868AE1-113 GEN
Solar/Wind Harmer
1.414
238208AF1-136 C
Solar/Wind Helper
0.22
205943AE1-185 GEN
Solar/Wind Helper
0.509
233990AG1-397 GEN
Solar/Wind Helper
0.27
964001AG1-254 GEN
Solar/Wind Helper
0.955
227927V4-067C
Solar/Wind Helper
0.01
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
214067T20SOLAR
Solar/Wind Helper
0.011
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.29
219620RIDERU C
Solar/Wind Helper
0.001
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
20676328BVR_Y1-020
Solar/Wind Helper
0.027
270120AB2-067 GEN2
50/50
7.059
270224U2-072_GEN2
Solar/Wind Harmer
0.001
938701AE1-092 GEN
Solar/Wind Harmer
12.917
964601AG1-323 GEN
Solar/Wind Harmer
3.215
964601AG1-323 GEN
Solar/Wind Harmer
2.143
971201AH1-060 GEN
Solar/Wind Harmer
1.52
970627AG2-408 GEN
Solar/Wind Harmer
2.246
960971AF2-388 GEN
Solar/Wind Harmer
4.347
970883AG2-550 GEN
Solar/Wind Harmer
7.389
25194408D.CRK1
Adder
8.004
270599AE1-208 GEN
Solar/Wind Harmer
6.737
926881AC1-175 GEN
Solar/Wind Harmer
0.001
270216AD2-079_GEN
Solar/Wind Harmer
0.001
24728905RICHG2
Adder
3.964
961051AF2-396 GEN
Solar/Wind Harmer
14.589
961051AF2-396 GEN
Solar/Wind Harmer
9.726
966841AG1-555 GEN
Solar/Wind Harmer
0.81
274803UNIV PARK;6U
Adder
5.97
274887GEN-1.85
Solar/Wind Harmer
0.188
274674JOLIET 9 ;6U
Adder
15.704
958481AF2-142 GEN
Solar/Wind Harmer
10.621
274862TOP CROP ;2U
Solar/Wind Harmer
0.958
274693ROCKY RD ;1P
Adder
11.16
274879MINONK ;1U
Solar/Wind Harmer
0.297
23585401KL_K28_T16
Solar/Wind Helper
1.482
23777901MDS_W4-102
Solar/Wind Helper
0.177
237002AB1-128_GEN
Solar/Wind Helper
0.443
237006AB1-125 GEN
Solar/Wind Helper
0.123
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
232424Y1-079 C
Solar/Wind Helper
0.116
233970AC1-092 C
Solar/Wind Helper
0.35
230433AD2-135 GEN
Solar/Wind Helper
0.017
219921AF1-264
Solar/Wind Helper
0.051
219615MILLCREEK C
Solar/Wind Helper
0.027
20674928WA_W3-044
Solar/Wind Helper
0.098
966111AG1-480 GEN
Solar/Wind Helper
0.074
274734ELWOOD EC;8P
Adder
16.768
274736ELWOOD EC;9P
Adder
16.768
943121AE2-341 GEN
Solar/Wind Harmer
11.888
943591AF1-030 GEN
Solar/Wind Harmer
7.906
274682WAUKEGAN ;7U
Adder
9.728
964991AG1-363 GEN
Solar/Wind Helper
5.136
316097T157 G90
Solar/Wind Helper
1.504
237080AD1-060 GEN
Solar/Wind Helper
0.342
966131AG1-482 GEN
Solar/Wind Helper
0.137
232422X3-066 FULL
Solar/Wind Helper
0.114
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
232434Z2-077 GEN
Solar/Wind Helper
0.127
219904AC1-010 C
Solar/Wind Helper
0.06
20720728JCB_W1-129
Solar/Wind Helper
0.057
20714828MDF_W3-079
Solar/Wind Helper
0.13
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.495
217208PARK ELE C
Solar/Wind Helper
0.004
24318905MLG2
50/50
7.071
270471AD2-092_GEN
Solar/Wind Harmer
0.006
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
971655AH1-328 GEN
Solar/Wind Harmer
2.854
276820AF1-078_GEN
Solar/Wind Harmer
0.002
25322209TAIT E
Adder
10.642
25322209TAIT E
Adder
10.403
253370AE2-315 SEC1
Adder
2.182
253317AC1-085 GEN4
Solar/Wind Harmer
0.005
252519AF1-045_GEN
Solar/Wind Harmer
6.44
252516AE2-318_GEN
Solar/Wind Harmer
5.712
247621Y3-024
Adder
0.255
971613AH1-306 GEN
Solar/Wind Harmer
3.512
965681AG1-436 GEN
Solar/Wind Harmer
9.095
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
238120AE2-309 GEN
Solar/Wind Helper
0.525
238169AE2-226 GEN1
Solar/Wind Helper
0.701
238170AE2-226 GEN2
Solar/Wind Helper
0.701
23777801MSM_W1-116
Solar/Wind Helper
0.114
237025AB1-124 C
Solar/Wind Helper
0.164
315651AD1-115 GEN
Solar/Wind Helper
0.785
316447AC1-158 HLD
Solar/Wind Helper
2.845
230407AD2-065 C
Solar/Wind Helper
0.04
20714928UPF_X1-085
Solar/Wind Helper
0.005
218440SUMMTASSOC C
Solar/Wind Helper
0.016
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
964851AG1-348 GEN
Solar/Wind Helper
0.081
219612MATRIX C
Solar/Wind Helper
0.024
219908AB1-139 C
Solar/Wind Helper
0.074
20673728F2S_V4-070
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
971997AH1-543 GEN
Solar/Wind Harmer
2.724
962761AG1-125 GEN
Solar/Wind Harmer
34.524
270462AD2-086
Solar/Wind Harmer
0.017
25326309TAIT D
Adder
1.196
241813AF1-122_GEN
Solar/Wind Harmer
3.405
247536S-71 GEN
Solar/Wind Harmer
0.297
252507AC2-088 GEN
Solar/Wind Harmer
0.335
270063AE2-323 C
Solar/Wind Harmer
0.006
970245AG2-165 GEN
Solar/Wind Harmer
3.191
944231AF1-091 GEN
Solar/Wind Harmer
1.953
276903AD2-071 C
Solar/Wind Harmer
8.137
958381AF2-132 GEN
Solar/Wind Harmer
0.001
274754CRETE EC ;4U
Adder
8.477
24385905FR-11G C
Solar/Wind Harmer
0.002
274732ELWOOD EC;7P
Adder
16.768
274674JOLIET 9 ;6U
Adder
15.704
939401AE1-172 GEN
Solar/Wind Harmer
5.301
238117U2-030
Solar/Wind Helper
0.341
238147AE2-230_GEN1
Solar/Wind Helper
0.495
235067AD1-061 GEN
Solar/Wind Helper
0.496
234015AF2-250 C
Solar/Wind Helper
0.038
316044AC1-158 PL1
Solar/Wind Helper
1.293
316450AC1-158 RIC
Solar/Wind Helper
0.345
219276PARKLANDSO C
Solar/Wind Helper
0.089
20720528MAN_W1-024
Solar/Wind Helper
0.028
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
NYPJM->LTFIMP_NY
CLTF
4.797
LGEELTFEXP_LGEE->PJM
CLTF
6.749
WECLTFEXP_WEC->PJM
CLTF
3.825
AG2-052LTFEXP_AG2-052->PJM
LTF
0.24
AH1-155LTFEXP_AH1-155->PJM
LTF
0.359
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.078
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.1
MECLTFEXP_MEC->PJM
CLTF
15.901
SIGELTFEXP_SIGE->PJM
CLTF
0.505
LAGNLTFEXP_LAGN->PJM
CLTF
14.837
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.802
TVALTFEXP_TVA->PJM
CLTF
7.293
CPLELTFEXP_CPLE->PJM
CLTF
0.624
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.816

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P1-2_MP-500-008A_SRT-SL


Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P1-2_MP-500-008A_SRT-SL
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:125.38 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4754.33
MW Contribution:1.08
Bus #Bus NameTypeMW Contribution
962771AG1-126 GEN
Solar/Wind Harmer
33.269
270284AF1-227 GEN1
Solar/Wind Harmer
0.01
253383AE2-342_GEN
Solar/Wind Harmer
0.003
241973AD2-163_GEN1
Solar/Wind Harmer
0.006
943861AF1-054 GEN
Solar/Wind Harmer
3.02
943851AF1-053 GEN
Solar/Wind Harmer
2.092
970689AG2-444 GEN
Solar/Wind Harmer
15.861
270302AB2-170 GEN
Solar/Wind Harmer
0.005
971653AH1-327 GEN
Solar/Wind Harmer
1.08
970179AG2-119 GEN
Solar/Wind Harmer
6.658
253372AE2-315 SEC3
Adder
1.989
253372AE2-315 SEC3
Adder
1.989
25306009OHH W.
Adder
3.018
957201AF2-014 GEN
Solar/Wind Harmer
0.001
971989AH1-539 GEN
Solar/Wind Harmer
3.109
970155AG2-107 GEN
Solar/Wind Harmer
21.245
270349AD2-093_GEN
Solar/Wind Harmer
0.006
24721705FLATG2
Adder
22.865
253343AC1-166 GEN
Solar/Wind Harmer
0.003
971995AH1-542 GEN
Solar/Wind Harmer
2.81
960071AF2-298 GEN
Solar/Wind Harmer
3.651
253370AE2-315 SEC1
Adder
2.103
253371AE2-315 SEC2
Adder
1.989
965421AG1-410 GEN
Solar/Wind Harmer
21.788
247521TR3_G114
Solar/Wind Harmer
0.263
270246TR4_N_V150
Solar/Wind Harmer
0.047
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.226
24695305TIMB G C
Solar/Wind Harmer
0.002
965651AG1-433 GEN
Solar/Wind Harmer
2.096
25194608D.CRK4
Adder
1.676
965031AG1-367 GEN
Solar/Wind Harmer
7.073
970947AG2-589 GEN
Solar/Wind Harmer
0.236
970613AG2-401 GEN
Solar/Wind Harmer
5.183
24639705ELKHART HY
Adder
0.155
970291AG2-192 GEN
Solar/Wind Harmer
0.916
270449AD2-020 GEN
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0.005
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.954
276776AD2-060 GEN
Solar/Wind Harmer
0.719
24728605AND G2
Adder
3.784
945681AF1-233 GEN
Solar/Wind Harmer
12.962
274676JOLIET 29;8U
Adder
30.175
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
276901AD2-066 C O1
Solar/Wind Harmer
0.007
316095T157 G97
Solar/Wind Helper
1.455
238185AF2-356 C
Solar/Wind Helper
2.425
237030AB1-096 C
Solar/Wind Helper
0.068
227287AC2-120 GEN
Solar/Wind Helper
0.335
233996TM1833_GEN
Solar/Wind Helper
0.253
232406W1-004 FULL
Solar/Wind Helper
0.49
230430AE1-229_GEN
Solar/Wind Helper
3.26
230415AB2-049 C
Solar/Wind Helper
0.029
219766PARADISE C
Solar/Wind Helper
0.053
219912AD2-042 GEN
Solar/Wind Helper
0.145
219291REEVESSOUT C
Solar/Wind Helper
0.011
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.04
20720828JCB_W4-025
Solar/Wind Helper
0.061
20714528FRN_Y2-051
Solar/Wind Helper
0.055
24318805MLG1
50/50
9.842
253338AC1-165 GEN
Solar/Wind Harmer
0.003
972173AH1-669 GEN
Solar/Wind Harmer
3.811
970191AG2-125 GEN
Solar/Wind Harmer
1.876
270491AE1-102 GEN2
Solar/Wind Harmer
0.945
270191TR4_S_V150
Solar/Wind Harmer
0.001
959331AF2-224 GEN
Solar/Wind Harmer
5.057
270258AD1-119 GEN
Solar/Wind Harmer
0.002
971617AH1-308 GEN
Solar/Wind Harmer
5.953
270222AC2-111 GEN
Solar/Wind Harmer
3.603
270004AE1-209 GEN
Solar/Wind Harmer
1.532
24642205MAYFLWER
Adder
0.641
270356AE2-297 GEN
Solar/Wind Harmer
0.009
970217AG2-149 GEN
Solar/Wind Harmer
6.066
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274753CRETE EC ;3U
Adder
8.172
972038AH1-567 GEN2
Adder
0.36
238148AE2-230_GEN2
Solar/Wind Helper
0.48
238118U2-030_1
Solar/Wind Helper
0.314
237038AE2-054 C
Solar/Wind Helper
0.262
23779801AA1-109
Solar/Wind Helper
0.187
316006AB2-029 C
Solar/Wind Helper
0.113
942861AE2-305 GEN
Solar/Wind Harmer
6.118
270518AE2-148 GEN
Solar/Wind Harmer
0.667
972159AH1-661 GEN
Adder
1.082
970329AG2-216 GEN
Solar/Wind Harmer
3.237
971199AH1-059 GEN
Solar/Wind Harmer
2.99
241960AC2-195 GEN
Solar/Wind Harmer
0.006
971073AG2-665 GEN
Solar/Wind Harmer
6.645
25326109MON D
Adder
1.391
971231AH1-075 GEN
Solar/Wind Harmer
0.833
25183208HLCRTG
Solar/Wind Harmer
0.011
944541AF1-119 GEN
Solar/Wind Harmer
0.479
970885AG2-551 GEN
Solar/Wind Harmer
2.374
270201AC2-176 GEN
Solar/Wind Harmer
0.001
25194508D.CRK3
Adder
1.442
964611AG1-324 GEN
Solar/Wind Harmer
0.534
252509AD1-136 GEN
Solar/Wind Harmer
0.036
270031AE2-169
Solar/Wind Harmer
3.897
270383AD1-128 GEN
Solar/Wind Harmer
0.004
247620Y3-023
Adder
0.466
24379505HDWTR1G C
Solar/Wind Harmer
0.002
960441AF2-335 GEN
Solar/Wind Harmer
7.065
24728805RICHG1
Adder
3.82
270526AF1-158 GEN
Solar/Wind Harmer
0.009
24441505OLIV SLR
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
6.431
945421AF1-207 GEN
Solar/Wind Harmer
0.001
276843GEN-1.7
Solar/Wind Harmer
0.223
958011AF2-095 GEN
Solar/Wind Harmer
9.913
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
971573AH1-285 GEN
Solar/Wind Harmer
1.271
958491AF2-143 GEN
Solar/Wind Harmer
10.205
237034AC2-136 C
Solar/Wind Helper
0.219
235063AE1-101 C2
Solar/Wind Helper
1.6
237001AB1-127_GEN
Solar/Wind Helper
0.426
226929AD2-058 GEN
Solar/Wind Helper
0.096
233987AB2-037 GEN
Solar/Wind Helper
2.264
234036AF2-325 C
Solar/Wind Helper
0.041
233901CHERRYDALE C
Solar/Wind Helper
0.225
20720628TIN_W1-124
Solar/Wind Helper
0.183
972239AH1-704 GEN
50/50
2.78
961821AG1-024 GEN
Solar/Wind Harmer
4.91
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
945631AF1-228 GEN
Solar/Wind Harmer
0
270578AF1-285 GEN2
Solar/Wind Harmer
0.518
270432AC2-029 GEN
Solar/Wind Harmer
3.428
270269AC2-059
Solar/Wind Harmer
0.004
241972AD1-140 GEN
Solar/Wind Harmer
0.824
270340AC2-060 GEN
Solar/Wind Harmer
0.009
253400AC2-068 GEN
Solar/Wind Harmer
0.923
965041AG1-368 GEN
Solar/Wind Harmer
7.21
965101AG1-375 GEN
Solar/Wind Harmer
7.135
270297AD1-101 GEN
Solar/Wind Harmer
0.002
25196508WSDLE4
Adder
8.656
971609AH1-304 GEN
Solar/Wind Harmer
1.157
970115AG2-085 GEN
Solar/Wind Harmer
2.826
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
270119AB2-067 GEN1
50/50
6.869
970077AG2-063 GEN
Solar/Wind Harmer
4.471
972269AH1-719 GEN
Adder
2.501
253378AE2-206_GEN
Solar/Wind Harmer
0.004
25326509SID D
Adder
1.4
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
246938BC-WTG3
Solar/Wind Harmer
0.263
246937BC-WTG2
Solar/Wind Harmer
0.295
970611AG2-400 GEN
Solar/Wind Harmer
7.225
270007AE1-245 C
Solar/Wind Harmer
0.002
970623AG2-406 GEN
Solar/Wind Harmer
1.309
962581AG1-107 GEN
Solar/Wind Harmer
0.001
942221AE2-234 GEN
Solar/Wind Harmer
0.036
970621AG2-405 GEN
Solar/Wind Harmer
1.305
970321AG2-212 GEN
Solar/Wind Harmer
3.076
270186AC1-089 GEN
Solar/Wind Harmer
0.004
270209AC1-174_GEN
Solar/Wind Harmer
0.001
970825AG2-519 GEN
Solar/Wind Harmer
7.834
957891AF2-083 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
970239AG2-162 GEN
Solar/Wind Harmer
1.73
274770LINCOLN ;1U
Adder
8.364
274771LINCOLN ;2U
Adder
8.364
274808UNIV PK N;4U
Adder
4.933
274888KELLY CRK;1U
Solar/Wind Harmer
0.404
972259AH1-714 GEN
Adder
18.805
970241AG2-163 GEN
Solar/Wind Harmer
3.993
238175AF1-290_GEN
Solar/Wind Helper
0.148
235020AA1-095 C
Solar/Wind Helper
0.051
205916AD1-020 GEN
Solar/Wind Helper
1.656
20390526W1-045 C
Solar/Wind Helper
0.338
233933AB2-153 GEN
Solar/Wind Helper
0.225
233944AB2-135 GEN
Solar/Wind Helper
0.569
24699105WLD G1 C
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
274776LINCOLN ;7U
Adder
8.364
274814UNIV PK N;0U
Adder
4.998
274807UNIV PK N;3U
Adder
4.987
274805UNIV PK N;1U
Adder
4.965
24386205FR-12G C
Solar/Wind Harmer
0.001
963841AG1-237 GEN
Solar/Wind Harmer
2.978
274687WILL CNTY;4U
Adder
27.495
274687WILL CNTY;4U
Adder
27.495
972163AH1-664 GEN
Solar/Wind Harmer
7.639
274731ELWOOD EC;2P
Adder
16.163
274733ELWOOD EC;3P
Adder
16.163
276882AE2-255 GEN
Solar/Wind Harmer
0.794
238152AF2-075_GEN
Solar/Wind Helper
0.683
23546401DTGZ2-030
Solar/Wind Helper
0.086
3138216PACIFIC
Solar/Wind Helper
0.043
23750501ELLIOTTS
Solar/Wind Helper
0.571
205956AE1-196_GEN
Solar/Wind Helper
0.492
233935AB2-179 C
Solar/Wind Helper
1.227
232436AB1-176 C
Solar/Wind Helper
0.043
233923SMA
Solar/Wind Helper
0.927
219914AD2-027 C
Solar/Wind Helper
0.111
23559001PLEAS1
50/50
5.385
961921AG1-034 GEN
Solar/Wind Harmer
7.364
942051AE2-217 GEN
Solar/Wind Harmer
14.169
970605AG2-385 GEN
Solar/Wind Harmer
4.731
270391AF1-285 GEN3
Solar/Wind Harmer
0.518
253333AC1-068 GEN
Solar/Wind Harmer
0.012
270273AD2-016 GEN
Solar/Wind Harmer
0.792
270291AC1-194 GEN
Solar/Wind Harmer
5.884
253415AE1-040 GEN
Solar/Wind Harmer
0.003
253406AD2-031_GEN
Solar/Wind Harmer
0.543
270377AD1-106 GEN
Solar/Wind Harmer
2.761
270247TR4_N_V136
Solar/Wind Harmer
0.047
944531AF1-118 GEN
Solar/Wind Harmer
32.203
270404AC1-167 GEN
Solar/Wind Harmer
0.003
25196608WSDLE5
Adder
8.745
970031AG2-029 GEN
Solar/Wind Harmer
4.625
970513AG2-328 GEN
Solar/Wind Harmer
3.076
970517AG2-330 GEN
Solar/Wind Harmer
18.457
970349AG2-230 GEN
Solar/Wind Harmer
10.632
958821AF2-173 GEN
Solar/Wind Harmer
9.902
270437AC2-090 C
Solar/Wind Harmer
0.003
247604X1-042
Adder
0.418
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
970781AG2-491 GEN
Solar/Wind Harmer
6.935
970519AG2-331 GEN
Solar/Wind Harmer
17.988
970699AG2-449 GEN
Solar/Wind Harmer
1.73
274752CRETE EC ;2U
Adder
8.172
958171AF2-111 GEN
Solar/Wind Harmer
17.278
274826FISK ;BP
Adder
10.802
24728705AND G3
Adder
7.914
972228AH1-698 GEN2
Adder
3.654
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
22.464
274730ELWOOD EC;6P
Adder
13.491
270541AE2-072 C
Solar/Wind Harmer
0.009
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
23750701CROSSCHOOL
Solar/Wind Helper
1.397
238127S14_GEN_2
Solar/Wind Helper
0.766
235062AE1-101 C1
Solar/Wind Helper
1.6
223401AF1-299 GEN
Solar/Wind Helper
0.355
233915AB1-141 GEN
Solar/Wind Helper
0.486
233998TM1NIN_3.36
Solar/Wind Helper
0.253
232404W1-003 C
Solar/Wind Helper
0.49
232428Y3-058 C
Solar/Wind Helper
0.327
233950AC2-186 GEN
Solar/Wind Helper
0.112
233972AC1-094 C
Solar/Wind Helper
0.292
228728W1-130C
Solar/Wind Helper
0.052
218660EHAMPSOLAR C
Solar/Wind Helper
0.032
316254AC1-120 GEN1
Solar/Wind Helper
1.026
963711AG1-223 GEN
Solar/Wind Helper
0.062
207454AA2-184 E
Solar/Wind Helper
0.299
20715228NPK_W1-113
Solar/Wind Helper
0.075
970153AG2-106 GEN
Solar/Wind Harmer
21.245
241955AC1-078 GEN
Solar/Wind Harmer
0.007
241974AD2-163_GEN2
Solar/Wind Harmer
0.006
24721905FLATG4
Adder
22.865
253370AE2-315 SEC1
Adder
2.103
253371AE2-315 SEC2
Adder
1.989
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
9.394
270588AE1-091_GEN
Solar/Wind Harmer
5.649
25194608D.CRK4
Adder
1.676
946031AF1-268 GEN
Solar/Wind Harmer
6.74
247643Z2-116 C
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.775
970291AG2-192 GEN
Solar/Wind Harmer
0.705
247642Z2-115 C
Solar/Wind Harmer
0.003
270535AF1-215 GEN1
Solar/Wind Harmer
0.009
24755605MDL-5G
Solar/Wind Harmer
0.001
276806AD2-047 C O1
Solar/Wind Harmer
3.901
24728505AND G1
Adder
3.784
274676JOLIET 29;8U
Adder
29.097
943121AE2-341 GEN
Solar/Wind Harmer
11.459
943591AF1-030 GEN
Solar/Wind Harmer
7.62
964991AG1-363 GEN
Solar/Wind Helper
4.969
316097T157 G90
Solar/Wind Helper
1.455
237080AD1-060 GEN
Solar/Wind Helper
0.33
966131AG1-482 GEN
Solar/Wind Helper
0.132
232422X3-066 FULL
Solar/Wind Helper
0.11
232426Y1-080 FULL
Solar/Wind Helper
0.038
233964AF2-378 GEN
Solar/Wind Helper
0.04
232434Z2-077 GEN
Solar/Wind Helper
0.123
219904AC1-010 C
Solar/Wind Helper
0.058
20720728JCB_W1-129
Solar/Wind Helper
0.055
20714828MDF_W3-079
Solar/Wind Helper
0.126
270120AB2-067 GEN2
50/50
6.869
270224U2-072_GEN2
Solar/Wind Harmer
0.001
938701AE1-092 GEN
Solar/Wind Harmer
12.484
964601AG1-323 GEN
Solar/Wind Harmer
3.106
964601AG1-323 GEN
Solar/Wind Harmer
2.071
971201AH1-060 GEN
Solar/Wind Harmer
1.471
970627AG2-408 GEN
Solar/Wind Harmer
2.167
960971AF2-388 GEN
Solar/Wind Harmer
4.192
970883AG2-550 GEN
Solar/Wind Harmer
7.123
25194408D.CRK1
Adder
7.711
270599AE1-208 GEN
Solar/Wind Harmer
6.495
926881AC1-175 GEN
Solar/Wind Harmer
0.001
270216AD2-079_GEN
Solar/Wind Harmer
0.001
24728905RICHG2
Adder
3.82
961051AF2-396 GEN
Solar/Wind Harmer
14.072
961051AF2-396 GEN
Solar/Wind Harmer
9.381
966841AG1-555 GEN
Solar/Wind Harmer
0.781
274803UNIV PARK;6U
Adder
5.755
274887GEN-1.85
Solar/Wind Harmer
0.181
958481AF2-142 GEN
Solar/Wind Harmer
10.238
274862TOP CROP ;2U
Solar/Wind Harmer
0.923
274879MINONK ;1U
Solar/Wind Harmer
0.287
23777901MDS_W4-102
Solar/Wind Helper
0.171
23585401KL_K28_T16
Solar/Wind Helper
1.328
237002AB1-128_GEN
Solar/Wind Helper
0.427
237006AB1-125 GEN
Solar/Wind Helper
0.119
208835TUHI V3-051
Solar/Wind Helper
0.023
208835TUHI V3-051
Solar/Wind Helper
0.023
232424Y1-079 C
Solar/Wind Helper
0.112
233970AC1-092 C
Solar/Wind Helper
0.338
230433AD2-135 GEN
Solar/Wind Helper
0.016
219921AF1-264
Solar/Wind Helper
0.049
219615MILLCREEK C
Solar/Wind Helper
0.026
219680HOPEWELLV C1
Solar/Wind Helper
0.003
24318905MLG2
50/50
6.89
270471AD2-092_GEN
Solar/Wind Harmer
0.006
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
971655AH1-328 GEN
Solar/Wind Harmer
2.758
276820AF1-078_GEN
Solar/Wind Harmer
0.002
970935AG2-582 GEN
Adder
242.403
25322209TAIT E
Adder
10.262
25322209TAIT E
Adder
10.031
253370AE2-315 SEC1
Adder
2.103
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
252519AF1-045_GEN
Solar/Wind Harmer
6.204
252516AE2-318_GEN
Solar/Wind Harmer
5.503
247621Y3-024
Adder
0.246
971613AH1-306 GEN
Solar/Wind Harmer
3.385
965681AG1-436 GEN
Solar/Wind Harmer
8.77
23559101PLEAS2
50/50
5.385
270122AB2-093 CT
50/50
3.689
970149AG2-104 GEN
Solar/Wind Harmer
35.932
270159DARBY CT4
Adder
9.89
970593AG2-378 GEN
Solar/Wind Harmer
1.75
270223U2-072_GEN1
Solar/Wind Harmer
0.001
253325AC1-069 GEN
Solar/Wind Harmer
0.012
270263AC1-001 GEN
Solar/Wind Harmer
0.758
270510AE1-227 GEN1
Solar/Wind Harmer
1.904
927014AC1-188 GEN
Solar/Wind Harmer
0.004
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
943021AE2-325 GEN
Solar/Wind Harmer
3.67
970773AG2-487 GEN
Solar/Wind Harmer
1.237
970373AG2-245 GEN
Solar/Wind Harmer
14.699
970515AG2-329 GEN
Solar/Wind Harmer
18.197
971917AH1-482 GEN
Solar/Wind Harmer
9.071
24791305MDL-5G
Solar/Wind Harmer
0.001
941551AE2-152 GEN
Solar/Wind Harmer
0.001
963741AG1-226 GEN
Solar/Wind Harmer
16.202
276691AA1-018 GEN1
Solar/Wind Harmer
0.827
238108AE1-109 GEN1
Solar/Wind Helper
0.106
235531U2-073 GEN
Solar/Wind Helper
3.034
235054AD2-180 GEN
Solar/Wind Helper
1.839
23562501BACKB
Solar/Wind Helper
0.842
205917AD1-020 ES
Solar/Wind Helper
0.356
233918AB1-142 GEN
Solar/Wind Helper
0.486
233994AC2-023 GEN
Solar/Wind Helper
0.929
233997TMININ_4.2
Solar/Wind Helper
0.253
233971AC1-093 C
Solar/Wind Helper
0.346
228729W2-030 C
Solar/Wind Helper
0.107
219348LDSOLAR C
Solar/Wind Helper
0.111
316170AC1-121 GEN2
Solar/Wind Helper
0.342
959561AF2-247 GEN
Solar/Wind Helper
0.02
20715028HAN_X4-015
Solar/Wind Helper
0.055
316045AC1-158 PL2
Solar/Wind Helper
4.009
219686LUMSOLAR_N C
Solar/Wind Helper
0.038
219304NAMERICA C
Solar/Wind Helper
0.127
207445AB1-138_GEN
Solar/Wind Helper
0.101
219607WPEMNERT C
Solar/Wind Helper
0.077
233946AB2-136 GEN
Solar/Wind Helper
0.549
232408W1-005 C
Solar/Wind Helper
0.49
232410W1-006 C
Solar/Wind Helper
0.49
233939AC1-091 C
Solar/Wind Helper
0.338
963401AG1-189 GEN
Solar/Wind Helper
0.054
963391AG1-188 GEN
Solar/Wind Helper
0.079
270166AC1-044 GEN3
50/50
6.869
246936BC-WTG1
Solar/Wind Harmer
0.295
270489AE1-102 GEN1
Solar/Wind Harmer
0.945
965011AG1-365 GEN
Solar/Wind Harmer
7.225
958861AF2-177 GEN
Solar/Wind Harmer
3.092
945371AF1-202 GEN
Solar/Wind Harmer
0.001
20715728PEM_W1-119
Solar/Wind Helper
0.093
316164AC1-076 GEN
Solar/Wind Helper
1.062
270005AE1-210 C O1
Solar/Wind Harmer
1.532
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
2.509
25196808ZIMRHP
Adder
76.799
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
270032AE2-172
Solar/Wind Harmer
4.701
945111AF1-176 GEN
Solar/Wind Harmer
12.568
270505AE1-170 C O1
Solar/Wind Harmer
7.393
247522W1-056 GEN
Solar/Wind Harmer
0.001
25196008MFTGT1
Adder
1.397
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.706
970333AG2-219 GEN
Solar/Wind Harmer
4.947
274751CRETE EC ;1U
Adder
8.172
274773LINCOLN ;4U
Adder
8.364
274774LINCOLN ;5U
Adder
8.364
274723RIVER EC ;12
Adder
17.756
24387305FR-4G C
Solar/Wind Harmer
0.003
274801UNIV PARK;4U
Adder
5.751
23583801GRNGAP
Solar/Wind Helper
5.418
238149AF1-291A_GEN
Solar/Wind Helper
0.137
237061AD1-155 GEN
Solar/Wind Helper
0.051
238221AF1-254 C O1
Solar/Wind Helper
0.265
3141196NOKESVL
Solar/Wind Helper
0.999
226910AB2-157 C
Solar/Wind Helper
0.014
223402AF1-300 C
Solar/Wind Helper
0.355
23751201ROTHROCK
Solar/Wind Helper
0.694
233982AB2-133 GEN
Solar/Wind Helper
0.346
233940AF2-379 C
Solar/Wind Helper
0.06
233952AC2-187 GEN
Solar/Wind Helper
0.225
219623KINSLEYBEA C
Solar/Wind Helper
0.002
20716028EGP_W2-019
Solar/Wind Helper
0.018
971997AH1-543 GEN
Solar/Wind Harmer
1.86
270051AF1-062 GEN
50/50
11.434
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270512AE1-227 GEN2
Solar/Wind Harmer
1.904
970065AG2-057 GEN
Solar/Wind Harmer
0.735
965021AG1-366 GEN
Solar/Wind Harmer
2.408
971191AH1-055 GEN
Solar/Wind Harmer
18.515
270043AE2-236 GEN
Solar/Wind Harmer
4.607
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
10.684
252510AF1-249 C
Solar/Wind Harmer
0.055
945111AF1-176 GEN
Solar/Wind Harmer
5.709
24441205WTRV SLR C
Solar/Wind Harmer
0
25196008MFTGT1
Adder
1.353
970243AG2-164 GEN
Solar/Wind Harmer
4.047
274772LINCOLN ;3U
Adder
8.364
274724RIVER EC ;11
Adder
17.549
274802UNIV PARK;5U
Adder
5.755
970941AG2-585 GEN
Solar/Wind Harmer
8.605
274800UNIV PARK;3U
Adder
5.751
972167AH1-666 GEN
Solar/Wind Harmer
5.505
276897AD1-100 C
Solar/Wind Harmer
0.009
274729ELWOOD EC;1P
Adder
16.163
276893AG1-478 C
Solar/Wind Harmer
0.272
276805AD2-038 GEN
Solar/Wind Harmer
0.002
237048AF1-022 C
Solar/Wind Helper
0.159
233930AB2-032 GEN
Solar/Wind Helper
0.368
233954AC2-188 GEN
Solar/Wind Helper
0.225
230511AF1-262
Solar/Wind Helper
0.014
230434AG1-499 GEN
Solar/Wind Helper
0.222
219258KINSLEYDEP C
Solar/Wind Helper
0.074
219907AC1-030 C
Solar/Wind Helper
0.033
270459AD2-067 GEN
Solar/Wind Harmer
0
270156DARBY CT1
Adder
10.05
270157DARBY CT2
Adder
10.026
940611AE2-048 GEN
Solar/Wind Harmer
18.967
941391AE2-136 GEN
Solar/Wind Harmer
10.684
970879AG2-548 GEN
Solar/Wind Harmer
6.645
270435AC2-044 GEN
Solar/Wind Harmer
0.92
971567AH1-282 GEN
Solar/Wind Harmer
10.843
247607V1-011 GEN
Solar/Wind Harmer
0.001
24729505KEY G4
Adder
6.671
270071AF1-092 GEN
Solar/Wind Harmer
13.737
270367AC2-061_GEN
Solar/Wind Harmer
0.006
971673AH1-337 GEN
Solar/Wind Harmer
4.631
270543AE2-219 C
Solar/Wind Harmer
0.004
25196408WSDLE3
Adder
9.002
25196308WSDLE2
Adder
8.924
25196208WSDLE1
Adder
8.902
25196708WSDLE6
Adder
8.879
270240V3-007_GEN2
Solar/Wind Harmer
0.002
270594AE1-207 GEN
Solar/Wind Harmer
7.898
971771AH1-392 GEN
Solar/Wind Harmer
7.046
971769AH1-391 GEN
Solar/Wind Harmer
7.844
25196108MFTGT2
Adder
1.54
25196108MFTGT2
Adder
1.43
971549AH1-272 GEN
Solar/Wind Harmer
14.344
24691005MDL-2G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
274728ELWOOD EC;5P
Adder
16.163
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
238126S14_GEN_1
Solar/Wind Helper
0.766
237085AD2-009_GEN
Solar/Wind Helper
1.588
316411AF1-147_GEN1
Solar/Wind Helper
0.86
316415AF1-147_GEN2
Solar/Wind Helper
0.86
3141426STAFORD
Solar/Wind Helper
0.051
228754AB1-001 C
Solar/Wind Helper
0.025
219272CLEANLIGHT C
Solar/Wind Helper
0.025
270054AF2-122 C O1
Solar/Wind Harmer
0.007
270520AE2-214 GEN
Solar/Wind Harmer
0.013
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
270158DARBY CT3
Adder
9.866
270317AD1-130_GEN
Solar/Wind Harmer
0.011
253349AC2-067 GEN
Solar/Wind Harmer
2.296
965051AG1-369 GEN
Solar/Wind Harmer
3.609
971985AH1-537 GEN
Solar/Wind Harmer
2.123
971029AG2-637 GEN
Solar/Wind Harmer
10.686
945581AF1-223 GEN
Solar/Wind Harmer
0.001
971347AH1-153 GEN
Solar/Wind Harmer
10.632
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
971619AH1-309 GEN
Solar/Wind Harmer
3.169
24725505WLD G2 C
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
4.146
24697605MDL-3G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
8.364
274777LINCOLN ;8U
Adder
8.364
24386405FR-21G C
Solar/Wind Harmer
0.001
972037AH1-567 GEN1
Adder
0.181
960591AF2-350 GEN
Solar/Wind Harmer
6.884
274675JOLIET 29;7U
Adder
30.175
274675JOLIET 29;7U
Adder
29.097
972165AH1-665 GEN
Solar/Wind Harmer
6.118
970833AG2-524 GEN
Solar/Wind Harmer
7.542
970833AG2-524 GEN
Solar/Wind Harmer
5.028
945641AF1-229 GEN
Solar/Wind Harmer
0.001
276868AE1-113 GEN
Solar/Wind Harmer
1.363
238208AF1-136 C
Solar/Wind Helper
0.211
205943AE1-185 GEN
Solar/Wind Helper
0.492
233990AG1-397 GEN
Solar/Wind Helper
0.261
964001AG1-254 GEN
Solar/Wind Helper
0.924
227927V4-067C
Solar/Wind Helper
0.01
219688LUMSOLAR_S C
Solar/Wind Helper
0.038
214067T20SOLAR
Solar/Wind Helper
0.011
20715828PEM_W1-120
Solar/Wind Helper
0.093
207459AE1-142 C O1
Solar/Wind Helper
0.28
219620RIDERU C
Solar/Wind Helper
0.001
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
971677AH1-339 GEN
Solar/Wind Harmer
0.768
238169AE2-226 GEN1
Solar/Wind Helper
0.677
238170AE2-226 GEN2
Solar/Wind Helper
0.677
238120AE2-309 GEN
Solar/Wind Helper
0.487
23777801MSM_W1-116
Solar/Wind Helper
0.11
237025AB1-124 C
Solar/Wind Helper
0.159
315651AD1-115 GEN
Solar/Wind Helper
0.76
316447AC1-158 HLD
Solar/Wind Helper
2.756
230407AD2-065 C
Solar/Wind Helper
0.039
20714928UPF_X1-085
Solar/Wind Helper
0.005
962761AG1-125 GEN
Solar/Wind Harmer
33.269
270462AD2-086
Solar/Wind Harmer
0.016
241813AF1-122_GEN
Solar/Wind Harmer
3.294
25326309TAIT D
Adder
1.153
247536S-71 GEN
Solar/Wind Harmer
0.287
270063AE2-323 C
Solar/Wind Harmer
0.006
252507AC2-088 GEN
Solar/Wind Harmer
0.323
970245AG2-165 GEN
Solar/Wind Harmer
3.076
944231AF1-091 GEN
Solar/Wind Harmer
1.885
276903AD2-071 C
Solar/Wind Harmer
7.842
958381AF2-132 GEN
Solar/Wind Harmer
0.001
274754CRETE EC ;4U
Adder
8.172
24385905FR-11G C
Solar/Wind Harmer
0.002
939401AE1-172 GEN
Solar/Wind Harmer
5.109
238147AE2-230_GEN1
Solar/Wind Helper
0.478
238117U2-030
Solar/Wind Helper
0.314
235067AD1-061 GEN
Solar/Wind Helper
0.478
234015AF2-250 C
Solar/Wind Helper
0.037
316044AC1-158 PL1
Solar/Wind Helper
1.252
316450AC1-158 RIC
Solar/Wind Helper
0.334
219276PARKLANDSO C
Solar/Wind Helper
0.086
20720528MAN_W1-024
Solar/Wind Helper
0.027
963791AG1-232 GEN
Solar/Wind Harmer
9.689
270024AE2-089 GEN
Solar/Wind Harmer
0.008
252524AE2-267 GEN
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
1.339
270536AF1-215 GEN2
Solar/Wind Harmer
0.009
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274811UNIV PK N;7U
Adder
4.954
274827FISK ;RP
Adder
7.655
972227AH1-698 GEN1
Adder
2.573
274735ELWOOD EC;4P
Adder
16.163
238109AE1-109 GEN2
Solar/Wind Helper
0.106
238110AE1-109 GEN3
Solar/Wind Helper
0.106
959381AF2-229 GEN
Solar/Wind Helper
0.345
960921AF2-383 GEN
Solar/Wind Helper
0.352
205932AD2-116_GEN
Solar/Wind Helper
0.492
234033AF1-007_GEN
Solar/Wind Helper
6.787
232432Z2-076 GEN
Solar/Wind Helper
0.065
203975AE1-071-GEN
Solar/Wind Helper
2.41
NYPJM->LTFIMP_NY
CLTF
4.628
LGEELTFEXP_LGEE->PJM
CLTF
6.497
WECLTFEXP_WEC->PJM
CLTF
3.686
AG2-052LTFEXP_AG2-052->PJM
LTF
0.231
AH1-155LTFEXP_AH1-155->PJM
LTF
0.346
CBM West 1LTFEXP_CBM-W1->PJM
CBM
137.982
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.984
MECLTFEXP_MEC->PJM
CLTF
15.319
SIGELTFEXP_SIGE->PJM
CLTF
0.486
LAGNLTFEXP_LAGN->PJM
CLTF
14.268
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.432
TVALTFEXP_TVA->PJM
CLTF
7.011
CPLELTFEXP_CPLE->PJM
CLTF
0.567
CBM West 2LTFEXP_CBM-W2->PJM
CBM
108.576

Details for 05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line l/o AP_P1-3_MP-765-501T_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AP_P1-3_MP-765-501T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.76 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4919.18
MW Contribution:1.38
Bus #Bus NameTypeMW Contribution
270475AD2-096_GEN
50/50
10.066
253338AC1-165 GEN
Solar/Wind Harmer
0.004
972173AH1-669 GEN
Solar/Wind Harmer
4.474
959331AF2-224 GEN
Solar/Wind Harmer
6.217
970191AG2-125 GEN
Solar/Wind Harmer
2.269
270191TR4_S_V150
Solar/Wind Harmer
0.001
971617AH1-308 GEN
Solar/Wind Harmer
7.263
270491AE1-102 GEN2
Solar/Wind Harmer
1.132
270004AE1-209 GEN
Solar/Wind Harmer
1.875
270222AC2-111 GEN
Solar/Wind Harmer
4.32
274753CRETE EC ;3U
Adder
10.063
24642205MAYFLWER
Adder
0.776
964401AG1-302 GEN
Solar/Wind Harmer
0.001
972038AH1-567 GEN2
Adder
0.444
270356AE2-297 GEN
Solar/Wind Harmer
0.011
274872LEEDK;1U
Solar/Wind Harmer
0.307
270258AD1-119 GEN
Solar/Wind Harmer
0.002
972236AH1-702 GEN2
Adder
2.611
20089126CSLMN_L13
Solar/Wind Helper
0.557
238118U2-030_1
Solar/Wind Helper
0.269
203854AF2-039 C
Solar/Wind Helper
0.3
20334926Z1-069 C
Solar/Wind Helper
1.268
270161DARBY CT6
50/50
0.725
942861AE2-305 GEN
Solar/Wind Harmer
8.094
270518AE2-148 GEN
Solar/Wind Harmer
0.847
970329AG2-216 GEN
Solar/Wind Harmer
4.005
25326109MON D
Adder
1.698
944541AF1-119 GEN
Solar/Wind Harmer
0.594
270031AE2-169
Solar/Wind Harmer
4.777
270201AC2-176 GEN
Solar/Wind Harmer
0.002
964611AG1-324 GEN
Solar/Wind Harmer
0.65
970885AG2-551 GEN
Solar/Wind Harmer
2.883
960441AF2-335 GEN
Solar/Wind Harmer
8.628
270383AD1-128 GEN
Solar/Wind Harmer
0.005
24379505HDWTR1G C
Solar/Wind Harmer
0.003
965791AG1-447 GEN
Solar/Wind Harmer
7.878
247620Y3-023
Adder
0.565
270526AF1-158 GEN
Solar/Wind Harmer
0.011
24441505OLIV SLR
Solar/Wind Harmer
0
276843GEN-1.7
Solar/Wind Harmer
0.275
958011AF2-095 GEN
Solar/Wind Harmer
12.235
24728805RICHG1
Adder
4.598
945421AF1-207 GEN
Solar/Wind Harmer
0.001
971573AH1-285 GEN
Solar/Wind Harmer
1.571
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274695ROCKY RD ;2P
Adder
13.416
25183208HLCRTG
Solar/Wind Harmer
0.013
958491AF2-143 GEN
Solar/Wind Harmer
12.583
25194508D.CRK3
Adder
1.697
942991AE2-321 GEN
Solar/Wind Harmer
9.334
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
971333AH1-146 GEN
Solar/Wind Harmer
16.689
20088926STNY CRK
Solar/Wind Helper
0.77
20088626ARWF_N39
Solar/Wind Helper
1.147
946381AF1-302 GEN
Solar/Wind Helper
0.21
203946AE2-131 C
Solar/Wind Helper
0.448
238217AF1-153 C O1
Solar/Wind Helper
0.223
270286AF1-227 GEN2
Solar/Wind Harmer
0.006
961821AG1-024 GEN
Solar/Wind Harmer
6.623
270578AF1-285 GEN2
Solar/Wind Harmer
0.678
945631AF1-228 GEN
Solar/Wind Harmer
0
241972AD1-140 GEN
Solar/Wind Harmer
1.032
270432AC2-029 GEN
Solar/Wind Harmer
4.134
270269AC2-059
Solar/Wind Harmer
0.005
965101AG1-375 GEN
Solar/Wind Harmer
8.831
253400AC2-068 GEN
Solar/Wind Harmer
1.117
965041AG1-368 GEN
Solar/Wind Harmer
8.719
270340AC2-060 GEN
Solar/Wind Harmer
0.01
971609AH1-304 GEN
Solar/Wind Harmer
1.419
970115AG2-085 GEN
Solar/Wind Harmer
3.451
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
274776LINCOLN ;7U
Adder
10.354
24699105WLD G1 C
Solar/Wind Harmer
0.001
274814UNIV PK N;0U
Adder
6.16
274807UNIV PK N;3U
Adder
6.147
274805UNIV PK N;1U
Adder
6.12
274687WILL CNTY;4U
Adder
33.939
274687WILL CNTY;4U
Adder
33.939
274731ELWOOD EC;2P
Adder
19.951
274733ELWOOD EC;3P
Adder
19.951
274746AC1-111 G10
Adder
6.762
24690905MDL-1G C
Solar/Wind Harmer
0.003
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
25196508WSDLE4
Adder
10.2
24386205FR-12G C
Solar/Wind Harmer
0.001
276882AE2-255 GEN
Solar/Wind Harmer
0.979
963841AG1-237 GEN
Solar/Wind Harmer
3.615
926823AC1-168 GEN
Solar/Wind Harmer
1.415
254304AE2-114 C
Solar/Wind Helper
0.214
241982AE2-343 S C
Solar/Wind Helper
0.217
23750501ELLIOTTS
Solar/Wind Helper
0.61
203961AE2-224 GEN
Solar/Wind Helper
2.278
270119AB2-067 GEN1
50/50
18.401
970077AG2-063 GEN
Solar/Wind Harmer
5.8
253378AE2-206_GEN
Solar/Wind Harmer
0.005
25326509SID D
Adder
1.713
970611AG2-400 GEN
Solar/Wind Harmer
8.881
970321AG2-212 GEN
Solar/Wind Harmer
3.83
942221AE2-234 GEN
Solar/Wind Harmer
0.044
246938BC-WTG3
Solar/Wind Harmer
0.316
246937BC-WTG2
Solar/Wind Harmer
0.353
253394AE2-221_GEN
Solar/Wind Harmer
0.011
253398AE2-221_GEN2
Solar/Wind Harmer
0.011
970825AG2-519 GEN
Solar/Wind Harmer
9.566
270209AC1-174_GEN
Solar/Wind Harmer
0.001
274770LINCOLN ;1U
Adder
10.354
274771LINCOLN ;2U
Adder
10.354
270007AE1-245 C
Solar/Wind Harmer
0.002
274808UNIV PK N;4U
Adder
6.08
274888KELLY CRK;1U
Solar/Wind Harmer
0.499
972259AH1-714 GEN
Adder
23.234
957891AF2-083 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
274696ROCKY RD ;4P
Adder
13.733
274697ROCKY RD ;3P
Adder
3.645
962691AG1-118 GEN
Solar/Wind Harmer
25.162
970623AG2-406 GEN
Solar/Wind Harmer
1.522
970241AG2-163 GEN
Solar/Wind Harmer
4.844
241985AE1-237 GEN
Solar/Wind Helper
0.242
962101AG1-054 GEN
Solar/Wind Helper
0.632
944781AF1-143 GEN
Solar/Wind Helper
2.312
203940AF1-140 C
Solar/Wind Helper
0.374
270159DARBY CT4
50/50
13.494
970149AG2-104 GEN
Solar/Wind Harmer
54.635
270223U2-072_GEN1
Solar/Wind Harmer
0.001
970593AG2-378 GEN
Solar/Wind Harmer
2.27
253325AC1-069 GEN
Solar/Wind Harmer
0.015
270263AC1-001 GEN
Solar/Wind Harmer
0.865
970373AG2-245 GEN
Solar/Wind Harmer
17.958
971917AH1-482 GEN
Solar/Wind Harmer
11.064
941551AE2-152 GEN
Solar/Wind Harmer
0.001
970773AG2-487 GEN
Solar/Wind Harmer
1.492
24791305MDL-5G
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
4.404
276691AA1-018 GEN1
Solar/Wind Harmer
1.02
274872LEEDK;1U
Solar/Wind Harmer
0.005
959081AF2-199 GEN
Solar/Wind Harmer
8.33
971067AG2-660 GEN
Solar/Wind Harmer
2.777
274822ROCKFORD ;11
Adder
23.399
963741AG1-226 GEN
Solar/Wind Harmer
19.652
20094526CT_V3-030
Solar/Wind Helper
0.446
235054AD2-180 GEN
Solar/Wind Helper
1.566
235531U2-073 GEN
Solar/Wind Helper
2.545
203954AE2-126 C
Solar/Wind Helper
0.443
970819AG2-516 GEN
Solar/Wind Harmer
7.858
270158DARBY CT3
50/50
13.461
270036AE2-216 BAT
50/50
8.994
270287AF1-227 GEN3
Solar/Wind Harmer
0.006
270520AE2-214 GEN
Solar/Wind Harmer
0.017
270054AF2-122 C O1
Solar/Wind Harmer
0.009
270317AD1-130_GEN
Solar/Wind Harmer
0.014
253349AC2-067 GEN
Solar/Wind Harmer
2.778
945581AF1-223 GEN
Solar/Wind Harmer
0.001
971347AH1-153 GEN
Solar/Wind Harmer
13.153
965051AG1-369 GEN
Solar/Wind Harmer
4.367
971029AG2-637 GEN
Solar/Wind Harmer
12.951
274775LINCOLN ;6U
Adder
10.354
274777LINCOLN ;8U
Adder
10.354
24725505WLD G2 C
Solar/Wind Harmer
0.002
960591AF2-350 GEN
Solar/Wind Harmer
8.497
972037AH1-567 GEN1
Adder
0.223
971619AH1-309 GEN
Solar/Wind Harmer
3.821
971611AH1-305 GEN
Solar/Wind Harmer
5.053
274675JOLIET 29;7U
Adder
37.252
274675JOLIET 29;7U
Adder
35.922
970833AG2-524 GEN
Solar/Wind Harmer
9.313
970833AG2-524 GEN
Solar/Wind Harmer
6.209
24697605MDL-3G C
Solar/Wind Harmer
0.002
270181AB1-006 GEN2
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0.001
276868AE1-113 GEN
Solar/Wind Harmer
1.681
971675AH1-338 GEN
Solar/Wind Harmer
3.256
971411AH1-196 GEN
Solar/Wind Harmer
12.519
971171AH1-044 GEN
Solar/Wind Harmer
16.66
274823ROCKFORD ;21
Adder
23.229
20092526R32
Solar/Wind Helper
1.098
203846AF2-130 C
Solar/Wind Helper
0.425
203855AF2-088 C
Solar/Wind Helper
0.144
961921AG1-034 GEN
Solar/Wind Harmer
9.935
942051AE2-217 GEN
Solar/Wind Harmer
18.548
270391AF1-285 GEN3
Solar/Wind Harmer
0.678
970605AG2-385 GEN
Solar/Wind Harmer
6.136
253333AC1-068 GEN
Solar/Wind Harmer
0.015
270273AD2-016 GEN
Solar/Wind Harmer
0.935
944531AF1-118 GEN
Solar/Wind Harmer
40.219
970513AG2-328 GEN
Solar/Wind Harmer
3.83
970517AG2-330 GEN
Solar/Wind Harmer
22.981
253415AE1-040 GEN
Solar/Wind Harmer
0.004
970349AG2-230 GEN
Solar/Wind Harmer
13.153
270247TR4_N_V136
Solar/Wind Harmer
0.056
970031AG2-029 GEN
Solar/Wind Harmer
5.627
958821AF2-173 GEN
Solar/Wind Harmer
12.116
253406AD2-031_GEN
Solar/Wind Harmer
0.643
270437AC2-090 C
Solar/Wind Harmer
0.004
274752CRETE EC ;2U
Adder
10.063
970707AG2-453 GEN
Solar/Wind Harmer
27.781
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
972228AH1-698 GEN2
Adder
4.511
274826FISK ;BP
Adder
13.329
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
274730ELWOOD EC;6P
Adder
19.951
970781AG2-491 GEN
Solar/Wind Harmer
8.438
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
25196608WSDLE5
Adder
10.305
274855GSG-6 ;RU
Solar/Wind Harmer
0.306
24728705AND G3
Adder
9.564
254305AE2-115 C
Solar/Wind Helper
0.214
202652Y1-033 WT C
Solar/Wind Helper
0.525
20089026BF_G21_K23
Solar/Wind Helper
0.441
23750701CROSSCHOOL
Solar/Wind Helper
1.122
238127S14_GEN_2
Solar/Wind Helper
0.64
238202AE2-262_GEN
Solar/Wind Helper
0.902
270120AB2-067 GEN2
50/50
18.401
270160DARBY CT5
50/50
0.735
270466AD2-091
50/50
8.176
270224U2-072_GEN2
Solar/Wind Harmer
0.001
964601AG1-323 GEN
Solar/Wind Harmer
3.902
964601AG1-323 GEN
Solar/Wind Harmer
2.601
938701AE1-092 GEN
Solar/Wind Harmer
15.513
970627AG2-408 GEN
Solar/Wind Harmer
2.664
960971AF2-388 GEN
Solar/Wind Harmer
5.197
270599AE1-208 GEN
Solar/Wind Harmer
7.961
970883AG2-550 GEN
Solar/Wind Harmer
8.648
926881AC1-175 GEN
Solar/Wind Harmer
0.001
270216AD2-079_GEN
Solar/Wind Harmer
0.001
274887GEN-1.85
Solar/Wind Harmer
0.224
274803UNIV PARK;6U
Adder
7.1
24728905RICHG2
Adder
4.598
274674JOLIET 9 ;6U
Adder
18.689
961051AF2-396 GEN
Solar/Wind Harmer
16.913
961051AF2-396 GEN
Solar/Wind Harmer
11.276
958481AF2-142 GEN
Solar/Wind Harmer
12.626
274862TOP CROP ;2U
Solar/Wind Harmer
1.139
274693ROCKY RD ;1P
Adder
13.284
274683WAUKEGAN ;8U
Adder
25.365
274683WAUKEGAN ;8U
Adder
21.381
966841AG1-555 GEN
Solar/Wind Harmer
0.948
970921AG2-575 GEN
Solar/Wind Harmer
8.38
970921AG2-575 GEN
Solar/Wind Harmer
2.793
274879MINONK ;1U
Solar/Wind Harmer
0.353
25194408D.CRK1
Adder
9.077
971335AH1-147 GEN
Solar/Wind Harmer
16.689
23652301WDPWR_K20
Solar/Wind Helper
0.137
241967AE2-285_GEN
Solar/Wind Helper
0.621
946071AF1-272 GEN
Solar/Wind Helper
2.567
23585401KL_K28_T16
Solar/Wind Helper
1.167
203955AF1-039 C O1
Solar/Wind Helper
0.346
20083426SW_E13_K22
Solar/Wind Helper
0.053
20084626FORWARD
Solar/Wind Helper
0.336
20398826ARMNA MT
Solar/Wind Helper
1.407
962761AG1-125 GEN
Solar/Wind Harmer
50.586
270462AD2-086
Solar/Wind Harmer
0.021
25326309TAIT D
Adder
1.4
970245AG2-165 GEN
Solar/Wind Harmer
3.83
247536S-71 GEN
Solar/Wind Harmer
0.349
270063AE2-323 C
Solar/Wind Harmer
0.007
276903AD2-071 C
Solar/Wind Harmer
9.56
274754CRETE EC ;4U
Adder
10.063
958381AF2-132 GEN
Solar/Wind Harmer
0.001
274674JOLIET 9 ;6U
Adder
18.689
274732ELWOOD EC;7P
Adder
19.951
939401AE1-172 GEN
Solar/Wind Harmer
6.298
24385905FR-11G C
Solar/Wind Harmer
0.002
962781AG1-127 GEN
Solar/Wind Harmer
7.975
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
972235AH1-702 GEN1
Adder
3.003
20088826HIGHLAND
Solar/Wind Helper
0.847
238117U2-030
Solar/Wind Helper
0.269
964391AG1-301 GEN
Solar/Wind Helper
0.446
970153AG2-106 GEN
Solar/Wind Harmer
32.303
241955AC1-078 GEN
Solar/Wind Harmer
0.009
241974AD2-163_GEN2
Solar/Wind Harmer
0.008
253370AE2-315 SEC1
Adder
2.545
253371AE2-315 SEC2
Adder
2.407
24721905FLATG4
Adder
25.369
946031AF1-268 GEN
Solar/Wind Harmer
8.226
970289AG2-191 GEN
Solar/Wind Harmer
0.947
970291AG2-192 GEN
Solar/Wind Harmer
0.861
247642Z2-115 C
Solar/Wind Harmer
0.004
247643Z2-116 C
Solar/Wind Harmer
0
253316AC1-085 GEN3
Solar/Wind Harmer
0.005
253433AC1-085 GEN1
Solar/Wind Harmer
0.004
946181AF1-283 GEN
Solar/Wind Harmer
11.138
270535AF1-215 GEN1
Solar/Wind Harmer
0.011
276806AD2-047 C O1
Solar/Wind Harmer
4.815
274676JOLIET 29;8U
Adder
35.922
274734ELWOOD EC;8P
Adder
19.951
274736ELWOOD EC;9P
Adder
19.951
943121AE2-341 GEN
Solar/Wind Harmer
14.16
943591AF1-030 GEN
Solar/Wind Harmer
9.416
24755605MDL-5G
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
21.642
25194608D.CRK4
Adder
1.973
959091AF2-200 GEN
Solar/Wind Harmer
16.66
24728505AND G1
Adder
4.573
235058AG1-386 C
Solar/Wind Helper
0.453
964991AG1-363 GEN
Solar/Wind Helper
3.577
203818AF1-086 GEN
Solar/Wind Helper
1.594
962771AG1-126 GEN
Solar/Wind Harmer
50.586
270284AF1-227 GEN1
Solar/Wind Harmer
0.014
253383AE2-342_GEN
Solar/Wind Harmer
0.004
241973AD2-163_GEN1
Solar/Wind Harmer
0.008
943861AF1-054 GEN
Solar/Wind Harmer
3.995
943851AF1-053 GEN
Solar/Wind Harmer
2.767
270302AB2-170 GEN
Solar/Wind Harmer
0.006
971653AH1-327 GEN
Solar/Wind Harmer
1.38
970689AG2-444 GEN
Solar/Wind Harmer
19.097
253372AE2-315 SEC3
Adder
2.407
253372AE2-315 SEC3
Adder
2.407
970155AG2-107 GEN
Solar/Wind Harmer
32.303
270349AD2-093_GEN
Solar/Wind Harmer
0.009
253343AC1-166 GEN
Solar/Wind Harmer
0.004
960071AF2-298 GEN
Solar/Wind Harmer
4.426
253370AE2-315 SEC1
Adder
2.545
253371AE2-315 SEC2
Adder
2.407
965651AG1-433 GEN
Solar/Wind Harmer
2.599
971995AH1-542 GEN
Solar/Wind Harmer
3.236
247521TR3_G114
Solar/Wind Harmer
0.319
270246TR4_N_V150
Solar/Wind Harmer
0.056
24721705FLATG2
Adder
25.369
965421AG1-410 GEN
Solar/Wind Harmer
26.181
965031AG1-367 GEN
Solar/Wind Harmer
8.654
24695305TIMB G C
Solar/Wind Harmer
0.002
970291AG2-192 GEN
Solar/Wind Harmer
1.119
970613AG2-401 GEN
Solar/Wind Harmer
6.306
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
8.568
24639705ELKHART HY
Adder
0.188
270055AF2-134 C O1
Solar/Wind Harmer
0.007
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
6.107
276776AD2-060 GEN
Solar/Wind Harmer
0.887
274676JOLIET 29;8U
Adder
37.252
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
274745AC1-111 GEN9
Adder
6.762
270449AD2-020 GEN
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
21.642
274828WAUKEGAN ;BP
Adder
13.296
276901AD2-066 C O1
Solar/Wind Harmer
0.008
25194608D.CRK4
Adder
1.973
957471AF2-041 GEN
Solar/Wind Harmer
24.989
24728605AND G2
Adder
4.573
241966AE1-183 GEN
Solar/Wind Helper
0.248
238185AF2-356 C
Solar/Wind Helper
2.025
964201AG1-281 GEN
Solar/Wind Helper
0.457
238206AE2-263_GEN
Solar/Wind Helper
0.858
270471AD2-092_GEN
Solar/Wind Harmer
0.009
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
971655AH1-328 GEN
Solar/Wind Harmer
3.428
276820AF1-078_GEN
Solar/Wind Harmer
0.002
25322209TAIT E
Adder
12.455
25322209TAIT E
Adder
12.175
253370AE2-315 SEC1
Adder
2.545
247621Y3-024
Adder
0.3
971613AH1-306 GEN
Solar/Wind Harmer
4.135
965681AG1-436 GEN
Solar/Wind Harmer
10.743
253317AC1-085 GEN4
Solar/Wind Harmer
0.005
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
252519AF1-045_GEN
Solar/Wind Harmer
7.283
252516AE2-318_GEN
Solar/Wind Harmer
6.46
971341AH1-150 GEN
Solar/Wind Harmer
16.66
971343AH1-151 GEN
Solar/Wind Harmer
16.66
241801AE1-079 GEN
Solar/Wind Helper
0.242
20303426NA_O38_P22
Solar/Wind Helper
0.94
203853AF1-134 C O1
Solar/Wind Helper
0.452
203952AE2-129 C
Solar/Wind Helper
0.447
238120AE2-309 GEN
Solar/Wind Helper
0.401
25306009OHH W.
Adder
3.647
963791AG1-232 GEN
Solar/Wind Harmer
11.841
270024AE2-089 GEN
Solar/Wind Harmer
0.009
957201AF2-014 GEN
Solar/Wind Harmer
0.001
970289AG2-191 GEN
Solar/Wind Harmer
1.635
270536AF1-215 GEN2
Solar/Wind Harmer
0.011
274811UNIV PK N;7U
Adder
6.107
958391AF2-133 GEN
Solar/Wind Harmer
0.001
972227AH1-698 GEN1
Adder
3.176
274827FISK ;RP
Adder
9.447
274735ELWOOD EC;4P
Adder
19.951
274744AC1-111 GEN8
Adder
6.762
252524AE2-267 GEN
Solar/Wind Harmer
0.003
970169AG2-114 GEN
Solar/Wind Harmer
8.358
241997AF1-093 GEN
Solar/Wind Helper
0.248
20091526CHSTN_FL
Solar/Wind Helper
0.55
20090526Q36
Solar/Wind Helper
0.985
203993AD2-133_GEN1
Solar/Wind Helper
0.985
203804AE2-113_GEN
Solar/Wind Helper
1.639
270166AC1-044 GEN3
50/50
18.401
965011AG1-365 GEN
Solar/Wind Harmer
8.881
958861AF2-177 GEN
Solar/Wind Harmer
3.827
945371AF1-202 GEN
Solar/Wind Harmer
0.001
246936BC-WTG1
Solar/Wind Harmer
0.353
270489AE1-102 GEN1
Solar/Wind Harmer
1.132
270005AE1-210 C O1
Solar/Wind Harmer
1.875
970825AG2-519 GEN
Solar/Wind Harmer
3.064
270032AE2-172
Solar/Wind Harmer
5.743
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0.001
274773LINCOLN ;4U
Adder
10.354
274774LINCOLN ;5U
Adder
10.354
274723RIVER EC ;12
Adder
21.894
274751CRETE EC ;1U
Adder
10.063
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
274801UNIV PARK;4U
Adder
7.097
945111AF1-176 GEN
Solar/Wind Harmer
15.149
270505AE1-170 C O1
Solar/Wind Harmer
8.915
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
10.609
24387305FR-4G C
Solar/Wind Harmer
0.003
971997AH1-543 GEN
Solar/Wind Harmer
4.396
276861AD2-134 GEN
Solar/Wind Harmer
0.15
970569AG2-363 GEN
Solar/Wind Harmer
24.96
25196808ZIMRHP
Adder
58.315
254303AC2-168 GEN
Solar/Wind Helper
0.155
237046AF1-021 C
Solar/Wind Helper
0.463
20089226LOOKOUT
Solar/Wind Helper
0.542
270051AF1-062 GEN
50/50
17.076
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270043AE2-236 GEN
Solar/Wind Harmer
5.712
965021AG1-366 GEN
Solar/Wind Harmer
2.96
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
13.019
274772LINCOLN ;3U
Adder
10.354
274724RIVER EC ;11
Adder
21.639
970941AG2-585 GEN
Solar/Wind Harmer
10.621
274802UNIV PARK;5U
Adder
7.1
274800UNIV PARK;3U
Adder
7.097
276897AD1-100 C
Solar/Wind Harmer
0.011
945111AF1-176 GEN
Solar/Wind Harmer
6.882
274729ELWOOD EC;1P
Adder
19.951
276893AG1-478 C
Solar/Wind Harmer
0.336
276805AD2-038 GEN
Solar/Wind Harmer
0.002
252510AF1-249 C
Solar/Wind Harmer
0.065
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
0.891
276889AE2-281 GEN
Solar/Wind Harmer
0.001
274850MENDOTA H;RU
Solar/Wind Harmer
0.098
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.15
24441205WTRV SLR C
Solar/Wind Harmer
0
970571AG2-364 GEN
Solar/Wind Harmer
16.64
237048AF1-022 C
Solar/Wind Helper
0.176
237043AE2-125 C
Solar/Wind Helper
0.172
270156DARBY CT1
50/50
13.713
270157DARBY CT2
50/50
13.679
270459AD2-067 GEN
Solar/Wind Harmer
0
24729505KEY G4
Adder
8.316
270071AF1-092 GEN
Solar/Wind Harmer
17.084
270435AC2-044 GEN
Solar/Wind Harmer
1.103
270543AE2-219 C
Solar/Wind Harmer
0.005
971673AH1-337 GEN
Solar/Wind Harmer
5.609
270594AE1-207 GEN
Solar/Wind Harmer
9.648
270240V3-007_GEN2
Solar/Wind Harmer
0.003
971771AH1-392 GEN
Solar/Wind Harmer
8.573
971769AH1-391 GEN
Solar/Wind Harmer
9.561
247607V1-011 GEN
Solar/Wind Harmer
0.001
274728ELWOOD EC;5P
Adder
19.951
24691005MDL-2G C
Solar/Wind Harmer
0.002
274863CRW1-WTG
Solar/Wind Harmer
0.003
274864CRW2-WTG
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
10.608
25196308WSDLE2
Adder
10.516
25196208WSDLE1
Adder
10.49
25196708WSDLE6
Adder
10.463
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
971177AH1-047 GEN
Solar/Wind Harmer
5.154
238126S14_GEN_1
Solar/Wind Helper
0.64
941231AE2-117 GEN
Solar/Wind Helper
0.447
23751201ROTHROCK
Solar/Wind Helper
0.652
NYPJM->LTFIMP_NY
CLTF
5.332
LGEELTFEXP_LGEE->PJM
CLTF
7.674
WECLTFEXP_WEC->PJM
CLTF
4.549
AG2-052LTFEXP_AG2-052->PJM
LTF
0.283
AH1-155LTFEXP_AH1-155->PJM
LTF
0.424
CBM West 1LTFEXP_CBM-W1->PJM
CBM
155.754
CBM South 1LTFEXP_CBM-S1->PJM
CBM
34.409
MECLTFEXP_MEC->PJM
CLTF
18.875
SIGELTFEXP_SIGE->PJM
CLTF
0.583
LAGNLTFEXP_LAGN->PJM
CLTF
17.886
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.768
TVALTFEXP_TVA->PJM
CLTF
8.721
CPLELTFEXP_CPLE->PJM
CLTF
2.705
CBM West 2LTFEXP_CBM-W2->PJM
CBM
133.737

Details for 05MALIS-05VASSEL 765.0 kV Ckt 1 line l/o AEP_P1-2_#706_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MALIS-05VASSEL 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#706_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.0 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4722.06
MW Contribution:1.38
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
4.694
270144AC1-141 ST1_
50/50
3.051
270286AF1-227 GEN2
Solar/Wind Harmer
0.006
270578AF1-285 GEN2
Solar/Wind Harmer
0.683
960681AF2-359 GEN
Solar/Wind Harmer
-0.002
965041AG1-368 GEN
Solar/Wind Harmer
9.739
274776LINCOLN ;7U
Adder
11.607
247620Y3-023
50/50
0.701
270101X2-052 CT2
50/50
2.1
270526AF1-158 GEN
Solar/Wind Harmer
0.012
24441505OLIV SLR
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
9.057
276843GEN-1.7
Solar/Wind Harmer
0.304
958011AF2-095 GEN
Solar/Wind Harmer
13.537
944541AF1-119 GEN
Solar/Wind Harmer
0.622
971573AH1-285 GEN
Solar/Wind Harmer
1.715
274695ROCKY RD ;2P
Adder
14.586
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
958491AF2-143 GEN
Solar/Wind Harmer
13.566
942991AE2-321 GEN
Solar/Wind Harmer
10.048
971333AH1-146 GEN
Solar/Wind Harmer
17.91
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
945421AF1-207 GEN
Solar/Wind Harmer
0.001
274765LEE CO EC;6U
Adder
11.682
274763LEE CO EC;4U
Adder
11.544
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
276646AC1-214 GEN2
Solar/Wind Harmer
0.339
270031AE2-169
Solar/Wind Harmer
4.634
960441AF2-335 GEN
Solar/Wind Harmer
7.977
270201AC2-176 GEN
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
0.595
276911AD2-131_GEN
Solar/Wind Harmer
0.843
24641605TWIN BRNCH
50/50
0.025
24344005CKG1
50/50
9.376
970349AG2-230 GEN
Solar/Wind Harmer
15.658
270391AF1-285 GEN3
Solar/Wind Harmer
0.683
970513AG2-328 GEN
Solar/Wind Harmer
4.403
970517AG2-330 GEN
Solar/Wind Harmer
26.415
970031AG2-029 GEN
Solar/Wind Harmer
6.551
944531AF1-118 GEN
Solar/Wind Harmer
44.632
247604X1-042
Adder
0.578
270247TR4_N_V136
Solar/Wind Harmer
0.062
274752CRETE EC ;2U
Adder
11.24
970707AG2-453 GEN
Solar/Wind Harmer
30.794
274826FISK ;BP
Adder
14.766
972228AH1-698 GEN2
Adder
4.987
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
274730ELWOOD EC;6P
Adder
21.93
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
274855GSG-6 ;RU
Solar/Wind Harmer
0.329
270404AC1-167 GEN
Solar/Wind Harmer
0.004
970781AG2-491 GEN
Solar/Wind Harmer
8.621
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
959611AF2-252 GEN
Solar/Wind Harmer
2.799
958821AF2-173 GEN
Solar/Wind Harmer
11.29
24728705AND G3
Adder
7.997
270102X2-052 ST
50/50
2.279
970627AG2-408 GEN
Solar/Wind Harmer
3.095
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270216AD2-079_GEN
Solar/Wind Harmer
0.002
961051AF2-396 GEN
Solar/Wind Harmer
19.83
961051AF2-396 GEN
Solar/Wind Harmer
13.22
274803UNIV PARK;6U
Adder
7.866
274887GEN-1.85
Solar/Wind Harmer
0.248
274674JOLIET 9 ;6U
Adder
20.555
960971AF2-388 GEN
Solar/Wind Harmer
5.442
958481AF2-142 GEN
Solar/Wind Harmer
13.715
274693ROCKY RD ;1P
Adder
14.442
274862TOP CROP ;2U
Solar/Wind Harmer
1.237
274683WAUKEGAN ;8U
Adder
27.535
274683WAUKEGAN ;8U
Adder
23.211
970921AG2-575 GEN
Solar/Wind Harmer
9.059
970921AG2-575 GEN
Solar/Wind Harmer
3.02
274879MINONK ;1U
Solar/Wind Harmer
0.38
971335AH1-147 GEN
Solar/Wind Harmer
17.91
962761AG1-125 GEN
Solar/Wind Harmer
109.549
970245AG2-165 GEN
Solar/Wind Harmer
4.403
270063AE2-323 C
Solar/Wind Harmer
0.008
270462AD2-086
Solar/Wind Harmer
0.02
274754CRETE EC ;4U
Adder
11.24
944231AF1-091 GEN
Solar/Wind Harmer
2.492
274674JOLIET 9 ;6U
Adder
20.555
274732ELWOOD EC;7P
Adder
21.93
958381AF2-132 GEN
Solar/Wind Harmer
0.001
962781AG1-127 GEN
Solar/Wind Harmer
8.621
939401AE1-172 GEN
Solar/Wind Harmer
6.775
24721805FLATG3
50/50
4.694
24721705FLATG2
50/50
86.059
270143AC1-141 CT2_
50/50
3.444
24639705ELKHART HY
50/50
0.234
970521AG2-332 GEN
50/50
16.668
970155AG2-107 GEN
Solar/Wind Harmer
69.955
270349AD2-093_GEN
Solar/Wind Harmer
0.009
270449AD2-020 GEN
Solar/Wind Harmer
0.001
247521TR3_G114
Solar/Wind Harmer
0.349
270246TR4_N_V150
Solar/Wind Harmer
0.062
276164X3-005 C
Solar/Wind Harmer
0
965421AG1-410 GEN
Solar/Wind Harmer
28.417
274812UNIV PK N;8U
Adder
6.792
24695305TIMB G C
Solar/Wind Harmer
0.002
276776AD2-060 GEN
Solar/Wind Harmer
0.981
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
972235AH1-702 GEN1
Adder
3.201
274857EASY ROAD;U1
Solar/Wind Harmer
0.002
24643105BUCHANAN
50/50
0.018
270036AE2-216 BAT
50/50
8.975
270287AF1-227 GEN3
Solar/Wind Harmer
0.006
971347AH1-153 GEN
Solar/Wind Harmer
15.658
971619AH1-309 GEN
Solar/Wind Harmer
4.486
270317AD1-130_GEN
Solar/Wind Harmer
0.014
274775LINCOLN ;6U
Adder
11.607
274777LINCOLN ;8U
Adder
11.607
965051AG1-369 GEN
Solar/Wind Harmer
4.783
972037AH1-567 GEN1
Adder
0.247
960591AF2-350 GEN
Solar/Wind Harmer
9.401
274675JOLIET 29;7U
Adder
41.022
274675JOLIET 29;7U
Adder
39.557
970833AG2-524 GEN
Solar/Wind Harmer
10.224
970833AG2-524 GEN
Solar/Wind Harmer
6.816
276868AE1-113 GEN
Solar/Wind Harmer
1.807
971411AH1-196 GEN
Solar/Wind Harmer
13.442
971675AH1-338 GEN
Solar/Wind Harmer
3.495
971611AH1-305 GEN
Solar/Wind Harmer
5.332
971171AH1-044 GEN
Solar/Wind Harmer
17.815
274823ROCKFORD ;21
Adder
24.797
945581AF1-223 GEN
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.002
270181AB1-006 GEN2
Solar/Wind Harmer
0
276656WTG2_EQ
Solar/Wind Harmer
0
941731AE2-173 GEN
Solar/Wind Harmer
7.108
946321AF1-296 GEN
Solar/Wind Harmer
4.721
24386405FR-21G C
Solar/Wind Harmer
0.001
24725505WLD G2 C
Solar/Wind Harmer
0.001
944961AF1-161 GEN
50/50
4.122
270043AE2-236 GEN
Solar/Wind Harmer
6.761
965021AG1-366 GEN
Solar/Wind Harmer
3.439
945111AF1-176 GEN
Solar/Wind Harmer
8.066
270485AE1-090_GEN
Solar/Wind Harmer
0.001
24441205WTRV SLR C
Solar/Wind Harmer
0
274772LINCOLN ;3U
Adder
11.607
274724RIVER EC ;11
Adder
24.177
274802UNIV PARK;5U
Adder
7.866
970941AG2-585 GEN
Solar/Wind Harmer
11.751
274800UNIV PARK;3U
Adder
7.856
276897AD1-100 C
Solar/Wind Harmer
0.012
274729ELWOOD EC;1P
Adder
21.93
276893AG1-478 C
Solar/Wind Harmer
0.369
276805AD2-038 GEN
Solar/Wind Harmer
0.003
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
0.956
274850MENDOTA H;RU
Solar/Wind Harmer
0.106
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.161
276889AE2-281 GEN
Solar/Wind Harmer
0.001
970571AG2-364 GEN
Solar/Wind Harmer
17.623
274858EASY ROAD;U2
Solar/Wind Harmer
0.002
276157O29GEN1
Solar/Wind Harmer
1.397
942111AE2-223 GEN
Solar/Wind Harmer
2.772
971993AH1-541 GEN
Solar/Wind Harmer
3.686
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
971599AH1-298 GEN
50/50
14.063
24653605MOTTVILLE
50/50
0.005
270071AF1-092 GEN
Solar/Wind Harmer
19.582
971771AH1-392 GEN
Solar/Wind Harmer
10.018
971769AH1-391 GEN
Solar/Wind Harmer
11.066
24729505KEY G4
Adder
9.092
270435AC2-044 GEN
Solar/Wind Harmer
1.189
274728ELWOOD EC;5P
Adder
21.93
971549AH1-272 GEN
Solar/Wind Harmer
19.16
971177AH1-047 GEN
Solar/Wind Harmer
5.547
247607V1-011 GEN
Solar/Wind Harmer
0.001
274863CRW1-WTG
Solar/Wind Harmer
0.003
274864CRW2-WTG
Solar/Wind Harmer
0.003
276612AE2-035 GEN
Solar/Wind Harmer
0.002
971681AH1-341 GEN
Solar/Wind Harmer
14.125
957751AF2-069 GEN
Solar/Wind Harmer
0.285
24691005MDL-2G C
Solar/Wind Harmer
0.002
970615AG2-402 GEN
50/50
3.439
270100X2-052 CT1
50/50
2.1
970611AG2-400 GEN
Solar/Wind Harmer
10.316
970321AG2-212 GEN
Solar/Wind Harmer
4.403
957891AF2-083 GEN
Solar/Wind Harmer
0.001
274770LINCOLN ;1U
Adder
11.607
274771LINCOLN ;2U
Adder
11.607
274808UNIV PK N;4U
Adder
6.763
274888KELLY CRK;1U
Solar/Wind Harmer
0.552
972259AH1-714 GEN
Adder
25.697
246938BC-WTG3
Solar/Wind Harmer
0.34
246937BC-WTG2
Solar/Wind Harmer
0.381
274696ROCKY RD ;4P
Adder
14.93
274697ROCKY RD ;3P
Adder
3.962
962691AG1-118 GEN
Solar/Wind Harmer
27.238
942221AE2-234 GEN
Solar/Wind Harmer
0.045
270007AE1-245 C
Solar/Wind Harmer
0.002
970623AG2-406 GEN
Solar/Wind Harmer
1.621
274856ECOGROVE ;U1
Solar/Wind Harmer
0.208
276611AD2-172 GEN
Solar/Wind Harmer
0.002
938861AE1-114 GEN
Solar/Wind Harmer
4.97
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
274762LEE CO EC;3U
Adder
11.654
276603SUBLETTE C
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.339
970241AG2-163 GEN
Solar/Wind Harmer
4.643
970825AG2-519 GEN
Solar/Wind Harmer
8.815
970621AG2-405 GEN
Solar/Wind Harmer
1.453
274814UNIV PK N;0U
Adder
6.852
274807UNIV PK N;3U
Adder
6.837
274805UNIV PK N;1U
Adder
6.807
274687WILL CNTY;4U
Adder
37.406
274687WILL CNTY;4U
Adder
37.406
274731ELWOOD EC;2P
Adder
21.93
274733ELWOOD EC;3P
Adder
21.93
274746AC1-111 G10
Adder
7.401
965101AG1-375 GEN
Solar/Wind Harmer
9.112
276882AE2-255 GEN
Solar/Wind Harmer
1.053
926823AC1-168 GEN
Solar/Wind Harmer
1.498
24690905MDL-1G C
Solar/Wind Harmer
0.003
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
276655WTG1_EQ
Solar/Wind Harmer
0.003
971609AH1-304 GEN
Solar/Wind Harmer
1.376
24386205FR-12G C
Solar/Wind Harmer
0.001
963841AG1-237 GEN
Solar/Wind Harmer
3.53
970115AG2-085 GEN
Solar/Wind Harmer
3.191
270297AD1-101 GEN
Solar/Wind Harmer
0.002
24699105WLD G1 C
Solar/Wind Harmer
0.001
962771AG1-126 GEN
Solar/Wind Harmer
109.549
270284AF1-227 GEN1
Solar/Wind Harmer
0.015
270302AB2-170 GEN
Solar/Wind Harmer
0.006
971653AH1-327 GEN
Solar/Wind Harmer
1.377
274811UNIV PK N;7U
Adder
6.792
274827FISK ;RP
Adder
10.465
972227AH1-698 GEN1
Adder
3.512
957201AF2-014 GEN
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
12.652
270536AF1-215 GEN2
Solar/Wind Harmer
0.012
274735ELWOOD EC;4P
Adder
21.93
274744AC1-111 GEN8
Adder
7.401
958391AF2-133 GEN
Solar/Wind Harmer
0.001
970169AG2-114 GEN
Solar/Wind Harmer
8.81
961011AF2-392 GEN
Solar/Wind Harmer
5.094
274848CAMPGROVE;RU
Solar/Wind Harmer
0.002
959341AF2-225 GEN
Solar/Wind Harmer
8.957
270024AE2-089 GEN
Solar/Wind Harmer
0.009
970289AG2-191 GEN
Solar/Wind Harmer
1.575
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.291
276848AB2-070 GEN3
Solar/Wind Harmer
0.29
24722005FLATG5
50/50
4.694
24721905FLATG4
50/50
86.059
270142AC1-141 CT1_
50/50
3.444
970153AG2-106 GEN
Solar/Wind Harmer
69.955
247643Z2-116 C
Solar/Wind Harmer
0
276806AD2-047 C O1
Solar/Wind Harmer
5.327
274676JOLIET 29;8U
Adder
39.557
270535AF1-215 GEN1
Solar/Wind Harmer
0.012
274734ELWOOD EC;8P
Adder
21.93
274736ELWOOD EC;9P
Adder
21.93
943121AE2-341 GEN
Solar/Wind Harmer
15.511
943591AF1-030 GEN
Solar/Wind Harmer
10.315
274682WAUKEGAN ;7U
Adder
23.511
959091AF2-200 GEN
Solar/Wind Harmer
17.815
274767LEE CO EC;8U
Adder
11.517
24755605MDL-5G
Solar/Wind Harmer
0.001
247642Z2-115 C
Solar/Wind Harmer
0.004
970289AG2-191 GEN
Solar/Wind Harmer
0.912
970291AG2-192 GEN
Solar/Wind Harmer
0.829
276668AB2-070 GEN1
Solar/Wind Harmer
0.291
946031AF1-268 GEN
Solar/Wind Harmer
7.527
24728505AND G1
Adder
3.824
24307105BERRINSP G
50/50
0.031
965011AG1-365 GEN
Solar/Wind Harmer
10.316
270505AE1-170 C O1
Solar/Wind Harmer
10.468
945111AF1-176 GEN
Solar/Wind Harmer
17.757
274773LINCOLN ;4U
Adder
11.607
274774LINCOLN ;5U
Adder
11.607
274723RIVER EC ;12
Adder
24.46
274751CRETE EC ;1U
Adder
11.24
274801UNIV PARK;4U
Adder
7.856
246936BC-WTG1
Solar/Wind Harmer
0.381
270489AE1-102 GEN1
Solar/Wind Harmer
1.22
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
958861AF2-177 GEN
Solar/Wind Harmer
3.948
971997AH1-543 GEN
Solar/Wind Harmer
4.718
276861AD2-134 GEN
Solar/Wind Harmer
0.161
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
11.195
970569AG2-363 GEN
Solar/Wind Harmer
26.435
945371AF1-202 GEN
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
11.654
276158O29GEN2
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
11.942
24387305FR-4G C
Solar/Wind Harmer
0.003
270032AE2-172
Solar/Wind Harmer
5.467
972175AH1-670 GEN
Solar/Wind Harmer
6.757
270005AE1-210 C O1
Solar/Wind Harmer
1.747
274880W4-005 GEN4
Solar/Wind Harmer
0.001
970825AG2-519 GEN
Solar/Wind Harmer
2.823
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
270594AE1-207 GEN
Solar/Wind Harmer
9.184
276174W4-005 GEN2
Solar/Wind Harmer
0.001
24344105CKG2
50/50
11.607
970149AG2-104 GEN
Solar/Wind Harmer
118.317
270223U2-072_GEN1
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
5.164
970373AG2-245 GEN
Solar/Wind Harmer
19.935
941551AE2-152 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
11.896
276691AA1-018 GEN1
Solar/Wind Harmer
1.108
274872LEEDK;1U
Solar/Wind Harmer
0.006
959081AF2-199 GEN
Solar/Wind Harmer
8.908
971067AG2-660 GEN
Solar/Wind Harmer
2.969
274822ROCKFORD ;11
Adder
24.978
970819AG2-516 GEN
Solar/Wind Harmer
10.6
971475AH1-234 GEN
Solar/Wind Harmer
4.275
24791305MDL-5G
Solar/Wind Harmer
0.001
276726Z2-087_GEN
Solar/Wind Harmer
0.003
274854TWINGROVE;U2
Solar/Wind Harmer
0.004
963741AG1-226 GEN
Solar/Wind Harmer
18.836
274676JOLIET 29;8U
Adder
41.022
270055AF2-134 C O1
Solar/Wind Harmer
0.007
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
965651AG1-433 GEN
Solar/Wind Harmer
2.721
274745AC1-111 GEN9
Adder
7.401
274682WAUKEGAN ;7U
Adder
23.511
274828WAUKEGAN ;BP
Adder
14.433
276901AD2-066 C O1
Solar/Wind Harmer
0.009
957471AF2-041 GEN
Solar/Wind Harmer
26.723
274877BISHOP HL;1U
Solar/Wind Harmer
0.289
970291AG2-192 GEN
Solar/Wind Harmer
1.078
965031AG1-367 GEN
Solar/Wind Harmer
8.064
24728605AND G2
Adder
3.824
274766LEE CO EC;7U
Adder
11.517
24385905FR-11G C
Solar/Wind Harmer
0.002
276903AD2-071 C
Solar/Wind Harmer
8.911
963831AG1-236 GEN
Solar/Wind Harmer
3.095
276615X2-022 GEN
Solar/Wind Harmer
0.082
965911AG1-460 GEN
Solar/Wind Harmer
1.521
247536S-71 GEN
Solar/Wind Harmer
0.305
274764LEE CO EC;5U
Adder
11.682
972267AH1-718 GEN
Adder
5.169
276708O09 GEN2
Solar/Wind Harmer
0.308
276782AC1-033 GEN
Solar/Wind Harmer
0.001
270599AE1-208 GEN
Solar/Wind Harmer
7.723
960611AF2-352 GEN
Solar/Wind Harmer
2.799
966841AG1-555 GEN
Solar/Wind Harmer
0.944
270471AD2-092_GEN
Solar/Wind Harmer
0.009
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
965681AG1-436 GEN
Solar/Wind Harmer
12.351
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
971341AH1-150 GEN
Solar/Wind Harmer
17.815
971343AH1-151 GEN
Solar/Wind Harmer
17.815
276741O09 GEN1
Solar/Wind Harmer
0.308
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
971613AH1-306 GEN
Solar/Wind Harmer
3.936
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
247621Y3-024
Adder
0.268
276916AD2-100_GEN
Solar/Wind Harmer
12.804
957741AF2-068 GEN
Solar/Wind Harmer
11.901
276621W2-048 GEN
Solar/Wind Harmer
0.396
276838X2-022 GEN2
Solar/Wind Harmer
0.442
942481AE2-261 GEN
Solar/Wind Harmer
22.745
270475AD2-096_GEN
50/50
10.488
24642205MAYFLWER
50/50
0.961
962601AG1-109 GEN
50/50
4.122
959331AF2-224 GEN
Solar/Wind Harmer
7.221
270191TR4_S_V150
Solar/Wind Harmer
0.001
274753CRETE EC ;3U
Adder
11.24
972038AH1-567 GEN2
Adder
0.492
270491AE1-102 GEN2
Solar/Wind Harmer
1.22
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274872LEEDK;1U
Solar/Wind Harmer
0.331
972236AH1-702 GEN2
Adder
2.783
270258AD1-119 GEN
Solar/Wind Harmer
0.002
274760LEE CO EC;1U
Adder
11.654
274878BISHOP HL;2U
Solar/Wind Harmer
0.289
971617AH1-308 GEN
Solar/Wind Harmer
7.081
965091AG1-374 GEN
Solar/Wind Harmer
25.189
965931AG1-462 GEN
Solar/Wind Harmer
21.385
270004AE1-209 GEN
Solar/Wind Harmer
1.747
276686W4-005 GEN3
Solar/Wind Harmer
0.001
944201AF1-088_MTX
Adder
80.786
NYPJM->LTFIMP_NY
CLTF
3.072
LGEELTFEXP_LGEE->PJM
CLTF
4.553
WECLTFEXP_WEC->PJM
CLTF
4.843
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.157
AG2-052LTFEXP_AG2-052->PJM
LTF
0.305
AH1-155LTFEXP_AH1-155->PJM
LTF
0.457
CBM West 1LTFEXP_CBM-W1->PJM
CBM
159.327
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.302
MECLTFEXP_MEC->PJM
CLTF
18.121
SIGELTFEXP_SIGE->PJM
CLTF
0.416
LAGNLTFEXP_LAGN->PJM
CLTF
11.481
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.982
TVALTFEXP_TVA->PJM
CLTF
4.813
CBM West 2LTFEXP_CBM-W2->PJM
CBM
98.823

Details for 05MALIS-05VASSEL 765.0 kV Ckt 1 line l/o AEP_P1-2_#708_11_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MALIS-05VASSEL 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#708_11_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.34 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4570.1
MW Contribution:0.92
Bus #Bus NameTypeMW Contribution
24722005FLATG5
50/50
1.744
24721905FLATG4
50/50
31.976
970153AG2-106 GEN
Solar/Wind Harmer
48.313
247643Z2-116 C
Solar/Wind Harmer
0
276806AD2-047 C O1
Solar/Wind Harmer
4.44
274676JOLIET 29;8U
Adder
33.037
274734ELWOOD EC;8P
Adder
18.324
274736ELWOOD EC;9P
Adder
18.324
971599AH1-298 GEN
50/50
11.197
270071AF1-092 GEN
Solar/Wind Harmer
15.806
971771AH1-392 GEN
Solar/Wind Harmer
8.114
971769AH1-391 GEN
Solar/Wind Harmer
9.011
24729505KEY G4
Adder
7.347
274728ELWOOD EC;5P
Adder
18.324
971177AH1-047 GEN
Solar/Wind Harmer
4.675
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
276612AE2-035 GEN
Solar/Wind Harmer
0.002
971681AH1-341 GEN
Solar/Wind Harmer
11.977
957751AF2-069 GEN
Solar/Wind Harmer
0.242
971549AH1-272 GEN
Solar/Wind Harmer
15.144
24691005MDL-2G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
0.881
276174W4-005 GEN2
Solar/Wind Harmer
0.001
270594AE1-207 GEN
Solar/Wind Harmer
7.657
247607V1-011 GEN
Solar/Wind Harmer
0.001
24318705GVG2
50/50
5.86
965011AG1-365 GEN
Solar/Wind Harmer
8.034
270505AE1-170 C O1
Solar/Wind Harmer
8.434
945111AF1-176 GEN
Solar/Wind Harmer
14.294
274773LINCOLN ;4U
Adder
9.647
24721605FLATG1
50/50
1.744
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
274776LINCOLN ;7U
Adder
9.647
274814UNIV PK N;0U
Adder
5.695
274807UNIV PK N;3U
Adder
5.682
274805UNIV PK N;1U
Adder
5.657
274687WILL CNTY;4U
Adder
31.227
274687WILL CNTY;4U
Adder
31.227
274731ELWOOD EC;2P
Adder
18.323
274733ELWOOD EC;3P
Adder
18.323
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
274746AC1-111 G10
Adder
6.199
276882AE2-255 GEN
Solar/Wind Harmer
0.887
965041AG1-368 GEN
Solar/Wind Harmer
7.485
926823AC1-168 GEN
Solar/Wind Harmer
1.268
965101AG1-375 GEN
Solar/Wind Harmer
7.427
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
276655WTG1_EQ
Solar/Wind Harmer
0.003
24386205FR-12G C
Solar/Wind Harmer
0.001
963841AG1-237 GEN
Solar/Wind Harmer
3.033
971609AH1-304 GEN
Solar/Wind Harmer
1.131
270578AF1-285 GEN2
Solar/Wind Harmer
0.457
970115AG2-085 GEN
Solar/Wind Harmer
2.642
24699105WLD G1 C
Solar/Wind Harmer
0.001
944221AF1-090 GEN
Solar/Wind Harmer
3.817
943121AE2-341 GEN
Solar/Wind Harmer
12.991
943591AF1-030 GEN
Solar/Wind Harmer
8.639
270535AF1-215 GEN1
Solar/Wind Harmer
0.01
274682WAUKEGAN ;7U
Adder
19.745
959091AF2-200 GEN
Solar/Wind Harmer
15.051
274767LEE CO EC;8U
Adder
9.775
24755605MDL-5G
Solar/Wind Harmer
0.001
247642Z2-115 C
Solar/Wind Harmer
0.003
962771AG1-126 GEN
Solar/Wind Harmer
75.658
274811UNIV PK N;7U
Adder
5.645
274827FISK ;RP
Adder
8.717
972227AH1-698 GEN1
Adder
2.928
274735ELWOOD EC;4P
Adder
18.323
270284AF1-227 GEN1
Solar/Wind Harmer
0.01
270536AF1-215 GEN2
Solar/Wind Harmer
0.01
274744AC1-111 GEN8
Adder
6.199
958391AF2-133 GEN
Solar/Wind Harmer
0.001
970169AG2-114 GEN
Solar/Wind Harmer
7.456
963791AG1-232 GEN
Solar/Wind Harmer
9.982
961011AF2-392 GEN
Solar/Wind Harmer
4.33
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
959341AF2-225 GEN
Solar/Wind Harmer
7.635
957201AF2-014 GEN
Solar/Wind Harmer
0.001
970289AG2-191 GEN
Solar/Wind Harmer
1.316
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.252
276848AB2-070 GEN3
Solar/Wind Harmer
0.251
270024AE2-089 GEN
Solar/Wind Harmer
0.007
270302AB2-170 GEN
Solar/Wind Harmer
0.004
971653AH1-327 GEN
Solar/Wind Harmer
0.924
971347AH1-153 GEN
Solar/Wind Harmer
12.731
971619AH1-309 GEN
Solar/Wind Harmer
3.615
274775LINCOLN ;6U
Adder
9.647
274777LINCOLN ;8U
Adder
9.647
972037AH1-567 GEN1
Adder
0.206
960591AF2-350 GEN
Solar/Wind Harmer
7.835
274675JOLIET 29;7U
Adder
34.261
274675JOLIET 29;7U
Adder
33.037
970833AG2-524 GEN
Solar/Wind Harmer
8.549
970833AG2-524 GEN
Solar/Wind Harmer
5.699
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
276868AE1-113 GEN
Solar/Wind Harmer
1.521
971675AH1-338 GEN
Solar/Wind Harmer
2.948
971411AH1-196 GEN
Solar/Wind Harmer
11.34
971171AH1-044 GEN
Solar/Wind Harmer
15.051
971611AH1-305 GEN
Solar/Wind Harmer
4.479
274823ROCKFORD ;21
Adder
20.965
24697605MDL-3G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
965051AG1-369 GEN
Solar/Wind Harmer
3.646
276656WTG2_EQ
Solar/Wind Harmer
0
941731AE2-173 GEN
Solar/Wind Harmer
6.06
946321AF1-296 GEN
Solar/Wind Harmer
4.042
945581AF1-223 GEN
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24725505WLD G2 C
Solar/Wind Harmer
0.001
270317AD1-130_GEN
Solar/Wind Harmer
0.009
962761AG1-125 GEN
Solar/Wind Harmer
75.658
970245AG2-165 GEN
Solar/Wind Harmer
3.647
270063AE2-323 C
Solar/Wind Harmer
0.007
274754CRETE EC ;4U
Adder
9.321
274674JOLIET 9 ;6U
Adder
17.174
274732ELWOOD EC;7P
Adder
18.324
958381AF2-132 GEN
Solar/Wind Harmer
0.001
962781AG1-127 GEN
Solar/Wind Harmer
7.255
939401AE1-172 GEN
Solar/Wind Harmer
5.697
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
972235AH1-702 GEN1
Adder
2.708
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274766LEE CO EC;7U
Adder
9.775
944231AF1-091 GEN
Solar/Wind Harmer
1.917
24385905FR-11G C
Solar/Wind Harmer
0.002
963831AG1-236 GEN
Solar/Wind Harmer
2.685
276615X2-022 GEN
Solar/Wind Harmer
0.072
276903AD2-071 C
Solar/Wind Harmer
7.475
965911AG1-460 GEN
Solar/Wind Harmer
1.335
270462AD2-086
Solar/Wind Harmer
0.014
24721805FLATG3
50/50
1.744
24721705FLATG2
50/50
31.976
243186AF1-051 GEN
50/50
6.296
970155AG2-107 GEN
Solar/Wind Harmer
48.313
270349AD2-093_GEN
Solar/Wind Harmer
0.006
24639705ELKHART HY
Adder
0.177
270449AD2-020 GEN
Solar/Wind Harmer
0.001
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
5.645
276776AD2-060 GEN
Solar/Wind Harmer
0.818
274676JOLIET 29;8U
Adder
34.26
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0.006
274745AC1-111 GEN9
Adder
6.199
274682WAUKEGAN ;7U
Adder
19.745
274828WAUKEGAN ;BP
Adder
12.125
276901AD2-066 C O1
Solar/Wind Harmer
0.008
965651AG1-433 GEN
Solar/Wind Harmer
2.213
957471AF2-041 GEN
Solar/Wind Harmer
22.577
274877BISHOP HL;1U
Solar/Wind Harmer
0.246
247521TR3_G114
Solar/Wind Harmer
0.266
270246TR4_N_V150
Solar/Wind Harmer
0.047
24695305TIMB G C
Solar/Wind Harmer
0.002
965421AG1-410 GEN
Solar/Wind Harmer
21.166
970291AG2-192 GEN
Solar/Wind Harmer
0.9
965031AG1-367 GEN
Solar/Wind Harmer
6.68
24728605AND G2
Adder
3.309
274774LINCOLN ;5U
Adder
9.647
274723RIVER EC ;12
Adder
20.298
274751CRETE EC ;1U
Adder
9.321
274801UNIV PARK;4U
Adder
6.546
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971997AH1-543 GEN
Solar/Wind Harmer
3.975
276861AD2-134 GEN
Solar/Wind Harmer
0.136
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
9.405
970569AG2-363 GEN
Solar/Wind Harmer
22.374
958861AF2-177 GEN
Solar/Wind Harmer
3.218
274761LEE CO EC;2U
Adder
9.891
276158O29GEN2
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
10.18
945371AF1-202 GEN
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.003
972175AH1-670 GEN
Solar/Wind Harmer
5.82
246936BC-WTG1
Solar/Wind Harmer
0.282
270489AE1-102 GEN1
Solar/Wind Harmer
0.904
274880W4-005 GEN4
Solar/Wind Harmer
0.001
270032AE2-172
Solar/Wind Harmer
4.558
270005AE1-210 C O1
Solar/Wind Harmer
1.447
970825AG2-519 GEN
Solar/Wind Harmer
2.337
970321AG2-212 GEN
Solar/Wind Harmer
3.647
970611AG2-400 GEN
Solar/Wind Harmer
8.034
957891AF2-083 GEN
Solar/Wind Harmer
0.001
274770LINCOLN ;1U
Adder
9.647
274771LINCOLN ;2U
Adder
9.647
274808UNIV PK N;4U
Adder
5.62
972259AH1-714 GEN
Adder
21.437
274888KELLY CRK;1U
Solar/Wind Harmer
0.46
274696ROCKY RD ;4P
Adder
12.536
274697ROCKY RD ;3P
Adder
3.327
962691AG1-118 GEN
Solar/Wind Harmer
22.909
274856ECOGROVE ;U1
Solar/Wind Harmer
0.176
276611AD2-172 GEN
Solar/Wind Harmer
0.002
938861AE1-114 GEN
Solar/Wind Harmer
4.214
274762LEE CO EC;3U
Adder
9.891
276603SUBLETTE C
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
276645AC1-214 GEN1
Solar/Wind Harmer
0.289
942221AE2-234 GEN
Solar/Wind Harmer
0.037
246938BC-WTG3
Solar/Wind Harmer
0.252
246937BC-WTG2
Solar/Wind Harmer
0.282
970241AG2-163 GEN
Solar/Wind Harmer
4.009
270007AE1-245 C
Solar/Wind Harmer
0.002
970623AG2-406 GEN
Solar/Wind Harmer
1.213
970825AG2-519 GEN
Solar/Wind Harmer
7.295
24318705GVG2
50/50
5.86
270043AE2-236 GEN
Solar/Wind Harmer
5.391
965021AG1-366 GEN
Solar/Wind Harmer
2.678
945111AF1-176 GEN
Solar/Wind Harmer
6.493
274772LINCOLN ;3U
Adder
9.647
274724RIVER EC ;11
Adder
20.063
274802UNIV PARK;5U
Adder
6.55
970941AG2-585 GEN
Solar/Wind Harmer
9.793
274800UNIV PARK;3U
Adder
6.546
24441205WTRV SLR C
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
0.01
274729ELWOOD EC;1P
Adder
18.323
276893AG1-478 C
Solar/Wind Harmer
0.308
276805AD2-038 GEN
Solar/Wind Harmer
0.002
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
0.807
274850MENDOTA H;RU
Solar/Wind Harmer
0.089
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.136
276889AE2-281 GEN
Solar/Wind Harmer
0.001
270216AD2-079_GEN
Solar/Wind Harmer
0.001
970627AG2-408 GEN
Solar/Wind Harmer
2.41
961051AF2-396 GEN
Solar/Wind Harmer
15.958
961051AF2-396 GEN
Solar/Wind Harmer
10.638
274803UNIV PARK;6U
Adder
6.55
274887GEN-1.85
Solar/Wind Harmer
0.206
274674JOLIET 9 ;6U
Adder
17.174
274693ROCKY RD ;1P
Adder
12.127
958481AF2-142 GEN
Solar/Wind Harmer
11.505
274862TOP CROP ;2U
Solar/Wind Harmer
1.037
274683WAUKEGAN ;8U
Adder
23.131
274683WAUKEGAN ;8U
Adder
19.498
970921AG2-575 GEN
Solar/Wind Harmer
7.623
970921AG2-575 GEN
Solar/Wind Harmer
2.541
274879MINONK ;1U
Solar/Wind Harmer
0.32
971335AH1-147 GEN
Solar/Wind Harmer
15.112
960971AF2-388 GEN
Solar/Wind Harmer
4.426
274764LEE CO EC;5U
Adder
9.914
972267AH1-718 GEN
Adder
4.397
276708O09 GEN2
Solar/Wind Harmer
0.262
276782AC1-033 GEN
Solar/Wind Harmer
0.001
960611AF2-352 GEN
Solar/Wind Harmer
2.395
966841AG1-555 GEN
Solar/Wind Harmer
0.807
270599AE1-208 GEN
Solar/Wind Harmer
6.348
270224U2-072_GEN2
Solar/Wind Harmer
0.001
945391AF1-204 GEN
Solar/Wind Harmer
0.768
970571AG2-364 GEN
Solar/Wind Harmer
14.916
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
276157O29GEN1
Solar/Wind Harmer
1.189
942111AE2-223 GEN
Solar/Wind Harmer
2.363
971993AH1-541 GEN
Solar/Wind Harmer
3.193
276621W2-048 GEN
Solar/Wind Harmer
0.344
276838X2-022 GEN2
Solar/Wind Harmer
0.385
942481AE2-261 GEN
Solar/Wind Harmer
19.953
270485AE1-090_GEN
Solar/Wind Harmer
0.001
970349AG2-230 GEN
Solar/Wind Harmer
12.731
970513AG2-328 GEN
Solar/Wind Harmer
3.647
970517AG2-330 GEN
Solar/Wind Harmer
21.88
944531AF1-118 GEN
Solar/Wind Harmer
35.992
970031AG2-029 GEN
Solar/Wind Harmer
5.217
274752CRETE EC ;2U
Adder
9.321
970707AG2-453 GEN
Solar/Wind Harmer
25.687
274826FISK ;BP
Adder
12.3
972228AH1-698 GEN2
Adder
4.158
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
274730ELWOOD EC;6P
Adder
18.324
247604X1-042
Adder
0.463
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
274855GSG-6 ;RU
Solar/Wind Harmer
0.277
970781AG2-491 GEN
Solar/Wind Harmer
7.314
270247TR4_N_V136
Solar/Wind Harmer
0.047
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
959611AF2-252 GEN
Solar/Wind Harmer
2.395
270391AF1-285 GEN3
Solar/Wind Harmer
0.457
958821AF2-173 GEN
Solar/Wind Harmer
9.351
270404AC1-167 GEN
Solar/Wind Harmer
0.003
24728705AND G3
Adder
6.92
24344105CKG2
50/50
9.432
970149AG2-104 GEN
Solar/Wind Harmer
81.713
943021AE2-325 GEN
Solar/Wind Harmer
4.155
970373AG2-245 GEN
Solar/Wind Harmer
16.486
941551AE2-152 GEN
Solar/Wind Harmer
0.001
276691AA1-018 GEN1
Solar/Wind Harmer
0.929
971917AH1-482 GEN
Solar/Wind Harmer
9.935
274872LEEDK;1U
Solar/Wind Harmer
0.005
959081AF2-199 GEN
Solar/Wind Harmer
7.526
971067AG2-660 GEN
Solar/Wind Harmer
2.509
274822ROCKFORD ;11
Adder
21.119
970819AG2-516 GEN
Solar/Wind Harmer
8.973
971475AH1-234 GEN
Solar/Wind Harmer
3.622
24791305MDL-5G
Solar/Wind Harmer
0.001
276726Z2-087_GEN
Solar/Wind Harmer
0.002
274854TWINGROVE;U2
Solar/Wind Harmer
0.003
963741AG1-226 GEN
Solar/Wind Harmer
16.266
270223U2-072_GEN1
Solar/Wind Harmer
0.001
965791AG1-447 GEN
Solar/Wind Harmer
7.415
270526AF1-158 GEN
Solar/Wind Harmer
0.01
24441505OLIV SLR
Solar/Wind Harmer
0
247620Y3-023
Adder
0.53
276843GEN-1.7
Solar/Wind Harmer
0.254
958011AF2-095 GEN
Solar/Wind Harmer
11.282
971573AH1-285 GEN
Solar/Wind Harmer
1.438
274695ROCKY RD ;2P
Adder
12.247
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
958491AF2-143 GEN
Solar/Wind Harmer
11.41
942991AE2-321 GEN
Solar/Wind Harmer
8.468
971333AH1-146 GEN
Solar/Wind Harmer
15.112
944541AF1-119 GEN
Solar/Wind Harmer
0.505
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
274765LEE CO EC;6U
Adder
9.914
274763LEE CO EC;4U
Adder
9.798
945421AF1-207 GEN
Solar/Wind Harmer
0.001
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
276646AC1-214 GEN2
Solar/Wind Harmer
0.289
270031AE2-169
Solar/Wind Harmer
3.809
276911AD2-131_GEN
Solar/Wind Harmer
0.918
960441AF2-335 GEN
Solar/Wind Harmer
6.605
270475AD2-096_GEN
50/50
6.951
24642205MAYFLWER
Adder
0.733
959331AF2-224 GEN
Solar/Wind Harmer
5.624
274753CRETE EC ;3U
Adder
9.321
972038AH1-567 GEN2
Adder
0.41
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274872LEEDK;1U
Solar/Wind Harmer
0.279
972236AH1-702 GEN2
Adder
2.355
274760LEE CO EC;1U
Adder
9.891
274878BISHOP HL;2U
Solar/Wind Harmer
0.246
270191TR4_S_V150
Solar/Wind Harmer
0.001
965931AG1-462 GEN
Solar/Wind Harmer
18.337
965091AG1-374 GEN
Solar/Wind Harmer
21.555
270491AE1-102 GEN2
Solar/Wind Harmer
0.904
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971617AH1-308 GEN
Solar/Wind Harmer
5.671
270004AE1-209 GEN
Solar/Wind Harmer
1.447
270258AD1-119 GEN
Solar/Wind Harmer
0.002
243186AF1-051 GEN
50/50
6.296
270471AD2-092_GEN
Solar/Wind Harmer
0.006
965681AG1-436 GEN
Solar/Wind Harmer
10.111
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
971341AH1-150 GEN
Solar/Wind Harmer
15.051
971343AH1-151 GEN
Solar/Wind Harmer
15.051
276741O09 GEN1
Solar/Wind Harmer
0.262
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
971613AH1-306 GEN
Solar/Wind Harmer
3.282
276916AD2-100_GEN
Solar/Wind Harmer
13.935
247621Y3-024
Adder
0.217
970289AG2-191 GEN
Solar/Wind Harmer
0.762
970291AG2-192 GEN
Solar/Wind Harmer
0.693
276668AB2-070 GEN1
Solar/Wind Harmer
0.252
946031AF1-268 GEN
Solar/Wind Harmer
6.2
24728505AND G1
Adder
3.309
NYPJM->LTFIMP_NY
CLTF
3.04
LGEELTFEXP_LGEE->PJM
CLTF
4.486
WECLTFEXP_WEC->PJM
CLTF
4.1
AG2-052LTFEXP_AG2-052->PJM
LTF
0.254
AH1-155LTFEXP_AH1-155->PJM
LTF
0.382
CBM West 1LTFEXP_CBM-W1->PJM
CBM
131.739
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.503
MECLTFEXP_MEC->PJM
CLTF
16.01
SIGELTFEXP_SIGE->PJM
CLTF
0.394
LAGNLTFEXP_LAGN->PJM
CLTF
12.804
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.945
TVALTFEXP_TVA->PJM
CLTF
5.874
CPLELTFEXP_CPLE->PJM
CLTF
1.704
CBM West 2LTFEXP_CBM-W2->PJM
CBM
98.437

Details for 05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line l/o AEP_P1-2_#706_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#706_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.18 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5310.77
MW Contribution:1.31
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
5.145
270144AC1-141 ST1_
50/50
3.152
270286AF1-227 GEN2
Solar/Wind Harmer
0.006
960681AF2-359 GEN
Solar/Wind Harmer
-0.002
274776LINCOLN ;7U
Adder
11.972
965041AG1-368 GEN
Solar/Wind Harmer
9.847
270578AF1-285 GEN2
Solar/Wind Harmer
0.651
274814UNIV PK N;0U
Adder
7.057
274807UNIV PK N;3U
Adder
7.042
274805UNIV PK N;1U
Adder
7.011
274687WILL CNTY;4U
Adder
38.503
274687WILL CNTY;4U
Adder
38.503
274731ELWOOD EC;2P
Adder
22.566
274733ELWOOD EC;3P
Adder
22.566
274746AC1-111 G10
Adder
7.614
276882AE2-255 GEN
Solar/Wind Harmer
1.081
965101AG1-375 GEN
Solar/Wind Harmer
9.202
926823AC1-168 GEN
Solar/Wind Harmer
1.535
24690905MDL-1G C
Solar/Wind Harmer
0.003
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
276655WTG1_EQ
Solar/Wind Harmer
0.003
24386205FR-12G C
Solar/Wind Harmer
0.001
971609AH1-304 GEN
Solar/Wind Harmer
1.375
963841AG1-237 GEN
Solar/Wind Harmer
3.575
970115AG2-085 GEN
Solar/Wind Harmer
3.159
24699105WLD G1 C
Solar/Wind Harmer
0.001
270297AD1-101 GEN
Solar/Wind Harmer
0.002
24344105CKG2
50/50
12.069
970149AG2-104 GEN
Solar/Wind Harmer
129.655
247620Y3-023
50/50
0.722
270101X2-052 CT2
50/50
2.169
270526AF1-158 GEN
Solar/Wind Harmer
0.013
24441505OLIV SLR
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
9.351
276843GEN-1.7
Solar/Wind Harmer
0.313
958011AF2-095 GEN
Solar/Wind Harmer
13.939
971573AH1-285 GEN
Solar/Wind Harmer
1.764
274695ROCKY RD ;2P
Adder
14.996
274861TOP CROP ;1U
Solar/Wind Harmer
0.003
944541AF1-119 GEN
Solar/Wind Harmer
0.629
958491AF2-143 GEN
Solar/Wind Harmer
13.931
942991AE2-321 GEN
Solar/Wind Harmer
10.32
971333AH1-146 GEN
Solar/Wind Harmer
18.389
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
274765LEE CO EC;6U
Adder
11.975
274763LEE CO EC;4U
Adder
11.834
945421AF1-207 GEN
Solar/Wind Harmer
0.001
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
276646AC1-214 GEN2
Solar/Wind Harmer
0.347
270031AE2-169
Solar/Wind Harmer
4.629
960441AF2-335 GEN
Solar/Wind Harmer
7.897
964611AG1-324 GEN
Solar/Wind Harmer
0.584
270201AC2-176 GEN
Solar/Wind Harmer
0.001
276911AD2-131_GEN
Solar/Wind Harmer
0.883
24643105BUCHANAN
50/50
0.019
270287AF1-227 GEN3
Solar/Wind Harmer
0.006
971347AH1-153 GEN
Solar/Wind Harmer
16.236
971619AH1-309 GEN
Solar/Wind Harmer
4.631
274775LINCOLN ;6U
Adder
11.972
274777LINCOLN ;8U
Adder
11.972
972037AH1-567 GEN1
Adder
0.254
960591AF2-350 GEN
Solar/Wind Harmer
9.68
965051AG1-369 GEN
Solar/Wind Harmer
4.807
274675JOLIET 29;7U
Adder
42.223
24641605TWIN BRNCH
50/50
0.026
24344005CKG1
50/50
9.691
247604X1-042
50/50
0.632
970349AG2-230 GEN
Solar/Wind Harmer
16.236
970513AG2-328 GEN
Solar/Wind Harmer
4.559
970517AG2-330 GEN
Solar/Wind Harmer
27.357
970031AG2-029 GEN
Solar/Wind Harmer
6.732
944531AF1-118 GEN
Solar/Wind Harmer
45.595
274752CRETE EC ;2U
Adder
11.58
270391AF1-285 GEN3
Solar/Wind Harmer
0.651
970707AG2-453 GEN
Solar/Wind Harmer
31.724
274826FISK ;BP
Adder
15.205
972228AH1-698 GEN2
Adder
5.135
270247TR4_N_V136
Solar/Wind Harmer
0.062
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
274730ELWOOD EC;6P
Adder
22.567
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
274855GSG-6 ;RU
Solar/Wind Harmer
0.337
970781AG2-491 GEN
Solar/Wind Harmer
8.785
270404AC1-167 GEN
Solar/Wind Harmer
0.004
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
959611AF2-252 GEN
Solar/Wind Harmer
2.854
958821AF2-173 GEN
Solar/Wind Harmer
11.2
24728705AND G3
Adder
7.82
270102X2-052 ST
50/50
2.354
970627AG2-408 GEN
Solar/Wind Harmer
3.161
270216AD2-079_GEN
Solar/Wind Harmer
0.002
961051AF2-396 GEN
Solar/Wind Harmer
20.46
961051AF2-396 GEN
Solar/Wind Harmer
13.64
270224U2-072_GEN2
Solar/Wind Harmer
0.001
274803UNIV PARK;6U
Adder
8.1
274887GEN-1.85
Solar/Wind Harmer
0.255
274674JOLIET 9 ;6U
Adder
21.154
958481AF2-142 GEN
Solar/Wind Harmer
14.096
274693ROCKY RD ;1P
Adder
14.848
274862TOP CROP ;2U
Solar/Wind Harmer
1.271
960971AF2-388 GEN
Solar/Wind Harmer
5.509
274683WAUKEGAN ;8U
Adder
28.303
274683WAUKEGAN ;8U
Adder
23.858
970921AG2-575 GEN
Solar/Wind Harmer
9.308
970921AG2-575 GEN
Solar/Wind Harmer
3.103
274879MINONK ;1U
Solar/Wind Harmer
0.39
971335AH1-147 GEN
Solar/Wind Harmer
18.389
274764LEE CO EC;5U
Adder
11.975
972267AH1-718 GEN
Adder
5.295
276708O09 GEN2
Solar/Wind Harmer
0.315
276782AC1-033 GEN
Solar/Wind Harmer
0.001
960611AF2-352 GEN
Solar/Wind Harmer
2.854
966841AG1-555 GEN
Solar/Wind Harmer
0.959
270599AE1-208 GEN
Solar/Wind Harmer
7.715
962761AG1-125 GEN
Solar/Wind Harmer
120.047
970245AG2-165 GEN
Solar/Wind Harmer
4.559
270063AE2-323 C
Solar/Wind Harmer
0.008
274754CRETE EC ;4U
Adder
11.58
274674JOLIET 9 ;6U
Adder
21.154
274732ELWOOD EC;7P
Adder
22.567
944231AF1-091 GEN
Solar/Wind Harmer
2.532
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270462AD2-086
Solar/Wind Harmer
0.02
962781AG1-127 GEN
Solar/Wind Harmer
8.858
939401AE1-172 GEN
Solar/Wind Harmer
6.954
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
972235AH1-702 GEN1
Adder
3.284
274857EASY ROAD;U1
Solar/Wind Harmer
0.002
274766LEE CO EC;7U
Adder
11.806
24385905FR-11G C
Solar/Wind Harmer
0.002
963831AG1-236 GEN
Solar/Wind Harmer
3.14
276615X2-022 GEN
Solar/Wind Harmer
0.084
276903AD2-071 C
Solar/Wind Harmer
8.872
965911AG1-460 GEN
Solar/Wind Harmer
1.538
24721805FLATG3
50/50
5.145
24721705FLATG2
50/50
94.33
270143AC1-141 CT2_
50/50
3.558
24639705ELKHART HY
50/50
0.241
970521AG2-332 GEN
50/50
17.184
970155AG2-107 GEN
Solar/Wind Harmer
76.659
270349AD2-093_GEN
Solar/Wind Harmer
0.009
270449AD2-020 GEN
Solar/Wind Harmer
0.001
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
6.996
276776AD2-060 GEN
Solar/Wind Harmer
1.011
247521TR3_G114
Solar/Wind Harmer
0.351
270246TR4_N_V150
Solar/Wind Harmer
0.062
274676JOLIET 29;8U
Adder
42.222
270055AF2-134 C O1
Solar/Wind Harmer
0.007
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
274745AC1-111 GEN9
Adder
7.614
24695305TIMB G C
Solar/Wind Harmer
0.002
965421AG1-410 GEN
Solar/Wind Harmer
28.36
965651AG1-433 GEN
Solar/Wind Harmer
2.755
274682WAUKEGAN ;7U
Adder
24.169
274828WAUKEGAN ;BP
Adder
14.836
276901AD2-066 C O1
Solar/Wind Harmer
0.009
957471AF2-041 GEN
Solar/Wind Harmer
27.428
274877BISHOP HL;1U
Solar/Wind Harmer
0.295
970291AG2-192 GEN
Solar/Wind Harmer
1.08
965031AG1-367 GEN
Solar/Wind Harmer
8
24728605AND G2
Adder
3.739
270471AD2-092_GEN
Solar/Wind Harmer
0.009
965681AG1-436 GEN
Solar/Wind Harmer
12.752
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
274675JOLIET 29;7U
Adder
40.715
970833AG2-524 GEN
Solar/Wind Harmer
10.52
970833AG2-524 GEN
Solar/Wind Harmer
7.013
270317AD1-130_GEN
Solar/Wind Harmer
0.013
276868AE1-113 GEN
Solar/Wind Harmer
1.855
971411AH1-196 GEN
Solar/Wind Harmer
13.802
971675AH1-338 GEN
Solar/Wind Harmer
3.588
971611AH1-305 GEN
Solar/Wind Harmer
5.454
971171AH1-044 GEN
Solar/Wind Harmer
18.285
274823ROCKFORD ;21
Adder
25.447
945581AF1-223 GEN
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.002
270181AB1-006 GEN2
Solar/Wind Harmer
0
276656WTG2_EQ
Solar/Wind Harmer
0
941731AE2-173 GEN
Solar/Wind Harmer
7.258
946321AF1-296 GEN
Solar/Wind Harmer
4.827
24386405FR-21G C
Solar/Wind Harmer
0.001
24725505WLD G2 C
Solar/Wind Harmer
0.001
944961AF1-161 GEN
50/50
4.253
270043AE2-236 GEN
Solar/Wind Harmer
6.969
965021AG1-366 GEN
Solar/Wind Harmer
3.512
945111AF1-176 GEN
Solar/Wind Harmer
8.323
24441205WTRV SLR C
Solar/Wind Harmer
0
274772LINCOLN ;3U
Adder
11.972
274724RIVER EC ;11
Adder
24.913
274802UNIV PARK;5U
Adder
8.1
274800UNIV PARK;3U
Adder
8.089
970941AG2-585 GEN
Solar/Wind Harmer
12.1
276897AD1-100 C
Solar/Wind Harmer
0.013
274729ELWOOD EC;1P
Adder
22.566
276893AG1-478 C
Solar/Wind Harmer
0.379
270485AE1-090_GEN
Solar/Wind Harmer
0.001
276805AD2-038 GEN
Solar/Wind Harmer
0.003
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
0.982
274850MENDOTA H;RU
Solar/Wind Harmer
0.108
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.165
276889AE2-281 GEN
Solar/Wind Harmer
0.001
970571AG2-364 GEN
Solar/Wind Harmer
18.064
274858EASY ROAD;U2
Solar/Wind Harmer
0.002
276157O29GEN1
Solar/Wind Harmer
1.431
942111AE2-223 GEN
Solar/Wind Harmer
2.831
971993AH1-541 GEN
Solar/Wind Harmer
3.74
276621W2-048 GEN
Solar/Wind Harmer
0.401
276838X2-022 GEN2
Solar/Wind Harmer
0.448
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
11.672
942481AE2-261 GEN
Solar/Wind Harmer
22.986
971599AH1-298 GEN
50/50
14.587
24653605MOTTVILLE
50/50
0.006
270071AF1-092 GEN
Solar/Wind Harmer
20.132
971771AH1-392 GEN
Solar/Wind Harmer
10.346
971769AH1-391 GEN
Solar/Wind Harmer
11.424
24729505KEY G4
Adder
9.267
274728ELWOOD EC;5P
Adder
22.567
971549AH1-272 GEN
Solar/Wind Harmer
19.681
270435AC2-044 GEN
Solar/Wind Harmer
1.183
971177AH1-047 GEN
Solar/Wind Harmer
5.697
274863CRW1-WTG
Solar/Wind Harmer
0.003
274864CRW2-WTG
Solar/Wind Harmer
0.003
276612AE2-035 GEN
Solar/Wind Harmer
0.002
971681AH1-341 GEN
Solar/Wind Harmer
14.483
247607V1-011 GEN
Solar/Wind Harmer
0.001
957751AF2-069 GEN
Solar/Wind Harmer
0.292
24691005MDL-2G C
Solar/Wind Harmer
0.002
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
270594AE1-207 GEN
Solar/Wind Harmer
9.172
276174W4-005 GEN2
Solar/Wind Harmer
0.001
970615AG2-402 GEN
50/50
3.512
270100X2-052 CT1
50/50
2.169
970611AG2-400 GEN
Solar/Wind Harmer
10.537
970321AG2-212 GEN
Solar/Wind Harmer
4.559
957891AF2-083 GEN
Solar/Wind Harmer
0.001
274770LINCOLN ;1U
Adder
11.972
274771LINCOLN ;2U
Adder
11.972
274808UNIV PK N;4U
Adder
6.965
274888KELLY CRK;1U
Solar/Wind Harmer
0.568
972259AH1-714 GEN
Adder
26.463
274697ROCKY RD ;3P
Adder
4.074
274696ROCKY RD ;4P
Adder
15.349
246938BC-WTG3
Solar/Wind Harmer
0.338
246937BC-WTG2
Solar/Wind Harmer
0.379
962691AG1-118 GEN
Solar/Wind Harmer
27.992
942221AE2-234 GEN
Solar/Wind Harmer
0.046
274856ECOGROVE ;U1
Solar/Wind Harmer
0.213
276611AD2-172 GEN
Solar/Wind Harmer
0.002
938861AE1-114 GEN
Solar/Wind Harmer
5.096
274762LEE CO EC;3U
Adder
11.947
276603SUBLETTE C
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
270007AE1-245 C
Solar/Wind Harmer
0.002
276645AC1-214 GEN1
Solar/Wind Harmer
0.347
970623AG2-406 GEN
Solar/Wind Harmer
1.614
970241AG2-163 GEN
Solar/Wind Harmer
4.69
970825AG2-519 GEN
Solar/Wind Harmer
8.719
970621AG2-405 GEN
Solar/Wind Harmer
1.413
24307105BERRINSP G
50/50
0.032
965011AG1-365 GEN
Solar/Wind Harmer
10.537
270505AE1-170 C O1
Solar/Wind Harmer
10.806
945111AF1-176 GEN
Solar/Wind Harmer
18.321
274773LINCOLN ;4U
Adder
11.972
274774LINCOLN ;5U
Adder
11.972
274723RIVER EC ;12
Adder
25.205
274751CRETE EC ;1U
Adder
11.58
274801UNIV PARK;4U
Adder
8.089
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
246936BC-WTG1
Solar/Wind Harmer
0.379
270489AE1-102 GEN1
Solar/Wind Harmer
1.214
971997AH1-543 GEN
Solar/Wind Harmer
4.843
958861AF2-177 GEN
Solar/Wind Harmer
3.987
276861AD2-134 GEN
Solar/Wind Harmer
0.165
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
11.452
970569AG2-363 GEN
Solar/Wind Harmer
27.095
274761LEE CO EC;2U
Adder
11.947
276158O29GEN2
Solar/Wind Harmer
0.001
945371AF1-202 GEN
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
12.194
24387305FR-4G C
Solar/Wind Harmer
0.003
972175AH1-670 GEN
Solar/Wind Harmer
6.873
270032AE2-172
Solar/Wind Harmer
5.46
274880W4-005 GEN4
Solar/Wind Harmer
0.001
270005AE1-210 C O1
Solar/Wind Harmer
1.733
962771AG1-126 GEN
Solar/Wind Harmer
120.047
270284AF1-227 GEN1
Solar/Wind Harmer
0.014
274811UNIV PK N;7U
Adder
6.996
274827FISK ;RP
Adder
10.776
972227AH1-698 GEN1
Adder
3.616
274735ELWOOD EC;4P
Adder
22.566
270536AF1-215 GEN2
Solar/Wind Harmer
0.012
274744AC1-111 GEN8
Adder
7.614
963791AG1-232 GEN
Solar/Wind Harmer
12.76
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270302AB2-170 GEN
Solar/Wind Harmer
0.006
971653AH1-327 GEN
Solar/Wind Harmer
1.314
958391AF2-133 GEN
Solar/Wind Harmer
0.001
970169AG2-114 GEN
Solar/Wind Harmer
9.023
961011AF2-392 GEN
Solar/Wind Harmer
5.219
274848CAMPGROVE;RU
Solar/Wind Harmer
0.002
959341AF2-225 GEN
Solar/Wind Harmer
9.145
270024AE2-089 GEN
Solar/Wind Harmer
0.009
970289AG2-191 GEN
Solar/Wind Harmer
1.578
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.295
276848AB2-070 GEN3
Solar/Wind Harmer
0.294
24722005FLATG5
50/50
5.145
24721905FLATG4
50/50
94.33
270142AC1-141 CT1_
50/50
3.558
970153AG2-106 GEN
Solar/Wind Harmer
76.659
247643Z2-116 C
Solar/Wind Harmer
0
276806AD2-047 C O1
Solar/Wind Harmer
5.485
274676JOLIET 29;8U
Adder
40.714
274734ELWOOD EC;8P
Adder
22.567
274736ELWOOD EC;9P
Adder
22.567
270535AF1-215 GEN1
Solar/Wind Harmer
0.012
943121AE2-341 GEN
Solar/Wind Harmer
15.96
943591AF1-030 GEN
Solar/Wind Harmer
10.614
274682WAUKEGAN ;7U
Adder
24.169
959091AF2-200 GEN
Solar/Wind Harmer
18.285
274767LEE CO EC;8U
Adder
11.806
24755605MDL-5G
Solar/Wind Harmer
0.001
247642Z2-115 C
Solar/Wind Harmer
0.004
970289AG2-191 GEN
Solar/Wind Harmer
0.914
970291AG2-192 GEN
Solar/Wind Harmer
0.831
276668AB2-070 GEN1
Solar/Wind Harmer
0.295
946031AF1-268 GEN
Solar/Wind Harmer
7.422
24728505AND G1
Adder
3.739
970825AG2-519 GEN
Solar/Wind Harmer
2.793
943021AE2-325 GEN
Solar/Wind Harmer
5.329
270223U2-072_GEN1
Solar/Wind Harmer
0.001
970373AG2-245 GEN
Solar/Wind Harmer
20.506
941551AE2-152 GEN
Solar/Wind Harmer
0.001
276691AA1-018 GEN1
Solar/Wind Harmer
1.138
971917AH1-482 GEN
Solar/Wind Harmer
12.195
274872LEEDK;1U
Solar/Wind Harmer
0.006
959081AF2-199 GEN
Solar/Wind Harmer
9.143
971067AG2-660 GEN
Solar/Wind Harmer
3.048
274822ROCKFORD ;11
Adder
25.633
970819AG2-516 GEN
Solar/Wind Harmer
10.874
971475AH1-234 GEN
Solar/Wind Harmer
4.385
24791305MDL-5G
Solar/Wind Harmer
0.001
276726Z2-087_GEN
Solar/Wind Harmer
0.003
274854TWINGROVE;U2
Solar/Wind Harmer
0.004
963741AG1-226 GEN
Solar/Wind Harmer
19.026
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
971341AH1-150 GEN
Solar/Wind Harmer
18.285
971343AH1-151 GEN
Solar/Wind Harmer
18.285
276741O09 GEN1
Solar/Wind Harmer
0.315
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
971613AH1-306 GEN
Solar/Wind Harmer
3.931
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
247621Y3-024
Adder
0.262
276916AD2-100_GEN
Solar/Wind Harmer
13.41
270475AD2-096_GEN
50/50
10.026
24642205MAYFLWER
50/50
0.992
962601AG1-109 GEN
50/50
4.253
959331AF2-224 GEN
Solar/Wind Harmer
7.376
274753CRETE EC ;3U
Adder
11.58
972038AH1-567 GEN2
Adder
0.506
270191TR4_S_V150
Solar/Wind Harmer
0.001
964401AG1-302 GEN
Solar/Wind Harmer
0.001
270491AE1-102 GEN2
Solar/Wind Harmer
1.214
274872LEEDK;1U
Solar/Wind Harmer
0.341
972236AH1-702 GEN2
Adder
2.856
274760LEE CO EC;1U
Adder
11.947
270258AD1-119 GEN
Solar/Wind Harmer
0.002
274878BISHOP HL;2U
Solar/Wind Harmer
0.295
965931AG1-462 GEN
Solar/Wind Harmer
21.861
965091AG1-374 GEN
Solar/Wind Harmer
25.685
971617AH1-308 GEN
Solar/Wind Harmer
7.03
276686W4-005 GEN3
Solar/Wind Harmer
0.001
270004AE1-209 GEN
Solar/Wind Harmer
1.733
944201AF1-088_MTX
Adder
85.667
NYPJM->LTFIMP_NY
CLTF
2.99
LGEELTFEXP_LGEE->PJM
CLTF
4.155
WECLTFEXP_WEC->PJM
CLTF
4.968
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.286
AG2-052LTFEXP_AG2-052->PJM
LTF
0.312
AH1-155LTFEXP_AH1-155->PJM
LTF
0.469
CBM West 1LTFEXP_CBM-W1->PJM
CBM
161.402
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.132
MECLTFEXP_MEC->PJM
CLTF
18.394
SIGELTFEXP_SIGE->PJM
CLTF
0.399
LAGNLTFEXP_LAGN->PJM
CLTF
11.144
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.328
TVALTFEXP_TVA->PJM
CLTF
4.56
CBM West 2LTFEXP_CBM-W2->PJM
CBM
96.989

Details for 05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line l/o AEP_P1-2_#728_584_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#728_584_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.32 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5088.24
MW Contribution:1.03
Bus #Bus NameTypeMW Contribution
270101X2-052 CT2
50/50
1.694
247620Y3-023
50/50
0.557
965791AG1-447 GEN
Solar/Wind Harmer
7.315
270526AF1-158 GEN
Solar/Wind Harmer
0.01
24441505OLIV SLR
Solar/Wind Harmer
0
276843GEN-1.7
Solar/Wind Harmer
0.249
958011AF2-095 GEN
Solar/Wind Harmer
11.061
971573AH1-285 GEN
Solar/Wind Harmer
1.407
274695ROCKY RD ;2P
Adder
11.974
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
958491AF2-143 GEN
Solar/Wind Harmer
11.137
942991AE2-321 GEN
Solar/Wind Harmer
8.265
971333AH1-146 GEN
Solar/Wind Harmer
14.742
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
944541AF1-119 GEN
Solar/Wind Harmer
0.485
274765LEE CO EC;6U
Adder
9.646
270144AC1-141 ST1_
50/50
2.435
270286AF1-227 GEN2
Solar/Wind Harmer
0.005
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
274776LINCOLN ;7U
Adder
9.481
270578AF1-285 GEN2
Solar/Wind Harmer
0.52
274814UNIV PK N;0U
Adder
5.588
274807UNIV PK N;3U
Adder
5.576
274805UNIV PK N;1U
Adder
5.552
274687WILL CNTY;4U
Adder
30.598
274687WILL CNTY;4U
Adder
30.598
274731ELWOOD EC;2P
Adder
17.946
274733ELWOOD EC;3P
Adder
17.946
274746AC1-111 G10
Adder
6.067
965041AG1-368 GEN
Solar/Wind Harmer
7.422
276882AE2-255 GEN
Solar/Wind Harmer
0.865
926823AC1-168 GEN
Solar/Wind Harmer
1.234
965101AG1-375 GEN
Solar/Wind Harmer
7.103
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
276655WTG1_EQ
Solar/Wind Harmer
0.003
24386205FR-12G C
Solar/Wind Harmer
0.001
963841AG1-237 GEN
Solar/Wind Harmer
2.903
270142AC1-141 CT1_
50/50
2.749
970153AG2-106 GEN
Solar/Wind Harmer
49.204
247643Z2-116 C
Solar/Wind Harmer
0
276806AD2-047 C O1
Solar/Wind Harmer
4.353
274676JOLIET 29;8U
Adder
32.367
274734ELWOOD EC;8P
Adder
17.946
274736ELWOOD EC;9P
Adder
17.946
943121AE2-341 GEN
Solar/Wind Harmer
12.717
943591AF1-030 GEN
Solar/Wind Harmer
8.457
270535AF1-215 GEN1
Solar/Wind Harmer
0.009
274682WAUKEGAN ;7U
Adder
19.302
959091AF2-200 GEN
Solar/Wind Harmer
14.674
274767LEE CO EC;8U
Adder
9.51
24755605MDL-5G
Solar/Wind Harmer
0.001
24721905FLATG4
Adder
20.046
247642Z2-115 C
Solar/Wind Harmer
0.003
276668AB2-070 GEN1
Solar/Wind Harmer
0.241
970289AG2-191 GEN
Solar/Wind Harmer
0.719
970291AG2-192 GEN
Solar/Wind Harmer
0.654
971599AH1-298 GEN
50/50
11.184
24653605MOTTVILLE
50/50
0.004
270071AF1-092 GEN
Solar/Wind Harmer
15.591
971771AH1-392 GEN
Solar/Wind Harmer
8.024
971769AH1-391 GEN
Solar/Wind Harmer
8.897
24729505KEY G4
Adder
7.133
274728ELWOOD EC;5P
Adder
17.946
971177AH1-047 GEN
Solar/Wind Harmer
4.563
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
276612AE2-035 GEN
Solar/Wind Harmer
0.002
971681AH1-341 GEN
Solar/Wind Harmer
11.658
971549AH1-272 GEN
Solar/Wind Harmer
14.911
957751AF2-069 GEN
Solar/Wind Harmer
0.235
24691005MDL-2G C
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
0.886
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
247607V1-011 GEN
Solar/Wind Harmer
0.001
270594AE1-207 GEN
Solar/Wind Harmer
7.194
965011AG1-365 GEN
Solar/Wind Harmer
8.015
270505AE1-170 C O1
Solar/Wind Harmer
8.343
945111AF1-176 GEN
Solar/Wind Harmer
14.138
274773LINCOLN ;4U
Adder
9.481
274774LINCOLN ;5U
Adder
9.481
274723RIVER EC ;12
Adder
19.934
274751CRETE EC ;1U
Adder
9.153
274801UNIV PARK;4U
Adder
6.418
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971997AH1-543 GEN
Solar/Wind Harmer
3.877
276861AD2-134 GEN
Solar/Wind Harmer
0.132
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
9.144
970569AG2-363 GEN
Solar/Wind Harmer
21.771
274761LEE CO EC;2U
Adder
9.624
276158O29GEN2
Solar/Wind Harmer
0.001
958861AF2-177 GEN
Solar/Wind Harmer
3.078
939741AE1-205 GEN
Solar/Wind Harmer
9.848
246936BC-WTG1
Solar/Wind Harmer
0.284
270489AE1-102 GEN1
Solar/Wind Harmer
0.91
24387305FR-4G C
Solar/Wind Harmer
0.003
945371AF1-202 GEN
Solar/Wind Harmer
0.001
972175AH1-670 GEN
Solar/Wind Harmer
5.597
274880W4-005 GEN4
Solar/Wind Harmer
0.001
270032AE2-172
Solar/Wind Harmer
4.282
270005AE1-210 C O1
Solar/Wind Harmer
1.345
970825AG2-519 GEN
Solar/Wind Harmer
2.164
971609AH1-304 GEN
Solar/Wind Harmer
1.065
944221AF1-090 GEN
Solar/Wind Harmer
3.617
24699105WLD G1 C
Solar/Wind Harmer
0.001
970115AG2-085 GEN
Solar/Wind Harmer
2.45
24344105CKG2
50/50
9.389
970149AG2-104 GEN
Solar/Wind Harmer
83.22
962771AG1-126 GEN
Solar/Wind Harmer
77.053
270284AF1-227 GEN1
Solar/Wind Harmer
0.012
274811UNIV PK N;7U
Adder
5.54
274827FISK ;RP
Adder
8.549
972227AH1-698 GEN1
Adder
2.87
274735ELWOOD EC;4P
Adder
17.946
270536AF1-215 GEN2
Solar/Wind Harmer
0.009
274744AC1-111 GEN8
Adder
6.067
958391AF2-133 GEN
Solar/Wind Harmer
0.001
270302AB2-170 GEN
Solar/Wind Harmer
0.004
971653AH1-327 GEN
Solar/Wind Harmer
1.033
970169AG2-114 GEN
Solar/Wind Harmer
7.246
963791AG1-232 GEN
Solar/Wind Harmer
9.7
961011AF2-392 GEN
Solar/Wind Harmer
4.21
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
959341AF2-225 GEN
Solar/Wind Harmer
7.386
957201AF2-014 GEN
Solar/Wind Harmer
0.001
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.241
276848AB2-070 GEN3
Solar/Wind Harmer
0.24
970289AG2-191 GEN
Solar/Wind Harmer
1.243
270024AE2-089 GEN
Solar/Wind Harmer
0.007
24643105BUCHANAN
50/50
0.015
270287AF1-227 GEN3
Solar/Wind Harmer
0.005
971347AH1-153 GEN
Solar/Wind Harmer
12.636
971619AH1-309 GEN
Solar/Wind Harmer
3.576
274775LINCOLN ;6U
Adder
9.481
274777LINCOLN ;8U
Adder
9.481
972037AH1-567 GEN1
Adder
0.202
960591AF2-350 GEN
Solar/Wind Harmer
7.682
274675JOLIET 29;7U
Adder
33.566
274675JOLIET 29;7U
Adder
32.367
970833AG2-524 GEN
Solar/Wind Harmer
8.371
970833AG2-524 GEN
Solar/Wind Harmer
5.581
276868AE1-113 GEN
Solar/Wind Harmer
1.484
971675AH1-338 GEN
Solar/Wind Harmer
2.876
971411AH1-196 GEN
Solar/Wind Harmer
11.063
270317AD1-130_GEN
Solar/Wind Harmer
0.01
971171AH1-044 GEN
Solar/Wind Harmer
14.674
274823ROCKFORD ;21
Adder
20.435
971611AH1-305 GEN
Solar/Wind Harmer
4.355
965051AG1-369 GEN
Solar/Wind Harmer
3.614
24697605MDL-3G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
276656WTG2_EQ
Solar/Wind Harmer
0
941731AE2-173 GEN
Solar/Wind Harmer
5.862
946321AF1-296 GEN
Solar/Wind Harmer
3.917
24386405FR-21G C
Solar/Wind Harmer
0.001
945581AF1-223 GEN
Solar/Wind Harmer
0.001
24725505WLD G2 C
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Helper
1.885
270520AE2-214 GEN
Solar/Wind Helper
4.768
962761AG1-125 GEN
Solar/Wind Harmer
77.053
970245AG2-165 GEN
Solar/Wind Harmer
3.603
270063AE2-323 C
Solar/Wind Harmer
0.007
274754CRETE EC ;4U
Adder
9.153
274674JOLIET 9 ;6U
Adder
16.822
274732ELWOOD EC;7P
Adder
17.946
958381AF2-132 GEN
Solar/Wind Harmer
0.001
962781AG1-127 GEN
Solar/Wind Harmer
7.086
939401AE1-172 GEN
Solar/Wind Harmer
5.557
270462AD2-086
Solar/Wind Harmer
0.015
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
972235AH1-702 GEN1
Adder
2.639
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274766LEE CO EC;7U
Adder
9.51
944231AF1-091 GEN
Solar/Wind Harmer
1.892
24385905FR-11G C
Solar/Wind Harmer
0.002
963831AG1-236 GEN
Solar/Wind Harmer
2.572
276615X2-022 GEN
Solar/Wind Harmer
0.069
965911AG1-460 GEN
Solar/Wind Harmer
1.271
276903AD2-071 C
Solar/Wind Harmer
6.987
270143AC1-141 CT2_
50/50
2.749
24639705ELKHART HY
50/50
0.186
970521AG2-332 GEN
50/50
13.262
970155AG2-107 GEN
Solar/Wind Harmer
49.204
270349AD2-093_GEN
Solar/Wind Harmer
0.008
270449AD2-020 GEN
Solar/Wind Harmer
0.001
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
5.54
276776AD2-060 GEN
Solar/Wind Harmer
0.802
274676JOLIET 29;8U
Adder
33.566
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0.006
274745AC1-111 GEN9
Adder
6.067
274682WAUKEGAN ;7U
Adder
19.302
274828WAUKEGAN ;BP
Adder
11.851
276901AD2-066 C O1
Solar/Wind Harmer
0.007
957471AF2-041 GEN
Solar/Wind Harmer
22.011
965651AG1-433 GEN
Solar/Wind Harmer
2.125
247521TR3_G114
Solar/Wind Harmer
0.264
270246TR4_N_V150
Solar/Wind Harmer
0.047
274877BISHOP HL;1U
Solar/Wind Harmer
0.238
965421AG1-410 GEN
Solar/Wind Harmer
21.282
24695305TIMB G C
Solar/Wind Harmer
0.002
24721705FLATG2
Adder
20.046
970291AG2-192 GEN
Solar/Wind Harmer
0.85
965031AG1-367 GEN
Solar/Wind Harmer
6.208
270100X2-052 CT1
50/50
1.694
970615AG2-402 GEN
50/50
2.672
970321AG2-212 GEN
Solar/Wind Harmer
3.603
970611AG2-400 GEN
Solar/Wind Harmer
8.015
957891AF2-083 GEN
Solar/Wind Harmer
0.001
274770LINCOLN ;1U
Adder
9.481
274771LINCOLN ;2U
Adder
9.481
274808UNIV PK N;4U
Adder
5.515
972259AH1-714 GEN
Adder
21.018
274888KELLY CRK;1U
Solar/Wind Harmer
0.451
274697ROCKY RD ;3P
Adder
3.253
274696ROCKY RD ;4P
Adder
12.256
962691AG1-118 GEN
Solar/Wind Harmer
22.382
274856ECOGROVE ;U1
Solar/Wind Harmer
0.172
276611AD2-172 GEN
Solar/Wind Harmer
0.002
938861AE1-114 GEN
Solar/Wind Harmer
4.102
274762LEE CO EC;3U
Adder
9.624
276603SUBLETTE C
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
276645AC1-214 GEN1
Solar/Wind Harmer
0.28
942221AE2-234 GEN
Solar/Wind Harmer
0.035
246938BC-WTG3
Solar/Wind Harmer
0.253
246937BC-WTG2
Solar/Wind Harmer
0.284
270007AE1-245 C
Solar/Wind Harmer
0.002
970241AG2-163 GEN
Solar/Wind Harmer
3.822
970623AG2-406 GEN
Solar/Wind Harmer
1.191
970825AG2-519 GEN
Solar/Wind Harmer
6.757
944961AF1-161 GEN
50/50
3.279
270043AE2-236 GEN
Solar/Wind Harmer
5.352
965021AG1-366 GEN
Solar/Wind Harmer
2.672
945111AF1-176 GEN
Solar/Wind Harmer
6.422
274772LINCOLN ;3U
Adder
9.481
274724RIVER EC ;11
Adder
19.704
24441205WTRV SLR C
Solar/Wind Harmer
0
274802UNIV PARK;5U
Adder
6.424
970941AG2-585 GEN
Solar/Wind Harmer
9.602
274800UNIV PARK;3U
Adder
6.418
276897AD1-100 C
Solar/Wind Harmer
0.01
274729ELWOOD EC;1P
Adder
17.946
276893AG1-478 C
Solar/Wind Harmer
0.302
276805AD2-038 GEN
Solar/Wind Harmer
0.002
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.787
274850MENDOTA H;RU
Solar/Wind Harmer
0.087
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.132
270485AE1-090_GEN
Solar/Wind Harmer
0.001
276889AE2-281 GEN
Solar/Wind Harmer
0.001
970571AG2-364 GEN
Solar/Wind Harmer
14.514
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
276157O29GEN1
Solar/Wind Harmer
1.155
942111AE2-223 GEN
Solar/Wind Harmer
2.286
971993AH1-541 GEN
Solar/Wind Harmer
3.06
276621W2-048 GEN
Solar/Wind Harmer
0.329
276838X2-022 GEN2
Solar/Wind Harmer
0.368
942481AE2-261 GEN
Solar/Wind Harmer
19.002
270102X2-052 ST
50/50
1.839
270216AD2-079_GEN
Solar/Wind Harmer
0.001
970627AG2-408 GEN
Solar/Wind Harmer
2.404
961051AF2-396 GEN
Solar/Wind Harmer
15.779
961051AF2-396 GEN
Solar/Wind Harmer
10.52
270224U2-072_GEN2
Solar/Wind Harmer
0.001
274803UNIV PARK;6U
Adder
6.424
274887GEN-1.85
Solar/Wind Harmer
0.202
274674JOLIET 9 ;6U
Adder
16.822
274693ROCKY RD ;1P
Adder
11.856
958481AF2-142 GEN
Solar/Wind Harmer
11.245
274862TOP CROP ;2U
Solar/Wind Harmer
1.014
274683WAUKEGAN ;8U
Adder
22.608
274683WAUKEGAN ;8U
Adder
19.058
970921AG2-575 GEN
Solar/Wind Harmer
7.446
970921AG2-575 GEN
Solar/Wind Harmer
2.482
274879MINONK ;1U
Solar/Wind Harmer
0.312
971335AH1-147 GEN
Solar/Wind Harmer
14.742
960971AF2-388 GEN
Solar/Wind Harmer
4.249
274764LEE CO EC;5U
Adder
9.646
972267AH1-718 GEN
Adder
4.273
276708O09 GEN2
Solar/Wind Harmer
0.254
276782AC1-033 GEN
Solar/Wind Harmer
0.001
960611AF2-352 GEN
Solar/Wind Harmer
2.312
966841AG1-555 GEN
Solar/Wind Harmer
0.776
270599AE1-208 GEN
Solar/Wind Harmer
5.977
945391AF1-204 GEN
Solar/Wind Harmer
6.429
24641605TWIN BRNCH
50/50
0.02
24344005CKG1
50/50
7.487
970349AG2-230 GEN
Solar/Wind Harmer
12.636
970513AG2-328 GEN
Solar/Wind Harmer
3.603
970517AG2-330 GEN
Solar/Wind Harmer
21.62
970031AG2-029 GEN
Solar/Wind Harmer
5.17
944531AF1-118 GEN
Solar/Wind Harmer
35.074
270391AF1-285 GEN3
Solar/Wind Harmer
0.52
274752CRETE EC ;2U
Adder
9.153
970707AG2-453 GEN
Solar/Wind Harmer
25.196
274826FISK ;BP
Adder
12.062
972228AH1-698 GEN2
Adder
4.076
247604X1-042
Adder
0.457
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
274730ELWOOD EC;6P
Adder
17.946
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274855GSG-6 ;RU
Solar/Wind Harmer
0.271
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
270247TR4_N_V136
Solar/Wind Harmer
0.047
970781AG2-491 GEN
Solar/Wind Harmer
7.069
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
959611AF2-252 GEN
Solar/Wind Harmer
2.312
270404AC1-167 GEN
Solar/Wind Harmer
0.003
958821AF2-173 GEN
Solar/Wind Harmer
8.691
970193AG2-126 GEN
Solar/Wind Harmer
0.05
943021AE2-325 GEN
Solar/Wind Harmer
4.108
270223U2-072_GEN1
Solar/Wind Harmer
0.001
970373AG2-245 GEN
Solar/Wind Harmer
16.169
941551AE2-152 GEN
Solar/Wind Harmer
0.001
276691AA1-018 GEN1
Solar/Wind Harmer
0.908
971917AH1-482 GEN
Solar/Wind Harmer
9.692
274872LEEDK;1U
Solar/Wind Harmer
0.005
959081AF2-199 GEN
Solar/Wind Harmer
7.337
971067AG2-660 GEN
Solar/Wind Harmer
2.446
274822ROCKFORD ;11
Adder
20.584
970819AG2-516 GEN
Solar/Wind Harmer
8.741
971475AH1-234 GEN
Solar/Wind Harmer
3.527
24791305MDL-5G
Solar/Wind Harmer
0.001
276726Z2-087_GEN
Solar/Wind Harmer
0.002
274854TWINGROVE;U2
Solar/Wind Harmer
0.003
963741AG1-226 GEN
Solar/Wind Harmer
15.506
274763LEE CO EC;4U
Adder
9.533
945421AF1-207 GEN
Solar/Wind Harmer
0.001
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
276646AC1-214 GEN2
Solar/Wind Harmer
0.28
270031AE2-169
Solar/Wind Harmer
3.586
276911AD2-131_GEN
Solar/Wind Harmer
0.873
960441AF2-335 GEN
Solar/Wind Harmer
6.126
946101AF1-275 GEN
Solar/Wind Helper
0.597
270475AD2-096_GEN
50/50
8.519
24642205MAYFLWER
50/50
0.768
962601AG1-109 GEN
50/50
3.279
959331AF2-224 GEN
Solar/Wind Harmer
5.61
274753CRETE EC ;3U
Adder
9.153
972038AH1-567 GEN2
Adder
0.402
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274872LEEDK;1U
Solar/Wind Harmer
0.273
972236AH1-702 GEN2
Adder
2.294
270191TR4_S_V150
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
9.624
274878BISHOP HL;2U
Solar/Wind Harmer
0.238
270491AE1-102 GEN2
Solar/Wind Harmer
0.91
965931AG1-462 GEN
Solar/Wind Harmer
17.759
965091AG1-374 GEN
Solar/Wind Harmer
20.808
276686W4-005 GEN3
Solar/Wind Harmer
0.001
270258AD1-119 GEN
Solar/Wind Harmer
0.002
971617AH1-308 GEN
Solar/Wind Harmer
5.346
270004AE1-209 GEN
Solar/Wind Harmer
1.345
270471AD2-092_GEN
Solar/Wind Harmer
0.008
965681AG1-436 GEN
Solar/Wind Harmer
9.975
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
971341AH1-150 GEN
Solar/Wind Harmer
14.674
971343AH1-151 GEN
Solar/Wind Harmer
14.674
276741O09 GEN1
Solar/Wind Harmer
0.254
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
971613AH1-306 GEN
Solar/Wind Harmer
3.083
276916AD2-100_GEN
Solar/Wind Harmer
13.256
NYPJM->LTFIMP_NY
CLTF
2.688
LGEELTFEXP_LGEE->PJM
CLTF
3.713
WECLTFEXP_WEC->PJM
CLTF
3.994
AG2-052LTFEXP_AG2-052->PJM
LTF
0.248
AH1-155LTFEXP_AH1-155->PJM
LTF
0.372
CBM West 1LTFEXP_CBM-W1->PJM
CBM
126.781
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.587
MECLTFEXP_MEC->PJM
CLTF
15.331
SIGELTFEXP_SIGE->PJM
CLTF
0.348
LAGNLTFEXP_LAGN->PJM
CLTF
11.555
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.616
TVALTFEXP_TVA->PJM
CLTF
5.174
CPLELTFEXP_CPLE->PJM
CLTF
1.382
CBM West 2LTFEXP_CBM-W2->PJM
CBM
89.919

Details for 05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line l/o AEP_P1-2_#706_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#706_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.43 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5322.01
MW Contribution:1.31
Bus #Bus NameTypeMW Contribution
270475AD2-096_GEN
50/50
10.026
24642205MAYFLWER
50/50
0.992
962601AG1-109 GEN
50/50
4.253
959331AF2-224 GEN
Solar/Wind Harmer
7.376
274753CRETE EC ;3U
Adder
11.58
972038AH1-567 GEN2
Adder
0.506
247620Y3-023
50/50
0.722
270101X2-052 CT2
50/50
2.169
270526AF1-158 GEN
Solar/Wind Harmer
0.013
24441505OLIV SLR
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
9.351
276843GEN-1.7
Solar/Wind Harmer
0.313
958011AF2-095 GEN
Solar/Wind Harmer
13.939
971573AH1-285 GEN
Solar/Wind Harmer
1.764
274695ROCKY RD ;2P
Adder
14.996
274861TOP CROP ;1U
Solar/Wind Harmer
0.003
944541AF1-119 GEN
Solar/Wind Harmer
0.629
958491AF2-143 GEN
Solar/Wind Harmer
13.931
24721605FLATG1
50/50
5.145
270144AC1-141 ST1_
50/50
3.152
270286AF1-227 GEN2
Solar/Wind Harmer
0.006
960681AF2-359 GEN
Solar/Wind Harmer
-0.002
274776LINCOLN ;7U
Adder
11.972
965041AG1-368 GEN
Solar/Wind Harmer
9.847
270578AF1-285 GEN2
Solar/Wind Harmer
0.651
274814UNIV PK N;0U
Adder
7.057
274807UNIV PK N;3U
Adder
7.042
274805UNIV PK N;1U
Adder
7.011
274687WILL CNTY;4U
Adder
38.503
274687WILL CNTY;4U
Adder
38.503
274731ELWOOD EC;2P
Adder
22.566
274733ELWOOD EC;3P
Adder
22.566
274746AC1-111 G10
Adder
7.614
276882AE2-255 GEN
Solar/Wind Harmer
1.081
965101AG1-375 GEN
Solar/Wind Harmer
9.202
926823AC1-168 GEN
Solar/Wind Harmer
1.535
24690905MDL-1G C
Solar/Wind Harmer
0.003
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
276655WTG1_EQ
Solar/Wind Harmer
0.003
24386205FR-12G C
Solar/Wind Harmer
0.001
971609AH1-304 GEN
Solar/Wind Harmer
1.375
963841AG1-237 GEN
Solar/Wind Harmer
3.575
970115AG2-085 GEN
Solar/Wind Harmer
3.159
24699105WLD G1 C
Solar/Wind Harmer
0.001
270297AD1-101 GEN
Solar/Wind Harmer
0.002
24344105CKG2
50/50
12.069
970149AG2-104 GEN
Solar/Wind Harmer
129.655
943021AE2-325 GEN
Solar/Wind Harmer
5.329
270223U2-072_GEN1
Solar/Wind Harmer
0.001
970373AG2-245 GEN
Solar/Wind Harmer
20.506
941551AE2-152 GEN
Solar/Wind Harmer
0.001
276691AA1-018 GEN1
Solar/Wind Harmer
1.138
971917AH1-482 GEN
Solar/Wind Harmer
12.195
274872LEEDK;1U
Solar/Wind Harmer
0.006
959081AF2-199 GEN
Solar/Wind Harmer
9.143
971067AG2-660 GEN
Solar/Wind Harmer
3.048
274822ROCKFORD ;11
Adder
25.633
970819AG2-516 GEN
Solar/Wind Harmer
10.874
971475AH1-234 GEN
Solar/Wind Harmer
4.385
24791305MDL-5G
Solar/Wind Harmer
0.001
276726Z2-087_GEN
Solar/Wind Harmer
0.003
274854TWINGROVE;U2
Solar/Wind Harmer
0.004
963741AG1-226 GEN
Solar/Wind Harmer
19.026
942991AE2-321 GEN
Solar/Wind Harmer
10.32
971333AH1-146 GEN
Solar/Wind Harmer
18.389
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
274765LEE CO EC;6U
Adder
11.975
274763LEE CO EC;4U
Adder
11.834
945421AF1-207 GEN
Solar/Wind Harmer
0.001
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
276646AC1-214 GEN2
Solar/Wind Harmer
0.347
270031AE2-169
Solar/Wind Harmer
4.629
960441AF2-335 GEN
Solar/Wind Harmer
7.897
964611AG1-324 GEN
Solar/Wind Harmer
0.584
270201AC2-176 GEN
Solar/Wind Harmer
0.001
276911AD2-131_GEN
Solar/Wind Harmer
0.883
24643105BUCHANAN
50/50
0.019
270287AF1-227 GEN3
Solar/Wind Harmer
0.006
971347AH1-153 GEN
Solar/Wind Harmer
16.236
971619AH1-309 GEN
Solar/Wind Harmer
4.631
274775LINCOLN ;6U
Adder
11.972
274777LINCOLN ;8U
Adder
11.972
972037AH1-567 GEN1
Adder
0.254
960591AF2-350 GEN
Solar/Wind Harmer
9.68
965051AG1-369 GEN
Solar/Wind Harmer
4.807
274675JOLIET 29;7U
Adder
42.223
274675JOLIET 29;7U
Adder
40.715
970833AG2-524 GEN
Solar/Wind Harmer
10.52
970833AG2-524 GEN
Solar/Wind Harmer
7.013
270317AD1-130_GEN
Solar/Wind Harmer
0.013
276868AE1-113 GEN
Solar/Wind Harmer
1.855
971411AH1-196 GEN
Solar/Wind Harmer
13.802
971675AH1-338 GEN
Solar/Wind Harmer
3.588
971611AH1-305 GEN
Solar/Wind Harmer
5.454
971171AH1-044 GEN
Solar/Wind Harmer
18.285
274823ROCKFORD ;21
Adder
25.447
945581AF1-223 GEN
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.002
270181AB1-006 GEN2
Solar/Wind Harmer
0
276656WTG2_EQ
Solar/Wind Harmer
0
941731AE2-173 GEN
Solar/Wind Harmer
7.258
946321AF1-296 GEN
Solar/Wind Harmer
4.827
24386405FR-21G C
Solar/Wind Harmer
0.001
24725505WLD G2 C
Solar/Wind Harmer
0.001
24641605TWIN BRNCH
50/50
0.026
24344005CKG1
50/50
9.691
247604X1-042
50/50
0.632
970349AG2-230 GEN
Solar/Wind Harmer
16.236
970513AG2-328 GEN
Solar/Wind Harmer
4.559
970517AG2-330 GEN
Solar/Wind Harmer
27.357
970031AG2-029 GEN
Solar/Wind Harmer
6.732
944531AF1-118 GEN
Solar/Wind Harmer
45.595
274752CRETE EC ;2U
Adder
11.58
270391AF1-285 GEN3
Solar/Wind Harmer
0.651
970707AG2-453 GEN
Solar/Wind Harmer
31.724
274826FISK ;BP
Adder
15.205
972228AH1-698 GEN2
Adder
5.135
270247TR4_N_V136
Solar/Wind Harmer
0.062
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
274730ELWOOD EC;6P
Adder
22.567
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
274855GSG-6 ;RU
Solar/Wind Harmer
0.337
970781AG2-491 GEN
Solar/Wind Harmer
8.785
270404AC1-167 GEN
Solar/Wind Harmer
0.004
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
959611AF2-252 GEN
Solar/Wind Harmer
2.854
958821AF2-173 GEN
Solar/Wind Harmer
11.2
24728705AND G3
Adder
7.82
270102X2-052 ST
50/50
2.354
970627AG2-408 GEN
Solar/Wind Harmer
3.161
270216AD2-079_GEN
Solar/Wind Harmer
0.002
961051AF2-396 GEN
Solar/Wind Harmer
20.46
961051AF2-396 GEN
Solar/Wind Harmer
13.64
270224U2-072_GEN2
Solar/Wind Harmer
0.001
274803UNIV PARK;6U
Adder
8.1
274887GEN-1.85
Solar/Wind Harmer
0.255
274674JOLIET 9 ;6U
Adder
21.154
958481AF2-142 GEN
Solar/Wind Harmer
14.096
274693ROCKY RD ;1P
Adder
14.848
274862TOP CROP ;2U
Solar/Wind Harmer
1.271
960971AF2-388 GEN
Solar/Wind Harmer
5.509
274683WAUKEGAN ;8U
Adder
28.303
274683WAUKEGAN ;8U
Adder
23.858
970921AG2-575 GEN
Solar/Wind Harmer
9.308
970921AG2-575 GEN
Solar/Wind Harmer
3.103
274879MINONK ;1U
Solar/Wind Harmer
0.39
971335AH1-147 GEN
Solar/Wind Harmer
18.389
274764LEE CO EC;5U
Adder
11.975
972267AH1-718 GEN
Adder
5.295
276708O09 GEN2
Solar/Wind Harmer
0.315
276782AC1-033 GEN
Solar/Wind Harmer
0.001
960611AF2-352 GEN
Solar/Wind Harmer
2.854
966841AG1-555 GEN
Solar/Wind Harmer
0.959
270599AE1-208 GEN
Solar/Wind Harmer
7.715
962761AG1-125 GEN
Solar/Wind Harmer
120.047
970245AG2-165 GEN
Solar/Wind Harmer
4.559
270063AE2-323 C
Solar/Wind Harmer
0.008
274754CRETE EC ;4U
Adder
11.58
274674JOLIET 9 ;6U
Adder
21.154
274732ELWOOD EC;7P
Adder
22.567
944231AF1-091 GEN
Solar/Wind Harmer
2.532
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270462AD2-086
Solar/Wind Harmer
0.02
962781AG1-127 GEN
Solar/Wind Harmer
8.858
939401AE1-172 GEN
Solar/Wind Harmer
6.954
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
972235AH1-702 GEN1
Adder
3.284
274857EASY ROAD;U1
Solar/Wind Harmer
0.002
274766LEE CO EC;7U
Adder
11.806
24385905FR-11G C
Solar/Wind Harmer
0.002
963831AG1-236 GEN
Solar/Wind Harmer
3.14
276615X2-022 GEN
Solar/Wind Harmer
0.084
276903AD2-071 C
Solar/Wind Harmer
8.872
965911AG1-460 GEN
Solar/Wind Harmer
1.538
24722005FLATG5
50/50
5.145
24721905FLATG4
50/50
94.33
270142AC1-141 CT1_
50/50
3.558
24721805FLATG3
50/50
5.145
24721705FLATG2
50/50
94.33
270143AC1-141 CT2_
50/50
3.558
24639705ELKHART HY
50/50
0.241
970521AG2-332 GEN
50/50
17.184
970155AG2-107 GEN
Solar/Wind Harmer
76.659
270349AD2-093_GEN
Solar/Wind Harmer
0.009
270449AD2-020 GEN
Solar/Wind Harmer
0.001
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
6.996
276776AD2-060 GEN
Solar/Wind Harmer
1.011
247521TR3_G114
Solar/Wind Harmer
0.351
270246TR4_N_V150
Solar/Wind Harmer
0.062
274676JOLIET 29;8U
Adder
42.222
270055AF2-134 C O1
Solar/Wind Harmer
0.007
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
274745AC1-111 GEN9
Adder
7.614
24695305TIMB G C
Solar/Wind Harmer
0.002
965421AG1-410 GEN
Solar/Wind Harmer
28.36
965651AG1-433 GEN
Solar/Wind Harmer
2.755
274682WAUKEGAN ;7U
Adder
24.169
274828WAUKEGAN ;BP
Adder
14.836
276901AD2-066 C O1
Solar/Wind Harmer
0.009
957471AF2-041 GEN
Solar/Wind Harmer
27.428
274877BISHOP HL;1U
Solar/Wind Harmer
0.295
970291AG2-192 GEN
Solar/Wind Harmer
1.08
965031AG1-367 GEN
Solar/Wind Harmer
8
24728605AND G2
Adder
3.739
270471AD2-092_GEN
Solar/Wind Harmer
0.009
965681AG1-436 GEN
Solar/Wind Harmer
12.752
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
971341AH1-150 GEN
Solar/Wind Harmer
18.285
971343AH1-151 GEN
Solar/Wind Harmer
18.285
276741O09 GEN1
Solar/Wind Harmer
0.315
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
971613AH1-306 GEN
Solar/Wind Harmer
3.931
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
247621Y3-024
Adder
0.262
276916AD2-100_GEN
Solar/Wind Harmer
13.41
962771AG1-126 GEN
Solar/Wind Harmer
120.047
270284AF1-227 GEN1
Solar/Wind Harmer
0.014
274811UNIV PK N;7U
Adder
6.996
274827FISK ;RP
Adder
10.776
972227AH1-698 GEN1
Adder
3.616
274735ELWOOD EC;4P
Adder
22.566
270536AF1-215 GEN2
Solar/Wind Harmer
0.012
274744AC1-111 GEN8
Adder
7.614
963791AG1-232 GEN
Solar/Wind Harmer
12.76
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270302AB2-170 GEN
Solar/Wind Harmer
0.006
971653AH1-327 GEN
Solar/Wind Harmer
1.314
958391AF2-133 GEN
Solar/Wind Harmer
0.001
970169AG2-114 GEN
Solar/Wind Harmer
9.023
961011AF2-392 GEN
Solar/Wind Harmer
5.219
274848CAMPGROVE;RU
Solar/Wind Harmer
0.002
959341AF2-225 GEN
Solar/Wind Harmer
9.145
944961AF1-161 GEN
50/50
4.253
270043AE2-236 GEN
Solar/Wind Harmer
6.969
965021AG1-366 GEN
Solar/Wind Harmer
3.512
945111AF1-176 GEN
Solar/Wind Harmer
8.323
24441205WTRV SLR C
Solar/Wind Harmer
0
274772LINCOLN ;3U
Adder
11.972
274724RIVER EC ;11
Adder
24.913
274802UNIV PARK;5U
Adder
8.1
274800UNIV PARK;3U
Adder
8.089
970941AG2-585 GEN
Solar/Wind Harmer
12.1
276897AD1-100 C
Solar/Wind Harmer
0.013
274729ELWOOD EC;1P
Adder
22.566
276893AG1-478 C
Solar/Wind Harmer
0.379
270485AE1-090_GEN
Solar/Wind Harmer
0.001
276805AD2-038 GEN
Solar/Wind Harmer
0.003
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
0.982
274850MENDOTA H;RU
Solar/Wind Harmer
0.108
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.165
276889AE2-281 GEN
Solar/Wind Harmer
0.001
970571AG2-364 GEN
Solar/Wind Harmer
18.064
274858EASY ROAD;U2
Solar/Wind Harmer
0.002
276157O29GEN1
Solar/Wind Harmer
1.431
942111AE2-223 GEN
Solar/Wind Harmer
2.831
971993AH1-541 GEN
Solar/Wind Harmer
3.74
276621W2-048 GEN
Solar/Wind Harmer
0.401
276838X2-022 GEN2
Solar/Wind Harmer
0.448
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
11.672
942481AE2-261 GEN
Solar/Wind Harmer
22.986
971599AH1-298 GEN
50/50
14.587
24653605MOTTVILLE
50/50
0.006
270071AF1-092 GEN
Solar/Wind Harmer
20.132
971771AH1-392 GEN
Solar/Wind Harmer
10.346
971769AH1-391 GEN
Solar/Wind Harmer
11.424
24729505KEY G4
Adder
9.267
274728ELWOOD EC;5P
Adder
22.567
971549AH1-272 GEN
Solar/Wind Harmer
19.681
270435AC2-044 GEN
Solar/Wind Harmer
1.183
971177AH1-047 GEN
Solar/Wind Harmer
5.697
274863CRW1-WTG
Solar/Wind Harmer
0.003
274864CRW2-WTG
Solar/Wind Harmer
0.003
276612AE2-035 GEN
Solar/Wind Harmer
0.002
971681AH1-341 GEN
Solar/Wind Harmer
14.483
247607V1-011 GEN
Solar/Wind Harmer
0.001
957751AF2-069 GEN
Solar/Wind Harmer
0.292
24691005MDL-2G C
Solar/Wind Harmer
0.002
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
270594AE1-207 GEN
Solar/Wind Harmer
9.172
276174W4-005 GEN2
Solar/Wind Harmer
0.001
970615AG2-402 GEN
50/50
3.512
270100X2-052 CT1
50/50
2.169
970611AG2-400 GEN
Solar/Wind Harmer
10.537
970321AG2-212 GEN
Solar/Wind Harmer
4.559
957891AF2-083 GEN
Solar/Wind Harmer
0.001
274770LINCOLN ;1U
Adder
11.972
274771LINCOLN ;2U
Adder
11.972
274808UNIV PK N;4U
Adder
6.965
274888KELLY CRK;1U
Solar/Wind Harmer
0.568
972259AH1-714 GEN
Adder
26.463
274697ROCKY RD ;3P
Adder
4.074
274696ROCKY RD ;4P
Adder
15.349
246938BC-WTG3
Solar/Wind Harmer
0.338
246937BC-WTG2
Solar/Wind Harmer
0.379
962691AG1-118 GEN
Solar/Wind Harmer
27.992
942221AE2-234 GEN
Solar/Wind Harmer
0.046
274856ECOGROVE ;U1
Solar/Wind Harmer
0.213
276611AD2-172 GEN
Solar/Wind Harmer
0.002
938861AE1-114 GEN
Solar/Wind Harmer
5.096
274762LEE CO EC;3U
Adder
11.947
276603SUBLETTE C
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
270007AE1-245 C
Solar/Wind Harmer
0.002
276645AC1-214 GEN1
Solar/Wind Harmer
0.347
970623AG2-406 GEN
Solar/Wind Harmer
1.614
970241AG2-163 GEN
Solar/Wind Harmer
4.69
970825AG2-519 GEN
Solar/Wind Harmer
8.719
970621AG2-405 GEN
Solar/Wind Harmer
1.413
24307105BERRINSP G
50/50
0.032
965011AG1-365 GEN
Solar/Wind Harmer
10.537
270505AE1-170 C O1
Solar/Wind Harmer
10.806
945111AF1-176 GEN
Solar/Wind Harmer
18.321
274773LINCOLN ;4U
Adder
11.972
274774LINCOLN ;5U
Adder
11.972
274723RIVER EC ;12
Adder
25.205
274751CRETE EC ;1U
Adder
11.58
274801UNIV PARK;4U
Adder
8.089
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
246936BC-WTG1
Solar/Wind Harmer
0.379
270489AE1-102 GEN1
Solar/Wind Harmer
1.214
971997AH1-543 GEN
Solar/Wind Harmer
4.843
958861AF2-177 GEN
Solar/Wind Harmer
3.987
276861AD2-134 GEN
Solar/Wind Harmer
0.165
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
11.452
970569AG2-363 GEN
Solar/Wind Harmer
27.095
274761LEE CO EC;2U
Adder
11.947
276158O29GEN2
Solar/Wind Harmer
0.001
945371AF1-202 GEN
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
12.194
24387305FR-4G C
Solar/Wind Harmer
0.003
972175AH1-670 GEN
Solar/Wind Harmer
6.873
270032AE2-172
Solar/Wind Harmer
5.46
274880W4-005 GEN4
Solar/Wind Harmer
0.001
270005AE1-210 C O1
Solar/Wind Harmer
1.733
970825AG2-519 GEN
Solar/Wind Harmer
2.793
270024AE2-089 GEN
Solar/Wind Harmer
0.009
970289AG2-191 GEN
Solar/Wind Harmer
1.578
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.295
276848AB2-070 GEN3
Solar/Wind Harmer
0.294
970153AG2-106 GEN
Solar/Wind Harmer
76.659
247643Z2-116 C
Solar/Wind Harmer
0
276806AD2-047 C O1
Solar/Wind Harmer
5.485
274676JOLIET 29;8U
Adder
40.714
274734ELWOOD EC;8P
Adder
22.567
274736ELWOOD EC;9P
Adder
22.567
270535AF1-215 GEN1
Solar/Wind Harmer
0.012
943121AE2-341 GEN
Solar/Wind Harmer
15.96
943591AF1-030 GEN
Solar/Wind Harmer
10.614
274682WAUKEGAN ;7U
Adder
24.169
959091AF2-200 GEN
Solar/Wind Harmer
18.285
274767LEE CO EC;8U
Adder
11.806
24755605MDL-5G
Solar/Wind Harmer
0.001
247642Z2-115 C
Solar/Wind Harmer
0.004
970289AG2-191 GEN
Solar/Wind Harmer
0.914
970291AG2-192 GEN
Solar/Wind Harmer
0.831
276668AB2-070 GEN1
Solar/Wind Harmer
0.295
946031AF1-268 GEN
Solar/Wind Harmer
7.422
24728505AND G1
Adder
3.739
270191TR4_S_V150
Solar/Wind Harmer
0.001
964401AG1-302 GEN
Solar/Wind Harmer
0.001
270491AE1-102 GEN2
Solar/Wind Harmer
1.214
274872LEEDK;1U
Solar/Wind Harmer
0.341
972236AH1-702 GEN2
Adder
2.856
274760LEE CO EC;1U
Adder
11.947
270258AD1-119 GEN
Solar/Wind Harmer
0.002
274878BISHOP HL;2U
Solar/Wind Harmer
0.295
965931AG1-462 GEN
Solar/Wind Harmer
21.861
965091AG1-374 GEN
Solar/Wind Harmer
25.685
971617AH1-308 GEN
Solar/Wind Harmer
7.03
276686W4-005 GEN3
Solar/Wind Harmer
0.001
270004AE1-209 GEN
Solar/Wind Harmer
1.733
944201AF1-088_MTX
Adder
85.667
NYPJM->LTFIMP_NY
CLTF
2.99
LGEELTFEXP_LGEE->PJM
CLTF
4.155
WECLTFEXP_WEC->PJM
CLTF
4.968
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.286
AG2-052LTFEXP_AG2-052->PJM
LTF
0.312
AH1-155LTFEXP_AH1-155->PJM
LTF
0.469
CBM West 1LTFEXP_CBM-W1->PJM
CBM
161.402
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.132
MECLTFEXP_MEC->PJM
CLTF
18.394
SIGELTFEXP_SIGE->PJM
CLTF
0.399
LAGNLTFEXP_LAGN->PJM
CLTF
11.144
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.328
TVALTFEXP_TVA->PJM
CLTF
4.56
CBM West 2LTFEXP_CBM-W2->PJM
CBM
96.989

Details for 05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line l/o AEP_P1-2_#728_584_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#728_584_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.46 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5094.73
MW Contribution:1.03
Bus #Bus NameTypeMW Contribution
270101X2-052 CT2
50/50
1.694
247620Y3-023
50/50
0.557
965791AG1-447 GEN
Solar/Wind Harmer
7.315
270526AF1-158 GEN
Solar/Wind Harmer
0.01
24441505OLIV SLR
Solar/Wind Harmer
0
276843GEN-1.7
Solar/Wind Harmer
0.249
958011AF2-095 GEN
Solar/Wind Harmer
11.061
971573AH1-285 GEN
Solar/Wind Harmer
1.407
274695ROCKY RD ;2P
Adder
11.974
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
958491AF2-143 GEN
Solar/Wind Harmer
11.137
942991AE2-321 GEN
Solar/Wind Harmer
8.265
971333AH1-146 GEN
Solar/Wind Harmer
14.742
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
944541AF1-119 GEN
Solar/Wind Harmer
0.485
274765LEE CO EC;6U
Adder
9.646
274763LEE CO EC;4U
Adder
9.533
945421AF1-207 GEN
Solar/Wind Harmer
0.001
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
276646AC1-214 GEN2
Solar/Wind Harmer
0.28
270031AE2-169
Solar/Wind Harmer
3.586
276911AD2-131_GEN
Solar/Wind Harmer
0.873
960441AF2-335 GEN
Solar/Wind Harmer
6.126
946101AF1-275 GEN
Solar/Wind Helper
0.597
24643105BUCHANAN
50/50
0.015
270287AF1-227 GEN3
Solar/Wind Harmer
0.005
971347AH1-153 GEN
Solar/Wind Harmer
12.636
971619AH1-309 GEN
Solar/Wind Harmer
3.576
274775LINCOLN ;6U
Adder
9.481
274777LINCOLN ;8U
Adder
9.481
972037AH1-567 GEN1
Adder
0.202
960591AF2-350 GEN
Solar/Wind Harmer
7.682
274675JOLIET 29;7U
Adder
33.566
274675JOLIET 29;7U
Adder
32.367
970833AG2-524 GEN
Solar/Wind Harmer
8.371
970833AG2-524 GEN
Solar/Wind Harmer
5.581
276868AE1-113 GEN
Solar/Wind Harmer
1.484
971675AH1-338 GEN
Solar/Wind Harmer
2.876
971411AH1-196 GEN
Solar/Wind Harmer
11.063
270317AD1-130_GEN
Solar/Wind Harmer
0.01
971171AH1-044 GEN
Solar/Wind Harmer
14.674
274823ROCKFORD ;21
Adder
20.435
971611AH1-305 GEN
Solar/Wind Harmer
4.355
965051AG1-369 GEN
Solar/Wind Harmer
3.614
24697605MDL-3G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
276656WTG2_EQ
Solar/Wind Harmer
0
941731AE2-173 GEN
Solar/Wind Harmer
5.862
946321AF1-296 GEN
Solar/Wind Harmer
3.917
24386405FR-21G C
Solar/Wind Harmer
0.001
270100X2-052 CT1
50/50
1.694
970615AG2-402 GEN
50/50
2.672
970321AG2-212 GEN
Solar/Wind Harmer
3.603
270144AC1-141 ST1_
50/50
2.435
270286AF1-227 GEN2
Solar/Wind Harmer
0.005
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
274776LINCOLN ;7U
Adder
9.481
270578AF1-285 GEN2
Solar/Wind Harmer
0.52
274814UNIV PK N;0U
Adder
5.588
274807UNIV PK N;3U
Adder
5.576
274805UNIV PK N;1U
Adder
5.552
274687WILL CNTY;4U
Adder
30.598
274687WILL CNTY;4U
Adder
30.598
274731ELWOOD EC;2P
Adder
17.946
274733ELWOOD EC;3P
Adder
17.946
274746AC1-111 G10
Adder
6.067
965041AG1-368 GEN
Solar/Wind Harmer
7.422
276882AE2-255 GEN
Solar/Wind Harmer
0.865
926823AC1-168 GEN
Solar/Wind Harmer
1.234
965101AG1-375 GEN
Solar/Wind Harmer
7.103
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
276655WTG1_EQ
Solar/Wind Harmer
0.003
24386205FR-12G C
Solar/Wind Harmer
0.001
963841AG1-237 GEN
Solar/Wind Harmer
2.903
971609AH1-304 GEN
Solar/Wind Harmer
1.065
944221AF1-090 GEN
Solar/Wind Harmer
3.617
24699105WLD G1 C
Solar/Wind Harmer
0.001
970115AG2-085 GEN
Solar/Wind Harmer
2.45
962771AG1-126 GEN
Solar/Wind Harmer
77.053
270284AF1-227 GEN1
Solar/Wind Harmer
0.012
274811UNIV PK N;7U
Adder
5.54
274827FISK ;RP
Adder
8.549
972227AH1-698 GEN1
Adder
2.87
274735ELWOOD EC;4P
Adder
17.946
270536AF1-215 GEN2
Solar/Wind Harmer
0.009
274744AC1-111 GEN8
Adder
6.067
958391AF2-133 GEN
Solar/Wind Harmer
0.001
270302AB2-170 GEN
Solar/Wind Harmer
0.004
971653AH1-327 GEN
Solar/Wind Harmer
1.033
970169AG2-114 GEN
Solar/Wind Harmer
7.246
270142AC1-141 CT1_
50/50
2.749
970153AG2-106 GEN
Solar/Wind Harmer
49.204
247643Z2-116 C
Solar/Wind Harmer
0
276806AD2-047 C O1
Solar/Wind Harmer
4.353
274676JOLIET 29;8U
Adder
32.367
274734ELWOOD EC;8P
Adder
17.946
274736ELWOOD EC;9P
Adder
17.946
943121AE2-341 GEN
Solar/Wind Harmer
12.717
943591AF1-030 GEN
Solar/Wind Harmer
8.457
270535AF1-215 GEN1
Solar/Wind Harmer
0.009
274682WAUKEGAN ;7U
Adder
19.302
959091AF2-200 GEN
Solar/Wind Harmer
14.674
274767LEE CO EC;8U
Adder
9.51
24755605MDL-5G
Solar/Wind Harmer
0.001
24721905FLATG4
Adder
20.046
247642Z2-115 C
Solar/Wind Harmer
0.003
276668AB2-070 GEN1
Solar/Wind Harmer
0.241
970289AG2-191 GEN
Solar/Wind Harmer
0.719
970291AG2-192 GEN
Solar/Wind Harmer
0.654
971599AH1-298 GEN
50/50
11.184
24653605MOTTVILLE
50/50
0.004
270071AF1-092 GEN
Solar/Wind Harmer
15.591
971771AH1-392 GEN
Solar/Wind Harmer
8.024
971769AH1-391 GEN
Solar/Wind Harmer
8.897
24729505KEY G4
Adder
7.133
274728ELWOOD EC;5P
Adder
17.946
971177AH1-047 GEN
Solar/Wind Harmer
4.563
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
276612AE2-035 GEN
Solar/Wind Harmer
0.002
971681AH1-341 GEN
Solar/Wind Harmer
11.658
971549AH1-272 GEN
Solar/Wind Harmer
14.911
957751AF2-069 GEN
Solar/Wind Harmer
0.235
24691005MDL-2G C
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
0.886
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
247607V1-011 GEN
Solar/Wind Harmer
0.001
270594AE1-207 GEN
Solar/Wind Harmer
7.194
965011AG1-365 GEN
Solar/Wind Harmer
8.015
270505AE1-170 C O1
Solar/Wind Harmer
8.343
945111AF1-176 GEN
Solar/Wind Harmer
14.138
274773LINCOLN ;4U
Adder
9.481
274774LINCOLN ;5U
Adder
9.481
274723RIVER EC ;12
Adder
19.934
274751CRETE EC ;1U
Adder
9.153
274801UNIV PARK;4U
Adder
6.418
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971997AH1-543 GEN
Solar/Wind Harmer
3.877
276861AD2-134 GEN
Solar/Wind Harmer
0.132
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
9.144
970569AG2-363 GEN
Solar/Wind Harmer
21.771
274761LEE CO EC;2U
Adder
9.624
276158O29GEN2
Solar/Wind Harmer
0.001
958861AF2-177 GEN
Solar/Wind Harmer
3.078
939741AE1-205 GEN
Solar/Wind Harmer
9.848
246936BC-WTG1
Solar/Wind Harmer
0.284
270489AE1-102 GEN1
Solar/Wind Harmer
0.91
24387305FR-4G C
Solar/Wind Harmer
0.003
945371AF1-202 GEN
Solar/Wind Harmer
0.001
972175AH1-670 GEN
Solar/Wind Harmer
5.597
274880W4-005 GEN4
Solar/Wind Harmer
0.001
270032AE2-172
Solar/Wind Harmer
4.282
270005AE1-210 C O1
Solar/Wind Harmer
1.345
970825AG2-519 GEN
Solar/Wind Harmer
2.164
24344105CKG2
50/50
9.389
970149AG2-104 GEN
Solar/Wind Harmer
83.22
943021AE2-325 GEN
Solar/Wind Harmer
4.108
270223U2-072_GEN1
Solar/Wind Harmer
0.001
970373AG2-245 GEN
Solar/Wind Harmer
16.169
941551AE2-152 GEN
Solar/Wind Harmer
0.001
276691AA1-018 GEN1
Solar/Wind Harmer
0.908
971917AH1-482 GEN
Solar/Wind Harmer
9.692
274872LEEDK;1U
Solar/Wind Harmer
0.005
959081AF2-199 GEN
Solar/Wind Harmer
7.337
971067AG2-660 GEN
Solar/Wind Harmer
2.446
274822ROCKFORD ;11
Adder
20.584
970819AG2-516 GEN
Solar/Wind Harmer
8.741
971475AH1-234 GEN
Solar/Wind Harmer
3.527
24791305MDL-5G
Solar/Wind Harmer
0.001
276726Z2-087_GEN
Solar/Wind Harmer
0.002
274854TWINGROVE;U2
Solar/Wind Harmer
0.003
963741AG1-226 GEN
Solar/Wind Harmer
15.506
963791AG1-232 GEN
Solar/Wind Harmer
9.7
961011AF2-392 GEN
Solar/Wind Harmer
4.21
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
959341AF2-225 GEN
Solar/Wind Harmer
7.386
957201AF2-014 GEN
Solar/Wind Harmer
0.001
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.241
276848AB2-070 GEN3
Solar/Wind Harmer
0.24
970289AG2-191 GEN
Solar/Wind Harmer
1.243
270024AE2-089 GEN
Solar/Wind Harmer
0.007
270143AC1-141 CT2_
50/50
2.749
24639705ELKHART HY
50/50
0.186
970521AG2-332 GEN
50/50
13.262
945581AF1-223 GEN
Solar/Wind Harmer
0.001
24725505WLD G2 C
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Helper
1.885
270520AE2-214 GEN
Solar/Wind Helper
4.768
962761AG1-125 GEN
Solar/Wind Harmer
77.053
970245AG2-165 GEN
Solar/Wind Harmer
3.603
270063AE2-323 C
Solar/Wind Harmer
0.007
274754CRETE EC ;4U
Adder
9.153
274674JOLIET 9 ;6U
Adder
16.822
274732ELWOOD EC;7P
Adder
17.946
958381AF2-132 GEN
Solar/Wind Harmer
0.001
962781AG1-127 GEN
Solar/Wind Harmer
7.086
939401AE1-172 GEN
Solar/Wind Harmer
5.557
270462AD2-086
Solar/Wind Harmer
0.015
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
972235AH1-702 GEN1
Adder
2.639
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274766LEE CO EC;7U
Adder
9.51
944231AF1-091 GEN
Solar/Wind Harmer
1.892
24385905FR-11G C
Solar/Wind Harmer
0.002
963831AG1-236 GEN
Solar/Wind Harmer
2.572
276615X2-022 GEN
Solar/Wind Harmer
0.069
965911AG1-460 GEN
Solar/Wind Harmer
1.271
276903AD2-071 C
Solar/Wind Harmer
6.987
270102X2-052 ST
50/50
1.839
270216AD2-079_GEN
Solar/Wind Harmer
0.001
970627AG2-408 GEN
Solar/Wind Harmer
2.404
961051AF2-396 GEN
Solar/Wind Harmer
15.779
961051AF2-396 GEN
Solar/Wind Harmer
10.52
270224U2-072_GEN2
Solar/Wind Harmer
0.001
274803UNIV PARK;6U
Adder
6.424
274887GEN-1.85
Solar/Wind Harmer
0.202
274674JOLIET 9 ;6U
Adder
16.822
274693ROCKY RD ;1P
Adder
11.856
958481AF2-142 GEN
Solar/Wind Harmer
11.245
274862TOP CROP ;2U
Solar/Wind Harmer
1.014
274683WAUKEGAN ;8U
Adder
22.608
274683WAUKEGAN ;8U
Adder
19.058
970921AG2-575 GEN
Solar/Wind Harmer
7.446
970921AG2-575 GEN
Solar/Wind Harmer
2.482
274879MINONK ;1U
Solar/Wind Harmer
0.312
971335AH1-147 GEN
Solar/Wind Harmer
14.742
960971AF2-388 GEN
Solar/Wind Harmer
4.249
274764LEE CO EC;5U
Adder
9.646
972267AH1-718 GEN
Adder
4.273
276708O09 GEN2
Solar/Wind Harmer
0.254
276782AC1-033 GEN
Solar/Wind Harmer
0.001
960611AF2-352 GEN
Solar/Wind Harmer
2.312
966841AG1-555 GEN
Solar/Wind Harmer
0.776
270599AE1-208 GEN
Solar/Wind Harmer
5.977
970155AG2-107 GEN
Solar/Wind Harmer
49.204
270349AD2-093_GEN
Solar/Wind Harmer
0.008
270449AD2-020 GEN
Solar/Wind Harmer
0.001
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
5.54
276776AD2-060 GEN
Solar/Wind Harmer
0.802
274676JOLIET 29;8U
Adder
33.566
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0.006
274745AC1-111 GEN9
Adder
6.067
274682WAUKEGAN ;7U
Adder
19.302
274828WAUKEGAN ;BP
Adder
11.851
276901AD2-066 C O1
Solar/Wind Harmer
0.007
957471AF2-041 GEN
Solar/Wind Harmer
22.011
965651AG1-433 GEN
Solar/Wind Harmer
2.125
247521TR3_G114
Solar/Wind Harmer
0.264
270246TR4_N_V150
Solar/Wind Harmer
0.047
274877BISHOP HL;1U
Solar/Wind Harmer
0.238
965421AG1-410 GEN
Solar/Wind Harmer
21.282
24695305TIMB G C
Solar/Wind Harmer
0.002
24721705FLATG2
Adder
20.046
970291AG2-192 GEN
Solar/Wind Harmer
0.85
965031AG1-367 GEN
Solar/Wind Harmer
6.208
970611AG2-400 GEN
Solar/Wind Harmer
8.015
957891AF2-083 GEN
Solar/Wind Harmer
0.001
274770LINCOLN ;1U
Adder
9.481
274771LINCOLN ;2U
Adder
9.481
274808UNIV PK N;4U
Adder
5.515
972259AH1-714 GEN
Adder
21.018
274888KELLY CRK;1U
Solar/Wind Harmer
0.451
274697ROCKY RD ;3P
Adder
3.253
274696ROCKY RD ;4P
Adder
12.256
962691AG1-118 GEN
Solar/Wind Harmer
22.382
274856ECOGROVE ;U1
Solar/Wind Harmer
0.172
276611AD2-172 GEN
Solar/Wind Harmer
0.002
938861AE1-114 GEN
Solar/Wind Harmer
4.102
274762LEE CO EC;3U
Adder
9.624
276603SUBLETTE C
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
276645AC1-214 GEN1
Solar/Wind Harmer
0.28
942221AE2-234 GEN
Solar/Wind Harmer
0.035
246938BC-WTG3
Solar/Wind Harmer
0.253
246937BC-WTG2
Solar/Wind Harmer
0.284
270007AE1-245 C
Solar/Wind Harmer
0.002
970241AG2-163 GEN
Solar/Wind Harmer
3.822
970623AG2-406 GEN
Solar/Wind Harmer
1.191
970825AG2-519 GEN
Solar/Wind Harmer
6.757
944961AF1-161 GEN
50/50
3.279
270043AE2-236 GEN
Solar/Wind Harmer
5.352
965021AG1-366 GEN
Solar/Wind Harmer
2.672
945111AF1-176 GEN
Solar/Wind Harmer
6.422
274772LINCOLN ;3U
Adder
9.481
274724RIVER EC ;11
Adder
19.704
24441205WTRV SLR C
Solar/Wind Harmer
0
274802UNIV PARK;5U
Adder
6.424
970941AG2-585 GEN
Solar/Wind Harmer
9.602
274800UNIV PARK;3U
Adder
6.418
276897AD1-100 C
Solar/Wind Harmer
0.01
274729ELWOOD EC;1P
Adder
17.946
276893AG1-478 C
Solar/Wind Harmer
0.302
276805AD2-038 GEN
Solar/Wind Harmer
0.002
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.787
274850MENDOTA H;RU
Solar/Wind Harmer
0.087
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.132
270485AE1-090_GEN
Solar/Wind Harmer
0.001
276889AE2-281 GEN
Solar/Wind Harmer
0.001
970571AG2-364 GEN
Solar/Wind Harmer
14.514
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
276157O29GEN1
Solar/Wind Harmer
1.155
942111AE2-223 GEN
Solar/Wind Harmer
2.286
971993AH1-541 GEN
Solar/Wind Harmer
3.06
276621W2-048 GEN
Solar/Wind Harmer
0.329
276838X2-022 GEN2
Solar/Wind Harmer
0.368
942481AE2-261 GEN
Solar/Wind Harmer
19.002
945391AF1-204 GEN
Solar/Wind Harmer
6.429
24641605TWIN BRNCH
50/50
0.02
24344005CKG1
50/50
7.487
970349AG2-230 GEN
Solar/Wind Harmer
12.636
970513AG2-328 GEN
Solar/Wind Harmer
3.603
970517AG2-330 GEN
Solar/Wind Harmer
21.62
970031AG2-029 GEN
Solar/Wind Harmer
5.17
944531AF1-118 GEN
Solar/Wind Harmer
35.074
270391AF1-285 GEN3
Solar/Wind Harmer
0.52
274752CRETE EC ;2U
Adder
9.153
970707AG2-453 GEN
Solar/Wind Harmer
25.196
274826FISK ;BP
Adder
12.062
972228AH1-698 GEN2
Adder
4.076
247604X1-042
Adder
0.457
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
274730ELWOOD EC;6P
Adder
17.946
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274855GSG-6 ;RU
Solar/Wind Harmer
0.271
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
270247TR4_N_V136
Solar/Wind Harmer
0.047
970781AG2-491 GEN
Solar/Wind Harmer
7.069
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
959611AF2-252 GEN
Solar/Wind Harmer
2.312
270404AC1-167 GEN
Solar/Wind Harmer
0.003
958821AF2-173 GEN
Solar/Wind Harmer
8.691
970193AG2-126 GEN
Solar/Wind Harmer
0.05
270475AD2-096_GEN
50/50
8.519
24642205MAYFLWER
50/50
0.768
962601AG1-109 GEN
50/50
3.279
959331AF2-224 GEN
Solar/Wind Harmer
5.61
274753CRETE EC ;3U
Adder
9.153
972038AH1-567 GEN2
Adder
0.402
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274872LEEDK;1U
Solar/Wind Harmer
0.273
972236AH1-702 GEN2
Adder
2.294
270191TR4_S_V150
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
9.624
274878BISHOP HL;2U
Solar/Wind Harmer
0.238
270491AE1-102 GEN2
Solar/Wind Harmer
0.91
965931AG1-462 GEN
Solar/Wind Harmer
17.759
965091AG1-374 GEN
Solar/Wind Harmer
20.808
276686W4-005 GEN3
Solar/Wind Harmer
0.001
270258AD1-119 GEN
Solar/Wind Harmer
0.002
971617AH1-308 GEN
Solar/Wind Harmer
5.346
270004AE1-209 GEN
Solar/Wind Harmer
1.345
270471AD2-092_GEN
Solar/Wind Harmer
0.008
965681AG1-436 GEN
Solar/Wind Harmer
9.975
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
971341AH1-150 GEN
Solar/Wind Harmer
14.674
971343AH1-151 GEN
Solar/Wind Harmer
14.674
276741O09 GEN1
Solar/Wind Harmer
0.254
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
971613AH1-306 GEN
Solar/Wind Harmer
3.083
276916AD2-100_GEN
Solar/Wind Harmer
13.256
NYPJM->LTFIMP_NY
CLTF
2.688
LGEELTFEXP_LGEE->PJM
CLTF
3.713
WECLTFEXP_WEC->PJM
CLTF
3.994
AG2-052LTFEXP_AG2-052->PJM
LTF
0.248
AH1-155LTFEXP_AH1-155->PJM
LTF
0.372
CBM West 1LTFEXP_CBM-W1->PJM
CBM
126.781
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.587
MECLTFEXP_MEC->PJM
CLTF
15.331
SIGELTFEXP_SIGE->PJM
CLTF
0.348
LAGNLTFEXP_LAGN->PJM
CLTF
11.555
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.616
TVALTFEXP_TVA->PJM
CLTF
5.174
CPLELTFEXP_CPLE->PJM
CLTF
1.382
CBM West 2LTFEXP_CBM-W2->PJM
CBM
89.919

Details for AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line l/o ATSI_P1-2_OEC-345-810_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_OEC-345-810_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:123.08 %
Rating:1798.0 MVA
Rating Type:B
MVA to Mitigate:2212.91
MW Contribution:0.5
Bus #Bus NameTypeMW Contribution
23888802TROY G4
50/50
1.793
247620Y3-023
Adder
0.247
270526AF1-158 GEN
Solar/Wind Harmer
0.004
24441505OLIV SLR
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
3.128
276843GEN-1.7
Solar/Wind Harmer
0.1
958011AF2-095 GEN
Solar/Wind Harmer
4.436
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
24189802OREGON_CT1
50/50
2.72
961051AF2-396 GEN
Solar/Wind Harmer
7.8
961051AF2-396 GEN
Solar/Wind Harmer
5.2
270216AD2-079_GEN
Solar/Wind Harmer
0.001
970627AG2-408 GEN
Solar/Wind Harmer
1.08
270224U2-072_GEN2
Solar/Wind Harmer
0
274803UNIV PARK;6U
Adder
2.587
274887GEN-1.85
Solar/Wind Harmer
0.081
274674JOLIET 9 ;6U
Adder
6.729
958481AF2-142 GEN
Solar/Wind Harmer
4.519
274862TOP CROP ;2U
Solar/Wind Harmer
0.408
203947AF1-006 C
Solar/Wind Helper
0.37
241967AE2-285_GEN
Solar/Wind Helper
0.33
23929302BS-PKR
50/50
2.125
958321AF2-126 GEN
Solar/Wind Harmer
1.109
270575GUS2 35KV
Solar/Wind Harmer
4.19
970217AG2-149 GEN
Solar/Wind Harmer
4.121
270258AD1-119 GEN
Solar/Wind Harmer
0.001
270491AE1-102 GEN2
Solar/Wind Harmer
0.518
24642205MAYFLWER
Adder
0.34
270191TR4_S_V150
Solar/Wind Harmer
0
959331AF2-224 GEN
Solar/Wind Harmer
2.52
274753CRETE EC ;3U
Adder
3.744
964401AG1-302 GEN
Solar/Wind Harmer
0
972038AH1-567 GEN2
Adder
0.161
971617AH1-308 GEN
Solar/Wind Harmer
2.509
962511AG1-100 GEN
Solar/Wind Helper
0.332
959441AF2-235 GEN
Solar/Wind Helper
0.143
945421AF1-207 GEN
Solar/Wind Harmer
0
971573AH1-285 GEN
Solar/Wind Harmer
0.56
946381AF1-302 GEN
Solar/Wind Helper
0.102
972211AH1-690 GEN
50/50
287.424
970817AG2-515 GEN
Solar/Wind Harmer
10.476
945411AF1-206 GEN
Solar/Wind Harmer
-0.001
270499AE1-146 GEN
Solar/Wind Harmer
0.027
270297AD1-101 GEN
Solar/Wind Harmer
0.001
965041AG1-368 GEN
Solar/Wind Harmer
3.74
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
270578AF1-285 GEN2
Solar/Wind Harmer
0.22
274814UNIV PK N;0U
Adder
2.267
274807UNIV PK N;3U
Adder
2.262
274805UNIV PK N;1U
Adder
2.252
274776LINCOLN ;7U
Adder
3.725
274687WILL CNTY;4U
Adder
12.26
274687WILL CNTY;4U
Adder
12.26
274731ELWOOD EC;2P
Adder
7.184
274733ELWOOD EC;3P
Adder
7.184
274746AC1-111 G10
Adder
2.415
241982AE2-343 S C
Solar/Wind Helper
0.115
254304AE2-114 C
Solar/Wind Helper
0.109
241832AE2-181_GEN
Solar/Wind Harmer
0.003
24441205WTRV SLR C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
3.117
965021AG1-366 GEN
Solar/Wind Harmer
1.2
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270043AE2-236 GEN
Solar/Wind Harmer
2.187
274724RIVER EC ;11
Adder
7.981
274802UNIV PARK;5U
Adder
2.587
274800UNIV PARK;3U
Adder
2.578
970941AG2-585 GEN
Solar/Wind Harmer
3.851
274772LINCOLN ;3U
Adder
3.725
276897AD1-100 C
Solar/Wind Harmer
0.004
276893AG1-478 C
Solar/Wind Harmer
0.121
274729ELWOOD EC;1P
Adder
7.184
241996AE2-282_GEN
Solar/Wind Harmer
0.005
970621AG2-405 GEN
Solar/Wind Harmer
0.843
970623AG2-406 GEN
Solar/Wind Harmer
0.778
270007AE1-245 C
Solar/Wind Harmer
0.001
246938BC-WTG3
Solar/Wind Harmer
0.144
246937BC-WTG2
Solar/Wind Harmer
0.162
957891AF2-083 GEN
Solar/Wind Harmer
0.001
970611AG2-400 GEN
Solar/Wind Harmer
3.601
274808UNIV PK N;4U
Adder
2.237
274888KELLY CRK;1U
Solar/Wind Harmer
0.181
274770LINCOLN ;1U
Adder
3.725
274771LINCOLN ;2U
Adder
3.725
972259AH1-714 GEN
Adder
8.36
942221AE2-234 GEN
Solar/Wind Harmer
0.015
970321AG2-212 GEN
Solar/Wind Harmer
1.317
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
241985AE1-237 GEN
Solar/Wind Helper
0.128
962101AG1-054 GEN
Solar/Wind Helper
0.319
23867002DVBSG1
50/50
14.099
23888502TROY G1
50/50
1.793
23888602TROY G2
50/50
1.793
241886AC2-103 GEN2
Solar/Wind Harmer
-0.001
971549AH1-272 GEN
Solar/Wind Harmer
9.983
247607V1-011 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
0.505
971771AH1-392 GEN
Solar/Wind Harmer
3.641
971769AH1-391 GEN
Solar/Wind Harmer
3.963
971567AH1-282 GEN
Solar/Wind Harmer
5.105
270071AF1-092 GEN
Solar/Wind Harmer
6.069
274728ELWOOD EC;5P
Adder
7.185
23920202STRYCT
50/50
1.866
970515AG2-329 GEN
Solar/Wind Harmer
12.364
943021AE2-325 GEN
Solar/Wind Harmer
2.053
270223U2-072_GEN1
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
6.889
971917AH1-482 GEN
Solar/Wind Harmer
4.099
941551AE2-152 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.365
945641AF1-229 GEN
Solar/Wind Harmer
0.001
971619AH1-309 GEN
Solar/Wind Harmer
1.729
965051AG1-369 GEN
Solar/Wind Harmer
1.855
270317AD1-130_GEN
Solar/Wind Harmer
0.005
971347AH1-153 GEN
Solar/Wind Harmer
5.093
972037AH1-567 GEN1
Adder
0.081
960591AF2-350 GEN
Solar/Wind Harmer
3.081
971611AH1-305 GEN
Solar/Wind Harmer
1.834
274775LINCOLN ;6U
Adder
3.725
274777LINCOLN ;8U
Adder
3.725
274675JOLIET 29;7U
Adder
13.434
274675JOLIET 29;7U
Adder
12.954
970833AG2-524 GEN
Solar/Wind Harmer
3.337
970833AG2-524 GEN
Solar/Wind Harmer
2.225
203846AF2-130 C
Solar/Wind Helper
0.241
23906502RICHG2&3
Adder
1.287
270588AE1-091_GEN
Solar/Wind Harmer
3.185
247643Z2-116 C
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0.004
276806AD2-047 C O1
Solar/Wind Harmer
1.746
274676JOLIET 29;8U
Adder
12.954
274734ELWOOD EC;8P
Adder
7.185
274736ELWOOD EC;9P
Adder
7.185
943121AE2-341 GEN
Solar/Wind Harmer
5.053
943591AF1-030 GEN
Solar/Wind Harmer
3.36
203830AF1-094 GEN
Solar/Wind Helper
0.314
23888702TROY G3
50/50
1.793
972253AH1-711 GEN
50/50
54.781
241885AC2-103 GEN1
Solar/Wind Harmer
-0.001
960841AF2-375 GEN
Solar/Wind Harmer
-0.001
247522W1-056 GEN
Solar/Wind Harmer
0.001
246936BC-WTG1
Solar/Wind Harmer
0.162
270489AE1-102 GEN1
Solar/Wind Harmer
0.518
945111AF1-176 GEN
Solar/Wind Harmer
6.861
270505AE1-170 C O1
Solar/Wind Harmer
4.035
965011AG1-365 GEN
Solar/Wind Harmer
3.601
274751CRETE EC ;1U
Adder
3.744
964861AG1-349 GEN
Solar/Wind Harmer
0
274723RIVER EC ;12
Adder
8.078
274801UNIV PARK;4U
Adder
2.578
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
3.85
274773LINCOLN ;4U
Adder
3.725
274774LINCOLN ;5U
Adder
3.725
961971AG1-040 GEN
Solar/Wind Helper
0.325
254303AC2-168 GEN
Solar/Wind Helper
0.074
23856402BAYSG1
50/50
1.208
241858AF1-205_GEN
Solar/Wind Harmer
3.754
241808AF1-120 C
Solar/Wind Harmer
0.003
270541AE2-072 C
Solar/Wind Harmer
0.008
270404AC1-167 GEN
Solar/Wind Harmer
0.002
247604X1-042
Adder
0.252
270247TR4_N_V136
Solar/Wind Harmer
0.024
970031AG2-029 GEN
Solar/Wind Harmer
2.401
970349AG2-230 GEN
Solar/Wind Harmer
5.093
270391AF1-285 GEN3
Solar/Wind Harmer
0.22
274752CRETE EC ;2U
Adder
3.744
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
274826FISK ;BP
Adder
4.849
972228AH1-698 GEN2
Adder
1.631
939351AE1-166 GEN
Solar/Wind Harmer
0
274730ELWOOD EC;6P
Adder
7.185
970707AG2-453 GEN
Solar/Wind Harmer
9.96
970513AG2-328 GEN
Solar/Wind Harmer
1.317
970517AG2-330 GEN
Solar/Wind Harmer
7.901
276694AA1-018 GEN2
Solar/Wind Harmer
0
254305AE2-115 C
Solar/Wind Helper
0.109
972301AH1-735 GEN
Adder
6.449
270361_3
Solar/Wind Harmer
4.19
944231AF1-091 GEN
Solar/Wind Harmer
1.193
270063AE2-323 C
Solar/Wind Harmer
0.003
270462AD2-086
Solar/Wind Harmer
0.007
274754CRETE EC ;4U
Adder
3.744
958381AF2-132 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
7.185
274674JOLIET 9 ;6U
Adder
6.729
970245AG2-165 GEN
Solar/Wind Harmer
1.317
957201AF2-014 GEN
Solar/Wind Harmer
0
971989AH1-539 GEN
Solar/Wind Harmer
1.655
270302AB2-170 GEN
Solar/Wind Harmer
0.002
971653AH1-327 GEN
Solar/Wind Harmer
0.5
963791AG1-232 GEN
Solar/Wind Harmer
4.498
270536AF1-215 GEN2
Solar/Wind Harmer
0.004
274811UNIV PK N;7U
Adder
2.247
958391AF2-133 GEN
Solar/Wind Harmer
0
274827FISK ;RP
Adder
3.437
972227AH1-698 GEN1
Adder
1.148
274735ELWOOD EC;4P
Adder
7.184
274744AC1-111 GEN8
Adder
2.415
270024AE2-089 GEN
Solar/Wind Harmer
0.003
241997AF1-093 GEN
Solar/Wind Helper
0.127
203804AE2-113_GEN
Solar/Wind Helper
0.842
24189902OREGON_CT2
50/50
2.665
241840AF1-064_GEN
Solar/Wind Harmer
0.004
23906402RICHG1
Adder
1.29
23906502RICHG2&3
Adder
1.287
965421AG1-410 GEN
Solar/Wind Harmer
11.847
270449AD2-020 GEN
Solar/Wind Harmer
0
24695305TIMB G C
Solar/Wind Harmer
0.001
24639705ELKHART HY
Adder
0.082
247521TR3_G114
Solar/Wind Harmer
0.135
270246TR4_N_V150
Solar/Wind Harmer
0.024
270055AF2-134 C O1
Solar/Wind Harmer
0.002
274812UNIV PK N;8U
Adder
2.247
276164X3-005 C
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
0.322
274676JOLIET 29;8U
Adder
13.434
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
2.415
203835AF1-098 GEN
Solar/Wind Helper
1.28
203860AG1-193 C
Solar/Wind Helper
0.145
241966AE1-183 GEN
Solar/Wind Helper
0.127
241807AE2-176_GEN
Solar/Wind Helper
0.767
24190002OREGON_ST1
50/50
3.585
971677AH1-339 GEN
Solar/Wind Harmer
0.599
965681AG1-436 GEN
Solar/Wind Harmer
4.266
270227U2-072_GEN3
Solar/Wind Harmer
0
270228U2-072_GEN4
Solar/Wind Harmer
0
270231U2-072_GEN5
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
203980AG1-197 GEN
Solar/Wind Helper
0.242
203979AG1-198 GEN
Solar/Wind Helper
0.188
241801AE1-079 GEN
Solar/Wind Helper
0.128
990142J1224
External Queue
13.159761428833008
991177J1571 G
External Queue
15.044508934020996
991182J1586 G
External Queue
24.65229034423828
990527J1329
External Queue
1.8002409934997559
NYPJM->LTFIMP_NY
CLTF
1.97
LGEELTFEXP_LGEE->PJM
CLTF
1.929
WECLTFEXP_WEC->PJM
CLTF
1.6
AG2-052LTFEXP_AG2-052->PJM
LTF
0.103
AH1-155LTFEXP_AH1-155->PJM
LTF
0.155
CBM West 1LTFEXP_CBM-W1->PJM
CBM
91.578
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.528
MECLTFEXP_MEC->PJM
CLTF
6.231
SIGELTFEXP_SIGE->PJM
CLTF
0.161
LAGNLTFEXP_LAGN->PJM
CLTF
4.752
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.085
TVALTFEXP_TVA->PJM
CLTF
2.153
CPLELTFEXP_CPLE->PJM
CLTF
0.308
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.025

Details for AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line l/o ATSI_P1-2_OEC-345-809_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_OEC-345-809_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:117.76 %
Rating:1798.0 MVA
Rating Type:B
MVA to Mitigate:2117.36
MW Contribution:0.51
Bus #Bus NameTypeMW Contribution
23929302BS-PKR
50/50
2.251
958321AF2-126 GEN
Solar/Wind Harmer
1.147
270575GUS2 35KV
Solar/Wind Harmer
4.647
970217AG2-149 GEN
Solar/Wind Harmer
4.178
270258AD1-119 GEN
Solar/Wind Harmer
0.001
270491AE1-102 GEN2
Solar/Wind Harmer
0.52
270191TR4_S_V150
Solar/Wind Harmer
0
24642205MAYFLWER
Adder
0.337
959331AF2-224 GEN
Solar/Wind Harmer
2.518
274753CRETE EC ;3U
Adder
3.712
964401AG1-302 GEN
Solar/Wind Harmer
0
972038AH1-567 GEN2
Adder
0.16
971617AH1-308 GEN
Solar/Wind Harmer
2.511
962511AG1-100 GEN
Solar/Wind Helper
0.336
959441AF2-235 GEN
Solar/Wind Helper
0.145
20334926Z1-069 C
Solar/Wind Helper
0.635
23888802TROY G4
50/50
1.734
247620Y3-023
Adder
0.245
270526AF1-158 GEN
Solar/Wind Harmer
0.004
24441505OLIV SLR
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
3.098
971231AH1-075 GEN
Solar/Wind Harmer
0.372
276843GEN-1.7
Solar/Wind Harmer
0.099
958011AF2-095 GEN
Solar/Wind Harmer
4.4
946381AF1-302 GEN
Solar/Wind Helper
0.103
972211AH1-690 GEN
50/50
274.788
970817AG2-515 GEN
Solar/Wind Harmer
10.276
945411AF1-206 GEN
Solar/Wind Harmer
-0.001
270499AE1-146 GEN
Solar/Wind Harmer
0.029
270297AD1-101 GEN
Solar/Wind Harmer
0.001
965041AG1-368 GEN
Solar/Wind Harmer
3.755
24191202EL_AA1-006
Adder
0.112
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
270578AF1-285 GEN2
Solar/Wind Harmer
0.222
274814UNIV PK N;0U
Adder
2.248
274807UNIV PK N;3U
Adder
2.243
274805UNIV PK N;1U
Adder
2.233
274776LINCOLN ;7U
Adder
3.695
274687WILL CNTY;4U
Adder
12.162
274687WILL CNTY;4U
Adder
12.162
274731ELWOOD EC;2P
Adder
7.127
274733ELWOOD EC;3P
Adder
7.127
241982AE2-343 S C
Solar/Wind Helper
0.116
254304AE2-114 C
Solar/Wind Helper
0.111
23920202STRYCT
50/50
1.883
970515AG2-329 GEN
Solar/Wind Harmer
12.533
943021AE2-325 GEN
Solar/Wind Harmer
2.028
270223U2-072_GEN1
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
6.828
971917AH1-482 GEN
Solar/Wind Harmer
4.065
941551AE2-152 GEN
Solar/Wind Harmer
0
945641AF1-229 GEN
Solar/Wind Harmer
0.001
971619AH1-309 GEN
Solar/Wind Harmer
1.709
965051AG1-369 GEN
Solar/Wind Harmer
1.865
270317AD1-130_GEN
Solar/Wind Harmer
0.005
971347AH1-153 GEN
Solar/Wind Harmer
5.047
972037AH1-567 GEN1
Adder
0.081
971611AH1-305 GEN
Solar/Wind Harmer
1.819
960591AF2-350 GEN
Solar/Wind Harmer
3.056
274775LINCOLN ;6U
Adder
3.695
274777LINCOLN ;8U
Adder
3.695
274675JOLIET 29;7U
Adder
13.327
274675JOLIET 29;7U
Adder
12.851
970833AG2-524 GEN
Solar/Wind Harmer
3.311
970833AG2-524 GEN
Solar/Wind Harmer
2.207
203846AF2-130 C
Solar/Wind Helper
0.244
270541AE2-072 C
Solar/Wind Harmer
0.008
270404AC1-167 GEN
Solar/Wind Harmer
0.002
247604X1-042
Adder
0.248
270247TR4_N_V136
Solar/Wind Harmer
0.024
970031AG2-029 GEN
Solar/Wind Harmer
2.384
970349AG2-230 GEN
Solar/Wind Harmer
5.047
270391AF1-285 GEN3
Solar/Wind Harmer
0.222
270377AD1-106 GEN
Solar/Wind Harmer
1.233
274752CRETE EC ;2U
Adder
3.712
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
274826FISK ;BP
Adder
4.81
972228AH1-698 GEN2
Adder
1.618
939351AE1-166 GEN
Solar/Wind Harmer
0
274730ELWOOD EC;6P
Adder
7.127
970707AG2-453 GEN
Solar/Wind Harmer
9.881
970513AG2-328 GEN
Solar/Wind Harmer
1.307
970517AG2-330 GEN
Solar/Wind Harmer
7.843
254305AE2-115 C
Solar/Wind Helper
0.111
24189802OREGON_CT1
50/50
2.6
961051AF2-396 GEN
Solar/Wind Harmer
7.707
961051AF2-396 GEN
Solar/Wind Harmer
5.138
270216AD2-079_GEN
Solar/Wind Harmer
0.001
970627AG2-408 GEN
Solar/Wind Harmer
1.079
270224U2-072_GEN2
Solar/Wind Harmer
0
274803UNIV PARK;6U
Adder
2.566
274887GEN-1.85
Solar/Wind Harmer
0.08
274674JOLIET 9 ;6U
Adder
6.676
203947AF1-006 C
Solar/Wind Helper
0.375
241967AE2-285_GEN
Solar/Wind Helper
0.334
23856402BAYSG1
50/50
1.279
241858AF1-205_GEN
Solar/Wind Harmer
3.794
241808AF1-120 C
Solar/Wind Harmer
0.003
972301AH1-735 GEN
Adder
6.527
270361_3
Solar/Wind Harmer
4.647
944231AF1-091 GEN
Solar/Wind Harmer
1.197
270063AE2-323 C
Solar/Wind Harmer
0.003
270462AD2-086
Solar/Wind Harmer
0.008
274754CRETE EC ;4U
Adder
3.712
958381AF2-132 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
7.127
274674JOLIET 9 ;6U
Adder
6.676
970245AG2-165 GEN
Solar/Wind Harmer
1.307
23906502RICHG2&3
Adder
1.303
270588AE1-091_GEN
Solar/Wind Harmer
3.347
247643Z2-116 C
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0.004
276806AD2-047 C O1
Solar/Wind Harmer
1.732
274676JOLIET 29;8U
Adder
12.851
274734ELWOOD EC;8P
Adder
7.127
274736ELWOOD EC;9P
Adder
7.127
203830AF1-094 GEN
Solar/Wind Helper
0.318
24189902OREGON_CT2
50/50
2.548
241840AF1-064_GEN
Solar/Wind Harmer
0.004
23906402RICHG1
Adder
1.305
23906502RICHG2&3
Adder
1.303
241807AE2-176_GEN
Solar/Wind Harmer
0.004
270428AC2-015 C
Solar/Wind Harmer
0.002
965421AG1-410 GEN
Solar/Wind Harmer
11.884
270449AD2-020 GEN
Solar/Wind Harmer
0
24695305TIMB G C
Solar/Wind Harmer
0.001
247521TR3_G114
Solar/Wind Harmer
0.136
270246TR4_N_V150
Solar/Wind Harmer
0.024
24639705ELKHART HY
Adder
0.081
270055AF2-134 C O1
Solar/Wind Harmer
0.002
274812UNIV PK N;8U
Adder
2.229
276164X3-005 C
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
0.319
274676JOLIET 29;8U
Adder
13.326
274871GR RIDGE ;2U
Solar/Wind Harmer
0
203835AF1-098 GEN
Solar/Wind Helper
1.297
203860AG1-193 C
Solar/Wind Helper
0.147
241966AE1-183 GEN
Solar/Wind Helper
0.128
24190002OREGON_ST1
50/50
3.428
971677AH1-339 GEN
Solar/Wind Harmer
0.654
965681AG1-436 GEN
Solar/Wind Harmer
4.224
270227U2-072_GEN3
Solar/Wind Harmer
0
270228U2-072_GEN4
Solar/Wind Harmer
0
270231U2-072_GEN5
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
203980AG1-197 GEN
Solar/Wind Helper
0.245
203979AG1-198 GEN
Solar/Wind Helper
0.191
241801AE1-079 GEN
Solar/Wind Helper
0.13
971989AH1-539 GEN
Solar/Wind Harmer
1.766
957201AF2-014 GEN
Solar/Wind Harmer
0
270302AB2-170 GEN
Solar/Wind Harmer
0.002
971653AH1-327 GEN
Solar/Wind Harmer
0.505
963791AG1-232 GEN
Solar/Wind Harmer
4.499
270536AF1-215 GEN2
Solar/Wind Harmer
0.004
274811UNIV PK N;7U
Adder
2.229
958391AF2-133 GEN
Solar/Wind Harmer
0
274827FISK ;RP
Adder
3.409
972227AH1-698 GEN1
Adder
1.139
274735ELWOOD EC;4P
Adder
7.127
270024AE2-089 GEN
Solar/Wind Harmer
0.003
241997AF1-093 GEN
Solar/Wind Helper
0.128
203804AE2-113_GEN
Solar/Wind Helper
0.852
241832AE2-181_GEN
Solar/Wind Harmer
0.003
24441205WTRV SLR C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
3.081
965021AG1-366 GEN
Solar/Wind Harmer
1.199
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270043AE2-236 GEN
Solar/Wind Harmer
2.178
274724RIVER EC ;11
Adder
7.915
274802UNIV PARK;5U
Adder
2.566
274800UNIV PARK;3U
Adder
2.557
970941AG2-585 GEN
Solar/Wind Harmer
3.82
274772LINCOLN ;3U
Adder
3.695
276897AD1-100 C
Solar/Wind Harmer
0.004
276893AG1-478 C
Solar/Wind Harmer
0.12
274729ELWOOD EC;1P
Adder
7.127
23867002DVBSG1
50/50
12.718
23888502TROY G1
50/50
1.734
23888602TROY G2
50/50
1.734
241886AC2-103 GEN2
Solar/Wind Harmer
-0.001
971549AH1-272 GEN
Solar/Wind Harmer
9.816
247607V1-011 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
0.507
971771AH1-392 GEN
Solar/Wind Harmer
3.604
971769AH1-391 GEN
Solar/Wind Harmer
3.923
971567AH1-282 GEN
Solar/Wind Harmer
5.235
270071AF1-092 GEN
Solar/Wind Harmer
6.048
274728ELWOOD EC;5P
Adder
7.127
241996AE2-282_GEN
Solar/Wind Harmer
0.005
970621AG2-405 GEN
Solar/Wind Harmer
0.864
970623AG2-406 GEN
Solar/Wind Harmer
0.785
270007AE1-245 C
Solar/Wind Harmer
0.001
246938BC-WTG3
Solar/Wind Harmer
0.145
246937BC-WTG2
Solar/Wind Harmer
0.162
957891AF2-083 GEN
Solar/Wind Harmer
0.001
970611AG2-400 GEN
Solar/Wind Harmer
3.597
274808UNIV PK N;4U
Adder
2.219
274888KELLY CRK;1U
Solar/Wind Harmer
0.179
274770LINCOLN ;1U
Adder
3.695
274771LINCOLN ;2U
Adder
3.695
942221AE2-234 GEN
Solar/Wind Harmer
0.015
972259AH1-714 GEN
Adder
8.293
970321AG2-212 GEN
Solar/Wind Harmer
1.307
241985AE1-237 GEN
Solar/Wind Helper
0.129
962101AG1-054 GEN
Solar/Wind Helper
0.322
23888702TROY G3
50/50
1.734
972253AH1-711 GEN
50/50
52.952
241885AC2-103 GEN1
Solar/Wind Harmer
-0.001
960841AF2-375 GEN
Solar/Wind Harmer
-0.002
247522W1-056 GEN
Solar/Wind Harmer
0.001
246936BC-WTG1
Solar/Wind Harmer
0.162
270489AE1-102 GEN1
Solar/Wind Harmer
0.52
945111AF1-176 GEN
Solar/Wind Harmer
6.783
270505AE1-170 C O1
Solar/Wind Harmer
3.988
965011AG1-365 GEN
Solar/Wind Harmer
3.597
970905AG2-564 GEN
Solar/Wind Harmer
1.725
274751CRETE EC ;1U
Adder
3.712
964861AG1-349 GEN
Solar/Wind Harmer
0
274723RIVER EC ;12
Adder
8.011
274801UNIV PARK;4U
Adder
2.557
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
3.82
274773LINCOLN ;4U
Adder
3.695
274774LINCOLN ;5U
Adder
3.695
961971AG1-040 GEN
Solar/Wind Helper
0.329
254303AC2-168 GEN
Solar/Wind Helper
0.075
990142J1224
External Queue
12.759525299072266
991177J1571 G
External Queue
14.724894523620605
991182J1586 G
External Queue
23.868927001953125
990527J1329
External Queue
1.745489239692688
NYPJM->LTFIMP_NY
CLTF
1.99
LGEELTFEXP_LGEE->PJM
CLTF
1.931
WECLTFEXP_WEC->PJM
CLTF
1.588
AG2-052LTFEXP_AG2-052->PJM
LTF
0.102
AH1-155LTFEXP_AH1-155->PJM
LTF
0.153
CBM West 1LTFEXP_CBM-W1->PJM
CBM
89.942
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.514
MECLTFEXP_MEC->PJM
CLTF
6.19
SIGELTFEXP_SIGE->PJM
CLTF
0.161
LAGNLTFEXP_LAGN->PJM
CLTF
4.735
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.079
TVALTFEXP_TVA->PJM
CLTF
2.148
CPLELTFEXP_CPLE->PJM
CLTF
0.305
CBM West 2LTFEXP_CBM-W2->PJM
CBM
37.878
CONTINGENCY 'AP_P1-2_MP-500-028_SRT-A'
 DISCONNECT BRANCH FROM BUS 235111 TO BUS 235117 CKT 1   /*01 502 J     500.0 - 01KAMMER     500.0
 DISCONNECT BRANCH FROM BUS 235117 TO BUS 242925 CKT 1   /*01KAMMER     500.0 - 05KAMMER     765.0
END
CONTINGENCY 'AP_P1-3_MP-765-502T_SRT-A'
 DISCONNECT BRANCH FROM BUS 235117 TO BUS 242925 CKT 1   /*01KAMMER     500.0 - 05KAMMER     765.0
END
CONTINGENCY 'AP_P1-2_MP-500-007A_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235235 CKT 1   /*01BELMNT     500.0 - 01FLINTRUN   500.0
END
CONTINGENCY 'AP_P1-2_MP-500-008A_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235235 TO BUS 235107 CKT 1          /*01FLINTRUN   500.0 - 01HARRSN     500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235107 TO BUS 235703 CKT 1 /*01HARRSN     500.0 - 01WYLIE R    500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235107 TO BUS 235703 CKT 1 /*01HARRSN     500.0 - 01WYLIE R    500.0
END
CONTINGENCY 'ATSI_P1-2_TE-345-602_SRT-A'
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 238889 CKT 1   /*02DAV-BE     345.0 - 02LEMOYN     345.0
END
CONTINGENCY 'ATSI_P1-2_OEC-345-825_SRT-A'
 DISCONNECT BRANCH FROM BUS 241877 TO BUS 238569 CKT 1   /*AC2-103 TAP  345.0 - 02BEAVER     345.0
END
CONTINGENCY 'ATSI_P1-2_OEC-345-824_SRT-A'
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 241877 CKT 1   /*02DAV-BE     345.0 - AC2-103 TAP  345.0
END
CONTINGENCY 'ATSI_P1-2_OEC-345-810_SRT-A'
 DISCONNECT BRANCH FROM BUS 239289 TO BUS 238654 CKT 1   /*02HAYES      345.0 - 02DAV-BE     345.0
END
CONTINGENCY 'ATSI_P1-2_OEC-345-809_SRT-A'
 DISCONNECT BRANCH FROM BUS 239289 TO BUS 238569 CKT 1   /*02HAYES      345.0 - 02BEAVER     345.0
END
CONTINGENCY 'ATSI_P1-2_TE-345-601_SRT-A'
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 238563 CKT 1   /*02DAV-BE     345.0 - 02BAY SH     345.0
END
CONTINGENCY 'AP_P1-3_MP-765-501T_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1   /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                   /*05BELMON     765.0
END
CONTINGENCY 'AEP_P1-2_#706_SRT-A'
 OPEN BRANCH FROM BUS 242922 TO BUS 290622 CKT 1    /*05FLTLCK     765.0 - 05GAVIN_RF   765.0
 OPEN BRANCH FROM BUS 242923 TO BUS 290622 CKT Z1   /*05GAVIN      765.0 - 05GAVIN_RF   765.0
END
CONTINGENCY 'AEP_P1-2_#708_11_SRT-A'
 OPEN BRANCH FROM BUS 242516 TO BUS 242923 CKT 1   /*05MOUNTN     765.0 - 05GAVIN      765.0
END
CONTINGENCY 'AEP_P1-2_#728_584_SRT-A'
 OPEN BRANCH FROM BUS 242939 TO BUS 243458 CKT 1   /*05MARYSV     345.0 - 05HYATT      345.0
END
235102 to 235235 ckt 1
235235 to 235107 ckt 1
235117 to 235111 ckt 1
238563 to 238654 ckt 1
238654 to 239289 ckt 1
238654 to 241877 ckt 1
239289 to 238569 ckt 1
238889 to 238654 ckt 1
242925 to 235117 ckt 1
290623 to 242925 ckt Z1
242926 to 246751 ckt 1
242928 to 290620 ckt Z1
290620 to 242926 ckt 1
241877 to 238569 ckt 1

Winter Peak Analysis

The New Service Request AH1-327 was evaluated as a 0.0 MW (8.44 MW Capacity) injection in the AEP area.

AH1-327 was evaluated as part of a plant. The plant consists of AH1-327. The total Energy output of the plant was evaluated at its maximum seasonal capability of 250.0 MW (0.0 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

(No impacts were found for this analysis)

Light Load Analysis

The New Service Request AH1-327 was evaluated as a 0.0 MW injection

AH1-327 was evaluated as part of a plant. The plant consists of AH1-327. The total Energy output of the plant was evaluated at its maximum seasonal capability of 250.0 MW (0.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

(No impacts were found for this analysis)

Short Circuit Analysis

Short Circuit analysis is not performed as part of the Phase I System Impact Study. Short Circuit analysis will commence in the Phase II System Impact Study.

Stability Analysis

Stability Analysis is Not Required.

Reactive Power Analysis

Reactive Power Analysis was not performed. This project is responsible for meeting all applicable power factor requirements.

Steady-State Voltage Analysis

Steady State Voltage Analysis is Not Required.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-018Powerton-Goodings GroveIn Service
AA1-095Halfway-Marlowe 34.5kVIn Service
AA2-184Atlantic-Red Bank 34kVIn Service
AB1-001Absecon 12 kVIn Service
AB1-006Meadow Lake 345kVIn Service
AB1-096Carroll-Mt. Airy 34.5kVIn Service
AB1-124Carroll-Monocacy 34.5kVPartially in Service - Under Construction
AB1-125Carroll-Monocacy 34.5kVIn Service
AB1-127St. Thomas-Guilford 34.5kVIn Service
AB1-128St. Thomas-Mercersburg 34.5kVIn Service
AB1-138Navy 34.5kVIn Service
AB1-139Metuchen 26kVIn Service
AB1-141Church-Wye Mills 138 kV IIn Service
AB1-142Church-Wye Mills 138 kV IIIn Service
AB1-176Price 25kV IIEngineering & Procurement
AB2-029Remington 34.5kVIn Service
AB2-032Church-Wye Mills 138 kVIn Service
AB2-037Keeney-Steele 230kVUnder Construction
AB2-049Gloucester Township 12kVIn Service
AB2-067Kammer-Vassell 765kVIn Service
AB2-070Mt. Pulaski-BrokawIn Service
AB2-093Ormet 138kVIn Service
AB2-133Chestertown 69kVUnder Construction
AB2-135Church-Kent 69kVIn Service
AB2-136Cambridge-West Cambridge 69kVUnder Construction
AB2-153Church-Wye Mills 138 kVIn Service
AB2-157Prince George's County 12kVIn Service
AB2-170East Lima-Marysville 345kVIn Service
AB2-179Townsend 138kVIn Service
AC1-001Delano 138kVIn Service
AC1-010Gloucester 26kVUnder Construction
AC1-017Levittown 13 kVIn Service
AC1-030Cinnaminson 13kVIn Service
AC1-033Kewanee 138 kVIn Service
AC1-044Kammer-Vassell 765kVIn Service
AC1-053Lanesville-BrokawPartially in Service - Under Construction
AC1-068Atlanta 69kV IIn Service
AC1-069Atlanta 69kV IIIn Service
AC1-074Jacksonville-Renaker 138kV IIn Service
AC1-076Locust Grove-Paytes 115kVIn Service
AC1-078Beatty-London 138kVIn Service
AC1-082Ravenswood-Hemlock 69kVUnder Construction
AC1-085Stuart-Clinton 345kVIn Service
AC1-089Hillsboro-Wildcat 138kVIn Service
AC1-091Cedar Creek 138kV IEngineering & Procurement
AC1-092Cedar Creek 138kV IIEngineering & Procurement
AC1-093Cedar Creek 138kV IIIEngineering & Procurement
AC1-094Cedar Creek 138kV IVEngineering & Procurement
AC1-101Johns Creek-Excel 138kV ISuspended
AC1-102Johns Creek-Excel 138kV IISuspended
AC1-111Aurora 138kVIn Service
AC1-120Mitchell-Mountain Run 115kVEngineering & Procurement
AC1-121Mitchell-Mountain Run 115kVEngineering & Procurement
AC1-141Cook-East Elkhart 345kVIn Service
AC1-158Spotsylvania 500kVIn Service
AC1-165Atlanta 69kV IIIIn Service
AC1-166Atlanta 69kV IVIn Service
AC1-167Mark Center 69kVUnder Construction
AC1-168Kewanee-StreatorSuspended
AC1-174Losantville 345kVIn Service
AC1-175Losantville 345kVIn Service
AC1-188Rio-Lick 138kVEngineering & Procurement
AC1-194Elk 138kVActive
AC1-214Crescent RidgeIn Service
AC2-015Chatfield-Howard 138kVPartially in Service - Under Construction
AC2-023Hebron 69kVEngineering & Procurement
AC2-029Circleville 138kVSuspended
AC2-044Maddox Creek 345kVSuspended
AC2-059Biers Run-Circleville 138kVIn Service
AC2-060Buckskin 69kVIn Service
AC2-061Hillsboro-Clinton 138kVIn Service
AC2-067Camden-Crystal I 69kVEngineering & Procurement
AC2-068Camden-Crystal II 69kVEngineering & Procurement
AC2-075Jacksonville-Renaker 138 kVIn Service
AC2-088S. Bethel-Brown 69kVIn Service
AC2-090Losantville 345kVIn Service
AC2-103Beaver-Davis Besse 345 kV IEngineering & Procurement
AC2-111College Corner 138kVEngineering & Procurement
AC2-120Ripley 69kVIn Service
AC2-136East Hagerstown 12kVUnder Construction
AC2-157Sullivan 345 kVUnder Construction
AC2-168Clinton 23kVIn Service
AC2-176Jay 138 kVIn Service
AC2-186Harrington 25kVUnder Construction
AC2-187Harrington 69kVUnder Construction
AC2-188Harrington 69 kVUnder Construction
AC2-195Galion-Roberts South 138 kVUnder Construction
AD1-013Twombly Road 138kVEngineering & Procurement
AD1-020Hunterstown-Lincoln 115 kVIn Service
AD1-060Mercersburg-Milnor 34.5 kVIn Service
AD1-061McConnelsburg-Mercersburg 34 kVIn Service
AD1-100Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVUnder Construction
AD1-101Continental 69 kVIn Service
AD1-106North Waldo-Wild Creek 138 kVSuspended
AD1-115Mountain Run-Mitchell 115 kVEngineering & Procurement
AD1-119Payne 69 kVIn Service
AD1-128Modoc-Delaware 138 kVPartially in Service - Under Construction
AD1-130Hardin Switch 345 kVIn Service
AD1-136South Bethel-Brown 69 kVIn Service
AD1-140Greene-Clark 138 kVEngineering & Procurement
AD1-155Meadow Brook-Strasburg 138 kVIn Service
AD2-009McConnellsburg 138 kVIn Service
AD2-016Biers Run-Circleville 138 kVIn Service
AD2-020Valley 138 kVEngineering & Procurement
AD2-027Camden Switch 26 kVIn Service
AD2-031Martinsville-Wilmington 69 kVIn Service
AD2-038Powerton-Nevada 345 kVUnder Construction
AD2-042Camden Switch 26 kV IIIn Service
AD2-047Davis Creek 138 kVSuspended
AD2-048Cynthia-Headquarters 69 kVUnder Construction
AD2-058St. Barnabas 13 kVIn Service
AD2-060Davis Creek 138kVEngineering & Procurement
AD2-065Atco 12 kVIn Service
AD2-066Mazon-Crescent Ridge 138 kVEngineering & Procurement
AD2-067Centerburg 138kVEngineering & Procurement
AD2-070Gilbert-Morris Park 34.5kVIn Service
AD2-071Strawton-Deer Creek 138 kVSuspended
AD2-079Capitol Ave 34.5kVIn Service
AD2-086Hardin Switch 345 kVIn Service
AD2-091Hardin Tap 345kVSuspended
AD2-092Marysville 345kVUnder Construction
AD2-093Marysville 345kVUnder Construction
AD2-096Marysville 345kVSuspended
AD2-100Kincaid-Pana 345 kVSuspended
AD2-115Lyons-Moselem 69kVIn Service
AD2-116Hokes-Grantley 69 kVIn Service
AD2-131Kincaid-Pana 345kVSuspended
AD2-133Eagle Valley 115kVIn Service
AD2-134Shady OaksPartially in Service - Under Construction
AD2-135Williamstown 12kVPartially in Service - Under Construction
AD2-163Broadview-Tangy 138 kVIn Service
AD2-172Lena 138kVIn Service
AD2-180Elk Garden-Parr Run 138kVIn Service
AE1-040Greenfield 69 kVIn Service
AE1-041Edison 4kVIn Service
AE1-071Shade Gap-Roxbury 115 kVIn Service
AE1-079Maysville-Sharon 69 kVUnder Construction
AE1-081Landing 12.47 kVIn Service
AE1-090Hardin Switch 345 kVIn Service
AE1-091West Newton-Lynn 138 kVSuspended
AE1-092Blue Jacket-Kirby 138 kVActive
AE1-101McConnellsburg-Texas Eastern 138 kVIn Service
AE1-102Maddox Creek 345 kVSuspended
AE1-109Frenchs Mill 34 kVIn Service
AE1-113Mole Creek 345 kVEngineering & Procurement
AE1-114Maryland-Lancaster 138 kVActive
AE1-142Manitou-Pleasant Plains 34.5 kVIn Service
AE1-146Ebersole #2-Fostoria Central 138 kVUnder Construction
AE1-156Quakertown Solar II 34.5 kVPartially in Service - Under Construction
AE1-163Powerton-Nevada 345 kVEngineering & Procurement
AE1-166Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE1-170Kenzie Creek-Colby 138 kVSuspended
AE1-172Loretto-Wilton CenterActive
AE1-183Maysville-McDowell 69 kVEngineering & Procurement
AE1-185Hokes-Jackson 69 kVIn Service
AE1-196Hokes-Jackson 69 kV IIIn Service
AE1-205McLean 345 kVEngineering & Procurement
AE1-207Mississinewa-Gaston 138 kVSuspended
AE1-208Delaware-Van Buren 138 kVSuspended
AE1-209Desoto 345 kVSuspended
AE1-210Desoto 345 kVSuspended
AE1-227South Cumberland 69 kVSuspended
AE1-229Deepwater-Upper Pittsgrove 138 kVSuspended
AE1-237Andover (Maysville) 69kV IUnder Construction
AE1-245Haviland 138 kVUnder Construction
AE2-035Lena 138 kVIn Service
AE2-045Olive-Reynolds 345 kVEngineering & Procurement
AE2-048Muskingum-W. Millersport 345 kVEngineering & Procurement
AE2-054Warfordsburg 34 kVIn Service
AE2-072East Leipsic-Richland 138 kVIn Service
AE2-089Pennville-Adams 138 kVEngineering & Procurement
AE2-113Farmers Valley-Ridgeway 115 kVUnder Construction
AE2-114Midland 23 kV IIn Service
AE2-115Midland 23 kV IIIn Service
AE2-117ABW Tap-Alexandria 46 kVSuspended
AE2-125Stahlstown-Ligonier 25 kVIn Service
AE2-126Dubois-Curwensville 34.5 kVIn Service
AE2-129Philipsburg-Clarence 34.5 kVIn Service
AE2-131Philipsburg-Karthaus 34.5Under Construction
AE2-136Muskingum River-W. Millersport 345 kVEngineering & Procurement
AE2-148Beatty-Greene 345 kVIn Service
AE2-152Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE2-169Delaware-Van Buren 138 kVSuspended
AE2-172Mississinewa-Gaston 138 kVSuspended
AE2-173McLean 345 kVActive
AE2-175Jackson-Long Pond 69 kVPartially in Service - Under Construction
AE2-176Groton 138 kV SolarIn Service
AE2-181Snyder 69kVUnder Construction
AE2-206East Sidney-Quincy 138 kVIn Service
AE2-214Cole 345 kVEngineering & Procurement
AE2-216Hardin Switch 345 kVEngineering & Procurement
AE2-217East Springfield-London 138 kVEngineering & Procurement
AE2-219Bluff Point-Randolph 138 kVSuspended
AE2-220Losantville 345 kVEngineering & Procurement
AE2-221Clinton-Stuart 345 kVUnder Construction
AE2-223McLean 345 kVActive
AE2-224Bear Rock-Johnstown 230 kVIn Service
AE2-226Millville-Old Chapel 138 kVEngineering & Procurement
AE2-230Bartonsville-Meadow Brook 138 kVIn Service
AE2-234Liberty Center-Buckeye Tap 69 kVEngineering & Procurement
AE2-236Columbia-Northeast 138 kVSuspended
AE2-255Molecreek 345 kVEngineering & Procurement
AE2-261Kincaid-Pana 345 kVActive
AE2-262Moshannon-Milesburg 230 kVEngineering & Procurement
AE2-263Moshannon-Milesburg 230 kV IIEngineering & Procurement
AE2-267Woodsdale 345 kVEngineering & Procurement
AE2-281Powerton-Nevada 345 kVEngineering & Procurement
AE2-282East Fayette 138 kVIn Service
AE2-285Maysville 69 kVEngineering & Procurement
AE2-297Madison-Tanners Creek 138 kVIn Service
AE2-305Givens-Mechanicsburg 138 kVEngineering & Procurement
AE2-309Carlos Junction-Lonaconing 34.5 kVIn Service
AE2-315Yankee Tap 69 kVIn Service
AE2-318Ford-Cedarville 138 kVSuspended
AE2-321Belvidere-Marengo 138 kVActive
AE2-323Twin Branch-Guardian 138 kVUnder Construction
AE2-325Valley 138 kVActive
AE2-341Sandwich-Plano 138 kVActive
AE2-342Woodstock 69 kVEngineering & Procurement
AE2-343Andover (Maysville) 69 kV IIUnder Construction
AF1-006Fairview East 34.5 kVIn Service
AF1-007Indian River 230 kV ISuspended
AF1-021Bethelboro-Connellsville #1 25 kVIn Service
AF1-022Lake Lynn-Uniontown 25 kVIn Service
AF1-030Sandwich-Plano 138 kVActive
AF1-039Listonburg-Highpoint 24.9 kVIn Service
AF1-045Cedarville-Ford 138 kVSuspended
AF1-051Gavin 765 kVIn Service
AF1-053Givens-Mechanicsburg 138 kVEngineering & Procurement
AF1-054Givens-Mechanicsburg 138 kVEngineering & Procurement
AF1-062Jug Street 138 kVEngineering & Procurement
AF1-064Weston 69 kVUnder Construction
AF1-078East Sidney-Quincy 138 kVIn Service
AF1-086Madera-Westover South 115 kVUnder Construction
AF1-088Sullivan 345 kVActive
AF1-090Kincaid-PanaEngineering & Procurement
AF1-091Varner - Sowers 138 kVEngineering & Procurement
AF1-092Huntington Jct. 138 kVSuspended
AF1-093Henderson-Stoneboro 69 kVEngineering & Procurement
AF1-094Union City-Cambridge Springs 34.5 kVEngineering & Procurement
AF1-098Four Mile Jct-Corry East 115 kVEngineering & Procurement
AF1-118Sorenson-Desoto 345 kVEngineering & Procurement
AF1-119Keystone-Desoto 345 kVEngineering & Procurement
AF1-120East Fayette 2 138 kVIn Service
AF1-122Cardington-Liberty 69 kVSuspended
AF1-130Inez 138 kVSuspended
AF1-134Philipsburg-Madera 34.5 kVEngineering & Procurement
AF1-136Warfordsburg-Purcell Junction 34.5 kVEngineering & Procurement
AF1-140Claysburg 23 kVEngineering & Procurement
AF1-143Lick Run 115 kVEngineering & Procurement
AF1-147Poland Rd-Runway DP 230kVUnder Construction
AF1-153Motion-Ridgeway 46 kVSuspended
AF1-158Edison-Gravel Pit 138 kVIn Service
AF1-161Valley 138 kVActive
AF1-162Inez 138 kVEngineering & Procurement
AF1-176Corey 138 kVActive
AF1-202Keystone-Desoto 345 kVUnder Construction
AF1-204Eugene 345 kVActive
AF1-205Napoleon Muni 138 kVSuspended
AF1-206East Fayette 138 kVEngineering & Procurement
AF1-207Reynolds-Olive #1 345 kVEngineering & Procurement
AF1-215Olive-Reynolds 345 kVIn Service
AF1-223Keystone-Desoto 345 kVUnder Construction
AF1-227Marysville – Gunn Road 345 kVIn Service
AF1-228Beatty-Greene 345 kVEngineering & Procurement
AF1-229Galion-South Berwick 345 kVEngineering & Procurement
AF1-233Flemingsburg – Spurlock 138kVActive
AF1-249Nickel 12.47 kVIn Service
AF1-254Milnor-Huyetts 34.5 kVUnder Construction
AF1-262Upper Pittsgrove 12 kVIn Service
AF1-264Runnemede 13 kVIn Service
AF1-268Desoto-Jay 138 kVEngineering & Procurement
AF1-272Lucerne 115 kVEngineering & Procurement
AF1-275Cole 345 kVEngineering & Procurement
AF1-282Stuart-Clinton 345 kVEngineering & Procurement
AF1-283Stuart-Clinton 345 kVEngineering & Procurement
AF1-285Gunn Road 345 kVUnder Construction
AF1-290Feagans Mill-Millville 138 kVIn Service
AF1-291ABartonsville-Meadow Brook 138 kVIn Service
AF1-296Garden Plain 138 kVActive
AF1-299Otter Point 34.5 kV IIn Service
AF1-300Otter Point 34.5 kV IIIn Service
AF1-302Brookville-Squab Hollow 138 kVEngineering & Procurement
AF1-320Merrill Creek 115 kVEngineering & Procurement
AF1-322Meadow Lake 345 kVEngineering & Procurement
AF1-331Twombley RoadEngineering & Procurement
AF2-008Sullivan 345 kVActive
AF2-014Maddox Creek 345 kVEngineering & Procurement
AF2-018Inez 138 kVEngineering & Procurement
AF2-039Shawville-Clearfield 34.5 kVEngineering & Procurement
AF2-041Nelson-Electric Junction 345 kVActive
AF2-068Jay 138 kVActive
AF2-069Crescent Ridge 138 kVActive
AF2-075Bartonsville-Meadow Brook 138 kV IIIIn Service
AF2-078Reynolds-Olive #1 345 kVEngineering & Procurement
AF2-083Kenzie Creek-Stone Lake 69 kVUnder Construction
AF2-088Shawville-Clearfield 34.5 kV IIEngineering & Procurement
AF2-095Davis Creek 138 kVActive
AF2-111North Clark-Spurlock 345 kVActive
AF2-122Kirk 138 kVUnder Construction
AF2-126Weston 69 kV IIActive
AF2-130Cobalt Corners 34.5 kVIn Service
AF2-132Reynolds-Olive #1 345 kVUnder Construction
AF2-133Reynolds-Olive #2 345 kVUnder Construction
AF2-134Olive-Reynolds #2 345 kVIn Service
AF2-138Flanders-West Wharton 34.5 kVIn Service
AF2-139Gilbert-Warren Glen 34.5 kVIn Service
AF2-142Nevada 345 kVActive
AF2-143Powerton-Nevada 345 kVActive
AF2-173Desoto 345 kVActive
AF2-177Sorenson-DeSoto #2 345 kVActive
AF2-192Frenchtown Solar-West Flemington 34.5 kVSuspended
AF2-199Nelson-Electric Junction 345 kVActive
AF2-200Nelson-Electric Junction 345 kVActive
AF2-205Olive-Reynolds #2 345 kVEngineering & Procurement
AF2-224Allen 345 kVEngineering & Procurement
AF2-225McLean 345 kVActive
AF2-229Roxbury 23 kVEngineering & Procurement
AF2-235Titusville-Oil Creek 34.5 kVWithdrawn
AF2-247Bustleton 13.2 kVIn Service
AF2-250Edgewood 12 kV IIIIn Service
AF2-252Blue Mound 345 kVEngineering & Procurement
AF2-291Sporn South-Leon 138 kVEngineering & Procurement
AF2-298Crown-New Lebanon 69 kVEngineering & Procurement
AF2-307Hope-Belvins Valley Tap 69 kVActive
AF2-325Jacktown 12 kVEngineering & Procurement
AF2-335Delaware-Royerton 138 kVActive
AF2-350Kensington 138 kVActive
AF2-352Blue Mound 345 kVEngineering & Procurement
AF2-354Washington 34.5 kV IIEngineering & Procurement
AF2-356Albright-Mt. Zion 138 kVUnder Construction
AF2-359Olive-University Park 345 kVEngineering & Procurement
AF2-375Ebersole-Fostoria 138 kVEngineering & Procurement
AF2-378Cambridge 12 kVEngineering & Procurement
AF2-379Princess Anne 25 kVUnder Construction
AF2-383Tolna 115 kVWithdrawn
AF2-388Keystone-Desoto 345 kVActive
AF2-392Nelson-Dixon 138 kVActive
AF2-396Stinger 138 kVActive
AG1-024Centerburg 138 kVEngineering & Procurement
AG1-034Centerburg 138 kVEngineering & Procurement
AG1-040Morgan Street-Mount Hope 34.5 kVEngineering & Procurement
AG1-047Jay 138 kVEngineering & Procurement
AG1-054Potter-Harlan 69 kVEngineering & Procurement
AG1-100Venango-Saegertown 34.5 kVEngineering & Procurement
AG1-107Hillsboro-Middleboro 138 kVEngineering & Procurement
AG1-109Valley 138 kVActive
AG1-118Sugar Grove-Waterman 138kVActive
AG1-125Marysville-Flatlick 765 kVEngineering & Procurement
AG1-126Marysville-Flatlick 765 kVEngineering & Procurement
AG1-127Crego Rd 138 kVActive
AG1-188Manitou-Oyster Creek 34.5 kVEngineering & Procurement
AG1-189Oyster Creek-Bamber Lake 34.5Engineering & Procurement
AG1-191Chester-Pohatcong Mountain 34.5 kVPartially in Service - Under Construction
AG1-193Utica Junction 34.5 kVSuspended
AG1-197Morgan Street-Cochranton 34.5 kVSuspended
AG1-198Union City 34.5 kVUnder Construction
AG1-223Larrabee-Allaire 34.5 kVUnder Construction
AG1-226Dequine-Eugene 345 kVActive
AG1-232Magley 138 kVEngineering & Procurement
AG1-236Lanesville-Brokaw 345 kVActive
AG1-237Dequine-Eugene 345 kVEngineering & Procurement
AG1-254Salem-Woodstown 69 kVEngineering & Procurement
AG1-281Claysburg-HCR Tap 46 kVEngineering & Procurement
AG1-301Miller REC-Warrior Ridge 46 kVEngineering & Procurement
AG1-302Olive-Reynolds #1 345 kVUnder Construction
AG1-323Blue Jacket 138 kVActive
AG1-324Jay-Desoto 138 kVEngineering & Procurement
AG1-348Pequest River-Washington 34.5 kVIn Service
AG1-349Olive-Reynolds #2 345 kVEngineering & Procurement
AG1-363Black Oak-Hatfield 500 kVEngineering & Procurement
AG1-365Allen 345 kVEngineering & Procurement
AG1-366Allen 345 kVEngineering & Procurement
AG1-367DeSoto 345 kVActive
AG1-368Tillman 138 kVEngineering & Procurement
AG1-369Logtown 138 kVEngineering & Procurement
AG1-374Blue Mound 345 kVActive
AG1-375Sorenson-Desoto 345 kVActive
AG1-386Smith-Francis Junction 25 kVIn Service
AG1-397Walston 12 kVWithdrawn
AG1-410Maddox Creek-RP Mone 345 kVActive
AG1-433Keystone-DeSoto 345 kVActive
AG1-436Olive-University Park 345 kVActive
AG1-447Olive-University Park 345 kVActive
AG1-460Kincaid-Pana 345 kVActive
AG1-462Cordova 345 kVActive
AG1-478Wilmington 34.5 kVEngineering & Procurement
AG1-480Shawnee 34.5 kVEngineering & Procurement
AG1-482Hamilton 115 kVWithdrawn
AG1-495Gilbert-Rocktown 34.5 kVEngineering & Procurement
AG1-499Lambs 12.47 kVUnder Construction
AG1-555Dequine 345 kVEngineering & Procurement
AG2-029Forest G. Hipple-Collingwood 345 kVActive
AG2-057Cardington-Liberty 69 kV IIActive
AG2-063North Hampton 69 kVActive
AG2-072Rockport 765 kVActive
AG2-081Mt. Sterling-Fogg Pike 69 kVActive
AG2-085Delaware-Royerton 138 kVActive
AG2-104Marysville-Flatlick 765 kVActive
AG2-106Marysville-Flatlick 765 kVActive
AG2-107Marysville-Flatlick 765 kVActive
AG2-114Dresden-Pontiac Midpoint 345 kVActive
AG2-119Galion-Roberts South 138 kV IIActive
AG2-125Camden-Crystal 69 kVActive
AG2-126Eugene 345 kVActive
AG2-149Galion-South Berwick 345 kVActive
AG2-159Williamstown 69 kVActive
AG2-162Jefferson-Greentown 765 kVActive
AG2-163Dequine-Eugene 345 kVActive
AG2-164Jefferson-Greentown 765 kVActive
AG2-165Dumont-Greentown 765 kVActive
AG2-191Mississinewa 138 kVActive
AG2-192Mississinewa 138 kVActive
AG2-212Dumont-Greentown 765 kVActive
AG2-216East Sidney-Quincy 138 kVActive
AG2-219Jefferson-Greentown 765 kVActive
AG2-230Dumont 345 kVActive
AG2-245Olive - Reynolds #1 345 kVActive
AG2-328Dumont - Greentown 765 kVActive
AG2-329S Berwick - Galion 345 kVActive
AG2-330Dumont - Greentown 765 kVActive
AG2-331Jefferson-Greentown 765 kVActive
AG2-332East Elkhart – Elcona Tap 138 kVActive
AG2-363Powerton 345 kVActive
AG2-364Powerton 345 kVActive
AG2-378North Hampton – Medway 69 kVActive
AG2-385North Hampton 69 kVActive
AG2-400Allen 345 kVActive
AG2-401Losantville 345 kVActive
AG2-402Allen 345 kVActive
AG2-405Continental 69 kVActive
AG2-406Payne 69 kVActive
AG2-408Allen 345 kVActive
AG2-444Bixby - Biers Run 345 kVActive
AG2-449Jefferson-Greentown 765 kVActive
AG2-453Lasalle - Plano 345 kVActive
AG2-487Madison - Tanners Creek 138 kVActive
AG2-491Meadow Lake 345 kVActive
AG2-515Midway 345 kV IIIActive
AG2-516Pecatonica 138kVActive
AG2-519Royerton - Desoto 138 kVActive
AG2-524LaSalle Station - Mazon 138 kVActive
AG2-548Corwin - Elk 138 kVActive
AG2-550Bluff Point - Randolph 138 kVActive
AG2-551Bluff Point - Randolph 138 kVActive
AG2-564Sulphur Springs 138 kVActive
AG2-575Crego Rd. 138 kVActive
AG2-582Flint Run 500 kVActive
AG2-585Kensington 138kVActive
AG2-589Ravenswood - Hemlock 69 kVActive
AG2-637Randolph - Hodgin 138 kVActive
AG2-660Nelson-Electric Junction 345 kVActive
AG2-665Corwin - Elk 138 kVActive
AH1-004Avon - Renaker 138 kVActive
AH1-044Nelson - Electric Junction 345 kVActive
AH1-047Marengo - Belvidere 138 kVActive
AH1-055Kyger Creek - Don Marquis 345 kVActive
AH1-059Sharp Road 69 kVActive
AH1-060Cardington-Liberty 69 kV IIIActive
AH1-075North Waldo - Wild Creek 138 kVActive
AH1-146White Rock - Wayne 345 kVActive
AH1-147White Rock - Wayne 345 kVActive
AH1-150Nelson-Electric Junction 345 kVActive
AH1-151Nelson-Electric Junction 345 kVActive
AH1-153Dumont 345 kVActive
AH1-196Prairie 345 kVActive
AH1-234Wempletown - Paddock 345 kVActive
AH1-272Argenta - Twin Branch 345 kVActive
AH1-282Galion - Ohio Central 345 kVActive
AH1-285Sandwich 138 kVActive
AH1-292Sullivan 345 kVActive
AH1-298Meridian 345 kVActive
AH1-302Olive - Reynolds 345 kVActive
AH1-304Delaware-Van Buren 138 kVActive
AH1-305Olive - Reynolds 345 kVActive
AH1-306Mississinewa-Gaston 138 kVActive
AH1-308Pennville - Adams 138 kVActive
AH1-309Kenzie Creek-Colby 138 kVActive
AH1-328Blue Jacket - Kirby 138 kVActive
AH1-337Randolph - Hodgin 138 kVActive
AH1-338McGirr Rd - Ritchie Road 138kVActive
AH1-339West Crawford 69 kVActive
AH1-341Stillman - Dixon 138KVActive
AH1-391Olive 138 kVActive
AH1-392Gravel Pit-Kankakee 138 kVActive
AH1-482Olive - Reynolds #2 345 kVActive
AH1-537Pierce - Kyger Creek 345 kVActive
AH1-539South Kenton 138 kVActive
AH1-541Chestnut 345 kVActive
AH1-542Crissinger-Kirby 138kVActive
AH1-543Mulberry – Tazewell 345 kVActive
AH1-567University Park 138 kVActive
AH1-570Headquarters - Millersburg Junction 69 kVActive
AH1-571Headquarters - Millersburg Junction 69 kVActive
AH1-661Cannelville 12.47 kVActive
AH1-664Goddard-Plumville 138 kVActive
AH1-665Goddard-Plumsville 138 kV IIActive
AH1-666Flemingsburg - Spurlock 138 kVActive
AH1-669Circleville-Biers Run 138 kVActive
AH1-670Blue Mound-Chestnut 345 kVActive
AH1-686Hanging Rock 765 kVActive
AH1-690Bay Shore - Lallendorf 345 kVActive
AH1-698Braidwood 345 kVActive
AH1-702Byron 345 kVActive
AH1-704Hannibal 138 kVActive
AH1-711Lemoyne 345 kVActive
AH1-714Lasalle 345 kVActive
AH1-718Nelson 345 kVActive
AH1-719Beverly 345 kVActive
AH1-735Richland 138 kVActive
U2-030Four Mile Ridge Wind 138kVIn Service
U2-072East Lima-Marysville 345kVIn Service
U2-073Frostburg 138kV IIIn Service
V1-011Haviland 138kVIn Service
V3-007Desoto-Tanners Creek #1 345kVIn Service
V4-067Cates Road Egg Harbor Township 12kVDeactivated
W1-003Oak HallIn Service
W1-004Oak HallIn Service
W1-005Oak HallIn Service
W1-006Oak HallIn Service
W1-056Ada-Dunkirk 69kVIn Service
W1-130Vine Road 12kVIn Service
W2-030Egg Harbor TownshipIn Service
W2-048Brokaw-LanesvilleIn Service
W3-077Broadway-Stewartsville 34.5kVIn Service
W4-005Blue Mound-LathamIn Service
X1-042WatervlietIn Service
X2-022Brokaw-LanesvilleIn Service
X2-052Dumont-Olive 345kVIn Service
X3-005Wildwood 12kVIn Service
X3-066Church Hill 69kVIn Service
Y1-033Penn Mar-Rock Wood 115kVIn Service
Y1-079Wye Mills 69kVIn Service
Y1-080Dorchester 12kVIn Service
Y3-023Country Side 12kVIn Service
Y3-024Bluff Point 12kVIn Service
Y3-058Rockawalkin 69kVIn Service
Z2-076Worcester South 25kVIn Service
Z2-077Worcester North 25kVIn Service
Z2-087Pontiac MidPoint-Brokaw 345kVIn Service
Z2-115Deer Creek 12.47kVIn Service
Z2-116Twin Branch 12.47kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with potential Affected System impacts. PJM initiates coordination with each Affected System Operator by providing a list of New Service Requests in the Cycle with potential impacts to their respective system. If the Affected System Operator indicates an Affected System Study is required, PJM will notify the Project Developer or Eligible Customer of the need for an Affected System Study. See below if any Affected System Operator requires a study for this project:

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

No cost allocated system reinforcements were identified for this project in the Phase I System Impact Study load flow analysis.

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement: b4000.7
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.7
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line - in DVP local area/Millville to Lovettsville section, roughly 10.5 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-327 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-327 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)

System Reinforcement: b4000.10
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.10
Title
Install four 250 MVAR cap banks (two on 765 and two on 500 kV side) and a +/-500 MVAR STATCOM on the 765 kV Rocky Point yard
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-327 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-327 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)

System Reinforcement: b4000.6
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.6
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (Welton Spring to DVP local area, roughly 21 miles) (VA Portion)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-327 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-327 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)

System Reinforcement: b4000.3
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.3
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - APS/FE Section of the line is 145 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-327 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-327 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)

System Reinforcement: b4000.9
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.9
Title
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard (Projected ISD 6/1/2029)
Description
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard. Loop in the Doubs-Goose Creek 500 kV line, the Doubs-Aspen 500 kV line, and the Woodside-Goose Creek 500 kV line. Install two 765/500 kV transformer at Rocky Point substation. 765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-327 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-327 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)

System Reinforcement: b4000.5
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.5
Title
Install four 250 MVAR shunt capacitors, and a +/-500 MVAR STATCOM at Welton Spring 765 kV substation
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-327 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-327 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)

System Reinforcement: b4000.2
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.2
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - AEP Section of the line is 30 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-327 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-327 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)

System Reinforcement: b4000.8
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.8
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (DVP local area to Rocky Point, roughly 4.8 miles)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-327 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-327 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.a
Title
Upgrade (4) 1024.5 ACAR 24/13 sub conductors at Davis Besse
Description
Upgrade (4) 1024.5 ACAR 24/13 sub conductors at Davis Besse
Total Cost ($USD)
$1,099,401
Allocated Cost ($USD)
$0
Time Estimate
14 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-327 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-327 could receive cost allocation. Although AH1-327 may not presently have cost responsibility for this upgrade, AH1-327 is a potential Aggregate Pool Contributor.

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.g
Title
Upgrade (2) 345kV circuit breakers at Bayshore and (2) at Davis Besse
Description
Upgrade (2) 345kV circuit breakers at Bayshore and (2) at Davis Besse
Total Cost ($USD)
$7,786,806
Allocated Cost ($USD)
$0
Time Estimate
60 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-327 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-327 could receive cost allocation. Although AH1-327 may not presently have cost responsibility for this upgrade, AH1-327 is a potential Aggregate Pool Contributor.

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.j
Title
Upgrade (1) 1590 ACSR 45/7 sub conductor at Davis Besse
Description
Upgrade (1) 1590 ACSR 45/7 sub conductor at Davis Besse
Total Cost ($USD)
$393,871
Allocated Cost ($USD)
$0
Time Estimate
13 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-327 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-327 could receive cost allocation. Although AH1-327 may not presently have cost responsibility for this upgrade, AH1-327 is a potential Aggregate Pool Contributor.

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.h
Title
Upgrade (8) 1590 AAC 61 sub conductor at BAYSHORE
Description
Upgrade (8) 1590 AAC 61 sub conductor at BAYSHORE
Total Cost ($USD)
$211,119
Allocated Cost ($USD)
$0
Time Estimate
13 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-327 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-327 could receive cost allocation. Although AH1-327 may not presently have cost responsibility for this upgrade, AH1-327 is a potential Aggregate Pool Contributor.

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.i
Title
Upgrade B34544 CT at BAYSHORE
Description
Upgrade B34544 CT at BAYSHORE
Total Cost ($USD)
$712,356
Allocated Cost ($USD)
$0
Time Estimate
20 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-327 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-327 could receive cost allocation. Although AH1-327 may not presently have cost responsibility for this upgrade, AH1-327 is a potential Aggregate Pool Contributor.

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.c
Title
Upgrade 345kV 1033.5 AAC 61 sub conductors at Davis Besse substation at Davis Besse
Description
Upgrade 345kV 1033.5 AAC 61 sub conductors at Davis Besse substation at Davis Besse
Total Cost ($USD)
$257,762
Allocated Cost ($USD)
$0
Time Estimate
13 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-327 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-327 could receive cost allocation. Although AH1-327 may not presently have cost responsibility for this upgrade, AH1-327 is a potential Aggregate Pool Contributor.

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.k
Title
Upgrade the B34545 and 34562 (4) Meter and (2) Relay Thermals at Bayshore and Davis Besse
Description
Upgrade the B34545 and 34562 (4) Meter and (2) Relay Thermals at Bayshore and Davis Besse
Total Cost ($USD)
$998,835
Allocated Cost ($USD)
$0
Time Estimate
19 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-327 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-327 could receive cost allocation. Although AH1-327 may not presently have cost responsibility for this upgrade, AH1-327 is a potential Aggregate Pool Contributor.

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.d
Title
Reconductor (possible rebuild) 345kV 20.75 miles of transmission line and line drops at both remote ends
Description
Reconductor (possible rebuild) 345kV 20.75 miles of transmission line and line drops at both remote ends using dual (2) 1590 54/19 "Falcon" ACSS
Total Cost ($USD)
$121,594,776
Allocated Cost ($USD)
$0
Time Estimate
71 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-327 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-327 could receive cost allocation. Although AH1-327 may not presently have cost responsibility for this upgrade, AH1-327 is a potential Aggregate Pool Contributor.

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.f
Title
Upgrade (2) 345kV Wave Traps at Bayshore and (2) at Davis Besse
Description
Upgrade (2) 345kV Wave Traps at Bayshore and (2) at Davis Besse
Total Cost ($USD)
$1,215,694
Allocated Cost ($USD)
$0
Time Estimate
22 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-327 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-327 could receive cost allocation. Although AH1-327 may not presently have cost responsibility for this upgrade, AH1-327 is a potential Aggregate Pool Contributor.

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.b
Title
Upgrade (3) 345kV bus and line side disconnect switches at Davis Besse substation at Davis Besse
Description
Upgrade (3) 345kV bus and line side disconnect switches at Davis Besse substation at Davis Besse
Total Cost ($USD)
$1,324,127
Allocated Cost ($USD)
$0
Time Estimate
37 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-327 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-327 could receive cost allocation. Although AH1-327 may not presently have cost responsibility for this upgrade, AH1-327 is a potential Aggregate Pool Contributor.

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.e
Title
Upgrade 345kV 3500 SAC 127 sub conductor at Davis Besse
Description
Upgrade 345kV 3500 SAC 127 sub conductor at Davis Besse
Total Cost ($USD)
$257,762
Allocated Cost ($USD)
$0
Time Estimate
13 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-327 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-327 could receive cost allocation. Although AH1-327 may not presently have cost responsibility for this upgrade, AH1-327 is a potential Aggregate Pool Contributor.

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-014.j
Title
Upgrade the B88 and B3 impedance relays at Beaver and Hayes
Description
Upgrade the B88 and B3 impedance relays at Beaver and Hayes
Total Cost ($USD)
$1,019,790
Allocated Cost ($USD)
$0
Time Estimate
19 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-327 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-327 could receive cost allocation. Although AH1-327 may not presently have cost responsibility for this upgrade, AH1-327 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-014.b
Title
Upgrade 3500 SAC (2) B3 and (2) B6 breaker leads at Hayes
Description
Upgrade 3500 SAC (2) B3 and (2) B6 breaker leads at Hayes
Total Cost ($USD)
$152,573
Allocated Cost ($USD)
$0
Time Estimate
18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-327 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-327 could receive cost allocation. Although AH1-327 may not presently have cost responsibility for this upgrade, AH1-327 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-014.e
Title
Upgrade the 1590 AAC (2) B88 and (2) B15 breaker leads at Beaver
Description
Upgrade the 1590 AAC (2) B88 and (2) B15 breaker leads at Beaver
Total Cost ($USD)
$152,573
Allocated Cost ($USD)
$0
Time Estimate
18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-327 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-327 could receive cost allocation. Although AH1-327 may not presently have cost responsibility for this upgrade, AH1-327 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-014.d
Title
Upgrade (4) circuit breakers at Beaver and Hayes (B88, B115, B3, B6)
Description
Upgrade (4) circuit breakers at Beaver and Hayes (B88, B115, B3, B6)
Total Cost ($USD)
$7,937,520
Allocated Cost ($USD)
$0
Time Estimate
60 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-327 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-327 could receive cost allocation. Although AH1-327 may not presently have cost responsibility for this upgrade, AH1-327 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-014.f
Title
Upgrade the B6 CT at Hayes
Description
Upgrade the B6 CT at Hayes
Total Cost ($USD)
$727,300
Allocated Cost ($USD)
$0
Time Estimate
20 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-327 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-327 could receive cost allocation. Although AH1-327 may not presently have cost responsibility for this upgrade, AH1-327 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-014.g
Title
Upgrade (3) 1590 AAC line drops at Beaver (line drop to WT, Phase 1&3 "B-B", and SHARED NODE TO: WT, PH 2 / 5" AL, PH 1&3)
Description
Upgrade (3) 1590 AAC line drops at Beaver (line drop to WT, Phase 1&3 "B-B", and SHARED NODE TO: WT, PH 2 / 5" AL, PH 1&3) using dual (2) 954 54/7 "Cardinal" ACSS
Total Cost ($USD)
$591,863
Allocated Cost ($USD)
$0
Time Estimate
18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-327 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-327 could receive cost allocation. Although AH1-327 may not presently have cost responsibility for this upgrade, AH1-327 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-014.i
Title
Upgrade the 10A B115 relay and B88 meter thermal at Beaver
Description
Upgrade the 10A B115 relay and B88 meter thermal at Beaver
Total Cost ($USD)
$509,895
Allocated Cost ($USD)
$0
Time Estimate
18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-327 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-327 could receive cost allocation. Although AH1-327 may not presently have cost responsibility for this upgrade, AH1-327 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-014.a
Title
Reconductor (possible rebuild) 29.61 miles of transmission line and line drops ( line drops at Hayes) on the Beaver - Hayes Ckt 1 345 kV line
Description
Reconductor (possible rebuild) 29.61 miles of transmission line and line drops ( line drops at Hayes) on the Beaver - Hayes Ckt 1 345 kV line using dual (2) 954 54/7 "Cardinal" ACSS
Total Cost ($USD)
$175,902,477
Allocated Cost ($USD)
$0
Time Estimate
90 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-327 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-327 could receive cost allocation. Although AH1-327 may not presently have cost responsibility for this upgrade, AH1-327 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-014.h
Title
Upgrade the B88 and B115 CTs at Beaver
Description
Upgrade the B88 and B115 CTs at Beaver
Total Cost ($USD)
$1,258,596
Allocated Cost ($USD)
$0
Time Estimate
21 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-327 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-327 could receive cost allocation. Although AH1-327 may not presently have cost responsibility for this upgrade, AH1-327 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-014.c
Title
Upgrade (2) L3000 wavetraps at Beaver and Hayes
Description
Upgrade (2) L3000 wavetraps at Beaver and Hayes
Total Cost ($USD)
$729,124
Allocated Cost ($USD)
$0
Time Estimate
18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-327 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-327 could receive cost allocation. Although AH1-327 may not presently have cost responsibility for this upgrade, AH1-327 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-020.a
Title
Upgrade B185 and B182 circuit breakers at Beaver
Description
Upgrade B185 and B182 circuit breakers at Beaver
Total Cost ($USD)
$3,893,404
Allocated Cost ($USD)
$0
Time Estimate
56 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-327 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-327 could receive cost allocation. Although AH1-327 may not presently have cost responsibility for this upgrade, AH1-327 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-020.d
Title
Reconductor (possible rebuild) 29.61 miles of transmission line and (4) line drops beginning at Beaver towards Davis Besse on the Beaver - Davis Besse Ckt 1 345 kV line
Description
Reconductor (possible rebuild) 29.61 miles of transmission line and (4) line drops beginning at Beaver towards Davis Besse on the Beaver - Davis Besse Ckt 1 345 kV line using dual (2) 1590 54/19 "Falcon" ACSS
Total Cost ($USD)
$149,403,319
Allocated Cost ($USD)
$0
Time Estimate
82 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-327 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-327 could receive cost allocation. Although AH1-327 may not presently have cost responsibility for this upgrade, AH1-327 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-020.c
Title
Upgrade 3000 AAC B185 and B185 breaker leads at Beaver
Description
Upgrade 3000 AAC B185 and B185 breaker leads at Beaver
Total Cost ($USD)
$187,449
Allocated Cost ($USD)
$0
Time Estimate
13 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-327 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-327 could receive cost allocation. Although AH1-327 may not presently have cost responsibility for this upgrade, AH1-327 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-020.b
Title
Upgrade (4) disconnect switches at Beaver (D186,184,181,183)
Description
Upgrade (4) disconnect switches at Beaver (D186,184,181,183)
Total Cost ($USD)
$1,699,640
Allocated Cost ($USD)
$0
Time Estimate
25 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-327 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-327 could receive cost allocation. Although AH1-327 may not presently have cost responsibility for this upgrade, AH1-327 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-020.e
Title
Upgrade (2) L3000 wavetraps at Beaver
Description
Upgrade (2) L3000 wavetraps at Beaver
Total Cost ($USD)
$620,600
Allocated Cost ($USD)
$0
Time Estimate
18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-327 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-327 could receive cost allocation. Although AH1-327 may not presently have cost responsibility for this upgrade, AH1-327 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-006.i
Title
Upgrade (2) 9.6 Ohms impedance relays at Hayes and (2) 12.9 Ohms impedance relays at Davis Besse
Description
Upgrade (2) 9.6 Ohms impedance relays at Hayes and (2) 12.9 Ohms impedance relays at Davis Besse
Total Cost ($USD)
$1,019,790
Allocated Cost ($USD)
$0
Time Estimate
19 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-327 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-327 could receive cost allocation. Although AH1-327 may not presently have cost responsibility for this upgrade, AH1-327 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-006.h
Title
Upgrade B66 (1) meter and (1) relay thermals and B67 (1) meter thermal at Davis Besse substation
Description
Upgrade B66 (1) meter and (1) relay thermals and B67 (1) meter thermal at Davis Besse substation
Total Cost ($USD)
$852,462
Allocated Cost ($USD)
$0
Time Estimate
19 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-327 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-327 could receive cost allocation. Although AH1-327 may not presently have cost responsibility for this upgrade, AH1-327 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-006.c
Title
Upgrade (2) Wave Traps at Davis Besse and (2) Wave Traps at Hayes
Description
Upgrade (2) Wave Traps at Davis Besse and (2) Wave Traps at Hayes
Total Cost ($USD)
$1,215,695
Allocated Cost ($USD)
$0
Time Estimate
20 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-327 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-327 could receive cost allocation. Although AH1-327 may not presently have cost responsibility for this upgrade, AH1-327 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-006.e
Title
Upgrade (2) B12 and B18 CTs at Hayes
Description
Upgrade (2) B12 and B18 CTs at Hayes
Total Cost ($USD)
$1,258,596
Allocated Cost ($USD)
$0
Time Estimate
21 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-327 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-327 could receive cost allocation. Although AH1-327 may not presently have cost responsibility for this upgrade, AH1-327 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-006.g
Title
Upgrade B66 and B67 circuit breakers at Davis Besse substation
Description
Upgrade B66 and B67 circuit breakers at Davis Besse substation
Total Cost ($USD)
$3,893,404
Allocated Cost ($USD)
$0
Time Estimate
56 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-327 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-327 could receive cost allocation. Although AH1-327 may not presently have cost responsibility for this upgrade, AH1-327 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-006.a
Title
Reconductor (possible rebuild) 30.25 miles of 954 ACSR 48/7 transmission line and line drops (line drops at Davis Besse) on the Davis Besse-Hayes 345 kV line
Description
Reconductor (possible rebuild) 30.25 miles of 954 ACSR 48/7 transmission line and line drops (line drops at Davis Besse) on the Davis Besse-Hayes 345 kV line using dual (2) 1590 54/19 "Falcon" ACSS
Total Cost ($USD)
$179,916,169
Allocated Cost ($USD)
$0
Time Estimate
90 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-327 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-327 could receive cost allocation. Although AH1-327 may not presently have cost responsibility for this upgrade, AH1-327 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-006.f
Title
Upgrade (10) 1590 ACSR sub conductor (B66 and B67 breaker leads, wave trap subconductor, Overheadline-34625) at Davis Besse and B12 breaker leads at Hayes
Description
Upgrade (10) 1590 ACSR sub conductor (B66 and B67 breaker leads, wave trap subconductor, Overheadline-34625) at Davis Besse and B12 breaker leads at Hayes
Total Cost ($USD)
$305,149
Allocated Cost ($USD)
$0
Time Estimate
18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-327 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-327 could receive cost allocation. Although AH1-327 may not presently have cost responsibility for this upgrade, AH1-327 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-006.b
Title
Upgrade 3500 SAC 127 OVERHEAD PIPE to disc sw. 34625 at Davis Besse and B18 breaker leads at Hayes
Description
Upgrade 3500 SAC 127 OVERHEAD PIPE to disc sw. 34625 at Davis Besse and B18 breaker leads at Hayes
Total Cost ($USD)
$284,061
Allocated Cost ($USD)
$0
Time Estimate
18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-327 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-327 could receive cost allocation. Although AH1-327 may not presently have cost responsibility for this upgrade, AH1-327 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-006.d
Title
Upgrade (2) B18 & B12 345 kV Ciruit Breakers at Hayes
Description
Upgrade (2) B18 & B12 345 kV Ciruit Breakers at Hayes
Total Cost ($USD)
$3,893,404
Allocated Cost ($USD)
$0
Time Estimate
56 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-327 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-327 could receive cost allocation. Although AH1-327 may not presently have cost responsibility for this upgrade, AH1-327 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-006.j
Title
Upgrade (6) disconnect switches at Davis Besse (D27,28,29,30,34625,37) and (5) disconnect switches at Hayes (D20,19,16,13,14)
Description
Upgrade (6) disconnect switches at Davis Besse (D27,28,29,30,34625,37) and (5) disconnect switches at Hayes (D20,19,16,13,14)
Total Cost ($USD)
$4,525,814
Allocated Cost ($USD)
$0
Time Estimate
31 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-327 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-327 could receive cost allocation. Although AH1-327 may not presently have cost responsibility for this upgrade, AH1-327 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-015.b
Title
Upgrade (4) L300 wavetraps at Davis Besse and Lemoyne
Description
Upgrade (4) L300 wavetraps at Davis Besse and Lemoyne
Total Cost ($USD)
$1,132,675
Allocated Cost ($USD)
$0
Time Estimate
22 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-327 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-327 could receive cost allocation. Although AH1-327 may not presently have cost responsibility for this upgrade, AH1-327 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-02LEMOYN 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-015.a
Title
Reconductor (possible rebuild) 21.68 miles of transmission line and (1) line drop (line drop at Lemoyne) on the Davis Besse - Lemoyne 345 kV
Description
Reconductor (possible rebuild) 21.68 miles of transmission line and (1) line drop (line drop at Lemoyne) on the Davis Besse - Lemoyne 345 kV using dual (2) 1272 54/19 "Pheasant" ACSS
Total Cost ($USD)
$126,131,949
Allocated Cost ($USD)
$0
Time Estimate
73 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-327 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-327 could receive cost allocation. Although AH1-327 may not presently have cost responsibility for this upgrade, AH1-327 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-02LEMOYN 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-008.h
Title
Upgrade Circuit Breaker 34564 at Davis Besse
Description
Upgrade Circuit Breaker 34564 at Davis Besse
Total Cost ($USD)
$2,068,856
Allocated Cost ($USD)
$0
Time Estimate
54 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-327 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-327 could receive cost allocation. Although AH1-327 may not presently have cost responsibility for this upgrade, AH1-327 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-008.d
Title
Upgrade (2) 3500 SAC 127 line drops at Davis Besse
Description
Upgrade (2) 3500 SAC 127 line drops at Davis Besse
Total Cost ($USD)
$263,169
Allocated Cost ($USD)
$0
Time Estimate
12 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-327 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-327 could receive cost allocation. Although AH1-327 may not presently have cost responsibility for this upgrade, AH1-327 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-008.b
Title
Upgrade (1) 1024 ACAR 6E550-52-1 "A" line drop at Davis Besse
Description
Upgrade (1) 1024 ACAR 6E550-52-1 "A" line drop at Davis Besse
Total Cost ($USD)
$263,169
Allocated Cost ($USD)
$0
Time Estimate
12 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-327 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-327 could receive cost allocation. Although AH1-327 may not presently have cost responsibility for this upgrade, AH1-327 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-008.a
Title
Upgrade D41 and D42 disconnect switches at Davis Besse
Description
Upgrade D41 and D42 disconnect switches at Davis Besse
Total Cost ($USD)
$967,716
Allocated Cost ($USD)
$0
Time Estimate
36 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-327 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-327 could receive cost allocation. Although AH1-327 may not presently have cost responsibility for this upgrade, AH1-327 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-008.f
Title
Reconductor (possible rebuild) 18.7 miles of 954 ACSR 48/7 on the Davis Besse - AC2-103 TAP 345kV
Description
Reconductor (possible rebuild) 18.7 miles of 954 ACSR 48/7 on the Davis Besse - AC2-103 TAP 345kV using dual (2) 1272 54/19 "Pheasant" ACSS
Total Cost ($USD)
$111,822,087
Allocated Cost ($USD)
$0
Time Estimate
64 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-327 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-327 could receive cost allocation. Although AH1-327 may not presently have cost responsibility for this upgrade, AH1-327 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-008.g
Title
Upgrade (2) Wave Traps at Davis Besse
Description
Upgrade (2) Wave Traps at Davis Besse
Total Cost ($USD)
$620,599
Allocated Cost ($USD)
$0
Time Estimate
20 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-327 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-327 could receive cost allocation. Although AH1-327 may not presently have cost responsibility for this upgrade, AH1-327 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-008.e
Title
Upgrade 3500 SAC B65 breaker leads and subconductor (D42 to wave trap) at Davis Besse
Description
Upgrade 3500 SAC B65 breaker leads and subconductor (D42 to wave trap) at Davis Besse
Total Cost ($USD)
$197,592
Allocated Cost ($USD)
$0
Time Estimate
13 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-327 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-327 could receive cost allocation. Although AH1-327 may not presently have cost responsibility for this upgrade, AH1-327 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-008.c
Title
Reconductor (possible rebuild) 15.6 miles of 954 ACSR 45/7 on the Davis Besse - AC2-103 Tap 345 kV line
Description
Reconductor (possible rebuild) 15.6 miles of 954 ACSR 45/7 on the Davis Besse - AC2-103 Tap 345 kV line using dual (2) 1272 54/19 "Pheasant" ACSS
Total Cost ($USD)
$91,775,258
Allocated Cost ($USD)
$0
Time Estimate
57 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-327 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-327 could receive cost allocation. Although AH1-327 may not presently have cost responsibility for this upgrade, AH1-327 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.11
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.11
Title
Expand Black Oak Substation & Loop in the 502 Jct-Woodside 500 kV line (Projected ISD 6/1/2029)
Description
Expand Black Oak Substation to accommodate the connection of the 502 Jct-Woodside 500 kV line and loop the 502 Jct-Woodside 500 kV line into the Black Oak substation by constructing ~0.85 miles of new 500 kV line into and out of Black Oak 500 kV substation
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-327 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-327 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)

System Reinforcement: b4000.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.1
Title
Add two 765 kV breakers at Amos Substation to expand the breaker and a half scheme to accommodate the new Amos-Welton Spring 765 kV line (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-327 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-327 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18635
Title
05MARYSVL_RM 765.0 kV to 05MALIS 765.0 kV ckt 1 - Replace Equipment
Description
Replace wave tap at Maliszewski towards Marysville along with circuit breakers, disconnects, and Sub Conductor.
Total Cost ($USD)
$24,200,000
Allocated Cost ($USD)
$0
Time Estimate
24 to 36 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-327 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-327 could receive cost allocation. Although AH1-327 may not presently have cost responsibility for this upgrade, AH1-327 is a potential Aggregate Pool Contributor.

FacilityContingency
05MALIS-05MARYSVL_RM 765.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18653
Title
05MALIS 765.0 kV to 05VASSEL 765.0 kV ckt 1 - Replace Equipment
Description
Replace circuit breaker B, Disconnects, and reconductor between structures 432-453 to bring rating up to the sub conductor.
Total Cost ($USD)
$153,100,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-327 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-327 could receive cost allocation. Although AH1-327 may not presently have cost responsibility for this upgrade, AH1-327 is a potential Aggregate Pool Contributor.

FacilityContingency
05MALIS-05VASSEL 765.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18680
Title
05MARYSV 765.0 kV to 05MARYSVL_RM 765.0 kV ckt Z1 - Replace Equipment
Description
Replace wave trap and associated equipment on Marysville Reactor towards Maliszewski.
Total Cost ($USD)
$2,200,000
Allocated Cost ($USD)
$0
Time Estimate
24 to 36 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-327 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-327 could receive cost allocation. Although AH1-327 may not presently have cost responsibility for this upgrade, AH1-327 is a potential Aggregate Pool Contributor.

FacilityContingency
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line(Any)

System Reinforcement: b4000.4
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.4
Title
Construct a new 765 kV switchyard - Welton Spring (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-327 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-327 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)

Attachments

AH1-327 One Line Diagram

AH1-327 One Line Diagram.jpg
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.